AG2-378 Phase I Study Report

v1.00 released 2025-10-29 20:38

North Hampton – Medway 69 kV

13.5 MW Capacity / 20.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is TerraForm Twin Creeks Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Transmission Systems, Incorporated.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the American Transmission Systems, Incorporated zone — Clark County, Ohio. This project is an increase to the developer’s AG2-063 project(s), which will share the same Point of Interconnection. The AG2-378 project is a 20.0 MW uprate (13.5 MW Capacity uprate) to the previous project(s). The total installed facilities will have a capability of 74.0 MW with 48.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-378
Project Name:
North Hampton – Medway 69 kV
Project Developer Name:
TerraForm Twin Creeks Solar, LLC
State:
Ohio
County:
Clark
Transmission Owner:
American Transmission Systems, Incorporated
MFO:
74.0
MWE:
20.0
MWC:
13.5
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-378 will interconnect on the American Transmission Systems, Incorporated transmission system tapping the North Hampton to Medway 69 kV line as an uprate to AG2-063.  AG2-378 is uprated by AG2-385.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-378 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-378Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$269,015$0
Other Scope$19,467$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$4,265,533$4,265,533
Network Upgrades$394,789$394,789
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$22,661,505$22,661,505
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$27,610,309$27,321,828

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-378

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-378 Project due at DP1
ABA - B
AG2-378$2,732,183$80,000$2,652,183

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construction of (1) span of conductor between the new Interconnection substation takeoff structure and Developer owned dead end structure.$745,724 $248,575 (See Note 1)
(Pending)Integrate Interconnection Facilities protection and controls to the Transmission Owner system.$61,320 $20,440 (See Note 1)
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construct a new 69 kV 3-breaker ring bus Interconnection substation.$11,847,599 $3,949,200 (See Note 1)
(Pending)ADSS fiber to new interconnection substation.$949,000 $316,333 (See Note 1)
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Cut the existing 69 kV line and Loop in the new Interconnection substation.$979,968 $326,656 (See Note 1)
(Pending)Revise relay settings at North Hampton substation as required.$51,100 $17,033 (See Note 1)
(Pending)Revise relay settings at Enon substation as required.$51,100 $17,033 (See Note 1)
(Pending)Revise relay settings at Medway substation as required.$51,100 $17,033 (See Note 1)
(Pending)Revise relay settings at Clark substation as required.$51,100 $17,033 (See Note 1)
Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install 69 kV revenue metering within new Interconnection substation.$58,400 $19,467 (See Note 1)

Based on the scope of work for the Interconnection Facilities, it is expected to take 36 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Note 1: A Common Use Upgrade is a Network Upgrade that is needed for the interconnection of Generating Facilities or Merchant Transmission Facilities of more than one Project Developer or Eligible Customer and which is the shared responsibility of each Project Developer or Eligible Customer. If multiple Project Developers request to connect to the same interconnection substation, the Transmission Owner will determine the cost to accommodate all the requests at the substation. The cost for the interconnection will be allocated in proportion to the number of required terminations into the substation.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts

There were no network impacts to Distribution facilities identified by the Transmission Owner.

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
240658 02N.HAMPTO 69.0 - 238624 02CLARK 69.0 CKT 1 ATSI_P1-2_OES-69-029_SRT-A-2 56.0220.93 %29.7
970076 (MEDWAY) AG2-063 TP 69.0 - 240658 02N.HAMPTO 69.0 CKT 1 ATSI_P1-2_OES-69-029_SRT-A-2 92.0139.13 %54.0
Transmission Owner Identified System Reinforcements
AG2-378 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDCategoryTitleMW ImpactPercent AllocationAllocated Cost ($USD)
ATSI(Pending) / TC2-ATSI-L01.aSubRegionalReconductor transmission line and line drop on North Hampton - Clark 69kV Line29.7 MW42.2%$528,900
ATSI(Pending) / TC2-ATSI-L01.bSubRegionalReconductor/rebuild 7.47 miles of North Hampton - Clark 69kV and 1 line drop at North Hampton29.7 MW42.2%$10,660,186
ATSI(Pending) / TC2-ATSI-L01.cSubRegionalReplace disconnect switches at Clark and North Hampton29.7 MW42.2%$449,005
ATSI(Pending) / TC2-ATSI-L08.aSubRegionalReconductor/rebuild 7.7 miles between North Hampton and Medway (AG2-063)54.0 MW42.2%$10,846,519
ATSI(Pending) / TC2-ATSI-L08.bSubRegionalUpgrade 1 disconnect switch at North Hampton54.0 MW42.2%$176,896
Grand Total:$22,661,506

System Reinforcement
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-L01.a
Category
SubRegional
Title
Reconductor transmission line and line drop on North Hampton - Clark 69kV Line
Description
Reconductor 0.1 miles of 3/0 ACSR 6/1 transmission line and 3/0 ACSR 6/1 (1) line drop at Clark on the North Hampton-Clark Ckt 1 69 kV line (Mad River TR4 Bus Tie line) using one (1) 556.5 26/7 "Dove" ACSR New facility rating to be 80/96/108 MVA
Total Cost
$1,253,689
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-06329.7 MW42.2%$528,900
AG2-37829.7 MW42.2%$528,900
AG2-38511.0 MW15.6%$195,889

System Reinforcement
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-L01.b
Category
SubRegional
Title
Reconductor/rebuild 7.47 miles of North Hampton - Clark 69kV and 1 line drop at North Hampton
Description
Reconductor (possible rebuild) 7.47 miles of 336 ACSR 26/7 transmission line and 336 ACSR 26/7 (1) line drop at North Hampton on the North Hampton-Clark Ckt 1 69 kV line using one (1) 556.5 26/7 "Dove" ACSR New ratings to be 82/103/119 MVA
Total Cost
$25,268,588
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-06329.7 MW42.2%$10,660,186
AG2-37829.7 MW42.2%$10,660,186
AG2-38511.0 MW15.6%$3,948,217

System Reinforcement
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-L01.c
Category
SubRegional
Title
Replace disconnect switches at Clark and North Hampton
Description
Upgrade (3) disconnect switches at Clark and North Hampton (D38, D40, A6) New ratings to be 153/160/166 MVA
Total Cost
$1,064,308
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-06329.7 MW42.2%$449,005
AG2-37829.7 MW42.2%$449,005
AG2-38511.0 MW15.6%$166,298

System Reinforcement
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-L08.a
Category
SubRegional
Title
Reconductor/rebuild 7.7 miles between North Hampton and Medway (AG2-063)
Description
Reconductor (possible rebuild) 7.7 miles of 336 ACSR 26/7 transmission line on the North Hampton-Medway Ckt 1 69 kV line using one (1) 556.5 26/7 "Dove" ACSR New ratings to be 82/103/119 MVA
Total Cost
$25,710,268
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-06354.0 MW42.2%$10,846,519
AG2-37854.0 MW42.2%$10,846,519
AG2-38520.0 MW15.6%$4,017,229

System Reinforcement
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-L08.b
Category
SubRegional
Title
Upgrade 1 disconnect switch at North Hampton
Description
Upgrade (1) transmission line A24 disconnect switch at North Hampton New ratings to be 164/206/237 MVA
Total Cost
$419,308
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-06354.0 MW42.2%$176,896
AG2-37854.0 MW42.2%$176,896
AG2-38520.0 MW15.6%$65,517

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-378 was evaluated as a 20.0 MW (13.5 MW Capacity) injection in the ATSI area.

AG2-378 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 74.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC121.47 %3792.0B4606.262.02
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC121.45 %3792.0B4605.382.01
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC121.43 %3792.0B4604.682.01
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.961.57
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.631.57
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.97 %3792.0B5307.791.95
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.96 %3792.0B5307.11.95
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC139.86 %3792.0B5303.431.97
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.611.53
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.911.53
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC132.75 %3729.0B4950.272.31
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC131.94 %3729.0B4919.932.31
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC131.63 %3729.0B4908.472.31
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC131.63 %3729.0B4908.472.31
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.981.81
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.262.35
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.61.75
GD2AEP
05BEATTY-05COLE 345.0 kV Ckt 1 line
AEP_P4_#3195_05BEATTY 345_304E_SRT-A
BreakerAC111.35 %1203.0B1339.590.97
GD2AEP
05BEATTY-05COLE 345.0 kV Ckt 1 line
AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A
BreakerAC100.06 %1203.0B1203.741.12
GD2AEP
05BEATTY-05COLE 345.0 kV Ckt 1 line
AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A
BreakerAC100.06 %1203.0B1203.721.12
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC124.65 %1409.0B1756.351.42
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC124.16 %1409.0B1749.361.42
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC124.05 %1409.0B1747.911.42
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC112.44 %1409.0B1584.271.41
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC112.42 %1409.0B1584.051.41
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
BreakerAC102.74 %1409.0B1447.541.42
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.01 %3792.0B5081.522.31
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.21 %3792.0B5051.22.31
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC132.9 %3792.0B5039.692.31
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC132.9 %3792.0B5039.692.31
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.281.81
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.982.35
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.331.75
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC124.95 %4142.0B5175.392.87
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC120.6 %4142.0B4995.092.9
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC120.39 %4142.0B4986.372.9
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC120.3 %4142.0B4982.822.89
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.182.27
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1558_05BAKER 765_Q_SRT-A
BreakerAC153.9 %1540.0B2370.071.03
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#309_05HANG R 765_B2_SRT-A
BreakerAC153.46 %1540.0B2363.361.03
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
BreakerAC153.34 %1540.0B2361.461.03
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC141.78 %1540.0B2183.340.81
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC141.21 %1540.0B2174.620.76
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-2
TowerAC132.53 %1540.0B2040.890.95
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P7-1_#10941___SRT-A
TowerAC132.04 %1540.0B2033.360.92
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC131.72 %1189.0A1566.090.73
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC130.87 %1540.0B2015.350.94
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
BusAC129.85 %1540.0B1999.630.95

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.47 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4606.26
MW Contribution:2.02
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
36.289
270330AC1-082 GEN2
Solar/Wind Harmer
0.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.473
270054AF2-122 C O1
Solar/Wind Harmer
3.4
270520AE2-214 GEN
Solar/Wind Harmer
6.265
270459AD2-067 GEN
Solar/Wind Harmer
8.652
961821AG1-024 GEN
Solar/Wind Harmer
8.784
970879AG2-548 GEN
Solar/Wind Harmer
4.434
970689AG2-444 GEN
Solar/Wind Harmer
16.764
270432AC2-029 GEN
Solar/Wind Harmer
7.199
270269AC2-059
Solar/Wind Harmer
9.583
972203AH1-686 GEN
Adder
2.36
940611AE2-048 GEN
Solar/Wind Harmer
22.51
941391AE2-136 GEN
Solar/Wind Harmer
11.664
270284AF1-227 GEN1
Solar/Wind Harmer
5.777
270286AF1-227 GEN2
Solar/Wind Harmer
2.137
270287AF1-227 GEN3
Solar/Wind Harmer
2.137
270156DARBY CT1
Adder
9.122
270157DARBY CT2
Adder
9.1
270158DARBY CT3
Adder
8.955
945631AF1-228 GEN
Solar/Wind Harmer
4.774
253383AE2-342_GEN
Solar/Wind Harmer
0.9
241973AD2-163_GEN1
Solar/Wind Harmer
2.012
943861AF1-054 GEN
Solar/Wind Harmer
3.894
943851AF1-053 GEN
Solar/Wind Harmer
1.882
971985AH1-537 GEN
Solar/Wind Harmer
18.016
270340AC2-060 GEN
Solar/Wind Harmer
3.05
241972AD1-140 GEN
Solar/Wind Harmer
4.451
270367AC2-061_GEN
Solar/Wind Harmer
3.138
253372AE2-315 SEC3
Adder
1.861
253372AE2-315 SEC3
Adder
1.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.457
25306009OHH W.
Adder
2.823
253349AC2-067 GEN
Solar/Wind Harmer
4.865
253400AC2-068 GEN
Solar/Wind Harmer
1.956
252524AE2-267 GEN
Solar/Wind Harmer
1.533
25196408WSDLE3
Adder
8.578
25196308WSDLE2
Adder
8.503
25196208WSDLE1
Adder
8.482
25196708WSDLE6
Adder
8.461
25196508WSDLE4
Adder
8.248
270302AB2-170 GEN
Solar/Wind Harmer
8.119
270317AD1-130_GEN
Solar/Wind Harmer
3.113
944031AF1-071 GEN
Solar/Wind Harmer
0.966
25196108MFTGT2
Adder
1.473
25196108MFTGT2
Adder
1.368
971673AH1-337 GEN
Solar/Wind Harmer
4.391
971029AG2-637 GEN
Solar/Wind Harmer
14.309
972163AH1-664 GEN
Solar/Wind Harmer
9.523
972165AH1-665 GEN
Solar/Wind Harmer
7.618
270543AE2-219 C
Solar/Wind Harmer
4.876
24729505KEY G4
Adder
6.165
270240V3-007_GEN2
Solar/Wind Harmer
5.881
958711AF2-162 GEN
Solar/Wind Harmer
0.961
965101AG1-375 GEN
Solar/Wind Harmer
9.494
945581AF1-223 GEN
Solar/Wind Harmer
4.304
961761AG1-017 GEN
Solar/Wind Harmer
0.406
970115AG2-085 GEN
Solar/Wind Harmer
3.786
24477305BRIDGE
Adder
0.323
274775LINCOLN ;6U
Adder
7.771
274776LINCOLN ;7U
Adder
7.771
274777LINCOLN ;8U
Adder
7.771
274814UNIV PK N;0U
Adder
4.642
274807UNIV PK N;3U
Adder
4.632
274805UNIV PK N;1U
Adder
4.612
274811UNIV PK N;7U
Adder
4.602
972037AH1-567 GEN1
Adder
0.168
972227AH1-698 GEN1
Adder
2.393
274827FISK ;RP
Adder
7.117
274687WILL CNTY;4U
Adder
25.585
274687WILL CNTY;4U
Adder
25.585
274731ELWOOD EC;2P
Adder
15.046
274733ELWOOD EC;3P
Adder
15.046
274735ELWOOD EC;4P
Adder
15.046
274728ELWOOD EC;5P
Adder
15.046
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
238126S14_GEN_1
Solar/Wind Helper
0.75
238152AF2-075_GEN
Solar/Wind Helper
0.615
23546401DTGZ2-030
Solar/Wind Helper
0.077
238208AF1-136 C
Solar/Wind Helper
0.191
23750501ELLIOTTS
Solar/Wind Helper
0.607
237085AD2-009_GEN
Solar/Wind Helper
1.43
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.761
316415AF1-147_GEN2
Solar/Wind Helper
0.761
270024AE2-089 GEN
Solar/Wind Harmer
0.702
24318905MLG2
50/50
4.888
270471AD2-092_GEN
Solar/Wind Harmer
3.8
946101AF1-275 GEN
Solar/Wind Harmer
1.564
970879AG2-548 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
4.434
24685805CER G1
Adder
8.39
24685905CER G2
Adder
8.39
942861AE2-305 GEN
Solar/Wind Harmer
7.89
270518AE2-148 GEN
Solar/Wind Harmer
12.226
24723005RIVRG1
Adder
18.943
24723105RIVRG2
Adder
18.943
970077AG2-063 GEN
Solar/Wind Harmer
5.44
972269AH1-719 GEN
Adder
2.314
962581AG1-107 GEN
Solar/Wind Harmer
4.971
961491AF2-440 GEN
Solar/Wind Harmer
2.066
253394AE2-221_GEN
Solar/Wind Harmer
4.473
253398AE2-221_GEN2
Solar/Wind Harmer
4.473
253317AC1-085 GEN4
Solar/Wind Harmer
8.238
25326109MON D
Adder
1.293
964601AG1-323 GEN
Solar/Wind Harmer
3.12
964601AG1-323 GEN
Solar/Wind Harmer
1.451
253370AE2-315 SEC1
Adder
1.967
270224U2-072_GEN2
Solar/Wind Harmer
1.941
270227U2-072_GEN3
Solar/Wind Harmer
1.941
270228U2-072_GEN4
Solar/Wind Harmer
1.941
270231U2-072_GEN5
Solar/Wind Harmer
1.941
25322209TAIT E
Adder
9.568
25322209TAIT E
Adder
9.353
270186AC1-089 GEN
Solar/Wind Harmer
5.991
972159AH1-661 GEN
Adder
0.977
938701AE1-092 GEN
Solar/Wind Harmer
20.234
25183208HLCRTG
Solar/Wind Harmer
5.927
252509AD1-136 GEN
Solar/Wind Harmer
0.25
252519AF1-045_GEN
Solar/Wind Harmer
5.924
252516AE2-318_GEN
Solar/Wind Harmer
4.519
253378AE2-206_GEN
Solar/Wind Harmer
3.5
276820AF1-078_GEN
Solar/Wind Harmer
1.555
25194408D.CRK1
Adder
7.352
25194508D.CRK3
Adder
1.375
25326509SID D
Adder
1.274
970239AG2-162 GEN
Solar/Wind Harmer
10.505
24728805RICHG1
Adder
3.601
24728905RICHG2
Adder
3.601
970883AG2-550 GEN
Solar/Wind Harmer
9.522
970885AG2-551 GEN
Solar/Wind Harmer
2.214
270383AD1-128 GEN
Solar/Wind Harmer
5.808
24379505HDWTR1G C
Solar/Wind Harmer
7.516
270209AC1-174_GEN
Solar/Wind Harmer
5.304
926881AC1-175 GEN
Solar/Wind Harmer
5.304
944541AF1-119 GEN
Solar/Wind Harmer
3.977
960971AF2-388 GEN
Solar/Wind Harmer
10.38
247621Y3-024
Adder
0.229
270201AC2-176 GEN
Solar/Wind Harmer
4.876
964611AG1-324 GEN
Solar/Wind Harmer
1.118
964611AG1-324 GEN
Solar/Wind Harmer
0.496
970825AG2-519 GEN
Solar/Wind Harmer
9.992
960441AF2-335 GEN
Solar/Wind Harmer
9.465
247620Y3-023
Adder
0.427
274770LINCOLN ;1U
Adder
7.771
274771LINCOLN ;2U
Adder
7.771
274808UNIV PK N;4U
Adder
4.582
274803UNIV PARK;6U
Adder
5.35
972259AH1-714 GEN
Adder
17.495
23585401KL_K28_T16
Solar/Wind Helper
1.401
238120AE2-309 GEN
Solar/Wind Helper
0.474
238175AF1-290_GEN
Solar/Wind Helper
0.131
238169AE2-226 GEN1
Solar/Wind Helper
0.604
238170AE2-226 GEN2
Solar/Wind Helper
0.604
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.152
235063AE1-101 C2
Solar/Wind Helper
1.439
237002AB1-128_GEN
Solar/Wind Helper
0.384
237001AB1-127_GEN
Solar/Wind Helper
0.383
237034AC2-136 C
Solar/Wind Helper
0.196
23777801MSM_W1-116
Solar/Wind Helper
0.099
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
23559101PLEAS2
50/50
11.904
23684101S70BUS1
50/50
0.301
23562301OGROV1
50/50
2.301
24721705FLATG2
Adder
24.275
962761AG1-125 GEN
Solar/Wind Harmer
36.289
970149AG2-104 GEN
Solar/Wind Harmer
44.817
970155AG2-107 GEN
Solar/Wind Harmer
15.824
270510AE1-227 GEN1
Solar/Wind Harmer
2.641
960001AF2-291 GEN
Solar/Wind Harmer
3.22
970947AG2-589 GEN
Solar/Wind Harmer
2.097
270331AC1-082 GEN3
Solar/Wind Harmer
0.474
270349AD2-093_GEN
Solar/Wind Harmer
3.8
927014AC1-188 GEN
Solar/Wind Harmer
1.647
270263AC1-001 GEN
Solar/Wind Harmer
1.075
270159DARBY CT4
Adder
8.977
24686105CER G3
Adder
8.446
24686505CER G6
Adder
8.435
253343AC1-166 GEN
Solar/Wind Harmer
1.099
253325AC1-069 GEN
Solar/Wind Harmer
1.06
24723205RIVRG3
Adder
18.943
970593AG2-378 GEN
Solar/Wind Harmer
2.015
253432AC1-085 GEN2
Solar/Wind Harmer
0.263
946171AF1-282 GEN
Solar/Wind Harmer
9.835
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
270223U2-072_GEN1
Solar/Wind Harmer
1.941
270578AF1-285 GEN2
Solar/Wind Harmer
1.187
270391AF1-285 GEN3
Solar/Wind Harmer
1.187
25326309TAIT D
Adder
1.075
960071AF2-298 GEN
Solar/Wind Harmer
4.886
252507AC2-088 GEN
Solar/Wind Harmer
1.752
25194608D.CRK4
Adder
1.598
270462AD2-086
Solar/Wind Harmer
6.754
25196808ZIMRHP
Adder
73.524
25196008MFTGT1
Adder
1.336
970333AG2-219 GEN
Solar/Wind Harmer
30.143
945681AF1-233 GEN
Solar/Wind Harmer
17.979
971995AH1-542 GEN
Solar/Wind Harmer
10.473
247536S-71 GEN
Solar/Wind Harmer
3.848
942081AE2-220 GEN
Solar/Wind Harmer
6.077
270239V3-007_GEN1
Solar/Wind Harmer
1.636
965651AG1-433 GEN
Solar/Wind Harmer
5.19
958861AF2-177 GEN
Solar/Wind Harmer
10.377
945371AF1-202 GEN
Solar/Wind Harmer
6.621
270005AE1-210 C O1
Solar/Wind Harmer
5.18
965031AG1-367 GEN
Solar/Wind Harmer
9.478
970825AG2-519 GEN
Solar/Wind Harmer
2.23
970091AG2-072 GEN
Adder
72.371
24728605AND G2
Adder
3.578
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.771
274774LINCOLN ;5U
Adder
7.771
274751CRETE EC ;1U
Adder
7.583
274754CRETE EC ;4U
Adder
7.583
274723RIVER EC ;12
Adder
16.483
274812UNIV PK N;8U
Adder
4.602
274801UNIV PARK;4U
Adder
5.348
274732ELWOOD EC;7P
Adder
8.785
23751101LEADS_P59
Solar/Wind Helper
1.563
23583801GRNGAP
Solar/Wind Helper
4.994
316095T157 G97
Solar/Wind Helper
1.335
23751201ROTHROCK
Solar/Wind Helper
0.822
238185AF2-356 C
Solar/Wind Helper
2.423
23562501BACKB
Solar/Wind Helper
1.01
235054AD2-180 GEN
Solar/Wind Helper
1.889
238108AE1-109 GEN1
Solar/Wind Helper
0.101
235531U2-073 GEN
Solar/Wind Helper
2.957
238117U2-030
Solar/Wind Helper
0.309
238147AE2-230_GEN1
Solar/Wind Helper
0.431
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.237
235067AD1-061 GEN
Solar/Wind Helper
0.429
237030AB1-096 C
Solar/Wind Helper
0.061
23559001PLEAS1
50/50
11.904
23684201S70BUS2
50/50
0.306
23562401OGROV2
50/50
2.286
24318805MLG1
50/50
6.661
24721905FLATG4
Adder
24.275
970153AG2-106 GEN
Solar/Wind Harmer
15.824
270512AE1-227 GEN2
Solar/Wind Harmer
2.242
971191AH1-055 GEN
Solar/Wind Harmer
22.996
957541AF2-048 GEN
Solar/Wind Harmer
1.643
961921AG1-034 GEN
Solar/Wind Harmer
13.176
270291AC1-194 GEN
Solar/Wind Harmer
10.919
960801AF2-371 GEN
Solar/Wind Harmer
2.612
964871AG1-351 GEN
Solar/Wind Harmer
1.804
270273AD2-016 GEN
Solar/Wind Harmer
2.741
972173AH1-669 GEN
Solar/Wind Harmer
5.136
241955AC1-078 GEN
Solar/Wind Harmer
7.631
942051AE2-217 GEN
Solar/Wind Harmer
18.255
24686205CER G4
Adder
8.402
24686405CER G5
Adder
8.368
241974AD2-163_GEN2
Solar/Wind Harmer
2.012
253338AC1-165 GEN
Solar/Wind Harmer
1.099
253333AC1-068 GEN
Solar/Wind Harmer
1.06
970605AG2-385 GEN
Solar/Wind Harmer
5.44
253415AE1-040 GEN
Solar/Wind Harmer
1.134
253406AD2-031_GEN
Solar/Wind Harmer
1.265
253316AC1-085 GEN3
Solar/Wind Harmer
8.238
253433AC1-085 GEN1
Solar/Wind Harmer
5.23
946181AF1-283 GEN
Solar/Wind Harmer
12.786
253303V4-073 C
Solar/Wind Harmer
0.114
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
942871AE2-306 GEN
Solar/Wind Harmer
0.89
270391AF1-285 GEN3
Solar/Wind Harmer
0.457
252510AF1-249 C
Solar/Wind Harmer
0.407
25196608WSDLE5
Adder
8.333
25194608D.CRK4
Adder
1.598
270485AE1-090_GEN
Solar/Wind Harmer
0.587
270222AC2-111 GEN
Solar/Wind Harmer
7.836
25196008MFTGT1
Adder
1.294
970243AG2-164 GEN
Solar/Wind Harmer
24.663
970519AG2-331 GEN
Solar/Wind Harmer
16.569
970699AG2-449 GEN
Solar/Wind Harmer
10.961
972167AH1-666 GEN
Solar/Wind Harmer
7.633
958171AF2-111 GEN
Solar/Wind Harmer
23.849
944531AF1-118 GEN
Solar/Wind Harmer
33.274
270437AC2-090 C
Solar/Wind Harmer
5.307
962031AG1-047 GEN
Solar/Wind Harmer
2.867
957741AF2-068 GEN
Solar/Wind Harmer
14.228
946031AF1-268 GEN
Solar/Wind Harmer
7.867
958821AF2-173 GEN
Solar/Wind Harmer
13.269
270004AE1-209 GEN
Solar/Wind Harmer
5.18
270356AE2-297 GEN
Solar/Wind Harmer
4.32
24728705AND G3
Adder
7.484
24728505AND G1
Adder
3.578
24642205MAYFLWER
Adder
0.588
274772LINCOLN ;3U
Adder
7.771
274752CRETE EC ;2U
Adder
7.583
274753CRETE EC ;3U
Adder
7.583
274724RIVER EC ;11
Adder
16.291
274802UNIV PARK;5U
Adder
5.35
972228AH1-698 GEN2
Adder
3.398
274826FISK ;BP
Adder
10.043
274800UNIV PARK;3U
Adder
5.348
972038AH1-567 GEN2
Adder
0.335
274729ELWOOD EC;1P
Adder
15.046
274730ELWOOD EC;6P
Adder
15.046
316097T157 G90
Solar/Wind Helper
1.335
964991AG1-363 GEN
Solar/Wind Helper
4.295
23750701CROSSCHOOL
Solar/Wind Helper
1.345
238127S14_GEN_2
Solar/Wind Helper
0.75
238118U2-030_1
Solar/Wind Helper
0.309
238148AE2-230_GEN2
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.236
235062AE1-101 C1
Solar/Wind Helper
1.439
23779801AA1-109
Solar/Wind Helper
0.167
971617AH1-308 GEN
Solar/Wind Harmer
0.869
944201AF1-088_MTX
Adder
106.917
957141AF2-008_MTX
Adder
53.458
CPLELTFEXP_CPLE->PJM
CLTF
1.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.814
LAGNLTFEXP_LAGN->PJM
CLTF
14.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.03
TVALTFEXP_TVA->PJM
CLTF
7.054
NYPJM->LTFIMP_NY
CLTF
4.499
LGEELTFEXP_LGEE->PJM
CLTF
6.294
WECLTFEXP_WEC->PJM
CLTF
3.447
AG2-052LTFEXP_AG2-052->PJM
LTF
0.215
AH1-155LTFEXP_AH1-155->PJM
LTF
0.322
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.934
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.919
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.468

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4605.38
MW Contribution:2.01
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
970689AG2-444 GEN
Solar/Wind Harmer
16.696
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270024AE2-089 GEN
Solar/Wind Harmer
0.699
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971617AH1-308 GEN
Solar/Wind Harmer
0.866
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.43 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4604.68
MW Contribution:2.01
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
970689AG2-444 GEN
Solar/Wind Harmer
16.696
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270024AE2-089 GEN
Solar/Wind Harmer
0.699
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971617AH1-308 GEN
Solar/Wind Harmer
0.866
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:1.57
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.97 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.79
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.96 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.1
MW Contribution:1.95
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.86 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5303.43
MW Contribution:1.97
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.24
23684101S70BUS1
50/50
0.316
23562301OGROV1
50/50
2.447
24721705FLATG2
Adder
23.592
962761AG1-125 GEN
Solar/Wind Harmer
35.245
970149AG2-104 GEN
Solar/Wind Harmer
43.528
970155AG2-107 GEN
Solar/Wind Harmer
15.368
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.176
970947AG2-589 GEN
Solar/Wind Harmer
2.074
270331AC1-082 GEN3
Solar/Wind Harmer
0.469
927014AC1-188 GEN
Solar/Wind Harmer
1.618
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270263AC1-001 GEN
Solar/Wind Harmer
1.052
270159DARBY CT4
Adder
8.767
24686105CER G3
Adder
8.308
24686505CER G6
Adder
8.298
24723205RIVRG3
Adder
18.592
253343AC1-166 GEN
Solar/Wind Harmer
1.074
253325AC1-069 GEN
Solar/Wind Harmer
1.035
970593AG2-378 GEN
Solar/Wind Harmer
1.966
253432AC1-085 GEN2
Solar/Wind Harmer
0.257
946171AF1-282 GEN
Solar/Wind Harmer
9.619
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
25326309TAIT D
Adder
1.05
960071AF2-298 GEN
Solar/Wind Harmer
4.772
23559001PLEAS1
50/50
11.24
23684201S70BUS2
50/50
0.322
23562401OGROV2
50/50
2.431
24318805MLG1
50/50
6.369
23534401HANNIB
50/50
0.15
24721905FLATG4
Adder
23.592
970153AG2-106 GEN
Solar/Wind Harmer
15.368
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
971191AH1-055 GEN
Solar/Wind Harmer
22.576
957541AF2-048 GEN
Solar/Wind Harmer
1.614
270291AC1-194 GEN
Solar/Wind Harmer
10.719
961921AG1-034 GEN
Solar/Wind Harmer
12.85
960801AF2-371 GEN
Solar/Wind Harmer
2.556
964871AG1-351 GEN
Solar/Wind Harmer
1.765
270273AD2-016 GEN
Solar/Wind Harmer
2.682
972173AH1-669 GEN
Solar/Wind Harmer
5.026
241955AC1-078 GEN
Solar/Wind Harmer
7.448
24686205CER G4
Adder
8.265
24686405CER G5
Adder
8.232
942051AE2-217 GEN
Solar/Wind Harmer
17.81
253338AC1-165 GEN
Solar/Wind Harmer
1.074
253333AC1-068 GEN
Solar/Wind Harmer
1.035
241974AD2-163_GEN2
Solar/Wind Harmer
1.962
253415AE1-040 GEN
Solar/Wind Harmer
1.109
970605AG2-385 GEN
Solar/Wind Harmer
5.308
253406AD2-031_GEN
Solar/Wind Harmer
1.238
253316AC1-085 GEN3
Solar/Wind Harmer
8.057
253433AC1-085 GEN1
Solar/Wind Harmer
5.115
946181AF1-283 GEN
Solar/Wind Harmer
12.504
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
942871AE2-306 GEN
Solar/Wind Harmer
0.866
270391AF1-285 GEN3
Solar/Wind Harmer
0.444
252510AF1-249 C
Solar/Wind Harmer
0.398
25194608D.CRK4
Adder
1.563
25196608WSDLE5
Adder
8.148
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
7.655
25196008MFTGT1
Adder
1.265
970243AG2-164 GEN
Solar/Wind Harmer
24.096
970519AG2-331 GEN
Solar/Wind Harmer
16.189
970699AG2-449 GEN
Solar/Wind Harmer
10.709
972167AH1-666 GEN
Solar/Wind Harmer
7.473
958171AF2-111 GEN
Solar/Wind Harmer
23.339
270437AC2-090 C
Solar/Wind Harmer
5.18
944531AF1-118 GEN
Solar/Wind Harmer
32.44
962031AG1-047 GEN
Solar/Wind Harmer
2.797
957741AF2-068 GEN
Solar/Wind Harmer
13.882
946031AF1-268 GEN
Solar/Wind Harmer
7.677
958821AF2-173 GEN
Solar/Wind Harmer
12.949
270004AE1-209 GEN
Solar/Wind Harmer
5.055
270356AE2-297 GEN
Solar/Wind Harmer
4.219
24728705AND G3
Adder
7.308
24728505AND G1
Adder
3.494
24642205MAYFLWER
Adder
0.573
274772LINCOLN ;3U
Adder
7.577
274752CRETE EC ;2U
Adder
7.394
274753CRETE EC ;3U
Adder
7.394
274724RIVER EC ;11
Adder
15.884
316097T157 G90
Solar/Wind Helper
1.324
964991AG1-363 GEN
Solar/Wind Helper
4.195
238148AE2-230_GEN2
Solar/Wind Helper
0.423
237080AD1-060 GEN
Solar/Wind Helper
0.287
23750701CROSSCHOOL
Solar/Wind Helper
1.116
237038AE2-054 C
Solar/Wind Helper
0.228
235062AE1-101 C1
Solar/Wind Helper
1.393
23779801AA1-109
Solar/Wind Helper
0.164
970935AG2-582 GEN
50/50
1215.723
24318905MLG2
50/50
4.724
270471AD2-092_GEN
Solar/Wind Harmer
3.698
970879AG2-548 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
4.353
946101AF1-275 GEN
Solar/Wind Harmer
1.525
972269AH1-719 GEN
Adder
2.293
24685805CER G1
Adder
8.254
24685905CER G2
Adder
8.254
24723005RIVRG1
Adder
18.592
24723105RIVRG2
Adder
18.592
942861AE2-305 GEN
Solar/Wind Harmer
7.696
270518AE2-148 GEN
Solar/Wind Harmer
11.94
970077AG2-063 GEN
Solar/Wind Harmer
5.308
962581AG1-107 GEN
Solar/Wind Harmer
4.865
961491AF2-440 GEN
Solar/Wind Harmer
2.022
972159AH1-661 GEN
Adder
0.962
253394AE2-221_GEN
Solar/Wind Harmer
4.373
253398AE2-221_GEN2
Solar/Wind Harmer
4.373
253317AC1-085 GEN4
Solar/Wind Harmer
8.057
25326109MON D
Adder
1.263
270186AC1-089 GEN
Solar/Wind Harmer
5.865
253370AE2-315 SEC1
Adder
1.922
25322209TAIT E
Adder
9.347
25322209TAIT E
Adder
9.137
964601AG1-323 GEN
Solar/Wind Harmer
3.04
964601AG1-323 GEN
Solar/Wind Harmer
1.414
25183208HLCRTG
Solar/Wind Harmer
5.797
270224U2-072_GEN2
Solar/Wind Harmer
1.889
270227U2-072_GEN3
Solar/Wind Harmer
1.889
270228U2-072_GEN4
Solar/Wind Harmer
1.889
270231U2-072_GEN5
Solar/Wind Harmer
1.889
252509AD1-136 GEN
Solar/Wind Harmer
0.245
252519AF1-045_GEN
Solar/Wind Harmer
5.794
252516AE2-318_GEN
Solar/Wind Harmer
4.42
938701AE1-092 GEN
Solar/Wind Harmer
19.71
25194408D.CRK1
Adder
7.189
25194508D.CRK3
Adder
1.344
253378AE2-206_GEN
Solar/Wind Harmer
3.413
276820AF1-078_GEN
Solar/Wind Harmer
1.516
25326509SID D
Adder
1.242
970239AG2-162 GEN
Solar/Wind Harmer
10.263
24728805RICHG1
Adder
3.517
24728905RICHG2
Adder
3.517
970883AG2-550 GEN
Solar/Wind Harmer
9.293
970885AG2-551 GEN
Solar/Wind Harmer
2.161
270383AD1-128 GEN
Solar/Wind Harmer
5.669
24379505HDWTR1G C
Solar/Wind Harmer
7.337
270209AC1-174_GEN
Solar/Wind Harmer
5.178
926881AC1-175 GEN
Solar/Wind Harmer
5.178
247621Y3-024
Adder
0.223
944541AF1-119 GEN
Solar/Wind Harmer
3.879
960971AF2-388 GEN
Solar/Wind Harmer
10.123
270201AC2-176 GEN
Solar/Wind Harmer
4.758
964611AG1-324 GEN
Solar/Wind Harmer
1.091
964611AG1-324 GEN
Solar/Wind Harmer
0.484
970825AG2-519 GEN
Solar/Wind Harmer
9.752
960441AF2-335 GEN
Solar/Wind Harmer
9.237
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.577
274771LINCOLN ;2U
Adder
7.577
238175AF1-290_GEN
Solar/Wind Helper
0.128
238169AE2-226 GEN1
Solar/Wind Helper
0.591
238170AE2-226 GEN2
Solar/Wind Helper
0.591
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
237034AC2-136 C
Solar/Wind Helper
0.192
237002AB1-128_GEN
Solar/Wind Helper
0.372
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.393
23777801MSM_W1-116
Solar/Wind Helper
0.097
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
270599AE1-208 GEN
Solar/Wind Harmer
0.766
270031AE2-169
Solar/Wind Harmer
0.766
270223U2-072_GEN1
Solar/Wind Harmer
1.889
252507AC2-088 GEN
Solar/Wind Harmer
1.713
270578AF1-285 GEN2
Solar/Wind Harmer
1.155
270391AF1-285 GEN3
Solar/Wind Harmer
1.155
25194608D.CRK4
Adder
1.563
25196808ZIMRHP
Adder
71.915
270462AD2-086
Solar/Wind Harmer
6.572
25196008MFTGT1
Adder
1.306
970333AG2-219 GEN
Solar/Wind Harmer
29.451
945681AF1-233 GEN
Solar/Wind Harmer
17.602
247536S-71 GEN
Solar/Wind Harmer
3.755
942081AE2-220 GEN
Solar/Wind Harmer
5.932
270239V3-007_GEN1
Solar/Wind Harmer
1.597
971995AH1-542 GEN
Solar/Wind Harmer
10.198
965651AG1-433 GEN
Solar/Wind Harmer
5.062
958861AF2-177 GEN
Solar/Wind Harmer
10.121
945371AF1-202 GEN
Solar/Wind Harmer
6.459
270005AE1-210 C O1
Solar/Wind Harmer
5.055
965031AG1-367 GEN
Solar/Wind Harmer
9.249
970825AG2-519 GEN
Solar/Wind Harmer
2.176
970091AG2-072 GEN
Adder
70.733
24728605AND G2
Adder
3.494
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.577
274774LINCOLN ;5U
Adder
7.577
274751CRETE EC ;1U
Adder
7.394
274754CRETE EC ;4U
Adder
7.394
274723RIVER EC ;12
Adder
16.072
274812UNIV PK N;8U
Adder
4.487
23583801GRNGAP
Solar/Wind Helper
4.952
316095T157 G97
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
238108AE1-109 GEN1
Solar/Wind Helper
0.087
235067AD1-061 GEN
Solar/Wind Helper
0.416
237030AB1-096 C
Solar/Wind Helper
0.06
962771AG1-126 GEN
Solar/Wind Harmer
35.245
270330AC1-082 GEN2
Solar/Wind Harmer
0.795
270329AC1-082 GEN1
Solar/Wind Harmer
0.468
270054AF2-122 C O1
Solar/Wind Harmer
3.32
940611AE2-048 GEN
Solar/Wind Harmer
22.287
941391AE2-136 GEN
Solar/Wind Harmer
11.549
970879AG2-548 GEN
Solar/Wind Harmer
4.353
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270459AD2-067 GEN
Solar/Wind Harmer
8.438
961821AG1-024 GEN
Solar/Wind Harmer
8.566
270432AC2-029 GEN
Solar/Wind Harmer
7.042
970689AG2-444 GEN
Solar/Wind Harmer
16.397
270269AC2-059
Solar/Wind Harmer
9.378
972203AH1-686 GEN
Adder
2.313
270156DARBY CT1
Adder
8.909
270157DARBY CT2
Adder
8.887
270158DARBY CT3
Adder
8.745
945631AF1-228 GEN
Solar/Wind Harmer
4.662
270284AF1-227 GEN1
Solar/Wind Harmer
5.621
270286AF1-227 GEN2
Solar/Wind Harmer
2.079
270287AF1-227 GEN3
Solar/Wind Harmer
2.079
253383AE2-342_GEN
Solar/Wind Harmer
0.877
971985AH1-537 GEN
Solar/Wind Harmer
17.658
241973AD2-163_GEN1
Solar/Wind Harmer
1.962
943861AF1-054 GEN
Solar/Wind Harmer
3.799
943851AF1-053 GEN
Solar/Wind Harmer
1.836
270340AC2-060 GEN
Solar/Wind Harmer
2.985
24477305BRIDGE
Adder
0.341
241972AD1-140 GEN
Solar/Wind Harmer
4.346
270367AC2-061_GEN
Solar/Wind Harmer
3.072
253372AE2-315 SEC3
Adder
1.818
253372AE2-315 SEC3
Adder
1.818
25306009OHH W.
Adder
2.758
270578AF1-285 GEN2
Solar/Wind Harmer
0.444
253349AC2-067 GEN
Solar/Wind Harmer
4.752
253400AC2-068 GEN
Solar/Wind Harmer
1.911
252524AE2-267 GEN
Solar/Wind Harmer
1.499
25196408WSDLE3
Adder
8.387
25196308WSDLE2
Adder
8.314
25196208WSDLE1
Adder
8.294
25196708WSDLE6
Adder
8.273
25196508WSDLE4
Adder
8.064
270302AB2-170 GEN
Solar/Wind Harmer
7.9
270317AD1-130_GEN
Solar/Wind Harmer
3.028
944031AF1-071 GEN
Solar/Wind Harmer
0.944
25196108MFTGT2
Adder
1.44
25196108MFTGT2
Adder
1.337
972163AH1-664 GEN
Solar/Wind Harmer
9.324
972165AH1-665 GEN
Solar/Wind Harmer
7.459
971673AH1-337 GEN
Solar/Wind Harmer
4.287
971029AG2-637 GEN
Solar/Wind Harmer
13.968
270543AE2-219 C
Solar/Wind Harmer
4.759
270240V3-007_GEN2
Solar/Wind Harmer
5.741
24729505KEY G4
Adder
6.012
958711AF2-162 GEN
Solar/Wind Harmer
0.937
965101AG1-375 GEN
Solar/Wind Harmer
9.26
945581AF1-223 GEN
Solar/Wind Harmer
4.198
961761AG1-017 GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
3.695
274775LINCOLN ;6U
Adder
7.577
274776LINCOLN ;7U
Adder
7.577
274777LINCOLN ;8U
Adder
7.577
274814UNIV PK N;0U
Adder
4.526
274807UNIV PK N;3U
Adder
4.517
274805UNIV PK N;1U
Adder
4.497
274811UNIV PK N;7U
Adder
0.593
238152AF2-075_GEN
Solar/Wind Helper
0.602
23546401DTGZ2-030
Solar/Wind Helper
0.076
238208AF1-136 C
Solar/Wind Helper
0.181
238109AE1-109 GEN2
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237085AD2-009_GEN
Solar/Wind Helper
1.378
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.751
316415AF1-147_GEN2
Solar/Wind Helper
0.751
944201AF1-088_MTX
Adder
104.45
957141AF2-008_MTX
Adder
52.225
CPLELTFEXP_CPLE->PJM
CLTF
1.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.491
LAGNLTFEXP_LAGN->PJM
CLTF
13.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.88
TVALTFEXP_TVA->PJM
CLTF
6.914
NYPJM->LTFIMP_NY
CLTF
4.434
LGEELTFEXP_LGEE->PJM
CLTF
6.157
WECLTFEXP_WEC->PJM
CLTF
3.363
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.724
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.351
MECLTFEXP_MEC->PJM
CLTF
14.175
SIGELTFEXP_SIGE->PJM
CLTF
0.458

