AG2-369 Phase I Study Report

v1.00 released 2025-10-29 20:14

Heritage - Wake 500 kV

51.6 MW Capacity / 86.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Greensville County, Virginia. The installed facilities will have a total capability of 86.0 MW with 51.6 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-369
Project Name:
Heritage - Wake 500 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia
State:
Virginia
County:
Greensville
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
86.0
MWE:
86.0
MWC:
51.6
Fuel Type:
Solar
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Chesterfield 6Deactivated Generator51.6Yes

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-369 will interconnect on the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) transmission system by tapping the Heritage - Wake 500 kV Line and will share a new interconnection switchyard with AG2-068 and AG2-069.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-369 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-369Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$2,200,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$12,500,000$12,500,000
Network Upgrades$2,500,000$2,500,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$8,027,404$8,027,404
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$25,227,404$23,027,404

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-369

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-369 Project due at DP1
ABA - B
AG2-369$2,302,740$344,000$1,958,740

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install (2) Point of Change in Ownership (PCO) disconnect switches, (2) runs of overhead line conductor from the PCOs to the bus positions that serve as the Points of Interconnection (POIs), as well as any metering and associated protection equipment.$4,400,000 $2,200,000 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construct a new four breaker ring bus switching station on the Heritage - Wake 500 kV Line 570. This station will serve as the interconnection location for AG2-068, AG2-069, and AG2-369. Project AG2-069 will be sharing interconnection facilities with AG2-068. Project AG2-369 will have a separate POI and will not share interconnection facilities with AG2-068 or AG2-069.$25,000,000 $12,500,000 (See Note 1)
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Remove, modify, and/or install backbones, structures, conductors, and supporting equipment to re-arrange transmission line and tie-in substation. Install static poles and shield wiring for substation protection and install fiber cable for communication if needed.$5,000,000 $2,500,000 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 50 to 54 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Remote end work required on a Facility owned by a non-PJM Transmission Owner:

 

Please note that your project interconnects directly to a/an Dominion (Interconnected Transmission Owner) facility which shares a tie line with CPLE (non-PJM Transmission Owner). The Transmission Owner Scope of Work above outlines the physical interconnection upgrades required on the Dominion facilities. Your project will also require upgrades at the remote end CPLE facility.  It is your responsibility to engage with CPLE regarding the upgrade work required to accommodate this interconnection.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-369 was evaluated as a 86.0 MW (51.6 MW Capacity) injection in the Dominion area.

AG2-369 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 86.0 MW (86.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC203.13 %678.68B1378.63.79
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.6 %830.0C1540.54.99
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.6 %830.0C1540.494.99
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC173.49 %830.0C1439.974.48
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC173.49 %830.0C1439.974.48
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC130.0 %830.0C1079.043.95
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Base Case
SingleAC113.92 %678.68A773.162.63
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC113.5 %830.0C942.093.74
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC111.23 %830.0C923.193.46
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC110.89 %830.0C920.433.46
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC202.03 %678.68B1371.173.79
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC184.71 %830.0C1533.114.99
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC184.71 %830.0C1533.14.99
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC172.6 %830.0C1432.614.48
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC172.6 %830.0C1432.614.48
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P2-2: BREMO B3_SRT-A
BusAC129.14 %830.0C1071.93.95
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Base Case
SingleAC112.86 %678.68A765.972.63
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC112.65 %830.0C934.973.74
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P7-1: LN 2066-282_SRT-S
TowerAC110.36 %830.0C916.03.46
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P7-1: LN 219-282_SRT-A
TowerAC110.03 %830.0C913.263.46
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC177.07 %571.52B1012.013.74
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC130.37 %699.0C911.293.71
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC126.86 %699.0C886.733.61
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 249-69_SRT-A
TowerAC122.66 %699.0C857.383.54
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC118.39 %699.0C827.523.46
GD2DVP
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Base Case
SingleAC112.79 %571.52A644.612.6
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC154.83 %1204.0C1864.168.61
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.18 %984.18B1428.845.11
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC121.21 %984.18B1192.963.98
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC121.16 %1204.0C1458.726.48
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC121.16 %1204.0C1458.726.48
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC111.6 %1204.0C1343.655.72
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P4-5: L552_SRT-A
BreakerAC106.53 %1204.0C1282.595.32
GD2DVP
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
DVP_P7-1: LN 2002-2003_SRT-A
TowerAC102.5 %1204.0C1234.135.25
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC131.37 %830.0C1090.345.66
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P1-2: LN 249_SRT-A
SingleAC124.58 %678.68B845.483.15
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC116.29 %678.68B789.263.28
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P4-2: 24972-3_SRT-A
BreakerAC104.19 %830.0C864.764.15
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P7-1: LN 249-69_SRT-A
TowerAC104.16 %830.0C864.564.15
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P4-5: LOCKS H322_SRT-A
BreakerAC104.14 %830.0C864.384.15
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P4-6: T152_SRT-A
BreakerAC102.78 %830.0C853.094.15
GD2DVP
6CARSON-6POE 230.0 kV Ckt 1 line
DVP_P4-2: 205T249_SRT-S
BreakerAC102.01 %830.0C846.724.15
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC152.97 %1204.0C1841.88.61
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC142.99 %984.18B1407.245.11
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC119.38 %1204.0C1437.316.48
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC119.38 %1204.0C1437.316.48
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P1-2: LN 2002_SRT-A
SingleAC119.0 %984.18B1171.163.98
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC109.8 %1204.0C1322.035.72
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P4-5: L552_SRT-A
BreakerAC104.78 %1204.0C1261.55.32
GD2DVP
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
DVP_P7-1: LN 2002-2003_SRT-A
TowerAC100.75 %1204.0C1213.065.25
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC146.61 %1417.0B2077.464.53
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC146.6 %1417.0B2077.394.53
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC145.68 %1417.0B2064.294.5
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC140.29 %1417.0B1987.893.6
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC131.46 %1417.0B1862.724.25
GD2DVP/PEPCO
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
DVP_P7-1: LN 514-2098_SRT-S
TowerAC104.66 %1417.0B1482.993.57
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC114.83 %997.0C1144.98.55
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC108.64 %814.98B885.416.54
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC106.47 %814.98B867.676.54
GD2DVP
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-S
BreakerAC100.2 %997.0C998.978.61
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC167.04 %559.3B934.253.75
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC118.81 %684.0C812.653.72
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC115.25 %684.0C788.333.62
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P2-2: ALTAVISTA 115KV_SRT-A
BusAC113.26 %684.0C774.733.6
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 249-69_SRT-A
TowerAC110.96 %684.0C758.973.55
GD2DVP
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Base Case
SingleAC101.32 %559.3A566.672.61
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC196.14 %678.68B1331.143.55
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.57 %830.0C1515.374.67
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.57 %830.0C1515.344.67
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC175.31 %830.0C1455.084.2
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC175.31 %830.0C1455.084.2
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC119.33 %830.0C990.473.48
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC117.39 %830.0C974.313.46
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC112.5 %830.0C933.783.44
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC198.54 %661.76B1313.883.55
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC185.18 %809.0C1498.14.67
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC185.18 %809.0C1498.084.67
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC177.73 %809.0C1437.824.2
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC177.73 %809.0C1437.824.2
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC120.29 %809.0C973.173.48
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC118.3 %809.0C957.013.46
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC113.29 %809.0C916.483.44
GD2DVP
6LDYSMITH CT-6SUMMIT 230.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC135.94 %1809.0C2459.123.74
GD2DVP
6MINE RD-6FREDBRG 230.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC166.64 %1303.0C2171.283.74
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC195.13 %661.76B1291.313.55
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC182.39 %809.0C1475.574.67
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC182.39 %809.0C1475.544.67
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC174.94 %809.0C1415.274.2
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC174.94 %809.0C1415.274.2
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P7-1: LN 39-91_SRT-A-2
TowerAC117.53 %809.0C950.83.48
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P2-2: DOOMS B2_SRT-A
BusAC115.53 %809.0C934.633.46
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC110.52 %809.0C894.113.44
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC182.88 %508.54B930.037.9
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC178.67 %508.54B908.597.9
GD2DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC143.82 %541.0C778.074.35
GD2DVP
6POE-6TYLER1 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC130.12 %441.8B574.862.64
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.79 %997.0C1094.578.57
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC103.53 %814.98B843.756.55
GD2DVP
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC101.35 %814.98B825.976.55
GD2DVP
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC165.56 %1360.0C2251.633.74
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H2T560_SRT-A
BreakerAC117.42 %1809.0C2124.154.53
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: H1T560_SRT-A
BreakerAC117.42 %1809.0C2124.084.53
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
DVP_P4-2: 560T571_SRT-S
BreakerAC116.69 %1809.0C2110.994.5
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC112.48 %1809.0C2034.783.6
GD2DVP
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC105.55 %1809.0C1909.414.25
GD2DVP
6TYLER-6CHESTF B 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC100.46 %1204.0C1209.556.53
GD2DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 562T563_SRT-S
BreakerAC105.06 %1039.5C1092.077.55
GD2DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 56372_SRT-S
BreakerAC150.06 %1056.8C1585.799.7
GD2DVP
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
DVP_P4-2: 562T563_SRT-S
BreakerAC111.2 %1056.8C1175.188.09
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC139.66 %3220.44B4497.8315.06
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC139.23 %3940.0C5485.7121.25
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56272_SRT-S
BreakerAC131.96 %3118.0C4114.6519.6
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P1-2: LN 567_SRT-A
SingleAC130.02 %3220.44B4187.0815.34
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC128.65 %3940.0C5068.7519.91
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC128.38 %3940.0C5058.2719.8
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P4-2: 56722_SRT-A
BreakerAC126.96 %3940.0C5002.2420.9
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P2-2: BREMO B1_SRT-A
BusAC108.3 %3940.0C4267.1518.47
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC107.33 %3940.0C4228.6718.97
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC106.32 %3940.0C4188.8218.16
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Base Case
SingleAC105.09 %3220.44A3384.2813.41
GD2DVP
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC104.67 %3940.0C4124.0518.47
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: 545T594_SRT-S
BreakerAC122.59 %3966.0C4861.7310.14
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC113.53 %5010.0C5687.8212.47
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC113.37 %5010.0C5679.6312.44
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: 515T594_SRT-S
BreakerAC113.36 %5010.0C5679.3712.44
GD2DVP
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC111.05 %5010.0C5563.7612.49
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC146.98 %2442.12B3589.4511.46
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC145.46 %2442.12B3552.311.85
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC121.82 %3637.0C4430.4416.48
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC121.82 %3637.0C4430.4416.48
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC115.4 %3637.0C4196.9915.93
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC114.49 %3637.0C4164.0515.09
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC114.49 %3637.0C4164.0515.09
GD2DVP
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Base Case
SingleAC102.62 %2442.12A2506.27.98
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC149.23 %5011.0C7478.018.42
GD2DVP
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC149.23 %5011.0C7477.9618.42
GD2DVP
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC105.18 %4124.72B4338.4834.31
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC110.22 %5011.0C5523.2812.54
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: 57302_SRT-S
BreakerAC108.51 %5011.0C5437.6312.7
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: XT573_SRT-S
BreakerAC108.51 %5011.0C5437.512.7
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: 515T573_SRT-S
BreakerAC108.24 %5011.0C5423.6712.65
GD2DVP
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC107.86 %5011.0C5404.7712.59
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC119.2 %3940.0C4696.329.37
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: 545T594_SRT-S
BreakerAC115.13 %3940.0C4535.939.7
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H4T581_SRT-S
BreakerAC112.18 %3940.0C4419.99.16
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC112.16 %3940.0C4419.229.15
GD2DVP
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC112.08 %3940.0C4415.89.14
GD2DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P1-2: LN 576_SRT-S
SingleAC127.08 %1057.5B1343.95.89
GD2DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P4-2: WT576_SRT-S
BreakerAC122.5 %1265.1C1549.87.75
GD2DVP
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
DVP_P4-2: 57602_SRT-S
BreakerAC122.5 %1265.1C1549.87.75
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 574_SRT-S
SingleAC175.45 %3220.44B5650.1414.6
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H2T574_SRT-S
BreakerAC154.63 %3940.0C6092.4319.36
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 557T574_SRT-S
BreakerAC154.23 %3940.0C6076.820.16
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: H1T574_SRT-S
BreakerAC152.97 %3940.0C6027.1319.23
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC136.69 %3220.44B4402.0713.87
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC132.12 %3940.0C5205.617.44
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P4-1: G202_SRT-S
BreakerAC131.07 %3118.0C4086.8815.63
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC126.92 %3118.0C3957.4415.7
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC126.92 %3118.0C3957.4415.7
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Base Case
SingleAC113.34 %3193.18A3619.1311.92
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2090-256_SRT-S
TowerAC104.73 %3940.0C4126.1816.09
GD2DVP
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
DVP_P7-1: LN 2054-2135_SRT-A
TowerAC104.47 %3940.0C4115.9515.78
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 57302_SRT-S
BreakerAC161.07 %3118.0C5022.1611.91
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 594_SRT-S
SingleAC150.27 %3220.44B4839.458.53
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P1-2: LN 573_SRT-S
SingleAC147.45 %3220.44B4748.68.96
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: SPOTS H1T594_SRT-S
BreakerAC134.78 %3940.0C5310.4911.73
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T594_SRT-S
BreakerAC130.91 %3940.0C5157.7311.25
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: 515T594_SRT-S
BreakerAC130.47 %3940.0C5140.4611.23
GD2DVP
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
DVP_P4-2: H1T573_SRT-S
BreakerAC128.18 %3940.0C5050.2511.82
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC210.08 %3940.0C8277.0218.5
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC174.96 %3940.0C6893.415.77
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: 57502_SRT-S
BreakerAC169.18 %3118.0C5274.9912.9
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC150.52 %3940.0C5930.6513.73
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC148.0 %3940.0C5831.0413.54
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B2_SRT-S
BusAC128.28 %3118.0C3999.6610.41
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P2-2: NORTH ANNA B1_SRT-S
BusAC128.28 %3118.0C3999.6610.41
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Base Case
SingleAC118.49 %3193.18A3783.567.91
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-1
TowerAC118.03 %3940.0C4650.5810.78
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P7-1: LN 11-2199_SRT-A-2
TowerAC117.81 %3940.0C4641.5610.78
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019B_SRT-A
BreakerAC114.93 %3099.0B3561.838.69
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
AP_P2-3_PE-500-019F_SRT-SL
BreakerAC107.21 %3099.0B3322.427.29
GD2DVP/PJM
8POSSUM-BURCHES 500.0 kV Ckt 1 line
PEPCO_P4_PP41_SRT-A
BreakerAC103.72 %3099.0B3214.417.29
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-1
SingleAC139.73 %4070.2B5687.3327.65
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 585_SRT-A-2
SingleAC133.78 %4070.2B5445.2827.65
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 58572_SRT-A
BreakerAC124.04 %4996.0C6196.9536.4
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-5: W72_SRT-A
BreakerAC123.43 %4996.0C6166.5636.15
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: XT585_SRT-S
BreakerAC114.16 %4996.0C5703.6636.4
GD2DVP
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 54472_SRT-S
BreakerAC111.74 %2858.0C3193.4917.84
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC123.06 %4070.2B5008.6527.36
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC109.25 %4996.0C5458.0636.03
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC108.79 %4996.0C5435.0735.79
GD2DVP
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC107.19 %4996.0C5355.1935.49
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC103.87 %2931.0C3044.3714.68
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC101.05 %2931.0C2961.8614.1
GD2DVP
8SEPTA-8SURRY 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC101.05 %2931.0C2961.8614.1
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 568T581_SRT-S
BreakerAC211.93 %3940.0C8350.2117.92
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC182.6 %3118.0C5693.4313.21
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 574T575_SRT-S
BreakerAC179.37 %3940.0C7067.1415.26
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC154.28 %3940.0C6078.7913.48
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC154.01 %3940.0C6067.8913.47
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P2-2: MORRISVILLE B1_SRT-S
BusAC140.84 %3118.0C4391.410.2
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Base Case
SingleAC129.41 %3220.44A4167.617.74
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P7-1: LN 2-2199_SRT-A-1
TowerAC124.66 %3940.0C4911.810.6
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P7-1: LN 2-2199_SRT-A-2
TowerAC124.41 %3940.0C4901.6110.6
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P2-2: GERMANNA_SRT-A
BusAC120.67 %3940.0C4754.2110.48
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC131.1 %2931.0C3842.6514.6
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC131.1 %2931.0C3842.6514.6
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC131.01 %2931.0C3840.0514.74
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC126.47 %2442.12B3088.5210.79
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: 57602_SRT-S
BreakerAC116.99 %2931.0C3428.9512.77
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P4-2: WT576_SRT-S
BreakerAC116.99 %2931.0C3428.9312.77
GD2DVP
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
DVP_P1-2: LN 576_SRT-S
SingleAC115.66 %2442.12B2824.629.7
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC136.1 %4070.2B5539.4127.36
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC120.36 %4996.0C6013.1136.03
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC119.82 %4996.0C5986.2935.79
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC118.15 %4996.0C5902.935.49
GD2DVP
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
DVP_P1-2: LN 591_SRT-S
SingleAC107.48 %4070.2B4374.4532.94
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC176.17 %559.3B985.353.75
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC128.06 %684.0C875.953.72
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC124.48 %684.0C851.473.62
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
DVP_P7-1: LN 249-69_SRT-A
TowerAC120.19 %684.0C822.073.55
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC115.8 %684.0C792.063.47
GD2DVP
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Base Case
SingleAC110.37 %559.3A617.322.61
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P1-2: LN 511_SRT-S
SingleAC129.2 %4070.2B5258.7227.36
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51192_SRT-S
BreakerAC114.25 %4996.0C5708.1236.03
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 51172_SRT-S
BreakerAC113.76 %4996.0C5683.4435.79
GD2DVP
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
DVP_P4-2: 511T544_SRT-S
BreakerAC112.13 %4996.0C5601.835.49
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC181.65 %559.3B1015.963.75
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC133.94 %684.0C916.123.72
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC130.34 %684.0C891.543.62
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
DVP_P7-1: LN 249-69_SRT-A
TowerAC126.04 %684.0C862.133.55
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC121.65 %684.0C832.113.47
GD2DVP
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Base Case
SingleAC115.81 %559.3A647.72.61
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC183.2 %571.52B1047.03.74
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
BusAC137.05 %699.0C957.973.71
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 2003-205_SRT-S
TowerAC133.52 %699.0C933.313.61
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
DVP_P7-1: LN 249-69_SRT-A
TowerAC129.32 %699.0C903.973.54
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
BusAC125.05 %699.0C874.13.46
GD2DVP
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Base Case
SingleAC118.94 %571.52A679.772.6

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:203.13 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1378.6
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
NYPJM->LTFIMP_NY
CLTF
0.579
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
LGEELTFEXP_LGEE->PJM
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.5
MW Contribution:4.99
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1540.49
MW Contribution:4.99
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
NYPJM->LTFIMP_NY
CLTF
0.574
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:4.48
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
NYPJM->LTFIMP_NY
CLTF
0.536
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LGEELTFEXP_LGEE->PJM
CLTF
0.012
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:173.49 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1439.97
MW Contribution:4.48
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
NYPJM->LTFIMP_NY
CLTF
0.536
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
LGEELTFEXP_LGEE->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.0 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1079.04
MW Contribution:3.95
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
5.002
3144293JTRSVLE
50/50
0.78
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.861
316313AB2-026
Solar/Wind Harmer
0.85
316258AE1-075 C
Solar/Wind Harmer
0.765
316405AF2-144 C
Solar/Wind Harmer
0.807
3143336POWHATN
Solar/Wind Harmer
3.179
970909AG2-566 GEN
Solar/Wind Harmer
2.663
3147133PAMPLIN
Solar/Wind Harmer
-0.086
971193AH1-056 GEN
Solar/Wind Harmer
17.264
963181AG1-167 GEN
Solar/Wind Harmer
2.434
959311AF2-222 GEN
Solar/Wind Harmer
22.717
970257AG2-171 GEN
Solar/Wind Harmer
7.889
315785AD2-033 C
Solar/Wind Harmer
4.54
964241AG1-285 GEN
Solar/Wind Harmer
13.569
316131AB2-060 GEN
Solar/Wind Harmer
1.699
316478AD1-087 GEN
Solar/Wind Harmer
1.036
316486AD2-202 GEN
Solar/Wind Harmer
0.304
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.29
960061AF2-297 GEN
Solar/Wind Harmer
4.81
966621AG1-532 GEN
Solar/Wind Harmer
0.173
313506AB2-031 GEN
Solar/Wind Harmer
0.663
971683AH1-343 GEN
Solar/Wind Harmer
3.528
3150861SPRUNCD
Adder
0.323
970917AG2-570 GEN
Solar/Wind Harmer
18.441
316365GEN2_N
Solar/Wind Harmer
0.488
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.463
961681AG1-008 GEN
Solar/Wind Harmer
5.463
316210AC1-098 GEN
Solar/Wind Harmer
1.08
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
962331AG1-082 GEN
Solar/Wind Harmer
0.846
316317KELFORD C
Solar/Wind Harmer
0.319
3145823KELFORD
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.671
315724AD1-057 GEN
Solar/Wind Harmer
0.374
315839AE2-212 C
Solar/Wind Harmer
0.195
3145273HOLLAND
Solar/Wind Harmer
-0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
0.87
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.015
965281AG1-393 GEN
Solar/Wind Harmer
0.8
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
970659AG2-427 GEN
Solar/Wind Harmer
0.6
316083AB2-161 GEN
Solar/Wind Harmer
1.033
3146206CASHIE
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.599
970661AG2-428 GEN
Solar/Wind Harmer
1.194
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
315616AA1-038_C
Solar/Wind Helper
0.641
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
24.399
971845AH1-439 GEN
Solar/Wind Harmer
25.003
970285AG2-188 GEN
Solar/Wind Harmer
39.727
315657AE1-056 GEN
Solar/Wind Harmer
10.359
946301AF1-294 GEN
Solar/Wind Harmer
6.652
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
18.415
970681AG2-440 GEN
Solar/Wind Harmer
14.732
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.098
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316118AC1-105 GEN
Solar/Wind Harmer
0.743
316233AE1-074 FULL
Solar/Wind Harmer
0.277
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.097
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.191
971967AH1-528 GEN
Solar/Wind Harmer
15.717
316087AB2-174 GEN
Solar/Wind Harmer
1.189
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
315607AA1-063A GEN
Solar/Wind Harmer
0.769
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
15.733
970673AG2-436 GEN
Solar/Wind Harmer
7.966
970865AG2-541 GEN
Solar/Wind Harmer
3.042
941031AE2-094 GEN
Solar/Wind Harmer
13.777
944011AF1-069 GEN
Solar/Wind Harmer
4.317
970085AG2-068 GEN
Solar/Wind Harmer
4.591
970581AG2-369 GEN
Solar/Wind Harmer
3.948
965291AG1-394 GEN
Solar/Wind Harmer
0.631
315814AE2-033 C
Solar/Wind Harmer
6.526
316315AB2-025 C
Solar/Wind Harmer
0.189
315652AC1-086 GEN
Solar/Wind Harmer
7.864
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.356
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.783
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.142
3144293JTRSVLE
50/50
0.78
3144293JTRSVLE
50/50
0.657
970535AG2-341 GEN
50/50
2.128
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
14.025
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.056
963191AG1-168 GEN
Solar/Wind Harmer
2.434
971741AH1-377 GEN
Solar/Wind Harmer
29.148
316034AC1-036 C
Solar/Wind Harmer
0.391
970323AG2-213 GEN
Solar/Wind Harmer
10.518
971775AH1-396 GEN
Solar/Wind Harmer
1.498
313527AB2-043 GEN
Solar/Wind Harmer
2.495
962561AG1-105 GEN
Solar/Wind Harmer
7.049
939181AE1-148 GEN
Solar/Wind Harmer
6.984
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.568
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.91
3143526WINTERP
Solar/Wind Harmer
-0.053
970933AG2-581 GEN
Solar/Wind Harmer
8.884
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.893
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.779
972187AH1-678 GEN
Adder
1.94
972185AH1-677 GEN
Adder
3.777
316274AC1-208 GEN
Solar/Wind Harmer
0.758
3144356SAPONY
Solar/Wind Harmer
0.244
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.691
316222AC1-221 GEN
Solar/Wind Harmer
0.652
316240AF1-291 C
Solar/Wind Harmer
0.193
944641AF1-129 GEN
Adder
26.988
970657AG2-426 GEN
Solar/Wind Harmer
1.987
970657AG2-426 GEN
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
3.168
315821AE2-092 GEN
Solar/Wind Helper
6.532
966001AG1-469 GEN
Solar/Wind Helper
0.168
3132123MT JACKSON
Solar/Wind Helper
0.376
3151931BEARGRDN S1
50/50
6.456
3151911BEARGRDN G1
50/50
5.002
3144293JTRSVLE
50/50
0.78
972003AH1-546 GEN
Solar/Wind Harmer
29.014
970937AG2-583 GEN
Solar/Wind Harmer
35.582
316322AB2-045
Solar/Wind Harmer
1.612
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
316336AC2-165 C
Solar/Wind Harmer
6.353
3143336POWHATN
Solar/Wind Harmer
3.74
963171AG1-166 GEN
Solar/Wind Harmer
3.245
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
20.625
962491AG1-098 GEN
Solar/Wind Harmer
10.531
315693AD1-088 GEN
Solar/Wind Harmer
7.538
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.275
315687AD1-152 GEN
Solar/Wind Harmer
1.296
971065AG2-659 GEN
Solar/Wind Harmer
5.329
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.915
3143526WINTERP
Solar/Wind Harmer
-0.053
971795AH1-408 GEN
Solar/Wind Harmer
7.462
316003AC1-222 GEN
Solar/Wind Harmer
0.864
960081AF2-299 GEN
Solar/Wind Harmer
0.959
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
970919AG2-571 GEN
Solar/Wind Harmer
2.334
970087AG2-069 GEN
Solar/Wind Harmer
6.886
316023GEN1_S
Solar/Wind Harmer
0.488
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.463
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
316212AC1-099_GEN
Solar/Wind Harmer
0.6
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.428
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.3
315722AD1-056 GEN
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
970659AG2-427 GEN
Solar/Wind Harmer
3.387
316381AD1-082 GEN
Solar/Wind Harmer
0.584
315671AE2-027_GEN
Solar/Wind Harmer
4.776
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.59
970661AG2-428 GEN
Solar/Wind Harmer
6.738
3147983MERCK5
Solar/Wind Helper
0.064
NYPJM->LTFIMP_NY
CLTF
0.338
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.543
LAGNLTFEXP_LAGN->PJM
CLTF
0.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.313
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.396
CPLELTFEXP_CPLE->PJM
CLTF
3.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.931
MDUPJM->LTFIMP_MDU
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.127
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.049

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.92 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:773.16
MW Contribution:2.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
NYPJM->LTFIMP_NY
CLTF
0.345
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.5 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:942.09
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.638
971845AH1-439 GEN
Solar/Wind Harmer
22.236
970285AG2-188 GEN
Solar/Wind Harmer
35.347
315657AE1-056 GEN
Solar/Wind Harmer
9.306
946301AF1-294 GEN
Solar/Wind Harmer
5.986
961791AG1-021 GEN
Solar/Wind Harmer
2.92
970683AG2-441 GEN
Solar/Wind Harmer
16.617
970681AG2-440 GEN
Solar/Wind Harmer
13.294
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.713
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
270494AE1-108_GEN
Solar/Wind Harmer
2.712
316118AC1-105 GEN
Solar/Wind Harmer
0.698
970831AG2-522 GEN
Solar/Wind Harmer
4.772
316233AE1-074 FULL
Solar/Wind Harmer
0.248
971281AH1-106 GEN
Solar/Wind Harmer
1.497
971283AH1-107 GEN
Solar/Wind Harmer
1.497
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.179
316087AB2-174 GEN
Solar/Wind Harmer
1.119
971967AH1-528 GEN
Solar/Wind Harmer
14.578
3137643SOCKMAN
Solar/Wind Harmer
-0.03
970865AG2-541 GEN
Solar/Wind Harmer
2.95
315607AA1-063A GEN
Solar/Wind Harmer
0.728
3146043SEABORD
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.475
970673AG2-436 GEN
Solar/Wind Harmer
14.663
970673AG2-436 GEN
Solar/Wind Harmer
7.425
970085AG2-068 GEN
Solar/Wind Harmer
4.347
970581AG2-369 GEN
Solar/Wind Harmer
3.738
941031AE2-094 GEN
Solar/Wind Harmer
12.804
944011AF1-069 GEN
Solar/Wind Harmer
4.012
965291AG1-394 GEN
Solar/Wind Harmer
0.596
315652AC1-086 GEN
Solar/Wind Harmer
7.525
316318V4-068
Solar/Wind Harmer
0.165
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
315814AE2-033 C
Solar/Wind Harmer
6.071
316315AB2-025 C
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
0.056
961941AG1-037 GEN
Solar/Wind Harmer
0.049
3145513AHOSKIE
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.351
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.125
3151921BEARGRDN G2
50/50
4.436
3144293JTRSVLE
50/50
0.702
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.35
316313AB2-026
Solar/Wind Harmer
0.755
316258AE1-075 C
Solar/Wind Harmer
0.68
316405AF2-144 C
Solar/Wind Harmer
0.717
3143336POWHATN
Solar/Wind Harmer
2.824
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.078
971193AH1-056 GEN
Solar/Wind Harmer
15.51
963181AG1-167 GEN
Solar/Wind Harmer
2.19
959311AF2-222 GEN
Solar/Wind Harmer
20.551
970257AG2-171 GEN
Solar/Wind Harmer
7.144
315785AD2-033 C
Solar/Wind Harmer
4.119
964241AG1-285 GEN
Solar/Wind Harmer
12.377
316131AB2-060 GEN
Solar/Wind Harmer
1.556
970221AG2-151 GEN
Solar/Wind Harmer
8.461
316478AD1-087 GEN
Solar/Wind Harmer
0.958
316486AD2-202 GEN
Solar/Wind Harmer
0.28
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.275
960061AF2-297 GEN
Solar/Wind Harmer
4.563
966621AG1-532 GEN
Solar/Wind Harmer
0.162
971683AH1-343 GEN
Solar/Wind Harmer
3.393
313506AB2-031 GEN
Solar/Wind Harmer
0.625
3150861SPRUNCD
Adder
0.29
970917AG2-570 GEN
Solar/Wind Harmer
17.439
316365GEN2_N
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.164
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.044
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.183
961681AG1-008 GEN
Solar/Wind Harmer
5.183
3146173TUNIS
Solar/Wind Harmer
-0.006
316327AA2-057 GEN
Solar/Wind Harmer
0.657
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.608
316463AE2-346 GEN
Solar/Wind Harmer
0.104
316140AB2-099
Solar/Wind Harmer
0.044
962331AG1-082 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
3138543CONSLDL
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.568
3132273ORANGE
Solar/Wind Helper
0.023
3151931BEARGRDN S1
50/50
5.725
3151911BEARGRDN G1
50/50
4.436
3144293JTRSVLE
50/50
0.702
972003AH1-546 GEN
Solar/Wind Harmer
25.74
970937AG2-583 GEN
Solar/Wind Harmer
31.567
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.64
3143336POWHATN
Solar/Wind Harmer
3.322
963171AG1-166 GEN
Solar/Wind Harmer
2.92
971563AH1-280 GEN
Solar/Wind Harmer
2.92
970685AG2-442 GEN
Solar/Wind Harmer
18.611
962491AG1-098 GEN
Solar/Wind Harmer
9.593
316237AB2-079_GEN
Solar/Wind Harmer
0.415
315693AD1-088 GEN
Solar/Wind Harmer
6.877
971377AH1-170 GEN
Solar/Wind Harmer
1.692
3147623JAMES R
Solar/Wind Harmer
0.209
970401AG2-262 GEN
Solar/Wind Harmer
0.731
957481AF2-042 GEN
Solar/Wind Harmer
34.315
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.213
971065AG2-659 GEN
Solar/Wind Harmer
4.98
3147043LAWRENC
Adder
0.793
316129AC1-054 GEN
Solar/Wind Harmer
0.856
971795AH1-408 GEN
Solar/Wind Harmer
6.949
3143526WINTERP
Solar/Wind Harmer
-0.048
316003AC1-222 GEN
Solar/Wind Harmer
0.825
960081AF2-299 GEN
Solar/Wind Harmer
0.9
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.09
3150851SPRUNCC
Adder
0.29
970919AG2-571 GEN
Solar/Wind Harmer
2.207
970087AG2-069 GEN
Solar/Wind Harmer
6.521
316023GEN1_S
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.4
962571AG1-106 GEN
Solar/Wind Harmer
0.962
316212AC1-099_GEN
Solar/Wind Harmer
0.58
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.006
3145823KELFORD
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
315722AD1-056 GEN
Solar/Wind Harmer
0.666
940641AE2-051 GEN
Solar/Wind Harmer
5.935
3147983MERCK5
Solar/Wind Helper
0.057
3144293JTRSVLE
50/50
0.702
3144293JTRSVLE
50/50
0.591
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.577
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.65
963191AG1-168 GEN
Solar/Wind Harmer
2.19
971741AH1-377 GEN
Solar/Wind Harmer
26.202
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.526
971775AH1-396 GEN
Solar/Wind Harmer
1.357
313527AB2-043 GEN
Solar/Wind Harmer
2.287
971489AH1-241 GEN
Solar/Wind Harmer
8.033
962561AG1-105 GEN
Solar/Wind Harmer
6.548
939181AE1-148 GEN
Solar/Wind Harmer
6.48
964791AG1-342 GEN
Solar/Wind Harmer
2.393
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.726
971223AH1-071 GEN
Solar/Wind Harmer
1.368
3143526WINTERP
Solar/Wind Harmer
-0.048
970933AG2-581 GEN
Solar/Wind Harmer
8.213
316181AB2-040 GEN
Solar/Wind Harmer
1.084
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.846
3145593CAROLNA
Solar/Wind Harmer
0.062
3145783HORNRTN
Solar/Wind Harmer
0.879
3145783HORNRTN
Solar/Wind Harmer
0.703
3145783HORNRTN
Solar/Wind Harmer
0.22
3145783HORNRTN
Solar/Wind Harmer
0.088
316426AA2-053 GEN
Solar/Wind Harmer
0.74
972187AH1-678 GEN
Adder
1.814
972185AH1-677 GEN
Adder
3.525
316274AC1-208 GEN
Solar/Wind Harmer
0.733
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.184
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.012
316222AC1-221 GEN
Solar/Wind Harmer
0.66
3146173TUNIS
Solar/Wind Harmer
-0.006
3146173TUNIS
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Helper
0.172
NYPJM->LTFIMP_NY
CLTF
0.342
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.137
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.398
LAGNLTFEXP_LAGN->PJM
CLTF
1.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.319
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.666
CPLELTFEXP_CPLE->PJM
CLTF
3.817
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.59
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.933
MECLTFEXP_MEC->PJM
CLTF
0.009

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:111.23 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:923.19
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.7
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.482
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.337
970257AG2-171 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
4.062
964241AG1-285 GEN
Solar/Wind Harmer
12.123
970221AG2-151 GEN
Solar/Wind Harmer
8.911
316131AB2-060 GEN
Solar/Wind Harmer
1.517
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.339
971683AH1-343 GEN
Solar/Wind Harmer
3.24
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.142
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
21.959
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.482
970285AG2-188 GEN
Solar/Wind Harmer
35.716
315657AE1-056 GEN
Solar/Wind Harmer
9.289
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.495
970681AG2-440 GEN
Solar/Wind Harmer
13.196
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.668
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.875
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.476
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.768
946281AF1-292 GEN
Solar/Wind Harmer
0.164
316087AB2-174 GEN
Solar/Wind Harmer
1.019
970865AG2-541 GEN
Solar/Wind Harmer
2.825
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.019
970581AG2-369 GEN
Solar/Wind Harmer
3.457
941031AE2-094 GEN
Solar/Wind Harmer
11.99
944011AF1-069 GEN
Solar/Wind Harmer
3.757
971447AH1-217 GEN
Solar/Wind Harmer
2.264
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.7
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.575
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.636
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.113
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.413
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.46
971223AH1-071 GEN
Solar/Wind Harmer
1.732
313527AB2-043 GEN
Solar/Wind Harmer
2.226
962561AG1-105 GEN
Solar/Wind Harmer
6.315
939181AE1-148 GEN
Solar/Wind Harmer
6.206
964791AG1-342 GEN
Solar/Wind Harmer
2.303
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.238
970933AG2-581 GEN
Solar/Wind Harmer
7.823
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.696
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.297
966001AG1-469 GEN
Solar/Wind Helper
0.17
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.7
970119AG2-088 GEN
50/50
16.441
972003AH1-546 GEN
Solar/Wind Harmer
26.109
970937AG2-583 GEN
Solar/Wind Harmer
32.485
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.475
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.39
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.718
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
33.096
315687AD1-152 GEN
Solar/Wind Harmer
1.157
971065AG2-659 GEN
Solar/Wind Harmer
4.696
3147043LAWRENC
Adder
0.745
316129AC1-054 GEN
Solar/Wind Harmer
0.805
971795AH1-408 GEN
Solar/Wind Harmer
6.476
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.043
970087AG2-069 GEN
Solar/Wind Harmer
6.029
3147983MERCK5
Solar/Wind Helper
0.056
NYPJM->LTFIMP_NY
CLTF
0.338
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
0.917
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.775
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.437
CPLELTFEXP_CPLE->PJM
CLTF
3.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.788
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.251

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.89 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:920.43
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.699
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.387
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.48
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.333
970257AG2-171 GEN
Solar/Wind Harmer
7.059
315785AD2-033 C
Solar/Wind Harmer
4.061
964241AG1-285 GEN
Solar/Wind Harmer
12.12
970221AG2-151 GEN
Solar/Wind Harmer
8.909
316131AB2-060 GEN
Solar/Wind Harmer
1.516
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.337
971683AH1-343 GEN
Solar/Wind Harmer
3.239
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.134
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
21.958
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.48
970285AG2-188 GEN
Solar/Wind Harmer
35.714
315657AE1-056 GEN
Solar/Wind Harmer
9.288
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.493
970681AG2-440 GEN
Solar/Wind Harmer
13.194
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.667
316233AE1-074 FULL
Solar/Wind Harmer
0.373
971281AH1-106 GEN
Solar/Wind Harmer
2.251
971283AH1-107 GEN
Solar/Wind Harmer
2.251
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.874
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.474
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.762
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.018
970865AG2-541 GEN
Solar/Wind Harmer
2.824
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.713
970673AG2-436 GEN
Solar/Wind Harmer
6.943
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.017
970581AG2-369 GEN
Solar/Wind Harmer
3.455
941031AE2-094 GEN
Solar/Wind Harmer
11.984
944011AF1-069 GEN
Solar/Wind Harmer
3.755
971447AH1-217 GEN
Solar/Wind Harmer
2.263
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.574
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.635
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.109
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.412
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.458
3143526WINTERP
Solar/Wind Harmer
-0.072
971223AH1-071 GEN
Solar/Wind Harmer
1.731
313527AB2-043 GEN
Solar/Wind Harmer
2.225
962561AG1-105 GEN
Solar/Wind Harmer
6.313
939181AE1-148 GEN
Solar/Wind Harmer
6.204
964791AG1-342 GEN
Solar/Wind Harmer
2.302
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.234
970933AG2-581 GEN
Solar/Wind Harmer
7.82
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.695
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.634
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.295
966001AG1-469 GEN
Solar/Wind Helper
0.17
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
16.437
972003AH1-546 GEN
Solar/Wind Harmer
26.108
970937AG2-583 GEN
Solar/Wind Harmer
32.483
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.472
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.388
3143526WINTERP
Solar/Wind Harmer
-0.072
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.716
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.703
957481AF2-042 GEN
Solar/Wind Harmer
33.086
315687AD1-152 GEN
Solar/Wind Harmer
1.156
971065AG2-659 GEN
Solar/Wind Harmer
4.694
3147043LAWRENC
Adder
0.744
316129AC1-054 GEN
Solar/Wind Harmer
0.804
971795AH1-408 GEN
Solar/Wind Harmer
6.473
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.042
970087AG2-069 GEN
Solar/Wind Harmer
6.026
3147983MERCK5
Solar/Wind Helper
0.056
NYPJM->LTFIMP_NY
CLTF
0.339
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
3.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.758
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.243

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:202.03 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1371.17
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.18
316303AF2-085
50/50
2.224
3151541CLOVER2
50/50
2.487
3151611KERR 4
50/50
0.234
3151621KERR 5
50/50
0.234
3151631KERR 6
50/50
0.234
3151641KERR 7
50/50
0.234
963041AG1-153 GEN
50/50
2.299
315244AE2-183_ST
50/50
2.451
3151281ROARAP4
50/50
0.1
3151281ROARAP4
50/50
0.094
971285AH1-108 GEN
50/50
0.651
315779AE2-040
50/50
1.092
971845AH1-439 GEN
Solar/Wind Harmer
17.513
970285AG2-188 GEN
Solar/Wind Harmer
29.552
315657AE1-056 GEN
Solar/Wind Harmer
8.144
946301AF1-294 GEN
Solar/Wind Harmer
4.404
961791AG1-021 GEN
Solar/Wind Harmer
2.143
970683AG2-441 GEN
Solar/Wind Harmer
13.644
970681AG2-440 GEN
Solar/Wind Harmer
10.915
3144303KENBRDG
Solar/Wind Harmer
0.148
971443AH1-215 GEN
Solar/Wind Harmer
3.079
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.084
971281AH1-106 GEN
Solar/Wind Harmer
1.459
971283AH1-107 GEN
Solar/Wind Harmer
1.459
316118AC1-105 GEN
Solar/Wind Harmer
0.27
270494AE1-108_GEN
Solar/Wind Harmer
1.236
970831AG2-522 GEN
Solar/Wind Harmer
4.291
3147173SINAI
Solar/Wind Harmer
0.095
3147243WELCO
Solar/Wind Harmer
0.059
971967AH1-528 GEN
Solar/Wind Harmer
14.709
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
18.242
970673AG2-436 GEN
Solar/Wind Harmer
12.162
941031AE2-094 GEN
Solar/Wind Harmer
15.639
944011AF1-069 GEN
Solar/Wind Harmer
5.11
3137643SOCKMAN
Solar/Wind Harmer
0.336
970085AG2-068 GEN
Solar/Wind Harmer
4.411
970581AG2-369 GEN
Solar/Wind Harmer
3.794
315607AA1-063A GEN
Solar/Wind Harmer
0.164
3146043SEABORD
Solar/Wind Harmer
0.08
315814AE2-033 C
Solar/Wind Harmer
6.192
316315AB2-025 C
Solar/Wind Harmer
0.063
970865AG2-541 GEN
Solar/Wind Harmer
2.68
965291AG1-394 GEN
Solar/Wind Harmer
0.339
315652AC1-086 GEN
Solar/Wind Harmer
8.307
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.075
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
0.292
3146033SCOT NK
Solar/Wind Harmer
0.294
3145513AHOSKIE
Solar/Wind Harmer
0.153
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.146
3145683EARLEYS
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
3146206CASHIE
Solar/Wind Harmer
0.07
970601AG2-382 GEN
Solar/Wind Harmer
2.62
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.048
316311AC2-079 GEN
Solar/Wind Harmer
2.01
316319Z2-044 C
Solar/Wind Harmer
0
315732AD1-074 GEN1
Solar/Wind Harmer
0.4
315733AD1-074 GEN2
Solar/Wind Harmer
0.4
315735AD1-075 GEN1
Solar/Wind Harmer
0.2
3130546PLYMOUTH
Solar/Wind Harmer
0.07
315835AF2-110_GEN
Solar/Wind Harmer
0.478
315816AE2-034 GEN
Solar/Wind Harmer
0.298
3130156CHOWAN
Solar/Wind Harmer
0.069
3130156CHOWAN
Solar/Wind Harmer
0.069
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.069
3146486SUNBURY
Solar/Wind Harmer
0.069
316321Z2-027
Solar/Wind Harmer
0.013
3145176PASQUOTANK
Solar/Wind Harmer
0.043
3146396TANGLEW
Solar/Wind Harmer
0.19
316305AF2-043 C
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Harmer
0.037
3146406KITTY HAWK
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
0.346
957871AF2-081 GEN
Solar/Wind Harmer
3.419
3151081ELIZAR1
Adder
6.268
3151091ELIZAR2
Adder
6.16
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.903
316005AA1-067
Solar/Wind Harmer
0.072
3145746EVERETS
Solar/Wind Harmer
0.267
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
970181AG2-120 GEN
Solar/Wind Harmer
0.836
971445AH1-216 GEN
Solar/Wind Harmer
4.703
972265AH1-717 GEN
Adder
5.124
3151201GRAVEL4
Adder
4.803
3151191GRAVEL3
Adder
4.742
3151211GRAVEL5
Adder
4.742
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.353
316123AC1-075 GEN
Solar/Wind Harmer
0.09
970165AG2-112 GEN
Solar/Wind Harmer
0.531
970163AG2-111 GEN
Solar/Wind Harmer
0.506
971447AH1-217 GEN
Solar/Wind Harmer
1.848
971167AH1-042 GEN
Solar/Wind Harmer
5.088
3138283WHITEMARSH
Solar/Wind Harmer
0.013
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.105
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.12
3151921BEARGRDN G2
50/50
4.548
3144293JTRSVLE
50/50
0.754
970413AG2-270 GEN
50/50
10.906
3151591KERR 2
50/50
0.234
3151031BRUNSWICKG2
50/50
1.135
3151261ROARAP2
50/50
0.101
3150861SPRUNCD
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
3146776BUCKING
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.188
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
316313AB2-026
Solar/Wind Harmer
0.171
316258AE1-075 C
Solar/Wind Harmer
0.204
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.088
970909AG2-566 GEN
Solar/Wind Harmer
2.566
3147133PAMPLIN
Solar/Wind Harmer
0.741
971193AH1-056 GEN
Solar/Wind Harmer
14.378
963181AG1-167 GEN
Solar/Wind Harmer
0.893
959311AF2-222 GEN
Solar/Wind Harmer
16.945
970257AG2-171 GEN
Solar/Wind Harmer
5.919
315785AD2-033 C
Solar/Wind Harmer
1.44
964241AG1-285 GEN
Solar/Wind Harmer
10.432
316131AB2-060 GEN
Solar/Wind Harmer
0.453
970221AG2-151 GEN
Solar/Wind Harmer
7.009
316478AD1-087 GEN
Solar/Wind Harmer
0.407
316486AD2-202 GEN
Solar/Wind Harmer
0.12
3147043LAWRENC
Solar/Wind Harmer
0.063
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.061
313506AB2-031 GEN
Solar/Wind Harmer
0.265
971683AH1-343 GEN
Solar/Wind Harmer
3.059
970917AG2-570 GEN
Solar/Wind Harmer
7.384
316365GEN2_N
Solar/Wind Harmer
0.176
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.076
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
0.075
957521AF2-046 GEN
Solar/Wind Harmer
5.572
961681AG1-008 GEN
Solar/Wind Harmer
5.572
3145796HORNRTN
Solar/Wind Harmer
0.297
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316210AC1-098 GEN
Solar/Wind Harmer
0.686
316463AE2-346 GEN
Solar/Wind Harmer
0.063
316140AB2-099
Solar/Wind Harmer
0.026
962331AG1-082 GEN
Solar/Wind Harmer
0.783
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.073
316327AA2-057 GEN
Solar/Wind Harmer
0.108
3145273HOLLAND
Solar/Wind Harmer
0.054
315813AE1-149 C
Solar/Wind Harmer
3.784
3156021HOLLOMANSOL
Solar/Wind Harmer
0.322
315839AE2-212 C
Solar/Wind Harmer
0.001
315724AD1-057 GEN
Solar/Wind Harmer
0.265
970659AG2-427 GEN
Solar/Wind Harmer
0.747
316083AB2-161 GEN
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
0.07
3146233WITAKRS
Solar/Wind Harmer
0.351
3146233WITAKRS
Solar/Wind Harmer
0.048
3138543CONSLDL
Solar/Wind Harmer
0.046
315737AD1-076 GEN
Solar/Wind Harmer
0.896
971157AH1-035 GEN
Solar/Wind Harmer
0.836
965281AG1-393 GEN
Solar/Wind Harmer
0.741
315614AA2-178 GEN
Solar/Wind Harmer
0.398
3146376EDENTON
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
0.069
971153AH1-033 GEN
Solar/Wind Harmer
0.794
944581AF1-123 GEN
Solar/Wind Harmer
15.457
944601AF1-125 GEN
Solar/Wind Harmer
15.219
3145963POPLR C
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.349
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.068
971623AH1-311 GEN
Solar/Wind Harmer
0.136
3144536CHRHLND
Solar/Wind Harmer
0.01
3145933PARMELE
Solar/Wind Harmer
0.068
966801AG1-551 GEN
Solar/Wind Harmer
0.788
961601AG1-000A GEN
Solar/Wind Harmer
4.808
315773AC2-141 GEN
Solar/Wind Harmer
2.468
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
316283AC2-100 C
Solar/Wind Harmer
0.132
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.027
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.798
3151171GRAVELC
Adder
0.923
961611AG1-000B GEN
Solar/Wind Harmer
1.758
315778AD1-151 GEN
Solar/Wind Harmer
5.261
970129AG2-093 GEN
Solar/Wind Harmer
3.971
970133AG2-095 GEN
Solar/Wind Harmer
0.63
3144216WINCHST
Adder
0.231
3150921YORKTN3
Adder
1.525
3142946ENON
Solar/Wind Harmer
0.02
316382AG1-145 C
Solar/Wind Harmer
0
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.175
316499AE2-029_GEN
Solar/Wind Helper
0.514
3132273ORANGE
Solar/Wind Helper
0.027
315616AA1-038_C
Solar/Wind Helper
0.545
3147666LOUISA
Solar/Wind Helper
0.273
3151931BEARGRDN S1
50/50
5.869
3151911BEARGRDN G1
50/50
4.548
3144293JTRSVLE
50/50
0.754
970119AG2-088 GEN
50/50
16.679
3151531CLOVER1
50/50
2.499
3151601KERR 3
50/50
0.234
3151581KERR 1
50/50
0.083
3147043LAWRENC
50/50
1
3151051BRUNSWICKS1
50/50
2.357
3151021BRUNSWICKG1
50/50
1.135
971451AH1-221 GEN
50/50
3.449
315243AE2-183_GT3
50/50
1.418
3151261ROARAP2
50/50
0.103
3150851SPRUNCC
50/50
0.398
3151391GASTONA
50/50
0.204
3151411GASTONB
50/50
0.204
972003AH1-546 GEN
Solar/Wind Harmer
20.039
970937AG2-583 GEN
Solar/Wind Harmer
24.928
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.157
3146926FARMVIL
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Harmer
0.012
3143336POWHATN
Solar/Wind Harmer
4.81
963171AG1-166 GEN
Solar/Wind Harmer
1.19
971563AH1-280 GEN
Solar/Wind Harmer
2.381
970685AG2-442 GEN
Solar/Wind Harmer
15.281
962491AG1-098 GEN
Solar/Wind Harmer
8.349
315693AD1-088 GEN
Solar/Wind Harmer
6.776
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971377AH1-170 GEN
Solar/Wind Harmer
1.402
3147623JAMES R
Solar/Wind Harmer
0.305
3143226MDLTHAN
Solar/Wind Harmer
0.125
957481AF2-042 GEN
Solar/Wind Harmer
31.266
970401AG2-262 GEN
Solar/Wind Harmer
0.671
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3143526WINTERP
Solar/Wind Harmer
0.547
971065AG2-659 GEN
Solar/Wind Harmer
4.446
316129AC1-054 GEN
Solar/Wind Harmer
0.385
971795AH1-408 GEN
Solar/Wind Harmer
6.611
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.847
970919AG2-571 GEN
Solar/Wind Harmer
2.953
970087AG2-069 GEN
Solar/Wind Harmer
6.617
3145783HORNRTN
Solar/Wind Harmer
0.082
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
6.459
316023GEN1_S
Solar/Wind Harmer
0.176
939411AE1-173 GEN
Solar/Wind Harmer
33.156
3146263WOODLND
Solar/Wind Harmer
0.076
316011AB1-132 GEN
Solar/Wind Harmer
1.373
962571AG1-106 GEN
Solar/Wind Harmer
1.074
3145893MURPHYS
Solar/Wind Harmer
0.301
3145893MURPHYS
Solar/Wind Harmer
0.334
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
316212AC1-099_GEN
Solar/Wind Harmer
0.382
3145823KELFORD
Solar/Wind Harmer
0.073
3145683EARLEYS
Solar/Wind Harmer
0.073
315722AD1-056 GEN
Solar/Wind Harmer
0.447
970659AG2-427 GEN
Solar/Wind Harmer
3.416
316381AD1-082 GEN
Solar/Wind Harmer
0.074
970661AG2-428 GEN
Solar/Wind Harmer
7.004
3146206CASHIE
Solar/Wind Harmer
0.07
971547AH1-271 GEN
Solar/Wind Harmer
1.497
3142543TWELFTH
Solar/Wind Harmer
0.007
3146233WITAKRS
Solar/Wind Harmer
0.278
316093AE2-104_GEN
Solar/Wind Harmer
1.171
3145663CRESWEL
Solar/Wind Harmer
0.194
971163AH1-040 GEN
Solar/Wind Harmer
5.558
3130156CHOWAN
Solar/Wind Harmer
0.069
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.223
3146516WINFALL
Solar/Wind Harmer
0.069
315671AE2-027_GEN
Solar/Wind Harmer
4.41
316246AF1-032 C
Solar/Wind Harmer
0.031
3146456SLIGO L269
Solar/Wind Harmer
0.069
316388AE2-253 GEN
Solar/Wind Harmer
0.215
944591AF1-124 GEN
Solar/Wind Harmer
15.512
3145963POPLR C
Solar/Wind Harmer
0.069
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.853
3145543BTLEBRO
Solar/Wind Harmer
0.068
3145543BTLEBRO
Solar/Wind Harmer
0.054
316359AB2-059 GEN
Solar/Wind Harmer
0.244
316049AB1-081 GEN
Solar/Wind Harmer
0.389
3142053HEARTS
Solar/Wind Harmer
0.12
316072AD1-144
Solar/Wind Harmer
0.025
3146293MARTNCO
Solar/Wind Harmer
0.063
316294AC1-161 GEN
Solar/Wind Harmer
1.171
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
316494AC1-189 GEN
Solar/Wind Harmer
0.227
3145746EVERETS
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.067
3145336SMITFLD
Solar/Wind Harmer
0.267
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
961611AG1-000B GEN
Solar/Wind Harmer
3.457
971647AH1-324 GEN
Solar/Wind Harmer
2.81
971069AG2-661 GEN
Solar/Wind Harmer
1.169
316458AB2-190 GEN2
Solar/Wind Harmer
0.353
970129AG2-093 GEN
Solar/Wind Harmer
1.869
944631AF1-128 GEN
Adder
29.45
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971317AH1-138 GEN
Solar/Wind Harmer
0.439
316159AE1-175 C
Solar/Wind Harmer
0.05
3142433PROV 92
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.056
316192AB2-158 GEN
Solar/Wind Helper
0.823
3147666LOUISA
Solar/Wind Helper
0.475
3144293JTRSVLE
50/50
0.754
3144293JTRSVLE
50/50
0.635
970535AG2-341 GEN
50/50
2.24
3152661PLYWOOD A
50/50
0.227
3151041BRUNSWICKG3
50/50
1.135
972187AH1-678 GEN
50/50
2.606
315242AE2-183_GT2
50/50
1.418
315241AE2-183_GT1
50/50
1.409
972185AH1-677 GEN
50/50
5.111
970533AG2-339 GEN
50/50
7.548
970531AG2-338 GEN
50/50
3.019
3146776BUCKING
Solar/Wind Harmer
1.571
3146776BUCKING
Solar/Wind Harmer
0.127
970301AG2-198 GEN
Solar/Wind Harmer
10.262
3147133PAMPLIN
Solar/Wind Harmer
0.236
3147133PAMPLIN
Solar/Wind Harmer
0.189
958211AF2-115 GEN
Solar/Wind Harmer
2.678
963191AG1-168 GEN
Solar/Wind Harmer
0.893
971741AH1-377 GEN
Solar/Wind Harmer
21.598
316034AC1-036 C
Solar/Wind Harmer
0.014
970323AG2-213 GEN
Solar/Wind Harmer
7.892
971775AH1-396 GEN
Solar/Wind Harmer
0.296
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
7.009
971223AH1-071 GEN
Solar/Wind Harmer
1.334
962561AG1-105 GEN
Solar/Wind Harmer
5.681
939181AE1-148 GEN
Solar/Wind Harmer
5.661
970099AG2-077 GEN
Solar/Wind Harmer
12.506
964791AG1-342 GEN
Solar/Wind Harmer
2.195
3146843MT LREL
Solar/Wind Harmer
0.114
3146843MT LREL
Solar/Wind Harmer
0.114
3143526WINTERP
Solar/Wind Harmer
0.547
970933AG2-581 GEN
Solar/Wind Harmer
7.995
316181AB2-040 GEN
Solar/Wind Harmer
0.124
3145593CAROLNA
Solar/Wind Harmer
0.083
3145593CAROLNA
Solar/Wind Harmer
0.083
966811AG1-552 GEN
Solar/Wind Harmer
0.899
3145593CAROLNA
Solar/Wind Harmer
0.103
3145783HORNRTN
Solar/Wind Harmer
1.451
3145783HORNRTN
Solar/Wind Harmer
1.161
3145783HORNRTN
Solar/Wind Harmer
0.363
3145783HORNRTN
Solar/Wind Harmer
0.145
316426AA2-053 GEN
Solar/Wind Harmer
0.274
3144356SAPONY
Solar/Wind Harmer
0.654
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
0.503
3145893MURPHYS
Solar/Wind Harmer
0.135
316274AC1-208 GEN
Solar/Wind Harmer
0.39
3145796HORNRTN
Solar/Wind Harmer
0.223
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970657AG2-426 GEN
Solar/Wind Harmer
2.47
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.223
3146376EDENTON
Solar/Wind Harmer
0.308
3146376EDENTON
Solar/Wind Harmer
0.308
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146626S HERTFORD
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
0.069
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.069
316240AF1-291 C
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Harmer
0.275
3137176SLIGO L2192
Solar/Wind Harmer
0.273
3146456SLIGO L269
Solar/Wind Harmer
1.215
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.038
316339AD2-160 GEN
Solar/Wind Harmer
0.111
3145506HICKORY
Solar/Wind Harmer
0.274
3145506HICKORY
Solar/Wind Harmer
0.165
3145506HICKORY
Solar/Wind Harmer
0.041
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.066
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.505
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316263AC1-034 GEN
Solar/Wind Harmer
2.586
3145933PARMELE
Solar/Wind Harmer
0.135
3145933PARMELE
Solar/Wind Harmer
0.068
961601AG1-000A GEN
Solar/Wind Harmer
1.202
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.074
3142366NRTHEST
Adder
0.195
3142946ENON
Solar/Wind Harmer
0.006
3150691DARBY 3
Adder
4.195
3150701DARBY 4
Adder
4.185
3150681DARBY 2
Adder
4.18
3150671DARBY 1
Adder
4.175
942751AE2-291 GEN
Solar/Wind Harmer
3.155
966001AG1-469 GEN
Solar/Wind Helper
0.19
NYPJM->LTFIMP_NY
CLTF
0.579
LGEELTFEXP_LGEE->PJM
CLTF
0.048
LAGNLTFEXP_LAGN->PJM
CLTF
1.781
WECLTFEXP_WEC->PJM
CLTF
0.018
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.535
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
4.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.276
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.726
MECLTFEXP_MEC->PJM
CLTF
0.354
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.11
MW Contribution:4.99
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.541
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.672
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.388
970937AG2-583 GEN
Solar/Wind Harmer
32.774
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.836
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.35
3151921BEARGRDN G2
50/50
4.541
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.895
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.178
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.229
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.484
972205AH1-687 GEN
50/50
22.146
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.67
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.409
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.745
3151211GRAVEL5
Adder
4.745
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.927
3147666LOUISA
Solar/Wind Helper
0.538
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.309
315616AA1-038_C
Solar/Wind Helper
0.548
944601AF1-125 GEN
Solar/Wind Harmer
11.266
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.238
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.529
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
NYPJM->LTFIMP_NY
CLTF
0.574
LAGNLTFEXP_LAGN->PJM
CLTF
1.77
LGEELTFEXP_LGEE->PJM
CLTF
0.044
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.515
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.202
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:184.71 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1533.1
MW Contribution:4.99
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
22.145
316303AF2-085
50/50
2.223
3151541CLOVER2
50/50
2.485
3151611KERR 4
50/50
0.233
3151621KERR 5
50/50
0.233
3151631KERR 6
50/50
0.233
3151641KERR 7
50/50
0.233
971845AH1-439 GEN
Solar/Wind Harmer
23.024
970285AG2-188 GEN
Solar/Wind Harmer
36.669
315657AE1-056 GEN
Solar/Wind Harmer
9.935
946301AF1-294 GEN
Solar/Wind Harmer
6.417
961791AG1-021 GEN
Solar/Wind Harmer
3.13
970683AG2-441 GEN
Solar/Wind Harmer
17.94
970681AG2-440 GEN
Solar/Wind Harmer
14.352
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.049
316239AB2-077_GEN
Solar/Wind Harmer
0.467
316238AB2-078_GEN
Solar/Wind Harmer
0.467
316233AE1-074 FULL
Solar/Wind Harmer
0.318
971281AH1-106 GEN
Solar/Wind Harmer
1.921
971283AH1-107 GEN
Solar/Wind Harmer
1.921
316118AC1-105 GEN
Solar/Wind Harmer
0.807
270494AE1-108_GEN
Solar/Wind Harmer
2.995
970831AG2-522 GEN
Solar/Wind Harmer
5.644
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
19.408
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.385
970673AG2-436 GEN
Solar/Wind Harmer
20.177
970673AG2-436 GEN
Solar/Wind Harmer
10.216
941031AE2-094 GEN
Solar/Wind Harmer
17.883
944011AF1-069 GEN
Solar/Wind Harmer
5.603
3137643SOCKMAN
Solar/Wind Harmer
-0.038
970085AG2-068 GEN
Solar/Wind Harmer
5.805
970581AG2-369 GEN
Solar/Wind Harmer
4.993
971285AH1-108 GEN
Adder
0.613
315607AA1-063A GEN
Solar/Wind Harmer
0.911
3146043SEABORD
Solar/Wind Harmer
-0.009
315814AE2-033 C
Solar/Wind Harmer
8.189
316315AB2-025 C
Solar/Wind Harmer
0.237
970865AG2-541 GEN
Solar/Wind Harmer
3.523
965291AG1-394 GEN
Solar/Wind Harmer
0.761
315652AC1-086 GEN
Solar/Wind Harmer
9.545
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.033
3146033SCOT NK
Solar/Wind Harmer
-0.033
3145513AHOSKIE
Solar/Wind Harmer
0.072
961941AG1-037 GEN
Solar/Wind Harmer
0.062
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.449
315833AF1-017_GEN
Solar/Wind Harmer
1.494
316349AD2-085 GEN
Solar/Wind Harmer
0.7
316311AC2-079 GEN
Solar/Wind Harmer
3.968
316319Z2-044 C
Solar/Wind Harmer
0.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.583
315733AD1-074 GEN2
Solar/Wind Harmer
1.583
315735AD1-075 GEN1
Solar/Wind Harmer
0.792
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.632
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315611Z1-036_GEN2
Solar/Wind Harmer
1.92
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.209
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.142
316305AF2-043 C
Solar/Wind Harmer
0.233
313526AB2-022
Solar/Wind Harmer
0.209
319010AE1-072 C
Solar/Wind Harmer
1.562
3146406KITTY HAWK
Solar/Wind Harmer
0.006
957871AF2-081 GEN
Solar/Wind Harmer
3.86
3151081ELIZAR1
Adder
6.271
3151931BEARGRDN S1
50/50
5.86
3151911BEARGRDN G1
50/50
4.54
3144293JTRSVLE
50/50
0.753
970119AG2-088 GEN
50/50
16.671
3151531CLOVER1
50/50
2.497
3151601KERR 3
50/50
0.233
3151581KERR 1
50/50
0.083
972003AH1-546 GEN
Solar/Wind Harmer
26.387
970937AG2-583 GEN
Solar/Wind Harmer
32.773
316322AB2-045
Solar/Wind Harmer
1.483
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.021
316336AC2-165 C
Solar/Wind Harmer
6.018
3143336POWHATN
Solar/Wind Harmer
3.603
963171AG1-166 GEN
Solar/Wind Harmer
3.13
971563AH1-280 GEN
Solar/Wind Harmer
3.13
970685AG2-442 GEN
Solar/Wind Harmer
20.093
962491AG1-098 GEN
Solar/Wind Harmer
10.981
315693AD1-088 GEN
Solar/Wind Harmer
7.922
316237AB2-079_GEN
Solar/Wind Harmer
0.467
971377AH1-170 GEN
Solar/Wind Harmer
1.835
3147623JAMES R
Solar/Wind Harmer
0.227
3143226MDLTHAN
Solar/Wind Harmer
-0.014
957481AF2-042 GEN
Solar/Wind Harmer
41.127
970401AG2-262 GEN
Solar/Wind Harmer
0.837
315687AD1-152 GEN
Solar/Wind Harmer
1.432
3143526WINTERP
Solar/Wind Harmer
-0.061
3147043LAWRENC
Adder
0.942
971065AG2-659 GEN
Solar/Wind Harmer
5.848
316129AC1-054 GEN
Solar/Wind Harmer
1.008
971795AH1-408 GEN
Solar/Wind Harmer
8.349
316003AC1-222 GEN
Solar/Wind Harmer
0.972
960081AF2-299 GEN
Solar/Wind Harmer
1.114
970919AG2-571 GEN
Solar/Wind Harmer
2.952
970087AG2-069 GEN
Solar/Wind Harmer
8.708
3145783HORNRTN
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.375
316190AA2-174 GEN
Solar/Wind Harmer
0.112
940641AE2-051 GEN
Solar/Wind Harmer
8.503
316023GEN1_S
Solar/Wind Harmer
0.594
939411AE1-173 GEN
Solar/Wind Harmer
43.657
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.775
962571AG1-106 GEN
Solar/Wind Harmer
1.22
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.723
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.219
316381AD1-082 GEN
Solar/Wind Harmer
0.728
315722AD1-056 GEN
Solar/Wind Harmer
0.83
970661AG2-428 GEN
Solar/Wind Harmer
8.41
3142543TWELFTH
Solar/Wind Harmer
-0.001
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
1.971
3146233WITAKRS
Solar/Wind Harmer
-0.031
316093AE2-104_GEN
Solar/Wind Harmer
2.275
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.318
3130156CHOWAN
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.92
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.811
316246AF1-032 C
Solar/Wind Harmer
0.157
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.521
944591AF1-124 GEN
Solar/Wind Harmer
35.23
3150981CHESPKA
Adder
0.854
3143096IRON208
Adder
0.277
3151171GRAVELC
Adder
0.702
944631AF1-128 GEN
Adder
29.485
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3147983MERCK5
Solar/Wind Helper
0.057
316192AB2-158 GEN
Solar/Wind Helper
0.928
3147666LOUISA
Solar/Wind Helper
0.539
3151921BEARGRDN G2
50/50
4.54
3144293JTRSVLE
50/50
0.753
970413AG2-270 GEN
50/50
10.894
3151591KERR 2
50/50
0.233
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
942461AE2-259 GEN
Solar/Wind Harmer
4.6
316313AB2-026
Solar/Wind Harmer
0.819
316258AE1-075 C
Solar/Wind Harmer
0.737
316405AF2-144 C
Solar/Wind Harmer
0.778
3143336POWHATN
Solar/Wind Harmer
3.062
970909AG2-566 GEN
Solar/Wind Harmer
2.562
3147133PAMPLIN
Solar/Wind Harmer
-0.083
971193AH1-056 GEN
Solar/Wind Harmer
16.559
963181AG1-167 GEN
Solar/Wind Harmer
2.348
959311AF2-222 GEN
Solar/Wind Harmer
22.325
970257AG2-171 GEN
Solar/Wind Harmer
7.783
315785AD2-033 C
Solar/Wind Harmer
4.506
964241AG1-285 GEN
Solar/Wind Harmer
13.718
316131AB2-060 GEN
Solar/Wind Harmer
1.742
970221AG2-151 GEN
Solar/Wind Harmer
9.177
316478AD1-087 GEN
Solar/Wind Harmer
1.133
316486AD2-202 GEN
Solar/Wind Harmer
0.332
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.322
960061AF2-297 GEN
Solar/Wind Harmer
5.34
966621AG1-532 GEN
Solar/Wind Harmer
0.201
313506AB2-031 GEN
Solar/Wind Harmer
0.773
970917AG2-570 GEN
Solar/Wind Harmer
23.32
971683AH1-343 GEN
Solar/Wind Harmer
4.021
3150861SPRUNCD
Adder
0.375
316365GEN2_N
Solar/Wind Harmer
0.594
3156081AA2-088 GEN
Solar/Wind Harmer
2.773
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.624
961681AG1-008 GEN
Solar/Wind Harmer
6.624
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.302
316463AE2-346 GEN
Solar/Wind Harmer
0.133
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.031
316317KELFORD C
Solar/Wind Harmer
0.388
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.813
3145273HOLLAND
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
4.985
3156021HOLLOMANSOL
Solar/Wind Harmer
1.073
315839AE2-212 C
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
0.748
316083AB2-161 GEN
Solar/Wind Harmer
1.288
315724AD1-057 GEN
Solar/Wind Harmer
0.456
970661AG2-428 GEN
Solar/Wind Harmer
1.49
3146206CASHIE
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.164
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.488
971157AH1-035 GEN
Solar/Wind Harmer
0.978
965281AG1-393 GEN
Solar/Wind Harmer
0.977
315614AA2-178 GEN
Solar/Wind Harmer
0.842
3146376EDENTON
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316435W1029_GEN3
Solar/Wind Harmer
1.405
316320Y1-086
Solar/Wind Harmer
0.453
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.941
944581AF1-123 GEN
Solar/Wind Harmer
35.103
3151101ELIZAR3
Adder
6.351
3143096IRON208
Adder
0.277
3143096IRON208
Adder
0.272
3151221GRAVEL6
Adder
4.801
3151171GRAVELC
Adder
0.924
3144216WINCHST
Adder
0.232
3150921YORKTN3
Adder
1.526
3142433PROV 92
Adder
0.11
3144293JTRSVLE
50/50
0.753
3144293JTRSVLE
50/50
0.634
970535AG2-341 GEN
50/50
2.237
3146776BUCKING
Solar/Wind Harmer
-0.175
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.493
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.913
963191AG1-168 GEN
Solar/Wind Harmer
2.348
971741AH1-377 GEN
Solar/Wind Harmer
28.4
316034AC1-036 C
Solar/Wind Harmer
0.386
970323AG2-213 GEN
Solar/Wind Harmer
10.377
971775AH1-396 GEN
Solar/Wind Harmer
1.478
313527AB2-043 GEN
Solar/Wind Harmer
2.568
971489AH1-241 GEN
Solar/Wind Harmer
8.713
971223AH1-071 GEN
Solar/Wind Harmer
1.756
962561AG1-105 GEN
Solar/Wind Harmer
7.471
939181AE1-148 GEN
Solar/Wind Harmer
7.446
970099AG2-077 GEN
Solar/Wind Harmer
16.451
964791AG1-342 GEN
Solar/Wind Harmer
2.74
3146843MT LREL
Solar/Wind Harmer
-0.013
3146843MT LREL
Solar/Wind Harmer
-0.013
3143526WINTERP
Solar/Wind Harmer
-0.061
970933AG2-581 GEN
Solar/Wind Harmer
10.52
972187AH1-678 GEN
Adder
2.454
972185AH1-677 GEN
Adder
4.815
316181AB2-040 GEN
Solar/Wind Harmer
1.342
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
1.047
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.088
3145783HORNRTN
Solar/Wind Harmer
0.87
3145783HORNRTN
Solar/Wind Harmer
0.272
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.92
3144356SAPONY
Solar/Wind Harmer
0.307
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
316274AC1-208 GEN
Solar/Wind Harmer
0.909
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.852
970657AG2-426 GEN
Solar/Wind Harmer
2.477
970657AG2-426 GEN
Solar/Wind Harmer
0.518
316065AD1-022 GEN
Solar/Wind Harmer
3.932
3146376EDENTON
Solar/Wind Harmer
0.231
3146376EDENTON
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.405
316433W1029_GEN2
Solar/Wind Harmer
1.405
316240AF1-291 C
Solar/Wind Harmer
0.233
3146386ELIZ CT
Solar/Wind Harmer
-0.008
3130086AYDLETT
Solar/Wind Harmer
-0.031
3137176SLIGO L2192
Solar/Wind Harmer
-0.031
3146456SLIGO L269
Solar/Wind Harmer
0.912
316018AA1-139 ULT2
Solar/Wind Harmer
0.661
316017AA1-139 ULT1
Solar/Wind Harmer
0.625
316339AD2-160 GEN
Solar/Wind Harmer
0.521
3150991CHESPKB
Adder
0.716
3150991CHESPKB
Adder
0.699
944641AF1-129 GEN
Adder
32.53
3142366NRTHEST
Adder
0.195
3150691DARBY 3
Adder
4.201
3150701DARBY 4
Adder
4.191
3150681DARBY 2
Adder
4.186
3150671DARBY 1
Adder
4.181
966001AG1-469 GEN
Solar/Wind Helper
0.199
3151091ELIZAR2
Adder
6.162
3152611GOSPORTB
Adder
0.871
3152621GOSPORTC
Adder
0.739
3152601GOSPORTA
Adder
0.682
972265AH1-717 GEN
Adder
5.127
3151201GRAVEL4
Adder
4.806
3151191GRAVEL3
Adder
4.746
3151211GRAVEL5
Adder
4.746
3142433PROV 92
Adder
0.11
3142433PROV 92
Adder
0.11
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.101
3148463FAIRFLD
Solar/Wind Helper
0.121
3142433PROV 92
Adder
0.11
3148013FISHERV
Solar/Wind Helper
0.176
316499AE2-029_GEN
Solar/Wind Helper
0.517
3132273ORANGE
Solar/Wind Helper
0.028
3147666LOUISA
Solar/Wind Helper
0.31
315616AA1-038_C
Solar/Wind Helper
0.549
944601AF1-125 GEN
Solar/Wind Harmer
11.266
NYPJM->LTFIMP_NY
CLTF
0.574
LGEELTFEXP_LGEE->PJM
CLTF
0.044
LAGNLTFEXP_LAGN->PJM
CLTF
1.769
WECLTFEXP_WEC->PJM
CLTF
0.016
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.514
TVALTFEXP_TVA->PJM
CLTF
0.864
CPLELTFEXP_CPLE->PJM
CLTF
4.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.703
MECLTFEXP_MEC->PJM
CLTF
0.346
SIGELTFEXP_SIGE->PJM
CLTF
0.008

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:4.48
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
NYPJM->LTFIMP_NY
CLTF
0.536
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
LGEELTFEXP_LGEE->PJM
CLTF
0.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:172.6 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1432.61
MW Contribution:4.48
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.601
3144293JTRSVLE
50/50
0.746
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.021
316313AB2-026
Solar/Wind Harmer
0.868
316258AE1-075 C
Solar/Wind Harmer
0.782
316405AF2-144 C
Solar/Wind Harmer
0.825
3143336POWHATN
Solar/Wind Harmer
3.247
942461AE2-259 GEN
Solar/Wind Harmer
4.59
970909AG2-566 GEN
Solar/Wind Harmer
2.539
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.45
963181AG1-167 GEN
Solar/Wind Harmer
2.328
959311AF2-222 GEN
Solar/Wind Harmer
22.003
970257AG2-171 GEN
Solar/Wind Harmer
7.661
315785AD2-033 C
Solar/Wind Harmer
4.427
964241AG1-285 GEN
Solar/Wind Harmer
13.397
316131AB2-060 GEN
Solar/Wind Harmer
1.694
970221AG2-151 GEN
Solar/Wind Harmer
9.59
316478AD1-087 GEN
Solar/Wind Harmer
1.073
316486AD2-202 GEN
Solar/Wind Harmer
0.314
3147043LAWRENC
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.417
316248AF1-058 C
Solar/Wind Harmer
0.306
960061AF2-297 GEN
Solar/Wind Harmer
5.079
966621AG1-532 GEN
Solar/Wind Harmer
0.189
313506AB2-031 GEN
Solar/Wind Harmer
0.727
971683AH1-343 GEN
Solar/Wind Harmer
3.823
970917AG2-570 GEN
Solar/Wind Harmer
20.936
316365GEN2_N
Solar/Wind Harmer
0.554
3143096IRON208
Adder
0.298
3143096IRON208
Adder
0.292
3156081AA2-088 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315839AE2-212 C
Solar/Wind Harmer
0.237
957521AF2-046 GEN
Solar/Wind Harmer
6.176
961681AG1-008 GEN
Solar/Wind Harmer
6.176
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
965281AG1-393 GEN
Solar/Wind Harmer
0.97
3146173TUNIS
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.214
315813AE1-149 C
Solar/Wind Harmer
4.801
316463AE2-346 GEN
Solar/Wind Harmer
0.124
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.959
316317KELFORD C
Solar/Wind Harmer
0.361
3145823KELFORD
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
0.714
316083AB2-161 GEN
Solar/Wind Harmer
1.228
970661AG2-428 GEN
Solar/Wind Harmer
1.415
316327AA2-057 GEN
Solar/Wind Harmer
0.756
3145273HOLLAND
Solar/Wind Harmer
-0.006
970133AG2-095 GEN
Solar/Wind Harmer
0.837
3156021HOLLOMANSOL
Solar/Wind Harmer
0.996
315724AD1-057 GEN
Solar/Wind Harmer
0.424
970129AG2-093 GEN
Solar/Wind Harmer
4.142
3146206CASHIE
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
315778AD1-151 GEN
Solar/Wind Harmer
6.319
3138543CONSLDL
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.378
971157AH1-035 GEN
Solar/Wind Harmer
0.905
315614AA2-178 GEN
Solar/Wind Harmer
0.779
3146376EDENTON
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.298
961611AG1-000B GEN
Solar/Wind Harmer
1.508
316320Y1-086
Solar/Wind Harmer
0.418
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151221GRAVEL6
Adder
4.597
3151171GRAVELC
Adder
0.884
3144873MCLAUGH
Solar/Wind Harmer
0
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.866
3144216WINCHST
Adder
0.221
3150921YORKTN3
Adder
1.456
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3148013FISHERV
Solar/Wind Helper
0.171
316499AE2-029_GEN
Solar/Wind Helper
0.503
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.534
3147666LOUISA
Solar/Wind Helper
0.265
944581AF1-123 GEN
Solar/Wind Harmer
1.127
3151931BEARGRDN S1
50/50
5.938
3151911BEARGRDN G1
50/50
4.601
3144293JTRSVLE
50/50
0.746
970119AG2-088 GEN
50/50
19.705
972003AH1-546 GEN
Solar/Wind Harmer
26.72
970937AG2-583 GEN
Solar/Wind Harmer
33.599
316322AB2-045
Solar/Wind Harmer
1.495
3146776BUCKING
Solar/Wind Harmer
-0.018
316336AC2-165 C
Solar/Wind Harmer
6.302
3146926FARMVIL
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
3.82
963171AG1-166 GEN
Solar/Wind Harmer
3.104
971563AH1-280 GEN
Solar/Wind Harmer
3.104
970685AG2-442 GEN
Solar/Wind Harmer
19.859
3143226MDLTHAN
Solar/Wind Harmer
-0.017
962491AG1-098 GEN
Solar/Wind Harmer
10.562
971377AH1-170 GEN
Solar/Wind Harmer
1.918
3147623JAMES R
Solar/Wind Harmer
0.237
315693AD1-088 GEN
Solar/Wind Harmer
7.599
316237AB2-079_GEN
Solar/Wind Harmer
0.453
3143526WINTERP
Solar/Wind Harmer
-0.071
957481AF2-042 GEN
Solar/Wind Harmer
38.757
970401AG2-262 GEN
Solar/Wind Harmer
0.805
315687AD1-152 GEN
Solar/Wind Harmer
1.355
3147043LAWRENC
Adder
0.898
971065AG2-659 GEN
Solar/Wind Harmer
5.572
316129AC1-054 GEN
Solar/Wind Harmer
0.96
971795AH1-408 GEN
Solar/Wind Harmer
7.936
3150851SPRUNCC
Adder
0.417
316003AC1-222 GEN
Solar/Wind Harmer
0.924
960081AF2-299 GEN
Solar/Wind Harmer
1.049
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3142543TWELFTH
Solar/Wind Harmer
-0.001
970919AG2-571 GEN
Solar/Wind Harmer
2.65
970087AG2-069 GEN
Solar/Wind Harmer
7.82
316023GEN1_S
Solar/Wind Harmer
0.554
940641AE2-051 GEN
Solar/Wind Harmer
7.517
3143096IRON208
Adder
0.298
3146263WOODLND
Solar/Wind Harmer
-0.008
316011AB1-132 GEN
Solar/Wind Harmer
1.653
962571AG1-106 GEN
Solar/Wind Harmer
1.136
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
939411AE1-173 GEN
Solar/Wind Harmer
38.95
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315671AE2-027_GEN
Solar/Wind Harmer
5.803
316212AC1-099_GEN
Solar/Wind Harmer
0.674
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
970659AG2-427 GEN
Solar/Wind Harmer
4.029
316381AD1-082 GEN
Solar/Wind Harmer
0.694
970661AG2-428 GEN
Solar/Wind Harmer
7.982
315722AD1-056 GEN
Solar/Wind Harmer
0.771
970129AG2-093 GEN
Solar/Wind Harmer
1.678
316458AB2-190 GEN2
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.827
3146233WITAKRS
Solar/Wind Harmer
-0.029
971069AG2-661 GEN
Solar/Wind Harmer
1.154
316093AE2-104_GEN
Solar/Wind Harmer
2.113
944631AF1-128 GEN
Adder
30.658
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.772
971647AH1-324 GEN
Solar/Wind Harmer
3.605
3130156CHOWAN
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.775
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.535
316246AF1-032 C
Solar/Wind Harmer
0.145
3145963POPLR C
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
316174AB2-169 GEN
Solar/Wind Harmer
1.097
3151171GRAVELC
Adder
0.673
316375AC2-012 GEN
Solar/Wind Harmer
2.457
3145336SMITFLD
Solar/Wind Harmer
-0.028
3150981CHESPKA
Adder
0.789
944591AF1-124 GEN
Solar/Wind Harmer
32.38
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.798
3147666LOUISA
Solar/Wind Helper
0.46
972205AH1-687 GEN
50/50
22.442
316303AF2-085
50/50
2.627
971845AH1-439 GEN
Solar/Wind Harmer
23.203
970285AG2-188 GEN
Solar/Wind Harmer
36.921
315657AE1-056 GEN
Solar/Wind Harmer
9.87
946301AF1-294 GEN
Solar/Wind Harmer
6.363
961791AG1-021 GEN
Solar/Wind Harmer
3.104
970683AG2-441 GEN
Solar/Wind Harmer
17.731
970681AG2-440 GEN
Solar/Wind Harmer
14.185
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.983
316239AB2-077_GEN
Solar/Wind Harmer
0.453
316238AB2-078_GEN
Solar/Wind Harmer
0.453
316233AE1-074 FULL
Solar/Wind Harmer
0.37
971281AH1-106 GEN
Solar/Wind Harmer
2.234
971283AH1-107 GEN
Solar/Wind Harmer
2.234
270494AE1-108_GEN
Solar/Wind Harmer
3.125
316118AC1-105 GEN
Solar/Wind Harmer
0.772
970831AG2-522 GEN
Solar/Wind Harmer
5.366
971285AH1-108 GEN
Adder
0.682
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.209
971967AH1-528 GEN
Solar/Wind Harmer
17.53
316087AB2-174 GEN
Solar/Wind Harmer
1.303
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970673AG2-436 GEN
Solar/Wind Harmer
17.985
970673AG2-436 GEN
Solar/Wind Harmer
9.106
941031AE2-094 GEN
Solar/Wind Harmer
15.864
944011AF1-069 GEN
Solar/Wind Harmer
4.971
315607AA1-063A GEN
Solar/Wind Harmer
0.854
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.213
970581AG2-369 GEN
Solar/Wind Harmer
4.483
970865AG2-541 GEN
Solar/Wind Harmer
3.349
315814AE2-033 C
Solar/Wind Harmer
7.587
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.711
3143316POE
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
8.889
316318V4-068
Solar/Wind Harmer
0.196
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315833AF1-017_GEN
Solar/Wind Harmer
1.402
316349AD2-085 GEN
Solar/Wind Harmer
0.657
971447AH1-217 GEN
Solar/Wind Harmer
2.63
316311AC2-079 GEN
Solar/Wind Harmer
3.722
316132AB2-190 GEN1
Solar/Wind Harmer
0.743
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.197
316319Z2-044 C
Solar/Wind Harmer
0.403
315835AF2-110_GEN
Solar/Wind Harmer
0.908
316369SG1_INVT
Solar/Wind Harmer
1.296
315732AD1-074 GEN1
Solar/Wind Harmer
1.466
315733AD1-074 GEN2
Solar/Wind Harmer
1.466
315735AD1-075 GEN1
Solar/Wind Harmer
0.733
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.585
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.775
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316305AF2-043 C
Solar/Wind Harmer
0.216
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
313526AB2-022
Solar/Wind Harmer
0.193
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.602
3151191GRAVEL3
Adder
4.544
3151211GRAVEL5
Adder
4.544
3152611GOSPORTB
Adder
0.805
3152621GOSPORTC
Adder
0.683
3152601GOSPORTA
Adder
0.63
971445AH1-216 GEN
Solar/Wind Harmer
4.395
3151081ELIZAR1
Adder
5.792
3151091ELIZAR2
Adder
5.691
3142433PROV 92
Adder
0.112
3142433PROV 92
Adder
0.112
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.103
3148013FISHERV
Solar/Wind Helper
0.098
3148463FAIRFLD
Solar/Wind Helper
0.118
3144293JTRSVLE
50/50
0.746
3144293JTRSVLE
50/50
0.629
970535AG2-341 GEN
50/50
2.158
3146776BUCKING
Solar/Wind Harmer
-0.177
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
13.372
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
958211AF2-115 GEN
Solar/Wind Harmer
3.88
963191AG1-168 GEN
Solar/Wind Harmer
2.328
971741AH1-377 GEN
Solar/Wind Harmer
28.01
316034AC1-036 C
Solar/Wind Harmer
0.38
970323AG2-213 GEN
Solar/Wind Harmer
10.214
971775AH1-396 GEN
Solar/Wind Harmer
1.455
971223AH1-071 GEN
Solar/Wind Harmer
2.076
313527AB2-043 GEN
Solar/Wind Harmer
2.493
971489AH1-241 GEN
Solar/Wind Harmer
9.104
3143526WINTERP
Solar/Wind Harmer
-0.071
962561AG1-105 GEN
Solar/Wind Harmer
7.195
939181AE1-148 GEN
Solar/Wind Harmer
7.148
970099AG2-077 GEN
Solar/Wind Harmer
15.503
964791AG1-342 GEN
Solar/Wind Harmer
2.634
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970933AG2-581 GEN
Solar/Wind Harmer
9.649
316181AB2-040 GEN
Solar/Wind Harmer
1.262
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.983
3145593CAROLNA
Solar/Wind Harmer
0.073
972187AH1-678 GEN
Adder
2.2
972185AH1-677 GEN
Adder
4.302
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316274AC1-208 GEN
Solar/Wind Harmer
0.849
316240AF1-291 C
Solar/Wind Harmer
0.235
944641AF1-129 GEN
Adder
33.028
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.793
970657AG2-426 GEN
Solar/Wind Harmer
2.358
970657AG2-426 GEN
Solar/Wind Harmer
0.493
316065AD1-022 GEN
Solar/Wind Harmer
3.643
316033AB2-134 GEN
Solar/Wind Harmer
2.34
315697AD1-025 GEN
Solar/Wind Harmer
1.468
3142366NRTHEST
Adder
0.21
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.298
316433W1029_GEN2
Solar/Wind Harmer
1.298
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316222AC1-221 GEN
Solar/Wind Harmer
0.722
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3142956BIRDNECK
Solar/Wind Harmer
0.381
316316AC1-027 C
Solar/Wind Harmer
0.218
316236AE1-162_GEN
Solar/Wind Harmer
0.214
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.662
3150991CHESPKB
Adder
0.646
3150691DARBY 3
Adder
4.502
3150701DARBY 4
Adder
4.491
3150681DARBY 2
Adder
4.486
3150671DARBY 1
Adder
4.481
966001AG1-469 GEN
Solar/Wind Helper
0.186
NYPJM->LTFIMP_NY
CLTF
0.536
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.012
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.013
LGEELTFEXP_LGEE->PJM
CLTF
0.012
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.774
TVALTFEXP_TVA->PJM
CLTF
0.758
CPLELTFEXP_CPLE->PJM
CLTF
3.992
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.116
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.345
MECLTFEXP_MEC->PJM
CLTF
0.252
SIGELTFEXP_SIGE->PJM
CLTF
0.005

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:129.14 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1071.9
MW Contribution:3.95
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
6.456
3151911BEARGRDN G1
50/50
5.002
3144293JTRSVLE
50/50
0.78
972003AH1-546 GEN
Solar/Wind Harmer
29.014
970937AG2-583 GEN
Solar/Wind Harmer
35.582
316322AB2-045
Solar/Wind Harmer
1.612
3146776BUCKING
Solar/Wind Harmer
-0.019
3146926FARMVIL
Solar/Wind Harmer
-0.022
316336AC2-165 C
Solar/Wind Harmer
6.353
3143336POWHATN
Solar/Wind Harmer
3.74
963171AG1-166 GEN
Solar/Wind Harmer
3.245
971563AH1-280 GEN
Solar/Wind Harmer
3.245
970685AG2-442 GEN
Solar/Wind Harmer
20.625
962491AG1-098 GEN
Solar/Wind Harmer
10.531
315693AD1-088 GEN
Solar/Wind Harmer
7.538
316237AB2-079_GEN
Solar/Wind Harmer
0.452
3143226MDLTHAN
Solar/Wind Harmer
-0.012
970401AG2-262 GEN
Solar/Wind Harmer
0.785
957481AF2-042 GEN
Solar/Wind Harmer
37.275
315687AD1-152 GEN
Solar/Wind Harmer
1.296
971065AG2-659 GEN
Solar/Wind Harmer
5.329
3147043LAWRENC
Adder
0.854
316129AC1-054 GEN
Solar/Wind Harmer
0.915
3143526WINTERP
Solar/Wind Harmer
-0.053
971795AH1-408 GEN
Solar/Wind Harmer
7.462
316003AC1-222 GEN
Solar/Wind Harmer
0.864
960081AF2-299 GEN
Solar/Wind Harmer
0.959
3150851SPRUNCC
Adder
0.323
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
972205AH1-687 GEN
50/50
24.399
971845AH1-439 GEN
Solar/Wind Harmer
25.003
970285AG2-188 GEN
Solar/Wind Harmer
39.727
315657AE1-056 GEN
Solar/Wind Harmer
10.359
946301AF1-294 GEN
Solar/Wind Harmer
6.652
961791AG1-021 GEN
Solar/Wind Harmer
3.245
970683AG2-441 GEN
Solar/Wind Harmer
18.415
970681AG2-440 GEN
Solar/Wind Harmer
14.732
3144303KENBRDG
Solar/Wind Harmer
-0.017
971443AH1-215 GEN
Solar/Wind Harmer
4.098
316239AB2-077_GEN
Solar/Wind Harmer
0.452
316238AB2-078_GEN
Solar/Wind Harmer
0.452
316118AC1-105 GEN
Solar/Wind Harmer
0.743
316233AE1-074 FULL
Solar/Wind Harmer
0.277
971281AH1-106 GEN
Solar/Wind Harmer
1.674
971283AH1-107 GEN
Solar/Wind Harmer
1.674
970831AG2-522 GEN
Solar/Wind Harmer
5.097
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.191
971967AH1-528 GEN
Solar/Wind Harmer
15.717
316087AB2-174 GEN
Solar/Wind Harmer
1.189
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971285AH1-108 GEN
Adder
0.528
315607AA1-063A GEN
Solar/Wind Harmer
0.769
3146043SEABORD
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
15.733
970673AG2-436 GEN
Solar/Wind Harmer
7.966
970865AG2-541 GEN
Solar/Wind Harmer
3.042
941031AE2-094 GEN
Solar/Wind Harmer
13.777
944011AF1-069 GEN
Solar/Wind Harmer
4.317
970085AG2-068 GEN
Solar/Wind Harmer
4.591
970581AG2-369 GEN
Solar/Wind Harmer
3.948
965291AG1-394 GEN
Solar/Wind Harmer
0.631
315814AE2-033 C
Solar/Wind Harmer
6.526
316315AB2-025 C
Solar/Wind Harmer
0.189
315652AC1-086 GEN
Solar/Wind Harmer
7.864
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.027
3145513AHOSKIE
Solar/Wind Harmer
0.059
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3143316POE
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.356
3146206CASHIE
Solar/Wind Harmer
-0.006
970601AG2-382 GEN
Solar/Wind Harmer
2.783
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.164
3148013FISHERV
Solar/Wind Helper
0.157
3148463FAIRFLD
Solar/Wind Helper
0.142
3151921BEARGRDN G2
50/50
5.002
3144293JTRSVLE
50/50
0.78
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.022
942461AE2-259 GEN
Solar/Wind Harmer
4.861
316313AB2-026
Solar/Wind Harmer
0.85
316258AE1-075 C
Solar/Wind Harmer
0.765
316405AF2-144 C
Solar/Wind Harmer
0.807
3143336POWHATN
Solar/Wind Harmer
3.179
970909AG2-566 GEN
Solar/Wind Harmer
2.663
3147133PAMPLIN
Solar/Wind Harmer
-0.086
971193AH1-056 GEN
Solar/Wind Harmer
17.264
963181AG1-167 GEN
Solar/Wind Harmer
2.434
959311AF2-222 GEN
Solar/Wind Harmer
22.717
970257AG2-171 GEN
Solar/Wind Harmer
7.889
315785AD2-033 C
Solar/Wind Harmer
4.54
964241AG1-285 GEN
Solar/Wind Harmer
13.569
316131AB2-060 GEN
Solar/Wind Harmer
1.699
316478AD1-087 GEN
Solar/Wind Harmer
1.036
316486AD2-202 GEN
Solar/Wind Harmer
0.304
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.29
960061AF2-297 GEN
Solar/Wind Harmer
4.81
966621AG1-532 GEN
Solar/Wind Harmer
0.173
313506AB2-031 GEN
Solar/Wind Harmer
0.663
971683AH1-343 GEN
Solar/Wind Harmer
3.528
3150861SPRUNCD
Adder
0.323
970917AG2-570 GEN
Solar/Wind Harmer
18.441
316365GEN2_N
Solar/Wind Harmer
0.488
3156081AA2-088 GEN
Solar/Wind Harmer
2.294
3146263WOODLND
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.463
961681AG1-008 GEN
Solar/Wind Harmer
5.463
316210AC1-098 GEN
Solar/Wind Harmer
1.08
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
962331AG1-082 GEN
Solar/Wind Harmer
0.846
316317KELFORD C
Solar/Wind Harmer
0.319
3145823KELFORD
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.671
315724AD1-057 GEN
Solar/Wind Harmer
0.374
315839AE2-212 C
Solar/Wind Harmer
0.195
3145273HOLLAND
Solar/Wind Harmer
-0.005
3156021HOLLOMANSOL
Solar/Wind Harmer
0.87
3146233WITAKRS
Solar/Wind Harmer
0.135
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
4.015
965281AG1-393 GEN
Solar/Wind Harmer
0.8
3143096IRON208
Adder
0.238
3143096IRON208
Adder
0.233
970659AG2-427 GEN
Solar/Wind Harmer
0.6
316083AB2-161 GEN
Solar/Wind Harmer
1.033
3146206CASHIE
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.599
970661AG2-428 GEN
Solar/Wind Harmer
1.194
3148013FISHERV
Solar/Wind Helper
0.273
316499AE2-029_GEN
Solar/Wind Helper
0.588
315616AA1-038_C
Solar/Wind Helper
0.641
3132273ORANGE
Solar/Wind Helper
0.023
3144293JTRSVLE
50/50
0.78
3144293JTRSVLE
50/50
0.657
970535AG2-341 GEN
50/50
2.128
3146776BUCKING
Solar/Wind Harmer
-0.191
3146776BUCKING
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
14.025
3147133PAMPLIN
Solar/Wind Harmer
-0.028
3147133PAMPLIN
Solar/Wind Harmer
-0.022
958211AF2-115 GEN
Solar/Wind Harmer
4.056
963191AG1-168 GEN
Solar/Wind Harmer
2.434
971741AH1-377 GEN
Solar/Wind Harmer
29.148
316034AC1-036 C
Solar/Wind Harmer
0.391
970323AG2-213 GEN
Solar/Wind Harmer
10.518
971775AH1-396 GEN
Solar/Wind Harmer
1.498
313527AB2-043 GEN
Solar/Wind Harmer
2.495
962561AG1-105 GEN
Solar/Wind Harmer
7.049
939181AE1-148 GEN
Solar/Wind Harmer
6.984
971223AH1-071 GEN
Solar/Wind Harmer
1.533
964791AG1-342 GEN
Solar/Wind Harmer
2.568
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.91
3143526WINTERP
Solar/Wind Harmer
-0.053
970933AG2-581 GEN
Solar/Wind Harmer
8.884
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.893
3145593CAROLNA
Solar/Wind Harmer
0.066
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.779
972187AH1-678 GEN
Adder
1.94
972185AH1-677 GEN
Adder
3.777
316274AC1-208 GEN
Solar/Wind Harmer
0.758
3144356SAPONY
Solar/Wind Harmer
0.244
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.021
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.691
316222AC1-221 GEN
Solar/Wind Harmer
0.652
316240AF1-291 C
Solar/Wind Harmer
0.193
944641AF1-129 GEN
Adder
26.988
970657AG2-426 GEN
Solar/Wind Harmer
1.987
970657AG2-426 GEN
Solar/Wind Harmer
0.415
316065AD1-022 GEN
Solar/Wind Harmer
3.168
315821AE2-092 GEN
Solar/Wind Helper
6.532
966001AG1-469 GEN
Solar/Wind Helper
0.168
3132123MT JACKSON
Solar/Wind Helper
0.376
970919AG2-571 GEN
Solar/Wind Harmer
2.334
970087AG2-069 GEN
Solar/Wind Harmer
6.886
316023GEN1_S
Solar/Wind Harmer
0.488
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.463
962571AG1-106 GEN
Solar/Wind Harmer
1.005
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
316212AC1-099_GEN
Solar/Wind Harmer
0.6
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
940641AE2-051 GEN
Solar/Wind Harmer
6.428
3146173TUNIS
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
3145683EARLEYS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
33.3
315722AD1-056 GEN
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.238
970659AG2-427 GEN
Solar/Wind Harmer
3.387
316381AD1-082 GEN
Solar/Wind Harmer
0.584
315671AE2-027_GEN
Solar/Wind Harmer
4.776
3146206CASHIE
Solar/Wind Harmer
-0.006
971547AH1-271 GEN
Solar/Wind Harmer
1.59
970661AG2-428 GEN
Solar/Wind Harmer
6.738
3147983MERCK5
Solar/Wind Helper
0.064
NYPJM->LTFIMP_NY
CLTF
0.338
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.543
LAGNLTFEXP_LAGN->PJM
CLTF
0.85
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.313
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.396
CPLELTFEXP_CPLE->PJM
CLTF
3.425
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.931
MDUPJM->LTFIMP_MDU
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.127
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.049

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.86 %
Rating:678.68 MVA
Rating Type:A
MVA to Mitigate:765.97
MW Contribution:2.63
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.69
3144293JTRSVLE
50/50
0.581
970535AG2-341 GEN
50/50
1.885
3152661PLYWOOD A
50/50
0.185
3151041BRUNSWICKG3
50/50
0.785
972187AH1-678 GEN
50/50
1.802
315242AE2-183_GT2
50/50
0.972
315241AE2-183_GT1
50/50
0.966
972185AH1-677 GEN
50/50
3.505
970533AG2-339 GEN
50/50
5.074
970531AG2-338 GEN
50/50
2.029
3146776BUCKING
Solar/Wind Harmer
1.508
3146776BUCKING
Solar/Wind Harmer
0.122
970301AG2-198 GEN
Solar/Wind Harmer
9.412
3147133PAMPLIN
Solar/Wind Harmer
0.217
3147133PAMPLIN
Solar/Wind Harmer
0.174
958211AF2-115 GEN
Solar/Wind Harmer
2.452
963191AG1-168 GEN
Solar/Wind Harmer
0.817
971741AH1-377 GEN
Solar/Wind Harmer
19.558
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
7.069
971775AH1-396 GEN
Solar/Wind Harmer
0.265
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971489AH1-241 GEN
Solar/Wind Harmer
6.362
962561AG1-105 GEN
Solar/Wind Harmer
4.763
939181AE1-148 GEN
Solar/Wind Harmer
4.697
971223AH1-071 GEN
Solar/Wind Harmer
1.017
964791AG1-342 GEN
Solar/Wind Harmer
1.83
3146843MT LREL
Solar/Wind Harmer
0.095
3146843MT LREL
Solar/Wind Harmer
0.095
970099AG2-077 GEN
Solar/Wind Harmer
9.986
3143526WINTERP
Solar/Wind Harmer
0.415
970933AG2-581 GEN
Solar/Wind Harmer
5.925
316181AB2-040 GEN
Solar/Wind Harmer
0.094
3145593CAROLNA
Solar/Wind Harmer
0.062
3145593CAROLNA
Solar/Wind Harmer
0.062
966811AG1-552 GEN
Solar/Wind Harmer
0.675
3145593CAROLNA
Solar/Wind Harmer
0.077
3145783HORNRTN
Solar/Wind Harmer
1.086
3145783HORNRTN
Solar/Wind Harmer
0.869
3145783HORNRTN
Solar/Wind Harmer
0.271
3145783HORNRTN
Solar/Wind Harmer
0.109
316426AA2-053 GEN
Solar/Wind Harmer
0.204
966001AG1-469 GEN
Solar/Wind Helper
0.174
3151931BEARGRDN S1
50/50
5.707
3151911BEARGRDN G1
50/50
4.422
3144293JTRSVLE
50/50
0.69
970119AG2-088 GEN
50/50
12.707
3151531CLOVER1
50/50
2.017
3151601KERR 3
50/50
0.192
3151581KERR 1
50/50
0.069
3147043LAWRENC
50/50
0.8
3151261ROARAP2
50/50
0.077
3150851SPRUNCC
50/50
0.297
3151051BRUNSWICKS1
50/50
1.63
3151021BRUNSWICKG1
50/50
0.785
971451AH1-221 GEN
50/50
2.385
315243AE2-183_GT3
50/50
0.972
972003AH1-546 GEN
Solar/Wind Harmer
19.447
970937AG2-583 GEN
Solar/Wind Harmer
23.874
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.151
3146926FARMVIL
Solar/Wind Harmer
0.178
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.396
963171AG1-166 GEN
Solar/Wind Harmer
1.09
971563AH1-280 GEN
Solar/Wind Harmer
2.18
970685AG2-442 GEN
Solar/Wind Harmer
13.857
962491AG1-098 GEN
Solar/Wind Harmer
7.06
971377AH1-170 GEN
Solar/Wind Harmer
1.272
3147623JAMES R
Solar/Wind Harmer
0.276
3151921BEARGRDN G2
50/50
4.422
3144293JTRSVLE
50/50
0.69
970413AG2-270 GEN
50/50
8.802
3151591KERR 2
50/50
0.192
3151261ROARAP2
50/50
0.076
3150861SPRUNCD
50/50
0.297
3151031BRUNSWICKG2
50/50
0.785
3146776BUCKING
Solar/Wind Harmer
0.136
3146926FARMVIL
Solar/Wind Harmer
0.178
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.156
316258AE1-075 C
Solar/Wind Harmer
0.187
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.737
970909AG2-566 GEN
Solar/Wind Harmer
2.353
3147133PAMPLIN
Solar/Wind Harmer
0.682
971193AH1-056 GEN
Solar/Wind Harmer
13.238
963181AG1-167 GEN
Solar/Wind Harmer
0.817
959311AF2-222 GEN
Solar/Wind Harmer
15.236
970257AG2-171 GEN
Solar/Wind Harmer
5.302
315785AD2-033 C
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
9.125
972205AH1-687 GEN
50/50
21.569
316303AF2-085
50/50
1.694
3151541CLOVER2
50/50
2.007
3151611KERR 4
50/50
0.192
3151621KERR 5
50/50
0.192
3151631KERR 6
50/50
0.192
3151641KERR 7
50/50
0.192
3151281ROARAP4
50/50
0.075
3151281ROARAP4
50/50
0.07
971285AH1-108 GEN
50/50
0.486
963041AG1-153 GEN
50/50
1.59
315244AE2-183_ST
50/50
1.681
971845AH1-439 GEN
Solar/Wind Harmer
16.786
970285AG2-188 GEN
Solar/Wind Harmer
28.258
315657AE1-056 GEN
Solar/Wind Harmer
7.498
946301AF1-294 GEN
Solar/Wind Harmer
4.032
961791AG1-021 GEN
Solar/Wind Harmer
1.962
970683AG2-441 GEN
Solar/Wind Harmer
12.373
970681AG2-440 GEN
Solar/Wind Harmer
9.898
3144303KENBRDG
Solar/Wind Harmer
0.132
971443AH1-215 GEN
Solar/Wind Harmer
2.755
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
270494AE1-108_GEN
Solar/Wind Harmer
1.107
316118AC1-105 GEN
Solar/Wind Harmer
0.222
970831AG2-522 GEN
Solar/Wind Harmer
3.422
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971281AH1-106 GEN
Solar/Wind Harmer
1.107
971283AH1-107 GEN
Solar/Wind Harmer
1.107
3147173SINAI
Solar/Wind Harmer
0.077
3147243WELCO
Solar/Wind Harmer
0.048
316087AB2-174 GEN
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
10.427
3137643SOCKMAN
Solar/Wind Harmer
0.253
970865AG2-541 GEN
Solar/Wind Harmer
2.127
315607AA1-063A GEN
Solar/Wind Harmer
0.122
3146043SEABORD
Solar/Wind Harmer
0.059
970673AG2-436 GEN
Solar/Wind Harmer
12.427
970673AG2-436 GEN
Solar/Wind Harmer
8.285
970085AG2-068 GEN
Solar/Wind Harmer
3.058
970581AG2-369 GEN
Solar/Wind Harmer
2.63
941031AE2-094 GEN
Solar/Wind Harmer
10.513
944011AF1-069 GEN
Solar/Wind Harmer
3.435
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.124
316131AB2-060 GEN
Solar/Wind Harmer
0.39
970221AG2-151 GEN
Solar/Wind Harmer
6.362
316478AD1-087 GEN
Solar/Wind Harmer
0.328
316486AD2-202 GEN
Solar/Wind Harmer
0.096
3147043LAWRENC
Solar/Wind Harmer
0.05
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.274
971683AH1-343 GEN
Solar/Wind Harmer
2.442
313506AB2-031 GEN
Solar/Wind Harmer
0.2
970917AG2-570 GEN
Solar/Wind Harmer
5.117
316365GEN2_N
Solar/Wind Harmer
0.127
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.562
3132273ORANGE
Solar/Wind Helper
0.024
315693AD1-088 GEN
Solar/Wind Harmer
5.685
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.095
970401AG2-262 GEN
Solar/Wind Harmer
0.559
957481AF2-042 GEN
Solar/Wind Harmer
24.966
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
3.579
316129AC1-054 GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Harmer
0.415
971795AH1-408 GEN
Solar/Wind Harmer
5.206
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.641
3145783HORNRTN
Solar/Wind Harmer
0.061
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
4.587
316023GEN1_S
Solar/Wind Harmer
0.127
3147983MERCK5
Solar/Wind Helper
0.057
NYPJM->LTFIMP_NY
CLTF
0.345
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.897
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.783
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.427
CPLELTFEXP_CPLE->PJM
CLTF
3.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.625
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.208

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.65 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:934.97
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.702
3144293JTRSVLE
50/50
0.591
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.577
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.65
963191AG1-168 GEN
Solar/Wind Harmer
2.19
971741AH1-377 GEN
Solar/Wind Harmer
26.202
316034AC1-036 C
Solar/Wind Harmer
0.354
970323AG2-213 GEN
Solar/Wind Harmer
9.526
971775AH1-396 GEN
Solar/Wind Harmer
1.357
313527AB2-043 GEN
Solar/Wind Harmer
2.287
971489AH1-241 GEN
Solar/Wind Harmer
8.033
962561AG1-105 GEN
Solar/Wind Harmer
6.548
939181AE1-148 GEN
Solar/Wind Harmer
6.48
964791AG1-342 GEN
Solar/Wind Harmer
2.393
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.726
971223AH1-071 GEN
Solar/Wind Harmer
1.368
3143526WINTERP
Solar/Wind Harmer
-0.048
970933AG2-581 GEN
Solar/Wind Harmer
8.213
316181AB2-040 GEN
Solar/Wind Harmer
1.084
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.846
3145593CAROLNA
Solar/Wind Harmer
0.062
3145783HORNRTN
Solar/Wind Harmer
0.879
3145783HORNRTN
Solar/Wind Harmer
0.703
3145783HORNRTN
Solar/Wind Harmer
0.22
3145783HORNRTN
Solar/Wind Harmer
0.088
316426AA2-053 GEN
Solar/Wind Harmer
0.74
972187AH1-678 GEN
Adder
1.814
972185AH1-677 GEN
Adder
3.525
316274AC1-208 GEN
Solar/Wind Harmer
0.733
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.184
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.012
316222AC1-221 GEN
Solar/Wind Harmer
0.66
3146173TUNIS
Solar/Wind Harmer
-0.006
3146173TUNIS
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Harmer
0.227
966001AG1-469 GEN
Solar/Wind Helper
0.172
3151921BEARGRDN G2
50/50
4.436
3144293JTRSVLE
50/50
0.702
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.35
316313AB2-026
Solar/Wind Harmer
0.755
316258AE1-075 C
Solar/Wind Harmer
0.68
316405AF2-144 C
Solar/Wind Harmer
0.717
3143336POWHATN
Solar/Wind Harmer
2.824
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.078
971193AH1-056 GEN
Solar/Wind Harmer
15.51
963181AG1-167 GEN
Solar/Wind Harmer
2.19
959311AF2-222 GEN
Solar/Wind Harmer
20.551
970257AG2-171 GEN
Solar/Wind Harmer
7.144
315785AD2-033 C
Solar/Wind Harmer
4.119
964241AG1-285 GEN
Solar/Wind Harmer
12.377
316131AB2-060 GEN
Solar/Wind Harmer
1.556
970221AG2-151 GEN
Solar/Wind Harmer
8.461
316478AD1-087 GEN
Solar/Wind Harmer
0.958
316486AD2-202 GEN
Solar/Wind Harmer
0.28
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.275
960061AF2-297 GEN
Solar/Wind Harmer
4.563
966621AG1-532 GEN
Solar/Wind Harmer
0.162
971683AH1-343 GEN
Solar/Wind Harmer
3.393
313506AB2-031 GEN
Solar/Wind Harmer
0.625
3150861SPRUNCD
Adder
0.29
970917AG2-570 GEN
Solar/Wind Harmer
17.439
316365GEN2_N
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.164
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.044
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.183
961681AG1-008 GEN
Solar/Wind Harmer
5.183
3146173TUNIS
Solar/Wind Harmer
-0.006
316327AA2-057 GEN
Solar/Wind Harmer
0.657
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
316283AC2-100 C
Solar/Wind Harmer
0.608
316463AE2-346 GEN
Solar/Wind Harmer
0.104
316140AB2-099
Solar/Wind Harmer
0.044
962331AG1-082 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
3138543CONSLDL
Solar/Wind Harmer
-0.004
3148013FISHERV
Solar/Wind Helper
0.18
316499AE2-029_GEN
Solar/Wind Helper
0.518
315616AA1-038_C
Solar/Wind Helper
0.568
3132273ORANGE
Solar/Wind Helper
0.023
3151931BEARGRDN S1
50/50
5.725
3151911BEARGRDN G1
50/50
4.436
3144293JTRSVLE
50/50
0.702
972003AH1-546 GEN
Solar/Wind Harmer
25.74
970937AG2-583 GEN
Solar/Wind Harmer
31.567
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.64
3143336POWHATN
Solar/Wind Harmer
3.322
963171AG1-166 GEN
Solar/Wind Harmer
2.92
971563AH1-280 GEN
Solar/Wind Harmer
2.92
970685AG2-442 GEN
Solar/Wind Harmer
18.611
962491AG1-098 GEN
Solar/Wind Harmer
9.593
316237AB2-079_GEN
Solar/Wind Harmer
0.415
315693AD1-088 GEN
Solar/Wind Harmer
6.877
971377AH1-170 GEN
Solar/Wind Harmer
1.692
3147623JAMES R
Solar/Wind Harmer
0.209
970401AG2-262 GEN
Solar/Wind Harmer
0.731
957481AF2-042 GEN
Solar/Wind Harmer
34.315
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.213
971065AG2-659 GEN
Solar/Wind Harmer
4.98
3147043LAWRENC
Adder
0.793
316129AC1-054 GEN
Solar/Wind Harmer
0.856
971795AH1-408 GEN
Solar/Wind Harmer
6.949
3143526WINTERP
Solar/Wind Harmer
-0.048
316003AC1-222 GEN
Solar/Wind Harmer
0.825
960081AF2-299 GEN
Solar/Wind Harmer
0.9
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.09
3150851SPRUNCC
Adder
0.29
970919AG2-571 GEN
Solar/Wind Harmer
2.207
970087AG2-069 GEN
Solar/Wind Harmer
6.521
316023GEN1_S
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.4
962571AG1-106 GEN
Solar/Wind Harmer
0.962
316212AC1-099_GEN
Solar/Wind Harmer
0.58
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.006
3145823KELFORD
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
315722AD1-056 GEN
Solar/Wind Harmer
0.666
940641AE2-051 GEN
Solar/Wind Harmer
5.935
3147983MERCK5
Solar/Wind Helper
0.057
972205AH1-687 GEN
50/50
21.638
971845AH1-439 GEN
Solar/Wind Harmer
22.236
970285AG2-188 GEN
Solar/Wind Harmer
35.347
315657AE1-056 GEN
Solar/Wind Harmer
9.306
946301AF1-294 GEN
Solar/Wind Harmer
5.986
961791AG1-021 GEN
Solar/Wind Harmer
2.92
970683AG2-441 GEN
Solar/Wind Harmer
16.617
970681AG2-440 GEN
Solar/Wind Harmer
13.294
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.713
316239AB2-077_GEN
Solar/Wind Harmer
0.415
316238AB2-078_GEN
Solar/Wind Harmer
0.415
270494AE1-108_GEN
Solar/Wind Harmer
2.712
316118AC1-105 GEN
Solar/Wind Harmer
0.698
970831AG2-522 GEN
Solar/Wind Harmer
4.772
316233AE1-074 FULL
Solar/Wind Harmer
0.248
971281AH1-106 GEN
Solar/Wind Harmer
1.497
971283AH1-107 GEN
Solar/Wind Harmer
1.497
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
946281AF1-292 GEN
Solar/Wind Harmer
0.179
316087AB2-174 GEN
Solar/Wind Harmer
1.119
971967AH1-528 GEN
Solar/Wind Harmer
14.578
3137643SOCKMAN
Solar/Wind Harmer
-0.03
970865AG2-541 GEN
Solar/Wind Harmer
2.95
315607AA1-063A GEN
Solar/Wind Harmer
0.728
3146043SEABORD
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.475
970673AG2-436 GEN
Solar/Wind Harmer
14.663
970673AG2-436 GEN
Solar/Wind Harmer
7.425
970085AG2-068 GEN
Solar/Wind Harmer
4.347
970581AG2-369 GEN
Solar/Wind Harmer
3.738
941031AE2-094 GEN
Solar/Wind Harmer
12.804
944011AF1-069 GEN
Solar/Wind Harmer
4.012
965291AG1-394 GEN
Solar/Wind Harmer
0.596
315652AC1-086 GEN
Solar/Wind Harmer
7.525
316318V4-068
Solar/Wind Harmer
0.165
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
315814AE2-033 C
Solar/Wind Harmer
6.071
316315AB2-025 C
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
0.056
961941AG1-037 GEN
Solar/Wind Harmer
0.049
3145513AHOSKIE
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.006
3145683EARLEYS
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.351
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.108
3148013FISHERV
Solar/Wind Helper
0.103
3148463FAIRFLD
Solar/Wind Helper
0.125
NYPJM->LTFIMP_NY
CLTF
0.342
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.137
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.398
LAGNLTFEXP_LAGN->PJM
CLTF
1.413
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.319
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.666
CPLELTFEXP_CPLE->PJM
CLTF
3.817
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.59
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.933
MECLTFEXP_MEC->PJM
CLTF
0.009

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2066-282_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2066-282_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.36 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:916.0
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.7
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.388
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.482
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.337
970257AG2-171 GEN
Solar/Wind Harmer
7.06
315785AD2-033 C
Solar/Wind Harmer
4.062
964241AG1-285 GEN
Solar/Wind Harmer
12.123
970221AG2-151 GEN
Solar/Wind Harmer
8.911
316131AB2-060 GEN
Solar/Wind Harmer
1.517
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.339
971683AH1-343 GEN
Solar/Wind Harmer
3.24
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.142
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
21.959
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.482
970285AG2-188 GEN
Solar/Wind Harmer
35.716
315657AE1-056 GEN
Solar/Wind Harmer
9.289
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.495
970681AG2-440 GEN
Solar/Wind Harmer
13.196
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.668
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.875
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.476
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.768
946281AF1-292 GEN
Solar/Wind Harmer
0.164
316087AB2-174 GEN
Solar/Wind Harmer
1.019
970865AG2-541 GEN
Solar/Wind Harmer
2.825
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.019
970581AG2-369 GEN
Solar/Wind Harmer
3.457
941031AE2-094 GEN
Solar/Wind Harmer
11.99
944011AF1-069 GEN
Solar/Wind Harmer
3.757
971447AH1-217 GEN
Solar/Wind Harmer
2.264
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.7
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.575
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.636
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.113
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.413
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.46
971223AH1-071 GEN
Solar/Wind Harmer
1.732
313527AB2-043 GEN
Solar/Wind Harmer
2.226
962561AG1-105 GEN
Solar/Wind Harmer
6.315
939181AE1-148 GEN
Solar/Wind Harmer
6.206
964791AG1-342 GEN
Solar/Wind Harmer
2.303
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.238
970933AG2-581 GEN
Solar/Wind Harmer
7.823
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.696
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.297
966001AG1-469 GEN
Solar/Wind Helper
0.17
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.7
970119AG2-088 GEN
50/50
16.441
972003AH1-546 GEN
Solar/Wind Harmer
26.109
970937AG2-583 GEN
Solar/Wind Harmer
32.485
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.475
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.39
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.718
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
33.096
315687AD1-152 GEN
Solar/Wind Harmer
1.157
971065AG2-659 GEN
Solar/Wind Harmer
4.696
3147043LAWRENC
Adder
0.745
316129AC1-054 GEN
Solar/Wind Harmer
0.805
971795AH1-408 GEN
Solar/Wind Harmer
6.476
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.043
970087AG2-069 GEN
Solar/Wind Harmer
6.029
3147983MERCK5
Solar/Wind Helper
0.056
NYPJM->LTFIMP_NY
CLTF
0.338
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.108
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.318
LAGNLTFEXP_LAGN->PJM
CLTF
0.917
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.775
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.437
CPLELTFEXP_CPLE->PJM
CLTF
3.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.788
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.251

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 219-282_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 219-282_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.03 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:913.26
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.502
3144293JTRSVLE
50/50
0.699
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.811
316258AE1-075 C
Solar/Wind Harmer
0.73
316405AF2-144 C
Solar/Wind Harmer
0.77
3143336POWHATN
Solar/Wind Harmer
3.032
942461AE2-259 GEN
Solar/Wind Harmer
4.363
970909AG2-566 GEN
Solar/Wind Harmer
2.387
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.48
963181AG1-167 GEN
Solar/Wind Harmer
2.181
959311AF2-222 GEN
Solar/Wind Harmer
20.333
970257AG2-171 GEN
Solar/Wind Harmer
7.059
315785AD2-033 C
Solar/Wind Harmer
4.061
964241AG1-285 GEN
Solar/Wind Harmer
12.12
970221AG2-151 GEN
Solar/Wind Harmer
8.909
316131AB2-060 GEN
Solar/Wind Harmer
1.516
316478AD1-087 GEN
Solar/Wind Harmer
0.922
316486AD2-202 GEN
Solar/Wind Harmer
0.27
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.261
960061AF2-297 GEN
Solar/Wind Harmer
4.337
971683AH1-343 GEN
Solar/Wind Harmer
3.239
966621AG1-532 GEN
Solar/Wind Harmer
0.148
313506AB2-031 GEN
Solar/Wind Harmer
0.568
970917AG2-570 GEN
Solar/Wind Harmer
16.134
3148013FISHERV
Solar/Wind Helper
0.177
316499AE2-029_GEN
Solar/Wind Helper
0.512
315616AA1-038_C
Solar/Wind Helper
0.557
3132273ORANGE
Solar/Wind Helper
0.023
972205AH1-687 GEN
50/50
21.958
316303AF2-085
50/50
2.192
971845AH1-439 GEN
Solar/Wind Harmer
22.48
970285AG2-188 GEN
Solar/Wind Harmer
35.714
315657AE1-056 GEN
Solar/Wind Harmer
9.288
946301AF1-294 GEN
Solar/Wind Harmer
5.962
961791AG1-021 GEN
Solar/Wind Harmer
2.908
970683AG2-441 GEN
Solar/Wind Harmer
16.493
970681AG2-440 GEN
Solar/Wind Harmer
13.194
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.667
316233AE1-074 FULL
Solar/Wind Harmer
0.373
971281AH1-106 GEN
Solar/Wind Harmer
2.251
971283AH1-107 GEN
Solar/Wind Harmer
2.251
316239AB2-077_GEN
Solar/Wind Harmer
0.403
316238AB2-078_GEN
Solar/Wind Harmer
0.403
270494AE1-108_GEN
Solar/Wind Harmer
2.874
316118AC1-105 GEN
Solar/Wind Harmer
0.668
970831AG2-522 GEN
Solar/Wind Harmer
4.474
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
971967AH1-528 GEN
Solar/Wind Harmer
13.762
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.018
970865AG2-541 GEN
Solar/Wind Harmer
2.824
3137643SOCKMAN
Solar/Wind Harmer
-0.028
970673AG2-436 GEN
Solar/Wind Harmer
13.713
970673AG2-436 GEN
Solar/Wind Harmer
6.943
315607AA1-063A GEN
Solar/Wind Harmer
0.655
3146043SEABORD
Solar/Wind Harmer
-0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.017
970581AG2-369 GEN
Solar/Wind Harmer
3.455
941031AE2-094 GEN
Solar/Wind Harmer
11.984
944011AF1-069 GEN
Solar/Wind Harmer
3.755
971447AH1-217 GEN
Solar/Wind Harmer
2.263
3138266HYDRAULIC
Solar/Wind Helper
0.019
3138266HYDRAULIC
Solar/Wind Helper
0.012
3148133STUARTS
Solar/Wind Helper
0.106
3148013FISHERV
Solar/Wind Helper
0.102
3148463FAIRFLD
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.589
3146776BUCKING
Solar/Wind Harmer
-0.172
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.574
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.635
963191AG1-168 GEN
Solar/Wind Harmer
2.181
971741AH1-377 GEN
Solar/Wind Harmer
26.109
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.412
971775AH1-396 GEN
Solar/Wind Harmer
1.34
971489AH1-241 GEN
Solar/Wind Harmer
8.458
3143526WINTERP
Solar/Wind Harmer
-0.072
971223AH1-071 GEN
Solar/Wind Harmer
1.731
313527AB2-043 GEN
Solar/Wind Harmer
2.225
962561AG1-105 GEN
Solar/Wind Harmer
6.313
939181AE1-148 GEN
Solar/Wind Harmer
6.204
964791AG1-342 GEN
Solar/Wind Harmer
2.302
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.234
970933AG2-581 GEN
Solar/Wind Harmer
7.82
316181AB2-040 GEN
Solar/Wind Harmer
0.986
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.766
3145593CAROLNA
Solar/Wind Harmer
0.057
972187AH1-678 GEN
Adder
1.695
3145783HORNRTN
Solar/Wind Harmer
0.793
3145783HORNRTN
Solar/Wind Harmer
0.634
3145783HORNRTN
Solar/Wind Harmer
0.198
3145783HORNRTN
Solar/Wind Harmer
0.079
316426AA2-053 GEN
Solar/Wind Harmer
0.667
972185AH1-677 GEN
Adder
3.295
966001AG1-469 GEN
Solar/Wind Helper
0.17
3151931BEARGRDN S1
50/50
5.81
3151911BEARGRDN G1
50/50
4.502
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
16.437
972003AH1-546 GEN
Solar/Wind Harmer
26.108
970937AG2-583 GEN
Solar/Wind Harmer
32.483
316322AB2-045
Solar/Wind Harmer
1.45
3146776BUCKING
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
5.96
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.567
963171AG1-166 GEN
Solar/Wind Harmer
2.908
971563AH1-280 GEN
Solar/Wind Harmer
2.908
970685AG2-442 GEN
Solar/Wind Harmer
18.472
971377AH1-170 GEN
Solar/Wind Harmer
1.782
3147623JAMES R
Solar/Wind Harmer
0.221
962491AG1-098 GEN
Solar/Wind Harmer
9.388
3143526WINTERP
Solar/Wind Harmer
-0.072
3143226MDLTHAN
Solar/Wind Harmer
-0.014
315693AD1-088 GEN
Solar/Wind Harmer
6.716
316237AB2-079_GEN
Solar/Wind Harmer
0.403
970401AG2-262 GEN
Solar/Wind Harmer
0.703
957481AF2-042 GEN
Solar/Wind Harmer
33.086
315687AD1-152 GEN
Solar/Wind Harmer
1.156
971065AG2-659 GEN
Solar/Wind Harmer
4.694
3147043LAWRENC
Adder
0.744
316129AC1-054 GEN
Solar/Wind Harmer
0.804
971795AH1-408 GEN
Solar/Wind Harmer
6.473
316003AC1-222 GEN
Solar/Wind Harmer
0.786
960081AF2-299 GEN
Solar/Wind Harmer
0.821
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.081
970919AG2-571 GEN
Solar/Wind Harmer
2.042
970087AG2-069 GEN
Solar/Wind Harmer
6.026
3147983MERCK5
Solar/Wind Helper
0.056
NYPJM->LTFIMP_NY
CLTF
0.339
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.11
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.323
LAGNLTFEXP_LAGN->PJM
CLTF
0.913
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.768
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.435
CPLELTFEXP_CPLE->PJM
CLTF
3.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.758
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.243

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:177.07 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1012.01
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
3151541CLOVER2
50/50
3.28
3151611KERR 4
50/50
0.314
3151621KERR 5
50/50
0.314
3151631KERR 6
50/50
0.314
3151641KERR 7
50/50
0.314
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.24
315244AE2-183_ST
50/50
2.342
971845AH1-439 GEN
Solar/Wind Harmer
30.733
970285AG2-188 GEN
Solar/Wind Harmer
51.665
315657AE1-056 GEN
Solar/Wind Harmer
13.38
946301AF1-294 GEN
Solar/Wind Harmer
7.167
961791AG1-021 GEN
Solar/Wind Harmer
3.487
970683AG2-441 GEN
Solar/Wind Harmer
21.847
970681AG2-440 GEN
Solar/Wind Harmer
17.477
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.818
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.368
3147173SINAI
Solar/Wind Harmer
0.126
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.363
970865AG2-541 GEN
Solar/Wind Harmer
3.482
971967AH1-528 GEN
Solar/Wind Harmer
15.038
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.358
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.675
970163AG2-111 GEN
Solar/Wind Harmer
0.644
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.164
970673AG2-436 GEN
Solar/Wind Harmer
11.442
941031AE2-094 GEN
Solar/Wind Harmer
14.261
944011AF1-069 GEN
Solar/Wind Harmer
4.66
315652AC1-086 GEN
Solar/Wind Harmer
8.006
3146033SCOT NK
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.231
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.319
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
0.143
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.033
970535AG2-341 GEN
50/50
3.148
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.106
972187AH1-678 GEN
50/50
2.539
315242AE2-183_GT2
50/50
1.355
315241AE2-183_GT1
50/50
1.346
972185AH1-677 GEN
50/50
4.884
970533AG2-339 GEN
50/50
6.883
970531AG2-338 GEN
50/50
2.753
3151361ROSEMG1
50/50
0.26
3151371ROSEMS1
50/50
0.161
3151381ROSEMG2
50/50
0.122
3146776BUCKING
Solar/Wind Harmer
2.762
3146776BUCKING
Solar/Wind Harmer
0.224
970301AG2-198 GEN
Solar/Wind Harmer
16.775
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.358
963191AG1-168 GEN
Solar/Wind Harmer
1.453
971741AH1-377 GEN
Solar/Wind Harmer
34.576
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.374
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
7.996
939181AE1-148 GEN
Solar/Wind Harmer
7.758
964791AG1-342 GEN
Solar/Wind Harmer
3.064
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.138
970933AG2-581 GEN
Solar/Wind Harmer
8.941
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.955
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.535
3145783HORNRTN
Solar/Wind Harmer
1.228
3145783HORNRTN
Solar/Wind Harmer
0.384
3145783HORNRTN
Solar/Wind Harmer
0.153
316426AA2-053 GEN
Solar/Wind Harmer
0.285
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.401
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.043
942751AE2-291 GEN
Solar/Wind Harmer
3.936
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.649
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.224
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.062
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.516
316065AD1-022 GEN
Solar/Wind Harmer
2.802
315742AE1-103 GEN
Solar/Wind Harmer
0.001
315821AE2-092 GEN
Solar/Wind Helper
2.989
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.295
3151601KERR 3
50/50
0.314
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.231
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.296
3151021BRUNSWICKG1
50/50
1.106
971451AH1-221 GEN
50/50
3.36
315243AE2-183_GT3
50/50
1.355
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.276
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.937
971563AH1-280 GEN
Solar/Wind Harmer
3.874
970685AG2-442 GEN
Solar/Wind Harmer
24.468
962491AG1-098 GEN
Solar/Wind Harmer
11.913
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.538
970401AG2-262 GEN
Solar/Wind Harmer
0.936
957481AF2-042 GEN
Solar/Wind Harmer
40.345
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.693
316129AC1-054 GEN
Solar/Wind Harmer
0.488
971795AH1-408 GEN
Solar/Wind Harmer
7.841
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.907
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.909
970087AG2-069 GEN
Solar/Wind Harmer
6.525
316212AC1-099_GEN
Solar/Wind Harmer
0.386
3146263WOODLND
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.323
316023GEN1_S
Solar/Wind Harmer
0.163
962571AG1-106 GEN
Solar/Wind Harmer
1.036
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.285
3145893MURPHYS
Solar/Wind Harmer
0.282
3145893MURPHYS
Solar/Wind Harmer
0.313
315722AD1-056 GEN
Solar/Wind Harmer
0.446
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.25
316049AB1-081 GEN
Solar/Wind Harmer
0.399
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.299
940641AE2-051 GEN
Solar/Wind Harmer
5.379
316494AC1-189 GEN
Solar/Wind Harmer
0.223
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.834
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
971547AH1-271 GEN
Solar/Wind Harmer
1.311
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.625
316336AC2-165 C
Solar/Wind Helper
1.515
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.381
3151591KERR 2
50/50
0.314
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.106
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
3146776BUCKING
Solar/Wind Harmer
0.249
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.194
3147133PAMPLIN
Solar/Wind Harmer
1.217
971193AH1-056 GEN
Solar/Wind Harmer
23.622
963181AG1-167 GEN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
26.742
970257AG2-171 GEN
Solar/Wind Harmer
9.28
315785AD2-033 C
Solar/Wind Harmer
2.237
964241AG1-285 GEN
Solar/Wind Harmer
15.699
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.394
971683AH1-343 GEN
Solar/Wind Harmer
4.007
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.161
970917AG2-570 GEN
Solar/Wind Harmer
7.271
316210AC1-098 GEN
Solar/Wind Harmer
0.691
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.073
316365GEN2_N
Solar/Wind Harmer
0.163
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.289
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.36
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
315724AD1-057 GEN
Solar/Wind Harmer
0.264
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.218
961681AG1-008 GEN
Solar/Wind Harmer
5.218
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.139
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.894
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.024
962331AG1-082 GEN
Solar/Wind Harmer
0.731
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3156021HOLLOMANSOL
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.741
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
315737AD1-076 GEN
Solar/Wind Harmer
0.769
971157AH1-035 GEN
Solar/Wind Harmer
0.714
315614AA2-178 GEN
Solar/Wind Harmer
0.331
3145273HOLLAND
Solar/Wind Harmer
0.043
316313AB2-026
Solar/Wind Helper
0.362
316258AE1-075 C
Solar/Wind Helper
0.326
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3145513AHOSKIE
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.845
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
970181AG2-120 GEN
Solar/Wind Harmer
0.803
315814AE2-033 C
Solar/Wind Harmer
4.928
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.061
970601AG2-382 GEN
Solar/Wind Harmer
2.295
315732AD1-074 GEN1
Solar/Wind Harmer
0.344
315733AD1-074 GEN2
Solar/Wind Harmer
0.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.172
3130546PLYMOUTH
Solar/Wind Harmer
0.059
315816AE2-034 GEN
Solar/Wind Harmer
0.248
270494AE1-108_GEN
Solar/Wind Helper
4.456
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.076
3148013FISHERV
Solar/Wind Helper
0.072
NYPJM->LTFIMP_NY
CLTF
0.491
LAGNLTFEXP_LAGN->PJM
CLTF
2.721
LGEELTFEXP_LGEE->PJM
CLTF
0.351
WECLTFEXP_WEC->PJM
CLTF
0.183
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.095
TVALTFEXP_TVA->PJM
CLTF
1.342
CPLELTFEXP_CPLE->PJM
CLTF
4.932
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.244
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.478
MECLTFEXP_MEC->PJM
CLTF
1.093
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.37 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:911.29
MW Contribution:3.71
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
3151611KERR 4
50/50
0.288
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
NYPJM->LTFIMP_NY
CLTF
0.305
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
LGEELTFEXP_LGEE->PJM
CLTF
0.208
WECLTFEXP_WEC->PJM
CLTF
0.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.86 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:886.73
MW Contribution:3.61
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
WECLTFEXP_WEC->PJM
CLTF
0.127
TVALTFEXP_TVA->PJM
CLTF
1.009
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 249-69_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 249-69_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:122.66 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:857.38
MW Contribution:3.54
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.282
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.892
3147043LAWRENC
50/50
1.085
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.282
970413AG2-270 GEN
50/50
12.618
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.563
970909AG2-566 GEN
Solar/Wind Harmer
4.055
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.433
963181AG1-167 GEN
Solar/Wind Harmer
3.7
959311AF2-222 GEN
Solar/Wind Harmer
33.751
970257AG2-171 GEN
Solar/Wind Harmer
11.662
315785AD2-033 C
Solar/Wind Harmer
6.662
964241AG1-285 GEN
Solar/Wind Harmer
19.425
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.313
316486AD2-202 GEN
Solar/Wind Harmer
0.384
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.378
960061AF2-297 GEN
Solar/Wind Harmer
6.266
971683AH1-343 GEN
Solar/Wind Harmer
4.627
966621AG1-532 GEN
Solar/Wind Harmer
0.18
313506AB2-031 GEN
Solar/Wind Harmer
0.685
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.039
970917AG2-570 GEN
Solar/Wind Harmer
16.504
316327AA2-057 GEN
Solar/Wind Harmer
0.66
316365GEN2_N
Solar/Wind Harmer
0.435
3146263WOODLND
Solar/Wind Harmer
-0.006
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.282
3151621KERR 5
50/50
0.282
3151631KERR 6
50/50
0.282
3151641KERR 7
50/50
0.282
3151541CLOVER2
50/50
2.878
971845AH1-439 GEN
Solar/Wind Harmer
40.152
970285AG2-188 GEN
Solar/Wind Harmer
63.623
315657AE1-056 GEN
Solar/Wind Harmer
15.86
946301AF1-294 GEN
Solar/Wind Harmer
10.112
961791AG1-021 GEN
Solar/Wind Harmer
4.933
970683AG2-441 GEN
Solar/Wind Harmer
27.661
970681AG2-440 GEN
Solar/Wind Harmer
22.129
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.049
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.988
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.176
970865AG2-541 GEN
Solar/Wind Harmer
4.007
946281AF1-292 GEN
Solar/Wind Harmer
0.199
316087AB2-174 GEN
Solar/Wind Harmer
1.232
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.769
970163AG2-111 GEN
Solar/Wind Harmer
0.734
971967AH1-528 GEN
Solar/Wind Harmer
14.744
315607AA1-063A GEN
Solar/Wind Harmer
0.745
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.118
970581AG2-369 GEN
Solar/Wind Harmer
3.541
315652AC1-086 GEN
Solar/Wind Harmer
7.239
3146033SCOT NK
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
316319Z2-044 C
Solar/Wind Harmer
0.351
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.877
3152661PLYWOOD A
50/50
0.272
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.357
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.166
963191AG1-168 GEN
Solar/Wind Harmer
3.7
971741AH1-377 GEN
Solar/Wind Harmer
43.663
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.549
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.593
939181AE1-148 GEN
Solar/Wind Harmer
9.23
964791AG1-342 GEN
Solar/Wind Harmer
3.474
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.429
970933AG2-581 GEN
Solar/Wind Harmer
9.348
316181AB2-040 GEN
Solar/Wind Harmer
1.189
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.914
3145593CAROLNA
Solar/Wind Harmer
0.068
3145783HORNRTN
Solar/Wind Harmer
0.942
3145783HORNRTN
Solar/Wind Harmer
0.753
3145783HORNRTN
Solar/Wind Harmer
0.235
3145783HORNRTN
Solar/Wind Harmer
0.094
316222AC1-221 GEN
Solar/Wind Harmer
0.791
316426AA2-053 GEN
Solar/Wind Harmer
0.779
942751AE2-291 GEN
Solar/Wind Harmer
4.447
316274AC1-208 GEN
Solar/Wind Harmer
0.748
972187AH1-678 GEN
Adder
1.705
972185AH1-677 GEN
Adder
3.223
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.984
963171AG1-166 GEN
Solar/Wind Harmer
4.933
971563AH1-280 GEN
Solar/Wind Harmer
4.933
970685AG2-442 GEN
Solar/Wind Harmer
30.981
962491AG1-098 GEN
Solar/Wind Harmer
14.318
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.124
970401AG2-262 GEN
Solar/Wind Harmer
1.062
957481AF2-042 GEN
Solar/Wind Harmer
46.073
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.611
316129AC1-054 GEN
Solar/Wind Harmer
1.122
316003AC1-222 GEN
Solar/Wind Harmer
1.129
971795AH1-408 GEN
Solar/Wind Harmer
8.625
960081AF2-299 GEN
Solar/Wind Harmer
0.999
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
316212AC1-099_GEN
Solar/Wind Harmer
0.577
970919AG2-571 GEN
Solar/Wind Harmer
2.089
970087AG2-069 GEN
Solar/Wind Harmer
6.176
316023GEN1_S
Solar/Wind Harmer
0.435
3146263WOODLND
Solar/Wind Harmer
-0.006
316011AB1-132 GEN
Solar/Wind Harmer
1.346
962571AG1-106 GEN
Solar/Wind Harmer
0.925
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
316336AC2-165 C
Solar/Wind Helper
1.454
NYPJM->LTFIMP_NY
CLTF
0.319
LGEELTFEXP_LGEE->PJM
CLTF
0.233
LAGNLTFEXP_LAGN->PJM
CLTF
2.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.822
WECLTFEXP_WEC->PJM
CLTF
0.123
TVALTFEXP_TVA->PJM
CLTF
0.989
CPLELTFEXP_CPLE->PJM
CLTF
3.872
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.147
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.273
MECLTFEXP_MEC->PJM
CLTF
0.763
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.39 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:827.52
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
NYPJM->LTFIMP_NY
CLTF
0.309
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
LGEELTFEXP_LGEE->PJM
CLTF
0.214
WECLTFEXP_WEC->PJM
CLTF
0.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
TVALTFEXP_TVA->PJM
CLTF
0.953
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.79 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:644.61
MW Contribution:2.6
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
NYPJM->LTFIMP_NY
CLTF
0.308
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.83 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1864.16
MW Contribution:8.61
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
316369SG1_INVT
Solar/Wind Helper
0.602
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
315697AD1-025 GEN
Solar/Wind Helper
1.43
NYPJM->LTFIMP_NY
CLTF
0.817
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.18 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1428.84
MW Contribution:5.11
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
NYPJM->LTFIMP_NY
CLTF
0.691
LGEELTFEXP_LGEE->PJM
CLTF
0.659
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
WECLTFEXP_WEC->PJM
CLTF
0.343
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.21 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1192.96
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
WECLTFEXP_WEC->PJM
CLTF
0.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.16 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1458.72
MW Contribution:6.48
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.03
315244AE2-183_ST
50/50
3.258
316315AB2-025 C
Solar/Wind Harmer
0.658
315814AE2-033 C
Solar/Wind Harmer
22.362
946281AF1-292 GEN
Solar/Wind Harmer
0.338
316087AB2-174 GEN
Solar/Wind Harmer
1.997
315652AC1-086 GEN
Solar/Wind Harmer
15.208
941031AE2-094 GEN
Solar/Wind Harmer
24.889
944011AF1-069 GEN
Solar/Wind Harmer
7.799
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
970673AG2-436 GEN
Solar/Wind Harmer
27.253
970673AG2-436 GEN
Solar/Wind Harmer
13.799
971967AH1-528 GEN
Solar/Wind Harmer
23.736
3137643SOCKMAN
Solar/Wind Harmer
-0.05
970085AG2-068 GEN
Solar/Wind Harmer
7.532
970581AG2-369 GEN
Solar/Wind Harmer
6.478
315607AA1-063A GEN
Solar/Wind Harmer
1.086
3146043SEABORD
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.273
316319Z2-044 C
Solar/Wind Harmer
0.57
3146033SCOT NK
Solar/Wind Harmer
-0.041
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
316420AA1-050 GEN
Solar/Wind Harmer
1.112
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
957861AF2-080 GEN
Solar/Wind Harmer
4.179
3145513AHOSKIE
Solar/Wind Harmer
0.083
961941AG1-037 GEN
Solar/Wind Harmer
0.072
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316318V4-068
Solar/Wind Harmer
0.232
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.815
316239AB2-077_GEN
Solar/Wind Harmer
0.277
316238AB2-078_GEN
Solar/Wind Harmer
0.277
316005AA1-067
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
-0.036
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.204
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.755
316118AC1-105 GEN
Solar/Wind Harmer
0.588
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
315732AD1-074 GEN1
Solar/Wind Harmer
1.641
315733AD1-074 GEN2
Solar/Wind Harmer
1.641
315735AD1-075 GEN1
Solar/Wind Harmer
0.821
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
1.576
3144303KENBRDG
Solar/Wind Harmer
-0.006
315816AE2-034 GEN
Solar/Wind Harmer
0.613
3143316POE
Solar/Wind Harmer
-0.029
970683AG2-441 GEN
Solar/Wind Harmer
5.791
970681AG2-440 GEN
Solar/Wind Harmer
4.633
970865AG2-541 GEN
Solar/Wind Harmer
2.878
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.768
961791AG1-021 GEN
Solar/Wind Harmer
0.863
270455AD2-022 GEN
Solar/Wind Harmer
1.198
270457AD2-023 GEN
Solar/Wind Harmer
0.607
315611Z1-036_GEN2
Solar/Wind Harmer
1.648
315657AE1-056 GEN
Solar/Wind Harmer
2.454
316233AE1-074 FULL
Solar/Wind Helper
0.26
316132AB2-190 GEN1
Solar/Wind Helper
0.962
316312AB1-027
Solar/Wind Helper
0.257
316369SG1_INVT
Solar/Wind Helper
0.561
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
3147043LAWRENC
50/50
1.136
315243AE2-183_GT3
50/50
1.885
316023GEN1_S
Solar/Wind Harmer
1.163
960081AF2-299 GEN
Solar/Wind Harmer
1.698
971795AH1-408 GEN
Solar/Wind Harmer
10.393
316011AB1-132 GEN
Solar/Wind Harmer
2.828
962571AG1-106 GEN
Solar/Wind Harmer
1.943
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
940641AE2-051 GEN
Solar/Wind Harmer
11.726
970919AG2-571 GEN
Solar/Wind Harmer
3.832
970087AG2-069 GEN
Solar/Wind Harmer
11.298
3145783HORNRTN
Solar/Wind Harmer
-0.012
315722AD1-056 GEN
Solar/Wind Harmer
1.205
316190AA2-174 GEN
Solar/Wind Harmer
0.14
939411AE1-173 GEN
Solar/Wind Harmer
53.98
957481AF2-042 GEN
Solar/Wind Harmer
33.308
316212AC1-099_GEN
Solar/Wind Harmer
0.912
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3146233WITAKRS
Solar/Wind Harmer
-0.041
971065AG2-659 GEN
Solar/Wind Harmer
5.148
316359AB2-059 GEN
Solar/Wind Harmer
1.375
316049AB1-081 GEN
Solar/Wind Harmer
1.101
3142053HEARTS
Solar/Wind Harmer
0.12
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.01
961671AG1-007 GEN
Solar/Wind Harmer
0.125
3146083TARBORO
Solar/Wind Harmer
-0.01
3145493TOT1
Solar/Wind Harmer
0.293
315693AD1-088 GEN
Solar/Wind Harmer
4.917
962491AG1-098 GEN
Solar/Wind Harmer
6.469
3145683EARLEYS
Solar/Wind Harmer
-0.01
316494AC1-189 GEN
Solar/Wind Harmer
1.028
315687AD1-152 GEN
Solar/Wind Harmer
1.146
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
0.276
316237AB2-079_GEN
Solar/Wind Harmer
0.277
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146293MARTNCO
Solar/Wind Harmer
0.056
970401AG2-262 GEN
Solar/Wind Harmer
0.569
316174AB2-169 GEN
Solar/Wind Harmer
1.336
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.146
3145963POPLR C
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.773
3145663CRESWEL
Solar/Wind Harmer
-0.021
971163AH1-040 GEN
Solar/Wind Harmer
7.107
970685AG2-442 GEN
Solar/Wind Harmer
6.486
3130156CHOWAN
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.863
971563AH1-280 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.196
315800Z1-036_GEN1
Solar/Wind Harmer
1.648
316294AC1-161 GEN
Solar/Wind Harmer
2.081
3142543TWELFTH
Solar/Wind Helper
0.025
3143526WINTERP
Solar/Wind Helper
0.886
316458AB2-190 GEN2
Solar/Wind Helper
0.962
3142433PROV 92
Solar/Wind Helper
0.66
3143226MDLTHAN
Solar/Wind Helper
0.165
3142416OLDCHRC
Solar/Wind Helper
0.352
3142416OLDCHRC
Solar/Wind Helper
0.135
970533AG2-339 GEN
50/50
10.502
970531AG2-338 GEN
50/50
4.201
3151361ROSEMG1
50/50
0.418
3151371ROSEMS1
50/50
0.259
3151381ROSEMG2
50/50
0.196
315242AE2-183_GT2
50/50
1.885
315241AE2-183_GT1
50/50
1.873
972185AH1-677 GEN
50/50
6.794
3144356SAPONY
Solar/Wind Harmer
0.851
316181AB2-040 GEN
Solar/Wind Harmer
1.887
3145796HORNRTN
Solar/Wind Harmer
-0.039
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
972187AH1-678 GEN
Adder
3.198
970933AG2-581 GEN
Solar/Wind Harmer
11.305
3145593CAROLNA
Solar/Wind Harmer
-0.012
3145593CAROLNA
Solar/Wind Harmer
-0.012
966811AG1-552 GEN
Solar/Wind Harmer
1.324
3145593CAROLNA
Solar/Wind Harmer
0.098
3145783HORNRTN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
1.102
3145783HORNRTN
Solar/Wind Harmer
0.344
3145783HORNRTN
Solar/Wind Harmer
0.138
316426AA2-053 GEN
Solar/Wind Harmer
1.15
316274AC1-208 GEN
Solar/Wind Harmer
1.161
970099AG2-077 GEN
Solar/Wind Harmer
13.323
961601AG1-000A GEN
Solar/Wind Harmer
4.038
316263AC1-034 GEN
Solar/Wind Harmer
4.782
3145493TOT1
Solar/Wind Harmer
0.153
3145453TOT5
Solar/Wind Harmer
0.092
3145603CNETO
Solar/Wind Harmer
0.061
939181AE1-148 GEN
Solar/Wind Harmer
5.399
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.26
3145893MURPHYS
Solar/Wind Harmer
-0.017
313527AB2-043 GEN
Solar/Wind Harmer
1.49
3145933PARMELE
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.009
962561AG1-105 GEN
Solar/Wind Harmer
4.944
964791AG1-342 GEN
Solar/Wind Harmer
1.863
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316065AD1-022 GEN
Solar/Wind Harmer
4.205
970323AG2-213 GEN
Solar/Wind Harmer
3.978
971775AH1-396 GEN
Solar/Wind Harmer
0.566
316034AC1-036 C
Solar/Wind Harmer
0.147
316222AC1-221 GEN
Solar/Wind Harmer
0.793
971741AH1-377 GEN
Solar/Wind Harmer
8.632
3146376EDENTON
Solar/Wind Harmer
0.208
3146376EDENTON
Solar/Wind Harmer
0.208
315742AE1-103 GEN
Solar/Wind Harmer
0.722
958211AF2-115 GEN
Solar/Wind Harmer
1.078
963191AG1-168 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
3144293JTRSVLE
Adder
0.165
970301AG2-198 GEN
Solar/Wind Harmer
3.354
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
316240AF1-291 C
Solar/Wind Helper
0.429
3143526WINTERP
Solar/Wind Helper
0.886
966871AG1-558 GEN
Solar/Wind Helper
0.219
3142946ENON
Solar/Wind Helper
0.016
316468AD1-105 GEN
Solar/Wind Helper
0.693
316075AC2-137 C
Solar/Wind Helper
0.195
316033AB2-134 GEN
Solar/Wind Helper
0.401
315697AD1-025 GEN
Solar/Wind Helper
1.333
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
316365GEN2_N
Solar/Wind Harmer
1.163
966621AG1-532 GEN
Solar/Wind Harmer
0.306
313506AB2-031 GEN
Solar/Wind Harmer
1.087
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970917AG2-570 GEN
Solar/Wind Harmer
30.27
315724AD1-057 GEN
Solar/Wind Harmer
0.663
316210AC1-098 GEN
Solar/Wind Harmer
1.641
316327AA2-057 GEN
Solar/Wind Harmer
1.056
3146233WITAKRS
Solar/Wind Harmer
0.216
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
4.089
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
316478AD1-087 GEN
Solar/Wind Harmer
0.876
316486AD2-202 GEN
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.467
3145823KELFORD
Solar/Wind Harmer
-0.01
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.192
3146173TUNIS
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.37
961681AG1-008 GEN
Solar/Wind Harmer
7.37
3145893MURPHYS
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.247
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
316131AB2-060 GEN
Solar/Wind Harmer
0.981
3156081AA2-088 GEN
Solar/Wind Harmer
2.919
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.122
964241AG1-285 GEN
Solar/Wind Harmer
6.83
3146206CASHIE
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
316248AF1-058 C
Solar/Wind Harmer
0.253
960061AF2-297 GEN
Solar/Wind Harmer
4.197
315785AD2-033 C
Solar/Wind Harmer
1.852
315737AD1-076 GEN
Solar/Wind Harmer
1.542
971157AH1-035 GEN
Solar/Wind Harmer
1.003
970257AG2-171 GEN
Solar/Wind Harmer
2.983
316283AC2-100 C
Solar/Wind Harmer
0.735
959311AF2-222 GEN
Solar/Wind Harmer
8.141
315614AA2-178 GEN
Solar/Wind Harmer
0.818
971683AH1-343 GEN
Solar/Wind Harmer
3.238
3146376EDENTON
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
970909AG2-566 GEN
Solar/Wind Harmer
0.637
3147133PAMPLIN
Solar/Wind Harmer
-0.02
971193AH1-056 GEN
Solar/Wind Harmer
4.09
315773AC2-141 GEN
Solar/Wind Harmer
2.692
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3145273HOLLAND
Solar/Wind Harmer
-0.005
315839AE2-212 C
Solar/Wind Helper
1.003
316473AC1-191 GEN
Solar/Wind Helper
0.992
3142946ENON
Solar/Wind Helper
0.053
NYPJM->LTFIMP_NY
CLTF
0.636
LAGNLTFEXP_LAGN->PJM
CLTF
3.613
LGEELTFEXP_LGEE->PJM
CLTF
0.626
WECLTFEXP_WEC->PJM
CLTF
0.327
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.467
TVALTFEXP_TVA->PJM
CLTF
1.799
CPLELTFEXP_CPLE->PJM
CLTF
5.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.154
MECLTFEXP_MEC->PJM
CLTF
1.751
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.16 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1458.72
MW Contribution:6.48
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.03
315244AE2-183_ST
50/50
3.258
316315AB2-025 C
Solar/Wind Harmer
0.658
315814AE2-033 C
Solar/Wind Harmer
22.362
946281AF1-292 GEN
Solar/Wind Harmer
0.338
316087AB2-174 GEN
Solar/Wind Harmer
1.997
315652AC1-086 GEN
Solar/Wind Harmer
15.208
941031AE2-094 GEN
Solar/Wind Harmer
24.889
944011AF1-069 GEN
Solar/Wind Harmer
7.799
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
970673AG2-436 GEN
Solar/Wind Harmer
27.253
970673AG2-436 GEN
Solar/Wind Harmer
13.799
971967AH1-528 GEN
Solar/Wind Harmer
23.736
3137643SOCKMAN
Solar/Wind Harmer
-0.05
970085AG2-068 GEN
Solar/Wind Harmer
7.532
970581AG2-369 GEN
Solar/Wind Harmer
6.478
315607AA1-063A GEN
Solar/Wind Harmer
1.086
3146043SEABORD
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.273
316319Z2-044 C
Solar/Wind Harmer
0.57
3146033SCOT NK
Solar/Wind Harmer
-0.041
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
316420AA1-050 GEN
Solar/Wind Harmer
1.112
3145683EARLEYS
Solar/Wind Harmer
-0.019
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
3147043LAWRENC
50/50
1.136
315243AE2-183_GT3
50/50
1.885
316023GEN1_S
Solar/Wind Harmer
1.163
960081AF2-299 GEN
Solar/Wind Harmer
1.698
971795AH1-408 GEN
Solar/Wind Harmer
10.393
316011AB1-132 GEN
Solar/Wind Harmer
2.828
962571AG1-106 GEN
Solar/Wind Harmer
1.943
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
940641AE2-051 GEN
Solar/Wind Harmer
11.726
970919AG2-571 GEN
Solar/Wind Harmer
3.832
970087AG2-069 GEN
Solar/Wind Harmer
11.298
3145783HORNRTN
Solar/Wind Harmer
-0.012
315722AD1-056 GEN
Solar/Wind Harmer
1.205
316190AA2-174 GEN
Solar/Wind Harmer
0.14
939411AE1-173 GEN
Solar/Wind Harmer
53.98
957481AF2-042 GEN
Solar/Wind Harmer
33.308
316212AC1-099_GEN
Solar/Wind Harmer
0.912
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3146233WITAKRS
Solar/Wind Harmer
-0.041
971065AG2-659 GEN
Solar/Wind Harmer
5.148
316359AB2-059 GEN
Solar/Wind Harmer
1.375
316049AB1-081 GEN
Solar/Wind Harmer
1.101
3142053HEARTS
Solar/Wind Harmer
0.12
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.01
961671AG1-007 GEN
Solar/Wind Harmer
0.125
3146083TARBORO
Solar/Wind Harmer
-0.01
3145493TOT1
Solar/Wind Harmer
0.293
315693AD1-088 GEN
Solar/Wind Harmer
4.917
962491AG1-098 GEN
Solar/Wind Harmer
6.469
3145683EARLEYS
Solar/Wind Harmer
-0.01
316494AC1-189 GEN
Solar/Wind Harmer
1.028
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
957861AF2-080 GEN
Solar/Wind Harmer
4.179
3145513AHOSKIE
Solar/Wind Harmer
0.083
961941AG1-037 GEN
Solar/Wind Harmer
0.072
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316318V4-068
Solar/Wind Harmer
0.232
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.815
316239AB2-077_GEN
Solar/Wind Harmer
0.277
316238AB2-078_GEN
Solar/Wind Harmer
0.277
316005AA1-067
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
-0.036
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.204
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.755
316118AC1-105 GEN
Solar/Wind Harmer
0.588
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
315732AD1-074 GEN1
Solar/Wind Harmer
1.641
315733AD1-074 GEN2
Solar/Wind Harmer
1.641
315735AD1-075 GEN1
Solar/Wind Harmer
0.821
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
1.576
3144303KENBRDG
Solar/Wind Harmer
-0.006
315816AE2-034 GEN
Solar/Wind Harmer
0.613
3143316POE
Solar/Wind Harmer
-0.029
970683AG2-441 GEN
Solar/Wind Harmer
5.791
970681AG2-440 GEN
Solar/Wind Harmer
4.633
970865AG2-541 GEN
Solar/Wind Harmer
2.878
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.768
961791AG1-021 GEN
Solar/Wind Harmer
0.863
270455AD2-022 GEN
Solar/Wind Harmer
1.198
270457AD2-023 GEN
Solar/Wind Harmer
0.607
315611Z1-036_GEN2
Solar/Wind Harmer
1.648
315657AE1-056 GEN
Solar/Wind Harmer
2.454
316233AE1-074 FULL
Solar/Wind Helper
0.26
316132AB2-190 GEN1
Solar/Wind Helper
0.962
316312AB1-027
Solar/Wind Helper
0.257
316369SG1_INVT
Solar/Wind Helper
0.561
970533AG2-339 GEN
50/50
10.502
970531AG2-338 GEN
50/50
4.201
3151361ROSEMG1
50/50
0.418
3151371ROSEMS1
50/50
0.259
3151381ROSEMG2
50/50
0.196
315242AE2-183_GT2
50/50
1.885
315241AE2-183_GT1
50/50
1.873
972185AH1-677 GEN
50/50
6.794
3144356SAPONY
Solar/Wind Harmer
0.851
316181AB2-040 GEN
Solar/Wind Harmer
1.887
3145796HORNRTN
Solar/Wind Harmer
-0.039
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
972187AH1-678 GEN
Adder
3.198
970933AG2-581 GEN
Solar/Wind Harmer
11.305
3145593CAROLNA
Solar/Wind Harmer
-0.012
3145593CAROLNA
Solar/Wind Harmer
-0.012
966811AG1-552 GEN
Solar/Wind Harmer
1.324
3145593CAROLNA
Solar/Wind Harmer
0.098
3145783HORNRTN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
1.102
3145783HORNRTN
Solar/Wind Harmer
0.344
3145783HORNRTN
Solar/Wind Harmer
0.138
316426AA2-053 GEN
Solar/Wind Harmer
1.15
316274AC1-208 GEN
Solar/Wind Harmer
1.161
970099AG2-077 GEN
Solar/Wind Harmer
13.323
961601AG1-000A GEN
Solar/Wind Harmer
4.038
316263AC1-034 GEN
Solar/Wind Harmer
4.782
3145493TOT1
Solar/Wind Harmer
0.153
3145453TOT5
Solar/Wind Harmer
0.092
3145603CNETO
Solar/Wind Harmer
0.061
939181AE1-148 GEN
Solar/Wind Harmer
5.399
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.26
3145893MURPHYS
Solar/Wind Harmer
-0.017
313527AB2-043 GEN
Solar/Wind Harmer
1.49
3145933PARMELE
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.009
962561AG1-105 GEN
Solar/Wind Harmer
4.944
964791AG1-342 GEN
Solar/Wind Harmer
1.863
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316065AD1-022 GEN
Solar/Wind Harmer
4.205
970323AG2-213 GEN
Solar/Wind Harmer
3.978
971775AH1-396 GEN
Solar/Wind Harmer
0.566
316034AC1-036 C
Solar/Wind Harmer
0.147
316222AC1-221 GEN
Solar/Wind Harmer
0.793
971741AH1-377 GEN
Solar/Wind Harmer
8.632
3146376EDENTON
Solar/Wind Harmer
0.208
3146376EDENTON
Solar/Wind Harmer
0.208
315742AE1-103 GEN
Solar/Wind Harmer
0.722
958211AF2-115 GEN
Solar/Wind Harmer
1.078
963191AG1-168 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
3144293JTRSVLE
Adder
0.165
970301AG2-198 GEN
Solar/Wind Harmer
3.354
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
316240AF1-291 C
Solar/Wind Helper
0.429
3143526WINTERP
Solar/Wind Helper
0.886
966871AG1-558 GEN
Solar/Wind Helper
0.219
3142946ENON
Solar/Wind Helper
0.016
316468AD1-105 GEN
Solar/Wind Helper
0.693
316075AC2-137 C
Solar/Wind Helper
0.195
316033AB2-134 GEN
Solar/Wind Helper
0.401
315697AD1-025 GEN
Solar/Wind Helper
1.333
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
316365GEN2_N
Solar/Wind Harmer
1.163
966621AG1-532 GEN
Solar/Wind Harmer
0.306
313506AB2-031 GEN
Solar/Wind Harmer
1.087
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970917AG2-570 GEN
Solar/Wind Harmer
30.27
315724AD1-057 GEN
Solar/Wind Harmer
0.663
316210AC1-098 GEN
Solar/Wind Harmer
1.641
316327AA2-057 GEN
Solar/Wind Harmer
1.056
3146233WITAKRS
Solar/Wind Harmer
0.216
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
4.089
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
316478AD1-087 GEN
Solar/Wind Harmer
0.876
316486AD2-202 GEN
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.467
3145823KELFORD
Solar/Wind Harmer
-0.01
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.192
3146173TUNIS
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.37
961681AG1-008 GEN
Solar/Wind Harmer
7.37
3145893MURPHYS
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.247
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
316131AB2-060 GEN
Solar/Wind Harmer
0.981
3156081AA2-088 GEN
Solar/Wind Harmer
2.919
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.122
964241AG1-285 GEN
Solar/Wind Harmer
6.83
3146206CASHIE
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
316248AF1-058 C
Solar/Wind Harmer
0.253
960061AF2-297 GEN
Solar/Wind Harmer
4.197
315785AD2-033 C
Solar/Wind Harmer
1.852
315737AD1-076 GEN
Solar/Wind Harmer
1.542
971157AH1-035 GEN
Solar/Wind Harmer
1.003
970257AG2-171 GEN
Solar/Wind Harmer
2.983
316283AC2-100 C
Solar/Wind Harmer
0.735
959311AF2-222 GEN
Solar/Wind Harmer
8.141
315614AA2-178 GEN
Solar/Wind Harmer
0.818
971683AH1-343 GEN
Solar/Wind Harmer
3.238
3146376EDENTON
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
970909AG2-566 GEN
Solar/Wind Harmer
0.637
3147133PAMPLIN
Solar/Wind Harmer
-0.02
971193AH1-056 GEN
Solar/Wind Harmer
4.09
315773AC2-141 GEN
Solar/Wind Harmer
2.692
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3145273HOLLAND
Solar/Wind Harmer
-0.005
315839AE2-212 C
Solar/Wind Helper
1.003
316473AC1-191 GEN
Solar/Wind Helper
0.992
3142946ENON
Solar/Wind Helper
0.053
315687AD1-152 GEN
Solar/Wind Harmer
1.146
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
0.276
316237AB2-079_GEN
Solar/Wind Harmer
0.277
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146293MARTNCO
Solar/Wind Harmer
0.056
970401AG2-262 GEN
Solar/Wind Harmer
0.569
316174AB2-169 GEN
Solar/Wind Harmer
1.336
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.146
3145963POPLR C
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.773
3145663CRESWEL
Solar/Wind Harmer
-0.021
971163AH1-040 GEN
Solar/Wind Harmer
7.107
970685AG2-442 GEN
Solar/Wind Harmer
6.486
3130156CHOWAN
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.863
971563AH1-280 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.196
315800Z1-036_GEN1
Solar/Wind Harmer
1.648
316294AC1-161 GEN
Solar/Wind Harmer
2.081
3142543TWELFTH
Solar/Wind Helper
0.025
3143526WINTERP
Solar/Wind Helper
0.886
316458AB2-190 GEN2
Solar/Wind Helper
0.962
3142433PROV 92
Solar/Wind Helper
0.66
3143226MDLTHAN
Solar/Wind Helper
0.165
3142416OLDCHRC
Solar/Wind Helper
0.352
3142416OLDCHRC
Solar/Wind Helper
0.135
NYPJM->LTFIMP_NY
CLTF
0.636
LGEELTFEXP_LGEE->PJM
CLTF
0.626
LAGNLTFEXP_LAGN->PJM
CLTF
3.613
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.467
WECLTFEXP_WEC->PJM
CLTF
0.327
TVALTFEXP_TVA->PJM
CLTF
1.799
CPLELTFEXP_CPLE->PJM
CLTF
5.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.154
MECLTFEXP_MEC->PJM
CLTF
1.751
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.6 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1343.65
MW Contribution:5.72
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.663
3151281ROARAP4
50/50
0.139
3151281ROARAP4
50/50
0.13
316315AB2-025 C
Solar/Wind Harmer
0.795
315814AE2-033 C
Solar/Wind Harmer
26.999
946281AF1-292 GEN
Solar/Wind Harmer
0.386
316087AB2-174 GEN
Solar/Wind Harmer
2.258
3151361ROSEMG1
50/50
0.469
3151371ROSEMS1
50/50
0.29
3151381ROSEMG2
50/50
0.219
3144356SAPONY
Solar/Wind Harmer
1.028
316181AB2-040 GEN
Solar/Wind Harmer
2.122
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
0.107
3145783HORNRTN
Solar/Wind Harmer
1.509
3145783HORNRTN
Solar/Wind Harmer
1.207
3145783HORNRTN
Solar/Wind Harmer
0.377
3145783HORNRTN
Solar/Wind Harmer
0.151
316426AA2-053 GEN
Solar/Wind Harmer
1.258
316274AC1-208 GEN
Solar/Wind Harmer
1.251
972185AH1-677 GEN
Adder
5.61
972187AH1-678 GEN
Adder
2.808
961601AG1-000A GEN
Solar/Wind Harmer
4.277
316263AC1-034 GEN
Solar/Wind Harmer
5.056
970933AG2-581 GEN
Solar/Wind Harmer
9.991
3145493TOT1
Solar/Wind Harmer
0.161
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
0.28
3145893MURPHYS
Solar/Wind Harmer
-0.018
970099AG2-077 GEN
Solar/Wind Harmer
12.007
939181AE1-148 GEN
Solar/Wind Harmer
5.392
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.009
313527AB2-043 GEN
Solar/Wind Harmer
1.499
316065AD1-022 GEN
Solar/Wind Harmer
4.409
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.813
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.001
971775AH1-396 GEN
Solar/Wind Harmer
0.57
316034AC1-036 C
Solar/Wind Harmer
0.148
316222AC1-221 GEN
Solar/Wind Harmer
0.751
315742AE1-103 GEN
Solar/Wind Harmer
0.77
3146376EDENTON
Solar/Wind Harmer
0.21
3146376EDENTON
Solar/Wind Harmer
0.21
971741AH1-377 GEN
Solar/Wind Harmer
8.082
958211AF2-115 GEN
Solar/Wind Harmer
1.085
963191AG1-168 GEN
Solar/Wind Harmer
0.651
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
970301AG2-198 GEN
Solar/Wind Harmer
3.177
316240AF1-291 C
Solar/Wind Helper
0.351
966871AG1-558 GEN
Solar/Wind Helper
0.184
3142946ENON
Solar/Wind Helper
0.013
3143526WINTERP
Solar/Wind Helper
0.647
316468AD1-105 GEN
Solar/Wind Helper
0.589
3151391GASTONA
50/50
0.367
3151411GASTONB
50/50
0.367
3151261ROARAP2
50/50
0.14
316365GEN2_N
Solar/Wind Harmer
1.356
966621AG1-532 GEN
Solar/Wind Harmer
0.35
313506AB2-031 GEN
Solar/Wind Harmer
1.223
3147043LAWRENC
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
315724AD1-057 GEN
Solar/Wind Harmer
0.723
315652AC1-086 GEN
Solar/Wind Harmer
17.155
3145796HORNRTN
Solar/Wind Harmer
-0.046
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.056
3143316POE
Solar/Wind Harmer
-0.048
315607AA1-063A GEN
Solar/Wind Harmer
1.187
941031AE2-094 GEN
Solar/Wind Harmer
21.703
944011AF1-069 GEN
Solar/Wind Harmer
6.8
3146043SEABORD
Solar/Wind Harmer
-0.012
970673AG2-436 GEN
Solar/Wind Harmer
23.837
970673AG2-436 GEN
Solar/Wind Harmer
12.069
971967AH1-528 GEN
Solar/Wind Harmer
20.84
970831AG2-522 GEN
Solar/Wind Harmer
5.503
3146033SCOT NK
Solar/Wind Harmer
-0.044
316319Z2-044 C
Solar/Wind Harmer
0.606
970085AG2-068 GEN
Solar/Wind Harmer
6.656
970581AG2-369 GEN
Solar/Wind Harmer
5.724
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
316420AA1-050 GEN
Solar/Wind Harmer
1.171
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316318V4-068
Solar/Wind Harmer
0.251
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
957861AF2-080 GEN
Solar/Wind Harmer
4.39
965291AG1-394 GEN
Solar/Wind Harmer
0.882
316005AA1-067
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
-0.038
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.259
316239AB2-077_GEN
Solar/Wind Harmer
0.278
316238AB2-078_GEN
Solar/Wind Harmer
0.278
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.951
315732AD1-074 GEN1
Solar/Wind Harmer
1.708
315733AD1-074 GEN2
Solar/Wind Harmer
1.708
315735AD1-075 GEN1
Solar/Wind Harmer
0.854
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.565
971443AH1-215 GEN
Solar/Wind Harmer
1.585
3144303KENBRDG
Solar/Wind Harmer
-0.006
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
315816AE2-034 GEN
Solar/Wind Harmer
0.631
970683AG2-441 GEN
Solar/Wind Harmer
5.825
970681AG2-440 GEN
Solar/Wind Harmer
4.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.779
961791AG1-021 GEN
Solar/Wind Harmer
0.868
970865AG2-541 GEN
Solar/Wind Harmer
2.735
315611Z1-036_GEN2
Solar/Wind Harmer
1.655
315657AE1-056 GEN
Solar/Wind Harmer
2.469
270455AD2-022 GEN
Solar/Wind Harmer
1.142
270457AD2-023 GEN
Solar/Wind Harmer
0.579
316132AB2-190 GEN1
Solar/Wind Helper
0.788
316233AE1-074 FULL
Solar/Wind Helper
0.19
316312AB1-027
Solar/Wind Helper
0.214
316210AC1-098 GEN
Solar/Wind Harmer
1.764
316327AA2-057 GEN
Solar/Wind Harmer
1.127
3146263WOODLND
Solar/Wind Harmer
-0.011
3146233WITAKRS
Solar/Wind Harmer
0.229
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
4.332
3145543BTLEBRO
Solar/Wind Harmer
-0.011
3145543BTLEBRO
Solar/Wind Harmer
-0.011
970917AG2-570 GEN
Solar/Wind Harmer
26.73
316317KELFORD C
Solar/Wind Harmer
0.501
3145823KELFORD
Solar/Wind Harmer
-0.011
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.28
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.946
961681AG1-008 GEN
Solar/Wind Harmer
7.946
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3156021HOLLOMANSOL
Solar/Wind Harmer
1.329
3156081AA2-088 GEN
Solar/Wind Harmer
3.157
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.173
316478AD1-087 GEN
Solar/Wind Harmer
0.797
316486AD2-202 GEN
Solar/Wind Harmer
0.233
316131AB2-060 GEN
Solar/Wind Harmer
0.986
3146206CASHIE
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
6.87
315737AD1-076 GEN
Solar/Wind Harmer
1.605
971157AH1-035 GEN
Solar/Wind Harmer
1.043
315785AD2-033 C
Solar/Wind Harmer
1.862
970257AG2-171 GEN
Solar/Wind Harmer
3.001
316248AF1-058 C
Solar/Wind Harmer
0.24
960061AF2-297 GEN
Solar/Wind Harmer
3.979
959311AF2-222 GEN
Solar/Wind Harmer
8.189
315614AA2-178 GEN
Solar/Wind Harmer
0.842
316283AC2-100 C
Solar/Wind Harmer
0.696
971683AH1-343 GEN
Solar/Wind Harmer
3.075
3146376EDENTON
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.651
3144293JTRSVLE
Adder
0.197
3145273HOLLAND
Solar/Wind Harmer
-0.005
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.115
3146626S HERTFORD
Solar/Wind Harmer
-0.006
970909AG2-566 GEN
Solar/Wind Harmer
0.603
315839AE2-212 C
Solar/Wind Helper
0.91
316473AC1-191 GEN
Solar/Wind Helper
0.834
3142946ENON
Solar/Wind Helper
0.044
3151391GASTONA
50/50
0.367
3151411GASTONB
50/50
0.367
3147043LAWRENC
50/50
1.265
3151261ROARAP2
50/50
0.143
316023GEN1_S
Solar/Wind Harmer
1.356
960081AF2-299 GEN
Solar/Wind Harmer
1.94
971795AH1-408 GEN
Solar/Wind Harmer
11.683
316011AB1-132 GEN
Solar/Wind Harmer
3.19
962571AG1-106 GEN
Solar/Wind Harmer
2.192
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
3145783HORNRTN
Solar/Wind Harmer
-0.013
315722AD1-056 GEN
Solar/Wind Harmer
1.314
316190AA2-174 GEN
Solar/Wind Harmer
0.153
316212AC1-099_GEN
Solar/Wind Harmer
0.98
3146263WOODLND
Solar/Wind Harmer
-0.011
3146233WITAKRS
Solar/Wind Harmer
-0.043
940641AE2-051 GEN
Solar/Wind Harmer
10.201
316129AC1-054 GEN
Solar/Wind Harmer
0.947
316359AB2-059 GEN
Solar/Wind Harmer
1.454
316049AB1-081 GEN
Solar/Wind Harmer
1.164
3142053HEARTS
Solar/Wind Harmer
0.127
3145543BTLEBRO
Solar/Wind Harmer
-0.011
3145543BTLEBRO
Solar/Wind Harmer
-0.009
970919AG2-571 GEN
Solar/Wind Harmer
3.384
970087AG2-069 GEN
Solar/Wind Harmer
9.984
3145823KELFORD
Solar/Wind Harmer
-0.011
971065AG2-659 GEN
Solar/Wind Harmer
5.306
961671AG1-007 GEN
Solar/Wind Harmer
0.132
3146083TARBORO
Solar/Wind Harmer
-0.01
3145493TOT1
Solar/Wind Harmer
0.309
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.298
316494AC1-189 GEN
Solar/Wind Harmer
1.08
957481AF2-042 GEN
Solar/Wind Harmer
30.018
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
939411AE1-173 GEN
Solar/Wind Harmer
47.496
3146293MARTNCO
Solar/Wind Harmer
0.058
316237AB2-079_GEN
Solar/Wind Harmer
0.278
316174AB2-169 GEN
Solar/Wind Harmer
1.394
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.258
315693AD1-088 GEN
Solar/Wind Harmer
4.482
3145963POPLR C
Solar/Wind Harmer
-0.009
962491AG1-098 GEN
Solar/Wind Harmer
5.904
315687AD1-152 GEN
Solar/Wind Harmer
1.054
970401AG2-262 GEN
Solar/Wind Harmer
0.554
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.314
316003AC1-222 GEN
Solar/Wind Harmer
0.734
970685AG2-442 GEN
Solar/Wind Harmer
6.524
3130156CHOWAN
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.868
971563AH1-280 GEN
Solar/Wind Harmer
0.868
3144293JTRSVLE
Adder
0.197
315800Z1-036_GEN1
Solar/Wind Harmer
1.655
3142543TWELFTH
Solar/Wind Helper
0.021
3142433PROV 92
Solar/Wind Helper
0.564
316458AB2-190 GEN2
Solar/Wind Helper
0.788
3143526WINTERP
Solar/Wind Helper
0.647
3143226MDLTHAN
Solar/Wind Helper
0.112
3142416OLDCHRC
Solar/Wind Helper
0.292
3142416OLDCHRC
Solar/Wind Helper
0.112
NYPJM->LTFIMP_NY
CLTF
0.631
LGEELTFEXP_LGEE->PJM
CLTF
0.598
LAGNLTFEXP_LAGN->PJM
CLTF
3.447
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.956
WECLTFEXP_WEC->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
1.717
CPLELTFEXP_CPLE->PJM
CLTF
5.179
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.13
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.874
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.05

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P4-5: L552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: L552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.53 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1282.59
MW Contribution:5.32
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.403
316315AB2-025 C
Solar/Wind Harmer
0.739
315814AE2-033 C
Solar/Wind Harmer
25.066
946281AF1-292 GEN
Solar/Wind Harmer
0.352
316087AB2-174 GEN
Solar/Wind Harmer
2.042
315652AC1-086 GEN
Solar/Wind Harmer
15.395
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.05
941031AE2-094 GEN
Solar/Wind Harmer
20.229
944011AF1-069 GEN
Solar/Wind Harmer
6.339
970673AG2-436 GEN
Solar/Wind Harmer
22.201
970673AG2-436 GEN
Solar/Wind Harmer
11.241
971967AH1-528 GEN
Solar/Wind Harmer
19.398
315607AA1-063A GEN
Solar/Wind Harmer
1.035
3146043SEABORD
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
4.947
970085AG2-068 GEN
Solar/Wind Harmer
6.181
970581AG2-369 GEN
Solar/Wind Harmer
5.316
316319Z2-044 C
Solar/Wind Harmer
0.537
3146033SCOT NK
Solar/Wind Harmer
-0.038
3151361ROSEMG1
50/50
0.42
3151371ROSEMS1
50/50
0.26
3151381ROSEMG2
50/50
0.197
3144356SAPONY
Solar/Wind Harmer
0.955
316181AB2-040 GEN
Solar/Wind Harmer
1.913
3145796HORNRTN
Solar/Wind Harmer
-0.039
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3151391GASTONA
50/50
0.329
3151411GASTONB
50/50
0.329
3147043LAWRENC
50/50
1.152
316023GEN1_S
Solar/Wind Harmer
1.24
960081AF2-299 GEN
Solar/Wind Harmer
1.766
971795AH1-408 GEN
Solar/Wind Harmer
10.639
316011AB1-132 GEN
Solar/Wind Harmer
2.863
962571AG1-106 GEN
Solar/Wind Harmer
1.967
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
3145783HORNRTN
Solar/Wind Harmer
-0.011
315722AD1-056 GEN
Solar/Wind Harmer
1.174
316190AA2-174 GEN
Solar/Wind Harmer
0.135
970919AG2-571 GEN
Solar/Wind Harmer
3.143
970087AG2-069 GEN
Solar/Wind Harmer
9.272
940641AE2-051 GEN
Solar/Wind Harmer
9.271
316212AC1-099_GEN
Solar/Wind Harmer
0.858
316129AC1-054 GEN
Solar/Wind Harmer
0.853
3146233WITAKRS
Solar/Wind Harmer
-0.038
316359AB2-059 GEN
Solar/Wind Harmer
1.293
316049AB1-081 GEN
Solar/Wind Harmer
1.035
3142053HEARTS
Solar/Wind Harmer
0.113
971065AG2-659 GEN
Solar/Wind Harmer
4.783
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.009
961671AG1-007 GEN
Solar/Wind Harmer
0.116
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.271
3145823KELFORD
Solar/Wind Harmer
-0.009
957481AF2-042 GEN
Solar/Wind Harmer
27.804
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316420AA1-050 GEN
Solar/Wind Harmer
1.023
957861AF2-080 GEN
Solar/Wind Harmer
3.811
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.075
961941AG1-037 GEN
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.009
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316239AB2-077_GEN
Solar/Wind Harmer
0.253
316238AB2-078_GEN
Solar/Wind Harmer
0.253
965291AG1-394 GEN
Solar/Wind Harmer
0.741
316005AA1-067
Solar/Wind Harmer
0.166
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.077
316118AC1-105 GEN
Solar/Wind Harmer
0.517
971443AH1-215 GEN
Solar/Wind Harmer
1.448
3144303KENBRDG
Solar/Wind Harmer
-0.006
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.184
970683AG2-441 GEN
Solar/Wind Harmer
5.324
970681AG2-440 GEN
Solar/Wind Harmer
4.26
315732AD1-074 GEN1
Solar/Wind Harmer
1.344
315733AD1-074 GEN2
Solar/Wind Harmer
1.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.672
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.627
961791AG1-021 GEN
Solar/Wind Harmer
0.793
3143316POE
Solar/Wind Helper
2.108
316132AB2-190 GEN1
Solar/Wind Helper
1.594
316369SG1_INVT
Solar/Wind Helper
1.025
316312AB1-027
Solar/Wind Helper
0.336
3143873LANEXA
Solar/Wind Helper
0.097
316233AE1-074 FULL
Solar/Wind Helper
0.221
315662AE1-191 GEN
Solar/Wind Helper
0.675
315666AE1-190 GEN
Solar/Wind Helper
0.169
316059AD1-063 C
Solar/Wind Helper
0.123
3141813NORNECK
Solar/Wind Helper
0.115
3141783LANCAST
Solar/Wind Helper
0.069
3141783LANCAST
Solar/Wind Helper
0.046
3138133OCRAN
Solar/Wind Helper
0.034
3141913WHIT STONE
Solar/Wind Helper
0.114
957601AF2-054 GEN
Solar/Wind Helper
0.153
3141873WAN 176
Solar/Wind Helper
0.023
316494AC1-189 GEN
Solar/Wind Harmer
0.937
3145683EARLEYS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
316237AB2-079_GEN
Solar/Wind Harmer
0.253
315693AD1-088 GEN
Solar/Wind Harmer
4.145
939411AE1-173 GEN
Solar/Wind Harmer
41.056
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
962491AG1-098 GEN
Solar/Wind Harmer
5.46
315687AD1-152 GEN
Solar/Wind Harmer
0.971
3146293MARTNCO
Solar/Wind Harmer
0.049
970401AG2-262 GEN
Solar/Wind Harmer
0.507
316174AB2-169 GEN
Solar/Wind Harmer
1.149
3145963POPLR C
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.82
316003AC1-222 GEN
Solar/Wind Harmer
0.671
970685AG2-442 GEN
Solar/Wind Harmer
5.963
963171AG1-166 GEN
Solar/Wind Harmer
0.793
971563AH1-280 GEN
Solar/Wind Harmer
0.793
3144293JTRSVLE
Adder
0.18
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
0.882
3142416OLDCHRC
Solar/Wind Helper
0.459
3142416OLDCHRC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.751
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.159
3141726DUNNSVL
Solar/Wind Helper
0.473
3138133OCRAN
Solar/Wind Helper
0.069
316337AD2-073 GEN
Solar/Wind Helper
0.17
3151391GASTONA
50/50
0.329
3151411GASTONB
50/50
0.329
316365GEN2_N
Solar/Wind Harmer
1.24
966621AG1-532 GEN
Solar/Wind Harmer
0.319
313506AB2-031 GEN
Solar/Wind Harmer
1.102
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
0.646
970917AG2-570 GEN
Solar/Wind Harmer
24.829
316327AA2-057 GEN
Solar/Wind Harmer
0.997
316210AC1-098 GEN
Solar/Wind Harmer
1.544
3146233WITAKRS
Solar/Wind Harmer
0.203
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.852
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.009
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.428
3145823KELFORD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.14
316140AB2-099
Solar/Wind Harmer
0.058
962331AG1-082 GEN
Solar/Wind Harmer
1.078
3146173TUNIS
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
0.737
316486AD2-202 GEN
Solar/Wind Harmer
0.216
957521AF2-046 GEN
Solar/Wind Harmer
6.683
961681AG1-008 GEN
Solar/Wind Harmer
6.683
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
316131AB2-060 GEN
Solar/Wind Harmer
0.9
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.102
3156081AA2-088 GEN
Solar/Wind Harmer
2.638
964241AG1-285 GEN
Solar/Wind Harmer
6.272
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
0.99
315785AD2-033 C
Solar/Wind Harmer
1.701
3145963POPLR C
Solar/Wind Harmer
-0.007
970257AG2-171 GEN
Solar/Wind Harmer
2.741
316248AF1-058 C
Solar/Wind Harmer
0.22
960061AF2-297 GEN
Solar/Wind Harmer
3.644
3146206CASHIE
Solar/Wind Harmer
-0.007
959311AF2-222 GEN
Solar/Wind Harmer
7.482
316283AC2-100 C
Solar/Wind Harmer
0.635
315737AD1-076 GEN
Solar/Wind Harmer
1.263
971157AH1-035 GEN
Solar/Wind Harmer
0.816
971683AH1-343 GEN
Solar/Wind Harmer
2.812
963181AG1-167 GEN
Solar/Wind Harmer
0.595
3144293JTRSVLE
Adder
0.18
315839AE2-212 C
Solar/Wind Helper
1.129
3142946ENON
Solar/Wind Helper
0.076
316473AC1-191 GEN
Solar/Wind Helper
1.222
316280AD1-041 GEN
Solar/Wind Helper
0.422
316404AE1-155 C
Solar/Wind Helper
0.97
316484AD2-074 GEN
Solar/Wind Helper
0.222
316156AD2-030 GEN
Solar/Wind Helper
0.172
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
966811AG1-552 GEN
Solar/Wind Harmer
1.292
3145593CAROLNA
Solar/Wind Harmer
0.095
3145783HORNRTN
Solar/Wind Harmer
1.339
3145783HORNRTN
Solar/Wind Harmer
1.072
3145783HORNRTN
Solar/Wind Harmer
0.335
3145783HORNRTN
Solar/Wind Harmer
0.134
316426AA2-053 GEN
Solar/Wind Harmer
1.11
972185AH1-677 GEN
Adder
5.222
972187AH1-678 GEN
Adder
2.613
316274AC1-208 GEN
Solar/Wind Harmer
1.104
970933AG2-581 GEN
Solar/Wind Harmer
9.288
961601AG1-000A GEN
Solar/Wind Harmer
3.804
316263AC1-034 GEN
Solar/Wind Harmer
4.494
3145493TOT1
Solar/Wind Harmer
0.141
3145453TOT5
Solar/Wind Harmer
0.085
3145603CNETO
Solar/Wind Harmer
0.057
970099AG2-077 GEN
Solar/Wind Harmer
11.121
939181AE1-148 GEN
Solar/Wind Harmer
4.902
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
1.368
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.423
964791AG1-342 GEN
Solar/Wind Harmer
1.658
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
3.655
971775AH1-396 GEN
Solar/Wind Harmer
0.52
316034AC1-036 C
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
3.523
316222AC1-221 GEN
Solar/Wind Harmer
0.685
971741AH1-377 GEN
Solar/Wind Harmer
7.461
958211AF2-115 GEN
Solar/Wind Harmer
0.992
963191AG1-168 GEN
Solar/Wind Harmer
0.595
3144293JTRSVLE
Adder
0.18
3144293JTRSVLE
Adder
0.151
316240AF1-291 C
Solar/Wind Helper
0.715
3142946ENON
Solar/Wind Helper
0.023
316033AB2-134 GEN
Solar/Wind Helper
0.733
315697AD1-025 GEN
Solar/Wind Helper
2.437
966871AG1-558 GEN
Solar/Wind Helper
0.269
316075AC2-137 C
Solar/Wind Helper
0.27
316468AD1-105 GEN
Solar/Wind Helper
0.837
3143526WINTERP
Solar/Wind Helper
0.751
316077AC2-138 C
Solar/Wind Helper
0.108
316487AF1-042 GEN
Solar/Wind Helper
0.116
NYPJM->LTFIMP_NY
CLTF
0.476
LAGNLTFEXP_LAGN->PJM
CLTF
3.172
LGEELTFEXP_LGEE->PJM
CLTF
0.565
WECLTFEXP_WEC->PJM
CLTF
0.297
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.949
TVALTFEXP_TVA->PJM
CLTF
1.578
CPLELTFEXP_CPLE->PJM
CLTF
4.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.414
MECLTFEXP_MEC->PJM
CLTF
1.572
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2002-2003_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2002-2003_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.5 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1234.13
MW Contribution:5.25
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.321
3151411GASTONB
50/50
0.321
316365GEN2_N
Solar/Wind Harmer
1.225
966621AG1-532 GEN
Solar/Wind Harmer
0.313
313506AB2-031 GEN
Solar/Wind Harmer
1.073
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
0.628
970917AG2-570 GEN
Solar/Wind Harmer
24.537
316327AA2-057 GEN
Solar/Wind Harmer
0.959
316210AC1-098 GEN
Solar/Wind Harmer
1.474
961601AG1-000A GEN
Solar/Wind Harmer
3.733
3146233WITAKRS
Solar/Wind Harmer
0.196
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3146263WOODLND
Solar/Wind Harmer
-0.009
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.402
3145823KELFORD
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
0.727
316486AD2-202 GEN
Solar/Wind Harmer
0.213
316131AB2-060 GEN
Solar/Wind Harmer
0.883
316463AE2-346 GEN
Solar/Wind Harmer
0.128
316140AB2-099
Solar/Wind Harmer
0.053
962331AG1-082 GEN
Solar/Wind Harmer
0.989
964241AG1-285 GEN
Solar/Wind Harmer
6.156
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.026
957521AF2-046 GEN
Solar/Wind Harmer
5.914
961681AG1-008 GEN
Solar/Wind Harmer
5.914
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.935
3145893MURPHYS
Solar/Wind Harmer
0.052
3145893MURPHYS
Solar/Wind Harmer
-0.007
315785AD2-033 C
Solar/Wind Harmer
1.671
970257AG2-171 GEN
Solar/Wind Harmer
2.693
316248AF1-058 C
Solar/Wind Harmer
0.216
3151361ROSEMG1
50/50
0.41
3151371ROSEMS1
50/50
0.254
3151381ROSEMG2
50/50
0.192
3144356SAPONY
Solar/Wind Harmer
0.955
316181AB2-040 GEN
Solar/Wind Harmer
1.863
3145796HORNRTN
Solar/Wind Harmer
-0.038
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
966811AG1-552 GEN
Solar/Wind Harmer
1.239
3145593CAROLNA
Solar/Wind Harmer
0.092
3145783HORNRTN
Solar/Wind Harmer
1.285
3145783HORNRTN
Solar/Wind Harmer
1.028
3145783HORNRTN
Solar/Wind Harmer
0.321
3145783HORNRTN
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
1.06
972185AH1-677 GEN
Adder
5.166
972187AH1-678 GEN
Adder
2.584
316274AC1-208 GEN
Solar/Wind Harmer
1.058
970933AG2-581 GEN
Solar/Wind Harmer
9.183
961601AG1-000A GEN
Solar/Wind Harmer
3.686
316263AC1-034 GEN
Solar/Wind Harmer
4.351
3145493TOT1
Solar/Wind Harmer
0.136
3145453TOT5
Solar/Wind Harmer
0.082
3145603CNETO
Solar/Wind Harmer
0.054
970099AG2-077 GEN
Solar/Wind Harmer
10.98
939181AE1-148 GEN
Solar/Wind Harmer
4.79
313527AB2-043 GEN
Solar/Wind Harmer
1.342
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.343
964791AG1-342 GEN
Solar/Wind Harmer
1.628
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.207
3145893MURPHYS
Solar/Wind Harmer
-0.013
970323AG2-213 GEN
Solar/Wind Harmer
3.59
971775AH1-396 GEN
Solar/Wind Harmer
0.511
316034AC1-036 C
Solar/Wind Harmer
0.133
316222AC1-221 GEN
Solar/Wind Harmer
0.672
316065AD1-022 GEN
Solar/Wind Harmer
3.235
971741AH1-377 GEN
Solar/Wind Harmer
7.368
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.712
315697AD1-025 GEN
Solar/Wind Helper
2.367
966871AG1-558 GEN
Solar/Wind Helper
0.264
316075AC2-137 C
Solar/Wind Helper
0.264
316468AD1-105 GEN
Solar/Wind Helper
0.819
3143526WINTERP
Solar/Wind Helper
0.731
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.114
3151391GASTONA
50/50
0.321
3151411GASTONB
50/50
0.321
3147043LAWRENC
50/50
1.133
316023GEN1_S
Solar/Wind Harmer
1.225
960081AF2-299 GEN
Solar/Wind Harmer
1.737
971795AH1-408 GEN
Solar/Wind Harmer
10.457
316011AB1-132 GEN
Solar/Wind Harmer
2.793
962571AG1-106 GEN
Solar/Wind Harmer
1.919
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.013
315722AD1-056 GEN
Solar/Wind Harmer
1.141
3145783HORNRTN
Solar/Wind Harmer
-0.011
316190AA2-174 GEN
Solar/Wind Harmer
0.129
970919AG2-571 GEN
Solar/Wind Harmer
3.106
970087AG2-069 GEN
Solar/Wind Harmer
9.162
940641AE2-051 GEN
Solar/Wind Harmer
9.147
316129AC1-054 GEN
Solar/Wind Harmer
0.826
316212AC1-099_GEN
Solar/Wind Harmer
0.819
3146233WITAKRS
Solar/Wind Harmer
-0.037
316359AB2-059 GEN
Solar/Wind Harmer
1.251
316049AB1-081 GEN
Solar/Wind Harmer
1.001
971065AG2-659 GEN
Solar/Wind Harmer
4.641
3142053HEARTS
Solar/Wind Harmer
0.109
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.009
961671AG1-007 GEN
Solar/Wind Harmer
0.111
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.261
957481AF2-042 GEN
Solar/Wind Harmer
27.45
3145823KELFORD
Solar/Wind Harmer
-0.009
316494AC1-189 GEN
Solar/Wind Harmer
0.897
316237AB2-079_GEN
Solar/Wind Harmer
0.248
315693AD1-088 GEN
Solar/Wind Harmer
4.091
3145683EARLEYS
Solar/Wind Harmer
-0.008
962491AG1-098 GEN
Solar/Wind Harmer
5.389
939411AE1-173 GEN
Solar/Wind Harmer
39.812
315687AD1-152 GEN
Solar/Wind Harmer
0.957
3145746EVERETS
Solar/Wind Harmer
-0.008
960061AF2-297 GEN
Solar/Wind Harmer
3.582
959311AF2-222 GEN
Solar/Wind Harmer
7.351
3145963POPLR C
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.211
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.623
971683AH1-343 GEN
Solar/Wind Harmer
2.764
315839AE2-212 C
Solar/Wind Helper
1.117
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.195
316280AD1-041 GEN
Solar/Wind Helper
0.415
316404AE1-155 C
Solar/Wind Helper
0.954
316484AD2-074 GEN
Solar/Wind Helper
0.218
316156AD2-030 GEN
Solar/Wind Helper
0.17
3145746EVERETS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970401AG2-262 GEN
Solar/Wind Harmer
0.498
3146293MARTNCO
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145893MURPHYS
Solar/Wind Harmer
0.22
316174AB2-169 GEN
Solar/Wind Harmer
1.073
3145963POPLR C
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.66
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.676
970685AG2-442 GEN
Solar/Wind Harmer
5.862
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.536
316381AD1-082 GEN
Solar/Wind Helper
1.166
3142433PROV 92
Solar/Wind Helper
0.862
3142416OLDCHRC
Solar/Wind Helper
0.45
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.731
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
315779AE2-040
50/50
3.401
316315AB2-025 C
Solar/Wind Harmer
0.739
315814AE2-033 C
Solar/Wind Harmer
25.048
946281AF1-292 GEN
Solar/Wind Harmer
0.346
316087AB2-174 GEN
Solar/Wind Harmer
1.995
315652AC1-086 GEN
Solar/Wind Harmer
15.018
3145796HORNRTN
Solar/Wind Harmer
-0.041
3145796HORNRTN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.048
941031AE2-094 GEN
Solar/Wind Harmer
20.02
944011AF1-069 GEN
Solar/Wind Harmer
6.273
970673AG2-436 GEN
Solar/Wind Harmer
21.964
970673AG2-436 GEN
Solar/Wind Harmer
11.121
971967AH1-528 GEN
Solar/Wind Harmer
19.187
970085AG2-068 GEN
Solar/Wind Harmer
6.108
970581AG2-369 GEN
Solar/Wind Harmer
5.253
970831AG2-522 GEN
Solar/Wind Harmer
4.789
315607AA1-063A GEN
Solar/Wind Harmer
0.957
316319Z2-044 C
Solar/Wind Harmer
0.518
3146043SEABORD
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.036
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316420AA1-050 GEN
Solar/Wind Harmer
0.982
957861AF2-080 GEN
Solar/Wind Harmer
3.647
316239AB2-077_GEN
Solar/Wind Harmer
0.248
316238AB2-078_GEN
Solar/Wind Harmer
0.248
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.069
961941AG1-037 GEN
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
-0.008
316005AA1-067
Solar/Wind Harmer
0.158
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.022
316318V4-068
Solar/Wind Harmer
0.185
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
316118AC1-105 GEN
Solar/Wind Harmer
0.508
971443AH1-215 GEN
Solar/Wind Harmer
1.422
3144303KENBRDG
Solar/Wind Harmer
-0.006
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.004
965291AG1-394 GEN
Solar/Wind Harmer
0.631
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.933
970683AG2-441 GEN
Solar/Wind Harmer
5.234
970681AG2-440 GEN
Solar/Wind Harmer
4.187
316132AB2-190 GEN1
Solar/Wind Helper
1.536
316369SG1_INVT
Solar/Wind Helper
0.996
316312AB1-027
Solar/Wind Helper
0.329
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.215
315662AE1-191 GEN
Solar/Wind Helper
0.665
315666AE1-190 GEN
Solar/Wind Helper
0.166
316059AD1-063 C
Solar/Wind Helper
0.121
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3138133OCRAN
Solar/Wind Helper
0.034
3141913WHIT STONE
Solar/Wind Helper
0.113
957601AF2-054 GEN
Solar/Wind Helper
0.151
3141873WAN 176
Solar/Wind Helper
0.023
NYPJM->LTFIMP_NY
CLTF
0.462
LGEELTFEXP_LGEE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
3.111
WECLTFEXP_WEC->PJM
CLTF
0.292
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.739
TVALTFEXP_TVA->PJM
CLTF
1.548
CPLELTFEXP_CPLE->PJM
CLTF
4.585
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.511
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.387
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.545
SIGELTFEXP_SIGE->PJM
CLTF
0.046

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.37 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1090.34
MW Contribution:5.66
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
2.287
316315AB2-025 C
Solar/Wind Harmer
0.497
315814AE2-033 C
Solar/Wind Harmer
16.859
941031AE2-094 GEN
Solar/Wind Harmer
21.947
944011AF1-069 GEN
Solar/Wind Harmer
6.877
970673AG2-436 GEN
Solar/Wind Harmer
23.989
970673AG2-436 GEN
Solar/Wind Harmer
12.146
971967AH1-528 GEN
Solar/Wind Harmer
20.889
946281AF1-292 GEN
Solar/Wind Harmer
0.247
970085AG2-068 GEN
Solar/Wind Harmer
6.581
970581AG2-369 GEN
Solar/Wind Harmer
5.659
316087AB2-174 GEN
Solar/Wind Harmer
1.435
315652AC1-086 GEN
Solar/Wind Harmer
10.732
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970831AG2-522 GEN
Solar/Wind Harmer
3.941
316239AB2-077_GEN
Solar/Wind Harmer
0.227
316238AB2-078_GEN
Solar/Wind Harmer
0.227
316319Z2-044 C
Solar/Wind Harmer
0.404
316118AC1-105 GEN
Solar/Wind Harmer
0.494
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.004
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
971443AH1-215 GEN
Solar/Wind Harmer
1.328
3144303KENBRDG
Solar/Wind Harmer
-0.005
316420AA1-050 GEN
Solar/Wind Harmer
0.767
3146033SCOT NK
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
0.664
957861AF2-080 GEN
Solar/Wind Harmer
2.835
970683AG2-441 GEN
Solar/Wind Harmer
4.967
970681AG2-440 GEN
Solar/Wind Harmer
3.974
3146043SEABORD
Solar/Wind Harmer
-0.006
3143316POE
Solar/Wind Helper
4.547
316349AD2-085 GEN
Solar/Wind Helper
0.918
316132AB2-190 GEN1
Solar/Wind Helper
0.843
316369SG1_INVT
Solar/Wind Helper
0.552
316365GEN2_N
Solar/Wind Harmer
0.85
966621AG1-532 GEN
Solar/Wind Harmer
0.224
970917AG2-570 GEN
Solar/Wind Harmer
26.461
3147043LAWRENC
Solar/Wind Harmer
-0.006
313506AB2-031 GEN
Solar/Wind Harmer
0.775
3145796HORNRTN
Solar/Wind Harmer
-0.037
3145796HORNRTN
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
0.761
316486AD2-202 GEN
Solar/Wind Harmer
0.223
315724AD1-057 GEN
Solar/Wind Harmer
0.474
316131AB2-060 GEN
Solar/Wind Harmer
0.805
961601AG1-000A GEN
Solar/Wind Harmer
2.948
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146233WITAKRS
Solar/Wind Harmer
0.153
3146233WITAKRS
Solar/Wind Harmer
-0.005
316327AA2-057 GEN
Solar/Wind Harmer
0.738
964241AG1-285 GEN
Solar/Wind Harmer
5.653
316248AF1-058 C
Solar/Wind Harmer
0.214
960061AF2-297 GEN
Solar/Wind Harmer
3.544
316210AC1-098 GEN
Solar/Wind Harmer
1.102
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
315785AD2-033 C
Solar/Wind Harmer
1.554
970257AG2-171 GEN
Solar/Wind Harmer
2.519
959311AF2-222 GEN
Solar/Wind Harmer
6.903
316283AC2-100 C
Solar/Wind Harmer
0.61
971683AH1-343 GEN
Solar/Wind Harmer
2.74
3146263WOODLND
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Harmer
0.642
972185AH1-677 GEN
Adder
5.631
972187AH1-678 GEN
Adder
2.809
970933AG2-581 GEN
Solar/Wind Harmer
9.937
316181AB2-040 GEN
Solar/Wind Harmer
1.344
970099AG2-077 GEN
Solar/Wind Harmer
11.655
3145796HORNRTN
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.907
3145593CAROLNA
Solar/Wind Harmer
0.067
3145783HORNRTN
Solar/Wind Harmer
0.944
3145783HORNRTN
Solar/Wind Harmer
0.755
3145783HORNRTN
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
0.094
939181AE1-148 GEN
Solar/Wind Harmer
4.338
316426AA2-053 GEN
Solar/Wind Harmer
0.772
313527AB2-043 GEN
Solar/Wind Harmer
1.222
961601AG1-000A GEN
Solar/Wind Harmer
2.911
316274AC1-208 GEN
Solar/Wind Harmer
0.796
316263AC1-034 GEN
Solar/Wind Harmer
3.445
962561AG1-105 GEN
Solar/Wind Harmer
4.11
964791AG1-342 GEN
Solar/Wind Harmer
1.553
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.107
3145453TOT5
Solar/Wind Harmer
0.064
3145603CNETO
Solar/Wind Harmer
0.043
971741AH1-377 GEN
Solar/Wind Harmer
7.84
970323AG2-213 GEN
Solar/Wind Harmer
3.358
971775AH1-396 GEN
Solar/Wind Harmer
0.478
316034AC1-036 C
Solar/Wind Harmer
0.124
316222AC1-221 GEN
Solar/Wind Harmer
0.659
316240AF1-291 C
Solar/Wind Helper
0.453
316033AB2-134 GEN
Solar/Wind Helper
0.395
315697AD1-025 GEN
Solar/Wind Helper
1.313
316023GEN1_S
Solar/Wind Harmer
0.85
960081AF2-299 GEN
Solar/Wind Harmer
1.242
970919AG2-571 GEN
Solar/Wind Harmer
3.349
970087AG2-069 GEN
Solar/Wind Harmer
9.871
971795AH1-408 GEN
Solar/Wind Harmer
7.73
3147043LAWRENC
Adder
0.803
316011AB1-132 GEN
Solar/Wind Harmer
1.996
962571AG1-106 GEN
Solar/Wind Harmer
1.371
957481AF2-042 GEN
Solar/Wind Harmer
29.137
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.009
315693AD1-088 GEN
Solar/Wind Harmer
4.318
962491AG1-098 GEN
Solar/Wind Harmer
5.69
315722AD1-056 GEN
Solar/Wind Harmer
0.862
315687AD1-152 GEN
Solar/Wind Harmer
0.987
939411AE1-173 GEN
Solar/Wind Harmer
40.565
3145783HORNRTN
Solar/Wind Harmer
-0.008
316129AC1-054 GEN
Solar/Wind Harmer
0.689
971065AG2-659 GEN
Solar/Wind Harmer
3.922
316190AA2-174 GEN
Solar/Wind Harmer
0.094
316237AB2-079_GEN
Solar/Wind Harmer
0.227
316359AB2-059 GEN
Solar/Wind Harmer
0.991
316049AB1-081 GEN
Solar/Wind Harmer
0.793
3142053HEARTS
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.029
970401AG2-262 GEN
Solar/Wind Harmer
0.474
316212AC1-099_GEN
Solar/Wind Harmer
0.612
961671AG1-007 GEN
Solar/Wind Harmer
0.087
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.205
316003AC1-222 GEN
Solar/Wind Harmer
0.654
316494AC1-189 GEN
Solar/Wind Harmer
0.697
970685AG2-442 GEN
Solar/Wind Harmer
5.563
3146263WOODLND
Solar/Wind Harmer
-0.006
316381AD1-082 GEN
Solar/Wind Helper
2.389
316458AB2-190 GEN2
Solar/Wind Helper
0.843
3142543TWELFTH
Solar/Wind Helper
0.012
NYPJM->LTFIMP_NY
CLTF
0.501
LAGNLTFEXP_LAGN->PJM
CLTF
3.039
LGEELTFEXP_LGEE->PJM
CLTF
0.546
WECLTFEXP_WEC->PJM
CLTF
0.286
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.403
TVALTFEXP_TVA->PJM
CLTF
1.514
CPLELTFEXP_CPLE->PJM
CLTF
4.36
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.138
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.201
MECLTFEXP_MEC->PJM
CLTF
1.511
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 249_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 249_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.58 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:845.48
MW Contribution:3.15
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
0.317
3151371ROSEMS1
50/50
0.196
3151381ROSEMG2
50/50
0.148
970533AG2-339 GEN
50/50
6.689
970531AG2-338 GEN
50/50
2.675
315242AE2-183_GT2
50/50
1.203
315241AE2-183_GT1
50/50
1.196
972185AH1-677 GEN
50/50
4.338
3151041BRUNSWICKG3
50/50
0.945
972187AH1-678 GEN
50/50
2.169
970535AG2-341 GEN
50/50
1.039
3144356SAPONY
Solar/Wind Harmer
1.648
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145796HORNRTN
Solar/Wind Harmer
0.264
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
3142666NORTHAMPTON
Solar/Wind Harmer
0.052
3145593CAROLNA
Solar/Wind Harmer
0.074
3145593CAROLNA
Solar/Wind Harmer
0.074
966811AG1-552 GEN
Solar/Wind Harmer
0.8
3145593CAROLNA
Solar/Wind Harmer
0.092
3145783HORNRTN
Solar/Wind Harmer
1.288
3145783HORNRTN
Solar/Wind Harmer
1.031
3145783HORNRTN
Solar/Wind Harmer
0.322
3145783HORNRTN
Solar/Wind Harmer
0.129
316426AA2-053 GEN
Solar/Wind Harmer
0.235
970933AG2-581 GEN
Solar/Wind Harmer
5.516
316274AC1-208 GEN
Solar/Wind Harmer
0.34
961601AG1-000A GEN
Solar/Wind Harmer
1.135
316263AC1-034 GEN
Solar/Wind Harmer
2.397
970099AG2-077 GEN
Solar/Wind Harmer
6.585
3145493TOT1
Solar/Wind Harmer
0.137
3145453TOT5
Solar/Wind Harmer
0.082
3145603CNETO
Solar/Wind Harmer
0.055
939181AE1-148 GEN
Solar/Wind Harmer
2.827
313527AB2-043 GEN
Solar/Wind Harmer
0.001
316240AF1-291 C
Solar/Wind Helper
0.668
316033AB2-134 GEN
Solar/Wind Helper
0.639
315697AD1-025 GEN
Solar/Wind Helper
2.123
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.09
3151031BRUNSWICKG2
50/50
0.945
3151591KERR 2
50/50
0.122
970413AG2-270 GEN
50/50
5.504
316365GEN2_N
Solar/Wind Harmer
0.287
3147043LAWRENC
Solar/Wind Harmer
0.056
313506AB2-031 GEN
Solar/Wind Harmer
0.284
3145796HORNRTN
Solar/Wind Harmer
0.352
3145796HORNRTN
Solar/Wind Harmer
0.088
3142666NORTHAMPTON
Solar/Wind Harmer
0.086
315724AD1-057 GEN
Solar/Wind Harmer
0.281
970917AG2-570 GEN
Solar/Wind Harmer
6.136
961601AG1-000A GEN
Solar/Wind Harmer
4.539
316327AA2-057 GEN
Solar/Wind Harmer
0.096
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.198
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.615
3147043LAWRENC
50/50
0.889
3151391GASTONA
50/50
0.249
3151411GASTONB
50/50
0.249
3151261ROARAP2
50/50
0.092
315243AE2-183_GT3
50/50
1.203
3151051BRUNSWICKS1
50/50
1.962
3151021BRUNSWICKG1
50/50
0.945
971451AH1-221 GEN
50/50
2.871
3151601KERR 3
50/50
0.122
3151581KERR 1
50/50
0.044
3151531CLOVER1
50/50
1.261
316023GEN1_S
Solar/Wind Harmer
0.287
960081AF2-299 GEN
Solar/Wind Harmer
1.037
971795AH1-408 GEN
Solar/Wind Harmer
6.499
316011AB1-132 GEN
Solar/Wind Harmer
1.672
962571AG1-106 GEN
Solar/Wind Harmer
1.309
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.088
315722AD1-056 GEN
Solar/Wind Harmer
0.473
3145783HORNRTN
Solar/Wind Harmer
0.072
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
5.498
940641AE2-051 GEN
Solar/Wind Harmer
5.458
316129AC1-054 GEN
Solar/Wind Harmer
0.242
971065AG2-659 GEN
Solar/Wind Harmer
2.706
3146233WITAKRS
Solar/Wind Harmer
0.252
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.361
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
316212AC1-099_GEN
Solar/Wind Harmer
0.322
957481AF2-042 GEN
Solar/Wind Harmer
16.463
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3146083TARBORO
Solar/Wind Harmer
0.059
3145493TOT1
Solar/Wind Harmer
0.263
315693AD1-088 GEN
Solar/Wind Harmer
2.76
316237AB2-079_GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.057
962491AG1-098 GEN
Solar/Wind Harmer
3.232
316381AD1-082 GEN
Solar/Wind Helper
2.648
316458AB2-190 GEN2
Solar/Wind Helper
1.354
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.592
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
3146233WITAKRS
Solar/Wind Harmer
0.318
3146233WITAKRS
Solar/Wind Harmer
0.043
3138543CONSLDL
Solar/Wind Harmer
0.042
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316210AC1-098 GEN
Solar/Wind Harmer
0.577
3146073TAR RVR
Solar/Wind Harmer
0.059
3146083TARBORO
Solar/Wind Harmer
0.059
316478AD1-087 GEN
Solar/Wind Harmer
0.206
316486AD2-202 GEN
Solar/Wind Harmer
0.06
316131AB2-060 GEN
Solar/Wind Harmer
0.179
3146263WOODLND
Solar/Wind Harmer
0.057
315839AE2-212 C
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.896
315779AE2-040
50/50
2.75
3151281ROARAP4
50/50
0.089
3151281ROARAP4
50/50
0.084
315244AE2-183_ST
50/50
2.08
963041AG1-153 GEN
50/50
1.914
3151611KERR 4
50/50
0.122
3151621KERR 5
50/50
0.122
3151631KERR 6
50/50
0.122
3151641KERR 7
50/50
0.122
3151541CLOVER2
50/50
1.255
316315AB2-025 C
Solar/Wind Harmer
0.159
315814AE2-033 C
Solar/Wind Harmer
15.301
316087AB2-174 GEN
Solar/Wind Harmer
0.003
315652AC1-086 GEN
Solar/Wind Harmer
10.118
3145796HORNRTN
Solar/Wind Harmer
0.281
3145796HORNRTN
Solar/Wind Harmer
0.035
3137643SOCKMAN
Solar/Wind Harmer
0.328
941031AE2-094 GEN
Solar/Wind Harmer
13.859
944011AF1-069 GEN
Solar/Wind Harmer
4.528
970673AG2-436 GEN
Solar/Wind Harmer
15.712
970673AG2-436 GEN
Solar/Wind Harmer
10.474
971967AH1-528 GEN
Solar/Wind Harmer
11.501
970085AG2-068 GEN
Solar/Wind Harmer
3.665
970581AG2-369 GEN
Solar/Wind Harmer
3.152
970831AG2-522 GEN
Solar/Wind Harmer
2.782
316319Z2-044 C
Solar/Wind Harmer
0
315607AA1-063A GEN
Solar/Wind Harmer
0.121
3145573BETHELC
Solar/Wind Harmer
0.059
3145573BETHELC
Solar/Wind Harmer
0.059
3146033SCOT NK
Solar/Wind Harmer
0.235
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316239AB2-077_GEN
Solar/Wind Harmer
0
316238AB2-078_GEN
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.057
3143316POE
Solar/Wind Helper
4.642
316132AB2-190 GEN1
Solar/Wind Helper
1.354
316349AD2-085 GEN
Solar/Wind Helper
1.038
316369SG1_INVT
Solar/Wind Helper
0.893
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.07
NYPJM->LTFIMP_NY
CLTF
0.342
LAGNLTFEXP_LAGN->PJM
CLTF
2.457
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.602
TVALTFEXP_TVA->PJM
CLTF
1.222
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.204
MECLTFEXP_MEC->PJM
CLTF
1.237
SIGELTFEXP_SIGE->PJM
CLTF
0.037

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.29 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:789.26
MW Contribution:3.28
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
7.009
970531AG2-338 GEN
50/50
2.804
315242AE2-183_GT2
50/50
1.258
315241AE2-183_GT1
50/50
1.25
972185AH1-677 GEN
50/50
4.534
3151041BRUNSWICKG3
50/50
0.987
972187AH1-678 GEN
50/50
2.264
3151361ROSEMG1
50/50
0.269
3151371ROSEMS1
50/50
0.167
3151381ROSEMG2
50/50
0.126
3144356SAPONY
Solar/Wind Harmer
1.251
316181AB2-040 GEN
Solar/Wind Harmer
0.112
3145796HORNRTN
Solar/Wind Harmer
0.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
970933AG2-581 GEN
Solar/Wind Harmer
5.741
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
966811AG1-552 GEN
Solar/Wind Harmer
0.703
3145593CAROLNA
Solar/Wind Harmer
0.081
3145783HORNRTN
Solar/Wind Harmer
1.137
3145783HORNRTN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.284
3145783HORNRTN
Solar/Wind Harmer
0.114
970099AG2-077 GEN
Solar/Wind Harmer
6.784
316426AA2-053 GEN
Solar/Wind Harmer
0.209
316274AC1-208 GEN
Solar/Wind Harmer
0.307
961601AG1-000A GEN
Solar/Wind Harmer
1.034
316263AC1-034 GEN
Solar/Wind Harmer
2.189
316240AF1-291 C
Solar/Wind Helper
0.46
3147043LAWRENC
50/50
0.75
3151391GASTONA
50/50
0.21
3151411GASTONB
50/50
0.21
315243AE2-183_GT3
50/50
1.258
3151051BRUNSWICKS1
50/50
2.048
3151021BRUNSWICKG1
50/50
0.987
971451AH1-221 GEN
50/50
2.997
3151261ROARAP2
50/50
0.081
3151531CLOVER1
50/50
1.291
3151601KERR 3
50/50
0.117
3151581KERR 1
50/50
0.042
316023GEN1_S
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
0.85
971795AH1-408 GEN
Solar/Wind Harmer
5.427
316011AB1-132 GEN
Solar/Wind Harmer
1.409
962571AG1-106 GEN
Solar/Wind Harmer
1.102
3145796HORNRTN
Solar/Wind Harmer
0.246
3145796HORNRTN
Solar/Wind Harmer
0.075
940641AE2-051 GEN
Solar/Wind Harmer
5.897
3151391GASTONA
50/50
0.21
3151411GASTONB
50/50
0.21
3151031BRUNSWICKG2
50/50
0.987
3151261ROARAP2
50/50
0.079
970413AG2-270 GEN
50/50
5.635
3151591KERR 2
50/50
0.117
316365GEN2_N
Solar/Wind Harmer
0.229
3147043LAWRENC
Solar/Wind Harmer
0.047
313506AB2-031 GEN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.299
3145796HORNRTN
Solar/Wind Harmer
0.075
3142666NORTHAMPTON
Solar/Wind Harmer
0.073
970917AG2-570 GEN
Solar/Wind Harmer
6.384
315724AD1-057 GEN
Solar/Wind Harmer
0.246
316478AD1-087 GEN
Solar/Wind Harmer
0.21
316486AD2-202 GEN
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316327AA2-057 GEN
Solar/Wind Harmer
0.088
3146233WITAKRS
Solar/Wind Harmer
0.29
3146233WITAKRS
Solar/Wind Harmer
0.039
3138543CONSLDL
Solar/Wind Harmer
0.038
971623AH1-311 GEN
Solar/Wind Harmer
0.115
3145543BTLEBRO
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.057
316210AC1-098 GEN
Solar/Wind Harmer
0.528
315779AE2-040
50/50
2.087
315244AE2-183_ST
50/50
2.174
970919AG2-571 GEN
Solar/Wind Harmer
2.554
970087AG2-069 GEN
Solar/Wind Harmer
5.718
315722AD1-056 GEN
Solar/Wind Harmer
0.416
3145783HORNRTN
Solar/Wind Harmer
0.064
957481AF2-042 GEN
Solar/Wind Harmer
16.959
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
26.124
316129AC1-054 GEN
Solar/Wind Harmer
0.223
315693AD1-088 GEN
Solar/Wind Harmer
2.832
971065AG2-659 GEN
Solar/Wind Harmer
2.514
962491AG1-098 GEN
Solar/Wind Harmer
3.316
3146233WITAKRS
Solar/Wind Harmer
0.23
316359AB2-059 GEN
Solar/Wind Harmer
0.207
316049AB1-081 GEN
Solar/Wind Harmer
0.33
3142053HEARTS
Solar/Wind Harmer
0.101
3145543BTLEBRO
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.046
316212AC1-099_GEN
Solar/Wind Harmer
0.294
315687AD1-152 GEN
Solar/Wind Harmer
0.002
316381AD1-082 GEN
Solar/Wind Helper
2.389
316458AB2-190 GEN2
Solar/Wind Helper
0.785
3142543TWELFTH
Solar/Wind Helper
0.012
963041AG1-153 GEN
50/50
1.998
3151281ROARAP4
50/50
0.079
3151281ROARAP4
50/50
0.073
3151541CLOVER2
50/50
1.285
3151611KERR 4
50/50
0.117
3151621KERR 5
50/50
0.117
3151631KERR 6
50/50
0.117
3151641KERR 7
50/50
0.117
316315AB2-025 C
Solar/Wind Harmer
0.121
315814AE2-033 C
Solar/Wind Harmer
11.633
316087AB2-174 GEN
Solar/Wind Harmer
0.002
941031AE2-094 GEN
Solar/Wind Harmer
14.523
944011AF1-069 GEN
Solar/Wind Harmer
4.745
315652AC1-086 GEN
Solar/Wind Harmer
8.522
970673AG2-436 GEN
Solar/Wind Harmer
16.437
970673AG2-436 GEN
Solar/Wind Harmer
10.958
971967AH1-528 GEN
Solar/Wind Harmer
12.009
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.03
970085AG2-068 GEN
Solar/Wind Harmer
3.812
970581AG2-369 GEN
Solar/Wind Harmer
3.278
3137643SOCKMAN
Solar/Wind Harmer
0.282
970831AG2-522 GEN
Solar/Wind Harmer
2.557
316319Z2-044 C
Solar/Wind Harmer
0
3143316POE
Solar/Wind Helper
4.623
316349AD2-085 GEN
Solar/Wind Helper
0.873
316132AB2-190 GEN1
Solar/Wind Helper
0.785
NYPJM->LTFIMP_NY
CLTF
0.411
LGEELTFEXP_LGEE->PJM
CLTF
0.433
LAGNLTFEXP_LAGN->PJM
CLTF
2.426
WECLTFEXP_WEC->PJM
CLTF
0.226
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.56
TVALTFEXP_TVA->PJM
CLTF
1.209
CPLELTFEXP_CPLE->PJM
CLTF
3.53
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.861
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.008
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.148
MECLTFEXP_MEC->PJM
CLTF
1.199
SIGELTFEXP_SIGE->PJM
CLTF
0.036

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 24972-3_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 24972-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.19 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:864.76
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
316023GEN1_S
Solar/Wind Harmer
0.971
960081AF2-299 GEN
Solar/Wind Harmer
1.365
971795AH1-408 GEN
Solar/Wind Harmer
8.215
3147043LAWRENC
Adder
0.838
316011AB1-132 GEN
Solar/Wind Harmer
2.163
962571AG1-106 GEN
Solar/Wind Harmer
1.486
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
0.878
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
7.239
940641AE2-051 GEN
Solar/Wind Harmer
7.187
316129AC1-054 GEN
Solar/Wind Harmer
0.633
315779AE2-040
50/50
2.75
316315AB2-025 C
Solar/Wind Harmer
0.597
315814AE2-033 C
Solar/Wind Harmer
20.237
946281AF1-292 GEN
Solar/Wind Harmer
0.272
316087AB2-174 GEN
Solar/Wind Harmer
1.551
315652AC1-086 GEN
Solar/Wind Harmer
11.632
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.037
941031AE2-094 GEN
Solar/Wind Harmer
15.852
944011AF1-069 GEN
Solar/Wind Harmer
4.967
970673AG2-436 GEN
Solar/Wind Harmer
17.384
970673AG2-436 GEN
Solar/Wind Harmer
8.802
971967AH1-528 GEN
Solar/Wind Harmer
15.183
970085AG2-068 GEN
Solar/Wind Harmer
4.826
970581AG2-369 GEN
Solar/Wind Harmer
4.15
970831AG2-522 GEN
Solar/Wind Harmer
3.663
316319Z2-044 C
Solar/Wind Harmer
0.393
315607AA1-063A GEN
Solar/Wind Harmer
0.674
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
316420AA1-050 GEN
Solar/Wind Harmer
0.737
316239AB2-077_GEN
Solar/Wind Harmer
0.194
316238AB2-078_GEN
Solar/Wind Harmer
0.194
3146043SEABORD
Solar/Wind Harmer
-0.006
3143316POE
Solar/Wind Helper
4.642
316132AB2-190 GEN1
Solar/Wind Helper
1.354
316349AD2-085 GEN
Solar/Wind Helper
1.038
316369SG1_INVT
Solar/Wind Helper
0.893
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.07
316365GEN2_N
Solar/Wind Harmer
0.971
966621AG1-532 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.006
313506AB2-031 GEN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
315724AD1-057 GEN
Solar/Wind Harmer
0.483
970917AG2-570 GEN
Solar/Wind Harmer
19.389
961601AG1-000A GEN
Solar/Wind Harmer
2.855
316327AA2-057 GEN
Solar/Wind Harmer
0.724
3146233WITAKRS
Solar/Wind Harmer
0.149
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.097
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
316131AB2-060 GEN
Solar/Wind Harmer
0.692
3146263WOODLND
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.896
971065AG2-659 GEN
Solar/Wind Harmer
3.563
3146233WITAKRS
Solar/Wind Harmer
-0.028
316359AB2-059 GEN
Solar/Wind Harmer
0.955
316049AB1-081 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316212AC1-099_GEN
Solar/Wind Harmer
0.609
957481AF2-042 GEN
Solar/Wind Harmer
21.676
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
315693AD1-088 GEN
Solar/Wind Harmer
3.23
316237AB2-079_GEN
Solar/Wind Harmer
0.194
3146263WOODLND
Solar/Wind Harmer
-0.006
962491AG1-098 GEN
Solar/Wind Harmer
4.256
316381AD1-082 GEN
Solar/Wind Helper
2.648
316458AB2-190 GEN2
Solar/Wind Helper
1.354
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.592
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
3144356SAPONY
Solar/Wind Harmer
0.772
316181AB2-040 GEN
Solar/Wind Harmer
1.44
3145796HORNRTN
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.933
3145593CAROLNA
Solar/Wind Harmer
0.069
972185AH1-677 GEN
Adder
4.088
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
972187AH1-678 GEN
Adder
2.044
316426AA2-053 GEN
Solar/Wind Harmer
0.791
970933AG2-581 GEN
Solar/Wind Harmer
7.263
316274AC1-208 GEN
Solar/Wind Harmer
0.794
961601AG1-000A GEN
Solar/Wind Harmer
2.819
316263AC1-034 GEN
Solar/Wind Harmer
3.322
970099AG2-077 GEN
Solar/Wind Harmer
8.67
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
939181AE1-148 GEN
Solar/Wind Harmer
3.722
313527AB2-043 GEN
Solar/Wind Harmer
1.051
316240AF1-291 C
Solar/Wind Helper
0.668
316033AB2-134 GEN
Solar/Wind Helper
0.639
315697AD1-025 GEN
Solar/Wind Helper
2.123
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.198
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.615
NYPJM->LTFIMP_NY
CLTF
0.342
LAGNLTFEXP_LAGN->PJM
CLTF
2.457
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.602
TVALTFEXP_TVA->PJM
CLTF
1.222
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.204
MECLTFEXP_MEC->PJM
CLTF
1.237
SIGELTFEXP_SIGE->PJM
CLTF
0.037

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 249-69_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 249-69_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.16 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:864.56
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
3144356SAPONY
Solar/Wind Harmer
0.772
316181AB2-040 GEN
Solar/Wind Harmer
1.44
3145796HORNRTN
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.933
3145593CAROLNA
Solar/Wind Harmer
0.069
972185AH1-677 GEN
Adder
4.088
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
972187AH1-678 GEN
Adder
2.044
316426AA2-053 GEN
Solar/Wind Harmer
0.791
970933AG2-581 GEN
Solar/Wind Harmer
7.263
316274AC1-208 GEN
Solar/Wind Harmer
0.794
961601AG1-000A GEN
Solar/Wind Harmer
2.819
316263AC1-034 GEN
Solar/Wind Harmer
3.322
970099AG2-077 GEN
Solar/Wind Harmer
8.67
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
939181AE1-148 GEN
Solar/Wind Harmer
3.722
316365GEN2_N
Solar/Wind Harmer
0.971
966621AG1-532 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.006
313506AB2-031 GEN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
315724AD1-057 GEN
Solar/Wind Harmer
0.483
970917AG2-570 GEN
Solar/Wind Harmer
19.389
961601AG1-000A GEN
Solar/Wind Harmer
2.855
316327AA2-057 GEN
Solar/Wind Harmer
0.724
3146233WITAKRS
Solar/Wind Harmer
0.149
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.097
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
316131AB2-060 GEN
Solar/Wind Harmer
0.692
3146263WOODLND
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.896
316023GEN1_S
Solar/Wind Harmer
0.971
960081AF2-299 GEN
Solar/Wind Harmer
1.365
971795AH1-408 GEN
Solar/Wind Harmer
8.215
3147043LAWRENC
Adder
0.838
316011AB1-132 GEN
Solar/Wind Harmer
2.163
962571AG1-106 GEN
Solar/Wind Harmer
1.486
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
0.878
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
7.239
940641AE2-051 GEN
Solar/Wind Harmer
7.187
316129AC1-054 GEN
Solar/Wind Harmer
0.633
971065AG2-659 GEN
Solar/Wind Harmer
3.563
3146233WITAKRS
Solar/Wind Harmer
-0.028
316359AB2-059 GEN
Solar/Wind Harmer
0.955
316049AB1-081 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316212AC1-099_GEN
Solar/Wind Harmer
0.609
957481AF2-042 GEN
Solar/Wind Harmer
21.676
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
315693AD1-088 GEN
Solar/Wind Harmer
3.23
316237AB2-079_GEN
Solar/Wind Harmer
0.194
3146263WOODLND
Solar/Wind Harmer
-0.006
962491AG1-098 GEN
Solar/Wind Harmer
4.256
316381AD1-082 GEN
Solar/Wind Helper
2.648
316458AB2-190 GEN2
Solar/Wind Helper
1.354
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.592
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
315779AE2-040
50/50
2.75
316315AB2-025 C
Solar/Wind Harmer
0.597
315814AE2-033 C
Solar/Wind Harmer
20.237
946281AF1-292 GEN
Solar/Wind Harmer
0.272
316087AB2-174 GEN
Solar/Wind Harmer
1.551
315652AC1-086 GEN
Solar/Wind Harmer
11.632
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.037
941031AE2-094 GEN
Solar/Wind Harmer
15.852
944011AF1-069 GEN
Solar/Wind Harmer
4.967
970673AG2-436 GEN
Solar/Wind Harmer
17.384
970673AG2-436 GEN
Solar/Wind Harmer
8.802
971967AH1-528 GEN
Solar/Wind Harmer
15.183
970085AG2-068 GEN
Solar/Wind Harmer
4.826
970581AG2-369 GEN
Solar/Wind Harmer
4.15
970831AG2-522 GEN
Solar/Wind Harmer
3.663
316319Z2-044 C
Solar/Wind Harmer
0.393
315607AA1-063A GEN
Solar/Wind Harmer
0.674
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
316420AA1-050 GEN
Solar/Wind Harmer
0.737
316239AB2-077_GEN
Solar/Wind Harmer
0.194
316238AB2-078_GEN
Solar/Wind Harmer
0.194
3146043SEABORD
Solar/Wind Harmer
-0.006
3143316POE
Solar/Wind Helper
4.642
316132AB2-190 GEN1
Solar/Wind Helper
1.354
316349AD2-085 GEN
Solar/Wind Helper
1.038
316369SG1_INVT
Solar/Wind Helper
0.893
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.07
313527AB2-043 GEN
Solar/Wind Harmer
1.051
316240AF1-291 C
Solar/Wind Helper
0.668
316033AB2-134 GEN
Solar/Wind Helper
0.639
315697AD1-025 GEN
Solar/Wind Helper
2.123
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.198
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.615
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.447
LAGNLTFEXP_LAGN->PJM
CLTF
2.457
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.602
WECLTFEXP_WEC->PJM
CLTF
0.235
TVALTFEXP_TVA->PJM
CLTF
1.222
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.204
MECLTFEXP_MEC->PJM
CLTF
1.237
SIGELTFEXP_SIGE->PJM
CLTF
0.037

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-5: LOCKS H322_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: LOCKS H322_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.14 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:864.38
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
316023GEN1_S
Solar/Wind Harmer
0.971
960081AF2-299 GEN
Solar/Wind Harmer
1.365
971795AH1-408 GEN
Solar/Wind Harmer
8.215
3147043LAWRENC
Adder
0.838
316011AB1-132 GEN
Solar/Wind Harmer
2.163
962571AG1-106 GEN
Solar/Wind Harmer
1.486
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
0.878
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
7.239
940641AE2-051 GEN
Solar/Wind Harmer
7.187
316129AC1-054 GEN
Solar/Wind Harmer
0.633
971065AG2-659 GEN
Solar/Wind Harmer
3.563
3146233WITAKRS
Solar/Wind Harmer
-0.028
316359AB2-059 GEN
Solar/Wind Harmer
0.955
316049AB1-081 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316212AC1-099_GEN
Solar/Wind Harmer
0.609
957481AF2-042 GEN
Solar/Wind Harmer
21.676
3144356SAPONY
Solar/Wind Harmer
0.772
316181AB2-040 GEN
Solar/Wind Harmer
1.44
3145796HORNRTN
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.933
3145593CAROLNA
Solar/Wind Harmer
0.069
972185AH1-677 GEN
Adder
4.088
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
972187AH1-678 GEN
Adder
2.044
316426AA2-053 GEN
Solar/Wind Harmer
0.791
970933AG2-581 GEN
Solar/Wind Harmer
7.263
316274AC1-208 GEN
Solar/Wind Harmer
0.794
961601AG1-000A GEN
Solar/Wind Harmer
2.819
316263AC1-034 GEN
Solar/Wind Harmer
3.322
970099AG2-077 GEN
Solar/Wind Harmer
8.67
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
939181AE1-148 GEN
Solar/Wind Harmer
3.722
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
315693AD1-088 GEN
Solar/Wind Harmer
3.23
316237AB2-079_GEN
Solar/Wind Harmer
0.194
3146263WOODLND
Solar/Wind Harmer
-0.006
962491AG1-098 GEN
Solar/Wind Harmer
4.256
316381AD1-082 GEN
Solar/Wind Helper
2.648
316458AB2-190 GEN2
Solar/Wind Helper
1.354
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.592
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
315779AE2-040
50/50
2.75
316315AB2-025 C
Solar/Wind Harmer
0.597
315814AE2-033 C
Solar/Wind Harmer
20.237
946281AF1-292 GEN
Solar/Wind Harmer
0.272
316087AB2-174 GEN
Solar/Wind Harmer
1.551
315652AC1-086 GEN
Solar/Wind Harmer
11.632
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.037
941031AE2-094 GEN
Solar/Wind Harmer
15.852
944011AF1-069 GEN
Solar/Wind Harmer
4.967
970673AG2-436 GEN
Solar/Wind Harmer
17.384
970673AG2-436 GEN
Solar/Wind Harmer
8.802
971967AH1-528 GEN
Solar/Wind Harmer
15.183
970085AG2-068 GEN
Solar/Wind Harmer
4.826
970581AG2-369 GEN
Solar/Wind Harmer
4.15
970831AG2-522 GEN
Solar/Wind Harmer
3.663
316319Z2-044 C
Solar/Wind Harmer
0.393
315607AA1-063A GEN
Solar/Wind Harmer
0.674
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
316420AA1-050 GEN
Solar/Wind Harmer
0.737
316239AB2-077_GEN
Solar/Wind Harmer
0.194
316238AB2-078_GEN
Solar/Wind Harmer
0.194
3146043SEABORD
Solar/Wind Harmer
-0.006
3143316POE
Solar/Wind Helper
4.642
316132AB2-190 GEN1
Solar/Wind Helper
1.354
316349AD2-085 GEN
Solar/Wind Helper
1.038
316369SG1_INVT
Solar/Wind Helper
0.893
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.07
316365GEN2_N
Solar/Wind Harmer
0.971
966621AG1-532 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.006
313506AB2-031 GEN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
315724AD1-057 GEN
Solar/Wind Harmer
0.483
970917AG2-570 GEN
Solar/Wind Harmer
19.389
961601AG1-000A GEN
Solar/Wind Harmer
2.855
316327AA2-057 GEN
Solar/Wind Harmer
0.724
3146233WITAKRS
Solar/Wind Harmer
0.149
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.097
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
316131AB2-060 GEN
Solar/Wind Harmer
0.692
3146263WOODLND
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.548
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.896
313527AB2-043 GEN
Solar/Wind Harmer
1.051
316240AF1-291 C
Solar/Wind Helper
0.668
316033AB2-134 GEN
Solar/Wind Helper
0.639
315697AD1-025 GEN
Solar/Wind Helper
2.123
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.198
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.615
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.447
LAGNLTFEXP_LAGN->PJM
CLTF
2.457
WECLTFEXP_WEC->PJM
CLTF
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.602
TVALTFEXP_TVA->PJM
CLTF
1.222
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.398
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.204
MECLTFEXP_MEC->PJM
CLTF
1.237
SIGELTFEXP_SIGE->PJM
CLTF
0.037

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-6: T152_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-6: T152_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.78 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:853.09
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
316023GEN1_S
Solar/Wind Harmer
0.97
960081AF2-299 GEN
Solar/Wind Harmer
1.365
971795AH1-408 GEN
Solar/Wind Harmer
8.213
3147043LAWRENC
Adder
0.838
316011AB1-132 GEN
Solar/Wind Harmer
2.163
962571AG1-106 GEN
Solar/Wind Harmer
1.486
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
0.878
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970919AG2-571 GEN
Solar/Wind Harmer
2.454
970087AG2-069 GEN
Solar/Wind Harmer
7.237
940641AE2-051 GEN
Solar/Wind Harmer
7.186
316129AC1-054 GEN
Solar/Wind Harmer
0.633
971065AG2-659 GEN
Solar/Wind Harmer
3.563
3146233WITAKRS
Solar/Wind Harmer
-0.028
316359AB2-059 GEN
Solar/Wind Harmer
0.955
316049AB1-081 GEN
Solar/Wind Harmer
0.764
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316212AC1-099_GEN
Solar/Wind Harmer
0.609
957481AF2-042 GEN
Solar/Wind Harmer
21.671
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
315693AD1-088 GEN
Solar/Wind Harmer
3.229
316237AB2-079_GEN
Solar/Wind Harmer
0.194
3146263WOODLND
Solar/Wind Harmer
-0.006
962491AG1-098 GEN
Solar/Wind Harmer
4.255
316381AD1-082 GEN
Solar/Wind Helper
2.641
316458AB2-190 GEN2
Solar/Wind Helper
1.356
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.583
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
315779AE2-040
50/50
2.749
316315AB2-025 C
Solar/Wind Harmer
0.597
315814AE2-033 C
Solar/Wind Harmer
20.231
946281AF1-292 GEN
Solar/Wind Harmer
0.272
316087AB2-174 GEN
Solar/Wind Harmer
1.55
315652AC1-086 GEN
Solar/Wind Harmer
11.63
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.037
941031AE2-094 GEN
Solar/Wind Harmer
15.849
944011AF1-069 GEN
Solar/Wind Harmer
4.966
970673AG2-436 GEN
Solar/Wind Harmer
17.38
970673AG2-436 GEN
Solar/Wind Harmer
8.8
971967AH1-528 GEN
Solar/Wind Harmer
15.18
970085AG2-068 GEN
Solar/Wind Harmer
4.825
970581AG2-369 GEN
Solar/Wind Harmer
4.149
970831AG2-522 GEN
Solar/Wind Harmer
3.662
316319Z2-044 C
Solar/Wind Harmer
0.393
315607AA1-063A GEN
Solar/Wind Harmer
0.674
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
316420AA1-050 GEN
Solar/Wind Harmer
0.737
316239AB2-077_GEN
Solar/Wind Harmer
0.194
316238AB2-078_GEN
Solar/Wind Harmer
0.194
3146043SEABORD
Solar/Wind Harmer
-0.006
3143316POE
Solar/Wind Helper
4.644
316132AB2-190 GEN1
Solar/Wind Helper
1.356
316349AD2-085 GEN
Solar/Wind Helper
1.035
316369SG1_INVT
Solar/Wind Helper
0.895
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.069
316365GEN2_N
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.006
313506AB2-031 GEN
Solar/Wind Harmer
0.83
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
315724AD1-057 GEN
Solar/Wind Harmer
0.483
970917AG2-570 GEN
Solar/Wind Harmer
19.385
316327AA2-057 GEN
Solar/Wind Harmer
0.724
961601AG1-000A GEN
Solar/Wind Harmer
2.855
3146233WITAKRS
Solar/Wind Harmer
0.149
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.096
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
316131AB2-060 GEN
Solar/Wind Harmer
0.692
3146263WOODLND
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.557
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.894
3144356SAPONY
Solar/Wind Harmer
0.772
316181AB2-040 GEN
Solar/Wind Harmer
1.44
3145796HORNRTN
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.933
3145593CAROLNA
Solar/Wind Harmer
0.069
972185AH1-677 GEN
Adder
4.087
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
972187AH1-678 GEN
Adder
2.044
316426AA2-053 GEN
Solar/Wind Harmer
0.791
970933AG2-581 GEN
Solar/Wind Harmer
7.262
316274AC1-208 GEN
Solar/Wind Harmer
0.794
961601AG1-000A GEN
Solar/Wind Harmer
2.819
316263AC1-034 GEN
Solar/Wind Harmer
3.321
970099AG2-077 GEN
Solar/Wind Harmer
8.668
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
939181AE1-148 GEN
Solar/Wind Harmer
3.721
313527AB2-043 GEN
Solar/Wind Harmer
1.051
316240AF1-291 C
Solar/Wind Helper
0.672
316033AB2-134 GEN
Solar/Wind Helper
0.64
315697AD1-025 GEN
Solar/Wind Helper
2.126
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.197
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.614
NYPJM->LTFIMP_NY
CLTF
0.342
LAGNLTFEXP_LAGN->PJM
CLTF
2.456
LGEELTFEXP_LGEE->PJM
CLTF
0.447
WECLTFEXP_WEC->PJM
CLTF
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.601
TVALTFEXP_TVA->PJM
CLTF
1.222
CPLELTFEXP_CPLE->PJM
CLTF
3.563
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.395
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.203
MECLTFEXP_MEC->PJM
CLTF
1.236
SIGELTFEXP_SIGE->PJM
CLTF
0.037

Details for 6CARSON-6POE 230.0 kV Ckt 1 line l/o DVP_P4-2: 205T249_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CARSON-6POE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 205T249_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.01 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:846.72
MW Contribution:4.15
Bus #Bus NameTypeMW Contribution
316023GEN1_S
Solar/Wind Harmer
0.97
960081AF2-299 GEN
Solar/Wind Harmer
1.364
971795AH1-408 GEN
Solar/Wind Harmer
8.212
3147043LAWRENC
Adder
0.838
316011AB1-132 GEN
Solar/Wind Harmer
2.163
962571AG1-106 GEN
Solar/Wind Harmer
1.486
3145796HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
0.878
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.096
970919AG2-571 GEN
Solar/Wind Harmer
2.453
970087AG2-069 GEN
Solar/Wind Harmer
7.236
940641AE2-051 GEN
Solar/Wind Harmer
7.184
316129AC1-054 GEN
Solar/Wind Harmer
0.633
971065AG2-659 GEN
Solar/Wind Harmer
3.562
3146233WITAKRS
Solar/Wind Harmer
-0.028
316359AB2-059 GEN
Solar/Wind Harmer
0.955
316049AB1-081 GEN
Solar/Wind Harmer
0.764
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316212AC1-099_GEN
Solar/Wind Harmer
0.609
957481AF2-042 GEN
Solar/Wind Harmer
21.666
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
315693AD1-088 GEN
Solar/Wind Harmer
3.229
316237AB2-079_GEN
Solar/Wind Harmer
0.194
3146263WOODLND
Solar/Wind Harmer
-0.006
962491AG1-098 GEN
Solar/Wind Harmer
4.254
316381AD1-082 GEN
Solar/Wind Helper
2.641
316458AB2-190 GEN2
Solar/Wind Helper
1.356
3142543TWELFTH
Solar/Wind Helper
0.022
3142433PROV 92
Solar/Wind Helper
0.583
3142416OLDCHRC
Solar/Wind Helper
0.348
3142416OLDCHRC
Solar/Wind Helper
0.133
315779AE2-040
50/50
2.749
316315AB2-025 C
Solar/Wind Harmer
0.597
315814AE2-033 C
Solar/Wind Harmer
20.23
946281AF1-292 GEN
Solar/Wind Harmer
0.272
316087AB2-174 GEN
Solar/Wind Harmer
1.55
315652AC1-086 GEN
Solar/Wind Harmer
11.628
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.037
941031AE2-094 GEN
Solar/Wind Harmer
15.846
944011AF1-069 GEN
Solar/Wind Harmer
4.965
970673AG2-436 GEN
Solar/Wind Harmer
17.377
970673AG2-436 GEN
Solar/Wind Harmer
8.798
971967AH1-528 GEN
Solar/Wind Harmer
15.176
970085AG2-068 GEN
Solar/Wind Harmer
4.824
970581AG2-369 GEN
Solar/Wind Harmer
4.148
970831AG2-522 GEN
Solar/Wind Harmer
3.661
316319Z2-044 C
Solar/Wind Harmer
0.393
315607AA1-063A GEN
Solar/Wind Harmer
0.674
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.026
316420AA1-050 GEN
Solar/Wind Harmer
0.737
316239AB2-077_GEN
Solar/Wind Harmer
0.194
316238AB2-078_GEN
Solar/Wind Harmer
0.194
3146043SEABORD
Solar/Wind Harmer
-0.006
3143316POE
Solar/Wind Helper
4.644
316132AB2-190 GEN1
Solar/Wind Helper
1.356
316349AD2-085 GEN
Solar/Wind Helper
1.035
316369SG1_INVT
Solar/Wind Helper
0.895
316312AB1-027
Solar/Wind Helper
0.255
3143873LANEXA
Solar/Wind Helper
0.069
316365GEN2_N
Solar/Wind Harmer
0.97
966621AG1-532 GEN
Solar/Wind Harmer
0.246
3147043LAWRENC
Solar/Wind Harmer
-0.006
313506AB2-031 GEN
Solar/Wind Harmer
0.829
3145796HORNRTN
Solar/Wind Harmer
-0.039
3145796HORNRTN
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
315724AD1-057 GEN
Solar/Wind Harmer
0.483
970917AG2-570 GEN
Solar/Wind Harmer
19.381
316327AA2-057 GEN
Solar/Wind Harmer
0.724
961601AG1-000A GEN
Solar/Wind Harmer
2.854
3146233WITAKRS
Solar/Wind Harmer
0.149
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.096
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.573
316486AD2-202 GEN
Solar/Wind Harmer
0.168
316131AB2-060 GEN
Solar/Wind Harmer
0.691
3146263WOODLND
Solar/Wind Harmer
-0.006
3142946ENON
Solar/Wind Helper
0.059
316473AC1-191 GEN
Solar/Wind Helper
0.894
3144356SAPONY
Solar/Wind Harmer
0.772
316181AB2-040 GEN
Solar/Wind Harmer
1.439
3145796HORNRTN
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
972185AH1-677 GEN
Adder
4.086
3145783HORNRTN
Solar/Wind Harmer
0.966
3145783HORNRTN
Solar/Wind Harmer
0.773
3145783HORNRTN
Solar/Wind Harmer
0.242
3145783HORNRTN
Solar/Wind Harmer
0.097
972187AH1-678 GEN
Adder
2.043
316426AA2-053 GEN
Solar/Wind Harmer
0.791
970933AG2-581 GEN
Solar/Wind Harmer
7.26
316274AC1-208 GEN
Solar/Wind Harmer
0.794
961601AG1-000A GEN
Solar/Wind Harmer
2.818
316263AC1-034 GEN
Solar/Wind Harmer
3.32
970099AG2-077 GEN
Solar/Wind Harmer
8.666
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
939181AE1-148 GEN
Solar/Wind Harmer
3.721
313527AB2-043 GEN
Solar/Wind Harmer
1.051
316240AF1-291 C
Solar/Wind Helper
0.672
316033AB2-134 GEN
Solar/Wind Helper
0.64
315697AD1-025 GEN
Solar/Wind Helper
2.126
3142946ENON
Solar/Wind Helper
0.018
966871AG1-558 GEN
Solar/Wind Helper
0.197
316075AC2-137 C
Solar/Wind Helper
0.206
316468AD1-105 GEN
Solar/Wind Helper
0.614
NYPJM->LTFIMP_NY
CLTF
0.342
LGEELTFEXP_LGEE->PJM
CLTF
0.446
LAGNLTFEXP_LAGN->PJM
CLTF
2.454
WECLTFEXP_WEC->PJM
CLTF
0.235
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.597
TVALTFEXP_TVA->PJM
CLTF
1.221
CPLELTFEXP_CPLE->PJM
CLTF
3.562
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.088
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.198
MECLTFEXP_MEC->PJM
CLTF
1.234
SIGELTFEXP_SIGE->PJM
CLTF
0.037

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1841.8
MW Contribution:8.61
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.378
315244AE2-183_ST
50/50
4.349
963041AG1-153 GEN
50/50
3.994
3151541CLOVER2
50/50
2.544
3151281ROARAP4
50/50
0.144
3151281ROARAP4
50/50
0.134
316315AB2-025 C
Solar/Wind Harmer
0.734
315814AE2-033 C
Solar/Wind Harmer
24.939
941031AE2-094 GEN
Solar/Wind Harmer
33.281
944011AF1-069 GEN
Solar/Wind Harmer
10.428
970673AG2-436 GEN
Solar/Wind Harmer
36.399
970673AG2-436 GEN
Solar/Wind Harmer
18.43
946281AF1-292 GEN
Solar/Wind Harmer
0.383
971967AH1-528 GEN
Solar/Wind Harmer
31.705
970085AG2-068 GEN
Solar/Wind Harmer
10.008
970581AG2-369 GEN
Solar/Wind Harmer
8.607
316087AB2-174 GEN
Solar/Wind Harmer
2.265
315652AC1-086 GEN
Solar/Wind Harmer
17.05
3145796HORNRTN
Solar/Wind Harmer
-0.047
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.057
970831AG2-522 GEN
Solar/Wind Harmer
6.31
315607AA1-063A GEN
Solar/Wind Harmer
1.207
316319Z2-044 C
Solar/Wind Harmer
0.657
3146043SEABORD
Solar/Wind Harmer
-0.012
316239AB2-077_GEN
Solar/Wind Harmer
0.35
316238AB2-078_GEN
Solar/Wind Harmer
0.35
3146033SCOT NK
Solar/Wind Harmer
-0.045
3145573BETHELC
Solar/Wind Harmer
-0.011
3145573BETHELC
Solar/Wind Harmer
-0.011
316420AA1-050 GEN
Solar/Wind Harmer
1.267
316118AC1-105 GEN
Solar/Wind Harmer
0.759
3147173SINAI
Solar/Wind Harmer
-0.011
3147243WELCO
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
4.731
971443AH1-215 GEN
Solar/Wind Harmer
2.043
3145683EARLEYS
Solar/Wind Harmer
-0.021
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
3144303KENBRDG
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.089
315243AE2-183_GT3
50/50
2.516
3151051BRUNSWICKS1
50/50
4.094
3151021BRUNSWICKG1
50/50
1.972
971451AH1-221 GEN
50/50
5.991
3147043LAWRENC
50/50
1.32
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
3151531CLOVER1
50/50
2.556
3151261ROARAP2
50/50
0.148
316023GEN1_S
Solar/Wind Harmer
1.302
960081AF2-299 GEN
Solar/Wind Harmer
1.926
970919AG2-571 GEN
Solar/Wind Harmer
5.093
970087AG2-069 GEN
Solar/Wind Harmer
15.012
971795AH1-408 GEN
Solar/Wind Harmer
11.982
316011AB1-132 GEN
Solar/Wind Harmer
3.171
962571AG1-106 GEN
Solar/Wind Harmer
2.179
3151031BRUNSWICKG2
50/50
1.972
3151391GASTONA
50/50
0.365
3151411GASTONB
50/50
0.365
970413AG2-270 GEN
50/50
11.155
3151261ROARAP2
50/50
0.144
316365GEN2_N
Solar/Wind Harmer
1.302
966621AG1-532 GEN
Solar/Wind Harmer
0.347
970917AG2-570 GEN
Solar/Wind Harmer
40.235
3147043LAWRENC
Solar/Wind Harmer
-0.009
313506AB2-031 GEN
Solar/Wind Harmer
1.233
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
1.161
316486AD2-202 GEN
Solar/Wind Harmer
0.34
315724AD1-057 GEN
Solar/Wind Harmer
0.758
316327AA2-057 GEN
Solar/Wind Harmer
1.21
961601AG1-000A GEN
Solar/Wind Harmer
4.742
3146233WITAKRS
Solar/Wind Harmer
0.249
3146233WITAKRS
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316210AC1-098 GEN
Solar/Wind Harmer
1.85
316131AB2-060 GEN
Solar/Wind Harmer
1.244
3146073TAR RVR
Solar/Wind Harmer
-0.011
3146083TARBORO
Solar/Wind Harmer
-0.011
964241AG1-285 GEN
Solar/Wind Harmer
8.72
3146263WOODLND
Solar/Wind Harmer
-0.011
316248AF1-058 C
Solar/Wind Harmer
0.328
960061AF2-297 GEN
Solar/Wind Harmer
5.444
316317KELFORD C
Solar/Wind Harmer
0.511
3145823KELFORD
Solar/Wind Harmer
-0.011
315785AD2-033 C
Solar/Wind Harmer
2.392
970257AG2-171 GEN
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.281
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
959311AF2-222 GEN
Solar/Wind Harmer
10.609
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.902
961681AG1-008 GEN
Solar/Wind Harmer
7.902
316283AC2-100 C
Solar/Wind Harmer
0.942
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.01
966801AG1-551 GEN
Solar/Wind Harmer
1.233
3156021HOLLOMANSOL
Solar/Wind Harmer
1.319
971683AH1-343 GEN
Solar/Wind Harmer
4.208
3156081AA2-088 GEN
Solar/Wind Harmer
3.105
970909AG2-566 GEN
Solar/Wind Harmer
0.889
963181AG1-167 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.028
971193AH1-056 GEN
Solar/Wind Harmer
5.522
3146206CASHIE
Solar/Wind Harmer
-0.009
315737AD1-076 GEN
Solar/Wind Harmer
1.551
971157AH1-035 GEN
Solar/Wind Harmer
1.003
942461AE2-259 GEN
Solar/Wind Harmer
1.167
315614AA2-178 GEN
Solar/Wind Harmer
0.791
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146376EDENTON
Solar/Wind Harmer
-0.006
315839AE2-212 C
Solar/Wind Helper
0.966
3142946ENON
Solar/Wind Helper
0.055
316473AC1-191 GEN
Solar/Wind Helper
1
970533AG2-339 GEN
50/50
14.043
970531AG2-338 GEN
50/50
5.617
315242AE2-183_GT2
50/50
2.516
315241AE2-183_GT1
50/50
2.5
972185AH1-677 GEN
50/50
9.069
3151041BRUNSWICKG3
50/50
1.972
972187AH1-678 GEN
50/50
4.526
3151361ROSEMG1
50/50
0.471
3151371ROSEMS1
50/50
0.292
3151381ROSEMG2
50/50
0.22
3144356SAPONY
Solar/Wind Harmer
0.948
970933AG2-581 GEN
Solar/Wind Harmer
15.092
316181AB2-040 GEN
Solar/Wind Harmer
2.139
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
970099AG2-077 GEN
Solar/Wind Harmer
17.742
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.5
3145593CAROLNA
Solar/Wind Harmer
0.111
3145783HORNRTN
Solar/Wind Harmer
1.561
3145783HORNRTN
Solar/Wind Harmer
1.249
3145783HORNRTN
Solar/Wind Harmer
0.39
3145783HORNRTN
Solar/Wind Harmer
0.156
316426AA2-053 GEN
Solar/Wind Harmer
1.293
316274AC1-208 GEN
Solar/Wind Harmer
1.319
939181AE1-148 GEN
Solar/Wind Harmer
6.767
961601AG1-000A GEN
Solar/Wind Harmer
4.682
316263AC1-034 GEN
Solar/Wind Harmer
5.552
313527AB2-043 GEN
Solar/Wind Harmer
1.888
3145493TOT1
Solar/Wind Harmer
0.175
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
962561AG1-105 GEN
Solar/Wind Harmer
6.333
964791AG1-342 GEN
Solar/Wind Harmer
2.391
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970323AG2-213 GEN
Solar/Wind Harmer
5.164
971775AH1-396 GEN
Solar/Wind Harmer
0.735
316034AC1-036 C
Solar/Wind Harmer
0.191
971741AH1-377 GEN
Solar/Wind Harmer
11.893
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
316222AC1-221 GEN
Solar/Wind Harmer
1.018
3145893MURPHYS
Solar/Wind Harmer
0.278
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.02
3145933PARMELE
Solar/Wind Harmer
-0.01
970301AG2-198 GEN
Solar/Wind Harmer
4.681
958211AF2-115 GEN
Solar/Wind Harmer
1.439
963191AG1-168 GEN
Solar/Wind Harmer
0.864
3144293JTRSVLE
Adder
0.261
3144293JTRSVLE
Adder
0.22
3147133PAMPLIN
Solar/Wind Harmer
-0.009
3147133PAMPLIN
Solar/Wind Harmer
-0.007
316065AD1-022 GEN
Solar/Wind Harmer
4.293
942751AE2-291 GEN
Solar/Wind Harmer
4.718
315742AE1-103 GEN
Solar/Wind Harmer
0.706
3146376EDENTON
Solar/Wind Harmer
0.191
3146376EDENTON
Solar/Wind Harmer
0.191
316240AF1-291 C
Solar/Wind Helper
0.402
3142946ENON
Solar/Wind Helper
0.017
966871AG1-558 GEN
Solar/Wind Helper
0.221
3143526WINTERP
Solar/Wind Helper
0.769
316468AD1-105 GEN
Solar/Wind Helper
0.714
316075AC2-137 C
Solar/Wind Helper
0.21
316033AB2-134 GEN
Solar/Wind Helper
0.43
315697AD1-025 GEN
Solar/Wind Helper
1.43
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316005AA1-067
Solar/Wind Harmer
0.207
3145746EVERETS
Solar/Wind Harmer
-0.041
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.344
316318V4-068
Solar/Wind Harmer
0.249
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
0.871
970683AG2-441 GEN
Solar/Wind Harmer
7.621
970681AG2-440 GEN
Solar/Wind Harmer
6.097
3143316POE
Solar/Wind Harmer
-0.038
970865AG2-541 GEN
Solar/Wind Harmer
3.743
946301AF1-294 GEN
Solar/Wind Harmer
2.361
961791AG1-021 GEN
Solar/Wind Harmer
1.152
315657AE1-056 GEN
Solar/Wind Harmer
3.313
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.864
270455AD2-022 GEN
Solar/Wind Harmer
1.529
270457AD2-023 GEN
Solar/Wind Harmer
0.775
315732AD1-074 GEN1
Solar/Wind Harmer
1.65
315733AD1-074 GEN2
Solar/Wind Harmer
1.65
315735AD1-075 GEN1
Solar/Wind Harmer
0.825
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.77
970163AG2-111 GEN
Solar/Wind Harmer
0.734
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.593
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
316132AB2-190 GEN1
Solar/Wind Helper
0.976
316233AE1-074 FULL
Solar/Wind Helper
0.226
316312AB1-027
Solar/Wind Helper
0.27
3143873LANEXA
Solar/Wind Helper
0.076
316369SG1_INVT
Solar/Wind Helper
0.602
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
44.356
315722AD1-056 GEN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
-0.013
315693AD1-088 GEN
Solar/Wind Harmer
6.574
939411AE1-173 GEN
Solar/Wind Harmer
65.115
962491AG1-098 GEN
Solar/Wind Harmer
8.662
316190AA2-174 GEN
Solar/Wind Harmer
0.157
316129AC1-054 GEN
Solar/Wind Harmer
1.1
315687AD1-152 GEN
Solar/Wind Harmer
1.509
971065AG2-659 GEN
Solar/Wind Harmer
6.236
3146233WITAKRS
Solar/Wind Harmer
-0.047
316359AB2-059 GEN
Solar/Wind Harmer
1.597
316049AB1-081 GEN
Solar/Wind Harmer
1.278
3142053HEARTS
Solar/Wind Harmer
0.139
3145543BTLEBRO
Solar/Wind Harmer
-0.012
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.028
316237AB2-079_GEN
Solar/Wind Harmer
0.35
961671AG1-007 GEN
Solar/Wind Harmer
0.143
3146083TARBORO
Solar/Wind Harmer
-0.011
3145493TOT1
Solar/Wind Harmer
0.335
970401AG2-262 GEN
Solar/Wind Harmer
0.731
3146263WOODLND
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.011
316494AC1-189 GEN
Solar/Wind Harmer
1.164
3145683EARLEYS
Solar/Wind Harmer
-0.01
316003AC1-222 GEN
Solar/Wind Harmer
1.004
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.296
3146293MARTNCO
Solar/Wind Harmer
0.061
970685AG2-442 GEN
Solar/Wind Harmer
8.535
316174AB2-169 GEN
Solar/Wind Harmer
1.424
963171AG1-166 GEN
Solar/Wind Harmer
1.152
971563AH1-280 GEN
Solar/Wind Harmer
1.152
3144293JTRSVLE
Adder
0.261
3145963POPLR C
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.873
3146926FARMVIL
Solar/Wind Harmer
-0.004
3130156CHOWAN
Solar/Wind Harmer
-0.006
3142543TWELFTH
Solar/Wind Helper
0.024
3142433PROV 92
Solar/Wind Helper
0.7
316458AB2-190 GEN2
Solar/Wind Helper
0.976
3143526WINTERP
Solar/Wind Helper
0.769
3142416OLDCHRC
Solar/Wind Helper
0.369
3142416OLDCHRC
Solar/Wind Helper
0.141
3143226MDLTHAN
Solar/Wind Helper
0.133
NYPJM->LTFIMP_NY
CLTF
0.817
LAGNLTFEXP_LAGN->PJM
CLTF
4.648
LGEELTFEXP_LGEE->PJM
CLTF
0.818
WECLTFEXP_WEC->PJM
CLTF
0.427
CBM South 2LTFEXP_CBM-S2->PJM
CBM
14.569
TVALTFEXP_TVA->PJM
CLTF
2.315
CPLELTFEXP_CPLE->PJM
CLTF
6.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.934
MECLTFEXP_MEC->PJM
CLTF
2.276
SIGELTFEXP_SIGE->PJM
CLTF
0.068

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.99 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1407.24
MW Contribution:5.11
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3151031BRUNSWICKG2
50/50
1.536
3151261ROARAP2
50/50
0.133
970413AG2-270 GEN
50/50
8.806
3151591KERR 2
50/50
0.187
316365GEN2_N
Solar/Wind Harmer
0.354
313506AB2-031 GEN
Solar/Wind Harmer
0.385
970533AG2-339 GEN
50/50
10.894
970531AG2-338 GEN
50/50
4.358
3151361ROSEMG1
50/50
0.433
3151371ROSEMS1
50/50
0.268
3151381ROSEMG2
50/50
0.203
315242AE2-183_GT2
50/50
1.956
315241AE2-183_GT1
50/50
1.944
972185AH1-677 GEN
50/50
7.053
3151041BRUNSWICKG3
50/50
1.536
972187AH1-678 GEN
50/50
3.524
970535AG2-341 GEN
50/50
1.57
3152661PLYWOOD A
50/50
0.18
3144356SAPONY
Solar/Wind Harmer
1.857
316181AB2-040 GEN
Solar/Wind Harmer
0.181
3145796HORNRTN
Solar/Wind Harmer
0.361
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
970933AG2-581 GEN
Solar/Wind Harmer
8.936
3145593CAROLNA
Solar/Wind Harmer
0.109
3145593CAROLNA
Solar/Wind Harmer
0.109
966811AG1-552 GEN
Solar/Wind Harmer
1.182
3145593CAROLNA
Solar/Wind Harmer
0.136
3145783HORNRTN
Solar/Wind Harmer
1.911
3145783HORNRTN
Solar/Wind Harmer
1.529
3145783HORNRTN
Solar/Wind Harmer
0.478
3145783HORNRTN
Solar/Wind Harmer
0.191
316426AA2-053 GEN
Solar/Wind Harmer
0.356
316274AC1-208 GEN
Solar/Wind Harmer
0.518
970099AG2-077 GEN
Solar/Wind Harmer
10.582
961601AG1-000A GEN
Solar/Wind Harmer
1.691
316263AC1-034 GEN
Solar/Wind Harmer
3.592
3151391GASTONA
50/50
0.337
3151411GASTONB
50/50
0.337
3147043LAWRENC
50/50
1.178
315243AE2-183_GT3
50/50
1.956
3151051BRUNSWICKS1
50/50
3.187
3151021BRUNSWICKG1
50/50
1.536
971451AH1-221 GEN
50/50
4.664
3151261ROARAP2
50/50
0.136
3151531CLOVER1
50/50
2.018
3151601KERR 3
50/50
0.187
3151581KERR 1
50/50
0.067
316023GEN1_S
Solar/Wind Harmer
0.354
960081AF2-299 GEN
Solar/Wind Harmer
1.332
971795AH1-408 GEN
Solar/Wind Harmer
8.516
316011AB1-132 GEN
Solar/Wind Harmer
2.263
962571AG1-106 GEN
Solar/Wind Harmer
1.771
3145796HORNRTN
Solar/Wind Harmer
0.397
3145796HORNRTN
Solar/Wind Harmer
0.12
940641AE2-051 GEN
Solar/Wind Harmer
9.263
970919AG2-571 GEN
Solar/Wind Harmer
3.98
970087AG2-069 GEN
Solar/Wind Harmer
8.913
3145783HORNRTN
Solar/Wind Harmer
0.107
315722AD1-056 GEN
Solar/Wind Harmer
0.674
316190AA2-174 GEN
Solar/Wind Harmer
0
939411AE1-173 GEN
Solar/Wind Harmer
42.901
957481AF2-042 GEN
Solar/Wind Harmer
26.456
316212AC1-099_GEN
Solar/Wind Harmer
0.502
316129AC1-054 GEN
Solar/Wind Harmer
0.364
971065AG2-659 GEN
Solar/Wind Harmer
4.087
3146233WITAKRS
Solar/Wind Harmer
0.38
3146263WOODLND
Solar/Wind Harmer
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0.34
316049AB1-081 GEN
Solar/Wind Harmer
0.541
3142053HEARTS
Solar/Wind Harmer
0.166
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.075
3145823KELFORD
Solar/Wind Harmer
0.092
315693AD1-088 GEN
Solar/Wind Harmer
4.418
961671AG1-007 GEN
Solar/Wind Harmer
0.014
3146083TARBORO
Solar/Wind Harmer
0.092
3145493TOT1
Solar/Wind Harmer
0.407
962491AG1-098 GEN
Solar/Wind Harmer
5.172
3145683EARLEYS
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.3
315687AD1-152 GEN
Solar/Wind Harmer
0.003
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.348
3145893MURPHYS
Solar/Wind Harmer
0.387
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3146293MARTNCO
Solar/Wind Harmer
0.078
970401AG2-262 GEN
Solar/Wind Harmer
0.478
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.08
971547AH1-271 GEN
Solar/Wind Harmer
1.719
3145963POPLR C
Solar/Wind Harmer
0.08
316003AC1-222 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.201
971163AH1-040 GEN
Solar/Wind Harmer
5.738
970685AG2-442 GEN
Solar/Wind Harmer
5.289
3130156CHOWAN
Solar/Wind Harmer
0.066
963171AG1-166 GEN
Solar/Wind Harmer
0.354
971563AH1-280 GEN
Solar/Wind Harmer
0.708
3144293JTRSVLE
Adder
0.211
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316294AC1-161 GEN
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.194
3146516WINFALL
Solar/Wind Harmer
0.06
944591AF1-124 GEN
Solar/Wind Harmer
12.705
3142543TWELFTH
Solar/Wind Helper
0.024
316458AB2-190 GEN2
Solar/Wind Helper
0.895
3142433PROV 92
Solar/Wind Helper
0.616
3143526WINTERP
Solar/Wind Helper
0.72
3143226MDLTHAN
Solar/Wind Helper
0.125
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
3147043LAWRENC
Solar/Wind Harmer
0.074
3145796HORNRTN
Solar/Wind Harmer
0.481
3145796HORNRTN
Solar/Wind Harmer
0.12
3142666NORTHAMPTON
Solar/Wind Harmer
0.119
970917AG2-570 GEN
Solar/Wind Harmer
9.95
315724AD1-057 GEN
Solar/Wind Harmer
0.4
316210AC1-098 GEN
Solar/Wind Harmer
0.901
316327AA2-057 GEN
Solar/Wind Harmer
0.146
3146233WITAKRS
Solar/Wind Harmer
0.48
3146233WITAKRS
Solar/Wind Harmer
0.065
3138543CONSLDL
Solar/Wind Harmer
0.063
961601AG1-000A GEN
Solar/Wind Harmer
6.766
3146263WOODLND
Solar/Wind Harmer
0.095
971623AH1-311 GEN
Solar/Wind Harmer
0.189
3145543BTLEBRO
Solar/Wind Harmer
0.094
3145543BTLEBRO
Solar/Wind Harmer
0.094
316478AD1-087 GEN
Solar/Wind Harmer
0.329
316486AD2-202 GEN
Solar/Wind Harmer
0.097
316317KELFORD C
Solar/Wind Harmer
0.009
3145823KELFORD
Solar/Wind Harmer
0.092
3146073TAR RVR
Solar/Wind Harmer
0.092
3146083TARBORO
Solar/Wind Harmer
0.092
316463AE2-346 GEN
Solar/Wind Harmer
0.076
316140AB2-099
Solar/Wind Harmer
0.032
962331AG1-082 GEN
Solar/Wind Harmer
0.95
3146173TUNIS
Solar/Wind Harmer
0.088
957521AF2-046 GEN
Solar/Wind Harmer
6.513
961681AG1-008 GEN
Solar/Wind Harmer
6.513
3145893MURPHYS
Solar/Wind Harmer
0.146
3145893MURPHYS
Solar/Wind Harmer
0.087
3156021HOLLOMANSOL
Solar/Wind Harmer
0.393
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.268
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.084
966801AG1-551 GEN
Solar/Wind Harmer
0.976
964241AG1-285 GEN
Solar/Wind Harmer
5.485
3146206CASHIE
Solar/Wind Harmer
0.08
3145963POPLR C
Solar/Wind Harmer
0.08
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.344
315785AD2-033 C
Solar/Wind Harmer
0.629
315737AD1-076 GEN
Solar/Wind Harmer
0.983
971157AH1-035 GEN
Solar/Wind Harmer
0.908
970257AG2-171 GEN
Solar/Wind Harmer
2.416
959311AF2-222 GEN
Solar/Wind Harmer
6.592
316283AC2-100 C
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.41
971683AH1-343 GEN
Solar/Wind Harmer
2.584
3146376EDENTON
Solar/Wind Harmer
0.067
963181AG1-167 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
970909AG2-566 GEN
Solar/Wind Harmer
0.692
3147133PAMPLIN
Solar/Wind Harmer
0.199
971193AH1-056 GEN
Solar/Wind Harmer
3.857
315773AC2-141 GEN
Solar/Wind Harmer
2.248
3146626S HERTFORD
Solar/Wind Harmer
0.061
3145273HOLLAND
Solar/Wind Harmer
0.046
3146516WINFALL
Solar/Wind Harmer
0.06
316435W1029_GEN3
Solar/Wind Harmer
0
316320Y1-086
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
12.66
944601AF1-125 GEN
Solar/Wind Harmer
12.465
315839AE2-212 C
Solar/Wind Helper
0.986
316473AC1-191 GEN
Solar/Wind Helper
0.925
3142946ENON
Solar/Wind Helper
0.049
315779AE2-040
50/50
3.099
315244AE2-183_ST
50/50
3.382
963041AG1-153 GEN
50/50
3.109
3151281ROARAP4
50/50
0.132
3151281ROARAP4
50/50
0.123
3151541CLOVER2
50/50
2.008
3151611KERR 4
50/50
0.187
3151621KERR 5
50/50
0.187
3151631KERR 6
50/50
0.187
3151641KERR 7
50/50
0.187
316315AB2-025 C
Solar/Wind Harmer
0.179
315814AE2-033 C
Solar/Wind Harmer
17.298
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.694
941031AE2-094 GEN
Solar/Wind Harmer
22.572
944011AF1-069 GEN
Solar/Wind Harmer
7.375
3145796HORNRTN
Solar/Wind Harmer
0.385
3145796HORNRTN
Solar/Wind Harmer
0.048
970673AG2-436 GEN
Solar/Wind Harmer
25.561
970673AG2-436 GEN
Solar/Wind Harmer
17.041
971967AH1-528 GEN
Solar/Wind Harmer
18.68
3137643SOCKMAN
Solar/Wind Harmer
0.464
970085AG2-068 GEN
Solar/Wind Harmer
5.942
970581AG2-369 GEN
Solar/Wind Harmer
5.11
315607AA1-063A GEN
Solar/Wind Harmer
0.204
3146043SEABORD
Solar/Wind Harmer
0.098
970831AG2-522 GEN
Solar/Wind Harmer
4.182
316319Z2-044 C
Solar/Wind Harmer
0
3146033SCOT NK
Solar/Wind Harmer
0.379
3145573BETHELC
Solar/Wind Harmer
0.092
3145573BETHELC
Solar/Wind Harmer
0.092
316420AA1-050 GEN
Solar/Wind Harmer
0.003
3145683EARLEYS
Solar/Wind Harmer
0.179
3145683EARLEYS
Solar/Wind Harmer
0.09
3145683EARLEYS
Solar/Wind Harmer
0.09
3145513AHOSKIE
Solar/Wind Harmer
0.186
3145513AHOSKIE
Solar/Wind Harmer
0.089
957861AF2-080 GEN
Solar/Wind Harmer
3.828
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
0.087
965291AG1-394 GEN
Solar/Wind Harmer
0.382
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316005AA1-067
Solar/Wind Harmer
0.092
3145746EVERETS
Solar/Wind Harmer
0.34
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
3145746EVERETS
Solar/Wind Harmer
0.085
970181AG2-120 GEN
Solar/Wind Harmer
1.064
3146206CASHIE
Solar/Wind Harmer
0.08
970601AG2-382 GEN
Solar/Wind Harmer
3.008
316118AC1-105 GEN
Solar/Wind Harmer
0.206
3147173SINAI
Solar/Wind Harmer
0.078
3147243WELCO
Solar/Wind Harmer
0.049
315732AD1-074 GEN1
Solar/Wind Harmer
0.439
315733AD1-074 GEN2
Solar/Wind Harmer
0.439
315735AD1-075 GEN1
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
1.275
3130546PLYMOUTH
Solar/Wind Harmer
0.076
3144303KENBRDG
Solar/Wind Harmer
0.06
3143316POE
Solar/Wind Harmer
0.287
315816AE2-034 GEN
Solar/Wind Harmer
0.308
970683AG2-441 GEN
Solar/Wind Harmer
4.722
970681AG2-440 GEN
Solar/Wind Harmer
3.778
3130156CHOWAN
Solar/Wind Harmer
0.066
3130156CHOWAN
Solar/Wind Harmer
0.066
946301AF1-294 GEN
Solar/Wind Harmer
1.311
961791AG1-021 GEN
Solar/Wind Harmer
0.638
970865AG2-541 GEN
Solar/Wind Harmer
2.298
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
315657AE1-056 GEN
Solar/Wind Harmer
2.185
316123AC1-075 GEN
Solar/Wind Harmer
0.08
970165AG2-112 GEN
Solar/Wind Harmer
0.473
970163AG2-111 GEN
Solar/Wind Harmer
0.451
3145176PASQUOTANK
Solar/Wind Harmer
0.036
316321Z2-027
Solar/Wind Harmer
0.011
3146396TANGLEW
Solar/Wind Harmer
0.161
313526AB2-022
Solar/Wind Harmer
0.031
3146486SUNBURY
Solar/Wind Harmer
0.057
3146486SUNBURY
Solar/Wind Harmer
0.057
316132AB2-190 GEN1
Solar/Wind Helper
0.895
316233AE1-074 FULL
Solar/Wind Helper
0.212
316312AB1-027
Solar/Wind Helper
0.237
3145493TOT1
Solar/Wind Harmer
0.212
3145453TOT5
Solar/Wind Harmer
0.127
3145603CNETO
Solar/Wind Harmer
0.085
939181AE1-148 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
0.088
3146173TUNIS
Solar/Wind Harmer
0.088
3145893MURPHYS
Solar/Wind Harmer
0.583
3145893MURPHYS
Solar/Wind Harmer
0.157
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3145933PARMELE
Solar/Wind Harmer
0.168
3145933PARMELE
Solar/Wind Harmer
0.084
962561AG1-105 GEN
Solar/Wind Harmer
3.947
964791AG1-342 GEN
Solar/Wind Harmer
1.566
3146843MT LREL
Solar/Wind Harmer
0.081
3146843MT LREL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.64
970323AG2-213 GEN
Solar/Wind Harmer
3.221
971775AH1-396 GEN
Solar/Wind Harmer
0.121
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.303
971741AH1-377 GEN
Solar/Wind Harmer
7.057
3146376EDENTON
Solar/Wind Harmer
0.296
3146376EDENTON
Solar/Wind Harmer
0.296
958211AF2-115 GEN
Solar/Wind Harmer
0.797
963191AG1-168 GEN
Solar/Wind Harmer
0.266
3144293JTRSVLE
Adder
0.211
3144293JTRSVLE
Adder
0.178
315742AE1-103 GEN
Solar/Wind Harmer
0.001
970301AG2-198 GEN
Solar/Wind Harmer
2.77
3147133PAMPLIN
Solar/Wind Harmer
0.063
3147133PAMPLIN
Solar/Wind Harmer
0.051
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
0.06
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
316240AF1-291 C
Solar/Wind Helper
0.411
966871AG1-558 GEN
Solar/Wind Helper
0.204
3142946ENON
Solar/Wind Helper
0.015
3143526WINTERP
Solar/Wind Helper
0.72
316468AD1-105 GEN
Solar/Wind Helper
0.653
316075AC2-137 C
Solar/Wind Helper
0.178
NYPJM->LTFIMP_NY
CLTF
0.691
LAGNLTFEXP_LAGN->PJM
CLTF
3.79
LGEELTFEXP_LGEE->PJM
CLTF
0.659
WECLTFEXP_WEC->PJM
CLTF
0.343
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.991
TVALTFEXP_TVA->PJM
CLTF
1.888
CPLELTFEXP_CPLE->PJM
CLTF
5.631
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.951
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.11
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.461
MECLTFEXP_MEC->PJM
CLTF
1.839
SIGELTFEXP_SIGE->PJM
CLTF
0.055

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.38 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1437.31
MW Contribution:6.48
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.03
315244AE2-183_ST
50/50
3.258
316315AB2-025 C
Solar/Wind Harmer
0.658
315814AE2-033 C
Solar/Wind Harmer
22.362
946281AF1-292 GEN
Solar/Wind Harmer
0.338
316087AB2-174 GEN
Solar/Wind Harmer
1.997
315652AC1-086 GEN
Solar/Wind Harmer
15.208
941031AE2-094 GEN
Solar/Wind Harmer
24.889
944011AF1-069 GEN
Solar/Wind Harmer
7.799
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
970673AG2-436 GEN
Solar/Wind Harmer
27.253
970673AG2-436 GEN
Solar/Wind Harmer
13.799
971967AH1-528 GEN
Solar/Wind Harmer
23.736
3137643SOCKMAN
Solar/Wind Harmer
-0.05
970085AG2-068 GEN
Solar/Wind Harmer
7.532
970581AG2-369 GEN
Solar/Wind Harmer
6.478
315607AA1-063A GEN
Solar/Wind Harmer
1.086
3146043SEABORD
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.273
316319Z2-044 C
Solar/Wind Harmer
0.57
3146033SCOT NK
Solar/Wind Harmer
-0.041
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
316420AA1-050 GEN
Solar/Wind Harmer
1.112
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
957861AF2-080 GEN
Solar/Wind Harmer
4.179
3145513AHOSKIE
Solar/Wind Harmer
0.083
961941AG1-037 GEN
Solar/Wind Harmer
0.072
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316318V4-068
Solar/Wind Harmer
0.232
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.815
316239AB2-077_GEN
Solar/Wind Harmer
0.277
316238AB2-078_GEN
Solar/Wind Harmer
0.277
316005AA1-067
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
-0.036
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.204
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.755
316118AC1-105 GEN
Solar/Wind Harmer
0.588
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
315732AD1-074 GEN1
Solar/Wind Harmer
1.641
315733AD1-074 GEN2
Solar/Wind Harmer
1.641
315735AD1-075 GEN1
Solar/Wind Harmer
0.821
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
1.576
3144303KENBRDG
Solar/Wind Harmer
-0.006
315816AE2-034 GEN
Solar/Wind Harmer
0.613
3143316POE
Solar/Wind Harmer
-0.029
970683AG2-441 GEN
Solar/Wind Harmer
5.791
970681AG2-440 GEN
Solar/Wind Harmer
4.633
970865AG2-541 GEN
Solar/Wind Harmer
2.878
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.768
961791AG1-021 GEN
Solar/Wind Harmer
0.863
270455AD2-022 GEN
Solar/Wind Harmer
1.198
270457AD2-023 GEN
Solar/Wind Harmer
0.607
315611Z1-036_GEN2
Solar/Wind Harmer
1.648
315657AE1-056 GEN
Solar/Wind Harmer
2.454
316233AE1-074 FULL
Solar/Wind Helper
0.26
316132AB2-190 GEN1
Solar/Wind Helper
0.962
316312AB1-027
Solar/Wind Helper
0.257
316369SG1_INVT
Solar/Wind Helper
0.561
970533AG2-339 GEN
50/50
10.502
970531AG2-338 GEN
50/50
4.201
3151361ROSEMG1
50/50
0.418
3151371ROSEMS1
50/50
0.259
3151381ROSEMG2
50/50
0.196
315242AE2-183_GT2
50/50
1.885
315241AE2-183_GT1
50/50
1.873
972185AH1-677 GEN
50/50
6.794
3144356SAPONY
Solar/Wind Harmer
0.851
316181AB2-040 GEN
Solar/Wind Harmer
1.887
3145796HORNRTN
Solar/Wind Harmer
-0.039
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
972187AH1-678 GEN
Adder
3.198
970933AG2-581 GEN
Solar/Wind Harmer
11.305
3145593CAROLNA
Solar/Wind Harmer
-0.012
3145593CAROLNA
Solar/Wind Harmer
-0.012
966811AG1-552 GEN
Solar/Wind Harmer
1.324
3145593CAROLNA
Solar/Wind Harmer
0.098
3145783HORNRTN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
1.102
3145783HORNRTN
Solar/Wind Harmer
0.344
3145783HORNRTN
Solar/Wind Harmer
0.138
316426AA2-053 GEN
Solar/Wind Harmer
1.15
316274AC1-208 GEN
Solar/Wind Harmer
1.161
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
316365GEN2_N
Solar/Wind Harmer
1.163
966621AG1-532 GEN
Solar/Wind Harmer
0.306
313506AB2-031 GEN
Solar/Wind Harmer
1.087
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970917AG2-570 GEN
Solar/Wind Harmer
30.27
315724AD1-057 GEN
Solar/Wind Harmer
0.663
316210AC1-098 GEN
Solar/Wind Harmer
1.641
316327AA2-057 GEN
Solar/Wind Harmer
1.056
3146233WITAKRS
Solar/Wind Harmer
0.216
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
4.089
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
316478AD1-087 GEN
Solar/Wind Harmer
0.876
316486AD2-202 GEN
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.467
3145823KELFORD
Solar/Wind Harmer
-0.01
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.192
3146173TUNIS
Solar/Wind Harmer
-0.009
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
3147043LAWRENC
50/50
1.136
315243AE2-183_GT3
50/50
1.885
316023GEN1_S
Solar/Wind Harmer
1.163
960081AF2-299 GEN
Solar/Wind Harmer
1.698
971795AH1-408 GEN
Solar/Wind Harmer
10.393
316011AB1-132 GEN
Solar/Wind Harmer
2.828
962571AG1-106 GEN
Solar/Wind Harmer
1.943
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
940641AE2-051 GEN
Solar/Wind Harmer
11.726
970919AG2-571 GEN
Solar/Wind Harmer
3.832
970087AG2-069 GEN
Solar/Wind Harmer
11.298
3145783HORNRTN
Solar/Wind Harmer
-0.012
315722AD1-056 GEN
Solar/Wind Harmer
1.205
316190AA2-174 GEN
Solar/Wind Harmer
0.14
939411AE1-173 GEN
Solar/Wind Harmer
53.98
957481AF2-042 GEN
Solar/Wind Harmer
33.308
316212AC1-099_GEN
Solar/Wind Harmer
0.912
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3146233WITAKRS
Solar/Wind Harmer
-0.041
971065AG2-659 GEN
Solar/Wind Harmer
5.148
316359AB2-059 GEN
Solar/Wind Harmer
1.375
316049AB1-081 GEN
Solar/Wind Harmer
1.101
3142053HEARTS
Solar/Wind Harmer
0.12
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.01
961671AG1-007 GEN
Solar/Wind Harmer
0.125
3146083TARBORO
Solar/Wind Harmer
-0.01
3145493TOT1
Solar/Wind Harmer
0.293
315693AD1-088 GEN
Solar/Wind Harmer
4.917
962491AG1-098 GEN
Solar/Wind Harmer
6.469
3145683EARLEYS
Solar/Wind Harmer
-0.01
316494AC1-189 GEN
Solar/Wind Harmer
1.028
315687AD1-152 GEN
Solar/Wind Harmer
1.146
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
0.276
316237AB2-079_GEN
Solar/Wind Harmer
0.277
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146293MARTNCO
Solar/Wind Harmer
0.056
970401AG2-262 GEN
Solar/Wind Harmer
0.569
316174AB2-169 GEN
Solar/Wind Harmer
1.336
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.146
3145963POPLR C
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.773
3145663CRESWEL
Solar/Wind Harmer
-0.021
971163AH1-040 GEN
Solar/Wind Harmer
7.107
970685AG2-442 GEN
Solar/Wind Harmer
6.486
3130156CHOWAN
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.863
971563AH1-280 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.196
315800Z1-036_GEN1
Solar/Wind Harmer
1.648
316294AC1-161 GEN
Solar/Wind Harmer
2.081
3142543TWELFTH
Solar/Wind Helper
0.025
3143526WINTERP
Solar/Wind Helper
0.886
316458AB2-190 GEN2
Solar/Wind Helper
0.962
3142433PROV 92
Solar/Wind Helper
0.66
3143226MDLTHAN
Solar/Wind Helper
0.165
3142416OLDCHRC
Solar/Wind Helper
0.352
3142416OLDCHRC
Solar/Wind Helper
0.135
957521AF2-046 GEN
Solar/Wind Harmer
7.37
961681AG1-008 GEN
Solar/Wind Harmer
7.37
3145893MURPHYS
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.247
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
316131AB2-060 GEN
Solar/Wind Harmer
0.981
3156081AA2-088 GEN
Solar/Wind Harmer
2.919
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.122
964241AG1-285 GEN
Solar/Wind Harmer
6.83
3146206CASHIE
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
316248AF1-058 C
Solar/Wind Harmer
0.253
960061AF2-297 GEN
Solar/Wind Harmer
4.197
315785AD2-033 C
Solar/Wind Harmer
1.852
315737AD1-076 GEN
Solar/Wind Harmer
1.542
971157AH1-035 GEN
Solar/Wind Harmer
1.003
970257AG2-171 GEN
Solar/Wind Harmer
2.983
316283AC2-100 C
Solar/Wind Harmer
0.735
959311AF2-222 GEN
Solar/Wind Harmer
8.141
315614AA2-178 GEN
Solar/Wind Harmer
0.818
971683AH1-343 GEN
Solar/Wind Harmer
3.238
3146376EDENTON
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
970909AG2-566 GEN
Solar/Wind Harmer
0.637
3147133PAMPLIN
Solar/Wind Harmer
-0.02
971193AH1-056 GEN
Solar/Wind Harmer
4.09
315773AC2-141 GEN
Solar/Wind Harmer
2.692
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3145273HOLLAND
Solar/Wind Harmer
-0.005
315839AE2-212 C
Solar/Wind Helper
1.003
316473AC1-191 GEN
Solar/Wind Helper
0.992
3142946ENON
Solar/Wind Helper
0.053
970099AG2-077 GEN
Solar/Wind Harmer
13.323
961601AG1-000A GEN
Solar/Wind Harmer
4.038
316263AC1-034 GEN
Solar/Wind Harmer
4.782
3145493TOT1
Solar/Wind Harmer
0.153
3145453TOT5
Solar/Wind Harmer
0.092
3145603CNETO
Solar/Wind Harmer
0.061
939181AE1-148 GEN
Solar/Wind Harmer
5.399
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.26
3145893MURPHYS
Solar/Wind Harmer
-0.017
313527AB2-043 GEN
Solar/Wind Harmer
1.49
3145933PARMELE
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.009
962561AG1-105 GEN
Solar/Wind Harmer
4.944
964791AG1-342 GEN
Solar/Wind Harmer
1.863
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316065AD1-022 GEN
Solar/Wind Harmer
4.205
970323AG2-213 GEN
Solar/Wind Harmer
3.978
971775AH1-396 GEN
Solar/Wind Harmer
0.566
316034AC1-036 C
Solar/Wind Harmer
0.147
316222AC1-221 GEN
Solar/Wind Harmer
0.793
971741AH1-377 GEN
Solar/Wind Harmer
8.632
3146376EDENTON
Solar/Wind Harmer
0.208
3146376EDENTON
Solar/Wind Harmer
0.208
315742AE1-103 GEN
Solar/Wind Harmer
0.722
958211AF2-115 GEN
Solar/Wind Harmer
1.078
963191AG1-168 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
3144293JTRSVLE
Adder
0.165
970301AG2-198 GEN
Solar/Wind Harmer
3.354
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
316240AF1-291 C
Solar/Wind Helper
0.429
3143526WINTERP
Solar/Wind Helper
0.886
966871AG1-558 GEN
Solar/Wind Helper
0.219
3142946ENON
Solar/Wind Helper
0.016
316468AD1-105 GEN
Solar/Wind Helper
0.693
316075AC2-137 C
Solar/Wind Helper
0.195
316033AB2-134 GEN
Solar/Wind Helper
0.401
315697AD1-025 GEN
Solar/Wind Helper
1.333
NYPJM->LTFIMP_NY
CLTF
0.636
LAGNLTFEXP_LAGN->PJM
CLTF
3.613
LGEELTFEXP_LGEE->PJM
CLTF
0.626
WECLTFEXP_WEC->PJM
CLTF
0.327
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.467
TVALTFEXP_TVA->PJM
CLTF
1.799
CPLELTFEXP_CPLE->PJM
CLTF
5.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.154
MECLTFEXP_MEC->PJM
CLTF
1.751
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.38 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1437.31
MW Contribution:6.48
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.03
315244AE2-183_ST
50/50
3.258
316315AB2-025 C
Solar/Wind Harmer
0.658
315814AE2-033 C
Solar/Wind Harmer
22.362
946281AF1-292 GEN
Solar/Wind Harmer
0.338
316087AB2-174 GEN
Solar/Wind Harmer
1.997
315652AC1-086 GEN
Solar/Wind Harmer
15.208
941031AE2-094 GEN
Solar/Wind Harmer
24.889
944011AF1-069 GEN
Solar/Wind Harmer
7.799
3145796HORNRTN
Solar/Wind Harmer
-0.042
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
3147043LAWRENC
50/50
1.136
315243AE2-183_GT3
50/50
1.885
316023GEN1_S
Solar/Wind Harmer
1.163
960081AF2-299 GEN
Solar/Wind Harmer
1.698
971795AH1-408 GEN
Solar/Wind Harmer
10.393
316011AB1-132 GEN
Solar/Wind Harmer
2.828
962571AG1-106 GEN
Solar/Wind Harmer
1.943
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
940641AE2-051 GEN
Solar/Wind Harmer
11.726
970919AG2-571 GEN
Solar/Wind Harmer
3.832
970087AG2-069 GEN
Solar/Wind Harmer
11.298
3145783HORNRTN
Solar/Wind Harmer
-0.012
315722AD1-056 GEN
Solar/Wind Harmer
1.205
316190AA2-174 GEN
Solar/Wind Harmer
0.14
939411AE1-173 GEN
Solar/Wind Harmer
53.98
957481AF2-042 GEN
Solar/Wind Harmer
33.308
316212AC1-099_GEN
Solar/Wind Harmer
0.912
316129AC1-054 GEN
Solar/Wind Harmer
0.913
3146233WITAKRS
Solar/Wind Harmer
-0.041
971065AG2-659 GEN
Solar/Wind Harmer
5.148
316359AB2-059 GEN
Solar/Wind Harmer
1.375
316049AB1-081 GEN
Solar/Wind Harmer
1.101
3142053HEARTS
Solar/Wind Harmer
0.12
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.01
961671AG1-007 GEN
Solar/Wind Harmer
0.125
3146083TARBORO
Solar/Wind Harmer
-0.01
3145796HORNRTN
Solar/Wind Harmer
-0.005
970673AG2-436 GEN
Solar/Wind Harmer
27.253
970673AG2-436 GEN
Solar/Wind Harmer
13.799
971967AH1-528 GEN
Solar/Wind Harmer
23.736
3137643SOCKMAN
Solar/Wind Harmer
-0.05
970085AG2-068 GEN
Solar/Wind Harmer
7.532
970581AG2-369 GEN
Solar/Wind Harmer
6.478
315607AA1-063A GEN
Solar/Wind Harmer
1.086
3146043SEABORD
Solar/Wind Harmer
-0.011
970831AG2-522 GEN
Solar/Wind Harmer
5.273
316319Z2-044 C
Solar/Wind Harmer
0.57
3146033SCOT NK
Solar/Wind Harmer
-0.041
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
316420AA1-050 GEN
Solar/Wind Harmer
1.112
3145683EARLEYS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
957861AF2-080 GEN
Solar/Wind Harmer
4.179
3145513AHOSKIE
Solar/Wind Harmer
0.083
961941AG1-037 GEN
Solar/Wind Harmer
0.072
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316318V4-068
Solar/Wind Harmer
0.232
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.815
316239AB2-077_GEN
Solar/Wind Harmer
0.277
316238AB2-078_GEN
Solar/Wind Harmer
0.277
316005AA1-067
Solar/Wind Harmer
0.186
3145746EVERETS
Solar/Wind Harmer
-0.036
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.204
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.755
316118AC1-105 GEN
Solar/Wind Harmer
0.588
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
315732AD1-074 GEN1
Solar/Wind Harmer
1.641
315733AD1-074 GEN2
Solar/Wind Harmer
1.641
315735AD1-075 GEN1
Solar/Wind Harmer
0.821
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
1.576
3144303KENBRDG
Solar/Wind Harmer
-0.006
315816AE2-034 GEN
Solar/Wind Harmer
0.613
3143316POE
Solar/Wind Harmer
-0.029
970683AG2-441 GEN
Solar/Wind Harmer
5.791
970681AG2-440 GEN
Solar/Wind Harmer
4.633
970865AG2-541 GEN
Solar/Wind Harmer
2.878
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.768
961791AG1-021 GEN
Solar/Wind Harmer
0.863
270455AD2-022 GEN
Solar/Wind Harmer
1.198
270457AD2-023 GEN
Solar/Wind Harmer
0.607
315611Z1-036_GEN2
Solar/Wind Harmer
1.648
315657AE1-056 GEN
Solar/Wind Harmer
2.454
316233AE1-074 FULL
Solar/Wind Helper
0.26
316132AB2-190 GEN1
Solar/Wind Helper
0.962
316312AB1-027
Solar/Wind Helper
0.257
316369SG1_INVT
Solar/Wind Helper
0.561
3151391GASTONA
50/50
0.325
3151411GASTONB
50/50
0.325
316365GEN2_N
Solar/Wind Harmer
1.163
966621AG1-532 GEN
Solar/Wind Harmer
0.306
313506AB2-031 GEN
Solar/Wind Harmer
1.087
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970917AG2-570 GEN
Solar/Wind Harmer
30.27
315724AD1-057 GEN
Solar/Wind Harmer
0.663
316210AC1-098 GEN
Solar/Wind Harmer
1.641
316327AA2-057 GEN
Solar/Wind Harmer
1.056
3146233WITAKRS
Solar/Wind Harmer
0.216
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
4.089
3146263WOODLND
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
316478AD1-087 GEN
Solar/Wind Harmer
0.876
316486AD2-202 GEN
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.467
3145823KELFORD
Solar/Wind Harmer
-0.01
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
316463AE2-346 GEN
Solar/Wind Harmer
0.154
316140AB2-099
Solar/Wind Harmer
0.064
962331AG1-082 GEN
Solar/Wind Harmer
1.192
3146173TUNIS
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
7.37
961681AG1-008 GEN
Solar/Wind Harmer
7.37
3145893MURPHYS
Solar/Wind Harmer
0.065
3145893MURPHYS
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.247
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
316131AB2-060 GEN
Solar/Wind Harmer
0.981
3156081AA2-088 GEN
Solar/Wind Harmer
2.919
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.122
964241AG1-285 GEN
Solar/Wind Harmer
6.83
3146206CASHIE
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
316248AF1-058 C
Solar/Wind Harmer
0.253
960061AF2-297 GEN
Solar/Wind Harmer
4.197
315785AD2-033 C
Solar/Wind Harmer
1.852
315737AD1-076 GEN
Solar/Wind Harmer
1.542
971157AH1-035 GEN
Solar/Wind Harmer
1.003
970257AG2-171 GEN
Solar/Wind Harmer
2.983
316283AC2-100 C
Solar/Wind Harmer
0.735
959311AF2-222 GEN
Solar/Wind Harmer
8.141
315614AA2-178 GEN
Solar/Wind Harmer
0.818
971683AH1-343 GEN
Solar/Wind Harmer
3.238
3146376EDENTON
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
970909AG2-566 GEN
Solar/Wind Harmer
0.637
3147133PAMPLIN
Solar/Wind Harmer
-0.02
971193AH1-056 GEN
Solar/Wind Harmer
4.09
315773AC2-141 GEN
Solar/Wind Harmer
2.692
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3145273HOLLAND
Solar/Wind Harmer
-0.005
315839AE2-212 C
Solar/Wind Helper
1.003
316473AC1-191 GEN
Solar/Wind Helper
0.992
3142946ENON
Solar/Wind Helper
0.053
970533AG2-339 GEN
50/50
10.502
970531AG2-338 GEN
50/50
4.201
3151361ROSEMG1
50/50
0.418
3151371ROSEMS1
50/50
0.259
3151381ROSEMG2
50/50
0.196
315242AE2-183_GT2
50/50
1.885
315241AE2-183_GT1
50/50
1.873
972185AH1-677 GEN
50/50
6.794
3144356SAPONY
Solar/Wind Harmer
0.851
316181AB2-040 GEN
Solar/Wind Harmer
1.887
3145796HORNRTN
Solar/Wind Harmer
-0.039
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
972187AH1-678 GEN
Adder
3.198
970933AG2-581 GEN
Solar/Wind Harmer
11.305
3145593CAROLNA
Solar/Wind Harmer
-0.012
3145593CAROLNA
Solar/Wind Harmer
-0.012
966811AG1-552 GEN
Solar/Wind Harmer
1.324
3145593CAROLNA
Solar/Wind Harmer
0.098
3145783HORNRTN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
1.102
3145493TOT1
Solar/Wind Harmer
0.293
315693AD1-088 GEN
Solar/Wind Harmer
4.917
962491AG1-098 GEN
Solar/Wind Harmer
6.469
3145683EARLEYS
Solar/Wind Harmer
-0.01
316494AC1-189 GEN
Solar/Wind Harmer
1.028
315687AD1-152 GEN
Solar/Wind Harmer
1.146
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
0.276
316237AB2-079_GEN
Solar/Wind Harmer
0.277
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146293MARTNCO
Solar/Wind Harmer
0.056
970401AG2-262 GEN
Solar/Wind Harmer
0.569
316174AB2-169 GEN
Solar/Wind Harmer
1.336
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.146
3145963POPLR C
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
0.773
3145663CRESWEL
Solar/Wind Harmer
-0.021
971163AH1-040 GEN
Solar/Wind Harmer
7.107
970685AG2-442 GEN
Solar/Wind Harmer
6.486
3130156CHOWAN
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.863
971563AH1-280 GEN
Solar/Wind Harmer
0.863
3144293JTRSVLE
Adder
0.196
315800Z1-036_GEN1
Solar/Wind Harmer
1.648
316294AC1-161 GEN
Solar/Wind Harmer
2.081
3142543TWELFTH
Solar/Wind Helper
0.025
3143526WINTERP
Solar/Wind Helper
0.886
316458AB2-190 GEN2
Solar/Wind Helper
0.962
3142433PROV 92
Solar/Wind Helper
0.66
3143226MDLTHAN
Solar/Wind Helper
0.165
3142416OLDCHRC
Solar/Wind Helper
0.352
3142416OLDCHRC
Solar/Wind Helper
0.135
3145783HORNRTN
Solar/Wind Harmer
0.344
3145783HORNRTN
Solar/Wind Harmer
0.138
316426AA2-053 GEN
Solar/Wind Harmer
1.15
316274AC1-208 GEN
Solar/Wind Harmer
1.161
970099AG2-077 GEN
Solar/Wind Harmer
13.323
961601AG1-000A GEN
Solar/Wind Harmer
4.038
316263AC1-034 GEN
Solar/Wind Harmer
4.782
3145493TOT1
Solar/Wind Harmer
0.153
3145453TOT5
Solar/Wind Harmer
0.092
3145603CNETO
Solar/Wind Harmer
0.061
939181AE1-148 GEN
Solar/Wind Harmer
5.399
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.26
3145893MURPHYS
Solar/Wind Harmer
-0.017
313527AB2-043 GEN
Solar/Wind Harmer
1.49
3145933PARMELE
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.009
962561AG1-105 GEN
Solar/Wind Harmer
4.944
964791AG1-342 GEN
Solar/Wind Harmer
1.863
3146843MT LREL
Solar/Wind Harmer
-0.009
3146843MT LREL
Solar/Wind Harmer
-0.009
316065AD1-022 GEN
Solar/Wind Harmer
4.205
970323AG2-213 GEN
Solar/Wind Harmer
3.978
971775AH1-396 GEN
Solar/Wind Harmer
0.566
316034AC1-036 C
Solar/Wind Harmer
0.147
316222AC1-221 GEN
Solar/Wind Harmer
0.793
971741AH1-377 GEN
Solar/Wind Harmer
8.632
3146376EDENTON
Solar/Wind Harmer
0.208
3146376EDENTON
Solar/Wind Harmer
0.208
315742AE1-103 GEN
Solar/Wind Harmer
0.722
958211AF2-115 GEN
Solar/Wind Harmer
1.078
963191AG1-168 GEN
Solar/Wind Harmer
0.647
3144293JTRSVLE
Adder
0.196
3144293JTRSVLE
Adder
0.165
970301AG2-198 GEN
Solar/Wind Harmer
3.354
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
316240AF1-291 C
Solar/Wind Helper
0.429
3143526WINTERP
Solar/Wind Helper
0.886
966871AG1-558 GEN
Solar/Wind Helper
0.219
3142946ENON
Solar/Wind Helper
0.016
316468AD1-105 GEN
Solar/Wind Helper
0.693
316075AC2-137 C
Solar/Wind Helper
0.195
316033AB2-134 GEN
Solar/Wind Helper
0.401
315697AD1-025 GEN
Solar/Wind Helper
1.333
NYPJM->LTFIMP_NY
CLTF
0.636
LAGNLTFEXP_LAGN->PJM
CLTF
3.613
LGEELTFEXP_LGEE->PJM
CLTF
0.626
WECLTFEXP_WEC->PJM
CLTF
0.327
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.467
TVALTFEXP_TVA->PJM
CLTF
1.799
CPLELTFEXP_CPLE->PJM
CLTF
5.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
19.007
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.535
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.154
MECLTFEXP_MEC->PJM
CLTF
1.751
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2002_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2002_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:119.0 %
Rating:984.18 MVA
Rating Type:B
MVA to Mitigate:1171.16
MW Contribution:3.98
Bus #Bus NameTypeMW Contribution
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3147043LAWRENC
50/50
1.13
3151261ROARAP2
50/50
0.121
315243AE2-183_GT3
50/50
1.518
315779AE2-040
50/50
3.401
3151281ROARAP4
50/50
0.118
3151281ROARAP4
50/50
0.11
315244AE2-183_ST
50/50
2.625
963041AG1-153 GEN
50/50
2.415
3151611KERR 4
50/50
0.157
3151621KERR 5
50/50
0.157
3151631KERR 6
50/50
0.157
3151641KERR 7
50/50
0.157
3151541CLOVER2
50/50
1.589
316315AB2-025 C
Solar/Wind Harmer
0.197
315814AE2-033 C
Solar/Wind Harmer
18.936
316087AB2-174 GEN
Solar/Wind Harmer
0.004
315652AC1-086 GEN
Solar/Wind Harmer
13.019
3145796HORNRTN
Solar/Wind Harmer
0.362
3145796HORNRTN
Solar/Wind Harmer
0.045
3137643SOCKMAN
Solar/Wind Harmer
0.427
941031AE2-094 GEN
Solar/Wind Harmer
17.475
944011AF1-069 GEN
Solar/Wind Harmer
5.71
970673AG2-436 GEN
Solar/Wind Harmer
19.819
970673AG2-436 GEN
Solar/Wind Harmer
13.213
971967AH1-528 GEN
Solar/Wind Harmer
14.51
970085AG2-068 GEN
Solar/Wind Harmer
4.631
970581AG2-369 GEN
Solar/Wind Harmer
3.982
3151391GASTONA
50/50
0.32
3151411GASTONB
50/50
0.32
3151261ROARAP2
50/50
0.119
3151031BRUNSWICKG2
50/50
1.193
3151591KERR 2
50/50
0.157
970413AG2-270 GEN
50/50
6.966
316365GEN2_N
Solar/Wind Harmer
0.362
313506AB2-031 GEN
Solar/Wind Harmer
0.366
3147043LAWRENC
Solar/Wind Harmer
0.071
3145796HORNRTN
Solar/Wind Harmer
0.453
3145796HORNRTN
Solar/Wind Harmer
0.113
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
315724AD1-057 GEN
Solar/Wind Harmer
0.363
970917AG2-570 GEN
Solar/Wind Harmer
7.751
316327AA2-057 GEN
Solar/Wind Harmer
0.127
961601AG1-000A GEN
Solar/Wind Harmer
5.909
316210AC1-098 GEN
Solar/Wind Harmer
0.77
3146233WITAKRS
Solar/Wind Harmer
0.417
3146233WITAKRS
Solar/Wind Harmer
0.056
3138543CONSLDL
Solar/Wind Harmer
0.055
971623AH1-311 GEN
Solar/Wind Harmer
0.164
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.082
3146263WOODLND
Solar/Wind Harmer
0.078
3146073TAR RVR
Solar/Wind Harmer
0.078
3146083TARBORO
Solar/Wind Harmer
0.078
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.075
316478AD1-087 GEN
Solar/Wind Harmer
0.26
316486AD2-202 GEN
Solar/Wind Harmer
0.076
316131AB2-060 GEN
Solar/Wind Harmer
0.229
964241AG1-285 GEN
Solar/Wind Harmer
4.665
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.742
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
3156021HOLLOMANSOL
Solar/Wind Harmer
0.305
3145933PARMELE
Solar/Wind Harmer
0.066
966801AG1-551 GEN
Solar/Wind Harmer
0.769
957521AF2-046 GEN
Solar/Wind Harmer
4.888
961681AG1-008 GEN
Solar/Wind Harmer
4.888
315785AD2-033 C
Solar/Wind Harmer
0.532
3145893MURPHYS
Solar/Wind Harmer
0.108
3145893MURPHYS
Solar/Wind Harmer
0.065
970257AG2-171 GEN
Solar/Wind Harmer
2.041
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
2.715
959311AF2-222 GEN
Solar/Wind Harmer
5.561
3145963POPLR C
Solar/Wind Harmer
0.06
3156081AA2-088 GEN
Solar/Wind Harmer
0.001
3146206CASHIE
Solar/Wind Harmer
0.059
316283AC2-100 C
Solar/Wind Harmer
0.115
971683AH1-343 GEN
Solar/Wind Harmer
2.095
315839AE2-212 C
Solar/Wind Helper
1.113
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.189
316280AD1-041 GEN
Solar/Wind Helper
0.416
316404AE1-155 C
Solar/Wind Helper
0.956
316484AD2-074 GEN
Solar/Wind Helper
0.219
316156AD2-030 GEN
Solar/Wind Helper
0.171
3151361ROSEMG1
50/50
0.408
3151371ROSEMS1
50/50
0.253
3151381ROSEMG2
50/50
0.191
970533AG2-339 GEN
50/50
8.434
970531AG2-338 GEN
50/50
3.373
315242AE2-183_GT2
50/50
1.518
315241AE2-183_GT1
50/50
1.509
972185AH1-677 GEN
50/50
5.473
3151041BRUNSWICKG3
50/50
1.193
972187AH1-678 GEN
50/50
2.737
970535AG2-341 GEN
50/50
1.329
3152661PLYWOOD A
50/50
0.148
3144356SAPONY
Solar/Wind Harmer
2.038
316181AB2-040 GEN
Solar/Wind Harmer
0.172
3145796HORNRTN
Solar/Wind Harmer
0.34
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3145593CAROLNA
Solar/Wind Harmer
0.097
3145593CAROLNA
Solar/Wind Harmer
0.097
966811AG1-552 GEN
Solar/Wind Harmer
1.057
3145593CAROLNA
Solar/Wind Harmer
0.121
3145783HORNRTN
Solar/Wind Harmer
1.703
3145783HORNRTN
Solar/Wind Harmer
1.362
3145783HORNRTN
Solar/Wind Harmer
0.426
3145783HORNRTN
Solar/Wind Harmer
0.17
316426AA2-053 GEN
Solar/Wind Harmer
0.313
970933AG2-581 GEN
Solar/Wind Harmer
6.963
316274AC1-208 GEN
Solar/Wind Harmer
0.45
961601AG1-000A GEN
Solar/Wind Harmer
1.477
316263AC1-034 GEN
Solar/Wind Harmer
3.125
970099AG2-077 GEN
Solar/Wind Harmer
8.325
3145493TOT1
Solar/Wind Harmer
0.181
3145453TOT5
Solar/Wind Harmer
0.108
3145603CNETO
Solar/Wind Harmer
0.072
939181AE1-148 GEN
Solar/Wind Harmer
3.627
313527AB2-043 GEN
Solar/Wind Harmer
0.001
962561AG1-105 GEN
Solar/Wind Harmer
3.291
3146173TUNIS
Solar/Wind Harmer
0.068
3146173TUNIS
Solar/Wind Harmer
0.068
964791AG1-342 GEN
Solar/Wind Harmer
1.3
3146843MT LREL
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.068
3145933PARMELE
Solar/Wind Harmer
0.132
3145933PARMELE
Solar/Wind Harmer
0.066
3145893MURPHYS
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
0.116
970323AG2-213 GEN
Solar/Wind Harmer
2.721
971775AH1-396 GEN
Solar/Wind Harmer
0.102
316034AC1-036 C
Solar/Wind Harmer
0.005
316222AC1-221 GEN
Solar/Wind Harmer
0.245
316065AD1-022 GEN
Solar/Wind Harmer
2.617
971741AH1-377 GEN
Solar/Wind Harmer
5.589
316240AF1-291 C
Solar/Wind Helper
0.691
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.717
315697AD1-025 GEN
Solar/Wind Helper
2.382
966871AG1-558 GEN
Solar/Wind Helper
0.262
316075AC2-137 C
Solar/Wind Helper
0.263
316468AD1-105 GEN
Solar/Wind Helper
0.815
3143526WINTERP
Solar/Wind Helper
0.727
316077AC2-138 C
Solar/Wind Helper
0.107
316487AF1-042 GEN
Solar/Wind Helper
0.114
3151051BRUNSWICKS1
50/50
2.476
3151021BRUNSWICKG1
50/50
1.193
971451AH1-221 GEN
50/50
3.623
3151601KERR 3
50/50
0.157
3151581KERR 1
50/50
0.056
3151531CLOVER1
50/50
1.596
316023GEN1_S
Solar/Wind Harmer
0.362
960081AF2-299 GEN
Solar/Wind Harmer
1.316
971795AH1-408 GEN
Solar/Wind Harmer
8.254
316011AB1-132 GEN
Solar/Wind Harmer
2.152
962571AG1-106 GEN
Solar/Wind Harmer
1.684
3145796HORNRTN
Solar/Wind Harmer
0.374
3145796HORNRTN
Solar/Wind Harmer
0.113
315722AD1-056 GEN
Solar/Wind Harmer
0.612
3145783HORNRTN
Solar/Wind Harmer
0.096
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
3.101
970087AG2-069 GEN
Solar/Wind Harmer
6.946
940641AE2-051 GEN
Solar/Wind Harmer
6.931
316129AC1-054 GEN
Solar/Wind Harmer
0.314
316212AC1-099_GEN
Solar/Wind Harmer
0.43
3146233WITAKRS
Solar/Wind Harmer
0.33
971065AG2-659 GEN
Solar/Wind Harmer
3.51
316359AB2-059 GEN
Solar/Wind Harmer
0.295
316049AB1-081 GEN
Solar/Wind Harmer
0.471
3142053HEARTS
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
0.066
3146263WOODLND
Solar/Wind Harmer
0.078
957481AF2-042 GEN
Solar/Wind Harmer
20.812
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.078
3145493TOT1
Solar/Wind Harmer
0.346
3145823KELFORD
Solar/Wind Harmer
0.075
316494AC1-189 GEN
Solar/Wind Harmer
0.249
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
3.49
962491AG1-098 GEN
Solar/Wind Harmer
4.086
3145683EARLEYS
Solar/Wind Harmer
0.071
315687AD1-152 GEN
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
30.084
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.068
970401AG2-262 GEN
Solar/Wind Harmer
0.397
3146293MARTNCO
Solar/Wind Harmer
0.061
3145893MURPHYS
Solar/Wind Harmer
0.259
3145893MURPHYS
Solar/Wind Harmer
0.288
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.06
316003AC1-222 GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
4.444
3146206CASHIE
Solar/Wind Harmer
0.059
971547AH1-271 GEN
Solar/Wind Harmer
1.257
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.544
316381AD1-082 GEN
Solar/Wind Helper
1.346
3142433PROV 92
Solar/Wind Helper
0.863
3142416OLDCHRC
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.727
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
970831AG2-522 GEN
Solar/Wind Harmer
3.621
315607AA1-063A GEN
Solar/Wind Harmer
0.17
316319Z2-044 C
Solar/Wind Harmer
0
3146043SEABORD
Solar/Wind Harmer
0.081
3146033SCOT NK
Solar/Wind Harmer
0.318
3145573BETHELC
Solar/Wind Harmer
0.078
3145573BETHELC
Solar/Wind Harmer
0.078
316420AA1-050 GEN
Solar/Wind Harmer
0.003
957861AF2-080 GEN
Solar/Wind Harmer
3.178
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3145683EARLEYS
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.145
3145513AHOSKIE
Solar/Wind Harmer
0.07
316005AA1-067
Solar/Wind Harmer
0.074
3145746EVERETS
Solar/Wind Harmer
0.274
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.069
970181AG2-120 GEN
Solar/Wind Harmer
0.856
316118AC1-105 GEN
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
0.065
971443AH1-215 GEN
Solar/Wind Harmer
1.078
3144303KENBRDG
Solar/Wind Harmer
0.051
3147173SINAI
Solar/Wind Harmer
0.064
3147243WELCO
Solar/Wind Harmer
0.04
965291AG1-394 GEN
Solar/Wind Harmer
0.275
970683AG2-441 GEN
Solar/Wind Harmer
3.967
970681AG2-440 GEN
Solar/Wind Harmer
3.174
3146206CASHIE
Solar/Wind Harmer
0.059
970601AG2-382 GEN
Solar/Wind Harmer
2.2
3143316POE
Solar/Wind Helper
1.93
316132AB2-190 GEN1
Solar/Wind Helper
1.544
316369SG1_INVT
Solar/Wind Helper
1.002
316312AB1-027
Solar/Wind Helper
0.328
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.214
315662AE1-191 GEN
Solar/Wind Helper
0.666
315666AE1-190 GEN
Solar/Wind Helper
0.167
316059AD1-063 C
Solar/Wind Helper
0.122
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3141913WHIT STONE
Solar/Wind Helper
0.113
3138133OCRAN
Solar/Wind Helper
0.034
957601AF2-054 GEN
Solar/Wind Helper
0.152
3141873WAN 176
Solar/Wind Helper
0.023
NYPJM->LTFIMP_NY
CLTF
0.457
LGEELTFEXP_LGEE->PJM
CLTF
0.557
LAGNLTFEXP_LAGN->PJM
CLTF
3.11
WECLTFEXP_WEC->PJM
CLTF
0.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.716
TVALTFEXP_TVA->PJM
CLTF
1.547
CPLELTFEXP_CPLE->PJM
CLTF
4.572
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.518
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.548
SIGELTFEXP_SIGE->PJM
CLTF
0.046

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.8 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1322.03
MW Contribution:5.72
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
0.469
3151371ROSEMS1
50/50
0.29
3151381ROSEMG2
50/50
0.219
3144356SAPONY
Solar/Wind Harmer
1.028
316181AB2-040 GEN
Solar/Wind Harmer
2.122
3145796HORNRTN
Solar/Wind Harmer
-0.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.013
3145593CAROLNA
Solar/Wind Harmer
-0.013
966811AG1-552 GEN
Solar/Wind Harmer
1.454
3145593CAROLNA
Solar/Wind Harmer
0.107
3145783HORNRTN
Solar/Wind Harmer
1.509
3145783HORNRTN
Solar/Wind Harmer
1.207
3145783HORNRTN
Solar/Wind Harmer
0.377
3145783HORNRTN
Solar/Wind Harmer
0.151
316426AA2-053 GEN
Solar/Wind Harmer
1.258
316274AC1-208 GEN
Solar/Wind Harmer
1.251
972185AH1-677 GEN
Adder
5.61
972187AH1-678 GEN
Adder
2.808
961601AG1-000A GEN
Solar/Wind Harmer
4.277
316263AC1-034 GEN
Solar/Wind Harmer
5.056
970933AG2-581 GEN
Solar/Wind Harmer
9.991
3145493TOT1
Solar/Wind Harmer
0.161
3151391GASTONA
50/50
0.367
3151411GASTONB
50/50
0.367
3151261ROARAP2
50/50
0.14
316365GEN2_N
Solar/Wind Harmer
1.356
966621AG1-532 GEN
Solar/Wind Harmer
0.35
313506AB2-031 GEN
Solar/Wind Harmer
1.223
3147043LAWRENC
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
315724AD1-057 GEN
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.764
316327AA2-057 GEN
Solar/Wind Harmer
1.127
3146263WOODLND
Solar/Wind Harmer
-0.011
3146233WITAKRS
Solar/Wind Harmer
0.229
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
4.332
3145543BTLEBRO
Solar/Wind Harmer
-0.011
3145543BTLEBRO
Solar/Wind Harmer
-0.011
970917AG2-570 GEN
Solar/Wind Harmer
26.73
316317KELFORD C
Solar/Wind Harmer
0.501
3145823KELFORD
Solar/Wind Harmer
-0.011
3146073TAR RVR
Solar/Wind Harmer
-0.01
3146083TARBORO
Solar/Wind Harmer
-0.01
316463AE2-346 GEN
Solar/Wind Harmer
0.166
316140AB2-099
Solar/Wind Harmer
0.069
962331AG1-082 GEN
Solar/Wind Harmer
1.28
3146173TUNIS
Solar/Wind Harmer
-0.01
957521AF2-046 GEN
Solar/Wind Harmer
7.946
961681AG1-008 GEN
Solar/Wind Harmer
7.946
3145893MURPHYS
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
-0.01
3156021HOLLOMANSOL
Solar/Wind Harmer
1.329
3156081AA2-088 GEN
Solar/Wind Harmer
3.157
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.173
316478AD1-087 GEN
Solar/Wind Harmer
0.797
316486AD2-202 GEN
Solar/Wind Harmer
0.233
315779AE2-040
50/50
3.663
3151281ROARAP4
50/50
0.139
3151281ROARAP4
50/50
0.13
316315AB2-025 C
Solar/Wind Harmer
0.795
315814AE2-033 C
Solar/Wind Harmer
26.999
946281AF1-292 GEN
Solar/Wind Harmer
0.386
316087AB2-174 GEN
Solar/Wind Harmer
2.258
315652AC1-086 GEN
Solar/Wind Harmer
17.155
3145796HORNRTN
Solar/Wind Harmer
-0.046
3145796HORNRTN
Solar/Wind Harmer
-0.006
3137643SOCKMAN
Solar/Wind Harmer
-0.056
3143316POE
Solar/Wind Harmer
-0.048
315607AA1-063A GEN
Solar/Wind Harmer
1.187
941031AE2-094 GEN
Solar/Wind Harmer
21.703
944011AF1-069 GEN
Solar/Wind Harmer
6.8
3146043SEABORD
Solar/Wind Harmer
-0.012
970673AG2-436 GEN
Solar/Wind Harmer
23.837
970673AG2-436 GEN
Solar/Wind Harmer
12.069
971967AH1-528 GEN
Solar/Wind Harmer
20.84
970831AG2-522 GEN
Solar/Wind Harmer
5.503
3146033SCOT NK
Solar/Wind Harmer
-0.044
316319Z2-044 C
Solar/Wind Harmer
0.606
970085AG2-068 GEN
Solar/Wind Harmer
6.656
970581AG2-369 GEN
Solar/Wind Harmer
5.724
3145573BETHELC
Solar/Wind Harmer
-0.01
3145573BETHELC
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.01
316420AA1-050 GEN
Solar/Wind Harmer
1.171
3145513AHOSKIE
Solar/Wind Harmer
0.089
961941AG1-037 GEN
Solar/Wind Harmer
0.077
3145513AHOSKIE
Solar/Wind Harmer
-0.01
316318V4-068
Solar/Wind Harmer
0.251
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.01
957861AF2-080 GEN
Solar/Wind Harmer
4.39
965291AG1-394 GEN
Solar/Wind Harmer
0.882
316005AA1-067
Solar/Wind Harmer
0.194
3145746EVERETS
Solar/Wind Harmer
-0.038
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
970181AG2-120 GEN
Solar/Wind Harmer
1.259
316239AB2-077_GEN
Solar/Wind Harmer
0.278
316238AB2-078_GEN
Solar/Wind Harmer
0.278
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.951
315732AD1-074 GEN1
Solar/Wind Harmer
1.708
315733AD1-074 GEN2
Solar/Wind Harmer
1.708
315735AD1-075 GEN1
Solar/Wind Harmer
0.854
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
316118AC1-105 GEN
Solar/Wind Harmer
0.565
971443AH1-215 GEN
Solar/Wind Harmer
1.585
3144303KENBRDG
Solar/Wind Harmer
-0.006
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
315816AE2-034 GEN
Solar/Wind Harmer
0.631
970683AG2-441 GEN
Solar/Wind Harmer
5.825
970681AG2-440 GEN
Solar/Wind Harmer
4.66
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.779
961791AG1-021 GEN
Solar/Wind Harmer
0.868
970865AG2-541 GEN
Solar/Wind Harmer
2.735
315611Z1-036_GEN2
Solar/Wind Harmer
1.655
315657AE1-056 GEN
Solar/Wind Harmer
2.469
270455AD2-022 GEN
Solar/Wind Harmer
1.142
270457AD2-023 GEN
Solar/Wind Harmer
0.579
316132AB2-190 GEN1
Solar/Wind Helper
0.788
316233AE1-074 FULL
Solar/Wind Helper
0.19
316312AB1-027
Solar/Wind Helper
0.214
316131AB2-060 GEN
Solar/Wind Harmer
0.986
3146206CASHIE
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
6.87
315737AD1-076 GEN
Solar/Wind Harmer
1.605
971157AH1-035 GEN
Solar/Wind Harmer
1.043
315785AD2-033 C
Solar/Wind Harmer
1.862
970257AG2-171 GEN
Solar/Wind Harmer
3.001
316248AF1-058 C
Solar/Wind Harmer
0.24
960061AF2-297 GEN
Solar/Wind Harmer
3.979
959311AF2-222 GEN
Solar/Wind Harmer
8.189
315614AA2-178 GEN
Solar/Wind Harmer
0.842
316283AC2-100 C
Solar/Wind Harmer
0.696
971683AH1-343 GEN
Solar/Wind Harmer
3.075
3146376EDENTON
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.651
3144293JTRSVLE
Adder
0.197
3145273HOLLAND
Solar/Wind Harmer
-0.005
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.115
3146626S HERTFORD
Solar/Wind Harmer
-0.006
970909AG2-566 GEN
Solar/Wind Harmer
0.603
315839AE2-212 C
Solar/Wind Helper
0.91
316473AC1-191 GEN
Solar/Wind Helper
0.834
3142946ENON
Solar/Wind Helper
0.044
3151391GASTONA
50/50
0.367
3151411GASTONB
50/50
0.367
3147043LAWRENC
50/50
1.265
3151261ROARAP2
50/50
0.143
316023GEN1_S
Solar/Wind Harmer
1.356
960081AF2-299 GEN
Solar/Wind Harmer
1.94
971795AH1-408 GEN
Solar/Wind Harmer
11.683
316011AB1-132 GEN
Solar/Wind Harmer
3.19
962571AG1-106 GEN
Solar/Wind Harmer
2.192
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145796HORNRTN
Solar/Wind Harmer
-0.015
3145783HORNRTN
Solar/Wind Harmer
-0.013
315722AD1-056 GEN
Solar/Wind Harmer
1.314
316190AA2-174 GEN
Solar/Wind Harmer
0.153
316212AC1-099_GEN
Solar/Wind Harmer
0.98
3146263WOODLND
Solar/Wind Harmer
-0.011
3146233WITAKRS
Solar/Wind Harmer
-0.043
940641AE2-051 GEN
Solar/Wind Harmer
10.201
316129AC1-054 GEN
Solar/Wind Harmer
0.947
316359AB2-059 GEN
Solar/Wind Harmer
1.454
316049AB1-081 GEN
Solar/Wind Harmer
1.164
3142053HEARTS
Solar/Wind Harmer
0.127
3145543BTLEBRO
Solar/Wind Harmer
-0.011
3145543BTLEBRO
Solar/Wind Harmer
-0.009
970919AG2-571 GEN
Solar/Wind Harmer
3.384
970087AG2-069 GEN
Solar/Wind Harmer
9.984
3145823KELFORD
Solar/Wind Harmer
-0.011
971065AG2-659 GEN
Solar/Wind Harmer
5.306
961671AG1-007 GEN
Solar/Wind Harmer
0.132
3146083TARBORO
Solar/Wind Harmer
-0.01
3145493TOT1
Solar/Wind Harmer
0.309
3145683EARLEYS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
0.298
316494AC1-189 GEN
Solar/Wind Harmer
1.08
957481AF2-042 GEN
Solar/Wind Harmer
30.018
3145746EVERETS
Solar/Wind Harmer
-0.01
3145746EVERETS
Solar/Wind Harmer
-0.01
939411AE1-173 GEN
Solar/Wind Harmer
47.496
3146293MARTNCO
Solar/Wind Harmer
0.058
316237AB2-079_GEN
Solar/Wind Harmer
0.278
316174AB2-169 GEN
Solar/Wind Harmer
1.394
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.258
315693AD1-088 GEN
Solar/Wind Harmer
4.482
3145963POPLR C
Solar/Wind Harmer
-0.009
962491AG1-098 GEN
Solar/Wind Harmer
5.904
315687AD1-152 GEN
Solar/Wind Harmer
1.054
970401AG2-262 GEN
Solar/Wind Harmer
0.554
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.314
316003AC1-222 GEN
Solar/Wind Harmer
0.734
970685AG2-442 GEN
Solar/Wind Harmer
6.524
3130156CHOWAN
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.868
971563AH1-280 GEN
Solar/Wind Harmer
0.868
3144293JTRSVLE
Adder
0.197
315800Z1-036_GEN1
Solar/Wind Harmer
1.655
3142543TWELFTH
Solar/Wind Helper
0.021
3142433PROV 92
Solar/Wind Helper
0.564
316458AB2-190 GEN2
Solar/Wind Helper
0.788
3143526WINTERP
Solar/Wind Helper
0.647
3143226MDLTHAN
Solar/Wind Helper
0.112
3142416OLDCHRC
Solar/Wind Helper
0.292
3142416OLDCHRC
Solar/Wind Helper
0.112
3145453TOT5
Solar/Wind Harmer
0.097
3145603CNETO
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
-0.01
3146173TUNIS
Solar/Wind Harmer
-0.01
3145893MURPHYS
Solar/Wind Harmer
0.28
3145893MURPHYS
Solar/Wind Harmer
-0.018
970099AG2-077 GEN
Solar/Wind Harmer
12.007
939181AE1-148 GEN
Solar/Wind Harmer
5.392
3145933PARMELE
Solar/Wind Harmer
-0.019
3145933PARMELE
Solar/Wind Harmer
-0.009
313527AB2-043 GEN
Solar/Wind Harmer
1.499
316065AD1-022 GEN
Solar/Wind Harmer
4.409
962561AG1-105 GEN
Solar/Wind Harmer
4.838
964791AG1-342 GEN
Solar/Wind Harmer
1.813
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
4.001
971775AH1-396 GEN
Solar/Wind Harmer
0.57
316034AC1-036 C
Solar/Wind Harmer
0.148
316222AC1-221 GEN
Solar/Wind Harmer
0.751
315742AE1-103 GEN
Solar/Wind Harmer
0.77
3146376EDENTON
Solar/Wind Harmer
0.21
3146376EDENTON
Solar/Wind Harmer
0.21
971741AH1-377 GEN
Solar/Wind Harmer
8.082
958211AF2-115 GEN
Solar/Wind Harmer
1.085
963191AG1-168 GEN
Solar/Wind Harmer
0.651
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
970301AG2-198 GEN
Solar/Wind Harmer
3.177
316240AF1-291 C
Solar/Wind Helper
0.351
966871AG1-558 GEN
Solar/Wind Helper
0.184
3142946ENON
Solar/Wind Helper
0.013
3143526WINTERP
Solar/Wind Helper
0.647
316468AD1-105 GEN
Solar/Wind Helper
0.589
NYPJM->LTFIMP_NY
CLTF
0.631
LGEELTFEXP_LGEE->PJM
CLTF
0.598
LAGNLTFEXP_LAGN->PJM
CLTF
3.447
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.956
WECLTFEXP_WEC->PJM
CLTF
0.311
TVALTFEXP_TVA->PJM
CLTF
1.717
CPLELTFEXP_CPLE->PJM
CLTF
5.179
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.13
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.874
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.05

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P4-5: L552_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: L552_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1261.5
MW Contribution:5.32
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
3.403
316315AB2-025 C
Solar/Wind Harmer
0.739
315814AE2-033 C
Solar/Wind Harmer
25.066
946281AF1-292 GEN
Solar/Wind Harmer
0.352
316087AB2-174 GEN
Solar/Wind Harmer
2.042
315652AC1-086 GEN
Solar/Wind Harmer
15.395
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.05
941031AE2-094 GEN
Solar/Wind Harmer
20.229
944011AF1-069 GEN
Solar/Wind Harmer
6.339
970673AG2-436 GEN
Solar/Wind Harmer
22.201
970673AG2-436 GEN
Solar/Wind Harmer
11.241
971967AH1-528 GEN
Solar/Wind Harmer
19.398
315607AA1-063A GEN
Solar/Wind Harmer
1.035
3146043SEABORD
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
4.947
970085AG2-068 GEN
Solar/Wind Harmer
6.181
3151391GASTONA
50/50
0.329
3151411GASTONB
50/50
0.329
3147043LAWRENC
50/50
1.152
316023GEN1_S
Solar/Wind Harmer
1.24
960081AF2-299 GEN
Solar/Wind Harmer
1.766
971795AH1-408 GEN
Solar/Wind Harmer
10.639
316011AB1-132 GEN
Solar/Wind Harmer
2.863
962571AG1-106 GEN
Solar/Wind Harmer
1.967
3145796HORNRTN
Solar/Wind Harmer
-0.043
3145796HORNRTN
Solar/Wind Harmer
-0.013
3145783HORNRTN
Solar/Wind Harmer
-0.011
315722AD1-056 GEN
Solar/Wind Harmer
1.174
316190AA2-174 GEN
Solar/Wind Harmer
0.135
970919AG2-571 GEN
Solar/Wind Harmer
3.143
970087AG2-069 GEN
Solar/Wind Harmer
9.272
940641AE2-051 GEN
Solar/Wind Harmer
9.271
316212AC1-099_GEN
Solar/Wind Harmer
0.858
316129AC1-054 GEN
Solar/Wind Harmer
0.853
3146233WITAKRS
Solar/Wind Harmer
-0.038
316359AB2-059 GEN
Solar/Wind Harmer
1.293
316049AB1-081 GEN
Solar/Wind Harmer
1.035
3142053HEARTS
Solar/Wind Harmer
0.113
971065AG2-659 GEN
Solar/Wind Harmer
4.783
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3146263WOODLND
Solar/Wind Harmer
-0.009
961671AG1-007 GEN
Solar/Wind Harmer
0.116
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.271
3145823KELFORD
Solar/Wind Harmer
-0.009
957481AF2-042 GEN
Solar/Wind Harmer
27.804
316494AC1-189 GEN
Solar/Wind Harmer
0.937
3145683EARLEYS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
316237AB2-079_GEN
Solar/Wind Harmer
0.253
315693AD1-088 GEN
Solar/Wind Harmer
4.145
939411AE1-173 GEN
Solar/Wind Harmer
41.056
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
962491AG1-098 GEN
Solar/Wind Harmer
5.46
315687AD1-152 GEN
Solar/Wind Harmer
0.971
3146293MARTNCO
Solar/Wind Harmer
0.049
970401AG2-262 GEN
Solar/Wind Harmer
0.507
316174AB2-169 GEN
Solar/Wind Harmer
1.149
3145963POPLR C
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.82
316003AC1-222 GEN
Solar/Wind Harmer
0.671
970685AG2-442 GEN
Solar/Wind Harmer
5.963
963171AG1-166 GEN
Solar/Wind Harmer
0.793
971563AH1-280 GEN
Solar/Wind Harmer
0.793
3144293JTRSVLE
Adder
0.18
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.594
3142433PROV 92
Solar/Wind Helper
0.882
3142416OLDCHRC
Solar/Wind Helper
0.459
3142416OLDCHRC
Solar/Wind Helper
0.176
3143526WINTERP
Solar/Wind Helper
0.751
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.159
3141726DUNNSVL
Solar/Wind Helper
0.473
3138133OCRAN
Solar/Wind Helper
0.069
316337AD2-073 GEN
Solar/Wind Helper
0.17
970581AG2-369 GEN
Solar/Wind Harmer
5.316
316319Z2-044 C
Solar/Wind Harmer
0.537
3146033SCOT NK
Solar/Wind Harmer
-0.038
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316420AA1-050 GEN
Solar/Wind Harmer
1.023
957861AF2-080 GEN
Solar/Wind Harmer
3.811
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.075
961941AG1-037 GEN
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.009
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
316239AB2-077_GEN
Solar/Wind Harmer
0.253
316238AB2-078_GEN
Solar/Wind Harmer
0.253
965291AG1-394 GEN
Solar/Wind Harmer
0.741
316005AA1-067
Solar/Wind Harmer
0.166
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.077
316118AC1-105 GEN
Solar/Wind Harmer
0.517
971443AH1-215 GEN
Solar/Wind Harmer
1.448
3144303KENBRDG
Solar/Wind Harmer
-0.006
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.184
970683AG2-441 GEN
Solar/Wind Harmer
5.324
970681AG2-440 GEN
Solar/Wind Harmer
4.26
315732AD1-074 GEN1
Solar/Wind Harmer
1.344
315733AD1-074 GEN2
Solar/Wind Harmer
1.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.672
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
946301AF1-294 GEN
Solar/Wind Harmer
1.627
961791AG1-021 GEN
Solar/Wind Harmer
0.793
3143316POE
Solar/Wind Helper
2.108
316132AB2-190 GEN1
Solar/Wind Helper
1.594
316369SG1_INVT
Solar/Wind Helper
1.025
316312AB1-027
Solar/Wind Helper
0.336
3143873LANEXA
Solar/Wind Helper
0.097
316233AE1-074 FULL
Solar/Wind Helper
0.221
315662AE1-191 GEN
Solar/Wind Helper
0.675
315666AE1-190 GEN
Solar/Wind Helper
0.169
316059AD1-063 C
Solar/Wind Helper
0.123
3141813NORNECK
Solar/Wind Helper
0.115
3141783LANCAST
Solar/Wind Helper
0.069
3141783LANCAST
Solar/Wind Helper
0.046
3138133OCRAN
Solar/Wind Helper
0.034
3141913WHIT STONE
Solar/Wind Helper
0.114
957601AF2-054 GEN
Solar/Wind Helper
0.153
3141873WAN 176
Solar/Wind Helper
0.023
3151391GASTONA
50/50
0.329
3151411GASTONB
50/50
0.329
316365GEN2_N
Solar/Wind Harmer
1.24
966621AG1-532 GEN
Solar/Wind Harmer
0.319
313506AB2-031 GEN
Solar/Wind Harmer
1.102
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
0.646
970917AG2-570 GEN
Solar/Wind Harmer
24.829
316327AA2-057 GEN
Solar/Wind Harmer
0.997
316210AC1-098 GEN
Solar/Wind Harmer
1.544
3146233WITAKRS
Solar/Wind Harmer
0.203
3146233WITAKRS
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.852
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3145543BTLEBRO
Solar/Wind Harmer
-0.01
3146263WOODLND
Solar/Wind Harmer
-0.009
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.428
3145823KELFORD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.14
316140AB2-099
Solar/Wind Harmer
0.058
962331AG1-082 GEN
Solar/Wind Harmer
1.078
3146173TUNIS
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
0.737
316486AD2-202 GEN
Solar/Wind Harmer
0.216
957521AF2-046 GEN
Solar/Wind Harmer
6.683
961681AG1-008 GEN
Solar/Wind Harmer
6.683
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
316131AB2-060 GEN
Solar/Wind Harmer
0.9
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.102
3156081AA2-088 GEN
Solar/Wind Harmer
2.638
964241AG1-285 GEN
Solar/Wind Harmer
6.272
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
0.99
315785AD2-033 C
Solar/Wind Harmer
1.701
3145963POPLR C
Solar/Wind Harmer
-0.007
970257AG2-171 GEN
Solar/Wind Harmer
2.741
316248AF1-058 C
Solar/Wind Harmer
0.22
960061AF2-297 GEN
Solar/Wind Harmer
3.644
3146206CASHIE
Solar/Wind Harmer
-0.007
959311AF2-222 GEN
Solar/Wind Harmer
7.482
316283AC2-100 C
Solar/Wind Harmer
0.635
315737AD1-076 GEN
Solar/Wind Harmer
1.263
971157AH1-035 GEN
Solar/Wind Harmer
0.816
971683AH1-343 GEN
Solar/Wind Harmer
2.812
963181AG1-167 GEN
Solar/Wind Harmer
0.595
3144293JTRSVLE
Adder
0.18
315839AE2-212 C
Solar/Wind Helper
1.129
3142946ENON
Solar/Wind Helper
0.076
316473AC1-191 GEN
Solar/Wind Helper
1.222
316280AD1-041 GEN
Solar/Wind Helper
0.422
316404AE1-155 C
Solar/Wind Helper
0.97
316484AD2-074 GEN
Solar/Wind Helper
0.222
316156AD2-030 GEN
Solar/Wind Helper
0.172
3151361ROSEMG1
50/50
0.42
3151371ROSEMS1
50/50
0.26
3151381ROSEMG2
50/50
0.197
3144356SAPONY
Solar/Wind Harmer
0.955
316181AB2-040 GEN
Solar/Wind Harmer
1.913
3145796HORNRTN
Solar/Wind Harmer
-0.039
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
966811AG1-552 GEN
Solar/Wind Harmer
1.292
3145593CAROLNA
Solar/Wind Harmer
0.095
3145783HORNRTN
Solar/Wind Harmer
1.339
3145783HORNRTN
Solar/Wind Harmer
1.072
3145783HORNRTN
Solar/Wind Harmer
0.335
3145783HORNRTN
Solar/Wind Harmer
0.134
316426AA2-053 GEN
Solar/Wind Harmer
1.11
972185AH1-677 GEN
Adder
5.222
972187AH1-678 GEN
Adder
2.613
316274AC1-208 GEN
Solar/Wind Harmer
1.104
970933AG2-581 GEN
Solar/Wind Harmer
9.288
961601AG1-000A GEN
Solar/Wind Harmer
3.804
316263AC1-034 GEN
Solar/Wind Harmer
4.494
3145493TOT1
Solar/Wind Harmer
0.141
3145453TOT5
Solar/Wind Harmer
0.085
3145603CNETO
Solar/Wind Harmer
0.057
970099AG2-077 GEN
Solar/Wind Harmer
11.121
939181AE1-148 GEN
Solar/Wind Harmer
4.902
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
313527AB2-043 GEN
Solar/Wind Harmer
1.368
3145933PARMELE
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.423
964791AG1-342 GEN
Solar/Wind Harmer
1.658
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
970323AG2-213 GEN
Solar/Wind Harmer
3.655
971775AH1-396 GEN
Solar/Wind Harmer
0.52
316034AC1-036 C
Solar/Wind Harmer
0.135
316065AD1-022 GEN
Solar/Wind Harmer
3.523
316222AC1-221 GEN
Solar/Wind Harmer
0.685
971741AH1-377 GEN
Solar/Wind Harmer
7.461
958211AF2-115 GEN
Solar/Wind Harmer
0.992
963191AG1-168 GEN
Solar/Wind Harmer
0.595
3144293JTRSVLE
Adder
0.18
3144293JTRSVLE
Adder
0.151
316240AF1-291 C
Solar/Wind Helper
0.715
3142946ENON
Solar/Wind Helper
0.023
316033AB2-134 GEN
Solar/Wind Helper
0.733
315697AD1-025 GEN
Solar/Wind Helper
2.437
966871AG1-558 GEN
Solar/Wind Helper
0.269
316075AC2-137 C
Solar/Wind Helper
0.27
316468AD1-105 GEN
Solar/Wind Helper
0.837
3143526WINTERP
Solar/Wind Helper
0.751
316077AC2-138 C
Solar/Wind Helper
0.108
316487AF1-042 GEN
Solar/Wind Helper
0.116
NYPJM->LTFIMP_NY
CLTF
0.476
LGEELTFEXP_LGEE->PJM
CLTF
0.565
LAGNLTFEXP_LAGN->PJM
CLTF
3.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.949
WECLTFEXP_WEC->PJM
CLTF
0.297
TVALTFEXP_TVA->PJM
CLTF
1.578
CPLELTFEXP_CPLE->PJM
CLTF
4.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.414
MECLTFEXP_MEC->PJM
CLTF
1.572
SIGELTFEXP_SIGE->PJM
CLTF
0.047

