AG2-384 Phase I Study Report

v1.00 released 2025-10-29 20:37

Chesterfield 230 kV

24.0 MW Capacity / 60.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Virginia Electric and Power Company (d/b/a Dominion Energy Virginia).

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Storage facility located in the Virginia Electric and Power Company (d/b/a Dominion Energy Virginia) zone — Chesterfield County, Virginia. The installed facilities will have a total capability of 60.0 MW with 24.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-384
Project Name:
Chesterfield 230 kV
Project Developer Name:
Virginia Electric and Power Company (d/b/a) Dominion Energy Virginia
State:
Virginia
County:
Chesterfield
Transmission Owner:
Virginia Electric and Power Company (d/b/a Dominion Energy Virginia)
MFO:
60.0
MWE:
60.0
MWC:
24.0
Battery Storage Specification:
240.0 MWh, 4.0-hr class
Grid Charging:
Yes
Fuel Type:
Storage
Basecase Study Year:
2028

Capacity Interconnection Rights (CIR) Transfer Details

This project intends to claim and transfer CIRs from the following Deactivation capacity generation resources. PJM performed a reliability analysis of the impacts to the system capability for the proposed transfer of CIRs from the Deactivation generation resources.

Unit NameStatusCIR ClaimedPOI Transfer
Possum Point 5Deactivated Generator24.0Yes

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-384 will interconnect on the Virginia Electric and Power Company  (d/b/a Dominion Energy Virginia) transmission system at the Chesterfield 230 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-384 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-384Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$3,500,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$14,000,000$14,000,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$43,897$43,897
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$17,543,897$14,043,897

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-384

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-384 Project due at DP1
ABA - B
AG2-384$1,404,390$240,000$1,164,390

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install the Point of Change in Ownership (PCO) disconnect switch, the overhead line conductor from the PCO to the bus position that serves as the Point of Interconnection (POI), as well as any metering and associated protection equipment.$3,500,000 $3,500,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Add two (2) new 230 kV breakers to the existing Chesterfield 230 kV Substation. Additional substation modification/expansion cost may be required after detailed design.$14,000,000 $14,000,000

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 46 to 50 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

PJM performed a power flow analysis of the transmission system using a 2028 load flow model and the results were verified by Dominion.

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. Dominion interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-384 was evaluated as a 60.0 MW (24.0 MW Capacity) injection in the Dominion area.

AG2-384 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 60.0 MW (60.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
DVP_P1-2: LN 2049_SRT-A
SingleAC108.69 %584.68B635.471.87
GD2DVP
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
DVP_P1-2: LN 2050_SRT-S
SingleAC104.83 %584.68B612.91.87
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 562T563_SRT-S
BreakerAC171.05 %812.0C1388.945.84
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-S
SingleAC170.7 %663.64B1132.825.82
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 56372_SRT-S
BreakerAC151.48 %812.0C1230.056.0
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-S
SingleAC127.8 %663.64B848.147.26
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: H6T563_SRT-S
BreakerAC126.92 %812.0C1030.575.5
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: H6T576_SRT-A
BreakerAC126.92 %812.0C1030.575.5
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P4-2: 21712_SRT-S
BreakerAC112.66 %812.0C914.787.26
GD2DVP
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC100.89 %1204.0C1214.756.7
GD2DVP
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
DVP_P1-2: LN 557_SRT-S
SingleAC106.04 %678.68B719.662.49
GD2DVP
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
DVP_P4-2: 55722_SRT-S
BreakerAC105.07 %830.0C872.092.52
GD2DVP
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
DVP_P4-2: 56722_SRT-A
BreakerAC105.07 %830.0C872.092.52
GD2DVP
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
DVP_P7-1: LN 208-259_SRT-S
TowerAC100.86 %1204.0C1214.46.7
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC172.64 %3220.44B5559.885.18
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC171.66 %3220.44B5528.275.27
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T581_SRT-S
BreakerAC150.52 %3940.0C5930.655.25
GD2DVP
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC148.0 %3940.0C5831.045.18
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: 545T552_SRT-S
BreakerAC182.6 %3118.0C5693.435.1
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 552_SRT-S
SingleAC179.85 %3220.44B5791.825.18
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P1-2: LN 581_SRT-S
SingleAC175.06 %3220.44B5637.75.1
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H1T552_SRT-S
BreakerAC154.28 %3940.0C6078.795.18
GD2DVP
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
DVP_P4-2: H3T552_SRT-S
BreakerAC154.01 %3940.0C6067.895.17

Details for 6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2049_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2049_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.69 %
Rating:584.68 MVA
Rating Type:B
MVA to Mitigate:635.47
MW Contribution:1.87
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
1.104
3143096IRON208
50/50
1.082
970129AG2-093 GEN
Solar/Wind Harmer
8.891
965281AG1-393 GEN
Solar/Wind Harmer
1.019
961611AG1-000B GEN
Solar/Wind Harmer
2.056
316404AE1-155 C
Solar/Wind Helper
1.724
316280AD1-041 GEN
Solar/Wind Helper
0.643
316382AG1-145 C
Solar/Wind Helper
0.249
3141906WESTMOR
Solar/Wind Helper
0.073
316132AB2-190 GEN1
Solar/Wind Harmer
0.772
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971283AH1-107 GEN
Solar/Wind Harmer
1.101
3141813NORNECK
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.261
315666AE1-190 GEN
Solar/Wind Helper
0.257
316223AC1-118
Solar/Wind Helper
0.278
971211AH1-065 GEN
50/50
1.272
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316484AD2-074 GEN
Solar/Wind Helper
0.39
316156AD2-030 GEN
Solar/Wind Helper
0.294
971213AH1-066 GEN
50/50
0.636
316033AB2-134 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
2
970657AG2-426 GEN
Solar/Wind Harmer
0.419
3150611CHESTG7
50/50
2.243
3150631CHESTG8
50/50
2.207
971047AG2-646 GEN
50/50
62.791
3141913WHIT STONE
Solar/Wind Helper
0.197
957831AF2-077 GEN
Solar/Wind Helper
0.182
316312AB1-027
Solar/Wind Helper
0.252
944631AF1-128 GEN
50/50
178.64
315671AE2-027_GEN
Solar/Wind Harmer
6.36
3143526WINTERP
Solar/Wind Harmer
0.413
964211AG1-282 GEN
Solar/Wind Helper
0.298
970133AG2-095 GEN
Solar/Wind Harmer
1.717
315813AE1-149 C
Solar/Wind Harmer
4.138
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3141766HARMONY
Solar/Wind Helper
0.046
3142416OLDCHRC
Solar/Wind Helper
0.344
3142416OLDCHRC
Solar/Wind Helper
0.132
3150781HOPHCF2
50/50
0.725
3150761HOPPOLC
50/50
0.46
316240AF1-291 C
Solar/Wind Harmer
0.001
3150641CHESTS8
50/50
1.137
970659AG2-427 GEN
Solar/Wind Harmer
3.04
3141726DUNNSVL
Solar/Wind Helper
0.885
316337AD2-073 GEN
Solar/Wind Helper
0.303
3143096IRON208
50/50
1.104
3150771HOPHCF1
50/50
0.725
970129AG2-093 GEN
Solar/Wind Harmer
4.184
316458AB2-190 GEN2
Solar/Wind Harmer
0.772
971069AG2-661 GEN
Solar/Wind Harmer
2.213
971647AH1-324 GEN
Solar/Wind Harmer
4.018
3142543TWELFTH
Solar/Wind Harmer
0.007
961611AG1-000B GEN
Solar/Wind Harmer
4.044
316381AD1-082 GEN
Solar/Wind Harmer
0.063
3138133OCRAN
Solar/Wind Helper
0.118
316159AE1-175 C
Solar/Wind Helper
0.281
316369SG1_INVT
Solar/Wind Harmer
0.004
971281AH1-106 GEN
Solar/Wind Harmer
1.101
3143316POE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Helper
0.059
3141873WAN 176
Solar/Wind Helper
0.039
315662AE1-191 GEN
Solar/Wind Helper
1.03
3143873LANEXA
Solar/Wind Helper
0.109
3150801HOPHCF4
50/50
1.054
315778AD1-151 GEN
Solar/Wind Harmer
9.957
315839AE2-212 C
Solar/Wind Harmer
0.001
3150621CHESTS7
50/50
1.03
3150791HOPHCF3
50/50
0.725
944641AF1-129 GEN
50/50
44.379
315697AD1-025 GEN
Solar/Wind Harmer
0.125
3143526WINTERP
Solar/Wind Harmer
0.413
316075AC2-137 C
Solar/Wind Helper
0.396
316077AC2-138 C
Solar/Wind Helper
0.196
970603AG2-384 GEN
50/50
1.872
316059AD1-063 C
Solar/Wind Helper
0.232
3141783LANCAST
Solar/Wind Helper
0.119
3141783LANCAST
Solar/Wind Helper
0.079
316487AF1-042 GEN
Solar/Wind Helper
0.204
CPLELTFEXP_CPLE->PJM
CLTF
0.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.201
NYPJM->LTFIMP_NY
CLTF
0.188
LGEELTFEXP_LGEE->PJM
CLTF
0.009
WECLTFEXP_WEC->PJM
CLTF
0.002
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.461
MECLTFEXP_MEC->PJM
CLTF
0.055
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.295
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.372
TVALTFEXP_TVA->PJM
CLTF
0.147

Details for 6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 2050_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF A-6CHCKAHM 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 2050_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.83 %
Rating:584.68 MVA
Rating Type:B
MVA to Mitigate:612.9
MW Contribution:1.87
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
1.104
3143096IRON208
50/50
1.082
970129AG2-093 GEN
Solar/Wind Harmer
8.891
965281AG1-393 GEN
Solar/Wind Harmer
1.019
961611AG1-000B GEN
Solar/Wind Harmer
2.056
971213AH1-066 GEN
50/50
0.636
316033AB2-134 GEN
Solar/Wind Harmer
0.007
970657AG2-426 GEN
Solar/Wind Harmer
2
970657AG2-426 GEN
Solar/Wind Harmer
0.419
3150611CHESTG7
50/50
2.243
3150631CHESTG8
50/50
2.207
971047AG2-646 GEN
50/50
62.79
3141913WHIT STONE
Solar/Wind Helper
0.197
957831AF2-077 GEN
Solar/Wind Helper
0.182
316312AB1-027
Solar/Wind Helper
0.252
944631AF1-128 GEN
50/50
178.638
315671AE2-027_GEN
Solar/Wind Harmer
6.36
3143526WINTERP
Solar/Wind Harmer
0.413
964211AG1-282 GEN
Solar/Wind Helper
0.298
3142946ENON
Solar/Wind Harmer
0.118
970133AG2-095 GEN
Solar/Wind Harmer
1.717
315813AE1-149 C
Solar/Wind Harmer
4.138
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3141766HARMONY
Solar/Wind Helper
0.046
3142416OLDCHRC
Solar/Wind Helper
0.344
3142416OLDCHRC
Solar/Wind Helper
0.132
971211AH1-065 GEN
50/50
1.272
970659AG2-427 GEN
Solar/Wind Harmer
0.665
316484AD2-074 GEN
Solar/Wind Helper
0.39
316156AD2-030 GEN
Solar/Wind Helper
0.294
3150781HOPHCF2
50/50
0.725
3150761HOPPOLC
50/50
0.46
316240AF1-291 C
Solar/Wind Harmer
0.001
3150641CHESTS8
50/50
1.137
970659AG2-427 GEN
Solar/Wind Harmer
3.04
3141726DUNNSVL
Solar/Wind Helper
0.885
316337AD2-073 GEN
Solar/Wind Helper
0.303
316132AB2-190 GEN1
Solar/Wind Harmer
0.772
316233AE1-074 FULL
Solar/Wind Harmer
0.064
971283AH1-107 GEN
Solar/Wind Harmer
1.101
3141813NORNECK
Solar/Wind Helper
0.208
957601AF2-054 GEN
Solar/Wind Helper
0.261
315666AE1-190 GEN
Solar/Wind Helper
0.257
316223AC1-118
Solar/Wind Helper
0.278
3143096IRON208
50/50
1.104
3150771HOPHCF1
50/50
0.725
970129AG2-093 GEN
Solar/Wind Harmer
4.184
316458AB2-190 GEN2
Solar/Wind Harmer
0.772
971069AG2-661 GEN
Solar/Wind Harmer
2.213
971647AH1-324 GEN
Solar/Wind Harmer
4.018
3142543TWELFTH
Solar/Wind Harmer
0.007
961611AG1-000B GEN
Solar/Wind Harmer
4.044
316381AD1-082 GEN
Solar/Wind Harmer
0.063
3138133OCRAN
Solar/Wind Helper
0.118
316159AE1-175 C
Solar/Wind Helper
0.281
316369SG1_INVT
Solar/Wind Harmer
0.004
971281AH1-106 GEN
Solar/Wind Harmer
1.101
3143316POE
Solar/Wind Harmer
0.256
3138133OCRAN
Solar/Wind Helper
0.059
3141873WAN 176
Solar/Wind Helper
0.039
315662AE1-191 GEN
Solar/Wind Helper
1.03
3143873LANEXA
Solar/Wind Helper
0.109
316404AE1-155 C
Solar/Wind Helper
1.724
316280AD1-041 GEN
Solar/Wind Helper
0.644
316382AG1-145 C
Solar/Wind Helper
0.249
3141906WESTMOR
Solar/Wind Helper
0.073
3150801HOPHCF4
50/50
1.054
315778AD1-151 GEN
Solar/Wind Harmer
9.957
315839AE2-212 C
Solar/Wind Harmer
0.001
3150621CHESTS7
50/50
1.03
3150791HOPHCF3
50/50
0.725
944641AF1-129 GEN
50/50
44.377
315697AD1-025 GEN
Solar/Wind Harmer
0.125
3143526WINTERP
Solar/Wind Harmer
0.413
316075AC2-137 C
Solar/Wind Helper
0.396
316077AC2-138 C
Solar/Wind Helper
0.196
970603AG2-384 GEN
50/50
1.872
316059AD1-063 C
Solar/Wind Helper
0.232
3141783LANCAST
Solar/Wind Helper
0.119
3141783LANCAST
Solar/Wind Helper
0.079
3142946ENON
Solar/Wind Harmer
0.035
316487AF1-042 GEN
Solar/Wind Helper
0.204
CPLELTFEXP_CPLE->PJM
CLTF
0.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.197
NYPJM->LTFIMP_NY
CLTF
0.188
LGEELTFEXP_LGEE->PJM
CLTF
0.008
WECLTFEXP_WEC->PJM
CLTF
0.002
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.46
MECLTFEXP_MEC->PJM
CLTF
0.054
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LAGNLTFEXP_LAGN->PJM
CLTF
0.295
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.371
TVALTFEXP_TVA->PJM
CLTF
0.147

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 562T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 562T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:171.05 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1388.94
MW Contribution:5.84
Bus #Bus NameTypeMW Contribution
3150781HOPHCF2
50/50
0.566
3150761HOPPOLC
50/50
0.359
316240AF1-291 C
Solar/Wind Harmer
0.89
972187AH1-678 GEN
Adder
2.422
966811AG1-552 GEN
Solar/Wind Harmer
0.959
316426AA2-053 GEN
Solar/Wind Harmer
0.85
3145893MURPHYS
Solar/Wind Harmer
0.227
3145893MURPHYS
Solar/Wind Harmer
-0.015
316065AD1-022 GEN
Solar/Wind Harmer
3.778
961601AG1-000A GEN
Solar/Wind Harmer
2.95
3145453TOT5
Solar/Wind Harmer
0.069
3146516WINFALL
Solar/Wind Harmer
-0.007
316023GEN1_S
Solar/Wind Harmer
0.733
971795AH1-408 GEN
Solar/Wind Harmer
6.821
3147043LAWRENC
Adder
0.706
3145336SMITFLD
Solar/Wind Harmer
-0.033
315722AD1-056 GEN
Solar/Wind Harmer
0.855
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
316359AB2-059 GEN
Solar/Wind Harmer
1.008
3142053HEARTS
Solar/Wind Harmer
0.088
3146083TARBORO
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.02
316375AC2-012 GEN
Solar/Wind Harmer
2.379
3146456SLIGO L269
Solar/Wind Harmer
-0.007
316336AC2-165 C
Solar/Wind Helper
0.633
970659AG2-427 GEN
Solar/Wind Harmer
7.425
316011AB1-132 GEN
Solar/Wind Harmer
1.936
970919AG2-571 GEN
Solar/Wind Harmer
2.898
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145893MURPHYS
Solar/Wind Harmer
0.241
3146263WOODLND
Solar/Wind Harmer
-0.008
316093AE2-104_GEN
Solar/Wind Harmer
2.321
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
961671AG1-007 GEN
Solar/Wind Harmer
0.094
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.141
316494AC1-189 GEN
Solar/Wind Harmer
0.795
315693AD1-088 GEN
Solar/Wind Harmer
3.59
315800Z1-036_GEN1
Solar/Wind Harmer
1.769
3146516WINFALL
Solar/Wind Harmer
-0.023
3146516WINFALL
Solar/Wind Harmer
-0.007
962491AG1-098 GEN
Solar/Wind Harmer
4.708
315779AE2-040
50/50
1.742
316132AB2-190 GEN1
Solar/Wind Harmer
1.401
944011AF1-069 GEN
Solar/Wind Harmer
5.925
971967AH1-528 GEN
Solar/Wind Harmer
17.946
315652AC1-086 GEN
Solar/Wind Harmer
10.41
972265AH1-717 GEN
Adder
6.391
3151191GRAVEL3
Adder
5.915
970085AG2-068 GEN
Solar/Wind Harmer
5.695
3137643SOCKMAN
Solar/Wind Harmer
-0.035
315607AA1-063A GEN
Solar/Wind Harmer
0.849
965291AG1-394 GEN
Solar/Wind Harmer
0.729
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
-0.008
315732AD1-074 GEN1
Solar/Wind Harmer
1.51
315735AD1-075 GEN1
Solar/Wind Harmer
0.755
316005AA1-067
Solar/Wind Harmer
0.148
316305AF2-043 C
Solar/Wind Harmer
0.215
3146406KITTY HAWK
Solar/Wind Harmer
0.006
316233AE1-074 FULL
Solar/Wind Helper
0.222
3150771HOPHCF1
50/50
0.566
970129AG2-093 GEN
Solar/Wind Harmer
3.197
316458AB2-190 GEN2
Solar/Wind Harmer
1.401
316381AD1-082 GEN
Solar/Wind Harmer
1.25
971069AG2-661 GEN
Solar/Wind Harmer
2.031
970661AG2-428 GEN
Solar/Wind Harmer
13.418
971647AH1-324 GEN
Solar/Wind Harmer
5.628
961611AG1-000B GEN
Solar/Wind Harmer
5.115
3151171GRAVELC
Adder
0.876
970087AG2-069 GEN
Solar/Wind Harmer
8.543
316190AA2-174 GEN
Solar/Wind Harmer
0.103
957481AF2-042 GEN
Solar/Wind Harmer
24.676
3146233WITAKRS
Solar/Wind Harmer
-0.03
316049AB1-081 GEN
Solar/Wind Harmer
0.807
3145493TOT1
Solar/Wind Harmer
0.221
3146293MARTNCO
Solar/Wind Harmer
0.046
971163AH1-040 GEN
Solar/Wind Harmer
6.893
3130156CHOWAN
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.144
3150981CHESPKA
Adder
0.764
316388AE2-253 GEN
Solar/Wind Harmer
0.457
3142543TWELFTH
Solar/Wind Helper
0.04
3143226MDLTHAN
Solar/Wind Helper
0.199
3143316POE
Solar/Wind Harmer
-0.079
316369SG1_INVT
Solar/Wind Harmer
2.168
946281AF1-292 GEN
Solar/Wind Harmer
0.22
316087AB2-174 GEN
Solar/Wind Harmer
1.339
970581AG2-369 GEN
Solar/Wind Harmer
4.898
3146033SCOT NK
Solar/Wind Harmer
-0.032
970601AG2-382 GEN
Solar/Wind Harmer
3.328
315733AD1-074 GEN2
Solar/Wind Harmer
1.51
970129AG2-093 GEN
Solar/Wind Harmer
7.894
970661AG2-428 GEN
Solar/Wind Harmer
2.378
965281AG1-393 GEN
Solar/Wind Harmer
1.512
961611AG1-000B GEN
Solar/Wind Harmer
2.183
3151171GRAVELC
Adder
1.151
313506AB2-031 GEN
Solar/Wind Harmer
0.74
970917AG2-570 GEN
Solar/Wind Harmer
22.893
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.663
961681AG1-008 GEN
Solar/Wind Harmer
6.374
962331AG1-082 GEN
Solar/Wind Harmer
0.997
3146233WITAKRS
Solar/Wind Harmer
0.159
3146233WITAKRS
Solar/Wind Harmer
-0.005
315737AD1-076 GEN
Solar/Wind Harmer
1.419
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.919
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3144873MCLAUGH
Solar/Wind Harmer
0
316405AF2-144 C
Solar/Wind Helper
0.153
971213AH1-066 GEN
50/50
0.496
970657AG2-426 GEN
Solar/Wind Harmer
4.142
970657AG2-426 GEN
Solar/Wind Harmer
0.866
316033AB2-134 GEN
Solar/Wind Harmer
3.913
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.071
316236AE1-162_GEN
Solar/Wind Harmer
0.251
3145493TOT1
Solar/Wind Harmer
0.115
3145933PARMELE
Solar/Wind Harmer
-0.015
3145933PARMELE
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.027
3137176SLIGO L2192
Solar/Wind Harmer
-0.027
316339AD2-160 GEN
Solar/Wind Harmer
0.457
3145506HICKORY
Solar/Wind Harmer
-0.027
3145506HICKORY
Solar/Wind Harmer
-0.016
3145506HICKORY
Solar/Wind Harmer
-0.004
313527AB2-043 GEN
Solar/Wind Harmer
1.038
315671AE2-027_GEN
Solar/Wind Harmer
7.708
960081AF2-299 GEN
Solar/Wind Harmer
1.103
962571AG1-106 GEN
Solar/Wind Harmer
1.33
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.009
939411AE1-173 GEN
Solar/Wind Harmer
44.626
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
316212AC1-099_GEN
Solar/Wind Harmer
0.69
971547AH1-271 GEN
Solar/Wind Harmer
1.902
316129AC1-054 GEN
Solar/Wind Harmer
0.658
971065AG2-659 GEN
Solar/Wind Harmer
3.709
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316072AD1-144
Solar/Wind Harmer
0.145
315687AD1-152 GEN
Solar/Wind Harmer
0.843
944591AF1-124 GEN
Solar/Wind Harmer
29.523
316237AB2-079_GEN
Solar/Wind Harmer
0.193
3143526WINTERP
Solar/Wind Helper
0.755
3150801HOPHCF4
50/50
0.823
315839AE2-212 C
Solar/Wind Harmer
0.75
315778AD1-151 GEN
Solar/Wind Harmer
11.121
966621AG1-532 GEN
Solar/Wind Harmer
0.199
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145796HORNRTN
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.373
3145823KELFORD
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.243
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3151101ELIZAR3
Adder
5.635
944601AF1-125 GEN
Solar/Wind Harmer
28.958
316258AE1-075 C
Solar/Wind Helper
0.184
944641AF1-129 GEN
50/50
138.358
3150791HOPHCF3
50/50
0.566
3144356SAPONY
Solar/Wind Harmer
0.489
315697AD1-025 GEN
Solar/Wind Harmer
2.454
972185AH1-677 GEN
Adder
4.854
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145783HORNRTN
Solar/Wind Harmer
1.001
3145783HORNRTN
Solar/Wind Harmer
0.801
3145783HORNRTN
Solar/Wind Harmer
0.25
3145783HORNRTN
Solar/Wind Harmer
0.1
970099AG2-077 GEN
Solar/Wind Harmer
9.87
316263AC1-034 GEN
Solar/Wind Harmer
3.504
3145603CNETO
Solar/Wind Harmer
0.046
316316AC1-027 C
Solar/Wind Harmer
0.209
316185AD1-033 GEN
Solar/Wind Harmer
0.709
3143526WINTERP
Solar/Wind Helper
0.755
316315AB2-025 C
Solar/Wind Harmer
0.378
315833AF1-017_GEN
Solar/Wind Harmer
1.93
941031AE2-094 GEN
Solar/Wind Harmer
18.91
970673AG2-436 GEN
Solar/Wind Harmer
20.676
970673AG2-436 GEN
Solar/Wind Harmer
10.469
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.004
971445AH1-216 GEN
Solar/Wind Harmer
5.206
970831AG2-522 GEN
Solar/Wind Harmer
3.803
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.234
3145746EVERETS
Solar/Wind Harmer
-0.029
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3152611GOSPORTB
Adder
0.78
3152621GOSPORTC
Adder
0.662
3152601GOSPORTA
Adder
0.611
3151081ELIZAR1
Adder
5.564
3151091ELIZAR2
Adder
5.467
957871AF2-081 GEN
Solar/Wind Harmer
3.391
316239AB2-077_GEN
Solar/Wind Harmer
0.193
316238AB2-078_GEN
Solar/Wind Harmer
0.193
316181AB2-040 GEN
Solar/Wind Harmer
1.284
970933AG2-581 GEN
Solar/Wind Harmer
8.502
315742AE1-103 GEN
Solar/Wind Harmer
0.845
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.861
3146376EDENTON
Solar/Wind Harmer
0.214
3146376EDENTON
Solar/Wind Harmer
0.214
316431W1029_GEN1
Solar/Wind Harmer
1.282
316433W1029_GEN2
Solar/Wind Harmer
1.282
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
0.803
316017AA1-139 ULT1
Solar/Wind Harmer
0.549
970603AG2-384 GEN
50/50
5.836
315814AE2-033 C
Solar/Wind Harmer
12.904
316349AD2-085 GEN
Solar/Wind Harmer
0.904
316311AC2-079 GEN
Solar/Wind Harmer
5.103
3151201GRAVEL4
Adder
5.991
3151211GRAVEL5
Adder
5.915
3146043SEABORD
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.202
315835AF2-110_GEN
Solar/Wind Harmer
0.998
961941AG1-037 GEN
Solar/Wind Harmer
0.06
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
316319Z2-044 C
Solar/Wind Harmer
0.42
316420AA1-050 GEN
Solar/Wind Harmer
0.848
3146396TANGLEW
Solar/Wind Harmer
0.128
313526AB2-022
Solar/Wind Harmer
0.187
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.595
970181AG2-120 GEN
Solar/Wind Harmer
0.962
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.769
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
316321Z2-027
Solar/Wind Harmer
0.188
319010AE1-072 C
Solar/Wind Harmer
1.378
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316036AC1-147 C
Solar/Wind Harmer
0.185
3150991CHESPKB
Adder
0.641
3150991CHESPKB
Adder
0.626
939181AE1-148 GEN
Solar/Wind Harmer
3.86
3142956BIRDNECK
Solar/Wind Harmer
0.365
316018AA1-139 ULT2
Solar/Wind Harmer
0.581
971211AH1-065 GEN
50/50
0.992
970659AG2-427 GEN
Solar/Wind Harmer
1.316
3145893MURPHYS
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.374
3146263WOODLND
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
316327AA2-057 GEN
Solar/Wind Harmer
0.781
961601AG1-000A GEN
Solar/Wind Harmer
2.988
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
971157AH1-035 GEN
Solar/Wind Harmer
0.931
3145963POPLR C
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.793
3144536CHRHLND
Solar/Wind Harmer
-0.001
316435W1029_GEN3
Solar/Wind Harmer
1.282
3146516WINFALL
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.406
944581AF1-123 GEN
Solar/Wind Harmer
29.417
316313AB2-026
Solar/Wind Helper
0.204
315813AE1-149 C
Solar/Wind Harmer
9.892
970133AG2-095 GEN
Solar/Wind Harmer
1.764
316083AB2-161 GEN
Solar/Wind Harmer
2.212
316365GEN2_N
Solar/Wind Harmer
0.733
3151221GRAVEL6
Adder
5.984
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145336SMITFLD
Solar/Wind Harmer
-0.003
315724AD1-057 GEN
Solar/Wind Harmer
0.47
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.052
3146206CASHIE
Solar/Wind Harmer
-0.008
3138543CONSLDL
Solar/Wind Harmer
-0.005
316478AD1-087 GEN
Solar/Wind Harmer
0.645
316486AD2-202 GEN
Solar/Wind Harmer
0.189
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.829
CPLELTFEXP_CPLE->PJM
CLTF
3.996
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.742
NYPJM->LTFIMP_NY
CLTF
0.594
LGEELTFEXP_LGEE->PJM
CLTF
0.385
WECLTFEXP_WEC->PJM
CLTF
0.198
CBM West 1LTFEXP_CBM-W1->PJM
CBM
6.809
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.207
MECLTFEXP_MEC->PJM
CLTF
1.111
SIGELTFEXP_SIGE->PJM
CLTF
0.033
LAGNLTFEXP_LAGN->PJM
CLTF
2.497
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.4
TVALTFEXP_TVA->PJM
CLTF
1.243

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:170.7 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:1132.82
MW Contribution:5.82
Bus #Bus NameTypeMW Contribution
970129AG2-093 GEN
Solar/Wind Harmer
7.687
970661AG2-428 GEN
Solar/Wind Harmer
2.393
965281AG1-393 GEN
Solar/Wind Harmer
1.127
961611AG1-000B GEN
Solar/Wind Harmer
2.578
3151171GRAVELC
Adder
1.222
313506AB2-031 GEN
Solar/Wind Harmer
0.24
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
961681AG1-008 GEN
Solar/Wind Harmer
5.314
970917AG2-570 GEN
Solar/Wind Harmer
6.276
962331AG1-082 GEN
Solar/Wind Harmer
0.749
3144873MCLAUGH
Solar/Wind Harmer
0.002
315737AD1-076 GEN
Solar/Wind Harmer
0.872
3146626S HERTFORD
Solar/Wind Harmer
0.067
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.746
3146233WITAKRS
Solar/Wind Harmer
0.322
3146233WITAKRS
Solar/Wind Harmer
0.044
316405AF2-144 C
Solar/Wind Helper
0.152
315779AE2-040
50/50
1.645
316132AB2-190 GEN1
Solar/Wind Harmer
0.675
972265AH1-717 GEN
Adder
6.782
3151191GRAVEL3
Adder
6.277
315652AC1-086 GEN
Solar/Wind Harmer
8.66
944011AF1-069 GEN
Solar/Wind Harmer
4.66
3137643SOCKMAN
Solar/Wind Harmer
0.299
971967AH1-528 GEN
Solar/Wind Harmer
11.737
965291AG1-394 GEN
Solar/Wind Harmer
0.323
315607AA1-063A GEN
Solar/Wind Harmer
0.148
3145893MURPHYS
Solar/Wind Harmer
0.194
3145893MURPHYS
Solar/Wind Harmer
0.072
970085AG2-068 GEN
Solar/Wind Harmer
3.748
3145513AHOSKIE
Solar/Wind Harmer
0.147
3145513AHOSKIE
Solar/Wind Harmer
0.07
316305AF2-043 C
Solar/Wind Harmer
0.001
315732AD1-074 GEN1
Solar/Wind Harmer
0.389
315735AD1-075 GEN1
Solar/Wind Harmer
0.195
3146406KITTY HAWK
Solar/Wind Harmer
0.008
316005AA1-067
Solar/Wind Harmer
0.068
316233AE1-074 FULL
Solar/Wind Helper
0.217
971213AH1-066 GEN
50/50
0.501
970657AG2-426 GEN
Solar/Wind Harmer
4.141
970657AG2-426 GEN
Solar/Wind Harmer
0.868
316033AB2-134 GEN
Solar/Wind Harmer
0.007
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.077
3142666NORTHAMPTON
Solar/Wind Harmer
0.046
3145593CAROLNA
Solar/Wind Harmer
0.072
3145593CAROLNA
Solar/Wind Harmer
0.072
3145593CAROLNA
Solar/Wind Harmer
0.09
3146626S HERTFORD
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.067
3130086AYDLETT
Solar/Wind Harmer
0.267
3137176SLIGO L2192
Solar/Wind Harmer
0.266
316339AD2-160 GEN
Solar/Wind Harmer
0.108
3145506HICKORY
Solar/Wind Harmer
0.266
3145506HICKORY
Solar/Wind Harmer
0.16
3145506HICKORY
Solar/Wind Harmer
0.04
3145933PARMELE
Solar/Wind Harmer
0.128
3145933PARMELE
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.146
971211AH1-065 GEN
50/50
1.003
3151161SURRY 1
50/50
3.355
970659AG2-427 GEN
Solar/Wind Harmer
1.314
3145893MURPHYS
Solar/Wind Harmer
0.12
3145893MURPHYS
Solar/Wind Harmer
0.072
3144536CHRHLND
Solar/Wind Harmer
0.011
957521AF2-046 GEN
Solar/Wind Harmer
5.314
3146263WOODLND
Solar/Wind Harmer
0.07
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
971157AH1-035 GEN
Solar/Wind Harmer
0.813
315614AA2-178 GEN
Solar/Wind Harmer
0.387
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.067
316320Y1-086
Solar/Wind Harmer
0
3145963POPLR C
Solar/Wind Harmer
0.066
316327AA2-057 GEN
Solar/Wind Harmer
0.099
944581AF1-123 GEN
Solar/Wind Harmer
14.652
961601AG1-000A GEN
Solar/Wind Harmer
4.481
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
315773AC2-141 GEN
Solar/Wind Harmer
2.115
316313AB2-026
Solar/Wind Helper
0.203
3150771HOPHCF1
50/50
0.572
970129AG2-093 GEN
Solar/Wind Harmer
3.618
316458AB2-190 GEN2
Solar/Wind Harmer
0.675
316381AD1-082 GEN
Solar/Wind Harmer
0.126
971069AG2-661 GEN
Solar/Wind Harmer
2.086
970661AG2-428 GEN
Solar/Wind Harmer
11.251
971647AH1-324 GEN
Solar/Wind Harmer
4.442
961611AG1-000B GEN
Solar/Wind Harmer
5.07
3151171GRAVELC
Adder
0.929
316190AA2-174 GEN
Solar/Wind Harmer
0
970087AG2-069 GEN
Solar/Wind Harmer
5.623
316246AF1-032 C
Solar/Wind Harmer
0.031
3150981CHESPKA
Adder
0.851
316315AB2-025 C
Solar/Wind Harmer
0.095
315833AF1-017_GEN
Solar/Wind Harmer
0
971445AH1-216 GEN
Solar/Wind Harmer
5.676
941031AE2-094 GEN
Solar/Wind Harmer
14.261
3145796HORNRTN
Solar/Wind Harmer
0.245
3145796HORNRTN
Solar/Wind Harmer
0.031
970673AG2-436 GEN
Solar/Wind Harmer
16.134
970673AG2-436 GEN
Solar/Wind Harmer
10.756
3152611GOSPORTB
Adder
0.868
3152621GOSPORTC
Adder
0.737
3152601GOSPORTA
Adder
0.68
3151081ELIZAR1
Adder
6.21
3151091ELIZAR2
Adder
6.102
957871AF2-081 GEN
Solar/Wind Harmer
3.324
3145746EVERETS
Solar/Wind Harmer
0.252
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
957861AF2-080 GEN
Solar/Wind Harmer
2.725
3145573BETHELC
Solar/Wind Harmer
0.063
3145573BETHELC
Solar/Wind Harmer
0.063
970831AG2-522 GEN
Solar/Wind Harmer
2.677
315671AE2-027_GEN
Solar/Wind Harmer
5.751
960081AF2-299 GEN
Solar/Wind Harmer
0.792
962571AG1-106 GEN
Solar/Wind Harmer
1.12
940641AE2-051 GEN
Solar/Wind Harmer
6.143
3145796HORNRTN
Solar/Wind Harmer
0.252
3145796HORNRTN
Solar/Wind Harmer
0.076
939411AE1-173 GEN
Solar/Wind Harmer
31.612
3145783HORNRTN
Solar/Wind Harmer
0.072
3145823KELFORD
Solar/Wind Harmer
0.069
316072AD1-144
Solar/Wind Harmer
0.025
971547AH1-271 GEN
Solar/Wind Harmer
1.459
316212AC1-099_GEN
Solar/Wind Harmer
0.35
944591AF1-124 GEN
Solar/Wind Harmer
14.705
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316129AC1-054 GEN
Solar/Wind Harmer
0.232
971065AG2-659 GEN
Solar/Wind Harmer
2.591
3143526WINTERP
Solar/Wind Helper
0.738
970133AG2-095 GEN
Solar/Wind Harmer
1.354
315813AE1-149 C
Solar/Wind Harmer
7.434
316083AB2-161 GEN
Solar/Wind Harmer
0.002
316365GEN2_N
Solar/Wind Harmer
0.206
3151221GRAVEL6
Adder
6.35
3145336SMITFLD
Solar/Wind Harmer
0.032
3145273HOLLAND
Solar/Wind Harmer
0.056
3147043LAWRENC
Solar/Wind Harmer
0.044
3146173TUNIS
Solar/Wind Harmer
0.071
3156021HOLLOMANSOL
Solar/Wind Harmer
0.315
315724AD1-057 GEN
Solar/Wind Harmer
0.259
3146206CASHIE
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.068
3146456SLIGO L269
Solar/Wind Harmer
0.067
971153AH1-033 GEN
Solar/Wind Harmer
0.772
3138543CONSLDL
Solar/Wind Harmer
0.042
3146073TAR RVR
Solar/Wind Harmer
0.063
3146083TARBORO
Solar/Wind Harmer
0.063
971623AH1-311 GEN
Solar/Wind Harmer
0.125
316478AD1-087 GEN
Solar/Wind Harmer
0.201
316486AD2-202 GEN
Solar/Wind Harmer
0.059
316023GEN1_S
Solar/Wind Harmer
0.206
3145336SMITFLD
Solar/Wind Harmer
0.32
971795AH1-408 GEN
Solar/Wind Harmer
5.061
3147043LAWRENC
Adder
0.659
3146173TUNIS
Solar/Wind Harmer
0.071
3145683EARLEYS
Solar/Wind Harmer
0.07
315722AD1-056 GEN
Solar/Wind Harmer
0.437
3146206CASHIE
Solar/Wind Harmer
0.068
316375AC2-012 GEN
Solar/Wind Harmer
0.002
3145663CRESWEL
Solar/Wind Harmer
0.189
3146456SLIGO L269
Solar/Wind Harmer
0.067
3146083TARBORO
Solar/Wind Harmer
0.063
316359AB2-059 GEN
Solar/Wind Harmer
0.225
3142053HEARTS
Solar/Wind Harmer
0.11
316294AC1-161 GEN
Solar/Wind Harmer
1.003
316336AC2-165 C
Solar/Wind Helper
0.631
3150781HOPHCF2
50/50
0.572
3150761HOPPOLC
50/50
0.363
316240AF1-291 C
Solar/Wind Harmer
0.002
972187AH1-678 GEN
Adder
2.094
966811AG1-552 GEN
Solar/Wind Harmer
0.786
316426AA2-053 GEN
Solar/Wind Harmer
0.243
3145893MURPHYS
Solar/Wind Harmer
0.48
3145893MURPHYS
Solar/Wind Harmer
0.129
316036AC1-147 C
Solar/Wind Harmer
0.013
3150991CHESPKB
Adder
0.714
3150991CHESPKB
Adder
0.697
316065AD1-022 GEN
Solar/Wind Harmer
3.139
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
3145453TOT5
Solar/Wind Harmer
0.088
961601AG1-000A GEN
Solar/Wind Harmer
1.12
970659AG2-427 GEN
Solar/Wind Harmer
6.005
316011AB1-132 GEN
Solar/Wind Harmer
1.431
316093AE2-104_GEN
Solar/Wind Harmer
1.261
3145893MURPHYS
Solar/Wind Harmer
0.287
3145893MURPHYS
Solar/Wind Harmer
0.319
970919AG2-571 GEN
Solar/Wind Harmer
2.51
3146263WOODLND
Solar/Wind Harmer
0.07
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.219
3146516WINFALL
Solar/Wind Harmer
0.067
3145963POPLR C
Solar/Wind Harmer
0.066
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316494AC1-189 GEN
Solar/Wind Harmer
0.213
961671AG1-007 GEN
Solar/Wind Harmer
0.01
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
970603AG2-384 GEN
50/50
5.819
315814AE2-033 C
Solar/Wind Harmer
9.215
316349AD2-085 GEN
Solar/Wind Harmer
0.064
316311AC2-079 GEN
Solar/Wind Harmer
2.655
3151201GRAVEL4
Adder
6.358
3151211GRAVEL5
Adder
6.277
315835AF2-110_GEN
Solar/Wind Harmer
0.514
3146043SEABORD
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.139
3145683EARLEYS
Solar/Wind Harmer
0.07
3145683EARLEYS
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.068
3146396TANGLEW
Solar/Wind Harmer
0.185
313526AB2-022
Solar/Wind Harmer
0.036
316319Z2-044 C
Solar/Wind Harmer
0
316420AA1-050 GEN
Solar/Wind Harmer
0.002
971163AH1-040 GEN
Solar/Wind Harmer
5.416
3130156CHOWAN
Solar/Wind Harmer
0.068
316388AE2-253 GEN
Solar/Wind Harmer
0.209
3146293MARTNCO
Solar/Wind Harmer
0.059
3146233WITAKRS
Solar/Wind Harmer
0.255
3145493TOT1
Solar/Wind Harmer
0.281
316049AB1-081 GEN
Solar/Wind Harmer
0.359
957481AF2-042 GEN
Solar/Wind Harmer
16.224
3142543TWELFTH
Solar/Wind Helper
0.04
3143226MDLTHAN
Solar/Wind Helper
0.196
3143316POE
Solar/Wind Harmer
0.686
316369SG1_INVT
Solar/Wind Harmer
0.004
316087AB2-174 GEN
Solar/Wind Harmer
0.002
970581AG2-369 GEN
Solar/Wind Harmer
3.224
970601AG2-382 GEN
Solar/Wind Harmer
2.553
3146033SCOT NK
Solar/Wind Harmer
0.273
3146486SUNBURY
Solar/Wind Harmer
0.068
3146486SUNBURY
Solar/Wind Harmer
0.068
315733AD1-074 GEN2
Solar/Wind Harmer
0.389
3130546PLYMOUTH
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.291
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
316321Z2-027
Solar/Wind Harmer
0.012
3145176PASQUOTANK
Solar/Wind Harmer
0.042
319010AE1-072 C
Solar/Wind Harmer
0.337
970181AG2-120 GEN
Solar/Wind Harmer
0.788
3150801HOPHCF4
50/50
0.831
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
9.385
3145796HORNRTN
Solar/Wind Harmer
0.306
3145796HORNRTN
Solar/Wind Harmer
0.076
316317KELFORD C
Solar/Wind Harmer
0.007
3145823KELFORD
Solar/Wind Harmer
0.069
3151101ELIZAR3
Adder
6.29
316210AC1-098 GEN
Solar/Wind Harmer
0.629
944601AF1-125 GEN
Solar/Wind Harmer
14.427
3145746EVERETS
Solar/Wind Harmer
0.063
3145746EVERETS
Solar/Wind Harmer
0.063
316258AE1-075 C
Solar/Wind Helper
0.183
944641AF1-129 GEN
50/50
137.955
3150791HOPHCF3
50/50
0.572
3144356SAPONY
Solar/Wind Harmer
0.986
315697AD1-025 GEN
Solar/Wind Harmer
0.125
3145796HORNRTN
Solar/Wind Harmer
0.229
972185AH1-677 GEN
Adder
4.193
3145783HORNRTN
Solar/Wind Harmer
1.275
3145783HORNRTN
Solar/Wind Harmer
1.02
3145783HORNRTN
Solar/Wind Harmer
0.319
3145783HORNRTN
Solar/Wind Harmer
0.128
316316AC1-027 C
Solar/Wind Harmer
0.065
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3145603CNETO
Solar/Wind Harmer
0.059
316263AC1-034 GEN
Solar/Wind Harmer
2.384
970099AG2-077 GEN
Solar/Wind Harmer
6.49
3143526WINTERP
Solar/Wind Helper
0.738
316181AB2-040 GEN
Solar/Wind Harmer
0.113
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146173TUNIS
Solar/Wind Harmer
0.071
3146173TUNIS
Solar/Wind Harmer
0.071
970933AG2-581 GEN
Solar/Wind Harmer
5.578
316274AC1-208 GEN
Solar/Wind Harmer
0.352
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146376EDENTON
Solar/Wind Harmer
0.301
3146376EDENTON
Solar/Wind Harmer
0.301
3146386ELIZ CT
Solar/Wind Harmer
0.067
3146456SLIGO L269
Solar/Wind Harmer
1.182
316017AA1-139 ULT1
Solar/Wind Harmer
0.037
CPLELTFEXP_CPLE->PJM
CLTF
3.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.141
NYPJM->LTFIMP_NY
CLTF
0.55
LGEELTFEXP_LGEE->PJM
CLTF
0.33
WECLTFEXP_WEC->PJM
CLTF
0.169
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.771
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.694
MECLTFEXP_MEC->PJM
CLTF
0.959
SIGELTFEXP_SIGE->PJM
CLTF
0.028
LAGNLTFEXP_LAGN->PJM
CLTF
2.199
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.502
TVALTFEXP_TVA->PJM
CLTF
1.094

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 56372_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56372_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.48 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1230.05
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
3150771HOPHCF1
50/50
0.592
970129AG2-093 GEN
Solar/Wind Harmer
3.358
316458AB2-190 GEN2
Solar/Wind Harmer
1.472
316381AD1-082 GEN
Solar/Wind Harmer
1.315
971069AG2-661 GEN
Solar/Wind Harmer
2.139
970661AG2-428 GEN
Solar/Wind Harmer
14.096
971647AH1-324 GEN
Solar/Wind Harmer
5.949
961611AG1-000B GEN
Solar/Wind Harmer
5.423
3151171GRAVELC
Adder
0.932
316190AA2-174 GEN
Solar/Wind Harmer
0.102
971163AH1-040 GEN
Solar/Wind Harmer
7.035
3130156CHOWAN
Solar/Wind Harmer
-0.007
316246AF1-032 C
Solar/Wind Harmer
0.15
3150981CHESPKA
Adder
0.818
3146233WITAKRS
Solar/Wind Harmer
-0.029
316388AE2-253 GEN
Solar/Wind Harmer
0.485
3146293MARTNCO
Solar/Wind Harmer
0.044
970087AG2-069 GEN
Solar/Wind Harmer
6.711
3145493TOT1
Solar/Wind Harmer
0.212
316049AB1-081 GEN
Solar/Wind Harmer
0.768
3142543TWELFTH
Solar/Wind Helper
0.039
3143226MDLTHAN
Solar/Wind Helper
0.191
970129AG2-093 GEN
Solar/Wind Harmer
8.29
970661AG2-428 GEN
Solar/Wind Harmer
2.498
965281AG1-393 GEN
Solar/Wind Harmer
1.628
961611AG1-000B GEN
Solar/Wind Harmer
2.314
3151171GRAVELC
Adder
1.226
313506AB2-031 GEN
Solar/Wind Harmer
0.741
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3156081AA2-088 GEN
Solar/Wind Harmer
2.685
961681AG1-008 GEN
Solar/Wind Harmer
6.399
962331AG1-082 GEN
Solar/Wind Harmer
0.998
315737AD1-076 GEN
Solar/Wind Harmer
1.437
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3144873MCLAUGH
Solar/Wind Harmer
0
3146233WITAKRS
Solar/Wind Harmer
0.152
3146233WITAKRS
Solar/Wind Harmer
-0.005
3145933PARMELE
Solar/Wind Harmer
-0.007
970917AG2-570 GEN
Solar/Wind Harmer
17.97
966801AG1-551 GEN
Solar/Wind Harmer
0.898
316405AF2-144 C
Solar/Wind Helper
0.149
3150801HOPHCF4
50/50
0.862
315839AE2-212 C
Solar/Wind Harmer
0.779
315778AD1-151 GEN
Solar/Wind Harmer
11.708
966621AG1-532 GEN
Solar/Wind Harmer
0.201
3145796HORNRTN
Solar/Wind Harmer
-0.036
3145796HORNRTN
Solar/Wind Harmer
-0.009
316317KELFORD C
Solar/Wind Harmer
0.371
3145823KELFORD
Solar/Wind Harmer
-0.008
316210AC1-098 GEN
Solar/Wind Harmer
1.215
3151101ELIZAR3
Adder
6.035
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944601AF1-125 GEN
Solar/Wind Harmer
31.133
316258AE1-075 C
Solar/Wind Helper
0.179
316315AB2-025 C
Solar/Wind Harmer
0.406
315833AF1-017_GEN
Solar/Wind Harmer
2.02
3145796HORNRTN
Solar/Wind Harmer
-0.029
3145796HORNRTN
Solar/Wind Harmer
-0.004
971445AH1-216 GEN
Solar/Wind Harmer
5.552
941031AE2-094 GEN
Solar/Wind Harmer
14.686
970673AG2-436 GEN
Solar/Wind Harmer
16.094
970673AG2-436 GEN
Solar/Wind Harmer
8.149
3152611GOSPORTB
Adder
0.834
3152621GOSPORTC
Adder
0.708
3152601GOSPORTA
Adder
0.653
3151081ELIZAR1
Adder
5.959
3151091ELIZAR2
Adder
5.855
957871AF2-081 GEN
Solar/Wind Harmer
3.603
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
3.117
3145746EVERETS
Solar/Wind Harmer
-0.028
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
970831AG2-522 GEN
Solar/Wind Harmer
3.523
316181AB2-040 GEN
Solar/Wind Harmer
1.285
315742AE1-103 GEN
Solar/Wind Harmer
0.867
971213AH1-066 GEN
50/50
0.52
970657AG2-426 GEN
Solar/Wind Harmer
4.354
970657AG2-426 GEN
Solar/Wind Harmer
0.91
316033AB2-134 GEN
Solar/Wind Harmer
4.127
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.009
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
316236AE1-162_GEN
Solar/Wind Harmer
0.268
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.07
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.029
3137176SLIGO L2192
Solar/Wind Harmer
-0.029
316339AD2-160 GEN
Solar/Wind Harmer
0.485
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3145506HICKORY
Solar/Wind Harmer
-0.029
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
3145493TOT1
Solar/Wind Harmer
0.11
315779AE2-040
50/50
1.868
316132AB2-190 GEN1
Solar/Wind Harmer
1.472
972265AH1-717 GEN
Adder
6.804
3150781HOPHCF2
50/50
0.592
3150761HOPPOLC
50/50
0.376
316240AF1-291 C
Solar/Wind Harmer
0.916
966811AG1-552 GEN
Solar/Wind Harmer
0.946
316426AA2-053 GEN
Solar/Wind Harmer
0.841
3145893MURPHYS
Solar/Wind Harmer
0.228
3145893MURPHYS
Solar/Wind Harmer
-0.015
316065AD1-022 GEN
Solar/Wind Harmer
3.817
972187AH1-678 GEN
Adder
1.891
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316036AC1-147 C
Solar/Wind Harmer
0.198
3150991CHESPKB
Adder
0.686
3150991CHESPKB
Adder
0.669
3142956BIRDNECK
Solar/Wind Harmer
0.389
316018AA1-139 ULT2
Solar/Wind Harmer
0.617
961601AG1-000A GEN
Solar/Wind Harmer
2.813
3145453TOT5
Solar/Wind Harmer
0.066
970603AG2-384 GEN
50/50
5.995
315814AE2-033 C
Solar/Wind Harmer
13.816
316349AD2-085 GEN
Solar/Wind Harmer
0.946
316311AC2-079 GEN
Solar/Wind Harmer
5.341
3151201GRAVEL4
Adder
6.378
3151211GRAVEL5
Adder
6.298
3146043SEABORD
Solar/Wind Harmer
-0.008
315835AF2-110_GEN
Solar/Wind Harmer
1.039
316318V4-068
Solar/Wind Harmer
0.203
961941AG1-037 GEN
Solar/Wind Harmer
0.06
3145683EARLEYS
Solar/Wind Harmer
-0.016
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
3146396TANGLEW
Solar/Wind Harmer
0.135
316319Z2-044 C
Solar/Wind Harmer
0.403
313526AB2-022
Solar/Wind Harmer
0.196
316420AA1-050 GEN
Solar/Wind Harmer
0.815
315813AE1-149 C
Solar/Wind Harmer
10.424
970133AG2-095 GEN
Solar/Wind Harmer
1.847
316083AB2-161 GEN
Solar/Wind Harmer
2.327
316365GEN2_N
Solar/Wind Harmer
0.759
3151221GRAVEL6
Adder
6.371
3145336SMITFLD
Solar/Wind Harmer
-0.004
3147043LAWRENC
Solar/Wind Harmer
-0.005
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146173TUNIS
Solar/Wind Harmer
-0.008
315724AD1-057 GEN
Solar/Wind Harmer
0.46
3156021HOLLOMANSOL
Solar/Wind Harmer
1.057
3146206CASHIE
Solar/Wind Harmer
-0.008
3146376EDENTON
Solar/Wind Harmer
-0.007
3138543CONSLDL
Solar/Wind Harmer
-0.005
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.88
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
971211AH1-065 GEN
50/50
1.039
970659AG2-427 GEN
Solar/Wind Harmer
1.384
3145893MURPHYS
Solar/Wind Harmer
0.057
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.399
3146263WOODLND
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.129
316140AB2-099
Solar/Wind Harmer
0.054
3144536CHRHLND
Solar/Wind Harmer
-0.001
971157AH1-035 GEN
Solar/Wind Harmer
0.944
315614AA2-178 GEN
Solar/Wind Harmer
0.81
316327AA2-057 GEN
Solar/Wind Harmer
0.754
316435W1029_GEN3
Solar/Wind Harmer
1.336
3146516WINFALL
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316320Y1-086
Solar/Wind Harmer
0.427
961601AG1-000A GEN
Solar/Wind Harmer
2.848
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
944581AF1-123 GEN
Solar/Wind Harmer
31.627
316313AB2-026
Solar/Wind Helper
0.199
3151191GRAVEL3
Adder
6.298
315652AC1-086 GEN
Solar/Wind Harmer
10.514
3137643SOCKMAN
Solar/Wind Harmer
-0.035
315607AA1-063A GEN
Solar/Wind Harmer
0.844
965291AG1-394 GEN
Solar/Wind Harmer
0.734
3145893MURPHYS
Solar/Wind Harmer
-0.022
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.07
3145513AHOSKIE
Solar/Wind Harmer
-0.008
944011AF1-069 GEN
Solar/Wind Harmer
4.602
315732AD1-074 GEN1
Solar/Wind Harmer
1.529
315735AD1-075 GEN1
Solar/Wind Harmer
0.765
971967AH1-528 GEN
Solar/Wind Harmer
13.984
316305AF2-043 C
Solar/Wind Harmer
0.224
3146406KITTY HAWK
Solar/Wind Harmer
0.006
970085AG2-068 GEN
Solar/Wind Harmer
4.474
316005AA1-067
Solar/Wind Harmer
0.144
316233AE1-074 FULL
Solar/Wind Helper
0.208
315671AE2-027_GEN
Solar/Wind Harmer
8.385
960081AF2-299 GEN
Solar/Wind Harmer
1.117
962571AG1-106 GEN
Solar/Wind Harmer
1.343
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.009
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.3
316212AC1-099_GEN
Solar/Wind Harmer
0.675
971547AH1-271 GEN
Solar/Wind Harmer
1.919
939411AE1-173 GEN
Solar/Wind Harmer
38.069
316072AD1-144
Solar/Wind Harmer
0.153
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
944591AF1-124 GEN
Solar/Wind Harmer
31.741
316129AC1-054 GEN
Solar/Wind Harmer
0.605
971065AG2-659 GEN
Solar/Wind Harmer
3.382
3143526WINTERP
Solar/Wind Helper
0.709
3143316POE
Solar/Wind Harmer
-0.083
316369SG1_INVT
Solar/Wind Harmer
2.286
946281AF1-292 GEN
Solar/Wind Harmer
0.222
316087AB2-174 GEN
Solar/Wind Harmer
1.345
3146033SCOT NK
Solar/Wind Harmer
-0.031
970601AG2-382 GEN
Solar/Wind Harmer
3.358
315733AD1-074 GEN2
Solar/Wind Harmer
1.529
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.607
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.831
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.197
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
319010AE1-072 C
Solar/Wind Harmer
1.461
970581AG2-369 GEN
Solar/Wind Harmer
3.847
970181AG2-120 GEN
Solar/Wind Harmer
0.933
316023GEN1_S
Solar/Wind Harmer
0.759
971795AH1-408 GEN
Solar/Wind Harmer
6.761
3145336SMITFLD
Solar/Wind Harmer
-0.035
3147043LAWRENC
Adder
0.692
3146173TUNIS
Solar/Wind Harmer
-0.008
315722AD1-056 GEN
Solar/Wind Harmer
0.836
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.008
3145663CRESWEL
Solar/Wind Harmer
-0.021
316375AC2-012 GEN
Solar/Wind Harmer
2.546
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.959
3142053HEARTS
Solar/Wind Harmer
0.084
316336AC2-165 C
Solar/Wind Helper
0.619
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316274AC1-208 GEN
Solar/Wind Harmer
0.84
3146376EDENTON
Solar/Wind Harmer
0.221
3146376EDENTON
Solar/Wind Harmer
0.221
316431W1029_GEN1
Solar/Wind Harmer
1.336
316433W1029_GEN2
Solar/Wind Harmer
1.336
3146386ELIZ CT
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
0.852
316017AA1-139 ULT1
Solar/Wind Harmer
0.583
970933AG2-581 GEN
Solar/Wind Harmer
6.643
970659AG2-427 GEN
Solar/Wind Harmer
7.812
316011AB1-132 GEN
Solar/Wind Harmer
1.955
316093AE2-104_GEN
Solar/Wind Harmer
2.417
3145893MURPHYS
Solar/Wind Harmer
-0.032
3145893MURPHYS
Solar/Wind Harmer
0.242
3146263WOODLND
Solar/Wind Harmer
-0.008
315800Z1-036_GEN1
Solar/Wind Harmer
1.831
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.129
970919AG2-571 GEN
Solar/Wind Harmer
2.275
961671AG1-007 GEN
Solar/Wind Harmer
0.09
316494AC1-189 GEN
Solar/Wind Harmer
0.767
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.006
944641AF1-129 GEN
50/50
142.125
3150791HOPHCF3
50/50
0.592
3144356SAPONY
Solar/Wind Harmer
0.524
315697AD1-025 GEN
Solar/Wind Harmer
2.588
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145783HORNRTN
Solar/Wind Harmer
0.986
3145783HORNRTN
Solar/Wind Harmer
0.789
3145783HORNRTN
Solar/Wind Harmer
0.247
3145783HORNRTN
Solar/Wind Harmer
0.099
972185AH1-677 GEN
Adder
3.783
316316AC1-027 C
Solar/Wind Harmer
0.223
316185AD1-033 GEN
Solar/Wind Harmer
0.757
3145603CNETO
Solar/Wind Harmer
0.044
316263AC1-034 GEN
Solar/Wind Harmer
3.335
3143526WINTERP
Solar/Wind Helper
0.709
CPLELTFEXP_CPLE->PJM
CLTF
3.413
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.422
NYPJM->LTFIMP_NY
CLTF
0.527
LGEELTFEXP_LGEE->PJM
CLTF
0.305
WECLTFEXP_WEC->PJM
CLTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.322
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.462
MECLTFEXP_MEC->PJM
CLTF
0.892
SIGELTFEXP_SIGE->PJM
CLTF
0.026
LAGNLTFEXP_LAGN->PJM
CLTF
2.063
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.093
TVALTFEXP_TVA->PJM
CLTF
1.027