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:1.53
Bus #Bus NameTypeMW Contribution
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:1.53
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.75 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4950.27
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.94 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4919.93
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:1.81
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:1.75
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 05BEATTY-05COLE 345.0 kV Ckt 1 line l/o AEP_P4_#3195_05BEATTY 345_304E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BEATTY-05COLE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3195_05BEATTY 345_304E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.35 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1339.59
MW Contribution:0.97
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
2.118
253371AE2-315 SEC2
50/50
2.003
25322209TAIT E
50/50
0.481
253338AC1-165 GEN
Solar/Wind Harmer
2.95
253333AC1-068 GEN
Solar/Wind Harmer
2.845
253316AC1-085 GEN3
Solar/Wind Harmer
9.138
270159DARBY CT4
50/50
31.323
253370AE2-315 SEC1
50/50
2.118
253371AE2-315 SEC2
50/50
2.003
25322209TAIT E
50/50
0.488
25322309TAIT W
50/50
0.487
253343AC1-166 GEN
Solar/Wind Harmer
2.95
253325AC1-069 GEN
Solar/Wind Harmer
2.845
253432AC1-085 GEN2
Solar/Wind Harmer
0.292
946171AF1-282 GEN
Solar/Wind Harmer
10.909
25326309TAIT D
Adder
1.05
960071AF2-298 GEN
Solar/Wind Harmer
4.497
25196808ZIMRHP
Adder
56.989
252507AC2-088 GEN
Solar/Wind Harmer
1.339
945681AF1-233 GEN
Solar/Wind Harmer
14.039
25194608D.CRK4
Adder
1.173
339216AC1-074 GEN
Solar/Wind Harmer
1.035
25196008MFTGT1
Adder
0.812
943111AE2-339 GEN
Solar/Wind Harmer
0.512
3429421JKCT 10G
Adder
4.71
3429241JKCT 3G
Adder
6.464
970593AG2-378 GEN
Solar/Wind Harmer
0.966
270349AD2-093_GEN
Solar/Wind Helper
0.832
270156DARBY CT1
50/50
31.83
270157DARBY CT2
50/50
31.752
270158DARBY CT3
50/50
31.245
253372AE2-315 SEC3
50/50
2.003
253372AE2-315 SEC3
50/50
2.003
25322309TAIT W
50/50
0.493
945631AF1-228 GEN
Solar/Wind Harmer
15.366
270340AC2-060 GEN
Solar/Wind Harmer
2.773
25306009OHH W.
Adder
2.634
241972AD1-140 GEN
Solar/Wind Harmer
3.809
253349AC2-067 GEN
Solar/Wind Harmer
4.166
253400AC2-068 GEN
Solar/Wind Harmer
1.675
972163AH1-664 GEN
Solar/Wind Harmer
7.327
972165AH1-665 GEN
Solar/Wind Harmer
5.862
252524AE2-267 GEN
Solar/Wind Harmer
1.136
25196408WSDLE3
Adder
6.354
25196308WSDLE2
Adder
6.299
25196208WSDLE1
Adder
6.283
25196708WSDLE6
Adder
6.267
25196508WSDLE4
Adder
6.109
270367AC2-061_GEN
Solar/Wind Harmer
2.081
339243AC2-075 GEN1
Solar/Wind Harmer
0.28
25196108MFTGT2
Adder
0.896
25196108MFTGT2
Adder
0.832
944031AF1-071 GEN
Solar/Wind Harmer
0.556
3429211JKCT 2G
Adder
6.38
339211AE2-254 GEN
Solar/Wind Harmer
0.653
270520AE2-214 GEN
Solar/Wind Helper
16.8
270284AF1-227 GEN1
Solar/Wind Helper
1.077
270286AF1-227 GEN2
Solar/Wind Helper
0.395
270287AF1-227 GEN3
Solar/Wind Helper
0.395
270160DARBY CT5
50/50
1.706
270161DARBY CT6
50/50
1.683
25326109MON D
50/50
1.396
253370AE2-315 SEC1
50/50
2.118
270518AE2-148 GEN
Solar/Wind Harmer
33.1
253394AE2-221_GEN
Solar/Wind Harmer
5.184
253398AE2-221_GEN2
Solar/Wind Harmer
5.184
253317AC1-085 GEN4
Solar/Wind Harmer
9.138
25322209TAIT E
Adder
9.353
25322209TAIT E
Adder
9.143
25183208HLCRTG
Solar/Wind Harmer
5.257
252519AF1-045_GEN
Solar/Wind Harmer
4.762
252516AE2-318_GEN
Solar/Wind Harmer
3.633
252509AD1-136 GEN
Solar/Wind Harmer
0.191
25194408D.CRK1
Adder
5.397
25194508D.CRK3
Adder
1.009
962581AG1-107 GEN
Solar/Wind Harmer
3.437
961491AF2-440 GEN
Solar/Wind Harmer
1.428
270186AC1-089 GEN
Solar/Wind Harmer
3.991
339221AD2-048_GEN
Solar/Wind Harmer
0.937
972043AH1-570 GEN
Solar/Wind Harmer
1.515
972045AH1-571 GEN
Solar/Wind Harmer
1.212
971125AH1-004 GEN
Solar/Wind Harmer
2.34
970107AG2-081 GEN
Solar/Wind Harmer
1.755
960161AF2-307 GEN
Solar/Wind Harmer
3.487
942891AE2-308 GEN
Solar/Wind Harmer
5.27
970235AG2-159 GEN
Solar/Wind Harmer
2.007
970235AG2-159 GEN
Solar/Wind Harmer
1.225
970077AG2-063 GEN
Solar/Wind Harmer
2.607
24728805RICHG1
Adder
1.761
24728905RICHG2
Adder
1.761
25326509SID D
Adder
0.568
946101AF1-275 GEN
Solar/Wind Helper
2.104
270471AD2-092_GEN
Solar/Wind Helper
0.832
253433AC1-085 GEN1
Solar/Wind Harmer
5.801
946181AF1-283 GEN
Solar/Wind Harmer
14.182
253415AE1-040 GEN
Solar/Wind Harmer
1.229
253406AD2-031_GEN
Solar/Wind Harmer
1.329
253303V4-073 C
Solar/Wind Harmer
0.115
958171AF2-111 GEN
Solar/Wind Harmer
20.161
972167AH1-666 GEN
Solar/Wind Harmer
5.985
241955AC1-078 GEN
Solar/Wind Harmer
5.548
25196608WSDLE5
Adder
6.172
252510AF1-249 C
Solar/Wind Harmer
0.299
25194608D.CRK4
Adder
1.173
25196008MFTGT1
Adder
0.787
3429391JKCT 9G
Adder
4.71
270222AC2-111 GEN
Solar/Wind Harmer
4.514
970093AG2-073 GEN
Solar/Wind Harmer
5
970605AG2-385 GEN
Solar/Wind Harmer
2.607
942051AE2-217 GEN
Solar/Wind Harmer
8.29
966571AG1-526 GEN
Solar/Wind Harmer
10.155
CPLELTFEXP_CPLE->PJM
CLTF
0.384
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.528
LAGNLTFEXP_LAGN->PJM
CLTF
3.277
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.954
TVALTFEXP_TVA->PJM
CLTF
1.778
NYPJM->LTFIMP_NY
CLTF
0.709
LGEELTFEXP_LGEE->PJM
CLTF
2.67
WECLTFEXP_WEC->PJM
CLTF
0.422
CBM West 1LTFEXP_CBM-W1->PJM
CBM
11.847
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.106
MECLTFEXP_MEC->PJM
CLTF
2.33
SIGELTFEXP_SIGE->PJM
CLTF
0.154

Details for 05BEATTY-05COLE 345.0 kV Ckt 1 line l/o AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BEATTY-05COLE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.06 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1203.74
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
28.923
270157DARBY CT2
50/50
28.852
270158DARBY CT3
50/50
28.391
253372AE2-315 SEC3
50/50
1.849
253372AE2-315 SEC3
50/50
1.849
25322309TAIT W
50/50
0.455
945631AF1-228 GEN
Solar/Wind Harmer
13.963
270340AC2-060 GEN
Solar/Wind Harmer
2.678
25306009OHH W.
Adder
2.431
241972AD1-140 GEN
Solar/Wind Harmer
3.722
253349AC2-067 GEN
Solar/Wind Harmer
3.843
253400AC2-068 GEN
Solar/Wind Harmer
1.545
972163AH1-664 GEN
Solar/Wind Harmer
6.768
972165AH1-665 GEN
Solar/Wind Harmer
5.414
252524AE2-267 GEN
Solar/Wind Harmer
1.048
25196408WSDLE3
Adder
5.862
25196308WSDLE2
Adder
5.811
25196208WSDLE1
Adder
5.796
25196708WSDLE6
Adder
5.782
25196508WSDLE4
Adder
5.636
270367AC2-061_GEN
Solar/Wind Harmer
1.956
270432AC2-029 GEN
Solar/Wind Harmer
4.062
339243AC2-075 GEN1
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
0.827
25196108MFTGT2
Adder
0.768
944031AF1-071 GEN
Solar/Wind Harmer
0.512
3429211JKCT 2G
Adder
5.894
270269AC2-059
Solar/Wind Harmer
4.061
270520AE2-214 GEN
Solar/Wind Helper
17.761
270284AF1-227 GEN1
Solar/Wind Helper
1.078
270286AF1-227 GEN2
Solar/Wind Helper
0.395
270287AF1-227 GEN3
Solar/Wind Helper
0.395
270160DARBY CT5
50/50
1.55
270161DARBY CT6
50/50
1.529
25326109MON D
50/50
1.292
253370AE2-315 SEC1
50/50
1.955
270518AE2-148 GEN
Solar/Wind Harmer
30.115
253394AE2-221_GEN
Solar/Wind Harmer
4.767
253398AE2-221_GEN2
Solar/Wind Harmer
4.767
253317AC1-085 GEN4
Solar/Wind Harmer
8.408
25322209TAIT E
Adder
8.638
25322209TAIT E
Adder
8.444
25183208HLCRTG
Solar/Wind Harmer
4.848
252519AF1-045_GEN
Solar/Wind Harmer
4.396
252516AE2-318_GEN
Solar/Wind Harmer
3.353
252509AD1-136 GEN
Solar/Wind Harmer
0.177
25194408D.CRK1
Adder
4.981
25194508D.CRK3
Adder
0.931
962581AG1-107 GEN
Solar/Wind Harmer
3.226
961491AF2-440 GEN
Solar/Wind Harmer
1.341
270186AC1-089 GEN
Solar/Wind Harmer
3.745
339221AD2-048_GEN
Solar/Wind Harmer
0.866
970077AG2-063 GEN
Solar/Wind Harmer
3.037
972043AH1-570 GEN
Solar/Wind Harmer
1.4
972045AH1-571 GEN
Solar/Wind Harmer
1.12
971125AH1-004 GEN
Solar/Wind Harmer
2.161
970107AG2-081 GEN
Solar/Wind Harmer
1.621
960161AF2-307 GEN
Solar/Wind Harmer
3.228
942891AE2-308 GEN
Solar/Wind Harmer
4.87
970235AG2-159 GEN
Solar/Wind Harmer
1.855
970235AG2-159 GEN
Solar/Wind Harmer
1.133
946101AF1-275 GEN
Solar/Wind Helper
2.225
270471AD2-092_GEN
Solar/Wind Helper
0.83
270159DARBY CT4
50/50
28.462
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.45
25322309TAIT W
50/50
0.45
253343AC1-166 GEN
Solar/Wind Harmer
2.687
253325AC1-069 GEN
Solar/Wind Harmer
2.592
253432AC1-085 GEN2
Solar/Wind Harmer
0.269
946171AF1-282 GEN
Solar/Wind Harmer
10.038
25326309TAIT D
Adder
0.97
960071AF2-298 GEN
Solar/Wind Harmer
4.15
25196808ZIMRHP
Adder
52.581
252507AC2-088 GEN
Solar/Wind Harmer
1.237
945681AF1-233 GEN
Solar/Wind Harmer
12.965
25194608D.CRK4
Adder
1.083
339216AC1-074 GEN
Solar/Wind Harmer
0.956
970593AG2-378 GEN
Solar/Wind Harmer
1.125
25196008MFTGT1
Adder
0.75
943111AE2-339 GEN
Solar/Wind Harmer
0.473
3429421JKCT 10G
Adder
4.349
3429241JKCT 3G
Adder
5.971
270349AD2-093_GEN
Solar/Wind Helper
0.83
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.445
253338AC1-165 GEN
Solar/Wind Harmer
2.687
253333AC1-068 GEN
Solar/Wind Harmer
2.592
241955AC1-078 GEN
Solar/Wind Harmer
8.592
253415AE1-040 GEN
Solar/Wind Harmer
1.168
253316AC1-085 GEN3
Solar/Wind Harmer
8.408
253433AC1-085 GEN1
Solar/Wind Harmer
5.337
946181AF1-283 GEN
Solar/Wind Harmer
13.049
253406AD2-031_GEN
Solar/Wind Harmer
1.233
253303V4-073 C
Solar/Wind Harmer
0.107
958171AF2-111 GEN
Solar/Wind Harmer
18.592
972167AH1-666 GEN
Solar/Wind Harmer
5.527
25196608WSDLE5
Adder
5.694
252510AF1-249 C
Solar/Wind Harmer
0.276
25194608D.CRK4
Adder
1.083
942051AE2-217 GEN
Solar/Wind Harmer
11.594
960801AF2-371 GEN
Solar/Wind Harmer
1.573
964871AG1-351 GEN
Solar/Wind Harmer
1.086
970605AG2-385 GEN
Solar/Wind Harmer
3.037
25196008MFTGT1
Adder
0.726
3429391JKCT 9G
Adder
4.349
270222AC2-111 GEN
Solar/Wind Harmer
4.153
970093AG2-073 GEN
Solar/Wind Harmer
4.621
270273AD2-016 GEN
Solar/Wind Harmer
1.161
CPLELTFEXP_CPLE->PJM
CLTF
0.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.427
LAGNLTFEXP_LAGN->PJM
CLTF
3.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.868
TVALTFEXP_TVA->PJM
CLTF
1.647
NYPJM->LTFIMP_NY
CLTF
0.65
LGEELTFEXP_LGEE->PJM
CLTF
2.466
WECLTFEXP_WEC->PJM
CLTF
0.372
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.317
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.499
MECLTFEXP_MEC->PJM
CLTF
2.097
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 05BEATTY-05COLE 345.0 kV Ckt 1 line l/o AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05BEATTY-05COLE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.06 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1203.72
MW Contribution:1.12
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
28.922
270157DARBY CT2
50/50
28.851
270158DARBY CT3
50/50
28.39
253372AE2-315 SEC3
50/50
1.849
253372AE2-315 SEC3
50/50
1.849
25322309TAIT W
50/50
0.455
945631AF1-228 GEN
Solar/Wind Harmer
13.963
270340AC2-060 GEN
Solar/Wind Harmer
2.678
25306009OHH W.
Adder
2.431
241972AD1-140 GEN
Solar/Wind Harmer
3.722
253349AC2-067 GEN
Solar/Wind Harmer
3.842
253400AC2-068 GEN
Solar/Wind Harmer
1.545
972163AH1-664 GEN
Solar/Wind Harmer
6.768
270160DARBY CT5
50/50
1.55
270161DARBY CT6
50/50
1.529
25326109MON D
50/50
1.291
253370AE2-315 SEC1
50/50
1.955
270518AE2-148 GEN
Solar/Wind Harmer
30.115
253394AE2-221_GEN
Solar/Wind Harmer
4.767
253398AE2-221_GEN2
Solar/Wind Harmer
4.767
253317AC1-085 GEN4
Solar/Wind Harmer
8.408
25322209TAIT E
Adder
8.638
25322209TAIT E
Adder
8.444
25183208HLCRTG
Solar/Wind Harmer
4.848
252519AF1-045_GEN
Solar/Wind Harmer
4.396
252516AE2-318_GEN
Solar/Wind Harmer
3.353
252509AD1-136 GEN
Solar/Wind Harmer
0.177
25194408D.CRK1
Adder
4.981
25194508D.CRK3
Adder
0.931
962581AG1-107 GEN
Solar/Wind Harmer
3.226
961491AF2-440 GEN
Solar/Wind Harmer
1.341
270186AC1-089 GEN
Solar/Wind Harmer
3.745
339221AD2-048_GEN
Solar/Wind Harmer
0.866
970077AG2-063 GEN
Solar/Wind Harmer
3.037
972043AH1-570 GEN
Solar/Wind Harmer
1.4
972045AH1-571 GEN
Solar/Wind Harmer
1.12
971125AH1-004 GEN
Solar/Wind Harmer
2.161
970107AG2-081 GEN
Solar/Wind Harmer
1.621
960161AF2-307 GEN
Solar/Wind Harmer
3.228
942891AE2-308 GEN
Solar/Wind Harmer
4.869
970235AG2-159 GEN
Solar/Wind Harmer
1.855
970235AG2-159 GEN
Solar/Wind Harmer
1.132
946101AF1-275 GEN
Solar/Wind Helper
2.225
270471AD2-092_GEN
Solar/Wind Helper
0.83
270159DARBY CT4
50/50
28.461
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.45
25322309TAIT W
50/50
0.45
253343AC1-166 GEN
Solar/Wind Harmer
2.687
253325AC1-069 GEN
Solar/Wind Harmer
2.592
253432AC1-085 GEN2
Solar/Wind Harmer
0.269
946171AF1-282 GEN
Solar/Wind Harmer
10.038
25326309TAIT D
Adder
0.97
960071AF2-298 GEN
Solar/Wind Harmer
4.15
25196808ZIMRHP
Adder
52.579
252507AC2-088 GEN
Solar/Wind Harmer
1.237
945681AF1-233 GEN
Solar/Wind Harmer
12.964
25194608D.CRK4
Adder
1.083
339216AC1-074 GEN
Solar/Wind Harmer
0.956
970593AG2-378 GEN
Solar/Wind Harmer
1.125
25196008MFTGT1
Adder
0.75
943111AE2-339 GEN
Solar/Wind Harmer
0.473
3429421JKCT 10G
Adder
4.349
3429241JKCT 3G
Adder
5.971
270349AD2-093_GEN
Solar/Wind Helper
0.83
253370AE2-315 SEC1
50/50
1.955
253371AE2-315 SEC2
50/50
1.849
25322209TAIT E
50/50
0.445
253338AC1-165 GEN
Solar/Wind Harmer
2.687
253333AC1-068 GEN
Solar/Wind Harmer
2.592
241955AC1-078 GEN
Solar/Wind Harmer
8.591
253415AE1-040 GEN
Solar/Wind Harmer
1.167
253316AC1-085 GEN3
Solar/Wind Harmer
8.408
253433AC1-085 GEN1
Solar/Wind Harmer
5.337
946181AF1-283 GEN
Solar/Wind Harmer
13.049
253406AD2-031_GEN
Solar/Wind Harmer
1.233
253303V4-073 C
Solar/Wind Harmer
0.107
958171AF2-111 GEN
Solar/Wind Harmer
18.591
972167AH1-666 GEN
Solar/Wind Harmer
5.527
25196608WSDLE5
Adder
5.694
252510AF1-249 C
Solar/Wind Harmer
0.276
25194608D.CRK4
Adder
1.083
942051AE2-217 GEN
Solar/Wind Harmer
11.593
972165AH1-665 GEN
Solar/Wind Harmer
5.414
252524AE2-267 GEN
Solar/Wind Harmer
1.048
25196408WSDLE3
Adder
5.862
25196308WSDLE2
Adder
5.811
25196208WSDLE1
Adder
5.796
25196708WSDLE6
Adder
5.782
25196508WSDLE4
Adder
5.636
270367AC2-061_GEN
Solar/Wind Harmer
1.956
270432AC2-029 GEN
Solar/Wind Harmer
4.061
339243AC2-075 GEN1
Solar/Wind Harmer
0.259
25196108MFTGT2
Adder
0.827
25196108MFTGT2
Adder
0.768
944031AF1-071 GEN
Solar/Wind Harmer
0.512
3429211JKCT 2G
Adder
5.894
270269AC2-059
Solar/Wind Harmer
4.061
270520AE2-214 GEN
Solar/Wind Helper
17.762
270284AF1-227 GEN1
Solar/Wind Helper
1.078
270286AF1-227 GEN2
Solar/Wind Helper
0.395
270287AF1-227 GEN3
Solar/Wind Helper
0.395
960801AF2-371 GEN
Solar/Wind Harmer
1.573
964871AG1-351 GEN
Solar/Wind Harmer
1.086
970605AG2-385 GEN
Solar/Wind Harmer
3.037
25196008MFTGT1
Adder
0.726
3429391JKCT 9G
Adder
4.349
270222AC2-111 GEN
Solar/Wind Harmer
4.153
970093AG2-073 GEN
Solar/Wind Harmer
4.621
270273AD2-016 GEN
Solar/Wind Harmer
1.161
CPLELTFEXP_CPLE->PJM
CLTF
0.379
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.426
LAGNLTFEXP_LAGN->PJM
CLTF
3.022
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.868
TVALTFEXP_TVA->PJM
CLTF
1.647
NYPJM->LTFIMP_NY
CLTF
0.65
LGEELTFEXP_LGEE->PJM
CLTF
2.466
WECLTFEXP_WEC->PJM
CLTF
0.372
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.316
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.499
MECLTFEXP_MEC->PJM
CLTF
2.097
SIGELTFEXP_SIGE->PJM
CLTF
0.142

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.65 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1756.35
MW Contribution:1.42
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.972
270284AF1-227 GEN1
Solar/Wind Harmer
6.854
270286AF1-227 GEN2
Solar/Wind Harmer
2.536
270287AF1-227 GEN3
Solar/Wind Harmer
2.536
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.822
270317AD1-130_GEN
Solar/Wind Harmer
2.998
270520AE2-214 GEN
Solar/Wind Harmer
5.402
970179AG2-119 GEN
Solar/Wind Harmer
6.794
962771AG1-126 GEN
Solar/Wind Harmer
20.924
957201AF2-014 GEN
Solar/Wind Harmer
2.73
270435AC2-044 GEN
Solar/Wind Harmer
1.204
241972AD1-140 GEN
Solar/Wind Harmer
2.573
247607V1-011 GEN
Solar/Wind Harmer
2.229
965051AG1-369 GEN
Solar/Wind Harmer
2.769
270297AD1-101 GEN
Solar/Wind Harmer
1.544
965041AG1-368 GEN
Solar/Wind Harmer
5.379
945631AF1-228 GEN
Solar/Wind Harmer
2.515
270156DARBY CT1
Adder
4.69
270157DARBY CT2
Adder
4.678
270158DARBY CT3
Adder
4.603
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.797
270071AF1-092 GEN
Solar/Wind Harmer
7.236
270024AE2-089 GEN
Solar/Wind Harmer
2.257
24729505KEY G4
Adder
3.093
253349AC2-067 GEN
Solar/Wind Harmer
2.35
253400AC2-068 GEN
Solar/Wind Harmer
0.945
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.472
25306009OHH W.
Adder
1.34
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
965101AG1-375 GEN
Solar/Wind Harmer
4.631
971347AH1-153 GEN
Solar/Wind Harmer
6.938
971771AH1-392 GEN
Solar/Wind Harmer
4.117
270543AE2-219 C
Solar/Wind Harmer
2.339
945581AF1-223 GEN
Solar/Wind Harmer
2.071
944161AF1-084 GEN
Solar/Wind Harmer
1.002
971769AH1-391 GEN
Solar/Wind Harmer
4.525
971029AG2-637 GEN
Solar/Wind Harmer
6.782
971673AH1-337 GEN
Solar/Wind Harmer
2.073
253383AE2-342_GEN
Solar/Wind Harmer
0.399
960681AF2-359 GEN
Solar/Wind Harmer
1.7
970115AG2-085 GEN
Solar/Wind Harmer
1.77
274775LINCOLN ;6U
Adder
3.698
274776LINCOLN ;7U
Adder
3.698
274777LINCOLN ;8U
Adder
3.698
274814UNIV PK N;0U
Adder
2.205
274807UNIV PK N;3U
Adder
2.2
274805UNIV PK N;1U
Adder
2.19
274811UNIV PK N;7U
Adder
2.185
972037AH1-567 GEN1
Adder
0.08
274827FISK ;RP
Adder
3.37
972227AH1-698 GEN1
Adder
1.131
274687WILL CNTY;4U
Adder
12.072
274687WILL CNTY;4U
Adder
12.072
274675JOLIET 29;7U
Adder
13.243
274675JOLIET 29;7U
Adder
12.77
270466AD2-091
50/50
5.429
270471AD2-092_GEN
Solar/Wind Harmer
4.882
938701AE1-092 GEN
Solar/Wind Harmer
21.983
964601AG1-323 GEN
Solar/Wind Harmer
3.2
964601AG1-323 GEN
Solar/Wind Harmer
1.488
270224U2-072_GEN2
Solar/Wind Harmer
1.977
270227U2-072_GEN3
Solar/Wind Harmer
1.977
270228U2-072_GEN4
Solar/Wind Harmer
1.977
270231U2-072_GEN5
Solar/Wind Harmer
1.977
946101AF1-275 GEN
Solar/Wind Harmer
1.348
241960AC2-195 GEN
Solar/Wind Harmer
2.362
971201AH1-060 GEN
Solar/Wind Harmer
1.534
970077AG2-063 GEN
Solar/Wind Harmer
3.836
253378AE2-206_GEN
Solar/Wind Harmer
2.399
276820AF1-078_GEN
Solar/Wind Harmer
1.066
25326509SID D
Adder
0.833
246938BC-WTG3
Solar/Wind Harmer
2.396
246937BC-WTG2
Solar/Wind Harmer
2.355
270007AE1-245 C
Solar/Wind Harmer
3.344
942801AE2-298 GEN
Solar/Wind Harmer
0.852
970611AG2-400 GEN
Solar/Wind Harmer
5.315
270518AE2-148 GEN
Solar/Wind Harmer
6.282
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.68
25322209TAIT E
Adder
4.575
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.402
944541AF1-119 GEN
Solar/Wind Harmer
1.954
960971AF2-388 GEN
Solar/Wind Harmer
5.098
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.929
964611AG1-324 GEN
Solar/Wind Harmer
0.546
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.28
960981AF2-389 GEN
Solar/Wind Harmer
0.691
957891AF2-083 GEN
Solar/Wind Harmer
1.542
970883AG2-550 GEN
Solar/Wind Harmer
4.568
970885AG2-551 GEN
Solar/Wind Harmer
1.062
961051AF2-396 GEN
Solar/Wind Harmer
7.242
961051AF2-396 GEN
Solar/Wind Harmer
3.368
270526AF1-158 GEN
Solar/Wind Harmer
2.06
24441505OLIV SLR
Solar/Wind Harmer
0.061
970321AG2-212 GEN
Solar/Wind Harmer
8.061
270599AE1-208 GEN
Solar/Wind Harmer
3.679
270031AE2-169
Solar/Wind Harmer
3.679
965681AG1-436 GEN
Solar/Wind Harmer
5.624
965791AG1-447 GEN
Solar/Wind Harmer
2.877
970825AG2-519 GEN
Solar/Wind Harmer
4.672
960441AF2-335 GEN
Solar/Wind Harmer
4.424
274770LINCOLN ;1U
Adder
3.698
274771LINCOLN ;2U
Adder
3.698
274808UNIV PK N;4U
Adder
2.176
274803UNIV PARK;6U
Adder
2.533
972259AH1-714 GEN
Adder
8.267
274674JOLIET 9 ;6U
Adder
6.64
270475AD2-096_GEN
50/50
7.813
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.566
942051AE2-217 GEN
Solar/Wind Harmer
13.984
970065AG2-057 GEN
Solar/Wind Harmer
0.767
970605AG2-385 GEN
Solar/Wind Harmer
3.836
241955AC1-078 GEN
Solar/Wind Harmer
5.001
970153AG2-106 GEN
Solar/Wind Harmer
9.124
270491AE1-102 GEN2
Solar/Wind Harmer
0.782
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.663
270247TR4_N_V136
Solar/Wind Harmer
0.472
270258AD1-119 GEN
Solar/Wind Harmer
1.498
959331AF2-224 GEN
Solar/Wind Harmer
5.315
965021AG1-366 GEN
Solar/Wind Harmer
1.236
270044AE2-322 C
Solar/Wind Harmer
0.691
270404AC1-167 GEN
Solar/Wind Harmer
0.576
270588AE1-091_GEN
Solar/Wind Harmer
5.503
270043AE2-236 GEN
Solar/Wind Harmer
2.714
253338AC1-165 GEN
Solar/Wind Harmer
0.526
253333AC1-068 GEN
Solar/Wind Harmer
0.507
970031AG2-029 GEN
Solar/Wind Harmer
14.514
971617AH1-308 GEN
Solar/Wind Harmer
2.796
944531AF1-118 GEN
Solar/Wind Harmer
16.819
270541AE2-072 C
Solar/Wind Harmer
2.163
962031AG1-047 GEN
Solar/Wind Harmer
1.413
957741AF2-068 GEN
Solar/Wind Harmer
7.01
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
970349AG2-230 GEN
Solar/Wind Harmer
6.938
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.591
24642205MAYFLWER
Adder
0.29
970513AG2-328 GEN
Solar/Wind Harmer
8.061
970517AG2-330 GEN
Solar/Wind Harmer
7.311
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.187
946031AF1-268 GEN
Solar/Wind Harmer
3.715
958821AF2-173 GEN
Solar/Wind Harmer
6.18
270004AE1-209 GEN
Solar/Wind Harmer
2.413
274752CRETE EC ;2U
Adder
3.613
274753CRETE EC ;3U
Adder
3.613
274772LINCOLN ;3U
Adder
3.698
274724RIVER EC ;11
Adder
7.758
274802UNIV PARK;5U
Adder
2.533
274826FISK ;BP
Adder
4.755
274800UNIV PARK;3U
Adder
2.53
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.606
274676JOLIET 29;8U
Adder
12.77
274729ELWOOD EC;1P
Adder
7.088
274730ELWOOD EC;6P
Adder
7.088
274734ELWOOD EC;8P
Adder
7.088
274736ELWOOD EC;9P
Adder
7.088
274731ELWOOD EC;2P
Adder
7.088
274733ELWOOD EC;3P
Adder
7.088
274735ELWOOD EC;4P
Adder
7.088
274728ELWOOD EC;5P
Adder
7.088
270054AF2-122 C O1
Solar/Wind Helper
0.823
971549AH1-272 GEN
Solar/Wind Harmer
6.331
270349AD2-093_GEN
Solar/Wind Harmer
4.882
971995AH1-542 GEN
Solar/Wind Harmer
11.801
270223U2-072_GEN1
Solar/Wind Harmer
1.977
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270462AD2-086
Solar/Wind Harmer
6.507
241813AF1-122_GEN
Solar/Wind Harmer
4.908
970593AG2-378 GEN
Solar/Wind Harmer
1.421
962761AG1-125 GEN
Solar/Wind Harmer
20.924
970149AG2-104 GEN
Solar/Wind Harmer
25.841
970155AG2-107 GEN
Solar/Wind Harmer
9.124
246936BC-WTG1
Solar/Wind Harmer
2.355
270489AE1-102 GEN1
Solar/Wind Harmer
0.782
965421AG1-410 GEN
Solar/Wind Harmer
17.855
247521TR3_G114
Solar/Wind Harmer
1.865
270246TR4_N_V150
Solar/Wind Harmer
0.472
24695305TIMB G C
Solar/Wind Harmer
3.018
965011AG1-365 GEN
Solar/Wind Harmer
5.315
270159DARBY CT4
Adder
4.615
944231AF1-091 GEN
Solar/Wind Harmer
1.845
253343AC1-166 GEN
Solar/Wind Harmer
0.526
253325AC1-069 GEN
Solar/Wind Harmer
0.507
960071AF2-298 GEN
Solar/Wind Harmer
2.404
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.058
965651AG1-433 GEN
Solar/Wind Harmer
2.549
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
958861AF2-177 GEN
Solar/Wind Harmer
5.061
247536S-71 GEN
Solar/Wind Harmer
1.868
945111AF1-176 GEN
Solar/Wind Harmer
8.176
270505AE1-170 C O1
Solar/Wind Harmer
6.853
945371AF1-202 GEN
Solar/Wind Harmer
3.186
270449AD2-020 GEN
Solar/Wind Harmer
1.276
943021AE2-325 GEN
Solar/Wind Harmer
1.657
970245AG2-165 GEN
Solar/Wind Harmer
8.061
970825AG2-519 GEN
Solar/Wind Harmer
1.042
270005AE1-210 C O1
Solar/Wind Harmer
2.413
965031AG1-367 GEN
Solar/Wind Harmer
4.414
970373AG2-245 GEN
Solar/Wind Harmer
9.267
274751CRETE EC ;1U
Adder
3.613
274754CRETE EC ;4U
Adder
3.613
274773LINCOLN ;4U
Adder
3.698
274774LINCOLN ;5U
Adder
3.698
274723RIVER EC ;12
Adder
7.85
274812UNIV PK N;8U
Adder
2.185
274801UNIV PARK;4U
Adder
2.53
274676JOLIET 29;8U
Adder
13.243
274674JOLIET 9 ;6U
Adder
6.64
274732ELWOOD EC;7P
Adder
7.088
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.92
LAGNLTFEXP_LAGN->PJM
CLTF
5.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.351
TVALTFEXP_TVA->PJM
CLTF
2.378
NYPJM->LTFIMP_NY
CLTF
1.307
LGEELTFEXP_LGEE->PJM
CLTF
2.299
WECLTFEXP_WEC->PJM
CLTF
1.593
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.587
MECLTFEXP_MEC->PJM
CLTF
6.34
SIGELTFEXP_SIGE->PJM
CLTF
0.182