Details for 6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2002-2003_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2002-2003_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.75 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1213.06
MW Contribution:5.25
Bus #Bus NameTypeMW Contribution
3151361ROSEMG1
50/50
0.41
3151371ROSEMS1
50/50
0.254
3151381ROSEMG2
50/50
0.192
3144356SAPONY
Solar/Wind Harmer
0.955
316181AB2-040 GEN
Solar/Wind Harmer
1.863
3145796HORNRTN
Solar/Wind Harmer
-0.038
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.011
3145593CAROLNA
Solar/Wind Harmer
-0.011
966811AG1-552 GEN
Solar/Wind Harmer
1.239
3145593CAROLNA
Solar/Wind Harmer
0.092
3145783HORNRTN
Solar/Wind Harmer
1.285
3145783HORNRTN
Solar/Wind Harmer
1.028
3145783HORNRTN
Solar/Wind Harmer
0.321
3145783HORNRTN
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
1.06
972185AH1-677 GEN
Adder
5.166
972187AH1-678 GEN
Adder
2.584
316274AC1-208 GEN
Solar/Wind Harmer
1.058
970933AG2-581 GEN
Solar/Wind Harmer
9.183
961601AG1-000A GEN
Solar/Wind Harmer
3.686
316263AC1-034 GEN
Solar/Wind Harmer
4.351
3145493TOT1
Solar/Wind Harmer
0.136
3145453TOT5
Solar/Wind Harmer
0.082
3145603CNETO
Solar/Wind Harmer
0.054
970099AG2-077 GEN
Solar/Wind Harmer
10.98
939181AE1-148 GEN
Solar/Wind Harmer
4.79
313527AB2-043 GEN
Solar/Wind Harmer
1.342
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
962561AG1-105 GEN
Solar/Wind Harmer
4.343
964791AG1-342 GEN
Solar/Wind Harmer
1.628
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.207
3145893MURPHYS
Solar/Wind Harmer
-0.013
970323AG2-213 GEN
Solar/Wind Harmer
3.59
971775AH1-396 GEN
Solar/Wind Harmer
0.511
316034AC1-036 C
Solar/Wind Harmer
0.133
315779AE2-040
50/50
3.401
316315AB2-025 C
Solar/Wind Harmer
0.739
315814AE2-033 C
Solar/Wind Harmer
25.048
946281AF1-292 GEN
Solar/Wind Harmer
0.346
316087AB2-174 GEN
Solar/Wind Harmer
1.995
3151391GASTONA
50/50
0.321
3151411GASTONB
50/50
0.321
316365GEN2_N
Solar/Wind Harmer
1.225
966621AG1-532 GEN
Solar/Wind Harmer
0.313
313506AB2-031 GEN
Solar/Wind Harmer
1.073
3147043LAWRENC
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
315724AD1-057 GEN
Solar/Wind Harmer
0.628
970917AG2-570 GEN
Solar/Wind Harmer
24.537
316327AA2-057 GEN
Solar/Wind Harmer
0.959
316210AC1-098 GEN
Solar/Wind Harmer
1.474
961601AG1-000A GEN
Solar/Wind Harmer
3.733
3146233WITAKRS
Solar/Wind Harmer
0.196
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3146263WOODLND
Solar/Wind Harmer
-0.009
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.402
3145823KELFORD
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
0.727
316486AD2-202 GEN
Solar/Wind Harmer
0.213
316131AB2-060 GEN
Solar/Wind Harmer
0.883
316463AE2-346 GEN
Solar/Wind Harmer
0.128
316140AB2-099
Solar/Wind Harmer
0.053
962331AG1-082 GEN
Solar/Wind Harmer
0.989
964241AG1-285 GEN
Solar/Wind Harmer
6.156
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.026
957521AF2-046 GEN
Solar/Wind Harmer
5.914
961681AG1-008 GEN
Solar/Wind Harmer
5.914
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.935
3145893MURPHYS
Solar/Wind Harmer
0.052
3145893MURPHYS
Solar/Wind Harmer
-0.007
315785AD2-033 C
Solar/Wind Harmer
1.671
970257AG2-171 GEN
Solar/Wind Harmer
2.693
316248AF1-058 C
Solar/Wind Harmer
0.216
960061AF2-297 GEN
Solar/Wind Harmer
3.582
959311AF2-222 GEN
Solar/Wind Harmer
7.351
3145963POPLR C
Solar/Wind Harmer
-0.007
3156081AA2-088 GEN
Solar/Wind Harmer
2.211
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.623
971683AH1-343 GEN
Solar/Wind Harmer
2.764
315839AE2-212 C
Solar/Wind Helper
1.117
3142946ENON
Solar/Wind Helper
0.074
316473AC1-191 GEN
Solar/Wind Helper
1.195
316280AD1-041 GEN
Solar/Wind Helper
0.415
316404AE1-155 C
Solar/Wind Helper
0.954
316484AD2-074 GEN
Solar/Wind Helper
0.218
316156AD2-030 GEN
Solar/Wind Helper
0.17
3151391GASTONA
50/50
0.321
3151411GASTONB
50/50
0.321
3147043LAWRENC
50/50
1.133
316023GEN1_S
Solar/Wind Harmer
1.225
960081AF2-299 GEN
Solar/Wind Harmer
1.737
971795AH1-408 GEN
Solar/Wind Harmer
10.457
316011AB1-132 GEN
Solar/Wind Harmer
2.793
962571AG1-106 GEN
Solar/Wind Harmer
1.919
3145796HORNRTN
Solar/Wind Harmer
-0.042
3145796HORNRTN
Solar/Wind Harmer
-0.013
315722AD1-056 GEN
Solar/Wind Harmer
1.141
3145783HORNRTN
Solar/Wind Harmer
-0.011
316190AA2-174 GEN
Solar/Wind Harmer
0.129
970919AG2-571 GEN
Solar/Wind Harmer
3.106
970087AG2-069 GEN
Solar/Wind Harmer
9.162
940641AE2-051 GEN
Solar/Wind Harmer
9.147
316129AC1-054 GEN
Solar/Wind Harmer
0.826
316212AC1-099_GEN
Solar/Wind Harmer
0.819
3146233WITAKRS
Solar/Wind Harmer
-0.037
316359AB2-059 GEN
Solar/Wind Harmer
1.251
316049AB1-081 GEN
Solar/Wind Harmer
1.001
971065AG2-659 GEN
Solar/Wind Harmer
4.641
3142053HEARTS
Solar/Wind Harmer
0.109
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.009
961671AG1-007 GEN
Solar/Wind Harmer
0.111
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.261
957481AF2-042 GEN
Solar/Wind Harmer
27.45
3145823KELFORD
Solar/Wind Harmer
-0.009
316494AC1-189 GEN
Solar/Wind Harmer
0.897
316237AB2-079_GEN
Solar/Wind Harmer
0.248
315693AD1-088 GEN
Solar/Wind Harmer
4.091
3145683EARLEYS
Solar/Wind Harmer
-0.008
962491AG1-098 GEN
Solar/Wind Harmer
5.389
939411AE1-173 GEN
Solar/Wind Harmer
39.812
315687AD1-152 GEN
Solar/Wind Harmer
0.957
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970401AG2-262 GEN
Solar/Wind Harmer
0.498
3146293MARTNCO
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145893MURPHYS
Solar/Wind Harmer
0.22
316174AB2-169 GEN
Solar/Wind Harmer
1.073
3145963POPLR C
Solar/Wind Harmer
-0.007
316003AC1-222 GEN
Solar/Wind Harmer
0.66
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.676
970685AG2-442 GEN
Solar/Wind Harmer
5.862
3142543TWELFTH
Solar/Wind Helper
0.031
316458AB2-190 GEN2
Solar/Wind Helper
1.536
316381AD1-082 GEN
Solar/Wind Helper
1.166
3142433PROV 92
Solar/Wind Helper
0.862
3142416OLDCHRC
Solar/Wind Helper
0.45
3142416OLDCHRC
Solar/Wind Helper
0.172
3143526WINTERP
Solar/Wind Helper
0.731
3141766HARMONY
Solar/Wind Helper
0.024
964211AG1-282 GEN
Solar/Wind Helper
0.157
3141726DUNNSVL
Solar/Wind Helper
0.465
3138133OCRAN
Solar/Wind Helper
0.068
315652AC1-086 GEN
Solar/Wind Harmer
15.018
3145796HORNRTN
Solar/Wind Harmer
-0.041
3145796HORNRTN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.048
941031AE2-094 GEN
Solar/Wind Harmer
20.02
944011AF1-069 GEN
Solar/Wind Harmer
6.273
970673AG2-436 GEN
Solar/Wind Harmer
21.964
970673AG2-436 GEN
Solar/Wind Harmer
11.121
971967AH1-528 GEN
Solar/Wind Harmer
19.187
970085AG2-068 GEN
Solar/Wind Harmer
6.108
970581AG2-369 GEN
Solar/Wind Harmer
5.253
970831AG2-522 GEN
Solar/Wind Harmer
4.789
315607AA1-063A GEN
Solar/Wind Harmer
0.957
316319Z2-044 C
Solar/Wind Harmer
0.518
3146043SEABORD
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.036
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316420AA1-050 GEN
Solar/Wind Harmer
0.982
957861AF2-080 GEN
Solar/Wind Harmer
3.647
316239AB2-077_GEN
Solar/Wind Harmer
0.248
316238AB2-078_GEN
Solar/Wind Harmer
0.248
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.069
961941AG1-037 GEN
Solar/Wind Harmer
0.059
316222AC1-221 GEN
Solar/Wind Harmer
0.672
316065AD1-022 GEN
Solar/Wind Harmer
3.235
971741AH1-377 GEN
Solar/Wind Harmer
7.368
3142946ENON
Solar/Wind Helper
0.022
316033AB2-134 GEN
Solar/Wind Helper
0.712
315697AD1-025 GEN
Solar/Wind Helper
2.367
966871AG1-558 GEN
Solar/Wind Helper
0.264
316075AC2-137 C
Solar/Wind Helper
0.264
316468AD1-105 GEN
Solar/Wind Helper
0.819
3143526WINTERP
Solar/Wind Helper
0.731
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.114
3145513AHOSKIE
Solar/Wind Harmer
-0.008
316005AA1-067
Solar/Wind Harmer
0.158
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.022
316318V4-068
Solar/Wind Harmer
0.185
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
316118AC1-105 GEN
Solar/Wind Harmer
0.508
971443AH1-215 GEN
Solar/Wind Harmer
1.422
3144303KENBRDG
Solar/Wind Harmer
-0.006
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.004
965291AG1-394 GEN
Solar/Wind Harmer
0.631
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.933
970683AG2-441 GEN
Solar/Wind Harmer
5.234
970681AG2-440 GEN
Solar/Wind Harmer
4.187
316132AB2-190 GEN1
Solar/Wind Helper
1.536
316369SG1_INVT
Solar/Wind Helper
0.996
316312AB1-027
Solar/Wind Helper
0.329
3143873LANEXA
Solar/Wind Helper
0.095
316233AE1-074 FULL
Solar/Wind Helper
0.215
315662AE1-191 GEN
Solar/Wind Helper
0.665
315666AE1-190 GEN
Solar/Wind Helper
0.166
316059AD1-063 C
Solar/Wind Helper
0.121
3141813NORNECK
Solar/Wind Helper
0.113
3141783LANCAST
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.045
3138133OCRAN
Solar/Wind Helper
0.034
3141913WHIT STONE
Solar/Wind Helper
0.113
957601AF2-054 GEN
Solar/Wind Helper
0.151
3141873WAN 176
Solar/Wind Helper
0.023
NYPJM->LTFIMP_NY
CLTF
0.462
LGEELTFEXP_LGEE->PJM
CLTF
0.556
LAGNLTFEXP_LAGN->PJM
CLTF
3.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.739
WECLTFEXP_WEC->PJM
CLTF
0.292
TVALTFEXP_TVA->PJM
CLTF
1.548
CPLELTFEXP_CPLE->PJM
CLTF
4.585
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.511
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.387
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.312
MECLTFEXP_MEC->PJM
CLTF
1.545
SIGELTFEXP_SIGE->PJM
CLTF
0.046

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.61 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2077.46
MW Contribution:4.53
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.027
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.247
3150331BIRCHWDA
Adder
16.693
3141316ARNOLDS
Adder
0.23
316044AC1-158 PL1
Solar/Wind Harmer
1.043
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.732
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.569
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.381
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
316045AC1-158 PL2
Solar/Wind Harmer
3.338
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.642
3151751LOISA D
Adder
5.598
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.692
3150371LDYSMT1
Adder
12.264
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.11
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.412
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.015
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
3141766HARMONY
Solar/Wind Harmer
0.847
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.196
944601AF1-125 GEN
Solar/Wind Harmer
40.553
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.766
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233940AF2-379 C
Solar/Wind Helper
0.037
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
3150381LDYSMT2
Adder
12.185
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
316059AD1-063 C
Solar/Wind Harmer
0.215
957601AF2-054 GEN
Solar/Wind Harmer
0.285
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.483
944011AF1-069 GEN
Solar/Wind Harmer
5.165
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.299
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.981
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.843
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.581
3150181POSSMC2
Adder
1.094
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
316447AC1-158 HLD
Solar/Wind Harmer
2.295
3150391LDYSMT3
Adder
12.669
972195AH1-682 GEN
Adder
1.665
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.8
957411AF2-035 GEN
Solar/Wind Harmer
4.619
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.598
3151721LOISA A
Adder
5.569
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
WECLTFEXP_WEC->PJM
CLTF
0.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
TVALTFEXP_TVA->PJM
CLTF
3.187
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.6 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2077.39
MW Contribution:4.53
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150331BIRCHWDA
Adder
16.699
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.246
3141316ARNOLDS
Adder
0.23
3150401LDYSMT4
Adder
12.694
3150371LDYSMT1
Adder
12.265
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.111
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.411
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.013
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
3141766HARMONY
Solar/Wind Harmer
0.847
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
970053AG2-049 GEN
50/50
2.028
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.733
3150381LDYSMT2
Adder
12.186
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
957601AF2-054 GEN
Solar/Wind Harmer
0.285
316059AD1-063 C
Solar/Wind Harmer
0.215
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.482
944011AF1-069 GEN
Solar/Wind Harmer
5.164
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.298
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.574
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.38
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.643
3151751LOISA D
Adder
5.597
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.98
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.842
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.195
944601AF1-125 GEN
Solar/Wind Harmer
40.552
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.765
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.613
3150181POSSMC2
Adder
1.095
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
3150391LDYSMT3
Adder
12.67
972195AH1-682 GEN
Adder
1.665
316447AC1-158 HLD
Solar/Wind Harmer
2.294
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.801
957411AF2-035 GEN
Solar/Wind Harmer
4.62
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.597
3151721LOISA A
Adder
5.568
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
316316AC1-027 C
Solar/Wind Harmer
0.278
3142956BIRDNECK
Solar/Wind Harmer
0.486
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
NYPJM->LTFIMP_NY
CLTF
2.575
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
TVALTFEXP_TVA->PJM
CLTF
3.187
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:145.68 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:2064.29
MW Contribution:4.5
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.897
3152121X4-039 GT2
50/50
1.836
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.401
3150151POSSMC1
Adder
1.063
3141346CRANES
Adder
0.118
3150221REMNGT2
Adder
12.484
3150211REMNGT1
Adder
12.401
972201AH1-685 GEN
Adder
2.154
3150281M RUN A
Adder
13.376
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.962
316045AC1-158 PL2
Solar/Wind Harmer
3.331
972197AH1-683 GEN
Adder
1.961
972219AH1-694 GEN
Adder
1.412
316254AC1-120 GEN1
Solar/Wind Harmer
0.848
957971AF2-091 GEN
Solar/Wind Harmer
1.025
315683AE1-153 C
Solar/Wind Harmer
9.493
972135AH1-637 GEN
Solar/Wind Harmer
1.018
966881AG1-559 GEN
Solar/Wind Harmer
0.105
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.181
316337AD2-073 GEN
Solar/Wind Harmer
0.265
3150351NORNECKC2
Adder
0.862
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3141726DUNNSVL
Solar/Wind Harmer
-0.039
3151751LOISA D
Adder
5.583
962861AG1-135 GEN
Solar/Wind Harmer
3.609
961951AG1-038 GEN
Solar/Wind Harmer
1.263
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.109
3141843SHACKLE
Adder
0.429
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143526WINTERP
Solar/Wind Harmer
-0.048
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.383
944631AF1-128 GEN
Adder
39.551
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.248
971317AH1-138 GEN
Solar/Wind Harmer
1.154
970129AG2-093 GEN
Solar/Wind Harmer
2.097
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
315671AE2-027_GEN
Solar/Wind Harmer
6.892
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.451
971647AH1-324 GEN
Solar/Wind Harmer
4.571
961611AG1-000B GEN
Solar/Wind Harmer
4.503
3151171GRAVELC
Adder
0.862
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.927
970659AG2-427 GEN
Solar/Wind Harmer
4.796
316381AD1-082 GEN
Solar/Wind Harmer
0.827
316375AC2-012 GEN
Solar/Wind Harmer
3.114
3150981CHESPKA
Adder
1
970661AG2-428 GEN
Solar/Wind Harmer
9.562
944591AF1-124 GEN
Solar/Wind Harmer
41.052
316072AD1-144
Solar/Wind Harmer
0.182
316388AE2-253 GEN
Solar/Wind Harmer
0.603
939411AE1-173 GEN
Solar/Wind Harmer
44.674
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.181
940641AE2-051 GEN
Solar/Wind Harmer
8.364
316093AE2-104_GEN
Solar/Wind Harmer
2.589
3143336POWHATN
Solar/Wind Harmer
1.052
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.521
315800Z1-036_GEN1
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.02
970937AG2-583 GEN
Solar/Wind Harmer
6.075
316023GEN1_S
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.101
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.655
970087AG2-069 GEN
Solar/Wind Harmer
7.848
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.934
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
25.866
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.66
3144293JTRSVLE
Adder
0.228
972277AH1-723 GEN
Adder
42.597
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.396
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.22
235062AE1-101 C1
Solar/Wind Helper
1.061
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.229
233915AB1-141 GEN
Solar/Wind Helper
0.302
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.202
233998TM1NIN_3.36
Solar/Wind Helper
0.156
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.303
233950AC2-186 GEN
Solar/Wind Helper
0.069
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.18
205941AD2-115 GEN
Solar/Wind Helper
0.301
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.897
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.236
212507AE2-042_GEN
Solar/Wind Helper
0.826
946731AF1-337 GEN
Solar/Wind Helper
0.232
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.364
3152111X4-039 GT1
50/50
1.841
315747AE2-019 GEN
50/50
13.211
963691AG1-221 GEN
Solar/Wind Harmer
2.318
971455AH1-223 GEN
Solar/Wind Harmer
2.318
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150151POSSMC1
Adder
1.063
3150151POSSMC1
Adder
1.063
3150231REMNGT3
Adder
13.478
3150241REMNGT4
Adder
12.566
972199AH1-684 GEN
Adder
1.905
972217AH1-693 GEN
Adder
1.657
3150301M RUN C
Adder
13.368
3150291M RUN B
Adder
13.268
3150331BIRCHWDA
Adder
16.45
3141316ARNOLDS
Adder
0.227
316044AC1-158 PL1
Solar/Wind Harmer
1.041
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.557
3150371LDYSMT1
Adder
12.133
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.306
970737AG2-469 GEN
Solar/Wind Harmer
5.052
3132273ORANGE
Solar/Wind Harmer
-0.002
3141906WESTMOR
Solar/Wind Harmer
-0.004
971781AH1-399 GEN
Solar/Wind Harmer
0.614
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.877
3151761LOISA E
Adder
11.381
972183AH1-676 GEN
Adder
91.775
316404AE1-155 C
Solar/Wind Harmer
1.859
316484AD2-074 GEN
Solar/Wind Harmer
2.414
970009AG2-005 GEN
Solar/Wind Harmer
1.199
316473AC1-191 GEN
Solar/Wind Harmer
1.031
962971AG1-146 GEN
Solar/Wind Harmer
1.793
3142416OLDCHRC
Solar/Wind Harmer
0.953
3141766HARMONY
Solar/Wind Harmer
0.84
316156AD2-030 GEN
Solar/Wind Harmer
0.252
3141873WAN 176
Solar/Wind Harmer
1.12
316280AD1-041 GEN
Solar/Wind Harmer
0.711
316203AE2-005 GEN
Solar/Wind Harmer
3.975
3141843SHACKLE
Adder
0.429
970293AG2-193 GEN
Solar/Wind Harmer
1.175
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143096IRON208
Adder
0.342
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.383
316382AG1-145 C
Solar/Wind Harmer
0.279
970133AG2-095 GEN
Solar/Wind Harmer
1.038
970129AG2-093 GEN
Solar/Wind Harmer
5.177
3150921YORKTN3
Adder
2.053
315778AD1-151 GEN
Solar/Wind Harmer
7.946
965281AG1-393 GEN
Solar/Wind Harmer
1.147
3144216WINCHST
Adder
0.308
315839AE2-212 C
Solar/Wind Harmer
0.276
961611AG1-000B GEN
Solar/Wind Harmer
1.921
3151221GRAVEL6
Adder
5.89
3151171GRAVELC
Adder
1.133
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.666
315773AC2-141 GEN
Solar/Wind Harmer
3.785
970659AG2-427 GEN
Solar/Wind Harmer
0.85
316083AB2-161 GEN
Solar/Wind Harmer
1.464
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.435
970661AG2-428 GEN
Solar/Wind Harmer
1.695
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
40.904
944601AF1-125 GEN
Solar/Wind Harmer
40.266
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.089
316320Y1-086
Solar/Wind Harmer
0.52
316313AB2-026
Solar/Wind Harmer
0.239
316258AE1-075 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.227
3143336POWHATN
Solar/Wind Harmer
0.895
316435W1029_GEN3
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.923
971157AH1-035 GEN
Solar/Wind Harmer
1.059
3156081AA2-088 GEN
Solar/Wind Harmer
2.747
315737AD1-076 GEN
Solar/Wind Harmer
1.607
316365GEN2_N
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
20.974
957521AF2-046 GEN
Solar/Wind Harmer
6.6
961681AG1-008 GEN
Solar/Wind Harmer
6.6
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.123
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.04
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.663
3144293JTRSVLE
Adder
0.228
972255AH1-712 GEN
Adder
36.554
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.489
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.396
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.311
233982AB2-133 GEN
Solar/Wind Helper
0.215
233918AB1-142 GEN
Solar/Wind Helper
0.302
233994AC2-023 GEN
Solar/Wind Helper
0.575
233996TM1833_GEN
Solar/Wind Helper
0.156
233997TMININ_4.2
Solar/Wind Helper
0.156
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.303
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.213
230430AE1-229_GEN
Solar/Wind Helper
1.988
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.241
963071AG1-156 GEN
Solar/Wind Helper
0.78
209027LOR2_Q27
Solar/Wind Helper
0.555
961331AF2-424 GEN
Solar/Wind Helper
0.236
961421AF2-433 GEN
Solar/Wind Helper
0.235
957921AF2-086 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.232
946741AF1-338 GEN
Solar/Wind Helper
0.232
209067AE2-060 GEN
Solar/Wind Helper
0.042
970053AG2-049 GEN
50/50
2.02
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.104
316415AF1-147_GEN2
Solar/Wind Harmer
1.104
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
12.596
3150381LDYSMT2
Adder
12.055
972213AH1-691 GEN
Adder
2.039
972215AH1-692 GEN
Adder
2.039
316164AC1-076 GEN
Solar/Wind Harmer
0.886
944491AF1-114 GEN
Solar/Wind Harmer
3.014
316223AC1-118
Solar/Wind Harmer
0.269
972189AH1-679 GEN
Adder
1.455
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.183
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316312AB1-027
Solar/Wind Harmer
0.319
316314AB2-024 C
Solar/Wind Harmer
0.807
316059AD1-063 C
Solar/Wind Harmer
0.213
957601AF2-054 GEN
Solar/Wind Harmer
0.282
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.137
315666AE1-190 GEN
Solar/Wind Harmer
0.284
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
971167AH1-042 GEN
Solar/Wind Harmer
9.035
315976AC1-164 GENA
Solar/Wind Harmer
9.907
316169AC1-164_GENC
Solar/Wind Harmer
8.558
315975AC1-164 GENB
Solar/Wind Harmer
0.293
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971281AH1-106 GEN
Solar/Wind Harmer
1.517
971283AH1-107 GEN
Solar/Wind Harmer
1.517
971285AH1-108 GEN
Adder
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.28
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
316369SG1_INVT
Solar/Wind Harmer
1.636
972265AH1-717 GEN
Adder
6.291
3151201GRAVEL4
Adder
5.897
3151191GRAVEL3
Adder
5.822
3151211GRAVEL5
Adder
5.822
971445AH1-216 GEN
Solar/Wind Harmer
5.611
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.342
3151091ELIZAR2
Adder
7.214
3152611GOSPORTB
Adder
1.02
3152621GOSPORTC
Adder
0.866
3152601GOSPORTA
Adder
0.798
315833AF1-017_GEN
Solar/Wind Harmer
1.7
316349AD2-085 GEN
Solar/Wind Harmer
0.796
316311AC2-079 GEN
Solar/Wind Harmer
4.513
957871AF2-081 GEN
Solar/Wind Harmer
4.471
319010AE1-072 C
Solar/Wind Harmer
1.806
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.113
313526AB2-022
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.239
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.163
316315AB2-025 C
Solar/Wind Harmer
0.237
315814AE2-033 C
Solar/Wind Harmer
8.149
941031AE2-094 GEN
Solar/Wind Harmer
16.374
944011AF1-069 GEN
Solar/Wind Harmer
5.131
315611Z1-036_GEN2
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.179
970673AG2-436 GEN
Solar/Wind Harmer
9.205
971967AH1-528 GEN
Solar/Wind Harmer
16.189
315816AE2-034 GEN
Solar/Wind Harmer
0.692
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.71
315733AD1-074 GEN2
Solar/Wind Harmer
1.71
315735AD1-075 GEN1
Solar/Wind Harmer
0.855
965291AG1-394 GEN
Solar/Wind Harmer
0.749
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.676
316318V4-068
Solar/Wind Harmer
0.209
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.232
970581AG2-369 GEN
Solar/Wind Harmer
4.499
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.837
316087AB2-174 GEN
Solar/Wind Harmer
1.179
972205AH1-687 GEN
Adder
3.118
972193AH1-681 GEN
Adder
1.633
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.386
205956AE1-196_GEN
Solar/Wind Helper
0.384
205932AD2-116_GEN
Solar/Wind Helper
0.384
959381AF2-229 GEN
Solar/Wind Helper
0.256
237085AD2-009_GEN
Solar/Wind Helper
0.968
203975AE1-071-GEN
Solar/Wind Helper
1.709
233935AB2-179 C
Solar/Wind Helper
0.769
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.573
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.196
964001AG1-254 GEN
Solar/Wind Helper
0.564
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.001
961261AF2-417 GEN
Solar/Wind Helper
0.24
959431AF2-234 GEN
Solar/Wind Helper
0.464
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.232
238208AF1-136 C
Solar/Wind Helper
0.089
972289AH1-729 GEN
50/50
13.276
3150071POSSM 5
Adder
48.607
3150181POSSMC2
Adder
1.072
3150181POSSMC2
Adder
1.063
3150181POSSMC2
Adder
1.063
316447AC1-158 HLD
Solar/Wind Harmer
2.29
315651AD1-115 GEN
Solar/Wind Harmer
4.658
3150391LDYSMT3
Adder
12.533
972195AH1-682 GEN
Adder
1.647
315673AE1-157 GEN
Solar/Wind Harmer
7.721
957411AF2-035 GEN
Solar/Wind Harmer
4.574
970317AG2-208 GEN
Solar/Wind Harmer
4.447
316468AD1-105 GEN
Solar/Wind Harmer
1.109
966001AG1-469 GEN
Solar/Wind Harmer
0.184
316077AC2-138 C
Solar/Wind Harmer
0.205
3150341NORNECKC1
Adder
0.906
3150341NORNECKC1
Adder
0.898
3151731LOISA B
Adder
5.583
3151721LOISA A
Adder
5.554
958261AF2-120 GEN
Solar/Wind Harmer
3.734
316487AF1-042 GEN
Solar/Wind Harmer
1.263
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.269
316441AF1-014 GEN
Solar/Wind Harmer
0.636
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.022
3150701DARBY 4
Adder
6.008
3150681DARBY 2
Adder
6.001
3150671DARBY 1
Adder
5.994
316075AC2-137 C
Solar/Wind Harmer
0.253
3143526WINTERP
Solar/Wind Harmer
-0.048
3142946ENON
Solar/Wind Harmer
-0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.164
944641AF1-129 GEN
Adder
39.124
316240AF1-291 C
Solar/Wind Harmer
0.277
316033AB2-134 GEN
Solar/Wind Harmer
2.953
315697AD1-025 GEN
Solar/Wind Harmer
1.852
316236AE1-162_GEN
Solar/Wind Harmer
0.273
970657AG2-426 GEN
Solar/Wind Harmer
2.816
970657AG2-426 GEN
Solar/Wind Harmer
0.589
316036AC1-147 C
Solar/Wind Harmer
0.243
3150991CHESPKB
Adder
0.839
3150991CHESPKB
Adder
0.819
3142956BIRDNECK
Solar/Wind Harmer
0.482
316316AC1-027 C
Solar/Wind Harmer
0.276
316185AD1-033 GEN
Solar/Wind Harmer
0.947
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.603
316018AA1-139 ULT2
Solar/Wind Harmer
0.766
316017AA1-139 ULT1
Solar/Wind Harmer
0.724
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3146456SLIGO L269
Solar/Wind Harmer
1.055
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.599
316433W1029_GEN2
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.306
315742AE1-103 GEN
Solar/Wind Harmer
0.91
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
972185AH1-677 GEN
Adder
4.302
972187AH1-678 GEN
Adder
2.17
970933AG2-581 GEN
Solar/Wind Harmer
7.988
316065AD1-022 GEN
Solar/Wind Harmer
4.211
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.347
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3144293JTRSVLE
Adder
0.228
3144293JTRSVLE
Adder
0.192
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.204
205916AD1-020 GEN
Solar/Wind Helper
1.477
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.306
237002AB1-128_GEN
Solar/Wind Helper
0.297
235063AE1-101 C2
Solar/Wind Helper
1.061
20390526W1-045 C
Solar/Wind Helper
0.251
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.354
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.402
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.34
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.303
232410W1-006 C
Solar/Wind Helper
0.303
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.177
961431AF2-434 GEN
Solar/Wind Helper
0.235
209029WAYMART-WD
Solar/Wind Helper
0.441
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.232
209137AF2-361 C
Solar/Wind Helper
0.706
NYPJM->LTFIMP_NY
CLTF
2.566
LGEELTFEXP_LGEE->PJM
CLTF
1.801
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
WECLTFEXP_WEC->PJM
CLTF
0.96
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.503
TVALTFEXP_TVA->PJM
CLTF
3.177
CPLELTFEXP_CPLE->PJM
CLTF
5.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.853
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.556
MECLTFEXP_MEC->PJM
CLTF
4.438
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:140.29 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1987.89
MW Contribution:3.6
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
2.877
3152121X4-039 GT2
50/50
1.823
3150221REMNGT2
Adder
10.939
3150211REMNGT1
Adder
10.866
972201AH1-685 GEN
Adder
1.887
3150281M RUN A
Adder
11.705
316006AB2-029 C
Solar/Wind Harmer
0.549
971685AH1-345 GEN
Solar/Wind Harmer
0.837
3140676OCCOQUN
Adder
0.203
316254AC1-120 GEN1
Solar/Wind Harmer
0.712
316045AC1-158 PL2
Solar/Wind Harmer
2.734
315683AE1-153 C
Solar/Wind Harmer
8.082
3147666LOUISA
Solar/Wind Harmer
-0.032
316192AB2-158 GEN
Solar/Wind Harmer
0.961
3151751LOISA D
Adder
4.652
972223AH1-696 GEN
Adder
5.63
3150151POSSMC1
Adder
0.713
3141346CRANES
Adder
0.082
972197AH1-683 GEN
Adder
1.435
972219AH1-694 GEN
Adder
1.033
966881AG1-559 GEN
Solar/Wind Harmer
0.078
957971AF2-091 GEN
Solar/Wind Harmer
0.75
972135AH1-637 GEN
Solar/Wind Harmer
0.75
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3150351NORNECKC2
Adder
0.651
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.741
961951AG1-038 GEN
Solar/Wind Harmer
0.961
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3150851SPRUNCC
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.852
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
30.629
316159AE1-175 C
Solar/Wind Harmer
0.193
971317AH1-138 GEN
Solar/Wind Harmer
0.895
315671AE2-027_GEN
Solar/Wind Harmer
5.367
970129AG2-093 GEN
Solar/Wind Harmer
1.632
316458AB2-190 GEN2
Solar/Wind Harmer
0.724
971069AG2-661 GEN
Solar/Wind Harmer
1.13
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.563
961611AG1-000B GEN
Solar/Wind Harmer
3.512
3151171GRAVELC
Adder
0.673
3143336POWHATN
Solar/Wind Harmer
0.841
3145336SMITFLD
Solar/Wind Harmer
-0.028
316294AC1-161 GEN
Solar/Wind Harmer
2.291
970659AG2-427 GEN
Solar/Wind Harmer
3.755
316381AD1-082 GEN
Solar/Wind Harmer
0.648
316375AC2-012 GEN
Solar/Wind Harmer
2.44
3150981CHESPKA
Adder
0.784
944591AF1-124 GEN
Solar/Wind Harmer
32.182
970661AG2-428 GEN
Solar/Wind Harmer
7.492
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.173
940641AE2-051 GEN
Solar/Wind Harmer
6.594
316336AC2-165 C
Solar/Wind Harmer
1.222
316388AE2-253 GEN
Solar/Wind Harmer
0.474
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.142
316093AE2-104_GEN
Solar/Wind Harmer
2.034
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.702
970937AG2-583 GEN
Solar/Wind Harmer
4.952
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.359
972003AH1-546 GEN
Solar/Wind Harmer
3.372
316322AB2-045
Solar/Wind Harmer
0.226
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.123
316023GEN1_S
Solar/Wind Harmer
0.452
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.673
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
35.15
3147043LAWRENC
Adder
0.53
3144293JTRSVLE
Adder
0.186
23779801AA1-109
Solar/Wind Helper
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.385
966131AG1-482 GEN
Solar/Wind Helper
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.242
3152111X4-039 GT1
50/50
1.829
315747AE2-019 GEN
50/50
12.54
963691AG1-221 GEN
Solar/Wind Harmer
2.26
971455AH1-223 GEN
Solar/Wind Harmer
2.26
3141196NOKESVL
Solar/Wind Harmer
-0.043
3150231REMNGT3
Adder
11.81
3150241REMNGT4
Adder
11.012
972199AH1-684 GEN
Adder
1.67
972217AH1-693 GEN
Adder
1.452
3150301M RUN C
Adder
11.698
3150291M RUN B
Adder
11.611
316170AC1-121 GEN2
Solar/Wind Harmer
0.237
316044AC1-158 PL1
Solar/Wind Harmer
0.855
316450AC1-158 RIC
Solar/Wind Harmer
0.228
3132273ORANGE
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Harmer
-0.018
3151761LOISA E
Adder
9.484
972183AH1-676 GEN
Adder
76.571
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.076
316415AF1-147_GEN2
Solar/Wind Harmer
1.076
970053AG2-049 GEN
Adder
1.475
316164AC1-076 GEN
Solar/Wind Harmer
0.73
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.22
3150381LDYSMT2
Adder
8.824
972213AH1-691 GEN
Adder
1.493
972215AH1-692 GEN
Adder
1.493
944491AF1-114 GEN
Solar/Wind Harmer
2.206
316223AC1-118
Solar/Wind Harmer
0.2
972189AH1-679 GEN
Adder
1.104
3141813NORNECK
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
3.188
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
1.184
971283AH1-107 GEN
Solar/Wind Harmer
1.184
316312AB1-027
Solar/Wind Harmer
0.245
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316314AB2-024 C
Solar/Wind Harmer
0.62
316059AD1-063 C
Solar/Wind Harmer
0.164
3143873LANEXA
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.873
315666AE1-190 GEN
Solar/Wind Harmer
0.218
957601AF2-054 GEN
Solar/Wind Harmer
0.217
3141873WAN 176
Solar/Wind Harmer
-0.001
315976AC1-164 GENA
Solar/Wind Harmer
7.645
316169AC1-164_GENC
Solar/Wind Harmer
6.604
315975AC1-164 GENB
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
971167AH1-042 GEN
Solar/Wind Harmer
6.965
957831AF2-077 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.724
316369SG1_INVT
Solar/Wind Harmer
1.275
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.603
3151191GRAVEL3
Adder
4.545
3151211GRAVEL5
Adder
4.545
3143316POE
Solar/Wind Harmer
-0.028
971445AH1-216 GEN
Solar/Wind Harmer
4.385
3151081ELIZAR1
Adder
5.753
3151091ELIZAR2
Adder
5.653
3152611GOSPORTB
Adder
0.799
3152621GOSPORTC
Adder
0.678
3152601GOSPORTA
Adder
0.626
315833AF1-017_GEN
Solar/Wind Harmer
1.334
316349AD2-085 GEN
Solar/Wind Harmer
0.624
316311AC2-079 GEN
Solar/Wind Harmer
3.541
957871AF2-081 GEN
Solar/Wind Harmer
3.509
319010AE1-072 C
Solar/Wind Harmer
1.418
316305AF2-043 C
Solar/Wind Harmer
0.211
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
0.874
313526AB2-022
Solar/Wind Harmer
0.188
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.188
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.128
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
12.98
944011AF1-069 GEN
Solar/Wind Harmer
4.067
315814AE2-033 C
Solar/Wind Harmer
6.44
315611Z1-036_GEN2
Solar/Wind Harmer
1.702
970673AG2-436 GEN
Solar/Wind Harmer
14.439
970673AG2-436 GEN
Solar/Wind Harmer
7.311
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.878
315816AE2-034 GEN
Solar/Wind Harmer
0.549
972205AH1-687 GEN
Adder
2.574
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.359
315733AD1-074 GEN2
Solar/Wind Harmer
1.359
315735AD1-075 GEN1
Solar/Wind Harmer
0.68
971845AH1-439 GEN
Solar/Wind Harmer
3.571
965291AG1-394 GEN
Solar/Wind Harmer
0.596
970285AG2-188 GEN
Solar/Wind Harmer
5.876
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.928
316318V4-068
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.348
960921AF2-383 GEN
Solar/Wind Helper
0.147
959381AF2-229 GEN
Solar/Wind Helper
0.283
205943AE1-185 GEN
Solar/Wind Helper
0.409
205956AE1-196_GEN
Solar/Wind Helper
0.406
205932AD2-116_GEN
Solar/Wind Helper
0.406
237085AD2-009_GEN
Solar/Wind Helper
1.049
972289AH1-729 GEN
50/50
13.169
315651AD1-115 GEN
Solar/Wind Harmer
3.939
316447AC1-158 HLD
Solar/Wind Harmer
1.879
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.652
3151721LOISA A
Adder
4.628
3150071POSSM 5
Adder
32.578
3150181POSSMC2
Adder
0.719
3150181POSSMC2
Adder
0.713
3150181POSSMC2
Adder
0.713
3150391LDYSMT3
Adder
9.175
972195AH1-682 GEN
Adder
1.206
315673AE1-157 GEN
Solar/Wind Harmer
5.71
957411AF2-035 GEN
Solar/Wind Harmer
3.403
970317AG2-208 GEN
Solar/Wind Harmer
3.309
316468AD1-105 GEN
Solar/Wind Harmer
0.83
316077AC2-138 C
Solar/Wind Harmer
0.155
3150341NORNECKC1
Adder
0.684
3150341NORNECKC1
Adder
0.679
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
958261AF2-120 GEN
Solar/Wind Harmer
2.834
3142296MT RD221
Adder
0.207
316487AF1-042 GEN
Solar/Wind Harmer
0.961
971223AH1-071 GEN
Solar/Wind Harmer
0.912
3143526WINTERP
Solar/Wind Harmer
-0.038
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.65
3150701DARBY 4
Adder
4.64
3150681DARBY 2
Adder
4.634
3150671DARBY 1
Adder
4.629
316075AC2-137 C
Solar/Wind Harmer
0.196
316441AF1-014 GEN
Solar/Wind Harmer
0.488
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.436
316240AF1-291 C
Solar/Wind Harmer
0.216
316033AB2-134 GEN
Solar/Wind Harmer
2.301
315697AD1-025 GEN
Solar/Wind Harmer
1.443
316236AE1-162_GEN
Solar/Wind Harmer
0.214
970657AG2-426 GEN
Solar/Wind Harmer
2.206
970657AG2-426 GEN
Solar/Wind Harmer
0.461
316036AC1-147 C
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.657
3150991CHESPKB
Adder
0.642
3142956BIRDNECK
Solar/Wind Harmer
0.378
316316AC1-027 C
Solar/Wind Harmer
0.216
316185AD1-033 GEN
Solar/Wind Harmer
0.743
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.474
316018AA1-139 ULT2
Solar/Wind Harmer
0.601
316017AA1-139 ULT1
Solar/Wind Harmer
0.568
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.828
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
971761AH1-387 GEN
Solar/Wind Harmer
3.885
316431W1029_GEN1
Solar/Wind Harmer
1.259
316433W1029_GEN2
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.242
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.719
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.421
972187AH1-678 GEN
Adder
1.728
970933AG2-581 GEN
Solar/Wind Harmer
6.373
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.351
3145893MURPHYS
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
-0.012
970301AG2-198 GEN
Solar/Wind Harmer
3.335
971741AH1-377 GEN
Solar/Wind Harmer
7.747
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.186
3144293JTRSVLE
Adder
0.157
3150151POSSMC1
Adder
0.713
3150151POSSMC1
Adder
0.713
3150331BIRCHWDA
Adder
11.674
3150401LDYSMT4
Adder
9.192
3150371LDYSMT1
Adder
8.882
3141316ARNOLDS
Adder
0.162
966881AG1-559 GEN
Solar/Wind Harmer
0.227
970737AG2-469 GEN
Solar/Wind Harmer
3.736
971781AH1-399 GEN
Solar/Wind Harmer
0.459
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.662
316473AC1-191 GEN
Solar/Wind Harmer
0.788
316404AE1-155 C
Solar/Wind Harmer
1.411
316484AD2-074 GEN
Solar/Wind Harmer
1.837
970009AG2-005 GEN
Solar/Wind Harmer
0.912
962971AG1-146 GEN
Solar/Wind Harmer
1.366
3142416OLDCHRC
Solar/Wind Harmer
0.734
970293AG2-193 GEN
Solar/Wind Harmer
0.907
3150861SPRUNCD
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
0.645
316203AE2-005 GEN
Solar/Wind Harmer
3.054
316280AD1-041 GEN
Solar/Wind Harmer
0.546
316156AD2-030 GEN
Solar/Wind Harmer
0.193
3141873WAN 176
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.265
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
316382AG1-145 C
Solar/Wind Harmer
0.216
970133AG2-095 GEN
Solar/Wind Harmer
0.807
970129AG2-093 GEN
Solar/Wind Harmer
4.029
965281AG1-393 GEN
Solar/Wind Harmer
0.893
315778AD1-151 GEN
Solar/Wind Harmer
6.188
3150921YORKTN3
Adder
1.597
315839AE2-212 C
Solar/Wind Harmer
0.215
3144216WINCHST
Adder
0.239
961611AG1-000B GEN
Solar/Wind Harmer
1.499
3151221GRAVEL6
Adder
4.598
3151171GRAVELC
Adder
0.885
315813AE1-149 C
Solar/Wind Harmer
4.431
316313AB2-026
Solar/Wind Harmer
0.191
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.182
3143336POWHATN
Solar/Wind Harmer
0.715
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
2.964
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
1.146
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.827
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
32.067
944601AF1-125 GEN
Solar/Wind Harmer
31.566
970661AG2-428 GEN
Solar/Wind Harmer
1.328
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.855
316320Y1-086
Solar/Wind Harmer
0.409
316435W1029_GEN3
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.732
3156081AA2-088 GEN
Solar/Wind Harmer
2.185
971157AH1-035 GEN
Solar/Wind Harmer
0.841
3146776BUCKING
Solar/Wind Harmer
-0.002
315737AD1-076 GEN
Solar/Wind Harmer
1.278
970917AG2-570 GEN
Solar/Wind Harmer
16.768
316365GEN2_N
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
957521AF2-046 GEN
Solar/Wind Harmer
5.262
961681AG1-008 GEN
Solar/Wind Harmer
5.262
970909AG2-566 GEN
Solar/Wind Harmer
0.633
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.164
3144293JTRSVLE
Adder
0.186
237030AB1-096 C
Solar/Wind Helper
0.1
223402AF1-300 C
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.014
205917AD1-020 ES
Solar/Wind Helper
0.357
227287AC2-120 GEN
Solar/Wind Helper
0.309
238221AF1-254 C O1
Solar/Wind Helper
0.197
235067AD1-061 GEN
Solar/Wind Helper
0.341
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.304
233994AC2-023 GEN
Solar/Wind Helper
0.578
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
232406W1-004 FULL
Solar/Wind Helper
0.305
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.992
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.239
963071AG1-156 GEN
Solar/Wind Helper
0.773
209027LOR2_Q27
Solar/Wind Helper
0.55
961331AF2-424 GEN
Solar/Wind Helper
0.233
961421AF2-433 GEN
Solar/Wind Helper
0.233
237025AB1-124 C
Solar/Wind Helper
0.233
237006AB1-125 GEN
Solar/Wind Helper
0.175
23777801MSM_W1-116
Solar/Wind Helper
0.156
237034AC2-136 C
Solar/Wind Helper
0.239
203975AE1-071-GEN
Solar/Wind Helper
1.871
233935AB2-179 C
Solar/Wind Helper
0.773
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.576
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.217
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.092
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.028
207530AG1-191 GEN
Solar/Wind Helper
0.037
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
0.994
961261AF2-417 GEN
Solar/Wind Helper
0.238
959431AF2-234 GEN
Solar/Wind Helper
0.459
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.229
238208AF1-136 C
Solar/Wind Helper
0.089
235062AE1-101 C1
Solar/Wind Helper
1.169
237038AE2-054 C
Solar/Wind Helper
0.19
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.304
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.14
232404W1-003 C
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230511AF1-262
Solar/Wind Helper
0.009
230434AG1-499 GEN
Solar/Wind Helper
0.136
228728W1-130C
Solar/Wind Helper
0.032
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.179
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
957921AF2-086 GEN
Solar/Wind Helper
0.23
209067AE2-060 GEN
Solar/Wind Helper
0.042
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.078
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.893
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
212266LOR1
Solar/Wind Helper
0.025
961341AF2-425 GEN
Solar/Wind Helper
0.233
212507AE2-042_GEN
Solar/Wind Helper
0.817
946731AF1-337 GEN
Solar/Wind Helper
0.23
209071AE2-133 GEN
Solar/Wind Helper
0.041
957481AF2-042 GEN
Solar/Wind Harmer
5.711
205916AD1-020 GEN
Solar/Wind Helper
1.658
237001AB1-127_GEN
Solar/Wind Helper
0.342
237002AB1-128_GEN
Solar/Wind Helper
0.33
226929AD2-058 GEN
Solar/Wind Helper
0.078
208835TUHI V3-051
Solar/Wind Helper
0.02
208835TUHI V3-051
Solar/Wind Helper
0.02
235063AE1-101 C2
Solar/Wind Helper
1.169
20390526W1-045 C
Solar/Wind Helper
0.277
23777901MDS_W4-102
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.141
233944AB2-135 GEN
Solar/Wind Helper
0.356
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.409
233946AB2-136 GEN
Solar/Wind Helper
0.342
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.14
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
233939AC1-091 C
Solar/Wind Helper
0.21
233970AC1-092 C
Solar/Wind Helper
0.21
230433AD2-135 GEN
Solar/Wind Helper
0.01
230407AD2-065 C
Solar/Wind Helper
0.024
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.187
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.084
211065PSPA IPP
Solar/Wind Helper
0.084
208972BECR K09
Solar/Wind Helper
0.176
961431AF2-434 GEN
Solar/Wind Helper
0.233
209029WAYMART-WD
Solar/Wind Helper
0.437
209137AF2-361 C
Solar/Wind Helper
0.703
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.23
970099AG2-077 GEN
Solar/Wind Harmer
2.284
NYPJM->LTFIMP_NY
CLTF
2.532
LAGNLTFEXP_LAGN->PJM
CLTF
5.835
LGEELTFEXP_LGEE->PJM
CLTF
1.753
WECLTFEXP_WEC->PJM
CLTF
0.941
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.776
TVALTFEXP_TVA->PJM
CLTF
2.938
CPLELTFEXP_CPLE->PJM
CLTF
4.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.691
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.772
MECLTFEXP_MEC->PJM
CLTF
4.292
SIGELTFEXP_SIGE->PJM
CLTF
0.135

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.46 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1862.72
MW Contribution:4.25
Bus #Bus NameTypeMW Contribution
3152131X4-039 ST
50/50
3.158
3152121X4-039 GT2
50/50
2.001
970467AG2-304 GEN
50/50
15.27
3150221REMNGT2
Adder
12.559
3150211REMNGT1
Adder
12.476
972201AH1-685 GEN
Adder
2.167
3150281M RUN A
Adder
13.444
316006AB2-029 C
Solar/Wind Harmer
0.632
971685AH1-345 GEN
Solar/Wind Harmer
0.963
3140676OCCOQUN
Adder
0.237
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
316045AC1-158 PL2
Solar/Wind Harmer
3.177
315683AE1-153 C
Solar/Wind Harmer
9.363
972223AH1-696 GEN
Adder
6.699
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.038
316192AB2-158 GEN
Solar/Wind Harmer
1.122
3151751LOISA D
Adder
5.425
3141346CRANES
Adder
0.098
972197AH1-683 GEN
Adder
1.698
972219AH1-694 GEN
Adder
1.223
966881AG1-559 GEN
Solar/Wind Harmer
0.092
957971AF2-091 GEN
Solar/Wind Harmer
0.888
972135AH1-637 GEN
Solar/Wind Harmer
0.887
316337AD2-073 GEN
Solar/Wind Harmer
0.235
3150351NORNECKC2
Adder
0.77
964211AG1-282 GEN
Solar/Wind Harmer
0.261
3141726DUNNSVL
Solar/Wind Harmer
-0.034
962861AG1-135 GEN
Solar/Wind Harmer
3.239
961951AG1-038 GEN
Solar/Wind Harmer
1.136
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3143526WINTERP
Solar/Wind Harmer
-0.044
3138133OCRAN
Solar/Wind Harmer
-0.005
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.006
3141843SHACKLE
Adder
0.389
3150851SPRUNCC
Adder
0.351
3143096IRON208
Adder
0.319
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
36.159
316159AE1-175 C
Solar/Wind Harmer
0.227
971317AH1-138 GEN
Solar/Wind Harmer
1.057
315671AE2-027_GEN
Solar/Wind Harmer
6.335
970129AG2-093 GEN
Solar/Wind Harmer
1.926
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
971069AG2-661 GEN
Solar/Wind Harmer
1.334
3138126ROCKLANDING
Solar/Wind Harmer
0.026
971647AH1-324 GEN
Solar/Wind Harmer
4.206
961611AG1-000B GEN
Solar/Wind Harmer
4.146
3151171GRAVELC
Adder
0.794
3145336SMITFLD
Solar/Wind Harmer
-0.033
316294AC1-161 GEN
Solar/Wind Harmer
2.704
3143336POWHATN
Solar/Wind Harmer
0.991
970659AG2-427 GEN
Solar/Wind Harmer
4.431
316381AD1-082 GEN
Solar/Wind Harmer
0.765
316375AC2-012 GEN
Solar/Wind Harmer
2.88
3150981CHESPKA
Adder
0.925
944591AF1-124 GEN
Solar/Wind Harmer
37.981
970661AG2-428 GEN
Solar/Wind Harmer
8.843
316072AD1-144
Solar/Wind Harmer
0.168
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
316336AC2-165 C
Solar/Wind Harmer
1.441
316388AE2-253 GEN
Solar/Wind Harmer
0.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.167
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
970053AG2-049 GEN
Adder
1.707
316164AC1-076 GEN
Solar/Wind Harmer
0.848
3141426STAFORD
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3150411LDYSMT5
Adder
10.908
3150381LDYSMT2
Adder
10.439
972213AH1-691 GEN
Adder
1.766
972215AH1-692 GEN
Adder
1.766
944491AF1-114 GEN
Solar/Wind Harmer
2.612
316223AC1-118
Solar/Wind Harmer
0.237
972189AH1-679 GEN
Adder
1.305
3141813NORNECK
Solar/Wind Harmer
-0.009
962981AG1-147 GEN
Solar/Wind Harmer
3.767
316312AB1-027
Solar/Wind Harmer
0.29
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971281AH1-106 GEN
Solar/Wind Harmer
1.396
971283AH1-107 GEN
Solar/Wind Harmer
1.396
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.732
316059AD1-063 C
Solar/Wind Harmer
0.193
315662AE1-191 GEN
Solar/Wind Harmer
1.031
315666AE1-190 GEN
Solar/Wind Harmer
0.258
957601AF2-054 GEN
Solar/Wind Harmer
0.256
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
971285AH1-108 GEN
Adder
0.574
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
315975AC1-164 GENB
Solar/Wind Harmer
0.267
971167AH1-042 GEN
Solar/Wind Harmer
8.225
957831AF2-077 GEN
Solar/Wind Harmer
0.255
3138283WHITEMARSH
Solar/Wind Harmer
0.013
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
316369SG1_INVT
Solar/Wind Harmer
1.505
972265AH1-717 GEN
Adder
5.796
3151201GRAVEL4
Adder
5.433
3151191GRAVEL3
Adder
5.364
3151211GRAVEL5
Adder
5.364
3143316POE
Solar/Wind Harmer
-0.033
971445AH1-216 GEN
Solar/Wind Harmer
5.176
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
3152601GOSPORTA
Adder
0.738
315833AF1-017_GEN
Solar/Wind Harmer
1.574
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316311AC2-079 GEN
Solar/Wind Harmer
4.18
957871AF2-081 GEN
Solar/Wind Harmer
4.142
319010AE1-072 C
Solar/Wind Harmer
1.673
316305AF2-043 C
Solar/Wind Harmer
0.249
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.032
313526AB2-022
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.222
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.151
316315AB2-025 C
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
15.312
944011AF1-069 GEN
Solar/Wind Harmer
4.798
315814AE2-033 C
Solar/Wind Harmer
7.6
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
971967AH1-528 GEN
Solar/Wind Harmer
15.195
315816AE2-034 GEN
Solar/Wind Harmer
0.648
972205AH1-687 GEN
Adder
3.036
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
965291AG1-394 GEN
Solar/Wind Harmer
0.704
971845AH1-439 GEN
Solar/Wind Harmer
4.213
970285AG2-188 GEN
Solar/Wind Harmer
6.934
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.94
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.595
3151881LOWMORC
Adder
0.669
3151881LOWMORC
Adder
0.659
3151861LOWMORA
Adder
0.648
972257AH1-713 GEN
Adder
0.697
23544701WINZ1-113
Adder
0.24
960921AF2-383 GEN
Solar/Wind Helper
0.152
205943AE1-185 GEN
Solar/Wind Helper
0.423
205932AD2-116_GEN
Solar/Wind Helper
0.422
205956AE1-196_GEN
Solar/Wind Helper
0.422
233935AB2-179 C
Solar/Wind Helper
1.004
232436AB1-176 C
Solar/Wind Helper
0.035
233923SMA
Solar/Wind Helper
0.755
233990AG1-397 GEN
Solar/Wind Helper
0.024
234033AF1-007_GEN
Solar/Wind Helper
5.529
232432Z2-076 GEN
Solar/Wind Helper
0.053
964001AG1-254 GEN
Solar/Wind Helper
0.738
227927V4-067C
Solar/Wind Helper
0.008
228754AB1-001 C
Solar/Wind Helper
0.02
219914AD2-027 C
Solar/Wind Helper
0.088
219272CLEANLIGHT C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
219607WPEMNERT C
Solar/Wind Helper
0.061
214067T20SOLAR
Solar/Wind Helper
0.009
20715728PEM_W1-119
Solar/Wind Helper
0.073
20715828PEM_W1-120
Solar/Wind Helper
0.073
207459AE1-142 C O1
Solar/Wind Helper
0.22
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.065
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
966261AG1-495 GEN
Solar/Wind Helper
0.06
207530AG1-191 GEN
Solar/Wind Helper
0.049
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20675928HOL_W4-097
Solar/Wind Helper
0.037
20674828DL_W4-046
Solar/Wind Helper
0.006
207484AF2-139 C O1
Solar/Wind Helper
0.062
207408W3-077 C
Solar/Wind Helper
0.062
20675728RH_W2-091
Solar/Wind Helper
0.1
20675128HRM_W1-127
Solar/Wind Helper
0.022
209116AE2-175 GEN
Solar/Wind Helper
1.289
961261AF2-417 GEN
Solar/Wind Helper
0.308
959381AF2-229 GEN
Solar/Wind Helper
0.23
959431AF2-234 GEN
Solar/Wind Helper
0.594
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
959421AF2-233 GEN
Solar/Wind Helper
0.297
203975AE1-071-GEN
Solar/Wind Helper
1.563
3152111X4-039 GT1
50/50
2.007
315747AE2-019 GEN
50/50
14.059
963691AG1-221 GEN
Solar/Wind Harmer
2.52
971455AH1-223 GEN
Solar/Wind Harmer
2.52
3141196NOKESVL
Solar/Wind Harmer
-0.049
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
972199AH1-684 GEN
Adder
1.917
972217AH1-693 GEN
Adder
1.667
3150301M RUN C
Adder
13.435
3150291M RUN B
Adder
13.336
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316450AC1-158 RIC
Solar/Wind Harmer
0.265
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.022
3151761LOISA E
Adder
11.06
972183AH1-676 GEN
Adder
89.287
3150331BIRCHWDA
Adder
13.842
3141316ARNOLDS
Adder
0.192
3150401LDYSMT4
Adder
10.874
3150371LDYSMT1
Adder
10.507
966881AG1-559 GEN
Solar/Wind Harmer
0.269
970737AG2-469 GEN
Solar/Wind Harmer
4.42
971781AH1-399 GEN
Solar/Wind Harmer
0.543
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.783
316473AC1-191 GEN
Solar/Wind Harmer
0.931
316404AE1-155 C
Solar/Wind Harmer
1.667
316484AD2-074 GEN
Solar/Wind Harmer
2.171
970009AG2-005 GEN
Solar/Wind Harmer
1.078
962971AG1-146 GEN
Solar/Wind Harmer
1.614
3142416OLDCHRC
Solar/Wind Harmer
0.867
970293AG2-193 GEN
Solar/Wind Harmer
1.071
3141766HARMONY
Solar/Wind Harmer
0.762
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316280AD1-041 GEN
Solar/Wind Harmer
0.645
316156AD2-030 GEN
Solar/Wind Harmer
0.228
3141873WAN 176
Solar/Wind Harmer
1.015
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.351
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.312
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
316382AG1-145 C
Solar/Wind Harmer
0.255
970133AG2-095 GEN
Solar/Wind Harmer
0.953
970129AG2-093 GEN
Solar/Wind Harmer
4.756
965281AG1-393 GEN
Solar/Wind Harmer
1.054
315778AD1-151 GEN
Solar/Wind Harmer
7.304
3150921YORKTN3
Adder
1.885
315839AE2-212 C
Solar/Wind Harmer
0.254
3144216WINCHST
Adder
0.283
961611AG1-000B GEN
Solar/Wind Harmer
1.769
3151221GRAVEL6
Adder
5.427
3151171GRAVELC
Adder
1.044
315813AE1-149 C
Solar/Wind Harmer
5.23
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316313AB2-026
Solar/Wind Harmer
0.225
316258AE1-075 C
Solar/Wind Harmer
0.203
316405AF2-144 C
Solar/Wind Harmer
0.214
3143336POWHATN
Solar/Wind Harmer
0.843
970659AG2-427 GEN
Solar/Wind Harmer
0.785
316083AB2-161 GEN
Solar/Wind Harmer
1.353
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
6.877
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
37.845
944601AF1-125 GEN
Solar/Wind Harmer
37.254
970661AG2-428 GEN
Solar/Wind Harmer
1.567
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
1.009
316320Y1-086
Solar/Wind Harmer
0.483
316435W1029_GEN3
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
315614AA2-178 GEN
Solar/Wind Harmer
0.864
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
971157AH1-035 GEN
Solar/Wind Harmer
0.994
315737AD1-076 GEN
Solar/Wind Harmer
1.509
3146776BUCKING
Solar/Wind Harmer
-0.003
970917AG2-570 GEN
Solar/Wind Harmer
19.793
316365GEN2_N
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
957521AF2-046 GEN
Solar/Wind Harmer
6.214
961681AG1-008 GEN
Solar/Wind Harmer
6.214
970909AG2-566 GEN
Solar/Wind Harmer
0.747
3146173TUNIS
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
35.693
3144293JTRSVLE
Adder
0.22
3151861LOWMORA
Adder
0.674
3152541MT STMG
Adder
0.593
237030AB1-096 C
Solar/Wind Helper
0.073
223402AF1-300 C
Solar/Wind Helper
0.379
226910AB2-157 C
Solar/Wind Helper
0.012
205917AD1-020 ES
Solar/Wind Helper
0.322
227287AC2-120 GEN
Solar/Wind Helper
0.266
233918AB1-142 GEN
Solar/Wind Helper
0.397
233982AB2-133 GEN
Solar/Wind Helper
0.282
233994AC2-023 GEN
Solar/Wind Helper
0.757
233996TM1833_GEN
Solar/Wind Helper
0.206
233997TMININ_4.2
Solar/Wind Helper
0.206
233940AF2-379 C
Solar/Wind Helper
0.049
234015AF2-250 C
Solar/Wind Helper
0.03
232406W1-004 FULL
Solar/Wind Helper
0.4
233952AC2-187 GEN
Solar/Wind Helper
0.183
233971AC1-093 C
Solar/Wind Helper
0.281
230430AE1-229_GEN
Solar/Wind Helper
2.603
230415AB2-049 C
Solar/Wind Helper
0.023
228729W2-030 C
Solar/Wind Helper
0.085
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.042
219912AD2-042 GEN
Solar/Wind Helper
0.115
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219906AC1-017 C
Solar/Wind Helper
0.032
219348LDSOLAR C
Solar/Wind Helper
0.088
959561AF2-247 GEN
Solar/Wind Helper
0.016
20716028EGP_W2-019
Solar/Wind Helper
0.014
20720828JCB_W4-025
Solar/Wind Helper
0.048
20715028HAN_X4-015
Solar/Wind Helper
0.043
219276PARKLANDSO C
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.043
20720528MAN_W1-024
Solar/Wind Helper
0.021
219612MATRIX C
Solar/Wind Helper
0.018
218438BLK ROCK C
Solar/Wind Helper
0.02
219908AB1-139 C
Solar/Wind Helper
0.055
219919AE1-041 FULL
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.008
20673728F2S_V4-070
Solar/Wind Helper
0.022
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
207510AF2-138 C
Solar/Wind Helper
0.06
20674628WNG_W3-110
Solar/Wind Helper
0.066
963161AG1-165 GEN
Solar/Wind Helper
0.309
963071AG1-156 GEN
Solar/Wind Helper
1.001
209027LOR2_Q27
Solar/Wind Helper
0.712
961331AF2-424 GEN
Solar/Wind Helper
0.302
961421AF2-433 GEN
Solar/Wind Helper
0.302
957921AF2-086 GEN
Solar/Wind Helper
0.298
946691AF1-333 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
209067AE2-060 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.122
235067AD1-061 GEN
Solar/Wind Helper
0.214
972289AH1-729 GEN
50/50
14.564
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316447AC1-158 HLD
Solar/Wind Harmer
2.184
3150071POSSM 5
Adder
38.76
3150181POSSMC2
Adder
0.855
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.425
3151721LOISA A
Adder
5.397
3150391LDYSMT3
Adder
10.854
972195AH1-682 GEN
Adder
1.426
315673AE1-157 GEN
Solar/Wind Harmer
6.752
957411AF2-035 GEN
Solar/Wind Harmer
4.024
970317AG2-208 GEN
Solar/Wind Harmer
3.912
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316077AC2-138 C
Solar/Wind Harmer
0.183
3150341NORNECKC1
Adder
0.809
3150341NORNECKC1
Adder
0.802
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
958261AF2-120 GEN
Solar/Wind Harmer
3.349
316487AF1-042 GEN
Solar/Wind Harmer
1.136
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.075
3143526WINTERP
Solar/Wind Harmer
-0.044
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3150681DARBY 2
Adder
5.471
3150671DARBY 1
Adder
5.465
316075AC2-137 C
Solar/Wind Harmer
0.231
316441AF1-014 GEN
Solar/Wind Harmer
0.577
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
35.924
316240AF1-291 C
Solar/Wind Harmer
0.255
316033AB2-134 GEN
Solar/Wind Harmer
2.716
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316236AE1-162_GEN
Solar/Wind Harmer
0.252
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
316036AC1-147 C
Solar/Wind Harmer
0.225
3150991CHESPKB
Adder
0.776
3150991CHESPKB
Adder
0.757
316316AC1-027 C
Solar/Wind Harmer
0.255
3142956BIRDNECK
Solar/Wind Harmer
0.446
316185AD1-033 GEN
Solar/Wind Harmer
0.876
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.559
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3146456SLIGO L269
Solar/Wind Harmer
0.977
3130086AYDLETT
Solar/Wind Harmer
-0.033
3146386ELIZ CT
Solar/Wind Harmer
-0.008
971761AH1-387 GEN
Solar/Wind Harmer
4.579
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3144356SAPONY
Solar/Wind Harmer
0.285
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.849
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
972185AH1-677 GEN
Adder
4.036
972187AH1-678 GEN
Adder
2.039
970933AG2-581 GEN
Solar/Wind Harmer
7.52
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.958
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
3.936
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
971741AH1-377 GEN
Solar/Wind Harmer
9.144
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.185
237025AB1-124 C
Solar/Wind Helper
0.168
237006AB1-125 GEN
Solar/Wind Helper
0.126
23777801MSM_W1-116
Solar/Wind Helper
0.11
205916AD1-020 GEN
Solar/Wind Helper
1.496
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
237034AC2-136 C
Solar/Wind Helper
0.157
233933AB2-153 GEN
Solar/Wind Helper
0.184
233944AB2-135 GEN
Solar/Wind Helper
0.465
232424Y1-079 C
Solar/Wind Helper
0.092
233987AB2-037 GEN
Solar/Wind Helper
1.847
233946AB2-136 GEN
Solar/Wind Helper
0.448
234036AF2-325 C
Solar/Wind Helper
0.033
233901CHERRYDALE C
Solar/Wind Helper
0.183
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
233939AC1-091 C
Solar/Wind Helper
0.275
233970AC1-092 C
Solar/Wind Helper
0.275
230433AD2-135 GEN
Solar/Wind Helper
0.013
230407AD2-065 C
Solar/Wind Helper
0.031
219921AF1-264
Solar/Wind Helper
0.039
219615MILLCREEK C
Solar/Wind Helper
0.02
963401AG1-189 GEN
Solar/Wind Helper
0.043
963391AG1-188 GEN
Solar/Wind Helper
0.062
20714928UPF_X1-085
Solar/Wind Helper
0.004
20720628TIN_W1-124
Solar/Wind Helper
0.143
20716928W4-060COL
Solar/Wind Helper
0.039
218440SUMMTASSOC C
Solar/Wind Helper
0.012
20673828FLE_V3-070
Solar/Wind Helper
0.068
207442AE1-156 GEN
Solar/Wind Helper
0.243
20676128MHD_W3-029
Solar/Wind Helper
0.072
20671828STAW2-080
Solar/Wind Helper
0.02
217081WEATEXAS C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
226929AD2-058 GEN
Solar/Wind Helper
0.066
207471AF2-354 C
Solar/Wind Helper
0.124
20674928WA_W3-044
Solar/Wind Helper
0.072
20676228FRD_X1-012
Solar/Wind Helper
0.067
964851AG1-348 GEN
Solar/Wind Helper
0.059
20674128FR_U2-059
Solar/Wind Helper
0.003
966111AG1-480 GEN
Solar/Wind Helper
0.032
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
20390526W1-045 C
Solar/Wind Helper
0.226
208972BECR K09
Solar/Wind Helper
0.227
961431AF2-434 GEN
Solar/Wind Helper
0.302
209029WAYMART-WD
Solar/Wind Helper
0.566
209054AE2-059 GEN
Solar/Wind Helper
0.054
946751AF1-339 GEN
Solar/Wind Helper
0.297
209137AF2-361 C
Solar/Wind Helper
0.864
237001AB1-127_GEN
Solar/Wind Helper
0.221
237002AB1-128_GEN
Solar/Wind Helper
0.212
235063AE1-101 C2
Solar/Wind Helper
0.747
970099AG2-077 GEN
Solar/Wind Harmer
2.697
970937AG2-583 GEN
Solar/Wind Harmer
5.84
3130156CHOWAN
Solar/Wind Harmer
-0.008
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.509
972003AH1-546 GEN
Solar/Wind Harmer
3.978
316322AB2-045
Solar/Wind Harmer
0.267
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.505
316023GEN1_S
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
970087AG2-069 GEN
Solar/Wind Harmer
7.409
971547AH1-271 GEN
Solar/Wind Harmer
1.976
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146173TUNIS
Solar/Wind Harmer
-0.008
972277AH1-723 GEN
Adder
41.593
3147043LAWRENC
Adder
0.626
3144293JTRSVLE
Adder
0.22
223401AF1-299 GEN
Solar/Wind Helper
0.379
23779801AA1-109
Solar/Wind Helper
0.182
966131AG1-482 GEN
Solar/Wind Helper
0.066
233930AB2-032 GEN
Solar/Wind Helper
0.301
233915AB1-141 GEN
Solar/Wind Helper
0.397
232422X3-066 FULL
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.033
232426Y1-080 FULL
Solar/Wind Helper
0.031
233998TM1NIN_3.36
Solar/Wind Helper
0.206
232428Y3-058 C
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.4
233954AC2-188 GEN
Solar/Wind Helper
0.183
233950AC2-186 GEN
Solar/Wind Helper
0.091
232434Z2-077 GEN
Solar/Wind Helper
0.1
233972AC1-094 C
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.011
230434AG1-499 GEN
Solar/Wind Helper
0.177
228728W1-130C
Solar/Wind Helper
0.041
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219904AC1-010 C
Solar/Wind Helper
0.047
219907AC1-030 C
Solar/Wind Helper
0.026
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219304NAMERICA C
Solar/Wind Helper
0.1
20720728JCB_W1-129
Solar/Wind Helper
0.043
207445AB1-138_GEN
Solar/Wind Helper
0.079
963711AG1-223 GEN
Solar/Wind Helper
0.048
20714828MDF_W3-079
Solar/Wind Helper
0.099
205941AD2-115 GEN
Solar/Wind Helper
0.375
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.234
20715228NPK_W1-113
Solar/Wind Helper
0.059
20742028HF_AC1-207
Solar/Wind Helper
0.106
218428ETC SOLAR C
Solar/Wind Helper
0.004
217213AMBOY SO C
Solar/Wind Helper
0.021
207528AF2-192 GEN
Solar/Wind Helper
0.057
20673628F1S_V4-069
Solar/Wind Helper
0.022
20675428EAM_W2-061
Solar/Wind Helper
0.012
20676428JCR_X2-075
Solar/Wind Helper
0.051
217209CENTRL HS C
Solar/Wind Helper
0.006
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.017
207439AE1-081 C O1
Solar/Wind Helper
0.014
207437AD2-070 GEN
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.022
207518AF1-320_GEN
Solar/Wind Helper
1.156
20671928W4-073
Solar/Wind Helper
0.066
961301AF2-421 GEN
Solar/Wind Helper
0.309
963151AG1-164 GEN
Solar/Wind Helper
0.309
212266LOR1
Solar/Wind Helper
0.033
961341AF2-425 GEN
Solar/Wind Helper
0.302
212507AE2-042_GEN
Solar/Wind Helper
1.058
946731AF1-337 GEN
Solar/Wind Helper
0.297
209071AE2-133 GEN
Solar/Wind Helper
0.054
235062AE1-101 C1
Solar/Wind Helper
0.747
237080AD1-060 GEN
Solar/Wind Helper
0.151
237038AE2-054 C
Solar/Wind Helper
0.119
957481AF2-042 GEN
Solar/Wind Harmer
6.742
NYPJM->LTFIMP_NY
CLTF
3.269
LGEELTFEXP_LGEE->PJM
CLTF
2.098
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
WECLTFEXP_WEC->PJM
CLTF
1.126
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
TVALTFEXP_TVA->PJM
CLTF
3.503
CPLELTFEXP_CPLE->PJM
CLTF
5.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
MECLTFEXP_MEC->PJM
CLTF
5.133
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 6EDFERRY-DICKH230 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 514-2098_SRT-S


Base Case Flowgate

Area:DVP/PEPCO
Facility Description:
6EDFERRY-DICKH230 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 514-2098_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.66 %
Rating:1417.0 MVA
Rating Type:B
MVA to Mitigate:1482.99
MW Contribution:3.57
Bus #Bus NameTypeMW Contribution
3152111X4-039 GT1
50/50
1.893
315747AE2-019 GEN
50/50
12.918
963691AG1-221 GEN
Solar/Wind Harmer
2.324
971455AH1-223 GEN
Solar/Wind Harmer
2.324
3141196NOKESVL
Solar/Wind Harmer
-0.045
3150231REMNGT3
Adder
12.096
3150241REMNGT4
Adder
11.278
972199AH1-684 GEN
Adder
1.71
972217AH1-693 GEN
Adder
1.487
3150301M RUN C
Adder
11.982
3150291M RUN B
Adder
11.893
316170AC1-121 GEN2
Solar/Wind Harmer
0.243
316044AC1-158 PL1
Solar/Wind Harmer
0.882
316450AC1-158 RIC
Solar/Wind Harmer
0.235
3150151POSSMC1
Adder
0.79
3150151POSSMC1
Adder
0.79
3132273ORANGE
Solar/Wind Harmer
-0.002
3150331BIRCHWDA
Adder
12.528
3147666LOUISA
Solar/Wind Harmer
-0.019
3141316ARNOLDS
Adder
0.173
3150401LDYSMT4
Adder
9.727
3150371LDYSMT1
Adder
9.399
3151761LOISA E
Adder
9.559
972183AH1-676 GEN
Adder
77.132
966881AG1-559 GEN
Solar/Wind Harmer
0.238
970737AG2-469 GEN
Solar/Wind Harmer
3.911
3141906WESTMOR
Solar/Wind Harmer
-0.003
971781AH1-399 GEN
Solar/Wind Harmer
0.478
3150351NORNECKC2
Adder
0.685
316404AE1-155 C
Solar/Wind Harmer
1.454
316473AC1-191 GEN
Solar/Wind Harmer
0.81
316484AD2-074 GEN
Solar/Wind Harmer
1.891
970009AG2-005 GEN
Solar/Wind Harmer
0.939
962971AG1-146 GEN
Solar/Wind Harmer
1.405
3142416OLDCHRC
Solar/Wind Harmer
0.751
3141766HARMONY
Solar/Wind Harmer
0.66
316280AD1-041 GEN
Solar/Wind Harmer
0.559
316156AD2-030 GEN
Solar/Wind Harmer
0.198
3141873WAN 176
Solar/Wind Harmer
0.88
316203AE2-005 GEN
Solar/Wind Harmer
3.126
3141843SHACKLE
Adder
0.337
970293AG2-193 GEN
Solar/Wind Harmer
0.926
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
3143096IRON208
Adder
0.275
3143096IRON208
Adder
0.27
3150861SPRUNCD
Adder
0.303
3142946ENON
Solar/Wind Harmer
-0.002
316382AG1-145 C
Solar/Wind Harmer
0.22
970133AG2-095 GEN
Solar/Wind Harmer
0.82
970129AG2-093 GEN
Solar/Wind Harmer
4.092
965281AG1-393 GEN
Solar/Wind Harmer
0.907
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.107
316415AF1-147_GEN2
Solar/Wind Harmer
1.107
970053AG2-049 GEN
Adder
1.58
316164AC1-076 GEN
Solar/Wind Harmer
0.75
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.757
3150381LDYSMT2
Adder
9.338
972213AH1-691 GEN
Adder
1.58
972215AH1-692 GEN
Adder
1.58
3147346CASHSCORNER
Solar/Wind Harmer
0.123
944491AF1-114 GEN
Solar/Wind Harmer
2.324
316223AC1-118
Solar/Wind Harmer
0.209
972189AH1-679 GEN
Adder
1.141
3141813NORNECK
Solar/Wind Harmer
-0.008
962981AG1-147 GEN
Solar/Wind Harmer
3.278
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
316312AB1-027
Solar/Wind Harmer
0.251
3141913WHIT STONE
Solar/Wind Harmer
-0.007
316314AB2-024 C
Solar/Wind Harmer
0.634
316059AD1-063 C
Solar/Wind Harmer
0.168
315662AE1-191 GEN
Solar/Wind Harmer
0.894
315666AE1-190 GEN
Solar/Wind Harmer
0.223
957601AF2-054 GEN
Solar/Wind Harmer
0.222
3141873WAN 176
Solar/Wind Harmer
-0.001
316233AE1-074 FULL
Solar/Wind Harmer
0.199
971281AH1-106 GEN
Solar/Wind Harmer
1.205
971283AH1-107 GEN
Solar/Wind Harmer
1.205
3143873LANEXA
Solar/Wind Harmer
-0.004
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
971167AH1-042 GEN
Solar/Wind Harmer
7.117
315976AC1-164 GENA
Solar/Wind Harmer
7.807
316169AC1-164_GENC
Solar/Wind Harmer
6.744
315975AC1-164 GENB
Solar/Wind Harmer
0.231
971285AH1-108 GEN
Adder
0.495
957831AF2-077 GEN
Solar/Wind Harmer
0.22
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.735
316369SG1_INVT
Solar/Wind Harmer
1.293
972265AH1-717 GEN
Adder
4.974
3151201GRAVEL4
Adder
4.663
3151191GRAVEL3
Adder
4.604
3151211GRAVEL5
Adder
4.604
971445AH1-216 GEN
Solar/Wind Harmer
4.438
3143316POE
Solar/Wind Harmer
-0.028
3151081ELIZAR1
Adder
5.812
3151091ELIZAR2
Adder
5.711
3152611GOSPORTB
Adder
0.807
3152621GOSPORTC
Adder
0.685
3152601GOSPORTA
Adder
0.632
315833AF1-017_GEN
Solar/Wind Harmer
1.345
316349AD2-085 GEN
Solar/Wind Harmer
0.63
316311AC2-079 GEN
Solar/Wind Harmer
3.572
957871AF2-081 GEN
Solar/Wind Harmer
3.539
319010AE1-072 C
Solar/Wind Harmer
1.429
316305AF2-043 C
Solar/Wind Harmer
0.213
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
0.881
313526AB2-022
Solar/Wind Harmer
0.19
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.189
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
972289AH1-729 GEN
50/50
13.565
315651AD1-115 GEN
Solar/Wind Harmer
4.033
316447AC1-158 HLD
Solar/Wind Harmer
1.939
3150071POSSM 5
Adder
36.095
3150181POSSMC2
Adder
0.796
3150181POSSMC2
Adder
0.79
3150181POSSMC2
Adder
0.79
966001AG1-469 GEN
Solar/Wind Harmer
0.155
3150391LDYSMT3
Adder
9.709
972195AH1-682 GEN
Adder
1.276
3151731LOISA B
Adder
4.689
3151721LOISA A
Adder
4.665
315673AE1-157 GEN
Solar/Wind Harmer
6.001
957411AF2-035 GEN
Solar/Wind Harmer
3.562
970317AG2-208 GEN
Solar/Wind Harmer
3.463
316468AD1-105 GEN
Solar/Wind Harmer
0.864
316077AC2-138 C
Solar/Wind Harmer
0.16
3150341NORNECKC1
Adder
0.707
3150341NORNECKC1
Adder
0.702
958261AF2-120 GEN
Solar/Wind Harmer
2.921
966871AG1-558 GEN
Solar/Wind Harmer
0.226
3152131X4-039 ST
50/50
2.978
3152121X4-039 GT2
50/50
1.887
3140676OCCOQUN
Adder
0.219
3150221REMNGT2
Adder
11.204
3150211REMNGT1
Adder
11.13
972201AH1-685 GEN
Adder
1.933
3150281M RUN A
Adder
11.989
316006AB2-029 C
Solar/Wind Harmer
0.563
971685AH1-345 GEN
Solar/Wind Harmer
0.858
316254AC1-120 GEN1
Solar/Wind Harmer
0.729
316045AC1-158 PL2
Solar/Wind Harmer
2.821
972223AH1-696 GEN
Adder
6.238
3150151POSSMC1
Adder
0.79
315683AE1-153 C
Solar/Wind Harmer
8.198
3141346CRANES
Adder
0.089
3147666LOUISA
Solar/Wind Harmer
-0.033
316192AB2-158 GEN
Solar/Wind Harmer
0.98
972197AH1-683 GEN
Adder
1.519
972219AH1-694 GEN
Adder
1.094
3151751LOISA D
Adder
4.689
957971AF2-091 GEN
Solar/Wind Harmer
0.79
966881AG1-559 GEN
Solar/Wind Harmer
0.081
972135AH1-637 GEN
Solar/Wind Harmer
0.787
316337AD2-073 GEN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
0.673
964211AG1-282 GEN
Solar/Wind Harmer
0.228
3141726DUNNSVL
Solar/Wind Harmer
-0.03
962861AG1-135 GEN
Solar/Wind Harmer
2.824
961951AG1-038 GEN
Solar/Wind Harmer
0.989
3138133OCRAN
Solar/Wind Harmer
-0.004
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3141766HARMONY
Solar/Wind Harmer
-0.001
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
971777AH1-397 GEN
Solar/Wind Harmer
0.872
3141843SHACKLE
Adder
0.337
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.128
3142433PROV 92
Adder
0.128
3143096IRON208
Adder
0.275
3150851SPRUNCC
Adder
0.303
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
31.219
316159AE1-175 C
Solar/Wind Harmer
0.196
971317AH1-138 GEN
Solar/Wind Harmer
0.911
970129AG2-093 GEN
Solar/Wind Harmer
1.657
315671AE2-027_GEN
Solar/Wind Harmer
5.45
316458AB2-190 GEN2
Solar/Wind Harmer
0.735
971069AG2-661 GEN
Solar/Wind Harmer
1.147
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.613
961611AG1-000B GEN
Solar/Wind Harmer
3.56
3151171GRAVELC
Adder
0.681
3145336SMITFLD
Solar/Wind Harmer
-0.029
316294AC1-161 GEN
Solar/Wind Harmer
2.317
970659AG2-427 GEN
Solar/Wind Harmer
3.796
316381AD1-082 GEN
Solar/Wind Harmer
0.655
3146396TANGLEW
Solar/Wind Harmer
0.129
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
13.006
944011AF1-069 GEN
Solar/Wind Harmer
4.075
315814AE2-033 C
Solar/Wind Harmer
6.458
315611Z1-036_GEN2
Solar/Wind Harmer
1.707
970673AG2-436 GEN
Solar/Wind Harmer
14.436
970673AG2-436 GEN
Solar/Wind Harmer
7.309
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.856
315816AE2-034 GEN
Solar/Wind Harmer
0.548
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.352
315733AD1-074 GEN2
Solar/Wind Harmer
1.352
315735AD1-075 GEN1
Solar/Wind Harmer
0.676
965291AG1-394 GEN
Solar/Wind Harmer
0.593
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.908
316318V4-068
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.15
970581AG2-369 GEN
Solar/Wind Harmer
3.569
972205AH1-687 GEN
Adder
2.506
3145513AHOSKIE
Solar/Wind Harmer
0.057
961941AG1-037 GEN
Solar/Wind Harmer
0.049
3145513AHOSKIE
Solar/Wind Harmer
-0.007
946281AF1-292 GEN
Solar/Wind Harmer
0.147
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.298
237085AD2-009_GEN
Solar/Wind Helper
1.037
959381AF2-229 GEN
Solar/Wind Helper
0.251
960921AF2-383 GEN
Solar/Wind Helper
0.119
205943AE1-185 GEN
Solar/Wind Helper
0.335
203975AE1-071-GEN
Solar/Wind Helper
1.667
205956AE1-196_GEN
Solar/Wind Helper
0.332
205932AD2-116_GEN
Solar/Wind Helper
0.332
238208AF1-136 C
Solar/Wind Helper
0.101
233935AB2-179 C
Solar/Wind Helper
0.644
232436AB1-176 C
Solar/Wind Helper
0.022
233923SMA
Solar/Wind Helper
0.482
233990AG1-397 GEN
Solar/Wind Helper
0.015
232432Z2-076 GEN
Solar/Wind Helper
0.034
234033AF1-007_GEN
Solar/Wind Helper
3.527
964001AG1-254 GEN
Solar/Wind Helper
0.476
219914AD2-027 C
Solar/Wind Helper
0.057
227927V4-067C
Solar/Wind Helper
0.005
228754AB1-001 C
Solar/Wind Helper
0.013
219272CLEANLIGHT C
Solar/Wind Helper
0.013
219688LUMSOLAR_S C
Solar/Wind Helper
0.02
219607WPEMNERT C
Solar/Wind Helper
0.04
214067T20SOLAR
Solar/Wind Helper
0.006
20715728PEM_W1-119
Solar/Wind Helper
0.047
20715828PEM_W1-120
Solar/Wind Helper
0.047
207459AE1-142 C O1
Solar/Wind Helper
0.143
219620RIDERU C
Solar/Wind Helper
0.001
316375AC2-012 GEN
Solar/Wind Harmer
2.465
3150981CHESPKA
Adder
0.791
970661AG2-428 GEN
Solar/Wind Harmer
7.568
944591AF1-124 GEN
Solar/Wind Harmer
32.501
316072AD1-144
Solar/Wind Harmer
0.144
939411AE1-173 GEN
Solar/Wind Harmer
35.449
3143336POWHATN
Solar/Wind Harmer
0.841
940641AE2-051 GEN
Solar/Wind Harmer
6.642
316388AE2-253 GEN
Solar/Wind Harmer
0.478
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.143
316093AE2-104_GEN
Solar/Wind Harmer
2.049
316336AC2-165 C
Solar/Wind Harmer
1.216
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.707
3130156CHOWAN
Solar/Wind Harmer
-0.007
970937AG2-583 GEN
Solar/Wind Harmer
4.871
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.345
970919AG2-571 GEN
Solar/Wind Harmer
2.106
316023GEN1_S
Solar/Wind Harmer
0.449
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.662
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.197
966871AG1-558 GEN
Solar/Wind Harmer
0.077
316487AF1-042 GEN
Solar/Wind Harmer
0.989
3142296MT RD221
Adder
0.212
3142366NRTHEST
Adder
0.216
3150691DARBY 3
Adder
4.75
3150701DARBY 4
Adder
4.739
3150681DARBY 2
Adder
4.734
3150671DARBY 1
Adder
4.728
971223AH1-071 GEN
Solar/Wind Harmer
0.927
316441AF1-014 GEN
Solar/Wind Harmer
0.5
3143526WINTERP
Solar/Wind Harmer
-0.038
316075AC2-137 C
Solar/Wind Harmer
0.2
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.931
316240AF1-291 C
Solar/Wind Harmer
0.219
316033AB2-134 GEN
Solar/Wind Harmer
2.335
315697AD1-025 GEN
Solar/Wind Harmer
1.464
316236AE1-162_GEN
Solar/Wind Harmer
0.216
970657AG2-426 GEN
Solar/Wind Harmer
2.229
970657AG2-426 GEN
Solar/Wind Harmer
0.466
316036AC1-147 C
Solar/Wind Harmer
0.192
3150991CHESPKB
Adder
0.664
3150991CHESPKB
Adder
0.648
3142956BIRDNECK
Solar/Wind Harmer
0.382
316316AC1-027 C
Solar/Wind Harmer
0.218
316185AD1-033 GEN
Solar/Wind Harmer
0.75
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.478
316018AA1-139 ULT2
Solar/Wind Harmer
0.606
316017AA1-139 ULT1
Solar/Wind Harmer
0.573
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.835
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.265
316433W1029_GEN2
Solar/Wind Harmer
1.265
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.242
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.72
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.416
972187AH1-678 GEN
Adder
1.723
970933AG2-581 GEN
Solar/Wind Harmer
6.344
316065AD1-022 GEN
Solar/Wind Harmer
3.331
3145893MURPHYS
Solar/Wind Harmer
0.185
3145893MURPHYS
Solar/Wind Harmer
-0.012
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970099AG2-077 GEN
Solar/Wind Harmer
8.214
3146776BUCKING
Solar/Wind Harmer
-0.026
3146776BUCKING
Solar/Wind Harmer
-0.002
3144293JTRSVLE
Adder
0.182
3144293JTRSVLE
Adder
0.153
237025AB1-124 C
Solar/Wind Helper
0.191
237006AB1-125 GEN
Solar/Wind Helper
0.143
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.211
237001AB1-127_GEN
Solar/Wind Helper
0.322
237002AB1-128_GEN
Solar/Wind Helper
0.314
205916AD1-020 GEN
Solar/Wind Helper
1.357
235063AE1-101 C2
Solar/Wind Helper
1.123
23777901MDS_W4-102
Solar/Wind Helper
0.114
235020AA1-095 C
Solar/Wind Helper
0.032
20390526W1-045 C
Solar/Wind Helper
0.246
208835TUHI V3-051
Solar/Wind Helper
0.015
208835TUHI V3-051
Solar/Wind Helper
0.015
226929AD2-058 GEN
Solar/Wind Helper
0.051
233933AB2-153 GEN
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.297
232424Y1-079 C
Solar/Wind Helper
0.059
233987AB2-037 GEN
Solar/Wind Helper
1.178
234036AF2-325 C
Solar/Wind Helper
0.021
233946AB2-136 GEN
Solar/Wind Helper
0.286
233901CHERRYDALE C
Solar/Wind Helper
0.117
232408W1-005 C
Solar/Wind Helper
0.255
232410W1-006 C
Solar/Wind Helper
0.255
233939AC1-091 C
Solar/Wind Helper
0.176
233970AC1-092 C
Solar/Wind Helper
0.176
230433AD2-135 GEN
Solar/Wind Helper
0.008
230407AD2-065 C
Solar/Wind Helper
0.02
219921AF1-264
Solar/Wind Helper
0.025
219615MILLCREEK C
Solar/Wind Helper
0.013
963401AG1-189 GEN
Solar/Wind Helper
0.028
963391AG1-188 GEN
Solar/Wind Helper
0.041
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.093
20716928W4-060COL
Solar/Wind Helper
0.025
20673828FLE_V3-070
Solar/Wind Helper
0.044
218440SUMMTASSOC C
Solar/Wind Helper
0.008
207442AE1-156 GEN
Solar/Wind Helper
0.159
20676128MHD_W3-029
Solar/Wind Helper
0.047
20671828STAW2-080
Solar/Wind Helper
0.013
217081WEATEXAS C
Solar/Wind Helper
0.006
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.003
315778AD1-151 GEN
Solar/Wind Harmer
6.281
3150921YORKTN3
Adder
1.622
3144216WINCHST
Adder
0.243
315839AE2-212 C
Solar/Wind Harmer
0.218
961611AG1-000B GEN
Solar/Wind Harmer
1.519
3151221GRAVEL6
Adder
4.658
3151171GRAVELC
Adder
0.896
315813AE1-149 C
Solar/Wind Harmer
4.484
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
2.997
970659AG2-427 GEN
Solar/Wind Harmer
0.673
316083AB2-161 GEN
Solar/Wind Harmer
1.159
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.886
3144873MCLAUGH
Solar/Wind Harmer
0
970661AG2-428 GEN
Solar/Wind Harmer
1.341
944581AF1-123 GEN
Solar/Wind Harmer
32.385
944601AF1-125 GEN
Solar/Wind Harmer
31.879
316313AB2-026
Solar/Wind Harmer
0.191
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.182
3143336POWHATN
Solar/Wind Harmer
0.715
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.862
316320Y1-086
Solar/Wind Harmer
0.412
316435W1029_GEN3
Solar/Wind Harmer
1.265
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.73
971157AH1-035 GEN
Solar/Wind Harmer
0.837
3156081AA2-088 GEN
Solar/Wind Harmer
2.173
315737AD1-076 GEN
Solar/Wind Harmer
1.271
970917AG2-570 GEN
Solar/Wind Harmer
16.639
316365GEN2_N
Solar/Wind Harmer
0.449
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.046
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.222
961681AG1-008 GEN
Solar/Wind Harmer
5.222
3146173TUNIS
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
0.888
316463AE2-346 GEN
Solar/Wind Harmer
0.107
316140AB2-099
Solar/Wind Harmer
0.044
962331AG1-082 GEN
Solar/Wind Harmer
0.823
966621AG1-532 GEN
Solar/Wind Harmer
0.133
3146776BUCKING
Solar/Wind Harmer
-0.002
3144293JTRSVLE
Adder
0.182
972255AH1-712 GEN
Adder
29.04
237030AB1-096 C
Solar/Wind Helper
0.082
238221AF1-254 C O1
Solar/Wind Helper
0.191
205917AD1-020 ES
Solar/Wind Helper
0.292
223402AF1-300 C
Solar/Wind Helper
0.282
235067AD1-061 GEN
Solar/Wind Helper
0.331
226910AB2-157 C
Solar/Wind Helper
0.01
227287AC2-120 GEN
Solar/Wind Helper
0.203
233982AB2-133 GEN
Solar/Wind Helper
0.181
233918AB1-142 GEN
Solar/Wind Helper
0.254
233994AC2-023 GEN
Solar/Wind Helper
0.483
233996TM1833_GEN
Solar/Wind Helper
0.131
233997TMININ_4.2
Solar/Wind Helper
0.131
233940AF2-379 C
Solar/Wind Helper
0.031
234015AF2-250 C
Solar/Wind Helper
0.019
233952AC2-187 GEN
Solar/Wind Helper
0.117
232406W1-004 FULL
Solar/Wind Helper
0.255
233971AC1-093 C
Solar/Wind Helper
0.179
230430AE1-229_GEN
Solar/Wind Helper
1.678
230415AB2-049 C
Solar/Wind Helper
0.015
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.027
219912AD2-042 GEN
Solar/Wind Helper
0.074
228729W2-030 C
Solar/Wind Helper
0.055
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.006
219906AC1-017 C
Solar/Wind Helper
0.021
219348LDSOLAR C
Solar/Wind Helper
0.057
959561AF2-247 GEN
Solar/Wind Helper
0.01
20716028EGP_W2-019
Solar/Wind Helper
0.009
20720828JCB_W4-025
Solar/Wind Helper
0.031
20715028HAN_X4-015
Solar/Wind Helper
0.028
219276PARKLANDSO C
Solar/Wind Helper
0.044
20714528FRN_Y2-051
Solar/Wind Helper
0.028
20720528MAN_W1-024
Solar/Wind Helper
0.014
219612MATRIX C
Solar/Wind Helper
0.012
218438BLK ROCK C
Solar/Wind Helper
0.013
20673728F2S_V4-070
Solar/Wind Helper
0.015
219908AB1-139 C
Solar/Wind Helper
0.036
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.005
217211CAMDEN ST C
Solar/Wind Helper
0.002
217169METRODIV C
Solar/Wind Helper
0.002
970087AG2-069 GEN
Solar/Wind Harmer
6.225
3146173TUNIS
Solar/Wind Harmer
-0.007
972003AH1-546 GEN
Solar/Wind Harmer
3.284
960081AF2-299 GEN
Solar/Wind Harmer
0.74
957481AF2-042 GEN
Solar/Wind Harmer
20.536
316322AB2-045
Solar/Wind Harmer
0.221
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146776BUCKING
Solar/Wind Harmer
-0.003
3147043LAWRENC
Adder
0.523
3144293JTRSVLE
Adder
0.182
972277AH1-723 GEN
Adder
33.84
23779801AA1-109
Solar/Wind Helper
0.218
223401AF1-299 GEN
Solar/Wind Helper
0.282
237080AD1-060 GEN
Solar/Wind Helper
0.235
237038AE2-054 C
Solar/Wind Helper
0.184
235062AE1-101 C1
Solar/Wind Helper
1.123
966131AG1-482 GEN
Solar/Wind Helper
0.056
233930AB2-032 GEN
Solar/Wind Helper
0.192
233915AB1-141 GEN
Solar/Wind Helper
0.254
232422X3-066 FULL
Solar/Wind Helper
0.058
205941AD2-115 GEN
Solar/Wind Helper
0.256
233964AF2-378 GEN
Solar/Wind Helper
0.021
232426Y1-080 FULL
Solar/Wind Helper
0.02
233998TM1NIN_3.36
Solar/Wind Helper
0.131
232428Y3-058 C
Solar/Wind Helper
0.17
233954AC2-188 GEN
Solar/Wind Helper
0.117
232404W1-003 C
Solar/Wind Helper
0.255
233950AC2-186 GEN
Solar/Wind Helper
0.058
232434Z2-077 GEN
Solar/Wind Helper
0.064
233972AC1-094 C
Solar/Wind Helper
0.152
230511AF1-262
Solar/Wind Helper
0.007
230434AG1-499 GEN
Solar/Wind Helper
0.114
219258KINSLEYDEP C
Solar/Wind Helper
0.038
228728W1-130C
Solar/Wind Helper
0.027
219904AC1-010 C
Solar/Wind Helper
0.03
219907AC1-030 C
Solar/Wind Helper
0.017
218660EHAMPSOLAR C
Solar/Wind Helper
0.016
219686LUMSOLAR_N C
Solar/Wind Helper
0.02
219304NAMERICA C
Solar/Wind Helper
0.065
20720728JCB_W1-129
Solar/Wind Helper
0.028
207445AB1-138_GEN
Solar/Wind Helper
0.051
963711AG1-223 GEN
Solar/Wind Helper
0.032
20714828MDF_W3-079
Solar/Wind Helper
0.064
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.152
20715228NPK_W1-113
Solar/Wind Helper
0.038
20742028HF_AC1-207
Solar/Wind Helper
0.069
207528AF2-192 GEN
Solar/Wind Helper
0.037
20673628F1S_V4-069
Solar/Wind Helper
0.015
20675428EAM_W2-061
Solar/Wind Helper
0.008
20676428JCR_X2-075
Solar/Wind Helper
0.033
218428ETC SOLAR C
Solar/Wind Helper
0.002
217213AMBOY SO C
Solar/Wind Helper
0.014
217209CENTRL HS C
Solar/Wind Helper
0.004
217208PARK ELE C
Solar/Wind Helper
0.002
20675528CPH_W2-050
Solar/Wind Helper
0.042
218526CNTRALGAS2 C
Solar/Wind Helper
0.079
218524CNTRALGAS1 C
Solar/Wind Helper
0.079
966261AG1-495 GEN
Solar/Wind Helper
0.04
971845AH1-439 GEN
Solar/Wind Harmer
0.654
NYPJM->LTFIMP_NY
CLTF
2.219
LGEELTFEXP_LGEE->PJM
CLTF
1.359
LAGNLTFEXP_LAGN->PJM
CLTF
4.834
WECLTFEXP_WEC->PJM
CLTF
0.721
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.78
TVALTFEXP_TVA->PJM
CLTF
2.439
CPLELTFEXP_CPLE->PJM
CLTF
3.96
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.603
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.848
MECLTFEXP_MEC->PJM
CLTF
3.353
SIGELTFEXP_SIGE->PJM
CLTF
0.105

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.83 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1144.9
MW Contribution:8.55
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.146
316118AC1-105 GEN
Solar/Wind Harmer
2.355
316123AC1-075 GEN
Solar/Wind Harmer
3.235
970165AG2-112 GEN
Solar/Wind Harmer
2.848
970163AG2-111 GEN
Solar/Wind Harmer
2.717
270455AD2-022 GEN
Solar/Wind Harmer
3.531
270457AD2-023 GEN
Solar/Wind Harmer
1.791
970085AG2-068 GEN
Solar/Wind Harmer
9.94
970581AG2-369 GEN
Solar/Wind Harmer
8.549
270069AE2-166 C O1
Solar/Wind Harmer
1.803
971981AH1-535 GEN
Solar/Wind Harmer
4.605
3143316POE
Solar/Wind Helper
0.634
316369SG1_INVT
Solar/Wind Helper
0.701
316132AB2-190 GEN1
Solar/Wind Helper
0.826
957831AF2-077 GEN
Solar/Wind Helper
0.192
319010AE1-072 C
Solar/Wind Helper
1.62
316305AF2-043 C
Solar/Wind Helper
0.189
316349AD2-085 GEN
Solar/Wind Helper
0.637
316233AE1-074 FULL
Solar/Wind Helper
0.211
957601AF2-054 GEN
Solar/Wind Helper
0.183
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.732
315666AE1-190 GEN
Solar/Wind Helper
0.183
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.137
3141913WHIT STONE
Solar/Wind Helper
0.135
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.054
313526AB2-022
Solar/Wind Helper
0.2
316315AB2-025 C
Solar/Wind Helper
0.199
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3141813NORNECK
Solar/Wind Helper
0.128
316312AB1-027
Solar/Wind Helper
0.241
316321Z2-027
Solar/Wind Helper
0.193
3145176PASQUOTANK
Solar/Wind Helper
0.078
316223AC1-118
Solar/Wind Helper
0.184
24728405LEESVG
50/50
0.137
316248AF1-058 C
Solar/Wind Harmer
1.27
960061AF2-297 GEN
Solar/Wind Harmer
21.067
971683AH1-343 GEN
Solar/Wind Harmer
16.042
316283AC2-100 C
Solar/Wind Harmer
2.82
970917AG2-570 GEN
Solar/Wind Harmer
39.759
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.353
270018AE2-047 C O1
Solar/Wind Harmer
1.019
943811AF1-049 GEN
Solar/Wind Harmer
2.868
270336AE1-100 GEN
Solar/Wind Harmer
1.167
971367AH1-164 GEN
Solar/Wind Harmer
1.912
961601AG1-000A GEN
Solar/Wind Harmer
2.784
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.08
316486AD2-202 GEN
Solar/Wind Helper
0.902
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.622
942461AE2-259 GEN
Solar/Wind Helper
1.133
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.205
3145336SMITFLD
Solar/Wind Helper
0.06
316382AG1-145 C
Solar/Wind Helper
0.193
3146456SLIGO L269
Solar/Wind Helper
0.143
316313AB2-026
Solar/Wind Helper
0.213
316258AE1-075 C
Solar/Wind Helper
0.192
316405AF2-144 C
Solar/Wind Helper
0.16
316156AD2-030 GEN
Solar/Wind Helper
0.206
316280AD1-041 GEN
Solar/Wind Helper
0.457
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.254
316320Y1-086
Solar/Wind Helper
0.059
316404AE1-155 C
Solar/Wind Helper
1.1
316473AC1-191 GEN
Solar/Wind Helper
0.746
3141906WESTMOR
Solar/Wind Helper
0.048
316435W1029_GEN3
Solar/Wind Helper
0.485
3146516WINFALL
Solar/Wind Helper
0.117
3152661PLYWOOD A
50/50
0.685
316222AC1-221 GEN
Solar/Wind Harmer
3.1
942751AE2-291 GEN
Solar/Wind Harmer
17.158
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.579
962561AG1-105 GEN
Solar/Wind Harmer
12.783
316217AC1-145 GEN
Solar/Wind Harmer
2.364
316197AC1-042 GEN
Solar/Wind Harmer
1.792
942671AE2-283 GEN
Solar/Wind Harmer
4.824
270013AE1-250 PV
Solar/Wind Harmer
2.226
961601AG1-000A GEN
Solar/Wind Harmer
2.749
316263AC1-034 GEN
Solar/Wind Harmer
3.259
3146776BUCKING
Solar/Wind Helper
0.779
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.235
316316AC1-027 C
Solar/Wind Helper
0.241
3142956BIRDNECK
Solar/Wind Helper
0.103
316185AD1-033 GEN
Solar/Wind Helper
0.715
316236AE1-162_GEN
Solar/Wind Helper
0.202
3145506HICKORY
Solar/Wind Helper
0.599
3145506HICKORY
Solar/Wind Helper
0.359
3145506HICKORY
Solar/Wind Helper
0.09
316240AF1-291 C
Solar/Wind Helper
0.198
316339AD2-160 GEN
Solar/Wind Helper
0.555
316033AB2-134 GEN
Solar/Wind Helper
0.501
315697AD1-025 GEN
Solar/Wind Helper
1.666
316018AA1-139 ULT2
Solar/Wind Helper
0.622
316017AA1-139 ULT1
Solar/Wind Helper
0.661
3137176SLIGO L2192
Solar/Wind Helper
0.569
3130086AYDLETT
Solar/Wind Helper
0.564
3143526WINTERP
Solar/Wind Helper
0.718
3142946ENON
Solar/Wind Helper
0.014
316075AC2-137 C
Solar/Wind Helper
0.201
316487AF1-042 GEN
Solar/Wind Helper
0.133
3146386ELIZ CT
Solar/Wind Helper
0.131
3144356SAPONY
Solar/Wind Helper
0.234
316077AC2-138 C
Solar/Wind Helper
0.12
966871AG1-558 GEN
Solar/Wind Helper
0.165
316431W1029_GEN1
Solar/Wind Helper
0.485
316433W1029_GEN2
Solar/Wind Helper
0.485
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.568
971629AH1-314 GEN
50/50
13.489
3151561HALLBR1
50/50
0.374
24728405LEESVG
50/50
0.136
315687AD1-152 GEN
Solar/Wind Harmer
8.943
316003AC1-222 GEN
Solar/Wind Harmer
3.856
970401AG2-262 GEN
Solar/Wind Harmer
1.705
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.91
970919AG2-571 GEN
Solar/Wind Harmer
5.033
970223AG2-152 GEN
Solar/Wind Harmer
13.358
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.461
270016AE1-250 BESS
Solar/Wind Harmer
2.226
270574AD1-017 GEN2
Solar/Wind Harmer
4.502
270030AE2-140 GEN
Solar/Wind Harmer
14.747
270173AC1-122 GEN
Solar/Wind Harmer
1.038
316359AB2-059 GEN
Solar/Wind Harmer
0.937
316049AB1-081 GEN
Solar/Wind Harmer
0.75
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Helper
0.145
316322AB2-045
Solar/Wind Helper
0.217
3146776BUCKING
Solar/Wind Helper
0.078
316294AC1-161 GEN
Solar/Wind Helper
3.077
316375AC2-012 GEN
Solar/Wind Helper
0.404
3145336SMITFLD
Solar/Wind Helper
0.602
316381AD1-082 GEN
Solar/Wind Helper
0.757
316388AE2-253 GEN
Solar/Wind Helper
0.555
316458AB2-190 GEN2
Solar/Wind Helper
0.826
316159AE1-175 C
Solar/Wind Helper
0.218
3146456SLIGO L269
Solar/Wind Helper
0.143
316072AD1-144
Solar/Wind Helper
0.163
3143226MDLTHAN
Solar/Wind Helper
0.141
316246AF1-032 C
Solar/Wind Helper
0.161
316336AC2-165 C
Solar/Wind Helper
0.752
3143526WINTERP
Solar/Wind Helper
0.718
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.545
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.081
964211AG1-282 GEN
Solar/Wind Helper
0.173
3141726DUNNSVL
Solar/Wind Helper
0.513
3142416OLDCHRC
Solar/Wind Helper
0.33
3142416OLDCHRC
Solar/Wind Helper
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.188
3146516WINFALL
Solar/Wind Helper
0.38
3146516WINFALL
Solar/Wind Helper
0.117
NYPJM->LTFIMP_NY
CLTF
0.755
LGEELTFEXP_LGEE->PJM
CLTF
1.98
LAGNLTFEXP_LAGN->PJM
CLTF
9.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.294
WECLTFEXP_WEC->PJM
CLTF
1.048
TVALTFEXP_TVA->PJM
CLTF
4.607
CPLELTFEXP_CPLE->PJM
CLTF
11.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.541
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.067
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.134
MECLTFEXP_MEC->PJM
CLTF
5.224
SIGELTFEXP_SIGE->PJM
CLTF
0.159

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.64 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:885.41
MW Contribution:6.54
Bus #Bus NameTypeMW Contribution
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
970917AG2-570 GEN
Solar/Wind Harmer
12.67
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970919AG2-571 GEN
Solar/Wind Harmer
5.068
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
NYPJM->LTFIMP_NY
CLTF
0.706
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
LGEELTFEXP_LGEE->PJM
CLTF
2.033
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.47 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:867.67
MW Contribution:6.54
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.899
24684705SMG5
50/50
0.33
970481AG2-311 GEN
50/50
4.594
315687AD1-152 GEN
Solar/Wind Harmer
0.022
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.37
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.404
970223AG2-152 GEN
Solar/Wind Harmer
9.437
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.18
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.396
270173AC1-122 GEN
Solar/Wind Harmer
0.217
316359AB2-059 GEN
Solar/Wind Harmer
0.226
316049AB1-081 GEN
Solar/Wind Harmer
0.36
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.862
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.042
971683AH1-343 GEN
Solar/Wind Harmer
12.22
316283AC2-100 C
Solar/Wind Harmer
0.523
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.18
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.353
961601AG1-000A GEN
Solar/Wind Harmer
4.498
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.778
316118AC1-105 GEN
Solar/Wind Harmer
0.789
316123AC1-075 GEN
Solar/Wind Harmer
0.366
970165AG2-112 GEN
Solar/Wind Harmer
2.171
970163AG2-111 GEN
Solar/Wind Harmer
2.071
970085AG2-068 GEN
Solar/Wind Harmer
7.603
970581AG2-369 GEN
Solar/Wind Harmer
6.538
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.177
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
3152661PLYWOOD A
50/50
0.687
24684405SMG2
50/50
0.856
24684505SMG3
50/50
0.529
24684305SMG1
50/50
0.31
316222AC1-221 GEN
Solar/Wind Harmer
1.136
942751AE2-291 GEN
Solar/Wind Harmer
13.086
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.482
962561AG1-105 GEN
Solar/Wind Harmer
9.757
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.251
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.124
316263AC1-034 GEN
Solar/Wind Harmer
2.389
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6EDMONSON-6BLACK WALNU 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:998.97
MW Contribution:8.61
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.192
316118AC1-105 GEN
Solar/Wind Harmer
2.363
316123AC1-075 GEN
Solar/Wind Harmer
3.247
970165AG2-112 GEN
Solar/Wind Harmer
2.859
970163AG2-111 GEN
Solar/Wind Harmer
2.727
270455AD2-022 GEN
Solar/Wind Harmer
3.551
270457AD2-023 GEN
Solar/Wind Harmer
1.801
970085AG2-068 GEN
Solar/Wind Harmer
10.01
970581AG2-369 GEN
Solar/Wind Harmer
8.609
270069AE2-166 C O1
Solar/Wind Harmer
1.824
971981AH1-535 GEN
Solar/Wind Harmer
4.681
3143316POE
Solar/Wind Helper
0.626
316369SG1_INVT
Solar/Wind Helper
0.691
316132AB2-190 GEN1
Solar/Wind Helper
0.815
957831AF2-077 GEN
Solar/Wind Helper
0.189
319010AE1-072 C
Solar/Wind Helper
1.597
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.628
316233AE1-074 FULL
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.18
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.721
315666AE1-190 GEN
Solar/Wind Helper
0.18
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.135
3141913WHIT STONE
Solar/Wind Helper
0.133
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.196
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.126
971629AH1-314 GEN
50/50
13.578
3151561HALLBR1
50/50
0.376
24728405LEESVG
50/50
0.138
315687AD1-152 GEN
Solar/Wind Harmer
8.957
316003AC1-222 GEN
Solar/Wind Harmer
3.867
970401AG2-262 GEN
Solar/Wind Harmer
1.712
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
15.015
970919AG2-571 GEN
Solar/Wind Harmer
5.068
970223AG2-152 GEN
Solar/Wind Harmer
13.457
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.503
270016AE1-250 BESS
Solar/Wind Harmer
2.243
270574AD1-017 GEN2
Solar/Wind Harmer
4.541
270030AE2-140 GEN
Solar/Wind Harmer
14.9
270173AC1-122 GEN
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.952
316049AB1-081 GEN
Solar/Wind Harmer
0.762
3142053HEARTS
Solar/Wind Harmer
0.083
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146926FARMVIL
Solar/Wind Helper
0.144
316322AB2-045
Solar/Wind Helper
0.215
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.041
316375AC2-012 GEN
Solar/Wind Helper
0.399
3145336SMITFLD
Solar/Wind Helper
0.594
316381AD1-082 GEN
Solar/Wind Helper
0.747
316388AE2-253 GEN
Solar/Wind Helper
0.548
316458AB2-190 GEN2
Solar/Wind Helper
0.815
316159AE1-175 C
Solar/Wind Helper
0.215
3146456SLIGO L269
Solar/Wind Helper
0.141
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.139
316246AF1-032 C
Solar/Wind Helper
0.159
316336AC2-165 C
Solar/Wind Helper
0.741
3143526WINTERP
Solar/Wind Helper
0.708
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.538
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.17
3141726DUNNSVL
Solar/Wind Helper
0.505
3142416OLDCHRC
Solar/Wind Helper
0.325
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.185
24728405LEESVG
50/50
0.138
316248AF1-058 C
Solar/Wind Harmer
1.273
960061AF2-297 GEN
Solar/Wind Harmer
21.123
971683AH1-343 GEN
Solar/Wind Harmer
16.09
316283AC2-100 C
Solar/Wind Harmer
2.83
970917AG2-570 GEN
Solar/Wind Harmer
40.038
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.503
270197AD1-017 GEN1
Solar/Wind Harmer
1.364
270018AE2-047 C O1
Solar/Wind Harmer
1.028
943811AF1-049 GEN
Solar/Wind Harmer
2.896
270336AE1-100 GEN
Solar/Wind Harmer
1.18
971367AH1-164 GEN
Solar/Wind Harmer
1.939
961601AG1-000A GEN
Solar/Wind Harmer
2.829
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.07
316486AD2-202 GEN
Solar/Wind Helper
0.899
3146926FARMVIL
Solar/Wind Helper
0.144
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.58
942461AE2-259 GEN
Solar/Wind Helper
1.12
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.202
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.191
3146456SLIGO L269
Solar/Wind Helper
0.141
316313AB2-026
Solar/Wind Helper
0.21
316258AE1-075 C
Solar/Wind Helper
0.189
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.203
316280AD1-041 GEN
Solar/Wind Helper
0.451
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.25
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.083
316473AC1-191 GEN
Solar/Wind Helper
0.734
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
316312AB1-027
Solar/Wind Helper
0.238
316321Z2-027
Solar/Wind Helper
0.19
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.181
3146516WINFALL
Solar/Wind Helper
0.373
3146516WINFALL
Solar/Wind Helper
0.115
3152661PLYWOOD A
50/50
0.687
316222AC1-221 GEN
Solar/Wind Harmer
3.111
942751AE2-291 GEN
Solar/Wind Harmer
17.229
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.603
962561AG1-105 GEN
Solar/Wind Harmer
12.846
316217AC1-145 GEN
Solar/Wind Harmer
2.382
316197AC1-042 GEN
Solar/Wind Harmer
1.806
942671AE2-283 GEN
Solar/Wind Harmer
4.861
270013AE1-250 PV
Solar/Wind Harmer
2.243
961601AG1-000A GEN
Solar/Wind Harmer
2.793
316263AC1-034 GEN
Solar/Wind Harmer
3.311
3146776BUCKING
Solar/Wind Helper
0.771
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.232
3142956BIRDNECK
Solar/Wind Helper
0.102
316316AC1-027 C
Solar/Wind Helper
0.238
316185AD1-033 GEN
Solar/Wind Helper
0.706
316236AE1-162_GEN
Solar/Wind Helper
0.2
3145506HICKORY
Solar/Wind Helper
0.591
3145506HICKORY
Solar/Wind Helper
0.355
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.195
316339AD2-160 GEN
Solar/Wind Helper
0.548
316033AB2-134 GEN
Solar/Wind Helper
0.494
315697AD1-025 GEN
Solar/Wind Helper
1.643
316018AA1-139 ULT2
Solar/Wind Helper
0.614
316017AA1-139 ULT1
Solar/Wind Helper
0.652
3137176SLIGO L2192
Solar/Wind Helper
0.561
3130086AYDLETT
Solar/Wind Helper
0.556
3143526WINTERP
Solar/Wind Helper
0.708
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.198
316487AF1-042 GEN
Solar/Wind Helper
0.131
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.23
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.162
316431W1029_GEN1
Solar/Wind Helper
0.477
316433W1029_GEN2
Solar/Wind Helper
0.477
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.559
NYPJM->LTFIMP_NY
CLTF
0.706
LGEELTFEXP_LGEE->PJM
CLTF
2.033
LAGNLTFEXP_LAGN->PJM
CLTF
9.357
WECLTFEXP_WEC->PJM
CLTF
1.077
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.525
TVALTFEXP_TVA->PJM
CLTF
4.684
CPLELTFEXP_CPLE->PJM
CLTF
11.235
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.18
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.424
MECLTFEXP_MEC->PJM
CLTF
5.352
SIGELTFEXP_SIGE->PJM
CLTF
0.163

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:167.04 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:934.25
MW Contribution:3.75
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.3
3151601KERR 3
50/50
0.315
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.233
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.302
3151021BRUNSWICKG1
50/50
1.109
971451AH1-221 GEN
50/50
3.369
315243AE2-183_GT3
50/50
1.358
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.938
971563AH1-280 GEN
Solar/Wind Harmer
3.876
970685AG2-442 GEN
Solar/Wind Harmer
24.484
962491AG1-098 GEN
Solar/Wind Harmer
11.925
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.548
970401AG2-262 GEN
Solar/Wind Harmer
0.937
957481AF2-042 GEN
Solar/Wind Harmer
40.4
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.034
970535AG2-341 GEN
50/50
3.152
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.109
972187AH1-678 GEN
50/50
2.545
315242AE2-183_GT2
50/50
1.358
315241AE2-183_GT1
50/50
1.35
972185AH1-677 GEN
50/50
4.896
970533AG2-339 GEN
50/50
6.901
970531AG2-338 GEN
50/50
2.76
3151361ROSEMG1
50/50
0.261
3151371ROSEMS1
50/50
0.162
3151381ROSEMG2
50/50
0.122
970301AG2-198 GEN
Solar/Wind Harmer
16.784
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.361
963191AG1-168 GEN
Solar/Wind Harmer
1.454
971741AH1-377 GEN
Solar/Wind Harmer
34.597
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.383
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
8.006
939181AE1-148 GEN
Solar/Wind Harmer
7.768
964791AG1-342 GEN
Solar/Wind Harmer
3.068
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.16
970933AG2-581 GEN
Solar/Wind Harmer
8.957
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.539
3145783HORNRTN
Solar/Wind Harmer
1.231
3145783HORNRTN
Solar/Wind Harmer
0.385
3145783HORNRTN
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.286
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.402
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
942751AE2-291 GEN
Solar/Wind Harmer
3.947
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.473
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.657
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.227
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.702
316129AC1-054 GEN
Solar/Wind Harmer
0.489
971795AH1-408 GEN
Solar/Wind Harmer
7.855
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.916
970087AG2-069 GEN
Solar/Wind Harmer
6.541
316212AC1-099_GEN
Solar/Wind Harmer
0.387
3146263WOODLND
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.327
316023GEN1_S
Solar/Wind Harmer
0.164
962571AG1-106 GEN
Solar/Wind Harmer
1.039
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.286
3145893MURPHYS
Solar/Wind Harmer
0.283
3145893MURPHYS
Solar/Wind Harmer
0.314
315722AD1-056 GEN
Solar/Wind Harmer
0.447
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.251
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.4
3151591KERR 2
50/50
0.315
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.109
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.196
3147133PAMPLIN
Solar/Wind Harmer
1.218
971193AH1-056 GEN
Solar/Wind Harmer
23.635
963181AG1-167 GEN
Solar/Wind Harmer
1.454
959311AF2-222 GEN
Solar/Wind Harmer
26.76
970257AG2-171 GEN
Solar/Wind Harmer
9.287
315785AD2-033 C
Solar/Wind Harmer
2.238
964241AG1-285 GEN
Solar/Wind Harmer
15.712
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.403
971683AH1-343 GEN
Solar/Wind Harmer
4.014
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.162
970917AG2-570 GEN
Solar/Wind Harmer
7.29
316210AC1-098 GEN
Solar/Wind Harmer
0.693
316327AA2-057 GEN
Solar/Wind Harmer
0.111
316049AB1-081 GEN
Solar/Wind Harmer
0.4
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
940641AE2-051 GEN
Solar/Wind Harmer
5.396
316494AC1-189 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.923
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
971547AH1-271 GEN
Solar/Wind Harmer
1.316
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.641
316322AB2-045
Solar/Wind Helper
0.957
3146776BUCKING
Solar/Wind Helper
0.343
316336AC2-165 C
Solar/Wind Helper
1.513
3146263WOODLND
Solar/Wind Harmer
0.074
316365GEN2_N
Solar/Wind Harmer
0.164
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.361
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.265
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.233
961681AG1-008 GEN
Solar/Wind Harmer
5.233
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.14
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.909
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.733
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3156021HOLLOMANSOL
Solar/Wind Harmer
0.291
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.744
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
315737AD1-076 GEN
Solar/Wind Harmer
0.772
971157AH1-035 GEN
Solar/Wind Harmer
0.716
315614AA2-178 GEN
Solar/Wind Harmer
0.332
3145273HOLLAND
Solar/Wind Harmer
0.043
3146776BUCKING
Solar/Wind Helper
0.309
316313AB2-026
Solar/Wind Helper
0.361
316258AE1-075 C
Solar/Wind Helper
0.325
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3145603CNETO
Solar/Wind Harmer
0.063
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.517
316065AD1-022 GEN
Solar/Wind Harmer
2.811
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
3.433
3146776BUCKING
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.985
3151541CLOVER2
50/50
3.284
3151611KERR 4
50/50
0.315
3151621KERR 5
50/50
0.315
3151631KERR 6
50/50
0.315
3151641KERR 7
50/50
0.315
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.246
315244AE2-183_ST
50/50
2.348
315657AE1-056 GEN
Solar/Wind Harmer
13.387
946301AF1-294 GEN
Solar/Wind Harmer
7.171
961791AG1-021 GEN
Solar/Wind Harmer
3.489
970683AG2-441 GEN
Solar/Wind Harmer
21.861
970681AG2-440 GEN
Solar/Wind Harmer
17.489
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.821
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.369
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.372
970865AG2-541 GEN
Solar/Wind Harmer
3.489
971967AH1-528 GEN
Solar/Wind Harmer
15.071
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.359
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.361
970581AG2-369 GEN
Solar/Wind Harmer
3.75
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.208
970673AG2-436 GEN
Solar/Wind Harmer
11.472
941031AE2-094 GEN
Solar/Wind Harmer
14.299
944011AF1-069 GEN
Solar/Wind Harmer
4.672
315652AC1-086 GEN
Solar/Wind Harmer
8.029
3146033SCOT NK
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.32
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.191
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.144
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.854
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
970181AG2-120 GEN
Solar/Wind Harmer
0.805
315814AE2-033 C
Solar/Wind Harmer
4.945
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.062
970601AG2-382 GEN
Solar/Wind Harmer
2.302
315732AD1-074 GEN1
Solar/Wind Harmer
0.345
315733AD1-074 GEN2
Solar/Wind Harmer
0.345
315735AD1-075 GEN1
Solar/Wind Harmer
0.173
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
0.249
270494AE1-108_GEN
Solar/Wind Helper
4.45
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
NYPJM->LTFIMP_NY
CLTF
0.48
LGEELTFEXP_LGEE->PJM
CLTF
0.362
LAGNLTFEXP_LAGN->PJM
CLTF
2.753
WECLTFEXP_WEC->PJM
CLTF
0.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.143
TVALTFEXP_TVA->PJM
CLTF
1.358
CPLELTFEXP_CPLE->PJM
CLTF
4.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.539
MECLTFEXP_MEC->PJM
CLTF
1.12
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:812.65
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
WECLTFEXP_WEC->PJM
CLTF
0.123
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.25 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:788.33
MW Contribution:3.62
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
WECLTFEXP_WEC->PJM
CLTF
0.133
TVALTFEXP_TVA->PJM
CLTF
1.025
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P2-2: ALTAVISTA 115KV_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: ALTAVISTA 115KV_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.26 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:774.73
MW Contribution:3.6
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.203
3144293JTRSVLE
50/50
1.013
970535AG2-341 GEN
50/50
2.978
3152661PLYWOOD A
50/50
0.306
970301AG2-198 GEN
Solar/Wind Harmer
21.525
3147133PAMPLIN
Solar/Wind Harmer
-0.043
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.252
963191AG1-168 GEN
Solar/Wind Harmer
3.751
971741AH1-377 GEN
Solar/Wind Harmer
44.063
316034AC1-036 C
Solar/Wind Harmer
0.59
970323AG2-213 GEN
Solar/Wind Harmer
15.873
971775AH1-396 GEN
Solar/Wind Harmer
2.26
313527AB2-043 GEN
Solar/Wind Harmer
3.607
962561AG1-105 GEN
Solar/Wind Harmer
10.348
964791AG1-342 GEN
Solar/Wind Harmer
3.783
3146843MT LREL
Solar/Wind Harmer
-0.018
3146843MT LREL
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.553
970099AG2-077 GEN
Solar/Wind Harmer
18.881
942751AE2-291 GEN
Solar/Wind Harmer
9.226
970933AG2-581 GEN
Solar/Wind Harmer
9.531
316181AB2-040 GEN
Solar/Wind Harmer
1.209
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
316222AC1-221 GEN
Solar/Wind Harmer
0.828
3145783HORNRTN
Solar/Wind Harmer
0.962
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316426AA2-053 GEN
Solar/Wind Harmer
0.796
316274AC1-208 GEN
Solar/Wind Harmer
0.764
972187AH1-678 GEN
Adder
1.732
972185AH1-677 GEN
Adder
3.271
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.456
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.97
3144293JTRSVLE
50/50
1.203
3151591KERR 2
50/50
0.292
970413AG2-270 GEN
50/50
13.01
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.625
970909AG2-566 GEN
Solar/Wind Harmer
4.087
3147133PAMPLIN
Solar/Wind Harmer
-0.134
971193AH1-056 GEN
Solar/Wind Harmer
26.755
963181AG1-167 GEN
Solar/Wind Harmer
3.751
959311AF2-222 GEN
Solar/Wind Harmer
34.411
970257AG2-171 GEN
Solar/Wind Harmer
11.905
315785AD2-033 C
Solar/Wind Harmer
6.813
964241AG1-285 GEN
Solar/Wind Harmer
19.989
316131AB2-060 GEN
Solar/Wind Harmer
2.467
316478AD1-087 GEN
Solar/Wind Harmer
1.354
316486AD2-202 GEN
Solar/Wind Harmer
0.396
971683AH1-343 GEN
Solar/Wind Harmer
6.24
316248AF1-058 C
Solar/Wind Harmer
0.436
960061AF2-297 GEN
Solar/Wind Harmer
7.234
3147043LAWRENC
Solar/Wind Harmer
-0.008
966621AG1-532 GEN
Solar/Wind Harmer
0.182
313506AB2-031 GEN
Solar/Wind Harmer
0.697
316283AC2-100 C
Solar/Wind Harmer
0.759
316210AC1-098 GEN
Solar/Wind Harmer
1.062
970917AG2-570 GEN
Solar/Wind Harmer
16.773
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
316365GEN2_N
Solar/Wind Harmer
0.431
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.334
316258AE1-075 C
Solar/Wind Helper
0.3
316405AF2-144 C
Solar/Wind Helper
0.25
3148013FISHERV
Solar/Wind Helper
0.123
3144293JTRSVLE
50/50
1.203
3151601KERR 3
50/50
0.292
3151581KERR 1
50/50
0.104
3151531CLOVER1
50/50
2.981
3147043LAWRENC
50/50
1.112
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
5.001
971563AH1-280 GEN
Solar/Wind Harmer
5.001
970685AG2-442 GEN
Solar/Wind Harmer
31.502
962491AG1-098 GEN
Solar/Wind Harmer
14.564
316237AB2-079_GEN
Solar/Wind Harmer
0.652
315693AD1-088 GEN
Solar/Wind Harmer
10.309
970401AG2-262 GEN
Solar/Wind Harmer
1.156
957481AF2-042 GEN
Solar/Wind Harmer
47.203
3147123OTTER R
Solar/Wind Harmer
-0.009
316003AC1-222 GEN
Solar/Wind Harmer
1.413
315687AD1-152 GEN
Solar/Wind Harmer
1.721
971065AG2-659 GEN
Solar/Wind Harmer
6.825
316129AC1-054 GEN
Solar/Wind Harmer
1.158
971795AH1-408 GEN
Solar/Wind Harmer
8.808
960081AF2-299 GEN
Solar/Wind Harmer
1.012
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.59
970919AG2-571 GEN
Solar/Wind Harmer
2.123
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.357
962571AG1-106 GEN
Solar/Wind Harmer
0.932
3146233WITAKRS
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
316023GEN1_S
Solar/Wind Harmer
0.431
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.345
316336AC2-165 C
Solar/Wind Helper
1.43
3151611KERR 4
50/50
0.292
3151621KERR 5
50/50
0.292
3151631KERR 6
50/50
0.292
3151641KERR 7
50/50
0.292
3151541CLOVER2
50/50
2.967
315657AE1-056 GEN
Solar/Wind Harmer
16.053
946301AF1-294 GEN
Solar/Wind Harmer
10.253
961791AG1-021 GEN
Solar/Wind Harmer
5.001
970683AG2-441 GEN
Solar/Wind Harmer
28.127
970681AG2-440 GEN
Solar/Wind Harmer
22.501
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.178
316239AB2-077_GEN
Solar/Wind Harmer
0.652
316238AB2-078_GEN
Solar/Wind Harmer
0.652
316118AC1-105 GEN
Solar/Wind Harmer
1.105
316123AC1-075 GEN
Solar/Wind Harmer
1.561
970165AG2-112 GEN
Solar/Wind Harmer
1.375
970163AG2-111 GEN
Solar/Wind Harmer
1.311
970865AG2-541 GEN
Solar/Wind Harmer
5.879
3147173SINAI
Solar/Wind Harmer
-0.014
3147243WELCO
Solar/Wind Harmer
-0.009
970831AG2-522 GEN
Solar/Wind Harmer
6.369
946281AF1-292 GEN
Solar/Wind Harmer
0.201
316087AB2-174 GEN
Solar/Wind Harmer
1.25
3137643SOCKMAN
Solar/Wind Harmer
-0.034
971967AH1-528 GEN
Solar/Wind Harmer
14.997
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146033SCOT NK
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
7.298
316319Z2-044 C
Solar/Wind Harmer
0.358
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.567
970673AG2-436 GEN
Solar/Wind Harmer
13.3
970673AG2-436 GEN
Solar/Wind Harmer
6.734
270494AE1-108_GEN
Solar/Wind Helper
4.519
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
NYPJM->LTFIMP_NY
CLTF
0.29
LGEELTFEXP_LGEE->PJM
CLTF
0.201
LAGNLTFEXP_LAGN->PJM
CLTF
1.949
WECLTFEXP_WEC->PJM
CLTF
0.107
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.898
TVALTFEXP_TVA->PJM
CLTF
0.953
CPLELTFEXP_CPLE->PJM
CLTF
3.953
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.193
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.695
SIGELTFEXP_SIGE->PJM
CLTF
0.019

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 249-69_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 249-69_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:110.96 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:758.97
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.187
3151591KERR 2
50/50
0.282
970413AG2-270 GEN
50/50
12.638
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.566
970909AG2-566 GEN
Solar/Wind Harmer
4.057
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.448
963181AG1-167 GEN
Solar/Wind Harmer
3.702
959311AF2-222 GEN
Solar/Wind Harmer
33.775
970257AG2-171 GEN
Solar/Wind Harmer
11.671
315785AD2-033 C
Solar/Wind Harmer
6.667
964241AG1-285 GEN
Solar/Wind Harmer
19.444
316131AB2-060 GEN
Solar/Wind Harmer
2.388
316478AD1-087 GEN
Solar/Wind Harmer
1.315
316486AD2-202 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.378
960061AF2-297 GEN
Solar/Wind Harmer
6.277
971683AH1-343 GEN
Solar/Wind Harmer
4.637
966621AG1-532 GEN
Solar/Wind Harmer
0.181
313506AB2-031 GEN
Solar/Wind Harmer
0.687
316283AC2-100 C
Solar/Wind Harmer
0.728
316210AC1-098 GEN
Solar/Wind Harmer
1.043
970917AG2-570 GEN
Solar/Wind Harmer
16.563
316327AA2-057 GEN
Solar/Wind Harmer
0.663
316365GEN2_N
Solar/Wind Harmer
0.436
3146263WOODLND
Solar/Wind Harmer
-0.006
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.34
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.282
3151621KERR 5
50/50
0.282
3151631KERR 6
50/50
0.282
3151641KERR 7
50/50
0.282
3151541CLOVER2
50/50
2.882
315657AE1-056 GEN
Solar/Wind Harmer
15.869
946301AF1-294 GEN
Solar/Wind Harmer
10.118
961791AG1-021 GEN
Solar/Wind Harmer
4.936
970683AG2-441 GEN
Solar/Wind Harmer
27.679
3144293JTRSVLE
50/50
1.187
3144293JTRSVLE
50/50
1
970535AG2-341 GEN
50/50
2.881
3152661PLYWOOD A
50/50
0.273
970301AG2-198 GEN
Solar/Wind Harmer
21.369
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.17
963191AG1-168 GEN
Solar/Wind Harmer
3.702
971741AH1-377 GEN
Solar/Wind Harmer
43.69
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.561
971775AH1-396 GEN
Solar/Wind Harmer
2.216
313527AB2-043 GEN
Solar/Wind Harmer
3.487
962561AG1-105 GEN
Solar/Wind Harmer
9.606
939181AE1-148 GEN
Solar/Wind Harmer
9.243
964791AG1-342 GEN
Solar/Wind Harmer
3.479
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.458
970933AG2-581 GEN
Solar/Wind Harmer
9.37
316181AB2-040 GEN
Solar/Wind Harmer
1.193
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.917
3145593CAROLNA
Solar/Wind Harmer
0.068
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.756
3145783HORNRTN
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
0.094
316222AC1-221 GEN
Solar/Wind Harmer
0.793
316426AA2-053 GEN
Solar/Wind Harmer
0.781
942751AE2-291 GEN
Solar/Wind Harmer
4.462
316274AC1-208 GEN
Solar/Wind Harmer
0.751
972187AH1-678 GEN
Adder
1.711
972185AH1-677 GEN
Adder
3.235
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.472
970681AG2-440 GEN
Solar/Wind Harmer
22.144
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.054
316239AB2-077_GEN
Solar/Wind Harmer
0.629
316238AB2-078_GEN
Solar/Wind Harmer
0.629
316118AC1-105 GEN
Solar/Wind Harmer
0.99
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.188
970865AG2-541 GEN
Solar/Wind Harmer
4.016
946281AF1-292 GEN
Solar/Wind Harmer
0.2
316087AB2-174 GEN
Solar/Wind Harmer
1.235
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316123AC1-075 GEN
Solar/Wind Harmer
0.876
970165AG2-112 GEN
Solar/Wind Harmer
0.771
970163AG2-111 GEN
Solar/Wind Harmer
0.736
971967AH1-528 GEN
Solar/Wind Harmer
14.788
315607AA1-063A GEN
Solar/Wind Harmer
0.747
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.132
970581AG2-369 GEN
Solar/Wind Harmer
3.554
315652AC1-086 GEN
Solar/Wind Harmer
7.265
3146033SCOT NK
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
316319Z2-044 C
Solar/Wind Harmer
0.352
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.98
3144293JTRSVLE
50/50
1.187
3151601KERR 3
50/50
0.282
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.896
3147043LAWRENC
50/50
1.087
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.936
971563AH1-280 GEN
Solar/Wind Harmer
4.936
970685AG2-442 GEN
Solar/Wind Harmer
31.001
962491AG1-098 GEN
Solar/Wind Harmer
14.334
316237AB2-079_GEN
Solar/Wind Harmer
0.629
315693AD1-088 GEN
Solar/Wind Harmer
10.136
970401AG2-262 GEN
Solar/Wind Harmer
1.063
957481AF2-042 GEN
Solar/Wind Harmer
46.146
315687AD1-152 GEN
Solar/Wind Harmer
1.644
971065AG2-659 GEN
Solar/Wind Harmer
6.622
316129AC1-054 GEN
Solar/Wind Harmer
1.124
316003AC1-222 GEN
Solar/Wind Harmer
1.132
971795AH1-408 GEN
Solar/Wind Harmer
8.642
960081AF2-299 GEN
Solar/Wind Harmer
1.002
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
316212AC1-099_GEN
Solar/Wind Harmer
0.579
970919AG2-571 GEN
Solar/Wind Harmer
2.097
970087AG2-069 GEN
Solar/Wind Harmer
6.198
316023GEN1_S
Solar/Wind Harmer
0.436
3146263WOODLND
Solar/Wind Harmer
-0.006
316011AB1-132 GEN
Solar/Wind Harmer
1.351
962571AG1-106 GEN
Solar/Wind Harmer
0.928
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.451
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.244
LAGNLTFEXP_LAGN->PJM
CLTF
2.044
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.87
WECLTFEXP_WEC->PJM
CLTF
0.129
TVALTFEXP_TVA->PJM
CLTF
1.005
CPLELTFEXP_CPLE->PJM
CLTF
3.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.9
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.333
MECLTFEXP_MEC->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for 6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.32 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:566.67
MW Contribution:2.61
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
NYPJM->LTFIMP_NY
CLTF
0.298
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:196.14 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:1331.14
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
NYPJM->LTFIMP_NY
CLTF
0.616
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
LGEELTFEXP_LGEE->PJM
CLTF
0.137
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.37
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
WECLTFEXP_WEC->PJM
CLTF
0.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.57 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1515.34
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
NYPJM->LTFIMP_NY
CLTF
0.612
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:4.2
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
NYPJM->LTFIMP_NY
CLTF
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:175.31 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:1455.08
MW Contribution:4.2
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.33 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:990.47
MW Contribution:3.48
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
NYPJM->LTFIMP_NY
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589
CPLELTFEXP_CPLE->PJM
CLTF
3.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.39 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:974.31
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
NYPJM->LTFIMP_NY
CLTF
0.42
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571
CPLELTFEXP_CPLE->PJM
CLTF
3.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.5 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:933.78
MW Contribution:3.44
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
NYPJM->LTFIMP_NY
CLTF
0.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757
CPLELTFEXP_CPLE->PJM
CLTF
3.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:198.54 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1313.88
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.1
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
WECLTFEXP_WEC->PJM
CLTF
0.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:185.18 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1498.08
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
NYPJM->LTFIMP_NY
CLTF
0.612
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
LGEELTFEXP_LGEE->PJM
CLTF
0.133
WECLTFEXP_WEC->PJM
CLTF
0.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:4.2
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:177.73 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1437.82
MW Contribution:4.2
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
NYPJM->LTFIMP_NY
CLTF
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.29 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:973.17
MW Contribution:3.48
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
NYPJM->LTFIMP_NY
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589
CPLELTFEXP_CPLE->PJM
CLTF
3.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.3 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:957.01
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
NYPJM->LTFIMP_NY
CLTF
0.42
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571
CPLELTFEXP_CPLE->PJM
CLTF
3.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:113.29 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:916.48
MW Contribution:3.44
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
NYPJM->LTFIMP_NY
CLTF
0.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757
CPLELTFEXP_CPLE->PJM
CLTF
3.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for 6LDYSMITH CT-6SUMMIT 230.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6LDYSMITH CT-6SUMMIT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.94 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2459.12
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
972197AH1-683 GEN
50/50
6.75
972219AH1-694 GEN
50/50
4.86
315052AA1-145 CT2
50/50
1.183
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.37
3143526WINTERP
Solar/Wind Harmer
-0.046
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.327
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315671AE2-027_GEN
Solar/Wind Harmer
6.265
944631AF1-128 GEN
Adder
35.154
970129AG2-093 GEN
Solar/Wind Harmer
1.876
316458AB2-190 GEN2
Solar/Wind Harmer
0.831
971069AG2-661 GEN
Solar/Wind Harmer
1.286
970659AG2-427 GEN
Solar/Wind Harmer
4.257
971647AH1-324 GEN
Solar/Wind Harmer
4
316381AD1-082 GEN
Solar/Wind Harmer
0.733
970661AG2-428 GEN
Solar/Wind Harmer
8.426
961611AG1-000B GEN
Solar/Wind Harmer
3.913
316294AC1-161 GEN
Solar/Wind Harmer
2.543
3151171GRAVELC
Adder
0.742
3145336SMITFLD
Solar/Wind Harmer
-0.031
944591AF1-124 GEN
Solar/Wind Harmer
35.438
316375AC2-012 GEN
Solar/Wind Harmer
2.685
3150981CHESPKA
Adder
0.862
939411AE1-173 GEN
Solar/Wind Harmer
38.501
316388AE2-253 GEN
Solar/Wind Harmer
0.519
940641AE2-051 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.155
316093AE2-104_GEN
Solar/Wind Harmer
2.222
316072AD1-144
Solar/Wind Harmer
0.154
3143336POWHATN
Solar/Wind Harmer
0.906
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.83
316159AE1-175 C
Solar/Wind Harmer
0.197
316336AC2-165 C
Solar/Wind Harmer
1.276
3130156CHOWAN
Solar/Wind Harmer
-0.007
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.74
316023GEN1_S
Solar/Wind Harmer
0.478
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.75
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.208
970919AG2-571 GEN
Solar/Wind Harmer
2.21
970087AG2-069 GEN
Solar/Wind Harmer
6.524
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
36.745
960081AF2-299 GEN
Solar/Wind Harmer
0.777
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
971317AH1-138 GEN
Solar/Wind Harmer
0.852
316011AB1-132 GEN
Solar/Wind Harmer
1.421
962571AG1-106 GEN
Solar/Wind Harmer
0.977
971795AH1-408 GEN
Solar/Wind Harmer
5.082
3145963POPLR C
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
21.138
316190AA2-174 GEN
Solar/Wind Harmer
0.083
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
1.035
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
315693AD1-088 GEN
Solar/Wind Harmer
3.339
962491AG1-098 GEN
Solar/Wind Harmer
4.459
970937AG2-583 GEN
Solar/Wind Harmer
4.746
316212AC1-099_GEN
Solar/Wind Harmer
0.57
3146293MARTNCO
Solar/Wind Harmer
0.04
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.207
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315722AD1-056 GEN
Solar/Wind Harmer
0.667
316337AD2-073 GEN
Solar/Wind Helper
0.174
3150411LDYSMT5
50/50
43.365
3150381LDYSMT2
50/50
41.502
972213AH1-691 GEN
50/50
7.02
972215AH1-692 GEN
50/50
7.02
963051AG1-154 GEN
50/50
5.4
972189AH1-679 GEN
50/50
2.64
316312AB1-027
Solar/Wind Harmer
0.323
971285AH1-108 GEN
Adder
0.606
316233AE1-074 FULL
Solar/Wind Harmer
0.24
971281AH1-106 GEN
Solar/Wind Harmer
1.451
971283AH1-107 GEN
Solar/Wind Harmer
1.451
316132AB2-190 GEN1
Solar/Wind Harmer
0.831
3143316POE
Solar/Wind Harmer
-0.032
316369SG1_INVT
Solar/Wind Harmer
1.442
972265AH1-717 GEN
Adder
5.416
3151201GRAVEL4
Adder
5.077
3151191GRAVEL3
Adder
5.013
3151211GRAVEL5
Adder
5.013
971445AH1-216 GEN
Solar/Wind Harmer
4.834
315833AF1-017_GEN
Solar/Wind Harmer
1.477
316349AD2-085 GEN
Solar/Wind Harmer
0.692
316311AC2-079 GEN
Solar/Wind Harmer
3.921
3151081ELIZAR1
Adder
6.332
3151091ELIZAR2
Adder
6.222
3152611GOSPORTB
Adder
0.879
3152621GOSPORTC
Adder
0.746
3152601GOSPORTA
Adder
0.688
957871AF2-081 GEN
Solar/Wind Harmer
3.844
319010AE1-072 C
Solar/Wind Harmer
1.551
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316315AB2-025 C
Solar/Wind Harmer
0.206
316305AF2-043 C
Solar/Wind Harmer
0.23
315835AF2-110_GEN
Solar/Wind Harmer
0.955
315976AC1-164 GENA
Solar/Wind Harmer
8.065
316169AC1-164_GENC
Solar/Wind Harmer
6.967
315975AC1-164 GENB
Solar/Wind Harmer
0.239
315814AE2-033 C
Solar/Wind Harmer
7.093
313526AB2-022
Solar/Wind Harmer
0.205
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.139
941031AE2-094 GEN
Solar/Wind Harmer
13.945
944011AF1-069 GEN
Solar/Wind Harmer
4.369
315611Z1-036_GEN2
Solar/Wind Harmer
1.83
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
15.399
970673AG2-436 GEN
Solar/Wind Harmer
7.797
971967AH1-528 GEN
Solar/Wind Harmer
13.65
315816AE2-034 GEN
Solar/Wind Harmer
0.582
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.428
315733AD1-074 GEN2
Solar/Wind Harmer
1.428
315735AD1-075 GEN1
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.626
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.063
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
972193AH1-681 GEN
Adder
1.409
946281AF1-292 GEN
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.06
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.693
316087AB2-174 GEN
Solar/Wind Harmer
0.977
315652AC1-086 GEN
Solar/Wind Harmer
7.643
3137643SOCKMAN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
3.234
316005AA1-067
Solar/Wind Harmer
0.129
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
970181AG2-120 GEN
Solar/Wind Harmer
0.838
3141426STAFORD
Solar/Wind Helper
0.114
316223AC1-118
Solar/Wind Helper
0.271
3150401LDYSMT4
50/50
43.23
3150371LDYSMT1
50/50
41.772
970497AG2-320 GEN
50/50
24.535
315051AA1-145 CT1
50/50
1.178
966881AG1-559 GEN
Solar/Wind Harmer
0.782
3142416OLDCHRC
Solar/Wind Harmer
0.967
3150861SPRUNCD
Adder
0.37
970293AG2-193 GEN
Solar/Wind Harmer
1.099
3143096IRON208
Adder
0.327
3143096IRON208
Adder
0.321
315839AE2-212 C
Solar/Wind Harmer
0.256
970133AG2-095 GEN
Solar/Wind Harmer
0.941
965281AG1-393 GEN
Solar/Wind Harmer
1.043
970129AG2-093 GEN
Solar/Wind Harmer
4.632
315778AD1-151 GEN
Solar/Wind Harmer
7.043
315813AE1-149 C
Solar/Wind Harmer
5.08
3142946ENON
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
0.754
316083AB2-161 GEN
Solar/Wind Harmer
1.297
970661AG2-428 GEN
Solar/Wind Harmer
1.493
961611AG1-000B GEN
Solar/Wind Harmer
1.669
315773AC2-141 GEN
Solar/Wind Harmer
3.289
3151221GRAVEL6
Adder
5.071
3151171GRAVELC
Adder
0.976
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
35.31
944601AF1-125 GEN
Solar/Wind Harmer
34.759
3151101ELIZAR3
Adder
6.413
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.935
316313AB2-026
Solar/Wind Harmer
0.206
316258AE1-075 C
Solar/Wind Harmer
0.185
316405AF2-144 C
Solar/Wind Harmer
0.196
3143336POWHATN
Solar/Wind Harmer
0.77
316320Y1-086
Solar/Wind Harmer
0.445
316435W1029_GEN3
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
0.8
316382AG1-145 C
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.245
3150921YORKTN3
Adder
1.611
315614AA2-178 GEN
Solar/Wind Harmer
0.776
316365GEN2_N
Solar/Wind Harmer
0.478
971157AH1-035 GEN
Solar/Wind Harmer
0.885
3156081AA2-088 GEN
Solar/Wind Harmer
2.298
315737AD1-076 GEN
Solar/Wind Harmer
1.342
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.459
957521AF2-046 GEN
Solar/Wind Harmer
5.494
961681AG1-008 GEN
Solar/Wind Harmer
5.494
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
31.532
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
966621AG1-532 GEN
Solar/Wind Harmer
0.14
316463AE2-346 GEN
Solar/Wind Harmer
0.112
316140AB2-099
Solar/Wind Harmer
0.047
962331AG1-082 GEN
Solar/Wind Harmer
0.863
3146263WOODLND
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.318
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316210AC1-098 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.006
966801AG1-551 GEN
Solar/Wind Harmer
0.813
970909AG2-566 GEN
Solar/Wind Harmer
0.613
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315724AD1-057 GEN
Solar/Wind Harmer
0.367
316327AA2-057 GEN
Solar/Wind Harmer
0.639
3141906WESTMOR
Solar/Wind Helper
0.071
3150391LDYSMT3
50/50
43.149
972195AH1-682 GEN
50/50
5.67
315673AE1-157 GEN
Solar/Wind Harmer
21.737
957411AF2-035 GEN
Solar/Wind Harmer
11.699
970317AG2-208 GEN
Solar/Wind Harmer
11.374
3142296MT RD221
Adder
0.302
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
5.91
3150701DARBY 4
Adder
5.896
3150681DARBY 2
Adder
5.889
3150671DARBY 1
Adder
5.882
3143526WINTERP
Solar/Wind Harmer
-0.046
944641AF1-129 GEN
Adder
37.086
971223AH1-071 GEN
Solar/Wind Harmer
1.092
316240AF1-291 C
Solar/Wind Harmer
0.262
316075AC2-137 C
Solar/Wind Harmer
0.224
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.603
315697AD1-025 GEN
Solar/Wind Harmer
1.633
970657AG2-426 GEN
Solar/Wind Harmer
2.49
970657AG2-426 GEN
Solar/Wind Harmer
0.521
316236AE1-162_GEN
Solar/Wind Harmer
0.235
316036AC1-147 C
Solar/Wind Harmer
0.209
3150991CHESPKB
Adder
0.723
3150991CHESPKB
Adder
0.706
3142956BIRDNECK
Solar/Wind Harmer
0.415
316316AC1-027 C
Solar/Wind Harmer
0.238
316185AD1-033 GEN
Solar/Wind Harmer
0.816
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316018AA1-139 ULT2
Solar/Wind Harmer
0.659
316017AA1-139 ULT1
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.03
3146456SLIGO L269
Solar/Wind Harmer
0.906
3130086AYDLETT
Solar/Wind Harmer
-0.03
3144356SAPONY
Solar/Wind Harmer
0.267
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.364
316433W1029_GEN2
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
966871AG1-558 GEN
Solar/Wind Harmer
0.223
966871AG1-558 GEN
Solar/Wind Harmer
0.076
315742AE1-103 GEN
Solar/Wind Harmer
0.772
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
972185AH1-677 GEN
Adder
3.634
972187AH1-678 GEN
Adder
1.826
970933AG2-581 GEN
Solar/Wind Harmer
6.679
316065AD1-022 GEN
Solar/Wind Harmer
3.511
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.952
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
970099AG2-077 GEN
Solar/Wind Harmer
8.455
316426AA2-053 GEN
Solar/Wind Harmer
0.683
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.757
3145593CAROLNA
Solar/Wind Harmer
0.056
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
0.794
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.199
3145783HORNRTN
Solar/Wind Harmer
0.079
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
971741AH1-377 GEN
Solar/Wind Harmer
7.563
316274AC1-208 GEN
Solar/Wind Harmer
0.701
970301AG2-198 GEN
Solar/Wind Harmer
3.227
NYPJM->LTFIMP_NY
CLTF
1.15
LAGNLTFEXP_LAGN->PJM
CLTF
3.071
LGEELTFEXP_LGEE->PJM
CLTF
0.646
WECLTFEXP_WEC->PJM
CLTF
0.327
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.25
TVALTFEXP_TVA->PJM
CLTF
1.556
CPLELTFEXP_CPLE->PJM
CLTF
3.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.979
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.426
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 6MINE RD-6FREDBRG 230.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MINE RD-6FREDBRG 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:166.64 %
Rating:1303.0 MVA
Rating Type:C
MVA to Mitigate:2171.28
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
3150401LDYSMT4
50/50
43.23
3150371LDYSMT1
50/50
41.772
970497AG2-320 GEN
50/50
24.535
315051AA1-145 CT1
50/50
1.178
966881AG1-559 GEN
Solar/Wind Harmer
0.782
3142416OLDCHRC
Solar/Wind Harmer
0.967
3150861SPRUNCD
Adder
0.37
970293AG2-193 GEN
Solar/Wind Harmer
1.099
3143096IRON208
Adder
0.327
3143096IRON208
Adder
0.321
315839AE2-212 C
Solar/Wind Harmer
0.256
970133AG2-095 GEN
Solar/Wind Harmer
0.941
965281AG1-393 GEN
Solar/Wind Harmer
1.043
970129AG2-093 GEN
Solar/Wind Harmer
4.632
315778AD1-151 GEN
Solar/Wind Harmer
7.043
315813AE1-149 C
Solar/Wind Harmer
5.08
3142946ENON
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
0.754
316083AB2-161 GEN
Solar/Wind Harmer
1.297
970661AG2-428 GEN
Solar/Wind Harmer
1.493
961611AG1-000B GEN
Solar/Wind Harmer
1.669
315773AC2-141 GEN
Solar/Wind Harmer
3.289
3151221GRAVEL6
Adder
5.071
3151171GRAVELC
Adder
0.976
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
35.31
944601AF1-125 GEN
Solar/Wind Harmer
34.759
3151101ELIZAR3
Adder
6.413
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.935
316313AB2-026
Solar/Wind Harmer
0.206
316258AE1-075 C
Solar/Wind Harmer
0.185
316405AF2-144 C
Solar/Wind Harmer
0.196
3143336POWHATN
Solar/Wind Harmer
0.77
316320Y1-086
Solar/Wind Harmer
0.445
316435W1029_GEN3
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
0.8
316382AG1-145 C
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.245
3150921YORKTN3
Adder
1.611
315614AA2-178 GEN
Solar/Wind Harmer
0.776
316365GEN2_N
Solar/Wind Harmer
0.478
971157AH1-035 GEN
Solar/Wind Harmer
0.885
3156081AA2-088 GEN
Solar/Wind Harmer
2.298
315737AD1-076 GEN
Solar/Wind Harmer
1.342
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.459
957521AF2-046 GEN
Solar/Wind Harmer
5.494
961681AG1-008 GEN
Solar/Wind Harmer
5.494
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
31.532
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3150411LDYSMT5
50/50
43.365
3150381LDYSMT2
50/50
41.502
972213AH1-691 GEN
50/50
7.02
972215AH1-692 GEN
50/50
7.02
963051AG1-154 GEN
50/50
5.4
972189AH1-679 GEN
50/50
2.64
316312AB1-027
Solar/Wind Harmer
0.323
971285AH1-108 GEN
Adder
0.606
316233AE1-074 FULL
Solar/Wind Harmer
0.24
971281AH1-106 GEN
Solar/Wind Harmer
1.451
971283AH1-107 GEN
Solar/Wind Harmer
1.451
316132AB2-190 GEN1
Solar/Wind Harmer
0.831
3143316POE
Solar/Wind Harmer
-0.032
316369SG1_INVT
Solar/Wind Harmer
1.442
972265AH1-717 GEN
Adder
5.416
3151201GRAVEL4
Adder
5.077
3151191GRAVEL3
Adder
5.013
3151211GRAVEL5
Adder
5.013
971445AH1-216 GEN
Solar/Wind Harmer
4.834
315833AF1-017_GEN
Solar/Wind Harmer
1.477
316349AD2-085 GEN
Solar/Wind Harmer
0.692
316311AC2-079 GEN
Solar/Wind Harmer
3.921
3151081ELIZAR1
Adder
6.332
3151091ELIZAR2
Adder
6.222
3152611GOSPORTB
Adder
0.879
3152621GOSPORTC
Adder
0.746
3152601GOSPORTA
Adder
0.688
957871AF2-081 GEN
Solar/Wind Harmer
3.844
319010AE1-072 C
Solar/Wind Harmer
1.551
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316315AB2-025 C
Solar/Wind Harmer
0.206
316305AF2-043 C
Solar/Wind Harmer
0.23
315835AF2-110_GEN
Solar/Wind Harmer
0.955
315976AC1-164 GENA
Solar/Wind Harmer
8.065
316169AC1-164_GENC
Solar/Wind Harmer
6.967
315975AC1-164 GENB
Solar/Wind Harmer
0.239
315814AE2-033 C
Solar/Wind Harmer
7.093
313526AB2-022
Solar/Wind Harmer
0.205
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.139
941031AE2-094 GEN
Solar/Wind Harmer
13.945
944011AF1-069 GEN
Solar/Wind Harmer
4.369
315611Z1-036_GEN2
Solar/Wind Harmer
1.83
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
15.399
970673AG2-436 GEN
Solar/Wind Harmer
7.797
971967AH1-528 GEN
Solar/Wind Harmer
13.65
315816AE2-034 GEN
Solar/Wind Harmer
0.582
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.428
315733AD1-074 GEN2
Solar/Wind Harmer
1.428
315735AD1-075 GEN1
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.626
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.063
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
972193AH1-681 GEN
Adder
1.409
946281AF1-292 GEN
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.06
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.693
316087AB2-174 GEN
Solar/Wind Harmer
0.977
315652AC1-086 GEN
Solar/Wind Harmer
7.643
3137643SOCKMAN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
3.234
316005AA1-067
Solar/Wind Harmer
0.129
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
970181AG2-120 GEN
Solar/Wind Harmer
0.838
3141426STAFORD
Solar/Wind Helper
0.114
316223AC1-118
Solar/Wind Helper
0.271
972197AH1-683 GEN
50/50
6.75
972219AH1-694 GEN
50/50
4.86
315052AA1-145 CT2
50/50
1.183
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.37
3143526WINTERP
Solar/Wind Harmer
-0.046
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.327
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315671AE2-027_GEN
Solar/Wind Harmer
6.265
944631AF1-128 GEN
Adder
35.154
970129AG2-093 GEN
Solar/Wind Harmer
1.876
316458AB2-190 GEN2
Solar/Wind Harmer
0.831
971069AG2-661 GEN
Solar/Wind Harmer
1.286
970659AG2-427 GEN
Solar/Wind Harmer
4.257
971647AH1-324 GEN
Solar/Wind Harmer
4
316381AD1-082 GEN
Solar/Wind Harmer
0.733
970661AG2-428 GEN
Solar/Wind Harmer
8.426
961611AG1-000B GEN
Solar/Wind Harmer
3.913
316294AC1-161 GEN
Solar/Wind Harmer
2.543
3151171GRAVELC
Adder
0.742
3145336SMITFLD
Solar/Wind Harmer
-0.031
944591AF1-124 GEN
Solar/Wind Harmer
35.438
316375AC2-012 GEN
Solar/Wind Harmer
2.685
3150981CHESPKA
Adder
0.862
939411AE1-173 GEN
Solar/Wind Harmer
38.501
316388AE2-253 GEN
Solar/Wind Harmer
0.519
940641AE2-051 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.155
316093AE2-104_GEN
Solar/Wind Harmer
2.222
316072AD1-144
Solar/Wind Harmer
0.154
3143336POWHATN
Solar/Wind Harmer
0.906
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.83
316159AE1-175 C
Solar/Wind Harmer
0.197
316336AC2-165 C
Solar/Wind Harmer
1.276
3130156CHOWAN
Solar/Wind Harmer
-0.007
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.74
316023GEN1_S
Solar/Wind Harmer
0.478
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.75
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.208
970919AG2-571 GEN
Solar/Wind Harmer
2.21
970087AG2-069 GEN
Solar/Wind Harmer
6.524
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
36.745
960081AF2-299 GEN
Solar/Wind Harmer
0.777
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
971317AH1-138 GEN
Solar/Wind Harmer
0.852
316011AB1-132 GEN
Solar/Wind Harmer
1.421
962571AG1-106 GEN
Solar/Wind Harmer
0.977
971795AH1-408 GEN
Solar/Wind Harmer
5.082
3145963POPLR C
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
21.138
316190AA2-174 GEN
Solar/Wind Harmer
0.083
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
1.035
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
315693AD1-088 GEN
Solar/Wind Harmer
3.339
962491AG1-098 GEN
Solar/Wind Harmer
4.459
970937AG2-583 GEN
Solar/Wind Harmer
4.746
316212AC1-099_GEN
Solar/Wind Harmer
0.57
3146293MARTNCO
Solar/Wind Harmer
0.04
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.207
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315722AD1-056 GEN
Solar/Wind Harmer
0.667
316337AD2-073 GEN
Solar/Wind Helper
0.174
966621AG1-532 GEN
Solar/Wind Harmer
0.14
316463AE2-346 GEN
Solar/Wind Harmer
0.112
316140AB2-099
Solar/Wind Harmer
0.047
962331AG1-082 GEN
Solar/Wind Harmer
0.863
3146263WOODLND
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.318
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316210AC1-098 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.006
966801AG1-551 GEN
Solar/Wind Harmer
0.813
970909AG2-566 GEN
Solar/Wind Harmer
0.613
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315724AD1-057 GEN
Solar/Wind Harmer
0.367
316327AA2-057 GEN
Solar/Wind Harmer
0.639
3141906WESTMOR
Solar/Wind Helper
0.071
3150391LDYSMT3
50/50
43.149
972195AH1-682 GEN
50/50
5.67
315673AE1-157 GEN
Solar/Wind Harmer
21.737
957411AF2-035 GEN
Solar/Wind Harmer
11.699
970317AG2-208 GEN
Solar/Wind Harmer
11.374
3142296MT RD221
Adder
0.302
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
5.91
3150701DARBY 4
Adder
5.896
3150681DARBY 2
Adder
5.889
3150671DARBY 1
Adder
5.882
3143526WINTERP
Solar/Wind Harmer
-0.046
944641AF1-129 GEN
Adder
37.086
971223AH1-071 GEN
Solar/Wind Harmer
1.092
316240AF1-291 C
Solar/Wind Harmer
0.262
316075AC2-137 C
Solar/Wind Harmer
0.224
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.603
315697AD1-025 GEN
Solar/Wind Harmer
1.633
970657AG2-426 GEN
Solar/Wind Harmer
2.49
970657AG2-426 GEN
Solar/Wind Harmer
0.521
316236AE1-162_GEN
Solar/Wind Harmer
0.235
316036AC1-147 C
Solar/Wind Harmer
0.209
3150991CHESPKB
Adder
0.723
3150991CHESPKB
Adder
0.706
3142956BIRDNECK
Solar/Wind Harmer
0.415
316316AC1-027 C
Solar/Wind Harmer
0.238
316185AD1-033 GEN
Solar/Wind Harmer
0.816
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316018AA1-139 ULT2
Solar/Wind Harmer
0.659
316017AA1-139 ULT1
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.03
3146456SLIGO L269
Solar/Wind Harmer
0.906
3130086AYDLETT
Solar/Wind Harmer
-0.03
3144356SAPONY
Solar/Wind Harmer
0.267
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.364
316433W1029_GEN2
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
966871AG1-558 GEN
Solar/Wind Harmer
0.223
966871AG1-558 GEN
Solar/Wind Harmer
0.076
315742AE1-103 GEN
Solar/Wind Harmer
0.772
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
972185AH1-677 GEN
Adder
3.634
972187AH1-678 GEN
Adder
1.826
970933AG2-581 GEN
Solar/Wind Harmer
6.679
316065AD1-022 GEN
Solar/Wind Harmer
3.511
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.952
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
970099AG2-077 GEN
Solar/Wind Harmer
8.455
316426AA2-053 GEN
Solar/Wind Harmer
0.683
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.757
3145593CAROLNA
Solar/Wind Harmer
0.056
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
0.794
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.199
3145783HORNRTN
Solar/Wind Harmer
0.079
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
971741AH1-377 GEN
Solar/Wind Harmer
7.563
316274AC1-208 GEN
Solar/Wind Harmer
0.701
970301AG2-198 GEN
Solar/Wind Harmer
3.227
NYPJM->LTFIMP_NY
CLTF
1.15
LGEELTFEXP_LGEE->PJM
CLTF
0.646
LAGNLTFEXP_LAGN->PJM
CLTF
3.071
WECLTFEXP_WEC->PJM
CLTF
0.327
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.25
TVALTFEXP_TVA->PJM
CLTF
1.556
CPLELTFEXP_CPLE->PJM
CLTF
3.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.979
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.426
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:195.13 %
Rating:661.76 MVA
Rating Type:B
MVA to Mitigate:1291.31
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.67
316303AF2-085
50/50
2.055
3151541CLOVER2
50/50
2.336
3151611KERR 4
50/50
0.22
3151621KERR 5
50/50
0.22
3151631KERR 6
50/50
0.22
3151641KERR 7
50/50
0.22
963041AG1-153 GEN
50/50
2.144
315244AE2-183_ST
50/50
2.284
3151281ROARAP4
50/50
0.094
3151281ROARAP4
50/50
0.088
971285AH1-108 GEN
50/50
0.596
315779AE2-040
50/50
1.013
971447AH1-217 GEN
Solar/Wind Harmer
11.337
971845AH1-439 GEN
Solar/Wind Harmer
16.33
970285AG2-188 GEN
Solar/Wind Harmer
27.559
270494AE1-108_GEN
Solar/Wind Harmer
3.817
315657AE1-056 GEN
Solar/Wind Harmer
7.617
946301AF1-294 GEN
Solar/Wind Harmer
4.122
961791AG1-021 GEN
Solar/Wind Harmer
2.005
970683AG2-441 GEN
Solar/Wind Harmer
12.78
970681AG2-440 GEN
Solar/Wind Harmer
10.224
3144303KENBRDG
Solar/Wind Harmer
0.139
971443AH1-215 GEN
Solar/Wind Harmer
2.888
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.258
316233AE1-074 FULL
Solar/Wind Harmer
0.078
971281AH1-106 GEN
Solar/Wind Harmer
1.344
971283AH1-107 GEN
Solar/Wind Harmer
1.344
970831AG2-522 GEN
Solar/Wind Harmer
4.036
3147173SINAI
Solar/Wind Harmer
0.092
3147243WELCO
Solar/Wind Harmer
0.057
971967AH1-528 GEN
Solar/Wind Harmer
13.711
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970673AG2-436 GEN
Solar/Wind Harmer
16.986
970673AG2-436 GEN
Solar/Wind Harmer
11.324
941031AE2-094 GEN
Solar/Wind Harmer
14.544
944011AF1-069 GEN
Solar/Wind Harmer
4.752
3137643SOCKMAN
Solar/Wind Harmer
0.315
970865AG2-541 GEN
Solar/Wind Harmer
2.702
970085AG2-068 GEN
Solar/Wind Harmer
4.124
970581AG2-369 GEN
Solar/Wind Harmer
3.547
315607AA1-063A GEN
Solar/Wind Harmer
0.154
3146043SEABORD
Solar/Wind Harmer
0.075
315814AE2-033 C
Solar/Wind Harmer
5.747
316315AB2-025 C
Solar/Wind Harmer
0.059
965291AG1-394 GEN
Solar/Wind Harmer
0.317
315652AC1-086 GEN
Solar/Wind Harmer
7.782
3151921BEARGRDN G2
50/50
4.238
3144293JTRSVLE
50/50
0.706
970413AG2-270 GEN
50/50
10.245
3151591KERR 2
50/50
0.22
3151031BRUNSWICKG2
50/50
1.059
3151261ROARAP2
50/50
0.095
3150861SPRUNCD
50/50
0.364
966251AG1-494 GEN
50/50
1.288
970221AG2-151 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
0.132
3146926FARMVIL
Solar/Wind Harmer
0.176
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.159
316258AE1-075 C
Solar/Wind Harmer
0.19
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.801
970909AG2-566 GEN
Solar/Wind Harmer
2.396
3147133PAMPLIN
Solar/Wind Harmer
0.693
971193AH1-056 GEN
Solar/Wind Harmer
13.448
963181AG1-167 GEN
Solar/Wind Harmer
0.835
959311AF2-222 GEN
Solar/Wind Harmer
15.884
970257AG2-171 GEN
Solar/Wind Harmer
5.55
315785AD2-033 C
Solar/Wind Harmer
1.352
964241AG1-285 GEN
Solar/Wind Harmer
9.804
316131AB2-060 GEN
Solar/Wind Harmer
0.426
958131AF2-107 GEN
Solar/Wind Harmer
3.651
316478AD1-087 GEN
Solar/Wind Harmer
0.382
316486AD2-202 GEN
Solar/Wind Harmer
0.112
3147043LAWRENC
Solar/Wind Harmer
0.059
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.912
971683AH1-343 GEN
Solar/Wind Harmer
3.032
313506AB2-031 GEN
Solar/Wind Harmer
0.248
970917AG2-570 GEN
Solar/Wind Harmer
6.901
316365GEN2_N
Solar/Wind Harmer
0.164
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3146263WOODLND
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3145893MURPHYS
Solar/Wind Harmer
0.117
3145893MURPHYS
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.202
961681AG1-008 GEN
Solar/Wind Harmer
5.202
3145796HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
0.07
316210AC1-098 GEN
Solar/Wind Harmer
0.644
3146173TUNIS
Solar/Wind Harmer
0.069
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.732
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
316327AA2-057 GEN
Solar/Wind Harmer
0.102
315724AD1-057 GEN
Solar/Wind Harmer
0.25
3145273HOLLAND
Solar/Wind Harmer
0.05
3156021HOLLOMANSOL
Solar/Wind Harmer
0.301
3146233WITAKRS
Solar/Wind Harmer
0.331
3146233WITAKRS
Solar/Wind Harmer
0.045
3138543CONSLDL
Solar/Wind Harmer
0.043
3146206CASHIE
Solar/Wind Harmer
0.065
315813AE1-149 C
Solar/Wind Harmer
3.482
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
0.001
316283AC2-100 C
Solar/Wind Harmer
0.127
315839AE2-212 C
Solar/Wind Harmer
0.001
315737AD1-076 GEN
Solar/Wind Harmer
0.835
970661AG2-428 GEN
Solar/Wind Harmer
1.373
971157AH1-035 GEN
Solar/Wind Harmer
0.778
315614AA2-178 GEN
Solar/Wind Harmer
0.37
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.064
971623AH1-311 GEN
Solar/Wind Harmer
0.129
3146376EDENTON
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
961601AG1-000A GEN
Solar/Wind Harmer
4.548
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316435W1029_GEN3
Solar/Wind Harmer
0
965281AG1-393 GEN
Solar/Wind Harmer
0.68
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
316320Y1-086
Solar/Wind Harmer
0
3145933PARMELE
Solar/Wind Harmer
0.063
966801AG1-551 GEN
Solar/Wind Harmer
0.74
3146456SLIGO L269
Solar/Wind Harmer
0.063
971153AH1-033 GEN
Solar/Wind Harmer
0.732
944581AF1-123 GEN
Solar/Wind Harmer
14.239
944601AF1-125 GEN
Solar/Wind Harmer
14.019
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3151101ELIZAR3
Adder
5.847
3144873MCLAUGH
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.009
315773AC2-141 GEN
Solar/Wind Harmer
2.27
3145336SMITFLD
Solar/Wind Harmer
0.025
3151221GRAVEL6
Adder
4.403
3151171GRAVELC
Adder
0.847
961611AG1-000B GEN
Solar/Wind Harmer
1.612
3143096IRON208
Adder
0.252
3143096IRON208
Adder
0.247
315778AD1-151 GEN
Solar/Wind Harmer
4.818
970129AG2-093 GEN
Solar/Wind Harmer
3.634
970133AG2-095 GEN
Solar/Wind Harmer
0.576
316499AE2-029_GEN
Solar/Wind Helper
0.501
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.3
3148013FISHERV
Solar/Wind Helper
0.129
315616AA1-038_C
Solar/Wind Helper
0.524
3151931BEARGRDN S1
50/50
5.469
3151911BEARGRDN G1
50/50
4.238
3144293JTRSVLE
50/50
0.706
970119AG2-088 GEN
50/50
15.414
3151531CLOVER1
50/50
2.348
3151601KERR 3
50/50
0.22
3151581KERR 1
50/50
0.079
3147043LAWRENC
50/50
0.939
3151051BRUNSWICKS1
50/50
2.197
3151021BRUNSWICKG1
50/50
1.059
971451AH1-221 GEN
50/50
3.216
315243AE2-183_GT3
50/50
1.321
3151261ROARAP2
50/50
0.097
3150851SPRUNCC
50/50
0.364
972003AH1-546 GEN
Solar/Wind Harmer
18.676
971377AH1-170 GEN
Solar/Wind Harmer
4.327
3147623JAMES R
Solar/Wind Harmer
0.94
970937AG2-583 GEN
Solar/Wind Harmer
23.217
316322AB2-045
Solar/Wind Harmer
0.003
3146776BUCKING
Solar/Wind Harmer
0.147
3146926FARMVIL
Solar/Wind Harmer
0.176
316336AC2-165 C
Solar/Wind Harmer
0.011
3143336POWHATN
Solar/Wind Harmer
4.472
963171AG1-166 GEN
Solar/Wind Harmer
1.114
971563AH1-280 GEN
Solar/Wind Harmer
2.228
970685AG2-442 GEN
Solar/Wind Harmer
14.313
962491AG1-098 GEN
Solar/Wind Harmer
7.815
315693AD1-088 GEN
Solar/Wind Harmer
6.344
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Harmer
0.116
957481AF2-042 GEN
Solar/Wind Harmer
29.295
970401AG2-262 GEN
Solar/Wind Harmer
0.638
315687AD1-152 GEN
Solar/Wind Harmer
0.003
971065AG2-659 GEN
Solar/Wind Harmer
4.184
3143526WINTERP
Solar/Wind Harmer
0.504
316129AC1-054 GEN
Solar/Wind Harmer
0.363
971795AH1-408 GEN
Solar/Wind Harmer
6.199
316003AC1-222 GEN
Solar/Wind Harmer
0.002
960081AF2-299 GEN
Solar/Wind Harmer
0.793
970919AG2-571 GEN
Solar/Wind Harmer
2.76
970087AG2-069 GEN
Solar/Wind Harmer
6.187
3145783HORNRTN
Solar/Wind Harmer
0.076
316190AA2-174 GEN
Solar/Wind Harmer
0
940641AE2-051 GEN
Solar/Wind Harmer
5.984
316023GEN1_S
Solar/Wind Harmer
0.164
939411AE1-173 GEN
Solar/Wind Harmer
30.681
316011AB1-132 GEN
Solar/Wind Harmer
1.286
962571AG1-106 GEN
Solar/Wind Harmer
1.007
3146263WOODLND
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.281
3145893MURPHYS
Solar/Wind Harmer
0.312
3145796HORNRTN
Solar/Wind Harmer
0.23
3145796HORNRTN
Solar/Wind Harmer
0.07
316212AC1-099_GEN
Solar/Wind Harmer
0.359
3146173TUNIS
Solar/Wind Harmer
0.069
3145823KELFORD
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
315722AD1-056 GEN
Solar/Wind Harmer
0.422
3146233WITAKRS
Solar/Wind Harmer
0.263
3146206CASHIE
Solar/Wind Harmer
0.065
971547AH1-271 GEN
Solar/Wind Harmer
1.396
970659AG2-427 GEN
Solar/Wind Harmer
3.146
316381AD1-082 GEN
Solar/Wind Harmer
0.068
970661AG2-428 GEN
Solar/Wind Harmer
6.453
3145663CRESWEL
Solar/Wind Harmer
0.181
971163AH1-040 GEN
Solar/Wind Harmer
5.167
3145543BTLEBRO
Solar/Wind Harmer
0.064
3145543BTLEBRO
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.231
316049AB1-081 GEN
Solar/Wind Harmer
0.368
3142053HEARTS
Solar/Wind Harmer
0.113
316093AE2-104_GEN
Solar/Wind Harmer
1.081
3130156CHOWAN
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.064
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.006
3146516WINFALL
Solar/Wind Harmer
0.207
3146516WINFALL
Solar/Wind Harmer
0.064
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
316246AF1-032 C
Solar/Wind Harmer
0.029
3146293MARTNCO
Solar/Wind Harmer
0.059
316494AC1-189 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
0.063
316388AE2-253 GEN
Solar/Wind Harmer
0.198
944591AF1-124 GEN
Solar/Wind Harmer
14.289
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
315671AE2-027_GEN
Solar/Wind Harmer
4.043
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.786
316072AD1-144
Solar/Wind Harmer
0.023
316294AC1-161 GEN
Solar/Wind Harmer
1.077
3145336SMITFLD
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
0.644
961611AG1-000B GEN
Solar/Wind Harmer
3.17
971647AH1-324 GEN
Solar/Wind Harmer
2.576
3143096IRON208
Adder
0.252
971069AG2-661 GEN
Solar/Wind Harmer
1.071
316458AB2-190 GEN2
Solar/Wind Harmer
0.323
970129AG2-093 GEN
Solar/Wind Harmer
1.71
3147983MERCK5
Solar/Wind Helper
0.055
316192AB2-158 GEN
Solar/Wind Helper
0.903
3147666LOUISA
Solar/Wind Helper
0.521
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145796HORNRTN
Solar/Wind Harmer
0.223
3145796HORNRTN
Solar/Wind Harmer
0.028
3146033SCOT NK
Solar/Wind Harmer
0.276
316123AC1-075 GEN
Solar/Wind Harmer
0.094
970165AG2-112 GEN
Solar/Wind Harmer
0.558
970163AG2-111 GEN
Solar/Wind Harmer
0.532
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3143316POE
Solar/Wind Harmer
0.269
316319Z2-044 C
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.065
970601AG2-382 GEN
Solar/Wind Harmer
2.444
315732AD1-074 GEN1
Solar/Wind Harmer
0.373
315733AD1-074 GEN2
Solar/Wind Harmer
0.373
315735AD1-075 GEN1
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.277
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.044
316311AC2-079 GEN
Solar/Wind Harmer
1.853
315835AF2-110_GEN
Solar/Wind Harmer
0.441
3130156CHOWAN
Solar/Wind Harmer
0.064
3130156CHOWAN
Solar/Wind Harmer
0.064
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
3146486SUNBURY
Solar/Wind Harmer
0.064
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.039
3146396TANGLEW
Solar/Wind Harmer
0.175
316420AA1-050 GEN
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
0.001
957861AF2-080 GEN
Solar/Wind Harmer
2.737
3146406KITTY HAWK
Solar/Wind Harmer
0.008
319010AE1-072 C
Solar/Wind Harmer
0.319
957871AF2-081 GEN
Solar/Wind Harmer
3.153
316005AA1-067
Solar/Wind Harmer
0.068
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
970181AG2-120 GEN
Solar/Wind Harmer
0.787
3151081ELIZAR1
Adder
5.773
3151091ELIZAR2
Adder
5.672
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.68
3152601GOSPORTA
Adder
0.628
971445AH1-216 GEN
Solar/Wind Harmer
4.321
972265AH1-717 GEN
Adder
4.702
3151201GRAVEL4
Adder
4.408
3151191GRAVEL3
Adder
4.352
3151211GRAVEL5
Adder
4.352
316369SG1_INVT
Solar/Wind Harmer
0.002
316132AB2-190 GEN1
Solar/Wind Harmer
0.323
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.077
3148013FISHERV
Solar/Wind Helper
0.074
3148463FAIRFLD
Solar/Wind Helper
0.116
3144293JTRSVLE
50/50
0.706
3144293JTRSVLE
50/50
0.594
970535AG2-341 GEN
50/50
2.11
3152661PLYWOOD A
50/50
0.217
3151041BRUNSWICKG3
50/50
1.059
972187AH1-678 GEN
50/50
2.43
315242AE2-183_GT2
50/50
1.321
315241AE2-183_GT1
50/50
1.313
972185AH1-677 GEN
50/50
4.762
970533AG2-339 GEN
50/50
7.019
970531AG2-338 GEN
50/50
2.808
971489AH1-241 GEN
Solar/Wind Harmer
21.635
3146776BUCKING
Solar/Wind Harmer
1.465
3146776BUCKING
Solar/Wind Harmer
0.119
315821AE2-092 GEN
Solar/Wind Harmer
0.014
970301AG2-198 GEN
Solar/Wind Harmer
9.583
3147133PAMPLIN
Solar/Wind Harmer
0.221
3147133PAMPLIN
Solar/Wind Harmer
0.176
958211AF2-115 GEN
Solar/Wind Harmer
2.506
963191AG1-168 GEN
Solar/Wind Harmer
0.835
971741AH1-377 GEN
Solar/Wind Harmer
20.177
316034AC1-036 C
Solar/Wind Harmer
0.013
970323AG2-213 GEN
Solar/Wind Harmer
7.401
971775AH1-396 GEN
Solar/Wind Harmer
0.278
313527AB2-043 GEN
Solar/Wind Harmer
0.002
971223AH1-071 GEN
Solar/Wind Harmer
1.233
962561AG1-105 GEN
Solar/Wind Harmer
5.397
939181AE1-148 GEN
Solar/Wind Harmer
5.333
970099AG2-077 GEN
Solar/Wind Harmer
11.718
964791AG1-342 GEN
Solar/Wind Harmer
2.089
3146843MT LREL
Solar/Wind Harmer
0.109
3146843MT LREL
Solar/Wind Harmer
0.109
3143526WINTERP
Solar/Wind Harmer
0.504
970933AG2-581 GEN
Solar/Wind Harmer
7.465
316181AB2-040 GEN
Solar/Wind Harmer
0.116
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.843
3145593CAROLNA
Solar/Wind Harmer
0.097
3145783HORNRTN
Solar/Wind Harmer
1.361
3145783HORNRTN
Solar/Wind Harmer
1.089
3145783HORNRTN
Solar/Wind Harmer
0.34
3145783HORNRTN
Solar/Wind Harmer
0.136
316426AA2-053 GEN
Solar/Wind Harmer
0.256
3144356SAPONY
Solar/Wind Harmer
0.607
316274AC1-208 GEN
Solar/Wind Harmer
0.366
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.042
3145893MURPHYS
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
0.126
3145796HORNRTN
Solar/Wind Harmer
0.209
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
315742AE1-103 GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.272
316065AD1-022 GEN
Solar/Wind Harmer
3.004
970657AG2-426 GEN
Solar/Wind Harmer
2.275
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
2.446
3146376EDENTON
Solar/Wind Harmer
0.286
3146376EDENTON
Solar/Wind Harmer
0.286
961601AG1-000A GEN
Solar/Wind Harmer
1.137
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146626S HERTFORD
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
3146516WINFALL
Solar/Wind Harmer
0.064
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
3146386ELIZ CT
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.063
3130086AYDLETT
Solar/Wind Harmer
0.253
3137176SLIGO L2192
Solar/Wind Harmer
0.252
3146456SLIGO L269
Solar/Wind Harmer
1.121
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.035
316339AD2-160 GEN
Solar/Wind Harmer
0.103
3145506HICKORY
Solar/Wind Harmer
0.253
3145506HICKORY
Solar/Wind Harmer
0.152
3145506HICKORY
Solar/Wind Harmer
0.038
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.061
942751AE2-291 GEN
Solar/Wind Harmer
3.43
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.012
3150991CHESPKB
Adder
0.659
3150991CHESPKB
Adder
0.643
944641AF1-129 GEN
Adder
29.755
316236AE1-162_GEN
Solar/Wind Harmer
0
316033AB2-134 GEN
Solar/Wind Harmer
0.004
315697AD1-025 GEN
Solar/Wind Harmer
0.068
966001AG1-469 GEN
Solar/Wind Helper
0.206
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
0.137
LAGNLTFEXP_LAGN->PJM
CLTF
1.972
WECLTFEXP_WEC->PJM
CLTF
0.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.458
TVALTFEXP_TVA->PJM
CLTF
0.973
CPLELTFEXP_CPLE->PJM
CLTF
4.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.705
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.642
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.131
MECLTFEXP_MEC->PJM
CLTF
0.546
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.57
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.432
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.588
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.518
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.598
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.485
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.586
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.841
316192AB2-158 GEN
Solar/Wind Helper
1.013
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.849
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.338
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.897
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.801
970681AG2-440 GEN
Solar/Wind Harmer
13.441
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.193
3146396TANGLEW
Solar/Wind Harmer
0.132
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316420AA1-050 GEN
Solar/Wind Harmer
0.816
316305AF2-043 C
Solar/Wind Harmer
0.215
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.362
970323AG2-213 GEN
Solar/Wind Harmer
9.73
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.78
966001AG1-469 GEN
Solar/Wind Helper
0.216
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
WECLTFEXP_WEC->PJM
CLTF
0.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.39 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1475.54
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.46
3151911BEARGRDN G1
50/50
4.23
3144293JTRSVLE
50/50
0.704
970119AG2-088 GEN
50/50
15.406
972003AH1-546 GEN
Solar/Wind Harmer
24.587
971377AH1-170 GEN
Solar/Wind Harmer
5.686
3147623JAMES R
Solar/Wind Harmer
0.704
970937AG2-583 GEN
Solar/Wind Harmer
30.517
316322AB2-045
Solar/Wind Harmer
1.382
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.597
3143336POWHATN
Solar/Wind Harmer
3.349
963171AG1-166 GEN
Solar/Wind Harmer
2.929
971563AH1-280 GEN
Solar/Wind Harmer
2.929
970685AG2-442 GEN
Solar/Wind Harmer
18.817
962491AG1-098 GEN
Solar/Wind Harmer
10.277
315693AD1-088 GEN
Solar/Wind Harmer
7.416
316237AB2-079_GEN
Solar/Wind Harmer
0.439
3143226MDLTHAN
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
38.531
970401AG2-262 GEN
Solar/Wind Harmer
0.797
315687AD1-152 GEN
Solar/Wind Harmer
1.353
971065AG2-659 GEN
Solar/Wind Harmer
5.503
3147043LAWRENC
Adder
0.884
3143526WINTERP
Solar/Wind Harmer
-0.056
316129AC1-054 GEN
Solar/Wind Harmer
0.948
971795AH1-408 GEN
Solar/Wind Harmer
7.828
316003AC1-222 GEN
Solar/Wind Harmer
0.95
960081AF2-299 GEN
Solar/Wind Harmer
1.043
970919AG2-571 GEN
Solar/Wind Harmer
2.759
970087AG2-069 GEN
Solar/Wind Harmer
8.141
3145783HORNRTN
Solar/Wind Harmer
-0.009
316190AA2-174 GEN
Solar/Wind Harmer
0.105
940641AE2-051 GEN
Solar/Wind Harmer
7.878
3150851SPRUNCC
Adder
0.344
316023GEN1_S
Solar/Wind Harmer
0.555
939411AE1-173 GEN
Solar/Wind Harmer
40.398
316011AB1-132 GEN
Solar/Wind Harmer
1.663
962571AG1-106 GEN
Solar/Wind Harmer
1.142
3146263WOODLND
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.68
3146173TUNIS
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.782
3146233WITAKRS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.838
970659AG2-427 GEN
Solar/Wind Harmer
3.885
316381AD1-082 GEN
Solar/Wind Harmer
0.67
970661AG2-428 GEN
Solar/Wind Harmer
7.748
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.803
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3151921BEARGRDN G2
50/50
4.23
3144293JTRSVLE
50/50
0.704
970221AG2-151 GEN
Solar/Wind Harmer
28.431
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.296
316313AB2-026
Solar/Wind Harmer
0.761
316258AE1-075 C
Solar/Wind Harmer
0.685
316405AF2-144 C
Solar/Wind Harmer
0.723
3143336POWHATN
Solar/Wind Harmer
2.847
970909AG2-566 GEN
Solar/Wind Harmer
2.392
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.484
963181AG1-167 GEN
Solar/Wind Harmer
2.197
959311AF2-222 GEN
Solar/Wind Harmer
20.924
970257AG2-171 GEN
Solar/Wind Harmer
7.297
315785AD2-033 C
Solar/Wind Harmer
4.227
964241AG1-285 GEN
Solar/Wind Harmer
12.89
316131AB2-060 GEN
Solar/Wind Harmer
1.639
958131AF2-107 GEN
Solar/Wind Harmer
4.847
316478AD1-087 GEN
Solar/Wind Harmer
1.065
316486AD2-202 GEN
Solar/Wind Harmer
0.312
3147043LAWRENC
Solar/Wind Harmer
-0.007
316248AF1-058 C
Solar/Wind Harmer
0.31
960061AF2-297 GEN
Solar/Wind Harmer
5.143
966621AG1-532 GEN
Solar/Wind Harmer
0.188
971683AH1-343 GEN
Solar/Wind Harmer
3.986
313506AB2-031 GEN
Solar/Wind Harmer
0.724
970917AG2-570 GEN
Solar/Wind Harmer
21.795
3150861SPRUNCD
Adder
0.344
316365GEN2_N
Solar/Wind Harmer
0.555
3156081AA2-088 GEN
Solar/Wind Harmer
2.585
3146263WOODLND
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.224
3146173TUNIS
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.125
316140AB2-099
Solar/Wind Harmer
0.052
316359AB2-059 GEN
Solar/Wind Harmer
0.974
316049AB1-081 GEN
Solar/Wind Harmer
0.78
316093AE2-104_GEN
Solar/Wind Harmer
2.1
3142053HEARTS
Solar/Wind Harmer
0.085
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Harmer
-0.001
315800Z1-036_GEN1
Solar/Wind Harmer
1.779
972205AH1-687 GEN
50/50
20.633
316303AF2-085
50/50
2.054
971447AH1-217 GEN
Solar/Wind Harmer
14.896
971845AH1-439 GEN
Solar/Wind Harmer
21.465
970285AG2-188 GEN
Solar/Wind Harmer
34.19
270494AE1-108_GEN
Solar/Wind Harmer
9.286
315657AE1-056 GEN
Solar/Wind Harmer
9.291
946301AF1-294 GEN
Solar/Wind Harmer
6.004
961791AG1-021 GEN
Solar/Wind Harmer
2.929
970683AG2-441 GEN
Solar/Wind Harmer
16.8
970681AG2-440 GEN
Solar/Wind Harmer
13.44
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.796
316239AB2-077_GEN
Solar/Wind Harmer
0.439
316238AB2-078_GEN
Solar/Wind Harmer
0.439
316118AC1-105 GEN
Solar/Wind Harmer
0.773
316233AE1-074 FULL
Solar/Wind Harmer
0.293
971281AH1-106 GEN
Solar/Wind Harmer
1.769
971283AH1-107 GEN
Solar/Wind Harmer
1.769
970831AG2-522 GEN
Solar/Wind Harmer
5.308
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971967AH1-528 GEN
Solar/Wind Harmer
18.09
946281AF1-292 GEN
Solar/Wind Harmer
0.208
316087AB2-174 GEN
Solar/Wind Harmer
1.297
970673AG2-436 GEN
Solar/Wind Harmer
18.787
970673AG2-436 GEN
Solar/Wind Harmer
9.512
941031AE2-094 GEN
Solar/Wind Harmer
16.63
944011AF1-069 GEN
Solar/Wind Harmer
5.211
3137643SOCKMAN
Solar/Wind Harmer
-0.035
970865AG2-541 GEN
Solar/Wind Harmer
3.55
970085AG2-068 GEN
Solar/Wind Harmer
5.427
970581AG2-369 GEN
Solar/Wind Harmer
4.667
315607AA1-063A GEN
Solar/Wind Harmer
0.852
3146043SEABORD
Solar/Wind Harmer
-0.008
971285AH1-108 GEN
Adder
0.562
315814AE2-033 C
Solar/Wind Harmer
7.6
316315AB2-025 C
Solar/Wind Harmer
0.22
965291AG1-394 GEN
Solar/Wind Harmer
0.71
315652AC1-086 GEN
Solar/Wind Harmer
8.941
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.031
316123AC1-075 GEN
Solar/Wind Harmer
0.832
970165AG2-112 GEN
Solar/Wind Harmer
0.733
970163AG2-111 GEN
Solar/Wind Harmer
0.699
3145513AHOSKIE
Solar/Wind Harmer
0.067
961941AG1-037 GEN
Solar/Wind Harmer
0.058
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.03
316319Z2-044 C
Solar/Wind Harmer
0.41
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.217
315732AD1-074 GEN1
Solar/Wind Harmer
1.475
315733AD1-074 GEN2
Solar/Wind Harmer
1.475
315735AD1-075 GEN1
Solar/Wind Harmer
0.737
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315833AF1-017_GEN
Solar/Wind Harmer
1.378
316349AD2-085 GEN
Solar/Wind Harmer
0.645
315816AE2-034 GEN
Solar/Wind Harmer
0.587
316311AC2-079 GEN
Solar/Wind Harmer
3.659
315835AF2-110_GEN
Solar/Wind Harmer
0.903
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.779
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.193
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.132
316174AB2-169 GEN
Solar/Wind Harmer
1.109
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
961671AG1-007 GEN
Solar/Wind Harmer
0.09
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.212
316246AF1-032 C
Solar/Wind Harmer
0.144
3146293MARTNCO
Solar/Wind Harmer
0.044
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.48
944591AF1-124 GEN
Solar/Wind Harmer
32.454
3150981CHESPKA
Adder
0.786
3151171GRAVELC
Adder
0.645
3143096IRON208
Adder
0.253
944631AF1-128 GEN
Adder
26.842
316192AB2-158 GEN
Solar/Wind Helper
1.014
3147666LOUISA
Solar/Wind Helper
0.589
3147983MERCK5
Solar/Wind Helper
0.055
3144293JTRSVLE
50/50
0.704
3144293JTRSVLE
50/50
0.593
970535AG2-341 GEN
50/50
2.107
971489AH1-241 GEN
Solar/Wind Harmer
26.992
3146776BUCKING
Solar/Wind Harmer
-0.164
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.547
970301AG2-198 GEN
Solar/Wind Harmer
12.599
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.661
963191AG1-168 GEN
Solar/Wind Harmer
2.197
971741AH1-377 GEN
Solar/Wind Harmer
26.527
316034AC1-036 C
Solar/Wind Harmer
0.361
970323AG2-213 GEN
Solar/Wind Harmer
9.729
971775AH1-396 GEN
Solar/Wind Harmer
1.386
313527AB2-043 GEN
Solar/Wind Harmer
2.416
971223AH1-071 GEN
Solar/Wind Harmer
1.623
962561AG1-105 GEN
Solar/Wind Harmer
7.096
939181AE1-148 GEN
Solar/Wind Harmer
7.013
970099AG2-077 GEN
Solar/Wind Harmer
15.412
964791AG1-342 GEN
Solar/Wind Harmer
2.608
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
3143526WINTERP
Solar/Wind Harmer
-0.056
970933AG2-581 GEN
Solar/Wind Harmer
9.821
972187AH1-678 GEN
Adder
2.289
962331AG1-082 GEN
Solar/Wind Harmer
0.963
316317KELFORD C
Solar/Wind Harmer
0.363
3145823KELFORD
Solar/Wind Harmer
-0.008
316327AA2-057 GEN
Solar/Wind Harmer
0.766
315724AD1-057 GEN
Solar/Wind Harmer
0.43
3145273HOLLAND
Solar/Wind Harmer
-0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.002
3146233WITAKRS
Solar/Wind Harmer
0.155
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
4.587
970659AG2-427 GEN
Solar/Wind Harmer
0.688
316083AB2-161 GEN
Solar/Wind Harmer
1.186
315839AE2-212 C
Solar/Wind Harmer
0.22
970661AG2-428 GEN
Solar/Wind Harmer
1.373
315737AD1-076 GEN
Solar/Wind Harmer
1.386
316283AC2-100 C
Solar/Wind Harmer
0.686
971157AH1-035 GEN
Solar/Wind Harmer
0.911
315614AA2-178 GEN
Solar/Wind Harmer
0.783
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.858
3146516WINFALL
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.896
316435W1029_GEN3
Solar/Wind Harmer
1.299
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.891
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.868
3151101ELIZAR3
Adder
5.85
3151221GRAVEL6
Adder
4.406
3151171GRAVELC
Adder
0.848
3143096IRON208
Adder
0.253
3143096IRON208
Adder
0.248
3132273ORANGE
Solar/Wind Helper
0.031
316499AE2-029_GEN
Solar/Wind Helper
0.505
3147666LOUISA
Solar/Wind Helper
0.339
3148013FISHERV
Solar/Wind Helper
0.13
315616AA1-038_C
Solar/Wind Helper
0.528
944581AF1-123 GEN
Solar/Wind Harmer
20.452
316181AB2-040 GEN
Solar/Wind Harmer
1.257
972185AH1-677 GEN
Adder
4.486
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.816
3145783HORNRTN
Solar/Wind Harmer
0.255
3145783HORNRTN
Solar/Wind Harmer
0.102
316426AA2-053 GEN
Solar/Wind Harmer
0.862
3144356SAPONY
Solar/Wind Harmer
0.284
316274AC1-208 GEN
Solar/Wind Harmer
0.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.79
316222AC1-221 GEN
Solar/Wind Harmer
0.745
316065AD1-022 GEN
Solar/Wind Harmer
3.665
970657AG2-426 GEN
Solar/Wind Harmer
2.282
970657AG2-426 GEN
Solar/Wind Harmer
0.477
316263AC1-034 GEN
Solar/Wind Harmer
3.387
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
961601AG1-000A GEN
Solar/Wind Harmer
2.822
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.299
316433W1029_GEN2
Solar/Wind Harmer
1.299
3145493TOT1
Solar/Wind Harmer
0.111
3145453TOT5
Solar/Wind Harmer
0.066
3145603CNETO
Solar/Wind Harmer
0.044
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.028
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.841
316018AA1-139 ULT2
Solar/Wind Harmer
0.61
316017AA1-139 ULT1
Solar/Wind Harmer
0.576
316339AD2-160 GEN
Solar/Wind Harmer
0.48
3150991CHESPKB
Adder
0.66
3150991CHESPKB
Adder
0.644
944641AF1-129 GEN
Adder
29.781
966001AG1-469 GEN
Solar/Wind Helper
0.216
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
313526AB2-022
Solar/Wind Harmer
0.193
316305AF2-043 C
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.816
957861AF2-080 GEN
Solar/Wind Harmer
3.119
3146406KITTY HAWK
Solar/Wind Harmer
0.006
319010AE1-072 C
Solar/Wind Harmer
1.441
957871AF2-081 GEN
Solar/Wind Harmer
3.56
3151081ELIZAR1
Adder
5.776
3151091ELIZAR2
Adder
5.675
3152611GOSPORTB
Adder
0.802
3152621GOSPORTC
Adder
0.681
3152601GOSPORTA
Adder
0.628
972265AH1-717 GEN
Adder
4.706
3151201GRAVEL4
Adder
4.411
3151191GRAVEL3
Adder
4.355
3151211GRAVEL5
Adder
4.355
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.078
3148013FISHERV
Solar/Wind Helper
0.075
3148463FAIRFLD
Solar/Wind Helper
0.116
NYPJM->LTFIMP_NY
CLTF
0.612
LGEELTFEXP_LGEE->PJM
CLTF
0.133
LAGNLTFEXP_LAGN->PJM
CLTF
1.959
WECLTFEXP_WEC->PJM
CLTF
0.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.437
TVALTFEXP_TVA->PJM
CLTF
0.967
CPLELTFEXP_CPLE->PJM
CLTF
4.206
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.626
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.572
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.107
MECLTFEXP_MEC->PJM
CLTF
0.537
SIGELTFEXP_SIGE->PJM
CLTF
0.014

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:4.2
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
NYPJM->LTFIMP_NY
CLTF
0.577
LGEELTFEXP_LGEE->PJM
CLTF
0.104
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.94 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:1415.27
MW Contribution:4.2
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.533
3151911BEARGRDN G1
50/50
4.287
3144293JTRSVLE
50/50
0.699
970119AG2-088 GEN
50/50
18.19
972003AH1-546 GEN
Solar/Wind Harmer
24.898
971377AH1-170 GEN
Solar/Wind Harmer
5.763
3147623JAMES R
Solar/Wind Harmer
0.713
970937AG2-583 GEN
Solar/Wind Harmer
31.282
316322AB2-045
Solar/Wind Harmer
1.394
3146776BUCKING
Solar/Wind Harmer
-0.016
316336AC2-165 C
Solar/Wind Harmer
5.86
3146926FARMVIL
Solar/Wind Harmer
-0.02
3143336POWHATN
Solar/Wind Harmer
3.549
963171AG1-166 GEN
Solar/Wind Harmer
2.905
971563AH1-280 GEN
Solar/Wind Harmer
2.905
970685AG2-442 GEN
Solar/Wind Harmer
18.606
3143226MDLTHAN
Solar/Wind Harmer
-0.015
962491AG1-098 GEN
Solar/Wind Harmer
9.894
315693AD1-088 GEN
Solar/Wind Harmer
7.12
316237AB2-079_GEN
Solar/Wind Harmer
0.427
3143526WINTERP
Solar/Wind Harmer
-0.065
970401AG2-262 GEN
Solar/Wind Harmer
0.767
957481AF2-042 GEN
Solar/Wind Harmer
36.362
315687AD1-152 GEN
Solar/Wind Harmer
1.282
971065AG2-659 GEN
Solar/Wind Harmer
5.251
3147043LAWRENC
Adder
0.844
316129AC1-054 GEN
Solar/Wind Harmer
0.904
971795AH1-408 GEN
Solar/Wind Harmer
7.449
3150851SPRUNCC
Adder
0.382
316003AC1-222 GEN
Solar/Wind Harmer
0.906
960081AF2-299 GEN
Solar/Wind Harmer
0.983
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
970919AG2-571 GEN
Solar/Wind Harmer
2.482
970087AG2-069 GEN
Solar/Wind Harmer
7.326
3142543TWELFTH
Solar/Wind Harmer
-0.001
316023GEN1_S
Solar/Wind Harmer
0.518
940641AE2-051 GEN
Solar/Wind Harmer
6.973
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.551
962571AG1-106 GEN
Solar/Wind Harmer
1.066
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.219
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
316212AC1-099_GEN
Solar/Wind Harmer
0.635
3146173TUNIS
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
36.08
3145823KELFORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315671AE2-027_GEN
Solar/Wind Harmer
5.319
970659AG2-427 GEN
Solar/Wind Harmer
3.71
316381AD1-082 GEN
Solar/Wind Harmer
0.639
315722AD1-056 GEN
Solar/Wind Harmer
0.728
970661AG2-428 GEN
Solar/Wind Harmer
7.356
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.706
970129AG2-093 GEN
Solar/Wind Harmer
1.536
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316458AB2-190 GEN2
Solar/Wind Harmer
0.68
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.303
316359AB2-059 GEN
Solar/Wind Harmer
0.905
316049AB1-081 GEN
Solar/Wind Harmer
0.725
3142053HEARTS
Solar/Wind Harmer
0.079
316093AE2-104_GEN
Solar/Wind Harmer
1.951
3145963POPLR C
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971069AG2-661 GEN
Solar/Wind Harmer
1.057
316174AB2-169 GEN
Solar/Wind Harmer
1.029
315800Z1-036_GEN1
Solar/Wind Harmer
1.645
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3146083TARBORO
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.197
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.041
316494AC1-189 GEN
Solar/Wind Harmer
0.712
971647AH1-324 GEN
Solar/Wind Harmer
3.305
316246AF1-032 C
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944631AF1-128 GEN
Adder
27.913
3146456SLIGO L269
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
3.242
316388AE2-253 GEN
Solar/Wind Harmer
0.443
316375AC2-012 GEN
Solar/Wind Harmer
2.263
3150981CHESPKA
Adder
0.727
3151171GRAVELC
Adder
0.617
3147983MERCK5
Solar/Wind Helper
0.054
316192AB2-158 GEN
Solar/Wind Helper
0.88
3147666LOUISA
Solar/Wind Helper
0.508
944591AF1-124 GEN
Solar/Wind Harmer
8.419
3144293JTRSVLE
50/50
0.699
3144293JTRSVLE
50/50
0.588
970535AG2-341 GEN
50/50
2.034
971489AH1-241 GEN
Solar/Wind Harmer
27.358
3146776BUCKING
Solar/Wind Harmer
-0.165
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.65
970301AG2-198 GEN
Solar/Wind Harmer
12.49
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.631
963191AG1-168 GEN
Solar/Wind Harmer
2.179
971741AH1-377 GEN
Solar/Wind Harmer
26.175
316034AC1-036 C
Solar/Wind Harmer
0.356
970323AG2-213 GEN
Solar/Wind Harmer
9.582
971775AH1-396 GEN
Solar/Wind Harmer
1.365
971223AH1-071 GEN
Solar/Wind Harmer
1.916
313527AB2-043 GEN
Solar/Wind Harmer
2.349
3143526WINTERP
Solar/Wind Harmer
-0.065
962561AG1-105 GEN
Solar/Wind Harmer
6.845
939181AE1-148 GEN
Solar/Wind Harmer
6.741
964791AG1-342 GEN
Solar/Wind Harmer
2.511
3146843MT LREL
Solar/Wind Harmer
-0.012
3146843MT LREL
Solar/Wind Harmer
-0.012
970099AG2-077 GEN
Solar/Wind Harmer
14.545
970933AG2-581 GEN
Solar/Wind Harmer
9.023
316181AB2-040 GEN
Solar/Wind Harmer
1.184
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.923
3145593CAROLNA
Solar/Wind Harmer
0.068
972187AH1-678 GEN
Adder
2.055
3145783HORNRTN
Solar/Wind Harmer
0.958
3145783HORNRTN
Solar/Wind Harmer
0.767
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
972185AH1-677 GEN
Adder
4.016
316426AA2-053 GEN
Solar/Wind Harmer
0.809
3144356SAPONY
Solar/Wind Harmer
0.264
316274AC1-208 GEN
Solar/Wind Harmer
0.799
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
0.206
3145893MURPHYS
Solar/Wind Harmer
-0.013
3145796HORNRTN
Solar/Wind Harmer
-0.022
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316240AF1-291 C
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
30.235
315742AE1-103 GEN
Solar/Wind Harmer
0.736
970657AG2-426 GEN
Solar/Wind Harmer
2.172
970657AG2-426 GEN
Solar/Wind Harmer
0.454
316222AC1-221 GEN
Solar/Wind Harmer
0.698
316065AD1-022 GEN
Solar/Wind Harmer
3.4
942751AE2-291 GEN
Solar/Wind Harmer
4.316
316263AC1-034 GEN
Solar/Wind Harmer
3.148
3146376EDENTON
Solar/Wind Harmer
0.198
3146376EDENTON
Solar/Wind Harmer
0.198
961601AG1-000A GEN
Solar/Wind Harmer
2.622
316033AB2-134 GEN
Solar/Wind Harmer
2.144
315697AD1-025 GEN
Solar/Wind Harmer
1.345
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
3145453TOT5
Solar/Wind Harmer
0.062
3145603CNETO
Solar/Wind Harmer
0.041
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316431W1029_GEN1
Solar/Wind Harmer
1.2
316433W1029_GEN2
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.026
3137176SLIGO L2192
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
0.776
316018AA1-139 ULT2
Solar/Wind Harmer
0.563
316017AA1-139 ULT1
Solar/Wind Harmer
0.531
316339AD2-160 GEN
Solar/Wind Harmer
0.443
3142366NRTHEST
Adder
0.191
3145506HICKORY
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
316185AD1-033 GEN
Solar/Wind Harmer
0.691
3142956BIRDNECK
Solar/Wind Harmer
0.351
316316AC1-027 C
Solar/Wind Harmer
0.201
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.61
3150991CHESPKB
Adder
0.595
3150691DARBY 3
Adder
4.082
3150701DARBY 4
Adder
4.072
3150681DARBY 2
Adder
4.067
3150671DARBY 1
Adder
4.063
966001AG1-469 GEN
Solar/Wind Helper
0.202
972205AH1-687 GEN
50/50
20.91
316303AF2-085
50/50
2.425
971447AH1-217 GEN
Solar/Wind Harmer
15.108
971845AH1-439 GEN
Solar/Wind Harmer
21.634
970285AG2-188 GEN
Solar/Wind Harmer
34.428
270494AE1-108_GEN
Solar/Wind Harmer
9.407
315657AE1-056 GEN
Solar/Wind Harmer
9.233
946301AF1-294 GEN
Solar/Wind Harmer
5.956
961791AG1-021 GEN
Solar/Wind Harmer
2.905
970683AG2-441 GEN
Solar/Wind Harmer
16.612
970681AG2-440 GEN
Solar/Wind Harmer
13.29
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.737
316239AB2-077_GEN
Solar/Wind Harmer
0.427
316238AB2-078_GEN
Solar/Wind Harmer
0.427
316233AE1-074 FULL
Solar/Wind Harmer
0.341
971281AH1-106 GEN
Solar/Wind Harmer
2.057
971283AH1-107 GEN
Solar/Wind Harmer
2.057
316118AC1-105 GEN
Solar/Wind Harmer
0.741
970831AG2-522 GEN
Solar/Wind Harmer
5.054
3147173SINAI
Solar/Wind Harmer
-0.01
3147243WELCO
Solar/Wind Harmer
-0.006
971285AH1-108 GEN
Adder
0.625
946281AF1-292 GEN
Solar/Wind Harmer
0.196
971967AH1-528 GEN
Solar/Wind Harmer
16.369
316087AB2-174 GEN
Solar/Wind Harmer
1.222
970865AG2-541 GEN
Solar/Wind Harmer
3.392
3137643SOCKMAN
Solar/Wind Harmer
-0.033
970673AG2-436 GEN
Solar/Wind Harmer
16.777
970673AG2-436 GEN
Solar/Wind Harmer
8.495
315607AA1-063A GEN
Solar/Wind Harmer
0.8
941031AE2-094 GEN
Solar/Wind Harmer
14.78
944011AF1-069 GEN
Solar/Wind Harmer
4.631
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.884
970581AG2-369 GEN
Solar/Wind Harmer
4.201
315814AE2-033 C
Solar/Wind Harmer
7.048
316315AB2-025 C
Solar/Wind Harmer
0.204
965291AG1-394 GEN
Solar/Wind Harmer
0.664
315652AC1-086 GEN
Solar/Wind Harmer
8.34
316123AC1-075 GEN
Solar/Wind Harmer
0.797
970165AG2-112 GEN
Solar/Wind Harmer
0.701
970163AG2-111 GEN
Solar/Wind Harmer
0.669
316318V4-068
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.003
3143316POE
Solar/Wind Harmer
-0.029
3146033SCOT NK
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.063
961941AG1-037 GEN
Solar/Wind Harmer
0.054
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
316319Z2-044 C
Solar/Wind Harmer
0.381
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.985
315833AF1-017_GEN
Solar/Wind Harmer
1.293
316349AD2-085 GEN
Solar/Wind Harmer
0.606
316311AC2-079 GEN
Solar/Wind Harmer
3.434
315732AD1-074 GEN1
Solar/Wind Harmer
1.367
315733AD1-074 GEN2
Solar/Wind Harmer
1.367
315735AD1-075 GEN1
Solar/Wind Harmer
0.684
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.68
315816AE2-034 GEN
Solar/Wind Harmer
0.544
315835AF2-110_GEN
Solar/Wind Harmer
0.839
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.645
316369SG1_INVT
Solar/Wind Harmer
1.188
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
316420AA1-050 GEN
Solar/Wind Harmer
0.757
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.895
316321Z2-027
Solar/Wind Harmer
0.178
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.122
316305AF2-043 C
Solar/Wind Harmer
0.199
313526AB2-022
Solar/Wind Harmer
0.178
316005AA1-067
Solar/Wind Harmer
0.133
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970181AG2-120 GEN
Solar/Wind Harmer
0.865
3146406KITTY HAWK
Solar/Wind Harmer
0.005
319010AE1-072 C
Solar/Wind Harmer
1.33
957871AF2-081 GEN
Solar/Wind Harmer
3.284
3152611GOSPORTB
Adder
0.742
3152621GOSPORTC
Adder
0.629
3152601GOSPORTA
Adder
0.581
3151081ELIZAR1
Adder
5.335
3151091ELIZAR2
Adder
5.243
972265AH1-717 GEN
Adder
4.506
3151201GRAVEL4
Adder
4.224
3151191GRAVEL3
Adder
4.17
3151211GRAVEL5
Adder
4.17
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3148463FAIRFLD
Solar/Wind Helper
0.113
3151921BEARGRDN G2
50/50
4.287
3144293JTRSVLE
50/50
0.699
970221AG2-151 GEN
Solar/Wind Harmer
28.817
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
316313AB2-026
Solar/Wind Harmer
0.807
316258AE1-075 C
Solar/Wind Harmer
0.726
316405AF2-144 C
Solar/Wind Harmer
0.766
3143336POWHATN
Solar/Wind Harmer
3.017
942461AE2-259 GEN
Solar/Wind Harmer
4.288
970909AG2-566 GEN
Solar/Wind Harmer
2.372
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.388
963181AG1-167 GEN
Solar/Wind Harmer
2.179
959311AF2-222 GEN
Solar/Wind Harmer
20.632
970257AG2-171 GEN
Solar/Wind Harmer
7.186
315785AD2-033 C
Solar/Wind Harmer
4.155
964241AG1-285 GEN
Solar/Wind Harmer
12.598
316131AB2-060 GEN
Solar/Wind Harmer
1.595
958131AF2-107 GEN
Solar/Wind Harmer
4.893
316478AD1-087 GEN
Solar/Wind Harmer
1.01
316486AD2-202 GEN
Solar/Wind Harmer
0.296
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.296
960061AF2-297 GEN
Solar/Wind Harmer
4.904
3150861SPRUNCD
Adder
0.382
971683AH1-343 GEN
Solar/Wind Harmer
3.805
966621AG1-532 GEN
Solar/Wind Harmer
0.177
313506AB2-031 GEN
Solar/Wind Harmer
0.682
970917AG2-570 GEN
Solar/Wind Harmer
19.61
316365GEN2_N
Solar/Wind Harmer
0.518
3156081AA2-088 GEN
Solar/Wind Harmer
2.417
3146263WOODLND
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.051
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.773
961681AG1-008 GEN
Solar/Wind Harmer
5.773
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.007
3143096IRON208
Adder
0.272
3143096IRON208
Adder
0.266
316210AC1-098 GEN
Solar/Wind Harmer
1.142
3146173TUNIS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.217
316463AE2-346 GEN
Solar/Wind Harmer
0.116
316140AB2-099
Solar/Wind Harmer
0.048
962331AG1-082 GEN
Solar/Wind Harmer
0.898
316317KELFORD C
Solar/Wind Harmer
0.338
3145823KELFORD
Solar/Wind Harmer
-0.007
965281AG1-393 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.714
315813AE1-149 C
Solar/Wind Harmer
4.418
970659AG2-427 GEN
Solar/Wind Harmer
0.658
316083AB2-161 GEN
Solar/Wind Harmer
1.131
315724AD1-057 GEN
Solar/Wind Harmer
0.4
3145273HOLLAND
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
1.304
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3146233WITAKRS
Solar/Wind Harmer
0.144
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146206CASHIE
Solar/Wind Harmer
-0.007
316283AC2-100 C
Solar/Wind Harmer
0.642
970133AG2-095 GEN
Solar/Wind Harmer
0.766
315737AD1-076 GEN
Solar/Wind Harmer
1.285
971157AH1-035 GEN
Solar/Wind Harmer
0.844
970129AG2-093 GEN
Solar/Wind Harmer
3.791
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.725
3145963POPLR C
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
315778AD1-151 GEN
Solar/Wind Harmer
5.787
961601AG1-000A GEN
Solar/Wind Harmer
2.655
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316435W1029_GEN3
Solar/Wind Harmer
1.2
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.827
316320Y1-086
Solar/Wind Harmer
0.387
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.801
961611AG1-000B GEN
Solar/Wind Harmer
1.383
3144873MCLAUGH
Solar/Wind Harmer
0
3151101ELIZAR3
Adder
5.404
3151221GRAVEL6
Adder
4.219
3151171GRAVELC
Adder
0.812
316499AE2-029_GEN
Solar/Wind Helper
0.492
3132273ORANGE
Solar/Wind Helper
0.029
3147666LOUISA
Solar/Wind Helper
0.292
3148013FISHERV
Solar/Wind Helper
0.125
315616AA1-038_C
Solar/Wind Helper
0.514
NYPJM->LTFIMP_NY
CLTF
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
1.764
LGEELTFEXP_LGEE->PJM
CLTF
0.104
WECLTFEXP_WEC->PJM
CLTF
0.046
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.761
TVALTFEXP_TVA->PJM
CLTF
0.87
CPLELTFEXP_CPLE->PJM
CLTF
3.883
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.641
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.055
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
0.452
SIGELTFEXP_SIGE->PJM
CLTF
0.012

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 39-91_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 39-91_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.53 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:950.8
MW Contribution:3.48
Bus #Bus NameTypeMW Contribution
972205AH1-687 GEN
50/50
21.692
971447AH1-217 GEN
Solar/Wind Harmer
18.622
971845AH1-439 GEN
Solar/Wind Harmer
22.237
270494AE1-108_GEN
Solar/Wind Harmer
10.551
970285AG2-188 GEN
Solar/Wind Harmer
35.335
315657AE1-056 GEN
Solar/Wind Harmer
9.243
946301AF1-294 GEN
Solar/Wind Harmer
5.939
961791AG1-021 GEN
Solar/Wind Harmer
2.897
970683AG2-441 GEN
Solar/Wind Harmer
16.461
970681AG2-440 GEN
Solar/Wind Harmer
13.169
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.67
316239AB2-077_GEN
Solar/Wind Harmer
0.407
316238AB2-078_GEN
Solar/Wind Harmer
0.407
316118AC1-105 GEN
Solar/Wind Harmer
0.689
970831AG2-522 GEN
Solar/Wind Harmer
4.571
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.238
971281AH1-106 GEN
Solar/Wind Harmer
1.438
971283AH1-107 GEN
Solar/Wind Harmer
1.438
970865AG2-541 GEN
Solar/Wind Harmer
3.115
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.055
971967AH1-528 GEN
Solar/Wind Harmer
13.769
3137643SOCKMAN
Solar/Wind Harmer
-0.029
316123AC1-075 GEN
Solar/Wind Harmer
0.731
970165AG2-112 GEN
Solar/Wind Harmer
0.643
970163AG2-111 GEN
Solar/Wind Harmer
0.614
315607AA1-063A GEN
Solar/Wind Harmer
0.681
971285AH1-108 GEN
Adder
0.449
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.72
970673AG2-436 GEN
Solar/Wind Harmer
6.947
970085AG2-068 GEN
Solar/Wind Harmer
4.042
970581AG2-369 GEN
Solar/Wind Harmer
3.477
941031AE2-094 GEN
Solar/Wind Harmer
11.972
944011AF1-069 GEN
Solar/Wind Harmer
3.751
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.127
3148463FAIRFLD
Solar/Wind Helper
0.134
3151921BEARGRDN G2
50/50
4.448
3144293JTRSVLE
50/50
0.697
970221AG2-151 GEN
Solar/Wind Harmer
32.428
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.331
316313AB2-026
Solar/Wind Harmer
0.751
316258AE1-075 C
Solar/Wind Harmer
0.676
316405AF2-144 C
Solar/Wind Harmer
0.713
3143336POWHATN
Solar/Wind Harmer
2.809
970909AG2-566 GEN
Solar/Wind Harmer
2.37
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.405
963181AG1-167 GEN
Solar/Wind Harmer
2.173
959311AF2-222 GEN
Solar/Wind Harmer
20.328
970257AG2-171 GEN
Solar/Wind Harmer
7.062
315785AD2-033 C
Solar/Wind Harmer
4.068
958131AF2-107 GEN
Solar/Wind Harmer
5.359
964241AG1-285 GEN
Solar/Wind Harmer
12.184
316131AB2-060 GEN
Solar/Wind Harmer
1.528
316478AD1-087 GEN
Solar/Wind Harmer
0.928
316486AD2-202 GEN
Solar/Wind Harmer
0.272
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.272
960061AF2-297 GEN
Solar/Wind Harmer
4.511
971683AH1-343 GEN
Solar/Wind Harmer
3.497
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.589
3150861SPRUNCD
Adder
0.274
970917AG2-570 GEN
Solar/Wind Harmer
16.228
316365GEN2_N
Solar/Wind Harmer
0.43
3148013FISHERV
Solar/Wind Helper
0.221
316499AE2-029_GEN
Solar/Wind Helper
0.571
315616AA1-038_C
Solar/Wind Helper
0.608
3132273ORANGE
Solar/Wind Helper
0.026
3151931BEARGRDN S1
50/50
5.74
3151911BEARGRDN G1
50/50
4.448
3144293JTRSVLE
50/50
0.697
971377AH1-170 GEN
Solar/Wind Harmer
6.486
3147623JAMES R
Solar/Wind Harmer
0.803
972003AH1-546 GEN
Solar/Wind Harmer
25.797
970937AG2-583 GEN
Solar/Wind Harmer
31.587
316322AB2-045
Solar/Wind Harmer
1.434
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.623
3143336POWHATN
Solar/Wind Harmer
3.304
963171AG1-166 GEN
Solar/Wind Harmer
2.897
971563AH1-280 GEN
Solar/Wind Harmer
2.897
970685AG2-442 GEN
Solar/Wind Harmer
18.436
962491AG1-098 GEN
Solar/Wind Harmer
9.378
316237AB2-079_GEN
Solar/Wind Harmer
0.407
315693AD1-088 GEN
Solar/Wind Harmer
6.713
970401AG2-262 GEN
Solar/Wind Harmer
0.72
957481AF2-042 GEN
Solar/Wind Harmer
33.181
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.173
971065AG2-659 GEN
Solar/Wind Harmer
4.785
3147043LAWRENC
Adder
0.762
316129AC1-054 GEN
Solar/Wind Harmer
0.821
971795AH1-408 GEN
Solar/Wind Harmer
6.648
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.833
960081AF2-299 GEN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.274
970919AG2-571 GEN
Solar/Wind Harmer
2.054
970087AG2-069 GEN
Solar/Wind Harmer
6.064
316023GEN1_S
Solar/Wind Harmer
0.43
3147983MERCK5
Solar/Wind Helper
0.062
3144293JTRSVLE
50/50
0.697
3144293JTRSVLE
50/50
0.587
971489AH1-241 GEN
Solar/Wind Harmer
30.786
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.481
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.621
963191AG1-168 GEN
Solar/Wind Harmer
2.173
971741AH1-377 GEN
Solar/Wind Harmer
25.942
316034AC1-036 C
Solar/Wind Harmer
0.35
970323AG2-213 GEN
Solar/Wind Harmer
9.416
971775AH1-396 GEN
Solar/Wind Harmer
1.341
313527AB2-043 GEN
Solar/Wind Harmer
2.245
962561AG1-105 GEN
Solar/Wind Harmer
6.444
939181AE1-148 GEN
Solar/Wind Harmer
6.287
964791AG1-342 GEN
Solar/Wind Harmer
2.356
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.272
971223AH1-071 GEN
Solar/Wind Harmer
1.326
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.828
316181AB2-040 GEN
Solar/Wind Harmer
1.022
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.794
3145593CAROLNA
Solar/Wind Harmer
0.059
3145783HORNRTN
Solar/Wind Harmer
0.823
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.206
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.692
972187AH1-678 GEN
Adder
1.699
972185AH1-677 GEN
Adder
3.299
966001AG1-469 GEN
Solar/Wind Helper
0.187
3132123MT JACKSON
Solar/Wind Helper
0.368
NYPJM->LTFIMP_NY
CLTF
0.409
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.035
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.087
LAGNLTFEXP_LAGN->PJM
CLTF
1.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.305
TVALTFEXP_TVA->PJM
CLTF
0.589
CPLELTFEXP_CPLE->PJM
CLTF
3.247
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.539
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.798
MECLTFEXP_MEC->PJM
CLTF
0.142
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P2-2: DOOMS B2_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: DOOMS B2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.53 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:934.63
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
0.696
3144293JTRSVLE
50/50
0.586
315821AE2-092 GEN
Solar/Wind Harmer
10.863
971489AH1-241 GEN
Solar/Wind Harmer
30.763
3146776BUCKING
Solar/Wind Harmer
-0.17
3146776BUCKING
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
12.465
3147133PAMPLIN
Solar/Wind Harmer
-0.025
3147133PAMPLIN
Solar/Wind Harmer
-0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.616
963191AG1-168 GEN
Solar/Wind Harmer
2.17
971741AH1-377 GEN
Solar/Wind Harmer
25.905
316034AC1-036 C
Solar/Wind Harmer
0.349
970323AG2-213 GEN
Solar/Wind Harmer
9.401
971775AH1-396 GEN
Solar/Wind Harmer
1.339
313527AB2-043 GEN
Solar/Wind Harmer
2.24
962561AG1-105 GEN
Solar/Wind Harmer
6.427
939181AE1-148 GEN
Solar/Wind Harmer
6.27
964791AG1-342 GEN
Solar/Wind Harmer
2.35
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
13.235
971223AH1-071 GEN
Solar/Wind Harmer
1.322
3143526WINTERP
Solar/Wind Harmer
-0.046
970933AG2-581 GEN
Solar/Wind Harmer
7.8
316181AB2-040 GEN
Solar/Wind Harmer
1.018
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.791
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.819
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
316426AA2-053 GEN
Solar/Wind Harmer
0.689
972187AH1-678 GEN
Adder
1.691
3151931BEARGRDN S1
50/50
5.736
3151911BEARGRDN G1
50/50
4.444
3144293JTRSVLE
50/50
0.696
971377AH1-170 GEN
Solar/Wind Harmer
6.481
3147623JAMES R
Solar/Wind Harmer
0.802
972003AH1-546 GEN
Solar/Wind Harmer
25.777
970937AG2-583 GEN
Solar/Wind Harmer
31.56
316322AB2-045
Solar/Wind Harmer
1.433
3146776BUCKING
Solar/Wind Harmer
-0.017
3146926FARMVIL
Solar/Wind Harmer
-0.02
316336AC2-165 C
Solar/Wind Harmer
5.617
3143336POWHATN
Solar/Wind Harmer
3.3
963171AG1-166 GEN
Solar/Wind Harmer
2.893
971563AH1-280 GEN
Solar/Wind Harmer
2.893
970685AG2-442 GEN
Solar/Wind Harmer
18.409
962491AG1-098 GEN
Solar/Wind Harmer
9.357
316237AB2-079_GEN
Solar/Wind Harmer
0.406
315693AD1-088 GEN
Solar/Wind Harmer
6.698
970401AG2-262 GEN
Solar/Wind Harmer
0.718
957481AF2-042 GEN
Solar/Wind Harmer
33.088
3143226MDLTHAN
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
1.169
971065AG2-659 GEN
Solar/Wind Harmer
4.77
3147043LAWRENC
Adder
0.76
316129AC1-054 GEN
Solar/Wind Harmer
0.818
971795AH1-408 GEN
Solar/Wind Harmer
6.626
3143526WINTERP
Solar/Wind Harmer
-0.046
316003AC1-222 GEN
Solar/Wind Harmer
0.83
960081AF2-299 GEN
Solar/Wind Harmer
0.847
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.084
3150851SPRUNCC
Adder
0.273
970919AG2-571 GEN
Solar/Wind Harmer
2.045
970087AG2-069 GEN
Solar/Wind Harmer
6.037
316023GEN1_S
Solar/Wind Harmer
0.428
3147983MERCK5
Solar/Wind Helper
0.063
972185AH1-677 GEN
Adder
3.285
966001AG1-469 GEN
Solar/Wind Helper
0.188
3132123MT JACKSON
Solar/Wind Helper
0.367
972205AH1-687 GEN
50/50
21.676
971447AH1-217 GEN
Solar/Wind Harmer
18.608
971845AH1-439 GEN
Solar/Wind Harmer
22.218
270494AE1-108_GEN
Solar/Wind Harmer
10.541
970285AG2-188 GEN
Solar/Wind Harmer
35.303
315657AE1-056 GEN
Solar/Wind Harmer
9.23
946301AF1-294 GEN
Solar/Wind Harmer
5.931
961791AG1-021 GEN
Solar/Wind Harmer
2.893
970683AG2-441 GEN
Solar/Wind Harmer
16.436
970681AG2-440 GEN
Solar/Wind Harmer
13.149
3144303KENBRDG
Solar/Wind Harmer
-0.015
971443AH1-215 GEN
Solar/Wind Harmer
3.664
316239AB2-077_GEN
Solar/Wind Harmer
0.406
316238AB2-078_GEN
Solar/Wind Harmer
0.406
316118AC1-105 GEN
Solar/Wind Harmer
0.687
970831AG2-522 GEN
Solar/Wind Harmer
4.556
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.006
316233AE1-074 FULL
Solar/Wind Harmer
0.237
971281AH1-106 GEN
Solar/Wind Harmer
1.433
971283AH1-107 GEN
Solar/Wind Harmer
1.433
970865AG2-541 GEN
Solar/Wind Harmer
3.104
946281AF1-292 GEN
Solar/Wind Harmer
0.169
316087AB2-174 GEN
Solar/Wind Harmer
1.051
971967AH1-528 GEN
Solar/Wind Harmer
13.715
3137643SOCKMAN
Solar/Wind Harmer
-0.028
316123AC1-075 GEN
Solar/Wind Harmer
0.728
970165AG2-112 GEN
Solar/Wind Harmer
0.641
970163AG2-111 GEN
Solar/Wind Harmer
0.611
315607AA1-063A GEN
Solar/Wind Harmer
0.678
971285AH1-108 GEN
Adder
0.447
3146043SEABORD
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
13.659
970673AG2-436 GEN
Solar/Wind Harmer
6.916
970085AG2-068 GEN
Solar/Wind Harmer
4.024
970581AG2-369 GEN
Solar/Wind Harmer
3.461
941031AE2-094 GEN
Solar/Wind Harmer
11.918
944011AF1-069 GEN
Solar/Wind Harmer
3.734
3138266HYDRAULIC
Solar/Wind Helper
0.021
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.136
3148013FISHERV
Solar/Wind Helper
0.13
3148463FAIRFLD
Solar/Wind Helper
0.135
3151921BEARGRDN G2
50/50
4.444
3144293JTRSVLE
50/50
0.696
970221AG2-151 GEN
Solar/Wind Harmer
32.404
3146776BUCKING
Solar/Wind Harmer
-0.015
3146926FARMVIL
Solar/Wind Harmer
-0.02
942461AE2-259 GEN
Solar/Wind Harmer
4.326
316313AB2-026
Solar/Wind Harmer
0.75
316258AE1-075 C
Solar/Wind Harmer
0.675
316405AF2-144 C
Solar/Wind Harmer
0.712
3143336POWHATN
Solar/Wind Harmer
2.805
970909AG2-566 GEN
Solar/Wind Harmer
2.367
3147133PAMPLIN
Solar/Wind Harmer
-0.077
971193AH1-056 GEN
Solar/Wind Harmer
15.384
963181AG1-167 GEN
Solar/Wind Harmer
2.17
959311AF2-222 GEN
Solar/Wind Harmer
20.295
970257AG2-171 GEN
Solar/Wind Harmer
7.05
315785AD2-033 C
Solar/Wind Harmer
4.061
958131AF2-107 GEN
Solar/Wind Harmer
5.349
964241AG1-285 GEN
Solar/Wind Harmer
12.16
316131AB2-060 GEN
Solar/Wind Harmer
1.525
316478AD1-087 GEN
Solar/Wind Harmer
0.925
316486AD2-202 GEN
Solar/Wind Harmer
0.271
3147043LAWRENC
Solar/Wind Harmer
-0.006
316248AF1-058 C
Solar/Wind Harmer
0.271
960061AF2-297 GEN
Solar/Wind Harmer
4.496
971683AH1-343 GEN
Solar/Wind Harmer
3.484
966621AG1-532 GEN
Solar/Wind Harmer
0.153
313506AB2-031 GEN
Solar/Wind Harmer
0.586
3150861SPRUNCD
Adder
0.273
970917AG2-570 GEN
Solar/Wind Harmer
16.156
316365GEN2_N
Solar/Wind Harmer
0.428
3148013FISHERV
Solar/Wind Helper
0.227
316499AE2-029_GEN
Solar/Wind Helper
0.572
315616AA1-038_C
Solar/Wind Helper
0.611
3132273ORANGE
Solar/Wind Helper
0.026
NYPJM->LTFIMP_NY
CLTF
0.42
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.046
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.122
LAGNLTFEXP_LAGN->PJM
CLTF
1.172
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.249
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.571
CPLELTFEXP_CPLE->PJM
CLTF
3.227
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.302
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.731
MECLTFEXP_MEC->PJM
CLTF
0.113
SIGELTFEXP_SIGE->PJM
CLTF
0.001

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.52 %
Rating:809.0 MVA
Rating Type:C
MVA to Mitigate:894.11
MW Contribution:3.44
Bus #Bus NameTypeMW Contribution
3151931BEARGRDN S1
50/50
5.33
3151911BEARGRDN G1
50/50
4.13
3144293JTRSVLE
50/50
0.655
972003AH1-546 GEN
Solar/Wind Harmer
23.962
971377AH1-170 GEN
Solar/Wind Harmer
5.548
3147623JAMES R
Solar/Wind Harmer
0.687
970937AG2-583 GEN
Solar/Wind Harmer
29.352
316322AB2-045
Solar/Wind Harmer
1.334
3146776BUCKING
Solar/Wind Harmer
-0.016
3146926FARMVIL
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
5.233
3143336POWHATN
Solar/Wind Harmer
3.078
963171AG1-166 GEN
Solar/Wind Harmer
2.723
971563AH1-280 GEN
Solar/Wind Harmer
2.723
970685AG2-442 GEN
Solar/Wind Harmer
17.365
962491AG1-098 GEN
Solar/Wind Harmer
8.919
316237AB2-079_GEN
Solar/Wind Harmer
0.389
315693AD1-088 GEN
Solar/Wind Harmer
6.394
970401AG2-262 GEN
Solar/Wind Harmer
0.692
957481AF2-042 GEN
Solar/Wind Harmer
31.87
3143226MDLTHAN
Solar/Wind Harmer
-0.01
315687AD1-152 GEN
Solar/Wind Harmer
1.137
971065AG2-659 GEN
Solar/Wind Harmer
4.648
3147043LAWRENC
Adder
0.737
316129AC1-054 GEN
Solar/Wind Harmer
0.798
971795AH1-408 GEN
Solar/Wind Harmer
6.453
3143526WINTERP
Solar/Wind Harmer
-0.043
316003AC1-222 GEN
Solar/Wind Harmer
0.805
960081AF2-299 GEN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.083
970919AG2-571 GEN
Solar/Wind Harmer
2.03
970087AG2-069 GEN
Solar/Wind Harmer
6
3150851SPRUNCC
Adder
0.261
3147983MERCK5
Solar/Wind Helper
0.055
3144293JTRSVLE
50/50
0.655
3144293JTRSVLE
50/50
0.551
971489AH1-241 GEN
Solar/Wind Harmer
26.337
3146776BUCKING
Solar/Wind Harmer
-0.158
3146776BUCKING
Solar/Wind Harmer
-0.013
315821AE2-092 GEN
Solar/Wind Harmer
5.386
970301AG2-198 GEN
Solar/Wind Harmer
11.705
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
958211AF2-115 GEN
Solar/Wind Harmer
3.404
963191AG1-168 GEN
Solar/Wind Harmer
2.042
971741AH1-377 GEN
Solar/Wind Harmer
24.381
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.895
971775AH1-396 GEN
Solar/Wind Harmer
1.267
313527AB2-043 GEN
Solar/Wind Harmer
2.141
962561AG1-105 GEN
Solar/Wind Harmer
6.187
939181AE1-148 GEN
Solar/Wind Harmer
6.061
964791AG1-342 GEN
Solar/Wind Harmer
2.266
3146843MT LREL
Solar/Wind Harmer
-0.011
3146843MT LREL
Solar/Wind Harmer
-0.011
970099AG2-077 GEN
Solar/Wind Harmer
12.748
971223AH1-071 GEN
Solar/Wind Harmer
1.248
3143526WINTERP
Solar/Wind Harmer
-0.043
970933AG2-581 GEN
Solar/Wind Harmer
7.571
316181AB2-040 GEN
Solar/Wind Harmer
1.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.784
3145593CAROLNA
Solar/Wind Harmer
0.058
3145783HORNRTN
Solar/Wind Harmer
0.814
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.081
316426AA2-053 GEN
Solar/Wind Harmer
0.684
972187AH1-678 GEN
Adder
1.664
972185AH1-677 GEN
Adder
3.229
966001AG1-469 GEN
Solar/Wind Helper
0.189
972205AH1-687 GEN
50/50
20.143
971447AH1-217 GEN
Solar/Wind Harmer
14.529
971845AH1-439 GEN
Solar/Wind Harmer
20.7
970285AG2-188 GEN
Solar/Wind Harmer
32.906
270494AE1-108_GEN
Solar/Wind Harmer
9.015
315657AE1-056 GEN
Solar/Wind Harmer
8.675
946301AF1-294 GEN
Solar/Wind Harmer
5.582
961791AG1-021 GEN
Solar/Wind Harmer
2.723
970683AG2-441 GEN
Solar/Wind Harmer
15.505
970681AG2-440 GEN
Solar/Wind Harmer
12.404
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.467
316239AB2-077_GEN
Solar/Wind Harmer
0.389
316238AB2-078_GEN
Solar/Wind Harmer
0.389
316118AC1-105 GEN
Solar/Wind Harmer
0.665
970831AG2-522 GEN
Solar/Wind Harmer
4.449
3147173SINAI
Solar/Wind Harmer
-0.009
3147243WELCO
Solar/Wind Harmer
-0.005
316233AE1-074 FULL
Solar/Wind Harmer
0.225
971281AH1-106 GEN
Solar/Wind Harmer
1.359
971283AH1-107 GEN
Solar/Wind Harmer
1.359
946281AF1-292 GEN
Solar/Wind Harmer
0.166
970865AG2-541 GEN
Solar/Wind Harmer
2.988
316087AB2-174 GEN
Solar/Wind Harmer
1.035
971967AH1-528 GEN
Solar/Wind Harmer
13.383
3137643SOCKMAN
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
0.672
3146043SEABORD
Solar/Wind Harmer
-0.007
316123AC1-075 GEN
Solar/Wind Harmer
0.694
970165AG2-112 GEN
Solar/Wind Harmer
0.611
970163AG2-111 GEN
Solar/Wind Harmer
0.583
970085AG2-068 GEN
Solar/Wind Harmer
4
970581AG2-369 GEN
Solar/Wind Harmer
3.44
970673AG2-436 GEN
Solar/Wind Harmer
13.415
970673AG2-436 GEN
Solar/Wind Harmer
6.792
971285AH1-108 GEN
Adder
0.428
3138266HYDRAULIC
Solar/Wind Helper
0.021
3151921BEARGRDN G2
50/50
4.13
3144293JTRSVLE
50/50
0.655
970221AG2-151 GEN
Solar/Wind Harmer
27.742
3146776BUCKING
Solar/Wind Harmer
-0.014
3146926FARMVIL
Solar/Wind Harmer
-0.019
942461AE2-259 GEN
Solar/Wind Harmer
4.053
316313AB2-026
Solar/Wind Harmer
0.699
316258AE1-075 C
Solar/Wind Harmer
0.63
316405AF2-144 C
Solar/Wind Harmer
0.664
3143336POWHATN
Solar/Wind Harmer
2.616
970909AG2-566 GEN
Solar/Wind Harmer
2.223
3147133PAMPLIN
Solar/Wind Harmer
-0.072
971193AH1-056 GEN
Solar/Wind Harmer
14.459
963181AG1-167 GEN
Solar/Wind Harmer
2.042
959311AF2-222 GEN
Solar/Wind Harmer
19.185
970257AG2-171 GEN
Solar/Wind Harmer
6.671
315785AD2-033 C
Solar/Wind Harmer
3.847
964241AG1-285 GEN
Solar/Wind Harmer
11.573
316131AB2-060 GEN
Solar/Wind Harmer
1.457
958131AF2-107 GEN
Solar/Wind Harmer
4.54
316478AD1-087 GEN
Solar/Wind Harmer
0.893
316486AD2-202 GEN
Solar/Wind Harmer
0.261
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.264
960061AF2-297 GEN
Solar/Wind Harmer
4.376
971683AH1-343 GEN
Solar/Wind Harmer
3.368
966621AG1-532 GEN
Solar/Wind Harmer
0.15
313506AB2-031 GEN
Solar/Wind Harmer
0.578
970917AG2-570 GEN
Solar/Wind Harmer
16.041
3150861SPRUNCD
Adder
0.261
316499AE2-029_GEN
Solar/Wind Helper
0.505
3148013FISHERV
Solar/Wind Helper
0.133
3132273ORANGE
Solar/Wind Helper
0.026
315616AA1-038_C
Solar/Wind Helper
0.545
3138266HYDRAULIC
Solar/Wind Helper
0.013
3148133STUARTS
Solar/Wind Helper
0.08
3148013FISHERV
Solar/Wind Helper
0.077
3148463FAIRFLD
Solar/Wind Helper
0.12
NYPJM->LTFIMP_NY
CLTF
0.389
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
1.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.039
TVALTFEXP_TVA->PJM
CLTF
0.757
CPLELTFEXP_CPLE->PJM
CLTF
3.638
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.961
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.309
MECLTFEXP_MEC->PJM
CLTF
0.208
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:182.88 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:930.03
MW Contribution:7.9
Bus #Bus NameTypeMW Contribution
970917AG2-570 GEN
Solar/Wind Harmer
15.316
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
961601AG1-000A GEN
Solar/Wind Harmer
5.289
971623AH1-311 GEN
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
274732ELWOOD EC;7P
Adder
4.672
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316248AF1-058 C
Solar/Wind Helper
0.977
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
315785AD2-033 C
Solar/Wind Helper
3.963
3147133PAMPLIN
Solar/Wind Helper
0.969
942461AE2-259 GEN
Solar/Wind Helper
1.948
3146926FARMVIL
Solar/Wind Helper
0.16
3146776BUCKING
Solar/Wind Helper
0.077
3147043LAWRENC
Solar/Wind Helper
0.109
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
316258AE1-075 C
Solar/Wind Helper
0.186
316405AF2-144 C
Solar/Wind Helper
0.155
315839AE2-212 C
Solar/Wind Helper
0.182
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.02
3145336SMITFLD
Solar/Wind Helper
0.053
971629AH1-314 GEN
50/50
15.388
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970919AG2-571 GEN
Solar/Wind Harmer
6.126
970223AG2-152 GEN
Solar/Wind Harmer
8.891
270016AE1-250 BESS
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3142053HEARTS
Solar/Wind Harmer
0.128
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
972273AH1-721 GEN
Adder
31.464
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274729ELWOOD EC;1P
Adder
4.672
274730ELWOOD EC;6P
Adder
4.672
274734ELWOOD EC;8P
Adder
4.672
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
315687AD1-152 GEN
Solar/Wind Helper
3.789
316003AC1-222 GEN
Solar/Wind Helper
2.887
316237AB2-079_GEN
Solar/Wind Helper
0.489
3146926FARMVIL
Solar/Wind Helper
0.16
316322AB2-045
Solar/Wind Helper
0.238
3146776BUCKING
Solar/Wind Helper
0.085
316129AC1-054 GEN
Solar/Wind Helper
0.854
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.123
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3138133OCRAN
Solar/Wind Helper
0.071
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
270013AE1-250 PV
Solar/Wind Harmer
0.003
961601AG1-000A GEN
Solar/Wind Harmer
1.322
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
316034AC1-036 C
Solar/Wind Helper
0.351
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.176
316240AF1-291 C
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
1.464
316339AD2-160 GEN
Solar/Wind Helper
0.48
316018AA1-139 ULT2
Solar/Wind Helper
0.537
316382AG1-145 C
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
316156AD2-030 GEN
Solar/Wind Helper
0.181
316280AD1-041 GEN
Solar/Wind Helper
0.403
316484AD2-074 GEN
Solar/Wind Helper
0.224
316404AE1-155 C
Solar/Wind Helper
0.968
316320Y1-086
Solar/Wind Helper
0.05
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3143526WINTERP
Solar/Wind Helper
0.647
3137176SLIGO L2192
Solar/Wind Helper
0.49
3144356SAPONY
Solar/Wind Helper
0.22
3130086AYDLETT
Solar/Wind Helper
0.486
3142946ENON
Solar/Wind Helper
0.012
316075AC2-137 C
Solar/Wind Helper
0.178
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
316077AC2-138 C
Solar/Wind Helper
0.106
970085AG2-068 GEN
Solar/Wind Harmer
9.19
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
274735ELWOOD EC;4P
Adder
4.672
274728ELWOOD EC;5P
Adder
4.672
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
972211AH1-690 GEN
Adder
28.667
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316118AC1-105 GEN
Solar/Wind Helper
2.53
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
3144303KENBRDG
Solar/Wind Helper
0.269
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
316132AB2-190 GEN1
Solar/Wind Helper
0.728
957831AF2-077 GEN
Solar/Wind Helper
0.168
316233AE1-074 FULL
Solar/Wind Helper
0.19
316349AD2-085 GEN
Solar/Wind Helper
0.563
316315AB2-025 C
Solar/Wind Helper
0.187
319010AE1-072 C
Solar/Wind Helper
1.397
316305AF2-043 C
Solar/Wind Helper
0.164
957601AF2-054 GEN
Solar/Wind Helper
0.161
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
315666AE1-190 GEN
Solar/Wind Helper
0.161
3143873LANEXA
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.12
3141913WHIT STONE
Solar/Wind Helper
0.119
3138133OCRAN
Solar/Wind Helper
0.036
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
316312AB1-027
Solar/Wind Helper
0.214
313526AB2-022
Solar/Wind Helper
0.171
3141813NORNECK
Solar/Wind Helper
0.112
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
NYPJM->LTFIMP_NY
CLTF
0.599
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:178.67 %
Rating:508.54 MVA
Rating Type:B
MVA to Mitigate:908.59
MW Contribution:7.9
Bus #Bus NameTypeMW Contribution
270018AE2-047 C O1
Solar/Wind Harmer
0.003
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.53
961601AG1-000A GEN
Solar/Wind Harmer
5.289
971623AH1-311 GEN
Solar/Wind Harmer
0.145
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.072
971367AH1-164 GEN
Solar/Wind Harmer
1.205
3146073TAR RVR
Solar/Wind Harmer
0.064
971629AH1-314 GEN
50/50
15.388
970417AG2-272 GEN
50/50
2.023
970087AG2-069 GEN
Solar/Wind Harmer
13.785
970223AG2-152 GEN
Solar/Wind Harmer
8.891
270016AE1-250 BESS
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
11.004
270574AD1-017 GEN2
Solar/Wind Harmer
0
316359AB2-059 GEN
Solar/Wind Harmer
0.261
316049AB1-081 GEN
Solar/Wind Harmer
0.416
3142053HEARTS
Solar/Wind Harmer
0.128
3145543BTLEBRO
Solar/Wind Harmer
0.072
3145543BTLEBRO
Solar/Wind Harmer
0.058
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.283
3146233WITAKRS
Solar/Wind Harmer
0.227
972273AH1-721 GEN
Adder
31.464
959091AF2-200 GEN
Solar/Wind Harmer
4.143
274729ELWOOD EC;1P
Adder
4.672
274730ELWOOD EC;6P
Adder
4.672
274734ELWOOD EC;8P
Adder
4.672
274736ELWOOD EC;9P
Adder
4.672
274676JOLIET 29;8U
Adder
8.408
315687AD1-152 GEN
Solar/Wind Helper
3.789
316003AC1-222 GEN
Solar/Wind Helper
2.887
316237AB2-079_GEN
Solar/Wind Helper
0.489
3146926FARMVIL
Solar/Wind Helper
0.16
316322AB2-045
Solar/Wind Helper
0.238
3146776BUCKING
Solar/Wind Helper
0.085
316129AC1-054 GEN
Solar/Wind Helper
0.854
316294AC1-161 GEN
Solar/Wind Helper
2.674
3147123OTTER R
Solar/Wind Helper
0.085
316336AC2-165 C
Solar/Wind Helper
0.744
316375AC2-012 GEN
Solar/Wind Helper
0.351
3145336SMITFLD
Solar/Wind Helper
0.525
316381AD1-082 GEN
Solar/Wind Helper
0.67
3143226MDLTHAN
Solar/Wind Helper
0.128
970085AG2-068 GEN
Solar/Wind Harmer
9.19
970581AG2-369 GEN
Solar/Wind Harmer
7.903
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.359
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
4.143
274731ELWOOD EC;2P
Adder
4.672
274733ELWOOD EC;3P
Adder
4.672
274735ELWOOD EC;4P
Adder
4.672
274728ELWOOD EC;5P
Adder
4.672
274675JOLIET 29;7U
Adder
8.719
274675JOLIET 29;7U
Adder
8.408
972211AH1-690 GEN
Adder
28.667
3147173SINAI
Solar/Wind Helper
0.727
3147243WELCO
Solar/Wind Helper
0.454
316118AC1-105 GEN
Solar/Wind Helper
2.53
316123AC1-075 GEN
Solar/Wind Helper
2.71
316239AB2-077_GEN
Solar/Wind Helper
0.489
316238AB2-078_GEN
Solar/Wind Helper
0.489
3144303KENBRDG
Solar/Wind Helper
0.269
3143316POE
Solar/Wind Helper
0.561
316369SG1_INVT
Solar/Wind Helper
0.616
316132AB2-190 GEN1
Solar/Wind Helper
0.728
957831AF2-077 GEN
Solar/Wind Helper
0.168
316233AE1-074 FULL
Solar/Wind Helper
0.19
316349AD2-085 GEN
Solar/Wind Helper
0.563
316315AB2-025 C
Solar/Wind Helper
0.187
319010AE1-072 C
Solar/Wind Helper
1.397
316305AF2-043 C
Solar/Wind Helper
0.164
957601AF2-054 GEN
Solar/Wind Helper
0.161
3141873WAN 176
Solar/Wind Helper
0.024
315662AE1-191 GEN
Solar/Wind Helper
0.644
315666AE1-190 GEN
Solar/Wind Helper
0.161
3143873LANEXA
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.12
3141913WHIT STONE
Solar/Wind Helper
0.119
3138133OCRAN
Solar/Wind Helper
0.036
3141783LANCAST
Solar/Wind Helper
0.071
3141783LANCAST
Solar/Wind Helper
0.047
316312AB1-027
Solar/Wind Helper
0.214
313526AB2-022
Solar/Wind Helper
0.171
3141813NORNECK
Solar/Wind Helper
0.112
270013AE1-250 PV
Solar/Wind Harmer
0.003
961601AG1-000A GEN
Solar/Wind Harmer
1.322
316263AC1-034 GEN
Solar/Wind Harmer
2.764
3145493TOT1
Solar/Wind Harmer
0.148
3145453TOT5
Solar/Wind Harmer
0.089
3145603CNETO
Solar/Wind Harmer
0.059
971341AH1-150 GEN
Solar/Wind Harmer
4.143
971343AH1-151 GEN
Solar/Wind Harmer
4.143
316222AC1-221 GEN
Solar/Wind Helper
8.797
3146843MT LREL
Solar/Wind Helper
0.574
3146843MT LREL
Solar/Wind Helper
0.574
316034AC1-036 C
Solar/Wind Helper
0.351
3147133PAMPLIN
Solar/Wind Helper
0.308
3147133PAMPLIN
Solar/Wind Helper
0.247
3146776BUCKING
Solar/Wind Helper
0.854
3146776BUCKING
Solar/Wind Helper
0.069
316036AC1-147 C
Solar/Wind Helper
0.204
3142956BIRDNECK
Solar/Wind Helper
0.089
316316AC1-027 C
Solar/Wind Helper
0.209
316185AD1-033 GEN
Solar/Wind Helper
0.62
316236AE1-162_GEN
Solar/Wind Helper
0.176
316240AF1-291 C
Solar/Wind Helper
0.176
3145506HICKORY
Solar/Wind Helper
0.519
3145506HICKORY
Solar/Wind Helper
0.311
3145506HICKORY
Solar/Wind Helper
0.078
316033AB2-134 GEN
Solar/Wind Helper
0.44
315697AD1-025 GEN
Solar/Wind Helper
1.464
316339AD2-160 GEN
Solar/Wind Helper
0.48
316018AA1-139 ULT2
Solar/Wind Helper
0.537
316017AA1-139 ULT1
Solar/Wind Helper
0.571
3143526WINTERP
Solar/Wind Helper
0.647
3137176SLIGO L2192
Solar/Wind Helper
0.49
3144356SAPONY
Solar/Wind Helper
0.22
3130086AYDLETT
Solar/Wind Helper
0.486
3142946ENON
Solar/Wind Helper
0.012
316075AC2-137 C
Solar/Wind Helper
0.178
316487AF1-042 GEN
Solar/Wind Helper
0.117
3146386ELIZ CT
Solar/Wind Helper
0.113
316077AC2-138 C
Solar/Wind Helper
0.106
316458AB2-190 GEN2
Solar/Wind Helper
0.728
316159AE1-175 C
Solar/Wind Helper
0.191
316388AE2-253 GEN
Solar/Wind Helper
0.48
3143526WINTERP
Solar/Wind Helper
0.647
316072AD1-144
Solar/Wind Helper
0.141
3146456SLIGO L269
Solar/Wind Helper
0.123
3142543TWELFTH
Solar/Wind Helper
0.012
316246AF1-032 C
Solar/Wind Helper
0.14
3142433PROV 92
Solar/Wind Helper
0.482
3141766HARMONY
Solar/Wind Helper
0.024
3138133OCRAN
Solar/Wind Helper
0.071
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142416OLDCHRC
Solar/Wind Helper
0.293
3142416OLDCHRC
Solar/Wind Helper
0.112
3146083TARBORO
Solar/Wind Harmer
0.064
3138543CONSLDL
Solar/Wind Harmer
0.039
3146233WITAKRS
Solar/Wind Harmer
0.287
3146233WITAKRS
Solar/Wind Harmer
0.039
957471AF2-041 GEN
Solar/Wind Harmer
6.215
959081AF2-199 GEN
Solar/Wind Harmer
2.072
971067AG2-660 GEN
Solar/Wind Harmer
0.691
274732ELWOOD EC;7P
Adder
4.672
274676JOLIET 29;8U
Adder
8.719
316283AC2-100 C
Solar/Wind Helper
8.307
316248AF1-058 C
Solar/Wind Helper
0.977
316478AD1-087 GEN
Solar/Wind Helper
2.495
316486AD2-202 GEN
Solar/Wind Helper
0.731
316131AB2-060 GEN
Solar/Wind Helper
2.179
315785AD2-033 C
Solar/Wind Helper
3.963
3147133PAMPLIN
Solar/Wind Helper
0.969
942461AE2-259 GEN
Solar/Wind Helper
1.948
3146926FARMVIL
Solar/Wind Helper
0.16
3146776BUCKING
Solar/Wind Helper
0.077
3147043LAWRENC
Solar/Wind Helper
0.109
315773AC2-141 GEN
Solar/Wind Helper
3.147
316313AB2-026
Solar/Wind Helper
0.207
316258AE1-075 C
Solar/Wind Helper
0.186
316405AF2-144 C
Solar/Wind Helper
0.155
315839AE2-212 C
Solar/Wind Helper
0.182
3144873MCLAUGH
Solar/Wind Helper
0.003
3144536CHRHLND
Solar/Wind Helper
0.02
3145336SMITFLD
Solar/Wind Helper
0.053
316382AG1-145 C
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.123
3142946ENON
Solar/Wind Helper
0.04
316156AD2-030 GEN
Solar/Wind Helper
0.181
316280AD1-041 GEN
Solar/Wind Helper
0.403
316484AD2-074 GEN
Solar/Wind Helper
0.224
316404AE1-155 C
Solar/Wind Helper
0.968
316320Y1-086
Solar/Wind Helper
0.05
944201AF1-088_MTX
Adder
34.575
900033ID_568986
External Queue
3.919766426086426
NYPJM->LTFIMP_NY
CLTF
0.599
LAGNLTFEXP_LAGN->PJM
CLTF
10.425
LGEELTFEXP_LGEE->PJM
CLTF
2.145
WECLTFEXP_WEC->PJM
CLTF
1.147
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.051
TVALTFEXP_TVA->PJM
CLTF
5.193
CPLELTFEXP_CPLE->PJM
CLTF
13.504
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.694
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.755
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.101
MECLTFEXP_MEC->PJM
CLTF
5.768
SIGELTFEXP_SIGE->PJM
CLTF
0.174

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.82 %
Rating:541.0 MVA
Rating Type:C
MVA to Mitigate:778.07
MW Contribution:4.35
Bus #Bus NameTypeMW Contribution
970659AG2-427 GEN
Solar/Wind Harmer
9.695
316381AD1-082 GEN
Solar/Wind Harmer
1.605
970661AG2-428 GEN
Solar/Wind Harmer
16.316
316023GEN1_S
Solar/Wind Harmer
0.661
960081AF2-299 GEN
Solar/Wind Harmer
0.988
971795AH1-408 GEN
Solar/Wind Harmer
6.141
970919AG2-571 GEN
Solar/Wind Harmer
2.572
970087AG2-069 GEN
Solar/Wind Harmer
7.581
316011AB1-132 GEN
Solar/Wind Harmer
1.656
962571AG1-106 GEN
Solar/Wind Harmer
1.138
3147043LAWRENC
Adder
0.637
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
22.41
3145783HORNRTN
Solar/Wind Harmer
-0.007
316190AA2-174 GEN
Solar/Wind Harmer
0.085
315722AD1-056 GEN
Solar/Wind Harmer
0.723
939411AE1-173 GEN
Solar/Wind Harmer
34.331
315693AD1-088 GEN
Solar/Wind Harmer
3.321
316129AC1-054 GEN
Solar/Wind Harmer
0.576
962491AG1-098 GEN
Solar/Wind Harmer
4.375
971065AG2-659 GEN
Solar/Wind Harmer
3.26
316212AC1-099_GEN
Solar/Wind Harmer
0.558
315687AD1-152 GEN
Solar/Wind Harmer
0.765
3146233WITAKRS
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
5.217
970657AG2-426 GEN
Solar/Wind Harmer
1.091
3144356SAPONY
Solar/Wind Harmer
0.467
972185AH1-677 GEN
Adder
4.31
972187AH1-678 GEN
Adder
2.152
970933AG2-581 GEN
Solar/Wind Harmer
7.613
316181AB2-040 GEN
Solar/Wind Harmer
1.119
3145796HORNRTN
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
970099AG2-077 GEN
Solar/Wind Harmer
8.964
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.807
3145593CAROLNA
Solar/Wind Harmer
0.06
3145783HORNRTN
Solar/Wind Harmer
0.84
3145783HORNRTN
Solar/Wind Harmer
0.672
3145783HORNRTN
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.084
316426AA2-053 GEN
Solar/Wind Harmer
0.701
316274AC1-208 GEN
Solar/Wind Harmer
0.71
316240AF1-291 C
Solar/Wind Helper
0.534
315813AE1-149 C
Solar/Wind Harmer
13.888
970659AG2-427 GEN
Solar/Wind Harmer
1.718
316083AB2-161 GEN
Solar/Wind Harmer
2.841
970661AG2-428 GEN
Solar/Wind Harmer
2.892
316365GEN2_N
Solar/Wind Harmer
0.661
966621AG1-532 GEN
Solar/Wind Harmer
0.178
970917AG2-570 GEN
Solar/Wind Harmer
20.318
313506AB2-031 GEN
Solar/Wind Harmer
0.645
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.398
316478AD1-087 GEN
Solar/Wind Harmer
0.587
316486AD2-202 GEN
Solar/Wind Harmer
0.172
316210AC1-098 GEN
Solar/Wind Harmer
1.005
316327AA2-057 GEN
Solar/Wind Harmer
0.647
3146233WITAKRS
Solar/Wind Harmer
0.132
3146233WITAKRS
Solar/Wind Harmer
-0.004
315779AE2-040
50/50
1.665
3143316POE
Solar/Wind Harmer
-0.171
316315AB2-025 C
Solar/Wind Harmer
0.361
315814AE2-033 C
Solar/Wind Harmer
12.304
315833AF1-017_GEN
Solar/Wind Harmer
1.911
316349AD2-085 GEN
Solar/Wind Harmer
0.895
316311AC2-079 GEN
Solar/Wind Harmer
5.027
941031AE2-094 GEN
Solar/Wind Harmer
16.77
944011AF1-069 GEN
Solar/Wind Harmer
5.255
946281AF1-292 GEN
Solar/Wind Harmer
0.197
970673AG2-436 GEN
Solar/Wind Harmer
18.349
970673AG2-436 GEN
Solar/Wind Harmer
9.291
971967AH1-528 GEN
Solar/Wind Harmer
15.986
316087AB2-174 GEN
Solar/Wind Harmer
1.177
970085AG2-068 GEN
Solar/Wind Harmer
5.054
970581AG2-369 GEN
Solar/Wind Harmer
4.347
315652AC1-086 GEN
Solar/Wind Harmer
8.907
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.003
3137643SOCKMAN
Solar/Wind Harmer
-0.03
315607AA1-063A GEN
Solar/Wind Harmer
0.69
3146043SEABORD
Solar/Wind Harmer
-0.007
970831AG2-522 GEN
Solar/Wind Harmer
3.315
316319Z2-044 C
Solar/Wind Harmer
0.349
NYPJM->LTFIMP_NY
CLTF
0.434
LAGNLTFEXP_LAGN->PJM
CLTF
2.355
LGEELTFEXP_LGEE->PJM
CLTF
0.407
WECLTFEXP_WEC->PJM
CLTF
0.212
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.464
TVALTFEXP_TVA->PJM
CLTF
1.173
CPLELTFEXP_CPLE->PJM
CLTF
3.495
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.382
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.013
MECLTFEXP_MEC->PJM
CLTF
1.138
SIGELTFEXP_SIGE->PJM
CLTF
0.034

Details for 6POE-6TYLER1 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6POE-6TYLER1 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.12 %
Rating:441.8 MVA
Rating Type:B
MVA to Mitigate:574.86
MW Contribution:2.64
Bus #Bus NameTypeMW Contribution
315779AE2-040
50/50
1.535
315244AE2-183_ST
50/50
1.743
963041AG1-153 GEN
50/50
1.603
3151281ROARAP4
50/50
0.072
3151281ROARAP4
50/50
0.067
3143316POE
Solar/Wind Harmer
1.51
316315AB2-025 C
Solar/Wind Harmer
0.089
315814AE2-033 C
Solar/Wind Harmer
8.577
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.064
316311AC2-079 GEN
Solar/Wind Harmer
2.641
316087AB2-174 GEN
Solar/Wind Harmer
0.002
315652AC1-086 GEN
Solar/Wind Harmer
7.218
3145796HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
0.025
941031AE2-094 GEN
Solar/Wind Harmer
11.623
944011AF1-069 GEN
Solar/Wind Harmer
3.798
3137643SOCKMAN
Solar/Wind Harmer
0.249
970673AG2-436 GEN
Solar/Wind Harmer
13.168
970673AG2-436 GEN
Solar/Wind Harmer
8.779
971967AH1-528 GEN
Solar/Wind Harmer
9.624
315607AA1-063A GEN
Solar/Wind Harmer
0.118
3146043SEABORD
Solar/Wind Harmer
0.058
970085AG2-068 GEN
Solar/Wind Harmer
3.066
970581AG2-369 GEN
Solar/Wind Harmer
2.637
3151391GASTONA
50/50
0.178
3151411GASTONB
50/50
0.178
3147043LAWRENC
50/50
0.61
315243AE2-183_GT3
50/50
1.008
3151051BRUNSWICKS1
50/50
1.643
3151021BRUNSWICKG1
50/50
0.791
971451AH1-221 GEN
50/50
2.404
3151261ROARAP2
50/50
0.074
970659AG2-427 GEN
Solar/Wind Harmer
7.841
316381AD1-082 GEN
Solar/Wind Harmer
0.162
970661AG2-428 GEN
Solar/Wind Harmer
13.69
316023GEN1_S
Solar/Wind Harmer
0.181
960081AF2-299 GEN
Solar/Wind Harmer
0.689
971795AH1-408 GEN
Solar/Wind Harmer
4.41
316011AB1-132 GEN
Solar/Wind Harmer
1.193
962571AG1-106 GEN
Solar/Wind Harmer
0.934
3145796HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.063
940641AE2-051 GEN
Solar/Wind Harmer
4.814
3145783HORNRTN
Solar/Wind Harmer
0.058
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.053
970087AG2-069 GEN
Solar/Wind Harmer
4.599
315722AD1-056 GEN
Solar/Wind Harmer
0.358
939411AE1-173 GEN
Solar/Wind Harmer
23.023
3151391GASTONA
50/50
0.178
3151411GASTONB
50/50
0.178
3151031BRUNSWICKG2
50/50
0.791
3151261ROARAP2
50/50
0.072
315813AE1-149 C
Solar/Wind Harmer
10.442
970659AG2-427 GEN
Solar/Wind Harmer
1.715
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
2.912
316365GEN2_N
Solar/Wind Harmer
0.181
313506AB2-031 GEN
Solar/Wind Harmer
0.204
3147043LAWRENC
Solar/Wind Harmer
0.038
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3145796HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.063
970917AG2-570 GEN
Solar/Wind Harmer
5.134
315724AD1-057 GEN
Solar/Wind Harmer
0.212
3151361ROSEMG1
50/50
0.229
3151371ROSEMS1
50/50
0.142
3151381ROSEMG2
50/50
0.107
970533AG2-339 GEN
50/50
5.61
970531AG2-338 GEN
50/50
2.244
315242AE2-183_GT2
50/50
1.008
315241AE2-183_GT1
50/50
1.002
972185AH1-677 GEN
50/50
3.634
3151041BRUNSWICKG3
50/50
0.791
972187AH1-678 GEN
50/50
1.816
970657AG2-426 GEN
Solar/Wind Harmer
5.218
970657AG2-426 GEN
Solar/Wind Harmer
1.094
3144356SAPONY
Solar/Wind Harmer
0.92
316181AB2-040 GEN
Solar/Wind Harmer
0.096
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3142666NORTHAMPTON
Solar/Wind Harmer
0.063
3142666NORTHAMPTON
Solar/Wind Harmer
0.038
3145796HORNRTN
Solar/Wind Harmer
0.19
3145593CAROLNA
Solar/Wind Harmer
0.059
3145593CAROLNA
Solar/Wind Harmer
0.059
966811AG1-552 GEN
Solar/Wind Harmer
0.643
3145593CAROLNA
Solar/Wind Harmer
0.074
3145783HORNRTN
Solar/Wind Harmer
1.04
3145783HORNRTN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
0.26
3145783HORNRTN
Solar/Wind Harmer
0.104
316426AA2-053 GEN
Solar/Wind Harmer
0.195
970933AG2-581 GEN
Solar/Wind Harmer
4.606
316240AF1-291 C
Solar/Wind Helper
0.538
NYPJM->LTFIMP_NY
CLTF
0.376
LGEELTFEXP_LGEE->PJM
CLTF
0.333
LAGNLTFEXP_LAGN->PJM
CLTF
1.956
WECLTFEXP_WEC->PJM
CLTF
0.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.263
TVALTFEXP_TVA->PJM
CLTF
0.974
CPLELTFEXP_CPLE->PJM
CLTF
2.954
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.087
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.327
MECLTFEXP_MEC->PJM
CLTF
0.935
SIGELTFEXP_SIGE->PJM
CLTF
0.028

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.79 %
Rating:997.0 MVA
Rating Type:C
MVA to Mitigate:1094.57
MW Contribution:8.57
Bus #Bus NameTypeMW Contribution
3147173SINAI
Solar/Wind Harmer
-0.042
3147243WELCO
Solar/Wind Harmer
-0.026
970865AG2-541 GEN
Solar/Wind Harmer
14.161
316118AC1-105 GEN
Solar/Wind Harmer
2.358
316123AC1-075 GEN
Solar/Wind Harmer
3.239
970165AG2-112 GEN
Solar/Wind Harmer
2.852
970163AG2-111 GEN
Solar/Wind Harmer
2.72
270455AD2-022 GEN
Solar/Wind Harmer
3.538
270457AD2-023 GEN
Solar/Wind Harmer
1.794
970085AG2-068 GEN
Solar/Wind Harmer
9.963
970581AG2-369 GEN
Solar/Wind Harmer
8.568
270069AE2-166 C O1
Solar/Wind Harmer
1.81
971981AH1-535 GEN
Solar/Wind Harmer
4.63
3143316POE
Solar/Wind Helper
0.631
316369SG1_INVT
Solar/Wind Helper
0.698
316132AB2-190 GEN1
Solar/Wind Helper
0.823
957831AF2-077 GEN
Solar/Wind Helper
0.191
319010AE1-072 C
Solar/Wind Helper
1.613
316305AF2-043 C
Solar/Wind Helper
0.188
316349AD2-085 GEN
Solar/Wind Helper
0.634
316233AE1-074 FULL
Solar/Wind Helper
0.21
957601AF2-054 GEN
Solar/Wind Helper
0.182
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.728
315666AE1-190 GEN
Solar/Wind Helper
0.182
971629AH1-314 GEN
50/50
13.518
3151561HALLBR1
50/50
0.374
24728405LEESVG
50/50
0.137
316003AC1-222 GEN
Solar/Wind Harmer
3.859
970401AG2-262 GEN
Solar/Wind Harmer
1.707
3147123OTTER R
Solar/Wind Harmer
-0.01
970087AG2-069 GEN
Solar/Wind Harmer
14.944
970919AG2-571 GEN
Solar/Wind Harmer
5.044
970223AG2-152 GEN
Solar/Wind Harmer
13.39
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.475
270016AE1-250 BESS
Solar/Wind Harmer
2.232
270574AD1-017 GEN2
Solar/Wind Harmer
4.514
270030AE2-140 GEN
Solar/Wind Harmer
14.796
270173AC1-122 GEN
Solar/Wind Harmer
1.042
316359AB2-059 GEN
Solar/Wind Harmer
0.942
316049AB1-081 GEN
Solar/Wind Harmer
0.754
3142053HEARTS
Solar/Wind Harmer
0.082
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
315687AD1-152 GEN
Solar/Wind Helper
4.938
3146926FARMVIL
Solar/Wind Helper
0.145
316322AB2-045
Solar/Wind Helper
0.216
3146776BUCKING
Solar/Wind Helper
0.078
316294AC1-161 GEN
Solar/Wind Helper
3.066
316375AC2-012 GEN
Solar/Wind Helper
0.403
3145336SMITFLD
Solar/Wind Helper
0.6
316381AD1-082 GEN
Solar/Wind Helper
0.754
316388AE2-253 GEN
Solar/Wind Helper
0.553
316458AB2-190 GEN2
Solar/Wind Helper
0.823
316159AE1-175 C
Solar/Wind Helper
0.217
3146456SLIGO L269
Solar/Wind Helper
0.142
316072AD1-144
Solar/Wind Helper
0.162
3143226MDLTHAN
Solar/Wind Helper
0.14
316246AF1-032 C
Solar/Wind Helper
0.16
316336AC2-165 C
Solar/Wind Helper
0.748
3143526WINTERP
Solar/Wind Helper
0.715
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.543
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.08
964211AG1-282 GEN
Solar/Wind Helper
0.172
3141726DUNNSVL
Solar/Wind Helper
0.511
3142416OLDCHRC
Solar/Wind Helper
0.328
3142416OLDCHRC
Solar/Wind Helper
0.126
316337AD2-073 GEN
Solar/Wind Helper
0.187
3146516WINFALL
Solar/Wind Helper
0.378
3146516WINFALL
Solar/Wind Helper
0.117
24728405LEESVG
50/50
0.137
316248AF1-058 C
Solar/Wind Harmer
1.271
960061AF2-297 GEN
Solar/Wind Harmer
21.085
971683AH1-343 GEN
Solar/Wind Harmer
16.057
316283AC2-100 C
Solar/Wind Harmer
2.823
970917AG2-570 GEN
Solar/Wind Harmer
39.848
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.475
270197AD1-017 GEN1
Solar/Wind Harmer
1.356
270018AE2-047 C O1
Solar/Wind Harmer
1.022
943811AF1-049 GEN
Solar/Wind Harmer
2.877
270336AE1-100 GEN
Solar/Wind Harmer
1.171
971367AH1-164 GEN
Solar/Wind Harmer
1.921
961601AG1-000A GEN
Solar/Wind Harmer
2.799
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Helper
3.077
316486AD2-202 GEN
Solar/Wind Helper
0.901
3146926FARMVIL
Solar/Wind Helper
0.145
3146776BUCKING
Solar/Wind Helper
0.07
315773AC2-141 GEN
Solar/Wind Helper
3.608
942461AE2-259 GEN
Solar/Wind Helper
1.129
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.204
3145336SMITFLD
Solar/Wind Helper
0.06
316382AG1-145 C
Solar/Wind Helper
0.193
3146456SLIGO L269
Solar/Wind Helper
0.142
316313AB2-026
Solar/Wind Helper
0.212
316258AE1-075 C
Solar/Wind Helper
0.191
316405AF2-144 C
Solar/Wind Helper
0.159
316156AD2-030 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.455
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.253
316320Y1-086
Solar/Wind Helper
0.058
316404AE1-155 C
Solar/Wind Helper
1.094
316473AC1-191 GEN
Solar/Wind Helper
0.742
3141906WESTMOR
Solar/Wind Helper
0.048
316435W1029_GEN3
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.117
3143873LANEXA
Solar/Wind Helper
0.081
316059AD1-063 C
Solar/Wind Helper
0.136
3141913WHIT STONE
Solar/Wind Helper
0.134
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.08
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.199
316315AB2-025 C
Solar/Wind Helper
0.198
3146486SUNBURY
Solar/Wind Helper
0.128
3146486SUNBURY
Solar/Wind Helper
0.128
3141813NORNECK
Solar/Wind Helper
0.127
316312AB1-027
Solar/Wind Helper
0.24
316321Z2-027
Solar/Wind Helper
0.192
3145176PASQUOTANK
Solar/Wind Helper
0.078
316223AC1-118
Solar/Wind Helper
0.183
3152661PLYWOOD A
50/50
0.686
316222AC1-221 GEN
Solar/Wind Harmer
3.103
942751AE2-291 GEN
Solar/Wind Harmer
17.181
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.586
962561AG1-105 GEN
Solar/Wind Harmer
12.803
316217AC1-145 GEN
Solar/Wind Harmer
2.369
316197AC1-042 GEN
Solar/Wind Harmer
1.796
942671AE2-283 GEN
Solar/Wind Harmer
4.836
270013AE1-250 PV
Solar/Wind Harmer
2.232
961601AG1-000A GEN
Solar/Wind Harmer
2.764
316263AC1-034 GEN
Solar/Wind Harmer
3.276
3146776BUCKING
Solar/Wind Helper
0.776
3146776BUCKING
Solar/Wind Helper
0.063
316036AC1-147 C
Solar/Wind Helper
0.234
3142956BIRDNECK
Solar/Wind Helper
0.103
316316AC1-027 C
Solar/Wind Helper
0.24
316185AD1-033 GEN
Solar/Wind Helper
0.713
316236AE1-162_GEN
Solar/Wind Helper
0.201
3145506HICKORY
Solar/Wind Helper
0.597
3145506HICKORY
Solar/Wind Helper
0.358
3145506HICKORY
Solar/Wind Helper
0.089
316240AF1-291 C
Solar/Wind Helper
0.197
316339AD2-160 GEN
Solar/Wind Helper
0.553
316033AB2-134 GEN
Solar/Wind Helper
0.499
315697AD1-025 GEN
Solar/Wind Helper
1.658
316018AA1-139 ULT2
Solar/Wind Helper
0.62
316017AA1-139 ULT1
Solar/Wind Helper
0.658
3137176SLIGO L2192
Solar/Wind Helper
0.566
3130086AYDLETT
Solar/Wind Helper
0.562
3143526WINTERP
Solar/Wind Helper
0.715
3142946ENON
Solar/Wind Helper
0.014
316075AC2-137 C
Solar/Wind Helper
0.2
316487AF1-042 GEN
Solar/Wind Helper
0.132
3146386ELIZ CT
Solar/Wind Helper
0.131
3144356SAPONY
Solar/Wind Helper
0.233
316077AC2-138 C
Solar/Wind Helper
0.12
966871AG1-558 GEN
Solar/Wind Helper
0.164
316431W1029_GEN1
Solar/Wind Helper
0.482
316433W1029_GEN2
Solar/Wind Helper
0.482
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
3146516WINFALL
Solar/Wind Helper
0.117
316468AD1-105 GEN
Solar/Wind Helper
0.565
NYPJM->LTFIMP_NY
CLTF
0.739
LAGNLTFEXP_LAGN->PJM
CLTF
9.252
LGEELTFEXP_LGEE->PJM
CLTF
1.997
WECLTFEXP_WEC->PJM
CLTF
1.057
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.368
TVALTFEXP_TVA->PJM
CLTF
4.632
CPLELTFEXP_CPLE->PJM
CLTF
11.178
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.871
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.227
MECLTFEXP_MEC->PJM
CLTF
5.265
SIGELTFEXP_SIGE->PJM
CLTF
0.161

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.53 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:843.75
MW Contribution:6.55
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970919AG2-571 GEN
Solar/Wind Harmer
5.079
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
970917AG2-570 GEN
Solar/Wind Harmer
12.699
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
NYPJM->LTFIMP_NY
CLTF
0.69
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.35 %
Rating:814.98 MVA
Rating Type:B
MVA to Mitigate:825.97
MW Contribution:6.55
Bus #Bus NameTypeMW Contribution
971629AH1-314 GEN
50/50
13.606
3151561HALLBR1
50/50
0.377
24728405LEESVG
50/50
0.138
970417AG2-272 GEN
50/50
1.905
24684705SMG5
50/50
0.331
970481AG2-311 GEN
50/50
4.609
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.371
3147123OTTER R
Solar/Wind Harmer
0.091
970087AG2-069 GEN
Solar/Wind Harmer
11.429
970223AG2-152 GEN
Solar/Wind Harmer
9.459
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.19
270016AE1-250 BESS
Solar/Wind Harmer
0.004
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
270030AE2-140 GEN
Solar/Wind Harmer
10.43
270173AC1-122 GEN
Solar/Wind Harmer
0.218
316359AB2-059 GEN
Solar/Wind Harmer
0.227
316049AB1-081 GEN
Solar/Wind Harmer
0.362
3142053HEARTS
Solar/Wind Harmer
0.111
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
315687AD1-152 GEN
Solar/Wind Helper
4.927
3146926FARMVIL
Solar/Wind Helper
0.143
316322AB2-045
Solar/Wind Helper
0.214
3146776BUCKING
Solar/Wind Helper
0.077
316294AC1-161 GEN
Solar/Wind Helper
3.03
316375AC2-012 GEN
Solar/Wind Helper
0.398
3145336SMITFLD
Solar/Wind Helper
0.592
316381AD1-082 GEN
Solar/Wind Helper
0.744
316388AE2-253 GEN
Solar/Wind Helper
0.545
316458AB2-190 GEN2
Solar/Wind Helper
0.811
316159AE1-175 C
Solar/Wind Helper
0.214
3146456SLIGO L269
Solar/Wind Helper
0.14
316072AD1-144
Solar/Wind Helper
0.16
3143226MDLTHAN
Solar/Wind Helper
0.138
316246AF1-032 C
Solar/Wind Helper
0.158
316336AC2-165 C
Solar/Wind Helper
0.738
3143526WINTERP
Solar/Wind Helper
0.705
3142543TWELFTH
Solar/Wind Helper
0.013
3142433PROV 92
Solar/Wind Helper
0.535
3141766HARMONY
Solar/Wind Helper
0.027
3138133OCRAN
Solar/Wind Helper
0.079
964211AG1-282 GEN
Solar/Wind Helper
0.169
3141726DUNNSVL
Solar/Wind Helper
0.503
3142416OLDCHRC
Solar/Wind Helper
0.323
3142416OLDCHRC
Solar/Wind Helper
0.124
316337AD2-073 GEN
Solar/Wind Helper
0.184
3146516WINFALL
Solar/Wind Helper
0.371
3146516WINFALL
Solar/Wind Helper
0.115
24728405LEESVG
50/50
0.138
24684605SMG4
50/50
0.864
24288905REUSENS
50/50
0.013
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
16.056
971683AH1-343 GEN
Solar/Wind Harmer
12.232
316283AC2-100 C
Solar/Wind Harmer
0.524
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.19
270197AD1-017 GEN1
Solar/Wind Harmer
0.768
270018AE2-047 C O1
Solar/Wind Harmer
0.002
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.003
971367AH1-164 GEN
Solar/Wind Harmer
1.359
961601AG1-000A GEN
Solar/Wind Harmer
4.52
971623AH1-311 GEN
Solar/Wind Harmer
0.126
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
316478AD1-087 GEN
Solar/Wind Helper
3.067
316486AD2-202 GEN
Solar/Wind Helper
0.898
3146926FARMVIL
Solar/Wind Helper
0.143
3146776BUCKING
Solar/Wind Helper
0.069
315773AC2-141 GEN
Solar/Wind Helper
3.566
942461AE2-259 GEN
Solar/Wind Helper
1.116
3144873MCLAUGH
Solar/Wind Helper
0.004
3144536CHRHLND
Solar/Wind Helper
0.023
315839AE2-212 C
Solar/Wind Helper
0.201
3145336SMITFLD
Solar/Wind Helper
0.059
316382AG1-145 C
Solar/Wind Helper
0.19
3146456SLIGO L269
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Helper
0.209
316258AE1-075 C
Solar/Wind Helper
0.188
316405AF2-144 C
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.202
316280AD1-041 GEN
Solar/Wind Helper
0.449
3142946ENON
Solar/Wind Helper
0.045
316484AD2-074 GEN
Solar/Wind Helper
0.249
316320Y1-086
Solar/Wind Helper
0.057
316404AE1-155 C
Solar/Wind Helper
1.078
316473AC1-191 GEN
Solar/Wind Helper
0.73
3141906WESTMOR
Solar/Wind Helper
0.047
316435W1029_GEN3
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3147173SINAI
Solar/Wind Harmer
0.376
3147243WELCO
Solar/Wind Harmer
0.235
970865AG2-541 GEN
Solar/Wind Harmer
10.789
316118AC1-105 GEN
Solar/Wind Harmer
0.79
316123AC1-075 GEN
Solar/Wind Harmer
0.367
970165AG2-112 GEN
Solar/Wind Harmer
2.174
970163AG2-111 GEN
Solar/Wind Harmer
2.074
970085AG2-068 GEN
Solar/Wind Harmer
7.62
970581AG2-369 GEN
Solar/Wind Harmer
6.553
270069AE2-166 C O1
Solar/Wind Harmer
0.003
971981AH1-535 GEN
Solar/Wind Harmer
2.189
3143316POE
Solar/Wind Helper
0.623
316369SG1_INVT
Solar/Wind Helper
0.688
316132AB2-190 GEN1
Solar/Wind Helper
0.811
957831AF2-077 GEN
Solar/Wind Helper
0.188
319010AE1-072 C
Solar/Wind Helper
1.59
316305AF2-043 C
Solar/Wind Helper
0.186
316349AD2-085 GEN
Solar/Wind Helper
0.625
316233AE1-074 FULL
Solar/Wind Helper
0.207
957601AF2-054 GEN
Solar/Wind Helper
0.179
3141873WAN 176
Solar/Wind Helper
0.027
315662AE1-191 GEN
Solar/Wind Helper
0.718
315666AE1-190 GEN
Solar/Wind Helper
0.179
3143873LANEXA
Solar/Wind Helper
0.08
316059AD1-063 C
Solar/Wind Helper
0.134
3141913WHIT STONE
Solar/Wind Helper
0.132
3138133OCRAN
Solar/Wind Helper
0.04
3141783LANCAST
Solar/Wind Helper
0.079
3141783LANCAST
Solar/Wind Helper
0.053
313526AB2-022
Solar/Wind Helper
0.196
316315AB2-025 C
Solar/Wind Helper
0.195
3146486SUNBURY
Solar/Wind Helper
0.126
3146486SUNBURY
Solar/Wind Helper
0.126
3141813NORNECK
Solar/Wind Helper
0.125
316312AB1-027
Solar/Wind Helper
0.236
316321Z2-027
Solar/Wind Helper
0.189
3145176PASQUOTANK
Solar/Wind Helper
0.077
316223AC1-118
Solar/Wind Helper
0.18
3152661PLYWOOD A
50/50
0.688
24684405SMG2
50/50
0.859
24684505SMG3
50/50
0.531
24684305SMG1
50/50
0.311
316222AC1-221 GEN
Solar/Wind Harmer
1.137
942751AE2-291 GEN
Solar/Wind Harmer
13.103
3146843MT LREL
Solar/Wind Harmer
0.235
3146843MT LREL
Solar/Wind Harmer
0.235
964791AG1-342 GEN
Solar/Wind Harmer
4.488
962561AG1-105 GEN
Solar/Wind Harmer
9.772
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.259
270013AE1-250 PV
Solar/Wind Harmer
0.004
961601AG1-000A GEN
Solar/Wind Harmer
1.13
316263AC1-034 GEN
Solar/Wind Harmer
2.401
3146776BUCKING
Solar/Wind Helper
0.769
3146776BUCKING
Solar/Wind Helper
0.062
316036AC1-147 C
Solar/Wind Helper
0.231
316316AC1-027 C
Solar/Wind Helper
0.237
3142956BIRDNECK
Solar/Wind Helper
0.101
316185AD1-033 GEN
Solar/Wind Helper
0.703
316236AE1-162_GEN
Solar/Wind Helper
0.199
3145506HICKORY
Solar/Wind Helper
0.589
3145506HICKORY
Solar/Wind Helper
0.353
3145506HICKORY
Solar/Wind Helper
0.088
316240AF1-291 C
Solar/Wind Helper
0.194
316339AD2-160 GEN
Solar/Wind Helper
0.545
316033AB2-134 GEN
Solar/Wind Helper
0.492
315697AD1-025 GEN
Solar/Wind Helper
1.636
316018AA1-139 ULT2
Solar/Wind Helper
0.611
316017AA1-139 ULT1
Solar/Wind Helper
0.649
3137176SLIGO L2192
Solar/Wind Helper
0.558
3130086AYDLETT
Solar/Wind Helper
0.554
3143526WINTERP
Solar/Wind Helper
0.705
3142946ENON
Solar/Wind Helper
0.013
316075AC2-137 C
Solar/Wind Helper
0.197
316487AF1-042 GEN
Solar/Wind Helper
0.13
3146386ELIZ CT
Solar/Wind Helper
0.129
3144356SAPONY
Solar/Wind Helper
0.229
316077AC2-138 C
Solar/Wind Helper
0.118
966871AG1-558 GEN
Solar/Wind Helper
0.161
316431W1029_GEN1
Solar/Wind Helper
0.474
316433W1029_GEN2
Solar/Wind Helper
0.474
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
3146516WINFALL
Solar/Wind Helper
0.115
316468AD1-105 GEN
Solar/Wind Helper
0.556
NYPJM->LTFIMP_NY
CLTF
0.69
LAGNLTFEXP_LAGN->PJM
CLTF
9.406
LGEELTFEXP_LGEE->PJM
CLTF
2.05
WECLTFEXP_WEC->PJM
CLTF
1.087
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.092
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.599
TVALTFEXP_TVA->PJM
CLTF
4.709
CPLELTFEXP_CPLE->PJM
CLTF
11.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.898
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.537
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.517
MECLTFEXP_MEC->PJM
CLTF
5.393
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 6SUMMIT-6MINE RD 230.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.56 %
Rating:1360.0 MVA
Rating Type:C
MVA to Mitigate:2251.63
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
972197AH1-683 GEN
50/50
6.75
972219AH1-694 GEN
50/50
4.86
315052AA1-145 CT2
50/50
1.183
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3150851SPRUNCC
Adder
0.37
3143526WINTERP
Solar/Wind Harmer
-0.046
3142543TWELFTH
Solar/Wind Harmer
-0.001
3143096IRON208
Adder
0.327
3143226MDLTHAN
Solar/Wind Harmer
-0.009
315671AE2-027_GEN
Solar/Wind Harmer
6.265
944631AF1-128 GEN
Adder
35.154
970129AG2-093 GEN
Solar/Wind Harmer
1.876
316458AB2-190 GEN2
Solar/Wind Harmer
0.831
971069AG2-661 GEN
Solar/Wind Harmer
1.286
970659AG2-427 GEN
Solar/Wind Harmer
4.257
971647AH1-324 GEN
Solar/Wind Harmer
4
316381AD1-082 GEN
Solar/Wind Harmer
0.733
970661AG2-428 GEN
Solar/Wind Harmer
8.426
961611AG1-000B GEN
Solar/Wind Harmer
3.913
316294AC1-161 GEN
Solar/Wind Harmer
2.543
3151171GRAVELC
Adder
0.742
3145336SMITFLD
Solar/Wind Harmer
-0.031
944591AF1-124 GEN
Solar/Wind Harmer
35.438
316375AC2-012 GEN
Solar/Wind Harmer
2.685
3150981CHESPKA
Adder
0.862
939411AE1-173 GEN
Solar/Wind Harmer
38.501
316388AE2-253 GEN
Solar/Wind Harmer
0.519
940641AE2-051 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.155
316093AE2-104_GEN
Solar/Wind Harmer
2.222
316072AD1-144
Solar/Wind Harmer
0.154
3143336POWHATN
Solar/Wind Harmer
0.906
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.83
316159AE1-175 C
Solar/Wind Harmer
0.197
316336AC2-165 C
Solar/Wind Harmer
1.276
3130156CHOWAN
Solar/Wind Harmer
-0.007
3138126ROCKLANDING
Solar/Wind Harmer
0.022
3145663CRESWEL
Solar/Wind Harmer
-0.02
971163AH1-040 GEN
Solar/Wind Harmer
6.74
316023GEN1_S
Solar/Wind Harmer
0.478
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.75
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.208
3150401LDYSMT4
50/50
43.23
3150371LDYSMT1
50/50
41.772
970497AG2-320 GEN
50/50
24.535
315051AA1-145 CT1
50/50
1.178
966881AG1-559 GEN
Solar/Wind Harmer
0.782
3142416OLDCHRC
Solar/Wind Harmer
0.967
3150861SPRUNCD
Adder
0.37
970293AG2-193 GEN
Solar/Wind Harmer
1.099
3143096IRON208
Adder
0.327
3143096IRON208
Adder
0.321
970919AG2-571 GEN
Solar/Wind Harmer
2.21
970087AG2-069 GEN
Solar/Wind Harmer
6.524
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
36.745
960081AF2-299 GEN
Solar/Wind Harmer
0.777
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146263WOODLND
Solar/Wind Harmer
-0.007
971317AH1-138 GEN
Solar/Wind Harmer
0.852
316011AB1-132 GEN
Solar/Wind Harmer
1.421
962571AG1-106 GEN
Solar/Wind Harmer
0.977
971795AH1-408 GEN
Solar/Wind Harmer
5.082
3145963POPLR C
Solar/Wind Harmer
-0.007
957481AF2-042 GEN
Solar/Wind Harmer
21.138
316190AA2-174 GEN
Solar/Wind Harmer
0.083
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Adder
0.541
316174AB2-169 GEN
Solar/Wind Harmer
1.035
315839AE2-212 C
Solar/Wind Harmer
0.256
970133AG2-095 GEN
Solar/Wind Harmer
0.941
965281AG1-393 GEN
Solar/Wind Harmer
1.043
970129AG2-093 GEN
Solar/Wind Harmer
4.632
315778AD1-151 GEN
Solar/Wind Harmer
7.043
315813AE1-149 C
Solar/Wind Harmer
5.08
3142946ENON
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
0.754
316083AB2-161 GEN
Solar/Wind Harmer
1.297
970661AG2-428 GEN
Solar/Wind Harmer
1.493
961611AG1-000B GEN
Solar/Wind Harmer
1.669
315773AC2-141 GEN
Solar/Wind Harmer
3.289
3151221GRAVEL6
Adder
5.071
3151171GRAVELC
Adder
0.976
3145336SMITFLD
Solar/Wind Harmer
-0.003
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
35.31
944601AF1-125 GEN
Solar/Wind Harmer
34.759
3151101ELIZAR3
Adder
6.413
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
0.935
316313AB2-026
Solar/Wind Harmer
0.206
316258AE1-075 C
Solar/Wind Harmer
0.185
316405AF2-144 C
Solar/Wind Harmer
0.196
3143336POWHATN
Solar/Wind Harmer
0.77
316320Y1-086
Solar/Wind Harmer
0.445
316435W1029_GEN3
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
0.8
316382AG1-145 C
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.245
3150921YORKTN3
Adder
1.611
315614AA2-178 GEN
Solar/Wind Harmer
0.776
316365GEN2_N
Solar/Wind Harmer
0.478
971157AH1-035 GEN
Solar/Wind Harmer
0.885
3156081AA2-088 GEN
Solar/Wind Harmer
2.298
315737AD1-076 GEN
Solar/Wind Harmer
1.342
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.459
957521AF2-046 GEN
Solar/Wind Harmer
5.494
961681AG1-008 GEN
Solar/Wind Harmer
5.494
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
31.532
3156021HOLLOMANSOL
Solar/Wind Harmer
0.931
3150411LDYSMT5
50/50
43.365
3150381LDYSMT2
50/50
41.502
972213AH1-691 GEN
50/50
7.02
972215AH1-692 GEN
50/50
7.02
963051AG1-154 GEN
50/50
5.4
972189AH1-679 GEN
50/50
2.64
316312AB1-027
Solar/Wind Harmer
0.323
971285AH1-108 GEN
Adder
0.606
316233AE1-074 FULL
Solar/Wind Harmer
0.24
971281AH1-106 GEN
Solar/Wind Harmer
1.451
971283AH1-107 GEN
Solar/Wind Harmer
1.451
316132AB2-190 GEN1
Solar/Wind Harmer
0.831
3143316POE
Solar/Wind Harmer
-0.032
316369SG1_INVT
Solar/Wind Harmer
1.442
972265AH1-717 GEN
Adder
5.416
3151201GRAVEL4
Adder
5.077
3151191GRAVEL3
Adder
5.013
3151211GRAVEL5
Adder
5.013
971445AH1-216 GEN
Solar/Wind Harmer
4.834
315833AF1-017_GEN
Solar/Wind Harmer
1.477
316349AD2-085 GEN
Solar/Wind Harmer
0.692
316311AC2-079 GEN
Solar/Wind Harmer
3.921
3151081ELIZAR1
Adder
6.332
3151091ELIZAR2
Adder
6.222
3152611GOSPORTB
Adder
0.879
3152621GOSPORTC
Adder
0.746
3152601GOSPORTA
Adder
0.688
957871AF2-081 GEN
Solar/Wind Harmer
3.844
319010AE1-072 C
Solar/Wind Harmer
1.551
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316315AB2-025 C
Solar/Wind Harmer
0.206
316305AF2-043 C
Solar/Wind Harmer
0.23
315835AF2-110_GEN
Solar/Wind Harmer
0.955
315976AC1-164 GENA
Solar/Wind Harmer
8.065
316169AC1-164_GENC
Solar/Wind Harmer
6.967
315975AC1-164 GENB
Solar/Wind Harmer
0.239
315814AE2-033 C
Solar/Wind Harmer
7.093
313526AB2-022
Solar/Wind Harmer
0.205
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.204
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.139
941031AE2-094 GEN
Solar/Wind Harmer
13.945
944011AF1-069 GEN
Solar/Wind Harmer
4.369
315611Z1-036_GEN2
Solar/Wind Harmer
1.83
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
970673AG2-436 GEN
Solar/Wind Harmer
15.399
970673AG2-436 GEN
Solar/Wind Harmer
7.797
971967AH1-528 GEN
Solar/Wind Harmer
13.65
315816AE2-034 GEN
Solar/Wind Harmer
0.582
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.428
315733AD1-074 GEN2
Solar/Wind Harmer
1.428
315735AD1-075 GEN1
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.626
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.063
316318V4-068
Solar/Wind Harmer
0.174
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
972193AH1-681 GEN
Adder
1.409
946281AF1-292 GEN
Solar/Wind Harmer
0.155
3145513AHOSKIE
Solar/Wind Harmer
0.06
961941AG1-037 GEN
Solar/Wind Harmer
0.052
3145513AHOSKIE
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.693
316087AB2-174 GEN
Solar/Wind Harmer
0.977
315652AC1-086 GEN
Solar/Wind Harmer
7.643
3137643SOCKMAN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
3.234
316005AA1-067
Solar/Wind Harmer
0.129
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
970181AG2-120 GEN
Solar/Wind Harmer
0.838
3141426STAFORD
Solar/Wind Helper
0.114
316223AC1-118
Solar/Wind Helper
0.271
966621AG1-532 GEN
Solar/Wind Harmer
0.14
316463AE2-346 GEN
Solar/Wind Harmer
0.112
316140AB2-099
Solar/Wind Harmer
0.047
962331AG1-082 GEN
Solar/Wind Harmer
0.863
3146263WOODLND
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.549
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316317KELFORD C
Solar/Wind Harmer
0.318
3145823KELFORD
Solar/Wind Harmer
-0.007
3147043LAWRENC
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
316478AD1-087 GEN
Solar/Wind Harmer
0.568
316486AD2-202 GEN
Solar/Wind Harmer
0.166
316210AC1-098 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.006
966801AG1-551 GEN
Solar/Wind Harmer
0.813
970909AG2-566 GEN
Solar/Wind Harmer
0.613
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315724AD1-057 GEN
Solar/Wind Harmer
0.367
316327AA2-057 GEN
Solar/Wind Harmer
0.639
3141906WESTMOR
Solar/Wind Helper
0.071
3150391LDYSMT3
50/50
43.149
972195AH1-682 GEN
50/50
5.67
315673AE1-157 GEN
Solar/Wind Harmer
21.737
957411AF2-035 GEN
Solar/Wind Harmer
11.699
970317AG2-208 GEN
Solar/Wind Harmer
11.374
3142296MT RD221
Adder
0.302
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
5.91
3150701DARBY 4
Adder
5.896
3150681DARBY 2
Adder
5.889
3150671DARBY 1
Adder
5.882
3143526WINTERP
Solar/Wind Harmer
-0.046
944641AF1-129 GEN
Adder
37.086
971223AH1-071 GEN
Solar/Wind Harmer
1.092
316240AF1-291 C
Solar/Wind Harmer
0.262
316075AC2-137 C
Solar/Wind Harmer
0.224
3142946ENON
Solar/Wind Harmer
-0.001
316033AB2-134 GEN
Solar/Wind Harmer
2.603
315697AD1-025 GEN
Solar/Wind Harmer
1.633
970657AG2-426 GEN
Solar/Wind Harmer
2.49
970657AG2-426 GEN
Solar/Wind Harmer
0.521
316236AE1-162_GEN
Solar/Wind Harmer
0.235
316036AC1-147 C
Solar/Wind Harmer
0.209
3150991CHESPKB
Adder
0.723
3150991CHESPKB
Adder
0.706
3142956BIRDNECK
Solar/Wind Harmer
0.415
316316AC1-027 C
Solar/Wind Harmer
0.238
316185AD1-033 GEN
Solar/Wind Harmer
0.816
3145506HICKORY
Solar/Wind Harmer
-0.031
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.519
316018AA1-139 ULT2
Solar/Wind Harmer
0.659
316017AA1-139 ULT1
Solar/Wind Harmer
0.622
3137176SLIGO L2192
Solar/Wind Harmer
-0.03
3146456SLIGO L269
Solar/Wind Harmer
0.906
3130086AYDLETT
Solar/Wind Harmer
-0.03
3144356SAPONY
Solar/Wind Harmer
0.267
3146386ELIZ CT
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.364
316433W1029_GEN2
Solar/Wind Harmer
1.364
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
966871AG1-558 GEN
Solar/Wind Harmer
0.223
966871AG1-558 GEN
Solar/Wind Harmer
0.076
315742AE1-103 GEN
Solar/Wind Harmer
0.772
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
972185AH1-677 GEN
Adder
3.634
972187AH1-678 GEN
Adder
1.826
970933AG2-581 GEN
Solar/Wind Harmer
6.679
316065AD1-022 GEN
Solar/Wind Harmer
3.511
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.952
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
970099AG2-077 GEN
Solar/Wind Harmer
8.455
316426AA2-053 GEN
Solar/Wind Harmer
0.683
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
966811AG1-552 GEN
Solar/Wind Harmer
0.757
3145593CAROLNA
Solar/Wind Harmer
0.056
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
0.794
3145783HORNRTN
Solar/Wind Harmer
0.635
3145783HORNRTN
Solar/Wind Harmer
0.199
3145783HORNRTN
Solar/Wind Harmer
0.079
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.006
971741AH1-377 GEN
Solar/Wind Harmer
7.563
316274AC1-208 GEN
Solar/Wind Harmer
0.701
970301AG2-198 GEN
Solar/Wind Harmer
3.227
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
315693AD1-088 GEN
Solar/Wind Harmer
3.339
962491AG1-098 GEN
Solar/Wind Harmer
4.459
970937AG2-583 GEN
Solar/Wind Harmer
4.746
316212AC1-099_GEN
Solar/Wind Harmer
0.57
3146293MARTNCO
Solar/Wind Harmer
0.04
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.207
3145746EVERETS
Solar/Wind Harmer
-0.006
3145746EVERETS
Solar/Wind Harmer
-0.006
315722AD1-056 GEN
Solar/Wind Harmer
0.667
316337AD2-073 GEN
Solar/Wind Helper
0.174
NYPJM->LTFIMP_NY
CLTF
1.15
LAGNLTFEXP_LAGN->PJM
CLTF
3.071
LGEELTFEXP_LGEE->PJM
CLTF
0.646
WECLTFEXP_WEC->PJM
CLTF
0.327
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.25
TVALTFEXP_TVA->PJM
CLTF
1.556
CPLELTFEXP_CPLE->PJM
CLTF
3.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.979
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.426
MECLTFEXP_MEC->PJM
CLTF
1.669
SIGELTFEXP_SIGE->PJM
CLTF
0.052

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H2T560_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2124.15
MW Contribution:4.53
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.027
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.732
3150381LDYSMT2
Adder
12.185
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
316059AD1-063 C
Solar/Wind Harmer
0.215
957601AF2-054 GEN
Solar/Wind Harmer
0.285
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.569
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.381
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.247
3150331BIRCHWDA
Adder
16.693
3141316ARNOLDS
Adder
0.23
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.692
3150371LDYSMT1
Adder
12.264
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.11
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.412
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.015
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
3141766HARMONY
Solar/Wind Harmer
0.847
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.196
944601AF1-125 GEN
Solar/Wind Harmer
40.553
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.483
944011AF1-069 GEN
Solar/Wind Harmer
5.165
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.299
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
316045AC1-158 PL2
Solar/Wind Harmer
3.338
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.642
3151751LOISA D
Adder
5.598
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.981
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.843
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.581
3150181POSSMC2
Adder
1.094
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
316447AC1-158 HLD
Solar/Wind Harmer
2.295
3150391LDYSMT3
Adder
12.669
972195AH1-682 GEN
Adder
1.665
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.8
957411AF2-035 GEN
Solar/Wind Harmer
4.619
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.598
3151721LOISA A
Adder
5.569
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.766
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233940AF2-379 C
Solar/Wind Helper
0.037
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.486
316316AC1-027 C
Solar/Wind Harmer
0.278
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
2.575
LGEELTFEXP_LGEE->PJM
CLTF
1.805
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
WECLTFEXP_WEC->PJM
CLTF
0.962
TVALTFEXP_TVA->PJM
CLTF
3.187
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: H1T560_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T560_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.42 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2124.08
MW Contribution:4.53
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.028
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.101
316415AF1-147_GEN2
Solar/Wind Harmer
1.101
3141426STAFORD
Solar/Wind Harmer
-0.003
3150411LDYSMT5
Adder
12.733
3150381LDYSMT2
Adder
12.186
972213AH1-691 GEN
Adder
2.061
972215AH1-692 GEN
Adder
2.061
316164AC1-076 GEN
Solar/Wind Harmer
0.887
944491AF1-114 GEN
Solar/Wind Harmer
3.051
316223AC1-118
Solar/Wind Harmer
0.272
972189AH1-679 GEN
Adder
1.468
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.221
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.01
316312AB1-027
Solar/Wind Harmer
0.321
3147346CASHSCORNER
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.813
957601AF2-054 GEN
Solar/Wind Harmer
0.285
316059AD1-063 C
Solar/Wind Harmer
0.215
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.146
315666AE1-190 GEN
Solar/Wind Harmer
0.287
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
971167AH1-042 GEN
Solar/Wind Harmer
9.109
315976AC1-164 GENA
Solar/Wind Harmer
9.985
316169AC1-164_GENC
Solar/Wind Harmer
8.626
315975AC1-164 GENB
Solar/Wind Harmer
0.295
316233AE1-074 FULL
Solar/Wind Harmer
0.253
971281AH1-106 GEN
Solar/Wind Harmer
1.528
971283AH1-107 GEN
Solar/Wind Harmer
1.528
971285AH1-108 GEN
Adder
0.631
957831AF2-077 GEN
Solar/Wind Harmer
0.282
3138283WHITEMARSH
Solar/Wind Harmer
0.015
316132AB2-190 GEN1
Solar/Wind Harmer
0.937
316369SG1_INVT
Solar/Wind Harmer
1.648
972265AH1-717 GEN
Adder
6.337
3151201GRAVEL4
Adder
5.94
3151191GRAVEL3
Adder
5.865
3151211GRAVEL5
Adder
5.865
971445AH1-216 GEN
Solar/Wind Harmer
5.652
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.394
3151091ELIZAR2
Adder
7.266
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
315833AF1-017_GEN
Solar/Wind Harmer
1.712
316349AD2-085 GEN
Solar/Wind Harmer
0.802
316311AC2-079 GEN
Solar/Wind Harmer
4.545
957871AF2-081 GEN
Solar/Wind Harmer
4.503
316305AF2-043 C
Solar/Wind Harmer
0.271
319010AE1-072 C
Solar/Wind Harmer
1.819
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.121
313526AB2-022
Solar/Wind Harmer
0.241
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.24
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
3146396TANGLEW
Solar/Wind Harmer
0.164
316315AB2-025 C
Solar/Wind Harmer
0.238
3152111X4-039 GT1
50/50
1.839
315747AE2-019 GEN
50/50
13.179
963691AG1-221 GEN
Solar/Wind Harmer
2.313
971455AH1-223 GEN
Solar/Wind Harmer
2.313
3150151POSSMC1
Adder
1.085
3150151POSSMC1
Adder
1.085
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150231REMNGT3
Adder
13.456
3150241REMNGT4
Adder
12.546
972199AH1-684 GEN
Adder
1.902
972217AH1-693 GEN
Adder
1.654
3150331BIRCHWDA
Adder
16.699
3150301M RUN C
Adder
13.346
3150291M RUN B
Adder
13.246
3141316ARNOLDS
Adder
0.23
3150401LDYSMT4
Adder
12.694
3150371LDYSMT1
Adder
12.265
316044AC1-158 PL1
Solar/Wind Harmer
1.043
316450AC1-158 RIC
Solar/Wind Harmer
0.278
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.309
970737AG2-469 GEN
Solar/Wind Harmer
5.111
3141906WESTMOR
Solar/Wind Harmer
-0.004
3132273ORANGE
Solar/Wind Harmer
-0.002
971781AH1-399 GEN
Solar/Wind Harmer
0.62
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.885
316404AE1-155 C
Solar/Wind Harmer
1.876
3151761LOISA E
Adder
11.411
3152131X4-039 ST
50/50
2.893
3152121X4-039 GT2
50/50
1.833
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.574
3150151POSSMC1
Adder
1.085
3141346CRANES
Adder
0.12
3150221REMNGT2
Adder
12.463
3150211REMNGT1
Adder
12.38
972201AH1-685 GEN
Adder
2.15
3150281M RUN A
Adder
13.354
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.961
972197AH1-683 GEN
Adder
1.982
972219AH1-694 GEN
Adder
1.427
316045AC1-158 PL2
Solar/Wind Harmer
3.338
316254AC1-120 GEN1
Solar/Wind Harmer
0.849
957971AF2-091 GEN
Solar/Wind Harmer
1.037
316484AD2-074 GEN
Solar/Wind Harmer
2.436
970009AG2-005 GEN
Solar/Wind Harmer
1.21
972183AH1-676 GEN
Adder
92.013
316473AC1-191 GEN
Solar/Wind Harmer
1.04
962971AG1-146 GEN
Solar/Wind Harmer
1.809
3142416OLDCHRC
Solar/Wind Harmer
0.961
316156AD2-030 GEN
Solar/Wind Harmer
0.254
3141873WAN 176
Solar/Wind Harmer
1.129
3141766HARMONY
Solar/Wind Harmer
0.847
316280AD1-041 GEN
Solar/Wind Harmer
0.717
316203AE2-005 GEN
Solar/Wind Harmer
4.009
3141843SHACKLE
Adder
0.432
970293AG2-193 GEN
Solar/Wind Harmer
1.184
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143096IRON208
Adder
0.344
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.385
316382AG1-145 C
Solar/Wind Harmer
0.281
970133AG2-095 GEN
Solar/Wind Harmer
1.046
970129AG2-093 GEN
Solar/Wind Harmer
5.216
3150921YORKTN3
Adder
2.069
315778AD1-151 GEN
Solar/Wind Harmer
8.005
965281AG1-393 GEN
Solar/Wind Harmer
1.155
3144216WINCHST
Adder
0.31
315839AE2-212 C
Solar/Wind Harmer
0.278
961611AG1-000B GEN
Solar/Wind Harmer
1.935
3151221GRAVEL6
Adder
5.934
3151171GRAVELC
Adder
1.142
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.707
315773AC2-141 GEN
Solar/Wind Harmer
3.812
970659AG2-427 GEN
Solar/Wind Harmer
0.856
316083AB2-161 GEN
Solar/Wind Harmer
1.475
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.489
970661AG2-428 GEN
Solar/Wind Harmer
1.707
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
41.195
944601AF1-125 GEN
Solar/Wind Harmer
40.552
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.096
316320Y1-086
Solar/Wind Harmer
0.524
316313AB2-026
Solar/Wind Harmer
0.241
316258AE1-075 C
Solar/Wind Harmer
0.217
316405AF2-144 C
Solar/Wind Harmer
0.229
3143336POWHATN
Solar/Wind Harmer
0.9
316435W1029_GEN3
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.929
971157AH1-035 GEN
Solar/Wind Harmer
1.066
3156081AA2-088 GEN
Solar/Wind Harmer
2.765
315737AD1-076 GEN
Solar/Wind Harmer
1.618
316365GEN2_N
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
21.109
957521AF2-046 GEN
Solar/Wind Harmer
6.644
961681AG1-008 GEN
Solar/Wind Harmer
6.644
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.13
316463AE2-346 GEN
Solar/Wind Harmer
0.136
316140AB2-099
Solar/Wind Harmer
0.056
972289AH1-729 GEN
50/50
13.252
3150071POSSM 5
Adder
49.613
3150181POSSMC2
Adder
1.095
3150181POSSMC2
Adder
1.085
3150181POSSMC2
Adder
1.085
3150391LDYSMT3
Adder
12.67
972195AH1-682 GEN
Adder
1.665
316447AC1-158 HLD
Solar/Wind Harmer
2.294
315651AD1-115 GEN
Solar/Wind Harmer
4.661
315673AE1-157 GEN
Solar/Wind Harmer
7.801
957411AF2-035 GEN
Solar/Wind Harmer
4.62
970317AG2-208 GEN
Solar/Wind Harmer
4.491
316468AD1-105 GEN
Solar/Wind Harmer
1.121
316077AC2-138 C
Solar/Wind Harmer
0.207
3150341NORNECKC1
Adder
0.915
3150341NORNECKC1
Adder
0.907
966001AG1-469 GEN
Solar/Wind Harmer
0.184
958261AF2-120 GEN
Solar/Wind Harmer
3.769
3151731LOISA B
Adder
5.597
3151721LOISA A
Adder
5.568
316487AF1-042 GEN
Solar/Wind Harmer
1.275
966871AG1-558 GEN
Solar/Wind Harmer
0.29
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.271
316441AF1-014 GEN
Solar/Wind Harmer
0.641
3142366NRTHEST
Adder
0.276
3150691DARBY 3
Adder
6.069
3150701DARBY 4
Adder
6.055
3150681DARBY 2
Adder
6.048
3150671DARBY 1
Adder
6.041
316075AC2-137 C
Solar/Wind Harmer
0.255
3142946ENON
Solar/Wind Harmer
-0.001
3143526WINTERP
Solar/Wind Harmer
-0.049
971223AH1-071 GEN
Solar/Wind Harmer
1.172
944641AF1-129 GEN
Adder
39.415
316240AF1-291 C
Solar/Wind Harmer
0.279
316033AB2-134 GEN
Solar/Wind Harmer
2.975
315697AD1-025 GEN
Solar/Wind Harmer
1.866
316236AE1-162_GEN
Solar/Wind Harmer
0.275
970657AG2-426 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
0.593
316036AC1-147 C
Solar/Wind Harmer
0.244
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
316316AC1-027 C
Solar/Wind Harmer
0.278
3142956BIRDNECK
Solar/Wind Harmer
0.486
316185AD1-033 GEN
Solar/Wind Harmer
0.954
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.608
316018AA1-139 ULT2
Solar/Wind Harmer
0.771
316017AA1-139 ULT1
Solar/Wind Harmer
0.729
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.062
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.61
316433W1029_GEN2
Solar/Wind Harmer
1.61
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.308
315742AE1-103 GEN
Solar/Wind Harmer
0.916
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
972185AH1-677 GEN
Adder
4.33
972187AH1-678 GEN
Adder
2.184
970933AG2-581 GEN
Solar/Wind Harmer
8.04
316065AD1-022 GEN
Solar/Wind Harmer
4.239
3145893MURPHYS
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.411
316181AB2-040 GEN
Solar/Wind Harmer
1.158
3144293JTRSVLE
Adder
0.23
3144293JTRSVLE
Adder
0.193
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
962331AG1-082 GEN
Solar/Wind Harmer
1.047
966621AG1-532 GEN
Solar/Wind Harmer
0.17
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.23
972255AH1-712 GEN
Adder
36.765
3151861LOWMORA
Adder
0.645
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.49
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.397
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
235067AD1-061 GEN
Solar/Wind Helper
0.312
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.303
233994AC2-023 GEN
Solar/Wind Helper
0.577
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.304
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.995
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.089
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.043
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.242
963071AG1-156 GEN
Solar/Wind Helper
0.783
209027LOR2_Q27
Solar/Wind Helper
0.557
961331AF2-424 GEN
Solar/Wind Helper
0.237
961421AF2-433 GEN
Solar/Wind Helper
0.236
957921AF2-086 GEN
Solar/Wind Helper
0.234
946691AF1-333 GEN
Solar/Wind Helper
0.233
946741AF1-338 GEN
Solar/Wind Helper
0.233
209067AE2-060 GEN
Solar/Wind Helper
0.042
972135AH1-637 GEN
Solar/Wind Harmer
1.031
966881AG1-559 GEN
Solar/Wind Harmer
0.106
315683AE1-153 C
Solar/Wind Harmer
9.501
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.185
316337AD2-073 GEN
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
0.871
964211AG1-282 GEN
Solar/Wind Harmer
0.294
3141726DUNNSVL
Solar/Wind Harmer
-0.039
962861AG1-135 GEN
Solar/Wind Harmer
3.643
3151751LOISA D
Adder
5.597
961951AG1-038 GEN
Solar/Wind Harmer
1.275
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.025
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.118
3141843SHACKLE
Adder
0.432
3142433PROV 92
Solar/Wind Harmer
-0.038
3142433PROV 92
Adder
0.164
3142433PROV 92
Adder
0.164
3143096IRON208
Adder
0.351
3143526WINTERP
Solar/Wind Harmer
-0.049
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.385
944631AF1-128 GEN
Adder
39.856
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.25
971317AH1-138 GEN
Solar/Wind Harmer
1.163
970129AG2-093 GEN
Solar/Wind Harmer
2.113
316458AB2-190 GEN2
Solar/Wind Harmer
0.937
315671AE2-027_GEN
Solar/Wind Harmer
6.943
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.462
971647AH1-324 GEN
Solar/Wind Harmer
4.604
961611AG1-000B GEN
Solar/Wind Harmer
4.536
3151171GRAVELC
Adder
0.868
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.948
970659AG2-427 GEN
Solar/Wind Harmer
4.83
316381AD1-082 GEN
Solar/Wind Harmer
0.833
316375AC2-012 GEN
Solar/Wind Harmer
3.136
3150981CHESPKA
Adder
1.007
970661AG2-428 GEN
Solar/Wind Harmer
9.631
944591AF1-124 GEN
Solar/Wind Harmer
41.344
316072AD1-144
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.98
316246AF1-032 C
Solar/Wind Harmer
0.182
940641AE2-051 GEN
Solar/Wind Harmer
8.42
316093AE2-104_GEN
Solar/Wind Harmer
2.607
3143336POWHATN
Solar/Wind Harmer
1.059
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316336AC2-165 C
Solar/Wind Harmer
1.53
315800Z1-036_GEN1
Solar/Wind Harmer
2.172
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.075
970937AG2-583 GEN
Solar/Wind Harmer
6.109
316023GEN1_S
Solar/Wind Harmer
0.57
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.115
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.251
970919AG2-571 GEN
Solar/Wind Harmer
2.672
970087AG2-069 GEN
Solar/Wind Harmer
7.898
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.94
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
26.028
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.664
3144293JTRSVLE
Adder
0.23
972277AH1-723 GEN
Adder
42.842
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.397
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.221
315814AE2-033 C
Solar/Wind Harmer
8.205
315611Z1-036_GEN2
Solar/Wind Harmer
2.172
941031AE2-094 GEN
Solar/Wind Harmer
16.482
944011AF1-069 GEN
Solar/Wind Harmer
5.164
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.298
970673AG2-436 GEN
Solar/Wind Harmer
9.265
971967AH1-528 GEN
Solar/Wind Harmer
16.294
315816AE2-034 GEN
Solar/Wind Harmer
0.697
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.721
315733AD1-074 GEN2
Solar/Wind Harmer
1.721
315735AD1-075 GEN1
Solar/Wind Harmer
0.861
965291AG1-394 GEN
Solar/Wind Harmer
0.754
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.701
316318V4-068
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.265
970581AG2-369 GEN
Solar/Wind Harmer
4.528
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3146043SEABORD
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.187
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.843
316087AB2-174 GEN
Solar/Wind Harmer
1.187
972205AH1-687 GEN
Adder
3.134
972193AH1-681 GEN
Adder
1.643
3151881LOWMORC
Adder
0.64
3151881LOWMORC
Adder
0.63
3151861LOWMORA
Adder
0.62
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.387
205956AE1-196_GEN
Solar/Wind Helper
0.385
205932AD2-116_GEN
Solar/Wind Helper
0.385
237034AC2-136 C
Solar/Wind Helper
0.205
205916AD1-020 GEN
Solar/Wind Helper
1.48
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.307
237002AB1-128_GEN
Solar/Wind Helper
0.298
235063AE1-101 C2
Solar/Wind Helper
1.064
20390526W1-045 C
Solar/Wind Helper
0.252
959381AF2-229 GEN
Solar/Wind Helper
0.257
237085AD2-009_GEN
Solar/Wind Helper
0.97
203975AE1-071-GEN
Solar/Wind Helper
1.713
233935AB2-179 C
Solar/Wind Helper
0.772
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.575
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.208
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.093
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.004
961261AF2-417 GEN
Solar/Wind Helper
0.241
959431AF2-234 GEN
Solar/Wind Helper
0.466
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.233
238208AF1-136 C
Solar/Wind Helper
0.089
235062AE1-101 C1
Solar/Wind Helper
1.064
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.303
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.304
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.082
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.017
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.9
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.242
963151AG1-164 GEN
Solar/Wind Helper
0.242
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.237
212507AE2-042_GEN
Solar/Wind Helper
0.829
946731AF1-337 GEN
Solar/Wind Helper
0.233
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.373
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.355
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.406
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.341
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.304
232410W1-006 C
Solar/Wind Helper
0.304
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.097
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.178
961431AF2-434 GEN
Solar/Wind Helper
0.236
209029WAYMART-WD
Solar/Wind Helper
0.442
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.233
209137AF2-361 C
Solar/Wind Helper
0.708
NYPJM->LTFIMP_NY
CLTF
2.575
LAGNLTFEXP_LAGN->PJM
CLTF
6.323
LGEELTFEXP_LGEE->PJM
CLTF
1.805
WECLTFEXP_WEC->PJM
CLTF
0.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.563
TVALTFEXP_TVA->PJM
CLTF
3.187
CPLELTFEXP_CPLE->PJM
CLTF
5.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.958
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.59
MECLTFEXP_MEC->PJM
CLTF
4.448
SIGELTFEXP_SIGE->PJM
CLTF
0.14