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.8 %
Rating:663.64 MVA
Rating Type:B
MVA to Mitigate:848.14
MW Contribution:7.26
Bus #Bus NameTypeMW Contribution
970129AG2-093 GEN
Solar/Wind Harmer
9.083
965281AG1-393 GEN
Solar/Wind Harmer
1.358
970661AG2-428 GEN
Solar/Wind Harmer
2.575
961611AG1-000B GEN
Solar/Wind Harmer
2.802
3151171GRAVELC
Adder
1.276
313506AB2-031 GEN
Solar/Wind Harmer
0.222
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
961681AG1-008 GEN
Solar/Wind Harmer
4.751
962331AG1-082 GEN
Solar/Wind Harmer
0.665
315737AD1-076 GEN
Solar/Wind Harmer
0.758
3144873MCLAUGH
Solar/Wind Harmer
0.001
3146626S HERTFORD
Solar/Wind Harmer
0.058
315779AE2-040
50/50
1.674
316132AB2-190 GEN1
Solar/Wind Harmer
0.795
972265AH1-717 GEN
Adder
7.085
3151191GRAVEL3
Adder
6.557
315652AC1-086 GEN
Solar/Wind Harmer
8.025
3137643SOCKMAN
Solar/Wind Harmer
0.273
965291AG1-394 GEN
Solar/Wind Harmer
0.291
315607AA1-063A GEN
Solar/Wind Harmer
0.133
3145893MURPHYS
Solar/Wind Harmer
0.173
3145893MURPHYS
Solar/Wind Harmer
0.064
3145513AHOSKIE
Solar/Wind Harmer
0.13
3145513AHOSKIE
Solar/Wind Harmer
0.062
315732AD1-074 GEN1
Solar/Wind Harmer
0.338
315735AD1-075 GEN1
Solar/Wind Harmer
0.169
316305AF2-043 C
Solar/Wind Harmer
0
3146406KITTY HAWK
Solar/Wind Harmer
0.007
316233AE1-074 FULL
Solar/Wind Helper
0.189
971213AH1-066 GEN
50/50
0.607
970657AG2-426 GEN
Solar/Wind Harmer
4.515
970657AG2-426 GEN
Solar/Wind Harmer
0.946
316033AB2-134 GEN
Solar/Wind Harmer
0.007
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.071
3142666NORTHAMPTON
Solar/Wind Harmer
0.043
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.081
971211AH1-065 GEN
50/50
1.214
3151161SURRY 1
50/50
3.505
970659AG2-427 GEN
Solar/Wind Harmer
1.452
3145893MURPHYS
Solar/Wind Harmer
0.107
3145893MURPHYS
Solar/Wind Harmer
0.064
3144536CHRHLND
Solar/Wind Harmer
0.01
957521AF2-046 GEN
Solar/Wind Harmer
4.751
3146263WOODLND
Solar/Wind Harmer
0.063
316463AE2-346 GEN
Solar/Wind Harmer
0.054
316140AB2-099
Solar/Wind Harmer
0.022
971157AH1-035 GEN
Solar/Wind Harmer
0.706
315614AA2-178 GEN
Solar/Wind Harmer
0.335
316435W1029_GEN3
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.058
316327AA2-057 GEN
Solar/Wind Harmer
0.086
316320Y1-086
Solar/Wind Harmer
0
3145963POPLR C
Solar/Wind Harmer
0.057
3146626S HERTFORD
Solar/Wind Harmer
0.058
3146626S HERTFORD
Solar/Wind Harmer
0.058
3130086AYDLETT
Solar/Wind Harmer
0.226
3137176SLIGO L2192
Solar/Wind Harmer
0.224
316315AB2-025 C
Solar/Wind Harmer
0.097
315833AF1-017_GEN
Solar/Wind Harmer
0
971445AH1-216 GEN
Solar/Wind Harmer
5.618
3145796HORNRTN
Solar/Wind Harmer
0.225
3145796HORNRTN
Solar/Wind Harmer
0.028
3152611GOSPORTB
Adder
0.746
3152621GOSPORTC
Adder
0.633
3152601GOSPORTA
Adder
0.584
3151081ELIZAR1
Adder
5.305
3151091ELIZAR2
Adder
5.213
957871AF2-081 GEN
Solar/Wind Harmer
2.802
315671AE2-027_GEN
Solar/Wind Harmer
7.008
960081AF2-299 GEN
Solar/Wind Harmer
0.746
962571AG1-106 GEN
Solar/Wind Harmer
1.038
3145796HORNRTN
Solar/Wind Harmer
0.232
3145796HORNRTN
Solar/Wind Harmer
0.07
3145783HORNRTN
Solar/Wind Harmer
0.064
316072AD1-144
Solar/Wind Harmer
0.022
3145823KELFORD
Solar/Wind Harmer
0.061
971547AH1-271 GEN
Solar/Wind Harmer
1.276
316212AC1-099_GEN
Solar/Wind Harmer
0.309
3143526WINTERP
Solar/Wind Helper
0.642
970133AG2-095 GEN
Solar/Wind Harmer
1.639
315813AE1-149 C
Solar/Wind Harmer
8.459
316083AB2-161 GEN
Solar/Wind Harmer
0.002
3151221GRAVEL6
Adder
6.634
316365GEN2_N
Solar/Wind Harmer
0.199
3145336SMITFLD
Solar/Wind Harmer
0.031
3145273HOLLAND
Solar/Wind Harmer
0.05
3147043LAWRENC
Solar/Wind Harmer
0.04
3146173TUNIS
Solar/Wind Harmer
0.063
315724AD1-057 GEN
Solar/Wind Harmer
0.231
3156021HOLLOMANSOL
Solar/Wind Harmer
0.277
3146206CASHIE
Solar/Wind Harmer
0.06
3146376EDENTON
Solar/Wind Harmer
0.058
3146456SLIGO L269
Solar/Wind Harmer
0.056
971153AH1-033 GEN
Solar/Wind Harmer
0.652
316473AC1-191 GEN
Solar/Wind Helper
0.741
316023GEN1_S
Solar/Wind Harmer
0.199
3145336SMITFLD
Solar/Wind Harmer
0.314
971795AH1-408 GEN
Solar/Wind Harmer
4.663
3147043LAWRENC
Adder
0.601
3146173TUNIS
Solar/Wind Harmer
0.063
3145683EARLEYS
Solar/Wind Harmer
0.062
315722AD1-056 GEN
Solar/Wind Harmer
0.39
3146206CASHIE
Solar/Wind Harmer
0.06
316375AC2-012 GEN
Solar/Wind Harmer
0.001
3145663CRESWEL
Solar/Wind Harmer
0.164
3146456SLIGO L269
Solar/Wind Harmer
0.056
3150781HOPHCF2
50/50
0.692
3150761HOPPOLC
50/50
0.439
316240AF1-291 C
Solar/Wind Harmer
0.003
966811AG1-552 GEN
Solar/Wind Harmer
0.708
316426AA2-053 GEN
Solar/Wind Harmer
0.218
3145893MURPHYS
Solar/Wind Harmer
0.43
3145893MURPHYS
Solar/Wind Harmer
0.115
316065AD1-022 GEN
Solar/Wind Harmer
2.738
316036AC1-147 C
Solar/Wind Harmer
0.011
3150991CHESPKB
Adder
0.613
3150991CHESPKB
Adder
0.599
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3146516WINFALL
Solar/Wind Harmer
0.058
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.001
966871AG1-558 GEN
Solar/Wind Helper
0.164
970659AG2-427 GEN
Solar/Wind Harmer
6.637
316011AB1-132 GEN
Solar/Wind Harmer
1.326
316093AE2-104_GEN
Solar/Wind Harmer
1.146
3145893MURPHYS
Solar/Wind Harmer
0.257
3145893MURPHYS
Solar/Wind Harmer
0.285
3146263WOODLND
Solar/Wind Harmer
0.063
315800Z1-036_GEN1
Solar/Wind Harmer
0
3146516WINFALL
Solar/Wind Harmer
0.187
3146516WINFALL
Solar/Wind Harmer
0.058
970603AG2-384 GEN
50/50
7.264
315814AE2-033 C
Solar/Wind Harmer
9.36
316349AD2-085 GEN
Solar/Wind Harmer
0.064
316311AC2-079 GEN
Solar/Wind Harmer
2.663
3151201GRAVEL4
Adder
6.641
3151211GRAVEL5
Adder
6.557
315835AF2-110_GEN
Solar/Wind Harmer
0.468
3146043SEABORD
Solar/Wind Harmer
0.065
3145683EARLEYS
Solar/Wind Harmer
0.123
3145683EARLEYS
Solar/Wind Harmer
0.062
3145683EARLEYS
Solar/Wind Harmer
0.062
3146206CASHIE
Solar/Wind Harmer
0.06
3146396TANGLEW
Solar/Wind Harmer
0.158
313526AB2-022
Solar/Wind Harmer
0.031
3145963POPLR C
Solar/Wind Harmer
0.057
316174AB2-169 GEN
Solar/Wind Harmer
0.002
3150771HOPHCF1
50/50
0.692
970129AG2-093 GEN
Solar/Wind Harmer
4.274
316458AB2-190 GEN2
Solar/Wind Harmer
0.795
971069AG2-661 GEN
Solar/Wind Harmer
2.412
316381AD1-082 GEN
Solar/Wind Harmer
0.139
970661AG2-428 GEN
Solar/Wind Harmer
12.106
971647AH1-324 GEN
Solar/Wind Harmer
4.953
961611AG1-000B GEN
Solar/Wind Harmer
5.51
3151171GRAVELC
Adder
0.971
316190AA2-174 GEN
Solar/Wind Harmer
0
316246AF1-032 C
Solar/Wind Harmer
0.026
3150981CHESPKA
Adder
0.731
971163AH1-040 GEN
Solar/Wind Harmer
4.686
3130156CHOWAN
Solar/Wind Harmer
0.058
3142543TWELFTH
Solar/Wind Helper
0.038
3143226MDLTHAN
Solar/Wind Helper
0.156
3143316POE
Solar/Wind Harmer
0.789
316369SG1_INVT
Solar/Wind Harmer
0.005
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3146033SCOT NK
Solar/Wind Harmer
0.241
970601AG2-382 GEN
Solar/Wind Harmer
2.233
315733AD1-074 GEN2
Solar/Wind Harmer
0.338
3130546PLYMOUTH
Solar/Wind Harmer
0.059
315816AE2-034 GEN
Solar/Wind Harmer
0.251
3130156CHOWAN
Solar/Wind Harmer
0.058
3130156CHOWAN
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
3146486SUNBURY
Solar/Wind Harmer
0.058
315611Z1-036_GEN2
Solar/Wind Harmer
0
316321Z2-027
Solar/Wind Harmer
0.011
3145176PASQUOTANK
Solar/Wind Harmer
0.035
319010AE1-072 C
Solar/Wind Harmer
0.284
3150801HOPHCF4
50/50
1.007
315839AE2-212 C
Solar/Wind Harmer
0.002
315778AD1-151 GEN
Solar/Wind Harmer
10.852
3145796HORNRTN
Solar/Wind Harmer
0.281
3145796HORNRTN
Solar/Wind Harmer
0.07
316317KELFORD C
Solar/Wind Harmer
0.006
3145823KELFORD
Solar/Wind Harmer
0.061
316210AC1-098 GEN
Solar/Wind Harmer
0.554
3151101ELIZAR3
Adder
5.373
944641AF1-129 GEN
50/50
172.228
3150791HOPHCF3
50/50
0.692
315697AD1-025 GEN
Solar/Wind Harmer
0.143
3144356SAPONY
Solar/Wind Harmer
1.003
3145796HORNRTN
Solar/Wind Harmer
0.211
3145783HORNRTN
Solar/Wind Harmer
1.146
3145783HORNRTN
Solar/Wind Harmer
0.916
3145783HORNRTN
Solar/Wind Harmer
0.286
3145783HORNRTN
Solar/Wind Harmer
0.115
316316AC1-027 C
Solar/Wind Harmer
0.055
3143526WINTERP
Solar/Wind Helper
0.642
316181AB2-040 GEN
Solar/Wind Harmer
0.104
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146173TUNIS
Solar/Wind Harmer
0.063
3146173TUNIS
Solar/Wind Harmer
0.063
316274AC1-208 GEN
Solar/Wind Harmer
0.311
3146376EDENTON
Solar/Wind Harmer
0.259
3146376EDENTON
Solar/Wind Harmer
0.259
316431W1029_GEN1
Solar/Wind Harmer
0
316433W1029_GEN2
Solar/Wind Harmer
0
3146386ELIZ CT
Solar/Wind Harmer
0.057
3146456SLIGO L269
Solar/Wind Harmer
0.998
316017AA1-139 ULT1
Solar/Wind Harmer
0.031
CPLELTFEXP_CPLE->PJM
CLTF
2.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.843
NYPJM->LTFIMP_NY
CLTF
0.415
LGEELTFEXP_LGEE->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.689
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.63
MECLTFEXP_MEC->PJM
CLTF
0.648
SIGELTFEXP_SIGE->PJM
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.583
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.669
TVALTFEXP_TVA->PJM
CLTF
0.786

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T563_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T563_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1030.57
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
3150781HOPHCF2
50/50
0.514
3150761HOPPOLC
50/50
0.326
316240AF1-291 C
Solar/Wind Harmer
0.835
972187AH1-678 GEN
Adder
1.816
966811AG1-552 GEN
Solar/Wind Harmer
0.796
970129AG2-093 GEN
Solar/Wind Harmer
7.195
970661AG2-428 GEN
Solar/Wind Harmer
2.144
965281AG1-393 GEN
Solar/Wind Harmer
1.286
961611AG1-000B GEN
Solar/Wind Harmer
2.004
3151171GRAVELC
Adder
1.061
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.296
961681AG1-008 GEN
Solar/Wind Harmer
5.468
970917AG2-570 GEN
Solar/Wind Harmer
17.182
962331AG1-082 GEN
Solar/Wind Harmer
0.853
315737AD1-076 GEN
Solar/Wind Harmer
1.244
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.006
316405AF2-144 C
Solar/Wind Helper
0.228
3150771HOPHCF1
50/50
0.514
970129AG2-093 GEN
Solar/Wind Harmer
2.914
316458AB2-190 GEN2
Solar/Wind Harmer
1.277
316381AD1-082 GEN
Solar/Wind Harmer
1.126
971069AG2-661 GEN
Solar/Wind Harmer
1.855
970661AG2-428 GEN
Solar/Wind Harmer
12.101
971647AH1-324 GEN
Solar/Wind Harmer
5.156
961611AG1-000B GEN
Solar/Wind Harmer
4.697
3151171GRAVELC
Adder
0.807
316190AA2-174 GEN
Solar/Wind Harmer
0.086
970087AG2-069 GEN
Solar/Wind Harmer
6.413
316246AF1-032 C
Solar/Wind Harmer
0.132
971163AH1-040 GEN
Solar/Wind Harmer
6.116
3150981CHESPKA
Adder
0.723
3130156CHOWAN
Solar/Wind Harmer
-0.006
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3142543TWELFTH
Solar/Wind Helper
0.044
3143226MDLTHAN
Solar/Wind Helper
0.286
971213AH1-066 GEN
50/50
0.451
970657AG2-426 GEN
Solar/Wind Harmer
3.732
970657AG2-426 GEN
Solar/Wind Harmer
0.78
316033AB2-134 GEN
Solar/Wind Harmer
3.578
316236AE1-162_GEN
Solar/Wind Harmer
0.233
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
316339AD2-160 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
316023GEN1_S
Solar/Wind Harmer
0.619
3145336SMITFLD
Solar/Wind Harmer
-0.031
971795AH1-408 GEN
Solar/Wind Harmer
5.557
3147043LAWRENC
Adder
0.569
3146173TUNIS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3146206CASHIE
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.018
316375AC2-012 GEN
Solar/Wind Harmer
2.253
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
0.958
316181AB2-040 GEN
Solar/Wind Harmer
1.066
315742AE1-103 GEN
Solar/Wind Harmer
0.75
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970933AG2-581 GEN
Solar/Wind Harmer
6.3
316274AC1-208 GEN
Solar/Wind Harmer
0.714
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316431W1029_GEN1
Solar/Wind Harmer
1.174
316132AB2-190 GEN1
Solar/Wind Harmer
1.277
972265AH1-717 GEN
Adder
5.888
3151191GRAVEL3
Adder
5.449
315652AC1-086 GEN
Solar/Wind Harmer
8.747
944011AF1-069 GEN
Solar/Wind Harmer
4.452
3137643SOCKMAN
Solar/Wind Harmer
-0.029
971967AH1-528 GEN
Solar/Wind Harmer
13.4
315607AA1-063A GEN
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.627
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.275
3145513AHOSKIE
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.324
315735AD1-075 GEN1
Solar/Wind Harmer
0.662
316305AF2-043 C
Solar/Wind Harmer
0.197
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316233AE1-074 FULL
Solar/Wind Helper
0.327
970659AG2-427 GEN
Solar/Wind Harmer
6.687
316011AB1-132 GEN
Solar/Wind Harmer
1.627
316093AE2-104_GEN
Solar/Wind Harmer
2.111
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
970919AG2-571 GEN
Solar/Wind Harmer
2.175
3146263WOODLND
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.603
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
3145963POPLR C
Solar/Wind Harmer
-0.006
316174AB2-169 GEN
Solar/Wind Harmer
0.977
316433W1029_GEN2
Solar/Wind Harmer
1.174
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
0.753
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
970603AG2-384 GEN
50/50
5.498
315814AE2-033 C
Solar/Wind Harmer
11.018
316349AD2-085 GEN
Solar/Wind Harmer
0.818
316311AC2-079 GEN
Solar/Wind Harmer
4.618
3151201GRAVEL4
Adder
5.519
3151211GRAVEL5
Adder
5.449
315835AF2-110_GEN
Solar/Wind Harmer
0.908
3146043SEABORD
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.174
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
315671AE2-027_GEN
Solar/Wind Harmer
6.365
960081AF2-299 GEN
Solar/Wind Harmer
0.917
962571AG1-106 GEN
Solar/Wind Harmer
1.118
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.023
939411AE1-173 GEN
Solar/Wind Harmer
35.95
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.655
316212AC1-099_GEN
Solar/Wind Harmer
0.575
316072AD1-144
Solar/Wind Harmer
0.133
3143526WINTERP
Solar/Wind Helper
1.113
316315AB2-025 C
Solar/Wind Harmer
0.323
315833AF1-017_GEN
Solar/Wind Harmer
1.746
971445AH1-216 GEN
Solar/Wind Harmer
4.836
941031AE2-094 GEN
Solar/Wind Harmer
14.21
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.003
970673AG2-436 GEN
Solar/Wind Harmer
15.521
970673AG2-436 GEN
Solar/Wind Harmer
7.859
3152611GOSPORTB
Adder
0.738
3152621GOSPORTC
Adder
0.626
3152601GOSPORTA
Adder
0.578
3151081ELIZAR1
Adder
5.276
3151091ELIZAR2
Adder
5.184
957871AF2-081 GEN
Solar/Wind Harmer
3.187
971211AH1-065 GEN
50/50
0.902
970659AG2-427 GEN
Solar/Wind Harmer
1.185
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.468
3146263WOODLND
Solar/Wind Harmer
-0.007
3144536CHRHLND
Solar/Wind Harmer
-0.001
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
971157AH1-035 GEN
Solar/Wind Harmer
0.818
315614AA2-178 GEN
Solar/Wind Harmer
0.704
316435W1029_GEN3
Solar/Wind Harmer
1.174
3143316POE
Solar/Wind Harmer
-0.071
316369SG1_INVT
Solar/Wind Harmer
1.982
946281AF1-292 GEN
Solar/Wind Harmer
0.182
316087AB2-174 GEN
Solar/Wind Harmer
1.112
970581AG2-369 GEN
Solar/Wind Harmer
3.677
3146033SCOT NK
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
2.896
315733AD1-074 GEN2
Solar/Wind Harmer
1.324
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.603
316321Z2-027
Solar/Wind Harmer
0.174
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
319010AE1-072 C
Solar/Wind Harmer
1.291
970133AG2-095 GEN
Solar/Wind Harmer
1.604
315813AE1-149 C
Solar/Wind Harmer
8.895
316083AB2-161 GEN
Solar/Wind Harmer
1.993
316365GEN2_N
Solar/Wind Harmer
0.619
3151221GRAVEL6
Adder
5.513
3145336SMITFLD
Solar/Wind Harmer
-0.003
3145273HOLLAND
Solar/Wind Harmer
-0.005
3147043LAWRENC
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3156021HOLLOMANSOL
Solar/Wind Harmer
0.906
3146206CASHIE
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.778
3150801HOPHCF4
50/50
0.748
315839AE2-212 C
Solar/Wind Harmer
0.693
315778AD1-151 GEN
Solar/Wind Harmer
10.156
966621AG1-532 GEN
Solar/Wind Harmer
0.165
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.316
3145823KELFORD
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.035
3151101ELIZAR3
Adder
5.343
316258AE1-075 C
Solar/Wind Helper
0.274
3146516WINFALL
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
0.376
316327AA2-057 GEN
Solar/Wind Harmer
0.644
3145963POPLR C
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.305
316426AA2-053 GEN
Solar/Wind Harmer
0.709
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
316065AD1-022 GEN
Solar/Wind Harmer
3.296
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.607
3150991CHESPKB
Adder
0.592
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.345
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
944641AF1-129 GEN
50/50
130.338
3150791HOPHCF3
50/50
0.514
3144356SAPONY
Solar/Wind Harmer
0.418
315697AD1-025 GEN
Solar/Wind Harmer
2.244
3145796HORNRTN
Solar/Wind Harmer
-0.022
972185AH1-677 GEN
Adder
3.642
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.664
3145783HORNRTN
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
0.083
316316AC1-027 C
Solar/Wind Harmer
0.198
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Helper
1.113
CPLELTFEXP_CPLE->PJM
CLTF
3.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.003
NYPJM->LTFIMP_NY
CLTF
0.426
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.131
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.998
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.316
TVALTFEXP_TVA->PJM
CLTF
0.892

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: H6T576_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H6T576_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.92 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:1030.57
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
970129AG2-093 GEN
Solar/Wind Harmer
7.195
970661AG2-428 GEN
Solar/Wind Harmer
2.144
965281AG1-393 GEN
Solar/Wind Harmer
1.286
961611AG1-000B GEN
Solar/Wind Harmer
2.004
3151171GRAVELC
Adder
1.061
313506AB2-031 GEN
Solar/Wind Harmer
0.614
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.296
961681AG1-008 GEN
Solar/Wind Harmer
5.468
970917AG2-570 GEN
Solar/Wind Harmer
17.182
962331AG1-082 GEN
Solar/Wind Harmer
0.853
315737AD1-076 GEN
Solar/Wind Harmer
1.244
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.006
316405AF2-144 C
Solar/Wind Helper
0.228
3150771HOPHCF1
50/50
0.514
970129AG2-093 GEN
Solar/Wind Harmer
2.914
316458AB2-190 GEN2
Solar/Wind Harmer
1.277
316381AD1-082 GEN
Solar/Wind Harmer
1.126
971069AG2-661 GEN
Solar/Wind Harmer
1.855
970661AG2-428 GEN
Solar/Wind Harmer
12.101
971647AH1-324 GEN
Solar/Wind Harmer
5.156
961611AG1-000B GEN
Solar/Wind Harmer
4.697
3151171GRAVELC
Adder
0.807
316190AA2-174 GEN
Solar/Wind Harmer
0.086
970087AG2-069 GEN
Solar/Wind Harmer
6.413
316246AF1-032 C
Solar/Wind Harmer
0.132
971163AH1-040 GEN
Solar/Wind Harmer
6.116
3150981CHESPKA
Adder
0.723
3130156CHOWAN
Solar/Wind Harmer
-0.006
316388AE2-253 GEN
Solar/Wind Harmer
0.43
3142543TWELFTH
Solar/Wind Helper
0.044
3143226MDLTHAN
Solar/Wind Helper
0.286
971213AH1-066 GEN
50/50
0.451
970657AG2-426 GEN
Solar/Wind Harmer
3.732
970657AG2-426 GEN
Solar/Wind Harmer
0.78
316033AB2-134 GEN
Solar/Wind Harmer
3.578
316236AE1-162_GEN
Solar/Wind Harmer
0.233
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.059
3146626S HERTFORD
Solar/Wind Harmer
-0.006
316023GEN1_S
Solar/Wind Harmer
0.619
3145336SMITFLD
Solar/Wind Harmer
-0.031
971795AH1-408 GEN
Solar/Wind Harmer
5.557
3147043LAWRENC
Adder
0.569
3146173TUNIS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.707
3146206CASHIE
Solar/Wind Harmer
-0.007
3145663CRESWEL
Solar/Wind Harmer
-0.018
316375AC2-012 GEN
Solar/Wind Harmer
2.253
3146456SLIGO L269
Solar/Wind Harmer
-0.006
316336AC2-165 C
Solar/Wind Helper
0.958
316132AB2-190 GEN1
Solar/Wind Harmer
1.277
972265AH1-717 GEN
Adder
5.888
3151191GRAVEL3
Adder
5.449
315652AC1-086 GEN
Solar/Wind Harmer
8.747
944011AF1-069 GEN
Solar/Wind Harmer
4.452
3137643SOCKMAN
Solar/Wind Harmer
-0.029
971967AH1-528 GEN
Solar/Wind Harmer
13.4
315607AA1-063A GEN
Solar/Wind Harmer
0.714
965291AG1-394 GEN
Solar/Wind Harmer
0.627
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
970085AG2-068 GEN
Solar/Wind Harmer
4.275
3145513AHOSKIE
Solar/Wind Harmer
0.059
3145513AHOSKIE
Solar/Wind Harmer
-0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.324
315735AD1-075 GEN1
Solar/Wind Harmer
0.662
316305AF2-043 C
Solar/Wind Harmer
0.197
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316233AE1-074 FULL
Solar/Wind Helper
0.327
970659AG2-427 GEN
Solar/Wind Harmer
6.687
316011AB1-132 GEN
Solar/Wind Harmer
1.627
316093AE2-104_GEN
Solar/Wind Harmer
2.111
3145893MURPHYS
Solar/Wind Harmer
-0.028
3145893MURPHYS
Solar/Wind Harmer
0.207
970919AG2-571 GEN
Solar/Wind Harmer
2.175
3146263WOODLND
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.603
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
3145963POPLR C
Solar/Wind Harmer
-0.006
316174AB2-169 GEN
Solar/Wind Harmer
0.977
316181AB2-040 GEN
Solar/Wind Harmer
1.066
315742AE1-103 GEN
Solar/Wind Harmer
0.75
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
970933AG2-581 GEN
Solar/Wind Harmer
6.3
316274AC1-208 GEN
Solar/Wind Harmer
0.714
3146376EDENTON
Solar/Wind Harmer
0.193
3146376EDENTON
Solar/Wind Harmer
0.193
316431W1029_GEN1
Solar/Wind Harmer
1.174
316433W1029_GEN2
Solar/Wind Harmer
1.174
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
0.753
316017AA1-139 ULT1
Solar/Wind Harmer
0.516
970603AG2-384 GEN
50/50
5.498
315814AE2-033 C
Solar/Wind Harmer
11.018
316349AD2-085 GEN
Solar/Wind Harmer
0.818
316311AC2-079 GEN
Solar/Wind Harmer
4.618
3151201GRAVEL4
Adder
5.519
3151211GRAVEL5
Adder
5.449
315835AF2-110_GEN
Solar/Wind Harmer
0.908
3146043SEABORD
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.174
961941AG1-037 GEN
Solar/Wind Harmer
0.051
3145683EARLEYS
Solar/Wind Harmer
-0.013
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
315671AE2-027_GEN
Solar/Wind Harmer
6.365
960081AF2-299 GEN
Solar/Wind Harmer
0.917
962571AG1-106 GEN
Solar/Wind Harmer
1.118
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.008
940641AE2-051 GEN
Solar/Wind Harmer
7.023
939411AE1-173 GEN
Solar/Wind Harmer
35.95
3145783HORNRTN
Solar/Wind Harmer
-0.007
3145823KELFORD
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.655
316212AC1-099_GEN
Solar/Wind Harmer
0.575
316072AD1-144
Solar/Wind Harmer
0.133
3143526WINTERP
Solar/Wind Helper
1.113
316315AB2-025 C
Solar/Wind Harmer
0.323
315833AF1-017_GEN
Solar/Wind Harmer
1.746
971445AH1-216 GEN
Solar/Wind Harmer
4.836
941031AE2-094 GEN
Solar/Wind Harmer
14.21
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.003
970673AG2-436 GEN
Solar/Wind Harmer
15.521
970673AG2-436 GEN
Solar/Wind Harmer
7.859
3152611GOSPORTB
Adder
0.738
3152621GOSPORTC
Adder
0.626
3152601GOSPORTA
Adder
0.578
3151081ELIZAR1
Adder
5.276
3151091ELIZAR2
Adder
5.184
957871AF2-081 GEN
Solar/Wind Harmer
3.187
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
316339AD2-160 GEN
Solar/Wind Harmer
0.43
3145506HICKORY
Solar/Wind Harmer
-0.025
3145506HICKORY
Solar/Wind Harmer
-0.015
3145506HICKORY
Solar/Wind Harmer
-0.004
3143316POE
Solar/Wind Harmer
-0.071
316369SG1_INVT
Solar/Wind Harmer
1.982
946281AF1-292 GEN
Solar/Wind Harmer
0.182
316087AB2-174 GEN
Solar/Wind Harmer
1.112
970581AG2-369 GEN
Solar/Wind Harmer
3.677
3146033SCOT NK
Solar/Wind Harmer
-0.026
970601AG2-382 GEN
Solar/Wind Harmer
2.896
315733AD1-074 GEN2
Solar/Wind Harmer
1.324
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.528
3130156CHOWAN
Solar/Wind Harmer
-0.006
3130156CHOWAN
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
3146486SUNBURY
Solar/Wind Harmer
-0.006
315611Z1-036_GEN2
Solar/Wind Harmer
1.603
316321Z2-027
Solar/Wind Harmer
0.174
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
319010AE1-072 C
Solar/Wind Harmer
1.291
970133AG2-095 GEN
Solar/Wind Harmer
1.604
315813AE1-149 C
Solar/Wind Harmer
8.895
316083AB2-161 GEN
Solar/Wind Harmer
1.993
316365GEN2_N
Solar/Wind Harmer
0.619
3151221GRAVEL6
Adder
5.513
3145336SMITFLD
Solar/Wind Harmer
-0.003
3145273HOLLAND
Solar/Wind Harmer
-0.005
3147043LAWRENC
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.389
3156021HOLLOMANSOL
Solar/Wind Harmer
0.906
3146206CASHIE
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.778
3150801HOPHCF4
50/50
0.748
315839AE2-212 C
Solar/Wind Harmer
0.693
315778AD1-151 GEN
Solar/Wind Harmer
10.156
966621AG1-532 GEN
Solar/Wind Harmer
0.165
3145796HORNRTN
Solar/Wind Harmer
-0.03
3145796HORNRTN
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.316
3145823KELFORD
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.035
3151101ELIZAR3
Adder
5.343
316258AE1-075 C
Solar/Wind Helper
0.274
971211AH1-065 GEN
50/50
0.902
970659AG2-427 GEN
Solar/Wind Harmer
1.185
3145893MURPHYS
Solar/Wind Harmer
0.049
3145893MURPHYS
Solar/Wind Harmer
-0.007
957521AF2-046 GEN
Solar/Wind Harmer
5.468
3146263WOODLND
Solar/Wind Harmer
-0.007
3144536CHRHLND
Solar/Wind Harmer
-0.001
316463AE2-346 GEN
Solar/Wind Harmer
0.11
316140AB2-099
Solar/Wind Harmer
0.046
971157AH1-035 GEN
Solar/Wind Harmer
0.818
315614AA2-178 GEN
Solar/Wind Harmer
0.704
316435W1029_GEN3
Solar/Wind Harmer
1.174
3146516WINFALL
Solar/Wind Harmer
-0.006
316320Y1-086
Solar/Wind Harmer
0.376
316327AA2-057 GEN
Solar/Wind Harmer
0.644
3145963POPLR C
Solar/Wind Harmer
-0.006
316313AB2-026
Solar/Wind Helper
0.305
3150781HOPHCF2
50/50
0.514
3150761HOPPOLC
50/50
0.326
316240AF1-291 C
Solar/Wind Harmer
0.835
972187AH1-678 GEN
Adder
1.816
966811AG1-552 GEN
Solar/Wind Harmer
0.796
316426AA2-053 GEN
Solar/Wind Harmer
0.709
3145893MURPHYS
Solar/Wind Harmer
0.195
3145893MURPHYS
Solar/Wind Harmer
-0.013
316065AD1-022 GEN
Solar/Wind Harmer
3.296
316036AC1-147 C
Solar/Wind Harmer
0.176
3150991CHESPKB
Adder
0.607
3150991CHESPKB
Adder
0.592
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.345
316018AA1-139 ULT2
Solar/Wind Harmer
0.546
944641AF1-129 GEN
50/50
130.338
3150791HOPHCF3
50/50
0.514
3144356SAPONY
Solar/Wind Harmer
0.418
315697AD1-025 GEN
Solar/Wind Harmer
2.244
3145796HORNRTN
Solar/Wind Harmer
-0.022
972185AH1-677 GEN
Adder
3.642
3145783HORNRTN
Solar/Wind Harmer
0.831
3145783HORNRTN
Solar/Wind Harmer
0.664
3145783HORNRTN
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
0.083
316316AC1-027 C
Solar/Wind Harmer
0.198
316185AD1-033 GEN
Solar/Wind Harmer
0.671
3143526WINTERP
Solar/Wind Helper
1.113
CPLELTFEXP_CPLE->PJM
CLTF
3.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.003
NYPJM->LTFIMP_NY
CLTF
0.426
LGEELTFEXP_LGEE->PJM
CLTF
0.255
WECLTFEXP_WEC->PJM
CLTF
0.131
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.47
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.998
MECLTFEXP_MEC->PJM
CLTF
0.759
SIGELTFEXP_SIGE->PJM
CLTF
0.022
LAGNLTFEXP_LAGN->PJM
CLTF
1.798
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.316
TVALTFEXP_TVA->PJM
CLTF
0.892

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P4-2: 21712_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 21712_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.66 %
Rating:812.0 MVA
Rating Type:C
MVA to Mitigate:914.78
MW Contribution:7.26
Bus #Bus NameTypeMW Contribution
970129AG2-093 GEN
Solar/Wind Harmer
9.507
965281AG1-393 GEN
Solar/Wind Harmer
1.788
970661AG2-428 GEN
Solar/Wind Harmer
2.575
961611AG1-000B GEN
Solar/Wind Harmer
2.486
3151171GRAVELC
Adder
1.276
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.389
961681AG1-008 GEN
Solar/Wind Harmer
5.65
962331AG1-082 GEN
Solar/Wind Harmer
0.875
315737AD1-076 GEN
Solar/Wind Harmer
1.258
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3150771HOPHCF1
50/50
0.692
970129AG2-093 GEN
Solar/Wind Harmer
3.851
316458AB2-190 GEN2
Solar/Wind Harmer
1.684
971069AG2-661 GEN
Solar/Wind Harmer
2.412
316381AD1-082 GEN
Solar/Wind Harmer
1.373
970661AG2-428 GEN
Solar/Wind Harmer
14.53
971647AH1-324 GEN
Solar/Wind Harmer
6.521
961611AG1-000B GEN
Solar/Wind Harmer
5.826
3151171GRAVELC
Adder
0.971
316190AA2-174 GEN
Solar/Wind Harmer
0.089
316246AF1-032 C
Solar/Wind Harmer
0.133
3150981CHESPKA
Adder
0.731
971163AH1-040 GEN
Solar/Wind Harmer
6.17
3130156CHOWAN
Solar/Wind Harmer
-0.007
3142543TWELFTH
Solar/Wind Helper
0.038
3143226MDLTHAN
Solar/Wind Helper
0.156
316023GEN1_S
Solar/Wind Harmer
0.672
3145336SMITFLD
Solar/Wind Harmer
-0.035
971795AH1-408 GEN
Solar/Wind Harmer
5.894
3147043LAWRENC
Adder
0.601
3146173TUNIS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.724
3146206CASHIE
Solar/Wind Harmer
-0.007
316375AC2-012 GEN
Solar/Wind Harmer
2.277
3145663CRESWEL
Solar/Wind Harmer
-0.018
3146456SLIGO L269
Solar/Wind Harmer
-0.006
315779AE2-040
50/50
1.674
316132AB2-190 GEN1
Solar/Wind Harmer
1.684
972265AH1-717 GEN
Adder
7.085
3151191GRAVEL3
Adder
6.557
315652AC1-086 GEN
Solar/Wind Harmer
9.225
3137643SOCKMAN
Solar/Wind Harmer
-0.03
965291AG1-394 GEN
Solar/Wind Harmer
0.652
315607AA1-063A GEN
Solar/Wind Harmer
0.741
3145893MURPHYS
Solar/Wind Harmer
-0.019
3145893MURPHYS
Solar/Wind Harmer
-0.007
3145513AHOSKIE
Solar/Wind Harmer
0.061
3145513AHOSKIE
Solar/Wind Harmer
-0.007
970659AG2-427 GEN
Solar/Wind Harmer
8.193
316011AB1-132 GEN
Solar/Wind Harmer
1.716
316093AE2-104_GEN
Solar/Wind Harmer
2.226
3145893MURPHYS
Solar/Wind Harmer
-0.029
3145893MURPHYS
Solar/Wind Harmer
0.214
3146263WOODLND
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.611
3146516WINFALL
Solar/Wind Harmer
-0.021
3146516WINFALL
Solar/Wind Harmer
-0.006
3145963POPLR C
Solar/Wind Harmer
-0.006
316174AB2-169 GEN
Solar/Wind Harmer
0.981
316181AB2-040 GEN
Solar/Wind Harmer
1.126
315742AE1-103 GEN
Solar/Wind Harmer
0.786
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.728
3146376EDENTON
Solar/Wind Harmer
0.194
3146376EDENTON
Solar/Wind Harmer
0.194
316431W1029_GEN1
Solar/Wind Harmer
1.178
316433W1029_GEN2
Solar/Wind Harmer
1.178
3146386ELIZ CT
Solar/Wind Harmer
-0.006
3146456SLIGO L269
Solar/Wind Harmer
0.748
316017AA1-139 ULT1
Solar/Wind Harmer
0.512
970603AG2-384 GEN
50/50
7.264
315671AE2-027_GEN
Solar/Wind Harmer
9.228
960081AF2-299 GEN
Solar/Wind Harmer
0.982
962571AG1-106 GEN
Solar/Wind Harmer
1.179
3145796HORNRTN
Solar/Wind Harmer
-0.026
3145796HORNRTN
Solar/Wind Harmer
-0.008
316315AB2-025 C
Solar/Wind Harmer
0.364
315833AF1-017_GEN
Solar/Wind Harmer
1.99
971445AH1-216 GEN
Solar/Wind Harmer
5.548
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
0.746
3152621GOSPORTC
Adder
0.633
3152601GOSPORTA
Adder
0.584
3151081ELIZAR1
Adder
5.305
3151091ELIZAR2
Adder
5.213
957871AF2-081 GEN
Solar/Wind Harmer
3.163
315732AD1-074 GEN1
Solar/Wind Harmer
1.338
315735AD1-075 GEN1
Solar/Wind Harmer
0.669
316305AF2-043 C
Solar/Wind Harmer
0.199
3146406KITTY HAWK
Solar/Wind Harmer
0.005
316233AE1-074 FULL
Solar/Wind Helper
0.189
971213AH1-066 GEN
50/50
0.607
970657AG2-426 GEN
Solar/Wind Harmer
4.526
970657AG2-426 GEN
Solar/Wind Harmer
0.946
316033AB2-134 GEN
Solar/Wind Harmer
4.6
316236AE1-162_GEN
Solar/Wind Harmer
0.266
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.061
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3146626S HERTFORD
Solar/Wind Harmer
-0.006
3130086AYDLETT
Solar/Wind Harmer
-0.025
3137176SLIGO L2192
Solar/Wind Harmer
-0.025
3143316POE
Solar/Wind Harmer
-0.088
316369SG1_INVT
Solar/Wind Harmer
2.549
946281AF1-292 GEN
Solar/Wind Harmer
0.195
316087AB2-174 GEN
Solar/Wind Harmer
1.18
3146033SCOT NK
Solar/Wind Harmer
-0.027
970601AG2-382 GEN
Solar/Wind Harmer
2.94
315814AE2-033 C
Solar/Wind Harmer
12.38
316349AD2-085 GEN
Solar/Wind Harmer
0.932
316311AC2-079 GEN
Solar/Wind Harmer
5.256
3151201GRAVEL4
Adder
6.641
3151211GRAVEL5
Adder
6.557
315835AF2-110_GEN
Solar/Wind Harmer
0.957
3146043SEABORD
Solar/Wind Harmer
-0.007
316318V4-068
Solar/Wind Harmer
0.18
961941AG1-037 GEN
Solar/Wind Harmer
0.053
3145683EARLEYS
Solar/Wind Harmer
-0.014
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146206CASHIE
Solar/Wind Harmer
-0.007
3146396TANGLEW
Solar/Wind Harmer
0.118
313526AB2-022
Solar/Wind Harmer
0.173
970133AG2-095 GEN
Solar/Wind Harmer
2.159
315813AE1-149 C
Solar/Wind Harmer
11.138
316083AB2-161 GEN
Solar/Wind Harmer
2.43
3151221GRAVEL6
Adder
6.634
316365GEN2_N
Solar/Wind Harmer
0.672
3145336SMITFLD
Solar/Wind Harmer
-0.003
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.004
3146173TUNIS
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.398
3156021HOLLOMANSOL
Solar/Wind Harmer
0.925
3146206CASHIE
Solar/Wind Harmer
-0.007
3146376EDENTON
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.006
971153AH1-033 GEN
Solar/Wind Harmer
0.772
316473AC1-191 GEN
Solar/Wind Helper
0.741
315733AD1-074 GEN2
Solar/Wind Harmer
1.338
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.533
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
315611Z1-036_GEN2
Solar/Wind Harmer
1.611
316321Z2-027
Solar/Wind Harmer
0.174
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
319010AE1-072 C
Solar/Wind Harmer
1.283
3145783HORNRTN
Solar/Wind Harmer
-0.007
316072AD1-144
Solar/Wind Harmer
0.14
3145823KELFORD
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.68
316212AC1-099_GEN
Solar/Wind Harmer
0.585
3143526WINTERP
Solar/Wind Helper
0.642
3150801HOPHCF4
50/50
1.007
315839AE2-212 C
Solar/Wind Harmer
0.899
315778AD1-151 GEN
Solar/Wind Harmer
13.204
966621AG1-532 GEN
Solar/Wind Harmer
0.177
3145796HORNRTN
Solar/Wind Harmer
-0.031
3145796HORNRTN
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.323
3145823KELFORD
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.054
3151101ELIZAR3
Adder
5.373
971211AH1-065 GEN
50/50
1.214
970659AG2-427 GEN
Solar/Wind Harmer
1.452
3145893MURPHYS
Solar/Wind Harmer
0.05
3145893MURPHYS
Solar/Wind Harmer
-0.007
3144536CHRHLND
Solar/Wind Harmer
-0.001
957521AF2-046 GEN
Solar/Wind Harmer
5.65
3146263WOODLND
Solar/Wind Harmer
-0.007
316463AE2-346 GEN
Solar/Wind Harmer
0.113
316140AB2-099
Solar/Wind Harmer
0.047
971157AH1-035 GEN
Solar/Wind Harmer
0.826
315614AA2-178 GEN
Solar/Wind Harmer
0.71
316435W1029_GEN3
Solar/Wind Harmer
1.178
3146516WINFALL
Solar/Wind Harmer
-0.006
316327AA2-057 GEN
Solar/Wind Harmer
0.649
316320Y1-086
Solar/Wind Harmer
0.375
3145963POPLR C
Solar/Wind Harmer
-0.006
3150781HOPHCF2
50/50
0.692
3150761HOPPOLC
50/50
0.439
316240AF1-291 C
Solar/Wind Harmer
1.099
966811AG1-552 GEN
Solar/Wind Harmer
0.825
316426AA2-053 GEN
Solar/Wind Harmer
0.734
3145893MURPHYS
Solar/Wind Harmer
0.201
3145893MURPHYS
Solar/Wind Harmer
-0.013
316065AD1-022 GEN
Solar/Wind Harmer
3.341
316036AC1-147 C
Solar/Wind Harmer
0.178
3150991CHESPKB
Adder
0.613
3150991CHESPKB
Adder
0.599
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3146516WINFALL
Solar/Wind Harmer
-0.006
3142956BIRDNECK
Solar/Wind Harmer
0.345
316018AA1-139 ULT2
Solar/Wind Harmer
0.542
966871AG1-558 GEN
Solar/Wind Helper
0.164
944641AF1-129 GEN
50/50
172.228
3150791HOPHCF3
50/50
0.692
315697AD1-025 GEN
Solar/Wind Harmer
2.885
3144356SAPONY
Solar/Wind Harmer
0.47
3145796HORNRTN
Solar/Wind Harmer
-0.024
3145783HORNRTN
Solar/Wind Harmer
0.859
3145783HORNRTN
Solar/Wind Harmer
0.687
3145783HORNRTN
Solar/Wind Harmer
0.215
3145783HORNRTN
Solar/Wind Harmer
0.086
316316AC1-027 C
Solar/Wind Harmer
0.198
3143526WINTERP
Solar/Wind Helper
0.642
CPLELTFEXP_CPLE->PJM
CLTF
2.766
CBM West 2LTFEXP_CBM-W2->PJM
CBM
7.843
NYPJM->LTFIMP_NY
CLTF
0.415
LGEELTFEXP_LGEE->PJM
CLTF
0.215
WECLTFEXP_WEC->PJM
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.689
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.63
MECLTFEXP_MEC->PJM
CLTF
0.648
SIGELTFEXP_SIGE->PJM
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.583
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.669
TVALTFEXP_TVA->PJM
CLTF
0.786