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1749.36
MW Contribution:1.42
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.416
270471AD2-092_GEN
Solar/Wind Harmer
4.871
938701AE1-092 GEN
Solar/Wind Harmer
21.927
964601AG1-323 GEN
Solar/Wind Harmer
3.191
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.972
270227U2-072_GEN3
Solar/Wind Harmer
1.972
270228U2-072_GEN4
Solar/Wind Harmer
1.972
270231U2-072_GEN5
Solar/Wind Harmer
1.972
946101AF1-275 GEN
Solar/Wind Harmer
1.344
241960AC2-195 GEN
Solar/Wind Harmer
2.356
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.824
270475AD2-096_GEN
50/50
7.794
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.946
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.824
241955AC1-078 GEN
Solar/Wind Harmer
4.991
970153AG2-106 GEN
Solar/Wind Harmer
9.103
270036AE2-216 BAT
50/50
5.958
270284AF1-227 GEN1
Solar/Wind Harmer
6.838
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.804
270317AD1-130_GEN
Solar/Wind Harmer
2.992
270520AE2-214 GEN
Solar/Wind Harmer
5.387
970179AG2-119 GEN
Solar/Wind Harmer
6.779
962771AG1-126 GEN
Solar/Wind Harmer
20.876
957201AF2-014 GEN
Solar/Wind Harmer
2.724
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.566
247607V1-011 GEN
Solar/Wind Harmer
2.224
965051AG1-369 GEN
Solar/Wind Harmer
2.763
270297AD1-101 GEN
Solar/Wind Harmer
1.54
965041AG1-368 GEN
Solar/Wind Harmer
5.367
945631AF1-228 GEN
Solar/Wind Harmer
2.511
270156DARBY CT1
Adder
4.681
270157DARBY CT2
Adder
4.67
270158DARBY CT3
Adder
4.595
963791AG1-232 GEN
Solar/Wind Harmer
6.783
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
270071AF1-092 GEN
Solar/Wind Harmer
7.22
270024AE2-089 GEN
Solar/Wind Harmer
2.252
24729505KEY G4
Adder
3.086
253349AC2-067 GEN
Solar/Wind Harmer
2.345
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
965101AG1-375 GEN
Solar/Wind Harmer
4.621
971347AH1-153 GEN
Solar/Wind Harmer
6.923
971771AH1-392 GEN
Solar/Wind Harmer
4.108
270543AE2-219 C
Solar/Wind Harmer
2.334
945581AF1-223 GEN
Solar/Wind Harmer
2.066
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.515
971029AG2-637 GEN
Solar/Wind Harmer
6.767
971673AH1-337 GEN
Solar/Wind Harmer
2.069
960681AF2-359 GEN
Solar/Wind Harmer
1.696
253383AE2-342_GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
1.766
274775LINCOLN ;6U
Adder
3.69
274776LINCOLN ;7U
Adder
3.69
274777LINCOLN ;8U
Adder
3.69
274814UNIV PK N;0U
Adder
2.2
274807UNIV PK N;3U
Adder
2.195
274805UNIV PK N;1U
Adder
2.186
274811UNIV PK N;7U
Adder
2.181
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.363
972227AH1-698 GEN1
Adder
1.129
274687WILL CNTY;4U
Adder
12.046
274687WILL CNTY;4U
Adder
12.046
274675JOLIET 29;7U
Adder
13.215
274675JOLIET 29;7U
Adder
12.743
274731ELWOOD EC;2P
Adder
7.072
274733ELWOOD EC;3P
Adder
7.072
274735ELWOOD EC;4P
Adder
7.072
274728ELWOOD EC;5P
Adder
7.073
270054AF2-122 C O1
Solar/Wind Helper
0.817
971549AH1-272 GEN
Solar/Wind Harmer
6.317
253378AE2-206_GEN
Solar/Wind Harmer
2.393
276820AF1-078_GEN
Solar/Wind Harmer
1.063
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.391
246937BC-WTG2
Solar/Wind Harmer
2.35
270007AE1-245 C
Solar/Wind Harmer
3.337
942801AE2-298 GEN
Solar/Wind Harmer
0.85
970611AG2-400 GEN
Solar/Wind Harmer
5.303
270518AE2-148 GEN
Solar/Wind Harmer
6.27
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.397
944541AF1-119 GEN
Solar/Wind Harmer
1.949
960971AF2-388 GEN
Solar/Wind Harmer
5.087
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.927
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
960981AF2-389 GEN
Solar/Wind Harmer
0.69
957891AF2-083 GEN
Solar/Wind Harmer
1.539
970883AG2-550 GEN
Solar/Wind Harmer
4.558
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.227
961051AF2-396 GEN
Solar/Wind Harmer
3.361
270526AF1-158 GEN
Solar/Wind Harmer
2.056
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.044
270599AE1-208 GEN
Solar/Wind Harmer
3.671
270031AE2-169
Solar/Wind Harmer
3.671
965681AG1-436 GEN
Solar/Wind Harmer
5.612
965791AG1-447 GEN
Solar/Wind Harmer
2.871
970825AG2-519 GEN
Solar/Wind Harmer
4.662
960441AF2-335 GEN
Solar/Wind Harmer
4.415
274770LINCOLN ;1U
Adder
3.69
274771LINCOLN ;2U
Adder
3.69
274808UNIV PK N;4U
Adder
2.171
274803UNIV PARK;6U
Adder
2.528
972259AH1-714 GEN
Adder
8.249
274674JOLIET 9 ;6U
Adder
6.626
270349AD2-093_GEN
Solar/Wind Harmer
4.871
971995AH1-542 GEN
Solar/Wind Harmer
11.773
270223U2-072_GEN1
Solar/Wind Harmer
1.972
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.492
241813AF1-122_GEN
Solar/Wind Harmer
4.897
970593AG2-378 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
20.876
970149AG2-104 GEN
Solar/Wind Harmer
25.782
970155AG2-107 GEN
Solar/Wind Harmer
9.103
246936BC-WTG1
Solar/Wind Harmer
2.35
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.815
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
24695305TIMB G C
Solar/Wind Harmer
3.012
965011AG1-365 GEN
Solar/Wind Harmer
5.303
270159DARBY CT4
Adder
4.607
944231AF1-091 GEN
Solar/Wind Harmer
1.841
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.398
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.544
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
958861AF2-177 GEN
Solar/Wind Harmer
5.05
247536S-71 GEN
Solar/Wind Harmer
1.864
945111AF1-176 GEN
Solar/Wind Harmer
8.158
270505AE1-170 C O1
Solar/Wind Harmer
6.839
945371AF1-202 GEN
Solar/Wind Harmer
3.179
270449AD2-020 GEN
Solar/Wind Harmer
1.273
943021AE2-325 GEN
Solar/Wind Harmer
1.654
970245AG2-165 GEN
Solar/Wind Harmer
8.044
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.407
965031AG1-367 GEN
Solar/Wind Harmer
4.405
970373AG2-245 GEN
Solar/Wind Harmer
9.248
274751CRETE EC ;1U
Adder
3.605
274754CRETE EC ;4U
Adder
3.605
274773LINCOLN ;4U
Adder
3.69
274774LINCOLN ;5U
Adder
3.69
274723RIVER EC ;12
Adder
7.833
274812UNIV PK N;8U
Adder
2.181
274801UNIV PARK;4U
Adder
2.525
274676JOLIET 29;8U
Adder
13.215
274674JOLIET 9 ;6U
Adder
6.626
274732ELWOOD EC;7P
Adder
7.073
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.303
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.69
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.708
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.483
971617AH1-308 GEN
Solar/Wind Harmer
2.79
944531AF1-118 GEN
Solar/Wind Harmer
16.782
270541AE2-072 C
Solar/Wind Harmer
2.158
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
970349AG2-230 GEN
Solar/Wind Harmer
6.923
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.586
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.044
970517AG2-330 GEN
Solar/Wind Harmer
7.296
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.707
958821AF2-173 GEN
Solar/Wind Harmer
6.167
270004AE1-209 GEN
Solar/Wind Harmer
2.407
274752CRETE EC ;2U
Adder
3.605
274753CRETE EC ;3U
Adder
3.605
274772LINCOLN ;3U
Adder
3.69
274724RIVER EC ;11
Adder
7.742
274802UNIV PARK;5U
Adder
2.528
274826FISK ;BP
Adder
4.745
274800UNIV PARK;3U
Adder
2.525
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.603
274676JOLIET 29;8U
Adder
12.743
274729ELWOOD EC;1P
Adder
7.072
274730ELWOOD EC;6P
Adder
7.073
274734ELWOOD EC;8P
Adder
7.073
274736ELWOOD EC;9P
Adder
7.073
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.837
LAGNLTFEXP_LAGN->PJM
CLTF
5.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.348
TVALTFEXP_TVA->PJM
CLTF
2.374
NYPJM->LTFIMP_NY
CLTF
1.305
LGEELTFEXP_LGEE->PJM
CLTF
2.295
WECLTFEXP_WEC->PJM
CLTF
1.59
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.568
MECLTFEXP_MEC->PJM
CLTF
6.327
SIGELTFEXP_SIGE->PJM
CLTF
0.182

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1747.91
MW Contribution:1.42
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.955
270284AF1-227 GEN1
Solar/Wind Harmer
6.834
270286AF1-227 GEN2
Solar/Wind Harmer
2.528
270287AF1-227 GEN3
Solar/Wind Harmer
2.528
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.95
270302AB2-170 GEN
Solar/Wind Harmer
7.799
270317AD1-130_GEN
Solar/Wind Harmer
2.99
270520AE2-214 GEN
Solar/Wind Harmer
5.383
970179AG2-119 GEN
Solar/Wind Harmer
6.775
962771AG1-126 GEN
Solar/Wind Harmer
20.865
957201AF2-014 GEN
Solar/Wind Harmer
2.722
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.565
247607V1-011 GEN
Solar/Wind Harmer
2.223
965051AG1-369 GEN
Solar/Wind Harmer
2.761
270297AD1-101 GEN
Solar/Wind Harmer
1.539
965041AG1-368 GEN
Solar/Wind Harmer
5.365
945631AF1-228 GEN
Solar/Wind Harmer
2.51
270156DARBY CT1
Adder
4.68
270157DARBY CT2
Adder
4.668
270158DARBY CT3
Adder
4.594
963791AG1-232 GEN
Solar/Wind Harmer
6.779
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
270071AF1-092 GEN
Solar/Wind Harmer
7.217
270024AE2-089 GEN
Solar/Wind Harmer
2.251
24729505KEY G4
Adder
3.085
253349AC2-067 GEN
Solar/Wind Harmer
2.344
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
965101AG1-375 GEN
Solar/Wind Harmer
4.618
971347AH1-153 GEN
Solar/Wind Harmer
6.92
971771AH1-392 GEN
Solar/Wind Harmer
4.106
270543AE2-219 C
Solar/Wind Harmer
2.333
945581AF1-223 GEN
Solar/Wind Harmer
2.065
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.513
971029AG2-637 GEN
Solar/Wind Harmer
6.764
971673AH1-337 GEN
Solar/Wind Harmer
2.068
960681AF2-359 GEN
Solar/Wind Harmer
1.695
253383AE2-342_GEN
Solar/Wind Harmer
0.395
970115AG2-085 GEN
Solar/Wind Harmer
1.765
274775LINCOLN ;6U
Adder
3.688
274776LINCOLN ;7U
Adder
3.688
274777LINCOLN ;8U
Adder
3.688
274814UNIV PK N;0U
Adder
2.199
274807UNIV PK N;3U
Adder
2.194
274805UNIV PK N;1U
Adder
2.185
274811UNIV PK N;7U
Adder
2.18
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.361
972227AH1-698 GEN1
Adder
1.128
274687WILL CNTY;4U
Adder
12.041
274687WILL CNTY;4U
Adder
12.041
274675JOLIET 29;7U
Adder
13.208
274675JOLIET 29;7U
Adder
12.736
274731ELWOOD EC;2P
Adder
7.069
274733ELWOOD EC;3P
Adder
7.069
274735ELWOOD EC;4P
Adder
7.069
274728ELWOOD EC;5P
Adder
7.069
270054AF2-122 C O1
Solar/Wind Helper
0.816
971549AH1-272 GEN
Solar/Wind Harmer
6.314
270466AD2-091
50/50
5.413
270471AD2-092_GEN
Solar/Wind Harmer
4.868
938701AE1-092 GEN
Solar/Wind Harmer
21.914
964601AG1-323 GEN
Solar/Wind Harmer
3.189
964601AG1-323 GEN
Solar/Wind Harmer
1.483
270224U2-072_GEN2
Solar/Wind Harmer
1.971
270227U2-072_GEN3
Solar/Wind Harmer
1.971
270228U2-072_GEN4
Solar/Wind Harmer
1.971
270231U2-072_GEN5
Solar/Wind Harmer
1.971
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.355
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.821
253378AE2-206_GEN
Solar/Wind Harmer
2.391
276820AF1-078_GEN
Solar/Wind Harmer
1.062
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.389
246937BC-WTG2
Solar/Wind Harmer
2.349
270007AE1-245 C
Solar/Wind Harmer
3.335
942801AE2-298 GEN
Solar/Wind Harmer
0.849
970611AG2-400 GEN
Solar/Wind Harmer
5.301
270518AE2-148 GEN
Solar/Wind Harmer
6.267
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.651
25322209TAIT E
Adder
4.667
25322209TAIT E
Adder
4.562
942221AE2-234 GEN
Solar/Wind Harmer
0.349
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.396
944541AF1-119 GEN
Solar/Wind Harmer
1.948
960971AF2-388 GEN
Solar/Wind Harmer
5.085
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.926
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
1.538
960981AF2-389 GEN
Solar/Wind Harmer
0.689
970883AG2-550 GEN
Solar/Wind Harmer
4.556
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.223
961051AF2-396 GEN
Solar/Wind Harmer
3.36
270526AF1-158 GEN
Solar/Wind Harmer
2.055
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.04
270599AE1-208 GEN
Solar/Wind Harmer
3.669
270031AE2-169
Solar/Wind Harmer
3.669
965681AG1-436 GEN
Solar/Wind Harmer
5.609
965791AG1-447 GEN
Solar/Wind Harmer
2.87
970825AG2-519 GEN
Solar/Wind Harmer
4.659
960441AF2-335 GEN
Solar/Wind Harmer
4.412
274770LINCOLN ;1U
Adder
3.688
274771LINCOLN ;2U
Adder
3.688
274808UNIV PK N;4U
Adder
2.17
274803UNIV PARK;6U
Adder
2.527
972259AH1-714 GEN
Adder
8.245
274674JOLIET 9 ;6U
Adder
6.622
270349AD2-093_GEN
Solar/Wind Harmer
4.868
971995AH1-542 GEN
Solar/Wind Harmer
11.766
270223U2-072_GEN1
Solar/Wind Harmer
1.971
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.488
241813AF1-122_GEN
Solar/Wind Harmer
4.895
970593AG2-378 GEN
Solar/Wind Harmer
1.415
962761AG1-125 GEN
Solar/Wind Harmer
20.865
970149AG2-104 GEN
Solar/Wind Harmer
25.768
970155AG2-107 GEN
Solar/Wind Harmer
9.098
246936BC-WTG1
Solar/Wind Harmer
2.349
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.806
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.47
24695305TIMB G C
Solar/Wind Harmer
3.01
965011AG1-365 GEN
Solar/Wind Harmer
5.301
270159DARBY CT4
Adder
4.605
944231AF1-091 GEN
Solar/Wind Harmer
1.84
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.397
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.542
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
958861AF2-177 GEN
Solar/Wind Harmer
5.048
247536S-71 GEN
Solar/Wind Harmer
1.863
945111AF1-176 GEN
Solar/Wind Harmer
8.154
270505AE1-170 C O1
Solar/Wind Harmer
6.835
945371AF1-202 GEN
Solar/Wind Harmer
3.177
270449AD2-020 GEN
Solar/Wind Harmer
1.272
943021AE2-325 GEN
Solar/Wind Harmer
1.653
970245AG2-165 GEN
Solar/Wind Harmer
8.04
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.406
965031AG1-367 GEN
Solar/Wind Harmer
4.403
970373AG2-245 GEN
Solar/Wind Harmer
9.243
274751CRETE EC ;1U
Adder
3.603
274754CRETE EC ;4U
Adder
3.603
274773LINCOLN ;4U
Adder
3.688
274774LINCOLN ;5U
Adder
3.688
274723RIVER EC ;12
Adder
7.829
274812UNIV PK N;8U
Adder
2.18
274801UNIV PARK;4U
Adder
2.524
274676JOLIET 29;8U
Adder
13.208
274674JOLIET 9 ;6U
Adder
6.622
274732ELWOOD EC;7P
Adder
7.069
270475AD2-096_GEN
50/50
7.79
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.95
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.937
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.821
241955AC1-078 GEN
Solar/Wind Harmer
4.989
970153AG2-106 GEN
Solar/Wind Harmer
9.098
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.659
270247TR4_N_V136
Solar/Wind Harmer
0.47
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.301
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.689
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.49
270043AE2-236 GEN
Solar/Wind Harmer
2.707
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.476
971617AH1-308 GEN
Solar/Wind Harmer
2.788
944531AF1-118 GEN
Solar/Wind Harmer
16.774
270541AE2-072 C
Solar/Wind Harmer
2.157
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.991
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
970349AG2-230 GEN
Solar/Wind Harmer
6.92
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.584
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.04
970517AG2-330 GEN
Solar/Wind Harmer
7.292
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.705
958821AF2-173 GEN
Solar/Wind Harmer
6.164
270004AE1-209 GEN
Solar/Wind Harmer
2.406
274752CRETE EC ;2U
Adder
3.603
274753CRETE EC ;3U
Adder
3.603
274772LINCOLN ;3U
Adder
3.688
274724RIVER EC ;11
Adder
7.738
274802UNIV PARK;5U
Adder
2.527
274826FISK ;BP
Adder
4.742
274800UNIV PARK;3U
Adder
2.524
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.602
274676JOLIET 29;8U
Adder
12.736
274729ELWOOD EC;1P
Adder
7.069
274730ELWOOD EC;6P
Adder
7.069
274734ELWOOD EC;8P
Adder
7.069
274736ELWOOD EC;9P
Adder
7.069
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.818
LAGNLTFEXP_LAGN->PJM
CLTF
5.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.347
TVALTFEXP_TVA->PJM
CLTF
2.373
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.294
WECLTFEXP_WEC->PJM
CLTF
1.589
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.564
MECLTFEXP_MEC->PJM
CLTF
6.323
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.27
MW Contribution:1.41
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.05
MW Contribution:1.41
Bus #Bus NameTypeMW Contribution
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7216_05VASSEL 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.74 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1447.54
MW Contribution:1.42
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
4.839
971995AH1-542 GEN
Solar/Wind Harmer
11.797
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
1.198
270391AF1-285 GEN3
Solar/Wind Harmer
1.198
270462AD2-086
Solar/Wind Harmer
6.448
241813AF1-122_GEN
Solar/Wind Harmer
4.917
970593AG2-378 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
20.13
970149AG2-104 GEN
Solar/Wind Harmer
24.861
970155AG2-107 GEN
Solar/Wind Harmer
8.778
246936BC-WTG1
Solar/Wind Harmer
2.324
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
965421AG1-410 GEN
Solar/Wind Harmer
17.611
247521TR3_G114
Solar/Wind Harmer
1.837
270246TR4_N_V150
Solar/Wind Harmer
0.465
24695305TIMB G C
Solar/Wind Harmer
2.974
270159DARBY CT4
Adder
4.69
965011AG1-365 GEN
Solar/Wind Harmer
5.222
253343AC1-166 GEN
Solar/Wind Harmer
0.533
253325AC1-069 GEN
Solar/Wind Harmer
0.514
944231AF1-091 GEN
Solar/Wind Harmer
1.814
960071AF2-298 GEN
Solar/Wind Harmer
2.399
270036AE2-216 BAT
50/50
5.918
270284AF1-227 GEN1
Solar/Wind Harmer
6.793
270286AF1-227 GEN2
Solar/Wind Harmer
2.513
270287AF1-227 GEN3
Solar/Wind Harmer
2.513
270578AF1-285 GEN2
Solar/Wind Harmer
0.461
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.752
270317AD1-130_GEN
Solar/Wind Harmer
2.972
270520AE2-214 GEN
Solar/Wind Harmer
5.445
970179AG2-119 GEN
Solar/Wind Harmer
6.8
962771AG1-126 GEN
Solar/Wind Harmer
20.13
957201AF2-014 GEN
Solar/Wind Harmer
2.694
270435AC2-044 GEN
Solar/Wind Harmer
1.188
241972AD1-140 GEN
Solar/Wind Harmer
2.576
247607V1-011 GEN
Solar/Wind Harmer
2.2
270297AD1-101 GEN
Solar/Wind Harmer
1.527
965051AG1-369 GEN
Solar/Wind Harmer
2.727
945631AF1-228 GEN
Solar/Wind Harmer
2.554
270156DARBY CT1
Adder
4.766
270157DARBY CT2
Adder
4.755
270158DARBY CT3
Adder
4.679
965041AG1-368 GEN
Solar/Wind Harmer
5.294
943861AF1-054 GEN
Solar/Wind Harmer
1.935
943851AF1-053 GEN
Solar/Wind Harmer
0.935
963791AG1-232 GEN
Solar/Wind Harmer
6.686
270024AE2-089 GEN
Solar/Wind Harmer
2.223
270071AF1-092 GEN
Solar/Wind Harmer
7.094
253349AC2-067 GEN
Solar/Wind Harmer
2.343
253400AC2-068 GEN
Solar/Wind Harmer
0.942
24729505KEY G4
Adder
3.036
25306009OHH W.
Adder
1.338
253372AE2-315 SEC3
Adder
0.878
253372AE2-315 SEC3
Adder
0.878
961761AG1-017 GEN
Solar/Wind Harmer
0.197
958711AF2-162 GEN
Solar/Wind Harmer
0.464
965101AG1-375 GEN
Solar/Wind Harmer
4.55
971347AH1-153 GEN
Solar/Wind Harmer
6.79
270543AE2-219 C
Solar/Wind Harmer
2.31
945581AF1-223 GEN
Solar/Wind Harmer
2.036
971771AH1-392 GEN
Solar/Wind Harmer
4.033
253383AE2-342_GEN
Solar/Wind Harmer
0.396
971029AG2-637 GEN
Solar/Wind Harmer
6.703
971673AH1-337 GEN
Solar/Wind Harmer
2.05
944161AF1-084 GEN
Solar/Wind Harmer
0.982
971769AH1-391 GEN
Solar/Wind Harmer
4.432
960681AF2-359 GEN
Solar/Wind Harmer
1.665
970115AG2-085 GEN
Solar/Wind Harmer
1.742
270054AF2-122 C O1
Solar/Wind Helper
0.786
270594AE1-207 GEN
Solar/Wind Harmer
2.721
270466AD2-091
50/50
5.38
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.937
964601AG1-323 GEN
Solar/Wind Harmer
3.19
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
946101AF1-275 GEN
Solar/Wind Harmer
1.359
241960AC2-195 GEN
Solar/Wind Harmer
2.364
971201AH1-060 GEN
Solar/Wind Harmer
1.536
970077AG2-063 GEN
Solar/Wind Harmer
3.843
253378AE2-206_GEN
Solar/Wind Harmer
2.386
276820AF1-078_GEN
Solar/Wind Harmer
1.06
25326509SID D
Adder
0.829
246938BC-WTG3
Solar/Wind Harmer
2.364
246937BC-WTG2
Solar/Wind Harmer
2.324
270007AE1-245 C
Solar/Wind Harmer
3.3
942801AE2-298 GEN
Solar/Wind Harmer
0.841
270518AE2-148 GEN
Solar/Wind Harmer
6.356
970611AG2-400 GEN
Solar/Wind Harmer
5.222
942861AE2-305 GEN
Solar/Wind Harmer
3.921
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.675
25322209TAIT E
Adder
4.57
942221AE2-234 GEN
Solar/Wind Harmer
0.344
253370AE2-315 SEC1
Adder
0.928
270201AC2-176 GEN
Solar/Wind Harmer
2.369
944541AF1-119 GEN
Solar/Wind Harmer
1.919
960971AF2-388 GEN
Solar/Wind Harmer
5.008
247620Y3-023
Adder
0.211
247621Y3-024
Adder
0.11
964611AG1-324 GEN
Solar/Wind Harmer
0.538
964611AG1-324 GEN
Solar/Wind Harmer
0.239
270216AD2-079_GEN
Solar/Wind Harmer
0.274
970883AG2-550 GEN
Solar/Wind Harmer
4.511
970885AG2-551 GEN
Solar/Wind Harmer
1.049
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.511
961051AF2-396 GEN
Solar/Wind Harmer
7.096
961051AF2-396 GEN
Solar/Wind Harmer
3.301
270526AF1-158 GEN
Solar/Wind Harmer
2.018
270599AE1-208 GEN
Solar/Wind Harmer
3.619
270031AE2-169
Solar/Wind Harmer
3.619
24441505OLIV SLR
Solar/Wind Harmer
0.059
970321AG2-212 GEN
Solar/Wind Harmer
7.888
965681AG1-436 GEN
Solar/Wind Harmer
5.508
965791AG1-447 GEN
Solar/Wind Harmer
2.818
970825AG2-519 GEN
Solar/Wind Harmer
4.6
960441AF2-335 GEN
Solar/Wind Harmer
4.356
270383AD1-128 GEN
Solar/Wind Harmer
2.637
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.037
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
965651AG1-433 GEN
Solar/Wind Harmer
2.504
247536S-71 GEN
Solar/Wind Harmer
1.844
958861AF2-177 GEN
Solar/Wind Harmer
4.973
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
8.011
945371AF1-202 GEN
Solar/Wind Harmer
3.132
270505AE1-170 C O1
Solar/Wind Harmer
6.714
270449AD2-020 GEN
Solar/Wind Harmer
1.25
943021AE2-325 GEN
Solar/Wind Harmer
1.624
970245AG2-165 GEN
Solar/Wind Harmer
7.888
970825AG2-519 GEN
Solar/Wind Harmer
1.026
270005AE1-210 C O1
Solar/Wind Harmer
2.375
965031AG1-367 GEN
Solar/Wind Harmer
4.346
970373AG2-245 GEN
Solar/Wind Harmer
9.08
270032AE2-172
Solar/Wind Harmer
0.861
270475AD2-096_GEN
50/50
7.743
942871AE2-306 GEN
Solar/Wind Harmer
0.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.461
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.561
942051AE2-217 GEN
Solar/Wind Harmer
14.042
970065AG2-057 GEN
Solar/Wind Harmer
0.768
970605AG2-385 GEN
Solar/Wind Harmer
3.843
241955AC1-078 GEN
Solar/Wind Harmer
5.062
970153AG2-106 GEN
Solar/Wind Harmer
8.778
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.639
270247TR4_N_V136
Solar/Wind Harmer
0.465
270258AD1-119 GEN
Solar/Wind Harmer
1.477
959331AF2-224 GEN
Solar/Wind Harmer
5.222
965021AG1-366 GEN
Solar/Wind Harmer
1.214
270044AE2-322 C
Solar/Wind Harmer
0.682
270404AC1-167 GEN
Solar/Wind Harmer
0.568
270588AE1-091_GEN
Solar/Wind Harmer
5.477
253338AC1-165 GEN
Solar/Wind Harmer
0.533
253333AC1-068 GEN
Solar/Wind Harmer
0.514
270043AE2-236 GEN
Solar/Wind Harmer
2.66
970031AG2-029 GEN
Solar/Wind Harmer
14.237
971617AH1-308 GEN
Solar/Wind Harmer
2.754
270541AE2-072 C
Solar/Wind Harmer
2.143
944531AF1-118 GEN
Solar/Wind Harmer
16.503
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
962031AG1-047 GEN
Solar/Wind Harmer
1.393
957741AF2-068 GEN
Solar/Wind Harmer
6.912
970349AG2-230 GEN
Solar/Wind Harmer
6.79
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.539
24642205MAYFLWER
Adder
0.284
970513AG2-328 GEN
Solar/Wind Harmer
7.888
970517AG2-330 GEN
Solar/Wind Harmer
7.154
24441205WTRV SLR C
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.659
247604X1-042
Adder
0.183
958821AF2-173 GEN
Solar/Wind Harmer
6.084
270004AE1-209 GEN
Solar/Wind Harmer
2.375
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.234
LAGNLTFEXP_LAGN->PJM
CLTF
5.039
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.304
TVALTFEXP_TVA->PJM
CLTF
2.34
NYPJM->LTFIMP_NY
CLTF
1.287
LGEELTFEXP_LGEE->PJM
CLTF
2.274
WECLTFEXP_WEC->PJM
CLTF
1.561
AG2-052LTFEXP_AG2-052->PJM
LTF
0.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.444
MECLTFEXP_MEC->PJM
CLTF
6.218
SIGELTFEXP_SIGE->PJM
CLTF
0.179