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o DVP_P4-2: 560T571_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 560T571_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.69 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2110.99
MW Contribution:4.5
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.02
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.104
316415AF1-147_GEN2
Solar/Wind Harmer
1.104
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
12.596
3150381LDYSMT2
Adder
12.055
972213AH1-691 GEN
Adder
2.039
972215AH1-692 GEN
Adder
2.039
316164AC1-076 GEN
Solar/Wind Harmer
0.886
944491AF1-114 GEN
Solar/Wind Harmer
3.014
316223AC1-118
Solar/Wind Harmer
0.269
972189AH1-679 GEN
Adder
1.455
3141813NORNECK
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
4.183
3141783LANCAST
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.004
3147346CASHSCORNER
Solar/Wind Harmer
0.147
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316312AB1-027
Solar/Wind Harmer
0.319
316314AB2-024 C
Solar/Wind Harmer
0.807
316059AD1-063 C
Solar/Wind Harmer
0.213
957601AF2-054 GEN
Solar/Wind Harmer
0.282
3141873WAN 176
Solar/Wind Harmer
-0.002
315662AE1-191 GEN
Solar/Wind Harmer
1.137
315666AE1-190 GEN
Solar/Wind Harmer
0.284
3143873LANEXA
Solar/Wind Harmer
-0.006
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
971167AH1-042 GEN
Solar/Wind Harmer
9.035
315976AC1-164 GENA
Solar/Wind Harmer
9.907
316169AC1-164_GENC
Solar/Wind Harmer
8.558
315975AC1-164 GENB
Solar/Wind Harmer
0.293
316233AE1-074 FULL
Solar/Wind Harmer
0.251
971281AH1-106 GEN
Solar/Wind Harmer
1.517
971283AH1-107 GEN
Solar/Wind Harmer
1.517
971285AH1-108 GEN
Adder
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.28
3138283WHITEMARSH
Solar/Wind Harmer
0.014
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
316369SG1_INVT
Solar/Wind Harmer
1.636
972265AH1-717 GEN
Adder
6.291
3151201GRAVEL4
Adder
5.897
3151191GRAVEL3
Adder
5.822
3151211GRAVEL5
Adder
5.822
971445AH1-216 GEN
Solar/Wind Harmer
5.611
3143316POE
Solar/Wind Harmer
-0.036
3151081ELIZAR1
Adder
7.342
3151091ELIZAR2
Adder
7.214
3152611GOSPORTB
Adder
1.02
3152621GOSPORTC
Adder
0.866
3152601GOSPORTA
Adder
0.798
315833AF1-017_GEN
Solar/Wind Harmer
1.7
316349AD2-085 GEN
Solar/Wind Harmer
0.796
316311AC2-079 GEN
Solar/Wind Harmer
4.513
957871AF2-081 GEN
Solar/Wind Harmer
4.471
319010AE1-072 C
Solar/Wind Harmer
1.806
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.113
313526AB2-022
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.239
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.163
316315AB2-025 C
Solar/Wind Harmer
0.237
3152131X4-039 ST
50/50
2.897
3152121X4-039 GT2
50/50
1.836
3140676OCCOQUN
Adder
0.27
972223AH1-696 GEN
Adder
8.401
3150151POSSMC1
Adder
1.063
3141346CRANES
Adder
0.118
3150221REMNGT2
Adder
12.484
3150211REMNGT1
Adder
12.401
972201AH1-685 GEN
Adder
2.154
3150281M RUN A
Adder
13.376
316006AB2-029 C
Solar/Wind Harmer
0.631
971685AH1-345 GEN
Solar/Wind Harmer
0.962
316045AC1-158 PL2
Solar/Wind Harmer
3.331
972197AH1-683 GEN
Adder
1.961
972219AH1-694 GEN
Adder
1.412
316254AC1-120 GEN1
Solar/Wind Harmer
0.848
957971AF2-091 GEN
Solar/Wind Harmer
1.025
315683AE1-153 C
Solar/Wind Harmer
9.493
972135AH1-637 GEN
Solar/Wind Harmer
1.018
966881AG1-559 GEN
Solar/Wind Harmer
0.105
3147666LOUISA
Solar/Wind Harmer
-0.04
316192AB2-158 GEN
Solar/Wind Harmer
1.181
316337AD2-073 GEN
Solar/Wind Harmer
0.265
3150351NORNECKC2
Adder
0.862
964211AG1-282 GEN
Solar/Wind Harmer
0.291
3141726DUNNSVL
Solar/Wind Harmer
-0.039
3151751LOISA D
Adder
5.583
962861AG1-135 GEN
Solar/Wind Harmer
3.609
961951AG1-038 GEN
Solar/Wind Harmer
1.263
3138133OCRAN
Solar/Wind Harmer
-0.006
3142416OLDCHRC
Solar/Wind Harmer
-0.024
3142416OLDCHRC
Solar/Wind Harmer
-0.009
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.109
3141843SHACKLE
Adder
0.429
3142433PROV 92
Solar/Wind Harmer
-0.037
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143526WINTERP
Solar/Wind Harmer
-0.048
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.383
944631AF1-128 GEN
Adder
39.551
3143226MDLTHAN
Solar/Wind Harmer
-0.009
316159AE1-175 C
Solar/Wind Harmer
0.248
971317AH1-138 GEN
Solar/Wind Harmer
1.154
970129AG2-093 GEN
Solar/Wind Harmer
2.097
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
315671AE2-027_GEN
Solar/Wind Harmer
6.892
3138126ROCKLANDING
Solar/Wind Harmer
0.028
971069AG2-661 GEN
Solar/Wind Harmer
1.451
971647AH1-324 GEN
Solar/Wind Harmer
4.571
961611AG1-000B GEN
Solar/Wind Harmer
4.503
3151171GRAVELC
Adder
0.862
3145336SMITFLD
Solar/Wind Harmer
-0.036
316294AC1-161 GEN
Solar/Wind Harmer
2.927
970659AG2-427 GEN
Solar/Wind Harmer
4.796
316381AD1-082 GEN
Solar/Wind Harmer
0.827
316375AC2-012 GEN
Solar/Wind Harmer
3.114
3150981CHESPKA
Adder
1
970661AG2-428 GEN
Solar/Wind Harmer
9.562
944591AF1-124 GEN
Solar/Wind Harmer
41.052
316072AD1-144
Solar/Wind Harmer
0.182
316388AE2-253 GEN
Solar/Wind Harmer
0.603
939411AE1-173 GEN
Solar/Wind Harmer
44.674
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.181
940641AE2-051 GEN
Solar/Wind Harmer
8.364
3152111X4-039 GT1
50/50
1.841
315747AE2-019 GEN
50/50
13.211
963691AG1-221 GEN
Solar/Wind Harmer
2.318
971455AH1-223 GEN
Solar/Wind Harmer
2.318
3141196NOKESVL
Solar/Wind Harmer
-0.048
3150151POSSMC1
Adder
1.063
3150151POSSMC1
Adder
1.063
3150231REMNGT3
Adder
13.478
3150241REMNGT4
Adder
12.566
972199AH1-684 GEN
Adder
1.905
972217AH1-693 GEN
Adder
1.657
3150301M RUN C
Adder
13.368
3150291M RUN B
Adder
13.268
3150331BIRCHWDA
Adder
16.45
3141316ARNOLDS
Adder
0.227
316044AC1-158 PL1
Solar/Wind Harmer
1.041
316450AC1-158 RIC
Solar/Wind Harmer
0.278
3150401LDYSMT4
Adder
12.557
3150371LDYSMT1
Adder
12.133
316170AC1-121 GEN2
Solar/Wind Harmer
0.283
966881AG1-559 GEN
Solar/Wind Harmer
0.306
970737AG2-469 GEN
Solar/Wind Harmer
5.052
3132273ORANGE
Solar/Wind Harmer
-0.002
3141906WESTMOR
Solar/Wind Harmer
-0.004
971781AH1-399 GEN
Solar/Wind Harmer
0.614
3147666LOUISA
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
0.877
3151761LOISA E
Adder
11.381
972183AH1-676 GEN
Adder
91.775
316404AE1-155 C
Solar/Wind Harmer
1.859
316484AD2-074 GEN
Solar/Wind Harmer
2.414
970009AG2-005 GEN
Solar/Wind Harmer
1.199
316473AC1-191 GEN
Solar/Wind Harmer
1.031
962971AG1-146 GEN
Solar/Wind Harmer
1.793
3142416OLDCHRC
Solar/Wind Harmer
0.953
3141766HARMONY
Solar/Wind Harmer
0.84
316156AD2-030 GEN
Solar/Wind Harmer
0.252
3141873WAN 176
Solar/Wind Harmer
1.12
316280AD1-041 GEN
Solar/Wind Harmer
0.711
316203AE2-005 GEN
Solar/Wind Harmer
3.975
3141843SHACKLE
Adder
0.429
970293AG2-193 GEN
Solar/Wind Harmer
1.175
3142433PROV 92
Adder
0.162
3142433PROV 92
Adder
0.162
3143096IRON208
Adder
0.349
3143096IRON208
Adder
0.342
3142946ENON
Solar/Wind Harmer
-0.003
3150861SPRUNCD
Adder
0.383
316382AG1-145 C
Solar/Wind Harmer
0.279
970133AG2-095 GEN
Solar/Wind Harmer
1.038
970129AG2-093 GEN
Solar/Wind Harmer
5.177
3150921YORKTN3
Adder
2.053
315778AD1-151 GEN
Solar/Wind Harmer
7.946
965281AG1-393 GEN
Solar/Wind Harmer
1.147
3144216WINCHST
Adder
0.308
315839AE2-212 C
Solar/Wind Harmer
0.276
961611AG1-000B GEN
Solar/Wind Harmer
1.921
3151221GRAVEL6
Adder
5.89
3151171GRAVELC
Adder
1.133
3145336SMITFLD
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
5.666
315773AC2-141 GEN
Solar/Wind Harmer
3.785
970659AG2-427 GEN
Solar/Wind Harmer
0.85
316083AB2-161 GEN
Solar/Wind Harmer
1.464
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
7.435
970661AG2-428 GEN
Solar/Wind Harmer
1.695
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
40.904
944601AF1-125 GEN
Solar/Wind Harmer
40.266
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.089
316320Y1-086
Solar/Wind Harmer
0.52
316313AB2-026
Solar/Wind Harmer
0.239
316258AE1-075 C
Solar/Wind Harmer
0.215
316405AF2-144 C
Solar/Wind Harmer
0.227
3143336POWHATN
Solar/Wind Harmer
0.895
316435W1029_GEN3
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3145273HOLLAND
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.923
971157AH1-035 GEN
Solar/Wind Harmer
1.059
3156081AA2-088 GEN
Solar/Wind Harmer
2.747
315737AD1-076 GEN
Solar/Wind Harmer
1.607
316365GEN2_N
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.059
3145893MURPHYS
Solar/Wind Harmer
-0.008
970917AG2-570 GEN
Solar/Wind Harmer
20.974
957521AF2-046 GEN
Solar/Wind Harmer
6.6
961681AG1-008 GEN
Solar/Wind Harmer
6.6
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.123
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.04
966621AG1-532 GEN
Solar/Wind Harmer
0.168
3146263WOODLND
Solar/Wind Harmer
-0.008
313506AB2-031 GEN
Solar/Wind Harmer
0.663
3144293JTRSVLE
Adder
0.228
972255AH1-712 GEN
Adder
36.554
3151861LOWMORA
Adder
0.643
226910AB2-157 C
Solar/Wind Helper
0.02
227287AC2-120 GEN
Solar/Wind Helper
0.489
237030AB1-096 C
Solar/Wind Helper
0.083
223402AF1-300 C
Solar/Wind Helper
0.396
205917AD1-020 ES
Solar/Wind Helper
0.318
238221AF1-254 C O1
Solar/Wind Helper
0.179
315814AE2-033 C
Solar/Wind Harmer
8.149
941031AE2-094 GEN
Solar/Wind Harmer
16.374
944011AF1-069 GEN
Solar/Wind Harmer
5.131
315611Z1-036_GEN2
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
970673AG2-436 GEN
Solar/Wind Harmer
18.179
970673AG2-436 GEN
Solar/Wind Harmer
9.205
971967AH1-528 GEN
Solar/Wind Harmer
16.189
315816AE2-034 GEN
Solar/Wind Harmer
0.692
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.71
315733AD1-074 GEN2
Solar/Wind Harmer
1.71
315735AD1-075 GEN1
Solar/Wind Harmer
0.855
965291AG1-394 GEN
Solar/Wind Harmer
0.749
3146206CASHIE
Solar/Wind Harmer
-0.008
970601AG2-382 GEN
Solar/Wind Harmer
3.676
316318V4-068
Solar/Wind Harmer
0.209
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
5.232
970581AG2-369 GEN
Solar/Wind Harmer
4.499
3145513AHOSKIE
Solar/Wind Harmer
0.073
961941AG1-037 GEN
Solar/Wind Harmer
0.063
3145513AHOSKIE
Solar/Wind Harmer
-0.008
946281AF1-292 GEN
Solar/Wind Harmer
0.186
3146043SEABORD
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
315607AA1-063A GEN
Solar/Wind Harmer
0.837
316087AB2-174 GEN
Solar/Wind Harmer
1.179
972205AH1-687 GEN
Adder
3.118
972193AH1-681 GEN
Adder
1.633
3151881LOWMORC
Adder
0.638
3151881LOWMORC
Adder
0.628
3151861LOWMORA
Adder
0.618
960921AF2-383 GEN
Solar/Wind Helper
0.139
205943AE1-185 GEN
Solar/Wind Helper
0.386
205956AE1-196_GEN
Solar/Wind Helper
0.384
205932AD2-116_GEN
Solar/Wind Helper
0.384
959381AF2-229 GEN
Solar/Wind Helper
0.256
237085AD2-009_GEN
Solar/Wind Helper
0.968
203975AE1-071-GEN
Solar/Wind Helper
1.709
233935AB2-179 C
Solar/Wind Helper
0.769
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.573
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.196
964001AG1-254 GEN
Solar/Wind Helper
0.564
219914AD2-027 C
Solar/Wind Helper
0.068
227927V4-067C
Solar/Wind Helper
0.006
228754AB1-001 C
Solar/Wind Helper
0.015
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.093
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.029
207530AG1-191 GEN
Solar/Wind Helper
0.038
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
1.001
961261AF2-417 GEN
Solar/Wind Helper
0.24
959431AF2-234 GEN
Solar/Wind Helper
0.464
964051AG1-259 GEN
Solar/Wind Helper
0.035
964061AG1-260 GEN
Solar/Wind Helper
0.035
959421AF2-233 GEN
Solar/Wind Helper
0.232
238208AF1-136 C
Solar/Wind Helper
0.089
316093AE2-104_GEN
Solar/Wind Harmer
2.589
3143336POWHATN
Solar/Wind Harmer
1.052
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
972289AH1-729 GEN
50/50
13.276
3150071POSSM 5
Adder
48.607
3150181POSSMC2
Adder
1.072
3150181POSSMC2
Adder
1.063
3150181POSSMC2
Adder
1.063
316447AC1-158 HLD
Solar/Wind Harmer
2.29
315651AD1-115 GEN
Solar/Wind Harmer
4.658
3150391LDYSMT3
Adder
12.533
972195AH1-682 GEN
Adder
1.647
315673AE1-157 GEN
Solar/Wind Harmer
7.721
957411AF2-035 GEN
Solar/Wind Harmer
4.574
970317AG2-208 GEN
Solar/Wind Harmer
4.447
316468AD1-105 GEN
Solar/Wind Harmer
1.109
966001AG1-469 GEN
Solar/Wind Harmer
0.184
316077AC2-138 C
Solar/Wind Harmer
0.205
3150341NORNECKC1
Adder
0.906
3150341NORNECKC1
Adder
0.898
3151731LOISA B
Adder
5.583
3151721LOISA A
Adder
5.554
958261AF2-120 GEN
Solar/Wind Harmer
3.734
316487AF1-042 GEN
Solar/Wind Harmer
1.263
966871AG1-558 GEN
Solar/Wind Harmer
0.288
966871AG1-558 GEN
Solar/Wind Harmer
0.099
3142296MT RD221
Adder
0.269
316441AF1-014 GEN
Solar/Wind Harmer
0.636
3142366NRTHEST
Adder
0.273
3150691DARBY 3
Adder
6.022
3150701DARBY 4
Adder
6.008
3150681DARBY 2
Adder
6.001
3150671DARBY 1
Adder
5.994
316075AC2-137 C
Solar/Wind Harmer
0.253
3143526WINTERP
Solar/Wind Harmer
-0.048
3142946ENON
Solar/Wind Harmer
-0.001
971223AH1-071 GEN
Solar/Wind Harmer
1.164
944641AF1-129 GEN
Adder
39.124
316240AF1-291 C
Solar/Wind Harmer
0.277
316033AB2-134 GEN
Solar/Wind Harmer
2.953
315697AD1-025 GEN
Solar/Wind Harmer
1.852
316236AE1-162_GEN
Solar/Wind Harmer
0.273
970657AG2-426 GEN
Solar/Wind Harmer
2.816
970657AG2-426 GEN
Solar/Wind Harmer
0.589
316036AC1-147 C
Solar/Wind Harmer
0.243
3150991CHESPKB
Adder
0.839
3150991CHESPKB
Adder
0.819
3142956BIRDNECK
Solar/Wind Harmer
0.482
316316AC1-027 C
Solar/Wind Harmer
0.276
316336AC2-165 C
Solar/Wind Harmer
1.521
315800Z1-036_GEN1
Solar/Wind Harmer
2.157
3130156CHOWAN
Solar/Wind Harmer
-0.009
3145663CRESWEL
Solar/Wind Harmer
-0.024
971163AH1-040 GEN
Solar/Wind Harmer
8.02
970937AG2-583 GEN
Solar/Wind Harmer
6.075
316023GEN1_S
Solar/Wind Harmer
0.567
3146206CASHIE
Solar/Wind Harmer
-0.008
971547AH1-271 GEN
Solar/Wind Harmer
2.101
3145893MURPHYS
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.249
970919AG2-571 GEN
Solar/Wind Harmer
2.655
970087AG2-069 GEN
Solar/Wind Harmer
7.848
3146173TUNIS
Solar/Wind Harmer
-0.008
960081AF2-299 GEN
Solar/Wind Harmer
0.934
3145683EARLEYS
Solar/Wind Harmer
-0.008
957481AF2-042 GEN
Solar/Wind Harmer
25.866
3146263WOODLND
Solar/Wind Harmer
-0.008
3147043LAWRENC
Adder
0.66
3144293JTRSVLE
Adder
0.228
972277AH1-723 GEN
Adder
42.597
23779801AA1-109
Solar/Wind Helper
0.217
223401AF1-299 GEN
Solar/Wind Helper
0.396
966131AG1-482 GEN
Solar/Wind Helper
0.063
237080AD1-060 GEN
Solar/Wind Helper
0.22
235062AE1-101 C1
Solar/Wind Helper
1.061
237038AE2-054 C
Solar/Wind Helper
0.173
233930AB2-032 GEN
Solar/Wind Helper
0.229
233915AB1-141 GEN
Solar/Wind Helper
0.302
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.202
233998TM1NIN_3.36
Solar/Wind Helper
0.156
233954AC2-188 GEN
Solar/Wind Helper
0.139
232404W1-003 C
Solar/Wind Helper
0.303
233950AC2-186 GEN
Solar/Wind Helper
0.069
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.18
205941AD2-115 GEN
Solar/Wind Helper
0.301
230434AG1-499 GEN
Solar/Wind Helper
0.136
230511AF1-262
Solar/Wind Helper
0.009
219258KINSLEYDEP C
Solar/Wind Helper
0.045
228728W1-130C
Solar/Wind Helper
0.032
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.18
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.079
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.897
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.241
963151AG1-164 GEN
Solar/Wind Helper
0.241
212266LOR1
Solar/Wind Helper
0.026
961341AF2-425 GEN
Solar/Wind Helper
0.236
235067AD1-061 GEN
Solar/Wind Helper
0.311
233982AB2-133 GEN
Solar/Wind Helper
0.215
233918AB1-142 GEN
Solar/Wind Helper
0.302
233994AC2-023 GEN
Solar/Wind Helper
0.575
233996TM1833_GEN
Solar/Wind Helper
0.156
233997TMININ_4.2
Solar/Wind Helper
0.156
233952AC2-187 GEN
Solar/Wind Helper
0.139
232406W1-004 FULL
Solar/Wind Helper
0.303
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233971AC1-093 C
Solar/Wind Helper
0.213
230430AE1-229_GEN
Solar/Wind Helper
1.988
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.241
963071AG1-156 GEN
Solar/Wind Helper
0.78
209027LOR2_Q27
Solar/Wind Helper
0.555
961331AF2-424 GEN
Solar/Wind Helper
0.236
961421AF2-433 GEN
Solar/Wind Helper
0.235
957921AF2-086 GEN
Solar/Wind Helper
0.233
946691AF1-333 GEN
Solar/Wind Helper
0.232
946741AF1-338 GEN
Solar/Wind Helper
0.232
209067AE2-060 GEN
Solar/Wind Helper
0.042
212507AE2-042_GEN
Solar/Wind Helper
0.826
946731AF1-337 GEN
Solar/Wind Helper
0.232
209071AE2-133 GEN
Solar/Wind Helper
0.042
315693AD1-088 GEN
Solar/Wind Harmer
1.364
316185AD1-033 GEN
Solar/Wind Harmer
0.947
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.603
316018AA1-139 ULT2
Solar/Wind Harmer
0.766
316017AA1-139 ULT1
Solar/Wind Harmer
0.724
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3146456SLIGO L269
Solar/Wind Harmer
1.055
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.599
316433W1029_GEN2
Solar/Wind Harmer
1.599
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3144356SAPONY
Solar/Wind Harmer
0.306
315742AE1-103 GEN
Solar/Wind Harmer
0.91
3146376EDENTON
Solar/Wind Harmer
0.257
3146376EDENTON
Solar/Wind Harmer
0.257
972185AH1-677 GEN
Adder
4.302
972187AH1-678 GEN
Adder
2.17
970933AG2-581 GEN
Solar/Wind Harmer
7.988
316065AD1-022 GEN
Solar/Wind Harmer
4.211
3145893MURPHYS
Solar/Wind Harmer
0.234
3145893MURPHYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
970099AG2-077 GEN
Solar/Wind Harmer
10.347
316181AB2-040 GEN
Solar/Wind Harmer
1.151
3144293JTRSVLE
Adder
0.228
3144293JTRSVLE
Adder
0.192
226929AD2-058 GEN
Solar/Wind Helper
0.143
237025AB1-124 C
Solar/Wind Helper
0.193
237006AB1-125 GEN
Solar/Wind Helper
0.145
23777801MSM_W1-116
Solar/Wind Helper
0.13
237034AC2-136 C
Solar/Wind Helper
0.204
205916AD1-020 GEN
Solar/Wind Helper
1.477
208835TUHI V3-051
Solar/Wind Helper
0.019
208835TUHI V3-051
Solar/Wind Helper
0.019
237001AB1-127_GEN
Solar/Wind Helper
0.306
237002AB1-128_GEN
Solar/Wind Helper
0.297
235063AE1-101 C2
Solar/Wind Helper
1.061
20390526W1-045 C
Solar/Wind Helper
0.251
23777901MDS_W4-102
Solar/Wind Helper
0.105
235020AA1-095 C
Solar/Wind Helper
0.029
233933AB2-153 GEN
Solar/Wind Helper
0.14
233944AB2-135 GEN
Solar/Wind Helper
0.354
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.402
234036AF2-325 C
Solar/Wind Helper
0.025
233946AB2-136 GEN
Solar/Wind Helper
0.34
233901CHERRYDALE C
Solar/Wind Helper
0.139
232408W1-005 C
Solar/Wind Helper
0.303
232410W1-006 C
Solar/Wind Helper
0.303
233939AC1-091 C
Solar/Wind Helper
0.209
233970AC1-092 C
Solar/Wind Helper
0.209
230433AD2-135 GEN
Solar/Wind Helper
0.01
219921AF1-264
Solar/Wind Helper
0.03
230407AD2-065 C
Solar/Wind Helper
0.024
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.188
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.085
211065PSPA IPP
Solar/Wind Helper
0.085
208972BECR K09
Solar/Wind Helper
0.177
961431AF2-434 GEN
Solar/Wind Helper
0.235
209029WAYMART-WD
Solar/Wind Helper
0.441
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.232
209137AF2-361 C
Solar/Wind Helper
0.706
NYPJM->LTFIMP_NY
CLTF
2.566
LGEELTFEXP_LGEE->PJM
CLTF
1.801
LAGNLTFEXP_LAGN->PJM
CLTF
6.303
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.503
WECLTFEXP_WEC->PJM
CLTF
0.96
TVALTFEXP_TVA->PJM
CLTF
3.177
CPLELTFEXP_CPLE->PJM
CLTF
5.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.853
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.419
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.556
MECLTFEXP_MEC->PJM
CLTF
4.438
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.48 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:2034.78
MW Contribution:3.6
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.076
316415AF1-147_GEN2
Solar/Wind Harmer
1.076
970053AG2-049 GEN
Adder
1.475
316164AC1-076 GEN
Solar/Wind Harmer
0.73
3147346CASHSCORNER
Solar/Wind Harmer
0.123
3141426STAFORD
Solar/Wind Harmer
-0.002
3150411LDYSMT5
Adder
9.22
3150381LDYSMT2
Adder
8.824
972213AH1-691 GEN
Adder
1.493
972215AH1-692 GEN
Adder
1.493
944491AF1-114 GEN
Solar/Wind Harmer
2.206
316223AC1-118
Solar/Wind Harmer
0.2
972189AH1-679 GEN
Adder
1.104
3141813NORNECK
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
3.188
316233AE1-074 FULL
Solar/Wind Harmer
0.196
971281AH1-106 GEN
Solar/Wind Harmer
1.184
971283AH1-107 GEN
Solar/Wind Harmer
1.184
316312AB1-027
Solar/Wind Harmer
0.245
3141783LANCAST
Solar/Wind Harmer
-0.004
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.002
3141913WHIT STONE
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
Adder
0.486
316314AB2-024 C
Solar/Wind Harmer
0.62
316059AD1-063 C
Solar/Wind Harmer
0.164
3143873LANEXA
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
0.873
315666AE1-190 GEN
Solar/Wind Harmer
0.218
957601AF2-054 GEN
Solar/Wind Harmer
0.217
3141873WAN 176
Solar/Wind Harmer
-0.001
315976AC1-164 GENA
Solar/Wind Harmer
7.645
316169AC1-164_GENC
Solar/Wind Harmer
6.604
315975AC1-164 GENB
Solar/Wind Harmer
0.226
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
971167AH1-042 GEN
Solar/Wind Harmer
6.965
957831AF2-077 GEN
Solar/Wind Harmer
0.216
3138283WHITEMARSH
Solar/Wind Harmer
0.011
316132AB2-190 GEN1
Solar/Wind Harmer
0.724
316369SG1_INVT
Solar/Wind Harmer
1.275
972265AH1-717 GEN
Adder
4.91
3151201GRAVEL4
Adder
4.603
3151191GRAVEL3
Adder
4.545
3151211GRAVEL5
Adder
4.545
3143316POE
Solar/Wind Harmer
-0.028
971445AH1-216 GEN
Solar/Wind Harmer
4.385
3151081ELIZAR1
Adder
5.753
3151091ELIZAR2
Adder
5.653
3152611GOSPORTB
Adder
0.799
3152621GOSPORTC
Adder
0.678
3152601GOSPORTA
Adder
0.626
315833AF1-017_GEN
Solar/Wind Harmer
1.334
316349AD2-085 GEN
Solar/Wind Harmer
0.624
316311AC2-079 GEN
Solar/Wind Harmer
3.541
957871AF2-081 GEN
Solar/Wind Harmer
3.509
319010AE1-072 C
Solar/Wind Harmer
1.418
316305AF2-043 C
Solar/Wind Harmer
0.211
3146406KITTY HAWK
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
0.874
313526AB2-022
Solar/Wind Harmer
0.188
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.188
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
3146396TANGLEW
Solar/Wind Harmer
0.128
316315AB2-025 C
Solar/Wind Harmer
0.187
941031AE2-094 GEN
Solar/Wind Harmer
12.98
944011AF1-069 GEN
Solar/Wind Harmer
4.067
315814AE2-033 C
Solar/Wind Harmer
6.44
315611Z1-036_GEN2
Solar/Wind Harmer
1.702
970673AG2-436 GEN
Solar/Wind Harmer
14.439
970673AG2-436 GEN
Solar/Wind Harmer
7.311
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
971967AH1-528 GEN
Solar/Wind Harmer
12.878
315816AE2-034 GEN
Solar/Wind Harmer
0.549
972205AH1-687 GEN
Adder
2.574
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.359
315733AD1-074 GEN2
Solar/Wind Harmer
1.359
315735AD1-075 GEN1
Solar/Wind Harmer
0.68
971845AH1-439 GEN
Solar/Wind Harmer
3.571
965291AG1-394 GEN
Solar/Wind Harmer
0.596
970285AG2-188 GEN
Solar/Wind Harmer
5.876
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
970085AG2-068 GEN
Solar/Wind Harmer
4.185
970581AG2-369 GEN
Solar/Wind Harmer
3.599
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.928
316318V4-068
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
1.348
960921AF2-383 GEN
Solar/Wind Helper
0.147
959381AF2-229 GEN
Solar/Wind Helper
0.283
205943AE1-185 GEN
Solar/Wind Helper
0.409
205956AE1-196_GEN
Solar/Wind Helper
0.406
205932AD2-116_GEN
Solar/Wind Helper
0.406
237085AD2-009_GEN
Solar/Wind Helper
1.049
203975AE1-071-GEN
Solar/Wind Helper
1.871
233935AB2-179 C
Solar/Wind Helper
0.773
232436AB1-176 C
Solar/Wind Helper
0.027
233923SMA
Solar/Wind Helper
0.576
233990AG1-397 GEN
Solar/Wind Helper
0.018
232432Z2-076 GEN
Solar/Wind Helper
0.04
234033AF1-007_GEN
Solar/Wind Helper
4.217
964001AG1-254 GEN
Solar/Wind Helper
0.565
219914AD2-027 C
Solar/Wind Helper
0.068
228754AB1-001 C
Solar/Wind Helper
0.015
227927V4-067C
Solar/Wind Helper
0.006
219272CLEANLIGHT C
Solar/Wind Helper
0.015
219688LUMSOLAR_S C
Solar/Wind Helper
0.023
3152111X4-039 GT1
50/50
1.829
315747AE2-019 GEN
50/50
12.54
963691AG1-221 GEN
Solar/Wind Harmer
2.26
971455AH1-223 GEN
Solar/Wind Harmer
2.26
3141196NOKESVL
Solar/Wind Harmer
-0.043
3150231REMNGT3
Adder
11.81
3150241REMNGT4
Adder
11.012
972199AH1-684 GEN
Adder
1.67
972217AH1-693 GEN
Adder
1.452
3150301M RUN C
Adder
11.698
3150291M RUN B
Adder
11.611
316170AC1-121 GEN2
Solar/Wind Harmer
0.237
316044AC1-158 PL1
Solar/Wind Harmer
0.855
316450AC1-158 RIC
Solar/Wind Harmer
0.228
3132273ORANGE
Solar/Wind Harmer
-0.002
3147666LOUISA
Solar/Wind Harmer
-0.018
3151761LOISA E
Adder
9.484
972183AH1-676 GEN
Adder
76.571
3150151POSSMC1
Adder
0.713
3150151POSSMC1
Adder
0.713
3150331BIRCHWDA
Adder
11.674
3150401LDYSMT4
Adder
9.192
3150371LDYSMT1
Adder
8.882
3141316ARNOLDS
Adder
0.162
966881AG1-559 GEN
Solar/Wind Harmer
0.227
970737AG2-469 GEN
Solar/Wind Harmer
3.736
971781AH1-399 GEN
Solar/Wind Harmer
0.459
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.662
316473AC1-191 GEN
Solar/Wind Harmer
0.788
316404AE1-155 C
Solar/Wind Harmer
1.411
316484AD2-074 GEN
Solar/Wind Harmer
1.837
970009AG2-005 GEN
Solar/Wind Harmer
0.912
962971AG1-146 GEN
Solar/Wind Harmer
1.366
3142416OLDCHRC
Solar/Wind Harmer
0.734
970293AG2-193 GEN
Solar/Wind Harmer
0.907
3150861SPRUNCD
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
0.645
316203AE2-005 GEN
Solar/Wind Harmer
3.054
316280AD1-041 GEN
Solar/Wind Harmer
0.546
316156AD2-030 GEN
Solar/Wind Harmer
0.193
3141873WAN 176
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3143096IRON208
Adder
0.265
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142946ENON
Solar/Wind Harmer
-0.002
316382AG1-145 C
Solar/Wind Harmer
0.216
970133AG2-095 GEN
Solar/Wind Harmer
0.807
970129AG2-093 GEN
Solar/Wind Harmer
4.029
965281AG1-393 GEN
Solar/Wind Harmer
0.893
315778AD1-151 GEN
Solar/Wind Harmer
6.188
3150921YORKTN3
Adder
1.597
315839AE2-212 C
Solar/Wind Harmer
0.215
3144216WINCHST
Adder
0.239
961611AG1-000B GEN
Solar/Wind Harmer
1.499
3151221GRAVEL6
Adder
4.598
3151171GRAVELC
Adder
0.885
315813AE1-149 C
Solar/Wind Harmer
4.431
316313AB2-026
Solar/Wind Harmer
0.191
316258AE1-075 C
Solar/Wind Harmer
0.172
316405AF2-144 C
Solar/Wind Harmer
0.182
3143336POWHATN
Solar/Wind Harmer
0.715
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
2.964
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316083AB2-161 GEN
Solar/Wind Harmer
1.146
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
5.827
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
32.067
944601AF1-125 GEN
Solar/Wind Harmer
31.566
970661AG2-428 GEN
Solar/Wind Harmer
1.328
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.855
316320Y1-086
Solar/Wind Harmer
0.409
316435W1029_GEN3
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3145273HOLLAND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.732
3156081AA2-088 GEN
Solar/Wind Harmer
2.185
971157AH1-035 GEN
Solar/Wind Harmer
0.841
3146776BUCKING
Solar/Wind Harmer
-0.002
315737AD1-076 GEN
Solar/Wind Harmer
1.278
970917AG2-570 GEN
Solar/Wind Harmer
16.768
316365GEN2_N
Solar/Wind Harmer
0.452
3146206CASHIE
Solar/Wind Harmer
-0.007
3145893MURPHYS
Solar/Wind Harmer
0.047
3145893MURPHYS
Solar/Wind Harmer
-0.007
3146926FARMVIL
Solar/Wind Harmer
-0.004
957521AF2-046 GEN
Solar/Wind Harmer
5.262
961681AG1-008 GEN
Solar/Wind Harmer
5.262
970909AG2-566 GEN
Solar/Wind Harmer
0.633
3146173TUNIS
Solar/Wind Harmer
-0.007
972255AH1-712 GEN
Adder
30.164
3144293JTRSVLE
Adder
0.186
237030AB1-096 C
Solar/Wind Helper
0.1
223402AF1-300 C
Solar/Wind Helper
0.385
226910AB2-157 C
Solar/Wind Helper
0.014
205917AD1-020 ES
Solar/Wind Helper
0.357
227287AC2-120 GEN
Solar/Wind Helper
0.309
238221AF1-254 C O1
Solar/Wind Helper
0.197
235067AD1-061 GEN
Solar/Wind Helper
0.341
233982AB2-133 GEN
Solar/Wind Helper
0.216
233918AB1-142 GEN
Solar/Wind Helper
0.304
233994AC2-023 GEN
Solar/Wind Helper
0.578
233996TM1833_GEN
Solar/Wind Helper
0.157
233997TMININ_4.2
Solar/Wind Helper
0.157
233940AF2-379 C
Solar/Wind Helper
0.037
234015AF2-250 C
Solar/Wind Helper
0.023
233952AC2-187 GEN
Solar/Wind Helper
0.14
232406W1-004 FULL
Solar/Wind Helper
0.305
233971AC1-093 C
Solar/Wind Helper
0.214
230430AE1-229_GEN
Solar/Wind Helper
1.992
230415AB2-049 C
Solar/Wind Helper
0.018
219623KINSLEYBEA C
Solar/Wind Helper
0.001
219766PARADISE C
Solar/Wind Helper
0.032
219912AD2-042 GEN
Solar/Wind Helper
0.088
228729W2-030 C
Solar/Wind Helper
0.065
219236SOUTHERNHQ C
Solar/Wind Helper
0.003
219291REEVESSOUT C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.025
219348LDSOLAR C
Solar/Wind Helper
0.067
959561AF2-247 GEN
Solar/Wind Helper
0.012
20716028EGP_W2-019
Solar/Wind Helper
0.011
20720828JCB_W4-025
Solar/Wind Helper
0.037
20715028HAN_X4-015
Solar/Wind Helper
0.033
219276PARKLANDSO C
Solar/Wind Helper
0.052
20714528FRN_Y2-051
Solar/Wind Helper
0.033
20720528MAN_W1-024
Solar/Wind Helper
0.016
219612MATRIX C
Solar/Wind Helper
0.014
218438BLK ROCK C
Solar/Wind Helper
0.016
20673728F2S_V4-070
Solar/Wind Helper
0.017
219908AB1-139 C
Solar/Wind Helper
0.042
219919AE1-041 FULL
Solar/Wind Helper
0.002
219249CENTRALDIV C
Solar/Wind Helper
0.006
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.002
20676728BRNX1-095
Solar/Wind Helper
0.017
207510AF2-138 C
Solar/Wind Helper
0.046
20674628WNG_W3-110
Solar/Wind Helper
0.051
963161AG1-165 GEN
Solar/Wind Helper
0.239
963071AG1-156 GEN
Solar/Wind Helper
0.773
209027LOR2_Q27
Solar/Wind Helper
0.55
961331AF2-424 GEN
Solar/Wind Helper
0.233
961421AF2-433 GEN
Solar/Wind Helper
0.233
957921AF2-086 GEN
Solar/Wind Helper
0.23
209067AE2-060 GEN
Solar/Wind Helper
0.042
946691AF1-333 GEN
Solar/Wind Helper
0.23
946741AF1-338 GEN
Solar/Wind Helper
0.23
3152131X4-039 ST
50/50
2.877
3152121X4-039 GT2
50/50
1.823
3150221REMNGT2
Adder
10.939
3150211REMNGT1
Adder
10.866
972201AH1-685 GEN
Adder
1.887
3150281M RUN A
Adder
11.705
316006AB2-029 C
Solar/Wind Harmer
0.549
971685AH1-345 GEN
Solar/Wind Harmer
0.837
3140676OCCOQUN
Adder
0.203
316254AC1-120 GEN1
Solar/Wind Harmer
0.712
316045AC1-158 PL2
Solar/Wind Harmer
2.734
315683AE1-153 C
Solar/Wind Harmer
8.082
3147666LOUISA
Solar/Wind Harmer
-0.032
316192AB2-158 GEN
Solar/Wind Harmer
0.961
3151751LOISA D
Adder
4.652
972223AH1-696 GEN
Adder
5.63
3150151POSSMC1
Adder
0.713
3141346CRANES
Adder
0.082
972197AH1-683 GEN
Adder
1.435
972219AH1-694 GEN
Adder
1.033
966881AG1-559 GEN
Solar/Wind Harmer
0.078
957971AF2-091 GEN
Solar/Wind Harmer
0.75
972135AH1-637 GEN
Solar/Wind Harmer
0.75
316337AD2-073 GEN
Solar/Wind Harmer
0.198
3150351NORNECKC2
Adder
0.651
964211AG1-282 GEN
Solar/Wind Harmer
0.22
3141726DUNNSVL
Solar/Wind Harmer
-0.029
962861AG1-135 GEN
Solar/Wind Harmer
2.741
961951AG1-038 GEN
Solar/Wind Harmer
0.961
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3143526WINTERP
Solar/Wind Harmer
-0.038
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.004
3150851SPRUNCC
Adder
0.297
3141766HARMONY
Solar/Wind Harmer
-0.001
971777AH1-397 GEN
Solar/Wind Harmer
0.852
3141843SHACKLE
Adder
0.329
3143096IRON208
Adder
0.27
3142433PROV 92
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.125
3142433PROV 92
Adder
0.125
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
30.629
316159AE1-175 C
Solar/Wind Harmer
0.193
971317AH1-138 GEN
Solar/Wind Harmer
0.895
315671AE2-027_GEN
Solar/Wind Harmer
5.367
970129AG2-093 GEN
Solar/Wind Harmer
1.632
316458AB2-190 GEN2
Solar/Wind Harmer
0.724
971069AG2-661 GEN
Solar/Wind Harmer
1.13
3138126ROCKLANDING
Solar/Wind Harmer
0.022
971647AH1-324 GEN
Solar/Wind Harmer
3.563
961611AG1-000B GEN
Solar/Wind Harmer
3.512
3151171GRAVELC
Adder
0.673
3143336POWHATN
Solar/Wind Harmer
0.841
3145336SMITFLD
Solar/Wind Harmer
-0.028
316294AC1-161 GEN
Solar/Wind Harmer
2.291
970659AG2-427 GEN
Solar/Wind Harmer
3.755
316381AD1-082 GEN
Solar/Wind Harmer
0.648
316375AC2-012 GEN
Solar/Wind Harmer
2.44
3150981CHESPKA
Adder
0.784
944591AF1-124 GEN
Solar/Wind Harmer
32.182
970661AG2-428 GEN
Solar/Wind Harmer
7.492
316072AD1-144
Solar/Wind Harmer
0.142
939411AE1-173 GEN
Solar/Wind Harmer
35.173
940641AE2-051 GEN
Solar/Wind Harmer
6.594
316336AC2-165 C
Solar/Wind Harmer
1.222
316388AE2-253 GEN
Solar/Wind Harmer
0.474
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.142
316093AE2-104_GEN
Solar/Wind Harmer
2.034
3146516WINFALL
Solar/Wind Harmer
-0.022
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.702
970937AG2-583 GEN
Solar/Wind Harmer
4.952
3130156CHOWAN
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.019
971163AH1-040 GEN
Solar/Wind Harmer
6.359
972003AH1-546 GEN
Solar/Wind Harmer
3.372
316322AB2-045
Solar/Wind Harmer
0.226
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.123
316023GEN1_S
Solar/Wind Harmer
0.452
970087AG2-069 GEN
Solar/Wind Harmer
6.277
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.673
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.198
3146926FARMVIL
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
972277AH1-723 GEN
Adder
35.15
3147043LAWRENC
Adder
0.53
3144293JTRSVLE
Adder
0.186
23779801AA1-109
Solar/Wind Helper
0.261
223401AF1-299 GEN
Solar/Wind Helper
0.385
966131AG1-482 GEN
Solar/Wind Helper
0.069
237080AD1-060 GEN
Solar/Wind Helper
0.242
235062AE1-101 C1
Solar/Wind Helper
1.169
237038AE2-054 C
Solar/Wind Helper
0.19
233930AB2-032 GEN
Solar/Wind Helper
0.23
233915AB1-141 GEN
Solar/Wind Helper
0.304
232422X3-066 FULL
Solar/Wind Helper
0.069
233964AF2-378 GEN
Solar/Wind Helper
0.025
232426Y1-080 FULL
Solar/Wind Helper
0.023
232428Y3-058 C
Solar/Wind Helper
0.203
233998TM1NIN_3.36
Solar/Wind Helper
0.157
233954AC2-188 GEN
Solar/Wind Helper
0.14
232404W1-003 C
Solar/Wind Helper
0.305
233950AC2-186 GEN
Solar/Wind Helper
0.07
232434Z2-077 GEN
Solar/Wind Helper
0.076
233972AC1-094 C
Solar/Wind Helper
0.181
205941AD2-115 GEN
Solar/Wind Helper
0.302
230511AF1-262
Solar/Wind Helper
0.009
230434AG1-499 GEN
Solar/Wind Helper
0.136
228728W1-130C
Solar/Wind Helper
0.032
219258KINSLEYDEP C
Solar/Wind Helper
0.045
219904AC1-010 C
Solar/Wind Helper
0.036
219907AC1-030 C
Solar/Wind Helper
0.02
218660EHAMPSOLAR C
Solar/Wind Helper
0.019
219686LUMSOLAR_N C
Solar/Wind Helper
0.023
219304NAMERICA C
Solar/Wind Helper
0.077
20720728JCB_W1-129
Solar/Wind Helper
0.033
207445AB1-138_GEN
Solar/Wind Helper
0.061
963711AG1-223 GEN
Solar/Wind Helper
0.037
20714828MDF_W3-079
Solar/Wind Helper
0.076
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.179
20715228NPK_W1-113
Solar/Wind Helper
0.045
20742028HF_AC1-207
Solar/Wind Helper
0.081
207528AF2-192 GEN
Solar/Wind Helper
0.044
20673628F1S_V4-069
Solar/Wind Helper
0.017
20675428EAM_W2-061
Solar/Wind Helper
0.009
218428ETC SOLAR C
Solar/Wind Helper
0.003
20676428JCR_X2-075
Solar/Wind Helper
0.039
217213AMBOY SO C
Solar/Wind Helper
0.016
217209CENTRL HS C
Solar/Wind Helper
0.005
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.013
207437AD2-070 GEN
Solar/Wind Helper
0.078
207439AE1-081 C O1
Solar/Wind Helper
0.011
207518AF1-320_GEN
Solar/Wind Helper
0.893
972289AH1-729 GEN
50/50
13.169
315651AD1-115 GEN
Solar/Wind Harmer
3.939
316447AC1-158 HLD
Solar/Wind Harmer
1.879
966001AG1-469 GEN
Solar/Wind Harmer
0.153
3151731LOISA B
Adder
4.652
3151721LOISA A
Adder
4.628
3150071POSSM 5
Adder
32.578
3150181POSSMC2
Adder
0.719
3150181POSSMC2
Adder
0.713
3150181POSSMC2
Adder
0.713
3150391LDYSMT3
Adder
9.175
972195AH1-682 GEN
Adder
1.206
315673AE1-157 GEN
Solar/Wind Harmer
5.71
957411AF2-035 GEN
Solar/Wind Harmer
3.403
970317AG2-208 GEN
Solar/Wind Harmer
3.309
316468AD1-105 GEN
Solar/Wind Harmer
0.83
316077AC2-138 C
Solar/Wind Harmer
0.155
3150341NORNECKC1
Adder
0.684
3150341NORNECKC1
Adder
0.679
966871AG1-558 GEN
Solar/Wind Harmer
0.22
966871AG1-558 GEN
Solar/Wind Harmer
0.075
958261AF2-120 GEN
Solar/Wind Harmer
2.834
3142296MT RD221
Adder
0.207
316487AF1-042 GEN
Solar/Wind Harmer
0.961
971223AH1-071 GEN
Solar/Wind Harmer
0.912
3143526WINTERP
Solar/Wind Harmer
-0.038
3142366NRTHEST
Adder
0.211
3150691DARBY 3
Adder
4.65
3150701DARBY 4
Adder
4.64
3150681DARBY 2
Adder
4.634
3150671DARBY 1
Adder
4.629
316075AC2-137 C
Solar/Wind Harmer
0.196
316441AF1-014 GEN
Solar/Wind Harmer
0.488
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
30.436
316240AF1-291 C
Solar/Wind Harmer
0.216
316033AB2-134 GEN
Solar/Wind Harmer
2.301
315697AD1-025 GEN
Solar/Wind Harmer
1.443
316236AE1-162_GEN
Solar/Wind Harmer
0.214
970657AG2-426 GEN
Solar/Wind Harmer
2.206
970657AG2-426 GEN
Solar/Wind Harmer
0.461
316036AC1-147 C
Solar/Wind Harmer
0.19
3150991CHESPKB
Adder
0.657
3150991CHESPKB
Adder
0.642
3142956BIRDNECK
Solar/Wind Harmer
0.378
316316AC1-027 C
Solar/Wind Harmer
0.216
316185AD1-033 GEN
Solar/Wind Harmer
0.743
3145506HICKORY
Solar/Wind Harmer
-0.028
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
316339AD2-160 GEN
Solar/Wind Harmer
0.474
316018AA1-139 ULT2
Solar/Wind Harmer
0.601
316017AA1-139 ULT1
Solar/Wind Harmer
0.568
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.828
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146386ELIZ CT
Solar/Wind Harmer
-0.007
971761AH1-387 GEN
Solar/Wind Harmer
3.885
316431W1029_GEN1
Solar/Wind Harmer
1.259
316433W1029_GEN2
Solar/Wind Harmer
1.259
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3144356SAPONY
Solar/Wind Harmer
0.242
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315742AE1-103 GEN
Solar/Wind Harmer
0.719
3146376EDENTON
Solar/Wind Harmer
0.203
3146376EDENTON
Solar/Wind Harmer
0.203
972185AH1-677 GEN
Adder
3.421
972187AH1-678 GEN
Adder
1.728
970933AG2-581 GEN
Solar/Wind Harmer
6.373
3146776BUCKING
Solar/Wind Harmer
-0.027
3146776BUCKING
Solar/Wind Harmer
-0.002
316065AD1-022 GEN
Solar/Wind Harmer
3.351
3145893MURPHYS
Solar/Wind Harmer
0.187
3145893MURPHYS
Solar/Wind Harmer
-0.012
970301AG2-198 GEN
Solar/Wind Harmer
3.335
971741AH1-377 GEN
Solar/Wind Harmer
7.747
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
3144293JTRSVLE
Adder
0.186
3144293JTRSVLE
Adder
0.157
237025AB1-124 C
Solar/Wind Helper
0.233
237006AB1-125 GEN
Solar/Wind Helper
0.175
23777801MSM_W1-116
Solar/Wind Helper
0.156
237034AC2-136 C
Solar/Wind Helper
0.239
205916AD1-020 GEN
Solar/Wind Helper
1.658
237001AB1-127_GEN
Solar/Wind Helper
0.342
237002AB1-128_GEN
Solar/Wind Helper
0.33
226929AD2-058 GEN
Solar/Wind Helper
0.078
208835TUHI V3-051
Solar/Wind Helper
0.02
208835TUHI V3-051
Solar/Wind Helper
0.02
235063AE1-101 C2
Solar/Wind Helper
1.169
20390526W1-045 C
Solar/Wind Helper
0.277
23777901MDS_W4-102
Solar/Wind Helper
0.113
235020AA1-095 C
Solar/Wind Helper
0.03
233933AB2-153 GEN
Solar/Wind Helper
0.141
233944AB2-135 GEN
Solar/Wind Helper
0.356
232424Y1-079 C
Solar/Wind Helper
0.07
233987AB2-037 GEN
Solar/Wind Helper
1.409
233946AB2-136 GEN
Solar/Wind Helper
0.342
234036AF2-325 C
Solar/Wind Helper
0.025
233901CHERRYDALE C
Solar/Wind Helper
0.14
232408W1-005 C
Solar/Wind Helper
0.305
232410W1-006 C
Solar/Wind Helper
0.305
233939AC1-091 C
Solar/Wind Helper
0.21
233970AC1-092 C
Solar/Wind Helper
0.21
230433AD2-135 GEN
Solar/Wind Helper
0.01
230407AD2-065 C
Solar/Wind Helper
0.024
219921AF1-264
Solar/Wind Helper
0.03
219615MILLCREEK C
Solar/Wind Helper
0.016
963401AG1-189 GEN
Solar/Wind Helper
0.033
963391AG1-188 GEN
Solar/Wind Helper
0.048
20714928UPF_X1-085
Solar/Wind Helper
0.003
20720628TIN_W1-124
Solar/Wind Helper
0.11
20716928W4-060COL
Solar/Wind Helper
0.03
20673828FLE_V3-070
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.009
207442AE1-156 GEN
Solar/Wind Helper
0.187
20676128MHD_W3-029
Solar/Wind Helper
0.055
20671828STAW2-080
Solar/Wind Helper
0.015
217081WEATEXAS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.004
217204WCALDSOLAR C
Solar/Wind Helper
0.002
207471AF2-354 C
Solar/Wind Helper
0.096
20674928WA_W3-044
Solar/Wind Helper
0.056
964851AG1-348 GEN
Solar/Wind Helper
0.046
20674128FR_U2-059
Solar/Wind Helper
0.002
20676228FRD_X1-012
Solar/Wind Helper
0.052
966111AG1-480 GEN
Solar/Wind Helper
0.025
211065PSPA IPP
Solar/Wind Helper
0.084
211065PSPA IPP
Solar/Wind Helper
0.084
208972BECR K09
Solar/Wind Helper
0.176
961431AF2-434 GEN
Solar/Wind Helper
0.233
209029WAYMART-WD
Solar/Wind Helper
0.437
219607WPEMNERT C
Solar/Wind Helper
0.047
214067T20SOLAR
Solar/Wind Helper
0.007
20715728PEM_W1-119
Solar/Wind Helper
0.056
20715828PEM_W1-120
Solar/Wind Helper
0.056
207459AE1-142 C O1
Solar/Wind Helper
0.169
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.05
218526CNTRALGAS2 C
Solar/Wind Helper
0.092
218524CNTRALGAS1 C
Solar/Wind Helper
0.092
966261AG1-495 GEN
Solar/Wind Helper
0.047
20675928HOL_W4-097
Solar/Wind Helper
0.028
207530AG1-191 GEN
Solar/Wind Helper
0.037
207484AF2-139 C O1
Solar/Wind Helper
0.048
20676328BVR_Y1-020
Solar/Wind Helper
0.015
20674828DL_W4-046
Solar/Wind Helper
0.004
207408W3-077 C
Solar/Wind Helper
0.048
20675728RH_W2-091
Solar/Wind Helper
0.078
20675128HRM_W1-127
Solar/Wind Helper
0.017
209116AE2-175 GEN
Solar/Wind Helper
0.994
961261AF2-417 GEN
Solar/Wind Helper
0.238
959431AF2-234 GEN
Solar/Wind Helper
0.459
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.229
238208AF1-136 C
Solar/Wind Helper
0.089
209137AF2-361 C
Solar/Wind Helper
0.703
209054AE2-059 GEN
Solar/Wind Helper
0.042
946751AF1-339 GEN
Solar/Wind Helper
0.23
970099AG2-077 GEN
Solar/Wind Harmer
2.284
20671928W4-073
Solar/Wind Helper
0.051
20675828AU_W4-064
Solar/Wind Helper
0.017
961301AF2-421 GEN
Solar/Wind Helper
0.239
963151AG1-164 GEN
Solar/Wind Helper
0.239
212266LOR1
Solar/Wind Helper
0.025
961341AF2-425 GEN
Solar/Wind Helper
0.233
212507AE2-042_GEN
Solar/Wind Helper
0.817
946731AF1-337 GEN
Solar/Wind Helper
0.23
209071AE2-133 GEN
Solar/Wind Helper
0.041
957481AF2-042 GEN
Solar/Wind Harmer
5.711
NYPJM->LTFIMP_NY
CLTF
2.532
LGEELTFEXP_LGEE->PJM
CLTF
1.753
LAGNLTFEXP_LAGN->PJM
CLTF
5.835
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.776
WECLTFEXP_WEC->PJM
CLTF
0.941
TVALTFEXP_TVA->PJM
CLTF
2.938
CPLELTFEXP_CPLE->PJM
CLTF
4.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.691
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.772
MECLTFEXP_MEC->PJM
CLTF
4.292
SIGELTFEXP_SIGE->PJM
CLTF
0.135

Details for 6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.55 %
Rating:1809.0 MVA
Rating Type:C
MVA to Mitigate:1909.41
MW Contribution:4.25
Bus #Bus NameTypeMW Contribution
3138216PACIFIC
Solar/Wind Harmer
-0.003
316411AF1-147_GEN1
Solar/Wind Harmer
1.2
316415AF1-147_GEN2
Solar/Wind Harmer
1.2
970053AG2-049 GEN
Adder
1.707
316164AC1-076 GEN
Solar/Wind Harmer
0.848
3141426STAFORD
Solar/Wind Harmer
-0.002
3147346CASHSCORNER
Solar/Wind Harmer
0.143
3150411LDYSMT5
Adder
10.908
3150381LDYSMT2
Adder
10.439
972213AH1-691 GEN
Adder
1.766
972215AH1-692 GEN
Adder
1.766
944491AF1-114 GEN
Solar/Wind Harmer
2.612
316223AC1-118
Solar/Wind Harmer
0.237
972189AH1-679 GEN
Adder
1.305
3141813NORNECK
Solar/Wind Harmer
-0.009
962981AG1-147 GEN
Solar/Wind Harmer
3.767
316312AB1-027
Solar/Wind Harmer
0.29
316233AE1-074 FULL
Solar/Wind Harmer
0.231
971281AH1-106 GEN
Solar/Wind Harmer
1.396
971283AH1-107 GEN
Solar/Wind Harmer
1.396
3141783LANCAST
Solar/Wind Harmer
-0.005
3141783LANCAST
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.003
3141913WHIT STONE
Solar/Wind Harmer
-0.009
316314AB2-024 C
Solar/Wind Harmer
0.732
316059AD1-063 C
Solar/Wind Harmer
0.193
315662AE1-191 GEN
Solar/Wind Harmer
1.031
315666AE1-190 GEN
Solar/Wind Harmer
0.258
957601AF2-054 GEN
Solar/Wind Harmer
0.256
3143873LANEXA
Solar/Wind Harmer
-0.005
3141873WAN 176
Solar/Wind Harmer
-0.002
971285AH1-108 GEN
Adder
0.574
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
315976AC1-164 GENA
Solar/Wind Harmer
9.028
316169AC1-164_GENC
Solar/Wind Harmer
7.799
315975AC1-164 GENB
Solar/Wind Harmer
0.267
971167AH1-042 GEN
Solar/Wind Harmer
8.225
957831AF2-077 GEN
Solar/Wind Harmer
0.255
3138283WHITEMARSH
Solar/Wind Harmer
0.013
316132AB2-190 GEN1
Solar/Wind Harmer
0.854
316369SG1_INVT
Solar/Wind Harmer
1.505
972265AH1-717 GEN
Adder
5.796
3151201GRAVEL4
Adder
5.433
3151191GRAVEL3
Adder
5.364
3151211GRAVEL5
Adder
5.364
3143316POE
Solar/Wind Harmer
-0.033
971445AH1-216 GEN
Solar/Wind Harmer
5.176
3151081ELIZAR1
Adder
6.79
3151091ELIZAR2
Adder
6.672
3152611GOSPORTB
Adder
0.943
3152621GOSPORTC
Adder
0.801
3152601GOSPORTA
Adder
0.738
315833AF1-017_GEN
Solar/Wind Harmer
1.574
316349AD2-085 GEN
Solar/Wind Harmer
0.737
316311AC2-079 GEN
Solar/Wind Harmer
4.18
957871AF2-081 GEN
Solar/Wind Harmer
4.142
319010AE1-072 C
Solar/Wind Harmer
1.673
316305AF2-043 C
Solar/Wind Harmer
0.249
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315835AF2-110_GEN
Solar/Wind Harmer
1.032
313526AB2-022
Solar/Wind Harmer
0.222
3146486SUNBURY
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.222
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
3146396TANGLEW
Solar/Wind Harmer
0.151
316315AB2-025 C
Solar/Wind Harmer
0.22
941031AE2-094 GEN
Solar/Wind Harmer
15.312
944011AF1-069 GEN
Solar/Wind Harmer
4.798
315814AE2-033 C
Solar/Wind Harmer
7.6
315611Z1-036_GEN2
Solar/Wind Harmer
2.009
970673AG2-436 GEN
Solar/Wind Harmer
17.036
970673AG2-436 GEN
Solar/Wind Harmer
8.626
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
971967AH1-528 GEN
Solar/Wind Harmer
15.195
315816AE2-034 GEN
Solar/Wind Harmer
0.648
972205AH1-687 GEN
Adder
3.036
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.605
315733AD1-074 GEN2
Solar/Wind Harmer
1.605
315735AD1-075 GEN1
Solar/Wind Harmer
0.803
965291AG1-394 GEN
Solar/Wind Harmer
0.704
971845AH1-439 GEN
Solar/Wind Harmer
4.213
970285AG2-188 GEN
Solar/Wind Harmer
6.934
3138266HYDRAULIC
Solar/Wind Harmer
0
3138266HYDRAULIC
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.94
970581AG2-369 GEN
Solar/Wind Harmer
4.248
970601AG2-382 GEN
Solar/Wind Harmer
3.458
316318V4-068
Solar/Wind Harmer
0.197
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
972193AH1-681 GEN
Adder
1.595
3151881LOWMORC
Adder
0.669
3151881LOWMORC
Adder
0.659
3151861LOWMORA
Adder
0.648
972257AH1-713 GEN
Adder
0.697
23544701WINZ1-113
Adder
0.24
960921AF2-383 GEN
Solar/Wind Helper
0.152
205943AE1-185 GEN
Solar/Wind Helper
0.423
205932AD2-116_GEN
Solar/Wind Helper
0.422
205956AE1-196_GEN
Solar/Wind Helper
0.422
233935AB2-179 C
Solar/Wind Helper
1.004
232436AB1-176 C
Solar/Wind Helper
0.035
233923SMA
Solar/Wind Helper
0.755
233990AG1-397 GEN
Solar/Wind Helper
0.024
234033AF1-007_GEN
Solar/Wind Helper
5.529
232432Z2-076 GEN
Solar/Wind Helper
0.053
964001AG1-254 GEN
Solar/Wind Helper
0.738
227927V4-067C
Solar/Wind Helper
0.008
228754AB1-001 C
Solar/Wind Helper
0.02
219914AD2-027 C
Solar/Wind Helper
0.088
219272CLEANLIGHT C
Solar/Wind Helper
0.019
219688LUMSOLAR_S C
Solar/Wind Helper
0.031
219607WPEMNERT C
Solar/Wind Helper
0.061
214067T20SOLAR
Solar/Wind Helper
0.009
20715728PEM_W1-119
Solar/Wind Helper
0.073
20715828PEM_W1-120
Solar/Wind Helper
0.073
207459AE1-142 C O1
Solar/Wind Helper
0.22
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.065
218526CNTRALGAS2 C
Solar/Wind Helper
0.12
218524CNTRALGAS1 C
Solar/Wind Helper
0.12
966261AG1-495 GEN
Solar/Wind Helper
0.06
207530AG1-191 GEN
Solar/Wind Helper
0.049
20676328BVR_Y1-020
Solar/Wind Helper
0.02
20675928HOL_W4-097
Solar/Wind Helper
0.037
20674828DL_W4-046
Solar/Wind Helper
0.006
207484AF2-139 C O1
Solar/Wind Helper
0.062
207408W3-077 C
Solar/Wind Helper
0.062
20675728RH_W2-091
Solar/Wind Helper
0.1
20675128HRM_W1-127
Solar/Wind Helper
0.022
209116AE2-175 GEN
Solar/Wind Helper
1.289
961261AF2-417 GEN
Solar/Wind Helper
0.308
959381AF2-229 GEN
Solar/Wind Helper
0.23
959431AF2-234 GEN
Solar/Wind Helper
0.594
964051AG1-259 GEN
Solar/Wind Helper
0.044
964061AG1-260 GEN
Solar/Wind Helper
0.044
959421AF2-233 GEN
Solar/Wind Helper
0.297
203975AE1-071-GEN
Solar/Wind Helper
1.563
3152131X4-039 ST
50/50
3.158
3152121X4-039 GT2
50/50
2.001
970467AG2-304 GEN
50/50
15.27
3150221REMNGT2
Adder
12.559
3150211REMNGT1
Adder
12.476
972201AH1-685 GEN
Adder
2.167
3150281M RUN A
Adder
13.444
316006AB2-029 C
Solar/Wind Harmer
0.632
971685AH1-345 GEN
Solar/Wind Harmer
0.963
3140676OCCOQUN
Adder
0.237
316254AC1-120 GEN1
Solar/Wind Harmer
0.825
316045AC1-158 PL2
Solar/Wind Harmer
3.177
315683AE1-153 C
Solar/Wind Harmer
9.363
972223AH1-696 GEN
Adder
6.699
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.038
316192AB2-158 GEN
Solar/Wind Harmer
1.122
3151751LOISA D
Adder
5.425
3141346CRANES
Adder
0.098
972197AH1-683 GEN
Adder
1.698
972219AH1-694 GEN
Adder
1.223
966881AG1-559 GEN
Solar/Wind Harmer
0.092
957971AF2-091 GEN
Solar/Wind Harmer
0.888
972135AH1-637 GEN
Solar/Wind Harmer
0.887
316337AD2-073 GEN
Solar/Wind Harmer
0.235
3150351NORNECKC2
Adder
0.77
964211AG1-282 GEN
Solar/Wind Harmer
0.261
3141726DUNNSVL
Solar/Wind Harmer
-0.034
962861AG1-135 GEN
Solar/Wind Harmer
3.239
961951AG1-038 GEN
Solar/Wind Harmer
1.136
3143226MDLTHAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3142416OLDCHRC
Solar/Wind Harmer
-0.008
3143526WINTERP
Solar/Wind Harmer
-0.044
3138133OCRAN
Solar/Wind Harmer
-0.005
3141766HARMONY
Solar/Wind Harmer
-0.002
971777AH1-397 GEN
Solar/Wind Harmer
1.006
3141843SHACKLE
Adder
0.389
3150851SPRUNCC
Adder
0.351
3143096IRON208
Adder
0.319
3142433PROV 92
Solar/Wind Harmer
-0.034
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142543TWELFTH
Solar/Wind Harmer
-0.001
944631AF1-128 GEN
Adder
36.159
316159AE1-175 C
Solar/Wind Harmer
0.227
971317AH1-138 GEN
Solar/Wind Harmer
1.057
315671AE2-027_GEN
Solar/Wind Harmer
6.335
970129AG2-093 GEN
Solar/Wind Harmer
1.926
316458AB2-190 GEN2
Solar/Wind Harmer
0.854
971069AG2-661 GEN
Solar/Wind Harmer
1.334
3138126ROCKLANDING
Solar/Wind Harmer
0.026
971647AH1-324 GEN
Solar/Wind Harmer
4.206
961611AG1-000B GEN
Solar/Wind Harmer
4.146
3151171GRAVELC
Adder
0.794
3145336SMITFLD
Solar/Wind Harmer
-0.033
316294AC1-161 GEN
Solar/Wind Harmer
2.704
3143336POWHATN
Solar/Wind Harmer
0.991
970659AG2-427 GEN
Solar/Wind Harmer
4.431
316381AD1-082 GEN
Solar/Wind Harmer
0.765
316375AC2-012 GEN
Solar/Wind Harmer
2.88
3150981CHESPKA
Adder
0.925
944591AF1-124 GEN
Solar/Wind Harmer
37.981
970661AG2-428 GEN
Solar/Wind Harmer
8.843
316072AD1-144
Solar/Wind Harmer
0.168
939411AE1-173 GEN
Solar/Wind Harmer
41.494
940641AE2-051 GEN
Solar/Wind Harmer
7.777
316336AC2-165 C
Solar/Wind Harmer
1.441
316388AE2-253 GEN
Solar/Wind Harmer
0.559
3146456SLIGO L269
Solar/Wind Harmer
-0.008
316246AF1-032 C
Solar/Wind Harmer
0.167
316093AE2-104_GEN
Solar/Wind Harmer
2.401
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
2.009
970937AG2-583 GEN
Solar/Wind Harmer
5.84
3130156CHOWAN
Solar/Wind Harmer
-0.008
3145663CRESWEL
Solar/Wind Harmer
-0.022
971163AH1-040 GEN
Solar/Wind Harmer
7.509
972003AH1-546 GEN
Solar/Wind Harmer
3.978
316322AB2-045
Solar/Wind Harmer
0.267
3146776BUCKING
Solar/Wind Harmer
-0.003
970919AG2-571 GEN
Solar/Wind Harmer
2.505
316023GEN1_S
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
970087AG2-069 GEN
Solar/Wind Harmer
7.409
971547AH1-271 GEN
Solar/Wind Harmer
1.976
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.234
3146926FARMVIL
Solar/Wind Harmer
-0.005
3146173TUNIS
Solar/Wind Harmer
-0.008
972277AH1-723 GEN
Adder
41.593
3147043LAWRENC
Adder
0.626
3144293JTRSVLE
Adder
0.22
223401AF1-299 GEN
Solar/Wind Helper
0.379
23779801AA1-109
Solar/Wind Helper
0.182
966131AG1-482 GEN
Solar/Wind Helper
0.066
233930AB2-032 GEN
Solar/Wind Helper
0.301
233915AB1-141 GEN
Solar/Wind Helper
0.397
232422X3-066 FULL
Solar/Wind Helper
0.09
233964AF2-378 GEN
Solar/Wind Helper
0.033
232426Y1-080 FULL
Solar/Wind Helper
0.031
233998TM1NIN_3.36
Solar/Wind Helper
0.206
232428Y3-058 C
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.4
233954AC2-188 GEN
Solar/Wind Helper
0.183
233950AC2-186 GEN
Solar/Wind Helper
0.091
232434Z2-077 GEN
Solar/Wind Helper
0.1
233972AC1-094 C
Solar/Wind Helper
0.238
230511AF1-262
Solar/Wind Helper
0.011
230434AG1-499 GEN
Solar/Wind Helper
0.177
228728W1-130C
Solar/Wind Helper
0.041
219258KINSLEYDEP C
Solar/Wind Helper
0.059
219904AC1-010 C
Solar/Wind Helper
0.047
219907AC1-030 C
Solar/Wind Helper
0.026
218660EHAMPSOLAR C
Solar/Wind Helper
0.025
219686LUMSOLAR_N C
Solar/Wind Helper
0.031
219304NAMERICA C
Solar/Wind Helper
0.1
20720728JCB_W1-129
Solar/Wind Helper
0.043
207445AB1-138_GEN
Solar/Wind Helper
0.079
963711AG1-223 GEN
Solar/Wind Helper
0.048
20714828MDF_W3-079
Solar/Wind Helper
0.099
205941AD2-115 GEN
Solar/Wind Helper
0.375
219680HOPEWELLV C1
Solar/Wind Helper
0.002
207454AA2-184 E
Solar/Wind Helper
0.234
20715228NPK_W1-113
Solar/Wind Helper
0.059
20742028HF_AC1-207
Solar/Wind Helper
0.106
218428ETC SOLAR C
Solar/Wind Helper
0.004
217213AMBOY SO C
Solar/Wind Helper
0.021
207528AF2-192 GEN
Solar/Wind Helper
0.057
20673628F1S_V4-069
Solar/Wind Helper
0.022
20675428EAM_W2-061
Solar/Wind Helper
0.012
20676428JCR_X2-075
Solar/Wind Helper
0.051
217209CENTRL HS C
Solar/Wind Helper
0.006
217208PARK ELE C
Solar/Wind Helper
0.003
20674328GAR_V4-001
Solar/Wind Helper
0.017
207439AE1-081 C O1
Solar/Wind Helper
0.014
207437AD2-070 GEN
Solar/Wind Helper
0.101
20675828AU_W4-064
Solar/Wind Helper
0.022
207518AF1-320_GEN
Solar/Wind Helper
1.156
20671928W4-073
Solar/Wind Helper
0.066
961301AF2-421 GEN
Solar/Wind Helper
0.309
963151AG1-164 GEN
Solar/Wind Helper
0.309
212266LOR1
Solar/Wind Helper
0.033
961341AF2-425 GEN
Solar/Wind Helper
0.302
212507AE2-042_GEN
Solar/Wind Helper
1.058
946731AF1-337 GEN
Solar/Wind Helper
0.297
209071AE2-133 GEN
Solar/Wind Helper
0.054
235062AE1-101 C1
Solar/Wind Helper
0.747
237080AD1-060 GEN
Solar/Wind Helper
0.151
237038AE2-054 C
Solar/Wind Helper
0.119
957481AF2-042 GEN
Solar/Wind Harmer
6.742
3152111X4-039 GT1
50/50
2.007
315747AE2-019 GEN
50/50
14.059
963691AG1-221 GEN
Solar/Wind Harmer
2.52
971455AH1-223 GEN
Solar/Wind Harmer
2.52
3141196NOKESVL
Solar/Wind Harmer
-0.049
3150231REMNGT3
Adder
13.559
3150241REMNGT4
Adder
12.643
972199AH1-684 GEN
Adder
1.917
972217AH1-693 GEN
Adder
1.667
3150301M RUN C
Adder
13.435
3150291M RUN B
Adder
13.336
316170AC1-121 GEN2
Solar/Wind Harmer
0.275
316044AC1-158 PL1
Solar/Wind Harmer
0.993
316450AC1-158 RIC
Solar/Wind Harmer
0.265
3132273ORANGE
Solar/Wind Harmer
-0.002
3150151POSSMC1
Adder
0.848
3150151POSSMC1
Adder
0.848
3147666LOUISA
Solar/Wind Harmer
-0.022
3151761LOISA E
Adder
11.06
972183AH1-676 GEN
Adder
89.287
3150331BIRCHWDA
Adder
13.842
3141316ARNOLDS
Adder
0.192
3150401LDYSMT4
Adder
10.874
3150371LDYSMT1
Adder
10.507
966881AG1-559 GEN
Solar/Wind Harmer
0.269
970737AG2-469 GEN
Solar/Wind Harmer
4.42
971781AH1-399 GEN
Solar/Wind Harmer
0.543
3141906WESTMOR
Solar/Wind Harmer
-0.003
3150351NORNECKC2
Adder
0.783
316473AC1-191 GEN
Solar/Wind Harmer
0.931
316404AE1-155 C
Solar/Wind Harmer
1.667
316484AD2-074 GEN
Solar/Wind Harmer
2.171
970009AG2-005 GEN
Solar/Wind Harmer
1.078
962971AG1-146 GEN
Solar/Wind Harmer
1.614
3142416OLDCHRC
Solar/Wind Harmer
0.867
970293AG2-193 GEN
Solar/Wind Harmer
1.071
3141766HARMONY
Solar/Wind Harmer
0.762
316203AE2-005 GEN
Solar/Wind Harmer
3.607
316280AD1-041 GEN
Solar/Wind Harmer
0.645
316156AD2-030 GEN
Solar/Wind Harmer
0.228
3141873WAN 176
Solar/Wind Harmer
1.015
3141843SHACKLE
Adder
0.389
3150861SPRUNCD
Adder
0.351
3143096IRON208
Adder
0.319
3143096IRON208
Adder
0.312
3142433PROV 92
Adder
0.148
3142433PROV 92
Adder
0.148
3142946ENON
Solar/Wind Harmer
-0.003
316382AG1-145 C
Solar/Wind Harmer
0.255
970133AG2-095 GEN
Solar/Wind Harmer
0.953
970129AG2-093 GEN
Solar/Wind Harmer
4.756
965281AG1-393 GEN
Solar/Wind Harmer
1.054
315778AD1-151 GEN
Solar/Wind Harmer
7.304
3150921YORKTN3
Adder
1.885
315839AE2-212 C
Solar/Wind Harmer
0.254
3144216WINCHST
Adder
0.283
961611AG1-000B GEN
Solar/Wind Harmer
1.769
3151221GRAVEL6
Adder
5.427
3151171GRAVELC
Adder
1.044
315813AE1-149 C
Solar/Wind Harmer
5.23
3145336SMITFLD
Solar/Wind Harmer
-0.003
315773AC2-141 GEN
Solar/Wind Harmer
3.497
316313AB2-026
Solar/Wind Harmer
0.225
316258AE1-075 C
Solar/Wind Harmer
0.203
316405AF2-144 C
Solar/Wind Harmer
0.214
3143336POWHATN
Solar/Wind Harmer
0.843
970659AG2-427 GEN
Solar/Wind Harmer
0.785
316083AB2-161 GEN
Solar/Wind Harmer
1.353
3144536CHRHLND
Solar/Wind Harmer
-0.001
3151101ELIZAR3
Adder
6.877
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
37.845
944601AF1-125 GEN
Solar/Wind Harmer
37.254
970661AG2-428 GEN
Solar/Wind Harmer
1.567
3146456SLIGO L269
Solar/Wind Harmer
-0.008
971153AH1-033 GEN
Solar/Wind Harmer
1.009
316320Y1-086
Solar/Wind Harmer
0.483
316435W1029_GEN3
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
315614AA2-178 GEN
Solar/Wind Harmer
0.864
3156081AA2-088 GEN
Solar/Wind Harmer
2.58
971157AH1-035 GEN
Solar/Wind Harmer
0.994
315737AD1-076 GEN
Solar/Wind Harmer
1.509
3146776BUCKING
Solar/Wind Harmer
-0.003
970917AG2-570 GEN
Solar/Wind Harmer
19.793
316365GEN2_N
Solar/Wind Harmer
0.534
3146206CASHIE
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.005
957521AF2-046 GEN
Solar/Wind Harmer
6.214
961681AG1-008 GEN
Solar/Wind Harmer
6.214
970909AG2-566 GEN
Solar/Wind Harmer
0.747
3146173TUNIS
Solar/Wind Harmer
-0.008
972255AH1-712 GEN
Adder
35.693
3144293JTRSVLE
Adder
0.22
3151861LOWMORA
Adder
0.674
3152541MT STMG
Adder
0.593
237030AB1-096 C
Solar/Wind Helper
0.073
223402AF1-300 C
Solar/Wind Helper
0.379
226910AB2-157 C
Solar/Wind Helper
0.012
205917AD1-020 ES
Solar/Wind Helper
0.322
227287AC2-120 GEN
Solar/Wind Helper
0.266
233918AB1-142 GEN
Solar/Wind Helper
0.397
233982AB2-133 GEN
Solar/Wind Helper
0.282
233994AC2-023 GEN
Solar/Wind Helper
0.757
233996TM1833_GEN
Solar/Wind Helper
0.206
233997TMININ_4.2
Solar/Wind Helper
0.206
233940AF2-379 C
Solar/Wind Helper
0.049
234015AF2-250 C
Solar/Wind Helper
0.03
232406W1-004 FULL
Solar/Wind Helper
0.4
233952AC2-187 GEN
Solar/Wind Helper
0.183
233971AC1-093 C
Solar/Wind Helper
0.281
230430AE1-229_GEN
Solar/Wind Helper
2.603
230415AB2-049 C
Solar/Wind Helper
0.023
228729W2-030 C
Solar/Wind Helper
0.085
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.042
219912AD2-042 GEN
Solar/Wind Helper
0.115
219291REEVESSOUT C
Solar/Wind Helper
0.009
219236SOUTHERNHQ C
Solar/Wind Helper
0.004
219906AC1-017 C
Solar/Wind Helper
0.032
219348LDSOLAR C
Solar/Wind Helper
0.088
959561AF2-247 GEN
Solar/Wind Helper
0.016
20716028EGP_W2-019
Solar/Wind Helper
0.014
20720828JCB_W4-025
Solar/Wind Helper
0.048
20715028HAN_X4-015
Solar/Wind Helper
0.043
219276PARKLANDSO C
Solar/Wind Helper
0.068
20714528FRN_Y2-051
Solar/Wind Helper
0.043
20720528MAN_W1-024
Solar/Wind Helper
0.021
219612MATRIX C
Solar/Wind Helper
0.018
218438BLK ROCK C
Solar/Wind Helper
0.02
219908AB1-139 C
Solar/Wind Helper
0.055
219919AE1-041 FULL
Solar/Wind Helper
0.003
219249CENTRALDIV C
Solar/Wind Helper
0.008
20673728F2S_V4-070
Solar/Wind Helper
0.022
217211CAMDEN ST C
Solar/Wind Helper
0.003
217169METRODIV C
Solar/Wind Helper
0.003
20676728BRNX1-095
Solar/Wind Helper
0.022
207510AF2-138 C
Solar/Wind Helper
0.06
20674628WNG_W3-110
Solar/Wind Helper
0.066
963161AG1-165 GEN
Solar/Wind Helper
0.309
963071AG1-156 GEN
Solar/Wind Helper
1.001
209027LOR2_Q27
Solar/Wind Helper
0.712
961331AF2-424 GEN
Solar/Wind Helper
0.302
961421AF2-433 GEN
Solar/Wind Helper
0.302
957921AF2-086 GEN
Solar/Wind Helper
0.298
946691AF1-333 GEN
Solar/Wind Helper
0.297
946741AF1-338 GEN
Solar/Wind Helper
0.297
209067AE2-060 GEN
Solar/Wind Helper
0.051
238221AF1-254 C O1
Solar/Wind Helper
0.122
235067AD1-061 GEN
Solar/Wind Helper
0.214
972289AH1-729 GEN
50/50
14.564
315651AD1-115 GEN
Solar/Wind Harmer
4.557
316447AC1-158 HLD
Solar/Wind Harmer
2.184
3150071POSSM 5
Adder
38.76
3150181POSSMC2
Adder
0.855
3150181POSSMC2
Adder
0.848
3150181POSSMC2
Adder
0.848
966001AG1-469 GEN
Solar/Wind Harmer
0.179
3151731LOISA B
Adder
5.425
3151721LOISA A
Adder
5.397
3150391LDYSMT3
Adder
10.854
972195AH1-682 GEN
Adder
1.426
315673AE1-157 GEN
Solar/Wind Harmer
6.752
957411AF2-035 GEN
Solar/Wind Harmer
4.024
970317AG2-208 GEN
Solar/Wind Harmer
3.912
316468AD1-105 GEN
Solar/Wind Harmer
0.981
316077AC2-138 C
Solar/Wind Harmer
0.183
3150341NORNECKC1
Adder
0.809
3150341NORNECKC1
Adder
0.802
966871AG1-558 GEN
Solar/Wind Harmer
0.26
966871AG1-558 GEN
Solar/Wind Harmer
0.089
958261AF2-120 GEN
Solar/Wind Harmer
3.349
316487AF1-042 GEN
Solar/Wind Harmer
1.136
3142296MT RD221
Adder
0.244
971223AH1-071 GEN
Solar/Wind Harmer
1.075
3143526WINTERP
Solar/Wind Harmer
-0.044
3142366NRTHEST
Adder
0.249
3150691DARBY 3
Adder
5.491
3150701DARBY 4
Adder
5.478
3150681DARBY 2
Adder
5.471
3150671DARBY 1
Adder
5.465
316075AC2-137 C
Solar/Wind Harmer
0.231
316441AF1-014 GEN
Solar/Wind Harmer
0.577
3142946ENON
Solar/Wind Harmer
-0.001
944641AF1-129 GEN
Adder
35.924
316240AF1-291 C
Solar/Wind Harmer
0.255
316033AB2-134 GEN
Solar/Wind Harmer
2.716
315697AD1-025 GEN
Solar/Wind Harmer
1.703
316236AE1-162_GEN
Solar/Wind Harmer
0.252
970657AG2-426 GEN
Solar/Wind Harmer
2.604
970657AG2-426 GEN
Solar/Wind Harmer
0.544
316036AC1-147 C
Solar/Wind Harmer
0.225
3150991CHESPKB
Adder
0.776
3150991CHESPKB
Adder
0.757
316316AC1-027 C
Solar/Wind Harmer
0.255
3142956BIRDNECK
Solar/Wind Harmer
0.446
316185AD1-033 GEN
Solar/Wind Harmer
0.876
3145506HICKORY
Solar/Wind Harmer
-0.033
3145506HICKORY
Solar/Wind Harmer
-0.02
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.559
316018AA1-139 ULT2
Solar/Wind Harmer
0.71
316017AA1-139 ULT1
Solar/Wind Harmer
0.67
3137176SLIGO L2192
Solar/Wind Harmer
-0.033
3146456SLIGO L269
Solar/Wind Harmer
0.977
3130086AYDLETT
Solar/Wind Harmer
-0.033
3146386ELIZ CT
Solar/Wind Harmer
-0.008
971761AH1-387 GEN
Solar/Wind Harmer
4.579
316431W1029_GEN1
Solar/Wind Harmer
1.486
316433W1029_GEN2
Solar/Wind Harmer
1.486
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.008
3144356SAPONY
Solar/Wind Harmer
0.285
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
315742AE1-103 GEN
Solar/Wind Harmer
0.849
3146376EDENTON
Solar/Wind Harmer
0.24
3146376EDENTON
Solar/Wind Harmer
0.24
972185AH1-677 GEN
Adder
4.036
972187AH1-678 GEN
Adder
2.039
970933AG2-581 GEN
Solar/Wind Harmer
7.52
3146776BUCKING
Solar/Wind Harmer
-0.032
3146776BUCKING
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
3.958
3145893MURPHYS
Solar/Wind Harmer
0.22
3145893MURPHYS
Solar/Wind Harmer
-0.014
970301AG2-198 GEN
Solar/Wind Harmer
3.936
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
971741AH1-377 GEN
Solar/Wind Harmer
9.144
3144293JTRSVLE
Adder
0.22
3144293JTRSVLE
Adder
0.185
237025AB1-124 C
Solar/Wind Helper
0.168
237006AB1-125 GEN
Solar/Wind Helper
0.126
23777801MSM_W1-116
Solar/Wind Helper
0.11
205916AD1-020 GEN
Solar/Wind Helper
1.496
208835TUHI V3-051
Solar/Wind Helper
0.021
208835TUHI V3-051
Solar/Wind Helper
0.021
237034AC2-136 C
Solar/Wind Helper
0.157
233933AB2-153 GEN
Solar/Wind Helper
0.184
233944AB2-135 GEN
Solar/Wind Helper
0.465
232424Y1-079 C
Solar/Wind Helper
0.092
233987AB2-037 GEN
Solar/Wind Helper
1.847
233946AB2-136 GEN
Solar/Wind Helper
0.448
234036AF2-325 C
Solar/Wind Helper
0.033
233901CHERRYDALE C
Solar/Wind Helper
0.183
232408W1-005 C
Solar/Wind Helper
0.4
232410W1-006 C
Solar/Wind Helper
0.4
233939AC1-091 C
Solar/Wind Helper
0.275
233970AC1-092 C
Solar/Wind Helper
0.275
230433AD2-135 GEN
Solar/Wind Helper
0.013
230407AD2-065 C
Solar/Wind Helper
0.031
219921AF1-264
Solar/Wind Helper
0.039
219615MILLCREEK C
Solar/Wind Helper
0.02
963401AG1-189 GEN
Solar/Wind Helper
0.043
963391AG1-188 GEN
Solar/Wind Helper
0.062
20714928UPF_X1-085
Solar/Wind Helper
0.004
20720628TIN_W1-124
Solar/Wind Helper
0.143
20716928W4-060COL
Solar/Wind Helper
0.039
218440SUMMTASSOC C
Solar/Wind Helper
0.012
20673828FLE_V3-070
Solar/Wind Helper
0.068
207442AE1-156 GEN
Solar/Wind Helper
0.243
20676128MHD_W3-029
Solar/Wind Helper
0.072
20671828STAW2-080
Solar/Wind Helper
0.02
217081WEATEXAS C
Solar/Wind Helper
0.009
217202FBANKSOLAR C
Solar/Wind Helper
0.002
217201HACKENSOLA C
Solar/Wind Helper
0.002
217206BARNGR HS C
Solar/Wind Helper
0.005
217204WCALDSOLAR C
Solar/Wind Helper
0.002
226929AD2-058 GEN
Solar/Wind Helper
0.066
207471AF2-354 C
Solar/Wind Helper
0.124
20674928WA_W3-044
Solar/Wind Helper
0.072
20676228FRD_X1-012
Solar/Wind Helper
0.067
964851AG1-348 GEN
Solar/Wind Helper
0.059
20674128FR_U2-059
Solar/Wind Helper
0.003
966111AG1-480 GEN
Solar/Wind Helper
0.032
211065PSPA IPP
Solar/Wind Helper
0.109
211065PSPA IPP
Solar/Wind Helper
0.109
20390526W1-045 C
Solar/Wind Helper
0.226
208972BECR K09
Solar/Wind Helper
0.227
961431AF2-434 GEN
Solar/Wind Helper
0.302
209029WAYMART-WD
Solar/Wind Helper
0.566
209054AE2-059 GEN
Solar/Wind Helper
0.054
946751AF1-339 GEN
Solar/Wind Helper
0.297
209137AF2-361 C
Solar/Wind Helper
0.864
237001AB1-127_GEN
Solar/Wind Helper
0.221
237002AB1-128_GEN
Solar/Wind Helper
0.212
235063AE1-101 C2
Solar/Wind Helper
0.747
970099AG2-077 GEN
Solar/Wind Harmer
2.697
NYPJM->LTFIMP_NY
CLTF
3.269
LGEELTFEXP_LGEE->PJM
CLTF
2.098
LAGNLTFEXP_LAGN->PJM
CLTF
6.958
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.786
WECLTFEXP_WEC->PJM
CLTF
1.126
AG2-052LTFEXP_AG2-052->PJM
LTF
0.067
AH1-155LTFEXP_AH1-155->PJM
LTF
0.101
TVALTFEXP_TVA->PJM
CLTF
3.503
CPLELTFEXP_CPLE->PJM
CLTF
5.01
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.81
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.819
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.851
MECLTFEXP_MEC->PJM
CLTF
5.133
SIGELTFEXP_SIGE->PJM
CLTF
0.162

Details for 6TYLER-6CHESTF B 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6TYLER-6CHESTF B 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.46 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1209.55
MW Contribution:6.53
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
1.908
3151051BRUNSWICKS1
50/50
3.105
3151021BRUNSWICKG1
50/50
1.496
971451AH1-221 GEN
50/50
4.543
315671AE2-027_GEN
Solar/Wind Harmer
19.499
316023GEN1_S
Solar/Wind Harmer
0.988
960081AF2-299 GEN
Solar/Wind Harmer
1.464
970919AG2-571 GEN
Solar/Wind Harmer
3.863
970087AG2-069 GEN
Solar/Wind Harmer
11.386
971795AH1-408 GEN
Solar/Wind Harmer
9.103
3147043LAWRENC
Adder
0.945
316011AB1-132 GEN
Solar/Wind Harmer
2.416
962571AG1-106 GEN
Solar/Wind Harmer
1.66
3145796HORNRTN
Solar/Wind Harmer
-0.037
3145796HORNRTN
Solar/Wind Harmer
-0.011
957481AF2-042 GEN
Solar/Wind Harmer
33.627
3145783HORNRTN
Solar/Wind Harmer
-0.01
315722AD1-056 GEN
Solar/Wind Harmer
1.05
315693AD1-088 GEN
Solar/Wind Harmer
4.982
939411AE1-173 GEN
Solar/Wind Harmer
49.774
962491AG1-098 GEN
Solar/Wind Harmer
6.564
316190AA2-174 GEN
Solar/Wind Harmer
0.12
316129AC1-054 GEN
Solar/Wind Harmer
0.838
971065AG2-659 GEN
Solar/Wind Harmer
4.751
315687AD1-152 GEN
Solar/Wind Harmer
1.144
3146233WITAKRS
Solar/Wind Harmer
-0.036
316359AB2-059 GEN
Solar/Wind Harmer
1.219
316049AB1-081 GEN
Solar/Wind Harmer
0.975
3142053HEARTS
Solar/Wind Harmer
0.106
316212AC1-099_GEN
Solar/Wind Harmer
0.788
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.266
961671AG1-007 GEN
Solar/Wind Harmer
0.109
3146083TARBORO
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.257
3146263WOODLND
Solar/Wind Harmer
-0.009
970401AG2-262 GEN
Solar/Wind Harmer
0.554
3145823KELFORD
Solar/Wind Harmer
-0.008
316494AC1-189 GEN
Solar/Wind Harmer
0.891
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.232
316003AC1-222 GEN
Solar/Wind Harmer
0.762
3146293MARTNCO
Solar/Wind Harmer
0.047
970685AG2-442 GEN
Solar/Wind Harmer
6.462
316174AB2-169 GEN
Solar/Wind Harmer
1.1
3145963POPLR C
Solar/Wind Harmer
-0.007
963171AG1-166 GEN
Solar/Wind Harmer
0.871
971563AH1-280 GEN
Solar/Wind Harmer
0.871
3144293JTRSVLE
Adder
0.197
3146206CASHIE
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.713
316458AB2-190 GEN2
Solar/Wind Helper
0.849
3151031BRUNSWICKG2
50/50
1.496
315839AE2-212 C
Solar/Wind Harmer
2.248
965281AG1-393 GEN
Solar/Wind Harmer
3.641
316365GEN2_N
Solar/Wind Harmer
0.988
966621AG1-532 GEN
Solar/Wind Harmer
0.264
970917AG2-570 GEN
Solar/Wind Harmer
30.516
3147043LAWRENC
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.94
3145796HORNRTN
Solar/Wind Harmer
-0.045
3145796HORNRTN
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316478AD1-087 GEN
Solar/Wind Harmer
0.88
316486AD2-202 GEN
Solar/Wind Harmer
0.258
315724AD1-057 GEN
Solar/Wind Harmer
0.578
316327AA2-057 GEN
Solar/Wind Harmer
0.925
3146233WITAKRS
Solar/Wind Harmer
0.19
315779AE2-040
50/50
2.552
315244AE2-183_ST
50/50
3.298
963041AG1-153 GEN
50/50
3.029
316315AB2-025 C
Solar/Wind Harmer
0.554
315814AE2-033 C
Solar/Wind Harmer
18.846
941031AE2-094 GEN
Solar/Wind Harmer
25.237
944011AF1-069 GEN
Solar/Wind Harmer
7.908
970673AG2-436 GEN
Solar/Wind Harmer
27.602
970673AG2-436 GEN
Solar/Wind Harmer
13.976
946281AF1-292 GEN
Solar/Wind Harmer
0.291
971967AH1-528 GEN
Solar/Wind Harmer
24.041
970085AG2-068 GEN
Solar/Wind Harmer
7.59
970581AG2-369 GEN
Solar/Wind Harmer
6.528
316087AB2-174 GEN
Solar/Wind Harmer
1.725
315652AC1-086 GEN
Solar/Wind Harmer
12.993
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145796HORNRTN
Solar/Wind Harmer
-0.004
3137643SOCKMAN
Solar/Wind Harmer
-0.043
970831AG2-522 GEN
Solar/Wind Harmer
4.811
315607AA1-063A GEN
Solar/Wind Harmer
0.934
316319Z2-044 C
Solar/Wind Harmer
0.502
3146043SEABORD
Solar/Wind Harmer
-0.009
316239AB2-077_GEN
Solar/Wind Harmer
0.266
316238AB2-078_GEN
Solar/Wind Harmer
0.266
3146033SCOT NK
Solar/Wind Harmer
-0.035
3145573BETHELC
Solar/Wind Harmer
-0.009
3145573BETHELC
Solar/Wind Harmer
-0.009
316420AA1-050 GEN
Solar/Wind Harmer
0.969
316118AC1-105 GEN
Solar/Wind Harmer
0.576
957861AF2-080 GEN
Solar/Wind Harmer
3.624
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.069
961941AG1-037 GEN
Solar/Wind Harmer
0.06
3145513AHOSKIE
Solar/Wind Harmer
-0.008
971443AH1-215 GEN
Solar/Wind Harmer
1.548
316005AA1-067
Solar/Wind Harmer
0.159
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
970181AG2-120 GEN
Solar/Wind Harmer
1.032
316318V4-068
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3144303KENBRDG
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
0.689
970683AG2-441 GEN
Solar/Wind Harmer
5.769
970681AG2-440 GEN
Solar/Wind Harmer
4.615
970865AG2-541 GEN
Solar/Wind Harmer
2.838
946301AF1-294 GEN
Solar/Wind Harmer
1.786
961791AG1-021 GEN
Solar/Wind Harmer
0.871
3146206CASHIE
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
2.997
315657AE1-056 GEN
Solar/Wind Harmer
2.505
270455AD2-022 GEN
Solar/Wind Harmer
1.161
270457AD2-023 GEN
Solar/Wind Harmer
0.589
3143316POE
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
1.284
315733AD1-074 GEN2
Solar/Wind Harmer
1.284
315735AD1-075 GEN1
Solar/Wind Harmer
0.642
316132AB2-190 GEN1
Solar/Wind Helper
0.849
3142543TWELFTH
Solar/Wind Helper
0.011
3146233WITAKRS
Solar/Wind Harmer
-0.006
961601AG1-000A GEN
Solar/Wind Harmer
3.618
3138543CONSLDL
Solar/Wind Harmer
-0.006
316210AC1-098 GEN
Solar/Wind Harmer
1.418
3145543BTLEBRO
Solar/Wind Harmer
-0.009
3145543BTLEBRO
Solar/Wind Harmer
-0.009
316131AB2-060 GEN
Solar/Wind Harmer
0.944
3146073TAR RVR
Solar/Wind Harmer
-0.009
3146083TARBORO
Solar/Wind Harmer
-0.009
3146263WOODLND
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
6.613
316317KELFORD C
Solar/Wind Harmer
0.394
3145823KELFORD
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.249
960061AF2-297 GEN
Solar/Wind Harmer
4.13
315785AD2-033 C
Solar/Wind Harmer
1.813
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
0.994
3146173TUNIS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
3145746EVERETS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.185
961681AG1-008 GEN
Solar/Wind Harmer
6.185
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
970257AG2-171 GEN
Solar/Wind Harmer
2.935
959311AF2-222 GEN
Solar/Wind Harmer
8.036
316283AC2-100 C
Solar/Wind Harmer
0.716
3145933PARMELE
Solar/Wind Harmer
-0.008
966801AG1-551 GEN
Solar/Wind Harmer
0.948
3156081AA2-088 GEN
Solar/Wind Harmer
2.463
3156021HOLLOMANSOL
Solar/Wind Harmer
1.02
971683AH1-343 GEN
Solar/Wind Harmer
3.191
970909AG2-566 GEN
Solar/Wind Harmer
0.671
3145963POPLR C
Solar/Wind Harmer
-0.007
963181AG1-167 GEN
Solar/Wind Harmer
0.653
3144293JTRSVLE
Adder
0.197
3146206CASHIE
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.021
971193AH1-056 GEN
Solar/Wind Harmer
4.174
315737AD1-076 GEN
Solar/Wind Harmer
1.206
316473AC1-191 GEN
Solar/Wind Helper
0.683
970533AG2-339 GEN
50/50
10.649
970531AG2-338 GEN
50/50
4.259
315242AE2-183_GT2
50/50
1.908
315241AE2-183_GT1
50/50
1.896
972185AH1-677 GEN
50/50
6.877
3151041BRUNSWICKG3
50/50
1.496
972187AH1-678 GEN
50/50
3.433
3144356SAPONY
Solar/Wind Harmer
0.717
970933AG2-581 GEN
Solar/Wind Harmer
11.443
316181AB2-040 GEN
Solar/Wind Harmer
1.631
3145796HORNRTN
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
970099AG2-077 GEN
Solar/Wind Harmer
13.451
3145593CAROLNA
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.01
966811AG1-552 GEN
Solar/Wind Harmer
1.148
3145593CAROLNA
Solar/Wind Harmer
0.085
3145783HORNRTN
Solar/Wind Harmer
1.195
3145783HORNRTN
Solar/Wind Harmer
0.956
3145783HORNRTN
Solar/Wind Harmer
0.299
3145783HORNRTN
Solar/Wind Harmer
0.12
316426AA2-053 GEN
Solar/Wind Harmer
0.991
316274AC1-208 GEN
Solar/Wind Harmer
1.01
939181AE1-148 GEN
Solar/Wind Harmer
5.143
961601AG1-000A GEN
Solar/Wind Harmer
3.573
316263AC1-034 GEN
Solar/Wind Harmer
4.237
313527AB2-043 GEN
Solar/Wind Harmer
1.432
3145493TOT1
Solar/Wind Harmer
0.134
3145453TOT5
Solar/Wind Harmer
0.08
3145603CNETO
Solar/Wind Harmer
0.054
962561AG1-105 GEN
Solar/Wind Harmer
4.805
964791AG1-342 GEN
Solar/Wind Harmer
1.814
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
3145893MURPHYS
Solar/Wind Harmer
0.218
3145893MURPHYS
Solar/Wind Harmer
-0.014
970323AG2-213 GEN
Solar/Wind Harmer
3.913
971775AH1-396 GEN
Solar/Wind Harmer
0.557
316034AC1-036 C
Solar/Wind Harmer
0.145
971741AH1-377 GEN
Solar/Wind Harmer
8.992
316222AC1-221 GEN
Solar/Wind Harmer
0.773
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.008
970301AG2-198 GEN
Solar/Wind Harmer
3.536
958211AF2-115 GEN
Solar/Wind Harmer
1.089
963191AG1-168 GEN
Solar/Wind Harmer
0.653
3144293JTRSVLE
Adder
0.197
3144293JTRSVLE
Adder
0.166
3147133PAMPLIN
Solar/Wind Harmer
-0.007
3147133PAMPLIN
Solar/Wind Harmer
-0.005
316065AD1-022 GEN
Solar/Wind Harmer
3.333
316240AF1-291 C
Solar/Wind Helper
0.486
966871AG1-558 GEN
Solar/Wind Helper
0.151
NYPJM->LTFIMP_NY
CLTF
0.626
LAGNLTFEXP_LAGN->PJM
CLTF
3.517
LGEELTFEXP_LGEE->PJM
CLTF
0.616
WECLTFEXP_WEC->PJM
CLTF
0.321
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.061
TVALTFEXP_TVA->PJM
CLTF
1.752
CPLELTFEXP_CPLE->PJM
CLTF
5.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.55
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.341
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.001
MECLTFEXP_MEC->PJM
CLTF
1.715
SIGELTFEXP_SIGE->PJM
CLTF
0.051

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.06 %
Rating:1039.5 MVA
Rating Type:C
MVA to Mitigate:1092.07
MW Contribution:7.55
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
3.947
963041AG1-153 GEN
50/50
3.597
941031AE2-094 GEN
Solar/Wind Harmer
30.716
944011AF1-069 GEN
Solar/Wind Harmer
9.624
970673AG2-436 GEN
Solar/Wind Harmer
33.229
970673AG2-436 GEN
Solar/Wind Harmer
16.825
971967AH1-528 GEN
Solar/Wind Harmer
28.628
970085AG2-068 GEN
Solar/Wind Harmer
8.78
970581AG2-369 GEN
Solar/Wind Harmer
7.55
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.004
316118AC1-105 GEN
Solar/Wind Harmer
0.435
316315AB2-025 C
Solar/Wind Helper
0.644
3143316POE
Solar/Wind Helper
1.545
946281AF1-292 GEN
Solar/Wind Helper
0.143
316132AB2-190 GEN1
Solar/Wind Helper
0.692
316087AB2-174 GEN
Solar/Wind Helper
0.788
315243AE2-183_GT3
50/50
2.283
3151051BRUNSWICKS1
50/50
3.687
3151021BRUNSWICKG1
50/50
1.776
971451AH1-221 GEN
50/50
5.395
970919AG2-571 GEN
Solar/Wind Harmer
4.48
970087AG2-069 GEN
Solar/Wind Harmer
13.169
939411AE1-173 GEN
Solar/Wind Harmer
59.872
957481AF2-042 GEN
Solar/Wind Harmer
36.689
315693AD1-088 GEN
Solar/Wind Harmer
5.287
962491AG1-098 GEN
Solar/Wind Harmer
6.96
315687AD1-152 GEN
Solar/Wind Harmer
1.13
316003AC1-222 GEN
Solar/Wind Harmer
0.631
316023GEN1_S
Solar/Wind Helper
0.815
316381AD1-082 GEN
Solar/Wind Helper
0.932
3142543TWELFTH
Solar/Wind Helper
0.014
316458AB2-190 GEN2
Solar/Wind Helper
0.692
3151031BRUNSWICKG2
50/50
1.776
970917AG2-570 GEN
Solar/Wind Harmer
35.395
316478AD1-087 GEN
Solar/Wind Harmer
0.919
316486AD2-202 GEN
Solar/Wind Harmer
0.269
970909AG2-566 GEN
Solar/Wind Harmer
0.698
316248AF1-058 C
Solar/Wind Harmer
0.206
960061AF2-297 GEN
Solar/Wind Harmer
3.421
315839AE2-212 C
Solar/Wind Helper
0.418
316365GEN2_N
Solar/Wind Helper
0.815
966621AG1-532 GEN
Solar/Wind Helper
0.13
970533AG2-339 GEN
50/50
12.961
970531AG2-338 GEN
50/50
5.184
315242AE2-183_GT2
50/50
2.283
315241AE2-183_GT1
50/50
2.269
972185AH1-677 GEN
50/50
8.231
3151041BRUNSWICKG3
50/50
1.776
972187AH1-678 GEN
50/50
4.076
970933AG2-581 GEN
Solar/Wind Harmer
13.348
970099AG2-077 GEN
Solar/Wind Harmer
14.675
971741AH1-377 GEN
Solar/Wind Harmer
9.409
970301AG2-198 GEN
Solar/Wind Harmer
3.678
3144356SAPONY
Solar/Wind Helper
0.758
316240AF1-291 C
Solar/Wind Helper
0.337
NYPJM->LTFIMP_NY
CLTF
0.461
LAGNLTFEXP_LAGN->PJM
CLTF
2.783
LGEELTFEXP_LGEE->PJM
CLTF
0.504
WECLTFEXP_WEC->PJM
CLTF
0.263
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.387
TVALTFEXP_TVA->PJM
CLTF
1.388
CPLELTFEXP_CPLE->PJM
CLTF
3.694
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.813
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.35
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.768
MECLTFEXP_MEC->PJM
CLTF
1.39
SIGELTFEXP_SIGE->PJM
CLTF
0.042

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.06 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1585.79
MW Contribution:9.7
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
16.763
970531AG2-338 GEN
50/50
6.705
315242AE2-183_GT2
50/50
2.946
315241AE2-183_GT1
50/50
2.928
972185AH1-677 GEN
50/50
10.62
3151041BRUNSWICKG3
50/50
2.289
972187AH1-678 GEN
50/50
5.253
970933AG2-581 GEN
Solar/Wind Harmer
17.132
970099AG2-077 GEN
Solar/Wind Harmer
18.596
971741AH1-377 GEN
Solar/Wind Harmer
11.67
970301AG2-198 GEN
Solar/Wind Harmer
4.534
316185AD1-033 GEN
Solar/Wind Harmer
0.819
3145506HICKORY
Solar/Wind Harmer
-0.03
3145506HICKORY
Solar/Wind Harmer
-0.018
3145506HICKORY
Solar/Wind Harmer
-0.005
3142956BIRDNECK
Solar/Wind Harmer
0.405
316316AC1-027 C
Solar/Wind Harmer
0.23
316222AC1-221 GEN
Solar/Wind Harmer
0.758
316339AD2-160 GEN
Solar/Wind Harmer
0.496
316036AC1-147 C
Solar/Wind Harmer
0.197
3150991CHESPKB
Adder
0.682
3150991CHESPKB
Adder
0.665
316018AA1-139 ULT2
Solar/Wind Harmer
0.624
316017AA1-139 ULT1
Solar/Wind Harmer
0.589
3137176SLIGO L2192
Solar/Wind Harmer
-0.028
3146456SLIGO L269
Solar/Wind Harmer
0.843
3130086AYDLETT
Solar/Wind Harmer
-0.028
3146843MT LREL
Solar/Wind Harmer
-0.007
3146843MT LREL
Solar/Wind Harmer
-0.007
964791AG1-342 GEN
Solar/Wind Harmer
1.391
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3144356SAPONY
Solar/Wind Helper
1.384
316240AF1-291 C
Solar/Wind Helper
0.58
316181AB2-040 GEN
Solar/Wind Helper
1.463
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3142666NORTHAMPTON
Solar/Wind Helper
0.112
3145796HORNRTN
Solar/Wind Helper
0.562
3142946ENON
Solar/Wind Helper
0.015
966871AG1-558 GEN
Solar/Wind Helper
0.195
3143526WINTERP
Solar/Wind Helper
0.702
316468AD1-105 GEN
Solar/Wind Helper
0.616
316033AB2-134 GEN
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
1.353
3145593CAROLNA
Solar/Wind Helper
0.116
3145593CAROLNA
Solar/Wind Helper
0.116
315244AE2-183_ST
50/50
5.093
963041AG1-153 GEN
50/50
4.635
3151541CLOVER2
50/50
2.532
941031AE2-094 GEN
Solar/Wind Harmer
39.728
944011AF1-069 GEN
Solar/Wind Harmer
12.448
970673AG2-436 GEN
Solar/Wind Harmer
42.909
970673AG2-436 GEN
Solar/Wind Harmer
21.726
971967AH1-528 GEN
Solar/Wind Harmer
36.888
970085AG2-068 GEN
Solar/Wind Harmer
11.275
970581AG2-369 GEN
Solar/Wind Harmer
9.696
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
3151081ELIZAR1
Adder
6.136
3151091ELIZAR2
Adder
6.029
316118AC1-105 GEN
Solar/Wind Harmer
0.506
3152611GOSPORTB
Adder
0.827
3152621GOSPORTC
Adder
0.702
3152601GOSPORTA
Adder
0.647
957871AF2-081 GEN
Solar/Wind Harmer
3.642
319010AE1-072 C
Solar/Wind Harmer
1.431
3146406KITTY HAWK
Solar/Wind Harmer
0.006
970865AG2-541 GEN
Solar/Wind Harmer
2.808
313526AB2-022
Solar/Wind Harmer
0.171
316315AB2-025 C
Solar/Wind Helper
1.176
3143316POE
Solar/Wind Helper
2.759
946281AF1-292 GEN
Solar/Wind Helper
0.283
316087AB2-174 GEN
Solar/Wind Helper
1.592
3145796HORNRTN
Solar/Wind Helper
0.6
3145796HORNRTN
Solar/Wind Helper
0.075
316132AB2-190 GEN1
Solar/Wind Helper
1.032
3137643SOCKMAN
Solar/Wind Helper
0.624
316233AE1-074 FULL
Solar/Wind Helper
0.206
316369SG1_INVT
Solar/Wind Helper
0.569
316312AB1-027
Solar/Wind Helper
0.221
3151031BRUNSWICKG2
50/50
2.289
970413AG2-270 GEN
50/50
11.103
970917AG2-570 GEN
Solar/Wind Harmer
45.471
316478AD1-087 GEN
Solar/Wind Harmer
1.154
316486AD2-202 GEN
Solar/Wind Harmer
0.338
315773AC2-141 GEN
Solar/Wind Harmer
4.566
970909AG2-566 GEN
Solar/Wind Harmer
0.861
944581AF1-123 GEN
Solar/Wind Harmer
39.916
944601AF1-125 GEN
Solar/Wind Harmer
39.293
316248AF1-058 C
Solar/Wind Harmer
0.247
960061AF2-297 GEN
Solar/Wind Harmer
4.091
3151101ELIZAR3
Adder
6.215
316283AC2-100 C
Solar/Wind Harmer
0.699
971683AH1-343 GEN
Solar/Wind Harmer
3.159
3144873MCLAUGH
Solar/Wind Harmer
0
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.87
316320Y1-086
Solar/Wind Harmer
0.371
315839AE2-212 C
Solar/Wind Helper
0.734
316365GEN2_N
Solar/Wind Helper
1.533
966621AG1-532 GEN
Solar/Wind Helper
0.257
313506AB2-031 GEN
Solar/Wind Helper
0.926
3142666NORTHAMPTON
Solar/Wind Helper
0.188
3145796HORNRTN
Solar/Wind Helper
0.75
3145796HORNRTN
Solar/Wind Helper
0.187
3147043LAWRENC
Solar/Wind Helper
0.104
3142946ENON
Solar/Wind Helper
0.049
316473AC1-191 GEN
Solar/Wind Helper
0.882
315243AE2-183_GT3
50/50
2.946
3151051BRUNSWICKS1
50/50
4.751
3151021BRUNSWICKG1
50/50
2.289
971451AH1-221 GEN
50/50
6.952
3151531CLOVER1
50/50
2.544
940641AE2-051 GEN
Solar/Wind Harmer
19.26
970919AG2-571 GEN
Solar/Wind Harmer
5.756
970087AG2-069 GEN
Solar/Wind Harmer
16.912
939411AE1-173 GEN
Solar/Wind Harmer
86.789
957481AF2-042 GEN
Solar/Wind Harmer
46.49
315693AD1-088 GEN
Solar/Wind Harmer
6.649
962491AG1-098 GEN
Solar/Wind Harmer
8.746
315687AD1-152 GEN
Solar/Wind Harmer
1.407
316294AC1-161 GEN
Solar/Wind Harmer
3.53
944591AF1-124 GEN
Solar/Wind Harmer
40.06
316003AC1-222 GEN
Solar/Wind Harmer
0.754
316388AE2-253 GEN
Solar/Wind Harmer
0.496
316375AC2-012 GEN
Solar/Wind Harmer
2.531
3150981CHESPKA
Adder
0.813
3146456SLIGO L269
Solar/Wind Harmer
-0.007
970401AG2-262 GEN
Solar/Wind Harmer
0.425
316023GEN1_S
Solar/Wind Helper
1.533
316381AD1-082 GEN
Solar/Wind Helper
1.562
3142543TWELFTH
Solar/Wind Helper
0.023
316011AB1-132 GEN
Solar/Wind Helper
2.299
3145796HORNRTN
Solar/Wind Helper
0.619
3145796HORNRTN
Solar/Wind Helper
0.187
316458AB2-190 GEN2
Solar/Wind Helper
1.032
3143526WINTERP
Solar/Wind Helper
0.702
3142433PROV 92
Solar/Wind Helper
0.503
3143226MDLTHAN
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.302
3142416OLDCHRC
Solar/Wind Helper
0.116
NYPJM->LTFIMP_NY
CLTF
0.573
LAGNLTFEXP_LAGN->PJM
CLTF
3.312
LGEELTFEXP_LGEE->PJM
CLTF
0.594
WECLTFEXP_WEC->PJM
CLTF
0.31
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.993
TVALTFEXP_TVA->PJM
CLTF
1.652
CPLELTFEXP_CPLE->PJM
CLTF
4.36
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.578
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.972
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.67
MECLTFEXP_MEC->PJM
CLTF
1.642
SIGELTFEXP_SIGE->PJM
CLTF
0.049

Details for 8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-6CARSON 500.0/230.0 kV Ckt 2 transformer
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.2 %
Rating:1056.8 MVA
Rating Type:C
MVA to Mitigate:1175.18
MW Contribution:8.09
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
4.228
963041AG1-153 GEN
50/50
3.852
941031AE2-094 GEN
Solar/Wind Harmer
32.902
944011AF1-069 GEN
Solar/Wind Harmer
10.309
970673AG2-436 GEN
Solar/Wind Harmer
35.593
970673AG2-436 GEN
Solar/Wind Harmer
18.022
970533AG2-339 GEN
50/50
13.883
970531AG2-338 GEN
50/50
5.553
315242AE2-183_GT2
50/50
2.446
315241AE2-183_GT1
50/50
2.431
972185AH1-677 GEN
50/50
8.817
3151041BRUNSWICKG3
50/50
1.903
972187AH1-678 GEN
50/50
4.366
970933AG2-581 GEN
Solar/Wind Harmer
14.297
970099AG2-077 GEN
Solar/Wind Harmer
15.72
971741AH1-377 GEN
Solar/Wind Harmer
10.078
970301AG2-198 GEN
Solar/Wind Harmer
3.939
316222AC1-221 GEN
Solar/Wind Harmer
0.674
3144356SAPONY
Solar/Wind Helper
0.812
316240AF1-291 C
Solar/Wind Helper
0.361
3151031BRUNSWICKG2
50/50
1.903
970917AG2-570 GEN
Solar/Wind Harmer
37.913
316478AD1-087 GEN
Solar/Wind Harmer
0.984
316486AD2-202 GEN
Solar/Wind Harmer
0.288
970909AG2-566 GEN
Solar/Wind Harmer
0.748
316248AF1-058 C
Solar/Wind Harmer
0.221
960061AF2-297 GEN
Solar/Wind Harmer
3.664
316283AC2-100 C
Solar/Wind Harmer
0.622
971683AH1-343 GEN
Solar/Wind Harmer
2.83
315839AE2-212 C
Solar/Wind Helper
0.448
316365GEN2_N
Solar/Wind Helper
0.873
966621AG1-532 GEN
Solar/Wind Helper
0.139
971967AH1-528 GEN
Solar/Wind Harmer
30.665
970085AG2-068 GEN
Solar/Wind Harmer
9.404
970581AG2-369 GEN
Solar/Wind Harmer
8.088
3147173SINAI
Solar/Wind Harmer
-0.007
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.466
316315AB2-025 C
Solar/Wind Helper
0.69
3143316POE
Solar/Wind Helper
1.655
946281AF1-292 GEN
Solar/Wind Helper
0.154
316132AB2-190 GEN1
Solar/Wind Helper
0.741
316087AB2-174 GEN
Solar/Wind Helper
0.844
315243AE2-183_GT3
50/50
2.446
3151051BRUNSWICKS1
50/50
3.949
3151021BRUNSWICKG1
50/50
1.903
971451AH1-221 GEN
50/50
5.779
970919AG2-571 GEN
Solar/Wind Harmer
4.799
970087AG2-069 GEN
Solar/Wind Harmer
14.106
939411AE1-173 GEN
Solar/Wind Harmer
64.131
957481AF2-042 GEN
Solar/Wind Harmer
39.299
315693AD1-088 GEN
Solar/Wind Harmer
5.663
962491AG1-098 GEN
Solar/Wind Harmer
7.455
315687AD1-152 GEN
Solar/Wind Harmer
1.21
316003AC1-222 GEN
Solar/Wind Harmer
0.675
316023GEN1_S
Solar/Wind Helper
0.873
316381AD1-082 GEN
Solar/Wind Helper
0.998
3142543TWELFTH
Solar/Wind Helper
0.015
316458AB2-190 GEN2
Solar/Wind Helper
0.741
316011AB1-132 GEN
Solar/Wind Helper
1.246
NYPJM->LTFIMP_NY
CLTF
0.494
LAGNLTFEXP_LAGN->PJM
CLTF
2.98
LGEELTFEXP_LGEE->PJM
CLTF
0.54
WECLTFEXP_WEC->PJM
CLTF
0.282
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.983
TVALTFEXP_TVA->PJM
CLTF
1.486
CPLELTFEXP_CPLE->PJM
CLTF
3.956
CBM West 2LTFEXP_CBM-W2->PJM
CBM
15.867
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.015
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.108
MECLTFEXP_MEC->PJM
CLTF
1.489
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4497.83
MW Contribution:15.06
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.54
970413AG2-270 GEN
50/50
25.77
3151101ELIZAR3
50/50
26.77
970917AG2-570 GEN
Solar/Wind Harmer
29.34
315773AC2-141 GEN
Solar/Wind Harmer
10.33
944581AF1-123 GEN
Solar/Wind Harmer
62.596
944601AF1-125 GEN
Solar/Wind Harmer
61.631
316478AD1-087 GEN
Solar/Wind Harmer
0.962
316486AD2-202 GEN
Solar/Wind Harmer
0.283
3146456SLIGO L269
Solar/Wind Harmer
0.272
971153AH1-033 GEN
Solar/Wind Harmer
3.148
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
316365GEN2_N
Solar/Wind Harmer
0.594
3146376EDENTON
Solar/Wind Harmer
0.263
3144536CHRHLND
Solar/Wind Harmer
0.039
3145273HOLLAND
Solar/Wind Harmer
0.197
315244AE2-183_ST
50/50
10.008
963041AG1-153 GEN
50/50
9.194
315779AE2-040
50/50
3.994
3151541CLOVER2
50/50
5.877
3151081ELIZAR1
50/50
26.432
941031AE2-094 GEN
Solar/Wind Harmer
66.901
944011AF1-069 GEN
Solar/Wind Harmer
21.859
970673AG2-436 GEN
Solar/Wind Harmer
75.678
970673AG2-436 GEN
Solar/Wind Harmer
50.452
971967AH1-528 GEN
Solar/Wind Harmer
55.275
970085AG2-068 GEN
Solar/Wind Harmer
17.517
970581AG2-369 GEN
Solar/Wind Harmer
15.064
316315AB2-025 C
Solar/Wind Harmer
0.231
315814AE2-033 C
Solar/Wind Harmer
22.552
957871AF2-081 GEN
Solar/Wind Harmer
13.58
319010AE1-072 C
Solar/Wind Harmer
1.371
3146406KITTY HAWK
Solar/Wind Harmer
0.034
3151091ELIZAR2
Adder
24.477
3152611GOSPORTB
Adder
3.448
3152621GOSPORTC
Adder
2.926
3152601GOSPORTA
Adder
2.699
313526AB2-022
Solar/Wind Harmer
0.146
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.05
3146396TANGLEW
Solar/Wind Harmer
0.743
3145176PASQUOTANK
Solar/Wind Harmer
0.167
3146486SUNBURY
Solar/Wind Harmer
0.269
3146486SUNBURY
Solar/Wind Harmer
0.269
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
1.82
3130156CHOWAN
Solar/Wind Harmer
0.263
3130156CHOWAN
Solar/Wind Harmer
0.263
315816AE2-034 GEN
Solar/Wind Harmer
1.116
3130546PLYMOUTH
Solar/Wind Harmer
0.257
315732AD1-074 GEN1
Solar/Wind Harmer
1.477
315733AD1-074 GEN2
Solar/Wind Harmer
1.477
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
965291AG1-394 GEN
Solar/Wind Harmer
1.138
3146206CASHIE
Solar/Wind Harmer
0.256
970601AG2-382 GEN
Solar/Wind Harmer
9.549
316311AC2-079 GEN
Solar/Wind Harmer
7.334
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.175
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145893MURPHYS
Solar/Wind Harmer
0.688
3145893MURPHYS
Solar/Wind Harmer
0.255
315652AC1-086 GEN
Solar/Wind Harmer
27.966
3145513AHOSKIE
Solar/Wind Harmer
0.53
3145513AHOSKIE
Solar/Wind Harmer
0.253
3146043SEABORD
Solar/Wind Harmer
0.253
315607AA1-063A GEN
Solar/Wind Harmer
0.517
3145683EARLEYS
Solar/Wind Harmer
0.506
3145683EARLEYS
Solar/Wind Harmer
0.253
3145683EARLEYS
Solar/Wind Harmer
0.253
3137643SOCKMAN
Solar/Wind Harmer
1.009
3145796HORNRTN
Solar/Wind Harmer
0.804
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
0.989
970831AG2-522 GEN
Solar/Wind Harmer
10.446
3143316POE
Solar/Wind Harmer
0.965
971445AH1-216 GEN
Solar/Wind Harmer
17.029
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.955
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
970181AG2-120 GEN
Solar/Wind Harmer
2.987
957861AF2-080 GEN
Solar/Wind Harmer
10.262
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
972265AH1-717 GEN
Adder
17.569
3151201GRAVEL4
Adder
16.47
3151191GRAVEL3
Adder
16.261
3151211GRAVEL5
Adder
16.261
316118AC1-105 GEN
Solar/Wind Harmer
0.578
3147173SINAI
Solar/Wind Harmer
0.223
3147243WELCO
Solar/Wind Harmer
0.14
971443AH1-215 GEN
Solar/Wind Harmer
3.472
3144303KENBRDG
Solar/Wind Harmer
0.165
316369SG1_INVT
Solar/Wind Harmer
0.007
970683AG2-441 GEN
Solar/Wind Harmer
13.122
970681AG2-440 GEN
Solar/Wind Harmer
10.498
970865AG2-541 GEN
Solar/Wind Harmer
6.671
946301AF1-294 GEN
Solar/Wind Harmer
3.715
961791AG1-021 GEN
Solar/Wind Harmer
1.807
3138283WHITEMARSH
Solar/Wind Harmer
0.044
316132AB2-190 GEN1
Solar/Wind Harmer
0.989
315657AE1-056 GEN
Solar/Wind Harmer
6.288
316123AC1-075 GEN
Solar/Wind Harmer
0.235
970165AG2-112 GEN
Solar/Wind Harmer
1.394
970163AG2-111 GEN
Solar/Wind Harmer
1.33
3141873WAN 176
Solar/Wind Harmer
0.031
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970189AG2-124 GEN
Solar/Wind Harmer
4.431
316059AD1-063 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.147
316314AB2-024 C
Solar/Wind Harmer
0.001
3138133OCRAN
Solar/Wind Harmer
0.044
3143873LANEXA
Solar/Wind Harmer
0.086
3141783LANCAST
Solar/Wind Harmer
0.085
3141783LANCAST
Solar/Wind Harmer
0.057
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
315243AE2-183_GT3
50/50
5.789
3151051BRUNSWICKS1
50/50
9.423
3151021BRUNSWICKG1
50/50
4.54
971451AH1-221 GEN
50/50
13.79
3151531CLOVER1
50/50
5.905
940641AE2-051 GEN
Solar/Wind Harmer
28.987
939411AE1-173 GEN
Solar/Wind Harmer
145.254
970919AG2-571 GEN
Solar/Wind Harmer
11.736
970087AG2-069 GEN
Solar/Wind Harmer
26.275
957481AF2-042 GEN
Solar/Wind Harmer
77.806
316294AC1-161 GEN
Solar/Wind Harmer
4.901
944591AF1-124 GEN
Solar/Wind Harmer
62.818
316388AE2-253 GEN
Solar/Wind Harmer
0.855
3146456SLIGO L269
Solar/Wind Harmer
0.272
315693AD1-088 GEN
Solar/Wind Harmer
13.02
316375AC2-012 GEN
Solar/Wind Harmer
0.007
3150981CHESPKA
Adder
3.38
316246AF1-032 C
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
0.867
3146516WINFALL
Solar/Wind Harmer
0.268
962491AG1-098 GEN
Solar/Wind Harmer
15.268
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.461
316023GEN1_S
Solar/Wind Harmer
0.594
3130156CHOWAN
Solar/Wind Harmer
0.263
3145663CRESWEL
Solar/Wind Harmer
0.728
971163AH1-040 GEN
Solar/Wind Harmer
20.811
316072AD1-144
Solar/Wind Harmer
0.094
315687AD1-152 GEN
Solar/Wind Harmer
0.008
960081AF2-299 GEN
Solar/Wind Harmer
2.469
3146206CASHIE
Solar/Wind Harmer
0.256
971547AH1-271 GEN
Solar/Wind Harmer
5.457
3145893MURPHYS
Solar/Wind Harmer
1.02
315614AA2-178 GEN
Solar/Wind Harmer
1.489
971157AH1-035 GEN
Solar/Wind Harmer
3.091
315737AD1-076 GEN
Solar/Wind Harmer
3.308
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.256
3145893MURPHYS
Solar/Wind Harmer
0.427
3145893MURPHYS
Solar/Wind Harmer
0.255
957521AF2-046 GEN
Solar/Wind Harmer
18.955
961681AG1-008 GEN
Solar/Wind Harmer
18.955
313506AB2-031 GEN
Solar/Wind Harmer
0.786
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
3156021HOLLOMANSOL
Solar/Wind Harmer
1.153
316463AE2-346 GEN
Solar/Wind Harmer
0.218
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
2.704
3146263WOODLND
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
1.005
3145796HORNRTN
Solar/Wind Harmer
0.251
316317KELFORD C
Solar/Wind Harmer
0.024
3145823KELFORD
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
3147043LAWRENC
Solar/Wind Harmer
0.149
316210AC1-098 GEN
Solar/Wind Harmer
2.273
970661AG2-428 GEN
Solar/Wind Harmer
5.16
3145336SMITFLD
Solar/Wind Harmer
0.097
3145933PARMELE
Solar/Wind Harmer
0.243
966801AG1-551 GEN
Solar/Wind Harmer
2.83
315724AD1-057 GEN
Solar/Wind Harmer
0.908
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316327AA2-057 GEN
Solar/Wind Harmer
0.362
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.515
3146233WITAKRS
Solar/Wind Harmer
1.189
3146233WITAKRS
Solar/Wind Harmer
0.161
3138543CONSLDL
Solar/Wind Harmer
0.156
3146073TAR RVR
Solar/Wind Harmer
0.236
3146083TARBORO
Solar/Wind Harmer
0.236
961601AG1-000A GEN
Solar/Wind Harmer
16.657
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.234
971623AH1-311 GEN
Solar/Wind Harmer
0.468
315813AE1-149 C
Solar/Wind Harmer
12.227
3151221GRAVEL6
Adder
16.451
3151171GRAVELC
Adder
3.165
316131AB2-060 GEN
Solar/Wind Harmer
0.707
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.527
3144216WINCHST
Adder
0.83
964241AG1-285 GEN
Solar/Wind Harmer
14.603
3150921YORKTN3
Adder
5.498
961611AG1-000B GEN
Solar/Wind Harmer
5.762
315785AD2-033 C
Solar/Wind Harmer
1.703
316283AC2-100 C
Solar/Wind Harmer
0.406
970257AG2-171 GEN
Solar/Wind Harmer
6.589
959311AF2-222 GEN
Solar/Wind Harmer
18.071
971683AH1-343 GEN
Solar/Wind Harmer
7.451
315839AE2-212 C
Solar/Wind Harmer
0.002
970909AG2-566 GEN
Solar/Wind Harmer
2.128
315778AD1-151 GEN
Solar/Wind Harmer
15.484
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.04
963181AG1-167 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
970129AG2-093 GEN
Solar/Wind Harmer
11.049
3147133PAMPLIN
Solar/Wind Harmer
0.572
971193AH1-056 GEN
Solar/Wind Harmer
11.101
970133AG2-095 GEN
Solar/Wind Harmer
1.61
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.114
3141873WAN 176
Solar/Wind Harmer
2.731
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
1.984
3146926FARMVIL
Solar/Wind Harmer
0.088
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
962971AG1-146 GEN
Solar/Wind Harmer
2.159
3142946ENON
Solar/Wind Harmer
0.044
970009AG2-005 GEN
Solar/Wind Harmer
0.976
316404AE1-155 C
Solar/Wind Harmer
0.028
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.766
316044AC1-158 PL1
Solar/Wind Helper
1.631
316450AC1-158 RIC
Solar/Wind Helper
0.435
3147666LOUISA
Solar/Wind Helper
0.576
316170AC1-121 GEN2
Solar/Wind Helper
0.345
3145893MURPHYS
Solar/Wind Harmer
1.134
316011AB1-132 GEN
Solar/Wind Harmer
4.622
962571AG1-106 GEN
Solar/Wind Harmer
3.617
3146173TUNIS
Solar/Wind Harmer
0.254
3145683EARLEYS
Solar/Wind Harmer
0.253
3146263WOODLND
Solar/Wind Harmer
0.252
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.829
3145796HORNRTN
Solar/Wind Harmer
0.251
971795AH1-408 GEN
Solar/Wind Harmer
16.715
3145823KELFORD
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.25
3145963POPLR C
Solar/Wind Harmer
0.249
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
2.242
316212AC1-099_GEN
Solar/Wind Harmer
1.268
316129AC1-054 GEN
Solar/Wind Harmer
0.918
970661AG2-428 GEN
Solar/Wind Harmer
24.263
971065AG2-659 GEN
Solar/Wind Harmer
10.39
3145336SMITFLD
Solar/Wind Harmer
0.973
3146293MARTNCO
Solar/Wind Harmer
0.225
315722AD1-056 GEN
Solar/Wind Harmer
1.532
3145746EVERETS
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.24
316381AD1-082 GEN
Solar/Wind Harmer
0.249
316494AC1-189 GEN
Solar/Wind Harmer
0.804
970659AG2-427 GEN
Solar/Wind Harmer
11.496
3146233WITAKRS
Solar/Wind Harmer
0.942
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.05
316359AB2-059 GEN
Solar/Wind Harmer
0.841
316049AB1-081 GEN
Solar/Wind Harmer
1.34
3145543BTLEBRO
Solar/Wind Harmer
0.234
3145543BTLEBRO
Solar/Wind Harmer
0.187
3142053HEARTS
Solar/Wind Harmer
0.412
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.407
970401AG2-262 GEN
Solar/Wind Harmer
1.317
3138126ROCKLANDING
Solar/Wind Harmer
0.101
961611AG1-000B GEN
Solar/Wind Harmer
11.332
316003AC1-222 GEN
Solar/Wind Harmer
0.006
971647AH1-324 GEN
Solar/Wind Harmer
8.873
971317AH1-138 GEN
Solar/Wind Harmer
1.539
970685AG2-442 GEN
Solar/Wind Harmer
14.697
971069AG2-661 GEN
Solar/Wind Harmer
3.441
316159AE1-175 C
Solar/Wind Harmer
0.165
963171AG1-166 GEN
Solar/Wind Harmer
1.004
971563AH1-280 GEN
Solar/Wind Harmer
2.008
3144293JTRSVLE
Adder
0.599
316458AB2-190 GEN2
Solar/Wind Harmer
0.989
315671AE2-027_GEN
Solar/Wind Harmer
11.755
970129AG2-093 GEN
Solar/Wind Harmer
5.199
971777AH1-397 GEN
Solar/Wind Harmer
0.395
3141843SHACKLE
Adder
0.764
3141766HARMONY
Solar/Wind Harmer
0.03
3146926FARMVIL
Solar/Wind Harmer
0.088
3138133OCRAN
Solar/Wind Harmer
0.087
3142433PROV 92
Solar/Wind Harmer
0.557
3142433PROV 92
Adder
0.271
3142433PROV 92
Adder
0.271
970223AG2-152 GEN
Solar/Wind Harmer
9.565
944631AF1-128 GEN
Adder
62.411
270016AE1-250 BESS
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.023
3147123OTTER R
Solar/Wind Harmer
0.07
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3141726DUNNSVL
Solar/Wind Harmer
0.457
316045AC1-158 PL2
Solar/Wind Helper
5.221
3147666LOUISA
Solar/Wind Helper
1.002
316192AB2-158 GEN
Solar/Wind Helper
1.658
316254AC1-120 GEN1
Solar/Wind Helper
1.035
971167AH1-042 GEN
Solar/Wind Harmer
12.277
315976AC1-164 GENA
Solar/Wind Harmer
14.222
316169AC1-164_GENC
Solar/Wind Harmer
12.287
315975AC1-164 GENB
Solar/Wind Harmer
0.421
962981AG1-147 GEN
Solar/Wind Harmer
5.038
970327AG2-215 GEN
Solar/Wind Harmer
4.29
316164AC1-076 GEN
Solar/Wind Helper
1.17
970533AG2-339 GEN
50/50
32.288
970531AG2-338 GEN
50/50
12.915
315242AE2-183_GT2
50/50
5.789
315241AE2-183_GT1
50/50
5.753
972185AH1-677 GEN
50/50
20.868
3151041BRUNSWICKG3
50/50
4.54
972187AH1-678 GEN
50/50
10.419
970933AG2-581 GEN
Solar/Wind Harmer
26.407
970099AG2-077 GEN
Solar/Wind Harmer
31.122
3144356SAPONY
Solar/Wind Harmer
2.393
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.094
3145506HICKORY
Solar/Wind Harmer
0.657
3145506HICKORY
Solar/Wind Harmer
0.164
316339AD2-160 GEN
Solar/Wind Harmer
0.443
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.152
3142956BIRDNECK
Solar/Wind Harmer
0
3137176SLIGO L2192
Solar/Wind Harmer
1.084
3146456SLIGO L269
Solar/Wind Harmer
4.819
316316AC1-027 C
Solar/Wind Harmer
0.261
3130086AYDLETT
Solar/Wind Harmer
1.088
316036AC1-147 C
Solar/Wind Harmer
0.05
3150991CHESPKB
Adder
2.836
3150991CHESPKB
Adder
2.768
3146386ELIZ CT
Solar/Wind Harmer
0.27
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146516WINFALL
Solar/Wind Harmer
0.268
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
0.267
3146376EDENTON
Solar/Wind Harmer
1.171
3146376EDENTON
Solar/Wind Harmer
1.171
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
11.799
3145893MURPHYS
Solar/Wind Harmer
1.706
3145893MURPHYS
Solar/Wind Harmer
0.459
316181AB2-040 GEN
Solar/Wind Harmer
0.369
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.254
3142666NORTHAMPTON
Solar/Wind Harmer
0.153
3146173TUNIS
Solar/Wind Harmer
0.254
3146173TUNIS
Solar/Wind Harmer
0.254
316426AA2-053 GEN
Solar/Wind Harmer
0.849
3145796HORNRTN
Solar/Wind Harmer
0.754
3145593CAROLNA
Solar/Wind Harmer
0.251
3145593CAROLNA
Solar/Wind Harmer
0.251
966811AG1-552 GEN
Solar/Wind Harmer
2.724
3145593CAROLNA
Solar/Wind Harmer
0.313
3145783HORNRTN
Solar/Wind Harmer
4.447
3145783HORNRTN
Solar/Wind Harmer
3.557
3145783HORNRTN
Solar/Wind Harmer
1.112
3145783HORNRTN
Solar/Wind Harmer
0.445
316274AC1-208 GEN
Solar/Wind Harmer
1.268
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.486
3145933PARMELE
Solar/Wind Harmer
0.243
970657AG2-426 GEN
Solar/Wind Harmer
8.443
970657AG2-426 GEN
Solar/Wind Harmer
1.77
939181AE1-148 GEN
Solar/Wind Harmer
11.415
3145493TOT1
Solar/Wind Harmer
0.548
3145453TOT5
Solar/Wind Harmer
0.329
3145603CNETO
Solar/Wind Harmer
0.219
961601AG1-000A GEN
Solar/Wind Harmer
4.164
316263AC1-034 GEN
Solar/Wind Harmer
8.897
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.79
964791AG1-342 GEN
Solar/Wind Harmer
4.311
3146843MT LREL
Solar/Wind Harmer
0.224
3146843MT LREL
Solar/Wind Harmer
0.224
971741AH1-377 GEN
Solar/Wind Harmer
21.422
316222AC1-221 GEN
Solar/Wind Harmer
0.867
970323AG2-213 GEN
Solar/Wind Harmer
8.785
971775AH1-396 GEN
Solar/Wind Harmer
0.329
316034AC1-036 C
Solar/Wind Harmer
0.015
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.225
970301AG2-198 GEN
Solar/Wind Harmer
8.511
958211AF2-115 GEN
Solar/Wind Harmer
2.259
963191AG1-168 GEN
Solar/Wind Harmer
0.753
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.505
3147133PAMPLIN
Solar/Wind Harmer
0.182
3147133PAMPLIN
Solar/Wind Harmer
0.146
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
78.098
942751AE2-291 GEN
Solar/Wind Harmer
8.652
3142946ENON
Solar/Wind Harmer
0.013
270013AE1-250 PV
Solar/Wind Harmer
0.004
958261AF2-120 GEN
Solar/Wind Harmer
4.097
316075AC2-137 C
Solar/Wind Harmer
0.033
316447AC1-158 HLD
Solar/Wind Helper
3.59
315651AD1-115 GEN
Solar/Wind Helper
0.751
NYPJM->LTFIMP_NY
CLTF
2.873
LGEELTFEXP_LGEE->PJM
CLTF
2
LAGNLTFEXP_LAGN->PJM
CLTF
11.265
WECLTFEXP_WEC->PJM
CLTF
1.023
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.702
TVALTFEXP_TVA->PJM
CLTF
5.645
CPLELTFEXP_CPLE->PJM
CLTF
15.998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.498
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.348
MECLTFEXP_MEC->PJM
CLTF
5.484
SIGELTFEXP_SIGE->PJM
CLTF
0.165

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5485.71
MW Contribution:21.25
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
6.204
3151051BRUNSWICKS1
50/50
10.099
3151021BRUNSWICKG1
50/50
4.866
971451AH1-221 GEN
50/50
14.779
3150981CHESPKA
50/50
4.121
3152331SURRY 2
50/50
12.732
940641AE2-051 GEN
Solar/Wind Harmer
41.411
939411AE1-173 GEN
Solar/Wind Harmer
209.945
970919AG2-571 GEN
Solar/Wind Harmer
12.575
970087AG2-069 GEN
Solar/Wind Harmer
37.068
316294AC1-161 GEN
Solar/Wind Harmer
11.942
944591AF1-124 GEN
Solar/Wind Harmer
163.837
316388AE2-253 GEN
Solar/Wind Harmer
2.371
957481AF2-042 GEN
Solar/Wind Harmer
109.7
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316375AC2-012 GEN
Solar/Wind Harmer
12.094
316246AF1-032 C
Solar/Wind Harmer
0.702
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
316093AE2-104_GEN
Solar/Wind Harmer
9.863
315800Z1-036_GEN1
Solar/Wind Harmer
8.362
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.677
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.87
315693AD1-088 GEN
Solar/Wind Harmer
16.313
316023GEN1_S
Solar/Wind Harmer
2.184
962491AG1-098 GEN
Solar/Wind Harmer
21.518
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.032
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.945
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145336SMITFLD
Solar/Wind Harmer
-0.125
960081AF2-299 GEN
Solar/Wind Harmer
3.535
3146263WOODLND
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.536
962571AG1-106 GEN
Solar/Wind Harmer
4.491
3145963POPLR C
Solar/Wind Harmer
-0.031
3145823KELFORD
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.381
316174AB2-169 GEN
Solar/Wind Harmer
4.777
315687AD1-152 GEN
Solar/Wind Harmer
3.732
3145796HORNRTN
Solar/Wind Harmer
-0.101
315244AE2-183_ST
50/50
10.726
963041AG1-153 GEN
50/50
9.853
3151081ELIZAR1
50/50
30.369
3151091ELIZAR2
50/50
29.842
941591AE2-156 GEN
50/50
27.695
3152611GOSPORTB
50/50
4.203
3152621GOSPORTC
50/50
3.567
3152601GOSPORTA
50/50
3.291
315779AE2-040
50/50
4.317
972263AH1-716 GEN
50/50
173.856
941031AE2-094 GEN
Solar/Wind Harmer
82.028
944011AF1-069 GEN
Solar/Wind Harmer
25.702
970673AG2-436 GEN
Solar/Wind Harmer
89.749
970673AG2-436 GEN
Solar/Wind Harmer
45.442
971967AH1-528 GEN
Solar/Wind Harmer
78.206
970085AG2-068 GEN
Solar/Wind Harmer
24.712
970581AG2-369 GEN
Solar/Wind Harmer
21.252
957871AF2-081 GEN
Solar/Wind Harmer
17.564
319010AE1-072 C
Solar/Wind Harmer
7.086
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316315AB2-025 C
Solar/Wind Harmer
0.937
313526AB2-022
Solar/Wind Harmer
0.936
316305AF2-043 C
Solar/Wind Harmer
1.045
315814AE2-033 C
Solar/Wind Harmer
32.246
316321Z2-027
Solar/Wind Harmer
0.932
3146396TANGLEW
Solar/Wind Harmer
0.636
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315835AF2-110_GEN
Solar/Wind Harmer
4.24
315611Z1-036_GEN2
Solar/Wind Harmer
8.362
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.664
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
316311AC2-079 GEN
Solar/Wind Harmer
16.358
315833AF1-017_GEN
Solar/Wind Harmer
6.154
316349AD2-085 GEN
Solar/Wind Harmer
2.882
315732AD1-074 GEN1
Solar/Wind Harmer
6.552
315733AD1-074 GEN2
Solar/Wind Harmer
6.552
315735AD1-075 GEN1
Solar/Wind Harmer
3.277
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.056
965291AG1-394 GEN
Solar/Wind Harmer
2.84
316318V4-068
Solar/Wind Harmer
0.794
3145893MURPHYS
Solar/Wind Harmer
-0.085
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.276
961941AG1-037 GEN
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
946281AF1-292 GEN
Solar/Wind Harmer
0.704
3146043SEABORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
970661AG2-428 GEN
Solar/Wind Harmer
32.599
971795AH1-408 GEN
Solar/Wind Harmer
22.92
316212AC1-099_GEN
Solar/Wind Harmer
2.633
3147043LAWRENC
Adder
2.429
3146293MARTNCO
Solar/Wind Harmer
0.187
316381AD1-082 GEN
Solar/Wind Harmer
2.75
970659AG2-427 GEN
Solar/Wind Harmer
15.8
316129AC1-054 GEN
Solar/Wind Harmer
2.604
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
315722AD1-056 GEN
Solar/Wind Harmer
3.098
971065AG2-659 GEN
Solar/Wind Harmer
14.797
3138126ROCKLANDING
Solar/Wind Harmer
0.09
3151171GRAVELC
Adder
2.779
316494AC1-189 GEN
Solar/Wind Harmer
3.154
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.367
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.861
3145543BTLEBRO
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316359AB2-059 GEN
Solar/Wind Harmer
3.858
316049AB1-081 GEN
Solar/Wind Harmer
3.087
3142053HEARTS
Solar/Wind Harmer
0.336
971317AH1-138 GEN
Solar/Wind Harmer
3.516
961611AG1-000B GEN
Solar/Wind Harmer
13.798
316237AB2-079_GEN
Solar/Wind Harmer
0.825
970401AG2-262 GEN
Solar/Wind Harmer
1.762
971647AH1-324 GEN
Solar/Wind Harmer
13.425
316159AE1-175 C
Solar/Wind Harmer
0.709
316003AC1-222 GEN
Solar/Wind Harmer
2.478
971069AG2-661 GEN
Solar/Wind Harmer
3.938
3144293JTRSVLE
Adder
0.641
3141843SHACKLE
Adder
0.947
3142433PROV 92
Adder
0.328
3142433PROV 92
Adder
0.328
944631AF1-128 GEN
Adder
73.982
3150351NORNECKC2
Adder
1.429
316045AC1-158 PL2
Solar/Wind Helper
5.164
3147666LOUISA
Solar/Wind Helper
1.005
316192AB2-158 GEN
Solar/Wind Helper
1.664
316254AC1-120 GEN1
Solar/Wind Helper
1.04
315607AA1-063A GEN
Solar/Wind Harmer
3.165
971445AH1-216 GEN
Solar/Wind Harmer
19.378
316087AB2-174 GEN
Solar/Wind Harmer
4.457
315652AC1-086 GEN
Solar/Wind Harmer
35.144
3137643SOCKMAN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970831AG2-522 GEN
Solar/Wind Harmer
14.908
3143316POE
Solar/Wind Harmer
-0.117
316005AA1-067
Solar/Wind Harmer
0.6
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
970181AG2-120 GEN
Solar/Wind Harmer
3.894
972265AH1-717 GEN
Adder
20.283
3151201GRAVEL4
Adder
19.014
3151191GRAVEL3
Adder
18.773
3151211GRAVEL5
Adder
18.773
957861AF2-080 GEN
Solar/Wind Harmer
12.824
316420AA1-050 GEN
Solar/Wind Harmer
3.328
316319Z2-044 C
Solar/Wind Harmer
1.602
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
316239AB2-077_GEN
Solar/Wind Harmer
0.825
316238AB2-078_GEN
Solar/Wind Harmer
0.825
316118AC1-105 GEN
Solar/Wind Harmer
1.849
3147173SINAI
Solar/Wind Harmer
-0.027
3147243WELCO
Solar/Wind Harmer
-0.017
316369SG1_INVT
Solar/Wind Harmer
4.602
957831AF2-077 GEN
Solar/Wind Harmer
0.771
3138283WHITEMARSH
Solar/Wind Harmer
0.04
971443AH1-215 GEN
Solar/Wind Harmer
4.9
3144303KENBRDG
Solar/Wind Harmer
-0.02
3142433PROV 92
Adder
0.328
3142433PROV 92
Adder
0.328
316164AC1-076 GEN
Solar/Wind Helper
1.169
3151031BRUNSWICKG2
50/50
4.866
3151101ELIZAR3
50/50
30.758
3151161SURRY 1
50/50
10.034
970917AG2-570 GEN
Solar/Wind Harmer
99.341
315773AC2-141 GEN
Solar/Wind Harmer
15.446
944581AF1-123 GEN
Solar/Wind Harmer
163.249
944601AF1-125 GEN
Solar/Wind Harmer
160.701
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.273
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.034
316435W1029_GEN3
Solar/Wind Harmer
6.217
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316478AD1-087 GEN
Solar/Wind Harmer
2.871
316486AD2-202 GEN
Solar/Wind Harmer
0.841
315614AA2-178 GEN
Solar/Wind Harmer
3.553
971157AH1-035 GEN
Solar/Wind Harmer
4.06
315737AD1-076 GEN
Solar/Wind Harmer
6.157
316365GEN2_N
Solar/Wind Harmer
2.184
3146206CASHIE
Solar/Wind Harmer
-0.032
3156081AA2-088 GEN
Solar/Wind Harmer
10.416
3145893MURPHYS
Solar/Wind Harmer
0.222
3145893MURPHYS
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.046
961681AG1-008 GEN
Solar/Wind Harmer
25.046
3156021HOLLOMANSOL
Solar/Wind Harmer
4.277
3146173TUNIS
Solar/Wind Harmer
-0.032
316463AE2-346 GEN
Solar/Wind Harmer
0.512
316140AB2-099
Solar/Wind Harmer
0.213
962331AG1-082 GEN
Solar/Wind Harmer
3.951
3145336SMITFLD
Solar/Wind Harmer
-0.012
966621AG1-532 GEN
Solar/Wind Harmer
0.638
3146263WOODLND
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
313506AB2-031 GEN
Solar/Wind Harmer
2.505
316317KELFORD C
Solar/Wind Harmer
1.464
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
970661AG2-428 GEN
Solar/Wind Harmer
5.777
316210AC1-098 GEN
Solar/Wind Harmer
4.739
3147043LAWRENC
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.768
316083AB2-161 GEN
Solar/Wind Harmer
4.866
970659AG2-427 GEN
Solar/Wind Harmer
2.8
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
315724AD1-057 GEN
Solar/Wind Harmer
1.704
3144216WINCHST
Adder
0.991
3150921YORKTN3
Adder
6.605
316327AA2-057 GEN
Solar/Wind Harmer
2.969
3151221GRAVEL6
Adder
18.992
3151171GRAVELC
Adder
3.654
3146233WITAKRS
Solar/Wind Harmer
0.607
3146233WITAKRS
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3138543CONSLDL
Solar/Wind Harmer
-0.019
961601AG1-000A GEN
Solar/Wind Harmer
11.396
3145543BTLEBRO
Solar/Wind Harmer
-0.029
3145543BTLEBRO
Solar/Wind Harmer
-0.029
315813AE1-149 C
Solar/Wind Harmer
17.781
961611AG1-000B GEN
Solar/Wind Harmer
5.887
316131AB2-060 GEN
Solar/Wind Harmer
2.926
316248AF1-058 C
Solar/Wind Harmer
0.807
960061AF2-297 GEN
Solar/Wind Harmer
13.386
316382AG1-145 C
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
20.631
315785AD2-033 C
Solar/Wind Harmer
5.719
316283AC2-100 C
Solar/Wind Harmer
2.345
315778AD1-151 GEN
Solar/Wind Harmer
21.559
970257AG2-171 GEN
Solar/Wind Harmer
9.298
959311AF2-222 GEN
Solar/Wind Harmer
25.545
315839AE2-212 C
Solar/Wind Harmer
0.733
971683AH1-343 GEN
Solar/Wind Harmer
10.422
3144293JTRSVLE
Adder
0.641
3141843SHACKLE
Adder
0.947
3142433PROV 92
Adder
0.328
3142433PROV 92
Adder
0.328
3150351NORNECKC2
Adder
1.453
316044AC1-158 PL1
Solar/Wind Helper
1.613
316450AC1-158 RIC
Solar/Wind Helper
0.43
3147666LOUISA
Solar/Wind Helper
0.578
316170AC1-121 GEN2
Solar/Wind Helper
0.347
970909AG2-566 GEN
Solar/Wind Harmer
2.035
970533AG2-339 GEN
50/50
34.611
970531AG2-338 GEN
50/50
13.844
315242AE2-183_GT2
50/50
6.204
315241AE2-183_GT1
50/50
6.166
972185AH1-677 GEN
50/50
22.366
3151041BRUNSWICKG3
50/50
4.866
972187AH1-678 GEN
50/50
11.167
3150991CHESPKB
50/50
3.457
3150991CHESPKB
50/50
3.374
970933AG2-581 GEN
Solar/Wind Harmer
37.255
316185AD1-033 GEN
Solar/Wind Harmer
3.726
3145506HICKORY
Solar/Wind Harmer
-0.14
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.371
3142956BIRDNECK
Solar/Wind Harmer
1.886
316316AC1-027 C
Solar/Wind Harmer
1.078
316018AA1-139 ULT2
Solar/Wind Harmer
3.009
316017AA1-139 ULT1
Solar/Wind Harmer
2.842
970099AG2-077 GEN
Solar/Wind Harmer
43.88
3137176SLIGO L2192
Solar/Wind Harmer
-0.139
3146456SLIGO L269
Solar/Wind Harmer
4.14
3130086AYDLETT
Solar/Wind Harmer
-0.139
316036AC1-147 C
Solar/Wind Harmer
0.943
3144356SAPONY
Solar/Wind Harmer
1.212
3146386ELIZ CT
Solar/Wind Harmer
-0.035
316431W1029_GEN1
Solar/Wind Harmer
6.217
316433W1029_GEN2
Solar/Wind Harmer
6.217
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
0.994
3146376EDENTON
Solar/Wind Harmer
0.994
315742AE1-103 GEN
Solar/Wind Harmer
3.459
316065AD1-022 GEN
Solar/Wind Harmer
16.113
3145893MURPHYS
Solar/Wind Harmer
0.889
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316236AE1-162_GEN
Solar/Wind Harmer
0.95
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316181AB2-040 GEN
Solar/Wind Harmer
4.348
316426AA2-053 GEN
Solar/Wind Harmer
3.132
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.475
3145593CAROLNA
Solar/Wind Harmer
0.257
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145783HORNRTN
Solar/Wind Harmer
3.649
3145783HORNRTN
Solar/Wind Harmer
2.919
3145783HORNRTN
Solar/Wind Harmer
0.912
3145783HORNRTN
Solar/Wind Harmer
0.365
970657AG2-426 GEN
Solar/Wind Harmer
9.452
970657AG2-426 GEN
Solar/Wind Harmer
1.977
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
316274AC1-208 GEN
Solar/Wind Harmer
3.24
3145493TOT1
Solar/Wind Harmer
0.449
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.18
939181AE1-148 GEN
Solar/Wind Harmer
16.17
961601AG1-000A GEN
Solar/Wind Harmer
11.253
316263AC1-034 GEN
Solar/Wind Harmer
13.413
313527AB2-043 GEN
Solar/Wind Harmer
4.434
962561AG1-105 GEN
Solar/Wind Harmer
15.207
964791AG1-342 GEN
Solar/Wind Harmer
5.765
3146843MT LREL
Solar/Wind Harmer
-0.027
3146843MT LREL
Solar/Wind Harmer
-0.027
971741AH1-377 GEN
Solar/Wind Harmer
30.134
316033AB2-134 GEN
Solar/Wind Harmer
8.307
315697AD1-025 GEN
Solar/Wind Harmer
5.21
316222AC1-221 GEN
Solar/Wind Harmer
2.532
970323AG2-213 GEN
Solar/Wind Harmer
12.397
971775AH1-396 GEN
Solar/Wind Harmer
1.765
316034AC1-036 C
Solar/Wind Harmer
0.46
3144293JTRSVLE
Adder
0.641
3144293JTRSVLE
Adder
0.54
944641AF1-129 GEN
Adder
84.798
3150341NORNECKC1
Adder
1.501
3150341NORNECKC1
Adder
1.489
316447AC1-158 HLD
Solar/Wind Helper
3.55
315651AD1-115 GEN
Solar/Wind Helper
0.754
970301AG2-198 GEN
Solar/Wind Harmer
10.716
NYPJM->LTFIMP_NY
CLTF
2.958
LGEELTFEXP_LGEE->PJM
CLTF
1.969
LAGNLTFEXP_LAGN->PJM
CLTF
11.587
WECLTFEXP_WEC->PJM
CLTF
1.007
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.707
TVALTFEXP_TVA->PJM
CLTF
5.796
CPLELTFEXP_CPLE->PJM
CLTF
17.078
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.508
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.948
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.784
MECLTFEXP_MEC->PJM
CLTF
5.477
SIGELTFEXP_SIGE->PJM
CLTF
0.164

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56272_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56272_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.96 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4114.65
MW Contribution:19.6
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.95
963041AG1-153 GEN
50/50
9.127
3151541CLOVER2
50/50
5.691
315779AE2-040
50/50
3.626
3151611KERR 4
50/50
0.458
3151621KERR 5
50/50
0.458
3151631KERR 6
50/50
0.458
3151641KERR 7
50/50
0.458
3151281ROARAP4
50/50
0.259
3151281ROARAP4
50/50
0.243
941031AE2-094 GEN
Solar/Wind Harmer
76.337
944011AF1-069 GEN
Solar/Wind Harmer
23.919
970673AG2-436 GEN
Solar/Wind Harmer
83.349
970673AG2-436 GEN
Solar/Wind Harmer
42.202
971967AH1-528 GEN
Solar/Wind Harmer
72.452
970085AG2-068 GEN
Solar/Wind Harmer
22.787
970581AG2-369 GEN
Solar/Wind Harmer
19.597
316315AB2-025 C
Solar/Wind Harmer
0.787
315814AE2-033 C
Solar/Wind Harmer
27.034
946281AF1-292 GEN
Solar/Wind Harmer
0.568
316087AB2-174 GEN
Solar/Wind Harmer
3.556
970831AG2-522 GEN
Solar/Wind Harmer
12.26
315652AC1-086 GEN
Solar/Wind Harmer
27.499
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
3147173SINAI
Solar/Wind Harmer
-0.024
3147243WELCO
Solar/Wind Harmer
-0.015
316118AC1-105 GEN
Solar/Wind Harmer
1.62
316239AB2-077_GEN
Solar/Wind Harmer
0.708
316238AB2-078_GEN
Solar/Wind Harmer
0.708
315607AA1-063A GEN
Solar/Wind Harmer
2.372
3146043SEABORD
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.269
3146033SCOT NK
Solar/Wind Harmer
-0.091
3143316POE
Solar/Wind Harmer
-0.09
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
965291AG1-394 GEN
Solar/Wind Harmer
2.008
316318V4-068
Solar/Wind Harmer
0.563
3145893MURPHYS
Solar/Wind Harmer
-0.061
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.197
961941AG1-037 GEN
Solar/Wind Harmer
0.17
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316420AA1-050 GEN
Solar/Wind Harmer
2.577
957861AF2-080 GEN
Solar/Wind Harmer
9.823
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.022
970601AG2-382 GEN
Solar/Wind Harmer
9.603
315732AD1-074 GEN1
Solar/Wind Harmer
4.385
315733AD1-074 GEN2
Solar/Wind Harmer
4.385
315735AD1-075 GEN1
Solar/Wind Harmer
2.193
3130546PLYMOUTH
Solar/Wind Harmer
-0.022
315816AE2-034 GEN
Solar/Wind Harmer
1.73
971443AH1-215 GEN
Solar/Wind Harmer
4.181
3144303KENBRDG
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
315611Z1-036_GEN2
Solar/Wind Harmer
5.153
315835AF2-110_GEN
Solar/Wind Harmer
2.575
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316305AF2-043 C
Solar/Wind Harmer
0.619
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
316321Z2-027
Solar/Wind Harmer
0.551
3146396TANGLEW
Solar/Wind Harmer
0.375
313526AB2-022
Solar/Wind Harmer
0.548
316311AC2-079 GEN
Solar/Wind Harmer
10.237
315833AF1-017_GEN
Solar/Wind Harmer
3.854
316349AD2-085 GEN
Solar/Wind Harmer
1.805
970683AG2-441 GEN
Solar/Wind Harmer
15.731
970681AG2-440 GEN
Solar/Wind Harmer
12.585
3146406KITTY HAWK
Solar/Wind Harmer
0.017
319010AE1-072 C
Solar/Wind Harmer
4.06
970865AG2-541 GEN
Solar/Wind Harmer
8.137
957871AF2-081 GEN
Solar/Wind Harmer
10.005
3151081ELIZAR1
Adder
15.891
3151091ELIZAR2
Adder
15.615
3152611GOSPORTB
Adder
2.203
3152621GOSPORTC
Adder
1.869
3152601GOSPORTA
Adder
1.724
946301AF1-294 GEN
Solar/Wind Harmer
4.916
961791AG1-021 GEN
Solar/Wind Harmer
2.398
3151031BRUNSWICKG2
50/50
4.507
970413AG2-270 GEN
50/50
24.952
3151591KERR 2
50/50
0.458
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.26
970917AG2-570 GEN
Solar/Wind Harmer
91.647
316478AD1-087 GEN
Solar/Wind Harmer
2.597
316486AD2-202 GEN
Solar/Wind Harmer
0.761
316365GEN2_N
Solar/Wind Harmer
1.761
966621AG1-532 GEN
Solar/Wind Harmer
0.515
3147043LAWRENC
Solar/Wind Harmer
-0.015
313506AB2-031 GEN
Solar/Wind Harmer
1.989
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.711
960061AF2-297 GEN
Solar/Wind Harmer
11.79
315724AD1-057 GEN
Solar/Wind Harmer
1.351
316131AB2-060 GEN
Solar/Wind Harmer
2.509
316210AC1-098 GEN
Solar/Wind Harmer
3.629
316327AA2-057 GEN
Solar/Wind Harmer
2.332
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
0.481
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
961601AG1-000A GEN
Solar/Wind Harmer
9.103
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.074
3145823KELFORD
Solar/Wind Harmer
-0.023
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
0.158
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
17.808
961681AG1-008 GEN
Solar/Wind Harmer
17.808
964241AG1-285 GEN
Solar/Wind Harmer
17.664
3146173TUNIS
Solar/Wind Harmer
-0.023
316463AE2-346 GEN
Solar/Wind Harmer
0.366
316140AB2-099
Solar/Wind Harmer
0.152
962331AG1-082 GEN
Solar/Wind Harmer
2.826
3156081AA2-088 GEN
Solar/Wind Harmer
7.311
3156021HOLLOMANSOL
Solar/Wind Harmer
3.009
3145746EVERETS
Solar/Wind Harmer
-0.022
315243AE2-183_GT3
50/50
5.755
3151051BRUNSWICKS1
50/50
9.355
3151021BRUNSWICKG1
50/50
4.507
971451AH1-221 GEN
50/50
13.69
3151531CLOVER1
50/50
5.718
3151601KERR 3
50/50
0.458
3151581KERR 1
50/50
0.163
3147043LAWRENC
50/50
2.116
3151391GASTONA
50/50
0.588
3151411GASTONB
50/50
0.588
3151261ROARAP2
50/50
0.266
970919AG2-571 GEN
Solar/Wind Harmer
11.601
970087AG2-069 GEN
Solar/Wind Harmer
34.181
939411AE1-173 GEN
Solar/Wind Harmer
170.129
957481AF2-042 GEN
Solar/Wind Harmer
99.882
315693AD1-088 GEN
Solar/Wind Harmer
14.731
962491AG1-098 GEN
Solar/Wind Harmer
19.405
315687AD1-152 GEN
Solar/Wind Harmer
3.35
316023GEN1_S
Solar/Wind Harmer
1.761
960081AF2-299 GEN
Solar/Wind Harmer
2.853
971795AH1-408 GEN
Solar/Wind Harmer
18.718
971065AG2-659 GEN
Solar/Wind Harmer
12.309
316129AC1-054 GEN
Solar/Wind Harmer
2.154
316011AB1-132 GEN
Solar/Wind Harmer
5.114
962571AG1-106 GEN
Solar/Wind Harmer
3.514
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
970401AG2-262 GEN
Solar/Wind Harmer
1.534
316237AB2-079_GEN
Solar/Wind Harmer
0.708
315722AD1-056 GEN
Solar/Wind Harmer
2.456
316212AC1-099_GEN
Solar/Wind Harmer
2.016
3146263WOODLND
Solar/Wind Harmer
-0.023
3146233WITAKRS
Solar/Wind Harmer
-0.091
316359AB2-059 GEN
Solar/Wind Harmer
3.083
316049AB1-081 GEN
Solar/Wind Harmer
2.467
3142053HEARTS
Solar/Wind Harmer
0.269
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.023
961671AG1-007 GEN
Solar/Wind Harmer
0.286
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
0.671
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.416
316003AC1-222 GEN
Solar/Wind Harmer
2.177
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3146293MARTNCO
Solar/Wind Harmer
0.137
316174AB2-169 GEN
Solar/Wind Harmer
3.387
3146206CASHIE
Solar/Wind Harmer
-0.022
971547AH1-271 GEN
Solar/Wind Harmer
5.488
3145963POPLR C
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.06
971163AH1-040 GEN
Solar/Wind Harmer
20.04
3130156CHOWAN
Solar/Wind Harmer
-0.021
315800Z1-036_GEN1
Solar/Wind Harmer
5.153
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.021
316093AE2-104_GEN
Solar/Wind Harmer
5.989
316246AF1-032 C
Solar/Wind Harmer
0.415
970685AG2-442 GEN
Solar/Wind Harmer
17.619
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316388AE2-253 GEN
Solar/Wind Harmer
1.348
970661AG2-428 GEN
Solar/Wind Harmer
21.192
944591AF1-124 GEN
Solar/Wind Harmer
90.948
316381AD1-082 GEN
Solar/Wind Harmer
1.816
970659AG2-427 GEN
Solar/Wind Harmer
10.495
316375AC2-012 GEN
Solar/Wind Harmer
6.72
3150981CHESPKA
Adder
2.158
963171AG1-166 GEN
Solar/Wind Harmer
2.398
3145746EVERETS
Solar/Wind Harmer
-0.022
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.766
3146206CASHIE
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
316283AC2-100 C
Solar/Wind Harmer
2.053
315737AD1-076 GEN
Solar/Wind Harmer
4.121
971157AH1-035 GEN
Solar/Wind Harmer
2.704
315785AD2-033 C
Solar/Wind Harmer
4.883
315614AA2-178 GEN
Solar/Wind Harmer
2.306
3145273HOLLAND
Solar/Wind Harmer
-0.016
971683AH1-343 GEN
Solar/Wind Harmer
9.136
970257AG2-171 GEN
Solar/Wind Harmer
7.93
3146376EDENTON
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.981
959311AF2-222 GEN
Solar/Wind Harmer
21.769
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316435W1029_GEN3
Solar/Wind Harmer
3.733
316320Y1-086
Solar/Wind Harmer
1.19
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.444
970661AG2-428 GEN
Solar/Wind Harmer
3.756
944581AF1-123 GEN
Solar/Wind Harmer
90.622
944601AF1-125 GEN
Solar/Wind Harmer
89.208
316083AB2-161 GEN
Solar/Wind Harmer
3.214
970659AG2-427 GEN
Solar/Wind Harmer
1.86
315813AE1-149 C
Solar/Wind Harmer
12.185
3151101ELIZAR3
Adder
16.095
3144873MCLAUGH
Solar/Wind Harmer
0
963181AG1-167 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144536CHRHLND
Solar/Wind Harmer
-0.003
3147133PAMPLIN
Solar/Wind Harmer
-0.058
971193AH1-056 GEN
Solar/Wind Harmer
11.575
3145336SMITFLD
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.509
3151221GRAVEL6
Adder
9.984
3151171GRAVELC
Adder
1.921
3144216WINCHST
Adder
0.443
3150921YORKTN3
Adder
2.878
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
970533AG2-339 GEN
50/50
32.21
970531AG2-338 GEN
50/50
12.884
315242AE2-183_GT2
50/50
5.755
315241AE2-183_GT1
50/50
5.72
972185AH1-677 GEN
50/50
20.748
3151041BRUNSWICKG3
50/50
4.507
972187AH1-678 GEN
50/50
10.344
3151361ROSEMG1
50/50
0.776
3151371ROSEMS1
50/50
0.481
3151381ROSEMG2
50/50
0.363
970535AG2-341 GEN
50/50
3.826
3152661PLYWOOD A
50/50
0.474
970933AG2-581 GEN
Solar/Wind Harmer
34.364
970099AG2-077 GEN
Solar/Wind Harmer
39.953
3144356SAPONY
Solar/Wind Harmer
1.018
316181AB2-040 GEN
Solar/Wind Harmer
3.451
939181AE1-148 GEN
Solar/Wind Harmer
13.835
3145796HORNRTN
Solar/Wind Harmer
-0.072
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.705
3145593CAROLNA
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
2.839
3145783HORNRTN
Solar/Wind Harmer
2.272
3145783HORNRTN
Solar/Wind Harmer
0.71
3145783HORNRTN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
2.403
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
5.022
962561AG1-105 GEN
Solar/Wind Harmer
13.216
313527AB2-043 GEN
Solar/Wind Harmer
3.804
316274AC1-208 GEN
Solar/Wind Harmer
2.516
961601AG1-000A GEN
Solar/Wind Harmer
8.989
316263AC1-034 GEN
Solar/Wind Harmer
10.719
971741AH1-377 GEN
Solar/Wind Harmer
26.554
3145493TOT1
Solar/Wind Harmer
0.35
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
3145893MURPHYS
Solar/Wind Harmer
0.631
3145893MURPHYS
Solar/Wind Harmer
-0.041
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
316222AC1-221 GEN
Solar/Wind Harmer
2.217
316065AD1-022 GEN
Solar/Wind Harmer
10.926
315742AE1-103 GEN
Solar/Wind Harmer
2.245
970323AG2-213 GEN
Solar/Wind Harmer
10.573
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
3146376EDENTON
Solar/Wind Harmer
0.624
3146376EDENTON
Solar/Wind Harmer
0.624
970301AG2-198 GEN
Solar/Wind Harmer
10.435
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.733
316433W1029_GEN2
Solar/Wind Harmer
3.733
3146386ELIZ CT
Solar/Wind Harmer
-0.02
3130086AYDLETT
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.368
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
316018AA1-139 ULT2
Solar/Wind Harmer
1.714
316017AA1-139 ULT1
Solar/Wind Harmer
1.619
316339AD2-160 GEN
Solar/Wind Harmer
1.348
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.048
270455AD2-022 GEN
Solar/Wind Harmer
3.325
270457AD2-023 GEN
Solar/Wind Harmer
1.686
315657AE1-056 GEN
Solar/Wind Harmer
6.945
316123AC1-075 GEN
Solar/Wind Harmer
1.908
970165AG2-112 GEN
Solar/Wind Harmer
1.68
970163AG2-111 GEN
Solar/Wind Harmer
1.602
972265AH1-717 GEN
Adder
10.663
3151201GRAVEL4
Adder
9.996
3151191GRAVEL3
Adder
9.869
3151211GRAVEL5
Adder
9.869
971445AH1-216 GEN
Solar/Wind Harmer
2.771
971563AH1-280 GEN
Solar/Wind Harmer
2.398
3144293JTRSVLE
Adder
0.543
316072AD1-144
Solar/Wind Harmer
0.387
3145336SMITFLD
Solar/Wind Harmer
-0.067
3151171GRAVELC
Adder
1.461
3143226MDLTHAN
Solar/Wind Helper
0.294
316045AC1-158 PL2
Solar/Wind Helper
4.138
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.206
970657AG2-426 GEN
Solar/Wind Harmer
1.298
316185AD1-033 GEN
Solar/Wind Harmer
2.091
3142956BIRDNECK
Solar/Wind Harmer
1.055
316316AC1-027 C
Solar/Wind Harmer
0.603
316036AC1-147 C
Solar/Wind Harmer
0.524
3150991CHESPKB
Adder
1.81
3150991CHESPKB
Adder
1.767
958211AF2-115 GEN
Solar/Wind Harmer
2.997
963191AG1-168 GEN
Solar/Wind Harmer
1.798
3144293JTRSVLE
Adder
0.543
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
316236AE1-162_GEN
Solar/Wind Harmer
0.511
316447AC1-158 HLD
Solar/Wind Helper
2.845
NYPJM->LTFIMP_NY
CLTF
2.22
LAGNLTFEXP_LAGN->PJM
CLTF
9.968
LGEELTFEXP_LGEE->PJM
CLTF
1.693
WECLTFEXP_WEC->PJM
CLTF
0.873
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.656
TVALTFEXP_TVA->PJM
CLTF
4.976
CPLELTFEXP_CPLE->PJM
CLTF
14.701
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.1
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.472
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.988
MECLTFEXP_MEC->PJM
CLTF
4.732
SIGELTFEXP_SIGE->PJM
CLTF
0.141

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 567_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 567_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.02 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4187.08
MW Contribution:15.34
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.909
3151051BRUNSWICKS1
50/50
9.612
3151021BRUNSWICKG1
50/50
4.631
971451AH1-221 GEN
50/50
14.067
3152331SURRY 2
50/50
12.237
3150981CHESPKA
50/50
3.828
940641AE2-051 GEN
Solar/Wind Harmer
30.053
939411AE1-173 GEN
Solar/Wind Harmer
151.675
970919AG2-571 GEN
Solar/Wind Harmer
11.95
970087AG2-069 GEN
Solar/Wind Harmer
26.75
316294AC1-161 GEN
Solar/Wind Harmer
5.441
944591AF1-124 GEN
Solar/Wind Harmer
67.777
957481AF2-042 GEN
Solar/Wind Harmer
78.492
316388AE2-253 GEN
Solar/Wind Harmer
0.915
3146456SLIGO L269
Solar/Wind Harmer
0.291
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316246AF1-032 C
Solar/Wind Harmer
0.129
3146516WINFALL
Solar/Wind Harmer
0.918
3146516WINFALL
Solar/Wind Harmer
0.283
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.671
3130156CHOWAN
Solar/Wind Harmer
0.277
315693AD1-088 GEN
Solar/Wind Harmer
13.054
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.745
316072AD1-144
Solar/Wind Harmer
0.098
962491AG1-098 GEN
Solar/Wind Harmer
15.287
3146206CASHIE
Solar/Wind Harmer
0.264
971547AH1-271 GEN
Solar/Wind Harmer
5.647
316023GEN1_S
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
1.045
3145893MURPHYS
Solar/Wind Harmer
1.162
3146173TUNIS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.259
315687AD1-152 GEN
Solar/Wind Harmer
0.008
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
960081AF2-299 GEN
Solar/Wind Harmer
2.46
316011AB1-132 GEN
Solar/Wind Harmer
4.645
962571AG1-106 GEN
Solar/Wind Harmer
3.635
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.255
316190AA2-174 GEN
Solar/Wind Harmer
0
3145796HORNRTN
Solar/Wind Harmer
0.833
3145796HORNRTN
Solar/Wind Harmer
0.252
3145783HORNRTN
Solar/Wind Harmer
0.252
971795AH1-408 GEN
Solar/Wind Harmer
16.631
3146293MARTNCO
Solar/Wind Harmer
0.23
3145336SMITFLD
Solar/Wind Harmer
0.992
316212AC1-099_GEN
Solar/Wind Harmer
1.284
3147043LAWRENC
Adder
2.229
316129AC1-054 GEN
Solar/Wind Harmer
0.919
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
971065AG2-659 GEN
Solar/Wind Harmer
10.397
315722AD1-056 GEN
Solar/Wind Harmer
1.539
316494AC1-189 GEN
Solar/Wind Harmer
0.815
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.239
3145493TOT1
Solar/Wind Harmer
1.061
3146233WITAKRS
Solar/Wind Harmer
0.949
970661AG2-428 GEN
Solar/Wind Harmer
23.724
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.188
316359AB2-059 GEN
Solar/Wind Harmer
0.846
316049AB1-081 GEN
Solar/Wind Harmer
1.347
3142053HEARTS
Solar/Wind Harmer
0.415
316381AD1-082 GEN
Solar/Wind Harmer
0.24
970659AG2-427 GEN
Solar/Wind Harmer
10.983
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3151171GRAVELC
Adder
2.368
3138126ROCKLANDING
Solar/Wind Harmer
0.102
970401AG2-262 GEN
Solar/Wind Harmer
1.303
316003AC1-222 GEN
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
10.827
971317AH1-138 GEN
Solar/Wind Harmer
1.51
971647AH1-324 GEN
Solar/Wind Harmer
8.259
970685AG2-442 GEN
Solar/Wind Harmer
14.261
963171AG1-166 GEN
Solar/Wind Harmer
0.968
971563AH1-280 GEN
Solar/Wind Harmer
1.936
3144293JTRSVLE
Adder
0.578
316159AE1-175 C
Solar/Wind Harmer
0.148
971069AG2-661 GEN
Solar/Wind Harmer
3.035
316458AB2-190 GEN2
Solar/Wind Harmer
0.837
970129AG2-093 GEN
Solar/Wind Harmer
4.37
315671AE2-027_GEN
Solar/Wind Harmer
9.434
3146926FARMVIL
Solar/Wind Harmer
0.081
970223AG2-152 GEN
Solar/Wind Harmer
8.965
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3143226MDLTHAN
Solar/Wind Helper
0.285
316045AC1-158 PL2
Solar/Wind Helper
4.385
3147666LOUISA
Solar/Wind Helper
0.894
3151031BRUNSWICKG2
50/50
4.631
3151101ELIZAR3
50/50
28.615
3151161SURRY 1
50/50
8.552
970917AG2-570 GEN
Solar/Wind Harmer
29.876
315773AC2-141 GEN
Solar/Wind Harmer
11.469
944581AF1-123 GEN
Solar/Wind Harmer
67.537
944601AF1-125 GEN
Solar/Wind Harmer
66.496
3146456SLIGO L269
Solar/Wind Harmer
0.291
971153AH1-033 GEN
Solar/Wind Harmer
3.364
3144873MCLAUGH
Solar/Wind Harmer
0.007
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144536CHRHLND
Solar/Wind Harmer
0.041
316478AD1-087 GEN
Solar/Wind Harmer
0.967
316486AD2-202 GEN
Solar/Wind Harmer
0.284
3146376EDENTON
Solar/Wind Harmer
0.277
3145273HOLLAND
Solar/Wind Harmer
0.205
315614AA2-178 GEN
Solar/Wind Harmer
1.556
971157AH1-035 GEN
Solar/Wind Harmer
3.215
315737AD1-076 GEN
Solar/Wind Harmer
3.437
3146206CASHIE
Solar/Wind Harmer
0.264
316365GEN2_N
Solar/Wind Harmer
0.591
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.261
3156021HOLLOMANSOL
Solar/Wind Harmer
1.186
957521AF2-046 GEN
Solar/Wind Harmer
19.425
961681AG1-008 GEN
Solar/Wind Harmer
19.425
3146173TUNIS
Solar/Wind Harmer
0.26
316463AE2-346 GEN
Solar/Wind Harmer
0.223
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.771
3146263WOODLND
Solar/Wind Harmer
0.257
3145963POPLR C
Solar/Wind Harmer
0.257
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.255
313506AB2-031 GEN
Solar/Wind Harmer
0.787
3145796HORNRTN
Solar/Wind Harmer
1.01
3145796HORNRTN
Solar/Wind Harmer
0.252
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.893
3145336SMITFLD
Solar/Wind Harmer
0.099
316210AC1-098 GEN
Solar/Wind Harmer
2.302
3147043LAWRENC
Solar/Wind Harmer
0.148
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
315724AD1-057 GEN
Solar/Wind Harmer
0.913
316327AA2-057 GEN
Solar/Wind Harmer
0.365
3146073TAR RVR
Solar/Wind Harmer
0.239
3146083TARBORO
Solar/Wind Harmer
0.239
3146233WITAKRS
Solar/Wind Harmer
1.197
3146233WITAKRS
Solar/Wind Harmer
0.162
970661AG2-428 GEN
Solar/Wind Harmer
5.046
3138543CONSLDL
Solar/Wind Harmer
0.157
961601AG1-000A GEN
Solar/Wind Harmer
16.749
3145543BTLEBRO
Solar/Wind Harmer
0.235
3145543BTLEBRO
Solar/Wind Harmer
0.235
971623AH1-311 GEN
Solar/Wind Harmer
0.471
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.402
3151221GRAVEL6
Adder
16.187
3151171GRAVELC
Adder
3.114
3144216WINCHST
Adder
0.839
316131AB2-060 GEN
Solar/Wind Harmer
0.698
3150921YORKTN3
Adder
5.575
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.432
964241AG1-285 GEN
Solar/Wind Harmer
14.377
315813AE1-149 C
Solar/Wind Harmer
11.28
961611AG1-000B GEN
Solar/Wind Harmer
5.505
316283AC2-100 C
Solar/Wind Harmer
0.403
315785AD2-033 C
Solar/Wind Harmer
1.667
970257AG2-171 GEN
Solar/Wind Harmer
6.434
971683AH1-343 GEN
Solar/Wind Harmer
7.298
959311AF2-222 GEN
Solar/Wind Harmer
17.616
970909AG2-566 GEN
Solar/Wind Harmer
2.061
963181AG1-167 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.578
3147133PAMPLIN
Solar/Wind Harmer
0.549
971193AH1-056 GEN
Solar/Wind Harmer
10.649
316382AG1-145 C
Solar/Wind Harmer
0.001
315778AD1-151 GEN
Solar/Wind Harmer
13.656
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.676
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
970129AG2-093 GEN
Solar/Wind Harmer
9.286
3146926FARMVIL
Solar/Wind Harmer
0.081
970133AG2-095 GEN
Solar/Wind Harmer
1.245
316156AD2-030 GEN
Solar/Wind Harmer
0.088
3141873WAN 176
Solar/Wind Harmer
2.112
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316044AC1-158 PL1
Solar/Wind Helper
1.37
316450AC1-158 RIC
Solar/Wind Helper
0.365
3147666LOUISA
Solar/Wind Helper
0.514
315244AE2-183_ST
50/50
10.216
963041AG1-153 GEN
50/50
9.378
3151081ELIZAR1
50/50
28.253
3151091ELIZAR2
50/50
27.762
941591AE2-156 GEN
50/50
25.74
3152611GOSPORTB
50/50
3.904
3152621GOSPORTC
50/50
3.313
3152601GOSPORTA
50/50
3.057
972263AH1-716 GEN
50/50
164.489
315779AE2-040
50/50
3.913
941031AE2-094 GEN
Solar/Wind Harmer
68.4
944011AF1-069 GEN
Solar/Wind Harmer
22.349
970673AG2-436 GEN
Solar/Wind Harmer
77.293
970673AG2-436 GEN
Solar/Wind Harmer
51.529
971967AH1-528 GEN
Solar/Wind Harmer
56.362
970085AG2-068 GEN
Solar/Wind Harmer
17.833
970581AG2-369 GEN
Solar/Wind Harmer
15.337
957871AF2-081 GEN
Solar/Wind Harmer
14.522
319010AE1-072 C
Solar/Wind Harmer
1.465
3146406KITTY HAWK
Solar/Wind Harmer
0.036
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
316305AF2-043 C
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.285
3146486SUNBURY
Solar/Wind Harmer
0.285
316315AB2-025 C
Solar/Wind Harmer
0.227
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315814AE2-033 C
Solar/Wind Harmer
22.11
315835AF2-110_GEN
Solar/Wind Harmer
1.906
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
315816AE2-034 GEN
Solar/Wind Harmer
1.167
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.535
315733AD1-074 GEN2
Solar/Wind Harmer
1.535
315735AD1-075 GEN1
Solar/Wind Harmer
0.768
3146206CASHIE
Solar/Wind Harmer
0.264
970601AG2-382 GEN
Solar/Wind Harmer
9.883
965291AG1-394 GEN
Solar/Wind Harmer
1.166
3145893MURPHYS
Solar/Wind Harmer
0.705
3145893MURPHYS
Solar/Wind Harmer
0.261
3145513AHOSKIE
Solar/Wind Harmer
0.543
3145513AHOSKIE
Solar/Wind Harmer
0.26
316311AC2-079 GEN
Solar/Wind Harmer
7.457
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.178
3145683EARLEYS
Solar/Wind Harmer
0.518
3145683EARLEYS
Solar/Wind Harmer
0.259
3145683EARLEYS
Solar/Wind Harmer
0.259
3146043SEABORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.525
315652AC1-086 GEN
Solar/Wind Harmer
28.1
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3137643SOCKMAN
Solar/Wind Harmer
1.014
3145796HORNRTN
Solar/Wind Harmer
0.808
3145796HORNRTN
Solar/Wind Harmer
0.101
3146033SCOT NK
Solar/Wind Harmer
1.005
971445AH1-216 GEN
Solar/Wind Harmer
17.313
970831AG2-522 GEN
Solar/Wind Harmer
10.467
316005AA1-067
Solar/Wind Harmer
0.262
3145746EVERETS
Solar/Wind Harmer
0.972
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.244
970181AG2-120 GEN
Solar/Wind Harmer
3.041
957861AF2-080 GEN
Solar/Wind Harmer
10.405
316420AA1-050 GEN
Solar/Wind Harmer
0.008
3145573BETHELC
Solar/Wind Harmer
0.239
3145573BETHELC
Solar/Wind Harmer
0.239
316319Z2-044 C
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
3143316POE
Solar/Wind Harmer
0.886
972265AH1-717 GEN
Adder
17.287
3151201GRAVEL4
Adder
16.205
3151191GRAVEL3
Adder
16
3151211GRAVEL5
Adder
16
316118AC1-105 GEN
Solar/Wind Harmer
0.572
3147173SINAI
Solar/Wind Harmer
0.221
3147243WELCO
Solar/Wind Harmer
0.138
971443AH1-215 GEN
Solar/Wind Harmer
3.393
3144303KENBRDG
Solar/Wind Harmer
0.161
970683AG2-441 GEN
Solar/Wind Harmer
12.733
970681AG2-440 GEN
Solar/Wind Harmer
10.187
970865AG2-541 GEN
Solar/Wind Harmer
6.495
946301AF1-294 GEN
Solar/Wind Harmer
3.582
961791AG1-021 GEN
Solar/Wind Harmer
1.742
316369SG1_INVT
Solar/Wind Harmer
0.007
315657AE1-056 GEN
Solar/Wind Harmer
6.032
3138283WHITEMARSH
Solar/Wind Harmer
0.04
316123AC1-075 GEN
Solar/Wind Harmer
0.226
970165AG2-112 GEN
Solar/Wind Harmer
1.338
970163AG2-111 GEN
Solar/Wind Harmer
1.276
316132AB2-190 GEN1
Solar/Wind Harmer
0.837
3141873WAN 176
Solar/Wind Harmer
0.024
315662AE1-191 GEN
Solar/Wind Harmer
0.004
315666AE1-190 GEN
Solar/Wind Harmer
0.001
970533AG2-339 GEN
50/50
33.012
970531AG2-338 GEN
50/50
13.205
315242AE2-183_GT2
50/50
5.909
315241AE2-183_GT1
50/50
5.872
972185AH1-677 GEN
50/50
21.302
3151041BRUNSWICKG3
50/50
4.631
972187AH1-678 GEN
50/50
10.628
3150991CHESPKB
50/50
3.212
3150991CHESPKB
50/50
3.134
970933AG2-581 GEN
Solar/Wind Harmer
26.853
970099AG2-077 GEN
Solar/Wind Harmer
31.397
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.172
3145506HICKORY
Solar/Wind Harmer
0.703
3145506HICKORY
Solar/Wind Harmer
0.176
316339AD2-160 GEN
Solar/Wind Harmer
0.474
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.163
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.279
3137176SLIGO L2192
Solar/Wind Harmer
1.158
3146456SLIGO L269
Solar/Wind Harmer
5.15
3130086AYDLETT
Solar/Wind Harmer
1.162
316036AC1-147 C
Solar/Wind Harmer
0.054
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146516WINFALL
Solar/Wind Harmer
0.283
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
3144356SAPONY
Solar/Wind Harmer
2.345
3146376EDENTON
Solar/Wind Harmer
1.231
3146376EDENTON
Solar/Wind Harmer
1.231
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
12.23
3145893MURPHYS
Solar/Wind Harmer
1.749
3145893MURPHYS
Solar/Wind Harmer
0.47
3146173TUNIS
Solar/Wind Harmer
0.26
3146173TUNIS
Solar/Wind Harmer
0.26
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.256
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
316181AB2-040 GEN
Solar/Wind Harmer
0.37
316426AA2-053 GEN
Solar/Wind Harmer
0.859
3145593CAROLNA
Solar/Wind Harmer
0.253
3145593CAROLNA
Solar/Wind Harmer
0.253
966811AG1-552 GEN
Solar/Wind Harmer
2.746
3145593CAROLNA
Solar/Wind Harmer
0.315
3145796HORNRTN
Solar/Wind Harmer
0.757
3145783HORNRTN
Solar/Wind Harmer
4.484
3145783HORNRTN
Solar/Wind Harmer
3.587
3145783HORNRTN
Solar/Wind Harmer
1.121
3145783HORNRTN
Solar/Wind Harmer
0.448
3145933PARMELE
Solar/Wind Harmer
0.497
3145933PARMELE
Solar/Wind Harmer
0.248
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316274AC1-208 GEN
Solar/Wind Harmer
1.28
3145493TOT1
Solar/Wind Harmer
0.553
3145453TOT5
Solar/Wind Harmer
0.332
3145603CNETO
Solar/Wind Harmer
0.221
939181AE1-148 GEN
Solar/Wind Harmer
11.37
961601AG1-000A GEN
Solar/Wind Harmer
4.187
316263AC1-034 GEN
Solar/Wind Harmer
8.947
970657AG2-426 GEN
Solar/Wind Harmer
8.169
970657AG2-426 GEN
Solar/Wind Harmer
1.713
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
10.674
964791AG1-342 GEN
Solar/Wind Harmer
4.265
3146843MT LREL
Solar/Wind Harmer
0.222
3146843MT LREL
Solar/Wind Harmer
0.222
971741AH1-377 GEN
Solar/Wind Harmer
20.961
316222AC1-221 GEN
Solar/Wind Harmer
0.858
970323AG2-213 GEN
Solar/Wind Harmer
8.579
971775AH1-396 GEN
Solar/Wind Harmer
0.322
316034AC1-036 C
Solar/Wind Harmer
0.015
970301AG2-198 GEN
Solar/Wind Harmer
8.245
958211AF2-115 GEN
Solar/Wind Harmer
2.178
963191AG1-168 GEN
Solar/Wind Harmer
0.726
3144293JTRSVLE
Adder
0.578
3144293JTRSVLE
Adder
0.487
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.203
3147133PAMPLIN
Solar/Wind Harmer
0.175
3147133PAMPLIN
Solar/Wind Harmer
0.14
942751AE2-291 GEN
Solar/Wind Harmer
8.208
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
58.874
270013AE1-250 PV
Solar/Wind Harmer
0.004
316447AC1-158 HLD
Solar/Wind Helper
3.015
NYPJM->LTFIMP_NY
CLTF
2.482
LAGNLTFEXP_LAGN->PJM
CLTF
10.343
LGEELTFEXP_LGEE->PJM
CLTF
1.68
WECLTFEXP_WEC->PJM
CLTF
0.862
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.715
TVALTFEXP_TVA->PJM
CLTF
5.16
CPLELTFEXP_CPLE->PJM
CLTF
15.827
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.541
MECLTFEXP_MEC->PJM
CLTF
4.755
SIGELTFEXP_SIGE->PJM
CLTF
0.141

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.65 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5068.75
MW Contribution:19.91
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
10.046
963041AG1-153 GEN
50/50
9.229
315779AE2-040
50/50
4.019
3151541CLOVER2
50/50
5.903
3151081ELIZAR1
50/50
26.625
941031AE2-094 GEN
Solar/Wind Harmer
76.807
944011AF1-069 GEN
Solar/Wind Harmer
24.066
970673AG2-436 GEN
Solar/Wind Harmer
84.048
970673AG2-436 GEN
Solar/Wind Harmer
42.556
971967AH1-528 GEN
Solar/Wind Harmer
73.252
970085AG2-068 GEN
Solar/Wind Harmer
23.153
970581AG2-369 GEN
Solar/Wind Harmer
19.912
316315AB2-025 C
Solar/Wind Harmer
0.873
315814AE2-033 C
Solar/Wind Harmer
30.01
957871AF2-081 GEN
Solar/Wind Harmer
15.436
319010AE1-072 C
Solar/Wind Harmer
6.231
3146406KITTY HAWK
Solar/Wind Harmer
0.026
3151091ELIZAR2
Adder
24.656
3152611GOSPORTB
Adder
3.473
3152621GOSPORTC
Adder
2.948
3152601GOSPORTA
Adder
2.719
313526AB2-022
Solar/Wind Harmer
0.825
316305AF2-043 C
Solar/Wind Harmer
0.92
316321Z2-027
Solar/Wind Harmer
0.822
3146396TANGLEW
Solar/Wind Harmer
0.561
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315611Z1-036_GEN2
Solar/Wind Harmer
7.417
315835AF2-110_GEN
Solar/Wind Harmer
3.752
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
315816AE2-034 GEN
Solar/Wind Harmer
2.381
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.881
315733AD1-074 GEN2
Solar/Wind Harmer
5.881
315735AD1-075 GEN1
Solar/Wind Harmer
2.941
946281AF1-292 GEN
Solar/Wind Harmer
0.651
965291AG1-394 GEN
Solar/Wind Harmer
2.57
316311AC2-079 GEN
Solar/Wind Harmer
14.59
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.655
315833AF1-017_GEN
Solar/Wind Harmer
5.49
316349AD2-085 GEN
Solar/Wind Harmer
2.571
316087AB2-174 GEN
Solar/Wind Harmer
4.115
316318V4-068
Solar/Wind Harmer
0.719
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.341
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.215
3145513AHOSKIE
Solar/Wind Harmer
-0.029
3146043SEABORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.891
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
3137643SOCKMAN
Solar/Wind Harmer
-0.114
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.111
970831AG2-522 GEN
Solar/Wind Harmer
13.829
3143316POE
Solar/Wind Harmer
-0.109
971445AH1-216 GEN
Solar/Wind Harmer
16.968
316005AA1-067
Solar/Wind Harmer
0.549
3145746EVERETS
Solar/Wind Harmer
-0.107
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.56
957861AF2-080 GEN
Solar/Wind Harmer
11.769
316420AA1-050 GEN
Solar/Wind Harmer
3.06
316319Z2-044 C
Solar/Wind Harmer
1.479
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
972265AH1-717 GEN
Adder
17.747
3151201GRAVEL4
Adder
16.636
3151191GRAVEL3
Adder
16.426
3151211GRAVEL5
Adder
16.426
316239AB2-077_GEN
Solar/Wind Harmer
0.772
316238AB2-078_GEN
Solar/Wind Harmer
0.772
316118AC1-105 GEN
Solar/Wind Harmer
1.739
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.598
3144303KENBRDG
Solar/Wind Harmer
-0.019
316369SG1_INVT
Solar/Wind Harmer
4.063
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
316164AC1-076 GEN
Solar/Wind Helper
1.186
970683AG2-441 GEN
Solar/Wind Harmer
2.176
970681AG2-440 GEN
Solar/Wind Harmer
1.741
3151031BRUNSWICKG2
50/50
4.558
970413AG2-270 GEN
50/50
25.882
3151101ELIZAR3
50/50
26.966
970917AG2-570 GEN
Solar/Wind Harmer
93.072
315773AC2-141 GEN
Solar/Wind Harmer
13.388
944581AF1-123 GEN
Solar/Wind Harmer
143.09
944601AF1-125 GEN
Solar/Wind Harmer
140.857
316478AD1-087 GEN
Solar/Wind Harmer
2.694
316486AD2-202 GEN
Solar/Wind Harmer
0.789
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.757
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.792
316435W1029_GEN3
Solar/Wind Harmer
5.494
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
316365GEN2_N
Solar/Wind Harmer
2.02
3146376EDENTON
Solar/Wind Harmer
-0.03
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315614AA2-178 GEN
Solar/Wind Harmer
3.175
971157AH1-035 GEN
Solar/Wind Harmer
3.641
315737AD1-076 GEN
Solar/Wind Harmer
5.527
966621AG1-532 GEN
Solar/Wind Harmer
0.59
3156081AA2-088 GEN
Solar/Wind Harmer
9.415
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.687
961681AG1-008 GEN
Solar/Wind Harmer
22.687
313506AB2-031 GEN
Solar/Wind Harmer
2.311
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.868
316463AE2-346 GEN
Solar/Wind Harmer
0.464
316140AB2-099
Solar/Wind Harmer
0.193
962331AG1-082 GEN
Solar/Wind Harmer
3.582
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.333
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.017
316210AC1-098 GEN
Solar/Wind Harmer
4.347
970661AG2-428 GEN
Solar/Wind Harmer
5.205
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.433
315724AD1-057 GEN
Solar/Wind Harmer
1.573
316083AB2-161 GEN
Solar/Wind Harmer
4.404
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.736
970659AG2-427 GEN
Solar/Wind Harmer
2.538
3146233WITAKRS
Solar/Wind Harmer
0.56
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.018
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
961601AG1-000A GEN
Solar/Wind Harmer
10.535
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
16.256
3151221GRAVEL6
Adder
16.617
3151171GRAVELC
Adder
3.197
316131AB2-060 GEN
Solar/Wind Harmer
2.74
316248AF1-058 C
Solar/Wind Harmer
0.76
960061AF2-297 GEN
Solar/Wind Harmer
12.605
3144216WINCHST
Adder
0.839
3150921YORKTN3
Adder
5.559
964241AG1-285 GEN
Solar/Wind Harmer
19.332
961611AG1-000B GEN
Solar/Wind Harmer
5.168
315785AD2-033 C
Solar/Wind Harmer
5.364
316283AC2-100 C
Solar/Wind Harmer
2.209
970257AG2-171 GEN
Solar/Wind Harmer
8.725
959311AF2-222 GEN
Solar/Wind Harmer
23.978
971683AH1-343 GEN
Solar/Wind Harmer
9.859
315839AE2-212 C
Solar/Wind Harmer
0.685
970909AG2-566 GEN
Solar/Wind Harmer
2.14
3144293JTRSVLE
Adder
0.603
3141843SHACKLE
Adder
0.78
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
3150351NORNECKC2
Adder
1.171
316044AC1-158 PL1
Solar/Wind Helper
1.651
316450AC1-158 RIC
Solar/Wind Helper
0.44
3147666LOUISA
Solar/Wind Helper
0.583
316170AC1-121 GEN2
Solar/Wind Helper
0.349
970533AG2-339 GEN
50/50
32.408
970531AG2-338 GEN
50/50
12.963
315242AE2-183_GT2
50/50
5.81
315241AE2-183_GT1
50/50
5.775
972185AH1-677 GEN
50/50
20.947
3151041BRUNSWICKG3
50/50
4.558
972187AH1-678 GEN
50/50
10.459
970933AG2-581 GEN
Solar/Wind Harmer
34.906
970099AG2-077 GEN
Solar/Wind Harmer
41.151
3144356SAPONY
Solar/Wind Harmer
1.128
316185AD1-033 GEN
Solar/Wind Harmer
3.27
3145506HICKORY
Solar/Wind Harmer
-0.123
3145506HICKORY
Solar/Wind Harmer
-0.074
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.083
316018AA1-139 ULT2
Solar/Wind Harmer
2.645
316017AA1-139 ULT1
Solar/Wind Harmer
2.498
3142956BIRDNECK
Solar/Wind Harmer
1.655
3137176SLIGO L2192
Solar/Wind Harmer
-0.122
3146456SLIGO L269
Solar/Wind Harmer
3.64
316316AC1-027 C
Solar/Wind Harmer
0.946
3130086AYDLETT
Solar/Wind Harmer
-0.123
316036AC1-147 C
Solar/Wind Harmer
0.827
3150991CHESPKB
Adder
2.857
3150991CHESPKB
Adder
2.788
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.494
316433W1029_GEN2
Solar/Wind Harmer
5.494
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
0.884
3146376EDENTON
Solar/Wind Harmer
0.884
315742AE1-103 GEN
Solar/Wind Harmer
3.09
316065AD1-022 GEN
Solar/Wind Harmer
14.49
3145893MURPHYS
Solar/Wind Harmer
0.805
3145893MURPHYS
Solar/Wind Harmer
-0.052
316181AB2-040 GEN
Solar/Wind Harmer
4.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316426AA2-053 GEN
Solar/Wind Harmer
2.872
3145796HORNRTN
Solar/Wind Harmer
-0.085
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.194
3145593CAROLNA
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
3.355
3145783HORNRTN
Solar/Wind Harmer
2.684
3145783HORNRTN
Solar/Wind Harmer
0.839
3145783HORNRTN
Solar/Wind Harmer
0.335
316274AC1-208 GEN
Solar/Wind Harmer
2.979
316236AE1-162_GEN
Solar/Wind Harmer
0.832
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
8.539
970657AG2-426 GEN
Solar/Wind Harmer
1.786
939181AE1-148 GEN
Solar/Wind Harmer
15.107
3145493TOT1
Solar/Wind Harmer
0.413
3145453TOT5
Solar/Wind Harmer
0.248
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.403
316263AC1-034 GEN
Solar/Wind Harmer
12.4
313527AB2-043 GEN
Solar/Wind Harmer
4.152
962561AG1-105 GEN
Solar/Wind Harmer
14.279
964791AG1-342 GEN
Solar/Wind Harmer
5.416
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.356
316222AC1-221 GEN
Solar/Wind Harmer
2.385
970323AG2-213 GEN
Solar/Wind Harmer
11.633
971775AH1-396 GEN
Solar/Wind Harmer
1.657
316034AC1-036 C
Solar/Wind Harmer
0.431
316033AB2-134 GEN
Solar/Wind Harmer
7.334
315697AD1-025 GEN
Solar/Wind Harmer
4.6
970301AG2-198 GEN
Solar/Wind Harmer
11.27
3144293JTRSVLE
Adder
0.603
3144293JTRSVLE
Adder
0.508
944641AF1-129 GEN
Adder
79.37
3150341NORNECKC1
Adder
1.21
3150341NORNECKC1
Adder
1.2
316447AC1-158 HLD
Solar/Wind Helper
3.634
315651AD1-115 GEN
Solar/Wind Helper
0.76
315243AE2-183_GT3
50/50
5.81
3151051BRUNSWICKS1
50/50
9.459
3151021BRUNSWICKG1
50/50
4.558
971451AH1-221 GEN
50/50
13.843
3151531CLOVER1
50/50
5.931
940641AE2-051 GEN
Solar/Wind Harmer
38.323
939411AE1-173 GEN
Solar/Wind Harmer
192.154
970919AG2-571 GEN
Solar/Wind Harmer
11.781
970087AG2-069 GEN
Solar/Wind Harmer
34.73
957481AF2-042 GEN
Solar/Wind Harmer
102.878
316294AC1-161 GEN
Solar/Wind Harmer
10.352
944591AF1-124 GEN
Solar/Wind Harmer
143.606
316388AE2-253 GEN
Solar/Wind Harmer
2.083
3146456SLIGO L269
Solar/Wind Harmer
-0.031
316375AC2-012 GEN
Solar/Wind Harmer
10.604
3150981CHESPKA
Adder
3.405
315693AD1-088 GEN
Solar/Wind Harmer
15.307
316246AF1-032 C
Solar/Wind Harmer
0.618
3146516WINFALL
Solar/Wind Harmer
-0.098
3146516WINFALL
Solar/Wind Harmer
-0.03
962491AG1-098 GEN
Solar/Wind Harmer
20.194
315800Z1-036_GEN1
Solar/Wind Harmer
7.417
316093AE2-104_GEN
Solar/Wind Harmer
8.728
316023GEN1_S
Solar/Wind Harmer
2.02
3130156CHOWAN
Solar/Wind Harmer
-0.03
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.585
316072AD1-144
Solar/Wind Harmer
0.593
315687AD1-152 GEN
Solar/Wind Harmer
3.505
960081AF2-299 GEN
Solar/Wind Harmer
3.27
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.231
3145893MURPHYS
Solar/Wind Harmer
-0.115
3145893MURPHYS
Solar/Wind Harmer
0.856
316011AB1-132 GEN
Solar/Wind Harmer
6.015
962571AG1-106 GEN
Solar/Wind Harmer
4.132
3146173TUNIS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.349
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
971795AH1-408 GEN
Solar/Wind Harmer
21.251
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.328
3147043LAWRENC
Adder
2.254
316212AC1-099_GEN
Solar/Wind Harmer
2.415
970661AG2-428 GEN
Solar/Wind Harmer
29.373
3145336SMITFLD
Solar/Wind Harmer
-0.11
316129AC1-054 GEN
Solar/Wind Harmer
2.418
971065AG2-659 GEN
Solar/Wind Harmer
13.753
3146293MARTNCO
Solar/Wind Harmer
0.17
315722AD1-056 GEN
Solar/Wind Harmer
2.859
316381AD1-082 GEN
Solar/Wind Harmer
2.488
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970659AG2-427 GEN
Solar/Wind Harmer
14.32
316494AC1-189 GEN
Solar/Wind Harmer
2.894
3146233WITAKRS
Solar/Wind Harmer
-0.106
961671AG1-007 GEN
Solar/Wind Harmer
0.338
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.792
316359AB2-059 GEN
Solar/Wind Harmer
3.567
316049AB1-081 GEN
Solar/Wind Harmer
2.854
3142053HEARTS
Solar/Wind Harmer
0.311
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3151171GRAVELC
Adder
2.431
316237AB2-079_GEN
Solar/Wind Harmer
0.772
970401AG2-262 GEN
Solar/Wind Harmer
1.655
3138126ROCKLANDING
Solar/Wind Harmer
0.076
961611AG1-000B GEN
Solar/Wind Harmer
12.112
316003AC1-222 GEN
Solar/Wind Harmer
2.339
971647AH1-324 GEN
Solar/Wind Harmer
11.817
971317AH1-138 GEN
Solar/Wind Harmer
2.931
970685AG2-442 GEN
Solar/Wind Harmer
19.464
3144293JTRSVLE
Adder
0.603
3141843SHACKLE
Adder
0.78
3142433PROV 92
Adder
0.277
3142433PROV 92
Adder
0.277
944631AF1-128 GEN
Adder
63.787
3150351NORNECKC2
Adder
1.152
316045AC1-158 PL2
Solar/Wind Helper
5.286
3147666LOUISA
Solar/Wind Helper
1.014
316192AB2-158 GEN
Solar/Wind Helper
1.677
316254AC1-120 GEN1
Solar/Wind Helper
1.048
NYPJM->LTFIMP_NY
CLTF
2.897
LAGNLTFEXP_LAGN->PJM
CLTF
11.324
LGEELTFEXP_LGEE->PJM
CLTF
2.011
WECLTFEXP_WEC->PJM
CLTF
1.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.876
TVALTFEXP_TVA->PJM
CLTF
5.674
CPLELTFEXP_CPLE->PJM
CLTF
16.076
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.809
CBM West 1LTFEXP_CBM-W1->PJM
CBM
35.878
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.45
MECLTFEXP_MEC->PJM
CLTF
5.512
SIGELTFEXP_SIGE->PJM
CLTF
0.166

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5058.27
MW Contribution:19.8
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
9.99
963041AG1-153 GEN
50/50
9.178
315779AE2-040
50/50
3.975
3151541CLOVER2
50/50
5.868
3151081ELIZAR1
50/50
26.417
941031AE2-094 GEN
Solar/Wind Harmer
76.384
944011AF1-069 GEN
Solar/Wind Harmer
23.934
970673AG2-436 GEN
Solar/Wind Harmer
83.585
970673AG2-436 GEN
Solar/Wind Harmer
42.321
971967AH1-528 GEN
Solar/Wind Harmer
72.843
970085AG2-068 GEN
Solar/Wind Harmer
23.025
970581AG2-369 GEN
Solar/Wind Harmer
19.802
316315AB2-025 C
Solar/Wind Harmer
0.863
315814AE2-033 C
Solar/Wind Harmer
29.689
957871AF2-081 GEN
Solar/Wind Harmer
15.319
319010AE1-072 C
Solar/Wind Harmer
6.184
3146406KITTY HAWK
Solar/Wind Harmer
0.025
3151091ELIZAR2
Adder
24.463
3152611GOSPORTB
Adder
3.446
3152621GOSPORTC
Adder
2.924
3152601GOSPORTA
Adder
2.697
313526AB2-022
Solar/Wind Harmer
0.819
316305AF2-043 C
Solar/Wind Harmer
0.913
316321Z2-027
Solar/Wind Harmer
0.816
3146396TANGLEW
Solar/Wind Harmer
0.557
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.03
3146486SUNBURY
Solar/Wind Harmer
-0.03
315611Z1-036_GEN2
Solar/Wind Harmer
7.359
315835AF2-110_GEN
Solar/Wind Harmer
3.719
3130156CHOWAN
Solar/Wind Harmer
-0.029
3130156CHOWAN
Solar/Wind Harmer
-0.029
315816AE2-034 GEN
Solar/Wind Harmer
2.363
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
315732AD1-074 GEN1
Solar/Wind Harmer
5.835
315733AD1-074 GEN2
Solar/Wind Harmer
5.835
315735AD1-075 GEN1
Solar/Wind Harmer
2.918
946281AF1-292 GEN
Solar/Wind Harmer
0.645
965291AG1-394 GEN
Solar/Wind Harmer
2.549
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.557
316318V4-068
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.077
3145893MURPHYS
Solar/Wind Harmer
-0.029
316311AC2-079 GEN
Solar/Wind Harmer
14.429
316087AB2-174 GEN
Solar/Wind Harmer
4.08
315833AF1-017_GEN
Solar/Wind Harmer
5.429
316349AD2-085 GEN
Solar/Wind Harmer
2.542
315652AC1-086 GEN
Solar/Wind Harmer
32.069
3145513AHOSKIE
Solar/Wind Harmer
0.248
961941AG1-037 GEN
Solar/Wind Harmer
0.214
3145513AHOSKIE
Solar/Wind Harmer
-0.028
3146043SEABORD
Solar/Wind Harmer
-0.028
315607AA1-063A GEN
Solar/Wind Harmer
2.867
3145683EARLEYS
Solar/Wind Harmer
-0.056
3145683EARLEYS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3137643SOCKMAN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.11
970831AG2-522 GEN
Solar/Wind Harmer
13.728
3143316POE
Solar/Wind Harmer
-0.107
971445AH1-216 GEN
Solar/Wind Harmer
16.766
316005AA1-067
Solar/Wind Harmer
0.545
3145746EVERETS
Solar/Wind Harmer
-0.107
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.535
957861AF2-080 GEN
Solar/Wind Harmer
11.684
316420AA1-050 GEN
Solar/Wind Harmer
3.038
316319Z2-044 C
Solar/Wind Harmer
1.468
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
316239AB2-077_GEN
Solar/Wind Harmer
0.767
316238AB2-078_GEN
Solar/Wind Harmer
0.767
972265AH1-717 GEN
Adder
17.492
3151201GRAVEL4
Adder
16.397
3151191GRAVEL3
Adder
16.19
3151211GRAVEL5
Adder
16.19
316118AC1-105 GEN
Solar/Wind Harmer
1.728
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.563
3144303KENBRDG
Solar/Wind Harmer
-0.018
316369SG1_INVT
Solar/Wind Harmer
3.979
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
316164AC1-076 GEN
Solar/Wind Helper
1.177
970683AG2-441 GEN
Solar/Wind Harmer
2.159
970681AG2-440 GEN
Solar/Wind Harmer
1.727
3151031BRUNSWICKG2
50/50
4.532
970413AG2-270 GEN
50/50
25.729
3151101ELIZAR3
50/50
26.755
970917AG2-570 GEN
Solar/Wind Harmer
92.559
315773AC2-141 GEN
Solar/Wind Harmer
13.31
944581AF1-123 GEN
Solar/Wind Harmer
142.072
944601AF1-125 GEN
Solar/Wind Harmer
139.855
316478AD1-087 GEN
Solar/Wind Harmer
2.678
316486AD2-202 GEN
Solar/Wind Harmer
0.784
3146456SLIGO L269
Solar/Wind Harmer
-0.03
971153AH1-033 GEN
Solar/Wind Harmer
3.729
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.779
316435W1029_GEN3
Solar/Wind Harmer
5.451
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
316365GEN2_N
Solar/Wind Harmer
2.001
3146376EDENTON
Solar/Wind Harmer
-0.029
3144536CHRHLND
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.022
315614AA2-178 GEN
Solar/Wind Harmer
3.15
971157AH1-035 GEN
Solar/Wind Harmer
3.613
315737AD1-076 GEN
Solar/Wind Harmer
5.484
966621AG1-532 GEN
Solar/Wind Harmer
0.585
3156081AA2-088 GEN
Solar/Wind Harmer
9.337
3146206CASHIE
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.2
3145893MURPHYS
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.503
961681AG1-008 GEN
Solar/Wind Harmer
22.503
313506AB2-031 GEN
Solar/Wind Harmer
2.291
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3156021HOLLOMANSOL
Solar/Wind Harmer
3.838
316463AE2-346 GEN
Solar/Wind Harmer
0.46
316140AB2-099
Solar/Wind Harmer
0.192
962331AG1-082 GEN
Solar/Wind Harmer
3.554
3146263WOODLND
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
316317KELFORD C
Solar/Wind Harmer
1.323
3145823KELFORD
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3147043LAWRENC
Solar/Wind Harmer
-0.016
316210AC1-098 GEN
Solar/Wind Harmer
4.313
3145336SMITFLD
Solar/Wind Harmer
-0.011
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.408
970661AG2-428 GEN
Solar/Wind Harmer
5.132
315724AD1-057 GEN
Solar/Wind Harmer
1.561
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316327AA2-057 GEN
Solar/Wind Harmer
2.715
316083AB2-161 GEN
Solar/Wind Harmer
4.337
3146233WITAKRS
Solar/Wind Harmer
0.556
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
970659AG2-427 GEN
Solar/Wind Harmer
2.498
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
961601AG1-000A GEN
Solar/Wind Harmer
10.46
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
315813AE1-149 C
Solar/Wind Harmer
15.961
3151221GRAVEL6
Adder
16.378
3151171GRAVELC
Adder
3.151
316131AB2-060 GEN
Solar/Wind Harmer
2.721
316248AF1-058 C
Solar/Wind Harmer
0.755
960061AF2-297 GEN
Solar/Wind Harmer
12.532
3144216WINCHST
Adder
0.828
964241AG1-285 GEN
Solar/Wind Harmer
19.192
3150921YORKTN3
Adder
5.492
961611AG1-000B GEN
Solar/Wind Harmer
5.082
315785AD2-033 C
Solar/Wind Harmer
5.324
316283AC2-100 C
Solar/Wind Harmer
2.197
970257AG2-171 GEN
Solar/Wind Harmer
8.658
959311AF2-222 GEN
Solar/Wind Harmer
23.794
971683AH1-343 GEN
Solar/Wind Harmer
9.806
970909AG2-566 GEN
Solar/Wind Harmer
2.123
315839AE2-212 C
Solar/Wind Harmer
0.667
3144293JTRSVLE
Adder
0.598
3141843SHACKLE
Adder
0.757
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
316044AC1-158 PL1
Solar/Wind Helper
1.641
316450AC1-158 RIC
Solar/Wind Helper
0.438
3147666LOUISA
Solar/Wind Helper
0.579
316170AC1-121 GEN2
Solar/Wind Helper
0.347
970533AG2-339 GEN
50/50
32.23
970531AG2-338 GEN
50/50
12.892
315242AE2-183_GT2
50/50
5.778
315241AE2-183_GT1
50/50
5.743
972185AH1-677 GEN
50/50
20.831
3151041BRUNSWICKG3
50/50
4.532
972187AH1-678 GEN
50/50
10.401
970933AG2-581 GEN
Solar/Wind Harmer
34.708
970099AG2-077 GEN
Solar/Wind Harmer
40.908
3144356SAPONY
Solar/Wind Harmer
1.116
316185AD1-033 GEN
Solar/Wind Harmer
3.245
3145506HICKORY
Solar/Wind Harmer
-0.122
3145506HICKORY
Solar/Wind Harmer
-0.073
3145506HICKORY
Solar/Wind Harmer
-0.018
316339AD2-160 GEN
Solar/Wind Harmer
2.068
316018AA1-139 ULT2
Solar/Wind Harmer
2.625
316017AA1-139 ULT1
Solar/Wind Harmer
2.479
3142956BIRDNECK
Solar/Wind Harmer
1.642
3137176SLIGO L2192
Solar/Wind Harmer
-0.121
3146456SLIGO L269
Solar/Wind Harmer
3.613
316316AC1-027 C
Solar/Wind Harmer
0.938
3130086AYDLETT
Solar/Wind Harmer
-0.122
316036AC1-147 C
Solar/Wind Harmer
0.82
3150991CHESPKB
Adder
2.834
3150991CHESPKB
Adder
2.766
3146386ELIZ CT
Solar/Wind Harmer
-0.03
316431W1029_GEN1
Solar/Wind Harmer
5.451
316433W1029_GEN2
Solar/Wind Harmer
5.451
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146516WINFALL
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.03
3146376EDENTON
Solar/Wind Harmer
0.877
3146376EDENTON
Solar/Wind Harmer
0.877
315742AE1-103 GEN
Solar/Wind Harmer
3.064
316065AD1-022 GEN
Solar/Wind Harmer
14.378
3145893MURPHYS
Solar/Wind Harmer
0.798
3145893MURPHYS
Solar/Wind Harmer
-0.051
316181AB2-040 GEN
Solar/Wind Harmer
3.977
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.849
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.169
3145593CAROLNA
Solar/Wind Harmer
0.234
3145783HORNRTN
Solar/Wind Harmer
3.328
3145783HORNRTN
Solar/Wind Harmer
2.662
3145783HORNRTN
Solar/Wind Harmer
0.832
3145783HORNRTN
Solar/Wind Harmer
0.333
316274AC1-208 GEN
Solar/Wind Harmer
2.956
316236AE1-162_GEN
Solar/Wind Harmer
0.822
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
970657AG2-426 GEN
Solar/Wind Harmer
8.413
970657AG2-426 GEN
Solar/Wind Harmer
1.759
939181AE1-148 GEN
Solar/Wind Harmer
15.005
3145493TOT1
Solar/Wind Harmer
0.41
3145453TOT5
Solar/Wind Harmer
0.246
3145603CNETO
Solar/Wind Harmer
0.164
961601AG1-000A GEN
Solar/Wind Harmer
10.329
316263AC1-034 GEN
Solar/Wind Harmer
12.313
313527AB2-043 GEN
Solar/Wind Harmer
4.123
962561AG1-105 GEN
Solar/Wind Harmer
14.187
964791AG1-342 GEN
Solar/Wind Harmer
5.382
3146843MT LREL
Solar/Wind Harmer
-0.025
3146843MT LREL
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.148
316222AC1-221 GEN
Solar/Wind Harmer
2.372
970323AG2-213 GEN
Solar/Wind Harmer
11.545
971775AH1-396 GEN
Solar/Wind Harmer
1.644
316034AC1-036 C
Solar/Wind Harmer
0.428
970301AG2-198 GEN
Solar/Wind Harmer
11.182
316033AB2-134 GEN
Solar/Wind Harmer
7.183
315697AD1-025 GEN
Solar/Wind Harmer
4.505
3144293JTRSVLE
Adder
0.598
3144293JTRSVLE
Adder
0.504
944641AF1-129 GEN
Adder
76.466
316447AC1-158 HLD
Solar/Wind Helper
3.611
315651AD1-115 GEN
Solar/Wind Helper
0.755
315243AE2-183_GT3
50/50
5.778
3151051BRUNSWICKS1
50/50
9.407
3151021BRUNSWICKG1
50/50
4.532
971451AH1-221 GEN
50/50
13.766
3151531CLOVER1
50/50
5.896
940641AE2-051 GEN
Solar/Wind Harmer
38.111
939411AE1-173 GEN
Solar/Wind Harmer
191.017
970919AG2-571 GEN
Solar/Wind Harmer
11.716
970087AG2-069 GEN
Solar/Wind Harmer
34.538
957481AF2-042 GEN
Solar/Wind Harmer
102.271
316294AC1-161 GEN
Solar/Wind Harmer
10.291
944591AF1-124 GEN
Solar/Wind Harmer
142.584
316388AE2-253 GEN
Solar/Wind Harmer
2.068
3146456SLIGO L269
Solar/Wind Harmer
-0.03
315693AD1-088 GEN
Solar/Wind Harmer
15.212
316375AC2-012 GEN
Solar/Wind Harmer
10.52
3150981CHESPKA
Adder
3.378
316246AF1-032 C
Solar/Wind Harmer
0.613
3146516WINFALL
Solar/Wind Harmer
-0.097
3146516WINFALL
Solar/Wind Harmer
-0.03
962491AG1-098 GEN
Solar/Wind Harmer
20.067
315800Z1-036_GEN1
Solar/Wind Harmer
7.359
316093AE2-104_GEN
Solar/Wind Harmer
8.651
316023GEN1_S
Solar/Wind Harmer
2.001
3130156CHOWAN
Solar/Wind Harmer
-0.029
3145663CRESWEL
Solar/Wind Harmer
-0.081
971163AH1-040 GEN
Solar/Wind Harmer
27.372
316072AD1-144
Solar/Wind Harmer
0.588
315687AD1-152 GEN
Solar/Wind Harmer
3.484
960081AF2-299 GEN
Solar/Wind Harmer
3.241
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.175
3145893MURPHYS
Solar/Wind Harmer
-0.114
3145893MURPHYS
Solar/Wind Harmer
0.849
316011AB1-132 GEN
Solar/Wind Harmer
5.964
962571AG1-106 GEN
Solar/Wind Harmer
4.098
3146173TUNIS
Solar/Wind Harmer
-0.028
3145683EARLEYS
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
316190AA2-174 GEN
Solar/Wind Harmer
0.346
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.028
971795AH1-408 GEN
Solar/Wind Harmer
21.071
3145823KELFORD
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.295
3147043LAWRENC
Adder
2.236
316212AC1-099_GEN
Solar/Wind Harmer
2.396
316129AC1-054 GEN
Solar/Wind Harmer
2.4
971065AG2-659 GEN
Solar/Wind Harmer
13.655
3145336SMITFLD
Solar/Wind Harmer
-0.109
3146293MARTNCO
Solar/Wind Harmer
0.169
970661AG2-428 GEN
Solar/Wind Harmer
28.962
315722AD1-056 GEN
Solar/Wind Harmer
2.838
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316381AD1-082 GEN
Solar/Wind Harmer
2.45
316494AC1-189 GEN
Solar/Wind Harmer
2.873
3146233WITAKRS
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
14.096
961671AG1-007 GEN
Solar/Wind Harmer
0.335
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.787
316359AB2-059 GEN
Solar/Wind Harmer
3.541
316049AB1-081 GEN
Solar/Wind Harmer
2.834
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3142053HEARTS
Solar/Wind Harmer
0.309
316237AB2-079_GEN
Solar/Wind Harmer
0.767
3151171GRAVELC
Adder
2.396
970401AG2-262 GEN
Solar/Wind Harmer
1.644
3138126ROCKLANDING
Solar/Wind Harmer
0.075
961611AG1-000B GEN
Solar/Wind Harmer
11.911
316003AC1-222 GEN
Solar/Wind Harmer
2.326
971647AH1-324 GEN
Solar/Wind Harmer
11.598
971317AH1-138 GEN
Solar/Wind Harmer
2.891
970685AG2-442 GEN
Solar/Wind Harmer
19.311
3144293JTRSVLE
Adder
0.598
3141843SHACKLE
Adder
0.757
3142433PROV 92
Adder
0.267
3142433PROV 92
Adder
0.267
944631AF1-128 GEN
Adder
61.132
316045AC1-158 PL2
Solar/Wind Helper
5.253
3147666LOUISA
Solar/Wind Helper
1.007
316192AB2-158 GEN
Solar/Wind Helper
1.665
3143226MDLTHAN
Solar/Wind Helper
0.228
316254AC1-120 GEN1
Solar/Wind Helper
1.04
NYPJM->LTFIMP_NY
CLTF
2.883
LAGNLTFEXP_LAGN->PJM
CLTF
11.311
LGEELTFEXP_LGEE->PJM
CLTF
2.019
WECLTFEXP_WEC->PJM
CLTF
1.033
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.727
TVALTFEXP_TVA->PJM
CLTF
5.669
CPLELTFEXP_CPLE->PJM
CLTF
15.993
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.825
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.059
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.441
MECLTFEXP_MEC->PJM
CLTF
5.526
SIGELTFEXP_SIGE->PJM
CLTF
0.166

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P4-2: 56722_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56722_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5002.24
MW Contribution:20.9
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
6.113
3151051BRUNSWICKS1
50/50
9.945
3151021BRUNSWICKG1
50/50
4.792
971451AH1-221 GEN
50/50
14.554
3152331SURRY 2
50/50
13.051
3150981CHESPKA
50/50
4.073
940641AE2-051 GEN
Solar/Wind Harmer
41.064
939411AE1-173 GEN
Solar/Wind Harmer
208.234
970919AG2-571 GEN
Solar/Wind Harmer
12.367
970087AG2-069 GEN
Solar/Wind Harmer
36.449
316294AC1-161 GEN
Solar/Wind Harmer
12.074
944591AF1-124 GEN
Solar/Wind Harmer
163.155
316388AE2-253 GEN
Solar/Wind Harmer
2.349
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316375AC2-012 GEN
Solar/Wind Harmer
11.954
957481AF2-042 GEN
Solar/Wind Harmer
107.108
316246AF1-032 C
Solar/Wind Harmer
0.692
3146516WINFALL
Solar/Wind Harmer
-0.109
3146516WINFALL
Solar/Wind Harmer
-0.034
315800Z1-036_GEN1
Solar/Wind Harmer
8.233
316093AE2-104_GEN
Solar/Wind Harmer
9.655
3130156CHOWAN
Solar/Wind Harmer
-0.033
316072AD1-144
Solar/Wind Harmer
0.66
3145663CRESWEL
Solar/Wind Harmer
-0.09
971163AH1-040 GEN
Solar/Wind Harmer
30.289
315693AD1-088 GEN
Solar/Wind Harmer
15.85
3146206CASHIE
Solar/Wind Harmer
-0.031
971547AH1-271 GEN
Solar/Wind Harmer
7.851
962491AG1-098 GEN
Solar/Wind Harmer
20.887
316023GEN1_S
Solar/Wind Harmer
2.098
3145893MURPHYS
Solar/Wind Harmer
-0.123
3145893MURPHYS
Solar/Wind Harmer
0.919
3146173TUNIS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
316174AB2-169 GEN
Solar/Wind Harmer
4.66
960081AF2-299 GEN
Solar/Wind Harmer
3.399
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.12
316011AB1-132 GEN
Solar/Wind Harmer
6.31
962571AG1-106 GEN
Solar/Wind Harmer
4.335
315687AD1-152 GEN
Solar/Wind Harmer
3.624
316190AA2-174 GEN
Solar/Wind Harmer
0.369
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145783HORNRTN
Solar/Wind Harmer
-0.03
971795AH1-408 GEN
Solar/Wind Harmer
22.032
3146293MARTNCO
Solar/Wind Harmer
0.182
316212AC1-099_GEN
Solar/Wind Harmer
2.552
3147043LAWRENC
Adder
2.334
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970661AG2-428 GEN
Solar/Wind Harmer
30.611
316129AC1-054 GEN
Solar/Wind Harmer
2.516
315722AD1-056 GEN
Solar/Wind Harmer
2.994
315244AE2-183_ST
50/50
10.569
963041AG1-153 GEN
50/50
9.703
3151081ELIZAR1
50/50
30.049
3151091ELIZAR2
50/50
29.527
941591AE2-156 GEN
50/50
27.384
3152611GOSPORTB
50/50
4.154
3152621GOSPORTC
50/50
3.526
3152601GOSPORTA
50/50
3.252
972263AH1-716 GEN
50/50
176.402
315779AE2-040
50/50
4.113
941031AE2-094 GEN
Solar/Wind Harmer
80.926
944011AF1-069 GEN
Solar/Wind Harmer
25.357
970673AG2-436 GEN
Solar/Wind Harmer
88.471
970673AG2-436 GEN
Solar/Wind Harmer
44.796
971967AH1-528 GEN
Solar/Wind Harmer
76.994
970085AG2-068 GEN
Solar/Wind Harmer
24.3
970581AG2-369 GEN
Solar/Wind Harmer
20.898
957871AF2-081 GEN
Solar/Wind Harmer
17.4
319010AE1-072 C
Solar/Wind Harmer
7.017
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.925
316305AF2-043 C
Solar/Wind Harmer
1.03
316321Z2-027
Solar/Wind Harmer
0.921
3146396TANGLEW
Solar/Wind Harmer
0.628
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315611Z1-036_GEN2
Solar/Wind Harmer
8.233
315835AF2-110_GEN
Solar/Wind Harmer
4.151
316315AB2-025 C
Solar/Wind Harmer
0.893
315814AE2-033 C
Solar/Wind Harmer
30.736
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.614
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
315732AD1-074 GEN1
Solar/Wind Harmer
6.414
315733AD1-074 GEN2
Solar/Wind Harmer
6.414
315735AD1-075 GEN1
Solar/Wind Harmer
3.208
3146206CASHIE
Solar/Wind Harmer
-0.031
970601AG2-382 GEN
Solar/Wind Harmer
13.738
316311AC2-079 GEN
Solar/Wind Harmer
15.73
315833AF1-017_GEN
Solar/Wind Harmer
5.916
316349AD2-085 GEN
Solar/Wind Harmer
2.77
965291AG1-394 GEN
Solar/Wind Harmer
2.762
316318V4-068
Solar/Wind Harmer
0.772
3145893MURPHYS
Solar/Wind Harmer
-0.083
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.268
961941AG1-037 GEN
Solar/Wind Harmer
0.231
3145513AHOSKIE
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.061
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3146043SEABORD
Solar/Wind Harmer
-0.03
315607AA1-063A GEN
Solar/Wind Harmer
3.067
946281AF1-292 GEN
Solar/Wind Harmer
0.677
315652AC1-086 GEN
Solar/Wind Harmer
33.928
316087AB2-174 GEN
Solar/Wind Harmer
4.294
3137643SOCKMAN
Solar/Wind Harmer
-0.119
971445AH1-216 GEN
Solar/Wind Harmer
18.512
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.118
316005AA1-067
Solar/Wind Harmer
0.583
3145746EVERETS
Solar/Wind Harmer
-0.114
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970181AG2-120 GEN
Solar/Wind Harmer
3.785
970831AG2-522 GEN
Solar/Wind Harmer
14.404
957861AF2-080 GEN
Solar/Wind Harmer
12.444
316420AA1-050 GEN
Solar/Wind Harmer
3.227
3145573BETHELC
Solar/Wind Harmer
-0.028
3145573BETHELC
Solar/Wind Harmer
-0.028
316319Z2-044 C
Solar/Wind Harmer
1.551
972265AH1-717 GEN
Adder
18.943
3151201GRAVEL4
Adder
17.758
3151191GRAVEL3
Adder
17.533
3151211GRAVEL5
Adder
17.533
3143316POE
Solar/Wind Harmer
-0.106
316239AB2-077_GEN
Solar/Wind Harmer
0.792
316238AB2-078_GEN
Solar/Wind Harmer
0.792
316118AC1-105 GEN
Solar/Wind Harmer
1.779
3147173SINAI
Solar/Wind Harmer
-0.026
3147243WELCO
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
4.662
3144303KENBRDG
Solar/Wind Harmer
-0.019
316369SG1_INVT
Solar/Wind Harmer
4.072
971065AG2-659 GEN
Solar/Wind Harmer
14.295
316494AC1-189 GEN
Solar/Wind Harmer
3.06
961671AG1-007 GEN
Solar/Wind Harmer
0.355
3146083TARBORO
Solar/Wind Harmer
-0.028
3145493TOT1
Solar/Wind Harmer
0.834
3146233WITAKRS
Solar/Wind Harmer
-0.111
316381AD1-082 GEN
Solar/Wind Harmer
2.555
3138126ROCKLANDING
Solar/Wind Harmer
0.085
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.022
316359AB2-059 GEN
Solar/Wind Harmer
3.732
316049AB1-081 GEN
Solar/Wind Harmer
2.986
3142053HEARTS
Solar/Wind Harmer
0.325
970659AG2-427 GEN
Solar/Wind Harmer
14.627
3151171GRAVELC
Adder
2.595
316237AB2-079_GEN
Solar/Wind Harmer
0.792
970401AG2-262 GEN
Solar/Wind Harmer
1.694
971317AH1-138 GEN
Solar/Wind Harmer
3.236
961611AG1-000B GEN
Solar/Wind Harmer
12.645
316003AC1-222 GEN
Solar/Wind Harmer
2.377
971647AH1-324 GEN
Solar/Wind Harmer
12.098
316159AE1-175 C
Solar/Wind Harmer
0.615
970685AG2-442 GEN
Solar/Wind Harmer
19.615
3144293JTRSVLE
Adder
0.604
3141843SHACKLE
Adder
0.734
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
3143226MDLTHAN
Solar/Wind Helper
0.265
316045AC1-158 PL2
Solar/Wind Helper
4.474
3147666LOUISA
Solar/Wind Helper
0.911
316192AB2-158 GEN
Solar/Wind Helper
1.512
957831AF2-077 GEN
Solar/Wind Harmer
0.682
3138283WHITEMARSH
Solar/Wind Harmer
0.035
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
970683AG2-441 GEN
Solar/Wind Harmer
1.465
970681AG2-440 GEN
Solar/Wind Harmer
1.172
3151031BRUNSWICKG2
50/50
4.792
3151101ELIZAR3
50/50
30.433
3151161SURRY 1
50/50
9.371
970917AG2-570 GEN
Solar/Wind Harmer
97.699
315773AC2-141 GEN
Solar/Wind Harmer
15.616
944581AF1-123 GEN
Solar/Wind Harmer
162.57
944601AF1-125 GEN
Solar/Wind Harmer
160.033
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.232
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
2.01
316435W1029_GEN3
Solar/Wind Harmer
6.131
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3144536CHRHLND
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
3.486
316478AD1-087 GEN
Solar/Wind Harmer
2.796
316486AD2-202 GEN
Solar/Wind Harmer
0.819
971157AH1-035 GEN
Solar/Wind Harmer
3.976
315737AD1-076 GEN
Solar/Wind Harmer
6.028
3146206CASHIE
Solar/Wind Harmer
-0.031
3156081AA2-088 GEN
Solar/Wind Harmer
10.133
316365GEN2_N
Solar/Wind Harmer
2.098
3145893MURPHYS
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.031
3156021HOLLOMANSOL
Solar/Wind Harmer
4.17
957521AF2-046 GEN
Solar/Wind Harmer
24.369
961681AG1-008 GEN
Solar/Wind Harmer
24.369
3146173TUNIS
Solar/Wind Harmer
-0.031
316463AE2-346 GEN
Solar/Wind Harmer
0.498
316140AB2-099
Solar/Wind Harmer
0.207
962331AG1-082 GEN
Solar/Wind Harmer
3.846
3146263WOODLND
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
966621AG1-532 GEN
Solar/Wind Harmer
0.613
316317KELFORD C
Solar/Wind Harmer
1.423
3145823KELFORD
Solar/Wind Harmer
-0.03
3145336SMITFLD
Solar/Wind Harmer
-0.012
313506AB2-031 GEN
Solar/Wind Harmer
2.416
3145796HORNRTN
Solar/Wind Harmer
-0.119
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.029
966801AG1-551 GEN
Solar/Wind Harmer
3.667
316210AC1-098 GEN
Solar/Wind Harmer
4.594
3147043LAWRENC
Solar/Wind Harmer
-0.017
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970661AG2-428 GEN
Solar/Wind Harmer
5.425
315724AD1-057 GEN
Solar/Wind Harmer
1.647
316327AA2-057 GEN
Solar/Wind Harmer
2.874
3146073TAR RVR
Solar/Wind Harmer
-0.028
3146083TARBORO
Solar/Wind Harmer
-0.028
3146233WITAKRS
Solar/Wind Harmer
0.587
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.018
316083AB2-161 GEN
Solar/Wind Harmer
4.522
3144216WINCHST
Adder
0.934
3150921YORKTN3
Adder
6.222
961601AG1-000A GEN
Solar/Wind Harmer
11.023
3145543BTLEBRO
Solar/Wind Harmer
-0.028
3145543BTLEBRO
Solar/Wind Harmer
-0.028
970659AG2-427 GEN
Solar/Wind Harmer
2.592
3151221GRAVEL6
Adder
17.737
3151171GRAVELC
Adder
3.413
316131AB2-060 GEN
Solar/Wind Harmer
2.806
315813AE1-149 C
Solar/Wind Harmer
16.113
316248AF1-058 C
Solar/Wind Harmer
0.777
960061AF2-297 GEN
Solar/Wind Harmer
12.888
961611AG1-000B GEN
Solar/Wind Harmer
5.395
964241AG1-285 GEN
Solar/Wind Harmer
19.739
315785AD2-033 C
Solar/Wind Harmer
5.448
316283AC2-100 C
Solar/Wind Harmer
2.259
970257AG2-171 GEN
Solar/Wind Harmer
8.842
959311AF2-222 GEN
Solar/Wind Harmer
24.263
971683AH1-343 GEN
Solar/Wind Harmer
9.965
316382AG1-145 C
Solar/Wind Harmer
0.691
970909AG2-566 GEN
Solar/Wind Harmer
2.15
3144293JTRSVLE
Adder
0.604
3141843SHACKLE
Adder
0.734
3142433PROV 92
Adder
0.238
3142433PROV 92
Adder
0.238
316044AC1-158 PL1
Solar/Wind Helper
1.398
316450AC1-158 RIC
Solar/Wind Helper
0.373
3147666LOUISA
Solar/Wind Helper
0.524
970533AG2-339 GEN
50/50
34.146
970531AG2-338 GEN
50/50
13.658
315242AE2-183_GT2
50/50
6.113
315241AE2-183_GT1
50/50
6.075
972185AH1-677 GEN
50/50
22.038
3151041BRUNSWICKG3
50/50
4.792
972187AH1-678 GEN
50/50
10.997
3150991CHESPKB
50/50
3.417
3150991CHESPKB
50/50
3.335
970933AG2-581 GEN
Solar/Wind Harmer
36.6
316185AD1-033 GEN
Solar/Wind Harmer
3.695
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.349
3142956BIRDNECK
Solar/Wind Harmer
1.868
316018AA1-139 ULT2
Solar/Wind Harmer
2.981
316017AA1-139 ULT1
Solar/Wind Harmer
2.816
316316AC1-027 C
Solar/Wind Harmer
1.067
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.1
3130086AYDLETT
Solar/Wind Harmer
-0.138
316036AC1-147 C
Solar/Wind Harmer
0.932
3146386ELIZ CT
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.843
316431W1029_GEN1
Solar/Wind Harmer
6.131
316433W1029_GEN2
Solar/Wind Harmer
6.131
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3144356SAPONY
Solar/Wind Harmer
1.155
3146376EDENTON
Solar/Wind Harmer
0.978
3146376EDENTON
Solar/Wind Harmer
0.978
315742AE1-103 GEN
Solar/Wind Harmer
3.377
316065AD1-022 GEN
Solar/Wind Harmer
15.758
3145893MURPHYS
Solar/Wind Harmer
0.864
3145893MURPHYS
Solar/Wind Harmer
-0.056
3146173TUNIS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.03
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316236AE1-162_GEN
Solar/Wind Harmer
0.909
316181AB2-040 GEN
Solar/Wind Harmer
4.192
316426AA2-053 GEN
Solar/Wind Harmer
3.033
3145593CAROLNA
Solar/Wind Harmer
-0.03
3145593CAROLNA
Solar/Wind Harmer
-0.03
966811AG1-552 GEN
Solar/Wind Harmer
3.361
3145593CAROLNA
Solar/Wind Harmer
0.248
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145783HORNRTN
Solar/Wind Harmer
3.53
3145783HORNRTN
Solar/Wind Harmer
2.824
3145783HORNRTN
Solar/Wind Harmer
0.882
3145783HORNRTN
Solar/Wind Harmer
0.353
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
316274AC1-208 GEN
Solar/Wind Harmer
3.137
970657AG2-426 GEN
Solar/Wind Harmer
8.819
970657AG2-426 GEN
Solar/Wind Harmer
1.844
3145493TOT1
Solar/Wind Harmer
0.435
3145453TOT5
Solar/Wind Harmer
0.261
3145603CNETO
Solar/Wind Harmer
0.174
939181AE1-148 GEN
Solar/Wind Harmer
15.597
961601AG1-000A GEN
Solar/Wind Harmer
10.885
316263AC1-034 GEN
Solar/Wind Harmer
12.975
313527AB2-043 GEN
Solar/Wind Harmer
4.255
962561AG1-105 GEN
Solar/Wind Harmer
14.617
964791AG1-342 GEN
Solar/Wind Harmer
5.543
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
971741AH1-377 GEN
Solar/Wind Harmer
28.741
316222AC1-221 GEN
Solar/Wind Harmer
2.439
970323AG2-213 GEN
Solar/Wind Harmer
11.79
971775AH1-396 GEN
Solar/Wind Harmer
1.679
316034AC1-036 C
Solar/Wind Harmer
0.437
316033AB2-134 GEN
Solar/Wind Harmer
7.35
315697AD1-025 GEN
Solar/Wind Harmer
4.61
970301AG2-198 GEN
Solar/Wind Harmer
11.323
3144293JTRSVLE
Adder
0.604
3144293JTRSVLE
Adder
0.509
944641AF1-129 GEN
Adder
67.1
316447AC1-158 HLD
Solar/Wind Helper
3.076
NYPJM->LTFIMP_NY
CLTF
2.585
LAGNLTFEXP_LAGN->PJM
CLTF
10.628
LGEELTFEXP_LGEE->PJM
CLTF
1.702
WECLTFEXP_WEC->PJM
CLTF
0.872
CBM South 2LTFEXP_CBM-S2->PJM
CBM
34.911
TVALTFEXP_TVA->PJM
CLTF
5.301
CPLELTFEXP_CPLE->PJM
CLTF
16.426
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.71
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.133
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.997
MECLTFEXP_MEC->PJM
CLTF
4.839
SIGELTFEXP_SIGE->PJM
CLTF
0.143

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P2-2: BREMO B1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: BREMO B1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.3 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4267.15
MW Contribution:18.47
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
29.851
970531AG2-338 GEN
50/50
11.94
315242AE2-183_GT2
50/50
5.38
315241AE2-183_GT1
50/50
5.347
972185AH1-677 GEN
50/50
19.395
3151041BRUNSWICKG3
50/50
4.23
972187AH1-678 GEN
50/50
9.708
3144293JTRSVLE
50/50
0.895
3144293JTRSVLE
50/50
0.754
970535AG2-341 GEN
50/50
4.4
3152661PLYWOOD A
50/50
0.514
3151361ROSEMG1
50/50
0.809
3151371ROSEMS1
50/50
0.501
3151381ROSEMG2
50/50
0.379
970933AG2-581 GEN
Solar/Wind Harmer
33.334
970099AG2-077 GEN
Solar/Wind Harmer
41.293
971741AH1-377 GEN
Solar/Wind Harmer
37.414
970301AG2-198 GEN
Solar/Wind Harmer
16.032
3146776BUCKING
Solar/Wind Harmer
-0.126
3146776BUCKING
Solar/Wind Harmer
-0.01
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
958211AF2-115 GEN
Solar/Wind Harmer
4.654
963191AG1-168 GEN
Solar/Wind Harmer
2.792
316034AC1-036 C
Solar/Wind Harmer
0.538
970323AG2-213 GEN
Solar/Wind Harmer
14.493
971775AH1-396 GEN
Solar/Wind Harmer
2.064
313527AB2-043 GEN
Solar/Wind Harmer
4.56
3144356SAPONY
Solar/Wind Harmer
0.979
939181AE1-148 GEN
Solar/Wind Harmer
15.561
962561AG1-105 GEN
Solar/Wind Harmer
15.007
964791AG1-342 GEN
Solar/Wind Harmer
5.646
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.899
3145593CAROLNA
Solar/Wind Harmer
0.214
316426AA2-053 GEN
Solar/Wind Harmer
2.588
3145783HORNRTN
Solar/Wind Harmer
3.04
3145783HORNRTN
Solar/Wind Harmer
2.432
3145783HORNRTN
Solar/Wind Harmer
0.76
3145783HORNRTN
Solar/Wind Harmer
0.304
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.101
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.674
316339AD2-160 GEN
Solar/Wind Harmer
1.708
316018AA1-139 ULT2
Solar/Wind Harmer
2.169
316017AA1-139 ULT1
Solar/Wind Harmer
2.049
3137176SLIGO L2192
Solar/Wind Harmer
-0.1
3146456SLIGO L269
Solar/Wind Harmer
2.987
3130086AYDLETT
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.075
3146386ELIZ CT
Solar/Wind Harmer
-0.025
3142956BIRDNECK
Solar/Wind Harmer
1.35
316316AC1-027 C
Solar/Wind Harmer
0.771
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.542
316433W1029_GEN2
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.267
315742AE1-103 GEN
Solar/Wind Harmer
2.599
316274AC1-208 GEN
Solar/Wind Harmer
2.674
316065AD1-022 GEN
Solar/Wind Harmer
12.38
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.368
3145453TOT5
Solar/Wind Harmer
0.221
3145603CNETO
Solar/Wind Harmer
0.147
316263AC1-034 GEN
Solar/Wind Harmer
11.133
961601AG1-000A GEN
Solar/Wind Harmer
9.326
316222AC1-221 GEN
Solar/Wind Harmer
2.263
316447AC1-158 HLD
Solar/Wind Helper
2.916
3143526WINTERP
Solar/Wind Helper
1.191
3151031BRUNSWICKG2
50/50
4.23
970413AG2-270 GEN
50/50
26.203
3144293JTRSVLE
50/50
0.895
3151591KERR 2
50/50
0.508
3151261ROARAP2
50/50
0.279
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
970917AG2-570 GEN
Solar/Wind Harmer
86.33
970909AG2-566 GEN
Solar/Wind Harmer
3.044
3146926FARMVIL
Solar/Wind Harmer
-0.019
3146776BUCKING
Solar/Wind Harmer
-0.011
316478AD1-087 GEN
Solar/Wind Harmer
2.727
316486AD2-202 GEN
Solar/Wind Harmer
0.799
942461AE2-259 GEN
Solar/Wind Harmer
4.631
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.784
963181AG1-167 GEN
Solar/Wind Harmer
2.792
959311AF2-222 GEN
Solar/Wind Harmer
30.378
970257AG2-171 GEN
Solar/Wind Harmer
10.87
315785AD2-033 C
Solar/Wind Harmer
6.532
964241AG1-285 GEN
Solar/Wind Harmer
22.181
316131AB2-060 GEN
Solar/Wind Harmer
3.035
3147043LAWRENC
Solar/Wind Harmer
-0.016
966621AG1-532 GEN
Solar/Wind Harmer
0.54
316365GEN2_N
Solar/Wind Harmer
1.787
313506AB2-031 GEN
Solar/Wind Harmer
2.107
315773AC2-141 GEN
Solar/Wind Harmer
10.925
944581AF1-123 GEN
Solar/Wind Harmer
117.317
944601AF1-125 GEN
Solar/Wind Harmer
115.486
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.083
316248AF1-058 C
Solar/Wind Harmer
0.761
960061AF2-297 GEN
Solar/Wind Harmer
12.626
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
316320Y1-086
Solar/Wind Harmer
1.477
3156081AA2-088 GEN
Solar/Wind Harmer
8.171
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.748
961681AG1-008 GEN
Solar/Wind Harmer
19.748
316435W1029_GEN3
Solar/Wind Harmer
4.542
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3151101ELIZAR3
Adder
20.681
3146173TUNIS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.119
3146376EDENTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315614AA2-178 GEN
Solar/Wind Harmer
2.681
316317KELFORD C
Solar/Wind Harmer
1.17
3145823KELFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3156021HOLLOMANSOL
Solar/Wind Harmer
3.338
971157AH1-035 GEN
Solar/Wind Harmer
3.096
3146206CASHIE
Solar/Wind Harmer
-0.025
315737AD1-076 GEN
Solar/Wind Harmer
4.705
316210AC1-098 GEN
Solar/Wind Harmer
3.877
315724AD1-057 GEN
Solar/Wind Harmer
1.404
3145963POPLR C
Solar/Wind Harmer
-0.024
316327AA2-057 GEN
Solar/Wind Harmer
2.454
3146233WITAKRS
Solar/Wind Harmer
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.999
3138543CONSLDL
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.444
971683AH1-343 GEN
Solar/Wind Harmer
9.745
316283AC2-100 C
Solar/Wind Harmer
2.093
3151221GRAVEL6
Adder
12.505
3151171GRAVELC
Adder
2.406
3144216WINCHST
Adder
0.613
315243AE2-183_GT3
50/50
5.38
3151051BRUNSWICKS1
50/50
8.78
3151021BRUNSWICKG1
50/50
4.23
971451AH1-221 GEN
50/50
12.849
3151531CLOVER1
50/50
6.004
3144293JTRSVLE
50/50
0.895
3151601KERR 3
50/50
0.508
3151581KERR 1
50/50
0.181
3147043LAWRENC
50/50
2.311
3151261ROARAP2
50/50
0.286
3151391GASTONA
50/50
0.614
3151411GASTONB
50/50
0.614
940641AE2-051 GEN
Solar/Wind Harmer
34.524
970919AG2-571 GEN
Solar/Wind Harmer
10.928
970087AG2-069 GEN
Solar/Wind Harmer
32.211
939411AE1-173 GEN
Solar/Wind Harmer
169.915
957481AF2-042 GEN
Solar/Wind Harmer
103.233
315693AD1-088 GEN
Solar/Wind Harmer
16.294
962491AG1-098 GEN
Solar/Wind Harmer
21.776
3146926FARMVIL
Solar/Wind Harmer
-0.019
316322AB2-045
Solar/Wind Harmer
1.065
3146776BUCKING
Solar/Wind Harmer
-0.013
972003AH1-546 GEN
Solar/Wind Harmer
15.792
963171AG1-166 GEN
Solar/Wind Harmer
3.723
971563AH1-280 GEN
Solar/Wind Harmer
3.723
970685AG2-442 GEN
Solar/Wind Harmer
25.722
315687AD1-152 GEN
Solar/Wind Harmer
3.514
316237AB2-079_GEN
Solar/Wind Harmer
0.842
971065AG2-659 GEN
Solar/Wind Harmer
13.526
316129AC1-054 GEN
Solar/Wind Harmer
2.362
971795AH1-408 GEN
Solar/Wind Harmer
20.182
960081AF2-299 GEN
Solar/Wind Harmer
2.993
316023GEN1_S
Solar/Wind Harmer
1.787
970401AG2-262 GEN
Solar/Wind Harmer
1.725
316294AC1-161 GEN
Solar/Wind Harmer
8.447
944591AF1-124 GEN
Solar/Wind Harmer
117.74
316190AA2-174 GEN
Solar/Wind Harmer
0.315
3145783HORNRTN
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.334
962571AG1-106 GEN
Solar/Wind Harmer
3.665
316388AE2-253 GEN
Solar/Wind Harmer
1.708
3146456SLIGO L269
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.745
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
316246AF1-032 C
Solar/Wind Harmer
0.507
3146173TUNIS
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.178
3130156CHOWAN
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.621
3150981CHESPKA
Adder
2.768
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.294
3145823KELFORD
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.191
316212AC1-099_GEN
Solar/Wind Harmer
2.154
316093AE2-104_GEN
Solar/Wind Harmer
7.155
315722AD1-056 GEN
Solar/Wind Harmer
2.553
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.744
3146233WITAKRS
Solar/Wind Harmer
-0.095
3146293MARTNCO
Solar/Wind Harmer
0.149
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316003AC1-222 GEN
Solar/Wind Harmer
2.327
316494AC1-189 GEN
Solar/Wind Harmer
2.561
961671AG1-007 GEN
Solar/Wind Harmer
0.3
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.705
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.202
316049AB1-081 GEN
Solar/Wind Harmer
2.562
3142053HEARTS
Solar/Wind Harmer
0.279
316072AD1-144
Solar/Wind Harmer
0.477
3151171GRAVELC
Adder
1.83
3143226MDLTHAN
Solar/Wind Helper
0.35
316336AC2-165 C
Solar/Wind Helper
1.883
316045AC1-158 PL2
Solar/Wind Helper
4.241
3143526WINTERP
Solar/Wind Helper
1.191
970661AG2-428 GEN
Solar/Wind Harmer
10.44
315244AE2-183_ST
50/50
9.302
963041AG1-153 GEN
50/50
8.566
3151541CLOVER2
50/50
5.976
315779AE2-040
50/50
3.486
3151611KERR 4
50/50
0.508
3151621KERR 5
50/50
0.508
3151631KERR 6
50/50
0.508
3151641KERR 7
50/50
0.508
3151281ROARAP4
50/50
0.278
3151281ROARAP4
50/50
0.26
941031AE2-094 GEN
Solar/Wind Harmer
70.747
944011AF1-069 GEN
Solar/Wind Harmer
22.167
970673AG2-436 GEN
Solar/Wind Harmer
77.682
970673AG2-436 GEN
Solar/Wind Harmer
39.333
971967AH1-528 GEN
Solar/Wind Harmer
68.625
970085AG2-068 GEN
Solar/Wind Harmer
21.474
970581AG2-369 GEN
Solar/Wind Harmer
18.468
970285AG2-188 GEN
Solar/Wind Harmer
27.712
971845AH1-439 GEN
Solar/Wind Harmer
16.825
315657AE1-056 GEN
Solar/Wind Harmer
11.27
946301AF1-294 GEN
Solar/Wind Harmer
7.632
961791AG1-021 GEN
Solar/Wind Harmer
3.723
970683AG2-441 GEN
Solar/Wind Harmer
22.967
970681AG2-440 GEN
Solar/Wind Harmer
18.373
3144303KENBRDG
Solar/Wind Harmer
-0.023
971443AH1-215 GEN
Solar/Wind Harmer
5.7
316315AB2-025 C
Solar/Wind Harmer
0.757
315814AE2-033 C
Solar/Wind Harmer
26.059
316239AB2-077_GEN
Solar/Wind Harmer
0.842
316238AB2-078_GEN
Solar/Wind Harmer
0.842
970831AG2-522 GEN
Solar/Wind Harmer
13.417
946281AF1-292 GEN
Solar/Wind Harmer
0.596
316087AB2-174 GEN
Solar/Wind Harmer
3.756
3137643SOCKMAN
Solar/Wind Harmer
-0.103
316118AC1-105 GEN
Solar/Wind Harmer
1.777
315607AA1-063A GEN
Solar/Wind Harmer
2.581
3146043SEABORD
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.68
957871AF2-081 GEN
Solar/Wind Harmer
12.659
319010AE1-072 C
Solar/Wind Harmer
5.115
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3147173SINAI
Solar/Wind Harmer
-0.025
3147243WELCO
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
965291AG1-394 GEN
Solar/Wind Harmer
2.237
313526AB2-022
Solar/Wind Harmer
0.68
316321Z2-027
Solar/Wind Harmer
0.679
3146396TANGLEW
Solar/Wind Harmer
0.463
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316318V4-068
Solar/Wind Harmer
0.626
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316305AF2-043 C
Solar/Wind Harmer
0.755
3151081ELIZAR1
Adder
20.42
3151091ELIZAR2
Adder
20.065
315611Z1-036_GEN2
Solar/Wind Harmer
6.178
3145513AHOSKIE
Solar/Wind Harmer
0.218
961941AG1-037 GEN
Solar/Wind Harmer
0.188
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.211
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.834
3146033SCOT NK
Solar/Wind Harmer
-0.099
315732AD1-074 GEN1
Solar/Wind Harmer
5.007
315733AD1-074 GEN2
Solar/Wind Harmer
5.007
3150921YORKTN3
Adder
4.045
316313AB2-026
Solar/Wind Helper
0.532
316258AE1-075 C
Solar/Wind Helper
0.479
316405AF2-144 C
Solar/Wind Helper
0.399
316044AC1-158 PL1
Solar/Wind Helper
1.325
316450AC1-158 RIC
Solar/Wind Helper
0.353
970661AG2-428 GEN
Solar/Wind Harmer
1.85
315735AD1-075 GEN1
Solar/Wind Harmer
2.504
315835AF2-110_GEN
Solar/Wind Harmer
3.076
316319Z2-044 C
Solar/Wind Harmer
1.327
316005AA1-067
Solar/Wind Harmer
0.482
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.13
957861AF2-080 GEN
Solar/Wind Harmer
10.414
316420AA1-050 GEN
Solar/Wind Harmer
2.716
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
11.791
315833AF1-017_GEN
Solar/Wind Harmer
4.435
316349AD2-085 GEN
Solar/Wind Harmer
2.077
3143316POE
Solar/Wind Harmer
-0.087
972265AH1-717 GEN
Adder
13.355
3151201GRAVEL4
Adder
12.519
3151191GRAVEL3
Adder
12.361
3151211GRAVEL5
Adder
12.361
316233AE1-074 FULL
Solar/Wind Helper
0.35
NYPJM->LTFIMP_NY
CLTF
2.27
LGEELTFEXP_LGEE->PJM
CLTF
1.633
LAGNLTFEXP_LAGN->PJM
CLTF
9.794
WECLTFEXP_WEC->PJM
CLTF
0.839
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.485
TVALTFEXP_TVA->PJM
CLTF
4.889
CPLELTFEXP_CPLE->PJM
CLTF
14.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.937
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.197
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.662
MECLTFEXP_MEC->PJM
CLTF
4.586
SIGELTFEXP_SIGE->PJM
CLTF
0.137

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.33 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4228.67
MW Contribution:18.97
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.351
970413AG2-270 GEN
50/50
24.296
3151391GASTONA
50/50
0.66
3151411GASTONB
50/50
0.66
3151261ROARAP2
50/50
0.288
3151591KERR 2
50/50
0.465
970917AG2-570 GEN
Solar/Wind Harmer
88.674
316365GEN2_N
Solar/Wind Harmer
1.997
316478AD1-087 GEN
Solar/Wind Harmer
2.529
316486AD2-202 GEN
Solar/Wind Harmer
0.741
966621AG1-532 GEN
Solar/Wind Harmer
0.573
313506AB2-031 GEN
Solar/Wind Harmer
2.207
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3147043LAWRENC
Solar/Wind Harmer
-0.016
315773AC2-141 GEN
Solar/Wind Harmer
11.18
944581AF1-123 GEN
Solar/Wind Harmer
119.255
944601AF1-125 GEN
Solar/Wind Harmer
117.394
3146263WOODLND
Solar/Wind Harmer
-0.026
3156081AA2-088 GEN
Solar/Wind Harmer
8.422
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
315244AE2-183_ST
50/50
9.597
963041AG1-153 GEN
50/50
8.809
315779AE2-040
50/50
4.21
3151541CLOVER2
50/50
5.541
3151281ROARAP4
50/50
0.287
3151281ROARAP4
50/50
0.268
3151151S HAMPT1
50/50
0.598
3151611KERR 4
50/50
0.465
3151621KERR 5
50/50
0.465
3151631KERR 6
50/50
0.465
3151641KERR 7
50/50
0.465
941031AE2-094 GEN
Solar/Wind Harmer
73.515
944011AF1-069 GEN
Solar/Wind Harmer
23.035
970673AG2-436 GEN
Solar/Wind Harmer
80.349
970673AG2-436 GEN
Solar/Wind Harmer
40.683
971967AH1-528 GEN
Solar/Wind Harmer
69.889
970085AG2-068 GEN
Solar/Wind Harmer
22.054
970581AG2-369 GEN
Solar/Wind Harmer
18.967
316315AB2-025 C
Solar/Wind Harmer
0.914
315814AE2-033 C
Solar/Wind Harmer
31.355
3143316POE
Solar/Wind Harmer
-0.131
946281AF1-292 GEN
Solar/Wind Harmer
0.632
316087AB2-174 GEN
Solar/Wind Harmer
3.95
315652AC1-086 GEN
Solar/Wind Harmer
30.832
3145796HORNRTN
Solar/Wind Harmer
-0.086
3145796HORNRTN
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.107
315607AA1-063A GEN
Solar/Wind Harmer
2.662
3146043SEABORD
Solar/Wind Harmer
-0.026
965291AG1-394 GEN
Solar/Wind Harmer
2.306
316318V4-068
Solar/Wind Harmer
0.646
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145513AHOSKIE
Solar/Wind Harmer
0.225
961941AG1-037 GEN
Solar/Wind Harmer
0.194
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.051
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
970831AG2-522 GEN
Solar/Wind Harmer
12.905
957871AF2-081 GEN
Solar/Wind Harmer
12.847
319010AE1-072 C
Solar/Wind Harmer
5.194
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3146033SCOT NK
Solar/Wind Harmer
-0.102
313526AB2-022
Solar/Wind Harmer
0.691
316321Z2-027
Solar/Wind Harmer
0.691
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3146396TANGLEW
Solar/Wind Harmer
0.471
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.197
315611Z1-036_GEN2
Solar/Wind Harmer
6.312
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.065
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.158
970533AG2-339 GEN
50/50
31.019
970531AG2-338 GEN
50/50
12.408
315242AE2-183_GT2
50/50
5.551
315241AE2-183_GT1
50/50
5.517
972185AH1-677 GEN
50/50
20.012
3151041BRUNSWICKG3
50/50
4.351
972187AH1-678 GEN
50/50
9.984
3151361ROSEMG1
50/50
0.866
3151371ROSEMS1
50/50
0.536
3151381ROSEMG2
50/50
0.405
970933AG2-581 GEN
Solar/Wind Harmer
33.195
3144356SAPONY
Solar/Wind Harmer
1.182
970099AG2-077 GEN
Solar/Wind Harmer
38.77
316181AB2-040 GEN
Solar/Wind Harmer
3.83
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.991
3145593CAROLNA
Solar/Wind Harmer
0.221
316426AA2-053 GEN
Solar/Wind Harmer
2.671
3145783HORNRTN
Solar/Wind Harmer
3.137
3145783HORNRTN
Solar/Wind Harmer
2.509
3145783HORNRTN
Solar/Wind Harmer
0.784
3145783HORNRTN
Solar/Wind Harmer
0.314
3145893MURPHYS
Solar/Wind Harmer
0.723
3145893MURPHYS
Solar/Wind Harmer
-0.047
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145506HICKORY
Solar/Wind Harmer
-0.102
3145506HICKORY
Solar/Wind Harmer
-0.061
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.733
316018AA1-139 ULT2
Solar/Wind Harmer
2.201
316017AA1-139 ULT1
Solar/Wind Harmer
2.079
316185AD1-033 GEN
Solar/Wind Harmer
2.71
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.033
3130086AYDLETT
Solar/Wind Harmer
-0.102
316274AC1-208 GEN
Solar/Wind Harmer
2.766
3146386ELIZ CT
Solar/Wind Harmer
-0.026
315742AE1-103 GEN
Solar/Wind Harmer
2.672
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
316065AD1-022 GEN
Solar/Wind Harmer
12.78
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.628
316433W1029_GEN2
Solar/Wind Harmer
4.628
3146376EDENTON
Solar/Wind Harmer
0.758
3146376EDENTON
Solar/Wind Harmer
0.758
3142956BIRDNECK
Solar/Wind Harmer
1.365
316316AC1-027 C
Solar/Wind Harmer
0.78
316036AC1-147 C
Solar/Wind Harmer
0.677
3150991CHESPKB
Adder
2.34
3150991CHESPKB
Adder
2.284
939181AE1-148 GEN
Solar/Wind Harmer
14.051
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
961601AG1-000A GEN
Solar/Wind Harmer
9.691
3145493TOT1
Solar/Wind Harmer
0.381
3145453TOT5
Solar/Wind Harmer
0.229
3145603CNETO
Solar/Wind Harmer
0.153
316263AC1-034 GEN
Solar/Wind Harmer
11.543
313527AB2-043 GEN
Solar/Wind Harmer
3.843
970657AG2-426 GEN
Solar/Wind Harmer
7.368
970657AG2-426 GEN
Solar/Wind Harmer
1.541
962561AG1-105 GEN
Solar/Wind Harmer
13.218
964791AG1-342 GEN
Solar/Wind Harmer
5.014
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
971741AH1-377 GEN
Solar/Wind Harmer
25.656
316222AC1-221 GEN
Solar/Wind Harmer
2.208
970323AG2-213 GEN
Solar/Wind Harmer
10.577
971775AH1-396 GEN
Solar/Wind Harmer
1.506
316034AC1-036 C
Solar/Wind Harmer
0.392
316236AE1-162_GEN
Solar/Wind Harmer
0.622
970301AG2-198 GEN
Solar/Wind Harmer
10.061
3144293JTRSVLE
Adder
0.538
3144293JTRSVLE
Adder
0.453
316447AC1-158 HLD
Solar/Wind Helper
2.9
3143526WINTERP
Solar/Wind Helper
1.167
958211AF2-115 GEN
Solar/Wind Harmer
1.923
315733AD1-074 GEN2
Solar/Wind Harmer
5.158
315735AD1-075 GEN1
Solar/Wind Harmer
2.58
316305AF2-043 C
Solar/Wind Harmer
0.767
3151081ELIZAR1
Adder
20.599
3151091ELIZAR2
Adder
20.241
315835AF2-110_GEN
Solar/Wind Harmer
3.156
3152611GOSPORTB
Adder
2.846
3152621GOSPORTC
Adder
2.415
3152601GOSPORTA
Adder
2.228
316319Z2-044 C
Solar/Wind Harmer
1.375
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
316420AA1-050 GEN
Solar/Wind Harmer
2.815
957861AF2-080 GEN
Solar/Wind Harmer
10.782
316005AA1-067
Solar/Wind Harmer
0.498
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
970181AG2-120 GEN
Solar/Wind Harmer
3.234
316311AC2-079 GEN
Solar/Wind Harmer
12.392
315833AF1-017_GEN
Solar/Wind Harmer
4.664
316349AD2-085 GEN
Solar/Wind Harmer
2.184
316239AB2-077_GEN
Solar/Wind Harmer
0.715
316238AB2-078_GEN
Solar/Wind Harmer
0.715
316118AC1-105 GEN
Solar/Wind Harmer
1.61
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
4.184
3144303KENBRDG
Solar/Wind Harmer
-0.017
971445AH1-216 GEN
Solar/Wind Harmer
12.623
970683AG2-441 GEN
Solar/Wind Harmer
15.657
970681AG2-440 GEN
Solar/Wind Harmer
12.525
970865AG2-541 GEN
Solar/Wind Harmer
8.054
972265AH1-717 GEN
Adder
12.35
3151201GRAVEL4
Adder
11.578
3151191GRAVEL3
Adder
11.431
3151211GRAVEL5
Adder
11.431
316233AE1-074 FULL
Solar/Wind Helper
0.343
946301AF1-294 GEN
Solar/Wind Harmer
3.153
961791AG1-021 GEN
Solar/Wind Harmer
1.538
957521AF2-046 GEN
Solar/Wind Harmer
20.404
961681AG1-008 GEN
Solar/Wind Harmer
20.404
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.418
316140AB2-099
Solar/Wind Harmer
0.174
962331AG1-082 GEN
Solar/Wind Harmer
3.23
316317KELFORD C
Solar/Wind Harmer
1.212
3145823KELFORD
Solar/Wind Harmer
-0.026
3156021HOLLOMANSOL
Solar/Wind Harmer
3.465
315724AD1-057 GEN
Solar/Wind Harmer
1.479
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.13
316320Y1-086
Solar/Wind Harmer
1.502
3146206CASHIE
Solar/Wind Harmer
-0.026
316210AC1-098 GEN
Solar/Wind Harmer
4.012
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316435W1029_GEN3
Solar/Wind Harmer
4.628
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.753
971157AH1-035 GEN
Solar/Wind Harmer
3.188
315737AD1-076 GEN
Solar/Wind Harmer
4.848
3145273HOLLAND
Solar/Wind Harmer
-0.019
3151101ELIZAR3
Adder
20.863
316327AA2-057 GEN
Solar/Wind Harmer
2.54
3145963POPLR C
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.521
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
3145933PARMELE
Solar/Wind Harmer
-0.025
966801AG1-551 GEN
Solar/Wind Harmer
3.098
961601AG1-000A GEN
Solar/Wind Harmer
9.813
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
970661AG2-428 GEN
Solar/Wind Harmer
4.477
316131AB2-060 GEN
Solar/Wind Harmer
2.533
316083AB2-161 GEN
Solar/Wind Harmer
3.807
970659AG2-427 GEN
Solar/Wind Harmer
2.198
316248AF1-058 C
Solar/Wind Harmer
0.703
960061AF2-297 GEN
Solar/Wind Harmer
11.67
964241AG1-285 GEN
Solar/Wind Harmer
17.789
315813AE1-149 C
Solar/Wind Harmer
14.226
316283AC2-100 C
Solar/Wind Harmer
2.044
315785AD2-033 C
Solar/Wind Harmer
4.894
970257AG2-171 GEN
Solar/Wind Harmer
7.933
971683AH1-343 GEN
Solar/Wind Harmer
9.043
959311AF2-222 GEN
Solar/Wind Harmer
21.747
3145336SMITFLD
Solar/Wind Harmer
-0.008
970909AG2-566 GEN
Solar/Wind Harmer
1.91
3144293JTRSVLE
Adder
0.538
3151221GRAVEL6
Adder
11.564
3151171GRAVELC
Adder
2.225
3144216WINCHST
Adder
0.593
3150921YORKTN3
Adder
3.941
316044AC1-158 PL1
Solar/Wind Helper
1.317
316450AC1-158 RIC
Solar/Wind Helper
0.351
315243AE2-183_GT3
50/50
5.551
3151051BRUNSWICKS1
50/50
9.029
3151021BRUNSWICKG1
50/50
4.351
971451AH1-221 GEN
50/50
13.214
3151531CLOVER1
50/50
5.567
3151391GASTONA
50/50
0.66
3151411GASTONB
50/50
0.66
3147043LAWRENC
50/50
2.293
3151261ROARAP2
50/50
0.295
3151601KERR 3
50/50
0.465
3151581KERR 1
50/50
0.166
940641AE2-051 GEN
Solar/Wind Harmer
36.076
970919AG2-571 GEN
Solar/Wind Harmer
11.225
939411AE1-173 GEN
Solar/Wind Harmer
176.638
970087AG2-069 GEN
Solar/Wind Harmer
33.081
957481AF2-042 GEN
Solar/Wind Harmer
96.924
316023GEN1_S
Solar/Wind Harmer
1.997
315693AD1-088 GEN
Solar/Wind Harmer
14.305
960081AF2-299 GEN
Solar/Wind Harmer
3.176
962491AG1-098 GEN
Solar/Wind Harmer
18.84
316011AB1-132 GEN
Solar/Wind Harmer
5.734
962571AG1-106 GEN
Solar/Wind Harmer
3.94
971795AH1-408 GEN
Solar/Wind Harmer
20.458
315687AD1-152 GEN
Solar/Wind Harmer
3.278
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.027
316294AC1-161 GEN
Solar/Wind Harmer
8.644
316190AA2-174 GEN
Solar/Wind Harmer
0.325
3145783HORNRTN
Solar/Wind Harmer
-0.026
944591AF1-124 GEN
Solar/Wind Harmer
119.684
3146263WOODLND
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.769
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
316129AC1-054 GEN
Solar/Wind Harmer
2.255
3145823KELFORD
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
2.689
316388AE2-253 GEN
Solar/Wind Harmer
1.733
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971065AG2-659 GEN
Solar/Wind Harmer
12.825
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.398
316212AC1-099_GEN
Solar/Wind Harmer
2.229
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.312
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.925
316246AF1-032 C
Solar/Wind Harmer
0.515
316093AE2-104_GEN
Solar/Wind Harmer
7.34
3145963POPLR C
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.687
3150981CHESPKA
Adder
2.789
316174AB2-169 GEN
Solar/Wind Harmer
3.863
3146233WITAKRS
Solar/Wind Harmer
-0.098
3146293MARTNCO
Solar/Wind Harmer
0.153
961671AG1-007 GEN
Solar/Wind Harmer
0.312
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.731
316494AC1-189 GEN
Solar/Wind Harmer
2.652
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316359AB2-059 GEN
Solar/Wind Harmer
3.32
316049AB1-081 GEN
Solar/Wind Harmer
2.657
3142053HEARTS
Solar/Wind Harmer
0.289
3145543BTLEBRO
Solar/Wind Harmer
-0.025
3145543BTLEBRO
Solar/Wind Harmer
-0.02
970661AG2-428 GEN
Solar/Wind Harmer
25.261
316237AB2-079_GEN
Solar/Wind Harmer
0.715
316072AD1-144
Solar/Wind Harmer
0.478
970401AG2-262 GEN
Solar/Wind Harmer
1.532
316381AD1-082 GEN
Solar/Wind Harmer
2.151
970659AG2-427 GEN
Solar/Wind Harmer
12.403
316003AC1-222 GEN
Solar/Wind Harmer
2.155
3145336SMITFLD
Solar/Wind Harmer
-0.082
970685AG2-442 GEN
Solar/Wind Harmer
17.535
3144293JTRSVLE
Adder
0.538
3151171GRAVELC
Adder
1.692
3143226MDLTHAN
Solar/Wind Helper
0.326
316045AC1-158 PL2
Solar/Wind Helper
4.217
3143526WINTERP
Solar/Wind Helper
1.167
971563AH1-280 GEN
Solar/Wind Harmer
1.538
NYPJM->LTFIMP_NY
CLTF
2.268
LGEELTFEXP_LGEE->PJM
CLTF
1.668
LAGNLTFEXP_LAGN->PJM
CLTF
9.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
31.751
WECLTFEXP_WEC->PJM
CLTF
0.858
TVALTFEXP_TVA->PJM
CLTF
4.954
CPLELTFEXP_CPLE->PJM
CLTF
14.825
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.72
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.895
MECLTFEXP_MEC->PJM
CLTF
4.674
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:106.32 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4188.82
MW Contribution:18.16
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.166
970413AG2-270 GEN
50/50
23.168
3151101ELIZAR3
50/50
22.818
970917AG2-570 GEN
Solar/Wind Harmer
84.887
316478AD1-087 GEN
Solar/Wind Harmer
2.411
316486AD2-202 GEN
Solar/Wind Harmer
0.706
315773AC2-141 GEN
Solar/Wind Harmer
11.199
316365GEN2_N
Solar/Wind Harmer
1.804
944581AF1-123 GEN
Solar/Wind Harmer
121.142
944601AF1-125 GEN
Solar/Wind Harmer
119.252
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.188
316320Y1-086
Solar/Wind Harmer
1.524
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316435W1029_GEN3
Solar/Wind Harmer
4.679
966621AG1-532 GEN
Solar/Wind Harmer
0.524
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
313506AB2-031 GEN
Solar/Wind Harmer
2.044
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.729
3156081AA2-088 GEN
Solar/Wind Harmer
8.176
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145796HORNRTN
Solar/Wind Harmer
-0.1
3145796HORNRTN
Solar/Wind Harmer
-0.025
971157AH1-035 GEN
Solar/Wind Harmer
3.139
315737AD1-076 GEN
Solar/Wind Harmer
4.767
3145893MURPHYS
Solar/Wind Harmer
0.175
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.729
961681AG1-008 GEN
Solar/Wind Harmer
19.729
3146206CASHIE
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
316463AE2-346 GEN
Solar/Wind Harmer
0.404
316140AB2-099
Solar/Wind Harmer
0.168
962331AG1-082 GEN
Solar/Wind Harmer
3.117
3156021HOLLOMANSOL
Solar/Wind Harmer
3.359
3146263WOODLND
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
1.163
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316210AC1-098 GEN
Solar/Wind Harmer
3.812
315724AD1-057 GEN
Solar/Wind Harmer
1.388
970661AG2-428 GEN
Solar/Wind Harmer
4.538
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.991
316327AA2-057 GEN
Solar/Wind Harmer
2.405
316083AB2-161 GEN
Solar/Wind Harmer
3.858
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
2.227
3146233WITAKRS
Solar/Wind Harmer
0.493
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
961601AG1-000A GEN
Solar/Wind Harmer
9.279
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145336SMITFLD
Solar/Wind Harmer
-0.009
315813AE1-149 C
Solar/Wind Harmer
14.408
316248AF1-058 C
Solar/Wind Harmer
0.668
960061AF2-297 GEN
Solar/Wind Harmer
11.09
316131AB2-060 GEN
Solar/Wind Harmer
2.386
3151221GRAVEL6
Adder
13.951
3151171GRAVELC
Adder
2.684
964241AG1-285 GEN
Solar/Wind Harmer
16.743
315839AE2-212 C
Solar/Wind Harmer
0.632
961611AG1-000B GEN
Solar/Wind Harmer
4.362
316283AC2-100 C
Solar/Wind Harmer
1.947
315785AD2-033 C
Solar/Wind Harmer
4.601
971683AH1-343 GEN
Solar/Wind Harmer
8.591
970257AG2-171 GEN
Solar/Wind Harmer
7.455
3144216WINCHST
Adder
0.658
959311AF2-222 GEN
Solar/Wind Harmer
20.43
3150921YORKTN3
Adder
4.314
970909AG2-566 GEN
Solar/Wind Harmer
1.802
315778AD1-151 GEN
Solar/Wind Harmer
16.326
3144293JTRSVLE
Adder
0.504
316044AC1-158 PL1
Solar/Wind Helper
1.306
316450AC1-158 RIC
Solar/Wind Helper
0.348
315244AE2-183_ST
50/50
9.192
963041AG1-153 GEN
50/50
8.436
315779AE2-040
50/50
3.649
3151541CLOVER2
50/50
5.284
3151081ELIZAR1
50/50
22.53
941031AE2-094 GEN
Solar/Wind Harmer
70.434
944011AF1-069 GEN
Solar/Wind Harmer
22.069
970673AG2-436 GEN
Solar/Wind Harmer
76.963
970673AG2-436 GEN
Solar/Wind Harmer
38.968
971967AH1-528 GEN
Solar/Wind Harmer
66.91
970085AG2-068 GEN
Solar/Wind Harmer
21.111
970581AG2-369 GEN
Solar/Wind Harmer
18.156
316315AB2-025 C
Solar/Wind Harmer
0.792
315814AE2-033 C
Solar/Wind Harmer
27.227
957871AF2-081 GEN
Solar/Wind Harmer
13.091
319010AE1-072 C
Solar/Wind Harmer
5.287
3146406KITTY HAWK
Solar/Wind Harmer
0.022
3151091ELIZAR2
Adder
20.863
313526AB2-022
Solar/Wind Harmer
0.701
316321Z2-027
Solar/Wind Harmer
0.7
3146396TANGLEW
Solar/Wind Harmer
0.477
316305AF2-043 C
Solar/Wind Harmer
0.782
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3152611GOSPORTB
Adder
2.939
3152621GOSPORTC
Adder
2.494
3152601GOSPORTA
Adder
2.301
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
946281AF1-292 GEN
Solar/Wind Harmer
0.578
315611Z1-036_GEN2
Solar/Wind Harmer
6.337
315835AF2-110_GEN
Solar/Wind Harmer
3.202
316087AB2-174 GEN
Solar/Wind Harmer
3.644
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.603
3143316POE
Solar/Wind Harmer
-0.099
315816AE2-034 GEN
Solar/Wind Harmer
2.046
3137643SOCKMAN
Solar/Wind Harmer
-0.1
965291AG1-394 GEN
Solar/Wind Harmer
2.234
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.073
315733AD1-074 GEN2
Solar/Wind Harmer
5.073
315735AD1-075 GEN1
Solar/Wind Harmer
2.537
316318V4-068
Solar/Wind Harmer
0.625
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.532
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.946
3145513AHOSKIE
Solar/Wind Harmer
0.217
961941AG1-037 GEN
Solar/Wind Harmer
0.187
3145513AHOSKIE
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.569
315833AF1-017_GEN
Solar/Wind Harmer
4.73
316349AD2-085 GEN
Solar/Wind Harmer
2.215
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3146033SCOT NK
Solar/Wind Harmer
-0.097
970831AG2-522 GEN
Solar/Wind Harmer
12.178
316005AA1-067
Solar/Wind Harmer
0.479
3145746EVERETS
Solar/Wind Harmer
-0.094
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.109
957861AF2-080 GEN
Solar/Wind Harmer
10.308
316319Z2-044 C
Solar/Wind Harmer
1.301
316420AA1-050 GEN
Solar/Wind Harmer
2.684
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
971445AH1-216 GEN
Solar/Wind Harmer
14.288
316239AB2-077_GEN
Solar/Wind Harmer
0.674
316238AB2-078_GEN
Solar/Wind Harmer
0.674
316118AC1-105 GEN
Solar/Wind Harmer
1.527
3147173SINAI
Solar/Wind Harmer
-0.022
3147243WELCO
Solar/Wind Harmer
-0.014
972265AH1-717 GEN
Adder
14.899
3151201GRAVEL4
Adder
13.967
3151191GRAVEL3
Adder
13.79
3151211GRAVEL5
Adder
13.79
971443AH1-215 GEN
Solar/Wind Harmer
3.932
3144303KENBRDG
Solar/Wind Harmer
-0.016
316369SG1_INVT
Solar/Wind Harmer
3.462
316233AE1-074 FULL
Solar/Wind Helper
0.392
970865AG2-541 GEN
Solar/Wind Harmer
2.854
970533AG2-339 GEN
50/50
29.719
970531AG2-338 GEN
50/50
11.888
315242AE2-183_GT2
50/50
5.316
315241AE2-183_GT1
50/50
5.284
972185AH1-677 GEN
50/50
19.166
3151041BRUNSWICKG3
50/50
4.166
972187AH1-678 GEN
50/50
9.56
970933AG2-581 GEN
Solar/Wind Harmer
31.755
970099AG2-077 GEN
Solar/Wind Harmer
37.003
3144356SAPONY
Solar/Wind Harmer
1.024
316185AD1-033 GEN
Solar/Wind Harmer
2.769
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.767
316018AA1-139 ULT2
Solar/Wind Harmer
2.243
316017AA1-139 ULT1
Solar/Wind Harmer
2.119
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.088
3130086AYDLETT
Solar/Wind Harmer
-0.104
3142956BIRDNECK
Solar/Wind Harmer
1.401
316316AC1-027 C
Solar/Wind Harmer
0.801
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316036AC1-147 C
Solar/Wind Harmer
0.7
3150991CHESPKB
Adder
2.417
3150991CHESPKB
Adder
2.359
316431W1029_GEN1
Solar/Wind Harmer
4.679
316433W1029_GEN2
Solar/Wind Harmer
4.679
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146376EDENTON
Solar/Wind Harmer
0.757
3146376EDENTON
Solar/Wind Harmer
0.757
316181AB2-040 GEN
Solar/Wind Harmer
3.547
315742AE1-103 GEN
Solar/Wind Harmer
2.658
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.7
3145893MURPHYS
Solar/Wind Harmer
-0.045
316065AD1-022 GEN
Solar/Wind Harmer
12.521
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.811
3145593CAROLNA
Solar/Wind Harmer
0.208
316426AA2-053 GEN
Solar/Wind Harmer
2.523
3145783HORNRTN
Solar/Wind Harmer
2.952
3145783HORNRTN
Solar/Wind Harmer
2.361
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.295
316274AC1-208 GEN
Solar/Wind Harmer
2.617
3145933PARMELE
Solar/Wind Harmer
-0.048
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
7.467
970657AG2-426 GEN
Solar/Wind Harmer
1.562
939181AE1-148 GEN
Solar/Wind Harmer
13.286
3145493TOT1
Solar/Wind Harmer
0.363
3145453TOT5
Solar/Wind Harmer
0.218
3145603CNETO
Solar/Wind Harmer
0.145
961601AG1-000A GEN
Solar/Wind Harmer
9.163
316263AC1-034 GEN
Solar/Wind Harmer
10.92
316236AE1-162_GEN
Solar/Wind Harmer
0.701
313527AB2-043 GEN
Solar/Wind Harmer
3.62
962561AG1-105 GEN
Solar/Wind Harmer
12.505
3146843MT LREL
Solar/Wind Harmer
-0.022
3146843MT LREL
Solar/Wind Harmer
-0.022
964791AG1-342 GEN
Solar/Wind Harmer
4.747
971741AH1-377 GEN
Solar/Wind Harmer
24.269
316222AC1-221 GEN
Solar/Wind Harmer
2.102
970323AG2-213 GEN
Solar/Wind Harmer
9.94
971775AH1-396 GEN
Solar/Wind Harmer
1.416
316034AC1-036 C
Solar/Wind Harmer
0.368
316033AB2-134 GEN
Solar/Wind Harmer
6.249
315697AD1-025 GEN
Solar/Wind Harmer
3.919
970301AG2-198 GEN
Solar/Wind Harmer
9.489
3144293JTRSVLE
Adder
0.504
3144293JTRSVLE
Adder
0.425
944641AF1-129 GEN
Adder
75.287
3143526WINTERP
Solar/Wind Helper
1.336
316447AC1-158 HLD
Solar/Wind Helper
2.874
315243AE2-183_GT3
50/50
5.316
3151051BRUNSWICKS1
50/50
8.646
3151021BRUNSWICKG1
50/50
4.166
971451AH1-221 GEN
50/50
12.653
3151531CLOVER1
50/50
5.309
940641AE2-051 GEN
Solar/Wind Harmer
34.779
939411AE1-173 GEN
Solar/Wind Harmer
172.015
970919AG2-571 GEN
Solar/Wind Harmer
10.745
970087AG2-069 GEN
Solar/Wind Harmer
31.667
957481AF2-042 GEN
Solar/Wind Harmer
92.508
315693AD1-088 GEN
Solar/Wind Harmer
13.627
962491AG1-098 GEN
Solar/Wind Harmer
17.939
316294AC1-161 GEN
Solar/Wind Harmer
8.659
316023GEN1_S
Solar/Wind Harmer
1.804
944591AF1-124 GEN
Solar/Wind Harmer
121.578
316388AE2-253 GEN
Solar/Wind Harmer
1.767
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316375AC2-012 GEN
Solar/Wind Harmer
8.973
3150981CHESPKA
Adder
2.881
316246AF1-032 C
Solar/Wind Harmer
0.525
315687AD1-152 GEN
Solar/Wind Harmer
3.124
960081AF2-299 GEN
Solar/Wind Harmer
2.904
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.337
316093AE2-104_GEN
Solar/Wind Harmer
7.449
3130156CHOWAN
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.319
962571AG1-106 GEN
Solar/Wind Harmer
3.655
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.71
3145796HORNRTN
Solar/Wind Harmer
-0.082
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.744
971795AH1-408 GEN
Solar/Wind Harmer
18.809
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.255
3146173TUNIS
Solar/Wind Harmer
-0.025
316190AA2-174 GEN
Solar/Wind Harmer
0.307
3146263WOODLND
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
1.992
316072AD1-144
Solar/Wind Harmer
0.5
3145823KELFORD
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.756
316212AC1-099_GEN
Solar/Wind Harmer
2.118
316129AC1-054 GEN
Solar/Wind Harmer
2.129
971065AG2-659 GEN
Solar/Wind Harmer
12.112
315722AD1-056 GEN
Solar/Wind Harmer
2.523
970661AG2-428 GEN
Solar/Wind Harmer
25.606
3146293MARTNCO
Solar/Wind Harmer
0.148
316381AD1-082 GEN
Solar/Wind Harmer
2.18
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
12.568
316494AC1-189 GEN
Solar/Wind Harmer
2.535
3146233WITAKRS
Solar/Wind Harmer
-0.093
961671AG1-007 GEN
Solar/Wind Harmer
0.296
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.696
316359AB2-059 GEN
Solar/Wind Harmer
3.141
316049AB1-081 GEN
Solar/Wind Harmer
2.514
3142053HEARTS
Solar/Wind Harmer
0.274
3145543BTLEBRO
Solar/Wind Harmer
-0.023
3145543BTLEBRO
Solar/Wind Harmer
-0.019
3145336SMITFLD
Solar/Wind Harmer
-0.093
316237AB2-079_GEN
Solar/Wind Harmer
0.674
970401AG2-262 GEN
Solar/Wind Harmer
1.45
3151171GRAVELC
Adder
2.041
316003AC1-222 GEN
Solar/Wind Harmer
2.048
961611AG1-000B GEN
Solar/Wind Harmer
10.222
971647AH1-324 GEN
Solar/Wind Harmer
10.02
3138126ROCKLANDING
Solar/Wind Harmer
0.06
971069AG2-661 GEN
Solar/Wind Harmer
2.982
3144293JTRSVLE
Adder
0.504
3143226MDLTHAN
Solar/Wind Helper
0.345
3143526WINTERP
Solar/Wind Helper
1.336
316045AC1-158 PL2
Solar/Wind Helper
4.18
NYPJM->LTFIMP_NY
CLTF
2.225
LGEELTFEXP_LGEE->PJM
CLTF
1.558
LAGNLTFEXP_LAGN->PJM
CLTF
9.388
WECLTFEXP_WEC->PJM
CLTF
0.8
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.224
TVALTFEXP_TVA->PJM
CLTF
4.687
CPLELTFEXP_CPLE->PJM
CLTF
14.126
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.754
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.772
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.963
MECLTFEXP_MEC->PJM
CLTF
4.378
SIGELTFEXP_SIGE->PJM
CLTF
0.13

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.09 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:3384.28
MW Contribution:13.41
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.054
970413AG2-270 GEN
50/50
22.561
3151101ELIZAR3
50/50
21.566
970917AG2-570 GEN
Solar/Wind Harmer
26.133
316478AD1-087 GEN
Solar/Wind Harmer
0.842
316486AD2-202 GEN
Solar/Wind Harmer
0.247
315773AC2-141 GEN
Solar/Wind Harmer
8.348
944581AF1-123 GEN
Solar/Wind Harmer
50.754
944601AF1-125 GEN
Solar/Wind Harmer
49.972
316365GEN2_N
Solar/Wind Harmer
0.501
3146456SLIGO L269
Solar/Wind Harmer
0.22
971153AH1-033 GEN
Solar/Wind Harmer
2.55
316320Y1-086
Solar/Wind Harmer
0.001
3144873MCLAUGH
Solar/Wind Harmer
0.005
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.215
313506AB2-031 GEN
Solar/Wind Harmer
0.662
3145273HOLLAND
Solar/Wind Harmer
0.16
315614AA2-178 GEN
Solar/Wind Harmer
1.222
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
971157AH1-035 GEN
Solar/Wind Harmer
2.545
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3145796HORNRTN
Solar/Wind Harmer
0.846
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
957521AF2-046 GEN
Solar/Wind Harmer
15.712
961681AG1-008 GEN
Solar/Wind Harmer
15.712
3146173TUNIS
Solar/Wind Harmer
0.211
3156021HOLLOMANSOL
Solar/Wind Harmer
0.955
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.21
962331AG1-082 GEN
Solar/Wind Harmer
2.245
3144536CHRHLND
Solar/Wind Harmer
0.031
3147043LAWRENC
Solar/Wind Harmer
0.126
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
316210AC1-098 GEN
Solar/Wind Harmer
1.908
315724AD1-057 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
316327AA2-057 GEN
Solar/Wind Harmer
0.305
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
1.004
3146233WITAKRS
Solar/Wind Harmer
0.136
3138543CONSLDL
Solar/Wind Harmer
0.132
3146073TAR RVR
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
0.199
961601AG1-000A GEN
Solar/Wind Harmer
14.088
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.198
971623AH1-311 GEN
Solar/Wind Harmer
0.396
970661AG2-428 GEN
Solar/Wind Harmer
4.071
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.184
316131AB2-060 GEN
Solar/Wind Harmer
0.6
3145336SMITFLD
Solar/Wind Harmer
0.076
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970533AG2-339 GEN
50/50
28.925
970531AG2-338 GEN
50/50
11.57
315242AE2-183_GT2
50/50
5.174
315241AE2-183_GT1
50/50
5.142
972185AH1-677 GEN
50/50
18.653
3151041BRUNSWICKG3
50/50
4.054
972187AH1-678 GEN
50/50
9.304
970933AG2-581 GEN
Solar/Wind Harmer
23.481
970099AG2-077 GEN
Solar/Wind Harmer
27.375
3144356SAPONY
Solar/Wind Harmer
2.028
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.885
3145506HICKORY
Solar/Wind Harmer
0.531
3145506HICKORY
Solar/Wind Harmer
0.133
316339AD2-160 GEN
Solar/Wind Harmer
0.358
316018AA1-139 ULT2
Solar/Wind Harmer
0.005
316017AA1-139 ULT1
Solar/Wind Harmer
0.123
3137176SLIGO L2192
Solar/Wind Harmer
0.878
3146456SLIGO L269
Solar/Wind Harmer
3.903
3130086AYDLETT
Solar/Wind Harmer
0.881
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.211
3146386ELIZ CT
Solar/Wind Harmer
0.219
316036AC1-147 C
Solar/Wind Harmer
0.04
3150991CHESPKB
Adder
2.282
3150991CHESPKB
Adder
2.228
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146516WINFALL
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146626S HERTFORD
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
316181AB2-040 GEN
Solar/Wind Harmer
0.311
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.634
316065AD1-022 GEN
Solar/Wind Harmer
9.736
3145893MURPHYS
Solar/Wind Harmer
1.414
3145893MURPHYS
Solar/Wind Harmer
0.38
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.291
3145593CAROLNA
Solar/Wind Harmer
0.263
316426AA2-053 GEN
Solar/Wind Harmer
0.712
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
3145783HORNRTN
Solar/Wind Harmer
3.739
3145783HORNRTN
Solar/Wind Harmer
2.991
315243AE2-183_GT3
50/50
5.174
3151051BRUNSWICKS1
50/50
8.414
3151021BRUNSWICKG1
50/50
4.054
971451AH1-221 GEN
50/50
12.314
3151531CLOVER1
50/50
5.17
940641AE2-051 GEN
Solar/Wind Harmer
25.663
939411AE1-173 GEN
Solar/Wind Harmer
126.366
970919AG2-571 GEN
Solar/Wind Harmer
10.453
970087AG2-069 GEN
Solar/Wind Harmer
23.397
957481AF2-042 GEN
Solar/Wind Harmer
68.436
315693AD1-088 GEN
Solar/Wind Harmer
11.355
962491AG1-098 GEN
Solar/Wind Harmer
13.293
316294AC1-161 GEN
Solar/Wind Harmer
3.96
944591AF1-124 GEN
Solar/Wind Harmer
50.934
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316023GEN1_S
Solar/Wind Harmer
0.501
316388AE2-253 GEN
Solar/Wind Harmer
0.692
3146456SLIGO L269
Solar/Wind Harmer
0.22
316246AF1-032 C
Solar/Wind Harmer
0.098
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.721
3146516WINFALL
Solar/Wind Harmer
0.705
3146516WINFALL
Solar/Wind Harmer
0.217
960081AF2-299 GEN
Solar/Wind Harmer
2.083
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
316093AE2-104_GEN
Solar/Wind Harmer
3.601
316011AB1-132 GEN
Solar/Wind Harmer
3.888
962571AG1-106 GEN
Solar/Wind Harmer
3.042
3145663CRESWEL
Solar/Wind Harmer
0.597
971163AH1-040 GEN
Solar/Wind Harmer
17.076
971795AH1-408 GEN
Solar/Wind Harmer
14.122
3145796HORNRTN
Solar/Wind Harmer
0.698
3145796HORNRTN
Solar/Wind Harmer
0.211
3145893MURPHYS
Solar/Wind Harmer
0.845
3145893MURPHYS
Solar/Wind Harmer
0.939
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.506
316190AA2-174 GEN
Solar/Wind Harmer
0
3146173TUNIS
Solar/Wind Harmer
0.211
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
3147043LAWRENC
Adder
1.895
3145823KELFORD
Solar/Wind Harmer
0.208
316129AC1-054 GEN
Solar/Wind Harmer
0.781
971065AG2-659 GEN
Solar/Wind Harmer
8.844
3145963POPLR C
Solar/Wind Harmer
0.207
316072AD1-144
Solar/Wind Harmer
0.075
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316212AC1-099_GEN
Solar/Wind Harmer
1.064
315722AD1-056 GEN
Solar/Wind Harmer
1.293
3146293MARTNCO
Solar/Wind Harmer
0.188
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3146233WITAKRS
Solar/Wind Harmer
0.796
316494AC1-189 GEN
Solar/Wind Harmer
0.676
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.199
3145493TOT1
Solar/Wind Harmer
0.885
316359AB2-059 GEN
Solar/Wind Harmer
0.711
316049AB1-081 GEN
Solar/Wind Harmer
1.133
3145543BTLEBRO
Solar/Wind Harmer
0.198
3145543BTLEBRO
Solar/Wind Harmer
0.158
3142053HEARTS
Solar/Wind Harmer
0.349
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
19.138
970401AG2-262 GEN
Solar/Wind Harmer
1.126
3145336SMITFLD
Solar/Wind Harmer
0.755
316381AD1-082 GEN
Solar/Wind Harmer
0.196
970659AG2-427 GEN
Solar/Wind Harmer
8.999
316003AC1-222 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
1.816
970685AG2-442 GEN
Solar/Wind Harmer
12.211
3138126ROCKLANDING
Solar/Wind Harmer
0.074
961611AG1-000B GEN
Solar/Wind Harmer
8.399
963171AG1-166 GEN
Solar/Wind Harmer
0.828
971563AH1-280 GEN
Solar/Wind Harmer
1.656
3144293JTRSVLE
Adder
0.494
971647AH1-324 GEN
Solar/Wind Harmer
6.473
971317AH1-138 GEN
Solar/Wind Harmer
1.095
971069AG2-661 GEN
Solar/Wind Harmer
2.431
316159AE1-175 C
Solar/Wind Harmer
0.112
315671AE2-027_GEN
Solar/Wind Harmer
8.259
316458AB2-190 GEN2
Solar/Wind Harmer
0.682
970129AG2-093 GEN
Solar/Wind Harmer
3.572
3146926FARMVIL
Solar/Wind Harmer
0.069
3143226MDLTHAN
Solar/Wind Helper
0.299
316045AC1-158 PL2
Solar/Wind Helper
4.09
970659AG2-427 GEN
Solar/Wind Harmer
1.969
964241AG1-285 GEN
Solar/Wind Harmer
12.343
316283AC2-100 C
Solar/Wind Harmer
0.349
315813AE1-149 C
Solar/Wind Harmer
9.464
315785AD2-033 C
Solar/Wind Harmer
1.43
971683AH1-343 GEN
Solar/Wind Harmer
6.344
970257AG2-171 GEN
Solar/Wind Harmer
5.516
3151221GRAVEL6
Adder
12.414
3151171GRAVELC
Adder
2.388
959311AF2-222 GEN
Solar/Wind Harmer
15.096
970909AG2-566 GEN
Solar/Wind Harmer
1.775
3144216WINCHST
Adder
0.609
961611AG1-000B GEN
Solar/Wind Harmer
4.271
3150921YORKTN3
Adder
4.021
963181AG1-167 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3147133PAMPLIN
Solar/Wind Harmer
0.469
971193AH1-056 GEN
Solar/Wind Harmer
9.098
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.464
315778AD1-151 GEN
Solar/Wind Harmer
10.941
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316382AG1-145 C
Solar/Wind Harmer
0.001
970129AG2-093 GEN
Solar/Wind Harmer
7.591
3146926FARMVIL
Solar/Wind Harmer
0.069
316044AC1-158 PL1
Solar/Wind Helper
1.278
316450AC1-158 RIC
Solar/Wind Helper
0.341
315244AE2-183_ST
50/50
8.945
963041AG1-153 GEN
50/50
8.209
315779AE2-040
50/50
3.384
3151541CLOVER2
50/50
5.145
3151081ELIZAR1
50/50
21.293
941031AE2-094 GEN
Solar/Wind Harmer
59.933
944011AF1-069 GEN
Solar/Wind Harmer
19.582
970673AG2-436 GEN
Solar/Wind Harmer
67.697
970673AG2-436 GEN
Solar/Wind Harmer
45.131
971967AH1-528 GEN
Solar/Wind Harmer
49.335
970085AG2-068 GEN
Solar/Wind Harmer
15.598
970581AG2-369 GEN
Solar/Wind Harmer
13.414
316315AB2-025 C
Solar/Wind Harmer
0.196
315814AE2-033 C
Solar/Wind Harmer
19.104
957871AF2-081 GEN
Solar/Wind Harmer
10.995
319010AE1-072 C
Solar/Wind Harmer
1.11
3146406KITTY HAWK
Solar/Wind Harmer
0.027
313526AB2-022
Solar/Wind Harmer
0.119
3151091ELIZAR2
Adder
19.718
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.603
3145176PASQUOTANK
Solar/Wind Harmer
0.136
316305AF2-043 C
Solar/Wind Harmer
0.002
3146486SUNBURY
Solar/Wind Harmer
0.218
3146486SUNBURY
Solar/Wind Harmer
0.218
3152611GOSPORTB
Adder
2.775
3152621GOSPORTC
Adder
2.355
3152601GOSPORTA
Adder
2.173
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.215
3130156CHOWAN
Solar/Wind Harmer
0.215
316087AB2-174 GEN
Solar/Wind Harmer
0.006
315835AF2-110_GEN
Solar/Wind Harmer
1.469
315652AC1-086 GEN
Solar/Wind Harmer
23.522
315816AE2-034 GEN
Solar/Wind Harmer
0.916
3137643SOCKMAN
Solar/Wind Harmer
0.849
3130546PLYMOUTH
Solar/Wind Harmer
0.212
965291AG1-394 GEN
Solar/Wind Harmer
0.942
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.085
3146043SEABORD
Solar/Wind Harmer
0.211
315607AA1-063A GEN
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
0.57
3145893MURPHYS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.886
3145513AHOSKIE
Solar/Wind Harmer
0.44
3145513AHOSKIE
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.873
3146033SCOT NK
Solar/Wind Harmer
0.827
316311AC2-079 GEN
Solar/Wind Harmer
5.862
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.14
316005AA1-067
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.8
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
3145746EVERETS
Solar/Wind Harmer
0.201
970181AG2-120 GEN
Solar/Wind Harmer
2.501
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
8.623
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.199
3145573BETHELC
Solar/Wind Harmer
0.199
3143316POE
Solar/Wind Harmer
0.769
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.495
3147173SINAI
Solar/Wind Harmer
0.192
3147243WELCO
Solar/Wind Harmer
0.12
971445AH1-216 GEN
Solar/Wind Harmer
13.184
971443AH1-215 GEN
Solar/Wind Harmer
2.909
3144303KENBRDG
Solar/Wind Harmer
0.138
972265AH1-717 GEN
Adder
13.258
3151201GRAVEL4
Adder
12.428
3151191GRAVEL3
Adder
12.271
3151211GRAVEL5
Adder
12.271
970683AG2-441 GEN
Solar/Wind Harmer
10.903
970681AG2-440 GEN
Solar/Wind Harmer
8.722
970865AG2-541 GEN
Solar/Wind Harmer
5.652
946301AF1-294 GEN
Solar/Wind Harmer
3.063
961791AG1-021 GEN
Solar/Wind Harmer
1.49
315657AE1-056 GEN
Solar/Wind Harmer
5.154
316123AC1-075 GEN
Solar/Wind Harmer
0.197
970165AG2-112 GEN
Solar/Wind Harmer
1.167
970163AG2-111 GEN
Solar/Wind Harmer
1.113
316369SG1_INVT
Solar/Wind Harmer
0.005
3138283WHITEMARSH
Solar/Wind Harmer
0.03
316132AB2-190 GEN1
Solar/Wind Harmer
0.682
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
316274AC1-208 GEN
Solar/Wind Harmer
1.066
939181AE1-148 GEN
Solar/Wind Harmer
9.756
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
3145493TOT1
Solar/Wind Harmer
0.462
3145453TOT5
Solar/Wind Harmer
0.277
3145603CNETO
Solar/Wind Harmer
0.185
961601AG1-000A GEN
Solar/Wind Harmer
3.522
316263AC1-034 GEN
Solar/Wind Harmer
7.526
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
9.215
3146843MT LREL
Solar/Wind Harmer
0.192
3146843MT LREL
Solar/Wind Harmer
0.192
964791AG1-342 GEN
Solar/Wind Harmer
3.686
970657AG2-426 GEN
Solar/Wind Harmer
6.636
970657AG2-426 GEN
Solar/Wind Harmer
1.391
316236AE1-162_GEN
Solar/Wind Harmer
0.002
971741AH1-377 GEN
Solar/Wind Harmer
18.103
316222AC1-221 GEN
Solar/Wind Harmer
0.745
970323AG2-213 GEN
Solar/Wind Harmer
7.354
971775AH1-396 GEN
Solar/Wind Harmer
0.276
316034AC1-036 C
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.099
958211AF2-115 GEN
Solar/Wind Harmer
1.863
963191AG1-168 GEN
Solar/Wind Harmer
0.621
3144293JTRSVLE
Adder
0.494
3144293JTRSVLE
Adder
0.416
3147133PAMPLIN
Solar/Wind Harmer
0.149
3147133PAMPLIN
Solar/Wind Harmer
0.119
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.161
942751AE2-291 GEN
Solar/Wind Harmer
7.176
316240AF1-291 C
Solar/Wind Harmer
0.001
316447AC1-158 HLD
Solar/Wind Helper
2.812
NYPJM->LTFIMP_NY
CLTF
2.148
LGEELTFEXP_LGEE->PJM
CLTF
1.532
LAGNLTFEXP_LAGN->PJM
CLTF
9.15
WECLTFEXP_WEC->PJM
CLTF
0.787
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.306
TVALTFEXP_TVA->PJM
CLTF
4.569
CPLELTFEXP_CPLE->PJM
CLTF
13.67
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.627
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.362
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.575
MECLTFEXP_MEC->PJM
CLTF
4.294
SIGELTFEXP_SIGE->PJM
CLTF
0.128

Details for 8CARSON-8MDLTHAN 500.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.67 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4124.05
MW Contribution:18.47
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
5.365
3151051BRUNSWICKS1
50/50
8.74
3151021BRUNSWICKG1
50/50
4.211
971451AH1-221 GEN
50/50
12.79
3151531CLOVER1
50/50
5.439
3151391GASTONA
50/50
0.617
3151411GASTONB
50/50
0.617
940641AE2-051 GEN
Solar/Wind Harmer
34.798
970919AG2-571 GEN
Solar/Wind Harmer
10.923
970087AG2-069 GEN
Solar/Wind Harmer
32.213
939411AE1-173 GEN
Solar/Wind Harmer
171.7
957481AF2-042 GEN
Solar/Wind Harmer
94.326
315693AD1-088 GEN
Solar/Wind Harmer
13.943
962491AG1-098 GEN
Solar/Wind Harmer
18.368
315687AD1-152 GEN
Solar/Wind Harmer
3.227
316294AC1-161 GEN
Solar/Wind Harmer
8.621
316023GEN1_S
Solar/Wind Harmer
1.79
944591AF1-124 GEN
Solar/Wind Harmer
120.234
316388AE2-253 GEN
Solar/Wind Harmer
1.745
3146456SLIGO L269
Solar/Wind Harmer
-0.026
960081AF2-299 GEN
Solar/Wind Harmer
2.906
316011AB1-132 GEN
Solar/Wind Harmer
5.361
962571AG1-106 GEN
Solar/Wind Harmer
3.683
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.518
315800Z1-036_GEN1
Solar/Wind Harmer
6.305
316375AC2-012 GEN
Solar/Wind Harmer
8.82
3150981CHESPKA
Adder
2.832
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.083
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.751
316190AA2-174 GEN
Solar/Wind Harmer
0.31
970533AG2-339 GEN
50/50
29.886
970531AG2-338 GEN
50/50
11.954
315242AE2-183_GT2
50/50
5.365
315241AE2-183_GT1
50/50
5.332
972185AH1-677 GEN
50/50
19.342
3151031BRUNSWICKG2
50/50
4.211
970413AG2-270 GEN
50/50
23.737
3151391GASTONA
50/50
0.617
3151411GASTONB
50/50
0.617
3151101ELIZAR3
50/50
22.447
970917AG2-570 GEN
Solar/Wind Harmer
86.292
316478AD1-087 GEN
Solar/Wind Harmer
2.471
316486AD2-202 GEN
Solar/Wind Harmer
0.724
315773AC2-141 GEN
Solar/Wind Harmer
11.15
316365GEN2_N
Solar/Wind Harmer
1.79
944581AF1-123 GEN
Solar/Wind Harmer
119.802
944601AF1-125 GEN
Solar/Wind Harmer
117.933
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.15
966621AG1-532 GEN
Solar/Wind Harmer
0.524
316320Y1-086
Solar/Wind Harmer
1.508
3146516WINFALL
Solar/Wind Harmer
-0.026
316435W1029_GEN3
Solar/Wind Harmer
4.638
313506AB2-031 GEN
Solar/Wind Harmer
2.056
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146376EDENTON
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.101
3145796HORNRTN
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.733
971157AH1-035 GEN
Solar/Wind Harmer
3.155
315737AD1-076 GEN
Solar/Wind Harmer
4.795
3156081AA2-088 GEN
Solar/Wind Harmer
8.181
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.176
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.831
961681AG1-008 GEN
Solar/Wind Harmer
19.831
3146173TUNIS
Solar/Wind Harmer
-0.025
3156021HOLLOMANSOL
Solar/Wind Harmer
3.39
3145273HOLLAND
Solar/Wind Harmer
-0.019
316463AE2-346 GEN
Solar/Wind Harmer
0.407
316140AB2-099
Solar/Wind Harmer
0.17
962331AG1-082 GEN
Solar/Wind Harmer
3.145
316317KELFORD C
Solar/Wind Harmer
1.18
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145963POPLR C
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.898
315724AD1-057 GEN
Solar/Wind Harmer
1.426
3145933PARMELE
Solar/Wind Harmer
-0.025
966801AG1-551 GEN
Solar/Wind Harmer
3.071
3144536CHRHLND
Solar/Wind Harmer
-0.004
316327AA2-057 GEN
Solar/Wind Harmer
2.481
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
0.511
3146233WITAKRS
Solar/Wind Harmer
-0.016
3138543CONSLDL
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.024
3146083TARBORO
Solar/Wind Harmer
-0.024
961601AG1-000A GEN
Solar/Wind Harmer
9.659
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
316248AF1-058 C
Solar/Wind Harmer
0.694
960061AF2-297 GEN
Solar/Wind Harmer
11.515
316131AB2-060 GEN
Solar/Wind Harmer
2.463
970661AG2-428 GEN
Solar/Wind Harmer
4.26
316283AC2-100 C
Solar/Wind Harmer
2.097
3145336SMITFLD
Solar/Wind Harmer
-0.009
964241AG1-285 GEN
Solar/Wind Harmer
17.312
316083AB2-161 GEN
Solar/Wind Harmer
3.584
970659AG2-427 GEN
Solar/Wind Harmer
2.061
315785AD2-033 C
Solar/Wind Harmer
4.772
315813AE1-149 C
Solar/Wind Harmer
13.059
970257AG2-171 GEN
Solar/Wind Harmer
7.741
971683AH1-343 GEN
Solar/Wind Harmer
8.872
959311AF2-222 GEN
Solar/Wind Harmer
21.233
3151221GRAVEL6
Adder
13.016
3151171GRAVELC
Adder
2.504
970909AG2-566 GEN
Solar/Wind Harmer
1.877
3144216WINCHST
Adder
0.639
3150921YORKTN3
Adder
4.218
3144293JTRSVLE
Adder
0.527
316044AC1-158 PL1
Solar/Wind Helper
1.242
316450AC1-158 RIC
Solar/Wind Helper
0.331
961611AG1-000B GEN
Solar/Wind Harmer
0.889
315244AE2-183_ST
50/50
9.276
963041AG1-153 GEN
50/50
8.526
3151541CLOVER2
50/50
5.413
315779AE2-040
50/50
3.53
941031AE2-094 GEN
Solar/Wind Harmer
70.83
944011AF1-069 GEN
Solar/Wind Harmer
22.193
970673AG2-436 GEN
Solar/Wind Harmer
77.572
970673AG2-436 GEN
Solar/Wind Harmer
39.277
971967AH1-528 GEN
Solar/Wind Harmer
67.508
970085AG2-068 GEN
Solar/Wind Harmer
21.475
970581AG2-369 GEN
Solar/Wind Harmer
18.469
316315AB2-025 C
Solar/Wind Harmer
0.766
315814AE2-033 C
Solar/Wind Harmer
26.373
957871AF2-081 GEN
Solar/Wind Harmer
12.934
319010AE1-072 C
Solar/Wind Harmer
5.226
3146406KITTY HAWK
Solar/Wind Harmer
0.021
946281AF1-292 GEN
Solar/Wind Harmer
0.578
313526AB2-022
Solar/Wind Harmer
0.694
316321Z2-027
Solar/Wind Harmer
0.693
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
316087AB2-174 GEN
Solar/Wind Harmer
3.659
315652AC1-086 GEN
Solar/Wind Harmer
28.827
3151081ELIZAR1
Adder
20.887
3151091ELIZAR2
Adder
20.524
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316305AF2-043 C
Solar/Wind Harmer
0.771
315611Z1-036_GEN2
Solar/Wind Harmer
6.305
3152611GOSPORTB
Adder
2.889
3152621GOSPORTC
Adder
2.452
3152601GOSPORTA
Adder
2.262
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
3137643SOCKMAN
Solar/Wind Harmer
-0.101
315816AE2-034 GEN
Solar/Wind Harmer
2.05
315607AA1-063A GEN
Solar/Wind Harmer
2.551
3146043SEABORD
Solar/Wind Harmer
-0.025
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.102
315733AD1-074 GEN2
Solar/Wind Harmer
5.102
315735AD1-075 GEN1
Solar/Wind Harmer
2.552
965291AG1-394 GEN
Solar/Wind Harmer
2.237
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.025
316318V4-068
Solar/Wind Harmer
0.628
3145893MURPHYS
Solar/Wind Harmer
-0.068
3145893MURPHYS
Solar/Wind Harmer
-0.025
3145513AHOSKIE
Solar/Wind Harmer
0.219
961941AG1-037 GEN
Solar/Wind Harmer
0.189
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315835AF2-110_GEN
Solar/Wind Harmer
3.142
3146033SCOT NK
Solar/Wind Harmer
-0.099
970831AG2-522 GEN
Solar/Wind Harmer
12.462
316005AA1-067
Solar/Wind Harmer
0.494
3145746EVERETS
Solar/Wind Harmer
-0.097
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.208
316319Z2-044 C
Solar/Wind Harmer
1.348
957861AF2-080 GEN
Solar/Wind Harmer
10.667
316420AA1-050 GEN
Solar/Wind Harmer
2.781
3145573BETHELC
Solar/Wind Harmer
-0.024
3145573BETHELC
Solar/Wind Harmer
-0.024
316311AC2-079 GEN
Solar/Wind Harmer
12.096
315833AF1-017_GEN
Solar/Wind Harmer
4.55
316349AD2-085 GEN
Solar/Wind Harmer
2.131
316239AB2-077_GEN
Solar/Wind Harmer
0.695
316238AB2-078_GEN
Solar/Wind Harmer
0.695
3147173SINAI
Solar/Wind Harmer
-0.023
3147243WELCO
Solar/Wind Harmer
-0.014
316118AC1-105 GEN
Solar/Wind Harmer
1.583
3143316POE
Solar/Wind Harmer
-0.09
3151041BRUNSWICKG3
50/50
4.211
972187AH1-678 GEN
50/50
9.663
970933AG2-581 GEN
Solar/Wind Harmer
32.122
970099AG2-077 GEN
Solar/Wind Harmer
37.73
3144356SAPONY
Solar/Wind Harmer
0.991
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316185AD1-033 GEN
Solar/Wind Harmer
2.733
316339AD2-160 GEN
Solar/Wind Harmer
1.745
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.052
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
3142956BIRDNECK
Solar/Wind Harmer
1.38
316316AC1-027 C
Solar/Wind Harmer
0.789
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.638
316433W1029_GEN2
Solar/Wind Harmer
4.638
316181AB2-040 GEN
Solar/Wind Harmer
3.567
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316036AC1-147 C
Solar/Wind Harmer
0.688
3150991CHESPKB
Adder
2.376
3150991CHESPKB
Adder
2.319
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.845
3145593CAROLNA
Solar/Wind Harmer
0.21
316426AA2-053 GEN
Solar/Wind Harmer
2.552
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
2.394
3145783HORNRTN
Solar/Wind Harmer
0.748
3145783HORNRTN
Solar/Wind Harmer
0.299
316065AD1-022 GEN
Solar/Wind Harmer
12.605
3145893MURPHYS
Solar/Wind Harmer
0.703
3145893MURPHYS
Solar/Wind Harmer
-0.045
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.631
316274AC1-208 GEN
Solar/Wind Harmer
2.679
3145933PARMELE
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.025
939181AE1-148 GEN
Solar/Wind Harmer
13.708
3145493TOT1
Solar/Wind Harmer
0.376
3145453TOT5
Solar/Wind Harmer
0.226
3145603CNETO
Solar/Wind Harmer
0.151
961601AG1-000A GEN
Solar/Wind Harmer
9.538
316263AC1-034 GEN
Solar/Wind Harmer
11.37
3146843MT LREL
Solar/Wind Harmer
-0.023
3146843MT LREL
Solar/Wind Harmer
-0.023
964791AG1-342 GEN
Solar/Wind Harmer
4.916
962561AG1-105 GEN
Solar/Wind Harmer
12.943
313527AB2-043 GEN
Solar/Wind Harmer
3.735
316222AC1-221 GEN
Solar/Wind Harmer
2.263
970657AG2-426 GEN
Solar/Wind Harmer
6.965
970657AG2-426 GEN
Solar/Wind Harmer
1.456
316236AE1-162_GEN
Solar/Wind Harmer
0.669
971741AH1-377 GEN
Solar/Wind Harmer
25.152
970323AG2-213 GEN
Solar/Wind Harmer
10.321
971775AH1-396 GEN
Solar/Wind Harmer
1.47
316034AC1-036 C
Solar/Wind Harmer
0.383
970301AG2-198 GEN
Solar/Wind Harmer
9.888
3144293JTRSVLE
Adder
0.527
3144293JTRSVLE
Adder
0.444
944641AF1-129 GEN
Adder
54.839
316447AC1-158 HLD
Solar/Wind Helper
2.734
971795AH1-408 GEN
Solar/Wind Harmer
18.929
3145783HORNRTN
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.3
3145893MURPHYS
Solar/Wind Harmer
-0.1
3145893MURPHYS
Solar/Wind Harmer
0.747
3146263WOODLND
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
316093AE2-104_GEN
Solar/Wind Harmer
7.308
3145823KELFORD
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.01
316129AC1-054 GEN
Solar/Wind Harmer
2.182
3145963POPLR C
Solar/Wind Harmer
-0.025
971065AG2-659 GEN
Solar/Wind Harmer
12.425
316212AC1-099_GEN
Solar/Wind Harmer
2.165
316174AB2-169 GEN
Solar/Wind Harmer
3.827
315722AD1-056 GEN
Solar/Wind Harmer
2.593
3146293MARTNCO
Solar/Wind Harmer
0.152
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3146233WITAKRS
Solar/Wind Harmer
-0.097
316494AC1-189 GEN
Solar/Wind Harmer
2.623
961671AG1-007 GEN
Solar/Wind Harmer
0.308
3146083TARBORO
Solar/Wind Harmer
-0.024
3145493TOT1
Solar/Wind Harmer
0.722
316359AB2-059 GEN
Solar/Wind Harmer
3.27
316049AB1-081 GEN
Solar/Wind Harmer
2.617
3142053HEARTS
Solar/Wind Harmer
0.285
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316072AD1-144
Solar/Wind Harmer
0.489
316237AB2-079_GEN
Solar/Wind Harmer
0.695
970401AG2-262 GEN
Solar/Wind Harmer
1.502
970661AG2-428 GEN
Solar/Wind Harmer
24.038
3145336SMITFLD
Solar/Wind Harmer
-0.088
316381AD1-082 GEN
Solar/Wind Harmer
2.025
970659AG2-427 GEN
Solar/Wind Harmer
11.632
316003AC1-222 GEN
Solar/Wind Harmer
2.12
3151171GRAVELC
Adder
1.904
970685AG2-442 GEN
Solar/Wind Harmer
17.147
3138126ROCKLANDING
Solar/Wind Harmer
0.058
3144293JTRSVLE
Adder
0.527
3143226MDLTHAN
Solar/Wind Helper
0.287
316045AC1-158 PL2
Solar/Wind Helper
3.977
961611AG1-000B GEN
Solar/Wind Harmer
2.084
971445AH1-216 GEN
Solar/Wind Harmer
13.611
971443AH1-215 GEN
Solar/Wind Harmer
4.082
3144303KENBRDG
Solar/Wind Harmer
-0.016
972265AH1-717 GEN
Adder
13.901
3151201GRAVEL4
Adder
13.031
3151191GRAVEL3
Adder
12.866
3151211GRAVEL5
Adder
12.866
970683AG2-441 GEN
Solar/Wind Harmer
15.31
970681AG2-440 GEN
Solar/Wind Harmer
12.248
970865AG2-541 GEN
Solar/Wind Harmer
7.877
270455AD2-022 GEN
Solar/Wind Harmer
3.414
270457AD2-023 GEN
Solar/Wind Harmer
1.731
NYPJM->LTFIMP_NY
CLTF
2.139
LGEELTFEXP_LGEE->PJM
CLTF
1.496
LAGNLTFEXP_LAGN->PJM
CLTF
10.658
WECLTFEXP_WEC->PJM
CLTF
0.787
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.715
TVALTFEXP_TVA->PJM
CLTF
5.269
CPLELTFEXP_CPLE->PJM
CLTF
15.822
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.369
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.217
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.694
MECLTFEXP_MEC->PJM
CLTF
4.528
SIGELTFEXP_SIGE->PJM
CLTF
0.13

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.59 %
Rating:3966.0 MVA
Rating Type:C
MVA to Mitigate:4861.73
MW Contribution:10.14
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
71.798
3150411LDYSMT5
50/50
29.26
3150381LDYSMT2
50/50
28.002
972213AH1-691 GEN
50/50
4.737
972215AH1-692 GEN
50/50
4.737
963051AG1-154 GEN
50/50
3.644
316164AC1-076 GEN
Solar/Wind Harmer
1.977
972189AH1-679 GEN
Adder
3.432
316312AB1-027
Solar/Wind Harmer
0.761
316233AE1-074 FULL
Solar/Wind Harmer
0.6
971281AH1-106 GEN
Solar/Wind Harmer
3.623
971283AH1-107 GEN
Solar/Wind Harmer
3.623
971285AH1-108 GEN
Adder
1.491
315976AC1-164 GENA
Solar/Wind Harmer
23.237
316169AC1-164_GENC
Solar/Wind Harmer
20.075
315975AC1-164 GENB
Solar/Wind Harmer
0.687
316132AB2-190 GEN1
Solar/Wind Harmer
2.192
316369SG1_INVT
Solar/Wind Harmer
3.854
972265AH1-717 GEN
Adder
14.786
3151201GRAVEL4
Adder
13.861
3151191GRAVEL3
Adder
13.685
3151211GRAVEL5
Adder
13.685
971167AH1-042 GEN
Solar/Wind Harmer
20.562
971445AH1-216 GEN
Solar/Wind Harmer
13.194
3143316POE
Solar/Wind Harmer
-0.084
3142433PROV 92
Adder
0.369
3142433PROV 92
Adder
0.369
3151081ELIZAR1
Adder
17.279
3151091ELIZAR2
Adder
16.979
3152611GOSPORTB
Adder
2.4
3152621GOSPORTC
Adder
2.037
3152601GOSPORTA
Adder
1.879
3143873LANEXA
Solar/Wind Harmer
-0.013
957831AF2-077 GEN
Solar/Wind Harmer
0.633
3138283WHITEMARSH
Solar/Wind Harmer
0.033
957871AF2-081 GEN
Solar/Wind Harmer
10.484
316314AB2-024 C
Solar/Wind Harmer
1.791
315833AF1-017_GEN
Solar/Wind Harmer
3.976
316349AD2-085 GEN
Solar/Wind Harmer
1.862
316311AC2-079 GEN
Solar/Wind Harmer
10.556
319010AE1-072 C
Solar/Wind Harmer
4.229
3146406KITTY HAWK
Solar/Wind Harmer
0.017
316305AF2-043 C
Solar/Wind Harmer
0.63
316059AD1-063 C
Solar/Wind Harmer
0.471
315835AF2-110_GEN
Solar/Wind Harmer
2.598
315662AE1-191 GEN
Solar/Wind Harmer
2.502
315666AE1-190 GEN
Solar/Wind Harmer
0.626
313526AB2-022
Solar/Wind Harmer
0.559
957601AF2-054 GEN
Solar/Wind Harmer
0.618
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
3141873WAN 176
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.556
3146396TANGLEW
Solar/Wind Harmer
0.379
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
3141913WHIT STONE
Solar/Wind Harmer
-0.02
316315AB2-025 C
Solar/Wind Harmer
0.548
941031AE2-094 GEN
Solar/Wind Harmer
38.047
944011AF1-069 GEN
Solar/Wind Harmer
11.921
3138133OCRAN
Solar/Wind Harmer
-0.006
315814AE2-033 C
Solar/Wind Harmer
18.834
315611Z1-036_GEN2
Solar/Wind Harmer
4.975
3141783LANCAST
Solar/Wind Harmer
-0.012
3141783LANCAST
Solar/Wind Harmer
-0.008
970673AG2-436 GEN
Solar/Wind Harmer
41.947
970673AG2-436 GEN
Solar/Wind Harmer
21.239
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
962981AG1-147 GEN
Solar/Wind Harmer
8.653
971967AH1-528 GEN
Solar/Wind Harmer
37.117
315816AE2-034 GEN
Solar/Wind Harmer
1.575
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
315732AD1-074 GEN1
Solar/Wind Harmer
3.857
315733AD1-074 GEN2
Solar/Wind Harmer
3.857
315735AD1-075 GEN1
Solar/Wind Harmer
1.929
965291AG1-394 GEN
Solar/Wind Harmer
1.684
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.26
970085AG2-068 GEN
Solar/Wind Harmer
11.786
970581AG2-369 GEN
Solar/Wind Harmer
10.136
316318V4-068
Solar/Wind Harmer
0.469
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3141813NORNECK
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.139
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.412
315607AA1-063A GEN
Solar/Wind Harmer
1.855
316087AB2-174 GEN
Solar/Wind Harmer
2.603
315652AC1-086 GEN
Solar/Wind Harmer
20.378
3137643SOCKMAN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
972193AH1-681 GEN
Adder
3.136
972205AH1-687 GEN
Adder
5.738
3152261N ANNA2
50/50
11.837
970497AG2-320 GEN
50/50
20.71
3150401LDYSMT4
50/50
29.168
3150371LDYSMT1
50/50
28.185
315051AA1-145 CT1
50/50
1.625
316044AC1-158 PL1
Solar/Wind Harmer
2.804
316450AC1-158 RIC
Solar/Wind Harmer
0.748
966881AG1-559 GEN
Solar/Wind Harmer
0.692
3142416OLDCHRC
Solar/Wind Harmer
2.276
970293AG2-193 GEN
Solar/Wind Harmer
2.786
3150861SPRUNCD
Adder
0.911
3143096IRON208
Adder
0.827
3143096IRON208
Adder
0.81
3142946ENON
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
2.356
970133AG2-095 GEN
Solar/Wind Harmer
2.451
970129AG2-093 GEN
Solar/Wind Harmer
12.209
316382AG1-145 C
Solar/Wind Harmer
0.653
965281AG1-393 GEN
Solar/Wind Harmer
2.702
315778AD1-151 GEN
Solar/Wind Harmer
18.722
315839AE2-212 C
Solar/Wind Harmer
0.651
961611AG1-000B GEN
Solar/Wind Harmer
4.519
3144216WINCHST
Adder
0.719
3150921YORKTN3
Adder
4.794
315773AC2-141 GEN
Solar/Wind Harmer
8.967
3151221GRAVEL6
Adder
13.845
3151171GRAVELC
Adder
2.664
315813AE1-149 C
Solar/Wind Harmer
13.325
3145336SMITFLD
Solar/Wind Harmer
-0.008
3142433PROV 92
Adder
0.369
3142433PROV 92
Adder
0.369
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.995
944581AF1-123 GEN
Solar/Wind Harmer
96.352
944601AF1-125 GEN
Solar/Wind Harmer
94.848
3151101ELIZAR3
Adder
17.5
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316083AB2-161 GEN
Solar/Wind Harmer
3.436
970661AG2-428 GEN
Solar/Wind Harmer
3.973
3146456SLIGO L269
Solar/Wind Harmer
-0.021
971153AH1-033 GEN
Solar/Wind Harmer
2.551
3141766HARMONY
Solar/Wind Harmer
1.855
3141843SHACKLE
Adder
0.947
316203AE2-005 GEN
Solar/Wind Harmer
8.783
316280AD1-041 GEN
Solar/Wind Harmer
1.564
316320Y1-086
Solar/Wind Harmer
1.214
316156AD2-030 GEN
Solar/Wind Harmer
0.552
3141873WAN 176
Solar/Wind Harmer
2.451
316435W1029_GEN3
Solar/Wind Harmer
3.714
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.02
962971AG1-146 GEN
Solar/Wind Harmer
3.709
316484AD2-074 GEN
Solar/Wind Harmer
4.929
970009AG2-005 GEN
Solar/Wind Harmer
2.448
315614AA2-178 GEN
Solar/Wind Harmer
2.1
316313AB2-026
Solar/Wind Harmer
0.523
316258AE1-075 C
Solar/Wind Harmer
0.471
316405AF2-144 C
Solar/Wind Harmer
0.497
3143336POWHATN
Solar/Wind Harmer
1.956
316404AE1-155 C
Solar/Wind Harmer
3.715
3147666LOUISA
Solar/Wind Harmer
-0.044
971157AH1-035 GEN
Solar/Wind Harmer
2.392
315737AD1-076 GEN
Solar/Wind Harmer
3.625
3156081AA2-088 GEN
Solar/Wind Harmer
6.186
970917AG2-570 GEN
Solar/Wind Harmer
47.325
3146206CASHIE
Solar/Wind Harmer
-0.019
316365GEN2_N
Solar/Wind Harmer
1.272
3145893MURPHYS
Solar/Wind Harmer
0.131
3145893MURPHYS
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.773
961681AG1-008 GEN
Solar/Wind Harmer
14.773
3150351NORNECKC2
Adder
1.686
3146173TUNIS
Solar/Wind Harmer
-0.019
3156021HOLLOMANSOL
Solar/Wind Harmer
2.506
316463AE2-346 GEN
Solar/Wind Harmer
0.3
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.318
971781AH1-399 GEN
Solar/Wind Harmer
1.141
966621AG1-532 GEN
Solar/Wind Harmer
0.373
3146263WOODLND
Solar/Wind Harmer
-0.018
971507AH1-251 GEN
50/50
14.786
3152251N ANNA1
50/50
11.838
972197AH1-683 GEN
50/50
4.555
972219AH1-694 GEN
50/50
3.279
315052AA1-145 CT2
50/50
1.632
316045AC1-158 PL2
Solar/Wind Harmer
8.968
966881AG1-559 GEN
Solar/Wind Harmer
0.237
3142416OLDCHRC
Solar/Wind Harmer
-0.058
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3143526WINTERP
Solar/Wind Harmer
-0.115
3143226MDLTHAN
Solar/Wind Harmer
-0.022
3150851SPRUNCC
Adder
0.911
3143096IRON208
Adder
0.827
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
93.32
970129AG2-093 GEN
Solar/Wind Harmer
4.946
316458AB2-190 GEN2
Solar/Wind Harmer
2.192
315671AE2-027_GEN
Solar/Wind Harmer
16.243
316159AE1-175 C
Solar/Wind Harmer
0.581
971069AG2-661 GEN
Solar/Wind Harmer
3.42
971647AH1-324 GEN
Solar/Wind Harmer
10.758
961611AG1-000B GEN
Solar/Wind Harmer
10.592
3138126ROCKLANDING
Solar/Wind Harmer
0.066
316294AC1-161 GEN
Solar/Wind Harmer
6.933
971317AH1-138 GEN
Solar/Wind Harmer
2.677
3151171GRAVELC
Adder
2.026
3145336SMITFLD
Solar/Wind Harmer
-0.085
3142433PROV 92
Solar/Wind Harmer
-0.085
3142433PROV 92
Adder
0.369
3142433PROV 92
Adder
0.369
970659AG2-427 GEN
Solar/Wind Harmer
11.259
944591AF1-124 GEN
Solar/Wind Harmer
96.699
316375AC2-012 GEN
Solar/Wind Harmer
7.327
3150981CHESPKA
Adder
2.353
316381AD1-082 GEN
Solar/Wind Harmer
1.941
970661AG2-428 GEN
Solar/Wind Harmer
22.42
939411AE1-173 GEN
Solar/Wind Harmer
105.248
940641AE2-051 GEN
Solar/Wind Harmer
19.719
316072AD1-144
Solar/Wind Harmer
0.425
316388AE2-253 GEN
Solar/Wind Harmer
1.415
3146456SLIGO L269
Solar/Wind Harmer
-0.021
316246AF1-032 C
Solar/Wind Harmer
0.423
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.45
3141843SHACKLE
Adder
0.947
316093AE2-104_GEN
Solar/Wind Harmer
6.043
3146516WINFALL
Solar/Wind Harmer
-0.066
3146516WINFALL
Solar/Wind Harmer
-0.02
3138133OCRAN
Solar/Wind Harmer
-0.012
315800Z1-036_GEN1
Solar/Wind Harmer
4.975
3130156CHOWAN
Solar/Wind Harmer
-0.02
961951AG1-038 GEN
Solar/Wind Harmer
2.579
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.248
3143336POWHATN
Solar/Wind Harmer
2.302
962861AG1-135 GEN
Solar/Wind Harmer
7.254
3147666LOUISA
Solar/Wind Harmer
-0.076
964211AG1-282 GEN
Solar/Wind Harmer
0.571
3141726DUNNSVL
Solar/Wind Harmer
-0.076
970919AG2-571 GEN
Solar/Wind Harmer
5.991
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.72
970087AG2-069 GEN
Solar/Wind Harmer
17.679
316023GEN1_S
Solar/Wind Harmer
1.272
316192AB2-158 GEN
Solar/Wind Harmer
2.241
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.558
3150351NORNECKC2
Adder
1.658
316336AC2-165 C
Solar/Wind Harmer
3.24
3146173TUNIS
Solar/Wind Harmer
-0.019
3145683EARLEYS
Solar/Wind Harmer
-0.018
960081AF2-299 GEN
Solar/Wind Harmer
2.069
3146263WOODLND
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
957481AF2-042 GEN
Solar/Wind Harmer
56.829
316011AB1-132 GEN
Solar/Wind Harmer
3.79
962571AG1-106 GEN
Solar/Wind Harmer
2.604
3145823KELFORD
Solar/Wind Harmer
-0.018
316190AA2-174 GEN
Solar/Wind Harmer
0.222
316174AB2-169 GEN
Solar/Wind Harmer
2.78
971795AH1-408 GEN
Solar/Wind Harmer
13.508
315693AD1-088 GEN
Solar/Wind Harmer
8.939
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.436
3144293JTRSVLE
Adder
0.467
972277AH1-723 GEN
Adder
81.777
3151751LOISA D
Adder
7.363
962491AG1-098 GEN
Solar/Wind Harmer
11.83
3150391LDYSMT3
50/50
29.114
972195AH1-682 GEN
50/50
3.826
316447AC1-158 HLD
Solar/Wind Harmer
6.165
315673AE1-157 GEN
Solar/Wind Harmer
17.268
957411AF2-035 GEN
Solar/Wind Harmer
10.36
970317AG2-208 GEN
Solar/Wind Harmer
10.072
3142296MT RD221
Adder
0.648
3142366NRTHEST
Adder
0.652
3150691DARBY 3
Adder
14.334
3150701DARBY 4
Adder
14.301
3150681DARBY 2
Adder
14.284
3150671DARBY 1
Adder
14.268
3143526WINTERP
Solar/Wind Harmer
-0.115
971223AH1-071 GEN
Solar/Wind Harmer
2.782
316075AC2-137 C
Solar/Wind Harmer
0.598
3142946ENON
Solar/Wind Harmer
-0.002
966871AG1-558 GEN
Solar/Wind Harmer
0.658
966871AG1-558 GEN
Solar/Wind Harmer
0.225
944641AF1-129 GEN
Adder
92.674
316240AF1-291 C
Solar/Wind Harmer
0.657
316033AB2-134 GEN
Solar/Wind Harmer
6.956
315697AD1-025 GEN
Solar/Wind Harmer
4.362
316236AE1-162_GEN
Solar/Wind Harmer
0.642
316036AC1-147 C
Solar/Wind Harmer
0.571
3150991CHESPKB
Adder
1.974
3150991CHESPKB
Adder
1.926
970657AG2-426 GEN
Solar/Wind Harmer
6.608
970657AG2-426 GEN
Solar/Wind Harmer
1.382
316316AC1-027 C
Solar/Wind Harmer
0.649
3142956BIRDNECK
Solar/Wind Harmer
1.134
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.415
316018AA1-139 ULT2
Solar/Wind Harmer
1.796
316017AA1-139 ULT1
Solar/Wind Harmer
1.697
3137176SLIGO L2192
Solar/Wind Harmer
-0.083
3146456SLIGO L269
Solar/Wind Harmer
2.471
3130086AYDLETT
Solar/Wind Harmer
-0.083
316441AF1-014 GEN
Solar/Wind Harmer
1.404
3146386ELIZ CT
Solar/Wind Harmer
-0.021
316431W1029_GEN1
Solar/Wind Harmer
3.714
316433W1029_GEN2
Solar/Wind Harmer
3.714
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3144356SAPONY
Solar/Wind Harmer
0.708
315742AE1-103 GEN
Solar/Wind Harmer
2.091
3146376EDENTON
Solar/Wind Harmer
0.59
3146376EDENTON
Solar/Wind Harmer
0.59
972185AH1-677 GEN
Adder
9.891
972187AH1-678 GEN
Adder
4.965
316487AF1-042 GEN
Solar/Wind Harmer
2.579
970933AG2-581 GEN
Solar/Wind Harmer
18.105
958261AF2-120 GEN
Solar/Wind Harmer
7.463
316065AD1-022 GEN
Solar/Wind Harmer
9.475
3145893MURPHYS
Solar/Wind Harmer
0.525
3145893MURPHYS
Solar/Wind Harmer
-0.034
316077AC2-138 C
Solar/Wind Harmer
0.394
3150341NORNECKC1
Adder
1.741
3150341NORNECKC1
Adder
1.727
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
316468AD1-105 GEN
Solar/Wind Harmer
2.063
316181AB2-040 GEN
Solar/Wind Harmer
2.537
970099AG2-077 GEN
Solar/Wind Harmer
22.731
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.824
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.021
3145593CAROLNA
Solar/Wind Harmer
0.149
3145783HORNRTN
Solar/Wind Harmer
2.12
3145783HORNRTN
Solar/Wind Harmer
1.696
3145783HORNRTN
Solar/Wind Harmer
0.53
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3144293JTRSVLE
Adder
0.467
3144293JTRSVLE
Adder
0.393
3151731LOISA B
Adder
7.363
3151721LOISA A
Adder
7.325
313506AB2-031 GEN
Solar/Wind Harmer
1.462
3145963POPLR C
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.853
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3144293JTRSVLE
Adder
0.467
972255AH1-712 GEN
Adder
70.176
3151761LOISA E
Adder
15.011
3141196NOKESVL
Solar/Wind Helper
1.31
NYPJM->LTFIMP_NY
CLTF
2.833
LAGNLTFEXP_LAGN->PJM
CLTF
7.028
LGEELTFEXP_LGEE->PJM
CLTF
1.274
WECLTFEXP_WEC->PJM
CLTF
0.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.882
TVALTFEXP_TVA->PJM
CLTF
3.562
CPLELTFEXP_CPLE->PJM
CLTF
9.417
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.314
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.222
MECLTFEXP_MEC->PJM
CLTF
3.393
SIGELTFEXP_SIGE->PJM
CLTF
0.104

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.53 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5687.82
MW Contribution:12.47
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
86.479
3150411LDYSMT5
50/50
37.377
3150381LDYSMT2
50/50
35.771
972213AH1-691 GEN
50/50
6.051
972215AH1-692 GEN
50/50
6.051
963051AG1-154 GEN
50/50
4.655
972189AH1-679 GEN
Adder
4.292
316312AB1-027
Solar/Wind Harmer
0.945
316164AC1-076 GEN
Solar/Wind Harmer
2.342
316233AE1-074 FULL
Solar/Wind Harmer
0.742
971281AH1-106 GEN
Solar/Wind Harmer
4.482
971283AH1-107 GEN
Solar/Wind Harmer
4.482
971285AH1-108 GEN
Adder
1.847
315976AC1-164 GENA
Solar/Wind Harmer
28.89
316169AC1-164_GENC
Solar/Wind Harmer
24.958
315975AC1-164 GENB
Solar/Wind Harmer
0.855
316132AB2-190 GEN1
Solar/Wind Harmer
2.717
316369SG1_INVT
Solar/Wind Harmer
4.774
971167AH1-042 GEN
Solar/Wind Harmer
25.638
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
972265AH1-717 GEN
Adder
18.308
3151201GRAVEL4
Adder
17.163
3151191GRAVEL3
Adder
16.945
3151211GRAVEL5
Adder
16.945
971445AH1-216 GEN
Solar/Wind Harmer
16.329
3143316POE
Solar/Wind Harmer
-0.104
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.789
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.241
3151081ELIZAR1
Adder
21.363
3151091ELIZAR2
Adder
20.992
3152611GOSPORTB
Adder
2.967
3152621GOSPORTC
Adder
2.518
3152601GOSPORTA
Adder
2.323
316059AD1-063 C
Solar/Wind Harmer
0.59
315662AE1-191 GEN
Solar/Wind Harmer
3.133
315666AE1-190 GEN
Solar/Wind Harmer
0.783
957871AF2-081 GEN
Solar/Wind Harmer
12.957
315833AF1-017_GEN
Solar/Wind Harmer
4.915
316349AD2-085 GEN
Solar/Wind Harmer
2.301
957601AF2-054 GEN
Solar/Wind Harmer
0.774
3141873WAN 176
Solar/Wind Harmer
-0.005
316311AC2-079 GEN
Solar/Wind Harmer
13.05
319010AE1-072 C
Solar/Wind Harmer
5.227
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.778
315835AF2-110_GEN
Solar/Wind Harmer
3.211
313526AB2-022
Solar/Wind Harmer
0.69
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.687
3146396TANGLEW
Solar/Wind Harmer
0.469
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.676
941031AE2-094 GEN
Solar/Wind Harmer
46.894
944011AF1-069 GEN
Solar/Wind Harmer
14.693
962981AG1-147 GEN
Solar/Wind Harmer
10.926
315814AE2-033 C
Solar/Wind Harmer
23.239
315611Z1-036_GEN2
Solar/Wind Harmer
6.142
970673AG2-436 GEN
Solar/Wind Harmer
51.677
970673AG2-436 GEN
Solar/Wind Harmer
26.165
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
971967AH1-528 GEN
Solar/Wind Harmer
45.703
315816AE2-034 GEN
Solar/Wind Harmer
1.942
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.753
315733AD1-074 GEN2
Solar/Wind Harmer
4.753
315735AD1-075 GEN1
Solar/Wind Harmer
2.377
965291AG1-394 GEN
Solar/Wind Harmer
2.074
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.174
970085AG2-068 GEN
Solar/Wind Harmer
14.495
970581AG2-369 GEN
Solar/Wind Harmer
12.466
316318V4-068
Solar/Wind Harmer
0.577
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.172
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.506
315607AA1-063A GEN
Solar/Wind Harmer
2.282
316087AB2-174 GEN
Solar/Wind Harmer
3.201
315652AC1-086 GEN
Solar/Wind Harmer
25.058
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
972193AH1-681 GEN
Adder
3.782
972205AH1-687 GEN
Adder
6.911
316411AF1-147_GEN1
Solar/Wind Helper
0.808
316415AF1-147_GEN2
Solar/Wind Helper
0.808
3138216PACIFIC
Solar/Wind Helper
0.039
3152261N ANNA2
50/50
14.608
970497AG2-320 GEN
50/50
26.225
3150401LDYSMT4
50/50
37.261
3150371LDYSMT1
50/50
36.004
315051AA1-145 CT1
50/50
2.032
316044AC1-158 PL1
Solar/Wind Harmer
3.455
316450AC1-158 RIC
Solar/Wind Harmer
0.921
966881AG1-559 GEN
Solar/Wind Harmer
0.876
3142416OLDCHRC
Solar/Wind Harmer
2.828
970293AG2-193 GEN
Solar/Wind Harmer
3.46
3143096IRON208
Adder
1.026
3143096IRON208
Adder
1.006
3150861SPRUNCD
Adder
1.129
316473AC1-191 GEN
Solar/Wind Harmer
2.944
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.038
316382AG1-145 C
Solar/Wind Harmer
0.81
970129AG2-093 GEN
Solar/Wind Harmer
15.13
315778AD1-151 GEN
Solar/Wind Harmer
23.197
965281AG1-393 GEN
Solar/Wind Harmer
3.347
315839AE2-212 C
Solar/Wind Harmer
0.806
3150921YORKTN3
Adder
5.947
3144216WINCHST
Adder
0.892
961611AG1-000B GEN
Solar/Wind Harmer
5.597
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
315773AC2-141 GEN
Solar/Wind Harmer
11.086
3151221GRAVEL6
Adder
17.143
3151171GRAVELC
Adder
3.298
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.487
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.468
944581AF1-123 GEN
Solar/Wind Harmer
119.107
944601AF1-125 GEN
Solar/Wind Harmer
117.248
3151101ELIZAR3
Adder
21.637
316083AB2-161 GEN
Solar/Wind Harmer
4.25
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.914
3141766HARMONY
Solar/Wind Harmer
2.322
3141843SHACKLE
Adder
1.186
316203AE2-005 GEN
Solar/Wind Harmer
10.992
316280AD1-041 GEN
Solar/Wind Harmer
1.958
316156AD2-030 GEN
Solar/Wind Harmer
0.691
3141873WAN 176
Solar/Wind Harmer
3.071
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.152
316320Y1-086
Solar/Wind Harmer
1.5
316435W1029_GEN3
Solar/Wind Harmer
4.587
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.683
316484AD2-074 GEN
Solar/Wind Harmer
6.235
970009AG2-005 GEN
Solar/Wind Harmer
3.096
3146376EDENTON
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.714
315614AA2-178 GEN
Solar/Wind Harmer
2.59
3150351NORNECKC2
Adder
2.151
971781AH1-399 GEN
Solar/Wind Harmer
1.468
316313AB2-026
Solar/Wind Harmer
0.641
316258AE1-075 C
Solar/Wind Harmer
0.577
316405AF2-144 C
Solar/Wind Harmer
0.609
3143336POWHATN
Solar/Wind Harmer
2.398
971157AH1-035 GEN
Solar/Wind Harmer
2.948
315737AD1-076 GEN
Solar/Wind Harmer
4.467
3156081AA2-088 GEN
Solar/Wind Harmer
7.621
970917AG2-570 GEN
Solar/Wind Harmer
58.212
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.565
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.189
961681AG1-008 GEN
Solar/Wind Harmer
18.189
3147666LOUISA
Solar/Wind Harmer
-0.053
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.086
316463AE2-346 GEN
Solar/Wind Harmer
0.369
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.853
966621AG1-532 GEN
Solar/Wind Harmer
0.459
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.797
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.049
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.569
972255AH1-712 GEN
Adder
84.642
3141316ARNOLDS
Adder
0.325
3151761LOISA E
Adder
17.177
972183AH1-676 GEN
Adder
134.74
3150331BIRCHWDA
Adder
21.291
3141196NOKESVL
Solar/Wind Helper
1.243
971507AH1-251 GEN
50/50
17.806
3152251N ANNA1
50/50
14.609
972197AH1-683 GEN
50/50
5.818
972219AH1-694 GEN
50/50
4.189
315052AA1-145 CT2
50/50
2.041
316045AC1-158 PL2
Solar/Wind Harmer
11.053
966881AG1-559 GEN
Solar/Wind Harmer
0.3
3142416OLDCHRC
Solar/Wind Harmer
-0.073
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.143
3143096IRON208
Adder
1.026
3150851SPRUNCC
Adder
1.129
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
115.833
316159AE1-175 C
Solar/Wind Harmer
0.721
970129AG2-093 GEN
Solar/Wind Harmer
6.129
316458AB2-190 GEN2
Solar/Wind Harmer
2.717
315671AE2-027_GEN
Solar/Wind Harmer
20.126
971069AG2-661 GEN
Solar/Wind Harmer
4.237
971647AH1-324 GEN
Solar/Wind Harmer
13.325
971317AH1-138 GEN
Solar/Wind Harmer
3.325
3138126ROCKLANDING
Solar/Wind Harmer
0.081
961611AG1-000B GEN
Solar/Wind Harmer
13.118
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
316294AC1-161 GEN
Solar/Wind Harmer
8.571
3151171GRAVELC
Adder
2.508
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.927
944591AF1-124 GEN
Solar/Wind Harmer
119.536
316375AC2-012 GEN
Solar/Wind Harmer
9.059
3150981CHESPKA
Adder
2.909
316381AD1-082 GEN
Solar/Wind Harmer
2.401
970661AG2-428 GEN
Solar/Wind Harmer
27.727
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.066
3141843SHACKLE
Adder
1.186
939411AE1-173 GEN
Solar/Wind Harmer
129.946
316072AD1-144
Solar/Wind Harmer
0.526
940641AE2-051 GEN
Solar/Wind Harmer
24.336
316388AE2-253 GEN
Solar/Wind Harmer
1.749
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.522
316093AE2-104_GEN
Solar/Wind Harmer
7.468
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.142
961951AG1-038 GEN
Solar/Wind Harmer
3.263
3130156CHOWAN
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
9.197
964211AG1-282 GEN
Solar/Wind Harmer
0.726
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.501
3150351NORNECKC2
Adder
2.116
3143336POWHATN
Solar/Wind Harmer
2.821
970919AG2-571 GEN
Solar/Wind Harmer
7.369
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.814
316023GEN1_S
Solar/Wind Harmer
1.565
970087AG2-069 GEN
Solar/Wind Harmer
21.743
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.687
3147666LOUISA
Solar/Wind Harmer
-0.092
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.613
316336AC2-165 C
Solar/Wind Harmer
3.962
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.544
3146263WOODLND
Solar/Wind Harmer
-0.022
316192AB2-158 GEN
Solar/Wind Harmer
2.682
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.745
316011AB1-132 GEN
Solar/Wind Harmer
4.66
962571AG1-106 GEN
Solar/Wind Harmer
3.202
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.273
316174AB2-169 GEN
Solar/Wind Harmer
3.419
971795AH1-408 GEN
Solar/Wind Harmer
16.592
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.957
3147043LAWRENC
Adder
1.763
3144293JTRSVLE
Adder
0.569
972277AH1-723 GEN
Adder
98.633
3151751LOISA D
Adder
8.426
962491AG1-098 GEN
Solar/Wind Harmer
13.911
3150391LDYSMT3
50/50
37.191
972195AH1-682 GEN
50/50
4.887
316447AC1-158 HLD
Solar/Wind Harmer
7.599
315673AE1-157 GEN
Solar/Wind Harmer
21.923
957411AF2-035 GEN
Solar/Wind Harmer
13.105
970317AG2-208 GEN
Solar/Wind Harmer
12.741
3142296MT RD221
Adder
0.804
3142366NRTHEST
Adder
0.81
3150691DARBY 3
Adder
17.798
3150701DARBY 4
Adder
17.756
3150681DARBY 2
Adder
17.736
3150671DARBY 1
Adder
17.715
3143526WINTERP
Solar/Wind Harmer
-0.143
316075AC2-137 C
Solar/Wind Harmer
0.743
971223AH1-071 GEN
Solar/Wind Harmer
3.437
966871AG1-558 GEN
Solar/Wind Harmer
0.823
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
114.823
316240AF1-291 C
Solar/Wind Harmer
0.813
316033AB2-134 GEN
Solar/Wind Harmer
8.617
315697AD1-025 GEN
Solar/Wind Harmer
5.404
316236AE1-162_GEN
Solar/Wind Harmer
0.795
316036AC1-147 C
Solar/Wind Harmer
0.706
3150991CHESPKB
Adder
2.44
3150991CHESPKB
Adder
2.382
970657AG2-426 GEN
Solar/Wind Harmer
8.172
970657AG2-426 GEN
Solar/Wind Harmer
1.709
316316AC1-027 C
Solar/Wind Harmer
0.802
3142956BIRDNECK
Solar/Wind Harmer
1.402
316185AD1-033 GEN
Solar/Wind Harmer
2.752
316441AF1-014 GEN
Solar/Wind Harmer
1.757
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.749
316018AA1-139 ULT2
Solar/Wind Harmer
2.22
316017AA1-139 ULT1
Solar/Wind Harmer
2.097
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.054
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.587
316433W1029_GEN2
Solar/Wind Harmer
4.587
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.874
316487AF1-042 GEN
Solar/Wind Harmer
3.263
315742AE1-103 GEN
Solar/Wind Harmer
2.58
3146376EDENTON
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.728
958261AF2-120 GEN
Solar/Wind Harmer
9.47
972185AH1-677 GEN
Adder
12.182
972187AH1-678 GEN
Adder
6.113
316077AC2-138 C
Solar/Wind Harmer
0.503
3150341NORNECKC1
Adder
2.222
3150341NORNECKC1
Adder
2.205
316468AD1-105 GEN
Solar/Wind Harmer
2.653
970933AG2-581 GEN
Solar/Wind Harmer
22.274
316065AD1-022 GEN
Solar/Wind Harmer
11.672
3145893MURPHYS
Solar/Wind Harmer
0.646
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.119
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.898
316426AA2-053 GEN
Solar/Wind Harmer
2.242
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.484
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.605
3145783HORNRTN
Solar/Wind Harmer
2.084
3145783HORNRTN
Solar/Wind Harmer
0.651
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
3144293JTRSVLE
Adder
0.569
3144293JTRSVLE
Adder
0.479
3151731LOISA B
Adder
8.426
3151721LOISA A
Adder
8.382
NYPJM->LTFIMP_NY
CLTF
3.27
LAGNLTFEXP_LAGN->PJM
CLTF
8.052
LGEELTFEXP_LGEE->PJM
CLTF
1.341
WECLTFEXP_WEC->PJM
CLTF
0.646
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.067
TVALTFEXP_TVA->PJM
CLTF
4.084
CPLELTFEXP_CPLE->PJM
CLTF
11.42
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.573
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.493
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.892
MECLTFEXP_MEC->PJM
CLTF
3.637
SIGELTFEXP_SIGE->PJM
CLTF
0.111

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.37 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5679.63
MW Contribution:12.44
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
14.574
970497AG2-320 GEN
50/50
26.212
3150401LDYSMT4
50/50
37.242
3150371LDYSMT1
50/50
35.986
315051AA1-145 CT1
50/50
2.029
316044AC1-158 PL1
Solar/Wind Harmer
3.445
316450AC1-158 RIC
Solar/Wind Harmer
0.919
966881AG1-559 GEN
Solar/Wind Harmer
0.875
3142416OLDCHRC
Solar/Wind Harmer
2.824
970293AG2-193 GEN
Solar/Wind Harmer
3.455
3143096IRON208
Adder
1.024
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
2.94
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.033
316382AG1-145 C
Solar/Wind Harmer
0.809
970129AG2-093 GEN
Solar/Wind Harmer
15.103
315778AD1-151 GEN
Solar/Wind Harmer
23.155
965281AG1-393 GEN
Solar/Wind Harmer
3.341
315839AE2-212 C
Solar/Wind Harmer
0.805
3150921YORKTN3
Adder
5.937
3144216WINCHST
Adder
0.89
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
5.587
315773AC2-141 GEN
Solar/Wind Harmer
11.065
3151221GRAVEL6
Adder
17.112
3151171GRAVELC
Adder
3.292
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.456
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.463
944581AF1-123 GEN
Solar/Wind Harmer
118.881
944601AF1-125 GEN
Solar/Wind Harmer
117.026
3151101ELIZAR3
Adder
21.596
316083AB2-161 GEN
Solar/Wind Harmer
4.242
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.318
970661AG2-428 GEN
Solar/Wind Harmer
4.904
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
10.974
316280AD1-041 GEN
Solar/Wind Harmer
1.955
316156AD2-030 GEN
Solar/Wind Harmer
0.69
3141873WAN 176
Solar/Wind Harmer
3.066
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.146
316320Y1-086
Solar/Wind Harmer
1.497
316435W1029_GEN3
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.675
316484AD2-074 GEN
Solar/Wind Harmer
6.226
970009AG2-005 GEN
Solar/Wind Harmer
3.091
3146376EDENTON
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.707
315614AA2-178 GEN
Solar/Wind Harmer
2.584
3150391LDYSMT3
50/50
37.173
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
7.576
315673AE1-157 GEN
Solar/Wind Harmer
21.908
957411AF2-035 GEN
Solar/Wind Harmer
13.095
970317AG2-208 GEN
Solar/Wind Harmer
12.731
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.769
3150701DARBY 4
Adder
17.728
3150681DARBY 2
Adder
17.707
3150671DARBY 1
Adder
17.686
3143526WINTERP
Solar/Wind Harmer
-0.142
316075AC2-137 C
Solar/Wind Harmer
0.742
971223AH1-071 GEN
Solar/Wind Harmer
3.429
966871AG1-558 GEN
Solar/Wind Harmer
0.822
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
114.617
316240AF1-291 C
Solar/Wind Harmer
0.812
971531AH1-263 GEN
50/50
86.469
3150411LDYSMT5
50/50
37.359
3150381LDYSMT2
50/50
35.754
972213AH1-691 GEN
50/50
6.048
972215AH1-692 GEN
50/50
6.048
963051AG1-154 GEN
50/50
4.652
972189AH1-679 GEN
Adder
4.287
316312AB1-027
Solar/Wind Harmer
0.944
316233AE1-074 FULL
Solar/Wind Harmer
0.74
971281AH1-106 GEN
Solar/Wind Harmer
4.473
971283AH1-107 GEN
Solar/Wind Harmer
4.473
971285AH1-108 GEN
Adder
1.843
316164AC1-076 GEN
Solar/Wind Harmer
2.308
315976AC1-164 GENA
Solar/Wind Harmer
28.844
316169AC1-164_GENC
Solar/Wind Harmer
24.919
315975AC1-164 GENB
Solar/Wind Harmer
0.853
316132AB2-190 GEN1
Solar/Wind Harmer
2.712
316369SG1_INVT
Solar/Wind Harmer
4.765
971167AH1-042 GEN
Solar/Wind Harmer
25.596
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.275
3151201GRAVEL4
Adder
17.131
3151191GRAVEL3
Adder
16.914
3151211GRAVEL5
Adder
16.914
971445AH1-216 GEN
Solar/Wind Harmer
16.299
3143316POE
Solar/Wind Harmer
-0.103
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.788
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.237
3151081ELIZAR1
Adder
21.323
3151091ELIZAR2
Adder
20.953
3152611GOSPORTB
Adder
2.961
3152621GOSPORTC
Adder
2.513
3152601GOSPORTA
Adder
2.318
316059AD1-063 C
Solar/Wind Harmer
0.589
315662AE1-191 GEN
Solar/Wind Harmer
3.128
315666AE1-190 GEN
Solar/Wind Harmer
0.782
957871AF2-081 GEN
Solar/Wind Harmer
12.932
957601AF2-054 GEN
Solar/Wind Harmer
0.773
3141873WAN 176
Solar/Wind Harmer
-0.005
315833AF1-017_GEN
Solar/Wind Harmer
4.905
316349AD2-085 GEN
Solar/Wind Harmer
2.297
316311AC2-079 GEN
Solar/Wind Harmer
13.025
319010AE1-072 C
Solar/Wind Harmer
5.217
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.777
315835AF2-110_GEN
Solar/Wind Harmer
3.205
313526AB2-022
Solar/Wind Harmer
0.689
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.686
3146396TANGLEW
Solar/Wind Harmer
0.468
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.674
941031AE2-094 GEN
Solar/Wind Harmer
46.791
944011AF1-069 GEN
Solar/Wind Harmer
14.661
962981AG1-147 GEN
Solar/Wind Harmer
10.909
315814AE2-033 C
Solar/Wind Harmer
23.19
315611Z1-036_GEN2
Solar/Wind Harmer
6.129
970673AG2-436 GEN
Solar/Wind Harmer
51.562
970673AG2-436 GEN
Solar/Wind Harmer
26.107
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
971967AH1-528 GEN
Solar/Wind Harmer
45.598
315816AE2-034 GEN
Solar/Wind Harmer
1.938
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.023
315732AD1-074 GEN1
Solar/Wind Harmer
4.743
315733AD1-074 GEN2
Solar/Wind Harmer
4.743
315735AD1-075 GEN1
Solar/Wind Harmer
2.372
965291AG1-394 GEN
Solar/Wind Harmer
2.07
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.153
970085AG2-068 GEN
Solar/Wind Harmer
14.462
970581AG2-369 GEN
Solar/Wind Harmer
12.437
316318V4-068
Solar/Wind Harmer
0.576
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.505
315607AA1-063A GEN
Solar/Wind Harmer
2.277
316087AB2-174 GEN
Solar/Wind Harmer
3.193
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
1.466
316313AB2-026
Solar/Wind Harmer
0.639
316258AE1-075 C
Solar/Wind Harmer
0.575
316405AF2-144 C
Solar/Wind Harmer
0.607
3143336POWHATN
Solar/Wind Harmer
2.388
971157AH1-035 GEN
Solar/Wind Harmer
2.941
315737AD1-076 GEN
Solar/Wind Harmer
4.458
3156081AA2-088 GEN
Solar/Wind Harmer
7.605
970917AG2-570 GEN
Solar/Wind Harmer
58.079
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.562
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.15
961681AG1-008 GEN
Solar/Wind Harmer
18.15
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.079
316463AE2-346 GEN
Solar/Wind Harmer
0.369
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.847
3147666LOUISA
Solar/Wind Harmer
-0.052
966621AG1-532 GEN
Solar/Wind Harmer
0.458
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.793
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.047
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.567
972255AH1-712 GEN
Adder
84.405
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.284
3151761LOISA E
Adder
16.401
972183AH1-676 GEN
Adder
128.361
3141196NOKESVL
Solar/Wind Helper
1.252
315652AC1-086 GEN
Solar/Wind Harmer
25.002
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
972193AH1-681 GEN
Adder
3.771
972205AH1-687 GEN
Adder
6.858
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
316033AB2-134 GEN
Solar/Wind Harmer
8.601
315697AD1-025 GEN
Solar/Wind Harmer
5.395
316236AE1-162_GEN
Solar/Wind Harmer
0.793
316036AC1-147 C
Solar/Wind Harmer
0.705
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.377
970657AG2-426 GEN
Solar/Wind Harmer
8.157
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.8
3142956BIRDNECK
Solar/Wind Harmer
1.399
316185AD1-033 GEN
Solar/Wind Harmer
2.747
316441AF1-014 GEN
Solar/Wind Harmer
1.755
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.746
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.048
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.579
316433W1029_GEN2
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.872
316487AF1-042 GEN
Solar/Wind Harmer
3.258
315742AE1-103 GEN
Solar/Wind Harmer
2.575
3146376EDENTON
Solar/Wind Harmer
0.727
3146376EDENTON
Solar/Wind Harmer
0.727
958261AF2-120 GEN
Solar/Wind Harmer
9.456
972185AH1-677 GEN
Adder
12.155
972187AH1-678 GEN
Adder
6.099
316077AC2-138 C
Solar/Wind Harmer
0.502
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.201
316468AD1-105 GEN
Solar/Wind Harmer
2.65
970933AG2-581 GEN
Solar/Wind Harmer
22.22
316065AD1-022 GEN
Solar/Wind Harmer
11.648
3145893MURPHYS
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.112
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.822
316426AA2-053 GEN
Solar/Wind Harmer
2.237
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.478
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.599
3145783HORNRTN
Solar/Wind Harmer
2.079
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3151731LOISA B
Adder
8.045
3151721LOISA A
Adder
8.003
971507AH1-251 GEN
50/50
17.78
3152251N ANNA1
50/50
14.575
972197AH1-683 GEN
50/50
5.815
972219AH1-694 GEN
50/50
4.187
315052AA1-145 CT2
50/50
2.038
316045AC1-158 PL2
Solar/Wind Harmer
11.02
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
-0.072
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.142
3143096IRON208
Adder
1.024
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
115.637
316159AE1-175 C
Solar/Wind Harmer
0.72
970129AG2-093 GEN
Solar/Wind Harmer
6.118
316458AB2-190 GEN2
Solar/Wind Harmer
2.712
315671AE2-027_GEN
Solar/Wind Harmer
20.089
971069AG2-661 GEN
Solar/Wind Harmer
4.229
971647AH1-324 GEN
Solar/Wind Harmer
13.301
971317AH1-138 GEN
Solar/Wind Harmer
3.319
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
13.094
316294AC1-161 GEN
Solar/Wind Harmer
8.555
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.9
944591AF1-124 GEN
Solar/Wind Harmer
119.31
316375AC2-012 GEN
Solar/Wind Harmer
9.042
3150981CHESPKA
Adder
2.903
316381AD1-082 GEN
Solar/Wind Harmer
2.397
3141766HARMONY
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
27.675
971777AH1-397 GEN
Solar/Wind Harmer
3.061
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.525
939411AE1-173 GEN
Solar/Wind Harmer
129.681
940641AE2-051 GEN
Solar/Wind Harmer
24.285
316388AE2-253 GEN
Solar/Wind Harmer
1.746
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.521
316093AE2-104_GEN
Solar/Wind Harmer
7.454
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.129
961951AG1-038 GEN
Solar/Wind Harmer
3.258
3130156CHOWAN
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
9.184
964211AG1-282 GEN
Solar/Wind Harmer
0.725
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.455
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
2.81
970919AG2-571 GEN
Solar/Wind Harmer
7.352
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.801
316023GEN1_S
Solar/Wind Harmer
1.562
970087AG2-069 GEN
Solar/Wind Harmer
21.693
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.686
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.613
316336AC2-165 C
Solar/Wind Harmer
3.944
3145683EARLEYS
Solar/Wind Harmer
-0.023
3147666LOUISA
Solar/Wind Harmer
-0.09
960081AF2-299 GEN
Solar/Wind Harmer
2.538
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.556
316011AB1-132 GEN
Solar/Wind Harmer
4.65
962571AG1-106 GEN
Solar/Wind Harmer
3.195
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.272
316174AB2-169 GEN
Solar/Wind Harmer
3.411
316192AB2-158 GEN
Solar/Wind Harmer
2.63
971795AH1-408 GEN
Solar/Wind Harmer
16.551
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.925
3147043LAWRENC
Adder
1.759
3144293JTRSVLE
Adder
0.567
972277AH1-723 GEN
Adder
98.358
3151751LOISA D
Adder
8.045
962491AG1-098 GEN
Solar/Wind Harmer
13.869
NYPJM->LTFIMP_NY
CLTF
3.26
LGEELTFEXP_LGEE->PJM
CLTF
1.336
LAGNLTFEXP_LAGN->PJM
CLTF
8.027
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.997
WECLTFEXP_WEC->PJM
CLTF
0.644
TVALTFEXP_TVA->PJM
CLTF
4.071
CPLELTFEXP_CPLE->PJM
CLTF
11.39
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.421
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.849
MECLTFEXP_MEC->PJM
CLTF
3.625
SIGELTFEXP_SIGE->PJM
CLTF
0.111