Details for 6CHESTF B-6VARINA 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6VARINA 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.89 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1214.75
MW Contribution:6.7
Bus #Bus NameTypeMW Contribution
315671AE2-027_GEN
Solar/Wind Harmer
10.881
944631AF1-128 GEN
Adder
42.519
960081AF2-299 GEN
Solar/Wind Harmer
1.027
962571AG1-106 GEN
Solar/Wind Harmer
1.241
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
316072AD1-144
Solar/Wind Harmer
0.16
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.847
316212AC1-099_GEN
Solar/Wind Harmer
0.632
939411AE1-173 GEN
Solar/Wind Harmer
34.71
940641AE2-051 GEN
Solar/Wind Harmer
6.466
944591AF1-124 GEN
Solar/Wind Harmer
31.446
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.161
970659AG2-427 GEN
Solar/Wind Harmer
8.328
316011AB1-132 GEN
Solar/Wind Harmer
1.806
316093AE2-104_GEN
Solar/Wind Harmer
2.456
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.232
3146263WOODLND
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.809
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.078
316494AC1-189 GEN
Solar/Wind Harmer
0.717
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
970919AG2-571 GEN
Solar/Wind Harmer
2.009
3150771HOPHCF1
50/50
0.727
970129AG2-093 GEN
Solar/Wind Harmer
4.076
316458AB2-190 GEN2
Solar/Wind Harmer
1.784
971069AG2-661 GEN
Solar/Wind Harmer
2.57
316381AD1-082 GEN
Solar/Wind Harmer
1.399
971647AH1-324 GEN
Solar/Wind Harmer
7.034
970661AG2-428 GEN
Solar/Wind Harmer
14.929
961611AG1-000B GEN
Solar/Wind Harmer
6.338
3151171GRAVELC
Adder
1.07
316190AA2-174 GEN
Solar/Wind Harmer
0.096
3150981CHESPKA
Adder
0.833
316246AF1-032 C
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
-0.007
971163AH1-040 GEN
Solar/Wind Harmer
6.858
316388AE2-253 GEN
Solar/Wind Harmer
0.486
3146293MARTNCO
Solar/Wind Harmer
0.042
3146233WITAKRS
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.197
316049AB1-081 GEN
Solar/Wind Harmer
0.71
970087AG2-069 GEN
Solar/Wind Harmer
5.929
970129AG2-093 GEN
Solar/Wind Harmer
10.063
965281AG1-393 GEN
Solar/Wind Harmer
1.997
970661AG2-428 GEN
Solar/Wind Harmer
2.646
961611AG1-000B GEN
Solar/Wind Harmer
2.704
3151171GRAVELC
Adder
1.407
313506AB2-031 GEN
Solar/Wind Harmer
0.685
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.594
961681AG1-008 GEN
Solar/Wind Harmer
6.136
962331AG1-082 GEN
Solar/Wind Harmer
0.952
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315737AD1-076 GEN
Solar/Wind Harmer
1.39
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.85
3146233WITAKRS
Solar/Wind Harmer
0.141
3146233WITAKRS
Solar/Wind Harmer
-0.005
970917AG2-570 GEN
Solar/Wind Harmer
15.874
971211AH1-065 GEN
50/50
1.275
970659AG2-427 GEN
Solar/Wind Harmer
1.476
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.136
3146263WOODLND
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.123
316140AB2-099
Solar/Wind Harmer
0.051
316435W1029_GEN3
Solar/Wind Harmer
1.33
3146516WINFALL
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.789
971157AH1-035 GEN
Solar/Wind Harmer
0.914
316320Y1-086
Solar/Wind Harmer
0.426
3145963POPLR C
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.701
944581AF1-123 GEN
Solar/Wind Harmer
31.333
961601AG1-000A GEN
Solar/Wind Harmer
2.632
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
971213AH1-066 GEN
50/50
0.638
316033AB2-134 GEN
Solar/Wind Harmer
4.927
970657AG2-426 GEN
Solar/Wind Harmer
4.626
970657AG2-426 GEN
Solar/Wind Harmer
0.967
316236AE1-162_GEN
Solar/Wind Harmer
0.296
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.065
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.029
3137176SLIGO L2192
Solar/Wind Harmer
-0.029
316339AD2-160 GEN
Solar/Wind Harmer
0.486
3145506HICKORY
Solar/Wind Harmer
-0.029
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
316023GEN1_S
Solar/Wind Harmer
0.693
3145336SMITFLD
Solar/Wind Harmer
-0.039
971795AH1-408 GEN
Solar/Wind Harmer
6.247
3147043LAWRENC
Adder
0.641
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.593
3146206CASHIE
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.772
3145663CRESWEL
Solar/Wind Harmer
-0.02
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.887
3142053HEARTS
Solar/Wind Harmer
0.077
970133AG2-095 GEN
Solar/Wind Harmer
2.267
315813AE1-149 C
Solar/Wind Harmer
11.193
316083AB2-161 GEN
Solar/Wind Harmer
2.477
3151221GRAVEL6
Adder
7.315
316365GEN2_N
Solar/Wind Harmer
0.693
3145336SMITFLD
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.005
3142946ENON
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.009
3146206CASHIE
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.425
3146376EDENTON
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.879
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Helper
1.195
316181AB2-040 GEN
Solar/Wind Harmer
1.19
315742AE1-103 GEN
Solar/Wind Harmer
0.861
3142946ENON
Solar/Wind Harmer
-0.001
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.33
316433W1029_GEN2
Solar/Wind Harmer
1.33
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.784
3146456SLIGO L269
Solar/Wind Harmer
0.852
316017AA1-139 ULT1
Solar/Wind Harmer
0.583
970603AG2-384 GEN
50/50
6.703
315814AE2-033 C
Solar/Wind Harmer
12.431
3151201GRAVEL4
Adder
7.323
3151211GRAVEL5
Adder
7.23
316349AD2-085 GEN
Solar/Wind Harmer
0.985
316311AC2-079 GEN
Solar/Wind Harmer
5.558
315835AF2-110_GEN
Solar/Wind Harmer
1.056
3146043SEABORD
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.195
961941AG1-037 GEN
Solar/Wind Harmer
0.057
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.007
3146396TANGLEW
Solar/Wind Harmer
0.134
313526AB2-022
Solar/Wind Harmer
0.196
316319Z2-044 C
Solar/Wind Harmer
0.373
316420AA1-050 GEN
Solar/Wind Harmer
0.759
3150801HOPHCF4
50/50
1.058
315839AE2-212 C
Solar/Wind Harmer
0.847
315778AD1-151 GEN
Solar/Wind Harmer
14.073
966621AG1-532 GEN
Solar/Wind Harmer
0.185
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.351
3145823KELFORD
Solar/Wind Harmer
-0.007
3151101ELIZAR3
Adder
6.126
316210AC1-098 GEN
Solar/Wind Harmer
1.138
944601AF1-125 GEN
Solar/Wind Harmer
30.844
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.213
3150781HOPHCF2
50/50
0.727
3150761HOPPOLC
50/50
0.461
316240AF1-291 C
Solar/Wind Harmer
1.017
966811AG1-552 GEN
Solar/Wind Harmer
0.883
3145893MURPHYS
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
0.788
316036AC1-147 C
Solar/Wind Harmer
0.202
3150991CHESPKB
Adder
0.698
3150991CHESPKB
Adder
0.682
316065AD1-022 GEN
Solar/Wind Harmer
3.68
3142956BIRDNECK
Solar/Wind Harmer
0.393
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316018AA1-139 ULT2
Solar/Wind Harmer
0.617
3145453TOT5
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
2.599
972187AH1-678 GEN
Adder
1.668
966871AG1-558 GEN
Solar/Wind Helper
0.264
315779AE2-040
50/50
1.679
316132AB2-190 GEN1
Solar/Wind Harmer
1.784
972265AH1-717 GEN
Adder
7.812
3151191GRAVEL3
Adder
7.23
315652AC1-086 GEN
Solar/Wind Harmer
9.71
3137643SOCKMAN
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
0.707
315607AA1-063A GEN
Solar/Wind Harmer
0.798
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.066
3145513AHOSKIE
Solar/Wind Harmer
-0.008
316305AF2-043 C
Solar/Wind Harmer
0.225
315732AD1-074 GEN1
Solar/Wind Harmer
1.479
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
3146406KITTY HAWK
Solar/Wind Harmer
0.006
944011AF1-069 GEN
Solar/Wind Harmer
4.041
316005AA1-067
Solar/Wind Harmer
0.135
971967AH1-528 GEN
Solar/Wind Harmer
12.369
970085AG2-068 GEN
Solar/Wind Harmer
3.953
3143316POE
Solar/Wind Harmer
-0.085
316369SG1_INVT
Solar/Wind Harmer
2.73
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.242
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.232
3146033SCOT NK
Solar/Wind Harmer
-0.029
315611Z1-036_GEN2
Solar/Wind Harmer
1.809
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.592
315733AD1-074 GEN2
Solar/Wind Harmer
1.479
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.196
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
319010AE1-072 C
Solar/Wind Harmer
1.46
970181AG2-120 GEN
Solar/Wind Harmer
0.878
970581AG2-369 GEN
Solar/Wind Harmer
3.399
944641AF1-129 GEN
50/50
158.905
3150791HOPHCF3
50/50
0.727
315697AD1-025 GEN
Solar/Wind Harmer
3.09
3144356SAPONY
Solar/Wind Harmer
0.472
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
0.921
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.23
3145783HORNRTN
Solar/Wind Harmer
0.092
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.759
972185AH1-677 GEN
Adder
3.332
3145603CNETO
Solar/Wind Harmer
0.041
316263AC1-034 GEN
Solar/Wind Harmer
3.083
316468AD1-105 GEN
Solar/Wind Helper
0.799
316315AB2-025 C
Solar/Wind Harmer
0.365
315833AF1-017_GEN
Solar/Wind Harmer
2.103
971445AH1-216 GEN
Solar/Wind Harmer
6.169
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
0.85
3152621GOSPORTC
Adder
0.721
3152601GOSPORTA
Adder
0.665
3151081ELIZAR1
Adder
6.048
3151091ELIZAR2
Adder
5.943
957871AF2-081 GEN
Solar/Wind Harmer
3.604
941031AE2-094 GEN
Solar/Wind Harmer
12.896
970673AG2-436 GEN
Solar/Wind Harmer
14.16
970673AG2-436 GEN
Solar/Wind Harmer
7.17
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.915
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
970831AG2-522 GEN
Solar/Wind Harmer
3.291
CPLELTFEXP_CPLE->PJM
CLTF
3.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.877
NYPJM->LTFIMP_NY
CLTF
0.472
LGEELTFEXP_LGEE->PJM
CLTF
0.247
WECLTFEXP_WEC->PJM
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.973
MECLTFEXP_MEC->PJM
CLTF
0.738
SIGELTFEXP_SIGE->PJM
CLTF
0.021
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.34
TVALTFEXP_TVA->PJM
CLTF
0.887

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 557_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 557_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.04 %
Rating:678.68 MVA
Rating Type:B
MVA to Mitigate:719.66
MW Contribution:2.49
Bus #Bus NameTypeMW Contribution
3150861SPRUNCD
50/50
1.107
3141843SHACKLE
50/50
0.611
965281AG1-393 GEN
Solar/Wind Harmer
1.223
316280AD1-041 GEN
Solar/Wind Harmer
0.002
316382AG1-145 C
Solar/Wind Harmer
0.001
3141873WAN 176
Solar/Wind Harmer
1.933
970129AG2-093 GEN
Solar/Wind Harmer
6.305
962971AG1-146 GEN
Solar/Wind Harmer
1.631
316404AE1-155 C
Solar/Wind Harmer
0.022
961611AG1-000B GEN
Solar/Wind Harmer
2.604
3151171GRAVELC
Adder
1.338
970661AG2-428 GEN
Solar/Wind Harmer
1.959
3144873MCLAUGH
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.081
3141906WESTMOR
Solar/Wind Harmer
0.03
315737AD1-076 GEN
Solar/Wind Harmer
0.942
3156081AA2-088 GEN
Solar/Wind Harmer
0.002
961681AG1-008 GEN
Solar/Wind Harmer
5.28
3143096IRON208
Adder
0.293
3143096IRON208
Adder
0.287
962331AG1-082 GEN
Solar/Wind Harmer
0.744
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
313506AB2-031 GEN
Solar/Wind Harmer
0.204
3145933PARMELE
Solar/Wind Harmer
0.064
966801AG1-551 GEN
Solar/Wind Harmer
0.74
970917AG2-570 GEN
Solar/Wind Harmer
5.377
3146233WITAKRS
Solar/Wind Harmer
0.29
3146233WITAKRS
Solar/Wind Harmer
0.039
971167AH1-042 GEN
Solar/Wind Harmer
11.132
970189AG2-124 GEN
Solar/Wind Harmer
3.339
315666AE1-190 GEN
Solar/Wind Harmer
0.001
3138283WHITEMARSH
Solar/Wind Harmer
0.024
316132AB2-190 GEN1
Solar/Wind Harmer
0.558
962981AG1-147 GEN
Solar/Wind Harmer
3.806
972265AH1-717 GEN
Adder
7.425
3151191GRAVEL3
Adder
6.872
3141813NORNECK
Solar/Wind Harmer
0.093
316305AF2-043 C
Solar/Wind Harmer
0.001
3146406KITTY HAWK
Solar/Wind Harmer
0.01
316223AC1-118
Solar/Wind Harmer
0.054
315732AD1-074 GEN1
Solar/Wind Harmer
0.421
315735AD1-075 GEN1
Solar/Wind Harmer
0.211
965291AG1-394 GEN
Solar/Wind Harmer
0.321
3145893MURPHYS
Solar/Wind Harmer
0.192
3145893MURPHYS
Solar/Wind Harmer
0.071
3145513AHOSKIE
Solar/Wind Harmer
0.146
3145513AHOSKIE
Solar/Wind Harmer
0.07
315749AE2-041 GEN
50/50
4.011
970293AG2-193 GEN
Solar/Wind Harmer
2.979
316203AE2-005 GEN
Solar/Wind Harmer
0
316156AD2-030 GEN
Solar/Wind Harmer
0.081
3150921YORKTN3
Adder
2.505
970659AG2-427 GEN
Solar/Wind Harmer
1.003
3150681DARBY 2
50/50
28.859
316033AB2-134 GEN
Solar/Wind Harmer
0.006
970657AG2-426 GEN
Solar/Wind Harmer
3.279
970657AG2-426 GEN
Solar/Wind Harmer
0.687
3150341NORNECKC1
Adder
0.979
3150341NORNECKC1
Adder
0.971
316236AE1-162_GEN
Solar/Wind Harmer
0.001
3145506HICKORY
Solar/Wind Harmer
0.339
3145506HICKORY
Solar/Wind Harmer
0.203
3145506HICKORY
Solar/Wind Harmer
0.051
316339AD2-160 GEN
Solar/Wind Harmer
0.137
3137176SLIGO L2192
Solar/Wind Harmer
0.334
3130086AYDLETT
Solar/Wind Harmer
0.335
3146626S HERTFORD
Solar/Wind Harmer
0.081
3146626S HERTFORD
Solar/Wind Harmer
0.081
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3142666NORTHAMPTON
Solar/Wind Harmer
0.067
3142666NORTHAMPTON
Solar/Wind Harmer
0.04
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.065
3145593CAROLNA
Solar/Wind Harmer
0.081
3145933PARMELE
Solar/Wind Harmer
0.127
3145933PARMELE
Solar/Wind Harmer
0.064
3145493TOT1
Solar/Wind Harmer
0.135
971285AH1-108 GEN
50/50
1.812
316314AB2-024 C
Solar/Wind Harmer
0
3141913WHIT STONE
Solar/Wind Harmer
0.106
970327AG2-215 GEN
Solar/Wind Harmer
3.295
971445AH1-216 GEN
Solar/Wind Harmer
6.5
315833AF1-017_GEN
Solar/Wind Harmer
0
3152611GOSPORTB
Adder
1.096
3152621GOSPORTC
Adder
0.93
3152601GOSPORTA
Adder
0.858
3151081ELIZAR1
Adder
7.878
3151091ELIZAR2
Adder
7.741
957871AF2-081 GEN
Solar/Wind Harmer
4.193
316315AB2-025 C
Solar/Wind Harmer
0.065
941031AE2-094 GEN
Solar/Wind Harmer
12.088
3145796HORNRTN
Solar/Wind Harmer
0.209
3145796HORNRTN
Solar/Wind Harmer
0.026
970673AG2-436 GEN
Solar/Wind Harmer
13.729
970673AG2-436 GEN
Solar/Wind Harmer
9.153
3145746EVERETS
Solar/Wind Harmer
0.244
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
957861AF2-080 GEN
Solar/Wind Harmer
2.574
3145573BETHELC
Solar/Wind Harmer
0.058
3145573BETHELC
Solar/Wind Harmer
0.058
970831AG2-522 GEN
Solar/Wind Harmer
2.461
315671AE2-027_GEN
Solar/Wind Harmer
7.528
944631AF1-128 GEN
Adder
50.091
971317AH1-138 GEN
Solar/Wind Harmer
0.769
3150351NORNECKC2
Adder
0.932
316072AD1-144
Solar/Wind Harmer
0.032
944591AF1-124 GEN
Solar/Wind Harmer
19.166
939411AE1-173 GEN
Solar/Wind Harmer
31.884
971547AH1-271 GEN
Solar/Wind Harmer
1.537
940641AE2-051 GEN
Solar/Wind Harmer
5.708
960081AF2-299 GEN
Solar/Wind Harmer
0.645
3145823KELFORD
Solar/Wind Harmer
0.067
962571AG1-106 GEN
Solar/Wind Harmer
0.951
3145796HORNRTN
Solar/Wind Harmer
0.216
3145796HORNRTN
Solar/Wind Harmer
0.065
3145783HORNRTN
Solar/Wind Harmer
0.064
316212AC1-099_GEN
Solar/Wind Harmer
0.325
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
316129AC1-054 GEN
Solar/Wind Harmer
0.214
3142433PROV 92
50/50
0.256
3142433PROV 92
50/50
0.256
3142946ENON
Solar/Wind Harmer
0.038
3141766HARMONY
Solar/Wind Harmer
1.504
970133AG2-095 GEN
Solar/Wind Harmer
1.03
970009AG2-005 GEN
Solar/Wind Harmer
0.75
315813AE1-149 C
Solar/Wind Harmer
5.226
3151221GRAVEL6
Adder
6.952
316083AB2-161 GEN
Solar/Wind Harmer
0.001
3145336SMITFLD
Solar/Wind Harmer
0.037
3146456SLIGO L269
Solar/Wind Harmer
0.084
971153AH1-033 GEN
Solar/Wind Harmer
0.971
3145273HOLLAND
Solar/Wind Harmer
0.061
3146376EDENTON
Solar/Wind Harmer
0.078
3146206CASHIE
Solar/Wind Harmer
0.072
316365GEN2_N
Solar/Wind Harmer
0.16
3156021HOLLOMANSOL
Solar/Wind Harmer
0.319
3146173TUNIS
Solar/Wind Harmer
0.07
3147043LAWRENC
Solar/Wind Harmer
0.037
315724AD1-057 GEN
Solar/Wind Harmer
0.227
3146073TAR RVR
Solar/Wind Harmer
0.058
3146083TARBORO
Solar/Wind Harmer
0.058
3138543CONSLDL
Solar/Wind Harmer
0.038
971623AH1-311 GEN
Solar/Wind Harmer
0.113
966881AG1-559 GEN
Solar/Wind Helper
0.162
3142433PROV 92
50/50
0.256
3142433PROV 92
50/50
0.256
3142433PROV 92
Solar/Wind Harmer
0.495
3141766HARMONY
Solar/Wind Harmer
0.023
971777AH1-397 GEN
Solar/Wind Harmer
0.298
3145336SMITFLD
Solar/Wind Harmer
0.368
316375AC2-012 GEN
Solar/Wind Harmer
0.002
316294AC1-161 GEN
Solar/Wind Harmer
1.478
3146456SLIGO L269
Solar/Wind Harmer
0.084
3145663CRESWEL
Solar/Wind Harmer
0.211
3146206CASHIE
Solar/Wind Harmer
0.072
316023GEN1_S
Solar/Wind Harmer
0.16
3146173TUNIS
Solar/Wind Harmer
0.07
3145683EARLEYS
Solar/Wind Harmer
0.069
971795AH1-408 GEN
Solar/Wind Harmer
4.241
3147043LAWRENC
Adder
0.561
315722AD1-056 GEN
Solar/Wind Harmer
0.382
972135AH1-637 GEN
Solar/Wind Harmer
0.511
3146083TARBORO
Solar/Wind Harmer
0.058
316359AB2-059 GEN
Solar/Wind Harmer
0.202
3142053HEARTS
Solar/Wind Harmer
0.099
3144536CHRHLND
Solar/Wind Harmer
0.013
315773AC2-141 GEN
Solar/Wind Harmer
3.115
944581AF1-123 GEN
Solar/Wind Harmer
19.098
316320Y1-086
Solar/Wind Harmer
0
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.081
315614AA2-178 GEN
Solar/Wind Harmer
0.432
971157AH1-035 GEN
Solar/Wind Harmer
0.883
3145893MURPHYS
Solar/Wind Harmer
0.119
3145893MURPHYS
Solar/Wind Harmer
0.071
957521AF2-046 GEN
Solar/Wind Harmer
5.28
316463AE2-346 GEN
Solar/Wind Harmer
0.06
316140AB2-099
Solar/Wind Harmer
0.025
3146263WOODLND
Solar/Wind Harmer
0.068
3145963POPLR C
Solar/Wind Harmer
0.068
970737AG2-469 GEN
Solar/Wind Harmer
2.813
316327AA2-057 GEN
Solar/Wind Harmer
0.09
961601AG1-000A GEN
Solar/Wind Harmer
4.009
3145543BTLEBRO
Solar/Wind Harmer
0.056
3145543BTLEBRO
Solar/Wind Harmer
0.056
3150671DARBY 1
50/50
28.825
3150781HOPHCF2
50/50
0.435
316240AF1-291 C
Solar/Wind Harmer
0.001
316036AC1-147 C
Solar/Wind Harmer
0.016
3150991CHESPKB
Adder
0.902
3150991CHESPKB
Adder
0.88
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.002
3146516WINFALL
Solar/Wind Harmer
0.081
3146516WINFALL
Solar/Wind Harmer
0.081
3146516WINFALL
Solar/Wind Harmer
0.081
316065AD1-022 GEN
Solar/Wind Harmer
3.336
3145893MURPHYS
Solar/Wind Harmer
0.477
3145893MURPHYS
Solar/Wind Harmer
0.128
316426AA2-053 GEN
Solar/Wind Harmer
0.222
966811AG1-552 GEN
Solar/Wind Harmer
0.705
972187AH1-678 GEN
Adder
1.79
971223AH1-071 GEN
Solar/Wind Harmer
0.633
3145453TOT5
Solar/Wind Harmer
0.081
961601AG1-000A GEN
Solar/Wind Harmer
1.002
3150851SPRUNCC
50/50
1.107
962861AG1-135 GEN
Solar/Wind Harmer
3.155
3141726DUNNSVL
Solar/Wind Harmer
0.387
970659AG2-427 GEN
Solar/Wind Harmer
4.587
316337AD2-073 GEN
Solar/Wind Harmer
0.074
316093AE2-104_GEN
Solar/Wind Harmer
1.425
3146516WINFALL
Solar/Wind Harmer
0.264
3146516WINFALL
Solar/Wind Harmer
0.081
315800Z1-036_GEN1
Solar/Wind Harmer
0.001
3145893MURPHYS
Solar/Wind Harmer
0.285
3145893MURPHYS
Solar/Wind Harmer
0.317
3146263WOODLND
Solar/Wind Harmer
0.068
3145963POPLR C
Solar/Wind Harmer
0.068
316174AB2-169 GEN
Solar/Wind Harmer
0.002
316011AB1-132 GEN
Solar/Wind Harmer
1.216
970919AG2-571 GEN
Solar/Wind Harmer
2.151
316494AC1-189 GEN
Solar/Wind Harmer
0.202
961671AG1-007 GEN
Solar/Wind Harmer
0.009
3145543BTLEBRO
Solar/Wind Harmer
0.056
3145543BTLEBRO
Solar/Wind Harmer
0.045
315607AA1-063A GEN
Solar/Wind Harmer
0.139
315652AC1-086 GEN
Solar/Wind Harmer
7.356
944011AF1-069 GEN
Solar/Wind Harmer
3.95
3137643SOCKMAN
Solar/Wind Harmer
0.262
971967AH1-528 GEN
Solar/Wind Harmer
10.107
316005AA1-067
Solar/Wind Harmer
0.066
970085AG2-068 GEN
Solar/Wind Harmer
3.212
3141843SHACKLE
50/50
0.611
3150771HOPHCF1
50/50
0.435
3142543TWELFTH
Solar/Wind Harmer
0.019
316159AE1-175 C
Solar/Wind Harmer
0.096
3138133OCRAN
Solar/Wind Harmer
0.064
970129AG2-093 GEN
Solar/Wind Harmer
2.967
316458AB2-190 GEN2
Solar/Wind Harmer
0.558
971069AG2-661 GEN
Solar/Wind Harmer
1.816
3138126ROCKLANDING
Solar/Wind Harmer
0.046
971647AH1-324 GEN
Solar/Wind Harmer
4.236
961611AG1-000B GEN
Solar/Wind Harmer
5.121
3151171GRAVELC
Adder
1.017
316381AD1-082 GEN
Solar/Wind Harmer
0.098
970661AG2-428 GEN
Solar/Wind Harmer
9.208
3150981CHESPKA
Adder
1.075
316246AF1-032 C
Solar/Wind Harmer
0.038
316388AE2-253 GEN
Solar/Wind Harmer
0.264
3130156CHOWAN
Solar/Wind Harmer
0.078
971163AH1-040 GEN
Solar/Wind Harmer
6.044
3143096IRON208
Adder
0.293
316190AA2-174 GEN
Solar/Wind Harmer
0
3146293MARTNCO
Solar/Wind Harmer
0.059
970087AG2-069 GEN
Solar/Wind Harmer
4.819
3143226MDLTHAN
Solar/Wind Harmer
0.059
3145493TOT1
Solar/Wind Harmer
0.259
3146233WITAKRS
Solar/Wind Harmer
0.23
316049AB1-081 GEN
Solar/Wind Harmer
0.322
315759AF1-018 GEN
50/50
4.011
3143873LANEXA
Solar/Wind Harmer
0.071
315662AE1-191 GEN
Solar/Wind Harmer
0.004
3141873WAN 176
Solar/Wind Harmer
0.022
3138133OCRAN
Solar/Wind Harmer
0.032
316369SG1_INVT
Solar/Wind Harmer
0.004
3143316POE
Solar/Wind Harmer
0.383
319010AE1-072 C
Solar/Wind Harmer
0.423
3146486SUNBURY
Solar/Wind Harmer
0.083
3146486SUNBURY
Solar/Wind Harmer
0.083
316321Z2-027
Solar/Wind Harmer
0.015
3145176PASQUOTANK
Solar/Wind Harmer
0.051
315611Z1-036_GEN2
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Harmer
0.078
3130156CHOWAN
Solar/Wind Harmer
0.078
315816AE2-034 GEN
Solar/Wind Harmer
0.324
3130546PLYMOUTH
Solar/Wind Harmer
0.074
315733AD1-074 GEN2
Solar/Wind Harmer
0.421
970601AG2-382 GEN
Solar/Wind Harmer
2.689
316087AB2-174 GEN
Solar/Wind Harmer
0.002
3146033SCOT NK
Solar/Wind Harmer
0.259
970181AG2-120 GEN
Solar/Wind Harmer
0.765
970581AG2-369 GEN
Solar/Wind Harmer
2.763
3150801HOPHCF4
50/50
0.633
315839AE2-212 C
Solar/Wind Harmer
0.001
315778AD1-151 GEN
Solar/Wind Harmer
8.173
3144216WINCHST
Adder
0.374
3150351NORNECKC2
Adder
0.947
3151101ELIZAR3
Adder
7.979
944601AF1-125 GEN
Solar/Wind Harmer
18.804
316317KELFORD C
Solar/Wind Harmer
0.006
3145823KELFORD
Solar/Wind Harmer
0.067
3145796HORNRTN
Solar/Wind Harmer
0.261
3145796HORNRTN
Solar/Wind Harmer
0.065
316210AC1-098 GEN
Solar/Wind Harmer
0.583
3145746EVERETS
Solar/Wind Harmer
0.061
3145746EVERETS
Solar/Wind Harmer
0.061
944641AF1-129 GEN
50/50
58.962
3150791HOPHCF3
50/50
0.435
316075AC2-137 C
Solar/Wind Harmer
0.047
315697AD1-025 GEN
Solar/Wind Harmer
0.113
316077AC2-138 C
Solar/Wind Harmer
0
316316AC1-027 C
Solar/Wind Harmer
0.082
316185AD1-033 GEN
Solar/Wind Harmer
0.002
3144356SAPONY
Solar/Wind Harmer
0.671
3145796HORNRTN
Solar/Wind Harmer
0.196
3145783HORNRTN
Solar/Wind Harmer
1.147
3145783HORNRTN
Solar/Wind Harmer
0.917
3145783HORNRTN
Solar/Wind Harmer
0.287
3145783HORNRTN
Solar/Wind Harmer
0.115
972185AH1-677 GEN
Adder
3.575
3145603CNETO
Solar/Wind Harmer
0.054
316263AC1-034 GEN
Solar/Wind Harmer
2.138
3142433PROV 92
50/50
0.256
3142433PROV 92
50/50
0.256
970603AG2-384 GEN
50/50
2.487
315976AC1-164 GENA
Solar/Wind Harmer
13.74
316169AC1-164_GENC
Solar/Wind Harmer
11.87
315975AC1-164 GENB
Solar/Wind Harmer
0.407
316059AD1-063 C
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.063
3141783LANCAST
Solar/Wind Harmer
0.042
3151201GRAVEL4
Adder
6.96
3151211GRAVEL5
Adder
6.872
316349AD2-085 GEN
Solar/Wind Harmer
0.061
316311AC2-079 GEN
Solar/Wind Harmer
2.536
315835AF2-110_GEN
Solar/Wind Harmer
0.581
313526AB2-022
Solar/Wind Harmer
0.045
3146396TANGLEW
Solar/Wind Harmer
0.227
315814AE2-033 C
Solar/Wind Harmer
6.307
3146206CASHIE
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.138
3145683EARLEYS
Solar/Wind Harmer
0.069
3145683EARLEYS
Solar/Wind Harmer
0.069
3146043SEABORD
Solar/Wind Harmer
0.068
316420AA1-050 GEN
Solar/Wind Harmer
0.002
316319Z2-044 C
Solar/Wind Harmer
0
3142366NRTHEST
50/50
1.511
3150691DARBY 3
50/50
28.96
3150701DARBY 4
50/50
28.893
3142946ENON
Solar/Wind Harmer
0.011
958261AF2-120 GEN
Solar/Wind Harmer
3.238
316017AA1-139 ULT1
Solar/Wind Harmer
0.047
3146456SLIGO L269
Solar/Wind Harmer
1.486
3146386ELIZ CT
Solar/Wind Harmer
0.083
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
315742AE1-103 GEN
Solar/Wind Harmer
0.001
3146376EDENTON
Solar/Wind Harmer
0.347
3146376EDENTON
Solar/Wind Harmer
0.347
3146173TUNIS
Solar/Wind Harmer
0.07
3146173TUNIS
Solar/Wind Harmer
0.07
316181AB2-040 GEN
Solar/Wind Harmer
0.096
316274AC1-208 GEN
Solar/Wind Harmer
0.322
970933AG2-581 GEN
Solar/Wind Harmer
4.888
CPLELTFEXP_CPLE->PJM
CLTF
3.173
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.691
NYPJM->LTFIMP_NY
CLTF
0.509
LGEELTFEXP_LGEE->PJM
CLTF
0.227
WECLTFEXP_WEC->PJM
CLTF
0.114
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.784
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.942
MECLTFEXP_MEC->PJM
CLTF
0.697
SIGELTFEXP_SIGE->PJM
CLTF
0.02
LAGNLTFEXP_LAGN->PJM
CLTF
1.779
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.508
TVALTFEXP_TVA->PJM
CLTF
0.883

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P4-2: 55722_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 55722_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.07 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:872.09
MW Contribution:2.52
Bus #Bus NameTypeMW Contribution
3150861SPRUNCD
50/50
1.12
3141843SHACKLE
50/50
0.636
965281AG1-393 GEN
Solar/Wind Harmer
1.627
316280AD1-041 GEN
Solar/Wind Harmer
0.977
3141873WAN 176
Solar/Wind Harmer
1.503
316382AG1-145 C
Solar/Wind Harmer
0.38
962971AG1-146 GEN
Solar/Wind Harmer
2.241
970129AG2-093 GEN
Solar/Wind Harmer
6.659
316404AE1-155 C
Solar/Wind Harmer
2.224
961611AG1-000B GEN
Solar/Wind Harmer
2.273
3151171GRAVELC
Adder
1.305
970661AG2-428 GEN
Solar/Wind Harmer
1.91
3144873MCLAUGH
Solar/Wind Harmer
0
3141906WESTMOR
Solar/Wind Harmer
-0.004
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3143096IRON208
Adder
0.311
3143096IRON208
Adder
0.305
3156081AA2-088 GEN
Solar/Wind Harmer
2.524
315737AD1-076 GEN
Solar/Wind Harmer
1.477
961681AG1-008 GEN
Solar/Wind Harmer
5.968
962331AG1-082 GEN
Solar/Wind Harmer
0.93
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.573
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.846
970917AG2-570 GEN
Solar/Wind Harmer
16.136
3141843SHACKLE
50/50
0.636
3142543TWELFTH
Solar/Wind Harmer
-0.002
316159AE1-175 C
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
-0.007
970129AG2-093 GEN
Solar/Wind Harmer
2.697
316458AB2-190 GEN2
Solar/Wind Harmer
1.192
971069AG2-661 GEN
Solar/Wind Harmer
1.819
971647AH1-324 GEN
Solar/Wind Harmer
5.523
3138126ROCKLANDING
Solar/Wind Harmer
0.033
961611AG1-000B GEN
Solar/Wind Harmer
5.328
3151171GRAVELC
Adder
0.992
316381AD1-082 GEN
Solar/Wind Harmer
0.953
970661AG2-428 GEN
Solar/Wind Harmer
10.777
3150981CHESPKA
Adder
1.007
316246AF1-032 C
Solar/Wind Harmer
0.18
316388AE2-253 GEN
Solar/Wind Harmer
0.597
3143096IRON208
Adder
0.311
3130156CHOWAN
Solar/Wind Harmer
-0.008
971163AH1-040 GEN
Solar/Wind Harmer
7.503
316190AA2-174 GEN
Solar/Wind Harmer
0.087
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.042
970087AG2-069 GEN
Solar/Wind Harmer
6.025
3142433PROV 92
50/50
0.266
3142433PROV 92
50/50
0.266
3150851SPRUNCC
50/50
1.12
962861AG1-135 GEN
Solar/Wind Harmer
4.349
3141726DUNNSVL
Solar/Wind Harmer
-0.046
970659AG2-427 GEN
Solar/Wind Harmer
5.564
316337AD2-073 GEN
Solar/Wind Harmer
0.271
316093AE2-104_GEN
Solar/Wind Harmer
2.618
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.076
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145893MURPHYS
Solar/Wind Harmer
0.226
3146263WOODLND
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
3142366NRTHEST
50/50
1.525
3150691DARBY 3
50/50
29.344
3150701DARBY 4
50/50
29.275
3142946ENON
Solar/Wind Harmer
-0.001
316487AF1-042 GEN
Solar/Wind Harmer
1.553
958261AF2-120 GEN
Solar/Wind Harmer
4.467
316017AA1-139 ULT1
Solar/Wind Harmer
0.716
3146456SLIGO L269
Solar/Wind Harmer
1.043
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.563
316433W1029_GEN2
Solar/Wind Harmer
1.563
315742AE1-103 GEN
Solar/Wind Harmer
0.883
3146376EDENTON
Solar/Wind Harmer
0.245
3146376EDENTON
Solar/Wind Harmer
0.245
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.995
316274AC1-208 GEN
Solar/Wind Harmer
0.717
970933AG2-581 GEN
Solar/Wind Harmer
6.117
971285AH1-108 GEN
50/50
1.833
316314AB2-024 C
Solar/Wind Harmer
1.164
3141913WHIT STONE
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.353
971445AH1-216 GEN
Solar/Wind Harmer
6.18
315833AF1-017_GEN
Solar/Wind Harmer
1.811
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
3151081ELIZAR1
Adder
7.376
3151091ELIZAR2
Adder
7.248
957871AF2-081 GEN
Solar/Wind Harmer
4.424
316315AB2-025 C
Solar/Wind Harmer
0.237
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
941031AE2-094 GEN
Solar/Wind Harmer
13.124
970673AG2-436 GEN
Solar/Wind Harmer
14.421
970673AG2-436 GEN
Solar/Wind Harmer
7.302
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.508
316174AB2-169 GEN
Solar/Wind Harmer
1.101
970919AG2-571 GEN
Solar/Wind Harmer
2.043
316494AC1-189 GEN
Solar/Wind Harmer
0.686
971167AH1-042 GEN
Solar/Wind Harmer
14.079
315666AE1-190 GEN
Solar/Wind Harmer
0.391
957601AF2-054 GEN
Solar/Wind Harmer
0.379
962981AG1-147 GEN
Solar/Wind Harmer
5.228
316132AB2-190 GEN1
Solar/Wind Harmer
1.192
3138283WHITEMARSH
Solar/Wind Harmer
0.018
3141813NORNECK
Solar/Wind Harmer
-0.011
972265AH1-717 GEN
Adder
7.242
3151191GRAVEL3
Adder
6.703
316223AC1-118
Solar/Wind Harmer
0.241
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.571
315735AD1-075 GEN1
Solar/Wind Harmer
0.786
965291AG1-394 GEN
Solar/Wind Harmer
0.685
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.734
315652AC1-086 GEN
Solar/Wind Harmer
8.107
3137643SOCKMAN
Solar/Wind Harmer
-0.028
944011AF1-069 GEN
Solar/Wind Harmer
4.112
971967AH1-528 GEN
Solar/Wind Harmer
12.672
316005AA1-067
Solar/Wind Harmer
0.133
970085AG2-068 GEN
Solar/Wind Harmer
4.017
3150681DARBY 2
50/50
29.241
316033AB2-134 GEN
Solar/Wind Harmer
3.642
3150341NORNECKC1
Adder
1.031
3150341NORNECKC1
Adder
1.023
970657AG2-426 GEN
Solar/Wind Harmer
3.218
970657AG2-426 GEN
Solar/Wind Harmer
0.673
316236AE1-162_GEN
Solar/Wind Harmer
0.299
3145506HICKORY
Solar/Wind Harmer
-0.035
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.597
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3130086AYDLETT
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.058
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
3142433PROV 92
50/50
0.266
3142433PROV 92
50/50
0.266
970603AG2-384 GEN
50/50
2.518
315976AC1-164 GENA
Solar/Wind Harmer
16.953
316169AC1-164_GENC
Solar/Wind Harmer
14.645
315975AC1-164 GENB
Solar/Wind Harmer
0.502
316059AD1-063 C
Solar/Wind Harmer
0.3
3141783LANCAST
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.005
3151201GRAVEL4
Adder
6.789
3151211GRAVEL5
Adder
6.703
316349AD2-085 GEN
Solar/Wind Harmer
0.848
316311AC2-079 GEN
Solar/Wind Harmer
4.805
315835AF2-110_GEN
Solar/Wind Harmer
1.125
315814AE2-033 C
Solar/Wind Harmer
8.133
313526AB2-022
Solar/Wind Harmer
0.235
3146396TANGLEW
Solar/Wind Harmer
0.16
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.19
961941AG1-037 GEN
Solar/Wind Harmer
0.056
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3142433PROV 92
Solar/Wind Harmer
-0.058
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.55
961951AG1-038 GEN
Solar/Wind Harmer
1.553
3145336SMITFLD
Solar/Wind Harmer
-0.04
316375AC2-012 GEN
Solar/Wind Harmer
3.137
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316294AC1-161 GEN
Solar/Wind Harmer
2.834
3145663CRESWEL
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
0.521
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
972135AH1-637 GEN
Solar/Wind Harmer
0.718
971795AH1-408 GEN
Solar/Wind Harmer
5.157
3147043LAWRENC
Adder
0.539
315722AD1-056 GEN
Solar/Wind Harmer
0.678
3142433PROV 92
50/50
0.266
3142433PROV 92
50/50
0.266
3142946ENON
Solar/Wind Harmer
-0.004
3141766HARMONY
Solar/Wind Harmer
1.18
970133AG2-095 GEN
Solar/Wind Harmer
1.383
970009AG2-005 GEN
Solar/Wind Harmer
1.474
315813AE1-149 C
Solar/Wind Harmer
6.83
3151221GRAVEL6
Adder
6.782
316083AB2-161 GEN
Solar/Wind Harmer
1.686
3145336SMITFLD
Solar/Wind Harmer
-0.004
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.076
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
316365GEN2_N
Solar/Wind Harmer
0.521
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
1.009
3147043LAWRENC
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.373
966881AG1-559 GEN
Solar/Wind Helper
0.157
315759AF1-018 GEN
50/50
4.196
3143873LANEXA
Solar/Wind Harmer
-0.008
315662AE1-191 GEN
Solar/Wind Harmer
1.563
3141873WAN 176
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.004
316369SG1_INVT
Solar/Wind Harmer
2.018
3143316POE
Solar/Wind Harmer
-0.043
319010AE1-072 C
Solar/Wind Harmer
1.784
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.234
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
315611Z1-036_GEN2
Solar/Wind Harmer
2.076
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.648
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.571
970601AG2-382 GEN
Solar/Wind Harmer
3.349
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.023
3146033SCOT NK
Solar/Wind Harmer
-0.028
970181AG2-120 GEN
Solar/Wind Harmer
0.861
970581AG2-369 GEN
Solar/Wind Harmer
3.454
957861AF2-080 GEN
Solar/Wind Harmer
2.791
315671AE2-027_GEN
Solar/Wind Harmer
10.035
944631AF1-128 GEN
Adder
52.71
964211AG1-282 GEN
Solar/Wind Harmer
0.345
971317AH1-138 GEN
Solar/Wind Harmer
1.426
3150351NORNECKC2
Adder
0.981
316072AD1-144
Solar/Wind Harmer
0.188
944591AF1-124 GEN
Solar/Wind Harmer
40.466
939411AE1-173 GEN
Solar/Wind Harmer
39.417
971547AH1-271 GEN
Solar/Wind Harmer
1.914
940641AE2-051 GEN
Solar/Wind Harmer
7.074
960081AF2-299 GEN
Solar/Wind Harmer
0.817
962571AG1-106 GEN
Solar/Wind Harmer
1.036
3145823KELFORD
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.587
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.369
315778AD1-151 GEN
Solar/Wind Harmer
9.957
3150351NORNECKC2
Adder
0.998
3144216WINCHST
Adder
0.364
3151101ELIZAR3
Adder
7.471
944601AF1-125 GEN
Solar/Wind Harmer
39.692
966621AG1-532 GEN
Solar/Wind Harmer
0.147
316317KELFORD C
Solar/Wind Harmer
0.337
3145823KELFORD
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.057
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315749AE2-041 GEN
50/50
4.196
970293AG2-193 GEN
Solar/Wind Harmer
4.016
316203AE2-005 GEN
Solar/Wind Harmer
5.557
316156AD2-030 GEN
Solar/Wind Harmer
0.338
316484AD2-074 GEN
Solar/Wind Harmer
2.968
3150921YORKTN3
Adder
2.437
970659AG2-427 GEN
Solar/Wind Harmer
0.986
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.321
315773AC2-141 GEN
Solar/Wind Harmer
3.665
316320Y1-086
Solar/Wind Harmer
0.511
316435W1029_GEN3
Solar/Wind Harmer
1.563
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.863
970737AG2-469 GEN
Solar/Wind Harmer
3.943
971157AH1-035 GEN
Solar/Wind Harmer
0.976
3145893MURPHYS
Solar/Wind Harmer
0.053
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
5.968
316463AE2-346 GEN
Solar/Wind Harmer
0.12
316140AB2-099
Solar/Wind Harmer
0.05
3146263WOODLND
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.643
3150671DARBY 1
50/50
29.207
316240AF1-291 C
Solar/Wind Harmer
0.391
316036AC1-147 C
Solar/Wind Harmer
0.245
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.482
316018AA1-139 ULT2
Solar/Wind Harmer
0.758
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
316065AD1-022 GEN
Solar/Wind Harmer
3.848
3145893MURPHYS
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
0.712
966811AG1-552 GEN
Solar/Wind Harmer
0.785
971223AH1-071 GEN
Solar/Wind Harmer
0.85
972187AH1-678 GEN
Adder
1.7
944641AF1-129 GEN
50/50
59.705
316075AC2-137 C
Solar/Wind Harmer
0.542
316441AF1-014 GEN
Solar/Wind Harmer
0.888
315697AD1-025 GEN
Solar/Wind Harmer
2.284
316077AC2-138 C
Solar/Wind Harmer
0.233
316316AC1-027 C
Solar/Wind Harmer
0.276
316185AD1-033 GEN
Solar/Wind Harmer
0.942
3144356SAPONY
Solar/Wind Harmer
0.307
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145783HORNRTN
Solar/Wind Harmer
0.822
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
972185AH1-677 GEN
Adder
3.394
CPLELTFEXP_CPLE->PJM
CLTF
3.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.204
NYPJM->LTFIMP_NY
CLTF
0.487
LGEELTFEXP_LGEE->PJM
CLTF
0.212
WECLTFEXP_WEC->PJM
CLTF
0.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.525
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.781
MECLTFEXP_MEC->PJM
CLTF
0.655
SIGELTFEXP_SIGE->PJM
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.182
TVALTFEXP_TVA->PJM
CLTF
0.835