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5081.52
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.2
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:2.31
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:1.81
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:2.35
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:1.75
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.95 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5175.39
MW Contribution:2.87
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
16.969
270475AD2-096_GEN
50/50
10
970153AG2-106 GEN
Solar/Wind Harmer
25.994
961921AG1-034 GEN
Solar/Wind Harmer
20.196
241955AC1-078 GEN
Solar/Wind Harmer
11.082
241974AD2-163_GEN2
Solar/Wind Harmer
2.945
942051AE2-217 GEN
Solar/Wind Harmer
26.379
942871AE2-306 GEN
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.673
970605AG2-385 GEN
Solar/Wind Harmer
7.746
270485AE1-090_GEN
Solar/Wind Harmer
0.845
253338AC1-165 GEN
Solar/Wind Harmer
1.495
253333AC1-068 GEN
Solar/Wind Harmer
1.442
960801AF2-371 GEN
Solar/Wind Harmer
3.362
964871AG1-351 GEN
Solar/Wind Harmer
2.322
270273AD2-016 GEN
Solar/Wind Harmer
3.416
944531AF1-118 GEN
Solar/Wind Harmer
44.619
972173AH1-669 GEN
Solar/Wind Harmer
6.355
270043AE2-236 GEN
Solar/Wind Harmer
6.955
959331AF2-224 GEN
Solar/Wind Harmer
12.615
965021AG1-366 GEN
Solar/Wind Harmer
2.934
253303V4-073 C
Solar/Wind Harmer
0.146
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
970513AG2-328 GEN
Solar/Wind Harmer
22.419
970517AG2-330 GEN
Solar/Wind Harmer
20.333
253415AE1-040 GEN
Solar/Wind Harmer
1.412
970349AG2-230 GEN
Solar/Wind Harmer
18.681
270191TR4_S_V150
Solar/Wind Harmer
3.726
270247TR4_N_V136
Solar/Wind Harmer
1.057
24721905FLATG4
Adder
25.137
971617AH1-308 GEN
Solar/Wind Harmer
7.196
270491AE1-102 GEN2
Solar/Wind Harmer
1.608
962031AG1-047 GEN
Solar/Wind Harmer
3.725
957741AF2-068 GEN
Solar/Wind Harmer
18.489
970031AG2-029 GEN
Solar/Wind Harmer
36.885
958821AF2-173 GEN
Solar/Wind Harmer
17.206
270004AE1-209 GEN
Solar/Wind Harmer
6.717
946031AF1-268 GEN
Solar/Wind Harmer
10.188
253406AD2-031_GEN
Solar/Wind Harmer
1.568
970289AG2-191 GEN
Solar/Wind Harmer
0.938
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247642Z2-115 C
Solar/Wind Harmer
0.078
270437AC2-090 C
Solar/Wind Harmer
6.819
270119AB2-067 GEN1
50/50
18.357
270120AB2-067 GEN2
50/50
18.357
270160DARBY CT5
50/50
0.729
270161DARBY CT6
50/50
0.719
270466AD2-091
50/50
8.11
270471AD2-092_GEN
Solar/Wind Harmer
6.249
946101AF1-275 GEN
Solar/Wind Harmer
2.346
942861AE2-305 GEN
Solar/Wind Harmer
11.513
270224U2-072_GEN2
Solar/Wind Harmer
2.862
270227U2-072_GEN3
Solar/Wind Harmer
2.862
270228U2-072_GEN4
Solar/Wind Harmer
2.862
270231U2-072_GEN5
Solar/Wind Harmer
2.862
970077AG2-063 GEN
Solar/Wind Harmer
7.746
270518AE2-148 GEN
Solar/Wind Harmer
16.865
964601AG1-323 GEN
Solar/Wind Harmer
4.402
964601AG1-323 GEN
Solar/Wind Harmer
2.047
938701AE1-092 GEN
Solar/Wind Harmer
28.355
253378AE2-206_GEN
Solar/Wind Harmer
4.74
276820AF1-078_GEN
Solar/Wind Harmer
2.106
25326509SID D
Adder
1.698
25326109MON D
Adder
1.683
25322209TAIT E
Adder
12.344
25322209TAIT E
Adder
12.066
970611AG2-400 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
944541AF1-119 GEN
Solar/Wind Harmer
5.27
960971AF2-388 GEN
Solar/Wind Harmer
13.754
970321AG2-212 GEN
Solar/Wind Harmer
22.419
942221AE2-234 GEN
Solar/Wind Harmer
0.913
246938BC-WTG3
Solar/Wind Harmer
4.925
246937BC-WTG2
Solar/Wind Harmer
4.841
270599AE1-208 GEN
Solar/Wind Harmer
10.052
270031AE2-169
Solar/Wind Harmer
10.052
253394AE2-221_GEN
Solar/Wind Harmer
5.603
253398AE2-221_GEN2
Solar/Wind Harmer
5.603
270201AC2-176 GEN
Solar/Wind Harmer
6.336
964611AG1-324 GEN
Solar/Wind Harmer
1.452
964611AG1-324 GEN
Solar/Wind Harmer
0.644
247621Y3-024
Adder
0.297
970883AG2-550 GEN
Solar/Wind Harmer
12.281
970885AG2-551 GEN
Solar/Wind Harmer
2.856
970825AG2-519 GEN
Solar/Wind Harmer
12.934
960441AF2-335 GEN
Solar/Wind Harmer
12.253
270383AD1-128 GEN
Solar/Wind Harmer
7.465
24379505HDWTR1G C
Solar/Wind Harmer
9.658
270209AC1-174_GEN
Solar/Wind Harmer
6.816
926881AC1-175 GEN
Solar/Wind Harmer
6.816
965681AG1-436 GEN
Solar/Wind Harmer
15.255
965791AG1-447 GEN
Solar/Wind Harmer
7.805
270216AD2-079_GEN
Solar/Wind Harmer
0.738
247620Y3-023
Adder
0.56
274770LINCOLN ;1U
Adder
10.257
274771LINCOLN ;2U
Adder
10.257
270156DARBY CT1
50/50
13.604
270157DARBY CT2
50/50
13.571
270158DARBY CT3
50/50
13.354
270036AE2-216 BAT
50/50
8.921
962771AG1-126 GEN
Solar/Wind Harmer
59.614
270284AF1-227 GEN1
Solar/Wind Harmer
9.137
270286AF1-227 GEN2
Solar/Wind Harmer
3.38
270287AF1-227 GEN3
Solar/Wind Harmer
3.38
270459AD2-067 GEN
Solar/Wind Harmer
13.262
961821AG1-024 GEN
Solar/Wind Harmer
13.464
270520AE2-214 GEN
Solar/Wind Harmer
9.4
270054AF2-122 C O1
Solar/Wind Harmer
5.025
253383AE2-342_GEN
Solar/Wind Harmer
1.352
241973AD2-163_GEN1
Solar/Wind Harmer
2.945
943861AF1-054 GEN
Solar/Wind Harmer
5.682
943851AF1-053 GEN
Solar/Wind Harmer
2.746
270578AF1-285 GEN2
Solar/Wind Harmer
0.673
945631AF1-228 GEN
Solar/Wind Harmer
6.732
270302AB2-170 GEN
Solar/Wind Harmer
11.684
270317AD1-130_GEN
Solar/Wind Harmer
4.479
241972AD1-140 GEN
Solar/Wind Harmer
6.007
970689AG2-444 GEN
Solar/Wind Harmer
21.667
270432AC2-029 GEN
Solar/Wind Harmer
9.275
270269AC2-059
Solar/Wind Harmer
11.946
24729505KEY G4
Adder
8.242
270071AF1-092 GEN
Solar/Wind Harmer
18.992
253372AE2-315 SEC3
Adder
2.385
253372AE2-315 SEC3
Adder
2.385
958711AF2-162 GEN
Solar/Wind Harmer
1.273
965101AG1-375 GEN
Solar/Wind Harmer
12.544
25306009OHH W.
Adder
3.614
253349AC2-067 GEN
Solar/Wind Harmer
6.244
253400AC2-068 GEN
Solar/Wind Harmer
2.511
945581AF1-223 GEN
Solar/Wind Harmer
5.655
963791AG1-232 GEN
Solar/Wind Harmer
16.817
971347AH1-153 GEN
Solar/Wind Harmer
18.681
965051AG1-369 GEN
Solar/Wind Harmer
6.202
965041AG1-368 GEN
Solar/Wind Harmer
12.384
270024AE2-089 GEN
Solar/Wind Harmer
5.81
957201AF2-014 GEN
Solar/Wind Harmer
5.611
270435AC2-044 GEN
Solar/Wind Harmer
2.474
270340AC2-060 GEN
Solar/Wind Harmer
3.749
961761AG1-017 GEN
Solar/Wind Harmer
0.528
270543AE2-219 C
Solar/Wind Harmer
6.289
971029AG2-637 GEN
Solar/Wind Harmer
18.391
971673AH1-337 GEN
Solar/Wind Harmer
5.637
970115AG2-085 GEN
Solar/Wind Harmer
4.901
270594AE1-207 GEN
Solar/Wind Harmer
17.978
965461AG1-414 GEN
Solar/Wind Harmer
2.772
970289AG2-191 GEN
Solar/Wind Harmer
2.322
270240V3-007_GEN2
Solar/Wind Harmer
7.556
960681AF2-359 GEN
Solar/Wind Harmer
4.61
971771AH1-392 GEN
Solar/Wind Harmer
10.956
274775LINCOLN ;6U
Adder
10.257
274776LINCOLN ;7U
Adder
10.257
274777LINCOLN ;8U
Adder
10.257
274814UNIV PK N;0U
Adder
6.103
274807UNIV PK N;3U
Adder
6.089
274805UNIV PK N;1U
Adder
6.063
274811UNIV PK N;7U
Adder
6.05
972227AH1-698 GEN1
Adder
3.146
972037AH1-567 GEN1
Adder
0.221
274827FISK ;RP
Adder
9.358
274687WILL CNTY;4U
Adder
33.62
274687WILL CNTY;4U
Adder
33.62
274675JOLIET 29;7U
Adder
36.901
274675JOLIET 29;7U
Adder
35.583
274731ELWOOD EC;2P
Adder
19.763
274733ELWOOD EC;3P
Adder
19.763
274735ELWOOD EC;4P
Adder
19.763
274728ELWOOD EC;5P
Adder
19.763
274746AC1-111 G10
Adder
6.698
274744AC1-111 GEN8
Adder
6.698
25196408WSDLE3
Adder
10.507
25196308WSDLE2
Adder
10.416
25196208WSDLE1
Adder
10.39
25196708WSDLE6
Adder
10.364
25196508WSDLE4
Adder
10.103
274823ROCKFORD ;21
Adder
23.006
254304AE2-114 C
Solar/Wind Helper
0.216
241982AE2-343 S C
Solar/Wind Helper
0.22
241997AF1-093 GEN
Solar/Wind Helper
0.251
23750501ELLIOTTS
Solar/Wind Helper
0.617
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.307
20091526CHSTN_FL
Solar/Wind Helper
0.557
20090526Q36
Solar/Wind Helper
0.998
203993AD2-133_GEN1
Solar/Wind Helper
0.998
203846AF2-130 C
Solar/Wind Helper
0.431
238126S14_GEN_1
Solar/Wind Helper
0.648
941231AE2-117 GEN
Solar/Wind Helper
0.453
203855AF2-088 C
Solar/Wind Helper
0.146
203804AE2-113_GEN
Solar/Wind Helper
1.661
274808UNIV PK N;4U
Adder
6.023
972259AH1-714 GEN
Adder
23.016
274803UNIV PARK;6U
Adder
7.033
24728805RICHG1
Adder
4.555
24728905RICHG2
Adder
4.555
274674JOLIET 9 ;6U
Adder
18.512
274696ROCKY RD ;4P
Adder
13.603
274695ROCKY RD ;2P
Adder
13.289
274693ROCKY RD ;1P
Adder
13.158
274697ROCKY RD ;3P
Adder
3.61
274683WAUKEGAN ;8U
Adder
25.124
274683WAUKEGAN ;8U
Adder
21.178
25194408D.CRK1
Adder
8.991
25194508D.CRK3
Adder
1.681
23652301WDPWR_K20
Solar/Wind Helper
0.139
241967AE2-285_GEN
Solar/Wind Helper
0.629
241801AE1-079 GEN
Solar/Wind Helper
0.245
241985AE1-237 GEN
Solar/Wind Helper
0.245
962101AG1-054 GEN
Solar/Wind Helper
0.639
946071AF1-272 GEN
Solar/Wind Helper
2.599
23585401KL_K28_T16
Solar/Wind Helper
1.182
203955AF1-039 C O1
Solar/Wind Helper
0.351
944781AF1-143 GEN
Solar/Wind Helper
2.342
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.34
20088926STNY CRK
Solar/Wind Helper
0.78
203940AF1-140 C
Solar/Wind Helper
0.378
20088626ARWF_N39
Solar/Wind Helper
1.161
20303426NA_O38_P22
Solar/Wind Helper
0.952
946381AF1-302 GEN
Solar/Wind Helper
0.212
203853AF1-134 C O1
Solar/Wind Helper
0.457
203952AE2-129 C
Solar/Wind Helper
0.453
203946AE2-131 C
Solar/Wind Helper
0.454
238120AE2-309 GEN
Solar/Wind Helper
0.406
238217AF1-153 C O1
Solar/Wind Helper
0.226
20398826ARMNA MT
Solar/Wind Helper
1.425
253317AC1-085 GEN4
Solar/Wind Harmer
9.161
270166AC1-044 GEN3
50/50
18.357
270159DARBY CT4
50/50
13.387
962761AG1-125 GEN
Solar/Wind Harmer
59.614
970149AG2-104 GEN
Solar/Wind Harmer
73.623
970155AG2-107 GEN
Solar/Wind Harmer
25.994
270349AD2-093_GEN
Solar/Wind Harmer
6.249
270223U2-072_GEN1
Solar/Wind Harmer
2.862
270578AF1-285 GEN2
Solar/Wind Harmer
1.75
270391AF1-285 GEN3
Solar/Wind Harmer
1.75
970593AG2-378 GEN
Solar/Wind Harmer
2.869
270462AD2-086
Solar/Wind Harmer
9.72
253343AC1-166 GEN
Solar/Wind Harmer
1.495
253325AC1-069 GEN
Solar/Wind Harmer
1.442
25326309TAIT D
Adder
1.387
960071AF2-298 GEN
Solar/Wind Harmer
6.296
965011AG1-365 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
965651AG1-433 GEN
Solar/Wind Harmer
6.877
970245AG2-165 GEN
Solar/Wind Harmer
22.419
247643Z2-116 C
Solar/Wind Harmer
0.085
274772LINCOLN ;3U
Adder
10.257
274724RIVER EC ;11
Adder
21.436
274752CRETE EC ;2U
Adder
9.969
274753CRETE EC ;3U
Adder
9.969
24642205MAYFLWER
Adder
0.769
274802UNIV PARK;5U
Adder
7.033
972228AH1-698 GEN2
Adder
4.468
274826FISK ;BP
Adder
13.204
274800UNIV PARK;3U
Adder
7.031
972038AH1-567 GEN2
Adder
0.44
274676JOLIET 29;8U
Adder
35.583
274729ELWOOD EC;1P
Adder
19.763
274730ELWOOD EC;6P
Adder
19.763
274734ELWOOD EC;8P
Adder
19.763
274736ELWOOD EC;9P
Adder
19.763
274682WAUKEGAN ;7U
Adder
21.437
25196608WSDLE5
Adder
10.207
25194608D.CRK4
Adder
1.955
24728705AND G3
Adder
9.473
24728505AND G1
Adder
4.529
972236AH1-702 GEN2
Adder
2.586
235058AG1-386 C
Solar/Wind Helper
0.458
237048AF1-022 C
Solar/Wind Helper
0.178
254305AE2-115 C
Solar/Wind Helper
0.216
237043AE2-125 C
Solar/Wind Helper
0.174
964991AG1-363 GEN
Solar/Wind Helper
3.62
202652Y1-033 WT C
Solar/Wind Helper
0.532
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089026BF_G21_K23
Solar/Wind Helper
0.447
23750701CROSSCHOOL
Solar/Wind Helper
1.136
203818AF1-086 GEN
Solar/Wind Helper
1.615
238118U2-030_1
Solar/Wind Helper
0.272
238127S14_GEN_2
Solar/Wind Helper
0.648
203854AF2-039 C
Solar/Wind Helper
0.304
20334926Z1-069 C
Solar/Wind Helper
1.285
238202AE2-262_GEN
Solar/Wind Helper
0.914
959441AF2-235 GEN
Solar/Wind Helper
0.223
941421AE2-139 GEN
Solar/Wind Helper
2.214
253316AC1-085 GEN3
Solar/Wind Harmer
9.161
253433AC1-085 GEN1
Solar/Wind Harmer
5.815
958861AF2-177 GEN
Solar/Wind Harmer
13.71
971995AH1-542 GEN
Solar/Wind Harmer
13.79
945371AF1-202 GEN
Solar/Wind Harmer
8.699
247521TR3_G114
Solar/Wind Harmer
4.176
270246TR4_N_V150
Solar/Wind Harmer
1.057
24721705FLATG2
Adder
25.137
965421AG1-410 GEN
Solar/Wind Harmer
37.184
246936BC-WTG1
Solar/Wind Harmer
4.841
270489AE1-102 GEN1
Solar/Wind Harmer
1.608
247536S-71 GEN
Solar/Wind Harmer
4.98
270005AE1-210 C O1
Solar/Wind Harmer
6.717
965031AG1-367 GEN
Solar/Wind Harmer
12.29
270063AE2-323 C
Solar/Wind Harmer
2.705
24695305TIMB G C
Solar/Wind Harmer
6.75
970825AG2-519 GEN
Solar/Wind Harmer
2.886
270263AC1-001 GEN
Solar/Wind Harmer
1.282
270032AE2-172
Solar/Wind Harmer
5.689
970291AG2-192 GEN
Solar/Wind Harmer
1.589
942081AE2-220 GEN
Solar/Wind Harmer
7.808
270239V3-007_GEN1
Solar/Wind Harmer
2.102
24639705ELKHART HY
Adder
0.187
274773LINCOLN ;4U
Adder
10.257
274774LINCOLN ;5U
Adder
10.257
274723RIVER EC ;12
Adder
21.689
274751CRETE EC ;1U
Adder
9.969
274754CRETE EC ;4U
Adder
9.969
274812UNIV PK N;8U
Adder
6.05
274801UNIV PARK;4U
Adder
7.031
274676JOLIET 29;8U
Adder
36.901
274674JOLIET 9 ;6U
Adder
18.512
274732ELWOOD EC;7P
Adder
19.763
274745AC1-111 GEN9
Adder
6.698
274682WAUKEGAN ;7U
Adder
21.437
274828WAUKEGAN ;BP
Adder
13.169
25194608D.CRK4
Adder
1.955
24728605AND G2
Adder
4.529
274822ROCKFORD ;11
Adder
23.174
972235AH1-702 GEN1
Adder
2.974
25196808ZIMRHP
Adder
57.753
254303AC2-168 GEN
Solar/Wind Helper
0.156
237046AF1-021 C
Solar/Wind Helper
0.468
241966AE1-183 GEN
Solar/Wind Helper
0.251
238185AF2-356 C
Solar/Wind Helper
2.051
20089226LOOKOUT
Solar/Wind Helper
0.549
20088826HIGHLAND
Solar/Wind Helper
0.858
20094526CT_V3-030
Solar/Wind Helper
0.452
235054AD2-180 GEN
Solar/Wind Helper
1.586
964201AG1-281 GEN
Solar/Wind Helper
0.463
238117U2-030
Solar/Wind Helper
0.272
235531U2-073 GEN
Solar/Wind Helper
2.578
964391AG1-301 GEN
Solar/Wind Helper
0.452
203954AE2-126 C
Solar/Wind Helper
0.449
23751201ROTHROCK
Solar/Wind Helper
0.661
238206AE2-263_GEN
Solar/Wind Helper
0.87
959471AF2-238 GEN
Solar/Wind Helper
0.445
203860AG1-193 C
Solar/Wind Helper
0.222
23562501BACKB
Solar/Wind Helper
0.804
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
CPLELTFEXP_CPLE->PJM
CLTF
2.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.191
LAGNLTFEXP_LAGN->PJM
CLTF
17.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.421
TVALTFEXP_TVA->PJM
CLTF
8.605
NYPJM->LTFIMP_NY
CLTF
5.405
LGEELTFEXP_LGEE->PJM
CLTF
7.595
WECLTFEXP_WEC->PJM
CLTF
4.506
AG2-052LTFEXP_AG2-052->PJM
LTF
0.28
AH1-155LTFEXP_AH1-155->PJM
LTF
0.42
CBM West 1LTFEXP_CBM-W1->PJM
CBM
154.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.973
MECLTFEXP_MEC->PJM
CLTF
18.683
SIGELTFEXP_SIGE->PJM
CLTF
0.577

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.6 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4995.09
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
18.415
270120AB2-067 GEN2
50/50
18.415
270160DARBY CT5
50/50
0.738
270161DARBY CT6
50/50
0.728
270466AD2-091
50/50
8.21
270471AD2-092_GEN
Solar/Wind Harmer
6.312
946101AF1-275 GEN
Solar/Wind Harmer
2.373
942861AE2-305 GEN
Solar/Wind Harmer
11.65
270224U2-072_GEN2
Solar/Wind Harmer
2.896
270227U2-072_GEN3
Solar/Wind Harmer
2.896
270228U2-072_GEN4
Solar/Wind Harmer
2.896
270231U2-072_GEN5
Solar/Wind Harmer
2.896
970077AG2-063 GEN
Solar/Wind Harmer
7.841
270518AE2-148 GEN
Solar/Wind Harmer
17.081
964601AG1-323 GEN
Solar/Wind Harmer
4.458
964601AG1-323 GEN
Solar/Wind Harmer
2.073
938701AE1-092 GEN
Solar/Wind Harmer
28.718
253378AE2-206_GEN
Solar/Wind Harmer
4.802
276820AF1-078_GEN
Solar/Wind Harmer
2.133
25326509SID D
Adder
1.721
25326109MON D
Adder
1.706
25322209TAIT E
Adder
12.514
25322209TAIT E
Adder
12.233
970611AG2-400 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
944541AF1-119 GEN
Solar/Wind Harmer
5.341
960971AF2-388 GEN
Solar/Wind Harmer
13.939
970321AG2-212 GEN
Solar/Wind Harmer
22.72
942221AE2-234 GEN
Solar/Wind Harmer
0.925
246938BC-WTG3
Solar/Wind Harmer
4.992
246937BC-WTG2
Solar/Wind Harmer
4.907
253394AE2-221_GEN
Solar/Wind Harmer
5.683
253398AE2-221_GEN2
Solar/Wind Harmer
5.683
270599AE1-208 GEN
Solar/Wind Harmer
10.191
270031AE2-169
Solar/Wind Harmer
10.191
270201AC2-176 GEN
Solar/Wind Harmer
6.424
964611AG1-324 GEN
Solar/Wind Harmer
1.472
964611AG1-324 GEN
Solar/Wind Harmer
0.653
247621Y3-024
Adder
0.301
970883AG2-550 GEN
Solar/Wind Harmer
12.452
970885AG2-551 GEN
Solar/Wind Harmer
2.896
970825AG2-519 GEN
Solar/Wind Harmer
13.114
960441AF2-335 GEN
Solar/Wind Harmer
12.423
270383AD1-128 GEN
Solar/Wind Harmer
7.569
24379505HDWTR1G C
Solar/Wind Harmer
9.793
270209AC1-174_GEN
Solar/Wind Harmer
6.911
926881AC1-175 GEN
Solar/Wind Harmer
6.911
965681AG1-436 GEN
Solar/Wind Harmer
15.464
965791AG1-447 GEN
Solar/Wind Harmer
7.912
270216AD2-079_GEN
Solar/Wind Harmer
0.748
253317AC1-085 GEN4
Solar/Wind Harmer
10.337
247620Y3-023
Adder
0.568
274770LINCOLN ;1U
Adder
10.399
274771LINCOLN ;2U
Adder
10.399
274808UNIV PK N;4U
Adder
6.107
972259AH1-714 GEN
Adder
23.335
274803UNIV PARK;6U
Adder
7.13
24728805RICHG1
Adder
4.62
24728905RICHG2
Adder
4.62
274674JOLIET 9 ;6U
Adder
18.77
274696ROCKY RD ;4P
Adder
13.793
274695ROCKY RD ;2P
Adder
13.475
274693ROCKY RD ;1P
Adder
13.342
274697ROCKY RD ;3P
Adder
3.661
274683WAUKEGAN ;8U
Adder
25.476
274683WAUKEGAN ;8U
Adder
21.475
25194408D.CRK1
Adder
9.122
25194508D.CRK3
Adder
1.705
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.575
23585401KL_K28_T16
Solar/Wind Helper
1.173
203955AF1-039 C O1
Solar/Wind Helper
0.348
944781AF1-143 GEN
Solar/Wind Helper
2.322
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.337
20088926STNY CRK
Solar/Wind Helper
0.773
203940AF1-140 C
Solar/Wind Helper
0.375
20088626ARWF_N39
Solar/Wind Helper
1.151
20303426NA_O38_P22
Solar/Wind Helper
0.944
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.453
238120AE2-309 GEN
Solar/Wind Helper
0.403
203952AE2-129 C
Solar/Wind Helper
0.449
203946AE2-131 C
Solar/Wind Helper
0.45
238217AF1-153 C O1
Solar/Wind Helper
0.224
20398826ARMNA MT
Solar/Wind Helper
1.411
270166AC1-044 GEN3
50/50
18.415
270159DARBY CT4
50/50
13.555
962761AG1-125 GEN
Solar/Wind Harmer
60.17
970149AG2-104 GEN
Solar/Wind Harmer
74.31
970155AG2-107 GEN
Solar/Wind Harmer
26.237
270349AD2-093_GEN
Solar/Wind Harmer
6.312
270223U2-072_GEN1
Solar/Wind Harmer
2.896
270578AF1-285 GEN2
Solar/Wind Harmer
1.771
270391AF1-285 GEN3
Solar/Wind Harmer
1.771
970593AG2-378 GEN
Solar/Wind Harmer
2.904
270462AD2-086
Solar/Wind Harmer
9.839
253343AC1-166 GEN
Solar/Wind Harmer
1.515
253325AC1-069 GEN
Solar/Wind Harmer
1.461
25326309TAIT D
Adder
1.406
960071AF2-298 GEN
Solar/Wind Harmer
6.383
965011AG1-365 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
965651AG1-433 GEN
Solar/Wind Harmer
6.97
970245AG2-165 GEN
Solar/Wind Harmer
22.72
958861AF2-177 GEN
Solar/Wind Harmer
13.896
971995AH1-542 GEN
Solar/Wind Harmer
13.983
945371AF1-202 GEN
Solar/Wind Harmer
8.818
247521TR3_G114
Solar/Wind Harmer
4.233
270246TR4_N_V150
Solar/Wind Harmer
1.071
24721705FLATG2
Adder
25.49
965421AG1-410 GEN
Solar/Wind Harmer
37.691
246936BC-WTG1
Solar/Wind Harmer
4.907
270489AE1-102 GEN1
Solar/Wind Harmer
1.63
247536S-71 GEN
Solar/Wind Harmer
5.049
270005AE1-210 C O1
Solar/Wind Harmer
6.81
965031AG1-367 GEN
Solar/Wind Harmer
12.46
270063AE2-323 C
Solar/Wind Harmer
2.742
24695305TIMB G C
Solar/Wind Harmer
6.843
970825AG2-519 GEN
Solar/Wind Harmer
2.926
270263AC1-001 GEN
Solar/Wind Harmer
1.301
270032AE2-172
Solar/Wind Harmer
5.768
970291AG2-192 GEN
Solar/Wind Harmer
1.611
942081AE2-220 GEN
Solar/Wind Harmer
7.917
270239V3-007_GEN1
Solar/Wind Harmer
2.131
253432AC1-085 GEN2
Solar/Wind Harmer
0.33
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.399
274774LINCOLN ;5U
Adder
10.399
274723RIVER EC ;12
Adder
21.989
274751CRETE EC ;1U
Adder
10.107
274754CRETE EC ;4U
Adder
10.107
274812UNIV PK N;8U
Adder
6.133
274801UNIV PARK;4U
Adder
7.128
274676JOLIET 29;8U
Adder
37.414
274674JOLIET 9 ;6U
Adder
18.77
274732ELWOOD EC;7P
Adder
20.037
274745AC1-111 GEN9
Adder
6.792
274682WAUKEGAN ;7U
Adder
21.737
274828WAUKEGAN ;BP
Adder
13.354
25194608D.CRK4
Adder
1.983
24728605AND G2
Adder
4.594
274822ROCKFORD ;11
Adder
23.501
972235AH1-702 GEN1
Adder
3.016
25196808ZIMRHP
Adder
58.606
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.465
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.036
20089226LOOKOUT
Solar/Wind Helper
0.545
20088826HIGHLAND
Solar/Wind Helper
0.85
20094526CT_V3-030
Solar/Wind Helper
0.448
235054AD2-180 GEN
Solar/Wind Helper
1.575
964201AG1-281 GEN
Solar/Wind Helper
0.458
238117U2-030
Solar/Wind Helper
0.27
235531U2-073 GEN
Solar/Wind Helper
2.559
964391AG1-301 GEN
Solar/Wind Helper
0.448
203954AE2-126 C
Solar/Wind Helper
0.445
23751201ROTHROCK
Solar/Wind Helper
0.656
238206AE2-263_GEN
Solar/Wind Helper
0.861
959471AF2-238 GEN
Solar/Wind Helper
0.441
270156DARBY CT1
50/50
13.775
270157DARBY CT2
50/50
13.741
270158DARBY CT3
50/50
13.521
270036AE2-216 BAT
50/50
9.031
962771AG1-126 GEN
Solar/Wind Harmer
60.17
270284AF1-227 GEN1
Solar/Wind Harmer
9.235
270286AF1-227 GEN2
Solar/Wind Harmer
3.417
270287AF1-227 GEN3
Solar/Wind Harmer
3.417
270459AD2-067 GEN
Solar/Wind Harmer
13.414
961821AG1-024 GEN
Solar/Wind Harmer
13.619
270520AE2-214 GEN
Solar/Wind Harmer
9.509
270054AF2-122 C O1
Solar/Wind Harmer
5.085
253383AE2-342_GEN
Solar/Wind Harmer
1.367
241973AD2-163_GEN1
Solar/Wind Harmer
2.98
943861AF1-054 GEN
Solar/Wind Harmer
5.751
943851AF1-053 GEN
Solar/Wind Harmer
2.779
270578AF1-285 GEN2
Solar/Wind Harmer
0.681
945631AF1-228 GEN
Solar/Wind Harmer
6.816
270302AB2-170 GEN
Solar/Wind Harmer
11.828
270317AD1-130_GEN
Solar/Wind Harmer
4.534
241972AD1-140 GEN
Solar/Wind Harmer
6.086
970689AG2-444 GEN
Solar/Wind Harmer
21.964
270432AC2-029 GEN
Solar/Wind Harmer
9.402
270269AC2-059
Solar/Wind Harmer
12.116
24729505KEY G4
Adder
8.352
270071AF1-092 GEN
Solar/Wind Harmer
19.246
253372AE2-315 SEC3
Adder
2.418
253372AE2-315 SEC3
Adder
2.418
958711AF2-162 GEN
Solar/Wind Harmer
1.29
25306009OHH W.
Adder
3.664
270051AF1-062 GEN
50/50
17.137
270475AD2-096_GEN
50/50
10.101
970153AG2-106 GEN
Solar/Wind Harmer
26.237
961921AG1-034 GEN
Solar/Wind Harmer
20.428
241955AC1-078 GEN
Solar/Wind Harmer
11.216
241974AD2-163_GEN2
Solar/Wind Harmer
2.98
942051AE2-217 GEN
Solar/Wind Harmer
26.699
942871AE2-306 GEN
Solar/Wind Harmer
1.328
270391AF1-285 GEN3
Solar/Wind Harmer
0.681
970605AG2-385 GEN
Solar/Wind Harmer
7.841
270485AE1-090_GEN
Solar/Wind Harmer
0.855
253338AC1-165 GEN
Solar/Wind Harmer
1.515
253333AC1-068 GEN
Solar/Wind Harmer
1.461
960801AF2-371 GEN
Solar/Wind Harmer
3.409
964871AG1-351 GEN
Solar/Wind Harmer
2.354
270273AD2-016 GEN
Solar/Wind Harmer
3.465
944531AF1-118 GEN
Solar/Wind Harmer
45.213
972173AH1-669 GEN
Solar/Wind Harmer
6.446
270043AE2-236 GEN
Solar/Wind Harmer
7.048
959331AF2-224 GEN
Solar/Wind Harmer
12.784
965021AG1-366 GEN
Solar/Wind Harmer
2.973
253303V4-073 C
Solar/Wind Harmer
0.148
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
970513AG2-328 GEN
Solar/Wind Harmer
22.72
970517AG2-330 GEN
Solar/Wind Harmer
20.606
253415AE1-040 GEN
Solar/Wind Harmer
1.432
970349AG2-230 GEN
Solar/Wind Harmer
18.933
270191TR4_S_V150
Solar/Wind Harmer
3.777
270247TR4_N_V136
Solar/Wind Harmer
1.071
24721905FLATG4
Adder
25.49
971617AH1-308 GEN
Solar/Wind Harmer
7.295
270491AE1-102 GEN2
Solar/Wind Harmer
1.63
962031AG1-047 GEN
Solar/Wind Harmer
3.777
957741AF2-068 GEN
Solar/Wind Harmer
18.744
970031AG2-029 GEN
Solar/Wind Harmer
37.389
958821AF2-173 GEN
Solar/Wind Harmer
17.445
270004AE1-209 GEN
Solar/Wind Harmer
6.81
946031AF1-268 GEN
Solar/Wind Harmer
10.33
253406AD2-031_GEN
Solar/Wind Harmer
1.591
970289AG2-191 GEN
Solar/Wind Harmer
0.951
970291AG2-192 GEN
Solar/Wind Harmer
0.865
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.914
247643Z2-116 C
Solar/Wind Harmer
0.086
253316AC1-085 GEN3
Solar/Wind Harmer
10.337
253433AC1-085 GEN1
Solar/Wind Harmer
6.562
274772LINCOLN ;3U
Adder
10.399
274724RIVER EC ;11
Adder
21.733
274752CRETE EC ;2U
Adder
10.107
274753CRETE EC ;3U
Adder
10.107
24642205MAYFLWER
Adder
0.779
274802UNIV PARK;5U
Adder
7.13
972228AH1-698 GEN2
Adder
4.53
274826FISK ;BP
Adder
13.387
274800UNIV PARK;3U
Adder
7.128
972038AH1-567 GEN2
Adder
0.446
274676JOLIET 29;8U
Adder
36.078
274729ELWOOD EC;1P
Adder
20.037
274730ELWOOD EC;6P
Adder
20.037
274734ELWOOD EC;8P
Adder
20.037
274736ELWOOD EC;9P
Adder
20.037
274682WAUKEGAN ;7U
Adder
21.737
25196608WSDLE5
Adder
10.356
25194608D.CRK4
Adder
1.983
24728705AND G3
Adder
9.609
24728505AND G1
Adder
4.594
972236AH1-702 GEN2
Adder
2.622
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.177
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.598
202652Y1-033 WT C
Solar/Wind Helper
0.528
23750701CROSSCHOOL
Solar/Wind Helper
1.128
20089126CSLMN_L13
Solar/Wind Helper
0.559
20089026BF_G21_K23
Solar/Wind Helper
0.443
203818AF1-086 GEN
Solar/Wind Helper
1.599
238118U2-030_1
Solar/Wind Helper
0.27
238127S14_GEN_2
Solar/Wind Helper
0.644
203854AF2-039 C
Solar/Wind Helper
0.301
20334926Z1-069 C
Solar/Wind Helper
1.271
238202AE2-262_GEN
Solar/Wind Helper
0.905
959441AF2-235 GEN
Solar/Wind Helper
0.22
946181AF1-283 GEN
Solar/Wind Harmer
8.323
965101AG1-375 GEN
Solar/Wind Harmer
12.713
253349AC2-067 GEN
Solar/Wind Harmer
6.33
253400AC2-068 GEN
Solar/Wind Harmer
2.546
945581AF1-223 GEN
Solar/Wind Harmer
5.732
963791AG1-232 GEN
Solar/Wind Harmer
17.046
971347AH1-153 GEN
Solar/Wind Harmer
18.933
965051AG1-369 GEN
Solar/Wind Harmer
6.287
965041AG1-368 GEN
Solar/Wind Harmer
12.553
270024AE2-089 GEN
Solar/Wind Harmer
5.889
270340AC2-060 GEN
Solar/Wind Harmer
3.803
957201AF2-014 GEN
Solar/Wind Harmer
5.688
270435AC2-044 GEN
Solar/Wind Harmer
2.508
961761AG1-017 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
6.376
971029AG2-637 GEN
Solar/Wind Harmer
18.648
971673AH1-337 GEN
Solar/Wind Harmer
5.716
970115AG2-085 GEN
Solar/Wind Harmer
4.969
270594AE1-207 GEN
Solar/Wind Harmer
18.228
965461AG1-414 GEN
Solar/Wind Harmer
2.81
970289AG2-191 GEN
Solar/Wind Harmer
2.355
270240V3-007_GEN2
Solar/Wind Harmer
7.662
960681AF2-359 GEN
Solar/Wind Harmer
4.674
274775LINCOLN ;6U
Adder
10.399
274776LINCOLN ;7U
Adder
10.399
274777LINCOLN ;8U
Adder
10.399
274814UNIV PK N;0U
Adder
6.187
274807UNIV PK N;3U
Adder
6.174
274805UNIV PK N;1U
Adder
6.147
274811UNIV PK N;7U
Adder
6.133
972037AH1-567 GEN1
Adder
0.224
972227AH1-698 GEN1
Adder
3.19
274827FISK ;RP
Adder
9.488
274687WILL CNTY;4U
Adder
34.087
274687WILL CNTY;4U
Adder
34.087
274675JOLIET 29;7U
Adder
37.414
274675JOLIET 29;7U
Adder
36.078
274731ELWOOD EC;2P
Adder
20.037
274733ELWOOD EC;3P
Adder
20.037
274735ELWOOD EC;4P
Adder
20.037
274728ELWOOD EC;5P
Adder
20.037
274746AC1-111 G10
Adder
6.792
274744AC1-111 GEN8
Adder
6.792
25196408WSDLE3
Adder
10.661
25196308WSDLE2
Adder
10.568
25196208WSDLE1
Adder
10.541
25196708WSDLE6
Adder
10.515
25196508WSDLE4
Adder
10.25
274823ROCKFORD ;21
Adder
23.331
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.613
20092526R32
Solar/Wind Helper
1.102
203961AE2-224 GEN
Solar/Wind Helper
2.286
20091526CHSTN_FL
Solar/Wind Helper
0.552
20090526Q36
Solar/Wind Helper
0.989
203993AD2-133_GEN1
Solar/Wind Helper
0.989
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.644
941231AE2-117 GEN
Solar/Wind Helper
0.449
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.643
CPLELTFEXP_CPLE->PJM
CLTF
2.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
134.362
LAGNLTFEXP_LAGN->PJM
CLTF
17.971
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.828
TVALTFEXP_TVA->PJM
CLTF
8.763
NYPJM->LTFIMP_NY
CLTF
5.354
LGEELTFEXP_LGEE->PJM
CLTF
7.711
WECLTFEXP_WEC->PJM
CLTF
4.569
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.426
CBM West 1LTFEXP_CBM-W1->PJM
CBM
156.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.576
MECLTFEXP_MEC->PJM
CLTF
18.96
SIGELTFEXP_SIGE->PJM
CLTF
0.586