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.36 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5679.37
MW Contribution:12.44
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
86.379
3150411LDYSMT5
50/50
37.362
3150381LDYSMT2
50/50
35.757
972213AH1-691 GEN
50/50
6.049
972215AH1-692 GEN
50/50
6.049
963051AG1-154 GEN
50/50
4.653
972189AH1-679 GEN
Adder
4.288
316312AB1-027
Solar/Wind Harmer
0.944
316233AE1-074 FULL
Solar/Wind Harmer
0.74
971281AH1-106 GEN
Solar/Wind Harmer
4.473
971283AH1-107 GEN
Solar/Wind Harmer
4.473
971285AH1-108 GEN
Adder
1.844
315976AC1-164 GENA
Solar/Wind Harmer
28.849
316169AC1-164_GENC
Solar/Wind Harmer
24.922
315975AC1-164 GENB
Solar/Wind Harmer
0.854
316164AC1-076 GEN
Solar/Wind Harmer
2.296
316132AB2-190 GEN1
Solar/Wind Harmer
2.712
316369SG1_INVT
Solar/Wind Harmer
4.766
971167AH1-042 GEN
Solar/Wind Harmer
25.599
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
972265AH1-717 GEN
Adder
18.278
3151201GRAVEL4
Adder
17.134
3151191GRAVEL3
Adder
16.917
3151211GRAVEL5
Adder
16.917
971445AH1-216 GEN
Solar/Wind Harmer
16.302
3143316POE
Solar/Wind Harmer
-0.103
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.788
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.238
3151081ELIZAR1
Adder
21.327
3151091ELIZAR2
Adder
20.956
3152611GOSPORTB
Adder
2.962
3152621GOSPORTC
Adder
2.514
3152601GOSPORTA
Adder
2.319
316059AD1-063 C
Solar/Wind Harmer
0.589
315662AE1-191 GEN
Solar/Wind Harmer
3.128
315666AE1-190 GEN
Solar/Wind Harmer
0.782
957871AF2-081 GEN
Solar/Wind Harmer
12.934
957601AF2-054 GEN
Solar/Wind Harmer
0.773
3141873WAN 176
Solar/Wind Harmer
-0.005
315833AF1-017_GEN
Solar/Wind Harmer
4.906
316349AD2-085 GEN
Solar/Wind Harmer
2.297
316311AC2-079 GEN
Solar/Wind Harmer
13.027
319010AE1-072 C
Solar/Wind Harmer
5.218
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.777
315835AF2-110_GEN
Solar/Wind Harmer
3.205
313526AB2-022
Solar/Wind Harmer
0.689
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.686
3146396TANGLEW
Solar/Wind Harmer
0.468
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.674
941031AE2-094 GEN
Solar/Wind Harmer
46.799
944011AF1-069 GEN
Solar/Wind Harmer
14.664
962981AG1-147 GEN
Solar/Wind Harmer
10.911
315814AE2-033 C
Solar/Wind Harmer
23.194
315611Z1-036_GEN2
Solar/Wind Harmer
6.13
970673AG2-436 GEN
Solar/Wind Harmer
51.571
970673AG2-436 GEN
Solar/Wind Harmer
26.112
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
971967AH1-528 GEN
Solar/Wind Harmer
45.606
315816AE2-034 GEN
Solar/Wind Harmer
1.938
3141813NORNECK
Solar/Wind Harmer
-0.024
3152261N ANNA2
50/50
14.578
970497AG2-320 GEN
50/50
26.215
3150401LDYSMT4
50/50
37.246
3150371LDYSMT1
50/50
35.99
315051AA1-145 CT1
50/50
2.03
316044AC1-158 PL1
Solar/Wind Harmer
3.447
316450AC1-158 RIC
Solar/Wind Harmer
0.919
966881AG1-559 GEN
Solar/Wind Harmer
0.875
3142416OLDCHRC
Solar/Wind Harmer
2.824
970293AG2-193 GEN
Solar/Wind Harmer
3.455
3143096IRON208
Adder
1.025
3143096IRON208
Adder
1.004
3150861SPRUNCD
Adder
1.127
316473AC1-191 GEN
Solar/Wind Harmer
2.941
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.033
316382AG1-145 C
Solar/Wind Harmer
0.809
970129AG2-093 GEN
Solar/Wind Harmer
15.106
315778AD1-151 GEN
Solar/Wind Harmer
23.159
965281AG1-393 GEN
Solar/Wind Harmer
3.342
315839AE2-212 C
Solar/Wind Harmer
0.805
3150921YORKTN3
Adder
5.938
3144216WINCHST
Adder
0.891
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
5.588
315773AC2-141 GEN
Solar/Wind Harmer
11.067
3151221GRAVEL6
Adder
17.114
3151171GRAVELC
Adder
3.293
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.458
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.464
944581AF1-123 GEN
Solar/Wind Harmer
118.901
944601AF1-125 GEN
Solar/Wind Harmer
117.045
3151101ELIZAR3
Adder
21.599
316083AB2-161 GEN
Solar/Wind Harmer
4.242
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.319
970661AG2-428 GEN
Solar/Wind Harmer
4.905
971507AH1-251 GEN
50/50
17.73
3152251N ANNA1
50/50
14.579
972197AH1-683 GEN
50/50
5.816
972219AH1-694 GEN
50/50
4.188
315052AA1-145 CT2
50/50
2.039
316045AC1-158 PL2
Solar/Wind Harmer
11.027
966881AG1-559 GEN
Solar/Wind Harmer
0.299
3142416OLDCHRC
Solar/Wind Harmer
-0.072
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.142
3143096IRON208
Adder
1.025
3150851SPRUNCC
Adder
1.127
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
115.654
316159AE1-175 C
Solar/Wind Harmer
0.72
970129AG2-093 GEN
Solar/Wind Harmer
6.119
316458AB2-190 GEN2
Solar/Wind Harmer
2.712
315671AE2-027_GEN
Solar/Wind Harmer
20.092
971069AG2-661 GEN
Solar/Wind Harmer
4.23
971647AH1-324 GEN
Solar/Wind Harmer
13.303
971317AH1-138 GEN
Solar/Wind Harmer
3.32
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
961611AG1-000B GEN
Solar/Wind Harmer
13.096
316294AC1-161 GEN
Solar/Wind Harmer
8.557
3151171GRAVELC
Adder
2.504
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.903
944591AF1-124 GEN
Solar/Wind Harmer
119.329
316375AC2-012 GEN
Solar/Wind Harmer
9.043
3150981CHESPKA
Adder
2.904
316381AD1-082 GEN
Solar/Wind Harmer
2.397
3141766HARMONY
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
27.679
971777AH1-397 GEN
Solar/Wind Harmer
3.061
3141843SHACKLE
Adder
1.184
316072AD1-144
Solar/Wind Harmer
0.525
939411AE1-173 GEN
Solar/Wind Harmer
129.703
940641AE2-051 GEN
Solar/Wind Harmer
24.29
316388AE2-253 GEN
Solar/Wind Harmer
1.746
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.521
316093AE2-104_GEN
Solar/Wind Harmer
7.455
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
3150391LDYSMT3
50/50
37.176
972195AH1-682 GEN
50/50
4.885
316447AC1-158 HLD
Solar/Wind Harmer
7.58
315673AE1-157 GEN
Solar/Wind Harmer
21.91
957411AF2-035 GEN
Solar/Wind Harmer
13.096
970317AG2-208 GEN
Solar/Wind Harmer
12.732
3142296MT RD221
Adder
0.803
3142366NRTHEST
Adder
0.809
3150691DARBY 3
Adder
17.772
3150701DARBY 4
Adder
17.73
3150681DARBY 2
Adder
17.71
3150671DARBY 1
Adder
17.689
3143526WINTERP
Solar/Wind Harmer
-0.142
316075AC2-137 C
Solar/Wind Harmer
0.742
971223AH1-071 GEN
Solar/Wind Harmer
3.429
966871AG1-558 GEN
Solar/Wind Harmer
0.822
966871AG1-558 GEN
Solar/Wind Harmer
0.281
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
114.635
316240AF1-291 C
Solar/Wind Harmer
0.812
316033AB2-134 GEN
Solar/Wind Harmer
8.603
315697AD1-025 GEN
Solar/Wind Harmer
5.395
316236AE1-162_GEN
Solar/Wind Harmer
0.794
316036AC1-147 C
Solar/Wind Harmer
0.705
3150991CHESPKB
Adder
2.436
3150991CHESPKB
Adder
2.378
970657AG2-426 GEN
Solar/Wind Harmer
8.158
970657AG2-426 GEN
Solar/Wind Harmer
1.706
316316AC1-027 C
Solar/Wind Harmer
0.801
315800Z1-036_GEN1
Solar/Wind Harmer
6.13
961951AG1-038 GEN
Solar/Wind Harmer
3.258
3130156CHOWAN
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
9.185
964211AG1-282 GEN
Solar/Wind Harmer
0.726
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.459
3150351NORNECKC2
Adder
2.113
3143336POWHATN
Solar/Wind Harmer
2.81
970919AG2-571 GEN
Solar/Wind Harmer
7.353
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.802
316023GEN1_S
Solar/Wind Harmer
1.562
970087AG2-069 GEN
Solar/Wind Harmer
21.697
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.686
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.613
316336AC2-165 C
Solar/Wind Harmer
3.944
3145683EARLEYS
Solar/Wind Harmer
-0.023
3147666LOUISA
Solar/Wind Harmer
-0.09
960081AF2-299 GEN
Solar/Wind Harmer
2.538
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.568
316011AB1-132 GEN
Solar/Wind Harmer
4.65
962571AG1-106 GEN
Solar/Wind Harmer
3.195
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.272
316174AB2-169 GEN
Solar/Wind Harmer
3.412
316192AB2-158 GEN
Solar/Wind Harmer
2.63
971795AH1-408 GEN
Solar/Wind Harmer
16.554
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.927
3147043LAWRENC
Adder
1.759
3144293JTRSVLE
Adder
0.567
972277AH1-723 GEN
Adder
98.366
3130546PLYMOUTH
Solar/Wind Harmer
-0.023
315732AD1-074 GEN1
Solar/Wind Harmer
4.744
315733AD1-074 GEN2
Solar/Wind Harmer
4.744
315735AD1-075 GEN1
Solar/Wind Harmer
2.373
965291AG1-394 GEN
Solar/Wind Harmer
2.07
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.154
970085AG2-068 GEN
Solar/Wind Harmer
14.465
970581AG2-369 GEN
Solar/Wind Harmer
12.44
316318V4-068
Solar/Wind Harmer
0.576
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.171
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.505
315607AA1-063A GEN
Solar/Wind Harmer
2.277
316087AB2-174 GEN
Solar/Wind Harmer
3.194
315652AC1-086 GEN
Solar/Wind Harmer
25.006
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
972193AH1-681 GEN
Adder
3.772
972205AH1-687 GEN
Adder
6.859
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
3142956BIRDNECK
Solar/Wind Harmer
1.399
316185AD1-033 GEN
Solar/Wind Harmer
2.747
316441AF1-014 GEN
Solar/Wind Harmer
1.755
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.746
316018AA1-139 ULT2
Solar/Wind Harmer
2.216
316017AA1-139 ULT1
Solar/Wind Harmer
2.093
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.049
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.025
316431W1029_GEN1
Solar/Wind Harmer
4.579
316433W1029_GEN2
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.872
316487AF1-042 GEN
Solar/Wind Harmer
3.258
315742AE1-103 GEN
Solar/Wind Harmer
2.576
3146376EDENTON
Solar/Wind Harmer
0.727
3146376EDENTON
Solar/Wind Harmer
0.727
958261AF2-120 GEN
Solar/Wind Harmer
9.457
972185AH1-677 GEN
Adder
12.157
972187AH1-678 GEN
Adder
6.1
316077AC2-138 C
Solar/Wind Harmer
0.502
3150341NORNECKC1
Adder
2.219
3150341NORNECKC1
Adder
2.202
316468AD1-105 GEN
Solar/Wind Harmer
2.65
970933AG2-581 GEN
Solar/Wind Harmer
22.224
316065AD1-022 GEN
Solar/Wind Harmer
11.65
3145893MURPHYS
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.112
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.827
316426AA2-053 GEN
Solar/Wind Harmer
2.237
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.479
3145593CAROLNA
Solar/Wind Harmer
0.183
3145783HORNRTN
Solar/Wind Harmer
2.599
3145783HORNRTN
Solar/Wind Harmer
2.079
3145783HORNRTN
Solar/Wind Harmer
0.65
3145783HORNRTN
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.065
3144293JTRSVLE
Adder
0.567
3144293JTRSVLE
Adder
0.477
3151731LOISA B
Adder
8.04
3151721LOISA A
Adder
7.998
3141843SHACKLE
Adder
1.184
316203AE2-005 GEN
Solar/Wind Harmer
10.976
316280AD1-041 GEN
Solar/Wind Harmer
1.955
316156AD2-030 GEN
Solar/Wind Harmer
0.69
3141873WAN 176
Solar/Wind Harmer
3.067
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.147
316320Y1-086
Solar/Wind Harmer
1.497
316435W1029_GEN3
Solar/Wind Harmer
4.579
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.676
316484AD2-074 GEN
Solar/Wind Harmer
6.227
970009AG2-005 GEN
Solar/Wind Harmer
3.092
3146376EDENTON
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.708
315614AA2-178 GEN
Solar/Wind Harmer
2.585
3150351NORNECKC2
Adder
2.148
971781AH1-399 GEN
Solar/Wind Harmer
1.466
316313AB2-026
Solar/Wind Harmer
0.639
316258AE1-075 C
Solar/Wind Harmer
0.575
316405AF2-144 C
Solar/Wind Harmer
0.607
3143336POWHATN
Solar/Wind Harmer
2.389
971157AH1-035 GEN
Solar/Wind Harmer
2.942
315737AD1-076 GEN
Solar/Wind Harmer
4.458
3156081AA2-088 GEN
Solar/Wind Harmer
7.606
970917AG2-570 GEN
Solar/Wind Harmer
58.089
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.562
3145893MURPHYS
Solar/Wind Harmer
0.161
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.153
961681AG1-008 GEN
Solar/Wind Harmer
18.153
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.079
316463AE2-346 GEN
Solar/Wind Harmer
0.369
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.847
3147666LOUISA
Solar/Wind Harmer
-0.052
966621AG1-532 GEN
Solar/Wind Harmer
0.458
3146263WOODLND
Solar/Wind Harmer
-0.022
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.793
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.047
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3144293JTRSVLE
Adder
0.567
972255AH1-712 GEN
Adder
84.412
3141316ARNOLDS
Adder
0.324
3150331BIRCHWDA
Adder
21.287
3151761LOISA E
Adder
16.391
972183AH1-676 GEN
Adder
128.276
3141196NOKESVL
Solar/Wind Helper
1.252
3151751LOISA D
Adder
8.04
962491AG1-098 GEN
Solar/Wind Harmer
13.871
NYPJM->LTFIMP_NY
CLTF
3.261
LAGNLTFEXP_LAGN->PJM
CLTF
8.029
LGEELTFEXP_LGEE->PJM
CLTF
1.336
WECLTFEXP_WEC->PJM
CLTF
0.644
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.001
TVALTFEXP_TVA->PJM
CLTF
4.071
CPLELTFEXP_CPLE->PJM
CLTF
11.392
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.447
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.423
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.85
MECLTFEXP_MEC->PJM
CLTF
3.626
SIGELTFEXP_SIGE->PJM
CLTF
0.111

Details for 8CHANCE-8BRISTER 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHANCE-8BRISTER 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.05 %
Rating:5010.0 MVA
Rating Type:C
MVA to Mitigate:5563.76
MW Contribution:12.49
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
14.616
970497AG2-320 GEN
50/50
26.297
3150401LDYSMT4
50/50
37.371
3150371LDYSMT1
50/50
36.111
315051AA1-145 CT1
50/50
2.037
966881AG1-559 GEN
Solar/Wind Harmer
0.878
3142416OLDCHRC
Solar/Wind Harmer
2.834
970293AG2-193 GEN
Solar/Wind Harmer
3.467
3143096IRON208
Adder
1.028
3143096IRON208
Adder
1.008
3150861SPRUNCD
Adder
1.131
316473AC1-191 GEN
Solar/Wind Harmer
2.951
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.044
316382AG1-145 C
Solar/Wind Harmer
0.812
970129AG2-093 GEN
Solar/Wind Harmer
15.161
315778AD1-151 GEN
Solar/Wind Harmer
23.243
965281AG1-393 GEN
Solar/Wind Harmer
3.354
315839AE2-212 C
Solar/Wind Harmer
0.808
3150921YORKTN3
Adder
5.96
3144216WINCHST
Adder
0.894
3142433PROV 92
Adder
0.461
3142433PROV 92
Adder
0.461
961611AG1-000B GEN
Solar/Wind Harmer
5.608
315773AC2-141 GEN
Solar/Wind Harmer
11.108
3151221GRAVEL6
Adder
17.177
3151171GRAVELC
Adder
3.305
3145336SMITFLD
Solar/Wind Harmer
-0.01
315813AE1-149 C
Solar/Wind Harmer
16.519
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.473
944581AF1-123 GEN
Solar/Wind Harmer
119.344
944601AF1-125 GEN
Solar/Wind Harmer
117.481
3151101ELIZAR3
Adder
21.68
316083AB2-161 GEN
Solar/Wind Harmer
4.258
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.327
970661AG2-428 GEN
Solar/Wind Harmer
4.923
3141843SHACKLE
Adder
1.188
316203AE2-005 GEN
Solar/Wind Harmer
11.017
316280AD1-041 GEN
Solar/Wind Harmer
1.963
316156AD2-030 GEN
Solar/Wind Harmer
0.693
3141873WAN 176
Solar/Wind Harmer
3.078
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.159
316320Y1-086
Solar/Wind Harmer
1.503
316435W1029_GEN3
Solar/Wind Harmer
4.597
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
962971AG1-146 GEN
Solar/Wind Harmer
4.694
316484AD2-074 GEN
Solar/Wind Harmer
6.252
970009AG2-005 GEN
Solar/Wind Harmer
3.104
3146376EDENTON
Solar/Wind Harmer
-0.025
316404AE1-155 C
Solar/Wind Harmer
4.727
315614AA2-178 GEN
Solar/Wind Harmer
2.595
971531AH1-263 GEN
50/50
86.63
3150411LDYSMT5
50/50
37.488
3150381LDYSMT2
50/50
35.877
972213AH1-691 GEN
50/50
6.069
972215AH1-692 GEN
50/50
6.069
963051AG1-154 GEN
50/50
4.668
972189AH1-679 GEN
Adder
4.302
316312AB1-027
Solar/Wind Harmer
0.947
316233AE1-074 FULL
Solar/Wind Harmer
0.743
971281AH1-106 GEN
Solar/Wind Harmer
4.489
971283AH1-107 GEN
Solar/Wind Harmer
4.489
971285AH1-108 GEN
Adder
1.85
316164AC1-076 GEN
Solar/Wind Harmer
2.317
315976AC1-164 GENA
Solar/Wind Harmer
28.952
316169AC1-164_GENC
Solar/Wind Harmer
25.012
315975AC1-164 GENB
Solar/Wind Harmer
0.857
316132AB2-190 GEN1
Solar/Wind Harmer
2.722
316369SG1_INVT
Solar/Wind Harmer
4.784
971167AH1-042 GEN
Solar/Wind Harmer
25.694
3142433PROV 92
Adder
0.461
3142433PROV 92
Adder
0.461
972265AH1-717 GEN
Adder
18.345
3151201GRAVEL4
Adder
17.197
3151191GRAVEL3
Adder
16.979
3151211GRAVEL5
Adder
16.979
971445AH1-216 GEN
Solar/Wind Harmer
16.362
3143316POE
Solar/Wind Harmer
-0.104
3143873LANEXA
Solar/Wind Harmer
-0.016
957831AF2-077 GEN
Solar/Wind Harmer
0.791
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.246
3151081ELIZAR1
Adder
21.406
3151091ELIZAR2
Adder
21.034
3152611GOSPORTB
Adder
2.973
3152621GOSPORTC
Adder
2.523
3152601GOSPORTA
Adder
2.327
316059AD1-063 C
Solar/Wind Harmer
0.591
315662AE1-191 GEN
Solar/Wind Harmer
3.14
315666AE1-190 GEN
Solar/Wind Harmer
0.785
957871AF2-081 GEN
Solar/Wind Harmer
12.983
957601AF2-054 GEN
Solar/Wind Harmer
0.776
3141873WAN 176
Solar/Wind Harmer
-0.005
315833AF1-017_GEN
Solar/Wind Harmer
4.925
316349AD2-085 GEN
Solar/Wind Harmer
2.306
316311AC2-079 GEN
Solar/Wind Harmer
13.076
319010AE1-072 C
Solar/Wind Harmer
5.237
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.78
315835AF2-110_GEN
Solar/Wind Harmer
3.217
313526AB2-022
Solar/Wind Harmer
0.692
3141913WHIT STONE
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
316321Z2-027
Solar/Wind Harmer
0.689
3146396TANGLEW
Solar/Wind Harmer
0.47
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
316315AB2-025 C
Solar/Wind Harmer
0.677
941031AE2-094 GEN
Solar/Wind Harmer
46.982
944011AF1-069 GEN
Solar/Wind Harmer
14.721
962981AG1-147 GEN
Solar/Wind Harmer
10.954
315814AE2-033 C
Solar/Wind Harmer
23.285
315611Z1-036_GEN2
Solar/Wind Harmer
6.155
970673AG2-436 GEN
Solar/Wind Harmer
51.775
970673AG2-436 GEN
Solar/Wind Harmer
26.215
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
45.789
315816AE2-034 GEN
Solar/Wind Harmer
1.946
3150351NORNECKC2
Adder
2.157
971781AH1-399 GEN
Solar/Wind Harmer
1.472
316313AB2-026
Solar/Wind Harmer
0.641
316258AE1-075 C
Solar/Wind Harmer
0.577
316405AF2-144 C
Solar/Wind Harmer
0.609
3143336POWHATN
Solar/Wind Harmer
2.399
971157AH1-035 GEN
Solar/Wind Harmer
2.954
315737AD1-076 GEN
Solar/Wind Harmer
4.477
3156081AA2-088 GEN
Solar/Wind Harmer
7.638
970917AG2-570 GEN
Solar/Wind Harmer
58.333
3146206CASHIE
Solar/Wind Harmer
-0.023
316365GEN2_N
Solar/Wind Harmer
1.569
3145893MURPHYS
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
-0.023
3150391LDYSMT3
50/50
37.301
972195AH1-682 GEN
50/50
4.902
315673AE1-157 GEN
Solar/Wind Harmer
21.984
957411AF2-035 GEN
Solar/Wind Harmer
13.14
970317AG2-208 GEN
Solar/Wind Harmer
12.775
3142296MT RD221
Adder
0.806
3142366NRTHEST
Adder
0.811
3150691DARBY 3
Adder
17.834
3150701DARBY 4
Adder
17.793
3150681DARBY 2
Adder
17.772
3150671DARBY 1
Adder
17.751
3143526WINTERP
Solar/Wind Harmer
-0.143
316075AC2-137 C
Solar/Wind Harmer
0.745
971223AH1-071 GEN
Solar/Wind Harmer
3.441
966871AG1-558 GEN
Solar/Wind Harmer
0.825
966871AG1-558 GEN
Solar/Wind Harmer
0.282
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
115.049
316240AF1-291 C
Solar/Wind Harmer
0.815
316033AB2-134 GEN
Solar/Wind Harmer
8.634
315697AD1-025 GEN
Solar/Wind Harmer
5.415
316236AE1-162_GEN
Solar/Wind Harmer
0.797
316036AC1-147 C
Solar/Wind Harmer
0.708
3150991CHESPKB
Adder
2.445
3150991CHESPKB
Adder
2.387
970657AG2-426 GEN
Solar/Wind Harmer
8.189
970657AG2-426 GEN
Solar/Wind Harmer
1.712
316316AC1-027 C
Solar/Wind Harmer
0.804
3142956BIRDNECK
Solar/Wind Harmer
1.405
316185AD1-033 GEN
Solar/Wind Harmer
2.758
316441AF1-014 GEN
Solar/Wind Harmer
1.761
3145506HICKORY
Solar/Wind Harmer
-0.104
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316339AD2-160 GEN
Solar/Wind Harmer
1.753
316018AA1-139 ULT2
Solar/Wind Harmer
2.224
316017AA1-139 ULT1
Solar/Wind Harmer
2.101
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.06
3130086AYDLETT
Solar/Wind Harmer
-0.103
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.597
316433W1029_GEN2
Solar/Wind Harmer
4.597
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.875
316487AF1-042 GEN
Solar/Wind Harmer
3.271
315742AE1-103 GEN
Solar/Wind Harmer
2.586
3146376EDENTON
Solar/Wind Harmer
0.73
3146376EDENTON
Solar/Wind Harmer
0.73
958261AF2-120 GEN
Solar/Wind Harmer
9.495
972185AH1-677 GEN
Adder
12.206
972187AH1-678 GEN
Adder
6.125
316077AC2-138 C
Solar/Wind Harmer
0.504
3150341NORNECKC1
Adder
2.229
3150341NORNECKC1
Adder
2.211
316468AD1-105 GEN
Solar/Wind Harmer
2.661
970933AG2-581 GEN
Solar/Wind Harmer
22.315
316065AD1-022 GEN
Solar/Wind Harmer
11.699
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.126
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.949
316426AA2-053 GEN
Solar/Wind Harmer
2.247
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.49
3145593CAROLNA
Solar/Wind Harmer
0.184
3145783HORNRTN
Solar/Wind Harmer
2.611
3145783HORNRTN
Solar/Wind Harmer
2.089
3145783HORNRTN
Solar/Wind Harmer
0.653
3145783HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.021
316274AC1-208 GEN
Solar/Wind Harmer
2.299
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
3151731LOISA B
Adder
8.104
3151721LOISA A
Adder
8.062
316447AC1-158 HLD
Solar/Wind Helper
4.724
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.764
315733AD1-074 GEN2
Solar/Wind Harmer
4.764
315735AD1-075 GEN1
Solar/Wind Harmer
2.383
965291AG1-394 GEN
Solar/Wind Harmer
2.079
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.197
970085AG2-068 GEN
Solar/Wind Harmer
14.526
970581AG2-369 GEN
Solar/Wind Harmer
12.492
316318V4-068
Solar/Wind Harmer
0.578
3145893MURPHYS
Solar/Wind Harmer
-0.062
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.199
961941AG1-037 GEN
Solar/Wind Harmer
0.172
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.507
315607AA1-063A GEN
Solar/Wind Harmer
2.287
316087AB2-174 GEN
Solar/Wind Harmer
3.208
315652AC1-086 GEN
Solar/Wind Harmer
25.116
3137643SOCKMAN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.087
316223AC1-118
Solar/Wind Harmer
0.588
972193AH1-681 GEN
Adder
3.792
972205AH1-687 GEN
Adder
6.897
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
0.169
957521AF2-046 GEN
Solar/Wind Harmer
18.23
961681AG1-008 GEN
Solar/Wind Harmer
18.23
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.093
316463AE2-346 GEN
Solar/Wind Harmer
0.37
316140AB2-099
Solar/Wind Harmer
0.154
962331AG1-082 GEN
Solar/Wind Harmer
2.86
3147666LOUISA
Solar/Wind Harmer
-0.052
966621AG1-532 GEN
Solar/Wind Harmer
0.46
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.801
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.052
3145823KELFORD
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
3141906WESTMOR
Solar/Wind Harmer
-0.009
316478AD1-087 GEN
Solar/Wind Harmer
1.867
316486AD2-202 GEN
Solar/Wind Harmer
0.547
316210AC1-098 GEN
Solar/Wind Harmer
3.37
3145933PARMELE
Solar/Wind Harmer
-0.021
966801AG1-551 GEN
Solar/Wind Harmer
2.68
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
84.869
3141316ARNOLDS
Adder
0.327
3150331BIRCHWDA
Adder
21.437
3151761LOISA E
Adder
16.521
972183AH1-676 GEN
Adder
129.328
316044AC1-158 PL1
Solar/Wind Helper
2.146
316450AC1-158 RIC
Solar/Wind Helper
0.572
3141196NOKESVL
Solar/Wind Helper
1.245
971507AH1-251 GEN
50/50
17.82
3152251N ANNA1
50/50
14.617
972197AH1-683 GEN
50/50
5.836
972219AH1-694 GEN
50/50
4.202
315052AA1-145 CT2
50/50
2.046
966881AG1-559 GEN
Solar/Wind Harmer
0.3
3142416OLDCHRC
Solar/Wind Harmer
-0.073
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143526WINTERP
Solar/Wind Harmer
-0.143
3143096IRON208
Adder
1.028
3150851SPRUNCC
Adder
1.131
3143226MDLTHAN
Solar/Wind Harmer
-0.027
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
116.069
316159AE1-175 C
Solar/Wind Harmer
0.723
970129AG2-093 GEN
Solar/Wind Harmer
6.141
316458AB2-190 GEN2
Solar/Wind Harmer
2.722
315671AE2-027_GEN
Solar/Wind Harmer
20.165
971069AG2-661 GEN
Solar/Wind Harmer
4.245
971647AH1-324 GEN
Solar/Wind Harmer
13.352
971317AH1-138 GEN
Solar/Wind Harmer
3.332
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3142433PROV 92
Solar/Wind Harmer
-0.106
3142433PROV 92
Adder
0.461
3142433PROV 92
Adder
0.461
961611AG1-000B GEN
Solar/Wind Harmer
13.144
316294AC1-161 GEN
Solar/Wind Harmer
8.588
3151171GRAVELC
Adder
2.513
3145336SMITFLD
Solar/Wind Harmer
-0.105
970659AG2-427 GEN
Solar/Wind Harmer
13.955
944591AF1-124 GEN
Solar/Wind Harmer
119.774
316375AC2-012 GEN
Solar/Wind Harmer
9.077
3150981CHESPKA
Adder
2.915
316381AD1-082 GEN
Solar/Wind Harmer
2.406
3141766HARMONY
Solar/Wind Harmer
-0.005
970661AG2-428 GEN
Solar/Wind Harmer
27.783
971777AH1-397 GEN
Solar/Wind Harmer
3.073
3141843SHACKLE
Adder
1.188
316072AD1-144
Solar/Wind Harmer
0.527
939411AE1-173 GEN
Solar/Wind Harmer
130.189
940641AE2-051 GEN
Solar/Wind Harmer
24.381
316388AE2-253 GEN
Solar/Wind Harmer
1.753
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.523
316093AE2-104_GEN
Solar/Wind Harmer
7.483
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.081
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.155
961951AG1-038 GEN
Solar/Wind Harmer
3.271
3130156CHOWAN
Solar/Wind Harmer
-0.025
962861AG1-135 GEN
Solar/Wind Harmer
9.222
964211AG1-282 GEN
Solar/Wind Harmer
0.728
3141726DUNNSVL
Solar/Wind Harmer
-0.096
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.551
3150351NORNECKC2
Adder
2.122
3143336POWHATN
Solar/Wind Harmer
2.822
970919AG2-571 GEN
Solar/Wind Harmer
7.384
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.827
316023GEN1_S
Solar/Wind Harmer
1.569
970087AG2-069 GEN
Solar/Wind Harmer
21.789
3145893MURPHYS
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
0.689
3146173TUNIS
Solar/Wind Harmer
-0.023
316337AD2-073 GEN
Solar/Wind Harmer
0.615
316336AC2-165 C
Solar/Wind Harmer
3.962
3145683EARLEYS
Solar/Wind Harmer
-0.023
3147666LOUISA
Solar/Wind Harmer
-0.09
960081AF2-299 GEN
Solar/Wind Harmer
2.549
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.874
316011AB1-132 GEN
Solar/Wind Harmer
4.671
962571AG1-106 GEN
Solar/Wind Harmer
3.209
3145823KELFORD
Solar/Wind Harmer
-0.022
316190AA2-174 GEN
Solar/Wind Harmer
0.273
316174AB2-169 GEN
Solar/Wind Harmer
3.427
316192AB2-158 GEN
Solar/Wind Harmer
2.642
971795AH1-408 GEN
Solar/Wind Harmer
16.627
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
315693AD1-088 GEN
Solar/Wind Harmer
10.976
3147043LAWRENC
Adder
1.767
962491AG1-098 GEN
Solar/Wind Harmer
14.639
316212AC1-099_GEN
Solar/Wind Harmer
1.872
3146293MARTNCO
Solar/Wind Harmer
0.133
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
98.898
3151751LOISA D
Adder
8.104
316045AC1-158 PL2
Solar/Wind Helper
6.871
NYPJM->LTFIMP_NY
CLTF
3.216
LGEELTFEXP_LGEE->PJM
CLTF
1.384
LAGNLTFEXP_LAGN->PJM
CLTF
8.168
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.207
WECLTFEXP_WEC->PJM
CLTF
0.67
TVALTFEXP_TVA->PJM
CLTF
4.141
CPLELTFEXP_CPLE->PJM
CLTF
11.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.376
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.433
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.112
MECLTFEXP_MEC->PJM
CLTF
3.742
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:146.98 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3589.45
MW Contribution:11.46
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.341
971353AH1-157 GEN
50/50
32.652
970017AG2-010 GEN
50/50
24.601
3150981CHESPKA
50/50
4.651
316294AC1-161 GEN
Solar/Wind Harmer
6.621
971317AH1-138 GEN
Solar/Wind Harmer
2.751
3138126ROCKLANDING
Solar/Wind Harmer
0.168
316159AE1-175 C
Solar/Wind Harmer
0.315
944591AF1-124 GEN
Solar/Wind Harmer
80.715
316375AC2-012 GEN
Solar/Wind Harmer
0.009
316388AE2-253 GEN
Solar/Wind Harmer
1.09
3146456SLIGO L269
Solar/Wind Harmer
0.346
316246AF1-032 C
Solar/Wind Harmer
0.154
316072AD1-144
Solar/Wind Harmer
0.123
3145336SMITFLD
Solar/Wind Harmer
1.331
3146516WINFALL
Solar/Wind Harmer
1.07
3146516WINFALL
Solar/Wind Harmer
0.33
316093AE2-104_GEN
Solar/Wind Harmer
5.536
3151171GRAVELC
Adder
3.419
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
0.064
939411AE1-173 GEN
Solar/Wind Harmer
134.654
3130156CHOWAN
Solar/Wind Harmer
0.314
971777AH1-397 GEN
Solar/Wind Harmer
0.828
3141843SHACKLE
Adder
1.603
961611AG1-000B GEN
Solar/Wind Harmer
16.242
3138133OCRAN
Solar/Wind Harmer
0.185
940641AE2-051 GEN
Solar/Wind Harmer
24.257
3145663CRESWEL
Solar/Wind Harmer
0.843
971163AH1-040 GEN
Solar/Wind Harmer
24.101
971647AH1-324 GEN
Solar/Wind Harmer
12.816
970661AG2-428 GEN
Solar/Wind Harmer
28.811
971069AG2-661 GEN
Solar/Wind Harmer
5.046
962861AG1-135 GEN
Solar/Wind Harmer
9.061
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.034
3142433PROV 92
Solar/Wind Harmer
1.129
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316381AD1-082 GEN
Solar/Wind Harmer
0.293
970659AG2-427 GEN
Solar/Wind Harmer
13.452
316458AB2-190 GEN2
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
1.091
3150991CHESPKB
50/50
3.902
3150991CHESPKB
50/50
3.808
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.337
316036AC1-147 C
Solar/Wind Harmer
0.065
3145506HICKORY
Solar/Wind Harmer
1.401
3145506HICKORY
Solar/Wind Harmer
0.841
3145506HICKORY
Solar/Wind Harmer
0.21
316339AD2-160 GEN
Solar/Wind Harmer
0.564
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.194
3137176SLIGO L2192
Solar/Wind Harmer
1.377
3146456SLIGO L269
Solar/Wind Harmer
6.122
3130086AYDLETT
Solar/Wind Harmer
1.379
3146386ELIZ CT
Solar/Wind Harmer
0.339
316236AE1-162_GEN
Solar/Wind Harmer
0.003
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146626S HERTFORD
Solar/Wind Harmer
0.326
3146376EDENTON
Solar/Wind Harmer
1.396
972263AH1-716 GEN
50/50
238.379
3151081ELIZAR1
50/50
34.239
3151091ELIZAR2
50/50
33.645
941591AE2-156 GEN
50/50
31.25
3152611GOSPORTB
50/50
4.742
3152621GOSPORTC
50/50
4.025
3152601GOSPORTA
50/50
3.713
957871AF2-081 GEN
Solar/Wind Harmer
17.29
319010AE1-072 C
Solar/Wind Harmer
1.74
3146406KITTY HAWK
Solar/Wind Harmer
0.043
3138283WHITEMARSH
Solar/Wind Harmer
0.08
316305AF2-043 C
Solar/Wind Harmer
0.003
315976AC1-164 GENA
Solar/Wind Harmer
35.232
316169AC1-164_GENC
Solar/Wind Harmer
30.437
315975AC1-164 GENB
Solar/Wind Harmer
1.042
313526AB2-022
Solar/Wind Harmer
0.184
316321Z2-027
Solar/Wind Harmer
0.062
3146396TANGLEW
Solar/Wind Harmer
0.926
3145176PASQUOTANK
Solar/Wind Harmer
0.208
3146486SUNBURY
Solar/Wind Harmer
0.335
3146486SUNBURY
Solar/Wind Harmer
0.335
971445AH1-216 GEN
Solar/Wind Harmer
23.372
315835AF2-110_GEN
Solar/Wind Harmer
2.259
316314AB2-024 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
24.957
3151201GRAVEL4
Adder
23.396
3151191GRAVEL3
Adder
23.099
3151211GRAVEL5
Adder
23.099
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.064
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.314
3130156CHOWAN
Solar/Wind Harmer
0.314
970189AG2-124 GEN
Solar/Wind Harmer
9.301
316311AC2-079 GEN
Solar/Wind Harmer
8.93
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.213
3141913WHIT STONE
Solar/Wind Harmer
0.31
3138133OCRAN
Solar/Wind Harmer
0.092
3143873LANEXA
Solar/Wind Harmer
0.185
3141783LANCAST
Solar/Wind Harmer
0.182
3141783LANCAST
Solar/Wind Harmer
0.122
315816AE2-034 GEN
Solar/Wind Harmer
1.293
962981AG1-147 GEN
Solar/Wind Harmer
11.004
3130546PLYMOUTH
Solar/Wind Harmer
0.291
316369SG1_INVT
Solar/Wind Harmer
0.011
315732AD1-074 GEN1
Solar/Wind Harmer
1.665
315733AD1-074 GEN2
Solar/Wind Harmer
1.665
3146376EDENTON
Solar/Wind Harmer
1.396
315742AE1-103 GEN
Solar/Wind Harmer
0.004
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.327
3142946ENON
Solar/Wind Harmer
0.028
316065AD1-022 GEN
Solar/Wind Harmer
13.139
970657AG2-426 GEN
Solar/Wind Harmer
9.959
970657AG2-426 GEN
Solar/Wind Harmer
2.088
958261AF2-120 GEN
Solar/Wind Harmer
9.287
316075AC2-137 C
Solar/Wind Harmer
0.076
3145893MURPHYS
Solar/Wind Harmer
1.826
3145893MURPHYS
Solar/Wind Harmer
0.491
3146173TUNIS
Solar/Wind Harmer
0.27
3146173TUNIS
Solar/Wind Harmer
0.27
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.78
3150341NORNECKC1
Adder
2.758
972185AH1-677 GEN
Adder
14.884
972187AH1-678 GEN
Adder
7.445
3144356SAPONY
Solar/Wind Harmer
2.128
970933AG2-581 GEN
Solar/Wind Harmer
20.23
3145933PARMELE
Solar/Wind Harmer
0.496
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316426AA2-053 GEN
Solar/Wind Harmer
0.834
3145593CAROLNA
Solar/Wind Harmer
0.242
3145593CAROLNA
Solar/Wind Harmer
0.242
966811AG1-552 GEN
Solar/Wind Harmer
2.63
3145593CAROLNA
Solar/Wind Harmer
0.302
3145783HORNRTN
Solar/Wind Harmer
4.289
3145783HORNRTN
Solar/Wind Harmer
3.432
3145783HORNRTN
Solar/Wind Harmer
1.072
3145783HORNRTN
Solar/Wind Harmer
0.429
316181AB2-040 GEN
Solar/Wind Harmer
0.349
3145796HORNRTN
Solar/Wind Harmer
0.718
316274AC1-208 GEN
Solar/Wind Harmer
1.219
970099AG2-077 GEN
Solar/Wind Harmer
24.387
3145493TOT1
Solar/Wind Harmer
0.519
3145453TOT5
Solar/Wind Harmer
0.311
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.829
316263AC1-034 GEN
Solar/Wind Harmer
8.179
316240AF1-291 C
Solar/Wind Harmer
0.002
944641AF1-129 GEN
Adder
100.049
939181AE1-148 GEN
Solar/Wind Harmer
9.766
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
8.948
971741AH1-377 GEN
Solar/Wind Harmer
18.452
964791AG1-342 GEN
Solar/Wind Harmer
3.551
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
3150691DARBY 3
Adder
13.256
3150701DARBY 4
Adder
13.225
3150681DARBY 2
Adder
13.21
3150671DARBY 1
Adder
13.194
970323AG2-213 GEN
Solar/Wind Harmer
7.78
971775AH1-396 GEN
Solar/Wind Harmer
0.292
316034AC1-036 C
Solar/Wind Harmer
0.013
970301AG2-198 GEN
Solar/Wind Harmer
7.54
971223AH1-071 GEN
Solar/Wind Harmer
1.839
958211AF2-115 GEN
Solar/Wind Harmer
2.062
3145893MURPHYS
Solar/Wind Harmer
1.213
3141726DUNNSVL
Solar/Wind Harmer
1.09
970129AG2-093 GEN
Solar/Wind Harmer
7.721
3146173TUNIS
Solar/Wind Harmer
0.27
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
2.647
944631AF1-128 GEN
Adder
125.685
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3146263WOODLND
Solar/Wind Harmer
0.26
3145823KELFORD
Solar/Wind Harmer
0.257
970919AG2-571 GEN
Solar/Wind Harmer
8.925
970087AG2-069 GEN
Solar/Wind Harmer
19.989
3146293MARTNCO
Solar/Wind Harmer
0.23
316190AA2-174 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.553
316011AB1-132 GEN
Solar/Wind Harmer
4.429
962571AG1-106 GEN
Solar/Wind Harmer
3.466
3145783HORNRTN
Solar/Wind Harmer
0.241
316337AD2-073 GEN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.79
3145796HORNRTN
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.29
316494AC1-189 GEN
Solar/Wind Harmer
0.78
971795AH1-408 GEN
Solar/Wind Harmer
15.293
957481AF2-042 GEN
Solar/Wind Harmer
60.968
315671AE2-027_GEN
Solar/Wind Harmer
14.563
315722AD1-056 GEN
Solar/Wind Harmer
1.431
3147043LAWRENC
Adder
2.037
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.996
3146233WITAKRS
Solar/Wind Harmer
0.879
316129AC1-054 GEN
Solar/Wind Harmer
0.821
315693AD1-088 GEN
Solar/Wind Harmer
10.427
971065AG2-659 GEN
Solar/Wind Harmer
9.224
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.773
316049AB1-081 GEN
Solar/Wind Harmer
1.232
3142053HEARTS
Solar/Wind Harmer
0.379
962491AG1-098 GEN
Solar/Wind Harmer
12.277
3143096IRON208
Adder
0.898
315687AD1-152 GEN
Solar/Wind Harmer
0.007
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3142543TWELFTH
Solar/Wind Harmer
0.018
970401AG2-262 GEN
Solar/Wind Harmer
1.085
3150851SPRUNCC
Adder
0.82
970685AG2-442 GEN
Solar/Wind Harmer
13.21
972135AH1-637 GEN
Solar/Wind Harmer
1.474
3143226MDLTHAN
Solar/Wind Harmer
0.172
963171AG1-166 GEN
Solar/Wind Harmer
0.916
971563AH1-280 GEN
Solar/Wind Harmer
1.832
3144293JTRSVLE
Adder
0.547
3143526WINTERP
Solar/Wind Harmer
0.885
3142416OLDCHRC
Solar/Wind Harmer
0.441
3142416OLDCHRC
Solar/Wind Harmer
0.169
316003AC1-222 GEN
Solar/Wind Harmer
0.004
3146926FARMVIL
Solar/Wind Harmer
0.088
3143336POWHATN
Solar/Wind Harmer
2.408
316336AC2-165 C
Solar/Wind Harmer
0.005
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.047
3150921YORKTN3
50/50
9.838
3144216WINCHST
50/50
1.454
3151101ELIZAR3
50/50
34.678
3151161SURRY 1
50/50
12.347
315773AC2-141 GEN
Solar/Wind Harmer
13.957
316382AG1-145 C
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
80.429
944601AF1-125 GEN
Solar/Wind Harmer
79.19
3144873MCLAUGH
Solar/Wind Harmer
0.009
3144536CHRHLND
Solar/Wind Harmer
0.052
3146456SLIGO L269
Solar/Wind Harmer
0.346
971153AH1-033 GEN
Solar/Wind Harmer
3.999
316320Y1-086
Solar/Wind Harmer
0.002
3145336SMITFLD
Solar/Wind Harmer
0.133
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.33
3146626S HERTFORD
Solar/Wind Harmer
0.326
3151221GRAVEL6
Adder
23.369
3151171GRAVELC
Adder
4.496
3141766HARMONY
Solar/Wind Harmer
4.28
316156AD2-030 GEN
Solar/Wind Harmer
0.236
3141873WAN 176
Solar/Wind Harmer
5.657
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3146376EDENTON
Solar/Wind Harmer
0.314
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.603
3145273HOLLAND
Solar/Wind Harmer
0.235
961611AG1-000B GEN
Solar/Wind Harmer
8.258
315614AA2-178 GEN
Solar/Wind Harmer
1.724
962971AG1-146 GEN
Solar/Wind Harmer
4.716
971157AH1-035 GEN
Solar/Wind Harmer
3.498
315737AD1-076 GEN
Solar/Wind Harmer
3.727
970661AG2-428 GEN
Solar/Wind Harmer
6.128
970009AG2-005 GEN
Solar/Wind Harmer
2.161
3142946ENON
Solar/Wind Harmer
0.096
315778AD1-151 GEN
Solar/Wind Harmer
22.705
3146206CASHIE
Solar/Wind Harmer
0.283
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316083AB2-161 GEN
Solar/Wind Harmer
0.004
316404AE1-155 C
Solar/Wind Harmer
0.063
970659AG2-427 GEN
Solar/Wind Harmer
2.943
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
1.24
3145893MURPHYS
Solar/Wind Harmer
0.457
3145893MURPHYS
Solar/Wind Harmer
0.273
957521AF2-046 GEN
Solar/Wind Harmer
20.241
961681AG1-008 GEN
Solar/Wind Harmer
20.241
970129AG2-093 GEN
Solar/Wind Harmer
16.408
3146173TUNIS
Solar/Wind Harmer
0.27
316463AE2-346 GEN
Solar/Wind Harmer
0.231
316140AB2-099
Solar/Wind Harmer
0.096
962331AG1-082 GEN
Solar/Wind Harmer
2.864
3145963POPLR C
Solar/Wind Harmer
0.267
3150351NORNECKC2
Adder
2.691
315813AE1-149 C
Solar/Wind Harmer
13.997
3146263WOODLND
Solar/Wind Harmer
0.26
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.257
970133AG2-095 GEN
Solar/Wind Harmer
2.439
970917AG2-570 GEN
Solar/Wind Harmer
22.313
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.89
3142666NORTHAMPTON
Solar/Wind Harmer
0.247
316365GEN2_N
Solar/Wind Harmer
0.553
313506AB2-031 GEN
Solar/Wind Harmer
0.743
3145796HORNRTN
Solar/Wind Harmer
0.958
3145796HORNRTN
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.222
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
965281AG1-393 GEN
Solar/Wind Harmer
2.451
970293AG2-193 GEN
Solar/Wind Harmer
2.439
316327AA2-057 GEN
Solar/Wind Harmer
0.342
315724AD1-057 GEN
Solar/Wind Harmer
0.848
3147043LAWRENC
Solar/Wind Harmer
0.135
315839AE2-212 C
Solar/Wind Harmer
0.002
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3146233WITAKRS
Solar/Wind Harmer
1.108
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.759
316486AD2-202 GEN
Solar/Wind Harmer
0.223
961601AG1-000A GEN
Solar/Wind Harmer
15.318
3145543BTLEBRO
Solar/Wind Harmer
0.215
3145543BTLEBRO
Solar/Wind Harmer
0.215
971623AH1-311 GEN
Solar/Wind Harmer
0.43
3143096IRON208
Adder
0.898
3143096IRON208
Adder
0.88
3141906WESTMOR
Solar/Wind Harmer
0.085
316131AB2-060 GEN
Solar/Wind Harmer
0.609
964241AG1-285 GEN
Solar/Wind Harmer
12.68
970737AG2-469 GEN
Solar/Wind Harmer
8.068
315785AD2-033 C
Solar/Wind Harmer
1.5
970257AG2-171 GEN
Solar/Wind Harmer
5.835
959311AF2-222 GEN
Solar/Wind Harmer
16.07
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.598
3150861SPRUNCD
Adder
0.82
970909AG2-566 GEN
Solar/Wind Harmer
1.885
963181AG1-167 GEN
Solar/Wind Harmer
0.687
3144293JTRSVLE
Adder
0.547
3142416OLDCHRC
Solar/Wind Harmer
1.645
3147133PAMPLIN
Solar/Wind Harmer
0.528
971193AH1-056 GEN
Solar/Wind Harmer
10.243
316283AC2-100 C
Solar/Wind Harmer
0.32
971683AH1-343 GEN
Solar/Wind Harmer
5.838
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.088
316313AB2-026
Solar/Wind Harmer
0.085
316258AE1-075 C
Solar/Wind Harmer
0.102
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.047
3146776BUCKING
Solar/Wind Harmer
0.042
315735AD1-075 GEN1
Solar/Wind Harmer
0.833
970327AG2-215 GEN
Solar/Wind Harmer
9.499
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.56
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
971167AH1-042 GEN
Solar/Wind Harmer
24.515
965291AG1-394 GEN
Solar/Wind Harmer
1.225
941031AE2-094 GEN
Solar/Wind Harmer
50.437
944011AF1-069 GEN
Solar/Wind Harmer
16.48
316132AB2-190 GEN1
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
0.273
3145513AHOSKIE
Solar/Wind Harmer
0.561
3145513AHOSKIE
Solar/Wind Harmer
0.268
970673AG2-436 GEN
Solar/Wind Harmer
57.198
970673AG2-436 GEN
Solar/Wind Harmer
38.132
3145683EARLEYS
Solar/Wind Harmer
0.534
3145683EARLEYS
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.267
3141813NORNECK
Solar/Wind Harmer
0.265
971967AH1-528 GEN
Solar/Wind Harmer
41.999
3146043SEABORD
Solar/Wind Harmer
0.257
315607AA1-063A GEN
Solar/Wind Harmer
0.522
316315AB2-025 C
Solar/Wind Harmer
0.206
315814AE2-033 C
Solar/Wind Harmer
20.097
970085AG2-068 GEN
Solar/Wind Harmer
13.326
970581AG2-369 GEN
Solar/Wind Harmer
11.461
3146033SCOT NK
Solar/Wind Harmer
0.989
3143316POE
Solar/Wind Harmer
0.966
315652AC1-086 GEN
Solar/Wind Harmer
26.799
3137643SOCKMAN
Solar/Wind Harmer
0.964
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3145796HORNRTN
Solar/Wind Harmer
0.766
3145796HORNRTN
Solar/Wind Harmer
0.096
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.951
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970181AG2-120 GEN
Solar/Wind Harmer
2.976
957861AF2-080 GEN
Solar/Wind Harmer
9.959
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
9.415
316223AC1-118
Solar/Wind Harmer
0.153
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.071
3144303KENBRDG
Solar/Wind Harmer
0.146
316118AC1-105 GEN
Solar/Wind Harmer
0.468
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
971285AH1-108 GEN
Adder
1.342
970683AG2-441 GEN
Solar/Wind Harmer
11.794
970681AG2-440 GEN
Solar/Wind Harmer
9.435
946301AF1-294 GEN
Solar/Wind Harmer
3.39
961791AG1-021 GEN
Solar/Wind Harmer
1.649
316233AE1-074 FULL
Solar/Wind Harmer
0.136
971281AH1-106 GEN
Solar/Wind Harmer
2.362
971283AH1-107 GEN
Solar/Wind Harmer
2.362
316312AB1-027
Solar/Wind Harmer
0.304
315657AE1-056 GEN
Solar/Wind Harmer
5.802
944491AF1-114 GEN
Solar/Wind Harmer
0
970865AG2-541 GEN
Solar/Wind Harmer
5.175
316123AC1-075 GEN
Solar/Wind Harmer
0.178
970165AG2-112 GEN
Solar/Wind Harmer
1.056
970163AG2-111 GEN
Solar/Wind Harmer
1.007
970285AG2-188 GEN
Solar/Wind Harmer
9.811
971845AH1-439 GEN
Solar/Wind Harmer
5.401
963191AG1-168 GEN
Solar/Wind Harmer
0.687
3144293JTRSVLE
Adder
0.547
3144293JTRSVLE
Adder
0.461
3143526WINTERP
Solar/Wind Harmer
0.885
3147133PAMPLIN
Solar/Wind Harmer
0.168
3147133PAMPLIN
Solar/Wind Harmer
0.134
316222AC1-221 GEN
Solar/Wind Harmer
0.683
3142366NRTHEST
Adder
0.52
942751AE2-291 GEN
Solar/Wind Harmer
6.426
3146776BUCKING
Solar/Wind Harmer
0.466
3146776BUCKING
Solar/Wind Harmer
0.038
NYPJM->LTFIMP_NY
CLTF
2.157
LGEELTFEXP_LGEE->PJM
CLTF
0.951
LAGNLTFEXP_LAGN->PJM
CLTF
7.286
WECLTFEXP_WEC->PJM
CLTF
0.477
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.32
TVALTFEXP_TVA->PJM
CLTF
3.623
CPLELTFEXP_CPLE->PJM
CLTF
12.747
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.757
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.81
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.09
MECLTFEXP_MEC->PJM
CLTF
2.89
SIGELTFEXP_SIGE->PJM
CLTF
0.083

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.46 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3552.3
MW Contribution:11.85
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.238
971353AH1-157 GEN
50/50
31.744
970017AG2-010 GEN
50/50
24.039
3150981CHESPKA
50/50
4.626
316294AC1-161 GEN
Solar/Wind Harmer
6.631
971317AH1-138 GEN
Solar/Wind Harmer
2.676
944591AF1-124 GEN
Solar/Wind Harmer
80.586
3138126ROCKLANDING
Solar/Wind Harmer
0.164
316159AE1-175 C
Solar/Wind Harmer
0.304
316375AC2-012 GEN
Solar/Wind Harmer
0.009
316388AE2-253 GEN
Solar/Wind Harmer
1.086
3146456SLIGO L269
Solar/Wind Harmer
0.345
316246AF1-032 C
Solar/Wind Harmer
0.153
316072AD1-144
Solar/Wind Harmer
0.122
3146516WINFALL
Solar/Wind Harmer
1.066
3146516WINFALL
Solar/Wind Harmer
0.329
316093AE2-104_GEN
Solar/Wind Harmer
5.492
3145336SMITFLD
Solar/Wind Harmer
1.303
939411AE1-173 GEN
Solar/Wind Harmer
137.667
315800Z1-036_GEN1
Solar/Wind Harmer
0.003
3130156CHOWAN
Solar/Wind Harmer
0.313
940641AE2-051 GEN
Solar/Wind Harmer
25.037
3151171GRAVELC
Adder
3.308
3141766HARMONY
Solar/Wind Harmer
0.061
3145663CRESWEL
Solar/Wind Harmer
0.84
971163AH1-040 GEN
Solar/Wind Harmer
24.028
961611AG1-000B GEN
Solar/Wind Harmer
15.572
971777AH1-397 GEN
Solar/Wind Harmer
0.783
3141843SHACKLE
Adder
1.515
3138133OCRAN
Solar/Wind Harmer
0.176
971647AH1-324 GEN
Solar/Wind Harmer
12.191
3146206CASHIE
Solar/Wind Harmer
0.282
971547AH1-271 GEN
Solar/Wind Harmer
6.019
970661AG2-428 GEN
Solar/Wind Harmer
27.952
3145893MURPHYS
Solar/Wind Harmer
1.086
3145893MURPHYS
Solar/Wind Harmer
1.208
316381AD1-082 GEN
Solar/Wind Harmer
0.283
3146173TUNIS
Solar/Wind Harmer
0.269
962861AG1-135 GEN
Solar/Wind Harmer
8.574
970659AG2-427 GEN
Solar/Wind Harmer
12.95
3145963POPLR C
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.266
971069AG2-661 GEN
Solar/Wind Harmer
4.727
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3146263WOODLND
Solar/Wind Harmer
0.259
970919AG2-571 GEN
Solar/Wind Harmer
9.228
3142433PROV 92
Solar/Wind Harmer
1.037
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
970087AG2-069 GEN
Solar/Wind Harmer
20.664
3141726DUNNSVL
Solar/Wind Harmer
1.028
3145823KELFORD
Solar/Wind Harmer
0.257
316458AB2-190 GEN2
Solar/Wind Harmer
1.358
970129AG2-093 GEN
Solar/Wind Harmer
7.142
3150351NORNECKC2
Adder
2.498
3146293MARTNCO
Solar/Wind Harmer
0.23
316190AA2-174 GEN
Solar/Wind Harmer
0
316023GEN1_S
Solar/Wind Harmer
0.55
316011AB1-132 GEN
Solar/Wind Harmer
4.417
962571AG1-106 GEN
Solar/Wind Harmer
3.457
3145783HORNRTN
Solar/Wind Harmer
0.24
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316212AC1-099_GEN
Solar/Wind Harmer
1.238
3145796HORNRTN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.239
960081AF2-299 GEN
Solar/Wind Harmer
2.276
944631AF1-128 GEN
Adder
111.457
957481AF2-042 GEN
Solar/Wind Harmer
61.861
316494AC1-189 GEN
Solar/Wind Harmer
0.781
971795AH1-408 GEN
Solar/Wind Harmer
15.163
316337AD2-073 GEN
Solar/Wind Harmer
0.197
315722AD1-056 GEN
Solar/Wind Harmer
1.431
961671AG1-007 GEN
Solar/Wind Harmer
0.034
3146083TARBORO
Solar/Wind Harmer
0.224
3145493TOT1
Solar/Wind Harmer
0.997
3147043LAWRENC
Adder
2.017
3146233WITAKRS
Solar/Wind Harmer
0.88
315693AD1-088 GEN
Solar/Wind Harmer
10.438
316129AC1-054 GEN
Solar/Wind Harmer
0.818
3145543BTLEBRO
Solar/Wind Harmer
0.216
3145543BTLEBRO
Solar/Wind Harmer
0.172
316359AB2-059 GEN
Solar/Wind Harmer
0.775
316049AB1-081 GEN
Solar/Wind Harmer
1.235
3142053HEARTS
Solar/Wind Harmer
0.38
971065AG2-659 GEN
Solar/Wind Harmer
9.183
962491AG1-098 GEN
Solar/Wind Harmer
12.255
315687AD1-152 GEN
Solar/Wind Harmer
0.007
315671AE2-027_GEN
Solar/Wind Harmer
13.142
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970401AG2-262 GEN
Solar/Wind Harmer
1.076
3143096IRON208
Adder
0.724
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
12.471
972135AH1-637 GEN
Solar/Wind Harmer
1.379
963171AG1-166 GEN
Solar/Wind Harmer
0.854
971563AH1-280 GEN
Solar/Wind Harmer
1.708
3144293JTRSVLE
Adder
0.51
3142543TWELFTH
Solar/Wind Harmer
0.014
3142416OLDCHRC
Solar/Wind Harmer
0.367
3142416OLDCHRC
Solar/Wind Harmer
0.141
3146926FARMVIL
Solar/Wind Harmer
0.076
3150851SPRUNCC
Adder
0.53
3150921YORKTN3
50/50
9.609
3144216WINCHST
50/50
1.419
3151101ELIZAR3
50/50
34.507
3151161SURRY 1
50/50
11.945
315773AC2-141 GEN
Solar/Wind Harmer
13.978
944581AF1-123 GEN
Solar/Wind Harmer
80.3
944601AF1-125 GEN
Solar/Wind Harmer
79.064
316382AG1-145 C
Solar/Wind Harmer
0.003
3144873MCLAUGH
Solar/Wind Harmer
0.009
3146456SLIGO L269
Solar/Wind Harmer
0.345
971153AH1-033 GEN
Solar/Wind Harmer
3.986
3144536CHRHLND
Solar/Wind Harmer
0.051
316320Y1-086
Solar/Wind Harmer
0.002
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.329
3145336SMITFLD
Solar/Wind Harmer
0.13
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
0.313
3145273HOLLAND
Solar/Wind Harmer
0.233
3151221GRAVEL6
Adder
22.609
3151171GRAVELC
Adder
4.35
3141766HARMONY
Solar/Wind Harmer
4.054
316156AD2-030 GEN
Solar/Wind Harmer
0.224
3141873WAN 176
Solar/Wind Harmer
5.376
315614AA2-178 GEN
Solar/Wind Harmer
1.719
316280AD1-041 GEN
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
7.918
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.515
971157AH1-035 GEN
Solar/Wind Harmer
3.489
315737AD1-076 GEN
Solar/Wind Harmer
3.717
3146206CASHIE
Solar/Wind Harmer
0.282
970661AG2-428 GEN
Solar/Wind Harmer
5.945
962971AG1-146 GEN
Solar/Wind Harmer
4.47
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970009AG2-005 GEN
Solar/Wind Harmer
2.047
3156021HOLLOMANSOL
Solar/Wind Harmer
1.237
3145893MURPHYS
Solar/Wind Harmer
0.455
3145893MURPHYS
Solar/Wind Harmer
0.271
316083AB2-161 GEN
Solar/Wind Harmer
0.004
957521AF2-046 GEN
Solar/Wind Harmer
20.157
961681AG1-008 GEN
Solar/Wind Harmer
20.157
3146173TUNIS
Solar/Wind Harmer
0.269
970659AG2-427 GEN
Solar/Wind Harmer
2.833
316463AE2-346 GEN
Solar/Wind Harmer
0.23
316140AB2-099
Solar/Wind Harmer
0.096
962331AG1-082 GEN
Solar/Wind Harmer
2.855
3145963POPLR C
Solar/Wind Harmer
0.267
315778AD1-151 GEN
Solar/Wind Harmer
21.272
316404AE1-155 C
Solar/Wind Harmer
0.06
3146263WOODLND
Solar/Wind Harmer
0.259
970917AG2-570 GEN
Solar/Wind Harmer
23.07
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
3142946ENON
Solar/Wind Harmer
0.086
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.257
970129AG2-093 GEN
Solar/Wind Harmer
15.176
3150351NORNECKC2
Adder
2.54
315813AE1-149 C
Solar/Wind Harmer
13.315
3145933PARMELE
Solar/Wind Harmer
0.248
966801AG1-551 GEN
Solar/Wind Harmer
2.89
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
316365GEN2_N
Solar/Wind Harmer
0.55
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
316210AC1-098 GEN
Solar/Wind Harmer
2.22
313506AB2-031 GEN
Solar/Wind Harmer
0.739
3145796HORNRTN
Solar/Wind Harmer
0.956
3145796HORNRTN
Solar/Wind Harmer
0.239
970133AG2-095 GEN
Solar/Wind Harmer
2.211
316327AA2-057 GEN
Solar/Wind Harmer
0.342
315724AD1-057 GEN
Solar/Wind Harmer
0.849
3146073TAR RVR
Solar/Wind Harmer
0.224
3146083TARBORO
Solar/Wind Harmer
0.224
3147043LAWRENC
Solar/Wind Harmer
0.134
3146233WITAKRS
Solar/Wind Harmer
1.11
3146233WITAKRS
Solar/Wind Harmer
0.15
3138543CONSLDL
Solar/Wind Harmer
0.145
316478AD1-087 GEN
Solar/Wind Harmer
0.767
316486AD2-202 GEN
Solar/Wind Harmer
0.225
961601AG1-000A GEN
Solar/Wind Harmer
15.354
3145543BTLEBRO
Solar/Wind Harmer
0.216
3145543BTLEBRO
Solar/Wind Harmer
0.216
971623AH1-311 GEN
Solar/Wind Harmer
0.431
965281AG1-393 GEN
Solar/Wind Harmer
2.229
315839AE2-212 C
Solar/Wind Harmer
0.002
3141906WESTMOR
Solar/Wind Harmer
0.08
970293AG2-193 GEN
Solar/Wind Harmer
2.109
316131AB2-060 GEN
Solar/Wind Harmer
0.596
964241AG1-285 GEN
Solar/Wind Harmer
12.329
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.602
315785AD2-033 C
Solar/Wind Harmer
1.441
970737AG2-469 GEN
Solar/Wind Harmer
7.562
970257AG2-171 GEN
Solar/Wind Harmer
5.579
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
959311AF2-222 GEN
Solar/Wind Harmer
15.31
316283AC2-100 C
Solar/Wind Harmer
0.323
970909AG2-566 GEN
Solar/Wind Harmer
1.761
963181AG1-167 GEN
Solar/Wind Harmer
0.641
3144293JTRSVLE
Adder
0.51
971683AH1-343 GEN
Solar/Wind Harmer
5.822
3147133PAMPLIN
Solar/Wind Harmer
0.487
971193AH1-056 GEN
Solar/Wind Harmer
9.458
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
1.369
3146926FARMVIL
Solar/Wind Harmer
0.076
3150861SPRUNCD
Adder
0.53
3150991CHESPKB
50/50
3.881
3150991CHESPKB
50/50
3.787
316185AD1-033 GEN
Solar/Wind Harmer
0.01
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.335
3145506HICKORY
Solar/Wind Harmer
1.396
3145506HICKORY
Solar/Wind Harmer
0.838
3145506HICKORY
Solar/Wind Harmer
0.21
316036AC1-147 C
Solar/Wind Harmer
0.065
316339AD2-160 GEN
Solar/Wind Harmer
0.562
316018AA1-139 ULT2
Solar/Wind Harmer
0.009
316017AA1-139 ULT1
Solar/Wind Harmer
0.193
3137176SLIGO L2192
Solar/Wind Harmer
1.372
3146456SLIGO L269
Solar/Wind Harmer
6.101
3130086AYDLETT
Solar/Wind Harmer
1.375
3146386ELIZ CT
Solar/Wind Harmer
0.338
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.329
3146516WINFALL
Solar/Wind Harmer
0.329
3146516WINFALL
Solar/Wind Harmer
0.329
316236AE1-162_GEN
Solar/Wind Harmer
0.003
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146626S HERTFORD
Solar/Wind Harmer
0.325
3146376EDENTON
Solar/Wind Harmer
1.391
3146376EDENTON
Solar/Wind Harmer
1.391
315742AE1-103 GEN
Solar/Wind Harmer
0.004
316065AD1-022 GEN
Solar/Wind Harmer
13.104
970657AG2-426 GEN
Solar/Wind Harmer
9.628
970657AG2-426 GEN
Solar/Wind Harmer
2.018
972185AH1-677 GEN
Adder
15.426
316033AB2-134 GEN
Solar/Wind Harmer
0.016
315697AD1-025 GEN
Solar/Wind Harmer
0.309
3145893MURPHYS
Solar/Wind Harmer
1.818
3145893MURPHYS
Solar/Wind Harmer
0.489
972187AH1-678 GEN
Adder
7.708
3146173TUNIS
Solar/Wind Harmer
0.269
3146173TUNIS
Solar/Wind Harmer
0.269
958261AF2-120 GEN
Solar/Wind Harmer
8.785
970933AG2-581 GEN
Solar/Wind Harmer
20.809
3142946ENON
Solar/Wind Harmer
0.026
3144356SAPONY
Solar/Wind Harmer
2.113
316075AC2-137 C
Solar/Wind Harmer
0.069
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.624
3150341NORNECKC1
Adder
2.603
3145933PARMELE
Solar/Wind Harmer
0.496
3145933PARMELE
Solar/Wind Harmer
0.248
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.246
3142666NORTHAMPTON
Solar/Wind Harmer
0.148
316426AA2-053 GEN
Solar/Wind Harmer
0.831
3145593CAROLNA
Solar/Wind Harmer
0.241
3145593CAROLNA
Solar/Wind Harmer
0.241
966811AG1-552 GEN
Solar/Wind Harmer
2.62
3145593CAROLNA
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
4.275
3145783HORNRTN
Solar/Wind Harmer
3.42
3145783HORNRTN
Solar/Wind Harmer
1.069
3145783HORNRTN
Solar/Wind Harmer
0.428
316181AB2-040 GEN
Solar/Wind Harmer
0.347
3145796HORNRTN
Solar/Wind Harmer
0.717
316274AC1-208 GEN
Solar/Wind Harmer
1.217
970099AG2-077 GEN
Solar/Wind Harmer
24.744
3145493TOT1
Solar/Wind Harmer
0.52
3145453TOT5
Solar/Wind Harmer
0.312
3145603CNETO
Solar/Wind Harmer
0.208
961601AG1-000A GEN
Solar/Wind Harmer
3.839
316263AC1-034 GEN
Solar/Wind Harmer
8.198
939181AE1-148 GEN
Solar/Wind Harmer
9.694
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316240AF1-291 C
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
8.858
944641AF1-129 GEN
Adder
87.436
964791AG1-342 GEN
Solar/Wind Harmer
3.522
3146843MT LREL
Solar/Wind Harmer
0.183
3146843MT LREL
Solar/Wind Harmer
0.183
971741AH1-377 GEN
Solar/Wind Harmer
17.569
970323AG2-213 GEN
Solar/Wind Harmer
7.438
971775AH1-396 GEN
Solar/Wind Harmer
0.279
316034AC1-036 C
Solar/Wind Harmer
0.013
316222AC1-221 GEN
Solar/Wind Harmer
0.689
970301AG2-198 GEN
Solar/Wind Harmer
7.044
958211AF2-115 GEN
Solar/Wind Harmer
1.922
963191AG1-168 GEN
Solar/Wind Harmer
0.641
3144293JTRSVLE
Adder
0.51
3144293JTRSVLE
Adder
0.429
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
3150691DARBY 3
Adder
10.708
3150701DARBY 4
Adder
10.683
3150681DARBY 2
Adder
10.671
3150671DARBY 1
Adder
10.658
3142366NRTHEST
Adder
0.396
942751AE2-291 GEN
Solar/Wind Harmer
6.34
972263AH1-716 GEN
50/50
236.435
3151081ELIZAR1
50/50
34.071
3151091ELIZAR2
50/50
33.48
941591AE2-156 GEN
50/50
31.086
3152611GOSPORTB
50/50
4.716
3152621GOSPORTC
50/50
4.003
3152601GOSPORTA
50/50
3.692
957871AF2-081 GEN
Solar/Wind Harmer
17.231
319010AE1-072 C
Solar/Wind Harmer
1.734
3146406KITTY HAWK
Solar/Wind Harmer
0.043
316305AF2-043 C
Solar/Wind Harmer
0.003
313526AB2-022
Solar/Wind Harmer
0.183
316321Z2-027
Solar/Wind Harmer
0.062
3146396TANGLEW
Solar/Wind Harmer
0.923
3145176PASQUOTANK
Solar/Wind Harmer
0.207
3146486SUNBURY
Solar/Wind Harmer
0.334
3146486SUNBURY
Solar/Wind Harmer
0.334
3138283WHITEMARSH
Solar/Wind Harmer
0.077
315835AF2-110_GEN
Solar/Wind Harmer
2.241
971445AH1-216 GEN
Solar/Wind Harmer
22.847
315611Z1-036_GEN2
Solar/Wind Harmer
0.003
315976AC1-164 GENA
Solar/Wind Harmer
32.93
316169AC1-164_GENC
Solar/Wind Harmer
28.449
315975AC1-164 GENB
Solar/Wind Harmer
0.974
3130156CHOWAN
Solar/Wind Harmer
0.313
3130156CHOWAN
Solar/Wind Harmer
0.313
972265AH1-717 GEN
Adder
24.145
3151201GRAVEL4
Adder
22.635
3151191GRAVEL3
Adder
22.348
3151211GRAVEL5
Adder
22.348
316311AC2-079 GEN
Solar/Wind Harmer
8.775
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.209
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
1.289
315662AE1-191 GEN
Solar/Wind Harmer
0.01
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
8.787
3141913WHIT STONE
Solar/Wind Harmer
0.294
3138133OCRAN
Solar/Wind Harmer
0.088
3130546PLYMOUTH
Solar/Wind Harmer
0.29
315732AD1-074 GEN1
Solar/Wind Harmer
1.66
315733AD1-074 GEN2
Solar/Wind Harmer
1.66
315735AD1-075 GEN1
Solar/Wind Harmer
0.831
3141783LANCAST
Solar/Wind Harmer
0.173
3141783LANCAST
Solar/Wind Harmer
0.115
3143873LANEXA
Solar/Wind Harmer
0.173
941031AE2-094 GEN
Solar/Wind Harmer
52.388
944011AF1-069 GEN
Solar/Wind Harmer
17.117
3146206CASHIE
Solar/Wind Harmer
0.282
970601AG2-382 GEN
Solar/Wind Harmer
10.532
962981AG1-147 GEN
Solar/Wind Harmer
10.429
970673AG2-436 GEN
Solar/Wind Harmer
59.327
970673AG2-436 GEN
Solar/Wind Harmer
39.552
316369SG1_INVT
Solar/Wind Harmer
0.01
965291AG1-394 GEN
Solar/Wind Harmer
1.219
970327AG2-215 GEN
Solar/Wind Harmer
8.996
3145893MURPHYS
Solar/Wind Harmer
0.733
3145893MURPHYS
Solar/Wind Harmer
0.271
971967AH1-528 GEN
Solar/Wind Harmer
43.419
3145513AHOSKIE
Solar/Wind Harmer
0.56
3145513AHOSKIE
Solar/Wind Harmer
0.267
3145683EARLEYS
Solar/Wind Harmer
0.533
3145683EARLEYS
Solar/Wind Harmer
0.266
3145683EARLEYS
Solar/Wind Harmer
0.266
3142433PROV 92
Adder
0.504
3142433PROV 92
Adder
0.504
970085AG2-068 GEN
Solar/Wind Harmer
13.776
970581AG2-369 GEN
Solar/Wind Harmer
11.847
3146043SEABORD
Solar/Wind Harmer
0.256
315607AA1-063A GEN
Solar/Wind Harmer
0.52
316132AB2-190 GEN1
Solar/Wind Harmer
1.358
316315AB2-025 C
Solar/Wind Harmer
0.204
971167AH1-042 GEN
Solar/Wind Harmer
22.411
315814AE2-033 C
Solar/Wind Harmer
19.96
3141813NORNECK
Solar/Wind Harmer
0.25
3146033SCOT NK
Solar/Wind Harmer
0.988
315652AC1-086 GEN
Solar/Wind Harmer
26.724
3137643SOCKMAN
Solar/Wind Harmer
0.96
316005AA1-067
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.952
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
3145746EVERETS
Solar/Wind Harmer
0.239
970181AG2-120 GEN
Solar/Wind Harmer
2.978
3145796HORNRTN
Solar/Wind Harmer
0.765
3145796HORNRTN
Solar/Wind Harmer
0.096
316087AB2-174 GEN
Solar/Wind Harmer
0.007
3143316POE
Solar/Wind Harmer
0.921
957861AF2-080 GEN
Solar/Wind Harmer
9.971
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.224
3145573BETHELC
Solar/Wind Harmer
0.224
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
9.375
316223AC1-118
Solar/Wind Harmer
0.144
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.467
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
971443AH1-215 GEN
Solar/Wind Harmer
2.94
3144303KENBRDG
Solar/Wind Harmer
0.139
970683AG2-441 GEN
Solar/Wind Harmer
11.135
970681AG2-440 GEN
Solar/Wind Harmer
8.908
946301AF1-294 GEN
Solar/Wind Harmer
3.16
961791AG1-021 GEN
Solar/Wind Harmer
1.537
315657AE1-056 GEN
Solar/Wind Harmer
5.357
970865AG2-541 GEN
Solar/Wind Harmer
5.15
316312AB1-027
Solar/Wind Harmer
0.253
944491AF1-114 GEN
Solar/Wind Harmer
0
316123AC1-075 GEN
Solar/Wind Harmer
0.176
970165AG2-112 GEN
Solar/Wind Harmer
1.046
970163AG2-111 GEN
Solar/Wind Harmer
0.997
971285AH1-108 GEN
Adder
0.868
NYPJM->LTFIMP_NY
CLTF
2.077
LAGNLTFEXP_LAGN->PJM
CLTF
7.278
LGEELTFEXP_LGEE->PJM
CLTF
0.931
WECLTFEXP_WEC->PJM
CLTF
0.469
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.541
TVALTFEXP_TVA->PJM
CLTF
3.613
CPLELTFEXP_CPLE->PJM
CLTF
12.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.58
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.522
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.042
MECLTFEXP_MEC->PJM
CLTF
2.857
SIGELTFEXP_SIGE->PJM
CLTF
0.082

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.82 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4430.44
MW Contribution:16.48
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
245.058
3151081ELIZAR1
50/50
35.616
3151091ELIZAR2
50/50
34.998
941591AE2-156 GEN
50/50
32.501
3152611GOSPORTB
50/50
4.932
3152621GOSPORTC
50/50
4.185
3152601GOSPORTA
50/50
3.861
957871AF2-081 GEN
Solar/Wind Harmer
20.328
319010AE1-072 C
Solar/Wind Harmer
8.18
3146406KITTY HAWK
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
1.203
313526AB2-022
Solar/Wind Harmer
1.071
316321Z2-027
Solar/Wind Harmer
1.062
3146396TANGLEW
Solar/Wind Harmer
0.724
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146486SUNBURY
Solar/Wind Harmer
-0.039
957831AF2-077 GEN
Solar/Wind Harmer
1.178
3138283WHITEMARSH
Solar/Wind Harmer
0.061
315835AF2-110_GEN
Solar/Wind Harmer
4.813
971445AH1-216 GEN
Solar/Wind Harmer
23.761
315976AC1-164 GENA
Solar/Wind Harmer
39.88
316169AC1-164_GENC
Solar/Wind Harmer
34.453
315975AC1-164 GENB
Solar/Wind Harmer
1.18
315611Z1-036_GEN2
Solar/Wind Harmer
9.308
972265AH1-717 GEN
Adder
25.54
3151201GRAVEL4
Adder
23.942
3151191GRAVEL3
Adder
23.639
3151211GRAVEL5
Adder
23.639
3130156CHOWAN
Solar/Wind Harmer
-0.037
3130156CHOWAN
Solar/Wind Harmer
-0.037
316311AC2-079 GEN
Solar/Wind Harmer
18.29
315833AF1-017_GEN
Solar/Wind Harmer
6.879
316349AD2-085 GEN
Solar/Wind Harmer
3.221
316314AB2-024 C
Solar/Wind Harmer
3.09
316059AD1-063 C
Solar/Wind Harmer
0.814
957601AF2-054 GEN
Solar/Wind Harmer
1.071
3152331SURRY 2
50/50
17.849
971353AH1-157 GEN
50/50
33.174
970017AG2-010 GEN
50/50
25.134
3150981CHESPKA
50/50
4.837
316294AC1-161 GEN
Solar/Wind Harmer
14.461
971317AH1-138 GEN
Solar/Wind Harmer
5.259
3138126ROCKLANDING
Solar/Wind Harmer
0.128
944591AF1-124 GEN
Solar/Wind Harmer
190.952
316159AE1-175 C
Solar/Wind Harmer
1.112
316375AC2-012 GEN
Solar/Wind Harmer
14.194
316388AE2-253 GEN
Solar/Wind Harmer
2.747
3146456SLIGO L269
Solar/Wind Harmer
-0.04
316246AF1-032 C
Solar/Wind Harmer
0.808
316072AD1-144
Solar/Wind Harmer
0.803
3146516WINFALL
Solar/Wind Harmer
-0.125
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.153
316093AE2-104_GEN
Solar/Wind Harmer
11.194
939411AE1-173 GEN
Solar/Wind Harmer
190.105
315800Z1-036_GEN1
Solar/Wind Harmer
9.308
3151171GRAVELC
Adder
3.499
940641AE2-051 GEN
Solar/Wind Harmer
34.625
3130156CHOWAN
Solar/Wind Harmer
-0.037
3141766HARMONY
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
17.499
3145663CRESWEL
Solar/Wind Harmer
-0.099
971163AH1-040 GEN
Solar/Wind Harmer
33.218
971777AH1-397 GEN
Solar/Wind Harmer
4.139
3141843SHACKLE
Adder
1.601
3138133OCRAN
Solar/Wind Harmer
-0.021
971647AH1-324 GEN
Solar/Wind Harmer
17.132
970661AG2-428 GEN
Solar/Wind Harmer
35.734
3146206CASHIE
Solar/Wind Harmer
-0.033
971547AH1-271 GEN
Solar/Wind Harmer
8.339
316381AD1-082 GEN
Solar/Wind Harmer
2.988
961951AG1-038 GEN
Solar/Wind Harmer
4.276
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.956
970659AG2-427 GEN
Solar/Wind Harmer
17.116
971069AG2-661 GEN
Solar/Wind Harmer
5.087
3146173TUNIS
Solar/Wind Harmer
-0.032
962861AG1-135 GEN
Solar/Wind Harmer
11.897
3145963POPLR C
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
3142433PROV 92
Solar/Wind Harmer
-0.125
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
316174AB2-169 GEN
Solar/Wind Harmer
4.805
3146263WOODLND
Solar/Wind Harmer
-0.031
970919AG2-571 GEN
Solar/Wind Harmer
9.751
3141873WAN 176
Solar/Wind Harmer
-0.007
315662AE1-191 GEN
Solar/Wind Harmer
4.274
315666AE1-190 GEN
Solar/Wind Harmer
1.068
315816AE2-034 GEN
Solar/Wind Harmer
2.867
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.02
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
6.901
315733AD1-074 GEN2
Solar/Wind Harmer
6.901
315735AD1-075 GEN1
Solar/Wind Harmer
3.452
941031AE2-094 GEN
Solar/Wind Harmer
63.201
944011AF1-069 GEN
Solar/Wind Harmer
19.803
3146206CASHIE
Solar/Wind Harmer
-0.033
970601AG2-382 GEN
Solar/Wind Harmer
14.593
316369SG1_INVT
Solar/Wind Harmer
5.912
962981AG1-147 GEN
Solar/Wind Harmer
14.47
970673AG2-436 GEN
Solar/Wind Harmer
69.275
970673AG2-436 GEN
Solar/Wind Harmer
35.076
965291AG1-394 GEN
Solar/Wind Harmer
2.886
971967AH1-528 GEN
Solar/Wind Harmer
60.585
316318V4-068
Solar/Wind Harmer
0.803
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.277
961941AG1-037 GEN
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
316132AB2-190 GEN1
Solar/Wind Harmer
3.115
970085AG2-068 GEN
Solar/Wind Harmer
19.167
970581AG2-369 GEN
Solar/Wind Harmer
16.484
971167AH1-042 GEN
Solar/Wind Harmer
29.439
3146043SEABORD
Solar/Wind Harmer
-0.03
316315AB2-025 C
Solar/Wind Harmer
0.819
315814AE2-033 C
Solar/Wind Harmer
28.221
315607AA1-063A GEN
Solar/Wind Harmer
3.058
3141813NORNECK
Solar/Wind Harmer
-0.03
3146033SCOT NK
Solar/Wind Harmer
-0.117
315652AC1-086 GEN
Solar/Wind Harmer
32.605
3137643SOCKMAN
Solar/Wind Harmer
-0.114
316087AB2-174 GEN
Solar/Wind Harmer
4.07
3145796HORNRTN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.011
316005AA1-067
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
-0.112
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
970181AG2-120 GEN
Solar/Wind Harmer
3.729
3143316POE
Solar/Wind Harmer
-0.112
946281AF1-292 GEN
Solar/Wind Harmer
0.636
957861AF2-080 GEN
Solar/Wind Harmer
12.026
316420AA1-050 GEN
Solar/Wind Harmer
3.089
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
316319Z2-044 C
Solar/Wind Harmer
1.456
970831AG2-522 GEN
Solar/Wind Harmer
13.167
971285AH1-108 GEN
Adder
1.156
316458AB2-190 GEN2
Solar/Wind Harmer
3.115
970087AG2-069 GEN
Solar/Wind Harmer
28.751
970129AG2-093 GEN
Solar/Wind Harmer
6.971
3145823KELFORD
Solar/Wind Harmer
-0.03
964211AG1-282 GEN
Solar/Wind Harmer
0.916
3141726DUNNSVL
Solar/Wind Harmer
-0.121
3150351NORNECKC2
Adder
2.633
3146293MARTNCO
Solar/Wind Harmer
0.182
316023GEN1_S
Solar/Wind Harmer
1.978
316190AA2-174 GEN
Solar/Wind Harmer
0.36
316011AB1-132 GEN
Solar/Wind Harmer
6.064
962571AG1-106 GEN
Solar/Wind Harmer
4.166
944631AF1-128 GEN
Adder
122.397
3145783HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.028
316212AC1-099_GEN
Solar/Wind Harmer
2.482
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
960081AF2-299 GEN
Solar/Wind Harmer
3.194
957481AF2-042 GEN
Solar/Wind Harmer
86.835
316494AC1-189 GEN
Solar/Wind Harmer
2.958
971795AH1-408 GEN
Solar/Wind Harmer
20.476
315722AD1-056 GEN
Solar/Wind Harmer
2.819
3147043LAWRENC
Adder
2.158
316337AD2-073 GEN
Solar/Wind Harmer
0.72
961671AG1-007 GEN
Solar/Wind Harmer
0.338
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.792
3146233WITAKRS
Solar/Wind Harmer
-0.104
315693AD1-088 GEN
Solar/Wind Harmer
13.109
316129AC1-054 GEN
Solar/Wind Harmer
2.286
962491AG1-098 GEN
Solar/Wind Harmer
17.339
971065AG2-659 GEN
Solar/Wind Harmer
12.912
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
316359AB2-059 GEN
Solar/Wind Harmer
3.466
316049AB1-081 GEN
Solar/Wind Harmer
2.774
3142053HEARTS
Solar/Wind Harmer
0.302
3143096IRON208
Adder
0.84
3144293JTRSVLE
Adder
0.566
3150851SPRUNCC
Adder
0.706
315671AE2-027_GEN
Solar/Wind Harmer
11.051
3150991CHESPKB
50/50
4.058
3150991CHESPKB
50/50
3.96
316185AD1-033 GEN
Solar/Wind Harmer
4.341
3142956BIRDNECK
Solar/Wind Harmer
2.204
316316AC1-027 C
Solar/Wind Harmer
1.26
316036AC1-147 C
Solar/Wind Harmer
1.107
3145506HICKORY
Solar/Wind Harmer
-0.163
3145506HICKORY
Solar/Wind Harmer
-0.098
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.747
316018AA1-139 ULT2
Solar/Wind Harmer
3.483
316017AA1-139 ULT1
Solar/Wind Harmer
3.29
3137176SLIGO L2192
Solar/Wind Harmer
-0.16
3146456SLIGO L269
Solar/Wind Harmer
4.784
3130086AYDLETT
Solar/Wind Harmer
-0.161
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.039
316433W1029_GEN2
Solar/Wind Harmer
7.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316236AE1-162_GEN
Solar/Wind Harmer
1.162
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3146376EDENTON
Solar/Wind Harmer
1.094
3146376EDENTON
Solar/Wind Harmer
1.094
315742AE1-103 GEN
Solar/Wind Harmer
3.754
316441AF1-014 GEN
Solar/Wind Harmer
2.373
316065AD1-022 GEN
Solar/Wind Harmer
16.818
316033AB2-134 GEN
Solar/Wind Harmer
10.67
315697AD1-025 GEN
Solar/Wind Harmer
6.692
970657AG2-426 GEN
Solar/Wind Harmer
10.306
970657AG2-426 GEN
Solar/Wind Harmer
2.155
972185AH1-677 GEN
Adder
16.285
316487AF1-042 GEN
Solar/Wind Harmer
4.276
3145893MURPHYS
Solar/Wind Harmer
0.899
3145893MURPHYS
Solar/Wind Harmer
-0.058
972187AH1-678 GEN
Adder
8.141
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
3142946ENON
Solar/Wind Harmer
-0.003
958261AF2-120 GEN
Solar/Wind Harmer
12.191
970933AG2-581 GEN
Solar/Wind Harmer
29.026
316075AC2-137 C
Solar/Wind Harmer
0.82
3144356SAPONY
Solar/Wind Harmer
1.059
316077AC2-138 C
Solar/Wind Harmer
0.626
3150341NORNECKC1
Adder
2.766
3150341NORNECKC1
Adder
2.744
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.961
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.242
3145593CAROLNA
Solar/Wind Harmer
0.239
3145783HORNRTN
Solar/Wind Harmer
3.403
3145783HORNRTN
Solar/Wind Harmer
2.722
3145783HORNRTN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
0.34
316181AB2-040 GEN
Solar/Wind Harmer
3.988
3145796HORNRTN
Solar/Wind Harmer
-0.085
316274AC1-208 GEN
Solar/Wind Harmer
3.015
970099AG2-077 GEN
Solar/Wind Harmer
34.734
3145493TOT1
Solar/Wind Harmer
0.413
3145453TOT5
Solar/Wind Harmer
0.248
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.115
316263AC1-034 GEN
Solar/Wind Harmer
12.052
944641AF1-129 GEN
Adder
98.625
3144293JTRSVLE
Adder
0.566
3144293JTRSVLE
Adder
0.477
3150691DARBY 3
Adder
12.42
3150701DARBY 4
Adder
12.391
3150681DARBY 2
Adder
12.376
3150671DARBY 1
Adder
12.362
3142366NRTHEST
Adder
0.477
3150921YORKTN3
50/50
10.038
3144216WINCHST
50/50
1.484
3151101ELIZAR3
50/50
36.072
3151161SURRY 1
50/50
12.635
315773AC2-141 GEN
Solar/Wind Harmer
18.703
944581AF1-123 GEN
Solar/Wind Harmer
190.267
944601AF1-125 GEN
Solar/Wind Harmer
187.297
316382AG1-145 C
Solar/Wind Harmer
1.248
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.937
3144536CHRHLND
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
2.327
316435W1029_GEN3
Solar/Wind Harmer
7.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.015
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3151221GRAVEL6
Adder
23.914
3151171GRAVELC
Adder
4.601
3146376EDENTON
Solar/Wind Harmer
-0.037
3145273HOLLAND
Solar/Wind Harmer
-0.027
3141766HARMONY
Solar/Wind Harmer
3.206
316156AD2-030 GEN
Solar/Wind Harmer
0.956
3141873WAN 176
Solar/Wind Harmer
4.248
961611AG1-000B GEN
Solar/Wind Harmer
7.467
316280AD1-041 GEN
Solar/Wind Harmer
2.671
315614AA2-178 GEN
Solar/Wind Harmer
3.823
316203AE2-005 GEN
Solar/Wind Harmer
14.843
3141843SHACKLE
Adder
1.601
971157AH1-035 GEN
Solar/Wind Harmer
4.292
315737AD1-076 GEN
Solar/Wind Harmer
6.486
970661AG2-428 GEN
Solar/Wind Harmer
6.333
3146206CASHIE
Solar/Wind Harmer
-0.033
962971AG1-146 GEN
Solar/Wind Harmer
6.201
3156081AA2-088 GEN
Solar/Wind Harmer
10.646
316083AB2-161 GEN
Solar/Wind Harmer
5.288
316484AD2-074 GEN
Solar/Wind Harmer
8.171
970009AG2-005 GEN
Solar/Wind Harmer
4.057
3156021HOLLOMANSOL
Solar/Wind Harmer
4.346
3145893MURPHYS
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
-0.032
970659AG2-427 GEN
Solar/Wind Harmer
3.033
315778AD1-151 GEN
Solar/Wind Harmer
27.849
957521AF2-046 GEN
Solar/Wind Harmer
25.299
961681AG1-008 GEN
Solar/Wind Harmer
25.299
3146173TUNIS
Solar/Wind Harmer
-0.032
316463AE2-346 GEN
Solar/Wind Harmer
0.514
316140AB2-099
Solar/Wind Harmer
0.214
962331AG1-082 GEN
Solar/Wind Harmer
3.966
3145963POPLR C
Solar/Wind Harmer
-0.032
3142946ENON
Solar/Wind Harmer
-0.01
316404AE1-155 C
Solar/Wind Harmer
6.069
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
3146263WOODLND
Solar/Wind Harmer
-0.031
970917AG2-570 GEN
Solar/Wind Harmer
77.031
970129AG2-093 GEN
Solar/Wind Harmer
17.21
316317KELFORD C
Solar/Wind Harmer
1.436
3145823KELFORD
Solar/Wind Harmer
-0.03
315813AE1-149 C
Solar/Wind Harmer
18.925
3150351NORNECKC2
Adder
2.677
3145933PARMELE
Solar/Wind Harmer
-0.029
966801AG1-551 GEN
Solar/Wind Harmer
3.677
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
316365GEN2_N
Solar/Wind Harmer
1.978
313506AB2-031 GEN
Solar/Wind Harmer
2.298
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316210AC1-098 GEN
Solar/Wind Harmer
4.468
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
966621AG1-532 GEN
Solar/Wind Harmer
0.576
970133AG2-095 GEN
Solar/Wind Harmer
3.189
316327AA2-057 GEN
Solar/Wind Harmer
2.724
315724AD1-057 GEN
Solar/Wind Harmer
1.551
3147043LAWRENC
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
316478AD1-087 GEN
Solar/Wind Harmer
2.285
316486AD2-202 GEN
Solar/Wind Harmer
0.669
3146233WITAKRS
Solar/Wind Harmer
0.551
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
965281AG1-393 GEN
Solar/Wind Harmer
3.244
961601AG1-000A GEN
Solar/Wind Harmer
10.243
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.84
3143096IRON208
Adder
0.823
3144293JTRSVLE
Adder
0.566
3150861SPRUNCD
Adder
0.706
NYPJM->LTFIMP_NY
CLTF
2.271
LGEELTFEXP_LGEE->PJM
CLTF
1.047
LAGNLTFEXP_LAGN->PJM
CLTF
7.902
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.391
WECLTFEXP_WEC->PJM
CLTF
0.527
TVALTFEXP_TVA->PJM
CLTF
3.928
CPLELTFEXP_CPLE->PJM
CLTF
13.727
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.914
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.126
MECLTFEXP_MEC->PJM
CLTF
3.168
SIGELTFEXP_SIGE->PJM
CLTF
0.092

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.82 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4430.44
MW Contribution:16.48
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.849
971353AH1-157 GEN
50/50
33.174
970017AG2-010 GEN
50/50
25.134
3150981CHESPKA
50/50
4.837
316294AC1-161 GEN
Solar/Wind Harmer
14.461
971317AH1-138 GEN
Solar/Wind Harmer
5.259
3138126ROCKLANDING
Solar/Wind Harmer
0.128
944591AF1-124 GEN
Solar/Wind Harmer
190.952
316159AE1-175 C
Solar/Wind Harmer
1.112
316375AC2-012 GEN
Solar/Wind Harmer
14.194
316388AE2-253 GEN
Solar/Wind Harmer
2.747
3146456SLIGO L269
Solar/Wind Harmer
-0.04
316246AF1-032 C
Solar/Wind Harmer
0.808
316072AD1-144
Solar/Wind Harmer
0.803
3146516WINFALL
Solar/Wind Harmer
-0.125
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.153
316093AE2-104_GEN
Solar/Wind Harmer
11.194
939411AE1-173 GEN
Solar/Wind Harmer
190.105
315800Z1-036_GEN1
Solar/Wind Harmer
9.308
3151171GRAVELC
Adder
3.499
940641AE2-051 GEN
Solar/Wind Harmer
34.625
3130156CHOWAN
Solar/Wind Harmer
-0.037
3141766HARMONY
Solar/Wind Harmer
-0.007
961611AG1-000B GEN
Solar/Wind Harmer
17.499
3145663CRESWEL
Solar/Wind Harmer
-0.099
971163AH1-040 GEN
Solar/Wind Harmer
33.218
971777AH1-397 GEN
Solar/Wind Harmer
4.139
3141843SHACKLE
Adder
1.601
3138133OCRAN
Solar/Wind Harmer
-0.021
971647AH1-324 GEN
Solar/Wind Harmer
17.132
970661AG2-428 GEN
Solar/Wind Harmer
35.734
3146206CASHIE
Solar/Wind Harmer
-0.033
971547AH1-271 GEN
Solar/Wind Harmer
8.339
316381AD1-082 GEN
Solar/Wind Harmer
2.988
961951AG1-038 GEN
Solar/Wind Harmer
4.276
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.956
970659AG2-427 GEN
Solar/Wind Harmer
17.116
971069AG2-661 GEN
Solar/Wind Harmer
5.087
3146173TUNIS
Solar/Wind Harmer
-0.032
962861AG1-135 GEN
Solar/Wind Harmer
11.897
3145963POPLR C
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
3142433PROV 92
Solar/Wind Harmer
-0.125
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
316174AB2-169 GEN
Solar/Wind Harmer
4.805
3146263WOODLND
Solar/Wind Harmer
-0.031
970919AG2-571 GEN
Solar/Wind Harmer
9.751
316458AB2-190 GEN2
Solar/Wind Harmer
3.115
970087AG2-069 GEN
Solar/Wind Harmer
28.751
970129AG2-093 GEN
Solar/Wind Harmer
6.971
3145823KELFORD
Solar/Wind Harmer
-0.03
964211AG1-282 GEN
Solar/Wind Harmer
0.916
3141726DUNNSVL
Solar/Wind Harmer
-0.121
3150351NORNECKC2
Adder
2.633
3146293MARTNCO
Solar/Wind Harmer
0.182
316023GEN1_S
Solar/Wind Harmer
1.978
316190AA2-174 GEN
Solar/Wind Harmer
0.36
316011AB1-132 GEN
Solar/Wind Harmer
6.064
962571AG1-106 GEN
Solar/Wind Harmer
4.166
944631AF1-128 GEN
Adder
122.397
3145783HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.094
972263AH1-716 GEN
50/50
245.058
3151081ELIZAR1
50/50
35.616
3151091ELIZAR2
50/50
34.998
941591AE2-156 GEN
50/50
32.501
3152611GOSPORTB
50/50
4.932
3152621GOSPORTC
50/50
4.185
3152601GOSPORTA
50/50
3.861
957871AF2-081 GEN
Solar/Wind Harmer
20.328
319010AE1-072 C
Solar/Wind Harmer
8.18
3146406KITTY HAWK
Solar/Wind Harmer
0.034
316305AF2-043 C
Solar/Wind Harmer
1.203
313526AB2-022
Solar/Wind Harmer
1.071
316321Z2-027
Solar/Wind Harmer
1.062
3146396TANGLEW
Solar/Wind Harmer
0.724
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
3146486SUNBURY
Solar/Wind Harmer
-0.039
3146486SUNBURY
Solar/Wind Harmer
-0.039
957831AF2-077 GEN
Solar/Wind Harmer
1.178
3138283WHITEMARSH
Solar/Wind Harmer
0.061
315835AF2-110_GEN
Solar/Wind Harmer
4.813
971445AH1-216 GEN
Solar/Wind Harmer
23.761
315976AC1-164 GENA
Solar/Wind Harmer
39.88
316169AC1-164_GENC
Solar/Wind Harmer
34.453
315975AC1-164 GENB
Solar/Wind Harmer
1.18
315611Z1-036_GEN2
Solar/Wind Harmer
9.308
972265AH1-717 GEN
Adder
25.54
3151201GRAVEL4
Adder
23.942
3151191GRAVEL3
Adder
23.639
3151211GRAVEL5
Adder
23.639
3130156CHOWAN
Solar/Wind Harmer
-0.037
3130156CHOWAN
Solar/Wind Harmer
-0.037
316311AC2-079 GEN
Solar/Wind Harmer
18.29
315833AF1-017_GEN
Solar/Wind Harmer
6.879
316349AD2-085 GEN
Solar/Wind Harmer
3.221
316314AB2-024 C
Solar/Wind Harmer
3.09
316059AD1-063 C
Solar/Wind Harmer
0.814
957601AF2-054 GEN
Solar/Wind Harmer
1.071
3141873WAN 176
Solar/Wind Harmer
-0.007
315662AE1-191 GEN
Solar/Wind Harmer
4.274
315666AE1-190 GEN
Solar/Wind Harmer
1.068
315816AE2-034 GEN
Solar/Wind Harmer
2.867
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.02
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
6.901
315733AD1-074 GEN2
Solar/Wind Harmer
6.901
315735AD1-075 GEN1
Solar/Wind Harmer
3.452
941031AE2-094 GEN
Solar/Wind Harmer
63.201
944011AF1-069 GEN
Solar/Wind Harmer
19.803
3146206CASHIE
Solar/Wind Harmer
-0.033
970601AG2-382 GEN
Solar/Wind Harmer
14.593
316369SG1_INVT
Solar/Wind Harmer
5.912
962981AG1-147 GEN
Solar/Wind Harmer
14.47
970673AG2-436 GEN
Solar/Wind Harmer
69.275
970673AG2-436 GEN
Solar/Wind Harmer
35.076
965291AG1-394 GEN
Solar/Wind Harmer
2.886
971967AH1-528 GEN
Solar/Wind Harmer
60.585
316318V4-068
Solar/Wind Harmer
0.803
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.277
961941AG1-037 GEN
Solar/Wind Harmer
0.238
3145513AHOSKIE
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
316132AB2-190 GEN1
Solar/Wind Harmer
3.115
970085AG2-068 GEN
Solar/Wind Harmer
19.167
970581AG2-369 GEN
Solar/Wind Harmer
16.484
971167AH1-042 GEN
Solar/Wind Harmer
29.439
3146043SEABORD
Solar/Wind Harmer
-0.03
316315AB2-025 C
Solar/Wind Harmer
0.819
315814AE2-033 C
Solar/Wind Harmer
28.221
315607AA1-063A GEN
Solar/Wind Harmer
3.058
3141813NORNECK
Solar/Wind Harmer
-0.03
3146033SCOT NK
Solar/Wind Harmer
-0.117
315652AC1-086 GEN
Solar/Wind Harmer
32.605
3137643SOCKMAN
Solar/Wind Harmer
-0.114
316087AB2-174 GEN
Solar/Wind Harmer
4.07
3145796HORNRTN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.011
316005AA1-067
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
-0.112
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
970181AG2-120 GEN
Solar/Wind Harmer
3.729
3143316POE
Solar/Wind Harmer
-0.112
946281AF1-292 GEN
Solar/Wind Harmer
0.636
957861AF2-080 GEN
Solar/Wind Harmer
12.026
316420AA1-050 GEN
Solar/Wind Harmer
3.089
3145573BETHELC
Solar/Wind Harmer
-0.027
3145573BETHELC
Solar/Wind Harmer
-0.027
316319Z2-044 C
Solar/Wind Harmer
1.456
970831AG2-522 GEN
Solar/Wind Harmer
13.167
971285AH1-108 GEN
Adder
1.156
3145796HORNRTN
Solar/Wind Harmer
-0.028
316212AC1-099_GEN
Solar/Wind Harmer
2.482
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
960081AF2-299 GEN
Solar/Wind Harmer
3.194
957481AF2-042 GEN
Solar/Wind Harmer
86.835
316494AC1-189 GEN
Solar/Wind Harmer
2.958
971795AH1-408 GEN
Solar/Wind Harmer
20.476
315722AD1-056 GEN
Solar/Wind Harmer
2.819
3147043LAWRENC
Adder
2.158
316337AD2-073 GEN
Solar/Wind Harmer
0.72
961671AG1-007 GEN
Solar/Wind Harmer
0.338
3146083TARBORO
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.792
3146233WITAKRS
Solar/Wind Harmer
-0.104
315693AD1-088 GEN
Solar/Wind Harmer
13.109
316129AC1-054 GEN
Solar/Wind Harmer
2.286
962491AG1-098 GEN
Solar/Wind Harmer
17.339
971065AG2-659 GEN
Solar/Wind Harmer
12.912
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.021
316359AB2-059 GEN
Solar/Wind Harmer
3.466
316049AB1-081 GEN
Solar/Wind Harmer
2.774
3142053HEARTS
Solar/Wind Harmer
0.302
3143096IRON208
Adder
0.84
3144293JTRSVLE
Adder
0.566
3150851SPRUNCC
Adder
0.706
315671AE2-027_GEN
Solar/Wind Harmer
11.051
3150921YORKTN3
50/50
10.038
3144216WINCHST
50/50
1.484
3151101ELIZAR3
50/50
36.072
3151161SURRY 1
50/50
12.635
315773AC2-141 GEN
Solar/Wind Harmer
18.703
944581AF1-123 GEN
Solar/Wind Harmer
190.267
944601AF1-125 GEN
Solar/Wind Harmer
187.297
316382AG1-145 C
Solar/Wind Harmer
1.248
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.937
3144536CHRHLND
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
2.327
316435W1029_GEN3
Solar/Wind Harmer
7.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3145336SMITFLD
Solar/Wind Harmer
-0.015
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3151221GRAVEL6
Adder
23.914
3151171GRAVELC
Adder
4.601
3146376EDENTON
Solar/Wind Harmer
-0.037
3145273HOLLAND
Solar/Wind Harmer
-0.027
3141766HARMONY
Solar/Wind Harmer
3.206
316156AD2-030 GEN
Solar/Wind Harmer
0.956
3141873WAN 176
Solar/Wind Harmer
4.248
961611AG1-000B GEN
Solar/Wind Harmer
7.467
316280AD1-041 GEN
Solar/Wind Harmer
2.671
315614AA2-178 GEN
Solar/Wind Harmer
3.823
316203AE2-005 GEN
Solar/Wind Harmer
14.843
3141843SHACKLE
Adder
1.601
971157AH1-035 GEN
Solar/Wind Harmer
4.292
315737AD1-076 GEN
Solar/Wind Harmer
6.486
970661AG2-428 GEN
Solar/Wind Harmer
6.333
3146206CASHIE
Solar/Wind Harmer
-0.033
962971AG1-146 GEN
Solar/Wind Harmer
6.201
3156081AA2-088 GEN
Solar/Wind Harmer
10.646
316083AB2-161 GEN
Solar/Wind Harmer
5.288
316484AD2-074 GEN
Solar/Wind Harmer
8.171
970009AG2-005 GEN
Solar/Wind Harmer
4.057
3156021HOLLOMANSOL
Solar/Wind Harmer
4.346
3145893MURPHYS
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
-0.032
970659AG2-427 GEN
Solar/Wind Harmer
3.033
315778AD1-151 GEN
Solar/Wind Harmer
27.849
957521AF2-046 GEN
Solar/Wind Harmer
25.299
961681AG1-008 GEN
Solar/Wind Harmer
25.299
3146173TUNIS
Solar/Wind Harmer
-0.032
316463AE2-346 GEN
Solar/Wind Harmer
0.514
316140AB2-099
Solar/Wind Harmer
0.214
962331AG1-082 GEN
Solar/Wind Harmer
3.966
3145963POPLR C
Solar/Wind Harmer
-0.032
3142946ENON
Solar/Wind Harmer
-0.01
316404AE1-155 C
Solar/Wind Harmer
6.069
3142433PROV 92
Adder
0.542
3142433PROV 92
Adder
0.542
3146263WOODLND
Solar/Wind Harmer
-0.031
970917AG2-570 GEN
Solar/Wind Harmer
77.031
970129AG2-093 GEN
Solar/Wind Harmer
17.21
316317KELFORD C
Solar/Wind Harmer
1.436
3145823KELFORD
Solar/Wind Harmer
-0.03
315813AE1-149 C
Solar/Wind Harmer
18.925
3150351NORNECKC2
Adder
2.677
3145933PARMELE
Solar/Wind Harmer
-0.029
966801AG1-551 GEN
Solar/Wind Harmer
3.677
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
316365GEN2_N
Solar/Wind Harmer
1.978
313506AB2-031 GEN
Solar/Wind Harmer
2.298
3145796HORNRTN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.028
316210AC1-098 GEN
Solar/Wind Harmer
4.468
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.028
966621AG1-532 GEN
Solar/Wind Harmer
0.576
970133AG2-095 GEN
Solar/Wind Harmer
3.189
316327AA2-057 GEN
Solar/Wind Harmer
2.724
315724AD1-057 GEN
Solar/Wind Harmer
1.551
3147043LAWRENC
Solar/Wind Harmer
-0.016
3146073TAR RVR
Solar/Wind Harmer
-0.027
3146083TARBORO
Solar/Wind Harmer
-0.027
316478AD1-087 GEN
Solar/Wind Harmer
2.285
316486AD2-202 GEN
Solar/Wind Harmer
0.669
3146233WITAKRS
Solar/Wind Harmer
0.551
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
965281AG1-393 GEN
Solar/Wind Harmer
3.244
961601AG1-000A GEN
Solar/Wind Harmer
10.243
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3145543BTLEBRO
Solar/Wind Harmer
-0.026
3143096IRON208
Adder
0.84
3143096IRON208
Adder
0.823
3144293JTRSVLE
Adder
0.566
3150861SPRUNCD
Adder
0.706
3150991CHESPKB
50/50
4.058
3150991CHESPKB
50/50
3.96
316185AD1-033 GEN
Solar/Wind Harmer
4.341
3142956BIRDNECK
Solar/Wind Harmer
2.204
316316AC1-027 C
Solar/Wind Harmer
1.26
316036AC1-147 C
Solar/Wind Harmer
1.107
3145506HICKORY
Solar/Wind Harmer
-0.163
3145506HICKORY
Solar/Wind Harmer
-0.098
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.747
316018AA1-139 ULT2
Solar/Wind Harmer
3.483
316017AA1-139 ULT1
Solar/Wind Harmer
3.29
3137176SLIGO L2192
Solar/Wind Harmer
-0.16
3146456SLIGO L269
Solar/Wind Harmer
4.784
3130086AYDLETT
Solar/Wind Harmer
-0.161
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.039
316433W1029_GEN2
Solar/Wind Harmer
7.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316236AE1-162_GEN
Solar/Wind Harmer
1.162
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3146626S HERTFORD
Solar/Wind Harmer
-0.038
3146376EDENTON
Solar/Wind Harmer
1.094
3146376EDENTON
Solar/Wind Harmer
1.094
315742AE1-103 GEN
Solar/Wind Harmer
3.754
316441AF1-014 GEN
Solar/Wind Harmer
2.373
316065AD1-022 GEN
Solar/Wind Harmer
16.818
316033AB2-134 GEN
Solar/Wind Harmer
10.67
315697AD1-025 GEN
Solar/Wind Harmer
6.692
970657AG2-426 GEN
Solar/Wind Harmer
10.306
970657AG2-426 GEN
Solar/Wind Harmer
2.155
972185AH1-677 GEN
Adder
16.285
316487AF1-042 GEN
Solar/Wind Harmer
4.276
3145893MURPHYS
Solar/Wind Harmer
0.899
3145893MURPHYS
Solar/Wind Harmer
-0.058
972187AH1-678 GEN
Adder
8.141
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
3142946ENON
Solar/Wind Harmer
-0.003
958261AF2-120 GEN
Solar/Wind Harmer
12.191
970933AG2-581 GEN
Solar/Wind Harmer
29.026
316075AC2-137 C
Solar/Wind Harmer
0.82
3144356SAPONY
Solar/Wind Harmer
1.059
316077AC2-138 C
Solar/Wind Harmer
0.626
3150341NORNECKC1
Adder
2.766
3150341NORNECKC1
Adder
2.744
3145933PARMELE
Solar/Wind Harmer
-0.058
3145933PARMELE
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.029
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.961
3145593CAROLNA
Solar/Wind Harmer
-0.029
3145593CAROLNA
Solar/Wind Harmer
-0.029
966811AG1-552 GEN
Solar/Wind Harmer
3.242
3145593CAROLNA
Solar/Wind Harmer
0.239
3145783HORNRTN
Solar/Wind Harmer
3.403
3145783HORNRTN
Solar/Wind Harmer
2.722
3145783HORNRTN
Solar/Wind Harmer
0.851
3145783HORNRTN
Solar/Wind Harmer
0.34
316181AB2-040 GEN
Solar/Wind Harmer
3.988
3145796HORNRTN
Solar/Wind Harmer
-0.085
316274AC1-208 GEN
Solar/Wind Harmer
3.015
970099AG2-077 GEN
Solar/Wind Harmer
34.734
3145493TOT1
Solar/Wind Harmer
0.413
3145453TOT5
Solar/Wind Harmer
0.248
3145603CNETO
Solar/Wind Harmer
0.165
961601AG1-000A GEN
Solar/Wind Harmer
10.115
316263AC1-034 GEN
Solar/Wind Harmer
12.052
944641AF1-129 GEN
Adder
98.625
3144293JTRSVLE
Adder
0.566
3144293JTRSVLE
Adder
0.477
3150691DARBY 3
Adder
12.42
3150701DARBY 4
Adder
12.391
3150681DARBY 2
Adder
12.376
3150671DARBY 1
Adder
12.362
3142366NRTHEST
Adder
0.477
NYPJM->LTFIMP_NY
CLTF
2.271
LAGNLTFEXP_LAGN->PJM
CLTF
7.902
LGEELTFEXP_LGEE->PJM
CLTF
1.047
WECLTFEXP_WEC->PJM
CLTF
0.527
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.391
TVALTFEXP_TVA->PJM
CLTF
3.928
CPLELTFEXP_CPLE->PJM
CLTF
13.727
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.914
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.552
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.126
MECLTFEXP_MEC->PJM
CLTF
3.168
SIGELTFEXP_SIGE->PJM
CLTF
0.092

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.4 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4196.99
MW Contribution:15.93
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
237.707
3151081ELIZAR1
50/50
34.291
3151091ELIZAR2
50/50
33.696
941591AE2-156 GEN
50/50
31.284
3152611GOSPORTB
50/50
4.746
3152621GOSPORTC
50/50
4.028
3152601GOSPORTA
50/50
3.716
3150991CHESPKB
50/50
3.905
3150991CHESPKB
50/50
3.811
316185AD1-033 GEN
Solar/Wind Harmer
4.182
3142956BIRDNECK
Solar/Wind Harmer
2.122
316316AC1-027 C
Solar/Wind Harmer
1.213
3145506HICKORY
Solar/Wind Harmer
-0.157
3145506HICKORY
Solar/Wind Harmer
-0.094
957871AF2-081 GEN
Solar/Wind Harmer
19.57
319010AE1-072 C
Solar/Wind Harmer
7.873
3146406KITTY HAWK
Solar/Wind Harmer
0.032
316305AF2-043 C
Solar/Wind Harmer
1.156
313526AB2-022
Solar/Wind Harmer
1.03
316321Z2-027
Solar/Wind Harmer
1.02
3146396TANGLEW
Solar/Wind Harmer
0.696
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
3146486SUNBURY
Solar/Wind Harmer
-0.038
3146486SUNBURY
Solar/Wind Harmer
-0.038
957831AF2-077 GEN
Solar/Wind Harmer
1.124
3138283WHITEMARSH
Solar/Wind Harmer
0.058
315835AF2-110_GEN
Solar/Wind Harmer
4.597
971445AH1-216 GEN
Solar/Wind Harmer
22.605
315611Z1-036_GEN2
Solar/Wind Harmer
8.919
315976AC1-164 GENA
Solar/Wind Harmer
37.531
316169AC1-164_GENC
Solar/Wind Harmer
32.423
315975AC1-164 GENB
Solar/Wind Harmer
1.11
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
972265AH1-717 GEN
Adder
24.127
3151201GRAVEL4
Adder
22.618
3151191GRAVEL3
Adder
22.331
3151211GRAVEL5
Adder
22.331
316314AB2-024 C
Solar/Wind Harmer
2.922
316311AC2-079 GEN
Solar/Wind Harmer
17.237
315833AF1-017_GEN
Solar/Wind Harmer
6.481
316349AD2-085 GEN
Solar/Wind Harmer
3.035
316059AD1-063 C
Solar/Wind Harmer
0.77
957601AF2-054 GEN
Solar/Wind Harmer
1.014
3141873WAN 176
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.737
315662AE1-191 GEN
Solar/Wind Harmer
4.039
315666AE1-190 GEN
Solar/Wind Harmer
1.01
3141913WHIT STONE
Solar/Wind Harmer
-0.033
3138133OCRAN
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
941031AE2-094 GEN
Solar/Wind Harmer
61.265
944011AF1-069 GEN
Solar/Wind Harmer
19.196
315732AD1-074 GEN1
Solar/Wind Harmer
6.574
315733AD1-074 GEN2
Solar/Wind Harmer
6.574
315735AD1-075 GEN1
Solar/Wind Harmer
3.288
3141783LANCAST
Solar/Wind Harmer
-0.019
3141783LANCAST
Solar/Wind Harmer
-0.013
3143873LANEXA
Solar/Wind Harmer
-0.019
970673AG2-436 GEN
Solar/Wind Harmer
67.092
970673AG2-436 GEN
Solar/Wind Harmer
33.97
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.871
962981AG1-147 GEN
Solar/Wind Harmer
13.697
971967AH1-528 GEN
Solar/Wind Harmer
58.566
965291AG1-394 GEN
Solar/Wind Harmer
2.727
316369SG1_INVT
Solar/Wind Harmer
5.474
316318V4-068
Solar/Wind Harmer
0.759
3145893MURPHYS
Solar/Wind Harmer
-0.082
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145513AHOSKIE
Solar/Wind Harmer
0.262
961941AG1-037 GEN
Solar/Wind Harmer
0.225
3145513AHOSKIE
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.059
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
970085AG2-068 GEN
Solar/Wind Harmer
18.519
970581AG2-369 GEN
Solar/Wind Harmer
15.926
3142433PROV 92
Adder
0.5
3142433PROV 92
Adder
0.5
3146043SEABORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.871
316132AB2-190 GEN1
Solar/Wind Harmer
2.843
971167AH1-042 GEN
Solar/Wind Harmer
27.039
3141813NORNECK
Solar/Wind Harmer
-0.028
3146033SCOT NK
Solar/Wind Harmer
-0.11
316315AB2-025 C
Solar/Wind Harmer
0.726
315814AE2-033 C
Solar/Wind Harmer
25.055
315652AC1-086 GEN
Solar/Wind Harmer
30.26
316005AA1-067
Solar/Wind Harmer
0.544
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.53
3137643SOCKMAN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.01
316087AB2-174 GEN
Solar/Wind Harmer
3.762
946281AF1-292 GEN
Solar/Wind Harmer
0.585
957861AF2-080 GEN
Solar/Wind Harmer
11.36
316420AA1-050 GEN
Solar/Wind Harmer
2.915
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
3143316POE
Solar/Wind Harmer
-0.097
316319Z2-044 C
Solar/Wind Harmer
1.369
970831AG2-522 GEN
Solar/Wind Harmer
12.344
3145506HICKORY
Solar/Wind Harmer
-0.023
316036AC1-147 C
Solar/Wind Harmer
1.065
316339AD2-160 GEN
Solar/Wind Harmer
2.645
316018AA1-139 ULT2
Solar/Wind Harmer
3.353
316017AA1-139 ULT1
Solar/Wind Harmer
3.167
3137176SLIGO L2192
Solar/Wind Harmer
-0.154
3146456SLIGO L269
Solar/Wind Harmer
4.604
3130086AYDLETT
Solar/Wind Harmer
-0.155
3146386ELIZ CT
Solar/Wind Harmer
-0.038
316431W1029_GEN1
Solar/Wind Harmer
6.756
316433W1029_GEN2
Solar/Wind Harmer
6.756
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
316236AE1-162_GEN
Solar/Wind Harmer
1.106
3146376EDENTON
Solar/Wind Harmer
1.047
3146376EDENTON
Solar/Wind Harmer
1.047
315742AE1-103 GEN
Solar/Wind Harmer
3.571
316441AF1-014 GEN
Solar/Wind Harmer
2.239
316065AD1-022 GEN
Solar/Wind Harmer
15.998
972185AH1-677 GEN
Adder
15.764
972187AH1-678 GEN
Adder
7.876
316487AF1-042 GEN
Solar/Wind Harmer
4.046
316033AB2-134 GEN
Solar/Wind Harmer
9.88
315697AD1-025 GEN
Solar/Wind Harmer
6.197
3145893MURPHYS
Solar/Wind Harmer
0.849
3145893MURPHYS
Solar/Wind Harmer
-0.055
970657AG2-426 GEN
Solar/Wind Harmer
9.485
970657AG2-426 GEN
Solar/Wind Harmer
1.983
3146173TUNIS
Solar/Wind Harmer
-0.03
3146173TUNIS
Solar/Wind Harmer
-0.03
970933AG2-581 GEN
Solar/Wind Harmer
27.977
958261AF2-120 GEN
Solar/Wind Harmer
11.534
3142946ENON
Solar/Wind Harmer
-0.003
316077AC2-138 C
Solar/Wind Harmer
0.592
3150341NORNECKC1
Adder
2.615
3150341NORNECKC1
Adder
2.594
316075AC2-137 C
Solar/Wind Harmer
0.755
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.028
316426AA2-053 GEN
Solar/Wind Harmer
2.773
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
-0.027
966811AG1-552 GEN
Solar/Wind Harmer
3.029
3145593CAROLNA
Solar/Wind Harmer
0.224
3144356SAPONY
Solar/Wind Harmer
0.939
3145783HORNRTN
Solar/Wind Harmer
3.182
3145783HORNRTN
Solar/Wind Harmer
2.546
3145783HORNRTN
Solar/Wind Harmer
0.795
3145783HORNRTN
Solar/Wind Harmer
0.318
970099AG2-077 GEN
Solar/Wind Harmer
33.208
3145796HORNRTN
Solar/Wind Harmer
-0.079
316181AB2-040 GEN
Solar/Wind Harmer
3.695
316274AC1-208 GEN
Solar/Wind Harmer
2.83
3145493TOT1
Solar/Wind Harmer
0.389
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
961601AG1-000A GEN
Solar/Wind Harmer
9.511
316263AC1-034 GEN
Solar/Wind Harmer
11.337
944641AF1-129 GEN
Adder
84.194
3144293JTRSVLE
Adder
0.515
3144293JTRSVLE
Adder
0.433
3150691DARBY 3
Adder
10.512
3150701DARBY 4
Adder
10.488
3150681DARBY 2
Adder
10.476
3150671DARBY 1
Adder
10.463
3142366NRTHEST
Adder
0.386
939181AE1-148 GEN
Solar/Wind Harmer
9.973
3152331SURRY 2
50/50
17.338
971353AH1-157 GEN
50/50
31.804
970017AG2-010 GEN
50/50
24.098
3150981CHESPKA
50/50
4.655
316294AC1-161 GEN
Solar/Wind Harmer
14.03
944591AF1-124 GEN
Solar/Wind Harmer
184.294
971317AH1-138 GEN
Solar/Wind Harmer
5.043
3138126ROCKLANDING
Solar/Wind Harmer
0.123
316159AE1-175 C
Solar/Wind Harmer
1.062
316375AC2-012 GEN
Solar/Wind Harmer
13.661
316388AE2-253 GEN
Solar/Wind Harmer
2.645
3146456SLIGO L269
Solar/Wind Harmer
-0.039
316246AF1-032 C
Solar/Wind Harmer
0.776
316072AD1-144
Solar/Wind Harmer
0.769
3146516WINFALL
Solar/Wind Harmer
-0.12
3146516WINFALL
Solar/Wind Harmer
-0.037
939411AE1-173 GEN
Solar/Wind Harmer
184.193
316093AE2-104_GEN
Solar/Wind Harmer
10.693
3145336SMITFLD
Solar/Wind Harmer
-0.146
315800Z1-036_GEN1
Solar/Wind Harmer
8.919
940641AE2-051 GEN
Solar/Wind Harmer
33.616
3130156CHOWAN
Solar/Wind Harmer
-0.035
3151171GRAVELC
Adder
3.305
3141766HARMONY
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.716
961611AG1-000B GEN
Solar/Wind Harmer
16.413
971777AH1-397 GEN
Solar/Wind Harmer
3.905
3141843SHACKLE
Adder
1.51
3138133OCRAN
Solar/Wind Harmer
-0.019
971647AH1-324 GEN
Solar/Wind Harmer
15.969
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.926
970661AG2-428 GEN
Solar/Wind Harmer
33.058
961951AG1-038 GEN
Solar/Wind Harmer
4.046
3145893MURPHYS
Solar/Wind Harmer
-0.121
3145893MURPHYS
Solar/Wind Harmer
0.903
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
962861AG1-135 GEN
Solar/Wind Harmer
11.256
316381AD1-082 GEN
Solar/Wind Harmer
2.741
3145683EARLEYS
Solar/Wind Harmer
-0.03
970919AG2-571 GEN
Solar/Wind Harmer
9.422
970087AG2-069 GEN
Solar/Wind Harmer
27.779
971069AG2-661 GEN
Solar/Wind Harmer
4.683
316174AB2-169 GEN
Solar/Wind Harmer
4.564
970659AG2-427 GEN
Solar/Wind Harmer
15.655
3146263WOODLND
Solar/Wind Harmer
-0.029
3142433PROV 92
Solar/Wind Harmer
-0.115
3142433PROV 92
Adder
0.5
3142433PROV 92
Adder
0.5
964211AG1-282 GEN
Solar/Wind Harmer
0.866
3141726DUNNSVL
Solar/Wind Harmer
-0.115
3145823KELFORD
Solar/Wind Harmer
-0.029
316458AB2-190 GEN2
Solar/Wind Harmer
2.843
3150351NORNECKC2
Adder
2.489
3146293MARTNCO
Solar/Wind Harmer
0.173
970129AG2-093 GEN
Solar/Wind Harmer
6.352
316190AA2-174 GEN
Solar/Wind Harmer
0.337
316011AB1-132 GEN
Solar/Wind Harmer
5.628
962571AG1-106 GEN
Solar/Wind Harmer
3.867
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145783HORNRTN
Solar/Wind Harmer
-0.027
316212AC1-099_GEN
Solar/Wind Harmer
2.334
316023GEN1_S
Solar/Wind Harmer
1.805
957481AF2-042 GEN
Solar/Wind Harmer
83.021
3145796HORNRTN
Solar/Wind Harmer
-0.087
3145796HORNRTN
Solar/Wind Harmer
-0.026
960081AF2-299 GEN
Solar/Wind Harmer
2.936
316494AC1-189 GEN
Solar/Wind Harmer
2.794
944631AF1-128 GEN
Adder
110.065
316337AD2-073 GEN
Solar/Wind Harmer
0.68
315722AD1-056 GEN
Solar/Wind Harmer
2.637
961671AG1-007 GEN
Solar/Wind Harmer
0.318
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.747
971795AH1-408 GEN
Solar/Wind Harmer
18.866
315693AD1-088 GEN
Solar/Wind Harmer
12.441
3146233WITAKRS
Solar/Wind Harmer
-0.098
3147043LAWRENC
Adder
1.991
962491AG1-098 GEN
Solar/Wind Harmer
16.431
316129AC1-054 GEN
Solar/Wind Harmer
2.144
971065AG2-659 GEN
Solar/Wind Harmer
12.115
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.261
316049AB1-081 GEN
Solar/Wind Harmer
2.609
3142053HEARTS
Solar/Wind Harmer
0.284
315687AD1-152 GEN
Solar/Wind Harmer
2.829
3143096IRON208
Adder
0.712
3144293JTRSVLE
Adder
0.515
3150921YORKTN3
50/50
9.632
3144216WINCHST
50/50
1.422
3151101ELIZAR3
50/50
34.73
3151161SURRY 1
50/50
11.936
315773AC2-141 GEN
Solar/Wind Harmer
18.146
944581AF1-123 GEN
Solar/Wind Harmer
183.632
944601AF1-125 GEN
Solar/Wind Harmer
180.766
316382AG1-145 C
Solar/Wind Harmer
1.192
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.039
971153AH1-033 GEN
Solar/Wind Harmer
4.752
3144536CHRHLND
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
2.237
316435W1029_GEN3
Solar/Wind Harmer
6.756
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3145336SMITFLD
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.035
3145273HOLLAND
Solar/Wind Harmer
-0.026
3151221GRAVEL6
Adder
22.592
3151171GRAVELC
Adder
4.347
3141766HARMONY
Solar/Wind Harmer
3.033
316156AD2-030 GEN
Solar/Wind Harmer
0.905
3141873WAN 176
Solar/Wind Harmer
4.024
315614AA2-178 GEN
Solar/Wind Harmer
3.65
316280AD1-041 GEN
Solar/Wind Harmer
2.524
961611AG1-000B GEN
Solar/Wind Harmer
7.003
316203AE2-005 GEN
Solar/Wind Harmer
14.004
3141843SHACKLE
Adder
1.51
971157AH1-035 GEN
Solar/Wind Harmer
4.089
315737AD1-076 GEN
Solar/Wind Harmer
6.178
3146206CASHIE
Solar/Wind Harmer
-0.032
962971AG1-146 GEN
Solar/Wind Harmer
5.87
970661AG2-428 GEN
Solar/Wind Harmer
5.858
3156081AA2-088 GEN
Solar/Wind Harmer
10.064
316484AD2-074 GEN
Solar/Wind Harmer
7.733
970009AG2-005 GEN
Solar/Wind Harmer
3.84
3156021HOLLOMANSOL
Solar/Wind Harmer
4.118
3145893MURPHYS
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
-0.03
957521AF2-046 GEN
Solar/Wind Harmer
23.907
961681AG1-008 GEN
Solar/Wind Harmer
23.907
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
316463AE2-346 GEN
Solar/Wind Harmer
0.486
316140AB2-099
Solar/Wind Harmer
0.202
962331AG1-082 GEN
Solar/Wind Harmer
3.749
316083AB2-161 GEN
Solar/Wind Harmer
4.852
970917AG2-570 GEN
Solar/Wind Harmer
74.436
316404AE1-155 C
Solar/Wind Harmer
5.742
315778AD1-151 GEN
Solar/Wind Harmer
25.642
970659AG2-427 GEN
Solar/Wind Harmer
2.774
3146263WOODLND
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.5
3142433PROV 92
Adder
0.5
3142946ENON
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
1.356
3145823KELFORD
Solar/Wind Harmer
-0.029
3150351NORNECKC2
Adder
2.531
3145933PARMELE
Solar/Wind Harmer
-0.028
966801AG1-551 GEN
Solar/Wind Harmer
3.485
970129AG2-093 GEN
Solar/Wind Harmer
15.682
3142666NORTHAMPTON
Solar/Wind Harmer
-0.027
315813AE1-149 C
Solar/Wind Harmer
17.008
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
316210AC1-098 GEN
Solar/Wind Harmer
4.202
316365GEN2_N
Solar/Wind Harmer
1.805
3145796HORNRTN
Solar/Wind Harmer
-0.105
3145796HORNRTN
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.129
966621AG1-532 GEN
Solar/Wind Harmer
0.53
970133AG2-095 GEN
Solar/Wind Harmer
2.858
316327AA2-057 GEN
Solar/Wind Harmer
2.561
315724AD1-057 GEN
Solar/Wind Harmer
1.45
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
316478AD1-087 GEN
Solar/Wind Harmer
2.178
316486AD2-202 GEN
Solar/Wind Harmer
0.638
3146233WITAKRS
Solar/Wind Harmer
0.519
3146233WITAKRS
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.016
961601AG1-000A GEN
Solar/Wind Harmer
9.632
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3143096IRON208
Adder
0.712
3143096IRON208
Adder
0.698
3144293JTRSVLE
Adder
0.515
NYPJM->LTFIMP_NY
CLTF
2.097
LAGNLTFEXP_LAGN->PJM
CLTF
7.39
LGEELTFEXP_LGEE->PJM
CLTF
0.951
WECLTFEXP_WEC->PJM
CLTF
0.479
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.879
TVALTFEXP_TVA->PJM
CLTF
3.669
CPLELTFEXP_CPLE->PJM
CLTF
13.033
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.174
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.233
MECLTFEXP_MEC->PJM
CLTF
2.913
SIGELTFEXP_SIGE->PJM
CLTF
0.084

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.49 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4164.05
MW Contribution:15.09
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
238.367
3151081ELIZAR1
50/50
34.238
3151091ELIZAR2
50/50
33.644
941591AE2-156 GEN
50/50
31.249
3152611GOSPORTB
50/50
4.742
3152621GOSPORTC
50/50
4.024
3152601GOSPORTA
50/50
3.712
957871AF2-081 GEN
Solar/Wind Harmer
19.512
319010AE1-072 C
Solar/Wind Harmer
7.851
3146406KITTY HAWK
Solar/Wind Harmer
0.032
957831AF2-077 GEN
Solar/Wind Harmer
1.164
3138283WHITEMARSH
Solar/Wind Harmer
0.06
316305AF2-043 C
Solar/Wind Harmer
1.155
3150991CHESPKB
50/50
3.902
3150991CHESPKB
50/50
3.808
316185AD1-033 GEN
Solar/Wind Harmer
4.169
3142956BIRDNECK
Solar/Wind Harmer
2.118
316316AC1-027 C
Solar/Wind Harmer
1.211
316036AC1-147 C
Solar/Wind Harmer
1.064
3145506HICKORY
Solar/Wind Harmer
-0.157
3145506HICKORY
Solar/Wind Harmer
-0.094
3145506HICKORY
Solar/Wind Harmer
-0.023
316339AD2-160 GEN
Solar/Wind Harmer
2.637
316018AA1-139 ULT2
Solar/Wind Harmer
3.343
316017AA1-139 ULT1
Solar/Wind Harmer
3.158
3137176SLIGO L2192
Solar/Wind Harmer
-0.154
3146456SLIGO L269
Solar/Wind Harmer
4.591
3130086AYDLETT
Solar/Wind Harmer
-0.154
3146386ELIZ CT
Solar/Wind Harmer
-0.038
316236AE1-162_GEN
Solar/Wind Harmer
1.128
316431W1029_GEN1
Solar/Wind Harmer
6.749
316433W1029_GEN2
Solar/Wind Harmer
6.749
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146376EDENTON
Solar/Wind Harmer
1.047
3146376EDENTON
Solar/Wind Harmer
1.047
316441AF1-014 GEN
Solar/Wind Harmer
2.377
315742AE1-103 GEN
Solar/Wind Harmer
3.594
316033AB2-134 GEN
Solar/Wind Harmer
10.549
315697AD1-025 GEN
Solar/Wind Harmer
6.616
316487AF1-042 GEN
Solar/Wind Harmer
4.283
3142946ENON
Solar/Wind Harmer
-0.003
315976AC1-164 GENA
Solar/Wind Harmer
40.333
316169AC1-164_GENC
Solar/Wind Harmer
34.844
315975AC1-164 GENB
Solar/Wind Harmer
1.193
313526AB2-022
Solar/Wind Harmer
1.027
316321Z2-027
Solar/Wind Harmer
1.018
3146396TANGLEW
Solar/Wind Harmer
0.694
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
3146486SUNBURY
Solar/Wind Harmer
-0.038
3146486SUNBURY
Solar/Wind Harmer
-0.038
971445AH1-216 GEN
Solar/Wind Harmer
23.079
315835AF2-110_GEN
Solar/Wind Harmer
4.623
316314AB2-024 C
Solar/Wind Harmer
3.099
972265AH1-717 GEN
Adder
24.956
3151201GRAVEL4
Adder
23.394
3151191GRAVEL3
Adder
23.098
3151211GRAVEL5
Adder
23.098
315611Z1-036_GEN2
Solar/Wind Harmer
8.913
316059AD1-063 C
Solar/Wind Harmer
0.815
957601AF2-054 GEN
Solar/Wind Harmer
1.069
3141873WAN 176
Solar/Wind Harmer
-0.007
315662AE1-191 GEN
Solar/Wind Harmer
4.275
315666AE1-190 GEN
Solar/Wind Harmer
1.069
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
316311AC2-079 GEN
Solar/Wind Harmer
17.624
315833AF1-017_GEN
Solar/Wind Harmer
6.629
316349AD2-085 GEN
Solar/Wind Harmer
3.104
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.014
315816AE2-034 GEN
Solar/Wind Harmer
2.739
962981AG1-147 GEN
Solar/Wind Harmer
14.486
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.845
315732AD1-074 GEN1
Solar/Wind Harmer
6.582
315733AD1-074 GEN2
Solar/Wind Harmer
6.582
315735AD1-075 GEN1
Solar/Wind Harmer
3.292
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.904
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
971167AH1-042 GEN
Solar/Wind Harmer
29.852
965291AG1-394 GEN
Solar/Wind Harmer
2.749
941031AE2-094 GEN
Solar/Wind Harmer
57.693
944011AF1-069 GEN
Solar/Wind Harmer
18.077
316132AB2-190 GEN1
Solar/Wind Harmer
3.105
316318V4-068
Solar/Wind Harmer
0.764
3145893MURPHYS
Solar/Wind Harmer
-0.082
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.263
961941AG1-037 GEN
Solar/Wind Harmer
0.227
3145513AHOSKIE
Solar/Wind Harmer
-0.03
970673AG2-436 GEN
Solar/Wind Harmer
63.289
970673AG2-436 GEN
Solar/Wind Harmer
32.045
3145683EARLEYS
Solar/Wind Harmer
-0.06
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3141813NORNECK
Solar/Wind Harmer
-0.03
971967AH1-528 GEN
Solar/Wind Harmer
55.45
3146043SEABORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.901
316315AB2-025 C
Solar/Wind Harmer
0.771
316065AD1-022 GEN
Solar/Wind Harmer
16.03
970657AG2-426 GEN
Solar/Wind Harmer
9.983
970657AG2-426 GEN
Solar/Wind Harmer
2.088
958261AF2-120 GEN
Solar/Wind Harmer
12.227
316075AC2-137 C
Solar/Wind Harmer
0.84
3145893MURPHYS
Solar/Wind Harmer
0.855
3145893MURPHYS
Solar/Wind Harmer
-0.055
3146173TUNIS
Solar/Wind Harmer
-0.03
3146173TUNIS
Solar/Wind Harmer
-0.03
316077AC2-138 C
Solar/Wind Harmer
0.629
3150341NORNECKC1
Adder
2.78
3150341NORNECKC1
Adder
2.758
972185AH1-677 GEN
Adder
14.884
972187AH1-678 GEN
Adder
7.445
3144356SAPONY
Solar/Wind Harmer
0.997
970933AG2-581 GEN
Solar/Wind Harmer
26.639
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
2.802
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
-0.027
966811AG1-552 GEN
Solar/Wind Harmer
3.065
3145593CAROLNA
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
3.217
3145783HORNRTN
Solar/Wind Harmer
2.574
3145783HORNRTN
Solar/Wind Harmer
0.804
3145783HORNRTN
Solar/Wind Harmer
0.322
316181AB2-040 GEN
Solar/Wind Harmer
3.768
3145796HORNRTN
Solar/Wind Harmer
-0.08
316274AC1-208 GEN
Solar/Wind Harmer
2.848
970099AG2-077 GEN
Solar/Wind Harmer
32.116
3145493TOT1
Solar/Wind Harmer
0.389
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
961601AG1-000A GEN
Solar/Wind Harmer
9.514
316263AC1-034 GEN
Solar/Wind Harmer
11.336
944641AF1-129 GEN
Adder
100.04
3150691DARBY 3
Adder
13.253
3150701DARBY 4
Adder
13.222
3150681DARBY 2
Adder
13.207
3150671DARBY 1
Adder
13.192
3144293JTRSVLE
Adder
0.547
3144293JTRSVLE
Adder
0.461
3142366NRTHEST
Adder
0.519
315814AE2-033 C
Solar/Wind Harmer
26.581
970085AG2-068 GEN
Solar/Wind Harmer
17.548
970581AG2-369 GEN
Solar/Wind Harmer
15.091
3146033SCOT NK
Solar/Wind Harmer
-0.111
3143316POE
Solar/Wind Harmer
-0.108
315652AC1-086 GEN
Solar/Wind Harmer
30.808
3137643SOCKMAN
Solar/Wind Harmer
-0.108
316087AB2-174 GEN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
-0.086
3145796HORNRTN
Solar/Wind Harmer
-0.011
316005AA1-067
Solar/Wind Harmer
0.544
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.527
946281AF1-292 GEN
Solar/Wind Harmer
0.6
957861AF2-080 GEN
Solar/Wind Harmer
11.356
316420AA1-050 GEN
Solar/Wind Harmer
2.914
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
316319Z2-044 C
Solar/Wind Harmer
1.371
970831AG2-522 GEN
Solar/Wind Harmer
12.399
971285AH1-108 GEN
Adder
1.342
3152331SURRY 2
50/50
17.34
971353AH1-157 GEN
50/50
32.65
970017AG2-010 GEN
50/50
24.599
3150981CHESPKA
50/50
4.651
316294AC1-161 GEN
Solar/Wind Harmer
13.89
971317AH1-138 GEN
Solar/Wind Harmer
5.173
3138126ROCKLANDING
Solar/Wind Harmer
0.126
316159AE1-175 C
Solar/Wind Harmer
1.1
944591AF1-124 GEN
Solar/Wind Harmer
183.228
316375AC2-012 GEN
Solar/Wind Harmer
13.649
316388AE2-253 GEN
Solar/Wind Harmer
2.637
3146456SLIGO L269
Solar/Wind Harmer
-0.039
316246AF1-032 C
Solar/Wind Harmer
0.775
316072AD1-144
Solar/Wind Harmer
0.774
3145336SMITFLD
Solar/Wind Harmer
-0.149
3146516WINFALL
Solar/Wind Harmer
-0.119
3146516WINFALL
Solar/Wind Harmer
-0.037
316093AE2-104_GEN
Solar/Wind Harmer
10.753
3151171GRAVELC
Adder
3.419
315800Z1-036_GEN1
Solar/Wind Harmer
8.913
3141766HARMONY
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
177.294
3130156CHOWAN
Solar/Wind Harmer
-0.035
971777AH1-397 GEN
Solar/Wind Harmer
4.145
3141843SHACKLE
Adder
1.603
961611AG1-000B GEN
Solar/Wind Harmer
17.172
3138133OCRAN
Solar/Wind Harmer
-0.021
940641AE2-051 GEN
Solar/Wind Harmer
31.938
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.733
971647AH1-324 GEN
Solar/Wind Harmer
16.873
970661AG2-428 GEN
Solar/Wind Harmer
34.577
961951AG1-038 GEN
Solar/Wind Harmer
4.283
971069AG2-661 GEN
Solar/Wind Harmer
5.045
962861AG1-135 GEN
Solar/Wind Harmer
11.928
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.945
3142433PROV 92
Solar/Wind Harmer
-0.126
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316381AD1-082 GEN
Solar/Wind Harmer
2.897
970659AG2-427 GEN
Solar/Wind Harmer
16.604
316458AB2-190 GEN2
Solar/Wind Harmer
3.105
3145893MURPHYS
Solar/Wind Harmer
-0.122
3145893MURPHYS
Solar/Wind Harmer
0.91
964211AG1-282 GEN
Solar/Wind Harmer
0.921
3141726DUNNSVL
Solar/Wind Harmer
-0.122
970129AG2-093 GEN
Solar/Wind Harmer
6.955
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3150351NORNECKC2
Adder
2.646
944631AF1-128 GEN
Adder
125.671
316174AB2-169 GEN
Solar/Wind Harmer
4.565
3146263WOODLND
Solar/Wind Harmer
-0.029
3145823KELFORD
Solar/Wind Harmer
-0.029
970919AG2-571 GEN
Solar/Wind Harmer
8.926
970087AG2-069 GEN
Solar/Wind Harmer
26.321
3146293MARTNCO
Solar/Wind Harmer
0.173
316190AA2-174 GEN
Solar/Wind Harmer
0.341
316023GEN1_S
Solar/Wind Harmer
1.866
316011AB1-132 GEN
Solar/Wind Harmer
5.73
962571AG1-106 GEN
Solar/Wind Harmer
3.937
3145783HORNRTN
Solar/Wind Harmer
-0.027
316337AD2-073 GEN
Solar/Wind Harmer
0.725
316212AC1-099_GEN
Solar/Wind Harmer
2.347
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
960081AF2-299 GEN
Solar/Wind Harmer
3.016
316494AC1-189 GEN
Solar/Wind Harmer
2.793
971795AH1-408 GEN
Solar/Wind Harmer
19.333
957481AF2-042 GEN
Solar/Wind Harmer
80.29
315671AE2-027_GEN
Solar/Wind Harmer
19.173
3150921YORKTN3
50/50
9.838
3144216WINCHST
50/50
1.454
3151101ELIZAR3
50/50
34.676
3151161SURRY 1
50/50
12.346
315773AC2-141 GEN
Solar/Wind Harmer
17.965
316382AG1-145 C
Solar/Wind Harmer
1.235
944581AF1-123 GEN
Solar/Wind Harmer
182.571
944601AF1-125 GEN
Solar/Wind Harmer
179.721
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144536CHRHLND
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.039
971153AH1-033 GEN
Solar/Wind Harmer
4.739
316320Y1-086
Solar/Wind Harmer
2.232
3145336SMITFLD
Solar/Wind Harmer
-0.015
316435W1029_GEN3
Solar/Wind Harmer
6.749
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3151221GRAVEL6
Adder
23.367
3151171GRAVELC
Adder
4.496
3141766HARMONY
Solar/Wind Harmer
3.21
316156AD2-030 GEN
Solar/Wind Harmer
0.954
3141873WAN 176
Solar/Wind Harmer
4.242
316280AD1-041 GEN
Solar/Wind Harmer
2.672
3146376EDENTON
Solar/Wind Harmer
-0.035
316203AE2-005 GEN
Solar/Wind Harmer
14.866
3141843SHACKLE
Adder
1.603
3145273HOLLAND
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
7.327
315614AA2-178 GEN
Solar/Wind Harmer
3.652
962971AG1-146 GEN
Solar/Wind Harmer
6.208
971157AH1-035 GEN
Solar/Wind Harmer
4.094
315737AD1-076 GEN
Solar/Wind Harmer
6.186
970661AG2-428 GEN
Solar/Wind Harmer
6.128
316484AD2-074 GEN
Solar/Wind Harmer
8.186
970009AG2-005 GEN
Solar/Wind Harmer
4.065
3142946ENON
Solar/Wind Harmer
-0.011
315778AD1-151 GEN
Solar/Wind Harmer
27.623
3146206CASHIE
Solar/Wind Harmer
-0.032
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316083AB2-161 GEN
Solar/Wind Harmer
5.126
316404AE1-155 C
Solar/Wind Harmer
6.087
970659AG2-427 GEN
Solar/Wind Harmer
2.942
3156081AA2-088 GEN
Solar/Wind Harmer
10.144
3156021HOLLOMANSOL
Solar/Wind Harmer
4.135
3145893MURPHYS
Solar/Wind Harmer
0.214
3145893MURPHYS
Solar/Wind Harmer
-0.031
957521AF2-046 GEN
Solar/Wind Harmer
24.072
961681AG1-008 GEN
Solar/Wind Harmer
24.072
970129AG2-093 GEN
Solar/Wind Harmer
17.171
3146173TUNIS
Solar/Wind Harmer
-0.03
316463AE2-346 GEN
Solar/Wind Harmer
0.488
316140AB2-099
Solar/Wind Harmer
0.203
962331AG1-082 GEN
Solar/Wind Harmer
3.771
3145963POPLR C
Solar/Wind Harmer
-0.03
3150351NORNECKC2
Adder
2.691
315813AE1-149 C
Solar/Wind Harmer
18.428
3146263WOODLND
Solar/Wind Harmer
-0.029
316317KELFORD C
Solar/Wind Harmer
1.363
3145823KELFORD
Solar/Wind Harmer
-0.029
970133AG2-095 GEN
Solar/Wind Harmer
3.212
970917AG2-570 GEN
Solar/Wind Harmer
70.514
3145933PARMELE
Solar/Wind Harmer
-0.028
966801AG1-551 GEN
Solar/Wind Harmer
3.484
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
316365GEN2_N
Solar/Wind Harmer
1.866
313506AB2-031 GEN
Solar/Wind Harmer
2.171
316210AC1-098 GEN
Solar/Wind Harmer
4.224
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
966621AG1-532 GEN
Solar/Wind Harmer
0.544
965281AG1-393 GEN
Solar/Wind Harmer
3.227
970293AG2-193 GEN
Solar/Wind Harmer
3.211
316327AA2-057 GEN
Solar/Wind Harmer
2.569
315724AD1-057 GEN
Solar/Wind Harmer
1.461
3147043LAWRENC
Solar/Wind Harmer
-0.015
315839AE2-212 C
Solar/Wind Harmer
0.759
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
3146233WITAKRS
Solar/Wind Harmer
0.519
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
316478AD1-087 GEN
Solar/Wind Harmer
2.118
316486AD2-202 GEN
Solar/Wind Harmer
0.62
961601AG1-000A GEN
Solar/Wind Harmer
9.635
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3143096IRON208
Adder
0.897
3143096IRON208
Adder
0.879
3150861SPRUNCD
Adder
0.82
3144293JTRSVLE
Adder
0.547
315722AD1-056 GEN
Solar/Wind Harmer
2.657
3147043LAWRENC
Adder
2.037
961671AG1-007 GEN
Solar/Wind Harmer
0.318
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.747
3146233WITAKRS
Solar/Wind Harmer
-0.098
316129AC1-054 GEN
Solar/Wind Harmer
2.151
315693AD1-088 GEN
Solar/Wind Harmer
12.207
971065AG2-659 GEN
Solar/Wind Harmer
12.147
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.261
316049AB1-081 GEN
Solar/Wind Harmer
2.609
3142053HEARTS
Solar/Wind Harmer
0.284
3143096IRON208
Adder
0.897
3150851SPRUNCC
Adder
0.82
3144293JTRSVLE
Adder
0.547
962491AG1-098 GEN
Solar/Wind Harmer
4.731
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
0.953
LAGNLTFEXP_LAGN->PJM
CLTF
7.29
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.328
WECLTFEXP_WEC->PJM
CLTF
0.478
TVALTFEXP_TVA->PJM
CLTF
3.625
CPLELTFEXP_CPLE->PJM
CLTF
12.75
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.099
MECLTFEXP_MEC->PJM
CLTF
2.893
SIGELTFEXP_SIGE->PJM
CLTF
0.084

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.49 %
Rating:3637.0 MVA
Rating Type:C
MVA to Mitigate:4164.05
MW Contribution:15.09
Bus #Bus NameTypeMW Contribution
3150921YORKTN3
50/50
9.838
3144216WINCHST
50/50
1.454
3151101ELIZAR3
50/50
34.676
3151161SURRY 1
50/50
12.346
315773AC2-141 GEN
Solar/Wind Harmer
17.965
316382AG1-145 C
Solar/Wind Harmer
1.235
944581AF1-123 GEN
Solar/Wind Harmer
182.571
944601AF1-125 GEN
Solar/Wind Harmer
179.721
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144536CHRHLND
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.039
971153AH1-033 GEN
Solar/Wind Harmer
4.739
316320Y1-086
Solar/Wind Harmer
2.232
3145336SMITFLD
Solar/Wind Harmer
-0.015
316435W1029_GEN3
Solar/Wind Harmer
6.749
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3151221GRAVEL6
Adder
23.367
3151171GRAVELC
Adder
4.496
3141766HARMONY
Solar/Wind Harmer
3.21
316156AD2-030 GEN
Solar/Wind Harmer
0.954
3141873WAN 176
Solar/Wind Harmer
4.242
316280AD1-041 GEN
Solar/Wind Harmer
2.672
3146376EDENTON
Solar/Wind Harmer
-0.035
316203AE2-005 GEN
Solar/Wind Harmer
14.866
3141843SHACKLE
Adder
1.603
3145273HOLLAND
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
7.327
315614AA2-178 GEN
Solar/Wind Harmer
3.652
962971AG1-146 GEN
Solar/Wind Harmer
6.208
971157AH1-035 GEN
Solar/Wind Harmer
4.094
315737AD1-076 GEN
Solar/Wind Harmer
6.186
970661AG2-428 GEN
Solar/Wind Harmer
6.128
316484AD2-074 GEN
Solar/Wind Harmer
8.186
970009AG2-005 GEN
Solar/Wind Harmer
4.065
3142946ENON
Solar/Wind Harmer
-0.011
315778AD1-151 GEN
Solar/Wind Harmer
27.623
3146206CASHIE
Solar/Wind Harmer
-0.032
3142433PROV 92
Adder
0.549
972263AH1-716 GEN
50/50
238.367
3151081ELIZAR1
50/50
34.238
3151091ELIZAR2
50/50
33.644
941591AE2-156 GEN
50/50
31.249
3152611GOSPORTB
50/50
4.742
3152621GOSPORTC
50/50
4.024
3152601GOSPORTA
50/50
3.712
957871AF2-081 GEN
Solar/Wind Harmer
19.512
319010AE1-072 C
Solar/Wind Harmer
7.851
3146406KITTY HAWK
Solar/Wind Harmer
0.032
957831AF2-077 GEN
Solar/Wind Harmer
1.164
3138283WHITEMARSH
Solar/Wind Harmer
0.06
316305AF2-043 C
Solar/Wind Harmer
1.155
315976AC1-164 GENA
Solar/Wind Harmer
40.333
316169AC1-164_GENC
Solar/Wind Harmer
34.844
315975AC1-164 GENB
Solar/Wind Harmer
1.193
313526AB2-022
Solar/Wind Harmer
1.027
316321Z2-027
Solar/Wind Harmer
1.018
3146396TANGLEW
Solar/Wind Harmer
0.694
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
3146486SUNBURY
Solar/Wind Harmer
-0.038
3146486SUNBURY
Solar/Wind Harmer
-0.038
971445AH1-216 GEN
Solar/Wind Harmer
23.079
315835AF2-110_GEN
Solar/Wind Harmer
4.623
316314AB2-024 C
Solar/Wind Harmer
3.099
972265AH1-717 GEN
Adder
24.956
3151201GRAVEL4
Adder
23.394
3151191GRAVEL3
Adder
23.098
3151211GRAVEL5
Adder
23.098
315611Z1-036_GEN2
Solar/Wind Harmer
8.913
316059AD1-063 C
Solar/Wind Harmer
0.815
957601AF2-054 GEN
Solar/Wind Harmer
1.069
3141873WAN 176
Solar/Wind Harmer
-0.007
315662AE1-191 GEN
Solar/Wind Harmer
4.275
315666AE1-190 GEN
Solar/Wind Harmer
1.069
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
316311AC2-079 GEN
Solar/Wind Harmer
17.624
315833AF1-017_GEN
Solar/Wind Harmer
6.629
316349AD2-085 GEN
Solar/Wind Harmer
3.104
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.01
3143873LANEXA
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.014
315816AE2-034 GEN
Solar/Wind Harmer
2.739
962981AG1-147 GEN
Solar/Wind Harmer
14.486
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.845
315732AD1-074 GEN1
Solar/Wind Harmer
6.582
315733AD1-074 GEN2
Solar/Wind Harmer
6.582
315735AD1-075 GEN1
Solar/Wind Harmer
3.292
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.904
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
971167AH1-042 GEN
Solar/Wind Harmer
29.852
965291AG1-394 GEN
Solar/Wind Harmer
2.749
941031AE2-094 GEN
Solar/Wind Harmer
57.693
944011AF1-069 GEN
Solar/Wind Harmer
18.077
316132AB2-190 GEN1
Solar/Wind Harmer
3.105
316318V4-068
Solar/Wind Harmer
0.764
3145893MURPHYS
Solar/Wind Harmer
-0.082
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.263
961941AG1-037 GEN
Solar/Wind Harmer
0.227
3145513AHOSKIE
Solar/Wind Harmer
-0.03
970673AG2-436 GEN
Solar/Wind Harmer
63.289
970673AG2-436 GEN
Solar/Wind Harmer
32.045
3145683EARLEYS
Solar/Wind Harmer
-0.06
3152331SURRY 2
50/50
17.34
971353AH1-157 GEN
50/50
32.65
970017AG2-010 GEN
50/50
24.599
3150981CHESPKA
50/50
4.651
316294AC1-161 GEN
Solar/Wind Harmer
13.89
971317AH1-138 GEN
Solar/Wind Harmer
5.173
3138126ROCKLANDING
Solar/Wind Harmer
0.126
316159AE1-175 C
Solar/Wind Harmer
1.1
944591AF1-124 GEN
Solar/Wind Harmer
183.228
316375AC2-012 GEN
Solar/Wind Harmer
13.649
316388AE2-253 GEN
Solar/Wind Harmer
2.637
3146456SLIGO L269
Solar/Wind Harmer
-0.039
316246AF1-032 C
Solar/Wind Harmer
0.775
316072AD1-144
Solar/Wind Harmer
0.774
3142433PROV 92
Adder
0.549
316083AB2-161 GEN
Solar/Wind Harmer
5.126
316404AE1-155 C
Solar/Wind Harmer
6.087
970659AG2-427 GEN
Solar/Wind Harmer
2.942
3156081AA2-088 GEN
Solar/Wind Harmer
10.144
3156021HOLLOMANSOL
Solar/Wind Harmer
4.135
3145893MURPHYS
Solar/Wind Harmer
0.214
3145893MURPHYS
Solar/Wind Harmer
-0.031
957521AF2-046 GEN
Solar/Wind Harmer
24.072
961681AG1-008 GEN
Solar/Wind Harmer
24.072
970129AG2-093 GEN
Solar/Wind Harmer
17.171
3146173TUNIS
Solar/Wind Harmer
-0.03
316463AE2-346 GEN
Solar/Wind Harmer
0.488
316140AB2-099
Solar/Wind Harmer
0.203
962331AG1-082 GEN
Solar/Wind Harmer
3.771
3145963POPLR C
Solar/Wind Harmer
-0.03
3150351NORNECKC2
Adder
2.691
315813AE1-149 C
Solar/Wind Harmer
18.428
3146263WOODLND
Solar/Wind Harmer
-0.029
316317KELFORD C
Solar/Wind Harmer
1.363
3145823KELFORD
Solar/Wind Harmer
-0.029
970133AG2-095 GEN
Solar/Wind Harmer
3.212
970917AG2-570 GEN
Solar/Wind Harmer
70.514
3145933PARMELE
Solar/Wind Harmer
-0.028
966801AG1-551 GEN
Solar/Wind Harmer
3.484
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
316365GEN2_N
Solar/Wind Harmer
1.866
313506AB2-031 GEN
Solar/Wind Harmer
2.171
316210AC1-098 GEN
Solar/Wind Harmer
4.224
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
966621AG1-532 GEN
Solar/Wind Harmer
0.544
965281AG1-393 GEN
Solar/Wind Harmer
3.227
970293AG2-193 GEN
Solar/Wind Harmer
3.211
316327AA2-057 GEN
Solar/Wind Harmer
2.569
315724AD1-057 GEN
Solar/Wind Harmer
1.461
3147043LAWRENC
Solar/Wind Harmer
-0.015
315839AE2-212 C
Solar/Wind Harmer
0.759
3146073TAR RVR
Solar/Wind Harmer
-0.025
3146083TARBORO
Solar/Wind Harmer
-0.025
3146233WITAKRS
Solar/Wind Harmer
0.519
3146233WITAKRS
Solar/Wind Harmer
-0.017
3138543CONSLDL
Solar/Wind Harmer
-0.016
316478AD1-087 GEN
Solar/Wind Harmer
2.118
316486AD2-202 GEN
Solar/Wind Harmer
0.62
961601AG1-000A GEN
Solar/Wind Harmer
9.635
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3143096IRON208
Adder
0.897
3143096IRON208
Adder
0.879
3150861SPRUNCD
Adder
0.82
3144293JTRSVLE
Adder
0.547
3150991CHESPKB
50/50
3.902
3150991CHESPKB
50/50
3.808
316185AD1-033 GEN
Solar/Wind Harmer
4.169
3142956BIRDNECK
Solar/Wind Harmer
2.118
316316AC1-027 C
Solar/Wind Harmer
1.211
316036AC1-147 C
Solar/Wind Harmer
1.064
3145506HICKORY
Solar/Wind Harmer
-0.157
3145506HICKORY
Solar/Wind Harmer
-0.094
3145506HICKORY
Solar/Wind Harmer
-0.023
316339AD2-160 GEN
Solar/Wind Harmer
2.637
316018AA1-139 ULT2
Solar/Wind Harmer
3.343
316017AA1-139 ULT1
Solar/Wind Harmer
3.158
3137176SLIGO L2192
Solar/Wind Harmer
-0.154
3146456SLIGO L269
Solar/Wind Harmer
4.591
3130086AYDLETT
Solar/Wind Harmer
-0.154
3146386ELIZ CT
Solar/Wind Harmer
-0.038
316236AE1-162_GEN
Solar/Wind Harmer
1.128
316431W1029_GEN1
Solar/Wind Harmer
6.749
316433W1029_GEN2
Solar/Wind Harmer
6.749
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146516WINFALL
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146626S HERTFORD
Solar/Wind Harmer
-0.037
3146376EDENTON
Solar/Wind Harmer
1.047
3146376EDENTON
Solar/Wind Harmer
1.047
316441AF1-014 GEN
Solar/Wind Harmer
2.377
315742AE1-103 GEN
Solar/Wind Harmer
3.594
316033AB2-134 GEN
Solar/Wind Harmer
10.549
315697AD1-025 GEN
Solar/Wind Harmer
6.616
316487AF1-042 GEN
Solar/Wind Harmer
4.283
3142946ENON
Solar/Wind Harmer
-0.003
316065AD1-022 GEN
Solar/Wind Harmer
16.03
970657AG2-426 GEN
Solar/Wind Harmer
9.983
970657AG2-426 GEN
Solar/Wind Harmer
2.088
958261AF2-120 GEN
Solar/Wind Harmer
12.227
316075AC2-137 C
Solar/Wind Harmer
0.84
3145893MURPHYS
Solar/Wind Harmer
0.855
3145893MURPHYS
Solar/Wind Harmer
-0.055
3146173TUNIS
Solar/Wind Harmer
-0.03
3146173TUNIS
Solar/Wind Harmer
-0.03
316077AC2-138 C
Solar/Wind Harmer
0.629
3150341NORNECKC1
Adder
2.78
3150341NORNECKC1
Adder
2.758
972185AH1-677 GEN
Adder
14.884
972187AH1-678 GEN
Adder
7.445
3144356SAPONY
Solar/Wind Harmer
0.997
970933AG2-581 GEN
Solar/Wind Harmer
26.639
3145933PARMELE
Solar/Wind Harmer
-0.055
3145933PARMELE
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
2.802
3145593CAROLNA
Solar/Wind Harmer
-0.027
3145593CAROLNA
Solar/Wind Harmer
-0.027
966811AG1-552 GEN
Solar/Wind Harmer
3.065
3145593CAROLNA
Solar/Wind Harmer
0.226
3145783HORNRTN
Solar/Wind Harmer
3.217
3145783HORNRTN
Solar/Wind Harmer
2.574
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3141813NORNECK
Solar/Wind Harmer
-0.03
971967AH1-528 GEN
Solar/Wind Harmer
55.45
3146043SEABORD
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.901
316315AB2-025 C
Solar/Wind Harmer
0.771
315814AE2-033 C
Solar/Wind Harmer
26.581
970085AG2-068 GEN
Solar/Wind Harmer
17.548
970581AG2-369 GEN
Solar/Wind Harmer
15.091
3146033SCOT NK
Solar/Wind Harmer
-0.111
3143316POE
Solar/Wind Harmer
-0.108
315652AC1-086 GEN
Solar/Wind Harmer
30.808
3137643SOCKMAN
Solar/Wind Harmer
-0.108
316087AB2-174 GEN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
-0.086
3145796HORNRTN
Solar/Wind Harmer
-0.011
316005AA1-067
Solar/Wind Harmer
0.544
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.527
946281AF1-292 GEN
Solar/Wind Harmer
0.6
957861AF2-080 GEN
Solar/Wind Harmer
11.356
316420AA1-050 GEN
Solar/Wind Harmer
2.914
3145573BETHELC
Solar/Wind Harmer
-0.025
3145573BETHELC
Solar/Wind Harmer
-0.025
316319Z2-044 C
Solar/Wind Harmer
1.371
970831AG2-522 GEN
Solar/Wind Harmer
12.399
971285AH1-108 GEN
Adder
1.342
3145783HORNRTN
Solar/Wind Harmer
0.804
3145783HORNRTN
Solar/Wind Harmer
0.322
316181AB2-040 GEN
Solar/Wind Harmer
3.768
3145796HORNRTN
Solar/Wind Harmer
-0.08
316274AC1-208 GEN
Solar/Wind Harmer
2.848
970099AG2-077 GEN
Solar/Wind Harmer
32.116
3145493TOT1
Solar/Wind Harmer
0.389
3145453TOT5
Solar/Wind Harmer
0.234
3145603CNETO
Solar/Wind Harmer
0.156
961601AG1-000A GEN
Solar/Wind Harmer
9.514
316263AC1-034 GEN
Solar/Wind Harmer
11.336
944641AF1-129 GEN
Adder
100.04
3150691DARBY 3
Adder
13.253
3150701DARBY 4
Adder
13.223
3150681DARBY 2
Adder
13.207
3150671DARBY 1
Adder
13.192
3144293JTRSVLE
Adder
0.547
3144293JTRSVLE
Adder
0.461
3142366NRTHEST
Adder
0.519
3145336SMITFLD
Solar/Wind Harmer
-0.149
3146516WINFALL
Solar/Wind Harmer
-0.119
3146516WINFALL
Solar/Wind Harmer
-0.037
316093AE2-104_GEN
Solar/Wind Harmer
10.753
3151171GRAVELC
Adder
3.419
315800Z1-036_GEN1
Solar/Wind Harmer
8.913
3141766HARMONY
Solar/Wind Harmer
-0.007
939411AE1-173 GEN
Solar/Wind Harmer
177.294
3130156CHOWAN
Solar/Wind Harmer
-0.035
971777AH1-397 GEN
Solar/Wind Harmer
4.145
3141843SHACKLE
Adder
1.603
961611AG1-000B GEN
Solar/Wind Harmer
17.172
3138133OCRAN
Solar/Wind Harmer
-0.021
940641AE2-051 GEN
Solar/Wind Harmer
31.938
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.733
971647AH1-324 GEN
Solar/Wind Harmer
16.873
970661AG2-428 GEN
Solar/Wind Harmer
34.577
961951AG1-038 GEN
Solar/Wind Harmer
4.283
971069AG2-661 GEN
Solar/Wind Harmer
5.045
962861AG1-135 GEN
Solar/Wind Harmer
11.928
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.945
3142433PROV 92
Solar/Wind Harmer
-0.126
3142433PROV 92
Adder
0.549
3142433PROV 92
Adder
0.549
316381AD1-082 GEN
Solar/Wind Harmer
2.897
970659AG2-427 GEN
Solar/Wind Harmer
16.604
316458AB2-190 GEN2
Solar/Wind Harmer
3.105
3145893MURPHYS
Solar/Wind Harmer
-0.122
3145893MURPHYS
Solar/Wind Harmer
0.91
964211AG1-282 GEN
Solar/Wind Harmer
0.921
3141726DUNNSVL
Solar/Wind Harmer
-0.122
970129AG2-093 GEN
Solar/Wind Harmer
6.955
3146173TUNIS
Solar/Wind Harmer
-0.03
3145963POPLR C
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.03
3150351NORNECKC2
Adder
2.646
944631AF1-128 GEN
Adder
125.671
316174AB2-169 GEN
Solar/Wind Harmer
4.565
3146263WOODLND
Solar/Wind Harmer
-0.029
3145823KELFORD
Solar/Wind Harmer
-0.029
970919AG2-571 GEN
Solar/Wind Harmer
8.926
970087AG2-069 GEN
Solar/Wind Harmer
26.321
3146293MARTNCO
Solar/Wind Harmer
0.173
316190AA2-174 GEN
Solar/Wind Harmer
0.341
316023GEN1_S
Solar/Wind Harmer
1.866
316011AB1-132 GEN
Solar/Wind Harmer
5.73
962571AG1-106 GEN
Solar/Wind Harmer
3.937
3145783HORNRTN
Solar/Wind Harmer
-0.027
316337AD2-073 GEN
Solar/Wind Harmer
0.725
316212AC1-099_GEN
Solar/Wind Harmer
2.347
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
960081AF2-299 GEN
Solar/Wind Harmer
3.016
316494AC1-189 GEN
Solar/Wind Harmer
2.793
971795AH1-408 GEN
Solar/Wind Harmer
19.333
957481AF2-042 GEN
Solar/Wind Harmer
80.29
315671AE2-027_GEN
Solar/Wind Harmer
19.173
315722AD1-056 GEN
Solar/Wind Harmer
2.657
3147043LAWRENC
Adder
2.037
961671AG1-007 GEN
Solar/Wind Harmer
0.318
3146083TARBORO
Solar/Wind Harmer
-0.025
3145493TOT1
Solar/Wind Harmer
0.747
3146233WITAKRS
Solar/Wind Harmer
-0.098
316129AC1-054 GEN
Solar/Wind Harmer
2.151
315693AD1-088 GEN
Solar/Wind Harmer
12.207
971065AG2-659 GEN
Solar/Wind Harmer
12.147
3145543BTLEBRO
Solar/Wind Harmer
-0.024
3145543BTLEBRO
Solar/Wind Harmer
-0.019
316359AB2-059 GEN
Solar/Wind Harmer
3.26
316049AB1-081 GEN
Solar/Wind Harmer
2.609
3142053HEARTS
Solar/Wind Harmer
0.284
3143096IRON208
Adder
0.897
3150851SPRUNCC
Adder
0.82
3144293JTRSVLE
Adder
0.547
962491AG1-098 GEN
Solar/Wind Harmer
4.731
NYPJM->LTFIMP_NY
CLTF
2.158
LAGNLTFEXP_LAGN->PJM
CLTF
7.29
LGEELTFEXP_LGEE->PJM
CLTF
0.953
WECLTFEXP_WEC->PJM
CLTF
0.478
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.328
TVALTFEXP_TVA->PJM
CLTF
3.625
CPLELTFEXP_CPLE->PJM
CLTF
12.75
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.786
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.099
MECLTFEXP_MEC->PJM
CLTF
2.893
SIGELTFEXP_SIGE->PJM
CLTF
0.084

Details for 8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.62 %
Rating:2442.12 MVA
Rating Type:A
MVA to Mitigate:2506.2
MW Contribution:7.98
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
204.764
3151081ELIZAR1
50/50
27.927
3151091ELIZAR2
50/50
27.442
941591AE2-156 GEN
50/50
25.486
3152611GOSPORTB
50/50
3.867
3152621GOSPORTC
50/50
3.282
3152601GOSPORTA
50/50
3.027
315759AF1-018 GEN
50/50
9.884
315976AC1-164 GENA
Solar/Wind Harmer
30.824
316169AC1-164_GENC
Solar/Wind Harmer
26.629
315975AC1-164 GENB
Solar/Wind Harmer
0.912
3138283WHITEMARSH
Solar/Wind Harmer
0.068
957871AF2-081 GEN
Solar/Wind Harmer
14.058
319010AE1-072 C
Solar/Wind Harmer
1.413
3146406KITTY HAWK
Solar/Wind Harmer
0.035
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.149
3141873WAN 176
Solar/Wind Harmer
0.055
315662AE1-191 GEN
Solar/Wind Harmer
0.009
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.05
3146396TANGLEW
Solar/Wind Harmer
0.749
3145176PASQUOTANK
Solar/Wind Harmer
0.168
3146486SUNBURY
Solar/Wind Harmer
0.271
3146486SUNBURY
Solar/Wind Harmer
0.271
971445AH1-216 GEN
Solar/Wind Harmer
19.042
970189AG2-124 GEN
Solar/Wind Harmer
8.003
3141913WHIT STONE
Solar/Wind Harmer
0.268
3138133OCRAN
Solar/Wind Harmer
0.08
315835AF2-110_GEN
Solar/Wind Harmer
1.817
3143873LANEXA
Solar/Wind Harmer
0.158
3141783LANCAST
Solar/Wind Harmer
0.158
3141783LANCAST
Solar/Wind Harmer
0.105
972265AH1-717 GEN
Adder
20.32
3151201GRAVEL4
Adder
19.048
3152331SURRY 2
50/50
14.903
971353AH1-157 GEN
50/50
28.02
970017AG2-010 GEN
50/50
20.837
3150981CHESPKA
50/50
3.793
3141843SHACKLE
50/50
1.464
316294AC1-161 GEN
Solar/Wind Harmer
5.488
971317AH1-138 GEN
Solar/Wind Harmer
2.36
316159AE1-175 C
Solar/Wind Harmer
0.271
3138126ROCKLANDING
Solar/Wind Harmer
0.142
944591AF1-124 GEN
Solar/Wind Harmer
65.888
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.887
3146456SLIGO L269
Solar/Wind Harmer
0.281
3141766HARMONY
Solar/Wind Harmer
0.056
316072AD1-144
Solar/Wind Harmer
0.1
316246AF1-032 C
Solar/Wind Harmer
0.125
3145336SMITFLD
Solar/Wind Harmer
1.085
971777AH1-397 GEN
Solar/Wind Harmer
0.713
3138133OCRAN
Solar/Wind Harmer
0.16
3146516WINFALL
Solar/Wind Harmer
0.862
3146516WINFALL
Solar/Wind Harmer
0.266
316093AE2-104_GEN
Solar/Wind Harmer
4.453
3151171GRAVELC
Adder
2.784
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.251
961611AG1-000B GEN
Solar/Wind Harmer
13.148
962861AG1-135 GEN
Solar/Wind Harmer
7.873
971647AH1-324 GEN
Solar/Wind Harmer
10.323
3145663CRESWEL
Solar/Wind Harmer
0.668
971163AH1-040 GEN
Solar/Wind Harmer
19.1
3141726DUNNSVL
Solar/Wind Harmer
0.952
939411AE1-173 GEN
Solar/Wind Harmer
101.201
3142433PROV 92
Solar/Wind Harmer
0.945
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3150351NORNECKC2
Adder
2.31
971069AG2-661 GEN
Solar/Wind Harmer
4.025
970661AG2-428 GEN
Solar/Wind Harmer
22.429
3146206CASHIE
Solar/Wind Harmer
0.221
971547AH1-271 GEN
Solar/Wind Harmer
4.718
3150921YORKTN3
50/50
8.377
3144216WINCHST
50/50
1.232
3151101ELIZAR3
50/50
28.284
315749AE2-041 GEN
50/50
9.884
3141843SHACKLE
50/50
1.464
3151161SURRY 1
50/50
10.052
315773AC2-141 GEN
Solar/Wind Harmer
11.569
316382AG1-145 C
Solar/Wind Harmer
0.003
944581AF1-123 GEN
Solar/Wind Harmer
65.654
944601AF1-125 GEN
Solar/Wind Harmer
64.643
3144873MCLAUGH
Solar/Wind Harmer
0.007
3144536CHRHLND
Solar/Wind Harmer
0.042
3146456SLIGO L269
Solar/Wind Harmer
0.281
971153AH1-033 GEN
Solar/Wind Harmer
3.25
3141766HARMONY
Solar/Wind Harmer
3.707
316320Y1-086
Solar/Wind Harmer
0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.203
3141873WAN 176
Solar/Wind Harmer
4.88
316280AD1-041 GEN
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.109
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.266
3146626S HERTFORD
Solar/Wind Harmer
0.262
3151221GRAVEL6
Adder
19.026
3151171GRAVELC
Adder
3.661
962971AG1-146 GEN
Solar/Wind Harmer
4.087
970009AG2-005 GEN
Solar/Wind Harmer
1.875
3146376EDENTON
Solar/Wind Harmer
0.251
961611AG1-000B GEN
Solar/Wind Harmer
6.685
3145273HOLLAND
Solar/Wind Harmer
0.187
316404AE1-155 C
Solar/Wind Harmer
0.055
315614AA2-178 GEN
Solar/Wind Harmer
1.366
3142946ENON
Solar/Wind Harmer
0.08
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
3150351NORNECKC2
Adder
2.349
971157AH1-035 GEN
Solar/Wind Harmer
2.754
315737AD1-076 GEN
Solar/Wind Harmer
2.931
315778AD1-151 GEN
Solar/Wind Harmer
18.115
970661AG2-428 GEN
Solar/Wind Harmer
4.77
3146206CASHIE
Solar/Wind Harmer
0.221
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
970129AG2-093 GEN
Solar/Wind Harmer
12.986
970659AG2-427 GEN
Solar/Wind Harmer
2.265
3156021HOLLOMANSOL
Solar/Wind Harmer
0.961
3145893MURPHYS
Solar/Wind Harmer
0.353
3145893MURPHYS
Solar/Wind Harmer
0.211
957521AF2-046 GEN
Solar/Wind Harmer
15.623
961681AG1-008 GEN
Solar/Wind Harmer
15.623
3146173TUNIS
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
316463AE2-346 GEN
Solar/Wind Harmer
0.178
316140AB2-099
Solar/Wind Harmer
0.074
962331AG1-082 GEN
Solar/Wind Harmer
2.207
3146263WOODLND
Solar/Wind Harmer
0.199
970133AG2-095 GEN
Solar/Wind Harmer
1.906
3150991CHESPKB
50/50
3.182
3150991CHESPKB
50/50
3.105
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3142956BIRDNECK
Solar/Wind Harmer
0
316036AC1-147 C
Solar/Wind Harmer
0.053
316316AC1-027 C
Solar/Wind Harmer
0.275
3145506HICKORY
Solar/Wind Harmer
1.141
3145506HICKORY
Solar/Wind Harmer
0.684
3145506HICKORY
Solar/Wind Harmer
0.171
316339AD2-160 GEN
Solar/Wind Harmer
0.459
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.158
3137176SLIGO L2192
Solar/Wind Harmer
1.119
3146456SLIGO L269
Solar/Wind Harmer
4.975
3130086AYDLETT
Solar/Wind Harmer
1.12
3146386ELIZ CT
Solar/Wind Harmer
0.274
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.266
3146516WINFALL
Solar/Wind Harmer
0.266
3146516WINFALL
Solar/Wind Harmer
0.266
3146626S HERTFORD
Solar/Wind Harmer
0.262
3146626S HERTFORD
Solar/Wind Harmer
0.262
3146376EDENTON
Solar/Wind Harmer
1.115
3146376EDENTON
Solar/Wind Harmer
1.115
958261AF2-120 GEN
Solar/Wind Harmer
8.075
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3142946ENON
Solar/Wind Harmer
0.024
316075AC2-137 C
Solar/Wind Harmer
0.065
316033AB2-134 GEN
Solar/Wind Harmer
0.014
315697AD1-025 GEN
Solar/Wind Harmer
0.262
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
2.426
3150341NORNECKC1
Adder
2.407
316065AD1-022 GEN
Solar/Wind Harmer
10.294
970657AG2-426 GEN
Solar/Wind Harmer
7.712
970657AG2-426 GEN
Solar/Wind Harmer
1.617
3145893MURPHYS
Solar/Wind Harmer
1.41
3145893MURPHYS
Solar/Wind Harmer
0.379
3146173TUNIS
Solar/Wind Harmer
0.208
3146173TUNIS
Solar/Wind Harmer
0.208
3145933PARMELE
Solar/Wind Harmer
0.379
3145933PARMELE
Solar/Wind Harmer
0.189
316426AA2-053 GEN
Solar/Wind Harmer
0.625
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3142666NORTHAMPTON
Solar/Wind Harmer
0.111
972185AH1-677 GEN
Adder
10.353
3144356SAPONY
Solar/Wind Harmer
1.528
972187AH1-678 GEN
Adder
5.178
3145593CAROLNA
Solar/Wind Harmer
0.18
3145593CAROLNA
Solar/Wind Harmer
0.18
966811AG1-552 GEN
Solar/Wind Harmer
1.959
3145593CAROLNA
Solar/Wind Harmer
0.225
3145783HORNRTN
Solar/Wind Harmer
3.196
3145783HORNRTN
Solar/Wind Harmer
2.557
3145783HORNRTN
Solar/Wind Harmer
0.799
3145783HORNRTN
Solar/Wind Harmer
0.32
3145796HORNRTN
Solar/Wind Harmer
0.534
316181AB2-040 GEN
Solar/Wind Harmer
0.257
970933AG2-581 GEN
Solar/Wind Harmer
14.033
316274AC1-208 GEN
Solar/Wind Harmer
0.91
3145493TOT1
Solar/Wind Harmer
0.387
3145453TOT5
Solar/Wind Harmer
0.232
3145603CNETO
Solar/Wind Harmer
0.155
961601AG1-000A GEN
Solar/Wind Harmer
2.822
316263AC1-034 GEN
Solar/Wind Harmer
6.026
970099AG2-077 GEN
Solar/Wind Harmer
16.845
316240AF1-291 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
Adder
72.632
939181AE1-148 GEN
Solar/Wind Harmer
6.878
3150691DARBY 3
Adder
10.054
3150701DARBY 4
Adder
10.031
3150681DARBY 2
Adder
10.019
3150671DARBY 1
Adder
10.008
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
6.199
964791AG1-342 GEN
Solar/Wind Harmer
2.458
3146843MT LREL
Solar/Wind Harmer
0.128
3146843MT LREL
Solar/Wind Harmer
0.128
970323AG2-213 GEN
Solar/Wind Harmer
5.316
971775AH1-396 GEN
Solar/Wind Harmer
0.199
316034AC1-036 C
Solar/Wind Harmer
0.009
971741AH1-377 GEN
Solar/Wind Harmer
12.345
970301AG2-198 GEN
Solar/Wind Harmer
4.996
958211AF2-115 GEN
Solar/Wind Harmer
1.384
963191AG1-168 GEN
Solar/Wind Harmer
0.461
3144293JTRSVLE
Adder
0.367
3144293JTRSVLE
Adder
0.309
316222AC1-221 GEN
Solar/Wind Harmer
0.474
3142366NRTHEST
Adder
0.372
315813AE1-149 C
Solar/Wind Harmer
10.584
316317KELFORD C
Solar/Wind Harmer
0.019
3145823KELFORD
Solar/Wind Harmer
0.196
3145933PARMELE
Solar/Wind Harmer
0.189
966801AG1-551 GEN
Solar/Wind Harmer
2.208
3141906WESTMOR
Solar/Wind Harmer
0.075
970293AG2-193 GEN
Solar/Wind Harmer
1.977
3142666NORTHAMPTON
Solar/Wind Harmer
0.185
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
316365GEN2_N
Solar/Wind Harmer
0.405
316210AC1-098 GEN
Solar/Wind Harmer
1.669
3145796HORNRTN
Solar/Wind Harmer
0.711
3145796HORNRTN
Solar/Wind Harmer
0.178
313506AB2-031 GEN
Solar/Wind Harmer
0.548
970917AG2-570 GEN
Solar/Wind Harmer
15.528
965281AG1-393 GEN
Solar/Wind Harmer
1.806
316327AA2-057 GEN
Solar/Wind Harmer
0.254
970737AG2-469 GEN
Solar/Wind Harmer
7.154
315724AD1-057 GEN
Solar/Wind Harmer
0.627
3146073TAR RVR
Solar/Wind Harmer
0.167
3146083TARBORO
Solar/Wind Harmer
0.167
3146233WITAKRS
Solar/Wind Harmer
0.82
3146233WITAKRS
Solar/Wind Harmer
0.111
3143096IRON208
Adder
0.683
3143096IRON208
Adder
0.669
3138543CONSLDL
Solar/Wind Harmer
0.107
3147043LAWRENC
Solar/Wind Harmer
0.098
315839AE2-212 C
Solar/Wind Harmer
0.001
961601AG1-000A GEN
Solar/Wind Harmer
11.289
3145543BTLEBRO
Solar/Wind Harmer
0.158
3145543BTLEBRO
Solar/Wind Harmer
0.158
971623AH1-311 GEN
Solar/Wind Harmer
0.317
316478AD1-087 GEN
Solar/Wind Harmer
0.524
316486AD2-202 GEN
Solar/Wind Harmer
0.154
316131AB2-060 GEN
Solar/Wind Harmer
0.423
3142416OLDCHRC
Solar/Wind Harmer
1.283
964241AG1-285 GEN
Solar/Wind Harmer
8.767
315785AD2-033 C
Solar/Wind Harmer
1.028
970257AG2-171 GEN
Solar/Wind Harmer
3.987
959311AF2-222 GEN
Solar/Wind Harmer
10.954
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.24
970909AG2-566 GEN
Solar/Wind Harmer
1.249
3150861SPRUNCD
Adder
0.537
963181AG1-167 GEN
Solar/Wind Harmer
0.461
3144293JTRSVLE
Adder
0.367
316283AC2-100 C
Solar/Wind Harmer
0.223
940641AE2-051 GEN
Solar/Wind Harmer
17.631
316381AD1-082 GEN
Solar/Wind Harmer
0.226
316458AB2-190 GEN2
Solar/Wind Harmer
1.162
970129AG2-093 GEN
Solar/Wind Harmer
6.111
970659AG2-427 GEN
Solar/Wind Harmer
10.353
944631AF1-128 GEN
Adder
101.924
316337AD2-073 GEN
Solar/Wind Harmer
0.183
3145893MURPHYS
Solar/Wind Harmer
0.842
3145893MURPHYS
Solar/Wind Harmer
0.937
3146173TUNIS
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3146263WOODLND
Solar/Wind Harmer
0.199
3145823KELFORD
Solar/Wind Harmer
0.196
3146293MARTNCO
Solar/Wind Harmer
0.176
316190AA2-174 GEN
Solar/Wind Harmer
0
316011AB1-132 GEN
Solar/Wind Harmer
3.295
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
962571AG1-106 GEN
Solar/Wind Harmer
2.579
316023GEN1_S
Solar/Wind Harmer
0.405
316212AC1-099_GEN
Solar/Wind Harmer
0.931
3145783HORNRTN
Solar/Wind Harmer
0.18
3145796HORNRTN
Solar/Wind Harmer
0.587
3145796HORNRTN
Solar/Wind Harmer
0.178
970919AG2-571 GEN
Solar/Wind Harmer
6.211
960081AF2-299 GEN
Solar/Wind Harmer
1.675
970087AG2-069 GEN
Solar/Wind Harmer
13.912
316494AC1-189 GEN
Solar/Wind Harmer
0.586
315671AE2-027_GEN
Solar/Wind Harmer
10.758
315722AD1-056 GEN
Solar/Wind Harmer
1.058
961671AG1-007 GEN
Solar/Wind Harmer
0.026
3146083TARBORO
Solar/Wind Harmer
0.167
3145493TOT1
Solar/Wind Harmer
0.742
971795AH1-408 GEN
Solar/Wind Harmer
11.088
3146233WITAKRS
Solar/Wind Harmer
0.65
3143096IRON208
Adder
0.683
3147043LAWRENC
Adder
1.471
3145543BTLEBRO
Solar/Wind Harmer
0.158
3145543BTLEBRO
Solar/Wind Harmer
0.127
316359AB2-059 GEN
Solar/Wind Harmer
0.57
316049AB1-081 GEN
Solar/Wind Harmer
0.908
3142053HEARTS
Solar/Wind Harmer
0.279
957481AF2-042 GEN
Solar/Wind Harmer
42.112
316129AC1-054 GEN
Solar/Wind Harmer
0.592
971065AG2-659 GEN
Solar/Wind Harmer
6.63
972135AH1-637 GEN
Solar/Wind Harmer
1.313
315693AD1-088 GEN
Solar/Wind Harmer
7.161
962491AG1-098 GEN
Solar/Wind Harmer
8.419
315687AD1-152 GEN
Solar/Wind Harmer
0.005
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3142543TWELFTH
Solar/Wind Harmer
0.013
3142416OLDCHRC
Solar/Wind Harmer
0.344
3142416OLDCHRC
Solar/Wind Harmer
0.132
970401AG2-262 GEN
Solar/Wind Harmer
0.751
970685AG2-442 GEN
Solar/Wind Harmer
8.947
3150851SPRUNCC
Adder
0.537
963171AG1-166 GEN
Solar/Wind Harmer
0.615
971563AH1-280 GEN
Solar/Wind Harmer
1.23
3144293JTRSVLE
Adder
0.367
316003AC1-222 GEN
Solar/Wind Harmer
0.003
3151191GRAVEL3
Adder
18.807
3151211GRAVEL5
Adder
18.807
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
962981AG1-147 GEN
Solar/Wind Harmer
9.537
970327AG2-215 GEN
Solar/Wind Harmer
8.242
3130156CHOWAN
Solar/Wind Harmer
0.251
3130156CHOWAN
Solar/Wind Harmer
0.251
316311AC2-079 GEN
Solar/Wind Harmer
7.083
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.169
315816AE2-034 GEN
Solar/Wind Harmer
1.025
3142433PROV 92
Adder
0.459
3142433PROV 92
Adder
0.459
316369SG1_INVT
Solar/Wind Harmer
0.009
3141813NORNECK
Solar/Wind Harmer
0.232
971167AH1-042 GEN
Solar/Wind Harmer
20.385
3130546PLYMOUTH
Solar/Wind Harmer
0.229
315732AD1-074 GEN1
Solar/Wind Harmer
1.309
315733AD1-074 GEN2
Solar/Wind Harmer
1.309
315735AD1-075 GEN1
Solar/Wind Harmer
0.655
3146206CASHIE
Solar/Wind Harmer
0.221
970601AG2-382 GEN
Solar/Wind Harmer
8.257
316132AB2-190 GEN1
Solar/Wind Harmer
1.162
965291AG1-394 GEN
Solar/Wind Harmer
0.947
3145893MURPHYS
Solar/Wind Harmer
0.569
3145893MURPHYS
Solar/Wind Harmer
0.211
3145513AHOSKIE
Solar/Wind Harmer
0.433
3145513AHOSKIE
Solar/Wind Harmer
0.207
3145683EARLEYS
Solar/Wind Harmer
0.411
3145683EARLEYS
Solar/Wind Harmer
0.206
3145683EARLEYS
Solar/Wind Harmer
0.206
3146043SEABORD
Solar/Wind Harmer
0.195
315607AA1-063A GEN
Solar/Wind Harmer
0.395
941031AE2-094 GEN
Solar/Wind Harmer
35.093
944011AF1-069 GEN
Solar/Wind Harmer
11.466
316223AC1-118
Solar/Wind Harmer
0.135
3146033SCOT NK
Solar/Wind Harmer
0.749
970673AG2-436 GEN
Solar/Wind Harmer
39.792
970673AG2-436 GEN
Solar/Wind Harmer
26.528
316315AB2-025 C
Solar/Wind Harmer
0.148
315814AE2-033 C
Solar/Wind Harmer
14.447
971967AH1-528 GEN
Solar/Wind Harmer
29.182
316005AA1-067
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.721
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
3145746EVERETS
Solar/Wind Harmer
0.181
315652AC1-086 GEN
Solar/Wind Harmer
19.936
970181AG2-120 GEN
Solar/Wind Harmer
2.256
3137643SOCKMAN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
0.569
3145796HORNRTN
Solar/Wind Harmer
0.071
3143316POE
Solar/Wind Harmer
0.699
316087AB2-174 GEN
Solar/Wind Harmer
0.005
970085AG2-068 GEN
Solar/Wind Harmer
9.275
970581AG2-369 GEN
Solar/Wind Harmer
7.976
957861AF2-080 GEN
Solar/Wind Harmer
7.482
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.167
3145573BETHELC
Solar/Wind Harmer
0.167
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
6.814
944491AF1-114 GEN
Solar/Wind Harmer
0
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316312AB1-027
Solar/Wind Harmer
0.237
316118AC1-105 GEN
Solar/Wind Harmer
0.324
971443AH1-215 GEN
Solar/Wind Harmer
2.1
3144303KENBRDG
Solar/Wind Harmer
0.1
3147173SINAI
Solar/Wind Harmer
0.123
3147243WELCO
Solar/Wind Harmer
0.077
970683AG2-441 GEN
Solar/Wind Harmer
7.989
970681AG2-440 GEN
Solar/Wind Harmer
6.391
971285AH1-108 GEN
Adder
0.879
946301AF1-294 GEN
Solar/Wind Harmer
2.276
961791AG1-021 GEN
Solar/Wind Harmer
1.107
NYPJM->LTFIMP_NY
CLTF
1.457
LGEELTFEXP_LGEE->PJM
CLTF
0.489
LAGNLTFEXP_LAGN->PJM
CLTF
4.637
WECLTFEXP_WEC->PJM
CLTF
0.242
CBM South 2LTFEXP_CBM-S2->PJM
CBM
18.084
TVALTFEXP_TVA->PJM
CLTF
2.295
CPLELTFEXP_CPLE->PJM
CLTF
8.941
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.836
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.626
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.547
MECLTFEXP_MEC->PJM
CLTF
1.618
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.23 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:7478.0
MW Contribution:18.42
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
220.481
316312AB1-027
Solar/Wind Harmer
1.473
315976AC1-164 GENA
Solar/Wind Harmer
45.938
316169AC1-164_GENC
Solar/Wind Harmer
39.686
315975AC1-164 GENB
Solar/Wind Harmer
1.359
316132AB2-190 GEN1
Solar/Wind Harmer
4.185
316369SG1_INVT
Solar/Wind Harmer
7.375
972265AH1-717 GEN
Adder
28.426
3151201GRAVEL4
Adder
26.648
3151191GRAVEL3
Adder
26.311
3151211GRAVEL5
Adder
26.311
971445AH1-216 GEN
Solar/Wind Harmer
25.381
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.275
3151091ELIZAR2
Adder
32.697
3152611GOSPORTB
Adder
4.62
3152621GOSPORTC
Adder
3.921
3152601GOSPORTA
Adder
3.617
971167AH1-042 GEN
Solar/Wind Harmer
38.839
957871AF2-081 GEN
Solar/Wind Harmer
20.163
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
957831AF2-077 GEN
Solar/Wind Harmer
1.21
3138283WHITEMARSH
Solar/Wind Harmer
0.062
319010AE1-072 C
Solar/Wind Harmer
8.132
3146406KITTY HAWK
Solar/Wind Harmer
0.033
316305AF2-043 C
Solar/Wind Harmer
1.209
315833AF1-017_GEN
Solar/Wind Harmer
7.57
316349AD2-085 GEN
Solar/Wind Harmer
3.545
316311AC2-079 GEN
Solar/Wind Harmer
20.103
316233AE1-074 FULL
Solar/Wind Harmer
1.071
3143873LANEXA
Solar/Wind Harmer
-0.024
971281AH1-106 GEN
Solar/Wind Harmer
6.47
971283AH1-107 GEN
Solar/Wind Harmer
6.47
315835AF2-110_GEN
Solar/Wind Harmer
4.973
313526AB2-022
Solar/Wind Harmer
1.073
316314AB2-024 C
Solar/Wind Harmer
3.388
3146486SUNBURY
Solar/Wind Harmer
-0.04
3146486SUNBURY
Solar/Wind Harmer
-0.04
3143316POE
Solar/Wind Harmer
-0.156
316321Z2-027
Solar/Wind Harmer
1.067
3146396TANGLEW
Solar/Wind Harmer
0.728
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
316059AD1-063 C
Solar/Wind Harmer
0.886
315662AE1-191 GEN
Solar/Wind Harmer
4.681
315666AE1-190 GEN
Solar/Wind Harmer
1.17
315611Z1-036_GEN2
Solar/Wind Harmer
9.52
957601AF2-054 GEN
Solar/Wind Harmer
1.152
3141873WAN 176
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.038
316315AB2-025 C
Solar/Wind Harmer
1.009
3141913WHIT STONE
Solar/Wind Harmer
-0.037
315814AE2-033 C
Solar/Wind Harmer
34.733
3138133OCRAN
Solar/Wind Harmer
-0.011
3152331SURRY 2
50/50
15.855
3142416OLDCHRC
Solar/Wind Harmer
-0.113
3142416OLDCHRC
Solar/Wind Harmer
-0.043
316159AE1-175 C
Solar/Wind Harmer
1.141
944631AF1-128 GEN
Adder
179.448
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.128
971317AH1-138 GEN
Solar/Wind Harmer
5.215
316294AC1-161 GEN
Solar/Wind Harmer
13.471
3142543TWELFTH
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
9.437
316458AB2-190 GEN2
Solar/Wind Harmer
4.185
971069AG2-661 GEN
Solar/Wind Harmer
6.537
971647AH1-324 GEN
Solar/Wind Harmer
20.617
961611AG1-000B GEN
Solar/Wind Harmer
20.327
3151171GRAVELC
Adder
3.894
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.163
944591AF1-124 GEN
Solar/Wind Harmer
186.31
316375AC2-012 GEN
Solar/Wind Harmer
14.108
3150981CHESPKA
Adder
4.53
315671AE2-027_GEN
Solar/Wind Harmer
30.454
316072AD1-144
Solar/Wind Harmer
0.817
316388AE2-253 GEN
Solar/Wind Harmer
2.723
3142433PROV 92
Solar/Wind Harmer
-0.16
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
316246AF1-032 C
Solar/Wind Harmer
0.811
970659AG2-427 GEN
Solar/Wind Harmer
21.25
316381AD1-082 GEN
Solar/Wind Harmer
3.667
970661AG2-428 GEN
Solar/Wind Harmer
42.449
3143526WINTERP
Solar/Wind Harmer
-0.206
316093AE2-104_GEN
Solar/Wind Harmer
11.566
3141766HARMONY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.126
3146516WINFALL
Solar/Wind Harmer
-0.039
939411AE1-173 GEN
Solar/Wind Harmer
195.386
971777AH1-397 GEN
Solar/Wind Harmer
4.594
3141843SHACKLE
Adder
1.777
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
36.152
315800Z1-036_GEN1
Solar/Wind Harmer
9.52
3130156CHOWAN
Solar/Wind Harmer
-0.038
3138133OCRAN
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.103
971163AH1-040 GEN
Solar/Wind Harmer
34.777
972277AH1-723 GEN
Adder
192.1
3146206CASHIE
Solar/Wind Harmer
-0.036
971547AH1-271 GEN
Solar/Wind Harmer
8.955
3145893MURPHYS
Solar/Wind Harmer
-0.141
3145893MURPHYS
Solar/Wind Harmer
1.053
3146173TUNIS
Solar/Wind Harmer
-0.035
316023GEN1_S
Solar/Wind Harmer
2.36
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
961951AG1-038 GEN
Solar/Wind Harmer
4.538
970919AG2-571 GEN
Solar/Wind Harmer
10.882
970087AG2-069 GEN
Solar/Wind Harmer
32.123
316174AB2-169 GEN
Solar/Wind Harmer
5.263
3145823KELFORD
Solar/Wind Harmer
-0.034
960081AF2-299 GEN
Solar/Wind Harmer
3.829
316011AB1-132 GEN
Solar/Wind Harmer
7.075
962571AG1-106 GEN
Solar/Wind Harmer
4.861
316190AA2-174 GEN
Solar/Wind Harmer
0.414
962861AG1-135 GEN
Solar/Wind Harmer
12.583
3145796HORNRTN
Solar/Wind Harmer
-0.109
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
971795AH1-408 GEN
Solar/Wind Harmer
24.88
3146293MARTNCO
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
2.639
957481AF2-042 GEN
Solar/Wind Harmer
102.405
316212AC1-099_GEN
Solar/Wind Harmer
2.851
3143336POWHATN
Solar/Wind Harmer
3.871
964211AG1-282 GEN
Solar/Wind Harmer
0.968
3141726DUNNSVL
Solar/Wind Harmer
-0.128
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
16.002
962491AG1-098 GEN
Solar/Wind Harmer
21.316
315722AD1-056 GEN
Solar/Wind Harmer
3.316
316494AC1-189 GEN
Solar/Wind Harmer
3.395
316129AC1-054 GEN
Solar/Wind Harmer
2.761
971065AG2-659 GEN
Solar/Wind Harmer
15.657
3150351NORNECKC2
Adder
2.755
3144293JTRSVLE
Adder
0.817
316045AC1-158 PL2
Solar/Wind Helper
8.047
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.539
3147666LOUISA
Solar/Wind Helper
1.158
316192AB2-158 GEN
Solar/Wind Helper
1.899
223401AF1-299 GEN
Solar/Wind Helper
0.394
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.234
235062AE1-101 C1
Solar/Wind Helper
1.425
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232428Y3-058 C
Solar/Wind Helper
0.328
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.113
233972AC1-094 C
Solar/Wind Helper
0.293
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
316336AC2-165 C
Solar/Wind Harmer
4.115
971645AH1-323 GEN
50/50
34.83
3151161SURRY 1
50/50
14.063
3142416OLDCHRC
Solar/Wind Harmer
4.408
970293AG2-193 GEN
Solar/Wind Harmer
5.386
3142946ENON
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
1.281
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.538
3150921YORKTN3
Adder
9.353
3144216WINCHST
Adder
1.401
315773AC2-141 GEN
Solar/Wind Harmer
17.422
970133AG2-095 GEN
Solar/Wind Harmer
4.665
970129AG2-093 GEN
Solar/Wind Harmer
23.298
315778AD1-151 GEN
Solar/Wind Harmer
35.792
961611AG1-000B GEN
Solar/Wind Harmer
8.673
3151221GRAVEL6
Adder
26.617
3151171GRAVELC
Adder
5.121
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
185.641
944601AF1-125 GEN
Solar/Wind Harmer
182.744
3151101ELIZAR3
Adder
33.701
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
5.061
315839AE2-212 C
Solar/Wind Harmer
1.217
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.905
316473AC1-191 GEN
Solar/Wind Harmer
4.326
315813AE1-149 C
Solar/Wind Harmer
25.043
970659AG2-427 GEN
Solar/Wind Harmer
3.766
316083AB2-161 GEN
Solar/Wind Harmer
6.49
970661AG2-428 GEN
Solar/Wind Harmer
7.523
316320Y1-086
Solar/Wind Harmer
2.331
316435W1029_GEN3
Solar/Wind Harmer
7.121
3141766HARMONY
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.039
3141843SHACKLE
Adder
1.777
316203AE2-005 GEN
Solar/Wind Harmer
16.468
3146626S HERTFORD
Solar/Wind Harmer
-0.039
316280AD1-041 GEN
Solar/Wind Harmer
2.926
3145273HOLLAND
Solar/Wind Harmer
-0.029
316156AD2-030 GEN
Solar/Wind Harmer
1.029
3141873WAN 176
Solar/Wind Harmer
4.571
3146376EDENTON
Solar/Wind Harmer
-0.038
315614AA2-178 GEN
Solar/Wind Harmer
4.002
971157AH1-035 GEN
Solar/Wind Harmer
4.549
315737AD1-076 GEN
Solar/Wind Harmer
6.891
972255AH1-712 GEN
Adder
164.849
3156081AA2-088 GEN
Solar/Wind Harmer
11.679
3146206CASHIE
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.248
3145893MURPHYS
Solar/Wind Harmer
-0.035
957521AF2-046 GEN
Solar/Wind Harmer
27.872
961681AG1-008 GEN
Solar/Wind Harmer
27.872
962971AG1-146 GEN
Solar/Wind Harmer
6.6
3156021HOLLOMANSOL
Solar/Wind Harmer
4.742
3146173TUNIS
Solar/Wind Harmer
-0.035
316365GEN2_N
Solar/Wind Harmer
2.36
316463AE2-346 GEN
Solar/Wind Harmer
0.566
316140AB2-099
Solar/Wind Harmer
0.236
962331AG1-082 GEN
Solar/Wind Harmer
4.374
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
316484AD2-074 GEN
Solar/Wind Harmer
8.672
970009AG2-005 GEN
Solar/Wind Harmer
4.306
970917AG2-570 GEN
Solar/Wind Harmer
85.969
316317KELFORD C
Solar/Wind Harmer
1.606
3145823KELFORD
Solar/Wind Harmer
-0.034
966621AG1-532 GEN
Solar/Wind Harmer
0.691
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
313506AB2-031 GEN
Solar/Wind Harmer
2.715
3145796HORNRTN
Solar/Wind Harmer
-0.133
3145796HORNRTN
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.411
3145933PARMELE
Solar/Wind Harmer
-0.033
966801AG1-551 GEN
Solar/Wind Harmer
4.109
3147043LAWRENC
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
5.131
316313AB2-026
Solar/Wind Harmer
0.88
316258AE1-075 C
Solar/Wind Harmer
0.792
316405AF2-144 C
Solar/Wind Harmer
0.836
3143336POWHATN
Solar/Wind Harmer
3.29
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315724AD1-057 GEN
Solar/Wind Harmer
1.824
316478AD1-087 GEN
Solar/Wind Harmer
2.743
316486AD2-202 GEN
Solar/Wind Harmer
0.803
316327AA2-057 GEN
Solar/Wind Harmer
3.182
3150351NORNECKC2
Adder
2.802
3144293JTRSVLE
Adder
0.817
3151861LOWMORA
Adder
1.616
316044AC1-158 PL1
Solar/Wind Helper
2.514
316450AC1-158 RIC
Solar/Wind Helper
0.67
3141196NOKESVL
Solar/Wind Helper
1.391
316170AC1-121 GEN2
Solar/Wind Helper
0.513
227287AC2-120 GEN
Solar/Wind Helper
0.433
226910AB2-157 C
Solar/Wind Helper
0.018
3147666LOUISA
Solar/Wind Helper
0.666
223402AF1-300 C
Solar/Wind Helper
0.394
237030AB1-096 C
Solar/Wind Helper
0.069
3132273ORANGE
Solar/Wind Helper
0.05
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233982AB2-133 GEN
Solar/Wind Helper
0.347
233918AB1-142 GEN
Solar/Wind Helper
0.487
233994AC2-023 GEN
Solar/Wind Helper
0.931
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.244
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
315816AE2-034 GEN
Solar/Wind Harmer
3.002
941031AE2-094 GEN
Solar/Wind Harmer
68.862
944011AF1-069 GEN
Solar/Wind Harmer
21.577
3141783LANCAST
Solar/Wind Harmer
-0.022
3141783LANCAST
Solar/Wind Harmer
-0.014
3130546PLYMOUTH
Solar/Wind Harmer
-0.036
315732AD1-074 GEN1
Solar/Wind Harmer
7.333
315733AD1-074 GEN2
Solar/Wind Harmer
7.333
315735AD1-075 GEN1
Solar/Wind Harmer
3.667
972193AH1-681 GEN
Adder
7.366
970673AG2-436 GEN
Solar/Wind Harmer
75.963
970673AG2-436 GEN
Solar/Wind Harmer
38.462
3146206CASHIE
Solar/Wind Harmer
-0.036
970601AG2-382 GEN
Solar/Wind Harmer
15.671
965291AG1-394 GEN
Solar/Wind Harmer
3.177
971967AH1-528 GEN
Solar/Wind Harmer
67.134
316318V4-068
Solar/Wind Harmer
0.884
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
-0.035
962981AG1-147 GEN
Solar/Wind Harmer
15.399
3145513AHOSKIE
Solar/Wind Harmer
0.305
961941AG1-037 GEN
Solar/Wind Harmer
0.263
3145513AHOSKIE
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.069
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146043SEABORD
Solar/Wind Harmer
-0.034
315607AA1-063A GEN
Solar/Wind Harmer
3.475
970085AG2-068 GEN
Solar/Wind Harmer
21.415
970581AG2-369 GEN
Solar/Wind Harmer
18.417
946281AF1-292 GEN
Solar/Wind Harmer
0.762
316087AB2-174 GEN
Solar/Wind Harmer
4.83
315652AC1-086 GEN
Solar/Wind Harmer
38.044
3137643SOCKMAN
Solar/Wind Harmer
-0.134
3145796HORNRTN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.133
316005AA1-067
Solar/Wind Harmer
0.65
3145746EVERETS
Solar/Wind Harmer
-0.127
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
970181AG2-120 GEN
Solar/Wind Harmer
4.22
970831AG2-522 GEN
Solar/Wind Harmer
15.843
957861AF2-080 GEN
Solar/Wind Harmer
13.805
316420AA1-050 GEN
Solar/Wind Harmer
3.571
3141813NORNECK
Solar/Wind Harmer
-0.031
972189AH1-679 GEN
Adder
4.354
972205AH1-687 GEN
Adder
8.98
3151881LOWMORC
Adder
1.603
3151881LOWMORC
Adder
1.578
3151861LOWMORA
Adder
1.553
316164AC1-076 GEN
Solar/Wind Helper
1.831
316411AF1-147_GEN1
Solar/Wind Helper
1.081
316415AF1-147_GEN2
Solar/Wind Helper
1.081
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.391
960921AF2-383 GEN
Solar/Wind Helper
0.176
233935AB2-179 C
Solar/Wind Helper
1.231
205943AE1-185 GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
233923SMA
Solar/Wind Helper
0.928
233990AG1-397 GEN
Solar/Wind Helper
0.029
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.8
964001AG1-254 GEN
Solar/Wind Helper
0.919
238208AF1-136 C
Solar/Wind Helper
0.173
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
3142296MT RD221
50/50
1.31
3150691DARBY 3
50/50
29.1
3150701DARBY 4
50/50
29.033
3150681DARBY 2
50/50
28.999
3150671DARBY 1
50/50
28.965
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
1.17
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
13.312
315697AD1-025 GEN
Solar/Wind Harmer
8.349
944641AF1-129 GEN
Adder
174.133
316236AE1-162_GEN
Solar/Wind Harmer
1.236
316240AF1-291 C
Solar/Wind Harmer
1.232
316036AC1-147 C
Solar/Wind Harmer
1.1
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.709
316316AC1-027 C
Solar/Wind Harmer
1.249
3142956BIRDNECK
Solar/Wind Harmer
2.183
316185AD1-033 GEN
Solar/Wind Harmer
4.286
3145506HICKORY
Solar/Wind Harmer
-0.161
3145506HICKORY
Solar/Wind Harmer
-0.097
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.723
316018AA1-139 ULT2
Solar/Wind Harmer
3.455
316017AA1-139 ULT1
Solar/Wind Harmer
3.263
3137176SLIGO L2192
Solar/Wind Harmer
-0.159
3146456SLIGO L269
Solar/Wind Harmer
4.752
966871AG1-558 GEN
Solar/Wind Harmer
1.209
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
-0.16
970657AG2-426 GEN
Solar/Wind Harmer
12.492
970657AG2-426 GEN
Solar/Wind Harmer
2.612
3143526WINTERP
Solar/Wind Harmer
-0.206
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.121
316433W1029_GEN2
Solar/Wind Harmer
7.121
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
316441AF1-014 GEN
Solar/Wind Harmer
2.633
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3146626S HERTFORD
Solar/Wind Harmer
-0.039
971223AH1-071 GEN
Solar/Wind Harmer
4.826
315742AE1-103 GEN
Solar/Wind Harmer
3.978
3146376EDENTON
Solar/Wind Harmer
1.128
3146376EDENTON
Solar/Wind Harmer
1.128
3144356SAPONY
Solar/Wind Harmer
1.305
316065AD1-022 GEN
Solar/Wind Harmer
17.989
972185AH1-677 GEN
Adder
17.917
972187AH1-678 GEN
Adder
8.997
3145893MURPHYS
Solar/Wind Harmer
0.99
3145893MURPHYS
Solar/Wind Harmer
-0.064
3146173TUNIS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
970933AG2-581 GEN
Solar/Wind Harmer
32.706
316487AF1-042 GEN
Solar/Wind Harmer
4.538
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316181AB2-040 GEN
Solar/Wind Harmer
4.712
316426AA2-053 GEN
Solar/Wind Harmer
3.407
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
966811AG1-552 GEN
Solar/Wind Harmer
3.768
3145593CAROLNA
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145783HORNRTN
Solar/Wind Harmer
3.954
3145783HORNRTN
Solar/Wind Harmer
3.163
3145783HORNRTN
Solar/Wind Harmer
0.988
3145783HORNRTN
Solar/Wind Harmer
0.395
958261AF2-120 GEN
Solar/Wind Harmer
12.878
3145933PARMELE
Solar/Wind Harmer
-0.065
3145933PARMELE
Solar/Wind Harmer
-0.033
970099AG2-077 GEN
Solar/Wind Harmer
40.962
316274AC1-208 GEN
Solar/Wind Harmer
3.495
316077AC2-138 C
Solar/Wind Harmer
0.655
3150341NORNECKC1
Adder
2.894
3150341NORNECKC1
Adder
2.871
3144293JTRSVLE
Adder
0.817
3144293JTRSVLE
Adder
0.688
316447AC1-158 HLD
Solar/Wind Helper
5.533
315651AD1-115 GEN
Solar/Wind Helper
1.131
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.16
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.425
205916AD1-020 GEN
Solar/Wind Helper
1.648
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.57
232424Y1-079 C
Solar/Wind Helper
0.113
233987AB2-037 GEN
Solar/Wind Helper
2.269
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.55
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.025
NYPJM->LTFIMP_NY
CLTF
4.642
LGEELTFEXP_LGEE->PJM
CLTF
3.021
LAGNLTFEXP_LAGN->PJM
CLTF
14.648
WECLTFEXP_WEC->PJM
CLTF
1.528
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.037
TVALTFEXP_TVA->PJM
CLTF
7.416
CPLELTFEXP_CPLE->PJM
CLTF
17.726
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.522
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.806
MECLTFEXP_MEC->PJM
CLTF
7.852
SIGELTFEXP_SIGE->PJM
CLTF
0.243

Details for 8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:149.23 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:7477.96
MW Contribution:18.42
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
15.855
3142416OLDCHRC
Solar/Wind Harmer
-0.113
3142416OLDCHRC
Solar/Wind Harmer
-0.043
316159AE1-175 C
Solar/Wind Harmer
1.141
944631AF1-128 GEN
Adder
179.449
3143096IRON208
Adder
1.57
3138126ROCKLANDING
Solar/Wind Harmer
0.128
971317AH1-138 GEN
Solar/Wind Harmer
5.215
316294AC1-161 GEN
Solar/Wind Harmer
13.471
3142543TWELFTH
Solar/Wind Harmer
-0.004
970129AG2-093 GEN
Solar/Wind Harmer
9.437
316458AB2-190 GEN2
Solar/Wind Harmer
4.185
971069AG2-661 GEN
Solar/Wind Harmer
6.537
971647AH1-324 GEN
Solar/Wind Harmer
20.617
961611AG1-000B GEN
Solar/Wind Harmer
20.327
971645AH1-323 GEN
50/50
34.83
3151161SURRY 1
50/50
14.063
3142416OLDCHRC
Solar/Wind Harmer
4.408
970293AG2-193 GEN
Solar/Wind Harmer
5.386
3142946ENON
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
1.281
3143096IRON208
Adder
1.57
3143096IRON208
Adder
1.538
3150921YORKTN3
Adder
9.353
3144216WINCHST
Adder
1.401
315773AC2-141 GEN
Solar/Wind Harmer
17.422
970133AG2-095 GEN
Solar/Wind Harmer
4.665
972263AH1-716 GEN
50/50
220.481
316312AB1-027
Solar/Wind Harmer
1.473
315976AC1-164 GENA
Solar/Wind Harmer
45.938
316169AC1-164_GENC
Solar/Wind Harmer
39.686
315975AC1-164 GENB
Solar/Wind Harmer
1.359
316132AB2-190 GEN1
Solar/Wind Harmer
4.185
316369SG1_INVT
Solar/Wind Harmer
7.375
972265AH1-717 GEN
Adder
28.427
3151201GRAVEL4
Adder
26.648
3151191GRAVEL3
Adder
26.311
3151211GRAVEL5
Adder
26.311
971445AH1-216 GEN
Solar/Wind Harmer
25.381
971285AH1-108 GEN
Adder
2.752
3151081ELIZAR1
Adder
33.275
3151091ELIZAR2
Adder
32.697
3152611GOSPORTB
Adder
4.62
3152621GOSPORTC
Adder
3.921
3152601GOSPORTA
Adder
3.617
971167AH1-042 GEN
Solar/Wind Harmer
38.839
957871AF2-081 GEN
Solar/Wind Harmer
20.163
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
957831AF2-077 GEN
Solar/Wind Harmer
1.21
3138283WHITEMARSH
Solar/Wind Harmer
0.062
319010AE1-072 C
Solar/Wind Harmer
8.132
3146406KITTY HAWK
Solar/Wind Harmer
0.033
316305AF2-043 C
Solar/Wind Harmer
1.209
315833AF1-017_GEN
Solar/Wind Harmer
7.57
316349AD2-085 GEN
Solar/Wind Harmer
3.545
316311AC2-079 GEN
Solar/Wind Harmer
20.103
970129AG2-093 GEN
Solar/Wind Harmer
23.298
315778AD1-151 GEN
Solar/Wind Harmer
35.792
961611AG1-000B GEN
Solar/Wind Harmer
8.673
3151221GRAVEL6
Adder
26.617
3151171GRAVELC
Adder
5.121
3150861SPRUNCD
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.016
3144536CHRHLND
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
185.642
944601AF1-125 GEN
Solar/Wind Harmer
182.744
3151101ELIZAR3
Adder
33.701
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
5.061
315839AE2-212 C
Solar/Wind Harmer
1.217
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
971153AH1-033 GEN
Solar/Wind Harmer
4.905
316473AC1-191 GEN
Solar/Wind Harmer
4.326
315813AE1-149 C
Solar/Wind Harmer
25.043
970659AG2-427 GEN
Solar/Wind Harmer
3.766
316083AB2-161 GEN
Solar/Wind Harmer
6.49
970661AG2-428 GEN
Solar/Wind Harmer
7.523
316320Y1-086
Solar/Wind Harmer
2.331
316435W1029_GEN3
Solar/Wind Harmer
7.121
3141766HARMONY
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.039
3141843SHACKLE
Adder
1.777
316203AE2-005 GEN
Solar/Wind Harmer
16.469
3146626S HERTFORD
Solar/Wind Harmer
-0.039
316280AD1-041 GEN
Solar/Wind Harmer
2.926
3145273HOLLAND
Solar/Wind Harmer
-0.029
316156AD2-030 GEN
Solar/Wind Harmer
1.029
3141873WAN 176
Solar/Wind Harmer
4.571
3146376EDENTON
Solar/Wind Harmer
-0.038
315614AA2-178 GEN
Solar/Wind Harmer
4.002
971157AH1-035 GEN
Solar/Wind Harmer
4.549
315737AD1-076 GEN
Solar/Wind Harmer
6.891
972255AH1-712 GEN
Adder
164.848
3156081AA2-088 GEN
Solar/Wind Harmer
11.679
3146206CASHIE
Solar/Wind Harmer
-0.036
3145893MURPHYS
Solar/Wind Harmer
0.248
3145893MURPHYS
Solar/Wind Harmer
-0.035
957521AF2-046 GEN
Solar/Wind Harmer
27.872
961681AG1-008 GEN
Solar/Wind Harmer
27.872
962971AG1-146 GEN
Solar/Wind Harmer
6.6
3156021HOLLOMANSOL
Solar/Wind Harmer
4.742
3146173TUNIS
Solar/Wind Harmer
-0.035
316365GEN2_N
Solar/Wind Harmer
2.36
316463AE2-346 GEN
Solar/Wind Harmer
0.566
316140AB2-099
Solar/Wind Harmer
0.236
962331AG1-082 GEN
Solar/Wind Harmer
4.374
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
316484AD2-074 GEN
Solar/Wind Harmer
8.672
970009AG2-005 GEN
Solar/Wind Harmer
4.306
970917AG2-570 GEN
Solar/Wind Harmer
85.968
316317KELFORD C
Solar/Wind Harmer
1.606
3145823KELFORD
Solar/Wind Harmer
-0.034
316233AE1-074 FULL
Solar/Wind Harmer
1.071
3143873LANEXA
Solar/Wind Harmer
-0.024
971281AH1-106 GEN
Solar/Wind Harmer
6.47
971283AH1-107 GEN
Solar/Wind Harmer
6.47
315835AF2-110_GEN
Solar/Wind Harmer
4.973
313526AB2-022
Solar/Wind Harmer
1.073
316314AB2-024 C
Solar/Wind Harmer
3.388
3146486SUNBURY
Solar/Wind Harmer
-0.04
3146486SUNBURY
Solar/Wind Harmer
-0.04
3143316POE
Solar/Wind Harmer
-0.156
316321Z2-027
Solar/Wind Harmer
1.067
3146396TANGLEW
Solar/Wind Harmer
0.728
3145176PASQUOTANK
Solar/Wind Harmer
-0.024
316059AD1-063 C
Solar/Wind Harmer
0.886
315662AE1-191 GEN
Solar/Wind Harmer
4.681
315666AE1-190 GEN
Solar/Wind Harmer
1.17
315611Z1-036_GEN2
Solar/Wind Harmer
9.52
957601AF2-054 GEN
Solar/Wind Harmer
1.152
3141873WAN 176
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.038
3130156CHOWAN
Solar/Wind Harmer
-0.038
316315AB2-025 C
Solar/Wind Harmer
1.009
3141913WHIT STONE
Solar/Wind Harmer
-0.037
315814AE2-033 C
Solar/Wind Harmer
34.733
3138133OCRAN
Solar/Wind Harmer
-0.011
315816AE2-034 GEN
Solar/Wind Harmer
3.002
941031AE2-094 GEN
Solar/Wind Harmer
68.861
944011AF1-069 GEN
Solar/Wind Harmer
21.577
3141783LANCAST
Solar/Wind Harmer
-0.022
3141783LANCAST
Solar/Wind Harmer
-0.014
3130546PLYMOUTH
Solar/Wind Harmer
-0.036
315732AD1-074 GEN1
Solar/Wind Harmer
7.333
315733AD1-074 GEN2
Solar/Wind Harmer
7.333
315735AD1-075 GEN1
Solar/Wind Harmer
3.667
972193AH1-681 GEN
Adder
7.366
970673AG2-436 GEN
Solar/Wind Harmer
75.963
970673AG2-436 GEN
Solar/Wind Harmer
38.462
3146206CASHIE
Solar/Wind Harmer
-0.036
970601AG2-382 GEN
Solar/Wind Harmer
15.671
965291AG1-394 GEN
Solar/Wind Harmer
3.177
971967AH1-528 GEN
Solar/Wind Harmer
67.133
316318V4-068
Solar/Wind Harmer
0.884
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
-0.035
962981AG1-147 GEN
Solar/Wind Harmer
15.399
3145513AHOSKIE
Solar/Wind Harmer
0.305
961941AG1-037 GEN
Solar/Wind Harmer
0.263
3145513AHOSKIE
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.069
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146043SEABORD
Solar/Wind Harmer
-0.034
315607AA1-063A GEN
Solar/Wind Harmer
3.475
970085AG2-068 GEN
Solar/Wind Harmer
21.415
970581AG2-369 GEN
Solar/Wind Harmer
18.417
946281AF1-292 GEN
Solar/Wind Harmer
0.762
316087AB2-174 GEN
Solar/Wind Harmer
4.83
315652AC1-086 GEN
Solar/Wind Harmer
38.044
3137643SOCKMAN
Solar/Wind Harmer
-0.134
3145796HORNRTN
Solar/Wind Harmer
-0.106
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.133
316005AA1-067
Solar/Wind Harmer
0.65
3145746EVERETS
Solar/Wind Harmer
-0.127
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
970181AG2-120 GEN
Solar/Wind Harmer
4.22
970831AG2-522 GEN
Solar/Wind Harmer
15.842
957861AF2-080 GEN
Solar/Wind Harmer
13.805
316420AA1-050 GEN
Solar/Wind Harmer
3.571
3141813NORNECK
Solar/Wind Harmer
-0.031
972189AH1-679 GEN
Adder
4.354
972205AH1-687 GEN
Adder
8.979
3151881LOWMORC
Adder
1.603
3151881LOWMORC
Adder
1.578
3151861LOWMORA
Adder
1.553
316164AC1-076 GEN
Solar/Wind Helper
1.831
316411AF1-147_GEN1
Solar/Wind Helper
1.081
316415AF1-147_GEN2
Solar/Wind Helper
1.081
3138216PACIFIC
Solar/Wind Helper
0.053
3141426STAFORD
Solar/Wind Helper
0.061
237085AD2-009_GEN
Solar/Wind Helper
1.39
960921AF2-383 GEN
Solar/Wind Helper
0.176
233935AB2-179 C
Solar/Wind Helper
1.231
205943AE1-185 GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
233923SMA
Solar/Wind Helper
0.928
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.8
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.919
238208AF1-136 C
Solar/Wind Helper
0.173
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.11
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
3142296MT RD221
50/50
1.31
3150691DARBY 3
50/50
29.1
3150701DARBY 4
50/50
29.033
3150681DARBY 2
50/50
28.999
3150671DARBY 1
50/50
28.965
3142366NRTHEST
50/50
1.317
316075AC2-137 C
Solar/Wind Harmer
1.17
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
13.312
315697AD1-025 GEN
Solar/Wind Harmer
8.349
944641AF1-129 GEN
Adder
174.133
316236AE1-162_GEN
Solar/Wind Harmer
1.236
316240AF1-291 C
Solar/Wind Harmer
1.232
316036AC1-147 C
Solar/Wind Harmer
1.1
3150991CHESPKB
Adder
3.801
3150991CHESPKB
Adder
3.709
316316AC1-027 C
Solar/Wind Harmer
1.249
3142956BIRDNECK
Solar/Wind Harmer
2.183
316185AD1-033 GEN
Solar/Wind Harmer
4.286
3145506HICKORY
Solar/Wind Harmer
-0.161
3145506HICKORY
Solar/Wind Harmer
-0.097
3145506HICKORY
Solar/Wind Harmer
-0.024
316339AD2-160 GEN
Solar/Wind Harmer
2.723
316018AA1-139 ULT2
Solar/Wind Harmer
3.455
316017AA1-139 ULT1
Solar/Wind Harmer
3.263
3137176SLIGO L2192
Solar/Wind Harmer
-0.159
3146456SLIGO L269
Solar/Wind Harmer
4.752
966871AG1-558 GEN
Solar/Wind Harmer
1.209
966871AG1-558 GEN
Solar/Wind Harmer
0.413
3130086AYDLETT
Solar/Wind Harmer
-0.16
970657AG2-426 GEN
Solar/Wind Harmer
12.492
970657AG2-426 GEN
Solar/Wind Harmer
2.612
3143526WINTERP
Solar/Wind Harmer
-0.206
3146386ELIZ CT
Solar/Wind Harmer
-0.04
316431W1029_GEN1
Solar/Wind Harmer
7.121
316433W1029_GEN2
Solar/Wind Harmer
7.121
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
3146516WINFALL
Solar/Wind Harmer
-0.039
966621AG1-532 GEN
Solar/Wind Harmer
0.691
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
313506AB2-031 GEN
Solar/Wind Harmer
2.715
3145796HORNRTN
Solar/Wind Harmer
-0.133
3145796HORNRTN
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.411
3145933PARMELE
Solar/Wind Harmer
-0.033
966801AG1-551 GEN
Solar/Wind Harmer
4.109
3147043LAWRENC
Solar/Wind Harmer
-0.019
316210AC1-098 GEN
Solar/Wind Harmer
5.131
316313AB2-026
Solar/Wind Harmer
0.88
316258AE1-075 C
Solar/Wind Harmer
0.792
316405AF2-144 C
Solar/Wind Harmer
0.836
3143336POWHATN
Solar/Wind Harmer
3.29
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315724AD1-057 GEN
Solar/Wind Harmer
1.824
316478AD1-087 GEN
Solar/Wind Harmer
2.743
316486AD2-202 GEN
Solar/Wind Harmer
0.803
316327AA2-057 GEN
Solar/Wind Harmer
3.182
3150351NORNECKC2
Adder
2.802
3144293JTRSVLE
Adder
0.817
3151861LOWMORA
Adder
1.616
316044AC1-158 PL1
Solar/Wind Helper
2.514
316450AC1-158 RIC
Solar/Wind Helper
0.67
3141196NOKESVL
Solar/Wind Helper
1.391
316170AC1-121 GEN2
Solar/Wind Helper
0.513
227287AC2-120 GEN
Solar/Wind Helper
0.433
226910AB2-157 C
Solar/Wind Helper
0.018
3147666LOUISA
Solar/Wind Helper
0.666
223402AF1-300 C
Solar/Wind Helper
0.394
237030AB1-096 C
Solar/Wind Helper
0.069
3132273ORANGE
Solar/Wind Helper
0.05
238221AF1-254 C O1
Solar/Wind Helper
0.238
235067AD1-061 GEN
Solar/Wind Helper
0.424
205917AD1-020 ES
Solar/Wind Helper
0.354
233982AB2-133 GEN
Solar/Wind Helper
0.347
233918AB1-142 GEN
Solar/Wind Helper
0.487
233994AC2-023 GEN
Solar/Wind Helper
0.931
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
230430AE1-229_GEN
Solar/Wind Helper
3.244
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.052
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
3151171GRAVELC
Adder
3.894
3150851SPRUNCC
Adder
1.682
3145336SMITFLD
Solar/Wind Harmer
-0.163
944591AF1-124 GEN
Solar/Wind Harmer
186.31
316375AC2-012 GEN
Solar/Wind Harmer
14.108
3150981CHESPKA
Adder
4.53
315671AE2-027_GEN
Solar/Wind Harmer
30.454
316072AD1-144
Solar/Wind Harmer
0.817
316388AE2-253 GEN
Solar/Wind Harmer
2.723
3142433PROV 92
Solar/Wind Harmer
-0.16
3142433PROV 92
Adder
0.696
3142433PROV 92
Adder
0.696
3146456SLIGO L269
Solar/Wind Harmer
-0.04
316246AF1-032 C
Solar/Wind Harmer
0.811
970659AG2-427 GEN
Solar/Wind Harmer
21.251
316381AD1-082 GEN
Solar/Wind Harmer
3.667
970661AG2-428 GEN
Solar/Wind Harmer
42.449
3143526WINTERP
Solar/Wind Harmer
-0.206
316093AE2-104_GEN
Solar/Wind Harmer
11.566
3141766HARMONY
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.126
3146516WINFALL
Solar/Wind Harmer
-0.039
939411AE1-173 GEN
Solar/Wind Harmer
195.386
971777AH1-397 GEN
Solar/Wind Harmer
4.594
3141843SHACKLE
Adder
1.777
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
36.152
315800Z1-036_GEN1
Solar/Wind Harmer
9.52
3130156CHOWAN
Solar/Wind Harmer
-0.038
3138133OCRAN
Solar/Wind Harmer
-0.022
3145663CRESWEL
Solar/Wind Harmer
-0.103
971163AH1-040 GEN
Solar/Wind Harmer
34.777
972277AH1-723 GEN
Adder
192.098
3146206CASHIE
Solar/Wind Harmer
-0.036
971547AH1-271 GEN
Solar/Wind Harmer
8.955
3145893MURPHYS
Solar/Wind Harmer
-0.141
3145893MURPHYS
Solar/Wind Harmer
1.053
3146173TUNIS
Solar/Wind Harmer
-0.035
316023GEN1_S
Solar/Wind Harmer
2.36
3145683EARLEYS
Solar/Wind Harmer
-0.035
3146263WOODLND
Solar/Wind Harmer
-0.034
3145963POPLR C
Solar/Wind Harmer
-0.034
961951AG1-038 GEN
Solar/Wind Harmer
4.538
970919AG2-571 GEN
Solar/Wind Harmer
10.882
970087AG2-069 GEN
Solar/Wind Harmer
32.123
316174AB2-169 GEN
Solar/Wind Harmer
5.263
3145823KELFORD
Solar/Wind Harmer
-0.034
960081AF2-299 GEN
Solar/Wind Harmer
3.829
316011AB1-132 GEN
Solar/Wind Harmer
7.075
962571AG1-106 GEN
Solar/Wind Harmer
4.861
316190AA2-174 GEN
Solar/Wind Harmer
0.414
962861AG1-135 GEN
Solar/Wind Harmer
12.583
3145796HORNRTN
Solar/Wind Harmer
-0.109
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
971795AH1-408 GEN
Solar/Wind Harmer
24.879
3146293MARTNCO
Solar/Wind Harmer
0.204
3147043LAWRENC
Adder
2.639
957481AF2-042 GEN
Solar/Wind Harmer
102.404
316212AC1-099_GEN
Solar/Wind Harmer
2.851
3143336POWHATN
Solar/Wind Harmer
3.871
964211AG1-282 GEN
Solar/Wind Harmer
0.968
3141726DUNNSVL
Solar/Wind Harmer
-0.128
3145746EVERETS
Solar/Wind Harmer
-0.032
3145746EVERETS
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
16.002
962491AG1-098 GEN
Solar/Wind Harmer
21.316
315722AD1-056 GEN
Solar/Wind Harmer
3.316
316494AC1-189 GEN
Solar/Wind Harmer
3.395
316129AC1-054 GEN
Solar/Wind Harmer
2.761
971065AG2-659 GEN
Solar/Wind Harmer
15.657
3150351NORNECKC2
Adder
2.755
3144293JTRSVLE
Adder
0.817
316045AC1-158 PL2
Solar/Wind Helper
8.047
316006AB2-029 C
Solar/Wind Helper
0.164
316254AC1-120 GEN1
Solar/Wind Helper
1.539
3147666LOUISA
Solar/Wind Helper
1.159
316192AB2-158 GEN
Solar/Wind Helper
1.901
223401AF1-299 GEN
Solar/Wind Helper
0.394
23779801AA1-109
Solar/Wind Helper
0.185
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.234
235062AE1-101 C1
Solar/Wind Helper
1.425
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232428Y3-058 C
Solar/Wind Helper
0.328
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
233972AC1-094 C
Solar/Wind Helper
0.293
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.221
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.032
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
316336AC2-165 C
Solar/Wind Harmer
4.115
316441AF1-014 GEN
Solar/Wind Harmer
2.633
3146626S HERTFORD
Solar/Wind Harmer
-0.039
3146626S HERTFORD
Solar/Wind Harmer
-0.039
971223AH1-071 GEN
Solar/Wind Harmer
4.826
315742AE1-103 GEN
Solar/Wind Harmer
3.978
3146376EDENTON
Solar/Wind Harmer
1.128
3146376EDENTON
Solar/Wind Harmer
1.128
3144356SAPONY
Solar/Wind Harmer
1.305
316065AD1-022 GEN
Solar/Wind Harmer
17.989
972185AH1-677 GEN
Adder
17.917
972187AH1-678 GEN
Adder
8.997
3145893MURPHYS
Solar/Wind Harmer
0.99
3145893MURPHYS
Solar/Wind Harmer
-0.064
3146173TUNIS
Solar/Wind Harmer
-0.035
3146173TUNIS
Solar/Wind Harmer
-0.035
970933AG2-581 GEN
Solar/Wind Harmer
32.706
316487AF1-042 GEN
Solar/Wind Harmer
4.538
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316181AB2-040 GEN
Solar/Wind Harmer
4.712
316426AA2-053 GEN
Solar/Wind Harmer
3.407
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
966811AG1-552 GEN
Solar/Wind Harmer
3.768
3145593CAROLNA
Solar/Wind Harmer
0.278
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145783HORNRTN
Solar/Wind Harmer
3.954
3145783HORNRTN
Solar/Wind Harmer
3.163
3145783HORNRTN
Solar/Wind Harmer
0.988
3145783HORNRTN
Solar/Wind Harmer
0.395
958261AF2-120 GEN
Solar/Wind Harmer
12.878
3145933PARMELE
Solar/Wind Harmer
-0.065
3145933PARMELE
Solar/Wind Harmer
-0.033
970099AG2-077 GEN
Solar/Wind Harmer
40.962
316274AC1-208 GEN
Solar/Wind Harmer
3.495
316077AC2-138 C
Solar/Wind Harmer
0.655
3150341NORNECKC1
Adder
2.894
3150341NORNECKC1
Adder
2.871
3144293JTRSVLE
Adder
0.817
3144293JTRSVLE
Adder
0.688
316447AC1-158 HLD
Solar/Wind Helper
5.533
315651AD1-115 GEN
Solar/Wind Helper
1.131
226929AD2-058 GEN
Solar/Wind Helper
0.127
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.16
237006AB1-125 GEN
Solar/Wind Helper
0.12
237034AC2-136 C
Solar/Wind Helper
0.207
23777901MDS_W4-102
Solar/Wind Helper
0.152
235020AA1-095 C
Solar/Wind Helper
0.045
237001AB1-127_GEN
Solar/Wind Helper
0.385
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237002AB1-128_GEN
Solar/Wind Helper
0.384
235063AE1-101 C2
Solar/Wind Helper
1.425
205916AD1-020 GEN
Solar/Wind Helper
1.648
233933AB2-153 GEN
Solar/Wind Helper
0.225
233944AB2-135 GEN
Solar/Wind Helper
0.57
232424Y1-079 C
Solar/Wind Helper
0.113
233987AB2-037 GEN
Solar/Wind Helper
2.269
233946AB2-136 GEN
Solar/Wind Helper
0.55
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
238175AF1-290_GEN
Solar/Wind Helper
0.118
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.025
NYPJM->LTFIMP_NY
CLTF
4.642
LAGNLTFEXP_LAGN->PJM
CLTF
14.648
LGEELTFEXP_LGEE->PJM
CLTF
3.02
WECLTFEXP_WEC->PJM
CLTF
1.528
AG2-052LTFEXP_AG2-052->PJM
LTF
0.084
AH1-155LTFEXP_AH1-155->PJM
LTF
0.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
40.037
TVALTFEXP_TVA->PJM
CLTF
7.415
CPLELTFEXP_CPLE->PJM
CLTF
17.726
CBM West 2LTFEXP_CBM-W2->PJM
CBM
80.521
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.689
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.805
MECLTFEXP_MEC->PJM
CLTF
7.852
SIGELTFEXP_SIGE->PJM
CLTF
0.243

Details for 8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.18 %
Rating:4124.72 MVA
Rating Type:B
MVA to Mitigate:4338.48
MW Contribution:34.31
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
22.294
3151021BRUNSWICKG1
50/50
10.742
971451AH1-221 GEN
50/50
32.625
315243AE2-183_GT3
50/50
13.474
971629AH1-314 GEN
50/50
11.242
970919AG2-571 GEN
Solar/Wind Harmer
26.837
970087AG2-069 GEN
Solar/Wind Harmer
59.841
316294AC1-161 GEN
Solar/Wind Helper
4.863
316375AC2-012 GEN
Solar/Wind Helper
0.64
3145336SMITFLD
Solar/Wind Helper
0.956
316381AD1-082 GEN
Solar/Wind Helper
1.204
316388AE2-253 GEN
Solar/Wind Helper
0.879
316458AB2-190 GEN2
Solar/Wind Helper
1.317
316159AE1-175 C
Solar/Wind Helper
0.349
316072AD1-144
Solar/Wind Helper
0.258
3146456SLIGO L269
Solar/Wind Helper
0.226
316246AF1-032 C
Solar/Wind Helper
0.255
3151031BRUNSWICKG2
50/50
10.742
970917AG2-570 GEN
Solar/Wind Harmer
67.092
316283AC2-100 C
Solar/Wind Harmer
0.248
315773AC2-141 GEN
Solar/Wind Helper
5.724
3144873MCLAUGH
Solar/Wind Helper
0.006
3144536CHRHLND
Solar/Wind Helper
0.037
315839AE2-212 C
Solar/Wind Helper
0.326
3145336SMITFLD
Solar/Wind Helper
0.096
316478AD1-087 GEN
Solar/Wind Helper
1.138
316486AD2-202 GEN
Solar/Wind Helper
0.333
316382AG1-145 C
Solar/Wind Helper
0.309
3146456SLIGO L269
Solar/Wind Helper
0.226
963041AG1-153 GEN
50/50
21.75
315244AE2-183_ST
50/50
23.295
970673AG2-436 GEN
Solar/Wind Harmer
173.991
970673AG2-436 GEN
Solar/Wind Harmer
115.994
941031AE2-094 GEN
Solar/Wind Harmer
150.205
944011AF1-069 GEN
Solar/Wind Harmer
49.078
970085AG2-068 GEN
Solar/Wind Harmer
39.894
970581AG2-369 GEN
Solar/Wind Harmer
34.309
3143316POE
Solar/Wind Helper
1.005
316369SG1_INVT
Solar/Wind Helper
1.116
316132AB2-190 GEN1
Solar/Wind Helper
1.317
957831AF2-077 GEN
Solar/Wind Helper
0.307
319010AE1-072 C
Solar/Wind Helper
2.564
316305AF2-043 C
Solar/Wind Helper
0.3
3151041BRUNSWICKG3
50/50
10.742
972187AH1-678 GEN
50/50
24.65
315242AE2-183_GT2
50/50
13.474
315241AE2-183_GT1
50/50
13.391
972185AH1-677 GEN
50/50
48.574
970533AG2-339 GEN
50/50
72.493
970531AG2-338 GEN
50/50
28.997
316222AC1-221 GEN
Solar/Wind Harmer
0.514
316036AC1-147 C
Solar/Wind Helper
0.372
316316AC1-027 C
Solar/Wind Helper
0.382
3142956BIRDNECK
Solar/Wind Helper
0.163
316185AD1-033 GEN
Solar/Wind Helper
1.132
316236AE1-162_GEN
Solar/Wind Helper
0.321
3145506HICKORY
Solar/Wind Helper
0.948
3145506HICKORY
Solar/Wind Helper
0.569
3145506HICKORY
Solar/Wind Helper
0.142
316240AF1-291 C
Solar/Wind Helper
0.315
316033AB2-134 GEN
Solar/Wind Helper
0.798
315697AD1-025 GEN
Solar/Wind Helper
2.652
316339AD2-160 GEN
Solar/Wind Helper
0.879
316018AA1-139 ULT2
Solar/Wind Helper
0.985
316017AA1-139 ULT1
Solar/Wind Helper
1.047
3137176SLIGO L2192
Solar/Wind Helper
0.9
3130086AYDLETT
Solar/Wind Helper
0.893
NYPJM->LTFIMP_NY
CLTF
1.845
LAGNLTFEXP_LAGN->PJM
CLTF
11.909
LGEELTFEXP_LGEE->PJM
CLTF
1.979
WECLTFEXP_WEC->PJM
CLTF
1.044
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.406
TVALTFEXP_TVA->PJM
CLTF
5.902
CPLELTFEXP_CPLE->PJM
CLTF
16.693
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.053
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.883
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.119
MECLTFEXP_MEC->PJM
CLTF
5.643
SIGELTFEXP_SIGE->PJM
CLTF
0.166

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.22 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5523.28
MW Contribution:12.54
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
37.955
972195AH1-682 GEN
50/50
4.988
316447AC1-158 HLD
Solar/Wind Harmer
7.651
315673AE1-157 GEN
Solar/Wind Harmer
22.335
957411AF2-035 GEN
Solar/Wind Harmer
13.337
970317AG2-208 GEN
Solar/Wind Harmer
12.967
3142296MT RD221
Adder
0.814
3142366NRTHEST
Adder
0.819
3150691DARBY 3
Adder
17.994
3150701DARBY 4
Adder
17.952
3150681DARBY 2
Adder
17.931
3150671DARBY 1
Adder
17.91
316075AC2-137 C
Solar/Wind Harmer
0.752
3143526WINTERP
Solar/Wind Harmer
-0.144
966871AG1-558 GEN
Solar/Wind Harmer
0.833
966871AG1-558 GEN
Solar/Wind Harmer
0.285
971223AH1-071 GEN
Solar/Wind Harmer
3.455
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
115.935
316240AF1-291 C
Solar/Wind Harmer
0.821
316033AB2-134 GEN
Solar/Wind Harmer
8.7
3150411LDYSMT5
50/50
38.145
3150381LDYSMT2
50/50
36.506
972213AH1-691 GEN
50/50
6.175
972215AH1-692 GEN
50/50
6.175
963051AG1-154 GEN
50/50
4.75
972189AH1-679 GEN
50/50
4.62
316312AB1-027
Solar/Wind Harmer
0.957
316233AE1-074 FULL
Solar/Wind Harmer
0.747
971281AH1-106 GEN
Solar/Wind Harmer
4.513
315697AD1-025 GEN
Solar/Wind Harmer
5.457
971283AH1-107 GEN
Solar/Wind Harmer
4.513
971285AH1-108 GEN
Adder
1.863
315976AC1-164 GENA
Solar/Wind Harmer
29.218
316169AC1-164_GENC
Solar/Wind Harmer
25.241
315975AC1-164 GENB
Solar/Wind Harmer
0.864
316132AB2-190 GEN1
Solar/Wind Harmer
2.743
316369SG1_INVT
Solar/Wind Harmer
4.82
971167AH1-042 GEN
Solar/Wind Harmer
25.921
3142433PROV 92
Adder
0.465
3142433PROV 92
Adder
0.465
972265AH1-717 GEN
Adder
18.482
3151201GRAVEL4
Adder
17.325
3151191GRAVEL3
Adder
17.106
3151211GRAVEL5
Adder
17.106
3143873LANEXA
Solar/Wind Harmer
-0.016
3152261N ANNA2
50/50
14.719
970497AG2-320 GEN
50/50
26.757
3150401LDYSMT4
50/50
38.026
3150371LDYSMT1
50/50
36.744
315051AA1-145 CT1
50/50
2.061
316044AC1-158 PL1
Solar/Wind Harmer
3.479
316450AC1-158 RIC
Solar/Wind Harmer
0.928
966881AG1-559 GEN
Solar/Wind Harmer
0.891
3142416OLDCHRC
Solar/Wind Harmer
2.862
970293AG2-193 GEN
Solar/Wind Harmer
3.499
3143096IRON208
Adder
1.037
971445AH1-216 GEN
Solar/Wind Harmer
16.481
3143316POE
Solar/Wind Harmer
-0.105
957831AF2-077 GEN
Solar/Wind Harmer
0.798
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.267
3151081ELIZAR1
Adder
21.555
3151091ELIZAR2
Adder
21.18
3152611GOSPORTB
Adder
2.993
3152621GOSPORTC
Adder
2.54
3152601GOSPORTA
Adder
2.344
316059AD1-063 C
Solar/Wind Harmer
0.597
315662AE1-191 GEN
Solar/Wind Harmer
3.169
315666AE1-190 GEN
Solar/Wind Harmer
0.792
957601AF2-054 GEN
Solar/Wind Harmer
0.783
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.071
315833AF1-017_GEN
Solar/Wind Harmer
4.958
316349AD2-085 GEN
Solar/Wind Harmer
2.321
316311AC2-079 GEN
Solar/Wind Harmer
13.164
319010AE1-072 C
Solar/Wind Harmer
5.273
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.785
315835AF2-110_GEN
Solar/Wind Harmer
3.238
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.696
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.693
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.062
316315AB2-025 C
Solar/Wind Harmer
0.681
941031AE2-094 GEN
Solar/Wind Harmer
47.207
944011AF1-069 GEN
Solar/Wind Harmer
14.791
315814AE2-033 C
Solar/Wind Harmer
23.412
315611Z1-036_GEN2
Solar/Wind Harmer
6.192
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
52.007
970673AG2-436 GEN
Solar/Wind Harmer
26.333
971967AH1-528 GEN
Solar/Wind Harmer
45.964
315816AE2-034 GEN
Solar/Wind Harmer
1.957
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.788
315733AD1-074 GEN2
Solar/Wind Harmer
4.788
315735AD1-075 GEN1
Solar/Wind Harmer
2.395
965291AG1-394 GEN
Solar/Wind Harmer
2.088
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.247
970085AG2-068 GEN
Solar/Wind Harmer
14.579
970581AG2-369 GEN
Solar/Wind Harmer
12.538
316318V4-068
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.2
961941AG1-037 GEN
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.045
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.509
315607AA1-063A GEN
Solar/Wind Harmer
2.296
316087AB2-174 GEN
Solar/Wind Harmer
3.217
315652AC1-086 GEN
Solar/Wind Harmer
25.21
3137643SOCKMAN
Solar/Wind Harmer
-0.089
316223AC1-118
Solar/Wind Harmer
0.595
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.087
972193AH1-681 GEN
Adder
3.778
972205AH1-687 GEN
Adder
6.629
316164AC1-076 GEN
Solar/Wind Helper
2.423
316411AF1-147_GEN1
Solar/Wind Helper
0.802
316415AF1-147_GEN2
Solar/Wind Helper
0.802
3138216PACIFIC
Solar/Wind Helper
0.039
316236AE1-162_GEN
Solar/Wind Harmer
0.802
316036AC1-147 C
Solar/Wind Harmer
0.713
3150991CHESPKB
Adder
2.462
3150991CHESPKB
Adder
2.403
970657AG2-426 GEN
Solar/Wind Harmer
8.245
970657AG2-426 GEN
Solar/Wind Harmer
1.724
316441AF1-014 GEN
Solar/Wind Harmer
1.778
316316AC1-027 C
Solar/Wind Harmer
0.809
3142956BIRDNECK
Solar/Wind Harmer
1.414
316185AD1-033 GEN
Solar/Wind Harmer
2.777
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.765
316018AA1-139 ULT2
Solar/Wind Harmer
2.239
316017AA1-139 ULT1
Solar/Wind Harmer
2.115
3137176SLIGO L2192
Solar/Wind Harmer
-0.103
3146456SLIGO L269
Solar/Wind Harmer
3.081
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.626
316433W1029_GEN2
Solar/Wind Harmer
4.626
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.88
316487AF1-042 GEN
Solar/Wind Harmer
3.304
315742AE1-103 GEN
Solar/Wind Harmer
2.601
958261AF2-120 GEN
Solar/Wind Harmer
9.593
3146376EDENTON
Solar/Wind Harmer
0.734
3146376EDENTON
Solar/Wind Harmer
0.734
972185AH1-677 GEN
Adder
12.258
972187AH1-678 GEN
Adder
6.15
316077AC2-138 C
Solar/Wind Harmer
0.51
3150341NORNECKC1
Adder
2.253
3150341NORNECKC1
Adder
2.235
316468AD1-105 GEN
Solar/Wind Harmer
2.693
970933AG2-581 GEN
Solar/Wind Harmer
22.379
316065AD1-022 GEN
Solar/Wind Harmer
11.757
3145893MURPHYS
Solar/Wind Harmer
0.65
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.135
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
27.958
316426AA2-053 GEN
Solar/Wind Harmer
2.255
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.497
3145593CAROLNA
Solar/Wind Harmer
0.184
3152251N ANNA1
50/50
14.72
972197AH1-683 GEN
50/50
5.938
972219AH1-694 GEN
50/50
4.275
315052AA1-145 CT2
50/50
2.07
316045AC1-158 PL2
Solar/Wind Harmer
11.13
966881AG1-559 GEN
Solar/Wind Harmer
0.305
3142416OLDCHRC
Solar/Wind Harmer
-0.073
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.037
3143526WINTERP
Solar/Wind Harmer
-0.144
3150851SPRUNCC
Adder
1.139
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
117.047
316159AE1-175 C
Solar/Wind Harmer
0.729
970129AG2-093 GEN
Solar/Wind Harmer
6.189
316458AB2-190 GEN2
Solar/Wind Harmer
2.743
315671AE2-027_GEN
Solar/Wind Harmer
20.317
971069AG2-661 GEN
Solar/Wind Harmer
4.278
971647AH1-324 GEN
Solar/Wind Harmer
13.453
971317AH1-138 GEN
Solar/Wind Harmer
3.36
3142433PROV 92
Solar/Wind Harmer
-0.107
3142433PROV 92
Adder
0.465
3142433PROV 92
Adder
0.465
3138126ROCKLANDING
Solar/Wind Harmer
0.082
961611AG1-000B GEN
Solar/Wind Harmer
13.243
3151171GRAVELC
Adder
2.532
316294AC1-161 GEN
Solar/Wind Harmer
8.649
3145336SMITFLD
Solar/Wind Harmer
-0.106
970659AG2-427 GEN
Solar/Wind Harmer
14.051
944591AF1-124 GEN
Solar/Wind Harmer
120.601
316375AC2-012 GEN
Solar/Wind Harmer
9.14
3150981CHESPKA
Adder
2.935
316381AD1-082 GEN
Solar/Wind Harmer
2.423
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.101
3141843SHACKLE
Adder
1.199
970661AG2-428 GEN
Solar/Wind Harmer
27.972
316072AD1-144
Solar/Wind Harmer
0.53
939411AE1-173 GEN
Solar/Wind Harmer
130.97
316388AE2-253 GEN
Solar/Wind Harmer
1.765
940641AE2-051 GEN
Solar/Wind Harmer
24.52
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.527
316093AE2-104_GEN
Solar/Wind Harmer
7.532
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
961951AG1-038 GEN
Solar/Wind Harmer
3.304
315800Z1-036_GEN1
Solar/Wind Harmer
6.192
962861AG1-135 GEN
Solar/Wind Harmer
9.316
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.736
3141726DUNNSVL
Solar/Wind Harmer
-0.097
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.675
3150351NORNECKC2
Adder
2.144
3143336POWHATN
Solar/Wind Harmer
2.796
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.856
970919AG2-571 GEN
Solar/Wind Harmer
7.412
316023GEN1_S
Solar/Wind Harmer
1.575
970087AG2-069 GEN
Solar/Wind Harmer
21.869
3145893MURPHYS
Solar/Wind Harmer
-0.093
3145893MURPHYS
Solar/Wind Harmer
0.692
316337AD2-073 GEN
Solar/Wind Harmer
0.622
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.557
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
316336AC2-165 C
Solar/Wind Harmer
3.909
316011AB1-132 GEN
Solar/Wind Harmer
4.688
962571AG1-106 GEN
Solar/Wind Harmer
3.221
3145823KELFORD
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
69.896
316174AB2-169 GEN
Solar/Wind Harmer
3.442
316190AA2-174 GEN
Solar/Wind Harmer
0.274
971795AH1-408 GEN
Solar/Wind Harmer
16.655
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.769
315693AD1-088 GEN
Solar/Wind Harmer
10.955
962491AG1-098 GEN
Solar/Wind Harmer
14.605
3144293JTRSVLE
Adder
0.564
972277AH1-723 GEN
Adder
98.538
316254AC1-120 GEN1
Solar/Wind Helper
1.567
316006AB2-029 C
Solar/Wind Helper
0.151
316212AC1-099_GEN
Solar/Wind Harmer
0.232
3143096IRON208
Adder
1.016
3150861SPRUNCD
Adder
1.139
316473AC1-191 GEN
Solar/Wind Harmer
2.981
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.068
316382AG1-145 C
Solar/Wind Harmer
0.819
970129AG2-093 GEN
Solar/Wind Harmer
15.278
315778AD1-151 GEN
Solar/Wind Harmer
23.422
965281AG1-393 GEN
Solar/Wind Harmer
3.379
315839AE2-212 C
Solar/Wind Harmer
0.814
3142433PROV 92
Adder
0.465
3142433PROV 92
Adder
0.465
3150921YORKTN3
Adder
6.008
3144216WINCHST
Adder
0.901
961611AG1-000B GEN
Solar/Wind Harmer
5.651
3151221GRAVEL6
Adder
17.305
3151171GRAVELC
Adder
3.329
315773AC2-141 GEN
Solar/Wind Harmer
11.187
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.635
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.49
944581AF1-123 GEN
Solar/Wind Harmer
120.168
944601AF1-125 GEN
Solar/Wind Harmer
118.293
3151101ELIZAR3
Adder
21.831
316083AB2-161 GEN
Solar/Wind Harmer
4.288
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.349
3141843SHACKLE
Adder
1.199
316203AE2-005 GEN
Solar/Wind Harmer
11.119
970661AG2-428 GEN
Solar/Wind Harmer
4.957
316280AD1-041 GEN
Solar/Wind Harmer
1.981
316156AD2-030 GEN
Solar/Wind Harmer
0.699
3141873WAN 176
Solar/Wind Harmer
3.107
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.18
316320Y1-086
Solar/Wind Harmer
1.512
316435W1029_GEN3
Solar/Wind Harmer
4.626
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.741
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.314
970009AG2-005 GEN
Solar/Wind Harmer
3.135
316404AE1-155 C
Solar/Wind Harmer
4.775
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.61
3150351NORNECKC2
Adder
2.18
971781AH1-399 GEN
Solar/Wind Harmer
1.49
971157AH1-035 GEN
Solar/Wind Harmer
2.97
315737AD1-076 GEN
Solar/Wind Harmer
4.5
3156081AA2-088 GEN
Solar/Wind Harmer
7.673
316313AB2-026
Solar/Wind Harmer
0.635
316258AE1-075 C
Solar/Wind Harmer
0.572
316405AF2-144 C
Solar/Wind Harmer
0.604
3143336POWHATN
Solar/Wind Harmer
2.377
3146206CASHIE
Solar/Wind Harmer
-0.023
970917AG2-570 GEN
Solar/Wind Harmer
58.551
316365GEN2_N
Solar/Wind Harmer
1.575
3145893MURPHYS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.311
961681AG1-008 GEN
Solar/Wind Harmer
18.311
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.107
316463AE2-346 GEN
Solar/Wind Harmer
0.372
316140AB2-099
Solar/Wind Harmer
0.155
962331AG1-082 GEN
Solar/Wind Harmer
2.872
966621AG1-532 GEN
Solar/Wind Harmer
0.461
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.022
313506AB2-031 GEN
Solar/Wind Harmer
1.807
3142666NORTHAMPTON
Solar/Wind Harmer
-0.022
316317KELFORD C
Solar/Wind Harmer
1.056
3145823KELFORD
Solar/Wind Harmer
-0.022
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.866
316486AD2-202 GEN
Solar/Wind Harmer
0.546
3144293JTRSVLE
Adder
0.564
972255AH1-712 GEN
Adder
84.56
3141316ARNOLDS
Adder
0.333
3150331BIRCHWDA
Adder
21.898
316170AC1-121 GEN2
Solar/Wind Helper
0.522
3141196NOKESVL
Solar/Wind Helper
1.252
316210AC1-098 GEN
Solar/Wind Harmer
0.418
3145783HORNRTN
Solar/Wind Harmer
2.619
3145783HORNRTN
Solar/Wind Harmer
2.095
3145783HORNRTN
Solar/Wind Harmer
0.655
3145783HORNRTN
Solar/Wind Harmer
0.262
3145796HORNRTN
Solar/Wind Harmer
-0.066
3144293JTRSVLE
Adder
0.564
3144293JTRSVLE
Adder
0.475
315651AD1-115 GEN
Solar/Wind Helper
1.13
NYPJM->LTFIMP_NY
CLTF
3.231
LAGNLTFEXP_LAGN->PJM
CLTF
8.031
LGEELTFEXP_LGEE->PJM
CLTF
1.33
WECLTFEXP_WEC->PJM
CLTF
0.642
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.091
TVALTFEXP_TVA->PJM
CLTF
4.071
CPLELTFEXP_CPLE->PJM
CLTF
11.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.416
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.339
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.845
MECLTFEXP_MEC->PJM
CLTF
3.617
SIGELTFEXP_SIGE->PJM
CLTF
0.11

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: 57302_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57302_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.51 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5437.63
MW Contribution:12.7
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
38.579
3150381LDYSMT2
50/50
36.921
972213AH1-691 GEN
50/50
6.246
972215AH1-692 GEN
50/50
6.246
963051AG1-154 GEN
50/50
4.804
972189AH1-679 GEN
50/50
4.673
316312AB1-027
Solar/Wind Harmer
0.968
316233AE1-074 FULL
Solar/Wind Harmer
0.756
971281AH1-106 GEN
Solar/Wind Harmer
4.569
971283AH1-107 GEN
Solar/Wind Harmer
4.569
971285AH1-108 GEN
Adder
1.886
315976AC1-164 GENA
Solar/Wind Harmer
29.566
316169AC1-164_GENC
Solar/Wind Harmer
25.542
315975AC1-164 GENB
Solar/Wind Harmer
0.875
316132AB2-190 GEN1
Solar/Wind Harmer
2.777
316369SG1_INVT
Solar/Wind Harmer
4.879
971167AH1-042 GEN
Solar/Wind Harmer
26.236
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
972265AH1-717 GEN
Adder
18.71
3151201GRAVEL4
Adder
17.539
3151191GRAVEL3
Adder
17.317
3151211GRAVEL5
Adder
17.317
971445AH1-216 GEN
Solar/Wind Harmer
16.686
3143873LANEXA
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.106
957831AF2-077 GEN
Solar/Wind Harmer
0.808
3138283WHITEMARSH
Solar/Wind Harmer
0.042
316314AB2-024 C
Solar/Wind Harmer
2.295
3151081ELIZAR1
Adder
21.824
3151091ELIZAR2
Adder
21.445
3152611GOSPORTB
Adder
3.031
3152621GOSPORTC
Adder
2.572
3152601GOSPORTA
Adder
2.373
316059AD1-063 C
Solar/Wind Harmer
0.604
315662AE1-191 GEN
Solar/Wind Harmer
3.208
315666AE1-190 GEN
Solar/Wind Harmer
0.802
957601AF2-054 GEN
Solar/Wind Harmer
0.793
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.235
315833AF1-017_GEN
Solar/Wind Harmer
5.02
316349AD2-085 GEN
Solar/Wind Harmer
2.351
316311AC2-079 GEN
Solar/Wind Harmer
13.329
319010AE1-072 C
Solar/Wind Harmer
5.339
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.795
315835AF2-110_GEN
Solar/Wind Harmer
3.279
3141913WHIT STONE
Solar/Wind Harmer
-0.026
3152261N ANNA2
50/50
14.959
970497AG2-320 GEN
50/50
27.052
3150401LDYSMT4
50/50
38.459
3150371LDYSMT1
50/50
37.162
315051AA1-145 CT1
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.901
3142416OLDCHRC
Solar/Wind Harmer
2.895
970293AG2-193 GEN
Solar/Wind Harmer
3.54
3143096IRON208
Adder
1.049
3143096IRON208
Adder
1.028
3150861SPRUNCD
Adder
1.153
316473AC1-191 GEN
Solar/Wind Harmer
3.016
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.105
3152251N ANNA1
50/50
14.961
972197AH1-683 GEN
50/50
6.005
972219AH1-694 GEN
50/50
4.324
315052AA1-145 CT2
50/50
2.094
966881AG1-559 GEN
Solar/Wind Harmer
0.308
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.049
3143526WINTERP
Solar/Wind Harmer
-0.145
3150851SPRUNCC
Adder
1.153
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
118.454
316159AE1-175 C
Solar/Wind Harmer
0.738
970129AG2-093 GEN
Solar/Wind Harmer
6.264
316458AB2-190 GEN2
Solar/Wind Harmer
2.777
315671AE2-027_GEN
Solar/Wind Harmer
20.567
971069AG2-661 GEN
Solar/Wind Harmer
4.33
971647AH1-324 GEN
Solar/Wind Harmer
13.619
971317AH1-138 GEN
Solar/Wind Harmer
3.401
3142433PROV 92
Solar/Wind Harmer
-0.108
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3138126ROCKLANDING
Solar/Wind Harmer
0.083
961611AG1-000B GEN
Solar/Wind Harmer
13.406
3151171GRAVELC
Adder
2.563
316294AC1-161 GEN
Solar/Wind Harmer
8.757
3145336SMITFLD
Solar/Wind Harmer
-0.107
970659AG2-427 GEN
Solar/Wind Harmer
14.226
944591AF1-124 GEN
Solar/Wind Harmer
122.112
316375AC2-012 GEN
Solar/Wind Harmer
9.255
3150981CHESPKA
Adder
2.972
316381AD1-082 GEN
Solar/Wind Harmer
2.453
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.139
3141843SHACKLE
Adder
1.214
970661AG2-428 GEN
Solar/Wind Harmer
28.322
316072AD1-144
Solar/Wind Harmer
0.537
939411AE1-173 GEN
Solar/Wind Harmer
132.654
316388AE2-253 GEN
Solar/Wind Harmer
1.787
940641AE2-051 GEN
Solar/Wind Harmer
24.838
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.534
316093AE2-104_GEN
Solar/Wind Harmer
7.627
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
961951AG1-038 GEN
Solar/Wind Harmer
3.345
315800Z1-036_GEN1
Solar/Wind Harmer
6.27
962861AG1-135 GEN
Solar/Wind Harmer
9.433
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.745
3141726DUNNSVL
Solar/Wind Harmer
-0.099
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.964
3150351NORNECKC2
Adder
2.172
3143336POWHATN
Solar/Wind Harmer
2.825
970919AG2-571 GEN
Solar/Wind Harmer
7.509
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
316023GEN1_S
Solar/Wind Harmer
1.596
970087AG2-069 GEN
Solar/Wind Harmer
22.157
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.701
316337AD2-073 GEN
Solar/Wind Harmer
0.63
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.947
316011AB1-132 GEN
Solar/Wind Harmer
4.749
962571AG1-106 GEN
Solar/Wind Harmer
3.263
3145823KELFORD
Solar/Wind Harmer
-0.023
957481AF2-042 GEN
Solar/Wind Harmer
70.778
316174AB2-169 GEN
Solar/Wind Harmer
3.486
316190AA2-174 GEN
Solar/Wind Harmer
0.278
971795AH1-408 GEN
Solar/Wind Harmer
16.865
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.791
313526AB2-022
Solar/Wind Harmer
0.705
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.702
3146396TANGLEW
Solar/Wind Harmer
0.479
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.2
316315AB2-025 C
Solar/Wind Harmer
0.689
941031AE2-094 GEN
Solar/Wind Harmer
47.824
944011AF1-069 GEN
Solar/Wind Harmer
14.985
315814AE2-033 C
Solar/Wind Harmer
23.711
315611Z1-036_GEN2
Solar/Wind Harmer
6.27
970673AG2-436 GEN
Solar/Wind Harmer
52.688
970673AG2-436 GEN
Solar/Wind Harmer
26.677
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.561
315816AE2-034 GEN
Solar/Wind Harmer
1.982
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.849
315733AD1-074 GEN2
Solar/Wind Harmer
4.849
315735AD1-075 GEN1
Solar/Wind Harmer
2.425
965291AG1-394 GEN
Solar/Wind Harmer
2.115
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
970085AG2-068 GEN
Solar/Wind Harmer
14.772
970581AG2-369 GEN
Solar/Wind Harmer
12.703
316318V4-068
Solar/Wind Harmer
0.588
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.203
961941AG1-037 GEN
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.515
315607AA1-063A GEN
Solar/Wind Harmer
2.325
316087AB2-174 GEN
Solar/Wind Harmer
3.258
315652AC1-086 GEN
Solar/Wind Harmer
25.536
3137643SOCKMAN
Solar/Wind Harmer
-0.09
316223AC1-118
Solar/Wind Harmer
0.603
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.817
972205AH1-687 GEN
Adder
6.664
316164AC1-076 GEN
Solar/Wind Helper
1.975
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.393
315693AD1-088 GEN
Solar/Wind Harmer
11.089
962491AG1-098 GEN
Solar/Wind Harmer
14.782
316212AC1-099_GEN
Solar/Wind Harmer
1.902
3146293MARTNCO
Solar/Wind Harmer
0.135
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
99.54
316045AC1-158 PL2
Solar/Wind Helper
7.073
316006AB2-029 C
Solar/Wind Helper
0.147
316254AC1-120 GEN1
Solar/Wind Helper
1.333
316382AG1-145 C
Solar/Wind Harmer
0.829
970129AG2-093 GEN
Solar/Wind Harmer
15.465
315778AD1-151 GEN
Solar/Wind Harmer
23.709
965281AG1-393 GEN
Solar/Wind Harmer
3.42
315839AE2-212 C
Solar/Wind Harmer
0.824
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3150921YORKTN3
Adder
6.081
3144216WINCHST
Adder
0.912
961611AG1-000B GEN
Solar/Wind Harmer
5.72
3151221GRAVEL6
Adder
17.519
3151171GRAVELC
Adder
3.371
315773AC2-141 GEN
Solar/Wind Harmer
11.326
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.842
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.521
944581AF1-123 GEN
Solar/Wind Harmer
121.674
944601AF1-125 GEN
Solar/Wind Harmer
119.775
3151101ELIZAR3
Adder
22.104
316083AB2-161 GEN
Solar/Wind Harmer
4.341
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.378
3141843SHACKLE
Adder
1.214
316203AE2-005 GEN
Solar/Wind Harmer
11.255
970661AG2-428 GEN
Solar/Wind Harmer
5.019
316280AD1-041 GEN
Solar/Wind Harmer
2.005
316156AD2-030 GEN
Solar/Wind Harmer
0.708
3141873WAN 176
Solar/Wind Harmer
3.145
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.22
316320Y1-086
Solar/Wind Harmer
1.532
316435W1029_GEN3
Solar/Wind Harmer
4.685
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
962971AG1-146 GEN
Solar/Wind Harmer
4.8
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.393
970009AG2-005 GEN
Solar/Wind Harmer
3.175
316404AE1-155 C
Solar/Wind Harmer
4.836
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.643
3150351NORNECKC2
Adder
2.208
971781AH1-399 GEN
Solar/Wind Harmer
1.509
971157AH1-035 GEN
Solar/Wind Harmer
3.007
315737AD1-076 GEN
Solar/Wind Harmer
4.557
3156081AA2-088 GEN
Solar/Wind Harmer
7.771
316313AB2-026
Solar/Wind Harmer
0.642
316258AE1-075 C
Solar/Wind Harmer
0.578
316405AF2-144 C
Solar/Wind Harmer
0.61
3143336POWHATN
Solar/Wind Harmer
2.401
970917AG2-570 GEN
Solar/Wind Harmer
59.322
3146206CASHIE
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
1.596
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.545
961681AG1-008 GEN
Solar/Wind Harmer
18.545
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.147
316463AE2-346 GEN
Solar/Wind Harmer
0.377
316140AB2-099
Solar/Wind Harmer
0.157
962331AG1-082 GEN
Solar/Wind Harmer
2.909
966621AG1-532 GEN
Solar/Wind Harmer
0.467
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.83
316317KELFORD C
Solar/Wind Harmer
1.069
3145823KELFORD
Solar/Wind Harmer
-0.023
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.889
316486AD2-202 GEN
Solar/Wind Harmer
0.553
316210AC1-098 GEN
Solar/Wind Harmer
3.424
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.725
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
85.42
3141316ARNOLDS
Adder
0.338
3150331BIRCHWDA
Adder
22.263
316044AC1-158 PL1
Solar/Wind Helper
2.209
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.444
3150391LDYSMT3
50/50
38.387
972195AH1-682 GEN
50/50
5.045
315673AE1-157 GEN
Solar/Wind Harmer
22.589
957411AF2-035 GEN
Solar/Wind Harmer
13.49
970317AG2-208 GEN
Solar/Wind Harmer
13.115
3142296MT RD221
Adder
0.824
3142366NRTHEST
Adder
0.828
3150691DARBY 3
Adder
18.207
3150701DARBY 4
Adder
18.165
3150681DARBY 2
Adder
18.143
3150671DARBY 1
Adder
18.122
316075AC2-137 C
Solar/Wind Harmer
0.761
3143526WINTERP
Solar/Wind Harmer
-0.145
966871AG1-558 GEN
Solar/Wind Harmer
0.843
966871AG1-558 GEN
Solar/Wind Harmer
0.288
971223AH1-071 GEN
Solar/Wind Harmer
3.498
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
117.349
316240AF1-291 C
Solar/Wind Harmer
0.831
316033AB2-134 GEN
Solar/Wind Harmer
8.807
315697AD1-025 GEN
Solar/Wind Harmer
5.524
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316036AC1-147 C
Solar/Wind Harmer
0.721
3150991CHESPKB
Adder
2.493
3150991CHESPKB
Adder
2.433
970657AG2-426 GEN
Solar/Wind Harmer
8.348
970657AG2-426 GEN
Solar/Wind Harmer
1.746
316316AC1-027 C
Solar/Wind Harmer
0.819
316441AF1-014 GEN
Solar/Wind Harmer
1.799
3142956BIRDNECK
Solar/Wind Harmer
1.432
316185AD1-033 GEN
Solar/Wind Harmer
2.811
3145506HICKORY
Solar/Wind Harmer
-0.106
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.787
316018AA1-139 ULT2
Solar/Wind Harmer
2.267
316017AA1-139 ULT1
Solar/Wind Harmer
2.142
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.119
3130086AYDLETT
Solar/Wind Harmer
-0.105
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.685
316433W1029_GEN2
Solar/Wind Harmer
4.685
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3144356SAPONY
Solar/Wind Harmer
0.891
316487AF1-042 GEN
Solar/Wind Harmer
3.345
315742AE1-103 GEN
Solar/Wind Harmer
2.634
958261AF2-120 GEN
Solar/Wind Harmer
9.714
3146376EDENTON
Solar/Wind Harmer
0.744
3146376EDENTON
Solar/Wind Harmer
0.744
972185AH1-677 GEN
Adder
12.419
972187AH1-678 GEN
Adder
6.23
316077AC2-138 C
Solar/Wind Harmer
0.516
3150341NORNECKC1
Adder
2.281
3150341NORNECKC1
Adder
2.263
316468AD1-105 GEN
Solar/Wind Harmer
2.727
970933AG2-581 GEN
Solar/Wind Harmer
22.667
316065AD1-022 GEN
Solar/Wind Harmer
11.908
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
3.176
970099AG2-077 GEN
Solar/Wind Harmer
28.311
316426AA2-053 GEN
Solar/Wind Harmer
2.284
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
0.187
3145783HORNRTN
Solar/Wind Harmer
2.652
3145783HORNRTN
Solar/Wind Harmer
2.122
3145783HORNRTN
Solar/Wind Harmer
0.663
3145783HORNRTN
Solar/Wind Harmer
0.265
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.336
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
316447AC1-158 HLD
Solar/Wind Helper
4.863
315651AD1-115 GEN
Solar/Wind Helper
0.986
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.382
LAGNLTFEXP_LAGN->PJM
CLTF
8.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.482
WECLTFEXP_WEC->PJM
CLTF
0.67
TVALTFEXP_TVA->PJM
CLTF
4.164
CPLELTFEXP_CPLE->PJM
CLTF
11.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.551
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.391
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.181
MECLTFEXP_MEC->PJM
CLTF
3.746
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: XT573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.51 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5437.5
MW Contribution:12.7
Bus #Bus NameTypeMW Contribution
3150411LDYSMT5
50/50
38.577
3150381LDYSMT2
50/50
36.92
972213AH1-691 GEN
50/50
6.245
972215AH1-692 GEN
50/50
6.245
963051AG1-154 GEN
50/50
4.804
972189AH1-679 GEN
50/50
4.673
316312AB1-027
Solar/Wind Harmer
0.968
316233AE1-074 FULL
Solar/Wind Harmer
0.756
971281AH1-106 GEN
Solar/Wind Harmer
4.569
971283AH1-107 GEN
Solar/Wind Harmer
4.569
971285AH1-108 GEN
Adder
1.886
315976AC1-164 GENA
Solar/Wind Harmer
29.565
316169AC1-164_GENC
Solar/Wind Harmer
25.541
315975AC1-164 GENB
Solar/Wind Harmer
0.875
316132AB2-190 GEN1
Solar/Wind Harmer
2.777
316369SG1_INVT
Solar/Wind Harmer
4.879
971167AH1-042 GEN
Solar/Wind Harmer
26.235
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
972265AH1-717 GEN
Adder
18.709
3151201GRAVEL4
Adder
17.539
3151191GRAVEL3
Adder
17.317
3151211GRAVEL5
Adder
17.317
971445AH1-216 GEN
Solar/Wind Harmer
16.685
3143873LANEXA
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.106
957831AF2-077 GEN
Solar/Wind Harmer
0.807
3138283WHITEMARSH
Solar/Wind Harmer
0.042
316314AB2-024 C
Solar/Wind Harmer
2.295
3151081ELIZAR1
Adder
21.824
3151091ELIZAR2
Adder
21.445
3152611GOSPORTB
Adder
3.031
3152621GOSPORTC
Adder
2.572
3152601GOSPORTA
Adder
2.373
316059AD1-063 C
Solar/Wind Harmer
0.604
315662AE1-191 GEN
Solar/Wind Harmer
3.208
315666AE1-190 GEN
Solar/Wind Harmer
0.802
957601AF2-054 GEN
Solar/Wind Harmer
0.793
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.234
315833AF1-017_GEN
Solar/Wind Harmer
5.02
316349AD2-085 GEN
Solar/Wind Harmer
2.35
316311AC2-079 GEN
Solar/Wind Harmer
13.328
319010AE1-072 C
Solar/Wind Harmer
5.338
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.795
315835AF2-110_GEN
Solar/Wind Harmer
3.279
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.705
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.702
3146396TANGLEW
Solar/Wind Harmer
0.479
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.2
316315AB2-025 C
Solar/Wind Harmer
0.689
941031AE2-094 GEN
Solar/Wind Harmer
47.822
944011AF1-069 GEN
Solar/Wind Harmer
14.984
315814AE2-033 C
Solar/Wind Harmer
23.71
315611Z1-036_GEN2
Solar/Wind Harmer
6.27
970673AG2-436 GEN
Solar/Wind Harmer
52.685
970673AG2-436 GEN
Solar/Wind Harmer
26.676
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.56
315816AE2-034 GEN
Solar/Wind Harmer
1.982
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.849
315733AD1-074 GEN2
Solar/Wind Harmer
4.849
315735AD1-075 GEN1
Solar/Wind Harmer
2.425
965291AG1-394 GEN
Solar/Wind Harmer
2.115
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.378
970085AG2-068 GEN
Solar/Wind Harmer
14.771
970581AG2-369 GEN
Solar/Wind Harmer
12.703
316318V4-068
Solar/Wind Harmer
0.588
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.203
961941AG1-037 GEN
Solar/Wind Harmer
0.175
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.515
315607AA1-063A GEN
Solar/Wind Harmer
2.325
316087AB2-174 GEN
Solar/Wind Harmer
3.258
315652AC1-086 GEN
Solar/Wind Harmer
25.535
3137643SOCKMAN
Solar/Wind Harmer
-0.09
316223AC1-118
Solar/Wind Harmer
0.603
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.817
972205AH1-687 GEN
Adder
6.664
316164AC1-076 GEN
Solar/Wind Helper
1.975
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.393
3152251N ANNA1
50/50
14.959
972197AH1-683 GEN
50/50
6.005
972219AH1-694 GEN
50/50
4.324
315052AA1-145 CT2
50/50
2.094
966881AG1-559 GEN
Solar/Wind Harmer
0.308
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.049
3143526WINTERP
Solar/Wind Harmer
-0.145
3150851SPRUNCC
Adder
1.152
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
118.449
316159AE1-175 C
Solar/Wind Harmer
0.738
970129AG2-093 GEN
Solar/Wind Harmer
6.264
316458AB2-190 GEN2
Solar/Wind Harmer
2.777
315671AE2-027_GEN
Solar/Wind Harmer
20.566
971069AG2-661 GEN
Solar/Wind Harmer
4.33
971647AH1-324 GEN
Solar/Wind Harmer
13.618
971317AH1-138 GEN
Solar/Wind Harmer
3.401
3142433PROV 92
Solar/Wind Harmer
-0.108
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3138126ROCKLANDING
Solar/Wind Harmer
0.083
961611AG1-000B GEN
Solar/Wind Harmer
13.406
3151171GRAVELC
Adder
2.563
316294AC1-161 GEN
Solar/Wind Harmer
8.757
3145336SMITFLD
Solar/Wind Harmer
-0.107
970659AG2-427 GEN
Solar/Wind Harmer
14.225
944591AF1-124 GEN
Solar/Wind Harmer
122.107
316375AC2-012 GEN
Solar/Wind Harmer
9.254
3150981CHESPKA
Adder
2.972
316381AD1-082 GEN
Solar/Wind Harmer
2.453
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.139
3141843SHACKLE
Adder
1.214
970661AG2-428 GEN
Solar/Wind Harmer
28.32
316072AD1-144
Solar/Wind Harmer
0.537
939411AE1-173 GEN
Solar/Wind Harmer
132.648
316388AE2-253 GEN
Solar/Wind Harmer
1.787
940641AE2-051 GEN
Solar/Wind Harmer
24.837
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.534
316093AE2-104_GEN
Solar/Wind Harmer
7.627
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
961951AG1-038 GEN
Solar/Wind Harmer
3.345
315800Z1-036_GEN1
Solar/Wind Harmer
6.27
962861AG1-135 GEN
Solar/Wind Harmer
9.433
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.745
3141726DUNNSVL
Solar/Wind Harmer
-0.099
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.963
3150351NORNECKC2
Adder
2.172
3143336POWHATN
Solar/Wind Harmer
2.825
970919AG2-571 GEN
Solar/Wind Harmer
7.509
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.93
316023GEN1_S
Solar/Wind Harmer
1.596
970087AG2-069 GEN
Solar/Wind Harmer
22.156
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.701
316337AD2-073 GEN
Solar/Wind Harmer
0.63
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.589
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.947
316011AB1-132 GEN
Solar/Wind Harmer
4.749
962571AG1-106 GEN
Solar/Wind Harmer
3.263
3145823KELFORD
Solar/Wind Harmer
-0.023
957481AF2-042 GEN
Solar/Wind Harmer
70.776
316174AB2-169 GEN
Solar/Wind Harmer
3.486
316190AA2-174 GEN
Solar/Wind Harmer
0.278
971795AH1-408 GEN
Solar/Wind Harmer
16.865
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.791
315693AD1-088 GEN
Solar/Wind Harmer
11.089
962491AG1-098 GEN
Solar/Wind Harmer
14.782
316212AC1-099_GEN
Solar/Wind Harmer
1.902
3146293MARTNCO
Solar/Wind Harmer
0.135
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
99.541
316045AC1-158 PL2
Solar/Wind Helper
7.073
316006AB2-029 C
Solar/Wind Helper
0.147
316254AC1-120 GEN1
Solar/Wind Helper
1.332
3152261N ANNA2
50/50
14.958
970497AG2-320 GEN
50/50
27.051
3150401LDYSMT4
50/50
38.457
3150371LDYSMT1
50/50
37.16
315051AA1-145 CT1
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.901
3142416OLDCHRC
Solar/Wind Harmer
2.895
970293AG2-193 GEN
Solar/Wind Harmer
3.54
3143096IRON208
Adder
1.049
3143096IRON208
Adder
1.028
3150861SPRUNCD
Adder
1.152
316473AC1-191 GEN
Solar/Wind Harmer
3.016
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.105
316382AG1-145 C
Solar/Wind Harmer
0.829
970129AG2-093 GEN
Solar/Wind Harmer
15.465
315778AD1-151 GEN
Solar/Wind Harmer
23.708
965281AG1-393 GEN
Solar/Wind Harmer
3.42
315839AE2-212 C
Solar/Wind Harmer
0.824
3142433PROV 92
Adder
0.47
3142433PROV 92
Adder
0.47
3150921YORKTN3
Adder
6.081
3144216WINCHST
Adder
0.912
961611AG1-000B GEN
Solar/Wind Harmer
5.72
3151221GRAVEL6
Adder
17.518
3151171GRAVELC
Adder
3.37
315773AC2-141 GEN
Solar/Wind Harmer
11.326
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.841
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.521
944581AF1-123 GEN
Solar/Wind Harmer
121.668
944601AF1-125 GEN
Solar/Wind Harmer
119.77
3151101ELIZAR3
Adder
22.103
316083AB2-161 GEN
Solar/Wind Harmer
4.341
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.378
3141843SHACKLE
Adder
1.214
316203AE2-005 GEN
Solar/Wind Harmer
11.254
970661AG2-428 GEN
Solar/Wind Harmer
5.019
316280AD1-041 GEN
Solar/Wind Harmer
2.005
316156AD2-030 GEN
Solar/Wind Harmer
0.708
3141873WAN 176
Solar/Wind Harmer
3.145
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.22
316320Y1-086
Solar/Wind Harmer
1.531
316435W1029_GEN3
Solar/Wind Harmer
4.684
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
962971AG1-146 GEN
Solar/Wind Harmer
4.8
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.393
970009AG2-005 GEN
Solar/Wind Harmer
3.174
316404AE1-155 C
Solar/Wind Harmer
4.835
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.643
3150351NORNECKC2
Adder
2.208
971781AH1-399 GEN
Solar/Wind Harmer
1.509
971157AH1-035 GEN
Solar/Wind Harmer
3.007
315737AD1-076 GEN
Solar/Wind Harmer
4.557
3156081AA2-088 GEN
Solar/Wind Harmer
7.771
316313AB2-026
Solar/Wind Harmer
0.642
316258AE1-075 C
Solar/Wind Harmer
0.578
316405AF2-144 C
Solar/Wind Harmer
0.61
3143336POWHATN
Solar/Wind Harmer
2.401
970917AG2-570 GEN
Solar/Wind Harmer
59.32
3146206CASHIE
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
1.596
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.545
961681AG1-008 GEN
Solar/Wind Harmer
18.545
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.147
316463AE2-346 GEN
Solar/Wind Harmer
0.377
316140AB2-099
Solar/Wind Harmer
0.157
962331AG1-082 GEN
Solar/Wind Harmer
2.909
966621AG1-532 GEN
Solar/Wind Harmer
0.467
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.83
316317KELFORD C
Solar/Wind Harmer
1.069
3145823KELFORD
Solar/Wind Harmer
-0.023
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.889
316486AD2-202 GEN
Solar/Wind Harmer
0.553
316210AC1-098 GEN
Solar/Wind Harmer
3.424
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.725
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
85.421
3141316ARNOLDS
Adder
0.338
3150331BIRCHWDA
Adder
22.262
316044AC1-158 PL1
Solar/Wind Helper
2.209
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.444
3150391LDYSMT3
50/50
38.385
972195AH1-682 GEN
50/50
5.044
315673AE1-157 GEN
Solar/Wind Harmer
22.588
957411AF2-035 GEN
Solar/Wind Harmer
13.489
970317AG2-208 GEN
Solar/Wind Harmer
13.114
3142296MT RD221
Adder
0.823
3142366NRTHEST
Adder
0.828
3150691DARBY 3
Adder
18.206
3150701DARBY 4
Adder
18.164
3150681DARBY 2
Adder
18.143
3150671DARBY 1
Adder
18.121
316075AC2-137 C
Solar/Wind Harmer
0.761
3143526WINTERP
Solar/Wind Harmer
-0.145
966871AG1-558 GEN
Solar/Wind Harmer
0.843
966871AG1-558 GEN
Solar/Wind Harmer
0.288
971223AH1-071 GEN
Solar/Wind Harmer
3.498
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
117.344
316240AF1-291 C
Solar/Wind Harmer
0.831
316033AB2-134 GEN
Solar/Wind Harmer
8.807
315697AD1-025 GEN
Solar/Wind Harmer
5.523
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316036AC1-147 C
Solar/Wind Harmer
0.721
3150991CHESPKB
Adder
2.493
3150991CHESPKB
Adder
2.433
970657AG2-426 GEN
Solar/Wind Harmer
8.347
970657AG2-426 GEN
Solar/Wind Harmer
1.746
316316AC1-027 C
Solar/Wind Harmer
0.819
316441AF1-014 GEN
Solar/Wind Harmer
1.799
3142956BIRDNECK
Solar/Wind Harmer
1.432
316185AD1-033 GEN
Solar/Wind Harmer
2.811
3145506HICKORY
Solar/Wind Harmer
-0.106
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.787
316018AA1-139 ULT2
Solar/Wind Harmer
2.267
316017AA1-139 ULT1
Solar/Wind Harmer
2.142
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.119
3130086AYDLETT
Solar/Wind Harmer
-0.105
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.684
316433W1029_GEN2
Solar/Wind Harmer
4.684
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3144356SAPONY
Solar/Wind Harmer
0.891
316487AF1-042 GEN
Solar/Wind Harmer
3.345
315742AE1-103 GEN
Solar/Wind Harmer
2.633
958261AF2-120 GEN
Solar/Wind Harmer
9.713
3146376EDENTON
Solar/Wind Harmer
0.744
3146376EDENTON
Solar/Wind Harmer
0.744
972185AH1-677 GEN
Adder
12.418
972187AH1-678 GEN
Adder
6.23
316077AC2-138 C
Solar/Wind Harmer
0.516
3150341NORNECKC1
Adder
2.281
3150341NORNECKC1
Adder
2.263
316468AD1-105 GEN
Solar/Wind Harmer
2.727
970933AG2-581 GEN
Solar/Wind Harmer
22.666
316065AD1-022 GEN
Solar/Wind Harmer
11.907
3145893MURPHYS
Solar/Wind Harmer
0.659
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
3.175
970099AG2-077 GEN
Solar/Wind Harmer
28.31
316426AA2-053 GEN
Solar/Wind Harmer
2.283
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
0.187
3145783HORNRTN
Solar/Wind Harmer
2.652
3145783HORNRTN
Solar/Wind Harmer
2.122
3145783HORNRTN
Solar/Wind Harmer
0.663
3145783HORNRTN
Solar/Wind Harmer
0.265
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.336
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
316447AC1-158 HLD
Solar/Wind Helper
4.863
315651AD1-115 GEN
Solar/Wind Helper
0.986
NYPJM->LTFIMP_NY
CLTF
3.205
LGEELTFEXP_LGEE->PJM
CLTF
1.382
LAGNLTFEXP_LAGN->PJM
CLTF
8.217
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.481
WECLTFEXP_WEC->PJM
CLTF
0.67
TVALTFEXP_TVA->PJM
CLTF
4.164
CPLELTFEXP_CPLE->PJM
CLTF
11.613
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.181
MECLTFEXP_MEC->PJM
CLTF
3.747
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.24 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5423.67
MW Contribution:12.65
Bus #Bus NameTypeMW Contribution
3150391LDYSMT3
50/50
38.213
972195AH1-682 GEN
50/50
5.022
315673AE1-157 GEN
Solar/Wind Harmer
22.49
957411AF2-035 GEN
Solar/Wind Harmer
13.431
970317AG2-208 GEN
Solar/Wind Harmer
13.058
3142296MT RD221
Adder
0.82
3142366NRTHEST
Adder
0.825
3150691DARBY 3
Adder
18.133
3150701DARBY 4
Adder
18.091
3150681DARBY 2
Adder
18.07
3150671DARBY 1
Adder
18.049
316075AC2-137 C
Solar/Wind Harmer
0.758
3143526WINTERP
Solar/Wind Harmer
-0.145
966871AG1-558 GEN
Solar/Wind Harmer
0.839
966871AG1-558 GEN
Solar/Wind Harmer
0.287
971223AH1-071 GEN
Solar/Wind Harmer
3.483
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
116.855
316240AF1-291 C
Solar/Wind Harmer
0.828
316033AB2-134 GEN
Solar/Wind Harmer
8.77
315697AD1-025 GEN
Solar/Wind Harmer
5.5
3152251N ANNA1
50/50
14.826
972197AH1-683 GEN
50/50
5.978
972219AH1-694 GEN
50/50
4.304
315052AA1-145 CT2
50/50
2.085
966881AG1-559 GEN
Solar/Wind Harmer
0.307
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.045
3143526WINTERP
Solar/Wind Harmer
-0.145
3150851SPRUNCC
Adder
1.148
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
117.965
316159AE1-175 C
Solar/Wind Harmer
0.735
970129AG2-093 GEN
Solar/Wind Harmer
6.238
316458AB2-190 GEN2
Solar/Wind Harmer
2.765
315671AE2-027_GEN
Solar/Wind Harmer
20.479
971069AG2-661 GEN
Solar/Wind Harmer
4.312
971647AH1-324 GEN
Solar/Wind Harmer
13.561
971317AH1-138 GEN
Solar/Wind Harmer
3.386
3142433PROV 92
Solar/Wind Harmer
-0.108
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3138126ROCKLANDING
Solar/Wind Harmer
0.083
3150411LDYSMT5
50/50
38.405
3150381LDYSMT2
50/50
36.755
972213AH1-691 GEN
50/50
6.217
972215AH1-692 GEN
50/50
6.217
963051AG1-154 GEN
50/50
4.783
972189AH1-679 GEN
50/50
4.654
316312AB1-027
Solar/Wind Harmer
0.964
316233AE1-074 FULL
Solar/Wind Harmer
0.753
971281AH1-106 GEN
Solar/Wind Harmer
4.55
971283AH1-107 GEN
Solar/Wind Harmer
4.55
971285AH1-108 GEN
Adder
1.878
315976AC1-164 GENA
Solar/Wind Harmer
29.445
316169AC1-164_GENC
Solar/Wind Harmer
25.437
315975AC1-164 GENB
Solar/Wind Harmer
0.871
316132AB2-190 GEN1
Solar/Wind Harmer
2.765
316369SG1_INVT
Solar/Wind Harmer
4.859
971167AH1-042 GEN
Solar/Wind Harmer
26.126
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
972265AH1-717 GEN
Adder
18.63
3151201GRAVEL4
Adder
17.465
3151191GRAVEL3
Adder
17.243
3151211GRAVEL5
Adder
17.243
971445AH1-216 GEN
Solar/Wind Harmer
16.614
3143873LANEXA
Solar/Wind Harmer
-0.016
3143316POE
Solar/Wind Harmer
-0.105
957831AF2-077 GEN
Solar/Wind Harmer
0.804
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.285
3151081ELIZAR1
Adder
21.73
3151091ELIZAR2
Adder
21.353
3152611GOSPORTB
Adder
3.018
3152621GOSPORTC
Adder
2.561
3152601GOSPORTA
Adder
2.363
316059AD1-063 C
Solar/Wind Harmer
0.601
315662AE1-191 GEN
Solar/Wind Harmer
3.194
315666AE1-190 GEN
Solar/Wind Harmer
0.799
957601AF2-054 GEN
Solar/Wind Harmer
0.789
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.177
315833AF1-017_GEN
Solar/Wind Harmer
4.998
316349AD2-085 GEN
Solar/Wind Harmer
2.341
316311AC2-079 GEN
Solar/Wind Harmer
13.272
319010AE1-072 C
Solar/Wind Harmer
5.316
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.791
315835AF2-110_GEN
Solar/Wind Harmer
3.265
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.702
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.699
3146396TANGLEW
Solar/Wind Harmer
0.477
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.152
316315AB2-025 C
Solar/Wind Harmer
0.686
941031AE2-094 GEN
Solar/Wind Harmer
47.608
944011AF1-069 GEN
Solar/Wind Harmer
14.917
315814AE2-033 C
Solar/Wind Harmer
23.609
315611Z1-036_GEN2
Solar/Wind Harmer
6.244
970673AG2-436 GEN
Solar/Wind Harmer
52.454
970673AG2-436 GEN
Solar/Wind Harmer
26.559
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.364
315816AE2-034 GEN
Solar/Wind Harmer
1.974
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.83
315733AD1-074 GEN2
Solar/Wind Harmer
4.83
315735AD1-075 GEN1
Solar/Wind Harmer
2.416
965291AG1-394 GEN
Solar/Wind Harmer
2.107
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.337
970085AG2-068 GEN
Solar/Wind Harmer
14.709
970581AG2-369 GEN
Solar/Wind Harmer
12.65
316318V4-068
Solar/Wind Harmer
0.586
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.202
961941AG1-037 GEN
Solar/Wind Harmer
0.174
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.514
315607AA1-063A GEN
Solar/Wind Harmer
2.316
316087AB2-174 GEN
Solar/Wind Harmer
3.247
315652AC1-086 GEN
Solar/Wind Harmer
25.438
3137643SOCKMAN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.009
316223AC1-118
Solar/Wind Harmer
0.6
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.818
972205AH1-687 GEN
Adder
6.726
316164AC1-076 GEN
Solar/Wind Helper
1.947
316411AF1-147_GEN1
Solar/Wind Helper
0.8
316415AF1-147_GEN2
Solar/Wind Helper
0.8
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.38
961611AG1-000B GEN
Solar/Wind Harmer
13.349
3151171GRAVELC
Adder
2.552
316294AC1-161 GEN
Solar/Wind Harmer
8.719
3145336SMITFLD
Solar/Wind Harmer
-0.107
970659AG2-427 GEN
Solar/Wind Harmer
14.165
944591AF1-124 GEN
Solar/Wind Harmer
121.581
316375AC2-012 GEN
Solar/Wind Harmer
9.215
3150981CHESPKA
Adder
2.959
316381AD1-082 GEN
Solar/Wind Harmer
2.442
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.126
3141843SHACKLE
Adder
1.209
970661AG2-428 GEN
Solar/Wind Harmer
28.2
316072AD1-144
Solar/Wind Harmer
0.535
939411AE1-173 GEN
Solar/Wind Harmer
132.05
316388AE2-253 GEN
Solar/Wind Harmer
1.779
940641AE2-051 GEN
Solar/Wind Harmer
24.723
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.531
316093AE2-104_GEN
Solar/Wind Harmer
7.594
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
961951AG1-038 GEN
Solar/Wind Harmer
3.331
315800Z1-036_GEN1
Solar/Wind Harmer
6.244
962861AG1-135 GEN
Solar/Wind Harmer
9.392
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.742
3141726DUNNSVL
Solar/Wind Harmer
-0.098
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.869
3150351NORNECKC2
Adder
2.162
3143336POWHATN
Solar/Wind Harmer
2.825
970919AG2-571 GEN
Solar/Wind Harmer
7.477
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.907
316023GEN1_S
Solar/Wind Harmer
1.589
970087AG2-069 GEN
Solar/Wind Harmer
22.064
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.698
316337AD2-073 GEN
Solar/Wind Harmer
0.628
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.58
3146263WOODLND
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.951
3145963POPLR C
Solar/Wind Harmer
-0.023
316011AB1-132 GEN
Solar/Wind Harmer
4.731
962571AG1-106 GEN
Solar/Wind Harmer
3.25
3145823KELFORD
Solar/Wind Harmer
-0.023
957481AF2-042 GEN
Solar/Wind Harmer
70.553
316174AB2-169 GEN
Solar/Wind Harmer
3.473
316190AA2-174 GEN
Solar/Wind Harmer
0.277
971795AH1-408 GEN
Solar/Wind Harmer
16.81
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.785
315693AD1-088 GEN
Solar/Wind Harmer
11.061
962491AG1-098 GEN
Solar/Wind Harmer
14.747
316212AC1-099_GEN
Solar/Wind Harmer
1.895
3146293MARTNCO
Solar/Wind Harmer
0.134
3144293JTRSVLE
Adder
0.57
972277AH1-723 GEN
Adder
99.579
316045AC1-158 PL2
Solar/Wind Helper
7.066
316006AB2-029 C
Solar/Wind Helper
0.145
316254AC1-120 GEN1
Solar/Wind Helper
1.294
3152261N ANNA2
50/50
14.825
970497AG2-320 GEN
50/50
26.932
3150401LDYSMT4
50/50
38.285
3150371LDYSMT1
50/50
36.994
315051AA1-145 CT1
50/50
2.076
966881AG1-559 GEN
Solar/Wind Harmer
0.897
3142416OLDCHRC
Solar/Wind Harmer
2.884
970293AG2-193 GEN
Solar/Wind Harmer
3.526
3143096IRON208
Adder
1.045
3143096IRON208
Adder
1.024
3150861SPRUNCD
Adder
1.148
316473AC1-191 GEN
Solar/Wind Harmer
3.004
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.092
316382AG1-145 C
Solar/Wind Harmer
0.825
970129AG2-093 GEN
Solar/Wind Harmer
15.4
315778AD1-151 GEN
Solar/Wind Harmer
23.609
965281AG1-393 GEN
Solar/Wind Harmer
3.406
315839AE2-212 C
Solar/Wind Harmer
0.82
3142433PROV 92
Adder
0.469
3142433PROV 92
Adder
0.469
3150921YORKTN3
Adder
6.055
3144216WINCHST
Adder
0.908
961611AG1-000B GEN
Solar/Wind Harmer
5.696
3151221GRAVEL6
Adder
17.444
3151171GRAVELC
Adder
3.356
315773AC2-141 GEN
Solar/Wind Harmer
11.277
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.769
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.51
944581AF1-123 GEN
Solar/Wind Harmer
121.145
944601AF1-125 GEN
Solar/Wind Harmer
119.254
3151101ELIZAR3
Adder
22.008
316083AB2-161 GEN
Solar/Wind Harmer
4.322
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.368
3141843SHACKLE
Adder
1.209
316203AE2-005 GEN
Solar/Wind Harmer
11.207
970661AG2-428 GEN
Solar/Wind Harmer
4.998
316280AD1-041 GEN
Solar/Wind Harmer
1.996
316156AD2-030 GEN
Solar/Wind Harmer
0.705
3141873WAN 176
Solar/Wind Harmer
3.132
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.206
316320Y1-086
Solar/Wind Harmer
1.525
316435W1029_GEN3
Solar/Wind Harmer
4.665
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.779
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.366
970009AG2-005 GEN
Solar/Wind Harmer
3.161
3146376EDENTON
Solar/Wind Harmer
-0.025
316404AE1-155 C
Solar/Wind Harmer
4.814
315614AA2-178 GEN
Solar/Wind Harmer
2.632
3150351NORNECKC2
Adder
2.198
971781AH1-399 GEN
Solar/Wind Harmer
1.502
971157AH1-035 GEN
Solar/Wind Harmer
2.995
315737AD1-076 GEN
Solar/Wind Harmer
4.539
3156081AA2-088 GEN
Solar/Wind Harmer
7.74
316313AB2-026
Solar/Wind Harmer
0.642
316258AE1-075 C
Solar/Wind Harmer
0.578
316405AF2-144 C
Solar/Wind Harmer
0.61
3143336POWHATN
Solar/Wind Harmer
2.401
970917AG2-570 GEN
Solar/Wind Harmer
59.071
3146206CASHIE
Solar/Wind Harmer
-0.024
316365GEN2_N
Solar/Wind Harmer
1.589
3145893MURPHYS
Solar/Wind Harmer
0.164
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.473
961681AG1-008 GEN
Solar/Wind Harmer
18.473
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.134
316463AE2-346 GEN
Solar/Wind Harmer
0.375
316140AB2-099
Solar/Wind Harmer
0.156
962331AG1-082 GEN
Solar/Wind Harmer
2.898
966621AG1-532 GEN
Solar/Wind Harmer
0.465
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.823
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.065
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.022
3141906WESTMOR
Solar/Wind Harmer
-0.009
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.884
316486AD2-202 GEN
Solar/Wind Harmer
0.552
316210AC1-098 GEN
Solar/Wind Harmer
3.412
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.715
3144293JTRSVLE
Adder
0.57
972255AH1-712 GEN
Adder
85.454
3141316ARNOLDS
Adder
0.336
3150331BIRCHWDA
Adder
22.127
316044AC1-158 PL1
Solar/Wind Helper
2.207
316450AC1-158 RIC
Solar/Wind Helper
0.589
3141196NOKESVL
Solar/Wind Helper
1.25
316170AC1-121 GEN2
Solar/Wind Helper
0.431
316236AE1-162_GEN
Solar/Wind Harmer
0.809
316036AC1-147 C
Solar/Wind Harmer
0.718
3150991CHESPKB
Adder
2.482
3150991CHESPKB
Adder
2.423
970657AG2-426 GEN
Solar/Wind Harmer
8.312
970657AG2-426 GEN
Solar/Wind Harmer
1.738
316441AF1-014 GEN
Solar/Wind Harmer
1.792
316316AC1-027 C
Solar/Wind Harmer
0.816
3142956BIRDNECK
Solar/Wind Harmer
1.426
316185AD1-033 GEN
Solar/Wind Harmer
2.799
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.779
316018AA1-139 ULT2
Solar/Wind Harmer
2.258
316017AA1-139 ULT1
Solar/Wind Harmer
2.133
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.106
3130086AYDLETT
Solar/Wind Harmer
-0.105
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.665
316433W1029_GEN2
Solar/Wind Harmer
4.665
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.888
316487AF1-042 GEN
Solar/Wind Harmer
3.331
315742AE1-103 GEN
Solar/Wind Harmer
2.623
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
958261AF2-120 GEN
Solar/Wind Harmer
9.671
972185AH1-677 GEN
Adder
12.364
972187AH1-678 GEN
Adder
6.203
316077AC2-138 C
Solar/Wind Harmer
0.514
3150341NORNECKC1
Adder
2.271
3150341NORNECKC1
Adder
2.253
316468AD1-105 GEN
Solar/Wind Harmer
2.715
970933AG2-581 GEN
Solar/Wind Harmer
22.578
316065AD1-022 GEN
Solar/Wind Harmer
11.86
3145893MURPHYS
Solar/Wind Harmer
0.656
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.164
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
28.221
316426AA2-053 GEN
Solar/Wind Harmer
2.275
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.52
3145593CAROLNA
Solar/Wind Harmer
0.186
3145783HORNRTN
Solar/Wind Harmer
2.643
3145783HORNRTN
Solar/Wind Harmer
2.114
3145783HORNRTN
Solar/Wind Harmer
0.661
3145783HORNRTN
Solar/Wind Harmer
0.264
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.327
3144293JTRSVLE
Adder
0.57
3144293JTRSVLE
Adder
0.48
316447AC1-158 HLD
Solar/Wind Helper
4.858
315651AD1-115 GEN
Solar/Wind Helper
0.961
NYPJM->LTFIMP_NY
CLTF
3.205
LAGNLTFEXP_LAGN->PJM
CLTF
8.214
LGEELTFEXP_LGEE->PJM
CLTF
1.386
WECLTFEXP_WEC->PJM
CLTF
0.672
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.425
TVALTFEXP_TVA->PJM
CLTF
4.163
CPLELTFEXP_CPLE->PJM
CLTF
11.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.571
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.182
MECLTFEXP_MEC->PJM
CLTF
3.753
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8CHANCE 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.86 %
Rating:5011.0 MVA
Rating Type:C
MVA to Mitigate:5404.77
MW Contribution:12.59
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
14.763
972197AH1-683 GEN
50/50
5.958
3152261N ANNA2
50/50
14.761
970497AG2-320 GEN
50/50
26.842
3150401LDYSMT4
50/50
38.156
3150371LDYSMT1
50/50
36.869
315051AA1-145 CT1
50/50
2.068
966881AG1-559 GEN
Solar/Wind Harmer
0.894
3142416OLDCHRC
Solar/Wind Harmer
2.872
970293AG2-193 GEN
Solar/Wind Harmer
3.512
3143096IRON208
Adder
1.04
3143096IRON208
Adder
1.02
3150861SPRUNCD
Adder
1.143
316473AC1-191 GEN
Solar/Wind Harmer
2.992
3142946ENON
Solar/Wind Harmer
-0.009
970133AG2-095 GEN
Solar/Wind Harmer
3.08
316382AG1-145 C
Solar/Wind Harmer
0.822
970129AG2-093 GEN
Solar/Wind Harmer
15.336
315778AD1-151 GEN
Solar/Wind Harmer
23.511
965281AG1-393 GEN
Solar/Wind Harmer
3.392
315839AE2-212 C
Solar/Wind Harmer
0.817
3142433PROV 92
Adder
0.467
3142433PROV 92
Adder
0.467
3150921YORKTN3
Adder
6.03
3144216WINCHST
Adder
0.904
961611AG1-000B GEN
Solar/Wind Harmer
5.672
3151221GRAVEL6
Adder
17.372
3151171GRAVELC
Adder
3.342
315773AC2-141 GEN
Solar/Wind Harmer
11.23
3145336SMITFLD
Solar/Wind Harmer
-0.011
315813AE1-149 C
Solar/Wind Harmer
16.699
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.5
944581AF1-123 GEN
Solar/Wind Harmer
120.633
944601AF1-125 GEN
Solar/Wind Harmer
118.751
3151101ELIZAR3
Adder
21.915
316083AB2-161 GEN
Solar/Wind Harmer
4.304
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3141766HARMONY
Solar/Wind Harmer
2.358
3141843SHACKLE
Adder
1.204
316203AE2-005 GEN
Solar/Wind Harmer
11.162
970661AG2-428 GEN
Solar/Wind Harmer
4.976
316280AD1-041 GEN
Solar/Wind Harmer
1.988
316156AD2-030 GEN
Solar/Wind Harmer
0.702
3141873WAN 176
Solar/Wind Harmer
3.119
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.192
316320Y1-086
Solar/Wind Harmer
1.518
316435W1029_GEN3
Solar/Wind Harmer
4.645
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.76
3145273HOLLAND
Solar/Wind Harmer
-0.019
316484AD2-074 GEN
Solar/Wind Harmer
6.34
970009AG2-005 GEN
Solar/Wind Harmer
3.148
316404AE1-155 C
Solar/Wind Harmer
4.795
3146376EDENTON
Solar/Wind Harmer
-0.025
315614AA2-178 GEN
Solar/Wind Harmer
2.621
3150351NORNECKC2
Adder
2.19
971781AH1-399 GEN
Solar/Wind Harmer
1.496
971157AH1-035 GEN
Solar/Wind Harmer
2.982
315737AD1-076 GEN
Solar/Wind Harmer
4.519
3156081AA2-088 GEN
Solar/Wind Harmer
7.706
316313AB2-026
Solar/Wind Harmer
0.638
316258AE1-075 C
Solar/Wind Harmer
0.575
316405AF2-144 C
Solar/Wind Harmer
0.606
3143336POWHATN
Solar/Wind Harmer
2.387
3146206CASHIE
Solar/Wind Harmer
-0.023
970917AG2-570 GEN
Solar/Wind Harmer
58.807
316365GEN2_N
Solar/Wind Harmer
1.582
3145893MURPHYS
Solar/Wind Harmer
0.163
3145893MURPHYS
Solar/Wind Harmer
-0.023
957521AF2-046 GEN
Solar/Wind Harmer
18.392
961681AG1-008 GEN
Solar/Wind Harmer
18.392
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.121
316463AE2-346 GEN
Solar/Wind Harmer
0.374
316140AB2-099
Solar/Wind Harmer
0.156
962331AG1-082 GEN
Solar/Wind Harmer
2.885
966621AG1-532 GEN
Solar/Wind Harmer
0.463
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.815
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.061
3145823KELFORD
Solar/Wind Harmer
-0.022
3150411LDYSMT5
50/50
38.275
3150381LDYSMT2
50/50
36.631
972213AH1-691 GEN
50/50
6.196
972215AH1-692 GEN
50/50
6.196
963051AG1-154 GEN
50/50
4.767
972189AH1-679 GEN
50/50
4.636
316312AB1-027
Solar/Wind Harmer
0.96
316233AE1-074 FULL
Solar/Wind Harmer
0.75
971281AH1-106 GEN
Solar/Wind Harmer
4.53
971283AH1-107 GEN
Solar/Wind Harmer
4.53
971285AH1-108 GEN
Adder
1.87
315976AC1-164 GENA
Solar/Wind Harmer
29.326
316169AC1-164_GENC
Solar/Wind Harmer
25.335
315975AC1-164 GENB
Solar/Wind Harmer
0.868
316132AB2-190 GEN1
Solar/Wind Harmer
2.754
316369SG1_INVT
Solar/Wind Harmer
4.838
971167AH1-042 GEN
Solar/Wind Harmer
26.02
3142433PROV 92
Adder
0.467
3142433PROV 92
Adder
0.467
972265AH1-717 GEN
Adder
18.552
3151201GRAVEL4
Adder
17.392
3151191GRAVEL3
Adder
17.171
3151211GRAVEL5
Adder
17.171
3143873LANEXA
Solar/Wind Harmer
-0.016
971445AH1-216 GEN
Solar/Wind Harmer
16.544
3143316POE
Solar/Wind Harmer
-0.105
957831AF2-077 GEN
Solar/Wind Harmer
0.801
3138283WHITEMARSH
Solar/Wind Harmer
0.041
316314AB2-024 C
Solar/Wind Harmer
2.276
3151081ELIZAR1
Adder
21.638
3151091ELIZAR2
Adder
21.262
3152611GOSPORTB
Adder
3.005
3152621GOSPORTC
Adder
2.55
3152601GOSPORTA
Adder
2.353
316059AD1-063 C
Solar/Wind Harmer
0.599
315662AE1-191 GEN
Solar/Wind Harmer
3.181
315666AE1-190 GEN
Solar/Wind Harmer
0.795
957601AF2-054 GEN
Solar/Wind Harmer
0.786
3141873WAN 176
Solar/Wind Harmer
-0.005
957871AF2-081 GEN
Solar/Wind Harmer
13.122
315833AF1-017_GEN
Solar/Wind Harmer
4.977
316349AD2-085 GEN
Solar/Wind Harmer
2.331
316311AC2-079 GEN
Solar/Wind Harmer
13.215
319010AE1-072 C
Solar/Wind Harmer
5.293
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.788
315835AF2-110_GEN
Solar/Wind Harmer
3.251
3141913WHIT STONE
Solar/Wind Harmer
-0.026
313526AB2-022
Solar/Wind Harmer
0.699
3138133OCRAN
Solar/Wind Harmer
-0.008
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.696
3146396TANGLEW
Solar/Wind Harmer
0.475
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
962981AG1-147 GEN
Solar/Wind Harmer
11.107
316315AB2-025 C
Solar/Wind Harmer
0.683
941031AE2-094 GEN
Solar/Wind Harmer
47.398
944011AF1-069 GEN
Solar/Wind Harmer
14.851
315814AE2-033 C
Solar/Wind Harmer
23.507
315611Z1-036_GEN2
Solar/Wind Harmer
6.217
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
52.222
970673AG2-436 GEN
Solar/Wind Harmer
26.441
971967AH1-528 GEN
Solar/Wind Harmer
46.156
315816AE2-034 GEN
Solar/Wind Harmer
1.965
3141813NORNECK
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.809
315733AD1-074 GEN2
Solar/Wind Harmer
4.809
315735AD1-075 GEN1
Solar/Wind Harmer
2.405
965291AG1-394 GEN
Solar/Wind Harmer
2.097
3146206CASHIE
Solar/Wind Harmer
-0.023
970601AG2-382 GEN
Solar/Wind Harmer
10.292
970085AG2-068 GEN
Solar/Wind Harmer
14.643
970581AG2-369 GEN
Solar/Wind Harmer
12.593
316318V4-068
Solar/Wind Harmer
0.584
3145893MURPHYS
Solar/Wind Harmer
-0.063
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145513AHOSKIE
Solar/Wind Harmer
0.201
961941AG1-037 GEN
Solar/Wind Harmer
0.173
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146043SEABORD
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.511
315607AA1-063A GEN
Solar/Wind Harmer
2.306
316087AB2-174 GEN
Solar/Wind Harmer
3.232
315652AC1-086 GEN
Solar/Wind Harmer
25.325
3137643SOCKMAN
Solar/Wind Harmer
-0.089
316223AC1-118
Solar/Wind Harmer
0.598
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.088
972193AH1-681 GEN
Adder
3.799
972205AH1-687 GEN
Adder
6.668
316164AC1-076 GEN
Solar/Wind Helper
2.414
316411AF1-147_GEN1
Solar/Wind Helper
0.796
316415AF1-147_GEN2
Solar/Wind Helper
0.796
3138216PACIFIC
Solar/Wind Helper
0.039
970831AG2-522 GEN
Solar/Wind Harmer
4.359
972219AH1-694 GEN
50/50
4.29
315052AA1-145 CT2
50/50
2.077
966881AG1-559 GEN
Solar/Wind Harmer
0.306
3142416OLDCHRC
Solar/Wind Harmer
-0.074
3142416OLDCHRC
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.04
3143526WINTERP
Solar/Wind Harmer
-0.144
3150851SPRUNCC
Adder
1.143
3142543TWELFTH
Solar/Wind Harmer
-0.003
3143226MDLTHAN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
117.48
316159AE1-175 C
Solar/Wind Harmer
0.732
970129AG2-093 GEN
Solar/Wind Harmer
6.212
316458AB2-190 GEN2
Solar/Wind Harmer
2.754
315671AE2-027_GEN
Solar/Wind Harmer
20.394
971069AG2-661 GEN
Solar/Wind Harmer
4.294
971647AH1-324 GEN
Solar/Wind Harmer
13.504
971317AH1-138 GEN
Solar/Wind Harmer
3.372
3142433PROV 92
Solar/Wind Harmer
-0.107
3142433PROV 92
Adder
0.467
3142433PROV 92
Adder
0.467
3138126ROCKLANDING
Solar/Wind Harmer
0.083
961611AG1-000B GEN
Solar/Wind Harmer
13.293
3151171GRAVELC
Adder
2.542
316294AC1-161 GEN
Solar/Wind Harmer
8.683
3145336SMITFLD
Solar/Wind Harmer
-0.106
970659AG2-427 GEN
Solar/Wind Harmer
14.105
944591AF1-124 GEN
Solar/Wind Harmer
121.068
316375AC2-012 GEN
Solar/Wind Harmer
9.176
3150981CHESPKA
Adder
2.946
316381AD1-082 GEN
Solar/Wind Harmer
2.432
3141766HARMONY
Solar/Wind Harmer
-0.005
971777AH1-397 GEN
Solar/Wind Harmer
3.113
3141843SHACKLE
Adder
1.204
970661AG2-428 GEN
Solar/Wind Harmer
28.081
316072AD1-144
Solar/Wind Harmer
0.532
939411AE1-173 GEN
Solar/Wind Harmer
131.481
316388AE2-253 GEN
Solar/Wind Harmer
1.772
940641AE2-051 GEN
Solar/Wind Harmer
24.616
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.529
316093AE2-104_GEN
Solar/Wind Harmer
7.562
3138133OCRAN
Solar/Wind Harmer
-0.015
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
961951AG1-038 GEN
Solar/Wind Harmer
3.317
315800Z1-036_GEN1
Solar/Wind Harmer
6.217
962861AG1-135 GEN
Solar/Wind Harmer
9.354
3130156CHOWAN
Solar/Wind Harmer
-0.025
964211AG1-282 GEN
Solar/Wind Harmer
0.739
3141726DUNNSVL
Solar/Wind Harmer
-0.098
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.771
3150351NORNECKC2
Adder
2.153
3143336POWHATN
Solar/Wind Harmer
2.808
3146206CASHIE
Solar/Wind Harmer
-0.023
971547AH1-271 GEN
Solar/Wind Harmer
5.881
970919AG2-571 GEN
Solar/Wind Harmer
7.444
316023GEN1_S
Solar/Wind Harmer
1.582
970087AG2-069 GEN
Solar/Wind Harmer
21.965
3145893MURPHYS
Solar/Wind Harmer
-0.093
3145893MURPHYS
Solar/Wind Harmer
0.695
316337AD2-073 GEN
Solar/Wind Harmer
0.625
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.568
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316336AC2-165 C
Solar/Wind Harmer
3.927
316011AB1-132 GEN
Solar/Wind Harmer
4.71
962571AG1-106 GEN
Solar/Wind Harmer
3.236
3145823KELFORD
Solar/Wind Harmer
-0.022
957481AF2-042 GEN
Solar/Wind Harmer
70.215
3150391LDYSMT3
50/50
38.084
972195AH1-682 GEN
50/50
5.005
315673AE1-157 GEN
Solar/Wind Harmer
22.411
957411AF2-035 GEN
Solar/Wind Harmer
13.383
970317AG2-208 GEN
Solar/Wind Harmer
13.012
3142296MT RD221
Adder
0.817
3142366NRTHEST
Adder
0.822
3150691DARBY 3
Adder
18.059
3150701DARBY 4
Adder
18.017
3150681DARBY 2
Adder
17.996
3150671DARBY 1
Adder
17.975
316075AC2-137 C
Solar/Wind Harmer
0.755
3143526WINTERP
Solar/Wind Harmer
-0.144
966871AG1-558 GEN
Solar/Wind Harmer
0.836
966871AG1-558 GEN
Solar/Wind Harmer
0.286
971223AH1-071 GEN
Solar/Wind Harmer
3.468
3142946ENON
Solar/Wind Harmer
-0.003
944641AF1-129 GEN
Adder
116.369
316240AF1-291 C
Solar/Wind Harmer
0.824
316033AB2-134 GEN
Solar/Wind Harmer
8.733
315697AD1-025 GEN
Solar/Wind Harmer
5.477
3141906WESTMOR
Solar/Wind Harmer
-0.009
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.875
316236AE1-162_GEN
Solar/Wind Harmer
0.805
316036AC1-147 C
Solar/Wind Harmer
0.715
3150991CHESPKB
Adder
2.472
3150991CHESPKB
Adder
2.412
970657AG2-426 GEN
Solar/Wind Harmer
8.277
970657AG2-426 GEN
Solar/Wind Harmer
1.731
316441AF1-014 GEN
Solar/Wind Harmer
1.785
316316AC1-027 C
Solar/Wind Harmer
0.812
3142956BIRDNECK
Solar/Wind Harmer
1.42
316185AD1-033 GEN
Solar/Wind Harmer
2.787
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.772
316018AA1-139 ULT2
Solar/Wind Harmer
2.248
316017AA1-139 ULT1
Solar/Wind Harmer
2.124
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.093
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.645
316433W1029_GEN2
Solar/Wind Harmer
4.645
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144356SAPONY
Solar/Wind Harmer
0.884
316487AF1-042 GEN
Solar/Wind Harmer
3.317
315742AE1-103 GEN
Solar/Wind Harmer
2.611
958261AF2-120 GEN
Solar/Wind Harmer
9.632
3146376EDENTON
Solar/Wind Harmer
0.737
3146376EDENTON
Solar/Wind Harmer
0.737
972185AH1-677 GEN
Adder
12.31
972187AH1-678 GEN
Adder
6.176
316077AC2-138 C
Solar/Wind Harmer
0.512
3150341NORNECKC1
Adder
2.262
3150341NORNECKC1
Adder
2.244
316468AD1-105 GEN
Solar/Wind Harmer
2.704
970933AG2-581 GEN
Solar/Wind Harmer
22.474
316065AD1-022 GEN
Solar/Wind Harmer
11.808
3145893MURPHYS
Solar/Wind Harmer
0.653
3145893MURPHYS
Solar/Wind Harmer
-0.042
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.15
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
970099AG2-077 GEN
Solar/Wind Harmer
28.086
316426AA2-053 GEN
Solar/Wind Harmer
2.265
3145593CAROLNA
Solar/Wind Harmer
-0.022
3145593CAROLNA
Solar/Wind Harmer
-0.022
966811AG1-552 GEN
Solar/Wind Harmer
2.509
3145593CAROLNA
Solar/Wind Harmer
0.185
3145783HORNRTN
Solar/Wind Harmer
2.631
3145783HORNRTN
Solar/Wind Harmer
2.105
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145933PARMELE
Solar/Wind Harmer
-0.043
3145933PARMELE
Solar/Wind Harmer
-0.022
316274AC1-208 GEN
Solar/Wind Harmer
2.317
3144293JTRSVLE
Adder
0.566
3144293JTRSVLE
Adder
0.477
316447AC1-158 HLD
Solar/Wind Helper
4.715
315651AD1-115 GEN
Solar/Wind Helper
1.124
316174AB2-169 GEN
Solar/Wind Harmer
3.457
316190AA2-174 GEN
Solar/Wind Harmer
0.275
971795AH1-408 GEN
Solar/Wind Harmer
16.732
3145783HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
3147043LAWRENC
Adder
1.777
315693AD1-088 GEN
Solar/Wind Harmer
11.006
962491AG1-098 GEN
Solar/Wind Harmer
14.673
316212AC1-099_GEN
Solar/Wind Harmer
1.887
3146293MARTNCO
Solar/Wind Harmer
0.134
3144293JTRSVLE
Adder
0.566
972277AH1-723 GEN
Adder
99.081
316045AC1-158 PL2
Solar/Wind Helper
6.858
316254AC1-120 GEN1
Solar/Wind Helper
1.559
316006AB2-029 C
Solar/Wind Helper
0.15
316486AD2-202 GEN
Solar/Wind Harmer
0.549
316210AC1-098 GEN
Solar/Wind Harmer
3.396
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.702
3144293JTRSVLE
Adder
0.566
972255AH1-712 GEN
Adder
85.026
3141316ARNOLDS
Adder
0.335
3150331BIRCHWDA
Adder
22.053
316044AC1-158 PL1
Solar/Wind Helper
2.142
316450AC1-158 RIC
Solar/Wind Helper
0.571
316170AC1-121 GEN2
Solar/Wind Helper
0.52
3141196NOKESVL
Solar/Wind Helper
1.245
NYPJM->LTFIMP_NY
CLTF
3.186
LGEELTFEXP_LGEE->PJM
CLTF
1.378
LAGNLTFEXP_LAGN->PJM
CLTF
8.173
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.302
WECLTFEXP_WEC->PJM
CLTF
0.668
TVALTFEXP_TVA->PJM
CLTF
4.142
CPLELTFEXP_CPLE->PJM
CLTF
11.526
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.356
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.357
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.11
MECLTFEXP_MEC->PJM
CLTF
3.734
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.2 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4696.32
MW Contribution:9.37
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
39.714
972189AH1-679 GEN
50/50
3.545
3150411LDYSMT5
50/50
28.349
3150381LDYSMT2
50/50
27.131
972213AH1-691 GEN
50/50
4.59
972215AH1-692 GEN
50/50
4.59
316312AB1-027
Solar/Wind Harmer
0.736
315976AC1-164 GENA
Solar/Wind Harmer
22.253
316169AC1-164_GENC
Solar/Wind Harmer
19.225
315975AC1-164 GENB
Solar/Wind Harmer
0.658
971285AH1-108 GEN
Adder
1.403
316233AE1-074 FULL
Solar/Wind Harmer
0.556
971281AH1-106 GEN
Solar/Wind Harmer
3.356
971283AH1-107 GEN
Solar/Wind Harmer
3.356
316132AB2-190 GEN1
Solar/Wind Harmer
2.074
316369SG1_INVT
Solar/Wind Harmer
3.641
972265AH1-717 GEN
Adder
13.944
3151201GRAVEL4
Adder
13.072
3151191GRAVEL3
Adder
12.906
3151211GRAVEL5
Adder
12.906
971167AH1-042 GEN
Solar/Wind Harmer
19.411
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
971445AH1-216 GEN
Solar/Wind Harmer
12.425
3143316POE
Solar/Wind Harmer
-0.078
3151081ELIZAR1
Adder
16.225
3151091ELIZAR2
Adder
15.943
3152611GOSPORTB
Adder
2.253
3152621GOSPORTC
Adder
1.912
3152601GOSPORTA
Adder
1.764
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.596
3138283WHITEMARSH
Solar/Wind Harmer
0.031
316314AB2-024 C
Solar/Wind Harmer
1.685
957871AF2-081 GEN
Solar/Wind Harmer
9.844
315833AF1-017_GEN
Solar/Wind Harmer
3.733
316349AD2-085 GEN
Solar/Wind Harmer
1.748
316311AC2-079 GEN
Solar/Wind Harmer
9.912
319010AE1-072 C
Solar/Wind Harmer
3.972
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.591
316059AD1-063 C
Solar/Wind Harmer
0.442
315835AF2-110_GEN
Solar/Wind Harmer
2.44
313526AB2-022
Solar/Wind Harmer
0.525
315662AE1-191 GEN
Solar/Wind Harmer
2.344
315666AE1-190 GEN
Solar/Wind Harmer
0.586
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.523
3146396TANGLEW
Solar/Wind Harmer
0.356
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
957601AF2-054 GEN
Solar/Wind Harmer
0.578
3141873WAN 176
Solar/Wind Harmer
-0.004
3141913WHIT STONE
Solar/Wind Harmer
-0.019
315611Z1-036_GEN2
Solar/Wind Harmer
4.677
316315AB2-025 C
Solar/Wind Harmer
0.509
3138133OCRAN
Solar/Wind Harmer
-0.006
315814AE2-033 C
Solar/Wind Harmer
17.521
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
941031AE2-094 GEN
Solar/Wind Harmer
34.885
944011AF1-069 GEN
Solar/Wind Harmer
10.931
970673AG2-436 GEN
Solar/Wind Harmer
38.527
970673AG2-436 GEN
Solar/Wind Harmer
19.507
315816AE2-034 GEN
Solar/Wind Harmer
1.482
315052AA1-145 CT2
50/50
1.588
972197AH1-683 GEN
50/50
4.413
972219AH1-694 GEN
50/50
3.177
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.022
3143096IRON208
Adder
0.787
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
88.83
3150851SPRUNCC
Adder
0.858
3143526WINTERP
Solar/Wind Harmer
-0.107
316159AE1-175 C
Solar/Wind Harmer
0.552
970129AG2-093 GEN
Solar/Wind Harmer
4.679
316458AB2-190 GEN2
Solar/Wind Harmer
2.074
971069AG2-661 GEN
Solar/Wind Harmer
3.233
315671AE2-027_GEN
Solar/Wind Harmer
15.31
971647AH1-324 GEN
Solar/Wind Harmer
10.159
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
961611AG1-000B GEN
Solar/Wind Harmer
9.996
971317AH1-138 GEN
Solar/Wind Harmer
2.531
3151171GRAVELC
Adder
1.91
316294AC1-161 GEN
Solar/Wind Harmer
6.513
3142433PROV 92
Solar/Wind Harmer
-0.08
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
3145336SMITFLD
Solar/Wind Harmer
-0.08
970659AG2-427 GEN
Solar/Wind Harmer
10.57
316375AC2-012 GEN
Solar/Wind Harmer
6.881
3150981CHESPKA
Adder
2.209
944591AF1-124 GEN
Solar/Wind Harmer
90.743
316381AD1-082 GEN
Solar/Wind Harmer
1.823
970661AG2-428 GEN
Solar/Wind Harmer
21.05
316072AD1-144
Solar/Wind Harmer
0.4
316388AE2-253 GEN
Solar/Wind Harmer
1.329
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.397
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.297
3141843SHACKLE
Adder
0.888
316093AE2-104_GEN
Solar/Wind Harmer
5.675
939411AE1-173 GEN
Solar/Wind Harmer
97.222
940641AE2-051 GEN
Solar/Wind Harmer
18.116
3146516WINFALL
Solar/Wind Harmer
-0.062
3146516WINFALL
Solar/Wind Harmer
-0.019
315800Z1-036_GEN1
Solar/Wind Harmer
4.677
3138133OCRAN
Solar/Wind Harmer
-0.011
3130156CHOWAN
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.051
971163AH1-040 GEN
Solar/Wind Harmer
17.174
3143336POWHATN
Solar/Wind Harmer
2.14
961951AG1-038 GEN
Solar/Wind Harmer
2.365
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.446
3145893MURPHYS
Solar/Wind Harmer
-0.07
3145893MURPHYS
Solar/Wind Harmer
0.525
316023GEN1_S
Solar/Wind Harmer
1.191
962861AG1-135 GEN
Solar/Wind Harmer
6.62
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.533
316336AC2-165 C
Solar/Wind Harmer
3.03
970087AG2-069 GEN
Solar/Wind Harmer
16.334
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.941
964211AG1-282 GEN
Solar/Wind Harmer
0.517
3141726DUNNSVL
Solar/Wind Harmer
-0.068
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.565
962571AG1-106 GEN
Solar/Wind Harmer
2.449
316174AB2-169 GEN
Solar/Wind Harmer
2.625
316190AA2-174 GEN
Solar/Wind Harmer
0.209
971795AH1-408 GEN
Solar/Wind Harmer
12.691
957481AF2-042 GEN
Solar/Wind Harmer
52.83
3145783HORNRTN
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.492
962981AG1-147 GEN
Solar/Wind Harmer
7.964
971967AH1-528 GEN
Solar/Wind Harmer
34.143
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.633
315733AD1-074 GEN2
Solar/Wind Harmer
3.633
315735AD1-075 GEN1
Solar/Wind Harmer
1.817
965291AG1-394 GEN
Solar/Wind Harmer
1.584
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.78
316318V4-068
Solar/Wind Harmer
0.441
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.152
961941AG1-037 GEN
Solar/Wind Harmer
0.131
3145513AHOSKIE
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.889
970581AG2-369 GEN
Solar/Wind Harmer
9.365
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.746
946281AF1-292 GEN
Solar/Wind Harmer
0.386
316087AB2-174 GEN
Solar/Wind Harmer
2.445
315652AC1-086 GEN
Solar/Wind Harmer
19.168
3137643SOCKMAN
Solar/Wind Harmer
-0.068
3141813NORNECK
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.067
972193AH1-681 GEN
Adder
3.317
972205AH1-687 GEN
Adder
5.556
970831AG2-522 GEN
Solar/Wind Harmer
4.191
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.017
3147043LAWRENC
Adder
1.35
315693AD1-088 GEN
Solar/Wind Harmer
8.336
962491AG1-098 GEN
Solar/Wind Harmer
11.128
3146293MARTNCO
Solar/Wind Harmer
0.102
316212AC1-099_GEN
Solar/Wind Harmer
1.436
972277AH1-723 GEN
Adder
86.505
3144293JTRSVLE
Adder
0.442
3150391LDYSMT3
50/50
28.208
972195AH1-682 GEN
50/50
3.707
957411AF2-035 GEN
Solar/Wind Harmer
10.059
970317AG2-208 GEN
Solar/Wind Harmer
9.78
315673AE1-157 GEN
Solar/Wind Harmer
16.754
3142296MT RD221
Adder
0.629
3142366NRTHEST
Adder
0.626
3150691DARBY 3
Adder
13.746
3150701DARBY 4
Adder
13.714
3150681DARBY 2
Adder
13.698
3150671DARBY 1
Adder
13.682
316075AC2-137 C
Solar/Wind Harmer
0.574
3142946ENON
Solar/Wind Harmer
-0.002
966871AG1-558 GEN
Solar/Wind Harmer
0.63
966871AG1-558 GEN
Solar/Wind Harmer
0.215
944641AF1-129 GEN
Adder
87.651
3143526WINTERP
Solar/Wind Harmer
-0.107
316240AF1-291 C
Solar/Wind Harmer
0.62
316033AB2-134 GEN
Solar/Wind Harmer
6.572
315697AD1-025 GEN
Solar/Wind Harmer
4.122
971223AH1-071 GEN
Solar/Wind Harmer
2.538
316236AE1-162_GEN
Solar/Wind Harmer
0.605
316036AC1-147 C
Solar/Wind Harmer
0.536
3150991CHESPKB
Adder
1.854
3150991CHESPKB
Adder
1.809
970657AG2-426 GEN
Solar/Wind Harmer
6.204
970657AG2-426 GEN
Solar/Wind Harmer
1.297
316316AC1-027 C
Solar/Wind Harmer
0.609
3142956BIRDNECK
Solar/Wind Harmer
1.065
316185AD1-033 GEN
Solar/Wind Harmer
2.09
3145506HICKORY
Solar/Wind Harmer
-0.079
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.329
316018AA1-139 ULT2
Solar/Wind Harmer
1.686
316017AA1-139 ULT1
Solar/Wind Harmer
1.593
3137176SLIGO L2192
Solar/Wind Harmer
-0.078
3146456SLIGO L269
Solar/Wind Harmer
2.32
3130086AYDLETT
Solar/Wind Harmer
-0.078
316441AF1-014 GEN
Solar/Wind Harmer
1.317
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.49
316433W1029_GEN2
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.658
315742AE1-103 GEN
Solar/Wind Harmer
1.965
3146376EDENTON
Solar/Wind Harmer
0.555
3146376EDENTON
Solar/Wind Harmer
0.555
972185AH1-677 GEN
Adder
9.093
972187AH1-678 GEN
Adder
4.569
316487AF1-042 GEN
Solar/Wind Harmer
2.365
316065AD1-022 GEN
Solar/Wind Harmer
8.924
970933AG2-581 GEN
Solar/Wind Harmer
16.701
3145893MURPHYS
Solar/Wind Harmer
0.494
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
958261AF2-120 GEN
Solar/Wind Harmer
6.798
316181AB2-040 GEN
Solar/Wind Harmer
2.384
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.717
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.903
3145593CAROLNA
Solar/Wind Harmer
0.14
970099AG2-077 GEN
Solar/Wind Harmer
21.132
3145783HORNRTN
Solar/Wind Harmer
1.996
3145783HORNRTN
Solar/Wind Harmer
1.597
3145783HORNRTN
Solar/Wind Harmer
0.499
3145783HORNRTN
Solar/Wind Harmer
0.2
316077AC2-138 C
Solar/Wind Harmer
0.355
3150341NORNECKC1
Adder
1.567
3150341NORNECKC1
Adder
1.555
970497AG2-320 GEN
50/50
20.535
971645AH1-323 GEN
50/50
17.746
315051AA1-145 CT1
50/50
1.581
3150401LDYSMT4
50/50
28.261
3150371LDYSMT1
50/50
27.308
966881AG1-559 GEN
Solar/Wind Harmer
0.672
3142416OLDCHRC
Solar/Wind Harmer
2.201
970293AG2-193 GEN
Solar/Wind Harmer
2.672
3143096IRON208
Adder
0.787
3143096IRON208
Adder
0.771
3142946ENON
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Harmer
2.254
3150861SPRUNCD
Adder
0.858
970133AG2-095 GEN
Solar/Wind Harmer
2.321
316382AG1-145 C
Solar/Wind Harmer
0.62
970129AG2-093 GEN
Solar/Wind Harmer
11.551
315778AD1-151 GEN
Solar/Wind Harmer
17.699
965281AG1-393 GEN
Solar/Wind Harmer
2.545
315839AE2-212 C
Solar/Wind Harmer
0.613
3150921YORKTN3
Adder
4.533
3144216WINCHST
Adder
0.68
961611AG1-000B GEN
Solar/Wind Harmer
4.265
3151221GRAVEL6
Adder
13.057
3151171GRAVELC
Adder
2.512
315773AC2-141 GEN
Solar/Wind Harmer
8.424
3142433PROV 92
Adder
0.348
3142433PROV 92
Adder
0.348
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.509
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.873
3151101ELIZAR3
Adder
16.432
944581AF1-123 GEN
Solar/Wind Harmer
90.418
944601AF1-125 GEN
Solar/Wind Harmer
89.007
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316083AB2-161 GEN
Solar/Wind Harmer
3.226
970661AG2-428 GEN
Solar/Wind Harmer
3.73
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.395
3141766HARMONY
Solar/Wind Harmer
1.741
3141843SHACKLE
Adder
0.888
316203AE2-005 GEN
Solar/Wind Harmer
8.236
316320Y1-086
Solar/Wind Harmer
1.14
316280AD1-041 GEN
Solar/Wind Harmer
1.465
316156AD2-030 GEN
Solar/Wind Harmer
0.516
3141873WAN 176
Solar/Wind Harmer
2.292
316435W1029_GEN3
Solar/Wind Harmer
3.49
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.019
315614AA2-178 GEN
Solar/Wind Harmer
1.976
962971AG1-146 GEN
Solar/Wind Harmer
3.413
316313AB2-026
Solar/Wind Harmer
0.486
316258AE1-075 C
Solar/Wind Harmer
0.438
316405AF2-144 C
Solar/Wind Harmer
0.462
3143336POWHATN
Solar/Wind Harmer
1.819
971157AH1-035 GEN
Solar/Wind Harmer
2.252
315737AD1-076 GEN
Solar/Wind Harmer
3.414
316484AD2-074 GEN
Solar/Wind Harmer
4.519
970009AG2-005 GEN
Solar/Wind Harmer
2.244
3156081AA2-088 GEN
Solar/Wind Harmer
5.819
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.124
3145893MURPHYS
Solar/Wind Harmer
-0.018
316365GEN2_N
Solar/Wind Harmer
1.191
957521AF2-046 GEN
Solar/Wind Harmer
13.906
961681AG1-008 GEN
Solar/Wind Harmer
13.906
3146173TUNIS
Solar/Wind Harmer
-0.017
316404AE1-155 C
Solar/Wind Harmer
3.384
3156021HOLLOMANSOL
Solar/Wind Harmer
2.361
970917AG2-570 GEN
Solar/Wind Harmer
43.708
316463AE2-346 GEN
Solar/Wind Harmer
0.283
316140AB2-099
Solar/Wind Harmer
0.118
962331AG1-082 GEN
Solar/Wind Harmer
2.183
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.35
3145963POPLR C
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.374
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
0.804
3145823KELFORD
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.517
3145796HORNRTN
Solar/Wind Harmer
-0.067
3145796HORNRTN
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
971781AH1-399 GEN
Solar/Wind Harmer
1.025
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.058
316210AC1-098 GEN
Solar/Wind Harmer
2.585
316478AD1-087 GEN
Solar/Wind Harmer
1.419
316486AD2-202 GEN
Solar/Wind Harmer
0.416
972255AH1-712 GEN
Adder
74.234
3144293JTRSVLE
Adder
0.442
227287AC2-120 GEN
Solar/Wind Helper
0.418
226910AB2-157 C
Solar/Wind Helper
0.017
3145796HORNRTN
Solar/Wind Harmer
-0.05
316468AD1-105 GEN
Solar/Wind Harmer
1.853
3145933PARMELE
Solar/Wind Harmer
-0.033
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.764
3144293JTRSVLE
Adder
0.442
3144293JTRSVLE
Adder
0.372
226929AD2-058 GEN
Solar/Wind Helper
0.128
NYPJM->LTFIMP_NY
CLTF
2.987
LGEELTFEXP_LGEE->PJM
CLTF
1.72
LAGNLTFEXP_LAGN->PJM
CLTF
7.934
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.871
WECLTFEXP_WEC->PJM
CLTF
0.877
TVALTFEXP_TVA->PJM
CLTF
4.016
CPLELTFEXP_CPLE->PJM
CLTF
9.143
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.304
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.014
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.058
MECLTFEXP_MEC->PJM
CLTF
4.425
SIGELTFEXP_SIGE->PJM
CLTF
0.137