Details for 6NRTHEST-6ELMONT 230.0 kV Ckt 1 line l/o DVP_P4-2: 56722_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
6NRTHEST-6ELMONT 230.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 56722_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.07 %
Rating:830.0 MVA
Rating Type:C
MVA to Mitigate:872.09
MW Contribution:2.52
Bus #Bus NameTypeMW Contribution
3150861SPRUNCD
50/50
1.12
3141843SHACKLE
50/50
0.636
965281AG1-393 GEN
Solar/Wind Harmer
1.627
316280AD1-041 GEN
Solar/Wind Harmer
0.977
3141873WAN 176
Solar/Wind Harmer
1.503
316382AG1-145 C
Solar/Wind Harmer
0.38
962971AG1-146 GEN
Solar/Wind Harmer
2.241
3141843SHACKLE
50/50
0.636
3142543TWELFTH
Solar/Wind Harmer
-0.002
316159AE1-175 C
Solar/Wind Harmer
0.338
3138133OCRAN
Solar/Wind Harmer
-0.007
970129AG2-093 GEN
Solar/Wind Harmer
2.697
316458AB2-190 GEN2
Solar/Wind Harmer
1.192
3142366NRTHEST
50/50
1.525
3150691DARBY 3
50/50
29.344
3150701DARBY 4
50/50
29.275
3142946ENON
Solar/Wind Harmer
-0.001
316487AF1-042 GEN
Solar/Wind Harmer
1.553
958261AF2-120 GEN
Solar/Wind Harmer
4.467
316017AA1-139 ULT1
Solar/Wind Harmer
0.716
3146456SLIGO L269
Solar/Wind Harmer
1.043
3146386ELIZ CT
Solar/Wind Harmer
-0.009
316431W1029_GEN1
Solar/Wind Harmer
1.563
316433W1029_GEN2
Solar/Wind Harmer
1.563
315742AE1-103 GEN
Solar/Wind Harmer
0.883
3146376EDENTON
Solar/Wind Harmer
0.245
3146376EDENTON
Solar/Wind Harmer
0.245
3146173TUNIS
Solar/Wind Harmer
-0.007
3146173TUNIS
Solar/Wind Harmer
-0.007
316181AB2-040 GEN
Solar/Wind Harmer
0.995
316274AC1-208 GEN
Solar/Wind Harmer
0.717
970933AG2-581 GEN
Solar/Wind Harmer
6.117
971167AH1-042 GEN
Solar/Wind Harmer
14.079
315666AE1-190 GEN
Solar/Wind Harmer
0.391
957601AF2-054 GEN
Solar/Wind Harmer
0.379
962981AG1-147 GEN
Solar/Wind Harmer
5.228
316132AB2-190 GEN1
Solar/Wind Harmer
1.192
3138283WHITEMARSH
Solar/Wind Harmer
0.018
3141813NORNECK
Solar/Wind Harmer
-0.011
972265AH1-717 GEN
Adder
7.242
3151191GRAVEL3
Adder
6.703
316223AC1-118
Solar/Wind Harmer
0.241
316305AF2-043 C
Solar/Wind Harmer
0.269
3146406KITTY HAWK
Solar/Wind Harmer
0.007
315732AD1-074 GEN1
Solar/Wind Harmer
1.571
315735AD1-075 GEN1
Solar/Wind Harmer
0.786
965291AG1-394 GEN
Solar/Wind Harmer
0.685
3145893MURPHYS
Solar/Wind Harmer
-0.02
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.065
3145513AHOSKIE
Solar/Wind Harmer
-0.007
315607AA1-063A GEN
Solar/Wind Harmer
0.734
315652AC1-086 GEN
Solar/Wind Harmer
8.107
3137643SOCKMAN
Solar/Wind Harmer
-0.028
944011AF1-069 GEN
Solar/Wind Harmer
4.112
971967AH1-528 GEN
Solar/Wind Harmer
12.672
316005AA1-067
Solar/Wind Harmer
0.133
970085AG2-068 GEN
Solar/Wind Harmer
4.017
3150851SPRUNCC
50/50
1.12
962861AG1-135 GEN
Solar/Wind Harmer
4.349
3141726DUNNSVL
Solar/Wind Harmer
-0.046
970659AG2-427 GEN
Solar/Wind Harmer
5.564
316337AD2-073 GEN
Solar/Wind Harmer
0.271
316093AE2-104_GEN
Solar/Wind Harmer
2.618
3146516WINFALL
Solar/Wind Harmer
-0.028
3146516WINFALL
Solar/Wind Harmer
-0.009
315800Z1-036_GEN1
Solar/Wind Harmer
2.076
3145893MURPHYS
Solar/Wind Harmer
-0.03
3145893MURPHYS
Solar/Wind Harmer
0.226
3146263WOODLND
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316011AB1-132 GEN
Solar/Wind Harmer
1.508
316174AB2-169 GEN
Solar/Wind Harmer
1.101
970919AG2-571 GEN
Solar/Wind Harmer
2.043
316494AC1-189 GEN
Solar/Wind Harmer
0.686
3150681DARBY 2
50/50
29.241
316033AB2-134 GEN
Solar/Wind Harmer
3.642
3150341NORNECKC1
Adder
1.031
3150341NORNECKC1
Adder
1.023
970657AG2-426 GEN
Solar/Wind Harmer
3.218
970657AG2-426 GEN
Solar/Wind Harmer
0.673
316236AE1-162_GEN
Solar/Wind Harmer
0.299
3145506HICKORY
Solar/Wind Harmer
-0.035
3142433PROV 92
50/50
0.266
3142433PROV 92
50/50
0.266
970603AG2-384 GEN
50/50
2.518
315976AC1-164 GENA
Solar/Wind Harmer
16.953
316169AC1-164_GENC
Solar/Wind Harmer
14.645
315975AC1-164 GENB
Solar/Wind Harmer
0.502
316059AD1-063 C
Solar/Wind Harmer
0.3
3141783LANCAST
Solar/Wind Harmer
-0.007
3141783LANCAST
Solar/Wind Harmer
-0.005
3151201GRAVEL4
Adder
6.789
3151211GRAVEL5
Adder
6.703
316349AD2-085 GEN
Solar/Wind Harmer
0.848
316311AC2-079 GEN
Solar/Wind Harmer
4.805
315835AF2-110_GEN
Solar/Wind Harmer
1.125
315814AE2-033 C
Solar/Wind Harmer
8.133
313526AB2-022
Solar/Wind Harmer
0.235
3146396TANGLEW
Solar/Wind Harmer
0.16
3146206CASHIE
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.19
961941AG1-037 GEN
Solar/Wind Harmer
0.056
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
3146043SEABORD
Solar/Wind Harmer
-0.007
3142433PROV 92
50/50
0.266
3142433PROV 92
50/50
0.266
3142433PROV 92
Solar/Wind Harmer
-0.058
3141766HARMONY
Solar/Wind Harmer
-0.003
971777AH1-397 GEN
Solar/Wind Harmer
1.55
961951AG1-038 GEN
Solar/Wind Harmer
1.553
3145336SMITFLD
Solar/Wind Harmer
-0.04
316375AC2-012 GEN
Solar/Wind Harmer
3.137
3146456SLIGO L269
Solar/Wind Harmer
-0.009
316294AC1-161 GEN
Solar/Wind Harmer
2.834
3145663CRESWEL
Solar/Wind Harmer
-0.022
316023GEN1_S
Solar/Wind Harmer
0.521
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.007
3145683EARLEYS
Solar/Wind Harmer
-0.007
972135AH1-637 GEN
Solar/Wind Harmer
0.718
971795AH1-408 GEN
Solar/Wind Harmer
5.157
3147043LAWRENC
Adder
0.539
315722AD1-056 GEN
Solar/Wind Harmer
0.678
3142433PROV 92
50/50
0.266
3142433PROV 92
50/50
0.266
3142946ENON
Solar/Wind Harmer
-0.004
3141766HARMONY
Solar/Wind Harmer
1.18
970133AG2-095 GEN
Solar/Wind Harmer
1.383
970009AG2-005 GEN
Solar/Wind Harmer
1.474
315813AE1-149 C
Solar/Wind Harmer
6.83
3151221GRAVEL6
Adder
6.782
316083AB2-161 GEN
Solar/Wind Harmer
1.686
3145336SMITFLD
Solar/Wind Harmer
-0.004
3146456SLIGO L269
Solar/Wind Harmer
-0.009
971153AH1-033 GEN
Solar/Wind Harmer
1.076
3145273HOLLAND
Solar/Wind Harmer
-0.006
3146376EDENTON
Solar/Wind Harmer
-0.008
316365GEN2_N
Solar/Wind Harmer
0.521
3146206CASHIE
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.007
3156021HOLLOMANSOL
Solar/Wind Harmer
1.009
3147043LAWRENC
Solar/Wind Harmer
-0.004
315724AD1-057 GEN
Solar/Wind Harmer
0.373
966881AG1-559 GEN
Solar/Wind Helper
0.157
315759AF1-018 GEN
50/50
4.196
3143873LANEXA
Solar/Wind Harmer
-0.008
315662AE1-191 GEN
Solar/Wind Harmer
1.563
3141873WAN 176
Solar/Wind Harmer
-0.003
3138133OCRAN
Solar/Wind Harmer
-0.004
316369SG1_INVT
Solar/Wind Harmer
2.018
3143316POE
Solar/Wind Harmer
-0.043
319010AE1-072 C
Solar/Wind Harmer
1.784
3146486SUNBURY
Solar/Wind Harmer
-0.009
3146486SUNBURY
Solar/Wind Harmer
-0.009
316321Z2-027
Solar/Wind Harmer
0.234
3145176PASQUOTANK
Solar/Wind Harmer
-0.005
315611Z1-036_GEN2
Solar/Wind Harmer
2.076
3130156CHOWAN
Solar/Wind Harmer
-0.008
3130156CHOWAN
Solar/Wind Harmer
-0.008
315816AE2-034 GEN
Solar/Wind Harmer
0.648
3130546PLYMOUTH
Solar/Wind Harmer
-0.008
315733AD1-074 GEN2
Solar/Wind Harmer
1.571
970601AG2-382 GEN
Solar/Wind Harmer
3.349
946281AF1-292 GEN
Solar/Wind Harmer
0.163
316087AB2-174 GEN
Solar/Wind Harmer
1.023
3146033SCOT NK
Solar/Wind Harmer
-0.028
970181AG2-120 GEN
Solar/Wind Harmer
0.861
970581AG2-369 GEN
Solar/Wind Harmer
3.454
971069AG2-661 GEN
Solar/Wind Harmer
1.819
971647AH1-324 GEN
Solar/Wind Harmer
5.523
3138126ROCKLANDING
Solar/Wind Harmer
0.033
961611AG1-000B GEN
Solar/Wind Harmer
5.328
3151171GRAVELC
Adder
0.992
316381AD1-082 GEN
Solar/Wind Harmer
0.953
970661AG2-428 GEN
Solar/Wind Harmer
10.777
3150981CHESPKA
Adder
1.007
316246AF1-032 C
Solar/Wind Harmer
0.18
316388AE2-253 GEN
Solar/Wind Harmer
0.597
3143096IRON208
Adder
0.311
3130156CHOWAN
Solar/Wind Harmer
-0.008
971163AH1-040 GEN
Solar/Wind Harmer
7.503
316190AA2-174 GEN
Solar/Wind Harmer
0.087
3143226MDLTHAN
Solar/Wind Harmer
-0.007
3146293MARTNCO
Solar/Wind Harmer
0.042
970087AG2-069 GEN
Solar/Wind Harmer
6.025
970129AG2-093 GEN
Solar/Wind Harmer
6.659
316404AE1-155 C
Solar/Wind Harmer
2.224
961611AG1-000B GEN
Solar/Wind Harmer
2.273
3151171GRAVELC
Adder
1.305
970661AG2-428 GEN
Solar/Wind Harmer
1.91
3144873MCLAUGH
Solar/Wind Harmer
0
3141906WESTMOR
Solar/Wind Harmer
-0.004
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3143096IRON208
Adder
0.311
3143096IRON208
Adder
0.305
3156081AA2-088 GEN
Solar/Wind Harmer
2.524
315737AD1-076 GEN
Solar/Wind Harmer
1.477
961681AG1-008 GEN
Solar/Wind Harmer
5.968
962331AG1-082 GEN
Solar/Wind Harmer
0.93
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
313506AB2-031 GEN
Solar/Wind Harmer
0.573
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.846
970917AG2-570 GEN
Solar/Wind Harmer
16.136
3145506HICKORY
Solar/Wind Harmer
-0.021
3145506HICKORY
Solar/Wind Harmer
-0.005
316339AD2-160 GEN
Solar/Wind Harmer
0.597
3137176SLIGO L2192
Solar/Wind Harmer
-0.035
3130086AYDLETT
Solar/Wind Harmer
-0.035
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3146626S HERTFORD
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.007
971285AH1-108 GEN
50/50
1.833
316314AB2-024 C
Solar/Wind Harmer
1.164
3141913WHIT STONE
Solar/Wind Harmer
-0.012
957831AF2-077 GEN
Solar/Wind Harmer
0.353
971445AH1-216 GEN
Solar/Wind Harmer
6.18
315833AF1-017_GEN
Solar/Wind Harmer
1.811
3152611GOSPORTB
Adder
1.027
3152621GOSPORTC
Adder
0.872
3152601GOSPORTA
Adder
0.804
3151081ELIZAR1
Adder
7.376
3151091ELIZAR2
Adder
7.248
957871AF2-081 GEN
Solar/Wind Harmer
4.424
316315AB2-025 C
Solar/Wind Harmer
0.237
3145796HORNRTN
Solar/Wind Harmer
-0.022
3145796HORNRTN
Solar/Wind Harmer
-0.003
941031AE2-094 GEN
Solar/Wind Harmer
13.124
970673AG2-436 GEN
Solar/Wind Harmer
14.421
970673AG2-436 GEN
Solar/Wind Harmer
7.302
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.791
315671AE2-027_GEN
Solar/Wind Harmer
10.035
944631AF1-128 GEN
Adder
52.71
964211AG1-282 GEN
Solar/Wind Harmer
0.345
971317AH1-138 GEN
Solar/Wind Harmer
1.426
3150351NORNECKC2
Adder
0.981
316072AD1-144
Solar/Wind Harmer
0.188
944591AF1-124 GEN
Solar/Wind Harmer
40.466
939411AE1-173 GEN
Solar/Wind Harmer
39.417
971547AH1-271 GEN
Solar/Wind Harmer
1.914
940641AE2-051 GEN
Solar/Wind Harmer
7.074
960081AF2-299 GEN
Solar/Wind Harmer
0.817
962571AG1-106 GEN
Solar/Wind Harmer
1.036
3145823KELFORD
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.007
3145783HORNRTN
Solar/Wind Harmer
-0.007
316212AC1-099_GEN
Solar/Wind Harmer
0.587
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
315839AE2-212 C
Solar/Wind Harmer
0.369
315778AD1-151 GEN
Solar/Wind Harmer
9.957
3150351NORNECKC2
Adder
0.998
3144216WINCHST
Adder
0.364
3151101ELIZAR3
Adder
7.471
944601AF1-125 GEN
Solar/Wind Harmer
39.692
966621AG1-532 GEN
Solar/Wind Harmer
0.147
316317KELFORD C
Solar/Wind Harmer
0.337
3145823KELFORD
Solar/Wind Harmer
-0.007
3145796HORNRTN
Solar/Wind Harmer
-0.028
3145796HORNRTN
Solar/Wind Harmer
-0.007
316210AC1-098 GEN
Solar/Wind Harmer
1.057
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3142666NORTHAMPTON
Solar/Wind Harmer
-0.004
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
-0.007
3145593CAROLNA
Solar/Wind Harmer
0.058
3145933PARMELE
Solar/Wind Harmer
-0.013
3145933PARMELE
Solar/Wind Harmer
-0.007
315749AE2-041 GEN
50/50
4.196
970293AG2-193 GEN
Solar/Wind Harmer
4.016
316203AE2-005 GEN
Solar/Wind Harmer
5.557
316156AD2-030 GEN
Solar/Wind Harmer
0.338
316484AD2-074 GEN
Solar/Wind Harmer
2.968
3150921YORKTN3
Adder
2.437
970659AG2-427 GEN
Solar/Wind Harmer
0.986
3144536CHRHLND
Solar/Wind Harmer
-0.001
944581AF1-123 GEN
Solar/Wind Harmer
40.321
315773AC2-141 GEN
Solar/Wind Harmer
3.665
316320Y1-086
Solar/Wind Harmer
0.511
316435W1029_GEN3
Solar/Wind Harmer
1.563
3146516WINFALL
Solar/Wind Harmer
-0.009
315614AA2-178 GEN
Solar/Wind Harmer
0.863
970737AG2-469 GEN
Solar/Wind Harmer
3.943
971157AH1-035 GEN
Solar/Wind Harmer
0.976
3145893MURPHYS
Solar/Wind Harmer
0.053
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
5.968
316463AE2-346 GEN
Solar/Wind Harmer
0.12
316140AB2-099
Solar/Wind Harmer
0.05
3146263WOODLND
Solar/Wind Harmer
-0.007
3145963POPLR C
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.643
3150671DARBY 1
50/50
29.207
316240AF1-291 C
Solar/Wind Harmer
0.391
316036AC1-147 C
Solar/Wind Harmer
0.245
3150991CHESPKB
Adder
0.845
3150991CHESPKB
Adder
0.825
3142956BIRDNECK
Solar/Wind Harmer
0.482
316018AA1-139 ULT2
Solar/Wind Harmer
0.758
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
3146516WINFALL
Solar/Wind Harmer
-0.009
316065AD1-022 GEN
Solar/Wind Harmer
3.848
3145893MURPHYS
Solar/Wind Harmer
0.212
3145893MURPHYS
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
0.712
966811AG1-552 GEN
Solar/Wind Harmer
0.785
971223AH1-071 GEN
Solar/Wind Harmer
0.85
972187AH1-678 GEN
Adder
1.7
944641AF1-129 GEN
50/50
59.705
316075AC2-137 C
Solar/Wind Harmer
0.542
316441AF1-014 GEN
Solar/Wind Harmer
0.888
315697AD1-025 GEN
Solar/Wind Harmer
2.284
316077AC2-138 C
Solar/Wind Harmer
0.233
316316AC1-027 C
Solar/Wind Harmer
0.276
316185AD1-033 GEN
Solar/Wind Harmer
0.942
3144356SAPONY
Solar/Wind Harmer
0.307
3145796HORNRTN
Solar/Wind Harmer
-0.021
3145783HORNRTN
Solar/Wind Harmer
0.822
3145783HORNRTN
Solar/Wind Harmer
0.658
3145783HORNRTN
Solar/Wind Harmer
0.205
3145783HORNRTN
Solar/Wind Harmer
0.082
972185AH1-677 GEN
Adder
3.394
CPLELTFEXP_CPLE->PJM
CLTF
3.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.204
NYPJM->LTFIMP_NY
CLTF
0.487
LGEELTFEXP_LGEE->PJM
CLTF
0.212
WECLTFEXP_WEC->PJM
CLTF
0.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.525
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.781
MECLTFEXP_MEC->PJM
CLTF
0.655
SIGELTFEXP_SIGE->PJM
CLTF
0.019
LAGNLTFEXP_LAGN->PJM
CLTF
1.683
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.182
TVALTFEXP_TVA->PJM
CLTF
0.835

Details for 6VARINA-6CHARCTY 230.0 kV Ckt 1 line l/o DVP_P7-1: LN 208-259_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
6VARINA-6CHARCTY 230.0 kV Ckt 1 line
Contingency Name:
DVP_P7-1: LN 208-259_SRT-S
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:100.86 %
Rating:1204.0 MVA
Rating Type:C
MVA to Mitigate:1214.4
MW Contribution:6.7
Bus #Bus NameTypeMW Contribution
315671AE2-027_GEN
Solar/Wind Harmer
10.881
944631AF1-128 GEN
Adder
42.519
960081AF2-299 GEN
Solar/Wind Harmer
1.027
962571AG1-106 GEN
Solar/Wind Harmer
1.241
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.008
316072AD1-144
Solar/Wind Harmer
0.16
3145783HORNRTN
Solar/Wind Harmer
-0.008
3145823KELFORD
Solar/Wind Harmer
-0.007
971547AH1-271 GEN
Solar/Wind Harmer
1.847
316212AC1-099_GEN
Solar/Wind Harmer
0.632
939411AE1-173 GEN
Solar/Wind Harmer
34.71
940641AE2-051 GEN
Solar/Wind Harmer
6.466
944591AF1-124 GEN
Solar/Wind Harmer
31.446
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
316129AC1-054 GEN
Solar/Wind Harmer
0.565
971065AG2-659 GEN
Solar/Wind Harmer
3.161
970659AG2-427 GEN
Solar/Wind Harmer
8.328
316011AB1-132 GEN
Solar/Wind Harmer
1.806
316093AE2-104_GEN
Solar/Wind Harmer
2.456
3145893MURPHYS
Solar/Wind Harmer
-0.031
3145893MURPHYS
Solar/Wind Harmer
0.232
3146263WOODLND
Solar/Wind Harmer
-0.008
3146516WINFALL
Solar/Wind Harmer
-0.024
3146516WINFALL
Solar/Wind Harmer
-0.007
315800Z1-036_GEN1
Solar/Wind Harmer
1.809
3145963POPLR C
Solar/Wind Harmer
-0.007
316174AB2-169 GEN
Solar/Wind Harmer
1.078
316494AC1-189 GEN
Solar/Wind Harmer
0.717
961671AG1-007 GEN
Solar/Wind Harmer
0.084
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.005
970919AG2-571 GEN
Solar/Wind Harmer
2.009
3150771HOPHCF1
50/50
0.727
970129AG2-093 GEN
Solar/Wind Harmer
4.076
316458AB2-190 GEN2
Solar/Wind Harmer
1.784
971069AG2-661 GEN
Solar/Wind Harmer
2.57
316381AD1-082 GEN
Solar/Wind Harmer
1.399
971647AH1-324 GEN
Solar/Wind Harmer
7.034
970661AG2-428 GEN
Solar/Wind Harmer
14.929
961611AG1-000B GEN
Solar/Wind Harmer
6.338
3151171GRAVELC
Adder
1.07
316190AA2-174 GEN
Solar/Wind Harmer
0.096
3150981CHESPKA
Adder
0.833
316246AF1-032 C
Solar/Wind Harmer
0.151
3130156CHOWAN
Solar/Wind Harmer
-0.007
971163AH1-040 GEN
Solar/Wind Harmer
6.858
316388AE2-253 GEN
Solar/Wind Harmer
0.486
3146293MARTNCO
Solar/Wind Harmer
0.042
3146233WITAKRS
Solar/Wind Harmer
-0.027
3145493TOT1
Solar/Wind Harmer
0.197
316049AB1-081 GEN
Solar/Wind Harmer
0.71
970087AG2-069 GEN
Solar/Wind Harmer
5.929
970129AG2-093 GEN
Solar/Wind Harmer
10.063
965281AG1-393 GEN
Solar/Wind Harmer
1.997
970661AG2-428 GEN
Solar/Wind Harmer
2.646
961611AG1-000B GEN
Solar/Wind Harmer
2.704
3151171GRAVELC
Adder
1.407
313506AB2-031 GEN
Solar/Wind Harmer
0.685
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3156081AA2-088 GEN
Solar/Wind Harmer
2.594
961681AG1-008 GEN
Solar/Wind Harmer
6.136
962331AG1-082 GEN
Solar/Wind Harmer
0.952
3144873MCLAUGH
Solar/Wind Harmer
0
3146626S HERTFORD
Solar/Wind Harmer
-0.007
315737AD1-076 GEN
Solar/Wind Harmer
1.39
3145933PARMELE
Solar/Wind Harmer
-0.007
966801AG1-551 GEN
Solar/Wind Harmer
0.85
3146233WITAKRS
Solar/Wind Harmer
0.141
3146233WITAKRS
Solar/Wind Harmer
-0.005
970917AG2-570 GEN
Solar/Wind Harmer
15.874
971211AH1-065 GEN
50/50
1.275
970659AG2-427 GEN
Solar/Wind Harmer
1.476
3144536CHRHLND
Solar/Wind Harmer
-0.001
3145893MURPHYS
Solar/Wind Harmer
0.055
3145893MURPHYS
Solar/Wind Harmer
-0.008
957521AF2-046 GEN
Solar/Wind Harmer
6.136
3146263WOODLND
Solar/Wind Harmer
-0.008
316463AE2-346 GEN
Solar/Wind Harmer
0.123
316140AB2-099
Solar/Wind Harmer
0.051
316435W1029_GEN3
Solar/Wind Harmer
1.33
3146516WINFALL
Solar/Wind Harmer
-0.007
315614AA2-178 GEN
Solar/Wind Harmer
0.789
971157AH1-035 GEN
Solar/Wind Harmer
0.914
316320Y1-086
Solar/Wind Harmer
0.426
3145963POPLR C
Solar/Wind Harmer
-0.007
316327AA2-057 GEN
Solar/Wind Harmer
0.701
944581AF1-123 GEN
Solar/Wind Harmer
31.333
961601AG1-000A GEN
Solar/Wind Harmer
2.632
3145543BTLEBRO
Solar/Wind Harmer
-0.007
3145543BTLEBRO
Solar/Wind Harmer
-0.007
971213AH1-066 GEN
50/50
0.638
316033AB2-134 GEN
Solar/Wind Harmer
4.927
970657AG2-426 GEN
Solar/Wind Harmer
4.626
970657AG2-426 GEN
Solar/Wind Harmer
0.967
316236AE1-162_GEN
Solar/Wind Harmer
0.296
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.008
3142666NORTHAMPTON
Solar/Wind Harmer
-0.005
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
-0.008
3145593CAROLNA
Solar/Wind Harmer
0.065
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3146626S HERTFORD
Solar/Wind Harmer
-0.007
3130086AYDLETT
Solar/Wind Harmer
-0.029
3137176SLIGO L2192
Solar/Wind Harmer
-0.029
316339AD2-160 GEN
Solar/Wind Harmer
0.486
3145506HICKORY
Solar/Wind Harmer
-0.029
3145506HICKORY
Solar/Wind Harmer
-0.017
3145506HICKORY
Solar/Wind Harmer
-0.004
3145933PARMELE
Solar/Wind Harmer
-0.014
3145933PARMELE
Solar/Wind Harmer
-0.007
3145493TOT1
Solar/Wind Harmer
0.103
316023GEN1_S
Solar/Wind Harmer
0.693
3145336SMITFLD
Solar/Wind Harmer
-0.039
971795AH1-408 GEN
Solar/Wind Harmer
6.247
3147043LAWRENC
Adder
0.641
3146173TUNIS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
316375AC2-012 GEN
Solar/Wind Harmer
2.593
3146206CASHIE
Solar/Wind Harmer
-0.007
315722AD1-056 GEN
Solar/Wind Harmer
0.772
3145663CRESWEL
Solar/Wind Harmer
-0.02
3146456SLIGO L269
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316359AB2-059 GEN
Solar/Wind Harmer
0.887
3142053HEARTS
Solar/Wind Harmer
0.077
970133AG2-095 GEN
Solar/Wind Harmer
2.267
315813AE1-149 C
Solar/Wind Harmer
11.193
316083AB2-161 GEN
Solar/Wind Harmer
2.477
3151221GRAVEL6
Adder
7.315
316365GEN2_N
Solar/Wind Harmer
0.693
3145336SMITFLD
Solar/Wind Harmer
-0.004
3145273HOLLAND
Solar/Wind Harmer
-0.006
3147043LAWRENC
Solar/Wind Harmer
-0.005
3142946ENON
Solar/Wind Harmer
-0.003
3146173TUNIS
Solar/Wind Harmer
-0.008
3156021HOLLOMANSOL
Solar/Wind Harmer
1.009
3146206CASHIE
Solar/Wind Harmer
-0.007
315724AD1-057 GEN
Solar/Wind Harmer
0.425
3146376EDENTON
Solar/Wind Harmer
-0.007
3146456SLIGO L269
Solar/Wind Harmer
-0.007
971153AH1-033 GEN
Solar/Wind Harmer
0.879
3138543CONSLDL
Solar/Wind Harmer
-0.004
3146073TAR RVR
Solar/Wind Harmer
-0.007
3146083TARBORO
Solar/Wind Harmer
-0.007
316473AC1-191 GEN
Solar/Wind Helper
1.195
316181AB2-040 GEN
Solar/Wind Harmer
1.19
315742AE1-103 GEN
Solar/Wind Harmer
0.861
3142946ENON
Solar/Wind Harmer
-0.001
3146173TUNIS
Solar/Wind Harmer
-0.008
3146173TUNIS
Solar/Wind Harmer
-0.008
316431W1029_GEN1
Solar/Wind Harmer
1.33
316433W1029_GEN2
Solar/Wind Harmer
1.33
3146376EDENTON
Solar/Wind Harmer
0.217
3146376EDENTON
Solar/Wind Harmer
0.217
3146386ELIZ CT
Solar/Wind Harmer
-0.007
316274AC1-208 GEN
Solar/Wind Harmer
0.784
3146456SLIGO L269
Solar/Wind Harmer
0.852
316017AA1-139 ULT1
Solar/Wind Harmer
0.583
970603AG2-384 GEN
50/50
6.703
315814AE2-033 C
Solar/Wind Harmer
12.431
3151201GRAVEL4
Adder
7.323
3151211GRAVEL5
Adder
7.23
316349AD2-085 GEN
Solar/Wind Harmer
0.985
316311AC2-079 GEN
Solar/Wind Harmer
5.558
315835AF2-110_GEN
Solar/Wind Harmer
1.056
3146043SEABORD
Solar/Wind Harmer
-0.008
316318V4-068
Solar/Wind Harmer
0.195
961941AG1-037 GEN
Solar/Wind Harmer
0.057
3145683EARLEYS
Solar/Wind Harmer
-0.015
3145683EARLEYS
Solar/Wind Harmer
-0.008
3145683EARLEYS
Solar/Wind Harmer
-0.008
3146206CASHIE
Solar/Wind Harmer
-0.007
3146396TANGLEW
Solar/Wind Harmer
0.134
313526AB2-022
Solar/Wind Harmer
0.196
316319Z2-044 C
Solar/Wind Harmer
0.373
316420AA1-050 GEN
Solar/Wind Harmer
0.759
3150801HOPHCF4
50/50
1.058
315839AE2-212 C
Solar/Wind Harmer
0.847
315778AD1-151 GEN
Solar/Wind Harmer
14.073
966621AG1-532 GEN
Solar/Wind Harmer
0.185
3145796HORNRTN
Solar/Wind Harmer
-0.033
3145796HORNRTN
Solar/Wind Harmer
-0.008
316317KELFORD C
Solar/Wind Harmer
0.351
3145823KELFORD
Solar/Wind Harmer
-0.007
3151101ELIZAR3
Adder
6.126
316210AC1-098 GEN
Solar/Wind Harmer
1.138
944601AF1-125 GEN
Solar/Wind Harmer
30.844
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3144216WINCHST
Adder
0.213
3150781HOPHCF2
50/50
0.727
3150761HOPPOLC
50/50
0.461
316240AF1-291 C
Solar/Wind Harmer
1.017
966811AG1-552 GEN
Solar/Wind Harmer
0.883
3145893MURPHYS
Solar/Wind Harmer
0.219
3145893MURPHYS
Solar/Wind Harmer
-0.014
316426AA2-053 GEN
Solar/Wind Harmer
0.788
316036AC1-147 C
Solar/Wind Harmer
0.202
3150991CHESPKB
Adder
0.698
3150991CHESPKB
Adder
0.682
316065AD1-022 GEN
Solar/Wind Harmer
3.68
3142956BIRDNECK
Solar/Wind Harmer
0.393
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
3146516WINFALL
Solar/Wind Harmer
-0.007
316018AA1-139 ULT2
Solar/Wind Harmer
0.617
3145453TOT5
Solar/Wind Harmer
0.062
961601AG1-000A GEN
Solar/Wind Harmer
2.599
972187AH1-678 GEN
Adder
1.668
966871AG1-558 GEN
Solar/Wind Helper
0.264
315779AE2-040
50/50
1.679
316132AB2-190 GEN1
Solar/Wind Harmer
1.784
972265AH1-717 GEN
Adder
7.812
3151191GRAVEL3
Adder
7.23
315652AC1-086 GEN
Solar/Wind Harmer
9.71
3137643SOCKMAN
Solar/Wind Harmer
-0.032
965291AG1-394 GEN
Solar/Wind Harmer
0.707
315607AA1-063A GEN
Solar/Wind Harmer
0.798
3145893MURPHYS
Solar/Wind Harmer
-0.021
3145893MURPHYS
Solar/Wind Harmer
-0.008
3145513AHOSKIE
Solar/Wind Harmer
0.066
3145513AHOSKIE
Solar/Wind Harmer
-0.008
3143316POE
Solar/Wind Harmer
-0.085
316369SG1_INVT
Solar/Wind Harmer
2.73
946281AF1-292 GEN
Solar/Wind Harmer
0.204
316087AB2-174 GEN
Solar/Wind Harmer
1.242
3146486SUNBURY
Solar/Wind Harmer
-0.007
3146486SUNBURY
Solar/Wind Harmer
-0.007
970601AG2-382 GEN
Solar/Wind Harmer
3.232
3146033SCOT NK
Solar/Wind Harmer
-0.029
315611Z1-036_GEN2
Solar/Wind Harmer
1.809
3130156CHOWAN
Solar/Wind Harmer
-0.007
3130156CHOWAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
0.592
944641AF1-129 GEN
50/50
158.905
3150791HOPHCF3
50/50
0.727
315697AD1-025 GEN
Solar/Wind Harmer
3.09
3144356SAPONY
Solar/Wind Harmer
0.472
3145796HORNRTN
Solar/Wind Harmer
-0.025
3145783HORNRTN
Solar/Wind Harmer
0.921
3145783HORNRTN
Solar/Wind Harmer
0.737
3145783HORNRTN
Solar/Wind Harmer
0.23
3145783HORNRTN
Solar/Wind Harmer
0.092
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.759
972185AH1-677 GEN
Adder
3.332
3145603CNETO
Solar/Wind Harmer
0.041
316263AC1-034 GEN
Solar/Wind Harmer
3.083
316468AD1-105 GEN
Solar/Wind Helper
0.799
316315AB2-025 C
Solar/Wind Harmer
0.365
315833AF1-017_GEN
Solar/Wind Harmer
2.103
971445AH1-216 GEN
Solar/Wind Harmer
6.169
3145796HORNRTN
Solar/Wind Harmer
-0.027
3145796HORNRTN
Solar/Wind Harmer
-0.003
3152611GOSPORTB
Adder
0.85
3152621GOSPORTC
Adder
0.721
3152601GOSPORTA
Adder
0.665
3151081ELIZAR1
Adder
6.048
3151091ELIZAR2
Adder
5.943
957871AF2-081 GEN
Solar/Wind Harmer
3.604
315733AD1-074 GEN2
Solar/Wind Harmer
1.479
3130546PLYMOUTH
Solar/Wind Harmer
-0.007
316321Z2-027
Solar/Wind Harmer
0.196
3145176PASQUOTANK
Solar/Wind Harmer
-0.004
319010AE1-072 C
Solar/Wind Harmer
1.46
970181AG2-120 GEN
Solar/Wind Harmer
0.878
970581AG2-369 GEN
Solar/Wind Harmer
3.399
316305AF2-043 C
Solar/Wind Harmer
0.225
315732AD1-074 GEN1
Solar/Wind Harmer
1.479
315735AD1-075 GEN1
Solar/Wind Harmer
0.74
3146406KITTY HAWK
Solar/Wind Harmer
0.006
944011AF1-069 GEN
Solar/Wind Harmer
4.041
316005AA1-067
Solar/Wind Harmer
0.135
971967AH1-528 GEN
Solar/Wind Harmer
12.369
970085AG2-068 GEN
Solar/Wind Harmer
3.953
941031AE2-094 GEN
Solar/Wind Harmer
12.896
970673AG2-436 GEN
Solar/Wind Harmer
14.16
970673AG2-436 GEN
Solar/Wind Harmer
7.17
3145746EVERETS
Solar/Wind Harmer
-0.026
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
3145746EVERETS
Solar/Wind Harmer
-0.007
957861AF2-080 GEN
Solar/Wind Harmer
2.915
3145573BETHELC
Solar/Wind Harmer
-0.007
3145573BETHELC
Solar/Wind Harmer
-0.007
970831AG2-522 GEN
Solar/Wind Harmer
3.291
CPLELTFEXP_CPLE->PJM
CLTF
3.081
CBM West 2LTFEXP_CBM-W2->PJM
CBM
8.877
NYPJM->LTFIMP_NY
CLTF
0.472
LGEELTFEXP_LGEE->PJM
CLTF
0.247
WECLTFEXP_WEC->PJM
CLTF
0.126
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.235
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.973
MECLTFEXP_MEC->PJM
CLTF
0.738
SIGELTFEXP_SIGE->PJM
CLTF
0.021
LAGNLTFEXP_LAGN->PJM
CLTF
1.785
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.34
TVALTFEXP_TVA->PJM
CLTF
0.887

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:172.64 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5559.88
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
3143526WINTERP
Solar/Wind Harmer
1.342
940641AE2-051 GEN
Solar/Wind Harmer
19.964
939411AE1-173 GEN
Solar/Wind Harmer
105.426
315671AE2-027_GEN
Solar/Wind Harmer
15.496
944591AF1-124 GEN
Solar/Wind Harmer
54.408
944631AF1-128 GEN
Adder
114.357
316072AD1-144
Solar/Wind Harmer
0.086
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
970659AG2-427 GEN
Solar/Wind Harmer
11.613
316093AE2-104_GEN
Solar/Wind Harmer
3.974
3146516WINFALL
Solar/Wind Harmer
0.754
3146516WINFALL
Solar/Wind Harmer
0.233
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
970919AG2-571 GEN
Solar/Wind Harmer
8.004
3145893MURPHYS
Solar/Wind Harmer
0.862
3145893MURPHYS
Solar/Wind Harmer
0.958
962861AG1-135 GEN
Solar/Wind Harmer
6.774
3146263WOODLND
Solar/Wind Harmer
0.21
315693AD1-088 GEN
Solar/Wind Harmer
10.091
962491AG1-098 GEN
Solar/Wind Harmer
11.959
316011AB1-132 GEN
Solar/Wind Harmer
3.796
3145963POPLR C
Solar/Wind Harmer
0.208
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.006
3143096IRON208
50/50
1.078
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
0.265
3147666LOUISA
Solar/Wind Harmer
1.028
3142543TWELFTH
Solar/Wind Harmer
0.023
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.274
3150981CHESPKA
Adder
3
971647AH1-324 GEN
Solar/Wind Harmer
10.242
316381AD1-082 GEN
Solar/Wind Harmer
0.25
961611AG1-000B GEN
Solar/Wind Harmer
12.579
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
23.801
316388AE2-253 GEN
Solar/Wind Harmer
0.747
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316246AF1-032 C
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.205
3141843SHACKLE
Adder
1.16
3130156CHOWAN
Solar/Wind Harmer
0.227
970087AG2-069 GEN
Solar/Wind Harmer
17.934
316337AD2-073 GEN
Solar/Wind Harmer
0.169
316494AC1-189 GEN
Solar/Wind Harmer
0.651
961671AG1-007 GEN
Solar/Wind Harmer
0.029
963171AG1-166 GEN
Solar/Wind Harmer
1.014
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.149
3146776BUCKING
Solar/Wind Harmer
0.072
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3147666LOUISA
Solar/Wind Harmer
0.591
965281AG1-393 GEN
Solar/Wind Harmer
2.585
970129AG2-093 GEN
Solar/Wind Harmer
14.547
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.396
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
316382AG1-145 C
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.231
3141843SHACKLE
Adder
1.16
316405AF2-144 C
Solar/Wind Harmer
0.002
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141873WAN 176
Solar/Wind Harmer
4.011
970917AG2-570 GEN
Solar/Wind Harmer
20.009
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
3152331SURRY 2
50/50
9.99
316192AB2-158 GEN
Solar/Wind Harmer
1.415
316294AC1-161 GEN
Solar/Wind Harmer
4.211
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.959
3146456SLIGO L269
Solar/Wind Harmer
0.238
3142416OLDCHRC
Solar/Wind Harmer
0.618
3142416OLDCHRC
Solar/Wind Harmer
0.237
3142433PROV 92
Solar/Wind Harmer
0.928
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141766HARMONY
Solar/Wind Harmer
0.045
966881AG1-559 GEN
Solar/Wind Harmer
0.26
3145663CRESWEL
Solar/Wind Harmer
0.622
316023GEN1_S
Solar/Wind Harmer
0.489
972197AH1-683 GEN
Adder
4.553
316336AC2-165 C
Solar/Wind Harmer
0.008
3146206CASHIE
Solar/Wind Harmer
0.216
3146173TUNIS
Solar/Wind Harmer
0.213
3145683EARLEYS
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
13.893
3147043LAWRENC
Adder
1.868
315722AD1-056 GEN
Solar/Wind Harmer
1.237
970937AG2-583 GEN
Solar/Wind Harmer
11.696
3146083TARBORO
Solar/Wind Harmer
0.19
316359AB2-059 GEN
Solar/Wind Harmer
0.672
3142053HEARTS
Solar/Wind Harmer
0.329
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.431
315813AE1-149 C
Solar/Wind Harmer
12.873
970133AG2-095 GEN
Solar/Wind Harmer
2.314
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.422
3142946ENON
Solar/Wind Harmer
0.08
3146456SLIGO L269
Solar/Wind Harmer
0.238
971153AH1-033 GEN
Solar/Wind Harmer
2.749
3142416OLDCHRC
Solar/Wind Harmer
2.305
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3145273HOLLAND
Solar/Wind Harmer
0.173
316473AC1-191 GEN
Solar/Wind Harmer
0.778
3146376EDENTON
Solar/Wind Harmer
0.227
3141766HARMONY
Solar/Wind Harmer
3.024
316365GEN2_N
Solar/Wind Harmer
0.489
3150371LDYSMT1
Adder
28.172
3146206CASHIE
Solar/Wind Harmer
0.216
970009AG2-005 GEN
Solar/Wind Harmer
1.599
3146173TUNIS
Solar/Wind Harmer
0.213
971133AH1-012 GEN
50/50
5.491
3142366NRTHEST
50/50
0.836
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3142946ENON
Solar/Wind Harmer
0.024
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3146456SLIGO L269
Solar/Wind Harmer
4.208
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
18.37
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
1.008
3146376EDENTON
Solar/Wind Harmer
1.008
957411AF2-035 GEN
Solar/Wind Harmer
9.597
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.97
316181AB2-040 GEN
Solar/Wind Harmer
0.305
316274AC1-208 GEN
Solar/Wind Harmer
1.034
958211AF2-115 GEN
Solar/Wind Harmer
2.282
3147133PAMPLIN
Solar/Wind Harmer
0.19
3147133PAMPLIN
Solar/Wind Harmer
0.152
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
316222AC1-221 GEN
Solar/Wind Harmer
0.661
316447AC1-158 HLD
Solar/Wind Helper
11.481
971317AH1-138 GEN
Solar/Wind Harmer
1.762
3143336POWHATN
Solar/Wind Harmer
4.034
972219AH1-694 GEN
Adder
3.278
971547AH1-271 GEN
Solar/Wind Harmer
4.607
960081AF2-299 GEN
Solar/Wind Harmer
2.041
962571AG1-106 GEN
Solar/Wind Harmer
2.971
3145823KELFORD
Solar/Wind Harmer
0.208
3145783HORNRTN
Solar/Wind Harmer
0.206
3145796HORNRTN
Solar/Wind Harmer
0.678
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.038
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.434
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3144293JTRSVLE
Adder
0.605
970401AG2-262 GEN
Solar/Wind Harmer
1.071
316322AB2-045
Solar/Wind Harmer
0.001
972003AH1-546 GEN
Solar/Wind Harmer
7.247
3147623JAMES R
Solar/Wind Harmer
0.366
972277AH1-723 GEN
Adder
87.353
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.205
315773AC2-141 GEN
Solar/Wind Harmer
8.876
944581AF1-123 GEN
Solar/Wind Harmer
54.216
3144536CHRHLND
Solar/Wind Harmer
0.036
970659AG2-427 GEN
Solar/Wind Harmer
2.54
970293AG2-193 GEN
Solar/Wind Harmer
2.548
3150921YORKTN3
Adder
5.966
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.233
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316313AB2-026
Solar/Wind Harmer
0.143
316156AD2-030 GEN
Solar/Wind Harmer
0.167
315614AA2-178 GEN
Solar/Wind Harmer
1.271
971157AH1-035 GEN
Solar/Wind Harmer
2.623
3145893MURPHYS
Solar/Wind Harmer
0.361
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.996
316463AE2-346 GEN
Solar/Wind Harmer
0.183
316140AB2-099
Solar/Wind Harmer
0.076
3146263WOODLND
Solar/Wind Harmer
0.21
3145963POPLR C
Solar/Wind Harmer
0.208
316327AA2-057 GEN
Solar/Wind Harmer
0.292
961601AG1-000A GEN
Solar/Wind Harmer
13.299
970531AG2-338 GEN
50/50
8.626
3150781HOPHCF2
50/50
0.977
3150761HOPPOLC
50/50
0.62
971223AH1-071 GEN
Solar/Wind Harmer
2.834
316240AF1-291 C
Solar/Wind Harmer
0.002
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
3142956BIRDNECK
Solar/Wind Harmer
0
3142296MT RD221
Adder
0.763
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
972187AH1-678 GEN
Adder
6.65
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
3146516WINFALL
Solar/Wind Harmer
0.233
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970317AG2-208 GEN
Solar/Wind Harmer
8.892
316065AD1-022 GEN
Solar/Wind Harmer
9.976
3145893MURPHYS
Solar/Wind Harmer
1.442
3145893MURPHYS
Solar/Wind Harmer
0.388
316426AA2-053 GEN
Solar/Wind Harmer
0.702
966811AG1-552 GEN
Solar/Wind Harmer
2.246
971741AH1-377 GEN
Solar/Wind Harmer
19.869
939181AE1-148 GEN
Solar/Wind Harmer
9.29
3145453TOT5
Solar/Wind Harmer
0.264
961601AG1-000A GEN
Solar/Wind Harmer
3.325
964791AG1-342 GEN
Solar/Wind Harmer
3.505
970533AG2-339 GEN
50/50
21.564
971213AH1-066 GEN
50/50
0.857
3150681DARBY 2
Adder
17.235
316033AB2-134 GEN
Solar/Wind Harmer
0.014
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
8.395
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3145506HICKORY
Solar/Wind Harmer
0.957
3145506HICKORY
Solar/Wind Harmer
0.574
3145506HICKORY
Solar/Wind Harmer
0.144
316339AD2-160 GEN
Solar/Wind Harmer
0.387
3137176SLIGO L2192
Solar/Wind Harmer
0.946
3130086AYDLETT
Solar/Wind Harmer
0.95
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
3150801HOPHCF4
50/50
1.421
3151101ELIZAR3
50/50
23.68
315839AE2-212 C
Solar/Wind Harmer
0.002
944601AF1-125 GEN
Solar/Wind Harmer
53.381
315778AD1-151 GEN
Solar/Wind Harmer
19.233
3144216WINCHST
Adder
0.896
316258AE1-075 C
Solar/Wind Harmer
0.171
3143336POWHATN
Solar/Wind Harmer
3.429
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.208
3145796HORNRTN
Solar/Wind Harmer
0.822
3145796HORNRTN
Solar/Wind Harmer
0.206
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.861
970909AG2-566 GEN
Solar/Wind Harmer
2.105
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
964241AG1-285 GEN
Solar/Wind Harmer
12.793
3144293JTRSVLE
Adder
0.605
971193AH1-056 GEN
Solar/Wind Harmer
11.558
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.491
971683AH1-343 GEN
Solar/Wind Harmer
5.965
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
3141196NOKESVL
Solar/Wind Helper
1.131
944641AF1-129 GEN
50/50
122.767
3150791HOPHCF3
50/50
0.977
3143526WINTERP
Solar/Wind Harmer
1.342
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
1.973
3150391LDYSMT3
Adder
29.101
970099AG2-077 GEN
Solar/Wind Harmer
22.899
3145783HORNRTN
Solar/Wind Harmer
3.66
3145783HORNRTN
Solar/Wind Harmer
2.928
3145783HORNRTN
Solar/Wind Harmer
0.915
3145783HORNRTN
Solar/Wind Harmer
0.366
3145796HORNRTN
Solar/Wind Harmer
0.617
316077AC2-138 C
Solar/Wind Harmer
0.001
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
316034AC1-036 C
Solar/Wind Harmer
0.014
3145603CNETO
Solar/Wind Harmer
0.176
963191AG1-168 GEN
Solar/Wind Harmer
0.761
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
316263AC1-034 GEN
Solar/Wind Harmer
7.104
962561AG1-105 GEN
Solar/Wind Harmer
8.835
315821AE2-092 GEN
Solar/Wind Harmer
0.008
972263AH1-716 GEN
50/50
139.063
971281AH1-106 GEN
Solar/Wind Harmer
3.58
3143316POE
Solar/Wind Harmer
0.964
316369SG1_INVT
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
1.197
3146486SUNBURY
Solar/Wind Harmer
0.235
3146486SUNBURY
Solar/Wind Harmer
0.235
316321Z2-027
Solar/Wind Harmer
0.044
3145176PASQUOTANK
Solar/Wind Harmer
0.145
972189AH1-679 GEN
Adder
3.913
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
3143873LANEXA
Solar/Wind Harmer
0.137
3130156CHOWAN
Solar/Wind Harmer
0.227
3130156CHOWAN
Solar/Wind Harmer
0.227
315662AE1-191 GEN
Solar/Wind Harmer
0.007
3141873WAN 176
Solar/Wind Harmer
0.045
970581AG2-369 GEN
Solar/Wind Harmer
10.282
315816AE2-034 GEN
Solar/Wind Harmer
0.953
3138133OCRAN
Solar/Wind Harmer
0.066
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315733AD1-074 GEN2
Solar/Wind Harmer
1.252
972213AH1-691 GEN
Adder
4.735
970601AG2-382 GEN
Solar/Wind Harmer
8.061
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3146033SCOT NK
Solar/Wind Harmer
0.815
970181AG2-120 GEN
Solar/Wind Harmer
2.436
972205AH1-687 GEN
Adder
7.204
944491AF1-114 GEN
Solar/Wind Harmer
0.001
3147346CASHSCORNER
Solar/Wind Harmer
0.293
315737AD1-076 GEN
Solar/Wind Harmer
2.804
3150401LDYSMT4
Adder
29.156
962971AG1-146 GEN
Solar/Wind Harmer
3.461
961681AG1-008 GEN
Solar/Wind Harmer
15.996
962331AG1-082 GEN
Solar/Wind Harmer
2.268
316404AE1-155 C
Solar/Wind Harmer
0.047
313506AB2-031 GEN
Solar/Wind Harmer
0.649
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145933PARMELE
Solar/Wind Harmer
0.2
966801AG1-551 GEN
Solar/Wind Harmer
2.326
315785AD2-033 C
Solar/Wind Harmer
1.556
970257AG2-171 GEN
Solar/Wind Harmer
6.117
3146233WITAKRS
Solar/Wind Harmer
0.955
3146233WITAKRS
Solar/Wind Harmer
0.129
963181AG1-167 GEN
Solar/Wind Harmer
0.761
3146926FARMVIL
Solar/Wind Harmer
0.113
3141906WESTMOR
Solar/Wind Harmer
0.074
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
316233AE1-074 FULL
Solar/Wind Harmer
0.207
971283AH1-107 GEN
Solar/Wind Harmer
3.58
944011AF1-069 GEN
Solar/Wind Harmer
14.599
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
972265AH1-717 GEN
Adder
18.606
3151191GRAVEL3
Adder
17.221
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
37.658
971167AH1-042 GEN
Solar/Wind Harmer
20.686
3138283WHITEMARSH
Solar/Wind Harmer
0.054
970189AG2-124 GEN
Solar/Wind Harmer
6.729
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970085AG2-068 GEN
Solar/Wind Harmer
11.956
315732AD1-074 GEN1
Solar/Wind Harmer
1.252
315735AD1-075 GEN1
Solar/Wind Harmer
0.627
965291AG1-394 GEN
Solar/Wind Harmer
0.966
3150411LDYSMT5
Adder
29.247
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
8.075
3145893MURPHYS
Solar/Wind Harmer
0.582
3145893MURPHYS
Solar/Wind Harmer
0.215
3145513AHOSKIE
Solar/Wind Harmer
0.444
3145513AHOSKIE
Solar/Wind Harmer
0.212
315607AA1-063A GEN
Solar/Wind Harmer
0.431
315652AC1-086 GEN
Solar/Wind Harmer
22.967
3137643SOCKMAN
Solar/Wind Harmer
0.832
3141813NORNECK
Solar/Wind Harmer
0.205
316005AA1-067
Solar/Wind Harmer
0.21
971443AH1-215 GEN
Solar/Wind Harmer
3.212
3144303KENBRDG
Solar/Wind Harmer
0.153
946301AF1-294 GEN
Solar/Wind Harmer
3.752
315657AE1-056 GEN
Solar/Wind Harmer
6.547
316223AC1-118
Solar/Wind Harmer
0.132
316118AC1-105 GEN
Solar/Wind Harmer
0.462
972193AH1-681 GEN
Adder
3.349
270494AE1-108_GEN
Solar/Wind Harmer
1.672
316164AC1-076 GEN
Solar/Wind Helper
1.38
3138216PACIFIC
Solar/Wind Helper
0.038
315673AE1-157 GEN
Solar/Wind Harmer
15.364
972195AH1-682 GEN
Adder
3.824
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.126
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.258
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
3145933PARMELE
Solar/Wind Harmer
0.399
3145933PARMELE
Solar/Wind Harmer
0.2
970301AG2-198 GEN
Solar/Wind Harmer
8.419
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
8.155
971775AH1-396 GEN
Solar/Wind Harmer
0.306
3145493TOT1
Solar/Wind Harmer
0.441
3151731LOISA B
Adder
8.676
3145543BTLEBRO
Solar/Wind Harmer
0.187
3145543BTLEBRO
Solar/Wind Harmer
0.187
3146776BUCKING
Solar/Wind Harmer
0.064
970737AG2-469 GEN
Solar/Wind Harmer
7.435
970221AG2-151 GEN
Solar/Wind Harmer
8.416
971163AH1-040 GEN
Solar/Wind Harmer
17.772
3138133OCRAN
Solar/Wind Harmer
0.133
957481AF2-042 GEN
Solar/Wind Harmer
57.247
316190AA2-174 GEN
Solar/Wind Harmer
0
3146293MARTNCO
Solar/Wind Harmer
0.185
970685AG2-442 GEN
Solar/Wind Harmer
14.234
3146233WITAKRS
Solar/Wind Harmer
0.757
3145493TOT1
Solar/Wind Harmer
0.845
971563AH1-280 GEN
Solar/Wind Harmer
2.028
3146926FARMVIL
Solar/Wind Harmer
0.113
316049AB1-081 GEN
Solar/Wind Harmer
1.07
971377AH1-170 GEN
Solar/Wind Harmer
1.683
3151751LOISA D
Adder
8.676
970223AG2-152 GEN
Solar/Wind Harmer
7.908
971285AH1-108 GEN
50/50
1.99
941031AE2-094 GEN
Solar/Wind Harmer
44.68
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
971445AH1-216 GEN
Solar/Wind Harmer
16.89
970673AG2-436 GEN
Solar/Wind Harmer
50.858
970673AG2-436 GEN
Solar/Wind Harmer
33.905
957871AF2-081 GEN
Solar/Wind Harmer
11.862
316312AB1-027
Solar/Wind Harmer
0.425
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.191
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.222
970327AG2-215 GEN
Solar/Wind Harmer
7.029
3145796HORNRTN
Solar/Wind Harmer
0.658
3145796HORNRTN
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
8.503
3145746EVERETS
Solar/Wind Harmer
0.779
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
3145746EVERETS
Solar/Wind Harmer
0.196
957861AF2-080 GEN
Solar/Wind Harmer
8.31
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
970683AG2-441 GEN
Solar/Wind Harmer
12.709
970681AG2-440 GEN
Solar/Wind Harmer
10.167
3145573BETHELC
Solar/Wind Harmer
0.19
3145573BETHELC
Solar/Wind Harmer
0.19
970865AG2-541 GEN
Solar/Wind Harmer
5.394
971447AH1-217 GEN
Solar/Wind Harmer
4.654
316123AC1-075 GEN
Solar/Wind Harmer
0.195
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
316303AF2-085
50/50
4.723
970603AG2-384 GEN
50/50
5.178
3151201GRAVEL4
Adder
17.442
3151211GRAVEL5
Adder
17.221
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.823
315835AF2-110_GEN
Solar/Wind Harmer
1.621
315976AC1-164 GENA
Solar/Wind Harmer
24.444
316169AC1-164_GENC
Solar/Wind Harmer
21.117
315975AC1-164 GENB
Solar/Wind Harmer
0.723
313526AB2-022
Solar/Wind Harmer
0.128
315814AE2-033 C
Solar/Wind Harmer
18.587
3146396TANGLEW
Solar/Wind Harmer
0.646
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
316059AD1-063 C
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150381LDYSMT2
Adder
27.99
3146206CASHIE
Solar/Wind Harmer
0.216
3146043SEABORD
Solar/Wind Harmer
0.212
3145683EARLEYS
Solar/Wind Harmer
0.423
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
3156021HOLLOMANSOL
Solar/Wind Harmer
0.967
316478AD1-087 GEN
Solar/Wind Harmer
0.721
316486AD2-202 GEN
Solar/Wind Harmer
0.212
3147043LAWRENC
Solar/Wind Harmer
0.124
971781AH1-399 GEN
Solar/Wind Harmer
0.26
315724AD1-057 GEN
Solar/Wind Harmer
0.733
316131AB2-060 GEN
Solar/Wind Harmer
0.604
959311AF2-222 GEN
Solar/Wind Harmer
16.978
3146073TAR RVR
Solar/Wind Harmer
0.19
3146083TARBORO
Solar/Wind Harmer
0.19
3138543CONSLDL
Solar/Wind Harmer
0.125
3147133PAMPLIN
Solar/Wind Harmer
0.596
971623AH1-311 GEN
Solar/Wind Harmer
0.374
316283AC2-100 C
Solar/Wind Harmer
0.31
972255AH1-712 GEN
Adder
74.962
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
971489AH1-241 GEN
Solar/Wind Harmer
8.416
942751AE2-291 GEN
Solar/Wind Harmer
7.289
3151721LOISA A
Adder
8.631
961791AG1-021 GEN
Solar/Wind Harmer
1.825
970285AG2-188 GEN
Solar/Wind Harmer
14.341
971845AH1-439 GEN
Solar/Wind Harmer
8.154
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
970165AG2-112 GEN
Solar/Wind Harmer
1.154
970163AG2-111 GEN
Solar/Wind Harmer
1.101
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:171.66 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5528.27
MW Contribution:5.27
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
20.435
970119AG2-088 GEN
50/50
35.934
3150851SPRUNCC
50/50
1.238
970659AG2-427 GEN
Solar/Wind Harmer
11.815
316093AE2-104_GEN
Solar/Wind Harmer
4.042
3146516WINFALL
Solar/Wind Harmer
0.766
3146516WINFALL
Solar/Wind Harmer
0.236
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
970919AG2-571 GEN
Solar/Wind Harmer
8.12
3145893MURPHYS
Solar/Wind Harmer
0.876
3145893MURPHYS
Solar/Wind Harmer
0.974
962861AG1-135 GEN
Solar/Wind Harmer
6.917
3146263WOODLND
Solar/Wind Harmer
0.214
315693AD1-088 GEN
Solar/Wind Harmer
10.231
962491AG1-098 GEN
Solar/Wind Harmer
12.124
3152331SURRY 2
50/50
10.173
316192AB2-158 GEN
Solar/Wind Harmer
1.397
316294AC1-161 GEN
Solar/Wind Harmer
4.284
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.976
3142416OLDCHRC
Solar/Wind Harmer
0.631
3142416OLDCHRC
Solar/Wind Harmer
0.242
3146456SLIGO L269
Solar/Wind Harmer
0.242
3142433PROV 92
Solar/Wind Harmer
0.947
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
971777AH1-397 GEN
Solar/Wind Harmer
0.612
971133AH1-012 GEN
50/50
5.467
3142366NRTHEST
50/50
0.853
3150691DARBY 3
50/50
18.729
3150701DARBY 4
50/50
18.685
3142946ENON
Solar/Wind Harmer
0.024
316017AA1-139 ULT1
Solar/Wind Harmer
0.135
3146456SLIGO L269
Solar/Wind Harmer
4.28
3146386ELIZ CT
Solar/Wind Harmer
0.239
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
18.633
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.864
3146376EDENTON
Solar/Wind Harmer
1.025
3146376EDENTON
Solar/Wind Harmer
1.025
3146173TUNIS
Solar/Wind Harmer
0.217
3146173TUNIS
Solar/Wind Harmer
0.217
958261AF2-120 GEN
Solar/Wind Harmer
7.118
316181AB2-040 GEN
Solar/Wind Harmer
0.309
316274AC1-208 GEN
Solar/Wind Harmer
1.051
958211AF2-115 GEN
Solar/Wind Harmer
2.311
3147133PAMPLIN
Solar/Wind Harmer
0.192
3143526WINTERP
Solar/Wind Harmer
1.363
3150801HOPHCF4
50/50
1.448
315839AE2-212 C
Solar/Wind Harmer
0.002
944601AF1-125 GEN
Solar/Wind Harmer
54.301
315778AD1-151 GEN
Solar/Wind Harmer
19.588
3151101ELIZAR3
Adder
22.703
3144216WINCHST
Adder
0.913
316258AE1-075 C
Solar/Wind Harmer
0.173
3143336POWHATN
Solar/Wind Harmer
3.472
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.211
3150351NORNECKC2
Adder
2.12
3145796HORNRTN
Solar/Wind Harmer
0.835
3145796HORNRTN
Solar/Wind Harmer
0.209
316210AC1-098 GEN
Solar/Wind Harmer
1.891
970909AG2-566 GEN
Solar/Wind Harmer
2.131
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
964241AG1-285 GEN
Solar/Wind Harmer
12.969
3144293JTRSVLE
Adder
0.613
971193AH1-056 GEN
Solar/Wind Harmer
11.702
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.001
944641AF1-129 GEN
50/50
125.042
3150791HOPHCF3
50/50
0.996
3143526WINTERP
Solar/Wind Harmer
1.363
315697AD1-025 GEN
Solar/Wind Harmer
0.275
316316AC1-027 C
Solar/Wind Harmer
0.234
316185AD1-033 GEN
Solar/Wind Harmer
0.007
316075AC2-137 C
Solar/Wind Harmer
0.066
972185AH1-677 GEN
Adder
13.452
3144356SAPONY
Solar/Wind Harmer
2.004
3150391LDYSMT3
Adder
30.003
970099AG2-077 GEN
Solar/Wind Harmer
23.222
3145783HORNRTN
Solar/Wind Harmer
3.718
3145783HORNRTN
Solar/Wind Harmer
2.974
3145783HORNRTN
Solar/Wind Harmer
0.93
3145783HORNRTN
Solar/Wind Harmer
0.372
316077AC2-138 C
Solar/Wind Harmer
0.001
3145796HORNRTN
Solar/Wind Harmer
0.626
316468AD1-105 GEN
Solar/Wind Harmer
-0.066
316034AC1-036 C
Solar/Wind Harmer
0.014
3145603CNETO
Solar/Wind Harmer
0.179
963191AG1-168 GEN
Solar/Wind Harmer
0.77
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
316263AC1-034 GEN
Solar/Wind Harmer
7.215
962561AG1-105 GEN
Solar/Wind Harmer
8.959
971281AH1-106 GEN
Solar/Wind Harmer
3.638
3143316POE
Solar/Wind Harmer
0.98
316369SG1_INVT
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
1.218
972189AH1-679 GEN
Adder
4.009
3152261N ANNA2
50/50
20.433
3150861SPRUNCD
50/50
1.238
3143096IRON208
50/50
1.099
3143096IRON208
50/50
1.077
3147666LOUISA
Solar/Wind Harmer
0.585
965281AG1-393 GEN
Solar/Wind Harmer
2.631
970129AG2-093 GEN
Solar/Wind Harmer
14.818
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.513
3151171GRAVELC
Adder
3.413
970661AG2-428 GEN
Solar/Wind Harmer
5.15
316382AG1-145 C
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.235
3141843SHACKLE
Adder
1.184
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141873WAN 176
Solar/Wind Harmer
4.092
316405AF2-144 C
Solar/Wind Harmer
0.002
970917AG2-570 GEN
Solar/Wind Harmer
20.3
3150401LDYSMT4
Adder
30.059
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.851
962971AG1-146 GEN
Solar/Wind Harmer
3.533
961681AG1-008 GEN
Solar/Wind Harmer
16.257
962331AG1-082 GEN
Solar/Wind Harmer
2.305
316404AE1-155 C
Solar/Wind Harmer
0.048
313506AB2-031 GEN
Solar/Wind Harmer
0.659
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3145933PARMELE
Solar/Wind Harmer
0.203
966801AG1-551 GEN
Solar/Wind Harmer
2.363
315785AD2-033 C
Solar/Wind Harmer
1.576
970257AG2-171 GEN
Solar/Wind Harmer
6.198
3146233WITAKRS
Solar/Wind Harmer
0.97
3146233WITAKRS
Solar/Wind Harmer
0.131
963181AG1-167 GEN
Solar/Wind Harmer
0.77
3146926FARMVIL
Solar/Wind Harmer
0.114
3141906WESTMOR
Solar/Wind Harmer
0.075
316044AC1-158 PL1
Solar/Wind Helper
5.254
316450AC1-158 RIC
Solar/Wind Helper
1.401
316233AE1-074 FULL
Solar/Wind Harmer
0.21
971283AH1-107 GEN
Solar/Wind Harmer
3.638
944011AF1-069 GEN
Solar/Wind Harmer
14.811
316132AB2-190 GEN1
Solar/Wind Harmer
1.315
972265AH1-717 GEN
Adder
18.943
3151191GRAVEL3
Adder
17.533
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
38.202
971167AH1-042 GEN
Solar/Wind Harmer
21.1
3138283WHITEMARSH
Solar/Wind Harmer
0.055
970189AG2-124 GEN
Solar/Wind Harmer
6.866
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970085AG2-068 GEN
Solar/Wind Harmer
12.13
3150411LDYSMT5
Adder
30.153
972215AH1-692 GEN
Adder
4.882
315732AD1-074 GEN1
Solar/Wind Harmer
1.273
315735AD1-075 GEN1
Solar/Wind Harmer
0.637
965291AG1-394 GEN
Solar/Wind Harmer
0.982
962981AG1-147 GEN
Solar/Wind Harmer
8.243
3145893MURPHYS
Solar/Wind Harmer
0.591
3145893MURPHYS
Solar/Wind Harmer
0.219
3145513AHOSKIE
Solar/Wind Harmer
0.452
3145513AHOSKIE
Solar/Wind Harmer
0.216
315607AA1-063A GEN
Solar/Wind Harmer
0.438
315652AC1-086 GEN
Solar/Wind Harmer
23.331
3137643SOCKMAN
Solar/Wind Harmer
0.845
3141813NORNECK
Solar/Wind Harmer
0.209
316005AA1-067
Solar/Wind Harmer
0.213
971443AH1-215 GEN
Solar/Wind Harmer
3.255
3144303KENBRDG
Solar/Wind Harmer
0.155
946301AF1-294 GEN
Solar/Wind Harmer
3.8
315657AE1-056 GEN
Solar/Wind Harmer
6.628
316223AC1-118
Solar/Wind Harmer
0.135
316118AC1-105 GEN
Solar/Wind Harmer
0.469
972193AH1-681 GEN
Adder
3.425
270494AE1-108_GEN
Solar/Wind Harmer
1.686
316164AC1-076 GEN
Solar/Wind Helper
2.196
3138216PACIFIC
Solar/Wind Helper
0.039
970533AG2-339 GEN
50/50
21.877
971213AH1-066 GEN
50/50
0.873
3150681DARBY 2
Adder
17.588
316033AB2-134 GEN
Solar/Wind Harmer
0.014
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
8.541
970657AG2-426 GEN
Solar/Wind Harmer
1.79
3145506HICKORY
Solar/Wind Harmer
0.973
3145506HICKORY
Solar/Wind Harmer
0.584
3145506HICKORY
Solar/Wind Harmer
0.146
316339AD2-160 GEN
Solar/Wind Harmer
0.393
3137176SLIGO L2192
Solar/Wind Harmer
0.963
3130086AYDLETT
Solar/Wind Harmer
0.966
3146626S HERTFORD
Solar/Wind Harmer
0.235
3146626S HERTFORD
Solar/Wind Harmer
0.235
315673AE1-157 GEN
Solar/Wind Harmer
15.809
972195AH1-682 GEN
Adder
3.943
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.212
3142666NORTHAMPTON
Solar/Wind Harmer
0.128
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.21
3145593CAROLNA
Solar/Wind Harmer
0.262
3150341NORNECKC1
Adder
2.19
3150341NORNECKC1
Adder
2.172
3145933PARMELE
Solar/Wind Harmer
0.406
3145933PARMELE
Solar/Wind Harmer
0.203
970301AG2-198 GEN
Solar/Wind Harmer
8.524
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
8.264
971775AH1-396 GEN
Solar/Wind Harmer
0.31
3145493TOT1
Solar/Wind Harmer
0.448
3151731LOISA B
Adder
8.255
971211AH1-065 GEN
50/50
1.746
3151161SURRY 1
50/50
9.371
315773AC2-141 GEN
Solar/Wind Harmer
9.03
944581AF1-123 GEN
Solar/Wind Harmer
55.15
3144536CHRHLND
Solar/Wind Harmer
0.037
970659AG2-427 GEN
Solar/Wind Harmer
2.585
970293AG2-193 GEN
Solar/Wind Harmer
2.6
3150921YORKTN3
Adder
6.079
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.236
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.17
316313AB2-026
Solar/Wind Harmer
0.145
315614AA2-178 GEN
Solar/Wind Harmer
1.293
971157AH1-035 GEN
Solar/Wind Harmer
2.667
3145893MURPHYS
Solar/Wind Harmer
0.367
3145893MURPHYS
Solar/Wind Harmer
0.219
957521AF2-046 GEN
Solar/Wind Harmer
16.257
316463AE2-346 GEN
Solar/Wind Harmer
0.186
316140AB2-099
Solar/Wind Harmer
0.077
3146263WOODLND
Solar/Wind Harmer
0.214
3145963POPLR C
Solar/Wind Harmer
0.211
316327AA2-057 GEN
Solar/Wind Harmer
0.297
961601AG1-000A GEN
Solar/Wind Harmer
13.507
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.19
3146776BUCKING
Solar/Wind Harmer
0.065
970737AG2-469 GEN
Solar/Wind Harmer
7.61
970221AG2-151 GEN
Solar/Wind Harmer
8.483
3150331BIRCHWDA
Adder
19.249
316170AC1-121 GEN2
Solar/Wind Helper
0.463
3143096IRON208
50/50
1.099
3150771HOPHCF1
50/50
0.996
3143226MDLTHAN
Solar/Wind Harmer
0.269
3147666LOUISA
Solar/Wind Harmer
1.017
3142543TWELFTH
Solar/Wind Harmer
0.024
970129AG2-093 GEN
Solar/Wind Harmer
6.973
316458AB2-190 GEN2
Solar/Wind Harmer
1.315
971069AG2-661 GEN
Solar/Wind Harmer
4.353
3150981CHESPKA
Adder
3.052
971647AH1-324 GEN
Solar/Wind Harmer
10.43
961611AG1-000B GEN
Solar/Wind Harmer
12.808
316381AD1-082 GEN
Solar/Wind Harmer
0.254
3151171GRAVELC
Adder
2.595
970661AG2-428 GEN
Solar/Wind Harmer
24.214
316388AE2-253 GEN
Solar/Wind Harmer
0.76
3138126ROCKLANDING
Solar/Wind Harmer
0.111
316159AE1-175 C
Solar/Wind Harmer
0.209
316246AF1-032 C
Solar/Wind Harmer
0.109
3141843SHACKLE
Adder
1.184
3130156CHOWAN
Solar/Wind Harmer
0.23
970087AG2-069 GEN
Solar/Wind Harmer
18.195
3138133OCRAN
Solar/Wind Harmer
0.136
971163AH1-040 GEN
Solar/Wind Harmer
18.07
957481AF2-042 GEN
Solar/Wind Harmer
58.056
316190AA2-174 GEN
Solar/Wind Harmer
0
3146293MARTNCO
Solar/Wind Harmer
0.188
3146233WITAKRS
Solar/Wind Harmer
0.769
3145493TOT1
Solar/Wind Harmer
0.859
970685AG2-442 GEN
Solar/Wind Harmer
14.419
971563AH1-280 GEN
Solar/Wind Harmer
2.054
3146926FARMVIL
Solar/Wind Harmer
0.114
316049AB1-081 GEN
Solar/Wind Harmer
1.086
971377AH1-170 GEN
Solar/Wind Harmer
1.697
3151751LOISA D
Adder
8.255
970223AG2-152 GEN
Solar/Wind Harmer
8.023
316254AC1-120 GEN1
Solar/Wind Helper
1.388
971285AH1-108 GEN
50/50
2.026
941031AE2-094 GEN
Solar/Wind Harmer
45.33
3151081ELIZAR1
Adder
22.416
3151091ELIZAR2
Adder
22.027
3152611GOSPORTB
Adder
3.112
3152621GOSPORTC
Adder
2.641
3152601GOSPORTA
Adder
2.437
971445AH1-216 GEN
Solar/Wind Harmer
17.191
316312AB1-027
Solar/Wind Harmer
0.435
957871AF2-081 GEN
Solar/Wind Harmer
12.066
970673AG2-436 GEN
Solar/Wind Harmer
51.597
970673AG2-436 GEN
Solar/Wind Harmer
34.398
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.194
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.227
970327AG2-215 GEN
Solar/Wind Harmer
7.177
3145796HORNRTN
Solar/Wind Harmer
0.668
3145796HORNRTN
Solar/Wind Harmer
0.084
970831AG2-522 GEN
Solar/Wind Harmer
8.631
3145746EVERETS
Solar/Wind Harmer
0.791
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
957861AF2-080 GEN
Solar/Wind Harmer
8.442
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
3145573BETHELC
Solar/Wind Harmer
0.193
3145573BETHELC
Solar/Wind Harmer
0.193
970683AG2-441 GEN
Solar/Wind Harmer
12.874
970681AG2-440 GEN
Solar/Wind Harmer
10.299
970865AG2-541 GEN
Solar/Wind Harmer
5.471
971447AH1-217 GEN
Solar/Wind Harmer
4.69
316123AC1-075 GEN
Solar/Wind Harmer
0.197
316411AF1-147_GEN1
Solar/Wind Helper
0.801
316415AF1-147_GEN2
Solar/Wind Helper
0.801
940641AE2-051 GEN
Solar/Wind Harmer
20.264
939411AE1-173 GEN
Solar/Wind Harmer
107.071
315671AE2-027_GEN
Solar/Wind Harmer
15.779
944591AF1-124 GEN
Solar/Wind Harmer
55.346
944631AF1-128 GEN
Adder
116.602
316072AD1-144
Solar/Wind Harmer
0.088
971317AH1-138 GEN
Solar/Wind Harmer
1.796
3143336POWHATN
Solar/Wind Harmer
4.084
972219AH1-694 GEN
Adder
3.38
971547AH1-271 GEN
Solar/Wind Harmer
4.683
960081AF2-299 GEN
Solar/Wind Harmer
2.073
962571AG1-106 GEN
Solar/Wind Harmer
3.018
3145823KELFORD
Solar/Wind Harmer
0.211
3145783HORNRTN
Solar/Wind Harmer
0.209
3150351NORNECKC2
Adder
2.084
3145796HORNRTN
Solar/Wind Harmer
0.689
3145796HORNRTN
Solar/Wind Harmer
0.209
316212AC1-099_GEN
Solar/Wind Harmer
1.054
316129AC1-054 GEN
Solar/Wind Harmer
0.758
971065AG2-659 GEN
Solar/Wind Harmer
8.56
3145746EVERETS
Solar/Wind Harmer
0.199
3145746EVERETS
Solar/Wind Harmer
0.199
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3144293JTRSVLE
Adder
0.613
970401AG2-262 GEN
Solar/Wind Harmer
1.086
316322AB2-045
Solar/Wind Harmer
0.001
972003AH1-546 GEN
Solar/Wind Harmer
7.307
3147623JAMES R
Solar/Wind Harmer
0.369
972277AH1-723 GEN
Adder
89.316
315813AE1-149 C
Solar/Wind Harmer
13.098
970133AG2-095 GEN
Solar/Wind Harmer
2.358
3145336SMITFLD
Solar/Wind Harmer
0.098
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.737
3142946ENON
Solar/Wind Harmer
0.081
3142416OLDCHRC
Solar/Wind Harmer
2.354
3146456SLIGO L269
Solar/Wind Harmer
0.242
971153AH1-033 GEN
Solar/Wind Harmer
2.796
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
316473AC1-191 GEN
Solar/Wind Harmer
0.795
3145273HOLLAND
Solar/Wind Harmer
0.176
3141766HARMONY
Solar/Wind Harmer
3.085
3146376EDENTON
Solar/Wind Harmer
0.23
3150371LDYSMT1
Adder
29.045
316365GEN2_N
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
970009AG2-005 GEN
Solar/Wind Harmer
1.633
3146173TUNIS
Solar/Wind Harmer
0.217
3156021HOLLOMANSOL
Solar/Wind Harmer
0.983
3147043LAWRENC
Solar/Wind Harmer
0.126
316478AD1-087 GEN
Solar/Wind Harmer
0.731
316486AD2-202 GEN
Solar/Wind Harmer
0.215
971781AH1-399 GEN
Solar/Wind Harmer
0.266
315724AD1-057 GEN
Solar/Wind Harmer
0.745
316131AB2-060 GEN
Solar/Wind Harmer
0.613
959311AF2-222 GEN
Solar/Wind Harmer
17.202
3146073TAR RVR
Solar/Wind Harmer
0.193
3146083TARBORO
Solar/Wind Harmer
0.193
3138543CONSLDL
Solar/Wind Harmer
0.127
3147133PAMPLIN
Solar/Wind Harmer
0.603
971623AH1-311 GEN
Solar/Wind Harmer
0.38
316283AC2-100 C
Solar/Wind Harmer
0.314
972255AH1-712 GEN
Adder
76.646
3141766HARMONY
Solar/Wind Harmer
0.046
966881AG1-559 GEN
Solar/Wind Harmer
0.267
3145663CRESWEL
Solar/Wind Harmer
0.632
972197AH1-683 GEN
Adder
4.694
316023GEN1_S
Solar/Wind Harmer
0.497
3146206CASHIE
Solar/Wind Harmer
0.219
316336AC2-165 C
Solar/Wind Harmer
0.009
3146173TUNIS
Solar/Wind Harmer
0.217
3145683EARLEYS
Solar/Wind Harmer
0.215
971795AH1-408 GEN
Solar/Wind Harmer
14.105
3147043LAWRENC
Adder
1.896
315722AD1-056 GEN
Solar/Wind Harmer
1.256
3146083TARBORO
Solar/Wind Harmer
0.193
970937AG2-583 GEN
Solar/Wind Harmer
11.813
316359AB2-059 GEN
Solar/Wind Harmer
0.682
3142053HEARTS
Solar/Wind Harmer
0.334
972135AH1-637 GEN
Solar/Wind Harmer
1.466
316003AC1-222 GEN
Solar/Wind Harmer
0.005
970531AG2-338 GEN
50/50
8.751
3150781HOPHCF2
50/50
0.996
3150761HOPPOLC
50/50
0.631
971223AH1-071 GEN
Solar/Wind Harmer
2.875
316240AF1-291 C
Solar/Wind Harmer
0.002
3150671DARBY 1
Adder
17.568
3142296MT RD221
Adder
0.779
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.56
3150991CHESPKB
Adder
2.499
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
3146516WINFALL
Solar/Wind Harmer
0.236
966871AG1-558 GEN
Solar/Wind Harmer
0.272
970317AG2-208 GEN
Solar/Wind Harmer
9.139
316065AD1-022 GEN
Solar/Wind Harmer
10.141
3145893MURPHYS
Solar/Wind Harmer
1.466
3145893MURPHYS
Solar/Wind Harmer
0.394
316426AA2-053 GEN
Solar/Wind Harmer
0.713
966811AG1-552 GEN
Solar/Wind Harmer
2.282
971741AH1-377 GEN
Solar/Wind Harmer
20.122
939181AE1-148 GEN
Solar/Wind Harmer
9.423
3145453TOT5
Solar/Wind Harmer
0.269
961601AG1-000A GEN
Solar/Wind Harmer
3.377
964791AG1-342 GEN
Solar/Wind Harmer
3.555
3146776BUCKING
Solar/Wind Harmer
0.723
3146776BUCKING
Solar/Wind Harmer
0.059
971489AH1-241 GEN
Solar/Wind Harmer
8.483
942751AE2-291 GEN
Solar/Wind Harmer
7.393
3151721LOISA A
Adder
8.212
316011AB1-132 GEN
Solar/Wind Harmer
3.856
3141726DUNNSVL
Solar/Wind Harmer
0.847
3145963POPLR C
Solar/Wind Harmer
0.211
316174AB2-169 GEN
Solar/Wind Harmer
0.006
316337AD2-073 GEN
Solar/Wind Harmer
0.173
316494AC1-189 GEN
Solar/Wind Harmer
0.661
961671AG1-007 GEN
Solar/Wind Harmer
0.03
963171AG1-166 GEN
Solar/Wind Harmer
1.027
3145543BTLEBRO
Solar/Wind Harmer
0.19
3145543BTLEBRO
Solar/Wind Harmer
0.152
3146776BUCKING
Solar/Wind Harmer
0.072
316045AC1-158 PL2
Solar/Wind Helper
16.818
316006AB2-029 C
Solar/Wind Helper
0.152
316303AF2-085
50/50
4.791
970603AG2-384 GEN
50/50
5.274
3151201GRAVEL4
Adder
17.758
3151211GRAVEL5
Adder
17.533
316349AD2-085 GEN
Solar/Wind Harmer
0.166
316311AC2-079 GEN
Solar/Wind Harmer
6.941
315976AC1-164 GENA
Solar/Wind Harmer
24.95
316169AC1-164_GENC
Solar/Wind Harmer
21.555
315975AC1-164 GENB
Solar/Wind Harmer
0.738
315835AF2-110_GEN
Solar/Wind Harmer
1.649
313526AB2-022
Solar/Wind Harmer
0.13
315814AE2-033 C
Solar/Wind Harmer
18.884
3146396TANGLEW
Solar/Wind Harmer
0.658
3142433PROV 92
Adder
0.46
3142433PROV 92
Adder
0.46
316059AD1-063 C
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.135
3141783LANCAST
Solar/Wind Harmer
0.09
3150381LDYSMT2
Adder
28.858
3146206CASHIE
Solar/Wind Harmer
0.219
3146043SEABORD
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.43
3145683EARLEYS
Solar/Wind Harmer
0.215
3145683EARLEYS
Solar/Wind Harmer
0.215
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
961791AG1-021 GEN
Solar/Wind Harmer
1.849
970285AG2-188 GEN
Solar/Wind Harmer
14.487
971845AH1-439 GEN
Solar/Wind Harmer
8.236
3147173SINAI
Solar/Wind Harmer
0.178
3147243WELCO
Solar/Wind Harmer
0.111
970165AG2-112 GEN
Solar/Wind Harmer
1.171
970163AG2-111 GEN
Solar/Wind Harmer
1.117
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
3146486SUNBURY
Solar/Wind Harmer
0.239
3146486SUNBURY
Solar/Wind Harmer
0.239
316321Z2-027
Solar/Wind Harmer
0.044
3145176PASQUOTANK
Solar/Wind Harmer
0.148
3143873LANEXA
Solar/Wind Harmer
0.14
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315662AE1-191 GEN
Solar/Wind Harmer
0.008
3130156CHOWAN
Solar/Wind Harmer
0.23
3130156CHOWAN
Solar/Wind Harmer
0.23
3141873WAN 176
Solar/Wind Harmer
0.046
970581AG2-369 GEN
Solar/Wind Harmer
10.432
3138133OCRAN
Solar/Wind Harmer
0.068
315816AE2-034 GEN
Solar/Wind Harmer
0.969
972213AH1-691 GEN
Adder
4.882
3130546PLYMOUTH
Solar/Wind Harmer
0.222
315733AD1-074 GEN2
Solar/Wind Harmer
1.273
970601AG2-382 GEN
Solar/Wind Harmer
8.195
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3146033SCOT NK
Solar/Wind Harmer
0.828
970181AG2-120 GEN
Solar/Wind Harmer
2.475
972205AH1-687 GEN
Adder
7.261
944491AF1-114 GEN
Solar/Wind Harmer
0.001
3147346CASHSCORNER
Solar/Wind Harmer
0.279
960061AF2-297 GEN
Solar/Wind Harmer
7.598
971683AH1-343 GEN
Solar/Wind Harmer
6.05
3151761LOISA E
Adder
16.829
3141316ARNOLDS
Adder
0.299
972183AH1-676 GEN
Adder
129.168
3141196NOKESVL
Solar/Wind Helper
1.151
315821AE2-092 GEN
Solar/Wind Harmer
0.008
3147133PAMPLIN
Solar/Wind Harmer
0.154
3146843MT LREL
Solar/Wind Harmer
0.185
3146843MT LREL
Solar/Wind Harmer
0.185
316222AC1-221 GEN
Solar/Wind Harmer
0.67
316447AC1-158 HLD
Solar/Wind Helper
11.564
315651AD1-115 GEN
Solar/Wind Helper
1.026
CPLELTFEXP_CPLE->PJM
CLTF
12.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.813
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.392
WECLTFEXP_WEC->PJM
CLTF
0.673
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.657
MECLTFEXP_MEC->PJM
CLTF
3.808
SIGELTFEXP_SIGE->PJM
CLTF
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
8.524
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.899
TVALTFEXP_TVA->PJM
CLTF
4.316