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.39 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4986.37
MW Contribution:2.9
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
18.405
270120AB2-067 GEN2
50/50
18.405
270160DARBY CT5
50/50
0.736
270161DARBY CT6
50/50
0.726
270466AD2-091
50/50
8.187
270471AD2-092_GEN
Solar/Wind Harmer
6.297
946101AF1-275 GEN
Solar/Wind Harmer
2.366
942861AE2-305 GEN
Solar/Wind Harmer
11.617
270224U2-072_GEN2
Solar/Wind Harmer
2.888
270227U2-072_GEN3
Solar/Wind Harmer
2.888
270228U2-072_GEN4
Solar/Wind Harmer
2.888
270231U2-072_GEN5
Solar/Wind Harmer
2.888
970077AG2-063 GEN
Solar/Wind Harmer
7.818
270518AE2-148 GEN
Solar/Wind Harmer
17.027
964601AG1-323 GEN
Solar/Wind Harmer
4.444
964601AG1-323 GEN
Solar/Wind Harmer
2.067
938701AE1-092 GEN
Solar/Wind Harmer
28.63
253378AE2-206_GEN
Solar/Wind Harmer
4.787
276820AF1-078_GEN
Solar/Wind Harmer
2.127
25326509SID D
Adder
1.715
25326109MON D
Adder
1.7
25322209TAIT E
Adder
12.473
25322209TAIT E
Adder
12.193
970611AG2-400 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
944541AF1-119 GEN
Solar/Wind Harmer
5.325
960971AF2-388 GEN
Solar/Wind Harmer
13.897
970321AG2-212 GEN
Solar/Wind Harmer
22.653
942221AE2-234 GEN
Solar/Wind Harmer
0.922
246938BC-WTG3
Solar/Wind Harmer
4.977
246937BC-WTG2
Solar/Wind Harmer
4.892
253394AE2-221_GEN
Solar/Wind Harmer
5.664
253398AE2-221_GEN2
Solar/Wind Harmer
5.664
270599AE1-208 GEN
Solar/Wind Harmer
10.159
270031AE2-169
Solar/Wind Harmer
10.159
270201AC2-176 GEN
Solar/Wind Harmer
6.404
964611AG1-324 GEN
Solar/Wind Harmer
1.468
964611AG1-324 GEN
Solar/Wind Harmer
0.651
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.413
970885AG2-551 GEN
Solar/Wind Harmer
2.887
970825AG2-519 GEN
Solar/Wind Harmer
13.073
960441AF2-335 GEN
Solar/Wind Harmer
12.384
270383AD1-128 GEN
Solar/Wind Harmer
7.545
24379505HDWTR1G C
Solar/Wind Harmer
9.762
270209AC1-174_GEN
Solar/Wind Harmer
6.889
926881AC1-175 GEN
Solar/Wind Harmer
6.889
965681AG1-436 GEN
Solar/Wind Harmer
15.418
965791AG1-447 GEN
Solar/Wind Harmer
7.888
270216AD2-079_GEN
Solar/Wind Harmer
0.746
247620Y3-023
Adder
0.566
274770LINCOLN ;1U
Adder
10.368
274771LINCOLN ;2U
Adder
10.368
274808UNIV PK N;4U
Adder
6.088
972259AH1-714 GEN
Adder
23.265
274803UNIV PARK;6U
Adder
7.109
24728805RICHG1
Adder
4.605
24728905RICHG2
Adder
4.605
274674JOLIET 9 ;6U
Adder
18.713
274696ROCKY RD ;4P
Adder
13.751
274695ROCKY RD ;2P
Adder
13.434
274693ROCKY RD ;1P
Adder
13.302
274697ROCKY RD ;3P
Adder
3.649
274683WAUKEGAN ;8U
Adder
25.399
274683WAUKEGAN ;8U
Adder
21.41
25194408D.CRK1
Adder
9.091
25194508D.CRK3
Adder
1.7
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.569
23585401KL_K28_T16
Solar/Wind Helper
1.169
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.315
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.771
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.148
20303426NA_O38_P22
Solar/Wind Helper
0.941
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.448
203946AE2-131 C
Solar/Wind Helper
0.449
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.408
253317AC1-085 GEN4
Solar/Wind Harmer
9.261
270166AC1-044 GEN3
50/50
18.405
270159DARBY CT4
50/50
13.513
962761AG1-125 GEN
Solar/Wind Harmer
60.041
970149AG2-104 GEN
Solar/Wind Harmer
74.151
970155AG2-107 GEN
Solar/Wind Harmer
26.181
270349AD2-093_GEN
Solar/Wind Harmer
6.297
270223U2-072_GEN1
Solar/Wind Harmer
2.888
270578AF1-285 GEN2
Solar/Wind Harmer
1.766
270391AF1-285 GEN3
Solar/Wind Harmer
1.766
970593AG2-378 GEN
Solar/Wind Harmer
2.895
270462AD2-086
Solar/Wind Harmer
9.812
253343AC1-166 GEN
Solar/Wind Harmer
1.51
253325AC1-069 GEN
Solar/Wind Harmer
1.456
25326309TAIT D
Adder
1.402
960071AF2-298 GEN
Solar/Wind Harmer
6.362
965011AG1-365 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
965651AG1-433 GEN
Solar/Wind Harmer
6.949
970245AG2-165 GEN
Solar/Wind Harmer
22.653
958861AF2-177 GEN
Solar/Wind Harmer
13.854
971995AH1-542 GEN
Solar/Wind Harmer
13.936
945371AF1-202 GEN
Solar/Wind Harmer
8.791
247521TR3_G114
Solar/Wind Harmer
4.221
270246TR4_N_V150
Solar/Wind Harmer
1.068
24721705FLATG2
Adder
25.406
965421AG1-410 GEN
Solar/Wind Harmer
37.577
246936BC-WTG1
Solar/Wind Harmer
4.892
270051AF1-062 GEN
50/50
17.095
270475AD2-096_GEN
50/50
10.077
970153AG2-106 GEN
Solar/Wind Harmer
26.181
961921AG1-034 GEN
Solar/Wind Harmer
20.368
241955AC1-078 GEN
Solar/Wind Harmer
11.182
241974AD2-163_GEN2
Solar/Wind Harmer
2.972
942051AE2-217 GEN
Solar/Wind Harmer
26.62
942871AE2-306 GEN
Solar/Wind Harmer
1.325
270391AF1-285 GEN3
Solar/Wind Harmer
0.679
970605AG2-385 GEN
Solar/Wind Harmer
7.818
270485AE1-090_GEN
Solar/Wind Harmer
0.853
253338AC1-165 GEN
Solar/Wind Harmer
1.51
253333AC1-068 GEN
Solar/Wind Harmer
1.456
960801AF2-371 GEN
Solar/Wind Harmer
3.397
964871AG1-351 GEN
Solar/Wind Harmer
2.345
270273AD2-016 GEN
Solar/Wind Harmer
3.452
944531AF1-118 GEN
Solar/Wind Harmer
45.079
972173AH1-669 GEN
Solar/Wind Harmer
6.423
270043AE2-236 GEN
Solar/Wind Harmer
7.027
959331AF2-224 GEN
Solar/Wind Harmer
12.746
965021AG1-366 GEN
Solar/Wind Harmer
2.964
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
970513AG2-328 GEN
Solar/Wind Harmer
22.653
970517AG2-330 GEN
Solar/Wind Harmer
20.546
253415AE1-040 GEN
Solar/Wind Harmer
1.427
970349AG2-230 GEN
Solar/Wind Harmer
18.878
270191TR4_S_V150
Solar/Wind Harmer
3.765
270247TR4_N_V136
Solar/Wind Harmer
1.068
24721905FLATG4
Adder
25.406
971617AH1-308 GEN
Solar/Wind Harmer
7.273
270491AE1-102 GEN2
Solar/Wind Harmer
1.625
962031AG1-047 GEN
Solar/Wind Harmer
3.765
957741AF2-068 GEN
Solar/Wind Harmer
18.686
970031AG2-029 GEN
Solar/Wind Harmer
37.277
958821AF2-173 GEN
Solar/Wind Harmer
17.391
270004AE1-209 GEN
Solar/Wind Harmer
6.789
946031AF1-268 GEN
Solar/Wind Harmer
10.298
253406AD2-031_GEN
Solar/Wind Harmer
1.585
970289AG2-191 GEN
Solar/Wind Harmer
0.948
970291AG2-192 GEN
Solar/Wind Harmer
0.862
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.893
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.368
274724RIVER EC ;11
Adder
21.668
274752CRETE EC ;2U
Adder
10.077
274753CRETE EC ;3U
Adder
10.077
24642205MAYFLWER
Adder
0.777
274802UNIV PARK;5U
Adder
7.109
972228AH1-698 GEN2
Adder
4.517
274826FISK ;BP
Adder
13.347
274800UNIV PARK;3U
Adder
7.107
972038AH1-567 GEN2
Adder
0.445
274676JOLIET 29;8U
Adder
35.969
274729ELWOOD EC;1P
Adder
19.977
274730ELWOOD EC;6P
Adder
19.977
274734ELWOOD EC;8P
Adder
19.977
274736ELWOOD EC;9P
Adder
19.977
274682WAUKEGAN ;7U
Adder
21.671
25196608WSDLE5
Adder
10.321
25194608D.CRK4
Adder
1.976
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.58
972236AH1-702 GEN2
Adder
2.615
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.583
202652Y1-033 WT C
Solar/Wind Helper
0.526
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089026BF_G21_K23
Solar/Wind Helper
0.442
23750701CROSSCHOOL
Solar/Wind Helper
1.124
203818AF1-086 GEN
Solar/Wind Helper
1.596
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.641
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.269
238202AE2-262_GEN
Solar/Wind Helper
0.903
253316AC1-085 GEN3
Solar/Wind Harmer
9.261
253433AC1-085 GEN1
Solar/Wind Harmer
5.879
270156DARBY CT1
50/50
13.732
270157DARBY CT2
50/50
13.698
270158DARBY CT3
50/50
13.479
270036AE2-216 BAT
50/50
9.005
962771AG1-126 GEN
Solar/Wind Harmer
60.041
270284AF1-227 GEN1
Solar/Wind Harmer
9.212
270286AF1-227 GEN2
Solar/Wind Harmer
3.408
270287AF1-227 GEN3
Solar/Wind Harmer
3.408
270459AD2-067 GEN
Solar/Wind Harmer
13.375
961821AG1-024 GEN
Solar/Wind Harmer
13.579
270520AE2-214 GEN
Solar/Wind Harmer
9.481
270054AF2-122 C O1
Solar/Wind Harmer
5.069
253383AE2-342_GEN
Solar/Wind Harmer
1.364
241973AD2-163_GEN1
Solar/Wind Harmer
2.972
943861AF1-054 GEN
Solar/Wind Harmer
5.734
943851AF1-053 GEN
Solar/Wind Harmer
2.771
270578AF1-285 GEN2
Solar/Wind Harmer
0.679
945631AF1-228 GEN
Solar/Wind Harmer
6.795
270302AB2-170 GEN
Solar/Wind Harmer
11.795
270317AD1-130_GEN
Solar/Wind Harmer
4.522
241972AD1-140 GEN
Solar/Wind Harmer
6.067
970689AG2-444 GEN
Solar/Wind Harmer
21.887
270432AC2-029 GEN
Solar/Wind Harmer
9.37
270269AC2-059
Solar/Wind Harmer
12.072
24729505KEY G4
Adder
8.327
270071AF1-092 GEN
Solar/Wind Harmer
19.189
253372AE2-315 SEC3
Adder
2.411
253372AE2-315 SEC3
Adder
2.411
958711AF2-162 GEN
Solar/Wind Harmer
1.286
965101AG1-375 GEN
Solar/Wind Harmer
12.675
25306009OHH W.
Adder
3.652
253349AC2-067 GEN
Solar/Wind Harmer
6.31
253400AC2-068 GEN
Solar/Wind Harmer
2.537
945581AF1-223 GEN
Solar/Wind Harmer
5.714
963791AG1-232 GEN
Solar/Wind Harmer
16.994
971347AH1-153 GEN
Solar/Wind Harmer
18.878
965051AG1-369 GEN
Solar/Wind Harmer
6.268
965041AG1-368 GEN
Solar/Wind Harmer
12.515
270024AE2-089 GEN
Solar/Wind Harmer
5.871
957201AF2-014 GEN
Solar/Wind Harmer
5.67
270435AC2-044 GEN
Solar/Wind Harmer
2.5
270340AC2-060 GEN
Solar/Wind Harmer
3.789
961761AG1-017 GEN
Solar/Wind Harmer
0.533
270543AE2-219 C
Solar/Wind Harmer
6.356
971029AG2-637 GEN
Solar/Wind Harmer
18.589
270489AE1-102 GEN1
Solar/Wind Harmer
1.625
247536S-71 GEN
Solar/Wind Harmer
5.033
270005AE1-210 C O1
Solar/Wind Harmer
6.789
965031AG1-367 GEN
Solar/Wind Harmer
12.422
270063AE2-323 C
Solar/Wind Harmer
2.733
24695305TIMB G C
Solar/Wind Harmer
6.822
970825AG2-519 GEN
Solar/Wind Harmer
2.917
270263AC1-001 GEN
Solar/Wind Harmer
1.296
270032AE2-172
Solar/Wind Harmer
5.75
970291AG2-192 GEN
Solar/Wind Harmer
1.606
942081AE2-220 GEN
Solar/Wind Harmer
7.893
270239V3-007_GEN1
Solar/Wind Harmer
2.124
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.368
274774LINCOLN ;5U
Adder
10.368
274723RIVER EC ;12
Adder
21.923
274751CRETE EC ;1U
Adder
10.077
274754CRETE EC ;4U
Adder
10.077
274812UNIV PK N;8U
Adder
6.115
274801UNIV PARK;4U
Adder
7.107
274676JOLIET 29;8U
Adder
37.301
274674JOLIET 9 ;6U
Adder
18.713
274732ELWOOD EC;7P
Adder
19.977
274745AC1-111 GEN9
Adder
6.771
274682WAUKEGAN ;7U
Adder
21.671
274828WAUKEGAN ;BP
Adder
13.314
25194608D.CRK4
Adder
1.976
24728605AND G2
Adder
4.58
274822ROCKFORD ;11
Adder
23.43
972235AH1-702 GEN1
Adder
3.007
25196808ZIMRHP
Adder
58.404
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.464
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.029
20089226LOOKOUT
Solar/Wind Helper
0.543
20088826HIGHLAND
Solar/Wind Helper
0.848
20094526CT_V3-030
Solar/Wind Helper
0.447
235054AD2-180 GEN
Solar/Wind Helper
1.569
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.549
964391AG1-301 GEN
Solar/Wind Helper
0.447
203954AE2-126 C
Solar/Wind Helper
0.444
23751201ROTHROCK
Solar/Wind Helper
0.653
238206AE2-263_GEN
Solar/Wind Helper
0.859
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
971673AH1-337 GEN
Solar/Wind Harmer
5.698
970115AG2-085 GEN
Solar/Wind Harmer
4.954
270594AE1-207 GEN
Solar/Wind Harmer
18.171
965461AG1-414 GEN
Solar/Wind Harmer
2.801
970289AG2-191 GEN
Solar/Wind Harmer
2.347
270240V3-007_GEN2
Solar/Wind Harmer
7.638
960681AF2-359 GEN
Solar/Wind Harmer
4.66
971771AH1-392 GEN
Solar/Wind Harmer
11.073
274775LINCOLN ;6U
Adder
10.368
274776LINCOLN ;7U
Adder
10.368
274777LINCOLN ;8U
Adder
10.368
274814UNIV PK N;0U
Adder
6.169
274807UNIV PK N;3U
Adder
6.155
274805UNIV PK N;1U
Adder
6.128
274811UNIV PK N;7U
Adder
6.115
972227AH1-698 GEN1
Adder
3.18
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.459
274687WILL CNTY;4U
Adder
33.985
274687WILL CNTY;4U
Adder
33.985
274675JOLIET 29;7U
Adder
37.302
274675JOLIET 29;7U
Adder
35.969
274731ELWOOD EC;2P
Adder
19.977
274733ELWOOD EC;3P
Adder
19.977
274735ELWOOD EC;4P
Adder
19.977
274728ELWOOD EC;5P
Adder
19.977
274746AC1-111 G10
Adder
6.771
274744AC1-111 GEN8
Adder
6.771
25196408WSDLE3
Adder
10.624
25196308WSDLE2
Adder
10.532
25196208WSDLE1
Adder
10.505
25196708WSDLE6
Adder
10.479
25196508WSDLE4
Adder
10.215
274823ROCKFORD ;21
Adder
23.26
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.611
20092526R32
Solar/Wind Helper
1.1
203961AE2-224 GEN
Solar/Wind Helper
2.28
20091526CHSTN_FL
Solar/Wind Helper
0.551
20090526Q36
Solar/Wind Helper
0.986
203993AD2-133_GEN1
Solar/Wind Helper
0.986
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.641
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.64
CPLELTFEXP_CPLE->PJM
CLTF
2.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.928
LAGNLTFEXP_LAGN->PJM
CLTF
17.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.787
TVALTFEXP_TVA->PJM
CLTF
8.734
NYPJM->LTFIMP_NY
CLTF
5.339
LGEELTFEXP_LGEE->PJM
CLTF
7.685
WECLTFEXP_WEC->PJM
CLTF
4.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.46
MECLTFEXP_MEC->PJM
CLTF
18.901
SIGELTFEXP_SIGE->PJM
CLTF
0.584

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4982.82
MW Contribution:2.89
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
6.29
946101AF1-275 GEN
Solar/Wind Harmer
2.363
942861AE2-305 GEN
Solar/Wind Harmer
11.602
270224U2-072_GEN2
Solar/Wind Harmer
2.884
270227U2-072_GEN3
Solar/Wind Harmer
2.884
270228U2-072_GEN4
Solar/Wind Harmer
2.884
270231U2-072_GEN5
Solar/Wind Harmer
2.884
970077AG2-063 GEN
Solar/Wind Harmer
7.807
270518AE2-148 GEN
Solar/Wind Harmer
17.003
964601AG1-323 GEN
Solar/Wind Harmer
4.438
964601AG1-323 GEN
Solar/Wind Harmer
2.064
938701AE1-092 GEN
Solar/Wind Harmer
28.592
253378AE2-206_GEN
Solar/Wind Harmer
4.781
276820AF1-078_GEN
Solar/Wind Harmer
2.124
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
26.156
961921AG1-034 GEN
Solar/Wind Harmer
20.342
241955AC1-078 GEN
Solar/Wind Harmer
11.167
241974AD2-163_GEN2
Solar/Wind Harmer
2.968
942051AE2-217 GEN
Solar/Wind Harmer
26.585
942871AE2-306 GEN
Solar/Wind Harmer
1.323
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
7.807
270485AE1-090_GEN
Solar/Wind Harmer
0.852
253338AC1-165 GEN
Solar/Wind Harmer
1.508
253333AC1-068 GEN
Solar/Wind Harmer
1.454
960801AF2-371 GEN
Solar/Wind Harmer
3.391
964871AG1-351 GEN
Solar/Wind Harmer
2.342
270273AD2-016 GEN
Solar/Wind Harmer
3.447
944531AF1-118 GEN
Solar/Wind Harmer
45.02
972173AH1-669 GEN
Solar/Wind Harmer
6.413
270043AE2-236 GEN
Solar/Wind Harmer
7.018
959331AF2-224 GEN
Solar/Wind Harmer
12.73
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
22.623
970517AG2-330 GEN
Solar/Wind Harmer
20.519
253415AE1-040 GEN
Solar/Wind Harmer
1.424
970349AG2-230 GEN
Solar/Wind Harmer
18.853
270191TR4_S_V150
Solar/Wind Harmer
3.76
270247TR4_N_V136
Solar/Wind Harmer
1.066
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.623
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
5.318
960971AF2-388 GEN
Solar/Wind Harmer
13.879
970321AG2-212 GEN
Solar/Wind Harmer
22.623
942221AE2-234 GEN
Solar/Wind Harmer
0.921
246938BC-WTG3
Solar/Wind Harmer
4.97
246937BC-WTG2
Solar/Wind Harmer
4.886
270599AE1-208 GEN
Solar/Wind Harmer
10.145
270031AE2-169
Solar/Wind Harmer
10.145
253394AE2-221_GEN
Solar/Wind Harmer
5.655
253398AE2-221_GEN2
Solar/Wind Harmer
5.655
270201AC2-176 GEN
Solar/Wind Harmer
6.395
964611AG1-324 GEN
Solar/Wind Harmer
1.466
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.396
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
13.055
960441AF2-335 GEN
Solar/Wind Harmer
12.367
270383AD1-128 GEN
Solar/Wind Harmer
7.535
24379505HDWTR1G C
Solar/Wind Harmer
9.748
270209AC1-174_GEN
Solar/Wind Harmer
6.88
926881AC1-175 GEN
Solar/Wind Harmer
6.88
965681AG1-436 GEN
Solar/Wind Harmer
15.398
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.745
247620Y3-023
Adder
0.565
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
274808UNIV PK N;4U
Adder
6.08
972259AH1-714 GEN
Adder
23.234
274803UNIV PARK;6U
Adder
7.1
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
253317AC1-085 GEN4
Solar/Wind Harmer
9.247
962031AG1-047 GEN
Solar/Wind Harmer
3.76
957741AF2-068 GEN
Solar/Wind Harmer
18.66
970031AG2-029 GEN
Solar/Wind Harmer
37.228
958821AF2-173 GEN
Solar/Wind Harmer
17.367
270004AE1-209 GEN
Solar/Wind Harmer
6.779
946031AF1-268 GEN
Solar/Wind Harmer
10.283
253406AD2-031_GEN
Solar/Wind Harmer
1.583
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.883
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.354
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
25194608D.CRK4
Adder
1.973
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
253316AC1-085 GEN3
Solar/Wind Harmer
9.247
253433AC1-085 GEN1
Solar/Wind Harmer
5.87
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
59.984
970149AG2-104 GEN
Solar/Wind Harmer
74.081
970155AG2-107 GEN
Solar/Wind Harmer
26.156
270349AD2-093_GEN
Solar/Wind Harmer
6.29
270223U2-072_GEN1
Solar/Wind Harmer
2.884
270578AF1-285 GEN2
Solar/Wind Harmer
1.764
270391AF1-285 GEN3
Solar/Wind Harmer
1.764
970593AG2-378 GEN
Solar/Wind Harmer
2.892
270462AD2-086
Solar/Wind Harmer
9.8
253343AC1-166 GEN
Solar/Wind Harmer
1.508
253325AC1-069 GEN
Solar/Wind Harmer
1.454
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
6.353
965011AG1-365 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
6.939
970245AG2-165 GEN
Solar/Wind Harmer
22.623
958861AF2-177 GEN
Solar/Wind Harmer
13.835
971995AH1-542 GEN
Solar/Wind Harmer
13.916
945371AF1-202 GEN
Solar/Wind Harmer
8.779
247521TR3_G114
Solar/Wind Harmer
4.215
270246TR4_N_V150
Solar/Wind Harmer
1.066
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
37.527
246936BC-WTG1
Solar/Wind Harmer
4.886
270489AE1-102 GEN1
Solar/Wind Harmer
1.623
247536S-71 GEN
Solar/Wind Harmer
5.026
270005AE1-210 C O1
Solar/Wind Harmer
6.779
965031AG1-367 GEN
Solar/Wind Harmer
12.405
270063AE2-323 C
Solar/Wind Harmer
2.73
24695305TIMB G C
Solar/Wind Harmer
6.813
970825AG2-519 GEN
Solar/Wind Harmer
2.913
270263AC1-001 GEN
Solar/Wind Harmer
1.294
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.604
942081AE2-220 GEN
Solar/Wind Harmer
7.882
270239V3-007_GEN1
Solar/Wind Harmer
2.121
24639705ELKHART HY
Adder
0.188
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
274812UNIV PK N;8U
Adder
6.107
274801UNIV PARK;4U
Adder
7.097
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274745AC1-111 GEN9
Adder
6.762
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
25194608D.CRK4
Adder
1.973
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
59.984
270284AF1-227 GEN1
Solar/Wind Harmer
9.201
270286AF1-227 GEN2
Solar/Wind Harmer
3.404
270287AF1-227 GEN3
Solar/Wind Harmer
3.404
270459AD2-067 GEN
Solar/Wind Harmer
13.358
961821AG1-024 GEN
Solar/Wind Harmer
13.561
270520AE2-214 GEN
Solar/Wind Harmer
9.469
270054AF2-122 C O1
Solar/Wind Harmer
5.062
253383AE2-342_GEN
Solar/Wind Harmer
1.362
241973AD2-163_GEN1
Solar/Wind Harmer
2.968
943861AF1-054 GEN
Solar/Wind Harmer
5.727
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
6.786
270302AB2-170 GEN
Solar/Wind Harmer
11.78
270317AD1-130_GEN
Solar/Wind Harmer
4.516
241972AD1-140 GEN
Solar/Wind Harmer
6.058
970689AG2-444 GEN
Solar/Wind Harmer
21.853
270432AC2-029 GEN
Solar/Wind Harmer
9.355
270269AC2-059
Solar/Wind Harmer
12.053
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
19.164
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
958711AF2-162 GEN
Solar/Wind Harmer
1.285
965101AG1-375 GEN
Solar/Wind Harmer
12.658
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
6.301
253400AC2-068 GEN
Solar/Wind Harmer
2.534
945581AF1-223 GEN
Solar/Wind Harmer
5.707
963791AG1-232 GEN
Solar/Wind Harmer
16.971
971347AH1-153 GEN
Solar/Wind Harmer
18.853
965051AG1-369 GEN
Solar/Wind Harmer
6.259
965041AG1-368 GEN
Solar/Wind Harmer
12.498
270024AE2-089 GEN
Solar/Wind Harmer
5.863
957201AF2-014 GEN
Solar/Wind Harmer
5.663
270435AC2-044 GEN
Solar/Wind Harmer
2.497
270340AC2-060 GEN
Solar/Wind Harmer
3.783
961761AG1-017 GEN
Solar/Wind Harmer
0.532
270543AE2-219 C
Solar/Wind Harmer
6.347
971029AG2-637 GEN
Solar/Wind Harmer
18.562
971673AH1-337 GEN
Solar/Wind Harmer
5.69
970115AG2-085 GEN
Solar/Wind Harmer
4.947
270594AE1-207 GEN
Solar/Wind Harmer
18.147
965461AG1-414 GEN
Solar/Wind Harmer
2.797
970289AG2-191 GEN
Solar/Wind Harmer
2.344
270240V3-007_GEN2
Solar/Wind Harmer
7.627
960681AF2-359 GEN
Solar/Wind Harmer
4.654
971771AH1-392 GEN
Solar/Wind Harmer
11.059
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:2.27
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.38
241972AD1-140 GEN
Solar/Wind Harmer
1.032
970689AG2-444 GEN
Solar/Wind Harmer
19.097
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
965101AG1-375 GEN
Solar/Wind Harmer
8.831
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
2.778
253400AC2-068 GEN
Solar/Wind Harmer
1.117
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
11.841
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
965041AG1-368 GEN
Solar/Wind Harmer
8.719
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
12.951
971673AH1-337 GEN
Solar/Wind Harmer
5.609
970115AG2-085 GEN
Solar/Wind Harmer
3.451
270594AE1-207 GEN
Solar/Wind Harmer
9.648
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270240V3-007_GEN2
Solar/Wind Harmer
0.003
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
247607V1-011 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
276882AE2-255 GEN
Solar/Wind Harmer
0.979
970169AG2-114 GEN
Solar/Wind Harmer
8.358
971177AH1-047 GEN
Solar/Wind Harmer
5.154
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
963841AG1-237 GEN
Solar/Wind Harmer
3.615
971171AH1-044 GEN
Solar/Wind Harmer
16.66
926823AC1-168 GEN
Solar/Wind Harmer
1.415
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
50.586
970149AG2-104 GEN
Solar/Wind Harmer
54.635
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
270462AD2-086
Solar/Wind Harmer
0.021
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.015
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
4.426
965011AG1-365 GEN
Solar/Wind Harmer
8.881
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
970245AG2-165 GEN
Solar/Wind Harmer
3.83
958861AF2-177 GEN
Solar/Wind Harmer
3.827
971995AH1-542 GEN
Solar/Wind Harmer
3.236
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
247536S-71 GEN
Solar/Wind Harmer
0.349
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.654
270063AE2-323 C
Solar/Wind Harmer
0.007
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270263AC1-001 GEN
Solar/Wind Harmer
0.865
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.119
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
276903AD2-071 C
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
970373AG2-245 GEN
Solar/Wind Harmer
17.958
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
276164X3-005 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.064
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
274801UNIV PARK;4U
Adder
7.097
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
274745AC1-111 GEN9
Adder
6.762
24791305MDL-5G
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
939401AE1-172 GEN
Solar/Wind Harmer
6.298
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
962781AG1-127 GEN
Solar/Wind Harmer
7.975
971997AH1-543 GEN
Solar/Wind Harmer
4.396
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.005
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.15
957471AF2-041 GEN
Solar/Wind Harmer
24.989
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
970569AG2-363 GEN
Solar/Wind Harmer
24.96
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
963741AG1-226 GEN
Solar/Wind Harmer
19.652
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
32.303
961921AG1-034 GEN
Solar/Wind Harmer
9.935
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
270485AE1-090_GEN
Solar/Wind Harmer
0.001
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
972173AH1-669 GEN
Solar/Wind Harmer
4.474
270043AE2-236 GEN
Solar/Wind Harmer
5.712
959331AF2-224 GEN
Solar/Wind Harmer
6.217
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
970191AG2-125 GEN
Solar/Wind Harmer
2.269
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.056
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
8.226
253406AD2-031_GEN
Solar/Wind Harmer
0.643
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.138
274772LINCOLN ;3U
Adder
10.354
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276806AD2-047 C O1
Solar/Wind Harmer
4.815
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
276897AD1-100 C
Solar/Wind Harmer
0.011
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
270356AE2-297 GEN
Solar/Wind Harmer
0.011
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
276805AD2-038 GEN
Solar/Wind Harmer
0.002
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.307
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
0.009
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970077AG2-063 GEN
Solar/Wind Harmer
5.8
270518AE2-148 GEN
Solar/Wind Harmer
0.847
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
971655AH1-328 GEN
Solar/Wind Harmer
3.428
253378AE2-206_GEN
Solar/Wind Harmer
0.005
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970627AG2-408 GEN
Solar/Wind Harmer
2.664
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
0.594
960971AF2-388 GEN
Solar/Wind Harmer
5.197
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
270599AE1-208 GEN
Solar/Wind Harmer
7.961
270031AE2-169
Solar/Wind Harmer
4.777
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
8.648
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
9.566
960441AF2-335 GEN
Solar/Wind Harmer
8.628
971613AH1-306 GEN
Solar/Wind Harmer
4.135
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
10.743
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
274887GEN-1.85
Solar/Wind Harmer
0.224
276843GEN-1.7
Solar/Wind Harmer
0.275
972259AH1-714 GEN
Adder
23.234
958011AF2-095 GEN
Solar/Wind Harmer
12.235
274803UNIV PARK;6U
Adder
7.1
957891AF2-083 GEN
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
971573AH1-285 GEN
Solar/Wind Harmer
1.571
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
962691AG1-118 GEN
Solar/Wind Harmer
25.162
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
971335AH1-147 GEN
Solar/Wind Harmer
16.689
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
970819AG2-516 GEN
Solar/Wind Harmer
7.858
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1558_05BAKER 765_Q_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2370.07
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.206
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.411
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.778
252524AE2-267 GEN
Solar/Wind Harmer
1.706
25196408WSDLE3
Adder
9.541
25196308WSDLE2
Adder
9.458
25196208WSDLE1
Adder
9.434
25196708WSDLE6
Adder
9.41
25196508WSDLE4
Adder
9.173
25196108MFTGT2
Adder
1.578
25196108MFTGT2
Adder
1.465
270367AC2-061_GEN
Solar/Wind Harmer
3.016
972163AH1-664 GEN
Solar/Wind Harmer
9.479
972165AH1-665 GEN
Solar/Wind Harmer
7.583
270269AC2-059
Solar/Wind Harmer
8.741
270340AC2-060 GEN
Solar/Wind Harmer
2.826
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
944031AF1-071 GEN
Solar/Wind Harmer
0.863
253372AE2-315 SEC3
Adder
1.627
253372AE2-315 SEC3
Adder
1.627
25306009OHH W.
Adder
2.431
970689AG2-444 GEN
Solar/Wind Harmer
13.51
253349AC2-067 GEN
Solar/Wind Harmer
4.095
253400AC2-068 GEN
Solar/Wind Harmer
1.647
3429211JKCT 2G
Adder
8.934
270432AC2-029 GEN
Solar/Wind Harmer
5.224
971673AH1-337 GEN
Solar/Wind Harmer
3.327
270240V3-007_GEN2
Solar/Wind Harmer
4.43
971029AG2-637 GEN
Solar/Wind Harmer
10.703
241972AD1-140 GEN
Solar/Wind Harmer
3.161
270543AE2-219 C
Solar/Wind Harmer
3.509
970455AG2-298 GEN
Solar/Wind Harmer
3.965
339211AE2-254 GEN
Solar/Wind Harmer
0.992
970115AG2-085 GEN
Solar/Wind Harmer
2.587
24725505WLD G2 C
Solar/Wind Harmer
2.527
24699105WLD G1 C
Solar/Wind Harmer
2.497
961761AG1-017 GEN
Solar/Wind Harmer
0.268
270594AE1-207 GEN
Solar/Wind Harmer
8.981
945581AF1-223 GEN
Solar/Wind Harmer
2.744
965461AG1-414 GEN
Solar/Wind Harmer
1.353
970289AG2-191 GEN
Solar/Wind Harmer
1.134
965101AG1-375 GEN
Solar/Wind Harmer
5.827
270024AE2-089 GEN
Solar/Wind Harmer
2.681
958711AF2-162 GEN
Solar/Wind Harmer
0.578
965401AG1-405 GEN
Solar/Wind Harmer
3.127
965411AG1-406 GEN
Solar/Wind Harmer
1.403
270156DARBY CT1
Adder
4.854
270157DARBY CT2
Adder
4.842
270158DARBY CT3
Adder
4.765
972203AH1-686 GEN
Adder
1.236
24729505KEY G4
Adder
3.472
963841AG1-237 GEN
Solar/Wind Harmer
5.739
945631AF1-228 GEN
Solar/Wind Harmer
2.433
24386205FR-12G C
Solar/Wind Harmer
2.21
24386405FR-21G C
Solar/Wind Harmer
2.218
24386605FR-22G C
Solar/Wind Harmer
2.218
24387005FR-3G C
Solar/Wind Harmer
2.04
24690905MDL-1G C
Solar/Wind Harmer
4.036
270180AB1-006 GEN1
Solar/Wind Harmer
3.615
274731ELWOOD EC;2P
Adder
7.226
274733ELWOOD EC;3P
Adder
7.226
274735ELWOOD EC;4P
Adder
7.226
274728ELWOOD EC;5P
Adder
7.225
972227AH1-698 GEN1
Adder
1.146
274675JOLIET 29;7U
Adder
13.447
274675JOLIET 29;7U
Adder
12.966
274687WILL CNTY;4U
Adder
12.245
274687WILL CNTY;4U
Adder
12.245
972037AH1-567 GEN1
Adder
0.08
274746AC1-111 G10
Adder
2.448
274744AC1-111 GEN8
Adder
2.448
274827FISK ;RP
Adder
3.396
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
946581AF1-322 GEN
Solar/Wind Harmer
1.964
24803006KYGER 3HP
50/50
4.182
24802806KYGER 2HP
50/50
4.157
24802906KYGER 2LP
50/50
2.444
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.907
252519AF1-045_GEN
Solar/Wind Harmer
6.804
252516AE2-318_GEN
Solar/Wind Harmer
5.19
25194408D.CRK1
Adder
8.18
25194508D.CRK3
Adder
1.529
253317AC1-085 GEN4
Solar/Wind Harmer
8.99
253394AE2-221_GEN
Solar/Wind Harmer
4.598
253398AE2-221_GEN2
Solar/Wind Harmer
4.598
270186AC1-089 GEN
Solar/Wind Harmer
5.704
962581AG1-107 GEN
Solar/Wind Harmer
4.651
961491AF2-440 GEN
Solar/Wind Harmer
1.933
970235AG2-159 GEN
Solar/Wind Harmer
3.657
970235AG2-159 GEN
Solar/Wind Harmer
2.233
339221AD2-048_GEN
Solar/Wind Harmer
1.371
972043AH1-570 GEN
Solar/Wind Harmer
2.168
972045AH1-571 GEN
Solar/Wind Harmer
1.734
253370AE2-315 SEC1
Adder
1.72
971125AH1-004 GEN
Solar/Wind Harmer
3.367
970107AG2-081 GEN
Solar/Wind Harmer
2.525
25322209TAIT E
Adder
8.1
25322209TAIT E
Adder
7.918
25326109MON D
Adder
1.066
24728805RICHG1
Adder
2.989
24728905RICHG2
Adder
2.989
942891AE2-308 GEN
Solar/Wind Harmer
7.489
24379505HDWTR1G C
Solar/Wind Harmer
5.662
270209AC1-174_GEN
Solar/Wind Harmer
3.996
926881AC1-175 GEN
Solar/Wind Harmer
3.996
270383AD1-128 GEN
Solar/Wind Harmer
4.312
960161AF2-307 GEN
Solar/Wind Harmer
4.476
970883AG2-550 GEN
Solar/Wind Harmer
6.854
970885AG2-551 GEN
Solar/Wind Harmer
1.594
970825AG2-519 GEN
Solar/Wind Harmer
6.864
960441AF2-335 GEN
Solar/Wind Harmer
6.467
964571AG1-320 GEN
Solar/Wind Harmer
5.282
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.745
964611AG1-324 GEN
Solar/Wind Harmer
0.331
970239AG2-162 GEN
Solar/Wind Harmer
6.902
270201AC2-176 GEN
Solar/Wind Harmer
3.22
970653AG2-424 GEN
Solar/Wind Harmer
2.961
970653AG2-424 GEN
Solar/Wind Harmer
1.071
270518AE2-148 GEN
Solar/Wind Harmer
7.398
270599AE1-208 GEN
Solar/Wind Harmer
4.966
270031AE2-169
Solar/Wind Harmer
4.966
270444AC2-157 GEN1
Solar/Wind Harmer
3.313
25326509SID D
Adder
0.762
944541AF1-119 GEN
Solar/Wind Harmer
2.391
960971AF2-388 GEN
Solar/Wind Harmer
6.241
945391AF1-204 GEN
Solar/Wind Harmer
7.862
971081AG2-670 GEN
Solar/Wind Harmer
4.133
942221AE2-234 GEN
Solar/Wind Harmer
0.395
253378AE2-206_GEN
Solar/Wind Harmer
1.933
276820AF1-078_GEN
Solar/Wind Harmer
0.858
970241AG2-163 GEN
Solar/Wind Harmer
13.348
339236AF1-050_GEN
Solar/Wind Harmer
0.955
970077AG2-063 GEN
Solar/Wind Harmer
2.789
966841AG1-555 GEN
Solar/Wind Harmer
1.294
274674JOLIET 9 ;6U
Adder
6.759
972259AH1-714 GEN
Adder
8.367
274803UNIV PARK;6U
Adder
2.554
274696ROCKY RD ;4P
Adder
0.295
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.411
971191AH1-055 GEN
Solar/Wind Harmer
86.587
25194608D.CRK4
Adder
1.778
25196608WSDLE5
Adder
9.268
252510AF1-249 C
Solar/Wind Harmer
0.452
253316AC1-085 GEN3
Solar/Wind Harmer
8.99
253433AC1-085 GEN1
Solar/Wind Harmer
5.707
946181AF1-283 GEN
Solar/Wind Harmer
13.952
958171AF2-111 GEN
Solar/Wind Harmer
25.736
25196008MFTGT1
Adder
1.386
972173AH1-669 GEN
Solar/Wind Harmer
4.892
972167AH1-666 GEN
Solar/Wind Harmer
7.71
253406AD2-031_GEN
Solar/Wind Harmer
1.22
270273AD2-016 GEN
Solar/Wind Harmer
2.5
253415AE1-040 GEN
Solar/Wind Harmer
1.023
270222AC2-111 GEN
Solar/Wind Harmer
7.003
253303V4-073 C
Solar/Wind Harmer
0.1
253370AE2-315 SEC1
Adder
1.72
253371AE2-315 SEC2
Adder
1.627
3429391JKCT 9G
Adder
6.576
270356AE2-297 GEN
Solar/Wind Harmer
3.463
270437AC2-090 C
Solar/Wind Harmer
3.998
970093AG2-073 GEN
Solar/Wind Harmer
7.116
966571AG1-526 GEN
Solar/Wind Harmer
15.203
24728705AND G3
Adder
5.409
24728505AND G1
Adder
2.586
253338AC1-165 GEN
Solar/Wind Harmer
0.731
253333AC1-068 GEN
Solar/Wind Harmer
0.705
958821AF2-173 GEN
Solar/Wind Harmer
9.202
270004AE1-209 GEN
Solar/Wind Harmer
3.592
946031AF1-268 GEN
Solar/Wind Harmer
5.411
970243AG2-164 GEN
Solar/Wind Harmer
16.205
970519AG2-331 GEN
Solar/Wind Harmer
10.887
970699AG2-449 GEN
Solar/Wind Harmer
7.202
962031AG1-047 GEN
Solar/Wind Harmer
1.893
957741AF2-068 GEN
Solar/Wind Harmer
9.396
970289AG2-191 GEN
Solar/Wind Harmer
0.458
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.321
970193AG2-126 GEN
Solar/Wind Harmer
8.463
960741AF2-365 GEN
Solar/Wind Harmer
2.669
944531AF1-118 GEN
Solar/Wind Harmer
18.282
970605AG2-385 GEN
Solar/Wind Harmer
2.789
972273AH1-721 GEN
Adder
41.984
274729ELWOOD EC;1P
Adder
7.226
274730ELWOOD EC;6P
Adder
7.225
274734ELWOOD EC;8P
Adder
7.225
274736ELWOOD EC;9P
Adder
7.225
972228AH1-698 GEN2
Adder
1.628
274800UNIV PARK;3U
Adder
2.555
972038AH1-567 GEN2
Adder
0.16
274676JOLIET 29;8U
Adder
12.966
274802UNIV PARK;5U
Adder
2.554
274826FISK ;BP
Adder
4.792
235780M24_1
Solar/Wind Helper
0.998
24803406KYGER 5HP
50/50
4.135
24803206KYGER 4HP
50/50
4.132
252507AC2-088 GEN
Solar/Wind Harmer
2.152
25196808ZIMRHP
Adder
83.726
25194608D.CRK4
Adder
1.778
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.732
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
18.088
270263AC1-001 GEN
Solar/Wind Harmer
0.979
339216AC1-074 GEN
Solar/Wind Harmer
1.526
253370AE2-315 SEC1
Adder
1.72
253371AE2-315 SEC2
Adder
1.627
25326309TAIT D
Adder
0.909
943111AE2-339 GEN
Solar/Wind Harmer
0.729
960071AF2-298 GEN
Solar/Wind Harmer
4.096
3429421JKCT 10G
Adder
6.576
3429241JKCT 3G
Adder
9.052
942081AE2-220 GEN
Solar/Wind Harmer
4.578
270239V3-007_GEN1
Solar/Wind Harmer
1.232
971565AH1-281 GEN
Solar/Wind Harmer
1.37
24728605AND G2
Adder
2.586
253343AC1-166 GEN
Solar/Wind Harmer
0.731
253325AC1-069 GEN
Solar/Wind Harmer
0.705
247536S-71 GEN
Solar/Wind Harmer
2.668
270005AE1-210 C O1
Solar/Wind Harmer
3.592
965031AG1-367 GEN
Solar/Wind Harmer
6.573
970825AG2-519 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
49.481
971821AH1-427 GEN
Solar/Wind Harmer
6.424
970333AG2-219 GEN
Solar/Wind Harmer
19.806
276903AD2-071 C
Solar/Wind Harmer
6.236
270032AE2-172
Solar/Wind Harmer
2.842
945371AF1-202 GEN
Solar/Wind Harmer
4.221
970291AG2-192 GEN
Solar/Wind Harmer
0.776
270445AC2-157 GEN2
Solar/Wind Harmer
3.313
958861AF2-177 GEN
Solar/Wind Harmer
6.369
965651AG1-433 GEN
Solar/Wind Harmer
3.12
339241AF1-083 GEN
Solar/Wind Harmer
0.932
270159DARBY CT4
Adder
4.776
963741AG1-226 GEN
Solar/Wind Harmer
24.026
970593AG2-378 GEN
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
4.286
24387305FR-4G C
Solar/Wind Harmer
2.62
964901AG1-354 GEN
Solar/Wind Harmer
7.622
274732ELWOOD EC;7P
Adder
7.225
274674JOLIET 9 ;6U
Adder
6.759
274801UNIV PARK;4U
Adder
2.555
274676JOLIET 29;8U
Adder
13.447
274745AC1-111 GEN9
Adder
2.448
960001AF2-291 GEN
Solar/Wind Helper
1.675
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
68.979
957141AF2-008_MTX
Adder
34.49
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.558
LAGNLTFEXP_LAGN->PJM
CLTF
5.577
TVALTFEXP_TVA->PJM
CLTF
2.613
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.304
WECLTFEXP_WEC->PJM
CLTF
1.665
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.668
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.83
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.269
MECLTFEXP_MEC->PJM
CLTF
7.133
SIGELTFEXP_SIGE->PJM
CLTF
0.33