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.13 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4535.93
MW Contribution:9.7
Bus #Bus NameTypeMW Contribution
972189AH1-679 GEN
50/50
3.41
316312AB1-027
Solar/Wind Harmer
0.719
316233AE1-074 FULL
Solar/Wind Harmer
0.569
971281AH1-106 GEN
Solar/Wind Harmer
3.437
971283AH1-107 GEN
Solar/Wind Harmer
3.437
971285AH1-108 GEN
Adder
1.413
3150411LDYSMT5
Adder
25.004
3150381LDYSMT2
Adder
23.93
972213AH1-691 GEN
Adder
4.048
972215AH1-692 GEN
Adder
4.048
315976AC1-164 GENA
Solar/Wind Harmer
21.931
316169AC1-164_GENC
Solar/Wind Harmer
18.947
315975AC1-164 GENB
Solar/Wind Harmer
0.649
316132AB2-190 GEN1
Solar/Wind Harmer
2.078
316369SG1_INVT
Solar/Wind Harmer
3.654
972265AH1-717 GEN
Adder
14.028
3152261N ANNA2
50/50
11.181
970497AG2-320 GEN
50/50
19.067
971645AH1-323 GEN
50/50
17.222
315051AA1-145 CT1
50/50
1.521
316044AC1-158 PL1
Solar/Wind Harmer
2.607
316450AC1-158 RIC
Solar/Wind Harmer
0.695
3142416OLDCHRC
Solar/Wind Harmer
2.152
966881AG1-559 GEN
Solar/Wind Harmer
0.637
970293AG2-193 GEN
Solar/Wind Harmer
2.633
3150861SPRUNCD
Adder
0.863
3143096IRON208
Adder
0.782
3143096IRON208
Adder
0.767
3150401LDYSMT4
Adder
24.926
3150371LDYSMT1
Adder
24.085
3142946ENON
Solar/Wind Harmer
-0.007
970133AG2-095 GEN
Solar/Wind Harmer
2.322
970129AG2-093 GEN
Solar/Wind Harmer
11.571
315839AE2-212 C
Solar/Wind Harmer
0.618
316473AC1-191 GEN
Solar/Wind Harmer
2.205
965281AG1-393 GEN
Solar/Wind Harmer
2.562
315778AD1-151 GEN
Solar/Wind Harmer
17.748
316382AG1-145 C
Solar/Wind Harmer
0.617
315773AC2-141 GEN
Solar/Wind Harmer
8.525
961611AG1-000B GEN
Solar/Wind Harmer
4.287
3151221GRAVEL6
Adder
13.136
3151171GRAVELC
Adder
2.527
3144216WINCHST
Adder
0.681
3150921YORKTN3
Adder
4.537
315813AE1-149 C
Solar/Wind Harmer
12.652
3145336SMITFLD
Solar/Wind Harmer
-0.008
3144536CHRHLND
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
91.618
944601AF1-125 GEN
Solar/Wind Harmer
90.188
3151101ELIZAR3
Adder
16.637
970659AG2-427 GEN
Solar/Wind Harmer
1.895
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316083AB2-161 GEN
Solar/Wind Harmer
3.264
970661AG2-428 GEN
Solar/Wind Harmer
3.776
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.426
316320Y1-086
Solar/Wind Harmer
1.155
316435W1029_GEN3
Solar/Wind Harmer
3.536
3146516WINFALL
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
1.731
3141843SHACKLE
Adder
0.884
316203AE2-005 GEN
Solar/Wind Harmer
8.198
316280AD1-041 GEN
Solar/Wind Harmer
1.459
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
316156AD2-030 GEN
Solar/Wind Harmer
0.514
3141873WAN 176
Solar/Wind Harmer
2.284
3146376EDENTON
Solar/Wind Harmer
-0.019
3147666LOUISA
Solar/Wind Harmer
-0.043
316313AB2-026
Solar/Wind Harmer
0.502
316258AE1-075 C
Solar/Wind Harmer
0.452
316405AF2-144 C
Solar/Wind Harmer
0.477
3152251N ANNA1
50/50
11.182
315052AA1-145 CT2
50/50
1.528
316045AC1-158 PL2
Solar/Wind Harmer
8.338
3142416OLDCHRC
Solar/Wind Harmer
-0.055
3142416OLDCHRC
Solar/Wind Harmer
-0.021
966881AG1-559 GEN
Solar/Wind Harmer
0.218
3143526WINTERP
Solar/Wind Harmer
-0.109
3143226MDLTHAN
Solar/Wind Harmer
-0.021
3150851SPRUNCC
Adder
0.863
3143096IRON208
Adder
0.782
3142543TWELFTH
Solar/Wind Harmer
-0.002
972197AH1-683 GEN
Adder
3.892
972219AH1-694 GEN
Adder
2.802
944631AF1-128 GEN
Adder
88.257
970129AG2-093 GEN
Solar/Wind Harmer
4.687
316458AB2-190 GEN2
Solar/Wind Harmer
2.078
315671AE2-027_GEN
Solar/Wind Harmer
15.394
971069AG2-661 GEN
Solar/Wind Harmer
3.242
316159AE1-175 C
Solar/Wind Harmer
0.549
971647AH1-324 GEN
Solar/Wind Harmer
10.202
316294AC1-161 GEN
Solar/Wind Harmer
6.591
961611AG1-000B GEN
Solar/Wind Harmer
10.047
3151171GRAVELC
Adder
1.922
3138126ROCKLANDING
Solar/Wind Harmer
0.062
3145336SMITFLD
Solar/Wind Harmer
-0.081
971317AH1-138 GEN
Solar/Wind Harmer
2.528
944591AF1-124 GEN
Solar/Wind Harmer
91.948
316375AC2-012 GEN
Solar/Wind Harmer
6.965
3150981CHESPKA
Adder
2.237
970659AG2-427 GEN
Solar/Wind Harmer
10.696
316381AD1-082 GEN
Solar/Wind Harmer
1.844
970661AG2-428 GEN
Solar/Wind Harmer
21.306
939411AE1-173 GEN
Solar/Wind Harmer
100.174
940641AE2-051 GEN
Solar/Wind Harmer
18.774
3142433PROV 92
Solar/Wind Harmer
-0.08
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
316072AD1-144
Solar/Wind Harmer
0.404
316388AE2-253 GEN
Solar/Wind Harmer
1.346
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.402
316093AE2-104_GEN
Solar/Wind Harmer
5.749
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.287
3141843SHACKLE
Adder
0.884
315800Z1-036_GEN1
Solar/Wind Harmer
4.742
3130156CHOWAN
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
3147666LOUISA
Solar/Wind Harmer
-0.074
3143336POWHATN
Solar/Wind Harmer
1.877
315614AA2-178 GEN
Solar/Wind Harmer
2.005
971157AH1-035 GEN
Solar/Wind Harmer
2.285
315737AD1-076 GEN
Solar/Wind Harmer
3.464
3156081AA2-088 GEN
Solar/Wind Harmer
5.913
962971AG1-146 GEN
Solar/Wind Harmer
3.411
970917AG2-570 GEN
Solar/Wind Harmer
45.296
3146206CASHIE
Solar/Wind Harmer
-0.018
316365GEN2_N
Solar/Wind Harmer
1.216
3145893MURPHYS
Solar/Wind Harmer
0.126
3145893MURPHYS
Solar/Wind Harmer
-0.018
316484AD2-074 GEN
Solar/Wind Harmer
4.52
970009AG2-005 GEN
Solar/Wind Harmer
2.244
957521AF2-046 GEN
Solar/Wind Harmer
14.132
961681AG1-008 GEN
Solar/Wind Harmer
14.132
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.398
316463AE2-346 GEN
Solar/Wind Harmer
0.287
316140AB2-099
Solar/Wind Harmer
0.12
962331AG1-082 GEN
Solar/Wind Harmer
2.219
966621AG1-532 GEN
Solar/Wind Harmer
0.357
316404AE1-155 C
Solar/Wind Harmer
3.389
3146263WOODLND
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.402
3145963POPLR C
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
0.818
3145823KELFORD
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
316478AD1-087 GEN
Solar/Wind Harmer
1.462
316486AD2-202 GEN
Solar/Wind Harmer
0.428
3150351NORNECKC2
Adder
1.523
3144293JTRSVLE
Adder
0.452
972255AH1-712 GEN
Adder
69.158
3151761LOISA E
Adder
15.204
227287AC2-120 GEN
Solar/Wind Helper
0.375
3142296MT RD221
50/50
0.65
3142366NRTHEST
50/50
0.655
3150691DARBY 3
50/50
14.384
3150701DARBY 4
50/50
14.351
316447AC1-158 HLD
Solar/Wind Harmer
5.732
957411AF2-035 GEN
Solar/Wind Harmer
9.538
970317AG2-208 GEN
Solar/Wind Harmer
9.273
3150681DARBY 2
Adder
13.508
3150671DARBY 1
Adder
13.493
3143526WINTERP
Solar/Wind Harmer
-0.109
971223AH1-071 GEN
Solar/Wind Harmer
2.643
315673AE1-157 GEN
Solar/Wind Harmer
15.81
316075AC2-137 C
Solar/Wind Harmer
0.565
3150391LDYSMT3
Adder
24.879
972195AH1-682 GEN
Adder
3.27
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
87.852
316240AF1-291 C
Solar/Wind Harmer
0.622
966871AG1-558 GEN
Solar/Wind Harmer
0.616
966871AG1-558 GEN
Solar/Wind Harmer
0.211
316033AB2-134 GEN
Solar/Wind Harmer
6.595
315697AD1-025 GEN
Solar/Wind Harmer
4.136
316236AE1-162_GEN
Solar/Wind Harmer
0.61
316036AC1-147 C
Solar/Wind Harmer
0.543
3150991CHESPKB
Adder
1.876
3150991CHESPKB
Adder
1.831
316316AC1-027 C
Solar/Wind Harmer
0.617
3142956BIRDNECK
Solar/Wind Harmer
1.078
970657AG2-426 GEN
Solar/Wind Harmer
6.278
970657AG2-426 GEN
Solar/Wind Harmer
1.313
316185AD1-033 GEN
Solar/Wind Harmer
2.117
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
316339AD2-160 GEN
Solar/Wind Harmer
1.346
316018AA1-139 ULT2
Solar/Wind Harmer
1.708
316017AA1-139 ULT1
Solar/Wind Harmer
1.614
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.351
3130086AYDLETT
Solar/Wind Harmer
-0.079
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.536
316433W1029_GEN2
Solar/Wind Harmer
3.536
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
316441AF1-014 GEN
Solar/Wind Harmer
1.311
3151201GRAVEL4
Adder
13.151
3151191GRAVEL3
Adder
12.984
3151211GRAVEL5
Adder
12.984
3143316POE
Solar/Wind Harmer
-0.08
971445AH1-216 GEN
Solar/Wind Harmer
12.527
3151081ELIZAR1
Adder
16.427
3151091ELIZAR2
Adder
16.142
3152611GOSPORTB
Adder
2.281
3152621GOSPORTC
Adder
1.936
3152601GOSPORTA
Adder
1.786
971167AH1-042 GEN
Solar/Wind Harmer
19.307
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
957871AF2-081 GEN
Solar/Wind Harmer
9.972
315833AF1-017_GEN
Solar/Wind Harmer
3.78
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.038
319010AE1-072 C
Solar/Wind Harmer
4.024
3146406KITTY HAWK
Solar/Wind Harmer
0.017
316305AF2-043 C
Solar/Wind Harmer
0.599
957831AF2-077 GEN
Solar/Wind Harmer
0.595
3138283WHITEMARSH
Solar/Wind Harmer
0.031
315835AF2-110_GEN
Solar/Wind Harmer
2.472
3143873LANEXA
Solar/Wind Harmer
-0.012
313526AB2-022
Solar/Wind Harmer
0.532
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.529
3146396TANGLEW
Solar/Wind Harmer
0.361
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
316314AB2-024 C
Solar/Wind Harmer
1.673
316059AD1-063 C
Solar/Wind Harmer
0.44
315662AE1-191 GEN
Solar/Wind Harmer
2.334
315666AE1-190 GEN
Solar/Wind Harmer
0.583
941031AE2-094 GEN
Solar/Wind Harmer
36.29
944011AF1-069 GEN
Solar/Wind Harmer
11.371
316315AB2-025 C
Solar/Wind Harmer
0.522
315814AE2-033 C
Solar/Wind Harmer
17.949
957601AF2-054 GEN
Solar/Wind Harmer
0.576
3141873WAN 176
Solar/Wind Harmer
-0.004
315611Z1-036_GEN2
Solar/Wind Harmer
4.742
970673AG2-436 GEN
Solar/Wind Harmer
40.043
970673AG2-436 GEN
Solar/Wind Harmer
20.275
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
3141913WHIT STONE
Solar/Wind Harmer
-0.019
971967AH1-528 GEN
Solar/Wind Harmer
35.457
3138133OCRAN
Solar/Wind Harmer
-0.006
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
1.504
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.686
315733AD1-074 GEN2
Solar/Wind Harmer
3.686
315735AD1-075 GEN1
Solar/Wind Harmer
1.844
962981AG1-147 GEN
Solar/Wind Harmer
7.96
965291AG1-394 GEN
Solar/Wind Harmer
1.61
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.898
970085AG2-068 GEN
Solar/Wind Harmer
11.282
970581AG2-369 GEN
Solar/Wind Harmer
9.703
316318V4-068
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.155
961941AG1-037 GEN
Solar/Wind Harmer
0.133
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.395
315607AA1-063A GEN
Solar/Wind Harmer
1.777
316087AB2-174 GEN
Solar/Wind Harmer
2.495
315652AC1-086 GEN
Solar/Wind Harmer
19.533
3137643SOCKMAN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.068
3141813NORNECK
Solar/Wind Harmer
-0.017
972193AH1-681 GEN
Adder
3.09
972205AH1-687 GEN
Adder
5.621
226910AB2-157 C
Solar/Wind Helper
0.015
316210AC1-098 GEN
Solar/Wind Harmer
1.553
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.675
315742AE1-103 GEN
Solar/Wind Harmer
1.993
3146376EDENTON
Solar/Wind Harmer
0.563
3146376EDENTON
Solar/Wind Harmer
0.563
972185AH1-677 GEN
Adder
9.446
972187AH1-678 GEN
Adder
4.744
970933AG2-581 GEN
Solar/Wind Harmer
17.317
316065AD1-022 GEN
Solar/Wind Harmer
9.058
3145893MURPHYS
Solar/Wind Harmer
0.502
3145893MURPHYS
Solar/Wind Harmer
-0.032
316487AF1-042 GEN
Solar/Wind Harmer
2.365
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
958261AF2-120 GEN
Solar/Wind Harmer
6.808
970099AG2-077 GEN
Solar/Wind Harmer
21.82
316181AB2-040 GEN
Solar/Wind Harmer
2.432
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.749
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.939
3145593CAROLNA
Solar/Wind Harmer
0.143
3145783HORNRTN
Solar/Wind Harmer
2.034
3145783HORNRTN
Solar/Wind Harmer
1.627
3145783HORNRTN
Solar/Wind Harmer
0.508
3145783HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
-0.051
316077AC2-138 C
Solar/Wind Harmer
0.356
3150341NORNECKC1
Adder
1.573
3150341NORNECKC1
Adder
1.56
3144293JTRSVLE
Adder
0.452
3144293JTRSVLE
Adder
0.38
3151731LOISA B
Adder
7.458
3151721LOISA A
Adder
7.419
226929AD2-058 GEN
Solar/Wind Helper
0.114
3143336POWHATN
Solar/Wind Harmer
2.208
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.421
316192AB2-158 GEN
Solar/Wind Harmer
2.18
970919AG2-571 GEN
Solar/Wind Harmer
5.734
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.513
970087AG2-069 GEN
Solar/Wind Harmer
16.924
316023GEN1_S
Solar/Wind Harmer
1.216
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.534
961951AG1-038 GEN
Solar/Wind Harmer
2.365
316336AC2-165 C
Solar/Wind Harmer
3.117
3146173TUNIS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
962861AG1-135 GEN
Solar/Wind Harmer
6.627
960081AF2-299 GEN
Solar/Wind Harmer
1.982
3146263WOODLND
Solar/Wind Harmer
-0.017
957481AF2-042 GEN
Solar/Wind Harmer
54.551
3145963POPLR C
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.633
962571AG1-106 GEN
Solar/Wind Harmer
2.496
3145823KELFORD
Solar/Wind Harmer
-0.017
316190AA2-174 GEN
Solar/Wind Harmer
0.213
316174AB2-169 GEN
Solar/Wind Harmer
2.665
971795AH1-408 GEN
Solar/Wind Harmer
12.961
964211AG1-282 GEN
Solar/Wind Harmer
0.518
3141726DUNNSVL
Solar/Wind Harmer
-0.069
315693AD1-088 GEN
Solar/Wind Harmer
8.593
962491AG1-098 GEN
Solar/Wind Harmer
11.467
3145783HORNRTN
Solar/Wind Harmer
-0.017
3147043LAWRENC
Adder
1.379
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
3150351NORNECKC2
Adder
1.498
3144293JTRSVLE
Adder
0.452
972277AH1-723 GEN
Adder
80.59
3151751LOISA D
Adder
7.458
316212AC1-099_GEN
Solar/Wind Harmer
0.862
NYPJM->LTFIMP_NY
CLTF
2.897
LAGNLTFEXP_LAGN->PJM
CLTF
7.571
LGEELTFEXP_LGEE->PJM
CLTF
1.548
WECLTFEXP_WEC->PJM
CLTF
0.782
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.834
TVALTFEXP_TVA->PJM
CLTF
3.832
CPLELTFEXP_CPLE->PJM
CLTF
9.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.506
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.364
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.323
MECLTFEXP_MEC->PJM
CLTF
4.03
SIGELTFEXP_SIGE->PJM
CLTF
0.124

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H4T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H4T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.18 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4419.9
MW Contribution:9.16
Bus #Bus NameTypeMW Contribution
970497AG2-320 GEN
50/50
20.809
3150401LDYSMT4
50/50
28.767
3150371LDYSMT1
50/50
27.797
315051AA1-145 CT1
50/50
1.582
971645AH1-323 GEN
50/50
17.655
966881AG1-559 GEN
Solar/Wind Harmer
0.679
3142416OLDCHRC
Solar/Wind Harmer
2.188
970293AG2-193 GEN
Solar/Wind Harmer
2.652
3143096IRON208
Adder
0.779
3143096IRON208
Adder
0.764
316473AC1-191 GEN
Solar/Wind Harmer
2.249
3142946ENON
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.847
970133AG2-095 GEN
Solar/Wind Harmer
2.296
316382AG1-145 C
Solar/Wind Harmer
0.614
970129AG2-093 GEN
Solar/Wind Harmer
11.42
315778AD1-151 GEN
Solar/Wind Harmer
17.494
965281AG1-393 GEN
Solar/Wind Harmer
2.513
315839AE2-212 C
Solar/Wind Harmer
0.605
3150921YORKTN3
Adder
4.486
3144216WINCHST
Adder
0.673
961611AG1-000B GEN
Solar/Wind Harmer
4.213
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151221GRAVEL6
Adder
12.894
3151171GRAVELC
Adder
2.481
315773AC2-141 GEN
Solar/Wind Harmer
8.304
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.337
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.847
3151101ELIZAR3
Adder
16.197
316083AB2-161 GEN
Solar/Wind Harmer
3.181
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
89.102
944601AF1-125 GEN
Solar/Wind Harmer
87.711
970661AG2-428 GEN
Solar/Wind Harmer
3.678
3141766HARMONY
Solar/Wind Harmer
1.734
3141843SHACKLE
Adder
0.885
316203AE2-005 GEN
Solar/Wind Harmer
8.201
316280AD1-041 GEN
Solar/Wind Harmer
1.459
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.36
316156AD2-030 GEN
Solar/Wind Harmer
0.514
3141873WAN 176
Solar/Wind Harmer
2.284
316320Y1-086
Solar/Wind Harmer
1.123
316435W1029_GEN3
Solar/Wind Harmer
3.437
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
962971AG1-146 GEN
Solar/Wind Harmer
3.417
315614AA2-178 GEN
Solar/Wind Harmer
1.944
316484AD2-074 GEN
Solar/Wind Harmer
4.529
970009AG2-005 GEN
Solar/Wind Harmer
2.249
971157AH1-035 GEN
Solar/Wind Harmer
2.214
315737AD1-076 GEN
Solar/Wind Harmer
3.356
316404AE1-155 C
Solar/Wind Harmer
3.398
3150411LDYSMT5
50/50
28.857
3150381LDYSMT2
50/50
27.617
972213AH1-691 GEN
50/50
4.672
972215AH1-692 GEN
50/50
4.672
963051AG1-154 GEN
50/50
3.594
972189AH1-679 GEN
50/50
3.546
316312AB1-027
Solar/Wind Harmer
0.731
315976AC1-164 GENA
Solar/Wind Harmer
22.101
316169AC1-164_GENC
Solar/Wind Harmer
19.093
315975AC1-164 GENB
Solar/Wind Harmer
0.654
971285AH1-108 GEN
Adder
1.386
316233AE1-074 FULL
Solar/Wind Harmer
0.547
971281AH1-106 GEN
Solar/Wind Harmer
3.302
971283AH1-107 GEN
Solar/Wind Harmer
3.302
316132AB2-190 GEN1
Solar/Wind Harmer
2.05
316369SG1_INVT
Solar/Wind Harmer
3.598
971167AH1-042 GEN
Solar/Wind Harmer
19.287
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
972265AH1-717 GEN
Adder
13.77
3151201GRAVEL4
Adder
12.909
3151191GRAVEL3
Adder
12.745
3151211GRAVEL5
Adder
12.745
971445AH1-216 GEN
Solar/Wind Harmer
12.262
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.591
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
-0.077
316314AB2-024 C
Solar/Wind Harmer
1.678
3151081ELIZAR1
Adder
15.992
3151091ELIZAR2
Adder
15.714
3152611GOSPORTB
Adder
2.221
3152621GOSPORTC
Adder
1.885
3152601GOSPORTA
Adder
1.739
316059AD1-063 C
Solar/Wind Harmer
0.44
957871AF2-081 GEN
Solar/Wind Harmer
9.699
315833AF1-017_GEN
Solar/Wind Harmer
3.679
316349AD2-085 GEN
Solar/Wind Harmer
1.723
316311AC2-079 GEN
Solar/Wind Harmer
9.769
315662AE1-191 GEN
Solar/Wind Harmer
2.334
315666AE1-190 GEN
Solar/Wind Harmer
0.584
319010AE1-072 C
Solar/Wind Harmer
3.913
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.582
957601AF2-054 GEN
Solar/Wind Harmer
0.576
3141873WAN 176
Solar/Wind Harmer
-0.004
315835AF2-110_GEN
Solar/Wind Harmer
2.404
313526AB2-022
Solar/Wind Harmer
0.517
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.515
3146396TANGLEW
Solar/Wind Harmer
0.351
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
4.604
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316315AB2-025 C
Solar/Wind Harmer
0.5
315814AE2-033 C
Solar/Wind Harmer
17.214
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
941031AE2-094 GEN
Solar/Wind Harmer
34.167
944011AF1-069 GEN
Solar/Wind Harmer
10.706
962981AG1-147 GEN
Solar/Wind Harmer
7.972
315816AE2-034 GEN
Solar/Wind Harmer
1.458
970673AG2-436 GEN
Solar/Wind Harmer
37.725
970673AG2-436 GEN
Solar/Wind Harmer
19.101
971967AH1-528 GEN
Solar/Wind Harmer
33.421
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.571
315733AD1-074 GEN2
Solar/Wind Harmer
3.571
315735AD1-075 GEN1
Solar/Wind Harmer
1.786
965291AG1-394 GEN
Solar/Wind Harmer
1.556
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.645
316318V4-068
Solar/Wind Harmer
0.433
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.15
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.655
970581AG2-369 GEN
Solar/Wind Harmer
9.164
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.713
3141813NORNECK
Solar/Wind Harmer
-0.017
946281AF1-292 GEN
Solar/Wind Harmer
0.379
316087AB2-174 GEN
Solar/Wind Harmer
2.398
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3137643SOCKMAN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.065
972193AH1-681 GEN
Adder
3.258
972205AH1-687 GEN
Adder
5.337
970831AG2-522 GEN
Solar/Wind Harmer
4.1
3150391LDYSMT3
50/50
28.713
972195AH1-682 GEN
50/50
3.773
3142296MT RD221
50/50
0.663
3142366NRTHEST
50/50
0.658
315673AE1-157 GEN
Solar/Wind Harmer
16.967
957411AF2-035 GEN
Solar/Wind Harmer
10.157
970317AG2-208 GEN
Solar/Wind Harmer
9.875
3150691DARBY 3
Adder
13.639
3150701DARBY 4
Adder
13.607
3150681DARBY 2
Adder
13.591
3150671DARBY 1
Adder
13.575
316075AC2-137 C
Solar/Wind Harmer
0.57
966871AG1-558 GEN
Solar/Wind Harmer
0.628
966871AG1-558 GEN
Solar/Wind Harmer
0.215
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
86.641
316240AF1-291 C
Solar/Wind Harmer
0.613
3143526WINTERP
Solar/Wind Harmer
-0.105
316033AB2-134 GEN
Solar/Wind Harmer
6.495
315697AD1-025 GEN
Solar/Wind Harmer
4.074
971223AH1-071 GEN
Solar/Wind Harmer
2.488
316236AE1-162_GEN
Solar/Wind Harmer
0.597
316036AC1-147 C
Solar/Wind Harmer
0.529
3150991CHESPKB
Adder
1.827
3150991CHESPKB
Adder
1.783
970657AG2-426 GEN
Solar/Wind Harmer
6.116
970657AG2-426 GEN
Solar/Wind Harmer
1.279
316316AC1-027 C
Solar/Wind Harmer
0.6
3142956BIRDNECK
Solar/Wind Harmer
1.049
316185AD1-033 GEN
Solar/Wind Harmer
2.06
3145506HICKORY
Solar/Wind Harmer
-0.078
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
316441AF1-014 GEN
Solar/Wind Harmer
1.311
316339AD2-160 GEN
Solar/Wind Harmer
1.309
316018AA1-139 ULT2
Solar/Wind Harmer
1.662
316017AA1-139 ULT1
Solar/Wind Harmer
1.57
3137176SLIGO L2192
Solar/Wind Harmer
-0.077
3146456SLIGO L269
Solar/Wind Harmer
2.286
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.437
316433W1029_GEN2
Solar/Wind Harmer
3.437
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.647
315742AE1-103 GEN
Solar/Wind Harmer
1.934
3146376EDENTON
Solar/Wind Harmer
0.546
3146376EDENTON
Solar/Wind Harmer
0.546
316487AF1-042 GEN
Solar/Wind Harmer
2.37
972185AH1-677 GEN
Adder
8.902
972187AH1-678 GEN
Adder
4.473
958261AF2-120 GEN
Solar/Wind Harmer
6.827
316065AD1-022 GEN
Solar/Wind Harmer
8.77
970933AG2-581 GEN
Solar/Wind Harmer
16.339
3145893MURPHYS
Solar/Wind Harmer
0.485
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.357
3150341NORNECKC1
Adder
1.579
3150341NORNECKC1
Adder
1.567
316468AD1-105 GEN
Solar/Wind Harmer
1.88
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
2.338
316426AA2-053 GEN
Solar/Wind Harmer
1.684
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.865
3145593CAROLNA
Solar/Wind Harmer
0.138
970099AG2-077 GEN
Solar/Wind Harmer
20.646
3145783HORNRTN
Solar/Wind Harmer
1.957
3145783HORNRTN
Solar/Wind Harmer
1.566
3145783HORNRTN
Solar/Wind Harmer
0.489
3145783HORNRTN
Solar/Wind Harmer
0.196
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.729
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
226929AD2-058 GEN
Solar/Wind Helper
0.118
3156081AA2-088 GEN
Solar/Wind Harmer
5.718
316313AB2-026
Solar/Wind Harmer
0.474
316258AE1-075 C
Solar/Wind Harmer
0.426
316405AF2-144 C
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
1.771
3146206CASHIE
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.658
961681AG1-008 GEN
Solar/Wind Harmer
13.658
316365GEN2_N
Solar/Wind Harmer
1.169
3146173TUNIS
Solar/Wind Harmer
-0.017
3156021HOLLOMANSOL
Solar/Wind Harmer
2.319
316463AE2-346 GEN
Solar/Wind Harmer
0.278
316140AB2-099
Solar/Wind Harmer
0.116
962331AG1-082 GEN
Solar/Wind Harmer
2.144
970917AG2-570 GEN
Solar/Wind Harmer
42.771
3150351NORNECKC2
Adder
1.529
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.343
971781AH1-399 GEN
Solar/Wind Harmer
1.04
3145963POPLR C
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.347
316317KELFORD C
Solar/Wind Harmer
0.789
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.019
316210AC1-098 GEN
Solar/Wind Harmer
2.534
972255AH1-712 GEN
Adder
72.909
316478AD1-087 GEN
Solar/Wind Harmer
1.386
316486AD2-202 GEN
Solar/Wind Harmer
0.406
3144293JTRSVLE
Adder
0.43
227287AC2-120 GEN
Solar/Wind Helper
0.387
226910AB2-157 C
Solar/Wind Helper
0.015
972197AH1-683 GEN
50/50
4.492
972219AH1-694 GEN
50/50
3.234
315052AA1-145 CT2
50/50
1.589
966881AG1-559 GEN
Solar/Wind Harmer
0.232
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
3143096IRON208
Adder
0.779
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
88.024
3150851SPRUNCC
Adder
0.847
316159AE1-175 C
Solar/Wind Harmer
0.547
3143526WINTERP
Solar/Wind Harmer
-0.105
970129AG2-093 GEN
Solar/Wind Harmer
4.626
316458AB2-190 GEN2
Solar/Wind Harmer
2.05
971069AG2-661 GEN
Solar/Wind Harmer
3.195
315671AE2-027_GEN
Solar/Wind Harmer
15.127
971647AH1-324 GEN
Solar/Wind Harmer
10.037
971317AH1-138 GEN
Solar/Wind Harmer
2.507
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.875
3142433PROV 92
Solar/Wind Harmer
-0.08
3142433PROV 92
Adder
0.346
3142433PROV 92
Adder
0.346
3151171GRAVELC
Adder
1.887
3143226MDLTHAN
Solar/Wind Harmer
-0.02
316294AC1-161 GEN
Solar/Wind Harmer
6.42
3145336SMITFLD
Solar/Wind Harmer
-0.079
970659AG2-427 GEN
Solar/Wind Harmer
10.422
316375AC2-012 GEN
Solar/Wind Harmer
6.782
3150981CHESPKA
Adder
2.178
316381AD1-082 GEN
Solar/Wind Harmer
1.797
944591AF1-124 GEN
Solar/Wind Harmer
89.423
970661AG2-428 GEN
Solar/Wind Harmer
20.752
3141766HARMONY
Solar/Wind Harmer
-0.004
316072AD1-144
Solar/Wind Harmer
0.394
971777AH1-397 GEN
Solar/Wind Harmer
2.288
3141843SHACKLE
Adder
0.885
316388AE2-253 GEN
Solar/Wind Harmer
1.309
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.391
316093AE2-104_GEN
Solar/Wind Harmer
5.591
939411AE1-173 GEN
Solar/Wind Harmer
95.482
940641AE2-051 GEN
Solar/Wind Harmer
17.771
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
315800Z1-036_GEN1
Solar/Wind Harmer
4.604
3130156CHOWAN
Solar/Wind Harmer
-0.018
3145663CRESWEL
Solar/Wind Harmer
-0.05
971163AH1-040 GEN
Solar/Wind Harmer
16.891
961951AG1-038 GEN
Solar/Wind Harmer
2.37
962861AG1-135 GEN
Solar/Wind Harmer
6.643
3143336POWHATN
Solar/Wind Harmer
2.084
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.369
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.516
316023GEN1_S
Solar/Wind Harmer
1.169
964211AG1-282 GEN
Solar/Wind Harmer
0.52
3141726DUNNSVL
Solar/Wind Harmer
-0.069
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.414
3145683EARLEYS
Solar/Wind Harmer
-0.017
970087AG2-069 GEN
Solar/Wind Harmer
15.983
3150351NORNECKC2
Adder
1.504
316336AC2-165 C
Solar/Wind Harmer
2.945
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.903
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
316174AB2-169 GEN
Solar/Wind Harmer
2.577
316190AA2-174 GEN
Solar/Wind Harmer
0.205
971795AH1-408 GEN
Solar/Wind Harmer
12.43
957481AF2-042 GEN
Solar/Wind Harmer
51.614
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.322
315693AD1-088 GEN
Solar/Wind Harmer
8.136
962491AG1-098 GEN
Solar/Wind Harmer
10.858
3146293MARTNCO
Solar/Wind Harmer
0.1
316212AC1-099_GEN
Solar/Wind Harmer
1.408
972277AH1-723 GEN
Adder
84.961
3144293JTRSVLE
Adder
0.43
NYPJM->LTFIMP_NY
CLTF
2.846
LAGNLTFEXP_LAGN->PJM
CLTF
7.584
LGEELTFEXP_LGEE->PJM
CLTF
1.614
WECLTFEXP_WEC->PJM
CLTF
0.82
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.244
TVALTFEXP_TVA->PJM
CLTF
3.839
CPLELTFEXP_CPLE->PJM
CLTF
8.902
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.096
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.41
MECLTFEXP_MEC->PJM
CLTF
4.166
SIGELTFEXP_SIGE->PJM
CLTF
0.129

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.16 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4419.22
MW Contribution:9.15
Bus #Bus NameTypeMW Contribution
970497AG2-320 GEN
50/50
20.643
3150401LDYSMT4
50/50
28.529
3150371LDYSMT1
50/50
27.567
315051AA1-145 CT1
50/50
1.573
966881AG1-559 GEN
Solar/Wind Harmer
0.674
3142416OLDCHRC
Solar/Wind Harmer
2.177
970293AG2-193 GEN
Solar/Wind Harmer
2.641
3143096IRON208
Adder
0.776
3143096IRON208
Adder
0.761
316473AC1-191 GEN
Solar/Wind Harmer
2.237
3142946ENON
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.844
970133AG2-095 GEN
Solar/Wind Harmer
2.287
316382AG1-145 C
Solar/Wind Harmer
0.612
970129AG2-093 GEN
Solar/Wind Harmer
11.378
315778AD1-151 GEN
Solar/Wind Harmer
17.43
965281AG1-393 GEN
Solar/Wind Harmer
2.504
315839AE2-212 C
Solar/Wind Harmer
0.603
3150921YORKTN3
Adder
4.468
3144216WINCHST
Adder
0.67
961611AG1-000B GEN
Solar/Wind Harmer
4.198
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151221GRAVEL6
Adder
12.849
3151171GRAVELC
Adder
2.472
315773AC2-141 GEN
Solar/Wind Harmer
8.277
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.297
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.841
3151101ELIZAR3
Adder
16.145
316083AB2-161 GEN
Solar/Wind Harmer
3.17
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
88.821
944601AF1-125 GEN
Solar/Wind Harmer
87.435
970661AG2-428 GEN
Solar/Wind Harmer
3.666
3141766HARMONY
Solar/Wind Harmer
1.726
3141843SHACKLE
Adder
0.881
316203AE2-005 GEN
Solar/Wind Harmer
8.164
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.353
316280AD1-041 GEN
Solar/Wind Harmer
1.452
316156AD2-030 GEN
Solar/Wind Harmer
0.511
3141873WAN 176
Solar/Wind Harmer
2.273
316320Y1-086
Solar/Wind Harmer
1.12
316435W1029_GEN3
Solar/Wind Harmer
3.426
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
962971AG1-146 GEN
Solar/Wind Harmer
3.399
315614AA2-178 GEN
Solar/Wind Harmer
1.938
316484AD2-074 GEN
Solar/Wind Harmer
4.506
970009AG2-005 GEN
Solar/Wind Harmer
2.237
971157AH1-035 GEN
Solar/Wind Harmer
2.208
315737AD1-076 GEN
Solar/Wind Harmer
3.347
3156081AA2-088 GEN
Solar/Wind Harmer
5.703
316313AB2-026
Solar/Wind Harmer
0.474
316258AE1-075 C
Solar/Wind Harmer
0.427
316405AF2-144 C
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
1.772
316404AE1-155 C
Solar/Wind Harmer
3.381
3146206CASHIE
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.623
961681AG1-008 GEN
Solar/Wind Harmer
13.623
316365GEN2_N
Solar/Wind Harmer
1.166
3146173TUNIS
Solar/Wind Harmer
-0.017
971531AH1-263 GEN
50/50
38.619
3150411LDYSMT5
50/50
28.618
3150381LDYSMT2
50/50
27.389
972213AH1-691 GEN
50/50
4.633
972215AH1-692 GEN
50/50
4.633
963051AG1-154 GEN
50/50
3.564
972189AH1-679 GEN
50/50
3.526
316312AB1-027
Solar/Wind Harmer
0.728
315976AC1-164 GENA
Solar/Wind Harmer
22.001
316169AC1-164_GENC
Solar/Wind Harmer
19.007
315975AC1-164 GENB
Solar/Wind Harmer
0.651
971285AH1-108 GEN
Adder
1.381
316233AE1-074 FULL
Solar/Wind Harmer
0.545
971281AH1-106 GEN
Solar/Wind Harmer
3.293
971283AH1-107 GEN
Solar/Wind Harmer
3.293
316132AB2-190 GEN1
Solar/Wind Harmer
2.043
316369SG1_INVT
Solar/Wind Harmer
3.585
971167AH1-042 GEN
Solar/Wind Harmer
19.203
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
972265AH1-717 GEN
Adder
13.722
3151201GRAVEL4
Adder
12.864
3151191GRAVEL3
Adder
12.701
3151211GRAVEL5
Adder
12.701
971445AH1-216 GEN
Solar/Wind Harmer
12.22
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.589
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
-0.077
3151081ELIZAR1
Adder
15.941
3151091ELIZAR2
Adder
15.664
316314AB2-024 C
Solar/Wind Harmer
1.67
3152611GOSPORTB
Adder
2.214
3152621GOSPORTC
Adder
1.879
3152601GOSPORTA
Adder
1.733
316059AD1-063 C
Solar/Wind Harmer
0.438
957871AF2-081 GEN
Solar/Wind Harmer
9.669
315833AF1-017_GEN
Solar/Wind Harmer
3.667
316349AD2-085 GEN
Solar/Wind Harmer
1.717
316311AC2-079 GEN
Solar/Wind Harmer
9.738
319010AE1-072 C
Solar/Wind Harmer
3.901
315662AE1-191 GEN
Solar/Wind Harmer
2.324
315666AE1-190 GEN
Solar/Wind Harmer
0.581
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.581
315835AF2-110_GEN
Solar/Wind Harmer
2.396
957601AF2-054 GEN
Solar/Wind Harmer
0.573
3141873WAN 176
Solar/Wind Harmer
-0.004
313526AB2-022
Solar/Wind Harmer
0.515
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.513
3146396TANGLEW
Solar/Wind Harmer
0.35
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
4.59
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316315AB2-025 C
Solar/Wind Harmer
0.499
315814AE2-033 C
Solar/Wind Harmer
17.17
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
941031AE2-094 GEN
Solar/Wind Harmer
34.101
944011AF1-069 GEN
Solar/Wind Harmer
10.685
962981AG1-147 GEN
Solar/Wind Harmer
7.932
315816AE2-034 GEN
Solar/Wind Harmer
1.454
970673AG2-436 GEN
Solar/Wind Harmer
37.654
970673AG2-436 GEN
Solar/Wind Harmer
19.065
971967AH1-528 GEN
Solar/Wind Harmer
33.362
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.561
315733AD1-074 GEN2
Solar/Wind Harmer
3.561
315735AD1-075 GEN1
Solar/Wind Harmer
1.781
965291AG1-394 GEN
Solar/Wind Harmer
1.552
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.625
316318V4-068
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
-0.047
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.636
970581AG2-369 GEN
Solar/Wind Harmer
9.147
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.709
946281AF1-292 GEN
Solar/Wind Harmer
0.378
3141813NORNECK
Solar/Wind Harmer
-0.017
316087AB2-174 GEN
Solar/Wind Harmer
2.392
315652AC1-086 GEN
Solar/Wind Harmer
18.758
3137643SOCKMAN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.065
3156021HOLLOMANSOL
Solar/Wind Harmer
2.313
316463AE2-346 GEN
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.115
962331AG1-082 GEN
Solar/Wind Harmer
2.139
970917AG2-570 GEN
Solar/Wind Harmer
42.694
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.343
3150351NORNECKC2
Adder
1.52
3145963POPLR C
Solar/Wind Harmer
-0.017
971781AH1-399 GEN
Solar/Wind Harmer
1.034
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.344
316317KELFORD C
Solar/Wind Harmer
0.787
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.014
316210AC1-098 GEN
Solar/Wind Harmer
2.528
316478AD1-087 GEN
Solar/Wind Harmer
1.384
316486AD2-202 GEN
Solar/Wind Harmer
0.405
972255AH1-712 GEN
Adder
72.68
3144293JTRSVLE
Adder
0.43
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
972193AH1-681 GEN
Adder
3.247
972205AH1-687 GEN
Adder
5.365
970831AG2-522 GEN
Solar/Wind Harmer
4.093
3150391LDYSMT3
50/50
28.476
972195AH1-682 GEN
50/50
3.742
315673AE1-157 GEN
Solar/Wind Harmer
16.839
957411AF2-035 GEN
Solar/Wind Harmer
10.085
970317AG2-208 GEN
Solar/Wind Harmer
9.805
3142296MT RD221
Adder
0.622
3142366NRTHEST
Adder
0.618
3150691DARBY 3
Adder
13.579
3150701DARBY 4
Adder
13.548
3150681DARBY 2
Adder
13.532
3150671DARBY 1
Adder
13.516
316075AC2-137 C
Solar/Wind Harmer
0.567
966871AG1-558 GEN
Solar/Wind Harmer
0.625
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
86.324
3143526WINTERP
Solar/Wind Harmer
-0.105
316240AF1-291 C
Solar/Wind Harmer
0.611
316033AB2-134 GEN
Solar/Wind Harmer
6.472
315697AD1-025 GEN
Solar/Wind Harmer
4.059
971223AH1-071 GEN
Solar/Wind Harmer
2.484
316236AE1-162_GEN
Solar/Wind Harmer
0.595
316036AC1-147 C
Solar/Wind Harmer
0.527
3150991CHESPKB
Adder
1.821
3150991CHESPKB
Adder
1.777
970657AG2-426 GEN
Solar/Wind Harmer
6.097
970657AG2-426 GEN
Solar/Wind Harmer
1.275
316316AC1-027 C
Solar/Wind Harmer
0.598
3142956BIRDNECK
Solar/Wind Harmer
1.046
316185AD1-033 GEN
Solar/Wind Harmer
2.053
3145506HICKORY
Solar/Wind Harmer
-0.077
3145506HICKORY
Solar/Wind Harmer
-0.046
3145506HICKORY
Solar/Wind Harmer
-0.012
316441AF1-014 GEN
Solar/Wind Harmer
1.305
316339AD2-160 GEN
Solar/Wind Harmer
1.305
316018AA1-139 ULT2
Solar/Wind Harmer
1.657
316017AA1-139 ULT1
Solar/Wind Harmer
1.565
3137176SLIGO L2192
Solar/Wind Harmer
-0.076
3146456SLIGO L269
Solar/Wind Harmer
2.279
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.426
316433W1029_GEN2
Solar/Wind Harmer
3.426
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.645
315742AE1-103 GEN
Solar/Wind Harmer
1.928
3146376EDENTON
Solar/Wind Harmer
0.545
3146376EDENTON
Solar/Wind Harmer
0.545
316487AF1-042 GEN
Solar/Wind Harmer
2.358
972185AH1-677 GEN
Adder
8.886
972187AH1-678 GEN
Adder
4.465
958261AF2-120 GEN
Solar/Wind Harmer
6.791
316065AD1-022 GEN
Solar/Wind Harmer
8.747
970933AG2-581 GEN
Solar/Wind Harmer
16.313
3145893MURPHYS
Solar/Wind Harmer
0.484
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.355
3150341NORNECKC1
Adder
1.571
3150341NORNECKC1
Adder
1.558
316468AD1-105 GEN
Solar/Wind Harmer
1.868
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
2.333
316426AA2-053 GEN
Solar/Wind Harmer
1.68
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.861
3145593CAROLNA
Solar/Wind Harmer
0.137
970099AG2-077 GEN
Solar/Wind Harmer
20.62
3145783HORNRTN
Solar/Wind Harmer
1.953
3145783HORNRTN
Solar/Wind Harmer
1.562
3145783HORNRTN
Solar/Wind Harmer
0.488
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.725
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
226929AD2-058 GEN
Solar/Wind Helper
0.118
972197AH1-683 GEN
50/50
4.455
972219AH1-694 GEN
50/50
3.208
315052AA1-145 CT2
50/50
1.58
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
3143096IRON208
Adder
0.776
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
87.663
3150851SPRUNCC
Adder
0.844
316159AE1-175 C
Solar/Wind Harmer
0.545
3143526WINTERP
Solar/Wind Harmer
-0.105
970129AG2-093 GEN
Solar/Wind Harmer
4.609
316458AB2-190 GEN2
Solar/Wind Harmer
2.043
971069AG2-661 GEN
Solar/Wind Harmer
3.184
315671AE2-027_GEN
Solar/Wind Harmer
15.073
971647AH1-324 GEN
Solar/Wind Harmer
10.001
971317AH1-138 GEN
Solar/Wind Harmer
2.498
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.84
3142433PROV 92
Solar/Wind Harmer
-0.079
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.88
316294AC1-161 GEN
Solar/Wind Harmer
6.4
3145336SMITFLD
Solar/Wind Harmer
-0.079
970659AG2-427 GEN
Solar/Wind Harmer
10.389
316375AC2-012 GEN
Solar/Wind Harmer
6.761
3150981CHESPKA
Adder
2.171
316381AD1-082 GEN
Solar/Wind Harmer
1.791
944591AF1-124 GEN
Solar/Wind Harmer
89.141
970661AG2-428 GEN
Solar/Wind Harmer
20.686
316072AD1-144
Solar/Wind Harmer
0.393
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.277
3141843SHACKLE
Adder
0.881
316388AE2-253 GEN
Solar/Wind Harmer
1.305
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.39
316093AE2-104_GEN
Solar/Wind Harmer
5.574
939411AE1-173 GEN
Solar/Wind Harmer
95.246
940641AE2-051 GEN
Solar/Wind Harmer
17.731
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
315800Z1-036_GEN1
Solar/Wind Harmer
4.59
3130156CHOWAN
Solar/Wind Harmer
-0.018
3145663CRESWEL
Solar/Wind Harmer
-0.05
971163AH1-040 GEN
Solar/Wind Harmer
16.843
961951AG1-038 GEN
Solar/Wind Harmer
2.358
962861AG1-135 GEN
Solar/Wind Harmer
6.609
3143336POWHATN
Solar/Wind Harmer
2.085
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.357
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.515
316023GEN1_S
Solar/Wind Harmer
1.166
964211AG1-282 GEN
Solar/Wind Harmer
0.518
3141726DUNNSVL
Solar/Wind Harmer
-0.069
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.404
3145683EARLEYS
Solar/Wind Harmer
-0.017
970087AG2-069 GEN
Solar/Wind Harmer
15.954
316336AC2-165 C
Solar/Wind Harmer
2.948
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.899
3150351NORNECKC2
Adder
1.495
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.489
962571AG1-106 GEN
Solar/Wind Harmer
2.397
316174AB2-169 GEN
Solar/Wind Harmer
2.57
316190AA2-174 GEN
Solar/Wind Harmer
0.204
971795AH1-408 GEN
Solar/Wind Harmer
12.407
957481AF2-042 GEN
Solar/Wind Harmer
51.549
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.319
315693AD1-088 GEN
Solar/Wind Harmer
8.129
962491AG1-098 GEN
Solar/Wind Harmer
10.849
3146293MARTNCO
Solar/Wind Harmer
0.1
316212AC1-099_GEN
Solar/Wind Harmer
1.404
972277AH1-723 GEN
Adder
84.694
3144293JTRSVLE
Adder
0.43
NYPJM->LTFIMP_NY
CLTF
2.849
LGEELTFEXP_LGEE->PJM
CLTF
1.614
LAGNLTFEXP_LAGN->PJM
CLTF
7.579
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.219
WECLTFEXP_WEC->PJM
CLTF
0.82
TVALTFEXP_TVA->PJM
CLTF
3.837
CPLELTFEXP_CPLE->PJM
CLTF
8.889
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.077
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.903
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.403
MECLTFEXP_MEC->PJM
CLTF
4.165
SIGELTFEXP_SIGE->PJM
CLTF
0.129

Details for 8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.08 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4415.8
MW Contribution:9.14
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
38.605
3150411LDYSMT5
50/50
28.611
3150381LDYSMT2
50/50
27.382
972213AH1-691 GEN
50/50
4.632
972215AH1-692 GEN
50/50
4.632
963051AG1-154 GEN
50/50
3.563
972189AH1-679 GEN
50/50
3.525
316312AB1-027
Solar/Wind Harmer
0.728
315976AC1-164 GENA
Solar/Wind Harmer
21.995
316169AC1-164_GENC
Solar/Wind Harmer
19.001
315975AC1-164 GENB
Solar/Wind Harmer
0.651
971285AH1-108 GEN
Adder
1.381
316233AE1-074 FULL
Solar/Wind Harmer
0.545
971281AH1-106 GEN
Solar/Wind Harmer
3.292
971283AH1-107 GEN
Solar/Wind Harmer
3.292
316132AB2-190 GEN1
Solar/Wind Harmer
2.042
316369SG1_INVT
Solar/Wind Harmer
3.584
971167AH1-042 GEN
Solar/Wind Harmer
19.197
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
972265AH1-717 GEN
Adder
13.718
3151201GRAVEL4
Adder
12.859
3151191GRAVEL3
Adder
12.697
3151211GRAVEL5
Adder
12.697
971445AH1-216 GEN
Solar/Wind Harmer
12.216
3143873LANEXA
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.589
3138283WHITEMARSH
Solar/Wind Harmer
0.03
3143316POE
Solar/Wind Harmer
-0.077
3151081ELIZAR1
Adder
15.936
3151091ELIZAR2
Adder
15.659
316314AB2-024 C
Solar/Wind Harmer
1.67
3152611GOSPORTB
Adder
2.213
3152621GOSPORTC
Adder
1.878
3152601GOSPORTA
Adder
1.733
316059AD1-063 C
Solar/Wind Harmer
0.438
957871AF2-081 GEN
Solar/Wind Harmer
9.666
315833AF1-017_GEN
Solar/Wind Harmer
3.666
316349AD2-085 GEN
Solar/Wind Harmer
1.717
316311AC2-079 GEN
Solar/Wind Harmer
9.735
319010AE1-072 C
Solar/Wind Harmer
3.9
315662AE1-191 GEN
Solar/Wind Harmer
2.323
315666AE1-190 GEN
Solar/Wind Harmer
0.581
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316305AF2-043 C
Solar/Wind Harmer
0.58
315835AF2-110_GEN
Solar/Wind Harmer
2.396
957601AF2-054 GEN
Solar/Wind Harmer
0.573
3141873WAN 176
Solar/Wind Harmer
-0.004
313526AB2-022
Solar/Wind Harmer
0.515
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.513
3146396TANGLEW
Solar/Wind Harmer
0.35
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
3141913WHIT STONE
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
4.589
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
316315AB2-025 C
Solar/Wind Harmer
0.499
315814AE2-033 C
Solar/Wind Harmer
17.164
3130156CHOWAN
Solar/Wind Harmer
-0.018
3130156CHOWAN
Solar/Wind Harmer
-0.018
941031AE2-094 GEN
Solar/Wind Harmer
34.089
944011AF1-069 GEN
Solar/Wind Harmer
10.681
962981AG1-147 GEN
Solar/Wind Harmer
7.93
315816AE2-034 GEN
Solar/Wind Harmer
1.453
970673AG2-436 GEN
Solar/Wind Harmer
37.641
970673AG2-436 GEN
Solar/Wind Harmer
19.058
971967AH1-528 GEN
Solar/Wind Harmer
33.35
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.56
315733AD1-074 GEN2
Solar/Wind Harmer
3.56
315735AD1-075 GEN1
Solar/Wind Harmer
1.78
965291AG1-394 GEN
Solar/Wind Harmer
1.552
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.622
316318V4-068
Solar/Wind Harmer
0.432
3145893MURPHYS
Solar/Wind Harmer
-0.047
970497AG2-320 GEN
50/50
20.637
3150401LDYSMT4
50/50
28.522
3150371LDYSMT1
50/50
27.56
315051AA1-145 CT1
50/50
1.572
966881AG1-559 GEN
Solar/Wind Harmer
0.674
3142416OLDCHRC
Solar/Wind Harmer
2.177
970293AG2-193 GEN
Solar/Wind Harmer
2.64
3143096IRON208
Adder
0.776
3143096IRON208
Adder
0.76
316473AC1-191 GEN
Solar/Wind Harmer
2.237
3142946ENON
Solar/Wind Harmer
-0.007
3150861SPRUNCD
Adder
0.844
970133AG2-095 GEN
Solar/Wind Harmer
2.286
316382AG1-145 C
Solar/Wind Harmer
0.612
970129AG2-093 GEN
Solar/Wind Harmer
11.374
315778AD1-151 GEN
Solar/Wind Harmer
17.424
965281AG1-393 GEN
Solar/Wind Harmer
2.504
315839AE2-212 C
Solar/Wind Harmer
0.602
3150921YORKTN3
Adder
4.467
3144216WINCHST
Adder
0.67
961611AG1-000B GEN
Solar/Wind Harmer
4.197
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3151221GRAVEL6
Adder
12.845
3151171GRAVELC
Adder
2.471
315773AC2-141 GEN
Solar/Wind Harmer
8.274
3145336SMITFLD
Solar/Wind Harmer
-0.008
315813AE1-149 C
Solar/Wind Harmer
12.293
3144536CHRHLND
Solar/Wind Harmer
-0.003
970659AG2-427 GEN
Solar/Wind Harmer
1.84
3151101ELIZAR3
Adder
16.14
316083AB2-161 GEN
Solar/Wind Harmer
3.169
3144873MCLAUGH
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
88.792
944601AF1-125 GEN
Solar/Wind Harmer
87.406
970661AG2-428 GEN
Solar/Wind Harmer
3.665
3141766HARMONY
Solar/Wind Harmer
1.726
3150391LDYSMT3
50/50
28.468
972195AH1-682 GEN
50/50
3.741
315673AE1-157 GEN
Solar/Wind Harmer
16.835
957411AF2-035 GEN
Solar/Wind Harmer
10.082
970317AG2-208 GEN
Solar/Wind Harmer
9.802
3142296MT RD221
Adder
0.622
3142366NRTHEST
Adder
0.618
3150691DARBY 3
Adder
13.575
3150701DARBY 4
Adder
13.543
3150681DARBY 2
Adder
13.528
3150671DARBY 1
Adder
13.512
316075AC2-137 C
Solar/Wind Harmer
0.567
966871AG1-558 GEN
Solar/Wind Harmer
0.625
966871AG1-558 GEN
Solar/Wind Harmer
0.214
3142946ENON
Solar/Wind Harmer
-0.002
944641AF1-129 GEN
Adder
86.296
3143526WINTERP
Solar/Wind Harmer
-0.105
316240AF1-291 C
Solar/Wind Harmer
0.61
316033AB2-134 GEN
Solar/Wind Harmer
6.469
315697AD1-025 GEN
Solar/Wind Harmer
4.057
971223AH1-071 GEN
Solar/Wind Harmer
2.483
316236AE1-162_GEN
Solar/Wind Harmer
0.595
316036AC1-147 C
Solar/Wind Harmer
0.527
3150991CHESPKB
Adder
1.821
3150991CHESPKB
Adder
1.777
970657AG2-426 GEN
Solar/Wind Harmer
6.095
970657AG2-426 GEN
Solar/Wind Harmer
1.274
316316AC1-027 C
Solar/Wind Harmer
0.598
3142956BIRDNECK
Solar/Wind Harmer
1.046
316185AD1-033 GEN
Solar/Wind Harmer
2.053
3145506HICKORY
Solar/Wind Harmer
-0.077
3145506HICKORY
Solar/Wind Harmer
-0.046
3145506HICKORY
Solar/Wind Harmer
-0.012
316441AF1-014 GEN
Solar/Wind Harmer
1.305
316339AD2-160 GEN
Solar/Wind Harmer
1.305
316018AA1-139 ULT2
Solar/Wind Harmer
1.656
316017AA1-139 ULT1
Solar/Wind Harmer
1.564
3137176SLIGO L2192
Solar/Wind Harmer
-0.076
3146456SLIGO L269
Solar/Wind Harmer
2.278
3130086AYDLETT
Solar/Wind Harmer
-0.077
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.425
316433W1029_GEN2
Solar/Wind Harmer
3.425
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3144356SAPONY
Solar/Wind Harmer
0.645
315742AE1-103 GEN
Solar/Wind Harmer
1.927
3146376EDENTON
Solar/Wind Harmer
0.545
3146376EDENTON
Solar/Wind Harmer
0.545
316487AF1-042 GEN
Solar/Wind Harmer
2.357
972185AH1-677 GEN
Adder
8.883
972187AH1-678 GEN
Adder
4.463
958261AF2-120 GEN
Solar/Wind Harmer
6.788
316065AD1-022 GEN
Solar/Wind Harmer
8.744
970933AG2-581 GEN
Solar/Wind Harmer
16.307
3145893MURPHYS
Solar/Wind Harmer
0.484
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
316077AC2-138 C
Solar/Wind Harmer
0.355
3150341NORNECKC1
Adder
1.57
3150341NORNECKC1
Adder
1.558
316468AD1-105 GEN
Solar/Wind Harmer
1.868
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316181AB2-040 GEN
Solar/Wind Harmer
2.332
316426AA2-053 GEN
Solar/Wind Harmer
1.68
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.861
3145593CAROLNA
Solar/Wind Harmer
0.137
970099AG2-077 GEN
Solar/Wind Harmer
20.612
3145783HORNRTN
Solar/Wind Harmer
1.952
3145783HORNRTN
Solar/Wind Harmer
1.562
3145783HORNRTN
Solar/Wind Harmer
0.488
3145783HORNRTN
Solar/Wind Harmer
0.195
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145933PARMELE
Solar/Wind Harmer
-0.032
3145933PARMELE
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.725
3144293JTRSVLE
Adder
0.43
3144293JTRSVLE
Adder
0.362
226929AD2-058 GEN
Solar/Wind Helper
0.118
972197AH1-683 GEN
50/50
4.454
972219AH1-694 GEN
50/50
3.207
315052AA1-145 CT2
50/50
1.579
966881AG1-559 GEN
Solar/Wind Harmer
0.23
3142416OLDCHRC
Solar/Wind Harmer
-0.056
3142416OLDCHRC
Solar/Wind Harmer
-0.021
3143096IRON208
Adder
0.776
3142543TWELFTH
Solar/Wind Harmer
-0.002
944631AF1-128 GEN
Adder
87.636
3150851SPRUNCC
Adder
0.844
316159AE1-175 C
Solar/Wind Harmer
0.545
3143526WINTERP
Solar/Wind Harmer
-0.105
970129AG2-093 GEN
Solar/Wind Harmer
4.607
316458AB2-190 GEN2
Solar/Wind Harmer
2.042
971069AG2-661 GEN
Solar/Wind Harmer
3.182
315671AE2-027_GEN
Solar/Wind Harmer
15.069
971647AH1-324 GEN
Solar/Wind Harmer
9.998
971317AH1-138 GEN
Solar/Wind Harmer
2.497
3138126ROCKLANDING
Solar/Wind Harmer
0.061
961611AG1-000B GEN
Solar/Wind Harmer
9.836
3142433PROV 92
Solar/Wind Harmer
-0.079
3142433PROV 92
Adder
0.344
3142433PROV 92
Adder
0.344
3143226MDLTHAN
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.879
316294AC1-161 GEN
Solar/Wind Harmer
6.398
3145336SMITFLD
Solar/Wind Harmer
-0.079
970659AG2-427 GEN
Solar/Wind Harmer
10.386
316375AC2-012 GEN
Solar/Wind Harmer
6.758
3150981CHESPKA
Adder
2.17
316381AD1-082 GEN
Solar/Wind Harmer
1.791
944591AF1-124 GEN
Solar/Wind Harmer
89.112
970661AG2-428 GEN
Solar/Wind Harmer
20.679
316072AD1-144
Solar/Wind Harmer
0.393
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.276
3141843SHACKLE
Adder
0.88
316388AE2-253 GEN
Solar/Wind Harmer
1.305
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.39
316093AE2-104_GEN
Solar/Wind Harmer
5.572
939411AE1-173 GEN
Solar/Wind Harmer
95.213
940641AE2-051 GEN
Solar/Wind Harmer
17.725
3146516WINFALL
Solar/Wind Harmer
-0.061
3146516WINFALL
Solar/Wind Harmer
-0.019
3138133OCRAN
Solar/Wind Harmer
-0.011
315800Z1-036_GEN1
Solar/Wind Harmer
4.589
3130156CHOWAN
Solar/Wind Harmer
-0.018
3145663CRESWEL
Solar/Wind Harmer
-0.05
971163AH1-040 GEN
Solar/Wind Harmer
16.838
961951AG1-038 GEN
Solar/Wind Harmer
2.357
962861AG1-135 GEN
Solar/Wind Harmer
6.607
3143336POWHATN
Solar/Wind Harmer
2.084
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.356
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.514
316023GEN1_S
Solar/Wind Harmer
1.166
964211AG1-282 GEN
Solar/Wind Harmer
0.517
3141726DUNNSVL
Solar/Wind Harmer
-0.068
3146173TUNIS
Solar/Wind Harmer
-0.017
970919AG2-571 GEN
Solar/Wind Harmer
5.402
3145683EARLEYS
Solar/Wind Harmer
-0.017
970087AG2-069 GEN
Solar/Wind Harmer
15.949
316336AC2-165 C
Solar/Wind Harmer
2.947
3146263WOODLND
Solar/Wind Harmer
-0.017
960081AF2-299 GEN
Solar/Wind Harmer
1.898
3150351NORNECKC2
Adder
1.495
3145963POPLR C
Solar/Wind Harmer
-0.017
3145823KELFORD
Solar/Wind Harmer
-0.017
316011AB1-132 GEN
Solar/Wind Harmer
3.487
962571AG1-106 GEN
Solar/Wind Harmer
2.396
316174AB2-169 GEN
Solar/Wind Harmer
2.569
316190AA2-174 GEN
Solar/Wind Harmer
0.204
971795AH1-408 GEN
Solar/Wind Harmer
12.402
957481AF2-042 GEN
Solar/Wind Harmer
51.531
3145783HORNRTN
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.319
315693AD1-088 GEN
Solar/Wind Harmer
8.126
962491AG1-098 GEN
Solar/Wind Harmer
10.846
3146293MARTNCO
Solar/Wind Harmer
0.1
316212AC1-099_GEN
Solar/Wind Harmer
1.404
972277AH1-723 GEN
Adder
84.669
3144293JTRSVLE
Adder
0.43
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
970085AG2-068 GEN
Solar/Wind Harmer
10.632
970581AG2-369 GEN
Solar/Wind Harmer
9.144
3146043SEABORD
Solar/Wind Harmer
-0.017
315607AA1-063A GEN
Solar/Wind Harmer
1.709
946281AF1-292 GEN
Solar/Wind Harmer
0.378
3141813NORNECK
Solar/Wind Harmer
-0.017
316087AB2-174 GEN
Solar/Wind Harmer
2.392
315652AC1-086 GEN
Solar/Wind Harmer
18.752
3137643SOCKMAN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146033SCOT NK
Solar/Wind Harmer
-0.065
972193AH1-681 GEN
Adder
3.246
972205AH1-687 GEN
Adder
5.363
970831AG2-522 GEN
Solar/Wind Harmer
4.092
3141843SHACKLE
Adder
0.88
316203AE2-005 GEN
Solar/Wind Harmer
8.161
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.352
316280AD1-041 GEN
Solar/Wind Harmer
1.452
316156AD2-030 GEN
Solar/Wind Harmer
0.511
3141873WAN 176
Solar/Wind Harmer
2.272
316320Y1-086
Solar/Wind Harmer
1.119
316435W1029_GEN3
Solar/Wind Harmer
3.425
3146516WINFALL
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3146376EDENTON
Solar/Wind Harmer
-0.018
962971AG1-146 GEN
Solar/Wind Harmer
3.398
315614AA2-178 GEN
Solar/Wind Harmer
1.938
316484AD2-074 GEN
Solar/Wind Harmer
4.504
970009AG2-005 GEN
Solar/Wind Harmer
2.237
971157AH1-035 GEN
Solar/Wind Harmer
2.207
315737AD1-076 GEN
Solar/Wind Harmer
3.346
3156081AA2-088 GEN
Solar/Wind Harmer
5.701
316313AB2-026
Solar/Wind Harmer
0.474
316258AE1-075 C
Solar/Wind Harmer
0.426
316405AF2-144 C
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
1.771
316404AE1-155 C
Solar/Wind Harmer
3.379
3146206CASHIE
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.619
961681AG1-008 GEN
Solar/Wind Harmer
13.619
316365GEN2_N
Solar/Wind Harmer
1.166
3146173TUNIS
Solar/Wind Harmer
-0.017
3156021HOLLOMANSOL
Solar/Wind Harmer
2.313
316463AE2-346 GEN
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.115
962331AG1-082 GEN
Solar/Wind Harmer
2.138
970917AG2-570 GEN
Solar/Wind Harmer
42.678
3146263WOODLND
Solar/Wind Harmer
-0.017
966621AG1-532 GEN
Solar/Wind Harmer
0.342
3150351NORNECKC2
Adder
1.52
3145963POPLR C
Solar/Wind Harmer
-0.017
971781AH1-399 GEN
Solar/Wind Harmer
1.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
313506AB2-031 GEN
Solar/Wind Harmer
1.344
316317KELFORD C
Solar/Wind Harmer
0.787
3145823KELFORD
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.016
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.016
966801AG1-551 GEN
Solar/Wind Harmer
2.013
316210AC1-098 GEN
Solar/Wind Harmer
2.527
316478AD1-087 GEN
Solar/Wind Harmer
1.384
316486AD2-202 GEN
Solar/Wind Harmer
0.405
972255AH1-712 GEN
Adder
72.658
3144293JTRSVLE
Adder
0.43
227287AC2-120 GEN
Solar/Wind Helper
0.388
226910AB2-157 C
Solar/Wind Helper
0.015
NYPJM->LTFIMP_NY
CLTF
2.848
LGEELTFEXP_LGEE->PJM
CLTF
1.613
LAGNLTFEXP_LAGN->PJM
CLTF
7.576
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.212
WECLTFEXP_WEC->PJM
CLTF
0.819
TVALTFEXP_TVA->PJM
CLTF
3.836
CPLELTFEXP_CPLE->PJM
CLTF
8.886
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.062
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.893
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.398
MECLTFEXP_MEC->PJM
CLTF
4.164
SIGELTFEXP_SIGE->PJM
CLTF
0.129

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.08 %
Rating:1057.5 MVA
Rating Type:B
MVA to Mitigate:1343.9
MW Contribution:5.89
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
2.294
3151051BRUNSWICKS1
50/50
3.716
3151021BRUNSWICKG1
50/50
1.791
970533AG2-339 GEN
50/50
12.931
3151031BRUNSWICKG2
50/50
1.791
970413AG2-270 GEN
50/50
8.961
3151391GASTONA
50/50
0.214
3151411GASTONB
50/50
0.214
3151101ELIZAR3
50/50
7.756
970917AG2-570 GEN
Solar/Wind Harmer
11.479
316478AD1-087 GEN
Solar/Wind Harmer
0.335
316486AD2-202 GEN
Solar/Wind Harmer
0.098
315773AC2-141 GEN
Solar/Wind Harmer
3.189
944581AF1-123 GEN
Solar/Wind Harmer
18.841
944601AF1-125 GEN
Solar/Wind Harmer
18.551
316365GEN2_N
Solar/Wind Harmer
0.183
3146456SLIGO L269
Solar/Wind Harmer
0.08
971153AH1-033 GEN
Solar/Wind Harmer
0.931
316320Y1-086
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.079
316435W1029_GEN3
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3146376EDENTON
Solar/Wind Harmer
0.079
3145796HORNRTN
Solar/Wind Harmer
0.314
3145796HORNRTN
Solar/Wind Harmer
0.079
315614AA2-178 GEN
Solar/Wind Harmer
0.449
971157AH1-035 GEN
Solar/Wind Harmer
0.938
313506AB2-031 GEN
Solar/Wind Harmer
0.241
315737AD1-076 GEN
Solar/Wind Harmer
1.005
3144873MCLAUGH
Solar/Wind Harmer
0.002
3146206CASHIE
Solar/Wind Harmer
0.078
3156021HOLLOMANSOL
Solar/Wind Harmer
0.353
3146263WOODLND
Solar/Wind Harmer
0.078
316463AE2-346 GEN
Solar/Wind Harmer
0.067
316140AB2-099
Solar/Wind Harmer
0.028
962331AG1-082 GEN
Solar/Wind Harmer
0.826
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
970531AG2-338 GEN
50/50
5.172
315242AE2-183_GT2
50/50
2.294
315241AE2-183_GT1
50/50
2.28
972185AH1-677 GEN
50/50
8.27
3151041BRUNSWICKG3
50/50
1.791
972187AH1-678 GEN
50/50
4.109
970933AG2-581 GEN
Solar/Wind Harmer
10.096
970099AG2-077 GEN
Solar/Wind Harmer
11.084
3144356SAPONY
Solar/Wind Harmer
0.732
3145506HICKORY
Solar/Wind Harmer
0.323
3145506HICKORY
Solar/Wind Harmer
0.194
3145506HICKORY
Solar/Wind Harmer
0.049
316185AD1-033 GEN
Solar/Wind Harmer
0.002
316339AD2-160 GEN
Solar/Wind Harmer
0.131
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
316017AA1-139 ULT1
Solar/Wind Harmer
0.045
3137176SLIGO L2192
Solar/Wind Harmer
0.32
3146456SLIGO L269
Solar/Wind Harmer
1.425
3130086AYDLETT
Solar/Wind Harmer
0.322
3146386ELIZ CT
Solar/Wind Harmer
0.08
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.076
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
3146516WINFALL
Solar/Wind Harmer
0.079
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
0.079
3146626S HERTFORD
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.079
3142666NORTHAMPTON
Solar/Wind Harmer
0.047
3146376EDENTON
Solar/Wind Harmer
0.35
3146376EDENTON
Solar/Wind Harmer
0.35
3145796HORNRTN
Solar/Wind Harmer
0.236
316181AB2-040 GEN
Solar/Wind Harmer
0.113
316065AD1-022 GEN
Solar/Wind Harmer
3.592
316036AC1-147 C
Solar/Wind Harmer
0.014
3150991CHESPKB
Adder
0.817
3150991CHESPKB
Adder
0.797
3145593CAROLNA
Solar/Wind Harmer
0.078
3145593CAROLNA
Solar/Wind Harmer
0.078
966811AG1-552 GEN
Solar/Wind Harmer
0.842
3145593CAROLNA
Solar/Wind Harmer
0.097
316426AA2-053 GEN
Solar/Wind Harmer
0.262
3145783HORNRTN
Solar/Wind Harmer
1.378
3145783HORNRTN
Solar/Wind Harmer
1.102
3145783HORNRTN
Solar/Wind Harmer
0.345
3145783HORNRTN
Solar/Wind Harmer
0.138
3146173TUNIS
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145893MURPHYS
Solar/Wind Harmer
0.515
3145893MURPHYS
Solar/Wind Harmer
0.139
316274AC1-208 GEN
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.153
3145933PARMELE
Solar/Wind Harmer
0.076
3145493TOT1
Solar/Wind Harmer
0.176
3145453TOT5
Solar/Wind Harmer
0.105
3145603CNETO
Solar/Wind Harmer
0.07
315742AE1-103 GEN
Solar/Wind Harmer
0.001
961601AG1-000A GEN
Solar/Wind Harmer
1.347
316263AC1-034 GEN
Solar/Wind Harmer
2.877
939181AE1-148 GEN
Solar/Wind Harmer
3.519
316222AC1-221 GEN
Solar/Wind Harmer
0.294
3146843MT LREL
Solar/Wind Harmer
0.069
3146843MT LREL
Solar/Wind Harmer
0.069
964791AG1-342 GEN
Solar/Wind Harmer
1.325
962561AG1-105 GEN
Solar/Wind Harmer
3.278
313527AB2-043 GEN
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Helper
2.674
966871AG1-558 GEN
Solar/Wind Helper
0.173
315821AE2-092 GEN
Solar/Wind Helper
1.114
957521AF2-046 GEN
Solar/Wind Harmer
5.738
961681AG1-008 GEN
Solar/Wind Harmer
5.738
3145893MURPHYS
Solar/Wind Harmer
0.129
3145893MURPHYS
Solar/Wind Harmer
0.077
315724AD1-057 GEN
Solar/Wind Harmer
0.289
316210AC1-098 GEN
Solar/Wind Harmer
0.713
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.076
966801AG1-551 GEN
Solar/Wind Harmer
0.89
316327AA2-057 GEN
Solar/Wind Harmer
0.115
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.381
3146233WITAKRS
Solar/Wind Harmer
0.052
3138543CONSLDL
Solar/Wind Harmer
0.05
3146073TAR RVR
Solar/Wind Harmer
0.076
3146083TARBORO
Solar/Wind Harmer
0.076
961601AG1-000A GEN
Solar/Wind Harmer
5.386
971623AH1-311 GEN
Solar/Wind Harmer
0.151
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145273HOLLAND
Solar/Wind Harmer
0.057
3147043LAWRENC
Solar/Wind Harmer
0.045
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
3.092
3144536CHRHLND
Solar/Wind Harmer
0.011
316283AC2-100 C
Solar/Wind Harmer
0.138
971683AH1-343 GEN
Solar/Wind Harmer
2.355
316131AB2-060 GEN
Solar/Wind Harmer
0.198
964241AG1-285 GEN
Solar/Wind Harmer
3.891
316313AB2-026
Solar/Wind Helper
0.727
316258AE1-075 C
Solar/Wind Helper
0.654
316405AF2-144 C
Solar/Wind Helper
0.545
316473AC1-191 GEN
Solar/Wind Helper
0.782
971451AH1-221 GEN
50/50
5.439
3151531CLOVER1
50/50
2.053
3151391GASTONA
50/50
0.214
3151411GASTONB
50/50
0.214
940641AE2-051 GEN
Solar/Wind Harmer
11.353
970919AG2-571 GEN
Solar/Wind Harmer
4.592
970087AG2-069 GEN
Solar/Wind Harmer
10.271
939411AE1-173 GEN
Solar/Wind Harmer
54.111
957481AF2-042 GEN
Solar/Wind Harmer
27.71
315693AD1-088 GEN
Solar/Wind Harmer
4.301
315687AD1-152 GEN
Solar/Wind Harmer
0.003
316294AC1-161 GEN
Solar/Wind Harmer
1.513
962491AG1-098 GEN
Solar/Wind Harmer
4.96
944591AF1-124 GEN
Solar/Wind Harmer
18.908
316023GEN1_S
Solar/Wind Harmer
0.183
316388AE2-253 GEN
Solar/Wind Harmer
0.253
3146456SLIGO L269
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.257
3146516WINFALL
Solar/Wind Harmer
0.079
316011AB1-132 GEN
Solar/Wind Harmer
1.438
962571AG1-106 GEN
Solar/Wind Harmer
1.125
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.079
316246AF1-032 C
Solar/Wind Harmer
0.035
3145796HORNRTN
Solar/Wind Harmer
0.259
3145796HORNRTN
Solar/Wind Harmer
0.079
960081AF2-299 GEN
Solar/Wind Harmer
0.754
3145663CRESWEL
Solar/Wind Harmer
0.22
971163AH1-040 GEN
Solar/Wind Harmer
6.276
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3150981CHESPKA
Adder
0.974
3146206CASHIE
Solar/Wind Harmer
0.078
971547AH1-271 GEN
Solar/Wind Harmer
1.663
316190AA2-174 GEN
Solar/Wind Harmer
0
3146263WOODLND
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3145783HORNRTN
Solar/Wind Harmer
0.077
3145823KELFORD
Solar/Wind Harmer
0.077
3146173TUNIS
Solar/Wind Harmer
0.077
3145963POPLR C
Solar/Wind Harmer
0.077
3145893MURPHYS
Solar/Wind Harmer
0.308
3145893MURPHYS
Solar/Wind Harmer
0.342
315722AD1-056 GEN
Solar/Wind Harmer
0.488
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316212AC1-099_GEN
Solar/Wind Harmer
0.398
3146293MARTNCO
Solar/Wind Harmer
0.071
316129AC1-054 GEN
Solar/Wind Harmer
0.286
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3146233WITAKRS
Solar/Wind Harmer
0.302
971065AG2-659 GEN
Solar/Wind Harmer
3.242
316494AC1-189 GEN
Solar/Wind Harmer
0.256
961671AG1-007 GEN
Solar/Wind Harmer
0.012
3146083TARBORO
Solar/Wind Harmer
0.076
3145493TOT1
Solar/Wind Harmer
0.337
316359AB2-059 GEN
Solar/Wind Harmer
0.272
316049AB1-081 GEN
Solar/Wind Harmer
0.433
3142053HEARTS
Solar/Wind Harmer
0.133
3145543BTLEBRO
Solar/Wind Harmer
0.076
3145543BTLEBRO
Solar/Wind Harmer
0.06
971795AH1-408 GEN
Solar/Wind Harmer
5.038
316093AE2-104_GEN
Solar/Wind Harmer
1.261
3147043LAWRENC
Adder
0.671
316072AD1-144
Solar/Wind Harmer
0.025
970401AG2-262 GEN
Solar/Wind Harmer
0.405
316003AC1-222 GEN
Solar/Wind Harmer
0.002
316237AB2-079_GEN
Solar/Wind Harmer
0.001
3143226MDLTHAN
Solar/Wind Helper
0.68
3143526WINTERP
Solar/Wind Helper
2.674
316336AC2-165 C
Solar/Wind Helper
2.289
3142543TWELFTH
Solar/Wind Helper
0.016
315244AE2-183_ST
50/50
3.966
963041AG1-153 GEN
50/50
3.626
3151541CLOVER2
50/50
2.044
315779AE2-040
50/50
1.222
941031AE2-094 GEN
Solar/Wind Harmer
26.792
944011AF1-069 GEN
Solar/Wind Harmer
8.754
970673AG2-436 GEN
Solar/Wind Harmer
30.101
970673AG2-436 GEN
Solar/Wind Harmer
20.067
971967AH1-528 GEN
Solar/Wind Harmer
21.652
970085AG2-068 GEN
Solar/Wind Harmer
6.847
970581AG2-369 GEN
Solar/Wind Harmer
5.888
316315AB2-025 C
Solar/Wind Harmer
0.071
315814AE2-033 C
Solar/Wind Harmer
6.9
957871AF2-081 GEN
Solar/Wind Harmer
4.015
319010AE1-072 C
Solar/Wind Harmer
0.405
3146406KITTY HAWK
Solar/Wind Harmer
0.01
313526AB2-022
Solar/Wind Harmer
0.043
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.049
3146396TANGLEW
Solar/Wind Harmer
0.22
315652AC1-086 GEN
Solar/Wind Harmer
8.7
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3146486SUNBURY
Solar/Wind Harmer
0.079
3146486SUNBURY
Solar/Wind Harmer
0.079
3130156CHOWAN
Solar/Wind Harmer
0.079
3130156CHOWAN
Solar/Wind Harmer
0.079
3151081ELIZAR1
Adder
7.217
3151091ELIZAR2
Adder
7.092
316305AF2-043 C
Solar/Wind Harmer
0.001
3145796HORNRTN
Solar/Wind Harmer
0.251
3145796HORNRTN
Solar/Wind Harmer
0.031
315816AE2-034 GEN
Solar/Wind Harmer
0.337
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3130546PLYMOUTH
Solar/Wind Harmer
0.078
315732AD1-074 GEN1
Solar/Wind Harmer
0.449
315733AD1-074 GEN2
Solar/Wind Harmer
0.449
315735AD1-075 GEN1
Solar/Wind Harmer
0.225
3152611GOSPORTB
Adder
0.993
3152621GOSPORTC
Adder
0.843
3152601GOSPORTA
Adder
0.777
3146206CASHIE
Solar/Wind Harmer
0.078
970601AG2-382 GEN
Solar/Wind Harmer
2.911
3137643SOCKMAN
Solar/Wind Harmer
0.311
3145683EARLEYS
Solar/Wind Harmer
0.155
3145683EARLEYS
Solar/Wind Harmer
0.078
3145683EARLEYS
Solar/Wind Harmer
0.078
3145513AHOSKIE
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.077
315607AA1-063A GEN
Solar/Wind Harmer
0.158
3146043SEABORD
Solar/Wind Harmer
0.077
3146033SCOT NK
Solar/Wind Harmer
0.308
3145893MURPHYS
Solar/Wind Harmer
0.208
3145893MURPHYS
Solar/Wind Harmer
0.077
965291AG1-394 GEN
Solar/Wind Harmer
0.341
970831AG2-522 GEN
Solar/Wind Harmer
3.254
316005AA1-067
Solar/Wind Harmer
0.082
3145746EVERETS
Solar/Wind Harmer
0.302
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
3145746EVERETS
Solar/Wind Harmer
0.076
970181AG2-120 GEN
Solar/Wind Harmer
0.946
316319Z2-044 C
Solar/Wind Harmer
0
957861AF2-080 GEN
Solar/Wind Harmer
3.273
316420AA1-050 GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.076
3145573BETHELC
Solar/Wind Harmer
0.076
315835AF2-110_GEN
Solar/Wind Harmer
0.515
3147173SINAI
Solar/Wind Harmer
0.072
3147243WELCO
Solar/Wind Harmer
0.045
316118AC1-105 GEN
Solar/Wind Harmer
0.183
316311AC2-079 GEN
Solar/Wind Harmer
1.874
315833AF1-017_GEN
Solar/Wind Harmer
0
316349AD2-085 GEN
Solar/Wind Harmer
0.045
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970865AG2-541 GEN
Solar/Wind Harmer
2.076
316233AE1-074 FULL
Solar/Wind Helper
0.785
270494AE1-108_GEN
Solar/Wind Helper
1.529
NYPJM->LTFIMP_NY
CLTF
0.638
LAGNLTFEXP_LAGN->PJM
CLTF
3.43
LGEELTFEXP_LGEE->PJM
CLTF
0.533
WECLTFEXP_WEC->PJM
CLTF
0.278
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.518
TVALTFEXP_TVA->PJM
CLTF
1.701
CPLELTFEXP_CPLE->PJM
CLTF
5.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.56
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.686
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.763
MECLTFEXP_MEC->PJM
CLTF
1.546
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.5 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1549.8
MW Contribution:7.75
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
3.966
963041AG1-153 GEN
50/50
3.626
941031AE2-094 GEN
Solar/Wind Harmer
30.645
944011AF1-069 GEN
Solar/Wind Harmer
9.602
970673AG2-436 GEN
Solar/Wind Harmer
33.304
970673AG2-436 GEN
Solar/Wind Harmer
16.863
971967AH1-528 GEN
Solar/Wind Harmer
28.583
970085AG2-068 GEN
Solar/Wind Harmer
9.015
970581AG2-369 GEN
Solar/Wind Harmer
7.753
316315AB2-025 C
Solar/Wind Harmer
0.265
315814AE2-033 C
Solar/Wind Harmer
9.126
957871AF2-081 GEN
Solar/Wind Harmer
4.531
319010AE1-072 C
Solar/Wind Harmer
1.83
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.242
316321Z2-027
Solar/Wind Harmer
0.242
3146396TANGLEW
Solar/Wind Harmer
0.165
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315652AC1-086 GEN
Solar/Wind Harmer
10.001
315611Z1-036_GEN2
Solar/Wind Harmer
2.194
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3151081ELIZAR1
Adder
7.217
3151091ELIZAR2
Adder
7.092
316305AF2-043 C
Solar/Wind Harmer
0.266
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.003
946281AF1-292 GEN
Solar/Wind Harmer
0.198
315816AE2-034 GEN
Solar/Wind Harmer
0.713
316087AB2-174 GEN
Solar/Wind Harmer
1.254
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.775
315733AD1-074 GEN2
Solar/Wind Harmer
1.775
315735AD1-075 GEN1
Solar/Wind Harmer
0.888
3152611GOSPORTB
Adder
0.993
3152621GOSPORTC
Adder
0.843
3152601GOSPORTA
Adder
0.777
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.833
3137643SOCKMAN
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.076
961941AG1-037 GEN
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.877
3146043SEABORD
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.034
316318V4-068
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
4.284
316005AA1-067
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
-0.034
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.121
316319Z2-044 C
Solar/Wind Harmer
0.472
957861AF2-080 GEN
Solar/Wind Harmer
3.732
316420AA1-050 GEN
Solar/Wind Harmer
0.974
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
315835AF2-110_GEN
Solar/Wind Harmer
1.053
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.547
316311AC2-079 GEN
Solar/Wind Harmer
3.698
315833AF1-017_GEN
Solar/Wind Harmer
1.388
316349AD2-085 GEN
Solar/Wind Harmer
0.65
316239AB2-077_GEN
Solar/Wind Harmer
0.22
316238AB2-078_GEN
Solar/Wind Harmer
0.22
970865AG2-541 GEN
Solar/Wind Harmer
2.733
270455AD2-022 GEN
Solar/Wind Harmer
1.2
270457AD2-023 GEN
Solar/Wind Harmer
0.608
316233AE1-074 FULL
Solar/Wind Helper
0.785
270494AE1-108_GEN
Solar/Wind Helper
1.53
3151031BRUNSWICKG2
50/50
1.791
970917AG2-570 GEN
Solar/Wind Harmer
36.273
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.273
315773AC2-141 GEN
Solar/Wind Harmer
4.105
944581AF1-123 GEN
Solar/Wind Harmer
42.771
944601AF1-125 GEN
Solar/Wind Harmer
42.103
316365GEN2_N
Solar/Wind Harmer
0.619
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.103
316320Y1-086
Solar/Wind Harmer
0.527
3146516WINFALL
Solar/Wind Harmer
-0.009
316435W1029_GEN3
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3146376EDENTON
Solar/Wind Harmer
-0.009
3151101ELIZAR3
Adder
7.309
3145796HORNRTN
Solar/Wind Harmer
-0.035
3145796HORNRTN
Solar/Wind Harmer
-0.009
966621AG1-532 GEN
Solar/Wind Harmer
0.179
315614AA2-178 GEN
Solar/Wind Harmer
0.951
971157AH1-035 GEN
Solar/Wind Harmer
1.098
313506AB2-031 GEN
Solar/Wind Harmer
0.706
315737AD1-076 GEN
Solar/Wind Harmer
1.668
3144873MCLAUGH
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.177
3146263WOODLND
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.141
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.088
316317KELFORD C
Solar/Wind Harmer
0.41
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
6.824
961681AG1-008 GEN
Solar/Wind Harmer
6.824
3145893MURPHYS
Solar/Wind Harmer
0.06
3145893MURPHYS
Solar/Wind Harmer
-0.009
315724AD1-057 GEN
Solar/Wind Harmer
0.498
316210AC1-098 GEN
Solar/Wind Harmer
1.355
3156081AA2-088 GEN
Solar/Wind Harmer
2.797
970533AG2-339 GEN
50/50
12.93
970531AG2-338 GEN
50/50
5.172
315242AE2-183_GT2
50/50
2.294
315241AE2-183_GT1
50/50
2.28
972185AH1-677 GEN
50/50
8.27
3151041BRUNSWICKG3
50/50
1.791
972187AH1-678 GEN
50/50
4.109
970933AG2-581 GEN
Solar/Wind Harmer
13.293
970099AG2-077 GEN
Solar/Wind Harmer
14.593
3144356SAPONY
Solar/Wind Harmer
0.343
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.958
316339AD2-160 GEN
Solar/Wind Harmer
0.612
316018AA1-139 ULT2
Solar/Wind Harmer
0.776
316017AA1-139 ULT1
Solar/Wind Harmer
0.733
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.069
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
3142956BIRDNECK
Solar/Wind Harmer
0.48
316316AC1-027 C
Solar/Wind Harmer
0.274
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.613
316433W1029_GEN2
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
0.263
3146376EDENTON
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
1.224
316065AD1-022 GEN
Solar/Wind Harmer
4.383
316036AC1-147 C
Solar/Wind Harmer
0.236
3150991CHESPKB
Adder
0.817
3150991CHESPKB
Adder
0.797
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
316426AA2-053 GEN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
1.034
3145783HORNRTN
Solar/Wind Harmer
0.827
3145783HORNRTN
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
0.103
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.241
3145893MURPHYS
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
0.931
3145933PARMELE
Solar/Wind Harmer
-0.017
3145933PARMELE
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
315742AE1-103 GEN
Solar/Wind Harmer
0.89
961601AG1-000A GEN
Solar/Wind Harmer
3.345
316263AC1-034 GEN
Solar/Wind Harmer
3.987
939181AE1-148 GEN
Solar/Wind Harmer
4.633
316222AC1-221 GEN
Solar/Wind Harmer
0.805
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
964791AG1-342 GEN
Solar/Wind Harmer
1.656
962561AG1-105 GEN
Solar/Wind Harmer
4.315
313527AB2-043 GEN
Solar/Wind Harmer
1.172
3143526WINTERP
Solar/Wind Helper
2.674
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.072
316327AA2-057 GEN
Solar/Wind Harmer
0.866
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.388
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.245
960061AF2-297 GEN
Solar/Wind Harmer
4.071
3144536CHRHLND
Solar/Wind Harmer
-0.001
315243AE2-183_GT3
50/50
2.294
3151051BRUNSWICKS1
50/50
3.716
3151021BRUNSWICKG1
50/50
1.791
971451AH1-221 GEN
50/50
5.438
940641AE2-051 GEN
Solar/Wind Harmer
14.948
970919AG2-571 GEN
Solar/Wind Harmer
4.592
970087AG2-069 GEN
Solar/Wind Harmer
13.523
939411AE1-173 GEN
Solar/Wind Harmer
71.246
957481AF2-042 GEN
Solar/Wind Harmer
36.481
315693AD1-088 GEN
Solar/Wind Harmer
5.033
315687AD1-152 GEN
Solar/Wind Harmer
1.199
316294AC1-161 GEN
Solar/Wind Harmer
3.174
962491AG1-098 GEN
Solar/Wind Harmer
6.529
944591AF1-124 GEN
Solar/Wind Harmer
42.925
316023GEN1_S
Solar/Wind Harmer
0.619
316388AE2-253 GEN
Solar/Wind Harmer
0.612
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.86
962571AG1-106 GEN
Solar/Wind Harmer
1.278
315800Z1-036_GEN1
Solar/Wind Harmer
2.194
3130156CHOWAN
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.179
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.993
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.264
316375AC2-012 GEN
Solar/Wind Harmer
3.032
3150981CHESPKA
Adder
0.974
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.19
316190AA2-174 GEN
Solar/Wind Harmer
0.107
3146263WOODLND
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.257
315722AD1-056 GEN
Solar/Wind Harmer
0.905
316174AB2-169 GEN
Solar/Wind Harmer
1.334
316212AC1-099_GEN
Solar/Wind Harmer
0.753
3146293MARTNCO
Solar/Wind Harmer
0.053
316129AC1-054 GEN
Solar/Wind Harmer
0.75
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
-0.034
971065AG2-659 GEN
Solar/Wind Harmer
4.268
316494AC1-189 GEN
Solar/Wind Harmer
0.918
961671AG1-007 GEN
Solar/Wind Harmer
0.108
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.253
316359AB2-059 GEN
Solar/Wind Harmer
1.147
316049AB1-081 GEN
Solar/Wind Harmer
0.918
3142053HEARTS
Solar/Wind Harmer
0.1
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
971795AH1-408 GEN
Solar/Wind Harmer
6.367
316093AE2-104_GEN
Solar/Wind Harmer
2.449
3147043LAWRENC
Adder
0.671
316072AD1-144
Solar/Wind Harmer
0.159
970401AG2-262 GEN
Solar/Wind Harmer
0.506
316003AC1-222 GEN
Solar/Wind Harmer
0.745
316237AB2-079_GEN
Solar/Wind Harmer
0.22
3143226MDLTHAN
Solar/Wind Helper
0.68
3143526WINTERP
Solar/Wind Helper
2.674
316336AC2-165 C
Solar/Wind Helper
2.289
3142543TWELFTH
Solar/Wind Helper
0.016
966871AG1-558 GEN
Solar/Wind Helper
0.173
315821AE2-092 GEN
Solar/Wind Helper
1.115
316283AC2-100 C
Solar/Wind Harmer
0.745
971683AH1-343 GEN
Solar/Wind Harmer
3.1
316131AB2-060 GEN
Solar/Wind Harmer
0.765
964241AG1-285 GEN
Solar/Wind Harmer
5.121
316313AB2-026
Solar/Wind Helper
0.727
316258AE1-075 C
Solar/Wind Helper
0.655
316405AF2-144 C
Solar/Wind Helper
0.545
316473AC1-191 GEN
Solar/Wind Helper
0.782
NYPJM->LTFIMP_NY
CLTF
0.637
LGEELTFEXP_LGEE->PJM
CLTF
0.533
LAGNLTFEXP_LAGN->PJM
CLTF
3.429
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.517
WECLTFEXP_WEC->PJM
CLTF
0.278
TVALTFEXP_TVA->PJM
CLTF
1.701
CPLELTFEXP_CPLE->PJM
CLTF
5.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.555
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.761
MECLTFEXP_MEC->PJM
CLTF
1.546
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for 8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-6MDLTHAN 500.0/230.0 kV Ckt 1 transformer
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.5 %
Rating:1265.1 MVA
Rating Type:C
MVA to Mitigate:1549.8
MW Contribution:7.75
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
3.966
963041AG1-153 GEN
50/50
3.626
941031AE2-094 GEN
Solar/Wind Harmer
30.645
944011AF1-069 GEN
Solar/Wind Harmer
9.602
970673AG2-436 GEN
Solar/Wind Harmer
33.304
970673AG2-436 GEN
Solar/Wind Harmer
16.863
971967AH1-528 GEN
Solar/Wind Harmer
28.583
970085AG2-068 GEN
Solar/Wind Harmer
9.015
970581AG2-369 GEN
Solar/Wind Harmer
7.753
316315AB2-025 C
Solar/Wind Harmer
0.265
315814AE2-033 C
Solar/Wind Harmer
9.126
957871AF2-081 GEN
Solar/Wind Harmer
4.531
319010AE1-072 C
Solar/Wind Harmer
1.83
3146406KITTY HAWK
Solar/Wind Harmer
0.008
313526AB2-022
Solar/Wind Harmer
0.242
316321Z2-027
Solar/Wind Harmer
0.242
3146396TANGLEW
Solar/Wind Harmer
0.165
3145176PASQUOTANK
Solar/Wind Harmer
-0.006
315652AC1-086 GEN
Solar/Wind Harmer
10.001
315611Z1-036_GEN2
Solar/Wind Harmer
2.194
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3130156CHOWAN
Solar/Wind Harmer
-0.009
3151081ELIZAR1
Adder
7.217
3151091ELIZAR2
Adder
7.092
316305AF2-043 C
Solar/Wind Harmer
0.266
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.003
946281AF1-292 GEN
Solar/Wind Harmer
0.198
315816AE2-034 GEN
Solar/Wind Harmer
0.713
316087AB2-174 GEN
Solar/Wind Harmer
1.254
3130546PLYMOUTH
Solar/Wind Harmer
-0.009
315732AD1-074 GEN1
Solar/Wind Harmer
1.775
315733AD1-074 GEN2
Solar/Wind Harmer
1.775
315735AD1-075 GEN1
Solar/Wind Harmer
0.888
3152611GOSPORTB
Adder
0.993
3152621GOSPORTC
Adder
0.843
3152601GOSPORTA
Adder
0.777
3146206CASHIE
Solar/Wind Harmer
-0.009
970601AG2-382 GEN
Solar/Wind Harmer
3.833
3137643SOCKMAN
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145513AHOSKIE
Solar/Wind Harmer
0.076
961941AG1-037 GEN
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.009
315607AA1-063A GEN
Solar/Wind Harmer
0.877
3146043SEABORD
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.034
316318V4-068
Solar/Wind Harmer
0.216
3145893MURPHYS
Solar/Wind Harmer
-0.023
3145893MURPHYS
Solar/Wind Harmer
-0.009
965291AG1-394 GEN
Solar/Wind Harmer
0.766
970831AG2-522 GEN
Solar/Wind Harmer
4.284
316005AA1-067
Solar/Wind Harmer
0.173
3145746EVERETS
Solar/Wind Harmer
-0.034
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
970181AG2-120 GEN
Solar/Wind Harmer
1.121
316319Z2-044 C
Solar/Wind Harmer
0.472
957861AF2-080 GEN
Solar/Wind Harmer
3.732
316420AA1-050 GEN
Solar/Wind Harmer
0.974
315243AE2-183_GT3
50/50
2.294
3151051BRUNSWICKS1
50/50
3.716
3151021BRUNSWICKG1
50/50
1.791
971451AH1-221 GEN
50/50
5.438
940641AE2-051 GEN
Solar/Wind Harmer
14.948
970919AG2-571 GEN
Solar/Wind Harmer
4.592
970087AG2-069 GEN
Solar/Wind Harmer
13.523
939411AE1-173 GEN
Solar/Wind Harmer
71.246
957481AF2-042 GEN
Solar/Wind Harmer
36.481
315693AD1-088 GEN
Solar/Wind Harmer
5.033
315687AD1-152 GEN
Solar/Wind Harmer
1.199
316294AC1-161 GEN
Solar/Wind Harmer
3.174
962491AG1-098 GEN
Solar/Wind Harmer
6.529
944591AF1-124 GEN
Solar/Wind Harmer
42.925
316023GEN1_S
Solar/Wind Harmer
0.619
316388AE2-253 GEN
Solar/Wind Harmer
0.612
3146456SLIGO L269
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.029
3146516WINFALL
Solar/Wind Harmer
-0.009
316011AB1-132 GEN
Solar/Wind Harmer
1.86
962571AG1-106 GEN
Solar/Wind Harmer
1.278
315800Z1-036_GEN1
Solar/Wind Harmer
2.194
3130156CHOWAN
Solar/Wind Harmer
-0.009
316246AF1-032 C
Solar/Wind Harmer
0.179
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.009
960081AF2-299 GEN
Solar/Wind Harmer
0.993
3145663CRESWEL
Solar/Wind Harmer
-0.025
971163AH1-040 GEN
Solar/Wind Harmer
8.264
316375AC2-012 GEN
Solar/Wind Harmer
3.032
3150981CHESPKA
Adder
0.974
3146206CASHIE
Solar/Wind Harmer
-0.009
971547AH1-271 GEN
Solar/Wind Harmer
2.19
316190AA2-174 GEN
Solar/Wind Harmer
0.107
3146263WOODLND
Solar/Wind Harmer
-0.009
3145683EARLEYS
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.009
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.257
315722AD1-056 GEN
Solar/Wind Harmer
0.905
316174AB2-169 GEN
Solar/Wind Harmer
1.334
316212AC1-099_GEN
Solar/Wind Harmer
0.753
3146293MARTNCO
Solar/Wind Harmer
0.053
3145573BETHELC
Solar/Wind Harmer
-0.008
3145573BETHELC
Solar/Wind Harmer
-0.008
315835AF2-110_GEN
Solar/Wind Harmer
1.053
3147173SINAI
Solar/Wind Harmer
-0.008
3147243WELCO
Solar/Wind Harmer
-0.005
316118AC1-105 GEN
Solar/Wind Harmer
0.547
316311AC2-079 GEN
Solar/Wind Harmer
3.698
315833AF1-017_GEN
Solar/Wind Harmer
1.388
316349AD2-085 GEN
Solar/Wind Harmer
0.65
316239AB2-077_GEN
Solar/Wind Harmer
0.22
316238AB2-078_GEN
Solar/Wind Harmer
0.22
970865AG2-541 GEN
Solar/Wind Harmer
2.733
270455AD2-022 GEN
Solar/Wind Harmer
1.2
270457AD2-023 GEN
Solar/Wind Harmer
0.608
316233AE1-074 FULL
Solar/Wind Helper
0.785
270494AE1-108_GEN
Solar/Wind Helper
1.53
316129AC1-054 GEN
Solar/Wind Harmer
0.75
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
-0.034
971065AG2-659 GEN
Solar/Wind Harmer
4.268
316494AC1-189 GEN
Solar/Wind Harmer
0.918
961671AG1-007 GEN
Solar/Wind Harmer
0.108
3146083TARBORO
Solar/Wind Harmer
-0.008
3145493TOT1
Solar/Wind Harmer
0.253
316359AB2-059 GEN
Solar/Wind Harmer
1.147
316049AB1-081 GEN
Solar/Wind Harmer
0.918
3142053HEARTS
Solar/Wind Harmer
0.1
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.007
971795AH1-408 GEN
Solar/Wind Harmer
6.367
316093AE2-104_GEN
Solar/Wind Harmer
2.449
3147043LAWRENC
Adder
0.671
316072AD1-144
Solar/Wind Harmer
0.159
970401AG2-262 GEN
Solar/Wind Harmer
0.506
316003AC1-222 GEN
Solar/Wind Harmer
0.745
316237AB2-079_GEN
Solar/Wind Harmer
0.22
3143226MDLTHAN
Solar/Wind Helper
0.68
3143526WINTERP
Solar/Wind Helper
2.674
316336AC2-165 C
Solar/Wind Helper
2.289
3142543TWELFTH
Solar/Wind Helper
0.016
970533AG2-339 GEN
50/50
12.93
970531AG2-338 GEN
50/50
5.172
315242AE2-183_GT2
50/50
2.294
315241AE2-183_GT1
50/50
2.28
972185AH1-677 GEN
50/50
8.27
3151041BRUNSWICKG3
50/50
1.791
972187AH1-678 GEN
50/50
4.109
970933AG2-581 GEN
Solar/Wind Harmer
13.293
970099AG2-077 GEN
Solar/Wind Harmer
14.593
3144356SAPONY
Solar/Wind Harmer
0.343
3145506HICKORY
Solar/Wind Harmer
-0.036
3145506HICKORY
Solar/Wind Harmer
-0.022
3145506HICKORY
Solar/Wind Harmer
-0.005
316185AD1-033 GEN
Solar/Wind Harmer
0.958
316339AD2-160 GEN
Solar/Wind Harmer
0.612
316018AA1-139 ULT2
Solar/Wind Harmer
0.776
316017AA1-139 ULT1
Solar/Wind Harmer
0.733
3137176SLIGO L2192
Solar/Wind Harmer
-0.036
3146456SLIGO L269
Solar/Wind Harmer
1.069
3130086AYDLETT
Solar/Wind Harmer
-0.036
3146386ELIZ CT
Solar/Wind Harmer
-0.009
3142956BIRDNECK
Solar/Wind Harmer
0.48
316316AC1-027 C
Solar/Wind Harmer
0.274
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.613
316433W1029_GEN2
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3146376EDENTON
Solar/Wind Harmer
0.263
3146376EDENTON
Solar/Wind Harmer
0.263
3145796HORNRTN
Solar/Wind Harmer
-0.026
316181AB2-040 GEN
Solar/Wind Harmer
1.224
316065AD1-022 GEN
Solar/Wind Harmer
4.383
316036AC1-147 C
Solar/Wind Harmer
0.236
3150991CHESPKB
Adder
0.817
3150991CHESPKB
Adder
0.797
3145593CAROLNA
Solar/Wind Harmer
-0.009
3145593CAROLNA
Solar/Wind Harmer
-0.009
966811AG1-552 GEN
Solar/Wind Harmer
0.981
3145593CAROLNA
Solar/Wind Harmer
0.072
316426AA2-053 GEN
Solar/Wind Harmer
0.881
3145783HORNRTN
Solar/Wind Harmer
1.034
3145783HORNRTN
Solar/Wind Harmer
0.827
3145783HORNRTN
Solar/Wind Harmer
0.258
3145783HORNRTN
Solar/Wind Harmer
0.103
3146173TUNIS
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145893MURPHYS
Solar/Wind Harmer
0.241
3145893MURPHYS
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
0.931
3145933PARMELE
Solar/Wind Harmer
-0.017
3145933PARMELE
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.132
3145453TOT5
Solar/Wind Harmer
0.079
3145603CNETO
Solar/Wind Harmer
0.053
315742AE1-103 GEN
Solar/Wind Harmer
0.89
961601AG1-000A GEN
Solar/Wind Harmer
3.345
316263AC1-034 GEN
Solar/Wind Harmer
3.987
939181AE1-148 GEN
Solar/Wind Harmer
4.633
316222AC1-221 GEN
Solar/Wind Harmer
0.805
3146843MT LREL
Solar/Wind Harmer
-0.008
3146843MT LREL
Solar/Wind Harmer
-0.008
964791AG1-342 GEN
Solar/Wind Harmer
1.656
962561AG1-105 GEN
Solar/Wind Harmer
4.315
313527AB2-043 GEN
Solar/Wind Harmer
1.172
3143526WINTERP
Solar/Wind Helper
2.674
966871AG1-558 GEN
Solar/Wind Helper
0.173
315821AE2-092 GEN
Solar/Wind Helper
1.115
3151031BRUNSWICKG2
50/50
1.791
970917AG2-570 GEN
Solar/Wind Harmer
36.273
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.273
315773AC2-141 GEN
Solar/Wind Harmer
4.105
944581AF1-123 GEN
Solar/Wind Harmer
42.771
944601AF1-125 GEN
Solar/Wind Harmer
42.103
316365GEN2_N
Solar/Wind Harmer
0.619
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.103
316320Y1-086
Solar/Wind Harmer
0.527
3146516WINFALL
Solar/Wind Harmer
-0.009
316435W1029_GEN3
Solar/Wind Harmer
1.613
3146626S HERTFORD
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3146376EDENTON
Solar/Wind Harmer
-0.009
3151101ELIZAR3
Adder
7.309
3145796HORNRTN
Solar/Wind Harmer
-0.035
3145796HORNRTN
Solar/Wind Harmer
-0.009
966621AG1-532 GEN
Solar/Wind Harmer
0.179
315614AA2-178 GEN
Solar/Wind Harmer
0.951
971157AH1-035 GEN
Solar/Wind Harmer
1.098
313506AB2-031 GEN
Solar/Wind Harmer
0.706
315737AD1-076 GEN
Solar/Wind Harmer
1.668
3144873MCLAUGH
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
-0.009
3156021HOLLOMANSOL
Solar/Wind Harmer
1.177
3146263WOODLND
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.141
316140AB2-099
Solar/Wind Harmer
0.059
962331AG1-082 GEN
Solar/Wind Harmer
1.088
316317KELFORD C
Solar/Wind Harmer
0.41
3145823KELFORD
Solar/Wind Harmer
-0.009
3146173TUNIS
Solar/Wind Harmer
-0.009
3145963POPLR C
Solar/Wind Harmer
-0.009
957521AF2-046 GEN
Solar/Wind Harmer
6.824
961681AG1-008 GEN
Solar/Wind Harmer
6.824
3145893MURPHYS
Solar/Wind Harmer
0.06
3145893MURPHYS
Solar/Wind Harmer
-0.009
315724AD1-057 GEN
Solar/Wind Harmer
0.498
316210AC1-098 GEN
Solar/Wind Harmer
1.355
3156081AA2-088 GEN
Solar/Wind Harmer
2.797
3145933PARMELE
Solar/Wind Harmer
-0.009
966801AG1-551 GEN
Solar/Wind Harmer
1.072
316327AA2-057 GEN
Solar/Wind Harmer
0.866
3145746EVERETS
Solar/Wind Harmer
-0.009
3145746EVERETS
Solar/Wind Harmer
-0.009
3146233WITAKRS
Solar/Wind Harmer
0.179
3146233WITAKRS
Solar/Wind Harmer
-0.006
3138543CONSLDL
Solar/Wind Harmer
-0.006
3146073TAR RVR
Solar/Wind Harmer
-0.008
3146083TARBORO
Solar/Wind Harmer
-0.008
961601AG1-000A GEN
Solar/Wind Harmer
3.388
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145543BTLEBRO
Solar/Wind Harmer
-0.008
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.005
316248AF1-058 C
Solar/Wind Harmer
0.245
960061AF2-297 GEN
Solar/Wind Harmer
4.071
3144536CHRHLND
Solar/Wind Harmer
-0.001
316283AC2-100 C
Solar/Wind Harmer
0.745
971683AH1-343 GEN
Solar/Wind Harmer
3.1
316131AB2-060 GEN
Solar/Wind Harmer
0.765
964241AG1-285 GEN
Solar/Wind Harmer
5.121
316313AB2-026
Solar/Wind Helper
0.727
316258AE1-075 C
Solar/Wind Helper
0.655
316405AF2-144 C
Solar/Wind Helper
0.545
316473AC1-191 GEN
Solar/Wind Helper
0.782
NYPJM->LTFIMP_NY
CLTF
0.637
LAGNLTFEXP_LAGN->PJM
CLTF
3.429
LGEELTFEXP_LGEE->PJM
CLTF
0.533
WECLTFEXP_WEC->PJM
CLTF
0.278
CBM South 2LTFEXP_CBM-S2->PJM
CBM
11.517
TVALTFEXP_TVA->PJM
CLTF
1.701
CPLELTFEXP_CPLE->PJM
CLTF
5.449
CBM West 2LTFEXP_CBM-W2->PJM
CBM
17.555
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.681
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.761
MECLTFEXP_MEC->PJM
CLTF
1.546
SIGELTFEXP_SIGE->PJM
CLTF
0.045

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 574_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5650.14
MW Contribution:14.6
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
49.132
315243AE2-183_GT3
50/50
5.558
3151051BRUNSWICKS1
50/50
9.077
3151021BRUNSWICKG1
50/50
4.373
971451AH1-221 GEN
50/50
13.283
3150981CHESPKA
50/50
4.07
3150851SPRUNCC
50/50
1.461
3152331SURRY 2
50/50
12.331
3143226MDLTHAN
Solar/Wind Harmer
0.368
940641AE2-051 GEN
Solar/Wind Harmer
28.054
939411AE1-173 GEN
Solar/Wind Harmer
145.057
3143526WINTERP
Solar/Wind Harmer
1.742
970919AG2-571 GEN
Solar/Wind Harmer
11.363
970087AG2-069 GEN
Solar/Wind Harmer
25.456
316294AC1-161 GEN
Solar/Wind Harmer
5.4
944591AF1-124 GEN
Solar/Wind Harmer
69.98
316375AC2-012 GEN
Solar/Wind Harmer
0.008
316388AE2-253 GEN
Solar/Wind Harmer
0.96
3146456SLIGO L269
Solar/Wind Harmer
0.306
316246AF1-032 C
Solar/Wind Harmer
0.137
316093AE2-104_GEN
Solar/Wind Harmer
5.099
970661AG2-428 GEN
Solar/Wind Harmer
30.138
316381AD1-082 GEN
Solar/Wind Harmer
0.316
970659AG2-427 GEN
Solar/Wind Harmer
14.649
316072AD1-144
Solar/Wind Harmer
0.109
3146516WINFALL
Solar/Wind Harmer
0.972
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
1.197
957481AF2-042 GEN
Solar/Wind Harmer
79.695
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
5.25
3130156CHOWAN
Solar/Wind Harmer
0.294
3151171GRAVELC
Adder
3.13
961611AG1-000B GEN
Solar/Wind Harmer
15.335
315671AE2-027_GEN
Solar/Wind Harmer
18.679
316023GEN1_S
Solar/Wind Harmer
0.655
971647AH1-324 GEN
Solar/Wind Harmer
12.413
3145663CRESWEL
Solar/Wind Harmer
0.81
971163AH1-040 GEN
Solar/Wind Harmer
23.157
315693AD1-088 GEN
Solar/Wind Harmer
13.873
971069AG2-661 GEN
Solar/Wind Harmer
5.126
962491AG1-098 GEN
Solar/Wind Harmer
16.401
316458AB2-190 GEN2
Solar/Wind Harmer
1.538
970129AG2-093 GEN
Solar/Wind Harmer
8.145
960081AF2-299 GEN
Solar/Wind Harmer
2.73
3138126ROCKLANDING
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
1.134
3145893MURPHYS
Solar/Wind Harmer
1.26
3146206CASHIE
Solar/Wind Harmer
0.283
971547AH1-271 GEN
Solar/Wind Harmer
6.043
3146173TUNIS
Solar/Wind Harmer
0.281
3142543TWELFTH
Solar/Wind Harmer
0.027
3145683EARLEYS
Solar/Wind Harmer
0.279
316011AB1-132 GEN
Solar/Wind Harmer
5.071
962571AG1-106 GEN
Solar/Wind Harmer
3.968
971795AH1-408 GEN
Solar/Wind Harmer
18.591
3146263WOODLND
Solar/Wind Harmer
0.278
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
2.5
316336AC2-165 C
Solar/Wind Harmer
0.011
971317AH1-138 GEN
Solar/Wind Harmer
2.057
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
0.907
3145796HORNRTN
Solar/Wind Harmer
0.275
3145783HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
316174AB2-169 GEN
Solar/Wind Harmer
0.007
316159AE1-175 C
Solar/Wind Harmer
0.235
944631AF1-128 GEN
Adder
128.871
315687AD1-152 GEN
Solar/Wind Harmer
0.009
316212AC1-099_GEN
Solar/Wind Harmer
1.386
316129AC1-054 GEN
Solar/Wind Harmer
1.006
971065AG2-659 GEN
Solar/Wind Harmer
11.378
3146293MARTNCO
Solar/Wind Harmer
0.246
315722AD1-056 GEN
Solar/Wind Harmer
1.662
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316494AC1-189 GEN
Solar/Wind Harmer
0.872
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3146233WITAKRS
Solar/Wind Harmer
1.019
961671AG1-007 GEN
Solar/Wind Harmer
0.039
3146083TARBORO
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
1.136
3142433PROV 92
Solar/Wind Harmer
1.012
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
316359AB2-059 GEN
Solar/Wind Harmer
0.906
316049AB1-081 GEN
Solar/Wind Harmer
1.444
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.444
970685AG2-442 GEN
Solar/Wind Harmer
18.609
970401AG2-262 GEN
Solar/Wind Harmer
1.452
963171AG1-166 GEN
Solar/Wind Harmer
1.316
971563AH1-280 GEN
Solar/Wind Harmer
2.632
3144293JTRSVLE
Adder
0.785
971777AH1-397 GEN
Solar/Wind Harmer
0.643
3141843SHACKLE
Adder
1.244
3141766HARMONY
Solar/Wind Harmer
0.048
3142416OLDCHRC
Solar/Wind Harmer
0.623
3142416OLDCHRC
Solar/Wind Harmer
0.239
3146926FARMVIL
Solar/Wind Harmer
0.141
3138133OCRAN
Solar/Wind Harmer
0.139
316003AC1-222 GEN
Solar/Wind Harmer
0.006
970937AG2-583 GEN
Solar/Wind Harmer
13.92
316322AB2-045
Solar/Wind Harmer
0.002
3146776BUCKING
Solar/Wind Harmer
0.085
962861AG1-135 GEN
Solar/Wind Harmer
6.647
3141726DUNNSVL
Solar/Wind Harmer
0.786
3150351NORNECKC2
Adder
1.901
972003AH1-546 GEN
Solar/Wind Harmer
8.083
971377AH1-170 GEN
Solar/Wind Harmer
1.823
3147623JAMES R
Solar/Wind Harmer
0.396
316337AD2-073 GEN
Solar/Wind Harmer
0.146
970223AG2-152 GEN
Solar/Wind Harmer
10.672
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.084
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.104
3146802CHATHAM
Solar/Wind Harmer
0.098
941801AE2-185 GEN
Solar/Wind Harmer
4.176
972277AH1-723 GEN
Adder
76.921
270030AE2-140 GEN
Solar/Wind Harmer
12.711
316045AC1-158 PL2
Solar/Wind Helper
7.036
3147666LOUISA
Solar/Wind Helper
1.244
316192AB2-158 GEN
Solar/Wind Helper
2.045
316254AC1-120 GEN1
Solar/Wind Helper
1.287
316006AB2-029 C
Solar/Wind Helper
0.13
3151031BRUNSWICKG2
50/50
4.373
3151101ELIZAR3
50/50
30.305
3150861SPRUNCD
50/50
1.461
3151161SURRY 1
50/50
11.304
970917AG2-570 GEN
Solar/Wind Harmer
28.408
315773AC2-141 GEN
Solar/Wind Harmer
11.382
944581AF1-123 GEN
Solar/Wind Harmer
69.733
944601AF1-125 GEN
Solar/Wind Harmer
68.658
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.306
971153AH1-033 GEN
Solar/Wind Harmer
3.534
3144536CHRHLND
Solar/Wind Harmer
0.046
316320Y1-086
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
6.41
316083AB2-161 GEN
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
3.204
315813AE1-149 C
Solar/Wind Harmer
16.153
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3145336SMITFLD
Solar/Wind Harmer
0.12
3146626S HERTFORD
Solar/Wind Harmer
0.299
315839AE2-212 C
Solar/Wind Harmer
0.002
3145273HOLLAND
Solar/Wind Harmer
0.223
316313AB2-026
Solar/Wind Harmer
0.186
316258AE1-075 C
Solar/Wind Harmer
0.223
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
4.463
965281AG1-393 GEN
Solar/Wind Harmer
3.139
3151221GRAVEL6
Adder
21.396
3151171GRAVELC
Adder
4.116
3146376EDENTON
Solar/Wind Harmer
0.294
961611AG1-000B GEN
Solar/Wind Harmer
7.797
316365GEN2_N
Solar/Wind Harmer
0.655
315614AA2-178 GEN
Solar/Wind Harmer
1.657
315778AD1-151 GEN
Solar/Wind Harmer
23.065
3156081AA2-088 GEN
Solar/Wind Harmer
0.007
970129AG2-093 GEN
Solar/Wind Harmer
17.309
316478AD1-087 GEN
Solar/Wind Harmer
0.999
316486AD2-202 GEN
Solar/Wind Harmer
0.293
971157AH1-035 GEN
Solar/Wind Harmer
3.43
315737AD1-076 GEN
Solar/Wind Harmer
3.669
3144216WINCHST
Adder
1.072
970133AG2-095 GEN
Solar/Wind Harmer
2.723
3145893MURPHYS
Solar/Wind Harmer
0.474
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
957521AF2-046 GEN
Solar/Wind Harmer
21.052
961681AG1-008 GEN
Solar/Wind Harmer
21.052
3150921YORKTN3
Adder
7.103
3146173TUNIS
Solar/Wind Harmer
0.281
313506AB2-031 GEN
Solar/Wind Harmer
0.867
3156021HOLLOMANSOL
Solar/Wind Harmer
1.274
316463AE2-346 GEN
Solar/Wind Harmer
0.241
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
2.99
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3146263WOODLND
Solar/Wind Harmer
0.278
3147043LAWRENC
Solar/Wind Harmer
0.166
316317KELFORD C
Solar/Wind Harmer
0.027
3145823KELFORD
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
1.1
3145796HORNRTN
Solar/Wind Harmer
0.275
3145963POPLR C
Solar/Wind Harmer
0.274
3143096IRON208
Adder
1.147
3143096IRON208
Adder
1.124
316382AG1-145 C
Solar/Wind Harmer
0.002
316210AC1-098 GEN
Solar/Wind Harmer
2.485
3145933PARMELE
Solar/Wind Harmer
0.265
966801AG1-551 GEN
Solar/Wind Harmer
3.091
3142946ENON
Solar/Wind Harmer
0.089
315724AD1-057 GEN
Solar/Wind Harmer
0.985
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
316327AA2-057 GEN
Solar/Wind Harmer
0.393
970909AG2-566 GEN
Solar/Wind Harmer
2.748
316131AB2-060 GEN
Solar/Wind Harmer
0.81
3146233WITAKRS
Solar/Wind Harmer
1.286
3146233WITAKRS
Solar/Wind Harmer
0.174
3138543CONSLDL
Solar/Wind Harmer
0.169
964241AG1-285 GEN
Solar/Wind Harmer
17.051
3146073TAR RVR
Solar/Wind Harmer
0.255
3146083TARBORO
Solar/Wind Harmer
0.255
970293AG2-193 GEN
Solar/Wind Harmer
2.717
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
315785AD2-033 C
Solar/Wind Harmer
2.056
961601AG1-000A GEN
Solar/Wind Harmer
17.946
3145543BTLEBRO
Solar/Wind Harmer
0.252
3145543BTLEBRO
Solar/Wind Harmer
0.252
971623AH1-311 GEN
Solar/Wind Harmer
0.505
970257AG2-171 GEN
Solar/Wind Harmer
8.061
959311AF2-222 GEN
Solar/Wind Harmer
22.323
963181AG1-167 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3147133PAMPLIN
Solar/Wind Harmer
0.769
971193AH1-056 GEN
Solar/Wind Harmer
14.916
3141843SHACKLE
Adder
1.244
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
3.224
316156AD2-030 GEN
Solar/Wind Harmer
0.179
3141873WAN 176
Solar/Wind Harmer
4.293
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
10.242
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.323
3146926FARMVIL
Solar/Wind Harmer
0.141
971683AH1-343 GEN
Solar/Wind Harmer
8.112
962971AG1-146 GEN
Solar/Wind Harmer
3.502
316283AC2-100 C
Solar/Wind Harmer
0.428
316473AC1-191 GEN
Solar/Wind Harmer
0.734
970009AG2-005 GEN
Solar/Wind Harmer
1.596
3146776BUCKING
Solar/Wind Harmer
0.076
316404AE1-155 C
Solar/Wind Harmer
0.046
3150351NORNECKC2
Adder
1.933
970221AG2-151 GEN
Solar/Wind Harmer
9.113
971781AH1-399 GEN
Solar/Wind Harmer
0.197
3141906WESTMOR
Solar/Wind Harmer
0.057
270197AD1-017 GEN1
Solar/Wind Harmer
0.888
270018AE2-047 C O1
Solar/Wind Harmer
0.003
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.176
972255AH1-712 GEN
Adder
66.009
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
970737AG2-469 GEN
Solar/Wind Harmer
5.167
958131AF2-107 GEN
Solar/Wind Harmer
3.333
316044AC1-158 PL1
Solar/Wind Helper
2.198
316450AC1-158 RIC
Solar/Wind Helper
0.586
3147666LOUISA
Solar/Wind Helper
0.715
316170AC1-121 GEN2
Solar/Wind Helper
0.429
3141196NOKESVL
Solar/Wind Helper
1.038
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
970533AG2-339 GEN
50/50
30.786
970531AG2-338 GEN
50/50
12.314
315242AE2-183_GT2
50/50
5.558
315241AE2-183_GT1
50/50
5.524
972185AH1-677 GEN
50/50
20.036
3151041BRUNSWICKG3
50/50
4.373
972187AH1-678 GEN
50/50
10.036
3150991CHESPKB
50/50
3.415
3150991CHESPKB
50/50
3.333
971223AH1-071 GEN
Solar/Wind Harmer
3.931
3143526WINTERP
Solar/Wind Harmer
1.742
970933AG2-581 GEN
Solar/Wind Harmer
25.944
3144356SAPONY
Solar/Wind Harmer
2.645
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.295
3145506HICKORY
Solar/Wind Harmer
1.229
3145506HICKORY
Solar/Wind Harmer
0.737
3145506HICKORY
Solar/Wind Harmer
0.184
316036AC1-147 C
Solar/Wind Harmer
0.057
316339AD2-160 GEN
Solar/Wind Harmer
0.497
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.171
3137176SLIGO L2192
Solar/Wind Harmer
1.217
3146456SLIGO L269
Solar/Wind Harmer
5.409
3130086AYDLETT
Solar/Wind Harmer
1.221
3146386ELIZ CT
Solar/Wind Harmer
0.303
970657AG2-426 GEN
Solar/Wind Harmer
10.611
970657AG2-426 GEN
Solar/Wind Harmer
2.224
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
3146516WINFALL
Solar/Wind Harmer
0.3
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.299
3146626S HERTFORD
Solar/Wind Harmer
0.299
970099AG2-077 GEN
Solar/Wind Harmer
31.878
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.308
3146376EDENTON
Solar/Wind Harmer
1.308
316240AF1-291 C
Solar/Wind Harmer
0.002
316033AB2-134 GEN
Solar/Wind Harmer
0.017
315697AD1-025 GEN
Solar/Wind Harmer
0.325
944641AF1-129 GEN
Adder
137.21
316065AD1-022 GEN
Solar/Wind Harmer
13.074
3145893MURPHYS
Solar/Wind Harmer
1.897
3145893MURPHYS
Solar/Wind Harmer
0.51
3146173TUNIS
Solar/Wind Harmer
0.281
3146173TUNIS
Solar/Wind Harmer
0.281
316181AB2-040 GEN
Solar/Wind Harmer
0.407
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.279
3142666NORTHAMPTON
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
0.935
3145593CAROLNA
Solar/Wind Harmer
0.276
3145593CAROLNA
Solar/Wind Harmer
0.276
966811AG1-552 GEN
Solar/Wind Harmer
2.997
3145593CAROLNA
Solar/Wind Harmer
0.344
3145796HORNRTN
Solar/Wind Harmer
0.825
3145783HORNRTN
Solar/Wind Harmer
4.886
3145783HORNRTN
Solar/Wind Harmer
3.909
3145783HORNRTN
Solar/Wind Harmer
1.222
3145783HORNRTN
Solar/Wind Harmer
0.489
316274AC1-208 GEN
Solar/Wind Harmer
1.384
3145933PARMELE
Solar/Wind Harmer
0.531
3145933PARMELE
Solar/Wind Harmer
0.265
3142946ENON
Solar/Wind Harmer
0.026
971741AH1-377 GEN
Solar/Wind Harmer
26.27
939181AE1-148 GEN
Solar/Wind Harmer
12.567
3142366NRTHEST
Adder
0.844
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970301AG2-198 GEN
Solar/Wind Harmer
10.992
3150691DARBY 3
Adder
18.496
3150701DARBY 4
Adder
18.453
3150681DARBY 2
Adder
18.432
3150671DARBY 1
Adder
18.41
3145493TOT1
Solar/Wind Harmer
0.592
3145453TOT5
Solar/Wind Harmer
0.355
3145603CNETO
Solar/Wind Harmer
0.237
961601AG1-000A GEN
Solar/Wind Harmer
4.486
316263AC1-034 GEN
Solar/Wind Harmer
9.586
316075AC2-137 C
Solar/Wind Harmer
0.069
970323AG2-213 GEN
Solar/Wind Harmer
10.747
971775AH1-396 GEN
Solar/Wind Harmer
0.403
316034AC1-036 C
Solar/Wind Harmer
0.018
962561AG1-105 GEN
Solar/Wind Harmer
11.957
964791AG1-342 GEN
Solar/Wind Harmer
4.752
3146843MT LREL
Solar/Wind Harmer
0.247
3146843MT LREL
Solar/Wind Harmer
0.247
958211AF2-115 GEN
Solar/Wind Harmer
2.961
963191AG1-168 GEN
Solar/Wind Harmer
0.987
3144293JTRSVLE
Adder
0.785
3144293JTRSVLE
Adder
0.661
3147133PAMPLIN
Solar/Wind Harmer
0.245
3147133PAMPLIN
Solar/Wind Harmer
0.196
3142296MT RD221
Adder
0.748
316222AC1-221 GEN
Solar/Wind Harmer
0.912
966871AG1-558 GEN
Solar/Wind Harmer
0.251
3146776BUCKING
Solar/Wind Harmer
0.848
3146776BUCKING
Solar/Wind Harmer
0.069
958261AF2-120 GEN
Solar/Wind Harmer
6.796
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.997
3150341NORNECKC1
Adder
1.981
942751AE2-291 GEN
Solar/Wind Harmer
9.768
971489AH1-241 GEN
Solar/Wind Harmer
9.113
316468AD1-105 GEN
Solar/Wind Harmer
-0.049
270013AE1-250 PV
Solar/Wind Harmer
0.004
315821AE2-092 GEN
Solar/Wind Harmer
0.008
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.248
316447AC1-158 HLD
Solar/Wind Helper
4.837
315651AD1-115 GEN
Solar/Wind Helper
0.937
226929AD2-058 GEN
Solar/Wind Helper
0.091
316303AF2-085
50/50
6.551
315244AE2-183_ST
50/50
9.609
963041AG1-153 GEN
50/50
8.856
315779AE2-040
50/50
4.414
3151081ELIZAR1
50/50
29.922
3151091ELIZAR2
50/50
29.403
941591AE2-156 GEN
50/50
27.332
3152611GOSPORTB
50/50
4.152
3152621GOSPORTC
50/50
3.523
3152601GOSPORTA
50/50
3.25
971285AH1-108 GEN
50/50
2.391
972263AH1-716 GEN
50/50
170.662
941031AE2-094 GEN
Solar/Wind Harmer
63.788
944011AF1-069 GEN
Solar/Wind Harmer
20.842
970673AG2-436 GEN
Solar/Wind Harmer
72.487
970673AG2-436 GEN
Solar/Wind Harmer
48.325
316233AE1-074 FULL
Solar/Wind Harmer
0.268
971281AH1-106 GEN
Solar/Wind Harmer
4.649
971283AH1-107 GEN
Solar/Wind Harmer
4.649
971967AH1-528 GEN
Solar/Wind Harmer
53.477
970085AG2-068 GEN
Solar/Wind Harmer
16.971
970581AG2-369 GEN
Solar/Wind Harmer
14.595
316315AB2-025 C
Solar/Wind Harmer
0.256
315814AE2-033 C
Solar/Wind Harmer
24.917
3143316POE
Solar/Wind Harmer
1.232
957871AF2-081 GEN
Solar/Wind Harmer
15.244
319010AE1-072 C
Solar/Wind Harmer
1.539
3146406KITTY HAWK
Solar/Wind Harmer
0.038
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.164
315835AF2-110_GEN
Solar/Wind Harmer
2.081
315833AF1-017_GEN
Solar/Wind Harmer
0.002
316349AD2-085 GEN
Solar/Wind Harmer
0.208
316311AC2-079 GEN
Solar/Wind Harmer
8.702
3146486SUNBURY
Solar/Wind Harmer
0.302
3146486SUNBURY
Solar/Wind Harmer
0.302
316321Z2-027
Solar/Wind Harmer
0.056
3146396TANGLEW
Solar/Wind Harmer
0.833
3145176PASQUOTANK
Solar/Wind Harmer
0.187
971445AH1-216 GEN
Solar/Wind Harmer
21.042
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.294
3130156CHOWAN
Solar/Wind Harmer
0.294
972265AH1-717 GEN
Adder
22.85
3151201GRAVEL4
Adder
21.42
3151191GRAVEL3
Adder
21.149
3151211GRAVEL5
Adder
21.149
316369SG1_INVT
Solar/Wind Harmer
0.011
315816AE2-034 GEN
Solar/Wind Harmer
1.242
316132AB2-190 GEN1
Solar/Wind Harmer
1.538
3130546PLYMOUTH
Solar/Wind Harmer
0.286
965291AG1-394 GEN
Solar/Wind Harmer
1.269
315732AD1-074 GEN1
Solar/Wind Harmer
1.639
315733AD1-074 GEN2
Solar/Wind Harmer
1.639
315735AD1-075 GEN1
Solar/Wind Harmer
0.82
3145893MURPHYS
Solar/Wind Harmer
0.765
3145893MURPHYS
Solar/Wind Harmer
0.283
3146206CASHIE
Solar/Wind Harmer
0.283
970601AG2-382 GEN
Solar/Wind Harmer
10.575
316087AB2-174 GEN
Solar/Wind Harmer
0.008
3146043SEABORD
Solar/Wind Harmer
0.28
3145513AHOSKIE
Solar/Wind Harmer
0.586
3145513AHOSKIE
Solar/Wind Harmer
0.28
315607AA1-063A GEN
Solar/Wind Harmer
0.572
3145683EARLEYS
Solar/Wind Harmer
0.558
3145683EARLEYS
Solar/Wind Harmer
0.279
3145683EARLEYS
Solar/Wind Harmer
0.279
315652AC1-086 GEN
Solar/Wind Harmer
30.678
3137643SOCKMAN
Solar/Wind Harmer
1.111
3145796HORNRTN
Solar/Wind Harmer
0.88
3145796HORNRTN
Solar/Wind Harmer
0.11
3146033SCOT NK
Solar/Wind Harmer
1.084
970831AG2-522 GEN
Solar/Wind Harmer
11.448
3138283WHITEMARSH
Solar/Wind Harmer
0.061
316005AA1-067
Solar/Wind Harmer
0.28
3145746EVERETS
Solar/Wind Harmer
1.039
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
3145746EVERETS
Solar/Wind Harmer
0.261
970181AG2-120 GEN
Solar/Wind Harmer
3.25
957861AF2-080 GEN
Solar/Wind Harmer
11.129
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.255
3145573BETHELC
Solar/Wind Harmer
0.255
971167AH1-042 GEN
Solar/Wind Harmer
22.645
315976AC1-164 GENA
Solar/Wind Harmer
26.291
316169AC1-164_GENC
Solar/Wind Harmer
22.713
315975AC1-164 GENB
Solar/Wind Harmer
0.778
3142433PROV 92
Adder
0.492
3142433PROV 92
Adder
0.492
971443AH1-215 GEN
Solar/Wind Harmer
4.236
3144303KENBRDG
Solar/Wind Harmer
0.201
970683AG2-441 GEN
Solar/Wind Harmer
16.616
970681AG2-440 GEN
Solar/Wind Harmer
13.292
946301AF1-294 GEN
Solar/Wind Harmer
4.868
961791AG1-021 GEN
Solar/Wind Harmer
2.368
3143873LANEXA
Solar/Wind Harmer
0.148
315657AE1-056 GEN
Solar/Wind Harmer
8.449
316118AC1-105 GEN
Solar/Wind Harmer
0.629
970189AG2-124 GEN
Solar/Wind Harmer
7.213
315662AE1-191 GEN
Solar/Wind Harmer
0.008
315666AE1-190 GEN
Solar/Wind Harmer
0.002
316314AB2-024 C
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.002
3141873WAN 176
Solar/Wind Harmer
0.048
3147173SINAI
Solar/Wind Harmer
0.24
3147243WELCO
Solar/Wind Harmer
0.15
316312AB1-027
Solar/Wind Harmer
0.429
3141913WHIT STONE
Solar/Wind Harmer
0.234
3138133OCRAN
Solar/Wind Harmer
0.069
3141783LANCAST
Solar/Wind Harmer
0.137
3141783LANCAST
Solar/Wind Harmer
0.091
962981AG1-147 GEN
Solar/Wind Harmer
8.172
970285AG2-188 GEN
Solar/Wind Harmer
17.223
971845AH1-439 GEN
Solar/Wind Harmer
9.707
970327AG2-215 GEN
Solar/Wind Harmer
7.016
970865AG2-541 GEN
Solar/Wind Harmer
7.314
316123AC1-075 GEN
Solar/Wind Harmer
0.262
970165AG2-112 GEN
Solar/Wind Harmer
1.554
970163AG2-111 GEN
Solar/Wind Harmer
1.483
3141813NORNECK
Solar/Wind Harmer
0.191
972205AH1-687 GEN
Adder
7.916
971447AH1-217 GEN
Solar/Wind Harmer
4.969
270494AE1-108_GEN
Solar/Wind Harmer
1.845
972189AH1-679 GEN
Adder
2.488
316223AC1-118
Solar/Wind Harmer
0.103
972193AH1-681 GEN
Adder
2.949
316164AC1-076 GEN
Solar/Wind Helper
1.496
316411AF1-147_GEN1
Solar/Wind Helper
0.807
316415AF1-147_GEN2
Solar/Wind Helper
0.807
3138216PACIFIC
Solar/Wind Helper
0.039
NYPJM->LTFIMP_NY
CLTF
3.567
LAGNLTFEXP_LAGN->PJM
CLTF
12.487
LGEELTFEXP_LGEE->PJM
CLTF
2.341
WECLTFEXP_WEC->PJM
CLTF
1.189
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.918
TVALTFEXP_TVA->PJM
CLTF
6.285
CPLELTFEXP_CPLE->PJM
CLTF
16.793
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.855
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.654
MECLTFEXP_MEC->PJM
CLTF
6.28
SIGELTFEXP_SIGE->PJM
CLTF
0.191

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H2T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H2T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.63 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6092.43
MW Contribution:19.36
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.405
3151101ELIZAR3
50/50
30.659
3150861SPRUNCD
50/50
1.485
3151161SURRY 1
50/50
11.463
970917AG2-570 GEN
Solar/Wind Harmer
90.418
315773AC2-141 GEN
Solar/Wind Harmer
14.817
944581AF1-123 GEN
Solar/Wind Harmer
160.093
944601AF1-125 GEN
Solar/Wind Harmer
157.595
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.035
971153AH1-033 GEN
Solar/Wind Harmer
4.235
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.552
970659AG2-427 GEN
Solar/Wind Harmer
3.246
316083AB2-161 GEN
Solar/Wind Harmer
5.596
970661AG2-428 GEN
Solar/Wind Harmer
6.491
316320Y1-086
Solar/Wind Harmer
2.02
316435W1029_GEN3
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.013
315839AE2-212 C
Solar/Wind Harmer
1.026
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3145273HOLLAND
Solar/Wind Harmer
-0.025
965281AG1-393 GEN
Solar/Wind Harmer
4.197
3151221GRAVEL6
Adder
21.696
3151171GRAVELC
Adder
4.174
316313AB2-026
Solar/Wind Harmer
0.903
316258AE1-075 C
Solar/Wind Harmer
0.813
316405AF2-144 C
Solar/Wind Harmer
0.857
3143336POWHATN
Solar/Wind Harmer
3.376
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
7.019
316365GEN2_N
Solar/Wind Harmer
2.232
315778AD1-151 GEN
Solar/Wind Harmer
28.5
315614AA2-178 GEN
Solar/Wind Harmer
3.547
970129AG2-093 GEN
Solar/Wind Harmer
18.408
3156081AA2-088 GEN
Solar/Wind Harmer
10.555
971157AH1-035 GEN
Solar/Wind Harmer
4.057
3144216WINCHST
Adder
1.088
970133AG2-095 GEN
Solar/Wind Harmer
3.645
316478AD1-087 GEN
Solar/Wind Harmer
2.805
316486AD2-202 GEN
Solar/Wind Harmer
0.821
315737AD1-076 GEN
Solar/Wind Harmer
6.155
966621AG1-532 GEN
Solar/Wind Harmer
0.655
3150921YORKTN3
Adder
7.214
3145893MURPHYS
Solar/Wind Harmer
0.225
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.297
961681AG1-008 GEN
Solar/Wind Harmer
25.297
3146173TUNIS
Solar/Wind Harmer
-0.032
3156021HOLLOMANSOL
Solar/Wind Harmer
4.291
313506AB2-031 GEN
Solar/Wind Harmer
2.559
316463AE2-346 GEN
Solar/Wind Harmer
0.515
316140AB2-099
Solar/Wind Harmer
0.215
962331AG1-082 GEN
Solar/Wind Harmer
3.978
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.032
3143096IRON208
Adder
1.169
3143096IRON208
Adder
1.146
3147043LAWRENC
Solar/Wind Harmer
-0.019
316317KELFORD C
Solar/Wind Harmer
1.473
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.939
3142946ENON
Solar/Wind Harmer
-0.01
316210AC1-098 GEN
Solar/Wind Harmer
4.769
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.764
315724AD1-057 GEN
Solar/Wind Harmer
1.713
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316327AA2-057 GEN
Solar/Wind Harmer
2.98
970293AG2-193 GEN
Solar/Wind Harmer
3.658
970909AG2-566 GEN
Solar/Wind Harmer
2.77
316131AB2-060 GEN
Solar/Wind Harmer
3.147
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
0.608
3146233WITAKRS
Solar/Wind Harmer
-0.02
3138543CONSLDL
Solar/Wind Harmer
-0.019
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
964241AG1-285 GEN
Solar/Wind Harmer
22.639
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
2.004
972255AH1-712 GEN
Adder
67.55
316044AC1-158 PL1
Solar/Wind Helper
2.235
316450AC1-158 RIC
Solar/Wind Helper
0.596
3147666LOUISA
Solar/Wind Helper
0.727
316170AC1-121 GEN2
Solar/Wind Helper
0.437
3141196NOKESVL
Solar/Wind Helper
1.052
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.315
226910AB2-157 C
Solar/Wind Helper
0.013
970119AG2-088 GEN
50/50
49.56
315243AE2-183_GT3
50/50
5.597
3151051BRUNSWICKS1
50/50
9.142
3151021BRUNSWICKG1
50/50
4.405
971451AH1-221 GEN
50/50
13.378
3150981CHESPKA
50/50
4.118
3150851SPRUNCC
50/50
1.485
3152331SURRY 2
50/50
12.49
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
37.221
939411AE1-173 GEN
Solar/Wind Harmer
192.62
3143526WINTERP
Solar/Wind Harmer
-0.197
970919AG2-571 GEN
Solar/Wind Harmer
11.445
970087AG2-069 GEN
Solar/Wind Harmer
33.76
316294AC1-161 GEN
Solar/Wind Harmer
11.456
944591AF1-124 GEN
Solar/Wind Harmer
160.67
316375AC2-012 GEN
Solar/Wind Harmer
12.086
316388AE2-253 GEN
Solar/Wind Harmer
2.349
3146456SLIGO L269
Solar/Wind Harmer
-0.035
316246AF1-032 C
Solar/Wind Harmer
0.701
970659AG2-427 GEN
Solar/Wind Harmer
18.316
316381AD1-082 GEN
Solar/Wind Harmer
3.162
970661AG2-428 GEN
Solar/Wind Harmer
36.628
316093AE2-104_GEN
Solar/Wind Harmer
10.019
316072AD1-144
Solar/Wind Harmer
0.693
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.136
957481AF2-042 GEN
Solar/Wind Harmer
105.713
315800Z1-036_GEN1
Solar/Wind Harmer
8.332
3151171GRAVELC
Adder
3.174
3143336POWHATN
Solar/Wind Harmer
3.972
3130156CHOWAN
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
16.45
315671AE2-027_GEN
Solar/Wind Harmer
24.982
971647AH1-324 GEN
Solar/Wind Harmer
16.587
316023GEN1_S
Solar/Wind Harmer
2.232
971069AG2-661 GEN
Solar/Wind Harmer
5.205
3145663CRESWEL
Solar/Wind Harmer
-0.092
971163AH1-040 GEN
Solar/Wind Harmer
30.822
316458AB2-190 GEN2
Solar/Wind Harmer
3.31
315693AD1-088 GEN
Solar/Wind Harmer
16.359
970129AG2-093 GEN
Solar/Wind Harmer
7.456
962491AG1-098 GEN
Solar/Wind Harmer
21.758
3138126ROCKLANDING
Solar/Wind Harmer
0.099
960081AF2-299 GEN
Solar/Wind Harmer
3.629
3145893MURPHYS
Solar/Wind Harmer
-0.128
3145893MURPHYS
Solar/Wind Harmer
0.955
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
8.041
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.623
962571AG1-106 GEN
Solar/Wind Harmer
4.551
971795AH1-408 GEN
Solar/Wind Harmer
23.72
3146263WOODLND
Solar/Wind Harmer
-0.032
971317AH1-138 GEN
Solar/Wind Harmer
3.934
316190AA2-174 GEN
Solar/Wind Harmer
0.386
3143096IRON208
Adder
1.169
3147043LAWRENC
Adder
2.523
316336AC2-165 C
Solar/Wind Harmer
5.44
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.836
944631AF1-128 GEN
Adder
131.354
316174AB2-169 GEN
Solar/Wind Harmer
4.773
315687AD1-152 GEN
Solar/Wind Harmer
3.672
316212AC1-099_GEN
Solar/Wind Harmer
2.649
316129AC1-054 GEN
Solar/Wind Harmer
2.658
971065AG2-659 GEN
Solar/Wind Harmer
15.113
3146293MARTNCO
Solar/Wind Harmer
0.186
315722AD1-056 GEN
Solar/Wind Harmer
3.115
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
316494AC1-189 GEN
Solar/Wind Harmer
3.151
316237AB2-079_GEN
Solar/Wind Harmer
0.879
3142433PROV 92
Solar/Wind Harmer
-0.116
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
3146233WITAKRS
Solar/Wind Harmer
-0.115
961671AG1-007 GEN
Solar/Wind Harmer
0.366
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.86
3141843SHACKLE
Adder
1.273
3144293JTRSVLE
Adder
0.792
3150351NORNECKC2
Adder
1.971
972277AH1-723 GEN
Adder
78.716
316045AC1-158 PL2
Solar/Wind Helper
7.153
3147666LOUISA
Solar/Wind Helper
1.265
316192AB2-158 GEN
Solar/Wind Helper
2.08
316254AC1-120 GEN1
Solar/Wind Helper
1.311
316006AB2-029 C
Solar/Wind Helper
0.132
316303AF2-085
50/50
6.608
315244AE2-183_ST
50/50
9.677
963041AG1-153 GEN
50/50
8.919
315779AE2-040
50/50
4.458
3151081ELIZAR1
50/50
30.271
3151091ELIZAR2
50/50
29.745
941591AE2-156 GEN
50/50
27.651
3152611GOSPORTB
50/50
4.2
3152621GOSPORTC
50/50
3.565
3152601GOSPORTA
50/50
3.288
971285AH1-108 GEN
50/50
2.43
972263AH1-716 GEN
50/50
172.931
941031AE2-094 GEN
Solar/Wind Harmer
73.475
944011AF1-069 GEN
Solar/Wind Harmer
23.022
970673AG2-436 GEN
Solar/Wind Harmer
80.77
970673AG2-436 GEN
Solar/Wind Harmer
40.896
316233AE1-074 FULL
Solar/Wind Harmer
1.026
971281AH1-106 GEN
Solar/Wind Harmer
6.195
971283AH1-107 GEN
Solar/Wind Harmer
6.195
971967AH1-528 GEN
Solar/Wind Harmer
71.103
970085AG2-068 GEN
Solar/Wind Harmer
22.506
970581AG2-369 GEN
Solar/Wind Harmer
19.356
316315AB2-025 C
Solar/Wind Harmer
0.968
315814AE2-033 C
Solar/Wind Harmer
33.285
3143316POE
Solar/Wind Harmer
-0.139
957871AF2-081 GEN
Solar/Wind Harmer
17.401
319010AE1-072 C
Solar/Wind Harmer
7.024
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.044
313526AB2-022
Solar/Wind Harmer
0.93
315833AF1-017_GEN
Solar/Wind Harmer
6.546
316349AD2-085 GEN
Solar/Wind Harmer
3.065
316311AC2-079 GEN
Solar/Wind Harmer
17.383
315835AF2-110_GEN
Solar/Wind Harmer
4.308
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.926
3146396TANGLEW
Solar/Wind Harmer
0.632
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
21.053
315611Z1-036_GEN2
Solar/Wind Harmer
8.332
972265AH1-717 GEN
Adder
23.171
3151201GRAVEL4
Adder
21.721
3151191GRAVEL3
Adder
21.446
3151211GRAVEL5
Adder
21.446
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.9
315816AE2-034 GEN
Solar/Wind Harmer
2.66
316132AB2-190 GEN1
Solar/Wind Harmer
3.31
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.878
315732AD1-074 GEN1
Solar/Wind Harmer
6.549
315733AD1-074 GEN2
Solar/Wind Harmer
6.549
315735AD1-075 GEN1
Solar/Wind Harmer
3.275
946281AF1-292 GEN
Solar/Wind Harmer
0.723
316318V4-068
Solar/Wind Harmer
0.802
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
14.071
316087AB2-174 GEN
Solar/Wind Harmer
4.56
3146043SEABORD
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.277
961941AG1-037 GEN
Solar/Wind Harmer
0.239
3145513AHOSKIE
Solar/Wind Harmer
-0.032
315607AA1-063A GEN
Solar/Wind Harmer
3.21
3145683EARLEYS
Solar/Wind Harmer
-0.063
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
315652AC1-086 GEN
Solar/Wind Harmer
35.613
3137643SOCKMAN
Solar/Wind Harmer
-0.126
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.122
970831AG2-522 GEN
Solar/Wind Harmer
15.209
957831AF2-077 GEN
Solar/Wind Harmer
0.905
3138283WHITEMARSH
Solar/Wind Harmer
0.047
316005AA1-067
Solar/Wind Harmer
0.599
3145746EVERETS
Solar/Wind Harmer
-0.117
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
3145746EVERETS
Solar/Wind Harmer
-0.03
970181AG2-120 GEN
Solar/Wind Harmer
3.889
957861AF2-080 GEN
Solar/Wind Harmer
12.812
971167AH1-042 GEN
Solar/Wind Harmer
28.174
316239AB2-077_GEN
Solar/Wind Harmer
0.879
316238AB2-078_GEN
Solar/Wind Harmer
0.879
316420AA1-050 GEN
Solar/Wind Harmer
3.326
315976AC1-164 GENA
Solar/Wind Harmer
30.748
316169AC1-164_GENC
Solar/Wind Harmer
26.564
315975AC1-164 GENB
Solar/Wind Harmer
0.91
3142433PROV 92
Adder
0.503
3142433PROV 92
Adder
0.503
316319Z2-044 C
Solar/Wind Harmer
1.605
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
972205AH1-687 GEN
Adder
7.988
972189AH1-679 GEN
Adder
2.712
972193AH1-681 GEN
Adder
3.018
316164AC1-076 GEN
Solar/Wind Helper
1.525
316411AF1-147_GEN1
Solar/Wind Helper
0.816
316415AF1-147_GEN2
Solar/Wind Helper
0.816
3138216PACIFIC
Solar/Wind Helper
0.04
970533AG2-339 GEN
50/50
31.002
970531AG2-338 GEN
50/50
12.401
315242AE2-183_GT2
50/50
5.597
315241AE2-183_GT1
50/50
5.563
972185AH1-677 GEN
50/50
20.179
3151041BRUNSWICKG3
50/50
4.405
972187AH1-678 GEN
50/50
10.108
3150991CHESPKB
50/50
3.455
3150991CHESPKB
50/50
3.372
971223AH1-071 GEN
Solar/Wind Harmer
5.22
3143526WINTERP
Solar/Wind Harmer
-0.197
970933AG2-581 GEN
Solar/Wind Harmer
34.405
3144356SAPONY
Solar/Wind Harmer
1.252
316185AD1-033 GEN
Solar/Wind Harmer
3.69
3142956BIRDNECK
Solar/Wind Harmer
1.875
316316AC1-027 C
Solar/Wind Harmer
1.073
316036AC1-147 C
Solar/Wind Harmer
0.942
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.021
316339AD2-160 GEN
Solar/Wind Harmer
2.349
316018AA1-139 ULT2
Solar/Wind Harmer
2.981
316017AA1-139 ULT1
Solar/Wind Harmer
2.816
3137176SLIGO L2192
Solar/Wind Harmer
-0.137
3146456SLIGO L269
Solar/Wind Harmer
4.103
3130086AYDLETT
Solar/Wind Harmer
-0.138
970657AG2-426 GEN
Solar/Wind Harmer
10.774
970657AG2-426 GEN
Solar/Wind Harmer
2.253
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.192
316433W1029_GEN2
Solar/Wind Harmer
6.192
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.027
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
970099AG2-077 GEN
Solar/Wind Harmer
42.285
315742AE1-103 GEN
Solar/Wind Harmer
3.51
3146376EDENTON
Solar/Wind Harmer
0.992
3146376EDENTON
Solar/Wind Harmer
0.992
316240AF1-291 C
Solar/Wind Harmer
1
316033AB2-134 GEN
Solar/Wind Harmer
10.649
315697AD1-025 GEN
Solar/Wind Harmer
6.679
944641AF1-129 GEN
Adder
139.506
316065AD1-022 GEN
Solar/Wind Harmer
16.121
3145893MURPHYS
Solar/Wind Harmer
0.898
3145893MURPHYS
Solar/Wind Harmer
-0.058
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.441
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.032
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.174
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.528
3145593CAROLNA
Solar/Wind Harmer
0.26
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
3.7
3145783HORNRTN
Solar/Wind Harmer
2.96
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.37
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
3.264
3145933PARMELE
Solar/Wind Harmer
-0.06
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.86
3142366NRTHEST
Adder
0.864
939181AE1-148 GEN
Solar/Wind Harmer
16.686
3150691DARBY 3
Adder
18.921
3150701DARBY 4
Adder
18.877
3150681DARBY 2
Adder
18.855
3150671DARBY 1
Adder
18.833
313527AB2-043 GEN
Solar/Wind Harmer
4.747
970301AG2-198 GEN
Solar/Wind Harmer
14.587
3145493TOT1
Solar/Wind Harmer
0.448
3145453TOT5
Solar/Wind Harmer
0.269
3145603CNETO
Solar/Wind Harmer
0.179
3144293JTRSVLE
Adder
0.792
3144293JTRSVLE
Adder
0.667
3142296MT RD221
Adder
0.77
3150341NORNECKC1
Adder
2.071
3150341NORNECKC1
Adder
2.054
316447AC1-158 HLD
Solar/Wind Helper
4.918
315651AD1-115 GEN
Solar/Wind Helper
0.954
226929AD2-058 GEN
Solar/Wind Helper
0.092
316075AC2-137 C
Solar/Wind Harmer
0.319
NYPJM->LTFIMP_NY
CLTF
3.61
LAGNLTFEXP_LAGN->PJM
CLTF
12.593
LGEELTFEXP_LGEE->PJM
CLTF
2.36
WECLTFEXP_WEC->PJM
CLTF
1.198
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.232
TVALTFEXP_TVA->PJM
CLTF
6.338
CPLELTFEXP_CPLE->PJM
CLTF
16.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.417
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.824
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.839
MECLTFEXP_MEC->PJM
CLTF
6.331
SIGELTFEXP_SIGE->PJM
CLTF
0.193

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 557T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 557T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.23 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6076.8
MW Contribution:20.16
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
4.589
3151101ELIZAR3
50/50
32.949
3151161SURRY 1
50/50
12.195
315773AC2-141 GEN
Solar/Wind Harmer
16.075
944581AF1-123 GEN
Solar/Wind Harmer
172.322
944601AF1-125 GEN
Solar/Wind Harmer
169.633
970917AG2-570 GEN
Solar/Wind Harmer
94.165
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.037
971153AH1-033 GEN
Solar/Wind Harmer
4.547
3144536CHRHLND
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
2.165
316435W1029_GEN3
Solar/Wind Harmer
6.628
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.036
970661AG2-428 GEN
Solar/Wind Harmer
6.819
316083AB2-161 GEN
Solar/Wind Harmer
5.857
3145273HOLLAND
Solar/Wind Harmer
-0.027
970659AG2-427 GEN
Solar/Wind Harmer
3.393
315813AE1-149 C
Solar/Wind Harmer
22.383
3151221GRAVEL6
Adder
23.081
3151171GRAVELC
Adder
4.441
3146376EDENTON
Solar/Wind Harmer
-0.036
961611AG1-000B GEN
Solar/Wind Harmer
7.432
3144216WINCHST
Adder
1.179
3150921YORKTN3
Adder
7.837
315614AA2-178 GEN
Solar/Wind Harmer
3.774
315839AE2-212 C
Solar/Wind Harmer
1.048
316365GEN2_N
Solar/Wind Harmer
2.328
315778AD1-151 GEN
Solar/Wind Harmer
29.865
971157AH1-035 GEN
Solar/Wind Harmer
4.308
965281AG1-393 GEN
Solar/Wind Harmer
4.3
315737AD1-076 GEN
Solar/Wind Harmer
6.532
3156081AA2-088 GEN
Solar/Wind Harmer
11.148
3150861SPRUNCD
Adder
1.401
970129AG2-093 GEN
Solar/Wind Harmer
19.191
3146206CASHIE
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.237
3145893MURPHYS
Solar/Wind Harmer
-0.034
957521AF2-046 GEN
Solar/Wind Harmer
26.697
961681AG1-008 GEN
Solar/Wind Harmer
26.697
316382AG1-145 C
Solar/Wind Harmer
1.02
3146173TUNIS
Solar/Wind Harmer
-0.034
3156021HOLLOMANSOL
Solar/Wind Harmer
4.534
966621AG1-532 GEN
Solar/Wind Harmer
0.682
316478AD1-087 GEN
Solar/Wind Harmer
2.909
316486AD2-202 GEN
Solar/Wind Harmer
0.852
316463AE2-346 GEN
Solar/Wind Harmer
0.543
316140AB2-099
Solar/Wind Harmer
0.226
962331AG1-082 GEN
Solar/Wind Harmer
4.197
970133AG2-095 GEN
Solar/Wind Harmer
3.773
316313AB2-026
Solar/Wind Harmer
0.901
316258AE1-075 C
Solar/Wind Harmer
0.811
316405AF2-144 C
Solar/Wind Harmer
0.856
3143336POWHATN
Solar/Wind Harmer
3.371
3146263WOODLND
Solar/Wind Harmer
-0.033
313506AB2-031 GEN
Solar/Wind Harmer
2.672
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3145963POPLR C
Solar/Wind Harmer
-0.033
316317KELFORD C
Solar/Wind Harmer
1.55
3145823KELFORD
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.13
970119AG2-088 GEN
50/50
49.614
315243AE2-183_GT3
50/50
5.833
3151051BRUNSWICKS1
50/50
9.525
3151021BRUNSWICKG1
50/50
4.589
971451AH1-221 GEN
50/50
13.939
3150981CHESPKA
50/50
4.425
3152331SURRY 2
50/50
13.773
3143226MDLTHAN
Solar/Wind Harmer
-0.042
940641AE2-051 GEN
Solar/Wind Harmer
39.09
939411AE1-173 GEN
Solar/Wind Harmer
203.387
316294AC1-161 GEN
Solar/Wind Harmer
12.429
3143526WINTERP
Solar/Wind Harmer
-0.197
944591AF1-124 GEN
Solar/Wind Harmer
172.943
970919AG2-571 GEN
Solar/Wind Harmer
11.92
316375AC2-012 GEN
Solar/Wind Harmer
12.985
970087AG2-069 GEN
Solar/Wind Harmer
35.157
316388AE2-253 GEN
Solar/Wind Harmer
2.523
3146456SLIGO L269
Solar/Wind Harmer
-0.037
316246AF1-032 C
Solar/Wind Harmer
0.751
316093AE2-104_GEN
Solar/Wind Harmer
10.699
316072AD1-144
Solar/Wind Harmer
0.743
3146516WINFALL
Solar/Wind Harmer
-0.118
3146516WINFALL
Solar/Wind Harmer
-0.036
3145336SMITFLD
Solar/Wind Harmer
-0.145
970661AG2-428 GEN
Solar/Wind Harmer
38.478
316381AD1-082 GEN
Solar/Wind Harmer
3.31
970659AG2-427 GEN
Solar/Wind Harmer
19.149
315800Z1-036_GEN1
Solar/Wind Harmer
8.901
3151171GRAVELC
Adder
3.377
3130156CHOWAN
Solar/Wind Harmer
-0.036
961611AG1-000B GEN
Solar/Wind Harmer
17.419
957481AF2-042 GEN
Solar/Wind Harmer
109.742
3138126ROCKLANDING
Solar/Wind Harmer
0.108
971647AH1-324 GEN
Solar/Wind Harmer
17.499
3145663CRESWEL
Solar/Wind Harmer
-0.097
971163AH1-040 GEN
Solar/Wind Harmer
32.791
316023GEN1_S
Solar/Wind Harmer
2.328
971069AG2-661 GEN
Solar/Wind Harmer
5.455
971317AH1-138 GEN
Solar/Wind Harmer
4.281
3150851SPRUNCC
Adder
1.401
316458AB2-190 GEN2
Solar/Wind Harmer
3.453
315671AE2-027_GEN
Solar/Wind Harmer
25.569
970129AG2-093 GEN
Solar/Wind Harmer
7.774
3146206CASHIE
Solar/Wind Harmer
-0.034
971547AH1-271 GEN
Solar/Wind Harmer
8.518
3145893MURPHYS
Solar/Wind Harmer
-0.135
3145893MURPHYS
Solar/Wind Harmer
1.008
315693AD1-088 GEN
Solar/Wind Harmer
16.949
316159AE1-175 C
Solar/Wind Harmer
0.909
3146173TUNIS
Solar/Wind Harmer
-0.034
962491AG1-098 GEN
Solar/Wind Harmer
22.532
960081AF2-299 GEN
Solar/Wind Harmer
3.783
3145683EARLEYS
Solar/Wind Harmer
-0.033
3143336POWHATN
Solar/Wind Harmer
3.966
3146263WOODLND
Solar/Wind Harmer
-0.033
316011AB1-132 GEN
Solar/Wind Harmer
6.928
962571AG1-106 GEN
Solar/Wind Harmer
4.76
3145963POPLR C
Solar/Wind Harmer
-0.033
316190AA2-174 GEN
Solar/Wind Harmer
0.404
971795AH1-408 GEN
Solar/Wind Harmer
24.687
3145823KELFORD
Solar/Wind Harmer
-0.033
316174AB2-169 GEN
Solar/Wind Harmer
5.041
3145796HORNRTN
Solar/Wind Harmer
-0.107
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145783HORNRTN
Solar/Wind Harmer
-0.033
3147043LAWRENC
Adder
2.624
3142543TWELFTH
Solar/Wind Harmer
-0.003
944631AF1-128 GEN
Adder
136.543
3143096IRON208
Adder
1.188
316212AC1-099_GEN
Solar/Wind Harmer
2.778
3146293MARTNCO
Solar/Wind Harmer
0.196
315687AD1-152 GEN
Solar/Wind Harmer
3.804
316303AF2-085
50/50
6.615
315244AE2-183_ST
50/50
10.085
963041AG1-153 GEN
50/50
9.293
3151081ELIZAR1
50/50
32.533
3151091ELIZAR2
50/50
31.968
941591AE2-156 GEN
50/50
29.713
3152611GOSPORTB
50/50
4.513
3152621GOSPORTC
50/50
3.83
3152601GOSPORTA
50/50
3.533
315779AE2-040
50/50
4.628
972263AH1-716 GEN
50/50
190.384
941031AE2-094 GEN
Solar/Wind Harmer
76.612
944011AF1-069 GEN
Solar/Wind Harmer
24.005
970673AG2-436 GEN
Solar/Wind Harmer
84.191
970673AG2-436 GEN
Solar/Wind Harmer
42.628
971967AH1-528 GEN
Solar/Wind Harmer
74.07
316233AE1-074 FULL
Solar/Wind Harmer
1.025
971281AH1-106 GEN
Solar/Wind Harmer
6.19
971283AH1-107 GEN
Solar/Wind Harmer
6.19
970085AG2-068 GEN
Solar/Wind Harmer
23.438
970581AG2-369 GEN
Solar/Wind Harmer
20.157
957871AF2-081 GEN
Solar/Wind Harmer
18.688
319010AE1-072 C
Solar/Wind Harmer
7.541
3146406KITTY HAWK
Solar/Wind Harmer
0.031
316315AB2-025 C
Solar/Wind Harmer
1.005
316305AF2-043 C
Solar/Wind Harmer
1.119
315814AE2-033 C
Solar/Wind Harmer
34.559
313526AB2-022
Solar/Wind Harmer
0.997
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146486SUNBURY
Solar/Wind Harmer
-0.037
316321Z2-027
Solar/Wind Harmer
0.993
3146396TANGLEW
Solar/Wind Harmer
0.677
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
315835AF2-110_GEN
Solar/Wind Harmer
4.6
316311AC2-079 GEN
Solar/Wind Harmer
18.424
315833AF1-017_GEN
Solar/Wind Harmer
6.937
316349AD2-085 GEN
Solar/Wind Harmer
3.248
3143316POE
Solar/Wind Harmer
-0.143
971445AH1-216 GEN
Solar/Wind Harmer
22.478
315611Z1-036_GEN2
Solar/Wind Harmer
8.901
972265AH1-717 GEN
Adder
24.649
3151201GRAVEL4
Adder
23.107
3151191GRAVEL3
Adder
22.815
3151211GRAVEL5
Adder
22.815
3130156CHOWAN
Solar/Wind Harmer
-0.036
3130156CHOWAN
Solar/Wind Harmer
-0.036
315816AE2-034 GEN
Solar/Wind Harmer
2.83
316369SG1_INVT
Solar/Wind Harmer
6.201
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.95
315733AD1-074 GEN2
Solar/Wind Harmer
6.95
315735AD1-075 GEN1
Solar/Wind Harmer
3.476
965291AG1-394 GEN
Solar/Wind Harmer
3.038
971285AH1-108 GEN
Adder
2.292
316132AB2-190 GEN1
Solar/Wind Harmer
3.453
3146206CASHIE
Solar/Wind Harmer
-0.034
970601AG2-382 GEN
Solar/Wind Harmer
14.907
316318V4-068
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
-0.091
3145893MURPHYS
Solar/Wind Harmer
-0.034
946281AF1-292 GEN
Solar/Wind Harmer
0.753
3145513AHOSKIE
Solar/Wind Harmer
0.293
961941AG1-037 GEN
Solar/Wind Harmer
0.252
3145513AHOSKIE
Solar/Wind Harmer
-0.033
3146043SEABORD
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.066
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.033
315607AA1-063A GEN
Solar/Wind Harmer
3.371
316087AB2-174 GEN
Solar/Wind Harmer
4.759
315652AC1-086 GEN
Solar/Wind Harmer
37.252
3137643SOCKMAN
Solar/Wind Harmer
-0.131
3145796HORNRTN
Solar/Wind Harmer
-0.104
3145796HORNRTN
Solar/Wind Harmer
-0.013
957831AF2-077 GEN
Solar/Wind Harmer
0.98
3138283WHITEMARSH
Solar/Wind Harmer
0.05
3146033SCOT NK
Solar/Wind Harmer
-0.129
970831AG2-522 GEN
Solar/Wind Harmer
15.839
315976AC1-164 GENA
Solar/Wind Harmer
33.15
316169AC1-164_GENC
Solar/Wind Harmer
28.639
315975AC1-164 GENB
Solar/Wind Harmer
0.981
316005AA1-067
Solar/Wind Harmer
0.63
3145746EVERETS
Solar/Wind Harmer
-0.123
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
970181AG2-120 GEN
Solar/Wind Harmer
4.087
971167AH1-042 GEN
Solar/Wind Harmer
29.578
957861AF2-080 GEN
Solar/Wind Harmer
13.434
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
316420AA1-050 GEN
Solar/Wind Harmer
3.484
316319Z2-044 C
Solar/Wind Harmer
1.678
3145573BETHELC
Solar/Wind Harmer
-0.03
3145573BETHELC
Solar/Wind Harmer
-0.03
3143873LANEXA
Solar/Wind Harmer
-0.018
316239AB2-077_GEN
Solar/Wind Harmer
0.91
316238AB2-078_GEN
Solar/Wind Harmer
0.91
316314AB2-024 C
Solar/Wind Harmer
2.562
315662AE1-191 GEN
Solar/Wind Harmer
3.613
970533AG2-339 GEN
50/50
32.326
970531AG2-338 GEN
50/50
12.93
315242AE2-183_GT2
50/50
5.833
315241AE2-183_GT1
50/50
5.797
972185AH1-677 GEN
50/50
21.03
3151041BRUNSWICKG3
50/50
4.589
972187AH1-678 GEN
50/50
10.532
3150991CHESPKB
50/50
3.712
3150991CHESPKB
50/50
3.623
971223AH1-071 GEN
Solar/Wind Harmer
5.226
970933AG2-581 GEN
Solar/Wind Harmer
35.807
3143526WINTERP
Solar/Wind Harmer
-0.197
316185AD1-033 GEN
Solar/Wind Harmer
3.966
3142956BIRDNECK
Solar/Wind Harmer
2.015
316316AC1-027 C
Solar/Wind Harmer
1.153
316036AC1-147 C
Solar/Wind Harmer
1.012
3145506HICKORY
Solar/Wind Harmer
-0.149
3145506HICKORY
Solar/Wind Harmer
-0.09
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.523
316018AA1-139 ULT2
Solar/Wind Harmer
3.202
316017AA1-139 ULT1
Solar/Wind Harmer
3.024
3137176SLIGO L2192
Solar/Wind Harmer
-0.148
3146456SLIGO L269
Solar/Wind Harmer
4.406
3130086AYDLETT
Solar/Wind Harmer
-0.148
3144356SAPONY
Solar/Wind Harmer
1.299
3146386ELIZ CT
Solar/Wind Harmer
-0.037
316431W1029_GEN1
Solar/Wind Harmer
6.628
316433W1029_GEN2
Solar/Wind Harmer
6.628
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
316236AE1-162_GEN
Solar/Wind Harmer
1.097
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
970657AG2-426 GEN
Solar/Wind Harmer
11.293
970657AG2-426 GEN
Solar/Wind Harmer
2.361
315742AE1-103 GEN
Solar/Wind Harmer
3.73
3146376EDENTON
Solar/Wind Harmer
1.058
3146376EDENTON
Solar/Wind Harmer
1.058
970099AG2-077 GEN
Solar/Wind Harmer
43.897
316033AB2-134 GEN
Solar/Wind Harmer
11.193
315697AD1-025 GEN
Solar/Wind Harmer
7.02
316065AD1-022 GEN
Solar/Wind Harmer
17.09
3145893MURPHYS
Solar/Wind Harmer
0.948
3145893MURPHYS
Solar/Wind Harmer
-0.061
316240AF1-291 C
Solar/Wind Harmer
1.017
3146173TUNIS
Solar/Wind Harmer
-0.034
3146173TUNIS
Solar/Wind Harmer
-0.034
944641AF1-129 GEN
Adder
141.653
316181AB2-040 GEN
Solar/Wind Harmer
4.638
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
316426AA2-053 GEN
Solar/Wind Harmer
3.327
3145593CAROLNA
Solar/Wind Harmer
-0.033
3145593CAROLNA
Solar/Wind Harmer
-0.033
966811AG1-552 GEN
Solar/Wind Harmer
3.692
3145593CAROLNA
Solar/Wind Harmer
0.273
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145783HORNRTN
Solar/Wind Harmer
3.873
3145783HORNRTN
Solar/Wind Harmer
3.098
3145783HORNRTN
Solar/Wind Harmer
0.968
3145783HORNRTN
Solar/Wind Harmer
0.387
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.063
3145933PARMELE
Solar/Wind Harmer
-0.032
316274AC1-208 GEN
Solar/Wind Harmer
3.418
971741AH1-377 GEN
Solar/Wind Harmer
35.868
939181AE1-148 GEN
Solar/Wind Harmer
17.303
3145493TOT1
Solar/Wind Harmer
0.469
3145453TOT5
Solar/Wind Harmer
0.282
3145603CNETO
Solar/Wind Harmer
0.188
316075AC2-137 C
Solar/Wind Harmer
0.818
313527AB2-043 GEN
Solar/Wind Harmer
4.909
316441AF1-014 GEN
Solar/Wind Harmer
2.024
3150691DARBY 3
Adder
18.946
3150701DARBY 4
Adder
18.902
3150681DARBY 2
Adder
18.88
3150671DARBY 1
Adder
18.858
3142366NRTHEST
Adder
0.854
3144293JTRSVLE
Adder
0.813
3144293JTRSVLE
Adder
0.685
3142296MT RD221
Adder
0.722
3150341NORNECKC1
Adder
2.217
3150341NORNECKC1
Adder
2.199
316447AC1-158 HLD
Solar/Wind Helper
4.811
315651AD1-115 GEN
Solar/Wind Helper
0.939
226929AD2-058 GEN
Solar/Wind Helper
0.091
970301AG2-198 GEN
Solar/Wind Harmer
14.287
315666AE1-190 GEN
Solar/Wind Harmer
0.903
972205AH1-687 GEN
Adder
7.91
972189AH1-679 GEN
Adder
2.347
316164AC1-076 GEN
Solar/Wind Helper
1.495
316411AF1-147_GEN1
Solar/Wind Helper
0.81
316415AF1-147_GEN2
Solar/Wind Helper
0.81
3138216PACIFIC
Solar/Wind Helper
0.04
3145796HORNRTN
Solar/Wind Harmer
-0.033
3147043LAWRENC
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.01
3143096IRON208
Adder
1.188
3143096IRON208
Adder
1.164
316210AC1-098 GEN
Solar/Wind Harmer
5
3145933PARMELE
Solar/Wind Harmer
-0.032
966801AG1-551 GEN
Solar/Wind Harmer
3.962
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
315724AD1-057 GEN
Solar/Wind Harmer
1.79
316327AA2-057 GEN
Solar/Wind Harmer
3.117
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
3146233WITAKRS
Solar/Wind Harmer
0.636
3146233WITAKRS
Solar/Wind Harmer
-0.02
3146073TAR RVR
Solar/Wind Harmer
-0.03
3146083TARBORO
Solar/Wind Harmer
-0.03
3138543CONSLDL
Solar/Wind Harmer
-0.02
316131AB2-060 GEN
Solar/Wind Harmer
3.254
3141843SHACKLE
Adder
1.366
316203AE2-005 GEN
Solar/Wind Harmer
12.66
316280AD1-041 GEN
Solar/Wind Harmer
2.258
3144293JTRSVLE
Adder
0.813
3150351NORNECKC2
Adder
2.146
316044AC1-158 PL1
Solar/Wind Helper
2.186
316450AC1-158 RIC
Solar/Wind Helper
0.583
3147666LOUISA
Solar/Wind Helper
0.716
316170AC1-121 GEN2
Solar/Wind Helper
0.43
3141196NOKESVL
Solar/Wind Helper
1.041
3132273ORANGE
Solar/Wind Helper
0.048
227287AC2-120 GEN
Solar/Wind Helper
0.313
226910AB2-157 C
Solar/Wind Helper
0.013
970909AG2-566 GEN
Solar/Wind Harmer
2.713
316129AC1-054 GEN
Solar/Wind Harmer
2.766
971065AG2-659 GEN
Solar/Wind Harmer
15.722
316336AC2-165 C
Solar/Wind Harmer
5.426
3145746EVERETS
Solar/Wind Harmer
-0.031
3145746EVERETS
Solar/Wind Harmer
-0.031
315722AD1-056 GEN
Solar/Wind Harmer
3.254
316494AC1-189 GEN
Solar/Wind Harmer
3.304
3142433PROV 92
Solar/Wind Harmer
-0.122
3142433PROV 92
Adder
0.53
3142433PROV 92
Adder
0.53
3146233WITAKRS
Solar/Wind Harmer
-0.12
961671AG1-007 GEN
Solar/Wind Harmer
0.384
3146083TARBORO
Solar/Wind Harmer
-0.03
3145493TOT1
Solar/Wind Harmer
0.9
316237AB2-079_GEN
Solar/Wind Harmer
0.91
971777AH1-397 GEN
Solar/Wind Harmer
3.531
3141843SHACKLE
Adder
1.366
3144293JTRSVLE
Adder
0.813
3150351NORNECKC2
Adder
2.111
316045AC1-158 PL2
Solar/Wind Helper
6.998
3147666LOUISA
Solar/Wind Helper
1.245
316192AB2-158 GEN
Solar/Wind Helper
2.049
316254AC1-120 GEN1
Solar/Wind Helper
1.291
316006AB2-029 C
Solar/Wind Helper
0.13
NYPJM->LTFIMP_NY
CLTF
3.623
LAGNLTFEXP_LAGN->PJM
CLTF
12.7
LGEELTFEXP_LGEE->PJM
CLTF
2.32
WECLTFEXP_WEC->PJM
CLTF
1.178
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
38.248
TVALTFEXP_TVA->PJM
CLTF
6.385
CPLELTFEXP_CPLE->PJM
CLTF
17.51
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.525
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.942
MECLTFEXP_MEC->PJM
CLTF
6.275
SIGELTFEXP_SIGE->PJM
CLTF
0.19

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T574_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T574_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:152.97 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6027.13
MW Contribution:19.23
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.58
315244AE2-183_ST
50/50
9.618
963041AG1-153 GEN
50/50
8.863
315779AE2-040
50/50
4.423
3151081ELIZAR1
50/50
29.93
3151091ELIZAR2
50/50
29.41
941591AE2-156 GEN
50/50
27.339
3152611GOSPORTB
50/50
4.153
3152621GOSPORTC
50/50
3.524
3152601GOSPORTA
50/50
3.251
971285AH1-108 GEN
50/50
2.407
972263AH1-716 GEN
50/50
170.499
941031AE2-094 GEN
Solar/Wind Harmer
73.029
944011AF1-069 GEN
Solar/Wind Harmer
22.883
970673AG2-436 GEN
Solar/Wind Harmer
80.276
970119AG2-088 GEN
50/50
49.347
315243AE2-183_GT3
50/50
5.563
3151051BRUNSWICKS1
50/50
9.085
3151021BRUNSWICKG1
50/50
4.377
971451AH1-221 GEN
50/50
13.295
3150981CHESPKA
50/50
4.072
3150851SPRUNCC
50/50
1.471
3152331SURRY 2
50/50
12.317
3143226MDLTHAN
Solar/Wind Harmer
-0.041
940641AE2-051 GEN
Solar/Wind Harmer
36.965
939411AE1-173 GEN
Solar/Wind Harmer
191.106
3143526WINTERP
Solar/Wind Harmer
-0.196
970919AG2-571 GEN
Solar/Wind Harmer
11.373
970087AG2-069 GEN
Solar/Wind Harmer
33.546
316294AC1-161 GEN
Solar/Wind Harmer
11.322
944591AF1-124 GEN
Solar/Wind Harmer
158.875
316375AC2-012 GEN
Solar/Wind Harmer
11.949
316388AE2-253 GEN
Solar/Wind Harmer
2.323
3146456SLIGO L269
Solar/Wind Harmer
-0.034
316246AF1-032 C
Solar/Wind Harmer
0.693
970659AG2-427 GEN
Solar/Wind Harmer
18.128
316381AD1-082 GEN
Solar/Wind Harmer
3.129
970661AG2-428 GEN
Solar/Wind Harmer
36.248
316093AE2-104_GEN
Solar/Wind Harmer
9.91
316072AD1-144
Solar/Wind Harmer
0.685
3146516WINFALL
Solar/Wind Harmer
-0.109
3151031BRUNSWICKG2
50/50
4.377
3151101ELIZAR3
50/50
30.313
3150861SPRUNCD
50/50
1.471
3151161SURRY 1
50/50
11.323
970917AG2-570 GEN
Solar/Wind Harmer
89.846
315773AC2-141 GEN
Solar/Wind Harmer
14.644
944581AF1-123 GEN
Solar/Wind Harmer
158.305
944601AF1-125 GEN
Solar/Wind Harmer
155.834
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
4.188
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
21.335
970659AG2-427 GEN
Solar/Wind Harmer
3.213
316083AB2-161 GEN
Solar/Wind Harmer
5.538
970661AG2-428 GEN
Solar/Wind Harmer
6.424
316320Y1-086
Solar/Wind Harmer
1.998
316435W1029_GEN3
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
1.016
3145336SMITFLD
Solar/Wind Harmer
-0.013
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.025
316313AB2-026
Solar/Wind Harmer
0.898
316258AE1-075 C
Solar/Wind Harmer
0.808
316405AF2-144 C
Solar/Wind Harmer
0.853
3143336POWHATN
Solar/Wind Harmer
3.359
965281AG1-393 GEN
Solar/Wind Harmer
4.153
3151221GRAVEL6
Adder
21.431
3151171GRAVELC
Adder
4.123
3146376EDENTON
Solar/Wind Harmer
-0.033
961611AG1-000B GEN
Solar/Wind Harmer
6.933
316365GEN2_N
Solar/Wind Harmer
2.214
315614AA2-178 GEN
Solar/Wind Harmer
3.511
315778AD1-151 GEN
Solar/Wind Harmer
28.152
970129AG2-093 GEN
Solar/Wind Harmer
18.183
3156081AA2-088 GEN
Solar/Wind Harmer
10.453
316478AD1-087 GEN
Solar/Wind Harmer
2.786
316486AD2-202 GEN
Solar/Wind Harmer
0.816
971157AH1-035 GEN
Solar/Wind Harmer
4.016
315737AD1-076 GEN
Solar/Wind Harmer
6.093
970133AG2-095 GEN
Solar/Wind Harmer
3.601
966621AG1-532 GEN
Solar/Wind Harmer
0.649
3144216WINCHST
Adder
1.073
3145893MURPHYS
Solar/Wind Harmer
0.222
970673AG2-436 GEN
Solar/Wind Harmer
40.646
316233AE1-074 FULL
Solar/Wind Harmer
1.019
971281AH1-106 GEN
Solar/Wind Harmer
6.156
971283AH1-107 GEN
Solar/Wind Harmer
6.156
971967AH1-528 GEN
Solar/Wind Harmer
70.663
970085AG2-068 GEN
Solar/Wind Harmer
22.364
970581AG2-369 GEN
Solar/Wind Harmer
19.233
316315AB2-025 C
Solar/Wind Harmer
0.96
315814AE2-033 C
Solar/Wind Harmer
33.023
3143316POE
Solar/Wind Harmer
-0.138
957871AF2-081 GEN
Solar/Wind Harmer
17.208
319010AE1-072 C
Solar/Wind Harmer
6.946
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
1.032
315833AF1-017_GEN
Solar/Wind Harmer
6.476
316349AD2-085 GEN
Solar/Wind Harmer
3.033
316311AC2-079 GEN
Solar/Wind Harmer
17.198
313526AB2-022
Solar/Wind Harmer
0.919
315835AF2-110_GEN
Solar/Wind Harmer
4.261
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
316321Z2-027
Solar/Wind Harmer
0.916
3146396TANGLEW
Solar/Wind Harmer
0.625
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
971445AH1-216 GEN
Solar/Wind Harmer
20.803
315611Z1-036_GEN2
Solar/Wind Harmer
8.244
972265AH1-717 GEN
Adder
22.888
3151201GRAVEL4
Adder
21.456
3151191GRAVEL3
Adder
21.184
3151211GRAVEL5
Adder
21.184
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
316369SG1_INVT
Solar/Wind Harmer
5.828
315816AE2-034 GEN
Solar/Wind Harmer
2.633
316132AB2-190 GEN1
Solar/Wind Harmer
3.27
3130546PLYMOUTH
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
2.85
315732AD1-074 GEN1
Solar/Wind Harmer
6.483
315733AD1-074 GEN2
Solar/Wind Harmer
6.483
315735AD1-075 GEN1
Solar/Wind Harmer
3.242
946281AF1-292 GEN
Solar/Wind Harmer
0.717
316318V4-068
Solar/Wind Harmer
0.794
3145893MURPHYS
Solar/Wind Harmer
-0.086
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
13.932
316087AB2-174 GEN
Solar/Wind Harmer
4.521
3146043SEABORD
Solar/Wind Harmer
-0.031
3145513AHOSKIE
Solar/Wind Harmer
0.275
961941AG1-037 GEN
Solar/Wind Harmer
0.237
3145513AHOSKIE
Solar/Wind Harmer
-0.031
315607AA1-063A GEN
Solar/Wind Harmer
3.181
3145683EARLEYS
Solar/Wind Harmer
-0.062
3145683EARLEYS
Solar/Wind Harmer
-0.031
3145683EARLEYS
Solar/Wind Harmer
-0.031
315652AC1-086 GEN
Solar/Wind Harmer
35.304
3137643SOCKMAN
Solar/Wind Harmer
-0.124
3145796HORNRTN
Solar/Wind Harmer
-0.098
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.121
970831AG2-522 GEN
Solar/Wind Harmer
15.086
957831AF2-077 GEN
Solar/Wind Harmer
0.889
3138283WHITEMARSH
Solar/Wind Harmer
0.046
316005AA1-067
Solar/Wind Harmer
0.594
3145746EVERETS
Solar/Wind Harmer
-0.116
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
970181AG2-120 GEN
Solar/Wind Harmer
3.854
957861AF2-080 GEN
Solar/Wind Harmer
12.697
316239AB2-077_GEN
Solar/Wind Harmer
0.873
316238AB2-078_GEN
Solar/Wind Harmer
0.873
316420AA1-050 GEN
Solar/Wind Harmer
3.296
316319Z2-044 C
Solar/Wind Harmer
1.592
971167AH1-042 GEN
Solar/Wind Harmer
27.693
3145573BETHELC
Solar/Wind Harmer
-0.029
3145573BETHELC
Solar/Wind Harmer
-0.029
315976AC1-164 GENA
Solar/Wind Harmer
30.185
316169AC1-164_GENC
Solar/Wind Harmer
26.077
315975AC1-164 GENB
Solar/Wind Harmer
0.893
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
972205AH1-687 GEN
Adder
7.923
972189AH1-679 GEN
Adder
2.542
972193AH1-681 GEN
Adder
2.896
316164AC1-076 GEN
Solar/Wind Helper
1.492
316411AF1-147_GEN1
Solar/Wind Helper
0.805
316415AF1-147_GEN2
Solar/Wind Helper
0.805
3138216PACIFIC
Solar/Wind Helper
0.039
3146516WINFALL
Solar/Wind Harmer
-0.034
3145336SMITFLD
Solar/Wind Harmer
-0.134
957481AF2-042 GEN
Solar/Wind Harmer
105.016
315800Z1-036_GEN1
Solar/Wind Harmer
8.244
3143336POWHATN
Solar/Wind Harmer
3.951
3151171GRAVELC
Adder
3.136
3130156CHOWAN
Solar/Wind Harmer
-0.033
315671AE2-027_GEN
Solar/Wind Harmer
24.714
961611AG1-000B GEN
Solar/Wind Harmer
16.249
316023GEN1_S
Solar/Wind Harmer
2.214
971647AH1-324 GEN
Solar/Wind Harmer
16.385
3145663CRESWEL
Solar/Wind Harmer
-0.091
971163AH1-040 GEN
Solar/Wind Harmer
30.505
315693AD1-088 GEN
Solar/Wind Harmer
16.249
971069AG2-661 GEN
Solar/Wind Harmer
5.142
316458AB2-190 GEN2
Solar/Wind Harmer
3.27
962491AG1-098 GEN
Solar/Wind Harmer
21.612
970129AG2-093 GEN
Solar/Wind Harmer
7.365
960081AF2-299 GEN
Solar/Wind Harmer
3.599
3138126ROCKLANDING
Solar/Wind Harmer
0.098
3145893MURPHYS
Solar/Wind Harmer
-0.127
3145893MURPHYS
Solar/Wind Harmer
0.946
3146206CASHIE
Solar/Wind Harmer
-0.032
971547AH1-271 GEN
Solar/Wind Harmer
7.961
3142543TWELFTH
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.031
316011AB1-132 GEN
Solar/Wind Harmer
6.566
962571AG1-106 GEN
Solar/Wind Harmer
4.511
971795AH1-408 GEN
Solar/Wind Harmer
23.527
3146263WOODLND
Solar/Wind Harmer
-0.031
316190AA2-174 GEN
Solar/Wind Harmer
0.382
316336AC2-165 C
Solar/Wind Harmer
5.409
3147043LAWRENC
Adder
2.503
971317AH1-138 GEN
Solar/Wind Harmer
3.871
3143096IRON208
Adder
1.154
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316159AE1-175 C
Solar/Wind Harmer
0.823
316174AB2-169 GEN
Solar/Wind Harmer
4.727
944631AF1-128 GEN
Adder
129.496
315687AD1-152 GEN
Solar/Wind Harmer
3.646
316212AC1-099_GEN
Solar/Wind Harmer
2.626
316129AC1-054 GEN
Solar/Wind Harmer
2.637
971065AG2-659 GEN
Solar/Wind Harmer
14.993
3146293MARTNCO
Solar/Wind Harmer
0.185
315722AD1-056 GEN
Solar/Wind Harmer
3.088
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316494AC1-189 GEN
Solar/Wind Harmer
3.123
316237AB2-079_GEN
Solar/Wind Harmer
0.873
3146233WITAKRS
Solar/Wind Harmer
-0.114
961671AG1-007 GEN
Solar/Wind Harmer
0.363
3146083TARBORO
Solar/Wind Harmer
-0.029
3145493TOT1
Solar/Wind Harmer
0.852
3142433PROV 92
Solar/Wind Harmer
-0.114
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.907
972277AH1-723 GEN
Adder
75.541
316045AC1-158 PL2
Solar/Wind Helper
7.02
3147666LOUISA
Solar/Wind Helper
1.242
316192AB2-158 GEN
Solar/Wind Helper
2.041
316254AC1-120 GEN1
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.129
970533AG2-339 GEN
50/50
30.814
970531AG2-338 GEN
50/50
12.326
315242AE2-183_GT2
50/50
5.563
315241AE2-183_GT1
50/50
5.529
972185AH1-677 GEN
50/50
20.054
3151041BRUNSWICKG3
50/50
4.377
972187AH1-678 GEN
50/50
10.045
3150991CHESPKB
50/50
3.416
3150991CHESPKB
50/50
3.334
971223AH1-071 GEN
Solar/Wind Harmer
5.198
3143526WINTERP
Solar/Wind Harmer
-0.196
970933AG2-581 GEN
Solar/Wind Harmer
34.189
3144356SAPONY
Solar/Wind Harmer
1.242
316185AD1-033 GEN
Solar/Wind Harmer
3.648
3142956BIRDNECK
Solar/Wind Harmer
1.854
316316AC1-027 C
Solar/Wind Harmer
1.061
316036AC1-147 C
Solar/Wind Harmer
0.932
3145506HICKORY
Solar/Wind Harmer
-0.137
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.02
316339AD2-160 GEN
Solar/Wind Harmer
2.323
316018AA1-139 ULT2
Solar/Wind Harmer
2.948
316017AA1-139 ULT1
Solar/Wind Harmer
2.785
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.058
3130086AYDLETT
Solar/Wind Harmer
-0.137
970657AG2-426 GEN
Solar/Wind Harmer
10.662
970657AG2-426 GEN
Solar/Wind Harmer
2.23
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
6.125
316433W1029_GEN2
Solar/Wind Harmer
6.125
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
316236AE1-162_GEN
Solar/Wind Harmer
1.015
970099AG2-077 GEN
Solar/Wind Harmer
42.007
3146626S HERTFORD
Solar/Wind Harmer
-0.033
3146626S HERTFORD
Solar/Wind Harmer
-0.033
315742AE1-103 GEN
Solar/Wind Harmer
3.474
3146376EDENTON
Solar/Wind Harmer
0.981
3146376EDENTON
Solar/Wind Harmer
0.981
316240AF1-291 C
Solar/Wind Harmer
0.989
316033AB2-134 GEN
Solar/Wind Harmer
10.519
315697AD1-025 GEN
Solar/Wind Harmer
6.597
944641AF1-129 GEN
Adder
138.008
316065AD1-022 GEN
Solar/Wind Harmer
15.96
3145893MURPHYS
Solar/Wind Harmer
0.889
3145893MURPHYS
Solar/Wind Harmer
-0.057
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
316181AB2-040 GEN
Solar/Wind Harmer
4.403
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.146
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.497
3145593CAROLNA
Solar/Wind Harmer
0.258
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146206CASHIE
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.055
961681AG1-008 GEN
Solar/Wind Harmer
25.055
3150921YORKTN3
Adder
7.106
3146173TUNIS
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.537
3156021HOLLOMANSOL
Solar/Wind Harmer
4.249
316463AE2-346 GEN
Solar/Wind Harmer
0.51
316140AB2-099
Solar/Wind Harmer
0.212
962331AG1-082 GEN
Solar/Wind Harmer
3.94
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3146263WOODLND
Solar/Wind Harmer
-0.031
3147043LAWRENC
Solar/Wind Harmer
-0.018
3143096IRON208
Adder
1.154
3143096IRON208
Adder
1.131
316317KELFORD C
Solar/Wind Harmer
1.459
3145823KELFORD
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316382AG1-145 C
Solar/Wind Harmer
0.924
316210AC1-098 GEN
Solar/Wind Harmer
4.726
3142946ENON
Solar/Wind Harmer
-0.01
3145933PARMELE
Solar/Wind Harmer
-0.03
966801AG1-551 GEN
Solar/Wind Harmer
3.729
315724AD1-057 GEN
Solar/Wind Harmer
1.698
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.029
316327AA2-057 GEN
Solar/Wind Harmer
2.954
970909AG2-566 GEN
Solar/Wind Harmer
2.75
316131AB2-060 GEN
Solar/Wind Harmer
3.123
970293AG2-193 GEN
Solar/Wind Harmer
3.602
3146233WITAKRS
Solar/Wind Harmer
0.603
3146233WITAKRS
Solar/Wind Harmer
-0.019
3138543CONSLDL
Solar/Wind Harmer
-0.019
964241AG1-285 GEN
Solar/Wind Harmer
22.468
3146073TAR RVR
Solar/Wind Harmer
-0.029
3146083TARBORO
Solar/Wind Harmer
-0.029
3142433PROV 92
Adder
0.494
3142433PROV 92
Adder
0.494
3144293JTRSVLE
Adder
0.786
3141843SHACKLE
Adder
1.247
3150351NORNECKC2
Adder
1.939
972255AH1-712 GEN
Adder
64.825
316044AC1-158 PL1
Solar/Wind Helper
2.193
316450AC1-158 RIC
Solar/Wind Helper
0.585
3147666LOUISA
Solar/Wind Helper
0.714
316170AC1-121 GEN2
Solar/Wind Helper
0.428
3141196NOKESVL
Solar/Wind Helper
1.035
3132273ORANGE
Solar/Wind Helper
0.047
227287AC2-120 GEN
Solar/Wind Helper
0.311
226910AB2-157 C
Solar/Wind Helper
0.013
3145783HORNRTN
Solar/Wind Harmer
3.668
3145783HORNRTN
Solar/Wind Harmer
2.934
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.367
316274AC1-208 GEN
Solar/Wind Harmer
3.236
3142946ENON
Solar/Wind Harmer
-0.003
3145933PARMELE
Solar/Wind Harmer
-0.059
3145933PARMELE
Solar/Wind Harmer
-0.03
971741AH1-377 GEN
Solar/Wind Harmer
34.617
939181AE1-148 GEN
Solar/Wind Harmer
16.559
3142366NRTHEST
Adder
0.852
3150691DARBY 3
Adder
18.657
3150701DARBY 4
Adder
18.614
3150681DARBY 2
Adder
18.592
3150671DARBY 1
Adder
18.57
313527AB2-043 GEN
Solar/Wind Harmer
4.711
970301AG2-198 GEN
Solar/Wind Harmer
14.484
3145493TOT1
Solar/Wind Harmer
0.444
3145453TOT5
Solar/Wind Harmer
0.267
3145603CNETO
Solar/Wind Harmer
0.178
3144293JTRSVLE
Adder
0.786
3144293JTRSVLE
Adder
0.662
3142296MT RD221
Adder
0.76
3150341NORNECKC1
Adder
2.003
3150341NORNECKC1
Adder
1.987
316447AC1-158 HLD
Solar/Wind Helper
4.827
315651AD1-115 GEN
Solar/Wind Helper
0.935
226929AD2-058 GEN
Solar/Wind Helper
0.091
316075AC2-137 C
Solar/Wind Harmer
0.313
NYPJM->LTFIMP_NY
CLTF
3.562
LAGNLTFEXP_LAGN->PJM
CLTF
12.464
LGEELTFEXP_LGEE->PJM
CLTF
2.331
WECLTFEXP_WEC->PJM
CLTF
1.184
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.906
TVALTFEXP_TVA->PJM
CLTF
6.273
CPLELTFEXP_CPLE->PJM
CLTF
16.795
CBM West 2LTFEXP_CBM-W2->PJM
CBM
66.696
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.329
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.608
MECLTFEXP_MEC->PJM
CLTF
6.26
SIGELTFEXP_SIGE->PJM
CLTF
0.19

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.69 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4402.07
MW Contribution:13.87
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
43.39
315243AE2-183_GT3
50/50
5.306
3151051BRUNSWICKS1
50/50
8.655
3151021BRUNSWICKG1
50/50
4.17
971451AH1-221 GEN
50/50
12.666
3150981CHESPKA
50/50
3.862
3152331SURRY 2
50/50
11.978
940641AE2-051 GEN
Solar/Wind Harmer
26.972
939411AE1-173 GEN
Solar/Wind Harmer
139.157
3143226MDLTHAN
Solar/Wind Harmer
0.325
970919AG2-571 GEN
Solar/Wind Harmer
10.802
970533AG2-339 GEN
50/50
29.471
970531AG2-338 GEN
50/50
11.789
315242AE2-183_GT2
50/50
5.306
315241AE2-183_GT1
50/50
5.273
972185AH1-677 GEN
50/50
19.129
3151041BRUNSWICKG3
50/50
4.17
972187AH1-678 GEN
50/50
9.57
3150991CHESPKB
50/50
3.24
3150991CHESPKB
50/50
3.162
971223AH1-071 GEN
Solar/Wind Harmer
3.471
970933AG2-581 GEN
Solar/Wind Harmer
24.629
316185AD1-033 GEN
Solar/Wind Harmer
0.008
3145506HICKORY
Solar/Wind Harmer
1.168
3145506HICKORY
Solar/Wind Harmer
0.701
3145506HICKORY
Solar/Wind Harmer
0.175
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.28
316036AC1-147 C
Solar/Wind Harmer
0.054
316339AD2-160 GEN
Solar/Wind Harmer
0.472
316018AA1-139 ULT2
Solar/Wind Harmer
0.007
316017AA1-139 ULT1
Solar/Wind Harmer
0.162
3137176SLIGO L2192
Solar/Wind Harmer
1.156
3146456SLIGO L269
Solar/Wind Harmer
5.139
3130086AYDLETT
Solar/Wind Harmer
1.16
3144356SAPONY
Solar/Wind Harmer
2.426
3146386ELIZ CT
Solar/Wind Harmer
0.287
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3146516WINFALL
Solar/Wind Harmer
0.284
3143526WINTERP
Solar/Wind Harmer
1.47
3146626S HERTFORD
Solar/Wind Harmer
0.282
3146626S HERTFORD
Solar/Wind Harmer
0.282
970099AG2-077 GEN
Solar/Wind Harmer
29.918
3146376EDENTON
Solar/Wind Harmer
1.233
3146376EDENTON
Solar/Wind Harmer
1.233
316236AE1-162_GEN
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.003
970657AG2-426 GEN
Solar/Wind Harmer
9.567
970657AG2-426 GEN
Solar/Wind Harmer
2.006
316065AD1-022 GEN
Solar/Wind Harmer
12.243
3145893MURPHYS
Solar/Wind Harmer
1.767
3145893MURPHYS
Solar/Wind Harmer
0.475
3146173TUNIS
Solar/Wind Harmer
0.262
3146173TUNIS
Solar/Wind Harmer
0.262
316181AB2-040 GEN
Solar/Wind Harmer
0.376
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
316426AA2-053 GEN
Solar/Wind Harmer
0.866
3145593CAROLNA
Solar/Wind Harmer
0.255
3145593CAROLNA
Solar/Wind Harmer
0.255
966811AG1-552 GEN
Solar/Wind Harmer
2.773
3145593CAROLNA
Solar/Wind Harmer
0.318
316033AB2-134 GEN
Solar/Wind Harmer
0.015
315697AD1-025 GEN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
4.52
3145783HORNRTN
Solar/Wind Harmer
3.616
3145783HORNRTN
Solar/Wind Harmer
1.13
3145783HORNRTN
Solar/Wind Harmer
0.452
3145796HORNRTN
Solar/Wind Harmer
0.762
3145933PARMELE
Solar/Wind Harmer
0.493
3145933PARMELE
Solar/Wind Harmer
0.247
316274AC1-208 GEN
Solar/Wind Harmer
1.28
971741AH1-377 GEN
Solar/Wind Harmer
23.908
939181AE1-148 GEN
Solar/Wind Harmer
11.558
316240AF1-291 C
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.547
3145453TOT5
Solar/Wind Harmer
0.328
3145603CNETO
Solar/Wind Harmer
0.219
313527AB2-043 GEN
Solar/Wind Harmer
0.003
944641AF1-129 GEN
Adder
111.535
970301AG2-198 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
4.135
316263AC1-034 GEN
Solar/Wind Harmer
8.835
970323AG2-213 GEN
Solar/Wind Harmer
9.727
970087AG2-069 GEN
Solar/Wind Harmer
24.19
316294AC1-161 GEN
Solar/Wind Harmer
5.215
944591AF1-124 GEN
Solar/Wind Harmer
66.808
316375AC2-012 GEN
Solar/Wind Harmer
0.007
316388AE2-253 GEN
Solar/Wind Harmer
0.912
3146456SLIGO L269
Solar/Wind Harmer
0.29
316246AF1-032 C
Solar/Wind Harmer
0.13
316093AE2-104_GEN
Solar/Wind Harmer
4.794
3146516WINFALL
Solar/Wind Harmer
0.92
3146516WINFALL
Solar/Wind Harmer
0.284
316072AD1-144
Solar/Wind Harmer
0.103
3143526WINTERP
Solar/Wind Harmer
1.47
957481AF2-042 GEN
Solar/Wind Harmer
74.795
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
27.311
316381AD1-082 GEN
Solar/Wind Harmer
0.284
3145663CRESWEL
Solar/Wind Harmer
0.761
971163AH1-040 GEN
Solar/Wind Harmer
21.769
970659AG2-427 GEN
Solar/Wind Harmer
13.13
315693AD1-088 GEN
Solar/Wind Harmer
12.923
3151031BRUNSWICKG2
50/50
4.17
3151101ELIZAR3
50/50
28.777
3151161SURRY 1
50/50
10.302
316303AF2-085
50/50
5.785
315244AE2-183_ST
50/50
9.174
963041AG1-153 GEN
50/50
8.444
3151081ELIZAR1
50/50
28.413
3151091ELIZAR2
50/50
27.92
941591AE2-156 GEN
50/50
25.939
3152611GOSPORTB
50/50
3.939
3152621GOSPORTC
50/50
3.343
3152601GOSPORTA
50/50
3.084
315779AE2-040
50/50
4.048
972263AH1-716 GEN
50/50
164.964
941031AE2-094 GEN
Solar/Wind Harmer
61.065
944011AF1-069 GEN
Solar/Wind Harmer
19.952
970673AG2-436 GEN
Solar/Wind Harmer
69.269
970673AG2-436 GEN
Solar/Wind Harmer
46.179
971967AH1-528 GEN
Solar/Wind Harmer
50.977
970085AG2-068 GEN
Solar/Wind Harmer
16.126
970581AG2-369 GEN
Solar/Wind Harmer
13.869
957871AF2-081 GEN
Solar/Wind Harmer
14.487
319010AE1-072 C
Solar/Wind Harmer
1.462
3146406KITTY HAWK
Solar/Wind Harmer
0.036
316315AB2-025 C
Solar/Wind Harmer
0.234
315814AE2-033 C
Solar/Wind Harmer
22.859
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.156
316321Z2-027
Solar/Wind Harmer
0.053
3146396TANGLEW
Solar/Wind Harmer
0.789
3145176PASQUOTANK
Solar/Wind Harmer
0.177
3146486SUNBURY
Solar/Wind Harmer
0.286
3146486SUNBURY
Solar/Wind Harmer
0.286
315835AF2-110_GEN
Solar/Wind Harmer
1.956
316233AE1-074 FULL
Solar/Wind Harmer
0.226
971281AH1-106 GEN
Solar/Wind Harmer
3.922
971283AH1-107 GEN
Solar/Wind Harmer
3.922
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316311AC2-079 GEN
Solar/Wind Harmer
8.046
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.192
3130156CHOWAN
Solar/Wind Harmer
0.277
3130156CHOWAN
Solar/Wind Harmer
0.277
971445AH1-216 GEN
Solar/Wind Harmer
19.461
3143316POE
Solar/Wind Harmer
1.085
315816AE2-034 GEN
Solar/Wind Harmer
1.168
972265AH1-717 GEN
Adder
20.825
3151201GRAVEL4
Adder
19.522
3151191GRAVEL3
Adder
19.275
3151211GRAVEL5
Adder
19.275
3130546PLYMOUTH
Solar/Wind Harmer
0.268
315732AD1-074 GEN1
Solar/Wind Harmer
1.536
315733AD1-074 GEN2
Solar/Wind Harmer
1.536
315735AD1-075 GEN1
Solar/Wind Harmer
0.769
965291AG1-394 GEN
Solar/Wind Harmer
1.182
3146206CASHIE
Solar/Wind Harmer
0.265
970601AG2-382 GEN
Solar/Wind Harmer
9.896
316023GEN1_S
Solar/Wind Harmer
0.603
3151171GRAVELC
Adder
2.853
962491AG1-098 GEN
Solar/Wind Harmer
15.256
3146206CASHIE
Solar/Wind Harmer
0.265
971547AH1-271 GEN
Solar/Wind Harmer
5.655
3138126ROCKLANDING
Solar/Wind Harmer
0.121
3145893MURPHYS
Solar/Wind Harmer
1.056
3145893MURPHYS
Solar/Wind Harmer
1.174
961611AG1-000B GEN
Solar/Wind Harmer
13.793
3146173TUNIS
Solar/Wind Harmer
0.262
960081AF2-299 GEN
Solar/Wind Harmer
2.514
3145683EARLEYS
Solar/Wind Harmer
0.26
3146263WOODLND
Solar/Wind Harmer
0.259
971647AH1-324 GEN
Solar/Wind Harmer
11.046
316011AB1-132 GEN
Solar/Wind Harmer
4.685
962571AG1-106 GEN
Solar/Wind Harmer
3.666
316190AA2-174 GEN
Solar/Wind Harmer
0
971795AH1-408 GEN
Solar/Wind Harmer
17.096
3145963POPLR C
Solar/Wind Harmer
0.256
971317AH1-138 GEN
Solar/Wind Harmer
1.913
3145823KELFORD
Solar/Wind Harmer
0.256
3143336POWHATN
Solar/Wind Harmer
4.523
316174AB2-169 GEN
Solar/Wind Harmer
0.007
3145783HORNRTN
Solar/Wind Harmer
0.254
3145796HORNRTN
Solar/Wind Harmer
0.838
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Adder
2.297
971069AG2-661 GEN
Solar/Wind Harmer
4.473
315687AD1-152 GEN
Solar/Wind Harmer
0.008
316159AE1-175 C
Solar/Wind Harmer
0.215
316212AC1-099_GEN
Solar/Wind Harmer
1.283
316458AB2-190 GEN2
Solar/Wind Harmer
1.325
3146293MARTNCO
Solar/Wind Harmer
0.229
316129AC1-054 GEN
Solar/Wind Harmer
0.928
970129AG2-093 GEN
Solar/Wind Harmer
7.001
971065AG2-659 GEN
Solar/Wind Harmer
10.492
315671AE2-027_GEN
Solar/Wind Harmer
15.643
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315722AD1-056 GEN
Solar/Wind Harmer
1.533
970917AG2-570 GEN
Solar/Wind Harmer
27.004
315773AC2-141 GEN
Solar/Wind Harmer
10.994
944581AF1-123 GEN
Solar/Wind Harmer
66.571
944601AF1-125 GEN
Solar/Wind Harmer
65.546
3144873MCLAUGH
Solar/Wind Harmer
0.007
3146456SLIGO L269
Solar/Wind Harmer
0.29
971153AH1-033 GEN
Solar/Wind Harmer
3.357
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.043
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.284
3146626S HERTFORD
Solar/Wind Harmer
0.282
3145273HOLLAND
Solar/Wind Harmer
0.209
3146376EDENTON
Solar/Wind Harmer
0.277
3145336SMITFLD
Solar/Wind Harmer
0.111
970661AG2-428 GEN
Solar/Wind Harmer
5.809
316083AB2-161 GEN
Solar/Wind Harmer
0.004
315614AA2-178 GEN
Solar/Wind Harmer
1.557
970659AG2-427 GEN
Solar/Wind Harmer
2.872
316365GEN2_N
Solar/Wind Harmer
0.603
3151221GRAVEL6
Adder
19.5
3151171GRAVELC
Adder
3.752
971157AH1-035 GEN
Solar/Wind Harmer
3.217
315813AE1-149 C
Solar/Wind Harmer
14.26
315737AD1-076 GEN
Solar/Wind Harmer
3.44
316478AD1-087 GEN
Solar/Wind Harmer
0.932
316486AD2-202 GEN
Solar/Wind Harmer
0.274
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3146206CASHIE
Solar/Wind Harmer
0.265
3144216WINCHST
Adder
0.999
3145893MURPHYS
Solar/Wind Harmer
0.442
3145893MURPHYS
Solar/Wind Harmer
0.264
3150921YORKTN3
Adder
6.638
957521AF2-046 GEN
Solar/Wind Harmer
19.613
961681AG1-008 GEN
Solar/Wind Harmer
19.613
961611AG1-000B GEN
Solar/Wind Harmer
7.014
3146173TUNIS
Solar/Wind Harmer
0.262
3156021HOLLOMANSOL
Solar/Wind Harmer
1.189
316463AE2-346 GEN
Solar/Wind Harmer
0.224
316140AB2-099
Solar/Wind Harmer
0.093
962331AG1-082 GEN
Solar/Wind Harmer
2.786
3146263WOODLND
Solar/Wind Harmer
0.259
313506AB2-031 GEN
Solar/Wind Harmer
0.8
3142666NORTHAMPTON
Solar/Wind Harmer
0.258
3145963POPLR C
Solar/Wind Harmer
0.256
316317KELFORD C
Solar/Wind Harmer
0.025
3145823KELFORD
Solar/Wind Harmer
0.256
316313AB2-026
Solar/Wind Harmer
0.16
316258AE1-075 C
Solar/Wind Harmer
0.192
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.845
3145796HORNRTN
Solar/Wind Harmer
1.016
3145796HORNRTN
Solar/Wind Harmer
0.254
3147043LAWRENC
Solar/Wind Harmer
0.152
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
20.127
316382AG1-145 C
Solar/Wind Harmer
0.002
965281AG1-393 GEN
Solar/Wind Harmer
2.647
316210AC1-098 GEN
Solar/Wind Harmer
2.301
3145933PARMELE
Solar/Wind Harmer
0.247
966801AG1-551 GEN
Solar/Wind Harmer
2.873
970129AG2-093 GEN
Solar/Wind Harmer
14.877
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
315724AD1-057 GEN
Solar/Wind Harmer
0.909
316327AA2-057 GEN
Solar/Wind Harmer
0.363
3150861SPRUNCD
Adder
1.101
970133AG2-095 GEN
Solar/Wind Harmer
2.289
3146233WITAKRS
Solar/Wind Harmer
1.186
3146233WITAKRS
Solar/Wind Harmer
0.161
3146073TAR RVR
Solar/Wind Harmer
0.236
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
0.264
3145513AHOSKIE
Solar/Wind Harmer
0.546
3145513AHOSKIE
Solar/Wind Harmer
0.261
3146043SEABORD
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.52
3145683EARLEYS
Solar/Wind Harmer
0.26
3145683EARLEYS
Solar/Wind Harmer
0.26
316087AB2-174 GEN
Solar/Wind Harmer
0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.531
315652AC1-086 GEN
Solar/Wind Harmer
28.344
3137643SOCKMAN
Solar/Wind Harmer
1.027
316369SG1_INVT
Solar/Wind Harmer
0.01
3145796HORNRTN
Solar/Wind Harmer
0.813
3145796HORNRTN
Solar/Wind Harmer
0.102
3146033SCOT NK
Solar/Wind Harmer
1.006
970831AG2-522 GEN
Solar/Wind Harmer
10.563
316132AB2-190 GEN1
Solar/Wind Harmer
1.325
316005AA1-067
Solar/Wind Harmer
0.26
3145746EVERETS
Solar/Wind Harmer
0.964
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
3145746EVERETS
Solar/Wind Harmer
0.242
970181AG2-120 GEN
Solar/Wind Harmer
3.014
3138283WHITEMARSH
Solar/Wind Harmer
0.056
971285AH1-108 GEN
Adder
1.802
957861AF2-080 GEN
Solar/Wind Harmer
10.3
316420AA1-050 GEN
Solar/Wind Harmer
0.008
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.236
3145573BETHELC
Solar/Wind Harmer
0.236
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
3.835
3144303KENBRDG
Solar/Wind Harmer
0.182
970683AG2-441 GEN
Solar/Wind Harmer
14.971
970681AG2-440 GEN
Solar/Wind Harmer
11.976
316118AC1-105 GEN
Solar/Wind Harmer
0.574
946301AF1-294 GEN
Solar/Wind Harmer
4.367
961791AG1-021 GEN
Solar/Wind Harmer
2.125
315657AE1-056 GEN
Solar/Wind Harmer
7.556
3147173SINAI
Solar/Wind Harmer
0.219
3147243WELCO
Solar/Wind Harmer
0.137
315976AC1-164 GENA
Solar/Wind Harmer
22.6
316169AC1-164_GENC
Solar/Wind Harmer
19.524
315975AC1-164 GENB
Solar/Wind Harmer
0.669
3141873WAN 176
Solar/Wind Harmer
0.043
315662AE1-191 GEN
Solar/Wind Harmer
0.007
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970189AG2-124 GEN
Solar/Wind Harmer
6.392
971167AH1-042 GEN
Solar/Wind Harmer
19.104
316059AD1-063 C
Solar/Wind Harmer
0.001
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3143873LANEXA
Solar/Wind Harmer
0.129
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.21
3138133OCRAN
Solar/Wind Harmer
0.062
3141783LANCAST
Solar/Wind Harmer
0.123
3141783LANCAST
Solar/Wind Harmer
0.082
962981AG1-147 GEN
Solar/Wind Harmer
7.345
970327AG2-215 GEN
Solar/Wind Harmer
6.31
970865AG2-541 GEN
Solar/Wind Harmer
6.523
970285AG2-188 GEN
Solar/Wind Harmer
14.703
971845AH1-439 GEN
Solar/Wind Harmer
8.235
3141813NORNECK
Solar/Wind Harmer
0.172
316123AC1-075 GEN
Solar/Wind Harmer
0.229
970165AG2-112 GEN
Solar/Wind Harmer
1.36
970163AG2-111 GEN
Solar/Wind Harmer
1.297
316312AB1-027
Solar/Wind Harmer
0.286
972205AH1-687 GEN
Adder
6.309
316223AC1-118
Solar/Wind Harmer
0.095
971447AH1-217 GEN
Solar/Wind Harmer
3.746
270494AE1-108_GEN
Solar/Wind Harmer
1.403
316164AC1-076 GEN
Solar/Wind Helper
1.139
3150851SPRUNCC
Adder
1.101
316494AC1-189 GEN
Solar/Wind Harmer
0.807
3146233WITAKRS
Solar/Wind Harmer
0.94
961671AG1-007 GEN
Solar/Wind Harmer
0.036
3146083TARBORO
Solar/Wind Harmer
0.236
3145493TOT1
Solar/Wind Harmer
1.049
316336AC2-165 C
Solar/Wind Harmer
0.009
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.835
316049AB1-081 GEN
Solar/Wind Harmer
1.331
3142053HEARTS
Solar/Wind Harmer
0.409
970401AG2-262 GEN
Solar/Wind Harmer
1.326
970685AG2-442 GEN
Solar/Wind Harmer
16.767
944631AF1-128 GEN
Adder
106.166
963171AG1-166 GEN
Solar/Wind Harmer
1.18
971563AH1-280 GEN
Solar/Wind Harmer
2.361
3144293JTRSVLE
Adder
0.705
3142543TWELFTH
Solar/Wind Harmer
0.021
971777AH1-397 GEN
Solar/Wind Harmer
0.569
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3141766HARMONY
Solar/Wind Harmer
0.043
3142433PROV 92
Solar/Wind Harmer
0.86
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
3138133OCRAN
Solar/Wind Harmer
0.125
316003AC1-222 GEN
Solar/Wind Harmer
0.006
3146926FARMVIL
Solar/Wind Harmer
0.123
970937AG2-583 GEN
Solar/Wind Harmer
11.537
962861AG1-135 GEN
Solar/Wind Harmer
5.983
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.072
3141726DUNNSVL
Solar/Wind Harmer
0.706
3150351NORNECKC2
Adder
1.716
3142416OLDCHRC
Solar/Wind Harmer
0.416
3142416OLDCHRC
Solar/Wind Harmer
0.159
972003AH1-546 GEN
Solar/Wind Harmer
6.522
316337AD2-073 GEN
Solar/Wind Harmer
0.133
971377AH1-170 GEN
Solar/Wind Harmer
1.41
3147623JAMES R
Solar/Wind Harmer
0.306
970223AG2-152 GEN
Solar/Wind Harmer
9.004
270016AE1-250 BESS
Solar/Wind Harmer
0.004
3147123OTTER R
Solar/Wind Harmer
0.068
316045AC1-158 PL2
Solar/Wind Helper
5.515
3147666LOUISA
Solar/Wind Helper
1.037
316192AB2-158 GEN
Solar/Wind Helper
1.708
3146083TARBORO
Solar/Wind Harmer
0.236
3138543CONSLDL
Solar/Wind Harmer
0.156
316131AB2-060 GEN
Solar/Wind Harmer
0.739
964241AG1-285 GEN
Solar/Wind Harmer
15.529
970909AG2-566 GEN
Solar/Wind Harmer
2.481
961601AG1-000A GEN
Solar/Wind Harmer
16.539
3145543BTLEBRO
Solar/Wind Harmer
0.232
3145543BTLEBRO
Solar/Wind Harmer
0.232
971623AH1-311 GEN
Solar/Wind Harmer
0.465
315785AD2-033 C
Solar/Wind Harmer
1.864
970257AG2-171 GEN
Solar/Wind Harmer
7.295
959311AF2-222 GEN
Solar/Wind Harmer
20.178
3142946ENON
Solar/Wind Harmer
0.074
963181AG1-167 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3147133PAMPLIN
Solar/Wind Harmer
0.687
971193AH1-056 GEN
Solar/Wind Harmer
13.34
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
9.346
316156AD2-030 GEN
Solar/Wind Harmer
0.16
3141873WAN 176
Solar/Wind Harmer
3.848
316280AD1-041 GEN
Solar/Wind Harmer
0.004
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
3141843SHACKLE
Adder
1.102
3143096IRON208
Adder
0.902
3143096IRON208
Adder
0.884
3141766HARMONY
Solar/Wind Harmer
2.867
3142433PROV 92
Adder
0.418
3142433PROV 92
Adder
0.418
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.123
316283AC2-100 C
Solar/Wind Harmer
0.389
971683AH1-343 GEN
Solar/Wind Harmer
7.294
962971AG1-146 GEN
Solar/Wind Harmer
3.148
970293AG2-193 GEN
Solar/Wind Harmer
2.064
970009AG2-005 GEN
Solar/Wind Harmer
1.436
316404AE1-155 C
Solar/Wind Harmer
0.042
3146776BUCKING
Solar/Wind Harmer
0.065
3150351NORNECKC2
Adder
1.745
3142416OLDCHRC
Solar/Wind Harmer
1.55
3141906WESTMOR
Solar/Wind Harmer
0.053
970221AG2-151 GEN
Solar/Wind Harmer
7.048
316473AC1-191 GEN
Solar/Wind Harmer
0.412
970737AG2-469 GEN
Solar/Wind Harmer
4.87
316044AC1-158 PL1
Solar/Wind Helper
1.723
316450AC1-158 RIC
Solar/Wind Helper
0.459
3147666LOUISA
Solar/Wind Helper
0.596
971775AH1-396 GEN
Solar/Wind Harmer
0.365
316034AC1-036 C
Solar/Wind Harmer
0.017
962561AG1-105 GEN
Solar/Wind Harmer
10.919
964791AG1-342 GEN
Solar/Wind Harmer
4.339
3146843MT LREL
Solar/Wind Harmer
0.226
3146843MT LREL
Solar/Wind Harmer
0.226
3142946ENON
Solar/Wind Harmer
0.022
958211AF2-115 GEN
Solar/Wind Harmer
2.656
963191AG1-168 GEN
Solar/Wind Harmer
0.885
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.593
3147133PAMPLIN
Solar/Wind Harmer
0.219
3147133PAMPLIN
Solar/Wind Harmer
0.175
316075AC2-137 C
Solar/Wind Harmer
0.055
316222AC1-221 GEN
Solar/Wind Harmer
0.83
3150691DARBY 3
Adder
13.407
3150701DARBY 4
Adder
13.376
3150681DARBY 2
Adder
13.36
3150671DARBY 1
Adder
13.345
958261AF2-120 GEN
Solar/Wind Harmer
6.119
3142366NRTHEST
Adder
0.595
3146776BUCKING
Solar/Wind Harmer
0.717
3146776BUCKING
Solar/Wind Harmer
0.058
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.803
3150341NORNECKC1
Adder
1.788
942751AE2-291 GEN
Solar/Wind Harmer
8.42
971489AH1-241 GEN
Solar/Wind Harmer
7.048
3142296MT RD221
Adder
0.414
270013AE1-250 PV
Solar/Wind Harmer
0.004
966871AG1-558 GEN
Solar/Wind Harmer
0.141
316447AC1-158 HLD
Solar/Wind Helper
3.792
NYPJM->LTFIMP_NY
CLTF
2.749
LGEELTFEXP_LGEE->PJM
CLTF
1.702
LAGNLTFEXP_LAGN->PJM
CLTF
10.194
WECLTFEXP_WEC->PJM
CLTF
0.865
CBM South 2LTFEXP_CBM-S2->PJM
CBM
32.592
TVALTFEXP_TVA->PJM
CLTF
5.103
CPLELTFEXP_CPLE->PJM
CLTF
15.205
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.962
CBM West 1LTFEXP_CBM-W1->PJM
CBM
29.866
CBM South 1LTFEXP_CBM-S1->PJM
CBM
17.385
MECLTFEXP_MEC->PJM
CLTF
4.747
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.12 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5205.6
MW Contribution:17.44
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
44.697
315243AE2-183_GT3
50/50
5.046
3151051BRUNSWICKS1
50/50
8.24
3151021BRUNSWICKG1
50/50
3.97
971451AH1-221 GEN
50/50
12.059
3150981CHESPKA
50/50
3.724
3150851SPRUNCC
50/50
1.346
3152331SURRY 2
50/50
11.301
3143226MDLTHAN
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
33.588
939411AE1-173 GEN
Solar/Wind Harmer
173.894
3143526WINTERP
Solar/Wind Harmer
-0.178
970919AG2-571 GEN
Solar/Wind Harmer
10.315
970087AG2-069 GEN
Solar/Wind Harmer
30.424
316294AC1-161 GEN
Solar/Wind Harmer
10.357
944591AF1-124 GEN
Solar/Wind Harmer
145.255
316375AC2-012 GEN
Solar/Wind Harmer
10.929
316388AE2-253 GEN
Solar/Wind Harmer
2.123
3146456SLIGO L269
Solar/Wind Harmer
-0.031
316246AF1-032 C
Solar/Wind Harmer
0.634
970659AG2-427 GEN
Solar/Wind Harmer
16.575
316381AD1-082 GEN
Solar/Wind Harmer
2.861
970661AG2-428 GEN
Solar/Wind Harmer
33.139
316093AE2-104_GEN
Solar/Wind Harmer
9.058
316072AD1-144
Solar/Wind Harmer
0.627
3145336SMITFLD
Solar/Wind Harmer
-0.123
3146516WINFALL
Solar/Wind Harmer
-0.099
3146516WINFALL
Solar/Wind Harmer
-0.031
315800Z1-036_GEN1
Solar/Wind Harmer
7.529
957481AF2-042 GEN
Solar/Wind Harmer
95.029
3151171GRAVELC
Adder
2.875
3130156CHOWAN
Solar/Wind Harmer
-0.03
315671AE2-027_GEN
Solar/Wind Harmer
22.65
961611AG1-000B GEN
Solar/Wind Harmer
14.902
971647AH1-324 GEN
Solar/Wind Harmer
15.03
316023GEN1_S
Solar/Wind Harmer
2.014
3143336POWHATN
Solar/Wind Harmer
3.544
971069AG2-661 GEN
Solar/Wind Harmer
4.719
3145663CRESWEL
Solar/Wind Harmer
-0.083
971163AH1-040 GEN
Solar/Wind Harmer
27.837
316458AB2-190 GEN2
Solar/Wind Harmer
3.001
970129AG2-093 GEN
Solar/Wind Harmer
6.761
315693AD1-088 GEN
Solar/Wind Harmer
14.68
3138126ROCKLANDING
Solar/Wind Harmer
0.09
3142543TWELFTH
Solar/Wind Harmer
-0.003
962491AG1-098 GEN
Solar/Wind Harmer
19.518
960081AF2-299 GEN
Solar/Wind Harmer
3.271
3145893MURPHYS
Solar/Wind Harmer
-0.116
3145893MURPHYS
Solar/Wind Harmer
0.862
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.259
3146173TUNIS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
971317AH1-138 GEN
Solar/Wind Harmer
3.571
316011AB1-132 GEN
Solar/Wind Harmer
5.973
962571AG1-106 GEN
Solar/Wind Harmer
4.104
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
971795AH1-408 GEN
Solar/Wind Harmer
21.355
316190AA2-174 GEN
Solar/Wind Harmer
0.348
316159AE1-175 C
Solar/Wind Harmer
0.759
3147043LAWRENC
Adder
2.27
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.028
944631AF1-128 GEN
Adder
119.343
3145963POPLR C
Solar/Wind Harmer
-0.028
3145783HORNRTN
Solar/Wind Harmer
-0.028
316174AB2-169 GEN
Solar/Wind Harmer
4.307
316336AC2-165 C
Solar/Wind Harmer
4.835
316212AC1-099_GEN
Solar/Wind Harmer
2.388
315687AD1-152 GEN
Solar/Wind Harmer
3.298
316129AC1-054 GEN
Solar/Wind Harmer
2.39
971065AG2-659 GEN
Solar/Wind Harmer
13.588
3146293MARTNCO
Solar/Wind Harmer
0.168
315722AD1-056 GEN
Solar/Wind Harmer
2.807
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
316494AC1-189 GEN
Solar/Wind Harmer
2.84
3146233WITAKRS
Solar/Wind Harmer
-0.104
316237AB2-079_GEN
Solar/Wind Harmer
0.788
961671AG1-007 GEN
Solar/Wind Harmer
0.33
3146083TARBORO
Solar/Wind Harmer
-0.026
3145493TOT1
Solar/Wind Harmer
0.775
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.828
972277AH1-723 GEN
Adder
69.838
316045AC1-158 PL2
Solar/Wind Helper
8.788
3147666LOUISA
Solar/Wind Helper
1.717
316192AB2-158 GEN
Solar/Wind Helper
2.822
316254AC1-120 GEN1
Solar/Wind Helper
1.415
316006AB2-029 C
Solar/Wind Helper
0.131
316303AF2-085
50/50
5.96
315244AE2-183_ST
50/50
8.724
963041AG1-153 GEN
50/50
8.039
315779AE2-040
50/50
4.026
3151081ELIZAR1
50/50
27.372
3151091ELIZAR2
50/50
26.896
941591AE2-156 GEN
50/50
25.004
3152611GOSPORTB
50/50
3.798
3152621GOSPORTC
50/50
3.223
3152601GOSPORTA
50/50
2.973
971285AH1-108 GEN
50/50
2.203
972263AH1-716 GEN
50/50
156.512
941031AE2-094 GEN
Solar/Wind Harmer
66.256
944011AF1-069 GEN
Solar/Wind Harmer
20.76
970673AG2-436 GEN
Solar/Wind Harmer
72.821
970673AG2-436 GEN
Solar/Wind Harmer
36.871
316233AE1-074 FULL
Solar/Wind Harmer
0.927
971281AH1-106 GEN
Solar/Wind Harmer
5.6
971283AH1-107 GEN
Solar/Wind Harmer
5.6
971967AH1-528 GEN
Solar/Wind Harmer
64.075
970085AG2-068 GEN
Solar/Wind Harmer
20.283
970581AG2-369 GEN
Solar/Wind Harmer
17.443
316315AB2-025 C
Solar/Wind Harmer
0.874
315814AE2-033 C
Solar/Wind Harmer
30.059
3143316POE
Solar/Wind Harmer
-0.126
957871AF2-081 GEN
Solar/Wind Harmer
15.731
319010AE1-072 C
Solar/Wind Harmer
6.35
3146406KITTY HAWK
Solar/Wind Harmer
0.026
316305AF2-043 C
Solar/Wind Harmer
0.944
315833AF1-017_GEN
Solar/Wind Harmer
5.92
316349AD2-085 GEN
Solar/Wind Harmer
2.772
316311AC2-079 GEN
Solar/Wind Harmer
15.721
313526AB2-022
Solar/Wind Harmer
0.84
315835AF2-110_GEN
Solar/Wind Harmer
3.894
3146486SUNBURY
Solar/Wind Harmer
-0.031
3146486SUNBURY
Solar/Wind Harmer
-0.031
316321Z2-027
Solar/Wind Harmer
0.837
3146396TANGLEW
Solar/Wind Harmer
0.571
3145176PASQUOTANK
Solar/Wind Harmer
-0.019
971445AH1-216 GEN
Solar/Wind Harmer
19.056
315611Z1-036_GEN2
Solar/Wind Harmer
7.529
972265AH1-717 GEN
Adder
20.984
3151201GRAVEL4
Adder
19.671
3151191GRAVEL3
Adder
19.422
3151211GRAVEL5
Adder
19.422
3130156CHOWAN
Solar/Wind Harmer
-0.03
3130156CHOWAN
Solar/Wind Harmer
-0.03
316369SG1_INVT
Solar/Wind Harmer
5.347
315816AE2-034 GEN
Solar/Wind Harmer
2.403
316132AB2-190 GEN1
Solar/Wind Harmer
3.001
3130546PLYMOUTH
Solar/Wind Harmer
-0.029
965291AG1-394 GEN
Solar/Wind Harmer
2.597
315732AD1-074 GEN1
Solar/Wind Harmer
5.913
315733AD1-074 GEN2
Solar/Wind Harmer
5.913
315735AD1-075 GEN1
Solar/Wind Harmer
2.957
946281AF1-292 GEN
Solar/Wind Harmer
0.651
316318V4-068
Solar/Wind Harmer
0.724
3145893MURPHYS
Solar/Wind Harmer
-0.078
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.703
316087AB2-174 GEN
Solar/Wind Harmer
4.11
3146043SEABORD
Solar/Wind Harmer
-0.029
3145513AHOSKIE
Solar/Wind Harmer
0.25
961941AG1-037 GEN
Solar/Wind Harmer
0.216
3145513AHOSKIE
Solar/Wind Harmer
-0.029
315607AA1-063A GEN
Solar/Wind Harmer
2.895
3145683EARLEYS
Solar/Wind Harmer
-0.057
3145683EARLEYS
Solar/Wind Harmer
-0.029
3145683EARLEYS
Solar/Wind Harmer
-0.029
315652AC1-086 GEN
Solar/Wind Harmer
32.119
3137643SOCKMAN
Solar/Wind Harmer
-0.113
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.011
3146033SCOT NK
Solar/Wind Harmer
-0.11
957831AF2-077 GEN
Solar/Wind Harmer
0.824
3138283WHITEMARSH
Solar/Wind Harmer
0.042
970831AG2-522 GEN
Solar/Wind Harmer
13.68
316005AA1-067
Solar/Wind Harmer
0.541
3145746EVERETS
Solar/Wind Harmer
-0.106
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970181AG2-120 GEN
Solar/Wind Harmer
3.507
971167AH1-042 GEN
Solar/Wind Harmer
25.67
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
3151031BRUNSWICKG2
50/50
3.97
3151101ELIZAR3
50/50
27.722
3150861SPRUNCD
50/50
1.346
3151161SURRY 1
50/50
10.381
970917AG2-570 GEN
Solar/Wind Harmer
81.486
315773AC2-141 GEN
Solar/Wind Harmer
13.395
944581AF1-123 GEN
Solar/Wind Harmer
144.734
944601AF1-125 GEN
Solar/Wind Harmer
142.475
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.031
971153AH1-033 GEN
Solar/Wind Harmer
3.829
3144536CHRHLND
Solar/Wind Harmer
-0.005
315813AE1-149 C
Solar/Wind Harmer
19.509
970659AG2-427 GEN
Solar/Wind Harmer
2.937
316083AB2-161 GEN
Solar/Wind Harmer
5.063
970661AG2-428 GEN
Solar/Wind Harmer
5.873
316320Y1-086
Solar/Wind Harmer
1.826
316435W1029_GEN3
Solar/Wind Harmer
5.597
315839AE2-212 C
Solar/Wind Harmer
0.929
3145336SMITFLD
Solar/Wind Harmer
-0.012
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
3.804
3151221GRAVEL6
Adder
19.649
3151171GRAVELC
Adder
3.78
3146376EDENTON
Solar/Wind Harmer
-0.03
961611AG1-000B GEN
Solar/Wind Harmer
6.358
316365GEN2_N
Solar/Wind Harmer
2.014
316313AB2-026
Solar/Wind Harmer
0.805
316258AE1-075 C
Solar/Wind Harmer
0.725
316405AF2-144 C
Solar/Wind Harmer
0.765
3143336POWHATN
Solar/Wind Harmer
3.012
315778AD1-151 GEN
Solar/Wind Harmer
25.835
315614AA2-178 GEN
Solar/Wind Harmer
3.204
970129AG2-093 GEN
Solar/Wind Harmer
16.692
3144216WINCHST
Adder
0.987
970133AG2-095 GEN
Solar/Wind Harmer
3.307
3156081AA2-088 GEN
Solar/Wind Harmer
9.526
971157AH1-035 GEN
Solar/Wind Harmer
3.664
3150921YORKTN3
Adder
6.541
315737AD1-076 GEN
Solar/Wind Harmer
5.557
316478AD1-087 GEN
Solar/Wind Harmer
2.52
316486AD2-202 GEN
Solar/Wind Harmer
0.738
966621AG1-532 GEN
Solar/Wind Harmer
0.59
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146206CASHIE
Solar/Wind Harmer
-0.029
957521AF2-046 GEN
Solar/Wind Harmer
22.828
961681AG1-008 GEN
Solar/Wind Harmer
22.828
3146173TUNIS
Solar/Wind Harmer
-0.029
3156021HOLLOMANSOL
Solar/Wind Harmer
3.873
316463AE2-346 GEN
Solar/Wind Harmer
0.465
316140AB2-099
Solar/Wind Harmer
0.194
962331AG1-082 GEN
Solar/Wind Harmer
3.59
313506AB2-031 GEN
Solar/Wind Harmer
2.306
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3146263WOODLND
Solar/Wind Harmer
-0.028
3143096IRON208
Adder
1.062
3143096IRON208
Adder
1.041
316382AG1-145 C
Solar/Wind Harmer
0.853
3147043LAWRENC
Solar/Wind Harmer
-0.017
316317KELFORD C
Solar/Wind Harmer
1.328
3145823KELFORD
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.112
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145963POPLR C
Solar/Wind Harmer
-0.028
3142946ENON
Solar/Wind Harmer
-0.009
316210AC1-098 GEN
Solar/Wind Harmer
4.299
3145933PARMELE
Solar/Wind Harmer
-0.027
966801AG1-551 GEN
Solar/Wind Harmer
3.395
315724AD1-057 GEN
Solar/Wind Harmer
1.544
3145746EVERETS
Solar/Wind Harmer
-0.027
3145746EVERETS
Solar/Wind Harmer
-0.027
970293AG2-193 GEN
Solar/Wind Harmer
3.331
316327AA2-057 GEN
Solar/Wind Harmer
2.686
3142433PROV 92
Adder
0.458
3142433PROV 92
Adder
0.458
3146233WITAKRS
Solar/Wind Harmer
0.548
3146233WITAKRS
Solar/Wind Harmer
-0.018
3138543CONSLDL
Solar/Wind Harmer
-0.017
316131AB2-060 GEN
Solar/Wind Harmer
2.82
3146073TAR RVR
Solar/Wind Harmer
-0.026
3146083TARBORO
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.466
3141843SHACKLE
Adder
1.162
3144293JTRSVLE
Adder
0.705
3150351NORNECKC2
Adder
1.858
972255AH1-712 GEN
Adder
59.932
316044AC1-158 PL1
Solar/Wind Helper
2.745
316450AC1-158 RIC
Solar/Wind Helper
0.732
3147666LOUISA
Solar/Wind Helper
0.987
316170AC1-121 GEN2
Solar/Wind Helper
0.472
3132273ORANGE
Solar/Wind Helper
0.057
3141196NOKESVL
Solar/Wind Helper
0.931
964241AG1-285 GEN
Solar/Wind Harmer
19.851
315976AC1-164 GENA
Solar/Wind Harmer
27.981
316169AC1-164_GENC
Solar/Wind Harmer
24.173
315975AC1-164 GENB
Solar/Wind Harmer
0.828
957861AF2-080 GEN
Solar/Wind Harmer
11.55
316420AA1-050 GEN
Solar/Wind Harmer
2.998
316319Z2-044 C
Solar/Wind Harmer
1.447
316239AB2-077_GEN
Solar/Wind Harmer
0.788
316238AB2-078_GEN
Solar/Wind Harmer
0.788
3145573BETHELC
Solar/Wind Harmer
-0.026
3145573BETHELC
Solar/Wind Harmer
-0.026
972205AH1-687 GEN
Adder
6.895
972189AH1-679 GEN
Adder
2.574
972193AH1-681 GEN
Adder
2.678
316164AC1-076 GEN
Solar/Wind Helper
1.627
970533AG2-339 GEN
50/50
27.956
970531AG2-338 GEN
50/50
11.182
315242AE2-183_GT2
50/50
5.046
315241AE2-183_GT1
50/50
5.015
972185AH1-677 GEN
50/50
18.191
3151041BRUNSWICKG3
50/50
3.97
972187AH1-678 GEN
50/50
9.111
3150991CHESPKB
50/50
3.124
3150991CHESPKB
50/50
3.049
971223AH1-071 GEN
Solar/Wind Harmer
4.708
3143526WINTERP
Solar/Wind Harmer
-0.178
970933AG2-581 GEN
Solar/Wind Harmer
30.984
3144356SAPONY
Solar/Wind Harmer
1.13
316185AD1-033 GEN
Solar/Wind Harmer
3.336
3142956BIRDNECK
Solar/Wind Harmer
1.696
316316AC1-027 C
Solar/Wind Harmer
0.97
316036AC1-147 C
Solar/Wind Harmer
0.852
3145506HICKORY
Solar/Wind Harmer
-0.126
3145506HICKORY
Solar/Wind Harmer
-0.075
3145506HICKORY
Solar/Wind Harmer
-0.019
316339AD2-160 GEN
Solar/Wind Harmer
2.123
316018AA1-139 ULT2
Solar/Wind Harmer
2.695
316017AA1-139 ULT1
Solar/Wind Harmer
2.546
3137176SLIGO L2192
Solar/Wind Harmer
-0.124
3146456SLIGO L269
Solar/Wind Harmer
3.71
3130086AYDLETT
Solar/Wind Harmer
-0.125
970657AG2-426 GEN
Solar/Wind Harmer
9.748
970657AG2-426 GEN
Solar/Wind Harmer
2.039
3146386ELIZ CT
Solar/Wind Harmer
-0.031
316431W1029_GEN1
Solar/Wind Harmer
5.597
316433W1029_GEN2
Solar/Wind Harmer
5.597
316236AE1-162_GEN
Solar/Wind Harmer
0.929
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
3146626S HERTFORD
Solar/Wind Harmer
-0.031
970099AG2-077 GEN
Solar/Wind Harmer
38.011
315742AE1-103 GEN
Solar/Wind Harmer
3.171
3146376EDENTON
Solar/Wind Harmer
0.896
3146376EDENTON
Solar/Wind Harmer
0.896
316240AF1-291 C
Solar/Wind Harmer
0.906
316033AB2-134 GEN
Solar/Wind Harmer
9.651
315697AD1-025 GEN
Solar/Wind Harmer
6.053
944641AF1-129 GEN
Adder
126.539
316065AD1-022 GEN
Solar/Wind Harmer
14.554
3145893MURPHYS
Solar/Wind Harmer
0.81
3145893MURPHYS
Solar/Wind Harmer
-0.052
3146173TUNIS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.029
316181AB2-040 GEN
Solar/Wind Harmer
4.002
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.028
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
316426AA2-053 GEN
Solar/Wind Harmer
2.861
3145593CAROLNA
Solar/Wind Harmer
-0.028
3145593CAROLNA
Solar/Wind Harmer
-0.028
966811AG1-552 GEN
Solar/Wind Harmer
3.179
3145593CAROLNA
Solar/Wind Harmer
0.235
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145783HORNRTN
Solar/Wind Harmer
3.335
3145783HORNRTN
Solar/Wind Harmer
2.668
3145783HORNRTN
Solar/Wind Harmer
0.834
3145783HORNRTN
Solar/Wind Harmer
0.334
3142946ENON
Solar/Wind Harmer
-0.003
316274AC1-208 GEN
Solar/Wind Harmer
2.942
3145933PARMELE
Solar/Wind Harmer
-0.054
3145933PARMELE
Solar/Wind Harmer
-0.027
3142366NRTHEST
Adder
0.786
3150691DARBY 3
Adder
17.226
3150701DARBY 4
Adder
17.185
3150681DARBY 2
Adder
17.165
3150671DARBY 1
Adder
17.145
971741AH1-377 GEN
Solar/Wind Harmer
31.097
939181AE1-148 GEN
Solar/Wind Harmer
14.98
316075AC2-137 C
Solar/Wind Harmer
0.711
313527AB2-043 GEN
Solar/Wind Harmer
4.254
3145493TOT1
Solar/Wind Harmer
0.404
3145453TOT5
Solar/Wind Harmer
0.242
3145603CNETO
Solar/Wind Harmer
0.162
970301AG2-198 GEN
Solar/Wind Harmer
12.986
3144293JTRSVLE
Adder
0.705
3144293JTRSVLE
Adder
0.594
3142296MT RD221
Adder
0.704
3150341NORNECKC1
Adder
1.92
3150341NORNECKC1
Adder
1.904
316447AC1-158 HLD
Solar/Wind Helper
6.042
315651AD1-115 GEN
Solar/Wind Helper
1.014
966001AG1-469 GEN
Solar/Wind Helper
0.285
NYPJM->LTFIMP_NY
CLTF
3.09
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
LGEELTFEXP_LGEE->PJM
CLTF
2.105
WECLTFEXP_WEC->PJM
CLTF
1.07
CBM South 2LTFEXP_CBM-S2->PJM
CBM
33.419
TVALTFEXP_TVA->PJM
CLTF
5.67
CPLELTFEXP_CPLE->PJM
CLTF
15.222
CBM West 2LTFEXP_CBM-W2->PJM
CBM
60.286
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.367
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.53
MECLTFEXP_MEC->PJM
CLTF
5.657
SIGELTFEXP_SIGE->PJM
CLTF
0.172

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P4-1: G202_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-1: G202_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.07 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4086.88
MW Contribution:15.63
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.525
315243AE2-183_GT3
50/50
4.543
3151051BRUNSWICKS1
50/50
7.411
3151021BRUNSWICKG1
50/50
3.571
971451AH1-221 GEN
50/50
10.845
316303AF2-085
50/50
5.403
315244AE2-183_ST
50/50
7.855
963041AG1-153 GEN
50/50
7.23
315779AE2-040
50/50
3.41
3151541CLOVER2
50/50
4.892
941031AE2-094 GEN
Solar/Wind Harmer
59.803
944011AF1-069 GEN
Solar/Wind Harmer
18.738
970673AG2-436 GEN
Solar/Wind Harmer
65.622
970673AG2-436 GEN
Solar/Wind Harmer
33.227
971967AH1-528 GEN
Solar/Wind Harmer
57.655
970085AG2-068 GEN
Solar/Wind Harmer
18.173
970581AG2-369 GEN
Solar/Wind Harmer
15.629
316233AE1-074 FULL
Solar/Wind Harmer
0.781
971281AH1-106 GEN
Solar/Wind Harmer
4.721
971283AH1-107 GEN
Solar/Wind Harmer
4.721
316315AB2-025 C
Solar/Wind Harmer
0.74
315814AE2-033 C
Solar/Wind Harmer
25.448
3143316POE
Solar/Wind Harmer
-0.102
3151081ELIZAR1
Adder
20.247
3151091ELIZAR2
Adder
19.895
957871AF2-081 GEN
Solar/Wind Harmer
12.412
319010AE1-072 C
Solar/Wind Harmer
5.013
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.808
3152621GOSPORTC
Adder
2.383
3152601GOSPORTA
Adder
2.198
316305AF2-043 C
Solar/Wind Harmer
0.745
313526AB2-022
Solar/Wind Harmer
0.665
315835AF2-110_GEN
Solar/Wind Harmer
3.079
316321Z2-027
Solar/Wind Harmer
0.663
3146396TANGLEW
Solar/Wind Harmer
0.452
970533AG2-339 GEN
50/50
25.233
970531AG2-338 GEN
50/50
10.093
315242AE2-183_GT2
50/50
4.543
315241AE2-183_GT1
50/50
4.515
972185AH1-677 GEN
50/50
16.379
3151041BRUNSWICKG3
50/50
3.571
972187AH1-678 GEN
50/50
8.194
971223AH1-071 GEN
Solar/Wind Harmer
4.269
970933AG2-581 GEN
Solar/Wind Harmer
27.802
3143526WINTERP
Solar/Wind Harmer
-0.15
3144356SAPONY
Solar/Wind Harmer
0.957
970099AG2-077 GEN
Solar/Wind Harmer
33.834
316185AD1-033 GEN
Solar/Wind Harmer
2.627
3145506HICKORY
Solar/Wind Harmer
-0.099
3145506HICKORY
Solar/Wind Harmer
-0.059
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.333
316316AC1-027 C
Solar/Wind Harmer
0.762
316339AD2-160 GEN
Solar/Wind Harmer
1.675
3151031BRUNSWICKG2
50/50
3.571
970413AG2-270 GEN
50/50
21.45
3151101ELIZAR3
50/50
21.759
970917AG2-570 GEN
Solar/Wind Harmer
73.039
316313AB2-026
Solar/Wind Harmer
0.72
316258AE1-075 C
Solar/Wind Harmer
0.648
316405AF2-144 C
Solar/Wind Harmer
0.684
3143336POWHATN
Solar/Wind Harmer
2.693
316478AD1-087 GEN
Solar/Wind Harmer
2.233
316486AD2-202 GEN
Solar/Wind Harmer
0.654
316365GEN2_N
Solar/Wind Harmer
1.694
944581AF1-123 GEN
Solar/Wind Harmer
114.149
944601AF1-125 GEN
Solar/Wind Harmer
112.367
315773AC2-141 GEN
Solar/Wind Harmer
10.461
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.022
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.445
970661AG2-428 GEN
Solar/Wind Harmer
4.62
966621AG1-532 GEN
Solar/Wind Harmer
0.498
316435W1029_GEN3
Solar/Wind Harmer
4.441
316083AB2-161 GEN
Solar/Wind Harmer
3.979
970659AG2-427 GEN
Solar/Wind Harmer
2.307
3146516WINFALL
Solar/Wind Harmer
-0.024
315813AE1-149 C
Solar/Wind Harmer
15.291
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.938
3156081AA2-088 GEN
Solar/Wind Harmer
7.776
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.579
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.166
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.716
957521AF2-046 GEN
Solar/Wind Harmer
18.692
961681AG1-008 GEN
Solar/Wind Harmer
18.692
971157AH1-035 GEN
Solar/Wind Harmer
2.963
315737AD1-076 GEN
Solar/Wind Harmer
4.498
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.381
316140AB2-099
Solar/Wind Harmer
0.159
962331AG1-082 GEN
Solar/Wind Harmer
2.944
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150861SPRUNCD
Adder
0.964
3156021HOLLOMANSOL
Solar/Wind Harmer
3.164
316317KELFORD C
Solar/Wind Harmer
1.095
3145823KELFORD
Solar/Wind Harmer
-0.023
316018AA1-139 ULT2
Solar/Wind Harmer
2.126
316017AA1-139 ULT1
Solar/Wind Harmer
2.009
3137176SLIGO L2192
Solar/Wind Harmer
-0.098
3146456SLIGO L269
Solar/Wind Harmer
2.928
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.668
3150991CHESPKB
Adder
2.309
3150991CHESPKB
Adder
2.254
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.663
970657AG2-426 GEN
Solar/Wind Harmer
1.602
316431W1029_GEN1
Solar/Wind Harmer
4.441
316433W1029_GEN2
Solar/Wind Harmer
4.441
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.543
3146376EDENTON
Solar/Wind Harmer
0.717
3146376EDENTON
Solar/Wind Harmer
0.717
316181AB2-040 GEN
Solar/Wind Harmer
3.363
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.663
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.661
3145593CAROLNA
Solar/Wind Harmer
0.196
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316426AA2-053 GEN
Solar/Wind Harmer
2.386
316065AD1-022 GEN
Solar/Wind Harmer
11.81
316236AE1-162_GEN
Solar/Wind Harmer
0.711
971741AH1-377 GEN
Solar/Wind Harmer
27.409
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145783HORNRTN
Solar/Wind Harmer
2.79
3145783HORNRTN
Solar/Wind Harmer
2.232
3145783HORNRTN
Solar/Wind Harmer
0.698
3145783HORNRTN
Solar/Wind Harmer
0.279
939181AE1-148 GEN
Solar/Wind Harmer
12.946
970301AG2-198 GEN
Solar/Wind Harmer
11.421
316274AC1-208 GEN
Solar/Wind Harmer
2.458
313527AB2-043 GEN
Solar/Wind Harmer
3.682
316240AF1-291 C
Solar/Wind Harmer
0.675
3145933PARMELE
Solar/Wind Harmer
-0.044
3145933PARMELE
Solar/Wind Harmer
-0.022
970323AG2-213 GEN
Solar/Wind Harmer
11.053
971775AH1-396 GEN
Solar/Wind Harmer
1.574
316034AC1-036 C
Solar/Wind Harmer
0.41
316033AB2-134 GEN
Solar/Wind Harmer
7.127
315697AD1-025 GEN
Solar/Wind Harmer
4.47
944641AF1-129 GEN
Adder
93.238
962561AG1-105 GEN
Solar/Wind Harmer
12.325
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3142366NRTHEST
Adder
0.501
3150691DARBY 3
Adder
10.867
3150701DARBY 4
Adder
10.841
3150681DARBY 2
Adder
10.829
3150671DARBY 1
Adder
10.816
3142296MT RD221
Adder
0.386
3150341NORNECKC1
Adder
1.198
3150341NORNECKC1
Adder
1.188
316447AC1-158 HLD
Solar/Wind Helper
3.615
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.402
315833AF1-017_GEN
Solar/Wind Harmer
4.67
316349AD2-085 GEN
Solar/Wind Harmer
2.187
946281AF1-292 GEN
Solar/Wind Harmer
0.549
315611Z1-036_GEN2
Solar/Wind Harmer
6.004
316087AB2-174 GEN
Solar/Wind Harmer
3.457
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.123
315816AE2-034 GEN
Solar/Wind Harmer
1.934
315652AC1-086 GEN
Solar/Wind Harmer
26.851
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.593
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.4
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.786
315733AD1-074 GEN2
Solar/Wind Harmer
4.786
315735AD1-075 GEN1
Solar/Wind Harmer
2.394
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.322
3145513AHOSKIE
Solar/Wind Harmer
0.205
961941AG1-037 GEN
Solar/Wind Harmer
0.177
3145513AHOSKIE
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.578
971445AH1-216 GEN
Solar/Wind Harmer
14.547
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
970831AG2-522 GEN
Solar/Wind Harmer
11.661
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.775
3151201GRAVEL4
Adder
14.788
3151191GRAVEL3
Adder
14.601
3151211GRAVEL5
Adder
14.601
316239AB2-077_GEN
Solar/Wind Harmer
0.682
316238AB2-078_GEN
Solar/Wind Harmer
0.682
971443AH1-215 GEN
Solar/Wind Harmer
4.356
316005AA1-067
Solar/Wind Harmer
0.448
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.904
3144303KENBRDG
Solar/Wind Harmer
-0.018
316369SG1_INVT
Solar/Wind Harmer
3.949
957861AF2-080 GEN
Solar/Wind Harmer
9.609
316319Z2-044 C
Solar/Wind Harmer
1.213
316420AA1-050 GEN
Solar/Wind Harmer
2.5
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
972205AH1-687 GEN
Adder
5.892
970683AG2-441 GEN
Solar/Wind Harmer
7.481
970681AG2-440 GEN
Solar/Wind Harmer
5.985
965281AG1-393 GEN
Solar/Wind Harmer
2.888
3145963POPLR C
Solar/Wind Harmer
-0.023
970909AG2-566 GEN
Solar/Wind Harmer
2.169
3151221GRAVEL6
Adder
14.771
3151171GRAVELC
Adder
2.842
316210AC1-098 GEN
Solar/Wind Harmer
3.58
316131AB2-060 GEN
Solar/Wind Harmer
2.441
961611AG1-000B GEN
Solar/Wind Harmer
4.747
315724AD1-057 GEN
Solar/Wind Harmer
1.295
964241AG1-285 GEN
Solar/Wind Harmer
17.552
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.798
316327AA2-057 GEN
Solar/Wind Harmer
2.249
315785AD2-033 C
Solar/Wind Harmer
5.032
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.289
959311AF2-222 GEN
Solar/Wind Harmer
22.999
3146233WITAKRS
Solar/Wind Harmer
0.46
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.014
315778AD1-151 GEN
Solar/Wind Harmer
18.993
3144293JTRSVLE
Adder
0.613
3144216WINCHST
Adder
0.711
3150921YORKTN3
Adder
4.681
3143096IRON208
Adder
0.73
3143096IRON208
Adder
0.715
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.16
316044AC1-158 PL1
Solar/Wind Helper
1.642
316450AC1-158 RIC
Solar/Wind Helper
0.438
3147666LOUISA
Solar/Wind Helper
0.519
3151531CLOVER1
50/50
4.915
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.721
939411AE1-173 GEN
Solar/Wind Harmer
150.037
970919AG2-571 GEN
Solar/Wind Harmer
9.245
970087AG2-069 GEN
Solar/Wind Harmer
27.26
3143526WINTERP
Solar/Wind Harmer
-0.15
957481AF2-042 GEN
Solar/Wind Harmer
84.586
3143336POWHATN
Solar/Wind Harmer
3.168
315693AD1-088 GEN
Solar/Wind Harmer
13.025
962491AG1-098 GEN
Solar/Wind Harmer
17.31
316023GEN1_S
Solar/Wind Harmer
1.694
944591AF1-124 GEN
Solar/Wind Harmer
114.56
316294AC1-161 GEN
Solar/Wind Harmer
8.089
316388AE2-253 GEN
Solar/Wind Harmer
1.675
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.572
3150981CHESPKA
Adder
2.753
316336AC2-165 C
Solar/Wind Harmer
4.3
316246AF1-032 C
Solar/Wind Harmer
0.5
316093AE2-104_GEN
Solar/Wind Harmer
7.163
970661AG2-428 GEN
Solar/Wind Harmer
26.068
960081AF2-299 GEN
Solar/Wind Harmer
2.759
316381AD1-082 GEN
Solar/Wind Harmer
2.248
970659AG2-427 GEN
Solar/Wind Harmer
13.019
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.024
315800Z1-036_GEN1
Solar/Wind Harmer
6.004
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.101
316072AD1-144
Solar/Wind Harmer
0.488
315687AD1-152 GEN
Solar/Wind Harmer
2.903
3147043LAWRENC
Adder
1.929
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.406
316011AB1-132 GEN
Solar/Wind Harmer
4.994
962571AG1-106 GEN
Solar/Wind Harmer
3.431
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.706
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.29
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.898
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
3150851SPRUNCC
Adder
0.964
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
316129AC1-054 GEN
Solar/Wind Harmer
2.042
971065AG2-659 GEN
Solar/Wind Harmer
11.627
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.526
3151171GRAVELC
Adder
2.161
316212AC1-099_GEN
Solar/Wind Harmer
1.989
315671AE2-027_GEN
Solar/Wind Harmer
17.038
316237AB2-079_GEN
Solar/Wind Harmer
0.682
961611AG1-000B GEN
Solar/Wind Harmer
11.126
315722AD1-056 GEN
Solar/Wind Harmer
2.354
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.16
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.363
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.469
970685AG2-442 GEN
Solar/Wind Harmer
19.125
3144293JTRSVLE
Adder
0.613
3143096IRON208
Adder
0.73
944631AF1-128 GEN
Adder
80.725
3142433PROV 92
Adder
0.303
3142433PROV 92
Adder
0.303
3141843SHACKLE
Adder
0.759
3150351NORNECKC2
Adder
1.14
316045AC1-158 PL2
Solar/Wind Helper
5.258
3147666LOUISA
Solar/Wind Helper
0.902
NYPJM->LTFIMP_NY
CLTF
2.444
LAGNLTFEXP_LAGN->PJM
CLTF
8.918
LGEELTFEXP_LGEE->PJM
CLTF
1.534
WECLTFEXP_WEC->PJM
CLTF
0.779
CBM South 2LTFEXP_CBM-S2->PJM
CBM
27.956
TVALTFEXP_TVA->PJM
CLTF
4.471
CPLELTFEXP_CPLE->PJM
CLTF
12.94
CBM West 2LTFEXP_CBM-W2->PJM
CBM
46.681
CBM West 1LTFEXP_CBM-W1->PJM
CBM
26.974
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.275
MECLTFEXP_MEC->PJM
CLTF
4.234
SIGELTFEXP_SIGE->PJM
CLTF
0.127

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:15.7
Bus #Bus NameTypeMW Contribution
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
NYPJM->LTFIMP_NY
CLTF
2.393
LGEELTFEXP_LGEE->PJM
CLTF
1.582
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
WECLTFEXP_WEC->PJM
CLTF
0.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3957.44
MW Contribution:15.7
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
60.059
944011AF1-069 GEN
Solar/Wind Harmer
18.818
970673AG2-436 GEN
Solar/Wind Harmer
65.906
970673AG2-436 GEN
Solar/Wind Harmer
33.37
971967AH1-528 GEN
Solar/Wind Harmer
57.904
970085AG2-068 GEN
Solar/Wind Harmer
18.255
970581AG2-369 GEN
Solar/Wind Harmer
15.699
316233AE1-074 FULL
Solar/Wind Harmer
0.785
971281AH1-106 GEN
Solar/Wind Harmer
4.743
971283AH1-107 GEN
Solar/Wind Harmer
4.743
316315AB2-025 C
Solar/Wind Harmer
0.744
315814AE2-033 C
Solar/Wind Harmer
25.573
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.48
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
73.368
316313AB2-026
Solar/Wind Harmer
0.722
316258AE1-075 C
Solar/Wind Harmer
0.65
316405AF2-144 C
Solar/Wind Harmer
0.686
3143336POWHATN
Solar/Wind Harmer
2.702
316478AD1-087 GEN
Solar/Wind Harmer
2.243
316486AD2-202 GEN
Solar/Wind Harmer
0.657
316365GEN2_N
Solar/Wind Harmer
1.702
944581AF1-123 GEN
Solar/Wind Harmer
114.775
944601AF1-125 GEN
Solar/Wind Harmer
112.984
315773AC2-141 GEN
Solar/Wind Harmer
10.519
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.039
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316320Y1-086
Solar/Wind Harmer
1.453
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
4.466
316083AB2-161 GEN
Solar/Wind Harmer
4.001
966621AG1-532 GEN
Solar/Wind Harmer
0.5
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
-0.025
315813AE1-149 C
Solar/Wind Harmer
15.377
3144536CHRHLND
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.018
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146376EDENTON
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.948
3156081AA2-088 GEN
Solar/Wind Harmer
7.818
3147043LAWRENC
Solar/Wind Harmer
-0.014
315614AA2-178 GEN
Solar/Wind Harmer
2.593
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.167
3145893MURPHYS
Solar/Wind Harmer
-0.024
315839AE2-212 C
Solar/Wind Harmer
0.72
957521AF2-046 GEN
Solar/Wind Harmer
18.794
961681AG1-008 GEN
Solar/Wind Harmer
18.794
971157AH1-035 GEN
Solar/Wind Harmer
2.979
315737AD1-076 GEN
Solar/Wind Harmer
4.523
3146173TUNIS
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.009
316463AE2-346 GEN
Solar/Wind Harmer
0.383
316140AB2-099
Solar/Wind Harmer
0.16
962331AG1-082 GEN
Solar/Wind Harmer
2.96
3145796HORNRTN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.182
316317KELFORD C
Solar/Wind Harmer
1.101
3145823KELFORD
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.906
3145963POPLR C
Solar/Wind Harmer
-0.023
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
3.599
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
2.453
961611AG1-000B GEN
Solar/Wind Harmer
4.776
315724AD1-057 GEN
Solar/Wind Harmer
1.302
964241AG1-285 GEN
Solar/Wind Harmer
17.632
3145933PARMELE
Solar/Wind Harmer
-0.022
966801AG1-551 GEN
Solar/Wind Harmer
2.814
316327AA2-057 GEN
Solar/Wind Harmer
2.261
315785AD2-033 C
Solar/Wind Harmer
5.054
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970257AG2-171 GEN
Solar/Wind Harmer
8.325
959311AF2-222 GEN
Solar/Wind Harmer
23.096
3146233WITAKRS
Solar/Wind Harmer
0.462
3146233WITAKRS
Solar/Wind Harmer
-0.015
315778AD1-151 GEN
Solar/Wind Harmer
19.113
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
5.041
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.749
313526AB2-022
Solar/Wind Harmer
0.669
315835AF2-110_GEN
Solar/Wind Harmer
3.096
316321Z2-027
Solar/Wind Harmer
0.667
3146396TANGLEW
Solar/Wind Harmer
0.455
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
316311AC2-079 GEN
Solar/Wind Harmer
12.471
315833AF1-017_GEN
Solar/Wind Harmer
4.696
316349AD2-085 GEN
Solar/Wind Harmer
2.199
946281AF1-292 GEN
Solar/Wind Harmer
0.552
315611Z1-036_GEN2
Solar/Wind Harmer
6.037
316087AB2-174 GEN
Solar/Wind Harmer
3.475
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
965291AG1-394 GEN
Solar/Wind Harmer
2.135
315816AE2-034 GEN
Solar/Wind Harmer
1.945
315652AC1-086 GEN
Solar/Wind Harmer
26.995
3137643SOCKMAN
Solar/Wind Harmer
-0.095
316318V4-068
Solar/Wind Harmer
0.596
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.413
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.813
315733AD1-074 GEN2
Solar/Wind Harmer
4.813
315735AD1-075 GEN1
Solar/Wind Harmer
2.407
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.379
3145513AHOSKIE
Solar/Wind Harmer
0.206
961941AG1-037 GEN
Solar/Wind Harmer
0.178
3145513AHOSKIE
Solar/Wind Harmer
-0.024
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
4.285
970933AG2-581 GEN
Solar/Wind Harmer
27.922
3143526WINTERP
Solar/Wind Harmer
-0.151
3144356SAPONY
Solar/Wind Harmer
0.962
970099AG2-077 GEN
Solar/Wind Harmer
33.984
316185AD1-033 GEN
Solar/Wind Harmer
2.641
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.34
316316AC1-027 C
Solar/Wind Harmer
0.766
316339AD2-160 GEN
Solar/Wind Harmer
1.684
316018AA1-139 ULT2
Solar/Wind Harmer
2.138
316017AA1-139 ULT1
Solar/Wind Harmer
2.02
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.944
316036AC1-147 C
Solar/Wind Harmer
0.672
3130086AYDLETT
Solar/Wind Harmer
-0.099
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
-0.025
970657AG2-426 GEN
Solar/Wind Harmer
7.706
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
4.466
316433W1029_GEN2
Solar/Wind Harmer
4.466
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.024
3146626S HERTFORD
Solar/Wind Harmer
-0.024
315742AE1-103 GEN
Solar/Wind Harmer
2.557
3146376EDENTON
Solar/Wind Harmer
0.721
3146376EDENTON
Solar/Wind Harmer
0.721
316181AB2-040 GEN
Solar/Wind Harmer
3.381
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.667
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.675
3145593CAROLNA
Solar/Wind Harmer
0.198
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316065AD1-022 GEN
Solar/Wind Harmer
11.875
316426AA2-053 GEN
Solar/Wind Harmer
2.399
316236AE1-162_GEN
Solar/Wind Harmer
0.715
3145796HORNRTN
Solar/Wind Harmer
-0.071
971741AH1-377 GEN
Solar/Wind Harmer
27.515
3145783HORNRTN
Solar/Wind Harmer
2.805
3145783HORNRTN
Solar/Wind Harmer
2.244
3145783HORNRTN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
0.281
939181AE1-148 GEN
Solar/Wind Harmer
13.009
970301AG2-198 GEN
Solar/Wind Harmer
11.463
316274AC1-208 GEN
Solar/Wind Harmer
2.472
313527AB2-043 GEN
Solar/Wind Harmer
3.699
316240AF1-291 C
Solar/Wind Harmer
0.679
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.022
316033AB2-134 GEN
Solar/Wind Harmer
7.172
315697AD1-025 GEN
Solar/Wind Harmer
4.498
970323AG2-213 GEN
Solar/Wind Harmer
11.1
971775AH1-396 GEN
Solar/Wind Harmer
1.581
316034AC1-036 C
Solar/Wind Harmer
0.412
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
12.386
3145493TOT1
Solar/Wind Harmer
0.34
3145453TOT5
Solar/Wind Harmer
0.204
3145603CNETO
Solar/Wind Harmer
0.136
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
3142296MT RD221
Adder
0.39
3150341NORNECKC1
Adder
1.211
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.852
939411AE1-173 GEN
Solar/Wind Harmer
150.731
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
27.383
3143526WINTERP
Solar/Wind Harmer
-0.151
957481AF2-042 GEN
Solar/Wind Harmer
84.959
3143336POWHATN
Solar/Wind Harmer
3.179
315693AD1-088 GEN
Solar/Wind Harmer
13.081
962491AG1-098 GEN
Solar/Wind Harmer
17.384
316023GEN1_S
Solar/Wind Harmer
1.702
944591AF1-124 GEN
Solar/Wind Harmer
115.189
316294AC1-161 GEN
Solar/Wind Harmer
8.133
316388AE2-253 GEN
Solar/Wind Harmer
1.684
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.62
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.503
316336AC2-165 C
Solar/Wind Harmer
4.313
316093AE2-104_GEN
Solar/Wind Harmer
7.202
970661AG2-428 GEN
Solar/Wind Harmer
26.214
316381AD1-082 GEN
Solar/Wind Harmer
2.261
960081AF2-299 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
13.092
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
315800Z1-036_GEN1
Solar/Wind Harmer
6.037
3130156CHOWAN
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
18.192
316072AD1-144
Solar/Wind Harmer
0.491
315687AD1-152 GEN
Solar/Wind Harmer
2.916
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.53
316011AB1-132 GEN
Solar/Wind Harmer
5.02
962571AG1-106 GEN
Solar/Wind Harmer
3.449
3145893MURPHYS
Solar/Wind Harmer
-0.095
3145893MURPHYS
Solar/Wind Harmer
0.709
3146173TUNIS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.292
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.931
3145336SMITFLD
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.052
971065AG2-659 GEN
Solar/Wind Harmer
11.686
3145823KELFORD
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.546
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
2
315671AE2-027_GEN
Solar/Wind Harmer
17.142
316237AB2-079_GEN
Solar/Wind Harmer
0.685
961611AG1-000B GEN
Solar/Wind Harmer
11.194
315722AD1-056 GEN
Solar/Wind Harmer
2.367
3146293MARTNCO
Solar/Wind Harmer
0.139
971647AH1-324 GEN
Solar/Wind Harmer
11.229
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
316494AC1-189 GEN
Solar/Wind Harmer
2.377
3146233WITAKRS
Solar/Wind Harmer
-0.087
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.278
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.651
970685AG2-442 GEN
Solar/Wind Harmer
19.204
3144293JTRSVLE
Adder
0.615
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.311
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.632
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.72
3146033SCOT NK
Solar/Wind Harmer
-0.092
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.685
316238AB2-078_GEN
Solar/Wind Harmer
0.685
316005AA1-067
Solar/Wind Harmer
0.45
3145746EVERETS
Solar/Wind Harmer
-0.088
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
3145746EVERETS
Solar/Wind Harmer
-0.022
970181AG2-120 GEN
Solar/Wind Harmer
2.92
316369SG1_INVT
Solar/Wind Harmer
3.973
971443AH1-215 GEN
Solar/Wind Harmer
4.375
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.664
316319Z2-044 C
Solar/Wind Harmer
1.22
316420AA1-050 GEN
Solar/Wind Harmer
2.514
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
972205AH1-687 GEN
Adder
5.897
970683AG2-441 GEN
Solar/Wind Harmer
6.68
970681AG2-440 GEN
Solar/Wind Harmer
5.344
3138543CONSLDL
Solar/Wind Harmer
-0.014
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
3144293JTRSVLE
Adder
0.615
3144216WINCHST
Adder
0.716
3150921YORKTN3
Adder
4.712
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.172
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
3141843SHACKLE
Adder
0.766
3150351NORNECKC2
Adder
1.153
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
3150341NORNECKC1
Adder
1.201
316447AC1-158 HLD
Solar/Wind Helper
3.579
NYPJM->LTFIMP_NY
CLTF
2.393
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.34 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3619.13
MW Contribution:11.92
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.341
970531AG2-338 GEN
50/50
10.136
315242AE2-183_GT2
50/50
4.563
315241AE2-183_GT1
50/50
4.535
972185AH1-677 GEN
50/50
16.45
3151041BRUNSWICKG3
50/50
3.586
972187AH1-678 GEN
50/50
8.23
971223AH1-071 GEN
Solar/Wind Harmer
3.255
970933AG2-581 GEN
Solar/Wind Harmer
21.207
3143526WINTERP
Solar/Wind Harmer
1.35
3144356SAPONY
Solar/Wind Harmer
2.053
970099AG2-077 GEN
Solar/Wind Harmer
25.81
316185AD1-033 GEN
Solar/Wind Harmer
0.006
3145506HICKORY
Solar/Wind Harmer
0.89
3145506HICKORY
Solar/Wind Harmer
0.534
970119AG2-088 GEN
50/50
40.684
315243AE2-183_GT3
50/50
4.563
3151051BRUNSWICKS1
50/50
7.443
3151021BRUNSWICKG1
50/50
3.586
971451AH1-221 GEN
50/50
10.893
3151531CLOVER1
50/50
4.938
3143226MDLTHAN
Solar/Wind Harmer
0.305
940641AE2-051 GEN
Solar/Wind Harmer
22.672
939411AE1-173 GEN
Solar/Wind Harmer
114.479
970919AG2-571 GEN
Solar/Wind Harmer
9.287
970087AG2-069 GEN
Solar/Wind Harmer
20.797
3143526WINTERP
Solar/Wind Harmer
1.35
957481AF2-042 GEN
Solar/Wind Harmer
64.526
3151031BRUNSWICKG2
50/50
3.586
970413AG2-270 GEN
50/50
21.547
3151101ELIZAR3
50/50
21.88
970917AG2-570 GEN
Solar/Wind Harmer
23.218
316313AB2-026
Solar/Wind Harmer
0.15
316258AE1-075 C
Solar/Wind Harmer
0.18
316405AF2-144 C
Solar/Wind Harmer
0.002
3143336POWHATN
Solar/Wind Harmer
3.602
316478AD1-087 GEN
Solar/Wind Harmer
0.805
316486AD2-202 GEN
Solar/Wind Harmer
0.236
316365GEN2_N
Solar/Wind Harmer
0.504
944581AF1-123 GEN
Solar/Wind Harmer
50.561
944601AF1-125 GEN
Solar/Wind Harmer
49.783
315773AC2-141 GEN
Solar/Wind Harmer
8.172
3146456SLIGO L269
Solar/Wind Harmer
0.222
971153AH1-033 GEN
Solar/Wind Harmer
2.565
3144873MCLAUGH
Solar/Wind Harmer
0.006
316320Y1-086
Solar/Wind Harmer
0.001
970661AG2-428 GEN
Solar/Wind Harmer
4.646
316435W1029_GEN3
Solar/Wind Harmer
0.001
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.32
3146516WINFALL
Solar/Wind Harmer
0.219
315813AE1-149 C
Solar/Wind Harmer
11.679
3144536CHRHLND
Solar/Wind Harmer
0.033
3145273HOLLAND
Solar/Wind Harmer
0.164
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146376EDENTON
Solar/Wind Harmer
0.216
313506AB2-031 GEN
Solar/Wind Harmer
0.667
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3147043LAWRENC
Solar/Wind Harmer
0.129
315614AA2-178 GEN
Solar/Wind Harmer
1.224
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3145893MURPHYS
Solar/Wind Harmer
0.356
3145893MURPHYS
Solar/Wind Harmer
0.213
315839AE2-212 C
Solar/Wind Harmer
0.002
957521AF2-046 GEN
Solar/Wind Harmer
15.803
961681AG1-008 GEN
Solar/Wind Harmer
15.803
971157AH1-035 GEN
Solar/Wind Harmer
2.546
315737AD1-076 GEN
Solar/Wind Harmer
2.725
3146173TUNIS
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.211
3145336SMITFLD
Solar/Wind Harmer
0.084
316463AE2-346 GEN
Solar/Wind Harmer
0.181
316140AB2-099
Solar/Wind Harmer
0.075
962331AG1-082 GEN
Solar/Wind Harmer
2.248
3145796HORNRTN
Solar/Wind Harmer
0.842
3145796HORNRTN
Solar/Wind Harmer
0.211
3150861SPRUNCD
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.954
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
965281AG1-393 GEN
Solar/Wind Harmer
2.207
3145963POPLR C
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
14.86
3151171GRAVELC
Adder
2.859
316210AC1-098 GEN
Solar/Wind Harmer
1.894
970909AG2-566 GEN
Solar/Wind Harmer
2.177
316131AB2-060 GEN
Solar/Wind Harmer
0.636
961611AG1-000B GEN
Solar/Wind Harmer
5.383
315724AD1-057 GEN
Solar/Wind Harmer
0.756
964241AG1-285 GEN
Solar/Wind Harmer
13.392
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.335
316327AA2-057 GEN
Solar/Wind Harmer
0.301
315785AD2-033 C
Solar/Wind Harmer
1.614
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970257AG2-171 GEN
Solar/Wind Harmer
6.323
959311AF2-222 GEN
Solar/Wind Harmer
17.507
3146233WITAKRS
Solar/Wind Harmer
0.986
316303AF2-085
50/50
5.424
315244AE2-183_ST
50/50
7.889
3146233WITAKRS
Solar/Wind Harmer
0.134
315778AD1-151 GEN
Solar/Wind Harmer
15.709
3138543CONSLDL
Solar/Wind Harmer
0.129
3146073TAR RVR
Solar/Wind Harmer
0.195
3146083TARBORO
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
13.786
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.194
971623AH1-311 GEN
Solar/Wind Harmer
0.388
970129AG2-093 GEN
Solar/Wind Harmer
11.71
963181AG1-167 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3147133PAMPLIN
Solar/Wind Harmer
0.602
971193AH1-056 GEN
Solar/Wind Harmer
11.673
970133AG2-095 GEN
Solar/Wind Harmer
1.824
3144216WINCHST
Adder
0.716
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
8.068
3150921YORKTN3
Adder
4.712
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.11
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
316382AG1-145 C
Solar/Wind Harmer
0.001
971683AH1-343 GEN
Solar/Wind Harmer
6.321
316283AC2-100 C
Solar/Wind Harmer
0.335
3142946ENON
Solar/Wind Harmer
0.055
3146776BUCKING
Solar/Wind Harmer
0.059
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3141843SHACKLE
Adder
0.766
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
316156AD2-030 GEN
Solar/Wind Harmer
0.111
3141873WAN 176
Solar/Wind Harmer
2.658
970293AG2-193 GEN
Solar/Wind Harmer
1.582
3141766HARMONY
Solar/Wind Harmer
1.964
962971AG1-146 GEN
Solar/Wind Harmer
2.151
970009AG2-005 GEN
Solar/Wind Harmer
0.978
3142416OLDCHRC
Solar/Wind Harmer
1.237
316404AE1-155 C
Solar/Wind Harmer
0.028
970221AG2-151 GEN
Solar/Wind Harmer
6.633
963041AG1-153 GEN
50/50
7.262
315779AE2-040
50/50
3.426
3151541CLOVER2
50/50
4.914
941031AE2-094 GEN
Solar/Wind Harmer
52.507
944011AF1-069 GEN
Solar/Wind Harmer
17.156
970673AG2-436 GEN
Solar/Wind Harmer
59.565
970673AG2-436 GEN
Solar/Wind Harmer
39.71
971967AH1-528 GEN
Solar/Wind Harmer
43.86
970085AG2-068 GEN
Solar/Wind Harmer
13.865
970581AG2-369 GEN
Solar/Wind Harmer
11.924
316233AE1-074 FULL
Solar/Wind Harmer
0.208
971281AH1-106 GEN
Solar/Wind Harmer
3.602
971283AH1-107 GEN
Solar/Wind Harmer
3.602
316315AB2-025 C
Solar/Wind Harmer
0.198
315814AE2-033 C
Solar/Wind Harmer
19.336
3143316POE
Solar/Wind Harmer
0.915
957871AF2-081 GEN
Solar/Wind Harmer
11.058
3151081ELIZAR1
Adder
20.359
3151091ELIZAR2
Adder
20.005
319010AE1-072 C
Solar/Wind Harmer
1.117
3146406KITTY HAWK
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
2.823
3152621GOSPORTC
Adder
2.396
3152601GOSPORTA
Adder
2.21
316305AF2-043 C
Solar/Wind Harmer
0.002
313526AB2-022
Solar/Wind Harmer
0.119
315835AF2-110_GEN
Solar/Wind Harmer
1.513
316321Z2-027
Solar/Wind Harmer
0.041
3146396TANGLEW
Solar/Wind Harmer
0.607
3145176PASQUOTANK
Solar/Wind Harmer
0.136
3146486SUNBURY
Solar/Wind Harmer
0.22
3146486SUNBURY
Solar/Wind Harmer
0.22
316311AC2-079 GEN
Solar/Wind Harmer
6.318
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.151
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3130156CHOWAN
Solar/Wind Harmer
0.216
3130156CHOWAN
Solar/Wind Harmer
0.216
965291AG1-394 GEN
Solar/Wind Harmer
0.951
315816AE2-034 GEN
Solar/Wind Harmer
0.918
315652AC1-086 GEN
Solar/Wind Harmer
23.483
3137643SOCKMAN
Solar/Wind Harmer
0.852
3145893MURPHYS
Solar/Wind Harmer
0.574
3145893MURPHYS
Solar/Wind Harmer
0.213
3146043SEABORD
Solar/Wind Harmer
0.213
315607AA1-063A GEN
Solar/Wind Harmer
0.434
3130546PLYMOUTH
Solar/Wind Harmer
0.212
315732AD1-074 GEN1
Solar/Wind Harmer
1.217
315733AD1-074 GEN2
Solar/Wind Harmer
1.217
315735AD1-075 GEN1
Solar/Wind Harmer
0.609
3146206CASHIE
Solar/Wind Harmer
0.211
970601AG2-382 GEN
Solar/Wind Harmer
7.883
3145513AHOSKIE
Solar/Wind Harmer
0.441
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145796HORNRTN
Solar/Wind Harmer
0.674
3145796HORNRTN
Solar/Wind Harmer
0.084
971285AH1-108 GEN
Adder
1.587
971445AH1-216 GEN
Solar/Wind Harmer
14.817
3145683EARLEYS
Solar/Wind Harmer
0.42
3145683EARLEYS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
970831AG2-522 GEN
Solar/Wind Harmer
8.902
3146033SCOT NK
Solar/Wind Harmer
0.823
972265AH1-717 GEN
Adder
15.87
3151201GRAVEL4
Adder
14.877
3151191GRAVEL3
Adder
14.689
3151211GRAVEL5
Adder
14.689
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316005AA1-067
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.788
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
970181AG2-120 GEN
Solar/Wind Harmer
2.464
316369SG1_INVT
Solar/Wind Harmer
0.007
971443AH1-215 GEN
Solar/Wind Harmer
3.323
3144303KENBRDG
Solar/Wind Harmer
0.158
957861AF2-080 GEN
Solar/Wind Harmer
8.475
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.195
3145573BETHELC
Solar/Wind Harmer
0.195
970683AG2-441 GEN
Solar/Wind Harmer
13.022
970681AG2-440 GEN
Solar/Wind Harmer
10.418
316132AB2-190 GEN1
Solar/Wind Harmer
1.041
946301AF1-294 GEN
Solar/Wind Harmer
3.812
961791AG1-021 GEN
Solar/Wind Harmer
1.855
316118AC1-105 GEN
Solar/Wind Harmer
0.495
315657AE1-056 GEN
Solar/Wind Harmer
6.612
3147173SINAI
Solar/Wind Harmer
0.189
3147243WELCO
Solar/Wind Harmer
0.118
3138283WHITEMARSH
Solar/Wind Harmer
0.039
970285AG2-188 GEN
Solar/Wind Harmer
13.256
971845AH1-439 GEN
Solar/Wind Harmer
7.448
970865AG2-541 GEN
Solar/Wind Harmer
5.665
971167AH1-042 GEN
Solar/Wind Harmer
14.133
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
3143873LANEXA
Solar/Wind Harmer
0.09
970189AG2-124 GEN
Solar/Wind Harmer
4.44
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.03
316059AD1-063 C
Solar/Wind Harmer
0.001
316123AC1-075 GEN
Solar/Wind Harmer
0.2
970165AG2-112 GEN
Solar/Wind Harmer
1.187
970163AG2-111 GEN
Solar/Wind Harmer
1.132
316314AB2-024 C
Solar/Wind Harmer
0.001
315976AC1-164 GENA
Solar/Wind Harmer
15.083
316169AC1-164_GENC
Solar/Wind Harmer
13.031
315975AC1-164 GENB
Solar/Wind Harmer
0.446
3141913WHIT STONE
Solar/Wind Harmer
0.144
3138133OCRAN
Solar/Wind Harmer
0.043
3141783LANCAST
Solar/Wind Harmer
0.084
3141783LANCAST
Solar/Wind Harmer
0.056
972205AH1-687 GEN
Adder
5.897
962981AG1-147 GEN
Solar/Wind Harmer
5.019
970327AG2-215 GEN
Solar/Wind Harmer
4.3
316312AB1-027
Solar/Wind Harmer
0.228
971447AH1-217 GEN
Solar/Wind Harmer
3.55
3141813NORNECK
Solar/Wind Harmer
0.116
3143336POWHATN
Solar/Wind Harmer
4.238
315693AD1-088 GEN
Solar/Wind Harmer
11.177
962491AG1-098 GEN
Solar/Wind Harmer
13.203
316023GEN1_S
Solar/Wind Harmer
0.504
944591AF1-124 GEN
Solar/Wind Harmer
50.741
316294AC1-161 GEN
Solar/Wind Harmer
3.877
316388AE2-253 GEN
Solar/Wind Harmer
0.696
3146456SLIGO L269
Solar/Wind Harmer
0.222
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3150981CHESPKA
Adder
2.768
316246AF1-032 C
Solar/Wind Harmer
0.1
316336AC2-165 C
Solar/Wind Harmer
0.009
316093AE2-104_GEN
Solar/Wind Harmer
3.708
970661AG2-428 GEN
Solar/Wind Harmer
21.842
316381AD1-082 GEN
Solar/Wind Harmer
0.229
960081AF2-299 GEN
Solar/Wind Harmer
2.106
970659AG2-427 GEN
Solar/Wind Harmer
10.606
3146516WINFALL
Solar/Wind Harmer
0.71
3146516WINFALL
Solar/Wind Harmer
0.219
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.216
971795AH1-408 GEN
Solar/Wind Harmer
14.392
316072AD1-144
Solar/Wind Harmer
0.078
315687AD1-152 GEN
Solar/Wind Harmer
0.007
3147043LAWRENC
Adder
1.939
3145663CRESWEL
Solar/Wind Harmer
0.599
971163AH1-040 GEN
Solar/Wind Harmer
17.112
316011AB1-132 GEN
Solar/Wind Harmer
3.881
962571AG1-106 GEN
Solar/Wind Harmer
3.037
3145893MURPHYS
Solar/Wind Harmer
0.851
3145893MURPHYS
Solar/Wind Harmer
0.946
3146173TUNIS
Solar/Wind Harmer
0.211
316190AA2-174 GEN
Solar/Wind Harmer
0
3146206CASHIE
Solar/Wind Harmer
0.211
971547AH1-271 GEN
Solar/Wind Harmer
4.504
3145336SMITFLD
Solar/Wind Harmer
0.844
3145796HORNRTN
Solar/Wind Harmer
0.695
3145796HORNRTN
Solar/Wind Harmer
0.211
3150851SPRUNCC
Adder
0.97
3146263WOODLND
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.21
316129AC1-054 GEN
Solar/Wind Harmer
0.783
971065AG2-659 GEN
Solar/Wind Harmer
8.875
3145823KELFORD
Solar/Wind Harmer
0.208
3145963POPLR C
Solar/Wind Harmer
0.206
316174AB2-169 GEN
Solar/Wind Harmer
0.005
3151171GRAVELC
Adder
2.174
316212AC1-099_GEN
Solar/Wind Harmer
1.056
315671AE2-027_GEN
Solar/Wind Harmer
13.019
316237AB2-079_GEN
Solar/Wind Harmer
0.002
961611AG1-000B GEN
Solar/Wind Harmer
10.587
315722AD1-056 GEN
Solar/Wind Harmer
1.275
3146293MARTNCO
Solar/Wind Harmer
0.186
971647AH1-324 GEN
Solar/Wind Harmer
8.529
3145746EVERETS
Solar/Wind Harmer
0.198
3145746EVERETS
Solar/Wind Harmer
0.198
316494AC1-189 GEN
Solar/Wind Harmer
0.664
3146233WITAKRS
Solar/Wind Harmer
0.782
971069AG2-661 GEN
Solar/Wind Harmer
3.491
961671AG1-007 GEN
Solar/Wind Harmer
0.03
3146083TARBORO
Solar/Wind Harmer
0.195
3145493TOT1
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
14.585
970401AG2-262 GEN
Solar/Wind Harmer
1.143
316458AB2-190 GEN2
Solar/Wind Harmer
1.041
316359AB2-059 GEN
Solar/Wind Harmer
0.696
316049AB1-081 GEN
Solar/Wind Harmer
1.109
3145543BTLEBRO
Solar/Wind Harmer
0.194
3145543BTLEBRO
Solar/Wind Harmer
0.155
3142053HEARTS
Solar/Wind Harmer
0.341
970129AG2-093 GEN
Solar/Wind Harmer
5.511
963171AG1-166 GEN
Solar/Wind Harmer
1.03
971563AH1-280 GEN
Solar/Wind Harmer
2.061
3144293JTRSVLE
Adder
0.615
3138126ROCKLANDING
Solar/Wind Harmer
0.087
3142543TWELFTH
Solar/Wind Harmer
0.018
3146926FARMVIL
Solar/Wind Harmer
0.11
316003AC1-222 GEN
Solar/Wind Harmer
0.005
971317AH1-138 GEN
Solar/Wind Harmer
1.337
970937AG2-583 GEN
Solar/Wind Harmer
10.797
3143096IRON208
Adder
0.735
316159AE1-175 C
Solar/Wind Harmer
0.149
944631AF1-128 GEN
Adder
81.311
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.065
3142433PROV 92
Solar/Wind Harmer
0.629
3142433PROV 92
Adder
0.306
3142433PROV 92
Adder
0.306
971777AH1-397 GEN
Solar/Wind Harmer
0.396
3141843SHACKLE
Adder
0.766
3141766HARMONY
Solar/Wind Harmer
0.029
3138133OCRAN
Solar/Wind Harmer
0.086
972003AH1-546 GEN
Solar/Wind Harmer
6.056
3142416OLDCHRC
Solar/Wind Harmer
0.332
3142416OLDCHRC
Solar/Wind Harmer
0.127
962861AG1-135 GEN
Solar/Wind Harmer
4.063
971377AH1-170 GEN
Solar/Wind Harmer
1.327
3147623JAMES R
Solar/Wind Harmer
0.288
3141726DUNNSVL
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
1.153
970223AG2-152 GEN
Solar/Wind Harmer
7.902
316045AC1-158 PL2
Solar/Wind Helper
5.205
3147666LOUISA
Solar/Wind Helper
0.977
316192AB2-158 GEN
Solar/Wind Helper
1.608
3150351NORNECKC2
Adder
1.172
316473AC1-191 GEN
Solar/Wind Harmer
0.383
316044AC1-158 PL1
Solar/Wind Helper
1.626
316450AC1-158 RIC
Solar/Wind Helper
0.434
3147666LOUISA
Solar/Wind Helper
0.562
3145506HICKORY
Solar/Wind Harmer
0.134
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.213
316339AD2-160 GEN
Solar/Wind Harmer
0.36
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
316017AA1-139 ULT1
Solar/Wind Harmer
0.124
3137176SLIGO L2192
Solar/Wind Harmer
0.883
3146456SLIGO L269
Solar/Wind Harmer
3.926
316036AC1-147 C
Solar/Wind Harmer
0.041
3130086AYDLETT
Solar/Wind Harmer
0.886
3150991CHESPKB
Adder
2.322
3150991CHESPKB
Adder
2.266
3146386ELIZ CT
Solar/Wind Harmer
0.22
970657AG2-426 GEN
Solar/Wind Harmer
7.686
970657AG2-426 GEN
Solar/Wind Harmer
1.611
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.219
3146626S HERTFORD
Solar/Wind Harmer
0.218
3146626S HERTFORD
Solar/Wind Harmer
0.218
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.961
3146376EDENTON
Solar/Wind Harmer
0.961
316181AB2-040 GEN
Solar/Wind Harmer
0.313
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.213
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
1.424
3145893MURPHYS
Solar/Wind Harmer
0.383
3145593CAROLNA
Solar/Wind Harmer
0.211
3145593CAROLNA
Solar/Wind Harmer
0.211
966811AG1-552 GEN
Solar/Wind Harmer
2.295
3145593CAROLNA
Solar/Wind Harmer
0.263
3146173TUNIS
Solar/Wind Harmer
0.211
3146173TUNIS
Solar/Wind Harmer
0.211
316065AD1-022 GEN
Solar/Wind Harmer
9.733
316426AA2-053 GEN
Solar/Wind Harmer
0.714
316236AE1-162_GEN
Solar/Wind Harmer
0.002
3145796HORNRTN
Solar/Wind Harmer
0.632
971741AH1-377 GEN
Solar/Wind Harmer
20.897
3145783HORNRTN
Solar/Wind Harmer
3.74
3145783HORNRTN
Solar/Wind Harmer
2.992
3145783HORNRTN
Solar/Wind Harmer
0.935
3145783HORNRTN
Solar/Wind Harmer
0.374
939181AE1-148 GEN
Solar/Wind Harmer
9.88
970301AG2-198 GEN
Solar/Wind Harmer
8.706
316274AC1-208 GEN
Solar/Wind Harmer
1.058
313527AB2-043 GEN
Solar/Wind Harmer
0.003
316240AF1-291 C
Solar/Wind Harmer
0.002
3145933PARMELE
Solar/Wind Harmer
0.401
3145933PARMELE
Solar/Wind Harmer
0.2
316033AB2-134 GEN
Solar/Wind Harmer
0.012
315697AD1-025 GEN
Solar/Wind Harmer
0.223
970323AG2-213 GEN
Solar/Wind Harmer
8.431
971775AH1-396 GEN
Solar/Wind Harmer
0.316
316034AC1-036 C
Solar/Wind Harmer
0.014
944641AF1-129 GEN
Adder
93.824
962561AG1-105 GEN
Solar/Wind Harmer
9.407
3145493TOT1
Solar/Wind Harmer
0.453
3145453TOT5
Solar/Wind Harmer
0.272
3145603CNETO
Solar/Wind Harmer
0.181
964791AG1-342 GEN
Solar/Wind Harmer
3.74
3146843MT LREL
Solar/Wind Harmer
0.195
3146843MT LREL
Solar/Wind Harmer
0.195
961601AG1-000A GEN
Solar/Wind Harmer
3.447
316263AC1-034 GEN
Solar/Wind Harmer
7.365
958211AF2-115 GEN
Solar/Wind Harmer
2.318
963191AG1-168 GEN
Solar/Wind Harmer
0.773
3144293JTRSVLE
Adder
0.615
3144293JTRSVLE
Adder
0.518
3147133PAMPLIN
Solar/Wind Harmer
0.192
3147133PAMPLIN
Solar/Wind Harmer
0.153
316222AC1-221 GEN
Solar/Wind Harmer
0.714
3142946ENON
Solar/Wind Harmer
0.016
3146776BUCKING
Solar/Wind Harmer
0.65
3146776BUCKING
Solar/Wind Harmer
0.053
3142366NRTHEST
Adder
0.505
3150691DARBY 3
Adder
10.955
3150701DARBY 4
Adder
10.93
3150681DARBY 2
Adder
10.917
3150671DARBY 1
Adder
10.904
316075AC2-137 C
Solar/Wind Harmer
0.04
942751AE2-291 GEN
Solar/Wind Harmer
7.378
958261AF2-120 GEN
Solar/Wind Harmer
4.15
971489AH1-241 GEN
Solar/Wind Harmer
6.633
3142296MT RD221
Adder
0.39
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.211
3150341NORNECKC1
Adder
1.201
966871AG1-558 GEN
Solar/Wind Harmer
0.131
316447AC1-158 HLD
Solar/Wind Helper
3.579
NYPJM->LTFIMP_NY
CLTF
2.393
LAGNLTFEXP_LAGN->PJM
CLTF
9.063
LGEELTFEXP_LGEE->PJM
CLTF
1.582
WECLTFEXP_WEC->PJM
CLTF
0.806
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.182
TVALTFEXP_TVA->PJM
CLTF
4.543
CPLELTFEXP_CPLE->PJM
CLTF
13.025
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.006
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.545
MECLTFEXP_MEC->PJM
CLTF
4.353
SIGELTFEXP_SIGE->PJM
CLTF
0.131

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2090-256_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2090-256_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.73 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4126.18
MW Contribution:16.09
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
3.674
970413AG2-270 GEN
50/50
22.109
3151101ELIZAR3
50/50
22.735
970917AG2-570 GEN
Solar/Wind Harmer
75.183
316313AB2-026
Solar/Wind Harmer
0.749
316258AE1-075 C
Solar/Wind Harmer
0.674
316303AF2-085
50/50
5.624
315244AE2-183_ST
50/50
8.082
963041AG1-153 GEN
50/50
7.44
315779AE2-040
50/50
3.552
3151541CLOVER2
50/50
5.042
941031AE2-094 GEN
Solar/Wind Harmer
61.515
944011AF1-069 GEN
Solar/Wind Harmer
19.275
970673AG2-436 GEN
Solar/Wind Harmer
67.512
970673AG2-436 GEN
Solar/Wind Harmer
34.183
971967AH1-528 GEN
Solar/Wind Harmer
59.326
316233AE1-074 FULL
Solar/Wind Harmer
0.825
971281AH1-106 GEN
Solar/Wind Harmer
4.985
971283AH1-107 GEN
Solar/Wind Harmer
4.985
970085AG2-068 GEN
Solar/Wind Harmer
18.707
970581AG2-369 GEN
Solar/Wind Harmer
16.088
316315AB2-025 C
Solar/Wind Harmer
0.771
315814AE2-033 C
Solar/Wind Harmer
26.508
3143316POE
Solar/Wind Harmer
-0.107
3151081ELIZAR1
Adder
21.155
3151091ELIZAR2
Adder
20.788
957871AF2-081 GEN
Solar/Wind Harmer
12.957
3152611GOSPORTB
Adder
2.934
3152621GOSPORTC
Adder
2.49
3152601GOSPORTA
Adder
2.297
319010AE1-072 C
Solar/Wind Harmer
5.234
3146406KITTY HAWK
Solar/Wind Harmer
0.021
316305AF2-043 C
Solar/Wind Harmer
0.778
315833AF1-017_GEN
Solar/Wind Harmer
4.898
316349AD2-085 GEN
Solar/Wind Harmer
2.293
316311AC2-079 GEN
Solar/Wind Harmer
13.006
315835AF2-110_GEN
Solar/Wind Harmer
3.219
313526AB2-022
Solar/Wind Harmer
0.694
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.692
3146396TANGLEW
Solar/Wind Harmer
0.472
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.571
315611Z1-036_GEN2
Solar/Wind Harmer
6.264
971285AH1-108 GEN
Adder
1.701
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.593
965291AG1-394 GEN
Solar/Wind Harmer
2.212
315816AE2-034 GEN
Solar/Wind Harmer
2.016
315652AC1-086 GEN
Solar/Wind Harmer
27.921
3137643SOCKMAN
Solar/Wind Harmer
-0.099
316318V4-068
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
971445AH1-216 GEN
Solar/Wind Harmer
15.317
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.496
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
4.987
315733AD1-074 GEN2
Solar/Wind Harmer
4.987
315735AD1-075 GEN1
Solar/Wind Harmer
2.494
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.751
3145513AHOSKIE
Solar/Wind Harmer
0.214
961941AG1-037 GEN
Solar/Wind Harmer
0.184
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.049
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
12.084
972265AH1-717 GEN
Adder
16.682
3151201GRAVEL4
Adder
15.639
3151191GRAVEL3
Adder
15.441
3151211GRAVEL5
Adder
15.441
3146033SCOT NK
Solar/Wind Harmer
-0.095
316369SG1_INVT
Solar/Wind Harmer
4.209
316239AB2-077_GEN
Solar/Wind Harmer
0.705
316238AB2-078_GEN
Solar/Wind Harmer
0.705
316132AB2-190 GEN1
Solar/Wind Harmer
2.348
316005AA1-067
Solar/Wind Harmer
0.465
3145746EVERETS
Solar/Wind Harmer
-0.091
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970181AG2-120 GEN
Solar/Wind Harmer
3.018
970533AG2-339 GEN
50/50
25.956
970531AG2-338 GEN
50/50
10.382
315242AE2-183_GT2
50/50
4.674
315241AE2-183_GT1
50/50
4.646
972185AH1-677 GEN
50/50
16.852
3151041BRUNSWICKG3
50/50
3.674
972187AH1-678 GEN
50/50
8.432
971223AH1-071 GEN
Solar/Wind Harmer
4.443
3143526WINTERP
Solar/Wind Harmer
-0.159
970933AG2-581 GEN
Solar/Wind Harmer
28.617
3144356SAPONY
Solar/Wind Harmer
0.997
970099AG2-077 GEN
Solar/Wind Harmer
34.857
316185AD1-033 GEN
Solar/Wind Harmer
2.743
3145506HICKORY
Solar/Wind Harmer
-0.103
3145506HICKORY
Solar/Wind Harmer
-0.062
3145506HICKORY
Solar/Wind Harmer
-0.015
316405AF2-144 C
Solar/Wind Harmer
0.711
3143336POWHATN
Solar/Wind Harmer
2.8
316478AD1-087 GEN
Solar/Wind Harmer
2.301
316486AD2-202 GEN
Solar/Wind Harmer
0.674
944581AF1-123 GEN
Solar/Wind Harmer
119.099
944601AF1-125 GEN
Solar/Wind Harmer
117.241
316365GEN2_N
Solar/Wind Harmer
1.762
315773AC2-141 GEN
Solar/Wind Harmer
10.906
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.155
315813AE1-149 C
Solar/Wind Harmer
16.172
970659AG2-427 GEN
Solar/Wind Harmer
2.433
316083AB2-161 GEN
Solar/Wind Harmer
4.194
970661AG2-428 GEN
Solar/Wind Harmer
4.863
316320Y1-086
Solar/Wind Harmer
1.508
3144536CHRHLND
Solar/Wind Harmer
-0.004
316435W1029_GEN3
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
966621AG1-532 GEN
Solar/Wind Harmer
0.517
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3150861SPRUNCD
Adder
1.039
315839AE2-212 C
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.014
3156081AA2-088 GEN
Solar/Wind Harmer
8.101
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3147043LAWRENC
Solar/Wind Harmer
-0.015
3145336SMITFLD
Solar/Wind Harmer
-0.01
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.173
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.463
961681AG1-008 GEN
Solar/Wind Harmer
19.463
965281AG1-393 GEN
Solar/Wind Harmer
3.089
971157AH1-035 GEN
Solar/Wind Harmer
3.087
315737AD1-076 GEN
Solar/Wind Harmer
4.686
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.397
316140AB2-099
Solar/Wind Harmer
0.165
962331AG1-082 GEN
Solar/Wind Harmer
3.064
3145796HORNRTN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.295
316317KELFORD C
Solar/Wind Harmer
1.139
3145823KELFORD
Solar/Wind Harmer
-0.024
3151221GRAVEL6
Adder
15.621
3151171GRAVELC
Adder
3.005
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.036
316210AC1-098 GEN
Solar/Wind Harmer
3.72
970909AG2-566 GEN
Solar/Wind Harmer
2.238
315778AD1-151 GEN
Solar/Wind Harmer
20.288
316131AB2-060 GEN
Solar/Wind Harmer
2.524
315724AD1-057 GEN
Solar/Wind Harmer
1.345
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.91
964241AG1-285 GEN
Solar/Wind Harmer
18.149
970129AG2-093 GEN
Solar/Wind Harmer
13.053
316327AA2-057 GEN
Solar/Wind Harmer
2.335
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
315785AD2-033 C
Solar/Wind Harmer
5.203
970257AG2-171 GEN
Solar/Wind Harmer
8.57
970133AG2-095 GEN
Solar/Wind Harmer
2.571
3146233WITAKRS
Solar/Wind Harmer
0.477
3146233WITAKRS
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
23.777
3138543CONSLDL
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
3144216WINCHST
Adder
0.753
3144293JTRSVLE
Adder
0.633
3150921YORKTN3
Adder
4.961
3143096IRON208
Adder
0.8
3143096IRON208
Adder
0.784
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.276
316044AC1-158 PL1
Solar/Wind Helper
1.676
316450AC1-158 RIC
Solar/Wind Helper
0.447
3147666LOUISA
Solar/Wind Helper
0.577
970119AG2-088 GEN
50/50
42.178
315243AE2-183_GT3
50/50
4.674
3151051BRUNSWICKS1
50/50
7.626
3151021BRUNSWICKG1
50/50
3.674
971451AH1-221 GEN
50/50
11.16
3151531CLOVER1
50/50
5.066
3143226MDLTHAN
Solar/Wind Harmer
-0.035
940641AE2-051 GEN
Solar/Wind Harmer
30.624
939411AE1-173 GEN
Solar/Wind Harmer
155.015
3143526WINTERP
Solar/Wind Harmer
-0.159
970919AG2-571 GEN
Solar/Wind Harmer
9.517
970087AG2-069 GEN
Solar/Wind Harmer
28.061
957481AF2-042 GEN
Solar/Wind Harmer
87.144
3143336POWHATN
Solar/Wind Harmer
3.295
315693AD1-088 GEN
Solar/Wind Harmer
13.425
962491AG1-098 GEN
Solar/Wind Harmer
17.843
944591AF1-124 GEN
Solar/Wind Harmer
119.528
316023GEN1_S
Solar/Wind Harmer
1.762
316294AC1-161 GEN
Solar/Wind Harmer
8.432
316388AE2-253 GEN
Solar/Wind Harmer
1.749
316375AC2-012 GEN
Solar/Wind Harmer
8.959
3150981CHESPKA
Adder
2.877
3146456SLIGO L269
Solar/Wind Harmer
-0.026
970659AG2-427 GEN
Solar/Wind Harmer
13.731
316381AD1-082 GEN
Solar/Wind Harmer
2.37
970661AG2-428 GEN
Solar/Wind Harmer
27.441
316246AF1-032 C
Solar/Wind Harmer
0.522
316093AE2-104_GEN
Solar/Wind Harmer
7.488
316336AC2-165 C
Solar/Wind Harmer
4.471
3146516WINFALL
Solar/Wind Harmer
-0.082
3146516WINFALL
Solar/Wind Harmer
-0.025
960081AF2-299 GEN
Solar/Wind Harmer
2.867
315800Z1-036_GEN1
Solar/Wind Harmer
6.264
3150851SPRUNCC
Adder
1.039
316072AD1-144
Solar/Wind Harmer
0.511
3130156CHOWAN
Solar/Wind Harmer
-0.025
971795AH1-408 GEN
Solar/Wind Harmer
18.794
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.356
3147043LAWRENC
Adder
2.002
315687AD1-152 GEN
Solar/Wind Harmer
2.994
316011AB1-132 GEN
Solar/Wind Harmer
5.193
962571AG1-106 GEN
Solar/Wind Harmer
3.568
3145336SMITFLD
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
-0.099
3145893MURPHYS
Solar/Wind Harmer
0.735
3146173TUNIS
Solar/Wind Harmer
-0.025
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.143
316190AA2-174 GEN
Solar/Wind Harmer
0.301
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3142956BIRDNECK
Solar/Wind Harmer
1.392
316316AC1-027 C
Solar/Wind Harmer
0.796
316339AD2-160 GEN
Solar/Wind Harmer
1.749
316018AA1-139 ULT2
Solar/Wind Harmer
2.22
316017AA1-139 ULT1
Solar/Wind Harmer
2.097
316036AC1-147 C
Solar/Wind Harmer
0.698
3150991CHESPKB
Adder
2.413
3150991CHESPKB
Adder
2.355
3137176SLIGO L2192
Solar/Wind Harmer
-0.102
3146456SLIGO L269
Solar/Wind Harmer
3.057
3130086AYDLETT
Solar/Wind Harmer
-0.103
970657AG2-426 GEN
Solar/Wind Harmer
8.074
970657AG2-426 GEN
Solar/Wind Harmer
1.688
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.635
316433W1029_GEN2
Solar/Wind Harmer
4.635
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.654
3146376EDENTON
Solar/Wind Harmer
0.747
3146376EDENTON
Solar/Wind Harmer
0.747
316181AB2-040 GEN
Solar/Wind Harmer
3.495
316236AE1-162_GEN
Solar/Wind Harmer
0.748
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.691
3145893MURPHYS
Solar/Wind Harmer
-0.044
316065AD1-022 GEN
Solar/Wind Harmer
12.302
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.765
3145593CAROLNA
Solar/Wind Harmer
0.204
316426AA2-053 GEN
Solar/Wind Harmer
2.48
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145783HORNRTN
Solar/Wind Harmer
2.899
3145783HORNRTN
Solar/Wind Harmer
2.32
3145783HORNRTN
Solar/Wind Harmer
0.725
3145783HORNRTN
Solar/Wind Harmer
0.29
971741AH1-377 GEN
Solar/Wind Harmer
28.28
316240AF1-291 C
Solar/Wind Harmer
0.727
939181AE1-148 GEN
Solar/Wind Harmer
13.388
944641AF1-129 GEN
Adder
100.657
316274AC1-208 GEN
Solar/Wind Harmer
2.554
970301AG2-198 GEN
Solar/Wind Harmer
11.788
316033AB2-134 GEN
Solar/Wind Harmer
7.598
315697AD1-025 GEN
Solar/Wind Harmer
4.765
313527AB2-043 GEN
Solar/Wind Harmer
3.807
3145933PARMELE
Solar/Wind Harmer
-0.046
3145933PARMELE
Solar/Wind Harmer
-0.023
970323AG2-213 GEN
Solar/Wind Harmer
11.427
971775AH1-396 GEN
Solar/Wind Harmer
1.627
316034AC1-036 C
Solar/Wind Harmer
0.424
3145493TOT1
Solar/Wind Harmer
0.351
3145453TOT5
Solar/Wind Harmer
0.21
3145603CNETO
Solar/Wind Harmer
0.14
962561AG1-105 GEN
Solar/Wind Harmer
12.738
3144293JTRSVLE
Adder
0.633
3144293JTRSVLE
Adder
0.533
3142366NRTHEST
Adder
0.564
3150691DARBY 3
Adder
12.219
3150701DARBY 4
Adder
12.191
3150681DARBY 2
Adder
12.177
3150671DARBY 1
Adder
12.163
3142296MT RD221
Adder
0.462
3150341NORNECKC1
Adder
1.318
3150341NORNECKC1
Adder
1.308
316447AC1-158 HLD
Solar/Wind Helper
3.689
3145783HORNRTN
Solar/Wind Harmer
-0.024
315671AE2-027_GEN
Solar/Wind Harmer
18.264
3145823KELFORD
Solar/Wind Harmer
-0.024
3151171GRAVELC
Adder
2.286
316129AC1-054 GEN
Solar/Wind Harmer
2.115
971065AG2-659 GEN
Solar/Wind Harmer
12.042
3145963POPLR C
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.802
316174AB2-169 GEN
Solar/Wind Harmer
3.669
971647AH1-324 GEN
Solar/Wind Harmer
11.868
316212AC1-099_GEN
Solar/Wind Harmer
2.067
971069AG2-661 GEN
Solar/Wind Harmer
3.706
316237AB2-079_GEN
Solar/Wind Harmer
0.705
315722AD1-056 GEN
Solar/Wind Harmer
2.445
3146293MARTNCO
Solar/Wind Harmer
0.144
316458AB2-190 GEN2
Solar/Wind Harmer
2.348
970129AG2-093 GEN
Solar/Wind Harmer
5.287
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.455
3146233WITAKRS
Solar/Wind Harmer
-0.09
3142543TWELFTH
Solar/Wind Harmer
-0.002
961671AG1-007 GEN
Solar/Wind Harmer
0.287
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.672
3144293JTRSVLE
Adder
0.633
3143096IRON208
Adder
0.8
944631AF1-128 GEN
Adder
88.052
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
3141843SHACKLE
Adder
0.825
3150351NORNECKC2
Adder
1.255
316045AC1-158 PL2
Solar/Wind Helper
5.365
3147666LOUISA
Solar/Wind Helper
1.003
316192AB2-158 GEN
Solar/Wind Helper
1.65
970685AG2-442 GEN
Solar/Wind Harmer
7.163
971443AH1-215 GEN
Solar/Wind Harmer
4.504
3144303KENBRDG
Solar/Wind Harmer
-0.018
957861AF2-080 GEN
Solar/Wind Harmer
9.982
316319Z2-044 C
Solar/Wind Harmer
1.259
316420AA1-050 GEN
Solar/Wind Harmer
2.596
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
3142433PROV 92
Adder
0.331
3142433PROV 92
Adder
0.331
972205AH1-687 GEN
Adder
6.109
972189AH1-679 GEN
Adder
2.243
316164AC1-076 GEN
Solar/Wind Helper
1.087
NYPJM->LTFIMP_NY
CLTF
2.509
LGEELTFEXP_LGEE->PJM
CLTF
1.615
LAGNLTFEXP_LAGN->PJM
CLTF
9.293
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
WECLTFEXP_WEC->PJM
CLTF
0.822
TVALTFEXP_TVA->PJM
CLTF
4.659
CPLELTFEXP_CPLE->PJM
CLTF
13.39
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
28.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.936
MECLTFEXP_MEC->PJM
CLTF
4.446
SIGELTFEXP_SIGE->PJM
CLTF
0.134

Details for 8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2054-2135_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2054-2135_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.47 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4115.95
MW Contribution:15.78
Bus #Bus NameTypeMW Contribution
970533AG2-339 GEN
50/50
25.396
970531AG2-338 GEN
50/50
10.158
315242AE2-183_GT2
50/50
4.579
315241AE2-183_GT1
50/50
4.551
972185AH1-677 GEN
50/50
16.507
3151041BRUNSWICKG3
50/50
3.601
972187AH1-678 GEN
50/50
8.263
971223AH1-071 GEN
Solar/Wind Harmer
4.31
970933AG2-581 GEN
Solar/Wind Harmer
28.14
3143526WINTERP
Solar/Wind Harmer
-0.152
3144356SAPONY
Solar/Wind Harmer
0.965
316303AF2-085
50/50
5.455
315244AE2-183_ST
50/50
7.916
963041AG1-153 GEN
50/50
7.291
315779AE2-040
50/50
3.435
3151541CLOVER2
50/50
5.002
3151031BRUNSWICKG2
50/50
3.601
970413AG2-270 GEN
50/50
21.932
3151101ELIZAR3
50/50
21.884
970917AG2-570 GEN
Solar/Wind Harmer
73.734
316313AB2-026
Solar/Wind Harmer
0.757
316258AE1-075 C
Solar/Wind Harmer
0.682
316405AF2-144 C
Solar/Wind Harmer
0.719
3143336POWHATN
Solar/Wind Harmer
2.833
316478AD1-087 GEN
Solar/Wind Harmer
2.283
316486AD2-202 GEN
Solar/Wind Harmer
0.669
316365GEN2_N
Solar/Wind Harmer
1.714
944581AF1-123 GEN
Solar/Wind Harmer
114.798
944601AF1-125 GEN
Solar/Wind Harmer
113.006
315773AC2-141 GEN
Solar/Wind Harmer
10.516
3146456SLIGO L269
Solar/Wind Harmer
-0.025
971153AH1-033 GEN
Solar/Wind Harmer
3.041
3144873MCLAUGH
Solar/Wind Harmer
-0.001
966621AG1-532 GEN
Solar/Wind Harmer
0.505
316320Y1-086
Solar/Wind Harmer
1.455
316435W1029_GEN3
Solar/Wind Harmer
4.473
970661AG2-428 GEN
Solar/Wind Harmer
4.649
316083AB2-161 GEN
Solar/Wind Harmer
4.004
3146516WINFALL
Solar/Wind Harmer
-0.025
970099AG2-077 GEN
Solar/Wind Harmer
34.511
316185AD1-033 GEN
Solar/Wind Harmer
2.642
3145506HICKORY
Solar/Wind Harmer
-0.1
3145506HICKORY
Solar/Wind Harmer
-0.06
3145506HICKORY
Solar/Wind Harmer
-0.015
3142956BIRDNECK
Solar/Wind Harmer
1.341
316339AD2-160 GEN
Solar/Wind Harmer
1.685
316316AC1-027 C
Solar/Wind Harmer
0.767
316018AA1-139 ULT2
Solar/Wind Harmer
2.14
316017AA1-139 ULT1
Solar/Wind Harmer
2.021
3137176SLIGO L2192
Solar/Wind Harmer
-0.099
3146456SLIGO L269
Solar/Wind Harmer
2.947
3130086AYDLETT
Solar/Wind Harmer
-0.099
316036AC1-147 C
Solar/Wind Harmer
0.672
3150991CHESPKB
Adder
2.323
3150991CHESPKB
Adder
2.267
3146386ELIZ CT
Solar/Wind Harmer
-0.025
971741AH1-377 GEN
Solar/Wind Harmer
28.815
316431W1029_GEN1
Solar/Wind Harmer
4.473
316433W1029_GEN2
Solar/Wind Harmer
4.473
970657AG2-426 GEN
Solar/Wind Harmer
7.711
970657AG2-426 GEN
Solar/Wind Harmer
1.613
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146516WINFALL
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315742AE1-103 GEN
Solar/Wind Harmer
2.566
316181AB2-040 GEN
Solar/Wind Harmer
3.416
3146376EDENTON
Solar/Wind Harmer
0.723
3146376EDENTON
Solar/Wind Harmer
0.723
970301AG2-198 GEN
Solar/Wind Harmer
12.1
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.672
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.703
3145593CAROLNA
Solar/Wind Harmer
0.2
316426AA2-053 GEN
Solar/Wind Harmer
2.423
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
2.835
3145783HORNRTN
Solar/Wind Harmer
2.268
3145783HORNRTN
Solar/Wind Harmer
0.709
3145783HORNRTN
Solar/Wind Harmer
0.283
3145796HORNRTN
Solar/Wind Harmer
-0.071
316065AD1-022 GEN
Solar/Wind Harmer
11.938
316236AE1-162_GEN
Solar/Wind Harmer
0.715
939181AE1-148 GEN
Solar/Wind Harmer
13.315
313527AB2-043 GEN
Solar/Wind Harmer
3.812
970323AG2-213 GEN
Solar/Wind Harmer
11.586
971775AH1-396 GEN
Solar/Wind Harmer
1.65
316034AC1-036 C
Solar/Wind Harmer
0.43
316274AC1-208 GEN
Solar/Wind Harmer
2.497
958211AF2-115 GEN
Solar/Wind Harmer
3.581
963191AG1-168 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
3144293JTRSVLE
Adder
0.547
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3145933PARMELE
Solar/Wind Harmer
-0.045
3145933PARMELE
Solar/Wind Harmer
-0.023
962561AG1-105 GEN
Solar/Wind Harmer
12.73
316240AF1-291 C
Solar/Wind Harmer
0.679
944641AF1-129 GEN
Adder
93.798
3142366NRTHEST
Adder
0.504
3150691DARBY 3
Adder
10.929
3150701DARBY 4
Adder
10.903
3150681DARBY 2
Adder
10.891
3150671DARBY 1
Adder
10.878
3142296MT RD221
Adder
0.387
3150341NORNECKC1
Adder
1.196
3150341NORNECKC1
Adder
1.186
316447AC1-158 HLD
Solar/Wind Helper
3.787
966001AG1-469 GEN
Solar/Wind Helper
0.322
315651AD1-115 GEN
Solar/Wind Helper
0.849
964791AG1-342 GEN
Solar/Wind Harmer
3.241
941031AE2-094 GEN
Solar/Wind Harmer
60.188
944011AF1-069 GEN
Solar/Wind Harmer
18.859
970673AG2-436 GEN
Solar/Wind Harmer
66.104
970673AG2-436 GEN
Solar/Wind Harmer
33.47
971967AH1-528 GEN
Solar/Wind Harmer
58.188
970085AG2-068 GEN
Solar/Wind Harmer
18.348
970581AG2-369 GEN
Solar/Wind Harmer
15.779
316233AE1-074 FULL
Solar/Wind Harmer
0.788
971281AH1-106 GEN
Solar/Wind Harmer
4.763
971283AH1-107 GEN
Solar/Wind Harmer
4.763
316315AB2-025 C
Solar/Wind Harmer
0.746
315814AE2-033 C
Solar/Wind Harmer
25.646
3143316POE
Solar/Wind Harmer
-0.102
957871AF2-081 GEN
Solar/Wind Harmer
12.489
3151081ELIZAR1
Adder
20.363
3151091ELIZAR2
Adder
20.009
319010AE1-072 C
Solar/Wind Harmer
5.045
3146406KITTY HAWK
Solar/Wind Harmer
0.021
3152611GOSPORTB
Adder
2.824
3152621GOSPORTC
Adder
2.397
3152601GOSPORTA
Adder
2.211
946281AF1-292 GEN
Solar/Wind Harmer
0.558
316305AF2-043 C
Solar/Wind Harmer
0.75
313526AB2-022
Solar/Wind Harmer
0.67
315835AF2-110_GEN
Solar/Wind Harmer
3.1
316321Z2-027
Solar/Wind Harmer
0.668
3146396TANGLEW
Solar/Wind Harmer
0.456
3145176PASQUOTANK
Solar/Wind Harmer
-0.015
3146486SUNBURY
Solar/Wind Harmer
-0.025
3146486SUNBURY
Solar/Wind Harmer
-0.025
315833AF1-017_GEN
Solar/Wind Harmer
4.701
316349AD2-085 GEN
Solar/Wind Harmer
2.201
316311AC2-079 GEN
Solar/Wind Harmer
12.483
316087AB2-174 GEN
Solar/Wind Harmer
3.511
315611Z1-036_GEN2
Solar/Wind Harmer
6.052
3130156CHOWAN
Solar/Wind Harmer
-0.024
3130156CHOWAN
Solar/Wind Harmer
-0.024
3137643SOCKMAN
Solar/Wind Harmer
-0.096
965291AG1-394 GEN
Solar/Wind Harmer
2.149
315652AC1-086 GEN
Solar/Wind Harmer
27.213
315816AE2-034 GEN
Solar/Wind Harmer
1.952
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.435
316318V4-068
Solar/Wind Harmer
0.6
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.837
315733AD1-074 GEN2
Solar/Wind Harmer
4.837
315735AD1-075 GEN1
Solar/Wind Harmer
2.419
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.436
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
970831AG2-522 GEN
Solar/Wind Harmer
11.922
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
971285AH1-108 GEN
Adder
1.59
971445AH1-216 GEN
Solar/Wind Harmer
14.631
316239AB2-077_GEN
Solar/Wind Harmer
0.706
316238AB2-078_GEN
Solar/Wind Harmer
0.706
3146033SCOT NK
Solar/Wind Harmer
-0.093
971443AH1-215 GEN
Solar/Wind Harmer
4.564
3144303KENBRDG
Solar/Wind Harmer
-0.019
970683AG2-441 GEN
Solar/Wind Harmer
18.002
970681AG2-440 GEN
Solar/Wind Harmer
14.401
972265AH1-717 GEN
Adder
15.866
3151201GRAVEL4
Adder
14.873
3151191GRAVEL3
Adder
14.685
3151211GRAVEL5
Adder
14.685
946301AF1-294 GEN
Solar/Wind Harmer
5.873
961791AG1-021 GEN
Solar/Wind Harmer
2.865
315657AE1-056 GEN
Solar/Wind Harmer
8.562
972205AH1-687 GEN
Adder
7.023
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
316164AC1-076 GEN
Solar/Wind Helper
1.276
970659AG2-427 GEN
Solar/Wind Harmer
2.322
3145273HOLLAND
Solar/Wind Harmer
-0.018
315813AE1-149 C
Solar/Wind Harmer
15.384
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3144536CHRHLND
Solar/Wind Harmer
-0.004
313506AB2-031 GEN
Solar/Wind Harmer
1.969
3147043LAWRENC
Solar/Wind Harmer
-0.015
3146376EDENTON
Solar/Wind Harmer
-0.024
3156081AA2-088 GEN
Solar/Wind Harmer
7.869
970909AG2-566 GEN
Solar/Wind Harmer
2.298
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
2.603
3145893MURPHYS
Solar/Wind Harmer
0.168
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.923
961681AG1-008 GEN
Solar/Wind Harmer
18.923
971157AH1-035 GEN
Solar/Wind Harmer
2.994
3146173TUNIS
Solar/Wind Harmer
-0.024
315737AD1-076 GEN
Solar/Wind Harmer
4.545
315839AE2-212 C
Solar/Wind Harmer
0.72
3145796HORNRTN
Solar/Wind Harmer
-0.095
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.98
3146263WOODLND
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.202
3145336SMITFLD
Solar/Wind Harmer
-0.009
3150861SPRUNCD
Adder
0.972
316317KELFORD C
Solar/Wind Harmer
1.11
3145823KELFORD
Solar/Wind Harmer
-0.023
316131AB2-060 GEN
Solar/Wind Harmer
2.53
964241AG1-285 GEN
Solar/Wind Harmer
18.252
3145963POPLR C
Solar/Wind Harmer
-0.023
965281AG1-393 GEN
Solar/Wind Harmer
2.905
315785AD2-033 C
Solar/Wind Harmer
5.263
970257AG2-171 GEN
Solar/Wind Harmer
8.69
316210AC1-098 GEN
Solar/Wind Harmer
3.635
959311AF2-222 GEN
Solar/Wind Harmer
24.148
3151221GRAVEL6
Adder
14.856
3151171GRAVELC
Adder
2.858
963181AG1-167 GEN
Solar/Wind Harmer
2.149
3144293JTRSVLE
Adder
0.649
315724AD1-057 GEN
Solar/Wind Harmer
1.315
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.27
3145933PARMELE
Solar/Wind Harmer
-0.023
966801AG1-551 GEN
Solar/Wind Harmer
2.838
961611AG1-000B GEN
Solar/Wind Harmer
4.775
316327AA2-057 GEN
Solar/Wind Harmer
2.286
942461AE2-259 GEN
Solar/Wind Harmer
3.394
3144216WINCHST
Adder
0.715
3150921YORKTN3
Adder
4.706
3143096IRON208
Adder
0.735
3143096IRON208
Adder
0.72
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.158
3147666LOUISA
Solar/Wind Helper
0.782
316044AC1-158 PL1
Solar/Wind Helper
1.721
316450AC1-158 RIC
Solar/Wind Helper
0.459
3132273ORANGE
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.398
970119AG2-088 GEN
50/50
40.916
315243AE2-183_GT3
50/50
4.579
3151051BRUNSWICKS1
50/50
7.473
3151021BRUNSWICKG1
50/50
3.601
971451AH1-221 GEN
50/50
10.937
3151531CLOVER1
50/50
5.026
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
29.864
939411AE1-173 GEN
Solar/Wind Harmer
150.793
970919AG2-571 GEN
Solar/Wind Harmer
9.333
970087AG2-069 GEN
Solar/Wind Harmer
27.522
3143526WINTERP
Solar/Wind Harmer
-0.152
3143336POWHATN
Solar/Wind Harmer
3.333
957481AF2-042 GEN
Solar/Wind Harmer
86.276
315693AD1-088 GEN
Solar/Wind Harmer
13.378
962491AG1-098 GEN
Solar/Wind Harmer
17.804
316336AC2-165 C
Solar/Wind Harmer
4.589
316023GEN1_S
Solar/Wind Harmer
1.714
944591AF1-124 GEN
Solar/Wind Harmer
115.211
316294AC1-161 GEN
Solar/Wind Harmer
8.131
316388AE2-253 GEN
Solar/Wind Harmer
1.685
3146456SLIGO L269
Solar/Wind Harmer
-0.025
316375AC2-012 GEN
Solar/Wind Harmer
8.622
3150981CHESPKA
Adder
2.768
960081AF2-299 GEN
Solar/Wind Harmer
2.801
316246AF1-032 C
Solar/Wind Harmer
0.503
316093AE2-104_GEN
Solar/Wind Harmer
7.211
970661AG2-428 GEN
Solar/Wind Harmer
26.234
316381AD1-082 GEN
Solar/Wind Harmer
2.262
3146516WINFALL
Solar/Wind Harmer
-0.079
3146516WINFALL
Solar/Wind Harmer
-0.025
970659AG2-427 GEN
Solar/Wind Harmer
13.1
315687AD1-152 GEN
Solar/Wind Harmer
2.972
971795AH1-408 GEN
Solar/Wind Harmer
18.452
315800Z1-036_GEN1
Solar/Wind Harmer
6.052
3147043LAWRENC
Adder
1.97
3130156CHOWAN
Solar/Wind Harmer
-0.024
316072AD1-144
Solar/Wind Harmer
0.491
316011AB1-132 GEN
Solar/Wind Harmer
5.061
962571AG1-106 GEN
Solar/Wind Harmer
3.477
3145663CRESWEL
Solar/Wind Harmer
-0.067
971163AH1-040 GEN
Solar/Wind Harmer
22.621
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.714
316190AA2-174 GEN
Solar/Wind Harmer
0.294
3146173TUNIS
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.078
3145796HORNRTN
Solar/Wind Harmer
-0.024
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.963
3146263WOODLND
Solar/Wind Harmer
-0.024
316129AC1-054 GEN
Solar/Wind Harmer
2.089
971065AG2-659 GEN
Solar/Wind Harmer
11.903
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145336SMITFLD
Solar/Wind Harmer
-0.094
3150851SPRUNCC
Adder
0.972
3145823KELFORD
Solar/Wind Harmer
-0.023
316237AB2-079_GEN
Solar/Wind Harmer
0.706
3145963POPLR C
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
2.019
316174AB2-169 GEN
Solar/Wind Harmer
3.571
970685AG2-442 GEN
Solar/Wind Harmer
20.162
3151171GRAVELC
Adder
2.174
963171AG1-166 GEN
Solar/Wind Harmer
2.865
971563AH1-280 GEN
Solar/Wind Harmer
2.865
3144293JTRSVLE
Adder
0.649
315722AD1-056 GEN
Solar/Wind Harmer
2.391
315671AE2-027_GEN
Solar/Wind Harmer
17.138
3146293MARTNCO
Solar/Wind Harmer
0.141
961611AG1-000B GEN
Solar/Wind Harmer
11.191
3143096IRON208
Adder
0.735
944631AF1-128 GEN
Adder
81.193
3142433PROV 92
Adder
0.305
3142433PROV 92
Adder
0.305
3141843SHACKLE
Adder
0.762
3150351NORNECKC2
Adder
1.139
3147666LOUISA
Solar/Wind Helper
1.36
316192AB2-158 GEN
Solar/Wind Helper
2.271
316045AC1-158 PL2
Solar/Wind Helper
5.508
316254AC1-120 GEN1
Solar/Wind Helper
1.194
970401AG2-262 GEN
Solar/Wind Harmer
0.99
NYPJM->LTFIMP_NY
CLTF
2.522
LGEELTFEXP_LGEE->PJM
CLTF
1.726
LAGNLTFEXP_LAGN->PJM
CLTF
9.537
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.961
WECLTFEXP_WEC->PJM
CLTF
0.88
TVALTFEXP_TVA->PJM
CLTF
4.788
CPLELTFEXP_CPLE->PJM
CLTF
13.285
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.607
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.685
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.441
MECLTFEXP_MEC->PJM
CLTF
4.694
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 57302_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57302_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:161.07 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5022.16
MW Contribution:11.91
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
36.75
3151771S ANNAG1
50/50
0.935
3151801S ANNAS2
50/50
0.481
3151761LOISA E
50/50
35.514
972183AH1-676 GEN
50/50
276.382
3151031BRUNSWICKG2
50/50
2.724
3147666LOUISA
Solar/Wind Harmer
-0.113
316313AB2-026
Solar/Wind Harmer
0.603
316258AE1-075 C
Solar/Wind Harmer
0.543
316405AF2-144 C
Solar/Wind Harmer
0.573
3143336POWHATN
Solar/Wind Harmer
2.255
970917AG2-570 GEN
Solar/Wind Harmer
55.674
316478AD1-087 GEN
Solar/Wind Harmer
1.738
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
1.825
316365GEN2_N
Solar/Wind Harmer
1.247
3146926FARMVIL
Solar/Wind Harmer
-0.011
966621AG1-532 GEN
Solar/Wind Harmer
0.37
942461AE2-259 GEN
Solar/Wind Harmer
2.731
3147043LAWRENC
Solar/Wind Harmer
-0.011
3147133PAMPLIN
Solar/Wind Harmer
-0.057
971193AH1-056 GEN
Solar/Wind Harmer
11.307
963181AG1-167 GEN
Solar/Wind Harmer
1.693
3144293JTRSVLE
Adder
0.512
959311AF2-222 GEN
Solar/Wind Harmer
18.777
970257AG2-171 GEN
Solar/Wind Harmer
6.741
315785AD2-033 C
Solar/Wind Harmer
4.07
964241AG1-285 GEN
Solar/Wind Harmer
13.995
313506AB2-031 GEN
Solar/Wind Harmer
1.439
316131AB2-060 GEN
Solar/Wind Harmer
1.93
944581AF1-123 GEN
Solar/Wind Harmer
80.086
944601AF1-125 GEN
Solar/Wind Harmer
78.837
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
315773AC2-141 GEN
Solar/Wind Harmer
7.296
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.122
316320Y1-086
Solar/Wind Harmer
1.017
3151101ELIZAR3
Adder
14.333
3156081AA2-088 GEN
Solar/Wind Harmer
5.629
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.133
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.12
3145893MURPHYS
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.562
961681AG1-008 GEN
Solar/Wind Harmer
13.562
3146263WOODLND
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970661AG2-428 GEN
Solar/Wind Harmer
3.225
316463AE2-346 GEN
Solar/Wind Harmer
0.277
316140AB2-099
Solar/Wind Harmer
0.115
962331AG1-082 GEN
Solar/Wind Harmer
2.137
316083AB2-161 GEN
Solar/Wind Harmer
2.773
970659AG2-427 GEN
Solar/Wind Harmer
1.607
315614AA2-178 GEN
Solar/Wind Harmer
1.842
971157AH1-035 GEN
Solar/Wind Harmer
2.125
315813AE1-149 C
Solar/Wind Harmer
10.623
3156021HOLLOMANSOL
Solar/Wind Harmer
2.289
3146206CASHIE
Solar/Wind Harmer
-0.017
315737AD1-076 GEN
Solar/Wind Harmer
3.228
3144536CHRHLND
Solar/Wind Harmer
-0.003
316317KELFORD C
Solar/Wind Harmer
0.799
3145823KELFORD
Solar/Wind Harmer
-0.017
316210AC1-098 GEN
Solar/Wind Harmer
2.634
3150861SPRUNCD
Adder
0.655
3151221GRAVEL6
Adder
9.971
3151171GRAVELC
Adder
1.918
3144216WINCHST
Adder
0.464
3150921YORKTN3
Adder
3.034
3152251N ANNA1
50/50
36.753
3151791S ANNAG2
50/50
0.935
3151781S ANNAS1
50/50
0.481
3151741LOISA C
50/50
0.953
3151751LOISA D
50/50
17.42
970119AG2-088 GEN
50/50
31.154
315243AE2-183_GT3
50/50
3.465
3151051BRUNSWICKS1
50/50
5.654
3151021BRUNSWICKG1
50/50
2.724
971451AH1-221 GEN
50/50
8.274
3147666LOUISA
Solar/Wind Harmer
-0.196
316192AB2-158 GEN
Solar/Wind Harmer
5.718
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
22.347
3143336POWHATN
Solar/Wind Harmer
2.653
970919AG2-571 GEN
Solar/Wind Harmer
7.047
939411AE1-173 GEN
Solar/Wind Harmer
111.228
970087AG2-069 GEN
Solar/Wind Harmer
20.777
316336AC2-165 C
Solar/Wind Harmer
3.708
3143526WINTERP
Solar/Wind Harmer
-0.11
957481AF2-042 GEN
Solar/Wind Harmer
65.731
315693AD1-088 GEN
Solar/Wind Harmer
10.265
962491AG1-098 GEN
Solar/Wind Harmer
13.684
970937AG2-583 GEN
Solar/Wind Harmer
13.455
315687AD1-152 GEN
Solar/Wind Harmer
2.252
316023GEN1_S
Solar/Wind Harmer
1.247
3146926FARMVIL
Solar/Wind Harmer
-0.011
960081AF2-299 GEN
Solar/Wind Harmer
2.052
971795AH1-408 GEN
Solar/Wind Harmer
13.624
3147043LAWRENC
Adder
1.46
963171AG1-166 GEN
Solar/Wind Harmer
2.258
971563AH1-280 GEN
Solar/Wind Harmer
2.258
3144293JTRSVLE
Adder
0.512
970685AG2-442 GEN
Solar/Wind Harmer
15.768
316237AB2-079_GEN
Solar/Wind Harmer
0.537
971065AG2-659 GEN
Solar/Wind Harmer
8.873
316129AC1-054 GEN
Solar/Wind Harmer
1.554
944591AF1-124 GEN
Solar/Wind Harmer
80.375
316011AB1-132 GEN
Solar/Wind Harmer
3.673
962571AG1-106 GEN
Solar/Wind Harmer
2.523
316322AB2-045
Solar/Wind Harmer
0.588
3146776BUCKING
Solar/Wind Harmer
-0.007
316294AC1-161 GEN
Solar/Wind Harmer
5.641
316388AE2-253 GEN
Solar/Wind Harmer
1.175
316190AA2-174 GEN
Solar/Wind Harmer
0.214
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.351
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316093AE2-104_GEN
Solar/Wind Harmer
5.036
316375AC2-012 GEN
Solar/Wind Harmer
5.989
3150981CHESPKA
Adder
1.923
3146516WINFALL
Solar/Wind Harmer
-0.056
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
0.512
315800Z1-036_GEN1
Solar/Wind Harmer
4.254
3146263WOODLND
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
970661AG2-428 GEN
Solar/Wind Harmer
18.199
316381AD1-082 GEN
Solar/Wind Harmer
1.567
970659AG2-427 GEN
Solar/Wind Harmer
9.07
3145663CRESWEL
Solar/Wind Harmer
-0.048
971163AH1-040 GEN
Solar/Wind Harmer
16.003
3145683EARLEYS
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.111
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.247
3145823KELFORD
Solar/Wind Harmer
-0.017
316212AC1-099_GEN
Solar/Wind Harmer
1.463
316072AD1-144
Solar/Wind Harmer
0.339
3150851SPRUNCC
Adder
0.655
3151171GRAVELC
Adder
1.459
972003AH1-546 GEN
Solar/Wind Harmer
6.164
316303AF2-085
50/50
4.154
315244AE2-183_ST
50/50
5.99
963041AG1-153 GEN
50/50
5.516
315779AE2-040
50/50
2.503
3147346CASHSCORNER
Solar/Wind Harmer
0.403
941031AE2-094 GEN
Solar/Wind Harmer
45.568
944011AF1-069 GEN
Solar/Wind Harmer
14.278
970673AG2-436 GEN
Solar/Wind Harmer
50.031
970673AG2-436 GEN
Solar/Wind Harmer
25.332
971967AH1-528 GEN
Solar/Wind Harmer
44.101
970085AG2-068 GEN
Solar/Wind Harmer
13.851
970581AG2-369 GEN
Solar/Wind Harmer
11.912
316233AE1-074 FULL
Solar/Wind Harmer
0.574
971281AH1-106 GEN
Solar/Wind Harmer
3.465
971283AH1-107 GEN
Solar/Wind Harmer
3.465
316315AB2-025 C
Solar/Wind Harmer
0.543
315814AE2-033 C
Solar/Wind Harmer
18.684
3143316POE
Solar/Wind Harmer
-0.072
946281AF1-292 GEN
Solar/Wind Harmer
0.409
315657AE1-056 GEN
Solar/Wind Harmer
6.784
946301AF1-294 GEN
Solar/Wind Harmer
4.628
961791AG1-021 GEN
Solar/Wind Harmer
2.258
970683AG2-441 GEN
Solar/Wind Harmer
14.079
970681AG2-440 GEN
Solar/Wind Harmer
11.263
316087AB2-174 GEN
Solar/Wind Harmer
2.568
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.538
316239AB2-077_GEN
Solar/Wind Harmer
0.537
316238AB2-078_GEN
Solar/Wind Harmer
0.537
970831AG2-522 GEN
Solar/Wind Harmer
8.853
3137643SOCKMAN
Solar/Wind Harmer
-0.07
970285AG2-188 GEN
Solar/Wind Harmer
15.458
315652AC1-086 GEN
Solar/Wind Harmer
19.749
971845AH1-439 GEN
Solar/Wind Harmer
9.317
315607AA1-063A GEN
Solar/Wind Harmer
1.762
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.713
319010AE1-072 C
Solar/Wind Harmer
3.521
3146406KITTY HAWK
Solar/Wind Harmer
0.014
313526AB2-022
Solar/Wind Harmer
0.468
316305AF2-043 C
Solar/Wind Harmer
0.523
3151081ELIZAR1
Adder
14.152
3151091ELIZAR2
Adder
13.906
965291AG1-394 GEN
Solar/Wind Harmer
1.539
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.467
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.319
315835AF2-110_GEN
Solar/Wind Harmer
2.165
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.962
3152621GOSPORTC
Adder
1.665
3152601GOSPORTA
Adder
1.536
316318V4-068
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.691
315833AF1-017_GEN
Solar/Wind Harmer
3.272
316349AD2-085 GEN
Solar/Wind Harmer
1.532
315611Z1-036_GEN2
Solar/Wind Harmer
4.254
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.149
961941AG1-037 GEN
Solar/Wind Harmer
0.129
3145513AHOSKIE
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.381
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.432
315732AD1-074 GEN1
Solar/Wind Harmer
3.435
315733AD1-074 GEN2
Solar/Wind Harmer
3.435
315735AD1-075 GEN1
Solar/Wind Harmer
1.718
3146033SCOT NK
Solar/Wind Harmer
-0.067
316118AC1-105 GEN
Solar/Wind Harmer
1.149
972205AH1-687 GEN
Adder
6.275
971285AH1-108 GEN
Adder
1.072
972265AH1-717 GEN
Adder
10.649
3151201GRAVEL4
Adder
9.982
3151191GRAVEL3
Adder
9.856
3151211GRAVEL5
Adder
9.856
971133AH1-012 GEN
50/50
9.167
3151731LOISA B
50/50
17.42
3151721LOISA A
50/50
17.33
970533AG2-339 GEN
50/50
19.227
970531AG2-338 GEN
50/50
7.691
315242AE2-183_GT2
50/50
3.465
315241AE2-183_GT1
50/50
3.443
972185AH1-677 GEN
50/50
12.491
3151041BRUNSWICKG3
50/50
2.724
972187AH1-678 GEN
50/50
6.252
971223AH1-071 GEN
Solar/Wind Harmer
3.282
966001AG1-469 GEN
Solar/Wind Harmer
0.464
970933AG2-581 GEN
Solar/Wind Harmer
21.362
3143526WINTERP
Solar/Wind Harmer
-0.11
970099AG2-077 GEN
Solar/Wind Harmer
26.292
3144356SAPONY
Solar/Wind Harmer
0.703
971741AH1-377 GEN
Solar/Wind Harmer
22.699
970301AG2-198 GEN
Solar/Wind Harmer
9.614
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.822
963191AG1-168 GEN
Solar/Wind Harmer
1.693
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.333
970323AG2-213 GEN
Solar/Wind Harmer
8.988
971775AH1-396 GEN
Solar/Wind Harmer
1.28
316181AB2-040 GEN
Solar/Wind Harmer
2.496
313527AB2-043 GEN
Solar/Wind Harmer
2.904
939181AE1-148 GEN
Solar/Wind Harmer
10.04
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.97
3145593CAROLNA
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
316185AD1-033 GEN
Solar/Wind Harmer
1.841
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.042
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.175
316426AA2-053 GEN
Solar/Wind Harmer
1.761
316018AA1-139 ULT2
Solar/Wind Harmer
1.493
316017AA1-139 ULT1
Solar/Wind Harmer
1.41
3137176SLIGO L2192
Solar/Wind Harmer
-0.069
3146456SLIGO L269
Solar/Wind Harmer
2.056
3130086AYDLETT
Solar/Wind Harmer
-0.069
3145783HORNRTN
Solar/Wind Harmer
2.065
3145783HORNRTN
Solar/Wind Harmer
1.652
3145783HORNRTN
Solar/Wind Harmer
0.516
3145783HORNRTN
Solar/Wind Harmer
0.206
3142956BIRDNECK
Solar/Wind Harmer
0.933
316316AC1-027 C
Solar/Wind Harmer
0.533
3146386ELIZ CT
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.052
315742AE1-103 GEN
Solar/Wind Harmer
1.812
316036AC1-147 C
Solar/Wind Harmer
0.467
3150991CHESPKB
Adder
1.613
3150991CHESPKB
Adder
1.575
316431W1029_GEN1
Solar/Wind Harmer
3.133
316433W1029_GEN2
Solar/Wind Harmer
3.133
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.481
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146376EDENTON
Solar/Wind Harmer
0.509
3146376EDENTON
Solar/Wind Harmer
0.509
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
962561AG1-105 GEN
Solar/Wind Harmer
9.645
970657AG2-426 GEN
Solar/Wind Harmer
5.345
970657AG2-426 GEN
Solar/Wind Harmer
1.118
964791AG1-342 GEN
Solar/Wind Harmer
3.634
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
316065AD1-022 GEN
Solar/Wind Harmer
8.493
316274AC1-208 GEN
Solar/Wind Harmer
1.814
944641AF1-129 GEN
Adder
61.579
NYPJM->LTFIMP_NY
CLTF
2.601
LGEELTFEXP_LGEE->PJM
CLTF
0.905
LAGNLTFEXP_LAGN->PJM
CLTF
6.179
WECLTFEXP_WEC->PJM
CLTF
0.439
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.792
TVALTFEXP_TVA->PJM
CLTF
3.107
CPLELTFEXP_CPLE->PJM
CLTF
9.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.98
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.458
MECLTFEXP_MEC->PJM
CLTF
2.584
SIGELTFEXP_SIGE->PJM
CLTF
0.077