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T581_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:150.52 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5930.65
MW Contribution:5.25
Bus #Bus NameTypeMW Contribution
3143096IRON208
50/50
1.093
3150771HOPHCF1
50/50
0.992
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3152261N ANNA2
50/50
20.538
3150861SPRUNCD
50/50
1.233
3143096IRON208
50/50
1.093
3150801HOPHCF4
50/50
1.442
3151101ELIZAR3
50/50
24.061
315839AE2-212 C
Solar/Wind Harmer
0.835
971285AH1-108 GEN
50/50
2.017
941031AE2-094 GEN
Solar/Wind Harmer
51.844
3151081ELIZAR1
Adder
22.389
3151091ELIZAR2
Adder
22
3152611GOSPORTB
Adder
3.108
3152621GOSPORTC
Adder
2.638
3152601GOSPORTA
Adder
2.434
971445AH1-216 GEN
Solar/Wind Harmer
16.942
957871AF2-081 GEN
Solar/Wind Harmer
13.602
970673AG2-436 GEN
Solar/Wind Harmer
57.084
970673AG2-436 GEN
Solar/Wind Harmer
28.903
315833AF1-017_GEN
Solar/Wind Harmer
5.15
316312AB1-027
Solar/Wind Harmer
0.914
316315AB2-025 C
Solar/Wind Harmer
0.725
957831AF2-077 GEN
Solar/Wind Harmer
0.794
316314AB2-024 C
Solar/Wind Harmer
2.214
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.075
3145796HORNRTN
Solar/Wind Harmer
-0.009
316411AF1-147_GEN1
Solar/Wind Helper
0.802
970533AG2-339 GEN
50/50
21.875
971213AH1-066 GEN
50/50
0.87
316033AB2-134 GEN
Solar/Wind Harmer
8.837
316236AE1-162_GEN
Solar/Wind Harmer
0.825
3150681DARBY 2
Adder
17.476
970657AG2-426 GEN
Solar/Wind Harmer
8.542
970657AG2-426 GEN
Solar/Wind Harmer
1.786
3145506HICKORY
Solar/Wind Harmer
-0.109
3145506HICKORY
Solar/Wind Harmer
-0.065
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.836
970531AG2-338 GEN
50/50
8.75
3150781HOPHCF2
50/50
0.992
3150761HOPPOLC
50/50
0.629
971223AH1-071 GEN
Solar/Wind Harmer
3.778
316240AF1-291 C
Solar/Wind Harmer
0.834
316036AC1-147 C
Solar/Wind Harmer
0.74
3150991CHESPKB
Adder
2.557
3150991CHESPKB
Adder
2.496
3142956BIRDNECK
Solar/Wind Harmer
1.47
3150671DARBY 1
Adder
17.456
3142296MT RD221
Adder
0.773
316018AA1-139 ULT2
Solar/Wind Harmer
2.33
972187AH1-678 GEN
Adder
6.746
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.787
966871AG1-558 GEN
Solar/Wind Harmer
0.269
316065AD1-022 GEN
Solar/Wind Harmer
12.361
3145893MURPHYS
Solar/Wind Harmer
0.686
3145893MURPHYS
Solar/Wind Harmer
-0.044
970317AG2-208 GEN
Solar/Wind Harmer
10.537
316426AA2-053 GEN
Solar/Wind Harmer
2.396
966811AG1-552 GEN
Solar/Wind Harmer
2.657
3151721LOISA A
Adder
8.279
971741AH1-377 GEN
Solar/Wind Harmer
12.626
316303AF2-085
50/50
4.782
970603AG2-384 GEN
50/50
5.251
3151201GRAVEL4
Adder
17.714
3151211GRAVEL5
Adder
17.489
316349AD2-085 GEN
Solar/Wind Harmer
2.412
316311AC2-079 GEN
Solar/Wind Harmer
13.676
315835AF2-110_GEN
Solar/Wind Harmer
3.371
315976AC1-164 GENA
Solar/Wind Harmer
28.429
316169AC1-164_GENC
Solar/Wind Harmer
24.56
315975AC1-164 GENB
Solar/Wind Harmer
0.841
313526AB2-022
Solar/Wind Harmer
0.725
315814AE2-033 C
Solar/Wind Harmer
24.939
3146396TANGLEW
Solar/Wind Harmer
0.493
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
316059AD1-063 C
Solar/Wind Harmer
0.583
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3146206CASHIE
Solar/Wind Harmer
-0.025
316318V4-068
Solar/Wind Harmer
0.613
961941AG1-037 GEN
Solar/Wind Harmer
0.182
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.048
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3150381LDYSMT2
Adder
25.67
315813AE1-149 C
Solar/Wind Harmer
17.198
970133AG2-095 GEN
Solar/Wind Harmer
3.091
3145336SMITFLD
Solar/Wind Harmer
-0.011
971211AH1-065 GEN
50/50
1.739
3151161SURRY 1
50/50
9.348
315773AC2-141 GEN
Solar/Wind Harmer
11.614
944581AF1-123 GEN
Solar/Wind Harmer
125.059
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.578
970293AG2-193 GEN
Solar/Wind Harmer
3.403
3150921YORKTN3
Adder
6.062
316320Y1-086
Solar/Wind Harmer
1.576
316435W1029_GEN3
Solar/Wind Harmer
4.824
3146516WINFALL
Solar/Wind Harmer
-0.026
316203AE2-005 GEN
Solar/Wind Harmer
10.898
316313AB2-026
Solar/Wind Harmer
0.695
316156AD2-030 GEN
Solar/Wind Harmer
0.685
315614AA2-178 GEN
Solar/Wind Harmer
2.735
971157AH1-035 GEN
Solar/Wind Harmer
3.118
3145893MURPHYS
Solar/Wind Harmer
0.172
3145893MURPHYS
Solar/Wind Harmer
-0.025
957521AF2-046 GEN
Solar/Wind Harmer
19.314
316484AD2-074 GEN
Solar/Wind Harmer
6.115
316463AE2-346 GEN
Solar/Wind Harmer
0.393
316140AB2-099
Solar/Wind Harmer
0.163
3146263WOODLND
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.024
316170AC1-121 GEN2
Solar/Wind Helper
0.46
316233AE1-074 FULL
Solar/Wind Harmer
0.79
971283AH1-107 GEN
Solar/Wind Harmer
4.774
944011AF1-069 GEN
Solar/Wind Harmer
16.245
316132AB2-190 GEN1
Solar/Wind Harmer
2.776
972265AH1-717 GEN
Adder
18.896
3151191GRAVEL3
Adder
17.489
3146406KITTY HAWK
Solar/Wind Harmer
0.023
316305AF2-043 C
Solar/Wind Harmer
0.817
971967AH1-528 GEN
Solar/Wind Harmer
50.429
971167AH1-042 GEN
Solar/Wind Harmer
25.534
3138283WHITEMARSH
Solar/Wind Harmer
0.041
315666AE1-190 GEN
Solar/Wind Harmer
0.777
957601AF2-054 GEN
Solar/Wind Harmer
0.768
970085AG2-068 GEN
Solar/Wind Harmer
15.97
315732AD1-074 GEN1
Solar/Wind Harmer
5.029
315735AD1-075 GEN1
Solar/Wind Harmer
2.515
965291AG1-394 GEN
Solar/Wind Harmer
2.201
3145893MURPHYS
Solar/Wind Harmer
-0.066
3145893MURPHYS
Solar/Wind Harmer
-0.025
962981AG1-147 GEN
Solar/Wind Harmer
10.738
3145513AHOSKIE
Solar/Wind Harmer
0.211
3145513AHOSKIE
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.433
315652AC1-086 GEN
Solar/Wind Harmer
26.795
3137643SOCKMAN
Solar/Wind Harmer
-0.094
3141813NORNECK
Solar/Wind Harmer
-0.023
316415AF1-147_GEN2
Solar/Wind Helper
0.802
3143526WINTERP
Solar/Wind Harmer
-0.152
940641AE2-051 GEN
Solar/Wind Harmer
26.675
939411AE1-173 GEN
Solar/Wind Harmer
140.912
315671AE2-027_GEN
Solar/Wind Harmer
20.692
944591AF1-124 GEN
Solar/Wind Harmer
125.51
944631AF1-128 GEN
Adder
116.045
316072AD1-144
Solar/Wind Harmer
0.549
971317AH1-138 GEN
Solar/Wind Harmer
3.367
3143336POWHATN
Solar/Wind Harmer
3.06
971547AH1-271 GEN
Solar/Wind Harmer
6.159
960081AF2-299 GEN
Solar/Wind Harmer
2.727
962571AG1-106 GEN
Solar/Wind Harmer
3.424
3145823KELFORD
Solar/Wind Harmer
-0.024
964211AG1-282 GEN
Solar/Wind Harmer
0.706
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.077
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.053
316212AC1-099_GEN
Solar/Wind Harmer
1.995
972219AH1-694 GEN
Adder
3.006
3144293JTRSVLE
Adder
0.613
972277AH1-723 GEN
Adder
89.642
972263AH1-716 GEN
50/50
141.451
971281AH1-106 GEN
Solar/Wind Harmer
4.774
3143316POE
Solar/Wind Harmer
-0.109
316369SG1_INVT
Solar/Wind Harmer
4.896
319010AE1-072 C
Solar/Wind Harmer
5.488
3146486SUNBURY
Solar/Wind Harmer
-0.027
3146486SUNBURY
Solar/Wind Harmer
-0.027
316321Z2-027
Solar/Wind Harmer
0.722
3145176PASQUOTANK
Solar/Wind Harmer
-0.017
315611Z1-036_GEN2
Solar/Wind Harmer
6.468
3143873LANEXA
Solar/Wind Harmer
-0.015
972189AH1-679 GEN
Adder
3.879
3130156CHOWAN
Solar/Wind Harmer
-0.026
3130156CHOWAN
Solar/Wind Harmer
-0.026
315662AE1-191 GEN
Solar/Wind Harmer
3.107
3141873WAN 176
Solar/Wind Harmer
-0.005
970581AG2-369 GEN
Solar/Wind Harmer
13.734
315816AE2-034 GEN
Solar/Wind Harmer
2.051
3138133OCRAN
Solar/Wind Harmer
-0.008
3130546PLYMOUTH
Solar/Wind Harmer
-0.025
315733AD1-074 GEN2
Solar/Wind Harmer
5.029
970601AG2-382 GEN
Solar/Wind Harmer
10.779
946281AF1-292 GEN
Solar/Wind Harmer
0.543
316087AB2-174 GEN
Solar/Wind Harmer
3.429
3146033SCOT NK
Solar/Wind Harmer
-0.093
972213AH1-691 GEN
Adder
4.342
972205AH1-687 GEN
Adder
7.266
3143096IRON208
50/50
1.071
3147666LOUISA
Solar/Wind Harmer
-0.066
965281AG1-393 GEN
Solar/Wind Harmer
3.451
970129AG2-093 GEN
Solar/Wind Harmer
15.452
3144873MCLAUGH
Solar/Wind Harmer
-0.001
961611AG1-000B GEN
Solar/Wind Harmer
5.762
3151171GRAVELC
Adder
3.404
970661AG2-428 GEN
Solar/Wind Harmer
5.139
316382AG1-145 C
Solar/Wind Harmer
0.815
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.176
316405AF2-144 C
Solar/Wind Harmer
0.66
316280AD1-041 GEN
Solar/Wind Harmer
1.942
3141873WAN 176
Solar/Wind Harmer
3.046
970917AG2-570 GEN
Solar/Wind Harmer
64.143
3156081AA2-088 GEN
Solar/Wind Harmer
8.083
315737AD1-076 GEN
Solar/Wind Harmer
4.727
962971AG1-146 GEN
Solar/Wind Harmer
4.602
961681AG1-008 GEN
Solar/Wind Harmer
19.314
962331AG1-082 GEN
Solar/Wind Harmer
3.031
313506AB2-031 GEN
Solar/Wind Harmer
1.925
316404AE1-155 C
Solar/Wind Harmer
4.606
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3150401LDYSMT4
Adder
26.739
316044AC1-158 PL1
Solar/Wind Helper
5.238
316450AC1-158 RIC
Solar/Wind Helper
1.397
316083AB2-161 GEN
Solar/Wind Harmer
4.441
3151221GRAVEL6
Adder
17.693
3142946ENON
Solar/Wind Harmer
-0.009
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.31
3142416OLDCHRC
Solar/Wind Harmer
2.734
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
3145273HOLLAND
Solar/Wind Harmer
-0.02
316473AC1-191 GEN
Solar/Wind Harmer
2.815
3146376EDENTON
Solar/Wind Harmer
-0.026
3141766HARMONY
Solar/Wind Harmer
2.298
316365GEN2_N
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.275
970009AG2-005 GEN
Solar/Wind Harmer
3.036
966881AG1-559 GEN
Solar/Wind Harmer
0.724
316478AD1-087 GEN
Solar/Wind Harmer
2.037
316486AD2-202 GEN
Solar/Wind Harmer
0.597
3147043LAWRENC
Solar/Wind Harmer
-0.014
3152331SURRY 2
50/50
10.164
316192AB2-158 GEN
Solar/Wind Harmer
3.325
316294AC1-161 GEN
Solar/Wind Harmer
8.98
316375AC2-012 GEN
Solar/Wind Harmer
9.491
3145336SMITFLD
Solar/Wind Harmer
-0.109
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142416OLDCHRC
Solar/Wind Harmer
-0.07
3142416OLDCHRC
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.105
3142433PROV 92
Adder
0.457
3142433PROV 92
Adder
0.457
971777AH1-397 GEN
Solar/Wind Harmer
3.039
3141766HARMONY
Solar/Wind Harmer
-0.005
3145663CRESWEL
Solar/Wind Harmer
-0.071
316023GEN1_S
Solar/Wind Harmer
1.677
3146206CASHIE
Solar/Wind Harmer
-0.025
316336AC2-165 C
Solar/Wind Harmer
4.278
3146173TUNIS
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.2
3145683EARLEYS
Solar/Wind Harmer
-0.024
966881AG1-559 GEN
Solar/Wind Harmer
0.248
971795AH1-408 GEN
Solar/Wind Harmer
17.814
3147043LAWRENC
Adder
1.895
972197AH1-683 GEN
Adder
4.175
3147666LOUISA
Solar/Wind Harmer
-0.114
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
6.259
316458AB2-190 GEN2
Solar/Wind Harmer
2.776
3150981CHESPKA
Adder
3.048
971069AG2-661 GEN
Solar/Wind Harmer
4.338
971647AH1-324 GEN
Solar/Wind Harmer
13.692
961611AG1-000B GEN
Solar/Wind Harmer
13.505
316381AD1-082 GEN
Solar/Wind Harmer
2.509
3151171GRAVELC
Adder
2.589
970661AG2-428 GEN
Solar/Wind Harmer
28.997
316388AE2-253 GEN
Solar/Wind Harmer
1.836
3138126ROCKLANDING
Solar/Wind Harmer
0.083
316246AF1-032 C
Solar/Wind Harmer
0.548
316159AE1-175 C
Solar/Wind Harmer
0.726
3130156CHOWAN
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.176
970087AG2-069 GEN
Solar/Wind Harmer
23.954
971163AH1-040 GEN
Solar/Wind Harmer
23.766
3138133OCRAN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
76.436
316190AA2-174 GEN
Solar/Wind Harmer
0.291
3151751LOISA D
Adder
8.322
316254AC1-120 GEN1
Solar/Wind Helper
1.381
3137176SLIGO L2192
Solar/Wind Harmer
-0.107
3130086AYDLETT
Solar/Wind Harmer
-0.108
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.024
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
-0.024
3145593CAROLNA
Solar/Wind Harmer
0.196
315673AE1-157 GEN
Solar/Wind Harmer
17.6
3150341NORNECKC1
Adder
2.157
3150341NORNECKC1
Adder
2.139
972195AH1-682 GEN
Adder
3.507
3151731LOISA B
Adder
8.322
971133AH1-012 GEN
50/50
5.498
3142366NRTHEST
50/50
0.848
3150691DARBY 3
Adder
17.538
3150701DARBY 4
Adder
17.497
3142946ENON
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
2.201
3146456SLIGO L269
Solar/Wind Harmer
3.207
3146386ELIZ CT
Solar/Wind Harmer
-0.027
316431W1029_GEN1
Solar/Wind Harmer
4.824
316433W1029_GEN2
Solar/Wind Harmer
4.824
970933AG2-581 GEN
Solar/Wind Harmer
24.532
315742AE1-103 GEN
Solar/Wind Harmer
2.721
3146376EDENTON
Solar/Wind Harmer
0.768
3146376EDENTON
Solar/Wind Harmer
0.768
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
316487AF1-042 GEN
Solar/Wind Harmer
3.2
957411AF2-035 GEN
Solar/Wind Harmer
10.838
316181AB2-040 GEN
Solar/Wind Harmer
3.34
958261AF2-120 GEN
Solar/Wind Harmer
9.253
316447AC1-158 HLD
Solar/Wind Helper
11.529
315651AD1-115 GEN
Solar/Wind Helper
1.021
3150411LDYSMT5
Adder
26.823
972215AH1-692 GEN
Adder
4.342
972193AH1-681 GEN
Adder
3.437
316164AC1-076 GEN
Solar/Wind Helper
2.187
3138216PACIFIC
Solar/Wind Helper
0.039
3152251N ANNA1
50/50
20.54
970119AG2-088 GEN
50/50
35.865
3150851SPRUNCC
50/50
1.233
970659AG2-427 GEN
Solar/Wind Harmer
14.549
316093AE2-104_GEN
Solar/Wind Harmer
7.84
3146516WINFALL
Solar/Wind Harmer
-0.086
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.468
970919AG2-571 GEN
Solar/Wind Harmer
8.119
3145893MURPHYS
Solar/Wind Harmer
-0.098
3145893MURPHYS
Solar/Wind Harmer
0.73
3146263WOODLND
Solar/Wind Harmer
-0.024
962861AG1-135 GEN
Solar/Wind Harmer
8.995
315693AD1-088 GEN
Solar/Wind Harmer
11.973
962491AG1-098 GEN
Solar/Wind Harmer
15.963
316011AB1-132 GEN
Solar/Wind Harmer
4.983
3145963POPLR C
Solar/Wind Harmer
-0.024
316174AB2-169 GEN
Solar/Wind Harmer
3.632
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316045AC1-158 PL2
Solar/Wind Helper
16.768
316006AB2-029 C
Solar/Wind Helper
0.152
3150371LDYSMT1
Adder
25.837
972255AH1-712 GEN
Adder
76.926
944601AF1-125 GEN
Solar/Wind Harmer
123.108
315778AD1-151 GEN
Solar/Wind Harmer
23.752
3144216WINCHST
Adder
0.911
316258AE1-075 C
Solar/Wind Harmer
0.626
3143336POWHATN
Solar/Wind Harmer
2.601
966621AG1-532 GEN
Solar/Wind Harmer
0.492
316317KELFORD C
Solar/Wind Harmer
1.117
3145823KELFORD
Solar/Wind Harmer
-0.024
3145796HORNRTN
Solar/Wind Harmer
-0.093
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.088
316210AC1-098 GEN
Solar/Wind Harmer
3.591
3144293JTRSVLE
Adder
0.613
3151761LOISA E
Adder
16.965
972183AH1-676 GEN
Adder
130.241
3141316ARNOLDS
Adder
0.278
3141196NOKESVL
Solar/Wind Helper
1.151
944641AF1-129 GEN
50/50
124.495
3150791HOPHCF3
50/50
0.992
3143526WINTERP
Solar/Wind Harmer
-0.152
315697AD1-025 GEN
Solar/Wind Harmer
5.542
316316AC1-027 C
Solar/Wind Harmer
0.841
316185AD1-033 GEN
Solar/Wind Harmer
2.888
316075AC2-137 C
Solar/Wind Harmer
0.73
972185AH1-677 GEN
Adder
13.451
3144356SAPONY
Solar/Wind Harmer
0.938
316441AF1-014 GEN
Solar/Wind Harmer
1.742
970099AG2-077 GEN
Solar/Wind Harmer
30.574
3145783HORNRTN
Solar/Wind Harmer
2.786
3145783HORNRTN
Solar/Wind Harmer
2.229
3145783HORNRTN
Solar/Wind Harmer
0.697
3145783HORNRTN
Solar/Wind Harmer
0.279
3145796HORNRTN
Solar/Wind Harmer
-0.07
316077AC2-138 C
Solar/Wind Harmer
0.488
3150391LDYSMT3
Adder
26.689
3144293JTRSVLE
Adder
0.613
3144293JTRSVLE
Adder
0.516
CPLELTFEXP_CPLE->PJM
CLTF
12.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.908
NYPJM->LTFIMP_NY
CLTF
3.309
LGEELTFEXP_LGEE->PJM
CLTF
1.397
WECLTFEXP_WEC->PJM
CLTF
0.676
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.478
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.684
MECLTFEXP_MEC->PJM
CLTF
3.82
SIGELTFEXP_SIGE->PJM
CLTF
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
8.538
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.91
TVALTFEXP_TVA->PJM
CLTF
4.323

Details for 8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.0 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:5831.04
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
970531AG2-338 GEN
50/50
8.626
3150781HOPHCF2
50/50
0.977
3150761HOPPOLC
50/50
0.62
971223AH1-071 GEN
Solar/Wind Harmer
3.731
316240AF1-291 C
Solar/Wind Harmer
0.822
3150671DARBY 1
Adder
17.215
316036AC1-147 C
Solar/Wind Harmer
0.728
3150991CHESPKB
Adder
2.516
3150991CHESPKB
Adder
2.456
3142956BIRDNECK
Solar/Wind Harmer
1.447
3142296MT RD221
Adder
0.763
316018AA1-139 ULT2
Solar/Wind Harmer
2.294
972187AH1-678 GEN
Adder
6.65
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.778
966871AG1-558 GEN
Solar/Wind Harmer
0.266
970317AG2-208 GEN
Solar/Wind Harmer
11.057
316065AD1-022 GEN
Solar/Wind Harmer
12.172
3145893MURPHYS
Solar/Wind Harmer
0.676
3145893MURPHYS
Solar/Wind Harmer
-0.043
316426AA2-053 GEN
Solar/Wind Harmer
2.36
966811AG1-552 GEN
Solar/Wind Harmer
2.618
3151721LOISA A
Adder
8.631
971741AH1-377 GEN
Solar/Wind Harmer
12.466
316303AF2-085
50/50
4.723
970603AG2-384 GEN
50/50
5.178
3151201GRAVEL4
Adder
17.442
3151211GRAVEL5
Adder
17.221
316349AD2-085 GEN
Solar/Wind Harmer
2.375
316311AC2-079 GEN
Solar/Wind Harmer
13.467
315835AF2-110_GEN
Solar/Wind Harmer
3.318
315976AC1-164 GENA
Solar/Wind Harmer
27.987
316169AC1-164_GENC
Solar/Wind Harmer
24.178
315975AC1-164 GENB
Solar/Wind Harmer
0.828
313526AB2-022
Solar/Wind Harmer
0.714
315814AE2-033 C
Solar/Wind Harmer
24.583
3146396TANGLEW
Solar/Wind Harmer
0.485
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
316059AD1-063 C
Solar/Wind Harmer
0.576
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150381LDYSMT2
Adder
27.99
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.205
315773AC2-141 GEN
Solar/Wind Harmer
11.425
944581AF1-123 GEN
Solar/Wind Harmer
123.071
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.54
970293AG2-193 GEN
Solar/Wind Harmer
3.354
3150921YORKTN3
Adder
5.966
316320Y1-086
Solar/Wind Harmer
1.551
316435W1029_GEN3
Solar/Wind Harmer
4.748
971285AH1-108 GEN
50/50
1.99
941031AE2-094 GEN
Solar/Wind Harmer
51.106
3151081ELIZAR1
Adder
22.034
3151091ELIZAR2
Adder
21.652
3152611GOSPORTB
Adder
3.059
3152621GOSPORTC
Adder
2.596
3152601GOSPORTA
Adder
2.395
971445AH1-216 GEN
Solar/Wind Harmer
16.679
970673AG2-436 GEN
Solar/Wind Harmer
56.272
970673AG2-436 GEN
Solar/Wind Harmer
28.492
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.285
939411AE1-173 GEN
Solar/Wind Harmer
138.811
315671AE2-027_GEN
Solar/Wind Harmer
20.403
944591AF1-124 GEN
Solar/Wind Harmer
123.514
944631AF1-128 GEN
Adder
114.357
316072AD1-144
Solar/Wind Harmer
0.54
971317AH1-138 GEN
Solar/Wind Harmer
3.315
3143336POWHATN
Solar/Wind Harmer
3.025
972219AH1-694 GEN
Adder
3.278
971547AH1-271 GEN
Solar/Wind Harmer
6.065
960081AF2-299 GEN
Solar/Wind Harmer
2.688
962571AG1-106 GEN
Solar/Wind Harmer
3.374
3145823KELFORD
Solar/Wind Harmer
-0.023
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
972263AH1-716 GEN
50/50
139.063
971281AH1-106 GEN
Solar/Wind Harmer
4.714
3143316POE
Solar/Wind Harmer
-0.108
316369SG1_INVT
Solar/Wind Harmer
4.823
319010AE1-072 C
Solar/Wind Harmer
5.402
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.711
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
972189AH1-679 GEN
Adder
3.913
315611Z1-036_GEN2
Solar/Wind Harmer
6.367
3143873LANEXA
Solar/Wind Harmer
-0.015
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
315662AE1-191 GEN
Solar/Wind Harmer
3.067
3141873WAN 176
Solar/Wind Harmer
-0.005
970581AG2-369 GEN
Solar/Wind Harmer
13.538
315816AE2-034 GEN
Solar/Wind Harmer
2.02
3138133OCRAN
Solar/Wind Harmer
-0.007
3152261N ANNA2
50/50
20.32
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.056
3147666LOUISA
Solar/Wind Harmer
-0.066
965281AG1-393 GEN
Solar/Wind Harmer
3.403
970129AG2-093 GEN
Solar/Wind Harmer
15.226
3144873MCLAUGH
Solar/Wind Harmer
-0.001
961611AG1-000B GEN
Solar/Wind Harmer
5.675
3151171GRAVELC
Adder
3.352
970661AG2-428 GEN
Solar/Wind Harmer
5.062
316382AG1-145 C
Solar/Wind Harmer
0.802
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3141843SHACKLE
Adder
1.16
316405AF2-144 C
Solar/Wind Harmer
0.653
316280AD1-041 GEN
Solar/Wind Harmer
1.917
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
63.229
3156081AA2-088 GEN
Solar/Wind Harmer
7.961
315737AD1-076 GEN
Solar/Wind Harmer
4.654
3150401LDYSMT4
Adder
29.156
962971AG1-146 GEN
Solar/Wind Harmer
4.557
961681AG1-008 GEN
Solar/Wind Harmer
19.023
962331AG1-082 GEN
Solar/Wind Harmer
2.986
316404AE1-155 C
Solar/Wind Harmer
4.568
313506AB2-031 GEN
Solar/Wind Harmer
1.897
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
316044AC1-158 PL1
Solar/Wind Helper
5.216
316450AC1-158 RIC
Solar/Wind Helper
1.391
3152331SURRY 2
50/50
9.99
316192AB2-158 GEN
Solar/Wind Harmer
3.345
316294AC1-161 GEN
Solar/Wind Harmer
8.834
316375AC2-012 GEN
Solar/Wind Harmer
9.341
3145336SMITFLD
Solar/Wind Harmer
-0.107
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
3
3141766HARMONY
Solar/Wind Harmer
-0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.26
3145663CRESWEL
Solar/Wind Harmer
-0.07
316023GEN1_S
Solar/Wind Harmer
1.652
972197AH1-683 GEN
Adder
4.553
3143096IRON208
50/50
1.078
3150771HOPHCF1
50/50
0.977
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3147666LOUISA
Solar/Wind Harmer
-0.115
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
971069AG2-661 GEN
Solar/Wind Harmer
4.274
3150981CHESPKA
Adder
3
971647AH1-324 GEN
Solar/Wind Harmer
13.486
316381AD1-082 GEN
Solar/Wind Harmer
2.472
961611AG1-000B GEN
Solar/Wind Harmer
13.3
3151171GRAVELC
Adder
2.549
970661AG2-428 GEN
Solar/Wind Harmer
28.566
316388AE2-253 GEN
Solar/Wind Harmer
1.807
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316246AF1-032 C
Solar/Wind Harmer
0.54
316159AE1-175 C
Solar/Wind Harmer
0.715
3141843SHACKLE
Adder
1.16
3130156CHOWAN
Solar/Wind Harmer
-0.025
970087AG2-069 GEN
Solar/Wind Harmer
23.613
971163AH1-040 GEN
Solar/Wind Harmer
23.4
3138133OCRAN
Solar/Wind Harmer
-0.015
957481AF2-042 GEN
Solar/Wind Harmer
75.375
316190AA2-174 GEN
Solar/Wind Harmer
0.287
3151751LOISA D
Adder
8.676
970533AG2-339 GEN
50/50
21.564
971213AH1-066 GEN
50/50
0.857
3150681DARBY 2
Adder
17.235
316033AB2-134 GEN
Solar/Wind Harmer
8.705
316236AE1-162_GEN
Solar/Wind Harmer
0.812
970657AG2-426 GEN
Solar/Wind Harmer
8.416
970657AG2-426 GEN
Solar/Wind Harmer
1.76
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.807
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3130086AYDLETT
Solar/Wind Harmer
-0.106
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
315673AE1-157 GEN
Solar/Wind Harmer
18.722
972195AH1-682 GEN
Adder
3.824
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.193
3150341NORNECKC1
Adder
2.143
3150341NORNECKC1
Adder
2.126
3151731LOISA B
Adder
8.676
316336AC2-165 C
Solar/Wind Harmer
4.232
3146206CASHIE
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
17.56
3147043LAWRENC
Adder
1.868
971133AH1-012 GEN
50/50
5.491
3142366NRTHEST
50/50
0.836
3150691DARBY 3
Adder
17.296
3150701DARBY 4
Adder
17.255
3142946ENON
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
2.166
3146456SLIGO L269
Solar/Wind Harmer
3.156
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.748
316433W1029_GEN2
Solar/Wind Harmer
4.748
970933AG2-581 GEN
Solar/Wind Harmer
24.187
315742AE1-103 GEN
Solar/Wind Harmer
2.679
3146376EDENTON
Solar/Wind Harmer
0.756
3146376EDENTON
Solar/Wind Harmer
0.756
957411AF2-035 GEN
Solar/Wind Harmer
11.373
316487AF1-042 GEN
Solar/Wind Harmer
3.17
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.177
316181AB2-040 GEN
Solar/Wind Harmer
3.292
316447AC1-158 HLD
Solar/Wind Helper
11.481
316233AE1-074 FULL
Solar/Wind Harmer
0.78
971283AH1-107 GEN
Solar/Wind Harmer
4.714
944011AF1-069 GEN
Solar/Wind Harmer
16.013
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
972265AH1-717 GEN
Adder
18.606
3151191GRAVEL3
Adder
17.221
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.804
971967AH1-528 GEN
Solar/Wind Harmer
49.715
971167AH1-042 GEN
Solar/Wind Harmer
25.191
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315666AE1-190 GEN
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
0.758
970085AG2-068 GEN
Solar/Wind Harmer
15.742
315732AD1-074 GEN1
Solar/Wind Harmer
4.952
315735AD1-075 GEN1
Solar/Wind Harmer
2.477
965291AG1-394 GEN
Solar/Wind Harmer
2.168
3150411LDYSMT5
Adder
29.247
972215AH1-692 GEN
Adder
4.735
962981AG1-147 GEN
Solar/Wind Harmer
10.632
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.208
3145513AHOSKIE
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.397
315652AC1-086 GEN
Solar/Wind Harmer
26.401
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3141813NORNECK
Solar/Wind Harmer
-0.023
972193AH1-681 GEN
Adder
3.349
316164AC1-076 GEN
Solar/Wind Helper
1.38
3138216PACIFIC
Solar/Wind Helper
0.038
3152251N ANNA1
50/50
20.321
970119AG2-088 GEN
50/50
35.422
3150851SPRUNCC
50/50
1.216
970659AG2-427 GEN
Solar/Wind Harmer
14.335
316093AE2-104_GEN
Solar/Wind Harmer
7.718
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.367
970919AG2-571 GEN
Solar/Wind Harmer
8.004
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.719
962861AG1-135 GEN
Solar/Wind Harmer
8.919
3146263WOODLND
Solar/Wind Harmer
-0.024
315693AD1-088 GEN
Solar/Wind Harmer
11.811
962491AG1-098 GEN
Solar/Wind Harmer
15.746
316011AB1-132 GEN
Solar/Wind Harmer
4.91
3145963POPLR C
Solar/Wind Harmer
-0.023
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316174AB2-169 GEN
Solar/Wind Harmer
3.577
316045AC1-158 PL2
Solar/Wind Helper
16.699
316006AB2-029 C
Solar/Wind Helper
0.14
3146206CASHIE
Solar/Wind Harmer
-0.024
316318V4-068
Solar/Wind Harmer
0.603
961941AG1-037 GEN
Solar/Wind Harmer
0.18
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
3150351NORNECKC2
Adder
2.04
316212AC1-099_GEN
Solar/Wind Harmer
1.965
3144293JTRSVLE
Adder
0.605
972277AH1-723 GEN
Adder
87.353
957871AF2-081 GEN
Solar/Wind Harmer
13.387
316312AB1-027
Solar/Wind Harmer
0.901
315833AF1-017_GEN
Solar/Wind Harmer
5.072
316315AB2-025 C
Solar/Wind Harmer
0.715
957831AF2-077 GEN
Solar/Wind Harmer
0.783
316314AB2-024 C
Solar/Wind Harmer
2.185
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
316411AF1-147_GEN1
Solar/Wind Helper
0.79
316415AF1-147_GEN2
Solar/Wind Helper
0.79
3146516WINFALL
Solar/Wind Harmer
-0.026
316203AE2-005 GEN
Solar/Wind Harmer
10.757
316313AB2-026
Solar/Wind Harmer
0.688
316156AD2-030 GEN
Solar/Wind Harmer
0.677
315614AA2-178 GEN
Solar/Wind Harmer
2.693
971157AH1-035 GEN
Solar/Wind Harmer
3.07
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
19.023
316484AD2-074 GEN
Solar/Wind Harmer
6.058
316463AE2-346 GEN
Solar/Wind Harmer
0.387
316140AB2-099
Solar/Wind Harmer
0.161
3146263WOODLND
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.023
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315733AD1-074 GEN2
Solar/Wind Harmer
4.952
972213AH1-691 GEN
Adder
4.735
970601AG2-382 GEN
Solar/Wind Harmer
10.614
946281AF1-292 GEN
Solar/Wind Harmer
0.535
316087AB2-174 GEN
Solar/Wind Harmer
3.379
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.204
315813AE1-149 C
Solar/Wind Harmer
16.949
970133AG2-095 GEN
Solar/Wind Harmer
3.047
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.375
3151221GRAVEL6
Adder
17.422
3142946ENON
Solar/Wind Harmer
-0.009
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.257
3142416OLDCHRC
Solar/Wind Harmer
2.696
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
3145273HOLLAND
Solar/Wind Harmer
-0.019
316473AC1-191 GEN
Solar/Wind Harmer
2.785
3146376EDENTON
Solar/Wind Harmer
-0.025
3141766HARMONY
Solar/Wind Harmer
2.268
966881AG1-559 GEN
Solar/Wind Harmer
0.76
316365GEN2_N
Solar/Wind Harmer
1.652
3150371LDYSMT1
Adder
28.172
3146206CASHIE
Solar/Wind Harmer
-0.024
970009AG2-005 GEN
Solar/Wind Harmer
3.008
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.225
316478AD1-087 GEN
Solar/Wind Harmer
2.009
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
972255AH1-712 GEN
Adder
74.962
3150801HOPHCF4
50/50
1.421
3151101ELIZAR3
50/50
23.68
315839AE2-212 C
Solar/Wind Harmer
0.823
944601AF1-125 GEN
Solar/Wind Harmer
121.15
315778AD1-151 GEN
Solar/Wind Harmer
23.4
3144216WINCHST
Adder
0.896
316258AE1-075 C
Solar/Wind Harmer
0.619
3143336POWHATN
Solar/Wind Harmer
2.572
966621AG1-532 GEN
Solar/Wind Harmer
0.485
316317KELFORD C
Solar/Wind Harmer
1.1
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
3.537
3144293JTRSVLE
Adder
0.605
3151761LOISA E
Adder
17.688
972183AH1-676 GEN
Adder
136.298
3141316ARNOLDS
Adder
0.29
3141196NOKESVL
Solar/Wind Helper
1.131
944641AF1-129 GEN
50/50
122.767
3150791HOPHCF3
50/50
0.977
3143526WINTERP
Solar/Wind Harmer
-0.15
315697AD1-025 GEN
Solar/Wind Harmer
5.46
316316AC1-027 C
Solar/Wind Harmer
0.828
316185AD1-033 GEN
Solar/Wind Harmer
2.842
316075AC2-137 C
Solar/Wind Harmer
0.719
972185AH1-677 GEN
Adder
13.26
3144356SAPONY
Solar/Wind Harmer
0.924
316441AF1-014 GEN
Solar/Wind Harmer
1.72
3150391LDYSMT3
Adder
29.101
970099AG2-077 GEN
Solar/Wind Harmer
30.15
3145783HORNRTN
Solar/Wind Harmer
2.745
3145783HORNRTN
Solar/Wind Harmer
2.196
3145783HORNRTN
Solar/Wind Harmer
0.686
3145783HORNRTN
Solar/Wind Harmer
0.275
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3144293JTRSVLE
Adder
0.605
3144293JTRSVLE
Adder
0.51
CPLELTFEXP_CPLE->PJM
CLTF
12.136
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.163
NYPJM->LTFIMP_NY
CLTF
3.266
LGEELTFEXP_LGEE->PJM
CLTF
1.371
WECLTFEXP_WEC->PJM
CLTF
0.662
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.027
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.441
MECLTFEXP_MEC->PJM
CLTF
3.751
SIGELTFEXP_SIGE->PJM
CLTF
0.114
LAGNLTFEXP_LAGN->PJM
CLTF
8.398
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.505
TVALTFEXP_TVA->PJM
CLTF
4.252