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#309_05HANG R 765_B2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2363.36
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.756
252524AE2-267 GEN
Solar/Wind Harmer
1.704
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
9.494
972165AH1-665 GEN
Solar/Wind Harmer
7.595
270367AC2-061_GEN
Solar/Wind Harmer
3.018
270269AC2-059
Solar/Wind Harmer
8.724
270340AC2-060 GEN
Solar/Wind Harmer
2.823
339243AC2-075 GEN1
Solar/Wind Harmer
0.414
944031AF1-071 GEN
Solar/Wind Harmer
0.862
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
13.474
253349AC2-067 GEN
Solar/Wind Harmer
4.09
253400AC2-068 GEN
Solar/Wind Harmer
1.644
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
5.21
971673AH1-337 GEN
Solar/Wind Harmer
3.321
270240V3-007_GEN2
Solar/Wind Harmer
4.424
971029AG2-637 GEN
Solar/Wind Harmer
10.686
241972AD1-140 GEN
Solar/Wind Harmer
3.154
270543AE2-219 C
Solar/Wind Harmer
3.503
970455AG2-298 GEN
Solar/Wind Harmer
3.979
339211AE2-254 GEN
Solar/Wind Harmer
0.997
970115AG2-085 GEN
Solar/Wind Harmer
2.582
24725505WLD G2 C
Solar/Wind Harmer
2.523
24699105WLD G1 C
Solar/Wind Harmer
2.493
961761AG1-017 GEN
Solar/Wind Harmer
0.268
270594AE1-207 GEN
Solar/Wind Harmer
8.964
945581AF1-223 GEN
Solar/Wind Harmer
2.738
965461AG1-414 GEN
Solar/Wind Harmer
1.35
970289AG2-191 GEN
Solar/Wind Harmer
1.132
965101AG1-375 GEN
Solar/Wind Harmer
5.814
270024AE2-089 GEN
Solar/Wind Harmer
2.674
958711AF2-162 GEN
Solar/Wind Harmer
0.576
965401AG1-405 GEN
Solar/Wind Harmer
3.152
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
5.728
945631AF1-228 GEN
Solar/Wind Harmer
2.424
24386205FR-12G C
Solar/Wind Harmer
2.206
24386405FR-21G C
Solar/Wind Harmer
2.213
24386605FR-22G C
Solar/Wind Harmer
2.213
24387005FR-3G C
Solar/Wind Harmer
2.036
24690905MDL-1G C
Solar/Wind Harmer
4.026
270180AB1-006 GEN1
Solar/Wind Harmer
3.607
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
274746AC1-111 G10
Adder
2.444
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.901
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
5.186
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
8.982
253394AE2-221_GEN
Solar/Wind Harmer
4.593
253398AE2-221_GEN2
Solar/Wind Harmer
4.593
270186AC1-089 GEN
Solar/Wind Harmer
5.711
962581AG1-107 GEN
Solar/Wind Harmer
4.655
961491AF2-440 GEN
Solar/Wind Harmer
1.934
970235AG2-159 GEN
Solar/Wind Harmer
3.659
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
1.373
972043AH1-570 GEN
Solar/Wind Harmer
2.172
972045AH1-571 GEN
Solar/Wind Harmer
1.738
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
3.374
970107AG2-081 GEN
Solar/Wind Harmer
2.53
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
7.516
24379505HDWTR1G C
Solar/Wind Harmer
5.654
270209AC1-174_GEN
Solar/Wind Harmer
3.99
926881AC1-175 GEN
Solar/Wind Harmer
3.99
270383AD1-128 GEN
Solar/Wind Harmer
4.306
960161AF2-307 GEN
Solar/Wind Harmer
4.504
970883AG2-550 GEN
Solar/Wind Harmer
6.842
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
6.852
964571AG1-320 GEN
Solar/Wind Harmer
5.299
960441AF2-335 GEN
Solar/Wind Harmer
6.456
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.744
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
6.882
270201AC2-176 GEN
Solar/Wind Harmer
3.214
970653AG2-424 GEN
Solar/Wind Harmer
2.974
970653AG2-424 GEN
Solar/Wind Harmer
1.075
270518AE2-148 GEN
Solar/Wind Harmer
7.376
270599AE1-208 GEN
Solar/Wind Harmer
4.957
270031AE2-169
Solar/Wind Harmer
4.957
270444AC2-157 GEN1
Solar/Wind Harmer
3.31
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
2.386
960971AF2-388 GEN
Solar/Wind Harmer
6.226
945391AF1-204 GEN
Solar/Wind Harmer
7.855
971081AG2-670 GEN
Solar/Wind Harmer
4.16
942221AE2-234 GEN
Solar/Wind Harmer
0.394
253378AE2-206_GEN
Solar/Wind Harmer
1.926
276820AF1-078_GEN
Solar/Wind Harmer
0.856
970241AG2-163 GEN
Solar/Wind Harmer
13.326
339236AF1-050_GEN
Solar/Wind Harmer
0.962
970077AG2-063 GEN
Solar/Wind Harmer
2.779
966841AG1-555 GEN
Solar/Wind Harmer
1.291
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
972267AH1-718 GEN
Adder
1.821
274803UNIV PARK;6U
Adder
2.549
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
86.549
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.451
253316AC1-085 GEN3
Solar/Wind Harmer
8.982
253433AC1-085 GEN1
Solar/Wind Harmer
5.702
946181AF1-283 GEN
Solar/Wind Harmer
13.94
958171AF2-111 GEN
Solar/Wind Harmer
25.744
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
4.883
972167AH1-666 GEN
Solar/Wind Harmer
7.721
253406AD2-031_GEN
Solar/Wind Harmer
1.219
270273AD2-016 GEN
Solar/Wind Harmer
2.495
253415AE1-040 GEN
Solar/Wind Harmer
1.022
270222AC2-111 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.099
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
3.459
270437AC2-090 C
Solar/Wind Harmer
3.992
970093AG2-073 GEN
Solar/Wind Harmer
7.147
966571AG1-526 GEN
Solar/Wind Harmer
15.27
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.729
253333AC1-068 GEN
Solar/Wind Harmer
0.703
958821AF2-173 GEN
Solar/Wind Harmer
9.186
270004AE1-209 GEN
Solar/Wind Harmer
3.586
946031AF1-268 GEN
Solar/Wind Harmer
5.401
970243AG2-164 GEN
Solar/Wind Harmer
16.159
970519AG2-331 GEN
Solar/Wind Harmer
10.856
970699AG2-449 GEN
Solar/Wind Harmer
7.182
962031AG1-047 GEN
Solar/Wind Harmer
1.89
957741AF2-068 GEN
Solar/Wind Harmer
9.378
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
8.454
960741AF2-365 GEN
Solar/Wind Harmer
2.685
944531AF1-118 GEN
Solar/Wind Harmer
18.231
970605AG2-385 GEN
Solar/Wind Harmer
2.779
972273AH1-721 GEN
Adder
42.389
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274802UNIV PARK;5U
Adder
2.549
235780M24_1
Solar/Wind Helper
0.999
274744AC1-111 GEN8
Adder
2.444
972037AH1-567 GEN1
Adder
0.08
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
946581AF1-322 GEN
Solar/Wind Harmer
1.959
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
2.151
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.723
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
18.114
270263AC1-001 GEN
Solar/Wind Harmer
0.977
339216AC1-074 GEN
Solar/Wind Harmer
1.528
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
943111AE2-339 GEN
Solar/Wind Harmer
0.73
960071AF2-298 GEN
Solar/Wind Harmer
4.09
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
942081AE2-220 GEN
Solar/Wind Harmer
4.571
270239V3-007_GEN1
Solar/Wind Harmer
1.23
971565AH1-281 GEN
Solar/Wind Harmer
1.374
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.729
253325AC1-069 GEN
Solar/Wind Harmer
0.703
247536S-71 GEN
Solar/Wind Harmer
2.663
270005AE1-210 C O1
Solar/Wind Harmer
3.586
965031AG1-367 GEN
Solar/Wind Harmer
6.561
970825AG2-519 GEN
Solar/Wind Harmer
1.529
971821AH1-427 GEN
Solar/Wind Harmer
6.457
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
19.749
276903AD2-071 C
Solar/Wind Harmer
6.224
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
4.213
970291AG2-192 GEN
Solar/Wind Harmer
0.774
270445AC2-157 GEN2
Solar/Wind Harmer
3.31
958861AF2-177 GEN
Solar/Wind Harmer
6.354
965651AG1-433 GEN
Solar/Wind Harmer
3.113
339241AF1-083 GEN
Solar/Wind Harmer
0.937
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
23.987
970593AG2-378 GEN
Solar/Wind Harmer
1.029
24385905FR-11G C
Solar/Wind Harmer
4.277
24387305FR-4G C
Solar/Wind Harmer
2.615
964901AG1-354 GEN
Solar/Wind Harmer
7.68
274732ELWOOD EC;7P
Adder
7.212
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1560_05BAKER 765_Q2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.34 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2361.46
MW Contribution:1.03
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.154
24802906KYGER 2LP
50/50
2.442
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.895
252519AF1-045_GEN
Solar/Wind Harmer
6.792
252516AE2-318_GEN
Solar/Wind Harmer
5.181
25194408D.CRK1
Adder
8.166
25194508D.CRK3
Adder
1.527
253317AC1-085 GEN4
Solar/Wind Harmer
8.973
253394AE2-221_GEN
Solar/Wind Harmer
4.589
253398AE2-221_GEN2
Solar/Wind Harmer
4.589
270186AC1-089 GEN
Solar/Wind Harmer
5.695
962581AG1-107 GEN
Solar/Wind Harmer
4.642
961491AF2-440 GEN
Solar/Wind Harmer
1.929
970235AG2-159 GEN
Solar/Wind Harmer
3.656
970235AG2-159 GEN
Solar/Wind Harmer
2.232
339221AD2-048_GEN
Solar/Wind Harmer
1.371
972043AH1-570 GEN
Solar/Wind Harmer
2.169
972045AH1-571 GEN
Solar/Wind Harmer
1.735
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
3.37
970107AG2-081 GEN
Solar/Wind Harmer
2.527
25322209TAIT E
Adder
8.079
25322209TAIT E
Adder
7.897
25326109MON D
Adder
1.063
24728805RICHG1
Adder
2.983
24728905RICHG2
Adder
2.983
942891AE2-308 GEN
Solar/Wind Harmer
7.505
24379505HDWTR1G C
Solar/Wind Harmer
5.649
270209AC1-174_GEN
Solar/Wind Harmer
3.987
926881AC1-175 GEN
Solar/Wind Harmer
3.987
270383AD1-128 GEN
Solar/Wind Harmer
4.302
960161AF2-307 GEN
Solar/Wind Harmer
4.486
970883AG2-550 GEN
Solar/Wind Harmer
6.835
970885AG2-551 GEN
Solar/Wind Harmer
1.59
970825AG2-519 GEN
Solar/Wind Harmer
6.846
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.409
971191AH1-055 GEN
Solar/Wind Harmer
86.509
25194608D.CRK4
Adder
1.775
25196608WSDLE5
Adder
9.252
252510AF1-249 C
Solar/Wind Harmer
0.451
253316AC1-085 GEN3
Solar/Wind Harmer
8.973
253433AC1-085 GEN1
Solar/Wind Harmer
5.696
946181AF1-283 GEN
Solar/Wind Harmer
13.926
958171AF2-111 GEN
Solar/Wind Harmer
25.716
25196008MFTGT1
Adder
1.384
972173AH1-669 GEN
Solar/Wind Harmer
4.876
972167AH1-666 GEN
Solar/Wind Harmer
7.706
253406AD2-031_GEN
Solar/Wind Harmer
1.218
270273AD2-016 GEN
Solar/Wind Harmer
2.491
253415AE1-040 GEN
Solar/Wind Harmer
1.02
270222AC2-111 GEN
Solar/Wind Harmer
6.988
253303V4-073 C
Solar/Wind Harmer
0.099
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
3429391JKCT 9G
Adder
6.587
270356AE2-297 GEN
Solar/Wind Harmer
3.456
270437AC2-090 C
Solar/Wind Harmer
3.989
970093AG2-073 GEN
Solar/Wind Harmer
7.136
966571AG1-526 GEN
Solar/Wind Harmer
15.255
24728705AND G3
Adder
5.399
24728505AND G1
Adder
2.582
253338AC1-165 GEN
Solar/Wind Harmer
0.728
253333AC1-068 GEN
Solar/Wind Harmer
0.702
958821AF2-173 GEN
Solar/Wind Harmer
9.178
270004AE1-209 GEN
Solar/Wind Harmer
3.583
946031AF1-268 GEN
Solar/Wind Harmer
5.397
970243AG2-164 GEN
Solar/Wind Harmer
16.146
970519AG2-331 GEN
Solar/Wind Harmer
10.848
970699AG2-449 GEN
Solar/Wind Harmer
7.176
962031AG1-047 GEN
Solar/Wind Harmer
1.888
957741AF2-068 GEN
Solar/Wind Harmer
9.369
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.415
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.31
970193AG2-126 GEN
Solar/Wind Harmer
8.449
960741AF2-365 GEN
Solar/Wind Harmer
2.684
944531AF1-118 GEN
Solar/Wind Harmer
18.215
970605AG2-385 GEN
Solar/Wind Harmer
2.775
972273AH1-721 GEN
Adder
42.355
274729ELWOOD EC;1P
Adder
7.207
274730ELWOOD EC;6P
Adder
7.207
274734ELWOOD EC;8P
Adder
7.207
274736ELWOOD EC;9P
Adder
7.207
972228AH1-698 GEN2
Adder
1.623
274676JOLIET 29;8U
Adder
12.934
274800UNIV PARK;3U
Adder
2.548
972038AH1-567 GEN2
Adder
0.159
274802UNIV PARK;5U
Adder
2.547
235780M24_1
Solar/Wind Helper
0.999
964571AG1-320 GEN
Solar/Wind Harmer
5.295
960441AF2-335 GEN
Solar/Wind Harmer
6.451
247621Y3-024
Adder
0.154
964611AG1-324 GEN
Solar/Wind Harmer
0.743
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
6.877
270201AC2-176 GEN
Solar/Wind Harmer
3.211
970653AG2-424 GEN
Solar/Wind Harmer
2.972
970653AG2-424 GEN
Solar/Wind Harmer
1.074
270518AE2-148 GEN
Solar/Wind Harmer
7.366
270599AE1-208 GEN
Solar/Wind Harmer
4.953
270031AE2-169
Solar/Wind Harmer
4.953
270444AC2-157 GEN1
Solar/Wind Harmer
3.307
25326509SID D
Adder
0.759
944541AF1-119 GEN
Solar/Wind Harmer
2.384
960971AF2-388 GEN
Solar/Wind Harmer
6.221
945391AF1-204 GEN
Solar/Wind Harmer
7.849
971081AG2-670 GEN
Solar/Wind Harmer
4.157
942221AE2-234 GEN
Solar/Wind Harmer
0.394
253378AE2-206_GEN
Solar/Wind Harmer
1.924
276820AF1-078_GEN
Solar/Wind Harmer
0.855
970241AG2-163 GEN
Solar/Wind Harmer
13.317
339236AF1-050_GEN
Solar/Wind Harmer
0.962
966841AG1-555 GEN
Solar/Wind Harmer
1.29
970077AG2-063 GEN
Solar/Wind Harmer
2.775
274674JOLIET 9 ;6U
Adder
6.742
972259AH1-714 GEN
Adder
8.345
972267AH1-718 GEN
Adder
1.82
274803UNIV PARK;6U
Adder
2.547
274764LEE CO EC;5U
Adder
4.073
274765LEE CO EC;6U
Adder
2.573
237033AB1-150 GEN
Solar/Wind Helper
0.403
24802606KYGER 1HP
50/50
4.203
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.409
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.731
252524AE2-267 GEN
Solar/Wind Harmer
1.703
25196408WSDLE3
Adder
9.524
25196308WSDLE2
Adder
9.441
25196208WSDLE1
Adder
9.417
25196708WSDLE6
Adder
9.394
25196508WSDLE4
Adder
9.157
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
972163AH1-664 GEN
Solar/Wind Harmer
9.474
972165AH1-665 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.01
270269AC2-059
Solar/Wind Harmer
8.712
270340AC2-060 GEN
Solar/Wind Harmer
2.818
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
944031AF1-071 GEN
Solar/Wind Harmer
0.861
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
970689AG2-444 GEN
Solar/Wind Harmer
13.458
253349AC2-067 GEN
Solar/Wind Harmer
4.085
253400AC2-068 GEN
Solar/Wind Harmer
1.643
3429211JKCT 2G
Adder
8.952
270432AC2-029 GEN
Solar/Wind Harmer
5.202
971673AH1-337 GEN
Solar/Wind Harmer
3.318
270240V3-007_GEN2
Solar/Wind Harmer
4.42
971029AG2-637 GEN
Solar/Wind Harmer
10.676
241972AD1-140 GEN
Solar/Wind Harmer
3.15
270543AE2-219 C
Solar/Wind Harmer
3.5
970455AG2-298 GEN
Solar/Wind Harmer
3.975
339211AE2-254 GEN
Solar/Wind Harmer
0.995
970115AG2-085 GEN
Solar/Wind Harmer
2.58
24725505WLD G2 C
Solar/Wind Harmer
2.521
24699105WLD G1 C
Solar/Wind Harmer
2.491
961761AG1-017 GEN
Solar/Wind Harmer
0.267
270594AE1-207 GEN
Solar/Wind Harmer
8.956
945581AF1-223 GEN
Solar/Wind Harmer
2.736
965461AG1-414 GEN
Solar/Wind Harmer
1.349
970289AG2-191 GEN
Solar/Wind Harmer
1.131
965101AG1-375 GEN
Solar/Wind Harmer
5.809
270024AE2-089 GEN
Solar/Wind Harmer
2.672
958711AF2-162 GEN
Solar/Wind Harmer
0.576
965401AG1-405 GEN
Solar/Wind Harmer
3.149
965411AG1-406 GEN
Solar/Wind Harmer
1.413
270156DARBY CT1
Adder
4.829
270157DARBY CT2
Adder
4.817
270158DARBY CT3
Adder
4.74
24729505KEY G4
Adder
3.46
972203AH1-686 GEN
Adder
1.224
963841AG1-237 GEN
Solar/Wind Harmer
5.724
945631AF1-228 GEN
Solar/Wind Harmer
2.42
24386205FR-12G C
Solar/Wind Harmer
2.204
24386405FR-21G C
Solar/Wind Harmer
2.212
24386605FR-22G C
Solar/Wind Harmer
2.212
24387005FR-3G C
Solar/Wind Harmer
2.034
24690905MDL-1G C
Solar/Wind Harmer
4.023
270180AB1-006 GEN1
Solar/Wind Harmer
3.604
274731ELWOOD EC;2P
Adder
7.207
274733ELWOOD EC;3P
Adder
7.207
274735ELWOOD EC;4P
Adder
7.207
274728ELWOOD EC;5P
Adder
7.207
972227AH1-698 GEN1
Adder
1.143
274675JOLIET 29;7U
Adder
13.413
274675JOLIET 29;7U
Adder
12.934
274687WILL CNTY;4U
Adder
12.214
274687WILL CNTY;4U
Adder
12.214
274746AC1-111 G10
Adder
2.442
274744AC1-111 GEN8
Adder
2.442
972037AH1-567 GEN1
Adder
0.08
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.2
946581AF1-322 GEN
Solar/Wind Harmer
1.958
24803406KYGER 5HP
50/50
4.132
24803206KYGER 4HP
50/50
4.129
252507AC2-088 GEN
Solar/Wind Harmer
2.149
25196808ZIMRHP
Adder
83.601
25194608D.CRK4
Adder
1.775
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.712
25196008MFTGT1
Adder
1.429
945681AF1-233 GEN
Solar/Wind Harmer
18.078
270263AC1-001 GEN
Solar/Wind Harmer
0.975
339216AC1-074 GEN
Solar/Wind Harmer
1.526
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.907
943111AE2-339 GEN
Solar/Wind Harmer
0.73
960071AF2-298 GEN
Solar/Wind Harmer
4.085
3429421JKCT 10G
Adder
6.587
3429241JKCT 3G
Adder
9.07
942081AE2-220 GEN
Solar/Wind Harmer
4.567
270239V3-007_GEN1
Solar/Wind Harmer
1.229
971565AH1-281 GEN
Solar/Wind Harmer
1.373
24728605AND G2
Adder
2.582
253343AC1-166 GEN
Solar/Wind Harmer
0.728
253325AC1-069 GEN
Solar/Wind Harmer
0.702
247536S-71 GEN
Solar/Wind Harmer
2.66
270005AE1-210 C O1
Solar/Wind Harmer
3.583
965031AG1-367 GEN
Solar/Wind Harmer
6.556
970825AG2-519 GEN
Solar/Wind Harmer
1.528
971821AH1-427 GEN
Solar/Wind Harmer
6.451
970091AG2-072 GEN
Adder
49.343
970333AG2-219 GEN
Solar/Wind Harmer
19.734
276903AD2-071 C
Solar/Wind Harmer
6.219
270032AE2-172
Solar/Wind Harmer
2.834
945371AF1-202 GEN
Solar/Wind Harmer
4.209
970291AG2-192 GEN
Solar/Wind Harmer
0.774
270445AC2-157 GEN2
Solar/Wind Harmer
3.307
958861AF2-177 GEN
Solar/Wind Harmer
6.349
965651AG1-433 GEN
Solar/Wind Harmer
3.11
339241AF1-083 GEN
Solar/Wind Harmer
0.937
270159DARBY CT4
Adder
4.752
963741AG1-226 GEN
Solar/Wind Harmer
23.97
24385905FR-11G C
Solar/Wind Harmer
4.274
24387305FR-4G C
Solar/Wind Harmer
2.613
970593AG2-378 GEN
Solar/Wind Harmer
1.028
964901AG1-354 GEN
Solar/Wind Harmer
7.677
274732ELWOOD EC;7P
Adder
7.207
274674JOLIET 9 ;6U
Adder
6.742
274676JOLIET 29;8U
Adder
13.413
274801UNIV PARK;4U
Adder
2.548
274745AC1-111 GEN9
Adder
2.442
960001AF2-291 GEN
Solar/Wind Helper
1.68
270331AC1-082 GEN3
Solar/Wind Helper
0.199
944201AF1-088_MTX
Adder
68.864
957141AF2-008_MTX
Adder
34.432
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.948
LAGNLTFEXP_LAGN->PJM
CLTF
5.68
TVALTFEXP_TVA->PJM
CLTF
2.676
NYPJM->LTFIMP_NY
CLTF
1.589
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.663
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.615
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.72
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.465
MECLTFEXP_MEC->PJM
CLTF
7.143
SIGELTFEXP_SIGE->PJM
CLTF
0.33

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.78 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2183.34
MW Contribution:0.81
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
0.38
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.481
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
12.638
270263AC1-001 GEN
Solar/Wind Harmer
0.653
339216AC1-074 GEN
Solar/Wind Harmer
0.174
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
960071AF2-298 GEN
Solar/Wind Harmer
2.849
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.657
971565AH1-281 GEN
Solar/Wind Harmer
0.959
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
247536S-71 GEN
Solar/Wind Harmer
0.185
270005AE1-210 C O1
Solar/Wind Harmer
0.992
965031AG1-367 GEN
Solar/Wind Harmer
4.578
970825AG2-519 GEN
Solar/Wind Harmer
1.608
971821AH1-427 GEN
Solar/Wind Harmer
4.505
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
3.125
276903AD2-071 C
Solar/Wind Harmer
4.849
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
958861AF2-177 GEN
Solar/Wind Harmer
1.758
965651AG1-433 GEN
Solar/Wind Harmer
1.166
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
8.802
970593AG2-378 GEN
Solar/Wind Harmer
0.808
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.358
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.212
962241AG1-070 GEN
Solar/Wind Harmer
1.862
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276615X2-022 GEN
Solar/Wind Harmer
0.035
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.214
963831AG1-236 GEN
Solar/Wind Harmer
1.313
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.749
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.279
958381AF2-132 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.562
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
6.619
970245AG2-165 GEN
Solar/Wind Harmer
1.366
939401AE1-172 GEN
Solar/Wind Harmer
2.35
274877BISHOP HL;1U
Solar/Wind Harmer
0.105
970569AG2-363 GEN
Solar/Wind Harmer
9.313
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
276158O29GEN2
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.212
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.15
959081AF2-199 GEN
Solar/Wind Harmer
3.05
971067AG2-660 GEN
Solar/Wind Harmer
1.017
274872LEEDK;1U
Solar/Wind Harmer
0.002
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
2.901
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
5.902
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
7.374
972165AH1-665 GEN
Solar/Wind Harmer
5.906
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
11.775
253349AC2-067 GEN
Solar/Wind Harmer
1.803
253400AC2-068 GEN
Solar/Wind Harmer
0.725
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
2.302
971673AH1-337 GEN
Solar/Wind Harmer
3.274
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.455
241972AD1-140 GEN
Solar/Wind Harmer
0.537
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
3.084
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.802
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.766
971609AH1-304 GEN
Solar/Wind Harmer
0.693
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.789
965101AG1-375 GEN
Solar/Wind Harmer
4.056
270024AE2-089 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
2.199
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
1.584
945631AF1-228 GEN
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.022
971611AH1-305 GEN
Solar/Wind Harmer
2.007
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.122
963791AG1-232 GEN
Solar/Wind Harmer
4.535
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.276
943851AF1-053 GEN
Solar/Wind Harmer
0.884
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.422
941731AE2-173 GEN
Solar/Wind Harmer
2.716
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.133
970169AG2-114 GEN
Solar/Wind Harmer
3.189
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.103
926823AC1-168 GEN
Solar/Wind Harmer
0.529
276868AE1-113 GEN
Solar/Wind Harmer
0.619
276882AE2-255 GEN
Solar/Wind Harmer
0.361
970833AG2-524 GEN
Solar/Wind Harmer
3.372
970833AG2-524 GEN
Solar/Wind Harmer
2.248
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
960591AF2-350 GEN
Solar/Wind Harmer
3.057
961011AF2-392 GEN
Solar/Wind Harmer
1.791
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
971681AH1-341 GEN
Solar/Wind Harmer
4.912
274746AC1-111 G10
Adder
2.444
274744AC1-111 GEN8
Adder
2.444
971171AH1-044 GEN
Solar/Wind Harmer
6.1
971675AH1-338 GEN
Solar/Wind Harmer
1.189
972037AH1-567 GEN1
Adder
0.08
946321AF1-296 GEN
Solar/Wind Harmer
1.708
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.447
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.058
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.726
958171AF2-111 GEN
Solar/Wind Harmer
17.961
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
3.407
972167AH1-666 GEN
Solar/Wind Harmer
5.387
253406AD2-031_GEN
Solar/Wind Harmer
0.496
270273AD2-016 GEN
Solar/Wind Harmer
0.676
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270222AC2-111 GEN
Solar/Wind Harmer
3.033
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
970191AG2-125 GEN
Solar/Wind Harmer
1.473
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.986
966571AG1-526 GEN
Solar/Wind Harmer
10.654
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
958821AF2-173 GEN
Solar/Wind Harmer
6.409
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.321
970243AG2-164 GEN
Solar/Wind Harmer
2.557
970519AG2-331 GEN
Solar/Wind Harmer
11.364
970699AG2-449 GEN
Solar/Wind Harmer
1.093
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.542
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
5.898
960741AF2-365 GEN
Solar/Wind Harmer
1.874
944531AF1-118 GEN
Solar/Wind Harmer
16.287
970605AG2-385 GEN
Solar/Wind Harmer
2.184
972273AH1-721 GEN
Adder
42.389
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.498
970273AG2-179 GEN
Solar/Wind Harmer
2.077
962251AG1-071 GEN
Solar/Wind Harmer
2.135
339250AF1-203 GEN
Solar/Wind Harmer
0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.156
971155AH1-034 GEN
Solar/Wind Harmer
3.958
276621W2-048 GEN
Solar/Wind Harmer
0.17
276838X2-022 GEN2
Solar/Wind Harmer
0.19
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.555
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.838
959611AF2-252 GEN
Solar/Wind Harmer
1.093
942111AE2-223 GEN
Solar/Wind Harmer
1.059
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.366
970517AG2-330 GEN
Solar/Wind Harmer
8.195
274878BISHOP HL;2U
Solar/Wind Harmer
0.105
970571AG2-364 GEN
Solar/Wind Harmer
6.209
942051AE2-217 GEN
Solar/Wind Harmer
5.584
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.821
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.1
274802UNIV PARK;5U
Adder
2.549
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.774
274872LEEDK;1U
Solar/Wind Harmer
0.112
235780M24_1
Solar/Wind Helper
0.999
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
6.03
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.893
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.576
972045AH1-571 GEN
Solar/Wind Harmer
1.263
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
2.354
970107AG2-081 GEN
Solar/Wind Harmer
1.765
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
5.244
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.231
970883AG2-550 GEN
Solar/Wind Harmer
4.773
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
5.021
964571AG1-320 GEN
Solar/Wind Harmer
4.118
960441AF2-335 GEN
Solar/Wind Harmer
4.504
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
1.093
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.075
970653AG2-424 GEN
Solar/Wind Harmer
1.075
971613AH1-306 GEN
Solar/Wind Harmer
2.042
270518AE2-148 GEN
Solar/Wind Harmer
0.367
270599AE1-208 GEN
Solar/Wind Harmer
3.89
270031AE2-169
Solar/Wind Harmer
2.334
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.032
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.178
971081AG2-670 GEN
Solar/Wind Harmer
2.902
942221AE2-234 GEN
Solar/Wind Harmer
0.019
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.613
970241AG2-163 GEN
Solar/Wind Harmer
2.169
970077AG2-063 GEN
Solar/Wind Harmer
2.064
966841AG1-555 GEN
Solar/Wind Harmer
0.406
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
276916AD2-100_GEN
Solar/Wind Harmer
7.156
276911AD2-131_GEN
Solar/Wind Harmer
0.471
339255AE2-071 GEN
Solar/Wind Harmer
-0.056
964781AG1-341 GEN
Solar/Wind Harmer
3.601
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
2.586
960611AF2-352 GEN
Solar/Wind Harmer
1.093
970321AG2-212 GEN
Solar/Wind Harmer
1.366
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.123
276646AC1-214 GEN2
Solar/Wind Harmer
0.123
971485AH1-239 GEN
Solar/Wind Harmer
2.495
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.13
958491AF2-143 GEN
Solar/Wind Harmer
4.624
966021AG1-471 GEN
Solar/Wind Harmer
1.664
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.416
958481AF2-142 GEN
Solar/Wind Harmer
4.61
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.402
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.821
971341AH1-150 GEN
Solar/Wind Harmer
6.1
971343AH1-151 GEN
Solar/Wind Harmer
6.1
274803UNIV PARK;6U
Adder
2.549
938861AE1-114 GEN
Solar/Wind Harmer
1.728
962691AG1-118 GEN
Solar/Wind Harmer
9.146
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
970921AG2-575 GEN
Solar/Wind Harmer
3.048
970921AG2-575 GEN
Solar/Wind Harmer
1.016
971573AH1-285 GEN
Solar/Wind Harmer
0.568
237033AB1-150 GEN
Solar/Wind Helper
0.403
971333AH1-146 GEN
Solar/Wind Harmer
3.002
971335AH1-147 GEN
Solar/Wind Harmer
3.002
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.21 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2174.62
MW Contribution:0.76
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.078
24803206KYGER 4HP
50/50
4.075
252507AC2-088 GEN
Solar/Wind Harmer
0.367
25196808ZIMRHP
Adder
80.97
25194608D.CRK4
Adder
1.724
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.127
25196008MFTGT1
Adder
1.401
945681AF1-233 GEN
Solar/Wind Harmer
12.229
339216AC1-074 GEN
Solar/Wind Harmer
0.17
270263AC1-001 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.649
253371AE2-315 SEC2
Adder
1.56
25326309TAIT D
Adder
0.872
960071AF2-298 GEN
Solar/Wind Harmer
2.739
3429421JKCT 10G
Adder
6.526
3429241JKCT 3G
Adder
9.013
970773AG2-487 GEN
Solar/Wind Harmer
0.928
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.628
971565AH1-281 GEN
Solar/Wind Harmer
0.973
970091AG2-072 GEN
Adder
52.877
24728605AND G2
Adder
2.601
970333AG2-219 GEN
Solar/Wind Harmer
3.361
971821AH1-427 GEN
Solar/Wind Harmer
4.564
270005AE1-210 C O1
Solar/Wind Harmer
0.988
965031AG1-367 GEN
Solar/Wind Harmer
4.558
247536S-71 GEN
Solar/Wind Harmer
0.183
970825AG2-519 GEN
Solar/Wind Harmer
1.602
276903AD2-071 C
Solar/Wind Harmer
4.881
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
270032AE2-172
Solar/Wind Harmer
2.855
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.546
958861AF2-177 GEN
Solar/Wind Harmer
1.753
965651AG1-433 GEN
Solar/Wind Harmer
1.163
963741AG1-226 GEN
Solar/Wind Harmer
9.112
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.578
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.264
962241AG1-070 GEN
Solar/Wind Harmer
1.948
965911AG1-460 GEN
Solar/Wind Harmer
0.707
276615X2-022 GEN
Solar/Wind Harmer
0.037
963831AG1-236 GEN
Solar/Wind Harmer
1.363
274880W4-005 GEN4
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.362
270159DARBY CT4
Adder
4.382
972175AH1-670 GEN
Solar/Wind Harmer
2.852
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.423
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.726
970593AG2-378 GEN
Solar/Wind Harmer
0.756
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970245AG2-165 GEN
Solar/Wind Harmer
1.415
970373AG2-245 GEN
Solar/Wind Harmer
6.824
939401AE1-172 GEN
Solar/Wind Harmer
2.429
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
970569AG2-363 GEN
Solar/Wind Harmer
9.647
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.681
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276158O29GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.45
274761LEE CO EC;2U
Adder
4.217
274766LEE CO EC;7U
Adder
4.167
957471AF2-041 GEN
Solar/Wind Harmer
9.481
959081AF2-199 GEN
Solar/Wind Harmer
3.16
971067AG2-660 GEN
Solar/Wind Harmer
1.053
276861AD2-134 GEN
Solar/Wind Harmer
0.057
274674JOLIET 9 ;6U
Adder
6.97
972235AH1-702 GEN1
Adder
1.141
274872LEEDK;1U
Solar/Wind Harmer
0.002
970819AG2-516 GEN
Solar/Wind Harmer
3.788
276776AD2-060 GEN
Solar/Wind Harmer
0.329
274822ROCKFORD ;11
Adder
8.878
962781AG1-127 GEN
Solar/Wind Harmer
3.003
274745AC1-111 GEN9
Adder
2.527
274676JOLIET 29;8U
Adder
13.865
960001AF2-291 GEN
Solar/Wind Helper
1.732
270331AC1-082 GEN3
Solar/Wind Helper
0.208
24802606KYGER 1HP
50/50
4.148
24802706KYGER 1LP
50/50
2.435
24803506KYGER 5LP
50/50
2.378
25016408BKJDB1
50/50
0.282
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
5.794
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.254
25196308WSDLE2
Adder
9.174
25196208WSDLE1
Adder
9.151
25196708WSDLE6
Adder
9.128
25196508WSDLE4
Adder
8.898
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
972163AH1-664 GEN
Solar/Wind Harmer
7.142
972165AH1-665 GEN
Solar/Wind Harmer
5.72
270367AC2-061_GEN
Solar/Wind Harmer
0.005
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.56
253372AE2-315 SEC3
Adder
1.56
25306009OHH W.
Adder
2.334
253349AC2-067 GEN
Solar/Wind Harmer
1.738
253400AC2-068 GEN
Solar/Wind Harmer
0.699
3429211JKCT 2G
Adder
8.896
970689AG2-444 GEN
Solar/Wind Harmer
10.729
971673AH1-337 GEN
Solar/Wind Harmer
3.222
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.342
270543AE2-219 C
Solar/Wind Harmer
0.003
270432AC2-029 GEN
Solar/Wind Harmer
2.087
970455AG2-298 GEN
Solar/Wind Harmer
3.135
241972AD1-140 GEN
Solar/Wind Harmer
0.511
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.796
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.796
971609AH1-304 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.797
965101AG1-375 GEN
Solar/Wind Harmer
4.045
965401AG1-405 GEN
Solar/Wind Harmer
2.261
965411AG1-406 GEN
Solar/Wind Harmer
1.454
270024AE2-089 GEN
Solar/Wind Harmer
0.004
963841AG1-237 GEN
Solar/Wind Harmer
1.641
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.458
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.105
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
971611AH1-305 GEN
Solar/Wind Harmer
2.078
270156DARBY CT1
Adder
4.453
270157DARBY CT2
Adder
4.442
270158DARBY CT3
Adder
4.371
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.544
941731AE2-173 GEN
Solar/Wind Harmer
2.813
963791AG1-232 GEN
Solar/Wind Harmer
4.514
945631AF1-228 GEN
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
970169AG2-114 GEN
Solar/Wind Harmer
3.3
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
6.21
957751AF2-069 GEN
Solar/Wind Harmer
0.107
926823AC1-168 GEN
Solar/Wind Harmer
0.548
276868AE1-113 GEN
Solar/Wind Harmer
0.641
276882AE2-255 GEN
Solar/Wind Harmer
0.373
946321AF1-296 GEN
Solar/Wind Harmer
1.775
961011AF2-392 GEN
Solar/Wind Harmer
1.859
970833AG2-524 GEN
Solar/Wind Harmer
3.484
970833AG2-524 GEN
Solar/Wind Harmer
2.323
971681AH1-341 GEN
Solar/Wind Harmer
5.094
274731ELWOOD EC;2P
Adder
7.45
274733ELWOOD EC;3P
Adder
7.45
274735ELWOOD EC;4P
Adder
7.45
274728ELWOOD EC;5P
Adder
7.45
971171AH1-044 GEN
Solar/Wind Harmer
6.32
971675AH1-338 GEN
Solar/Wind Harmer
1.232
972227AH1-698 GEN1
Adder
1.181
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
8.814
960591AF2-350 GEN
Solar/Wind Harmer
3.156
274746AC1-111 G10
Adder
2.527
274744AC1-111 GEN8
Adder
2.527
274675JOLIET 29;7U
Adder
13.865
274675JOLIET 29;7U
Adder
0.85
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.209
971411AH1-196 GEN
Solar/Wind Harmer
0.519
24803106KYGER 3LP
50/50
2.428
24803306KYGER 4LP
50/50
2.378
971191AH1-055 GEN
Solar/Wind Harmer
68.522
25196608WSDLE5
Adder
8.99
25194608D.CRK4
Adder
1.724
252510AF1-249 C
Solar/Wind Harmer
0.056
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.265
25196008MFTGT1
Adder
1.357
958171AF2-111 GEN
Solar/Wind Harmer
17.326
972167AH1-666 GEN
Solar/Wind Harmer
5.211
253406AD2-031_GEN
Solar/Wind Harmer
0.471
972173AH1-669 GEN
Solar/Wind Harmer
3.114
270273AD2-016 GEN
Solar/Wind Harmer
0.618
253415AE1-040 GEN
Solar/Wind Harmer
0.002
270222AC2-111 GEN
Solar/Wind Harmer
2.968
253370AE2-315 SEC1
Adder
1.649
253371AE2-315 SEC2
Adder
1.56
970191AG2-125 GEN
Solar/Wind Harmer
1.42
3429391JKCT 9G
Adder
6.526
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970093AG2-073 GEN
Solar/Wind Harmer
4.983
270437AC2-090 C
Solar/Wind Harmer
0.002
966571AG1-526 GEN
Solar/Wind Harmer
10.726
24728705AND G3
Adder
5.44
24728505AND G1
Adder
2.601
970243AG2-164 GEN
Solar/Wind Harmer
2.75
970519AG2-331 GEN
Solar/Wind Harmer
12.22
970699AG2-449 GEN
Solar/Wind Harmer
1.175
958821AF2-173 GEN
Solar/Wind Harmer
6.381
270004AE1-209 GEN
Solar/Wind Harmer
0.988
946031AF1-268 GEN
Solar/Wind Harmer
4.297
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.485
970289AG2-191 GEN
Solar/Wind Harmer
0.462
970291AG2-192 GEN
Solar/Wind Harmer
0.42
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.094
971617AH1-308 GEN
Solar/Wind Harmer
3.288
960741AF2-365 GEN
Solar/Wind Harmer
1.942
972273AH1-721 GEN
Adder
44.027
944531AF1-118 GEN
Solar/Wind Harmer
16.271
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.627
970273AG2-179 GEN
Solar/Wind Harmer
2.166
962251AG1-071 GEN
Solar/Wind Harmer
2.234
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.144
942481AE2-261 GEN
Solar/Wind Harmer
10.562
276621W2-048 GEN
Solar/Wind Harmer
0.177
276838X2-022 GEN2
Solar/Wind Harmer
0.197
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.614
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.197
959611AF2-252 GEN
Solar/Wind Harmer
1.133
964401AG1-302 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.097
970605AG2-385 GEN
Solar/Wind Harmer
2.043
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.415
970517AG2-330 GEN
Solar/Wind Harmer
8.489
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
970571AG2-364 GEN
Solar/Wind Harmer
6.432
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.515
276694AA1-018 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.083
276893AG1-478 C
Solar/Wind Harmer
0.125
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
7.45
274730ELWOOD EC;6P
Adder
7.45
274734ELWOOD EC;8P
Adder
7.45
274736ELWOOD EC;9P
Adder
7.45
274760LEE CO EC;1U
Adder
4.217
274767LEE CO EC;8U
Adder
4.167
959091AF2-200 GEN
Solar/Wind Harmer
6.32
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
972228AH1-698 GEN2
Adder
1.677
972236AH1-702 GEN2
Adder
0.992
274872LEEDK;1U
Solar/Wind Harmer
0.116
276806AD2-047 C O1
Solar/Wind Harmer
1.788
970941AG2-585 GEN
Solar/Wind Harmer
3.945
235780M24_1
Solar/Wind Helper
1.009
24803006KYGER 3HP
50/50
4.124
24802806KYGER 2HP
50/50
4.1
24802906KYGER 2LP
50/50
2.411
252509AD1-136 GEN
Solar/Wind Harmer
0.041
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.564
252516AE2-318_GEN
Solar/Wind Harmer
5.822
25194408D.CRK1
Adder
7.931
25194508D.CRK3
Adder
1.483
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
970235AG2-159 GEN
Solar/Wind Harmer
3.857
970235AG2-159 GEN
Solar/Wind Harmer
2.213
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.547
972045AH1-571 GEN
Solar/Wind Harmer
1.239
971125AH1-004 GEN
Solar/Wind Harmer
2.32
970107AG2-081 GEN
Solar/Wind Harmer
1.74
253370AE2-315 SEC1
Adder
1.649
25322209TAIT E
Adder
7.765
25322209TAIT E
Adder
7.591
24728805RICHG1
Adder
2.942
24728905RICHG2
Adder
2.942
25326109MON D
Adder
1.02
942891AE2-308 GEN
Solar/Wind Harmer
5.216
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.205
970883AG2-550 GEN
Solar/Wind Harmer
4.71
970885AG2-551 GEN
Solar/Wind Harmer
1.57
970239AG2-162 GEN
Solar/Wind Harmer
1.175
964571AG1-320 GEN
Solar/Wind Harmer
4.203
970825AG2-519 GEN
Solar/Wind Harmer
5.003
960441AF2-335 GEN
Solar/Wind Harmer
4.491
247621Y3-024
Adder
0.153
970653AG2-424 GEN
Solar/Wind Harmer
2.124
970653AG2-424 GEN
Solar/Wind Harmer
1.101
964611AG1-324 GEN
Solar/Wind Harmer
0.327
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.178
270201AC2-176 GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
2.055
270599AE1-208 GEN
Solar/Wind Harmer
3.884
270031AE2-169
Solar/Wind Harmer
2.33
945391AF1-204 GEN
Solar/Wind Harmer
4.317
971081AG2-670 GEN
Solar/Wind Harmer
2.994
270518AE2-148 GEN
Solar/Wind Harmer
0.344
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.326
25326509SID D
Adder
0.727
970241AG2-163 GEN
Solar/Wind Harmer
2.246
942221AE2-234 GEN
Solar/Wind Harmer
0.019
966841AG1-555 GEN
Solar/Wind Harmer
0.421
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
339255AE2-071 GEN
Solar/Wind Harmer
-0.058
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.538
964781AG1-341 GEN
Solar/Wind Harmer
3.771
276916AD2-100_GEN
Solar/Wind Harmer
7.444
276911AD2-131_GEN
Solar/Wind Harmer
0.49
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970077AG2-063 GEN
Solar/Wind Harmer
1.932
971485AH1-239 GEN
Solar/Wind Harmer
2.635
970321AG2-212 GEN
Solar/Wind Harmer
1.415
966021AG1-471 GEN
Solar/Wind Harmer
1.759
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.135
958491AF2-143 GEN
Solar/Wind Harmer
4.784
276741O09 GEN1
Solar/Wind Harmer
0.113
276708O09 GEN2
Solar/Wind Harmer
0.113
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.767
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.89
938861AE1-114 GEN
Solar/Wind Harmer
1.792
274764LEE CO EC;5U
Adder
4.227
274765LEE CO EC;6U
Adder
4.227
274762LEE CO EC;3U
Adder
4.217
274763LEE CO EC;4U
Adder
4.177
971341AH1-150 GEN
Solar/Wind Harmer
6.32
971343AH1-151 GEN
Solar/Wind Harmer
6.32
274856ECOGROVE ;U1
Solar/Wind Harmer
0.075
276611AD2-172 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
6.97
971333AH1-146 GEN
Solar/Wind Harmer
6.312
971335AH1-147 GEN
Solar/Wind Harmer
6.312
274888KELLY CRK;1U
Solar/Wind Harmer
0.185
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.544
970921AG2-575 GEN
Solar/Wind Harmer
3.156
970921AG2-575 GEN
Solar/Wind Harmer
1.052
962691AG1-118 GEN
Solar/Wind Harmer
9.466
972259AH1-714 GEN
Adder
8.624
274696ROCKY RD ;4P
Adder
5.152
274695ROCKY RD ;2P
Adder
5.033
274693ROCKY RD ;1P
Adder
4.983
274697ROCKY RD ;3P
Adder
1.367
237033AB1-150 GEN
Solar/Wind Helper
0.407
944201AF1-088_MTX
Adder
72.238
957141AF2-008_MTX
Adder
36.119
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.499
LAGNLTFEXP_LAGN->PJM
CLTF
6.342
TVALTFEXP_TVA->PJM
CLTF
3.038
NYPJM->LTFIMP_NY
CLTF
1.588
LGEELTFEXP_LGEE->PJM
CLTF
5.37
WECLTFEXP_WEC->PJM
CLTF
1.725
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.313
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.642
MECLTFEXP_MEC->PJM
CLTF
7.485
SIGELTFEXP_SIGE->PJM
CLTF
0.339