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 594_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:150.27 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4839.45
MW Contribution:8.53
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
35.378
3151791S ANNAG2
50/50
1.098
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.127
3151751LOISA D
50/50
20.602
970119AG2-088 GEN
50/50
29.412
315243AE2-183_GT3
50/50
3.266
3151051BRUNSWICKS1
50/50
5.329
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.799
316045AC1-158 PL2
Solar/Wind Harmer
11.495
3147666LOUISA
Solar/Wind Harmer
1.947
316192AB2-158 GEN
Solar/Wind Harmer
2.693
316254AC1-120 GEN1
Solar/Wind Harmer
0.471
3143226MDLTHAN
Solar/Wind Harmer
0.22
940641AE2-051 GEN
Solar/Wind Harmer
15.946
3143336POWHATN
Solar/Wind Harmer
3.398
970919AG2-571 GEN
Solar/Wind Harmer
6.642
970087AG2-069 GEN
Solar/Wind Harmer
14.871
939411AE1-173 GEN
Solar/Wind Harmer
79.115
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.921
957481AF2-042 GEN
Solar/Wind Harmer
47.237
315693AD1-088 GEN
Solar/Wind Harmer
8.323
962491AG1-098 GEN
Solar/Wind Harmer
9.868
315683AE1-153 C
Solar/Wind Harmer
13.39
970937AG2-583 GEN
Solar/Wind Harmer
10.032
3146926FARMVIL
Solar/Wind Harmer
0.095
315687AD1-152 GEN
Solar/Wind Harmer
0.005
963171AG1-166 GEN
Solar/Wind Harmer
0.823
971563AH1-280 GEN
Solar/Wind Harmer
1.646
3144293JTRSVLE
Adder
0.491
316023GEN1_S
Solar/Wind Harmer
0.345
970685AG2-442 GEN
Solar/Wind Harmer
11.466
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.061
960081AF2-299 GEN
Solar/Wind Harmer
1.461
971795AH1-408 GEN
Solar/Wind Harmer
10.127
3147043LAWRENC
Adder
1.373
316237AB2-079_GEN
Solar/Wind Harmer
0.001
971065AG2-659 GEN
Solar/Wind Harmer
6.351
316129AC1-054 GEN
Solar/Wind Harmer
0.559
972003AH1-546 GEN
Solar/Wind Harmer
6.284
316011AB1-132 GEN
Solar/Wind Harmer
2.654
962571AG1-106 GEN
Solar/Wind Harmer
2.077
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.145
944591AF1-124 GEN
Solar/Wind Harmer
32.725
3145796HORNRTN
Solar/Wind Harmer
0.476
3145796HORNRTN
Solar/Wind Harmer
0.144
970401AG2-262 GEN
Solar/Wind Harmer
0.842
316388AE2-253 GEN
Solar/Wind Harmer
0.449
3146456SLIGO L269
Solar/Wind Harmer
0.143
316294AC1-161 GEN
Solar/Wind Harmer
2.482
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.636
316246AF1-032 C
Solar/Wind Harmer
0.064
3146263WOODLND
Solar/Wind Harmer
0.143
316093AE2-104_GEN
Solar/Wind Harmer
2.398
3146516WINFALL
Solar/Wind Harmer
0.461
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.776
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.141
3145663CRESWEL
Solar/Wind Harmer
0.395
971163AH1-040 GEN
Solar/Wind Harmer
11.283
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
13.998
3146206CASHIE
Solar/Wind Harmer
0.14
971547AH1-271 GEN
Solar/Wind Harmer
3
316381AD1-082 GEN
Solar/Wind Harmer
0.146
970659AG2-427 GEN
Solar/Wind Harmer
6.78
316212AC1-099_GEN
Solar/Wind Harmer
0.722
315722AD1-056 GEN
Solar/Wind Harmer
0.876
3145963POPLR C
Solar/Wind Harmer
0.138
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316072AD1-144
Solar/Wind Harmer
0.05
3146293MARTNCO
Solar/Wind Harmer
0.126
3146233WITAKRS
Solar/Wind Harmer
0.538
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
971377AH1-170 GEN
Solar/Wind Harmer
1.433
3147623JAMES R
Solar/Wind Harmer
0.311
316494AC1-189 GEN
Solar/Wind Harmer
0.453
961671AG1-007 GEN
Solar/Wind Harmer
0.02
3146083TARBORO
Solar/Wind Harmer
0.134
3145493TOT1
Solar/Wind Harmer
0.595
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.107
316359AB2-059 GEN
Solar/Wind Harmer
0.48
316049AB1-081 GEN
Solar/Wind Harmer
0.765
3142053HEARTS
Solar/Wind Harmer
0.235
3145336SMITFLD
Solar/Wind Harmer
0.528
316003AC1-222 GEN
Solar/Wind Harmer
0.003
3150851SPRUNCC
Adder
0.601
3151171GRAVELC
Adder
1.335
315671AE2-027_GEN
Solar/Wind Harmer
7.939
961611AG1-000B GEN
Solar/Wind Harmer
6.453
971647AH1-324 GEN
Solar/Wind Harmer
5.166
971069AG2-661 GEN
Solar/Wind Harmer
2.09
316458AB2-190 GEN2
Solar/Wind Harmer
0.619
970129AG2-093 GEN
Solar/Wind Harmer
3.27
3152261N ANNA2
50/50
35.375
3151771S ANNAG1
50/50
1.098
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
42.002
972183AH1-676 GEN
50/50
328.628
3151031BRUNSWICKG2
50/50
2.568
316044AC1-158 PL1
Solar/Wind Harmer
3.595
316450AC1-158 RIC
Solar/Wind Harmer
0.958
3147666LOUISA
Solar/Wind Harmer
1.12
3132273ORANGE
Solar/Wind Harmer
0.054
316170AC1-121 GEN2
Solar/Wind Harmer
0.236
316313AB2-026
Solar/Wind Harmer
0.12
316258AE1-075 C
Solar/Wind Harmer
0.144
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.888
970917AG2-570 GEN
Solar/Wind Harmer
16.604
316478AD1-087 GEN
Solar/Wind Harmer
0.59
316486AD2-202 GEN
Solar/Wind Harmer
0.173
970909AG2-566 GEN
Solar/Wind Harmer
1.755
3146926FARMVIL
Solar/Wind Harmer
0.095
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.486
971193AH1-056 GEN
Solar/Wind Harmer
9.427
963181AG1-167 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
316365GEN2_N
Solar/Wind Harmer
0.345
959311AF2-222 GEN
Solar/Wind Harmer
13.6
3146776BUCKING
Solar/Wind Harmer
0.055
970257AG2-171 GEN
Solar/Wind Harmer
4.889
315785AD2-033 C
Solar/Wind Harmer
1.239
3147043LAWRENC
Solar/Wind Harmer
0.091
964241AG1-285 GEN
Solar/Wind Harmer
10.109
316131AB2-060 GEN
Solar/Wind Harmer
0.475
313506AB2-031 GEN
Solar/Wind Harmer
0.461
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
944581AF1-123 GEN
Solar/Wind Harmer
32.61
944601AF1-125 GEN
Solar/Wind Harmer
32.107
3145796HORNRTN
Solar/Wind Harmer
0.577
3145796HORNRTN
Solar/Wind Harmer
0.144
3156081AA2-088 GEN
Solar/Wind Harmer
0.003
3146456SLIGO L269
Solar/Wind Harmer
0.143
971153AH1-033 GEN
Solar/Wind Harmer
1.656
315773AC2-141 GEN
Solar/Wind Harmer
5.232
3145893MURPHYS
Solar/Wind Harmer
0.239
3145893MURPHYS
Solar/Wind Harmer
0.143
3145273HOLLAND
Solar/Wind Harmer
0.107
316320Y1-086
Solar/Wind Harmer
0.001
957521AF2-046 GEN
Solar/Wind Harmer
10.626
961681AG1-008 GEN
Solar/Wind Harmer
10.626
3146263WOODLND
Solar/Wind Harmer
0.143
3151101ELIZAR3
Adder
13.236
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3144873MCLAUGH
Solar/Wind Harmer
0.004
3146626S HERTFORD
Solar/Wind Harmer
0.142
316463AE2-346 GEN
Solar/Wind Harmer
0.122
316140AB2-099
Solar/Wind Harmer
0.051
962331AG1-082 GEN
Solar/Wind Harmer
1.513
3146376EDENTON
Solar/Wind Harmer
0.142
315614AA2-178 GEN
Solar/Wind Harmer
0.807
3156021HOLLOMANSOL
Solar/Wind Harmer
0.639
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.141
970661AG2-428 GEN
Solar/Wind Harmer
2.977
3146206CASHIE
Solar/Wind Harmer
0.14
971157AH1-035 GEN
Solar/Wind Harmer
1.687
315737AD1-076 GEN
Solar/Wind Harmer
1.808
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.483
316210AC1-098 GEN
Solar/Wind Harmer
1.296
315813AE1-149 C
Solar/Wind Harmer
7.439
3144536CHRHLND
Solar/Wind Harmer
0.021
315724AD1-057 GEN
Solar/Wind Harmer
0.519
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.888
3145963POPLR C
Solar/Wind Harmer
0.138
316327AA2-057 GEN
Solar/Wind Harmer
0.207
3145933PARMELE
Solar/Wind Harmer
0.135
966801AG1-551 GEN
Solar/Wind Harmer
1.578
3146233WITAKRS
Solar/Wind Harmer
0.679
3146233WITAKRS
Solar/Wind Harmer
0.092
3138543CONSLDL
Solar/Wind Harmer
0.089
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970221AG2-151 GEN
Solar/Wind Harmer
7.167
3146073TAR RVR
Solar/Wind Harmer
0.134
3146083TARBORO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
3145543BTLEBRO
Solar/Wind Harmer
0.134
971623AH1-311 GEN
Solar/Wind Harmer
0.267
961601AG1-000A GEN
Solar/Wind Harmer
9.498
315839AE2-212 C
Solar/Wind Harmer
0.001
3145336SMITFLD
Solar/Wind Harmer
0.053
3150861SPRUNCD
Adder
0.601
965281AG1-393 GEN
Solar/Wind Harmer
1.359
3151221GRAVEL6
Adder
9.127
3151171GRAVELC
Adder
1.756
971683AH1-343 GEN
Solar/Wind Harmer
4.614
961611AG1-000B GEN
Solar/Wind Harmer
3.281
316283AC2-100 C
Solar/Wind Harmer
0.239
315778AD1-151 GEN
Solar/Wind Harmer
9.406
970129AG2-093 GEN
Solar/Wind Harmer
6.948
971133AH1-012 GEN
50/50
10.055
3151731LOISA B
50/50
20.602
3151721LOISA A
50/50
20.496
970533AG2-339 GEN
50/50
18.118
970531AG2-338 GEN
50/50
7.247
315242AE2-183_GT2
50/50
3.266
315241AE2-183_GT1
50/50
3.246
972185AH1-677 GEN
50/50
11.773
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.893
316447AC1-158 HLD
Solar/Wind Harmer
7.902
966001AG1-469 GEN
Solar/Wind Harmer
0.166
971223AH1-071 GEN
Solar/Wind Harmer
2.353
970933AG2-581 GEN
Solar/Wind Harmer
15.316
315651AD1-115 GEN
Solar/Wind Harmer
0.006
3143526WINTERP
Solar/Wind Harmer
0.921
970099AG2-077 GEN
Solar/Wind Harmer
18.895
3144356SAPONY
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
16.521
970301AG2-198 GEN
Solar/Wind Harmer
7.019
3147133PAMPLIN
Solar/Wind Harmer
0.155
3147133PAMPLIN
Solar/Wind Harmer
0.124
958211AF2-115 GEN
Solar/Wind Harmer
1.852
963191AG1-168 GEN
Solar/Wind Harmer
0.617
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.414
3146776BUCKING
Solar/Wind Harmer
0.611
3146776BUCKING
Solar/Wind Harmer
0.049
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.518
971775AH1-396 GEN
Solar/Wind Harmer
0.244
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.211
316181AB2-040 GEN
Solar/Wind Harmer
0.216
3145593CAROLNA
Solar/Wind Harmer
0.146
3145593CAROLNA
Solar/Wind Harmer
0.146
966811AG1-552 GEN
Solar/Wind Harmer
1.582
3145593CAROLNA
Solar/Wind Harmer
0.182
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.145
3142666NORTHAMPTON
Solar/Wind Harmer
0.087
316426AA2-053 GEN
Solar/Wind Harmer
0.49
3145783HORNRTN
Solar/Wind Harmer
2.577
3145783HORNRTN
Solar/Wind Harmer
2.062
3145783HORNRTN
Solar/Wind Harmer
0.644
3145783HORNRTN
Solar/Wind Harmer
0.258
962561AG1-105 GEN
Solar/Wind Harmer
6.941
3145796HORNRTN
Solar/Wind Harmer
0.432
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.344
3145506HICKORY
Solar/Wind Harmer
0.086
316185AD1-033 GEN
Solar/Wind Harmer
0.004
964791AG1-342 GEN
Solar/Wind Harmer
2.754
316339AD2-160 GEN
Solar/Wind Harmer
0.233
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.08
3137176SLIGO L2192
Solar/Wind Harmer
0.57
3146456SLIGO L269
Solar/Wind Harmer
2.535
3130086AYDLETT
Solar/Wind Harmer
0.573
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.957
3145893MURPHYS
Solar/Wind Harmer
0.257
3142956BIRDNECK
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.143
316316AC1-027 C
Solar/Wind Harmer
0.137
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146516WINFALL
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
3146173TUNIS
Solar/Wind Harmer
0.142
316036AC1-147 C
Solar/Wind Harmer
0.026
3150991CHESPKB
Adder
1.49
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146626S HERTFORD
Solar/Wind Harmer
0.142
3146376EDENTON
Solar/Wind Harmer
0.63
3146376EDENTON
Solar/Wind Harmer
0.63
316065AD1-022 GEN
Solar/Wind Harmer
6.472
970657AG2-426 GEN
Solar/Wind Harmer
4.92
970657AG2-426 GEN
Solar/Wind Harmer
1.032
316274AC1-208 GEN
Solar/Wind Harmer
0.727
3145933PARMELE
Solar/Wind Harmer
0.271
3145933PARMELE
Solar/Wind Harmer
0.135
971489AH1-241 GEN
Solar/Wind Harmer
7.167
3145493TOT1
Solar/Wind Harmer
0.31
3145453TOT5
Solar/Wind Harmer
0.186
3145603CNETO
Solar/Wind Harmer
0.124
316263AC1-034 GEN
Solar/Wind Harmer
5.078
961601AG1-000A GEN
Solar/Wind Harmer
2.374
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.509
316240AF1-291 C
Solar/Wind Harmer
0.001
316033AB2-134 GEN
Solar/Wind Harmer
0.007
315697AD1-025 GEN
Solar/Wind Harmer
0.134
944641AF1-129 GEN
Adder
56.042
316303AF2-085
50/50
3.922
315244AE2-183_ST
50/50
5.646
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
0.44
3147346CASHSCORNER
Solar/Wind Harmer
0.637
941031AE2-094 GEN
Solar/Wind Harmer
37.541
944011AF1-069 GEN
Solar/Wind Harmer
12.266
970673AG2-436 GEN
Solar/Wind Harmer
42.616
970673AG2-436 GEN
Solar/Wind Harmer
28.411
971967AH1-528 GEN
Solar/Wind Harmer
31.505
970085AG2-068 GEN
Solar/Wind Harmer
9.914
970581AG2-369 GEN
Solar/Wind Harmer
8.526
316233AE1-074 FULL
Solar/Wind Harmer
0.142
971281AH1-106 GEN
Solar/Wind Harmer
2.458
971283AH1-107 GEN
Solar/Wind Harmer
2.458
316315AB2-025 C
Solar/Wind Harmer
0.135
315814AE2-033 C
Solar/Wind Harmer
13.201
315657AE1-056 GEN
Solar/Wind Harmer
5.34
946301AF1-294 GEN
Solar/Wind Harmer
3.045
961791AG1-021 GEN
Solar/Wind Harmer
1.481
970285AG2-188 GEN
Solar/Wind Harmer
12.195
970683AG2-441 GEN
Solar/Wind Harmer
10.238
970681AG2-440 GEN
Solar/Wind Harmer
8.19
971845AH1-439 GEN
Solar/Wind Harmer
6.951
3144303KENBRDG
Solar/Wind Harmer
0.122
971443AH1-215 GEN
Solar/Wind Harmer
2.566
3143316POE
Solar/Wind Harmer
0.596
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316087AB2-174 GEN
Solar/Wind Harmer
0.004
970831AG2-522 GEN
Solar/Wind Harmer
6.33
3137643SOCKMAN
Solar/Wind Harmer
0.589
972205AH1-687 GEN
Adder
6.271
315652AC1-086 GEN
Solar/Wind Harmer
16.059
315607AA1-063A GEN
Solar/Wind Harmer
0.296
3146043SEABORD
Solar/Wind Harmer
0.145
3145796HORNRTN
Solar/Wind Harmer
0.461
3145796HORNRTN
Solar/Wind Harmer
0.058
965291AG1-394 GEN
Solar/Wind Harmer
0.639
957871AF2-081 GEN
Solar/Wind Harmer
7.137
319010AE1-072 C
Solar/Wind Harmer
0.721
3146406KITTY HAWK
Solar/Wind Harmer
0.018
3145893MURPHYS
Solar/Wind Harmer
0.386
3145893MURPHYS
Solar/Wind Harmer
0.143
313526AB2-022
Solar/Wind Harmer
0.077
316305AF2-043 C
Solar/Wind Harmer
0.001
316321Z2-027
Solar/Wind Harmer
0.027
3146396TANGLEW
Solar/Wind Harmer
0.393
3145176PASQUOTANK
Solar/Wind Harmer
0.088
3151081ELIZAR1
Adder
13.069
3151091ELIZAR2
Adder
12.842
3146486SUNBURY
Solar/Wind Harmer
0.142
3146486SUNBURY
Solar/Wind Harmer
0.142
315835AF2-110_GEN
Solar/Wind Harmer
0.978
3152611GOSPORTB
Adder
1.811
3152621GOSPORTC
Adder
1.537
3152601GOSPORTA
Adder
1.418
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3145513AHOSKIE
Solar/Wind Harmer
0.297
3145513AHOSKIE
Solar/Wind Harmer
0.142
316311AC2-079 GEN
Solar/Wind Harmer
4.069
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.097
3130156CHOWAN
Solar/Wind Harmer
0.142
3130156CHOWAN
Solar/Wind Harmer
0.142
3145683EARLEYS
Solar/Wind Harmer
0.283
3145683EARLEYS
Solar/Wind Harmer
0.141
3145683EARLEYS
Solar/Wind Harmer
0.141
315816AE2-034 GEN
Solar/Wind Harmer
0.605
316118AC1-105 GEN
Solar/Wind Harmer
0.363
3146206CASHIE
Solar/Wind Harmer
0.14
970601AG2-382 GEN
Solar/Wind Harmer
5.25
3130546PLYMOUTH
Solar/Wind Harmer
0.14
315732AD1-074 GEN1
Solar/Wind Harmer
0.807
315733AD1-074 GEN2
Solar/Wind Harmer
0.807
315735AD1-075 GEN1
Solar/Wind Harmer
0.404
3146033SCOT NK
Solar/Wind Harmer
0.56
3147173SINAI
Solar/Wind Harmer
0.138
3147243WELCO
Solar/Wind Harmer
0.086
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.535
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
3145746EVERETS
Solar/Wind Harmer
0.134
970181AG2-120 GEN
Solar/Wind Harmer
1.673
957861AF2-080 GEN
Solar/Wind Harmer
5.784
316420AA1-050 GEN
Solar/Wind Harmer
0.004
3145573BETHELC
Solar/Wind Harmer
0.134
3145573BETHELC
Solar/Wind Harmer
0.134
971445AH1-216 GEN
Solar/Wind Harmer
9.249
971285AH1-108 GEN
Adder
0.983
971447AH1-217 GEN
Solar/Wind Harmer
3.898
972265AH1-717 GEN
Adder
9.747
3151201GRAVEL4
Adder
9.137
3151191GRAVEL3
Adder
9.022
3151211GRAVEL5
Adder
9.022
970865AG2-541 GEN
Solar/Wind Harmer
4.136
316369SG1_INVT
Solar/Wind Harmer
0.004
316132AB2-190 GEN1
Solar/Wind Harmer
0.619
270494AE1-108_GEN
Solar/Wind Harmer
1.368
NYPJM->LTFIMP_NY
CLTF
2.592
LGEELTFEXP_LGEE->PJM
CLTF
0.801
LAGNLTFEXP_LAGN->PJM
CLTF
5.7
WECLTFEXP_WEC->PJM
CLTF
0.384
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
TVALTFEXP_TVA->PJM
CLTF
2.869
CPLELTFEXP_CPLE->PJM
CLTF
9.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.621
MECLTFEXP_MEC->PJM
CLTF
2.309
SIGELTFEXP_SIGE->PJM
CLTF
0.069

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 573_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:147.45 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:4748.6
MW Contribution:8.96
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
36.46
3151791S ANNAG2
50/50
1.04
3151781S ANNAS1
50/50
0.534
3151741LOISA C
50/50
1.06
3151751LOISA D
50/50
19.381
970119AG2-088 GEN
50/50
30.855
315243AE2-183_GT3
50/50
3.43
3151051BRUNSWICKS1
50/50
5.597
3151021BRUNSWICKG1
50/50
2.697
971451AH1-221 GEN
50/50
8.191
3152261N ANNA2
50/50
36.457
3151771S ANNAG1
50/50
1.04
3151801S ANNAS2
50/50
0.534
3151761LOISA E
50/50
39.513
972183AH1-676 GEN
50/50
307.587
3151031BRUNSWICKG2
50/50
2.697
3147666LOUISA
Solar/Wind Harmer
1.117
316313AB2-026
Solar/Wind Harmer
0.125
316258AE1-075 C
Solar/Wind Harmer
0.15
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
3.006
970917AG2-570 GEN
Solar/Wind Harmer
17.445
316478AD1-087 GEN
Solar/Wind Harmer
0.619
316486AD2-202 GEN
Solar/Wind Harmer
0.182
970909AG2-566 GEN
Solar/Wind Harmer
1.827
3146926FARMVIL
Solar/Wind Harmer
0.098
316365GEN2_N
Solar/Wind Harmer
0.365
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3147133PAMPLIN
Solar/Wind Harmer
0.506
971193AH1-056 GEN
Solar/Wind Harmer
9.82
963181AG1-167 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3147043LAWRENC
Solar/Wind Harmer
0.096
959311AF2-222 GEN
Solar/Wind Harmer
14.213
970257AG2-171 GEN
Solar/Wind Harmer
5.111
315785AD2-033 C
Solar/Wind Harmer
1.297
964241AG1-285 GEN
Solar/Wind Harmer
10.591
316131AB2-060 GEN
Solar/Wind Harmer
0.498
313506AB2-031 GEN
Solar/Wind Harmer
0.487
3146776BUCKING
Solar/Wind Harmer
0.057
944581AF1-123 GEN
Solar/Wind Harmer
34.771
944601AF1-125 GEN
Solar/Wind Harmer
34.236
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3132273ORANGE
Solar/Wind Harmer
0.031
315773AC2-141 GEN
Solar/Wind Harmer
5.584
3146456SLIGO L269
Solar/Wind Harmer
0.153
971153AH1-033 GEN
Solar/Wind Harmer
1.766
3145796HORNRTN
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.152
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
316320Y1-086
Solar/Wind Harmer
0.001
3151101ELIZAR3
Adder
14.124
3145273HOLLAND
Solar/Wind Harmer
0.114
3144873MCLAUGH
Solar/Wind Harmer
0.004
316435W1029_GEN3
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.254
3145893MURPHYS
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
957521AF2-046 GEN
Solar/Wind Harmer
11.271
961681AG1-008 GEN
Solar/Wind Harmer
11.271
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.151
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
962331AG1-082 GEN
Solar/Wind Harmer
1.604
970661AG2-428 GEN
Solar/Wind Harmer
3.178
971133AH1-012 GEN
50/50
10.162
3151731LOISA B
50/50
19.381
3151721LOISA A
50/50
19.281
970533AG2-339 GEN
50/50
19.027
970531AG2-338 GEN
50/50
7.611
315242AE2-183_GT2
50/50
3.43
315241AE2-183_GT1
50/50
3.409
972185AH1-677 GEN
50/50
12.365
3151041BRUNSWICKG3
50/50
2.697
972187AH1-678 GEN
50/50
6.189
966001AG1-469 GEN
Solar/Wind Harmer
0.142
971223AH1-071 GEN
Solar/Wind Harmer
2.468
970933AG2-581 GEN
Solar/Wind Harmer
16.076
3143526WINTERP
Solar/Wind Harmer
0.974
970099AG2-077 GEN
Solar/Wind Harmer
19.819
3144356SAPONY
Solar/Wind Harmer
1.482
971741AH1-377 GEN
Solar/Wind Harmer
17.227
970301AG2-198 GEN
Solar/Wind Harmer
7.308
3147133PAMPLIN
Solar/Wind Harmer
0.161
3147133PAMPLIN
Solar/Wind Harmer
0.129
958211AF2-115 GEN
Solar/Wind Harmer
1.931
963191AG1-168 GEN
Solar/Wind Harmer
0.644
3144293JTRSVLE
Adder
0.512
3144293JTRSVLE
Adder
0.431
316034AC1-036 C
Solar/Wind Harmer
0.012
970323AG2-213 GEN
Solar/Wind Harmer
6.815
971775AH1-396 GEN
Solar/Wind Harmer
0.256
313527AB2-043 GEN
Solar/Wind Harmer
0.002
939181AE1-148 GEN
Solar/Wind Harmer
7.578
316181AB2-040 GEN
Solar/Wind Harmer
0.229
3146776BUCKING
Solar/Wind Harmer
0.63
3146776BUCKING
Solar/Wind Harmer
0.051
3145593CAROLNA
Solar/Wind Harmer
0.154
3145593CAROLNA
Solar/Wind Harmer
0.154
966811AG1-552 GEN
Solar/Wind Harmer
1.673
3145593CAROLNA
Solar/Wind Harmer
0.192
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.154
3142666NORTHAMPTON
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.518
3145783HORNRTN
Solar/Wind Harmer
2.725
3145783HORNRTN
Solar/Wind Harmer
2.18
3145783HORNRTN
Solar/Wind Harmer
0.681
3145783HORNRTN
Solar/Wind Harmer
0.273
316185AD1-033 GEN
Solar/Wind Harmer
0.004
3145506HICKORY
Solar/Wind Harmer
0.612
3145506HICKORY
Solar/Wind Harmer
0.367
3145506HICKORY
Solar/Wind Harmer
0.092
316339AD2-160 GEN
Solar/Wind Harmer
0.248
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.085
3137176SLIGO L2192
Solar/Wind Harmer
0.608
3146456SLIGO L269
Solar/Wind Harmer
2.703
3130086AYDLETT
Solar/Wind Harmer
0.61
3145796HORNRTN
Solar/Wind Harmer
0.458
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.146
3146386ELIZ CT
Solar/Wind Harmer
0.152
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316036AC1-147 C
Solar/Wind Harmer
0.028
3150991CHESPKB
Adder
1.59
3150991CHESPKB
Adder
1.552
962561AG1-105 GEN
Solar/Wind Harmer
7.287
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
1.015
3145893MURPHYS
Solar/Wind Harmer
0.273
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146516WINFALL
Solar/Wind Harmer
0.152
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146626S HERTFORD
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3146376EDENTON
Solar/Wind Harmer
0.67
3146376EDENTON
Solar/Wind Harmer
0.67
964791AG1-342 GEN
Solar/Wind Harmer
2.892
3146843MT LREL
Solar/Wind Harmer
0.15
3147666LOUISA
Solar/Wind Harmer
1.943
316192AB2-158 GEN
Solar/Wind Harmer
2.682
3143226MDLTHAN
Solar/Wind Harmer
0.231
940641AE2-051 GEN
Solar/Wind Harmer
16.781
3143336POWHATN
Solar/Wind Harmer
3.536
970919AG2-571 GEN
Solar/Wind Harmer
6.978
939411AE1-173 GEN
Solar/Wind Harmer
83.474
970087AG2-069 GEN
Solar/Wind Harmer
15.624
316336AC2-165 C
Solar/Wind Harmer
0.007
3143526WINTERP
Solar/Wind Harmer
0.974
957481AF2-042 GEN
Solar/Wind Harmer
49.548
315693AD1-088 GEN
Solar/Wind Harmer
8.718
962491AG1-098 GEN
Solar/Wind Harmer
10.335
970937AG2-583 GEN
Solar/Wind Harmer
10.339
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3146926FARMVIL
Solar/Wind Harmer
0.098
316023GEN1_S
Solar/Wind Harmer
0.365
963171AG1-166 GEN
Solar/Wind Harmer
0.858
971563AH1-280 GEN
Solar/Wind Harmer
1.716
3144293JTRSVLE
Adder
0.512
960081AF2-299 GEN
Solar/Wind Harmer
1.543
970685AG2-442 GEN
Solar/Wind Harmer
11.971
971795AH1-408 GEN
Solar/Wind Harmer
10.682
3147043LAWRENC
Adder
1.448
316237AB2-079_GEN
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.063
971065AG2-659 GEN
Solar/Wind Harmer
6.688
316129AC1-054 GEN
Solar/Wind Harmer
0.589
316011AB1-132 GEN
Solar/Wind Harmer
2.809
315614AA2-178 GEN
Solar/Wind Harmer
0.858
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970659AG2-427 GEN
Solar/Wind Harmer
1.584
3156021HOLLOMANSOL
Solar/Wind Harmer
0.678
971157AH1-035 GEN
Solar/Wind Harmer
1.793
3146206CASHIE
Solar/Wind Harmer
0.149
315737AD1-076 GEN
Solar/Wind Harmer
1.921
316317KELFORD C
Solar/Wind Harmer
0.014
3145823KELFORD
Solar/Wind Harmer
0.149
315813AE1-149 C
Solar/Wind Harmer
7.948
3144536CHRHLND
Solar/Wind Harmer
0.022
316210AC1-098 GEN
Solar/Wind Harmer
1.371
315724AD1-057 GEN
Solar/Wind Harmer
0.549
3145963POPLR C
Solar/Wind Harmer
0.146
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.188
316327AA2-057 GEN
Solar/Wind Harmer
0.219
3145933PARMELE
Solar/Wind Harmer
0.144
966801AG1-551 GEN
Solar/Wind Harmer
1.673
3146233WITAKRS
Solar/Wind Harmer
0.718
3146233WITAKRS
Solar/Wind Harmer
0.097
3138543CONSLDL
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
315839AE2-212 C
Solar/Wind Harmer
0.001
3146073TAR RVR
Solar/Wind Harmer
0.142
3146083TARBORO
Solar/Wind Harmer
0.142
3145336SMITFLD
Solar/Wind Harmer
0.057
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
961601AG1-000A GEN
Solar/Wind Harmer
10.046
3150861SPRUNCD
Adder
0.645
970221AG2-151 GEN
Solar/Wind Harmer
7.325
965281AG1-393 GEN
Solar/Wind Harmer
1.459
3151221GRAVEL6
Adder
9.808
3151171GRAVELC
Adder
1.887
961611AG1-000B GEN
Solar/Wind Harmer
3.53
971683AH1-343 GEN
Solar/Wind Harmer
4.854
316283AC2-100 C
Solar/Wind Harmer
0.252
315778AD1-151 GEN
Solar/Wind Harmer
10.15
970129AG2-093 GEN
Solar/Wind Harmer
7.509
3144216WINCHST
Adder
0.455
970133AG2-095 GEN
Solar/Wind Harmer
1.157
3150921YORKTN3
Adder
2.978
3146843MT LREL
Solar/Wind Harmer
0.15
970657AG2-426 GEN
Solar/Wind Harmer
5.253
970657AG2-426 GEN
Solar/Wind Harmer
1.101
316065AD1-022 GEN
Solar/Wind Harmer
6.875
316274AC1-208 GEN
Solar/Wind Harmer
0.769
3145933PARMELE
Solar/Wind Harmer
0.287
3145933PARMELE
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.328
3145453TOT5
Solar/Wind Harmer
0.197
3145603CNETO
Solar/Wind Harmer
0.131
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316263AC1-034 GEN
Solar/Wind Harmer
5.37
961601AG1-000A GEN
Solar/Wind Harmer
2.512
971489AH1-241 GEN
Solar/Wind Harmer
7.325
316240AF1-291 C
Solar/Wind Harmer
0.001
316222AC1-221 GEN
Solar/Wind Harmer
0.537
316033AB2-134 GEN
Solar/Wind Harmer
0.008
315697AD1-025 GEN
Solar/Wind Harmer
0.144
944641AF1-129 GEN
Adder
60.502
316303AF2-085
50/50
4.114
315244AE2-183_ST
50/50
5.93
963041AG1-153 GEN
50/50
5.461
3147346CASHSCORNER
Solar/Wind Harmer
0.597
941031AE2-094 GEN
Solar/Wind Harmer
39.425
944011AF1-069 GEN
Solar/Wind Harmer
12.882
970673AG2-436 GEN
Solar/Wind Harmer
44.756
970673AG2-436 GEN
Solar/Wind Harmer
29.837
971967AH1-528 GEN
Solar/Wind Harmer
33.079
970085AG2-068 GEN
Solar/Wind Harmer
10.416
970581AG2-369 GEN
Solar/Wind Harmer
8.958
316233AE1-074 FULL
Solar/Wind Harmer
0.15
971281AH1-106 GEN
Solar/Wind Harmer
2.6
971283AH1-107 GEN
Solar/Wind Harmer
2.6
316315AB2-025 C
Solar/Wind Harmer
0.143
315814AE2-033 C
Solar/Wind Harmer
13.959
315657AE1-056 GEN
Solar/Wind Harmer
5.562
946301AF1-294 GEN
Solar/Wind Harmer
3.175
961791AG1-021 GEN
Solar/Wind Harmer
1.544
3143316POE
Solar/Wind Harmer
0.635
970683AG2-441 GEN
Solar/Wind Harmer
10.688
970681AG2-440 GEN
Solar/Wind Harmer
8.55
3144303KENBRDG
Solar/Wind Harmer
0.128
971443AH1-215 GEN
Solar/Wind Harmer
2.682
970285AG2-188 GEN
Solar/Wind Harmer
12.58
316087AB2-174 GEN
Solar/Wind Harmer
0.005
971845AH1-439 GEN
Solar/Wind Harmer
7.164
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
970831AG2-522 GEN
Solar/Wind Harmer
6.67
3137643SOCKMAN
Solar/Wind Harmer
0.622
315652AC1-086 GEN
Solar/Wind Harmer
16.994
315607AA1-063A GEN
Solar/Wind Harmer
0.314
962571AG1-106 GEN
Solar/Wind Harmer
2.198
944591AF1-124 GEN
Solar/Wind Harmer
34.895
316190AA2-174 GEN
Solar/Wind Harmer
0
3145783HORNRTN
Solar/Wind Harmer
0.153
316388AE2-253 GEN
Solar/Wind Harmer
0.479
316294AC1-161 GEN
Solar/Wind Harmer
2.649
3146456SLIGO L269
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.503
3145796HORNRTN
Solar/Wind Harmer
0.152
315683AE1-153 C
Solar/Wind Harmer
12.128
316246AF1-032 C
Solar/Wind Harmer
0.069
316093AE2-104_GEN
Solar/Wind Harmer
2.556
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
1.895
3145893MURPHYS
Solar/Wind Harmer
0.607
3145893MURPHYS
Solar/Wind Harmer
0.674
3146516WINFALL
Solar/Wind Harmer
0.491
3146516WINFALL
Solar/Wind Harmer
0.152
972003AH1-546 GEN
Solar/Wind Harmer
6.434
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146263WOODLND
Solar/Wind Harmer
0.151
3146173TUNIS
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
970401AG2-262 GEN
Solar/Wind Harmer
0.884
970661AG2-428 GEN
Solar/Wind Harmer
14.943
3145683EARLEYS
Solar/Wind Harmer
0.15
3145663CRESWEL
Solar/Wind Harmer
0.42
971163AH1-040 GEN
Solar/Wind Harmer
11.998
316381AD1-082 GEN
Solar/Wind Harmer
0.156
970659AG2-427 GEN
Solar/Wind Harmer
7.24
3146206CASHIE
Solar/Wind Harmer
0.149
971547AH1-271 GEN
Solar/Wind Harmer
3.186
3145823KELFORD
Solar/Wind Harmer
0.149
316212AC1-099_GEN
Solar/Wind Harmer
0.765
316072AD1-144
Solar/Wind Harmer
0.053
315722AD1-056 GEN
Solar/Wind Harmer
0.927
3145963POPLR C
Solar/Wind Harmer
0.146
316174AB2-169 GEN
Solar/Wind Harmer
0.004
3146293MARTNCO
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
0.569
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
316494AC1-189 GEN
Solar/Wind Harmer
0.48
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.142
3145493TOT1
Solar/Wind Harmer
0.63
3145336SMITFLD
Solar/Wind Harmer
0.565
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
3150851SPRUNCC
Adder
0.645
316003AC1-222 GEN
Solar/Wind Harmer
0.004
971377AH1-170 GEN
Solar/Wind Harmer
1.465
3147623JAMES R
Solar/Wind Harmer
0.318
3151171GRAVELC
Adder
1.435
315671AE2-027_GEN
Solar/Wind Harmer
8.542
961611AG1-000B GEN
Solar/Wind Harmer
6.943
971647AH1-324 GEN
Solar/Wind Harmer
5.564
971069AG2-661 GEN
Solar/Wind Harmer
2.256
316458AB2-190 GEN2
Solar/Wind Harmer
0.669
970129AG2-093 GEN
Solar/Wind Harmer
3.534
3138126ROCKLANDING
Solar/Wind Harmer
0.055
3142543TWELFTH
Solar/Wind Harmer
0.011
3146043SEABORD
Solar/Wind Harmer
0.153
957871AF2-081 GEN
Solar/Wind Harmer
7.61
319010AE1-072 C
Solar/Wind Harmer
0.769
3146406KITTY HAWK
Solar/Wind Harmer
0.019
3145796HORNRTN
Solar/Wind Harmer
0.488
3145796HORNRTN
Solar/Wind Harmer
0.061
965291AG1-394 GEN
Solar/Wind Harmer
0.678
313526AB2-022
Solar/Wind Harmer
0.082
316305AF2-043 C
Solar/Wind Harmer
0.001
3151081ELIZAR1
Adder
13.946
3151091ELIZAR2
Adder
13.704
316321Z2-027
Solar/Wind Harmer
0.028
3146396TANGLEW
Solar/Wind Harmer
0.419
3145176PASQUOTANK
Solar/Wind Harmer
0.094
315835AF2-110_GEN
Solar/Wind Harmer
1.043
3146486SUNBURY
Solar/Wind Harmer
0.152
3146486SUNBURY
Solar/Wind Harmer
0.152
3152611GOSPORTB
Adder
1.933
3152621GOSPORTC
Adder
1.641
3152601GOSPORTA
Adder
1.513
3145893MURPHYS
Solar/Wind Harmer
0.41
3145893MURPHYS
Solar/Wind Harmer
0.152
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316311AC2-079 GEN
Solar/Wind Harmer
4.34
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.104
3130156CHOWAN
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
0.314
3145513AHOSKIE
Solar/Wind Harmer
0.15
972205AH1-687 GEN
Adder
6.411
3145683EARLEYS
Solar/Wind Harmer
0.3
3145683EARLEYS
Solar/Wind Harmer
0.15
3145683EARLEYS
Solar/Wind Harmer
0.15
315816AE2-034 GEN
Solar/Wind Harmer
0.644
3130546PLYMOUTH
Solar/Wind Harmer
0.149
3146206CASHIE
Solar/Wind Harmer
0.149
970601AG2-382 GEN
Solar/Wind Harmer
5.575
315732AD1-074 GEN1
Solar/Wind Harmer
0.858
315733AD1-074 GEN2
Solar/Wind Harmer
0.858
315735AD1-075 GEN1
Solar/Wind Harmer
0.429
3146033SCOT NK
Solar/Wind Harmer
0.593
316118AC1-105 GEN
Solar/Wind Harmer
0.382
3147173SINAI
Solar/Wind Harmer
0.145
3147243WELCO
Solar/Wind Harmer
0.091
316319Z2-044 C
Solar/Wind Harmer
0
316005AA1-067
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
0.567
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
3145746EVERETS
Solar/Wind Harmer
0.142
970181AG2-120 GEN
Solar/Wind Harmer
1.773
957861AF2-080 GEN
Solar/Wind Harmer
6.125
316420AA1-050 GEN
Solar/Wind Harmer
0.005
3145573BETHELC
Solar/Wind Harmer
0.142
3145573BETHELC
Solar/Wind Harmer
0.142
971445AH1-216 GEN
Solar/Wind Harmer
9.913
971285AH1-108 GEN
Adder
1.055
972265AH1-717 GEN
Adder
10.474
3151201GRAVEL4
Adder
9.819
3151191GRAVEL3
Adder
9.695
3151211GRAVEL5
Adder
9.695
971447AH1-217 GEN
Solar/Wind Harmer
3.983
316369SG1_INVT
Solar/Wind Harmer
0.005
970865AG2-541 GEN
Solar/Wind Harmer
4.353
316132AB2-190 GEN1
Solar/Wind Harmer
0.669
270494AE1-108_GEN
Solar/Wind Harmer
1.404
316123AC1-075 GEN
Solar/Wind Harmer
0.154
970165AG2-112 GEN
Solar/Wind Harmer
0.913
970163AG2-111 GEN
Solar/Wind Harmer
0.871
NYPJM->LTFIMP_NY
CLTF
2.601
LAGNLTFEXP_LAGN->PJM
CLTF
6.172
LGEELTFEXP_LGEE->PJM
CLTF
0.913
WECLTFEXP_WEC->PJM
CLTF
0.444
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.668
TVALTFEXP_TVA->PJM
CLTF
3.105
CPLELTFEXP_CPLE->PJM
CLTF
9.633
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.022
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.582
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.459
MECLTFEXP_MEC->PJM
CLTF
2.598
SIGELTFEXP_SIGE->PJM
CLTF
0.077

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: SPOTS H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: SPOTS H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.78 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5310.49
MW Contribution:11.73
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
10.157
3151731LOISA B
50/50
19.419
3151721LOISA A
50/50
19.318
970533AG2-339 GEN
50/50
18.931
970531AG2-338 GEN
50/50
7.573
315242AE2-183_GT2
50/50
3.412
315241AE2-183_GT1
50/50
3.391
316303AF2-085
50/50
4.096
315244AE2-183_ST
50/50
5.899
963041AG1-153 GEN
50/50
5.432
3147346CASHSCORNER
Solar/Wind Harmer
0.449
941031AE2-094 GEN
Solar/Wind Harmer
44.868
944011AF1-069 GEN
Solar/Wind Harmer
14.059
970673AG2-436 GEN
Solar/Wind Harmer
49.264
970673AG2-436 GEN
Solar/Wind Harmer
24.944
971967AH1-528 GEN
Solar/Wind Harmer
43.441
970085AG2-068 GEN
Solar/Wind Harmer
13.637
970581AG2-369 GEN
Solar/Wind Harmer
11.728
316233AE1-074 FULL
Solar/Wind Harmer
0.564
971281AH1-106 GEN
Solar/Wind Harmer
3.405
971283AH1-107 GEN
Solar/Wind Harmer
3.405
316315AB2-025 C
Solar/Wind Harmer
0.534
315814AE2-033 C
Solar/Wind Harmer
18.349
315657AE1-056 GEN
Solar/Wind Harmer
6.751
946301AF1-294 GEN
Solar/Wind Harmer
4.601
961791AG1-021 GEN
Solar/Wind Harmer
2.245
946281AF1-292 GEN
Solar/Wind Harmer
0.402
3143316POE
Solar/Wind Harmer
-0.07
970683AG2-441 GEN
Solar/Wind Harmer
13.979
970681AG2-440 GEN
Solar/Wind Harmer
11.183
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.508
970285AG2-188 GEN
Solar/Wind Harmer
15.538
316087AB2-174 GEN
Solar/Wind Harmer
2.524
971845AH1-439 GEN
Solar/Wind Harmer
9.375
316239AB2-077_GEN
Solar/Wind Harmer
0.531
3152261N ANNA2
50/50
36.414
3151771S ANNAG1
50/50
1.042
3151801S ANNAS2
50/50
0.535
3151761LOISA E
50/50
39.589
972183AH1-676 GEN
50/50
308.231
3151031BRUNSWICKG2
50/50
2.683
316044AC1-158 PL1
Solar/Wind Harmer
8.611
316450AC1-158 RIC
Solar/Wind Harmer
2.296
3147666LOUISA
Solar/Wind Harmer
-0.125
316313AB2-026
Solar/Wind Harmer
0.6
316258AE1-075 C
Solar/Wind Harmer
0.54
316405AF2-144 C
Solar/Wind Harmer
0.57
3143336POWHATN
Solar/Wind Harmer
2.243
970917AG2-570 GEN
Solar/Wind Harmer
54.816
316478AD1-087 GEN
Solar/Wind Harmer
1.715
316486AD2-202 GEN
Solar/Wind Harmer
0.502
970909AG2-566 GEN
Solar/Wind Harmer
1.816
3146926FARMVIL
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
1.225
942461AE2-259 GEN
Solar/Wind Harmer
2.724
3132273ORANGE
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.252
963181AG1-167 GEN
Solar/Wind Harmer
1.683
3144293JTRSVLE
Adder
0.509
966621AG1-532 GEN
Solar/Wind Harmer
0.364
3147043LAWRENC
Solar/Wind Harmer
-0.011
959311AF2-222 GEN
Solar/Wind Harmer
18.625
970257AG2-171 GEN
Solar/Wind Harmer
6.684
315785AD2-033 C
Solar/Wind Harmer
4.033
964241AG1-285 GEN
Solar/Wind Harmer
13.848
316131AB2-060 GEN
Solar/Wind Harmer
1.908
313506AB2-031 GEN
Solar/Wind Harmer
1.414
3146776BUCKING
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
78.382
944601AF1-125 GEN
Solar/Wind Harmer
77.158
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
315773AC2-141 GEN
Solar/Wind Harmer
7.138
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.077
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
3156081AA2-088 GEN
Solar/Wind Harmer
5.522
316320Y1-086
Solar/Wind Harmer
0.996
3151101ELIZAR3
Adder
14.024
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.067
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.305
961681AG1-008 GEN
Solar/Wind Harmer
13.305
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.272
316140AB2-099
Solar/Wind Harmer
0.113
962331AG1-082 GEN
Solar/Wind Harmer
2.097
970661AG2-428 GEN
Solar/Wind Harmer
3.155
315614AA2-178 GEN
Solar/Wind Harmer
1.805
316083AB2-161 GEN
Solar/Wind Harmer
2.713
970659AG2-427 GEN
Solar/Wind Harmer
1.572
3156021HOLLOMANSOL
Solar/Wind Harmer
2.245
971157AH1-035 GEN
Solar/Wind Harmer
2.083
3146206CASHIE
Solar/Wind Harmer
-0.017
3150861SPRUNCD
Adder
0.64
3152251N ANNA1
50/50
36.417
3151791S ANNAG2
50/50
1.042
3151781S ANNAS1
50/50
0.535
3151741LOISA C
50/50
1.062
3151751LOISA D
50/50
19.419
970119AG2-088 GEN
50/50
30.719
315243AE2-183_GT3
50/50
3.412
3151051BRUNSWICKS1
50/50
5.568
3151021BRUNSWICKG1
50/50
2.683
971451AH1-221 GEN
50/50
8.148
316045AC1-158 PL2
Solar/Wind Harmer
27.544
3147666LOUISA
Solar/Wind Harmer
-0.217
316192AB2-158 GEN
Solar/Wind Harmer
6.343
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
21.983
3143336POWHATN
Solar/Wind Harmer
2.639
970919AG2-571 GEN
Solar/Wind Harmer
6.939
939411AE1-173 GEN
Solar/Wind Harmer
109.306
970087AG2-069 GEN
Solar/Wind Harmer
20.456
316336AC2-165 C
Solar/Wind Harmer
3.699
3143526WINTERP
Solar/Wind Harmer
-0.108
957481AF2-042 GEN
Solar/Wind Harmer
64.853
315693AD1-088 GEN
Solar/Wind Harmer
10.143
962491AG1-098 GEN
Solar/Wind Harmer
13.526
970937AG2-583 GEN
Solar/Wind Harmer
13.537
315687AD1-152 GEN
Solar/Wind Harmer
2.221
3146926FARMVIL
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
1.225
963171AG1-166 GEN
Solar/Wind Harmer
2.245
971563AH1-280 GEN
Solar/Wind Harmer
2.245
3144293JTRSVLE
Adder
0.509
960081AF2-299 GEN
Solar/Wind Harmer
2.018
970685AG2-442 GEN
Solar/Wind Harmer
15.656
971795AH1-408 GEN
Solar/Wind Harmer
13.409
3147043LAWRENC
Adder
1.438
316237AB2-079_GEN
Solar/Wind Harmer
0.531
316322AB2-045
Solar/Wind Harmer
0.592
3146776BUCKING
Solar/Wind Harmer
-0.007
971065AG2-659 GEN
Solar/Wind Harmer
8.742
316129AC1-054 GEN
Solar/Wind Harmer
1.531
316011AB1-132 GEN
Solar/Wind Harmer
3.607
962571AG1-106 GEN
Solar/Wind Harmer
2.478
972185AH1-677 GEN
50/50
12.3
3151041BRUNSWICKG3
50/50
2.683
972187AH1-678 GEN
50/50
6.156
316447AC1-158 HLD
Solar/Wind Harmer
18.935
966001AG1-469 GEN
Solar/Wind Harmer
0.523
971223AH1-071 GEN
Solar/Wind Harmer
3.236
970933AG2-581 GEN
Solar/Wind Harmer
21.052
3143526WINTERP
Solar/Wind Harmer
-0.108
970099AG2-077 GEN
Solar/Wind Harmer
25.941
3144356SAPONY
Solar/Wind Harmer
0.69
971741AH1-377 GEN
Solar/Wind Harmer
22.545
970301AG2-198 GEN
Solar/Wind Harmer
9.564
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.806
944591AF1-124 GEN
Solar/Wind Harmer
78.664
315683AE1-153 C
Solar/Wind Harmer
15.955
316190AA2-174 GEN
Solar/Wind Harmer
0.21
3145783HORNRTN
Solar/Wind Harmer
-0.017
316388AE2-253 GEN
Solar/Wind Harmer
1.15
316294AC1-161 GEN
Solar/Wind Harmer
5.519
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.344
316093AE2-104_GEN
Solar/Wind Harmer
4.929
316375AC2-012 GEN
Solar/Wind Harmer
5.859
3150981CHESPKA
Adder
1.882
3146516WINFALL
Solar/Wind Harmer
-0.054
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.067
3145893MURPHYS
Solar/Wind Harmer
0.502
972003AH1-546 GEN
Solar/Wind Harmer
8.434
315800Z1-036_GEN1
Solar/Wind Harmer
4.166
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.096
970661AG2-428 GEN
Solar/Wind Harmer
17.805
3145663CRESWEL
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.017
971163AH1-040 GEN
Solar/Wind Harmer
15.681
316381AD1-082 GEN
Solar/Wind Harmer
1.533
970659AG2-427 GEN
Solar/Wind Harmer
8.872
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.163
3150851SPRUNCC
Adder
0.64
3151171GRAVELC
Adder
1.424
316238AB2-078_GEN
Solar/Wind Harmer
0.531
970831AG2-522 GEN
Solar/Wind Harmer
8.718
3137643SOCKMAN
Solar/Wind Harmer
-0.069
315652AC1-086 GEN
Solar/Wind Harmer
19.393
315607AA1-063A GEN
Solar/Wind Harmer
1.731
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.527
319010AE1-072 C
Solar/Wind Harmer
3.447
3146406KITTY HAWK
Solar/Wind Harmer
0.014
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
1.51
313526AB2-022
Solar/Wind Harmer
0.458
316305AF2-043 C
Solar/Wind Harmer
0.512
3151081ELIZAR1
Adder
13.847
3151091ELIZAR2
Adder
13.607
316321Z2-027
Solar/Wind Harmer
0.458
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.312
315835AF2-110_GEN
Solar/Wind Harmer
2.119
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.919
3152621GOSPORTC
Adder
1.629
3152601GOSPORTA
Adder
1.503
316318V4-068
Solar/Wind Harmer
0.422
3145893MURPHYS
Solar/Wind Harmer
-0.045
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.505
315611Z1-036_GEN2
Solar/Wind Harmer
4.166
315833AF1-017_GEN
Solar/Wind Harmer
3.202
316349AD2-085 GEN
Solar/Wind Harmer
1.5
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.146
961941AG1-037 GEN
Solar/Wind Harmer
0.126
3145513AHOSKIE
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.372
315816AE2-034 GEN
Solar/Wind Harmer
1.353
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.286
971285AH1-108 GEN
Adder
1.047
972265AH1-717 GEN
Adder
10.391
3151201GRAVEL4
Adder
9.741
3151191GRAVEL3
Adder
9.617
3151211GRAVEL5
Adder
9.617
315732AD1-074 GEN1
Solar/Wind Harmer
0.429
315733AD1-074 GEN2
Solar/Wind Harmer
0.429
315735AD1-075 GEN1
Solar/Wind Harmer
0.214
3151221GRAVEL6
Adder
9.73
3151171GRAVELC
Adder
1.872
3144216WINCHST
Adder
0.451
3150921YORKTN3
Adder
2.951
315737AD1-076 GEN
Solar/Wind Harmer
0.403
963191AG1-168 GEN
Solar/Wind Harmer
1.683
3144293JTRSVLE
Adder
0.509
3144293JTRSVLE
Adder
0.428
316034AC1-036 C
Solar/Wind Harmer
0.331
970323AG2-213 GEN
Solar/Wind Harmer
8.912
971775AH1-396 GEN
Solar/Wind Harmer
1.269
313527AB2-043 GEN
Solar/Wind Harmer
2.871
939181AE1-148 GEN
Solar/Wind Harmer
9.906
316181AB2-040 GEN
Solar/Wind Harmer
2.454
3146776BUCKING
Solar/Wind Harmer
-0.07
3146776BUCKING
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.936
3145593CAROLNA
Solar/Wind Harmer
0.143
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.73
3145783HORNRTN
Solar/Wind Harmer
2.029
3145783HORNRTN
Solar/Wind Harmer
1.623
3145783HORNRTN
Solar/Wind Harmer
0.507
3145783HORNRTN
Solar/Wind Harmer
0.203
316185AD1-033 GEN
Solar/Wind Harmer
1.801
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.15
316018AA1-139 ULT2
Solar/Wind Harmer
1.461
316017AA1-139 ULT1
Solar/Wind Harmer
1.38
3137176SLIGO L2192
Solar/Wind Harmer
-0.067
3146456SLIGO L269
Solar/Wind Harmer
2.013
3130086AYDLETT
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.051
3142956BIRDNECK
Solar/Wind Harmer
0.913
316316AC1-027 C
Solar/Wind Harmer
0.522
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315742AE1-103 GEN
Solar/Wind Harmer
1.775
316036AC1-147 C
Solar/Wind Harmer
0.457
3150991CHESPKB
Adder
1.578
3150991CHESPKB
Adder
1.541
316431W1029_GEN1
Solar/Wind Harmer
3.067
316433W1029_GEN2
Solar/Wind Harmer
3.067
962561AG1-105 GEN
Solar/Wind Harmer
9.523
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
-0.03
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
0.499
3146376EDENTON
Solar/Wind Harmer
0.499
964791AG1-342 GEN
Solar/Wind Harmer
3.588
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
5.229
970657AG2-426 GEN
Solar/Wind Harmer
1.093
316065AD1-022 GEN
Solar/Wind Harmer
8.326
944641AF1-129 GEN
Adder
59.993
NYPJM->LTFIMP_NY
CLTF
2.685
LGEELTFEXP_LGEE->PJM
CLTF
0.835
LAGNLTFEXP_LAGN->PJM
CLTF
5.952
WECLTFEXP_WEC->PJM
CLTF
0.4
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.368
TVALTFEXP_TVA->PJM
CLTF
2.995
CPLELTFEXP_CPLE->PJM
CLTF
9.529
CBM West 2LTFEXP_CBM-W2->PJM
CBM
29.532
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.913
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.044
MECLTFEXP_MEC->PJM
CLTF
2.409
SIGELTFEXP_SIGE->PJM
CLTF
0.072

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.91 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5157.73
MW Contribution:11.25
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
35.401
3151771S ANNAG1
50/50
1.115
3151801S ANNAS2
50/50
0.573
3151761LOISA E
50/50
42.735
972183AH1-676 GEN
50/50
334.654
3151031BRUNSWICKG2
50/50
2.573
316044AC1-158 PL1
Solar/Wind Harmer
8.144
316450AC1-158 RIC
Solar/Wind Harmer
2.171
3147666LOUISA
Solar/Wind Harmer
-0.126
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.691
316313AB2-026
Solar/Wind Harmer
0.581
316258AE1-075 C
Solar/Wind Harmer
0.523
316405AF2-144 C
Solar/Wind Harmer
0.552
3143336POWHATN
Solar/Wind Harmer
2.174
970917AG2-570 GEN
Solar/Wind Harmer
52.576
316478AD1-087 GEN
Solar/Wind Harmer
1.649
316486AD2-202 GEN
Solar/Wind Harmer
0.483
970909AG2-566 GEN
Solar/Wind Harmer
1.762
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.651
3147133PAMPLIN
Solar/Wind Harmer
-0.055
971193AH1-056 GEN
Solar/Wind Harmer
10.918
963181AG1-167 GEN
Solar/Wind Harmer
1.632
3144293JTRSVLE
Adder
0.493
316365GEN2_N
Solar/Wind Harmer
1.169
3146776BUCKING
Solar/Wind Harmer
-0.006
959311AF2-222 GEN
Solar/Wind Harmer
18.009
970257AG2-171 GEN
Solar/Wind Harmer
6.46
315785AD2-033 C
Solar/Wind Harmer
3.896
966621AG1-532 GEN
Solar/Wind Harmer
0.348
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.355
316131AB2-060 GEN
Solar/Wind Harmer
1.838
313506AB2-031 GEN
Solar/Wind Harmer
1.351
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
944581AF1-123 GEN
Solar/Wind Harmer
74.206
944601AF1-125 GEN
Solar/Wind Harmer
73.048
3145796HORNRTN
Solar/Wind Harmer
-0.065
316303AF2-085
50/50
3.93
315244AE2-183_ST
50/50
5.657
963041AG1-153 GEN
50/50
5.21
316164AC1-076 GEN
Solar/Wind Harmer
3.006
3147346CASHSCORNER
Solar/Wind Harmer
0.486
941031AE2-094 GEN
Solar/Wind Harmer
43.024
944011AF1-069 GEN
Solar/Wind Harmer
13.481
970673AG2-436 GEN
Solar/Wind Harmer
47.245
970673AG2-436 GEN
Solar/Wind Harmer
23.921
971967AH1-528 GEN
Solar/Wind Harmer
41.678
970085AG2-068 GEN
Solar/Wind Harmer
13.08
970581AG2-369 GEN
Solar/Wind Harmer
11.249
316233AE1-074 FULL
Solar/Wind Harmer
0.537
971281AH1-106 GEN
Solar/Wind Harmer
3.245
971283AH1-107 GEN
Solar/Wind Harmer
3.245
316315AB2-025 C
Solar/Wind Harmer
0.509
315814AE2-033 C
Solar/Wind Harmer
17.498
315657AE1-056 GEN
Solar/Wind Harmer
6.551
970285AG2-188 GEN
Solar/Wind Harmer
15.241
946301AF1-294 GEN
Solar/Wind Harmer
4.461
961791AG1-021 GEN
Solar/Wind Harmer
2.176
971845AH1-439 GEN
Solar/Wind Harmer
9.206
970683AG2-441 GEN
Solar/Wind Harmer
13.532
970681AG2-440 GEN
Solar/Wind Harmer
10.825
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.39
946281AF1-292 GEN
Solar/Wind Harmer
0.384
316239AB2-077_GEN
Solar/Wind Harmer
0.511
316238AB2-078_GEN
Solar/Wind Harmer
0.511
3143316POE
Solar/Wind Harmer
-0.067
316087AB2-174 GEN
Solar/Wind Harmer
2.412
970831AG2-522 GEN
Solar/Wind Harmer
8.357
972205AH1-687 GEN
Adder
6.317
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.506
315607AA1-063A GEN
Solar/Wind Harmer
1.651
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
1.438
957871AF2-081 GEN
Solar/Wind Harmer
8.074
319010AE1-072 C
Solar/Wind Harmer
3.264
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.401
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
313526AB2-022
Solar/Wind Harmer
0.434
316305AF2-043 C
Solar/Wind Harmer
0.485
316321Z2-027
Solar/Wind Harmer
0.434
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3146396TANGLEW
Solar/Wind Harmer
0.296
3151081ELIZAR1
Adder
13.101
3151091ELIZAR2
Adder
12.874
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.007
3152611GOSPORTB
Adder
1.816
3152621GOSPORTC
Adder
1.541
3152601GOSPORTA
Adder
1.422
315611Z1-036_GEN2
Solar/Wind Harmer
3.951
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
316311AC2-079 GEN
Solar/Wind Harmer
8.051
315833AF1-017_GEN
Solar/Wind Harmer
3.031
316349AD2-085 GEN
Solar/Wind Harmer
1.419
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.285
316118AC1-105 GEN
Solar/Wind Harmer
1.09
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.929
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
971285AH1-108 GEN
Adder
0.985
972265AH1-717 GEN
Adder
9.774
3151201GRAVEL4
Adder
9.162
3151191GRAVEL3
Adder
9.046
3151211GRAVEL5
Adder
9.046
315732AD1-074 GEN1
Solar/Wind Harmer
1.025
315733AD1-074 GEN2
Solar/Wind Harmer
1.025
315735AD1-075 GEN1
Solar/Wind Harmer
0.513
3152251N ANNA1
50/50
35.404
3151791S ANNAG2
50/50
1.115
3151781S ANNAS1
50/50
0.573
3151741LOISA C
50/50
1.146
3151751LOISA D
50/50
20.962
970119AG2-088 GEN
50/50
29.475
315243AE2-183_GT3
50/50
3.272
3151051BRUNSWICKS1
50/50
5.34
3151021BRUNSWICKG1
50/50
2.573
971451AH1-221 GEN
50/50
7.815
316045AC1-158 PL2
Solar/Wind Harmer
26.051
3147666LOUISA
Solar/Wind Harmer
-0.219
316192AB2-158 GEN
Solar/Wind Harmer
6.415
316254AC1-120 GEN1
Solar/Wind Harmer
2.072
3143226MDLTHAN
Solar/Wind Harmer
-0.025
940641AE2-051 GEN
Solar/Wind Harmer
21.037
3143336POWHATN
Solar/Wind Harmer
2.558
970919AG2-571 GEN
Solar/Wind Harmer
6.655
970087AG2-069 GEN
Solar/Wind Harmer
19.62
939411AE1-173 GEN
Solar/Wind Harmer
104.381
316336AC2-165 C
Solar/Wind Harmer
3.596
315683AE1-153 C
Solar/Wind Harmer
18.631
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.351
315693AD1-088 GEN
Solar/Wind Harmer
9.768
962491AG1-098 GEN
Solar/Wind Harmer
13.03
970937AG2-583 GEN
Solar/Wind Harmer
13.286
3146926FARMVIL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
2.135
963171AG1-166 GEN
Solar/Wind Harmer
2.176
971563AH1-280 GEN
Solar/Wind Harmer
2.176
3144293JTRSVLE
Adder
0.493
316023GEN1_S
Solar/Wind Harmer
1.169
970685AG2-442 GEN
Solar/Wind Harmer
15.155
316322AB2-045
Solar/Wind Harmer
0.581
3146776BUCKING
Solar/Wind Harmer
-0.007
960081AF2-299 GEN
Solar/Wind Harmer
1.928
971795AH1-408 GEN
Solar/Wind Harmer
12.835
3147043LAWRENC
Adder
1.377
316237AB2-079_GEN
Solar/Wind Harmer
0.511
971065AG2-659 GEN
Solar/Wind Harmer
8.385
316129AC1-054 GEN
Solar/Wind Harmer
1.468
972003AH1-546 GEN
Solar/Wind Harmer
8.347
316011AB1-132 GEN
Solar/Wind Harmer
3.442
962571AG1-106 GEN
Solar/Wind Harmer
2.365
316190AA2-174 GEN
Solar/Wind Harmer
0.201
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.473
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.055
316388AE2-253 GEN
Solar/Wind Harmer
1.089
3146456SLIGO L269
Solar/Wind Harmer
-0.016
316294AC1-161 GEN
Solar/Wind Harmer
5.219
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.478
316246AF1-032 C
Solar/Wind Harmer
0.325
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.669
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.543
3150981CHESPKA
Adder
1.78
315800Z1-036_GEN1
Solar/Wind Harmer
3.951
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.893
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
16.843
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.96
3150851SPRUNCC
Adder
0.602
3151171GRAVELC
Adder
1.339
971133AH1-012 GEN
50/50
10.1
3151731LOISA B
50/50
20.962
3151721LOISA A
50/50
20.854
970533AG2-339 GEN
50/50
18.154
970531AG2-338 GEN
50/50
7.261
315242AE2-183_GT2
50/50
3.272
315241AE2-183_GT1
50/50
3.252
972185AH1-677 GEN
50/50
11.796
3151041BRUNSWICKG3
50/50
2.573
972187AH1-678 GEN
50/50
5.905
316447AC1-158 HLD
Solar/Wind Harmer
17.909
966001AG1-469 GEN
Solar/Wind Harmer
0.617
971223AH1-071 GEN
Solar/Wind Harmer
3.105
970933AG2-581 GEN
Solar/Wind Harmer
20.21
315651AD1-115 GEN
Solar/Wind Harmer
9.377
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.94
3144356SAPONY
Solar/Wind Harmer
0.658
971741AH1-377 GEN
Solar/Wind Harmer
21.833
970301AG2-198 GEN
Solar/Wind Harmer
9.278
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
958211AF2-115 GEN
Solar/Wind Harmer
2.72
963191AG1-168 GEN
Solar/Wind Harmer
1.632
3144293JTRSVLE
Adder
0.493
3144293JTRSVLE
Adder
0.415
3146776BUCKING
Solar/Wind Harmer
-0.069
3146776BUCKING
Solar/Wind Harmer
-0.006
316034AC1-036 C
Solar/Wind Harmer
0.32
970323AG2-213 GEN
Solar/Wind Harmer
8.614
971775AH1-396 GEN
Solar/Wind Harmer
1.227
313527AB2-043 GEN
Solar/Wind Harmer
2.765
939181AE1-148 GEN
Solar/Wind Harmer
9.523
316181AB2-040 GEN
Solar/Wind Harmer
2.344
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.849
3145593CAROLNA
Solar/Wind Harmer
0.137
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.651
3145783HORNRTN
Solar/Wind Harmer
1.938
3145783HORNRTN
Solar/Wind Harmer
1.55
3145783HORNRTN
Solar/Wind Harmer
0.484
3145783HORNRTN
Solar/Wind Harmer
0.194
962561AG1-105 GEN
Solar/Wind Harmer
9.166
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.705
964791AG1-342 GEN
Solar/Wind Harmer
3.453
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.089
316018AA1-139 ULT2
Solar/Wind Harmer
1.383
316017AA1-139 ULT1
Solar/Wind Harmer
1.307
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.906
3130086AYDLETT
Solar/Wind Harmer
-0.064
315742AE1-103 GEN
Solar/Wind Harmer
1.685
3145893MURPHYS
Solar/Wind Harmer
0.449
3145893MURPHYS
Solar/Wind Harmer
-0.029
3142956BIRDNECK
Solar/Wind Harmer
0.864
3146386ELIZ CT
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.494
316431W1029_GEN1
Solar/Wind Harmer
2.907
316433W1029_GEN2
Solar/Wind Harmer
2.907
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316036AC1-147 C
Solar/Wind Harmer
0.432
3150991CHESPKB
Adder
1.493
3150991CHESPKB
Adder
1.457
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
0.473
3146376EDENTON
Solar/Wind Harmer
0.473
316065AD1-022 GEN
Solar/Wind Harmer
7.917
970657AG2-426 GEN
Solar/Wind Harmer
4.945
970657AG2-426 GEN
Solar/Wind Harmer
1.034
944641AF1-129 GEN
Adder
56.207
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.256
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.967
315773AC2-141 GEN
Solar/Wind Harmer
6.751
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.943
957521AF2-046 GEN
Solar/Wind Harmer
12.668
961681AG1-008 GEN
Solar/Wind Harmer
12.668
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.269
316435W1029_GEN3
Solar/Wind Harmer
2.907
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.259
316140AB2-099
Solar/Wind Harmer
0.108
962331AG1-082 GEN
Solar/Wind Harmer
1.997
3146376EDENTON
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.714
316317KELFORD C
Solar/Wind Harmer
0.748
3145823KELFORD
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
2.136
970661AG2-428 GEN
Solar/Wind Harmer
2.985
3146206CASHIE
Solar/Wind Harmer
-0.016
971157AH1-035 GEN
Solar/Wind Harmer
1.979
3150861SPRUNCD
Adder
0.602
3151221GRAVEL6
Adder
9.152
3151171GRAVELC
Adder
1.761
315737AD1-076 GEN
Solar/Wind Harmer
0.963
NYPJM->LTFIMP_NY
CLTF
2.601
LAGNLTFEXP_LAGN->PJM
CLTF
5.721
LGEELTFEXP_LGEE->PJM
CLTF
0.805
WECLTFEXP_WEC->PJM
CLTF
0.386
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.547
TVALTFEXP_TVA->PJM
CLTF
2.88
CPLELTFEXP_CPLE->PJM
CLTF
9.138
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.402
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.442
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.658
MECLTFEXP_MEC->PJM
CLTF
2.319
SIGELTFEXP_SIGE->PJM
CLTF
0.069

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: 515T594_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 515T594_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.47 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5140.46
MW Contribution:11.23
Bus #Bus NameTypeMW Contribution
971133AH1-012 GEN
50/50
10.055
3151731LOISA B
50/50
20.602
3151721LOISA A
50/50
20.496
970533AG2-339 GEN
50/50
18.118
970531AG2-338 GEN
50/50
7.247
315242AE2-183_GT2
50/50
3.266
315241AE2-183_GT1
50/50
3.246
972185AH1-677 GEN
50/50
11.773
3151041BRUNSWICKG3
50/50
2.568
972187AH1-678 GEN
50/50
5.893
316447AC1-158 HLD
Solar/Wind Harmer
17.893
966001AG1-469 GEN
Solar/Wind Harmer
0.606
971223AH1-071 GEN
Solar/Wind Harmer
3.098
970933AG2-581 GEN
Solar/Wind Harmer
20.166
315651AD1-115 GEN
Solar/Wind Harmer
8.933
3143526WINTERP
Solar/Wind Harmer
-0.103
970099AG2-077 GEN
Solar/Wind Harmer
24.878
3144356SAPONY
Solar/Wind Harmer
0.657
971741AH1-377 GEN
Solar/Wind Harmer
21.753
970301AG2-198 GEN
Solar/Wind Harmer
9.241
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3152261N ANNA2
50/50
35.375
3151771S ANNAG1
50/50
1.098
3151801S ANNAS2
50/50
0.564
3151761LOISA E
50/50
42.002
972183AH1-676 GEN
50/50
328.628
3151031BRUNSWICKG2
50/50
2.568
316044AC1-158 PL1
Solar/Wind Harmer
8.137
316450AC1-158 RIC
Solar/Wind Harmer
2.17
3147666LOUISA
Solar/Wind Harmer
-0.125
3132273ORANGE
Solar/Wind Harmer
-0.006
316170AC1-121 GEN2
Solar/Wind Harmer
0.668
316313AB2-026
Solar/Wind Harmer
0.579
316258AE1-075 C
Solar/Wind Harmer
0.521
316405AF2-144 C
Solar/Wind Harmer
0.55
3143336POWHATN
Solar/Wind Harmer
2.166
970917AG2-570 GEN
Solar/Wind Harmer
52.468
316478AD1-087 GEN
Solar/Wind Harmer
1.645
316486AD2-202 GEN
Solar/Wind Harmer
0.482
970909AG2-566 GEN
Solar/Wind Harmer
1.755
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.639
3147133PAMPLIN
Solar/Wind Harmer
-0.054
971193AH1-056 GEN
Solar/Wind Harmer
10.872
963181AG1-167 GEN
Solar/Wind Harmer
1.625
3144293JTRSVLE
Adder
0.491
316365GEN2_N
Solar/Wind Harmer
1.166
959311AF2-222 GEN
Solar/Wind Harmer
17.943
3146776BUCKING
Solar/Wind Harmer
-0.006
970257AG2-171 GEN
Solar/Wind Harmer
6.437
315785AD2-033 C
Solar/Wind Harmer
3.882
966621AG1-532 GEN
Solar/Wind Harmer
0.347
316303AF2-085
50/50
3.922
315244AE2-183_ST
50/50
5.646
963041AG1-153 GEN
50/50
5.199
316164AC1-076 GEN
Solar/Wind Harmer
2.965
3147346CASHSCORNER
Solar/Wind Harmer
0.478
941031AE2-094 GEN
Solar/Wind Harmer
42.941
944011AF1-069 GEN
Solar/Wind Harmer
13.455
970673AG2-436 GEN
Solar/Wind Harmer
47.152
970673AG2-436 GEN
Solar/Wind Harmer
23.874
971967AH1-528 GEN
Solar/Wind Harmer
41.593
970085AG2-068 GEN
Solar/Wind Harmer
13.053
970581AG2-369 GEN
Solar/Wind Harmer
11.226
316233AE1-074 FULL
Solar/Wind Harmer
0.536
971281AH1-106 GEN
Solar/Wind Harmer
3.237
971283AH1-107 GEN
Solar/Wind Harmer
3.237
316315AB2-025 C
Solar/Wind Harmer
0.508
315814AE2-033 C
Solar/Wind Harmer
17.459
315657AE1-056 GEN
Solar/Wind Harmer
6.523
946301AF1-294 GEN
Solar/Wind Harmer
4.443
961791AG1-021 GEN
Solar/Wind Harmer
2.167
970285AG2-188 GEN
Solar/Wind Harmer
15.154
970683AG2-441 GEN
Solar/Wind Harmer
13.48
970681AG2-440 GEN
Solar/Wind Harmer
10.784
971845AH1-439 GEN
Solar/Wind Harmer
9.152
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.378
946281AF1-292 GEN
Solar/Wind Harmer
0.383
3143316POE
Solar/Wind Harmer
-0.067
316239AB2-077_GEN
Solar/Wind Harmer
0.51
316238AB2-078_GEN
Solar/Wind Harmer
0.51
316087AB2-174 GEN
Solar/Wind Harmer
2.406
970831AG2-522 GEN
Solar/Wind Harmer
8.334
3137643SOCKMAN
Solar/Wind Harmer
-0.066
972205AH1-687 GEN
Adder
6.271
315652AC1-086 GEN
Solar/Wind Harmer
18.46
315607AA1-063A GEN
Solar/Wind Harmer
1.647
3146043SEABORD
Solar/Wind Harmer
-0.016
3145796HORNRTN
Solar/Wind Harmer
-0.052
3145796HORNRTN
Solar/Wind Harmer
-0.006
965291AG1-394 GEN
Solar/Wind Harmer
1.434
957871AF2-081 GEN
Solar/Wind Harmer
8.054
3147043LAWRENC
Solar/Wind Harmer
-0.01
964241AG1-285 GEN
Solar/Wind Harmer
13.31
316131AB2-060 GEN
Solar/Wind Harmer
1.832
313506AB2-031 GEN
Solar/Wind Harmer
1.347
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
944581AF1-123 GEN
Solar/Wind Harmer
74.024
944601AF1-125 GEN
Solar/Wind Harmer
72.869
3145796HORNRTN
Solar/Wind Harmer
-0.064
3145796HORNRTN
Solar/Wind Harmer
-0.016
3156081AA2-088 GEN
Solar/Wind Harmer
5.243
3146456SLIGO L269
Solar/Wind Harmer
-0.016
971153AH1-033 GEN
Solar/Wind Harmer
1.962
315773AC2-141 GEN
Solar/Wind Harmer
6.734
3145893MURPHYS
Solar/Wind Harmer
0.112
3145893MURPHYS
Solar/Wind Harmer
-0.016
3145273HOLLAND
Solar/Wind Harmer
-0.012
316320Y1-086
Solar/Wind Harmer
0.941
957521AF2-046 GEN
Solar/Wind Harmer
12.636
961681AG1-008 GEN
Solar/Wind Harmer
12.636
3146263WOODLND
Solar/Wind Harmer
-0.016
3151101ELIZAR3
Adder
13.236
316435W1029_GEN3
Solar/Wind Harmer
2.9
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316463AE2-346 GEN
Solar/Wind Harmer
0.258
316140AB2-099
Solar/Wind Harmer
0.107
962331AG1-082 GEN
Solar/Wind Harmer
1.992
3146376EDENTON
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.71
3156021HOLLOMANSOL
Solar/Wind Harmer
2.131
316317KELFORD C
Solar/Wind Harmer
0.746
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
2.977
3146206CASHIE
Solar/Wind Harmer
-0.016
971157AH1-035 GEN
Solar/Wind Harmer
1.974
3150861SPRUNCD
Adder
0.601
3151221GRAVEL6
Adder
9.127
3152251N ANNA1
50/50
35.378
3151791S ANNAG2
50/50
1.098
3151781S ANNAS1
50/50
0.564
3151741LOISA C
50/50
1.127
3151751LOISA D
50/50
20.602
970119AG2-088 GEN
50/50
29.412
315243AE2-183_GT3
50/50
3.266
3151051BRUNSWICKS1
50/50
5.329
3151021BRUNSWICKG1
50/50
2.568
971451AH1-221 GEN
50/50
7.799
316045AC1-158 PL2
Solar/Wind Harmer
26.028
3147666LOUISA
Solar/Wind Harmer
-0.218
316192AB2-158 GEN
Solar/Wind Harmer
6.369
316254AC1-120 GEN1
Solar/Wind Harmer
2.003
3143226MDLTHAN
Solar/Wind Harmer
-0.025
940641AE2-051 GEN
Solar/Wind Harmer
20.996
3143336POWHATN
Solar/Wind Harmer
2.548
970919AG2-571 GEN
Solar/Wind Harmer
6.642
970087AG2-069 GEN
Solar/Wind Harmer
19.58
939411AE1-173 GEN
Solar/Wind Harmer
104.168
316336AC2-165 C
Solar/Wind Harmer
3.581
3143526WINTERP
Solar/Wind Harmer
-0.103
957481AF2-042 GEN
Solar/Wind Harmer
62.195
315693AD1-088 GEN
Solar/Wind Harmer
9.741
962491AG1-098 GEN
Solar/Wind Harmer
12.993
315683AE1-153 C
Solar/Wind Harmer
17.63
970937AG2-583 GEN
Solar/Wind Harmer
13.209
3146926FARMVIL
Solar/Wind Harmer
-0.011
315687AD1-152 GEN
Solar/Wind Harmer
2.13
963171AG1-166 GEN
Solar/Wind Harmer
2.167
971563AH1-280 GEN
Solar/Wind Harmer
2.167
3144293JTRSVLE
Adder
0.491
316023GEN1_S
Solar/Wind Harmer
1.166
970685AG2-442 GEN
Solar/Wind Harmer
15.097
316322AB2-045
Solar/Wind Harmer
0.578
3146776BUCKING
Solar/Wind Harmer
-0.007
960081AF2-299 GEN
Solar/Wind Harmer
1.923
971795AH1-408 GEN
Solar/Wind Harmer
12.801
3147043LAWRENC
Adder
1.373
316237AB2-079_GEN
Solar/Wind Harmer
0.51
971065AG2-659 GEN
Solar/Wind Harmer
8.362
316129AC1-054 GEN
Solar/Wind Harmer
1.464
972003AH1-546 GEN
Solar/Wind Harmer
8.288
316011AB1-132 GEN
Solar/Wind Harmer
3.433
962571AG1-106 GEN
Solar/Wind Harmer
2.359
316190AA2-174 GEN
Solar/Wind Harmer
0.2
3145783HORNRTN
Solar/Wind Harmer
-0.016
944591AF1-124 GEN
Solar/Wind Harmer
74.291
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.016
970401AG2-262 GEN
Solar/Wind Harmer
1.052
316388AE2-253 GEN
Solar/Wind Harmer
1.087
3146456SLIGO L269
Solar/Wind Harmer
-0.016
316294AC1-161 GEN
Solar/Wind Harmer
5.207
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
0.477
316246AF1-032 C
Solar/Wind Harmer
0.325
3146263WOODLND
Solar/Wind Harmer
-0.016
316093AE2-104_GEN
Solar/Wind Harmer
4.657
3146516WINFALL
Solar/Wind Harmer
-0.052
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316375AC2-012 GEN
Solar/Wind Harmer
5.53
3150981CHESPKA
Adder
1.776
315800Z1-036_GEN1
Solar/Wind Harmer
3.941
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.856
3145823KELFORD
Solar/Wind Harmer
-0.016
970661AG2-428 GEN
Solar/Wind Harmer
16.801
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
3.95
3150851SPRUNCC
Adder
0.601
3151171GRAVELC
Adder
1.335
319010AE1-072 C
Solar/Wind Harmer
3.256
3146406KITTY HAWK
Solar/Wind Harmer
0.013
316318V4-068
Solar/Wind Harmer
0.4
3145893MURPHYS
Solar/Wind Harmer
-0.043
3145893MURPHYS
Solar/Wind Harmer
-0.016
313526AB2-022
Solar/Wind Harmer
0.433
316305AF2-043 C
Solar/Wind Harmer
0.483
316321Z2-027
Solar/Wind Harmer
0.433
3146396TANGLEW
Solar/Wind Harmer
0.295
3145176PASQUOTANK
Solar/Wind Harmer
-0.01
3151081ELIZAR1
Adder
13.069
3151091ELIZAR2
Adder
12.842
3146486SUNBURY
Solar/Wind Harmer
-0.016
3146486SUNBURY
Solar/Wind Harmer
-0.016
315835AF2-110_GEN
Solar/Wind Harmer
2.002
3152611GOSPORTB
Adder
1.811
3152621GOSPORTC
Adder
1.537
3152601GOSPORTA
Adder
1.418
315611Z1-036_GEN2
Solar/Wind Harmer
3.941
3145513AHOSKIE
Solar/Wind Harmer
0.139
961941AG1-037 GEN
Solar/Wind Harmer
0.12
3145513AHOSKIE
Solar/Wind Harmer
-0.016
316311AC2-079 GEN
Solar/Wind Harmer
8.031
315833AF1-017_GEN
Solar/Wind Harmer
3.024
316349AD2-085 GEN
Solar/Wind Harmer
1.416
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
315816AE2-034 GEN
Solar/Wind Harmer
1.282
316118AC1-105 GEN
Solar/Wind Harmer
1.087
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
6.912
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
971285AH1-108 GEN
Adder
0.983
972265AH1-717 GEN
Adder
9.747
3151201GRAVEL4
Adder
9.137
3151191GRAVEL3
Adder
9.022
3151211GRAVEL5
Adder
9.022
315732AD1-074 GEN1
Solar/Wind Harmer
2.756
315733AD1-074 GEN2
Solar/Wind Harmer
2.756
315735AD1-075 GEN1
Solar/Wind Harmer
1.378
3151171GRAVELC
Adder
1.756
315737AD1-076 GEN
Solar/Wind Harmer
2.59
958211AF2-115 GEN
Solar/Wind Harmer
2.709
963191AG1-168 GEN
Solar/Wind Harmer
1.625
3144293JTRSVLE
Adder
0.491
3144293JTRSVLE
Adder
0.414
3146776BUCKING
Solar/Wind Harmer
-0.068
3146776BUCKING
Solar/Wind Harmer
-0.006
316034AC1-036 C
Solar/Wind Harmer
0.318
970323AG2-213 GEN
Solar/Wind Harmer
8.582
971775AH1-396 GEN
Solar/Wind Harmer
1.222
313527AB2-043 GEN
Solar/Wind Harmer
2.756
939181AE1-148 GEN
Solar/Wind Harmer
9.495
316181AB2-040 GEN
Solar/Wind Harmer
2.338
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.844
3145593CAROLNA
Solar/Wind Harmer
0.136
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.647
3145783HORNRTN
Solar/Wind Harmer
1.933
3145783HORNRTN
Solar/Wind Harmer
1.546
3145783HORNRTN
Solar/Wind Harmer
0.483
3145783HORNRTN
Solar/Wind Harmer
0.193
962561AG1-105 GEN
Solar/Wind Harmer
9.138
3145796HORNRTN
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.039
3145506HICKORY
Solar/Wind Harmer
-0.01
316185AD1-033 GEN
Solar/Wind Harmer
1.701
964791AG1-342 GEN
Solar/Wind Harmer
3.443
316339AD2-160 GEN
Solar/Wind Harmer
1.087
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
316018AA1-139 ULT2
Solar/Wind Harmer
1.38
316017AA1-139 ULT1
Solar/Wind Harmer
1.303
3137176SLIGO L2192
Solar/Wind Harmer
-0.064
3146456SLIGO L269
Solar/Wind Harmer
1.901
3130086AYDLETT
Solar/Wind Harmer
-0.064
315742AE1-103 GEN
Solar/Wind Harmer
1.681
3145893MURPHYS
Solar/Wind Harmer
0.448
3145893MURPHYS
Solar/Wind Harmer
-0.029
3142956BIRDNECK
Solar/Wind Harmer
0.862
3146386ELIZ CT
Solar/Wind Harmer
-0.016
316316AC1-027 C
Solar/Wind Harmer
0.493
316431W1029_GEN1
Solar/Wind Harmer
2.9
316433W1029_GEN2
Solar/Wind Harmer
2.9
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316036AC1-147 C
Solar/Wind Harmer
0.431
3150991CHESPKB
Adder
1.49
3150991CHESPKB
Adder
1.454
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146376EDENTON
Solar/Wind Harmer
0.472
3146376EDENTON
Solar/Wind Harmer
0.472
316065AD1-022 GEN
Solar/Wind Harmer
7.897
944641AF1-129 GEN
Adder
56.042
NYPJM->LTFIMP_NY
CLTF
2.592
LGEELTFEXP_LGEE->PJM
CLTF
0.801
LAGNLTFEXP_LAGN->PJM
CLTF
5.7
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.49
WECLTFEXP_WEC->PJM
CLTF
0.384
TVALTFEXP_TVA->PJM
CLTF
2.869
CPLELTFEXP_CPLE->PJM
CLTF
9.114
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.291
CBM West 1LTFEXP_CBM-W1->PJM
CBM
12.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.621
MECLTFEXP_MEC->PJM
CLTF
2.309
SIGELTFEXP_SIGE->PJM
CLTF
0.069

Details for 8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T573_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8LADYSMITH 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T573_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.18 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5050.25
MW Contribution:11.82
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.123
315244AE2-183_ST
50/50
5.943
963041AG1-153 GEN
50/50
5.473
3147346CASHSCORNER
Solar/Wind Harmer
0.451
941031AE2-094 GEN
Solar/Wind Harmer
45.192
944011AF1-069 GEN
Solar/Wind Harmer
14.16
970673AG2-436 GEN
Solar/Wind Harmer
49.627
970673AG2-436 GEN
Solar/Wind Harmer
25.128
971967AH1-528 GEN
Solar/Wind Harmer
43.766
970085AG2-068 GEN
Solar/Wind Harmer
13.745
970581AG2-369 GEN
Solar/Wind Harmer
11.821
316233AE1-074 FULL
Solar/Wind Harmer
0.568
971281AH1-106 GEN
Solar/Wind Harmer
3.433
971283AH1-107 GEN
Solar/Wind Harmer
3.433
316315AB2-025 C
Solar/Wind Harmer
0.538
315814AE2-033 C
Solar/Wind Harmer
18.51
315657AE1-056 GEN
Solar/Wind Harmer
6.816
946301AF1-294 GEN
Solar/Wind Harmer
4.646
961791AG1-021 GEN
Solar/Wind Harmer
2.266
946281AF1-292 GEN
Solar/Wind Harmer
0.406
3143316POE
Solar/Wind Harmer
-0.071
970683AG2-441 GEN
Solar/Wind Harmer
14.114
970681AG2-440 GEN
Solar/Wind Harmer
11.291
3144303KENBRDG
Solar/Wind Harmer
-0.014
971443AH1-215 GEN
Solar/Wind Harmer
3.542
970285AG2-188 GEN
Solar/Wind Harmer
15.689
3152261N ANNA2
50/50
36.486
3151771S ANNAG1
50/50
1.047
3151801S ANNAS2
50/50
0.538
3151761LOISA E
50/50
39.805
972183AH1-676 GEN
50/50
309.976
3151031BRUNSWICKG2
50/50
2.703
3147666LOUISA
Solar/Wind Harmer
-0.125
316313AB2-026
Solar/Wind Harmer
0.604
316258AE1-075 C
Solar/Wind Harmer
0.544
316405AF2-144 C
Solar/Wind Harmer
0.574
3143336POWHATN
Solar/Wind Harmer
2.261
970917AG2-570 GEN
Solar/Wind Harmer
55.248
316478AD1-087 GEN
Solar/Wind Harmer
1.73
316486AD2-202 GEN
Solar/Wind Harmer
0.507
970909AG2-566 GEN
Solar/Wind Harmer
1.832
3146926FARMVIL
Solar/Wind Harmer
-0.011
316365GEN2_N
Solar/Wind Harmer
1.237
942461AE2-259 GEN
Solar/Wind Harmer
2.75
3132273ORANGE
Solar/Wind Harmer
-0.004
3147133PAMPLIN
Solar/Wind Harmer
-0.057
971193AH1-056 GEN
Solar/Wind Harmer
11.36
963181AG1-167 GEN
Solar/Wind Harmer
1.7
3144293JTRSVLE
Adder
0.514
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3147043LAWRENC
Solar/Wind Harmer
-0.011
959311AF2-222 GEN
Solar/Wind Harmer
18.805
970257AG2-171 GEN
Solar/Wind Harmer
6.749
315785AD2-033 C
Solar/Wind Harmer
4.072
964241AG1-285 GEN
Solar/Wind Harmer
13.983
316131AB2-060 GEN
Solar/Wind Harmer
1.926
313506AB2-031 GEN
Solar/Wind Harmer
1.428
3146776BUCKING
Solar/Wind Harmer
-0.006
944581AF1-123 GEN
Solar/Wind Harmer
79.168
944601AF1-125 GEN
Solar/Wind Harmer
77.932
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
315773AC2-141 GEN
Solar/Wind Harmer
7.21
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.098
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
3156081AA2-088 GEN
Solar/Wind Harmer
5.579
316320Y1-086
Solar/Wind Harmer
1.006
3151101ELIZAR3
Adder
14.167
3145273HOLLAND
Solar/Wind Harmer
-0.013
3144873MCLAUGH
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
3.099
3145893MURPHYS
Solar/Wind Harmer
0.119
3145893MURPHYS
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
957521AF2-046 GEN
Solar/Wind Harmer
13.441
961681AG1-008 GEN
Solar/Wind Harmer
13.441
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
-0.017
316463AE2-346 GEN
Solar/Wind Harmer
0.274
316140AB2-099
Solar/Wind Harmer
0.114
962331AG1-082 GEN
Solar/Wind Harmer
2.118
970661AG2-428 GEN
Solar/Wind Harmer
3.188
315614AA2-178 GEN
Solar/Wind Harmer
1.823
316083AB2-161 GEN
Solar/Wind Harmer
2.741
970659AG2-427 GEN
Solar/Wind Harmer
1.589
3156021HOLLOMANSOL
Solar/Wind Harmer
2.268
971157AH1-035 GEN
Solar/Wind Harmer
2.104
3146206CASHIE
Solar/Wind Harmer
-0.017
315737AD1-076 GEN
Solar/Wind Harmer
3.197
3150861SPRUNCD
Adder
0.647
3151221GRAVEL6
Adder
9.841
3151171GRAVELC
Adder
1.893
3144216WINCHST
Adder
0.457
3150921YORKTN3
Adder
2.989
316317KELFORD C
Solar/Wind Harmer
0.786
316087AB2-174 GEN
Solar/Wind Harmer
2.549
971845AH1-439 GEN
Solar/Wind Harmer
9.467
316239AB2-077_GEN
Solar/Wind Harmer
0.536
316238AB2-078_GEN
Solar/Wind Harmer
0.536
970831AG2-522 GEN
Solar/Wind Harmer
8.805
3137643SOCKMAN
Solar/Wind Harmer
-0.07
315652AC1-086 GEN
Solar/Wind Harmer
19.588
315607AA1-063A GEN
Solar/Wind Harmer
1.748
3146043SEABORD
Solar/Wind Harmer
-0.017
957871AF2-081 GEN
Solar/Wind Harmer
8.614
319010AE1-072 C
Solar/Wind Harmer
3.482
3146406KITTY HAWK
Solar/Wind Harmer
0.014
3145796HORNRTN
Solar/Wind Harmer
-0.055
3145796HORNRTN
Solar/Wind Harmer
-0.007
965291AG1-394 GEN
Solar/Wind Harmer
1.526
313526AB2-022
Solar/Wind Harmer
0.463
316305AF2-043 C
Solar/Wind Harmer
0.517
3151081ELIZAR1
Adder
13.988
3151091ELIZAR2
Adder
13.745
316321Z2-027
Solar/Wind Harmer
0.462
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.315
315835AF2-110_GEN
Solar/Wind Harmer
2.141
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
3152611GOSPORTB
Adder
1.939
3152621GOSPORTC
Adder
1.646
3152601GOSPORTA
Adder
1.518
316318V4-068
Solar/Wind Harmer
0.426
3145893MURPHYS
Solar/Wind Harmer
-0.046
3145893MURPHYS
Solar/Wind Harmer
-0.017
316311AC2-079 GEN
Solar/Wind Harmer
8.593
315611Z1-036_GEN2
Solar/Wind Harmer
4.209
315833AF1-017_GEN
Solar/Wind Harmer
3.235
316349AD2-085 GEN
Solar/Wind Harmer
1.515
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
3145513AHOSKIE
Solar/Wind Harmer
0.148
961941AG1-037 GEN
Solar/Wind Harmer
0.127
3145513AHOSKIE
Solar/Wind Harmer
-0.017
972205AH1-687 GEN
Adder
6.438
3145683EARLEYS
Solar/Wind Harmer
-0.034
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
315816AE2-034 GEN
Solar/Wind Harmer
1.367
3130546PLYMOUTH
Solar/Wind Harmer
-0.017
3146206CASHIE
Solar/Wind Harmer
-0.017
970601AG2-382 GEN
Solar/Wind Harmer
7.362
315732AD1-074 GEN1
Solar/Wind Harmer
3.402
315733AD1-074 GEN2
Solar/Wind Harmer
3.402
315735AD1-075 GEN1
Solar/Wind Harmer
1.701
971285AH1-108 GEN
Adder
1.059
972265AH1-717 GEN
Adder
10.51
3151201GRAVEL4
Adder
9.853
3151191GRAVEL3
Adder
9.728
3151211GRAVEL5
Adder
9.728
971133AH1-012 GEN
50/50
10.184
3151731LOISA B
50/50
19.525
3151721LOISA A
50/50
19.424
970533AG2-339 GEN
50/50
19.068
970531AG2-338 GEN
50/50
7.627
315242AE2-183_GT2
50/50
3.437
315241AE2-183_GT1
50/50
3.416
972185AH1-677 GEN
50/50
12.391
3151041BRUNSWICKG3
50/50
2.703
972187AH1-678 GEN
50/50
6.203
966001AG1-469 GEN
Solar/Wind Harmer
0.526
971223AH1-071 GEN
Solar/Wind Harmer
3.257
970933AG2-581 GEN
Solar/Wind Harmer
21.214
3143526WINTERP
Solar/Wind Harmer
-0.109
970099AG2-077 GEN
Solar/Wind Harmer
26.157
3144356SAPONY
Solar/Wind Harmer
0.696
971741AH1-377 GEN
Solar/Wind Harmer
22.746
970301AG2-198 GEN
Solar/Wind Harmer
9.65
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.833
963191AG1-168 GEN
Solar/Wind Harmer
1.7
3144293JTRSVLE
Adder
0.514
3144293JTRSVLE
Adder
0.433
316034AC1-036 C
Solar/Wind Harmer
0.334
970323AG2-213 GEN
Solar/Wind Harmer
8.998
971775AH1-396 GEN
Solar/Wind Harmer
1.281
313527AB2-043 GEN
Solar/Wind Harmer
2.899
939181AE1-148 GEN
Solar/Wind Harmer
10.003
316181AB2-040 GEN
Solar/Wind Harmer
2.478
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.955
3145593CAROLNA
Solar/Wind Harmer
0.144
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.747
3145783HORNRTN
Solar/Wind Harmer
2.049
3145783HORNRTN
Solar/Wind Harmer
1.64
3145783HORNRTN
Solar/Wind Harmer
0.512
3145783HORNRTN
Solar/Wind Harmer
0.205
316185AD1-033 GEN
Solar/Wind Harmer
1.82
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.162
316018AA1-139 ULT2
Solar/Wind Harmer
1.476
316017AA1-139 ULT1
Solar/Wind Harmer
1.394
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3146456SLIGO L269
Solar/Wind Harmer
2.033
3130086AYDLETT
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.051
3142956BIRDNECK
Solar/Wind Harmer
0.922
316316AC1-027 C
Solar/Wind Harmer
0.527
3146386ELIZ CT
Solar/Wind Harmer
-0.017
315742AE1-103 GEN
Solar/Wind Harmer
1.793
316036AC1-147 C
Solar/Wind Harmer
0.461
3150991CHESPKB
Adder
1.595
3150991CHESPKB
Adder
1.556
316431W1029_GEN1
Solar/Wind Harmer
3.099
316433W1029_GEN2
Solar/Wind Harmer
3.099
962561AG1-105 GEN
Solar/Wind Harmer
9.62
3145893MURPHYS
Solar/Wind Harmer
0.477
3145893MURPHYS
Solar/Wind Harmer
-0.031
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3146376EDENTON
Solar/Wind Harmer
0.504
3146376EDENTON
Solar/Wind Harmer
0.504
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970657AG2-426 GEN
Solar/Wind Harmer
5.283
970657AG2-426 GEN
Solar/Wind Harmer
1.105
316065AD1-022 GEN
Solar/Wind Harmer
8.412
944641AF1-129 GEN
Adder
60.727
3152251N ANNA1
50/50
36.489
3151791S ANNAG2
50/50
1.047
3151781S ANNAS1
50/50
0.538
3151741LOISA C
50/50
1.068
3151751LOISA D
50/50
19.525
970119AG2-088 GEN
50/50
30.924
315243AE2-183_GT3
50/50
3.437
3151051BRUNSWICKS1
50/50
5.61
3151021BRUNSWICKG1
50/50
2.703
971451AH1-221 GEN
50/50
8.209
3147666LOUISA
Solar/Wind Harmer
-0.218
316192AB2-158 GEN
Solar/Wind Harmer
6.364
3143226MDLTHAN
Solar/Wind Harmer
-0.026
940641AE2-051 GEN
Solar/Wind Harmer
22.145
3143336POWHATN
Solar/Wind Harmer
2.66
970919AG2-571 GEN
Solar/Wind Harmer
6.993
939411AE1-173 GEN
Solar/Wind Harmer
110.17
970087AG2-069 GEN
Solar/Wind Harmer
20.618
316336AC2-165 C
Solar/Wind Harmer
3.729
3143526WINTERP
Solar/Wind Harmer
-0.109
957481AF2-042 GEN
Solar/Wind Harmer
65.393
315693AD1-088 GEN
Solar/Wind Harmer
10.229
962491AG1-098 GEN
Solar/Wind Harmer
13.642
970937AG2-583 GEN
Solar/Wind Harmer
13.661
315687AD1-152 GEN
Solar/Wind Harmer
2.242
3146926FARMVIL
Solar/Wind Harmer
-0.011
316023GEN1_S
Solar/Wind Harmer
1.237
963171AG1-166 GEN
Solar/Wind Harmer
2.266
971563AH1-280 GEN
Solar/Wind Harmer
2.266
3144293JTRSVLE
Adder
0.514
960081AF2-299 GEN
Solar/Wind Harmer
2.037
970685AG2-442 GEN
Solar/Wind Harmer
15.808
971795AH1-408 GEN
Solar/Wind Harmer
13.539
3147043LAWRENC
Adder
1.452
316237AB2-079_GEN
Solar/Wind Harmer
0.536
316322AB2-045
Solar/Wind Harmer
0.597
3146776BUCKING
Solar/Wind Harmer
-0.007
971065AG2-659 GEN
Solar/Wind Harmer
8.829
316129AC1-054 GEN
Solar/Wind Harmer
1.546
316011AB1-132 GEN
Solar/Wind Harmer
3.643
962571AG1-106 GEN
Solar/Wind Harmer
2.503
944591AF1-124 GEN
Solar/Wind Harmer
79.453
315683AE1-153 C
Solar/Wind Harmer
16.116
316190AA2-174 GEN
Solar/Wind Harmer
0.212
3145783HORNRTN
Solar/Wind Harmer
-0.017
316388AE2-253 GEN
Solar/Wind Harmer
1.162
316294AC1-161 GEN
Solar/Wind Harmer
5.575
3146456SLIGO L269
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.347
316093AE2-104_GEN
Solar/Wind Harmer
4.98
316375AC2-012 GEN
Solar/Wind Harmer
5.919
3150981CHESPKA
Adder
1.901
3145893MURPHYS
Solar/Wind Harmer
-0.068
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
0.507
972003AH1-546 GEN
Solar/Wind Harmer
8.52
315800Z1-036_GEN1
Solar/Wind Harmer
4.209
3146263WOODLND
Solar/Wind Harmer
-0.017
3146173TUNIS
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970401AG2-262 GEN
Solar/Wind Harmer
1.108
970661AG2-428 GEN
Solar/Wind Harmer
17.989
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145663CRESWEL
Solar/Wind Harmer
-0.047
971163AH1-040 GEN
Solar/Wind Harmer
15.843
316381AD1-082 GEN
Solar/Wind Harmer
1.549
970659AG2-427 GEN
Solar/Wind Harmer
8.964
3146206CASHIE
Solar/Wind Harmer
-0.017
971547AH1-271 GEN
Solar/Wind Harmer
4.207
3150851SPRUNCC
Adder
0.647
3151171GRAVELC
Adder
1.44
NYPJM->LTFIMP_NY
CLTF
2.609
LGEELTFEXP_LGEE->PJM
CLTF
0.916
LAGNLTFEXP_LAGN->PJM
CLTF
6.191
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.725
WECLTFEXP_WEC->PJM
CLTF
0.445
TVALTFEXP_TVA->PJM
CLTF
3.115
CPLELTFEXP_CPLE->PJM
CLTF
9.658
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.121
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.634
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.492
MECLTFEXP_MEC->PJM
CLTF
2.607
SIGELTFEXP_SIGE->PJM
CLTF
0.078

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:210.08 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:8277.02
MW Contribution:18.5
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
6.43
971285AH1-108 GEN
50/50
2.792
316233AE1-074 FULL
Solar/Wind Harmer
1.077
971281AH1-106 GEN
Solar/Wind Harmer
6.508
971283AH1-107 GEN
Solar/Wind Harmer
6.508
316312AB1-027
Solar/Wind Harmer
1.301
972189AH1-679 GEN
Adder
5.748
316132AB2-190 GEN1
Solar/Wind Harmer
3.853
3152251N ANNA1
50/50
24.932
970119AG2-088 GEN
50/50
48.227
3150851SPRUNCC
50/50
1.706
3143096IRON208
50/50
1.529
3143226MDLTHAN
Solar/Wind Harmer
-0.041
3143526WINTERP
Solar/Wind Harmer
-0.207
3142543TWELFTH
Solar/Wind Harmer
-0.004
3142416OLDCHRC
Solar/Wind Harmer
-0.1
3142416OLDCHRC
Solar/Wind Harmer
-0.038
940641AE2-051 GEN
Solar/Wind Harmer
35.93
944631AF1-128 GEN
Adder
162.412
315671AE2-027_GEN
Solar/Wind Harmer
28.648
939411AE1-173 GEN
Solar/Wind Harmer
190.668
316294AC1-161 GEN
Solar/Wind Harmer
12.329
970129AG2-093 GEN
Solar/Wind Harmer
8.69
316458AB2-190 GEN2
Solar/Wind Harmer
3.853
971069AG2-661 GEN
Solar/Wind Harmer
6.016
971647AH1-324 GEN
Solar/Wind Harmer
18.957
961611AG1-000B GEN
Solar/Wind Harmer
18.682
3151171GRAVELC
Adder
3.577
316159AE1-175 C
Solar/Wind Harmer
1.013
3145336SMITFLD
Solar/Wind Harmer
-0.15
944591AF1-124 GEN
Solar/Wind Harmer
172.182
966881AG1-559 GEN
Solar/Wind Harmer
0.388
316375AC2-012 GEN
Solar/Wind Harmer
13.033
3150981CHESPKA
Adder
4.185
970659AG2-427 GEN
Solar/Wind Harmer
20.009
3138126ROCKLANDING
Solar/Wind Harmer
0.115
316381AD1-082 GEN
Solar/Wind Harmer
3.451
970661AG2-428 GEN
Solar/Wind Harmer
39.862
971317AH1-138 GEN
Solar/Wind Harmer
4.684
316388AE2-253 GEN
Solar/Wind Harmer
2.52
316072AD1-144
Solar/Wind Harmer
0.755
3146456SLIGO L269
Solar/Wind Harmer
-0.037
316246AF1-032 C
Solar/Wind Harmer
0.752
316093AE2-104_GEN
Solar/Wind Harmer
10.761
3142433PROV 92
Solar/Wind Harmer
-0.147
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
972197AH1-683 GEN
Adder
6.897
972219AH1-694 GEN
Adder
4.966
3146516WINFALL
Solar/Wind Harmer
-0.117
3146516WINFALL
Solar/Wind Harmer
-0.036
3147666LOUISA
Solar/Wind Harmer
-0.144
971777AH1-397 GEN
Solar/Wind Harmer
4.252
3141843SHACKLE
Adder
1.644
3141766HARMONY
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.871
3130156CHOWAN
Solar/Wind Harmer
-0.035
316192AB2-158 GEN
Solar/Wind Harmer
4.195
3138133OCRAN
Solar/Wind Harmer
-0.021
3143336POWHATN
Solar/Wind Harmer
4.148
3145663CRESWEL
Solar/Wind Harmer
-0.097
971163AH1-040 GEN
Solar/Wind Harmer
32.582
970919AG2-571 GEN
Solar/Wind Harmer
10.938
970087AG2-069 GEN
Solar/Wind Harmer
32.274
961951AG1-038 GEN
Solar/Wind Harmer
4.47
316023GEN1_S
Solar/Wind Harmer
2.287
3146206CASHIE
Solar/Wind Harmer
-0.034
971547AH1-271 GEN
Solar/Wind Harmer
8.439
3145893MURPHYS
Solar/Wind Harmer
-0.134
3145893MURPHYS
Solar/Wind Harmer
0.999
962861AG1-135 GEN
Solar/Wind Harmer
12.565
316336AC2-165 C
Solar/Wind Harmer
5.815
3146173TUNIS
Solar/Wind Harmer
-0.033
960081AF2-299 GEN
Solar/Wind Harmer
3.72
957481AF2-042 GEN
Solar/Wind Harmer
103.301
3145683EARLEYS
Solar/Wind Harmer
-0.033
3146263WOODLND
Solar/Wind Harmer
-0.033
964211AG1-282 GEN
Solar/Wind Harmer
0.987
3141726DUNNSVL
Solar/Wind Harmer
-0.131
3145963POPLR C
Solar/Wind Harmer
-0.032
316011AB1-132 GEN
Solar/Wind Harmer
6.808
962571AG1-106 GEN
Solar/Wind Harmer
4.677
3145823KELFORD
Solar/Wind Harmer
-0.032
315693AD1-088 GEN
Solar/Wind Harmer
16.208
316190AA2-174 GEN
Solar/Wind Harmer
0.398
971795AH1-408 GEN
Solar/Wind Harmer
24.298
962491AG1-098 GEN
Solar/Wind Harmer
21.614
3150351NORNECKC2
Adder
2.867
316174AB2-169 GEN
Solar/Wind Harmer
4.976
3147043LAWRENC
Adder
2.584
3145783HORNRTN
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.105
3145796HORNRTN
Solar/Wind Harmer
-0.032
316212AC1-099_GEN
Solar/Wind Harmer
2.729
3146293MARTNCO
Solar/Wind Harmer
0.193
3144293JTRSVLE
Adder
0.837
972277AH1-723 GEN
Adder
133.532
3151751LOISA D
Adder
11.364
316045AC1-158 PL2
Solar/Wind Helper
15.147
316006AB2-029 C
Solar/Wind Helper
0.159
3143316POE
Solar/Wind Harmer
-0.15
316369SG1_INVT
Solar/Wind Harmer
6.784
315976AC1-164 GENA
Solar/Wind Harmer
40.068
316169AC1-164_GENC
Solar/Wind Harmer
34.615
315975AC1-164 GENB
Solar/Wind Harmer
1.185
972265AH1-717 GEN
Adder
26.11
3151201GRAVEL4
Adder
24.476
3151191GRAVEL3
Adder
24.166
3151211GRAVEL5
Adder
24.166
971445AH1-216 GEN
Solar/Wind Harmer
23.358
3151081ELIZAR1
Adder
30.739
3151091ELIZAR2
Adder
30.205
3152611GOSPORTB
Adder
4.268
3152621GOSPORTC
Adder
3.622
3152601GOSPORTA
Adder
3.342
957871AF2-081 GEN
Solar/Wind Harmer
18.665
315833AF1-017_GEN
Solar/Wind Harmer
7.074
316349AD2-085 GEN
Solar/Wind Harmer
3.313
316311AC2-079 GEN
Solar/Wind Harmer
18.784
319010AE1-072 C
Solar/Wind Harmer
7.531
3146406KITTY HAWK
Solar/Wind Harmer
0.031
316305AF2-043 C
Solar/Wind Harmer
1.121
941031AE2-094 GEN
Solar/Wind Harmer
69.631
944011AF1-069 GEN
Solar/Wind Harmer
21.818
971167AH1-042 GEN
Solar/Wind Harmer
35.733
315835AF2-110_GEN
Solar/Wind Harmer
4.626
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
3150411LDYSMT5
Adder
44.306
3150381LDYSMT2
Adder
42.402
972213AH1-691 GEN
Adder
7.173
972215AH1-692 GEN
Adder
7.173
313526AB2-022
Solar/Wind Harmer
0.995
3146486SUNBURY
Solar/Wind Harmer
-0.037
3146486SUNBURY
Solar/Wind Harmer
-0.037
957831AF2-077 GEN
Solar/Wind Harmer
1.106
3138283WHITEMARSH
Solar/Wind Harmer
0.057
316321Z2-027
Solar/Wind Harmer
0.991
3146396TANGLEW
Solar/Wind Harmer
0.676
3145176PASQUOTANK
Solar/Wind Harmer
-0.023
316315AB2-025 C
Solar/Wind Harmer
0.987
3143873LANEXA
Solar/Wind Harmer
-0.022
970673AG2-436 GEN
Solar/Wind Harmer
76.723
970673AG2-436 GEN
Solar/Wind Harmer
38.847
315814AE2-033 C
Solar/Wind Harmer
33.934
316314AB2-024 C
Solar/Wind Harmer
3.103
316059AD1-063 C
Solar/Wind Harmer
0.817
971967AH1-528 GEN
Solar/Wind Harmer
67.827
315662AE1-191 GEN
Solar/Wind Harmer
4.344
315666AE1-190 GEN
Solar/Wind Harmer
1.086
315611Z1-036_GEN2
Solar/Wind Harmer
8.871
957601AF2-054 GEN
Solar/Wind Harmer
1.073
3141873WAN 176
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.035
3130156CHOWAN
Solar/Wind Harmer
-0.035
3141913WHIT STONE
Solar/Wind Harmer
-0.035
3138133OCRAN
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.021
3141783LANCAST
Solar/Wind Harmer
-0.014
315816AE2-034 GEN
Solar/Wind Harmer
2.812
970085AG2-068 GEN
Solar/Wind Harmer
21.516
970581AG2-369 GEN
Solar/Wind Harmer
18.504
962981AG1-147 GEN
Solar/Wind Harmer
15.002
3130546PLYMOUTH
Solar/Wind Harmer
-0.034
315732AD1-074 GEN1
Solar/Wind Harmer
6.893
315733AD1-074 GEN2
Solar/Wind Harmer
6.893
315735AD1-075 GEN1
Solar/Wind Harmer
3.447
965291AG1-394 GEN
Solar/Wind Harmer
3.013
3146206CASHIE
Solar/Wind Harmer
-0.034
970601AG2-382 GEN
Solar/Wind Harmer
14.768
316318V4-068
Solar/Wind Harmer
0.839
3145893MURPHYS
Solar/Wind Harmer
-0.09
3145893MURPHYS
Solar/Wind Harmer
-0.034
3145513AHOSKIE
Solar/Wind Harmer
0.289
961941AG1-037 GEN
Solar/Wind Harmer
0.25
3145513AHOSKIE
Solar/Wind Harmer
-0.033
946281AF1-292 GEN
Solar/Wind Harmer
0.741
3145683EARLEYS
Solar/Wind Harmer
-0.066
3145683EARLEYS
Solar/Wind Harmer
-0.033
3145683EARLEYS
Solar/Wind Harmer
-0.033
3146043SEABORD
Solar/Wind Harmer
-0.033
315607AA1-063A GEN
Solar/Wind Harmer
3.327
316087AB2-174 GEN
Solar/Wind Harmer
4.68
315652AC1-086 GEN
Solar/Wind Harmer
36.606
3137643SOCKMAN
Solar/Wind Harmer
-0.129
3141813NORNECK
Solar/Wind Harmer
-0.032
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.013
3146033SCOT NK
Solar/Wind Harmer
-0.127
972205AH1-687 GEN
Adder
10.039
972193AH1-681 GEN
Adder
5.12
3151881LOWMORC
Adder
1.285
3151881LOWMORC
Adder
1.265
3151861LOWMORA
Adder
1.245
316164AC1-076 GEN
Solar/Wind Helper
1.978
316411AF1-147_GEN1
Solar/Wind Helper
1.078
316415AF1-147_GEN2
Solar/Wind Helper
1.078
3138216PACIFIC
Solar/Wind Helper
0.053
237085AD2-009_GEN
Solar/Wind Helper
1.439
238208AF1-136 C
Solar/Wind Helper
0.182
316254AC1-120 GEN1
Solar/Wind Helper
1.225
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.373
237080AD1-060 GEN
Solar/Wind Helper
0.304
237038AE2-054 C
Solar/Wind Helper
0.241
235062AE1-101 C1
Solar/Wind Helper
1.47
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
233964AF2-378 GEN
Solar/Wind Helper
0.04
232426Y1-080 FULL
Solar/Wind Helper
0.038
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.491
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.293
238148AE2-230_GEN2
Solar/Wind Helper
0.39
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
3152261N ANNA2
50/50
24.93
970497AG2-320 GEN
50/50
33.128
3150861SPRUNCD
50/50
1.706
971645AH1-323 GEN
50/50
30.891
3143096IRON208
50/50
1.529
3143096IRON208
50/50
1.499
3142416OLDCHRC
Solar/Wind Harmer
3.892
970293AG2-193 GEN
Solar/Wind Harmer
4.804
315839AE2-212 C
Solar/Wind Harmer
1.153
970133AG2-095 GEN
Solar/Wind Harmer
4.299
3142946ENON
Solar/Wind Harmer
-0.013
965281AG1-393 GEN
Solar/Wind Harmer
4.773
315773AC2-141 GEN
Solar/Wind Harmer
15.945
970129AG2-093 GEN
Solar/Wind Harmer
21.453
315778AD1-151 GEN
Solar/Wind Harmer
32.937
315813AE1-149 C
Solar/Wind Harmer
23.666
961611AG1-000B GEN
Solar/Wind Harmer
7.971
3151221GRAVEL6
Adder
24.448
3151171GRAVELC
Adder
4.704
316382AG1-145 C
Solar/Wind Harmer
1.138
3145336SMITFLD
Solar/Wind Harmer
-0.015
944581AF1-123 GEN
Solar/Wind Harmer
171.564
944601AF1-125 GEN
Solar/Wind Harmer
168.886
966881AG1-559 GEN
Solar/Wind Harmer
1.134
3144536CHRHLND
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
31.133
970659AG2-427 GEN
Solar/Wind Harmer
3.546
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144216WINCHST
Adder
1.263
316083AB2-161 GEN
Solar/Wind Harmer
6.107
3150921YORKTN3
Adder
8.413
970661AG2-428 GEN
Solar/Wind Harmer
7.064
316473AC1-191 GEN
Solar/Wind Harmer
4.017
3146456SLIGO L269
Solar/Wind Harmer
-0.037
971153AH1-033 GEN
Solar/Wind Harmer
4.542
3142433PROV 92
Adder
0.64
3142433PROV 92
Adder
0.64
3150401LDYSMT4
Adder
44.168
3150371LDYSMT1
Adder
42.678
316320Y1-086
Solar/Wind Harmer
2.162
316435W1029_GEN3
Solar/Wind Harmer
6.618
3146516WINFALL
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3147666LOUISA
Solar/Wind Harmer
-0.083
3141843SHACKLE
Adder
1.644
316203AE2-005 GEN
Solar/Wind Harmer
15.244
3141766HARMONY
Solar/Wind Harmer
3.217
3145273HOLLAND
Solar/Wind Harmer
-0.027
316280AD1-041 GEN
Solar/Wind Harmer
2.715
316156AD2-030 GEN
Solar/Wind Harmer
0.958
3141873WAN 176
Solar/Wind Harmer
4.258
3146376EDENTON
Solar/Wind Harmer
-0.035
316313AB2-026
Solar/Wind Harmer
0.943
316258AE1-075 C
Solar/Wind Harmer
0.849
316405AF2-144 C
Solar/Wind Harmer
0.895
3143336POWHATN
Solar/Wind Harmer
3.526
315614AA2-178 GEN
Solar/Wind Harmer
3.75
970917AG2-570 GEN
Solar/Wind Harmer
86.408
962971AG1-146 GEN
Solar/Wind Harmer
6.43
971157AH1-035 GEN
Solar/Wind Harmer
4.274
3156081AA2-088 GEN
Solar/Wind Harmer
11.067
315737AD1-076 GEN
Solar/Wind Harmer
6.478
316484AD2-074 GEN
Solar/Wind Harmer
8.542
970009AG2-005 GEN
Solar/Wind Harmer
4.242
316365GEN2_N
Solar/Wind Harmer
2.287
3146206CASHIE
Solar/Wind Harmer
-0.034
3145893MURPHYS
Solar/Wind Harmer
0.235
3145893MURPHYS
Solar/Wind Harmer
-0.034
957521AF2-046 GEN
Solar/Wind Harmer
26.442
961681AG1-008 GEN
Solar/Wind Harmer
26.442
3146173TUNIS
Solar/Wind Harmer
-0.033
316404AE1-155 C
Solar/Wind Harmer
6.434
3156021HOLLOMANSOL
Solar/Wind Harmer
4.485
316463AE2-346 GEN
Solar/Wind Harmer
0.537
316140AB2-099
Solar/Wind Harmer
0.224
962331AG1-082 GEN
Solar/Wind Harmer
4.15
966621AG1-532 GEN
Solar/Wind Harmer
0.671
3146263WOODLND
Solar/Wind Harmer
-0.033
313506AB2-031 GEN
Solar/Wind Harmer
2.628
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3145963POPLR C
Solar/Wind Harmer
-0.032
316317KELFORD C
Solar/Wind Harmer
1.529
3145823KELFORD
Solar/Wind Harmer
-0.032
3150351NORNECKC2
Adder
2.915
3147043LAWRENC
Solar/Wind Harmer
-0.019
3145796HORNRTN
Solar/Wind Harmer
-0.128
3145796HORNRTN
Solar/Wind Harmer
-0.032
316478AD1-087 GEN
Solar/Wind Harmer
2.758
316486AD2-202 GEN
Solar/Wind Harmer
0.808
971781AH1-399 GEN
Solar/Wind Harmer
1.944
316210AC1-098 GEN
Solar/Wind Harmer
4.912
3145933PARMELE
Solar/Wind Harmer
-0.031
966801AG1-551 GEN
Solar/Wind Harmer
3.899
3144293JTRSVLE
Adder
0.837
972255AH1-712 GEN
Adder
114.59
3151761LOISA E
Adder
23.168
972183AH1-676 GEN
Adder
179.308
3141316ARNOLDS
Adder
0.38
3150331BIRCHWDA
Adder
23.913
3151861LOWMORA
Adder
1.295
316044AC1-158 PL1
Solar/Wind Helper
4.732
316450AC1-158 RIC
Solar/Wind Helper
1.262
3141196NOKESVL
Solar/Wind Helper
1.429
227287AC2-120 GEN
Solar/Wind Helper
0.373
226910AB2-157 C
Solar/Wind Helper
0.015
316170AC1-121 GEN2
Solar/Wind Helper
0.408
237030AB1-096 C
Solar/Wind Helper
0.069
223402AF1-300 C
Solar/Wind Helper
0.373
238221AF1-254 C O1
Solar/Wind Helper
0.245
235067AD1-061 GEN
Solar/Wind Helper
0.438
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.487
233982AB2-133 GEN
Solar/Wind Helper
0.347
233994AC2-023 GEN
Solar/Wind Helper
0.931
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.491
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
238147AE2-230_GEN1
Solar/Wind Helper
0.388
238149AF1-291A_GEN
Solar/Wind Helper
0.111
230430AE1-229_GEN
Solar/Wind Helper
3.252
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.106
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
959561AF2-247 GEN
Solar/Wind Helper
0.02
971133AH1-012 GEN
50/50
6.819
3142296MT RD221
50/50
1.172
3142366NRTHEST
50/50
1.196
3150691DARBY 3
50/50
26.261
3150701DARBY 4
50/50
26.199
3150681DARBY 2
50/50
26.169
971223AH1-071 GEN
Solar/Wind Harmer
5.08
3143526WINTERP
Solar/Wind Harmer
-0.207
3150671DARBY 1
Adder
24.633
944641AF1-129 GEN
Adder
162.93
316240AF1-291 C
Solar/Wind Harmer
1.156
316075AC2-137 C
Solar/Wind Harmer
1.03
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
12.245
315697AD1-025 GEN
Solar/Wind Harmer
7.68
316236AE1-162_GEN
Solar/Wind Harmer
1.137
957411AF2-035 GEN
Solar/Wind Harmer
16.975
970317AG2-208 GEN
Solar/Wind Harmer
16.504
316036AC1-147 C
Solar/Wind Harmer
1.016
3150991CHESPKB
Adder
3.511
3150991CHESPKB
Adder
3.427
316316AC1-027 C
Solar/Wind Harmer
1.154
3142956BIRDNECK
Solar/Wind Harmer
2.018
970657AG2-426 GEN
Solar/Wind Harmer
11.745
970657AG2-426 GEN
Solar/Wind Harmer
2.456
316185AD1-033 GEN
Solar/Wind Harmer
3.963
3145506HICKORY
Solar/Wind Harmer
-0.149
3145506HICKORY
Solar/Wind Harmer
-0.09
3145506HICKORY
Solar/Wind Harmer
-0.022
315673AE1-157 GEN
Solar/Wind Harmer
28.094
316339AD2-160 GEN
Solar/Wind Harmer
2.52
966871AG1-558 GEN
Solar/Wind Harmer
1.122
966871AG1-558 GEN
Solar/Wind Harmer
0.384
316018AA1-139 ULT2
Solar/Wind Harmer
3.198
316017AA1-139 ULT1
Solar/Wind Harmer
3.021
3137176SLIGO L2192
Solar/Wind Harmer
-0.147
3146456SLIGO L269
Solar/Wind Harmer
4.4
3130086AYDLETT
Solar/Wind Harmer
-0.148
3150391LDYSMT3
Adder
44.085
972195AH1-682 GEN
Adder
5.793
3146386ELIZ CT
Solar/Wind Harmer
-0.037
3144356SAPONY
Solar/Wind Harmer
1.276
316431W1029_GEN1
Solar/Wind Harmer
6.618
316433W1029_GEN2
Solar/Wind Harmer
6.618
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146516WINFALL
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
3146626S HERTFORD
Solar/Wind Harmer
-0.036
972185AH1-677 GEN
Adder
18.085
316441AF1-014 GEN
Solar/Wind Harmer
2.437
972187AH1-678 GEN
Adder
9.074
315742AE1-103 GEN
Solar/Wind Harmer
3.731
3146376EDENTON
Solar/Wind Harmer
1.053
3146376EDENTON
Solar/Wind Harmer
1.053
970933AG2-581 GEN
Solar/Wind Harmer
33.038
316487AF1-042 GEN
Solar/Wind Harmer
4.47
316065AD1-022 GEN
Solar/Wind Harmer
16.937
3145893MURPHYS
Solar/Wind Harmer
0.939
3145893MURPHYS
Solar/Wind Harmer
-0.06
3146173TUNIS
Solar/Wind Harmer
-0.033
3146173TUNIS
Solar/Wind Harmer
-0.033
958261AF2-120 GEN
Solar/Wind Harmer
12.924
970099AG2-077 GEN
Solar/Wind Harmer
41.32
316181AB2-040 GEN
Solar/Wind Harmer
4.56
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.033
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.274
316077AC2-138 C
Solar/Wind Harmer
0.682
3150341NORNECKC1
Adder
3.012
3150341NORNECKC1
Adder
2.987
3145593CAROLNA
Solar/Wind Harmer
-0.032
3145593CAROLNA
Solar/Wind Harmer
-0.032
966811AG1-552 GEN
Solar/Wind Harmer
3.63
3145593CAROLNA
Solar/Wind Harmer
0.268
3145783HORNRTN
Solar/Wind Harmer
3.807
3145783HORNRTN
Solar/Wind Harmer
3.046
3145783HORNRTN
Solar/Wind Harmer
0.952
3145783HORNRTN
Solar/Wind Harmer
0.381
3145796HORNRTN
Solar/Wind Harmer
-0.096
316468AD1-105 GEN
Solar/Wind Harmer
3.513
3145933PARMELE
Solar/Wind Harmer
-0.062
3145933PARMELE
Solar/Wind Harmer
-0.031
316274AC1-208 GEN
Solar/Wind Harmer
3.354
3144293JTRSVLE
Adder
0.837
3144293JTRSVLE
Adder
0.705
3151731LOISA B
Adder
11.364
3151721LOISA A
Adder
11.305
316447AC1-158 HLD
Solar/Wind Helper
10.414
315651AD1-115 GEN
Solar/Wind Helper
0.939
226929AD2-058 GEN
Solar/Wind Helper
0.108
23777801MSM_W1-116
Solar/Wind Helper
0.111
237025AB1-124 C
Solar/Wind Helper
0.161
237006AB1-125 GEN
Solar/Wind Helper
0.121
237034AC2-136 C
Solar/Wind Helper
0.211
23777901MDS_W4-102
Solar/Wind Helper
0.157
235020AA1-095 C
Solar/Wind Helper
0.046
237001AB1-127_GEN
Solar/Wind Helper
0.396
237002AB1-128_GEN
Solar/Wind Helper
0.396
235063AE1-101 C2
Solar/Wind Helper
1.47
238175AF1-290_GEN
Solar/Wind Helper
0.127
238169AE2-226 GEN1
Solar/Wind Helper
0.578
238170AE2-226 GEN2
Solar/Wind Helper
0.578
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.656
233933AB2-153 GEN
Solar/Wind Helper
0.225
233987AB2-037 GEN
Solar/Wind Helper
2.269
233944AB2-135 GEN
Solar/Wind Helper
0.57
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.55
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.491
232410W1-006 C
Solar/Wind Helper
0.491
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
20390526W1-045 C
Solar/Wind Helper
0.327
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
960921AF2-383 GEN
Solar/Wind Helper
0.176
205943AE1-185 GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.23
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.928
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.799
232432Z2-076 GEN
Solar/Wind Helper
0.065
959381AF2-229 GEN
Solar/Wind Helper
0.334
238152AF2-075_GEN
Solar/Wind Helper
0.554
964001AG1-254 GEN
Solar/Wind Helper
0.922
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
970831AG2-522 GEN
Solar/Wind Harmer
4.516
NYPJM->LTFIMP_NY
CLTF
4.79
LAGNLTFEXP_LAGN->PJM
CLTF
12.471
LGEELTFEXP_LGEE->PJM
CLTF
2.231
WECLTFEXP_WEC->PJM
CLTF
1.099
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.435
TVALTFEXP_TVA->PJM
CLTF
6.314
CPLELTFEXP_CPLE->PJM
CLTF
16.95
CBM West 2LTFEXP_CBM-W2->PJM
CBM
65.721
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.411
CBM South 1LTFEXP_CBM-S1->PJM
CBM
21.636
MECLTFEXP_MEC->PJM
CLTF
5.976
SIGELTFEXP_SIGE->PJM
CLTF
0.183

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.96 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6893.4
MW Contribution:15.77
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
31.961
970119AG2-088 GEN
50/50
40.696
315243AE2-183_GT3
50/50
4.555
3151051BRUNSWICKS1
50/50
7.445
3151021BRUNSWICKG1
50/50
3.587
971451AH1-221 GEN
50/50
10.895
3150981CHESPKA
50/50
3.363
3147666LOUISA
Solar/Wind Harmer
-0.188
316192AB2-158 GEN
Solar/Wind Harmer
5.479
3143226MDLTHAN
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
30.211
3143526WINTERP
Solar/Wind Harmer
-0.162
939411AE1-173 GEN
Solar/Wind Harmer
156.554
3143336POWHATN
Solar/Wind Harmer
3.513
970919AG2-571 GEN
Solar/Wind Harmer
9.325
970087AG2-069 GEN
Solar/Wind Harmer
27.507
316294AC1-161 GEN
Solar/Wind Harmer
9.352
944591AF1-124 GEN
Solar/Wind Harmer
131.161
316375AC2-012 GEN
Solar/Wind Harmer
9.869
316388AE2-253 GEN
Solar/Wind Harmer
1.918
3146456SLIGO L269
Solar/Wind Harmer
-0.028
316336AC2-165 C
Solar/Wind Harmer
4.931
316246AF1-032 C
Solar/Wind Harmer
0.572
316381AD1-082 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
14.969
316303AF2-085
50/50
5.426
315244AE2-183_ST
50/50
7.875
963041AG1-153 GEN
50/50
7.263
315779AE2-040
50/50
3.636
3151081ELIZAR1
50/50
24.718
3151091ELIZAR2
50/50
24.289
941591AE2-156 GEN
50/50
22.58
3152611GOSPORTB
50/50
3.43
3152621GOSPORTC
50/50
2.911
3152601GOSPORTA
50/50
2.685
941031AE2-094 GEN
Solar/Wind Harmer
59.691
944011AF1-069 GEN
Solar/Wind Harmer
18.703
316233AE1-074 FULL
Solar/Wind Harmer
0.843
971281AH1-106 GEN
Solar/Wind Harmer
5.091
971283AH1-107 GEN
Solar/Wind Harmer
5.091
970673AG2-436 GEN
Solar/Wind Harmer
65.689
970673AG2-436 GEN
Solar/Wind Harmer
33.26
971967AH1-528 GEN
Solar/Wind Harmer
58.02
970085AG2-068 GEN
Solar/Wind Harmer
18.338
970581AG2-369 GEN
Solar/Wind Harmer
15.771
316315AB2-025 C
Solar/Wind Harmer
0.79
315814AE2-033 C
Solar/Wind Harmer
27.155
3143316POE
Solar/Wind Harmer
-0.114
957871AF2-081 GEN
Solar/Wind Harmer
14.21
319010AE1-072 C
Solar/Wind Harmer
5.736
3146406KITTY HAWK
Solar/Wind Harmer
0.024
316305AF2-043 C
Solar/Wind Harmer
0.853
315833AF1-017_GEN
Solar/Wind Harmer
5.349
316349AD2-085 GEN
Solar/Wind Harmer
2.505
316311AC2-079 GEN
Solar/Wind Harmer
14.204
313526AB2-022
Solar/Wind Harmer
0.759
315835AF2-110_GEN
Solar/Wind Harmer
3.519
3146486SUNBURY
Solar/Wind Harmer
-0.028
3146486SUNBURY
Solar/Wind Harmer
-0.028
316321Z2-027
Solar/Wind Harmer
0.757
3146396TANGLEW
Solar/Wind Harmer
0.516
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971285AH1-108 GEN
Adder
1.882
971445AH1-216 GEN
Solar/Wind Harmer
17.213
315611Z1-036_GEN2
Solar/Wind Harmer
6.81
972265AH1-717 GEN
Adder
18.958
3151201GRAVEL4
Adder
17.771
3151191GRAVEL3
Adder
17.547
3151211GRAVEL5
Adder
17.547
3130156CHOWAN
Solar/Wind Harmer
-0.027
3130156CHOWAN
Solar/Wind Harmer
-0.027
316369SG1_INVT
Solar/Wind Harmer
4.832
315816AE2-034 GEN
Solar/Wind Harmer
2.176
316132AB2-190 GEN1
Solar/Wind Harmer
2.713
965291AG1-394 GEN
Solar/Wind Harmer
2.36
946281AF1-292 GEN
Solar/Wind Harmer
0.595
3152261N ANNA2
50/50
31.958
3151031BRUNSWICKG2
50/50
3.587
3151101ELIZAR3
50/50
25.035
3147666LOUISA
Solar/Wind Harmer
-0.108
316313AB2-026
Solar/Wind Harmer
0.798
316258AE1-075 C
Solar/Wind Harmer
0.719
316405AF2-144 C
Solar/Wind Harmer
0.758
3143336POWHATN
Solar/Wind Harmer
2.986
970917AG2-570 GEN
Solar/Wind Harmer
73.668
315773AC2-141 GEN
Solar/Wind Harmer
12.096
944581AF1-123 GEN
Solar/Wind Harmer
130.69
944601AF1-125 GEN
Solar/Wind Harmer
128.65
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.028
971153AH1-033 GEN
Solar/Wind Harmer
3.459
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.615
316083AB2-161 GEN
Solar/Wind Harmer
4.573
970659AG2-427 GEN
Solar/Wind Harmer
2.653
970661AG2-428 GEN
Solar/Wind Harmer
5.305
316320Y1-086
Solar/Wind Harmer
1.65
3150861SPRUNCD
Adder
1.15
316435W1029_GEN3
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.011
315839AE2-212 C
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3145273HOLLAND
Solar/Wind Harmer
-0.021
965281AG1-393 GEN
Solar/Wind Harmer
3.435
3151221GRAVEL6
Adder
17.751
3151171GRAVELC
Adder
3.415
3146376EDENTON
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
5.745
316365GEN2_N
Solar/Wind Harmer
1.828
316478AD1-087 GEN
Solar/Wind Harmer
2.335
316486AD2-202 GEN
Solar/Wind Harmer
0.684
315778AD1-151 GEN
Solar/Wind Harmer
23.348
315614AA2-178 GEN
Solar/Wind Harmer
2.901
970129AG2-093 GEN
Solar/Wind Harmer
15.087
3156081AA2-088 GEN
Solar/Wind Harmer
8.655
3151761LOISA E
Adder
31.328
970133AG2-095 GEN
Solar/Wind Harmer
2.99
966621AG1-532 GEN
Solar/Wind Harmer
0.539
3144216WINCHST
Adder
0.891
971157AH1-035 GEN
Solar/Wind Harmer
3.319
315737AD1-076 GEN
Solar/Wind Harmer
5.035
3150921YORKTN3
Adder
5.907
3145893MURPHYS
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.741
961681AG1-008 GEN
Solar/Wind Harmer
20.741
3146206CASHIE
Solar/Wind Harmer
-0.026
313506AB2-031 GEN
Solar/Wind Harmer
2.107
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.422
316140AB2-099
Solar/Wind Harmer
0.176
962331AG1-082 GEN
Solar/Wind Harmer
3.26
3156021HOLLOMANSOL
Solar/Wind Harmer
3.513
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3146263WOODLND
Solar/Wind Harmer
-0.026
970909AG2-566 GEN
Solar/Wind Harmer
2.462
3143096IRON208
Adder
0.962
3143096IRON208
Adder
0.943
316317KELFORD C
Solar/Wind Harmer
1.207
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.026
972183AH1-676 GEN
Adder
243.274
316382AG1-145 C
Solar/Wind Harmer
0.77
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
3.914
316131AB2-060 GEN
Solar/Wind Harmer
2.677
964241AG1-285 GEN
Solar/Wind Harmer
19.386
315785AD2-033 C
Solar/Wind Harmer
5.622
970257AG2-171 GEN
Solar/Wind Harmer
9.302
959311AF2-222 GEN
Solar/Wind Harmer
25.891
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.625
972255AH1-712 GEN
Adder
63.154
316044AC1-158 PL1
Solar/Wind Helper
3.502
316450AC1-158 RIC
Solar/Wind Helper
0.934
3141196NOKESVL
Solar/Wind Helper
1.078
227287AC2-120 GEN
Solar/Wind Helper
0.305
226910AB2-157 C
Solar/Wind Helper
0.012
970661AG2-428 GEN
Solar/Wind Harmer
29.933
316093AE2-104_GEN
Solar/Wind Harmer
8.186
957481AF2-042 GEN
Solar/Wind Harmer
87.747
3150851SPRUNCC
Adder
1.15
316072AD1-144
Solar/Wind Harmer
0.567
3146516WINFALL
Solar/Wind Harmer
-0.09
3146516WINFALL
Solar/Wind Harmer
-0.028
3145336SMITFLD
Solar/Wind Harmer
-0.111
315800Z1-036_GEN1
Solar/Wind Harmer
6.81
315693AD1-088 GEN
Solar/Wind Harmer
13.752
3151171GRAVELC
Adder
2.597
962491AG1-098 GEN
Solar/Wind Harmer
18.339
3130156CHOWAN
Solar/Wind Harmer
-0.027
961611AG1-000B GEN
Solar/Wind Harmer
13.464
315671AE2-027_GEN
Solar/Wind Harmer
20.456
971647AH1-324 GEN
Solar/Wind Harmer
13.581
316023GEN1_S
Solar/Wind Harmer
1.828
971069AG2-661 GEN
Solar/Wind Harmer
4.264
3145663CRESWEL
Solar/Wind Harmer
-0.075
971163AH1-040 GEN
Solar/Wind Harmer
25.206
316458AB2-190 GEN2
Solar/Wind Harmer
2.713
970129AG2-093 GEN
Solar/Wind Harmer
6.111
3151751LOISA D
Adder
15.367
960081AF2-299 GEN
Solar/Wind Harmer
2.989
3138126ROCKLANDING
Solar/Wind Harmer
0.081
3142543TWELFTH
Solar/Wind Harmer
-0.003
3145893MURPHYS
Solar/Wind Harmer
-0.105
3145893MURPHYS
Solar/Wind Harmer
0.783
3146206CASHIE
Solar/Wind Harmer
-0.026
971547AH1-271 GEN
Solar/Wind Harmer
6.58
971795AH1-408 GEN
Solar/Wind Harmer
19.653
3146173TUNIS
Solar/Wind Harmer
-0.026
3147043LAWRENC
Adder
2.097
3145683EARLEYS
Solar/Wind Harmer
-0.026
316011AB1-132 GEN
Solar/Wind Harmer
5.429
962571AG1-106 GEN
Solar/Wind Harmer
3.73
3146263WOODLND
Solar/Wind Harmer
-0.026
316190AA2-174 GEN
Solar/Wind Harmer
0.317
3143096IRON208
Adder
0.962
971317AH1-138 GEN
Solar/Wind Harmer
3.222
3145783HORNRTN
Solar/Wind Harmer
-0.026
3145823KELFORD
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.084
3145796HORNRTN
Solar/Wind Harmer
-0.026
316159AE1-175 C
Solar/Wind Harmer
0.686
3145963POPLR C
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
107.977
315687AD1-152 GEN
Solar/Wind Harmer
3.055
316174AB2-169 GEN
Solar/Wind Harmer
3.908
970937AG2-583 GEN
Solar/Wind Harmer
18.128
316129AC1-054 GEN
Solar/Wind Harmer
2.211
971065AG2-659 GEN
Solar/Wind Harmer
12.582
316212AC1-099_GEN
Solar/Wind Harmer
2.175
970685AG2-442 GEN
Solar/Wind Harmer
21.702
3144293JTRSVLE
Adder
0.703
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
3141843SHACKLE
Adder
1.042
3150351NORNECKC2
Adder
1.599
972277AH1-723 GEN
Adder
73.593
316045AC1-158 PL2
Solar/Wind Helper
11.209
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.358
315733AD1-074 GEN2
Solar/Wind Harmer
5.358
315735AD1-075 GEN1
Solar/Wind Harmer
2.68
316318V4-068
Solar/Wind Harmer
0.658
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
-0.026
3146206CASHIE
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
11.515
316087AB2-174 GEN
Solar/Wind Harmer
3.755
3146043SEABORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.638
3145513AHOSKIE
Solar/Wind Harmer
0.227
961941AG1-037 GEN
Solar/Wind Harmer
0.196
3145513AHOSKIE
Solar/Wind Harmer
-0.026
3137643SOCKMAN
Solar/Wind Harmer
-0.103
3145683EARLEYS
Solar/Wind Harmer
-0.052
3145683EARLEYS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.026
315652AC1-086 GEN
Solar/Wind Harmer
29.194
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.637
3146033SCOT NK
Solar/Wind Harmer
-0.1
971443AH1-215 GEN
Solar/Wind Harmer
4.884
3144303KENBRDG
Solar/Wind Harmer
-0.02
3147346CASHSCORNER
Solar/Wind Harmer
0.384
3142433PROV 92
Adder
0.412
3142433PROV 92
Adder
0.412
972205AH1-687 GEN
Adder
8.575
972189AH1-679 GEN
Adder
2.228
972193AH1-681 GEN
Adder
2.822
316411AF1-147_GEN1
Solar/Wind Helper
0.847
316415AF1-147_GEN2
Solar/Wind Helper
0.847
3138216PACIFIC
Solar/Wind Helper
0.041
316164AC1-076 GEN
Solar/Wind Helper
1.148
970683AG2-441 GEN
Solar/Wind Harmer
5.411
970681AG2-440 GEN
Solar/Wind Harmer
4.329
971133AH1-012 GEN
50/50
8.834
970533AG2-339 GEN
50/50
25.186
970531AG2-338 GEN
50/50
10.074
315242AE2-183_GT2
50/50
4.555
315241AE2-183_GT1
50/50
4.527
972185AH1-677 GEN
50/50
16.42
3151041BRUNSWICKG3
50/50
3.587
972187AH1-678 GEN
50/50
8.232
3150991CHESPKB
50/50
2.821
3150991CHESPKB
50/50
2.753
971223AH1-071 GEN
Solar/Wind Harmer
4.287
3143526WINTERP
Solar/Wind Harmer
-0.162
970933AG2-581 GEN
Solar/Wind Harmer
28.21
3144356SAPONY
Solar/Wind Harmer
1.021
316185AD1-033 GEN
Solar/Wind Harmer
3.013
3142956BIRDNECK
Solar/Wind Harmer
1.531
316316AC1-027 C
Solar/Wind Harmer
0.876
316036AC1-147 C
Solar/Wind Harmer
0.769
3145506HICKORY
Solar/Wind Harmer
-0.113
3145506HICKORY
Solar/Wind Harmer
-0.068
3145506HICKORY
Solar/Wind Harmer
-0.017
316339AD2-160 GEN
Solar/Wind Harmer
1.918
316018AA1-139 ULT2
Solar/Wind Harmer
2.435
316017AA1-139 ULT1
Solar/Wind Harmer
2.3
3137176SLIGO L2192
Solar/Wind Harmer
-0.112
3146456SLIGO L269
Solar/Wind Harmer
3.351
3130086AYDLETT
Solar/Wind Harmer
-0.113
970657AG2-426 GEN
Solar/Wind Harmer
8.805
970657AG2-426 GEN
Solar/Wind Harmer
1.841
3146386ELIZ CT
Solar/Wind Harmer
-0.028
970099AG2-077 GEN
Solar/Wind Harmer
35.099
316431W1029_GEN1
Solar/Wind Harmer
5.059
316433W1029_GEN2
Solar/Wind Harmer
5.059
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.028
316236AE1-162_GEN
Solar/Wind Harmer
0.839
3146626S HERTFORD
Solar/Wind Harmer
-0.028
3146626S HERTFORD
Solar/Wind Harmer
-0.028
315742AE1-103 GEN
Solar/Wind Harmer
2.873
3146376EDENTON
Solar/Wind Harmer
0.811
3146376EDENTON
Solar/Wind Harmer
0.811
316240AF1-291 C
Solar/Wind Harmer
0.819
316033AB2-134 GEN
Solar/Wind Harmer
8.722
315697AD1-025 GEN
Solar/Wind Harmer
5.47
944641AF1-129 GEN
Adder
114.368
3151731LOISA B
Adder
15.367
3151721LOISA A
Adder
15.287
3145893MURPHYS
Solar/Wind Harmer
0.736
3145893MURPHYS
Solar/Wind Harmer
-0.047
316065AD1-022 GEN
Solar/Wind Harmer
13.191
971741AH1-377 GEN
Solar/Wind Harmer
30.569
316181AB2-040 GEN
Solar/Wind Harmer
3.656
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
970301AG2-198 GEN
Solar/Wind Harmer
12.968
316426AA2-053 GEN
Solar/Wind Harmer
2.61
3145593CAROLNA
Solar/Wind Harmer
-0.026
3145593CAROLNA
Solar/Wind Harmer
-0.026
966811AG1-552 GEN
Solar/Wind Harmer
2.903
3145593CAROLNA
Solar/Wind Harmer
0.214
3145783HORNRTN
Solar/Wind Harmer
3.044
3145783HORNRTN
Solar/Wind Harmer
2.436
3145783HORNRTN
Solar/Wind Harmer
0.761
3145783HORNRTN
Solar/Wind Harmer
0.304
3145796HORNRTN
Solar/Wind Harmer
-0.076
3142946ENON
Solar/Wind Harmer
-0.003
939181AE1-148 GEN
Solar/Wind Harmer
13.998
316274AC1-208 GEN
Solar/Wind Harmer
2.681
313527AB2-043 GEN
Solar/Wind Harmer
4.032
316034AC1-036 C
Solar/Wind Harmer
0.46
970323AG2-213 GEN
Solar/Wind Harmer
12.403
971775AH1-396 GEN
Solar/Wind Harmer
1.766
3144293JTRSVLE
Adder
0.703
3144293JTRSVLE
Adder
0.592
3142366NRTHEST
Adder
0.712
3150691DARBY 3
Adder
15.594
3150701DARBY 4
Adder
15.558
3150681DARBY 2
Adder
15.54
3150671DARBY 1
Adder
15.522
3142296MT RD221
Adder
0.637
3150341NORNECKC1
Adder
1.679
3150341NORNECKC1
Adder
1.666
316447AC1-158 HLD
Solar/Wind Helper
7.707
226929AD2-058 GEN
Solar/Wind Helper
0.088
NYPJM->LTFIMP_NY
CLTF
3.837
LAGNLTFEXP_LAGN->PJM
CLTF
9.821
LGEELTFEXP_LGEE->PJM
CLTF
1.676
WECLTFEXP_WEC->PJM
CLTF
0.823
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.397
TVALTFEXP_TVA->PJM
CLTF
4.963
CPLELTFEXP_CPLE->PJM
CLTF
13.878
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.117
CBM West 1LTFEXP_CBM-W1->PJM
CBM
27.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.931
MECLTFEXP_MEC->PJM
CLTF
4.554
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: 57502_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57502_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:169.18 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5274.99
MW Contribution:12.9
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
32.427
3151031BRUNSWICKG2
50/50
2.942
3151771S ANNAG1
50/50
0.782
3151801S ANNAS2
50/50
0.402
3151761LOISA E
50/50
29.536
972183AH1-676 GEN
50/50
229.088
3147666LOUISA
Solar/Wind Harmer
-0.097
316313AB2-026
Solar/Wind Harmer
0.652
316258AE1-075 C
Solar/Wind Harmer
0.587
316405AF2-144 C
Solar/Wind Harmer
0.619
3143336POWHATN
Solar/Wind Harmer
2.437
970917AG2-570 GEN
Solar/Wind Harmer
60.26
316478AD1-087 GEN
Solar/Wind Harmer
1.891
316486AD2-202 GEN
Solar/Wind Harmer
0.554
944581AF1-123 GEN
Solar/Wind Harmer
97.831
944601AF1-125 GEN
Solar/Wind Harmer
96.304
315773AC2-141 GEN
Solar/Wind Harmer
8.987
3151101ELIZAR3
Adder
17.61
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.021
971153AH1-033 GEN
Solar/Wind Harmer
2.591
316365GEN2_N
Solar/Wind Harmer
1.431
316320Y1-086
Solar/Wind Harmer
1.238
970661AG2-428 GEN
Solar/Wind Harmer
3.976
316083AB2-161 GEN
Solar/Wind Harmer
3.427
970659AG2-427 GEN
Solar/Wind Harmer
1.988
315813AE1-149 C
Solar/Wind Harmer
13.193
3144536CHRHLND
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
3.804
3146516WINFALL
Solar/Wind Harmer
-0.021
3145273HOLLAND
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.021
970909AG2-566 GEN
Solar/Wind Harmer
1.979
966621AG1-532 GEN
Solar/Wind Harmer
0.423
3150861SPRUNCD
Adder
0.848
315839AE2-212 C
Solar/Wind Harmer
0.622
3146376EDENTON
Solar/Wind Harmer
-0.021
3147043LAWRENC
Solar/Wind Harmer
-0.012
313506AB2-031 GEN
Solar/Wind Harmer
1.647
3145336SMITFLD
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
6.634
315614AA2-178 GEN
Solar/Wind Harmer
2.202
3145893MURPHYS
Solar/Wind Harmer
0.141
3145893MURPHYS
Solar/Wind Harmer
-0.02
957521AF2-046 GEN
Solar/Wind Harmer
15.928
961681AG1-008 GEN
Solar/Wind Harmer
15.928
971157AH1-035 GEN
Solar/Wind Harmer
2.527
965281AG1-393 GEN
Solar/Wind Harmer
2.525
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
315737AD1-076 GEN
Solar/Wind Harmer
3.836
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
316463AE2-346 GEN
Solar/Wind Harmer
0.324
316140AB2-099
Solar/Wind Harmer
0.135
962331AG1-082 GEN
Solar/Wind Harmer
2.506
3146263WOODLND
Solar/Wind Harmer
-0.02
3156021HOLLOMANSOL
Solar/Wind Harmer
2.693
3151221GRAVEL6
Adder
12.908
3151171GRAVELC
Adder
2.483
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.02
3146926FARMVIL
Solar/Wind Harmer
-0.012
942461AE2-259 GEN
Solar/Wind Harmer
2.971
3147133PAMPLIN
Solar/Wind Harmer
-0.062
971193AH1-056 GEN
Solar/Wind Harmer
12.355
963181AG1-167 GEN
Solar/Wind Harmer
1.853
3144293JTRSVLE
Adder
0.56
959311AF2-222 GEN
Solar/Wind Harmer
20.628
970257AG2-171 GEN
Solar/Wind Harmer
7.411
961611AG1-000B GEN
Solar/Wind Harmer
4.161
315785AD2-033 C
Solar/Wind Harmer
4.478
964241AG1-285 GEN
Solar/Wind Harmer
15.437
316317KELFORD C
Solar/Wind Harmer
0.931
3145823KELFORD
Solar/Wind Harmer
-0.02
316131AB2-060 GEN
Solar/Wind Harmer
2.132
3145963POPLR C
Solar/Wind Harmer
-0.019
3144216WINCHST
Adder
0.63
3150921YORKTN3
Adder
4.159
3143096IRON208
Adder
0.665
3143096IRON208
Adder
0.651
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
3141843SHACKLE
Adder
0.703
316044AC1-158 PL1
Solar/Wind Helper
3.277
316450AC1-158 RIC
Solar/Wind Helper
0.874
3152251N ANNA1
50/50
32.429
970119AG2-088 GEN
50/50
33.739
315243AE2-183_GT3
50/50
3.74
3151051BRUNSWICKS1
50/50
6.107
3151021BRUNSWICKG1
50/50
2.942
971451AH1-221 GEN
50/50
8.937
3151791S ANNAG2
50/50
0.782
3151781S ANNAS1
50/50
0.402
3151741LOISA C
50/50
0.792
3151751LOISA D
50/50
14.488
3147666LOUISA
Solar/Wind Harmer
-0.169
316192AB2-158 GEN
Solar/Wind Harmer
4.93
3143226MDLTHAN
Solar/Wind Harmer
-0.028
940641AE2-051 GEN
Solar/Wind Harmer
24.512
939411AE1-173 GEN
Solar/Wind Harmer
124.766
3143526WINTERP
Solar/Wind Harmer
-0.128
3143336POWHATN
Solar/Wind Harmer
2.867
970919AG2-571 GEN
Solar/Wind Harmer
7.628
970087AG2-069 GEN
Solar/Wind Harmer
22.494
316336AC2-165 C
Solar/Wind Harmer
4.004
957481AF2-042 GEN
Solar/Wind Harmer
71.332
315693AD1-088 GEN
Solar/Wind Harmer
11.147
962491AG1-098 GEN
Solar/Wind Harmer
14.859
944591AF1-124 GEN
Solar/Wind Harmer
98.183
316294AC1-161 GEN
Solar/Wind Harmer
6.948
316388AE2-253 GEN
Solar/Wind Harmer
1.436
316375AC2-012 GEN
Solar/Wind Harmer
7.364
3150981CHESPKA
Adder
2.365
3146456SLIGO L269
Solar/Wind Harmer
-0.021
316023GEN1_S
Solar/Wind Harmer
1.431
316246AF1-032 C
Solar/Wind Harmer
0.429
316093AE2-104_GEN
Solar/Wind Harmer
6.144
970661AG2-428 GEN
Solar/Wind Harmer
22.438
316381AD1-082 GEN
Solar/Wind Harmer
1.936
970659AG2-427 GEN
Solar/Wind Harmer
11.217
3146516WINFALL
Solar/Wind Harmer
-0.068
3146516WINFALL
Solar/Wind Harmer
-0.021
960081AF2-299 GEN
Solar/Wind Harmer
2.343
316072AD1-144
Solar/Wind Harmer
0.421
315800Z1-036_GEN1
Solar/Wind Harmer
5.136
3150851SPRUNCC
Adder
0.848
3130156CHOWAN
Solar/Wind Harmer
-0.021
971795AH1-408 GEN
Solar/Wind Harmer
15.455
3147043LAWRENC
Adder
1.651
3145336SMITFLD
Solar/Wind Harmer
-0.081
315687AD1-152 GEN
Solar/Wind Harmer
2.461
3145663CRESWEL
Solar/Wind Harmer
-0.057
971163AH1-040 GEN
Solar/Wind Harmer
19.129
3145893MURPHYS
Solar/Wind Harmer
-0.081
3145893MURPHYS
Solar/Wind Harmer
0.601
316011AB1-132 GEN
Solar/Wind Harmer
4.229
962571AG1-106 GEN
Solar/Wind Harmer
2.906
970937AG2-583 GEN
Solar/Wind Harmer
14.494
3146173TUNIS
Solar/Wind Harmer
-0.02
3146206CASHIE
Solar/Wind Harmer
-0.02
971547AH1-271 GEN
Solar/Wind Harmer
5.026
316190AA2-174 GEN
Solar/Wind Harmer
0.247
3146263WOODLND
Solar/Wind Harmer
-0.02
3145783HORNRTN
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
3151171GRAVELC
Adder
1.889
3145796HORNRTN
Solar/Wind Harmer
-0.065
3145796HORNRTN
Solar/Wind Harmer
-0.02
315671AE2-027_GEN
Solar/Wind Harmer
14.951
316129AC1-054 GEN
Solar/Wind Harmer
1.746
971065AG2-659 GEN
Solar/Wind Harmer
9.947
3146926FARMVIL
Solar/Wind Harmer
-0.012
963171AG1-166 GEN
Solar/Wind Harmer
2.471
971563AH1-280 GEN
Solar/Wind Harmer
2.471
3144293JTRSVLE
Adder
0.56
970685AG2-442 GEN
Solar/Wind Harmer
17.294
961611AG1-000B GEN
Solar/Wind Harmer
9.753
3145823KELFORD
Solar/Wind Harmer
-0.02
316237AB2-079_GEN
Solar/Wind Harmer
0.594
971647AH1-324 GEN
Solar/Wind Harmer
9.808
3145963POPLR C
Solar/Wind Harmer
-0.019
3143096IRON208
Adder
0.665
944631AF1-128 GEN
Adder
73.735
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
3141843SHACKLE
Adder
0.703
316045AC1-158 PL2
Solar/Wind Helper
10.491
316303AF2-085
50/50
4.498
315244AE2-183_ST
50/50
6.466
963041AG1-153 GEN
50/50
5.958
315779AE2-040
50/50
2.865
941031AE2-094 GEN
Solar/Wind Harmer
49.114
944011AF1-069 GEN
Solar/Wind Harmer
15.389
970673AG2-436 GEN
Solar/Wind Harmer
53.974
970673AG2-436 GEN
Solar/Wind Harmer
27.329
971967AH1-528 GEN
Solar/Wind Harmer
47.608
316233AE1-074 FULL
Solar/Wind Harmer
0.665
971281AH1-106 GEN
Solar/Wind Harmer
4.02
971283AH1-107 GEN
Solar/Wind Harmer
4.02
970085AG2-068 GEN
Solar/Wind Harmer
14.996
970581AG2-369 GEN
Solar/Wind Harmer
12.896
316315AB2-025 C
Solar/Wind Harmer
0.622
315814AE2-033 C
Solar/Wind Harmer
21.391
3143316POE
Solar/Wind Harmer
-0.087
3147346CASHSCORNER
Solar/Wind Harmer
0.337
3151081ELIZAR1
Adder
17.387
3151091ELIZAR2
Adder
17.085
957871AF2-081 GEN
Solar/Wind Harmer
10.642
3152611GOSPORTB
Adder
2.412
3152621GOSPORTC
Adder
2.047
3152601GOSPORTA
Adder
1.888
319010AE1-072 C
Solar/Wind Harmer
4.298
3146406KITTY HAWK
Solar/Wind Harmer
0.018
316305AF2-043 C
Solar/Wind Harmer
0.639
315835AF2-110_GEN
Solar/Wind Harmer
2.641
313526AB2-022
Solar/Wind Harmer
0.57
315833AF1-017_GEN
Solar/Wind Harmer
4.012
316349AD2-085 GEN
Solar/Wind Harmer
1.879
316311AC2-079 GEN
Solar/Wind Harmer
10.655
3146486SUNBURY
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.021
316321Z2-027
Solar/Wind Harmer
0.568
3146396TANGLEW
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.467
315611Z1-036_GEN2
Solar/Wind Harmer
5.136
971285AH1-108 GEN
Adder
1.388
3130156CHOWAN
Solar/Wind Harmer
-0.021
3130156CHOWAN
Solar/Wind Harmer
-0.021
316087AB2-174 GEN
Solar/Wind Harmer
2.938
971445AH1-216 GEN
Solar/Wind Harmer
12.633
965291AG1-394 GEN
Solar/Wind Harmer
1.811
315816AE2-034 GEN
Solar/Wind Harmer
1.651
3137643SOCKMAN
Solar/Wind Harmer
-0.081
316318V4-068
Solar/Wind Harmer
0.505
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
-0.02
3146043SEABORD
Solar/Wind Harmer
-0.02
315607AA1-063A GEN
Solar/Wind Harmer
2.043
3130546PLYMOUTH
Solar/Wind Harmer
-0.02
315652AC1-086 GEN
Solar/Wind Harmer
22.742
315732AD1-074 GEN1
Solar/Wind Harmer
4.081
315733AD1-074 GEN2
Solar/Wind Harmer
4.081
315735AD1-075 GEN1
Solar/Wind Harmer
2.041
3146206CASHIE
Solar/Wind Harmer
-0.02
970601AG2-382 GEN
Solar/Wind Harmer
8.795
3145513AHOSKIE
Solar/Wind Harmer
0.175
961941AG1-037 GEN
Solar/Wind Harmer
0.151
3145513AHOSKIE
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.04
3145683EARLEYS
Solar/Wind Harmer
-0.02
3145683EARLEYS
Solar/Wind Harmer
-0.02
972265AH1-717 GEN
Adder
13.785
3151201GRAVEL4
Adder
12.922
3151191GRAVEL3
Adder
12.759
3151211GRAVEL5
Adder
12.759
3145796HORNRTN
Solar/Wind Harmer
-0.063
3145796HORNRTN
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
9.966
315657AE1-056 GEN
Solar/Wind Harmer
7.413
946301AF1-294 GEN
Solar/Wind Harmer
5.065
961791AG1-021 GEN
Solar/Wind Harmer
2.471
970683AG2-441 GEN
Solar/Wind Harmer
15.441
970681AG2-440 GEN
Solar/Wind Harmer
12.353
3144303KENBRDG
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.891
316239AB2-077_GEN
Solar/Wind Harmer
0.594
316238AB2-078_GEN
Solar/Wind Harmer
0.594
3146033SCOT NK
Solar/Wind Harmer
-0.078
972205AH1-687 GEN
Adder
6.743
3142433PROV 92
Adder
0.28
3142433PROV 92
Adder
0.28
971133AH1-012 GEN
50/50
7.972
970533AG2-339 GEN
50/50
20.723
970531AG2-338 GEN
50/50
8.289
315242AE2-183_GT2
50/50
3.74
315241AE2-183_GT1
50/50
3.717
972185AH1-677 GEN
50/50
13.482
3151041BRUNSWICKG3
50/50
2.942
972187AH1-678 GEN
50/50
6.752
3151731LOISA B
50/50
14.488
3151721LOISA A
50/50
14.413
971223AH1-071 GEN
Solar/Wind Harmer
3.554
3143526WINTERP
Solar/Wind Harmer
-0.128
970933AG2-581 GEN
Solar/Wind Harmer
23.091
3144356SAPONY
Solar/Wind Harmer
0.804
970099AG2-077 GEN
Solar/Wind Harmer
28.533
316185AD1-033 GEN
Solar/Wind Harmer
2.253
3145506HICKORY
Solar/Wind Harmer
-0.085
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
3142956BIRDNECK
Solar/Wind Harmer
1.144
316316AC1-027 C
Solar/Wind Harmer
0.654
316339AD2-160 GEN
Solar/Wind Harmer
1.436
316036AC1-147 C
Solar/Wind Harmer
0.574
3150991CHESPKB
Adder
1.984
3150991CHESPKB
Adder
1.936
316018AA1-139 ULT2
Solar/Wind Harmer
1.823
316017AA1-139 ULT1
Solar/Wind Harmer
1.722
3137176SLIGO L2192
Solar/Wind Harmer
-0.084
3146456SLIGO L269
Solar/Wind Harmer
2.51
3130086AYDLETT
Solar/Wind Harmer
-0.085
971741AH1-377 GEN
Solar/Wind Harmer
24.619
3146386ELIZ CT
Solar/Wind Harmer
-0.021
970657AG2-426 GEN
Solar/Wind Harmer
6.599
970657AG2-426 GEN
Solar/Wind Harmer
1.38
316431W1029_GEN1
Solar/Wind Harmer
3.804
316433W1029_GEN2
Solar/Wind Harmer
3.804
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
3146626S HERTFORD
Solar/Wind Harmer
-0.021
970301AG2-198 GEN
Solar/Wind Harmer
10.423
315742AE1-103 GEN
Solar/Wind Harmer
2.176
3146376EDENTON
Solar/Wind Harmer
0.613
3146376EDENTON
Solar/Wind Harmer
0.613
316181AB2-040 GEN
Solar/Wind Harmer
2.859
316236AE1-162_GEN
Solar/Wind Harmer
0.617
3145893MURPHYS
Solar/Wind Harmer
0.565
3145893MURPHYS
Solar/Wind Harmer
-0.036
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.012
316065AD1-022 GEN
Solar/Wind Harmer
10.065
3146173TUNIS
Solar/Wind Harmer
-0.02
3146173TUNIS
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
3145593CAROLNA
Solar/Wind Harmer
-0.02
966811AG1-552 GEN
Solar/Wind Harmer
2.263
3145593CAROLNA
Solar/Wind Harmer
0.167
316426AA2-053 GEN
Solar/Wind Harmer
2.029
3145783HORNRTN
Solar/Wind Harmer
2.372
3145783HORNRTN
Solar/Wind Harmer
1.898
3145783HORNRTN
Solar/Wind Harmer
0.593
3145783HORNRTN
Solar/Wind Harmer
0.237
3145796HORNRTN
Solar/Wind Harmer
-0.059
939181AE1-148 GEN
Solar/Wind Harmer
11.135
3147133PAMPLIN
Solar/Wind Harmer
-0.02
3147133PAMPLIN
Solar/Wind Harmer
-0.016
958211AF2-115 GEN
Solar/Wind Harmer
3.088
963191AG1-168 GEN
Solar/Wind Harmer
1.853
3144293JTRSVLE
Adder
0.56
3144293JTRSVLE
Adder
0.472
316034AC1-036 C
Solar/Wind Harmer
0.367
970323AG2-213 GEN
Solar/Wind Harmer
9.881
971775AH1-396 GEN
Solar/Wind Harmer
1.407
313527AB2-043 GEN
Solar/Wind Harmer
3.21
316240AF1-291 C
Solar/Wind Harmer
0.595
966001AG1-469 GEN
Solar/Wind Harmer
0.369
944641AF1-129 GEN
Adder
82.518
3142366NRTHEST
Adder
0.471
3150691DARBY 3
Adder
10.241
3150701DARBY 4
Adder
10.217
3150681DARBY 2
Adder
10.205
3150671DARBY 1
Adder
10.193
3142296MT RD221
Adder
0.388
316447AC1-158 HLD
Solar/Wind Helper
7.213
316033AB2-134 GEN
Solar/Wind Harmer
5.503
NYPJM->LTFIMP_NY
CLTF
2.887
LAGNLTFEXP_LAGN->PJM
CLTF
7.115
LGEELTFEXP_LGEE->PJM
CLTF
1.081
WECLTFEXP_WEC->PJM
CLTF
0.523
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.438
TVALTFEXP_TVA->PJM
CLTF
3.587
CPLELTFEXP_CPLE->PJM
CLTF
10.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.96
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.227
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.109
MECLTFEXP_MEC->PJM
CLTF
3.039
SIGELTFEXP_SIGE->PJM
CLTF
0.091

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.52 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5930.65
MW Contribution:13.73
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
4.782
971285AH1-108 GEN
50/50
2.017
970603AG2-384 GEN
50/50
5.251
972263AH1-716 GEN
50/50
141.451
316233AE1-074 FULL
Solar/Wind Harmer
0.79
971281AH1-106 GEN
Solar/Wind Harmer
4.774
971283AH1-107 GEN
Solar/Wind Harmer
4.774
3143316POE
Solar/Wind Harmer
-0.109
941031AE2-094 GEN
Solar/Wind Harmer
51.844
944011AF1-069 GEN
Solar/Wind Harmer
16.245
3151081ELIZAR1
Adder
22.389
3151091ELIZAR2
Adder
22
316132AB2-190 GEN1
Solar/Wind Harmer
2.776
3152611GOSPORTB
Adder
3.108
3152621GOSPORTC
Adder
2.638
3152601GOSPORTA
Adder
2.434
316369SG1_INVT
Solar/Wind Harmer
4.896
971445AH1-216 GEN
Solar/Wind Harmer
16.942
972265AH1-717 GEN
Adder
18.896
3151201GRAVEL4
Adder
17.714
3151191GRAVEL3
Adder
17.489
3151211GRAVEL5
Adder
17.489
957871AF2-081 GEN
Solar/Wind Harmer
13.602
970673AG2-436 GEN
Solar/Wind Harmer
57.084
970673AG2-436 GEN
Solar/Wind Harmer
28.903
319010AE1-072 C
Solar/Wind Harmer
5.488
3146406KITTY HAWK
Solar/Wind Harmer
0.023
315833AF1-017_GEN
Solar/Wind Harmer
5.15
316349AD2-085 GEN
Solar/Wind Harmer
2.412
316311AC2-079 GEN
Solar/Wind Harmer
13.676
316305AF2-043 C
Solar/Wind Harmer
0.817
316312AB1-027
Solar/Wind Harmer
0.914
315835AF2-110_GEN
Solar/Wind Harmer
3.371
315976AC1-164 GENA
Solar/Wind Harmer
28.429
316169AC1-164_GENC
Solar/Wind Harmer
24.56
315975AC1-164 GENB
Solar/Wind Harmer
0.841
313526AB2-022
Solar/Wind Harmer
0.725
316315AB2-025 C
Solar/Wind Harmer
0.725
971967AH1-528 GEN
Solar/Wind Harmer
50.429
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
315814AE2-033 C
Solar/Wind Harmer
24.939
316321Z2-027
Solar/Wind Harmer
0.722
3146396TANGLEW
Solar/Wind Harmer
0.493
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971167AH1-042 GEN
Solar/Wind Harmer
25.534
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
957831AF2-077 GEN
Solar/Wind Harmer
0.794
3138283WHITEMARSH
Solar/Wind Harmer
0.041
315611Z1-036_GEN2
Solar/Wind Harmer
6.468
3143873LANEXA
Solar/Wind Harmer
-0.015
972189AH1-679 GEN
Adder
3.879
316314AB2-024 C
Solar/Wind Harmer
2.214
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316059AD1-063 C
Solar/Wind Harmer
0.583
315662AE1-191 GEN
Solar/Wind Harmer
3.107
315666AE1-190 GEN
Solar/Wind Harmer
0.777
957601AF2-054 GEN
Solar/Wind Harmer
0.768
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.97
970581AG2-369 GEN
Solar/Wind Harmer
13.734
315816AE2-034 GEN
Solar/Wind Harmer
2.051
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.008
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315732AD1-074 GEN1
Solar/Wind Harmer
5.029
315733AD1-074 GEN2
Solar/Wind Harmer
5.029
315735AD1-075 GEN1
Solar/Wind Harmer
2.515
965291AG1-394 GEN
Solar/Wind Harmer
2.201
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
10.779
316318V4-068
Solar/Wind Harmer
0.613
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
962981AG1-147 GEN
Solar/Wind Harmer
10.738
3145513AHOSKIE
Solar/Wind Harmer
0.211
961941AG1-037 GEN
Solar/Wind Harmer
0.182
3145513AHOSKIE
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.543
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.048
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.433
316087AB2-174 GEN
Solar/Wind Harmer
3.429
315652AC1-086 GEN
Solar/Wind Harmer
26.795
3137643SOCKMAN
Solar/Wind Harmer
-0.094
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
3146033SCOT NK
Solar/Wind Harmer
-0.093
3141813NORNECK
Solar/Wind Harmer
-0.023
3150411LDYSMT5
Adder
26.823
3150381LDYSMT2
Adder
25.67
972213AH1-691 GEN
Adder
4.342
972215AH1-692 GEN
Adder
4.342
972205AH1-687 GEN
Adder
7.266
972193AH1-681 GEN
Adder
3.437
316164AC1-076 GEN
Solar/Wind Helper
2.187
316411AF1-147_GEN1
Solar/Wind Helper
0.802
316415AF1-147_GEN2
Solar/Wind Helper
0.802
3138216PACIFIC
Solar/Wind Helper
0.039
3152251N ANNA1
50/50
20.54
970119AG2-088 GEN
50/50
35.865
3150851SPRUNCC
50/50
1.233
3143096IRON208
50/50
1.093
3152331SURRY 2
50/50
10.164
3150771HOPHCF1
50/50
0.992
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.152
3147666LOUISA
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
26.675
939411AE1-173 GEN
Solar/Wind Harmer
140.912
316192AB2-158 GEN
Solar/Wind Harmer
3.325
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.98
315671AE2-027_GEN
Solar/Wind Harmer
20.692
944591AF1-124 GEN
Solar/Wind Harmer
125.51
970129AG2-093 GEN
Solar/Wind Harmer
6.259
316458AB2-190 GEN2
Solar/Wind Harmer
2.776
316375AC2-012 GEN
Solar/Wind Harmer
9.491
3150981CHESPKA
Adder
3.048
971069AG2-661 GEN
Solar/Wind Harmer
4.338
970659AG2-427 GEN
Solar/Wind Harmer
14.549
3145336SMITFLD
Solar/Wind Harmer
-0.109
971647AH1-324 GEN
Solar/Wind Harmer
13.692
961611AG1-000B GEN
Solar/Wind Harmer
13.505
316381AD1-082 GEN
Solar/Wind Harmer
2.509
944631AF1-128 GEN
Adder
116.045
3151171GRAVELC
Adder
2.589
970661AG2-428 GEN
Solar/Wind Harmer
28.997
316388AE2-253 GEN
Solar/Wind Harmer
1.836
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.549
3138126ROCKLANDING
Solar/Wind Harmer
0.083
316246AF1-032 C
Solar/Wind Harmer
0.548
3142416OLDCHRC
Solar/Wind Harmer
-0.07
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316159AE1-175 C
Solar/Wind Harmer
0.726
316093AE2-104_GEN
Solar/Wind Harmer
7.84
971317AH1-138 GEN
Solar/Wind Harmer
3.367
3146516WINFALL
Solar/Wind Harmer
-0.086
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
315800Z1-036_GEN1
Solar/Wind Harmer
6.468
3130156CHOWAN
Solar/Wind Harmer
-0.026
971777AH1-397 GEN
Solar/Wind Harmer
3.039
3141843SHACKLE
Adder
1.176
3141766HARMONY
Solar/Wind Harmer
-0.005
3143336POWHATN
Solar/Wind Harmer
3.06
970919AG2-571 GEN
Solar/Wind Harmer
8.119
970087AG2-069 GEN
Solar/Wind Harmer
23.954
3145663CRESWEL
Solar/Wind Harmer
-0.071
971163AH1-040 GEN
Solar/Wind Harmer
23.766
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.159
316336AC2-165 C
Solar/Wind Harmer
4.278
3145893MURPHYS
Solar/Wind Harmer
-0.098
3145893MURPHYS
Solar/Wind Harmer
0.73
957481AF2-042 GEN
Solar/Wind Harmer
76.436
3146173TUNIS
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.2
960081AF2-299 GEN
Solar/Wind Harmer
2.727
3145683EARLEYS
Solar/Wind Harmer
-0.024
966881AG1-559 GEN
Solar/Wind Harmer
0.248
3146263WOODLND
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
8.995
315693AD1-088 GEN
Solar/Wind Harmer
11.973
962491AG1-098 GEN
Solar/Wind Harmer
15.963
316011AB1-132 GEN
Solar/Wind Harmer
4.983
962571AG1-106 GEN
Solar/Wind Harmer
3.424
971795AH1-408 GEN
Solar/Wind Harmer
17.814
3145963POPLR C
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.291
3145823KELFORD
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.632
3147043LAWRENC
Adder
1.895
964211AG1-282 GEN
Solar/Wind Harmer
0.706
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.053
316212AC1-099_GEN
Solar/Wind Harmer
1.995
972197AH1-683 GEN
Adder
4.175
972219AH1-694 GEN
Adder
3.006
3144293JTRSVLE
Adder
0.613
972277AH1-723 GEN
Adder
89.642
3151751LOISA D
Adder
8.322
316045AC1-158 PL2
Solar/Wind Helper
16.768
316006AB2-029 C
Solar/Wind Helper
0.152
316254AC1-120 GEN1
Solar/Wind Helper
1.381
3152261N ANNA2
50/50
20.538
3150861SPRUNCD
50/50
1.233
3143096IRON208
50/50
1.093
3143096IRON208
50/50
1.071
3150801HOPHCF4
50/50
1.442
971211AH1-065 GEN
50/50
1.739
3151101ELIZAR3
50/50
24.061
3151161SURRY 1
50/50
9.348
3147666LOUISA
Solar/Wind Harmer
-0.066
315773AC2-141 GEN
Solar/Wind Harmer
11.614
315839AE2-212 C
Solar/Wind Harmer
0.835
965281AG1-393 GEN
Solar/Wind Harmer
3.451
315813AE1-149 C
Solar/Wind Harmer
17.198
944581AF1-123 GEN
Solar/Wind Harmer
125.059
944601AF1-125 GEN
Solar/Wind Harmer
123.108
970133AG2-095 GEN
Solar/Wind Harmer
3.091
970129AG2-093 GEN
Solar/Wind Harmer
15.452
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
315778AD1-151 GEN
Solar/Wind Harmer
23.752
970659AG2-427 GEN
Solar/Wind Harmer
2.578
3145336SMITFLD
Solar/Wind Harmer
-0.011
961611AG1-000B GEN
Solar/Wind Harmer
5.762
316083AB2-161 GEN
Solar/Wind Harmer
4.441
3151221GRAVEL6
Adder
17.693
3151171GRAVELC
Adder
3.404
970661AG2-428 GEN
Solar/Wind Harmer
5.139
3142946ENON
Solar/Wind Harmer
-0.009
970293AG2-193 GEN
Solar/Wind Harmer
3.403
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.31
3144216WINCHST
Adder
0.911
3150921YORKTN3
Adder
6.062
3142416OLDCHRC
Solar/Wind Harmer
2.734
316382AG1-145 C
Solar/Wind Harmer
0.815
316320Y1-086
Solar/Wind Harmer
1.576
316435W1029_GEN3
Solar/Wind Harmer
4.824
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.02
316473AC1-191 GEN
Solar/Wind Harmer
2.815
3146376EDENTON
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.176
316203AE2-005 GEN
Solar/Wind Harmer
10.898
3141766HARMONY
Solar/Wind Harmer
2.298
316313AB2-026
Solar/Wind Harmer
0.695
316258AE1-075 C
Solar/Wind Harmer
0.626
316405AF2-144 C
Solar/Wind Harmer
0.66
3143336POWHATN
Solar/Wind Harmer
2.601
316280AD1-041 GEN
Solar/Wind Harmer
1.942
316156AD2-030 GEN
Solar/Wind Harmer
0.685
3141873WAN 176
Solar/Wind Harmer
3.046
970917AG2-570 GEN
Solar/Wind Harmer
64.143
315614AA2-178 GEN
Solar/Wind Harmer
2.735
971157AH1-035 GEN
Solar/Wind Harmer
3.118
3156081AA2-088 GEN
Solar/Wind Harmer
8.083
315737AD1-076 GEN
Solar/Wind Harmer
4.727
316365GEN2_N
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
3145893MURPHYS
Solar/Wind Harmer
0.172
3145893MURPHYS
Solar/Wind Harmer
-0.025
962971AG1-146 GEN
Solar/Wind Harmer
4.602
957521AF2-046 GEN
Solar/Wind Harmer
19.314
961681AG1-008 GEN
Solar/Wind Harmer
19.314
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.275
316484AD2-074 GEN
Solar/Wind Harmer
6.115
970009AG2-005 GEN
Solar/Wind Harmer
3.036
316463AE2-346 GEN
Solar/Wind Harmer
0.393
316140AB2-099
Solar/Wind Harmer
0.163
962331AG1-082 GEN
Solar/Wind Harmer
3.031
966621AG1-532 GEN
Solar/Wind Harmer
0.492
966881AG1-559 GEN
Solar/Wind Harmer
0.724
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.925
316404AE1-155 C
Solar/Wind Harmer
4.606
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.024
316317KELFORD C
Solar/Wind Harmer
1.117
3145823KELFORD
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
2.037
316486AD2-202 GEN
Solar/Wind Harmer
0.597
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.088
316210AC1-098 GEN
Solar/Wind Harmer
3.591
3150401LDYSMT4
Adder
26.739
3150371LDYSMT1
Adder
25.837
3144293JTRSVLE
Adder
0.613
972255AH1-712 GEN
Adder
76.926
3151761LOISA E
Adder
16.965
972183AH1-676 GEN
Adder
130.241
3141316ARNOLDS
Adder
0.278
316044AC1-158 PL1
Solar/Wind Helper
5.238
316450AC1-158 RIC
Solar/Wind Helper
1.397
316170AC1-121 GEN2
Solar/Wind Helper
0.46
3141196NOKESVL
Solar/Wind Helper
1.151
971133AH1-012 GEN
50/50
5.498
944641AF1-129 GEN
50/50
124.495
970533AG2-339 GEN
50/50
21.875
970531AG2-338 GEN
50/50
8.75
3150781HOPHCF2
50/50
0.992
3150791HOPHCF3
50/50
0.992
3150761HOPPOLC
50/50
0.629
971213AH1-066 GEN
50/50
0.87
3142366NRTHEST
50/50
0.848
971223AH1-071 GEN
Solar/Wind Harmer
3.778
3143526WINTERP
Solar/Wind Harmer
-0.152
316240AF1-291 C
Solar/Wind Harmer
0.834
316036AC1-147 C
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.557
3150991CHESPKB
Adder
2.496
316033AB2-134 GEN
Solar/Wind Harmer
8.837
315697AD1-025 GEN
Solar/Wind Harmer
5.542
316316AC1-027 C
Solar/Wind Harmer
0.841
3142956BIRDNECK
Solar/Wind Harmer
1.47
316236AE1-162_GEN
Solar/Wind Harmer
0.825
3150691DARBY 3
Adder
17.538
3150701DARBY 4
Adder
17.497
3150681DARBY 2
Adder
17.476
3150671DARBY 1
Adder
17.456
316185AD1-033 GEN
Solar/Wind Harmer
2.888
970657AG2-426 GEN
Solar/Wind Harmer
8.542
970657AG2-426 GEN
Solar/Wind Harmer
1.786
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
3142296MT RD221
Adder
0.773
316339AD2-160 GEN
Solar/Wind Harmer
1.836
3142946ENON
Solar/Wind Harmer
-0.003
316018AA1-139 ULT2
Solar/Wind Harmer
2.33
316017AA1-139 ULT1
Solar/Wind Harmer
2.201
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
3.207
3130086AYDLETT
Solar/Wind Harmer
-0.108
316075AC2-137 C
Solar/Wind Harmer
0.73
972185AH1-677 GEN
Adder
13.451
3146386ELIZ CT
Solar/Wind Harmer
-0.027
3144356SAPONY
Solar/Wind Harmer
0.938
316431W1029_GEN1
Solar/Wind Harmer
4.824
316433W1029_GEN2
Solar/Wind Harmer
4.824
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.532
966871AG1-558 GEN
Solar/Wind Harmer
0.787
966871AG1-558 GEN
Solar/Wind Harmer
0.269
315742AE1-103 GEN
Solar/Wind Harmer
2.721
3146376EDENTON
Solar/Wind Harmer
0.768
3146376EDENTON
Solar/Wind Harmer
0.768
316441AF1-014 GEN
Solar/Wind Harmer
1.742
316065AD1-022 GEN
Solar/Wind Harmer
12.361
3145893MURPHYS
Solar/Wind Harmer
0.686
3145893MURPHYS
Solar/Wind Harmer
-0.044
970099AG2-077 GEN
Solar/Wind Harmer
30.574
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316487AF1-042 GEN
Solar/Wind Harmer
3.2
957411AF2-035 GEN
Solar/Wind Harmer
10.838
970317AG2-208 GEN
Solar/Wind Harmer
10.537
316181AB2-040 GEN
Solar/Wind Harmer
3.34
958261AF2-120 GEN
Solar/Wind Harmer
9.253
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.396
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
966811AG1-552 GEN
Solar/Wind Harmer
2.657
3145593CAROLNA
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
2.786
3145783HORNRTN
Solar/Wind Harmer
2.229
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
315673AE1-157 GEN
Solar/Wind Harmer
17.6
3145796HORNRTN
Solar/Wind Harmer
-0.07
316077AC2-138 C
Solar/Wind Harmer
0.488
3150341NORNECKC1
Adder
2.157
3150341NORNECKC1
Adder
2.139
3150391LDYSMT3
Adder
26.689
972195AH1-682 GEN
Adder
3.507
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
3151731LOISA B
Adder
8.322
3151721LOISA A
Adder
8.279
316447AC1-158 HLD
Solar/Wind Helper
11.529
315651AD1-115 GEN
Solar/Wind Helper
1.021
971741AH1-377 GEN
Solar/Wind Harmer
12.626
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.397
LAGNLTFEXP_LAGN->PJM
CLTF
8.538
WECLTFEXP_WEC->PJM
CLTF
0.676
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.91
TVALTFEXP_TVA->PJM
CLTF
4.323
CPLELTFEXP_CPLE->PJM
CLTF
12.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.908
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.684
MECLTFEXP_MEC->PJM
CLTF
3.82
SIGELTFEXP_SIGE->PJM
CLTF
0.116

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.0 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5831.04
MW Contribution:13.54
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151101ELIZAR3
50/50
23.68
3151161SURRY 1
50/50
9.205
3147666LOUISA
Solar/Wind Harmer
-0.066
315839AE2-212 C
Solar/Wind Harmer
0.823
971133AH1-012 GEN
50/50
5.491
944641AF1-129 GEN
50/50
122.767
970533AG2-339 GEN
50/50
21.564
970531AG2-338 GEN
50/50
8.626
3142366NRTHEST
50/50
0.836
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
971223AH1-071 GEN
Solar/Wind Harmer
3.731
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3150681DARBY 2
Adder
17.235
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.728
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
315773AC2-141 GEN
Solar/Wind Harmer
11.425
965281AG1-393 GEN
Solar/Wind Harmer
3.403
315813AE1-149 C
Solar/Wind Harmer
16.949
970133AG2-095 GEN
Solar/Wind Harmer
3.047
944581AF1-123 GEN
Solar/Wind Harmer
123.071
944601AF1-125 GEN
Solar/Wind Harmer
121.15
970129AG2-093 GEN
Solar/Wind Harmer
15.226
315778AD1-151 GEN
Solar/Wind Harmer
23.4
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.54
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.375
961611AG1-000B GEN
Solar/Wind Harmer
5.675
3151221GRAVEL6
Adder
17.422
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
970293AG2-193 GEN
Solar/Wind Harmer
3.354
3142946ENON
Solar/Wind Harmer
-0.009
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.257
3142416OLDCHRC
Solar/Wind Harmer
2.696
3144216WINCHST
Adder
0.896
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.551
316435W1029_GEN3
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316473AC1-191 GEN
Solar/Wind Harmer
2.785
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.757
316303AF2-085
50/50
4.723
971285AH1-108 GEN
50/50
1.99
970603AG2-384 GEN
50/50
5.178
972263AH1-716 GEN
50/50
139.063
316233AE1-074 FULL
Solar/Wind Harmer
0.78
971281AH1-106 GEN
Solar/Wind Harmer
4.714
971283AH1-107 GEN
Solar/Wind Harmer
4.714
3143316POE
Solar/Wind Harmer
-0.108
941031AE2-094 GEN
Solar/Wind Harmer
51.106
944011AF1-069 GEN
Solar/Wind Harmer
16.013
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
316369SG1_INVT
Solar/Wind Harmer
4.823
971445AH1-216 GEN
Solar/Wind Harmer
16.679
972265AH1-717 GEN
Adder
18.606
3151201GRAVEL4
Adder
17.442
3151191GRAVEL3
Adder
17.221
3151211GRAVEL5
Adder
17.221
970673AG2-436 GEN
Solar/Wind Harmer
56.272
970673AG2-436 GEN
Solar/Wind Harmer
28.492
957871AF2-081 GEN
Solar/Wind Harmer
13.387
316312AB1-027
Solar/Wind Harmer
0.901
319010AE1-072 C
Solar/Wind Harmer
5.402
315833AF1-017_GEN
Solar/Wind Harmer
5.072
316349AD2-085 GEN
Solar/Wind Harmer
2.375
316311AC2-079 GEN
Solar/Wind Harmer
13.467
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.804
315835AF2-110_GEN
Solar/Wind Harmer
3.318
316315AB2-025 C
Solar/Wind Harmer
0.715
315976AC1-164 GENA
Solar/Wind Harmer
27.987
316169AC1-164_GENC
Solar/Wind Harmer
24.178
315975AC1-164 GENB
Solar/Wind Harmer
0.828
313526AB2-022
Solar/Wind Harmer
0.714
971967AH1-528 GEN
Solar/Wind Harmer
49.715
315814AE2-033 C
Solar/Wind Harmer
24.583
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.711
3146396TANGLEW
Solar/Wind Harmer
0.485
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
972189AH1-679 GEN
Adder
3.913
971167AH1-042 GEN
Solar/Wind Harmer
25.191
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315611Z1-036_GEN2
Solar/Wind Harmer
6.367
3143873LANEXA
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
2.185
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.742
970581AG2-369 GEN
Solar/Wind Harmer
13.538
3141913WHIT STONE
Solar/Wind Harmer
-0.025
315816AE2-034 GEN
Solar/Wind Harmer
2.02
3138133OCRAN
Solar/Wind Harmer
-0.007
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.99
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
3147666LOUISA
Solar/Wind Harmer
-0.115
316192AB2-158 GEN
Solar/Wind Harmer
3.345
940641AE2-051 GEN
Solar/Wind Harmer
26.285
939411AE1-173 GEN
Solar/Wind Harmer
138.811
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.834
315671AE2-027_GEN
Solar/Wind Harmer
20.403
944591AF1-124 GEN
Solar/Wind Harmer
123.514
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
971069AG2-661 GEN
Solar/Wind Harmer
4.274
316375AC2-012 GEN
Solar/Wind Harmer
9.341
3150981CHESPKA
Adder
3
970659AG2-427 GEN
Solar/Wind Harmer
14.335
971647AH1-324 GEN
Solar/Wind Harmer
13.486
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.472
944631AF1-128 GEN
Adder
114.357
961611AG1-000B GEN
Solar/Wind Harmer
13.3
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
28.566
316388AE2-253 GEN
Solar/Wind Harmer
1.807
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316072AD1-144
Solar/Wind Harmer
0.54
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316246AF1-032 C
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316093AE2-104_GEN
Solar/Wind Harmer
7.718
971317AH1-138 GEN
Solar/Wind Harmer
3.315
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
315800Z1-036_GEN1
Solar/Wind Harmer
6.367
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3143336POWHATN
Solar/Wind Harmer
3.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
-0.005
970919AG2-571 GEN
Solar/Wind Harmer
8.004
966881AG1-559 GEN
Solar/Wind Harmer
0.26
970087AG2-069 GEN
Solar/Wind Harmer
23.613
3145663CRESWEL
Solar/Wind Harmer
-0.07
971163AH1-040 GEN
Solar/Wind Harmer
23.4
3138133OCRAN
Solar/Wind Harmer
-0.015
316023GEN1_S
Solar/Wind Harmer
1.652
972197AH1-683 GEN
Adder
4.553
972219AH1-694 GEN
Adder
3.278
316336AC2-165 C
Solar/Wind Harmer
4.232
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.065
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.719
957481AF2-042 GEN
Solar/Wind Harmer
75.375
961951AG1-038 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.688
962861AG1-135 GEN
Solar/Wind Harmer
8.919
3145683EARLEYS
Solar/Wind Harmer
-0.024
3146263WOODLND
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
962491AG1-098 GEN
Solar/Wind Harmer
15.746
316011AB1-132 GEN
Solar/Wind Harmer
4.91
962571AG1-106 GEN
Solar/Wind Harmer
3.374
971795AH1-408 GEN
Solar/Wind Harmer
17.56
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.287
3145823KELFORD
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316174AB2-169 GEN
Solar/Wind Harmer
3.577
3147043LAWRENC
Adder
1.868
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.965
3144293JTRSVLE
Adder
0.605
972277AH1-723 GEN
Adder
87.353
3151751LOISA D
Adder
8.676
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
316313AB2-026
Solar/Wind Harmer
0.688
316258AE1-075 C
Solar/Wind Harmer
0.619
316405AF2-144 C
Solar/Wind Harmer
0.653
3143336POWHATN
Solar/Wind Harmer
2.572
3146376EDENTON
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
63.229
966881AG1-559 GEN
Solar/Wind Harmer
0.76
315614AA2-178 GEN
Solar/Wind Harmer
2.693
971157AH1-035 GEN
Solar/Wind Harmer
3.07
3156081AA2-088 GEN
Solar/Wind Harmer
7.961
316365GEN2_N
Solar/Wind Harmer
1.652
315737AD1-076 GEN
Solar/Wind Harmer
4.654
3150401LDYSMT4
Adder
29.156
3150371LDYSMT1
Adder
28.172
962971AG1-146 GEN
Solar/Wind Harmer
4.557
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
19.023
961681AG1-008 GEN
Solar/Wind Harmer
19.023
316484AD2-074 GEN
Solar/Wind Harmer
6.058
970009AG2-005 GEN
Solar/Wind Harmer
3.008
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.225
966621AG1-532 GEN
Solar/Wind Harmer
0.485
316463AE2-346 GEN
Solar/Wind Harmer
0.387
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.986
316404AE1-155 C
Solar/Wind Harmer
4.568
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.897
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.1
3145823KELFORD
Solar/Wind Harmer
-0.023
316478AD1-087 GEN
Solar/Wind Harmer
2.009
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
3.537
3144293JTRSVLE
Adder
0.605
972255AH1-712 GEN
Adder
74.962
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3141196NOKESVL
Solar/Wind Helper
1.131
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.952
315733AD1-074 GEN2
Solar/Wind Harmer
4.952
315735AD1-075 GEN1
Solar/Wind Harmer
2.477
965291AG1-394 GEN
Solar/Wind Harmer
2.168
3150411LDYSMT5
Adder
29.247
3150381LDYSMT2
Adder
27.99
972213AH1-691 GEN
Adder
4.735
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
10.632
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.614
316318V4-068
Solar/Wind Harmer
0.603
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.535
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.18
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.397
316087AB2-174 GEN
Solar/Wind Harmer
3.379
315652AC1-086 GEN
Solar/Wind Harmer
26.401
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.204
972193AH1-681 GEN
Adder
3.349
316164AC1-076 GEN
Solar/Wind Helper
1.38
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3138216PACIFIC
Solar/Wind Helper
0.038
316033AB2-134 GEN
Solar/Wind Harmer
8.705
315697AD1-025 GEN
Solar/Wind Harmer
5.46
3142956BIRDNECK
Solar/Wind Harmer
1.447
316316AC1-027 C
Solar/Wind Harmer
0.828
316236AE1-162_GEN
Solar/Wind Harmer
0.812
316185AD1-033 GEN
Solar/Wind Harmer
2.842
970657AG2-426 GEN
Solar/Wind Harmer
8.416
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3142296MT RD221
Adder
0.763
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
3142946ENON
Solar/Wind Harmer
-0.003
316339AD2-160 GEN
Solar/Wind Harmer
1.807
316018AA1-139 ULT2
Solar/Wind Harmer
2.294
316017AA1-139 ULT1
Solar/Wind Harmer
2.166
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.156
3130086AYDLETT
Solar/Wind Harmer
-0.106
316075AC2-137 C
Solar/Wind Harmer
0.719
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
0.924
3146386ELIZ CT
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.65
316431W1029_GEN1
Solar/Wind Harmer
4.748
316433W1029_GEN2
Solar/Wind Harmer
4.748
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.778
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970933AG2-581 GEN
Solar/Wind Harmer
24.187
315742AE1-103 GEN
Solar/Wind Harmer
2.679
316441AF1-014 GEN
Solar/Wind Harmer
1.72
3146376EDENTON
Solar/Wind Harmer
0.756
3146376EDENTON
Solar/Wind Harmer
0.756
957411AF2-035 GEN
Solar/Wind Harmer
11.373
970317AG2-208 GEN
Solar/Wind Harmer
11.057
315673AE1-157 GEN
Solar/Wind Harmer
18.722
3150391LDYSMT3
Adder
29.101
972195AH1-682 GEN
Adder
3.824
316065AD1-022 GEN
Solar/Wind Harmer
12.172
3145893MURPHYS
Solar/Wind Harmer
0.676
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.15
316487AF1-042 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.177
316181AB2-040 GEN
Solar/Wind Harmer
3.292
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.36
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.618
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.745
3145783HORNRTN
Solar/Wind Harmer
2.196
3145783HORNRTN
Solar/Wind Harmer
0.686
3145783HORNRTN
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
3151731LOISA B
Adder
8.676
3151721LOISA A
Adder
8.631
316447AC1-158 HLD
Solar/Wind Helper
11.481
971741AH1-377 GEN
Solar/Wind Harmer
12.466
NYPJM->LTFIMP_NY
CLTF
3.266
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B2_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B2_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.28 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3999.66
MW Contribution:10.41
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
-0.057
315773AC2-141 GEN
Solar/Wind Harmer
8.509
315839AE2-212 C
Solar/Wind Harmer
0.609
944581AF1-123 GEN
Solar/Wind Harmer
91.816
944601AF1-125 GEN
Solar/Wind Harmer
90.383
315813AE1-149 C
Solar/Wind Harmer
12.605
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.513
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
-0.003
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.871
3143526WINTERP
Solar/Wind Harmer
-0.113
316036AC1-147 C
Solar/Wind Harmer
0.543
3142956BIRDNECK
Solar/Wind Harmer
1.078
316316AC1-027 C
Solar/Wind Harmer
0.617
316185AD1-033 GEN
Solar/Wind Harmer
2.119
316240AF1-291 C
Solar/Wind Harmer
0.605
3144356SAPONY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
-0.099
316192AB2-158 GEN
Solar/Wind Harmer
2.866
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.113
940641AE2-051 GEN
Solar/Wind Harmer
20.147
939411AE1-173 GEN
Solar/Wind Harmer
105.7
316294AC1-161 GEN
Solar/Wind Harmer
6.579
944591AF1-124 GEN
Solar/Wind Harmer
92.147
316375AC2-012 GEN
Solar/Wind Harmer
6.96
970659AG2-427 GEN
Solar/Wind Harmer
10.669
316381AD1-082 GEN
Solar/Wind Harmer
1.84
315671AE2-027_GEN
Solar/Wind Harmer
15.038
970661AG2-428 GEN
Solar/Wind Harmer
21.272
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.348
3145336SMITFLD
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.403
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.402
961611AG1-000B GEN
Solar/Wind Harmer
9.803
971647AH1-324 GEN
Solar/Wind Harmer
9.928
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
2.006
970129AG2-093 GEN
Solar/Wind Harmer
4.523
316093AE2-104_GEN
Solar/Wind Harmer
5.759
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
2.321
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
18.16
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.265
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
1.348
316018AA1-139 ULT2
Solar/Wind Harmer
1.711
316017AA1-139 ULT1
Solar/Wind Harmer
1.616
316236AE1-162_GEN
Solar/Wind Harmer
0.602
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.355
3130086AYDLETT
Solar/Wind Harmer
-0.079
970933AG2-581 GEN
Solar/Wind Harmer
18.608
316033AB2-134 GEN
Solar/Wind Harmer
6.401
315697AD1-025 GEN
Solar/Wind Harmer
4.014
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.546
316433W1029_GEN2
Solar/Wind Harmer
3.546
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.388
316083AB2-161 GEN
Solar/Wind Harmer
3.257
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.43
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.183
315778AD1-151 GEN
Solar/Wind Harmer
17.189
970129AG2-093 GEN
Solar/Wind Harmer
11.167
970133AG2-095 GEN
Solar/Wind Harmer
2.23
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
1.158
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
3.546
316313AB2-026
Solar/Wind Harmer
0.527
316258AE1-075 C
Solar/Wind Harmer
0.475
316405AF2-144 C
Solar/Wind Harmer
0.501
3143336POWHATN
Solar/Wind Harmer
1.973
3146516WINFALL
Solar/Wind Harmer
-0.019
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
48.634
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.589
971281AH1-106 GEN
Solar/Wind Harmer
3.557
971283AH1-107 GEN
Solar/Wind Harmer
3.557
941031AE2-094 GEN
Solar/Wind Harmer
39.382
944011AF1-069 GEN
Solar/Wind Harmer
12.34
970673AG2-436 GEN
Solar/Wind Harmer
43.344
970673AG2-436 GEN
Solar/Wind Harmer
21.946
3143316POE
Solar/Wind Harmer
-0.08
971967AH1-528 GEN
Solar/Wind Harmer
38.278
316315AB2-025 C
Solar/Wind Harmer
0.541
315814AE2-033 C
Solar/Wind Harmer
18.612
957871AF2-081 GEN
Solar/Wind Harmer
9.987
971445AH1-216 GEN
Solar/Wind Harmer
12.352
319010AE1-072 C
Solar/Wind Harmer
4.03
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.781
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.04
316305AF2-043 C
Solar/Wind Harmer
0.6
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
3.546
316132AB2-190 GEN1
Solar/Wind Harmer
2.006
315835AF2-110_GEN
Solar/Wind Harmer
2.476
313526AB2-022
Solar/Wind Harmer
0.533
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.531
3146396TANGLEW
Solar/Wind Harmer
0.362
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.107
970581AG2-369 GEN
Solar/Wind Harmer
10.412
315611Z1-036_GEN2
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.998
316169AC1-164_GENC
Solar/Wind Harmer
17.276
315975AC1-164 GENB
Solar/Wind Harmer
0.592
957831AF2-077 GEN
Solar/Wind Harmer
0.569
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
18.178
316312AB1-027
Solar/Wind Harmer
0.636
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
1.513
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.714
315733AD1-074 GEN2
Solar/Wind Harmer
3.714
315735AD1-075 GEN1
Solar/Wind Harmer
1.858
965291AG1-394 GEN
Solar/Wind Harmer
1.63
316314AB2-024 C
Solar/Wind Harmer
1.568
315662AE1-191 GEN
Solar/Wind Harmer
2.207
315666AE1-190 GEN
Solar/Wind Harmer
0.552
316059AD1-063 C
Solar/Wind Harmer
0.414
957601AF2-054 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.968
316318V4-068
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.405
3145513AHOSKIE
Solar/Wind Harmer
0.157
961941AG1-037 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.556
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.808
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.944
3137643SOCKMAN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.617
3146033SCOT NK
Solar/Wind Harmer
-0.069
970831AG2-522 GEN
Solar/Wind Harmer
8.501
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
972205AH1-687 GEN
Adder
5.489
316164AC1-076 GEN
Solar/Wind Helper
1.636
3145273HOLLAND
Solar/Wind Harmer
-0.014
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.582
970293AG2-193 GEN
Solar/Wind Harmer
2.398
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.904
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
2.017
316365GEN2_N
Solar/Wind Harmer
1.25
3156081AA2-088 GEN
Solar/Wind Harmer
5.982
971157AH1-035 GEN
Solar/Wind Harmer
2.302
315737AD1-076 GEN
Solar/Wind Harmer
3.491
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
7.74
316280AD1-041 GEN
Solar/Wind Harmer
1.38
3141766HARMONY
Solar/Wind Harmer
1.629
316156AD2-030 GEN
Solar/Wind Harmer
0.487
3141873WAN 176
Solar/Wind Harmer
2.165
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.127
3145893MURPHYS
Solar/Wind Harmer
-0.018
316473AC1-191 GEN
Solar/Wind Harmer
1.956
957521AF2-046 GEN
Solar/Wind Harmer
14.304
961681AG1-008 GEN
Solar/Wind Harmer
14.304
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.424
316463AE2-346 GEN
Solar/Wind Harmer
0.291
316140AB2-099
Solar/Wind Harmer
0.121
962331AG1-082 GEN
Solar/Wind Harmer
2.246
313506AB2-031 GEN
Solar/Wind Harmer
1.435
3146263WOODLND
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.541
316486AD2-202 GEN
Solar/Wind Harmer
0.451
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145963POPLR C
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.264
316484AD2-074 GEN
Solar/Wind Harmer
4.335
970009AG2-005 GEN
Solar/Wind Harmer
2.153
316210AC1-098 GEN
Solar/Wind Harmer
2.67
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
3.263
3150351NORNECKC2
Adder
1.476
3144293JTRSVLE
Adder
0.462
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
2.005
3146376EDENTON
Solar/Wind Harmer
0.566
3146376EDENTON
Solar/Wind Harmer
0.566
316075AC2-137 C
Solar/Wind Harmer
0.513
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
23.148
316441AF1-014 GEN
Solar/Wind Harmer
1.237
316065AD1-022 GEN
Solar/Wind Harmer
9.134
3145893MURPHYS
Solar/Wind Harmer
0.508
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.547
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.49
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.782
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
1.979
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.075
3145783HORNRTN
Solar/Wind Harmer
1.66
3145783HORNRTN
Solar/Wind Harmer
0.519
3145783HORNRTN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.052
971741AH1-377 GEN
Solar/Wind Harmer
20.037
316487AF1-042 GEN
Solar/Wind Harmer
2.268
970301AG2-198 GEN
Solar/Wind Harmer
8.487
316274AC1-208 GEN
Solar/Wind Harmer
1.826
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
316447AC1-158 HLD
Solar/Wind Helper
11.807
958261AF2-120 GEN
Solar/Wind Harmer
3.594
971317AH1-138 GEN
Solar/Wind Harmer
2.416
316159AE1-175 C
Solar/Wind Harmer
0.519
315800Z1-036_GEN1
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.53
316336AC2-165 C
Solar/Wind Harmer
3.244
316023GEN1_S
Solar/Wind Harmer
1.25
957481AF2-042 GEN
Solar/Wind Harmer
57.87
971777AH1-397 GEN
Solar/Wind Harmer
2.159
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.553
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.54
315693AD1-088 GEN
Solar/Wind Harmer
9.06
960081AF2-299 GEN
Solar/Wind Harmer
2.034
962491AG1-098 GEN
Solar/Wind Harmer
12.078
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.31
316011AB1-132 GEN
Solar/Wind Harmer
3.709
962571AG1-106 GEN
Solar/Wind Harmer
2.548
316190AA2-174 GEN
Solar/Wind Harmer
0.217
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.689
961951AG1-038 GEN
Solar/Wind Harmer
2.268
316212AC1-099_GEN
Solar/Wind Harmer
1.483
962861AG1-135 GEN
Solar/Wind Harmer
6.373
316129AC1-054 GEN
Solar/Wind Harmer
1.485
3150351NORNECKC2
Adder
1.452
3144293JTRSVLE
Adder
0.462
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
WECLTFEXP_WEC->PJM
CLTF
0.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P2-2: NORTH ANNA B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: NORTH ANNA B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.28 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:3999.66
MW Contribution:10.41
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
-0.099
316192AB2-158 GEN
Solar/Wind Harmer
2.866
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.113
940641AE2-051 GEN
Solar/Wind Harmer
20.147
939411AE1-173 GEN
Solar/Wind Harmer
105.7
316294AC1-161 GEN
Solar/Wind Harmer
6.579
944591AF1-124 GEN
Solar/Wind Harmer
92.147
316375AC2-012 GEN
Solar/Wind Harmer
6.96
970659AG2-427 GEN
Solar/Wind Harmer
10.669
316381AD1-082 GEN
Solar/Wind Harmer
1.84
315671AE2-027_GEN
Solar/Wind Harmer
15.038
970661AG2-428 GEN
Solar/Wind Harmer
21.272
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.348
3145336SMITFLD
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.403
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.402
961611AG1-000B GEN
Solar/Wind Harmer
9.803
971647AH1-324 GEN
Solar/Wind Harmer
9.928
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
2.006
970129AG2-093 GEN
Solar/Wind Harmer
4.523
316093AE2-104_GEN
Solar/Wind Harmer
5.759
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
2.321
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.019
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
18.16
971317AH1-138 GEN
Solar/Wind Harmer
2.416
316159AE1-175 C
Solar/Wind Harmer
0.519
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.871
3143526WINTERP
Solar/Wind Harmer
-0.113
316036AC1-147 C
Solar/Wind Harmer
0.543
3142956BIRDNECK
Solar/Wind Harmer
1.078
316316AC1-027 C
Solar/Wind Harmer
0.617
316185AD1-033 GEN
Solar/Wind Harmer
2.119
316240AF1-291 C
Solar/Wind Harmer
0.605
3144356SAPONY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.265
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
1.348
316018AA1-139 ULT2
Solar/Wind Harmer
1.711
316017AA1-139 ULT1
Solar/Wind Harmer
1.616
316236AE1-162_GEN
Solar/Wind Harmer
0.602
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.355
3130086AYDLETT
Solar/Wind Harmer
-0.079
970933AG2-581 GEN
Solar/Wind Harmer
18.608
316033AB2-134 GEN
Solar/Wind Harmer
6.401
315800Z1-036_GEN1
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.53
316336AC2-165 C
Solar/Wind Harmer
3.244
316023GEN1_S
Solar/Wind Harmer
1.25
957481AF2-042 GEN
Solar/Wind Harmer
57.87
971777AH1-397 GEN
Solar/Wind Harmer
2.159
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.553
3145893MURPHYS
Solar/Wind Harmer
-0.072
3145893MURPHYS
Solar/Wind Harmer
0.54
315693AD1-088 GEN
Solar/Wind Harmer
9.06
960081AF2-299 GEN
Solar/Wind Harmer
2.034
962491AG1-098 GEN
Solar/Wind Harmer
12.078
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.31
316011AB1-132 GEN
Solar/Wind Harmer
3.709
962571AG1-106 GEN
Solar/Wind Harmer
2.548
316190AA2-174 GEN
Solar/Wind Harmer
0.217
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
-0.018
3145823KELFORD
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.689
961951AG1-038 GEN
Solar/Wind Harmer
2.268
316212AC1-099_GEN
Solar/Wind Harmer
1.483
962861AG1-135 GEN
Solar/Wind Harmer
6.373
316129AC1-054 GEN
Solar/Wind Harmer
1.485
3150351NORNECKC2
Adder
1.452
3144293JTRSVLE
Adder
0.462
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.589
971281AH1-106 GEN
Solar/Wind Harmer
3.557
971283AH1-107 GEN
Solar/Wind Harmer
3.557
941031AE2-094 GEN
Solar/Wind Harmer
39.382
944011AF1-069 GEN
Solar/Wind Harmer
12.34
970673AG2-436 GEN
Solar/Wind Harmer
43.344
970673AG2-436 GEN
Solar/Wind Harmer
21.946
3143316POE
Solar/Wind Harmer
-0.08
971967AH1-528 GEN
Solar/Wind Harmer
38.278
316315AB2-025 C
Solar/Wind Harmer
0.541
315814AE2-033 C
Solar/Wind Harmer
18.612
957871AF2-081 GEN
Solar/Wind Harmer
9.987
971445AH1-216 GEN
Solar/Wind Harmer
12.352
319010AE1-072 C
Solar/Wind Harmer
4.03
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.781
316349AD2-085 GEN
Solar/Wind Harmer
1.77
316311AC2-079 GEN
Solar/Wind Harmer
10.04
316305AF2-043 C
Solar/Wind Harmer
0.6
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
3.546
316132AB2-190 GEN1
Solar/Wind Harmer
2.006
315835AF2-110_GEN
Solar/Wind Harmer
2.476
313526AB2-022
Solar/Wind Harmer
0.533
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.531
3146396TANGLEW
Solar/Wind Harmer
0.362
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.107
970581AG2-369 GEN
Solar/Wind Harmer
10.412
315611Z1-036_GEN2
Solar/Wind Harmer
4.76
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.998
316169AC1-164_GENC
Solar/Wind Harmer
17.276
315975AC1-164 GENB
Solar/Wind Harmer
0.592
957831AF2-077 GEN
Solar/Wind Harmer
0.569
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
18.178
316312AB1-027
Solar/Wind Harmer
0.636
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
1.513
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
315732AD1-074 GEN1
Solar/Wind Harmer
3.714
315733AD1-074 GEN2
Solar/Wind Harmer
3.714
315735AD1-075 GEN1
Solar/Wind Harmer
1.858
965291AG1-394 GEN
Solar/Wind Harmer
1.63
316314AB2-024 C
Solar/Wind Harmer
1.568
315662AE1-191 GEN
Solar/Wind Harmer
2.207
315666AE1-190 GEN
Solar/Wind Harmer
0.552
316059AD1-063 C
Solar/Wind Harmer
0.414
957601AF2-054 GEN
Solar/Wind Harmer
0.546
3141873WAN 176
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.968
316318V4-068
Solar/Wind Harmer
0.454
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
946281AF1-292 GEN
Solar/Wind Harmer
0.405
3145513AHOSKIE
Solar/Wind Harmer
0.157
961941AG1-037 GEN
Solar/Wind Harmer
0.135
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.556
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.808
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.944
3137643SOCKMAN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.617
3146033SCOT NK
Solar/Wind Harmer
-0.069
970831AG2-522 GEN
Solar/Wind Harmer
8.501
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
972205AH1-687 GEN
Adder
5.489
316164AC1-076 GEN
Solar/Wind Helper
1.636
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
-0.057
315773AC2-141 GEN
Solar/Wind Harmer
8.509
315839AE2-212 C
Solar/Wind Harmer
0.609
944581AF1-123 GEN
Solar/Wind Harmer
91.816
944601AF1-125 GEN
Solar/Wind Harmer
90.383
315813AE1-149 C
Solar/Wind Harmer
12.605
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.513
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.257
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.43
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.183
315778AD1-151 GEN
Solar/Wind Harmer
17.189
970129AG2-093 GEN
Solar/Wind Harmer
11.167
970133AG2-095 GEN
Solar/Wind Harmer
2.23
3143096IRON208
Adder
0.737
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
1.158
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
3.546
316313AB2-026
Solar/Wind Harmer
0.527
316258AE1-075 C
Solar/Wind Harmer
0.475
316405AF2-144 C
Solar/Wind Harmer
0.501
3143336POWHATN
Solar/Wind Harmer
1.973
3146516WINFALL
Solar/Wind Harmer
-0.019
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
48.634
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.014
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.582
970293AG2-193 GEN
Solar/Wind Harmer
2.398
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.904
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
2.017
316365GEN2_N
Solar/Wind Harmer
1.25
3156081AA2-088 GEN
Solar/Wind Harmer
5.982
971157AH1-035 GEN
Solar/Wind Harmer
2.302
315737AD1-076 GEN
Solar/Wind Harmer
3.491
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
7.74
316280AD1-041 GEN
Solar/Wind Harmer
1.38
3141766HARMONY
Solar/Wind Harmer
1.629
316156AD2-030 GEN
Solar/Wind Harmer
0.487
3141873WAN 176
Solar/Wind Harmer
2.165
3146206CASHIE
Solar/Wind Harmer
-0.018
3145893MURPHYS
Solar/Wind Harmer
0.127
3145893MURPHYS
Solar/Wind Harmer
-0.018
316473AC1-191 GEN
Solar/Wind Harmer
1.956
957521AF2-046 GEN
Solar/Wind Harmer
14.304
961681AG1-008 GEN
Solar/Wind Harmer
14.304
966621AG1-532 GEN
Solar/Wind Harmer
0.367
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.424
316463AE2-346 GEN
Solar/Wind Harmer
0.291
316140AB2-099
Solar/Wind Harmer
0.121
962331AG1-082 GEN
Solar/Wind Harmer
2.246
313506AB2-031 GEN
Solar/Wind Harmer
1.435
3146263WOODLND
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.541
316486AD2-202 GEN
Solar/Wind Harmer
0.451
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.01
3145963POPLR C
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.829
3145823KELFORD
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.264
316484AD2-074 GEN
Solar/Wind Harmer
4.335
970009AG2-005 GEN
Solar/Wind Harmer
2.153
316210AC1-098 GEN
Solar/Wind Harmer
2.67
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
3.263
3150351NORNECKC2
Adder
1.476
3144293JTRSVLE
Adder
0.462
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
315697AD1-025 GEN
Solar/Wind Harmer
4.014
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.546
316433W1029_GEN2
Solar/Wind Harmer
3.546
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
2.005
3146376EDENTON
Solar/Wind Harmer
0.566
3146376EDENTON
Solar/Wind Harmer
0.566
316075AC2-137 C
Solar/Wind Harmer
0.513
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
23.148
316441AF1-014 GEN
Solar/Wind Harmer
1.237
316065AD1-022 GEN
Solar/Wind Harmer
9.134
3145893MURPHYS
Solar/Wind Harmer
0.508
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.547
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.49
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.782
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
1.979
3145593CAROLNA
Solar/Wind Harmer
0.146
3145783HORNRTN
Solar/Wind Harmer
2.075
3145783HORNRTN
Solar/Wind Harmer
1.66
3145783HORNRTN
Solar/Wind Harmer
0.519
3145783HORNRTN
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
-0.052
971741AH1-377 GEN
Solar/Wind Harmer
20.037
316487AF1-042 GEN
Solar/Wind Harmer
2.268
970301AG2-198 GEN
Solar/Wind Harmer
8.487
316274AC1-208 GEN
Solar/Wind Harmer
1.826
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
316447AC1-158 HLD
Solar/Wind Helper
11.807
958261AF2-120 GEN
Solar/Wind Harmer
3.594
NYPJM->LTFIMP_NY
CLTF
2.427
LGEELTFEXP_LGEE->PJM
CLTF
1
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
WECLTFEXP_WEC->PJM
CLTF
0.483
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.49 %
Rating:3193.18 MVA
Rating Type:A
MVA to Mitigate:3783.56
MW Contribution:7.91
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
17.597
3150861SPRUNCD
50/50
0.898
3151031BRUNSWICKG2
50/50
2.367
3151101ELIZAR3
50/50
17.646
3147666LOUISA
Solar/Wind Harmer
0.507
315773AC2-141 GEN
Solar/Wind Harmer
6.611
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.447
944601AF1-125 GEN
Solar/Wind Harmer
39.824
315813AE1-149 C
Solar/Wind Harmer
9.573
3144873MCLAUGH
Solar/Wind Harmer
0.004
965281AG1-393 GEN
Solar/Wind Harmer
1.908
970659AG2-427 GEN
Solar/Wind Harmer
1.891
3144536CHRHLND
Solar/Wind Harmer
0.027
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.77
3145336SMITFLD
Solar/Wind Harmer
0.071
3146456SLIGO L269
Solar/Wind Harmer
0.177
971153AH1-033 GEN
Solar/Wind Harmer
2.051
3151221GRAVEL6
Adder
12.86
3151171GRAVELC
Adder
2.474
961611AG1-000B GEN
Solar/Wind Harmer
4.714
315778AD1-151 GEN
Solar/Wind Harmer
14.128
970129AG2-093 GEN
Solar/Wind Harmer
10.67
970133AG2-095 GEN
Solar/Wind Harmer
1.693
3143096IRON208
Adder
0.737
971133AH1-012 GEN
50/50
4.727
970533AG2-339 GEN
50/50
16.617
970531AG2-338 GEN
50/50
6.647
315242AE2-183_GT2
50/50
3.006
315241AE2-183_GT1
50/50
2.987
972185AH1-677 GEN
50/50
10.835
3151041BRUNSWICKG3
50/50
2.367
972187AH1-678 GEN
50/50
5.432
3150991CHESPKB
50/50
1.99
3150991CHESPKB
50/50
1.942
971223AH1-071 GEN
Solar/Wind Harmer
2.18
3143526WINTERP
Solar/Wind Harmer
1.012
316036AC1-147 C
Solar/Wind Harmer
0.033
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.172
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3144356SAPONY
Solar/Wind Harmer
1.494
3145506HICKORY
Solar/Wind Harmer
0.714
3145506HICKORY
Solar/Wind Harmer
0.428
3145506HICKORY
Solar/Wind Harmer
0.107
970657AG2-426 GEN
Solar/Wind Harmer
6.25
970657AG2-426 GEN
Solar/Wind Harmer
1.31
944641AF1-129 GEN
Adder
84.93
316339AD2-160 GEN
Solar/Wind Harmer
0.288
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.099
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3137176SLIGO L2192
Solar/Wind Harmer
0.706
3146456SLIGO L269
Solar/Wind Harmer
3.14
3130086AYDLETT
Solar/Wind Harmer
0.709
970933AG2-581 GEN
Solar/Wind Harmer
14.133
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.199
3146386ELIZ CT
Solar/Wind Harmer
0.176
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3146516WINFALL
Solar/Wind Harmer
0.174
3142366NRTHEST
Adder
0.565
3146626S HERTFORD
Solar/Wind Harmer
0.173
3146626S HERTFORD
Solar/Wind Harmer
0.173
3142946ENON
Solar/Wind Harmer
0.017
3150691DARBY 3
Adder
12.388
3150701DARBY 4
Adder
12.359
3150681DARBY 2
Adder
12.344
3150671DARBY 1
Adder
12.33
315742AE1-103 GEN
Solar/Wind Harmer
0.002
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
316075AC2-137 C
Solar/Wind Harmer
0.046
3142296MT RD221
Adder
0.537
970099AG2-077 GEN
Solar/Wind Harmer
17.581
316065AD1-022 GEN
Solar/Wind Harmer
7.487
3145893MURPHYS
Solar/Wind Harmer
1.084
3145893MURPHYS
Solar/Wind Harmer
0.291
966871AG1-558 GEN
Solar/Wind Harmer
0.187
3146173TUNIS
Solar/Wind Harmer
0.161
3146173TUNIS
Solar/Wind Harmer
0.161
316181AB2-040 GEN
Solar/Wind Harmer
0.23
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3142666NORTHAMPTON
Solar/Wind Harmer
0.095
316426AA2-053 GEN
Solar/Wind Harmer
0.53
3145593CAROLNA
Solar/Wind Harmer
0.156
3145593CAROLNA
Solar/Wind Harmer
0.156
966811AG1-552 GEN
Solar/Wind Harmer
1.698
3145593CAROLNA
Solar/Wind Harmer
0.195
3145783HORNRTN
Solar/Wind Harmer
2.766
3145783HORNRTN
Solar/Wind Harmer
2.213
3145783HORNRTN
Solar/Wind Harmer
0.692
3145783HORNRTN
Solar/Wind Harmer
0.277
3145796HORNRTN
Solar/Wind Harmer
0.466
971741AH1-377 GEN
Solar/Wind Harmer
15.218
970301AG2-198 GEN
Solar/Wind Harmer
6.446
316274AC1-208 GEN
Solar/Wind Harmer
0.781
958261AF2-120 GEN
Solar/Wind Harmer
4.978
3145933PARMELE
Solar/Wind Harmer
0.301
3145933PARMELE
Solar/Wind Harmer
0.15
939181AE1-148 GEN
Solar/Wind Harmer
7.079
957411AF2-035 GEN
Solar/Wind Harmer
6.288
970317AG2-208 GEN
Solar/Wind Harmer
5.826
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.221
971775AH1-396 GEN
Solar/Wind Harmer
0.233
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.525
3150341NORNECKC1
Adder
1.513
958211AF2-115 GEN
Solar/Wind Harmer
1.742
963191AG1-168 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3144293JTRSVLE
Adder
0.389
3147133PAMPLIN
Solar/Wind Harmer
0.145
3147133PAMPLIN
Solar/Wind Harmer
0.116
3145493TOT1
Solar/Wind Harmer
0.333
3145453TOT5
Solar/Wind Harmer
0.2
3145603CNETO
Solar/Wind Harmer
0.133
315673AE1-157 GEN
Solar/Wind Harmer
9.924
961601AG1-000A GEN
Solar/Wind Harmer
2.515
316263AC1-034 GEN
Solar/Wind Harmer
5.374
962561AG1-105 GEN
Solar/Wind Harmer
6.736
964791AG1-342 GEN
Solar/Wind Harmer
2.673
3146843MT LREL
Solar/Wind Harmer
0.139
3146843MT LREL
Solar/Wind Harmer
0.139
316468AD1-105 GEN
Solar/Wind Harmer
-0.045
3150391LDYSMT3
Adder
18.314
972195AH1-682 GEN
Adder
2.407
3146776BUCKING
Solar/Wind Harmer
0.547
3146776BUCKING
Solar/Wind Harmer
0.044
316222AC1-221 GEN
Solar/Wind Harmer
0.503
971489AH1-241 GEN
Solar/Wind Harmer
6.389
316447AC1-158 HLD
Solar/Wind Helper
11.807
3143096IRON208
Adder
0.722
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.657
316435W1029_GEN3
Solar/Wind Harmer
0.001
316313AB2-026
Solar/Wind Harmer
0.11
316258AE1-075 C
Solar/Wind Harmer
0.131
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.631
3146516WINFALL
Solar/Wind Harmer
0.174
3150921YORKTN3
Adder
4.366
970917AG2-570 GEN
Solar/Wind Harmer
15.39
3146626S HERTFORD
Solar/Wind Harmer
0.173
3145273HOLLAND
Solar/Wind Harmer
0.129
3142946ENON
Solar/Wind Harmer
0.058
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.821
3146376EDENTON
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
1.628
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315614AA2-178 GEN
Solar/Wind Harmer
0.952
316365GEN2_N
Solar/Wind Harmer
0.37
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.967
315737AD1-076 GEN
Solar/Wind Harmer
2.103
3141843SHACKLE
Adder
0.835
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.172
316156AD2-030 GEN
Solar/Wind Harmer
0.12
3141873WAN 176
Solar/Wind Harmer
2.887
3146206CASHIE
Solar/Wind Harmer
0.162
3145893MURPHYS
Solar/Wind Harmer
0.271
3145893MURPHYS
Solar/Wind Harmer
0.162
316473AC1-191 GEN
Solar/Wind Harmer
0.547
957521AF2-046 GEN
Solar/Wind Harmer
12.028
961681AG1-008 GEN
Solar/Wind Harmer
12.028
3146173TUNIS
Solar/Wind Harmer
0.161
3156021HOLLOMANSOL
Solar/Wind Harmer
0.727
316463AE2-346 GEN
Solar/Wind Harmer
0.137
316140AB2-099
Solar/Wind Harmer
0.057
962331AG1-082 GEN
Solar/Wind Harmer
1.706
313506AB2-031 GEN
Solar/Wind Harmer
0.491
3146263WOODLND
Solar/Wind Harmer
0.158
316478AD1-087 GEN
Solar/Wind Harmer
0.553
316486AD2-202 GEN
Solar/Wind Harmer
0.162
3142666NORTHAMPTON
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
0.156
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.156
3145796HORNRTN
Solar/Wind Harmer
0.621
3145796HORNRTN
Solar/Wind Harmer
0.155
962971AG1-146 GEN
Solar/Wind Harmer
2.479
970009AG2-005 GEN
Solar/Wind Harmer
1.144
316210AC1-098 GEN
Solar/Wind Harmer
1.405
970909AG2-566 GEN
Solar/Wind Harmer
1.611
316404AE1-155 C
Solar/Wind Harmer
0.034
3145933PARMELE
Solar/Wind Harmer
0.15
966801AG1-551 GEN
Solar/Wind Harmer
1.752
315724AD1-057 GEN
Solar/Wind Harmer
0.554
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
316131AB2-060 GEN
Solar/Wind Harmer
0.461
316327AA2-057 GEN
Solar/Wind Harmer
0.221
964241AG1-285 GEN
Solar/Wind Harmer
9.755
315785AD2-033 C
Solar/Wind Harmer
1.187
970257AG2-171 GEN
Solar/Wind Harmer
4.666
959311AF2-222 GEN
Solar/Wind Harmer
12.953
3150351NORNECKC2
Adder
1.476
963181AG1-167 GEN
Solar/Wind Harmer
0.581
3144293JTRSVLE
Adder
0.462
3147133PAMPLIN
Solar/Wind Harmer
0.455
971193AH1-056 GEN
Solar/Wind Harmer
8.824
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146233WITAKRS
Solar/Wind Harmer
0.722
3146233WITAKRS
Solar/Wind Harmer
0.098
3146073TAR RVR
Solar/Wind Harmer
0.144
3146083TARBORO
Solar/Wind Harmer
0.144
3138543CONSLDL
Solar/Wind Harmer
0.095
3146926FARMVIL
Solar/Wind Harmer
0.086
961601AG1-000A GEN
Solar/Wind Harmer
10.061
3152251N ANNA1
50/50
17.599
970119AG2-088 GEN
50/50
27.254
3150851SPRUNCC
50/50
0.898
315243AE2-183_GT3
50/50
3.006
3151051BRUNSWICKS1
50/50
4.913
3151021BRUNSWICKG1
50/50
2.367
971451AH1-221 GEN
50/50
7.19
3150981CHESPKA
50/50
2.372
3147666LOUISA
Solar/Wind Harmer
0.882
316192AB2-158 GEN
Solar/Wind Harmer
1.212
3143226MDLTHAN
Solar/Wind Harmer
0.204
3143526WINTERP
Solar/Wind Harmer
1.012
940641AE2-051 GEN
Solar/Wind Harmer
15.302
939411AE1-173 GEN
Solar/Wind Harmer
80.278
316294AC1-161 GEN
Solar/Wind Harmer
3.136
944591AF1-124 GEN
Solar/Wind Harmer
40.591
316375AC2-012 GEN
Solar/Wind Harmer
0.005
970659AG2-427 GEN
Solar/Wind Harmer
8.643
316381AD1-082 GEN
Solar/Wind Harmer
0.186
315671AE2-027_GEN
Solar/Wind Harmer
11.421
970661AG2-428 GEN
Solar/Wind Harmer
17.724
3142543TWELFTH
Solar/Wind Harmer
0.017
316388AE2-253 GEN
Solar/Wind Harmer
0.557
3145336SMITFLD
Solar/Wind Harmer
0.711
3146456SLIGO L269
Solar/Wind Harmer
0.177
316246AF1-032 C
Solar/Wind Harmer
0.08
3151171GRAVELC
Adder
1.882
316072AD1-144
Solar/Wind Harmer
0.064
961611AG1-000B GEN
Solar/Wind Harmer
9.271
971647AH1-324 GEN
Solar/Wind Harmer
7.54
971069AG2-661 GEN
Solar/Wind Harmer
3.14
316458AB2-190 GEN2
Solar/Wind Harmer
0.947
970129AG2-093 GEN
Solar/Wind Harmer
5.021
316093AE2-104_GEN
Solar/Wind Harmer
2.965
3143096IRON208
Adder
0.737
3143336POWHATN
Solar/Wind Harmer
3.095
3138126ROCKLANDING
Solar/Wind Harmer
0.08
3146516WINFALL
Solar/Wind Harmer
0.563
3146516WINFALL
Solar/Wind Harmer
0.174
944631AF1-128 GEN
Adder
82.804
970919AG2-571 GEN
Solar/Wind Harmer
6.156
970087AG2-069 GEN
Solar/Wind Harmer
13.793
971317AH1-138 GEN
Solar/Wind Harmer
1.284
316159AE1-175 C
Solar/Wind Harmer
0.148
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3142416OLDCHRC
Solar/Wind Harmer
0.437
3142416OLDCHRC
Solar/Wind Harmer
0.167
3142433PROV 92
Solar/Wind Harmer
0.669
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
3145663CRESWEL
Solar/Wind Harmer
0.466
971163AH1-040 GEN
Solar/Wind Harmer
13.314
316336AC2-165 C
Solar/Wind Harmer
0.006
316023GEN1_S
Solar/Wind Harmer
0.37
957481AF2-042 GEN
Solar/Wind Harmer
43.952
971777AH1-397 GEN
Solar/Wind Harmer
0.431
3141843SHACKLE
Adder
0.835
3141766HARMONY
Solar/Wind Harmer
0.033
3146206CASHIE
Solar/Wind Harmer
0.162
971547AH1-271 GEN
Solar/Wind Harmer
3.458
3145893MURPHYS
Solar/Wind Harmer
0.648
3145893MURPHYS
Solar/Wind Harmer
0.72
315693AD1-088 GEN
Solar/Wind Harmer
7.741
960081AF2-299 GEN
Solar/Wind Harmer
1.545
962491AG1-098 GEN
Solar/Wind Harmer
9.173
3146173TUNIS
Solar/Wind Harmer
0.161
3138133OCRAN
Solar/Wind Harmer
0.096
3145683EARLEYS
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.158
971795AH1-408 GEN
Solar/Wind Harmer
10.53
316011AB1-132 GEN
Solar/Wind Harmer
2.868
962571AG1-106 GEN
Solar/Wind Harmer
2.244
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.417
3145963POPLR C
Solar/Wind Harmer
0.156
3145823KELFORD
Solar/Wind Harmer
0.156
3145783HORNRTN
Solar/Wind Harmer
0.155
3145796HORNRTN
Solar/Wind Harmer
0.512
3145796HORNRTN
Solar/Wind Harmer
0.155
316174AB2-169 GEN
Solar/Wind Harmer
0.004
316212AC1-099_GEN
Solar/Wind Harmer
0.783
962861AG1-135 GEN
Solar/Wind Harmer
4.841
316129AC1-054 GEN
Solar/Wind Harmer
0.567
3146293MARTNCO
Solar/Wind Harmer
0.139
971065AG2-659 GEN
Solar/Wind Harmer
6.41
315687AD1-152 GEN
Solar/Wind Harmer
0.005
3141726DUNNSVL
Solar/Wind Harmer
0.591
315722AD1-056 GEN
Solar/Wind Harmer
0.935
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
966881AG1-559 GEN
Solar/Wind Harmer
0.17
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970937AG2-583 GEN
Solar/Wind Harmer
8.939
3150351NORNECKC2
Adder
1.452
316494AC1-189 GEN
Solar/Wind Harmer
0.491
970685AG2-442 GEN
Solar/Wind Harmer
10.862
963171AG1-166 GEN
Solar/Wind Harmer
0.774
971563AH1-280 GEN
Solar/Wind Harmer
1.548
3144293JTRSVLE
Adder
0.462
3146233WITAKRS
Solar/Wind Harmer
0.573
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.144
3145493TOT1
Solar/Wind Harmer
0.639
3146926FARMVIL
Solar/Wind Harmer
0.086
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.113
316359AB2-059 GEN
Solar/Wind Harmer
0.508
316049AB1-081 GEN
Solar/Wind Harmer
0.809
3142053HEARTS
Solar/Wind Harmer
0.249
970401AG2-262 GEN
Solar/Wind Harmer
0.817
316337AD2-073 GEN
Solar/Wind Harmer
0.12
972197AH1-683 GEN
Adder
2.865
972219AH1-694 GEN
Adder
2.063
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
972003AH1-546 GEN
Solar/Wind Harmer
5.523
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.278
3147623JAMES R
Solar/Wind Harmer
0.278
972135AH1-637 GEN
Solar/Wind Harmer
0.998
316045AC1-158 PL2
Solar/Wind Helper
17.173
316006AB2-029 C
Solar/Wind Helper
0.112
3145543BTLEBRO
Solar/Wind Harmer
0.141
3145543BTLEBRO
Solar/Wind Harmer
0.141
971623AH1-311 GEN
Solar/Wind Harmer
0.283
971781AH1-399 GEN
Solar/Wind Harmer
0.181
3150401LDYSMT4
Adder
18.348
3150371LDYSMT1
Adder
17.729
3146776BUCKING
Solar/Wind Harmer
0.049
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.713
3141906WESTMOR
Solar/Wind Harmer
0.052
971683AH1-343 GEN
Solar/Wind Harmer
4.538
970737AG2-469 GEN
Solar/Wind Harmer
5.206
316283AC2-100 C
Solar/Wind Harmer
0.236
970221AG2-151 GEN
Solar/Wind Harmer
6.389
316044AC1-158 PL1
Solar/Wind Helper
5.365
316450AC1-158 RIC
Solar/Wind Helper
1.431
316303AF2-085
50/50
3.634
971285AH1-108 GEN
50/50
1.469
315244AE2-183_ST
50/50
5.196
963041AG1-153 GEN
50/50
4.793
3151081ELIZAR1
50/50
17.423
3151091ELIZAR2
50/50
17.121
941591AE2-156 GEN
50/50
15.921
3152611GOSPORTB
50/50
2.419
3152621GOSPORTC
50/50
2.053
3152601GOSPORTA
50/50
1.894
315779AE2-040
50/50
2.493
316233AE1-074 FULL
Solar/Wind Harmer
0.156
971281AH1-106 GEN
Solar/Wind Harmer
2.702
971283AH1-107 GEN
Solar/Wind Harmer
2.702
941031AE2-094 GEN
Solar/Wind Harmer
34.43
944011AF1-069 GEN
Solar/Wind Harmer
11.25
970673AG2-436 GEN
Solar/Wind Harmer
39.174
970673AG2-436 GEN
Solar/Wind Harmer
26.116
3143316POE
Solar/Wind Harmer
0.721
971967AH1-528 GEN
Solar/Wind Harmer
28.994
316315AB2-025 C
Solar/Wind Harmer
0.144
315814AE2-033 C
Solar/Wind Harmer
14.072
957871AF2-081 GEN
Solar/Wind Harmer
8.849
971445AH1-216 GEN
Solar/Wind Harmer
12.508
319010AE1-072 C
Solar/Wind Harmer
0.893
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.121
316311AC2-079 GEN
Solar/Wind Harmer
5.087
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.734
3151201GRAVEL4
Adder
12.875
3151191GRAVEL3
Adder
12.712
3151211GRAVEL5
Adder
12.712
316369SG1_INVT
Solar/Wind Harmer
0.007
316132AB2-190 GEN1
Solar/Wind Harmer
0.947
315835AF2-110_GEN
Solar/Wind Harmer
1.21
313526AB2-022
Solar/Wind Harmer
0.095
3146486SUNBURY
Solar/Wind Harmer
0.175
3146486SUNBURY
Solar/Wind Harmer
0.175
316321Z2-027
Solar/Wind Harmer
0.033
3146396TANGLEW
Solar/Wind Harmer
0.483
3145176PASQUOTANK
Solar/Wind Harmer
0.109
970085AG2-068 GEN
Solar/Wind Harmer
9.195
970581AG2-369 GEN
Solar/Wind Harmer
7.908
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.17
3130156CHOWAN
Solar/Wind Harmer
0.17
315976AC1-164 GENA
Solar/Wind Harmer
17.467
316169AC1-164_GENC
Solar/Wind Harmer
15.09
315975AC1-164 GENB
Solar/Wind Harmer
0.517
3138283WHITEMARSH
Solar/Wind Harmer
0.039
971167AH1-042 GEN
Solar/Wind Harmer
14.927
316312AB1-027
Solar/Wind Harmer
0.3
3142433PROV 92
Adder
0.325
3142433PROV 92
Adder
0.325
315816AE2-034 GEN
Solar/Wind Harmer
0.714
3143873LANEXA
Solar/Wind Harmer
0.099
3130546PLYMOUTH
Solar/Wind Harmer
0.164
315732AD1-074 GEN1
Solar/Wind Harmer
0.939
315733AD1-074 GEN2
Solar/Wind Harmer
0.939
315735AD1-075 GEN1
Solar/Wind Harmer
0.47
965291AG1-394 GEN
Solar/Wind Harmer
0.726
970189AG2-124 GEN
Solar/Wind Harmer
4.842
316314AB2-024 C
Solar/Wind Harmer
0.001
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3146206CASHIE
Solar/Wind Harmer
0.162
970601AG2-382 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
0.437
3145893MURPHYS
Solar/Wind Harmer
0.162
3145513AHOSKIE
Solar/Wind Harmer
0.334
3145513AHOSKIE
Solar/Wind Harmer
0.16
3141913WHIT STONE
Solar/Wind Harmer
0.16
3146043SEABORD
Solar/Wind Harmer
0.16
316087AB2-174 GEN
Solar/Wind Harmer
0.005
972189AH1-679 GEN
Adder
2.672
3138133OCRAN
Solar/Wind Harmer
0.048
315607AA1-063A GEN
Solar/Wind Harmer
0.325
3145683EARLEYS
Solar/Wind Harmer
0.318
3145683EARLEYS
Solar/Wind Harmer
0.159
3145683EARLEYS
Solar/Wind Harmer
0.159
3141783LANCAST
Solar/Wind Harmer
0.095
3141783LANCAST
Solar/Wind Harmer
0.063
315652AC1-086 GEN
Solar/Wind Harmer
17.349
3137643SOCKMAN
Solar/Wind Harmer
0.629
3145796HORNRTN
Solar/Wind Harmer
0.497
3145796HORNRTN
Solar/Wind Harmer
0.062
962981AG1-147 GEN
Solar/Wind Harmer
5.785
3146033SCOT NK
Solar/Wind Harmer
0.614
970327AG2-215 GEN
Solar/Wind Harmer
5.03
970831AG2-522 GEN
Solar/Wind Harmer
6.456
316005AA1-067
Solar/Wind Harmer
0.158
3145746EVERETS
Solar/Wind Harmer
0.587
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
3145746EVERETS
Solar/Wind Harmer
0.147
970181AG2-120 GEN
Solar/Wind Harmer
1.837
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
971443AH1-215 GEN
Solar/Wind Harmer
2.45
3144303KENBRDG
Solar/Wind Harmer
0.117
3141813NORNECK
Solar/Wind Harmer
0.146
957861AF2-080 GEN
Solar/Wind Harmer
6.272
970683AG2-441 GEN
Solar/Wind Harmer
9.698
970681AG2-440 GEN
Solar/Wind Harmer
7.758
946301AF1-294 GEN
Solar/Wind Harmer
2.864
961791AG1-021 GEN
Solar/Wind Harmer
1.393
315657AE1-056 GEN
Solar/Wind Harmer
4.998
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.144
3145573BETHELC
Solar/Wind Harmer
0.144
970285AG2-188 GEN
Solar/Wind Harmer
10.95
971845AH1-439 GEN
Solar/Wind Harmer
6.225
3150411LDYSMT5
Adder
18.406
3150381LDYSMT2
Adder
17.615
972213AH1-691 GEN
Adder
2.98
972215AH1-692 GEN
Adder
2.98
316118AC1-105 GEN
Solar/Wind Harmer
0.352
3147173SINAI
Solar/Wind Harmer
0.134
3147243WELCO
Solar/Wind Harmer
0.084
316223AC1-118
Solar/Wind Harmer
0.093
972205AH1-687 GEN
Adder
5.489
970865AG2-541 GEN
Solar/Wind Harmer
4.099
971447AH1-217 GEN
Solar/Wind Harmer
3.524
316164AC1-076 GEN
Solar/Wind Helper
1.636
NYPJM->LTFIMP_NY
CLTF
2.427
LAGNLTFEXP_LAGN->PJM
CLTF
6.271
LGEELTFEXP_LGEE->PJM
CLTF
1
WECLTFEXP_WEC->PJM
CLTF
0.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.05
TVALTFEXP_TVA->PJM
CLTF
3.173
CPLELTFEXP_CPLE->PJM
CLTF
9.213
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.977
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.753
MECLTFEXP_MEC->PJM
CLTF
2.757
SIGELTFEXP_SIGE->PJM
CLTF
0.083

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.03 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4650.58
MW Contribution:10.78
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.765
971285AH1-108 GEN
50/50
1.513
315244AE2-183_ST
50/50
5.368
963041AG1-153 GEN
50/50
4.955
3147346CASHSCORNER
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.609
971281AH1-106 GEN
Solar/Wind Harmer
3.677
971283AH1-107 GEN
Solar/Wind Harmer
3.677
941031AE2-094 GEN
Solar/Wind Harmer
40.621
944011AF1-069 GEN
Solar/Wind Harmer
12.728
970673AG2-436 GEN
Solar/Wind Harmer
44.754
970673AG2-436 GEN
Solar/Wind Harmer
22.66
971967AH1-528 GEN
Solar/Wind Harmer
39.617
3143316POE
Solar/Wind Harmer
-0.083
3151081ELIZAR1
Adder
16.891
3151091ELIZAR2
Adder
16.598
316315AB2-025 C
Solar/Wind Harmer
0.558
3152611GOSPORTB
Adder
2.345
3152621GOSPORTC
Adder
1.99
3152601GOSPORTA
Adder
1.836
315814AE2-033 C
Solar/Wind Harmer
19.205
957871AF2-081 GEN
Solar/Wind Harmer
10.278
971445AH1-216 GEN
Solar/Wind Harmer
12.702
319010AE1-072 C
Solar/Wind Harmer
4.148
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.893
316349AD2-085 GEN
Solar/Wind Harmer
1.823
316311AC2-079 GEN
Solar/Wind Harmer
10.336
316305AF2-043 C
Solar/Wind Harmer
0.617
972265AH1-717 GEN
Adder
14.121
3151201GRAVEL4
Adder
13.238
3151191GRAVEL3
Adder
13.07
3151211GRAVEL5
Adder
13.07
316369SG1_INVT
Solar/Wind Harmer
3.645
315835AF2-110_GEN
Solar/Wind Harmer
2.55
316132AB2-190 GEN1
Solar/Wind Harmer
2.062
313526AB2-022
Solar/Wind Harmer
0.549
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.547
3146396TANGLEW
Solar/Wind Harmer
0.373
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
12.532
970581AG2-369 GEN
Solar/Wind Harmer
10.778
315611Z1-036_GEN2
Solar/Wind Harmer
4.908
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
315976AC1-164 GENA
Solar/Wind Harmer
20.509
316169AC1-164_GENC
Solar/Wind Harmer
17.718
315975AC1-164 GENB
Solar/Wind Harmer
0.607
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.644
316312AB1-027
Solar/Wind Harmer
0.652
315816AE2-034 GEN
Solar/Wind Harmer
1.563
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.688
315732AD1-074 GEN1
Solar/Wind Harmer
3.84
315733AD1-074 GEN2
Solar/Wind Harmer
3.84
315735AD1-075 GEN1
Solar/Wind Harmer
1.921
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.243
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316314AB2-024 C
Solar/Wind Harmer
1.606
315662AE1-191 GEN
Solar/Wind Harmer
2.261
315666AE1-190 GEN
Solar/Wind Harmer
0.565
3152251N ANNA1
50/50
17.76
3151791S ANNAG2
50/50
0.883
3151781S ANNAS1
50/50
0.454
3151741LOISA C
50/50
0.935
3151751LOISA D
50/50
17.091
970119AG2-088 GEN
50/50
28.238
3150851SPRUNCC
50/50
0.925
315243AE2-183_GT3
50/50
3.105
3151051BRUNSWICKS1
50/50
5.079
3151021BRUNSWICKG1
50/50
2.447
971451AH1-221 GEN
50/50
7.433
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
4.001
315683AE1-153 C
Solar/Wind Harmer
25.661
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.735
939411AE1-173 GEN
Solar/Wind Harmer
108.776
3143336POWHATN
Solar/Wind Harmer
2.52
316294AC1-161 GEN
Solar/Wind Harmer
6.764
944591AF1-124 GEN
Solar/Wind Harmer
94.789
316375AC2-012 GEN
Solar/Wind Harmer
7.16
3150981CHESPKA
Adder
2.299
970659AG2-427 GEN
Solar/Wind Harmer
10.98
316381AD1-082 GEN
Solar/Wind Harmer
1.894
315671AE2-027_GEN
Solar/Wind Harmer
15.462
970661AG2-428 GEN
Solar/Wind Harmer
21.895
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.387
316336AC2-165 C
Solar/Wind Harmer
3.574
3145336SMITFLD
Solar/Wind Harmer
-0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.414
316072AD1-144
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
1.935
961611AG1-000B GEN
Solar/Wind Harmer
10.078
971647AH1-324 GEN
Solar/Wind Harmer
10.206
316093AE2-104_GEN
Solar/Wind Harmer
5.931
971069AG2-661 GEN
Solar/Wind Harmer
3.227
316458AB2-190 GEN2
Solar/Wind Harmer
2.062
970129AG2-093 GEN
Solar/Wind Harmer
4.65
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.372
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
970087AG2-069 GEN
Solar/Wind Harmer
18.798
944631AF1-128 GEN
Adder
85.046
315800Z1-036_GEN1
Solar/Wind Harmer
4.908
971317AH1-138 GEN
Solar/Wind Harmer
2.48
316159AE1-175 C
Solar/Wind Harmer
0.532
3130156CHOWAN
Solar/Wind Harmer
-0.02
957481AF2-042 GEN
Solar/Wind Harmer
60.65
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.105
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316023GEN1_S
Solar/Wind Harmer
1.295
315693AD1-088 GEN
Solar/Wind Harmer
9.573
962491AG1-098 GEN
Solar/Wind Harmer
12.783
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.56
970937AG2-583 GEN
Solar/Wind Harmer
13.548
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.71
960081AF2-299 GEN
Solar/Wind Harmer
2.117
971777AH1-397 GEN
Solar/Wind Harmer
2.211
3141843SHACKLE
Adder
0.855
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
971795AH1-408 GEN
Solar/Wind Harmer
13.912
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.484
316011AB1-132 GEN
Solar/Wind Harmer
3.849
962571AG1-106 GEN
Solar/Wind Harmer
2.644
316190AA2-174 GEN
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.06
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
2.787
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.48
972197AH1-683 GEN
Adder
2.852
3152261N ANNA2
50/50
17.758
3151771S ANNAG1
50/50
0.883
3151801S ANNAS2
50/50
0.454
3151761LOISA E
50/50
34.843
972183AH1-676 GEN
50/50
278.318
3150861SPRUNCD
50/50
0.925
3151031BRUNSWICKG2
50/50
2.447
3147666LOUISA
Solar/Wind Harmer
-0.078
316313AB2-026
Solar/Wind Harmer
0.573
316258AE1-075 C
Solar/Wind Harmer
0.516
316405AF2-144 C
Solar/Wind Harmer
0.544
3143336POWHATN
Solar/Wind Harmer
2.142
315773AC2-141 GEN
Solar/Wind Harmer
8.749
315839AE2-212 C
Solar/Wind Harmer
0.627
944581AF1-123 GEN
Solar/Wind Harmer
94.449
944601AF1-125 GEN
Solar/Wind Harmer
92.975
315813AE1-149 C
Solar/Wind Harmer
12.969
3151101ELIZAR3
Adder
17.107
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
1.946
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.352
970661AG2-428 GEN
Solar/Wind Harmer
3.88
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.501
3151221GRAVEL6
Adder
13.222
3151171GRAVELC
Adder
2.544
961611AG1-000B GEN
Solar/Wind Harmer
4.3
315778AD1-151 GEN
Solar/Wind Harmer
17.67
970129AG2-093 GEN
Solar/Wind Harmer
11.479
970133AG2-095 GEN
Solar/Wind Harmer
2.292
316320Y1-086
Solar/Wind Harmer
1.192
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.742
316435W1029_GEN3
Solar/Wind Harmer
3.654
970917AG2-570 GEN
Solar/Wind Harmer
50.335
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.675
3150921YORKTN3
Adder
4.485
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
316382AG1-145 C
Solar/Wind Harmer
0.598
970293AG2-193 GEN
Solar/Wind Harmer
2.461
3146376EDENTON
Solar/Wind Harmer
-0.02
3142416OLDCHRC
Solar/Wind Harmer
1.951
315614AA2-178 GEN
Solar/Wind Harmer
2.084
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316365GEN2_N
Solar/Wind Harmer
1.295
3156081AA2-088 GEN
Solar/Wind Harmer
6.195
971157AH1-035 GEN
Solar/Wind Harmer
2.38
315737AD1-076 GEN
Solar/Wind Harmer
3.609
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.82
961681AG1-008 GEN
Solar/Wind Harmer
14.82
966621AG1-532 GEN
Solar/Wind Harmer
0.382
3141843SHACKLE
Adder
0.855
316203AE2-005 GEN
Solar/Wind Harmer
7.929
316280AD1-041 GEN
Solar/Wind Harmer
1.413
3141766HARMONY
Solar/Wind Harmer
1.669
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.619
316486AD2-202 GEN
Solar/Wind Harmer
0.474
316156AD2-030 GEN
Solar/Wind Harmer
0.499
3141873WAN 176
Solar/Wind Harmer
2.218
3156021HOLLOMANSOL
Solar/Wind Harmer
2.51
316463AE2-346 GEN
Solar/Wind Harmer
0.301
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.327
316473AC1-191 GEN
Solar/Wind Harmer
2.002
313506AB2-031 GEN
Solar/Wind Harmer
1.493
970909AG2-566 GEN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.86
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.701
3147133PAMPLIN
Solar/Wind Harmer
-0.056
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.505
3150401LDYSMT4
Adder
18.264
3150371LDYSMT1
Adder
17.648
316044AC1-158 PL1
Solar/Wind Helper
5.408
316450AC1-158 RIC
Solar/Wind Helper
1.442
316170AC1-121 GEN2
Solar/Wind Helper
0.698
971193AH1-056 GEN
Solar/Wind Harmer
5.031
316059AD1-063 C
Solar/Wind Harmer
0.424
957601AF2-054 GEN
Solar/Wind Harmer
0.559
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.66
3146043SEABORD
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
315607AA1-063A GEN
Solar/Wind Harmer
1.878
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.696
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.006
972189AH1-679 GEN
Adder
2.721
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.071
970285AG2-188 GEN
Solar/Wind Harmer
15.636
972205AH1-687 GEN
Adder
6.614
3150411LDYSMT5
Adder
18.321
3150381LDYSMT2
Adder
17.534
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
316164AC1-076 GEN
Solar/Wind Helper
2.448
971133AH1-012 GEN
50/50
5.78
3151731LOISA B
50/50
17.091
3151721LOISA A
50/50
17.002
970533AG2-339 GEN
50/50
17.139
970531AG2-338 GEN
50/50
6.856
315242AE2-183_GT2
50/50
3.105
315241AE2-183_GT1
50/50
3.086
972185AH1-677 GEN
50/50
11.194
3151041BRUNSWICKG3
50/50
2.447
972187AH1-678 GEN
50/50
5.616
966001AG1-469 GEN
Solar/Wind Harmer
0.521
971223AH1-071 GEN
Solar/Wind Harmer
2.974
3143526WINTERP
Solar/Wind Harmer
-0.117
3144356SAPONY
Solar/Wind Harmer
0.722
316036AC1-147 C
Solar/Wind Harmer
0.558
3150991CHESPKB
Adder
1.929
3150991CHESPKB
Adder
1.882
3142956BIRDNECK
Solar/Wind Harmer
1.109
316316AC1-027 C
Solar/Wind Harmer
0.635
316185AD1-033 GEN
Solar/Wind Harmer
2.18
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
316240AF1-291 C
Solar/Wind Harmer
0.622
970657AG2-426 GEN
Solar/Wind Harmer
6.448
970657AG2-426 GEN
Solar/Wind Harmer
1.348
970933AG2-581 GEN
Solar/Wind Harmer
19.327
944641AF1-129 GEN
Adder
87.32
316339AD2-160 GEN
Solar/Wind Harmer
1.387
316018AA1-139 ULT2
Solar/Wind Harmer
1.761
316017AA1-139 ULT1
Solar/Wind Harmer
1.663
316236AE1-162_GEN
Solar/Wind Harmer
0.619
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.424
3130086AYDLETT
Solar/Wind Harmer
-0.082
316033AB2-134 GEN
Solar/Wind Harmer
6.58
315697AD1-025 GEN
Solar/Wind Harmer
4.127
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.654
316433W1029_GEN2
Solar/Wind Harmer
3.654
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.58
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.715
3150701DARBY 4
Adder
12.685
3150681DARBY 2
Adder
12.67
3150671DARBY 1
Adder
12.655
315742AE1-103 GEN
Solar/Wind Harmer
2.07
3146376EDENTON
Solar/Wind Harmer
0.584
3146376EDENTON
Solar/Wind Harmer
0.584
316075AC2-137 C
Solar/Wind Harmer
0.526
3142296MT RD221
Adder
0.55
970099AG2-077 GEN
Solar/Wind Harmer
24.26
316065AD1-022 GEN
Solar/Wind Harmer
9.447
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.268
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.726
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
316181AB2-040 GEN
Solar/Wind Harmer
2.591
970301AG2-198 GEN
Solar/Wind Harmer
9.277
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.853
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.059
3145593CAROLNA
Solar/Wind Harmer
0.152
3145783HORNRTN
Solar/Wind Harmer
2.159
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.54
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.505
3144293JTRSVLE
Adder
0.425
3150341NORNECKC1
Adder
1.555
3150341NORNECKC1
Adder
1.542
3150391LDYSMT3
Adder
18.23
972195AH1-682 GEN
Adder
2.396
316447AC1-158 HLD
Solar/Wind Helper
11.902
315651AD1-115 GEN
Solar/Wind Helper
1.457
972219AH1-694 GEN
Adder
2.053
316045AC1-158 PL2
Solar/Wind Helper
17.311
316254AC1-120 GEN1
Solar/Wind Helper
2.093
316006AB2-029 C
Solar/Wind Helper
0.162
NYPJM->LTFIMP_NY
CLTF
2.632
LGEELTFEXP_LGEE->PJM
CLTF
1.138
LAGNLTFEXP_LAGN->PJM
CLTF
6.822
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.257
WECLTFEXP_WEC->PJM
CLTF
0.551
TVALTFEXP_TVA->PJM
CLTF
3.456
CPLELTFEXP_CPLE->PJM
CLTF
9.69
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.42
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.761
MECLTFEXP_MEC->PJM
CLTF
3.094
SIGELTFEXP_SIGE->PJM
CLTF
0.094

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 11-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 11-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:117.81 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4641.56
MW Contribution:10.78
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.765
971285AH1-108 GEN
50/50
1.513
315244AE2-183_ST
50/50
5.368
963041AG1-153 GEN
50/50
4.955
3147346CASHSCORNER
Solar/Wind Harmer
0.41
316233AE1-074 FULL
Solar/Wind Harmer
0.609
971281AH1-106 GEN
Solar/Wind Harmer
3.677
971283AH1-107 GEN
Solar/Wind Harmer
3.677
941031AE2-094 GEN
Solar/Wind Harmer
40.621
944011AF1-069 GEN
Solar/Wind Harmer
12.728
970673AG2-436 GEN
Solar/Wind Harmer
44.754
970673AG2-436 GEN
Solar/Wind Harmer
22.66
971967AH1-528 GEN
Solar/Wind Harmer
39.617
3143316POE
Solar/Wind Harmer
-0.083
3151081ELIZAR1
Adder
16.891
3151091ELIZAR2
Adder
16.598
316315AB2-025 C
Solar/Wind Harmer
0.558
3152611GOSPORTB
Adder
2.345
3152621GOSPORTC
Adder
1.99
3152601GOSPORTA
Adder
1.836
315814AE2-033 C
Solar/Wind Harmer
19.205
957871AF2-081 GEN
Solar/Wind Harmer
10.278
971445AH1-216 GEN
Solar/Wind Harmer
12.702
319010AE1-072 C
Solar/Wind Harmer
4.148
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.893
316349AD2-085 GEN
Solar/Wind Harmer
1.823
316311AC2-079 GEN
Solar/Wind Harmer
10.336
316305AF2-043 C
Solar/Wind Harmer
0.617
972265AH1-717 GEN
Adder
14.121
3151201GRAVEL4
Adder
13.238
3151191GRAVEL3
Adder
13.07
3151211GRAVEL5
Adder
13.07
316369SG1_INVT
Solar/Wind Harmer
3.645
315835AF2-110_GEN
Solar/Wind Harmer
2.55
316132AB2-190 GEN1
Solar/Wind Harmer
2.062
313526AB2-022
Solar/Wind Harmer
0.549
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.547
3146396TANGLEW
Solar/Wind Harmer
0.373
3145176PASQUOTANK
Solar/Wind Harmer
-0.013
970085AG2-068 GEN
Solar/Wind Harmer
12.532
970581AG2-369 GEN
Solar/Wind Harmer
10.778
315611Z1-036_GEN2
Solar/Wind Harmer
4.908
3130156CHOWAN
Solar/Wind Harmer
-0.02
3130156CHOWAN
Solar/Wind Harmer
-0.02
315976AC1-164 GENA
Solar/Wind Harmer
20.509
316169AC1-164_GENC
Solar/Wind Harmer
17.718
315975AC1-164 GENB
Solar/Wind Harmer
0.607
957831AF2-077 GEN
Solar/Wind Harmer
0.583
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.644
316312AB1-027
Solar/Wind Harmer
0.652
315816AE2-034 GEN
Solar/Wind Harmer
1.563
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.688
315732AD1-074 GEN1
Solar/Wind Harmer
3.84
315733AD1-074 GEN2
Solar/Wind Harmer
3.84
315735AD1-075 GEN1
Solar/Wind Harmer
1.921
3143873LANEXA
Solar/Wind Harmer
-0.011
316318V4-068
Solar/Wind Harmer
0.47
3145893MURPHYS
Solar/Wind Harmer
-0.051
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
970601AG2-382 GEN
Solar/Wind Harmer
8.243
946281AF1-292 GEN
Solar/Wind Harmer
0.421
316314AB2-024 C
Solar/Wind Harmer
1.606
315662AE1-191 GEN
Solar/Wind Harmer
2.261
315666AE1-190 GEN
Solar/Wind Harmer
0.565
316059AD1-063 C
Solar/Wind Harmer
0.424
957601AF2-054 GEN
Solar/Wind Harmer
0.559
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.66
3146043SEABORD
Solar/Wind Harmer
-0.019
3145513AHOSKIE
Solar/Wind Harmer
0.162
961941AG1-037 GEN
Solar/Wind Harmer
0.14
3145513AHOSKIE
Solar/Wind Harmer
-0.019
315607AA1-063A GEN
Solar/Wind Harmer
1.878
3145683EARLEYS
Solar/Wind Harmer
-0.037
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.073
315652AC1-086 GEN
Solar/Wind Harmer
20.696
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.006
972189AH1-679 GEN
Adder
2.721
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.071
970285AG2-188 GEN
Solar/Wind Harmer
15.636
315657AE1-056 GEN
Solar/Wind Harmer
6.696
972205AH1-687 GEN
Adder
6.614
3150411LDYSMT5
Adder
18.321
3150381LDYSMT2
Adder
17.534
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
316164AC1-076 GEN
Solar/Wind Helper
2.448
970831AG2-522 GEN
Solar/Wind Harmer
3.798
971133AH1-012 GEN
50/50
5.78
3151731LOISA B
50/50
17.091
3151721LOISA A
50/50
17.002
970533AG2-339 GEN
50/50
17.139
970531AG2-338 GEN
50/50
6.856
315242AE2-183_GT2
50/50
3.105
315241AE2-183_GT1
50/50
3.086
972185AH1-677 GEN
50/50
11.194
3151041BRUNSWICKG3
50/50
2.447
972187AH1-678 GEN
50/50
5.616
966001AG1-469 GEN
Solar/Wind Harmer
0.521
971223AH1-071 GEN
Solar/Wind Harmer
2.974
3143526WINTERP
Solar/Wind Harmer
-0.117
3144356SAPONY
Solar/Wind Harmer
0.722
316036AC1-147 C
Solar/Wind Harmer
0.558
3150991CHESPKB
Adder
1.929
3150991CHESPKB
Adder
1.882
3142956BIRDNECK
Solar/Wind Harmer
1.109
316316AC1-027 C
Solar/Wind Harmer
0.635
316185AD1-033 GEN
Solar/Wind Harmer
2.18
3145506HICKORY
Solar/Wind Harmer
-0.082
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
316240AF1-291 C
Solar/Wind Harmer
0.622
970657AG2-426 GEN
Solar/Wind Harmer
6.448
970657AG2-426 GEN
Solar/Wind Harmer
1.348
970933AG2-581 GEN
Solar/Wind Harmer
19.327
944641AF1-129 GEN
Adder
87.32
316339AD2-160 GEN
Solar/Wind Harmer
1.387
316018AA1-139 ULT2
Solar/Wind Harmer
1.761
316017AA1-139 ULT1
Solar/Wind Harmer
1.663
316236AE1-162_GEN
Solar/Wind Harmer
0.619
3137176SLIGO L2192
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
2.424
3130086AYDLETT
Solar/Wind Harmer
-0.082
316033AB2-134 GEN
Solar/Wind Harmer
6.58
315697AD1-025 GEN
Solar/Wind Harmer
4.127
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.654
316433W1029_GEN2
Solar/Wind Harmer
3.654
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.58
3142946ENON
Solar/Wind Harmer
-0.002
3150691DARBY 3
Adder
12.715
3150701DARBY 4
Adder
12.685
3150681DARBY 2
Adder
12.67
3150671DARBY 1
Adder
12.655
315742AE1-103 GEN
Solar/Wind Harmer
2.07
3146376EDENTON
Solar/Wind Harmer
0.584
3146376EDENTON
Solar/Wind Harmer
0.584
316075AC2-137 C
Solar/Wind Harmer
0.526
3142296MT RD221
Adder
0.55
970099AG2-077 GEN
Solar/Wind Harmer
24.26
316065AD1-022 GEN
Solar/Wind Harmer
9.447
3152251N ANNA1
50/50
17.76
3151791S ANNAG2
50/50
0.883
3151781S ANNAS1
50/50
0.454
3151741LOISA C
50/50
0.935
3151751LOISA D
50/50
17.091
970119AG2-088 GEN
50/50
28.238
3150851SPRUNCC
50/50
0.925
315243AE2-183_GT3
50/50
3.105
3151051BRUNSWICKS1
50/50
5.079
3152261N ANNA2
50/50
17.758
3151771S ANNAG1
50/50
0.883
3151801S ANNAS2
50/50
0.454
3151761LOISA E
50/50
34.843
972183AH1-676 GEN
50/50
278.318
3150861SPRUNCD
50/50
0.925
3151031BRUNSWICKG2
50/50
2.447
3147666LOUISA
Solar/Wind Harmer
-0.078
316313AB2-026
Solar/Wind Harmer
0.573
316258AE1-075 C
Solar/Wind Harmer
0.516
316405AF2-144 C
Solar/Wind Harmer
0.544
3143336POWHATN
Solar/Wind Harmer
2.142
315773AC2-141 GEN
Solar/Wind Harmer
8.749
315839AE2-212 C
Solar/Wind Harmer
0.627
944581AF1-123 GEN
Solar/Wind Harmer
94.449
944601AF1-125 GEN
Solar/Wind Harmer
92.975
315813AE1-149 C
Solar/Wind Harmer
12.969
3151101ELIZAR3
Adder
17.107
3144873MCLAUGH
Solar/Wind Harmer
-0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.584
970659AG2-427 GEN
Solar/Wind Harmer
1.946
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.352
970661AG2-428 GEN
Solar/Wind Harmer
3.88
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.501
3151221GRAVEL6
Adder
13.222
3151171GRAVELC
Adder
2.544
961611AG1-000B GEN
Solar/Wind Harmer
4.3
315778AD1-151 GEN
Solar/Wind Harmer
17.67
970129AG2-093 GEN
Solar/Wind Harmer
11.479
970133AG2-095 GEN
Solar/Wind Harmer
2.292
316320Y1-086
Solar/Wind Harmer
1.192
3143096IRON208
Adder
0.757
3143096IRON208
Adder
0.742
316435W1029_GEN3
Solar/Wind Harmer
3.654
970917AG2-570 GEN
Solar/Wind Harmer
50.335
3146516WINFALL
Solar/Wind Harmer
-0.02
3144216WINCHST
Adder
0.675
3150921YORKTN3
Adder
4.485
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.007
316382AG1-145 C
Solar/Wind Harmer
0.598
970293AG2-193 GEN
Solar/Wind Harmer
2.461
3146376EDENTON
Solar/Wind Harmer
-0.02
3142416OLDCHRC
Solar/Wind Harmer
1.951
315614AA2-178 GEN
Solar/Wind Harmer
2.084
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316365GEN2_N
Solar/Wind Harmer
1.295
3156081AA2-088 GEN
Solar/Wind Harmer
6.195
971157AH1-035 GEN
Solar/Wind Harmer
2.38
315737AD1-076 GEN
Solar/Wind Harmer
3.609
3145893MURPHYS
Solar/Wind Harmer
0.132
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.019
957521AF2-046 GEN
Solar/Wind Harmer
14.82
961681AG1-008 GEN
Solar/Wind Harmer
14.82
966621AG1-532 GEN
Solar/Wind Harmer
0.382
3141843SHACKLE
Adder
0.855
316203AE2-005 GEN
Solar/Wind Harmer
7.929
316280AD1-041 GEN
Solar/Wind Harmer
1.413
3141766HARMONY
Solar/Wind Harmer
1.669
3146173TUNIS
Solar/Wind Harmer
-0.019
316478AD1-087 GEN
Solar/Wind Harmer
1.619
316486AD2-202 GEN
Solar/Wind Harmer
0.474
316156AD2-030 GEN
Solar/Wind Harmer
0.499
3141873WAN 176
Solar/Wind Harmer
2.218
3156021HOLLOMANSOL
Solar/Wind Harmer
2.51
316463AE2-346 GEN
Solar/Wind Harmer
0.301
316140AB2-099
Solar/Wind Harmer
0.125
962331AG1-082 GEN
Solar/Wind Harmer
2.327
316473AC1-191 GEN
Solar/Wind Harmer
2.002
313506AB2-031 GEN
Solar/Wind Harmer
1.493
970909AG2-566 GEN
Solar/Wind Harmer
1.761
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.86
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
942461AE2-259 GEN
Solar/Wind Harmer
2.701
3147133PAMPLIN
Solar/Wind Harmer
-0.056
971193AH1-056 GEN
Solar/Wind Harmer
11.159
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.505
3150401LDYSMT4
Adder
18.264
3150371LDYSMT1
Adder
17.648
316044AC1-158 PL1
Solar/Wind Helper
5.408
316450AC1-158 RIC
Solar/Wind Helper
1.442
316170AC1-121 GEN2
Solar/Wind Helper
0.698
3145893MURPHYS
Solar/Wind Harmer
0.526
3145893MURPHYS
Solar/Wind Harmer
-0.034
316441AF1-014 GEN
Solar/Wind Harmer
1.268
3146173TUNIS
Solar/Wind Harmer
-0.019
3146173TUNIS
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.726
966871AG1-558 GEN
Solar/Wind Harmer
0.559
966871AG1-558 GEN
Solar/Wind Harmer
0.191
316181AB2-040 GEN
Solar/Wind Harmer
2.591
970301AG2-198 GEN
Solar/Wind Harmer
9.277
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.853
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.059
3145593CAROLNA
Solar/Wind Harmer
0.152
3145783HORNRTN
Solar/Wind Harmer
2.159
3145783HORNRTN
Solar/Wind Harmer
1.727
3145783HORNRTN
Solar/Wind Harmer
0.54
3145783HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
-0.054
3147133PAMPLIN
Solar/Wind Harmer
-0.018
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.505
3144293JTRSVLE
Adder
0.425
3150341NORNECKC1
Adder
1.555
3150341NORNECKC1
Adder
1.542
3150391LDYSMT3
Adder
18.23
972195AH1-682 GEN
Adder
2.396
316447AC1-158 HLD
Solar/Wind Helper
11.902
315651AD1-115 GEN
Solar/Wind Helper
1.457
3151021BRUNSWICKG1
50/50
2.447
971451AH1-221 GEN
50/50
7.433
3147666LOUISA
Solar/Wind Harmer
-0.135
316192AB2-158 GEN
Solar/Wind Harmer
4.001
3143226MDLTHAN
Solar/Wind Harmer
-0.024
3143526WINTERP
Solar/Wind Harmer
-0.117
940641AE2-051 GEN
Solar/Wind Harmer
20.735
939411AE1-173 GEN
Solar/Wind Harmer
108.776
3143336POWHATN
Solar/Wind Harmer
2.52
316294AC1-161 GEN
Solar/Wind Harmer
6.764
944591AF1-124 GEN
Solar/Wind Harmer
94.789
316375AC2-012 GEN
Solar/Wind Harmer
7.16
3150981CHESPKA
Adder
2.299
970659AG2-427 GEN
Solar/Wind Harmer
10.98
316381AD1-082 GEN
Solar/Wind Harmer
1.894
315671AE2-027_GEN
Solar/Wind Harmer
15.462
970661AG2-428 GEN
Solar/Wind Harmer
21.895
3142543TWELFTH
Solar/Wind Harmer
-0.002
316388AE2-253 GEN
Solar/Wind Harmer
1.387
316336AC2-165 C
Solar/Wind Harmer
3.574
3145336SMITFLD
Solar/Wind Harmer
-0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.414
316072AD1-144
Solar/Wind Harmer
0.413
3151171GRAVELC
Adder
1.935
961611AG1-000B GEN
Solar/Wind Harmer
10.078
971647AH1-324 GEN
Solar/Wind Harmer
10.206
316093AE2-104_GEN
Solar/Wind Harmer
5.931
971069AG2-661 GEN
Solar/Wind Harmer
3.227
316458AB2-190 GEN2
Solar/Wind Harmer
2.062
970129AG2-093 GEN
Solar/Wind Harmer
4.65
3143096IRON208
Adder
0.757
970919AG2-571 GEN
Solar/Wind Harmer
6.372
3146516WINFALL
Solar/Wind Harmer
-0.065
3146516WINFALL
Solar/Wind Harmer
-0.02
3138126ROCKLANDING
Solar/Wind Harmer
0.062
970087AG2-069 GEN
Solar/Wind Harmer
18.798
944631AF1-128 GEN
Adder
85.046
315800Z1-036_GEN1
Solar/Wind Harmer
4.908
971317AH1-138 GEN
Solar/Wind Harmer
2.48
316159AE1-175 C
Solar/Wind Harmer
0.532
3130156CHOWAN
Solar/Wind Harmer
-0.02
957481AF2-042 GEN
Solar/Wind Harmer
60.65
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3145663CRESWEL
Solar/Wind Harmer
-0.054
971163AH1-040 GEN
Solar/Wind Harmer
18.105
3142433PROV 92
Solar/Wind Harmer
-0.077
3142433PROV 92
Adder
0.334
3142433PROV 92
Adder
0.334
316023GEN1_S
Solar/Wind Harmer
1.295
315693AD1-088 GEN
Solar/Wind Harmer
9.573
962491AG1-098 GEN
Solar/Wind Harmer
12.783
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
0.56
970937AG2-583 GEN
Solar/Wind Harmer
13.548
3146206CASHIE
Solar/Wind Harmer
-0.019
971547AH1-271 GEN
Solar/Wind Harmer
4.71
960081AF2-299 GEN
Solar/Wind Harmer
2.117
971777AH1-397 GEN
Solar/Wind Harmer
2.211
3141843SHACKLE
Adder
0.855
3141766HARMONY
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.019
971795AH1-408 GEN
Solar/Wind Harmer
13.912
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.484
316011AB1-132 GEN
Solar/Wind Harmer
3.849
962571AG1-106 GEN
Solar/Wind Harmer
2.644
316190AA2-174 GEN
Solar/Wind Harmer
0.225
3138133OCRAN
Solar/Wind Harmer
-0.011
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.06
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
316174AB2-169 GEN
Solar/Wind Harmer
2.787
3144293JTRSVLE
Adder
0.505
3150351NORNECKC2
Adder
1.48
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316045AC1-158 PL2
Solar/Wind Helper
17.311
316254AC1-120 GEN1
Solar/Wind Helper
2.093
316006AB2-029 C
Solar/Wind Helper
0.162
NYPJM->LTFIMP_NY
CLTF
2.632
LGEELTFEXP_LGEE->PJM
CLTF
1.138
LAGNLTFEXP_LAGN->PJM
CLTF
6.822
WECLTFEXP_WEC->PJM
CLTF
0.551
CBM South 2LTFEXP_CBM-S2->PJM
CBM
21.257
TVALTFEXP_TVA->PJM
CLTF
3.456
CPLELTFEXP_CPLE->PJM
CLTF
9.69
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.259
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.42
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.761
MECLTFEXP_MEC->PJM
CLTF
3.094
SIGELTFEXP_SIGE->PJM
CLTF
0.094

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019B_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.93 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3561.83
MW Contribution:8.69
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
3.273
972223AH1-696 GEN
50/50
17.601
3150151POSSMC1
50/50
2.228
3141346CRANES
50/50
0.247
3150011OMF A
50/50
0.367
3140676OCCOQUN
50/50
0.487
972197AH1-683 GEN
50/50
4.033
972219AH1-694 GEN
50/50
2.904
957971AF2-091 GEN
Solar/Wind Harmer
1.991
972135AH1-637 GEN
Solar/Wind Harmer
1.978
966881AG1-559 GEN
Solar/Wind Harmer
0.202
316337AD2-073 GEN
Solar/Wind Harmer
0.512
3150351NORNECKC2
Adder
1.667
964211AG1-282 GEN
Solar/Wind Harmer
0.563
3141726DUNNSVL
Solar/Wind Harmer
-0.074
962861AG1-135 GEN
Solar/Wind Harmer
6.97
961951AG1-038 GEN
Solar/Wind Harmer
2.439
3138133OCRAN
Solar/Wind Harmer
-0.011
316045AC1-158 PL2
Solar/Wind Harmer
5.715
3142416OLDCHRC
Solar/Wind Harmer
-0.047
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3141766HARMONY
Solar/Wind Harmer
-0.004
971777AH1-397 GEN
Solar/Wind Harmer
2.137
3141843SHACKLE
Adder
0.827
3142433PROV 92
Solar/Wind Harmer
-0.072
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
3143096IRON208
Adder
0.67
944631AF1-128 GEN
Adder
76.064
3142543TWELFTH
Solar/Wind Harmer
-0.002
3150851SPRUNCC
Adder
0.733
3143526WINTERP
Solar/Wind Harmer
-0.092
3150101POSSM6S
50/50
2.528
3150081POSSM6A
50/50
1.654
3150151POSSMC1
50/50
2.228
3150151POSSMC1
50/50
2.228
3150331BIRCHWDA
50/50
34.1
3150021OMF B
50/50
0.367
3141316ARNOLDS
50/50
0.47
3150401LDYSMT4
50/50
25.826
3150371LDYSMT1
50/50
24.955
970497AG2-320 GEN
50/50
16.885
966881AG1-559 GEN
Solar/Wind Harmer
0.591
970737AG2-469 GEN
Solar/Wind Harmer
9.802
3141906WESTMOR
Solar/Wind Harmer
-0.008
971781AH1-399 GEN
Solar/Wind Harmer
1.188
3150351NORNECKC2
Adder
1.695
316404AE1-155 C
Solar/Wind Harmer
3.591
316484AD2-074 GEN
Solar/Wind Harmer
4.661
970009AG2-005 GEN
Solar/Wind Harmer
2.314
316473AC1-191 GEN
Solar/Wind Harmer
1.987
962971AG1-146 GEN
Solar/Wind Harmer
3.46
316044AC1-158 PL1
Solar/Wind Harmer
1.787
316450AC1-158 RIC
Solar/Wind Harmer
0.476
3142416OLDCHRC
Solar/Wind Harmer
1.836
3141766HARMONY
Solar/Wind Harmer
1.619
316156AD2-030 GEN
Solar/Wind Harmer
0.486
3141873WAN 176
Solar/Wind Harmer
2.158
316280AD1-041 GEN
Solar/Wind Harmer
1.37
316203AE2-005 GEN
Solar/Wind Harmer
7.663
3141843SHACKLE
Adder
0.827
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
970293AG2-193 GEN
Solar/Wind Harmer
2.261
3143096IRON208
Adder
0.67
3143096IRON208
Adder
0.657
3142946ENON
Solar/Wind Harmer
-0.006
3150861SPRUNCD
Adder
0.733
316382AG1-145 C
Solar/Wind Harmer
0.537
3147666LOUISA
Solar/Wind Harmer
-0.041
970133AG2-095 GEN
Solar/Wind Harmer
1.996
970129AG2-093 GEN
Solar/Wind Harmer
9.954
3150921YORKTN3
Adder
3.952
3144216WINCHST
Adder
0.592
315778AD1-151 GEN
Solar/Wind Harmer
15.278
965281AG1-393 GEN
Solar/Wind Harmer
2.203
315839AE2-212 C
Solar/Wind Harmer
0.53
316170AC1-121 GEN2
Solar/Wind Harmer
0.473
961611AG1-000B GEN
Solar/Wind Harmer
3.695
3151221GRAVEL6
Adder
11.329
3151171GRAVELC
Adder
2.18
3145336SMITFLD
Solar/Wind Harmer
-0.007
315813AE1-149 C
Solar/Wind Harmer
10.889
315773AC2-141 GEN
Solar/Wind Harmer
7.274
970659AG2-427 GEN
Solar/Wind Harmer
1.634
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
2.815
3151101ELIZAR3
Adder
14.297
970661AG2-428 GEN
Solar/Wind Harmer
3.259
3144873MCLAUGH
Solar/Wind Harmer
0
3132273ORANGE
Solar/Wind Harmer
-0.003
944581AF1-123 GEN
Solar/Wind Harmer
78.643
944601AF1-125 GEN
Solar/Wind Harmer
77.415
3146456SLIGO L269
Solar/Wind Harmer
-0.017
971153AH1-033 GEN
Solar/Wind Harmer
2.095
316320Y1-086
Solar/Wind Harmer
1.002
3150301M RUN C
Adder
20.568
3150091POSSM6B
50/50
1.654
3150071POSSM 5
50/50
101.841
3150181POSSMC2
50/50
2.247
3150181POSSMC2
50/50
2.228
3150181POSSMC2
50/50
2.228
957191AF2-013 GEN
50/50
16.389
3150391LDYSMT3
50/50
25.778
972195AH1-682 GEN
50/50
3.388
315673AE1-157 GEN
Solar/Wind Harmer
14.947
957411AF2-035 GEN
Solar/Wind Harmer
8.848
970317AG2-208 GEN
Solar/Wind Harmer
8.602
316468AD1-105 GEN
Solar/Wind Harmer
2.147
316077AC2-138 C
Solar/Wind Harmer
0.396
3150341NORNECKC1
Adder
1.751
3150341NORNECKC1
Adder
1.737
958261AF2-120 GEN
Solar/Wind Harmer
7.213
316487AF1-042 GEN
Solar/Wind Harmer
2.439
966871AG1-558 GEN
Solar/Wind Harmer
0.555
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3142296MT RD221
Adder
0.518
316447AC1-158 HLD
Solar/Wind Harmer
3.929
316441AF1-014 GEN
Solar/Wind Harmer
1.225
316075AC2-137 C
Solar/Wind Harmer
0.488
3150691DARBY 3
Adder
11.585
3150701DARBY 4
Adder
11.558
3150681DARBY 2
Adder
11.544
3150671DARBY 1
Adder
11.531
3142366NRTHEST
Adder
0.526
3142946ENON
Solar/Wind Harmer
-0.002
3143526WINTERP
Solar/Wind Harmer
-0.092
971223AH1-071 GEN
Solar/Wind Harmer
2.216
944641AF1-129 GEN
Adder
75.175
316240AF1-291 C
Solar/Wind Harmer
0.533
316033AB2-134 GEN
Solar/Wind Harmer
5.679
315697AD1-025 GEN
Solar/Wind Harmer
3.562
315651AD1-115 GEN
Solar/Wind Harmer
7.681
316236AE1-162_GEN
Solar/Wind Harmer
0.525
970657AG2-426 GEN
Solar/Wind Harmer
5.416
970657AG2-426 GEN
Solar/Wind Harmer
1.133
316036AC1-147 C
Solar/Wind Harmer
0.467
3150991CHESPKB
Adder
1.613
3150991CHESPKB
Adder
1.574
316316AC1-027 C
Solar/Wind Harmer
0.53
3142956BIRDNECK
Solar/Wind Harmer
0.927
316185AD1-033 GEN
Solar/Wind Harmer
1.821
3145506HICKORY
Solar/Wind Harmer
-0.069
3145506HICKORY
Solar/Wind Harmer
-0.041
3145506HICKORY
Solar/Wind Harmer
-0.01
316339AD2-160 GEN
Solar/Wind Harmer
1.161
316018AA1-139 ULT2
Solar/Wind Harmer
1.474
316017AA1-139 ULT1
Solar/Wind Harmer
1.392
3137176SLIGO L2192
Solar/Wind Harmer
-0.068
3146456SLIGO L269
Solar/Wind Harmer
2.03
3130086AYDLETT
Solar/Wind Harmer
-0.068
3146386ELIZ CT
Solar/Wind Harmer
-0.017
966001AG1-469 GEN
Solar/Wind Harmer
0.321
316431W1029_GEN1
Solar/Wind Harmer
3.081
316433W1029_GEN2
Solar/Wind Harmer
3.081
3151731LOISA B
Adder
9.812
3151721LOISA A
Adder
9.761
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146516WINFALL
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3146626S HERTFORD
Solar/Wind Harmer
-0.017
3144356SAPONY
Solar/Wind Harmer
0.589
315742AE1-103 GEN
Solar/Wind Harmer
1.756
3146376EDENTON
Solar/Wind Harmer
0.496
3146376EDENTON
Solar/Wind Harmer
0.496
972185AH1-677 GEN
Adder
8.276
972187AH1-678 GEN
Adder
4.177
970933AG2-581 GEN
Solar/Wind Harmer
15.383
316065AD1-022 GEN
Solar/Wind Harmer
8.157
3145893MURPHYS
Solar/Wind Harmer
0.454
3150411LDYSMT5
50/50
25.907
3150381LDYSMT2
50/50
24.794
972213AH1-691 GEN
50/50
4.194
972215AH1-692 GEN
50/50
4.194
963051AG1-154 GEN
50/50
3.226
3141426STAFORD
Solar/Wind Harmer
-0.005
944491AF1-114 GEN
Solar/Wind Harmer
5.857
316223AC1-118
Solar/Wind Harmer
0.522
972189AH1-679 GEN
Adder
2.807
3141813NORNECK
Solar/Wind Harmer
-0.019
962981AG1-147 GEN
Solar/Wind Harmer
8.074
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3138133OCRAN
Solar/Wind Harmer
-0.006
3141913WHIT STONE
Solar/Wind Harmer
-0.018
316312AB1-027
Solar/Wind Harmer
0.614
316314AB2-024 C
Solar/Wind Harmer
1.555
316059AD1-063 C
Solar/Wind Harmer
0.411
957601AF2-054 GEN
Solar/Wind Harmer
0.544
3141873WAN 176
Solar/Wind Harmer
-0.004
315662AE1-191 GEN
Solar/Wind Harmer
2.192
315666AE1-190 GEN
Solar/Wind Harmer
0.548
3143873LANEXA
Solar/Wind Harmer
-0.011
3142433PROV 92
Adder
0.313
3142433PROV 92
Adder
0.313
971167AH1-042 GEN
Solar/Wind Harmer
17.397
315976AC1-164 GENA
Solar/Wind Harmer
19.078
316169AC1-164_GENC
Solar/Wind Harmer
16.482
315975AC1-164 GENB
Solar/Wind Harmer
0.564
316164AC1-076 GEN
Solar/Wind Harmer
1.517
957831AF2-077 GEN
Solar/Wind Harmer
0.539
3138283WHITEMARSH
Solar/Wind Harmer
0.028
971285AH1-108 GEN
Adder
1.2
316233AE1-074 FULL
Solar/Wind Harmer
0.48
971281AH1-106 GEN
Solar/Wind Harmer
2.897
971283AH1-107 GEN
Solar/Wind Harmer
2.897
316132AB2-190 GEN1
Solar/Wind Harmer
1.788
316369SG1_INVT
Solar/Wind Harmer
3.146
972265AH1-717 GEN
Adder
12.099
3151201GRAVEL4
Adder
11.342
3151191GRAVEL3
Adder
11.198
3151211GRAVEL5
Adder
11.198
971445AH1-216 GEN
Solar/Wind Harmer
10.79
3143316POE
Solar/Wind Harmer
-0.068
3151081ELIZAR1
Adder
14.117
3151091ELIZAR2
Adder
13.871
3152611GOSPORTB
Adder
1.961
3152621GOSPORTC
Adder
1.664
3152601GOSPORTA
Adder
1.535
315833AF1-017_GEN
Solar/Wind Harmer
3.27
316349AD2-085 GEN
Solar/Wind Harmer
1.531
316311AC2-079 GEN
Solar/Wind Harmer
8.684
957871AF2-081 GEN
Solar/Wind Harmer
8.603
316305AF2-043 C
Solar/Wind Harmer
0.518
319010AE1-072 C
Solar/Wind Harmer
3.475
3146406KITTY HAWK
Solar/Wind Harmer
0.014
315835AF2-110_GEN
Solar/Wind Harmer
2.143
313526AB2-022
Solar/Wind Harmer
0.461
3146486SUNBURY
Solar/Wind Harmer
-0.017
3146486SUNBURY
Solar/Wind Harmer
-0.017
316321Z2-027
Solar/Wind Harmer
0.46
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3146396TANGLEW
Solar/Wind Harmer
0.314
316315AB2-025 C
Solar/Wind Harmer
0.455
315814AE2-033 C
Solar/Wind Harmer
15.687
315611Z1-036_GEN2
Solar/Wind Harmer
4.161
3147346CASHSCORNER
Solar/Wind Harmer
0.26
941031AE2-094 GEN
Solar/Wind Harmer
31.438
944011AF1-069 GEN
Solar/Wind Harmer
9.851
3130156CHOWAN
Solar/Wind Harmer
-0.017
3130156CHOWAN
Solar/Wind Harmer
-0.017
970673AG2-436 GEN
Solar/Wind Harmer
34.947
970673AG2-436 GEN
Solar/Wind Harmer
17.695
971967AH1-528 GEN
Solar/Wind Harmer
31.136
315816AE2-034 GEN
Solar/Wind Harmer
1.339
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.31
315733AD1-074 GEN2
Solar/Wind Harmer
3.31
315735AD1-075 GEN1
Solar/Wind Harmer
1.656
965291AG1-394 GEN
Solar/Wind Harmer
1.45
3146206CASHIE
Solar/Wind Harmer
-0.016
970601AG2-382 GEN
Solar/Wind Harmer
7.123
316318V4-068
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
-0.044
3145893MURPHYS
Solar/Wind Harmer
-0.016
970085AG2-068 GEN
Solar/Wind Harmer
10.104
970581AG2-369 GEN
Solar/Wind Harmer
8.69
3145513AHOSKIE
Solar/Wind Harmer
0.141
961941AG1-037 GEN
Solar/Wind Harmer
0.121
3145513AHOSKIE
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.016
3146043SEABORD
Solar/Wind Harmer
-0.016
946281AF1-292 GEN
Solar/Wind Harmer
0.36
315607AA1-063A GEN
Solar/Wind Harmer
1.624
316087AB2-174 GEN
Solar/Wind Harmer
2.286
972193AH1-681 GEN
Adder
3.199
972205AH1-687 GEN
Adder
5.971
3151881LOWMORC
Adder
1.27
3151881LOWMORC
Adder
1.25
3151861LOWMORA
Adder
1.23
233935AB2-179 C
Solar/Wind Helper
1.735
232436AB1-176 C
Solar/Wind Helper
0.06
233923SMA
Solar/Wind Helper
1.302
233990AG1-397 GEN
Solar/Wind Helper
0.041
232432Z2-076 GEN
Solar/Wind Helper
0.091
234033AF1-007_GEN
Solar/Wind Helper
9.531
964001AG1-254 GEN
Solar/Wind Helper
1.261
228754AB1-001 C
Solar/Wind Helper
0.034
227927V4-067C
Solar/Wind Helper
0.013
219914AD2-027 C
Solar/Wind Helper
0.15
219272CLEANLIGHT C
Solar/Wind Helper
0.033
219688LUMSOLAR_S C
Solar/Wind Helper
0.052
219607WPEMNERT C
Solar/Wind Helper
0.104
214067T20SOLAR
Solar/Wind Helper
0.015
20715728PEM_W1-119
Solar/Wind Helper
0.124
20715828PEM_W1-120
Solar/Wind Helper
0.124
207459AE1-142 C O1
Solar/Wind Helper
0.373
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.109
218526CNTRALGAS2 C
Solar/Wind Helper
0.203
218524CNTRALGAS1 C
Solar/Wind Helper
0.203
966261AG1-495 GEN
Solar/Wind Helper
0.101
207530AG1-191 GEN
Solar/Wind Helper
0.081
20676328BVR_Y1-020
Solar/Wind Helper
0.033
20674828DL_W4-046
Solar/Wind Helper
0.01
20675928HOL_W4-097
Solar/Wind Helper
0.061
207484AF2-139 C O1
Solar/Wind Helper
0.103
207408W3-077 C
Solar/Wind Helper
0.103
20675728RH_W2-091
Solar/Wind Helper
0.168
3150291M RUN B
Adder
20.415
3150231REMNGT3
Adder
20.661
3150241REMNGT4
Adder
19.264
972199AH1-684 GEN
Adder
2.921
972217AH1-693 GEN
Adder
2.54
316435W1029_GEN3
Solar/Wind Harmer
3.081
3151761LOISA E
Adder
20.004
3146516WINFALL
Solar/Wind Harmer
-0.017
972183AH1-676 GEN
Adder
161.171
3146626S HERTFORD
Solar/Wind Harmer
-0.017
316313AB2-026
Solar/Wind Harmer
0.456
316258AE1-075 C
Solar/Wind Harmer
0.411
316405AF2-144 C
Solar/Wind Harmer
0.433
3143336POWHATN
Solar/Wind Harmer
1.707
3145273HOLLAND
Solar/Wind Harmer
-0.013
3146376EDENTON
Solar/Wind Harmer
-0.017
3141196NOKESVL
Solar/Wind Harmer
-0.067
315614AA2-178 GEN
Solar/Wind Harmer
1.785
971157AH1-035 GEN
Solar/Wind Harmer
2.049
3156081AA2-088 GEN
Solar/Wind Harmer
5.315
315737AD1-076 GEN
Solar/Wind Harmer
3.111
3146206CASHIE
Solar/Wind Harmer
-0.016
316365GEN2_N
Solar/Wind Harmer
1.097
3145893MURPHYS
Solar/Wind Harmer
0.113
3145893MURPHYS
Solar/Wind Harmer
-0.016
957521AF2-046 GEN
Solar/Wind Harmer
12.788
961681AG1-008 GEN
Solar/Wind Harmer
12.788
970917AG2-570 GEN
Solar/Wind Harmer
40.495
3146173TUNIS
Solar/Wind Harmer
-0.016
3156021HOLLOMANSOL
Solar/Wind Harmer
2.177
316463AE2-346 GEN
Solar/Wind Harmer
0.261
316140AB2-099
Solar/Wind Harmer
0.109
962331AG1-082 GEN
Solar/Wind Harmer
2.017
966621AG1-532 GEN
Solar/Wind Harmer
0.326
3146263WOODLND
Solar/Wind Harmer
-0.016
313506AB2-031 GEN
Solar/Wind Harmer
1.286
3145963POPLR C
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
972255AH1-712 GEN
Adder
71.607
3144293JTRSVLE
Adder
0.442
3151861LOWMORA
Adder
1.28
227287AC2-120 GEN
Solar/Wind Helper
1.262
226910AB2-157 C
Solar/Wind Helper
0.049
223402AF1-300 C
Solar/Wind Helper
0.748
233918AB1-142 GEN
Solar/Wind Helper
0.685
233982AB2-133 GEN
Solar/Wind Helper
0.488
233994AC2-023 GEN
Solar/Wind Helper
1.306
233996TM1833_GEN
Solar/Wind Helper
0.355
233997TMININ_4.2
Solar/Wind Helper
0.355
233940AF2-379 C
Solar/Wind Helper
0.084
234015AF2-250 C
Solar/Wind Helper
0.051
232406W1-004 FULL
Solar/Wind Helper
0.689
233952AC2-187 GEN
Solar/Wind Helper
0.315
233971AC1-093 C
Solar/Wind Helper
0.485
230430AE1-229_GEN
Solar/Wind Helper
4.448
230415AB2-049 C
Solar/Wind Helper
0.04
228729W2-030 C
Solar/Wind Helper
0.145
219623KINSLEYBEA C
Solar/Wind Helper
0.003
219766PARADISE C
Solar/Wind Helper
0.072
219912AD2-042 GEN
Solar/Wind Helper
0.196
219291REEVESSOUT C
Solar/Wind Helper
0.015
219236SOUTHERNHQ C
Solar/Wind Helper
0.007
219906AC1-017 C
Solar/Wind Helper
0.054
219348LDSOLAR C
Solar/Wind Helper
0.149
959561AF2-247 GEN
Solar/Wind Helper
0.027
20716028EGP_W2-019
Solar/Wind Helper
0.024
20720828JCB_W4-025
Solar/Wind Helper
0.082
20715028HAN_X4-015
Solar/Wind Helper
0.074
219276PARKLANDSO C
Solar/Wind Helper
0.115
20714528FRN_Y2-051
Solar/Wind Helper
0.073
20720528MAN_W1-024
Solar/Wind Helper
0.036
219612MATRIX C
Solar/Wind Helper
0.03
218438BLK ROCK C
Solar/Wind Helper
0.035
219908AB1-139 C
Solar/Wind Helper
0.093
219919AE1-041 FULL
Solar/Wind Helper
0.005
219249CENTRALDIV C
Solar/Wind Helper
0.013
20673728F2S_V4-070
Solar/Wind Helper
0.037
217211CAMDEN ST C
Solar/Wind Helper
0.006
217169METRODIV C
Solar/Wind Helper
0.005
20676728BRNX1-095
Solar/Wind Helper
0.037
207510AF2-138 C
Solar/Wind Helper
0.1
20674628WNG_W3-110
Solar/Wind Helper
0.11
963161AG1-165 GEN
Solar/Wind Helper
0.512
963071AG1-156 GEN
Solar/Wind Helper
1.658
209027LOR2_Q27
Solar/Wind Helper
1.175
961331AF2-424 GEN
Solar/Wind Helper
0.499
961421AF2-433 GEN
Solar/Wind Helper
0.497
957921AF2-086 GEN
Solar/Wind Helper
0.492
946691AF1-333 GEN
Solar/Wind Helper
0.489
946741AF1-338 GEN
Solar/Wind Helper
0.489
209067AE2-060 GEN
Solar/Wind Helper
0.08
20675128HRM_W1-127
Solar/Wind Helper
0.036
960921AF2-383 GEN
Solar/Wind Helper
0.211
209116AE2-175 GEN
Solar/Wind Helper
2.147
205932AD2-116_GEN
Solar/Wind Helper
0.581
205956AE1-196_GEN
Solar/Wind Helper
0.581
205943AE1-185 GEN
Solar/Wind Helper
0.575
961261AF2-417 GEN
Solar/Wind Helper
0.512
959431AF2-234 GEN
Solar/Wind Helper
0.976
964051AG1-259 GEN
Solar/Wind Helper
0.073
964061AG1-260 GEN
Solar/Wind Helper
0.073
959421AF2-233 GEN
Solar/Wind Helper
0.488
316159AE1-175 C
Solar/Wind Harmer
0.478
971317AH1-138 GEN
Solar/Wind Harmer
2.221
3147666LOUISA
Solar/Wind Harmer
-0.071
3143226MDLTHAN
Solar/Wind Harmer
-0.018
316192AB2-158 GEN
Solar/Wind Harmer
2.108
970129AG2-093 GEN
Solar/Wind Harmer
4.032
316458AB2-190 GEN2
Solar/Wind Harmer
1.788
315671AE2-027_GEN
Solar/Wind Harmer
13.243
3138126ROCKLANDING
Solar/Wind Harmer
0.054
971069AG2-661 GEN
Solar/Wind Harmer
2.791
971647AH1-324 GEN
Solar/Wind Harmer
8.789
316254AC1-120 GEN1
Solar/Wind Harmer
1.418
961611AG1-000B GEN
Solar/Wind Harmer
8.659
3151171GRAVELC
Adder
1.658
3145336SMITFLD
Solar/Wind Harmer
-0.069
316294AC1-161 GEN
Solar/Wind Harmer
5.624
970659AG2-427 GEN
Solar/Wind Harmer
9.221
316381AD1-082 GEN
Solar/Wind Harmer
1.591
316375AC2-012 GEN
Solar/Wind Harmer
5.987
970661AG2-428 GEN
Solar/Wind Harmer
18.39
3150981CHESPKA
Adder
1.923
944591AF1-124 GEN
Solar/Wind Harmer
78.926
316072AD1-144
Solar/Wind Harmer
0.349
316388AE2-253 GEN
Solar/Wind Harmer
1.161
3146456SLIGO L269
Solar/Wind Harmer
-0.017
316246AF1-032 C
Solar/Wind Harmer
0.348
316093AE2-104_GEN
Solar/Wind Harmer
4.984
939411AE1-173 GEN
Solar/Wind Harmer
85.695
316006AB2-029 C
Solar/Wind Harmer
0.983
971685AH1-345 GEN
Solar/Wind Harmer
1.499
940641AE2-051 GEN
Solar/Wind Harmer
16.029
3150281M RUN A
Adder
20.58
3150221REMNGT2
Adder
19.137
3150211REMNGT1
Adder
19.01
972201AH1-685 GEN
Adder
3.302
3151751LOISA D
Adder
9.812
3146516WINFALL
Solar/Wind Harmer
-0.055
3146516WINFALL
Solar/Wind Harmer
-0.017
315683AE1-153 C
Solar/Wind Harmer
15.812
3143336POWHATN
Solar/Wind Harmer
2.008
315800Z1-036_GEN1
Solar/Wind Harmer
4.161
3130156CHOWAN
Solar/Wind Harmer
-0.017
316336AC2-165 C
Solar/Wind Harmer
2.903
3145663CRESWEL
Solar/Wind Harmer
-0.046
971163AH1-040 GEN
Solar/Wind Harmer
15.508
3146206CASHIE
Solar/Wind Harmer
-0.016
971547AH1-271 GEN
Solar/Wind Harmer
4.071
316023GEN1_S
Solar/Wind Harmer
1.097
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
0.482
970919AG2-571 GEN
Solar/Wind Harmer
5.126
3146173TUNIS
Solar/Wind Harmer
-0.016
970087AG2-069 GEN
Solar/Wind Harmer
15.156
970937AG2-583 GEN
Solar/Wind Harmer
11.617
3145683EARLEYS
Solar/Wind Harmer
-0.016
960081AF2-299 GEN
Solar/Wind Harmer
1.81
3146263WOODLND
Solar/Wind Harmer
-0.016
957481AF2-042 GEN
Solar/Wind Harmer
49.991
3145963POPLR C
Solar/Wind Harmer
-0.016
3147043LAWRENC
Adder
1.279
972277AH1-723 GEN
Adder
83.443
3144293JTRSVLE
Adder
0.442
223401AF1-299 GEN
Solar/Wind Helper
0.748
233930AB2-032 GEN
Solar/Wind Helper
0.519
233915AB1-141 GEN
Solar/Wind Helper
0.685
232422X3-066 FULL
Solar/Wind Helper
0.156
233964AF2-378 GEN
Solar/Wind Helper
0.057
232426Y1-080 FULL
Solar/Wind Helper
0.053
232428Y3-058 C
Solar/Wind Helper
0.459
233998TM1NIN_3.36
Solar/Wind Helper
0.355
232404W1-003 C
Solar/Wind Helper
0.689
233954AC2-188 GEN
Solar/Wind Helper
0.315
233950AC2-186 GEN
Solar/Wind Helper
0.158
232434Z2-077 GEN
Solar/Wind Helper
0.172
233972AC1-094 C
Solar/Wind Helper
0.41
230511AF1-262
Solar/Wind Helper
0.019
230434AG1-499 GEN
Solar/Wind Helper
0.303
228728W1-130C
Solar/Wind Helper
0.071
219258KINSLEYDEP C
Solar/Wind Helper
0.101
219904AC1-010 C
Solar/Wind Helper
0.079
219907AC1-030 C
Solar/Wind Helper
0.044
218660EHAMPSOLAR C
Solar/Wind Helper
0.043
219686LUMSOLAR_N C
Solar/Wind Helper
0.052
219304NAMERICA C
Solar/Wind Helper
0.171
20720728JCB_W1-129
Solar/Wind Helper
0.074
207445AB1-138_GEN
Solar/Wind Helper
0.134
963711AG1-223 GEN
Solar/Wind Helper
0.082
20714828MDF_W3-079
Solar/Wind Helper
0.167
219680HOPEWELLV C1
Solar/Wind Helper
0.004
207454AA2-184 E
Solar/Wind Helper
0.395
20715228NPK_W1-113
Solar/Wind Helper
0.1
20742028HF_AC1-207
Solar/Wind Helper
0.179
218428ETC SOLAR C
Solar/Wind Helper
0.006
217213AMBOY SO C
Solar/Wind Helper
0.036
207528AF2-192 GEN
Solar/Wind Helper
0.096
20673628F1S_V4-069
Solar/Wind Helper
0.037
20675428EAM_W2-061
Solar/Wind Helper
0.02
20676428JCR_X2-075
Solar/Wind Helper
0.085
217209CENTRL HS C
Solar/Wind Helper
0.01
217208PARK ELE C
Solar/Wind Helper
0.006
205941AD2-115 GEN
Solar/Wind Helper
0.613
20674328GAR_V4-001
Solar/Wind Helper
0.028
207439AE1-081 C O1
Solar/Wind Helper
0.023
20675828AU_W4-064
Solar/Wind Helper
0.036
207437AD2-070 GEN
Solar/Wind Helper
0.169
207518AF1-320_GEN
Solar/Wind Helper
1.931
20671928W4-073
Solar/Wind Helper
0.11
961301AF2-421 GEN
Solar/Wind Helper
0.512
963151AG1-164 GEN
Solar/Wind Helper
0.512
212266LOR1
Solar/Wind Helper
0.054
961341AF2-425 GEN
Solar/Wind Helper
0.499
212507AE2-042_GEN
Solar/Wind Helper
1.74
946731AF1-337 GEN
Solar/Wind Helper
0.489
209071AE2-133 GEN
Solar/Wind Helper
0.088
966131AG1-482 GEN
Solar/Wind Helper
0.075
971795AH1-408 GEN
Solar/Wind Harmer
10.192
3145893MURPHYS
Solar/Wind Harmer
-0.029
3146173TUNIS
Solar/Wind Harmer
-0.016
3146173TUNIS
Solar/Wind Harmer
-0.016
316181AB2-040 GEN
Solar/Wind Harmer
2.231
970099AG2-077 GEN
Solar/Wind Harmer
19.996
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3144293JTRSVLE
Adder
0.442
3144293JTRSVLE
Adder
0.372
226929AD2-058 GEN
Solar/Wind Helper
0.393
208835TUHI V3-051
Solar/Wind Helper
0.036
208835TUHI V3-051
Solar/Wind Helper
0.036
233933AB2-153 GEN
Solar/Wind Helper
0.317
233944AB2-135 GEN
Solar/Wind Helper
0.802
232424Y1-079 C
Solar/Wind Helper
0.158
233987AB2-037 GEN
Solar/Wind Helper
3.185
234036AF2-325 C
Solar/Wind Helper
0.057
233946AB2-136 GEN
Solar/Wind Helper
0.772
233901CHERRYDALE C
Solar/Wind Helper
0.316
232408W1-005 C
Solar/Wind Helper
0.689
232410W1-006 C
Solar/Wind Helper
0.689
233939AC1-091 C
Solar/Wind Helper
0.474
233970AC1-092 C
Solar/Wind Helper
0.474
230433AD2-135 GEN
Solar/Wind Helper
0.022
230407AD2-065 C
Solar/Wind Helper
0.053
219921AF1-264
Solar/Wind Helper
0.067
219615MILLCREEK C
Solar/Wind Helper
0.035
963401AG1-189 GEN
Solar/Wind Helper
0.072
963391AG1-188 GEN
Solar/Wind Helper
0.106
20714928UPF_X1-085
Solar/Wind Helper
0.007
20720628TIN_W1-124
Solar/Wind Helper
0.242
20716928W4-060COL
Solar/Wind Helper
0.065
218440SUMMTASSOC C
Solar/Wind Helper
0.021
20673828FLE_V3-070
Solar/Wind Helper
0.114
207442AE1-156 GEN
Solar/Wind Helper
0.41
20676128MHD_W3-029
Solar/Wind Helper
0.121
20671828STAW2-080
Solar/Wind Helper
0.033
217081WEATEXAS C
Solar/Wind Helper
0.016
217202FBANKSOLAR C
Solar/Wind Helper
0.004
217201HACKENSOLA C
Solar/Wind Helper
0.004
217206BARNGR HS C
Solar/Wind Helper
0.008
217204WCALDSOLAR C
Solar/Wind Helper
0.004
20676228FRD_X1-012
Solar/Wind Helper
0.113
207471AF2-354 C
Solar/Wind Helper
0.208
20674928WA_W3-044
Solar/Wind Helper
0.121
964851AG1-348 GEN
Solar/Wind Helper
0.099
20674128FR_U2-059
Solar/Wind Helper
0.005
966111AG1-480 GEN
Solar/Wind Helper
0.054
211065PSPA IPP
Solar/Wind Helper
0.182
211065PSPA IPP
Solar/Wind Helper
0.182
208972BECR K09
Solar/Wind Helper
0.376
961431AF2-434 GEN
Solar/Wind Helper
0.497
209029WAYMART-WD
Solar/Wind Helper
0.936
209054AE2-059 GEN
Solar/Wind Helper
0.089
946751AF1-339 GEN
Solar/Wind Helper
0.489
209137AF2-361 C
Solar/Wind Helper
1.35
NYPJM->LTFIMP_NY
CLTF
5.379
LAGNLTFEXP_LAGN->PJM
CLTF
13.612
LGEELTFEXP_LGEE->PJM
CLTF
4.06
WECLTFEXP_WEC->PJM
CLTF
2.182
AG2-052LTFEXP_AG2-052->PJM
LTF
0.13
AH1-155LTFEXP_AH1-155->PJM
LTF
0.195
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.468
TVALTFEXP_TVA->PJM
CLTF
6.85
CPLELTFEXP_CPLE->PJM
CLTF
10.068
CBM West 2LTFEXP_CBM-W2->PJM
CBM
85.372
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.121
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.087
MECLTFEXP_MEC->PJM
CLTF
9.963
SIGELTFEXP_SIGE->PJM
CLTF
0.313

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o AP_P2-3_PE-500-019F_SRT-SL


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-019F_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.21 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3322.42
MW Contribution:7.29
Bus #Bus NameTypeMW Contribution
970053AG2-049 GEN
50/50
2.783
3150411LDYSMT5
50/50
22.239
3150381LDYSMT2
50/50
21.283
972213AH1-691 GEN
50/50
3.6
972215AH1-692 GEN
50/50
3.6
972223AH1-696 GEN
50/50
15.409
3150151POSSMC1
50/50
1.951
3141346CRANES
50/50
0.214
3150011OMF A
50/50
0.314
3140676OCCOQUN
50/50
0.417
972197AH1-683 GEN
50/50
3.462
972219AH1-694 GEN
50/50
2.493
957971AF2-091 GEN
Solar/Wind Harmer
1.709
972135AH1-637 GEN
Solar/Wind Harmer
1.695
966881AG1-559 GEN
Solar/Wind Harmer
0.173
316337AD2-073 GEN
Solar/Wind Harmer
0.437
3150351NORNECKC2
Adder
1.419
964211AG1-282 GEN
Solar/Wind Harmer
0.479
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.928
961951AG1-038 GEN
Solar/Wind Harmer
2.073
3138133OCRAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.812
3141843SHACKLE
Adder
0.701
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3143096IRON208
Adder
0.567
316045AC1-158 PL2
Solar/Wind Harmer
4.767
944631AF1-128 GEN
Adder
64.359
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.62
316159AE1-175 C
Solar/Wind Harmer
0.404
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.879
3143226MDLTHAN
Solar/Wind Harmer
-0.015
970129AG2-093 GEN
Solar/Wind Harmer
3.407
316458AB2-190 GEN2
Solar/Wind Harmer
1.511
315671AE2-027_GEN
Solar/Wind Harmer
11.189
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971069AG2-661 GEN
Solar/Wind Harmer
2.358
3147666LOUISA
Solar/Wind Harmer
-0.059
971647AH1-324 GEN
Solar/Wind Harmer
7.424
961611AG1-000B GEN
Solar/Wind Harmer
7.313
316192AB2-158 GEN
Solar/Wind Harmer
1.761
3151171GRAVELC
Adder
1.4
3145336SMITFLD
Solar/Wind Harmer
-0.059
316294AC1-161 GEN
Solar/Wind Harmer
4.745
970659AG2-427 GEN
Solar/Wind Harmer
7.779
316381AD1-082 GEN
Solar/Wind Harmer
1.342
970661AG2-428 GEN
Solar/Wind Harmer
15.511
316375AC2-012 GEN
Solar/Wind Harmer
5.05
3150981CHESPKA
Adder
1.622
944591AF1-124 GEN
Solar/Wind Harmer
66.562
316072AD1-144
Solar/Wind Harmer
0.295
316254AC1-120 GEN1
Solar/Wind Harmer
1.174
316388AE2-253 GEN
Solar/Wind Harmer
0.979
3146456SLIGO L269
Solar/Wind Harmer
-0.014
316246AF1-032 C
Solar/Wind Harmer
0.293
316093AE2-104_GEN
Solar/Wind Harmer
4.2
939411AE1-173 GEN
Solar/Wind Harmer
72.191
940641AE2-051 GEN
Solar/Wind Harmer
13.499
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
3143336POWHATN
Solar/Wind Harmer
1.684
315800Z1-036_GEN1
Solar/Wind Harmer
3.503
3151751LOISA D
Adder
8.139
3130156CHOWAN
Solar/Wind Harmer
-0.014
316006AB2-029 C
Solar/Wind Harmer
0.804
971685AH1-345 GEN
Solar/Wind Harmer
1.226
315683AE1-153 C
Solar/Wind Harmer
13.032
316336AC2-165 C
Solar/Wind Harmer
2.431
3150281M RUN A
Adder
16.797
3145663CRESWEL
Solar/Wind Harmer
-0.039
971163AH1-040 GEN
Solar/Wind Harmer
13.037
3150221REMNGT2
Adder
15.611
3150211REMNGT1
Adder
15.507
972201AH1-685 GEN
Adder
2.693
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.418
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.405
316023GEN1_S
Solar/Wind Harmer
0.92
970919AG2-571 GEN
Solar/Wind Harmer
4.3
3146173TUNIS
Solar/Wind Harmer
-0.014
970087AG2-069 GEN
Solar/Wind Harmer
12.711
3145683EARLEYS
Solar/Wind Harmer
-0.013
960081AF2-299 GEN
Solar/Wind Harmer
1.517
970937AG2-583 GEN
Solar/Wind Harmer
9.686
3146263WOODLND
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
41.862
3145963POPLR C
Solar/Wind Harmer
-0.013
3145823KELFORD
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.795
3147043LAWRENC
Adder
1.071
972277AH1-723 GEN
Adder
69.269
3144293JTRSVLE
Adder
0.368
223401AF1-299 GEN
Solar/Wind Helper
0.708
233930AB2-032 GEN
Solar/Wind Helper
0.373
233915AB1-141 GEN
Solar/Wind Helper
0.492
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.328
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.493
233954AC2-188 GEN
Solar/Wind Helper
0.226
963051AG1-154 GEN
50/50
2.769
3141426STAFORD
Solar/Wind Harmer
-0.004
944491AF1-114 GEN
Solar/Wind Harmer
5.027
316223AC1-118
Solar/Wind Harmer
0.446
972189AH1-679 GEN
Adder
2.388
3141813NORNECK
Solar/Wind Harmer
-0.016
962981AG1-147 GEN
Solar/Wind Harmer
6.86
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.015
316312AB1-027
Solar/Wind Harmer
0.52
957601AF2-054 GEN
Solar/Wind Harmer
0.461
316059AD1-063 C
Solar/Wind Harmer
0.349
3141873WAN 176
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.318
315662AE1-191 GEN
Solar/Wind Harmer
1.858
315666AE1-190 GEN
Solar/Wind Harmer
0.465
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
971167AH1-042 GEN
Solar/Wind Harmer
14.738
315976AC1-164 GENA
Solar/Wind Harmer
16.157
316169AC1-164_GENC
Solar/Wind Harmer
13.958
315975AC1-164 GENB
Solar/Wind Harmer
0.478
957831AF2-077 GEN
Solar/Wind Harmer
0.456
3138283WHITEMARSH
Solar/Wind Harmer
0.023
971285AH1-108 GEN
Adder
1.014
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971281AH1-106 GEN
Solar/Wind Harmer
2.447
971283AH1-107 GEN
Solar/Wind Harmer
2.447
316164AC1-076 GEN
Solar/Wind Harmer
1.264
316132AB2-190 GEN1
Solar/Wind Harmer
1.511
316369SG1_INVT
Solar/Wind Harmer
2.658
972265AH1-717 GEN
Adder
10.215
3151201GRAVEL4
Adder
9.576
3151191GRAVEL3
Adder
9.455
3151211GRAVEL5
Adder
9.455
971445AH1-216 GEN
Solar/Wind Harmer
9.107
3143316POE
Solar/Wind Harmer
-0.058
3151081ELIZAR1
Adder
11.906
3151091ELIZAR2
Adder
11.7
3152611GOSPORTB
Adder
1.654
3152621GOSPORTC
Adder
1.404
3152601GOSPORTA
Adder
1.295
315833AF1-017_GEN
Solar/Wind Harmer
2.757
316349AD2-085 GEN
Solar/Wind Harmer
1.291
316311AC2-079 GEN
Solar/Wind Harmer
7.321
957871AF2-081 GEN
Solar/Wind Harmer
7.253
316305AF2-043 C
Solar/Wind Harmer
0.437
319010AE1-072 C
Solar/Wind Harmer
2.929
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315835AF2-110_GEN
Solar/Wind Harmer
1.806
313526AB2-022
Solar/Wind Harmer
0.389
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3150101POSSM6S
50/50
2.213
3150081POSSM6A
50/50
1.448
3150151POSSMC1
50/50
1.951
3150151POSSMC1
50/50
1.951
3150331BIRCHWDA
50/50
29.482
3150021OMF B
50/50
0.314
3141316ARNOLDS
50/50
0.405
3150401LDYSMT4
50/50
22.17
3150371LDYSMT1
50/50
21.422
970497AG2-320 GEN
50/50
14.485
966881AG1-559 GEN
Solar/Wind Harmer
0.505
970737AG2-469 GEN
Solar/Wind Harmer
8.391
3141906WESTMOR
Solar/Wind Harmer
-0.007
971781AH1-399 GEN
Solar/Wind Harmer
1.014
3150351NORNECKC2
Adder
1.443
316404AE1-155 C
Solar/Wind Harmer
3.054
316484AD2-074 GEN
Solar/Wind Harmer
3.962
970009AG2-005 GEN
Solar/Wind Harmer
1.967
962971AG1-146 GEN
Solar/Wind Harmer
2.94
316473AC1-191 GEN
Solar/Wind Harmer
1.687
316156AD2-030 GEN
Solar/Wind Harmer
0.412
3141873WAN 176
Solar/Wind Harmer
1.83
3142416OLDCHRC
Solar/Wind Harmer
1.556
3141766HARMONY
Solar/Wind Harmer
1.373
316280AD1-041 GEN
Solar/Wind Harmer
1.161
316203AE2-005 GEN
Solar/Wind Harmer
6.497
3141843SHACKLE
Adder
0.701
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
970293AG2-193 GEN
Solar/Wind Harmer
1.915
3142946ENON
Solar/Wind Harmer
-0.005
3143096IRON208
Adder
0.567
3143096IRON208
Adder
0.556
316044AC1-158 PL1
Solar/Wind Harmer
1.49
316450AC1-158 RIC
Solar/Wind Harmer
0.397
3150861SPRUNCD
Adder
0.62
316382AG1-145 C
Solar/Wind Harmer
0.454
970133AG2-095 GEN
Solar/Wind Harmer
1.687
970129AG2-093 GEN
Solar/Wind Harmer
8.412
3150921YORKTN3
Adder
3.34
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
12.908
965281AG1-393 GEN
Solar/Wind Harmer
1.861
3147666LOUISA
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
0.447
961611AG1-000B GEN
Solar/Wind Harmer
3.12
3151221GRAVEL6
Adder
9.565
3151171GRAVELC
Adder
1.84
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.189
315773AC2-141 GEN
Solar/Wind Harmer
6.136
970659AG2-427 GEN
Solar/Wind Harmer
1.379
3144536CHRHLND
Solar/Wind Harmer
-0.002
316083AB2-161 GEN
Solar/Wind Harmer
2.375
970661AG2-428 GEN
Solar/Wind Harmer
2.749
3151101ELIZAR3
Adder
12.059
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
66.324
944601AF1-125 GEN
Solar/Wind Harmer
65.289
316170AC1-121 GEN2
Solar/Wind Harmer
0.391
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.766
316320Y1-086
Solar/Wind Harmer
0.844
3132273ORANGE
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3145273HOLLAND
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Harmer
0.383
316258AE1-075 C
Solar/Wind Harmer
0.345
316405AF2-144 C
Solar/Wind Harmer
0.364
3143336POWHATN
Solar/Wind Harmer
1.431
3151761LOISA E
Adder
16.592
3146376EDENTON
Solar/Wind Harmer
-0.014
972183AH1-676 GEN
Adder
133.629
3150301M RUN C
Adder
16.786
3150291M RUN B
Adder
16.662
315614AA2-178 GEN
Solar/Wind Harmer
1.5
3150231REMNGT3
Adder
16.854
3150241REMNGT4
Adder
15.715
972199AH1-684 GEN
Adder
2.383
972217AH1-693 GEN
Adder
2.072
971157AH1-035 GEN
Solar/Wind Harmer
1.722
3156081AA2-088 GEN
Solar/Wind Harmer
4.464
315737AD1-076 GEN
Solar/Wind Harmer
2.613
3146206CASHIE
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
316365GEN2_N
Solar/Wind Harmer
0.92
957521AF2-046 GEN
Solar/Wind Harmer
10.733
961681AG1-008 GEN
Solar/Wind Harmer
10.733
970917AG2-570 GEN
Solar/Wind Harmer
33.966
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.827
316463AE2-346 GEN
Solar/Wind Harmer
0.219
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
1.693
966621AG1-532 GEN
Solar/Wind Harmer
0.274
3141196NOKESVL
Solar/Wind Harmer
-0.054
3146263WOODLND
Solar/Wind Harmer
-0.013
313506AB2-031 GEN
Solar/Wind Harmer
1.078
3145963POPLR C
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316317KELFORD C
Solar/Wind Harmer
0.63
3145823KELFORD
Solar/Wind Harmer
-0.013
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
233972AC1-094 C
Solar/Wind Helper
0.293
316321Z2-027
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
3146396TANGLEW
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.383
315611Z1-036_GEN2
Solar/Wind Harmer
3.503
315814AE2-033 C
Solar/Wind Harmer
13.2
941031AE2-094 GEN
Solar/Wind Harmer
26.435
944011AF1-069 GEN
Solar/Wind Harmer
8.283
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970673AG2-436 GEN
Solar/Wind Harmer
29.368
970673AG2-436 GEN
Solar/Wind Harmer
14.87
971967AH1-528 GEN
Solar/Wind Harmer
26.154
315816AE2-034 GEN
Solar/Wind Harmer
1.125
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
2.781
315733AD1-074 GEN2
Solar/Wind Harmer
2.781
315735AD1-075 GEN1
Solar/Wind Harmer
1.391
965291AG1-394 GEN
Solar/Wind Harmer
1.218
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.981
316318V4-068
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.474
970581AG2-369 GEN
Solar/Wind Harmer
7.288
3145513AHOSKIE
Solar/Wind Harmer
0.118
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145513AHOSKIE
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.302
315607AA1-063A GEN
Solar/Wind Harmer
1.361
316087AB2-174 GEN
Solar/Wind Harmer
1.916
972193AH1-681 GEN
Adder
2.656
972205AH1-687 GEN
Adder
4.959
233935AB2-179 C
Solar/Wind Helper
1.252
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.931
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.814
960921AF2-383 GEN
Solar/Wind Helper
0.173
315652AC1-086 GEN
Solar/Wind Harmer
5.139
3150091POSSM6B
50/50
1.448
3150071POSSM 5
50/50
89.158
3150181POSSMC2
50/50
1.967
3150181POSSMC2
50/50
1.951
3150181POSSMC2
50/50
1.951
957191AF2-013 GEN
50/50
14.124
3150391LDYSMT3
50/50
22.128
972195AH1-682 GEN
50/50
2.908
315673AE1-157 GEN
Solar/Wind Harmer
12.798
957411AF2-035 GEN
Solar/Wind Harmer
7.564
970317AG2-208 GEN
Solar/Wind Harmer
7.354
316468AD1-105 GEN
Solar/Wind Harmer
1.833
316077AC2-138 C
Solar/Wind Harmer
0.337
3150341NORNECKC1
Adder
1.491
3150341NORNECKC1
Adder
1.479
958261AF2-120 GEN
Solar/Wind Harmer
6.135
316487AF1-042 GEN
Solar/Wind Harmer
2.073
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.439
316441AF1-014 GEN
Solar/Wind Harmer
1.039
316075AC2-137 C
Solar/Wind Harmer
0.413
3150691DARBY 3
Adder
9.809
3150701DARBY 4
Adder
9.787
3150681DARBY 2
Adder
9.775
3150671DARBY 1
Adder
9.764
3142366NRTHEST
Adder
0.445
3142946ENON
Solar/Wind Harmer
-0.002
316447AC1-158 HLD
Solar/Wind Harmer
3.277
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.531
971223AH1-071 GEN
Solar/Wind Harmer
1.869
316240AF1-291 C
Solar/Wind Harmer
0.45
316033AB2-134 GEN
Solar/Wind Harmer
4.797
315697AD1-025 GEN
Solar/Wind Harmer
3.009
316236AE1-162_GEN
Solar/Wind Harmer
0.443
970657AG2-426 GEN
Solar/Wind Harmer
4.568
970657AG2-426 GEN
Solar/Wind Harmer
0.955
316036AC1-147 C
Solar/Wind Harmer
0.394
3150991CHESPKB
Adder
1.36
3150991CHESPKB
Adder
1.328
316316AC1-027 C
Solar/Wind Harmer
0.447
3142956BIRDNECK
Solar/Wind Harmer
0.782
316185AD1-033 GEN
Solar/Wind Harmer
1.536
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.979
316018AA1-139 ULT2
Solar/Wind Harmer
1.243
316017AA1-139 ULT1
Solar/Wind Harmer
1.174
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3146456SLIGO L269
Solar/Wind Harmer
1.711
3130086AYDLETT
Solar/Wind Harmer
-0.058
315651AD1-115 GEN
Solar/Wind Harmer
6.347
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.595
316433W1029_GEN2
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3144356SAPONY
Solar/Wind Harmer
0.495
315742AE1-103 GEN
Solar/Wind Harmer
1.477
966001AG1-469 GEN
Solar/Wind Harmer
0.267
3151731LOISA B
Adder
8.139
3151721LOISA A
Adder
8.097
3146376EDENTON
Solar/Wind Harmer
0.418
3146376EDENTON
Solar/Wind Harmer
0.418
972185AH1-677 GEN
Adder
6.952
972187AH1-678 GEN
Adder
3.508
970933AG2-581 GEN
Solar/Wind Harmer
12.91
316065AD1-022 GEN
Solar/Wind Harmer
6.85
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.87
970099AG2-077 GEN
Solar/Wind Harmer
16.745
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.31
226929AD2-058 GEN
Solar/Wind Helper
0.403
208835TUHI V3-051
Solar/Wind Helper
0.031
208835TUHI V3-051
Solar/Wind Helper
0.031
233933AB2-153 GEN
Solar/Wind Helper
0.227
233944AB2-135 GEN
Solar/Wind Helper
0.575
232424Y1-079 C
Solar/Wind Helper
0.113
233987AB2-037 GEN
Solar/Wind Helper
2.278
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.552
233901CHERRYDALE C
Solar/Wind Helper
0.226
232408W1-005 C
Solar/Wind Helper
0.493
232410W1-006 C
Solar/Wind Helper
0.493
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
972255AH1-712 GEN
Adder
59.443
3144293JTRSVLE
Adder
0.368
227287AC2-120 GEN
Solar/Wind Helper
1.292
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.708
233982AB2-133 GEN
Solar/Wind Helper
0.35
233918AB1-142 GEN
Solar/Wind Helper
0.492
233994AC2-023 GEN
Solar/Wind Helper
0.934
233996TM1833_GEN
Solar/Wind Helper
0.254
233997TMININ_4.2
Solar/Wind Helper
0.254
233940AF2-379 C
Solar/Wind Helper
0.06
232406W1-004 FULL
Solar/Wind Helper
0.493
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.226
233971AC1-093 C
Solar/Wind Helper
0.346
NYPJM->LTFIMP_NY
CLTF
3.821
LAGNLTFEXP_LAGN->PJM
CLTF
10.958
LGEELTFEXP_LGEE->PJM
CLTF
3.225
WECLTFEXP_WEC->PJM
CLTF
1.731
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.907
TVALTFEXP_TVA->PJM
CLTF
5.516
CPLELTFEXP_CPLE->PJM
CLTF
8.326
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.371
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.289
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.158
MECLTFEXP_MEC->PJM
CLTF
7.931
SIGELTFEXP_SIGE->PJM
CLTF
0.249

Details for 8POSSUM-BURCHES 500.0 kV Ckt 1 line l/o PEPCO_P4_PP41_SRT-A


Base Case Flowgate

Area:DVP/PJM
Facility Description:
8POSSUM-BURCHES 500.0 kV Ckt 1 line
Contingency Name:
PEPCO_P4_PP41_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.72 %
Rating:3099.0 MVA
Rating Type:B
MVA to Mitigate:3214.41
MW Contribution:7.29
Bus #Bus NameTypeMW Contribution
972223AH1-696 GEN
50/50
15.444
3150151POSSMC1
50/50
1.955
3141346CRANES
50/50
0.215
3150011OMF A
50/50
0.315
3140676OCCOQUN
50/50
0.417
972197AH1-683 GEN
50/50
3.465
972219AH1-694 GEN
50/50
2.495
957971AF2-091 GEN
Solar/Wind Harmer
1.711
972135AH1-637 GEN
Solar/Wind Harmer
1.697
966881AG1-559 GEN
Solar/Wind Harmer
0.173
316337AD2-073 GEN
Solar/Wind Harmer
0.437
3150351NORNECKC2
Adder
1.42
964211AG1-282 GEN
Solar/Wind Harmer
0.479
3141726DUNNSVL
Solar/Wind Harmer
-0.063
962861AG1-135 GEN
Solar/Wind Harmer
5.93
961951AG1-038 GEN
Solar/Wind Harmer
2.074
3138133OCRAN
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
-0.04
3142416OLDCHRC
Solar/Wind Harmer
-0.015
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.812
3141843SHACKLE
Adder
0.701
3142433PROV 92
Solar/Wind Harmer
-0.061
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
3143096IRON208
Adder
0.567
970053AG2-049 GEN
50/50
2.789
3150411LDYSMT5
50/50
22.262
3150381LDYSMT2
50/50
21.306
972213AH1-691 GEN
50/50
3.604
972215AH1-692 GEN
50/50
3.604
963051AG1-154 GEN
50/50
2.772
3141426STAFORD
Solar/Wind Harmer
-0.004
944491AF1-114 GEN
Solar/Wind Harmer
5.033
316223AC1-118
Solar/Wind Harmer
0.446
972189AH1-679 GEN
Adder
2.389
3141813NORNECK
Solar/Wind Harmer
-0.016
962981AG1-147 GEN
Solar/Wind Harmer
6.863
3141783LANCAST
Solar/Wind Harmer
-0.009
3141783LANCAST
Solar/Wind Harmer
-0.006
3138133OCRAN
Solar/Wind Harmer
-0.005
3141913WHIT STONE
Solar/Wind Harmer
-0.015
957601AF2-054 GEN
Solar/Wind Harmer
0.462
3141873WAN 176
Solar/Wind Harmer
-0.003
316314AB2-024 C
Solar/Wind Harmer
1.319
316312AB1-027
Solar/Wind Harmer
0.52
316059AD1-063 C
Solar/Wind Harmer
0.349
315662AE1-191 GEN
Solar/Wind Harmer
1.859
315666AE1-190 GEN
Solar/Wind Harmer
0.465
3143873LANEXA
Solar/Wind Harmer
-0.009
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
971167AH1-042 GEN
Solar/Wind Harmer
14.742
315976AC1-164 GENA
Solar/Wind Harmer
16.161
316169AC1-164_GENC
Solar/Wind Harmer
13.961
315975AC1-164 GENB
Solar/Wind Harmer
0.478
957831AF2-077 GEN
Solar/Wind Harmer
0.456
3138283WHITEMARSH
Solar/Wind Harmer
0.023
971285AH1-108 GEN
Adder
1.015
316233AE1-074 FULL
Solar/Wind Harmer
0.405
971281AH1-106 GEN
Solar/Wind Harmer
2.447
971283AH1-107 GEN
Solar/Wind Harmer
2.447
316164AC1-076 GEN
Solar/Wind Harmer
1.264
316132AB2-190 GEN1
Solar/Wind Harmer
1.511
316369SG1_INVT
Solar/Wind Harmer
2.658
972265AH1-717 GEN
Adder
10.216
3151201GRAVEL4
Adder
9.577
3151191GRAVEL3
Adder
9.455
3151211GRAVEL5
Adder
9.455
971445AH1-216 GEN
Solar/Wind Harmer
9.107
3143316POE
Solar/Wind Harmer
-0.058
3151081ELIZAR1
Adder
11.906
3151091ELIZAR2
Adder
11.699
3152611GOSPORTB
Adder
1.654
3152621GOSPORTC
Adder
1.404
3152601GOSPORTA
Adder
1.295
315833AF1-017_GEN
Solar/Wind Harmer
2.757
316349AD2-085 GEN
Solar/Wind Harmer
1.291
316311AC2-079 GEN
Solar/Wind Harmer
7.321
957871AF2-081 GEN
Solar/Wind Harmer
7.252
316305AF2-043 C
Solar/Wind Harmer
0.436
319010AE1-072 C
Solar/Wind Harmer
2.929
3146406KITTY HAWK
Solar/Wind Harmer
0.012
315835AF2-110_GEN
Solar/Wind Harmer
1.806
313526AB2-022
Solar/Wind Harmer
0.389
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
316321Z2-027
Solar/Wind Harmer
0.388
3145176PASQUOTANK
Solar/Wind Harmer
-0.009
3146396TANGLEW
Solar/Wind Harmer
0.264
316315AB2-025 C
Solar/Wind Harmer
0.383
315611Z1-036_GEN2
Solar/Wind Harmer
3.502
315814AE2-033 C
Solar/Wind Harmer
13.198
941031AE2-094 GEN
Solar/Wind Harmer
26.429
944011AF1-069 GEN
Solar/Wind Harmer
8.281
3130156CHOWAN
Solar/Wind Harmer
-0.014
3130156CHOWAN
Solar/Wind Harmer
-0.014
970673AG2-436 GEN
Solar/Wind Harmer
29.36
970673AG2-436 GEN
Solar/Wind Harmer
14.866
971967AH1-528 GEN
Solar/Wind Harmer
26.146
315816AE2-034 GEN
Solar/Wind Harmer
1.125
3147346CASHSCORNER
Solar/Wind Harmer
0.215
3130546PLYMOUTH
Solar/Wind Harmer
-0.014
315732AD1-074 GEN1
Solar/Wind Harmer
2.78
315733AD1-074 GEN2
Solar/Wind Harmer
2.78
315735AD1-075 GEN1
Solar/Wind Harmer
1.39
965291AG1-394 GEN
Solar/Wind Harmer
1.217
3146206CASHIE
Solar/Wind Harmer
-0.014
970601AG2-382 GEN
Solar/Wind Harmer
5.979
316318V4-068
Solar/Wind Harmer
0.34
3145893MURPHYS
Solar/Wind Harmer
-0.037
3145893MURPHYS
Solar/Wind Harmer
-0.014
970085AG2-068 GEN
Solar/Wind Harmer
8.471
970581AG2-369 GEN
Solar/Wind Harmer
7.285
3145513AHOSKIE
Solar/Wind Harmer
0.118
961941AG1-037 GEN
Solar/Wind Harmer
0.102
3145513AHOSKIE
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.013
3146043SEABORD
Solar/Wind Harmer
-0.013
946281AF1-292 GEN
Solar/Wind Harmer
0.302
315607AA1-063A GEN
Solar/Wind Harmer
1.361
316087AB2-174 GEN
Solar/Wind Harmer
1.915
972193AH1-681 GEN
Adder
2.653
972205AH1-687 GEN
Adder
4.954
233935AB2-179 C
Solar/Wind Helper
1.253
232436AB1-176 C
Solar/Wind Helper
0.043
316045AC1-158 PL2
Solar/Wind Harmer
4.768
944631AF1-128 GEN
Adder
64.371
3142543TWELFTH
Solar/Wind Harmer
-0.001
3150851SPRUNCC
Adder
0.62
316159AE1-175 C
Solar/Wind Harmer
0.404
3143526WINTERP
Solar/Wind Harmer
-0.078
971317AH1-138 GEN
Solar/Wind Harmer
1.879
3143226MDLTHAN
Solar/Wind Harmer
-0.015
970129AG2-093 GEN
Solar/Wind Harmer
3.408
316458AB2-190 GEN2
Solar/Wind Harmer
1.511
3138126ROCKLANDING
Solar/Wind Harmer
0.046
315671AE2-027_GEN
Solar/Wind Harmer
11.19
971069AG2-661 GEN
Solar/Wind Harmer
2.358
3147666LOUISA
Solar/Wind Harmer
-0.059
971647AH1-324 GEN
Solar/Wind Harmer
7.424
961611AG1-000B GEN
Solar/Wind Harmer
7.313
316192AB2-158 GEN
Solar/Wind Harmer
1.761
3151171GRAVELC
Adder
1.4
3145336SMITFLD
Solar/Wind Harmer
-0.059
316294AC1-161 GEN
Solar/Wind Harmer
4.745
970659AG2-427 GEN
Solar/Wind Harmer
7.779
316381AD1-082 GEN
Solar/Wind Harmer
1.342
970661AG2-428 GEN
Solar/Wind Harmer
15.511
316375AC2-012 GEN
Solar/Wind Harmer
5.05
3150981CHESPKA
Adder
1.622
944591AF1-124 GEN
Solar/Wind Harmer
66.561
316072AD1-144
Solar/Wind Harmer
0.295
316254AC1-120 GEN1
Solar/Wind Harmer
1.174
316388AE2-253 GEN
Solar/Wind Harmer
0.979
3146456SLIGO L269
Solar/Wind Harmer
-0.014
316246AF1-032 C
Solar/Wind Harmer
0.293
316093AE2-104_GEN
Solar/Wind Harmer
4.2
939411AE1-173 GEN
Solar/Wind Harmer
72.185
940641AE2-051 GEN
Solar/Wind Harmer
13.497
3146516WINFALL
Solar/Wind Harmer
-0.046
3146516WINFALL
Solar/Wind Harmer
-0.014
3143336POWHATN
Solar/Wind Harmer
1.683
315800Z1-036_GEN1
Solar/Wind Harmer
3.502
3151751LOISA D
Adder
8.136
3130156CHOWAN
Solar/Wind Harmer
-0.014
316006AB2-029 C
Solar/Wind Harmer
0.804
971685AH1-345 GEN
Solar/Wind Harmer
1.225
315683AE1-153 C
Solar/Wind Harmer
13.027
316336AC2-165 C
Solar/Wind Harmer
2.43
3150281M RUN A
Adder
16.791
3145663CRESWEL
Solar/Wind Harmer
-0.039
971163AH1-040 GEN
Solar/Wind Harmer
13.033
3150221REMNGT2
Adder
15.606
3150211REMNGT1
Adder
15.502
972201AH1-685 GEN
Adder
2.692
3146206CASHIE
Solar/Wind Harmer
-0.014
971547AH1-271 GEN
Solar/Wind Harmer
3.417
3145893MURPHYS
Solar/Wind Harmer
-0.054
3145893MURPHYS
Solar/Wind Harmer
0.405
316023GEN1_S
Solar/Wind Harmer
0.92
970919AG2-571 GEN
Solar/Wind Harmer
4.298
3146173TUNIS
Solar/Wind Harmer
-0.014
970087AG2-069 GEN
Solar/Wind Harmer
12.706
3145683EARLEYS
Solar/Wind Harmer
-0.013
960081AF2-299 GEN
Solar/Wind Harmer
1.517
970937AG2-583 GEN
Solar/Wind Harmer
9.68
3146263WOODLND
Solar/Wind Harmer
-0.013
957481AF2-042 GEN
Solar/Wind Harmer
41.84
3145963POPLR C
Solar/Wind Harmer
-0.013
316011AB1-132 GEN
Solar/Wind Harmer
2.794
3145823KELFORD
Solar/Wind Harmer
-0.013
3147043LAWRENC
Adder
1.071
972277AH1-723 GEN
Adder
69.197
3144293JTRSVLE
Adder
0.368
223401AF1-299 GEN
Solar/Wind Helper
0.699
233930AB2-032 GEN
Solar/Wind Helper
0.373
233915AB1-141 GEN
Solar/Wind Helper
0.492
232422X3-066 FULL
Solar/Wind Helper
0.112
233964AF2-378 GEN
Solar/Wind Helper
0.041
232426Y1-080 FULL
Solar/Wind Helper
0.038
232428Y3-058 C
Solar/Wind Helper
0.329
233998TM1NIN_3.36
Solar/Wind Helper
0.254
232404W1-003 C
Solar/Wind Helper
0.493
233954AC2-188 GEN
Solar/Wind Helper
0.226
233950AC2-186 GEN
Solar/Wind Helper
0.113
232434Z2-077 GEN
Solar/Wind Helper
0.123
233972AC1-094 C
Solar/Wind Helper
0.293
3150101POSSM6S
50/50
2.218
3150081POSSM6A
50/50
1.451
3150151POSSMC1
50/50
1.955
3150151POSSMC1
50/50
1.955
3150331BIRCHWDA
50/50
29.526
3150021OMF B
50/50
0.315
3141316ARNOLDS
50/50
0.406
3150401LDYSMT4
50/50
22.193
3150371LDYSMT1
50/50
21.444
970497AG2-320 GEN
50/50
14.499
966881AG1-559 GEN
Solar/Wind Harmer
0.506
970737AG2-469 GEN
Solar/Wind Harmer
8.399
3141906WESTMOR
Solar/Wind Harmer
-0.007
971781AH1-399 GEN
Solar/Wind Harmer
1.015
3150351NORNECKC2
Adder
1.444
316404AE1-155 C
Solar/Wind Harmer
3.056
316484AD2-074 GEN
Solar/Wind Harmer
3.964
970009AG2-005 GEN
Solar/Wind Harmer
1.968
962971AG1-146 GEN
Solar/Wind Harmer
2.941
316473AC1-191 GEN
Solar/Wind Harmer
1.687
316156AD2-030 GEN
Solar/Wind Harmer
0.412
3141873WAN 176
Solar/Wind Harmer
1.831
3142416OLDCHRC
Solar/Wind Harmer
1.556
3141766HARMONY
Solar/Wind Harmer
1.373
316280AD1-041 GEN
Solar/Wind Harmer
1.162
316203AE2-005 GEN
Solar/Wind Harmer
6.499
3141843SHACKLE
Adder
0.701
3142433PROV 92
Adder
0.265
3142433PROV 92
Adder
0.265
970293AG2-193 GEN
Solar/Wind Harmer
1.915
3142946ENON
Solar/Wind Harmer
-0.005
3143096IRON208
Adder
0.567
3143096IRON208
Adder
0.556
316044AC1-158 PL1
Solar/Wind Harmer
1.49
316450AC1-158 RIC
Solar/Wind Harmer
0.397
3150861SPRUNCD
Adder
0.62
316382AG1-145 C
Solar/Wind Harmer
0.454
970133AG2-095 GEN
Solar/Wind Harmer
1.687
970129AG2-093 GEN
Solar/Wind Harmer
8.413
3150921YORKTN3
Adder
3.34
3144216WINCHST
Adder
0.5
315778AD1-151 GEN
Solar/Wind Harmer
12.909
965281AG1-393 GEN
Solar/Wind Harmer
1.861
3147666LOUISA
Solar/Wind Harmer
-0.034
315839AE2-212 C
Solar/Wind Harmer
0.447
961611AG1-000B GEN
Solar/Wind Harmer
3.12
3151221GRAVEL6
Adder
9.566
3151171GRAVELC
Adder
1.84
3145336SMITFLD
Solar/Wind Harmer
-0.006
315813AE1-149 C
Solar/Wind Harmer
9.19
315773AC2-141 GEN
Solar/Wind Harmer
6.136
970659AG2-427 GEN
Solar/Wind Harmer
1.379
3144536CHRHLND
Solar/Wind Harmer
-0.002
316083AB2-161 GEN
Solar/Wind Harmer
2.375
970661AG2-428 GEN
Solar/Wind Harmer
2.749
3151101ELIZAR3
Adder
12.058
3144873MCLAUGH
Solar/Wind Harmer
0
944581AF1-123 GEN
Solar/Wind Harmer
66.322
944601AF1-125 GEN
Solar/Wind Harmer
65.287
316170AC1-121 GEN2
Solar/Wind Harmer
0.391
3146456SLIGO L269
Solar/Wind Harmer
-0.014
971153AH1-033 GEN
Solar/Wind Harmer
1.766
316320Y1-086
Solar/Wind Harmer
0.844
3132273ORANGE
Solar/Wind Harmer
-0.003
316435W1029_GEN3
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3145273HOLLAND
Solar/Wind Harmer
-0.011
316313AB2-026
Solar/Wind Harmer
0.383
316258AE1-075 C
Solar/Wind Harmer
0.344
316405AF2-144 C
Solar/Wind Harmer
0.363
3143336POWHATN
Solar/Wind Harmer
1.431
3151761LOISA E
Adder
16.586
3146376EDENTON
Solar/Wind Harmer
-0.014
972183AH1-676 GEN
Adder
133.578
3150301M RUN C
Adder
16.781
3150291M RUN B
Adder
16.656
315614AA2-178 GEN
Solar/Wind Harmer
1.5
3150231REMNGT3
Adder
16.848
3150241REMNGT4
Adder
15.709
972199AH1-684 GEN
Adder
2.382
972217AH1-693 GEN
Adder
2.071
971157AH1-035 GEN
Solar/Wind Harmer
1.721
3156081AA2-088 GEN
Solar/Wind Harmer
4.463
315737AD1-076 GEN
Solar/Wind Harmer
2.612
3146206CASHIE
Solar/Wind Harmer
-0.014
3145893MURPHYS
Solar/Wind Harmer
0.095
3145893MURPHYS
Solar/Wind Harmer
-0.014
316365GEN2_N
Solar/Wind Harmer
0.92
957521AF2-046 GEN
Solar/Wind Harmer
10.729
961681AG1-008 GEN
Solar/Wind Harmer
10.729
970917AG2-570 GEN
Solar/Wind Harmer
33.953
3146173TUNIS
Solar/Wind Harmer
-0.014
3156021HOLLOMANSOL
Solar/Wind Harmer
1.826
316463AE2-346 GEN
Solar/Wind Harmer
0.219
316140AB2-099
Solar/Wind Harmer
0.091
962331AG1-082 GEN
Solar/Wind Harmer
1.692
966621AG1-532 GEN
Solar/Wind Harmer
0.274
3141196NOKESVL
Solar/Wind Harmer
-0.054
3146263WOODLND
Solar/Wind Harmer
-0.013
313506AB2-031 GEN
Solar/Wind Harmer
1.077
3145963POPLR C
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
316317KELFORD C
Solar/Wind Harmer
0.629
3145823KELFORD
Solar/Wind Harmer
-0.013
972255AH1-712 GEN
Adder
59.381
3144293JTRSVLE
Adder
0.368
227287AC2-120 GEN
Solar/Wind Helper
1.281
226910AB2-157 C
Solar/Wind Helper
0.05
223402AF1-300 C
Solar/Wind Helper
0.699
233982AB2-133 GEN
Solar/Wind Helper
0.351
233918AB1-142 GEN
Solar/Wind Helper
0.492
233994AC2-023 GEN
Solar/Wind Helper
0.935
233996TM1833_GEN
Solar/Wind Helper
0.254
233997TMININ_4.2
Solar/Wind Helper
0.254
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
232406W1-004 FULL
Solar/Wind Helper
0.493
233952AC2-187 GEN
Solar/Wind Helper
0.226
233971AC1-093 C
Solar/Wind Helper
0.347
233923SMA
Solar/Wind Helper
0.932
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.065
234033AF1-007_GEN
Solar/Wind Helper
6.824
315652AC1-086 GEN
Solar/Wind Harmer
5.136
3150091POSSM6B
50/50
1.451
3150071POSSM 5
50/50
89.359
3150181POSSMC2
50/50
1.972
3150181POSSMC2
50/50
1.955
3150181POSSMC2
50/50
1.955
957191AF2-013 GEN
50/50
14.143
3150391LDYSMT3
50/50
22.151
972195AH1-682 GEN
50/50
2.911
315673AE1-157 GEN
Solar/Wind Harmer
12.809
957411AF2-035 GEN
Solar/Wind Harmer
7.57
970317AG2-208 GEN
Solar/Wind Harmer
7.36
316468AD1-105 GEN
Solar/Wind Harmer
1.834
316077AC2-138 C
Solar/Wind Harmer
0.338
3150341NORNECKC1
Adder
1.492
3150341NORNECKC1
Adder
1.48
958261AF2-120 GEN
Solar/Wind Harmer
6.138
316487AF1-042 GEN
Solar/Wind Harmer
2.074
966871AG1-558 GEN
Solar/Wind Harmer
0.471
966871AG1-558 GEN
Solar/Wind Harmer
0.161
3142296MT RD221
Adder
0.439
316441AF1-014 GEN
Solar/Wind Harmer
1.039
316075AC2-137 C
Solar/Wind Harmer
0.413
3150691DARBY 3
Adder
9.812
3150701DARBY 4
Adder
9.789
3150681DARBY 2
Adder
9.777
3150671DARBY 1
Adder
9.766
3142366NRTHEST
Adder
0.445
3142946ENON
Solar/Wind Harmer
-0.002
316447AC1-158 HLD
Solar/Wind Harmer
3.278
3143526WINTERP
Solar/Wind Harmer
-0.078
944641AF1-129 GEN
Adder
63.538
971223AH1-071 GEN
Solar/Wind Harmer
1.869
316240AF1-291 C
Solar/Wind Harmer
0.45
316033AB2-134 GEN
Solar/Wind Harmer
4.798
315697AD1-025 GEN
Solar/Wind Harmer
3.009
316236AE1-162_GEN
Solar/Wind Harmer
0.443
970657AG2-426 GEN
Solar/Wind Harmer
4.568
970657AG2-426 GEN
Solar/Wind Harmer
0.955
316036AC1-147 C
Solar/Wind Harmer
0.394
3150991CHESPKB
Adder
1.36
3150991CHESPKB
Adder
1.328
316316AC1-027 C
Solar/Wind Harmer
0.447
3142956BIRDNECK
Solar/Wind Harmer
0.782
316185AD1-033 GEN
Solar/Wind Harmer
1.536
3145506HICKORY
Solar/Wind Harmer
-0.058
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.009
316339AD2-160 GEN
Solar/Wind Harmer
0.979
316018AA1-139 ULT2
Solar/Wind Harmer
1.243
316017AA1-139 ULT1
Solar/Wind Harmer
1.174
3137176SLIGO L2192
Solar/Wind Harmer
-0.057
3146456SLIGO L269
Solar/Wind Harmer
1.711
3130086AYDLETT
Solar/Wind Harmer
-0.058
315651AD1-115 GEN
Solar/Wind Harmer
6.346
3146386ELIZ CT
Solar/Wind Harmer
-0.014
316431W1029_GEN1
Solar/Wind Harmer
2.595
316433W1029_GEN2
Solar/Wind Harmer
2.595
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146516WINFALL
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3146626S HERTFORD
Solar/Wind Harmer
-0.014
3144356SAPONY
Solar/Wind Harmer
0.495
315742AE1-103 GEN
Solar/Wind Harmer
1.477
966001AG1-469 GEN
Solar/Wind Harmer
0.266
3151731LOISA B
Adder
8.136
3151721LOISA A
Adder
8.094
3146376EDENTON
Solar/Wind Harmer
0.418
3146376EDENTON
Solar/Wind Harmer
0.418
972185AH1-677 GEN
Adder
6.951
972187AH1-678 GEN
Adder
3.507
970933AG2-581 GEN
Solar/Wind Harmer
12.906
316065AD1-022 GEN
Solar/Wind Harmer
6.847
3145893MURPHYS
Solar/Wind Harmer
0.381
3145893MURPHYS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.014
3146173TUNIS
Solar/Wind Harmer
-0.014
316181AB2-040 GEN
Solar/Wind Harmer
1.869
970099AG2-077 GEN
Solar/Wind Harmer
16.736
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.013
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3144293JTRSVLE
Adder
0.368
3144293JTRSVLE
Adder
0.31
226929AD2-058 GEN
Solar/Wind Helper
0.4
208835TUHI V3-051
Solar/Wind Helper
0.031
208835TUHI V3-051
Solar/Wind Helper
0.031
233933AB2-153 GEN
Solar/Wind Helper
0.228
233944AB2-135 GEN
Solar/Wind Helper
0.576
232424Y1-079 C
Solar/Wind Helper
0.114
233987AB2-037 GEN
Solar/Wind Helper
2.282
234036AF2-325 C
Solar/Wind Helper
0.041
233946AB2-136 GEN
Solar/Wind Helper
0.553
233901CHERRYDALE C
Solar/Wind Helper
0.226
232408W1-005 C
Solar/Wind Helper
0.493
232410W1-006 C
Solar/Wind Helper
0.493
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
NYPJM->LTFIMP_NY
CLTF
3.816
LGEELTFEXP_LGEE->PJM
CLTF
3.208
LAGNLTFEXP_LAGN->PJM
CLTF
10.915
WECLTFEXP_WEC->PJM
CLTF
1.721
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.861
TVALTFEXP_TVA->PJM
CLTF
5.494
CPLELTFEXP_CPLE->PJM
CLTF
8.313
CBM West 2LTFEXP_CBM-W2->PJM
CBM
68.064
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.932
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.074
MECLTFEXP_MEC->PJM
CLTF
7.89
SIGELTFEXP_SIGE->PJM
CLTF
0.248