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: 545T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: 545T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:182.6 %
Rating:3118.0 MVA
Rating Type:C
MVA to Mitigate:5693.43
MW Contribution:5.1
Bus #Bus NameTypeMW Contribution
3150681DARBY 2
Adder
17.056
316033AB2-134 GEN
Solar/Wind Harmer
8.573
316236AE1-162_GEN
Solar/Wind Harmer
0.799
970657AG2-426 GEN
Solar/Wind Harmer
8.268
970657AG2-426 GEN
Solar/Wind Harmer
1.729
3145506HICKORY
Solar/Wind Harmer
-0.105
971285AH1-108 GEN
50/50
1.961
941031AE2-094 GEN
Solar/Wind Harmer
49.887
3151081ELIZAR1
Adder
21.638
3151091ELIZAR2
Adder
21.263
3152611GOSPORTB
Adder
3.004
3152621GOSPORTC
Adder
2.55
3143526WINTERP
Solar/Wind Harmer
-0.147
970133AG2-095 GEN
Solar/Wind Harmer
3.004
315813AE1-149 C
Solar/Wind Harmer
16.657
3142946ENON
Solar/Wind Harmer
-0.009
3145336SMITFLD
Solar/Wind Harmer
-0.01
3142416OLDCHRC
Solar/Wind Harmer
2.673
3151221GRAVEL6
Adder
17.144
316083AB2-161 GEN
Solar/Wind Harmer
4.299
3146456SLIGO L269
Solar/Wind Harmer
-0.026
971153AH1-033 GEN
Solar/Wind Harmer
3.198
3142433PROV 92
Adder
0.447
971507AH1-251 GEN
50/50
16.115
316192AB2-158 GEN
Solar/Wind Harmer
3.431
316294AC1-161 GEN
Solar/Wind Harmer
8.675
316375AC2-012 GEN
Solar/Wind Harmer
9.174
3145336SMITFLD
Solar/Wind Harmer
-0.105
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
-0.026
3142433PROV 92
Solar/Wind Harmer
-0.103
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
966881AG1-559 GEN
Solar/Wind Harmer
0.262
971777AH1-397 GEN
Solar/Wind Harmer
2.977
3141766HARMONY
Solar/Wind Harmer
-0.005
972197AH1-683 GEN
Adder
4.637
3145663CRESWEL
Solar/Wind Harmer
-0.068
316336AC2-165 C
Solar/Wind Harmer
4.171
961951AG1-038 GEN
Solar/Wind Harmer
3.162
316023GEN1_S
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
971795AH1-408 GEN
Solar/Wind Harmer
17.176
3147043LAWRENC
Adder
1.827
315773AC2-141 GEN
Solar/Wind Harmer
11.22
944581AF1-123 GEN
Solar/Wind Harmer
120.829
970293AG2-193 GEN
Solar/Wind Harmer
3.321
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.496
3150921YORKTN3
Adder
5.882
316320Y1-086
Solar/Wind Harmer
1.522
316435W1029_GEN3
Solar/Wind Harmer
4.659
3146516WINFALL
Solar/Wind Harmer
-0.026
316203AE2-005 GEN
Solar/Wind Harmer
10.672
316156AD2-030 GEN
Solar/Wind Harmer
0.672
316313AB2-026
Solar/Wind Harmer
0.677
315614AA2-178 GEN
Solar/Wind Harmer
2.639
971157AH1-035 GEN
Solar/Wind Harmer
3.007
316484AD2-074 GEN
Solar/Wind Harmer
6.042
3145893MURPHYS
Solar/Wind Harmer
0.165
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.624
971223AH1-071 GEN
Solar/Wind Harmer
3.653
316240AF1-291 C
Solar/Wind Harmer
0.81
3150671DARBY 1
Adder
17.036
3142296MT RD221
Adder
0.757
316036AC1-147 C
Solar/Wind Harmer
0.715
3150991CHESPKB
Adder
2.471
3150991CHESPKB
Adder
2.412
3142956BIRDNECK
Solar/Wind Harmer
1.42
316018AA1-139 ULT2
Solar/Wind Harmer
2.252
966871AG1-558 GEN
Solar/Wind Harmer
0.774
966871AG1-558 GEN
Solar/Wind Harmer
0.265
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
972187AH1-678 GEN
Adder
6.489
970317AG2-208 GEN
Solar/Wind Harmer
11.157
316065AD1-022 GEN
Solar/Wind Harmer
11.919
3145893MURPHYS
Solar/Wind Harmer
0.662
3145893MURPHYS
Solar/Wind Harmer
-0.043
316426AA2-053 GEN
Solar/Wind Harmer
2.308
966811AG1-552 GEN
Solar/Wind Harmer
2.56
3151721LOISA A
Adder
10.067
3152251N ANNA1
50/50
19.45
970119AG2-088 GEN
50/50
34.68
3150851SPRUNCC
50/50
1.198
316045AC1-158 PL2
Solar/Wind Harmer
21.331
970659AG2-427 GEN
Solar/Wind Harmer
14.084
316093AE2-104_GEN
Solar/Wind Harmer
7.576
3146516WINFALL
Solar/Wind Harmer
-0.083
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.245
970919AG2-571 GEN
Solar/Wind Harmer
7.807
962861AG1-135 GEN
Solar/Wind Harmer
8.906
3145893MURPHYS
Solar/Wind Harmer
-0.094
3145893MURPHYS
Solar/Wind Harmer
0.704
3141726DUNNSVL
Solar/Wind Harmer
-0.093
3146263WOODLND
Solar/Wind Harmer
-0.023
315693AD1-088 GEN
Solar/Wind Harmer
11.547
962491AG1-098 GEN
Solar/Wind Harmer
15.398
316011AB1-132 GEN
Solar/Wind Harmer
4.801
3145963POPLR C
Solar/Wind Harmer
-0.023
316174AB2-169 GEN
Solar/Wind Harmer
3.498
316006AB2-029 C
Solar/Wind Helper
0.108
316164AC1-076 GEN
Solar/Wind Harmer
2.874
316233AE1-074 FULL
Solar/Wind Harmer
0.766
971283AH1-107 GEN
Solar/Wind Harmer
4.628
316132AB2-190 GEN1
Solar/Wind Harmer
2.695
944011AF1-069 GEN
Solar/Wind Harmer
15.631
972265AH1-717 GEN
Adder
18.309
3151191GRAVEL3
Adder
16.946
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.789
971167AH1-042 GEN
Solar/Wind Harmer
24.945
971967AH1-528 GEN
Solar/Wind Harmer
48.532
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315666AE1-190 GEN
Solar/Wind Harmer
0.761
957601AF2-054 GEN
Solar/Wind Harmer
0.752
3150411LDYSMT5
Adder
29.791
972215AH1-692 GEN
Adder
4.823
970085AG2-068 GEN
Solar/Wind Harmer
15.354
962981AG1-147 GEN
Solar/Wind Harmer
10.594
315732AD1-074 GEN1
Solar/Wind Harmer
4.85
315735AD1-075 GEN1
Solar/Wind Harmer
2.426
965291AG1-394 GEN
Solar/Wind Harmer
2.123
3145893MURPHYS
Solar/Wind Harmer
-0.064
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.204
3145513AHOSKIE
Solar/Wind Harmer
-0.023
315607AA1-063A GEN
Solar/Wind Harmer
2.345
3141813NORNECK
Solar/Wind Harmer
-0.023
315652AC1-086 GEN
Solar/Wind Harmer
25.813
3137643SOCKMAN
Solar/Wind Harmer
-0.091
972193AH1-681 GEN
Adder
3.309
3138216PACIFIC
Solar/Wind Helper
0.038
3143096IRON208
50/50
1.065
3147666LOUISA
Solar/Wind Harmer
-0.117
3143226MDLTHAN
Solar/Wind Harmer
-0.029
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
6.077
316458AB2-190 GEN2
Solar/Wind Harmer
2.695
971069AG2-661 GEN
Solar/Wind Harmer
4.21
971647AH1-324 GEN
Solar/Wind Harmer
13.278
961611AG1-000B GEN
Solar/Wind Harmer
13.092
3150981CHESPKA
Adder
2.946
3151171GRAVELC
Adder
2.508
316381AD1-082 GEN
Solar/Wind Harmer
2.429
970661AG2-428 GEN
Solar/Wind Harmer
28.06
3138126ROCKLANDING
Solar/Wind Harmer
0.081
316388AE2-253 GEN
Solar/Wind Harmer
1.774
316159AE1-175 C
Solar/Wind Harmer
0.706
316246AF1-032 C
Solar/Wind Harmer
0.53
3141843SHACKLE
Adder
1.151
3130156CHOWAN
Solar/Wind Harmer
-0.025
3138133OCRAN
Solar/Wind Harmer
-0.015
970087AG2-069 GEN
Solar/Wind Harmer
23.032
971163AH1-040 GEN
Solar/Wind Harmer
22.931
957481AF2-042 GEN
Solar/Wind Harmer
73.619
316190AA2-174 GEN
Solar/Wind Harmer
0.281
3151751LOISA D
Adder
10.119
971531AH1-263 GEN
50/50
59.005
971281AH1-106 GEN
Solar/Wind Harmer
4.628
3143316POE
Solar/Wind Harmer
-0.106
316369SG1_INVT
Solar/Wind Harmer
4.75
319010AE1-072 C
Solar/Wind Harmer
5.302
972189AH1-679 GEN
Adder
3.909
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.698
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.245
315662AE1-191 GEN
Solar/Wind Harmer
3.043
3141873WAN 176
Solar/Wind Harmer
-0.005
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
972213AH1-691 GEN
Adder
4.823
3138133OCRAN
Solar/Wind Harmer
-0.007
970581AG2-369 GEN
Solar/Wind Harmer
13.205
315816AE2-034 GEN
Solar/Wind Harmer
1.979
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315733AD1-074 GEN2
Solar/Wind Harmer
4.85
970601AG2-382 GEN
Solar/Wind Harmer
10.393
946281AF1-292 GEN
Solar/Wind Harmer
0.523
316087AB2-174 GEN
Solar/Wind Harmer
3.305
972205AH1-687 GEN
Adder
7.173
3152261N ANNA2
50/50
19.448
3150861SPRUNCD
50/50
1.198
3143096IRON208
50/50
1.065
3143096IRON208
50/50
1.043
316044AC1-158 PL1
Solar/Wind Harmer
6.668
316450AC1-158 RIC
Solar/Wind Harmer
1.778
3147666LOUISA
Solar/Wind Harmer
-0.067
965281AG1-393 GEN
Solar/Wind Harmer
3.35
970129AG2-093 GEN
Solar/Wind Harmer
15.004
961611AG1-000B GEN
Solar/Wind Harmer
5.586
3144873MCLAUGH
Solar/Wind Harmer
-0.001
3151171GRAVELC
Adder
3.298
970661AG2-428 GEN
Solar/Wind Harmer
4.973
316382AG1-145 C
Solar/Wind Harmer
0.792
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3141843SHACKLE
Adder
1.151
316280AD1-041 GEN
Solar/Wind Harmer
1.902
3141873WAN 176
Solar/Wind Harmer
2.985
316405AF2-144 C
Solar/Wind Harmer
0.643
3150401LDYSMT4
Adder
29.698
970917AG2-570 GEN
Solar/Wind Harmer
61.676
962971AG1-146 GEN
Solar/Wind Harmer
4.54
3156081AA2-088 GEN
Solar/Wind Harmer
7.797
315737AD1-076 GEN
Solar/Wind Harmer
4.558
316404AE1-155 C
Solar/Wind Harmer
4.564
961681AG1-008 GEN
Solar/Wind Harmer
18.624
962331AG1-082 GEN
Solar/Wind Harmer
2.922
313506AB2-031 GEN
Solar/Wind Harmer
1.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3145506HICKORY
Solar/Wind Harmer
-0.063
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.774
3137176SLIGO L2192
Solar/Wind Harmer
-0.104
3130086AYDLETT
Solar/Wind Harmer
-0.104
3146626S HERTFORD
Solar/Wind Harmer
-0.025
3146626S HERTFORD
Solar/Wind Harmer
-0.025
315673AE1-157 GEN
Solar/Wind Harmer
18.955
972195AH1-682 GEN
Adder
3.895
3150341NORNECKC1
Adder
2.147
3150341NORNECKC1
Adder
2.13
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.189
3151731LOISA B
Adder
10.119
940641AE2-051 GEN
Solar/Wind Harmer
25.691
939411AE1-173 GEN
Solar/Wind Harmer
135.819
315671AE2-027_GEN
Solar/Wind Harmer
20.092
944631AF1-128 GEN
Adder
112.977
944591AF1-124 GEN
Solar/Wind Harmer
121.264
316072AD1-144
Solar/Wind Harmer
0.531
971317AH1-138 GEN
Solar/Wind Harmer
3.272
3143336POWHATN
Solar/Wind Harmer
2.977
972219AH1-694 GEN
Adder
3.339
971547AH1-271 GEN
Solar/Wind Harmer
5.939
960081AF2-299 GEN
Solar/Wind Harmer
2.629
964211AG1-282 GEN
Solar/Wind Harmer
0.702
3150351NORNECKC2
Adder
2.044
962571AG1-106 GEN
Solar/Wind Harmer
3.298
3145823KELFORD
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.074
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
972277AH1-723 GEN
Adder
86.298
315839AE2-212 C
Solar/Wind Harmer
0.81
315778AD1-151 GEN
Solar/Wind Harmer
23.05
944601AF1-125 GEN
Solar/Wind Harmer
118.944
3151101ELIZAR3
Adder
21.915
3144216WINCHST
Adder
0.884
316258AE1-075 C
Solar/Wind Harmer
0.609
3143336POWHATN
Solar/Wind Harmer
2.53
966621AG1-532 GEN
Solar/Wind Harmer
0.474
3150351NORNECKC2
Adder
2.079
316317KELFORD C
Solar/Wind Harmer
1.076
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.09
3145796HORNRTN
Solar/Wind Harmer
-0.023
3144293JTRSVLE
Adder
0.594
3151761LOISA E
Adder
20.63
972183AH1-676 GEN
Adder
160.944
3141316ARNOLDS
Adder
0.31
3141196NOKESVL
Solar/Wind Helper
0.97
944641AF1-129 GEN
50/50
120.961
3143526WINTERP
Solar/Wind Harmer
-0.147
315697AD1-025 GEN
Solar/Wind Harmer
5.377
316316AC1-027 C
Solar/Wind Harmer
0.813
316185AD1-033 GEN
Solar/Wind Harmer
2.79
316075AC2-137 C
Solar/Wind Harmer
0.712
3144356SAPONY
Solar/Wind Harmer
0.905
972185AH1-677 GEN
Adder
12.941
316441AF1-014 GEN
Solar/Wind Harmer
1.706
3150391LDYSMT3
Adder
29.642
970099AG2-077 GEN
Solar/Wind Harmer
29.447
316077AC2-138 C
Solar/Wind Harmer
0.486
3145783HORNRTN
Solar/Wind Harmer
2.684
3145783HORNRTN
Solar/Wind Harmer
2.147
3145783HORNRTN
Solar/Wind Harmer
0.671
3145783HORNRTN
Solar/Wind Harmer
0.268
3145796HORNRTN
Solar/Wind Harmer
-0.067
3144293JTRSVLE
Adder
0.594
3144293JTRSVLE
Adder
0.5
316468AD1-105 GEN
Solar/Wind Harmer
1.252
3152601GOSPORTA
Adder
2.352
971445AH1-216 GEN
Solar/Wind Harmer
16.401
316312AB1-027
Solar/Wind Harmer
0.894
957871AF2-081 GEN
Solar/Wind Harmer
13.142
315833AF1-017_GEN
Solar/Wind Harmer
4.98
970673AG2-436 GEN
Solar/Wind Harmer
54.922
970673AG2-436 GEN
Solar/Wind Harmer
27.809
316315AB2-025 C
Solar/Wind Harmer
0.7
957831AF2-077 GEN
Solar/Wind Harmer
0.774
316314AB2-024 C
Solar/Wind Harmer
2.168
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.072
3145796HORNRTN
Solar/Wind Harmer
-0.009
316411AF1-147_GEN1
Solar/Wind Helper
0.769
316415AF1-147_GEN2
Solar/Wind Helper
0.769
316303AF2-085
50/50
4.624
970603AG2-384 GEN
50/50
5.102
3151201GRAVEL4
Adder
17.164
3151211GRAVEL5
Adder
16.946
315976AC1-164 GENA
Solar/Wind Harmer
27.715
316169AC1-164_GENC
Solar/Wind Harmer
23.943
315975AC1-164 GENB
Solar/Wind Harmer
0.82
316349AD2-085 GEN
Solar/Wind Harmer
2.332
316311AC2-079 GEN
Solar/Wind Harmer
13.224
315835AF2-110_GEN
Solar/Wind Harmer
3.257
313526AB2-022
Solar/Wind Harmer
0.701
3146396TANGLEW
Solar/Wind Harmer
0.476
315814AE2-033 C
Solar/Wind Harmer
24.069
3142433PROV 92
Adder
0.447
3142433PROV 92
Adder
0.447
316059AD1-063 C
Solar/Wind Harmer
0.572
3150381LDYSMT2
Adder
28.511
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3146206CASHIE
Solar/Wind Harmer
-0.024
316318V4-068
Solar/Wind Harmer
0.591
961941AG1-037 GEN
Solar/Wind Harmer
0.176
3146043SEABORD
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.046
3145683EARLEYS
Solar/Wind Harmer
-0.023
3145683EARLEYS
Solar/Wind Harmer
-0.023
971133AH1-012 GEN
50/50
5.464
3142366NRTHEST
50/50
0.827
3150691DARBY 3
50/50
18.162
3150701DARBY 4
50/50
18.119
316447AC1-158 HLD
Solar/Wind Harmer
14.664
3142946ENON
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
2.127
3146456SLIGO L269
Solar/Wind Harmer
3.098
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.659
316433W1029_GEN2
Solar/Wind Harmer
4.659
957411AF2-035 GEN
Solar/Wind Harmer
11.475
970933AG2-581 GEN
Solar/Wind Harmer
23.615
315742AE1-103 GEN
Solar/Wind Harmer
2.627
3146376EDENTON
Solar/Wind Harmer
0.741
3146376EDENTON
Solar/Wind Harmer
0.741
316487AF1-042 GEN
Solar/Wind Harmer
3.162
958261AF2-120 GEN
Solar/Wind Harmer
9.168
3146173TUNIS
Solar/Wind Harmer
-0.023
3146173TUNIS
Solar/Wind Harmer
-0.023
316181AB2-040 GEN
Solar/Wind Harmer
3.22
316463AE2-346 GEN
Solar/Wind Harmer
0.378
316140AB2-099
Solar/Wind Harmer
0.158
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3150331BIRCHWDA
Adder
20.259
3142433PROV 92
Adder
0.447
316473AC1-191 GEN
Solar/Wind Harmer
2.772
966881AG1-559 GEN
Solar/Wind Harmer
0.767
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
2.25
3146376EDENTON
Solar/Wind Harmer
-0.025
3150371LDYSMT1
Adder
28.696
970009AG2-005 GEN
Solar/Wind Harmer
3
316365GEN2_N
Solar/Wind Harmer
1.617
3146206CASHIE
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.023
3156021HOLLOMANSOL
Solar/Wind Harmer
3.157
3147043LAWRENC
Solar/Wind Harmer
-0.013
316478AD1-087 GEN
Solar/Wind Harmer
1.962
316486AD2-202 GEN
Solar/Wind Harmer
0.574
972255AH1-712 GEN
Adder
74.056
CPLELTFEXP_CPLE->PJM
CLTF
11.751
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.921
NYPJM->LTFIMP_NY
CLTF
3.258
LGEELTFEXP_LGEE->PJM
CLTF
1.156
WECLTFEXP_WEC->PJM
CLTF
0.544
CBM West 1LTFEXP_CBM-W1->PJM
CBM
17.526
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.238
MECLTFEXP_MEC->PJM
CLTF
3.227
SIGELTFEXP_SIGE->PJM
CLTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
7.753
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.482
TVALTFEXP_TVA->PJM
CLTF
3.93