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-2


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.53 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2040.89
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.109
24803206KYGER 4HP
50/50
4.105
252507AC2-088 GEN
Solar/Wind Harmer
2.066
25196808ZIMRHP
Adder
80.558
25194608D.CRK4
Adder
1.715
253432AC1-085 GEN2
Solar/Wind Harmer
0.274
946171AF1-282 GEN
Solar/Wind Harmer
10.233
25196008MFTGT1
Adder
1.383
24803006KYGER 3HP
50/50
4.155
24802806KYGER 2HP
50/50
4.131
24802906KYGER 2LP
50/50
2.429
252509AD1-136 GEN
Solar/Wind Harmer
0.295
25183208HLCRTG
Solar/Wind Harmer
6.619
252519AF1-045_GEN
Solar/Wind Harmer
6.537
252516AE2-318_GEN
Solar/Wind Harmer
4.987
25194408D.CRK1
Adder
7.888
25194508D.CRK3
Adder
1.475
253317AC1-085 GEN4
Solar/Wind Harmer
8.572
253394AE2-221_GEN
Solar/Wind Harmer
4.381
253398AE2-221_GEN2
Solar/Wind Harmer
4.381
270186AC1-089 GEN
Solar/Wind Harmer
5.492
962581AG1-107 GEN
Solar/Wind Harmer
4.472
961491AF2-440 GEN
Solar/Wind Harmer
1.858
970235AG2-159 GEN
Solar/Wind Harmer
3.517
970235AG2-159 GEN
Solar/Wind Harmer
2.147
339221AD2-048_GEN
Solar/Wind Harmer
1.329
972043AH1-570 GEN
Solar/Wind Harmer
2.107
972045AH1-571 GEN
Solar/Wind Harmer
1.685
253370AE2-315 SEC1
Adder
1.644
971125AH1-004 GEN
Solar/Wind Harmer
3.274
970107AG2-081 GEN
Solar/Wind Harmer
2.456
24379505HDWTR1G C
Solar/Wind Harmer
6.316
270209AC1-174_GEN
Solar/Wind Harmer
4.458
926881AC1-175 GEN
Solar/Wind Harmer
4.458
24728805RICHG1
Adder
3.015
24728905RICHG2
Adder
3.015
25322209TAIT E
Adder
7.731
25322209TAIT E
Adder
7.557
25326109MON D
Adder
1.013
944541AF1-119 GEN
Solar/Wind Harmer
3.193
960971AF2-388 GEN
Solar/Wind Harmer
8.332
270383AD1-128 GEN
Solar/Wind Harmer
4.617
942891AE2-308 GEN
Solar/Wind Harmer
7.358
970825AG2-519 GEN
Solar/Wind Harmer
7.45
970883AG2-550 GEN
Solar/Wind Harmer
6.99
970885AG2-551 GEN
Solar/Wind Harmer
1.626
960161AF2-307 GEN
Solar/Wind Harmer
4.476
960441AF2-335 GEN
Solar/Wind Harmer
6.95
964611AG1-324 GEN
Solar/Wind Harmer
0.778
964611AG1-324 GEN
Solar/Wind Harmer
0.345
247621Y3-024
Adder
0.158
270201AC2-176 GEN
Solar/Wind Harmer
3.324
964571AG1-320 GEN
Solar/Wind Harmer
5.12
270599AE1-208 GEN
Solar/Wind Harmer
5.076
270031AE2-169
Solar/Wind Harmer
5.076
970653AG2-424 GEN
Solar/Wind Harmer
2.899
970653AG2-424 GEN
Solar/Wind Harmer
1.048
270518AE2-148 GEN
Solar/Wind Harmer
6.898
971081AG2-670 GEN
Solar/Wind Harmer
4.12
25326509SID D
Adder
0.706
339236AF1-050_GEN
Solar/Wind Harmer
0.956
270444AC2-157 GEN1
Solar/Wind Harmer
2.925
970239AG2-162 GEN
Solar/Wind Harmer
5.617
945391AF1-204 GEN
Solar/Wind Harmer
7.082
942221AE2-234 GEN
Solar/Wind Harmer
0.37
339231AF1-038_GEN
Solar/Wind Harmer
0.913
253378AE2-206_GEN
Solar/Wind Harmer
1.776
276820AF1-078_GEN
Solar/Wind Harmer
0.789
339255AE2-071 GEN
Solar/Wind Harmer
0.518
964781AG1-341 GEN
Solar/Wind Harmer
5.161
970077AG2-063 GEN
Solar/Wind Harmer
2.579
970241AG2-163 GEN
Solar/Wind Harmer
11.618
971485AH1-239 GEN
Solar/Wind Harmer
3.655
966021AG1-471 GEN
Solar/Wind Harmer
2.445
237033AB1-150 GEN
Solar/Wind Helper
0.37
24803106KYGER 3LP
50/50
2.446
24803306KYGER 4LP
50/50
2.395
971191AH1-055 GEN
Solar/Wind Harmer
85.07
25194608D.CRK4
Adder
1.715
25196608WSDLE5
Adder
8.935
252510AF1-249 C
Solar/Wind Harmer
0.435
253316AC1-085 GEN3
Solar/Wind Harmer
8.572
253433AC1-085 GEN1
Solar/Wind Harmer
5.441
946181AF1-283 GEN
Solar/Wind Harmer
13.303
25196008MFTGT1
Adder
1.339
958171AF2-111 GEN
Solar/Wind Harmer
24.764
972167AH1-666 GEN
Solar/Wind Harmer
7.466
972173AH1-669 GEN
Solar/Wind Harmer
4.568
253406AD2-031_GEN
Solar/Wind Harmer
1.163
270273AD2-016 GEN
Solar/Wind Harmer
2.331
253415AE1-040 GEN
Solar/Wind Harmer
0.967
270222AC2-111 GEN
Solar/Wind Harmer
6.971
253303V4-073 C
Solar/Wind Harmer
0.095
253370AE2-315 SEC1
Adder
1.644
253371AE2-315 SEC2
Adder
1.555
270437AC2-090 C
Solar/Wind Harmer
4.46
270356AE2-297 GEN
Solar/Wind Harmer
3.532
3429391JKCT 9G
Adder
6.432
944531AF1-118 GEN
Solar/Wind Harmer
26.698
958821AF2-173 GEN
Solar/Wind Harmer
10.658
270004AE1-209 GEN
Solar/Wind Harmer
4.16
946031AF1-268 GEN
Solar/Wind Harmer
5.902
970093AG2-073 GEN
Solar/Wind Harmer
7.027
966571AG1-526 GEN
Solar/Wind Harmer
15.01
24728705AND G3
Adder
5.414
24728505AND G1
Adder
2.589
962031AG1-047 GEN
Solar/Wind Harmer
1.954
957741AF2-068 GEN
Solar/Wind Harmer
9.698
253338AC1-165 GEN
Solar/Wind Harmer
0.683
253333AC1-068 GEN
Solar/Wind Harmer
0.659
970289AG2-191 GEN
Solar/Wind Harmer
0.453
970291AG2-192 GEN
Solar/Wind Harmer
0.412
247642Z2-115 C
Solar/Wind Harmer
0.036
971617AH1-308 GEN
Solar/Wind Harmer
3.252
960741AF2-365 GEN
Solar/Wind Harmer
2.649
972273AH1-721 GEN
Adder
43.057
970243AG2-164 GEN
Solar/Wind Harmer
13.187
970519AG2-331 GEN
Solar/Wind Harmer
8.86
970699AG2-449 GEN
Solar/Wind Harmer
5.861
970193AG2-126 GEN
Solar/Wind Harmer
7.623
970273AG2-179 GEN
Solar/Wind Harmer
1.955
339250AF1-203 GEN
Solar/Wind Harmer
0.296
962251AG1-071 GEN
Solar/Wind Harmer
2.687
971155AH1-034 GEN
Solar/Wind Harmer
4.865
970605AG2-385 GEN
Solar/Wind Harmer
2.579
24802606KYGER 1HP
50/50
4.179
24802706KYGER 1LP
50/50
2.453
24803506KYGER 5LP
50/50
2.395
25016408BKJDB1
50/50
0.279
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
49.909
252524AE2-267 GEN
Solar/Wind Harmer
1.644
25196408WSDLE3
Adder
9.197
25196308WSDLE2
Adder
9.117
25196208WSDLE1
Adder
9.094
25196708WSDLE6
Adder
9.072
25196508WSDLE4
Adder
8.843
25196108MFTGT2
Adder
1.524
25196108MFTGT2
Adder
1.415
972163AH1-664 GEN
Solar/Wind Harmer
9.19
972165AH1-665 GEN
Solar/Wind Harmer
7.352
270367AC2-061_GEN
Solar/Wind Harmer
2.901
270340AC2-060 GEN
Solar/Wind Harmer
2.67
339243AC2-075 GEN1
Solar/Wind Harmer
0.4
270269AC2-059
Solar/Wind Harmer
8.152
944031AF1-071 GEN
Solar/Wind Harmer
0.859
253372AE2-315 SEC3
Adder
1.555
253372AE2-315 SEC3
Adder
1.555
25306009OHH W.
Adder
2.33
270240V3-007_GEN2
Solar/Wind Harmer
4.942
253349AC2-067 GEN
Solar/Wind Harmer
3.944
253400AC2-068 GEN
Solar/Wind Harmer
1.586
970689AG2-444 GEN
Solar/Wind Harmer
12.539
24729505KEY G4
Adder
4.948
958711AF2-162 GEN
Solar/Wind Harmer
0.771
965101AG1-375 GEN
Solar/Wind Harmer
7.621
945581AF1-223 GEN
Solar/Wind Harmer
3.455
3429211JKCT 2G
Adder
8.768
971673AH1-337 GEN
Solar/Wind Harmer
3.371
971029AG2-637 GEN
Solar/Wind Harmer
10.87
270543AE2-219 C
Solar/Wind Harmer
3.579
970115AG2-085 GEN
Solar/Wind Harmer
2.78
270432AC2-029 GEN
Solar/Wind Harmer
4.836
241972AD1-140 GEN
Solar/Wind Harmer
2.98
339211AE2-254 GEN
Solar/Wind Harmer
0.982
961761AG1-017 GEN
Solar/Wind Harmer
0.277
970455AG2-298 GEN
Solar/Wind Harmer
3.86
24725505WLD G2 C
Solar/Wind Harmer
2.558
24699105WLD G1 C
Solar/Wind Harmer
2.528
270594AE1-207 GEN
Solar/Wind Harmer
9.141
965461AG1-414 GEN
Solar/Wind Harmer
1.338
970289AG2-191 GEN
Solar/Wind Harmer
1.121
270024AE2-089 GEN
Solar/Wind Harmer
2.625
965401AG1-405 GEN
Solar/Wind Harmer
3.173
965411AG1-406 GEN
Solar/Wind Harmer
1.424
270156DARBY CT1
Adder
4.477
270157DARBY CT2
Adder
4.466
270158DARBY CT3
Adder
4.395
945631AF1-228 GEN
Solar/Wind Harmer
2.242
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.198
963841AG1-237 GEN
Solar/Wind Harmer
4.069
235780M24_1
Solar/Wind Helper
0.918
945681AF1-233 GEN
Solar/Wind Harmer
17.522
339216AC1-074 GEN
Solar/Wind Harmer
1.477
270263AC1-001 GEN
Solar/Wind Harmer
0.913
253370AE2-315 SEC1
Adder
1.644
253371AE2-315 SEC2
Adder
1.555
943111AE2-339 GEN
Solar/Wind Harmer
0.71
942081AE2-220 GEN
Solar/Wind Harmer
5.107
270239V3-007_GEN1
Solar/Wind Harmer
1.375
25326309TAIT D
Adder
0.868
960071AF2-298 GEN
Solar/Wind Harmer
3.915
3429421JKCT 10G
Adder
6.432
965651AG1-433 GEN
Solar/Wind Harmer
4.166
958861AF2-177 GEN
Solar/Wind Harmer
8.33
945371AF1-202 GEN
Solar/Wind Harmer
5.316
270005AE1-210 C O1
Solar/Wind Harmer
4.16
965031AG1-367 GEN
Solar/Wind Harmer
7.613
3429241JKCT 3G
Adder
8.883
970825AG2-519 GEN
Solar/Wind Harmer
1.662
24728605AND G2
Adder
2.589
247536S-71 GEN
Solar/Wind Harmer
2.729
971565AH1-281 GEN
Solar/Wind Harmer
1.327
971821AH1-427 GEN
Solar/Wind Harmer
6.372
253343AC1-166 GEN
Solar/Wind Harmer
0.683
253325AC1-069 GEN
Solar/Wind Harmer
0.659
276903AD2-071 C
Solar/Wind Harmer
6.244
270032AE2-172
Solar/Wind Harmer
2.893
970291AG2-192 GEN
Solar/Wind Harmer
0.767
339241AF1-083 GEN
Solar/Wind Harmer
0.928
970091AG2-072 GEN
Adder
41.592
270445AC2-157 GEN2
Solar/Wind Harmer
2.925
970333AG2-219 GEN
Solar/Wind Harmer
16.118
964901AG1-354 GEN
Solar/Wind Harmer
7.649
970273AG2-179 GEN
Solar/Wind Harmer
1.224
270159DARBY CT4
Adder
4.406
962241AG1-070 GEN
Solar/Wind Harmer
2.198
970593AG2-378 GEN
Solar/Wind Harmer
0.955
963741AG1-226 GEN
Solar/Wind Harmer
20.913
960001AF2-291 GEN
Solar/Wind Helper
1.675
270331AC1-082 GEN3
Solar/Wind Helper
0.197
944201AF1-088_MTX
Adder
60.901
957141AF2-008_MTX
Adder
30.451
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.273
LAGNLTFEXP_LAGN->PJM
CLTF
5.86
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.127
TVALTFEXP_TVA->PJM
CLTF
2.893
NYPJM->LTFIMP_NY
CLTF
1.454
LGEELTFEXP_LGEE->PJM
CLTF
5.045
WECLTFEXP_WEC->PJM
CLTF
1.402
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.188
AG2-052LTFEXP_AG2-052->PJM
LTF
0.091
AH1-155LTFEXP_AH1-155->PJM
LTF
0.136
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.877
MECLTFEXP_MEC->PJM
CLTF
6.307
SIGELTFEXP_SIGE->PJM
CLTF
0.315

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P7-1_#10941___SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10941___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.04 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2033.36
MW Contribution:0.92
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.177
24802806KYGER 2HP
50/50
4.153
24802906KYGER 2LP
50/50
2.442
252509AD1-136 GEN
Solar/Wind Harmer
0.291
25183208HLCRTG
Solar/Wind Harmer
6.54
252519AF1-045_GEN
Solar/Wind Harmer
6.388
252516AE2-318_GEN
Solar/Wind Harmer
4.873
253317AC1-085 GEN4
Solar/Wind Harmer
8.528
25194408D.CRK1
Adder
7.67
25194508D.CRK3
Adder
1.434
253394AE2-221_GEN
Solar/Wind Harmer
4.329
253398AE2-221_GEN2
Solar/Wind Harmer
4.329
970235AG2-159 GEN
Solar/Wind Harmer
3.451
970235AG2-159 GEN
Solar/Wind Harmer
2.107
339221AD2-048_GEN
Solar/Wind Harmer
1.293
972043AH1-570 GEN
Solar/Wind Harmer
2.047
972045AH1-571 GEN
Solar/Wind Harmer
1.637
971125AH1-004 GEN
Solar/Wind Harmer
3.218
970107AG2-081 GEN
Solar/Wind Harmer
2.413
253370AE2-315 SEC1
Adder
1.565
25322209TAIT E
Adder
7.402
25322209TAIT E
Adder
7.235
25326109MON D
Adder
0.982
24728805RICHG1
Adder
2.755
24728905RICHG2
Adder
2.755
942891AE2-308 GEN
Solar/Wind Harmer
7.206
270186AC1-089 GEN
Solar/Wind Harmer
4.174
960161AF2-307 GEN
Solar/Wind Harmer
4.298
24379505HDWTR1G C
Solar/Wind Harmer
5.205
270209AC1-174_GEN
Solar/Wind Harmer
3.673
926881AC1-175 GEN
Solar/Wind Harmer
3.673
962581AG1-107 GEN
Solar/Wind Harmer
3.299
961491AF2-440 GEN
Solar/Wind Harmer
1.371
270383AD1-128 GEN
Solar/Wind Harmer
3.947
970883AG2-550 GEN
Solar/Wind Harmer
6.258
970885AG2-551 GEN
Solar/Wind Harmer
1.455
964571AG1-320 GEN
Solar/Wind Harmer
5.009
970825AG2-519 GEN
Solar/Wind Harmer
6.251
960441AF2-335 GEN
Solar/Wind Harmer
5.886
970653AG2-424 GEN
Solar/Wind Harmer
2.837
970653AG2-424 GEN
Solar/Wind Harmer
1.026
247621Y3-024
Adder
0.141
964611AG1-324 GEN
Solar/Wind Harmer
0.677
964611AG1-324 GEN
Solar/Wind Harmer
0.3
270201AC2-176 GEN
Solar/Wind Harmer
2.925
270518AE2-148 GEN
Solar/Wind Harmer
6.682
270599AE1-208 GEN
Solar/Wind Harmer
4.499
270031AE2-169
Solar/Wind Harmer
4.499
971081AG2-670 GEN
Solar/Wind Harmer
4.033
25326509SID D
Adder
0.693
970239AG2-162 GEN
Solar/Wind Harmer
5.724
270444AC2-157 GEN1
Solar/Wind Harmer
2.902
339236AF1-050_GEN
Solar/Wind Harmer
0.936
944541AF1-119 GEN
Solar/Wind Harmer
2.16
960971AF2-388 GEN
Solar/Wind Harmer
5.637
945391AF1-204 GEN
Solar/Wind Harmer
6.995
339231AF1-038_GEN
Solar/Wind Harmer
0.894
253378AE2-206_GEN
Solar/Wind Harmer
1.749
276820AF1-078_GEN
Solar/Wind Harmer
0.777
942221AE2-234 GEN
Solar/Wind Harmer
0.355
339255AE2-071 GEN
Solar/Wind Harmer
0.507
964781AG1-341 GEN
Solar/Wind Harmer
5.055
970241AG2-163 GEN
Solar/Wind Harmer
11.74
970077AG2-063 GEN
Solar/Wind Harmer
2.49
237033AB1-150 GEN
Solar/Wind Helper
0.373
24802606KYGER 1HP
50/50
4.202
24802706KYGER 1LP
50/50
2.466
24803506KYGER 5LP
50/50
2.408
25016408BKJDB1
50/50
0.277
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
50.147
252524AE2-267 GEN
Solar/Wind Harmer
1.606
25196408WSDLE3
Adder
8.983
25196308WSDLE2
Adder
8.905
25196208WSDLE1
Adder
8.883
25196708WSDLE6
Adder
8.86
25196508WSDLE4
Adder
8.637
25196108MFTGT2
Adder
1.486
25196108MFTGT2
Adder
1.38
972163AH1-664 GEN
Solar/Wind Harmer
8.96
972165AH1-665 GEN
Solar/Wind Harmer
7.168
339243AC2-075 GEN1
Solar/Wind Harmer
0.393
944031AF1-071 GEN
Solar/Wind Harmer
0.798
253372AE2-315 SEC3
Adder
1.48
253372AE2-315 SEC3
Adder
1.48
25306009OHH W.
Adder
2.197
970689AG2-444 GEN
Solar/Wind Harmer
12.425
270269AC2-059
Solar/Wind Harmer
7.038
253349AC2-067 GEN
Solar/Wind Harmer
3.728
253400AC2-068 GEN
Solar/Wind Harmer
1.499
3429211JKCT 2G
Adder
8.608
270340AC2-060 GEN
Solar/Wind Harmer
2.169
270367AC2-061_GEN
Solar/Wind Harmer
2.146
971673AH1-337 GEN
Solar/Wind Harmer
3.046
270240V3-007_GEN2
Solar/Wind Harmer
4.072
971029AG2-637 GEN
Solar/Wind Harmer
9.794
241972AD1-140 GEN
Solar/Wind Harmer
2.89
339211AE2-254 GEN
Solar/Wind Harmer
0.961
970455AG2-298 GEN
Solar/Wind Harmer
3.778
270543AE2-219 C
Solar/Wind Harmer
3.204
970115AG2-085 GEN
Solar/Wind Harmer
2.354
24725505WLD G2 C
Solar/Wind Harmer
2.286
24699105WLD G1 C
Solar/Wind Harmer
2.259
961761AG1-017 GEN
Solar/Wind Harmer
0.244
270432AC2-029 GEN
Solar/Wind Harmer
3.871
270594AE1-207 GEN
Solar/Wind Harmer
8.077
945581AF1-223 GEN
Solar/Wind Harmer
2.49
965401AG1-405 GEN
Solar/Wind Harmer
3.103
965411AG1-406 GEN
Solar/Wind Harmer
1.393
965461AG1-414 GEN
Solar/Wind Harmer
1.211
970289AG2-191 GEN
Solar/Wind Harmer
1.015
965101AG1-375 GEN
Solar/Wind Harmer
5.271
958711AF2-162 GEN
Solar/Wind Harmer
0.522
270024AE2-089 GEN
Solar/Wind Harmer
2.418
270156DARBY CT1
Adder
4.342
270157DARBY CT2
Adder
4.331
270158DARBY CT3
Adder
4.262
24729505KEY G4
Adder
3.119
945631AF1-228 GEN
Solar/Wind Harmer
2.16
963841AG1-237 GEN
Solar/Wind Harmer
5.029
270330AC1-082 GEN2
Solar/Wind Helper
0.046
270329AC1-082 GEN1
Solar/Wind Helper
0.224
24386205FR-12G C
Solar/Wind Harmer
0.731
24386405FR-21G C
Solar/Wind Harmer
0.734
24386605FR-22G C
Solar/Wind Harmer
0.734
24387005FR-3G C
Solar/Wind Harmer
0.675
24803106KYGER 3LP
50/50
2.459
24803306KYGER 4LP
50/50
2.408
971191AH1-055 GEN
Solar/Wind Harmer
86.579
25196608WSDLE5
Adder
8.727
253316AC1-085 GEN3
Solar/Wind Harmer
8.528
253433AC1-085 GEN1
Solar/Wind Harmer
5.413
946181AF1-283 GEN
Solar/Wind Harmer
13.235
25194608D.CRK4
Adder
1.667
252510AF1-249 C
Solar/Wind Harmer
0.419
958171AF2-111 GEN
Solar/Wind Harmer
24.596
25196008MFTGT1
Adder
1.306
972167AH1-666 GEN
Solar/Wind Harmer
7.298
253406AD2-031_GEN
Solar/Wind Harmer
1.023
972173AH1-669 GEN
Solar/Wind Harmer
3.991
270222AC2-111 GEN
Solar/Wind Harmer
6.471
253303V4-073 C
Solar/Wind Harmer
0.091
253370AE2-315 SEC1
Adder
1.565
253371AE2-315 SEC2
Adder
1.48
3429391JKCT 9G
Adder
6.329
270273AD2-016 GEN
Solar/Wind Harmer
2.013
253415AE1-040 GEN
Solar/Wind Harmer
0.808
270356AE2-297 GEN
Solar/Wind Harmer
3.191
970093AG2-073 GEN
Solar/Wind Harmer
6.876
966571AG1-526 GEN
Solar/Wind Harmer
14.719
270437AC2-090 C
Solar/Wind Harmer
3.675
24728705AND G3
Adder
4.936
24728505AND G1
Adder
2.36
253338AC1-165 GEN
Solar/Wind Harmer
0.656
253333AC1-068 GEN
Solar/Wind Harmer
0.632
958821AF2-173 GEN
Solar/Wind Harmer
8.401
270004AE1-209 GEN
Solar/Wind Harmer
3.279
946031AF1-268 GEN
Solar/Wind Harmer
4.93
962031AG1-047 GEN
Solar/Wind Harmer
1.72
957741AF2-068 GEN
Solar/Wind Harmer
8.534
970289AG2-191 GEN
Solar/Wind Harmer
0.41
970291AG2-192 GEN
Solar/Wind Harmer
0.373
970243AG2-164 GEN
Solar/Wind Harmer
13.439
970519AG2-331 GEN
Solar/Wind Harmer
9.029
970699AG2-449 GEN
Solar/Wind Harmer
5.973
247642Z2-115 C
Solar/Wind Harmer
0.033
960741AF2-365 GEN
Solar/Wind Harmer
2.594
971617AH1-308 GEN
Solar/Wind Harmer
2.995
972273AH1-721 GEN
Adder
42.117
970193AG2-126 GEN
Solar/Wind Harmer
7.529
970273AG2-179 GEN
Solar/Wind Harmer
1.914
339250AF1-203 GEN
Solar/Wind Harmer
0.29
962251AG1-071 GEN
Solar/Wind Harmer
2.632
971155AH1-034 GEN
Solar/Wind Harmer
4.765
944531AF1-118 GEN
Solar/Wind Harmer
16.385
970605AG2-385 GEN
Solar/Wind Harmer
2.49
957541AF2-048 GEN
Solar/Wind Helper
0.913
235780M24_1
Solar/Wind Helper
0.925
24803406KYGER 5HP
50/50
4.131
24803206KYGER 4HP
50/50
4.127
252507AC2-088 GEN
Solar/Wind Harmer
2.037
25196808ZIMRHP
Adder
79.49
253432AC1-085 GEN2
Solar/Wind Harmer
0.273
946171AF1-282 GEN
Solar/Wind Harmer
10.181
25194608D.CRK4
Adder
1.667
25196008MFTGT1
Adder
1.348
945681AF1-233 GEN
Solar/Wind Harmer
17.118
339216AC1-074 GEN
Solar/Wind Harmer
1.453
943111AE2-339 GEN
Solar/Wind Harmer
0.698
253370AE2-315 SEC1
Adder
1.565
253371AE2-315 SEC2
Adder
1.48
3429421JKCT 10G
Adder
6.329
25326309TAIT D
Adder
0.831
960071AF2-298 GEN
Solar/Wind Harmer
3.733
3429241JKCT 3G
Adder
8.721
942081AE2-220 GEN
Solar/Wind Harmer
4.208
270239V3-007_GEN1
Solar/Wind Harmer
1.133
971565AH1-281 GEN
Solar/Wind Harmer
1.299
971821AH1-427 GEN
Solar/Wind Harmer
6.238
24728605AND G2
Adder
2.36
253343AC1-166 GEN
Solar/Wind Harmer
0.656
253325AC1-069 GEN
Solar/Wind Harmer
0.632
247536S-71 GEN
Solar/Wind Harmer
2.43
270005AE1-210 C O1
Solar/Wind Harmer
3.279
965031AG1-367 GEN
Solar/Wind Harmer
6.001
970825AG2-519 GEN
Solar/Wind Harmer
1.395
270263AC1-001 GEN
Solar/Wind Harmer
0.608
276903AD2-071 C
Solar/Wind Harmer
5.623
270032AE2-172
Solar/Wind Harmer
2.556
945371AF1-202 GEN
Solar/Wind Harmer
3.83
339241AF1-083 GEN
Solar/Wind Harmer
0.908
970091AG2-072 GEN
Adder
41.703
970291AG2-192 GEN
Solar/Wind Harmer
0.695
958861AF2-177 GEN
Solar/Wind Harmer
5.762
970333AG2-219 GEN
Solar/Wind Harmer
16.425
270445AC2-157 GEN2
Solar/Wind Harmer
2.902
965651AG1-433 GEN
Solar/Wind Harmer
2.818
964901AG1-354 GEN
Solar/Wind Harmer
7.49
970273AG2-179 GEN
Solar/Wind Harmer
1.198
270159DARBY CT4
Adder
4.272
962241AG1-070 GEN
Solar/Wind Harmer
2.153
963741AG1-226 GEN
Solar/Wind Harmer
21.132
970593AG2-378 GEN
Solar/Wind Harmer
0.922
960001AF2-291 GEN
Solar/Wind Helper
1.762
270331AC1-082 GEN3
Solar/Wind Helper
0.223
927014AC1-188 GEN
Solar/Wind Helper
0.91
24385905FR-11G C
Solar/Wind Harmer
1.419
24387305FR-4G C
Solar/Wind Harmer
0.867
944201AF1-088_MTX
Adder
60.434
957141AF2-008_MTX
Adder
30.217
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.604
LAGNLTFEXP_LAGN->PJM
CLTF
5.827
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.06
TVALTFEXP_TVA->PJM
CLTF
2.85
NYPJM->LTFIMP_NY
CLTF
1.459
LGEELTFEXP_LGEE->PJM
CLTF
4.943
WECLTFEXP_WEC->PJM
CLTF
1.478
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.202
AG2-052LTFEXP_AG2-052->PJM
LTF
0.095
AH1-155LTFEXP_AH1-155->PJM
LTF
0.143
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.413
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.644
MECLTFEXP_MEC->PJM
CLTF
6.5
SIGELTFEXP_SIGE->PJM
CLTF
0.306