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.73 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5687.33
MW Contribution:27.65
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
941031AE2-094 GEN
Solar/Wind Harmer
118.914
944011AF1-069 GEN
Solar/Wind Harmer
38.854
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
NYPJM->LTFIMP_NY
CLTF
2.484
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 585_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 585_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:133.78 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5445.28
MW Contribution:27.65
Bus #Bus NameTypeMW Contribution
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
48.225
957481AF2-042 GEN
Solar/Wind Harmer
144.711
315693AD1-088 GEN
Solar/Wind Harmer
23.762
962491AG1-098 GEN
Solar/Wind Harmer
27.839
315687AD1-152 GEN
Solar/Wind Harmer
0.015
316003AC1-222 GEN
Solar/Wind Harmer
0.009
970401AG2-262 GEN
Solar/Wind Harmer
1.882
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
20.472
963171AG1-166 GEN
Solar/Wind Harmer
1.443
971563AH1-280 GEN
Solar/Wind Harmer
2.885
3146926FARMVIL
Solar/Wind Harmer
0.151
971065AG2-659 GEN
Solar/Wind Harmer
9.511
316129AC1-054 GEN
Solar/Wind Harmer
0.786
970223AG2-152 GEN
Solar/Wind Harmer
12.908
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.097
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.064
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.115
3146802CHATHAM
Solar/Wind Harmer
0.108
941801AE2-185 GEN
Solar/Wind Harmer
4.622
270030AE2-140 GEN
Solar/Wind Harmer
14.688
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.099
316359AB2-059 GEN
Solar/Wind Harmer
0.442
316049AB1-081 GEN
Solar/Wind Harmer
0.704
3142053HEARTS
Solar/Wind Harmer
0.217
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
53.965
316478AD1-087 GEN
Solar/Wind Harmer
1.733
316486AD2-202 GEN
Solar/Wind Harmer
0.509
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
0.003
960061AF2-297 GEN
Solar/Wind Harmer
14.727
971683AH1-343 GEN
Solar/Wind Harmer
11.379
316283AC2-100 C
Solar/Wind Harmer
0.592
316131AB2-060 GEN
Solar/Wind Harmer
0.901
964241AG1-285 GEN
Solar/Wind Harmer
18.92
315785AD2-033 C
Solar/Wind Harmer
2.274
970257AG2-171 GEN
Solar/Wind Harmer
8.9
959311AF2-222 GEN
Solar/Wind Harmer
24.62
963181AG1-167 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.841
971193AH1-056 GEN
Solar/Wind Harmer
16.311
942461AE2-259 GEN
Solar/Wind Harmer
-0.002
3146926FARMVIL
Solar/Wind Harmer
0.151
3146776BUCKING
Solar/Wind Harmer
0.058
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
1.012
3147312GRETNA
Solar/Wind Harmer
0.029
941821AE2-187 GEN
Solar/Wind Harmer
4.622
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
270336AE1-100 GEN
Solar/Wind Harmer
0.004
3145543BTLEBRO
Solar/Wind Harmer
0.123
3145543BTLEBRO
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.246
961601AG1-000A GEN
Solar/Wind Harmer
8.544
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
109.53
970673AG2-436 GEN
Solar/Wind Harmer
137.75
970673AG2-436 GEN
Solar/Wind Harmer
91.833
970085AG2-068 GEN
Solar/Wind Harmer
32.15
970581AG2-369 GEN
Solar/Wind Harmer
27.649
3147173SINAI
Solar/Wind Harmer
0.345
3147243WELCO
Solar/Wind Harmer
0.216
316118AC1-105 GEN
Solar/Wind Harmer
0.86
970865AG2-541 GEN
Solar/Wind Harmer
10.119
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.678
3144303KENBRDG
Solar/Wind Harmer
0.222
970683AG2-441 GEN
Solar/Wind Harmer
18.278
970681AG2-440 GEN
Solar/Wind Harmer
14.623
946301AF1-294 GEN
Solar/Wind Harmer
5.338
961791AG1-021 GEN
Solar/Wind Harmer
2.597
315657AE1-056 GEN
Solar/Wind Harmer
9.239
316123AC1-075 GEN
Solar/Wind Harmer
0.351
970165AG2-112 GEN
Solar/Wind Harmer
2.08
970163AG2-111 GEN
Solar/Wind Harmer
1.985
970831AG2-522 GEN
Solar/Wind Harmer
8.286
970285AG2-188 GEN
Solar/Wind Harmer
14.461
971845AH1-439 GEN
Solar/Wind Harmer
7.612
270069AE2-166 C O1
Solar/Wind Harmer
0.005
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
51.542
970099AG2-077 GEN
Solar/Wind Harmer
57.884
971741AH1-377 GEN
Solar/Wind Harmer
38.437
970301AG2-198 GEN
Solar/Wind Harmer
15.165
3146843MT LREL
Solar/Wind Harmer
0.321
3146843MT LREL
Solar/Wind Harmer
0.321
964791AG1-342 GEN
Solar/Wind Harmer
6.159
962561AG1-105 GEN
Solar/Wind Harmer
15.15
316222AC1-221 GEN
Solar/Wind Harmer
1.267
939181AE1-148 GEN
Solar/Wind Harmer
13.97
313527AB2-043 GEN
Solar/Wind Harmer
0.004
970323AG2-213 GEN
Solar/Wind Harmer
11.867
971775AH1-396 GEN
Solar/Wind Harmer
0.445
316034AC1-036 C
Solar/Wind Harmer
0.02
958211AF2-115 GEN
Solar/Wind Harmer
3.246
963191AG1-168 GEN
Solar/Wind Harmer
1.082
3147133PAMPLIN
Solar/Wind Harmer
0.268
3147133PAMPLIN
Solar/Wind Harmer
0.214
942751AE2-291 GEN
Solar/Wind Harmer
12.744
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.64
3146776BUCKING
Solar/Wind Harmer
0.052
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.595
316263AC1-034 GEN
Solar/Wind Harmer
4.676
961601AG1-000A GEN
Solar/Wind Harmer
2.136
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
NYPJM->LTFIMP_NY
CLTF
2.484
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 58572_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 58572_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.04 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6196.95
MW Contribution:36.4
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970673AG2-436 GEN
Solar/Wind Harmer
152.413
970673AG2-436 GEN
Solar/Wind Harmer
77.171
941031AE2-094 GEN
Solar/Wind Harmer
136.017
944011AF1-069 GEN
Solar/Wind Harmer
42.619
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
970533AG2-339 GEN
50/50
57.391
970531AG2-338 GEN
50/50
22.956
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
NYPJM->LTFIMP_NY
CLTF
2.484
LGEELTFEXP_LGEE->PJM
CLTF
2.833
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-5: W72_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-5: W72_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.43 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6166.56
MW Contribution:36.15
Bus #Bus NameTypeMW Contribution
3151041BRUNSWICKG3
50/50
8.442
972187AH1-678 GEN
50/50
19.374
315242AE2-183_GT2
50/50
10.589
315241AE2-183_GT1
50/50
10.524
972185AH1-677 GEN
50/50
38.176
970533AG2-339 GEN
50/50
56.972
970531AG2-338 GEN
50/50
22.789
3152661PLYWOOD A
50/50
0.749
970535AG2-341 GEN
50/50
5.154
3144293JTRSVLE
50/50
0.912
3144293JTRSVLE
50/50
0.768
970933AG2-581 GEN
Solar/Wind Harmer
67.369
970099AG2-077 GEN
Solar/Wind Harmer
75.708
971741AH1-377 GEN
Solar/Wind Harmer
50.305
970301AG2-198 GEN
Solar/Wind Harmer
19.85
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.683
962561AG1-105 GEN
Solar/Wind Harmer
19.916
316222AC1-221 GEN
Solar/Wind Harmer
3.458
939181AE1-148 GEN
Solar/Wind Harmer
18.413
313527AB2-043 GEN
Solar/Wind Harmer
5.244
970323AG2-213 GEN
Solar/Wind Harmer
15.621
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.741
963191AG1-168 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.715
270013AE1-250 PV
Solar/Wind Harmer
3.032
3146776BUCKING
Solar/Wind Harmer
-0.071
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.625
316197AC1-042 GEN
Solar/Wind Harmer
1.99
942671AE2-283 GEN
Solar/Wind Harmer
5.357
316263AC1-034 GEN
Solar/Wind Harmer
6.638
961601AG1-000A GEN
Solar/Wind Harmer
5.443
963041AG1-153 GEN
50/50
17.095
315244AE2-183_ST
50/50
18.308
3151541CLOVER2
50/50
10.527
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
143.519
970673AG2-436 GEN
Solar/Wind Harmer
151.3
970673AG2-436 GEN
Solar/Wind Harmer
76.608
941031AE2-094 GEN
Solar/Wind Harmer
135.024
944011AF1-069 GEN
Solar/Wind Harmer
42.308
970085AG2-068 GEN
Solar/Wind Harmer
42.031
970581AG2-369 GEN
Solar/Wind Harmer
36.147
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.567
970865AG2-541 GEN
Solar/Wind Harmer
13.271
316239AB2-077_GEN
Solar/Wind Harmer
0.98
316238AB2-078_GEN
Solar/Wind Harmer
0.98
971443AH1-215 GEN
Solar/Wind Harmer
6.158
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.044
970681AG2-440 GEN
Solar/Wind Harmer
19.235
946301AF1-294 GEN
Solar/Wind Harmer
7.775
961791AG1-021 GEN
Solar/Wind Harmer
3.793
315657AE1-056 GEN
Solar/Wind Harmer
11.263
316123AC1-075 GEN
Solar/Wind Harmer
3.099
970165AG2-112 GEN
Solar/Wind Harmer
2.728
970163AG2-111 GEN
Solar/Wind Harmer
2.603
270455AD2-022 GEN
Solar/Wind Harmer
4.991
270457AD2-023 GEN
Solar/Wind Harmer
2.531
970831AG2-522 GEN
Solar/Wind Harmer
11.041
970285AG2-188 GEN
Solar/Wind Harmer
17.881
971845AH1-439 GEN
Solar/Wind Harmer
9.974
270069AE2-166 C O1
Solar/Wind Harmer
2.569
319010AE1-072 C
Solar/Wind Helper
4.32
3143316POE
Solar/Wind Helper
1.486
316305AF2-043 C
Solar/Wind Helper
0.5
316369SG1_INVT
Solar/Wind Helper
1.758
957831AF2-077 GEN
Solar/Wind Helper
0.492
316132AB2-190 GEN1
Solar/Wind Helper
2.041
316349AD2-085 GEN
Solar/Wind Helper
1.61
313526AB2-022
Solar/Wind Helper
0.535
957601AF2-054 GEN
Solar/Wind Helper
0.462
3141873WAN 176
Solar/Wind Helper
0.069
315662AE1-191 GEN
Solar/Wind Helper
1.844
315666AE1-190 GEN
Solar/Wind Helper
0.461
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316059AD1-063 C
Solar/Wind Helper
0.344
3141913WHIT STONE
Solar/Wind Helper
0.341
3138133OCRAN
Solar/Wind Helper
0.102
3143873LANEXA
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.203
3141783LANCAST
Solar/Wind Helper
0.135
316321Z2-027
Solar/Wind Helper
0.515
3145176PASQUOTANK
Solar/Wind Helper
0.209
3141813NORNECK
Solar/Wind Helper
0.321
316312AB1-027
Solar/Wind Helper
0.585
316223AC1-118
Solar/Wind Helper
0.461
316233AE1-074 FULL
Solar/Wind Helper
0.462
316315AB2-025 C
Solar/Wind Helper
0.44
315611Z1-036_GEN2
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
3130156CHOWAN
Solar/Wind Helper
0.24
3151031BRUNSWICKG2
50/50
8.442
970413AG2-270 GEN
50/50
46.159
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.912
970917AG2-570 GEN
Solar/Wind Harmer
169.32
316478AD1-087 GEN
Solar/Wind Harmer
4.801
316486AD2-202 GEN
Solar/Wind Harmer
1.406
970909AG2-566 GEN
Solar/Wind Harmer
3.769
316248AF1-058 C
Solar/Wind Harmer
1.164
960061AF2-297 GEN
Solar/Wind Harmer
19.314
971683AH1-343 GEN
Solar/Wind Harmer
14.923
316283AC2-100 C
Solar/Wind Harmer
3.192
316131AB2-060 GEN
Solar/Wind Harmer
3.475
964241AG1-285 GEN
Solar/Wind Harmer
24.93
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.716
959311AF2-222 GEN
Solar/Wind Harmer
32.468
963181AG1-167 GEN
Solar/Wind Harmer
2.845
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.772
942461AE2-259 GEN
Solar/Wind Harmer
4.384
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.461
270197AD1-017 GEN1
Solar/Wind Harmer
1.796
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.064
943811AF1-049 GEN
Solar/Wind Harmer
4.077
270336AE1-100 GEN
Solar/Wind Harmer
1.664
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.512
3138543CONSLDL
Solar/Wind Harmer
-0.008
315773AC2-141 GEN
Solar/Wind Helper
9.706
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
3146456SLIGO L269
Solar/Wind Helper
0.38
316382AG1-145 C
Solar/Wind Helper
0.496
315839AE2-212 C
Solar/Wind Helper
0.483
316320Y1-086
Solar/Wind Helper
0.157
316156AD2-030 GEN
Solar/Wind Helper
0.52
316280AD1-041 GEN
Solar/Wind Helper
1.152
3142946ENON
Solar/Wind Helper
0.111
316484AD2-074 GEN
Solar/Wind Helper
0.641
316404AE1-155 C
Solar/Wind Helper
2.769
316435W1029_GEN3
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.121
3146626S HERTFORD
Solar/Wind Helper
0.296
316473AC1-191 GEN
Solar/Wind Helper
1.785
3145273HOLLAND
Solar/Wind Helper
0.198
966881AG1-559 GEN
Solar/Wind Helper
0.346
3146376EDENTON
Solar/Wind Helper
0.239
3151051BRUNSWICKS1
50/50
17.522
3151021BRUNSWICKG1
50/50
8.442
971451AH1-221 GEN
50/50
25.642
316036AC1-147 C
Solar/Wind Helper
0.624
3142956BIRDNECK
Solar/Wind Helper
0.274
316316AC1-027 C
Solar/Wind Helper
0.642
316185AD1-033 GEN
Solar/Wind Helper
1.905
3145506HICKORY
Solar/Wind Helper
1.596
3145506HICKORY
Solar/Wind Helper
0.958
3145506HICKORY
Solar/Wind Helper
0.239
316236AE1-162_GEN
Solar/Wind Helper
0.527
316339AD2-160 GEN
Solar/Wind Helper
1.48
316018AA1-139 ULT2
Solar/Wind Helper
1.659
316017AA1-139 ULT1
Solar/Wind Helper
1.763
3137176SLIGO L2192
Solar/Wind Helper
1.516
3130086AYDLETT
Solar/Wind Helper
1.505
316033AB2-134 GEN
Solar/Wind Helper
1.257
315697AD1-025 GEN
Solar/Wind Helper
4.177
3146386ELIZ CT
Solar/Wind Helper
0.351
316240AF1-291 C
Solar/Wind Helper
0.468
3142946ENON
Solar/Wind Helper
0.033
316487AF1-042 GEN
Solar/Wind Helper
0.335
316075AC2-137 C
Solar/Wind Helper
0.492
316077AC2-138 C
Solar/Wind Helper
0.302
316431W1029_GEN1
Solar/Wind Helper
1.297
316433W1029_GEN2
Solar/Wind Helper
1.297
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.573
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
966871AG1-558 GEN
Solar/Wind Helper
0.394
3144356SAPONY
Solar/Wind Helper
0.518
316468AD1-105 GEN
Solar/Wind Helper
1.373
315742AE1-103 GEN
Solar/Wind Helper
0.362
315243AE2-183_GT3
50/50
10.589
3151531CLOVER1
50/50
10.578
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.912
971629AH1-314 GEN
50/50
18.997
3151561HALLBR1
50/50
0.403
970919AG2-571 GEN
Solar/Wind Harmer
21.433
970087AG2-069 GEN
Solar/Wind Harmer
63.047
957481AF2-042 GEN
Solar/Wind Harmer
189.269
315693AD1-088 GEN
Solar/Wind Harmer
27.634
962491AG1-098 GEN
Solar/Wind Harmer
36.422
315687AD1-152 GEN
Solar/Wind Harmer
5.988
316003AC1-222 GEN
Solar/Wind Harmer
3.561
970401AG2-262 GEN
Solar/Wind Harmer
2.348
316237AB2-079_GEN
Solar/Wind Harmer
0.98
970685AG2-442 GEN
Solar/Wind Harmer
26.929
963171AG1-166 GEN
Solar/Wind Harmer
3.793
971563AH1-280 GEN
Solar/Wind Harmer
3.793
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.621
316129AC1-054 GEN
Solar/Wind Harmer
2.079
970223AG2-152 GEN
Solar/Wind Harmer
18.347
270016AE1-250 BESS
Solar/Wind Harmer
3.032
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.602
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.978
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.064
270030AE2-140 GEN
Solar/Wind Harmer
20.984
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.909
316049AB1-081 GEN
Solar/Wind Harmer
1.528
3142053HEARTS
Solar/Wind Harmer
0.166
316294AC1-161 GEN
Solar/Wind Helper
8.246
316375AC2-012 GEN
Solar/Wind Helper
1.074
3145336SMITFLD
Solar/Wind Helper
1.568
316388AE2-253 GEN
Solar/Wind Helper
1.48
3146456SLIGO L269
Solar/Wind Helper
0.38
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.426
316159AE1-175 C
Solar/Wind Helper
0.559
316381AD1-082 GEN
Solar/Wind Helper
1.857
316458AB2-190 GEN2
Solar/Wind Helper
2.041
3141766HARMONY
Solar/Wind Helper
0.068
3138133OCRAN
Solar/Wind Helper
0.204
3142433PROV 92
Solar/Wind Helper
1.345
3142543TWELFTH
Solar/Wind Helper
0.031
964211AG1-282 GEN
Solar/Wind Helper
0.434
3141726DUNNSVL
Solar/Wind Helper
1.289
3146516WINFALL
Solar/Wind Helper
1.017
3146516WINFALL
Solar/Wind Helper
0.314
316337AD2-073 GEN
Solar/Wind Helper
0.473
3142416OLDCHRC
Solar/Wind Helper
0.799
3142416OLDCHRC
Solar/Wind Helper
0.306
3143526WINTERP
Solar/Wind Helper
1.573
3143226MDLTHAN
Solar/Wind Helper
0.298
315800Z1-036_GEN1
Solar/Wind Helper
1.494
3130156CHOWAN
Solar/Wind Helper
0.24
NYPJM->LTFIMP_NY
CLTF
2.481
LAGNLTFEXP_LAGN->PJM
CLTF
15.349
LGEELTFEXP_LGEE->PJM
CLTF
2.822
WECLTFEXP_WEC->PJM
CLTF
1.476
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.145
TVALTFEXP_TVA->PJM
CLTF
7.657
CPLELTFEXP_CPLE->PJM
CLTF
20.587
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.048
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.486
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.354
MECLTFEXP_MEC->PJM
CLTF
7.751
SIGELTFEXP_SIGE->PJM
CLTF
0.232

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: XT585_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: XT585_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.16 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5703.66
MW Contribution:36.4
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.505
970413AG2-270 GEN
50/50
46.449
3151591KERR 2
50/50
0.604
3144293JTRSVLE
50/50
0.914
970917AG2-570 GEN
Solar/Wind Harmer
170.53
963041AG1-153 GEN
50/50
17.22
315244AE2-183_ST
50/50
18.443
3151541CLOVER2
50/50
10.593
3151611KERR 4
50/50
0.604
3151621KERR 5
50/50
0.604
3151631KERR 6
50/50
0.604
3151641KERR 7
50/50
0.604
971967AH1-528 GEN
Solar/Wind Harmer
144.6
970085AG2-068 GEN
Solar/Wind Harmer
42.331
970581AG2-369 GEN
Solar/Wind Harmer
36.404
3147173SINAI
Solar/Wind Harmer
-0.039
3147243WELCO
Solar/Wind Harmer
-0.024
316118AC1-105 GEN
Solar/Wind Harmer
2.575
970865AG2-541 GEN
Solar/Wind Harmer
13.323
316239AB2-077_GEN
Solar/Wind Harmer
0.978
316238AB2-078_GEN
Solar/Wind Harmer
0.978
971443AH1-215 GEN
Solar/Wind Harmer
6.159
3144303KENBRDG
Solar/Wind Harmer
-0.025
970683AG2-441 GEN
Solar/Wind Harmer
24.066
316478AD1-087 GEN
Solar/Wind Harmer
4.831
316486AD2-202 GEN
Solar/Wind Harmer
1.415
970909AG2-566 GEN
Solar/Wind Harmer
3.791
316248AF1-058 C
Solar/Wind Harmer
1.169
960061AF2-297 GEN
Solar/Wind Harmer
19.391
971683AH1-343 GEN
Solar/Wind Harmer
14.982
316283AC2-100 C
Solar/Wind Harmer
3.205
316131AB2-060 GEN
Solar/Wind Harmer
3.471
964241AG1-285 GEN
Solar/Wind Harmer
24.911
315785AD2-033 C
Solar/Wind Harmer
7.122
970257AG2-171 GEN
Solar/Wind Harmer
11.718
959311AF2-222 GEN
Solar/Wind Harmer
32.481
963181AG1-167 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.094
971193AH1-056 GEN
Solar/Wind Harmer
18.811
942461AE2-259 GEN
Solar/Wind Harmer
4.399
3146926FARMVIL
Solar/Wind Harmer
-0.017
3146776BUCKING
Solar/Wind Harmer
-0.006
270018AE2-047 C O1
Solar/Wind Harmer
1.466
270197AD1-017 GEN1
Solar/Wind Harmer
1.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
6.086
943811AF1-049 GEN
Solar/Wind Harmer
4.09
270336AE1-100 GEN
Solar/Wind Harmer
1.669
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.014
961601AG1-000A GEN
Solar/Wind Harmer
5.373
315773AC2-141 GEN
Solar/Wind Helper
9.595
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.061
3145336SMITFLD
Solar/Wind Helper
0.157
315839AE2-212 C
Solar/Wind Helper
0.523
3146456SLIGO L269
Solar/Wind Helper
0.379
316382AG1-145 C
Solar/Wind Helper
0.498
316320Y1-086
Solar/Wind Helper
0.156
316156AD2-030 GEN
Solar/Wind Helper
0.525
316280AD1-041 GEN
Solar/Wind Helper
1.166
3142946ENON
Solar/Wind Helper
0.114
316484AD2-074 GEN
Solar/Wind Helper
0.648
316404AE1-155 C
Solar/Wind Helper
2.8
316435W1029_GEN3
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3141906WESTMOR
Solar/Wind Helper
0.122
316473AC1-191 GEN
Solar/Wind Helper
1.829
3146626S HERTFORD
Solar/Wind Helper
0.296
3145273HOLLAND
Solar/Wind Helper
0.201
966881AG1-559 GEN
Solar/Wind Helper
0.35
3146376EDENTON
Solar/Wind Helper
0.24
970681AG2-440 GEN
Solar/Wind Harmer
19.253
946301AF1-294 GEN
Solar/Wind Harmer
7.788
961791AG1-021 GEN
Solar/Wind Harmer
3.799
315657AE1-056 GEN
Solar/Wind Harmer
11.287
316123AC1-075 GEN
Solar/Wind Harmer
3.111
970165AG2-112 GEN
Solar/Wind Harmer
2.739
970163AG2-111 GEN
Solar/Wind Harmer
2.613
270455AD2-022 GEN
Solar/Wind Harmer
5.008
270457AD2-023 GEN
Solar/Wind Harmer
2.539
970831AG2-522 GEN
Solar/Wind Harmer
10.909
970285AG2-188 GEN
Solar/Wind Harmer
17.971
971845AH1-439 GEN
Solar/Wind Harmer
10.023
270069AE2-166 C O1
Solar/Wind Harmer
2.578
3143316POE
Solar/Wind Helper
1.64
319010AE1-072 C
Solar/Wind Helper
4.299
316369SG1_INVT
Solar/Wind Helper
1.8
316305AF2-043 C
Solar/Wind Helper
0.499
316132AB2-190 GEN1
Solar/Wind Helper
2.107
957831AF2-077 GEN
Solar/Wind Helper
0.495
316349AD2-085 GEN
Solar/Wind Helper
1.649
313526AB2-022
Solar/Wind Helper
0.533
957601AF2-054 GEN
Solar/Wind Helper
0.467
3141873WAN 176
Solar/Wind Helper
0.07
315662AE1-191 GEN
Solar/Wind Helper
1.865
315666AE1-190 GEN
Solar/Wind Helper
0.466
316059AD1-063 C
Solar/Wind Helper
0.348
3141913WHIT STONE
Solar/Wind Helper
0.345
3138133OCRAN
Solar/Wind Helper
0.103
3143873LANEXA
Solar/Wind Helper
0.206
3141783LANCAST
Solar/Wind Helper
0.205
3151041BRUNSWICKG3
50/50
8.505
972187AH1-678 GEN
50/50
19.517
315242AE2-183_GT2
50/50
10.667
315241AE2-183_GT1
50/50
10.602
972185AH1-677 GEN
50/50
38.457
3152661PLYWOOD A
50/50
0.751
970535AG2-341 GEN
50/50
5.149
3144293JTRSVLE
50/50
0.914
3144293JTRSVLE
50/50
0.769
970933AG2-581 GEN
Solar/Wind Harmer
67.863
970099AG2-077 GEN
Solar/Wind Harmer
76.214
971741AH1-377 GEN
Solar/Wind Harmer
50.609
970301AG2-198 GEN
Solar/Wind Harmer
19.968
3146843MT LREL
Solar/Wind Harmer
-0.036
3146843MT LREL
Solar/Wind Harmer
-0.036
964791AG1-342 GEN
Solar/Wind Harmer
7.699
962561AG1-105 GEN
Solar/Wind Harmer
19.948
316222AC1-221 GEN
Solar/Wind Harmer
3.472
939181AE1-148 GEN
Solar/Wind Harmer
18.394
313527AB2-043 GEN
Solar/Wind Harmer
5.237
970323AG2-213 GEN
Solar/Wind Harmer
15.625
971775AH1-396 GEN
Solar/Wind Harmer
2.225
316034AC1-036 C
Solar/Wind Harmer
0.579
958211AF2-115 GEN
Solar/Wind Harmer
4.748
963191AG1-168 GEN
Solar/Wind Harmer
2.849
3147133PAMPLIN
Solar/Wind Harmer
-0.03
3147133PAMPLIN
Solar/Wind Harmer
-0.024
942751AE2-291 GEN
Solar/Wind Harmer
16.78
270013AE1-250 PV
Solar/Wind Harmer
3.042
3146776BUCKING
Solar/Wind Harmer
-0.072
3146776BUCKING
Solar/Wind Harmer
-0.006
316217AC1-145 GEN
Solar/Wind Harmer
2.634
316197AC1-042 GEN
Solar/Wind Harmer
1.997
942671AE2-283 GEN
Solar/Wind Harmer
5.376
316263AC1-034 GEN
Solar/Wind Harmer
6.481
961601AG1-000A GEN
Solar/Wind Harmer
5.306
316036AC1-147 C
Solar/Wind Helper
0.621
3142956BIRDNECK
Solar/Wind Helper
0.272
316316AC1-027 C
Solar/Wind Helper
0.638
316185AD1-033 GEN
Solar/Wind Helper
1.893
3145506HICKORY
Solar/Wind Helper
1.587
3145506HICKORY
Solar/Wind Helper
0.952
3145506HICKORY
Solar/Wind Helper
0.238
316236AE1-162_GEN
Solar/Wind Helper
0.529
316339AD2-160 GEN
Solar/Wind Helper
1.472
316018AA1-139 ULT2
Solar/Wind Helper
1.65
316017AA1-139 ULT1
Solar/Wind Helper
1.754
3137176SLIGO L2192
Solar/Wind Helper
1.508
3130086AYDLETT
Solar/Wind Helper
1.498
316033AB2-134 GEN
Solar/Wind Helper
1.287
315697AD1-025 GEN
Solar/Wind Helper
4.277
316240AF1-291 C
Solar/Wind Helper
0.501
3146386ELIZ CT
Solar/Wind Helper
0.35
3142946ENON
Solar/Wind Helper
0.034
316487AF1-042 GEN
Solar/Wind Helper
0.339
3144356SAPONY
Solar/Wind Helper
0.597
316075AC2-137 C
Solar/Wind Helper
0.502
316077AC2-138 C
Solar/Wind Helper
0.305
316431W1029_GEN1
Solar/Wind Helper
1.295
316433W1029_GEN2
Solar/Wind Helper
1.295
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
966871AG1-558 GEN
Solar/Wind Helper
0.403
3146626S HERTFORD
Solar/Wind Helper
0.296
3146626S HERTFORD
Solar/Wind Helper
0.296
316468AD1-105 GEN
Solar/Wind Helper
1.402
315742AE1-103 GEN
Solar/Wind Helper
0.368
3141783LANCAST
Solar/Wind Helper
0.137
3146486SUNBURY
Solar/Wind Helper
0.341
3146486SUNBURY
Solar/Wind Helper
0.341
316321Z2-027
Solar/Wind Helper
0.514
3145176PASQUOTANK
Solar/Wind Helper
0.209
316315AB2-025 C
Solar/Wind Helper
0.507
3141813NORNECK
Solar/Wind Helper
0.325
316312AB1-027
Solar/Wind Helper
0.597
316233AE1-074 FULL
Solar/Wind Helper
0.469
316223AC1-118
Solar/Wind Helper
0.466
315611Z1-036_GEN2
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
3130156CHOWAN
Solar/Wind Helper
0.241
3151051BRUNSWICKS1
50/50
17.651
3151021BRUNSWICKG1
50/50
8.505
971451AH1-221 GEN
50/50
25.831
315243AE2-183_GT3
50/50
10.667
3151531CLOVER1
50/50
10.644
3151601KERR 3
50/50
0.604
3151581KERR 1
50/50
0.216
3144293JTRSVLE
50/50
0.914
971629AH1-314 GEN
50/50
19.06
3151561HALLBR1
50/50
0.404
970919AG2-571 GEN
Solar/Wind Harmer
21.586
970087AG2-069 GEN
Solar/Wind Harmer
63.496
957481AF2-042 GEN
Solar/Wind Harmer
190.536
315693AD1-088 GEN
Solar/Wind Harmer
27.811
962491AG1-098 GEN
Solar/Wind Harmer
36.654
315687AD1-152 GEN
Solar/Wind Harmer
6.022
316003AC1-222 GEN
Solar/Wind Harmer
3.575
970401AG2-262 GEN
Solar/Wind Harmer
2.352
316237AB2-079_GEN
Solar/Wind Harmer
0.978
970685AG2-442 GEN
Solar/Wind Harmer
26.954
963171AG1-166 GEN
Solar/Wind Harmer
3.799
971563AH1-280 GEN
Solar/Wind Harmer
3.799
3146926FARMVIL
Solar/Wind Harmer
-0.017
971065AG2-659 GEN
Solar/Wind Harmer
12.523
316129AC1-054 GEN
Solar/Wind Harmer
2.059
970223AG2-152 GEN
Solar/Wind Harmer
18.408
270016AE1-250 BESS
Solar/Wind Harmer
3.042
3147123OTTER R
Solar/Wind Harmer
-0.011
316322AB2-045
Solar/Wind Harmer
0.605
3146776BUCKING
Solar/Wind Harmer
-0.007
270574AD1-017 GEN2
Solar/Wind Harmer
5.998
3147312GRETNA
Solar/Wind Harmer
-0.013
3146802CHATHAM
Solar/Wind Harmer
-0.012
941801AE2-185 GEN
Solar/Wind Harmer
6.086
270030AE2-140 GEN
Solar/Wind Harmer
21.053
3145543BTLEBRO
Solar/Wind Harmer
-0.014
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.864
316049AB1-081 GEN
Solar/Wind Harmer
1.492
3142053HEARTS
Solar/Wind Harmer
0.163
316294AC1-161 GEN
Solar/Wind Helper
8.153
316375AC2-012 GEN
Solar/Wind Helper
1.068
3145336SMITFLD
Solar/Wind Helper
1.575
316388AE2-253 GEN
Solar/Wind Helper
1.472
3146456SLIGO L269
Solar/Wind Helper
0.379
316381AD1-082 GEN
Solar/Wind Helper
1.955
316072AD1-144
Solar/Wind Helper
0.428
316246AF1-032 C
Solar/Wind Helper
0.424
316159AE1-175 C
Solar/Wind Helper
0.562
316458AB2-190 GEN2
Solar/Wind Helper
2.107
3141766HARMONY
Solar/Wind Helper
0.069
3142433PROV 92
Solar/Wind Helper
1.376
3138133OCRAN
Solar/Wind Helper
0.206
3142543TWELFTH
Solar/Wind Helper
0.032
964211AG1-282 GEN
Solar/Wind Helper
0.439
3141726DUNNSVL
Solar/Wind Helper
1.304
316337AD2-073 GEN
Solar/Wind Helper
0.478
3142416OLDCHRC
Solar/Wind Helper
0.816
3142416OLDCHRC
Solar/Wind Helper
0.312
3146516WINFALL
Solar/Wind Helper
1.016
3146516WINFALL
Solar/Wind Helper
0.314
3143526WINTERP
Solar/Wind Helper
1.596
3143226MDLTHAN
Solar/Wind Helper
0.3
315800Z1-036_GEN1
Solar/Wind Helper
1.497
3130156CHOWAN
Solar/Wind Helper
0.241
NYPJM->LTFIMP_NY
CLTF
2.484
LAGNLTFEXP_LAGN->PJM
CLTF
15.403
LGEELTFEXP_LGEE->PJM
CLTF
2.833
WECLTFEXP_WEC->PJM
CLTF
1.482
AG2-052LTFEXP_AG2-052->PJM
LTF
0.08
AH1-155LTFEXP_AH1-155->PJM
LTF
0.12
CBM South 2LTFEXP_CBM-S2->PJM
CBM
46.288
TVALTFEXP_TVA->PJM
CLTF
7.684
CPLELTFEXP_CPLE->PJM
CLTF
20.639
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.697
CBM South 1LTFEXP_CBM-S1->PJM
CBM
26.447
MECLTFEXP_MEC->PJM
CLTF
7.78
SIGELTFEXP_SIGE->PJM
CLTF
0.233

Details for 8RAWLINGS-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 54472_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8RAWLINGS-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 54472_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.74 %
Rating:2858.0 MVA
Rating Type:C
MVA to Mitigate:3193.49
MW Contribution:17.84
Bus #Bus NameTypeMW Contribution
970413AG2-270 GEN
50/50
34.77
3151031BRUNSWICKG2
50/50
4.131
3151591KERR 2
50/50
0.44
3144293JTRSVLE
50/50
0.691
316478AD1-087 GEN
Solar/Wind Harmer
3.615
316486AD2-202 GEN
Solar/Wind Harmer
1.059
970917AG2-570 GEN
Solar/Wind Harmer
83.468
970909AG2-566 GEN
Solar/Wind Harmer
2.9
316248AF1-058 C
Solar/Wind Harmer
0.833
960061AF2-297 GEN
Solar/Wind Harmer
13.826
971683AH1-343 GEN
Solar/Wind Harmer
10.636
316131AB2-060 GEN
Solar/Wind Harmer
2.567
964241AG1-285 GEN
Solar/Wind Harmer
18.486
315785AD2-033 C
Solar/Wind Harmer
5.315
970257AG2-171 GEN
Solar/Wind Harmer
8.764
959311AF2-222 GEN
Solar/Wind Harmer
24.33
963181AG1-167 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.071
971193AH1-056 GEN
Solar/Wind Harmer
14.275
942461AE2-259 GEN
Solar/Wind Harmer
3.375
3146926FARMVIL
Solar/Wind Harmer
-0.013
316283AC2-100 C
Solar/Wind Harmer
2.04
3146776BUCKING
Solar/Wind Harmer
-0.005
315773AC2-141 GEN
Solar/Wind Helper
5.476
315839AE2-212 C
Solar/Wind Helper
0.317
3151541CLOVER2
50/50
7.93
963041AG1-153 GEN
50/50
8.365
315244AE2-183_ST
50/50
6.698
3151611KERR 4
50/50
0.44
3151621KERR 5
50/50
0.44
3151631KERR 6
50/50
0.44
3151641KERR 7
50/50
0.44
971967AH1-528 GEN
Solar/Wind Harmer
110.812
970085AG2-068 GEN
Solar/Wind Harmer
20.738
970581AG2-369 GEN
Solar/Wind Harmer
17.835
3147173SINAI
Solar/Wind Harmer
-0.028
3147243WELCO
Solar/Wind Harmer
-0.017
316118AC1-105 GEN
Solar/Wind Harmer
1.848
316239AB2-077_GEN
Solar/Wind Harmer
0.722
316238AB2-078_GEN
Solar/Wind Harmer
0.722
971443AH1-215 GEN
Solar/Wind Harmer
4.604
3144303KENBRDG
Solar/Wind Harmer
-0.019
970865AG2-541 GEN
Solar/Wind Harmer
9.435
970683AG2-441 GEN
Solar/Wind Harmer
18.098
970681AG2-440 GEN
Solar/Wind Harmer
14.478
946301AF1-294 GEN
Solar/Wind Harmer
5.887
961791AG1-021 GEN
Solar/Wind Harmer
2.872
315657AE1-056 GEN
Solar/Wind Harmer
8.565
316123AC1-075 GEN
Solar/Wind Harmer
2.19
970165AG2-112 GEN
Solar/Wind Harmer
1.928
970163AG2-111 GEN
Solar/Wind Harmer
1.839
970673AG2-436 GEN
Solar/Wind Harmer
40.956
970673AG2-436 GEN
Solar/Wind Harmer
20.737
270455AD2-022 GEN
Solar/Wind Harmer
3.036
270457AD2-023 GEN
Solar/Wind Harmer
1.539
970285AG2-188 GEN
Solar/Wind Harmer
14.324
970831AG2-522 GEN
Solar/Wind Harmer
8.077
971845AH1-439 GEN
Solar/Wind Harmer
8.053
3143316POE
Solar/Wind Helper
1.004
3151041BRUNSWICKG3
50/50
4.131
972187AH1-678 GEN
50/50
9.481
3152661PLYWOOD A
50/50
0.538
315242AE2-183_GT2
50/50
3.874
315241AE2-183_GT1
50/50
3.85
972185AH1-677 GEN
50/50
13.967
970535AG2-341 GEN
50/50
3.778
3144293JTRSVLE
50/50
0.691
3144293JTRSVLE
50/50
0.582
970933AG2-581 GEN
Solar/Wind Harmer
51.852
970099AG2-077 GEN
Solar/Wind Harmer
57.614
971741AH1-377 GEN
Solar/Wind Harmer
38.586
970301AG2-198 GEN
Solar/Wind Harmer
15.274
3146843MT LREL
Solar/Wind Harmer
-0.026
3146843MT LREL
Solar/Wind Harmer
-0.026
964791AG1-342 GEN
Solar/Wind Harmer
5.564
962561AG1-105 GEN
Solar/Wind Harmer
14.462
939181AE1-148 GEN
Solar/Wind Harmer
13.444
313527AB2-043 GEN
Solar/Wind Harmer
3.87
970323AG2-213 GEN
Solar/Wind Harmer
11.685
971775AH1-396 GEN
Solar/Wind Harmer
1.664
316034AC1-036 C
Solar/Wind Harmer
0.433
958211AF2-115 GEN
Solar/Wind Harmer
3.59
963191AG1-168 GEN
Solar/Wind Harmer
2.154
3147133PAMPLIN
Solar/Wind Harmer
-0.023
3147133PAMPLIN
Solar/Wind Harmer
-0.018
316222AC1-221 GEN
Solar/Wind Harmer
2.218
942751AE2-291 GEN
Solar/Wind Harmer
11.754
3146776BUCKING
Solar/Wind Harmer
-0.058
3146776BUCKING
Solar/Wind Harmer
-0.005
316240AF1-291 C
Solar/Wind Helper
0.299
3151531CLOVER1
50/50
7.968
3151051BRUNSWICKS1
50/50
8.574
3151021BRUNSWICKG1
50/50
4.131
971451AH1-221 GEN
50/50
12.548
315243AE2-183_GT3
50/50
3.874
3151601KERR 3
50/50
0.44
3151581KERR 1
50/50
0.157
3144293JTRSVLE
50/50
0.691
971629AH1-314 GEN
50/50
11.594
957481AF2-042 GEN
Solar/Wind Harmer
144.035
315693AD1-088 GEN
Solar/Wind Harmer
21.036
962491AG1-098 GEN
Solar/Wind Harmer
27.737
315687AD1-152 GEN
Solar/Wind Harmer
4.411
970919AG2-571 GEN
Solar/Wind Harmer
10.566
970087AG2-069 GEN
Solar/Wind Harmer
31.107
970401AG2-262 GEN
Solar/Wind Harmer
1.7
316003AC1-222 GEN
Solar/Wind Harmer
2.544
316237AB2-079_GEN
Solar/Wind Harmer
0.722
970685AG2-442 GEN
Solar/Wind Harmer
20.27
963171AG1-166 GEN
Solar/Wind Harmer
2.872
971563AH1-280 GEN
Solar/Wind Harmer
2.872
3146926FARMVIL
Solar/Wind Harmer
-0.013
971065AG2-659 GEN
Solar/Wind Harmer
9.218
316129AC1-054 GEN
Solar/Wind Harmer
1.52
316322AB2-045
Solar/Wind Harmer
0.488
3146776BUCKING
Solar/Wind Harmer
-0.006
970223AG2-152 GEN
Solar/Wind Harmer
11.343
316294AC1-161 GEN
Solar/Wind Helper
4.653
NYPJM->LTFIMP_NY
CLTF
1.417
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
LGEELTFEXP_LGEE->PJM
CLTF
1.692
WECLTFEXP_WEC->PJM
CLTF
0.884
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.434
TVALTFEXP_TVA->PJM
CLTF
4.461
CPLELTFEXP_CPLE->PJM
CLTF
11.786
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.401
MECLTFEXP_MEC->PJM
CLTF
4.601
SIGELTFEXP_SIGE->PJM
CLTF
0.139

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:123.06 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5008.65
MW Contribution:27.36
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
NYPJM->LTFIMP_NY
CLTF
2.382
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5458.06
MW Contribution:36.03
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.79 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5435.07
MW Contribution:35.79
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
NYPJM->LTFIMP_NY
CLTF
2.38
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
LGEELTFEXP_LGEE->PJM
CLTF
2.666
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for 8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.19 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5355.19
MW Contribution:35.49
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.637
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.87 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3044.37
MW Contribution:14.68
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
7.478
963041AG1-153 GEN
50/50
6.855
3151541CLOVER2
50/50
4.265
3151081ELIZAR1
50/50
18.321
941031AE2-094 GEN
Solar/Wind Harmer
57.43
944011AF1-069 GEN
Solar/Wind Harmer
17.995
970673AG2-436 GEN
Solar/Wind Harmer
62.661
970673AG2-436 GEN
Solar/Wind Harmer
31.727
971967AH1-528 GEN
Solar/Wind Harmer
54.485
970085AG2-068 GEN
Solar/Wind Harmer
17.073
970581AG2-369 GEN
Solar/Wind Harmer
14.683
3151091ELIZAR2
Adder
16.966
3152611GOSPORTB
Adder
2.331
3152621GOSPORTC
Adder
1.978
3152601GOSPORTA
Adder
1.825
957871AF2-081 GEN
Solar/Wind Harmer
10.216
319010AE1-072 C
Solar/Wind Harmer
4.045
3146406KITTY HAWK
Solar/Wind Harmer
0.017
313526AB2-022
Solar/Wind Harmer
0.498
316321Z2-027
Solar/Wind Harmer
0.479
3146396TANGLEW
Solar/Wind Harmer
0.327
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
316118AC1-105 GEN
Solar/Wind Harmer
1.188
316239AB2-077_GEN
Solar/Wind Harmer
0.514
316238AB2-078_GEN
Solar/Wind Harmer
0.514
970831AG2-522 GEN
Solar/Wind Harmer
8.491
315611Z1-036_GEN2
Solar/Wind Harmer
4.001
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316315AB2-025 C
Solar/Wind Harmer
0.431
315814AE2-033 C
Solar/Wind Harmer
14.87
946281AF1-292 GEN
Solar/Wind Harmer
0.356
316087AB2-174 GEN
Solar/Wind Harmer
2.26
971443AH1-215 GEN
Solar/Wind Harmer
3.103
3137643SOCKMAN
Solar/Wind Harmer
-0.063
315816AE2-034 GEN
Solar/Wind Harmer
1.272
3144303KENBRDG
Solar/Wind Harmer
-0.013
315652AC1-086 GEN
Solar/Wind Harmer
17.441
3145796HORNRTN
Solar/Wind Harmer
-0.049
3145796HORNRTN
Solar/Wind Harmer
-0.006
316319Z2-044 C
Solar/Wind Harmer
0.856
3130546PLYMOUTH
Solar/Wind Harmer
-0.015
315732AD1-074 GEN1
Solar/Wind Harmer
3.122
315733AD1-074 GEN2
Solar/Wind Harmer
3.122
315735AD1-075 GEN1
Solar/Wind Harmer
1.561
3145573BETHELC
Solar/Wind Harmer
-0.015
3145573BETHELC
Solar/Wind Harmer
-0.015
316420AA1-050 GEN
Solar/Wind Harmer
1.751
957861AF2-080 GEN
Solar/Wind Harmer
6.681
3146033SCOT NK
Solar/Wind Harmer
-0.061
315607AA1-063A GEN
Solar/Wind Harmer
1.534
316005AA1-067
Solar/Wind Harmer
0.307
3145746EVERETS
Solar/Wind Harmer
-0.06
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
1.989
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.629
970683AG2-441 GEN
Solar/Wind Harmer
11.827
970681AG2-440 GEN
Solar/Wind Harmer
9.461
3146043SEABORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3151031BRUNSWICKG2
50/50
3.386
970413AG2-270 GEN
50/50
18.7
3151101ELIZAR3
50/50
18.555
315773AC2-141 GEN
Solar/Wind Harmer
27.544
970917AG2-570 GEN
Solar/Wind Harmer
68.686
944581AF1-123 GEN
Solar/Wind Harmer
109.673
944601AF1-125 GEN
Solar/Wind Harmer
107.961
316478AD1-087 GEN
Solar/Wind Harmer
1.946
316486AD2-202 GEN
Solar/Wind Harmer
0.57
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.454
316320Y1-086
Solar/Wind Harmer
1.083
3144536CHRHLND
Solar/Wind Harmer
-0.003
316248AF1-058 C
Solar/Wind Harmer
0.522
960061AF2-297 GEN
Solar/Wind Harmer
8.669
316131AB2-060 GEN
Solar/Wind Harmer
1.825
964241AG1-285 GEN
Solar/Wind Harmer
12.927
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.549
3147043LAWRENC
Solar/Wind Harmer
-0.01
3146376EDENTON
Solar/Wind Harmer
-0.016
315785AD2-033 C
Solar/Wind Harmer
3.613
316435W1029_GEN3
Solar/Wind Harmer
2.886
966621AG1-532 GEN
Solar/Wind Harmer
0.323
316283AC2-100 C
Solar/Wind Harmer
1.496
313506AB2-031 GEN
Solar/Wind Harmer
1.271
316365GEN2_N
Solar/Wind Harmer
1.06
315614AA2-178 GEN
Solar/Wind Harmer
1.696
970257AG2-171 GEN
Solar/Wind Harmer
5.892
959311AF2-222 GEN
Solar/Wind Harmer
16.228
971683AH1-343 GEN
Solar/Wind Harmer
6.691
315243AE2-183_GT3
50/50
4.325
3151051BRUNSWICKS1
50/50
7.027
3151021BRUNSWICKG1
50/50
3.386
971451AH1-221 GEN
50/50
10.283
3151531CLOVER1
50/50
4.285
316294AC1-161 GEN
Solar/Wind Harmer
21.297
940641AE2-051 GEN
Solar/Wind Harmer
36.033
970919AG2-571 GEN
Solar/Wind Harmer
8.694
970087AG2-069 GEN
Solar/Wind Harmer
25.61
944591AF1-124 GEN
Solar/Wind Harmer
110.068
957481AF2-042 GEN
Solar/Wind Harmer
75.055
939411AE1-173 GEN
Solar/Wind Harmer
119.429
315693AD1-088 GEN
Solar/Wind Harmer
11.114
962491AG1-098 GEN
Solar/Wind Harmer
14.661
315687AD1-152 GEN
Solar/Wind Harmer
2.497
316375AC2-012 GEN
Solar/Wind Harmer
7.148
3150981CHESPKA
Adder
2.295
316388AE2-253 GEN
Solar/Wind Harmer
1.388
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971065AG2-659 GEN
Solar/Wind Harmer
8.623
970401AG2-262 GEN
Solar/Wind Harmer
1.122
316129AC1-054 GEN
Solar/Wind Harmer
1.501
316237AB2-079_GEN
Solar/Wind Harmer
0.514
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.598
3147043LAWRENC
Adder
1.308
315800Z1-036_GEN1
Solar/Wind Harmer
4.001
971795AH1-408 GEN
Solar/Wind Harmer
12.102
3130156CHOWAN
Solar/Wind Harmer
-0.016
960081AF2-299 GEN
Solar/Wind Harmer
1.79
316023GEN1_S
Solar/Wind Harmer
1.06
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.733
3145783HORNRTN
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.191
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.012
316359AB2-059 GEN
Solar/Wind Harmer
2.091
316049AB1-081 GEN
Solar/Wind Harmer
1.673
3142053HEARTS
Solar/Wind Harmer
0.182
316011AB1-132 GEN
Solar/Wind Harmer
3.244
962571AG1-106 GEN
Solar/Wind Harmer
2.229
3145796HORNRTN
Solar/Wind Harmer
-0.051
3145796HORNRTN
Solar/Wind Harmer
-0.015
315722AD1-056 GEN
Solar/Wind Harmer
1.622
3146233WITAKRS
Solar/Wind Harmer
-0.061
961671AG1-007 GEN
Solar/Wind Harmer
0.194
3146083TARBORO
Solar/Wind Harmer
-0.015
3145493TOT1
Solar/Wind Harmer
0.456
316212AC1-099_GEN
Solar/Wind Harmer
1.34
3145963POPLR C
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.357
316494AC1-189 GEN
Solar/Wind Harmer
1.643
3146293MARTNCO
Solar/Wind Harmer
0.094
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.788
970685AG2-442 GEN
Solar/Wind Harmer
13.246
3146263WOODLND
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
963171AG1-166 GEN
Solar/Wind Harmer
1.825
971563AH1-280 GEN
Solar/Wind Harmer
1.825
3144293JTRSVLE
Adder
0.414
3145893MURPHYS
Solar/Wind Harmer
-0.058
3145893MURPHYS
Solar/Wind Harmer
0.431
316159AE1-175 C
Solar/Wind Helper
0.509
3141766HARMONY
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.148
964211AG1-282 GEN
Solar/Wind Helper
0.305
3141726DUNNSVL
Solar/Wind Helper
0.905
3145513AHOSKIE
Solar/Wind Harmer
0.129
961941AG1-037 GEN
Solar/Wind Harmer
0.111
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970865AG2-541 GEN
Solar/Wind Harmer
5.947
946301AF1-294 GEN
Solar/Wind Harmer
3.74
961791AG1-021 GEN
Solar/Wind Harmer
1.825
316318V4-068
Solar/Wind Harmer
0.362
3145893MURPHYS
Solar/Wind Harmer
-0.039
3145893MURPHYS
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
965291AG1-394 GEN
Solar/Wind Harmer
1.275
315657AE1-056 GEN
Solar/Wind Harmer
5.332
270455AD2-022 GEN
Solar/Wind Harmer
2.402
270457AD2-023 GEN
Solar/Wind Harmer
1.218
316123AC1-075 GEN
Solar/Wind Harmer
1.387
970165AG2-112 GEN
Solar/Wind Harmer
1.221
970163AG2-111 GEN
Solar/Wind Harmer
1.165
957831AF2-077 GEN
Solar/Wind Helper
0.39
957601AF2-054 GEN
Solar/Wind Helper
0.337
3141873WAN 176
Solar/Wind Helper
0.05
3141913WHIT STONE
Solar/Wind Helper
0.247
316059AD1-063 C
Solar/Wind Helper
0.249
3138133OCRAN
Solar/Wind Helper
0.074
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.098
315662AE1-191 GEN
Solar/Wind Helper
1.31
315666AE1-190 GEN
Solar/Wind Helper
0.327
3141813NORNECK
Solar/Wind Helper
0.225
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145543BTLEBRO
Solar/Wind Harmer
-0.015
3145796HORNRTN
Solar/Wind Harmer
-0.062
3145796HORNRTN
Solar/Wind Harmer
-0.015
315724AD1-057 GEN
Solar/Wind Harmer
0.892
3138543CONSLDL
Solar/Wind Harmer
-0.01
3146233WITAKRS
Solar/Wind Harmer
0.324
3146233WITAKRS
Solar/Wind Harmer
-0.01
961601AG1-000A GEN
Solar/Wind Harmer
6.167
316327AA2-057 GEN
Solar/Wind Harmer
1.564
971157AH1-035 GEN
Solar/Wind Harmer
1.935
315737AD1-076 GEN
Solar/Wind Harmer
2.934
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3146073TAR RVR
Solar/Wind Harmer
-0.015
3146083TARBORO
Solar/Wind Harmer
-0.015
316210AC1-098 GEN
Solar/Wind Harmer
2.411
3145963POPLR C
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.9
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3146206CASHIE
Solar/Wind Harmer
-0.015
3146263WOODLND
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.709
3145823KELFORD
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.239
316140AB2-099
Solar/Wind Harmer
0.1
962331AG1-082 GEN
Solar/Wind Harmer
1.848
3156021HOLLOMANSOL
Solar/Wind Harmer
1.987
3146173TUNIS
Solar/Wind Harmer
-0.015
963181AG1-167 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
957521AF2-046 GEN
Solar/Wind Harmer
11.482
961681AG1-008 GEN
Solar/Wind Harmer
11.482
3145893MURPHYS
Solar/Wind Harmer
0.101
3145893MURPHYS
Solar/Wind Harmer
-0.014
3156081AA2-088 GEN
Solar/Wind Harmer
4.63
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.887
942461AE2-259 GEN
Solar/Wind Harmer
1.975
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.451
316156AD2-030 GEN
Solar/Wind Helper
0.379
316280AD1-041 GEN
Solar/Wind Helper
0.819
316484AD2-074 GEN
Solar/Wind Helper
0.458
316404AE1-155 C
Solar/Wind Helper
1.965
970533AG2-339 GEN
50/50
24.232
970531AG2-338 GEN
50/50
9.693
315242AE2-183_GT2
50/50
4.325
315241AE2-183_GT1
50/50
4.299
972185AH1-677 GEN
50/50
15.592
3151041BRUNSWICKG3
50/50
3.386
972187AH1-678 GEN
50/50
7.769
970933AG2-581 GEN
Solar/Wind Harmer
25.842
970099AG2-077 GEN
Solar/Wind Harmer
30.022
316185AD1-033 GEN
Solar/Wind Harmer
2.257
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.051
3145506HICKORY
Solar/Wind Harmer
-0.013
3142956BIRDNECK
Solar/Wind Harmer
1.119
316316AC1-027 C
Solar/Wind Harmer
0.638
316036AC1-147 C
Solar/Wind Harmer
0.557
3150991CHESPKB
Adder
1.926
3150991CHESPKB
Adder
1.879
316339AD2-160 GEN
Solar/Wind Harmer
1.388
316018AA1-139 ULT2
Solar/Wind Harmer
1.75
316017AA1-139 ULT1
Solar/Wind Harmer
1.653
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.378
3130086AYDLETT
Solar/Wind Harmer
-0.079
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.967
971741AH1-377 GEN
Solar/Wind Harmer
20.543
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.674
962561AG1-105 GEN
Solar/Wind Harmer
9.657
313527AB2-043 GEN
Solar/Wind Harmer
2.762
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
970301AG2-198 GEN
Solar/Wind Harmer
8.157
3146376EDENTON
Solar/Wind Harmer
0.475
3146376EDENTON
Solar/Wind Harmer
0.475
3144356SAPONY
Solar/Wind Harmer
0.557
316222AC1-221 GEN
Solar/Wind Harmer
1.617
316431W1029_GEN1
Solar/Wind Harmer
2.886
316433W1029_GEN2
Solar/Wind Harmer
2.886
316181AB2-040 GEN
Solar/Wind Harmer
2.206
970323AG2-213 GEN
Solar/Wind Harmer
7.857
971775AH1-396 GEN
Solar/Wind Harmer
1.119
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.767
3145593CAROLNA
Solar/Wind Harmer
0.13
316034AC1-036 C
Solar/Wind Harmer
0.291
3145783HORNRTN
Solar/Wind Harmer
1.86
3145783HORNRTN
Solar/Wind Harmer
1.488
3145783HORNRTN
Solar/Wind Harmer
0.465
3145783HORNRTN
Solar/Wind Harmer
0.186
316426AA2-053 GEN
Solar/Wind Harmer
1.572
316263AC1-034 GEN
Solar/Wind Harmer
7.27
3145796HORNRTN
Solar/Wind Harmer
-0.046
961601AG1-000A GEN
Solar/Wind Harmer
6.09
316274AC1-208 GEN
Solar/Wind Harmer
1.672
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3145493TOT1
Solar/Wind Harmer
0.238
3145453TOT5
Solar/Wind Harmer
0.143
3145603CNETO
Solar/Wind Harmer
0.095
316065AD1-022 GEN
Solar/Wind Harmer
7.628
3145933PARMELE
Solar/Wind Harmer
-0.03
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
958211AF2-115 GEN
Solar/Wind Harmer
2.281
963191AG1-168 GEN
Solar/Wind Harmer
1.368
3144293JTRSVLE
Adder
0.414
3144293JTRSVLE
Adder
0.348
3145893MURPHYS
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.368
316487AF1-042 GEN
Solar/Wind Helper
0.24
316077AC2-138 C
Solar/Wind Helper
0.212
NYPJM->LTFIMP_NY
CLTF
1.354
LAGNLTFEXP_LAGN->PJM
CLTF
7.136
LGEELTFEXP_LGEE->PJM
CLTF
1.211
WECLTFEXP_WEC->PJM
CLTF
0.63
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.765
TVALTFEXP_TVA->PJM
CLTF
3.554
CPLELTFEXP_CPLE->PJM
CLTF
10.589
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.328
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.129
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.134
MECLTFEXP_MEC->PJM
CLTF
3.403
SIGELTFEXP_SIGE->PJM
CLTF
0.101

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.05 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:2961.86
MW Contribution:14.1
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
4.144
3151051BRUNSWICKS1
50/50
6.736
3151021BRUNSWICKG1
50/50
3.245
971451AH1-221 GEN
50/50
9.857
3151531CLOVER1
50/50
4.146
316294AC1-161 GEN
Solar/Wind Harmer
21.122
940641AE2-051 GEN
Solar/Wind Harmer
34.85
970919AG2-571 GEN
Solar/Wind Harmer
8.346
970087AG2-069 GEN
Solar/Wind Harmer
24.586
944591AF1-124 GEN
Solar/Wind Harmer
108.386
957481AF2-042 GEN
Solar/Wind Harmer
72.436
939411AE1-173 GEN
Solar/Wind Harmer
114.333
315693AD1-088 GEN
Solar/Wind Harmer
10.761
962491AG1-098 GEN
Solar/Wind Harmer
14.201
315244AE2-183_ST
50/50
7.165
963041AG1-153 GEN
50/50
6.572
3151541CLOVER2
50/50
4.126
3151081ELIZAR1
50/50
18.089
941031AE2-094 GEN
Solar/Wind Harmer
54.965
944011AF1-069 GEN
Solar/Wind Harmer
17.222
970673AG2-436 GEN
Solar/Wind Harmer
60.015
970673AG2-436 GEN
Solar/Wind Harmer
30.387
971967AH1-528 GEN
Solar/Wind Harmer
52.234
3151031BRUNSWICKG2
50/50
3.245
970413AG2-270 GEN
50/50
18.093
3151101ELIZAR3
50/50
18.321
315773AC2-141 GEN
Solar/Wind Harmer
27.318
970917AG2-570 GEN
Solar/Wind Harmer
65.93
944581AF1-123 GEN
Solar/Wind Harmer
107.997
944601AF1-125 GEN
Solar/Wind Harmer
106.312
316478AD1-087 GEN
Solar/Wind Harmer
1.883
316486AD2-202 GEN
Solar/Wind Harmer
0.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.424
316320Y1-086
Solar/Wind Harmer
1.072
3144536CHRHLND
Solar/Wind Harmer
-0.003
316365GEN2_N
Solar/Wind Harmer
1.198
966621AG1-532 GEN
Solar/Wind Harmer
0.354
3147043LAWRENC
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.365
316248AF1-058 C
Solar/Wind Harmer
0.511
960061AF2-297 GEN
Solar/Wind Harmer
8.482
316131AB2-060 GEN
Solar/Wind Harmer
1.822
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.017
316375AC2-012 GEN
Solar/Wind Harmer
7.061
3150981CHESPKA
Adder
2.267
316388AE2-253 GEN
Solar/Wind Harmer
1.371
315687AD1-152 GEN
Solar/Wind Harmer
2.422
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316023GEN1_S
Solar/Wind Harmer
1.198
960081AF2-299 GEN
Solar/Wind Harmer
1.961
971065AG2-659 GEN
Solar/Wind Harmer
8.708
316129AC1-054 GEN
Solar/Wind Harmer
1.52
971795AH1-408 GEN
Solar/Wind Harmer
13
3147043LAWRENC
Adder
1.392
316237AB2-079_GEN
Solar/Wind Harmer
0.513
970401AG2-262 GEN
Solar/Wind Harmer
1.108
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
1.696
315800Z1-036_GEN1
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.563
3146233WITAKRS
Solar/Wind Harmer
-0.063
316359AB2-059 GEN
Solar/Wind Harmer
2.141
316049AB1-081 GEN
Solar/Wind Harmer
1.714
3142053HEARTS
Solar/Wind Harmer
0.187
316212AC1-099_GEN
Solar/Wind Harmer
1.384
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.826
961671AG1-007 GEN
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.466
3146263WOODLND
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.675
3145963POPLR C
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.391
3146293MARTNCO
Solar/Wind Harmer
0.096
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.855
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
970685AG2-442 GEN
Solar/Wind Harmer
13.211
3145893MURPHYS
Solar/Wind Harmer
-0.06
3145893MURPHYS
Solar/Wind Harmer
0.445
963171AG1-166 GEN
Solar/Wind Harmer
1.819
971563AH1-280 GEN
Solar/Wind Harmer
1.819
3144293JTRSVLE
Adder
0.412
316159AE1-175 C
Solar/Wind Helper
0.502
3138133OCRAN
Solar/Wind Helper
0.143
3141766HARMONY
Solar/Wind Helper
0.048
970085AG2-068 GEN
Solar/Wind Harmer
16.391
970581AG2-369 GEN
Solar/Wind Harmer
14.096
3151091ELIZAR2
Adder
16.751
3152611GOSPORTB
Adder
2.303
3152621GOSPORTC
Adder
1.954
3152601GOSPORTA
Adder
1.803
957871AF2-081 GEN
Solar/Wind Harmer
10.089
319010AE1-072 C
Solar/Wind Harmer
3.997
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316315AB2-025 C
Solar/Wind Harmer
0.53
315814AE2-033 C
Solar/Wind Harmer
18.209
313526AB2-022
Solar/Wind Harmer
0.493
316321Z2-027
Solar/Wind Harmer
0.475
3146396TANGLEW
Solar/Wind Harmer
0.324
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
946281AF1-292 GEN
Solar/Wind Harmer
0.39
970831AG2-522 GEN
Solar/Wind Harmer
8.629
316087AB2-174 GEN
Solar/Wind Harmer
2.442
316239AB2-077_GEN
Solar/Wind Harmer
0.513
316238AB2-078_GEN
Solar/Wind Harmer
0.513
316118AC1-105 GEN
Solar/Wind Harmer
1.167
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316319Z2-044 C
Solar/Wind Harmer
0.879
315607AA1-063A GEN
Solar/Wind Harmer
1.601
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3146043SEABORD
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.096
3146033SCOT NK
Solar/Wind Harmer
-0.063
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.013
316420AA1-050 GEN
Solar/Wind Harmer
1.787
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.159
315733AD1-074 GEN2
Solar/Wind Harmer
3.159
315735AD1-075 GEN1
Solar/Wind Harmer
1.58
957861AF2-080 GEN
Solar/Wind Harmer
6.812
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.746
316005AA1-067
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.022
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.133
961941AG1-037 GEN
Solar/Wind Harmer
0.115
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
11.796
970681AG2-440 GEN
Solar/Wind Harmer
9.436
316318V4-068
Solar/Wind Harmer
0.374
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
-0.015
965291AG1-394 GEN
Solar/Wind Harmer
1.319
946301AF1-294 GEN
Solar/Wind Harmer
3.729
961791AG1-021 GEN
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
970865AG2-541 GEN
Solar/Wind Harmer
5.823
315657AE1-056 GEN
Solar/Wind Harmer
5.314
3143316POE
Solar/Wind Harmer
-0.054
270455AD2-022 GEN
Solar/Wind Harmer
2.354
270457AD2-023 GEN
Solar/Wind Harmer
1.194
957831AF2-077 GEN
Solar/Wind Helper
0.384
957601AF2-054 GEN
Solar/Wind Helper
0.326
3141873WAN 176
Solar/Wind Helper
0.049
3141913WHIT STONE
Solar/Wind Helper
0.239
3138133OCRAN
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.24
3141783LANCAST
Solar/Wind Helper
0.142
3141783LANCAST
Solar/Wind Helper
0.094
315662AE1-191 GEN
Solar/Wind Helper
1.261
315666AE1-190 GEN
Solar/Wind Helper
0.315
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
964241AG1-285 GEN
Solar/Wind Harmer
12.904
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
315724AD1-057 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.517
316327AA2-057 GEN
Solar/Wind Harmer
1.611
3146233WITAKRS
Solar/Wind Harmer
0.333
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.01
315785AD2-033 C
Solar/Wind Harmer
3.605
961601AG1-000A GEN
Solar/Wind Harmer
6.324
316210AC1-098 GEN
Solar/Wind Harmer
2.492
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.706
316435W1029_GEN3
Solar/Wind Harmer
2.865
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
970257AG2-171 GEN
Solar/Wind Harmer
5.879
971157AH1-035 GEN
Solar/Wind Harmer
1.956
3146263WOODLND
Solar/Wind Harmer
-0.016
315737AD1-076 GEN
Solar/Wind Harmer
2.968
316283AC2-100 C
Solar/Wind Harmer
1.463
3145963POPLR C
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.731
3145823KELFORD
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
16.19
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.929
3146206CASHIE
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.247
316140AB2-099
Solar/Wind Harmer
0.103
962331AG1-082 GEN
Solar/Wind Harmer
1.905
971683AH1-343 GEN
Solar/Wind Harmer
6.55
3146173TUNIS
Solar/Wind Harmer
-0.015
3156021HOLLOMANSOL
Solar/Wind Harmer
2.039
957521AF2-046 GEN
Solar/Wind Harmer
11.856
961681AG1-008 GEN
Solar/Wind Harmer
11.856
3145893MURPHYS
Solar/Wind Harmer
0.105
3145893MURPHYS
Solar/Wind Harmer
-0.015
3156081AA2-088 GEN
Solar/Wind Harmer
4.785
963181AG1-167 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.857
942461AE2-259 GEN
Solar/Wind Harmer
1.967
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.367
316280AD1-041 GEN
Solar/Wind Helper
0.788
316484AD2-074 GEN
Solar/Wind Helper
0.442
316404AE1-155 C
Solar/Wind Helper
1.895
970533AG2-339 GEN
50/50
23.192
970531AG2-338 GEN
50/50
9.277
315242AE2-183_GT2
50/50
4.144
315241AE2-183_GT1
50/50
4.119
972185AH1-677 GEN
50/50
14.94
3151041BRUNSWICKG3
50/50
3.245
972187AH1-678 GEN
50/50
7.448
970933AG2-581 GEN
Solar/Wind Harmer
24.816
970099AG2-077 GEN
Solar/Wind Harmer
28.974
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
3142956BIRDNECK
Solar/Wind Harmer
1.104
316316AC1-027 C
Solar/Wind Harmer
0.63
316036AC1-147 C
Solar/Wind Harmer
0.55
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
316339AD2-160 GEN
Solar/Wind Harmer
1.371
316018AA1-139 ULT2
Solar/Wind Harmer
1.729
316017AA1-139 ULT1
Solar/Wind Harmer
1.633
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.349
3130086AYDLETT
Solar/Wind Harmer
-0.078
3144356SAPONY
Solar/Wind Harmer
0.685
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.927
971741AH1-377 GEN
Solar/Wind Harmer
20.052
316181AB2-040 GEN
Solar/Wind Harmer
2.37
313527AB2-043 GEN
Solar/Wind Harmer
2.758
962561AG1-105 GEN
Solar/Wind Harmer
9.546
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3145796HORNRTN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.856
3145593CAROLNA
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
1.949
3145783HORNRTN
Solar/Wind Harmer
1.559
3145783HORNRTN
Solar/Wind Harmer
0.487
3145783HORNRTN
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
1.645
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.732
3146376EDENTON
Solar/Wind Harmer
0.476
3146376EDENTON
Solar/Wind Harmer
0.476
970301AG2-198 GEN
Solar/Wind Harmer
7.988
961601AG1-000A GEN
Solar/Wind Harmer
6.245
316263AC1-034 GEN
Solar/Wind Harmer
7.445
316431W1029_GEN1
Solar/Wind Harmer
2.865
316433W1029_GEN2
Solar/Wind Harmer
2.865
3145493TOT1
Solar/Wind Harmer
0.243
3145453TOT5
Solar/Wind Harmer
0.146
3145603CNETO
Solar/Wind Harmer
0.097
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971775AH1-396 GEN
Solar/Wind Harmer
1.116
316034AC1-036 C
Solar/Wind Harmer
0.291
316222AC1-221 GEN
Solar/Wind Harmer
1.581
316065AD1-022 GEN
Solar/Wind Harmer
7.746
3145933PARMELE
Solar/Wind Harmer
-0.031
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.419
3145893MURPHYS
Solar/Wind Harmer
-0.027
958211AF2-115 GEN
Solar/Wind Harmer
2.274
963191AG1-168 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.347
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.397
316487AF1-042 GEN
Solar/Wind Helper
0.231
NYPJM->LTFIMP_NY
CLTF
1.344
LAGNLTFEXP_LAGN->PJM
CLTF
6.991
LGEELTFEXP_LGEE->PJM
CLTF
1.186
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
TVALTFEXP_TVA->PJM
CLTF
3.482
CPLELTFEXP_CPLE->PJM
CLTF
10.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.559
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.888
MECLTFEXP_MEC->PJM
CLTF
3.331
SIGELTFEXP_SIGE->PJM
CLTF
0.099

Details for 8SEPTA-8SURRY 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SEPTA-8SURRY 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.05 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:2961.86
MW Contribution:14.1
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
7.165
963041AG1-153 GEN
50/50
6.572
3151541CLOVER2
50/50
4.126
3151081ELIZAR1
50/50
18.089
941031AE2-094 GEN
Solar/Wind Harmer
54.965
944011AF1-069 GEN
Solar/Wind Harmer
17.222
970673AG2-436 GEN
Solar/Wind Harmer
60.015
970673AG2-436 GEN
Solar/Wind Harmer
30.387
971967AH1-528 GEN
Solar/Wind Harmer
52.234
970085AG2-068 GEN
Solar/Wind Harmer
16.391
970581AG2-369 GEN
Solar/Wind Harmer
14.096
3151091ELIZAR2
Adder
16.751
3152611GOSPORTB
Adder
2.303
3152621GOSPORTC
Adder
1.954
3152601GOSPORTA
Adder
1.803
957871AF2-081 GEN
Solar/Wind Harmer
10.089
319010AE1-072 C
Solar/Wind Harmer
3.997
3146406KITTY HAWK
Solar/Wind Harmer
0.016
316315AB2-025 C
Solar/Wind Harmer
0.53
315814AE2-033 C
Solar/Wind Harmer
18.209
313526AB2-022
Solar/Wind Harmer
0.493
316321Z2-027
Solar/Wind Harmer
0.475
3146396TANGLEW
Solar/Wind Harmer
0.324
3145176PASQUOTANK
Solar/Wind Harmer
-0.011
946281AF1-292 GEN
Solar/Wind Harmer
0.39
970831AG2-522 GEN
Solar/Wind Harmer
8.629
316087AB2-174 GEN
Solar/Wind Harmer
2.442
316239AB2-077_GEN
Solar/Wind Harmer
0.513
316238AB2-078_GEN
Solar/Wind Harmer
0.513
316118AC1-105 GEN
Solar/Wind Harmer
1.167
3147173SINAI
Solar/Wind Harmer
-0.017
3147243WELCO
Solar/Wind Harmer
-0.011
3137643SOCKMAN
Solar/Wind Harmer
-0.066
315652AC1-086 GEN
Solar/Wind Harmer
18.802
3145796HORNRTN
Solar/Wind Harmer
-0.053
3145796HORNRTN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
3130156CHOWAN
Solar/Wind Harmer
-0.016
316319Z2-044 C
Solar/Wind Harmer
0.879
315607AA1-063A GEN
Solar/Wind Harmer
1.601
315816AE2-034 GEN
Solar/Wind Harmer
1.28
3146043SEABORD
Solar/Wind Harmer
-0.016
971443AH1-215 GEN
Solar/Wind Harmer
3.096
3146033SCOT NK
Solar/Wind Harmer
-0.063
3145573BETHELC
Solar/Wind Harmer
-0.016
3145573BETHELC
Solar/Wind Harmer
-0.016
3144303KENBRDG
Solar/Wind Harmer
-0.013
316420AA1-050 GEN
Solar/Wind Harmer
1.787
3130546PLYMOUTH
Solar/Wind Harmer
-0.016
315732AD1-074 GEN1
Solar/Wind Harmer
3.159
315733AD1-074 GEN2
Solar/Wind Harmer
3.159
315735AD1-075 GEN1
Solar/Wind Harmer
1.58
957861AF2-080 GEN
Solar/Wind Harmer
6.812
3146206CASHIE
Solar/Wind Harmer
-0.015
970601AG2-382 GEN
Solar/Wind Harmer
6.746
316005AA1-067
Solar/Wind Harmer
0.312
3145746EVERETS
Solar/Wind Harmer
-0.061
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
970181AG2-120 GEN
Solar/Wind Harmer
2.022
3145683EARLEYS
Solar/Wind Harmer
-0.03
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145513AHOSKIE
Solar/Wind Harmer
0.133
961941AG1-037 GEN
Solar/Wind Harmer
0.115
3145513AHOSKIE
Solar/Wind Harmer
-0.015
970683AG2-441 GEN
Solar/Wind Harmer
11.796
970681AG2-440 GEN
Solar/Wind Harmer
9.436
316318V4-068
Solar/Wind Harmer
0.374
3145893MURPHYS
Solar/Wind Harmer
-0.04
3145893MURPHYS
Solar/Wind Harmer
-0.015
315243AE2-183_GT3
50/50
4.144
3151051BRUNSWICKS1
50/50
6.736
3151021BRUNSWICKG1
50/50
3.245
971451AH1-221 GEN
50/50
9.857
3151531CLOVER1
50/50
4.146
316294AC1-161 GEN
Solar/Wind Harmer
21.122
940641AE2-051 GEN
Solar/Wind Harmer
34.85
970919AG2-571 GEN
Solar/Wind Harmer
8.346
970087AG2-069 GEN
Solar/Wind Harmer
24.586
944591AF1-124 GEN
Solar/Wind Harmer
108.386
957481AF2-042 GEN
Solar/Wind Harmer
72.436
939411AE1-173 GEN
Solar/Wind Harmer
114.333
315693AD1-088 GEN
Solar/Wind Harmer
10.761
962491AG1-098 GEN
Solar/Wind Harmer
14.201
316375AC2-012 GEN
Solar/Wind Harmer
7.061
3150981CHESPKA
Adder
2.267
316388AE2-253 GEN
Solar/Wind Harmer
1.371
315687AD1-152 GEN
Solar/Wind Harmer
2.422
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316023GEN1_S
Solar/Wind Harmer
1.198
960081AF2-299 GEN
Solar/Wind Harmer
1.961
971065AG2-659 GEN
Solar/Wind Harmer
8.708
316129AC1-054 GEN
Solar/Wind Harmer
1.52
971795AH1-408 GEN
Solar/Wind Harmer
13
3147043LAWRENC
Adder
1.392
316237AB2-079_GEN
Solar/Wind Harmer
0.513
970401AG2-262 GEN
Solar/Wind Harmer
1.108
316011AB1-132 GEN
Solar/Wind Harmer
3.497
962571AG1-106 GEN
Solar/Wind Harmer
2.402
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.053
3146516WINFALL
Solar/Wind Harmer
-0.016
316190AA2-174 GEN
Solar/Wind Harmer
0.2
315722AD1-056 GEN
Solar/Wind Harmer
1.696
315800Z1-036_GEN1
Solar/Wind Harmer
3.991
3130156CHOWAN
Solar/Wind Harmer
-0.016
316003AC1-222 GEN
Solar/Wind Harmer
1.563
3146233WITAKRS
Solar/Wind Harmer
-0.063
316359AB2-059 GEN
Solar/Wind Harmer
2.141
316049AB1-081 GEN
Solar/Wind Harmer
1.714
3142053HEARTS
Solar/Wind Harmer
0.187
316212AC1-099_GEN
Solar/Wind Harmer
1.384
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145663CRESWEL
Solar/Wind Harmer
-0.044
971163AH1-040 GEN
Solar/Wind Harmer
14.826
961671AG1-007 GEN
Solar/Wind Harmer
0.199
3146083TARBORO
Solar/Wind Harmer
-0.016
3145493TOT1
Solar/Wind Harmer
0.466
3146263WOODLND
Solar/Wind Harmer
-0.016
316494AC1-189 GEN
Solar/Wind Harmer
1.675
3145963POPLR C
Solar/Wind Harmer
-0.015
3145823KELFORD
Solar/Wind Harmer
-0.015
316174AB2-169 GEN
Solar/Wind Harmer
2.391
3146293MARTNCO
Solar/Wind Harmer
0.096
3146206CASHIE
Solar/Wind Harmer
-0.015
971547AH1-271 GEN
Solar/Wind Harmer
3.855
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
970685AG2-442 GEN
Solar/Wind Harmer
13.211
3145893MURPHYS
Solar/Wind Harmer
-0.06
3145893MURPHYS
Solar/Wind Harmer
0.445
963171AG1-166 GEN
Solar/Wind Harmer
1.819
971563AH1-280 GEN
Solar/Wind Harmer
1.819
3144293JTRSVLE
Adder
0.412
316159AE1-175 C
Solar/Wind Helper
0.502
3138133OCRAN
Solar/Wind Helper
0.143
965291AG1-394 GEN
Solar/Wind Harmer
1.319
946301AF1-294 GEN
Solar/Wind Harmer
3.729
961791AG1-021 GEN
Solar/Wind Harmer
1.819
3146486SUNBURY
Solar/Wind Harmer
-0.014
3146486SUNBURY
Solar/Wind Harmer
-0.014
970865AG2-541 GEN
Solar/Wind Harmer
5.823
315657AE1-056 GEN
Solar/Wind Harmer
5.314
3143316POE
Solar/Wind Harmer
-0.054
270455AD2-022 GEN
Solar/Wind Harmer
2.354
270457AD2-023 GEN
Solar/Wind Harmer
1.194
957831AF2-077 GEN
Solar/Wind Helper
0.384
957601AF2-054 GEN
Solar/Wind Helper
0.326
3141873WAN 176
Solar/Wind Helper
0.049
3141913WHIT STONE
Solar/Wind Helper
0.239
3138133OCRAN
Solar/Wind Helper
0.072
316059AD1-063 C
Solar/Wind Helper
0.24
3141783LANCAST
Solar/Wind Helper
0.142
3141783LANCAST
Solar/Wind Helper
0.094
315662AE1-191 GEN
Solar/Wind Helper
1.261
315666AE1-190 GEN
Solar/Wind Helper
0.315
3151031BRUNSWICKG2
50/50
3.245
970413AG2-270 GEN
50/50
18.093
3151101ELIZAR3
50/50
18.321
315773AC2-141 GEN
Solar/Wind Harmer
27.318
970917AG2-570 GEN
Solar/Wind Harmer
65.93
944581AF1-123 GEN
Solar/Wind Harmer
107.997
944601AF1-125 GEN
Solar/Wind Harmer
106.312
316478AD1-087 GEN
Solar/Wind Harmer
1.883
316486AD2-202 GEN
Solar/Wind Harmer
0.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.424
316320Y1-086
Solar/Wind Harmer
1.072
3144536CHRHLND
Solar/Wind Harmer
-0.003
316365GEN2_N
Solar/Wind Harmer
1.198
966621AG1-532 GEN
Solar/Wind Harmer
0.354
3147043LAWRENC
Solar/Wind Harmer
-0.01
313506AB2-031 GEN
Solar/Wind Harmer
1.365
316248AF1-058 C
Solar/Wind Harmer
0.511
960061AF2-297 GEN
Solar/Wind Harmer
8.482
316131AB2-060 GEN
Solar/Wind Harmer
1.822
3145796HORNRTN
Solar/Wind Harmer
-0.066
3145796HORNRTN
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
964241AG1-285 GEN
Solar/Wind Harmer
12.904
3146516WINFALL
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
315724AD1-057 GEN
Solar/Wind Harmer
0.933
3146376EDENTON
Solar/Wind Harmer
-0.016
970909AG2-566 GEN
Solar/Wind Harmer
1.517
316327AA2-057 GEN
Solar/Wind Harmer
1.611
3146233WITAKRS
Solar/Wind Harmer
0.333
3146233WITAKRS
Solar/Wind Harmer
-0.011
3138543CONSLDL
Solar/Wind Harmer
-0.01
315785AD2-033 C
Solar/Wind Harmer
3.605
961601AG1-000A GEN
Solar/Wind Harmer
6.324
316210AC1-098 GEN
Solar/Wind Harmer
2.492
3145543BTLEBRO
Solar/Wind Harmer
-0.016
3145543BTLEBRO
Solar/Wind Harmer
-0.016
315614AA2-178 GEN
Solar/Wind Harmer
1.706
316435W1029_GEN3
Solar/Wind Harmer
2.865
3146073TAR RVR
Solar/Wind Harmer
-0.016
3146083TARBORO
Solar/Wind Harmer
-0.016
970257AG2-171 GEN
Solar/Wind Harmer
5.879
971157AH1-035 GEN
Solar/Wind Harmer
1.956
3146263WOODLND
Solar/Wind Harmer
-0.016
315737AD1-076 GEN
Solar/Wind Harmer
2.968
316283AC2-100 C
Solar/Wind Harmer
1.463
3145963POPLR C
Solar/Wind Harmer
-0.015
316317KELFORD C
Solar/Wind Harmer
0.731
3145823KELFORD
Solar/Wind Harmer
-0.015
959311AF2-222 GEN
Solar/Wind Harmer
16.19
3145933PARMELE
Solar/Wind Harmer
-0.015
966801AG1-551 GEN
Solar/Wind Harmer
1.929
3146206CASHIE
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
3145746EVERETS
Solar/Wind Harmer
-0.015
316463AE2-346 GEN
Solar/Wind Harmer
0.247
316140AB2-099
Solar/Wind Harmer
0.103
962331AG1-082 GEN
Solar/Wind Harmer
1.905
971683AH1-343 GEN
Solar/Wind Harmer
6.55
3146173TUNIS
Solar/Wind Harmer
-0.015
3156021HOLLOMANSOL
Solar/Wind Harmer
2.039
957521AF2-046 GEN
Solar/Wind Harmer
11.856
961681AG1-008 GEN
Solar/Wind Harmer
11.856
3145893MURPHYS
Solar/Wind Harmer
0.105
3145893MURPHYS
Solar/Wind Harmer
-0.015
3156081AA2-088 GEN
Solar/Wind Harmer
4.785
963181AG1-167 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3147133PAMPLIN
Solar/Wind Harmer
-0.044
971193AH1-056 GEN
Solar/Wind Harmer
8.857
942461AE2-259 GEN
Solar/Wind Harmer
1.967
3145273HOLLAND
Solar/Wind Harmer
-0.01
316382AG1-145 C
Solar/Wind Helper
0.445
316156AD2-030 GEN
Solar/Wind Helper
0.367
316280AD1-041 GEN
Solar/Wind Helper
0.788
316484AD2-074 GEN
Solar/Wind Helper
0.442
316404AE1-155 C
Solar/Wind Helper
1.895
3141766HARMONY
Solar/Wind Helper
0.048
970533AG2-339 GEN
50/50
23.192
970531AG2-338 GEN
50/50
9.277
315242AE2-183_GT2
50/50
4.144
315241AE2-183_GT1
50/50
4.119
972185AH1-677 GEN
50/50
14.94
3151041BRUNSWICKG3
50/50
3.245
972187AH1-678 GEN
50/50
7.448
970933AG2-581 GEN
Solar/Wind Harmer
24.816
970099AG2-077 GEN
Solar/Wind Harmer
28.974
316185AD1-033 GEN
Solar/Wind Harmer
2.226
3145506HICKORY
Solar/Wind Harmer
-0.083
3145506HICKORY
Solar/Wind Harmer
-0.05
3145506HICKORY
Solar/Wind Harmer
-0.012
3142956BIRDNECK
Solar/Wind Harmer
1.104
316316AC1-027 C
Solar/Wind Harmer
0.63
316036AC1-147 C
Solar/Wind Harmer
0.55
3150991CHESPKB
Adder
1.902
3150991CHESPKB
Adder
1.857
316339AD2-160 GEN
Solar/Wind Harmer
1.371
316018AA1-139 ULT2
Solar/Wind Harmer
1.729
316017AA1-139 ULT1
Solar/Wind Harmer
1.633
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.349
3130086AYDLETT
Solar/Wind Harmer
-0.078
3144356SAPONY
Solar/Wind Harmer
0.685
3146386ELIZ CT
Solar/Wind Harmer
-0.018
939181AE1-148 GEN
Solar/Wind Harmer
9.927
971741AH1-377 GEN
Solar/Wind Harmer
20.052
316181AB2-040 GEN
Solar/Wind Harmer
2.37
313527AB2-043 GEN
Solar/Wind Harmer
2.758
962561AG1-105 GEN
Solar/Wind Harmer
9.546
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
964791AG1-342 GEN
Solar/Wind Harmer
3.625
3145796HORNRTN
Solar/Wind Harmer
-0.049
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.016
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
3145593CAROLNA
Solar/Wind Harmer
-0.016
3145593CAROLNA
Solar/Wind Harmer
-0.016
966811AG1-552 GEN
Solar/Wind Harmer
1.856
3145593CAROLNA
Solar/Wind Harmer
0.137
3145783HORNRTN
Solar/Wind Harmer
1.949
3145783HORNRTN
Solar/Wind Harmer
1.559
3145783HORNRTN
Solar/Wind Harmer
0.487
3145783HORNRTN
Solar/Wind Harmer
0.195
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
3146516WINFALL
Solar/Wind Harmer
-0.016
316426AA2-053 GEN
Solar/Wind Harmer
1.645
3146626S HERTFORD
Solar/Wind Harmer
-0.016
3146626S HERTFORD
Solar/Wind Harmer
-0.016
316274AC1-208 GEN
Solar/Wind Harmer
1.732
3146376EDENTON
Solar/Wind Harmer
0.476
3146376EDENTON
Solar/Wind Harmer
0.476
970301AG2-198 GEN
Solar/Wind Harmer
7.988
961601AG1-000A GEN
Solar/Wind Harmer
6.245
316263AC1-034 GEN
Solar/Wind Harmer
7.445
316431W1029_GEN1
Solar/Wind Harmer
2.865
316433W1029_GEN2
Solar/Wind Harmer
2.865
3145493TOT1
Solar/Wind Harmer
0.243
3145453TOT5
Solar/Wind Harmer
0.146
3145603CNETO
Solar/Wind Harmer
0.097
970323AG2-213 GEN
Solar/Wind Harmer
7.839
971775AH1-396 GEN
Solar/Wind Harmer
1.116
316034AC1-036 C
Solar/Wind Harmer
0.291
316222AC1-221 GEN
Solar/Wind Harmer
1.581
316065AD1-022 GEN
Solar/Wind Harmer
7.746
3145933PARMELE
Solar/Wind Harmer
-0.031
3145933PARMELE
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3146173TUNIS
Solar/Wind Harmer
-0.015
3145893MURPHYS
Solar/Wind Harmer
0.419
3145893MURPHYS
Solar/Wind Harmer
-0.027
958211AF2-115 GEN
Solar/Wind Harmer
2.274
963191AG1-168 GEN
Solar/Wind Harmer
1.364
3144293JTRSVLE
Adder
0.412
3144293JTRSVLE
Adder
0.347
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3147133PAMPLIN
Solar/Wind Harmer
-0.011
315742AE1-103 GEN
Solar/Wind Harmer
1.397
316487AF1-042 GEN
Solar/Wind Helper
0.231
NYPJM->LTFIMP_NY
CLTF
1.344
LGEELTFEXP_LGEE->PJM
CLTF
1.186
LAGNLTFEXP_LAGN->PJM
CLTF
6.991
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.32
TVALTFEXP_TVA->PJM
CLTF
3.482
CPLELTFEXP_CPLE->PJM
CLTF
10.401
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.559
CBM West 1LTFEXP_CBM-W1->PJM
CBM
21.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.888
MECLTFEXP_MEC->PJM
CLTF
3.331
SIGELTFEXP_SIGE->PJM
CLTF
0.099

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 568T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 568T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:211.93 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:8350.21
MW Contribution:17.92
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
24.095
970119AG2-088 GEN
50/50
46.768
3150851SPRUNCC
50/50
1.653
3143096IRON208
50/50
1.481
316045AC1-158 PL2
Solar/Wind Harmer
23.52
3143226MDLTHAN
Solar/Wind Harmer
-0.039
3143526WINTERP
Solar/Wind Harmer
-0.201
3142543TWELFTH
Solar/Wind Harmer
-0.004
3147666LOUISA
Solar/Wind Harmer
-0.149
3142416OLDCHRC
Solar/Wind Harmer
-0.097
3142416OLDCHRC
Solar/Wind Harmer
-0.037
940641AE2-051 GEN
Solar/Wind Harmer
34.79
944631AF1-128 GEN
Adder
157.238
315671AE2-027_GEN
Solar/Wind Harmer
27.738
939411AE1-173 GEN
Solar/Wind Harmer
184.612
316294AC1-161 GEN
Solar/Wind Harmer
11.936
970129AG2-093 GEN
Solar/Wind Harmer
8.413
316458AB2-190 GEN2
Solar/Wind Harmer
3.73
971069AG2-661 GEN
Solar/Wind Harmer
5.824
971647AH1-324 GEN
Solar/Wind Harmer
18.353
961611AG1-000B GEN
Solar/Wind Harmer
18.086
316192AB2-158 GEN
Solar/Wind Harmer
4.354
3151171GRAVELC
Adder
3.463
316159AE1-175 C
Solar/Wind Harmer
0.981
3145336SMITFLD
Solar/Wind Harmer
-0.145
944591AF1-124 GEN
Solar/Wind Harmer
166.698
316375AC2-012 GEN
Solar/Wind Harmer
12.618
3150981CHESPKA
Adder
4.052
970659AG2-427 GEN
Solar/Wind Harmer
19.373
966881AG1-559 GEN
Solar/Wind Harmer
0.375
3138126ROCKLANDING
Solar/Wind Harmer
0.112
316381AD1-082 GEN
Solar/Wind Harmer
3.341
970661AG2-428 GEN
Solar/Wind Harmer
38.595
971317AH1-138 GEN
Solar/Wind Harmer
4.533
316388AE2-253 GEN
Solar/Wind Harmer
2.44
316072AD1-144
Solar/Wind Harmer
0.731
3146456SLIGO L269
Solar/Wind Harmer
-0.036
316246AF1-032 C
Solar/Wind Harmer
0.728
316093AE2-104_GEN
Solar/Wind Harmer
10.418
3142433PROV 92
Solar/Wind Harmer
-0.143
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
972197AH1-683 GEN
Adder
6.656
972219AH1-694 GEN
Adder
4.792
3146516WINFALL
Solar/Wind Harmer
-0.114
3146516WINFALL
Solar/Wind Harmer
-0.035
971777AH1-397 GEN
Solar/Wind Harmer
4.114
3141843SHACKLE
Adder
1.591
3141766HARMONY
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
8.589
3130156CHOWAN
Solar/Wind Harmer
-0.034
3143336POWHATN
Solar/Wind Harmer
4.05
3138133OCRAN
Solar/Wind Harmer
-0.02
3145663CRESWEL
Solar/Wind Harmer
-0.094
971163AH1-040 GEN
Solar/Wind Harmer
31.545
970919AG2-571 GEN
Solar/Wind Harmer
10.592
970087AG2-069 GEN
Solar/Wind Harmer
31.254
316023GEN1_S
Solar/Wind Harmer
2.215
961951AG1-038 GEN
Solar/Wind Harmer
4.322
316336AC2-165 C
Solar/Wind Harmer
5.691
3146206CASHIE
Solar/Wind Harmer
-0.033
971547AH1-271 GEN
Solar/Wind Harmer
8.17
3145893MURPHYS
Solar/Wind Harmer
-0.13
3145893MURPHYS
Solar/Wind Harmer
0.967
3152261N ANNA2
50/50
24.093
970497AG2-320 GEN
50/50
31.984
3150861SPRUNCD
50/50
1.653
971645AH1-323 GEN
50/50
29.901
3143096IRON208
50/50
1.481
3143096IRON208
50/50
1.451
316044AC1-158 PL1
Solar/Wind Harmer
7.353
316450AC1-158 RIC
Solar/Wind Harmer
1.961
3147666LOUISA
Solar/Wind Harmer
-0.086
3142416OLDCHRC
Solar/Wind Harmer
3.768
970293AG2-193 GEN
Solar/Wind Harmer
4.65
315839AE2-212 C
Solar/Wind Harmer
1.116
970133AG2-095 GEN
Solar/Wind Harmer
4.162
965281AG1-393 GEN
Solar/Wind Harmer
4.621
3142946ENON
Solar/Wind Harmer
-0.012
315773AC2-141 GEN
Solar/Wind Harmer
15.437
970129AG2-093 GEN
Solar/Wind Harmer
20.77
315778AD1-151 GEN
Solar/Wind Harmer
31.888
315813AE1-149 C
Solar/Wind Harmer
22.914
961611AG1-000B GEN
Solar/Wind Harmer
7.717
3151221GRAVEL6
Adder
23.669
3151171GRAVELC
Adder
4.554
316382AG1-145 C
Solar/Wind Harmer
1.101
3145336SMITFLD
Solar/Wind Harmer
-0.014
944581AF1-123 GEN
Solar/Wind Harmer
166.1
944601AF1-125 GEN
Solar/Wind Harmer
163.508
3144536CHRHLND
Solar/Wind Harmer
-0.006
3151101ELIZAR3
Adder
30.141
970659AG2-427 GEN
Solar/Wind Harmer
3.433
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3144216WINCHST
Adder
1.223
966881AG1-559 GEN
Solar/Wind Harmer
1.096
316083AB2-161 GEN
Solar/Wind Harmer
5.913
3150921YORKTN3
Adder
8.144
970661AG2-428 GEN
Solar/Wind Harmer
6.84
316473AC1-191 GEN
Solar/Wind Harmer
3.887
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.397
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
316320Y1-086
Solar/Wind Harmer
2.093
3150401LDYSMT4
Adder
42.622
3150371LDYSMT1
Adder
41.184
316435W1029_GEN3
Solar/Wind Harmer
6.407
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
3141843SHACKLE
Adder
1.591
316203AE2-005 GEN
Solar/Wind Harmer
14.749
3145273HOLLAND
Solar/Wind Harmer
-0.026
3141766HARMONY
Solar/Wind Harmer
3.112
316280AD1-041 GEN
Solar/Wind Harmer
2.627
316156AD2-030 GEN
Solar/Wind Harmer
0.927
3141873WAN 176
Solar/Wind Harmer
4.119
3146376EDENTON
Solar/Wind Harmer
-0.034
316313AB2-026
Solar/Wind Harmer
0.92
316258AE1-075 C
Solar/Wind Harmer
0.829
316405AF2-144 C
Solar/Wind Harmer
0.874
3143336POWHATN
Solar/Wind Harmer
3.443
315614AA2-178 GEN
Solar/Wind Harmer
3.63
970917AG2-570 GEN
Solar/Wind Harmer
83.678
962971AG1-146 GEN
Solar/Wind Harmer
6.217
971157AH1-035 GEN
Solar/Wind Harmer
4.137
3156081AA2-088 GEN
Solar/Wind Harmer
10.718
315737AD1-076 GEN
Solar/Wind Harmer
6.272
316365GEN2_N
Solar/Wind Harmer
2.215
316484AD2-074 GEN
Solar/Wind Harmer
8.259
970009AG2-005 GEN
Solar/Wind Harmer
4.101
3146206CASHIE
Solar/Wind Harmer
-0.033
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.032
957521AF2-046 GEN
Solar/Wind Harmer
25.606
961681AG1-008 GEN
Solar/Wind Harmer
25.606
3146173TUNIS
Solar/Wind Harmer
-0.032
316404AE1-155 C
Solar/Wind Harmer
6.22
3156021HOLLOMANSOL
Solar/Wind Harmer
4.342
316463AE2-346 GEN
Solar/Wind Harmer
0.52
316140AB2-099
Solar/Wind Harmer
0.217
962331AG1-082 GEN
Solar/Wind Harmer
4.019
966621AG1-532 GEN
Solar/Wind Harmer
0.65
3146263WOODLND
Solar/Wind Harmer
-0.032
313506AB2-031 GEN
Solar/Wind Harmer
2.546
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3145963POPLR C
Solar/Wind Harmer
-0.031
316317KELFORD C
Solar/Wind Harmer
1.48
3145823KELFORD
Solar/Wind Harmer
-0.031
3150351NORNECKC2
Adder
2.817
3147043LAWRENC
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.123
3145796HORNRTN
Solar/Wind Harmer
-0.031
316478AD1-087 GEN
Solar/Wind Harmer
2.676
316486AD2-202 GEN
Solar/Wind Harmer
0.784
3144293JTRSVLE
Adder
0.817
972255AH1-712 GEN
Adder
111.469
3151761LOISA E
Adder
27.223
972183AH1-676 GEN
Adder
213.104
3141316ARNOLDS
Adder
0.364
3150331BIRCHWDA
Adder
22.835
3151861LOWMORA
Adder
1.276
3141196NOKESVL
Solar/Wind Helper
1.408
227287AC2-120 GEN
Solar/Wind Helper
0.371
226910AB2-157 C
Solar/Wind Helper
0.015
237030AB1-096 C
Solar/Wind Helper
0.069
223402AF1-300 C
Solar/Wind Helper
0.373
238221AF1-254 C O1
Solar/Wind Helper
0.245
235067AD1-061 GEN
Solar/Wind Helper
0.438
205917AD1-020 ES
Solar/Wind Helper
0.356
233918AB1-142 GEN
Solar/Wind Helper
0.487
233982AB2-133 GEN
Solar/Wind Helper
0.347
233994AC2-023 GEN
Solar/Wind Helper
0.932
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.492
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
316303AF2-085
50/50
6.236
971285AH1-108 GEN
50/50
2.704
316233AE1-074 FULL
Solar/Wind Harmer
1.044
971281AH1-106 GEN
Solar/Wind Harmer
6.308
971283AH1-107 GEN
Solar/Wind Harmer
6.308
316312AB1-027
Solar/Wind Harmer
1.259
972189AH1-679 GEN
Adder
5.56
316132AB2-190 GEN1
Solar/Wind Harmer
3.73
3143316POE
Solar/Wind Harmer
-0.145
316369SG1_INVT
Solar/Wind Harmer
6.568
315976AC1-164 GENA
Solar/Wind Harmer
38.783
316169AC1-164_GENC
Solar/Wind Harmer
33.504
315975AC1-164 GENB
Solar/Wind Harmer
1.147
972265AH1-717 GEN
Adder
25.277
3151201GRAVEL4
Adder
23.696
3151191GRAVEL3
Adder
23.396
3151211GRAVEL5
Adder
23.396
971445AH1-216 GEN
Solar/Wind Harmer
22.614
3151081ELIZAR1
Adder
29.76
3151091ELIZAR2
Adder
29.243
3152611GOSPORTB
Adder
4.132
3152621GOSPORTC
Adder
3.507
3152601GOSPORTA
Adder
3.235
957871AF2-081 GEN
Solar/Wind Harmer
18.071
315833AF1-017_GEN
Solar/Wind Harmer
6.849
316349AD2-085 GEN
Solar/Wind Harmer
3.207
316311AC2-079 GEN
Solar/Wind Harmer
18.186
319010AE1-072 C
Solar/Wind Harmer
7.291
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
1.085
941031AE2-094 GEN
Solar/Wind Harmer
67.43
944011AF1-069 GEN
Solar/Wind Harmer
21.128
971167AH1-042 GEN
Solar/Wind Harmer
34.583
315835AF2-110_GEN
Solar/Wind Harmer
4.479
3142433PROV 92
Adder
0.62
3142433PROV 92
Adder
0.62
313526AB2-022
Solar/Wind Harmer
0.963
3150411LDYSMT5
Adder
42.755
3150381LDYSMT2
Adder
40.918
972213AH1-691 GEN
Adder
6.922
972215AH1-692 GEN
Adder
6.922
3146486SUNBURY
Solar/Wind Harmer
-0.036
3146486SUNBURY
Solar/Wind Harmer
-0.036
957831AF2-077 GEN
Solar/Wind Harmer
1.07
3138283WHITEMARSH
Solar/Wind Harmer
0.055
316321Z2-027
Solar/Wind Harmer
0.959
3146396TANGLEW
Solar/Wind Harmer
0.654
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
316315AB2-025 C
Solar/Wind Harmer
0.955
970673AG2-436 GEN
Solar/Wind Harmer
74.301
962861AG1-135 GEN
Solar/Wind Harmer
12.147
3146173TUNIS
Solar/Wind Harmer
-0.032
957481AF2-042 GEN
Solar/Wind Harmer
100.212
960081AF2-299 GEN
Solar/Wind Harmer
3.604
3145683EARLEYS
Solar/Wind Harmer
-0.032
3146263WOODLND
Solar/Wind Harmer
-0.032
964211AG1-282 GEN
Solar/Wind Harmer
0.954
3141726DUNNSVL
Solar/Wind Harmer
-0.126
316011AB1-132 GEN
Solar/Wind Harmer
6.592
962571AG1-106 GEN
Solar/Wind Harmer
4.529
3145963POPLR C
Solar/Wind Harmer
-0.031
315693AD1-088 GEN
Solar/Wind Harmer
15.742
971795AH1-408 GEN
Solar/Wind Harmer
23.556
3145823KELFORD
Solar/Wind Harmer
-0.031
962491AG1-098 GEN
Solar/Wind Harmer
20.998
316190AA2-174 GEN
Solar/Wind Harmer
0.385
316174AB2-169 GEN
Solar/Wind Harmer
4.817
3150351NORNECKC2
Adder
2.771
3147043LAWRENC
Adder
2.506
3145783HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.102
3145796HORNRTN
Solar/Wind Harmer
-0.031
3144293JTRSVLE
Adder
0.817
972277AH1-723 GEN
Adder
129.895
3151751LOISA D
Adder
13.353
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.373
237080AD1-060 GEN
Solar/Wind Helper
0.304
237038AE2-054 C
Solar/Wind Helper
0.241
235062AE1-101 C1
Solar/Wind Helper
1.47
966131AG1-482 GEN
Solar/Wind Helper
0.075
233930AB2-032 GEN
Solar/Wind Helper
0.369
233915AB1-141 GEN
Solar/Wind Helper
0.487
232422X3-066 FULL
Solar/Wind Helper
0.111
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.492
232428Y3-058 C
Solar/Wind Helper
0.328
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.113
233972AC1-094 C
Solar/Wind Helper
0.293
238148AE2-230_GEN2
Solar/Wind Helper
0.391
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.126
20720728JCB_W1-129
Solar/Wind Helper
0.055
233971AC1-093 C
Solar/Wind Helper
0.346
238147AE2-230_GEN1
Solar/Wind Helper
0.39
238149AF1-291A_GEN
Solar/Wind Helper
0.111
230430AE1-229_GEN
Solar/Wind Helper
3.256
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.144
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.11
959561AF2-247 GEN
Solar/Wind Helper
0.02
20716028EGP_W2-019
Solar/Wind Helper
0.018
20720828JCB_W4-025
Solar/Wind Helper
0.061
20715028HAN_X4-015
Solar/Wind Helper
0.055
971781AH1-399 GEN
Solar/Wind Harmer
0.994
970673AG2-436 GEN
Solar/Wind Harmer
37.621
3143873LANEXA
Solar/Wind Harmer
-0.021
315814AE2-033 C
Solar/Wind Harmer
32.86
316314AB2-024 C
Solar/Wind Harmer
3.002
316059AD1-063 C
Solar/Wind Harmer
0.79
971967AH1-528 GEN
Solar/Wind Harmer
65.706
315662AE1-191 GEN
Solar/Wind Harmer
4.203
315666AE1-190 GEN
Solar/Wind Harmer
1.051
315611Z1-036_GEN2
Solar/Wind Harmer
8.589
957601AF2-054 GEN
Solar/Wind Harmer
1.038
3141873WAN 176
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.034
3130156CHOWAN
Solar/Wind Harmer
-0.034
3141913WHIT STONE
Solar/Wind Harmer
-0.034
3138133OCRAN
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.02
3141783LANCAST
Solar/Wind Harmer
-0.013
315816AE2-034 GEN
Solar/Wind Harmer
2.723
970085AG2-068 GEN
Solar/Wind Harmer
20.836
970581AG2-369 GEN
Solar/Wind Harmer
17.919
962981AG1-147 GEN
Solar/Wind Harmer
14.507
3130546PLYMOUTH
Solar/Wind Harmer
-0.033
315732AD1-074 GEN1
Solar/Wind Harmer
6.673
315733AD1-074 GEN2
Solar/Wind Harmer
6.673
315735AD1-075 GEN1
Solar/Wind Harmer
3.338
965291AG1-394 GEN
Solar/Wind Harmer
2.918
3146206CASHIE
Solar/Wind Harmer
-0.033
970601AG2-382 GEN
Solar/Wind Harmer
14.298
316318V4-068
Solar/Wind Harmer
0.812
3145893MURPHYS
Solar/Wind Harmer
-0.087
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145513AHOSKIE
Solar/Wind Harmer
0.28
961941AG1-037 GEN
Solar/Wind Harmer
0.242
3145513AHOSKIE
Solar/Wind Harmer
-0.032
946281AF1-292 GEN
Solar/Wind Harmer
0.718
3145683EARLEYS
Solar/Wind Harmer
-0.064
3145683EARLEYS
Solar/Wind Harmer
-0.032
3145683EARLEYS
Solar/Wind Harmer
-0.032
3146043SEABORD
Solar/Wind Harmer
-0.032
315607AA1-063A GEN
Solar/Wind Harmer
3.223
316087AB2-174 GEN
Solar/Wind Harmer
4.534
315652AC1-086 GEN
Solar/Wind Harmer
35.448
3137643SOCKMAN
Solar/Wind Harmer
-0.125
3141813NORNECK
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.012
3146033SCOT NK
Solar/Wind Harmer
-0.123
972205AH1-687 GEN
Adder
9.958
972193AH1-681 GEN
Adder
4.981
3151881LOWMORC
Adder
1.266
3151881LOWMORC
Adder
1.246
3151861LOWMORA
Adder
1.226
316411AF1-147_GEN1
Solar/Wind Helper
1.074
316415AF1-147_GEN2
Solar/Wind Helper
1.074
3138216PACIFIC
Solar/Wind Helper
0.052
237085AD2-009_GEN
Solar/Wind Helper
1.439
238208AF1-136 C
Solar/Wind Helper
0.182
960921AF2-383 GEN
Solar/Wind Helper
0.176
205943AE1-185 GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.231
205932AD2-116_GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.929
233990AG1-397 GEN
Solar/Wind Helper
0.029
234033AF1-007_GEN
Solar/Wind Helper
6.804
232432Z2-076 GEN
Solar/Wind Helper
0.065
238152AF2-075_GEN
Solar/Wind Helper
0.557
959381AF2-229 GEN
Solar/Wind Helper
0.335
964001AG1-254 GEN
Solar/Wind Helper
0.923
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.025
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.024
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.092
20715828PEM_W1-120
Solar/Wind Helper
0.092
971133AH1-012 GEN
50/50
6.863
3142296MT RD221
50/50
1.135
3142366NRTHEST
50/50
1.158
3150691DARBY 3
50/50
25.424
3150701DARBY 4
50/50
25.364
3150681DARBY 2
50/50
25.335
316447AC1-158 HLD
Solar/Wind Harmer
16.169
971223AH1-071 GEN
Solar/Wind Harmer
4.926
3143526WINTERP
Solar/Wind Harmer
-0.201
3150671DARBY 1
Adder
23.848
944641AF1-129 GEN
Adder
157.758
316240AF1-291 C
Solar/Wind Harmer
1.119
316075AC2-137 C
Solar/Wind Harmer
0.997
3142946ENON
Solar/Wind Harmer
-0.004
316033AB2-134 GEN
Solar/Wind Harmer
11.856
315697AD1-025 GEN
Solar/Wind Harmer
7.436
316236AE1-162_GEN
Solar/Wind Harmer
1.101
316036AC1-147 C
Solar/Wind Harmer
0.984
3150991CHESPKB
Adder
3.399
3150991CHESPKB
Adder
3.318
957411AF2-035 GEN
Solar/Wind Harmer
16.399
970317AG2-208 GEN
Solar/Wind Harmer
15.944
316316AC1-027 C
Solar/Wind Harmer
1.117
3142956BIRDNECK
Solar/Wind Harmer
1.953
970657AG2-426 GEN
Solar/Wind Harmer
11.372
970657AG2-426 GEN
Solar/Wind Harmer
2.378
316185AD1-033 GEN
Solar/Wind Harmer
3.837
3145506HICKORY
Solar/Wind Harmer
-0.144
3145506HICKORY
Solar/Wind Harmer
-0.087
3145506HICKORY
Solar/Wind Harmer
-0.022
316339AD2-160 GEN
Solar/Wind Harmer
2.44
315673AE1-157 GEN
Solar/Wind Harmer
27.13
316018AA1-139 ULT2
Solar/Wind Harmer
3.096
316017AA1-139 ULT1
Solar/Wind Harmer
2.925
966871AG1-558 GEN
Solar/Wind Harmer
1.086
966871AG1-558 GEN
Solar/Wind Harmer
0.372
3137176SLIGO L2192
Solar/Wind Harmer
-0.143
3146456SLIGO L269
Solar/Wind Harmer
4.26
3130086AYDLETT
Solar/Wind Harmer
-0.143
3146386ELIZ CT
Solar/Wind Harmer
-0.036
3150391LDYSMT3
Adder
42.542
972195AH1-682 GEN
Adder
5.591
3144356SAPONY
Solar/Wind Harmer
1.235
316431W1029_GEN1
Solar/Wind Harmer
6.407
316433W1029_GEN2
Solar/Wind Harmer
6.407
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.035
972185AH1-677 GEN
Adder
17.515
316441AF1-014 GEN
Solar/Wind Harmer
2.358
972187AH1-678 GEN
Adder
8.788
315742AE1-103 GEN
Solar/Wind Harmer
3.612
3146376EDENTON
Solar/Wind Harmer
1.02
3146376EDENTON
Solar/Wind Harmer
1.02
970933AG2-581 GEN
Solar/Wind Harmer
32.018
316487AF1-042 GEN
Solar/Wind Harmer
4.322
316065AD1-022 GEN
Solar/Wind Harmer
16.398
3145893MURPHYS
Solar/Wind Harmer
0.909
3145893MURPHYS
Solar/Wind Harmer
-0.059
3146173TUNIS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.032
958261AF2-120 GEN
Solar/Wind Harmer
12.494
970099AG2-077 GEN
Solar/Wind Harmer
40.085
316181AB2-040 GEN
Solar/Wind Harmer
4.418
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.031
3142666NORTHAMPTON
Solar/Wind Harmer
-0.019
316426AA2-053 GEN
Solar/Wind Harmer
3.171
3145593CAROLNA
Solar/Wind Harmer
-0.031
3145593CAROLNA
Solar/Wind Harmer
-0.031
966811AG1-552 GEN
Solar/Wind Harmer
3.517
3145593CAROLNA
Solar/Wind Harmer
0.26
316077AC2-138 C
Solar/Wind Harmer
0.659
3150341NORNECKC1
Adder
2.91
3150341NORNECKC1
Adder
2.887
3145783HORNRTN
Solar/Wind Harmer
3.688
3145783HORNRTN
Solar/Wind Harmer
2.95
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.369
3145796HORNRTN
Solar/Wind Harmer
-0.093
316468AD1-105 GEN
Solar/Wind Harmer
3.393
3144293JTRSVLE
Adder
0.817
3144293JTRSVLE
Adder
0.688
3151731LOISA B
Adder
13.353
3151721LOISA A
Adder
13.284
226929AD2-058 GEN
Solar/Wind Helper
0.107
23777801MSM_W1-116
Solar/Wind Helper
0.111
237025AB1-124 C
Solar/Wind Helper
0.161
237006AB1-125 GEN
Solar/Wind Helper
0.121
237034AC2-136 C
Solar/Wind Helper
0.211
23777901MDS_W4-102
Solar/Wind Helper
0.157
235020AA1-095 C
Solar/Wind Helper
0.046
237001AB1-127_GEN
Solar/Wind Helper
0.396
237002AB1-128_GEN
Solar/Wind Helper
0.396
235063AE1-101 C2
Solar/Wind Helper
1.47
238175AF1-290_GEN
Solar/Wind Helper
0.127
238169AE2-226 GEN1
Solar/Wind Helper
0.579
238170AE2-226 GEN2
Solar/Wind Helper
0.579
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
205916AD1-020 GEN
Solar/Wind Helper
1.657
233933AB2-153 GEN
Solar/Wind Helper
0.225
233987AB2-037 GEN
Solar/Wind Helper
2.27
233944AB2-135 GEN
Solar/Wind Helper
0.571
232424Y1-079 C
Solar/Wind Helper
0.113
233946AB2-136 GEN
Solar/Wind Helper
0.551
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.492
232410W1-006 C
Solar/Wind Helper
0.492
233939AC1-091 C
Solar/Wind Helper
0.339
233970AC1-092 C
Solar/Wind Helper
0.339
20390526W1-045 C
Solar/Wind Helper
0.328
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
NYPJM->LTFIMP_NY
CLTF
4.81
LGEELTFEXP_LGEE->PJM
CLTF
2.081
LAGNLTFEXP_LAGN->PJM
CLTF
11.897
WECLTFEXP_WEC->PJM
CLTF
1.018
CBM South 2LTFEXP_CBM-S2->PJM
CBM
36.13
TVALTFEXP_TVA->PJM
CLTF
6.026
CPLELTFEXP_CPLE->PJM
CLTF
16.389
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.285
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.397
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.604
MECLTFEXP_MEC->PJM
CLTF
5.595
SIGELTFEXP_SIGE->PJM
CLTF
0.171

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.6 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5693.43
MW Contribution:13.21
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
59.005
316303AF2-085
50/50
4.624
971285AH1-108 GEN
50/50
1.961
970603AG2-384 GEN
50/50
5.102
316164AC1-076 GEN
Solar/Wind Harmer
2.874
316233AE1-074 FULL
Solar/Wind Harmer
0.766
971281AH1-106 GEN
Solar/Wind Harmer
4.628
971283AH1-107 GEN
Solar/Wind Harmer
4.628
3143316POE
Solar/Wind Harmer
-0.106
316132AB2-190 GEN1
Solar/Wind Harmer
2.695
941031AE2-094 GEN
Solar/Wind Harmer
49.887
944011AF1-069 GEN
Solar/Wind Harmer
15.631
316369SG1_INVT
Solar/Wind Harmer
4.75
3151081ELIZAR1
Adder
21.638
3151091ELIZAR2
Adder
21.263
3152611GOSPORTB
Adder
3.004
3152621GOSPORTC
Adder
2.55
3152601GOSPORTA
Adder
2.352
971445AH1-216 GEN
Solar/Wind Harmer
16.401
316312AB1-027
Solar/Wind Harmer
0.894
972265AH1-717 GEN
Adder
18.309
3151201GRAVEL4
Adder
17.164
3151191GRAVEL3
Adder
16.946
3151211GRAVEL5
Adder
16.946
957871AF2-081 GEN
Solar/Wind Harmer
13.142
315976AC1-164 GENA
Solar/Wind Harmer
27.715
316169AC1-164_GENC
Solar/Wind Harmer
23.943
315975AC1-164 GENB
Solar/Wind Harmer
0.82
315833AF1-017_GEN
Solar/Wind Harmer
4.98
316349AD2-085 GEN
Solar/Wind Harmer
2.332
316311AC2-079 GEN
Solar/Wind Harmer
13.224
319010AE1-072 C
Solar/Wind Harmer
5.302
972189AH1-679 GEN
Adder
3.909
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.789
970673AG2-436 GEN
Solar/Wind Harmer
54.922
970673AG2-436 GEN
Solar/Wind Harmer
27.809
315835AF2-110_GEN
Solar/Wind Harmer
3.257
313526AB2-022
Solar/Wind Harmer
0.701
316315AB2-025 C
Solar/Wind Harmer
0.7
971167AH1-042 GEN
Solar/Wind Harmer
24.945
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.698
3146396TANGLEW
Solar/Wind Harmer
0.476
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
315814AE2-033 C
Solar/Wind Harmer
24.069
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
971967AH1-528 GEN
Solar/Wind Harmer
48.532
957831AF2-077 GEN
Solar/Wind Harmer
0.774
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
316314AB2-024 C
Solar/Wind Harmer
2.168
316059AD1-063 C
Solar/Wind Harmer
0.572
315611Z1-036_GEN2
Solar/Wind Harmer
6.245
315662AE1-191 GEN
Solar/Wind Harmer
3.043
315666AE1-190 GEN
Solar/Wind Harmer
0.761
957601AF2-054 GEN
Solar/Wind Harmer
0.752
3141873WAN 176
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3150411LDYSMT5
Adder
29.791
3150381LDYSMT2
Adder
28.511
972213AH1-691 GEN
Adder
4.823
972215AH1-692 GEN
Adder
4.823
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
970085AG2-068 GEN
Solar/Wind Harmer
15.354
970581AG2-369 GEN
Solar/Wind Harmer
13.205
315816AE2-034 GEN
Solar/Wind Harmer
1.979
962981AG1-147 GEN
Solar/Wind Harmer
10.594
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.85
315733AD1-074 GEN2
Solar/Wind Harmer
4.85
315735AD1-075 GEN1
Solar/Wind Harmer
2.426
965291AG1-394 GEN
Solar/Wind Harmer
2.123
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.393
316318V4-068
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.204
971133AH1-012 GEN
50/50
5.464
944641AF1-129 GEN
50/50
120.961
3142366NRTHEST
50/50
0.827
3150691DARBY 3
50/50
18.162
3150701DARBY 4
50/50
18.119
316447AC1-158 HLD
Solar/Wind Harmer
14.664
971223AH1-071 GEN
Solar/Wind Harmer
3.653
3143526WINTERP
Solar/Wind Harmer
-0.147
316240AF1-291 C
Solar/Wind Harmer
0.81
3150681DARBY 2
Adder
17.056
3150671DARBY 1
Adder
17.036
3142296MT RD221
Adder
0.757
316033AB2-134 GEN
Solar/Wind Harmer
8.573
315697AD1-025 GEN
Solar/Wind Harmer
5.377
316036AC1-147 C
Solar/Wind Harmer
0.715
3150991CHESPKB
Adder
2.471
3150991CHESPKB
Adder
2.412
3142946ENON
Solar/Wind Harmer
-0.003
316236AE1-162_GEN
Solar/Wind Harmer
0.799
316316AC1-027 C
Solar/Wind Harmer
0.813
3142956BIRDNECK
Solar/Wind Harmer
1.42
970657AG2-426 GEN
Solar/Wind Harmer
8.268
970657AG2-426 GEN
Solar/Wind Harmer
1.729
316185AD1-033 GEN
Solar/Wind Harmer
2.79
3145506HICKORY
Solar/Wind Harmer
-0.105
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316075AC2-137 C
Solar/Wind Harmer
0.712
316339AD2-160 GEN
Solar/Wind Harmer
1.774
316018AA1-139 ULT2
Solar/Wind Harmer
2.252
316017AA1-139 ULT1
Solar/Wind Harmer
2.127
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3146456SLIGO L269
Solar/Wind Harmer
3.098
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146386ELIZ CT
Solar/Wind Harmer
-0.026
3144356SAPONY
Solar/Wind Harmer
0.905
972185AH1-677 GEN
Adder
12.941
966871AG1-558 GEN
Solar/Wind Harmer
0.774
966871AG1-558 GEN
Solar/Wind Harmer
0.265
316431W1029_GEN1
Solar/Wind Harmer
4.659
316433W1029_GEN2
Solar/Wind Harmer
4.659
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.489
957411AF2-035 GEN
Solar/Wind Harmer
11.475
970317AG2-208 GEN
Solar/Wind Harmer
11.157
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
316441AF1-014 GEN
Solar/Wind Harmer
1.706
315673AE1-157 GEN
Solar/Wind Harmer
18.955
970933AG2-581 GEN
Solar/Wind Harmer
23.615
315742AE1-103 GEN
Solar/Wind Harmer
2.627
3146376EDENTON
Solar/Wind Harmer
0.741
3146376EDENTON
Solar/Wind Harmer
0.741
3150391LDYSMT3
Adder
29.642
972195AH1-682 GEN
Adder
3.895
316487AF1-042 GEN
Solar/Wind Harmer
3.162
316065AD1-022 GEN
Solar/Wind Harmer
11.919
3145893MURPHYS
Solar/Wind Harmer
0.662
3145893MURPHYS
Solar/Wind Harmer
-0.043
958261AF2-120 GEN
Solar/Wind Harmer
9.168
970099AG2-077 GEN
Solar/Wind Harmer
29.447
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.22
316077AC2-138 C
Solar/Wind Harmer
0.486
3150341NORNECKC1
Adder
2.147
3150341NORNECKC1
Adder
2.13
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.308
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.56
3145593CAROLNA
Solar/Wind Harmer
0.189
3145783HORNRTN
Solar/Wind Harmer
2.684
3145783HORNRTN
Solar/Wind Harmer
2.147
3145783HORNRTN
Solar/Wind Harmer
0.671
3145783HORNRTN
Solar/Wind Harmer
0.268
3145796HORNRTN
Solar/Wind Harmer
-0.067
3144293JTRSVLE
Adder
0.594
3144293JTRSVLE
Adder
0.5
3151731LOISA B
Adder
10.119
3151721LOISA A
Adder
10.067
316468AD1-105 GEN
Solar/Wind Harmer
1.252
3152251N ANNA1
50/50
19.45
971507AH1-251 GEN
50/50
16.115
970119AG2-088 GEN
50/50
34.68
3150851SPRUNCC
50/50
1.198
3143096IRON208
50/50
1.065
316045AC1-158 PL2
Solar/Wind Harmer
21.331
3147666LOUISA
Solar/Wind Harmer
-0.117
3143226MDLTHAN
Solar/Wind Harmer
-0.029
316192AB2-158 GEN
Solar/Wind Harmer
3.431
3143526WINTERP
Solar/Wind Harmer
-0.147
940641AE2-051 GEN
Solar/Wind Harmer
25.691
939411AE1-173 GEN
Solar/Wind Harmer
135.819
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.675
315671AE2-027_GEN
Solar/Wind Harmer
20.092
970129AG2-093 GEN
Solar/Wind Harmer
6.077
316458AB2-190 GEN2
Solar/Wind Harmer
2.695
944631AF1-128 GEN
Adder
112.977
971069AG2-661 GEN
Solar/Wind Harmer
4.21
944591AF1-124 GEN
Solar/Wind Harmer
121.264
971647AH1-324 GEN
Solar/Wind Harmer
13.278
961611AG1-000B GEN
Solar/Wind Harmer
13.092
316375AC2-012 GEN
Solar/Wind Harmer
9.174
3150981CHESPKA
Adder
2.946
970659AG2-427 GEN
Solar/Wind Harmer
14.084
3145336SMITFLD
Solar/Wind Harmer
-0.105
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
3151171GRAVELC
Adder
2.508
316381AD1-082 GEN
Solar/Wind Harmer
2.429
970661AG2-428 GEN
Solar/Wind Harmer
28.06
3138126ROCKLANDING
Solar/Wind Harmer
0.081
316388AE2-253 GEN
Solar/Wind Harmer
1.774
316159AE1-175 C
Solar/Wind Harmer
0.706
316072AD1-144
Solar/Wind Harmer
0.531
3146456SLIGO L269
Solar/Wind Harmer
-0.026
316246AF1-032 C
Solar/Wind Harmer
0.53
971317AH1-138 GEN
Solar/Wind Harmer
3.272
316093AE2-104_GEN
Solar/Wind Harmer
7.576
3142433PROV 92
Solar/Wind Harmer
-0.103
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
966881AG1-559 GEN
Solar/Wind Harmer
0.262
971777AH1-397 GEN
Solar/Wind Harmer
2.977
3141843SHACKLE
Adder
1.151
3141766HARMONY
Solar/Wind Harmer
-0.005
315800Z1-036_GEN1
Solar/Wind Harmer
6.245
3143336POWHATN
Solar/Wind Harmer
2.977
3130156CHOWAN
Solar/Wind Harmer
-0.025
972197AH1-683 GEN
Adder
4.637
972219AH1-694 GEN
Adder
3.339
3138133OCRAN
Solar/Wind Harmer
-0.015
970919AG2-571 GEN
Solar/Wind Harmer
7.807
970087AG2-069 GEN
Solar/Wind Harmer
23.032
3145663CRESWEL
Solar/Wind Harmer
-0.068
971163AH1-040 GEN
Solar/Wind Harmer
22.931
316336AC2-165 C
Solar/Wind Harmer
4.171
961951AG1-038 GEN
Solar/Wind Harmer
3.162
316023GEN1_S
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
5.939
962861AG1-135 GEN
Solar/Wind Harmer
8.906
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.704
957481AF2-042 GEN
Solar/Wind Harmer
73.619
3146173TUNIS
Solar/Wind Harmer
-0.023
960081AF2-299 GEN
Solar/Wind Harmer
2.629
964211AG1-282 GEN
Solar/Wind Harmer
0.702
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3145683EARLEYS
Solar/Wind Harmer
-0.023
3146263WOODLND
Solar/Wind Harmer
-0.023
315693AD1-088 GEN
Solar/Wind Harmer
11.547
3150351NORNECKC2
Adder
2.044
962491AG1-098 GEN
Solar/Wind Harmer
15.398
316011AB1-132 GEN
Solar/Wind Harmer
4.801
962571AG1-106 GEN
Solar/Wind Harmer
3.298
971795AH1-408 GEN
Solar/Wind Harmer
17.176
3145963POPLR C
Solar/Wind Harmer
-0.023
316190AA2-174 GEN
Solar/Wind Harmer
0.281
3145823KELFORD
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.498
3147043LAWRENC
Adder
1.827
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
3151751LOISA D
Adder
10.119
972277AH1-723 GEN
Adder
86.298
316006AB2-029 C
Solar/Wind Helper
0.108
961941AG1-037 GEN
Solar/Wind Harmer
0.176
3145513AHOSKIE
Solar/Wind Harmer
-0.023
946281AF1-292 GEN
Solar/Wind Harmer
0.523
3146043SEABORD
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.345
316087AB2-174 GEN
Solar/Wind Harmer
3.305
3141813NORNECK
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.813
3137643SOCKMAN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.009
972205AH1-687 GEN
Adder
7.173
972193AH1-681 GEN
Adder
3.309
316411AF1-147_GEN1
Solar/Wind Helper
0.769
316415AF1-147_GEN2
Solar/Wind Helper
0.769
3138216PACIFIC
Solar/Wind Helper
0.038
3152261N ANNA2
50/50
19.448
3150861SPRUNCD
50/50
1.198
3143096IRON208
50/50
1.065
3143096IRON208
50/50
1.043
316044AC1-158 PL1
Solar/Wind Harmer
6.668
316450AC1-158 RIC
Solar/Wind Harmer
1.778
3147666LOUISA
Solar/Wind Harmer
-0.067
315839AE2-212 C
Solar/Wind Harmer
0.81
315773AC2-141 GEN
Solar/Wind Harmer
11.22
965281AG1-393 GEN
Solar/Wind Harmer
3.35
970133AG2-095 GEN
Solar/Wind Harmer
3.004
315813AE1-149 C
Solar/Wind Harmer
16.657
970129AG2-093 GEN
Solar/Wind Harmer
15.004
315778AD1-151 GEN
Solar/Wind Harmer
23.05
944581AF1-123 GEN
Solar/Wind Harmer
120.829
944601AF1-125 GEN
Solar/Wind Harmer
118.944
970293AG2-193 GEN
Solar/Wind Harmer
3.321
3151101ELIZAR3
Adder
21.915
961611AG1-000B GEN
Solar/Wind Harmer
5.586
3144536CHRHLND
Solar/Wind Harmer
-0.004
3142946ENON
Solar/Wind Harmer
-0.009
970659AG2-427 GEN
Solar/Wind Harmer
2.496
3145336SMITFLD
Solar/Wind Harmer
-0.01
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3142416OLDCHRC
Solar/Wind Harmer
2.673
3151221GRAVEL6
Adder
17.144
3151171GRAVELC
Adder
3.298
316083AB2-161 GEN
Solar/Wind Harmer
4.299
970661AG2-428 GEN
Solar/Wind Harmer
4.973
3144216WINCHST
Adder
0.884
3150921YORKTN3
Adder
5.882
316382AG1-145 C
Solar/Wind Harmer
0.792
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.198
316320Y1-086
Solar/Wind Harmer
1.522
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
316473AC1-191 GEN
Solar/Wind Harmer
2.772
316435W1029_GEN3
Solar/Wind Harmer
4.659
3146516WINFALL
Solar/Wind Harmer
-0.026
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141843SHACKLE
Adder
1.151
316203AE2-005 GEN
Solar/Wind Harmer
10.672
3141766HARMONY
Solar/Wind Harmer
2.25
316280AD1-041 GEN
Solar/Wind Harmer
1.902
316156AD2-030 GEN
Solar/Wind Harmer
0.672
3141873WAN 176
Solar/Wind Harmer
2.985
316313AB2-026
Solar/Wind Harmer
0.677
316258AE1-075 C
Solar/Wind Harmer
0.609
316405AF2-144 C
Solar/Wind Harmer
0.643
3143336POWHATN
Solar/Wind Harmer
2.53
3146376EDENTON
Solar/Wind Harmer
-0.025
3150401LDYSMT4
Adder
29.698
3150371LDYSMT1
Adder
28.696
970917AG2-570 GEN
Solar/Wind Harmer
61.676
315614AA2-178 GEN
Solar/Wind Harmer
2.639
962971AG1-146 GEN
Solar/Wind Harmer
4.54
971157AH1-035 GEN
Solar/Wind Harmer
3.007
3156081AA2-088 GEN
Solar/Wind Harmer
7.797
316484AD2-074 GEN
Solar/Wind Harmer
6.042
970009AG2-005 GEN
Solar/Wind Harmer
3
315737AD1-076 GEN
Solar/Wind Harmer
4.558
316365GEN2_N
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
316404AE1-155 C
Solar/Wind Harmer
4.564
957521AF2-046 GEN
Solar/Wind Harmer
18.624
961681AG1-008 GEN
Solar/Wind Harmer
18.624
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.157
316463AE2-346 GEN
Solar/Wind Harmer
0.378
316140AB2-099
Solar/Wind Harmer
0.158
962331AG1-082 GEN
Solar/Wind Harmer
2.922
966621AG1-532 GEN
Solar/Wind Harmer
0.474
3146263WOODLND
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.855
3150351NORNECKC2
Adder
2.079
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.076
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.962
316486AD2-202 GEN
Solar/Wind Harmer
0.574
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
3151761LOISA E
Adder
20.63
972183AH1-676 GEN
Adder
160.944
972255AH1-712 GEN
Adder
74.056
3141316ARNOLDS
Adder
0.31
3150331BIRCHWDA
Adder
20.259
3141196NOKESVL
Solar/Wind Helper
0.97
NYPJM->LTFIMP_NY
CLTF
3.258
LAGNLTFEXP_LAGN->PJM
CLTF
7.753
LGEELTFEXP_LGEE->PJM
CLTF
1.156
WECLTFEXP_WEC->PJM
CLTF
0.544
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.482
TVALTFEXP_TVA->PJM
CLTF
3.93
CPLELTFEXP_CPLE->PJM
CLTF
11.751
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.921
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.526
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.238
MECLTFEXP_MEC->PJM
CLTF
3.227
SIGELTFEXP_SIGE->PJM
CLTF
0.097

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 574T575_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 574T575_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:179.37 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:7067.14
MW Contribution:15.26
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
30.744
970119AG2-088 GEN
50/50
39.456
3151791S ANNAG2
50/50
0.958
3151781S ANNAS1
50/50
0.492
315243AE2-183_GT3
50/50
4.407
3151051BRUNSWICKS1
50/50
7.204
3151021BRUNSWICKG1
50/50
3.471
971451AH1-221 GEN
50/50
10.542
3151741LOISA C
50/50
0.984
3151751LOISA D
50/50
17.992
316045AC1-158 PL2
Solar/Wind Harmer
27.219
3147666LOUISA
Solar/Wind Harmer
-0.19
316192AB2-158 GEN
Solar/Wind Harmer
5.545
3143226MDLTHAN
Solar/Wind Harmer
-0.033
940641AE2-051 GEN
Solar/Wind Harmer
29.235
3143526WINTERP
Solar/Wind Harmer
-0.157
939411AE1-173 GEN
Solar/Wind Harmer
151.543
3143336POWHATN
Solar/Wind Harmer
3.431
970919AG2-571 GEN
Solar/Wind Harmer
9.022
970087AG2-069 GEN
Solar/Wind Harmer
26.614
316294AC1-161 GEN
Solar/Wind Harmer
9.062
944591AF1-124 GEN
Solar/Wind Harmer
127.089
316336AC2-165 C
Solar/Wind Harmer
4.826
316375AC2-012 GEN
Solar/Wind Harmer
9.564
3150981CHESPKA
Adder
3.071
316388AE2-253 GEN
Solar/Wind Harmer
1.858
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316246AF1-032 C
Solar/Wind Harmer
0.555
970659AG2-427 GEN
Solar/Wind Harmer
14.512
316381AD1-082 GEN
Solar/Wind Harmer
2.505
970661AG2-428 GEN
Solar/Wind Harmer
29.016
316093AE2-104_GEN
Solar/Wind Harmer
7.933
3150851SPRUNCC
Adder
1.117
957481AF2-042 GEN
Solar/Wind Harmer
85.059
316072AD1-144
Solar/Wind Harmer
0.549
3145336SMITFLD
Solar/Wind Harmer
-0.107
3146516WINFALL
Solar/Wind Harmer
-0.087
3146516WINFALL
Solar/Wind Harmer
-0.027
315800Z1-036_GEN1
Solar/Wind Harmer
6.597
315693AD1-088 GEN
Solar/Wind Harmer
13.348
962491AG1-098 GEN
Solar/Wind Harmer
17.806
3151171GRAVELC
Adder
2.519
3130156CHOWAN
Solar/Wind Harmer
-0.026
315671AE2-027_GEN
Solar/Wind Harmer
19.85
961611AG1-000B GEN
Solar/Wind Harmer
13.059
971647AH1-324 GEN
Solar/Wind Harmer
13.175
316023GEN1_S
Solar/Wind Harmer
1.771
971133AH1-012 GEN
50/50
8.748
970533AG2-339 GEN
50/50
24.369
970531AG2-338 GEN
50/50
9.748
315242AE2-183_GT2
50/50
4.407
315241AE2-183_GT1
50/50
4.38
972185AH1-677 GEN
50/50
15.889
3151041BRUNSWICKG3
50/50
3.471
972187AH1-678 GEN
50/50
7.965
3151731LOISA B
50/50
17.992
3151721LOISA A
50/50
17.899
316447AC1-158 HLD
Solar/Wind Harmer
18.712
971223AH1-071 GEN
Solar/Wind Harmer
4.156
3143526WINTERP
Solar/Wind Harmer
-0.157
970933AG2-581 GEN
Solar/Wind Harmer
27.317
3144356SAPONY
Solar/Wind Harmer
0.989
966001AG1-469 GEN
Solar/Wind Harmer
0.532
316185AD1-033 GEN
Solar/Wind Harmer
2.919
3142956BIRDNECK
Solar/Wind Harmer
1.484
316316AC1-027 C
Solar/Wind Harmer
0.849
316036AC1-147 C
Solar/Wind Harmer
0.746
316303AF2-085
50/50
5.261
315244AE2-183_ST
50/50
7.62
963041AG1-153 GEN
50/50
7.028
315779AE2-040
50/50
3.522
316164AC1-076 GEN
Solar/Wind Harmer
2.938
941031AE2-094 GEN
Solar/Wind Harmer
57.754
944011AF1-069 GEN
Solar/Wind Harmer
18.096
316233AE1-074 FULL
Solar/Wind Harmer
0.818
971281AH1-106 GEN
Solar/Wind Harmer
4.94
971283AH1-107 GEN
Solar/Wind Harmer
4.94
970673AG2-436 GEN
Solar/Wind Harmer
63.56
970673AG2-436 GEN
Solar/Wind Harmer
32.182
971967AH1-528 GEN
Solar/Wind Harmer
56.158
970085AG2-068 GEN
Solar/Wind Harmer
17.743
970581AG2-369 GEN
Solar/Wind Harmer
15.259
316315AB2-025 C
Solar/Wind Harmer
0.765
315814AE2-033 C
Solar/Wind Harmer
26.3
3143316POE
Solar/Wind Harmer
-0.11
3151081ELIZAR1
Adder
22.573
3151091ELIZAR2
Adder
22.181
3152611GOSPORTB
Adder
3.132
3152621GOSPORTC
Adder
2.658
3152601GOSPORTA
Adder
2.452
957871AF2-081 GEN
Solar/Wind Harmer
13.769
319010AE1-072 C
Solar/Wind Harmer
5.558
3147346CASHSCORNER
Solar/Wind Harmer
0.425
3146406KITTY HAWK
Solar/Wind Harmer
0.023
316305AF2-043 C
Solar/Wind Harmer
0.826
315833AF1-017_GEN
Solar/Wind Harmer
5.184
316349AD2-085 GEN
Solar/Wind Harmer
2.427
316311AC2-079 GEN
Solar/Wind Harmer
13.767
315835AF2-110_GEN
Solar/Wind Harmer
3.41
313526AB2-022
Solar/Wind Harmer
0.736
971285AH1-108 GEN
Adder
1.828
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
316321Z2-027
Solar/Wind Harmer
0.733
3146396TANGLEW
Solar/Wind Harmer
0.5
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
971445AH1-216 GEN
Solar/Wind Harmer
16.689
315611Z1-036_GEN2
Solar/Wind Harmer
6.597
972265AH1-717 GEN
Adder
18.385
3151201GRAVEL4
Adder
17.235
3151191GRAVEL3
Adder
17.017
3151211GRAVEL5
Adder
17.017
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
316369SG1_INVT
Solar/Wind Harmer
4.688
315816AE2-034 GEN
Solar/Wind Harmer
2.107
971069AG2-661 GEN
Solar/Wind Harmer
4.138
3145663CRESWEL
Solar/Wind Harmer
-0.073
971163AH1-040 GEN
Solar/Wind Harmer
24.415
316458AB2-190 GEN2
Solar/Wind Harmer
2.633
970129AG2-093 GEN
Solar/Wind Harmer
5.931
960081AF2-299 GEN
Solar/Wind Harmer
2.896
3138126ROCKLANDING
Solar/Wind Harmer
0.079
3142543TWELFTH
Solar/Wind Harmer
-0.002
3145893MURPHYS
Solar/Wind Harmer
-0.102
3145893MURPHYS
Solar/Wind Harmer
0.759
3146206CASHIE
Solar/Wind Harmer
-0.025
971547AH1-271 GEN
Solar/Wind Harmer
6.373
971795AH1-408 GEN
Solar/Wind Harmer
19.052
3146173TUNIS
Solar/Wind Harmer
-0.025
3147043LAWRENC
Adder
2.033
3145683EARLEYS
Solar/Wind Harmer
-0.025
316011AB1-132 GEN
Solar/Wind Harmer
5.258
962571AG1-106 GEN
Solar/Wind Harmer
3.612
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
316190AA2-174 GEN
Solar/Wind Harmer
0.307
971317AH1-138 GEN
Solar/Wind Harmer
3.127
970937AG2-583 GEN
Solar/Wind Harmer
17.864
3145783HORNRTN
Solar/Wind Harmer
-0.025
316159AE1-175 C
Solar/Wind Harmer
0.666
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.081
3145796HORNRTN
Solar/Wind Harmer
-0.025
944631AF1-128 GEN
Adder
104.9
3145963POPLR C
Solar/Wind Harmer
-0.025
315687AD1-152 GEN
Solar/Wind Harmer
2.961
316174AB2-169 GEN
Solar/Wind Harmer
3.783
316129AC1-054 GEN
Solar/Wind Harmer
2.143
971065AG2-659 GEN
Solar/Wind Harmer
12.198
3146926FARMVIL
Solar/Wind Harmer
-0.014
963171AG1-166 GEN
Solar/Wind Harmer
3.025
971563AH1-280 GEN
Solar/Wind Harmer
3.025
3144293JTRSVLE
Adder
0.686
970685AG2-442 GEN
Solar/Wind Harmer
21.155
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.557
972277AH1-723 GEN
Adder
72.107
3152261N ANNA2
50/50
30.741
3151771S ANNAG1
50/50
0.958
3151801S ANNAS2
50/50
0.492
3151031BRUNSWICKG2
50/50
3.471
3151761LOISA E
50/50
36.68
972183AH1-676 GEN
50/50
287.058
316044AC1-158 PL1
Solar/Wind Harmer
8.509
316450AC1-158 RIC
Solar/Wind Harmer
2.269
3147666LOUISA
Solar/Wind Harmer
-0.109
316313AB2-026
Solar/Wind Harmer
0.78
316258AE1-075 C
Solar/Wind Harmer
0.702
316405AF2-144 C
Solar/Wind Harmer
0.741
3143336POWHATN
Solar/Wind Harmer
2.916
970917AG2-570 GEN
Solar/Wind Harmer
71.277
315773AC2-141 GEN
Solar/Wind Harmer
11.72
944581AF1-123 GEN
Solar/Wind Harmer
126.633
944601AF1-125 GEN
Solar/Wind Harmer
124.656
3151101ELIZAR3
Adder
22.862
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.351
3144536CHRHLND
Solar/Wind Harmer
-0.004
315813AE1-149 C
Solar/Wind Harmer
17.079
970659AG2-427 GEN
Solar/Wind Harmer
2.572
316083AB2-161 GEN
Solar/Wind Harmer
4.433
970661AG2-428 GEN
Solar/Wind Harmer
5.142
316320Y1-086
Solar/Wind Harmer
1.598
3132273ORANGE
Solar/Wind Harmer
-0.005
3150861SPRUNCD
Adder
1.117
316435W1029_GEN3
Solar/Wind Harmer
4.902
315839AE2-212 C
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3145336SMITFLD
Solar/Wind Harmer
-0.011
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3145273HOLLAND
Solar/Wind Harmer
-0.02
965281AG1-393 GEN
Solar/Wind Harmer
3.333
3151221GRAVEL6
Adder
17.215
3151171GRAVELC
Adder
3.312
3146376EDENTON
Solar/Wind Harmer
-0.026
961611AG1-000B GEN
Solar/Wind Harmer
5.572
316365GEN2_N
Solar/Wind Harmer
1.771
315778AD1-151 GEN
Solar/Wind Harmer
22.655
316478AD1-087 GEN
Solar/Wind Harmer
2.264
316486AD2-202 GEN
Solar/Wind Harmer
0.663
315614AA2-178 GEN
Solar/Wind Harmer
2.81
970129AG2-093 GEN
Solar/Wind Harmer
14.642
3156081AA2-088 GEN
Solar/Wind Harmer
8.385
970133AG2-095 GEN
Solar/Wind Harmer
2.902
3144216WINCHST
Adder
0.865
966621AG1-532 GEN
Solar/Wind Harmer
0.522
971157AH1-035 GEN
Solar/Wind Harmer
3.215
315737AD1-076 GEN
Solar/Wind Harmer
4.877
3150921YORKTN3
Adder
5.73
3145893MURPHYS
Solar/Wind Harmer
0.178
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
20.091
961681AG1-008 GEN
Solar/Wind Harmer
20.091
3146206CASHIE
Solar/Wind Harmer
-0.025
313506AB2-031 GEN
Solar/Wind Harmer
2.041
3146173TUNIS
Solar/Wind Harmer
-0.025
970909AG2-566 GEN
Solar/Wind Harmer
2.403
316463AE2-346 GEN
Solar/Wind Harmer
0.409
316140AB2-099
Solar/Wind Harmer
0.17
962331AG1-082 GEN
Solar/Wind Harmer
3.158
3156021HOLLOMANSOL
Solar/Wind Harmer
3.402
3147043LAWRENC
Solar/Wind Harmer
-0.015
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3146263WOODLND
Solar/Wind Harmer
-0.025
3143096IRON208
Adder
0.935
3143096IRON208
Adder
0.916
316382AG1-145 C
Solar/Wind Harmer
0.748
316317KELFORD C
Solar/Wind Harmer
1.169
3145823KELFORD
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.099
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145963POPLR C
Solar/Wind Harmer
-0.025
3142946ENON
Solar/Wind Harmer
-0.008
3146926FARMVIL
Solar/Wind Harmer
-0.014
942461AE2-259 GEN
Solar/Wind Harmer
3.644
3147133PAMPLIN
Solar/Wind Harmer
-0.076
971193AH1-056 GEN
Solar/Wind Harmer
15.132
963181AG1-167 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
3141843SHACKLE
Adder
1.013
3150351NORNECKC2
Adder
1.583
972255AH1-712 GEN
Adder
61.879
3141196NOKESVL
Solar/Wind Helper
1.074
959311AF2-222 GEN
Solar/Wind Harmer
12.268
3150991CHESPKB
Adder
2.576
3150991CHESPKB
Adder
2.515
3145506HICKORY
Solar/Wind Harmer
-0.11
3145506HICKORY
Solar/Wind Harmer
-0.066
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.858
316018AA1-139 ULT2
Solar/Wind Harmer
2.359
316017AA1-139 ULT1
Solar/Wind Harmer
2.228
3137176SLIGO L2192
Solar/Wind Harmer
-0.109
3146456SLIGO L269
Solar/Wind Harmer
3.247
3130086AYDLETT
Solar/Wind Harmer
-0.109
970657AG2-426 GEN
Solar/Wind Harmer
8.535
970657AG2-426 GEN
Solar/Wind Harmer
1.785
3146386ELIZ CT
Solar/Wind Harmer
-0.027
970099AG2-077 GEN
Solar/Wind Harmer
34.024
316431W1029_GEN1
Solar/Wind Harmer
4.902
316433W1029_GEN2
Solar/Wind Harmer
4.902
316236AE1-162_GEN
Solar/Wind Harmer
0.814
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146516WINFALL
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
3146626S HERTFORD
Solar/Wind Harmer
-0.027
315742AE1-103 GEN
Solar/Wind Harmer
2.783
3146376EDENTON
Solar/Wind Harmer
0.785
3146376EDENTON
Solar/Wind Harmer
0.785
316240AF1-291 C
Solar/Wind Harmer
0.795
316033AB2-134 GEN
Solar/Wind Harmer
8.462
315697AD1-025 GEN
Solar/Wind Harmer
5.307
944641AF1-129 GEN
Adder
111.019
971741AH1-377 GEN
Solar/Wind Harmer
29.798
3145893MURPHYS
Solar/Wind Harmer
0.713
3145893MURPHYS
Solar/Wind Harmer
-0.046
316065AD1-022 GEN
Solar/Wind Harmer
12.776
316181AB2-040 GEN
Solar/Wind Harmer
3.542
3146173TUNIS
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
12.658
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
316426AA2-053 GEN
Solar/Wind Harmer
2.529
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.813
3145593CAROLNA
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
2.949
3145783HORNRTN
Solar/Wind Harmer
2.359
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.295
3145796HORNRTN
Solar/Wind Harmer
-0.074
3142946ENON
Solar/Wind Harmer
-0.002
3147133PAMPLIN
Solar/Wind Harmer
-0.024
3147133PAMPLIN
Solar/Wind Harmer
-0.019
958211AF2-115 GEN
Solar/Wind Harmer
3.781
963191AG1-168 GEN
Solar/Wind Harmer
2.268
3144293JTRSVLE
Adder
0.686
3144293JTRSVLE
Adder
0.577
3142366NRTHEST
Adder
0.692
3150691DARBY 3
Adder
15.167
3150701DARBY 4
Adder
15.132
3150681DARBY 2
Adder
15.114
3150671DARBY 1
Adder
15.096
3142296MT RD221
Adder
0.621
3150341NORNECKC1
Adder
1.636
3150341NORNECKC1
Adder
1.623
226929AD2-058 GEN
Solar/Wind Helper
0.087
316132AB2-190 GEN1
Solar/Wind Harmer
2.633
965291AG1-394 GEN
Solar/Wind Harmer
2.286
946281AF1-292 GEN
Solar/Wind Harmer
0.577
3130546PLYMOUTH
Solar/Wind Harmer
-0.026
315732AD1-074 GEN1
Solar/Wind Harmer
5.189
315733AD1-074 GEN2
Solar/Wind Harmer
5.189
315735AD1-075 GEN1
Solar/Wind Harmer
2.595
316318V4-068
Solar/Wind Harmer
0.637
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.025
316087AB2-174 GEN
Solar/Wind Harmer
3.638
3146206CASHIE
Solar/Wind Harmer
-0.025
970601AG2-382 GEN
Solar/Wind Harmer
11.153
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.556
3145513AHOSKIE
Solar/Wind Harmer
0.22
961941AG1-037 GEN
Solar/Wind Harmer
0.19
3145513AHOSKIE
Solar/Wind Harmer
-0.025
3137643SOCKMAN
Solar/Wind Harmer
-0.1
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
315652AC1-086 GEN
Solar/Wind Harmer
28.271
3145796HORNRTN
Solar/Wind Harmer
-0.079
3145796HORNRTN
Solar/Wind Harmer
-0.01
970831AG2-522 GEN
Solar/Wind Harmer
12.25
3146033SCOT NK
Solar/Wind Harmer
-0.097
315657AE1-056 GEN
Solar/Wind Harmer
9.079
946301AF1-294 GEN
Solar/Wind Harmer
6.2
961791AG1-021 GEN
Solar/Wind Harmer
3.025
970683AG2-441 GEN
Solar/Wind Harmer
18.888
970681AG2-440 GEN
Solar/Wind Harmer
15.111
3142433PROV 92
Adder
0.401
3142433PROV 92
Adder
0.401
972205AH1-687 GEN
Adder
8.511
972189AH1-679 GEN
Adder
2.2
972193AH1-681 GEN
Adder
2.765
316411AF1-147_GEN1
Solar/Wind Helper
0.849
316415AF1-147_GEN2
Solar/Wind Helper
0.849
3138216PACIFIC
Solar/Wind Helper
0.042
NYPJM->LTFIMP_NY
CLTF
3.877
LAGNLTFEXP_LAGN->PJM
CLTF
9.308
LGEELTFEXP_LGEE->PJM
CLTF
1.536
WECLTFEXP_WEC->PJM
CLTF
0.747
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.279
TVALTFEXP_TVA->PJM
CLTF
4.707
CPLELTFEXP_CPLE->PJM
CLTF
13.402
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.993
CBM West 1LTFEXP_CBM-W1->PJM
CBM
24.945
CBM South 1LTFEXP_CBM-S1->PJM
CBM
16.004
MECLTFEXP_MEC->PJM
CLTF
4.2
SIGELTFEXP_SIGE->PJM
CLTF
0.127

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6078.79
MW Contribution:13.48
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
3152251N ANNA1
50/50
19.951
971507AH1-251 GEN
50/50
16.627
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.079
3152331SURRY 2
50/50
9.986
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.057
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.585
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3150801HOPHCF4
50/50
1.421
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
316044AC1-158 PL1
Solar/Wind Harmer
6.895
316450AC1-158 RIC
Solar/Wind Harmer
1.839
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.408
965281AG1-393 GEN
Solar/Wind Harmer
3.401
970133AG2-095 GEN
Solar/Wind Harmer
3.047
315813AE1-149 C
Solar/Wind Harmer
16.929
970129AG2-093 GEN
Solar/Wind Harmer
15.225
944581AF1-123 GEN
Solar/Wind Harmer
122.873
944601AF1-125 GEN
Solar/Wind Harmer
120.955
315778AD1-151 GEN
Solar/Wind Harmer
23.395
3151101ELIZAR3
Adder
22.283
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.537
961611AG1-000B GEN
Solar/Wind Harmer
5.672
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.37
3151221GRAVEL6
Adder
17.41
3151171GRAVELC
Adder
3.35
970293AG2-193 GEN
Solar/Wind Harmer
3.361
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.055
3142416OLDCHRC
Solar/Wind Harmer
2.704
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.252
3150921YORKTN3
Adder
5.966
316382AG1-145 C
Solar/Wind Harmer
0.803
316320Y1-086
Solar/Wind Harmer
1.548
316435W1029_GEN3
Solar/Wind Harmer
4.74
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.794
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.658
3143336POWHATN
Solar/Wind Harmer
2.59
3141843SHACKLE
Adder
1.161
316203AE2-005 GEN
Solar/Wind Harmer
10.766
3141766HARMONY
Solar/Wind Harmer
2.27
316280AD1-041 GEN
Solar/Wind Harmer
1.918
966881AG1-559 GEN
Solar/Wind Harmer
0.765
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.01
970917AG2-570 GEN
Solar/Wind Harmer
62.97
315614AA2-178 GEN
Solar/Wind Harmer
2.688
3150401LDYSMT4
Adder
29.389
3150371LDYSMT1
Adder
28.398
971157AH1-035 GEN
Solar/Wind Harmer
3.064
3156081AA2-088 GEN
Solar/Wind Harmer
7.946
316365GEN2_N
Solar/Wind Harmer
1.648
315737AD1-076 GEN
Solar/Wind Harmer
4.644
962971AG1-146 GEN
Solar/Wind Harmer
4.559
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.984
961681AG1-008 GEN
Solar/Wind Harmer
18.984
316484AD2-074 GEN
Solar/Wind Harmer
6.061
970009AG2-005 GEN
Solar/Wind Harmer
3.009
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.218
966621AG1-532 GEN
Solar/Wind Harmer
0.484
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.979
316404AE1-155 C
Solar/Wind Harmer
4.57
3146263WOODLND
Solar/Wind Harmer
-0.024
313506AB2-031 GEN
Solar/Wind Harmer
1.893
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.098
3145823KELFORD
Solar/Wind Harmer
-0.023
971531AH1-263 GEN
50/50
60.398
316303AF2-085
50/50
4.712
971285AH1-108 GEN
50/50
1.991
970603AG2-384 GEN
50/50
5.178
316164AC1-076 GEN
Solar/Wind Harmer
3.019
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.708
971283AH1-107 GEN
Solar/Wind Harmer
4.708
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.888
944011AF1-069 GEN
Solar/Wind Harmer
15.945
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
316369SG1_INVT
Solar/Wind Harmer
4.821
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.663
972265AH1-717 GEN
Adder
18.594
3151201GRAVEL4
Adder
17.43
3151191GRAVEL3
Adder
17.21
3151211GRAVEL5
Adder
17.21
316312AB1-027
Solar/Wind Harmer
0.904
957871AF2-081 GEN
Solar/Wind Harmer
13.366
970673AG2-436 GEN
Solar/Wind Harmer
56.037
970673AG2-436 GEN
Solar/Wind Harmer
28.373
315833AF1-017_GEN
Solar/Wind Harmer
5.064
316349AD2-085 GEN
Solar/Wind Harmer
2.371
319010AE1-072 C
Solar/Wind Harmer
5.393
316311AC2-079 GEN
Solar/Wind Harmer
13.447
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.803
315976AC1-164 GENA
Solar/Wind Harmer
28.04
316169AC1-164_GENC
Solar/Wind Harmer
24.224
315975AC1-164 GENB
Solar/Wind Harmer
0.83
315835AF2-110_GEN
Solar/Wind Harmer
3.313
316315AB2-025 C
Solar/Wind Harmer
0.713
313526AB2-022
Solar/Wind Harmer
0.713
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.529
315814AE2-033 C
Solar/Wind Harmer
24.517
316321Z2-027
Solar/Wind Harmer
0.71
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.215
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
957831AF2-077 GEN
Solar/Wind Harmer
0.783
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.355
316314AB2-024 C
Solar/Wind Harmer
2.187
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.069
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.759
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.677
970581AG2-369 GEN
Solar/Wind Harmer
13.482
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.016
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.481
3150381LDYSMT2
Adder
28.214
972213AH1-691 GEN
Adder
4.773
972215AH1-692 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.942
315733AD1-074 GEN2
Solar/Wind Harmer
4.942
315735AD1-075 GEN1
Solar/Wind Harmer
2.472
965291AG1-394 GEN
Solar/Wind Harmer
2.164
962981AG1-147 GEN
Solar/Wind Harmer
10.637
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.591
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.392
316087AB2-174 GEN
Solar/Wind Harmer
3.373
315652AC1-086 GEN
Solar/Wind Harmer
26.336
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.416
972193AH1-681 GEN
Adder
3.397
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
3138216PACIFIC
Solar/Wind Helper
0.04
971133AH1-012 GEN
50/50
5.665
944641AF1-129 GEN
50/50
122.768
3142366NRTHEST
50/50
0.838
970533AG2-339 GEN
50/50
21.472
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3150761HOPPOLC
50/50
0.62
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
15.163
971223AH1-071 GEN
Solar/Wind Harmer
3.723
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.822
3150701DARBY 4
Adder
17.29
3150681DARBY 2
Adder
17.27
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.703
315697AD1-025 GEN
Solar/Wind Harmer
5.458
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
316236AE1-162_GEN
Solar/Wind Harmer
0.812
3142956BIRDNECK
Solar/Wind Harmer
1.444
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.837
970657AG2-426 GEN
Solar/Wind Harmer
8.405
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.804
316018AA1-139 ULT2
Solar/Wind Harmer
2.29
316017AA1-139 ULT1
Solar/Wind Harmer
2.163
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3146456SLIGO L269
Solar/Wind Harmer
3.151
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
0.922
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.74
316433W1029_GEN2
Solar/Wind Harmer
4.74
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.182
939411AE1-173 GEN
Solar/Wind Harmer
138.344
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.821
315671AE2-027_GEN
Solar/Wind Harmer
20.395
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
944591AF1-124 GEN
Solar/Wind Harmer
123.316
971069AG2-661 GEN
Solar/Wind Harmer
4.273
944631AF1-128 GEN
Adder
114.478
316375AC2-012 GEN
Solar/Wind Harmer
9.327
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
13.48
970659AG2-427 GEN
Solar/Wind Harmer
14.317
961611AG1-000B GEN
Solar/Wind Harmer
13.293
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.469
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
28.527
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.027
316388AE2-253 GEN
Solar/Wind Harmer
1.804
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
316246AF1-032 C
Solar/Wind Harmer
0.539
971317AH1-138 GEN
Solar/Wind Harmer
3.316
316093AE2-104_GEN
Solar/Wind Harmer
7.706
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.355
3143336POWHATN
Solar/Wind Harmer
3.047
971777AH1-397 GEN
Solar/Wind Harmer
3.003
3141843SHACKLE
Adder
1.161
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.262
970919AG2-571 GEN
Solar/Wind Harmer
7.971
970087AG2-069 GEN
Solar/Wind Harmer
23.516
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.353
972197AH1-683 GEN
Adder
4.589
972219AH1-694 GEN
Adder
3.304
316336AC2-165 C
Solar/Wind Harmer
4.275
316023GEN1_S
Solar/Wind Harmer
1.648
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.052
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.252
961951AG1-038 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.682
962861AG1-135 GEN
Solar/Wind Harmer
8.922
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
3146263WOODLND
Solar/Wind Harmer
-0.024
962491AG1-098 GEN
Solar/Wind Harmer
15.753
316011AB1-132 GEN
Solar/Wind Harmer
4.898
962571AG1-106 GEN
Solar/Wind Harmer
3.365
971795AH1-408 GEN
Solar/Wind Harmer
17.538
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.866
316174AB2-169 GEN
Solar/Wind Harmer
3.568
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.041
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.898
972277AH1-723 GEN
Adder
88.606
316478AD1-087 GEN
Solar/Wind Harmer
2.006
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
972255AH1-712 GEN
Adder
76.037
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
966871AG1-558 GEN
Solar/Wind Harmer
0.781
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.111
315742AE1-103 GEN
Solar/Wind Harmer
2.675
316441AF1-014 GEN
Solar/Wind Harmer
1.721
957411AF2-035 GEN
Solar/Wind Harmer
11.447
970317AG2-208 GEN
Solar/Wind Harmer
11.129
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
315673AE1-157 GEN
Solar/Wind Harmer
18.853
3150391LDYSMT3
Adder
29.334
972195AH1-682 GEN
Adder
3.855
316065AD1-022 GEN
Solar/Wind Harmer
12.145
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.101
316487AF1-042 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.18
316181AB2-040 GEN
Solar/Wind Harmer
3.285
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.355
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.613
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.74
3145783HORNRTN
Solar/Wind Harmer
2.192
3145783HORNRTN
Solar/Wind Harmer
0.685
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.898
3151721LOISA A
Adder
10.842
971741AH1-377 GEN
Solar/Wind Harmer
1.355
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.01 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6067.89
MW Contribution:13.47
Bus #Bus NameTypeMW Contribution
971531AH1-263 GEN
50/50
60.354
316303AF2-085
50/50
4.709
971285AH1-108 GEN
50/50
1.989
970603AG2-384 GEN
50/50
5.174
316164AC1-076 GEN
Solar/Wind Harmer
3.016
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971281AH1-106 GEN
Solar/Wind Harmer
4.705
971283AH1-107 GEN
Solar/Wind Harmer
4.705
3143316POE
Solar/Wind Harmer
-0.107
941031AE2-094 GEN
Solar/Wind Harmer
50.85
944011AF1-069 GEN
Solar/Wind Harmer
15.933
316132AB2-190 GEN1
Solar/Wind Harmer
2.733
316369SG1_INVT
Solar/Wind Harmer
4.818
3151081ELIZAR1
Adder
21.985
3151091ELIZAR2
Adder
21.603
3152611GOSPORTB
Adder
3.052
3152621GOSPORTC
Adder
2.591
3152601GOSPORTA
Adder
2.39
971445AH1-216 GEN
Solar/Wind Harmer
16.65
972265AH1-717 GEN
Adder
18.58
3151201GRAVEL4
Adder
17.417
3151191GRAVEL3
Adder
17.197
3151211GRAVEL5
Adder
17.197
316312AB1-027
Solar/Wind Harmer
0.903
957871AF2-081 GEN
Solar/Wind Harmer
13.355
970673AG2-436 GEN
Solar/Wind Harmer
55.995
970673AG2-436 GEN
Solar/Wind Harmer
28.352
315833AF1-017_GEN
Solar/Wind Harmer
5.061
316349AD2-085 GEN
Solar/Wind Harmer
2.37
319010AE1-072 C
Solar/Wind Harmer
5.389
316311AC2-079 GEN
Solar/Wind Harmer
13.437
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.802
315976AC1-164 GENA
Solar/Wind Harmer
28.019
316169AC1-164_GENC
Solar/Wind Harmer
24.206
315975AC1-164 GENB
Solar/Wind Harmer
0.829
315835AF2-110_GEN
Solar/Wind Harmer
3.311
316315AB2-025 C
Solar/Wind Harmer
0.712
313526AB2-022
Solar/Wind Harmer
0.712
972189AH1-679 GEN
Adder
3.929
3146486SUNBURY
Solar/Wind Harmer
-0.026
3152261N ANNA2
50/50
19.936
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
3150801HOPHCF4
50/50
1.42
971211AH1-065 GEN
50/50
1.713
3151161SURRY 1
50/50
9.192
316044AC1-158 PL1
Solar/Wind Harmer
6.891
316450AC1-158 RIC
Solar/Wind Harmer
1.837
3147666LOUISA
Solar/Wind Harmer
-0.07
315839AE2-212 C
Solar/Wind Harmer
0.822
315773AC2-141 GEN
Solar/Wind Harmer
11.4
965281AG1-393 GEN
Solar/Wind Harmer
3.399
970133AG2-095 GEN
Solar/Wind Harmer
3.045
315813AE1-149 C
Solar/Wind Harmer
16.916
970129AG2-093 GEN
Solar/Wind Harmer
15.214
944581AF1-123 GEN
Solar/Wind Harmer
122.781
944601AF1-125 GEN
Solar/Wind Harmer
120.864
315778AD1-151 GEN
Solar/Wind Harmer
23.378
3151101ELIZAR3
Adder
22.266
3144536CHRHLND
Solar/Wind Harmer
-0.004
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
2.535
961611AG1-000B GEN
Solar/Wind Harmer
5.668
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.366
3151221GRAVEL6
Adder
17.397
3151171GRAVELC
Adder
3.347
970293AG2-193 GEN
Solar/Wind Harmer
3.359
3142946ENON
Solar/Wind Harmer
-0.009
970661AG2-428 GEN
Solar/Wind Harmer
5.052
3142416OLDCHRC
Solar/Wind Harmer
2.702
3144216WINCHST
Adder
0.896
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.25
3150921YORKTN3
Adder
5.961
316382AG1-145 C
Solar/Wind Harmer
0.802
316320Y1-086
Solar/Wind Harmer
1.547
316435W1029_GEN3
Solar/Wind Harmer
4.736
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.026
316473AC1-191 GEN
Solar/Wind Harmer
2.792
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3145273HOLLAND
Solar/Wind Harmer
-0.019
316313AB2-026
Solar/Wind Harmer
0.692
316258AE1-075 C
Solar/Wind Harmer
0.623
316405AF2-144 C
Solar/Wind Harmer
0.657
3143336POWHATN
Solar/Wind Harmer
2.588
3141843SHACKLE
Adder
1.16
316203AE2-005 GEN
Solar/Wind Harmer
10.758
3141766HARMONY
Solar/Wind Harmer
2.268
316280AD1-041 GEN
Solar/Wind Harmer
1.917
966881AG1-559 GEN
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
316156AD2-030 GEN
Solar/Wind Harmer
0.677
3141873WAN 176
Solar/Wind Harmer
3.008
971133AH1-012 GEN
50/50
5.661
944641AF1-129 GEN
50/50
122.675
3142366NRTHEST
50/50
0.837
970533AG2-339 GEN
50/50
21.455
970531AG2-338 GEN
50/50
8.582
3150781HOPHCF2
50/50
0.977
3150791HOPHCF3
50/50
0.977
3152251N ANNA1
50/50
19.938
971507AH1-251 GEN
50/50
16.616
970119AG2-088 GEN
50/50
35.315
3150851SPRUNCC
50/50
1.216
3143096IRON208
50/50
1.078
3152331SURRY 2
50/50
9.978
3150771HOPHCF1
50/50
0.977
316045AC1-158 PL2
Solar/Wind Harmer
22.043
3147666LOUISA
Solar/Wind Harmer
-0.123
316192AB2-158 GEN
Solar/Wind Harmer
3.583
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.162
939411AE1-173 GEN
Solar/Wind Harmer
138.24
3142543TWELFTH
Solar/Wind Harmer
-0.003
316294AC1-161 GEN
Solar/Wind Harmer
8.814
315671AE2-027_GEN
Solar/Wind Harmer
20.38
970129AG2-093 GEN
Solar/Wind Harmer
6.163
316458AB2-190 GEN2
Solar/Wind Harmer
2.733
944591AF1-124 GEN
Solar/Wind Harmer
123.223
971069AG2-661 GEN
Solar/Wind Harmer
4.27
944631AF1-128 GEN
Adder
114.392
316375AC2-012 GEN
Solar/Wind Harmer
9.32
3150981CHESPKA
Adder
2.993
971647AH1-324 GEN
Solar/Wind Harmer
13.47
970659AG2-427 GEN
Solar/Wind Harmer
14.306
961611AG1-000B GEN
Solar/Wind Harmer
13.283
3145336SMITFLD
Solar/Wind Harmer
-0.107
316381AD1-082 GEN
Solar/Wind Harmer
2.467
3151171GRAVELC
Adder
2.545
970661AG2-428 GEN
Solar/Wind Harmer
28.505
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
316388AE2-253 GEN
Solar/Wind Harmer
1.803
3138126ROCKLANDING
Solar/Wind Harmer
0.082
3146456SLIGO L269
Solar/Wind Harmer
-0.027
316072AD1-144
Solar/Wind Harmer
0.539
316159AE1-175 C
Solar/Wind Harmer
0.714
316246AF1-032 C
Solar/Wind Harmer
0.538
971317AH1-138 GEN
Solar/Wind Harmer
3.313
316093AE2-104_GEN
Solar/Wind Harmer
7.7
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.351
3143336POWHATN
Solar/Wind Harmer
3.045
971777AH1-397 GEN
Solar/Wind Harmer
3
3141843SHACKLE
Adder
1.16
3141766HARMONY
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
966881AG1-559 GEN
Solar/Wind Harmer
0.261
970919AG2-571 GEN
Solar/Wind Harmer
7.965
970087AG2-069 GEN
Solar/Wind Harmer
23.498
3138133OCRAN
Solar/Wind Harmer
-0.015
3145663CRESWEL
Solar/Wind Harmer
-0.069
971163AH1-040 GEN
Solar/Wind Harmer
23.335
972197AH1-683 GEN
Adder
4.586
972219AH1-694 GEN
Adder
3.302
316336AC2-165 C
Solar/Wind Harmer
4.272
316023GEN1_S
Solar/Wind Harmer
1.647
3146206CASHIE
Solar/Wind Harmer
-0.024
971547AH1-271 GEN
Solar/Wind Harmer
6.047
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
957481AF2-042 GEN
Solar/Wind Harmer
75.195
961951AG1-038 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
960081AF2-299 GEN
Solar/Wind Harmer
2.68
962861AG1-135 GEN
Solar/Wind Harmer
8.916
3145683EARLEYS
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.802
3146263WOODLND
Solar/Wind Harmer
-0.023
962491AG1-098 GEN
Solar/Wind Harmer
15.74
316011AB1-132 GEN
Solar/Wind Harmer
4.894
962571AG1-106 GEN
Solar/Wind Harmer
3.363
971795AH1-408 GEN
Solar/Wind Harmer
17.524
3145963POPLR C
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Adder
1.864
316174AB2-169 GEN
Solar/Wind Harmer
3.565
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.039
3144293JTRSVLE
Adder
0.609
3151751LOISA D
Adder
10.888
972277AH1-723 GEN
Adder
88.526
3150761HOPPOLC
50/50
0.619
971213AH1-066 GEN
50/50
0.857
3150691DARBY 3
50/50
18.376
316447AC1-158 HLD
Solar/Wind Harmer
15.154
971223AH1-071 GEN
Solar/Wind Harmer
3.72
3143526WINTERP
Solar/Wind Harmer
-0.15
316240AF1-291 C
Solar/Wind Harmer
0.821
3150701DARBY 4
Adder
17.277
3150681DARBY 2
Adder
17.257
3150671DARBY 1
Adder
17.237
3142296MT RD221
Adder
0.765
316033AB2-134 GEN
Solar/Wind Harmer
8.696
315697AD1-025 GEN
Solar/Wind Harmer
5.454
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.451
316236AE1-162_GEN
Solar/Wind Harmer
0.811
3142956BIRDNECK
Solar/Wind Harmer
1.443
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.835
970657AG2-426 GEN
Solar/Wind Harmer
8.398
970657AG2-426 GEN
Solar/Wind Harmer
1.756
3142946ENON
Solar/Wind Harmer
-0.003
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.803
316018AA1-139 ULT2
Solar/Wind Harmer
2.288
316017AA1-139 ULT1
Solar/Wind Harmer
2.161
316075AC2-137 C
Solar/Wind Harmer
0.72
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3146456SLIGO L269
Solar/Wind Harmer
3.148
3130086AYDLETT
Solar/Wind Harmer
-0.106
972185AH1-677 GEN
Adder
13.195
3144356SAPONY
Solar/Wind Harmer
0.921
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.736
316433W1029_GEN2
Solar/Wind Harmer
4.736
972187AH1-678 GEN
Adder
6.618
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.78
966871AG1-558 GEN
Solar/Wind Harmer
0.267
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
970933AG2-581 GEN
Solar/Wind Harmer
24.093
315742AE1-103 GEN
Solar/Wind Harmer
2.673
316441AF1-014 GEN
Solar/Wind Harmer
1.72
957411AF2-035 GEN
Solar/Wind Harmer
11.438
970317AG2-208 GEN
Solar/Wind Harmer
11.12
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
315673AE1-157 GEN
Solar/Wind Harmer
18.839
3150391LDYSMT3
Adder
29.312
972195AH1-682 GEN
Adder
3.852
316065AD1-022 GEN
Solar/Wind Harmer
12.136
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
970099AG2-077 GEN
Solar/Wind Harmer
30.078
316487AF1-042 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.173
316181AB2-040 GEN
Solar/Wind Harmer
3.283
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
2.354
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.611
3145593CAROLNA
Solar/Wind Harmer
0.193
3145783HORNRTN
Solar/Wind Harmer
2.737
3145783HORNRTN
Solar/Wind Harmer
2.19
3145783HORNRTN
Solar/Wind Harmer
0.684
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.125
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3151731LOISA B
Adder
10.888
3151721LOISA A
Adder
10.832
971741AH1-377 GEN
Solar/Wind Harmer
1.353
3146486SUNBURY
Solar/Wind Harmer
-0.026
971967AH1-528 GEN
Solar/Wind Harmer
49.492
315814AE2-033 C
Solar/Wind Harmer
24.499
316321Z2-027
Solar/Wind Harmer
0.709
3146396TANGLEW
Solar/Wind Harmer
0.484
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
971167AH1-042 GEN
Solar/Wind Harmer
25.196
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
957831AF2-077 GEN
Solar/Wind Harmer
0.782
3138283WHITEMARSH
Solar/Wind Harmer
0.04
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.351
316314AB2-024 C
Solar/Wind Harmer
2.185
316059AD1-063 C
Solar/Wind Harmer
0.576
315662AE1-191 GEN
Solar/Wind Harmer
3.067
315666AE1-190 GEN
Solar/Wind Harmer
0.767
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
957601AF2-054 GEN
Solar/Wind Harmer
0.758
3141873WAN 176
Solar/Wind Harmer
-0.005
970085AG2-068 GEN
Solar/Wind Harmer
15.665
970581AG2-369 GEN
Solar/Wind Harmer
13.472
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.014
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150411LDYSMT5
Adder
29.459
3150381LDYSMT2
Adder
28.193
972213AH1-691 GEN
Adder
4.769
972215AH1-692 GEN
Adder
4.769
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315732AD1-074 GEN1
Solar/Wind Harmer
4.938
315733AD1-074 GEN2
Solar/Wind Harmer
4.938
315735AD1-075 GEN1
Solar/Wind Harmer
2.47
965291AG1-394 GEN
Solar/Wind Harmer
2.162
962981AG1-147 GEN
Solar/Wind Harmer
10.629
3146206CASHIE
Solar/Wind Harmer
-0.024
970601AG2-382 GEN
Solar/Wind Harmer
10.583
316318V4-068
Solar/Wind Harmer
0.602
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
946281AF1-292 GEN
Solar/Wind Harmer
0.534
3145513AHOSKIE
Solar/Wind Harmer
0.208
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3145513AHOSKIE
Solar/Wind Harmer
-0.024
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.391
316087AB2-174 GEN
Solar/Wind Harmer
3.37
970917AG2-570 GEN
Solar/Wind Harmer
62.922
315614AA2-178 GEN
Solar/Wind Harmer
2.686
3150401LDYSMT4
Adder
29.367
3150371LDYSMT1
Adder
28.377
971157AH1-035 GEN
Solar/Wind Harmer
3.061
3156081AA2-088 GEN
Solar/Wind Harmer
7.94
316365GEN2_N
Solar/Wind Harmer
1.647
315737AD1-076 GEN
Solar/Wind Harmer
4.641
962971AG1-146 GEN
Solar/Wind Harmer
4.555
3146206CASHIE
Solar/Wind Harmer
-0.024
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.97
961681AG1-008 GEN
Solar/Wind Harmer
18.97
316484AD2-074 GEN
Solar/Wind Harmer
6.056
970009AG2-005 GEN
Solar/Wind Harmer
3.007
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.215
966621AG1-532 GEN
Solar/Wind Harmer
0.483
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.161
962331AG1-082 GEN
Solar/Wind Harmer
2.977
316404AE1-155 C
Solar/Wind Harmer
4.567
3146263WOODLND
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.892
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
316317KELFORD C
Solar/Wind Harmer
1.097
3145823KELFORD
Solar/Wind Harmer
-0.023
3147043LAWRENC
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
2.005
316486AD2-202 GEN
Solar/Wind Harmer
0.587
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.074
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.198
972183AH1-676 GEN
Adder
173.63
972255AH1-712 GEN
Adder
75.968
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.139
315652AC1-086 GEN
Solar/Wind Harmer
26.316
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
3141813NORNECK
Solar/Wind Harmer
-0.023
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.409
972193AH1-681 GEN
Adder
3.394
316411AF1-147_GEN1
Solar/Wind Helper
0.818
316415AF1-147_GEN2
Solar/Wind Helper
0.818
3138216PACIFIC
Solar/Wind Helper
0.04
NYPJM->LTFIMP_NY
CLTF
3.429
LGEELTFEXP_LGEE->PJM
CLTF
1.289
LAGNLTFEXP_LAGN->PJM
CLTF
8.194
WECLTFEXP_WEC->PJM
CLTF
0.615
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.289
TVALTFEXP_TVA->PJM
CLTF
4.152
CPLELTFEXP_CPLE->PJM
CLTF
12.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.692
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.053
MECLTFEXP_MEC->PJM
CLTF
3.551
SIGELTFEXP_SIGE->PJM
CLTF
0.108

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P2-2: MORRISVILLE B1_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: MORRISVILLE B1_SRT-S
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:140.84 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:4391.4
MW Contribution:10.2
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
2.467
316233AE1-074 FULL
Solar/Wind Harmer
0.578
971281AH1-106 GEN
Solar/Wind Harmer
3.494
971283AH1-107 GEN
Solar/Wind Harmer
3.494
941031AE2-094 GEN
Solar/Wind Harmer
38.562
944011AF1-069 GEN
Solar/Wind Harmer
12.083
970673AG2-436 GEN
Solar/Wind Harmer
42.445
970673AG2-436 GEN
Solar/Wind Harmer
21.491
3143316POE
Solar/Wind Harmer
-0.079
971967AH1-528 GEN
Solar/Wind Harmer
37.503
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.531
957871AF2-081 GEN
Solar/Wind Harmer
9.796
315814AE2-033 C
Solar/Wind Harmer
18.244
971445AH1-216 GEN
Solar/Wind Harmer
12.122
319010AE1-072 C
Solar/Wind Harmer
3.953
3146406KITTY HAWK
Solar/Wind Harmer
0.016
315833AF1-017_GEN
Solar/Wind Harmer
3.709
316349AD2-085 GEN
Solar/Wind Harmer
1.737
316311AC2-079 GEN
Solar/Wind Harmer
9.849
316305AF2-043 C
Solar/Wind Harmer
0.588
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
3.482
316132AB2-190 GEN1
Solar/Wind Harmer
1.97
315835AF2-110_GEN
Solar/Wind Harmer
2.429
313526AB2-022
Solar/Wind Harmer
0.523
3146486SUNBURY
Solar/Wind Harmer
-0.019
3146486SUNBURY
Solar/Wind Harmer
-0.019
316321Z2-027
Solar/Wind Harmer
0.521
3146396TANGLEW
Solar/Wind Harmer
0.355
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
11.856
970581AG2-369 GEN
Solar/Wind Harmer
10.196
315611Z1-036_GEN2
Solar/Wind Harmer
4.669
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
19.666
316169AC1-164_GENC
Solar/Wind Harmer
16.99
315975AC1-164 GENB
Solar/Wind Harmer
0.582
316312AB1-027
Solar/Wind Harmer
0.626
957831AF2-077 GEN
Solar/Wind Harmer
0.558
3138283WHITEMARSH
Solar/Wind Harmer
0.029
971167AH1-042 GEN
Solar/Wind Harmer
17.862
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
1.484
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
316314AB2-024 C
Solar/Wind Harmer
1.54
965291AG1-394 GEN
Solar/Wind Harmer
1.598
315732AD1-074 GEN1
Solar/Wind Harmer
3.642
315733AD1-074 GEN2
Solar/Wind Harmer
3.642
315735AD1-075 GEN1
Solar/Wind Harmer
1.821
315662AE1-191 GEN
Solar/Wind Harmer
2.168
315666AE1-190 GEN
Solar/Wind Harmer
0.542
316059AD1-063 C
Solar/Wind Harmer
0.406
957601AF2-054 GEN
Solar/Wind Harmer
0.536
3141873WAN 176
Solar/Wind Harmer
-0.004
316318V4-068
Solar/Wind Harmer
0.445
3145893MURPHYS
Solar/Wind Harmer
-0.048
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
7.812
946281AF1-292 GEN
Solar/Wind Harmer
0.397
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.154
961941AG1-037 GEN
Solar/Wind Harmer
0.132
3145513AHOSKIE
Solar/Wind Harmer
-0.018
3146043SEABORD
Solar/Wind Harmer
-0.018
316087AB2-174 GEN
Solar/Wind Harmer
2.508
3138133OCRAN
Solar/Wind Harmer
-0.005
315607AA1-063A GEN
Solar/Wind Harmer
1.773
3145683EARLEYS
Solar/Wind Harmer
-0.035
3145683EARLEYS
Solar/Wind Harmer
-0.017
3145683EARLEYS
Solar/Wind Harmer
-0.017
3141783LANCAST
Solar/Wind Harmer
-0.01
3141783LANCAST
Solar/Wind Harmer
-0.007
315652AC1-086 GEN
Solar/Wind Harmer
19.55
3137643SOCKMAN
Solar/Wind Harmer
-0.069
3145796HORNRTN
Solar/Wind Harmer
-0.054
3145796HORNRTN
Solar/Wind Harmer
-0.007
962981AG1-147 GEN
Solar/Wind Harmer
7.478
3146033SCOT NK
Solar/Wind Harmer
-0.067
970831AG2-522 GEN
Solar/Wind Harmer
8.348
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
972205AH1-687 GEN
Adder
5.595
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
6.723
316450AC1-158 RIC
Solar/Wind Harmer
1.793
3147666LOUISA
Solar/Wind Harmer
-0.06
315773AC2-141 GEN
Solar/Wind Harmer
8.348
315839AE2-212 C
Solar/Wind Harmer
0.598
944581AF1-123 GEN
Solar/Wind Harmer
90.063
944601AF1-125 GEN
Solar/Wind Harmer
88.657
315813AE1-149 C
Solar/Wind Harmer
12.369
965281AG1-393 GEN
Solar/Wind Harmer
2.467
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.196
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.019
971153AH1-033 GEN
Solar/Wind Harmer
2.384
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.106
315778AD1-151 GEN
Solar/Wind Harmer
16.88
970129AG2-093 GEN
Solar/Wind Harmer
10.967
970133AG2-095 GEN
Solar/Wind Harmer
2.19
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.524
316258AE1-075 C
Solar/Wind Harmer
0.471
316405AF2-144 C
Solar/Wind Harmer
0.497
3143336POWHATN
Solar/Wind Harmer
1.959
316320Y1-086
Solar/Wind Harmer
1.136
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
3.478
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
-0.019
970917AG2-570 GEN
Solar/Wind Harmer
47.625
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3142946ENON
Solar/Wind Harmer
-0.006
3145273HOLLAND
Solar/Wind Harmer
-0.014
316382AG1-145 C
Solar/Wind Harmer
0.572
970293AG2-193 GEN
Solar/Wind Harmer
2.359
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.874
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
1.978
316365GEN2_N
Solar/Wind Harmer
1.225
3156081AA2-088 GEN
Solar/Wind Harmer
5.867
971157AH1-035 GEN
Solar/Wind Harmer
2.257
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
7.603
315737AD1-076 GEN
Solar/Wind Harmer
3.423
316280AD1-041 GEN
Solar/Wind Harmer
1.355
3141766HARMONY
Solar/Wind Harmer
1.601
316156AD2-030 GEN
Solar/Wind Harmer
0.479
3141873WAN 176
Solar/Wind Harmer
2.127
316473AC1-191 GEN
Solar/Wind Harmer
1.925
3145893MURPHYS
Solar/Wind Harmer
0.125
3145893MURPHYS
Solar/Wind Harmer
-0.018
3146206CASHIE
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.027
961681AG1-008 GEN
Solar/Wind Harmer
14.027
3132273ORANGE
Solar/Wind Harmer
-0.004
966621AG1-532 GEN
Solar/Wind Harmer
0.36
3146173TUNIS
Solar/Wind Harmer
-0.018
3156021HOLLOMANSOL
Solar/Wind Harmer
2.376
316463AE2-346 GEN
Solar/Wind Harmer
0.285
316140AB2-099
Solar/Wind Harmer
0.119
962331AG1-082 GEN
Solar/Wind Harmer
2.202
313506AB2-031 GEN
Solar/Wind Harmer
1.407
316478AD1-087 GEN
Solar/Wind Harmer
1.513
316486AD2-202 GEN
Solar/Wind Harmer
0.443
3146263WOODLND
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3147043LAWRENC
Solar/Wind Harmer
-0.01
316317KELFORD C
Solar/Wind Harmer
0.812
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.068
3145796HORNRTN
Solar/Wind Harmer
-0.017
962971AG1-146 GEN
Solar/Wind Harmer
3.205
316484AD2-074 GEN
Solar/Wind Harmer
4.255
970009AG2-005 GEN
Solar/Wind Harmer
2.113
970909AG2-566 GEN
Solar/Wind Harmer
1.6
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
972183AH1-676 GEN
Adder
147.354
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
316210AC1-098 GEN
Solar/Wind Harmer
1.148
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
14.784
971223AH1-071 GEN
Solar/Wind Harmer
2.818
3143526WINTERP
Solar/Wind Harmer
-0.111
316036AC1-147 C
Solar/Wind Harmer
0.532
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
1.058
316316AC1-027 C
Solar/Wind Harmer
0.605
316185AD1-033 GEN
Solar/Wind Harmer
2.079
316240AF1-291 C
Solar/Wind Harmer
0.594
3145506HICKORY
Solar/Wind Harmer
-0.078
3145506HICKORY
Solar/Wind Harmer
-0.047
3145506HICKORY
Solar/Wind Harmer
-0.012
970657AG2-426 GEN
Solar/Wind Harmer
6.147
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
0.686
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
1.322
316236AE1-162_GEN
Solar/Wind Harmer
0.591
316018AA1-139 ULT2
Solar/Wind Harmer
1.678
316017AA1-139 ULT1
Solar/Wind Harmer
1.585
3137176SLIGO L2192
Solar/Wind Harmer
-0.077
3146456SLIGO L269
Solar/Wind Harmer
2.31
3130086AYDLETT
Solar/Wind Harmer
-0.078
316033AB2-134 GEN
Solar/Wind Harmer
6.285
315697AD1-025 GEN
Solar/Wind Harmer
3.942
970933AG2-581 GEN
Solar/Wind Harmer
18.245
3146386ELIZ CT
Solar/Wind Harmer
-0.019
316431W1029_GEN1
Solar/Wind Harmer
3.478
316433W1029_GEN2
Solar/Wind Harmer
3.478
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3146516WINFALL
Solar/Wind Harmer
-0.019
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
1.967
316075AC2-137 C
Solar/Wind Harmer
0.504
3146376EDENTON
Solar/Wind Harmer
0.555
3146376EDENTON
Solar/Wind Harmer
0.555
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
22.734
316441AF1-014 GEN
Solar/Wind Harmer
1.216
316065AD1-022 GEN
Solar/Wind Harmer
8.955
966871AG1-558 GEN
Solar/Wind Harmer
0.538
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
0.498
3145893MURPHYS
Solar/Wind Harmer
-0.032
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
316181AB2-040 GEN
Solar/Wind Harmer
2.443
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.017
3142666NORTHAMPTON
Solar/Wind Harmer
-0.01
316426AA2-053 GEN
Solar/Wind Harmer
1.748
3145593CAROLNA
Solar/Wind Harmer
-0.017
3145593CAROLNA
Solar/Wind Harmer
-0.017
966811AG1-552 GEN
Solar/Wind Harmer
1.941
3145593CAROLNA
Solar/Wind Harmer
0.143
3145783HORNRTN
Solar/Wind Harmer
2.035
3145783HORNRTN
Solar/Wind Harmer
1.628
3145783HORNRTN
Solar/Wind Harmer
0.509
3145783HORNRTN
Solar/Wind Harmer
0.203
3145796HORNRTN
Solar/Wind Harmer
-0.051
971741AH1-377 GEN
Solar/Wind Harmer
19.85
316487AF1-042 GEN
Solar/Wind Harmer
2.227
970301AG2-198 GEN
Solar/Wind Harmer
8.425
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
21.506
3147666LOUISA
Solar/Wind Harmer
-0.105
316192AB2-158 GEN
Solar/Wind Harmer
3.057
3143226MDLTHAN
Solar/Wind Harmer
-0.022
3143526WINTERP
Solar/Wind Harmer
-0.111
940641AE2-051 GEN
Solar/Wind Harmer
19.731
939411AE1-173 GEN
Solar/Wind Harmer
103.557
316294AC1-161 GEN
Solar/Wind Harmer
6.454
944591AF1-124 GEN
Solar/Wind Harmer
90.387
316375AC2-012 GEN
Solar/Wind Harmer
6.828
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
10.468
316381AD1-082 GEN
Solar/Wind Harmer
1.806
315671AE2-027_GEN
Solar/Wind Harmer
14.765
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
20.871
316388AE2-253 GEN
Solar/Wind Harmer
1.322
3145336SMITFLD
Solar/Wind Harmer
-0.078
3146456SLIGO L269
Solar/Wind Harmer
-0.019
316246AF1-032 C
Solar/Wind Harmer
0.395
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.624
971647AH1-324 GEN
Solar/Wind Harmer
9.747
316072AD1-144
Solar/Wind Harmer
0.394
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
1.97
970129AG2-093 GEN
Solar/Wind Harmer
4.442
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
5.649
3143336POWHATN
Solar/Wind Harmer
2.304
3138126ROCKLANDING
Solar/Wind Harmer
0.059
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
-0.062
3146516WINFALL
Solar/Wind Harmer
-0.019
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.509
971317AH1-138 GEN
Solar/Wind Harmer
2.373
970087AG2-069 GEN
Solar/Wind Harmer
17.783
315800Z1-036_GEN1
Solar/Wind Harmer
4.669
3130156CHOWAN
Solar/Wind Harmer
-0.019
316336AC2-165 C
Solar/Wind Harmer
3.232
3142416OLDCHRC
Solar/Wind Harmer
-0.048
3142416OLDCHRC
Solar/Wind Harmer
-0.018
3142433PROV 92
Solar/Wind Harmer
-0.074
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
-0.051
971163AH1-040 GEN
Solar/Wind Harmer
17.189
957481AF2-042 GEN
Solar/Wind Harmer
56.834
316023GEN1_S
Solar/Wind Harmer
1.225
971777AH1-397 GEN
Solar/Wind Harmer
2.121
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
-0.004
3145893MURPHYS
Solar/Wind Harmer
-0.071
3145893MURPHYS
Solar/Wind Harmer
0.53
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.464
315693AD1-088 GEN
Solar/Wind Harmer
8.916
962491AG1-098 GEN
Solar/Wind Harmer
11.891
960081AF2-299 GEN
Solar/Wind Harmer
1.996
3146173TUNIS
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.01
3145683EARLEYS
Solar/Wind Harmer
-0.017
3146263WOODLND
Solar/Wind Harmer
-0.017
971795AH1-408 GEN
Solar/Wind Harmer
13.07
316011AB1-132 GEN
Solar/Wind Harmer
3.636
962571AG1-106 GEN
Solar/Wind Harmer
2.498
316190AA2-174 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
-0.017
3145963POPLR C
Solar/Wind Harmer
-0.017
3145783HORNRTN
Solar/Wind Harmer
-0.017
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.017
316174AB2-169 GEN
Solar/Wind Harmer
2.636
961951AG1-038 GEN
Solar/Wind Harmer
2.227
962861AG1-135 GEN
Solar/Wind Harmer
6.255
3144293JTRSVLE
Adder
0.458
3150351NORNECKC2
Adder
1.425
3151751LOISA D
Adder
9.244
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
316212AC1-099_GEN
Solar/Wind Harmer
0.638
NYPJM->LTFIMP_NY
CLTF
2.547
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.426
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
SIGELTFEXP_SIGE->PJM
CLTF
0.076

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.41 %
Rating:3220.44 MVA
Rating Type:A
MVA to Mitigate:4167.61
MW Contribution:7.74
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
17.069
971507AH1-251 GEN
50/50
10.56
970119AG2-088 GEN
50/50
26.753
3150851SPRUNCC
50/50
0.882
315243AE2-183_GT3
50/50
2.943
3151051BRUNSWICKS1
50/50
4.812
3151021BRUNSWICKG1
50/50
2.318
971451AH1-221 GEN
50/50
7.041
316045AC1-158 PL2
Solar/Wind Harmer
9.498
3147666LOUISA
Solar/Wind Harmer
0.935
316192AB2-158 GEN
Solar/Wind Harmer
1.293
3143226MDLTHAN
Solar/Wind Harmer
0.2
3143526WINTERP
Solar/Wind Harmer
0.994
940641AE2-051 GEN
Solar/Wind Harmer
14.986
939411AE1-173 GEN
Solar/Wind Harmer
78.651
316294AC1-161 GEN
Solar/Wind Harmer
3.077
944591AF1-124 GEN
Solar/Wind Harmer
39.816
316375AC2-012 GEN
Solar/Wind Harmer
0.004
3150981CHESPKA
Adder
2.192
970659AG2-427 GEN
Solar/Wind Harmer
8.481
316381AD1-082 GEN
Solar/Wind Harmer
0.183
315671AE2-027_GEN
Solar/Wind Harmer
11.214
3142543TWELFTH
Solar/Wind Harmer
0.017
970661AG2-428 GEN
Solar/Wind Harmer
17.39
316388AE2-253 GEN
Solar/Wind Harmer
0.547
3145336SMITFLD
Solar/Wind Harmer
0.697
3146456SLIGO L269
Solar/Wind Harmer
0.174
316246AF1-032 C
Solar/Wind Harmer
0.078
3151171GRAVELC
Adder
1.847
961611AG1-000B GEN
Solar/Wind Harmer
9.102
971647AH1-324 GEN
Solar/Wind Harmer
7.403
316072AD1-144
Solar/Wind Harmer
0.063
971069AG2-661 GEN
Solar/Wind Harmer
3.083
316458AB2-190 GEN2
Solar/Wind Harmer
0.93
970129AG2-093 GEN
Solar/Wind Harmer
4.931
3143096IRON208
Adder
0.724
316093AE2-104_GEN
Solar/Wind Harmer
2.908
3143336POWHATN
Solar/Wind Harmer
3.072
3138126ROCKLANDING
Solar/Wind Harmer
0.078
944631AF1-128 GEN
Adder
81.389
3146516WINFALL
Solar/Wind Harmer
0.552
3146516WINFALL
Solar/Wind Harmer
0.17
970919AG2-571 GEN
Solar/Wind Harmer
6.028
316159AE1-175 C
Solar/Wind Harmer
0.146
971317AH1-138 GEN
Solar/Wind Harmer
1.261
970087AG2-069 GEN
Solar/Wind Harmer
13.506
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
316336AC2-165 C
Solar/Wind Harmer
0.006
3142416OLDCHRC
Solar/Wind Harmer
0.43
3142416OLDCHRC
Solar/Wind Harmer
0.165
3142433PROV 92
Solar/Wind Harmer
0.658
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
3145663CRESWEL
Solar/Wind Harmer
0.457
971163AH1-040 GEN
Solar/Wind Harmer
13.055
957481AF2-042 GEN
Solar/Wind Harmer
43.165
316023GEN1_S
Solar/Wind Harmer
0.363
971777AH1-397 GEN
Solar/Wind Harmer
0.424
3141843SHACKLE
Adder
0.82
3141766HARMONY
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.635
3145893MURPHYS
Solar/Wind Harmer
0.706
3146206CASHIE
Solar/Wind Harmer
0.159
971547AH1-271 GEN
Solar/Wind Harmer
3.39
315693AD1-088 GEN
Solar/Wind Harmer
7.618
962491AG1-098 GEN
Solar/Wind Harmer
9.031
960081AF2-299 GEN
Solar/Wind Harmer
1.516
3146173TUNIS
Solar/Wind Harmer
0.157
3138133OCRAN
Solar/Wind Harmer
0.094
3145683EARLEYS
Solar/Wind Harmer
0.156
3146263WOODLND
Solar/Wind Harmer
0.155
971795AH1-408 GEN
Solar/Wind Harmer
10.34
316011AB1-132 GEN
Solar/Wind Harmer
2.811
962571AG1-106 GEN
Solar/Wind Harmer
2.2
316190AA2-174 GEN
Solar/Wind Harmer
0
3147043LAWRENC
Adder
1.392
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145783HORNRTN
Solar/Wind Harmer
0.152
3145796HORNRTN
Solar/Wind Harmer
0.502
3145796HORNRTN
Solar/Wind Harmer
0.152
316174AB2-169 GEN
Solar/Wind Harmer
0.004
962861AG1-135 GEN
Solar/Wind Harmer
4.751
316212AC1-099_GEN
Solar/Wind Harmer
0.768
316129AC1-054 GEN
Solar/Wind Harmer
0.557
971065AG2-659 GEN
Solar/Wind Harmer
6.296
3146293MARTNCO
Solar/Wind Harmer
0.137
970937AG2-583 GEN
Solar/Wind Harmer
9.004
315687AD1-152 GEN
Solar/Wind Harmer
0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.168
3141726DUNNSVL
Solar/Wind Harmer
0.58
315722AD1-056 GEN
Solar/Wind Harmer
0.916
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970685AG2-442 GEN
Solar/Wind Harmer
10.759
316254AC1-120 GEN1
Solar/Wind Harmer
0.307
316237AB2-079_GEN
Solar/Wind Harmer
0.001
963171AG1-166 GEN
Solar/Wind Harmer
0.768
971563AH1-280 GEN
Solar/Wind Harmer
1.536
3144293JTRSVLE
Adder
0.458
3146926FARMVIL
Solar/Wind Harmer
0.086
3150351NORNECKC2
Adder
1.425
316494AC1-189 GEN
Solar/Wind Harmer
0.481
3151751LOISA D
Adder
9.244
3146233WITAKRS
Solar/Wind Harmer
0.561
961671AG1-007 GEN
Solar/Wind Harmer
0.022
3146083TARBORO
Solar/Wind Harmer
0.141
3145493TOT1
Solar/Wind Harmer
0.626
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.111
316359AB2-059 GEN
Solar/Wind Harmer
0.498
316049AB1-081 GEN
Solar/Wind Harmer
0.793
3142053HEARTS
Solar/Wind Harmer
0.244
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
970401AG2-262 GEN
Solar/Wind Harmer
0.803
316337AD2-073 GEN
Solar/Wind Harmer
0.118
972197AH1-683 GEN
Adder
2.827
972219AH1-694 GEN
Adder
2.035
972003AH1-546 GEN
Solar/Wind Harmer
5.618
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971377AH1-170 GEN
Solar/Wind Harmer
1.304
3147623JAMES R
Solar/Wind Harmer
0.283
972135AH1-637 GEN
Solar/Wind Harmer
0.976
3152261N ANNA2
50/50
17.068
3150861SPRUNCD
50/50
0.882
3151031BRUNSWICKG2
50/50
2.318
3151101ELIZAR3
50/50
17.311
316044AC1-158 PL1
Solar/Wind Harmer
2.971
316450AC1-158 RIC
Solar/Wind Harmer
0.792
3147666LOUISA
Solar/Wind Harmer
0.538
315773AC2-141 GEN
Solar/Wind Harmer
6.485
315839AE2-212 C
Solar/Wind Harmer
0.001
944581AF1-123 GEN
Solar/Wind Harmer
39.675
944601AF1-125 GEN
Solar/Wind Harmer
39.064
315813AE1-149 C
Solar/Wind Harmer
9.394
965281AG1-393 GEN
Solar/Wind Harmer
1.874
3144873MCLAUGH
Solar/Wind Harmer
0.004
970659AG2-427 GEN
Solar/Wind Harmer
1.855
3144536CHRHLND
Solar/Wind Harmer
0.026
316083AB2-161 GEN
Solar/Wind Harmer
0.002
970661AG2-428 GEN
Solar/Wind Harmer
3.699
3145336SMITFLD
Solar/Wind Harmer
0.07
3146456SLIGO L269
Solar/Wind Harmer
0.174
971153AH1-033 GEN
Solar/Wind Harmer
2.012
3151221GRAVEL6
Adder
12.623
3151171GRAVELC
Adder
2.429
961611AG1-000B GEN
Solar/Wind Harmer
4.628
315778AD1-151 GEN
Solar/Wind Harmer
13.874
970129AG2-093 GEN
Solar/Wind Harmer
10.479
970133AG2-095 GEN
Solar/Wind Harmer
1.663
3143096IRON208
Adder
0.724
3143096IRON208
Adder
0.71
316313AB2-026
Solar/Wind Harmer
0.109
316258AE1-075 C
Solar/Wind Harmer
0.13
316405AF2-144 C
Solar/Wind Harmer
0.001
3143336POWHATN
Solar/Wind Harmer
2.611
316320Y1-086
Solar/Wind Harmer
0.001
3144216WINCHST
Adder
0.645
316435W1029_GEN3
Solar/Wind Harmer
0.001
3150921YORKTN3
Adder
4.287
3146516WINFALL
Solar/Wind Harmer
0.17
970917AG2-570 GEN
Solar/Wind Harmer
15.071
3146626S HERTFORD
Solar/Wind Harmer
0.169
3142946ENON
Solar/Wind Harmer
0.057
3145273HOLLAND
Solar/Wind Harmer
0.127
316382AG1-145 C
Solar/Wind Harmer
0.001
970293AG2-193 GEN
Solar/Wind Harmer
1.792
3146376EDENTON
Solar/Wind Harmer
0.166
3142416OLDCHRC
Solar/Wind Harmer
1.602
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315614AA2-178 GEN
Solar/Wind Harmer
0.934
316365GEN2_N
Solar/Wind Harmer
0.363
3156081AA2-088 GEN
Solar/Wind Harmer
0.004
971157AH1-035 GEN
Solar/Wind Harmer
1.929
3141843SHACKLE
Adder
0.82
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
315737AD1-076 GEN
Solar/Wind Harmer
2.062
316280AD1-041 GEN
Solar/Wind Harmer
0.003
3141766HARMONY
Solar/Wind Harmer
2.134
316156AD2-030 GEN
Solar/Wind Harmer
0.118
3141873WAN 176
Solar/Wind Harmer
2.836
316473AC1-191 GEN
Solar/Wind Harmer
0.538
3145893MURPHYS
Solar/Wind Harmer
0.266
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
957521AF2-046 GEN
Solar/Wind Harmer
11.795
961681AG1-008 GEN
Solar/Wind Harmer
11.795
3132273ORANGE
Solar/Wind Harmer
0.032
3146173TUNIS
Solar/Wind Harmer
0.157
3156021HOLLOMANSOL
Solar/Wind Harmer
0.713
316463AE2-346 GEN
Solar/Wind Harmer
0.135
316140AB2-099
Solar/Wind Harmer
0.056
962331AG1-082 GEN
Solar/Wind Harmer
1.672
313506AB2-031 GEN
Solar/Wind Harmer
0.482
316478AD1-087 GEN
Solar/Wind Harmer
0.543
316486AD2-202 GEN
Solar/Wind Harmer
0.159
3146263WOODLND
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3147043LAWRENC
Solar/Wind Harmer
0.092
316317KELFORD C
Solar/Wind Harmer
0.015
3145823KELFORD
Solar/Wind Harmer
0.153
3145963POPLR C
Solar/Wind Harmer
0.153
3145796HORNRTN
Solar/Wind Harmer
0.609
3145796HORNRTN
Solar/Wind Harmer
0.152
962971AG1-146 GEN
Solar/Wind Harmer
2.434
970009AG2-005 GEN
Solar/Wind Harmer
1.123
970909AG2-566 GEN
Solar/Wind Harmer
1.6
316303AF2-085
50/50
3.567
971285AH1-108 GEN
50/50
1.443
315244AE2-183_ST
50/50
5.089
963041AG1-153 GEN
50/50
4.694
3151081ELIZAR1
50/50
17.092
3151091ELIZAR2
50/50
16.795
316164AC1-076 GEN
Solar/Wind Harmer
0.366
316233AE1-074 FULL
Solar/Wind Harmer
0.153
971281AH1-106 GEN
Solar/Wind Harmer
2.654
971283AH1-107 GEN
Solar/Wind Harmer
2.654
941031AE2-094 GEN
Solar/Wind Harmer
33.713
944011AF1-069 GEN
Solar/Wind Harmer
11.015
970673AG2-436 GEN
Solar/Wind Harmer
38.362
970673AG2-436 GEN
Solar/Wind Harmer
25.574
3143316POE
Solar/Wind Harmer
0.707
971967AH1-528 GEN
Solar/Wind Harmer
28.408
3152611GOSPORTB
Adder
2.236
3152621GOSPORTC
Adder
1.898
3152601GOSPORTA
Adder
1.751
316315AB2-025 C
Solar/Wind Harmer
0.141
957871AF2-081 GEN
Solar/Wind Harmer
8.68
315814AE2-033 C
Solar/Wind Harmer
13.794
971445AH1-216 GEN
Solar/Wind Harmer
12.275
319010AE1-072 C
Solar/Wind Harmer
0.876
3146406KITTY HAWK
Solar/Wind Harmer
0.022
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.119
316311AC2-079 GEN
Solar/Wind Harmer
4.99
316305AF2-043 C
Solar/Wind Harmer
0.001
972265AH1-717 GEN
Adder
13.481
3151201GRAVEL4
Adder
12.638
3151191GRAVEL3
Adder
12.478
3151211GRAVEL5
Adder
12.478
316369SG1_INVT
Solar/Wind Harmer
0.006
316132AB2-190 GEN1
Solar/Wind Harmer
0.93
315835AF2-110_GEN
Solar/Wind Harmer
1.187
313526AB2-022
Solar/Wind Harmer
0.093
3146486SUNBURY
Solar/Wind Harmer
0.172
3146486SUNBURY
Solar/Wind Harmer
0.172
316321Z2-027
Solar/Wind Harmer
0.032
3146396TANGLEW
Solar/Wind Harmer
0.473
3145176PASQUOTANK
Solar/Wind Harmer
0.106
970085AG2-068 GEN
Solar/Wind Harmer
9.004
970581AG2-369 GEN
Solar/Wind Harmer
7.744
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.166
3130156CHOWAN
Solar/Wind Harmer
0.166
315976AC1-164 GENA
Solar/Wind Harmer
17.177
316169AC1-164_GENC
Solar/Wind Harmer
14.839
315975AC1-164 GENB
Solar/Wind Harmer
0.508
316312AB1-027
Solar/Wind Harmer
0.296
3138283WHITEMARSH
Solar/Wind Harmer
0.038
971167AH1-042 GEN
Solar/Wind Harmer
14.667
3142433PROV 92
Adder
0.32
3142433PROV 92
Adder
0.32
315816AE2-034 GEN
Solar/Wind Harmer
0.7
3143873LANEXA
Solar/Wind Harmer
0.097
3130546PLYMOUTH
Solar/Wind Harmer
0.161
970189AG2-124 GEN
Solar/Wind Harmer
4.756
316314AB2-024 C
Solar/Wind Harmer
0.001
965291AG1-394 GEN
Solar/Wind Harmer
0.712
315732AD1-074 GEN1
Solar/Wind Harmer
0.921
315733AD1-074 GEN2
Solar/Wind Harmer
0.921
315735AD1-075 GEN1
Solar/Wind Harmer
0.461
315662AE1-191 GEN
Solar/Wind Harmer
0.005
315666AE1-190 GEN
Solar/Wind Harmer
0.001
316059AD1-063 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
0.032
3145893MURPHYS
Solar/Wind Harmer
0.429
3145893MURPHYS
Solar/Wind Harmer
0.159
3146206CASHIE
Solar/Wind Harmer
0.159
970601AG2-382 GEN
Solar/Wind Harmer
5.933
972189AH1-679 GEN
Adder
2.633
3141913WHIT STONE
Solar/Wind Harmer
0.157
3145513AHOSKIE
Solar/Wind Harmer
0.328
3145513AHOSKIE
Solar/Wind Harmer
0.157
3146043SEABORD
Solar/Wind Harmer
0.156
316087AB2-174 GEN
Solar/Wind Harmer
0.004
3138133OCRAN
Solar/Wind Harmer
0.047
315607AA1-063A GEN
Solar/Wind Harmer
0.319
3145683EARLEYS
Solar/Wind Harmer
0.312
3145683EARLEYS
Solar/Wind Harmer
0.156
3145683EARLEYS
Solar/Wind Harmer
0.156
3141783LANCAST
Solar/Wind Harmer
0.093
3141783LANCAST
Solar/Wind Harmer
0.062
315652AC1-086 GEN
Solar/Wind Harmer
17.007
3137643SOCKMAN
Solar/Wind Harmer
0.617
3145796HORNRTN
Solar/Wind Harmer
0.487
3145796HORNRTN
Solar/Wind Harmer
0.061
962981AG1-147 GEN
Solar/Wind Harmer
5.679
3146033SCOT NK
Solar/Wind Harmer
0.602
970327AG2-215 GEN
Solar/Wind Harmer
4.937
970831AG2-522 GEN
Solar/Wind Harmer
6.34
316005AA1-067
Solar/Wind Harmer
0.155
3145746EVERETS
Solar/Wind Harmer
0.575
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
970181AG2-120 GEN
Solar/Wind Harmer
1.799
971443AH1-215 GEN
Solar/Wind Harmer
2.423
3144303KENBRDG
Solar/Wind Harmer
0.115
970683AG2-441 GEN
Solar/Wind Harmer
9.607
970681AG2-440 GEN
Solar/Wind Harmer
7.685
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
946301AF1-294 GEN
Solar/Wind Harmer
2.841
961791AG1-021 GEN
Solar/Wind Harmer
1.382
315657AE1-056 GEN
Solar/Wind Harmer
4.964
3141813NORNECK
Solar/Wind Harmer
0.143
957861AF2-080 GEN
Solar/Wind Harmer
6.144
316420AA1-050 GEN
Solar/Wind Harmer
0.005
316319Z2-044 C
Solar/Wind Harmer
0
3145573BETHELC
Solar/Wind Harmer
0.141
3145573BETHELC
Solar/Wind Harmer
0.141
970285AG2-188 GEN
Solar/Wind Harmer
11.015
971845AH1-439 GEN
Solar/Wind Harmer
6.271
971133AH1-012 GEN
50/50
4.837
970533AG2-339 GEN
50/50
16.271
970531AG2-338 GEN
50/50
6.508
315242AE2-183_GT2
50/50
2.943
315241AE2-183_GT1
50/50
2.925
972185AH1-677 GEN
50/50
10.611
3151041BRUNSWICKG3
50/50
2.318
972187AH1-678 GEN
50/50
5.32
316447AC1-158 HLD
Solar/Wind Harmer
6.529
971223AH1-071 GEN
Solar/Wind Harmer
2.14
3143526WINTERP
Solar/Wind Harmer
0.994
316036AC1-147 C
Solar/Wind Harmer
0.033
3150991CHESPKB
Adder
1.839
3150991CHESPKB
Adder
1.795
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.168
316185AD1-033 GEN
Solar/Wind Harmer
0.005
316240AF1-291 C
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.7
3145506HICKORY
Solar/Wind Harmer
0.42
3145506HICKORY
Solar/Wind Harmer
0.105
970657AG2-426 GEN
Solar/Wind Harmer
6.132
970657AG2-426 GEN
Solar/Wind Harmer
1.286
3144356SAPONY
Solar/Wind Harmer
1.464
944641AF1-129 GEN
Adder
83.418
316339AD2-160 GEN
Solar/Wind Harmer
0.283
316236AE1-162_GEN
Solar/Wind Harmer
0.001
316018AA1-139 ULT2
Solar/Wind Harmer
0.004
316017AA1-139 ULT1
Solar/Wind Harmer
0.097
3137176SLIGO L2192
Solar/Wind Harmer
0.693
3146456SLIGO L269
Solar/Wind Harmer
3.08
3130086AYDLETT
Solar/Wind Harmer
0.695
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.195
970933AG2-581 GEN
Solar/Wind Harmer
13.857
3146386ELIZ CT
Solar/Wind Harmer
0.172
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3146516WINFALL
Solar/Wind Harmer
0.17
3142366NRTHEST
Adder
0.556
3146626S HERTFORD
Solar/Wind Harmer
0.169
3146626S HERTFORD
Solar/Wind Harmer
0.169
3150691DARBY 3
Adder
12.185
3150701DARBY 4
Adder
12.157
3150681DARBY 2
Adder
12.142
3150671DARBY 1
Adder
12.128
3142946ENON
Solar/Wind Harmer
0.017
315742AE1-103 GEN
Solar/Wind Harmer
0.002
316075AC2-137 C
Solar/Wind Harmer
0.046
3146376EDENTON
Solar/Wind Harmer
0.74
3146376EDENTON
Solar/Wind Harmer
0.74
3142296MT RD221
Adder
0.528
970099AG2-077 GEN
Solar/Wind Harmer
17.266
316065AD1-022 GEN
Solar/Wind Harmer
7.34
966871AG1-558 GEN
Solar/Wind Harmer
0.184
3145893MURPHYS
Solar/Wind Harmer
1.063
3145893MURPHYS
Solar/Wind Harmer
0.286
3146173TUNIS
Solar/Wind Harmer
0.157
3146173TUNIS
Solar/Wind Harmer
0.157
316181AB2-040 GEN
Solar/Wind Harmer
0.226
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.155
3142666NORTHAMPTON
Solar/Wind Harmer
0.093
316426AA2-053 GEN
Solar/Wind Harmer
0.52
3145593CAROLNA
Solar/Wind Harmer
0.153
3145593CAROLNA
Solar/Wind Harmer
0.153
966811AG1-552 GEN
Solar/Wind Harmer
1.665
3145593CAROLNA
Solar/Wind Harmer
0.191
3145783HORNRTN
Solar/Wind Harmer
2.713
3145783HORNRTN
Solar/Wind Harmer
2.17
3145783HORNRTN
Solar/Wind Harmer
0.678
3145783HORNRTN
Solar/Wind Harmer
0.271
3145796HORNRTN
Solar/Wind Harmer
0.457
971741AH1-377 GEN
Solar/Wind Harmer
15.076
970301AG2-198 GEN
Solar/Wind Harmer
6.399
958261AF2-120 GEN
Solar/Wind Harmer
4.886
316274AC1-208 GEN
Solar/Wind Harmer
0.766
3145933PARMELE
Solar/Wind Harmer
0.295
3145933PARMELE
Solar/Wind Harmer
0.147
957411AF2-035 GEN
Solar/Wind Harmer
6.2
970317AG2-208 GEN
Solar/Wind Harmer
5.744
939181AE1-148 GEN
Solar/Wind Harmer
6.96
313527AB2-043 GEN
Solar/Wind Harmer
0.002
316034AC1-036 C
Solar/Wind Harmer
0.011
970323AG2-213 GEN
Solar/Wind Harmer
6.152
971775AH1-396 GEN
Solar/Wind Harmer
0.231
958211AF2-115 GEN
Solar/Wind Harmer
1.728
963191AG1-168 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3144293JTRSVLE
Adder
0.386
3147133PAMPLIN
Solar/Wind Harmer
0.144
3147133PAMPLIN
Solar/Wind Harmer
0.115
316077AC2-138 C
Solar/Wind Harmer
0.001
3150341NORNECKC1
Adder
1.496
3150341NORNECKC1
Adder
1.484
966001AG1-469 GEN
Solar/Wind Harmer
0.083
3151731LOISA B
Adder
9.244
3151721LOISA A
Adder
9.197
315673AE1-157 GEN
Solar/Wind Harmer
9.786
3145493TOT1
Solar/Wind Harmer
0.326
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.13
961601AG1-000A GEN
Solar/Wind Harmer
2.463
316263AC1-034 GEN
Solar/Wind Harmer
5.264
962561AG1-105 GEN
Solar/Wind Harmer
6.627
3146776BUCKING
Solar/Wind Harmer
0.551
3146776BUCKING
Solar/Wind Harmer
0.045
964791AG1-342 GEN
Solar/Wind Harmer
2.629
3146843MT LREL
Solar/Wind Harmer
0.137
3146843MT LREL
Solar/Wind Harmer
0.137
3150391LDYSMT3
Adder
18.067
972195AH1-682 GEN
Adder
2.374
316468AD1-105 GEN
Solar/Wind Harmer
-0.044
971489AH1-241 GEN
Solar/Wind Harmer
6.519
316222AC1-221 GEN
Solar/Wind Harmer
0.492
316210AC1-098 GEN
Solar/Wind Harmer
1.377
316404AE1-155 C
Solar/Wind Harmer
0.033
3145933PARMELE
Solar/Wind Harmer
0.147
966801AG1-551 GEN
Solar/Wind Harmer
1.716
315724AD1-057 GEN
Solar/Wind Harmer
0.543
3145746EVERETS
Solar/Wind Harmer
0.144
3145746EVERETS
Solar/Wind Harmer
0.144
316131AB2-060 GEN
Solar/Wind Harmer
0.454
964241AG1-285 GEN
Solar/Wind Harmer
9.624
315785AD2-033 C
Solar/Wind Harmer
1.173
970257AG2-171 GEN
Solar/Wind Harmer
4.614
959311AF2-222 GEN
Solar/Wind Harmer
12.815
316170AC1-121 GEN2
Solar/Wind Harmer
0.154
963181AG1-167 GEN
Solar/Wind Harmer
0.576
3144293JTRSVLE
Adder
0.458
3147133PAMPLIN
Solar/Wind Harmer
0.452
971193AH1-056 GEN
Solar/Wind Harmer
8.764
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.086
316327AA2-057 GEN
Solar/Wind Harmer
0.217
3150351NORNECKC2
Adder
1.449
3151761LOISA E
Adder
18.847
3146233WITAKRS
Solar/Wind Harmer
0.708
3146233WITAKRS
Solar/Wind Harmer
0.096
3138543CONSLDL
Solar/Wind Harmer
0.093
3146073TAR RVR
Solar/Wind Harmer
0.141
3146083TARBORO
Solar/Wind Harmer
0.141
961601AG1-000A GEN
Solar/Wind Harmer
9.854
3145543BTLEBRO
Solar/Wind Harmer
0.138
3145543BTLEBRO
Solar/Wind Harmer
0.138
971623AH1-311 GEN
Solar/Wind Harmer
0.277
972183AH1-676 GEN
Adder
147.354
3146776BUCKING
Solar/Wind Harmer
0.05
3150401LDYSMT4
Adder
18.101
3150371LDYSMT1
Adder
17.49
971781AH1-399 GEN
Solar/Wind Harmer
0.177
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.61
3141906WESTMOR
Solar/Wind Harmer
0.051
970221AG2-151 GEN
Solar/Wind Harmer
6.519
971683AH1-343 GEN
Solar/Wind Harmer
4.456
970737AG2-469 GEN
Solar/Wind Harmer
5.095
316283AC2-100 C
Solar/Wind Harmer
0.231
3150411LDYSMT5
Adder
18.158
3150381LDYSMT2
Adder
17.377
972213AH1-691 GEN
Adder
2.94
972215AH1-692 GEN
Adder
2.94
3147346CASHSCORNER
Solar/Wind Harmer
0.311
316118AC1-105 GEN
Solar/Wind Harmer
0.346
3147173SINAI
Solar/Wind Harmer
0.131
3147243WELCO
Solar/Wind Harmer
0.082
972205AH1-687 GEN
Adder
5.595
316223AC1-118
Solar/Wind Harmer
0.091
971447AH1-217 GEN
Solar/Wind Harmer
3.599
970865AG2-541 GEN
Solar/Wind Harmer
4.024
NYPJM->LTFIMP_NY
CLTF
2.547
LGEELTFEXP_LGEE->PJM
CLTF
0.9
LAGNLTFEXP_LAGN->PJM
CLTF
5.963
WECLTFEXP_WEC->PJM
CLTF
0.426
CBM South 2LTFEXP_CBM-S2->PJM
CBM
19.52
TVALTFEXP_TVA->PJM
CLTF
3.02
CPLELTFEXP_CPLE->PJM
CLTF
9
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.817
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.186
MECLTFEXP_MEC->PJM
CLTF
2.509
SIGELTFEXP_SIGE->PJM
CLTF
0.076

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2-2199_SRT-A-1


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2-2199_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.66 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4911.8
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
17.342
3151771S ANNAG1
50/50
0.915
3151801S ANNAS2
50/50
0.47
3151761LOISA E
50/50
36.194
972183AH1-676 GEN
50/50
289.654
3150861SPRUNCD
50/50
0.914
3151031BRUNSWICKG2
50/50
2.407
316044AC1-158 PL1
Solar/Wind Harmer
6.731
316450AC1-158 RIC
Solar/Wind Harmer
1.795
316170AC1-121 GEN2
Solar/Wind Harmer
1.027
3147666LOUISA
Solar/Wind Harmer
-0.078
3132273ORANGE
Solar/Wind Harmer
-0.007
316313AB2-026
Solar/Wind Harmer
0.567
316258AE1-075 C
Solar/Wind Harmer
0.51
316405AF2-144 C
Solar/Wind Harmer
0.538
3143336POWHATN
Solar/Wind Harmer
2.119
315773AC2-141 GEN
Solar/Wind Harmer
8.631
315839AE2-212 C
Solar/Wind Harmer
0.619
944581AF1-123 GEN
Solar/Wind Harmer
93.163
944601AF1-125 GEN
Solar/Wind Harmer
91.709
315813AE1-149 C
Solar/Wind Harmer
12.797
3151101ELIZAR3
Adder
16.875
965281AG1-393 GEN
Solar/Wind Harmer
2.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
316303AF2-085
50/50
3.711
971285AH1-108 GEN
50/50
1.495
315244AE2-183_ST
50/50
5.281
316164AC1-076 GEN
Solar/Wind Harmer
3.466
3147346CASHSCORNER
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.601
971281AH1-106 GEN
Solar/Wind Harmer
3.628
971283AH1-107 GEN
Solar/Wind Harmer
3.628
941031AE2-094 GEN
Solar/Wind Harmer
39.963
944011AF1-069 GEN
Solar/Wind Harmer
12.522
970673AG2-436 GEN
Solar/Wind Harmer
44.026
970673AG2-436 GEN
Solar/Wind Harmer
22.292
3143316POE
Solar/Wind Harmer
-0.082
971967AH1-528 GEN
Solar/Wind Harmer
38.978
3151081ELIZAR1
Adder
16.662
3151091ELIZAR2
Adder
16.373
3152611GOSPORTB
Adder
2.313
3152621GOSPORTC
Adder
1.963
3152601GOSPORTA
Adder
1.811
3152251N ANNA1
50/50
17.343
971507AH1-251 GEN
50/50
12.192
3151791S ANNAG2
50/50
0.915
3151781S ANNAS1
50/50
0.47
3151741LOISA C
50/50
0.971
3151751LOISA D
50/50
17.753
970119AG2-088 GEN
50/50
27.833
3150851SPRUNCC
50/50
0.914
315243AE2-183_GT3
50/50
3.054
3151051BRUNSWICKS1
50/50
4.996
3151021BRUNSWICKG1
50/50
2.407
316045AC1-158 PL2
Solar/Wind Harmer
21.532
316254AC1-120 GEN1
Solar/Wind Harmer
3.082
3147666LOUISA
Solar/Wind Harmer
-0.136
316192AB2-158 GEN
Solar/Wind Harmer
4.034
315683AE1-153 C
Solar/Wind Harmer
26.707
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.116
940641AE2-051 GEN
Solar/Wind Harmer
20.412
939411AE1-173 GEN
Solar/Wind Harmer
107.132
3143336POWHATN
Solar/Wind Harmer
2.493
316294AC1-161 GEN
Solar/Wind Harmer
6.674
944591AF1-124 GEN
Solar/Wind Harmer
93.498
316375AC2-012 GEN
Solar/Wind Harmer
7.063
3150981CHESPKA
Adder
2.268
970659AG2-427 GEN
Solar/Wind Harmer
10.833
316381AD1-082 GEN
Solar/Wind Harmer
1.869
316336AC2-165 C
Solar/Wind Harmer
3.539
315671AE2-027_GEN
Solar/Wind Harmer
15.27
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
21.6
316388AE2-253 GEN
Solar/Wind Harmer
1.368
970659AG2-427 GEN
Solar/Wind Harmer
1.92
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.307
970661AG2-428 GEN
Solar/Wind Harmer
3.828
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.467
3151221GRAVEL6
Adder
13.054
3151171GRAVELC
Adder
2.512
961611AG1-000B GEN
Solar/Wind Harmer
4.246
315778AD1-151 GEN
Solar/Wind Harmer
17.454
970129AG2-093 GEN
Solar/Wind Harmer
11.34
970133AG2-095 GEN
Solar/Wind Harmer
2.265
3143096IRON208
Adder
0.749
3143096IRON208
Adder
0.734
316320Y1-086
Solar/Wind Harmer
1.176
316435W1029_GEN3
Solar/Wind Harmer
3.602
3144216WINCHST
Adder
0.666
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.43
970917AG2-570 GEN
Solar/Wind Harmer
49.496
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.591
970293AG2-193 GEN
Solar/Wind Harmer
2.436
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.934
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315614AA2-178 GEN
Solar/Wind Harmer
2.053
316365GEN2_N
Solar/Wind Harmer
1.275
3156081AA2-088 GEN
Solar/Wind Harmer
6.102
971157AH1-035 GEN
Solar/Wind Harmer
2.344
315737AD1-076 GEN
Solar/Wind Harmer
3.555
3141843SHACKLE
Adder
0.846
316203AE2-005 GEN
Solar/Wind Harmer
7.84
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
316280AD1-041 GEN
Solar/Wind Harmer
1.397
3141766HARMONY
Solar/Wind Harmer
1.65
957521AF2-046 GEN
Solar/Wind Harmer
14.595
961681AG1-008 GEN
Solar/Wind Harmer
14.595
966621AG1-532 GEN
Solar/Wind Harmer
0.376
316156AD2-030 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
2.193
316473AC1-191 GEN
Solar/Wind Harmer
1.984
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.593
316486AD2-202 GEN
Solar/Wind Harmer
0.467
3156021HOLLOMANSOL
Solar/Wind Harmer
2.471
316463AE2-346 GEN
Solar/Wind Harmer
0.297
316140AB2-099
Solar/Wind Harmer
0.124
962331AG1-082 GEN
Solar/Wind Harmer
2.291
970909AG2-566 GEN
Solar/Wind Harmer
1.74
313506AB2-031 GEN
Solar/Wind Harmer
1.47
3146263WOODLND
Solar/Wind Harmer
-0.018
316315AB2-025 C
Solar/Wind Harmer
0.55
315814AE2-033 C
Solar/Wind Harmer
18.917
957871AF2-081 GEN
Solar/Wind Harmer
10.138
971445AH1-216 GEN
Solar/Wind Harmer
12.537
319010AE1-072 C
Solar/Wind Harmer
4.091
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.84
316349AD2-085 GEN
Solar/Wind Harmer
1.798
316311AC2-079 GEN
Solar/Wind Harmer
10.195
316305AF2-043 C
Solar/Wind Harmer
0.609
972265AH1-717 GEN
Adder
13.942
3151201GRAVEL4
Adder
13.069
3151191GRAVEL3
Adder
12.904
3151211GRAVEL5
Adder
12.904
316369SG1_INVT
Solar/Wind Harmer
3.601
316132AB2-190 GEN1
Solar/Wind Harmer
2.037
315835AF2-110_GEN
Solar/Wind Harmer
2.515
313526AB2-022
Solar/Wind Harmer
0.541
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.539
3146396TANGLEW
Solar/Wind Harmer
0.368
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.323
970581AG2-369 GEN
Solar/Wind Harmer
10.597
315611Z1-036_GEN2
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
20.303
316169AC1-164_GENC
Solar/Wind Harmer
17.54
315975AC1-164 GENB
Solar/Wind Harmer
0.601
316312AB1-027
Solar/Wind Harmer
0.647
957831AF2-077 GEN
Solar/Wind Harmer
0.576
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.438
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315816AE2-034 GEN
Solar/Wind Harmer
1.54
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.663
315732AD1-074 GEN1
Solar/Wind Harmer
3.783
315733AD1-074 GEN2
Solar/Wind Harmer
3.783
315735AD1-075 GEN1
Solar/Wind Harmer
1.892
316314AB2-024 C
Solar/Wind Harmer
1.588
316318V4-068
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.117
315662AE1-191 GEN
Solar/Wind Harmer
2.236
315666AE1-190 GEN
Solar/Wind Harmer
0.559
316059AD1-063 C
Solar/Wind Harmer
0.419
946281AF1-292 GEN
Solar/Wind Harmer
0.415
957601AF2-054 GEN
Solar/Wind Harmer
0.553
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.619
3146043SEABORD
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.16
961941AG1-037 GEN
Solar/Wind Harmer
0.138
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315607AA1-063A GEN
Solar/Wind Harmer
1.849
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.072
972189AH1-679 GEN
Adder
2.703
3138133OCRAN
Solar/Wind Harmer
-0.005
315652AC1-086 GEN
Solar/Wind Harmer
20.367
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
Adder
6.589
3150411LDYSMT5
Adder
18.318
3150381LDYSMT2
Adder
17.531
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
971133AH1-012 GEN
50/50
5.76
3151731LOISA B
50/50
17.753
3151721LOISA A
50/50
17.662
970533AG2-339 GEN
50/50
16.862
970531AG2-338 GEN
50/50
6.745
315242AE2-183_GT2
50/50
3.054
315241AE2-183_GT1
50/50
3.036
972185AH1-677 GEN
50/50
11.011
3151041BRUNSWICKG3
50/50
2.407
972187AH1-678 GEN
50/50
5.524
316447AC1-158 HLD
Solar/Wind Harmer
14.802
315651AD1-115 GEN
Solar/Wind Harmer
16.777
966001AG1-469 GEN
Solar/Wind Harmer
0.563
971223AH1-071 GEN
Solar/Wind Harmer
2.932
3143526WINTERP
Solar/Wind Harmer
-0.116
316036AC1-147 C
Solar/Wind Harmer
0.551
3150991CHESPKB
Adder
1.903
3150991CHESPKB
Adder
1.857
3142956BIRDNECK
Solar/Wind Harmer
1.094
316316AC1-027 C
Solar/Wind Harmer
0.626
3144356SAPONY
Solar/Wind Harmer
0.711
316185AD1-033 GEN
Solar/Wind Harmer
2.151
316240AF1-291 C
Solar/Wind Harmer
0.614
970657AG2-426 GEN
Solar/Wind Harmer
6.362
970657AG2-426 GEN
Solar/Wind Harmer
1.33
3145506HICKORY
Solar/Wind Harmer
-0.081
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
86.27
316339AD2-160 GEN
Solar/Wind Harmer
1.368
970933AG2-581 GEN
Solar/Wind Harmer
19.018
316018AA1-139 ULT2
Solar/Wind Harmer
1.737
316017AA1-139 ULT1
Solar/Wind Harmer
1.641
316236AE1-162_GEN
Solar/Wind Harmer
0.611
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.39
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.499
315697AD1-025 GEN
Solar/Wind Harmer
4.076
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.602
316433W1029_GEN2
Solar/Wind Harmer
3.602
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.574
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3150691DARBY 3
Adder
12.588
3150701DARBY 4
Adder
12.559
3150681DARBY 2
Adder
12.544
3150671DARBY 1
Adder
12.529
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
2.04
3146376EDENTON
Solar/Wind Harmer
0.575
3146376EDENTON
Solar/Wind Harmer
0.575
316075AC2-137 C
Solar/Wind Harmer
0.521
3142296MT RD221
Adder
0.545
970099AG2-077 GEN
Solar/Wind Harmer
23.878
316065AD1-022 GEN
Solar/Wind Harmer
9.304
316441AF1-014 GEN
Solar/Wind Harmer
1.254
3145893MURPHYS
Solar/Wind Harmer
0.518
3145893MURPHYS
Solar/Wind Harmer
-0.033
971741AH1-377 GEN
Solar/Wind Harmer
21.449
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
9.165
316181AB2-040 GEN
Solar/Wind Harmer
2.55
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.824
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.027
3145593CAROLNA
Solar/Wind Harmer
0.15
3145783HORNRTN
Solar/Wind Harmer
2.124
3145783HORNRTN
Solar/Wind Harmer
1.7
3145783HORNRTN
Solar/Wind Harmer
0.531
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3144293JTRSVLE
Adder
0.498
3144293JTRSVLE
Adder
0.42
3150341NORNECKC1
Adder
1.537
3150341NORNECKC1
Adder
1.525
3150391LDYSMT3
Adder
18.227
972195AH1-682 GEN
Adder
2.395
3145336SMITFLD
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.409
3151171GRAVELC
Adder
1.91
316072AD1-144
Solar/Wind Harmer
0.408
961611AG1-000B GEN
Solar/Wind Harmer
9.952
971647AH1-324 GEN
Solar/Wind Harmer
10.079
971069AG2-661 GEN
Solar/Wind Harmer
3.188
316458AB2-190 GEN2
Solar/Wind Harmer
2.037
970129AG2-093 GEN
Solar/Wind Harmer
4.593
316093AE2-104_GEN
Solar/Wind Harmer
5.849
3143096IRON208
Adder
0.749
3138126ROCKLANDING
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
-0.064
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
84.115
970919AG2-571 GEN
Solar/Wind Harmer
6.265
970087AG2-069 GEN
Solar/Wind Harmer
18.484
316159AE1-175 C
Solar/Wind Harmer
0.526
971317AH1-138 GEN
Solar/Wind Harmer
2.451
315800Z1-036_GEN1
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957481AF2-042 GEN
Solar/Wind Harmer
59.695
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3145663CRESWEL
Solar/Wind Harmer
-0.053
971163AH1-040 GEN
Solar/Wind Harmer
17.838
316023GEN1_S
Solar/Wind Harmer
1.275
315693AD1-088 GEN
Solar/Wind Harmer
9.429
962491AG1-098 GEN
Solar/Wind Harmer
12.593
970937AG2-583 GEN
Solar/Wind Harmer
13.457
971777AH1-397 GEN
Solar/Wind Harmer
2.187
3141843SHACKLE
Adder
0.846
3145893MURPHYS
Solar/Wind Harmer
-0.074
3145893MURPHYS
Solar/Wind Harmer
0.551
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.639
3141766HARMONY
Solar/Wind Harmer
-0.004
960081AF2-299 GEN
Solar/Wind Harmer
2.084
3146173TUNIS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.698
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.461
3138133OCRAN
Solar/Wind Harmer
-0.011
316011AB1-132 GEN
Solar/Wind Harmer
3.788
962571AG1-106 GEN
Solar/Wind Harmer
2.602
316190AA2-174 GEN
Solar/Wind Harmer
0.222
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
316174AB2-169 GEN
Solar/Wind Harmer
2.743
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.463
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316006AB2-029 C
Solar/Wind Helper
0.152
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.846
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.488
3150401LDYSMT4
Adder
18.261
3150371LDYSMT1
Adder
17.645
942461AE2-259 GEN
Solar/Wind Harmer
0.234
NYPJM->LTFIMP_NY
CLTF
2.76
LGEELTFEXP_LGEE->PJM
CLTF
1.015
LAGNLTFEXP_LAGN->PJM
CLTF
6.457
WECLTFEXP_WEC->PJM
CLTF
0.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.695
TVALTFEXP_TVA->PJM
CLTF
3.275
CPLELTFEXP_CPLE->PJM
CLTF
9.48
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.839
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.781
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.081
MECLTFEXP_MEC->PJM
CLTF
2.792
SIGELTFEXP_SIGE->PJM
CLTF
0.085

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P7-1: LN 2-2199_SRT-A-2


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2-2199_SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.41 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4901.61
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
3152261N ANNA2
50/50
17.342
3151771S ANNAG1
50/50
0.915
3151801S ANNAS2
50/50
0.47
3151761LOISA E
50/50
36.194
972183AH1-676 GEN
50/50
289.654
3150861SPRUNCD
50/50
0.914
3151031BRUNSWICKG2
50/50
2.407
316044AC1-158 PL1
Solar/Wind Harmer
6.731
316450AC1-158 RIC
Solar/Wind Harmer
1.795
316170AC1-121 GEN2
Solar/Wind Harmer
1.027
3147666LOUISA
Solar/Wind Harmer
-0.078
3132273ORANGE
Solar/Wind Harmer
-0.007
316313AB2-026
Solar/Wind Harmer
0.567
316258AE1-075 C
Solar/Wind Harmer
0.51
316405AF2-144 C
Solar/Wind Harmer
0.538
3143336POWHATN
Solar/Wind Harmer
2.119
315773AC2-141 GEN
Solar/Wind Harmer
8.631
315839AE2-212 C
Solar/Wind Harmer
0.619
944581AF1-123 GEN
Solar/Wind Harmer
93.163
944601AF1-125 GEN
Solar/Wind Harmer
91.709
315813AE1-149 C
Solar/Wind Harmer
12.797
3151101ELIZAR3
Adder
16.875
965281AG1-393 GEN
Solar/Wind Harmer
2.551
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.92
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.307
970661AG2-428 GEN
Solar/Wind Harmer
3.828
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.467
3151221GRAVEL6
Adder
13.054
3151171GRAVELC
Adder
2.512
961611AG1-000B GEN
Solar/Wind Harmer
4.246
315778AD1-151 GEN
Solar/Wind Harmer
17.454
970129AG2-093 GEN
Solar/Wind Harmer
11.34
970133AG2-095 GEN
Solar/Wind Harmer
2.265
3143096IRON208
Adder
0.749
3143096IRON208
Adder
0.734
316320Y1-086
Solar/Wind Harmer
1.176
316435W1029_GEN3
Solar/Wind Harmer
3.602
3144216WINCHST
Adder
0.666
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.43
970917AG2-570 GEN
Solar/Wind Harmer
49.496
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.591
970293AG2-193 GEN
Solar/Wind Harmer
2.436
316303AF2-085
50/50
3.711
971285AH1-108 GEN
50/50
1.495
315244AE2-183_ST
50/50
5.281
316164AC1-076 GEN
Solar/Wind Harmer
3.466
3147346CASHSCORNER
Solar/Wind Harmer
0.426
316233AE1-074 FULL
Solar/Wind Harmer
0.601
971281AH1-106 GEN
Solar/Wind Harmer
3.628
971283AH1-107 GEN
Solar/Wind Harmer
3.628
941031AE2-094 GEN
Solar/Wind Harmer
39.963
944011AF1-069 GEN
Solar/Wind Harmer
12.522
970673AG2-436 GEN
Solar/Wind Harmer
44.026
970673AG2-436 GEN
Solar/Wind Harmer
22.292
3143316POE
Solar/Wind Harmer
-0.082
971967AH1-528 GEN
Solar/Wind Harmer
38.978
3151081ELIZAR1
Adder
16.662
3151091ELIZAR2
Adder
16.373
3152611GOSPORTB
Adder
2.313
3152621GOSPORTC
Adder
1.963
3152601GOSPORTA
Adder
1.811
316315AB2-025 C
Solar/Wind Harmer
0.55
315814AE2-033 C
Solar/Wind Harmer
18.917
957871AF2-081 GEN
Solar/Wind Harmer
10.138
971445AH1-216 GEN
Solar/Wind Harmer
12.537
319010AE1-072 C
Solar/Wind Harmer
4.091
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.84
316349AD2-085 GEN
Solar/Wind Harmer
1.798
316311AC2-079 GEN
Solar/Wind Harmer
10.195
316305AF2-043 C
Solar/Wind Harmer
0.609
972265AH1-717 GEN
Adder
13.942
3151201GRAVEL4
Adder
13.069
3151191GRAVEL3
Adder
12.904
3151211GRAVEL5
Adder
12.904
316369SG1_INVT
Solar/Wind Harmer
3.601
316132AB2-190 GEN1
Solar/Wind Harmer
2.037
315835AF2-110_GEN
Solar/Wind Harmer
2.515
313526AB2-022
Solar/Wind Harmer
0.541
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.539
3146396TANGLEW
Solar/Wind Harmer
0.368
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.323
970581AG2-369 GEN
Solar/Wind Harmer
10.597
315611Z1-036_GEN2
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
20.303
316169AC1-164_GENC
Solar/Wind Harmer
17.54
315975AC1-164 GENB
Solar/Wind Harmer
0.601
316312AB1-027
Solar/Wind Harmer
0.647
957831AF2-077 GEN
Solar/Wind Harmer
0.576
3138283WHITEMARSH
Solar/Wind Harmer
0.03
971167AH1-042 GEN
Solar/Wind Harmer
18.438
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315816AE2-034 GEN
Solar/Wind Harmer
1.54
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.019
965291AG1-394 GEN
Solar/Wind Harmer
1.663
315732AD1-074 GEN1
Solar/Wind Harmer
3.783
315733AD1-074 GEN2
Solar/Wind Harmer
3.783
315735AD1-075 GEN1
Solar/Wind Harmer
1.892
316314AB2-024 C
Solar/Wind Harmer
1.588
316318V4-068
Solar/Wind Harmer
0.463
3145893MURPHYS
Solar/Wind Harmer
-0.05
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.117
315662AE1-191 GEN
Solar/Wind Harmer
2.236
315666AE1-190 GEN
Solar/Wind Harmer
0.559
316059AD1-063 C
Solar/Wind Harmer
0.419
946281AF1-292 GEN
Solar/Wind Harmer
0.415
957601AF2-054 GEN
Solar/Wind Harmer
0.553
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.619
3146043SEABORD
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.16
961941AG1-037 GEN
Solar/Wind Harmer
0.138
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315607AA1-063A GEN
Solar/Wind Harmer
1.849
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
3137643SOCKMAN
Solar/Wind Harmer
-0.072
972189AH1-679 GEN
Adder
2.703
3138133OCRAN
Solar/Wind Harmer
-0.005
315652AC1-086 GEN
Solar/Wind Harmer
20.367
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.057
3145796HORNRTN
Solar/Wind Harmer
-0.007
972205AH1-687 GEN
Adder
6.589
3150411LDYSMT5
Adder
18.318
3150381LDYSMT2
Adder
17.531
972213AH1-691 GEN
Adder
2.966
972215AH1-692 GEN
Adder
2.966
970285AG2-188 GEN
Solar/Wind Harmer
14.082
3152251N ANNA1
50/50
17.343
971507AH1-251 GEN
50/50
12.192
3151791S ANNAG2
50/50
0.915
3151781S ANNAS1
50/50
0.47
3151741LOISA C
50/50
0.971
3151751LOISA D
50/50
17.753
970119AG2-088 GEN
50/50
27.833
3150851SPRUNCC
50/50
0.914
315243AE2-183_GT3
50/50
3.054
3151051BRUNSWICKS1
50/50
4.996
3151021BRUNSWICKG1
50/50
2.407
316045AC1-158 PL2
Solar/Wind Harmer
21.532
316254AC1-120 GEN1
Solar/Wind Harmer
3.082
3147666LOUISA
Solar/Wind Harmer
-0.136
316192AB2-158 GEN
Solar/Wind Harmer
4.034
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.116
940641AE2-051 GEN
Solar/Wind Harmer
20.412
939411AE1-173 GEN
Solar/Wind Harmer
107.132
3143336POWHATN
Solar/Wind Harmer
2.493
316294AC1-161 GEN
Solar/Wind Harmer
6.674
944591AF1-124 GEN
Solar/Wind Harmer
93.498
316375AC2-012 GEN
Solar/Wind Harmer
7.063
3150981CHESPKA
Adder
2.268
970659AG2-427 GEN
Solar/Wind Harmer
10.833
316381AD1-082 GEN
Solar/Wind Harmer
1.869
316336AC2-165 C
Solar/Wind Harmer
3.539
315671AE2-027_GEN
Solar/Wind Harmer
15.27
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
21.6
316388AE2-253 GEN
Solar/Wind Harmer
1.368
3145336SMITFLD
Solar/Wind Harmer
-0.081
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.409
3151171GRAVELC
Adder
1.91
316072AD1-144
Solar/Wind Harmer
0.408
961611AG1-000B GEN
Solar/Wind Harmer
9.952
971647AH1-324 GEN
Solar/Wind Harmer
10.079
971069AG2-661 GEN
Solar/Wind Harmer
3.188
316458AB2-190 GEN2
Solar/Wind Harmer
2.037
970129AG2-093 GEN
Solar/Wind Harmer
4.593
316093AE2-104_GEN
Solar/Wind Harmer
5.849
3143096IRON208
Adder
0.749
3138126ROCKLANDING
Solar/Wind Harmer
0.061
3146516WINFALL
Solar/Wind Harmer
-0.064
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
84.115
970919AG2-571 GEN
Solar/Wind Harmer
6.265
970087AG2-069 GEN
Solar/Wind Harmer
18.484
316159AE1-175 C
Solar/Wind Harmer
0.526
971317AH1-138 GEN
Solar/Wind Harmer
2.451
315800Z1-036_GEN1
Solar/Wind Harmer
4.839
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.05
3142416OLDCHRC
Solar/Wind Harmer
-0.019
957481AF2-042 GEN
Solar/Wind Harmer
59.695
3142433PROV 92
Solar/Wind Harmer
-0.076
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
3145663CRESWEL
Solar/Wind Harmer
-0.053
971163AH1-040 GEN
Solar/Wind Harmer
17.838
316023GEN1_S
Solar/Wind Harmer
1.275
315693AD1-088 GEN
Solar/Wind Harmer
9.429
962491AG1-098 GEN
Solar/Wind Harmer
12.593
970937AG2-583 GEN
Solar/Wind Harmer
13.457
971777AH1-397 GEN
Solar/Wind Harmer
2.187
3141843SHACKLE
Adder
0.846
3145893MURPHYS
Solar/Wind Harmer
-0.074
3145893MURPHYS
Solar/Wind Harmer
0.551
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.639
3141766HARMONY
Solar/Wind Harmer
-0.004
960081AF2-299 GEN
Solar/Wind Harmer
2.084
3146173TUNIS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.698
3145683EARLEYS
Solar/Wind Harmer
-0.018
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Adder
1.461
3138133OCRAN
Solar/Wind Harmer
-0.011
316011AB1-132 GEN
Solar/Wind Harmer
3.788
962571AG1-106 GEN
Solar/Wind Harmer
2.602
316190AA2-174 GEN
Solar/Wind Harmer
0.222
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.059
3145796HORNRTN
Solar/Wind Harmer
-0.018
316174AB2-169 GEN
Solar/Wind Harmer
2.743
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.463
972197AH1-683 GEN
Adder
2.852
972219AH1-694 GEN
Adder
2.053
316006AB2-029 C
Solar/Wind Helper
0.152
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.934
3142433PROV 92
Adder
0.33
3142433PROV 92
Adder
0.33
315614AA2-178 GEN
Solar/Wind Harmer
2.053
316365GEN2_N
Solar/Wind Harmer
1.275
3156081AA2-088 GEN
Solar/Wind Harmer
6.102
971157AH1-035 GEN
Solar/Wind Harmer
2.344
315737AD1-076 GEN
Solar/Wind Harmer
3.555
3141843SHACKLE
Adder
0.846
316203AE2-005 GEN
Solar/Wind Harmer
7.84
3145893MURPHYS
Solar/Wind Harmer
0.13
3145893MURPHYS
Solar/Wind Harmer
-0.019
3146206CASHIE
Solar/Wind Harmer
-0.018
316280AD1-041 GEN
Solar/Wind Harmer
1.397
3141766HARMONY
Solar/Wind Harmer
1.65
957521AF2-046 GEN
Solar/Wind Harmer
14.595
961681AG1-008 GEN
Solar/Wind Harmer
14.595
966621AG1-532 GEN
Solar/Wind Harmer
0.376
316156AD2-030 GEN
Solar/Wind Harmer
0.493
3141873WAN 176
Solar/Wind Harmer
2.193
316473AC1-191 GEN
Solar/Wind Harmer
1.984
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.593
316486AD2-202 GEN
Solar/Wind Harmer
0.467
3156021HOLLOMANSOL
Solar/Wind Harmer
2.471
316463AE2-346 GEN
Solar/Wind Harmer
0.297
316140AB2-099
Solar/Wind Harmer
0.124
962331AG1-082 GEN
Solar/Wind Harmer
2.291
970909AG2-566 GEN
Solar/Wind Harmer
1.74
313506AB2-031 GEN
Solar/Wind Harmer
1.47
3146263WOODLND
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
316317KELFORD C
Solar/Wind Harmer
0.846
3145823KELFORD
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.011
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.071
3145796HORNRTN
Solar/Wind Harmer
-0.018
942461AE2-259 GEN
Solar/Wind Harmer
2.672
3144293JTRSVLE
Adder
0.498
3150351NORNECKC2
Adder
1.488
3150401LDYSMT4
Adder
18.261
3150371LDYSMT1
Adder
17.645
971133AH1-012 GEN
50/50
5.76
3151731LOISA B
50/50
17.753
3151721LOISA A
50/50
17.662
970533AG2-339 GEN
50/50
16.862
970531AG2-338 GEN
50/50
6.745
315242AE2-183_GT2
50/50
3.054
315241AE2-183_GT1
50/50
3.036
972185AH1-677 GEN
50/50
11.011
3151041BRUNSWICKG3
50/50
2.407
972187AH1-678 GEN
50/50
5.524
316447AC1-158 HLD
Solar/Wind Harmer
14.802
315651AD1-115 GEN
Solar/Wind Harmer
16.777
966001AG1-469 GEN
Solar/Wind Harmer
0.563
971223AH1-071 GEN
Solar/Wind Harmer
2.932
3143526WINTERP
Solar/Wind Harmer
-0.116
316036AC1-147 C
Solar/Wind Harmer
0.551
3150991CHESPKB
Adder
1.903
3150991CHESPKB
Adder
1.857
3142956BIRDNECK
Solar/Wind Harmer
1.094
316316AC1-027 C
Solar/Wind Harmer
0.626
3144356SAPONY
Solar/Wind Harmer
0.711
316185AD1-033 GEN
Solar/Wind Harmer
2.151
316240AF1-291 C
Solar/Wind Harmer
0.614
970657AG2-426 GEN
Solar/Wind Harmer
6.362
970657AG2-426 GEN
Solar/Wind Harmer
1.33
3145506HICKORY
Solar/Wind Harmer
-0.081
3145506HICKORY
Solar/Wind Harmer
-0.049
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
86.27
316339AD2-160 GEN
Solar/Wind Harmer
1.368
970933AG2-581 GEN
Solar/Wind Harmer
19.018
316018AA1-139 ULT2
Solar/Wind Harmer
1.737
316017AA1-139 ULT1
Solar/Wind Harmer
1.641
316236AE1-162_GEN
Solar/Wind Harmer
0.611
3137176SLIGO L2192
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
2.39
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.499
315697AD1-025 GEN
Solar/Wind Harmer
4.076
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.602
316433W1029_GEN2
Solar/Wind Harmer
3.602
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.574
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3146626S HERTFORD
Solar/Wind Harmer
-0.02
3150691DARBY 3
Adder
12.588
3150701DARBY 4
Adder
12.559
3150681DARBY 2
Adder
12.544
3150671DARBY 1
Adder
12.529
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
2.04
3146376EDENTON
Solar/Wind Harmer
0.575
3146376EDENTON
Solar/Wind Harmer
0.575
316075AC2-137 C
Solar/Wind Harmer
0.521
3142296MT RD221
Adder
0.545
970099AG2-077 GEN
Solar/Wind Harmer
23.878
316065AD1-022 GEN
Solar/Wind Harmer
9.304
316441AF1-014 GEN
Solar/Wind Harmer
1.254
3145893MURPHYS
Solar/Wind Harmer
0.518
3145893MURPHYS
Solar/Wind Harmer
-0.033
971741AH1-377 GEN
Solar/Wind Harmer
21.449
966871AG1-558 GEN
Solar/Wind Harmer
0.554
966871AG1-558 GEN
Solar/Wind Harmer
0.19
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
970301AG2-198 GEN
Solar/Wind Harmer
9.165
316181AB2-040 GEN
Solar/Wind Harmer
2.55
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.824
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.027
3145593CAROLNA
Solar/Wind Harmer
0.15
3145783HORNRTN
Solar/Wind Harmer
2.124
3145783HORNRTN
Solar/Wind Harmer
1.7
3145783HORNRTN
Solar/Wind Harmer
0.531
3145783HORNRTN
Solar/Wind Harmer
0.212
3145796HORNRTN
Solar/Wind Harmer
-0.053
3144293JTRSVLE
Adder
0.498
3144293JTRSVLE
Adder
0.42
3150341NORNECKC1
Adder
1.537
3150341NORNECKC1
Adder
1.525
3150391LDYSMT3
Adder
18.227
972195AH1-682 GEN
Adder
2.395
NYPJM->LTFIMP_NY
CLTF
2.76
LGEELTFEXP_LGEE->PJM
CLTF
1.015
LAGNLTFEXP_LAGN->PJM
CLTF
6.457
WECLTFEXP_WEC->PJM
CLTF
0.483
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.695
TVALTFEXP_TVA->PJM
CLTF
3.275
CPLELTFEXP_CPLE->PJM
CLTF
9.48
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.839
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.781
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.081
MECLTFEXP_MEC->PJM
CLTF
2.792
SIGELTFEXP_SIGE->PJM
CLTF
0.085

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P2-2: GERMANNA_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P2-2: GERMANNA_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:120.67 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:4754.21
MW Contribution:10.48
Bus #Bus NameTypeMW Contribution
316303AF2-085
50/50
3.67
971285AH1-108 GEN
50/50
1.479
315244AE2-183_ST
50/50
5.225
316164AC1-076 GEN
Solar/Wind Harmer
2.601
3147346CASHSCORNER
Solar/Wind Harmer
0.387
316233AE1-074 FULL
Solar/Wind Harmer
0.594
971281AH1-106 GEN
Solar/Wind Harmer
3.589
971283AH1-107 GEN
Solar/Wind Harmer
3.589
941031AE2-094 GEN
Solar/Wind Harmer
39.549
944011AF1-069 GEN
Solar/Wind Harmer
12.392
970673AG2-436 GEN
Solar/Wind Harmer
43.562
970673AG2-436 GEN
Solar/Wind Harmer
22.057
3143316POE
Solar/Wind Harmer
-0.081
971967AH1-528 GEN
Solar/Wind Harmer
38.553
3151081ELIZAR1
Adder
16.492
3151091ELIZAR2
Adder
16.205
3152611GOSPORTB
Adder
2.29
3152621GOSPORTC
Adder
1.943
3152601GOSPORTA
Adder
1.792
316315AB2-025 C
Solar/Wind Harmer
0.544
315814AE2-033 C
Solar/Wind Harmer
18.717
957871AF2-081 GEN
Solar/Wind Harmer
10.033
971445AH1-216 GEN
Solar/Wind Harmer
12.409
319010AE1-072 C
Solar/Wind Harmer
4.049
3146406KITTY HAWK
Solar/Wind Harmer
0.017
315833AF1-017_GEN
Solar/Wind Harmer
3.8
316349AD2-085 GEN
Solar/Wind Harmer
1.779
316311AC2-079 GEN
Solar/Wind Harmer
10.09
316305AF2-043 C
Solar/Wind Harmer
0.603
972265AH1-717 GEN
Adder
13.799
3151201GRAVEL4
Adder
12.936
3151191GRAVEL3
Adder
12.772
3151211GRAVEL5
Adder
12.772
316369SG1_INVT
Solar/Wind Harmer
3.564
316132AB2-190 GEN1
Solar/Wind Harmer
2.016
315835AF2-110_GEN
Solar/Wind Harmer
2.489
313526AB2-022
Solar/Wind Harmer
0.536
3146486SUNBURY
Solar/Wind Harmer
-0.02
3146486SUNBURY
Solar/Wind Harmer
-0.02
316321Z2-027
Solar/Wind Harmer
0.533
3146396TANGLEW
Solar/Wind Harmer
0.364
3145176PASQUOTANK
Solar/Wind Harmer
-0.012
970085AG2-068 GEN
Solar/Wind Harmer
12.189
970581AG2-369 GEN
Solar/Wind Harmer
10.482
315611Z1-036_GEN2
Solar/Wind Harmer
4.788
3130156CHOWAN
Solar/Wind Harmer
-0.019
3130156CHOWAN
Solar/Wind Harmer
-0.019
315976AC1-164 GENA
Solar/Wind Harmer
20.098
316169AC1-164_GENC
Solar/Wind Harmer
17.362
315975AC1-164 GENB
Solar/Wind Harmer
0.595
957831AF2-077 GEN
Solar/Wind Harmer
0.571
3138283WHITEMARSH
Solar/Wind Harmer
0.029
316312AB1-027
Solar/Wind Harmer
0.64
971167AH1-042 GEN
Solar/Wind Harmer
18.254
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
315816AE2-034 GEN
Solar/Wind Harmer
1.523
3143873LANEXA
Solar/Wind Harmer
-0.011
3130546PLYMOUTH
Solar/Wind Harmer
-0.018
965291AG1-394 GEN
Solar/Wind Harmer
1.644
315732AD1-074 GEN1
Solar/Wind Harmer
3.741
315733AD1-074 GEN2
Solar/Wind Harmer
3.741
315735AD1-075 GEN1
Solar/Wind Harmer
1.871
316314AB2-024 C
Solar/Wind Harmer
1.573
316318V4-068
Solar/Wind Harmer
0.458
3145893MURPHYS
Solar/Wind Harmer
-0.049
3145893MURPHYS
Solar/Wind Harmer
-0.018
315662AE1-191 GEN
Solar/Wind Harmer
2.214
315666AE1-190 GEN
Solar/Wind Harmer
0.553
316059AD1-063 C
Solar/Wind Harmer
0.415
3146206CASHIE
Solar/Wind Harmer
-0.018
970601AG2-382 GEN
Solar/Wind Harmer
8.029
946281AF1-292 GEN
Solar/Wind Harmer
0.41
957601AF2-054 GEN
Solar/Wind Harmer
0.547
3141873WAN 176
Solar/Wind Harmer
-0.004
316087AB2-174 GEN
Solar/Wind Harmer
2.588
3146043SEABORD
Solar/Wind Harmer
-0.018
3145513AHOSKIE
Solar/Wind Harmer
0.158
961941AG1-037 GEN
Solar/Wind Harmer
0.136
3145513AHOSKIE
Solar/Wind Harmer
-0.018
315607AA1-063A GEN
Solar/Wind Harmer
1.827
3145683EARLEYS
Solar/Wind Harmer
-0.036
3145683EARLEYS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
3141913WHIT STONE
Solar/Wind Harmer
-0.018
972189AH1-679 GEN
Adder
2.678
3138133OCRAN
Solar/Wind Harmer
-0.005
3137643SOCKMAN
Solar/Wind Harmer
-0.071
315652AC1-086 GEN
Solar/Wind Harmer
20.135
3141783LANCAST
Solar/Wind Harmer
-0.011
3141783LANCAST
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.056
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146033SCOT NK
Solar/Wind Harmer
-0.069
962981AG1-147 GEN
Solar/Wind Harmer
7.624
970831AG2-522 GEN
Solar/Wind Harmer
8.659
972205AH1-687 GEN
Adder
6.375
3150411LDYSMT5
Adder
18.197
3150381LDYSMT2
Adder
17.416
972213AH1-691 GEN
Adder
2.946
972215AH1-692 GEN
Adder
2.946
3152261N ANNA2
50/50
17.234
3151771S ANNAG1
50/50
0.836
3151801S ANNAS2
50/50
0.43
3151761LOISA E
50/50
32.955
972183AH1-676 GEN
50/50
263.019
3150861SPRUNCD
50/50
0.904
3151031BRUNSWICKG2
50/50
2.381
316044AC1-158 PL1
Solar/Wind Harmer
6.712
316450AC1-158 RIC
Solar/Wind Harmer
1.79
3147666LOUISA
Solar/Wind Harmer
-0.074
3132273ORANGE
Solar/Wind Harmer
-0.005
316313AB2-026
Solar/Wind Harmer
0.556
316258AE1-075 C
Solar/Wind Harmer
0.501
316405AF2-144 C
Solar/Wind Harmer
0.528
3143336POWHATN
Solar/Wind Harmer
2.08
315773AC2-141 GEN
Solar/Wind Harmer
8.544
315839AE2-212 C
Solar/Wind Harmer
0.612
944581AF1-123 GEN
Solar/Wind Harmer
92.211
944601AF1-125 GEN
Solar/Wind Harmer
90.772
315813AE1-149 C
Solar/Wind Harmer
12.666
3151101ELIZAR3
Adder
16.703
965281AG1-393 GEN
Solar/Wind Harmer
2.525
3144873MCLAUGH
Solar/Wind Harmer
-0.001
970659AG2-427 GEN
Solar/Wind Harmer
1.9
3144536CHRHLND
Solar/Wind Harmer
-0.003
316083AB2-161 GEN
Solar/Wind Harmer
3.273
970661AG2-428 GEN
Solar/Wind Harmer
3.788
3145336SMITFLD
Solar/Wind Harmer
-0.008
3146456SLIGO L269
Solar/Wind Harmer
-0.02
971153AH1-033 GEN
Solar/Wind Harmer
2.442
3151221GRAVEL6
Adder
12.921
3151171GRAVELC
Adder
2.486
961611AG1-000B GEN
Solar/Wind Harmer
4.203
315778AD1-151 GEN
Solar/Wind Harmer
17.275
970129AG2-093 GEN
Solar/Wind Harmer
11.224
970133AG2-095 GEN
Solar/Wind Harmer
2.241
3143096IRON208
Adder
0.741
3143096IRON208
Adder
0.727
316320Y1-086
Solar/Wind Harmer
1.163
316435W1029_GEN3
Solar/Wind Harmer
3.565
3144216WINCHST
Adder
0.66
3146516WINFALL
Solar/Wind Harmer
-0.02
3150921YORKTN3
Adder
4.385
970917AG2-570 GEN
Solar/Wind Harmer
48.958
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3145273HOLLAND
Solar/Wind Harmer
-0.015
3142946ENON
Solar/Wind Harmer
-0.006
316382AG1-145 C
Solar/Wind Harmer
0.585
970293AG2-193 GEN
Solar/Wind Harmer
2.411
3146376EDENTON
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
1.915
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
315614AA2-178 GEN
Solar/Wind Harmer
2.031
316365GEN2_N
Solar/Wind Harmer
1.26
3156081AA2-088 GEN
Solar/Wind Harmer
6.034
971157AH1-035 GEN
Solar/Wind Harmer
2.319
315737AD1-076 GEN
Solar/Wind Harmer
3.516
3141843SHACKLE
Adder
0.837
316203AE2-005 GEN
Solar/Wind Harmer
7.763
3145893MURPHYS
Solar/Wind Harmer
0.128
3145893MURPHYS
Solar/Wind Harmer
-0.018
316280AD1-041 GEN
Solar/Wind Harmer
1.384
3141766HARMONY
Solar/Wind Harmer
1.634
3146206CASHIE
Solar/Wind Harmer
-0.018
957521AF2-046 GEN
Solar/Wind Harmer
14.432
961681AG1-008 GEN
Solar/Wind Harmer
14.432
966621AG1-532 GEN
Solar/Wind Harmer
0.371
316156AD2-030 GEN
Solar/Wind Harmer
0.489
3141873WAN 176
Solar/Wind Harmer
2.171
316473AC1-191 GEN
Solar/Wind Harmer
1.965
3146173TUNIS
Solar/Wind Harmer
-0.018
316478AD1-087 GEN
Solar/Wind Harmer
1.572
316486AD2-202 GEN
Solar/Wind Harmer
0.46
3156021HOLLOMANSOL
Solar/Wind Harmer
2.444
316463AE2-346 GEN
Solar/Wind Harmer
0.293
316140AB2-099
Solar/Wind Harmer
0.122
962331AG1-082 GEN
Solar/Wind Harmer
2.266
313506AB2-031 GEN
Solar/Wind Harmer
1.452
316170AC1-121 GEN2
Solar/Wind Harmer
0.484
3146263WOODLND
Solar/Wind Harmer
-0.018
970909AG2-566 GEN
Solar/Wind Harmer
1.707
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3147043LAWRENC
Solar/Wind Harmer
-0.011
316317KELFORD C
Solar/Wind Harmer
0.837
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.018
3146926FARMVIL
Solar/Wind Harmer
-0.01
962971AG1-146 GEN
Solar/Wind Harmer
3.267
942461AE2-259 GEN
Solar/Wind Harmer
2.615
3147133PAMPLIN
Solar/Wind Harmer
-0.054
3144293JTRSVLE
Adder
0.489
3150351NORNECKC2
Adder
1.474
3150401LDYSMT4
Adder
18.141
3150371LDYSMT1
Adder
17.529
971193AH1-056 GEN
Solar/Wind Harmer
2.03
971133AH1-012 GEN
50/50
5.563
3151731LOISA B
50/50
16.164
3151721LOISA A
50/50
16.081
970533AG2-339 GEN
50/50
16.687
970531AG2-338 GEN
50/50
6.675
315242AE2-183_GT2
50/50
3.022
315241AE2-183_GT1
50/50
3.003
972185AH1-677 GEN
50/50
10.895
3151041BRUNSWICKG3
50/50
2.381
972187AH1-678 GEN
50/50
5.465
316447AC1-158 HLD
Solar/Wind Harmer
14.76
966001AG1-469 GEN
Solar/Wind Harmer
0.484
971223AH1-071 GEN
Solar/Wind Harmer
2.899
3143526WINTERP
Solar/Wind Harmer
-0.114
316036AC1-147 C
Solar/Wind Harmer
0.545
3150991CHESPKB
Adder
1.883
3150991CHESPKB
Adder
1.838
3142956BIRDNECK
Solar/Wind Harmer
1.083
316316AC1-027 C
Solar/Wind Harmer
0.62
316185AD1-033 GEN
Solar/Wind Harmer
2.129
3144356SAPONY
Solar/Wind Harmer
0.704
316240AF1-291 C
Solar/Wind Harmer
0.608
970657AG2-426 GEN
Solar/Wind Harmer
6.296
970657AG2-426 GEN
Solar/Wind Harmer
1.317
3145506HICKORY
Solar/Wind Harmer
-0.08
3145506HICKORY
Solar/Wind Harmer
-0.048
3145506HICKORY
Solar/Wind Harmer
-0.012
944641AF1-129 GEN
Adder
85.383
316339AD2-160 GEN
Solar/Wind Harmer
1.354
316018AA1-139 ULT2
Solar/Wind Harmer
1.719
316017AA1-139 ULT1
Solar/Wind Harmer
1.624
316236AE1-162_GEN
Solar/Wind Harmer
0.605
970933AG2-581 GEN
Solar/Wind Harmer
18.801
3137176SLIGO L2192
Solar/Wind Harmer
-0.079
3146456SLIGO L269
Solar/Wind Harmer
2.366
3130086AYDLETT
Solar/Wind Harmer
-0.08
316033AB2-134 GEN
Solar/Wind Harmer
6.432
315697AD1-025 GEN
Solar/Wind Harmer
4.034
3146386ELIZ CT
Solar/Wind Harmer
-0.02
316431W1029_GEN1
Solar/Wind Harmer
3.565
316433W1029_GEN2
Solar/Wind Harmer
3.565
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3146516WINFALL
Solar/Wind Harmer
-0.02
3142366NRTHEST
Adder
0.568
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3146626S HERTFORD
Solar/Wind Harmer
-0.019
3150691DARBY 3
Adder
12.459
3150701DARBY 4
Adder
12.43
3150681DARBY 2
Adder
12.416
3150671DARBY 1
Adder
12.401
3142946ENON
Solar/Wind Harmer
-0.002
315742AE1-103 GEN
Solar/Wind Harmer
2.019
3146376EDENTON
Solar/Wind Harmer
0.569
3146376EDENTON
Solar/Wind Harmer
0.569
316075AC2-137 C
Solar/Wind Harmer
0.516
3142296MT RD221
Adder
0.54
970099AG2-077 GEN
Solar/Wind Harmer
23.572
316441AF1-014 GEN
Solar/Wind Harmer
1.241
316065AD1-022 GEN
Solar/Wind Harmer
9.202
3145893MURPHYS
Solar/Wind Harmer
0.513
3145893MURPHYS
Solar/Wind Harmer
-0.033
966871AG1-558 GEN
Solar/Wind Harmer
0.549
966871AG1-558 GEN
Solar/Wind Harmer
0.188
3146173TUNIS
Solar/Wind Harmer
-0.018
3146173TUNIS
Solar/Wind Harmer
-0.018
971741AH1-377 GEN
Solar/Wind Harmer
21.065
316181AB2-040 GEN
Solar/Wind Harmer
2.52
970301AG2-198 GEN
Solar/Wind Harmer
8.99
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.018
3142666NORTHAMPTON
Solar/Wind Harmer
-0.011
316426AA2-053 GEN
Solar/Wind Harmer
1.803
3145593CAROLNA
Solar/Wind Harmer
-0.018
3145593CAROLNA
Solar/Wind Harmer
-0.018
966811AG1-552 GEN
Solar/Wind Harmer
2.003
3145593CAROLNA
Solar/Wind Harmer
0.148
3145783HORNRTN
Solar/Wind Harmer
2.099
3145783HORNRTN
Solar/Wind Harmer
1.68
3145783HORNRTN
Solar/Wind Harmer
0.525
3145783HORNRTN
Solar/Wind Harmer
0.21
3145796HORNRTN
Solar/Wind Harmer
-0.053
3147133PAMPLIN
Solar/Wind Harmer
-0.017
3147133PAMPLIN
Solar/Wind Harmer
-0.014
3144293JTRSVLE
Adder
0.489
3144293JTRSVLE
Adder
0.412
3150341NORNECKC1
Adder
1.523
3150341NORNECKC1
Adder
1.511
3150391LDYSMT3
Adder
18.107
972195AH1-682 GEN
Adder
2.379
3152251N ANNA1
50/50
17.235
971507AH1-251 GEN
50/50
10.732
3151791S ANNAG2
50/50
0.836
3151781S ANNAS1
50/50
0.43
3151741LOISA C
50/50
0.884
3151751LOISA D
50/50
16.164
970119AG2-088 GEN
50/50
27.523
3150851SPRUNCC
50/50
0.904
315243AE2-183_GT3
50/50
3.022
3151051BRUNSWICKS1
50/50
4.943
3151021BRUNSWICKG1
50/50
2.381
316045AC1-158 PL2
Solar/Wind Harmer
21.471
3147666LOUISA
Solar/Wind Harmer
-0.13
316192AB2-158 GEN
Solar/Wind Harmer
3.833
3143226MDLTHAN
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.114
940641AE2-051 GEN
Solar/Wind Harmer
20.206
939411AE1-173 GEN
Solar/Wind Harmer
106.047
3143336POWHATN
Solar/Wind Harmer
2.448
316294AC1-161 GEN
Solar/Wind Harmer
6.606
944591AF1-124 GEN
Solar/Wind Harmer
92.543
316375AC2-012 GEN
Solar/Wind Harmer
6.991
3150981CHESPKA
Adder
2.245
970659AG2-427 GEN
Solar/Wind Harmer
10.721
316381AD1-082 GEN
Solar/Wind Harmer
1.849
315671AE2-027_GEN
Solar/Wind Harmer
15.114
3142543TWELFTH
Solar/Wind Harmer
-0.002
970661AG2-428 GEN
Solar/Wind Harmer
21.377
316388AE2-253 GEN
Solar/Wind Harmer
1.354
3145336SMITFLD
Solar/Wind Harmer
-0.08
3146456SLIGO L269
Solar/Wind Harmer
-0.02
316246AF1-032 C
Solar/Wind Harmer
0.404
3151171GRAVELC
Adder
1.89
316072AD1-144
Solar/Wind Harmer
0.404
961611AG1-000B GEN
Solar/Wind Harmer
9.85
316336AC2-165 C
Solar/Wind Harmer
3.467
971647AH1-324 GEN
Solar/Wind Harmer
9.976
971069AG2-661 GEN
Solar/Wind Harmer
3.155
316458AB2-190 GEN2
Solar/Wind Harmer
2.016
970129AG2-093 GEN
Solar/Wind Harmer
4.546
316093AE2-104_GEN
Solar/Wind Harmer
5.788
3143096IRON208
Adder
0.741
3138126ROCKLANDING
Solar/Wind Harmer
0.06
3146516WINFALL
Solar/Wind Harmer
-0.063
3146516WINFALL
Solar/Wind Harmer
-0.02
944631AF1-128 GEN
Adder
83.254
970919AG2-571 GEN
Solar/Wind Harmer
6.197
970087AG2-069 GEN
Solar/Wind Harmer
18.283
316159AE1-175 C
Solar/Wind Harmer
0.521
971317AH1-138 GEN
Solar/Wind Harmer
2.426
315800Z1-036_GEN1
Solar/Wind Harmer
4.788
3130156CHOWAN
Solar/Wind Harmer
-0.019
3142416OLDCHRC
Solar/Wind Harmer
-0.049
3142416OLDCHRC
Solar/Wind Harmer
-0.019
3142433PROV 92
Solar/Wind Harmer
-0.075
3142433PROV 92
Adder
0.327
3142433PROV 92
Adder
0.327
957481AF2-042 GEN
Solar/Wind Harmer
58.931
3145663CRESWEL
Solar/Wind Harmer
-0.052
971163AH1-040 GEN
Solar/Wind Harmer
17.646
316023GEN1_S
Solar/Wind Harmer
1.26
315693AD1-088 GEN
Solar/Wind Harmer
9.296
962491AG1-098 GEN
Solar/Wind Harmer
12.413
971777AH1-397 GEN
Solar/Wind Harmer
2.165
3141843SHACKLE
Adder
0.837
3145893MURPHYS
Solar/Wind Harmer
-0.073
3145893MURPHYS
Solar/Wind Harmer
0.545
3141766HARMONY
Solar/Wind Harmer
-0.004
3146206CASHIE
Solar/Wind Harmer
-0.018
971547AH1-271 GEN
Solar/Wind Harmer
4.588
960081AF2-299 GEN
Solar/Wind Harmer
2.059
970937AG2-583 GEN
Solar/Wind Harmer
13.101
3146173TUNIS
Solar/Wind Harmer
-0.018
3145683EARLEYS
Solar/Wind Harmer
-0.018
971795AH1-408 GEN
Solar/Wind Harmer
13.527
316254AC1-120 GEN1
Solar/Wind Harmer
1.451
3146263WOODLND
Solar/Wind Harmer
-0.018
3138133OCRAN
Solar/Wind Harmer
-0.011
3147043LAWRENC
Adder
1.442
316011AB1-132 GEN
Solar/Wind Harmer
3.745
962571AG1-106 GEN
Solar/Wind Harmer
2.573
316190AA2-174 GEN
Solar/Wind Harmer
0.219
3145823KELFORD
Solar/Wind Harmer
-0.018
3145963POPLR C
Solar/Wind Harmer
-0.018
3145783HORNRTN
Solar/Wind Harmer
-0.018
3145796HORNRTN
Solar/Wind Harmer
-0.058
3145796HORNRTN
Solar/Wind Harmer
-0.018
316174AB2-169 GEN
Solar/Wind Harmer
2.712
3146926FARMVIL
Solar/Wind Harmer
-0.01
3144293JTRSVLE
Adder
0.489
3150351NORNECKC2
Adder
1.45
972197AH1-683 GEN
Adder
2.833
972219AH1-694 GEN
Adder
2.04
NYPJM->LTFIMP_NY
CLTF
2.701
LAGNLTFEXP_LAGN->PJM
CLTF
6.351
LGEELTFEXP_LGEE->PJM
CLTF
0.994
WECLTFEXP_WEC->PJM
CLTF
0.473
CBM South 2LTFEXP_CBM-S2->PJM
CBM
20.405
TVALTFEXP_TVA->PJM
CLTF
3.22
CPLELTFEXP_CPLE->PJM
CLTF
9.356
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.269
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.456
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.892
MECLTFEXP_MEC->PJM
CLTF
2.739
SIGELTFEXP_SIGE->PJM
CLTF
0.083

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.1 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3842.65
MW Contribution:14.6
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.636
3150981CHESPKA
50/50
4.335
970017AG2-010 GEN
50/50
18.774
316294AC1-161 GEN
Solar/Wind Harmer
13.897
944591AF1-124 GEN
Solar/Wind Harmer
175.385
316388AE2-253 GEN
Solar/Wind Harmer
2.485
316375AC2-012 GEN
Solar/Wind Harmer
12.723
3146456SLIGO L269
Solar/Wind Harmer
-0.036
316246AF1-032 C
Solar/Wind Harmer
0.718
3146516WINFALL
Solar/Wind Harmer
-0.111
3146516WINFALL
Solar/Wind Harmer
-0.035
939411AE1-173 GEN
Solar/Wind Harmer
172.22
316072AD1-144
Solar/Wind Harmer
0.687
316093AE2-104_GEN
Solar/Wind Harmer
9.772
315800Z1-036_GEN1
Solar/Wind Harmer
8.3
940641AE2-051 GEN
Solar/Wind Harmer
31.321
3130156CHOWAN
Solar/Wind Harmer
-0.033
3145663CRESWEL
Solar/Wind Harmer
-0.087
971163AH1-040 GEN
Solar/Wind Harmer
29.428
3145336SMITFLD
Solar/Wind Harmer
-0.124
3138126ROCKLANDING
Solar/Wind Harmer
0.095
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.327
971317AH1-138 GEN
Solar/Wind Harmer
3.528
3145893MURPHYS
Solar/Wind Harmer
-0.111
3145893MURPHYS
Solar/Wind Harmer
0.828
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
2.607
3145683EARLEYS
Solar/Wind Harmer
-0.027
316174AB2-169 GEN
Solar/Wind Harmer
4.218
970919AG2-571 GEN
Solar/Wind Harmer
8.634
970087AG2-069 GEN
Solar/Wind Harmer
25.458
3146263WOODLND
Solar/Wind Harmer
-0.027
3145823KELFORD
Solar/Wind Harmer
-0.026
970661AG2-428 GEN
Solar/Wind Harmer
27.486
3146293MARTNCO
Solar/Wind Harmer
0.159
316190AA2-174 GEN
Solar/Wind Harmer
0.309
961611AG1-000B GEN
Solar/Wind Harmer
12.311
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.144
316011AB1-132 GEN
Solar/Wind Harmer
5.139
962571AG1-106 GEN
Solar/Wind Harmer
3.531
3145783HORNRTN
Solar/Wind Harmer
-0.024
957481AF2-042 GEN
Solar/Wind Harmer
76.03
316023GEN1_S
Solar/Wind Harmer
1.636
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
316381AD1-082 GEN
Solar/Wind Harmer
2.219
316494AC1-189 GEN
Solar/Wind Harmer
2.574
960081AF2-299 GEN
Solar/Wind Harmer
2.668
970659AG2-427 GEN
Solar/Wind Harmer
12.549
961671AG1-007 GEN
Solar/Wind Harmer
0.293
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.687
315722AD1-056 GEN
Solar/Wind Harmer
2.417
971795AH1-408 GEN
Solar/Wind Harmer
17.168
971647AH1-324 GEN
Solar/Wind Harmer
11.441
3146233WITAKRS
Solar/Wind Harmer
-0.09
315693AD1-088 GEN
Solar/Wind Harmer
11.384
3147043LAWRENC
Adder
1.812
962491AG1-098 GEN
Solar/Wind Harmer
15.033
316129AC1-054 GEN
Solar/Wind Harmer
1.963
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316359AB2-059 GEN
Solar/Wind Harmer
2.997
316049AB1-081 GEN
Solar/Wind Harmer
2.399
3142053HEARTS
Solar/Wind Harmer
0.261
971065AG2-659 GEN
Solar/Wind Harmer
11.096
316159AE1-175 C
Solar/Wind Harmer
0.587
315687AD1-152 GEN
Solar/Wind Harmer
2.597
316237AB2-079_GEN
Solar/Wind Harmer
0.596
971069AG2-661 GEN
Solar/Wind Harmer
3.042
970401AG2-262 GEN
Solar/Wind Harmer
1.249
316003AC1-222 GEN
Solar/Wind Harmer
1.719
970685AG2-442 GEN
Solar/Wind Harmer
15.11
3144293JTRSVLE
Adder
0.469
3151101ELIZAR3
50/50
32.443
3150921YORKTN3
50/50
7.395
3144216WINCHST
50/50
1.098
3151161SURRY 1
50/50
9.413
315773AC2-141 GEN
Solar/Wind Harmer
17.974
944581AF1-123 GEN
Solar/Wind Harmer
174.755
944601AF1-125 GEN
Solar/Wind Harmer
172.028
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.462
316320Y1-086
Solar/Wind Harmer
2.093
3144536CHRHLND
Solar/Wind Harmer
-0.005
316435W1029_GEN3
Solar/Wind Harmer
6.29
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
3.387
3145336SMITFLD
Solar/Wind Harmer
-0.012
971157AH1-035 GEN
Solar/Wind Harmer
3.788
315737AD1-076 GEN
Solar/Wind Harmer
5.721
3146206CASHIE
Solar/Wind Harmer
-0.029
3156081AA2-088 GEN
Solar/Wind Harmer
9.214
3156021HOLLOMANSOL
Solar/Wind Harmer
3.796
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.028
957521AF2-046 GEN
Solar/Wind Harmer
21.937
972263AH1-716 GEN
50/50
234.068
3151081ELIZAR1
50/50
32.033
3151091ELIZAR2
50/50
31.476
941591AE2-156 GEN
50/50
29.167
3152611GOSPORTB
50/50
4.42
3152621GOSPORTC
50/50
3.751
3152601GOSPORTA
50/50
3.46
3151151S HAMPT1
50/50
0.694
957871AF2-081 GEN
Solar/Wind Harmer
18.385
319010AE1-072 C
Solar/Wind Harmer
7.39
3146406KITTY HAWK
Solar/Wind Harmer
0.03
313526AB2-022
Solar/Wind Harmer
0.963
316305AF2-043 C
Solar/Wind Harmer
1.07
316321Z2-027
Solar/Wind Harmer
0.953
3146396TANGLEW
Solar/Wind Harmer
0.65
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
3146486SUNBURY
Solar/Wind Harmer
-0.035
3146486SUNBURY
Solar/Wind Harmer
-0.035
315835AF2-110_GEN
Solar/Wind Harmer
4.201
315611Z1-036_GEN2
Solar/Wind Harmer
8.3
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.54
971445AH1-216 GEN
Solar/Wind Harmer
19.051
3130546PLYMOUTH
Solar/Wind Harmer
-0.03
315732AD1-074 GEN1
Solar/Wind Harmer
6.088
315733AD1-074 GEN2
Solar/Wind Harmer
6.088
315735AD1-075 GEN1
Solar/Wind Harmer
3.045
316311AC2-079 GEN
Solar/Wind Harmer
15.157
315833AF1-017_GEN
Solar/Wind Harmer
5.694
316349AD2-085 GEN
Solar/Wind Harmer
2.666
941031AE2-094 GEN
Solar/Wind Harmer
56.074
944011AF1-069 GEN
Solar/Wind Harmer
17.57
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.822
970673AG2-436 GEN
Solar/Wind Harmer
61.422
970673AG2-436 GEN
Solar/Wind Harmer
31.1
971967AH1-528 GEN
Solar/Wind Harmer
53.614
965291AG1-394 GEN
Solar/Wind Harmer
2.497
316318V4-068
Solar/Wind Harmer
0.696
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145513AHOSKIE
Solar/Wind Harmer
0.24
961941AG1-037 GEN
Solar/Wind Harmer
0.207
3145513AHOSKIE
Solar/Wind Harmer
-0.027
972265AH1-717 GEN
Adder
19.027
3151201GRAVEL4
Adder
17.836
3151191GRAVEL3
Adder
17.61
3151211GRAVEL5
Adder
17.61
3145683EARLEYS
Solar/Wind Harmer
-0.055
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.027
970085AG2-068 GEN
Solar/Wind Harmer
16.972
970581AG2-369 GEN
Solar/Wind Harmer
14.596
3146043SEABORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.628
3146033SCOT NK
Solar/Wind Harmer
-0.101
316005AA1-067
Solar/Wind Harmer
0.502
3145746EVERETS
Solar/Wind Harmer
-0.098
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
970181AG2-120 GEN
Solar/Wind Harmer
3.255
315652AC1-086 GEN
Solar/Wind Harmer
27.632
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
315814AE2-033 C
Solar/Wind Harmer
22.412
316315AB2-025 C
Solar/Wind Harmer
0.649
316087AB2-174 GEN
Solar/Wind Harmer
3.426
957861AF2-080 GEN
Solar/Wind Harmer
10.465
946281AF1-292 GEN
Solar/Wind Harmer
0.531
316420AA1-050 GEN
Solar/Wind Harmer
2.684
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.258
970831AG2-522 GEN
Solar/Wind Harmer
11.304
957831AF2-077 GEN
Solar/Wind Harmer
0.674
3138283WHITEMARSH
Solar/Wind Harmer
0.035
316369SG1_INVT
Solar/Wind Harmer
3.725
316239AB2-077_GEN
Solar/Wind Harmer
0.596
316238AB2-078_GEN
Solar/Wind Harmer
0.596
3143316POE
Solar/Wind Harmer
-0.076
316118AC1-105 GEN
Solar/Wind Harmer
1.3
3147173SINAI
Solar/Wind Harmer
-0.019
3147243WELCO
Solar/Wind Harmer
-0.012
971443AH1-215 GEN
Solar/Wind Harmer
3.563
3144303KENBRDG
Solar/Wind Harmer
-0.014
970683AG2-441 GEN
Solar/Wind Harmer
1.145
970681AG2-440 GEN
Solar/Wind Harmer
0.916
961681AG1-008 GEN
Solar/Wind Harmer
21.937
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
316463AE2-346 GEN
Solar/Wind Harmer
0.446
316140AB2-099
Solar/Wind Harmer
0.186
962331AG1-082 GEN
Solar/Wind Harmer
3.448
3151221GRAVEL6
Adder
17.816
3151171GRAVELC
Adder
3.428
970917AG2-570 GEN
Solar/Wind Harmer
68.211
3146263WOODLND
Solar/Wind Harmer
-0.027
316317KELFORD C
Solar/Wind Harmer
1.247
3145823KELFORD
Solar/Wind Harmer
-0.026
970661AG2-428 GEN
Solar/Wind Harmer
4.871
3145933PARMELE
Solar/Wind Harmer
-0.026
966801AG1-551 GEN
Solar/Wind Harmer
3.217
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
961611AG1-000B GEN
Solar/Wind Harmer
5.253
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.859
316365GEN2_N
Solar/Wind Harmer
1.636
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
316083AB2-161 GEN
Solar/Wind Harmer
3.928
313506AB2-031 GEN
Solar/Wind Harmer
1.941
966621AG1-532 GEN
Solar/Wind Harmer
0.481
970659AG2-427 GEN
Solar/Wind Harmer
2.224
316327AA2-057 GEN
Solar/Wind Harmer
2.352
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
315724AD1-057 GEN
Solar/Wind Harmer
1.329
316478AD1-087 GEN
Solar/Wind Harmer
1.996
316486AD2-202 GEN
Solar/Wind Harmer
0.585
3146233WITAKRS
Solar/Wind Harmer
0.476
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
3147043LAWRENC
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.854
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
316382AG1-145 C
Solar/Wind Harmer
0.659
315813AE1-149 C
Solar/Wind Harmer
12.837
316131AB2-060 GEN
Solar/Wind Harmer
2.117
315778AD1-151 GEN
Solar/Wind Harmer
16.654
964241AG1-285 GEN
Solar/Wind Harmer
14.949
316248AF1-058 C
Solar/Wind Harmer
0.563
960061AF2-297 GEN
Solar/Wind Harmer
9.345
315785AD2-033 C
Solar/Wind Harmer
4.154
970257AG2-171 GEN
Solar/Wind Harmer
6.761
959311AF2-222 GEN
Solar/Wind Harmer
18.591
316283AC2-100 C
Solar/Wind Harmer
1.638
3144293JTRSVLE
Adder
0.469
3150991CHESPKB
50/50
3.637
3150991CHESPKB
50/50
3.55
970533AG2-339 GEN
50/50
23.66
970531AG2-338 GEN
50/50
9.464
316185AD1-033 GEN
Solar/Wind Harmer
3.934
3145506HICKORY
Solar/Wind Harmer
-0.148
3145506HICKORY
Solar/Wind Harmer
-0.089
3145506HICKORY
Solar/Wind Harmer
-0.022
3142956BIRDNECK
Solar/Wind Harmer
1.987
316316AC1-027 C
Solar/Wind Harmer
1.136
316339AD2-160 GEN
Solar/Wind Harmer
2.485
316036AC1-147 C
Solar/Wind Harmer
0.992
316018AA1-139 ULT2
Solar/Wind Harmer
3.15
316017AA1-139 ULT1
Solar/Wind Harmer
2.975
3137176SLIGO L2192
Solar/Wind Harmer
-0.145
3146456SLIGO L269
Solar/Wind Harmer
4.323
3130086AYDLETT
Solar/Wind Harmer
-0.145
3146386ELIZ CT
Solar/Wind Harmer
-0.036
316431W1029_GEN1
Solar/Wind Harmer
6.29
316433W1029_GEN2
Solar/Wind Harmer
6.29
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
0.973
3146376EDENTON
Solar/Wind Harmer
0.973
315742AE1-103 GEN
Solar/Wind Harmer
3.266
316236AE1-162_GEN
Solar/Wind Harmer
0.938
316065AD1-022 GEN
Solar/Wind Harmer
14.799
972185AH1-677 GEN
Adder
14.434
972187AH1-678 GEN
Adder
7.212
3145893MURPHYS
Solar/Wind Harmer
0.779
3145893MURPHYS
Solar/Wind Harmer
-0.05
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
970933AG2-581 GEN
Solar/Wind Harmer
25.613
3145933PARMELE
Solar/Wind Harmer
-0.051
3145933PARMELE
Solar/Wind Harmer
-0.026
316426AA2-053 GEN
Solar/Wind Harmer
2.539
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
970657AG2-426 GEN
Solar/Wind Harmer
7.759
970657AG2-426 GEN
Solar/Wind Harmer
1.623
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.771
3145593CAROLNA
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
2.912
3145783HORNRTN
Solar/Wind Harmer
2.33
3145783HORNRTN
Solar/Wind Harmer
0.728
3145783HORNRTN
Solar/Wind Harmer
0.291
970099AG2-077 GEN
Solar/Wind Harmer
30.412
3145796HORNRTN
Solar/Wind Harmer
-0.072
316181AB2-040 GEN
Solar/Wind Harmer
3.369
316274AC1-208 GEN
Solar/Wind Harmer
2.597
3144356SAPONY
Solar/Wind Harmer
0.839
3145493TOT1
Solar/Wind Harmer
0.358
3145453TOT5
Solar/Wind Harmer
0.215
3145603CNETO
Solar/Wind Harmer
0.143
961601AG1-000A GEN
Solar/Wind Harmer
8.743
316263AC1-034 GEN
Solar/Wind Harmer
10.421
939181AE1-148 GEN
Solar/Wind Harmer
11.775
316033AB2-134 GEN
Solar/Wind Harmer
6.724
315697AD1-025 GEN
Solar/Wind Harmer
4.217
313527AB2-043 GEN
Solar/Wind Harmer
3.207
962561AG1-105 GEN
Solar/Wind Harmer
10.812
964791AG1-342 GEN
Solar/Wind Harmer
4.086
3146843MT LREL
Solar/Wind Harmer
-0.019
3146843MT LREL
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.456
970323AG2-213 GEN
Solar/Wind Harmer
9.015
971775AH1-396 GEN
Solar/Wind Harmer
1.284
316034AC1-036 C
Solar/Wind Harmer
0.334
316222AC1-221 GEN
Solar/Wind Harmer
1.769
3144293JTRSVLE
Adder
0.469
3144293JTRSVLE
Adder
0.395
NYPJM->LTFIMP_NY
CLTF
1.906
LGEELTFEXP_LGEE->PJM
CLTF
1.024
LAGNLTFEXP_LAGN->PJM
CLTF
7.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.145
WECLTFEXP_WEC->PJM
CLTF
0.521
TVALTFEXP_TVA->PJM
CLTF
3.582
CPLELTFEXP_CPLE->PJM
CLTF
12.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.037
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.629
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.037
MECLTFEXP_MEC->PJM
CLTF
3.029
SIGELTFEXP_SIGE->PJM
CLTF
0.088

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.1 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3842.65
MW Contribution:14.6
Bus #Bus NameTypeMW Contribution
3152331SURRY 2
50/50
17.636
3150981CHESPKA
50/50
4.335
970017AG2-010 GEN
50/50
18.774
316294AC1-161 GEN
Solar/Wind Harmer
13.897
944591AF1-124 GEN
Solar/Wind Harmer
175.385
316388AE2-253 GEN
Solar/Wind Harmer
2.485
316375AC2-012 GEN
Solar/Wind Harmer
12.723
3146456SLIGO L269
Solar/Wind Harmer
-0.036
316246AF1-032 C
Solar/Wind Harmer
0.718
3146516WINFALL
Solar/Wind Harmer
-0.111
3146516WINFALL
Solar/Wind Harmer
-0.035
939411AE1-173 GEN
Solar/Wind Harmer
172.22
316072AD1-144
Solar/Wind Harmer
0.687
316093AE2-104_GEN
Solar/Wind Harmer
9.772
315800Z1-036_GEN1
Solar/Wind Harmer
8.3
940641AE2-051 GEN
Solar/Wind Harmer
31.321
3130156CHOWAN
Solar/Wind Harmer
-0.033
3145663CRESWEL
Solar/Wind Harmer
-0.087
971163AH1-040 GEN
Solar/Wind Harmer
29.428
3145336SMITFLD
Solar/Wind Harmer
-0.124
3138126ROCKLANDING
Solar/Wind Harmer
0.095
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.327
971317AH1-138 GEN
Solar/Wind Harmer
3.528
3145893MURPHYS
Solar/Wind Harmer
-0.111
3145893MURPHYS
Solar/Wind Harmer
0.828
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
3151171GRAVELC
Adder
2.607
3145683EARLEYS
Solar/Wind Harmer
-0.027
316174AB2-169 GEN
Solar/Wind Harmer
4.218
970919AG2-571 GEN
Solar/Wind Harmer
8.634
970087AG2-069 GEN
Solar/Wind Harmer
25.458
3146263WOODLND
Solar/Wind Harmer
-0.027
3145823KELFORD
Solar/Wind Harmer
-0.026
970661AG2-428 GEN
Solar/Wind Harmer
27.486
3146293MARTNCO
Solar/Wind Harmer
0.159
316190AA2-174 GEN
Solar/Wind Harmer
0.309
961611AG1-000B GEN
Solar/Wind Harmer
12.311
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316212AC1-099_GEN
Solar/Wind Harmer
2.144
316011AB1-132 GEN
Solar/Wind Harmer
5.139
962571AG1-106 GEN
Solar/Wind Harmer
3.531
3145783HORNRTN
Solar/Wind Harmer
-0.024
957481AF2-042 GEN
Solar/Wind Harmer
76.03
316023GEN1_S
Solar/Wind Harmer
1.636
3145796HORNRTN
Solar/Wind Harmer
-0.08
3145796HORNRTN
Solar/Wind Harmer
-0.024
316381AD1-082 GEN
Solar/Wind Harmer
2.219
316494AC1-189 GEN
Solar/Wind Harmer
2.574
960081AF2-299 GEN
Solar/Wind Harmer
2.668
970659AG2-427 GEN
Solar/Wind Harmer
12.549
961671AG1-007 GEN
Solar/Wind Harmer
0.293
3146083TARBORO
Solar/Wind Harmer
-0.023
3145493TOT1
Solar/Wind Harmer
0.687
315722AD1-056 GEN
Solar/Wind Harmer
2.417
971795AH1-408 GEN
Solar/Wind Harmer
17.168
971647AH1-324 GEN
Solar/Wind Harmer
11.441
3146233WITAKRS
Solar/Wind Harmer
-0.09
315693AD1-088 GEN
Solar/Wind Harmer
11.384
3147043LAWRENC
Adder
1.812
962491AG1-098 GEN
Solar/Wind Harmer
15.033
316129AC1-054 GEN
Solar/Wind Harmer
1.963
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.018
316359AB2-059 GEN
Solar/Wind Harmer
2.997
316049AB1-081 GEN
Solar/Wind Harmer
2.399
3142053HEARTS
Solar/Wind Harmer
0.261
971065AG2-659 GEN
Solar/Wind Harmer
11.096
316159AE1-175 C
Solar/Wind Harmer
0.587
315687AD1-152 GEN
Solar/Wind Harmer
2.597
316237AB2-079_GEN
Solar/Wind Harmer
0.596
971069AG2-661 GEN
Solar/Wind Harmer
3.042
970401AG2-262 GEN
Solar/Wind Harmer
1.249
316003AC1-222 GEN
Solar/Wind Harmer
1.719
970685AG2-442 GEN
Solar/Wind Harmer
15.11
3144293JTRSVLE
Adder
0.469
972263AH1-716 GEN
50/50
234.068
3151081ELIZAR1
50/50
32.033
3151091ELIZAR2
50/50
31.476
941591AE2-156 GEN
50/50
29.167
3152611GOSPORTB
50/50
4.42
3152621GOSPORTC
50/50
3.751
3152601GOSPORTA
50/50
3.46
3151151S HAMPT1
50/50
0.694
957871AF2-081 GEN
Solar/Wind Harmer
18.385
319010AE1-072 C
Solar/Wind Harmer
7.39
3146406KITTY HAWK
Solar/Wind Harmer
0.03
313526AB2-022
Solar/Wind Harmer
0.963
316305AF2-043 C
Solar/Wind Harmer
1.07
316321Z2-027
Solar/Wind Harmer
0.953
3146396TANGLEW
Solar/Wind Harmer
0.65
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
3146486SUNBURY
Solar/Wind Harmer
-0.035
3146486SUNBURY
Solar/Wind Harmer
-0.035
315835AF2-110_GEN
Solar/Wind Harmer
4.201
315611Z1-036_GEN2
Solar/Wind Harmer
8.3
3130156CHOWAN
Solar/Wind Harmer
-0.033
3130156CHOWAN
Solar/Wind Harmer
-0.033
315816AE2-034 GEN
Solar/Wind Harmer
2.54
971445AH1-216 GEN
Solar/Wind Harmer
19.051
3130546PLYMOUTH
Solar/Wind Harmer
-0.03
315732AD1-074 GEN1
Solar/Wind Harmer
6.088
315733AD1-074 GEN2
Solar/Wind Harmer
6.088
315735AD1-075 GEN1
Solar/Wind Harmer
3.045
316311AC2-079 GEN
Solar/Wind Harmer
15.157
315833AF1-017_GEN
Solar/Wind Harmer
5.694
316349AD2-085 GEN
Solar/Wind Harmer
2.666
941031AE2-094 GEN
Solar/Wind Harmer
56.074
944011AF1-069 GEN
Solar/Wind Harmer
17.57
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.822
970673AG2-436 GEN
Solar/Wind Harmer
61.422
970673AG2-436 GEN
Solar/Wind Harmer
31.1
971967AH1-528 GEN
Solar/Wind Harmer
53.614
965291AG1-394 GEN
Solar/Wind Harmer
2.497
316318V4-068
Solar/Wind Harmer
0.696
3145893MURPHYS
Solar/Wind Harmer
-0.075
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145513AHOSKIE
Solar/Wind Harmer
0.24
961941AG1-037 GEN
Solar/Wind Harmer
0.207
3145513AHOSKIE
Solar/Wind Harmer
-0.027
972265AH1-717 GEN
Adder
19.027
3151201GRAVEL4
Adder
17.836
3151191GRAVEL3
Adder
17.61
3151211GRAVEL5
Adder
17.61
3145683EARLEYS
Solar/Wind Harmer
-0.055
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.027
970085AG2-068 GEN
Solar/Wind Harmer
16.972
970581AG2-369 GEN
Solar/Wind Harmer
14.596
3146043SEABORD
Solar/Wind Harmer
-0.026
315607AA1-063A GEN
Solar/Wind Harmer
2.628
3146033SCOT NK
Solar/Wind Harmer
-0.101
316005AA1-067
Solar/Wind Harmer
0.502
3145746EVERETS
Solar/Wind Harmer
-0.098
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
970181AG2-120 GEN
Solar/Wind Harmer
3.255
315652AC1-086 GEN
Solar/Wind Harmer
27.632
3137643SOCKMAN
Solar/Wind Harmer
-0.097
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.01
315814AE2-033 C
Solar/Wind Harmer
22.412
316315AB2-025 C
Solar/Wind Harmer
0.649
316087AB2-174 GEN
Solar/Wind Harmer
3.426
957861AF2-080 GEN
Solar/Wind Harmer
10.465
946281AF1-292 GEN
Solar/Wind Harmer
0.531
316420AA1-050 GEN
Solar/Wind Harmer
2.684
3145573BETHELC
Solar/Wind Harmer
-0.023
3145573BETHELC
Solar/Wind Harmer
-0.023
316319Z2-044 C
Solar/Wind Harmer
1.258
970831AG2-522 GEN
Solar/Wind Harmer
11.304
957831AF2-077 GEN
Solar/Wind Harmer
0.674
3138283WHITEMARSH
Solar/Wind Harmer
0.035
316369SG1_INVT
Solar/Wind Harmer
3.725
316239AB2-077_GEN
Solar/Wind Harmer
0.596
316238AB2-078_GEN
Solar/Wind Harmer
0.596
3143316POE
Solar/Wind Harmer
-0.076
316118AC1-105 GEN
Solar/Wind Harmer
1.3
3151101ELIZAR3
50/50
32.443
3150921YORKTN3
50/50
7.395
3144216WINCHST
50/50
1.098
3151161SURRY 1
50/50
9.413
315773AC2-141 GEN
Solar/Wind Harmer
17.974
3147173SINAI
Solar/Wind Harmer
-0.019
3147243WELCO
Solar/Wind Harmer
-0.012
971443AH1-215 GEN
Solar/Wind Harmer
3.563
3144303KENBRDG
Solar/Wind Harmer
-0.014
970683AG2-441 GEN
Solar/Wind Harmer
1.145
970681AG2-440 GEN
Solar/Wind Harmer
0.916
3150991CHESPKB
50/50
3.637
3150991CHESPKB
50/50
3.55
970533AG2-339 GEN
50/50
23.66
970531AG2-338 GEN
50/50
9.464
316185AD1-033 GEN
Solar/Wind Harmer
3.934
3145506HICKORY
Solar/Wind Harmer
-0.148
3145506HICKORY
Solar/Wind Harmer
-0.089
3145506HICKORY
Solar/Wind Harmer
-0.022
3142956BIRDNECK
Solar/Wind Harmer
1.987
316316AC1-027 C
Solar/Wind Harmer
1.136
316339AD2-160 GEN
Solar/Wind Harmer
2.485
316036AC1-147 C
Solar/Wind Harmer
0.992
316018AA1-139 ULT2
Solar/Wind Harmer
3.15
316017AA1-139 ULT1
Solar/Wind Harmer
2.975
3137176SLIGO L2192
Solar/Wind Harmer
-0.145
3146456SLIGO L269
Solar/Wind Harmer
4.323
3130086AYDLETT
Solar/Wind Harmer
-0.145
3146386ELIZ CT
Solar/Wind Harmer
-0.036
316431W1029_GEN1
Solar/Wind Harmer
6.29
316433W1029_GEN2
Solar/Wind Harmer
6.29
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
0.973
3146376EDENTON
Solar/Wind Harmer
0.973
315742AE1-103 GEN
Solar/Wind Harmer
3.266
316236AE1-162_GEN
Solar/Wind Harmer
0.938
316065AD1-022 GEN
Solar/Wind Harmer
14.799
972185AH1-677 GEN
Adder
14.434
972187AH1-678 GEN
Adder
7.212
3145893MURPHYS
Solar/Wind Harmer
0.779
3145893MURPHYS
Solar/Wind Harmer
-0.05
3146173TUNIS
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
970933AG2-581 GEN
Solar/Wind Harmer
25.613
3145933PARMELE
Solar/Wind Harmer
-0.051
3145933PARMELE
Solar/Wind Harmer
-0.026
316426AA2-053 GEN
Solar/Wind Harmer
2.539
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
3142666NORTHAMPTON
Solar/Wind Harmer
-0.015
970657AG2-426 GEN
Solar/Wind Harmer
7.759
970657AG2-426 GEN
Solar/Wind Harmer
1.623
3145593CAROLNA
Solar/Wind Harmer
-0.025
3145593CAROLNA
Solar/Wind Harmer
-0.025
966811AG1-552 GEN
Solar/Wind Harmer
2.771
3145593CAROLNA
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
2.912
3145783HORNRTN
Solar/Wind Harmer
2.33
3145783HORNRTN
Solar/Wind Harmer
0.728
3145783HORNRTN
Solar/Wind Harmer
0.291
970099AG2-077 GEN
Solar/Wind Harmer
30.412
3145796HORNRTN
Solar/Wind Harmer
-0.072
316181AB2-040 GEN
Solar/Wind Harmer
3.369
316274AC1-208 GEN
Solar/Wind Harmer
2.597
3144356SAPONY
Solar/Wind Harmer
0.839
3145493TOT1
Solar/Wind Harmer
0.358
3145453TOT5
Solar/Wind Harmer
0.215
3145603CNETO
Solar/Wind Harmer
0.143
961601AG1-000A GEN
Solar/Wind Harmer
8.743
316263AC1-034 GEN
Solar/Wind Harmer
10.421
939181AE1-148 GEN
Solar/Wind Harmer
11.775
316033AB2-134 GEN
Solar/Wind Harmer
6.724
315697AD1-025 GEN
Solar/Wind Harmer
4.217
313527AB2-043 GEN
Solar/Wind Harmer
3.207
962561AG1-105 GEN
Solar/Wind Harmer
10.812
964791AG1-342 GEN
Solar/Wind Harmer
4.086
3146843MT LREL
Solar/Wind Harmer
-0.019
3146843MT LREL
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.456
970323AG2-213 GEN
Solar/Wind Harmer
9.015
971775AH1-396 GEN
Solar/Wind Harmer
1.284
316034AC1-036 C
Solar/Wind Harmer
0.334
316222AC1-221 GEN
Solar/Wind Harmer
1.769
3144293JTRSVLE
Adder
0.469
3144293JTRSVLE
Adder
0.395
944581AF1-123 GEN
Solar/Wind Harmer
174.755
944601AF1-125 GEN
Solar/Wind Harmer
172.028
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.462
316320Y1-086
Solar/Wind Harmer
2.093
3144536CHRHLND
Solar/Wind Harmer
-0.005
316435W1029_GEN3
Solar/Wind Harmer
6.29
3146516WINFALL
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
-0.033
3145273HOLLAND
Solar/Wind Harmer
-0.024
315614AA2-178 GEN
Solar/Wind Harmer
3.387
3145336SMITFLD
Solar/Wind Harmer
-0.012
971157AH1-035 GEN
Solar/Wind Harmer
3.788
315737AD1-076 GEN
Solar/Wind Harmer
5.721
3146206CASHIE
Solar/Wind Harmer
-0.029
3156081AA2-088 GEN
Solar/Wind Harmer
9.214
3156021HOLLOMANSOL
Solar/Wind Harmer
3.796
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.028
957521AF2-046 GEN
Solar/Wind Harmer
21.937
961681AG1-008 GEN
Solar/Wind Harmer
21.937
3145963POPLR C
Solar/Wind Harmer
-0.028
3146173TUNIS
Solar/Wind Harmer
-0.028
316463AE2-346 GEN
Solar/Wind Harmer
0.446
316140AB2-099
Solar/Wind Harmer
0.186
962331AG1-082 GEN
Solar/Wind Harmer
3.448
3151221GRAVEL6
Adder
17.816
3151171GRAVELC
Adder
3.428
970917AG2-570 GEN
Solar/Wind Harmer
68.211
3146263WOODLND
Solar/Wind Harmer
-0.027
316317KELFORD C
Solar/Wind Harmer
1.247
3145823KELFORD
Solar/Wind Harmer
-0.026
970661AG2-428 GEN
Solar/Wind Harmer
4.871
3145933PARMELE
Solar/Wind Harmer
-0.026
966801AG1-551 GEN
Solar/Wind Harmer
3.217
3142666NORTHAMPTON
Solar/Wind Harmer
-0.025
961611AG1-000B GEN
Solar/Wind Harmer
5.253
3145746EVERETS
Solar/Wind Harmer
-0.025
3145746EVERETS
Solar/Wind Harmer
-0.025
316210AC1-098 GEN
Solar/Wind Harmer
3.859
316365GEN2_N
Solar/Wind Harmer
1.636
3145796HORNRTN
Solar/Wind Harmer
-0.096
3145796HORNRTN
Solar/Wind Harmer
-0.024
316083AB2-161 GEN
Solar/Wind Harmer
3.928
313506AB2-031 GEN
Solar/Wind Harmer
1.941
966621AG1-532 GEN
Solar/Wind Harmer
0.481
970659AG2-427 GEN
Solar/Wind Harmer
2.224
316327AA2-057 GEN
Solar/Wind Harmer
2.352
3146073TAR RVR
Solar/Wind Harmer
-0.023
3146083TARBORO
Solar/Wind Harmer
-0.023
315724AD1-057 GEN
Solar/Wind Harmer
1.329
316478AD1-087 GEN
Solar/Wind Harmer
1.996
316486AD2-202 GEN
Solar/Wind Harmer
0.585
3146233WITAKRS
Solar/Wind Harmer
0.476
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.015
3147043LAWRENC
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
8.854
3145543BTLEBRO
Solar/Wind Harmer
-0.022
3145543BTLEBRO
Solar/Wind Harmer
-0.022
316382AG1-145 C
Solar/Wind Harmer
0.659
315813AE1-149 C
Solar/Wind Harmer
12.837
316131AB2-060 GEN
Solar/Wind Harmer
2.117
315778AD1-151 GEN
Solar/Wind Harmer
16.654
964241AG1-285 GEN
Solar/Wind Harmer
14.949
316248AF1-058 C
Solar/Wind Harmer
0.563
960061AF2-297 GEN
Solar/Wind Harmer
9.345
315785AD2-033 C
Solar/Wind Harmer
4.154
970257AG2-171 GEN
Solar/Wind Harmer
6.761
959311AF2-222 GEN
Solar/Wind Harmer
18.591
316283AC2-100 C
Solar/Wind Harmer
1.638
3144293JTRSVLE
Adder
0.469
NYPJM->LTFIMP_NY
CLTF
1.906
LAGNLTFEXP_LAGN->PJM
CLTF
7.202
LGEELTFEXP_LGEE->PJM
CLTF
1.024
WECLTFEXP_WEC->PJM
CLTF
0.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.145
TVALTFEXP_TVA->PJM
CLTF
3.582
CPLELTFEXP_CPLE->PJM
CLTF
12.083
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.037
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.629
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.037
MECLTFEXP_MEC->PJM
CLTF
3.029
SIGELTFEXP_SIGE->PJM
CLTF
0.088

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.01 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3840.05
MW Contribution:14.74
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
232.345
3151081ELIZAR1
50/50
31.711
3151091ELIZAR2
50/50
31.16
941591AE2-156 GEN
50/50
28.866
3152611GOSPORTB
50/50
4.373
3152621GOSPORTC
50/50
3.712
3152601GOSPORTA
50/50
3.424
315244AE2-183_ST
50/50
7.432
957871AF2-081 GEN
Solar/Wind Harmer
18.198
319010AE1-072 C
Solar/Wind Harmer
7.312
3146406KITTY HAWK
Solar/Wind Harmer
0.03
313526AB2-022
Solar/Wind Harmer
0.952
316305AF2-043 C
Solar/Wind Harmer
1.057
316321Z2-027
Solar/Wind Harmer
0.941
3146396TANGLEW
Solar/Wind Harmer
0.642
3145176PASQUOTANK
Solar/Wind Harmer
-0.022
3146486SUNBURY
Solar/Wind Harmer
-0.034
3146486SUNBURY
Solar/Wind Harmer
-0.034
315611Z1-036_GEN2
Solar/Wind Harmer
8.173
315835AF2-110_GEN
Solar/Wind Harmer
4.12
3130156CHOWAN
Solar/Wind Harmer
-0.032
3130156CHOWAN
Solar/Wind Harmer
-0.032
315816AE2-034 GEN
Solar/Wind Harmer
2.491
941031AE2-094 GEN
Solar/Wind Harmer
56.808
944011AF1-069 GEN
Solar/Wind Harmer
17.8
971445AH1-216 GEN
Solar/Wind Harmer
18.596
3130546PLYMOUTH
Solar/Wind Harmer
-0.03
970673AG2-436 GEN
Solar/Wind Harmer
62.174
970673AG2-436 GEN
Solar/Wind Harmer
31.48
315732AD1-074 GEN1
Solar/Wind Harmer
5.955
315733AD1-074 GEN2
Solar/Wind Harmer
5.955
315735AD1-075 GEN1
Solar/Wind Harmer
2.978
316311AC2-079 GEN
Solar/Wind Harmer
14.599
315833AF1-017_GEN
Solar/Wind Harmer
5.482
316349AD2-085 GEN
Solar/Wind Harmer
2.567
971967AH1-528 GEN
Solar/Wind Harmer
54.198
3146206CASHIE
Solar/Wind Harmer
-0.029
970601AG2-382 GEN
Solar/Wind Harmer
12.509
970085AG2-068 GEN
Solar/Wind Harmer
17.137
970581AG2-369 GEN
Solar/Wind Harmer
14.738
965291AG1-394 GEN
Solar/Wind Harmer
2.417
316318V4-068
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.073
3145893MURPHYS
Solar/Wind Harmer
-0.027
3145513AHOSKIE
Solar/Wind Harmer
0.233
961941AG1-037 GEN
Solar/Wind Harmer
0.201
3145513AHOSKIE
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.053
3145683EARLEYS
Solar/Wind Harmer
-0.027
3145683EARLEYS
Solar/Wind Harmer
-0.027
972265AH1-717 GEN
Adder
18.386
3151201GRAVEL4
Adder
17.236
3151191GRAVEL3
Adder
17.018
3151211GRAVEL5
Adder
17.018
3146043SEABORD
Solar/Wind Harmer
-0.025
315607AA1-063A GEN
Solar/Wind Harmer
2.525
3146033SCOT NK
Solar/Wind Harmer
-0.098
316005AA1-067
Solar/Wind Harmer
0.488
3145746EVERETS
Solar/Wind Harmer
-0.095
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
970181AG2-120 GEN
Solar/Wind Harmer
3.168
957861AF2-080 GEN
Solar/Wind Harmer
10.163
3137643SOCKMAN
Solar/Wind Harmer
-0.092
315652AC1-086 GEN
Solar/Wind Harmer
26.061
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
316420AA1-050 GEN
Solar/Wind Harmer
2.603
316087AB2-174 GEN
Solar/Wind Harmer
3.218
3145573BETHELC
Solar/Wind Harmer
-0.022
3145573BETHELC
Solar/Wind Harmer
-0.022
946281AF1-292 GEN
Solar/Wind Harmer
0.494
316319Z2-044 C
Solar/Wind Harmer
1.215
970831AG2-522 GEN
Solar/Wind Harmer
10.945
957831AF2-077 GEN
Solar/Wind Harmer
0.651
3138283WHITEMARSH
Solar/Wind Harmer
0.034
315814AE2-033 C
Solar/Wind Harmer
19.44
316315AB2-025 C
Solar/Wind Harmer
0.561
316369SG1_INVT
Solar/Wind Harmer
3.485
316239AB2-077_GEN
Solar/Wind Harmer
0.581
316238AB2-078_GEN
Solar/Wind Harmer
0.581
316118AC1-105 GEN
Solar/Wind Harmer
1.283
3147173SINAI
Solar/Wind Harmer
-0.018
3147243WELCO
Solar/Wind Harmer
-0.011
971443AH1-215 GEN
Solar/Wind Harmer
3.452
3144303KENBRDG
Solar/Wind Harmer
-0.014
3151101ELIZAR3
50/50
32.117
3150921YORKTN3
50/50
7.245
3144216WINCHST
50/50
1.074
3151161SURRY 1
50/50
9.096
315773AC2-141 GEN
Solar/Wind Harmer
17.911
944581AF1-123 GEN
Solar/Wind Harmer
173.437
944601AF1-125 GEN
Solar/Wind Harmer
170.731
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.036
971153AH1-033 GEN
Solar/Wind Harmer
4.415
316320Y1-086
Solar/Wind Harmer
2.068
3144536CHRHLND
Solar/Wind Harmer
-0.005
316435W1029_GEN3
Solar/Wind Harmer
6.205
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
-0.032
3145273HOLLAND
Solar/Wind Harmer
-0.023
315614AA2-178 GEN
Solar/Wind Harmer
3.322
3145336SMITFLD
Solar/Wind Harmer
-0.012
971157AH1-035 GEN
Solar/Wind Harmer
3.707
315737AD1-076 GEN
Solar/Wind Harmer
5.597
3146206CASHIE
Solar/Wind Harmer
-0.029
970917AG2-570 GEN
Solar/Wind Harmer
68.885
3156081AA2-088 GEN
Solar/Wind Harmer
8.927
3156021HOLLOMANSOL
Solar/Wind Harmer
3.688
3145963POPLR C
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
0.189
3145893MURPHYS
Solar/Wind Harmer
-0.027
957521AF2-046 GEN
Solar/Wind Harmer
21.249
961681AG1-008 GEN
Solar/Wind Harmer
21.249
3146173TUNIS
Solar/Wind Harmer
-0.027
316463AE2-346 GEN
Solar/Wind Harmer
0.433
316140AB2-099
Solar/Wind Harmer
0.18
962331AG1-082 GEN
Solar/Wind Harmer
3.341
3151221GRAVEL6
Adder
17.216
3151171GRAVELC
Adder
3.312
3146263WOODLND
Solar/Wind Harmer
-0.026
316317KELFORD C
Solar/Wind Harmer
1.207
3145823KELFORD
Solar/Wind Harmer
-0.026
3145933PARMELE
Solar/Wind Harmer
-0.025
966801AG1-551 GEN
Solar/Wind Harmer
3.134
970661AG2-428 GEN
Solar/Wind Harmer
4.561
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.024
316210AC1-098 GEN
Solar/Wind Harmer
3.722
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
316478AD1-087 GEN
Solar/Wind Harmer
1.996
316486AD2-202 GEN
Solar/Wind Harmer
0.584
3145796HORNRTN
Solar/Wind Harmer
-0.091
3145796HORNRTN
Solar/Wind Harmer
-0.023
313506AB2-031 GEN
Solar/Wind Harmer
1.83
316327AA2-057 GEN
Solar/Wind Harmer
2.269
3146073TAR RVR
Solar/Wind Harmer
-0.022
3146083TARBORO
Solar/Wind Harmer
-0.022
316083AB2-161 GEN
Solar/Wind Harmer
3.626
316365GEN2_N
Solar/Wind Harmer
1.499
315724AD1-057 GEN
Solar/Wind Harmer
1.272
966621AG1-532 GEN
Solar/Wind Harmer
0.448
3146233WITAKRS
Solar/Wind Harmer
0.46
3146233WITAKRS
Solar/Wind Harmer
-0.015
3138543CONSLDL
Solar/Wind Harmer
-0.014
970659AG2-427 GEN
Solar/Wind Harmer
2.042
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.021
961601AG1-000A GEN
Solar/Wind Harmer
8.556
3147043LAWRENC
Solar/Wind Harmer
-0.013
316382AG1-145 C
Solar/Wind Harmer
0.635
316131AB2-060 GEN
Solar/Wind Harmer
2.06
964241AG1-285 GEN
Solar/Wind Harmer
14.528
316248AF1-058 C
Solar/Wind Harmer
0.557
960061AF2-297 GEN
Solar/Wind Harmer
9.25
315813AE1-149 C
Solar/Wind Harmer
11.379
315778AD1-151 GEN
Solar/Wind Harmer
15.404
315785AD2-033 C
Solar/Wind Harmer
4.029
970257AG2-171 GEN
Solar/Wind Harmer
6.551
316283AC2-100 C
Solar/Wind Harmer
1.625
959311AF2-222 GEN
Solar/Wind Harmer
18
970909AG2-566 GEN
Solar/Wind Harmer
1.591
3144293JTRSVLE
Adder
0.452
3150991CHESPKB
50/50
3.599
3150991CHESPKB
50/50
3.513
970533AG2-339 GEN
50/50
23.97
970531AG2-338 GEN
50/50
9.588
315242AE2-183_GT2
50/50
4.299
315241AE2-183_GT1
50/50
4.272
972185AH1-677 GEN
50/50
15.497
316185AD1-033 GEN
Solar/Wind Harmer
3.897
3145506HICKORY
Solar/Wind Harmer
-0.146
3145506HICKORY
Solar/Wind Harmer
-0.088
3145506HICKORY
Solar/Wind Harmer
-0.022
3142956BIRDNECK
Solar/Wind Harmer
1.968
316316AC1-027 C
Solar/Wind Harmer
1.124
316339AD2-160 GEN
Solar/Wind Harmer
2.46
316018AA1-139 ULT2
Solar/Wind Harmer
3.118
316017AA1-139 ULT1
Solar/Wind Harmer
2.945
316036AC1-147 C
Solar/Wind Harmer
0.982
3137176SLIGO L2192
Solar/Wind Harmer
-0.143
3146456SLIGO L269
Solar/Wind Harmer
4.278
3130086AYDLETT
Solar/Wind Harmer
-0.144
3146386ELIZ CT
Solar/Wind Harmer
-0.035
316431W1029_GEN1
Solar/Wind Harmer
6.205
316433W1029_GEN2
Solar/Wind Harmer
6.205
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146516WINFALL
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146626S HERTFORD
Solar/Wind Harmer
-0.034
3146376EDENTON
Solar/Wind Harmer
0.957
3146376EDENTON
Solar/Wind Harmer
0.957
315742AE1-103 GEN
Solar/Wind Harmer
3.187
316236AE1-162_GEN
Solar/Wind Harmer
0.916
316065AD1-022 GEN
Solar/Wind Harmer
14.452
972187AH1-678 GEN
Adder
7.293
970933AG2-581 GEN
Solar/Wind Harmer
25.835
3145893MURPHYS
Solar/Wind Harmer
0.754
3145893MURPHYS
Solar/Wind Harmer
-0.049
3146173TUNIS
Solar/Wind Harmer
-0.027
3146173TUNIS
Solar/Wind Harmer
-0.027
3145933PARMELE
Solar/Wind Harmer
-0.05
3145933PARMELE
Solar/Wind Harmer
-0.025
970099AG2-077 GEN
Solar/Wind Harmer
30.484
316426AA2-053 GEN
Solar/Wind Harmer
2.434
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.648
3145593CAROLNA
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
2.786
3145783HORNRTN
Solar/Wind Harmer
2.229
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
316274AC1-208 GEN
Solar/Wind Harmer
2.5
970657AG2-426 GEN
Solar/Wind Harmer
7.203
970657AG2-426 GEN
Solar/Wind Harmer
1.506
3145796HORNRTN
Solar/Wind Harmer
-0.068
316181AB2-040 GEN
Solar/Wind Harmer
3.175
3145493TOT1
Solar/Wind Harmer
0.347
3145453TOT5
Solar/Wind Harmer
0.208
3145603CNETO
Solar/Wind Harmer
0.139
316263AC1-034 GEN
Solar/Wind Harmer
10.077
961601AG1-000A GEN
Solar/Wind Harmer
8.449
3144356SAPONY
Solar/Wind Harmer
0.725
939181AE1-148 GEN
Solar/Wind Harmer
11.511
316033AB2-134 GEN
Solar/Wind Harmer
6.291
315697AD1-025 GEN
Solar/Wind Harmer
3.946
313527AB2-043 GEN
Solar/Wind Harmer
3.122
962561AG1-105 GEN
Solar/Wind Harmer
10.61
964791AG1-342 GEN
Solar/Wind Harmer
4.015
3146843MT LREL
Solar/Wind Harmer
-0.019
3146843MT LREL
Solar/Wind Harmer
-0.019
971741AH1-377 GEN
Solar/Wind Harmer
21.074
970323AG2-213 GEN
Solar/Wind Harmer
8.734
971775AH1-396 GEN
Solar/Wind Harmer
1.244
316034AC1-036 C
Solar/Wind Harmer
0.324
316222AC1-221 GEN
Solar/Wind Harmer
1.754
970301AG2-198 GEN
Solar/Wind Harmer
8.382
3144293JTRSVLE
Adder
0.452
3144293JTRSVLE
Adder
0.381
3152331SURRY 2
50/50
17.53
3150981CHESPKA
50/50
4.29
970017AG2-010 GEN
50/50
18.389
315243AE2-183_GT3
50/50
4.299
316294AC1-161 GEN
Solar/Wind Harmer
13.849
944591AF1-124 GEN
Solar/Wind Harmer
174.062
316388AE2-253 GEN
Solar/Wind Harmer
2.46
316375AC2-012 GEN
Solar/Wind Harmer
12.59
3146456SLIGO L269
Solar/Wind Harmer
-0.036
316246AF1-032 C
Solar/Wind Harmer
0.709
939411AE1-173 GEN
Solar/Wind Harmer
173.085
3146516WINFALL
Solar/Wind Harmer
-0.11
3146516WINFALL
Solar/Wind Harmer
-0.034
940641AE2-051 GEN
Solar/Wind Harmer
31.646
316072AD1-144
Solar/Wind Harmer
0.676
315800Z1-036_GEN1
Solar/Wind Harmer
8.173
316093AE2-104_GEN
Solar/Wind Harmer
9.583
3130156CHOWAN
Solar/Wind Harmer
-0.032
3145663CRESWEL
Solar/Wind Harmer
-0.086
971163AH1-040 GEN
Solar/Wind Harmer
28.862
3145336SMITFLD
Solar/Wind Harmer
-0.121
3138126ROCKLANDING
Solar/Wind Harmer
0.093
3146206CASHIE
Solar/Wind Harmer
-0.029
971547AH1-271 GEN
Solar/Wind Harmer
7.148
971317AH1-138 GEN
Solar/Wind Harmer
3.445
970919AG2-571 GEN
Solar/Wind Harmer
8.72
970087AG2-069 GEN
Solar/Wind Harmer
25.705
3145963POPLR C
Solar/Wind Harmer
-0.027
3145893MURPHYS
Solar/Wind Harmer
-0.108
3145893MURPHYS
Solar/Wind Harmer
0.802
3146173TUNIS
Solar/Wind Harmer
-0.027
316174AB2-169 GEN
Solar/Wind Harmer
4.116
3145683EARLEYS
Solar/Wind Harmer
-0.027
3151171GRAVELC
Adder
2.519
3146263WOODLND
Solar/Wind Harmer
-0.026
3145823KELFORD
Solar/Wind Harmer
-0.026
3146293MARTNCO
Solar/Wind Harmer
0.155
957481AF2-042 GEN
Solar/Wind Harmer
76.21
970661AG2-428 GEN
Solar/Wind Harmer
25.737
3145746EVERETS
Solar/Wind Harmer
-0.024
3145746EVERETS
Solar/Wind Harmer
-0.024
316190AA2-174 GEN
Solar/Wind Harmer
0.296
961611AG1-000B GEN
Solar/Wind Harmer
11.774
316212AC1-099_GEN
Solar/Wind Harmer
2.068
3145783HORNRTN
Solar/Wind Harmer
-0.023
316494AC1-189 GEN
Solar/Wind Harmer
2.499
316011AB1-132 GEN
Solar/Wind Harmer
4.847
962571AG1-106 GEN
Solar/Wind Harmer
3.33
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.023
315693AD1-088 GEN
Solar/Wind Harmer
11.356
961671AG1-007 GEN
Solar/Wind Harmer
0.284
3146083TARBORO
Solar/Wind Harmer
-0.022
3145493TOT1
Solar/Wind Harmer
0.666
962491AG1-098 GEN
Solar/Wind Harmer
14.983
316381AD1-082 GEN
Solar/Wind Harmer
2.049
316023GEN1_S
Solar/Wind Harmer
1.499
315722AD1-056 GEN
Solar/Wind Harmer
2.313
960081AF2-299 GEN
Solar/Wind Harmer
2.484
3146233WITAKRS
Solar/Wind Harmer
-0.087
316129AC1-054 GEN
Solar/Wind Harmer
1.904
970659AG2-427 GEN
Solar/Wind Harmer
11.521
971647AH1-324 GEN
Solar/Wind Harmer
10.834
971065AG2-659 GEN
Solar/Wind Harmer
10.775
3145543BTLEBRO
Solar/Wind Harmer
-0.021
3145543BTLEBRO
Solar/Wind Harmer
-0.017
316359AB2-059 GEN
Solar/Wind Harmer
2.898
316049AB1-081 GEN
Solar/Wind Harmer
2.319
3142053HEARTS
Solar/Wind Harmer
0.253
315687AD1-152 GEN
Solar/Wind Harmer
2.591
971795AH1-408 GEN
Solar/Wind Harmer
16.11
3147043LAWRENC
Adder
1.707
316159AE1-175 C
Solar/Wind Harmer
0.566
316237AB2-079_GEN
Solar/Wind Harmer
0.581
970401AG2-262 GEN
Solar/Wind Harmer
1.227
971069AG2-661 GEN
Solar/Wind Harmer
2.814
316003AC1-222 GEN
Solar/Wind Harmer
1.7
3144293JTRSVLE
Adder
0.452
970685AG2-442 GEN
Solar/Wind Harmer
6.6
NYPJM->LTFIMP_NY
CLTF
1.853
LGEELTFEXP_LGEE->PJM
CLTF
1.006
LAGNLTFEXP_LAGN->PJM
CLTF
7.109
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.88
WECLTFEXP_WEC->PJM
CLTF
0.512
TVALTFEXP_TVA->PJM
CLTF
3.534
CPLELTFEXP_CPLE->PJM
CLTF
11.952
CBM West 2LTFEXP_CBM-W2->PJM
CBM
35.536
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.339
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.871
MECLTFEXP_MEC->PJM
CLTF
2.982
SIGELTFEXP_SIGE->PJM
CLTF
0.087