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 552_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:179.85 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5791.82
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
3143526WINTERP
Solar/Wind Harmer
1.34
940641AE2-051 GEN
Solar/Wind Harmer
19.885
939411AE1-173 GEN
Solar/Wind Harmer
105.071
315671AE2-027_GEN
Solar/Wind Harmer
15.49
944591AF1-124 GEN
Solar/Wind Harmer
54.321
944631AF1-128 GEN
Adder
114.478
316072AD1-144
Solar/Wind Harmer
0.086
971317AH1-138 GEN
Solar/Wind Harmer
1.763
3143336POWHATN
Solar/Wind Harmer
4.063
972219AH1-694 GEN
Adder
3.304
971547AH1-271 GEN
Solar/Wind Harmer
4.597
960081AF2-299 GEN
Solar/Wind Harmer
2.037
962571AG1-106 GEN
Solar/Wind Harmer
2.963
3145823KELFORD
Solar/Wind Harmer
0.207
3145783HORNRTN
Solar/Wind Harmer
0.205
3145796HORNRTN
Solar/Wind Harmer
0.677
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.041
316212AC1-099_GEN
Solar/Wind Harmer
1.035
316129AC1-054 GEN
Solar/Wind Harmer
0.746
971065AG2-659 GEN
Solar/Wind Harmer
8.425
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3144293JTRSVLE
Adder
0.609
316322AB2-045
Solar/Wind Harmer
0.001
970401AG2-262 GEN
Solar/Wind Harmer
1.071
972003AH1-546 GEN
Solar/Wind Harmer
7.446
3147623JAMES R
Solar/Wind Harmer
0.377
972277AH1-723 GEN
Adder
88.606
3152251N ANNA1
50/50
19.951
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
316045AC1-158 PL2
Solar/Wind Harmer
9.742
970659AG2-427 GEN
Solar/Wind Harmer
11.598
316093AE2-104_GEN
Solar/Wind Harmer
3.967
3146516WINFALL
Solar/Wind Harmer
0.752
3146516WINFALL
Solar/Wind Harmer
0.232
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
970919AG2-571 GEN
Solar/Wind Harmer
7.971
3145893MURPHYS
Solar/Wind Harmer
0.86
3145893MURPHYS
Solar/Wind Harmer
0.956
962861AG1-135 GEN
Solar/Wind Harmer
6.776
315693AD1-088 GEN
Solar/Wind Harmer
10.092
3146263WOODLND
Solar/Wind Harmer
0.21
962491AG1-098 GEN
Solar/Wind Harmer
11.964
316011AB1-132 GEN
Solar/Wind Harmer
3.787
3145963POPLR C
Solar/Wind Harmer
0.207
3141726DUNNSVL
Solar/Wind Harmer
0.83
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316337AD2-073 GEN
Solar/Wind Harmer
0.169
316494AC1-189 GEN
Solar/Wind Harmer
0.649
963171AG1-166 GEN
Solar/Wind Harmer
1.021
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.149
3146776BUCKING
Solar/Wind Harmer
0.073
3143096IRON208
50/50
1.079
3150771HOPHCF1
50/50
0.977
3147666LOUISA
Solar/Wind Harmer
1.096
3143226MDLTHAN
Solar/Wind Harmer
0.265
3142543TWELFTH
Solar/Wind Harmer
0.023
970129AG2-093 GEN
Solar/Wind Harmer
6.846
316458AB2-190 GEN2
Solar/Wind Harmer
1.291
971069AG2-661 GEN
Solar/Wind Harmer
4.273
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
10.238
961611AG1-000B GEN
Solar/Wind Harmer
12.573
316381AD1-082 GEN
Solar/Wind Harmer
0.25
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
23.769
316388AE2-253 GEN
Solar/Wind Harmer
0.746
3138126ROCKLANDING
Solar/Wind Harmer
0.109
316159AE1-175 C
Solar/Wind Harmer
0.205
316246AF1-032 C
Solar/Wind Harmer
0.107
3141843SHACKLE
Adder
1.161
3130156CHOWAN
Solar/Wind Harmer
0.226
970087AG2-069 GEN
Solar/Wind Harmer
17.86
3138133OCRAN
Solar/Wind Harmer
0.133
971163AH1-040 GEN
Solar/Wind Harmer
17.736
957481AF2-042 GEN
Solar/Wind Harmer
57.154
316190AA2-174 GEN
Solar/Wind Harmer
0
3146293MARTNCO
Solar/Wind Harmer
0.185
970685AG2-442 GEN
Solar/Wind Harmer
14.314
971563AH1-280 GEN
Solar/Wind Harmer
2.042
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.755
3145493TOT1
Solar/Wind Harmer
0.843
316049AB1-081 GEN
Solar/Wind Harmer
1.066
316254AC1-120 GEN1
Solar/Wind Harmer
0.366
3151751LOISA D
Adder
10.898
971377AH1-170 GEN
Solar/Wind Harmer
1.734
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
316044AC1-158 PL1
Solar/Wind Harmer
3.047
316450AC1-158 RIC
Solar/Wind Harmer
0.812
3147666LOUISA
Solar/Wind Harmer
0.63
965281AG1-393 GEN
Solar/Wind Harmer
2.583
970129AG2-093 GEN
Solar/Wind Harmer
14.547
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.393
3151171GRAVELC
Adder
3.35
970661AG2-428 GEN
Solar/Wind Harmer
5.055
316382AG1-145 C
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.231
316405AF2-144 C
Solar/Wind Harmer
0.002
3141843SHACKLE
Adder
1.161
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141873WAN 176
Solar/Wind Harmer
4.013
970917AG2-570 GEN
Solar/Wind Harmer
19.927
3150401LDYSMT4
Adder
29.389
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.798
962971AG1-146 GEN
Solar/Wind Harmer
3.462
961681AG1-008 GEN
Solar/Wind Harmer
15.963
962331AG1-082 GEN
Solar/Wind Harmer
2.263
316404AE1-155 C
Solar/Wind Harmer
0.047
313506AB2-031 GEN
Solar/Wind Harmer
0.648
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3145933PARMELE
Solar/Wind Harmer
0.199
966801AG1-551 GEN
Solar/Wind Harmer
2.319
315785AD2-033 C
Solar/Wind Harmer
1.561
970257AG2-171 GEN
Solar/Wind Harmer
6.143
963181AG1-167 GEN
Solar/Wind Harmer
0.766
3146926FARMVIL
Solar/Wind Harmer
0.114
3146233WITAKRS
Solar/Wind Harmer
0.953
3146233WITAKRS
Solar/Wind Harmer
0.129
3141906WESTMOR
Solar/Wind Harmer
0.074
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
315773AC2-141 GEN
Solar/Wind Harmer
8.863
944581AF1-123 GEN
Solar/Wind Harmer
54.129
3144536CHRHLND
Solar/Wind Harmer
0.036
970659AG2-427 GEN
Solar/Wind Harmer
2.537
970293AG2-193 GEN
Solar/Wind Harmer
2.553
3150921YORKTN3
Adder
5.966
316320Y1-086
Solar/Wind Harmer
0.001
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.232
316313AB2-026
Solar/Wind Harmer
0.144
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.167
315614AA2-178 GEN
Solar/Wind Harmer
1.269
971157AH1-035 GEN
Solar/Wind Harmer
2.618
3145893MURPHYS
Solar/Wind Harmer
0.36
3145893MURPHYS
Solar/Wind Harmer
0.215
957521AF2-046 GEN
Solar/Wind Harmer
15.963
316463AE2-346 GEN
Solar/Wind Harmer
0.182
316140AB2-099
Solar/Wind Harmer
0.076
3146263WOODLND
Solar/Wind Harmer
0.21
3145963POPLR C
Solar/Wind Harmer
0.207
316327AA2-057 GEN
Solar/Wind Harmer
0.292
3132273ORANGE
Solar/Wind Harmer
0.038
961601AG1-000A GEN
Solar/Wind Harmer
13.257
3145543BTLEBRO
Solar/Wind Harmer
0.186
3145543BTLEBRO
Solar/Wind Harmer
0.186
3146776BUCKING
Solar/Wind Harmer
0.066
970737AG2-469 GEN
Solar/Wind Harmer
7.427
316170AC1-121 GEN2
Solar/Wind Harmer
0.183
970221AG2-151 GEN
Solar/Wind Harmer
8.67
970533AG2-339 GEN
50/50
21.472
971213AH1-066 GEN
50/50
0.857
3150681DARBY 2
Adder
17.27
316033AB2-134 GEN
Solar/Wind Harmer
0.014
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
8.383
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3145506HICKORY
Solar/Wind Harmer
0.955
3145506HICKORY
Solar/Wind Harmer
0.573
3145506HICKORY
Solar/Wind Harmer
0.143
971507AH1-251 GEN
50/50
16.627
3152331SURRY 2
50/50
9.986
316192AB2-158 GEN
Solar/Wind Harmer
1.516
316294AC1-161 GEN
Solar/Wind Harmer
4.205
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.958
3142416OLDCHRC
Solar/Wind Harmer
0.62
3142416OLDCHRC
Solar/Wind Harmer
0.237
3146456SLIGO L269
Solar/Wind Harmer
0.237
3142433PROV 92
Solar/Wind Harmer
0.929
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
971777AH1-397 GEN
Solar/Wind Harmer
0.6
3141766HARMONY
Solar/Wind Harmer
0.045
966881AG1-559 GEN
Solar/Wind Harmer
0.262
3145663CRESWEL
Solar/Wind Harmer
0.62
972197AH1-683 GEN
Adder
4.589
316336AC2-165 C
Solar/Wind Harmer
0.009
316023GEN1_S
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
3146173TUNIS
Solar/Wind Harmer
0.213
3145683EARLEYS
Solar/Wind Harmer
0.211
971795AH1-408 GEN
Solar/Wind Harmer
13.875
3147043LAWRENC
Adder
1.866
315722AD1-056 GEN
Solar/Wind Harmer
1.233
970937AG2-583 GEN
Solar/Wind Harmer
11.922
3146083TARBORO
Solar/Wind Harmer
0.189
316359AB2-059 GEN
Solar/Wind Harmer
0.669
3142053HEARTS
Solar/Wind Harmer
0.328
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.429
970133AG2-095 GEN
Solar/Wind Harmer
2.314
315813AE1-149 C
Solar/Wind Harmer
12.857
3145336SMITFLD
Solar/Wind Harmer
0.096
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.41
3142946ENON
Solar/Wind Harmer
0.08
3142416OLDCHRC
Solar/Wind Harmer
2.311
3146456SLIGO L269
Solar/Wind Harmer
0.237
971153AH1-033 GEN
Solar/Wind Harmer
2.744
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
316473AC1-191 GEN
Solar/Wind Harmer
0.781
3145273HOLLAND
Solar/Wind Harmer
0.173
3141766HARMONY
Solar/Wind Harmer
3.026
3146376EDENTON
Solar/Wind Harmer
0.226
3150371LDYSMT1
Adder
28.398
316365GEN2_N
Solar/Wind Harmer
0.488
3146206CASHIE
Solar/Wind Harmer
0.215
970009AG2-005 GEN
Solar/Wind Harmer
1.6
3146173TUNIS
Solar/Wind Harmer
0.213
3156021HOLLOMANSOL
Solar/Wind Harmer
0.965
316478AD1-087 GEN
Solar/Wind Harmer
0.72
316486AD2-202 GEN
Solar/Wind Harmer
0.211
3147043LAWRENC
Solar/Wind Harmer
0.124
971781AH1-399 GEN
Solar/Wind Harmer
0.26
315724AD1-057 GEN
Solar/Wind Harmer
0.731
316131AB2-060 GEN
Solar/Wind Harmer
0.605
959311AF2-222 GEN
Solar/Wind Harmer
17.057
3147133PAMPLIN
Solar/Wind Harmer
0.6
3146073TAR RVR
Solar/Wind Harmer
0.189
3146083TARBORO
Solar/Wind Harmer
0.189
3138543CONSLDL
Solar/Wind Harmer
0.125
971623AH1-311 GEN
Solar/Wind Harmer
0.373
316283AC2-100 C
Solar/Wind Harmer
0.309
972255AH1-712 GEN
Adder
76.037
971133AH1-012 GEN
50/50
5.665
3142366NRTHEST
50/50
0.838
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
6.696
3150701DARBY 4
Adder
17.29
3142946ENON
Solar/Wind Harmer
0.024
316017AA1-139 ULT1
Solar/Wind Harmer
0.133
3146456SLIGO L269
Solar/Wind Harmer
4.201
3146386ELIZ CT
Solar/Wind Harmer
0.235
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
18.312
315742AE1-103 GEN
Solar/Wind Harmer
0.003
957411AF2-035 GEN
Solar/Wind Harmer
9.66
3146376EDENTON
Solar/Wind Harmer
1.006
3146376EDENTON
Solar/Wind Harmer
1.006
3146173TUNIS
Solar/Wind Harmer
0.213
3146173TUNIS
Solar/Wind Harmer
0.213
958261AF2-120 GEN
Solar/Wind Harmer
6.972
316181AB2-040 GEN
Solar/Wind Harmer
0.304
316274AC1-208 GEN
Solar/Wind Harmer
1.032
958211AF2-115 GEN
Solar/Wind Harmer
2.298
3147133PAMPLIN
Solar/Wind Harmer
0.191
3147133PAMPLIN
Solar/Wind Harmer
0.153
3146843MT LREL
Solar/Wind Harmer
0.182
3146843MT LREL
Solar/Wind Harmer
0.182
316222AC1-221 GEN
Solar/Wind Harmer
0.658
315651AD1-115 GEN
Solar/Wind Harmer
0.004
316303AF2-085
50/50
4.712
3150801HOPHCF4
50/50
1.421
315839AE2-212 C
Solar/Wind Harmer
0.002
944601AF1-125 GEN
Solar/Wind Harmer
53.295
315778AD1-151 GEN
Solar/Wind Harmer
19.229
3151101ELIZAR3
Adder
22.283
3144216WINCHST
Adder
0.896
316258AE1-075 C
Solar/Wind Harmer
0.172
3143336POWHATN
Solar/Wind Harmer
3.453
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.207
3145796HORNRTN
Solar/Wind Harmer
0.82
3145796HORNRTN
Solar/Wind Harmer
0.205
3150351NORNECKC2
Adder
2.075
316210AC1-098 GEN
Solar/Wind Harmer
1.857
970909AG2-566 GEN
Solar/Wind Harmer
2.12
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
964241AG1-285 GEN
Solar/Wind Harmer
12.823
3144293JTRSVLE
Adder
0.609
971193AH1-056 GEN
Solar/Wind Harmer
11.648
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.481
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
971683AH1-343 GEN
Solar/Wind Harmer
5.958
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150761HOPPOLC
50/50
0.62
971223AH1-071 GEN
Solar/Wind Harmer
2.827
316240AF1-291 C
Solar/Wind Harmer
0.002
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316036AC1-147 C
Solar/Wind Harmer
0.045
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
3146516WINFALL
Solar/Wind Harmer
0.232
966871AG1-558 GEN
Solar/Wind Harmer
0.267
970317AG2-208 GEN
Solar/Wind Harmer
8.949
316065AD1-022 GEN
Solar/Wind Harmer
9.955
3145893MURPHYS
Solar/Wind Harmer
1.439
3145893MURPHYS
Solar/Wind Harmer
0.387
316426AA2-053 GEN
Solar/Wind Harmer
0.701
966811AG1-552 GEN
Solar/Wind Harmer
2.242
971741AH1-377 GEN
Solar/Wind Harmer
19.978
939181AE1-148 GEN
Solar/Wind Harmer
9.287
3145453TOT5
Solar/Wind Harmer
0.264
961601AG1-000A GEN
Solar/Wind Harmer
3.314
3146776BUCKING
Solar/Wind Harmer
0.73
3146776BUCKING
Solar/Wind Harmer
0.059
964791AG1-342 GEN
Solar/Wind Harmer
3.505
3151721LOISA A
Adder
10.842
971489AH1-241 GEN
Solar/Wind Harmer
8.67
942751AE2-291 GEN
Solar/Wind Harmer
7.283
316339AD2-160 GEN
Solar/Wind Harmer
0.386
3137176SLIGO L2192
Solar/Wind Harmer
0.945
3130086AYDLETT
Solar/Wind Harmer
0.948
3146626S HERTFORD
Solar/Wind Harmer
0.231
3146626S HERTFORD
Solar/Wind Harmer
0.231
315673AE1-157 GEN
Solar/Wind Harmer
15.472
972195AH1-682 GEN
Adder
3.855
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.209
3142666NORTHAMPTON
Solar/Wind Harmer
0.125
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.207
3145593CAROLNA
Solar/Wind Harmer
0.257
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
3145933PARMELE
Solar/Wind Harmer
0.398
3145933PARMELE
Solar/Wind Harmer
0.199
970301AG2-198 GEN
Solar/Wind Harmer
8.48
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
8.19
971775AH1-396 GEN
Solar/Wind Harmer
0.307
3145493TOT1
Solar/Wind Harmer
0.439
966001AG1-469 GEN
Solar/Wind Harmer
0.098
3151731LOISA B
Adder
10.898
944641AF1-129 GEN
50/50
122.768
3150791HOPHCF3
50/50
0.977
3143526WINTERP
Solar/Wind Harmer
1.34
315697AD1-025 GEN
Solar/Wind Harmer
0.27
316316AC1-027 C
Solar/Wind Harmer
0.23
316185AD1-033 GEN
Solar/Wind Harmer
0.007
316075AC2-137 C
Solar/Wind Harmer
0.065
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
1.967
3150391LDYSMT3
Adder
29.334
970099AG2-077 GEN
Solar/Wind Harmer
22.861
3145783HORNRTN
Solar/Wind Harmer
3.653
3145783HORNRTN
Solar/Wind Harmer
2.922
3145783HORNRTN
Solar/Wind Harmer
0.913
3145783HORNRTN
Solar/Wind Harmer
0.365
3145796HORNRTN
Solar/Wind Harmer
0.615
316077AC2-138 C
Solar/Wind Harmer
0.001
316468AD1-105 GEN
Solar/Wind Harmer
-0.064
316034AC1-036 C
Solar/Wind Harmer
0.014
963191AG1-168 GEN
Solar/Wind Harmer
0.766
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
3145603CNETO
Solar/Wind Harmer
0.176
316263AC1-034 GEN
Solar/Wind Harmer
7.082
962561AG1-105 GEN
Solar/Wind Harmer
8.835
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971531AH1-263 GEN
50/50
60.398
971281AH1-106 GEN
Solar/Wind Harmer
3.576
3143316POE
Solar/Wind Harmer
0.962
316369SG1_INVT
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
1.195
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
0.234
3146486SUNBURY
Solar/Wind Harmer
0.234
316321Z2-027
Solar/Wind Harmer
0.044
3145176PASQUOTANK
Solar/Wind Harmer
0.145
3143873LANEXA
Solar/Wind Harmer
0.138
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315662AE1-191 GEN
Solar/Wind Harmer
0.007
3130156CHOWAN
Solar/Wind Harmer
0.226
3130156CHOWAN
Solar/Wind Harmer
0.226
3141873WAN 176
Solar/Wind Harmer
0.045
970581AG2-369 GEN
Solar/Wind Harmer
10.24
3138133OCRAN
Solar/Wind Harmer
0.066
315816AE2-034 GEN
Solar/Wind Harmer
0.951
972213AH1-691 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
0.218
315733AD1-074 GEN2
Solar/Wind Harmer
1.25
970601AG2-382 GEN
Solar/Wind Harmer
8.044
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3146033SCOT NK
Solar/Wind Harmer
0.813
970181AG2-120 GEN
Solar/Wind Harmer
2.429
972205AH1-687 GEN
Adder
7.416
3147346CASHSCORNER
Solar/Wind Harmer
0.37
944491AF1-114 GEN
Solar/Wind Harmer
0.001
316164AC1-076 GEN
Solar/Wind Harmer
0.448
316233AE1-074 FULL
Solar/Wind Harmer
0.206
971283AH1-107 GEN
Solar/Wind Harmer
3.576
944011AF1-069 GEN
Solar/Wind Harmer
14.536
316132AB2-190 GEN1
Solar/Wind Harmer
1.291
972265AH1-717 GEN
Adder
18.594
3151191GRAVEL3
Adder
17.21
3146406KITTY HAWK
Solar/Wind Harmer
0.03
316305AF2-043 C
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
37.517
971167AH1-042 GEN
Solar/Wind Harmer
20.705
3138283WHITEMARSH
Solar/Wind Harmer
0.054
970189AG2-124 GEN
Solar/Wind Harmer
6.735
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970085AG2-068 GEN
Solar/Wind Harmer
11.907
3150411LDYSMT5
Adder
29.481
972215AH1-692 GEN
Adder
4.773
315732AD1-074 GEN1
Solar/Wind Harmer
1.25
315735AD1-075 GEN1
Solar/Wind Harmer
0.626
965291AG1-394 GEN
Solar/Wind Harmer
0.964
962981AG1-147 GEN
Solar/Wind Harmer
8.079
3145893MURPHYS
Solar/Wind Harmer
0.581
3145893MURPHYS
Solar/Wind Harmer
0.215
3145513AHOSKIE
Solar/Wind Harmer
0.443
3145513AHOSKIE
Solar/Wind Harmer
0.212
315607AA1-063A GEN
Solar/Wind Harmer
0.431
315652AC1-086 GEN
Solar/Wind Harmer
22.91
3137643SOCKMAN
Solar/Wind Harmer
0.831
3141813NORNECK
Solar/Wind Harmer
0.205
316005AA1-067
Solar/Wind Harmer
0.209
971443AH1-215 GEN
Solar/Wind Harmer
3.225
3144303KENBRDG
Solar/Wind Harmer
0.153
946301AF1-294 GEN
Solar/Wind Harmer
3.778
315657AE1-056 GEN
Solar/Wind Harmer
6.598
316223AC1-118
Solar/Wind Harmer
0.132
316118AC1-105 GEN
Solar/Wind Harmer
0.462
972193AH1-681 GEN
Adder
3.397
270494AE1-108_GEN
Solar/Wind Harmer
1.716
3138216PACIFIC
Solar/Wind Helper
0.04
971285AH1-108 GEN
50/50
1.991
941031AE2-094 GEN
Solar/Wind Harmer
44.489
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.874
316312AB1-027
Solar/Wind Harmer
0.427
957871AF2-081 GEN
Solar/Wind Harmer
11.843
970673AG2-436 GEN
Solar/Wind Harmer
50.646
970673AG2-436 GEN
Solar/Wind Harmer
33.764
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.19
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.222
970327AG2-215 GEN
Solar/Wind Harmer
7.032
3145796HORNRTN
Solar/Wind Harmer
0.656
3145796HORNRTN
Solar/Wind Harmer
0.082
970831AG2-522 GEN
Solar/Wind Harmer
8.493
3145746EVERETS
Solar/Wind Harmer
0.776
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
3145746EVERETS
Solar/Wind Harmer
0.195
957861AF2-080 GEN
Solar/Wind Harmer
8.286
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
970683AG2-441 GEN
Solar/Wind Harmer
12.781
970681AG2-440 GEN
Solar/Wind Harmer
10.225
3145573BETHELC
Solar/Wind Harmer
0.189
3145573BETHELC
Solar/Wind Harmer
0.189
971447AH1-217 GEN
Solar/Wind Harmer
4.798
970865AG2-541 GEN
Solar/Wind Harmer
5.388
316123AC1-075 GEN
Solar/Wind Harmer
0.194
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
970603AG2-384 GEN
50/50
5.178
3151201GRAVEL4
Adder
17.43
3151211GRAVEL5
Adder
17.21
316349AD2-085 GEN
Solar/Wind Harmer
0.163
316311AC2-079 GEN
Solar/Wind Harmer
6.813
315976AC1-164 GENA
Solar/Wind Harmer
24.491
316169AC1-164_GENC
Solar/Wind Harmer
21.158
315975AC1-164 GENB
Solar/Wind Harmer
0.725
315835AF2-110_GEN
Solar/Wind Harmer
1.619
313526AB2-022
Solar/Wind Harmer
0.127
315814AE2-033 C
Solar/Wind Harmer
18.537
3146396TANGLEW
Solar/Wind Harmer
0.645
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
316059AD1-063 C
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.132
3141783LANCAST
Solar/Wind Harmer
0.088
3150381LDYSMT2
Adder
28.214
3146206CASHIE
Solar/Wind Harmer
0.215
3146043SEABORD
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.422
3145683EARLEYS
Solar/Wind Harmer
0.211
3145683EARLEYS
Solar/Wind Harmer
0.211
961791AG1-021 GEN
Solar/Wind Harmer
1.838
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
14.603
971845AH1-439 GEN
Solar/Wind Harmer
8.313
3147173SINAI
Solar/Wind Harmer
0.175
3147243WELCO
Solar/Wind Harmer
0.11
970165AG2-112 GEN
Solar/Wind Harmer
1.153
970163AG2-111 GEN
Solar/Wind Harmer
1.1
3138266HYDRAULIC
Solar/Wind Harmer
0.006
3138266HYDRAULIC
Solar/Wind Harmer
0.003
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 581_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 581_SRT-S
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:175.06 %
Rating:3220.44 MVA
Rating Type:B
MVA to Mitigate:5637.7
MW Contribution:5.1
Bus #Bus NameTypeMW Contribution
3143526WINTERP
Solar/Wind Harmer
1.319
940641AE2-051 GEN
Solar/Wind Harmer
19.587
939411AE1-173 GEN
Solar/Wind Harmer
103.486
315671AE2-027_GEN
Solar/Wind Harmer
15.248
944591AF1-124 GEN
Solar/Wind Harmer
53.482
944631AF1-128 GEN
Adder
112.66
316072AD1-144
Solar/Wind Harmer
0.085
971317AH1-138 GEN
Solar/Wind Harmer
1.735
3143336POWHATN
Solar/Wind Harmer
3.993
972219AH1-694 GEN
Adder
3.248
971547AH1-271 GEN
Solar/Wind Harmer
4.525
960081AF2-299 GEN
Solar/Wind Harmer
2.005
962571AG1-106 GEN
Solar/Wind Harmer
2.917
3145823KELFORD
Solar/Wind Harmer
0.204
3145783HORNRTN
Solar/Wind Harmer
0.202
3145796HORNRTN
Solar/Wind Harmer
0.666
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.009
316212AC1-099_GEN
Solar/Wind Harmer
1.019
316129AC1-054 GEN
Solar/Wind Harmer
0.734
971065AG2-659 GEN
Solar/Wind Harmer
8.291
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
315687AD1-152 GEN
Solar/Wind Harmer
0.006
316237AB2-079_GEN
Solar/Wind Harmer
0.002
3144293JTRSVLE
Adder
0.599
970401AG2-262 GEN
Solar/Wind Harmer
1.053
316322AB2-045
Solar/Wind Harmer
0.001
972003AH1-546 GEN
Solar/Wind Harmer
7.289
3147623JAMES R
Solar/Wind Harmer
0.368
972277AH1-723 GEN
Adder
86.868
3152251N ANNA1
50/50
19.719
970119AG2-088 GEN
50/50
34.806
3150851SPRUNCC
50/50
1.197
316045AC1-158 PL2
Solar/Wind Harmer
9.665
970659AG2-427 GEN
Solar/Wind Harmer
11.419
316093AE2-104_GEN
Solar/Wind Harmer
3.906
3146516WINFALL
Solar/Wind Harmer
0.741
3146516WINFALL
Solar/Wind Harmer
0.229
315800Z1-036_GEN1
Solar/Wind Harmer
0.002
970919AG2-571 GEN
Solar/Wind Harmer
7.85
3145893MURPHYS
Solar/Wind Harmer
0.847
3145893MURPHYS
Solar/Wind Harmer
0.941
962861AG1-135 GEN
Solar/Wind Harmer
6.67
315693AD1-088 GEN
Solar/Wind Harmer
9.93
3146263WOODLND
Solar/Wind Harmer
0.207
962491AG1-098 GEN
Solar/Wind Harmer
11.772
316011AB1-132 GEN
Solar/Wind Harmer
3.728
3145963POPLR C
Solar/Wind Harmer
0.204
3141726DUNNSVL
Solar/Wind Harmer
0.817
316174AB2-169 GEN
Solar/Wind Harmer
0.005
316337AD2-073 GEN
Solar/Wind Harmer
0.167
316494AC1-189 GEN
Solar/Wind Harmer
0.639
963171AG1-166 GEN
Solar/Wind Harmer
1.003
961671AG1-007 GEN
Solar/Wind Harmer
0.029
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.147
3146776BUCKING
Solar/Wind Harmer
0.072
3143096IRON208
50/50
1.062
3150771HOPHCF1
50/50
0.962
3147666LOUISA
Solar/Wind Harmer
1.067
3143226MDLTHAN
Solar/Wind Harmer
0.261
3142543TWELFTH
Solar/Wind Harmer
0.023
970129AG2-093 GEN
Solar/Wind Harmer
6.738
316458AB2-190 GEN2
Solar/Wind Harmer
1.271
971069AG2-661 GEN
Solar/Wind Harmer
4.206
3150981CHESPKA
Adder
2.949
971647AH1-324 GEN
Solar/Wind Harmer
10.078
961611AG1-000B GEN
Solar/Wind Harmer
12.376
316381AD1-082 GEN
Solar/Wind Harmer
0.246
3151171GRAVELC
Adder
2.508
970661AG2-428 GEN
Solar/Wind Harmer
23.401
316388AE2-253 GEN
Solar/Wind Harmer
0.734
3138126ROCKLANDING
Solar/Wind Harmer
0.107
316159AE1-175 C
Solar/Wind Harmer
0.201
316246AF1-032 C
Solar/Wind Harmer
0.105
3141843SHACKLE
Adder
1.143
3130156CHOWAN
Solar/Wind Harmer
0.223
970087AG2-069 GEN
Solar/Wind Harmer
17.59
3138133OCRAN
Solar/Wind Harmer
0.131
971163AH1-040 GEN
Solar/Wind Harmer
17.461
957481AF2-042 GEN
Solar/Wind Harmer
56.258
316190AA2-174 GEN
Solar/Wind Harmer
0
3146293MARTNCO
Solar/Wind Harmer
0.182
970685AG2-442 GEN
Solar/Wind Harmer
14.068
971563AH1-280 GEN
Solar/Wind Harmer
2.007
3146233WITAKRS
Solar/Wind Harmer
0.743
3146926FARMVIL
Solar/Wind Harmer
0.112
3145493TOT1
Solar/Wind Harmer
0.829
316049AB1-081 GEN
Solar/Wind Harmer
1.05
3151751LOISA D
Adder
10.327
971377AH1-170 GEN
Solar/Wind Harmer
1.696
316254AC1-120 GEN1
Solar/Wind Harmer
0.26
3152261N ANNA2
50/50
19.717
3150861SPRUNCD
50/50
1.197
3143096IRON208
50/50
1.062
3143096IRON208
50/50
1.041
316044AC1-158 PL1
Solar/Wind Harmer
3.023
316450AC1-158 RIC
Solar/Wind Harmer
0.806
3147666LOUISA
Solar/Wind Harmer
0.614
971211AH1-065 GEN
50/50
1.687
3151161SURRY 1
50/50
9.055
315773AC2-141 GEN
Solar/Wind Harmer
8.726
944581AF1-123 GEN
Solar/Wind Harmer
53.293
3144536CHRHLND
Solar/Wind Harmer
0.035
970659AG2-427 GEN
Solar/Wind Harmer
2.498
970293AG2-193 GEN
Solar/Wind Harmer
2.512
3150921YORKTN3
Adder
5.872
316320Y1-086
Solar/Wind Harmer
0.001
965281AG1-393 GEN
Solar/Wind Harmer
2.543
970129AG2-093 GEN
Solar/Wind Harmer
14.319
3144873MCLAUGH
Solar/Wind Harmer
0.006
961611AG1-000B GEN
Solar/Wind Harmer
6.293
3151171GRAVELC
Adder
3.297
970661AG2-428 GEN
Solar/Wind Harmer
4.977
316382AG1-145 C
Solar/Wind Harmer
0.002
3146626S HERTFORD
Solar/Wind Harmer
0.227
316405AF2-144 C
Solar/Wind Harmer
0.002
3141843SHACKLE
Adder
1.143
316280AD1-041 GEN
Solar/Wind Harmer
0.005
3141873WAN 176
Solar/Wind Harmer
3.95
970917AG2-570 GEN
Solar/Wind Harmer
19.626
3150401LDYSMT4
Adder
28.893
3156081AA2-088 GEN
Solar/Wind Harmer
0.005
315737AD1-076 GEN
Solar/Wind Harmer
2.755
962971AG1-146 GEN
Solar/Wind Harmer
3.408
961681AG1-008 GEN
Solar/Wind Harmer
15.715
962331AG1-082 GEN
Solar/Wind Harmer
2.227
316404AE1-155 C
Solar/Wind Harmer
0.047
313506AB2-031 GEN
Solar/Wind Harmer
0.638
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3145933PARMELE
Solar/Wind Harmer
0.196
966801AG1-551 GEN
Solar/Wind Harmer
2.283
315785AD2-033 C
Solar/Wind Harmer
1.535
970257AG2-171 GEN
Solar/Wind Harmer
6.039
963181AG1-167 GEN
Solar/Wind Harmer
0.752
3146233WITAKRS
Solar/Wind Harmer
0.938
3146233WITAKRS
Solar/Wind Harmer
0.127
3146926FARMVIL
Solar/Wind Harmer
0.112
3141906WESTMOR
Solar/Wind Harmer
0.072
3152331SURRY 2
50/50
9.829
316192AB2-158 GEN
Solar/Wind Harmer
1.475
316294AC1-161 GEN
Solar/Wind Harmer
4.14
316375AC2-012 GEN
Solar/Wind Harmer
0.006
3145336SMITFLD
Solar/Wind Harmer
0.943
3142416OLDCHRC
Solar/Wind Harmer
0.61
3142416OLDCHRC
Solar/Wind Harmer
0.234
3146456SLIGO L269
Solar/Wind Harmer
0.234
3142433PROV 92
Solar/Wind Harmer
0.914
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
971777AH1-397 GEN
Solar/Wind Harmer
0.591
3141766HARMONY
Solar/Wind Harmer
0.045
966881AG1-559 GEN
Solar/Wind Harmer
0.257
3145663CRESWEL
Solar/Wind Harmer
0.611
972197AH1-683 GEN
Adder
4.512
316336AC2-165 C
Solar/Wind Harmer
0.008
316023GEN1_S
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
3146173TUNIS
Solar/Wind Harmer
0.21
3145683EARLEYS
Solar/Wind Harmer
0.208
971795AH1-408 GEN
Solar/Wind Harmer
13.656
3147043LAWRENC
Adder
1.836
315722AD1-056 GEN
Solar/Wind Harmer
1.214
970937AG2-583 GEN
Solar/Wind Harmer
11.689
3146083TARBORO
Solar/Wind Harmer
0.186
316359AB2-059 GEN
Solar/Wind Harmer
0.659
3142053HEARTS
Solar/Wind Harmer
0.323
316003AC1-222 GEN
Solar/Wind Harmer
0.004
972135AH1-637 GEN
Solar/Wind Harmer
1.408
315813AE1-149 C
Solar/Wind Harmer
12.658
970133AG2-095 GEN
Solar/Wind Harmer
2.278
3145336SMITFLD
Solar/Wind Harmer
0.094
316083AB2-161 GEN
Solar/Wind Harmer
0.003
3151221GRAVEL6
Adder
17.139
3142946ENON
Solar/Wind Harmer
0.079
3142416OLDCHRC
Solar/Wind Harmer
2.274
3146456SLIGO L269
Solar/Wind Harmer
0.234
971153AH1-033 GEN
Solar/Wind Harmer
2.702
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
316473AC1-191 GEN
Solar/Wind Harmer
0.768
3145273HOLLAND
Solar/Wind Harmer
0.17
3141766HARMONY
Solar/Wind Harmer
2.978
3146376EDENTON
Solar/Wind Harmer
0.223
3150371LDYSMT1
Adder
27.918
316365GEN2_N
Solar/Wind Harmer
0.481
3146206CASHIE
Solar/Wind Harmer
0.212
970009AG2-005 GEN
Solar/Wind Harmer
1.575
3146173TUNIS
Solar/Wind Harmer
0.21
3156021HOLLOMANSOL
Solar/Wind Harmer
0.95
316478AD1-087 GEN
Solar/Wind Harmer
0.708
316486AD2-202 GEN
Solar/Wind Harmer
0.208
3147043LAWRENC
Solar/Wind Harmer
0.122
971781AH1-399 GEN
Solar/Wind Harmer
0.256
315724AD1-057 GEN
Solar/Wind Harmer
0.72
316131AB2-060 GEN
Solar/Wind Harmer
0.595
959311AF2-222 GEN
Solar/Wind Harmer
16.767
3147133PAMPLIN
Solar/Wind Harmer
0.59
3146073TAR RVR
Solar/Wind Harmer
0.186
3146083TARBORO
Solar/Wind Harmer
0.186
3138543CONSLDL
Solar/Wind Harmer
0.123
971623AH1-311 GEN
Solar/Wind Harmer
0.367
316283AC2-100 C
Solar/Wind Harmer
0.304
972255AH1-712 GEN
Adder
74.545
971133AH1-012 GEN
50/50
5.548
3142366NRTHEST
50/50
0.824
3150691DARBY 3
50/50
18.094
3150701DARBY 4
50/50
18.052
316447AC1-158 HLD
Solar/Wind Harmer
6.644
3142946ENON
Solar/Wind Harmer
0.023
316017AA1-139 ULT1
Solar/Wind Harmer
0.131
3146456SLIGO L269
Solar/Wind Harmer
4.136
3146386ELIZ CT
Solar/Wind Harmer
0.231
316431W1029_GEN1
Solar/Wind Harmer
0.001
316433W1029_GEN2
Solar/Wind Harmer
0.001
970933AG2-581 GEN
Solar/Wind Harmer
18.033
315742AE1-103 GEN
Solar/Wind Harmer
0.003
3146376EDENTON
Solar/Wind Harmer
0.99
3146376EDENTON
Solar/Wind Harmer
0.99
957411AF2-035 GEN
Solar/Wind Harmer
9.498
3146173TUNIS
Solar/Wind Harmer
0.21
3146173TUNIS
Solar/Wind Harmer
0.21
958261AF2-120 GEN
Solar/Wind Harmer
6.863
316181AB2-040 GEN
Solar/Wind Harmer
0.299
316274AC1-208 GEN
Solar/Wind Harmer
1.016
958211AF2-115 GEN
Solar/Wind Harmer
2.257
3147133PAMPLIN
Solar/Wind Harmer
0.188
3147133PAMPLIN
Solar/Wind Harmer
0.15
3146843MT LREL
Solar/Wind Harmer
0.179
3146843MT LREL
Solar/Wind Harmer
0.179
316222AC1-221 GEN
Solar/Wind Harmer
0.648
3150801HOPHCF4
50/50
1.399
315839AE2-212 C
Solar/Wind Harmer
0.002
944601AF1-125 GEN
Solar/Wind Harmer
52.472
315778AD1-151 GEN
Solar/Wind Harmer
18.928
3151101ELIZAR3
Adder
21.938
3144216WINCHST
Adder
0.882
316258AE1-075 C
Solar/Wind Harmer
0.17
3143336POWHATN
Solar/Wind Harmer
3.394
316317KELFORD C
Solar/Wind Harmer
0.02
3145823KELFORD
Solar/Wind Harmer
0.204
3145796HORNRTN
Solar/Wind Harmer
0.807
3145796HORNRTN
Solar/Wind Harmer
0.202
3150351NORNECKC2
Adder
2.043
316210AC1-098 GEN
Solar/Wind Harmer
1.828
970909AG2-566 GEN
Solar/Wind Harmer
2.083
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
964241AG1-285 GEN
Solar/Wind Harmer
12.61
3144293JTRSVLE
Adder
0.599
971193AH1-056 GEN
Solar/Wind Harmer
11.443
942461AE2-259 GEN
Solar/Wind Harmer
-0.001
316248AF1-058 C
Solar/Wind Harmer
0.001
960061AF2-297 GEN
Solar/Wind Harmer
7.36
971683AH1-343 GEN
Solar/Wind Harmer
5.86
3151761LOISA E
Adder
21.054
972183AH1-676 GEN
Adder
164.313
3141316ARNOLDS
Adder
0.285
316435W1029_GEN3
Solar/Wind Harmer
0.001
3146516WINFALL
Solar/Wind Harmer
0.229
316313AB2-026
Solar/Wind Harmer
0.142
316203AE2-005 GEN
Solar/Wind Harmer
-0.001
316156AD2-030 GEN
Solar/Wind Harmer
0.165
315614AA2-178 GEN
Solar/Wind Harmer
1.249
971157AH1-035 GEN
Solar/Wind Harmer
2.577
3145893MURPHYS
Solar/Wind Harmer
0.354
3145893MURPHYS
Solar/Wind Harmer
0.212
957521AF2-046 GEN
Solar/Wind Harmer
15.715
316463AE2-346 GEN
Solar/Wind Harmer
0.179
316140AB2-099
Solar/Wind Harmer
0.075
3146263WOODLND
Solar/Wind Harmer
0.207
3145963POPLR C
Solar/Wind Harmer
0.204
316327AA2-057 GEN
Solar/Wind Harmer
0.287
961601AG1-000A GEN
Solar/Wind Harmer
13.049
3145543BTLEBRO
Solar/Wind Harmer
0.183
3145543BTLEBRO
Solar/Wind Harmer
0.183
3146776BUCKING
Solar/Wind Harmer
0.064
970737AG2-469 GEN
Solar/Wind Harmer
7.314
970221AG2-151 GEN
Solar/Wind Harmer
8.48
3132273ORANGE
Solar/Wind Harmer
0.031
316170AC1-121 GEN2
Solar/Wind Harmer
0.13
970531AG2-338 GEN
50/50
8.46
3150781HOPHCF2
50/50
0.962
3150761HOPPOLC
50/50
0.61
971223AH1-071 GEN
Solar/Wind Harmer
2.784
316240AF1-291 C
Solar/Wind Harmer
0.002
3150671DARBY 1
Adder
16.973
3142296MT RD221
Adder
0.753
316036AC1-147 C
Solar/Wind Harmer
0.044
3150991CHESPKB
Adder
2.474
3150991CHESPKB
Adder
2.414
3142956BIRDNECK
Solar/Wind Harmer
0
316018AA1-139 ULT2
Solar/Wind Harmer
0.006
972187AH1-678 GEN
Adder
6.523
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
3146516WINFALL
Solar/Wind Harmer
0.229
966871AG1-558 GEN
Solar/Wind Harmer
0.263
970317AG2-208 GEN
Solar/Wind Harmer
8.8
316065AD1-022 GEN
Solar/Wind Harmer
9.8
3145893MURPHYS
Solar/Wind Harmer
1.417
3145893MURPHYS
Solar/Wind Harmer
0.381
316426AA2-053 GEN
Solar/Wind Harmer
0.69
966811AG1-552 GEN
Solar/Wind Harmer
2.207
971741AH1-377 GEN
Solar/Wind Harmer
19.637
939181AE1-148 GEN
Solar/Wind Harmer
9.137
3145453TOT5
Solar/Wind Harmer
0.259
961601AG1-000A GEN
Solar/Wind Harmer
3.262
964791AG1-342 GEN
Solar/Wind Harmer
3.448
3146776BUCKING
Solar/Wind Harmer
0.716
3146776BUCKING
Solar/Wind Harmer
0.058
3151721LOISA A
Adder
10.274
971489AH1-241 GEN
Solar/Wind Harmer
8.48
942751AE2-291 GEN
Solar/Wind Harmer
7.158
970533AG2-339 GEN
50/50
21.15
971213AH1-066 GEN
50/50
0.844
3150681DARBY 2
Adder
16.992
316033AB2-134 GEN
Solar/Wind Harmer
0.014
316236AE1-162_GEN
Solar/Wind Harmer
0.002
970657AG2-426 GEN
Solar/Wind Harmer
8.254
970657AG2-426 GEN
Solar/Wind Harmer
1.73
3145506HICKORY
Solar/Wind Harmer
0.94
3145506HICKORY
Solar/Wind Harmer
0.564
3145506HICKORY
Solar/Wind Harmer
0.141
316339AD2-160 GEN
Solar/Wind Harmer
0.38
3137176SLIGO L2192
Solar/Wind Harmer
0.93
3130086AYDLETT
Solar/Wind Harmer
0.933
3146626S HERTFORD
Solar/Wind Harmer
0.227
3146626S HERTFORD
Solar/Wind Harmer
0.227
315673AE1-157 GEN
Solar/Wind Harmer
15.213
972195AH1-682 GEN
Adder
3.79
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.205
3142666NORTHAMPTON
Solar/Wind Harmer
0.123
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.203
3145593CAROLNA
Solar/Wind Harmer
0.253
3150341NORNECKC1
Adder
2.11
3150341NORNECKC1
Adder
2.093
3145933PARMELE
Solar/Wind Harmer
0.392
3145933PARMELE
Solar/Wind Harmer
0.196
970301AG2-198 GEN
Solar/Wind Harmer
8.333
313527AB2-043 GEN
Solar/Wind Harmer
0.002
970323AG2-213 GEN
Solar/Wind Harmer
8.051
971775AH1-396 GEN
Solar/Wind Harmer
0.302
3145493TOT1
Solar/Wind Harmer
0.432
3151731LOISA B
Adder
10.327
966001AG1-469 GEN
Solar/Wind Harmer
0.09
3141196NOKESVL
Solar/Wind Helper
1.139
944641AF1-129 GEN
50/50
120.841
3150791HOPHCF3
50/50
0.962
3143526WINTERP
Solar/Wind Harmer
1.319
315697AD1-025 GEN
Solar/Wind Harmer
0.266
316316AC1-027 C
Solar/Wind Harmer
0.226
316185AD1-033 GEN
Solar/Wind Harmer
0.007
316075AC2-137 C
Solar/Wind Harmer
0.064
972185AH1-677 GEN
Adder
13.007
3144356SAPONY
Solar/Wind Harmer
1.937
3150391LDYSMT3
Adder
28.839
970099AG2-077 GEN
Solar/Wind Harmer
22.503
3145783HORNRTN
Solar/Wind Harmer
3.596
3145783HORNRTN
Solar/Wind Harmer
2.876
3145783HORNRTN
Solar/Wind Harmer
0.899
3145783HORNRTN
Solar/Wind Harmer
0.36
3145796HORNRTN
Solar/Wind Harmer
0.606
316077AC2-138 C
Solar/Wind Harmer
0.001
316468AD1-105 GEN
Solar/Wind Harmer
-0.063
316034AC1-036 C
Solar/Wind Harmer
0.014
963191AG1-168 GEN
Solar/Wind Harmer
0.752
3144293JTRSVLE
Adder
0.599
3144293JTRSVLE
Adder
0.504
3145603CNETO
Solar/Wind Harmer
0.173
316263AC1-034 GEN
Solar/Wind Harmer
6.97
962561AG1-105 GEN
Solar/Wind Harmer
8.691
315821AE2-092 GEN
Solar/Wind Harmer
0.008
971281AH1-106 GEN
Solar/Wind Harmer
3.521
3143316POE
Solar/Wind Harmer
0.947
316369SG1_INVT
Solar/Wind Harmer
0.009
319010AE1-072 C
Solar/Wind Harmer
1.177
3146486SUNBURY
Solar/Wind Harmer
0.231
3146486SUNBURY
Solar/Wind Harmer
0.231
972189AH1-679 GEN
Adder
3.867
316321Z2-027
Solar/Wind Harmer
0.043
3145176PASQUOTANK
Solar/Wind Harmer
0.143
3143873LANEXA
Solar/Wind Harmer
0.135
315611Z1-036_GEN2
Solar/Wind Harmer
0.002
315662AE1-191 GEN
Solar/Wind Harmer
0.007
3130156CHOWAN
Solar/Wind Harmer
0.223
3130156CHOWAN
Solar/Wind Harmer
0.223
3141873WAN 176
Solar/Wind Harmer
0.044
970581AG2-369 GEN
Solar/Wind Harmer
10.085
3138133OCRAN
Solar/Wind Harmer
0.065
315816AE2-034 GEN
Solar/Wind Harmer
0.937
972213AH1-691 GEN
Adder
4.692
3130546PLYMOUTH
Solar/Wind Harmer
0.215
315733AD1-074 GEN2
Solar/Wind Harmer
1.23
970601AG2-382 GEN
Solar/Wind Harmer
7.919
316087AB2-174 GEN
Solar/Wind Harmer
0.006
3146033SCOT NK
Solar/Wind Harmer
0.8
970181AG2-120 GEN
Solar/Wind Harmer
2.391
972205AH1-687 GEN
Adder
7.256
944491AF1-114 GEN
Solar/Wind Harmer
0.001
3147346CASHSCORNER
Solar/Wind Harmer
0.35
316233AE1-074 FULL
Solar/Wind Harmer
0.203
971283AH1-107 GEN
Solar/Wind Harmer
3.521
944011AF1-069 GEN
Solar/Wind Harmer
14.319
316132AB2-190 GEN1
Solar/Wind Harmer
1.271
972265AH1-717 GEN
Adder
18.304
3151191GRAVEL3
Adder
16.941
316164AC1-076 GEN
Solar/Wind Harmer
0.329
3146406KITTY HAWK
Solar/Wind Harmer
0.029
316305AF2-043 C
Solar/Wind Harmer
0.002
971967AH1-528 GEN
Solar/Wind Harmer
36.95
971167AH1-042 GEN
Solar/Wind Harmer
20.377
3138283WHITEMARSH
Solar/Wind Harmer
0.053
970189AG2-124 GEN
Solar/Wind Harmer
6.628
315666AE1-190 GEN
Solar/Wind Harmer
0.002
970085AG2-068 GEN
Solar/Wind Harmer
11.727
3150411LDYSMT5
Adder
28.983
972215AH1-692 GEN
Adder
4.692
315732AD1-074 GEN1
Solar/Wind Harmer
1.23
315735AD1-075 GEN1
Solar/Wind Harmer
0.616
965291AG1-394 GEN
Solar/Wind Harmer
0.949
962981AG1-147 GEN
Solar/Wind Harmer
7.952
3145893MURPHYS
Solar/Wind Harmer
0.572
3145893MURPHYS
Solar/Wind Harmer
0.212
3145513AHOSKIE
Solar/Wind Harmer
0.437
3145513AHOSKIE
Solar/Wind Harmer
0.209
315607AA1-063A GEN
Solar/Wind Harmer
0.424
315652AC1-086 GEN
Solar/Wind Harmer
22.553
3137643SOCKMAN
Solar/Wind Harmer
0.818
3141813NORNECK
Solar/Wind Harmer
0.201
316005AA1-067
Solar/Wind Harmer
0.206
971443AH1-215 GEN
Solar/Wind Harmer
3.171
3144303KENBRDG
Solar/Wind Harmer
0.151
946301AF1-294 GEN
Solar/Wind Harmer
3.712
315657AE1-056 GEN
Solar/Wind Harmer
6.482
316223AC1-118
Solar/Wind Harmer
0.13
316118AC1-105 GEN
Solar/Wind Harmer
0.454
972193AH1-681 GEN
Adder
3.331
270494AE1-108_GEN
Solar/Wind Harmer
1.679
3138216PACIFIC
Solar/Wind Helper
0.039
971285AH1-108 GEN
50/50
1.959
941031AE2-094 GEN
Solar/Wind Harmer
43.824
3151081ELIZAR1
Adder
21.661
3151091ELIZAR2
Adder
21.285
3152611GOSPORTB
Adder
3.008
3152621GOSPORTC
Adder
2.552
3152601GOSPORTA
Adder
2.355
971445AH1-216 GEN
Solar/Wind Harmer
16.611
316312AB1-027
Solar/Wind Harmer
0.42
957871AF2-081 GEN
Solar/Wind Harmer
11.66
970673AG2-436 GEN
Solar/Wind Harmer
49.886
970673AG2-436 GEN
Solar/Wind Harmer
33.257
315833AF1-017_GEN
Solar/Wind Harmer
0.001
316315AB2-025 C
Solar/Wind Harmer
0.187
316314AB2-024 C
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.219
970327AG2-215 GEN
Solar/Wind Harmer
6.922
3145796HORNRTN
Solar/Wind Harmer
0.646
3145796HORNRTN
Solar/Wind Harmer
0.081
970831AG2-522 GEN
Solar/Wind Harmer
8.358
3145746EVERETS
Solar/Wind Harmer
0.764
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
3145746EVERETS
Solar/Wind Harmer
0.192
957861AF2-080 GEN
Solar/Wind Harmer
8.156
316239AB2-077_GEN
Solar/Wind Harmer
0.002
316238AB2-078_GEN
Solar/Wind Harmer
0.002
970683AG2-441 GEN
Solar/Wind Harmer
12.561
970681AG2-440 GEN
Solar/Wind Harmer
10.049
3145573BETHELC
Solar/Wind Harmer
0.186
3145573BETHELC
Solar/Wind Harmer
0.186
971447AH1-217 GEN
Solar/Wind Harmer
4.692
970865AG2-541 GEN
Solar/Wind Harmer
5.299
316123AC1-075 GEN
Solar/Wind Harmer
0.191
316411AF1-147_GEN1
Solar/Wind Helper
0.804
316415AF1-147_GEN2
Solar/Wind Helper
0.804
316303AF2-085
50/50
4.641
970603AG2-384 GEN
50/50
5.097
3151201GRAVEL4
Adder
17.158
3151211GRAVEL5
Adder
16.941
316349AD2-085 GEN
Solar/Wind Harmer
0.16
316311AC2-079 GEN
Solar/Wind Harmer
6.708
315976AC1-164 GENA
Solar/Wind Harmer
24.098
316169AC1-164_GENC
Solar/Wind Harmer
20.818
315975AC1-164 GENB
Solar/Wind Harmer
0.713
315835AF2-110_GEN
Solar/Wind Harmer
1.594
313526AB2-022
Solar/Wind Harmer
0.125
315814AE2-033 C
Solar/Wind Harmer
18.254
3146396TANGLEW
Solar/Wind Harmer
0.635
3142433PROV 92
Adder
0.445
3142433PROV 92
Adder
0.445
316059AD1-063 C
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.13
3141783LANCAST
Solar/Wind Harmer
0.087
3150381LDYSMT2
Adder
27.738
3146206CASHIE
Solar/Wind Harmer
0.212
3146043SEABORD
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.416
3145683EARLEYS
Solar/Wind Harmer
0.208
3145683EARLEYS
Solar/Wind Harmer
0.208
961791AG1-021 GEN
Solar/Wind Harmer
1.806
316420AA1-050 GEN
Solar/Wind Harmer
0.006
316319Z2-044 C
Solar/Wind Harmer
0
970285AG2-188 GEN
Solar/Wind Harmer
14.319
971845AH1-439 GEN
Solar/Wind Harmer
8.149
3147173SINAI
Solar/Wind Harmer
0.172
3147243WELCO
Solar/Wind Harmer
0.108
970165AG2-112 GEN
Solar/Wind Harmer
1.134
970163AG2-111 GEN
Solar/Wind Harmer
1.081
3138266HYDRAULIC
Solar/Wind Harmer
0.005
3138266HYDRAULIC
Solar/Wind Harmer
0.003
CPLELTFEXP_CPLE->PJM
CLTF
11.88
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.966
NYPJM->LTFIMP_NY
CLTF
3.369
LGEELTFEXP_LGEE->PJM
CLTF
1.264
WECLTFEXP_WEC->PJM
CLTF
0.603
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.76
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.813
MECLTFEXP_MEC->PJM
CLTF
3.485
SIGELTFEXP_SIGE->PJM
CLTF
0.106
LAGNLTFEXP_LAGN->PJM
CLTF
8.056
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.878
TVALTFEXP_TVA->PJM
CLTF
4.082

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H1T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H1T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.28 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6078.79
MW Contribution:5.18
Bus #Bus NameTypeMW Contribution
971507AH1-251 GEN
50/50
16.627
3152331SURRY 2
50/50
9.986
316192AB2-158 GEN
Solar/Wind Harmer
3.585
316294AC1-161 GEN
Solar/Wind Harmer
8.821
316375AC2-012 GEN
Solar/Wind Harmer
9.327
3145336SMITFLD
Solar/Wind Harmer
-0.107
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.027
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
971777AH1-397 GEN
Solar/Wind Harmer
3.003
3141766HARMONY
Solar/Wind Harmer
-0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.262
3145663CRESWEL
Solar/Wind Harmer
-0.069
972197AH1-683 GEN
Adder
4.589
316336AC2-165 C
Solar/Wind Harmer
4.275
316023GEN1_S
Solar/Wind Harmer
1.648
3152251N ANNA1
50/50
19.951
970119AG2-088 GEN
50/50
35.342
3150851SPRUNCC
50/50
1.216
316045AC1-158 PL2
Solar/Wind Harmer
22.057
970659AG2-427 GEN
Solar/Wind Harmer
14.317
316093AE2-104_GEN
Solar/Wind Harmer
7.706
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.355
970919AG2-571 GEN
Solar/Wind Harmer
7.971
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
962861AG1-135 GEN
Solar/Wind Harmer
8.922
315693AD1-088 GEN
Solar/Wind Harmer
11.811
3146263WOODLND
Solar/Wind Harmer
-0.024
962491AG1-098 GEN
Solar/Wind Harmer
15.753
316011AB1-132 GEN
Solar/Wind Harmer
4.898
3145963POPLR C
Solar/Wind Harmer
-0.023
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316174AB2-169 GEN
Solar/Wind Harmer
3.568
316164AC1-076 GEN
Solar/Wind Harmer
3.019
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971283AH1-107 GEN
Solar/Wind Harmer
4.708
944011AF1-069 GEN
Solar/Wind Harmer
15.945
316132AB2-190 GEN1
Solar/Wind Harmer
2.735
972265AH1-717 GEN
Adder
18.594
3151191GRAVEL3
Adder
17.21
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.803
971967AH1-528 GEN
Solar/Wind Harmer
49.529
971167AH1-042 GEN
Solar/Wind Harmer
25.215
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315666AE1-190 GEN
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
0.759
970085AG2-068 GEN
Solar/Wind Harmer
15.677
3150411LDYSMT5
Adder
29.481
972215AH1-692 GEN
Adder
4.773
315732AD1-074 GEN1
Solar/Wind Harmer
4.942
315735AD1-075 GEN1
Solar/Wind Harmer
2.472
965291AG1-394 GEN
Solar/Wind Harmer
2.164
962981AG1-147 GEN
Solar/Wind Harmer
10.637
3145893MURPHYS
Solar/Wind Harmer
-0.065
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.208
3145513AHOSKIE
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.392
315652AC1-086 GEN
Solar/Wind Harmer
26.336
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3141813NORNECK
Solar/Wind Harmer
-0.023
972193AH1-681 GEN
Adder
3.397
3138216PACIFIC
Solar/Wind Helper
0.04
3143096IRON208
50/50
1.079
3150771HOPHCF1
50/50
0.977
3147666LOUISA
Solar/Wind Harmer
-0.123
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
6.167
316458AB2-190 GEN2
Solar/Wind Harmer
2.735
971069AG2-661 GEN
Solar/Wind Harmer
4.273
3150981CHESPKA
Adder
2.995
971647AH1-324 GEN
Solar/Wind Harmer
13.48
961611AG1-000B GEN
Solar/Wind Harmer
13.293
316381AD1-082 GEN
Solar/Wind Harmer
2.469
3151171GRAVELC
Adder
2.547
970661AG2-428 GEN
Solar/Wind Harmer
28.527
316388AE2-253 GEN
Solar/Wind Harmer
1.804
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316159AE1-175 C
Solar/Wind Harmer
0.715
316246AF1-032 C
Solar/Wind Harmer
0.539
3141843SHACKLE
Adder
1.161
3130156CHOWAN
Solar/Wind Harmer
-0.025
970087AG2-069 GEN
Solar/Wind Harmer
23.516
3138133OCRAN
Solar/Wind Harmer
-0.015
971163AH1-040 GEN
Solar/Wind Harmer
23.353
957481AF2-042 GEN
Solar/Wind Harmer
75.252
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3151751LOISA D
Adder
10.898
3152261N ANNA2
50/50
19.95
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.079
3143096IRON208
50/50
1.057
316044AC1-158 PL1
Solar/Wind Harmer
6.895
316450AC1-158 RIC
Solar/Wind Harmer
1.839
3147666LOUISA
Solar/Wind Harmer
-0.07
965281AG1-393 GEN
Solar/Wind Harmer
3.401
970129AG2-093 GEN
Solar/Wind Harmer
15.225
3144873MCLAUGH
Solar/Wind Harmer
-0.001
961611AG1-000B GEN
Solar/Wind Harmer
5.672
3151171GRAVELC
Adder
3.35
970661AG2-428 GEN
Solar/Wind Harmer
5.055
316382AG1-145 C
Solar/Wind Harmer
0.803
3146626S HERTFORD
Solar/Wind Harmer
-0.026
316405AF2-144 C
Solar/Wind Harmer
0.658
3141843SHACKLE
Adder
1.161
316280AD1-041 GEN
Solar/Wind Harmer
1.918
3141873WAN 176
Solar/Wind Harmer
3.01
970917AG2-570 GEN
Solar/Wind Harmer
62.97
3150401LDYSMT4
Adder
29.389
3156081AA2-088 GEN
Solar/Wind Harmer
7.946
315737AD1-076 GEN
Solar/Wind Harmer
4.644
962971AG1-146 GEN
Solar/Wind Harmer
4.559
961681AG1-008 GEN
Solar/Wind Harmer
18.984
962331AG1-082 GEN
Solar/Wind Harmer
2.979
316404AE1-155 C
Solar/Wind Harmer
4.57
313506AB2-031 GEN
Solar/Wind Harmer
1.893
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
970533AG2-339 GEN
50/50
21.472
971213AH1-066 GEN
50/50
0.857
3150681DARBY 2
Adder
17.27
316033AB2-134 GEN
Solar/Wind Harmer
8.703
316236AE1-162_GEN
Solar/Wind Harmer
0.812
970657AG2-426 GEN
Solar/Wind Harmer
8.405
970657AG2-426 GEN
Solar/Wind Harmer
1.758
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.804
3137176SLIGO L2192
Solar/Wind Harmer
-0.106
3130086AYDLETT
Solar/Wind Harmer
-0.106
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
315673AE1-157 GEN
Solar/Wind Harmer
18.853
972195AH1-682 GEN
Adder
3.855
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.193
3150341NORNECKC1
Adder
2.144
3150341NORNECKC1
Adder
2.127
3151731LOISA B
Adder
10.898
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.182
939411AE1-173 GEN
Solar/Wind Harmer
138.344
315671AE2-027_GEN
Solar/Wind Harmer
20.395
3150801HOPHCF4
50/50
1.421
315839AE2-212 C
Solar/Wind Harmer
0.822
944601AF1-125 GEN
Solar/Wind Harmer
120.955
315778AD1-151 GEN
Solar/Wind Harmer
23.395
3151101ELIZAR3
Adder
22.283
3144216WINCHST
Adder
0.896
316258AE1-075 C
Solar/Wind Harmer
0.623
3143336POWHATN
Solar/Wind Harmer
2.59
966621AG1-532 GEN
Solar/Wind Harmer
0.484
316317KELFORD C
Solar/Wind Harmer
1.098
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.075
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.218
972183AH1-676 GEN
Adder
173.787
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.164
944641AF1-129 GEN
50/50
122.768
3150791HOPHCF3
50/50
0.977
3143526WINTERP
Solar/Wind Harmer
-0.15
315697AD1-025 GEN
Solar/Wind Harmer
5.458
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.837
316075AC2-137 C
Solar/Wind Harmer
0.72
972185AH1-677 GEN
Adder
13.205
3144356SAPONY
Solar/Wind Harmer
0.922
316441AF1-014 GEN
Solar/Wind Harmer
1.721
3150391LDYSMT3
Adder
29.334
970099AG2-077 GEN
Solar/Wind Harmer
30.101
3145783HORNRTN
Solar/Wind Harmer
2.74
3145783HORNRTN
Solar/Wind Harmer
2.192
3145783HORNRTN
Solar/Wind Harmer
0.685
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3144293JTRSVLE
Adder
0.609
3144293JTRSVLE
Adder
0.513
971285AH1-108 GEN
50/50
1.991
941031AE2-094 GEN
Solar/Wind Harmer
50.888
3151081ELIZAR1
Adder
22.001
3151091ELIZAR2
Adder
21.619
3152611GOSPORTB
Adder
3.055
3152621GOSPORTC
Adder
2.593
3152601GOSPORTA
Adder
2.392
971445AH1-216 GEN
Solar/Wind Harmer
16.663
316312AB1-027
Solar/Wind Harmer
0.904
957871AF2-081 GEN
Solar/Wind Harmer
13.366
970673AG2-436 GEN
Solar/Wind Harmer
56.037
970673AG2-436 GEN
Solar/Wind Harmer
28.373
315833AF1-017_GEN
Solar/Wind Harmer
5.064
316315AB2-025 C
Solar/Wind Harmer
0.713
957831AF2-077 GEN
Solar/Wind Harmer
0.783
316314AB2-024 C
Solar/Wind Harmer
2.187
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
316411AF1-147_GEN1
Solar/Wind Helper
0.82
316415AF1-147_GEN2
Solar/Wind Helper
0.82
971133AH1-012 GEN
50/50
5.665
3142366NRTHEST
50/50
0.838
3150691DARBY 3
50/50
18.39
316447AC1-158 HLD
Solar/Wind Harmer
15.163
3150701DARBY 4
Adder
17.29
3142946ENON
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
2.163
3146456SLIGO L269
Solar/Wind Harmer
3.151
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.74
316433W1029_GEN2
Solar/Wind Harmer
4.74
970933AG2-581 GEN
Solar/Wind Harmer
24.111
315742AE1-103 GEN
Solar/Wind Harmer
2.675
957411AF2-035 GEN
Solar/Wind Harmer
11.447
3146376EDENTON
Solar/Wind Harmer
0.755
3146376EDENTON
Solar/Wind Harmer
0.755
316487AF1-042 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.18
316181AB2-040 GEN
Solar/Wind Harmer
3.285
316303AF2-085
50/50
4.712
970603AG2-384 GEN
50/50
5.178
3151201GRAVEL4
Adder
17.43
3151211GRAVEL5
Adder
17.21
316349AD2-085 GEN
Solar/Wind Harmer
2.371
316311AC2-079 GEN
Solar/Wind Harmer
13.447
315976AC1-164 GENA
Solar/Wind Harmer
28.04
316169AC1-164_GENC
Solar/Wind Harmer
24.224
971531AH1-263 GEN
50/50
60.398
971281AH1-106 GEN
Solar/Wind Harmer
4.708
3143316POE
Solar/Wind Harmer
-0.107
316369SG1_INVT
Solar/Wind Harmer
4.821
319010AE1-072 C
Solar/Wind Harmer
5.393
972189AH1-679 GEN
Adder
3.932
3146486SUNBURY
Solar/Wind Harmer
-0.026
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.71
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.355
315662AE1-191 GEN
Solar/Wind Harmer
3.069
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141873WAN 176
Solar/Wind Harmer
-0.005
970581AG2-369 GEN
Solar/Wind Harmer
13.482
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.016
972213AH1-691 GEN
Adder
4.773
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315733AD1-074 GEN2
Solar/Wind Harmer
4.942
970601AG2-382 GEN
Solar/Wind Harmer
10.591
946281AF1-292 GEN
Solar/Wind Harmer
0.534
316087AB2-174 GEN
Solar/Wind Harmer
3.373
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.416
970531AG2-338 GEN
50/50
8.589
3150781HOPHCF2
50/50
0.977
3150761HOPPOLC
50/50
0.62
971223AH1-071 GEN
Solar/Wind Harmer
3.723
316240AF1-291 C
Solar/Wind Harmer
0.822
3150671DARBY 1
Adder
17.25
3142296MT RD221
Adder
0.765
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.513
3150991CHESPKB
Adder
2.452
3142956BIRDNECK
Solar/Wind Harmer
1.444
316018AA1-139 ULT2
Solar/Wind Harmer
2.29
972187AH1-678 GEN
Adder
6.623
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.781
966871AG1-558 GEN
Solar/Wind Harmer
0.267
970317AG2-208 GEN
Solar/Wind Harmer
11.129
316065AD1-022 GEN
Solar/Wind Harmer
12.145
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
316426AA2-053 GEN
Solar/Wind Harmer
2.355
966811AG1-552 GEN
Solar/Wind Harmer
2.613
3151721LOISA A
Adder
10.842
971741AH1-377 GEN
Solar/Wind Harmer
1.355
971211AH1-065 GEN
50/50
1.714
3151161SURRY 1
50/50
9.199
315773AC2-141 GEN
Solar/Wind Harmer
11.408
944581AF1-123 GEN
Solar/Wind Harmer
122.873
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.537
970293AG2-193 GEN
Solar/Wind Harmer
3.361
3150921YORKTN3
Adder
5.966
316320Y1-086
Solar/Wind Harmer
1.548
316435W1029_GEN3
Solar/Wind Harmer
4.74
3146516WINFALL
Solar/Wind Harmer
-0.026
316313AB2-026
Solar/Wind Harmer
0.692
316203AE2-005 GEN
Solar/Wind Harmer
10.766
316156AD2-030 GEN
Solar/Wind Harmer
0.677
315614AA2-178 GEN
Solar/Wind Harmer
2.688
971157AH1-035 GEN
Solar/Wind Harmer
3.064
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.984
316484AD2-074 GEN
Solar/Wind Harmer
6.061
316463AE2-346 GEN
Solar/Wind Harmer
0.386
316140AB2-099
Solar/Wind Harmer
0.161
3146263WOODLND
Solar/Wind Harmer
-0.024
3145963POPLR C
Solar/Wind Harmer
-0.023
315975AC1-164 GENB
Solar/Wind Harmer
0.83
315835AF2-110_GEN
Solar/Wind Harmer
3.313
313526AB2-022
Solar/Wind Harmer
0.713
315814AE2-033 C
Solar/Wind Harmer
24.517
3146396TANGLEW
Solar/Wind Harmer
0.484
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
316059AD1-063 C
Solar/Wind Harmer
0.576
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150381LDYSMT2
Adder
28.214
3146206CASHIE
Solar/Wind Harmer
-0.024
316318V4-068
Solar/Wind Harmer
0.602
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970133AG2-095 GEN
Solar/Wind Harmer
3.047
315813AE1-149 C
Solar/Wind Harmer
16.929
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.37
3151221GRAVEL6
Adder
17.41
3142946ENON
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
2.704
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.252
3142433PROV 92
Adder
0.452
3142433PROV 92
Adder
0.452
316473AC1-191 GEN
Solar/Wind Harmer
2.794
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
2.27
966881AG1-559 GEN
Solar/Wind Harmer
0.765
3146376EDENTON
Solar/Wind Harmer
-0.025
3150371LDYSMT1
Adder
28.398
316365GEN2_N
Solar/Wind Harmer
1.648
3146206CASHIE
Solar/Wind Harmer
-0.024
970009AG2-005 GEN
Solar/Wind Harmer
3.009
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.218
316478AD1-087 GEN
Solar/Wind Harmer
2.006
316486AD2-202 GEN
Solar/Wind Harmer
0.588
3147043LAWRENC
Solar/Wind Harmer
-0.014
972255AH1-712 GEN
Adder
76.037
944591AF1-124 GEN
Solar/Wind Harmer
123.316
944631AF1-128 GEN
Adder
114.478
316072AD1-144
Solar/Wind Harmer
0.54
971317AH1-138 GEN
Solar/Wind Harmer
3.316
3143336POWHATN
Solar/Wind Harmer
3.047
972219AH1-694 GEN
Adder
3.304
971547AH1-271 GEN
Solar/Wind Harmer
6.052
960081AF2-299 GEN
Solar/Wind Harmer
2.682
962571AG1-106 GEN
Solar/Wind Harmer
3.365
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3145823KELFORD
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.041
3144293JTRSVLE
Adder
0.609
972277AH1-723 GEN
Adder
88.606
3146206CASHIE
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.171
3146173TUNIS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
17.538
3147043LAWRENC
Adder
1.866
CPLELTFEXP_CPLE->PJM
CLTF
12.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.739
NYPJM->LTFIMP_NY
CLTF
3.433
LGEELTFEXP_LGEE->PJM
CLTF
1.291
WECLTFEXP_WEC->PJM
CLTF
0.616
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.068
MECLTFEXP_MEC->PJM
CLTF
3.555
SIGELTFEXP_SIGE->PJM
CLTF
0.108
LAGNLTFEXP_LAGN->PJM
CLTF
8.202
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.311
TVALTFEXP_TVA->PJM
CLTF
4.157

Details for 8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line l/o DVP_P4-2: H3T552_SRT-S