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1566.09
MW Contribution:0.73
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.149
24802806KYGER 2HP
50/50
4.125
24802906KYGER 2LP
50/50
2.425
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
24802606KYGER 1HP
50/50
4.173
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
25016408BKJDB1
50/50
0.272
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.759
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.879
25196308WSDLE2
Adder
8.801
25196208WSDLE1
Adder
8.779
25196708WSDLE6
Adder
8.757
25196508WSDLE4
Adder
8.537
25196108MFTGT2
Adder
1.463
25196108MFTGT2
Adder
1.358
972163AH1-664 GEN
Solar/Wind Harmer
6.955
972165AH1-665 GEN
Solar/Wind Harmer
5.57
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.003
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.506
253372AE2-315 SEC3
Adder
1.506
25306009OHH W.
Adder
2.247
970689AG2-444 GEN
Solar/Wind Harmer
10.893
253349AC2-067 GEN
Solar/Wind Harmer
1.665
253400AC2-068 GEN
Solar/Wind Harmer
0.67
3429211JKCT 2G
Adder
8.494
270432AC2-029 GEN
Solar/Wind Harmer
2.121
971673AH1-337 GEN
Solar/Wind Harmer
2.979
241972AD1-140 GEN
Solar/Wind Harmer
0.495
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
6.776
339211AE2-254 GEN
Solar/Wind Harmer
0.002
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
2.878
970115AG2-085 GEN
Solar/Wind Harmer
1.619
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.62
270594AE1-207 GEN
Solar/Wind Harmer
4.227
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.132
965411AG1-406 GEN
Solar/Wind Harmer
1.371
970289AG2-191 GEN
Solar/Wind Harmer
0.697
965101AG1-375 GEN
Solar/Wind Harmer
3.623
270024AE2-089 GEN
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
4.415
270157DARBY CT2
Adder
4.404
270158DARBY CT3
Adder
4.334
24729505KEY G4
Adder
3.073
945631AF1-228 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.363
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
1.779
943861AF1-054 GEN
Solar/Wind Harmer
1.158
943851AF1-053 GEN
Solar/Wind Harmer
0.802
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
69.07
25194608D.CRK4
Adder
1.656
25196608WSDLE5
Adder
8.625
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.086
958171AF2-111 GEN
Solar/Wind Harmer
16.854
25196008MFTGT1
Adder
1.285
972167AH1-666 GEN
Solar/Wind Harmer
5.077
972173AH1-669 GEN
Solar/Wind Harmer
3.165
253406AD2-031_GEN
Solar/Wind Harmer
0.462
270273AD2-016 GEN
Solar/Wind Harmer
0.628
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
270222AC2-111 GEN
Solar/Wind Harmer
2.79
970191AG2-125 GEN
Solar/Wind Harmer
1.36
3429391JKCT 9G
Adder
6.235
270356AE2-297 GEN
Solar/Wind Harmer
0.006
970093AG2-073 GEN
Solar/Wind Harmer
4.742
966571AG1-526 GEN
Solar/Wind Harmer
10.106
270437AC2-090 C
Solar/Wind Harmer
0.002
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
24728705AND G3
Adder
4.853
24728505AND G1
Adder
2.32
958821AF2-173 GEN
Solar/Wind Harmer
5.771
270004AE1-209 GEN
Solar/Wind Harmer
0.893
946031AF1-268 GEN
Solar/Wind Harmer
3.889
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.885
970289AG2-191 GEN
Solar/Wind Harmer
0.403
970291AG2-192 GEN
Solar/Wind Harmer
0.367
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
2.961
960741AF2-365 GEN
Solar/Wind Harmer
1.775
970243AG2-164 GEN
Solar/Wind Harmer
2.07
970519AG2-331 GEN
Solar/Wind Harmer
9.199
970699AG2-449 GEN
Solar/Wind Harmer
0.884
972273AH1-721 GEN
Adder
41.409
970193AG2-126 GEN
Solar/Wind Harmer
5.147
970273AG2-179 GEN
Solar/Wind Harmer
2.017
339250AF1-203 GEN
Solar/Wind Harmer
0
962251AG1-071 GEN
Solar/Wind Harmer
2.045
970605AG2-385 GEN
Solar/Wind Harmer
1.988
971155AH1-034 GEN
Solar/Wind Harmer
3.802
944531AF1-118 GEN
Solar/Wind Harmer
14.426
235780M24_1
Solar/Wind Helper
0.923
252519AF1-045_GEN
Solar/Wind Harmer
6.35
252516AE2-318_GEN
Solar/Wind Harmer
5.632
25194408D.CRK1
Adder
7.616
25194508D.CRK3
Adder
1.424
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.484
972045AH1-571 GEN
Solar/Wind Harmer
1.189
253370AE2-315 SEC1
Adder
1.592
971125AH1-004 GEN
Solar/Wind Harmer
2.215
970107AG2-081 GEN
Solar/Wind Harmer
1.662
25322209TAIT E
Adder
7.486
25322209TAIT E
Adder
7.317
25326109MON D
Adder
0.984
24728805RICHG1
Adder
2.73
24728905RICHG2
Adder
2.73
942891AE2-308 GEN
Solar/Wind Harmer
4.97
960161AF2-307 GEN
Solar/Wind Harmer
3.112
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.325
970885AG2-551 GEN
Solar/Wind Harmer
1.442
964571AG1-320 GEN
Solar/Wind Harmer
3.821
970825AG2-519 GEN
Solar/Wind Harmer
4.514
960441AF2-335 GEN
Solar/Wind Harmer
4.047
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
1.943
970653AG2-424 GEN
Solar/Wind Harmer
1.007
964611AG1-324 GEN
Solar/Wind Harmer
0.297
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.337
270599AE1-208 GEN
Solar/Wind Harmer
3.479
270031AE2-169
Solar/Wind Harmer
2.087
971613AH1-306 GEN
Solar/Wind Harmer
1.811
971081AG2-670 GEN
Solar/Wind Harmer
2.763
25326509SID D
Adder
0.693
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.6
944541AF1-119 GEN
Solar/Wind Harmer
0.237
960971AF2-388 GEN
Solar/Wind Harmer
2.079
970239AG2-162 GEN
Solar/Wind Harmer
0.884
945391AF1-204 GEN
Solar/Wind Harmer
3.646
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.467
942221AE2-234 GEN
Solar/Wind Harmer
0.017
339255AE2-071 GEN
Solar/Wind Harmer
-0.054
970077AG2-063 GEN
Solar/Wind Harmer
1.879
964781AG1-341 GEN
Solar/Wind Harmer
3.457
970241AG2-163 GEN
Solar/Wind Harmer
1.873
966841AG1-555 GEN
Solar/Wind Harmer
0.348
971485AH1-239 GEN
Solar/Wind Harmer
2.448
966021AG1-471 GEN
Solar/Wind Harmer
1.637
942861AE2-305 GEN
Solar/Wind Harmer
2.346
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.099
252507AC2-088 GEN
Solar/Wind Harmer
0.356
25196808ZIMRHP
Adder
78.156
25194608D.CRK4
Adder
1.656
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.99
25196008MFTGT1
Adder
1.327
945681AF1-233 GEN
Solar/Wind Harmer
11.914
270263AC1-001 GEN
Solar/Wind Harmer
0.606
339216AC1-074 GEN
Solar/Wind Harmer
0.163
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
25326309TAIT D
Adder
0.84
960071AF2-298 GEN
Solar/Wind Harmer
2.635
3429421JKCT 10G
Adder
6.235
3429241JKCT 3G
Adder
8.606
970773AG2-487 GEN
Solar/Wind Harmer
0.849
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.314
971565AH1-281 GEN
Solar/Wind Harmer
0.891
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
971821AH1-427 GEN
Solar/Wind Harmer
4.286
24728605AND G2
Adder
2.32
247536S-71 GEN
Solar/Wind Harmer
0.167
270005AE1-210 C O1
Solar/Wind Harmer
0.893
965031AG1-367 GEN
Solar/Wind Harmer
4.122
970825AG2-519 GEN
Solar/Wind Harmer
1.446
276903AD2-071 C
Solar/Wind Harmer
4.31
270032AE2-172
Solar/Wind Harmer
2.516
945371AF1-202 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
40.612
970291AG2-192 GEN
Solar/Wind Harmer
0.477
958861AF2-177 GEN
Solar/Wind Harmer
1.57
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.04
970333AG2-219 GEN
Solar/Wind Harmer
2.53
270159DARBY CT4
Adder
4.344
964901AG1-354 GEN
Solar/Wind Harmer
5.126
970273AG2-179 GEN
Solar/Wind Harmer
1.177
962241AG1-070 GEN
Solar/Wind Harmer
1.783
970593AG2-378 GEN
Solar/Wind Harmer
0.735
963741AG1-226 GEN
Solar/Wind Harmer
7.599
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
59.081
957141AF2-008_MTX
Adder
29.541
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.459
LAGNLTFEXP_LAGN->PJM
CLTF
5.678
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.447
LGEELTFEXP_LGEE->PJM
CLTF
4.851
WECLTFEXP_WEC->PJM
CLTF
1.45
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.094
AH1-155LTFEXP_AH1-155->PJM
LTF
0.141
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.512
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.324
MECLTFEXP_MEC->PJM
CLTF
6.369
SIGELTFEXP_SIGE->PJM
CLTF
0.3

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.87 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2015.35
MW Contribution:0.94
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.148
24802806KYGER 2HP
50/50
4.124
24802906KYGER 2LP
50/50
2.424
252509AD1-136 GEN
Solar/Wind Harmer
0.287
25183208HLCRTG
Solar/Wind Harmer
6.445
252519AF1-045_GEN
Solar/Wind Harmer
6.343
252516AE2-318_GEN
Solar/Wind Harmer
4.838
25194408D.CRK1
Adder
7.607
25194508D.CRK3
Adder
1.422
253317AC1-085 GEN4
Solar/Wind Harmer
8.382
253394AE2-221_GEN
Solar/Wind Harmer
4.278
253398AE2-221_GEN2
Solar/Wind Harmer
4.278
270186AC1-089 GEN
Solar/Wind Harmer
5.345
962581AG1-107 GEN
Solar/Wind Harmer
4.348
961491AF2-440 GEN
Solar/Wind Harmer
1.807
970235AG2-159 GEN
Solar/Wind Harmer
3.391
970235AG2-159 GEN
Solar/Wind Harmer
2.07
339221AD2-048_GEN
Solar/Wind Harmer
1.288
972043AH1-570 GEN
Solar/Wind Harmer
2.042
972045AH1-571 GEN
Solar/Wind Harmer
1.634
253370AE2-315 SEC1
Adder
1.59
971125AH1-004 GEN
Solar/Wind Harmer
3.171
970107AG2-081 GEN
Solar/Wind Harmer
2.378
25322209TAIT E
Adder
7.474
25322209TAIT E
Adder
7.306
25326109MON D
Adder
0.983
24728805RICHG1
Adder
2.726
24728905RICHG2
Adder
2.726
942891AE2-308 GEN
Solar/Wind Harmer
7.111
960161AF2-307 GEN
Solar/Wind Harmer
4.331
24379505HDWTR1G C
Solar/Wind Harmer
5.113
270209AC1-174_GEN
Solar/Wind Harmer
3.609
926881AC1-175 GEN
Solar/Wind Harmer
3.609
270383AD1-128 GEN
Solar/Wind Harmer
3.893
970883AG2-550 GEN
Solar/Wind Harmer
6.188
970885AG2-551 GEN
Solar/Wind Harmer
1.439
964571AG1-320 GEN
Solar/Wind Harmer
4.907
970825AG2-519 GEN
Solar/Wind Harmer
6.148
960441AF2-335 GEN
Solar/Wind Harmer
5.788
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
2.78
970653AG2-424 GEN
Solar/Wind Harmer
1.005
964611AG1-324 GEN
Solar/Wind Harmer
0.667
964611AG1-324 GEN
Solar/Wind Harmer
0.296
270201AC2-176 GEN
Solar/Wind Harmer
2.885
270518AE2-148 GEN
Solar/Wind Harmer
6.747
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.098
252507AC2-088 GEN
Solar/Wind Harmer
2.011
25196808ZIMRHP
Adder
78.065
25194608D.CRK4
Adder
1.654
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
946171AF1-282 GEN
Solar/Wind Harmer
10.007
25196008MFTGT1
Adder
1.325
945681AF1-233 GEN
Solar/Wind Harmer
17.054
270263AC1-001 GEN
Solar/Wind Harmer
0.904
339216AC1-074 GEN
Solar/Wind Harmer
1.432
253370AE2-315 SEC1
Adder
1.59
253371AE2-315 SEC2
Adder
1.504
943111AE2-339 GEN
Solar/Wind Harmer
0.687
25326309TAIT D
Adder
0.839
960071AF2-298 GEN
Solar/Wind Harmer
3.776
3429421JKCT 10G
Adder
6.225
3429241JKCT 3G
Adder
8.591
942081AE2-220 GEN
Solar/Wind Harmer
4.134
270239V3-007_GEN1
Solar/Wind Harmer
1.113
971565AH1-281 GEN
Solar/Wind Harmer
1.274
253343AC1-166 GEN
Solar/Wind Harmer
0.67
253325AC1-069 GEN
Solar/Wind Harmer
0.647
971821AH1-427 GEN
Solar/Wind Harmer
6.132
24728605AND G2
Adder
2.316
247536S-71 GEN
Solar/Wind Harmer
2.401
270005AE1-210 C O1
Solar/Wind Harmer
3.222
965031AG1-367 GEN
Solar/Wind Harmer
5.896
970825AG2-519 GEN
Solar/Wind Harmer
1.372
276903AD2-071 C
Solar/Wind Harmer
5.52
270032AE2-172
Solar/Wind Harmer
2.51
945371AF1-202 GEN
Solar/Wind Harmer
3.764
339241AF1-083 GEN
Solar/Wind Harmer
0.89
970091AG2-072 GEN
Adder
40.521
970291AG2-192 GEN
Solar/Wind Harmer
0.682
958861AF2-177 GEN
Solar/Wind Harmer
5.663
270445AC2-157 GEN2
Solar/Wind Harmer
2.831
965651AG1-433 GEN
Solar/Wind Harmer
2.77
970333AG2-219 GEN
Solar/Wind Harmer
15.949
270159DARBY CT4
Adder
4.334
964901AG1-354 GEN
Solar/Wind Harmer
7.329
970273AG2-179 GEN
Solar/Wind Harmer
1.174
962241AG1-070 GEN
Solar/Wind Harmer
2.105
970593AG2-378 GEN
Solar/Wind Harmer
0.935
963741AG1-226 GEN
Solar/Wind Harmer
20.657
270599AE1-208 GEN
Solar/Wind Harmer
4.424
270031AE2-169
Solar/Wind Harmer
4.424
971081AG2-670 GEN
Solar/Wind Harmer
3.951
25326509SID D
Adder
0.691
270444AC2-157 GEN1
Solar/Wind Harmer
2.831
944541AF1-119 GEN
Solar/Wind Harmer
2.123
960971AF2-388 GEN
Solar/Wind Harmer
5.54
970239AG2-162 GEN
Solar/Wind Harmer
5.558
339236AF1-050_GEN
Solar/Wind Harmer
0.916
945391AF1-204 GEN
Solar/Wind Harmer
6.838
253378AE2-206_GEN
Solar/Wind Harmer
1.747
276820AF1-078_GEN
Solar/Wind Harmer
0.776
339231AF1-038_GEN
Solar/Wind Harmer
0.875
942221AE2-234 GEN
Solar/Wind Harmer
0.349
339255AE2-071 GEN
Solar/Wind Harmer
0.496
970077AG2-063 GEN
Solar/Wind Harmer
2.523
964781AG1-341 GEN
Solar/Wind Harmer
4.942
970241AG2-163 GEN
Solar/Wind Harmer
11.476
237033AB1-150 GEN
Solar/Wind Helper
0.373
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.448
24803506KYGER 5LP
50/50
2.391
25016408BKJDB1
50/50
0.271
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
49.503
252524AE2-267 GEN
Solar/Wind Harmer
1.585
25196408WSDLE3
Adder
8.868
25196308WSDLE2
Adder
8.791
25196208WSDLE1
Adder
8.769
25196708WSDLE6
Adder
8.747
25196508WSDLE4
Adder
8.527
25196108MFTGT2
Adder
1.461
25196108MFTGT2
Adder
1.356
972163AH1-664 GEN
Solar/Wind Harmer
8.942
972165AH1-665 GEN
Solar/Wind Harmer
7.153
270367AC2-061_GEN
Solar/Wind Harmer
2.821
270269AC2-059
Solar/Wind Harmer
8.083
270340AC2-060 GEN
Solar/Wind Harmer
2.623
339243AC2-075 GEN1
Solar/Wind Harmer
0.388
253372AE2-315 SEC3
Adder
1.504
253372AE2-315 SEC3
Adder
1.504
944031AF1-071 GEN
Solar/Wind Harmer
0.792
25306009OHH W.
Adder
2.244
970689AG2-444 GEN
Solar/Wind Harmer
12.446
253349AC2-067 GEN
Solar/Wind Harmer
3.771
253400AC2-068 GEN
Solar/Wind Harmer
1.517
3429211JKCT 2G
Adder
8.48
270432AC2-029 GEN
Solar/Wind Harmer
4.791
971673AH1-337 GEN
Solar/Wind Harmer
3.016
241972AD1-140 GEN
Solar/Wind Harmer
2.901
270240V3-007_GEN2
Solar/Wind Harmer
4.001
971029AG2-637 GEN
Solar/Wind Harmer
9.695
339211AE2-254 GEN
Solar/Wind Harmer
0.945
270543AE2-219 C
Solar/Wind Harmer
3.168
970455AG2-298 GEN
Solar/Wind Harmer
3.705
970115AG2-085 GEN
Solar/Wind Harmer
2.315
24725505WLD G2 C
Solar/Wind Harmer
2.245
24699105WLD G1 C
Solar/Wind Harmer
2.218
961761AG1-017 GEN
Solar/Wind Harmer
0.24
270594AE1-207 GEN
Solar/Wind Harmer
7.932
945581AF1-223 GEN
Solar/Wind Harmer
2.447
965401AG1-405 GEN
Solar/Wind Harmer
3.049
965411AG1-406 GEN
Solar/Wind Harmer
1.368
965461AG1-414 GEN
Solar/Wind Harmer
1.189
970289AG2-191 GEN
Solar/Wind Harmer
0.996
965101AG1-375 GEN
Solar/Wind Harmer
5.181
270024AE2-089 GEN
Solar/Wind Harmer
2.385
958711AF2-162 GEN
Solar/Wind Harmer
0.513
270156DARBY CT1
Adder
4.404
270157DARBY CT2
Adder
4.393
270158DARBY CT3
Adder
4.323
24729505KEY G4
Adder
3.066
945631AF1-228 GEN
Solar/Wind Harmer
2.201
963841AG1-237 GEN
Solar/Wind Harmer
4.916
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.2
24386205FR-12G C
Solar/Wind Harmer
0.715
24386405FR-21G C
Solar/Wind Harmer
0.718
24386605FR-22G C
Solar/Wind Harmer
0.718
24387005FR-3G C
Solar/Wind Harmer
0.66
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.199
24385905FR-11G C
Solar/Wind Harmer
1.387
24387305FR-4G C
Solar/Wind Harmer
0.848
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.391
971191AH1-055 GEN
Solar/Wind Harmer
84.832
25194608D.CRK4
Adder
1.654
25196608WSDLE5
Adder
8.615
252510AF1-249 C
Solar/Wind Harmer
0.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.382
253433AC1-085 GEN1
Solar/Wind Harmer
5.321
946181AF1-283 GEN
Solar/Wind Harmer
13.008
958171AF2-111 GEN
Solar/Wind Harmer
24.127
25196008MFTGT1
Adder
1.283
972167AH1-666 GEN
Solar/Wind Harmer
7.267
972173AH1-669 GEN
Solar/Wind Harmer
4.53
253406AD2-031_GEN
Solar/Wind Harmer
1.135
270273AD2-016 GEN
Solar/Wind Harmer
2.312
253415AE1-040 GEN
Solar/Wind Harmer
0.949
253303V4-073 C
Solar/Wind Harmer
0.092
253370AE2-315 SEC1
Adder
1.59
253371AE2-315 SEC2
Adder
1.504
270222AC2-111 GEN
Solar/Wind Harmer
6.424
3429391JKCT 9G
Adder
6.225
270356AE2-297 GEN
Solar/Wind Harmer
3.136
970093AG2-073 GEN
Solar/Wind Harmer
6.785
966571AG1-526 GEN
Solar/Wind Harmer
14.46
270437AC2-090 C
Solar/Wind Harmer
3.61
253338AC1-165 GEN
Solar/Wind Harmer
0.67
253333AC1-068 GEN
Solar/Wind Harmer
0.647
24728705AND G3
Adder
4.843
24728505AND G1
Adder
2.316
958821AF2-173 GEN
Solar/Wind Harmer
8.255
270004AE1-209 GEN
Solar/Wind Harmer
3.222
946031AF1-268 GEN
Solar/Wind Harmer
4.852
962031AG1-047 GEN
Solar/Wind Harmer
1.696
957741AF2-068 GEN
Solar/Wind Harmer
8.417
970289AG2-191 GEN
Solar/Wind Harmer
0.402
970291AG2-192 GEN
Solar/Wind Harmer
0.366
247642Z2-115 C
Solar/Wind Harmer
0.033
971617AH1-308 GEN
Solar/Wind Harmer
2.954
960741AF2-365 GEN
Solar/Wind Harmer
2.538
970243AG2-164 GEN
Solar/Wind Harmer
13.049
970519AG2-331 GEN
Solar/Wind Harmer
8.767
970699AG2-449 GEN
Solar/Wind Harmer
5.799
972273AH1-721 GEN
Adder
41.309
970193AG2-126 GEN
Solar/Wind Harmer
7.36
970273AG2-179 GEN
Solar/Wind Harmer
1.875
339250AF1-203 GEN
Solar/Wind Harmer
0.284
962251AG1-071 GEN
Solar/Wind Harmer
2.573
970605AG2-385 GEN
Solar/Wind Harmer
2.523
971155AH1-034 GEN
Solar/Wind Harmer
4.659
944531AF1-118 GEN
Solar/Wind Harmer
16.107
235780M24_1
Solar/Wind Helper
0.926
944201AF1-088_MTX
Adder
58.943
957141AF2-008_MTX
Adder
29.471
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.298
LAGNLTFEXP_LAGN->PJM
CLTF
5.654
TVALTFEXP_TVA->PJM
CLTF
2.763
NYPJM->LTFIMP_NY
CLTF
1.454
LGEELTFEXP_LGEE->PJM
CLTF
4.843
WECLTFEXP_WEC->PJM
CLTF
1.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.234
AG2-052LTFEXP_AG2-052->PJM
LTF
0.093
AH1-155LTFEXP_AH1-155->PJM
LTF
0.14
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.278
MECLTFEXP_MEC->PJM
CLTF
6.349
SIGELTFEXP_SIGE->PJM
CLTF
0.299

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#308_05CULLOD 765_1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#308_05CULLOD 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:129.85 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1999.63
MW Contribution:0.95
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.155
24802806KYGER 2HP
50/50
4.131
24802906KYGER 2LP
50/50
2.429
252509AD1-136 GEN
Solar/Wind Harmer
0.295
25183208HLCRTG
Solar/Wind Harmer
6.613
252519AF1-045_GEN
Solar/Wind Harmer
6.511
252516AE2-318_GEN
Solar/Wind Harmer
4.966
25194408D.CRK1
Adder
7.814
25194508D.CRK3
Adder
1.461
253317AC1-085 GEN4
Solar/Wind Harmer
8.597
253394AE2-221_GEN
Solar/Wind Harmer
4.388
253398AE2-221_GEN2
Solar/Wind Harmer
4.388
270186AC1-089 GEN
Solar/Wind Harmer
5.544
962581AG1-107 GEN
Solar/Wind Harmer
4.504
961491AF2-440 GEN
Solar/Wind Harmer
1.872
970235AG2-159 GEN
Solar/Wind Harmer
3.522
970235AG2-159 GEN
Solar/Wind Harmer
2.15
339221AD2-048_GEN
Solar/Wind Harmer
1.339
972043AH1-570 GEN
Solar/Wind Harmer
2.126
972045AH1-571 GEN
Solar/Wind Harmer
1.701
971125AH1-004 GEN
Solar/Wind Harmer
3.304
970107AG2-081 GEN
Solar/Wind Harmer
2.478
253370AE2-315 SEC1
Adder
1.632
25322209TAIT E
Adder
7.67
25322209TAIT E
Adder
7.497
25326109MON D
Adder
1.008
942891AE2-308 GEN
Solar/Wind Harmer
7.459
24728805RICHG1
Adder
2.819
24728905RICHG2
Adder
2.819
960161AF2-307 GEN
Solar/Wind Harmer
4.583
24379505HDWTR1G C
Solar/Wind Harmer
5.297
270209AC1-174_GEN
Solar/Wind Harmer
3.738
926881AC1-175 GEN
Solar/Wind Harmer
3.738
270383AD1-128 GEN
Solar/Wind Harmer
4.033
970883AG2-550 GEN
Solar/Wind Harmer
6.402
970885AG2-551 GEN
Solar/Wind Harmer
1.489
964571AG1-320 GEN
Solar/Wind Harmer
5.185
970653AG2-424 GEN
Solar/Wind Harmer
2.945
970653AG2-424 GEN
Solar/Wind Harmer
1.064
970825AG2-519 GEN
Solar/Wind Harmer
6.384
960441AF2-335 GEN
Solar/Wind Harmer
6.013
247621Y3-024
Adder
0.144
964611AG1-324 GEN
Solar/Wind Harmer
0.692
964611AG1-324 GEN
Solar/Wind Harmer
0.307
270201AC2-176 GEN
Solar/Wind Harmer
2.99
270518AE2-148 GEN
Solar/Wind Harmer
6.89
270599AE1-208 GEN
Solar/Wind Harmer
4.598
270031AE2-169
Solar/Wind Harmer
4.598
971081AG2-670 GEN
Solar/Wind Harmer
4.21
970239AG2-162 GEN
Solar/Wind Harmer
6.013
270444AC2-157 GEN1
Solar/Wind Harmer
3.02
339236AF1-050_GEN
Solar/Wind Harmer
0.979
25326509SID D
Adder
0.708
944541AF1-119 GEN
Solar/Wind Harmer
2.204
960971AF2-388 GEN
Solar/Wind Harmer
5.752
945391AF1-204 GEN
Solar/Wind Harmer
7.237
339231AF1-038_GEN
Solar/Wind Harmer
0.94
339255AE2-071 GEN
Solar/Wind Harmer
0.533
964781AG1-341 GEN
Solar/Wind Harmer
5.305
253378AE2-206_GEN
Solar/Wind Harmer
1.785
276820AF1-078_GEN
Solar/Wind Harmer
0.793
942221AE2-234 GEN
Solar/Wind Harmer
0.363
970241AG2-163 GEN
Solar/Wind Harmer
12.155
970077AG2-063 GEN
Solar/Wind Harmer
2.572
971485AH1-239 GEN
Solar/Wind Harmer
3.781
237033AB1-150 GEN
Solar/Wind Helper
0.388
966021AG1-471 GEN
Solar/Wind Harmer
1.628
24802606KYGER 1HP
50/50
4.179
24802706KYGER 1LP
50/50
2.453
24803506KYGER 5LP
50/50
2.395
25016408BKJDB1
50/50
0.278
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
49.916
252524AE2-267 GEN
Solar/Wind Harmer
1.628
25196408WSDLE3
Adder
9.108
25196308WSDLE2
Adder
9.029
25196208WSDLE1
Adder
9.006
25196708WSDLE6
Adder
8.984
25196508WSDLE4
Adder
8.757
25196108MFTGT2
Adder
1.505
25196108MFTGT2
Adder
1.398
972163AH1-664 GEN
Solar/Wind Harmer
9.279
972165AH1-665 GEN
Solar/Wind Harmer
7.423
270367AC2-061_GEN
Solar/Wind Harmer
2.923
270340AC2-060 GEN
Solar/Wind Harmer
2.694
339243AC2-075 GEN1
Solar/Wind Harmer
0.403
270269AC2-059
Solar/Wind Harmer
8.257
253372AE2-315 SEC3
Adder
1.544
253372AE2-315 SEC3
Adder
1.544
944031AF1-071 GEN
Solar/Wind Harmer
0.817
25306009OHH W.
Adder
2.305
970689AG2-444 GEN
Solar/Wind Harmer
12.68
253349AC2-067 GEN
Solar/Wind Harmer
3.875
253400AC2-068 GEN
Solar/Wind Harmer
1.558
3429211JKCT 2G
Adder
8.883
270432AC2-029 GEN
Solar/Wind Harmer
4.894
971673AH1-337 GEN
Solar/Wind Harmer
3.118
24803406KYGER 5HP
50/50
4.109
24803206KYGER 4HP
50/50
4.106
252507AC2-088 GEN
Solar/Wind Harmer
2.063
25196808ZIMRHP
Adder
80.243
25194608D.CRK4
Adder
1.699
253432AC1-085 GEN2
Solar/Wind Harmer
0.275
946171AF1-282 GEN
Solar/Wind Harmer
10.264
25196008MFTGT1
Adder
1.365
945681AF1-233 GEN
Solar/Wind Harmer
17.684
339216AC1-074 GEN
Solar/Wind Harmer
1.487
270263AC1-001 GEN
Solar/Wind Harmer
0.926
253370AE2-315 SEC1
Adder
1.632
253371AE2-315 SEC2
Adder
1.544
943111AE2-339 GEN
Solar/Wind Harmer
0.717
25326309TAIT D
Adder
0.861
3429421JKCT 10G
Adder
6.507
960071AF2-298 GEN
Solar/Wind Harmer
3.876
3429241JKCT 3G
Adder
9
971565AH1-281 GEN
Solar/Wind Harmer
1.343
942081AE2-220 GEN
Solar/Wind Harmer
4.283
270239V3-007_GEN1
Solar/Wind Harmer
1.153
971821AH1-427 GEN
Solar/Wind Harmer
6.483
253343AC1-166 GEN
Solar/Wind Harmer
0.685
253325AC1-069 GEN
Solar/Wind Harmer
0.661
24728605AND G2
Adder
2.418
247536S-71 GEN
Solar/Wind Harmer
2.485
270005AE1-210 C O1
Solar/Wind Harmer
3.344
965031AG1-367 GEN
Solar/Wind Harmer
6.119
970825AG2-519 GEN
Solar/Wind Harmer
1.424
276903AD2-071 C
Solar/Wind Harmer
5.761
970091AG2-072 GEN
Adder
43.741
339241AF1-083 GEN
Solar/Wind Harmer
0.947
270032AE2-172
Solar/Wind Harmer
2.619
945371AF1-202 GEN
Solar/Wind Harmer
3.908
970291AG2-192 GEN
Solar/Wind Harmer
0.712
970333AG2-219 GEN
Solar/Wind Harmer
17.254
270445AC2-157 GEN2
Solar/Wind Harmer
3.02
958861AF2-177 GEN
Solar/Wind Harmer
5.879
965651AG1-433 GEN
Solar/Wind Harmer
2.876
964901AG1-354 GEN
Solar/Wind Harmer
7.844
970273AG2-179 GEN
Solar/Wind Harmer
1.26
270159DARBY CT4
Adder
4.417
962241AG1-070 GEN
Solar/Wind Harmer
2.258
963741AG1-226 GEN
Solar/Wind Harmer
21.878
970593AG2-378 GEN
Solar/Wind Harmer
0.952
960001AF2-291 GEN
Solar/Wind Helper
1.685
270331AC1-082 GEN3
Solar/Wind Helper
0.198
24803106KYGER 3LP
50/50
2.446
24803306KYGER 4LP
50/50
2.395
971191AH1-055 GEN
Solar/Wind Harmer
85.348
25194608D.CRK4
Adder
1.699
252510AF1-249 C
Solar/Wind Harmer
0.432
25196608WSDLE5
Adder
8.848
253316AC1-085 GEN3
Solar/Wind Harmer
8.597
253433AC1-085 GEN1
Solar/Wind Harmer
5.457
946181AF1-283 GEN
Solar/Wind Harmer
13.343
958171AF2-111 GEN
Solar/Wind Harmer
24.891
25196008MFTGT1
Adder
1.322
972167AH1-666 GEN
Solar/Wind Harmer
7.534
972173AH1-669 GEN
Solar/Wind Harmer
4.627
253406AD2-031_GEN
Solar/Wind Harmer
1.167
270273AD2-016 GEN
Solar/Wind Harmer
2.361
253415AE1-040 GEN
Solar/Wind Harmer
0.974
253303V4-073 C
Solar/Wind Harmer
0.094
253370AE2-315 SEC1
Adder
1.632
253371AE2-315 SEC2
Adder
1.544
270222AC2-111 GEN
Solar/Wind Harmer
6.625
3429391JKCT 9G
Adder
6.507
970093AG2-073 GEN
Solar/Wind Harmer
7.137
270356AE2-297 GEN
Solar/Wind Harmer
3.253
966571AG1-526 GEN
Solar/Wind Harmer
15.237
270437AC2-090 C
Solar/Wind Harmer
3.74
253338AC1-165 GEN
Solar/Wind Harmer
0.685
253333AC1-068 GEN
Solar/Wind Harmer
0.661
24728705AND G3
Adder
5.058
24728505AND G1
Adder
2.418
958821AF2-173 GEN
Solar/Wind Harmer
8.567
270004AE1-209 GEN
Solar/Wind Harmer
3.344
946031AF1-268 GEN
Solar/Wind Harmer
5.034
962031AG1-047 GEN
Solar/Wind Harmer
1.758
957741AF2-068 GEN
Solar/Wind Harmer
8.723
970289AG2-191 GEN
Solar/Wind Harmer
0.421
970291AG2-192 GEN
Solar/Wind Harmer
0.382
970243AG2-164 GEN
Solar/Wind Harmer
14.117
970519AG2-331 GEN
Solar/Wind Harmer
9.484
970699AG2-449 GEN
Solar/Wind Harmer
6.274
960741AF2-365 GEN
Solar/Wind Harmer
2.708
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
44.331
971617AH1-308 GEN
Solar/Wind Harmer
3.063
970193AG2-126 GEN
Solar/Wind Harmer
7.79
970273AG2-179 GEN
Solar/Wind Harmer
2.013
339250AF1-203 GEN
Solar/Wind Harmer
0.304
962251AG1-071 GEN
Solar/Wind Harmer
2.76
971155AH1-034 GEN
Solar/Wind Harmer
5.002
944531AF1-118 GEN
Solar/Wind Harmer
16.727
970605AG2-385 GEN
Solar/Wind Harmer
2.572
235780M24_1
Solar/Wind Helper
0.963
270240V3-007_GEN2
Solar/Wind Harmer
4.145
971029AG2-637 GEN
Solar/Wind Harmer
10.023
241972AD1-140 GEN
Solar/Wind Harmer
2.969
339211AE2-254 GEN
Solar/Wind Harmer
0.998
970455AG2-298 GEN
Solar/Wind Harmer
3.91
270543AE2-219 C
Solar/Wind Harmer
3.278
970115AG2-085 GEN
Solar/Wind Harmer
2.405
24725505WLD G2 C
Solar/Wind Harmer
2.341
24699105WLD G1 C
Solar/Wind Harmer
2.313
961761AG1-017 GEN
Solar/Wind Harmer
0.249
965401AG1-405 GEN
Solar/Wind Harmer
3.255
965411AG1-406 GEN
Solar/Wind Harmer
1.461
270594AE1-207 GEN
Solar/Wind Harmer
8.276
945581AF1-223 GEN
Solar/Wind Harmer
2.54
965461AG1-414 GEN
Solar/Wind Harmer
1.243
970289AG2-191 GEN
Solar/Wind Harmer
1.041
965101AG1-375 GEN
Solar/Wind Harmer
5.378
270024AE2-089 GEN
Solar/Wind Harmer
2.472
958711AF2-162 GEN
Solar/Wind Harmer
0.532
270156DARBY CT1
Adder
4.488
270157DARBY CT2
Adder
4.477
270158DARBY CT3
Adder
4.406
24729505KEY G4
Adder
3.183
945631AF1-228 GEN
Solar/Wind Harmer
2.242
963841AG1-237 GEN
Solar/Wind Harmer
5.208
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944201AF1-088_MTX
Adder
62.879
957141AF2-008_MTX
Adder
31.44
CBM West 2LTFEXP_CBM-W2->PJM
CBM
54.292
LAGNLTFEXP_LAGN->PJM
CLTF
6.26
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.502
TVALTFEXP_TVA->PJM
CLTF
3.092
NYPJM->LTFIMP_NY
CLTF
1.51
LGEELTFEXP_LGEE->PJM
CLTF
5.08
WECLTFEXP_WEC->PJM
CLTF
1.532
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.12
AG2-052LTFEXP_AG2-052->PJM
LTF
0.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.148
CBM West 1LTFEXP_CBM-W1->PJM
CBM
61.189
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.524
MECLTFEXP_MEC->PJM
CLTF
6.778
SIGELTFEXP_SIGE->PJM
CLTF
0.316
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AEP_P4_#3195_05BEATTY 345_304E_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 288778 CKT 1   /*05BEATTY     345.0 - 05CYPRUS     345.0
 OPEN BRANCH FROM BUS 243453 TO BUS 290098 CKT 4   /*05BEATTY     345.0 - 05BEATTY 4EQ   1.0
 OPEN BRANCH FROM BUS 243469 TO BUS 290098 CKT 4   /*05BEATTY     138.0 - 05BEATTY 4EQ   1.0
 OPEN BRANCH FROM BUS 290098 TO BUS 290099 CKT 4   /*05BEATTY 4EQ   1.0 - 05BEATTY T4   34.5
END
CONTINGENCY 'AEP_P4_#18045_05CYPRUS 345_CB4_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 288778 CKT 1   /*05BEATTY     345.0 - 05CYPRUS     345.0
 OPEN BRANCH FROM BUS 288776 TO BUS 288781 CKT 2   /*05CYPRUS34   138.0 - 05CYPRUS2EQ    1.0
 OPEN BRANCH FROM BUS 288778 TO BUS 288781 CKT 2   /*05CYPRUS     345.0 - 05CYPRUS2EQ    1.0
 OPEN BRANCH FROM BUS 288781 TO BUS 288782 CKT 2   /*05CYPRUS2EQ    1.0 - 05CYPRUST2    34.5
END
CONTINGENCY 'AEP_P4_#18042_05CYPRUS 345_CB1_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 288778 CKT 1   /*05BEATTY     345.0 - 05CYPRUS     345.0
 OPEN BRANCH FROM BUS 288778 TO BUS 288779 CKT 1   /*05CYPRUS     345.0 - 05CYPRUS1EQ    1.0
 OPEN BRANCH FROM BUS 288779 TO BUS 288780 CKT 1   /*05CYPRUS1EQ    1.0 - 05CYPRUST1    34.5
 OPEN BRANCH FROM BUS 288779 TO BUS 290230 CKT 1   /*05CYPRUS1EQ    1.0 - 05CYPRUS12   138.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7216_05VASSEL 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1   /*05MALIS      765.0 - 05VASSEL     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#1558_05BAKER 765_Q_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#309_05HANG R 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#1560_05BAKER 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242523 CKT 1   /*05BAKER      765.0 - 05BAKER      345.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-2'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 944530 TO BUS 243232 CKT 2   /*AF1-118 TP   345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P7-1_#10941___SRT-A'
 OPEN BRANCH FROM BUS 243034 TO BUS 243501 CKT 1   /*05MARQUI     138.0 - 05E.BEAV     138.0
 OPEN BRANCH FROM BUS 243034 TO BUS 243544 CKT 2   /*05MARQUI     138.0 - 05MILPRD     138.0
 OPEN BRANCH FROM BUS 243034 TO BUS 245632 CKT 1   /*05MARQUI     138.0 - 05ARBOLES    138.0
 OPEN BRANCH FROM BUS 243501 TO BUS 243534 CKT 1   /*05E.BEAV     138.0 - 05LICK       138.0
 OPEN BRANCH FROM BUS 243544 TO BUS 243585 CKT 2   /*05MILPRD     138.0 - 05WAVERL     138.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AEP_P2-2_#308_05CULLOD 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
243453 to 244022 ckt 1
243458 to 246752 ckt 1
242925 to 235117 ckt 1
290623 to 242925 ckt Z1
248005 to 242528 ckt 1

Winter Peak Analysis

The New Service Request AG2-378 was evaluated as a 20.0 MW (13.5 MW Capacity) injection in the ATSI area.

AG2-378 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 74.0 MW (20.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-378 was evaluated as a 20.0 MW injection

AG2-378 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 74.0 MW (20.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-150Grassy Falls 138kVIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-157Sullivan 345 kVUnder Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-526West Garrard 345 kVActive
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Prairie 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: s2063.4
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2063.4 / AEPO0001a
Title
Upgrade/Replace 3-345kV 1600A switches at Beatty station
Description
Upgrade/Replace 3-345kV 1600A switches at Beatty station Scope of s2063 replaced the need for network upgrade: n6769.1
Cost Information
Time Estimate
Nov 15 2022

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-378 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
05BEATTY-05COLE 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Nov 18 2027

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-378 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-378 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-378 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-378 could receive cost allocation. Although AG2-378 may not presently have cost responsibility for this upgrade, AG2-378 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

Attachments

AG2-378 One Line Diagram

AG2-378 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.