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.47 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:3088.52
MW Contribution:10.79
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
230.289
3151081ELIZAR1
50/50
31.355
3151091ELIZAR2
50/50
30.811
941591AE2-156 GEN
50/50
28.547
3152611GOSPORTB
50/50
4.325
3152621GOSPORTC
50/50
3.671
3152601GOSPORTA
50/50
3.386
3151151S HAMPT1
50/50
0.676
957871AF2-081 GEN
Solar/Wind Harmer
15.948
319010AE1-072 C
Solar/Wind Harmer
1.603
3146406KITTY HAWK
Solar/Wind Harmer
0.04
313526AB2-022
Solar/Wind Harmer
0.168
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.057
3146396TANGLEW
Solar/Wind Harmer
0.848
3145176PASQUOTANK
Solar/Wind Harmer
0.191
3146486SUNBURY
Solar/Wind Harmer
0.305
3146486SUNBURY
Solar/Wind Harmer
0.305
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315835AF2-110_GEN
Solar/Wind Harmer
2.004
3130156CHOWAN
Solar/Wind Harmer
0.285
3130156CHOWAN
Solar/Wind Harmer
0.285
315816AE2-034 GEN
Solar/Wind Harmer
1.171
971445AH1-216 GEN
Solar/Wind Harmer
18.76
3130546PLYMOUTH
Solar/Wind Harmer
0.263
315732AD1-074 GEN1
Solar/Wind Harmer
1.502
315733AD1-074 GEN2
Solar/Wind Harmer
1.502
315735AD1-075 GEN1
Solar/Wind Harmer
0.752
316311AC2-079 GEN
Solar/Wind Harmer
7.464
941031AE2-094 GEN
Solar/Wind Harmer
47.768
3152331SURRY 2
50/50
17.368
3150981CHESPKA
50/50
4.243
970017AG2-010 GEN
50/50
18.294
316294AC1-161 GEN
Solar/Wind Harmer
6.51
944591AF1-124 GEN
Solar/Wind Harmer
75.711
316388AE2-253 GEN
Solar/Wind Harmer
1.006
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.319
316246AF1-032 C
Solar/Wind Harmer
0.139
3146516WINFALL
Solar/Wind Harmer
0.976
3146516WINFALL
Solar/Wind Harmer
0.301
939411AE1-173 GEN
Solar/Wind Harmer
127.856
316072AD1-144
Solar/Wind Harmer
0.107
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
316093AE2-104_GEN
Solar/Wind Harmer
4.912
940641AE2-051 GEN
Solar/Wind Harmer
23.236
3130156CHOWAN
Solar/Wind Harmer
0.285
3145663CRESWEL
Solar/Wind Harmer
0.763
3151101ELIZAR3
50/50
31.757
3150921YORKTN3
50/50
7.207
3144216WINCHST
50/50
1.069
3151161SURRY 1
50/50
9.11
315773AC2-141 GEN
Solar/Wind Harmer
13.721
944581AF1-123 GEN
Solar/Wind Harmer
75.443
944601AF1-125 GEN
Solar/Wind Harmer
74.281
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.319
971153AH1-033 GEN
Solar/Wind Harmer
3.686
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.046
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146376EDENTON
Solar/Wind Harmer
0.285
3145273HOLLAND
Solar/Wind Harmer
0.208
315614AA2-178 GEN
Solar/Wind Harmer
1.561
3145336SMITFLD
Solar/Wind Harmer
0.108
971157AH1-035 GEN
Solar/Wind Harmer
3.159
315737AD1-076 GEN
Solar/Wind Harmer
3.364
3146206CASHIE
Solar/Wind Harmer
0.254
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.109
3145893MURPHYS
Solar/Wind Harmer
0.405
3145893MURPHYS
Solar/Wind Harmer
0.242
957521AF2-046 GEN
Solar/Wind Harmer
17.957
961681AG1-008 GEN
Solar/Wind Harmer
17.957
3145963POPLR C
Solar/Wind Harmer
0.241
3146173TUNIS
Solar/Wind Harmer
0.24
316463AE2-346 GEN
Solar/Wind Harmer
0.205
316140AB2-099
Solar/Wind Harmer
0.085
962331AG1-082 GEN
Solar/Wind Harmer
2.55
3151221GRAVEL6
Adder
17.243
3151171GRAVELC
Adder
3.318
970917AG2-570 GEN
Solar/Wind Harmer
21.013
3146263WOODLND
Solar/Wind Harmer
0.231
316317KELFORD C
Solar/Wind Harmer
0.022
3145823KELFORD
Solar/Wind Harmer
0.229
3145933PARMELE
Solar/Wind Harmer
0.223
966801AG1-551 GEN
Solar/Wind Harmer
2.598
970661AG2-428 GEN
Solar/Wind Harmer
4.701
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
961611AG1-000B GEN
Solar/Wind Harmer
5.702
316210AC1-098 GEN
Solar/Wind Harmer
1.973
3145796HORNRTN
Solar/Wind Harmer
0.836
3145796HORNRTN
Solar/Wind Harmer
0.209
316365GEN2_N
Solar/Wind Harmer
0.469
313506AB2-031 GEN
Solar/Wind Harmer
0.643
316083AB2-161 GEN
Solar/Wind Harmer
0.003
970659AG2-427 GEN
Solar/Wind Harmer
2.136
316327AA2-057 GEN
Solar/Wind Harmer
0.304
3146073TAR RVR
Solar/Wind Harmer
0.2
3146083TARBORO
Solar/Wind Harmer
0.2
315724AD1-057 GEN
Solar/Wind Harmer
0.749
316478AD1-087 GEN
Solar/Wind Harmer
0.693
316486AD2-202 GEN
Solar/Wind Harmer
0.204
3146233WITAKRS
Solar/Wind Harmer
0.987
3146233WITAKRS
Solar/Wind Harmer
0.134
3138543CONSLDL
Solar/Wind Harmer
0.129
3147043LAWRENC
Solar/Wind Harmer
0.116
961601AG1-000A GEN
Solar/Wind Harmer
13.669
3145543BTLEBRO
Solar/Wind Harmer
0.192
3145543BTLEBRO
Solar/Wind Harmer
0.192
971623AH1-311 GEN
Solar/Wind Harmer
0.384
316382AG1-145 C
Solar/Wind Harmer
0.001
315813AE1-149 C
Solar/Wind Harmer
9.286
316131AB2-060 GEN
Solar/Wind Harmer
0.528
964241AG1-285 GEN
Solar/Wind Harmer
10.893
315778AD1-151 GEN
Solar/Wind Harmer
12.979
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.855
315785AD2-033 C
Solar/Wind Harmer
1.268
970257AG2-171 GEN
Solar/Wind Harmer
4.903
959311AF2-222 GEN
Solar/Wind Harmer
13.44
316283AC2-100 C
Solar/Wind Harmer
0.293
970909AG2-566 GEN
Solar/Wind Harmer
1.544
971683AH1-343 GEN
Solar/Wind Harmer
5.265
963181AG1-167 GEN
Solar/Wind Harmer
0.558
3144293JTRSVLE
Adder
0.444
970129AG2-093 GEN
Solar/Wind Harmer
8.316
3147133PAMPLIN
Solar/Wind Harmer
0.423
971193AH1-056 GEN
Solar/Wind Harmer
8.217
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
315839AE2-212 C
Solar/Wind Harmer
0.001
3150991CHESPKB
50/50
3.559
3150991CHESPKB
50/50
3.474
970533AG2-339 GEN
50/50
23.054
970531AG2-338 GEN
50/50
9.222
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3145506HICKORY
Solar/Wind Harmer
1.295
3145506HICKORY
Solar/Wind Harmer
0.777
3145506HICKORY
Solar/Wind Harmer
0.194
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.309
316339AD2-160 GEN
Solar/Wind Harmer
0.521
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.179
316036AC1-147 C
Solar/Wind Harmer
0.06
3137176SLIGO L2192
Solar/Wind Harmer
1.269
3146456SLIGO L269
Solar/Wind Harmer
5.642
3130086AYDLETT
Solar/Wind Harmer
1.271
3146386ELIZ CT
Solar/Wind Harmer
0.311
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146516WINFALL
Solar/Wind Harmer
0.301
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146626S HERTFORD
Solar/Wind Harmer
0.297
3146376EDENTON
Solar/Wind Harmer
1.268
3146376EDENTON
Solar/Wind Harmer
1.268
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316236AE1-162_GEN
Solar/Wind Harmer
0.002
316065AD1-022 GEN
Solar/Wind Harmer
11.831
972185AH1-677 GEN
Adder
14.057
972187AH1-678 GEN
Adder
7.022
3145893MURPHYS
Solar/Wind Harmer
1.618
3145893MURPHYS
Solar/Wind Harmer
0.435
3146173TUNIS
Solar/Wind Harmer
0.24
3146173TUNIS
Solar/Wind Harmer
0.24
970933AG2-581 GEN
Solar/Wind Harmer
18.911
3145933PARMELE
Solar/Wind Harmer
0.446
3145933PARMELE
Solar/Wind Harmer
0.223
316426AA2-053 GEN
Solar/Wind Harmer
0.733
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.216
3142666NORTHAMPTON
Solar/Wind Harmer
0.13
970657AG2-426 GEN
Solar/Wind Harmer
7.454
970657AG2-426 GEN
Solar/Wind Harmer
1.563
3145593CAROLNA
Solar/Wind Harmer
0.213
3145593CAROLNA
Solar/Wind Harmer
0.213
966811AG1-552 GEN
Solar/Wind Harmer
2.307
3145593CAROLNA
Solar/Wind Harmer
0.265
3145783HORNRTN
Solar/Wind Harmer
3.768
3145783HORNRTN
Solar/Wind Harmer
3.015
3145783HORNRTN
Solar/Wind Harmer
0.942
3145783HORNRTN
Solar/Wind Harmer
0.377
970099AG2-077 GEN
Solar/Wind Harmer
22.381
3145796HORNRTN
Solar/Wind Harmer
0.627
316181AB2-040 GEN
Solar/Wind Harmer
0.302
316274AC1-208 GEN
Solar/Wind Harmer
1.08
3144356SAPONY
Solar/Wind Harmer
1.726
3145493TOT1
Solar/Wind Harmer
0.464
3145453TOT5
Solar/Wind Harmer
0.279
3145603CNETO
Solar/Wind Harmer
0.186
961601AG1-000A GEN
Solar/Wind Harmer
3.417
316263AC1-034 GEN
Solar/Wind Harmer
7.3
939181AE1-148 GEN
Solar/Wind Harmer
8.634
316033AB2-134 GEN
Solar/Wind Harmer
0.01
315697AD1-025 GEN
Solar/Wind Harmer
0.199
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.914
964791AG1-342 GEN
Solar/Wind Harmer
3.152
3146843MT LREL
Solar/Wind Harmer
0.164
3146843MT LREL
Solar/Wind Harmer
0.164
971741AH1-377 GEN
Solar/Wind Harmer
15.521
970323AG2-213 GEN
Solar/Wind Harmer
6.537
971775AH1-396 GEN
Solar/Wind Harmer
0.245
316034AC1-036 C
Solar/Wind Harmer
0.011
316222AC1-221 GEN
Solar/Wind Harmer
0.625
970301AG2-198 GEN
Solar/Wind Harmer
6.178
958211AF2-115 GEN
Solar/Wind Harmer
1.675
963191AG1-168 GEN
Solar/Wind Harmer
0.558
3144293JTRSVLE
Adder
0.444
3144293JTRSVLE
Adder
0.374
3147133PAMPLIN
Solar/Wind Harmer
0.135
3147133PAMPLIN
Solar/Wind Harmer
0.108
971163AH1-040 GEN
Solar/Wind Harmer
21.824
3145336SMITFLD
Solar/Wind Harmer
1.077
3138126ROCKLANDING
Solar/Wind Harmer
0.123
3146206CASHIE
Solar/Wind Harmer
0.254
971547AH1-271 GEN
Solar/Wind Harmer
5.427
971317AH1-138 GEN
Solar/Wind Harmer
1.823
3145893MURPHYS
Solar/Wind Harmer
0.967
3145893MURPHYS
Solar/Wind Harmer
1.075
3145963POPLR C
Solar/Wind Harmer
0.241
3146173TUNIS
Solar/Wind Harmer
0.24
3145683EARLEYS
Solar/Wind Harmer
0.238
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3151171GRAVELC
Adder
2.523
970919AG2-571 GEN
Solar/Wind Harmer
8.405
970087AG2-069 GEN
Solar/Wind Harmer
18.821
3146263WOODLND
Solar/Wind Harmer
0.231
3145823KELFORD
Solar/Wind Harmer
0.229
3146293MARTNCO
Solar/Wind Harmer
0.207
970661AG2-428 GEN
Solar/Wind Harmer
22.103
316190AA2-174 GEN
Solar/Wind Harmer
0
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
961611AG1-000B GEN
Solar/Wind Harmer
11.214
316212AC1-099_GEN
Solar/Wind Harmer
1.1
316011AB1-132 GEN
Solar/Wind Harmer
3.854
962571AG1-106 GEN
Solar/Wind Harmer
3.016
3145783HORNRTN
Solar/Wind Harmer
0.212
957481AF2-042 GEN
Solar/Wind Harmer
55.952
3145796HORNRTN
Solar/Wind Harmer
0.69
3145796HORNRTN
Solar/Wind Harmer
0.209
316023GEN1_S
Solar/Wind Harmer
0.469
316381AD1-082 GEN
Solar/Wind Harmer
0.216
316494AC1-189 GEN
Solar/Wind Harmer
0.699
960081AF2-299 GEN
Solar/Wind Harmer
1.961
970659AG2-427 GEN
Solar/Wind Harmer
9.765
961671AG1-007 GEN
Solar/Wind Harmer
0.031
3146083TARBORO
Solar/Wind Harmer
0.2
3145493TOT1
Solar/Wind Harmer
0.891
315722AD1-056 GEN
Solar/Wind Harmer
1.264
971795AH1-408 GEN
Solar/Wind Harmer
13.128
3146233WITAKRS
Solar/Wind Harmer
0.783
315693AD1-088 GEN
Solar/Wind Harmer
9.393
971647AH1-324 GEN
Solar/Wind Harmer
8.33
3147043LAWRENC
Adder
1.751
962491AG1-098 GEN
Solar/Wind Harmer
11.017
316129AC1-054 GEN
Solar/Wind Harmer
0.725
3145543BTLEBRO
Solar/Wind Harmer
0.192
3145543BTLEBRO
Solar/Wind Harmer
0.154
316359AB2-059 GEN
Solar/Wind Harmer
0.69
316049AB1-081 GEN
Solar/Wind Harmer
1.099
3142053HEARTS
Solar/Wind Harmer
0.338
971065AG2-659 GEN
Solar/Wind Harmer
8.154
316159AE1-175 C
Solar/Wind Harmer
0.162
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.963
971069AG2-661 GEN
Solar/Wind Harmer
2.884
316003AC1-222 GEN
Solar/Wind Harmer
0.004
970685AG2-442 GEN
Solar/Wind Harmer
10.916
316458AB2-190 GEN2
Solar/Wind Harmer
0.757
963171AG1-166 GEN
Solar/Wind Harmer
0.744
971563AH1-280 GEN
Solar/Wind Harmer
1.489
3144293JTRSVLE
Adder
0.444
970129AG2-093 GEN
Solar/Wind Harmer
3.913
944011AF1-069 GEN
Solar/Wind Harmer
15.607
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.178
3146206CASHIE
Solar/Wind Harmer
0.254
970601AG2-382 GEN
Solar/Wind Harmer
9.497
970673AG2-436 GEN
Solar/Wind Harmer
54.074
970673AG2-436 GEN
Solar/Wind Harmer
36.049
971967AH1-528 GEN
Solar/Wind Harmer
39.527
965291AG1-394 GEN
Solar/Wind Harmer
1.083
3145893MURPHYS
Solar/Wind Harmer
0.653
3145893MURPHYS
Solar/Wind Harmer
0.242
3145513AHOSKIE
Solar/Wind Harmer
0.5
3145513AHOSKIE
Solar/Wind Harmer
0.239
3145683EARLEYS
Solar/Wind Harmer
0.476
3145683EARLEYS
Solar/Wind Harmer
0.238
3145683EARLEYS
Solar/Wind Harmer
0.238
972265AH1-717 GEN
Adder
18.416
3151201GRAVEL4
Adder
17.263
3151191GRAVEL3
Adder
17.045
3151211GRAVEL5
Adder
17.045
970085AG2-068 GEN
Solar/Wind Harmer
12.547
970581AG2-369 GEN
Solar/Wind Harmer
10.791
3146043SEABORD
Solar/Wind Harmer
0.227
315607AA1-063A GEN
Solar/Wind Harmer
0.459
3146033SCOT NK
Solar/Wind Harmer
0.88
316005AA1-067
Solar/Wind Harmer
0.23
3145746EVERETS
Solar/Wind Harmer
0.854
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
3145746EVERETS
Solar/Wind Harmer
0.215
970181AG2-120 GEN
Solar/Wind Harmer
2.673
315652AC1-086 GEN
Solar/Wind Harmer
23.319
3137643SOCKMAN
Solar/Wind Harmer
0.841
3145796HORNRTN
Solar/Wind Harmer
0.669
3145796HORNRTN
Solar/Wind Harmer
0.084
316087AB2-174 GEN
Solar/Wind Harmer
0.006
957861AF2-080 GEN
Solar/Wind Harmer
8.925
315814AE2-033 C
Solar/Wind Harmer
16.342
316315AB2-025 C
Solar/Wind Harmer
0.167
316420AA1-050 GEN
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
0.2
3145573BETHELC
Solar/Wind Harmer
0.2
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
8.311
3138283WHITEMARSH
Solar/Wind Harmer
0.045
316369SG1_INVT
Solar/Wind Harmer
0.007
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3143316POE
Solar/Wind Harmer
0.643
316118AC1-105 GEN
Solar/Wind Harmer
0.419
3147173SINAI
Solar/Wind Harmer
0.161
3147243WELCO
Solar/Wind Harmer
0.1
971443AH1-215 GEN
Solar/Wind Harmer
2.584
3144303KENBRDG
Solar/Wind Harmer
0.122
970683AG2-441 GEN
Solar/Wind Harmer
9.746
970681AG2-440 GEN
Solar/Wind Harmer
7.797
316132AB2-190 GEN1
Solar/Wind Harmer
0.757
946301AF1-294 GEN
Solar/Wind Harmer
2.754
961791AG1-021 GEN
Solar/Wind Harmer
1.34
315657AE1-056 GEN
Solar/Wind Harmer
4.655
970865AG2-541 GEN
Solar/Wind Harmer
4.665
316123AC1-075 GEN
Solar/Wind Harmer
0.16
970165AG2-112 GEN
Solar/Wind Harmer
0.951
970163AG2-111 GEN
Solar/Wind Harmer
0.907
NYPJM->LTFIMP_NY
CLTF
1.821
LGEELTFEXP_LGEE->PJM
CLTF
0.973
LAGNLTFEXP_LAGN->PJM
CLTF
6.928
WECLTFEXP_WEC->PJM
CLTF
0.495
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.334
TVALTFEXP_TVA->PJM
CLTF
3.444
CPLELTFEXP_CPLE->PJM
CLTF
11.714
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.575
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.561
MECLTFEXP_MEC->PJM
CLTF
2.893
SIGELTFEXP_SIGE->PJM
CLTF
0.084

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: 57602_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57602_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.99 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3428.95
MW Contribution:12.77
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
225.326
3151081ELIZAR1
50/50
30.232
3151091ELIZAR2
50/50
29.706
941591AE2-156 GEN
50/50
27.531
3152611GOSPORTB
50/50
4.172
3152621GOSPORTC
50/50
3.541
3152601GOSPORTA
50/50
3.266
3151151S HAMPT1
50/50
0.647
957871AF2-081 GEN
Solar/Wind Harmer
17.319
319010AE1-072 C
Solar/Wind Harmer
6.96
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.906
316305AF2-043 C
Solar/Wind Harmer
1.007
316321Z2-027
Solar/Wind Harmer
0.896
3146396TANGLEW
Solar/Wind Harmer
0.611
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.033
3146486SUNBURY
Solar/Wind Harmer
-0.033
315835AF2-110_GEN
Solar/Wind Harmer
3.954
315611Z1-036_GEN2
Solar/Wind Harmer
7.784
3130156CHOWAN
Solar/Wind Harmer
-0.031
3130156CHOWAN
Solar/Wind Harmer
-0.031
971445AH1-216 GEN
Solar/Wind Harmer
18.161
315816AE2-034 GEN
Solar/Wind Harmer
2.372
316311AC2-079 GEN
Solar/Wind Harmer
14.288
315833AF1-017_GEN
Solar/Wind Harmer
5.368
316349AD2-085 GEN
Solar/Wind Harmer
2.513
3130546PLYMOUTH
Solar/Wind Harmer
-0.028
315732AD1-074 GEN1
Solar/Wind Harmer
5.671
315733AD1-074 GEN2
Solar/Wind Harmer
5.671
315735AD1-075 GEN1
Solar/Wind Harmer
2.836
3146206CASHIE
Solar/Wind Harmer
-0.027
970601AG2-382 GEN
Solar/Wind Harmer
11.922
972265AH1-717 GEN
Adder
18.264
3151201GRAVEL4
Adder
17.121
3151191GRAVEL3
Adder
16.904
3151211GRAVEL5
Adder
16.904
965291AG1-394 GEN
Solar/Wind Harmer
2.317
941031AE2-094 GEN
Solar/Wind Harmer
48.872
944011AF1-069 GEN
Solar/Wind Harmer
15.313
316318V4-068
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.069
3152331SURRY 2
50/50
16.971
3150981CHESPKA
50/50
4.092
970017AG2-010 GEN
50/50
18.076
316294AC1-161 GEN
Solar/Wind Harmer
13.15
944591AF1-124 GEN
Solar/Wind Harmer
165.29
316388AE2-253 GEN
Solar/Wind Harmer
2.342
316375AC2-012 GEN
Solar/Wind Harmer
12.01
3146456SLIGO L269
Solar/Wind Harmer
-0.034
316246AF1-032 C
Solar/Wind Harmer
0.676
3146516WINFALL
Solar/Wind Harmer
-0.105
3146516WINFALL
Solar/Wind Harmer
-0.032
316072AD1-144
Solar/Wind Harmer
0.649
316093AE2-104_GEN
Solar/Wind Harmer
9.196
315800Z1-036_GEN1
Solar/Wind Harmer
7.784
939411AE1-173 GEN
Solar/Wind Harmer
155.471
3130156CHOWAN
Solar/Wind Harmer
-0.031
3138126ROCKLANDING
Solar/Wind Harmer
0.091
940641AE2-051 GEN
Solar/Wind Harmer
27.808
3145336SMITFLD
Solar/Wind Harmer
-0.118
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.485
971317AH1-138 GEN
Solar/Wind Harmer
3.417
3146206CASHIE
Solar/Wind Harmer
-0.027
971547AH1-271 GEN
Solar/Wind Harmer
6.812
3151171GRAVELC
Adder
2.502
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145513AHOSKIE
Solar/Wind Harmer
0.223
961941AG1-037 GEN
Solar/Wind Harmer
0.192
3145513AHOSKIE
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
53.595
970673AG2-436 GEN
Solar/Wind Harmer
27.137
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.897
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.421
970085AG2-068 GEN
Solar/Wind Harmer
14.854
970581AG2-369 GEN
Solar/Wind Harmer
12.774
3146033SCOT NK
Solar/Wind Harmer
-0.093
316005AA1-067
Solar/Wind Harmer
0.461
3145746EVERETS
Solar/Wind Harmer
-0.09
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970181AG2-120 GEN
Solar/Wind Harmer
2.991
315652AC1-086 GEN
Solar/Wind Harmer
25.282
3137643SOCKMAN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316087AB2-174 GEN
Solar/Wind Harmer
3.132
957861AF2-080 GEN
Solar/Wind Harmer
9.588
957831AF2-077 GEN
Solar/Wind Harmer
0.656
3138283WHITEMARSH
Solar/Wind Harmer
0.034
315814AE2-033 C
Solar/Wind Harmer
20.267
316315AB2-025 C
Solar/Wind Harmer
0.586
946281AF1-292 GEN
Solar/Wind Harmer
0.485
316420AA1-050 GEN
Solar/Wind Harmer
2.455
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
316319Z2-044 C
Solar/Wind Harmer
1.147
970831AG2-522 GEN
Solar/Wind Harmer
10.299
316369SG1_INVT
Solar/Wind Harmer
3.638
316239AB2-077_GEN
Solar/Wind Harmer
0.544
316238AB2-078_GEN
Solar/Wind Harmer
0.544
3143316POE
Solar/Wind Harmer
-0.071
316118AC1-105 GEN
Solar/Wind Harmer
1.172
971443AH1-215 GEN
Solar/Wind Harmer
3.313
3147173SINAI
Solar/Wind Harmer
-0.017
3144303KENBRDG
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.01
316132AB2-190 GEN1
Solar/Wind Harmer
1.695
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.768
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.025
316174AB2-169 GEN
Solar/Wind Harmer
3.904
3146263WOODLND
Solar/Wind Harmer
-0.025
970661AG2-428 GEN
Solar/Wind Harmer
25.975
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.883
970919AG2-571 GEN
Solar/Wind Harmer
7.555
970087AG2-069 GEN
Solar/Wind Harmer
22.28
3146293MARTNCO
Solar/Wind Harmer
0.147
316190AA2-174 GEN
Solar/Wind Harmer
0.283
316381AD1-082 GEN
Solar/Wind Harmer
2.1
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
1.967
3145783HORNRTN
Solar/Wind Harmer
-0.022
316011AB1-132 GEN
Solar/Wind Harmer
4.702
962571AG1-106 GEN
Solar/Wind Harmer
3.23
970659AG2-427 GEN
Solar/Wind Harmer
11.88
971647AH1-324 GEN
Solar/Wind Harmer
11.103
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
1.491
316494AC1-189 GEN
Solar/Wind Harmer
2.358
960081AF2-299 GEN
Solar/Wind Harmer
2.435
957481AF2-042 GEN
Solar/Wind Harmer
67.465
316159AE1-175 C
Solar/Wind Harmer
0.572
961671AG1-007 GEN
Solar/Wind Harmer
0.268
3146083TARBORO
Solar/Wind Harmer
-0.021
3145493TOT1
Solar/Wind Harmer
0.628
315722AD1-056 GEN
Solar/Wind Harmer
2.204
971795AH1-408 GEN
Solar/Wind Harmer
15.673
3146233WITAKRS
Solar/Wind Harmer
-0.082
3147043LAWRENC
Adder
1.655
315693AD1-088 GEN
Solar/Wind Harmer
10.204
316129AC1-054 GEN
Solar/Wind Harmer
1.787
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316359AB2-059 GEN
Solar/Wind Harmer
2.728
316049AB1-081 GEN
Solar/Wind Harmer
2.183
3142053HEARTS
Solar/Wind Harmer
0.238
962491AG1-098 GEN
Solar/Wind Harmer
13.502
971065AG2-659 GEN
Solar/Wind Harmer
10.095
315687AD1-152 GEN
Solar/Wind Harmer
2.316
971069AG2-661 GEN
Solar/Wind Harmer
2.988
316237AB2-079_GEN
Solar/Wind Harmer
0.544
970401AG2-262 GEN
Solar/Wind Harmer
1.13
316458AB2-190 GEN2
Solar/Wind Harmer
1.695
970129AG2-093 GEN
Solar/Wind Harmer
3.741
3144293JTRSVLE
Adder
0.444
970685AG2-442 GEN
Solar/Wind Harmer
4.766
3151101ELIZAR3
50/50
30.618
3150921YORKTN3
50/50
7.134
3144216WINCHST
50/50
1.058
3151161SURRY 1
50/50
9.035
315773AC2-141 GEN
Solar/Wind Harmer
17.008
944581AF1-123 GEN
Solar/Wind Harmer
164.697
944601AF1-125 GEN
Solar/Wind Harmer
162.127
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
4.203
316320Y1-086
Solar/Wind Harmer
1.969
3144536CHRHLND
Solar/Wind Harmer
-0.005
316435W1029_GEN3
Solar/Wind Harmer
5.911
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146376EDENTON
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.022
3145336SMITFLD
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
3.163
971157AH1-035 GEN
Solar/Wind Harmer
3.53
315737AD1-076 GEN
Solar/Wind Harmer
5.329
3146206CASHIE
Solar/Wind Harmer
-0.027
3151221GRAVEL6
Adder
17.101
3151171GRAVELC
Adder
3.29
3156081AA2-088 GEN
Solar/Wind Harmer
8.556
3156021HOLLOMANSOL
Solar/Wind Harmer
3.519
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.333
961681AG1-008 GEN
Solar/Wind Harmer
20.333
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.413
316140AB2-099
Solar/Wind Harmer
0.172
962331AG1-082 GEN
Solar/Wind Harmer
3.192
3146263WOODLND
Solar/Wind Harmer
-0.025
970661AG2-428 GEN
Solar/Wind Harmer
4.603
316317KELFORD C
Solar/Wind Harmer
1.151
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.07
970917AG2-570 GEN
Solar/Wind Harmer
59.688
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.965
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316083AB2-161 GEN
Solar/Wind Harmer
3.716
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316210AC1-098 GEN
Solar/Wind Harmer
3.54
970659AG2-427 GEN
Solar/Wind Harmer
2.105
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
316365GEN2_N
Solar/Wind Harmer
1.491
313506AB2-031 GEN
Solar/Wind Harmer
1.775
966621AG1-532 GEN
Solar/Wind Harmer
0.439
316382AG1-145 C
Solar/Wind Harmer
0.642
316327AA2-057 GEN
Solar/Wind Harmer
2.148
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
315724AD1-057 GEN
Solar/Wind Harmer
1.212
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
3147043LAWRENC
Solar/Wind Harmer
-0.012
316478AD1-087 GEN
Solar/Wind Harmer
1.777
316486AD2-202 GEN
Solar/Wind Harmer
0.521
961601AG1-000A GEN
Solar/Wind Harmer
8.058
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
315813AE1-149 C
Solar/Wind Harmer
12.189
315778AD1-151 GEN
Solar/Wind Harmer
16.359
316131AB2-060 GEN
Solar/Wind Harmer
1.938
964241AG1-285 GEN
Solar/Wind Harmer
13.75
315785AD2-033 C
Solar/Wind Harmer
3.854
316248AF1-058 C
Solar/Wind Harmer
0.506
960061AF2-297 GEN
Solar/Wind Harmer
8.39
970257AG2-171 GEN
Solar/Wind Harmer
6.293
959311AF2-222 GEN
Solar/Wind Harmer
17.346
970129AG2-093 GEN
Solar/Wind Harmer
9.235
3144293JTRSVLE
Adder
0.444
3150991CHESPKB
50/50
3.433
3150991CHESPKB
50/50
3.351
316185AD1-033 GEN
Solar/Wind Harmer
3.709
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
3142956BIRDNECK
Solar/Wind Harmer
1.874
316316AC1-027 C
Solar/Wind Harmer
1.071
316339AD2-160 GEN
Solar/Wind Harmer
2.342
316036AC1-147 C
Solar/Wind Harmer
0.936
316018AA1-139 ULT2
Solar/Wind Harmer
2.967
316017AA1-139 ULT1
Solar/Wind Harmer
2.803
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.072
3130086AYDLETT
Solar/Wind Harmer
-0.137
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
5.911
316433W1029_GEN2
Solar/Wind Harmer
5.911
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146376EDENTON
Solar/Wind Harmer
0.912
3146376EDENTON
Solar/Wind Harmer
0.912
316236AE1-162_GEN
Solar/Wind Harmer
0.893
315742AE1-103 GEN
Solar/Wind Harmer
3.056
316065AD1-022 GEN
Solar/Wind Harmer
13.769
3145893MURPHYS
Solar/Wind Harmer
0.722
3145893MURPHYS
Solar/Wind Harmer
-0.046
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
972185AH1-677 GEN
Adder
12.602
972187AH1-678 GEN
Adder
6.302
970933AG2-581 GEN
Solar/Wind Harmer
22.49
3145933PARMELE
Solar/Wind Harmer
-0.047
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
7.338
970657AG2-426 GEN
Solar/Wind Harmer
1.535
316426AA2-053 GEN
Solar/Wind Harmer
2.332
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.54
3145593CAROLNA
Solar/Wind Harmer
0.188
3145783HORNRTN
Solar/Wind Harmer
2.669
3145783HORNRTN
Solar/Wind Harmer
2.136
3145783HORNRTN
Solar/Wind Harmer
0.667
3145783HORNRTN
Solar/Wind Harmer
0.267
3145796HORNRTN
Solar/Wind Harmer
-0.066
316181AB2-040 GEN
Solar/Wind Harmer
3.081
316274AC1-208 GEN
Solar/Wind Harmer
2.378
3144356SAPONY
Solar/Wind Harmer
0.758
970099AG2-077 GEN
Solar/Wind Harmer
26.986
3145493TOT1
Solar/Wind Harmer
0.327
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.131
316033AB2-134 GEN
Solar/Wind Harmer
6.566
315697AD1-025 GEN
Solar/Wind Harmer
4.118
961601AG1-000A GEN
Solar/Wind Harmer
7.957
316263AC1-034 GEN
Solar/Wind Harmer
9.484
939181AE1-148 GEN
Solar/Wind Harmer
10.688
313527AB2-043 GEN
Solar/Wind Harmer
2.932
962561AG1-105 GEN
Solar/Wind Harmer
9.801
964791AG1-342 GEN
Solar/Wind Harmer
3.698
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
971741AH1-377 GEN
Solar/Wind Harmer
19.947
970323AG2-213 GEN
Solar/Wind Harmer
8.39
971775AH1-396 GEN
Solar/Wind Harmer
1.195
316034AC1-036 C
Solar/Wind Harmer
0.311
3144293JTRSVLE
Adder
0.444
3144293JTRSVLE
Adder
0.374
NYPJM->LTFIMP_NY
CLTF
1.758
LAGNLTFEXP_LAGN->PJM
CLTF
6.399
LGEELTFEXP_LGEE->PJM
CLTF
0.9
WECLTFEXP_WEC->PJM
CLTF
0.456
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.443
TVALTFEXP_TVA->PJM
CLTF
3.184
CPLELTFEXP_CPLE->PJM
CLTF
10.804
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.931
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.372
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.689
MECLTFEXP_MEC->PJM
CLTF
2.668
SIGELTFEXP_SIGE->PJM
CLTF
0.078

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P4-2: WT576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: WT576_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.99 %
Rating:2931.0 MVA
Rating Type:C
MVA to Mitigate:3428.93
MW Contribution:12.77
Bus #Bus NameTypeMW Contribution
972263AH1-716 GEN
50/50
225.326
3151081ELIZAR1
50/50
30.232
3151091ELIZAR2
50/50
29.706
941591AE2-156 GEN
50/50
27.531
3152611GOSPORTB
50/50
4.172
3152621GOSPORTC
50/50
3.541
3152601GOSPORTA
50/50
3.266
3151151S HAMPT1
50/50
0.647
957871AF2-081 GEN
Solar/Wind Harmer
17.319
319010AE1-072 C
Solar/Wind Harmer
6.96
3146406KITTY HAWK
Solar/Wind Harmer
0.029
313526AB2-022
Solar/Wind Harmer
0.906
316305AF2-043 C
Solar/Wind Harmer
1.007
316321Z2-027
Solar/Wind Harmer
0.896
3146396TANGLEW
Solar/Wind Harmer
0.611
3145176PASQUOTANK
Solar/Wind Harmer
-0.021
3146486SUNBURY
Solar/Wind Harmer
-0.033
3146486SUNBURY
Solar/Wind Harmer
-0.033
315835AF2-110_GEN
Solar/Wind Harmer
3.954
315611Z1-036_GEN2
Solar/Wind Harmer
7.784
3130156CHOWAN
Solar/Wind Harmer
-0.031
3130156CHOWAN
Solar/Wind Harmer
-0.031
971445AH1-216 GEN
Solar/Wind Harmer
18.161
315816AE2-034 GEN
Solar/Wind Harmer
2.372
316311AC2-079 GEN
Solar/Wind Harmer
14.288
315833AF1-017_GEN
Solar/Wind Harmer
5.368
316349AD2-085 GEN
Solar/Wind Harmer
2.513
3130546PLYMOUTH
Solar/Wind Harmer
-0.028
315732AD1-074 GEN1
Solar/Wind Harmer
5.671
315733AD1-074 GEN2
Solar/Wind Harmer
5.671
315735AD1-075 GEN1
Solar/Wind Harmer
2.836
3146206CASHIE
Solar/Wind Harmer
-0.027
970601AG2-382 GEN
Solar/Wind Harmer
11.922
972265AH1-717 GEN
Adder
18.264
3151201GRAVEL4
Adder
17.121
3151191GRAVEL3
Adder
16.904
3151211GRAVEL5
Adder
16.904
965291AG1-394 GEN
Solar/Wind Harmer
2.317
941031AE2-094 GEN
Solar/Wind Harmer
48.872
944011AF1-069 GEN
Solar/Wind Harmer
15.313
316318V4-068
Solar/Wind Harmer
0.645
3145893MURPHYS
Solar/Wind Harmer
-0.069
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145513AHOSKIE
Solar/Wind Harmer
0.223
961941AG1-037 GEN
Solar/Wind Harmer
0.192
3145513AHOSKIE
Solar/Wind Harmer
-0.025
970673AG2-436 GEN
Solar/Wind Harmer
53.595
970673AG2-436 GEN
Solar/Wind Harmer
27.137
3145683EARLEYS
Solar/Wind Harmer
-0.05
3145683EARLEYS
Solar/Wind Harmer
-0.025
3145683EARLEYS
Solar/Wind Harmer
-0.025
971967AH1-528 GEN
Solar/Wind Harmer
46.897
3146043SEABORD
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.421
970085AG2-068 GEN
Solar/Wind Harmer
14.853
970581AG2-369 GEN
Solar/Wind Harmer
12.774
3146033SCOT NK
Solar/Wind Harmer
-0.093
316005AA1-067
Solar/Wind Harmer
0.461
3145746EVERETS
Solar/Wind Harmer
-0.09
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
970181AG2-120 GEN
Solar/Wind Harmer
2.991
315652AC1-086 GEN
Solar/Wind Harmer
25.282
3137643SOCKMAN
Solar/Wind Harmer
-0.089
3145796HORNRTN
Solar/Wind Harmer
-0.07
3145796HORNRTN
Solar/Wind Harmer
-0.009
316087AB2-174 GEN
Solar/Wind Harmer
3.132
957861AF2-080 GEN
Solar/Wind Harmer
9.588
957831AF2-077 GEN
Solar/Wind Harmer
0.656
3138283WHITEMARSH
Solar/Wind Harmer
0.034
315814AE2-033 C
Solar/Wind Harmer
20.267
316315AB2-025 C
Solar/Wind Harmer
0.586
946281AF1-292 GEN
Solar/Wind Harmer
0.485
316420AA1-050 GEN
Solar/Wind Harmer
2.455
3145573BETHELC
Solar/Wind Harmer
-0.021
3145573BETHELC
Solar/Wind Harmer
-0.021
316319Z2-044 C
Solar/Wind Harmer
1.147
970831AG2-522 GEN
Solar/Wind Harmer
10.299
316369SG1_INVT
Solar/Wind Harmer
3.638
316239AB2-077_GEN
Solar/Wind Harmer
0.544
316238AB2-078_GEN
Solar/Wind Harmer
0.544
3143316POE
Solar/Wind Harmer
-0.071
316118AC1-105 GEN
Solar/Wind Harmer
1.172
971443AH1-215 GEN
Solar/Wind Harmer
3.313
3147173SINAI
Solar/Wind Harmer
-0.017
3144303KENBRDG
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.01
316132AB2-190 GEN1
Solar/Wind Harmer
1.695
3150991CHESPKB
50/50
3.433
3150991CHESPKB
50/50
3.351
316185AD1-033 GEN
Solar/Wind Harmer
3.709
3145506HICKORY
Solar/Wind Harmer
-0.139
3145506HICKORY
Solar/Wind Harmer
-0.084
3145506HICKORY
Solar/Wind Harmer
-0.021
3142956BIRDNECK
Solar/Wind Harmer
1.874
316316AC1-027 C
Solar/Wind Harmer
1.071
316339AD2-160 GEN
Solar/Wind Harmer
2.342
316036AC1-147 C
Solar/Wind Harmer
0.936
316018AA1-139 ULT2
Solar/Wind Harmer
2.967
316017AA1-139 ULT1
Solar/Wind Harmer
2.803
3137176SLIGO L2192
Solar/Wind Harmer
-0.136
3146456SLIGO L269
Solar/Wind Harmer
4.072
3130086AYDLETT
Solar/Wind Harmer
-0.137
3146386ELIZ CT
Solar/Wind Harmer
-0.034
316431W1029_GEN1
Solar/Wind Harmer
5.911
316433W1029_GEN2
Solar/Wind Harmer
5.911
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146376EDENTON
Solar/Wind Harmer
0.912
3146376EDENTON
Solar/Wind Harmer
0.912
316236AE1-162_GEN
Solar/Wind Harmer
0.893
315742AE1-103 GEN
Solar/Wind Harmer
3.056
316065AD1-022 GEN
Solar/Wind Harmer
13.769
3145893MURPHYS
Solar/Wind Harmer
0.722
3145893MURPHYS
Solar/Wind Harmer
-0.046
3146173TUNIS
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
972185AH1-677 GEN
Adder
12.602
972187AH1-678 GEN
Adder
6.302
970933AG2-581 GEN
Solar/Wind Harmer
22.49
3145933PARMELE
Solar/Wind Harmer
-0.047
3145933PARMELE
Solar/Wind Harmer
-0.024
970657AG2-426 GEN
Solar/Wind Harmer
7.338
970657AG2-426 GEN
Solar/Wind Harmer
1.535
316426AA2-053 GEN
Solar/Wind Harmer
2.332
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
966811AG1-552 GEN
Solar/Wind Harmer
2.54
3145593CAROLNA
Solar/Wind Harmer
0.188
3145783HORNRTN
Solar/Wind Harmer
2.669
3145783HORNRTN
Solar/Wind Harmer
2.136
3145783HORNRTN
Solar/Wind Harmer
0.667
3145783HORNRTN
Solar/Wind Harmer
0.267
3145796HORNRTN
Solar/Wind Harmer
-0.066
316181AB2-040 GEN
Solar/Wind Harmer
3.081
316274AC1-208 GEN
Solar/Wind Harmer
2.378
3144356SAPONY
Solar/Wind Harmer
0.758
970099AG2-077 GEN
Solar/Wind Harmer
26.986
3145493TOT1
Solar/Wind Harmer
0.327
3145453TOT5
Solar/Wind Harmer
0.196
3145603CNETO
Solar/Wind Harmer
0.131
316033AB2-134 GEN
Solar/Wind Harmer
6.566
315697AD1-025 GEN
Solar/Wind Harmer
4.118
961601AG1-000A GEN
Solar/Wind Harmer
7.957
316263AC1-034 GEN
Solar/Wind Harmer
9.484
939181AE1-148 GEN
Solar/Wind Harmer
10.688
313527AB2-043 GEN
Solar/Wind Harmer
2.932
962561AG1-105 GEN
Solar/Wind Harmer
9.801
964791AG1-342 GEN
Solar/Wind Harmer
3.698
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
971741AH1-377 GEN
Solar/Wind Harmer
19.946
970323AG2-213 GEN
Solar/Wind Harmer
8.39
971775AH1-396 GEN
Solar/Wind Harmer
1.195
316034AC1-036 C
Solar/Wind Harmer
0.311
3144293JTRSVLE
Adder
0.444
3144293JTRSVLE
Adder
0.374
3152331SURRY 2
50/50
16.971
3150981CHESPKA
50/50
4.092
970017AG2-010 GEN
50/50
18.076
316294AC1-161 GEN
Solar/Wind Harmer
13.15
944591AF1-124 GEN
Solar/Wind Harmer
165.29
316388AE2-253 GEN
Solar/Wind Harmer
2.342
316375AC2-012 GEN
Solar/Wind Harmer
12.01
3146456SLIGO L269
Solar/Wind Harmer
-0.034
316246AF1-032 C
Solar/Wind Harmer
0.676
3146516WINFALL
Solar/Wind Harmer
-0.105
3146516WINFALL
Solar/Wind Harmer
-0.032
316072AD1-144
Solar/Wind Harmer
0.649
316093AE2-104_GEN
Solar/Wind Harmer
9.196
3151101ELIZAR3
50/50
30.618
3150921YORKTN3
50/50
7.134
3144216WINCHST
50/50
1.058
3151161SURRY 1
50/50
9.035
315773AC2-141 GEN
Solar/Wind Harmer
17.008
944581AF1-123 GEN
Solar/Wind Harmer
164.697
944601AF1-125 GEN
Solar/Wind Harmer
162.127
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3146456SLIGO L269
Solar/Wind Harmer
-0.034
971153AH1-033 GEN
Solar/Wind Harmer
4.203
316320Y1-086
Solar/Wind Harmer
1.969
3144536CHRHLND
Solar/Wind Harmer
-0.005
316435W1029_GEN3
Solar/Wind Harmer
5.911
3146516WINFALL
Solar/Wind Harmer
-0.032
3146626S HERTFORD
Solar/Wind Harmer
-0.032
3146376EDENTON
Solar/Wind Harmer
-0.031
3145273HOLLAND
Solar/Wind Harmer
-0.022
3145336SMITFLD
Solar/Wind Harmer
-0.012
315614AA2-178 GEN
Solar/Wind Harmer
3.163
971157AH1-035 GEN
Solar/Wind Harmer
3.53
315737AD1-076 GEN
Solar/Wind Harmer
5.329
3146206CASHIE
Solar/Wind Harmer
-0.027
3151221GRAVEL6
Adder
17.101
3151171GRAVELC
Adder
3.29
3156081AA2-088 GEN
Solar/Wind Harmer
8.556
3156021HOLLOMANSOL
Solar/Wind Harmer
3.519
3145893MURPHYS
Solar/Wind Harmer
0.181
3145893MURPHYS
Solar/Wind Harmer
-0.026
957521AF2-046 GEN
Solar/Wind Harmer
20.333
961681AG1-008 GEN
Solar/Wind Harmer
20.333
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
316463AE2-346 GEN
Solar/Wind Harmer
0.413
316140AB2-099
Solar/Wind Harmer
0.172
962331AG1-082 GEN
Solar/Wind Harmer
3.192
3146263WOODLND
Solar/Wind Harmer
-0.025
970661AG2-428 GEN
Solar/Wind Harmer
4.603
316317KELFORD C
Solar/Wind Harmer
1.151
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
5.07
970917AG2-570 GEN
Solar/Wind Harmer
59.688
3145933PARMELE
Solar/Wind Harmer
-0.024
966801AG1-551 GEN
Solar/Wind Harmer
2.965
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316083AB2-161 GEN
Solar/Wind Harmer
3.716
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316210AC1-098 GEN
Solar/Wind Harmer
3.54
970659AG2-427 GEN
Solar/Wind Harmer
2.105
3145796HORNRTN
Solar/Wind Harmer
-0.088
3145796HORNRTN
Solar/Wind Harmer
-0.022
316365GEN2_N
Solar/Wind Harmer
1.491
313506AB2-031 GEN
Solar/Wind Harmer
1.775
966621AG1-532 GEN
Solar/Wind Harmer
0.439
316382AG1-145 C
Solar/Wind Harmer
0.642
316327AA2-057 GEN
Solar/Wind Harmer
2.148
3146073TAR RVR
Solar/Wind Harmer
-0.021
3146083TARBORO
Solar/Wind Harmer
-0.021
315724AD1-057 GEN
Solar/Wind Harmer
1.212
3146233WITAKRS
Solar/Wind Harmer
0.434
3146233WITAKRS
Solar/Wind Harmer
-0.014
3138543CONSLDL
Solar/Wind Harmer
-0.014
3147043LAWRENC
Solar/Wind Harmer
-0.012
316478AD1-087 GEN
Solar/Wind Harmer
1.777
316486AD2-202 GEN
Solar/Wind Harmer
0.521
961601AG1-000A GEN
Solar/Wind Harmer
8.058
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.02
315813AE1-149 C
Solar/Wind Harmer
12.189
315778AD1-151 GEN
Solar/Wind Harmer
16.359
316131AB2-060 GEN
Solar/Wind Harmer
1.938
964241AG1-285 GEN
Solar/Wind Harmer
13.75
315785AD2-033 C
Solar/Wind Harmer
3.854
315800Z1-036_GEN1
Solar/Wind Harmer
7.784
939411AE1-173 GEN
Solar/Wind Harmer
155.471
3130156CHOWAN
Solar/Wind Harmer
-0.031
3138126ROCKLANDING
Solar/Wind Harmer
0.091
940641AE2-051 GEN
Solar/Wind Harmer
27.808
3145336SMITFLD
Solar/Wind Harmer
-0.118
3145663CRESWEL
Solar/Wind Harmer
-0.082
971163AH1-040 GEN
Solar/Wind Harmer
27.485
971317AH1-138 GEN
Solar/Wind Harmer
3.417
3146206CASHIE
Solar/Wind Harmer
-0.027
971547AH1-271 GEN
Solar/Wind Harmer
6.812
3151171GRAVELC
Adder
2.502
3145893MURPHYS
Solar/Wind Harmer
-0.103
3145893MURPHYS
Solar/Wind Harmer
0.768
3145963POPLR C
Solar/Wind Harmer
-0.026
3146173TUNIS
Solar/Wind Harmer
-0.026
3145683EARLEYS
Solar/Wind Harmer
-0.025
316174AB2-169 GEN
Solar/Wind Harmer
3.904
3146263WOODLND
Solar/Wind Harmer
-0.025
970661AG2-428 GEN
Solar/Wind Harmer
25.975
3145823KELFORD
Solar/Wind Harmer
-0.024
961611AG1-000B GEN
Solar/Wind Harmer
11.883
970919AG2-571 GEN
Solar/Wind Harmer
7.555
970087AG2-069 GEN
Solar/Wind Harmer
22.28
3146293MARTNCO
Solar/Wind Harmer
0.147
316190AA2-174 GEN
Solar/Wind Harmer
0.283
316381AD1-082 GEN
Solar/Wind Harmer
2.1
3145746EVERETS
Solar/Wind Harmer
-0.023
3145746EVERETS
Solar/Wind Harmer
-0.023
316212AC1-099_GEN
Solar/Wind Harmer
1.967
3145783HORNRTN
Solar/Wind Harmer
-0.022
316011AB1-132 GEN
Solar/Wind Harmer
4.702
962571AG1-106 GEN
Solar/Wind Harmer
3.23
970659AG2-427 GEN
Solar/Wind Harmer
11.88
971647AH1-324 GEN
Solar/Wind Harmer
11.103
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
1.491
316494AC1-189 GEN
Solar/Wind Harmer
2.358
960081AF2-299 GEN
Solar/Wind Harmer
2.435
957481AF2-042 GEN
Solar/Wind Harmer
67.465
316159AE1-175 C
Solar/Wind Harmer
0.572
961671AG1-007 GEN
Solar/Wind Harmer
0.268
3146083TARBORO
Solar/Wind Harmer
-0.021
3145493TOT1
Solar/Wind Harmer
0.628
315722AD1-056 GEN
Solar/Wind Harmer
2.204
971795AH1-408 GEN
Solar/Wind Harmer
15.673
3146233WITAKRS
Solar/Wind Harmer
-0.082
3147043LAWRENC
Adder
1.655
315693AD1-088 GEN
Solar/Wind Harmer
10.204
316129AC1-054 GEN
Solar/Wind Harmer
1.787
3145543BTLEBRO
Solar/Wind Harmer
-0.02
3145543BTLEBRO
Solar/Wind Harmer
-0.016
316359AB2-059 GEN
Solar/Wind Harmer
2.728
316049AB1-081 GEN
Solar/Wind Harmer
2.183
3142053HEARTS
Solar/Wind Harmer
0.238
962491AG1-098 GEN
Solar/Wind Harmer
13.502
971065AG2-659 GEN
Solar/Wind Harmer
10.095
315687AD1-152 GEN
Solar/Wind Harmer
2.316
971069AG2-661 GEN
Solar/Wind Harmer
2.988
316237AB2-079_GEN
Solar/Wind Harmer
0.544
970401AG2-262 GEN
Solar/Wind Harmer
1.13
316458AB2-190 GEN2
Solar/Wind Harmer
1.695
970129AG2-093 GEN
Solar/Wind Harmer
3.741
3144293JTRSVLE
Adder
0.444
970685AG2-442 GEN
Solar/Wind Harmer
4.766
316248AF1-058 C
Solar/Wind Harmer
0.506
960061AF2-297 GEN
Solar/Wind Harmer
8.39
970257AG2-171 GEN
Solar/Wind Harmer
6.293
959311AF2-222 GEN
Solar/Wind Harmer
17.346
970129AG2-093 GEN
Solar/Wind Harmer
9.235
3144293JTRSVLE
Adder
0.444
NYPJM->LTFIMP_NY
CLTF
1.758
LGEELTFEXP_LGEE->PJM
CLTF
0.9
LAGNLTFEXP_LAGN->PJM
CLTF
6.399
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.443
WECLTFEXP_WEC->PJM
CLTF
0.456
TVALTFEXP_TVA->PJM
CLTF
3.184
CPLELTFEXP_CPLE->PJM
CLTF
10.804
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.931
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.372
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.689
MECLTFEXP_MEC->PJM
CLTF
2.668
SIGELTFEXP_SIGE->PJM
CLTF
0.078

Details for 8SURRY-8CHCKAHM 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 576_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SURRY-8CHCKAHM 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 576_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.66 %
Rating:2442.12 MVA
Rating Type:B
MVA to Mitigate:2824.62
MW Contribution:9.7
Bus #Bus NameTypeMW Contribution
3150991CHESPKB
50/50
3.433
3150991CHESPKB
50/50
3.351
316185AD1-033 GEN
Solar/Wind Harmer
0.009
3145506HICKORY
Solar/Wind Harmer
1.246
3145506HICKORY
Solar/Wind Harmer
0.748
3145506HICKORY
Solar/Wind Harmer
0.187
3142956BIRDNECK
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.298
316339AD2-160 GEN
Solar/Wind Harmer
0.501
316036AC1-147 C
Solar/Wind Harmer
0.057
316018AA1-139 ULT2
Solar/Wind Harmer
0.008
316017AA1-139 ULT1
Solar/Wind Harmer
0.172
3137176SLIGO L2192
Solar/Wind Harmer
1.221
3146456SLIGO L269
Solar/Wind Harmer
5.429
3130086AYDLETT
Solar/Wind Harmer
1.222
3146386ELIZ CT
Solar/Wind Harmer
0.299
316431W1029_GEN1
Solar/Wind Harmer
0.002
316433W1029_GEN2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.289
3146516WINFALL
Solar/Wind Harmer
0.289
3146516WINFALL
Solar/Wind Harmer
0.289
3146626S HERTFORD
Solar/Wind Harmer
0.285
3146626S HERTFORD
Solar/Wind Harmer
0.285
3146376EDENTON
Solar/Wind Harmer
1.215
3146376EDENTON
Solar/Wind Harmer
1.215
316236AE1-162_GEN
Solar/Wind Harmer
0.002
315742AE1-103 GEN
Solar/Wind Harmer
0.003
316065AD1-022 GEN
Solar/Wind Harmer
11.285
3145893MURPHYS
Solar/Wind Harmer
1.541
3145893MURPHYS
Solar/Wind Harmer
0.414
3146173TUNIS
Solar/Wind Harmer
0.228
3146173TUNIS
Solar/Wind Harmer
0.228
972185AH1-677 GEN
Adder
12.602
972187AH1-678 GEN
Adder
6.302
970933AG2-581 GEN
Solar/Wind Harmer
17.079
3145933PARMELE
Solar/Wind Harmer
0.422
3145933PARMELE
Solar/Wind Harmer
0.211
970657AG2-426 GEN
Solar/Wind Harmer
7.32
970657AG2-426 GEN
Solar/Wind Harmer
1.535
316426AA2-053 GEN
Solar/Wind Harmer
0.694
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
3142666NORTHAMPTON
Solar/Wind Harmer
0.122
3145593CAROLNA
Solar/Wind Harmer
0.201
3145593CAROLNA
Solar/Wind Harmer
0.201
966811AG1-552 GEN
Solar/Wind Harmer
2.179
3145593CAROLNA
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
3.559
3145783HORNRTN
Solar/Wind Harmer
2.847
3145783HORNRTN
Solar/Wind Harmer
0.89
3145783HORNRTN
Solar/Wind Harmer
0.356
3145796HORNRTN
Solar/Wind Harmer
0.591
316181AB2-040 GEN
Solar/Wind Harmer
0.285
316274AC1-208 GEN
Solar/Wind Harmer
1.018
3144356SAPONY
Solar/Wind Harmer
1.618
970099AG2-077 GEN
Solar/Wind Harmer
20.492
3145493TOT1
Solar/Wind Harmer
0.436
3145453TOT5
Solar/Wind Harmer
0.262
3145603CNETO
Solar/Wind Harmer
0.175
316033AB2-134 GEN
Solar/Wind Harmer
0.011
315697AD1-025 GEN
Solar/Wind Harmer
0.204
961601AG1-000A GEN
Solar/Wind Harmer
3.203
316263AC1-034 GEN
Solar/Wind Harmer
6.842
939181AE1-148 GEN
Solar/Wind Harmer
8.116
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.441
964791AG1-342 GEN
Solar/Wind Harmer
2.957
3146843MT LREL
Solar/Wind Harmer
0.154
3146843MT LREL
Solar/Wind Harmer
0.154
971741AH1-377 GEN
Solar/Wind Harmer
15.14
970323AG2-213 GEN
Solar/Wind Harmer
6.369
971775AH1-396 GEN
Solar/Wind Harmer
0.239
316034AC1-036 C
Solar/Wind Harmer
0.011
3151101ELIZAR3
50/50
30.619
3150921YORKTN3
50/50
7.134
3144216WINCHST
50/50
1.059
3151161SURRY 1
50/50
9.036
315773AC2-141 GEN
Solar/Wind Harmer
13.214
944581AF1-123 GEN
Solar/Wind Harmer
72.555
944601AF1-125 GEN
Solar/Wind Harmer
71.437
3144873MCLAUGH
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.307
971153AH1-033 GEN
Solar/Wind Harmer
3.547
316320Y1-086
Solar/Wind Harmer
0.002
3144536CHRHLND
Solar/Wind Harmer
0.044
316435W1029_GEN3
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.289
3146626S HERTFORD
Solar/Wind Harmer
0.285
3146376EDENTON
Solar/Wind Harmer
0.273
3145273HOLLAND
Solar/Wind Harmer
0.2
3145336SMITFLD
Solar/Wind Harmer
0.106
315614AA2-178 GEN
Solar/Wind Harmer
1.493
971157AH1-035 GEN
Solar/Wind Harmer
3.016
315737AD1-076 GEN
Solar/Wind Harmer
3.211
3146206CASHIE
Solar/Wind Harmer
0.242
3151221GRAVEL6
Adder
17.102
3151171GRAVELC
Adder
3.29
3156081AA2-088 GEN
Solar/Wind Harmer
0.006
3156021HOLLOMANSOL
Solar/Wind Harmer
1.055
3145893MURPHYS
Solar/Wind Harmer
0.385
3145893MURPHYS
Solar/Wind Harmer
0.23
957521AF2-046 GEN
Solar/Wind Harmer
17.097
961681AG1-008 GEN
Solar/Wind Harmer
17.097
3145963POPLR C
Solar/Wind Harmer
0.229
3146173TUNIS
Solar/Wind Harmer
0.228
316463AE2-346 GEN
Solar/Wind Harmer
0.195
316140AB2-099
Solar/Wind Harmer
0.081
962331AG1-082 GEN
Solar/Wind Harmer
2.424
3146263WOODLND
Solar/Wind Harmer
0.219
970661AG2-428 GEN
Solar/Wind Harmer
4.603
316317KELFORD C
Solar/Wind Harmer
0.021
3145823KELFORD
Solar/Wind Harmer
0.217
961611AG1-000B GEN
Solar/Wind Harmer
5.715
970917AG2-570 GEN
Solar/Wind Harmer
18.887
3145933PARMELE
Solar/Wind Harmer
0.211
966801AG1-551 GEN
Solar/Wind Harmer
2.459
3142666NORTHAMPTON
Solar/Wind Harmer
0.204
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
316210AC1-098 GEN
Solar/Wind Harmer
1.863
970659AG2-427 GEN
Solar/Wind Harmer
2.105
3145796HORNRTN
Solar/Wind Harmer
0.788
3145796HORNRTN
Solar/Wind Harmer
0.197
316365GEN2_N
Solar/Wind Harmer
0.441
313506AB2-031 GEN
Solar/Wind Harmer
0.607
316382AG1-145 C
Solar/Wind Harmer
0.002
316327AA2-057 GEN
Solar/Wind Harmer
0.286
3146073TAR RVR
Solar/Wind Harmer
0.188
3146083TARBORO
Solar/Wind Harmer
0.188
315724AD1-057 GEN
Solar/Wind Harmer
0.704
3146233WITAKRS
Solar/Wind Harmer
0.927
3146233WITAKRS
Solar/Wind Harmer
0.126
3138543CONSLDL
Solar/Wind Harmer
0.122
3147043LAWRENC
Solar/Wind Harmer
0.11
316478AD1-087 GEN
Solar/Wind Harmer
0.637
316486AD2-202 GEN
Solar/Wind Harmer
0.187
961601AG1-000A GEN
Solar/Wind Harmer
12.811
3145543BTLEBRO
Solar/Wind Harmer
0.18
3145543BTLEBRO
Solar/Wind Harmer
0.18
971623AH1-311 GEN
Solar/Wind Harmer
0.36
315813AE1-149 C
Solar/Wind Harmer
9.258
315778AD1-151 GEN
Solar/Wind Harmer
13.447
316131AB2-060 GEN
Solar/Wind Harmer
0.503
964241AG1-285 GEN
Solar/Wind Harmer
10.439
315785AD2-033 C
Solar/Wind Harmer
1.23
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
6.37
970257AG2-171 GEN
Solar/Wind Harmer
4.777
959311AF2-222 GEN
Solar/Wind Harmer
13.141
970129AG2-093 GEN
Solar/Wind Harmer
8.825
970909AG2-566 GEN
Solar/Wind Harmer
1.536
963181AG1-167 GEN
Solar/Wind Harmer
0.558
3144293JTRSVLE
Adder
0.444
316283AC2-100 C
Solar/Wind Harmer
0.27
3147133PAMPLIN
Solar/Wind Harmer
0.427
971193AH1-056 GEN
Solar/Wind Harmer
8.291
971683AH1-343 GEN
Solar/Wind Harmer
4.904
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
315839AE2-212 C
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
1.271
3146926FARMVIL
Solar/Wind Harmer
0.07
970133AG2-095 GEN
Solar/Wind Harmer
1.104
316156AD2-030 GEN
Solar/Wind Harmer
0.084
3141873WAN 176
Solar/Wind Harmer
2.026
3152331SURRY 2
50/50
16.971
3150981CHESPKA
50/50
4.092
970017AG2-010 GEN
50/50
18.077
316294AC1-161 GEN
Solar/Wind Harmer
6.269
944591AF1-124 GEN
Solar/Wind Harmer
72.813
316388AE2-253 GEN
Solar/Wind Harmer
0.968
316375AC2-012 GEN
Solar/Wind Harmer
0.008
3146456SLIGO L269
Solar/Wind Harmer
0.307
316246AF1-032 C
Solar/Wind Harmer
0.134
3146516WINFALL
Solar/Wind Harmer
0.937
3146516WINFALL
Solar/Wind Harmer
0.289
316072AD1-144
Solar/Wind Harmer
0.103
316093AE2-104_GEN
Solar/Wind Harmer
4.734
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
939411AE1-173 GEN
Solar/Wind Harmer
118.08
3130156CHOWAN
Solar/Wind Harmer
0.273
3138126ROCKLANDING
Solar/Wind Harmer
0.122
940641AE2-051 GEN
Solar/Wind Harmer
21.12
3145336SMITFLD
Solar/Wind Harmer
1.055
3145663CRESWEL
Solar/Wind Harmer
0.73
971163AH1-040 GEN
Solar/Wind Harmer
20.875
971317AH1-138 GEN
Solar/Wind Harmer
1.817
3146206CASHIE
Solar/Wind Harmer
0.242
971547AH1-271 GEN
Solar/Wind Harmer
5.174
3151171GRAVELC
Adder
2.502
3145893MURPHYS
Solar/Wind Harmer
0.921
3145893MURPHYS
Solar/Wind Harmer
1.024
3145963POPLR C
Solar/Wind Harmer
0.229
3146173TUNIS
Solar/Wind Harmer
0.228
3145683EARLEYS
Solar/Wind Harmer
0.226
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3146263WOODLND
Solar/Wind Harmer
0.219
970661AG2-428 GEN
Solar/Wind Harmer
21.643
3145823KELFORD
Solar/Wind Harmer
0.217
961611AG1-000B GEN
Solar/Wind Harmer
11.24
970919AG2-571 GEN
Solar/Wind Harmer
7.555
970087AG2-069 GEN
Solar/Wind Harmer
16.921
3146293MARTNCO
Solar/Wind Harmer
0.196
316190AA2-174 GEN
Solar/Wind Harmer
0
316381AD1-082 GEN
Solar/Wind Harmer
0.212
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
316212AC1-099_GEN
Solar/Wind Harmer
1.039
3145783HORNRTN
Solar/Wind Harmer
0.2
316011AB1-132 GEN
Solar/Wind Harmer
3.635
962571AG1-106 GEN
Solar/Wind Harmer
2.845
970659AG2-427 GEN
Solar/Wind Harmer
9.625
971647AH1-324 GEN
Solar/Wind Harmer
8.433
3145796HORNRTN
Solar/Wind Harmer
0.65
3145796HORNRTN
Solar/Wind Harmer
0.197
316023GEN1_S
Solar/Wind Harmer
0.441
316494AC1-189 GEN
Solar/Wind Harmer
0.659
960081AF2-299 GEN
Solar/Wind Harmer
1.849
957481AF2-042 GEN
Solar/Wind Harmer
51.23
970301AG2-198 GEN
Solar/Wind Harmer
6.144
958211AF2-115 GEN
Solar/Wind Harmer
1.674
963191AG1-168 GEN
Solar/Wind Harmer
0.558
3144293JTRSVLE
Adder
0.444
3144293JTRSVLE
Adder
0.374
316222AC1-221 GEN
Solar/Wind Harmer
0.577
3147133PAMPLIN
Solar/Wind Harmer
0.136
3147133PAMPLIN
Solar/Wind Harmer
0.109
316159AE1-175 C
Solar/Wind Harmer
0.164
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3146083TARBORO
Solar/Wind Harmer
0.188
3145493TOT1
Solar/Wind Harmer
0.837
315722AD1-056 GEN
Solar/Wind Harmer
1.187
971795AH1-408 GEN
Solar/Wind Harmer
12.398
3146233WITAKRS
Solar/Wind Harmer
0.735
3147043LAWRENC
Adder
1.655
315693AD1-088 GEN
Solar/Wind Harmer
8.716
316129AC1-054 GEN
Solar/Wind Harmer
0.682
3145543BTLEBRO
Solar/Wind Harmer
0.18
3145543BTLEBRO
Solar/Wind Harmer
0.144
316359AB2-059 GEN
Solar/Wind Harmer
0.647
316049AB1-081 GEN
Solar/Wind Harmer
1.03
3142053HEARTS
Solar/Wind Harmer
0.317
971065AG2-659 GEN
Solar/Wind Harmer
7.665
962491AG1-098 GEN
Solar/Wind Harmer
10.251
315687AD1-152 GEN
Solar/Wind Harmer
0.006
971069AG2-661 GEN
Solar/Wind Harmer
2.988
316237AB2-079_GEN
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
0.904
316458AB2-190 GEN2
Solar/Wind Harmer
0.8
970129AG2-093 GEN
Solar/Wind Harmer
4.153
970685AG2-442 GEN
Solar/Wind Harmer
10.77
316003AC1-222 GEN
Solar/Wind Harmer
0.004
963171AG1-166 GEN
Solar/Wind Harmer
0.744
971563AH1-280 GEN
Solar/Wind Harmer
1.488
3144293JTRSVLE
Adder
0.444
3146926FARMVIL
Solar/Wind Harmer
0.07
315671AE2-027_GEN
Solar/Wind Harmer
7.231
972263AH1-716 GEN
50/50
225.336
3151081ELIZAR1
50/50
30.232
3151091ELIZAR2
50/50
29.707
941591AE2-156 GEN
50/50
27.532
3152611GOSPORTB
50/50
4.172
3152621GOSPORTC
50/50
3.541
3152601GOSPORTA
50/50
3.266
3151151S HAMPT1
50/50
0.647
957871AF2-081 GEN
Solar/Wind Harmer
15.347
319010AE1-072 C
Solar/Wind Harmer
1.542
3146406KITTY HAWK
Solar/Wind Harmer
0.038
313526AB2-022
Solar/Wind Harmer
0.162
316305AF2-043 C
Solar/Wind Harmer
0.002
316321Z2-027
Solar/Wind Harmer
0.055
3146396TANGLEW
Solar/Wind Harmer
0.815
3145176PASQUOTANK
Solar/Wind Harmer
0.183
3146486SUNBURY
Solar/Wind Harmer
0.293
3146486SUNBURY
Solar/Wind Harmer
0.293
315835AF2-110_GEN
Solar/Wind Harmer
1.932
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3130156CHOWAN
Solar/Wind Harmer
0.273
3130156CHOWAN
Solar/Wind Harmer
0.273
971445AH1-216 GEN
Solar/Wind Harmer
18.391
315816AE2-034 GEN
Solar/Wind Harmer
1.12
316311AC2-079 GEN
Solar/Wind Harmer
7.239
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316349AD2-085 GEN
Solar/Wind Harmer
0.172
3130546PLYMOUTH
Solar/Wind Harmer
0.251
315732AD1-074 GEN1
Solar/Wind Harmer
1.434
315733AD1-074 GEN2
Solar/Wind Harmer
1.434
315735AD1-075 GEN1
Solar/Wind Harmer
0.718
3146206CASHIE
Solar/Wind Harmer
0.242
970601AG2-382 GEN
Solar/Wind Harmer
9.054
972265AH1-717 GEN
Adder
18.265
3151201GRAVEL4
Adder
17.122
3151191GRAVEL3
Adder
16.905
3151211GRAVEL5
Adder
16.905
965291AG1-394 GEN
Solar/Wind Harmer
1.033
941031AE2-094 GEN
Solar/Wind Harmer
42.726
944011AF1-069 GEN
Solar/Wind Harmer
13.96
3145893MURPHYS
Solar/Wind Harmer
0.622
3145893MURPHYS
Solar/Wind Harmer
0.23
3145513AHOSKIE
Solar/Wind Harmer
0.475
3145513AHOSKIE
Solar/Wind Harmer
0.227
970673AG2-436 GEN
Solar/Wind Harmer
48.437
970673AG2-436 GEN
Solar/Wind Harmer
32.291
3145683EARLEYS
Solar/Wind Harmer
0.452
3145683EARLEYS
Solar/Wind Harmer
0.226
3145683EARLEYS
Solar/Wind Harmer
0.226
971967AH1-528 GEN
Solar/Wind Harmer
35.521
3146043SEABORD
Solar/Wind Harmer
0.215
315607AA1-063A GEN
Solar/Wind Harmer
0.436
970085AG2-068 GEN
Solar/Wind Harmer
11.28
970581AG2-369 GEN
Solar/Wind Harmer
9.701
3146033SCOT NK
Solar/Wind Harmer
0.832
316005AA1-067
Solar/Wind Harmer
0.218
3145746EVERETS
Solar/Wind Harmer
0.807
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
3145746EVERETS
Solar/Wind Harmer
0.203
970181AG2-120 GEN
Solar/Wind Harmer
2.524
315652AC1-086 GEN
Solar/Wind Harmer
21.992
3137643SOCKMAN
Solar/Wind Harmer
0.794
3145796HORNRTN
Solar/Wind Harmer
0.63
3145796HORNRTN
Solar/Wind Harmer
0.079
316087AB2-174 GEN
Solar/Wind Harmer
0.006
957861AF2-080 GEN
Solar/Wind Harmer
8.409
3138283WHITEMARSH
Solar/Wind Harmer
0.045
315814AE2-033 C
Solar/Wind Harmer
15.324
316315AB2-025 C
Solar/Wind Harmer
0.156
316420AA1-050 GEN
Solar/Wind Harmer
0.006
3145573BETHELC
Solar/Wind Harmer
0.188
3145573BETHELC
Solar/Wind Harmer
0.188
316319Z2-044 C
Solar/Wind Harmer
0
970831AG2-522 GEN
Solar/Wind Harmer
7.82
316369SG1_INVT
Solar/Wind Harmer
0.007
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
3143316POE
Solar/Wind Harmer
0.633
316118AC1-105 GEN
Solar/Wind Harmer
0.391
971443AH1-215 GEN
Solar/Wind Harmer
2.515
3147173SINAI
Solar/Wind Harmer
0.149
3147243WELCO
Solar/Wind Harmer
0.093
3144303KENBRDG
Solar/Wind Harmer
0.119
316132AB2-190 GEN1
Solar/Wind Harmer
0.8
970683AG2-441 GEN
Solar/Wind Harmer
9.616
970681AG2-440 GEN
Solar/Wind Harmer
7.693
946301AF1-294 GEN
Solar/Wind Harmer
2.752
961791AG1-021 GEN
Solar/Wind Harmer
1.339
315657AE1-056 GEN
Solar/Wind Harmer
4.696
970865AG2-541 GEN
Solar/Wind Harmer
4.351
3141873WAN 176
Solar/Wind Harmer
0.023
NYPJM->LTFIMP_NY
CLTF
1.756
LAGNLTFEXP_LAGN->PJM
CLTF
6.396
LGEELTFEXP_LGEE->PJM
CLTF
0.899
WECLTFEXP_WEC->PJM
CLTF
0.455
CBM South 2LTFEXP_CBM-S2->PJM
CBM
22.437
TVALTFEXP_TVA->PJM
CLTF
3.182
CPLELTFEXP_CPLE->PJM
CLTF
10.802
CBM West 2LTFEXP_CBM-W2->PJM
CBM
31.909
CBM West 1LTFEXP_CBM-W1->PJM
CBM
15.352
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.682
MECLTFEXP_MEC->PJM
CLTF
2.665
SIGELTFEXP_SIGE->PJM
CLTF
0.078

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.1 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5539.41
MW Contribution:27.36
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
138.271
944011AF1-069 GEN
Solar/Wind Harmer
45.178
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
NYPJM->LTFIMP_NY
CLTF
2.382
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.36 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:6013.11
MW Contribution:36.03
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
941031AE2-094 GEN
Solar/Wind Harmer
158.157
944011AF1-069 GEN
Solar/Wind Harmer
49.556
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
970533AG2-339 GEN
50/50
66.733
970531AG2-338 GEN
50/50
26.693
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
NYPJM->LTFIMP_NY
CLTF
2.382
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
LGEELTFEXP_LGEE->PJM
CLTF
2.675
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.82 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5986.29
MW Contribution:35.79
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
941031AE2-094 GEN
Solar/Wind Harmer
157.012
944011AF1-069 GEN
Solar/Wind Harmer
49.197
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3151031BRUNSWICKG2
50/50
8.374
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
970533AG2-339 GEN
50/50
66.25
970531AG2-338 GEN
50/50
26.5
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.15 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5902.9
MW Contribution:35.49
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
941031AE2-094 GEN
Solar/Wind Harmer
155.676
944011AF1-069 GEN
Solar/Wind Harmer
48.778
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
970533AG2-339 GEN
50/50
65.686
970531AG2-338 GEN
50/50
26.274
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
NYPJM->LTFIMP_NY
CLTF
2.38
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for AE2-094 TP-8CARSON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 591_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AE2-094 TP-8CARSON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 591_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.48 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:4374.45
MW Contribution:32.94
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
23.093
963041AG1-153 GEN
50/50
20.853
941031AE2-094 GEN
Solar/Wind Harmer
160.06
944011AF1-069 GEN
Solar/Wind Harmer
52.298
970673AG2-436 GEN
Solar/Wind Harmer
176.854
970673AG2-436 GEN
Solar/Wind Harmer
117.903
970085AG2-068 GEN
Solar/Wind Harmer
38.301
970581AG2-369 GEN
Solar/Wind Harmer
32.939
3143316POE
Solar/Wind Helper
1.046
316369SG1_INVT
Solar/Wind Helper
1.16
316132AB2-190 GEN1
Solar/Wind Helper
1.367
957831AF2-077 GEN
Solar/Wind Helper
0.32
319010AE1-072 C
Solar/Wind Helper
2.682
316305AF2-043 C
Solar/Wind Helper
0.313
316349AD2-085 GEN
Solar/Wind Helper
1.054
957601AF2-054 GEN
Solar/Wind Helper
0.305
3141873WAN 176
Solar/Wind Helper
0.046
315662AE1-191 GEN
Solar/Wind Helper
1.221
315666AE1-190 GEN
Solar/Wind Helper
0.305
316059AD1-063 C
Solar/Wind Helper
0.228
3143873LANEXA
Solar/Wind Helper
0.136
3141913WHIT STONE
Solar/Wind Helper
0.226
3138133OCRAN
Solar/Wind Helper
0.068
3141783LANCAST
Solar/Wind Helper
0.134
3141783LANCAST
Solar/Wind Helper
0.09
315243AE2-183_GT3
50/50
13.357
3151051BRUNSWICKS1
50/50
21.374
3151021BRUNSWICKG1
50/50
10.298
971451AH1-221 GEN
50/50
31.279
971629AH1-314 GEN
50/50
11.732
970919AG2-571 GEN
Solar/Wind Harmer
25.761
970087AG2-069 GEN
Solar/Wind Harmer
57.452
316294AC1-161 GEN
Solar/Wind Helper
5.084
316375AC2-012 GEN
Solar/Wind Helper
0.669
3145336SMITFLD
Solar/Wind Helper
0.997
316381AD1-082 GEN
Solar/Wind Helper
1.253
316388AE2-253 GEN
Solar/Wind Helper
0.919
316458AB2-190 GEN2
Solar/Wind Helper
1.367
316159AE1-175 C
Solar/Wind Helper
0.363
3146456SLIGO L269
Solar/Wind Helper
0.236
316072AD1-144
Solar/Wind Helper
0.269
316246AF1-032 C
Solar/Wind Helper
0.266
3142433PROV 92
Solar/Wind Helper
0.908
3141766HARMONY
Solar/Wind Helper
0.045
3142543TWELFTH
Solar/Wind Helper
0.022
3138133OCRAN
Solar/Wind Helper
0.135
3151031BRUNSWICKG2
50/50
10.298
970917AG2-570 GEN
Solar/Wind Harmer
64.403
316283AC2-100 C
Solar/Wind Harmer
0.275
315773AC2-141 GEN
Solar/Wind Helper
5.984
3144873MCLAUGH
Solar/Wind Helper
0.006
3144536CHRHLND
Solar/Wind Helper
0.038
315839AE2-212 C
Solar/Wind Helper
0.339
3145336SMITFLD
Solar/Wind Helper
0.1
316382AG1-145 C
Solar/Wind Helper
0.322
3146456SLIGO L269
Solar/Wind Helper
0.236
316156AD2-030 GEN
Solar/Wind Helper
0.343
316280AD1-041 GEN
Solar/Wind Helper
0.763
3142946ENON
Solar/Wind Helper
0.075
970533AG2-339 GEN
50/50
77.249
970531AG2-338 GEN
50/50
30.9
315242AE2-183_GT2
50/50
13.357
315241AE2-183_GT1
50/50
13.275
972185AH1-677 GEN
50/50
48.153
3151041BRUNSWICKG3
50/50
10.298
972187AH1-678 GEN
50/50
23.633
316222AC1-221 GEN
Solar/Wind Harmer
0.574
316036AC1-147 C
Solar/Wind Helper
0.389
316316AC1-027 C
Solar/Wind Helper
0.399
3142956BIRDNECK
Solar/Wind Helper
0.17
316185AD1-033 GEN
Solar/Wind Helper
1.183
316236AE1-162_GEN
Solar/Wind Helper
0.335
3145506HICKORY
Solar/Wind Helper
0.991
3145506HICKORY
Solar/Wind Helper
0.595
3145506HICKORY
Solar/Wind Helper
0.149
316240AF1-291 C
Solar/Wind Helper
0.327
316033AB2-134 GEN
Solar/Wind Helper
0.83
315697AD1-025 GEN
Solar/Wind Helper
2.757
316339AD2-160 GEN
Solar/Wind Helper
0.919
316018AA1-139 ULT2
Solar/Wind Helper
1.03
316017AA1-139 ULT1
Solar/Wind Helper
1.094
3137176SLIGO L2192
Solar/Wind Helper
0.941
3130086AYDLETT
Solar/Wind Helper
0.934
3142946ENON
Solar/Wind Helper
0.023
NYPJM->LTFIMP_NY
CLTF
1.879
LAGNLTFEXP_LAGN->PJM
CLTF
11.955
LGEELTFEXP_LGEE->PJM
CLTF
2.007
WECLTFEXP_WEC->PJM
CLTF
1.057
CBM South 2LTFEXP_CBM-S2->PJM
CBM
37.412
TVALTFEXP_TVA->PJM
CLTF
5.929
CPLELTFEXP_CPLE->PJM
CLTF
16.699
CBM West 2LTFEXP_CBM-W2->PJM
CBM
62.441
CBM West 1LTFEXP_CBM-W1->PJM
CBM
37.352
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.231
MECLTFEXP_MEC->PJM
CLTF
5.698
SIGELTFEXP_SIGE->PJM
CLTF
0.168

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:176.17 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:985.35
MW Contribution:3.75
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.3
3151601KERR 3
50/50
0.315
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.233
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.302
3151021BRUNSWICKG1
50/50
1.109
971451AH1-221 GEN
50/50
3.369
315243AE2-183_GT3
50/50
1.358
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.938
971563AH1-280 GEN
Solar/Wind Harmer
3.876
970685AG2-442 GEN
Solar/Wind Harmer
24.484
962491AG1-098 GEN
Solar/Wind Harmer
11.925
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.548
970401AG2-262 GEN
Solar/Wind Harmer
0.937
957481AF2-042 GEN
Solar/Wind Harmer
40.4
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.702
316129AC1-054 GEN
Solar/Wind Harmer
0.489
971795AH1-408 GEN
Solar/Wind Harmer
7.855
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.916
970087AG2-069 GEN
Solar/Wind Harmer
6.541
316212AC1-099_GEN
Solar/Wind Harmer
0.387
3146263WOODLND
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.327
316023GEN1_S
Solar/Wind Harmer
0.164
962571AG1-106 GEN
Solar/Wind Harmer
1.039
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.286
3145893MURPHYS
Solar/Wind Harmer
0.283
3145893MURPHYS
Solar/Wind Harmer
0.314
315722AD1-056 GEN
Solar/Wind Harmer
0.447
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.251
316049AB1-081 GEN
Solar/Wind Harmer
0.4
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
940641AE2-051 GEN
Solar/Wind Harmer
5.396
316494AC1-189 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.923
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
971547AH1-271 GEN
Solar/Wind Harmer
1.316
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.641
316322AB2-045
Solar/Wind Helper
0.957
3146776BUCKING
Solar/Wind Helper
0.343
316336AC2-165 C
Solar/Wind Helper
1.513
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.4
3151591KERR 2
50/50
0.315
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.109
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.196
3147133PAMPLIN
Solar/Wind Harmer
1.218
971193AH1-056 GEN
Solar/Wind Harmer
23.635
963181AG1-167 GEN
Solar/Wind Harmer
1.454
959311AF2-222 GEN
Solar/Wind Harmer
26.76
970257AG2-171 GEN
Solar/Wind Harmer
9.287
315785AD2-033 C
Solar/Wind Harmer
2.238
964241AG1-285 GEN
Solar/Wind Harmer
15.712
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.403
971683AH1-343 GEN
Solar/Wind Harmer
4.014
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.162
970917AG2-570 GEN
Solar/Wind Harmer
7.29
316210AC1-098 GEN
Solar/Wind Harmer
0.693
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.074
316365GEN2_N
Solar/Wind Harmer
0.164
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.361
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.265
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.233
961681AG1-008 GEN
Solar/Wind Harmer
5.233
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.14
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.909
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.733
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3156021HOLLOMANSOL
Solar/Wind Harmer
0.291
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.744
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
315737AD1-076 GEN
Solar/Wind Harmer
0.772
971157AH1-035 GEN
Solar/Wind Harmer
0.716
315614AA2-178 GEN
Solar/Wind Harmer
0.332
3145273HOLLAND
Solar/Wind Harmer
0.043
3146776BUCKING
Solar/Wind Helper
0.309
316313AB2-026
Solar/Wind Helper
0.361
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.034
970535AG2-341 GEN
50/50
3.152
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.109
972187AH1-678 GEN
50/50
2.545
315242AE2-183_GT2
50/50
1.358
315241AE2-183_GT1
50/50
1.35
972185AH1-677 GEN
50/50
4.896
970533AG2-339 GEN
50/50
6.901
970531AG2-338 GEN
50/50
2.76
3151361ROSEMG1
50/50
0.261
3151371ROSEMS1
50/50
0.162
3151381ROSEMG2
50/50
0.122
970301AG2-198 GEN
Solar/Wind Harmer
16.784
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.361
963191AG1-168 GEN
Solar/Wind Harmer
1.454
971741AH1-377 GEN
Solar/Wind Harmer
34.597
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.383
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
8.006
939181AE1-148 GEN
Solar/Wind Harmer
7.768
964791AG1-342 GEN
Solar/Wind Harmer
3.068
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.16
970933AG2-581 GEN
Solar/Wind Harmer
8.957
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.539
3145783HORNRTN
Solar/Wind Harmer
1.231
3145783HORNRTN
Solar/Wind Harmer
0.385
3145783HORNRTN
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.286
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.402
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
942751AE2-291 GEN
Solar/Wind Harmer
3.947
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.473
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.657
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.227
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.517
316065AD1-022 GEN
Solar/Wind Harmer
2.811
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
3.433
3146776BUCKING
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.985
3151541CLOVER2
50/50
3.284
3151611KERR 4
50/50
0.315
3151621KERR 5
50/50
0.315
3151631KERR 6
50/50
0.315
3151641KERR 7
50/50
0.315
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.246
315244AE2-183_ST
50/50
2.348
970285AG2-188 GEN
Solar/Wind Harmer
51.681
315657AE1-056 GEN
Solar/Wind Harmer
13.387
946301AF1-294 GEN
Solar/Wind Harmer
7.171
961791AG1-021 GEN
Solar/Wind Harmer
3.489
970683AG2-441 GEN
Solar/Wind Harmer
21.861
970681AG2-440 GEN
Solar/Wind Harmer
17.489
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.821
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.369
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.372
970865AG2-541 GEN
Solar/Wind Harmer
3.489
971967AH1-528 GEN
Solar/Wind Harmer
15.071
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.359
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.361
970581AG2-369 GEN
Solar/Wind Harmer
3.75
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.208
970673AG2-436 GEN
Solar/Wind Harmer
11.472
941031AE2-094 GEN
Solar/Wind Harmer
14.299
944011AF1-069 GEN
Solar/Wind Harmer
4.672
315652AC1-086 GEN
Solar/Wind Harmer
8.029
3146033SCOT NK
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.32
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.191
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.144
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.854
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
970181AG2-120 GEN
Solar/Wind Harmer
0.805
315814AE2-033 C
Solar/Wind Harmer
4.945
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.062
970601AG2-382 GEN
Solar/Wind Harmer
2.302
315732AD1-074 GEN1
Solar/Wind Harmer
0.345
315733AD1-074 GEN2
Solar/Wind Harmer
0.345
315735AD1-075 GEN1
Solar/Wind Harmer
0.173
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
0.249
270494AE1-108_GEN
Solar/Wind Helper
4.45
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
316258AE1-075 C
Solar/Wind Helper
0.325
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
NYPJM->LTFIMP_NY
CLTF
0.48
LGEELTFEXP_LGEE->PJM
CLTF
0.362
LAGNLTFEXP_LAGN->PJM
CLTF
2.753
WECLTFEXP_WEC->PJM
CLTF
0.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.143
TVALTFEXP_TVA->PJM
CLTF
1.358
CPLELTFEXP_CPLE->PJM
CLTF
4.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.539
MECLTFEXP_MEC->PJM
CLTF
1.12
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.06 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:875.95
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
NYPJM->LTFIMP_NY
CLTF
0.295
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
LGEELTFEXP_LGEE->PJM
CLTF
0.219
WECLTFEXP_WEC->PJM
CLTF
0.123
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
TVALTFEXP_TVA->PJM
CLTF
1.216
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.48 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:851.47
MW Contribution:3.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
970285AG2-188 GEN
Solar/Wind Harmer
63.671
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
WECLTFEXP_WEC->PJM
CLTF
0.133
TVALTFEXP_TVA->PJM
CLTF
1.025
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 249-69_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 249-69_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:120.19 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:822.07
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.282
3151621KERR 5
50/50
0.282
3151631KERR 6
50/50
0.282
3151641KERR 7
50/50
0.282
3151541CLOVER2
50/50
2.882
970285AG2-188 GEN
Solar/Wind Harmer
63.644
315657AE1-056 GEN
Solar/Wind Harmer
15.869
946301AF1-294 GEN
Solar/Wind Harmer
10.118
961791AG1-021 GEN
Solar/Wind Harmer
4.936
970683AG2-441 GEN
Solar/Wind Harmer
27.679
970681AG2-440 GEN
Solar/Wind Harmer
22.144
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.054
316239AB2-077_GEN
Solar/Wind Harmer
0.629
316238AB2-078_GEN
Solar/Wind Harmer
0.629
316118AC1-105 GEN
Solar/Wind Harmer
0.99
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.188
970865AG2-541 GEN
Solar/Wind Harmer
4.016
946281AF1-292 GEN
Solar/Wind Harmer
0.2
316087AB2-174 GEN
Solar/Wind Harmer
1.235
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316123AC1-075 GEN
Solar/Wind Harmer
0.876
970165AG2-112 GEN
Solar/Wind Harmer
0.771
970163AG2-111 GEN
Solar/Wind Harmer
0.736
971967AH1-528 GEN
Solar/Wind Harmer
14.788
315607AA1-063A GEN
Solar/Wind Harmer
0.747
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.132
970581AG2-369 GEN
Solar/Wind Harmer
3.554
315652AC1-086 GEN
Solar/Wind Harmer
7.265
3146033SCOT NK
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
316319Z2-044 C
Solar/Wind Harmer
0.352
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.187
3151601KERR 3
50/50
0.282
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.896
3147043LAWRENC
50/50
1.087
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.936
971563AH1-280 GEN
Solar/Wind Harmer
4.936
970685AG2-442 GEN
Solar/Wind Harmer
31.001
962491AG1-098 GEN
Solar/Wind Harmer
14.334
316237AB2-079_GEN
Solar/Wind Harmer
0.629
315693AD1-088 GEN
Solar/Wind Harmer
10.136
970401AG2-262 GEN
Solar/Wind Harmer
1.063
957481AF2-042 GEN
Solar/Wind Harmer
46.146
315687AD1-152 GEN
Solar/Wind Harmer
1.644
971065AG2-659 GEN
Solar/Wind Harmer
6.622
316129AC1-054 GEN
Solar/Wind Harmer
1.124
316003AC1-222 GEN
Solar/Wind Harmer
1.132
971795AH1-408 GEN
Solar/Wind Harmer
8.642
960081AF2-299 GEN
Solar/Wind Harmer
1.002
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
316212AC1-099_GEN
Solar/Wind Harmer
0.579
970919AG2-571 GEN
Solar/Wind Harmer
2.097
970087AG2-069 GEN
Solar/Wind Harmer
6.198
316023GEN1_S
Solar/Wind Harmer
0.436
3146263WOODLND
Solar/Wind Harmer
-0.006
316011AB1-132 GEN
Solar/Wind Harmer
1.351
962571AG1-106 GEN
Solar/Wind Harmer
0.928
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.451
3144293JTRSVLE
50/50
1.187
3151591KERR 2
50/50
0.282
970413AG2-270 GEN
50/50
12.638
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.566
970909AG2-566 GEN
Solar/Wind Harmer
4.057
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.448
963181AG1-167 GEN
Solar/Wind Harmer
3.702
959311AF2-222 GEN
Solar/Wind Harmer
33.775
970257AG2-171 GEN
Solar/Wind Harmer
11.671
315785AD2-033 C
Solar/Wind Harmer
6.667
964241AG1-285 GEN
Solar/Wind Harmer
19.444
316131AB2-060 GEN
Solar/Wind Harmer
2.388
316478AD1-087 GEN
Solar/Wind Harmer
1.315
316486AD2-202 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.378
960061AF2-297 GEN
Solar/Wind Harmer
6.277
971683AH1-343 GEN
Solar/Wind Harmer
4.637
966621AG1-532 GEN
Solar/Wind Harmer
0.181
313506AB2-031 GEN
Solar/Wind Harmer
0.687
316283AC2-100 C
Solar/Wind Harmer
0.728
316210AC1-098 GEN
Solar/Wind Harmer
1.043
970917AG2-570 GEN
Solar/Wind Harmer
16.563
316327AA2-057 GEN
Solar/Wind Harmer
0.663
316365GEN2_N
Solar/Wind Harmer
0.436
3146263WOODLND
Solar/Wind Harmer
-0.006
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.34
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.187
3144293JTRSVLE
50/50
1
970535AG2-341 GEN
50/50
2.881
3152661PLYWOOD A
50/50
0.273
970301AG2-198 GEN
Solar/Wind Harmer
21.369
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.17
963191AG1-168 GEN
Solar/Wind Harmer
3.702
971741AH1-377 GEN
Solar/Wind Harmer
43.69
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.561
971775AH1-396 GEN
Solar/Wind Harmer
2.216
313527AB2-043 GEN
Solar/Wind Harmer
3.487
962561AG1-105 GEN
Solar/Wind Harmer
9.606
939181AE1-148 GEN
Solar/Wind Harmer
9.243
964791AG1-342 GEN
Solar/Wind Harmer
3.479
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.458
970933AG2-581 GEN
Solar/Wind Harmer
9.37
316181AB2-040 GEN
Solar/Wind Harmer
1.193
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.917
3145593CAROLNA
Solar/Wind Harmer
0.068
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.756
3145783HORNRTN
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
0.094
316222AC1-221 GEN
Solar/Wind Harmer
0.793
316426AA2-053 GEN
Solar/Wind Harmer
0.781
942751AE2-291 GEN
Solar/Wind Harmer
4.462
316274AC1-208 GEN
Solar/Wind Harmer
0.751
972187AH1-678 GEN
Adder
1.711
972185AH1-677 GEN
Adder
3.235
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.472
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.98
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.244
LAGNLTFEXP_LAGN->PJM
CLTF
2.044
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.87
WECLTFEXP_WEC->PJM
CLTF
0.129
TVALTFEXP_TVA->PJM
CLTF
1.005
CPLELTFEXP_CPLE->PJM
CLTF
3.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.9
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.333
MECLTFEXP_MEC->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:115.8 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:792.06
MW Contribution:3.47
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.444
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
WECLTFEXP_WEC->PJM
CLTF
0.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.37 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:617.32
MW Contribution:2.61
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
NYPJM->LTFIMP_NY
CLTF
0.298
LGEELTFEXP_LGEE->PJM
CLTF
0.232
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
WECLTFEXP_WEC->PJM
CLTF
0.123
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 511_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 511_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.2 %
Rating:4070.2 MVA
Rating Type:B
MVA to Mitigate:5258.72
MW Contribution:27.36
Bus #Bus NameTypeMW Contribution
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
47.73
957481AF2-042 GEN
Solar/Wind Harmer
126.807
315693AD1-088 GEN
Solar/Wind Harmer
20.818
962491AG1-098 GEN
Solar/Wind Harmer
24.385
315687AD1-152 GEN
Solar/Wind Harmer
0.013
316003AC1-222 GEN
Solar/Wind Harmer
0.008
970401AG2-262 GEN
Solar/Wind Harmer
1.677
316237AB2-079_GEN
Solar/Wind Harmer
0.002
970685AG2-442 GEN
Solar/Wind Harmer
17.979
963171AG1-166 GEN
Solar/Wind Harmer
1.264
971563AH1-280 GEN
Solar/Wind Harmer
2.529
3146926FARMVIL
Solar/Wind Harmer
0.131
971065AG2-659 GEN
Solar/Wind Harmer
8.445
316129AC1-054 GEN
Solar/Wind Harmer
0.698
970223AG2-152 GEN
Solar/Wind Harmer
12.094
270016AE1-250 BESS
Solar/Wind Harmer
0.005
3147123OTTER R
Solar/Wind Harmer
0.088
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
316322AB2-045
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Harmer
0.055
3147312GRETNA
Solar/Wind Harmer
0.105
3146802CHATHAM
Solar/Wind Harmer
0.099
941801AE2-185 GEN
Solar/Wind Harmer
4.212
270030AE2-140 GEN
Solar/Wind Harmer
13.804
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0.421
316049AB1-081 GEN
Solar/Wind Harmer
0.67
3142053HEARTS
Solar/Wind Harmer
0.206
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
53.421
316478AD1-087 GEN
Solar/Wind Harmer
1.525
316486AD2-202 GEN
Solar/Wind Harmer
0.448
970909AG2-566 GEN
Solar/Wind Harmer
3.307
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
149.315
970673AG2-436 GEN
Solar/Wind Harmer
99.544
971967AH1-528 GEN
Solar/Wind Harmer
95.481
970085AG2-068 GEN
Solar/Wind Harmer
31.82
970581AG2-369 GEN
Solar/Wind Harmer
27.365
3147173SINAI
Solar/Wind Harmer
0.309
3147243WELCO
Solar/Wind Harmer
0.193
316118AC1-105 GEN
Solar/Wind Harmer
0.768
970865AG2-541 GEN
Solar/Wind Harmer
9.078
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
971443AH1-215 GEN
Solar/Wind Harmer
4.118
3144303KENBRDG
Solar/Wind Harmer
0.196
970683AG2-441 GEN
Solar/Wind Harmer
16.053
970681AG2-440 GEN
Solar/Wind Harmer
12.842
946301AF1-294 GEN
Solar/Wind Harmer
4.678
961791AG1-021 GEN
Solar/Wind Harmer
2.276
315657AE1-056 GEN
Solar/Wind Harmer
8.085
316123AC1-075 GEN
Solar/Wind Harmer
0.315
970165AG2-112 GEN
Solar/Wind Harmer
1.87
970163AG2-111 GEN
Solar/Wind Harmer
1.784
970831AG2-522 GEN
Solar/Wind Harmer
7.35
970285AG2-188 GEN
Solar/Wind Harmer
12.402
971845AH1-439 GEN
Solar/Wind Harmer
6.507
270069AE2-166 C O1
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
316248AF1-058 C
Solar/Wind Harmer
0.002
960061AF2-297 GEN
Solar/Wind Harmer
13.182
316283AC2-100 C
Solar/Wind Harmer
0.55
971683AH1-343 GEN
Solar/Wind Harmer
10.2
316131AB2-060 GEN
Solar/Wind Harmer
0.796
964241AG1-285 GEN
Solar/Wind Harmer
16.703
315785AD2-033 C
Solar/Wind Harmer
2.003
970257AG2-171 GEN
Solar/Wind Harmer
7.834
959311AF2-222 GEN
Solar/Wind Harmer
21.656
963181AG1-167 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.736
971193AH1-056 GEN
Solar/Wind Harmer
14.274
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
3146926FARMVIL
Solar/Wind Harmer
0.131
270018AE2-047 C O1
Solar/Wind Harmer
0.003
270197AD1-017 GEN1
Solar/Wind Harmer
0.943
3146776BUCKING
Solar/Wind Harmer
0.049
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
3147312GRETNA
Solar/Wind Harmer
0.026
941821AE2-187 GEN
Solar/Wind Harmer
4.212
270336AE1-100 GEN
Solar/Wind Harmer
0.003
3145543BTLEBRO
Solar/Wind Harmer
0.117
3145543BTLEBRO
Solar/Wind Harmer
0.117
971623AH1-311 GEN
Solar/Wind Harmer
0.234
961601AG1-000A GEN
Solar/Wind Harmer
8.141
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
44.982
970099AG2-077 GEN
Solar/Wind Harmer
50.723
971741AH1-377 GEN
Solar/Wind Harmer
33.569
970301AG2-198 GEN
Solar/Wind Harmer
13.228
3146843MT LREL
Solar/Wind Harmer
0.286
3146843MT LREL
Solar/Wind Harmer
0.286
964791AG1-342 GEN
Solar/Wind Harmer
5.488
316222AC1-221 GEN
Solar/Wind Harmer
1.175
962561AG1-105 GEN
Solar/Wind Harmer
13.485
939181AE1-148 GEN
Solar/Wind Harmer
12.41
313527AB2-043 GEN
Solar/Wind Harmer
0.003
970323AG2-213 GEN
Solar/Wind Harmer
10.445
971775AH1-396 GEN
Solar/Wind Harmer
0.392
316034AC1-036 C
Solar/Wind Harmer
0.018
958211AF2-115 GEN
Solar/Wind Harmer
2.845
963191AG1-168 GEN
Solar/Wind Harmer
0.948
3147133PAMPLIN
Solar/Wind Harmer
0.234
3147133PAMPLIN
Solar/Wind Harmer
0.187
942751AE2-291 GEN
Solar/Wind Harmer
11.476
270013AE1-250 PV
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.546
3146776BUCKING
Solar/Wind Harmer
0.044
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.001
942671AE2-283 GEN
Solar/Wind Harmer
3.276
316263AC1-034 GEN
Solar/Wind Harmer
4.449
961601AG1-000A GEN
Solar/Wind Harmer
2.035
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51192_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51192_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.25 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5708.12
MW Contribution:36.03
Bus #Bus NameTypeMW Contribution
315242AE2-183_GT2
50/50
11.133
315241AE2-183_GT1
50/50
11.065
972185AH1-677 GEN
50/50
40.137
3151041BRUNSWICKG3
50/50
8.432
972187AH1-678 GEN
50/50
19.349
3152661PLYWOOD A
50/50
0.671
970535AG2-341 GEN
50/50
4.566
3144293JTRSVLE
50/50
0.801
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
59.226
970099AG2-077 GEN
Solar/Wind Harmer
66.785
971741AH1-377 GEN
Solar/Wind Harmer
44.199
970301AG2-198 GEN
Solar/Wind Harmer
17.416
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.86
316222AC1-221 GEN
Solar/Wind Harmer
3.218
962561AG1-105 GEN
Solar/Wind Harmer
17.755
939181AE1-148 GEN
Solar/Wind Harmer
16.34
313527AB2-043 GEN
Solar/Wind Harmer
4.631
970323AG2-213 GEN
Solar/Wind Harmer
13.752
971775AH1-396 GEN
Solar/Wind Harmer
1.958
316034AC1-036 C
Solar/Wind Harmer
0.51
958211AF2-115 GEN
Solar/Wind Harmer
4.162
963191AG1-168 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.11
270013AE1-250 PV
Solar/Wind Harmer
2.846
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.4
316197AC1-042 GEN
Solar/Wind Harmer
1.819
942671AE2-283 GEN
Solar/Wind Harmer
4.898
316263AC1-034 GEN
Solar/Wind Harmer
6.166
961601AG1-000A GEN
Solar/Wind Harmer
5.056
316036AC1-147 C
Solar/Wind Helper
0.586
3142956BIRDNECK
Solar/Wind Helper
0.257
316316AC1-027 C
Solar/Wind Helper
0.602
316185AD1-033 GEN
Solar/Wind Helper
1.787
3145506HICKORY
Solar/Wind Helper
1.497
3145506HICKORY
Solar/Wind Helper
0.899
3145506HICKORY
Solar/Wind Helper
0.225
316236AE1-162_GEN
Solar/Wind Helper
0.5
316339AD2-160 GEN
Solar/Wind Helper
1.389
316018AA1-139 ULT2
Solar/Wind Helper
1.557
316017AA1-139 ULT1
Solar/Wind Helper
1.655
3137176SLIGO L2192
Solar/Wind Helper
1.424
316033AB2-134 GEN
Solar/Wind Helper
1.217
315697AD1-025 GEN
Solar/Wind Helper
4.045
3130086AYDLETT
Solar/Wind Helper
1.414
315244AE2-183_ST
50/50
19.249
963041AG1-153 GEN
50/50
17.073
3151541CLOVER2
50/50
9.317
3151611KERR 4
50/50
0.537
3151621KERR 5
50/50
0.537
3151631KERR 6
50/50
0.537
3151641KERR 7
50/50
0.537
970673AG2-436 GEN
Solar/Wind Harmer
165.209
970673AG2-436 GEN
Solar/Wind Harmer
83.65
971967AH1-528 GEN
Solar/Wind Harmer
126.052
970085AG2-068 GEN
Solar/Wind Harmer
41.896
970581AG2-369 GEN
Solar/Wind Harmer
36.031
3147173SINAI
Solar/Wind Harmer
-0.035
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.3
970865AG2-541 GEN
Solar/Wind Harmer
11.953
316239AB2-077_GEN
Solar/Wind Harmer
0.866
316238AB2-078_GEN
Solar/Wind Harmer
0.866
971443AH1-215 GEN
Solar/Wind Harmer
5.422
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.136
970681AG2-440 GEN
Solar/Wind Harmer
16.909
946301AF1-294 GEN
Solar/Wind Harmer
6.825
961791AG1-021 GEN
Solar/Wind Harmer
3.329
270455AD2-022 GEN
Solar/Wind Harmer
4.714
270457AD2-023 GEN
Solar/Wind Harmer
2.39
315657AE1-056 GEN
Solar/Wind Harmer
9.877
316123AC1-075 GEN
Solar/Wind Harmer
2.797
970165AG2-112 GEN
Solar/Wind Harmer
2.462
970163AG2-111 GEN
Solar/Wind Harmer
2.349
970831AG2-522 GEN
Solar/Wind Harmer
9.678
970285AG2-188 GEN
Solar/Wind Harmer
15.412
971845AH1-439 GEN
Solar/Wind Harmer
8.567
270069AE2-166 C O1
Solar/Wind Harmer
2.422
3143316POE
Solar/Wind Helper
1.55
319010AE1-072 C
Solar/Wind Helper
4.057
316369SG1_INVT
Solar/Wind Helper
1.702
316305AF2-043 C
Solar/Wind Helper
0.471
316132AB2-190 GEN1
Solar/Wind Helper
1.993
957831AF2-077 GEN
Solar/Wind Helper
0.468
316349AD2-085 GEN
Solar/Wind Helper
1.559
313526AB2-022
Solar/Wind Helper
0.503
957601AF2-054 GEN
Solar/Wind Helper
0.442
3141873WAN 176
Solar/Wind Helper
0.066
315662AE1-191 GEN
Solar/Wind Helper
1.766
315666AE1-190 GEN
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.329
3141913WHIT STONE
Solar/Wind Helper
0.326
3138133OCRAN
Solar/Wind Helper
0.098
3143873LANEXA
Solar/Wind Helper
0.195
3141783LANCAST
Solar/Wind Helper
0.194
3141783LANCAST
Solar/Wind Helper
0.129
3146486SUNBURY
Solar/Wind Helper
0.322
3146486SUNBURY
Solar/Wind Helper
0.322
316321Z2-027
Solar/Wind Helper
0.485
3145176PASQUOTANK
Solar/Wind Helper
0.197
316315AB2-025 C
Solar/Wind Helper
0.48
3141813NORNECK
Solar/Wind Helper
0.308
316312AB1-027
Solar/Wind Helper
0.567
316233AE1-074 FULL
Solar/Wind Helper
0.447
316223AC1-118
Solar/Wind Helper
0.442
315611Z1-036_GEN2
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
3130156CHOWAN
Solar/Wind Helper
0.227
3151031BRUNSWICKG2
50/50
8.432
970413AG2-270 GEN
50/50
40.853
3151591KERR 2
50/50
0.537
3144293JTRSVLE
50/50
0.801
970917AG2-570 GEN
Solar/Wind Harmer
168.81
316478AD1-087 GEN
Solar/Wind Harmer
4.25
316486AD2-202 GEN
Solar/Wind Harmer
1.245
970909AG2-566 GEN
Solar/Wind Harmer
3.307
316248AF1-058 C
Solar/Wind Harmer
1.046
960061AF2-297 GEN
Solar/Wind Harmer
17.357
316283AC2-100 C
Solar/Wind Harmer
2.974
971683AH1-343 GEN
Solar/Wind Harmer
13.43
316131AB2-060 GEN
Solar/Wind Harmer
3.068
964241AG1-285 GEN
Solar/Wind Harmer
21.992
315785AD2-033 C
Solar/Wind Harmer
6.274
970257AG2-171 GEN
Solar/Wind Harmer
10.314
959311AF2-222 GEN
Solar/Wind Harmer
28.571
963181AG1-167 GEN
Solar/Wind Harmer
2.497
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.462
942461AE2-259 GEN
Solar/Wind Harmer
3.832
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.378
270197AD1-017 GEN1
Solar/Wind Harmer
1.68
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.844
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.545
270336AE1-100 GEN
Solar/Wind Harmer
1.569
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
961601AG1-000A GEN
Solar/Wind Harmer
5.12
315773AC2-141 GEN
Solar/Wind Helper
9.054
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.057
3145336SMITFLD
Solar/Wind Helper
0.149
315839AE2-212 C
Solar/Wind Helper
0.495
3146456SLIGO L269
Solar/Wind Helper
0.357
316382AG1-145 C
Solar/Wind Helper
0.471
316320Y1-086
Solar/Wind Helper
0.147
316156AD2-030 GEN
Solar/Wind Helper
0.497
316280AD1-041 GEN
Solar/Wind Helper
1.104
3142946ENON
Solar/Wind Helper
0.108
316484AD2-074 GEN
Solar/Wind Helper
0.613
316404AE1-155 C
Solar/Wind Helper
2.651
316435W1029_GEN3
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3141906WESTMOR
Solar/Wind Helper
0.116
316473AC1-191 GEN
Solar/Wind Helper
1.736
3146626S HERTFORD
Solar/Wind Helper
0.28
3145273HOLLAND
Solar/Wind Helper
0.191
966881AG1-559 GEN
Solar/Wind Helper
0.333
3146376EDENTON
Solar/Wind Helper
0.227
315243AE2-183_GT3
50/50
11.133
3151051BRUNSWICKS1
50/50
17.499
3151021BRUNSWICKG1
50/50
8.432
971451AH1-221 GEN
50/50
25.609
3151531CLOVER1
50/50
9.362
3151601KERR 3
50/50
0.537
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.801
971629AH1-314 GEN
50/50
17.923
3151561HALLBR1
50/50
0.367
970919AG2-571 GEN
Solar/Wind Harmer
21.368
970087AG2-069 GEN
Solar/Wind Harmer
62.844
957481AF2-042 GEN
Solar/Wind Harmer
166.962
315693AD1-088 GEN
Solar/Wind Harmer
24.364
962491AG1-098 GEN
Solar/Wind Harmer
32.107
315687AD1-152 GEN
Solar/Wind Harmer
5.339
316003AC1-222 GEN
Solar/Wind Harmer
3.203
970401AG2-262 GEN
Solar/Wind Harmer
2.096
316237AB2-079_GEN
Solar/Wind Harmer
0.866
970685AG2-442 GEN
Solar/Wind Harmer
23.673
963171AG1-166 GEN
Solar/Wind Harmer
3.329
971563AH1-280 GEN
Solar/Wind Harmer
3.329
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.119
316129AC1-054 GEN
Solar/Wind Harmer
1.828
970223AG2-152 GEN
Solar/Wind Harmer
17.247
270016AE1-250 BESS
Solar/Wind Harmer
2.846
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.591
316322AB2-045
Solar/Wind Harmer
0.516
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.545
270030AE2-140 GEN
Solar/Wind Harmer
19.786
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.774
316049AB1-081 GEN
Solar/Wind Harmer
1.419
3142053HEARTS
Solar/Wind Harmer
0.155
316294AC1-161 GEN
Solar/Wind Helper
7.693
316375AC2-012 GEN
Solar/Wind Helper
1.008
3145336SMITFLD
Solar/Wind Helper
1.487
316388AE2-253 GEN
Solar/Wind Helper
1.389
3146456SLIGO L269
Solar/Wind Helper
0.357
316381AD1-082 GEN
Solar/Wind Helper
1.848
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.401
316159AE1-175 C
Solar/Wind Helper
0.531
316458AB2-190 GEN2
Solar/Wind Helper
1.993
3141766HARMONY
Solar/Wind Helper
0.065
3142433PROV 92
Solar/Wind Helper
1.303
3138133OCRAN
Solar/Wind Helper
0.195
3142543TWELFTH
Solar/Wind Helper
0.03
964211AG1-282 GEN
Solar/Wind Helper
0.416
3141726DUNNSVL
Solar/Wind Helper
1.235
316337AD2-073 GEN
Solar/Wind Helper
0.453
3142416OLDCHRC
Solar/Wind Helper
0.774
3142416OLDCHRC
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.959
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
3143226MDLTHAN
Solar/Wind Helper
0.286
315800Z1-036_GEN1
Solar/Wind Helper
1.413
3130156CHOWAN
Solar/Wind Helper
0.227
316240AF1-291 C
Solar/Wind Helper
0.474
3146386ELIZ CT
Solar/Wind Helper
0.33
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.321
3144356SAPONY
Solar/Wind Helper
0.565
316075AC2-137 C
Solar/Wind Helper
0.475
316077AC2-138 C
Solar/Wind Helper
0.289
316431W1029_GEN1
Solar/Wind Helper
1.222
316433W1029_GEN2
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3146516WINFALL
Solar/Wind Helper
0.296
3143526WINTERP
Solar/Wind Helper
1.52
966871AG1-558 GEN
Solar/Wind Helper
0.383
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
316468AD1-105 GEN
Solar/Wind Helper
1.331
NYPJM->LTFIMP_NY
CLTF
2.382
LGEELTFEXP_LGEE->PJM
CLTF
2.675
LAGNLTFEXP_LAGN->PJM
CLTF
14.669
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.275
WECLTFEXP_WEC->PJM
CLTF
1.4
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
TVALTFEXP_TVA->PJM
CLTF
7.315
CPLELTFEXP_CPLE->PJM
CLTF
19.748
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.24
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.156
MECLTFEXP_MEC->PJM
CLTF
7.366
SIGELTFEXP_SIGE->PJM
CLTF
0.221

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 51172_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 51172_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5683.44
MW Contribution:35.79
Bus #Bus NameTypeMW Contribution
3151031BRUNSWICKG2
50/50
8.374
315244AE2-183_ST
50/50
19.115
963041AG1-153 GEN
50/50
16.957
3151541CLOVER2
50/50
9.268
3151611KERR 4
50/50
0.538
3151621KERR 5
50/50
0.538
3151631KERR 6
50/50
0.538
3151641KERR 7
50/50
0.538
970673AG2-436 GEN
Solar/Wind Harmer
164.043
970673AG2-436 GEN
Solar/Wind Harmer
83.06
971967AH1-528 GEN
Solar/Wind Harmer
125.223
970085AG2-068 GEN
Solar/Wind Harmer
41.62
970581AG2-369 GEN
Solar/Wind Harmer
35.794
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.295
970865AG2-541 GEN
Solar/Wind Harmer
11.917
316239AB2-077_GEN
Solar/Wind Harmer
0.868
316238AB2-078_GEN
Solar/Wind Harmer
0.868
971443AH1-215 GEN
Solar/Wind Harmer
5.428
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
21.145
970681AG2-440 GEN
Solar/Wind Harmer
16.916
946301AF1-294 GEN
Solar/Wind Harmer
6.823
961791AG1-021 GEN
Solar/Wind Harmer
3.328
270455AD2-022 GEN
Solar/Wind Harmer
4.701
270457AD2-023 GEN
Solar/Wind Harmer
2.384
315657AE1-056 GEN
Solar/Wind Harmer
9.869
316123AC1-075 GEN
Solar/Wind Harmer
2.789
970165AG2-112 GEN
Solar/Wind Harmer
2.455
970163AG2-111 GEN
Solar/Wind Harmer
2.342
970831AG2-522 GEN
Solar/Wind Harmer
9.813
970285AG2-188 GEN
Solar/Wind Harmer
15.354
971845AH1-439 GEN
Solar/Wind Harmer
8.535
270069AE2-166 C O1
Solar/Wind Harmer
2.415
319010AE1-072 C
Solar/Wind Helper
4.079
3143316POE
Solar/Wind Helper
1.407
316305AF2-043 C
Solar/Wind Helper
0.473
316369SG1_INVT
Solar/Wind Helper
1.664
957831AF2-077 GEN
Solar/Wind Helper
0.466
316132AB2-190 GEN1
Solar/Wind Helper
1.933
316349AD2-085 GEN
Solar/Wind Helper
1.523
313526AB2-022
Solar/Wind Helper
0.505
957601AF2-054 GEN
Solar/Wind Helper
0.438
3141873WAN 176
Solar/Wind Helper
0.065
315662AE1-191 GEN
Solar/Wind Helper
1.747
315666AE1-190 GEN
Solar/Wind Helper
0.437
316059AD1-063 C
Solar/Wind Helper
0.326
3141913WHIT STONE
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3146486SUNBURY
Solar/Wind Helper
0.323
3138133OCRAN
Solar/Wind Helper
0.097
3143873LANEXA
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.192
3141783LANCAST
Solar/Wind Helper
0.128
316321Z2-027
Solar/Wind Helper
0.487
3145176PASQUOTANK
Solar/Wind Helper
0.198
3141813NORNECK
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.556
316233AE1-074 FULL
Solar/Wind Helper
0.44
316223AC1-118
Solar/Wind Helper
0.438
316315AB2-025 C
Solar/Wind Helper
0.418
315611Z1-036_GEN2
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
3130156CHOWAN
Solar/Wind Helper
0.226
315243AE2-183_GT3
50/50
11.056
3151051BRUNSWICKS1
50/50
17.38
3151021BRUNSWICKG1
50/50
8.374
971451AH1-221 GEN
50/50
25.435
3151531CLOVER1
50/50
9.312
3151601KERR 3
50/50
0.538
3151581KERR 1
50/50
0.192
3144293JTRSVLE
50/50
0.8
971629AH1-314 GEN
50/50
17.875
3151561HALLBR1
50/50
0.366
970919AG2-571 GEN
Solar/Wind Harmer
21.227
970087AG2-069 GEN
Solar/Wind Harmer
62.431
957481AF2-042 GEN
Solar/Wind Harmer
166.01
315693AD1-088 GEN
Solar/Wind Harmer
24.233
962491AG1-098 GEN
Solar/Wind Harmer
31.935
315687AD1-152 GEN
Solar/Wind Harmer
5.313
316003AC1-222 GEN
Solar/Wind Harmer
3.193
970401AG2-262 GEN
Solar/Wind Harmer
2.094
316237AB2-079_GEN
Solar/Wind Harmer
0.868
970685AG2-442 GEN
Solar/Wind Harmer
23.682
963171AG1-166 GEN
Solar/Wind Harmer
3.328
971563AH1-280 GEN
Solar/Wind Harmer
3.328
3146926FARMVIL
Solar/Wind Harmer
-0.015
971065AG2-659 GEN
Solar/Wind Harmer
11.224
316129AC1-054 GEN
Solar/Wind Harmer
1.849
970223AG2-152 GEN
Solar/Wind Harmer
17.201
270016AE1-250 BESS
Solar/Wind Harmer
2.839
3147123OTTER R
Solar/Wind Harmer
-0.01
970413AG2-270 GEN
50/50
40.637
3151591KERR 2
50/50
0.538
3144293JTRSVLE
50/50
0.8
970917AG2-570 GEN
Solar/Wind Harmer
167.695
316478AD1-087 GEN
Solar/Wind Harmer
4.227
316486AD2-202 GEN
Solar/Wind Harmer
1.238
970909AG2-566 GEN
Solar/Wind Harmer
3.291
316248AF1-058 C
Solar/Wind Harmer
1.043
960061AF2-297 GEN
Solar/Wind Harmer
17.305
316283AC2-100 C
Solar/Wind Harmer
2.965
971683AH1-343 GEN
Solar/Wind Harmer
13.39
316131AB2-060 GEN
Solar/Wind Harmer
3.076
964241AG1-285 GEN
Solar/Wind Harmer
22.038
315785AD2-033 C
Solar/Wind Harmer
6.282
970257AG2-171 GEN
Solar/Wind Harmer
10.326
959311AF2-222 GEN
Solar/Wind Harmer
28.597
963181AG1-167 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.082
971193AH1-056 GEN
Solar/Wind Harmer
16.449
942461AE2-259 GEN
Solar/Wind Harmer
3.824
3146926FARMVIL
Solar/Wind Harmer
-0.015
270018AE2-047 C O1
Solar/Wind Harmer
1.375
270197AD1-017 GEN1
Solar/Wind Harmer
1.676
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.834
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.53
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.564
961601AG1-000A GEN
Solar/Wind Harmer
5.252
315773AC2-141 GEN
Solar/Wind Helper
9.163
3144873MCLAUGH
Solar/Wind Helper
0.01
3144536CHRHLND
Solar/Wind Helper
0.058
3145336SMITFLD
Solar/Wind Helper
0.148
3146456SLIGO L269
Solar/Wind Helper
0.359
316382AG1-145 C
Solar/Wind Helper
0.469
315839AE2-212 C
Solar/Wind Helper
0.457
316320Y1-086
Solar/Wind Helper
0.148
316156AD2-030 GEN
Solar/Wind Helper
0.492
316280AD1-041 GEN
Solar/Wind Helper
1.092
3142946ENON
Solar/Wind Helper
0.105
316484AD2-074 GEN
Solar/Wind Helper
0.607
316404AE1-155 C
Solar/Wind Helper
2.624
316435W1029_GEN3
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3141906WESTMOR
Solar/Wind Helper
0.115
3146626S HERTFORD
Solar/Wind Helper
0.28
316473AC1-191 GEN
Solar/Wind Helper
1.696
3145273HOLLAND
Solar/Wind Helper
0.188
966881AG1-559 GEN
Solar/Wind Helper
0.329
3146376EDENTON
Solar/Wind Helper
0.226
270574AD1-017 GEN2
Solar/Wind Harmer
5.577
316322AB2-045
Solar/Wind Harmer
0.514
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.53
270030AE2-140 GEN
Solar/Wind Harmer
19.734
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.817
316049AB1-081 GEN
Solar/Wind Harmer
1.454
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.785
316375AC2-012 GEN
Solar/Wind Helper
1.014
3145336SMITFLD
Solar/Wind Helper
1.482
316388AE2-253 GEN
Solar/Wind Helper
1.397
3146456SLIGO L269
Solar/Wind Helper
0.359
316072AD1-144
Solar/Wind Helper
0.404
316246AF1-032 C
Solar/Wind Helper
0.402
316159AE1-175 C
Solar/Wind Helper
0.529
316381AD1-082 GEN
Solar/Wind Helper
1.758
316458AB2-190 GEN2
Solar/Wind Helper
1.933
3141766HARMONY
Solar/Wind Helper
0.065
3138133OCRAN
Solar/Wind Helper
0.193
3142433PROV 92
Solar/Wind Helper
1.275
3142543TWELFTH
Solar/Wind Helper
0.029
964211AG1-282 GEN
Solar/Wind Helper
0.412
3141726DUNNSVL
Solar/Wind Helper
1.222
3146516WINFALL
Solar/Wind Helper
0.961
3146516WINFALL
Solar/Wind Helper
0.297
316337AD2-073 GEN
Solar/Wind Helper
0.448
3142416OLDCHRC
Solar/Wind Helper
0.759
3142416OLDCHRC
Solar/Wind Helper
0.291
3143526WINTERP
Solar/Wind Helper
1.499
3143226MDLTHAN
Solar/Wind Helper
0.284
315800Z1-036_GEN1
Solar/Wind Helper
1.411
3130156CHOWAN
Solar/Wind Helper
0.226
315242AE2-183_GT2
50/50
11.056
315241AE2-183_GT1
50/50
10.988
972185AH1-677 GEN
50/50
39.858
3151041BRUNSWICKG3
50/50
8.374
972187AH1-678 GEN
50/50
19.217
3152661PLYWOOD A
50/50
0.67
970535AG2-341 GEN
50/50
4.577
3144293JTRSVLE
50/50
0.8
3144293JTRSVLE
50/50
0.674
970933AG2-581 GEN
Solar/Wind Harmer
58.849
970099AG2-077 GEN
Solar/Wind Harmer
66.404
971741AH1-377 GEN
Solar/Wind Harmer
43.978
970301AG2-198 GEN
Solar/Wind Harmer
17.332
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.854
316222AC1-221 GEN
Solar/Wind Harmer
3.208
962561AG1-105 GEN
Solar/Wind Harmer
17.747
939181AE1-148 GEN
Solar/Wind Harmer
16.378
313527AB2-043 GEN
Solar/Wind Harmer
4.643
970323AG2-213 GEN
Solar/Wind Harmer
13.768
971775AH1-396 GEN
Solar/Wind Harmer
1.961
316034AC1-036 C
Solar/Wind Harmer
0.511
958211AF2-115 GEN
Solar/Wind Harmer
4.16
963191AG1-168 GEN
Solar/Wind Harmer
2.496
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
15.066
270013AE1-250 PV
Solar/Wind Harmer
2.839
3146776BUCKING
Solar/Wind Harmer
-0.061
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.394
316197AC1-042 GEN
Solar/Wind Harmer
1.815
942671AE2-283 GEN
Solar/Wind Harmer
4.885
316263AC1-034 GEN
Solar/Wind Harmer
6.316
961601AG1-000A GEN
Solar/Wind Harmer
5.186
316036AC1-147 C
Solar/Wind Helper
0.59
3142956BIRDNECK
Solar/Wind Helper
0.259
316316AC1-027 C
Solar/Wind Helper
0.606
316185AD1-033 GEN
Solar/Wind Helper
1.799
3145506HICKORY
Solar/Wind Helper
1.507
3145506HICKORY
Solar/Wind Helper
0.904
3145506HICKORY
Solar/Wind Helper
0.226
316236AE1-162_GEN
Solar/Wind Helper
0.498
316339AD2-160 GEN
Solar/Wind Helper
1.397
316018AA1-139 ULT2
Solar/Wind Helper
1.567
316017AA1-139 ULT1
Solar/Wind Helper
1.665
3137176SLIGO L2192
Solar/Wind Helper
1.432
3130086AYDLETT
Solar/Wind Helper
1.421
316033AB2-134 GEN
Solar/Wind Helper
1.19
315697AD1-025 GEN
Solar/Wind Helper
3.953
3146386ELIZ CT
Solar/Wind Helper
0.331
316240AF1-291 C
Solar/Wind Helper
0.444
3142946ENON
Solar/Wind Helper
0.032
316487AF1-042 GEN
Solar/Wind Helper
0.318
316075AC2-137 C
Solar/Wind Helper
0.467
316077AC2-138 C
Solar/Wind Helper
0.286
316431W1029_GEN1
Solar/Wind Helper
1.225
316433W1029_GEN2
Solar/Wind Helper
1.225
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3146516WINFALL
Solar/Wind Helper
0.297
3143526WINTERP
Solar/Wind Helper
1.499
3146626S HERTFORD
Solar/Wind Helper
0.28
3146626S HERTFORD
Solar/Wind Helper
0.28
966871AG1-558 GEN
Solar/Wind Helper
0.374
3144356SAPONY
Solar/Wind Helper
0.492
316468AD1-105 GEN
Solar/Wind Helper
1.305
NYPJM->LTFIMP_NY
CLTF
2.38
LGEELTFEXP_LGEE->PJM
CLTF
2.666
LAGNLTFEXP_LAGN->PJM
CLTF
14.626
CBM South 2LTFEXP_CBM-S2->PJM
CBM
44.161
WECLTFEXP_WEC->PJM
CLTF
1.395
AG2-052LTFEXP_AG2-052->PJM
LTF
0.075
AH1-155LTFEXP_AH1-155->PJM
LTF
0.113
TVALTFEXP_TVA->PJM
CLTF
7.294
CPLELTFEXP_CPLE->PJM
CLTF
19.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
78.004
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.554
CBM South 1LTFEXP_CBM-S1->PJM
CBM
25.081
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.22

Details for AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line l/o DVP_P4-2: 511T544_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AG2-436 TP-AE2-094 TP 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 511T544_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.13 %
Rating:4996.0 MVA
Rating Type:C
MVA to Mitigate:5601.8
MW Contribution:35.49
Bus #Bus NameTypeMW Contribution
315244AE2-183_ST
50/50
18.952
963041AG1-153 GEN
50/50
16.812
3151541CLOVER2
50/50
9.183
3151611KERR 4
50/50
0.532
3151621KERR 5
50/50
0.532
3151631KERR 6
50/50
0.532
3151641KERR 7
50/50
0.532
970673AG2-436 GEN
Solar/Wind Harmer
162.646
970673AG2-436 GEN
Solar/Wind Harmer
82.352
3151031BRUNSWICKG2
50/50
8.303
970413AG2-270 GEN
50/50
40.265
3151591KERR 2
50/50
0.532
3144293JTRSVLE
50/50
0.79
970917AG2-570 GEN
Solar/Wind Harmer
166.275
316478AD1-087 GEN
Solar/Wind Harmer
4.189
316486AD2-202 GEN
Solar/Wind Harmer
1.227
970909AG2-566 GEN
Solar/Wind Harmer
3.255
316248AF1-058 C
Solar/Wind Harmer
1.033
960061AF2-297 GEN
Solar/Wind Harmer
17.135
316283AC2-100 C
Solar/Wind Harmer
2.94
971683AH1-343 GEN
Solar/Wind Harmer
13.259
316131AB2-060 GEN
Solar/Wind Harmer
3.032
964241AG1-285 GEN
Solar/Wind Harmer
21.724
315785AD2-033 C
Solar/Wind Harmer
6.194
970257AG2-171 GEN
Solar/Wind Harmer
10.181
959311AF2-222 GEN
Solar/Wind Harmer
28.197
963181AG1-167 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.081
971193AH1-056 GEN
Solar/Wind Harmer
16.225
942461AE2-259 GEN
Solar/Wind Harmer
3.773
3146926FARMVIL
Solar/Wind Harmer
-0.014
270018AE2-047 C O1
Solar/Wind Harmer
1.363
270197AD1-017 GEN1
Solar/Wind Harmer
1.661
3146776BUCKING
Solar/Wind Harmer
-0.005
943811AF1-049 GEN
Solar/Wind Harmer
3.802
3147312GRETNA
Solar/Wind Harmer
-0.003
941821AE2-187 GEN
Solar/Wind Harmer
5.477
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.013
270336AE1-100 GEN
Solar/Wind Harmer
1.551
961601AG1-000A GEN
Solar/Wind Harmer
5.225
315773AC2-141 GEN
Solar/Wind Helper
8.525
315839AE2-212 C
Solar/Wind Helper
0.497
3144536CHRHLND
Solar/Wind Helper
0.05
3144873MCLAUGH
Solar/Wind Helper
0.008
3145336SMITFLD
Solar/Wind Helper
0.133
316382AG1-145 C
Solar/Wind Helper
0.441
316156AD2-030 GEN
Solar/Wind Helper
0.47
971967AH1-528 GEN
Solar/Wind Harmer
124.141
970085AG2-068 GEN
Solar/Wind Harmer
41.268
970581AG2-369 GEN
Solar/Wind Harmer
35.491
3147173SINAI
Solar/Wind Harmer
-0.034
3147243WELCO
Solar/Wind Harmer
-0.021
316118AC1-105 GEN
Solar/Wind Harmer
2.271
970865AG2-541 GEN
Solar/Wind Harmer
11.801
316239AB2-077_GEN
Solar/Wind Harmer
0.856
316238AB2-078_GEN
Solar/Wind Harmer
0.856
971443AH1-215 GEN
Solar/Wind Harmer
5.352
3144303KENBRDG
Solar/Wind Harmer
-0.022
970683AG2-441 GEN
Solar/Wind Harmer
20.851
970681AG2-440 GEN
Solar/Wind Harmer
16.681
946301AF1-294 GEN
Solar/Wind Harmer
6.73
961791AG1-021 GEN
Solar/Wind Harmer
3.283
270455AD2-022 GEN
Solar/Wind Harmer
4.664
270457AD2-023 GEN
Solar/Wind Harmer
2.365
315657AE1-056 GEN
Solar/Wind Harmer
9.735
316123AC1-075 GEN
Solar/Wind Harmer
2.761
970165AG2-112 GEN
Solar/Wind Harmer
2.431
970163AG2-111 GEN
Solar/Wind Harmer
2.319
970831AG2-522 GEN
Solar/Wind Harmer
9.696
970285AG2-188 GEN
Solar/Wind Harmer
15.118
971845AH1-439 GEN
Solar/Wind Harmer
8.397
270069AE2-166 C O1
Solar/Wind Harmer
2.394
3143316POE
Solar/Wind Helper
1.57
316132AB2-190 GEN1
Solar/Wind Helper
1.893
316369SG1_INVT
Solar/Wind Helper
1.59
957831AF2-077 GEN
Solar/Wind Helper
0.437
316315AB2-025 C
Solar/Wind Helper
0.494
957601AF2-054 GEN
Solar/Wind Helper
0.418
3141873WAN 176
Solar/Wind Helper
0.062
315662AE1-191 GEN
Solar/Wind Helper
1.674
315666AE1-190 GEN
Solar/Wind Helper
0.419
3143873LANEXA
Solar/Wind Helper
0.186
316059AD1-063 C
Solar/Wind Helper
0.312
3141913WHIT STONE
Solar/Wind Helper
0.309
3138133OCRAN
Solar/Wind Helper
0.093
3141783LANCAST
Solar/Wind Helper
0.184
3141783LANCAST
Solar/Wind Helper
0.123
319010AE1-072 C
Solar/Wind Helper
3.5
316349AD2-085 GEN
Solar/Wind Helper
1.396
316305AF2-043 C
Solar/Wind Helper
0.402
3141813NORNECK
Solar/Wind Helper
0.293
316233AE1-074 FULL
Solar/Wind Helper
0.446
316312AB1-027
Solar/Wind Helper
0.55
313526AB2-022
Solar/Wind Helper
0.431
316223AC1-118
Solar/Wind Helper
0.424
3146486SUNBURY
Solar/Wind Helper
0.274
3146486SUNBURY
Solar/Wind Helper
0.274
316321Z2-027
Solar/Wind Helper
0.414
3145176PASQUOTANK
Solar/Wind Helper
0.168
3142946ENON
Solar/Wind Helper
0.104
316280AD1-041 GEN
Solar/Wind Helper
1.046
3146456SLIGO L269
Solar/Wind Helper
0.308
316484AD2-074 GEN
Solar/Wind Helper
0.583
316404AE1-155 C
Solar/Wind Helper
2.523
316320Y1-086
Solar/Wind Helper
0.126
316473AC1-191 GEN
Solar/Wind Helper
1.704
3141906WESTMOR
Solar/Wind Helper
0.111
316435W1029_GEN3
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
966881AG1-559 GEN
Solar/Wind Helper
0.328
3146626S HERTFORD
Solar/Wind Helper
0.236
315242AE2-183_GT2
50/50
10.962
315241AE2-183_GT1
50/50
10.894
972185AH1-677 GEN
50/50
39.518
3151041BRUNSWICKG3
50/50
8.303
972187AH1-678 GEN
50/50
19.053
3152661PLYWOOD A
50/50
0.663
970535AG2-341 GEN
50/50
4.519
3144293JTRSVLE
50/50
0.79
3144293JTRSVLE
50/50
0.665
970933AG2-581 GEN
Solar/Wind Harmer
58.334
970099AG2-077 GEN
Solar/Wind Harmer
65.804
971741AH1-377 GEN
Solar/Wind Harmer
43.523
970301AG2-198 GEN
Solar/Wind Harmer
17.145
3146843MT LREL
Solar/Wind Harmer
-0.032
3146843MT LREL
Solar/Wind Harmer
-0.032
964791AG1-342 GEN
Solar/Wind Harmer
6.775
316222AC1-221 GEN
Solar/Wind Harmer
3.182
962561AG1-105 GEN
Solar/Wind Harmer
17.536
939181AE1-148 GEN
Solar/Wind Harmer
16.186
313527AB2-043 GEN
Solar/Wind Harmer
4.576
970323AG2-213 GEN
Solar/Wind Harmer
13.574
971775AH1-396 GEN
Solar/Wind Harmer
1.933
316034AC1-036 C
Solar/Wind Harmer
0.503
958211AF2-115 GEN
Solar/Wind Harmer
4.103
963191AG1-168 GEN
Solar/Wind Harmer
2.462
3147133PAMPLIN
Solar/Wind Harmer
-0.026
3147133PAMPLIN
Solar/Wind Harmer
-0.021
942751AE2-291 GEN
Solar/Wind Harmer
14.918
270013AE1-250 PV
Solar/Wind Harmer
2.815
3146776BUCKING
Solar/Wind Harmer
-0.06
3146776BUCKING
Solar/Wind Harmer
-0.005
316217AC1-145 GEN
Solar/Wind Harmer
2.37
316197AC1-042 GEN
Solar/Wind Harmer
1.797
942671AE2-283 GEN
Solar/Wind Harmer
4.838
316263AC1-034 GEN
Solar/Wind Harmer
6.29
961601AG1-000A GEN
Solar/Wind Harmer
5.16
316240AF1-291 C
Solar/Wind Helper
0.471
316036AC1-147 C
Solar/Wind Helper
0.511
316236AE1-162_GEN
Solar/Wind Helper
0.447
316316AC1-027 C
Solar/Wind Helper
0.524
3142956BIRDNECK
Solar/Wind Helper
0.223
316033AB2-134 GEN
Solar/Wind Helper
1.137
315697AD1-025 GEN
Solar/Wind Helper
3.779
316185AD1-033 GEN
Solar/Wind Helper
1.551
3145506HICKORY
Solar/Wind Helper
1.298
3145506HICKORY
Solar/Wind Helper
0.779
3145506HICKORY
Solar/Wind Helper
0.195
3144356SAPONY
Solar/Wind Helper
0.581
316339AD2-160 GEN
Solar/Wind Helper
1.201
316018AA1-139 ULT2
Solar/Wind Helper
1.346
316017AA1-139 ULT1
Solar/Wind Helper
1.43
3142946ENON
Solar/Wind Helper
0.031
3137176SLIGO L2192
Solar/Wind Helper
1.229
3130086AYDLETT
Solar/Wind Helper
1.219
316487AF1-042 GEN
Solar/Wind Helper
0.305
316075AC2-137 C
Solar/Wind Helper
0.459
316077AC2-138 C
Solar/Wind Helper
0.276
3143526WINTERP
Solar/Wind Helper
1.519
3146386ELIZ CT
Solar/Wind Helper
0.283
966871AG1-558 GEN
Solar/Wind Helper
0.376
316468AD1-105 GEN
Solar/Wind Helper
1.308
316431W1029_GEN1
Solar/Wind Helper
1.037
316433W1029_GEN2
Solar/Wind Helper
1.037
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146516WINFALL
Solar/Wind Helper
0.251
3146626S HERTFORD
Solar/Wind Helper
0.236
3146626S HERTFORD
Solar/Wind Helper
0.236
315243AE2-183_GT3
50/50
10.962
3151051BRUNSWICKS1
50/50
17.232
3151021BRUNSWICKG1
50/50
8.303
971451AH1-221 GEN
50/50
25.218
3151531CLOVER1
50/50
9.227
3151601KERR 3
50/50
0.532
3151581KERR 1
50/50
0.19
3144293JTRSVLE
50/50
0.79
971629AH1-314 GEN
50/50
17.731
3151561HALLBR1
50/50
0.363
970919AG2-571 GEN
Solar/Wind Harmer
21.047
970087AG2-069 GEN
Solar/Wind Harmer
61.902
957481AF2-042 GEN
Solar/Wind Harmer
164.509
315693AD1-088 GEN
Solar/Wind Harmer
24.007
962491AG1-098 GEN
Solar/Wind Harmer
31.634
315687AD1-152 GEN
Solar/Wind Harmer
5.265
316003AC1-222 GEN
Solar/Wind Harmer
3.162
970401AG2-262 GEN
Solar/Wind Harmer
2.07
316237AB2-079_GEN
Solar/Wind Harmer
0.856
970685AG2-442 GEN
Solar/Wind Harmer
23.354
963171AG1-166 GEN
Solar/Wind Harmer
3.283
971563AH1-280 GEN
Solar/Wind Harmer
3.283
3146926FARMVIL
Solar/Wind Harmer
-0.014
971065AG2-659 GEN
Solar/Wind Harmer
11.094
316129AC1-054 GEN
Solar/Wind Harmer
1.827
970223AG2-152 GEN
Solar/Wind Harmer
17.059
270016AE1-250 BESS
Solar/Wind Harmer
2.815
3147123OTTER R
Solar/Wind Harmer
-0.01
270574AD1-017 GEN2
Solar/Wind Harmer
5.528
316322AB2-045
Solar/Wind Harmer
0.506
3146776BUCKING
Solar/Wind Harmer
-0.006
3147312GRETNA
Solar/Wind Harmer
-0.012
3146802CHATHAM
Solar/Wind Harmer
-0.011
941801AE2-185 GEN
Solar/Wind Harmer
5.477
270030AE2-140 GEN
Solar/Wind Harmer
19.567
3145543BTLEBRO
Solar/Wind Harmer
-0.013
3145543BTLEBRO
Solar/Wind Harmer
-0.011
316359AB2-059 GEN
Solar/Wind Harmer
1.809
316049AB1-081 GEN
Solar/Wind Harmer
1.448
3142053HEARTS
Solar/Wind Harmer
0.158
316294AC1-161 GEN
Solar/Wind Helper
7.244
316381AD1-082 GEN
Solar/Wind Helper
1.747
316375AC2-012 GEN
Solar/Wind Helper
0.879
3145336SMITFLD
Solar/Wind Helper
1.331
316458AB2-190 GEN2
Solar/Wind Helper
1.893
316159AE1-175 C
Solar/Wind Helper
0.497
316388AE2-253 GEN
Solar/Wind Helper
1.201
3142433PROV 92
Solar/Wind Helper
1.254
3142543TWELFTH
Solar/Wind Helper
0.03
3141766HARMONY
Solar/Wind Helper
0.062
3146456SLIGO L269
Solar/Wind Helper
0.308
3138133OCRAN
Solar/Wind Helper
0.185
316072AD1-144
Solar/Wind Helper
0.35
316246AF1-032 C
Solar/Wind Helper
0.342
964211AG1-282 GEN
Solar/Wind Helper
0.397
3141726DUNNSVL
Solar/Wind Helper
1.179
3143526WINTERP
Solar/Wind Helper
1.519
3142416OLDCHRC
Solar/Wind Helper
0.752
3143226MDLTHAN
Solar/Wind Helper
0.289
3142416OLDCHRC
Solar/Wind Helper
0.288
316337AD2-073 GEN
Solar/Wind Helper
0.434
3146516WINFALL
Solar/Wind Helper
0.813
3146516WINFALL
Solar/Wind Helper
0.251
NYPJM->LTFIMP_NY
CLTF
2.38
LAGNLTFEXP_LAGN->PJM
CLTF
14.499
LGEELTFEXP_LGEE->PJM
CLTF
2.637
WECLTFEXP_WEC->PJM
CLTF
1.38
AG2-052LTFEXP_AG2-052->PJM
LTF
0.074
AH1-155LTFEXP_AH1-155->PJM
LTF
0.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
43.842
TVALTFEXP_TVA->PJM
CLTF
7.231
CPLELTFEXP_CPLE->PJM
CLTF
19.58
CBM West 2LTFEXP_CBM-W2->PJM
CBM
77.279
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.858
MECLTFEXP_MEC->PJM
CLTF
7.267
SIGELTFEXP_SIGE->PJM
CLTF
0.218

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:181.65 %
Rating:559.3 MVA
Rating Type:B
MVA to Mitigate:1015.96
MW Contribution:3.75
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.4
3151591KERR 2
50/50
0.315
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.109
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.3
3151601KERR 3
50/50
0.315
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.233
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.302
3151021BRUNSWICKG1
50/50
1.109
971451AH1-221 GEN
50/50
3.369
315243AE2-183_GT3
50/50
1.358
3151391GASTONA
50/50
0.198
3151411GASTONB
50/50
0.198
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.938
971563AH1-280 GEN
Solar/Wind Harmer
3.876
970685AG2-442 GEN
Solar/Wind Harmer
24.484
962491AG1-098 GEN
Solar/Wind Harmer
11.925
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.548
970401AG2-262 GEN
Solar/Wind Harmer
0.937
957481AF2-042 GEN
Solar/Wind Harmer
40.4
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.702
316129AC1-054 GEN
Solar/Wind Harmer
0.489
971795AH1-408 GEN
Solar/Wind Harmer
7.855
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.909
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.916
970087AG2-069 GEN
Solar/Wind Harmer
6.541
316212AC1-099_GEN
Solar/Wind Harmer
0.387
3146263WOODLND
Solar/Wind Harmer
0.074
316011AB1-132 GEN
Solar/Wind Harmer
1.327
316023GEN1_S
Solar/Wind Harmer
0.164
962571AG1-106 GEN
Solar/Wind Harmer
1.039
3145796HORNRTN
Solar/Wind Harmer
0.239
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.286
3145893MURPHYS
Solar/Wind Harmer
0.283
3145893MURPHYS
Solar/Wind Harmer
0.314
315722AD1-056 GEN
Solar/Wind Harmer
0.447
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.251
316049AB1-081 GEN
Solar/Wind Harmer
0.4
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.3
940641AE2-051 GEN
Solar/Wind Harmer
5.396
316494AC1-189 GEN
Solar/Wind Harmer
0.224
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.923
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
971547AH1-271 GEN
Solar/Wind Harmer
1.316
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.641
316322AB2-045
Solar/Wind Helper
0.957
3146776BUCKING
Solar/Wind Helper
0.343
316336AC2-165 C
Solar/Wind Helper
1.513
3151541CLOVER2
50/50
3.284
3151611KERR 4
50/50
0.315
3151621KERR 5
50/50
0.315
3151631KERR 6
50/50
0.315
3151641KERR 7
50/50
0.315
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.246
315244AE2-183_ST
50/50
2.348
971845AH1-439 GEN
Solar/Wind Harmer
30.743
970285AG2-188 GEN
Solar/Wind Harmer
51.681
315657AE1-056 GEN
Solar/Wind Harmer
13.387
946301AF1-294 GEN
Solar/Wind Harmer
7.171
961791AG1-021 GEN
Solar/Wind Harmer
3.489
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.196
3147133PAMPLIN
Solar/Wind Harmer
1.218
971193AH1-056 GEN
Solar/Wind Harmer
23.635
963181AG1-167 GEN
Solar/Wind Harmer
1.454
959311AF2-222 GEN
Solar/Wind Harmer
26.76
970257AG2-171 GEN
Solar/Wind Harmer
9.287
315785AD2-033 C
Solar/Wind Harmer
2.238
964241AG1-285 GEN
Solar/Wind Harmer
15.712
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.403
971683AH1-343 GEN
Solar/Wind Harmer
4.014
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.162
970917AG2-570 GEN
Solar/Wind Harmer
7.29
316210AC1-098 GEN
Solar/Wind Harmer
0.693
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.074
316365GEN2_N
Solar/Wind Harmer
0.164
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.361
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.071
315724AD1-057 GEN
Solar/Wind Harmer
0.265
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.233
961681AG1-008 GEN
Solar/Wind Harmer
5.233
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.14
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.909
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.025
962331AG1-082 GEN
Solar/Wind Harmer
0.733
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3156021HOLLOMANSOL
Solar/Wind Harmer
0.291
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.744
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.062
315737AD1-076 GEN
Solar/Wind Harmer
0.772
971157AH1-035 GEN
Solar/Wind Harmer
0.716
315614AA2-178 GEN
Solar/Wind Harmer
0.332
3145273HOLLAND
Solar/Wind Harmer
0.043
3146776BUCKING
Solar/Wind Helper
0.309
316313AB2-026
Solar/Wind Helper
0.361
316258AE1-075 C
Solar/Wind Helper
0.325
316405AF2-144 C
Solar/Wind Helper
0.271
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.034
970535AG2-341 GEN
50/50
3.152
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.109
972187AH1-678 GEN
50/50
2.545
315242AE2-183_GT2
50/50
1.358
315241AE2-183_GT1
50/50
1.35
972185AH1-677 GEN
50/50
4.896
970533AG2-339 GEN
50/50
6.901
970531AG2-338 GEN
50/50
2.76
3151361ROSEMG1
50/50
0.261
3151371ROSEMS1
50/50
0.162
3151381ROSEMG2
50/50
0.122
970301AG2-198 GEN
Solar/Wind Harmer
16.784
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.361
963191AG1-168 GEN
Solar/Wind Harmer
1.454
971741AH1-377 GEN
Solar/Wind Harmer
34.597
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.383
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
8.006
939181AE1-148 GEN
Solar/Wind Harmer
7.768
964791AG1-342 GEN
Solar/Wind Harmer
3.068
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.16
970933AG2-581 GEN
Solar/Wind Harmer
8.957
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.957
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.539
3145783HORNRTN
Solar/Wind Harmer
1.231
3145783HORNRTN
Solar/Wind Harmer
0.385
3145783HORNRTN
Solar/Wind Harmer
0.154
316426AA2-053 GEN
Solar/Wind Harmer
0.286
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.402
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.044
942751AE2-291 GEN
Solar/Wind Harmer
3.947
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.473
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.657
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.227
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.063
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.517
316065AD1-022 GEN
Solar/Wind Harmer
2.811
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146776BUCKING
Solar/Wind Helper
3.433
3146776BUCKING
Solar/Wind Helper
0.278
315821AE2-092 GEN
Solar/Wind Helper
2.985
3148013FISHERV
Solar/Wind Helper
0.126
970683AG2-441 GEN
Solar/Wind Harmer
21.861
970681AG2-440 GEN
Solar/Wind Harmer
17.489
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.821
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.369
3147173SINAI
Solar/Wind Harmer
0.127
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.372
970865AG2-541 GEN
Solar/Wind Harmer
3.489
971967AH1-528 GEN
Solar/Wind Harmer
15.071
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.359
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.676
970163AG2-111 GEN
Solar/Wind Harmer
0.645
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.361
970581AG2-369 GEN
Solar/Wind Harmer
3.75
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.208
970673AG2-436 GEN
Solar/Wind Harmer
11.472
941031AE2-094 GEN
Solar/Wind Harmer
14.299
944011AF1-069 GEN
Solar/Wind Harmer
4.672
315652AC1-086 GEN
Solar/Wind Harmer
8.029
3146033SCOT NK
Solar/Wind Harmer
0.291
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.32
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.191
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.144
3145513AHOSKIE
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.854
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
3145746EVERETS
Solar/Wind Harmer
0.065
970181AG2-120 GEN
Solar/Wind Harmer
0.805
315814AE2-033 C
Solar/Wind Harmer
4.945
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.062
970601AG2-382 GEN
Solar/Wind Harmer
2.302
315732AD1-074 GEN1
Solar/Wind Harmer
0.345
315733AD1-074 GEN2
Solar/Wind Harmer
0.345
315735AD1-075 GEN1
Solar/Wind Harmer
0.173
3130546PLYMOUTH
Solar/Wind Harmer
0.06
315816AE2-034 GEN
Solar/Wind Harmer
0.249
270494AE1-108_GEN
Solar/Wind Helper
4.45
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
NYPJM->LTFIMP_NY
CLTF
0.48
LGEELTFEXP_LGEE->PJM
CLTF
0.362
LAGNLTFEXP_LAGN->PJM
CLTF
2.753
WECLTFEXP_WEC->PJM
CLTF
0.189
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.143
TVALTFEXP_TVA->PJM
CLTF
1.358
CPLELTFEXP_CPLE->PJM
CLTF
4.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.581
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.475
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.539
MECLTFEXP_MEC->PJM
CLTF
1.12
SIGELTFEXP_SIGE->PJM
CLTF
0.032

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.94 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:916.12
MW Contribution:3.72
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.289
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.955
3147043LAWRENC
50/50
1.106
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.97
971563AH1-280 GEN
Solar/Wind Harmer
4.97
970685AG2-442 GEN
Solar/Wind Harmer
31.247
962491AG1-098 GEN
Solar/Wind Harmer
14.52
316237AB2-079_GEN
Solar/Wind Harmer
0.639
315693AD1-088 GEN
Solar/Wind Harmer
10.276
970401AG2-262 GEN
Solar/Wind Harmer
1.085
957481AF2-042 GEN
Solar/Wind Harmer
47.025
315687AD1-152 GEN
Solar/Wind Harmer
1.689
971065AG2-659 GEN
Solar/Wind Harmer
6.793
316129AC1-054 GEN
Solar/Wind Harmer
1.154
316003AC1-222 GEN
Solar/Wind Harmer
1.163
971795AH1-408 GEN
Solar/Wind Harmer
8.792
960081AF2-299 GEN
Solar/Wind Harmer
1.021
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.099
316212AC1-099_GEN
Solar/Wind Harmer
0.614
970919AG2-571 GEN
Solar/Wind Harmer
2.193
970087AG2-069 GEN
Solar/Wind Harmer
6.491
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.406
962571AG1-106 GEN
Solar/Wind Harmer
0.966
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.899
316049AB1-081 GEN
Solar/Wind Harmer
0.72
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.694
316023GEN1_S
Solar/Wind Harmer
0.443
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.191
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.189
316322AB2-045
Solar/Wind Helper
0.963
3146776BUCKING
Solar/Wind Helper
0.346
316336AC2-165 C
Solar/Wind Helper
1.425
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.007
970535AG2-341 GEN
50/50
2.934
3152661PLYWOOD A
50/50
0.28
970301AG2-198 GEN
Solar/Wind Harmer
21.495
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.212
963191AG1-168 GEN
Solar/Wind Harmer
3.727
971741AH1-377 GEN
Solar/Wind Harmer
43.991
316034AC1-036 C
Solar/Wind Harmer
0.584
970323AG2-213 GEN
Solar/Wind Harmer
15.706
971775AH1-396 GEN
Solar/Wind Harmer
2.237
313527AB2-043 GEN
Solar/Wind Harmer
3.538
962561AG1-105 GEN
Solar/Wind Harmer
9.795
939181AE1-148 GEN
Solar/Wind Harmer
9.44
964791AG1-342 GEN
Solar/Wind Harmer
3.552
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.81
970933AG2-581 GEN
Solar/Wind Harmer
9.592
316181AB2-040 GEN
Solar/Wind Harmer
1.225
316222AC1-221 GEN
Solar/Wind Harmer
0.857
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.951
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.982
3145783HORNRTN
Solar/Wind Harmer
0.786
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.813
316274AC1-208 GEN
Solar/Wind Harmer
0.793
942751AE2-291 GEN
Solar/Wind Harmer
4.536
972187AH1-678 GEN
Adder
1.773
972185AH1-677 GEN
Adder
3.35
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.126
961601AG1-000A GEN
Solar/Wind Harmer
2.583
3145893MURPHYS
Solar/Wind Harmer
0.18
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
3146776BUCKING
Solar/Wind Helper
3.457
3146776BUCKING
Solar/Wind Helper
0.28
315821AE2-092 GEN
Solar/Wind Helper
2.963
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.289
970413AG2-270 GEN
50/50
12.897
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.604
970909AG2-566 GEN
Solar/Wind Harmer
4.081
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.615
963181AG1-167 GEN
Solar/Wind Harmer
3.727
959311AF2-222 GEN
Solar/Wind Harmer
34.076
970257AG2-171 GEN
Solar/Wind Harmer
11.779
315785AD2-033 C
Solar/Wind Harmer
6.734
964241AG1-285 GEN
Solar/Wind Harmer
19.68
316131AB2-060 GEN
Solar/Wind Harmer
2.422
316478AD1-087 GEN
Solar/Wind Harmer
1.342
316486AD2-202 GEN
Solar/Wind Harmer
0.393
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.458
971683AH1-343 GEN
Solar/Wind Harmer
4.759
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.706
316283AC2-100 C
Solar/Wind Harmer
0.787
316210AC1-098 GEN
Solar/Wind Harmer
1.105
316327AA2-057 GEN
Solar/Wind Harmer
0.707
970917AG2-570 GEN
Solar/Wind Harmer
17.327
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3151611KERR 4
50/50
0.289
3151621KERR 5
50/50
0.289
3151631KERR 6
50/50
0.289
3151641KERR 7
50/50
0.289
3151541CLOVER2
50/50
2.941
971845AH1-439 GEN
Solar/Wind Harmer
40.276
970285AG2-188 GEN
Solar/Wind Harmer
63.831
315657AE1-056 GEN
Solar/Wind Harmer
15.969
946301AF1-294 GEN
Solar/Wind Harmer
10.188
961791AG1-021 GEN
Solar/Wind Harmer
4.97
970683AG2-441 GEN
Solar/Wind Harmer
27.899
970681AG2-440 GEN
Solar/Wind Harmer
22.32
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.111
316239AB2-077_GEN
Solar/Wind Harmer
0.639
316238AB2-078_GEN
Solar/Wind Harmer
0.639
316118AC1-105 GEN
Solar/Wind Harmer
1.014
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.355
970865AG2-541 GEN
Solar/Wind Harmer
4.115
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.265
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.894
970165AG2-112 GEN
Solar/Wind Harmer
0.787
970163AG2-111 GEN
Solar/Wind Harmer
0.751
971967AH1-528 GEN
Solar/Wind Harmer
15.203
315607AA1-063A GEN
Solar/Wind Harmer
0.778
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.327
970581AG2-369 GEN
Solar/Wind Harmer
3.722
316319Z2-044 C
Solar/Wind Harmer
0.378
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.562
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.582
970673AG2-436 GEN
Solar/Wind Harmer
13.618
970673AG2-436 GEN
Solar/Wind Harmer
6.895
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.464
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.382
316365GEN2_N
Solar/Wind Harmer
0.443
961601AG1-000A GEN
Solar/Wind Harmer
2.615
316317KELFORD C
Solar/Wind Harmer
0.306
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.09
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.039
961681AG1-008 GEN
Solar/Wind Harmer
5.039
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.311
316313AB2-026
Solar/Wind Helper
0.332
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.123
NYPJM->LTFIMP_NY
CLTF
0.295
LGEELTFEXP_LGEE->PJM
CLTF
0.219
LAGNLTFEXP_LAGN->PJM
CLTF
2.505
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.252
WECLTFEXP_WEC->PJM
CLTF
0.123
TVALTFEXP_TVA->PJM
CLTF
1.216
CPLELTFEXP_CPLE->PJM
CLTF
4.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.552
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.102
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.96
MECLTFEXP_MEC->PJM
CLTF
0.838
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.34 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:891.54
MW Contribution:3.62
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.19
3144293JTRSVLE
50/50
1.002
970535AG2-341 GEN
50/50
2.898
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.406
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.183
963191AG1-168 GEN
Solar/Wind Harmer
3.71
3144293JTRSVLE
50/50
1.19
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.102
3151531CLOVER1
50/50
2.917
3147043LAWRENC
50/50
1.102
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.946
971563AH1-280 GEN
Solar/Wind Harmer
4.946
970685AG2-442 GEN
Solar/Wind Harmer
31.078
962491AG1-098 GEN
Solar/Wind Harmer
14.404
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.19
970401AG2-262 GEN
Solar/Wind Harmer
1.07
957481AF2-042 GEN
Solar/Wind Harmer
46.506
315687AD1-152 GEN
Solar/Wind Harmer
1.657
971065AG2-659 GEN
Solar/Wind Harmer
6.686
316129AC1-054 GEN
Solar/Wind Harmer
1.136
971795AH1-408 GEN
Solar/Wind Harmer
8.781
316003AC1-222 GEN
Solar/Wind Harmer
1.14
960081AF2-299 GEN
Solar/Wind Harmer
1.025
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.591
970919AG2-571 GEN
Solar/Wind Harmer
2.137
970087AG2-069 GEN
Solar/Wind Harmer
6.318
316023GEN1_S
Solar/Wind Harmer
0.452
316011AB1-132 GEN
Solar/Wind Harmer
1.389
962571AG1-106 GEN
Solar/Wind Harmer
0.954
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.903
971845AH1-439 GEN
Solar/Wind Harmer
40.178
970285AG2-188 GEN
Solar/Wind Harmer
63.671
315657AE1-056 GEN
Solar/Wind Harmer
15.898
946301AF1-294 GEN
Solar/Wind Harmer
10.139
961791AG1-021 GEN
Solar/Wind Harmer
4.946
970683AG2-441 GEN
Solar/Wind Harmer
27.748
970681AG2-440 GEN
Solar/Wind Harmer
22.198
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.073
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.997
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.254
970865AG2-541 GEN
Solar/Wind Harmer
4.048
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.884
970165AG2-112 GEN
Solar/Wind Harmer
0.778
970163AG2-111 GEN
Solar/Wind Harmer
0.742
971967AH1-528 GEN
Solar/Wind Harmer
15.039
315607AA1-063A GEN
Solar/Wind Harmer
0.762
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.212
970581AG2-369 GEN
Solar/Wind Harmer
3.623
315652AC1-086 GEN
Solar/Wind Harmer
7.469
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.36
970673AG2-436 GEN
Solar/Wind Harmer
13.449
970673AG2-436 GEN
Solar/Wind Harmer
6.81
965291AG1-394 GEN
Solar/Wind Harmer
0.565
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.19
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.729
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.576
970909AG2-566 GEN
Solar/Wind Harmer
4.064
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.496
963181AG1-167 GEN
Solar/Wind Harmer
3.71
959311AF2-222 GEN
Solar/Wind Harmer
33.872
970257AG2-171 GEN
Solar/Wind Harmer
11.706
315785AD2-033 C
Solar/Wind Harmer
6.689
964241AG1-285 GEN
Solar/Wind Harmer
19.525
316131AB2-060 GEN
Solar/Wind Harmer
2.4
316478AD1-087 GEN
Solar/Wind Harmer
1.324
316486AD2-202 GEN
Solar/Wind Harmer
0.388
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.381
960061AF2-297 GEN
Solar/Wind Harmer
6.325
971683AH1-343 GEN
Solar/Wind Harmer
4.674
966621AG1-532 GEN
Solar/Wind Harmer
0.185
313506AB2-031 GEN
Solar/Wind Harmer
0.702
316283AC2-100 C
Solar/Wind Harmer
0.736
316210AC1-098 GEN
Solar/Wind Harmer
1.064
970917AG2-570 GEN
Solar/Wind Harmer
16.885
316365GEN2_N
Solar/Wind Harmer
0.452
316327AA2-057 GEN
Solar/Wind Harmer
0.676
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.367
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.256
3148013FISHERV
Solar/Wind Helper
0.124
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.667
3145543BTLEBRO
Solar/Wind Harmer
-0.006
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.456
971741AH1-377 GEN
Solar/Wind Harmer
43.786
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.608
971775AH1-396 GEN
Solar/Wind Harmer
2.223
313527AB2-043 GEN
Solar/Wind Harmer
3.505
962561AG1-105 GEN
Solar/Wind Harmer
9.664
939181AE1-148 GEN
Solar/Wind Harmer
9.308
964791AG1-342 GEN
Solar/Wind Harmer
3.501
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.602
970933AG2-581 GEN
Solar/Wind Harmer
9.49
316181AB2-040 GEN
Solar/Wind Harmer
1.218
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.934
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.963
3145783HORNRTN
Solar/Wind Harmer
0.77
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.802
316426AA2-053 GEN
Solar/Wind Harmer
0.797
316274AC1-208 GEN
Solar/Wind Harmer
0.766
942751AE2-291 GEN
Solar/Wind Harmer
4.503
972187AH1-678 GEN
Adder
1.745
972185AH1-677 GEN
Adder
3.302
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.47
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.982
NYPJM->LTFIMP_NY
CLTF
0.315
LGEELTFEXP_LGEE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
2.085
WECLTFEXP_WEC->PJM
CLTF
0.133
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.001
TVALTFEXP_TVA->PJM
CLTF
1.025
CPLELTFEXP_CPLE->PJM
CLTF
3.951
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.116
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.403
MECLTFEXP_MEC->PJM
CLTF
0.809
SIGELTFEXP_SIGE->PJM
CLTF
0.023

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 249-69_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 249-69_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:126.04 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:862.13
MW Contribution:3.55
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.187
3151591KERR 2
50/50
0.282
970413AG2-270 GEN
50/50
12.638
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.566
970909AG2-566 GEN
Solar/Wind Harmer
4.057
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.448
963181AG1-167 GEN
Solar/Wind Harmer
3.702
959311AF2-222 GEN
Solar/Wind Harmer
33.775
970257AG2-171 GEN
Solar/Wind Harmer
11.671
315785AD2-033 C
Solar/Wind Harmer
6.667
964241AG1-285 GEN
Solar/Wind Harmer
19.444
316131AB2-060 GEN
Solar/Wind Harmer
2.388
316478AD1-087 GEN
Solar/Wind Harmer
1.315
316486AD2-202 GEN
Solar/Wind Harmer
0.385
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.378
960061AF2-297 GEN
Solar/Wind Harmer
6.277
971683AH1-343 GEN
Solar/Wind Harmer
4.637
3144293JTRSVLE
50/50
1.187
3144293JTRSVLE
50/50
1
970535AG2-341 GEN
50/50
2.881
3152661PLYWOOD A
50/50
0.273
970301AG2-198 GEN
Solar/Wind Harmer
21.369
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
3144293JTRSVLE
50/50
1.187
3151601KERR 3
50/50
0.282
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.896
3147043LAWRENC
50/50
1.087
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.936
971563AH1-280 GEN
Solar/Wind Harmer
4.936
970685AG2-442 GEN
Solar/Wind Harmer
31.001
962491AG1-098 GEN
Solar/Wind Harmer
14.334
316237AB2-079_GEN
Solar/Wind Harmer
0.629
315693AD1-088 GEN
Solar/Wind Harmer
10.136
970401AG2-262 GEN
Solar/Wind Harmer
1.063
957481AF2-042 GEN
Solar/Wind Harmer
46.146
315687AD1-152 GEN
Solar/Wind Harmer
1.644
971065AG2-659 GEN
Solar/Wind Harmer
6.622
316129AC1-054 GEN
Solar/Wind Harmer
1.124
316003AC1-222 GEN
Solar/Wind Harmer
1.132
971795AH1-408 GEN
Solar/Wind Harmer
8.642
960081AF2-299 GEN
Solar/Wind Harmer
1.002
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
316212AC1-099_GEN
Solar/Wind Harmer
0.579
970919AG2-571 GEN
Solar/Wind Harmer
2.097
970087AG2-069 GEN
Solar/Wind Harmer
6.198
316023GEN1_S
Solar/Wind Harmer
0.436
3146263WOODLND
Solar/Wind Harmer
-0.006
316011AB1-132 GEN
Solar/Wind Harmer
1.351
962571AG1-106 GEN
Solar/Wind Harmer
0.928
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
316322AB2-045
Solar/Wind Helper
0.967
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.451
966621AG1-532 GEN
Solar/Wind Harmer
0.181
313506AB2-031 GEN
Solar/Wind Harmer
0.687
316283AC2-100 C
Solar/Wind Harmer
0.728
316210AC1-098 GEN
Solar/Wind Harmer
1.043
970917AG2-570 GEN
Solar/Wind Harmer
16.563
316327AA2-057 GEN
Solar/Wind Harmer
0.663
316365GEN2_N
Solar/Wind Harmer
0.436
3146263WOODLND
Solar/Wind Harmer
-0.006
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.34
316258AE1-075 C
Solar/Wind Helper
0.306
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.282
3151621KERR 5
50/50
0.282
3151631KERR 6
50/50
0.282
3151641KERR 7
50/50
0.282
3151541CLOVER2
50/50
2.882
971845AH1-439 GEN
Solar/Wind Harmer
40.164
970285AG2-188 GEN
Solar/Wind Harmer
63.644
315657AE1-056 GEN
Solar/Wind Harmer
15.869
946301AF1-294 GEN
Solar/Wind Harmer
10.118
961791AG1-021 GEN
Solar/Wind Harmer
4.936
970683AG2-441 GEN
Solar/Wind Harmer
27.679
970681AG2-440 GEN
Solar/Wind Harmer
22.144
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.054
316239AB2-077_GEN
Solar/Wind Harmer
0.629
316238AB2-078_GEN
Solar/Wind Harmer
0.629
316118AC1-105 GEN
Solar/Wind Harmer
0.99
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.188
970865AG2-541 GEN
Solar/Wind Harmer
4.016
946281AF1-292 GEN
Solar/Wind Harmer
0.2
316087AB2-174 GEN
Solar/Wind Harmer
1.235
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316123AC1-075 GEN
Solar/Wind Harmer
0.876
970165AG2-112 GEN
Solar/Wind Harmer
0.771
970163AG2-111 GEN
Solar/Wind Harmer
0.736
971967AH1-528 GEN
Solar/Wind Harmer
14.788
315607AA1-063A GEN
Solar/Wind Harmer
0.747
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.132
970581AG2-369 GEN
Solar/Wind Harmer
3.554
315652AC1-086 GEN
Solar/Wind Harmer
7.265
3146033SCOT NK
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
316319Z2-044 C
Solar/Wind Harmer
0.352
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
958211AF2-115 GEN
Solar/Wind Harmer
6.17
963191AG1-168 GEN
Solar/Wind Harmer
3.702
971741AH1-377 GEN
Solar/Wind Harmer
43.69
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.561
971775AH1-396 GEN
Solar/Wind Harmer
2.216
313527AB2-043 GEN
Solar/Wind Harmer
3.487
962561AG1-105 GEN
Solar/Wind Harmer
9.606
939181AE1-148 GEN
Solar/Wind Harmer
9.243
964791AG1-342 GEN
Solar/Wind Harmer
3.479
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.458
970933AG2-581 GEN
Solar/Wind Harmer
9.37
316181AB2-040 GEN
Solar/Wind Harmer
1.193
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.917
3145593CAROLNA
Solar/Wind Harmer
0.068
3145783HORNRTN
Solar/Wind Harmer
0.945
3145783HORNRTN
Solar/Wind Harmer
0.756
3145783HORNRTN
Solar/Wind Harmer
0.236
3145783HORNRTN
Solar/Wind Harmer
0.094
316222AC1-221 GEN
Solar/Wind Harmer
0.793
316426AA2-053 GEN
Solar/Wind Harmer
0.781
942751AE2-291 GEN
Solar/Wind Harmer
4.462
316274AC1-208 GEN
Solar/Wind Harmer
0.751
972187AH1-678 GEN
Adder
1.711
972185AH1-677 GEN
Adder
3.235
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3146776BUCKING
Solar/Wind Helper
3.472
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.98
NYPJM->LTFIMP_NY
CLTF
0.308
LGEELTFEXP_LGEE->PJM
CLTF
0.244
LAGNLTFEXP_LAGN->PJM
CLTF
2.044
WECLTFEXP_WEC->PJM
CLTF
0.129
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.87
TVALTFEXP_TVA->PJM
CLTF
1.005
CPLELTFEXP_CPLE->PJM
CLTF
3.89
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.9
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.379
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.333
MECLTFEXP_MEC->PJM
CLTF
0.789
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.65 %
Rating:684.0 MVA
Rating Type:C
MVA to Mitigate:832.11
MW Contribution:3.47
Bus #Bus NameTypeMW Contribution
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.869
971845AH1-439 GEN
Solar/Wind Harmer
40.155
970285AG2-188 GEN
Solar/Wind Harmer
63.627
315657AE1-056 GEN
Solar/Wind Harmer
15.857
946301AF1-294 GEN
Solar/Wind Harmer
10.111
961791AG1-021 GEN
Solar/Wind Harmer
4.932
970683AG2-441 GEN
Solar/Wind Harmer
27.657
970681AG2-440 GEN
Solar/Wind Harmer
22.126
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.048
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
1
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.134
970865AG2-541 GEN
Solar/Wind Harmer
4.26
316123AC1-075 GEN
Solar/Wind Harmer
0.971
970165AG2-112 GEN
Solar/Wind Harmer
0.855
970163AG2-111 GEN
Solar/Wind Harmer
0.816
946281AF1-292 GEN
Solar/Wind Harmer
0.194
316087AB2-174 GEN
Solar/Wind Harmer
1.202
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.485
315607AA1-063A GEN
Solar/Wind Harmer
0.732
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.036
970581AG2-369 GEN
Solar/Wind Harmer
3.471
270494AE1-108_GEN
Solar/Wind Helper
4.511
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.579
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.561
970909AG2-566 GEN
Solar/Wind Harmer
4.052
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.429
963181AG1-167 GEN
Solar/Wind Harmer
3.699
959311AF2-222 GEN
Solar/Wind Harmer
33.746
970257AG2-171 GEN
Solar/Wind Harmer
11.66
315785AD2-033 C
Solar/Wind Harmer
6.661
964241AG1-285 GEN
Solar/Wind Harmer
19.423
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.308
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.384
960061AF2-297 GEN
Solar/Wind Harmer
6.368
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.838
966621AG1-532 GEN
Solar/Wind Harmer
0.176
313506AB2-031 GEN
Solar/Wind Harmer
0.67
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.021
970917AG2-570 GEN
Solar/Wind Harmer
16.174
316327AA2-057 GEN
Solar/Wind Harmer
0.648
3146263WOODLND
Solar/Wind Harmer
-0.006
3146776BUCKING
Solar/Wind Helper
0.312
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.873
3152661PLYWOOD A
50/50
0.275
970301AG2-198 GEN
Solar/Wind Harmer
21.341
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.165
963191AG1-168 GEN
Solar/Wind Harmer
3.699
971741AH1-377 GEN
Solar/Wind Harmer
43.617
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.547
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.649
964791AG1-342 GEN
Solar/Wind Harmer
3.499
939181AE1-148 GEN
Solar/Wind Harmer
9.211
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.337
970933AG2-581 GEN
Solar/Wind Harmer
9.235
316181AB2-040 GEN
Solar/Wind Harmer
1.163
942751AE2-291 GEN
Solar/Wind Harmer
5.136
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.898
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.791
3145783HORNRTN
Solar/Wind Harmer
0.925
3145783HORNRTN
Solar/Wind Harmer
0.74
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.765
316274AC1-208 GEN
Solar/Wind Harmer
0.735
972187AH1-678 GEN
Adder
1.669
3146776BUCKING
Solar/Wind Helper
3.473
3146776BUCKING
Solar/Wind Helper
0.281
315821AE2-092 GEN
Solar/Wind Helper
2.981
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.882
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.932
971563AH1-280 GEN
Solar/Wind Harmer
4.932
970685AG2-442 GEN
Solar/Wind Harmer
30.976
962491AG1-098 GEN
Solar/Wind Harmer
14.277
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.093
970401AG2-262 GEN
Solar/Wind Harmer
1.069
957481AF2-042 GEN
Solar/Wind Harmer
45.841
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.575
316129AC1-054 GEN
Solar/Wind Harmer
1.116
3147043LAWRENC
Adder
1.01
316003AC1-222 GEN
Solar/Wind Harmer
1.164
971795AH1-408 GEN
Solar/Wind Harmer
8.484
960081AF2-299 GEN
Solar/Wind Harmer
0.973
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.567
970919AG2-571 GEN
Solar/Wind Harmer
2.047
970087AG2-069 GEN
Solar/Wind Harmer
6.053
3146263WOODLND
Solar/Wind Harmer
-0.006
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.444
NYPJM->LTFIMP_NY
CLTF
0.299
LGEELTFEXP_LGEE->PJM
CLTF
0.225
LAGNLTFEXP_LAGN->PJM
CLTF
1.974
WECLTFEXP_WEC->PJM
CLTF
0.119
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.732
TVALTFEXP_TVA->PJM
CLTF
0.969
CPLELTFEXP_CPLE->PJM
CLTF
3.836
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.023
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.205
MECLTFEXP_MEC->PJM
CLTF
0.743
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-439 TP-6BUCKING 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:559.3 MVA
Rating Type:A
MVA to Mitigate:647.7
MW Contribution:2.61
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.183
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.851
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.765
972187AH1-678 GEN
50/50
1.756
970301AG2-198 GEN
Solar/Wind Harmer
16.182
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.203
963191AG1-168 GEN
Solar/Wind Harmer
1.401
971741AH1-377 GEN
Solar/Wind Harmer
33.06
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.759
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.224
939181AE1-148 GEN
Solar/Wind Harmer
6.94
3144293JTRSVLE
50/50
1.183
3151601KERR 3
50/50
0.279
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.861
3147043LAWRENC
50/50
1.063
3151261ROARAP2
50/50
0.088
3151051BRUNSWICKS1
50/50
1.588
3151021BRUNSWICKG1
50/50
0.765
971451AH1-221 GEN
50/50
2.324
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.868
971563AH1-280 GEN
Solar/Wind Harmer
3.736
970685AG2-442 GEN
Solar/Wind Harmer
23.448
962491AG1-098 GEN
Solar/Wind Harmer
10.797
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.584
970401AG2-262 GEN
Solar/Wind Harmer
0.842
957481AF2-042 GEN
Solar/Wind Harmer
34.592
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.952
316129AC1-054 GEN
Solar/Wind Harmer
0.422
3144293JTRSVLE
50/50
1.183
3151591KERR 2
50/50
0.279
970413AG2-270 GEN
50/50
12.485
3151261ROARAP2
50/50
0.086
3151031BRUNSWICKG2
50/50
0.765
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.045
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.863
963181AG1-167 GEN
Solar/Wind Harmer
1.401
959311AF2-222 GEN
Solar/Wind Harmer
25.479
970257AG2-171 GEN
Solar/Wind Harmer
8.819
315785AD2-033 C
Solar/Wind Harmer
2.117
964241AG1-285 GEN
Solar/Wind Harmer
14.665
316131AB2-060 GEN
Solar/Wind Harmer
0.615
316478AD1-087 GEN
Solar/Wind Harmer
0.466
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
4.708
971683AH1-343 GEN
Solar/Wind Harmer
3.476
313506AB2-031 GEN
Solar/Wind Harmer
0.227
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.656
960081AF2-299 GEN
Solar/Wind Harmer
0.732
3145783HORNRTN
Solar/Wind Harmer
0.069
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.296
970919AG2-571 GEN
Solar/Wind Harmer
2.029
970087AG2-069 GEN
Solar/Wind Harmer
4.556
316322AB2-045
Solar/Wind Helper
0.968
3146776BUCKING
Solar/Wind Helper
0.347
316336AC2-165 C
Solar/Wind Helper
1.445
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.531
970917AG2-570 GEN
Solar/Wind Harmer
5.072
316327AA2-057 GEN
Solar/Wind Harmer
0.085
3146776BUCKING
Solar/Wind Helper
0.313
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.123
3151611KERR 4
50/50
0.279
3151621KERR 5
50/50
0.279
3151631KERR 6
50/50
0.279
3151641KERR 7
50/50
0.279
3151541CLOVER2
50/50
2.847
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.08
963041AG1-153 GEN
50/50
1.549
971845AH1-439 GEN
Solar/Wind Harmer
30.485
970285AG2-188 GEN
Solar/Wind Harmer
51.175
315657AE1-056 GEN
Solar/Wind Harmer
12.95
946301AF1-294 GEN
Solar/Wind Harmer
6.911
961791AG1-021 GEN
Solar/Wind Harmer
3.362
970683AG2-441 GEN
Solar/Wind Harmer
20.935
970681AG2-440 GEN
Solar/Wind Harmer
16.748
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.574
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.327
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.619
970865AG2-541 GEN
Solar/Wind Harmer
3.009
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.287
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.577
970163AG2-111 GEN
Solar/Wind Harmer
0.551
971967AH1-528 GEN
Solar/Wind Harmer
10.885
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.037
970581AG2-369 GEN
Solar/Wind Harmer
2.612
270494AE1-108_GEN
Solar/Wind Helper
4.476
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
964791AG1-342 GEN
Solar/Wind Harmer
2.755
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.837
970933AG2-581 GEN
Solar/Wind Harmer
6.964
316181AB2-040 GEN
Solar/Wind Harmer
0.107
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.763
3145593CAROLNA
Solar/Wind Harmer
0.088
3145783HORNRTN
Solar/Wind Harmer
1.221
3145783HORNRTN
Solar/Wind Harmer
0.977
3145783HORNRTN
Solar/Wind Harmer
0.305
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.284
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.338
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146776BUCKING
Solar/Wind Helper
3.475
3146776BUCKING
Solar/Wind Helper
0.282
315821AE2-092 GEN
Solar/Wind Helper
2.978
NYPJM->LTFIMP_NY
CLTF
0.298
LAGNLTFEXP_LAGN->PJM
CLTF
1.976
LGEELTFEXP_LGEE->PJM
CLTF
0.232
WECLTFEXP_WEC->PJM
CLTF
0.123
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.656
TVALTFEXP_TVA->PJM
CLTF
0.971
CPLELTFEXP_CPLE->PJM
CLTF
3.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.54
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.153
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
0.756
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:183.2 %
Rating:571.52 MVA
Rating Type:B
MVA to Mitigate:1047.0
MW Contribution:3.74
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.227
3151531CLOVER1
50/50
3.295
3151601KERR 3
50/50
0.314
3151581KERR 1
50/50
0.112
3147043LAWRENC
50/50
1.231
3151261ROARAP2
50/50
0.11
3151051BRUNSWICKS1
50/50
2.296
3151021BRUNSWICKG1
50/50
1.106
971451AH1-221 GEN
50/50
3.36
315243AE2-183_GT3
50/50
1.355
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
972003AH1-546 GEN
Solar/Wind Harmer
35.869
316322AB2-045
Solar/Wind Harmer
0.006
3146776BUCKING
Solar/Wind Harmer
0.276
3146926FARMVIL
Solar/Wind Harmer
0.322
963171AG1-166 GEN
Solar/Wind Harmer
1.937
971563AH1-280 GEN
Solar/Wind Harmer
3.874
970685AG2-442 GEN
Solar/Wind Harmer
24.468
962491AG1-098 GEN
Solar/Wind Harmer
11.913
316237AB2-079_GEN
Solar/Wind Harmer
0.002
315693AD1-088 GEN
Solar/Wind Harmer
9.538
970401AG2-262 GEN
Solar/Wind Harmer
0.936
957481AF2-042 GEN
Solar/Wind Harmer
40.345
315687AD1-152 GEN
Solar/Wind Harmer
0.005
971065AG2-659 GEN
Solar/Wind Harmer
5.693
316129AC1-054 GEN
Solar/Wind Harmer
0.488
971795AH1-408 GEN
Solar/Wind Harmer
7.841
316003AC1-222 GEN
Solar/Wind Harmer
0.003
960081AF2-299 GEN
Solar/Wind Harmer
0.907
3145783HORNRTN
Solar/Wind Harmer
0.086
316190AA2-174 GEN
Solar/Wind Harmer
0
970919AG2-571 GEN
Solar/Wind Harmer
2.909
970087AG2-069 GEN
Solar/Wind Harmer
6.525
316212AC1-099_GEN
Solar/Wind Harmer
0.386
3146263WOODLND
Solar/Wind Harmer
0.073
316011AB1-132 GEN
Solar/Wind Harmer
1.323
316023GEN1_S
Solar/Wind Harmer
0.163
962571AG1-106 GEN
Solar/Wind Harmer
1.036
3145796HORNRTN
Solar/Wind Harmer
0.238
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.285
3145893MURPHYS
Solar/Wind Harmer
0.282
3145893MURPHYS
Solar/Wind Harmer
0.313
315722AD1-056 GEN
Solar/Wind Harmer
0.446
3145823KELFORD
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.056
316359AB2-059 GEN
Solar/Wind Harmer
0.25
316049AB1-081 GEN
Solar/Wind Harmer
0.399
3142053HEARTS
Solar/Wind Harmer
0.123
3146173TUNIS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.068
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3146083TARBORO
Solar/Wind Harmer
0.067
3145493TOT1
Solar/Wind Harmer
0.299
940641AE2-051 GEN
Solar/Wind Harmer
5.379
316494AC1-189 GEN
Solar/Wind Harmer
0.223
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3146293MARTNCO
Solar/Wind Harmer
0.059
939411AE1-173 GEN
Solar/Wind Harmer
26.834
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
971547AH1-271 GEN
Solar/Wind Harmer
1.311
3145663CRESWEL
Solar/Wind Harmer
0.162
971163AH1-040 GEN
Solar/Wind Harmer
4.625
316336AC2-165 C
Solar/Wind Helper
1.515
3144293JTRSVLE
50/50
1.227
970413AG2-270 GEN
50/50
14.381
3151591KERR 2
50/50
0.314
3151261ROARAP2
50/50
0.107
3151031BRUNSWICKG2
50/50
1.106
3151391GASTONA
50/50
0.197
3151411GASTONB
50/50
0.197
3146776BUCKING
Solar/Wind Harmer
0.249
3146926FARMVIL
Solar/Wind Harmer
0.322
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.194
3147133PAMPLIN
Solar/Wind Harmer
1.217
971193AH1-056 GEN
Solar/Wind Harmer
23.622
963181AG1-167 GEN
Solar/Wind Harmer
1.453
959311AF2-222 GEN
Solar/Wind Harmer
26.742
970257AG2-171 GEN
Solar/Wind Harmer
9.28
315785AD2-033 C
Solar/Wind Harmer
2.237
964241AG1-285 GEN
Solar/Wind Harmer
15.699
316131AB2-060 GEN
Solar/Wind Harmer
0.665
316478AD1-087 GEN
Solar/Wind Harmer
0.537
316486AD2-202 GEN
Solar/Wind Harmer
0.158
3147043LAWRENC
Solar/Wind Harmer
0.077
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
5.394
971683AH1-343 GEN
Solar/Wind Harmer
4.007
313506AB2-031 GEN
Solar/Wind Harmer
0.283
316283AC2-100 C
Solar/Wind Harmer
0.161
970917AG2-570 GEN
Solar/Wind Harmer
7.271
316210AC1-098 GEN
Solar/Wind Harmer
0.691
316327AA2-057 GEN
Solar/Wind Harmer
0.111
3146263WOODLND
Solar/Wind Harmer
0.073
316365GEN2_N
Solar/Wind Harmer
0.163
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3145796HORNRTN
Solar/Wind Harmer
0.289
3145796HORNRTN
Solar/Wind Harmer
0.072
3146233WITAKRS
Solar/Wind Harmer
0.36
3146233WITAKRS
Solar/Wind Harmer
0.049
3138543CONSLDL
Solar/Wind Harmer
0.047
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
3145893MURPHYS
Solar/Wind Harmer
0.118
3145893MURPHYS
Solar/Wind Harmer
0.07
315724AD1-057 GEN
Solar/Wind Harmer
0.264
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.07
957521AF2-046 GEN
Solar/Wind Harmer
5.218
961681AG1-008 GEN
Solar/Wind Harmer
5.218
3145543BTLEBRO
Solar/Wind Harmer
0.07
3145543BTLEBRO
Solar/Wind Harmer
0.07
971623AH1-311 GEN
Solar/Wind Harmer
0.139
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
4.894
316463AE2-346 GEN
Solar/Wind Harmer
0.059
316140AB2-099
Solar/Wind Harmer
0.024
962331AG1-082 GEN
Solar/Wind Harmer
0.731
3146073TAR RVR
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.067
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3156021HOLLOMANSOL
Solar/Wind Harmer
0.29
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.741
3145963POPLR C
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.061
315737AD1-076 GEN
Solar/Wind Harmer
0.769
971157AH1-035 GEN
Solar/Wind Harmer
0.714
315614AA2-178 GEN
Solar/Wind Harmer
0.331
3145273HOLLAND
Solar/Wind Harmer
0.043
316313AB2-026
Solar/Wind Helper
0.362
316258AE1-075 C
Solar/Wind Helper
0.326
316405AF2-144 C
Solar/Wind Helper
0.271
3148013FISHERV
Solar/Wind Helper
0.126
3144293JTRSVLE
50/50
1.227
3144293JTRSVLE
50/50
1.033
970535AG2-341 GEN
50/50
3.148
3152661PLYWOOD A
50/50
0.306
3151041BRUNSWICKG3
50/50
1.106
972187AH1-678 GEN
50/50
2.539
315242AE2-183_GT2
50/50
1.355
315241AE2-183_GT1
50/50
1.346
972185AH1-677 GEN
50/50
4.884
970533AG2-339 GEN
50/50
6.883
970531AG2-338 GEN
50/50
2.753
3151361ROSEMG1
50/50
0.26
3151371ROSEMS1
50/50
0.161
3151381ROSEMG2
50/50
0.122
3146776BUCKING
Solar/Wind Harmer
2.762
3146776BUCKING
Solar/Wind Harmer
0.224
970301AG2-198 GEN
Solar/Wind Harmer
16.775
3147133PAMPLIN
Solar/Wind Harmer
0.388
3147133PAMPLIN
Solar/Wind Harmer
0.31
958211AF2-115 GEN
Solar/Wind Harmer
4.358
963191AG1-168 GEN
Solar/Wind Harmer
1.453
971741AH1-377 GEN
Solar/Wind Harmer
34.576
316034AC1-036 C
Solar/Wind Harmer
0.021
970323AG2-213 GEN
Solar/Wind Harmer
12.374
971775AH1-396 GEN
Solar/Wind Harmer
0.464
313527AB2-043 GEN
Solar/Wind Harmer
0.003
962561AG1-105 GEN
Solar/Wind Harmer
7.996
939181AE1-148 GEN
Solar/Wind Harmer
7.758
964791AG1-342 GEN
Solar/Wind Harmer
3.064
3146843MT LREL
Solar/Wind Harmer
0.159
3146843MT LREL
Solar/Wind Harmer
0.159
970099AG2-077 GEN
Solar/Wind Harmer
16.138
970933AG2-581 GEN
Solar/Wind Harmer
8.941
316181AB2-040 GEN
Solar/Wind Harmer
0.133
3145593CAROLNA
Solar/Wind Harmer
0.088
3145593CAROLNA
Solar/Wind Harmer
0.088
966811AG1-552 GEN
Solar/Wind Harmer
0.955
3145593CAROLNA
Solar/Wind Harmer
0.11
3145783HORNRTN
Solar/Wind Harmer
1.535
3145783HORNRTN
Solar/Wind Harmer
1.228
3145783HORNRTN
Solar/Wind Harmer
0.384
3145783HORNRTN
Solar/Wind Harmer
0.153
316426AA2-053 GEN
Solar/Wind Harmer
0.285
316222AC1-221 GEN
Solar/Wind Harmer
0.347
316274AC1-208 GEN
Solar/Wind Harmer
0.401
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
0.043
942751AE2-291 GEN
Solar/Wind Harmer
3.936
3145796HORNRTN
Solar/Wind Harmer
0.217
3145893MURPHYS
Solar/Wind Harmer
0.472
3145893MURPHYS
Solar/Wind Harmer
0.127
316263AC1-034 GEN
Solar/Wind Harmer
2.649
3146173TUNIS
Solar/Wind Harmer
0.069
3146173TUNIS
Solar/Wind Harmer
0.069
961601AG1-000A GEN
Solar/Wind Harmer
1.224
3145493TOT1
Solar/Wind Harmer
0.156
3145453TOT5
Solar/Wind Harmer
0.094
3145603CNETO
Solar/Wind Harmer
0.062
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.064
3144356SAPONY
Solar/Wind Harmer
0.516
316065AD1-022 GEN
Solar/Wind Harmer
2.802
315742AE1-103 GEN
Solar/Wind Harmer
0.001
315821AE2-092 GEN
Solar/Wind Helper
2.989
3151541CLOVER2
50/50
3.28
3151611KERR 4
50/50
0.314
3151621KERR 5
50/50
0.314
3151631KERR 6
50/50
0.314
3151641KERR 7
50/50
0.314
3151281ROARAP4
50/50
0.107
3151281ROARAP4
50/50
0.1
963041AG1-153 GEN
50/50
2.24
315244AE2-183_ST
50/50
2.342
971845AH1-439 GEN
Solar/Wind Harmer
30.733
970285AG2-188 GEN
Solar/Wind Harmer
51.665
315657AE1-056 GEN
Solar/Wind Harmer
13.38
946301AF1-294 GEN
Solar/Wind Harmer
7.167
961791AG1-021 GEN
Solar/Wind Harmer
3.487
970683AG2-441 GEN
Solar/Wind Harmer
21.847
970681AG2-440 GEN
Solar/Wind Harmer
17.477
3144303KENBRDG
Solar/Wind Harmer
0.232
971443AH1-215 GEN
Solar/Wind Harmer
4.818
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
316118AC1-105 GEN
Solar/Wind Harmer
0.368
3147173SINAI
Solar/Wind Harmer
0.126
3147243WELCO
Solar/Wind Harmer
0.079
970831AG2-522 GEN
Solar/Wind Harmer
5.363
970865AG2-541 GEN
Solar/Wind Harmer
3.482
971967AH1-528 GEN
Solar/Wind Harmer
15.038
316087AB2-174 GEN
Solar/Wind Harmer
0.003
3137643SOCKMAN
Solar/Wind Harmer
0.358
316123AC1-075 GEN
Solar/Wind Harmer
0.114
970165AG2-112 GEN
Solar/Wind Harmer
0.675
970163AG2-111 GEN
Solar/Wind Harmer
0.644
315607AA1-063A GEN
Solar/Wind Harmer
0.167
970085AG2-068 GEN
Solar/Wind Harmer
4.35
970581AG2-369 GEN
Solar/Wind Harmer
3.741
3146043SEABORD
Solar/Wind Harmer
0.081
970673AG2-436 GEN
Solar/Wind Harmer
17.164
970673AG2-436 GEN
Solar/Wind Harmer
11.442
941031AE2-094 GEN
Solar/Wind Harmer
14.261
944011AF1-069 GEN
Solar/Wind Harmer
4.66
315652AC1-086 GEN
Solar/Wind Harmer
8.006
3146033SCOT NK
Solar/Wind Harmer
0.29
3145796HORNRTN
Solar/Wind Harmer
0.231
3145796HORNRTN
Solar/Wind Harmer
0.029
965291AG1-394 GEN
Solar/Wind Harmer
0.319
316319Z2-044 C
Solar/Wind Harmer
0
3145893MURPHYS
Solar/Wind Harmer
0.19
3145893MURPHYS
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
0.143
3145513AHOSKIE
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.136
3145683EARLEYS
Solar/Wind Harmer
0.068
3145683EARLEYS
Solar/Wind Harmer
0.068
3145573BETHELC
Solar/Wind Harmer
0.067
3145573BETHELC
Solar/Wind Harmer
0.067
316420AA1-050 GEN
Solar/Wind Harmer
0.002
957861AF2-080 GEN
Solar/Wind Harmer
2.845
316005AA1-067
Solar/Wind Harmer
0.069
3145746EVERETS
Solar/Wind Harmer
0.257
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
970181AG2-120 GEN
Solar/Wind Harmer
0.803
315814AE2-033 C
Solar/Wind Harmer
4.928
316315AB2-025 C
Solar/Wind Harmer
0.05
3146206CASHIE
Solar/Wind Harmer
0.061
970601AG2-382 GEN
Solar/Wind Harmer
2.295
315732AD1-074 GEN1
Solar/Wind Harmer
0.344
315733AD1-074 GEN2
Solar/Wind Harmer
0.344
315735AD1-075 GEN1
Solar/Wind Harmer
0.172
3130546PLYMOUTH
Solar/Wind Harmer
0.059
315816AE2-034 GEN
Solar/Wind Harmer
0.248
270494AE1-108_GEN
Solar/Wind Helper
4.456
3138266HYDRAULIC
Solar/Wind Helper
0.009
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.076
3148013FISHERV
Solar/Wind Helper
0.072
NYPJM->LTFIMP_NY
CLTF
0.491
LGEELTFEXP_LGEE->PJM
CLTF
0.351
LAGNLTFEXP_LAGN->PJM
CLTF
2.721
WECLTFEXP_WEC->PJM
CLTF
0.183
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.095
TVALTFEXP_TVA->PJM
CLTF
1.342
CPLELTFEXP_CPLE->PJM
CLTF
4.932
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.244
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.478
MECLTFEXP_MEC->PJM
CLTF
1.093
SIGELTFEXP_SIGE->PJM
CLTF
0.031

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#1377_05J.FERR 765_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#1377_05J.FERR 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:137.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:957.97
MW Contribution:3.71
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.195
3151601KERR 3
50/50
0.288
3151581KERR 1
50/50
0.103
3151531CLOVER1
50/50
2.951
3147043LAWRENC
50/50
1.104
972003AH1-546 GEN
Solar/Wind Harmer
47.347
316322AB2-045
Solar/Wind Harmer
2.6
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.967
971563AH1-280 GEN
Solar/Wind Harmer
4.967
970685AG2-442 GEN
Solar/Wind Harmer
31.227
962491AG1-098 GEN
Solar/Wind Harmer
14.504
316237AB2-079_GEN
Solar/Wind Harmer
0.638
315693AD1-088 GEN
Solar/Wind Harmer
10.264
970401AG2-262 GEN
Solar/Wind Harmer
1.084
957481AF2-042 GEN
Solar/Wind Harmer
46.952
315687AD1-152 GEN
Solar/Wind Harmer
1.686
971065AG2-659 GEN
Solar/Wind Harmer
6.782
316129AC1-054 GEN
Solar/Wind Harmer
1.152
316003AC1-222 GEN
Solar/Wind Harmer
1.16
971795AH1-408 GEN
Solar/Wind Harmer
8.774
960081AF2-299 GEN
Solar/Wind Harmer
1.019
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.098
316212AC1-099_GEN
Solar/Wind Harmer
0.612
970919AG2-571 GEN
Solar/Wind Harmer
2.186
970087AG2-069 GEN
Solar/Wind Harmer
6.469
3146233WITAKRS
Solar/Wind Harmer
-0.027
3146263WOODLND
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.401
962571AG1-106 GEN
Solar/Wind Harmer
0.963
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
316359AB2-059 GEN
Solar/Wind Harmer
0.896
316049AB1-081 GEN
Solar/Wind Harmer
0.717
3142053HEARTS
Solar/Wind Harmer
0.078
315722AD1-056 GEN
Solar/Wind Harmer
0.692
316023GEN1_S
Solar/Wind Harmer
0.442
3145823KELFORD
Solar/Wind Harmer
-0.006
3145893MURPHYS
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
0.19
961671AG1-007 GEN
Solar/Wind Harmer
0.08
3146083TARBORO
Solar/Wind Harmer
-0.006
3145493TOT1
Solar/Wind Harmer
0.188
316336AC2-165 C
Solar/Wind Helper
1.427
3144293JTRSVLE
50/50
1.195
3144293JTRSVLE
50/50
1.006
970535AG2-341 GEN
50/50
2.93
3152661PLYWOOD A
50/50
0.279
3146776BUCKING
Solar/Wind Harmer
-0.308
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.483
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.209
963191AG1-168 GEN
Solar/Wind Harmer
3.725
971741AH1-377 GEN
Solar/Wind Harmer
43.964
316034AC1-036 C
Solar/Wind Harmer
0.583
970323AG2-213 GEN
Solar/Wind Harmer
15.694
971775AH1-396 GEN
Solar/Wind Harmer
2.235
313527AB2-043 GEN
Solar/Wind Harmer
3.534
962561AG1-105 GEN
Solar/Wind Harmer
9.782
939181AE1-148 GEN
Solar/Wind Harmer
9.427
964791AG1-342 GEN
Solar/Wind Harmer
3.547
3146843MT LREL
Solar/Wind Harmer
-0.017
3146843MT LREL
Solar/Wind Harmer
-0.017
970099AG2-077 GEN
Solar/Wind Harmer
18.781
970933AG2-581 GEN
Solar/Wind Harmer
9.57
316181AB2-040 GEN
Solar/Wind Harmer
1.222
316222AC1-221 GEN
Solar/Wind Harmer
0.854
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.948
3145593CAROLNA
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.979
3145783HORNRTN
Solar/Wind Harmer
0.783
3145783HORNRTN
Solar/Wind Harmer
0.245
3145783HORNRTN
Solar/Wind Harmer
0.098
316426AA2-053 GEN
Solar/Wind Harmer
0.81
316274AC1-208 GEN
Solar/Wind Harmer
0.791
942751AE2-291 GEN
Solar/Wind Harmer
4.521
972187AH1-678 GEN
Adder
1.767
972185AH1-677 GEN
Adder
3.338
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
316263AC1-034 GEN
Solar/Wind Harmer
3.115
961601AG1-000A GEN
Solar/Wind Harmer
2.573
3145893MURPHYS
Solar/Wind Harmer
0.179
3145893MURPHYS
Solar/Wind Harmer
-0.012
3145493TOT1
Solar/Wind Harmer
0.098
3145453TOT5
Solar/Wind Harmer
0.059
3145603CNETO
Solar/Wind Harmer
0.039
315821AE2-092 GEN
Solar/Wind Helper
2.966
3144293JTRSVLE
50/50
1.195
3151591KERR 2
50/50
0.288
970413AG2-270 GEN
50/50
12.878
3146776BUCKING
Solar/Wind Harmer
-0.028
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.6
970909AG2-566 GEN
Solar/Wind Harmer
4.079
3147133PAMPLIN
Solar/Wind Harmer
-0.133
971193AH1-056 GEN
Solar/Wind Harmer
26.601
963181AG1-167 GEN
Solar/Wind Harmer
3.725
959311AF2-222 GEN
Solar/Wind Harmer
34.052
970257AG2-171 GEN
Solar/Wind Harmer
11.771
315785AD2-033 C
Solar/Wind Harmer
6.728
964241AG1-285 GEN
Solar/Wind Harmer
19.662
316131AB2-060 GEN
Solar/Wind Harmer
2.419
316478AD1-087 GEN
Solar/Wind Harmer
1.34
316486AD2-202 GEN
Solar/Wind Harmer
0.392
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.389
960061AF2-297 GEN
Solar/Wind Harmer
6.446
971683AH1-343 GEN
Solar/Wind Harmer
4.749
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.704
316283AC2-100 C
Solar/Wind Harmer
0.785
316210AC1-098 GEN
Solar/Wind Harmer
1.101
316327AA2-057 GEN
Solar/Wind Harmer
0.705
970917AG2-570 GEN
Solar/Wind Harmer
17.269
3146233WITAKRS
Solar/Wind Harmer
0.143
3146233WITAKRS
Solar/Wind Harmer
-0.005
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.38
316365GEN2_N
Solar/Wind Harmer
0.442
961601AG1-000A GEN
Solar/Wind Harmer
2.606
316317KELFORD C
Solar/Wind Harmer
0.305
3145823KELFORD
Solar/Wind Harmer
-0.006
3156081AA2-088 GEN
Solar/Wind Harmer
2.082
3145893MURPHYS
Solar/Wind Harmer
0.045
3145893MURPHYS
Solar/Wind Harmer
-0.006
957521AF2-046 GEN
Solar/Wind Harmer
5.021
961681AG1-008 GEN
Solar/Wind Harmer
5.021
3146073TAR RVR
Solar/Wind Harmer
-0.006
3146083TARBORO
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.333
316258AE1-075 C
Solar/Wind Helper
0.299
316405AF2-144 C
Solar/Wind Helper
0.249
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.288
3151621KERR 5
50/50
0.288
3151631KERR 6
50/50
0.288
3151641KERR 7
50/50
0.288
3151541CLOVER2
50/50
2.937
971845AH1-439 GEN
Solar/Wind Harmer
40.264
970285AG2-188 GEN
Solar/Wind Harmer
63.811
315657AE1-056 GEN
Solar/Wind Harmer
15.96
946301AF1-294 GEN
Solar/Wind Harmer
10.183
961791AG1-021 GEN
Solar/Wind Harmer
4.967
970683AG2-441 GEN
Solar/Wind Harmer
27.881
970681AG2-440 GEN
Solar/Wind Harmer
22.305
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.107
316239AB2-077_GEN
Solar/Wind Harmer
0.638
316238AB2-078_GEN
Solar/Wind Harmer
0.638
316118AC1-105 GEN
Solar/Wind Harmer
1.013
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.344
970865AG2-541 GEN
Solar/Wind Harmer
4.105
946281AF1-292 GEN
Solar/Wind Harmer
0.203
316087AB2-174 GEN
Solar/Wind Harmer
1.262
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.891
970165AG2-112 GEN
Solar/Wind Harmer
0.785
970163AG2-111 GEN
Solar/Wind Harmer
0.749
971967AH1-528 GEN
Solar/Wind Harmer
15.159
315607AA1-063A GEN
Solar/Wind Harmer
0.776
3146043SEABORD
Solar/Wind Harmer
-0.008
970085AG2-068 GEN
Solar/Wind Harmer
4.313
970581AG2-369 GEN
Solar/Wind Harmer
3.709
316319Z2-044 C
Solar/Wind Harmer
0.377
3146033SCOT NK
Solar/Wind Harmer
-0.027
315652AC1-086 GEN
Solar/Wind Harmer
7.536
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
965291AG1-394 GEN
Solar/Wind Harmer
0.58
970673AG2-436 GEN
Solar/Wind Harmer
13.57
970673AG2-436 GEN
Solar/Wind Harmer
6.871
316318V4-068
Solar/Wind Harmer
0.16
3145893MURPHYS
Solar/Wind Harmer
-0.017
3145893MURPHYS
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
3145573BETHELC
Solar/Wind Harmer
-0.006
270494AE1-108_GEN
Solar/Wind Helper
4.47
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
NYPJM->LTFIMP_NY
CLTF
0.305
LGEELTFEXP_LGEE->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
2.472
WECLTFEXP_WEC->PJM
CLTF
0.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
10.204
TVALTFEXP_TVA->PJM
CLTF
1.2
CPLELTFEXP_CPLE->PJM
CLTF
4.525
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.338
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.871
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.899
MECLTFEXP_MEC->PJM
CLTF
0.811
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 2003-205_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 2003-205_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:133.52 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:933.31
MW Contribution:3.61
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.189
3151601KERR 3
50/50
0.284
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.913
3147043LAWRENC
50/50
1.1
972003AH1-546 GEN
Solar/Wind Harmer
47.254
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.031
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.943
971563AH1-280 GEN
Solar/Wind Harmer
4.943
970685AG2-442 GEN
Solar/Wind Harmer
31.058
962491AG1-098 GEN
Solar/Wind Harmer
14.389
316237AB2-079_GEN
Solar/Wind Harmer
0.632
315693AD1-088 GEN
Solar/Wind Harmer
10.178
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
46.433
315687AD1-152 GEN
Solar/Wind Harmer
1.654
971065AG2-659 GEN
Solar/Wind Harmer
6.674
316129AC1-054 GEN
Solar/Wind Harmer
1.134
971795AH1-408 GEN
Solar/Wind Harmer
8.763
316003AC1-222 GEN
Solar/Wind Harmer
1.138
960081AF2-299 GEN
Solar/Wind Harmer
1.022
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.097
316212AC1-099_GEN
Solar/Wind Harmer
0.589
970919AG2-571 GEN
Solar/Wind Harmer
2.13
970087AG2-069 GEN
Solar/Wind Harmer
6.297
316023GEN1_S
Solar/Wind Harmer
0.451
316011AB1-132 GEN
Solar/Wind Harmer
1.384
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
-0.026
315722AD1-056 GEN
Solar/Wind Harmer
0.665
316336AC2-165 C
Solar/Wind Helper
1.458
3144293JTRSVLE
50/50
1.189
3144293JTRSVLE
50/50
1.001
970535AG2-341 GEN
50/50
2.895
3152661PLYWOOD A
50/50
0.274
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.395
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.179
963191AG1-168 GEN
Solar/Wind Harmer
3.707
971741AH1-377 GEN
Solar/Wind Harmer
43.759
316034AC1-036 C
Solar/Wind Harmer
0.58
970323AG2-213 GEN
Solar/Wind Harmer
15.596
971775AH1-396 GEN
Solar/Wind Harmer
2.221
313527AB2-043 GEN
Solar/Wind Harmer
3.501
962561AG1-105 GEN
Solar/Wind Harmer
9.651
939181AE1-148 GEN
Solar/Wind Harmer
9.294
964791AG1-342 GEN
Solar/Wind Harmer
3.496
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.573
970933AG2-581 GEN
Solar/Wind Harmer
9.469
316181AB2-040 GEN
Solar/Wind Harmer
1.215
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.932
3145593CAROLNA
Solar/Wind Harmer
0.069
3145783HORNRTN
Solar/Wind Harmer
0.96
3145783HORNRTN
Solar/Wind Harmer
0.768
3145783HORNRTN
Solar/Wind Harmer
0.24
3145783HORNRTN
Solar/Wind Harmer
0.096
316222AC1-221 GEN
Solar/Wind Harmer
0.8
316426AA2-053 GEN
Solar/Wind Harmer
0.794
316274AC1-208 GEN
Solar/Wind Harmer
0.763
942751AE2-291 GEN
Solar/Wind Harmer
4.488
972187AH1-678 GEN
Adder
1.739
972185AH1-677 GEN
Adder
3.291
3145796HORNRTN
Solar/Wind Harmer
-0.02
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3151611KERR 4
50/50
0.284
3151621KERR 5
50/50
0.284
3151631KERR 6
50/50
0.284
3151641KERR 7
50/50
0.284
3151541CLOVER2
50/50
2.899
971845AH1-439 GEN
Solar/Wind Harmer
40.166
970285AG2-188 GEN
Solar/Wind Harmer
63.65
315657AE1-056 GEN
Solar/Wind Harmer
15.889
946301AF1-294 GEN
Solar/Wind Harmer
10.133
961791AG1-021 GEN
Solar/Wind Harmer
4.943
970683AG2-441 GEN
Solar/Wind Harmer
27.73
970681AG2-440 GEN
Solar/Wind Harmer
22.184
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.068
316239AB2-077_GEN
Solar/Wind Harmer
0.632
316238AB2-078_GEN
Solar/Wind Harmer
0.632
316118AC1-105 GEN
Solar/Wind Harmer
0.995
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.242
970865AG2-541 GEN
Solar/Wind Harmer
4.039
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.259
3137643SOCKMAN
Solar/Wind Harmer
-0.034
316123AC1-075 GEN
Solar/Wind Harmer
0.881
970165AG2-112 GEN
Solar/Wind Harmer
0.776
3144293JTRSVLE
50/50
1.189
3151591KERR 2
50/50
0.284
970413AG2-270 GEN
50/50
12.71
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.572
970909AG2-566 GEN
Solar/Wind Harmer
4.062
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.482
963181AG1-167 GEN
Solar/Wind Harmer
3.707
959311AF2-222 GEN
Solar/Wind Harmer
33.848
970257AG2-171 GEN
Solar/Wind Harmer
11.697
315785AD2-033 C
Solar/Wind Harmer
6.684
964241AG1-285 GEN
Solar/Wind Harmer
19.507
316131AB2-060 GEN
Solar/Wind Harmer
2.398
316478AD1-087 GEN
Solar/Wind Harmer
1.322
316486AD2-202 GEN
Solar/Wind Harmer
0.387
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.38
960061AF2-297 GEN
Solar/Wind Harmer
6.313
971683AH1-343 GEN
Solar/Wind Harmer
4.664
966621AG1-532 GEN
Solar/Wind Harmer
0.184
313506AB2-031 GEN
Solar/Wind Harmer
0.7
316283AC2-100 C
Solar/Wind Harmer
0.734
316210AC1-098 GEN
Solar/Wind Harmer
1.061
970917AG2-570 GEN
Solar/Wind Harmer
16.827
316365GEN2_N
Solar/Wind Harmer
0.451
316327AA2-057 GEN
Solar/Wind Harmer
0.674
3146263WOODLND
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3146233WITAKRS
Solar/Wind Harmer
0.136
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.366
316313AB2-026
Solar/Wind Helper
0.342
316258AE1-075 C
Solar/Wind Helper
0.308
316405AF2-144 C
Solar/Wind Helper
0.257
3148013FISHERV
Solar/Wind Helper
0.124
970163AG2-111 GEN
Solar/Wind Harmer
0.74
971967AH1-528 GEN
Solar/Wind Harmer
14.996
315607AA1-063A GEN
Solar/Wind Harmer
0.76
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.198
970581AG2-369 GEN
Solar/Wind Harmer
3.61
315652AC1-086 GEN
Solar/Wind Harmer
7.443
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.003
3146033SCOT NK
Solar/Wind Harmer
-0.026
316319Z2-044 C
Solar/Wind Harmer
0.358
970673AG2-436 GEN
Solar/Wind Harmer
13.401
970673AG2-436 GEN
Solar/Wind Harmer
6.785
965291AG1-394 GEN
Solar/Wind Harmer
0.563
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.075
3148013FISHERV
Solar/Wind Helper
0.072
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.986
NYPJM->LTFIMP_NY
CLTF
0.325
LGEELTFEXP_LGEE->PJM
CLTF
0.24
LAGNLTFEXP_LAGN->PJM
CLTF
2.053
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.953
WECLTFEXP_WEC->PJM
CLTF
0.127
TVALTFEXP_TVA->PJM
CLTF
1.009
CPLELTFEXP_CPLE->PJM
CLTF
3.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.902
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.279
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.343
MECLTFEXP_MEC->PJM
CLTF
0.782
SIGELTFEXP_SIGE->PJM
CLTF
0.022

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 249-69_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 249-69_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:129.32 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:903.97
MW Contribution:3.54
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.282
3151581KERR 1
50/50
0.101
3151531CLOVER1
50/50
2.892
3147043LAWRENC
50/50
1.085
972003AH1-546 GEN
Solar/Wind Harmer
47.255
316322AB2-045
Solar/Wind Harmer
2.593
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.933
971563AH1-280 GEN
Solar/Wind Harmer
4.933
970685AG2-442 GEN
Solar/Wind Harmer
30.981
962491AG1-098 GEN
Solar/Wind Harmer
14.318
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.124
970401AG2-262 GEN
Solar/Wind Harmer
1.062
957481AF2-042 GEN
Solar/Wind Harmer
46.073
315687AD1-152 GEN
Solar/Wind Harmer
1.641
971065AG2-659 GEN
Solar/Wind Harmer
6.611
316129AC1-054 GEN
Solar/Wind Harmer
1.122
316003AC1-222 GEN
Solar/Wind Harmer
1.129
971795AH1-408 GEN
Solar/Wind Harmer
8.625
960081AF2-299 GEN
Solar/Wind Harmer
0.999
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.095
316212AC1-099_GEN
Solar/Wind Harmer
0.577
970919AG2-571 GEN
Solar/Wind Harmer
2.089
970087AG2-069 GEN
Solar/Wind Harmer
6.176
316023GEN1_S
Solar/Wind Harmer
0.435
3146263WOODLND
Solar/Wind Harmer
-0.006
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.282
970413AG2-270 GEN
50/50
12.618
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.563
970909AG2-566 GEN
Solar/Wind Harmer
4.055
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.433
963181AG1-167 GEN
Solar/Wind Harmer
3.7
959311AF2-222 GEN
Solar/Wind Harmer
33.751
970257AG2-171 GEN
Solar/Wind Harmer
11.662
315785AD2-033 C
Solar/Wind Harmer
6.662
964241AG1-285 GEN
Solar/Wind Harmer
19.425
316131AB2-060 GEN
Solar/Wind Harmer
2.386
316478AD1-087 GEN
Solar/Wind Harmer
1.313
316486AD2-202 GEN
Solar/Wind Harmer
0.384
3147043LAWRENC
Solar/Wind Harmer
-0.008
316248AF1-058 C
Solar/Wind Harmer
0.378
960061AF2-297 GEN
Solar/Wind Harmer
6.266
971683AH1-343 GEN
Solar/Wind Harmer
4.627
966621AG1-532 GEN
Solar/Wind Harmer
0.18
313506AB2-031 GEN
Solar/Wind Harmer
0.685
316283AC2-100 C
Solar/Wind Harmer
0.725
316210AC1-098 GEN
Solar/Wind Harmer
1.039
970917AG2-570 GEN
Solar/Wind Harmer
16.504
316327AA2-057 GEN
Solar/Wind Harmer
0.66
316365GEN2_N
Solar/Wind Harmer
0.435
3151611KERR 4
50/50
0.282
3151621KERR 5
50/50
0.282
3151631KERR 6
50/50
0.282
3151641KERR 7
50/50
0.282
3146263WOODLND
Solar/Wind Harmer
-0.006
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
0.133
3146233WITAKRS
Solar/Wind Harmer
-0.004
3138543CONSLDL
Solar/Wind Harmer
-0.004
316313AB2-026
Solar/Wind Helper
0.341
316258AE1-075 C
Solar/Wind Helper
0.307
316405AF2-144 C
Solar/Wind Helper
0.255
3148013FISHERV
Solar/Wind Helper
0.124
3151541CLOVER2
50/50
2.878
971845AH1-439 GEN
Solar/Wind Harmer
40.152
970285AG2-188 GEN
Solar/Wind Harmer
63.623
315657AE1-056 GEN
Solar/Wind Harmer
15.86
946301AF1-294 GEN
Solar/Wind Harmer
10.112
961791AG1-021 GEN
Solar/Wind Harmer
4.933
970683AG2-441 GEN
Solar/Wind Harmer
27.661
970681AG2-440 GEN
Solar/Wind Harmer
22.129
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.049
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.988
3147173SINAI
Solar/Wind Harmer
-0.012
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.176
970865AG2-541 GEN
Solar/Wind Harmer
4.007
946281AF1-292 GEN
Solar/Wind Harmer
0.199
316087AB2-174 GEN
Solar/Wind Harmer
1.232
3137643SOCKMAN
Solar/Wind Harmer
-0.033
316123AC1-075 GEN
Solar/Wind Harmer
0.874
970165AG2-112 GEN
Solar/Wind Harmer
0.769
970163AG2-111 GEN
Solar/Wind Harmer
0.734
971967AH1-528 GEN
Solar/Wind Harmer
14.744
315607AA1-063A GEN
Solar/Wind Harmer
0.745
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.118
970581AG2-369 GEN
Solar/Wind Harmer
3.541
315652AC1-086 GEN
Solar/Wind Harmer
7.239
3146033SCOT NK
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.02
3145796HORNRTN
Solar/Wind Harmer
-0.003
316319Z2-044 C
Solar/Wind Harmer
0.351
270494AE1-108_GEN
Solar/Wind Helper
4.481
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.999
970535AG2-341 GEN
50/50
2.877
3152661PLYWOOD A
50/50
0.272
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.357
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.166
963191AG1-168 GEN
Solar/Wind Harmer
3.7
971741AH1-377 GEN
Solar/Wind Harmer
43.663
316034AC1-036 C
Solar/Wind Harmer
0.578
970323AG2-213 GEN
Solar/Wind Harmer
15.549
971775AH1-396 GEN
Solar/Wind Harmer
2.214
313527AB2-043 GEN
Solar/Wind Harmer
3.483
962561AG1-105 GEN
Solar/Wind Harmer
9.593
316011AB1-132 GEN
Solar/Wind Harmer
1.346
962571AG1-106 GEN
Solar/Wind Harmer
0.925
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145796HORNRTN
Solar/Wind Harmer
-0.006
3146233WITAKRS
Solar/Wind Harmer
-0.025
316336AC2-165 C
Solar/Wind Helper
1.454
939181AE1-148 GEN
Solar/Wind Harmer
9.23
964791AG1-342 GEN
Solar/Wind Harmer
3.474
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.429
970933AG2-581 GEN
Solar/Wind Harmer
9.348
316181AB2-040 GEN
Solar/Wind Harmer
1.189
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.914
3145593CAROLNA
Solar/Wind Harmer
0.068
3145783HORNRTN
Solar/Wind Harmer
0.942
3145783HORNRTN
Solar/Wind Harmer
0.753
3145783HORNRTN
Solar/Wind Harmer
0.235
3145783HORNRTN
Solar/Wind Harmer
0.094
316222AC1-221 GEN
Solar/Wind Harmer
0.791
316426AA2-053 GEN
Solar/Wind Harmer
0.779
942751AE2-291 GEN
Solar/Wind Harmer
4.447
316274AC1-208 GEN
Solar/Wind Harmer
0.748
972187AH1-678 GEN
Adder
1.705
972185AH1-677 GEN
Adder
3.223
3145796HORNRTN
Solar/Wind Harmer
-0.019
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.006
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
315821AE2-092 GEN
Solar/Wind Helper
2.984
NYPJM->LTFIMP_NY
CLTF
0.319
LGEELTFEXP_LGEE->PJM
CLTF
0.233
LAGNLTFEXP_LAGN->PJM
CLTF
2.012
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.822
WECLTFEXP_WEC->PJM
CLTF
0.123
TVALTFEXP_TVA->PJM
CLTF
0.989
CPLELTFEXP_CPLE->PJM
CLTF
3.872
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.686
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.147
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.273
MECLTFEXP_MEC->PJM
CLTF
0.763
SIGELTFEXP_SIGE->PJM
CLTF
0.021

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:125.05 %
Rating:699.0 MVA
Rating Type:C
MVA to Mitigate:874.1
MW Contribution:3.46
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.186
3144293JTRSVLE
50/50
0.998
970535AG2-341 GEN
50/50
2.87
3152661PLYWOOD A
50/50
0.275
3146776BUCKING
Solar/Wind Harmer
-0.307
3146776BUCKING
Solar/Wind Harmer
-0.025
970301AG2-198 GEN
Solar/Wind Harmer
21.329
3147133PAMPLIN
Solar/Wind Harmer
-0.042
3147133PAMPLIN
Solar/Wind Harmer
-0.034
958211AF2-115 GEN
Solar/Wind Harmer
6.162
963191AG1-168 GEN
Solar/Wind Harmer
3.697
971741AH1-377 GEN
Solar/Wind Harmer
43.59
316034AC1-036 C
Solar/Wind Harmer
0.577
970323AG2-213 GEN
Solar/Wind Harmer
15.535
971775AH1-396 GEN
Solar/Wind Harmer
2.212
313527AB2-043 GEN
Solar/Wind Harmer
3.479
962561AG1-105 GEN
Solar/Wind Harmer
9.636
964791AG1-342 GEN
Solar/Wind Harmer
3.494
939181AE1-148 GEN
Solar/Wind Harmer
9.198
3146843MT LREL
Solar/Wind Harmer
-0.016
3146843MT LREL
Solar/Wind Harmer
-0.016
970099AG2-077 GEN
Solar/Wind Harmer
18.308
970933AG2-581 GEN
Solar/Wind Harmer
9.214
316181AB2-040 GEN
Solar/Wind Harmer
1.159
942751AE2-291 GEN
Solar/Wind Harmer
5.121
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
966811AG1-552 GEN
Solar/Wind Harmer
0.895
3145593CAROLNA
Solar/Wind Harmer
0.066
316222AC1-221 GEN
Solar/Wind Harmer
0.788
3145783HORNRTN
Solar/Wind Harmer
0.922
3145783HORNRTN
Solar/Wind Harmer
0.738
3145783HORNRTN
Solar/Wind Harmer
0.231
3145783HORNRTN
Solar/Wind Harmer
0.092
316426AA2-053 GEN
Solar/Wind Harmer
0.763
316274AC1-208 GEN
Solar/Wind Harmer
0.732
972187AH1-678 GEN
Adder
1.663
315821AE2-092 GEN
Solar/Wind Helper
2.985
3144293JTRSVLE
50/50
1.186
3151591KERR 2
50/50
0.281
970413AG2-270 GEN
50/50
12.559
3146776BUCKING
Solar/Wind Harmer
-0.027
3146926FARMVIL
Solar/Wind Harmer
-0.035
942461AE2-259 GEN
Solar/Wind Harmer
7.558
970909AG2-566 GEN
Solar/Wind Harmer
4.05
3147133PAMPLIN
Solar/Wind Harmer
-0.132
971193AH1-056 GEN
Solar/Wind Harmer
26.415
963181AG1-167 GEN
Solar/Wind Harmer
3.697
959311AF2-222 GEN
Solar/Wind Harmer
33.722
3151611KERR 4
50/50
0.281
3151621KERR 5
50/50
0.281
3151631KERR 6
50/50
0.281
3151641KERR 7
50/50
0.281
3151541CLOVER2
50/50
2.864
971845AH1-439 GEN
Solar/Wind Harmer
40.143
970285AG2-188 GEN
Solar/Wind Harmer
63.606
315657AE1-056 GEN
Solar/Wind Harmer
15.849
946301AF1-294 GEN
Solar/Wind Harmer
10.105
961791AG1-021 GEN
Solar/Wind Harmer
4.929
970683AG2-441 GEN
Solar/Wind Harmer
27.639
970681AG2-440 GEN
Solar/Wind Harmer
22.111
3144303KENBRDG
Solar/Wind Harmer
-0.025
971443AH1-215 GEN
Solar/Wind Harmer
6.044
316239AB2-077_GEN
Solar/Wind Harmer
0.628
316238AB2-078_GEN
Solar/Wind Harmer
0.628
316118AC1-105 GEN
Solar/Wind Harmer
0.998
3147173SINAI
Solar/Wind Harmer
-0.013
3147243WELCO
Solar/Wind Harmer
-0.008
970831AG2-522 GEN
Solar/Wind Harmer
6.123
970865AG2-541 GEN
Solar/Wind Harmer
4.251
316123AC1-075 GEN
Solar/Wind Harmer
0.968
3144293JTRSVLE
50/50
1.186
3151601KERR 3
50/50
0.281
3151581KERR 1
50/50
0.1
3151531CLOVER1
50/50
2.878
972003AH1-546 GEN
Solar/Wind Harmer
47.257
316322AB2-045
Solar/Wind Harmer
2.592
3146776BUCKING
Solar/Wind Harmer
-0.03
3146926FARMVIL
Solar/Wind Harmer
-0.035
963171AG1-166 GEN
Solar/Wind Harmer
4.929
971563AH1-280 GEN
Solar/Wind Harmer
4.929
970685AG2-442 GEN
Solar/Wind Harmer
30.955
962491AG1-098 GEN
Solar/Wind Harmer
14.261
316237AB2-079_GEN
Solar/Wind Harmer
0.628
315693AD1-088 GEN
Solar/Wind Harmer
10.081
970401AG2-262 GEN
Solar/Wind Harmer
1.068
957481AF2-042 GEN
Solar/Wind Harmer
45.769
315687AD1-152 GEN
Solar/Wind Harmer
1.638
971065AG2-659 GEN
Solar/Wind Harmer
6.564
316129AC1-054 GEN
Solar/Wind Harmer
1.114
3147043LAWRENC
Adder
1.008
316003AC1-222 GEN
Solar/Wind Harmer
1.162
971795AH1-408 GEN
Solar/Wind Harmer
8.467
960081AF2-299 GEN
Solar/Wind Harmer
0.97
3145783HORNRTN
Solar/Wind Harmer
-0.008
316190AA2-174 GEN
Solar/Wind Harmer
0.093
316212AC1-099_GEN
Solar/Wind Harmer
0.565
970919AG2-571 GEN
Solar/Wind Harmer
2.04
970087AG2-069 GEN
Solar/Wind Harmer
6.032
316336AC2-165 C
Solar/Wind Helper
1.446
970165AG2-112 GEN
Solar/Wind Harmer
0.853
970163AG2-111 GEN
Solar/Wind Harmer
0.813
946281AF1-292 GEN
Solar/Wind Harmer
0.193
316087AB2-174 GEN
Solar/Wind Harmer
1.199
3137643SOCKMAN
Solar/Wind Harmer
-0.032
971967AH1-528 GEN
Solar/Wind Harmer
14.441
315607AA1-063A GEN
Solar/Wind Harmer
0.73
3146043SEABORD
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.021
970581AG2-369 GEN
Solar/Wind Harmer
3.458
270494AE1-108_GEN
Solar/Wind Helper
4.516
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
970257AG2-171 GEN
Solar/Wind Harmer
11.651
315785AD2-033 C
Solar/Wind Harmer
6.656
964241AG1-285 GEN
Solar/Wind Harmer
19.405
316131AB2-060 GEN
Solar/Wind Harmer
2.383
316478AD1-087 GEN
Solar/Wind Harmer
1.306
316486AD2-202 GEN
Solar/Wind Harmer
0.383
316248AF1-058 C
Solar/Wind Harmer
0.383
960061AF2-297 GEN
Solar/Wind Harmer
6.356
3147043LAWRENC
Solar/Wind Harmer
-0.007
971683AH1-343 GEN
Solar/Wind Harmer
4.828
966621AG1-532 GEN
Solar/Wind Harmer
0.175
313506AB2-031 GEN
Solar/Wind Harmer
0.668
316283AC2-100 C
Solar/Wind Harmer
0.723
316210AC1-098 GEN
Solar/Wind Harmer
1.017
970917AG2-570 GEN
Solar/Wind Harmer
16.116
316327AA2-057 GEN
Solar/Wind Harmer
0.646
316313AB2-026
Solar/Wind Helper
0.338
316258AE1-075 C
Solar/Wind Helper
0.304
316405AF2-144 C
Solar/Wind Helper
0.253
3148013FISHERV
Solar/Wind Helper
0.124
NYPJM->LTFIMP_NY
CLTF
0.309
LGEELTFEXP_LGEE->PJM
CLTF
0.214
LAGNLTFEXP_LAGN->PJM
CLTF
1.942
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.684
WECLTFEXP_WEC->PJM
CLTF
0.113
TVALTFEXP_TVA->PJM
CLTF
0.953
CPLELTFEXP_CPLE->PJM
CLTF
3.818
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.791
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.144
MECLTFEXP_MEC->PJM
CLTF
0.716
SIGELTFEXP_SIGE->PJM
CLTF
0.02

Details for AH1-546 TP-6BREMO 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:DVP
Facility Description:
AH1-546 TP-6BREMO 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.94 %
Rating:571.52 MVA
Rating Type:A
MVA to Mitigate:679.77
MW Contribution:2.6
Bus #Bus NameTypeMW Contribution
3144293JTRSVLE
50/50
1.182
3151591KERR 2
50/50
0.278
970413AG2-270 GEN
50/50
12.466
3151261ROARAP2
50/50
0.085
3151031BRUNSWICKG2
50/50
0.762
3146776BUCKING
Solar/Wind Harmer
0.247
3146926FARMVIL
Solar/Wind Harmer
0.316
942461AE2-259 GEN
Solar/Wind Harmer
-0.003
970909AG2-566 GEN
Solar/Wind Harmer
4.043
3147133PAMPLIN
Solar/Wind Harmer
1.178
971193AH1-056 GEN
Solar/Wind Harmer
22.85
963181AG1-167 GEN
Solar/Wind Harmer
1.4
959311AF2-222 GEN
Solar/Wind Harmer
25.461
970257AG2-171 GEN
Solar/Wind Harmer
8.812
315785AD2-033 C
Solar/Wind Harmer
2.115
964241AG1-285 GEN
Solar/Wind Harmer
14.651
316131AB2-060 GEN
Solar/Wind Harmer
0.614
316478AD1-087 GEN
Solar/Wind Harmer
0.465
316486AD2-202 GEN
Solar/Wind Harmer
0.137
3147043LAWRENC
Solar/Wind Harmer
0.066
316248AF1-058 C
Solar/Wind Harmer
0.001
3144293JTRSVLE
50/50
1.182
3144293JTRSVLE
50/50
0.996
970535AG2-341 GEN
50/50
2.848
3152661PLYWOOD A
50/50
0.269
3151041BRUNSWICKG3
50/50
0.762
972187AH1-678 GEN
50/50
1.749
3146776BUCKING
Solar/Wind Harmer
2.741
3146776BUCKING
Solar/Wind Harmer
0.222
970301AG2-198 GEN
Solar/Wind Harmer
16.173
3147133PAMPLIN
Solar/Wind Harmer
0.375
3147133PAMPLIN
Solar/Wind Harmer
0.3
958211AF2-115 GEN
Solar/Wind Harmer
4.2
963191AG1-168 GEN
Solar/Wind Harmer
1.4
971741AH1-377 GEN
Solar/Wind Harmer
33.04
316034AC1-036 C
Solar/Wind Harmer
0.02
970323AG2-213 GEN
Solar/Wind Harmer
11.75
971775AH1-396 GEN
Solar/Wind Harmer
0.441
313527AB2-043 GEN
Solar/Wind Harmer
0.002
962561AG1-105 GEN
Solar/Wind Harmer
7.214
939181AE1-148 GEN
Solar/Wind Harmer
6.93
964791AG1-342 GEN
Solar/Wind Harmer
2.751
3146843MT LREL
Solar/Wind Harmer
0.143
3146843MT LREL
Solar/Wind Harmer
0.143
970099AG2-077 GEN
Solar/Wind Harmer
13.815
970933AG2-581 GEN
Solar/Wind Harmer
6.948
316181AB2-040 GEN
Solar/Wind Harmer
0.106
3145593CAROLNA
Solar/Wind Harmer
0.07
3145593CAROLNA
Solar/Wind Harmer
0.07
966811AG1-552 GEN
Solar/Wind Harmer
0.761
3145593CAROLNA
Solar/Wind Harmer
0.087
3145783HORNRTN
Solar/Wind Harmer
1.218
3145783HORNRTN
Solar/Wind Harmer
0.974
3145783HORNRTN
Solar/Wind Harmer
0.304
3145783HORNRTN
Solar/Wind Harmer
0.122
316222AC1-221 GEN
Solar/Wind Harmer
0.283
316426AA2-053 GEN
Solar/Wind Harmer
0.225
942751AE2-291 GEN
Solar/Wind Harmer
3.327
316274AC1-208 GEN
Solar/Wind Harmer
0.31
315821AE2-092 GEN
Solar/Wind Helper
2.982
3144293JTRSVLE
50/50
1.182
3151601KERR 3
50/50
0.278
3151581KERR 1
50/50
0.099
3151531CLOVER1
50/50
2.857
3147043LAWRENC
50/50
1.061
3151261ROARAP2
50/50
0.087
3151051BRUNSWICKS1
50/50
1.582
3151021BRUNSWICKG1
50/50
0.762
971451AH1-221 GEN
50/50
2.315
972003AH1-546 GEN
Solar/Wind Harmer
35.828
316322AB2-045
Solar/Wind Harmer
0.005
3146776BUCKING
Solar/Wind Harmer
0.274
3146926FARMVIL
Solar/Wind Harmer
0.316
963171AG1-166 GEN
Solar/Wind Harmer
1.867
971563AH1-280 GEN
Solar/Wind Harmer
3.734
970685AG2-442 GEN
Solar/Wind Harmer
23.432
962491AG1-098 GEN
Solar/Wind Harmer
10.785
316237AB2-079_GEN
Solar/Wind Harmer
0.001
315693AD1-088 GEN
Solar/Wind Harmer
8.574
970401AG2-262 GEN
Solar/Wind Harmer
0.841
957481AF2-042 GEN
Solar/Wind Harmer
34.537
315687AD1-152 GEN
Solar/Wind Harmer
0.004
971065AG2-659 GEN
Solar/Wind Harmer
4.943
316129AC1-054 GEN
Solar/Wind Harmer
0.422
316003AC1-222 GEN
Solar/Wind Harmer
0.003
971795AH1-408 GEN
Solar/Wind Harmer
6.643
960081AF2-299 GEN
Solar/Wind Harmer
0.73
3145783HORNRTN
Solar/Wind Harmer
0.068
316190AA2-174 GEN
Solar/Wind Harmer
0
316212AC1-099_GEN
Solar/Wind Harmer
0.295
970919AG2-571 GEN
Solar/Wind Harmer
2.021
970087AG2-069 GEN
Solar/Wind Harmer
4.539
316336AC2-165 C
Solar/Wind Helper
1.447
960061AF2-297 GEN
Solar/Wind Harmer
4.699
971683AH1-343 GEN
Solar/Wind Harmer
3.468
313506AB2-031 GEN
Solar/Wind Harmer
0.226
316283AC2-100 C
Solar/Wind Harmer
0.132
316210AC1-098 GEN
Solar/Wind Harmer
0.53
970917AG2-570 GEN
Solar/Wind Harmer
5.054
316327AA2-057 GEN
Solar/Wind Harmer
0.085
316313AB2-026
Solar/Wind Helper
0.339
316258AE1-075 C
Solar/Wind Helper
0.305
316405AF2-144 C
Solar/Wind Helper
0.254
3148013FISHERV
Solar/Wind Helper
0.124
3151611KERR 4
50/50
0.278
3151621KERR 5
50/50
0.278
3151631KERR 6
50/50
0.278
3151641KERR 7
50/50
0.278
3151541CLOVER2
50/50
2.843
3151281ROARAP4
50/50
0.085
3151281ROARAP4
50/50
0.079
963041AG1-153 GEN
50/50
1.544
971845AH1-439 GEN
Solar/Wind Harmer
30.475
970285AG2-188 GEN
Solar/Wind Harmer
51.158
315657AE1-056 GEN
Solar/Wind Harmer
12.943
946301AF1-294 GEN
Solar/Wind Harmer
6.907
961791AG1-021 GEN
Solar/Wind Harmer
3.36
970683AG2-441 GEN
Solar/Wind Harmer
20.922
970681AG2-440 GEN
Solar/Wind Harmer
16.737
3144303KENBRDG
Solar/Wind Harmer
0.22
971443AH1-215 GEN
Solar/Wind Harmer
4.571
316239AB2-077_GEN
Solar/Wind Harmer
0.001
316238AB2-078_GEN
Solar/Wind Harmer
0.001
316118AC1-105 GEN
Solar/Wind Harmer
0.326
3147173SINAI
Solar/Wind Harmer
0.11
3147243WELCO
Solar/Wind Harmer
0.069
970831AG2-522 GEN
Solar/Wind Harmer
4.61
970865AG2-541 GEN
Solar/Wind Harmer
3.002
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3137643SOCKMAN
Solar/Wind Harmer
0.286
316123AC1-075 GEN
Solar/Wind Harmer
0.097
970165AG2-112 GEN
Solar/Wind Harmer
0.576
970163AG2-111 GEN
Solar/Wind Harmer
0.549
971967AH1-528 GEN
Solar/Wind Harmer
10.852
315607AA1-063A GEN
Solar/Wind Harmer
0.13
3146043SEABORD
Solar/Wind Harmer
0.063
970085AG2-068 GEN
Solar/Wind Harmer
3.026
970581AG2-369 GEN
Solar/Wind Harmer
2.602
270494AE1-108_GEN
Solar/Wind Helper
4.482
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.005
3148133STUARTS
Solar/Wind Helper
0.074
3148013FISHERV
Solar/Wind Helper
0.071
NYPJM->LTFIMP_NY
CLTF
0.308
LAGNLTFEXP_LAGN->PJM
CLTF
1.944
LGEELTFEXP_LGEE->PJM
CLTF
0.221
WECLTFEXP_WEC->PJM
CLTF
0.117
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.608
TVALTFEXP_TVA->PJM
CLTF
0.955
CPLELTFEXP_CPLE->PJM
CLTF
3.771
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.326
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.157
MECLTFEXP_MEC->PJM
CLTF
0.729
SIGELTFEXP_SIGE->PJM
CLTF
0.02
CONTINGENCY 'DVP_P1-2: LN 576_SRT-S'
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: WT576_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: 57602_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B3_SRT-A'
 OPEN BRANCH FROM BUS 313708 TO BUS 314744 CKT 2   /*3FORK UNION  115.0 - 3BREMO       115.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314746 CKT 1   /*3BREMO       115.0 - 4BREMO       138.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 2   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BUS 314868                                   /*3BREMO_1     115.0
END
CONTINGENCY 'AEP_P2-2_#1377_05J.FERR 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242514 TO BUS 290022 CKT 1   /*05J.FERR     765.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 290022 CKT 1   /*05J.FERR     500.0 - 05J.FERR 1EQ   1.0
 OPEN BRANCH FROM BUS 242520 TO BUS 306719 CKT 1   /*05J.FERR     500.0 - 8ANTIOCH     500.0
 OPEN BRANCH FROM BUS 290022 TO BUS 290023 CKT 1   /*05J.FERR 1EQ   1.0 - 05J.FERR T1   13.8
END
CONTINGENCY 'DVP_P7-1: LN 2066-282_SRT-S'
 OPEN BRANCH FROM BUS 313740 TO BUS 314322 CKT 1                /*6GENITO      230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 313740 TO BUS 314352 CKT 1                /*6GENITO      230.0 - 6WINTERP     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314311 CKT 1                /*6HULL282     230.0 - 6IRON282     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314322 CKT 1                /*6HULL282     230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 314311 TO BUS 314339 CKT 1                /*6IRON282     230.0 - 6SPRUNCE     230.0
 OPEN BRANCH FROM BUS 314339 TO BUS 315083 CKT 1                /*6SPRUNCE     230.0 - 1SPRUNCA      13.8
 OPEN BRANCH FROM BUS 314339 TO BUS 315084 CKT 1                /*6SPRUNCE     230.0 - 1SPRUNCB      13.8
 OPEN BUS 313740                                                /*6GENITO      230.0
 OPEN BUS 314307                                                /*6HULL282     230.0
 OPEN BUS 314311                                                /*6IRON282     230.0
 OPEN BUS 315083                                                /*1SPRUNCA      13.8
 OPEN BUS 315084                                                /*1SPRUNCB      13.8
 SET POSTCONTRATING 876 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314233 TO BUS 314322 CKT 1 /*6N POLE      230.0 - 6MDLTHAN     230.0
END
CONTINGENCY 'DVP_P7-1: LN 219-282_SRT-A'
 OPEN BRANCH FROM BUS 314306 TO BUS 314338 CKT 1   /*6HULL219     230.0 - 6SOUWEST     230.0
 OPEN BRANCH FROM BUS 314306 TO BUS 314352 CKT 1   /*6HULL219     230.0 - 6WINTERP     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314311 CKT 1   /*6HULL282     230.0 - 6IRON282     230.0
 OPEN BRANCH FROM BUS 314307 TO BUS 314322 CKT 1   /*6HULL282     230.0 - 6MDLTHAN     230.0
 OPEN BRANCH FROM BUS 314311 TO BUS 314339 CKT 1   /*6IRON282     230.0 - 6SPRUNCE     230.0
 OPEN BRANCH FROM BUS 314339 TO BUS 315083 CKT 1   /*6SPRUNCE     230.0 - 1SPRUNCA      13.8
 OPEN BRANCH FROM BUS 314339 TO BUS 315084 CKT 1   /*6SPRUNCE     230.0 - 1SPRUNCB      13.8
 OPEN BUS 314306                                   /*6HULL219     230.0
 OPEN BUS 314307                                   /*6HULL282     230.0
 OPEN BUS 314311                                   /*6IRON282     230.0
 OPEN BUS 315083                                   /*1SPRUNCA      13.8
 OPEN BUS 315084                                   /*1SPRUNCB      13.8
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P7-1: LN 2003-205_SRT-S'
 OPEN BRANCH FROM BUS 314263 TO BUS 314287 CKT 1                /*6TYLER1      230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314263 TO BUS 314331 CKT 1                /*6TYLER1      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314346 CKT 1                /*6CHESTF B    230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314316 CKT 1                /*6HARR205     230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314346 CKT 1                /*6HARR205     230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 1                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 2                /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314263                                                /*6TYLER1      230.0
 OPEN BUS 314301                                                /*6HARR205     230.0
 OPEN BUS 314346                                                /*6TYLER       230.0
 OPEN BUS 315839                                                /*AE2-212 C    230.0
 OPEN BUS 316240                                                /*AF1-291 C    230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P7-1: LN 249-69_SRT-A'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1   /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 313251 TO BUS 314334 CKT 1   /*3SAPONY      115.0 - 3REAMS D     115.0
 OPEN BRANCH FROM BUS 313251 TO BUS 314337 CKT 1   /*3SAPONY      115.0 - 3 69T148     115.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1   /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1   /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2   /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                   /*6CHAPARRAL   230.0
 OPEN BUS 313251                                   /*3SAPONY      115.0
 OPEN BUS 314285                                   /*6CHAPARRAL T 230.0
 OPEN BUS 314337                                   /*3 69T148     115.0
END
CONTINGENCY 'AEP_P2-2_#10292_05NEWLDN 138_1_SRT-A'
 OPEN BRANCH FROM BUS 242569 TO BUS 242734 CKT 1   /*05BRUSHT     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242641 TO BUS 242734 CKT 1   /*05FOREST     138.0 - 05NEWLDN     138.0
 OPEN BRANCH FROM BUS 242687 TO BUS 242734 CKT 1   /*05JOHNMT     138.0 - 05NEWLDN     138.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 2002_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1   /*6CARSON      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1   /*3POE         115.0 - 6POE         230.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-5: L552_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1   /*6CARSON      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1   /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314329                                   /*3POE         115.0
 OPEN BUS 314454                                   /*3POE_1       115.0
END
CONTINGENCY 'DVP_P7-1: LN 2002-2003_SRT-A'
 OPEN BRANCH FROM BUS 314263 TO BUS 314287 CKT 1   /*6TYLER1      230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314263 TO BUS 314331 CKT 1   /*6TYLER1      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314331 CKT 1   /*6CARSON      230.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 1   /*3POE         115.0 - 6POE         230.0
 OPEN BRANCH FROM BUS 314329 TO BUS 314331 CKT 2   /*3POE         115.0 - 6POE         230.0
 OPEN BUS 314263                                   /*6TYLER1      230.0
 OPEN BUS 316240                                   /*AF1-291 C    230.0
END
CONTINGENCY 'DVP_P1-2: LN 249_SRT-A'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1   /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1   /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1   /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2   /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                   /*6CHAPARRAL   230.0
 OPEN BUS 314285                                   /*6CHAPARRAL T 230.0
END
CONTINGENCY 'DVP_P4-2: 24972-3_SRT-A'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1   /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1   /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1   /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2   /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                   /*6CHAPARRAL   230.0
 OPEN BUS 314285                                   /*6CHAPARRAL T 230.0
 REMOVE SWSHUNT FROM BUS 314282                    /*6CARSON      230.0
END
CONTINGENCY 'DVP_P4-5: LOCKS H322_SRT-A'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1   /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1   /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1   /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2   /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                   /*6CHAPARRAL   230.0
 OPEN BUS 314285                                   /*6CHAPARRAL T 230.0
END
CONTINGENCY 'DVP_P4-6: T152_SRT-A'
 OPEN BUS 314316   /*6LOCKS       230.0
 OPEN BUS 314368   /*3FREDB_1     115.0
END
CONTINGENCY 'DVP_P4-2: 205T249_SRT-S'
 OPEN BRANCH FROM BUS 313014 TO BUS 314285 CKT 1                /*6CHAPARRAL   230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314282 TO BUS 314285 CKT 1                /*6CARSON      230.0 - 6CHAPARRAL T 230.0
 OPEN BRANCH FROM BUS 314285 TO BUS 314316 CKT 1                /*6CHAPARRAL T 230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314287 TO BUS 314346 CKT 1                /*6CHESTF B    230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314316 CKT 1                /*6HARR205     230.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314301 TO BUS 314346 CKT 1                /*6HARR205     230.0 - 6TYLER       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 1                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BRANCH FROM BUS 314314 TO BUS 314316 CKT 2                /*3LOCKS       115.0 - 6LOCKS       230.0
 OPEN BUS 313014                                                /*6CHAPARRAL   230.0
 OPEN BUS 314285                                                /*6CHAPARRAL T 230.0
 OPEN BUS 314301                                                /*6HARR205     230.0
 OPEN BUS 314346                                                /*6TYLER       230.0
 OPEN BUS 315839                                                /*AE2-212 C    230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314260 TO BUS 314287 CKT 1 /*6VARINA      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P4-2: H2T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313908 TO BUS 314922 CKT 1   /*6POS PT TAP2 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: H1T560_SRT-A'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1   /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313058 TO BUS 314922 CKT 1   /*6POSS PT TAP 230.0 - 8POSSUM      500.0
END
CONTINGENCY 'DVP_P4-2: 560T571_SRT-S'
 OPEN BRANCH FROM BUS 200019 TO BUS 314922 CKT 1                /*BURCHES      500.0 - 8POSSUM      500.0
 OPEN BRANCH FROM BUS 313383 TO BUS 314922 CKT 1                /*8OCCOQUN     500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019F_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200003 TO BUS 235105 CKT 1          /*BRIGHTON     500.0 - 01DOUBS      500.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 2          /*01DOUBS      500.0 - 01DOUBS      230.0
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 235459 CKT 4          /*01DOUBS      500.0 - 01DOUBS      230.0
 REMOVE SWSHUNT FROM BUS 235105 BLOCK 1 STEP 1                  /*01DOUBS      500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET POSTCONTRATING 4357 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 313403 CKT 1 /*01DOUBS      500.0 - 8ASPEN       500.0
 SET PRECONTRATING 4178 BRANCH FROM BUS 235105 TO BUS 314939 CKT 1 /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
END
CONTINGENCY 'AP_P2-3_PE-500-019B_SRT-A'
 DISCONNECT BRANCH FROM BUS 235105 TO BUS 200003 CKT 1   /*01DOUBS      500.0 - BRIGHTON     500.0
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P7-1: LN 514-2098_SRT-S'
 OPEN BRANCH FROM BUS 235105 TO BUS 314939 CKT 1                /*01DOUBS      500.0 - 8GOOSE CREEK 500.0
 OPEN BRANCH FROM BUS 313010 TO BUS 313021 CKT 1                /*6BREEZYKNOLL 230.0 - 6DRYMILLS    230.0
 OPEN BRANCH FROM BUS 313010 TO BUS 313021 CKT 2                /*6BREEZYKNOLL 230.0 - 6DRYMILLS    230.0
 OPEN BRANCH FROM BUS 313010 TO BUS 314005 CKT 1                /*6BREEZYKNOLL 230.0 - 6HAMLTON     230.0
 OPEN BRANCH FROM BUS 313021 TO BUS 314072 CKT 1                /*6DRYMILLS    230.0 - 6PL VIEW     230.0
 OPEN BUS 313010                                                /*6BREEZYKNOLL 230.0
 OPEN BUS 313021                                                /*6DRYMILLS    230.0
 OPEN BUS 314005                                                /*6HAMLTON     230.0
 SET POSTCONTRATING 1315 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
 SET PRECONTRATING 1219 BRANCH FROM BUS 314004 TO BUS 314072 CKT 1 /*6ASHBURN     230.0 - 6PL VIEW     230.0
END
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-S'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P2-2: ALTAVISTA 115KV_SRT-A'
 OPEN BUS 313162   /*3HALL BR TAP 115.0
 OPEN BUS 314515   /*3ALTVS_1     115.0
 OPEN BUS 314666   /*3ALTVSTA     115.0
 OPEN BUS 314700   /*3HALL BR     115.0
 OPEN BUS 314705   /*3HURT        115.0
 OPEN BUS 315156   /*1HALLBR1      13.8
END
CONTINGENCY 'DVP_P7-1: LN 39-91_SRT-A-2'
 OPEN BRANCH FROM BUS 313179 TO BUS 313271 CKT 1   /*3TURKEYRUN   115.0 - 3TRANSCO TAP 115.0
 OPEN BRANCH FROM BUS 313179 TO BUS 313783 CKT 1   /*3TURKEYRUN   115.0 - 3WALNUT CRK  115.0
 OPEN BRANCH FROM BUS 313270 TO BUS 313271 CKT 1   /*3TRANSCO DP  115.0 - 3TRANSCO TAP 115.0
 OPEN BRANCH FROM BUS 313271 TO BUS 314763 CKT 1   /*3TRANSCO TAP 115.0 - 3KIDDSTO     115.0
 OPEN BRANCH FROM BUS 313783 TO BUS 314773 CKT 1   /*3WALNUT CRK  115.0 - 3RED HIL     115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314773 CKT 1   /*3MIDWAY      115.0 - 3RED HIL     115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314793 CKT 1   /*3MIDWAY      115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 971446 TO BUS 314763 CKT 1   /*AH1-217 TP   115.0 - 3KIDDSTO     115.0
 OPEN BUS 247086                                   /*05REDHIL     115.0
 OPEN BUS 313179                                   /*3TURKEYRUN   115.0
 OPEN BUS 313270                                   /*3TRANSCO DP  115.0
 OPEN BUS 313271                                   /*3TRANSCO TAP 115.0
 OPEN BUS 314763                                   /*3KIDDSTO     115.0
 OPEN BUS 314767                                   /*3MIDWAY      115.0
 OPEN BUS 314773                                   /*3RED HIL     115.0
 OPEN BUS 315817                                   /*AE2-092 MAIN 115.0
 OPEN BUS 315818                                   /*AE2-092 COL   34.5
 OPEN BUS 315819                                   /*AE2-092 TER   13.8
 OPEN BUS 315820                                   /*AE2-092 GSU   34.5
 OPEN BUS 315821                                   /*AE2-092 GEN    0.6
END
CONTINGENCY 'DVP_P2-2: DOOMS B2_SRT-A'
 OPEN BRANCH FROM BUS 313286 TO BUS 314793 CKT 1   /*3WAYNESBORO  115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 314767 TO BUS 314793 CKT 1   /*3MIDWAY      115.0 - 3DOOMS       115.0
 OPEN BRANCH FROM BUS 314791 TO BUS 314793 CKT 1   /*3BRAND TAP   115.0 - 3DOOMS       115.0
END
CONTINGENCY 'DVP_P4-2: 568T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314922 CKT 1                /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P1-2: LN 574_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 557T574_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56272_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1                /*8CARSON      500.0 - AE2-051 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314923 TO BUS 314927 CKT 1 /*8SEPTA       500.0 - 8YADKIN      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314914 CKT 1 /*8CARSON      500.0 - 8MDLTHAN     500.0
END
CONTINGENCY 'DVP_P1-2: LN 567_SRT-A'
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P4-2: H2T574_SRT-S'
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 2                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T574_SRT-S'
 OPEN BRANCH FROM BUS 314218 TO BUS 314908 CKT 1                /*6ELMONT      230.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314910 CKT 1 /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56722_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1   /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P2-2: BREMO B1_SRT-A'
 OPEN BRANCH FROM BUS 313867 TO BUS 314747 CKT 1   /*6BREMODIST   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 1   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314326 TO BUS 314747 CKT 2   /*6BEARGRDN    230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 314744 TO BUS 314747 CKT 1   /*3BREMO       115.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 970936 TO BUS 314747 CKT 1   /*AG2-583 TP   230.0 - 6BREMO       230.0
 OPEN BRANCH FROM BUS 972002 TO BUS 314747 CKT 1   /*AH1-546 TP   230.0 - 6BREMO       230.0
 OPEN BUS 314326                                   /*6BEARGRDN    230.0
 OPEN BUS 314747                                   /*6BREMO       230.0
 OPEN BUS 315191                                   /*1BEARGRDN G1  18.0
 OPEN BUS 315192                                   /*1BEARGRDN G2  18.0
 OPEN BUS 315193                                   /*1BEARGRDN S1  18.0
END
CONTINGENCY 'DVP_P7-1: LN 208-259_SRT-S'
 OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1                /*6BASIN       230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1                /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1                /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                                /*6IRON208     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P4-2: 545T594_SRT-S'
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314900 TO BUS 314905 CKT 1 /*8BRISTER     500.0 - 8CHANCE      500.0
END
CONTINGENCY 'DVP_P4-2: H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314063 TO BUS 314916 CKT 1                /*6MORRSVL     230.0 - 8MORRSVL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
END
CONTINGENCY 'DVP_P4-2: SPOTS H1T594_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: 515T594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1                /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                                /*8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T573_SRT-S'
 OPEN BRANCH FROM BUS 314755 TO BUS 314934 CKT 1                /*3SPOTSYL     115.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-1'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57302_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: XT573_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 515T573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1   /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 OPEN BRANCH FROM BUS 314934 TO BUS 314944 CKT 1   /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 OPEN BUS 314944                                   /*8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H4T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H3T552_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 574T575_SRT-S'
 OPEN BRANCH FROM BUS 314908 TO BUS 314911 CKT 1                /*8ELMONT      500.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3966 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 3572 BRANCH FROM BUS 314905 TO BUS 314911 CKT 1 /*8CHANCE      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-1: G202_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 2                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314918 TO BUS 315226 CKT 1                /*8NO ANNA     500.0 - 1N ANNA2      22.0
 OPEN BUS 315226                                                /*1N ANNA2      22.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B1_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P2-2: NORTH ANNA B2_SRT-S'
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2090-256_SRT-S'
 OPEN BRANCH FROM BUS 313837 TO BUS 314138 CKT 1                /*6SUMMIT      230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 313837 TO BUS 314197 CKT 1                /*6SUMMIT      230.0 - 6LDYSMITH CT 230.0
 OPEN BRANCH FROM BUS 314137 TO BUS 314138 CKT 1                /*6FREDBRG     230.0 - 6MINE RD     230.0
 OPEN BRANCH FROM BUS 314150 TO BUS 314212 CKT 1                /*6STJOHN      230.0 - 6FOUR RIVERS 230.0
 OPEN BRANCH FROM BUS 314197 TO BUS 315672 CKT 1                /*6LDYSMITH CT 230.0 - AE1-157 TAP  230.0
 OPEN BUS 313837                                                /*6SUMMIT      230.0
 OPEN BUS 314138                                                /*6MINE RD     230.0
 OPEN BUS 314149                                                /*3STJOHND     115.0
 OPEN BUS 314150                                                /*6STJOHN      230.0
 OPEN BUS 314154                                                /*3STJOHNS     115.0
 OPEN BUS 315672                                                /*AE1-157 TAP  230.0
 OPEN BUS 315673                                                /*AE1-157 GEN    0.6
 OPEN BUS 315803                                                /*AE1-157 MAIN 230.0
 OPEN BUS 315804                                                /*AE1-157 COL1  34.5
 OPEN BUS 315805                                                /*AE1-157 COL2  34.5
 SET POSTCONTRATING 657 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
 SET PRECONTRATING 598 BRANCH FROM BUS 313027 TO BUS 314212 CKT 1 /*6FOUR RIVER1 230.0 - 6FOUR RIVERS 230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314212 TO BUS 315610 CKT 1 /*6FOUR RIVERS 230.0 - AA1-145 MAIN 230.0
END
CONTINGENCY 'DVP_P7-1: LN 2054-2135_SRT-A'
 OPEN BRANCH FROM BUS 314734 TO BUS 314758 CKT 1   /*6CASHSCORNER 230.0 - 6GORDNVL     230.0
 OPEN BRANCH FROM BUS 314734 TO BUS 314759 CKT 1   /*6CASHSCORNER 230.0 - 6HOLLYMD     230.0
 OPEN BRANCH FROM BUS 314749 TO BUS 314772 CKT 1   /*6CHARLVL     230.0 - 6PROFFIT     230.0
 OPEN BRANCH FROM BUS 314759 TO BUS 314772 CKT 1   /*6HOLLYMD     230.0 - 6PROFFIT     230.0
 OPEN BUS 314734                                   /*6CASHSCORNER 230.0
 OPEN BUS 314772                                   /*6PROFFIT     230.0
END
CONTINGENCY 'DVP_P1-2: LN 594_SRT-S'
 OPEN BRANCH FROM BUS 314916 TO BUS 314934 CKT 1                /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 573_SRT-S'
 OPEN BRANCH FROM BUS 314918 TO BUS 314934 CKT 1                /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET POSTCONTRATING 2831 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
 SET PRECONTRATING 2552 BRANCH FROM BUS 314934 TO BUS 314944 CKT 1 /*8SPOTSYL     500.0 - 8SPOTSYL EC  500.0
END
CONTINGENCY 'DVP_P4-2: 57502_SRT-S'
 OPEN BRANCH FROM BUS 314232 TO BUS 314918 CKT 1                /*6NO ANNA     230.0 - 8NO ANNA     500.0
 OPEN BRANCH FROM BUS 314911 TO BUS 314918 CKT 1                /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314922 CKT 1 /*8LADYSMITH   500.0 - 8POSSUM      500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314914 TO BUS 314918 CKT 1 /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314918 TO BUS 314934 CKT 1 /*8NO ANNA     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H1T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'DVP_P7-1: LN 11-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 313227 TO BUS 314769 CKT 1   /*3ORANGE      115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314769 CKT 1   /*3DOUBLDY     115.0 - 3ORANGE TAP  115.0
 OPEN BRANCH FROM BUS 314756 TO BUS 314776 CKT 1   /*3DOUBLDY     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314757 TO BUS 314776 CKT 1   /*3GORDNVL     115.0 - 3SOMRSET     115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314769 TO BUS 314815 CKT 1   /*3ORANGE TAP  115.0 - 3OAK GRE     115.0
 OPEN BRANCH FROM BUS 314776 TO BUS 314884 CKT 1   /*3SOMRSET     115.0 - 3SOMRS_1     115.0
 OPEN BUS 313227                                   /*3ORANGE      115.0
 OPEN BUS 314756                                   /*3DOUBLDY     115.0
 OPEN BUS 314769                                   /*3ORANGE TAP  115.0
 OPEN BUS 314776                                   /*3SOMRSET     115.0
 OPEN BUS 314884                                   /*3SOMRS_1     115.0
END
CONTINGENCY 'PEPCO_P4_PP41_SRT-A'
 OPEN BRANCH FROM BUS 200003 TO BUS 224058 CKT 1   /*BRIGHTON     500.0 - BRG 3T 230   230.0
 OPEN BRANCH FROM BUS 200003 TO BUS 235105 CKT 1   /*BRIGHTON     500.0 - 01DOUBS      500.0
END
CONTINGENCY 'DVP_P1-2: LN 585_SRT-A-2'
 OPEN BRANCH FROM BUS 941030 TO BUS 970672 CKT 1   /*AE2-094 TP   500.0 - AG2-436 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 58572_SRT-A'
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-5: W72_SRT-A'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1   /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 941030 CKT 1   /*8CARSON      500.0 - AE2-094 TP   500.0
END
CONTINGENCY 'DVP_P4-2: XT585_SRT-S'
 OPEN BRANCH FROM BUS 970672 TO BUS 314940 CKT 1                /*AG2-436 TP   500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 3464 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
END
CONTINGENCY 'DVP_P4-2: 54472_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P1-2: LN 511_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51192_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BUS 314921                                                /*8RAWLIN_STC2 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 51172_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 939410 CKT 1 /*8CARSON      500.0 - AE1-173 TP   500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P4-2: 511T544_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314936 CKT 1                /*8CARSON      500.0 - 8RAWLINGS    500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 939410 CKT 1                /*8CARSON      500.0 - AE1-173 TP   500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
CONTINGENCY 'DVP_P2-2: MORRISVILLE B1_SRT-S'
 OPEN BUS 314897                                                /*8MORRS_1     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314929 CKT 1 /*8MORRSVL     500.0 - 8FRONT ROYAL 500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P7-1: LN 2-2199_SRT-A-1'
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314078 TO BUS 314743 CKT 1   /*3REMNGTN     115.0 - 3BRANDY      115.0
 OPEN BRANCH FROM BUS 314743 TO BUS 316256 CKT 1   /*3BRANDY      115.0 - AC1-043 TAP  115.0
 OPEN BUS 314743                                   /*3BRANDY      115.0
END
CONTINGENCY 'DVP_P7-1: LN 2-2199_SRT-A-2'
 OPEN BRANCH FROM BUS 314078 TO BUS 314743 CKT 1   /*3REMNGTN     115.0 - 3BRANDY      115.0
 OPEN BRANCH FROM BUS 314743 TO BUS 316256 CKT 1   /*3BRANDY      115.0 - AC1-043 TAP  115.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BUS 314743                                   /*3BRANDY      115.0
END
CONTINGENCY 'DVP_P2-2: GERMANNA_SRT-A'
 OPEN BRANCH FROM BUS 313671 TO BUS 313679 CKT 1   /*6GERMANNA    230.0 - 6CIRRUS      230.0
 OPEN BRANCH FROM BUS 313671 TO BUS 315678 CKT 1   /*6GERMANNA    230.0 - AE1-153 TAP  230.0
 OPEN BRANCH FROM BUS 314758 TO BUS 315678 CKT 1   /*6GORDNVL     230.0 - AE1-153 TAP  230.0
 OPEN BUS 315678                                   /*AE1-153 TAP  230.0
 OPEN BUS 315679                                   /*AE1-153 MAIN 230.0
 OPEN BUS 315680                                   /*AE1-153 COL1  34.5
 OPEN BUS 315681                                   /*AE1-153 COL2  34.5
 OPEN BUS 315682                                   /*AE1-153 TER   13.8
 OPEN BUS 315683                                   /*AE1-153 C      0.6
END
CONTINGENCY 'DVP_P1-2: LN 591_SRT-S'
 OPEN BRANCH FROM BUS 314935 TO BUS 314936 CKT 1                /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET POSTCONTRATING 3811 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3533 BRANCH FROM BUS 314902 TO BUS 314936 CKT 1 /*8CARSON      500.0 - 8RAWLINGS    500.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314677 to 972002 ckt 1
314282 to 314285 ckt 1
314282 to 314331 ckt 1
314285 to 314316 ckt 1
314290 to 223938 ckt 1
315684 to 314690 ckt 1
314692 to 970284 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314197 to 313837 ckt 1
314138 to 314137 ckt 1
314765 to 314749 ckt 1
304070 to 316281 ckt 1
314331 to 314263 ckt 1
314697 to 315684 ckt 1
313837 to 314138 ckt 1
313911 to 314290 ckt 1
314346 to 314287 ckt 1
314902 to 314282 ckt 1
314902 to 314282 ckt 2
314902 to 314914 ckt 1
314905 to 314900 ckt 1
314903 to 314908 ckt 1
314908 to 314911 ckt 1
314935 to 314936 ckt 1
314911 to 314905 ckt 1
314911 to 314922 ckt 1
314914 to 314322 ckt 1
314914 to 314918 ckt 1
314918 to 314911 ckt 1
314918 to 314934 ckt 1
314922 to 200019 ckt 1
314936 to 314902 ckt 1
314940 to 970672 ckt 1
314923 to 314924 ckt 1
314934 to 314916 ckt 1
314924 to 314903 ckt 1
941030 to 314902 ckt 1
970284 to 971844 ckt 1
970672 to 941030 ckt 1
971844 to 314677 ckt 1
972002 to 314747 ckt 1

Winter Peak Analysis

The New Service Request AG2-369 was evaluated as a 86.0 MW (51.6 MW Capacity) injection in the Dominion area.

AG2-369 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 86.0 MW (86.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC143.28 %694.0B994.380.66
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-3
SingleAC136.4 %652.36B889.840.66
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P1-2: LN 570_SRT-A-2
SingleAC134.99 %652.36B880.620.66
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 57062_SRT-W
BreakerAC130.48 %694.0B905.50.66
IPDCPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC107.58 %694.0B746.5913.14

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.28 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:994.38
MW Contribution:0.66
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.153
3147133PAMPLIN
Solar/Wind Helper
1.357
3147133PAMPLIN
Solar/Wind Helper
0.346
3147133PAMPLIN
Solar/Wind Helper
0.432
3143316POE
Solar/Wind Helper
0.789
3145506HICKORY
Solar/Wind Helper
0.729
3145506HICKORY
Solar/Wind Helper
0.438
3145506HICKORY
Solar/Wind Helper
0.109
3146776BUCKING
Solar/Wind Helper
1.198
3146776BUCKING
Solar/Wind Helper
0.097
3146776BUCKING
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
0.12
3143226MDLTHAN
Solar/Wind Helper
0.18
3146843MT LREL
Solar/Wind Helper
0.804
3146843MT LREL
Solar/Wind Helper
0.804
3146926FARMVIL
Solar/Wind Helper
0.225
3146926FARMVIL
Solar/Wind Helper
0.225
3147123OTTER R
Solar/Wind Helper
0.119
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.061
316159AE1-175 C
Solar/Wind Helper
0.057
316240AF1-291 C
Solar/Wind Helper
0.059
316248AF1-058 C
Solar/Wind Helper
0.327
316258AE1-075 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.053
316336AC2-165 C
Solar/Wind Helper
0.312
316382AG1-145 C
Solar/Wind Helper
0.057
316405AF2-144 C
Solar/Wind Helper
0.052
3145336SMITFLD
Solar/Wind Helper
0.738
3145336SMITFLD
Solar/Wind Helper
0.074
3147243WELCO
Solar/Wind Helper
0.636
316017AA1-139 ULT1
Solar/Wind Helper
0.169
316018AA1-139 ULT2
Solar/Wind Helper
0.016
316033AB2-134 GEN
Solar/Wind Helper
0.412
316388AE2-253 GEN
Solar/Wind Helper
0.142
3144303KENBRDG
Solar/Wind Helper
0.376
3147173SINAI
Solar/Wind Helper
1.018
316369SG1_INVT
Solar/Wind Helper
0.284
315839AE2-212 C
Solar/Wind Helper
0.061
315697AD1-025 GEN
Solar/Wind Helper
0.434
316185AD1-033 GEN
Solar/Wind Helper
0.208
316478AD1-087 GEN
Solar/Wind Helper
0.737
316486AD2-202 GEN
Solar/Wind Helper
0.216
315687AD1-152 GEN
Solar/Wind Helper
1.268
315785AD2-033 C
Solar/Wind Helper
0.995
316313AB2-026
Solar/Wind Helper
0.061
270030AE2-140 GEN
Solar/Wind Harmer
0.914
313527AB2-043 GEN
Solar/Wind Helper
0.404
316322AB2-045
Solar/Wind Helper
0.095
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.644
316083AB2-161 GEN
Solar/Wind Helper
0.146
316132AB2-190 GEN1
Solar/Wind Helper
0.216
316458AB2-190 GEN2
Solar/Wind Helper
0.216
316123AC1-075 GEN
Solar/Wind Helper
0.801
316375AC2-012 GEN
Solar/Wind Helper
0.357
316339AD2-160 GEN
Solar/Wind Helper
0.142
316239AB2-077_GEN
Solar/Wind Helper
0.164
316238AB2-078_GEN
Solar/Wind Helper
0.164
316237AB2-079_GEN
Solar/Wind Helper
0.164
316381AD1-082 GEN
Solar/Wind Helper
0.199
316236AE1-162_GEN
Solar/Wind Helper
0.059
3145543BTLEBRO
Solar/Wind Harmer
-0.146
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3145543BTLEBRO
Solar/Wind Harmer
-0.183
3138543CONSLDL
Solar/Wind Harmer
-0.098
3142053HEARTS
Solar/Wind Harmer
0.006
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.161
3145573BETHELC
Solar/Wind Harmer
-0.161
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.161
3146083TARBORO
Solar/Wind Harmer
-0.161
3146083TARBORO
Solar/Wind Harmer
-0.161
3146233WITAKRS
Solar/Wind Harmer
0.03
3146233WITAKRS
Solar/Wind Harmer
-0.575
3146233WITAKRS
Solar/Wind Harmer
-0.098
942461AE2-259 GEN
Solar/Wind Helper
0.651
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.329
961601AG1-000A GEN
Solar/Wind Harmer
5.263
961611AG1-000B GEN
Solar/Wind Helper
0.259
970085AG2-068 GEN
Solar/Wind Harmer
0.764
970087AG2-069 GEN
Solar/Wind Harmer
1.146
970223AG2-152 GEN
Solar/Wind Harmer
0.735
970581AG2-369 GEN
Solar/Wind Harmer
0.657
970917AG2-570 GEN
Solar/Wind Harmer
3.057
970919AG2-571 GEN
Solar/Wind Harmer
6.113
971367AH1-164 GEN
Solar/Wind Harmer
0.1
971629AH1-314 GEN
50/50
15.356
971981AH1-535 GEN
Solar/Wind Harmer
0.293
315773AC2-141 GEN
Solar/Wind Helper
0.792
316003AC1-222 GEN
Solar/Wind Helper
0.97
316118AC1-105 GEN
Solar/Wind Helper
0.747
316129AC1-054 GEN
Solar/Wind Helper
0.253
316222AC1-221 GEN
Solar/Wind Helper
2.596
316263AC1-034 GEN
Solar/Wind Harmer
0.241
316283AC2-100 C
Solar/Wind Helper
2.444
316294AC1-161 GEN
Solar/Wind Helper
0.792
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.454
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.037
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.468
NYPJM->LTFIMP_NY
CLTF
0.617
LGEELTFEXP_LGEE->PJM
CLTF
2.103
WECLTFEXP_WEC->PJM
CLTF
1.136
CPLELTFEXP_CPLE->PJM
CLTF
13.823
TVALTFEXP_TVA->PJM
CLTF
5.181
MECLTFEXP_MEC->PJM
CLTF
5.746
LAGNLTFEXP_LAGN->PJM
CLTF
10.439
SIGELTFEXP_SIGE->PJM
CLTF
0.173
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-3


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.4 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:889.84
MW Contribution:0.66
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970417AG2-272 GEN
50/50
2.037
970581AG2-369 GEN
Solar/Wind Harmer
0.661
970917AG2-570 GEN
Solar/Wind Harmer
3.076
970919AG2-571 GEN
Solar/Wind Harmer
6.153
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
SIGELTFEXP_SIGE->PJM
CLTF
0.177
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 570_SRT-A-2


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 570_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.99 %
Rating:652.36 MVA
Rating Type:B
MVA to Mitigate:880.62
MW Contribution:0.66
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970417AG2-272 GEN
50/50
2.037
970581AG2-369 GEN
Solar/Wind Harmer
0.661
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
SIGELTFEXP_SIGE->PJM
CLTF
0.177
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 57062_SRT-W


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 57062_SRT-W
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.48 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:905.5
MW Contribution:0.66
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Helper
0.151
3147133PAMPLIN
Solar/Wind Helper
1.348
3147133PAMPLIN
Solar/Wind Helper
0.343
3147133PAMPLIN
Solar/Wind Helper
0.429
3137176SLIGO L2192
Solar/Wind Helper
0.678
3142433PROV 92
Solar/Wind Helper
0.666
3143316POE
Solar/Wind Helper
0.777
3145506HICKORY
Solar/Wind Helper
0.717
3145506HICKORY
Solar/Wind Helper
0.43
3145506HICKORY
Solar/Wind Helper
0.108
3146776BUCKING
Solar/Wind Helper
1.185
3146776BUCKING
Solar/Wind Helper
0.096
3146776BUCKING
Solar/Wind Helper
0.107
3146776BUCKING
Solar/Wind Helper
0.119
316075AC2-137 C
Solar/Wind Helper
0.052
3138133OCRAN
Solar/Wind Helper
0.049
3138133OCRAN
Solar/Wind Helper
0.098
3141766HARMONY
Solar/Wind Helper
0.033
3141783LANCAST
Solar/Wind Helper
0.098
3141783LANCAST
Solar/Wind Helper
0.065
3141913WHIT STONE
Solar/Wind Helper
0.164
3143226MDLTHAN
Solar/Wind Helper
0.177
3143873LANEXA
Solar/Wind Helper
0.099
3146456SLIGO L269
Solar/Wind Helper
0.17
3146456SLIGO L269
Solar/Wind Helper
0.17
3146843MT LREL
Solar/Wind Helper
0.801
3146843MT LREL
Solar/Wind Helper
0.801
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.117
3141726DUNNSVL
Solar/Wind Helper
0.624
316034AC1-036 C
Solar/Wind Helper
0.104
316036AC1-147 C
Solar/Wind Helper
0.06
316059AD1-063 C
Solar/Wind Helper
0.04
316159AE1-175 C
Solar/Wind Helper
0.056
316240AF1-291 C
Solar/Wind Helper
0.058
316246AF1-032 C
Solar/Wind Helper
0.041
316248AF1-058 C
Solar/Wind Helper
0.326
316258AE1-075 C
Solar/Wind Helper
0.054
316305AF2-043 C
Solar/Wind Helper
0.054
316314AB2-024 C
Solar/Wind Helper
0.053
316315AB2-025 C
Solar/Wind Helper
0.055
316316AC1-027 C
Solar/Wind Helper
0.052
316336AC2-165 C
Solar/Wind Helper
0.307
316382AG1-145 C
Solar/Wind Helper
0.056
316405AF2-144 C
Solar/Wind Helper
0.051
3145336SMITFLD
Solar/Wind Helper
0.726
3145336SMITFLD
Solar/Wind Helper
0.073
3147243WELCO
Solar/Wind Helper
0.634
3141873WAN 176
Solar/Wind Helper
0.033
3143526WINTERP
Solar/Wind Helper
0.894
3143526WINTERP
Solar/Wind Helper
0.894
316404AE1-155 C
Solar/Wind Helper
0.323
316017AA1-139 ULT1
Solar/Wind Helper
0.166
316018AA1-139 ULT2
Solar/Wind Helper
0.166
316033AB2-134 GEN
Solar/Wind Helper
0.405
316388AE2-253 GEN
Solar/Wind Helper
0.14
3142543TWELFTH
Solar/Wind Helper
0.016
3144303KENBRDG
Solar/Wind Helper
0.374
3147173SINAI
Solar/Wind Helper
1.015
316203AE2-005 GEN
Solar/Wind Helper
0.345
316441AF1-014 GEN
Solar/Wind Helper
0.053
316484AD2-074 GEN
Solar/Wind Helper
0.221
315833AF1-017_GEN
Solar/Wind Helper
0.109
316369SG1_INVT
Solar/Wind Helper
0.279
316487AF1-042 GEN
Solar/Wind Helper
0.116
315839AE2-212 C
Solar/Wind Helper
0.06
315662AE1-191 GEN
Solar/Wind Helper
0.213
315666AE1-190 GEN
Solar/Wind Helper
0.053
319010AE1-072 C
Solar/Wind Helper
0.407
315697AD1-025 GEN
Solar/Wind Helper
0.427
316185AD1-033 GEN
Solar/Wind Helper
0.205
316280AD1-041 GEN
Solar/Wind Helper
0.133
316478AD1-087 GEN
Solar/Wind Helper
0.734
316486AD2-202 GEN
Solar/Wind Helper
0.215
316072AD1-144
Solar/Wind Helper
0.041
315687AD1-152 GEN
Solar/Wind Helper
1.264
316156AD2-030 GEN
Solar/Wind Helper
0.053
315785AD2-033 C
Solar/Wind Helper
0.988
316313AB2-026
Solar/Wind Helper
0.06
270030AE2-140 GEN
Solar/Wind Harmer
0.924
316349AD2-085 GEN
Solar/Wind Helper
0.139
313527AB2-043 GEN
Solar/Wind Helper
0.402
316322AB2-045
Solar/Wind Helper
0.094
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
0.64
316083AB2-161 GEN
Solar/Wind Helper
0.144
316132AB2-190 GEN1
Solar/Wind Helper
0.212
316458AB2-190 GEN2
Solar/Wind Helper
0.212
316123AC1-075 GEN
Solar/Wind Helper
0.797
316375AC2-012 GEN
Solar/Wind Helper
0.351
316339AD2-160 GEN
Solar/Wind Helper
0.14
316239AB2-077_GEN
Solar/Wind Helper
0.163
316238AB2-078_GEN
Solar/Wind Helper
0.163
316237AB2-079_GEN
Solar/Wind Helper
0.163
316381AD1-082 GEN
Solar/Wind Helper
0.195
316233AE1-074 FULL
Solar/Wind Helper
0.055
316236AE1-162_GEN
Solar/Wind Helper
0.058
3145543BTLEBRO
Solar/Wind Harmer
-0.149
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3145543BTLEBRO
Solar/Wind Harmer
-0.186
3130086AYDLETT
Solar/Wind Helper
0.672
3138543CONSLDL
Solar/Wind Harmer
-0.1
3142053HEARTS
Solar/Wind Harmer
0.006
3142946ENON
Solar/Wind Helper
0.017
3142946ENON
Solar/Wind Helper
0.056
3144536CHRHLND
Solar/Wind Helper
0.028
3144873MCLAUGH
Solar/Wind Helper
0.005
3145453TOT5
Solar/Wind Harmer
0.004
3145493TOT1
Solar/Wind Harmer
0.014
3145493TOT1
Solar/Wind Harmer
0.007
3145573BETHELC
Solar/Wind Harmer
-0.164
3145573BETHELC
Solar/Wind Harmer
-0.164
3145603CNETO
Solar/Wind Harmer
0.003
3146073TAR RVR
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146083TARBORO
Solar/Wind Harmer
-0.164
3146233WITAKRS
Solar/Wind Harmer
0.031
3146233WITAKRS
Solar/Wind Harmer
-0.586
3146233WITAKRS
Solar/Wind Harmer
-0.1
942461AE2-259 GEN
Solar/Wind Helper
0.646
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
0.334
961601AG1-000A GEN
Solar/Wind Harmer
5.342
961611AG1-000B GEN
Solar/Wind Helper
0.254
961951AG1-038 GEN
Solar/Wind Helper
0.116
970085AG2-068 GEN
Solar/Wind Harmer
0.769
970087AG2-069 GEN
Solar/Wind Harmer
1.154
970223AG2-152 GEN
Solar/Wind Harmer
0.742
970581AG2-369 GEN
Solar/Wind Harmer
0.661
970917AG2-570 GEN
Solar/Wind Harmer
3.076
970919AG2-571 GEN
Solar/Wind Harmer
6.153
971367AH1-164 GEN
Solar/Wind Harmer
0.102
971629AH1-314 GEN
50/50
15.454
957601AF2-054 GEN
Solar/Wind Helper
0.053
957831AF2-077 GEN
Solar/Wind Helper
0.055
964211AG1-282 GEN
Solar/Wind Helper
0.05
971981AH1-535 GEN
Solar/Wind Harmer
0.298
315773AC2-141 GEN
Solar/Wind Helper
0.78
316003AC1-222 GEN
Solar/Wind Helper
0.967
316118AC1-105 GEN
Solar/Wind Helper
0.744
316129AC1-054 GEN
Solar/Wind Helper
0.25
316222AC1-221 GEN
Solar/Wind Helper
2.592
316263AC1-034 GEN
Solar/Wind Harmer
0.245
316283AC2-100 C
Solar/Wind Helper
2.441
316294AC1-161 GEN
Solar/Wind Helper
0.78
944201AF1-088_MTX
Adder
35.265
957141AF2-008_MTX
Adder
17.632
900033ID_568986
External Queue
0.2332763522863388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.691
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.452
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.359
CBM South 2LTFEXP_CBM-S2->PJM
CBM
30.725
NYPJM->LTFIMP_NY
CLTF
0.562
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.169
CPLELTFEXP_CPLE->PJM
CLTF
13.916
TVALTFEXP_TVA->PJM
CLTF
5.267
MECLTFEXP_MEC->PJM
CLTF
5.888
LAGNLTFEXP_LAGN->PJM
CLTF
10.611
SIGELTFEXP_SIGE->PJM
CLTF
0.177
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.495
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098

Details for [AG2-369] 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.58 %
Rating:694.0 MVA
Rating Type:B
MVA to Mitigate:746.59
MW Contribution:13.14
IPD Plant:AG2-369
Bus #Bus NameTypeMW Contribution
970581AG2-369 GEN
PJM_IPD
13.145
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-3'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
END
CONTINGENCY 'DVP_P1-2: LN 570_SRT-A-2'
 OPEN BRANCH FROM BUS 970916 TO BUS 970084 CKT 1   /*AG2-570 TP   500.0 - AG2-068 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 57062_SRT-W'
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1                /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 SET POSTCONTRATING 4018 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET POSTCONTRATING 4538 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
 SET PRECONTRATING 3984 BRANCH FROM BUS 314935 TO BUS 314940 CKT 1 /*8HERITAGE    500.0 - 8ROGERS RD   500.0
 SET PRECONTRATING 4261 BRANCH FROM BUS 314935 TO BUS 314936 CKT 1 /*8HERITAGE    500.0 - 8RAWLINGS    500.0
END
304070 to 316281 ckt 1

Light Load Analysis

The New Service Request AG2-369 was evaluated as a 86.0 MW injection

AG2-369 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 86.0 MW (86.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2CPLE/DVP
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
DVP_P4-2: 509T570_SRT-A
BreakerAC109.87 %541.0B594.427.68

Details for 6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line l/o DVP_P4-2: 509T570_SRT-A


Base Case Flowgate

Area:CPLE/DVP
Facility Description:
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 509T570_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.87 %
Rating:541.0 MVA
Rating Type:B
MVA to Mitigate:594.42
MW Contribution:7.68
Bus #Bus NameTypeMW Contribution
3142956BIRDNECK
Solar/Wind Helper
0.29
316075AC2-137 C
Solar/Wind Helper
0.279
316034AC1-036 C
Solar/Wind Helper
0.557
316036AC1-147 C
Solar/Wind Helper
0.321
316059AD1-063 C
Solar/Wind Helper
0.214
316159AE1-175 C
Solar/Wind Helper
0.301
316240AF1-291 C
Solar/Wind Helper
0.313
316246AF1-032 C
Solar/Wind Helper
0.219
316248AF1-058 C
Solar/Wind Helper
1.76
316258AE1-075 C
Solar/Wind Helper
0.293
316305AF2-043 C
Solar/Wind Helper
0.292
316314AB2-024 C
Solar/Wind Helper
0.285
316315AB2-025 C
Solar/Wind Helper
0.294
316316AC1-027 C
Solar/Wind Helper
0.259
316336AC2-165 C
Solar/Wind Helper
1.653
316382AG1-145 C
Solar/Wind Helper
0.302
316405AF2-144 C
Solar/Wind Helper
0.205
316404AE1-155 C
Solar/Wind Helper
1.741
316017AA1-139 ULT1
Solar/Wind Helper
0.898
316018AA1-139 ULT2
Solar/Wind Helper
0.898
316033AB2-134 GEN
Solar/Wind Helper
2.184
316388AE2-253 GEN
Solar/Wind Helper
0.754
316203AE2-005 GEN
Solar/Wind Helper
1.863
316441AF1-014 GEN
Solar/Wind Helper
0.285
316484AD2-074 GEN
Solar/Wind Helper
1.103
315833AF1-017_GEN
Solar/Wind Helper
0.589
316369SG1_INVT
Solar/Wind Helper
1.502
316487AF1-042 GEN
Solar/Wind Helper
0.577
315839AE2-212 C
Solar/Wind Helper
0.324
315662AE1-191 GEN
Solar/Wind Helper
1.147
315666AE1-190 GEN
Solar/Wind Helper
0.287
319010AE1-072 C
Solar/Wind Helper
2.194
315697AD1-025 GEN
Solar/Wind Helper
2.301
316185AD1-033 GEN
Solar/Wind Helper
1.106
315773AC2-141 GEN
Solar/Wind Helper
3.897
316280AD1-041 GEN
Solar/Wind Helper
0.717
316003AC1-222 GEN
Solar/Wind Helper
5.211
316478AD1-087 GEN
Solar/Wind Helper
3.961
316486AD2-202 GEN
Solar/Wind Helper
1.16
316072AD1-144
Solar/Wind Helper
0.222
315687AD1-152 GEN
Solar/Wind Helper
6.825
316156AD2-030 GEN
Solar/Wind Helper
0.284
315785AD2-033 C
Solar/Wind Helper
4.938
316313AB2-026
Solar/Wind Helper
0.326
270030AE2-140 GEN
Solar/Wind Harmer
10.168
316349AD2-085 GEN
Solar/Wind Helper
0.696
313527AB2-043 GEN
Solar/Wind Helper
2.164
316322AB2-045
Solar/Wind Helper
0.501
316359AB2-059 GEN
Solar/Wind Harmer
0
316131AB2-060 GEN
Solar/Wind Helper
3.454
316083AB2-161 GEN
Solar/Wind Helper
0.201
316132AB2-190 GEN1
Solar/Wind Helper
1.145
316458AB2-190 GEN2
Solar/Wind Helper
1.145
316263AC1-034 GEN
Solar/Wind Harmer
2.844
316129AC1-054 GEN
Solar/Wind Helper
1.347
316123AC1-075 GEN
Solar/Wind Helper
4.3
316118AC1-105 GEN
Solar/Wind Helper
4.018
316222AC1-221 GEN
Solar/Wind Helper
13.996
316375AC2-012 GEN
Solar/Wind Helper
1.755
316283AC2-100 C
Solar/Wind Helper
13.179
316339AD2-160 GEN
Solar/Wind Helper
0.754
316239AB2-077_GEN
Solar/Wind Helper
0.88
316238AB2-078_GEN
Solar/Wind Helper
0.88
316237AB2-079_GEN
Solar/Wind Helper
0.88
316294AC1-161 GEN
Solar/Wind Helper
4.209
316381AD1-082 GEN
Solar/Wind Helper
1.054
316233AE1-074 FULL
Solar/Wind Helper
0.298
316236AE1-162_GEN
Solar/Wind Helper
0.315
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.188
3145543BTLEBRO
Solar/Wind Harmer
0.151
3138543CONSLDL
Solar/Wind Harmer
0.102
3142053HEARTS
Solar/Wind Harmer
0.075
3145453TOT5
Solar/Wind Harmer
0.052
3145493TOT1
Solar/Wind Harmer
0.166
3145493TOT1
Solar/Wind Harmer
0.087
3145573BETHELC
Solar/Wind Harmer
0.166
3145573BETHELC
Solar/Wind Harmer
0.166
3145603CNETO
Solar/Wind Harmer
0.035
3146073TAR RVR
Solar/Wind Harmer
0.166
3146083TARBORO
Solar/Wind Harmer
0.166
3146083TARBORO
Solar/Wind Harmer
0.166
3146233WITAKRS
Solar/Wind Harmer
0.595
3146233WITAKRS
Solar/Wind Harmer
0.359
3146233WITAKRS
Solar/Wind Harmer
0.102
942461AE2-259 GEN
Solar/Wind Helper
3.485
943811AF1-049 GEN
Solar/Wind Harmer
0
961601AG1-000A GEN
Solar/Wind Harmer
2.81
961601AG1-000A GEN
Solar/Wind Harmer
3.875
961671AG1-007 GEN
Solar/Wind Harmer
0.313
961951AG1-038 GEN
Solar/Wind Helper
0.624
970085AG2-068 GEN
Solar/Wind Harmer
8.927
970087AG2-069 GEN
Solar/Wind Harmer
13.39
970223AG2-152 GEN
Solar/Wind Harmer
8.162
970413AG2-270 GEN
50/50
Charging
34.023
970535AG2-341 GEN
50/50
Charging
6.525
970581AG2-369 GEN
Solar/Wind Harmer
7.677
970865AG2-541 GEN
50/50
Charging
16.223
970909AG2-566 GEN
50/50
Charging
4.285
970917AG2-570 GEN
Solar/Wind Harmer
35.706
970919AG2-571 GEN
Solar/Wind Harmer
15.391
971367AH1-164 GEN
Solar/Wind Harmer
1.119
971443AH1-215 GEN
50/50
Charging
2.844
971629AH1-314 GEN
50/50
15.462
957601AF2-054 GEN
Solar/Wind Helper
0.286
957831AF2-077 GEN
Solar/Wind Helper
0.299
964211AG1-282 GEN
Solar/Wind Helper
0.27
971981AH1-535 GEN
Solar/Wind Harmer
2.856
971981AH1-535 GEN
Solar/Wind Harmer
3.116
944201AF1-088_MTX
Adder
35.322
957141AF2-008_MTX
Adder
14.034
900033ID_568986
External Queue
3.5454747676849365
CBM West 1LTFEXP_CBM-W1->PJM
CBM
43.161
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.725
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.69
CBM South 2LTFEXP_CBM-S2->PJM
CBM
28.334
NYPJM->LTFIMP_NY
CLTF
0.559
LGEELTFEXP_LGEE->PJM
CLTF
2.162
WECLTFEXP_WEC->PJM
CLTF
1.175
CPLELTFEXP_CPLE->PJM
CLTF
12.214
TVALTFEXP_TVA->PJM
CLTF
5.364
MECLTFEXP_MEC->PJM
CLTF
5.904
LAGNLTFEXP_LAGN->PJM
CLTF
10.551
SIGELTFEXP_SIGE->PJM
CLTF
0.178
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
28.118
AG2-052LTFEXP_AG2-052->PJM
LTF
0.066
AH1-155LTFEXP_AH1-155->PJM
LTF
0.099
CONTINGENCY 'DVP_P4-2: 509T570_SRT-A'
 OPEN BRANCH FROM BUS 314935 TO BUS 314945 CKT 1   /*8HERITAGE    500.0 - 8BRUNSWICK   500.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315102 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG1  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315103 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG2  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315104 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKG3  21.0
 OPEN BRANCH FROM BUS 314945 TO BUS 315105 CKT 1   /*8BRUNSWICK   500.0 - 1BRUNSWICKS1  19.0
 OPEN BRANCH FROM BUS 970916 TO BUS 314935 CKT 1   /*AG2-570 TP   500.0 - 8HERITAGE    500.0
 OPEN BUS 314945                                   /*8BRUNSWICK   500.0
 OPEN BUS 315102                                   /*1BRUNSWICKG1  21.0
 OPEN BUS 315103                                   /*1BRUNSWICKG2  21.0
 OPEN BUS 315104                                   /*1BRUNSWICKG3  21.0
 OPEN BUS 315105                                   /*1BRUNSWICKS1  19.0
END
304070 to 316281 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA1-145Four Rivers 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-041Edison 4kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-081Landing 12.47 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-153Remington-Gordonsville 230 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-019New Road 230 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-042Milton 69 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-140Axton-Danville 138 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-166Stockton 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-183Rogers Road 500 kVIn Service
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-283Gladys-Stone Mill 69 kVActive
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-075Harrisburg-Endless Caverns 230 kVSuspended
AF1-088Sullivan 345 kVActive
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-013Arnold's Corner-Dahlgren 230 kVEngineering & Procurement
AF2-035St. Johns 115 kVActive
AF2-041Nelson-Electric Junction 345 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-091Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-124Gladstone 138 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-154Ladysmith CT 230 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-210Northern Neck 34.5 kVEngineering & Procurement
AG1-221Poland Rd-Runway DP 230 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-397Walston 12 kVWithdrawn
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-494Boxwood-Riverville 138 kVActive
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-536Garner-Northern Neck 115 kVActive
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-010Peninsula-Whealton 115 kVActive
AG2-049Van Dorn 34.5 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-272Berry Hill 138 kVActive
AG2-304Liberty 230 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-320Ladysmith 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-366Garner Delivery Point - Lancaster 115 kVActive
AG2-382Cashie 230 kVActive
AG2-384Chesterfield 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-646Chesterfield 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-086Morrisville 230kVActive
AH1-087Morrisville 230kVActive
AH1-088Morrisville 230kVActive
AH1-089Morrisville 230kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-157Penniman - Waller 230 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-221Heritage 500 kVActive
AH1-223Poland Rd-Runway DP 230 kVActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-314East Danville 138 kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-345Remington 324 34.5 kVActive
AH1-377Clover- Farmville 230kVActive
AH1-387Meadowbrook-Greenland Gap 500kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-684Remington CT 230 kVActive
AH1-685Remington CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-693Remington CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-696Possum Point 230kVActive
AH1-712Cunningham 500 kVActive
AH1-713Mt. Storm 500kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-723Cunningham 500 kVActive
AH1-727Brambleton-Goose Creek 500kVActive
AH1-729Ocean Court 230 kVActive
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-068Murphy's 34.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
X3-066Church Hill 69kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
CPLE
RTEP ID / TO ID
(Pending) / TC2-CPLE-0001
Title
Person - VP Hendrick 230kV Line (Existing Line Uprate)
Description
Currently no costs since there is already a DEP project to reconductor to upgrade this line. This is the estimated ISD for the current project CPLE is developing. The Person - Hendrick 230 kV line will be reconductored with bundled 795 ACSS/TW and will have a rating 1195MVA.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 48 Months

Info

Note: AG2-369 contributes to the loading of an overloaded tie line facility between PJM and an affected system entity, which was identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line and will be confirmed in subsequent study phases, along with cost allocation of such upgrade if applicable, in coordination with the affected system.

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)

Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Study Pending
Duke Energy Progress – East (CPLE)Study Pending
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-369 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominion(Pending) / TC2-PH1-DOM-1036Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C$3,558,016
Dominionn9249.0 / TC1-PH2-DOM-043Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.$2,549,532
Dominion(Pending) / TC2-PH1-DOM-0044Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$1,081,064
Dominion(Pending) / TC2-PH1-DOM-0045Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.$429,050
Dominion(Pending) / TC2-PH1-DOM-1037Replace Breaker 56372 at Carson 500 kV with 5000 Amp device$113,248
Dominionn7568 / dom-369-TC2Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.$79,602
Dominionn9203.0 / TC1-PH2-DOM-008-TC2Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.$65,248
Dominion(Pending) / TC2-PH1-DOM-2043Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.$34,099
Dominionn7569 / dom-490-TC2Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.$28,898
Dominionn9644.0 / TC1-PH3-DOM-006-TC2Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.$18,202
Dominion(Pending) / TC1-PH1-DOM-079Replace Wave Trap 567 WT at Surry 500 kV$13,250
Dominionn9198.0 / TC1-PH2-DOM-003-TC2Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).$10,993
Dominionn9221.0 / TC1-PH3-DOM-015-TC2Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).$9,996
Dominion(Pending) / TC2-PH1-DOM-2065Replace switches 219324 and 219325 at Bremo 230 kV$4,160
Dominion(Pending) / TC2-PH1-DOM-2077Replace switches 29824 and 29825 at Bremo 230 kV$3,887
Dominion(Pending) / TC2-PH1-DOM-2085Replace wavetrap 298WT at Farmville 230 kV$3,060
Dominion(Pending) / TC2-PH1-DOM-2078Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV$2,429
Dominion(Pending) / TC2-PH1-DOM-2066Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV$2,192
Dominion(Pending) / TC2-PH1-DOM-2067Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV$2,192
Dominion(Pending) / TC2-PH1-DOM-2064Replace 2-1590 line lead on line 2193 at Fork Union 230 kV$2,192
Dominion(Pending) / TC2-PH1-DOM-2063Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$2,174
Dominion(Pending) / TC2-PH1-DOM-0080Replace switch 219326 at Bremo 230 kV$2,080
Dominion(Pending) / TC2-PH1-DOM-2069Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV$2,042
Dominion(Pending) / TC2-PH1-DOM-2073Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV$2,008
Dominion(Pending) / TC2-PH1-DOM-2071Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV$2,008
Dominion(Pending) / TC2-PH1-DOM-2076Replace wave trap 298 WT at Bremo 230 kV$1,944
Dominion(Pending) / TC2-PH1-DOM-2072Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV$1,081
Dominion(Pending) / TC2-PH1-DOM-2068Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C$1,007
Dominion(Pending) / TC2-PH1-DOM-2070Replace wave trap 2028WT at Fork Union 230 kV$884
Dominion(Pending) / TC1-PH3-DOM-007Replace Wave Trap 2028WT at Charlottesville$865
Dominion(Pending)No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)$0
Grand Total:$8,027,403

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.354
Type
Short Circuit
TO
Dominion
RTEP ID / TO ID
b4000.354
Title
Ladysmith substation breakers replacement: 574T575 and 568T581
Description
Expand Ladysmith substation to a add redundant circuit breakers to the middle breakers on both 500kV strings (574T575 and 568T581). The equipment including switches 57518, 57515, H115 will be replaced with 5000A equipment.
Cost Information
Time Estimate
Nov 14 2029

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 568T581_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P2-2: LADYSMITH B2_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: H1T581_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: H4T581_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 568T581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1036
Title
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Description
Wreck and rebuild 37.41 mi of 500 kV line 563 between Carson and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C
Total Cost ($USD)
$157,122,000
Allocated Cost ($USD)
$3,558,016
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
11.5 MW1.9%$3,017,571
AG2-069
17.3 MW2.9%$4,526,357
AG2-077
42.8 MW7.2%$11,239,940
AG2-338
12.9 MW2.2%$3,388,274
AG2-339
32.3 MW5.4%$8,470,817
AG2-369
13.6 MW2.3%$3,558,016
AG2-436
126.1 MW21.1%$33,090,702
AG2-440
10.3 MW1.7%$2,697,502
AG2-441
12.9 MW2.1%$3,372,271
AG2-442
14.7 MW2.5%$3,855,785
AG2-570
29.3 MW4.9%$7,697,403
AG2-571
11.7 MW2.0%$3,078,961
AG2-581
34.4 MW5.7%$9,015,459
AH1-528
55.3 MW9.2%$14,501,499
AH1-716
173.9 MW29.0%$45,611,444

System Reinforcement: n9249.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9249.0 / TC1-PH2-DOM-043
Title
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line.
Description
Construct new 37.26 mile line between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C. Station upgrades at Midlothian and Carson to accommodate new line. New Rating = 4356/4356/5009 MVA
Total Cost ($USD)
$231,012,000
Allocated Cost ($USD)
$2,549,532
Time Estimate
48 to 60 Months

Contributor

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
11.5 MW0.9%$2,162,271
AG2-069
17.3 MW1.4%$3,243,406
AG2-077
42.8 MW3.5%$8,054,092
AG2-369
13.6 MW1.1%$2,549,532
AG2-436
223.5 MW18.2%$42,020,468
AG2-440
6.8 MW0.6%$1,283,978
AG2-441
8.5 MW0.7%$1,605,066
AG2-442
14.7 MW1.2%$2,762,902
AG2-570
29.3 MW2.4%$5,515,652
AG2-571
11.7 MW1.0%$2,206,261
AG2-581
34.4 MW2.8%$6,460,118
AH1-528
98.4 MW8.0%$18,504,880
AH1-681
7.0 MW0.6%$1,323,268
AH1-712
157.5 MW12.8%$29,616,268
AH1-716
368.1 MW30.0%$69,191,915
AH1-723
183.6 MW14.9%$34,511,925

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0044
Title
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 4.5 miles of 230 kV Line 2204 between Black Walnut and Edmonson with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$17,100,000
Allocated Cost ($USD)
$1,081,064
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6BLACK WALNU-6EDMONSON 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.9 MW7.4%$1,256,962
AG2-069
14.9 MW11.0%$1,885,444
AG2-152
13.4 MW9.9%$1,689,186
AG2-369
8.5 MW6.3%$1,081,064
AG2-541
14.1 MW10.5%$1,788,832
AG2-570
39.8 MW29.4%$5,027,723
AG2-571
5.0 MW3.7%$636,448
AH1-314
13.5 MW10.0%$1,705,751
AH1-343
16.0 MW11.9%$2,028,591

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0045
Title
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.3 miles of 230 kV Line 2250 between Edmonson and Sedge Hill with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$31,540,000
Allocated Cost ($USD)
$429,050
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6SEDGE HILL-6EDMONSON 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
10.0 MW1.6%$498,905
AG2-069
14.9 MW2.4%$748,333
AG2-077
80.7 MW12.8%$4,042,771
AG2-152
13.4 MW2.1%$670,515
AG2-188
22.3 MW3.5%$1,116,290
AG2-198
21.6 MW3.4%$1,082,038
AG2-270
56.8 MW9.0%$2,844,056
AG2-369
8.6 MW1.4%$429,050
AG2-440
13.1 MW2.1%$656,895
AG2-441
16.4 MW2.6%$821,143
AG2-442
18.4 MW2.9%$919,642
AG2-541
14.2 MW2.2%$709,124
AG2-566
4.1 MW0.7%$205,461
AG2-570
39.8 MW6.3%$1,995,421
AG2-571
5.0 MW0.8%$252,582
AG2-581
59.5 MW9.4%$2,977,307
AH1-056
15.1 MW2.4%$754,092
AH1-314
13.5 MW2.1%$676,925
AH1-343
16.1 MW2.5%$804,067
AH1-377
54.4 MW8.6%$2,722,822
AH1-439
12.8 MW2.0%$641,972
AH1-528
119.2 MW18.9%$5,970,589

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-1037
Title
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Description
Replace Breaker 56372 at Carson 500 kV with 5000 Amp device
Total Cost ($USD)
$2,750,000
Allocated Cost ($USD)
$113,248
Time Estimate
42 to 48 Months

Contributor

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P1-2: LN 562_SRT-S-1
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
8CARSON-8MDLTHAN 500.0 kV Ckt 1 lineDVP_P4-2: 56272_SRT-S
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
17.0 MW3.6%$98,425
AG2-069
25.5 MW5.4%$147,638
AG2-338
12.9 MW2.7%$74,455
AG2-339
32.2 MW6.8%$186,137
AG2-369
19.6 MW4.1%$113,248
AG2-436
125.6 MW26.4%$725,541
AG2-440
6.8 MW1.4%$39,470
AG2-441
8.5 MW1.8%$49,340
AG2-442
17.6 MW3.7%$101,818
AG2-570
91.6 MW19.3%$529,615
AG2-571
11.6 MW2.4%$67,040
AG2-581
34.4 MW7.2%$198,584
AH1-528
72.5 MW15.2%$418,689

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$79,602
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$386,666
AG2-069
6.2 MW1.6%$580,093
AG2-077
11.7 MW3.0%$1,098,680
AG2-088
15.4 MW3.9%$1,445,217
AG2-151
21.6 MW5.5%$2,028,498
AG2-171
8.1 MW2.1%$763,488
AG2-188
27.6 MW7.0%$2,583,932
AG2-198
9.6 MW2.4%$898,502
AG2-213
7.4 MW1.9%$693,918
AG2-270
14.4 MW3.7%$1,346,206
AG2-338
2.8 MW0.7%$263,278
AG2-339
7.0 MW1.8%$658,101
AG2-369
0.8 MW0.2%$79,602
AG2-428
7.8 MW2.0%$733,766
AG2-436
28.3 MW7.2%$2,654,439
AG2-440
10.2 MW2.6%$958,602
AG2-441
12.8 MW3.3%$1,198,253
AG2-442
14.3 MW3.6%$1,341,987
AG2-566
5.9 MW1.5%$556,372
AG2-570
6.9 MW1.8%$647,038
AG2-571
2.8 MW0.7%$258,778
AG2-581
7.5 MW1.9%$699,918
AG2-583
23.2 MW5.9%$2,176,826
AH1-056
13.4 MW3.4%$1,260,884
AH1-217
11.3 MW2.9%$1,062,957
AH1-241
21.6 MW5.5%$2,028,498
AH1-377
20.2 MW5.1%$1,891,795
AH1-439
16.3 MW4.2%$1,531,101
AH1-528
13.7 MW3.5%$1,285,543
AH1-546
18.7 MW4.8%$1,751,062
AH1-687
20.7 MW5.3%$1,938,019

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$65,248
Time Estimate
45 to 46 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$316,942
AG2-069
6.2 MW1.6%$475,489
AG2-077
11.7 MW3.0%$900,563
AG2-088
15.4 MW4.0%$1,184,612
AG2-151
21.6 MW5.6%$1,662,714
AG2-188
27.6 MW7.2%$2,117,991
AG2-198
9.6 MW2.5%$736,482
AG2-213
7.4 MW1.9%$568,789
AG2-270
14.4 MW3.7%$1,103,455
AG2-338
2.8 MW0.7%$215,803
AG2-339
7.0 MW1.8%$539,431
AG2-369
0.8 MW0.2%$65,248
AG2-428
7.8 MW2.0%$601,451
AG2-436
28.3 MW7.4%$2,175,784
AG2-440
10.2 MW2.7%$785,745
AG2-441
12.8 MW3.3%$982,181
AG2-442
14.3 MW3.7%$1,099,996
AG2-566
5.9 MW1.5%$456,045
AG2-570
6.9 MW1.8%$530,362
AG2-571
2.8 MW0.7%$212,114
AG2-581
7.5 MW1.9%$573,707
AG2-583
23.2 MW6.0%$1,784,295
AH1-056
13.4 MW3.5%$1,033,519
AH1-217
11.3 MW2.9%$871,282
AH1-241
21.6 MW5.6%$1,662,714
AH1-377
20.2 MW5.2%$1,550,662
AH1-439
16.3 MW4.2%$1,255,009
AH1-528
13.7 MW3.6%$1,053,731
AH1-546
18.7 MW4.9%$1,435,306
AH1-687
20.7 MW5.4%$1,588,551

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2043
Title
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Description
Wreck and rebuild 0.93 miles of 230 kV Line 2241 between Hendrick and Persons with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C. Dominion portion of line only.
Total Cost ($USD)
$3,534,000
Allocated Cost ($USD)
$34,099
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6PERSON230 T-AC2-100 TAP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
9.2 MW1.1%$39,652
AG2-069
13.8 MW1.7%$59,477
AG2-077
67.9 MW8.3%$292,796
AG2-111
3.5 MW0.4%$15,101
AG2-112
3.7 MW0.4%$15,830
AG2-151
7.2 MW0.9%$31,260
AG2-152
14.7 MW1.8%$63,434
AG2-171
13.1 MW1.6%$56,405
AG2-188
21.4 MW2.6%$92,359
AG2-198
19.5 MW2.4%$83,993
AG2-213
17.4 MW2.1%$75,209
AG2-270
47.1 MW5.8%$203,423
AG2-272
5.3 MW0.7%$23,062
AG2-341
6.5 MW0.8%$27,834
AG2-369
7.9 MW1.0%$34,099
AG2-440
21.4 MW2.6%$92,165
AG2-441
26.7 MW3.3%$115,205
AG2-442
29.9 MW3.7%$129,034
AG2-522
10.0 MW1.2%$43,134
AG2-541
19.1 MW2.3%$82,250
AG2-566
9.3 MW1.1%$39,936
AG2-570
35.7 MW4.4%$154,059
AG2-571
15.5 MW1.9%$67,037
AG2-581
50.2 MW6.1%$216,526
AG2-583
7.5 MW0.9%$32,494
AG2-659
11.3 MW1.4%$48,915
AH1-056
20.7 MW2.5%$89,249
AH1-215
8.7 MW1.1%$37,455
AH1-241
6.9 MW0.8%$29,676
AH1-314
15.6 MW1.9%$67,343
AH1-343
22.0 MW2.7%$94,896
AH1-377
48.3 MW5.9%$208,557
AH1-408
10.5 MW1.3%$45,498
AH1-439
12.3 MW1.5%$53,152
AH1-528
100.6 MW12.3%$434,213
AH1-535
6.0 MW0.7%$25,767
AH1-546
7.3 MW0.9%$31,579
AH1-687
5.2 MW0.6%$22,479
AH1-690
28.7 MW3.5%$123,688
AH1-721
31.5 MW3.8%$135,756

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$28,898
Time Estimate
43 to 44 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$140,371
AG2-069
6.2 MW1.6%$210,591
AG2-077
11.7 MW3.0%$398,854
AG2-088
15.4 MW3.9%$524,657
AG2-151
21.6 MW5.5%$736,406
AG2-171
8.1 MW2.1%$277,169
AG2-188
27.6 MW7.0%$938,045
AG2-198
9.6 MW2.4%$326,183
AG2-213
7.4 MW1.9%$251,913
AG2-270
14.4 MW3.7%$488,713
AG2-338
2.8 MW0.7%$95,578
AG2-339
7.0 MW1.8%$238,911
AG2-369
0.8 MW0.2%$28,898
AG2-428
7.8 MW2.0%$266,379
AG2-436
28.3 MW7.2%$963,641
AG2-440
10.2 MW2.6%$348,002
AG2-441
12.8 MW3.3%$435,002
AG2-442
14.3 MW3.6%$487,182
AG2-566
5.9 MW1.5%$201,980
AG2-570
6.9 MW1.8%$234,894
AG2-571
2.8 MW0.7%$93,944
AG2-581
7.5 MW1.9%$254,091
AG2-583
23.2 MW5.9%$790,253
AH1-056
13.4 MW3.4%$457,739
AH1-217
11.3 MW2.9%$385,885
AH1-241
21.6 MW5.5%$736,406
AH1-377
20.2 MW5.1%$686,779
AH1-439
16.3 MW4.2%$555,836
AH1-528
13.7 MW3.5%$466,691
AH1-546
18.7 MW4.8%$635,688
AH1-687
20.7 MW5.3%$703,559

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$18,202
Time Estimate
Mar 31 2029

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$88,418
AG2-069
6.2 MW1.6%$132,648
AG2-077
11.7 MW3.0%$251,231
AG2-088
15.4 MW3.9%$330,472
AG2-151
21.6 MW5.5%$463,849
AG2-171
8.1 MW2.1%$174,584
AG2-188
27.6 MW7.0%$590,858
AG2-198
9.6 MW2.4%$205,457
AG2-213
7.4 MW1.9%$158,676
AG2-270
14.4 MW3.7%$307,832
AG2-338
2.8 MW0.7%$60,203
AG2-339
7.0 MW1.8%$150,486
AG2-369
0.8 MW0.2%$18,202
AG2-428
7.8 MW2.0%$167,787
AG2-436
28.3 MW7.2%$606,981
AG2-440
10.2 MW2.6%$219,200
AG2-441
12.8 MW3.3%$274,000
AG2-442
14.3 MW3.6%$306,867
AG2-566
5.9 MW1.5%$127,223
AG2-570
6.9 MW1.8%$147,956
AG2-571
2.8 MW0.7%$59,174
AG2-581
7.5 MW1.9%$160,048
AG2-583
23.2 MW5.9%$497,767
AH1-056
13.4 MW3.4%$288,322
AH1-217
11.3 MW2.9%$243,062
AH1-241
21.6 MW5.5%$463,849
AH1-377
20.2 MW5.1%$432,590
AH1-439
16.3 MW4.2%$350,111
AH1-528
13.7 MW3.5%$293,960
AH1-546
18.7 MW4.8%$400,409
AH1-687
20.7 MW5.3%$443,160

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH1-DOM-079
Title
Replace Wave Trap 567 WT at Surry 500 kV
Description
Replace Wave Trap 567 WT at Surry 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$13,250
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-338
9.2 MW1.9%$11,323
AG2-339
23.1 MW4.7%$28,307
AG2-369
10.8 MW2.2%$13,250
AG2-428
26.8 MW5.5%$32,911
AG2-436
90.1 MW18.4%$110,658
AG2-570
21.0 MW4.3%$25,801
AG2-571
8.4 MW1.7%$10,320
AH1-040
29.4 MW6.0%$36,133
AH1-528
39.5 MW8.1%$48,534
AH1-716
230.3 MW47.1%$282,762

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$10,993
Time Estimate
40 to 41 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.5 MW0.7%$14,813
AG2-069
8.3 MW1.1%$22,223
AG2-077
20.7 MW2.6%$55,670
AG2-088
33.4 MW4.2%$89,747
AG2-151
27.7 MW3.5%$74,401
AG2-171
17.4 MW2.2%$46,851
AG2-188
59.1 MW7.5%$159,015
AG2-198
20.5 MW2.6%$55,218
AG2-213
17.6 MW2.2%$47,443
AG2-270
30.6 MW3.9%$82,279
AG2-338
6.0 MW0.8%$16,245
AG2-339
15.1 MW1.9%$40,615
AG2-369
4.1 MW0.5%$10,993
AG2-428
17.0 MW2.2%$45,705
AG2-436
60.8 MW7.7%$163,599
AG2-440
20.9 MW2.7%$56,176
AG2-441
26.1 MW3.3%$70,215
AG2-442
30.6 MW3.9%$82,225
AG2-566
12.7 MW1.6%$34,201
AG2-570
14.8 MW1.9%$39,732
AG2-571
5.9 MW0.8%$15,890
AG2-581
16.0 MW2.0%$43,020
AG2-583
49.9 MW6.3%$134,134
AH1-056
28.8 MW3.7%$77,366
AH1-241
27.7 MW3.5%$74,401
AH1-377
43.2 MW5.5%$116,216
AH1-408
16.7 MW2.1%$44,930
AH1-439
35.0 MW4.5%$94,235
AH1-528
29.4 MW3.7%$79,147
AH1-546
40.1 MW5.1%$107,827
AH1-687
44.4 MW5.6%$119,347

System Reinforcement: n9221.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9221.0 / TC1-PH3-DOM-015-TC2
Title
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Description
Replace 230 kV Breaker 29822 at Bremo with a higher-rated device (Buckingham - Bremo).
Total Cost ($USD)
$2,057,335
Allocated Cost ($USD)
$9,996
Time Estimate
38 to 39 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$11,624
AG2-069
6.5 MW0.8%$17,436
AG2-077
47.9 MW6.2%$127,897
AG2-171
16.0 MW2.1%$42,650
AG2-188
71.8 MW9.3%$191,886
AG2-198
29.4 MW3.8%$78,462
AG2-213
21.3 MW2.8%$56,868
AG2-270
30.0 MW3.9%$80,033
AG2-338
2.8 MW0.4%$7,356
AG2-339
6.9 MW0.9%$18,392
AG2-341
7.8 MW1.0%$20,843
AG2-369
3.7 MW0.5%$9,996
AG2-436
28.6 MW3.7%$76,439
AG2-440
29.3 MW3.8%$78,406
AG2-441
36.7 MW4.8%$98,006
AG2-442
41.1 MW5.3%$109,766
AG2-522
9.8 MW1.3%$26,214
AG2-541
8.0 MW1.0%$21,431
AG2-566
10.4 MW1.4%$27,902
AG2-570
7.3 MW0.9%$19,429
AG2-571
2.9 MW0.4%$7,773
AG2-581
36.5 MW4.7%$97,645
AG2-659
10.8 MW1.4%$28,784
AH1-056
33.7 MW4.4%$90,107
AH1-215
8.3 MW1.1%$22,192
AH1-314
6.0 MW0.8%$15,905
AH1-343
9.2 MW1.2%$24,554
AH1-377
63.7 MW8.3%$170,330
AH1-408
11.4 MW1.5%$30,369
AH1-439
44.8 MW5.8%$119,784
AH1-528
73.3 MW9.5%$195,806
AH1-546
49.8 MW6.5%$133,048

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$4,160
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$5,606
AG2-069
4.1 MW1.1%$8,410
AG2-077
10.3 MW2.6%$21,068
AG2-088
16.7 MW4.2%$33,965
AG2-151
13.8 MW3.5%$28,157
AG2-171
8.7 MW2.2%$17,731
AG2-188
29.6 MW7.5%$60,179
AG2-198
10.3 MW2.6%$20,897
AG2-213
8.8 MW2.2%$17,955
AG2-270
15.3 MW3.9%$31,138
AG2-338
3.0 MW0.8%$6,148
AG2-339
7.5 MW1.9%$15,371
AG2-369
2.0 MW0.5%$4,160
AG2-428
8.5 MW2.2%$17,297
AG2-436
30.4 MW7.7%$61,914
AG2-440
10.4 MW2.7%$21,260
AG2-441
13.0 MW3.3%$26,573
AG2-442
15.3 MW3.9%$31,118
AG2-566
6.4 MW1.6%$12,943
AG2-570
7.4 MW1.9%$15,037
AG2-571
3.0 MW0.8%$6,013
AG2-581
8.0 MW2.0%$16,281
AG2-583
24.9 MW6.3%$50,763
AH1-056
14.4 MW3.7%$29,279
AH1-241
13.8 MW3.5%$28,157
AH1-377
21.6 MW5.5%$43,982
AH1-408
8.3 MW2.1%$17,004
AH1-439
17.5 MW4.5%$35,663
AH1-528
14.7 MW3.7%$29,953
AH1-546
20.0 MW5.1%$40,807
AH1-687
22.2 MW5.6%$45,167

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2077
Title
Replace switches 29824 and 29825 at Bremo 230 kV
Description
Replace switches 29824 and 29825 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$3,887
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$4,520
AG2-069
6.5 MW0.8%$6,780
AG2-077
47.9 MW6.2%$49,733
AG2-171
16.0 MW2.1%$16,585
AG2-188
71.8 MW9.3%$74,615
AG2-198
29.4 MW3.8%$30,510
AG2-213
21.3 MW2.8%$22,113
AG2-270
30.0 MW3.9%$31,121
AG2-338
2.8 MW0.4%$2,861
AG2-339
6.9 MW0.9%$7,152
AG2-341
7.8 MW1.0%$8,105
AG2-369
3.7 MW0.5%$3,887
AG2-436
28.6 MW3.7%$29,724
AG2-440
29.3 MW3.8%$30,488
AG2-441
36.7 MW4.8%$38,110
AG2-442
41.1 MW5.3%$42,683
AG2-522
9.8 MW1.3%$10,193
AG2-541
8.0 MW1.0%$8,333
AG2-566
10.4 MW1.4%$10,850
AG2-570
7.3 MW0.9%$7,555
AG2-571
2.9 MW0.4%$3,023
AG2-581
36.5 MW4.7%$37,970
AG2-659
10.8 MW1.4%$11,193
AH1-056
33.7 MW4.4%$35,038
AH1-215
8.3 MW1.1%$8,629
AH1-314
6.0 MW0.8%$6,185
AH1-343
9.2 MW1.2%$9,548
AH1-377
63.7 MW8.3%$66,233
AH1-408
11.4 MW1.5%$11,809
AH1-439
44.8 MW5.8%$46,578
AH1-528
73.3 MW9.5%$76,140
AH1-546
49.8 MW6.5%$51,736

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2085
Title
Replace wavetrap 298WT at Farmville 230 kV
Description
Replace wavetrap 298WT at Farmville 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$3,060
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.4 MW0.9%$3,558
AG2-069
6.5 MW1.3%$5,337
AG2-077
36.3 MW7.4%$29,621
AG2-171
12.1 MW2.5%$9,886
AG2-198
22.3 MW4.5%$18,192
AG2-213
16.2 MW3.3%$13,181
AG2-270
29.9 MW6.1%$24,400
AG2-338
2.8 MW0.6%$2,252
AG2-339
6.9 MW1.4%$5,631
AG2-341
7.8 MW1.6%$6,369
AG2-369
3.8 MW0.8%$3,060
AG2-436
28.7 MW5.9%$23,401
AG2-440
22.3 MW4.5%$18,175
AG2-441
27.8 MW5.7%$22,719
AG2-442
31.2 MW6.4%$25,446
AG2-522
7.4 MW1.5%$6,073
AG2-541
6.1 MW1.2%$4,955
AG2-566
10.4 MW2.1%$8,523
AG2-570
7.3 MW1.5%$5,948
AG2-571
2.9 MW0.6%$2,379
AG2-581
27.7 MW5.7%$22,616
AG2-659
8.2 MW1.7%$6,667
AH1-056
29.2 MW6.0%$23,852
AH1-215
6.3 MW1.3%$5,144
AH1-314
6.0 MW1.2%$4,871
AH1-343
7.0 MW1.4%$5,678
AH1-377
48.4 MW9.9%$39,485
AH1-408
9.0 MW1.8%$7,347
AH1-528
55.4 MW11.3%$45,231

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2078
Title
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 298 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$2,429
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$2,825
AG2-069
6.5 MW0.8%$4,237
AG2-077
47.9 MW6.2%$31,083
AG2-171
16.0 MW2.1%$10,365
AG2-188
71.8 MW9.3%$46,635
AG2-198
29.4 MW3.8%$19,069
AG2-213
21.3 MW2.8%$13,821
AG2-270
30.0 MW3.9%$19,451
AG2-338
2.8 MW0.4%$1,788
AG2-339
6.9 MW0.9%$4,470
AG2-341
7.8 MW1.0%$5,065
AG2-369
3.7 MW0.5%$2,429
AG2-436
28.6 MW3.7%$18,577
AG2-440
29.3 MW3.8%$19,055
AG2-441
36.7 MW4.8%$23,819
AG2-442
41.1 MW5.3%$26,677
AG2-522
9.8 MW1.3%$6,371
AG2-541
8.0 MW1.0%$5,208
AG2-566
10.4 MW1.4%$6,781
AG2-570
7.3 MW0.9%$4,722
AG2-571
2.9 MW0.4%$1,889
AG2-581
36.5 MW4.7%$23,731
AG2-659
10.8 MW1.4%$6,996
AH1-056
33.7 MW4.4%$21,899
AH1-215
8.3 MW1.1%$5,393
AH1-314
6.0 MW0.8%$3,865
AH1-343
9.2 MW1.2%$5,967
AH1-377
63.7 MW8.3%$41,396
AH1-408
11.4 MW1.5%$7,381
AH1-439
44.8 MW5.8%$29,111
AH1-528
73.3 MW9.5%$47,587
AH1-546
49.8 MW6.5%$32,335

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2066
Title
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Description
Replace 2-636 ACSR line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$2,192
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2067
Title
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Description
Replace 3 1/2" pipe line lead on line 2193 at Bremo 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$2,192
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2064
Title
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Description
Replace 2-1590 line lead on line 2193 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$2,192
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.6%$2,954
AG2-069
4.1 MW0.9%$4,432
AG2-077
10.3 MW2.2%$11,102
AG2-088
16.7 MW3.6%$17,891
AG2-151
13.8 MW3.0%$14,838
AG2-171
8.7 MW1.9%$9,343
AG2-188
36.7 MW7.9%$39,350
AG2-198
13.5 MW2.9%$14,479
AG2-213
11.6 MW2.5%$12,458
AG2-270
15.3 MW3.3%$16,409
AG2-338
3.0 MW0.6%$3,240
AG2-339
7.5 MW1.6%$8,100
AG2-369
2.0 MW0.4%$2,192
AG2-428
9.9 MW2.1%$10,624
AG2-436
30.4 MW6.5%$32,614
AG2-440
11.3 MW2.4%$12,126
AG2-441
14.1 MW3.0%$15,157
AG2-442
20.1 MW4.3%$21,562
AG2-566
6.4 MW1.4%$6,821
AG2-570
23.3 MW5.0%$25,024
AG2-571
3.0 MW0.6%$3,168
AG2-581
10.5 MW2.3%$11,289
AG2-583
32.8 MW7.0%$35,169
AH1-056
16.6 MW3.6%$17,769
AH1-241
13.8 MW3.0%$14,838
AH1-377
28.4 MW6.1%$30,476
AH1-408
8.3 MW1.8%$8,960
AH1-439
23.0 MW4.9%$24,707
AH1-528
19.4 MW4.2%$20,828
AH1-546
26.4 MW5.7%$28,317
AH1-687
22.1 MW4.8%$23,765

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2063
Title
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.11 miles of 230 kV line 2193 between Fork Union and Bremo Dist with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$418,000
Allocated Cost ($USD)
$2,174
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,929
AG2-069
4.1 MW1.1%$4,394
AG2-077
10.3 MW2.6%$11,008
AG2-088
16.7 MW4.2%$17,747
AG2-151
13.8 MW3.5%$14,712
AG2-171
8.7 MW2.2%$9,264
AG2-188
29.6 MW7.5%$31,444
AG2-198
10.3 MW2.6%$10,919
AG2-213
8.8 MW2.2%$9,381
AG2-270
15.3 MW3.9%$16,270
AG2-338
3.0 MW0.8%$3,212
AG2-339
7.5 MW1.9%$8,031
AG2-369
2.0 MW0.5%$2,174
AG2-428
8.5 MW2.2%$9,038
AG2-436
30.4 MW7.7%$32,350
AG2-440
10.4 MW2.7%$11,108
AG2-441
13.0 MW3.3%$13,884
AG2-442
15.3 MW3.9%$16,259
AG2-566
6.4 MW1.6%$6,763
AG2-570
7.4 MW1.9%$7,857
AG2-571
3.0 MW0.8%$3,142
AG2-581
8.0 MW2.0%$8,507
AG2-583
24.9 MW6.3%$26,524
AH1-056
14.4 MW3.7%$15,298
AH1-241
13.8 MW3.5%$14,712
AH1-377
21.6 MW5.5%$22,981
AH1-408
8.3 MW2.1%$8,885
AH1-439
17.5 MW4.5%$18,634
AH1-528
14.7 MW3.7%$15,651
AH1-546
20.0 MW5.1%$21,322
AH1-687
22.2 MW5.6%$23,600

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0080
Title
Replace switch 219326 at Bremo 230 kV
Description
Replace switch 219326 at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$2,080
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
2.8 MW0.7%$2,803
AG2-069
4.1 MW1.1%$4,205
AG2-077
10.3 MW2.6%$10,534
AG2-088
16.7 MW4.2%$16,982
AG2-151
13.8 MW3.5%$14,079
AG2-171
8.7 MW2.2%$8,865
AG2-188
29.6 MW7.5%$30,090
AG2-198
10.3 MW2.6%$10,449
AG2-213
8.8 MW2.2%$8,977
AG2-270
15.3 MW3.9%$15,569
AG2-338
3.0 MW0.8%$3,074
AG2-339
7.5 MW1.9%$7,685
AG2-369
2.0 MW0.5%$2,080
AG2-428
8.5 MW2.2%$8,649
AG2-436
30.4 MW7.7%$30,957
AG2-440
10.4 MW2.7%$10,630
AG2-441
13.0 MW3.3%$13,286
AG2-442
15.3 MW3.9%$15,559
AG2-566
6.4 MW1.6%$6,472
AG2-570
7.4 MW1.9%$7,518
AG2-571
3.0 MW0.8%$3,007
AG2-581
8.0 MW2.0%$8,140
AG2-583
24.9 MW6.3%$25,382
AH1-056
14.4 MW3.7%$14,640
AH1-241
13.8 MW3.5%$14,079
AH1-377
21.6 MW5.5%$21,991
AH1-408
8.3 MW2.1%$8,502
AH1-439
17.5 MW4.5%$17,832
AH1-528
14.7 MW3.7%$14,977
AH1-546
20.0 MW5.1%$20,404
AH1-687
22.2 MW5.6%$22,584

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2069
Title
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Description
Replace 2-1590 AAC line lead on line 2028 at Fork Union 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$2,042
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,636
AG2-069
8.1 MW1.7%$8,454
AG2-077
15.4 MW3.2%$16,005
AG2-088
15.4 MW3.2%$15,999
AG2-151
28.4 MW5.9%$29,526
AG2-188
34.2 MW7.1%$35,506
AG2-198
12.6 MW2.6%$13,084
AG2-213
9.7 MW2.0%$10,104
AG2-270
14.4 MW3.0%$14,911
AG2-338
2.8 MW0.6%$2,916
AG2-339
7.0 MW1.5%$7,289
AG2-369
2.0 MW0.4%$2,042
AG2-428
9.1 MW1.9%$9,472
AG2-436
28.3 MW5.9%$29,388
AG2-440
13.4 MW2.8%$13,958
AG2-441
16.8 MW3.5%$17,448
AG2-442
18.8 MW3.9%$19,541
AG2-566
5.9 MW1.2%$6,162
AG2-570
21.8 MW4.5%$22,634
AG2-571
2.8 MW0.6%$2,865
AG2-581
9.8 MW2.0%$10,199
AG2-583
30.5 MW6.3%$31,692
AH1-056
15.5 MW3.2%$16,081
AH1-217
14.9 MW3.1%$15,470
AH1-241
27.0 MW5.6%$28,031
AH1-377
26.5 MW5.5%$27,548
AH1-439
21.5 MW4.5%$22,291
AH1-528
18.1 MW3.8%$18,786
AH1-546
24.6 MW5.1%$25,534
AH1-687
20.6 MW4.3%$21,427

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2073
Title
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Charlottesville and Mt Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$2,008
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2071
Title
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Description
Replace 2-1590 line lead on line 2028 at Mt. Eagle 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$2,008
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.4 MW1.1%$5,542
AG2-069
8.1 MW1.7%$8,314
AG2-077
15.4 MW3.1%$15,739
AG2-088
15.4 MW3.1%$15,733
AG2-151
28.4 MW5.8%$29,035
AG2-171
8.1 MW1.7%$8,316
AG2-188
34.2 MW7.0%$34,915
AG2-198
12.6 MW2.6%$12,866
AG2-213
9.7 MW2.0%$9,936
AG2-270
14.4 MW2.9%$14,663
AG2-338
2.8 MW0.6%$2,868
AG2-339
7.0 MW1.4%$7,168
AG2-369
2.0 MW0.4%$2,008
AG2-428
9.1 MW1.9%$9,314
AG2-436
28.3 MW5.8%$28,899
AG2-440
13.4 MW2.7%$13,726
AG2-441
16.8 MW3.4%$17,157
AG2-442
18.8 MW3.8%$19,216
AG2-566
5.9 MW1.2%$6,060
AG2-570
21.8 MW4.5%$22,257
AG2-571
2.8 MW0.6%$2,818
AG2-581
9.8 MW2.0%$10,029
AG2-583
30.5 MW6.2%$31,165
AH1-056
15.5 MW3.2%$15,813
AH1-217
14.9 MW3.0%$15,213
AH1-241
27.0 MW5.5%$27,565
AH1-377
26.5 MW5.4%$27,090
AH1-439
21.5 MW4.4%$21,920
AH1-528
18.1 MW3.7%$18,474
AH1-546
24.6 MW5.0%$25,110
AH1-687
20.6 MW4.2%$21,071

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2076
Title
Replace wave trap 298 WT at Bremo 230 kV
Description
Replace wave trap 298 WT at Bremo 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$1,944
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.3 MW0.6%$2,260
AG2-069
6.5 MW0.8%$3,390
AG2-077
47.9 MW6.2%$24,866
AG2-171
16.0 MW2.1%$8,292
AG2-188
71.8 MW9.3%$37,308
AG2-198
29.4 MW3.8%$15,255
AG2-213
21.3 MW2.8%$11,057
AG2-270
30.0 MW3.9%$15,561
AG2-338
2.8 MW0.4%$1,430
AG2-339
6.9 MW0.9%$3,576
AG2-341
7.8 MW1.0%$4,052
AG2-369
3.7 MW0.5%$1,944
AG2-436
28.6 MW3.7%$14,862
AG2-440
29.3 MW3.8%$15,244
AG2-441
36.7 MW4.8%$19,055
AG2-442
41.1 MW5.3%$21,341
AG2-522
9.8 MW1.3%$5,097
AG2-541
8.0 MW1.0%$4,167
AG2-566
10.4 MW1.4%$5,425
AG2-570
7.3 MW0.9%$3,778
AG2-571
2.9 MW0.4%$1,511
AG2-581
36.5 MW4.7%$18,985
AG2-659
10.8 MW1.4%$5,596
AH1-056
33.7 MW4.4%$17,519
AH1-215
8.3 MW1.1%$4,315
AH1-314
6.0 MW0.8%$3,092
AH1-343
9.2 MW1.2%$4,774
AH1-377
63.7 MW8.3%$33,117
AH1-408
11.4 MW1.5%$5,905
AH1-439
44.8 MW5.8%$23,289
AH1-528
73.3 MW9.5%$38,070
AH1-546
49.8 MW6.5%$25,868

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$1,081
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$5,253
AG2-069
6.2 MW1.6%$7,881
AG2-077
11.7 MW3.0%$14,927
AG2-088
15.4 MW3.9%$19,635
AG2-151
21.6 MW5.5%$27,560
AG2-171
8.1 MW2.1%$10,373
AG2-188
27.6 MW7.0%$35,106
AG2-198
9.6 MW2.4%$12,207
AG2-213
7.4 MW1.9%$9,428
AG2-270
14.4 MW3.7%$18,290
AG2-338
2.8 MW0.7%$3,577
AG2-339
7.0 MW1.8%$8,941
AG2-369
0.8 MW0.2%$1,081
AG2-428
7.8 MW2.0%$9,969
AG2-436
28.3 MW7.2%$36,064
AG2-440
10.2 MW2.6%$13,024
AG2-441
12.8 MW3.3%$16,280
AG2-442
14.3 MW3.6%$18,233
AG2-566
5.9 MW1.5%$7,559
AG2-570
6.9 MW1.8%$8,791
AG2-571
2.8 MW0.7%$3,516
AG2-581
7.5 MW1.9%$9,509
AG2-583
23.2 MW5.9%$29,575
AH1-056
13.4 MW3.4%$17,131
AH1-217
11.3 MW2.9%$14,442
AH1-241
21.6 MW5.5%$27,560
AH1-377
20.2 MW5.1%$25,702
AH1-439
16.3 MW4.2%$20,802
AH1-528
13.7 MW3.5%$17,466
AH1-546
18.7 MW4.8%$23,790
AH1-687
20.7 MW5.3%$26,330

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2068
Title
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Description
Wreck and rebuild 0.12 miles of 230 kV line 2028 between Fork Union and Grape Vine with (2) 768.2 ACSS/TW (20/7) "Maumee" @ 250C
Total Cost ($USD)
$456,000
Allocated Cost ($USD)
$1,007
Time Estimate
36 to 42 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,893
AG2-069
6.2 MW1.6%$7,340
AG2-077
11.7 MW3.0%$13,902
AG2-088
15.4 MW4.0%$18,287
AG2-151
21.6 MW5.6%$25,667
AG2-188
27.6 MW7.2%$32,695
AG2-198
9.6 MW2.5%$11,369
AG2-213
7.4 MW1.9%$8,780
AG2-270
14.4 MW3.7%$17,034
AG2-338
2.8 MW0.7%$3,331
AG2-339
7.0 MW1.8%$8,327
AG2-369
0.8 MW0.2%$1,007
AG2-428
7.8 MW2.0%$9,284
AG2-436
28.3 MW7.4%$33,587
AG2-440
10.2 MW2.7%$12,129
AG2-441
12.8 MW3.3%$15,162
AG2-442
14.3 MW3.7%$16,980
AG2-566
5.9 MW1.5%$7,040
AG2-570
6.9 MW1.8%$8,187
AG2-571
2.8 MW0.7%$3,274
AG2-581
7.5 MW1.9%$8,856
AG2-583
23.2 MW6.0%$27,544
AH1-056
13.4 MW3.5%$15,954
AH1-217
11.3 MW2.9%$13,450
AH1-241
21.6 MW5.6%$25,667
AH1-377
20.2 MW5.2%$23,937
AH1-439
16.3 MW4.2%$19,373
AH1-528
13.7 MW3.6%$16,266
AH1-546
18.7 MW4.9%$22,156
AH1-687
20.7 MW5.4%$24,522

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2070
Title
Replace wave trap 2028WT at Fork Union 230 kV
Description
Replace wave trap 2028WT at Fork Union 230 kV
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$884
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,292
AG2-069
6.2 MW1.6%$6,439
AG2-077
11.7 MW3.0%$12,195
AG2-088
15.4 MW4.0%$16,041
AG2-151
21.6 MW5.6%$22,515
AG2-188
27.6 MW7.2%$28,680
AG2-198
9.6 MW2.5%$9,973
AG2-213
7.4 MW1.9%$7,702
AG2-270
14.4 MW3.7%$14,942
AG2-338
2.8 MW0.7%$2,922
AG2-339
7.0 MW1.8%$7,304
AG2-369
0.8 MW0.2%$884
AG2-428
7.8 MW2.0%$8,144
AG2-436
28.3 MW7.4%$29,462
AG2-440
10.2 MW2.7%$10,640
AG2-441
12.8 MW3.3%$13,300
AG2-442
14.3 MW3.7%$14,895
AG2-566
5.9 MW1.5%$6,175
AG2-570
6.9 MW1.8%$7,182
AG2-571
2.8 MW0.7%$2,872
AG2-581
7.5 MW1.9%$7,769
AG2-583
23.2 MW6.0%$24,161
AH1-056
13.4 MW3.5%$13,995
AH1-217
11.3 MW2.9%$11,798
AH1-241
21.6 MW5.6%$22,515
AH1-377
20.2 MW5.2%$20,997
AH1-439
16.3 MW4.2%$16,994
AH1-528
13.7 MW3.6%$14,269
AH1-546
18.7 MW4.9%$19,435
AH1-687
20.7 MW5.4%$21,511

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$865
Time Estimate
16 to 18 Months

Contributor

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
4.1 MW1.1%$4,203
AG2-069
6.2 MW1.6%$6,305
AG2-077
11.7 MW3.0%$11,942
AG2-088
15.4 MW3.9%$15,708
AG2-151
21.6 MW5.5%$22,048
AG2-171
8.1 MW2.1%$8,298
AG2-188
27.6 MW7.0%$28,085
AG2-198
9.6 MW2.4%$9,766
AG2-213
7.4 MW1.9%$7,542
AG2-270
14.4 MW3.7%$14,632
AG2-338
2.8 MW0.7%$2,862
AG2-339
7.0 MW1.8%$7,153
AG2-369
0.8 MW0.2%$865
AG2-428
7.8 MW2.0%$7,975
AG2-436
28.3 MW7.2%$28,851
AG2-440
10.2 MW2.6%$10,419
AG2-441
12.8 MW3.3%$13,024
AG2-442
14.3 MW3.6%$14,586
AG2-566
5.9 MW1.5%$6,047
AG2-570
6.9 MW1.8%$7,033
AG2-571
2.8 MW0.7%$2,813
AG2-581
7.5 MW1.9%$7,607
AG2-583
23.2 MW5.9%$23,660
AH1-056
13.4 MW3.4%$13,705
AH1-217
11.3 MW2.9%$11,553
AH1-241
21.6 MW5.5%$22,048
AH1-377
20.2 MW5.1%$20,562
AH1-439
16.3 MW4.2%$16,641
AH1-528
13.7 MW3.5%$13,973
AH1-546
18.7 MW4.8%$19,032
AH1-687
20.7 MW5.3%$21,064

System Reinforcement: n9220.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9220.0 / TC1-PH2-DOM-033
Title
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 15.42 miles of 230 kV Line #298 from Buckingham to Bremo Substations with twin bundled (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$44,465,922
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-546 TP 230.0 kV Ckt 1 line(Any)
6BREMO-AH1-546 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9217.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9217.0 / TC1-PH2-DOM-028
Title
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Description
Wreck and rebuild 12.73 miles of 230 kV Line 298 from Buckingham to Farmville Substations with twin bundled (2) 768 ACSS/TW (20/7) "MAUMEE" conductor.
Total Cost ($USD)
$40,414,822
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 is a potential Aggregate Pool Contributor.

FacilityContingency
6BUCKING-AH1-439 TP 230.0 kV Ckt 1 line(Any)
AG2-188 TP-AH1-439 TP 230.0 kV Ckt 1 line(Any)
6FARMVIL-AG2-188 TP 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3694.8
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3694.8
Title
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA.
Description
Partial wreck and rebuild 10.34 miles of 230 kV line #249 Carson-Locks to achieve a minimum summer emergency rating of 1572 MVA. Upgrade terminal equipment at Carson and Locks to not limit the new conductor rating.
Cost Information
Time Estimate
May 03 2025

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it is already in-service.

FacilityContingency
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 line(Any)
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.319
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.319
Title
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2002 Carson – Poe. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.320
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.320
Title
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Carson substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.321
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.321
Title
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Description
At Poe substation, upgrade all line #2002 terminal equipment at Carson to 4000A. CCVTs will also be replaced due to aging.
Cost Information
Time Estimate
Mar 20 2030

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CARSON-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9378.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9378.0 / TC1-PH3-DOM-010
Title
Replace existing 230/500 kV Carson transformer 2 with (4)-480 MVA single phase transformers.
Description
Replace Existing 230/500 kV Carson transformer 2 with (4)-480 MVA Single Phase transformers.
Total Cost ($USD)
$37,801,301
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 is a potential Aggregate Pool Contributor.

FacilityContingency
6CARSON-8CARSON 230.0/500.0 kV Ckt 2 transformer(Any)

System Reinforcement: b4000.314
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.314
Title
Reconductor 230kV Line #2003 Chesterfield – Tyler segment. New conductor has a summer rating of 1573 MVA
Description
Reconductor 230kV Line #2003 Chesterfield – Tyler segment. New conductor has a summer rating of 1573 MVA
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CHESTF B-6TYLER 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.317
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.317
Title
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Description
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Cost Information
Time Estimate
Apr 22 2030

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
6CHESTF B-6TYLER 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9379.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9379.0 / TC1-PH3-DOM-011
Title
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase transformers.
Description
Replace existing 230/500 kV Transformer 1 at Midlothian with (4)-480 MVA Single Phase 500/230 kV transformers.
Total Cost ($USD)
$37,836,293
Allocated Cost ($USD)
$0
Time Estimate
Dec 31 2029

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6MDLTHAN-8MDLTHAN 230.0/500.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2097
Title
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Description
Build a new 11.95 mile line from Aspen 230 kV to Dickerson 230 kV with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor at 250 degrees C.
Total Cost ($USD)
$33,230,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 lineAP_P1-2_PE-500-406T_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019F_SRT-SL
DICKH230-6EDFERRY 230.0 kV Ckt 1 lineAP_P2-3_PE-500-019B_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
DICKH230-6EDFERRY 230.0 kV Ckt 1 linePEPCO_P1_5070_SRT-A
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.315
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.315
Title
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Description
Reconductor 230kV Line #2003 Tyler – Poe segment. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.316
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.316
Title
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Description
At Poe substation, uprate all Line #2003 terminal equipment, line leads, and bus to be rated to 4000A.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.317
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.317
Title
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Description
At Tyler substation, upgrade the necessary line terminal equipment to maintain 4000A at Tyler substation.
Cost Information
Time Estimate
Apr 22 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6TYLER1-6POE 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.


System Reinforcement: n9139.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9139.0 / TC1-PH1-DOM-073
Title
Wreck and rebuild 37.41 miles of 500kV line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" and associated substation work.
Description
Wreck and rebuild 37.41 miles of 500kV transmission line 563 between Midlothian and Carson with (3) 1351.5 ACSR (45/7) "Dipper" at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA. Remove wave traps.
Total Cost ($USD)
$245,455,768
Allocated Cost ($USD)
$0
Time Estimate
69 to 70 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8CARSON-8MDLTHAN 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 563_SRT-S

System Reinforcement: n9138.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9138.0 / TC1-PH1-DOM-070
Title
Wreck and rebuild 22.59 miles of Line #511 between Carson and Rawlings Substations with three (3) 1351 ACSS/TW and associated substation work.
Description
Wreck and rebuild 22.59 miles of Line 511 between Carson and Rawlings with three (3) 1351 ACSS/TW and associated substation work.
Total Cost ($USD)
$111,130,292
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9250.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9250.0 / TC1-PH2-DOM-044
Title
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Description
Construct a new 22.59 mile line between Carson and Rawlings Substations.
Total Cost ($USD)
$108,728,086
Allocated Cost ($USD)
$0
Time Estimate
60 to 61 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 is a potential Aggregate Pool Contributor.

FacilityContingency
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-A
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51172_SRT-S
8ROGERS RD-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 511T544_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
AE2-094 TP-AG2-436 TP 500.0 kV Ckt 1 lineDVP_P4-2: 51192_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S-C
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 511_SRT-S
8CARSON-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3692
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3692
Title
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy.
Description
Rebuild approximately 27.7-miles of 500 kV transmission line from Elmont to Chickahominy with current 500 kV standards construction practices to achieve a summer rating of 4330 MVA. Projected ISD: 06/01/2026
Cost Information
Time Estimate
Jun 01 2026

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8CHCKAHM-8ELMONT 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9264.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9264.0 / TC1-PH1-DOM-080
Title
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Description
Replace Line Lead at Surry for increased rating on Line 567 8SURRY 500 KV to 8CHCKAHM 500 KV ckt 1.
Total Cost ($USD)
$582,006
Allocated Cost ($USD)
$0
Time Estimate
12 to 13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 is a potential Aggregate Pool Contributor.

FacilityContingency
8CHCKAHM-8SURRY 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9191.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9191.0 / TC1-PH1-DOM-090
Title
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor and associated substation work.
Description
Rebuild 41.13 miles of line 576 between North Anna and Midlothian with triple bundled (3) 1351.5 ACSR (45/7) "Dipper" conductor at 110 degrees C and associated substation work to achieve new rating of 4356/4356/5009 MVA.
Total Cost ($USD)
$256,706,175
Allocated Cost ($USD)
$0
Time Estimate
74 to 75 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.353
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.353
Title
Upgrade 500kV terminal equipment at Elmont substation.
Description
Upgrade 500kV terminal equipment at Elmont substation.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P2-2: ELMONT B1_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: H1T553_SRT-S

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)

System Reinforcement: n9248.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9248.0 / TC1-PH2-DOM-042
Title
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Description
Construct new 41.13 mile line between North Anna and Midlothian with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN" at 145 degrees C. Station upgrades at North Anna and Midlothian to accommodate new line.
Total Cost ($USD)
$345,766,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 574_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P1-2: LN 576_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P1-2: LN 557_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: WT576_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 lineDVP_P4-2: 57602_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H2T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 557T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: H1T574_SRT-S
8MDLTHAN-8NO ANNA 500.0 kV Ckt 1 lineDVP_P4-2: 574T575_SRT-S

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8NO ANNA 500.0 kV Ckt 1 line(Any)
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Contingent

Note: Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8CARSON-AE2-094 TP 500.0 kV Ckt 1 lineDVP_P1-2: LN 591_SRT-S
8ELMONT-8LADYSMITH 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
6CARSON-6CHAPARRAL T 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6CHAPARRAL T-6LOCKS 230.0 kV Ckt 1 lineDVP_P4-2: 562T563_SRT-S
6SUMMIT-6LDYSMITH CT 230.0 kV Ckt 1 line(Any)
8BRISTER-8CHANCE 500.0 kV Ckt 1 line(Any)
6CARSON-8CARSON 230.0/500.0 kV Ckt 1 transformer(Any)
6FREDBRG-6MINE RD 230.0 kV Ckt 1 line(Any)
8HERITAGE-8RAWLINGS 500.0 kV Ckt 1 line(Any)
8SEPTA-8SURRY 500.0 kV Ckt 1 line(Any)
8LADYSMITH-8POSSUM 500.0 kV Ckt 1 line(Any)
8CHANCE-8LADYSMITH 500.0 kV Ckt 1 line(Any)
6SUMMIT-6MINE RD 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending)
Title
No overload on Dominion equipment for 8POSSUM - BURCHES (TC2)
Description
Dominion End Ratings Winter: 5414/5581/6107 Light Load: 5227/5388/5941 Summer: 4257/4388/5046
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
TC2 Upgrade for BURCHES 500.0 kV to 8POSSUM 500.0 kV ckt 1
Description
Replaces the terminal equipment at Burches Hill 500 kV station (breakers, switches, and stranded bus) that upgrades the ratings.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
BURCHES-8POSSUM 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.242
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b3800.242
Title
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Description
Upgrading switches 20366M and 20369M and line leads to 4000A continuous current rating of 230kV Line #203 at Edwards Ferry substation
Cost Information
Time Estimate
Sep 13 2030

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.244
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.244
Title
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Description
Rebuild 7.26 miles of existing 230 kV circuit from Dickerson Station H to Ed's Ferry area to accommodate the new 500 kV circuit between Doubs and Aspen. (The 230kV portion of the project)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-369 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-369 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
(Pending) / (Pending)
Title
Additional Aspen to Dickerson H 230 kV line
Description
PEPCO’s substation cost to accommodate an additional circuit at Dickerson H to be approximately $7.86 million. The cost for the remaining 7.25 miles of 230 kV transmission line is estimated at $78.62 million.
Total Cost ($USD)
$86,480,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 48 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-369 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-369 could receive cost allocation. Although AG2-369 may not presently have cost responsibility for this upgrade, AG2-369 may need this upgrade in-service to be deliverable to the PJM system. If AG2-369 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
DICKH230-6EDFERRY 230.0 kV Ckt 1 line(Any)
6TWINCREEK-6EDFERRY 230.0 kV Ckt 1 line(Any)
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AE2-094 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-338, AG2-339
        
          AG2-440 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-440, AG2-441, AG2-442
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        
          Cunningham 500 kV (Dominion): This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-681, AH1-712, AH1-723
        
          AG2-198 230 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-198, AG2-566
        
          Perth 115 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-111, AG2-112
        

Attachments

AG2-369 One Line Diagram

AG2-369 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.