Base Case Flowgate

Area:DVP
Facility Description:
8SPOTSYL-8MORRSVL 500.0 kV Ckt 1 line
Contingency Name:
DVP_P4-2: H3T552_SRT-S
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.01 %
Rating:3940.0 MVA
Rating Type:C
MVA to Mitigate:6067.89
MW Contribution:5.17
Bus #Bus NameTypeMW Contribution
3152251N ANNA1
50/50
19.938
970119AG2-088 GEN
50/50
35.315
316164AC1-076 GEN
Solar/Wind Harmer
3.016
316233AE1-074 FULL
Solar/Wind Harmer
0.779
971283AH1-107 GEN
Solar/Wind Harmer
4.705
944011AF1-069 GEN
Solar/Wind Harmer
15.933
316132AB2-190 GEN1
Solar/Wind Harmer
2.733
972265AH1-717 GEN
Adder
18.58
3151191GRAVEL3
Adder
17.197
3146406KITTY HAWK
Solar/Wind Harmer
0.022
316305AF2-043 C
Solar/Wind Harmer
0.802
971967AH1-528 GEN
Solar/Wind Harmer
49.492
971167AH1-042 GEN
Solar/Wind Harmer
25.196
3138283WHITEMARSH
Solar/Wind Harmer
0.04
315666AE1-190 GEN
Solar/Wind Harmer
0.767
957601AF2-054 GEN
Solar/Wind Harmer
0.758
970085AG2-068 GEN
Solar/Wind Harmer
15.665
3150411LDYSMT5
Adder
29.459
972215AH1-692 GEN
Adder
4.769
315732AD1-074 GEN1
Solar/Wind Harmer
4.938
315735AD1-075 GEN1
Solar/Wind Harmer
2.47
965291AG1-394 GEN
Solar/Wind Harmer
2.162
962981AG1-147 GEN
Solar/Wind Harmer
10.629
3145893MURPHYS
Solar/Wind Harmer
-0.065
3143096IRON208
50/50
1.078
3150771HOPHCF1
50/50
0.977
3147666LOUISA
Solar/Wind Harmer
-0.123
3143226MDLTHAN
Solar/Wind Harmer
-0.03
3142543TWELFTH
Solar/Wind Harmer
-0.003
970129AG2-093 GEN
Solar/Wind Harmer
6.163
316458AB2-190 GEN2
Solar/Wind Harmer
2.733
971069AG2-661 GEN
Solar/Wind Harmer
4.27
3150981CHESPKA
Adder
2.993
971647AH1-324 GEN
Solar/Wind Harmer
13.47
961611AG1-000B GEN
Solar/Wind Harmer
13.283
316381AD1-082 GEN
Solar/Wind Harmer
2.467
3151171GRAVELC
Adder
2.545
970661AG2-428 GEN
Solar/Wind Harmer
28.505
316388AE2-253 GEN
Solar/Wind Harmer
1.803
3138126ROCKLANDING
Solar/Wind Harmer
0.082
316159AE1-175 C
Solar/Wind Harmer
0.714
316246AF1-032 C
Solar/Wind Harmer
0.538
3141843SHACKLE
Adder
1.16
3130156CHOWAN
Solar/Wind Harmer
-0.025
970087AG2-069 GEN
Solar/Wind Harmer
23.498
3138133OCRAN
Solar/Wind Harmer
-0.015
971163AH1-040 GEN
Solar/Wind Harmer
23.335
957481AF2-042 GEN
Solar/Wind Harmer
75.195
316190AA2-174 GEN
Solar/Wind Harmer
0.286
3151751LOISA D
Adder
10.888
3152261N ANNA2
50/50
19.936
3150861SPRUNCD
50/50
1.216
3143096IRON208
50/50
1.078
3143096IRON208
50/50
1.057
316044AC1-158 PL1
Solar/Wind Harmer
6.891
316450AC1-158 RIC
Solar/Wind Harmer
1.837
3147666LOUISA
Solar/Wind Harmer
-0.07
965281AG1-393 GEN
Solar/Wind Harmer
3.399
970129AG2-093 GEN
Solar/Wind Harmer
15.214
3144873MCLAUGH
Solar/Wind Harmer
-0.001
961611AG1-000B GEN
Solar/Wind Harmer
5.668
3151171GRAVELC
Adder
3.347
970661AG2-428 GEN
Solar/Wind Harmer
5.052
316382AG1-145 C
Solar/Wind Harmer
0.802
3146626S HERTFORD
Solar/Wind Harmer
-0.026
316405AF2-144 C
Solar/Wind Harmer
0.657
3141843SHACKLE
Adder
1.16
316280AD1-041 GEN
Solar/Wind Harmer
1.917
3141873WAN 176
Solar/Wind Harmer
3.008
970917AG2-570 GEN
Solar/Wind Harmer
62.922
3150401LDYSMT4
Adder
29.367
3156081AA2-088 GEN
Solar/Wind Harmer
7.94
315737AD1-076 GEN
Solar/Wind Harmer
4.641
962971AG1-146 GEN
Solar/Wind Harmer
4.555
961681AG1-008 GEN
Solar/Wind Harmer
18.97
962331AG1-082 GEN
Solar/Wind Harmer
2.977
316404AE1-155 C
Solar/Wind Harmer
4.567
313506AB2-031 GEN
Solar/Wind Harmer
1.892
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3150801HOPHCF4
50/50
1.42
315839AE2-212 C
Solar/Wind Harmer
0.822
944601AF1-125 GEN
Solar/Wind Harmer
120.864
315778AD1-151 GEN
Solar/Wind Harmer
23.378
3151101ELIZAR3
Adder
22.266
3144216WINCHST
Adder
0.896
316258AE1-075 C
Solar/Wind Harmer
0.623
3143336POWHATN
Solar/Wind Harmer
2.588
966621AG1-532 GEN
Solar/Wind Harmer
0.483
316317KELFORD C
Solar/Wind Harmer
1.097
3145823KELFORD
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.092
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.074
3144293JTRSVLE
Adder
0.609
3151761LOISA E
Adder
22.198
972183AH1-676 GEN
Adder
173.63
3141316ARNOLDS
Adder
0.289
3141196NOKESVL
Solar/Wind Helper
1.139
944641AF1-129 GEN
50/50
122.675
3150791HOPHCF3
50/50
0.977
3143526WINTERP
Solar/Wind Harmer
-0.15
315697AD1-025 GEN
Solar/Wind Harmer
5.454
316316AC1-027 C
Solar/Wind Harmer
0.826
316185AD1-033 GEN
Solar/Wind Harmer
2.835
316075AC2-137 C
Solar/Wind Harmer
0.72
972185AH1-677 GEN
Adder
13.195
3144356SAPONY
Solar/Wind Harmer
0.921
316441AF1-014 GEN
Solar/Wind Harmer
1.72
3150391LDYSMT3
Adder
29.312
970099AG2-077 GEN
Solar/Wind Harmer
30.078
3145783HORNRTN
Solar/Wind Harmer
2.737
3145783HORNRTN
Solar/Wind Harmer
2.19
3145783HORNRTN
Solar/Wind Harmer
0.684
3145783HORNRTN
Solar/Wind Harmer
0.274
3145796HORNRTN
Solar/Wind Harmer
-0.069
316077AC2-138 C
Solar/Wind Harmer
0.485
3144293JTRSVLE
Adder
0.609
971285AH1-108 GEN
50/50
1.989
941031AE2-094 GEN
Solar/Wind Harmer
50.85
3151081ELIZAR1
Adder
21.985
3151091ELIZAR2
Adder
21.603
3152611GOSPORTB
Adder
3.052
3152621GOSPORTC
Adder
2.591
3152601GOSPORTA
Adder
2.39
971445AH1-216 GEN
Solar/Wind Harmer
16.65
316312AB1-027
Solar/Wind Harmer
0.903
957871AF2-081 GEN
Solar/Wind Harmer
13.355
970673AG2-436 GEN
Solar/Wind Harmer
55.995
970673AG2-436 GEN
Solar/Wind Harmer
28.352
315833AF1-017_GEN
Solar/Wind Harmer
5.061
316315AB2-025 C
Solar/Wind Harmer
0.712
957831AF2-077 GEN
Solar/Wind Harmer
0.782
316314AB2-024 C
Solar/Wind Harmer
2.185
3141913WHIT STONE
Solar/Wind Harmer
-0.025
3145796HORNRTN
Solar/Wind Harmer
-0.073
3145796HORNRTN
Solar/Wind Harmer
-0.009
316411AF1-147_GEN1
Solar/Wind Helper
0.818
316415AF1-147_GEN2
Solar/Wind Helper
0.818
971133AH1-012 GEN
50/50
5.661
3142366NRTHEST
50/50
0.837
3150691DARBY 3
50/50
18.376
316447AC1-158 HLD
Solar/Wind Harmer
15.154
3150701DARBY 4
Adder
17.277
3142946ENON
Solar/Wind Harmer
-0.003
316017AA1-139 ULT1
Solar/Wind Harmer
2.161
3146456SLIGO L269
Solar/Wind Harmer
3.148
3146386ELIZ CT
Solar/Wind Harmer
-0.026
316431W1029_GEN1
Solar/Wind Harmer
4.736
316433W1029_GEN2
Solar/Wind Harmer
4.736
970933AG2-581 GEN
Solar/Wind Harmer
24.093
315742AE1-103 GEN
Solar/Wind Harmer
2.673
957411AF2-035 GEN
Solar/Wind Harmer
11.438
3146376EDENTON
Solar/Wind Harmer
0.754
3146376EDENTON
Solar/Wind Harmer
0.754
316487AF1-042 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
3146173TUNIS
Solar/Wind Harmer
-0.024
958261AF2-120 GEN
Solar/Wind Harmer
9.173
316181AB2-040 GEN
Solar/Wind Harmer
3.283
970533AG2-339 GEN
50/50
21.455
971213AH1-066 GEN
50/50
0.857
3150681DARBY 2
Adder
17.257
316033AB2-134 GEN
Solar/Wind Harmer
8.696
316236AE1-162_GEN
Solar/Wind Harmer
0.811
970657AG2-426 GEN
Solar/Wind Harmer
8.398
970657AG2-426 GEN
Solar/Wind Harmer
1.756
3145506HICKORY
Solar/Wind Harmer
-0.107
3145506HICKORY
Solar/Wind Harmer
-0.064
3145506HICKORY
Solar/Wind Harmer
-0.016
316339AD2-160 GEN
Solar/Wind Harmer
1.803
3137176SLIGO L2192
Solar/Wind Harmer
-0.105
3130086AYDLETT
Solar/Wind Harmer
-0.106
3146626S HERTFORD
Solar/Wind Harmer
-0.026
3146626S HERTFORD
Solar/Wind Harmer
-0.026
315673AE1-157 GEN
Solar/Wind Harmer
18.839
972195AH1-682 GEN
Adder
3.852
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.023
3142666NORTHAMPTON
Solar/Wind Harmer
-0.014
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
-0.023
3145593CAROLNA
Solar/Wind Harmer
0.193
3150341NORNECKC1
Adder
2.142
3150341NORNECKC1
Adder
2.125
3151731LOISA B
Adder
10.888
971531AH1-263 GEN
50/50
60.354
971281AH1-106 GEN
Solar/Wind Harmer
4.705
3143316POE
Solar/Wind Harmer
-0.107
316369SG1_INVT
Solar/Wind Harmer
4.818
319010AE1-072 C
Solar/Wind Harmer
5.389
972189AH1-679 GEN
Adder
3.929
3146486SUNBURY
Solar/Wind Harmer
-0.026
3145893MURPHYS
Solar/Wind Harmer
-0.024
3145513AHOSKIE
Solar/Wind Harmer
0.208
3145513AHOSKIE
Solar/Wind Harmer
-0.024
315607AA1-063A GEN
Solar/Wind Harmer
2.391
315652AC1-086 GEN
Solar/Wind Harmer
26.316
3137643SOCKMAN
Solar/Wind Harmer
-0.093
3141813NORNECK
Solar/Wind Harmer
-0.023
972193AH1-681 GEN
Adder
3.394
3138216PACIFIC
Solar/Wind Helper
0.04
970531AG2-338 GEN
50/50
8.582
3150781HOPHCF2
50/50
0.977
3150761HOPPOLC
50/50
0.619
971223AH1-071 GEN
Solar/Wind Harmer
3.72
316240AF1-291 C
Solar/Wind Harmer
0.821
3150671DARBY 1
Adder
17.237
3142296MT RD221
Adder
0.765
316036AC1-147 C
Solar/Wind Harmer
0.727
3150991CHESPKB
Adder
2.511
3150991CHESPKB
Adder
2.451
3142956BIRDNECK
Solar/Wind Harmer
1.443
316018AA1-139 ULT2
Solar/Wind Harmer
2.288
972187AH1-678 GEN
Adder
6.618
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
3146516WINFALL
Solar/Wind Harmer
-0.026
966871AG1-558 GEN
Solar/Wind Harmer
0.78
966871AG1-558 GEN
Solar/Wind Harmer
0.267
970317AG2-208 GEN
Solar/Wind Harmer
11.12
316065AD1-022 GEN
Solar/Wind Harmer
12.136
3145893MURPHYS
Solar/Wind Harmer
0.674
3145893MURPHYS
Solar/Wind Harmer
-0.043
316426AA2-053 GEN
Solar/Wind Harmer
2.354
966811AG1-552 GEN
Solar/Wind Harmer
2.611
3151721LOISA A
Adder
10.832
971741AH1-377 GEN
Solar/Wind Harmer
1.353
971211AH1-065 GEN
50/50
1.713
3151161SURRY 1
50/50
9.192
315773AC2-141 GEN
Solar/Wind Harmer
11.4
944581AF1-123 GEN
Solar/Wind Harmer
122.781
3144536CHRHLND
Solar/Wind Harmer
-0.004
970659AG2-427 GEN
Solar/Wind Harmer
2.535
970293AG2-193 GEN
Solar/Wind Harmer
3.359
3150921YORKTN3
Adder
5.961
316320Y1-086
Solar/Wind Harmer
1.547
316435W1029_GEN3
Solar/Wind Harmer
4.736
3146516WINFALL
Solar/Wind Harmer
-0.026
316313AB2-026
Solar/Wind Harmer
0.692
316203AE2-005 GEN
Solar/Wind Harmer
10.758
316156AD2-030 GEN
Solar/Wind Harmer
0.677
315614AA2-178 GEN
Solar/Wind Harmer
2.686
971157AH1-035 GEN
Solar/Wind Harmer
3.061
3145893MURPHYS
Solar/Wind Harmer
0.169
3145893MURPHYS
Solar/Wind Harmer
-0.024
957521AF2-046 GEN
Solar/Wind Harmer
18.97
316303AF2-085
50/50
4.709
970603AG2-384 GEN
50/50
5.174
3151201GRAVEL4
Adder
17.417
3151211GRAVEL5
Adder
17.197
316349AD2-085 GEN
Solar/Wind Harmer
2.37
316311AC2-079 GEN
Solar/Wind Harmer
13.437
315976AC1-164 GENA
Solar/Wind Harmer
28.019
316169AC1-164_GENC
Solar/Wind Harmer
24.206
315975AC1-164 GENB
Solar/Wind Harmer
0.829
315835AF2-110_GEN
Solar/Wind Harmer
3.311
313526AB2-022
Solar/Wind Harmer
0.712
315814AE2-033 C
Solar/Wind Harmer
24.499
3146396TANGLEW
Solar/Wind Harmer
0.484
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
316059AD1-063 C
Solar/Wind Harmer
0.576
3141783LANCAST
Solar/Wind Harmer
-0.015
3141783LANCAST
Solar/Wind Harmer
-0.01
3150381LDYSMT2
Adder
28.193
3146206CASHIE
Solar/Wind Harmer
-0.024
316318V4-068
Solar/Wind Harmer
0.602
961941AG1-037 GEN
Solar/Wind Harmer
0.179
3146043SEABORD
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.047
3145683EARLEYS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
970133AG2-095 GEN
Solar/Wind Harmer
3.045
315813AE1-149 C
Solar/Wind Harmer
16.916
3145336SMITFLD
Solar/Wind Harmer
-0.011
316083AB2-161 GEN
Solar/Wind Harmer
4.366
3151221GRAVEL6
Adder
17.397
3142946ENON
Solar/Wind Harmer
-0.009
3142416OLDCHRC
Solar/Wind Harmer
2.702
3146456SLIGO L269
Solar/Wind Harmer
-0.027
971153AH1-033 GEN
Solar/Wind Harmer
3.25
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
316473AC1-191 GEN
Solar/Wind Harmer
2.792
3145273HOLLAND
Solar/Wind Harmer
-0.019
3141766HARMONY
Solar/Wind Harmer
2.268
966881AG1-559 GEN
Solar/Wind Harmer
0.764
3146376EDENTON
Solar/Wind Harmer
-0.025
3150371LDYSMT1
Adder
28.377
316365GEN2_N
Solar/Wind Harmer
1.647
3146206CASHIE
Solar/Wind Harmer
-0.024
970009AG2-005 GEN
Solar/Wind Harmer
3.007
3146173TUNIS
Solar/Wind Harmer
-0.024
3156021HOLLOMANSOL
Solar/Wind Harmer
3.215
3147043LAWRENC
Solar/Wind Harmer
-0.014
316478AD1-087 GEN
Solar/Wind Harmer
2.005
316486AD2-202 GEN
Solar/Wind Harmer
0.587
972255AH1-712 GEN
Adder
75.968
316484AD2-074 GEN
Solar/Wind Harmer
6.056
316463AE2-346 GEN
Solar/Wind Harmer
0.385
316140AB2-099
Solar/Wind Harmer
0.161
3146263WOODLND
Solar/Wind Harmer
-0.023
3145963POPLR C
Solar/Wind Harmer
-0.023
3143526WINTERP
Solar/Wind Harmer
-0.15
940641AE2-051 GEN
Solar/Wind Harmer
26.162
939411AE1-173 GEN
Solar/Wind Harmer
138.24
315671AE2-027_GEN
Solar/Wind Harmer
20.38
944591AF1-124 GEN
Solar/Wind Harmer
123.223
944631AF1-128 GEN
Adder
114.392
316072AD1-144
Solar/Wind Harmer
0.539
971317AH1-138 GEN
Solar/Wind Harmer
3.313
3143336POWHATN
Solar/Wind Harmer
3.045
972219AH1-694 GEN
Adder
3.302
971547AH1-271 GEN
Solar/Wind Harmer
6.047
960081AF2-299 GEN
Solar/Wind Harmer
2.68
962571AG1-106 GEN
Solar/Wind Harmer
3.363
964211AG1-282 GEN
Solar/Wind Harmer
0.701
3145823KELFORD
Solar/Wind Harmer
-0.023
3145783HORNRTN
Solar/Wind Harmer
-0.023
3145796HORNRTN
Solar/Wind Harmer
-0.076
3145796HORNRTN
Solar/Wind Harmer
-0.023
3150351NORNECKC2
Adder
2.039
3144293JTRSVLE
Adder
0.609
972277AH1-723 GEN
Adder
88.526
3146486SUNBURY
Solar/Wind Harmer
-0.026
316321Z2-027
Solar/Wind Harmer
0.709
3145176PASQUOTANK
Solar/Wind Harmer
-0.016
3143873LANEXA
Solar/Wind Harmer
-0.015
315611Z1-036_GEN2
Solar/Wind Harmer
6.351
315662AE1-191 GEN
Solar/Wind Harmer
3.067
3130156CHOWAN
Solar/Wind Harmer
-0.025
3130156CHOWAN
Solar/Wind Harmer
-0.025
3141873WAN 176
Solar/Wind Harmer
-0.005
970581AG2-369 GEN
Solar/Wind Harmer
13.472
3138133OCRAN
Solar/Wind Harmer
-0.007
315816AE2-034 GEN
Solar/Wind Harmer
2.014
972213AH1-691 GEN
Adder
4.769
3130546PLYMOUTH
Solar/Wind Harmer
-0.024
315733AD1-074 GEN2
Solar/Wind Harmer
4.938
970601AG2-382 GEN
Solar/Wind Harmer
10.583
946281AF1-292 GEN
Solar/Wind Harmer
0.534
316087AB2-174 GEN
Solar/Wind Harmer
3.37
3146033SCOT NK
Solar/Wind Harmer
-0.091
972205AH1-687 GEN
Adder
7.409
971507AH1-251 GEN
50/50
16.616
3152331SURRY 2
50/50
9.978
316192AB2-158 GEN
Solar/Wind Harmer
3.583
316294AC1-161 GEN
Solar/Wind Harmer
8.814
316375AC2-012 GEN
Solar/Wind Harmer
9.32
3145336SMITFLD
Solar/Wind Harmer
-0.107
3142416OLDCHRC
Solar/Wind Harmer
-0.069
3142416OLDCHRC
Solar/Wind Harmer
-0.026
3146456SLIGO L269
Solar/Wind Harmer
-0.027
3142433PROV 92
Solar/Wind Harmer
-0.104
3142433PROV 92
Adder
0.451
3142433PROV 92
Adder
0.451
971777AH1-397 GEN
Solar/Wind Harmer
3
3141766HARMONY
Solar/Wind Harmer
-0.005
966881AG1-559 GEN
Solar/Wind Harmer
0.261
3145663CRESWEL
Solar/Wind Harmer
-0.069
972197AH1-683 GEN
Adder
4.586
316336AC2-165 C
Solar/Wind Harmer
4.272
316023GEN1_S
Solar/Wind Harmer
1.647
3146206CASHIE
Solar/Wind Harmer
-0.024
961951AG1-038 GEN
Solar/Wind Harmer
3.169
3146173TUNIS
Solar/Wind Harmer
-0.024
3145683EARLEYS
Solar/Wind Harmer
-0.024
971795AH1-408 GEN
Solar/Wind Harmer
17.524
3147043LAWRENC
Adder
1.864
3150851SPRUNCC
50/50
1.216
316045AC1-158 PL2
Solar/Wind Harmer
22.043
970659AG2-427 GEN
Solar/Wind Harmer
14.306
316093AE2-104_GEN
Solar/Wind Harmer
7.7
3146516WINFALL
Solar/Wind Harmer
-0.084
3146516WINFALL
Solar/Wind Harmer
-0.026
315800Z1-036_GEN1
Solar/Wind Harmer
6.351
970919AG2-571 GEN
Solar/Wind Harmer
7.965
3145893MURPHYS
Solar/Wind Harmer
-0.096
3145893MURPHYS
Solar/Wind Harmer
0.717
962861AG1-135 GEN
Solar/Wind Harmer
8.916
315693AD1-088 GEN
Solar/Wind Harmer
11.802
3146263WOODLND
Solar/Wind Harmer
-0.023
962491AG1-098 GEN
Solar/Wind Harmer
15.74
316011AB1-132 GEN
Solar/Wind Harmer
4.894
3145963POPLR C
Solar/Wind Harmer
-0.023
3141726DUNNSVL
Solar/Wind Harmer
-0.093
316174AB2-169 GEN
Solar/Wind Harmer
3.565
3144293JTRSVLE
Adder
0.513
CPLELTFEXP_CPLE->PJM
CLTF
12.064
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.692
NYPJM->LTFIMP_NY
CLTF
3.429
LGEELTFEXP_LGEE->PJM
CLTF
1.289
WECLTFEXP_WEC->PJM
CLTF
0.615
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.16
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.053
MECLTFEXP_MEC->PJM
CLTF
3.551
SIGELTFEXP_SIGE->PJM
CLTF
0.108
LAGNLTFEXP_LAGN->PJM
CLTF
8.194
CBM South 2LTFEXP_CBM-S2->PJM
CBM
26.289
TVALTFEXP_TVA->PJM
CLTF
4.152
CONTINGENCY 'DVP_P1-2: LN 2049_SRT-A'
 OPEN BRANCH FROM BUS 314271 TO BUS 314281 CKT 1   /*6ALLIED      230.0 - 6BURDET      230.0
 OPEN BRANCH FROM BUS 314281 TO BUS 314294 CKT 1   /*6BURDET      230.0 - 6ENON        230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314294 CKT 1   /*6CHESTF A    230.0 - 6ENON        230.0
 OPEN BUS 314281                                   /*6BURDET      230.0
 OPEN BUS 314294                                   /*6ENON        230.0
END
CONTINGENCY 'DVP_P1-2: LN 2050_SRT-S'
 OPEN BRANCH FROM BUS 314214 TO BUS 314308 CKT 1                /*6CHCKAHM     230.0 - 6ICI         230.0
 OPEN BRANCH FROM BUS 314271 TO BUS 314272 CKT 1                /*6ALLIED      230.0 - 6ALPINE      230.0
 OPEN BRANCH FROM BUS 314272 TO BUS 314308 CKT 1                /*6ALPINE      230.0 - 6ICI         230.0
 OPEN BUS 314272                                                /*6ALPINE      230.0
 OPEN BUS 314308                                                /*6ICI         230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314271 TO BUS 314281 CKT 1 /*6ALLIED      230.0 - 6BURDET      230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314271 TO BUS 314281 CKT 1 /*6ALLIED      230.0 - 6BURDET      230.0
END
CONTINGENCY 'DVP_P4-2: 562T563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 940640 CKT 1   /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-S'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: 56372_SRT-S'
 OPEN BRANCH FROM BUS 314282 TO BUS 314902 CKT 1                /*6CARSON      230.0 - 8CARSON      500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-S'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1                /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1                /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1                /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                                /*6CHARCTY     230.0
 OPEN BUS 314260                                                /*6VARINA      230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
END
CONTINGENCY 'DVP_P4-2: H6T563_SRT-S'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1                /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1                /*8MDLTHAN     500.0 - 8NO ANNA     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P4-2: H6T576_SRT-A'
 OPEN BRANCH FROM BUS 314322 TO BUS 314914 CKT 1   /*6MDLTHAN     230.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1   /*8CARSON      500.0 - 8MDLTHAN     500.0
 OPEN BRANCH FROM BUS 314914 TO BUS 314918 CKT 1   /*8MDLTHAN     500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: 21712_SRT-S'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1                /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1                /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1                /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                                /*6CHARCTY     230.0
 OPEN BUS 314260                                                /*6VARINA      230.0
 SET POSTCONTRATING 956 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
 SET PRECONTRATING 876 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
END
CONTINGENCY 'DVP_P7-1: LN 208-259_SRT-S'
 OPEN BRANCH FROM BUS 314276 TO BUS 314287 CKT 1                /*6BASIN       230.0 - 6CHESTF B    230.0
 OPEN BRANCH FROM BUS 314286 TO BUS 314309 CKT 1                /*6CHESTF A    230.0 - 6IRON208     230.0
 OPEN BRANCH FROM BUS 314309 TO BUS 314338 CKT 1                /*6IRON208     230.0 - 6SOUWEST     230.0
 OPEN BUS 314309                                                /*6IRON208     230.0
 SET POSTCONTRATING 876 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
 SET PRECONTRATING 813 BRANCH FROM BUS 314263 TO BUS 314287 CKT 1 /*6TYLER1      230.0 - 6CHESTF B    230.0
END
CONTINGENCY 'DVP_P1-2: LN 557_SRT-S'
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 55722_SRT-S'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1                /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1                /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1                /*8CHCKAHM     500.0 - 8SURRY       500.0
 SET POSTCONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2650 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: 56722_SRT-A'
 OPEN BRANCH FROM BUS 314214 TO BUS 314903 CKT 1   /*6CHCKAHM     230.0 - 8CHCKAHM     500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314908 CKT 1   /*8CHCKAHM     500.0 - 8ELMONT      500.0
 OPEN BRANCH FROM BUS 314903 TO BUS 314924 CKT 1   /*8CHCKAHM     500.0 - 8SURRY       500.0
END
CONTINGENCY 'DVP_P1-2: LN 552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P1-2: LN 581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
END
CONTINGENCY 'DVP_P4-2: H1T581_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 2                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314196 TO BUS 314911 CKT 1                /*6LADYSMITH   230.0 - 8LADYSMITH   500.0
 OPEN BRANCH FROM BUS 314905 TO BUS 314911 CKT 1                /*8CHANCE      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 2913 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314908 TO BUS 314911 CKT 1 /*8ELMONT      500.0 - 8LADYSMITH   500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314911 TO BUS 314918 CKT 1 /*8LADYSMITH   500.0 - 8NO ANNA     500.0
END
CONTINGENCY 'DVP_P4-2: H1T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
CONTINGENCY 'DVP_P4-2: 545T552_SRT-S'
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314916 CKT 1                /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314916 TO BUS 314934 CKT 1 /*8MORRSVL     500.0 - 8SPOTSYL     500.0
END
CONTINGENCY 'DVP_P4-2: H3T552_SRT-S'
 OPEN BRANCH FROM BUS 314130 TO BUS 314900 CKT 2                /*6BRISTER     230.0 - 8BRISTER     500.0
 OPEN BRANCH FROM BUS 314135 TO BUS 314905 CKT 1                /*3CHANCE      115.0 - 8CHANCE      500.0
 OPEN BRANCH FROM BUS 314900 TO BUS 314905 CKT 1                /*8BRISTER     500.0 - 8CHANCE      500.0
 SET POSTCONTRATING 3118 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
 SET PRECONTRATING 2858 BRANCH FROM BUS 314900 TO BUS 314916 CKT 1 /*8BRISTER     500.0 - 8MORRSVL     500.0
END
314286 to 314214 ckt 1
314287 to 314276 ckt 1
314287 to 314260 ckt 1
314236 to 314218 ckt 1
314260 to 314225 ckt 1
314918 to 314934 ckt 1
314934 to 314916 ckt 1

Winter Peak Analysis

The New Service Request AG2-384 was evaluated as a 60.0 MW (24.0 MW Capacity) injection in the Dominion area.

AG2-384 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 60.0 MW (60.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-384 was evaluated as a 60.0 MW injection and 60.0 MW withdrawal in the Dominion area.

AG2-384 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 60.0 MW (60.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.81 %830.96B920.763.4
GD2DVP
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-L
SingleAC105.8 %830.96B879.143.44
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC110.63 %830.96B919.263.4
GD2DVP
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
DVP_P1-2: LN 553_SRT-L
SingleAC105.62 %830.96B877.653.44
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 563_SRT-L
SingleAC111.19 %722.86B803.7514.49
GD2DVP
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
DVP_P1-2: LN 217_SRT-L
SingleAC104.04 %722.86B752.0418.09
GD2DVP
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC111.7 %830.96B928.213.08
GD2DVP
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC114.32 %808.4B924.153.08
GD2DVP
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
DVP_P1-2: LN 534_SRT-L
SingleAC113.71 %808.4B919.253.08

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.81 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:920.76
MW Contribution:3.4
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.859
3147133PAMPLIN
Solar/Wind Harmer
1.765
3147133PAMPLIN
Solar/Wind Harmer
0.562
3147133PAMPLIN
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
2.592
3143336POWHATN
Solar/Wind Harmer
2.203
3146776BUCKING
Solar/Wind Harmer
3.848
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.346
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.456
3146926FARMVIL
Solar/Wind Harmer
0.456
316303AF2-085
50/50
1.901
3144303KENBRDG
Solar/Wind Harmer
0.346
315616AA1-038_C
Solar/Wind Helper
1.61
315760AF1-028 GEN
50/50
Charging
15.637
315779AE2-040
50/50
0.908
316499AE2-029_GEN
Solar/Wind Helper
1.253
315657AE1-056 GEN
Solar/Wind Harmer
6.745
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.292
946301AF1-294 GEN
Solar/Wind Harmer
4.339
959311AF2-222 GEN
Solar/Wind Harmer
14.907
961791AG1-021 GEN
Solar/Wind Harmer
2.117
962491AG1-098 GEN
Solar/Wind Harmer
5.333
963041AG1-153 GEN
50/50
4.555
963171AG1-166 GEN
Solar/Wind Harmer
2.117
963181AG1-167 GEN
Solar/Wind Harmer
1.587
963191AG1-168 GEN
Solar/Wind Harmer
1.587
970117AG2-086 GEN
50/50
Charging
1.232
970119AG2-088 GEN
50/50
14.256
970257AG2-171 GEN
Solar/Wind Harmer
5.183
970285AG2-188 GEN
Solar/Wind Harmer
25.543
970301AG2-198 GEN
Solar/Wind Harmer
9.152
970323AG2-213 GEN
Solar/Wind Harmer
6.911
970413AG2-270 GEN
50/50
13.231
970531AG2-338 GEN
50/50
2.376
970533AG2-339 GEN
50/50
5.94
970535AG2-341 GEN
50/50
4.866
970603AG2-384 GEN
50/50
3.405
970681AG2-440 GEN
Solar/Wind Harmer
9.64
970683AG2-441 GEN
Solar/Wind Harmer
12.05
970685AG2-442 GEN
Solar/Wind Harmer
13.496
970909AG2-566 GEN
Solar/Wind Harmer
5.918
970937AG2-583 GEN
Solar/Wind Harmer
22.906
971193AH1-056 GEN
Solar/Wind Harmer
11.241
971211AH1-065 GEN
50/50
0.534
971563AH1-280 GEN
Solar/Wind Harmer
2.117
958211AF2-115 GEN
Solar/Wind Harmer
2.646
964241AG1-285 GEN
Solar/Wind Harmer
8.987
966001AG1-469 GEN
Solar/Wind Helper
0.283
971741AH1-377 GEN
Solar/Wind Harmer
19.11
971775AH1-396 GEN
Solar/Wind Harmer
1.037
971845AH1-439 GEN
Solar/Wind Harmer
16.063
972003AH1-546 GEN
Solar/Wind Harmer
18.559
972185AH1-677 GEN
50/50
4.042
972187AH1-678 GEN
50/50
2.065
972205AH1-687 GEN
50/50
21.244
NYPJM->LTFIMP_NY
CLTF
0.415
CPLELTFEXP_CPLE->PJM
CLTF
2.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.62
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.509
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.564
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.514
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6BREMO-6BREMODIST 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMO-6BREMODIST 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.8 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:879.14
MW Contribution:3.44
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.864
3147133PAMPLIN
Solar/Wind Harmer
1.77
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.598
3143336POWHATN
Solar/Wind Harmer
2.208
3146776BUCKING
Solar/Wind Harmer
3.854
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.347
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.457
3146926FARMVIL
Solar/Wind Harmer
0.457
316303AF2-085
50/50
1.911
3144303KENBRDG
Solar/Wind Harmer
0.347
315616AA1-038_C
Solar/Wind Helper
1.6
315760AF1-028 GEN
50/50
Charging
15.534
315779AE2-040
50/50
0.916
316499AE2-029_GEN
Solar/Wind Helper
1.246
315657AE1-056 GEN
Solar/Wind Harmer
6.762
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.584
946301AF1-294 GEN
Solar/Wind Harmer
4.351
959311AF2-222 GEN
Solar/Wind Harmer
14.957
961791AG1-021 GEN
Solar/Wind Harmer
2.123
962491AG1-098 GEN
Solar/Wind Harmer
5.357
963041AG1-153 GEN
50/50
4.594
963171AG1-166 GEN
Solar/Wind Harmer
2.123
963181AG1-167 GEN
Solar/Wind Harmer
1.592
963191AG1-168 GEN
Solar/Wind Harmer
1.592
970117AG2-086 GEN
50/50
Charging
1.223
970119AG2-088 GEN
50/50
14.333
970257AG2-171 GEN
Solar/Wind Harmer
5.201
970285AG2-188 GEN
Solar/Wind Harmer
25.585
970301AG2-198 GEN
Solar/Wind Harmer
9.176
970323AG2-213 GEN
Solar/Wind Harmer
6.935
970413AG2-270 GEN
50/50
13.308
970531AG2-338 GEN
50/50
2.397
970533AG2-339 GEN
50/50
5.992
970535AG2-341 GEN
50/50
4.892
970603AG2-384 GEN
50/50
3.436
970681AG2-440 GEN
Solar/Wind Harmer
9.67
970683AG2-441 GEN
Solar/Wind Harmer
12.087
970685AG2-442 GEN
Solar/Wind Harmer
13.538
970909AG2-566 GEN
Solar/Wind Harmer
5.933
970937AG2-583 GEN
Solar/Wind Harmer
22.94
971193AH1-056 GEN
Solar/Wind Harmer
11.271
971211AH1-065 GEN
50/50
0.539
971563AH1-280 GEN
Solar/Wind Harmer
2.123
958211AF2-115 GEN
Solar/Wind Harmer
2.653
964241AG1-285 GEN
Solar/Wind Harmer
9.024
966001AG1-469 GEN
Solar/Wind Helper
0.281
971741AH1-377 GEN
Solar/Wind Harmer
19.165
971775AH1-396 GEN
Solar/Wind Harmer
1.04
971845AH1-439 GEN
Solar/Wind Harmer
16.088
972003AH1-546 GEN
Solar/Wind Harmer
18.583
972185AH1-677 GEN
50/50
4.077
972187AH1-678 GEN
50/50
2.083
972205AH1-687 GEN
50/50
21.27
NYPJM->LTFIMP_NY
CLTF
0.387
CPLELTFEXP_CPLE->PJM
CLTF
2.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.487
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.481
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.649
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.63 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:919.26
MW Contribution:3.4
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.859
3147133PAMPLIN
Solar/Wind Harmer
1.765
3147133PAMPLIN
Solar/Wind Harmer
0.562
3147133PAMPLIN
Solar/Wind Harmer
0.45
3143336POWHATN
Solar/Wind Harmer
2.592
3143336POWHATN
Solar/Wind Harmer
2.203
3146776BUCKING
Solar/Wind Harmer
3.848
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.346
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.456
3146926FARMVIL
Solar/Wind Harmer
0.456
316303AF2-085
50/50
1.901
3144303KENBRDG
Solar/Wind Harmer
0.346
315616AA1-038_C
Solar/Wind Helper
1.61
315760AF1-028 GEN
50/50
Charging
15.637
315779AE2-040
50/50
0.908
316499AE2-029_GEN
Solar/Wind Helper
1.253
315657AE1-056 GEN
Solar/Wind Harmer
6.745
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.292
946301AF1-294 GEN
Solar/Wind Harmer
4.339
959311AF2-222 GEN
Solar/Wind Harmer
14.907
961791AG1-021 GEN
Solar/Wind Harmer
2.117
962491AG1-098 GEN
Solar/Wind Harmer
5.333
963041AG1-153 GEN
50/50
4.555
963171AG1-166 GEN
Solar/Wind Harmer
2.117
963181AG1-167 GEN
Solar/Wind Harmer
1.587
963191AG1-168 GEN
Solar/Wind Harmer
1.587
970117AG2-086 GEN
50/50
Charging
1.232
970119AG2-088 GEN
50/50
14.256
970257AG2-171 GEN
Solar/Wind Harmer
5.183
970285AG2-188 GEN
Solar/Wind Harmer
25.543
970301AG2-198 GEN
Solar/Wind Harmer
9.152
970323AG2-213 GEN
Solar/Wind Harmer
6.911
970413AG2-270 GEN
50/50
13.231
970531AG2-338 GEN
50/50
2.376
970533AG2-339 GEN
50/50
5.94
970535AG2-341 GEN
50/50
4.866
970603AG2-384 GEN
50/50
3.405
970681AG2-440 GEN
Solar/Wind Harmer
9.64
970683AG2-441 GEN
Solar/Wind Harmer
12.05
970685AG2-442 GEN
Solar/Wind Harmer
13.496
970909AG2-566 GEN
Solar/Wind Harmer
5.918
970937AG2-583 GEN
Solar/Wind Harmer
22.906
971193AH1-056 GEN
Solar/Wind Harmer
11.241
971211AH1-065 GEN
50/50
0.534
971563AH1-280 GEN
Solar/Wind Harmer
2.117
958211AF2-115 GEN
Solar/Wind Harmer
2.646
964241AG1-285 GEN
Solar/Wind Harmer
8.987
966001AG1-469 GEN
Solar/Wind Helper
0.283
971741AH1-377 GEN
Solar/Wind Harmer
19.11
971775AH1-396 GEN
Solar/Wind Harmer
1.037
971845AH1-439 GEN
Solar/Wind Harmer
16.063
972003AH1-546 GEN
Solar/Wind Harmer
18.559
972185AH1-677 GEN
50/50
4.042
972187AH1-678 GEN
50/50
2.065
972205AH1-687 GEN
50/50
21.244
NYPJM->LTFIMP_NY
CLTF
0.415
CPLELTFEXP_CPLE->PJM
CLTF
2.798
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.62
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.509
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.564
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.514
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 553_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6BREMODIST-6FORK UNION 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 553_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.62 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:877.65
MW Contribution:3.44
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.864
3147133PAMPLIN
Solar/Wind Harmer
1.77
3147133PAMPLIN
Solar/Wind Harmer
0.564
3147133PAMPLIN
Solar/Wind Harmer
0.451
3143336POWHATN
Solar/Wind Harmer
2.598
3143336POWHATN
Solar/Wind Harmer
2.208
3146776BUCKING
Solar/Wind Harmer
3.854
3146776BUCKING
Solar/Wind Harmer
0.385
3146776BUCKING
Solar/Wind Harmer
0.347
3146776BUCKING
Solar/Wind Harmer
0.312
3146926FARMVIL
Solar/Wind Harmer
0.457
3146926FARMVIL
Solar/Wind Harmer
0.457
316303AF2-085
50/50
1.911
3144303KENBRDG
Solar/Wind Harmer
0.347
315616AA1-038_C
Solar/Wind Helper
1.6
315760AF1-028 GEN
50/50
Charging
15.534
315779AE2-040
50/50
0.916
316499AE2-029_GEN
Solar/Wind Helper
1.246
315657AE1-056 GEN
Solar/Wind Harmer
6.762
315785AD2-033 C
Solar/Wind Harmer
0
316322AB2-045
Solar/Wind Harmer
0.028
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
32.584
946301AF1-294 GEN
Solar/Wind Harmer
4.351
959311AF2-222 GEN
Solar/Wind Harmer
14.957
961791AG1-021 GEN
Solar/Wind Harmer
2.123
962491AG1-098 GEN
Solar/Wind Harmer
5.357
963041AG1-153 GEN
50/50
4.594
963171AG1-166 GEN
Solar/Wind Harmer
2.123
963181AG1-167 GEN
Solar/Wind Harmer
1.592
963191AG1-168 GEN
Solar/Wind Harmer
1.592
970117AG2-086 GEN
50/50
Charging
1.223
970119AG2-088 GEN
50/50
14.333
970257AG2-171 GEN
Solar/Wind Harmer
5.201
970285AG2-188 GEN
Solar/Wind Harmer
25.585
970301AG2-198 GEN
Solar/Wind Harmer
9.176
970323AG2-213 GEN
Solar/Wind Harmer
6.935
970413AG2-270 GEN
50/50
13.308
970531AG2-338 GEN
50/50
2.397
970533AG2-339 GEN
50/50
5.992
970535AG2-341 GEN
50/50
4.892
970603AG2-384 GEN
50/50
3.436
970681AG2-440 GEN
Solar/Wind Harmer
9.67
970683AG2-441 GEN
Solar/Wind Harmer
12.087
970685AG2-442 GEN
Solar/Wind Harmer
13.538
970909AG2-566 GEN
Solar/Wind Harmer
5.933
970937AG2-583 GEN
Solar/Wind Harmer
22.94
971193AH1-056 GEN
Solar/Wind Harmer
11.271
971211AH1-065 GEN
50/50
0.539
971563AH1-280 GEN
Solar/Wind Harmer
2.123
958211AF2-115 GEN
Solar/Wind Harmer
2.653
964241AG1-285 GEN
Solar/Wind Harmer
9.024
966001AG1-469 GEN
Solar/Wind Helper
0.281
971741AH1-377 GEN
Solar/Wind Harmer
19.165
971775AH1-396 GEN
Solar/Wind Harmer
1.04
971845AH1-439 GEN
Solar/Wind Harmer
16.088
972003AH1-546 GEN
Solar/Wind Harmer
18.583
972185AH1-677 GEN
50/50
4.077
972187AH1-678 GEN
50/50
2.083
972205AH1-687 GEN
50/50
21.27
NYPJM->LTFIMP_NY
CLTF
0.387
CPLELTFEXP_CPLE->PJM
CLTF
2.847
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.487
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.481
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.649
GibsonPJM->LTFIMP_GIBSON
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.706

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 563_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 563_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.19 %
Rating:722.86 MVA
Rating Type:B
MVA to Mitigate:803.75
MW Contribution:14.49
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.689
3143316POE
Solar/Wind Harmer
1.758
3144356SAPONY
Solar/Wind Harmer
1.204
316258AE1-075 C
Solar/Wind Helper
0.296
316303AF2-085
50/50
Charging
1.778
316336AC2-165 C
Solar/Wind Helper
1.446
316405AF2-144 C
50/50
Charging
0.67
3145336SMITFLD
Solar/Wind Harmer
0.813
3145336SMITFLD
Solar/Wind Harmer
0.081
316033AB2-134 GEN
Solar/Wind Harmer
0
315779AE2-040
50/50
1.629
315814AE2-033 C
Solar/Wind Harmer
8.863
315671AE2-027_GEN
Solar/Wind Harmer
5.491
315813AE1-149 C
Solar/Wind Harmer
7.13
315697AD1-025 GEN
Solar/Wind Harmer
0
315778AD1-151 GEN
Solar/Wind Harmer
8.057
316313AB2-026
Solar/Wind Helper
0.329
315652AC1-086 GEN
Solar/Wind Harmer
7.206
316083AB2-161 GEN
Solar/Wind Harmer
1.069
316311AC2-079 GEN
Solar/Wind Harmer
4.004
316233AE1-074 FULL
Solar/Wind Helper
0.35
944011AF1-069 GEN
Solar/Wind Harmer
2.029
944011AF1-069 GEN
Solar/Wind Harmer
2.52
944641AF1-129 GEN
50/50
137.395
960081AF2-299 GEN
Solar/Wind Harmer
0.756
963041AG1-153 GEN
50/50
4.827
970119AG2-088 GEN
50/50
Charging
13.335
970133AG2-095 GEN
Solar/Wind Harmer
1.298
970413AG2-270 GEN
50/50
7.54
970531AG2-338 GEN
50/50
2.714
970533AG2-339 GEN
50/50
6.785
970603AG2-384 GEN
50/50
14.488
970657AG2-426 GEN
Solar/Wind Harmer
3.02
970657AG2-426 GEN
Solar/Wind Harmer
2.15
970659AG2-427 GEN
Solar/Wind Harmer
5.394
970659AG2-427 GEN
Solar/Wind Harmer
3.255
970661AG2-428 GEN
Solar/Wind Harmer
9.817
970661AG2-428 GEN
Solar/Wind Harmer
5.924
971069AG2-661 GEN
Solar/Wind Harmer
5.165
971211AH1-065 GEN
50/50
2.487
971213AH1-066 GEN
50/50
1.244
971647AH1-324 GEN
Solar/Wind Harmer
4.248
941031AE2-094 GEN
Solar/Wind Harmer
6.476
941031AE2-094 GEN
Solar/Wind Harmer
7.712
941591AE2-156 GEN
50/50
5.949
965281AG1-393 GEN
Solar/Wind Harmer
1.078
972185AH1-677 GEN
50/50
4.383
972187AH1-678 GEN
50/50
2.188
972265AH1-717 GEN
50/50
7.106
NYPJM->LTFIMP_NY
CLTF
0.604
LGEELTFEXP_LGEE->PJM
CLTF
0.263
WECLTFEXP_WEC->PJM
CLTF
0.137
CPLELTFEXP_CPLE->PJM
CLTF
3.375
LAGNLTFEXP_LAGN->PJM
CLTF
2.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.674
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.052
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.475
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.888
TVALTFEXP_TVA->PJM
CLTF
1.04
MECLTFEXP_MEC->PJM
CLTF
0.825
SIGELTFEXP_SIGE->PJM
CLTF
0.024
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.583

Details for 6CHESTF B-6BASIN 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 217_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6CHESTF B-6BASIN 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 217_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.04 %
Rating:722.86 MVA
Rating Type:B
MVA to Mitigate:752.04
MW Contribution:18.09
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
Solar/Wind Harmer
0.047
3147043LAWRENC
50/50
0.625
3147133PAMPLIN
Solar/Wind Harmer
0.087
3147133PAMPLIN
Solar/Wind Harmer
0.028
3147133PAMPLIN
Solar/Wind Harmer
0.022
3137176SLIGO L2192
Solar/Wind Harmer
0.262
3143316POE
Solar/Wind Harmer
0.935
3144356SAPONY
Solar/Wind Harmer
0.566
3145506HICKORY
Solar/Wind Harmer
0.261
3145506HICKORY
Solar/Wind Harmer
0.157
3145506HICKORY
Solar/Wind Harmer
0.039
3146386ELIZ CT
Solar/Wind Harmer
0.067
3146396TANGLEW
Solar/Wind Harmer
0.041
3138133OCRAN
Solar/Wind Harmer
0.003
3138133OCRAN
Solar/Wind Harmer
0.001
3141766HARMONY
Solar/Wind Harmer
0.005
3141766HARMONY
Solar/Wind Harmer
0.001
3141783LANCAST
Solar/Wind Harmer
0.002
3141783LANCAST
Solar/Wind Harmer
0.001
3141913WHIT STONE
Solar/Wind Harmer
0.005
3143226MDLTHAN
Solar/Wind Harmer
-0.096
3145273HOLLAND
Solar/Wind Harmer
0.059
3146376EDENTON
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.068
3146376EDENTON
Solar/Wind Harmer
0.068
3146456SLIGO L269
Solar/Wind Harmer
0.262
3146456SLIGO L269
Solar/Wind Harmer
0.066
3146456SLIGO L269
Solar/Wind Harmer
0.066
3146486SUNBURY
Solar/Wind Harmer
0.068
3146486SUNBURY
Solar/Wind Harmer
0.068
3146516WINFALL
Solar/Wind Harmer
0.218
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146516WINFALL
Solar/Wind Harmer
0.067
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146626S HERTFORD
Solar/Wind Harmer
0.068
3146843MT LREL
Solar/Wind Harmer
0.044
3146843MT LREL
Solar/Wind Harmer
0.044
3146926FARMVIL
Solar/Wind Harmer
0.007
3146926FARMVIL
Solar/Wind Harmer
0.007
3147123OTTER R
Solar/Wind Harmer
0.01
3147312GRETNA
Solar/Wind Harmer
0.011
3147312GRETNA
Solar/Wind Harmer
0.003
3145663CRESWEL
Solar/Wind Harmer
0.191
316303AF2-085
50/50
Charging
1.424
316316AC1-027 C
Solar/Wind Harmer
0
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
3130156CHOWAN
Solar/Wind Harmer
0.068
3145336SMITFLD
Solar/Wind Harmer
0.369
3145336SMITFLD
Solar/Wind Harmer
0.037
3146802CHATHAM
Solar/Wind Harmer
0.011
3147243WELCO
Solar/Wind Harmer
0.026
3141873WAN 176
Solar/Wind Harmer
0.025
3141873WAN 176
Solar/Wind Harmer
0.001
3143526WINTERP
Solar/Wind Harmer
-0.395
3143526WINTERP
Solar/Wind Harmer
-0.395
316033AB2-134 GEN
Solar/Wind Harmer
0
3145176PASQUOTANK
Solar/Wind Harmer
0.041
3142543TWELFTH
Solar/Wind Harmer
-0.023
3144303KENBRDG
Solar/Wind Harmer
0.03
3147173SINAI
Solar/Wind Harmer
0.041
3156081AA2-088 GEN
Solar/Wind Harmer
0
315835AF2-110_GEN
Solar/Wind Harmer
0.69
315779AE2-040
50/50
1.657
315814AE2-033 C
Solar/Wind Harmer
8.993
315671AE2-027_GEN
Solar/Wind Harmer
6.698
315813AE1-149 C
Solar/Wind Harmer
8.113
315697AD1-025 GEN
Solar/Wind Harmer
0
316473AC1-191 GEN
Solar/Wind Helper
1.201
315778AD1-151 GEN
Solar/Wind Harmer
9.319
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145513AHOSKIE
Solar/Wind Harmer
0.073
3145746EVERETS
Solar/Wind Harmer
0.253
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3145746EVERETS
Solar/Wind Harmer
0.064
3146206CASHIE
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.07
3146206CASHIE
Solar/Wind Harmer
0.07
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.084
3142666NORTHAMPTON
Solar/Wind Harmer
0.05
315652AC1-086 GEN
Solar/Wind Harmer
6.657
316083AB2-161 GEN
Solar/Wind Harmer
1.173
316311AC2-079 GEN
Solar/Wind Harmer
4.01
316233AE1-074 FULL
Solar/Wind Helper
0.305
316093AE2-104_GEN
Solar/Wind Harmer
1.69
3130546PLYMOUTH
Solar/Wind Harmer
0.069
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.063
3145543BTLEBRO
Solar/Wind Harmer
0.05
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.076
3145593CAROLNA
Solar/Wind Harmer
0.021
3145683EARLEYS
Solar/Wind Harmer
0.144
3145683EARLEYS
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.072
3145683EARLEYS
Solar/Wind Harmer
0.072
3130086AYDLETT
Solar/Wind Harmer
0.264
3137643SOCKMAN
Solar/Wind Harmer
0.319
3138543CONSLDL
Solar/Wind Harmer
0.043
3142946ENON
Solar/Wind Harmer
0.011
3142946ENON
Solar/Wind Harmer
0.003
3144536CHRHLND
Solar/Wind Harmer
0.011
3144873MCLAUGH
Solar/Wind Harmer
0.002
3145493TOT1
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145573BETHELC
Solar/Wind Harmer
0.064
3145783HORNRTN
Solar/Wind Harmer
0.301
3145783HORNRTN
Solar/Wind Harmer
0.241
3145783HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.075
3145783HORNRTN
Solar/Wind Harmer
0.03
3145796HORNRTN
Solar/Wind Harmer
0.329
3145796HORNRTN
Solar/Wind Harmer
0.272
3145796HORNRTN
Solar/Wind Harmer
0.264
3145796HORNRTN
Solar/Wind Harmer
0.247
3145796HORNRTN
Solar/Wind Harmer
0.082
3145796HORNRTN
Solar/Wind Harmer
0.082
3145796HORNRTN
Solar/Wind Harmer
0.033
3145823KELFORD
Solar/Wind Harmer
0.071
3145823KELFORD
Solar/Wind Harmer
0.071
3145893MURPHYS
Solar/Wind Harmer
0.3
3145893MURPHYS
Solar/Wind Harmer
0.519
3145893MURPHYS
Solar/Wind Harmer
0.203
3145893MURPHYS
Solar/Wind Harmer
0.135
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.075
3145893MURPHYS
Solar/Wind Harmer
0.075
3145933PARMELE
Solar/Wind Harmer
0.129
3145933PARMELE
Solar/Wind Harmer
0.064
3145933PARMELE
Solar/Wind Harmer
0.064
3145963POPLR C
Solar/Wind Harmer
0.066
3145963POPLR C
Solar/Wind Harmer
0.066
3146033SCOT NK
Solar/Wind Harmer
0.282
3146043SEABORD
Solar/Wind Harmer
0.076
3146073TAR RVR
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3146083TARBORO
Solar/Wind Harmer
0.064
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146173TUNIS
Solar/Wind Harmer
0.074
3146233WITAKRS
Solar/Wind Harmer
0.258
3146233WITAKRS
Solar/Wind Harmer
0.156
3146233WITAKRS
Solar/Wind Harmer
0.044
3146263WOODLND
Solar/Wind Harmer
0.073
3146263WOODLND
Solar/Wind Harmer
0.073
3146406KITTY HAWK
Solar/Wind Harmer
0.002
316318V4-068
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
171.597
960081AF2-299 GEN
Solar/Wind Harmer
0.709
966811AG1-552 GEN
Solar/Wind Harmer
0.594
970119AG2-088 GEN
50/50
Charging
10.679
970133AG2-095 GEN
Solar/Wind Harmer
1.573
970603AG2-384 GEN
50/50
18.095
970657AG2-426 GEN
Solar/Wind Harmer
3.291
970657AG2-426 GEN
Solar/Wind Harmer
2.343
970659AG2-427 GEN
Solar/Wind Harmer
5.961
970659AG2-427 GEN
Solar/Wind Harmer
3.597
970661AG2-428 GEN
Solar/Wind Harmer
10.558
970661AG2-428 GEN
Solar/Wind Harmer
6.371
971069AG2-661 GEN
Solar/Wind Harmer
5.974
971211AH1-065 GEN
50/50
3.014
971213AH1-066 GEN
50/50
1.507
971645AH1-323 GEN
50/50
Charging
5.587
971647AH1-324 GEN
Solar/Wind Harmer
4.736
941591AE2-156 GEN
50/50
5.075
965281AG1-393 GEN
Solar/Wind Harmer
1.3
965291AG1-394 GEN
Solar/Wind Harmer
0.47
971795AH1-408 GEN
Solar/Wind Harmer
4.25
972265AH1-717 GEN
50/50
7.415
NYPJM->LTFIMP_NY
CLTF
0.476
LGEELTFEXP_LGEE->PJM
CLTF
0.143
WECLTFEXP_WEC->PJM
CLTF
0.074
CPLELTFEXP_CPLE->PJM
CLTF
2.563
LAGNLTFEXP_LAGN->PJM
CLTF
1.388
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
6.596
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.347
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.094
TVALTFEXP_TVA->PJM
CLTF
0.713
MECLTFEXP_MEC->PJM
CLTF
0.494
SIGELTFEXP_SIGE->PJM
CLTF
0.014
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
6.528

Details for 6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6FORK UNION-6GRAPEVINE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.7 %
Rating:830.96 MVA
Rating Type:B
MVA to Mitigate:928.21
MW Contribution:3.08
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.8
3147133PAMPLIN
Solar/Wind Harmer
1.646
3147133PAMPLIN
Solar/Wind Harmer
0.524
3147133PAMPLIN
Solar/Wind Harmer
0.419
3143336POWHATN
Solar/Wind Harmer
2.402
3143336POWHATN
Solar/Wind Harmer
2.042
3146776BUCKING
Solar/Wind Harmer
3.583
3146776BUCKING
Solar/Wind Harmer
0.358
3146776BUCKING
Solar/Wind Harmer
0.322
3146776BUCKING
Solar/Wind Harmer
0.29
3146926FARMVIL
Solar/Wind Harmer
0.424
3146926FARMVIL
Solar/Wind Harmer
0.424
316303AF2-085
50/50
1.738
315616AA1-038_C
Solar/Wind Helper
1.534
315760AF1-028 GEN
50/50
Charging
15.049
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.831
316499AE2-029_GEN
Solar/Wind Helper
1.21
315657AE1-056 GEN
Solar/Wind Harmer
6.292
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.518
316322AB2-045
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
29.223
946301AF1-294 GEN
Solar/Wind Harmer
4.049
959311AF2-222 GEN
Solar/Wind Harmer
13.93
961791AG1-021 GEN
Solar/Wind Harmer
1.975
963041AG1-153 GEN
50/50
4.194
963171AG1-166 GEN
Solar/Wind Harmer
1.975
963181AG1-167 GEN
Solar/Wind Harmer
1.481
963191AG1-168 GEN
Solar/Wind Harmer
1.481
970117AG2-086 GEN
50/50
Charging
1.192
970119AG2-088 GEN
50/50
13.036
970221AG2-151 GEN
Solar/Wind Harmer
19.866
970257AG2-171 GEN
Solar/Wind Harmer
0.159
970285AG2-188 GEN
Solar/Wind Harmer
23.783
970301AG2-198 GEN
Solar/Wind Harmer
8.523
970323AG2-213 GEN
Solar/Wind Harmer
6.46
970413AG2-270 GEN
50/50
12.353
970531AG2-338 GEN
50/50
2.179
970533AG2-339 GEN
50/50
5.446
970535AG2-341 GEN
50/50
4.562
970603AG2-384 GEN
50/50
3.082
970681AG2-440 GEN
Solar/Wind Harmer
9.003
970683AG2-441 GEN
Solar/Wind Harmer
11.253
970685AG2-442 GEN
Solar/Wind Harmer
12.604
970909AG2-566 GEN
Solar/Wind Harmer
5.51
970937AG2-583 GEN
Solar/Wind Harmer
21.3
971193AH1-056 GEN
Solar/Wind Harmer
10.486
971377AH1-170 GEN
Solar/Wind Harmer
3.973
971447AH1-217 GEN
Solar/Wind Harmer
10.342
971489AH1-241 GEN
Solar/Wind Harmer
19.866
971563AH1-280 GEN
Solar/Wind Harmer
1.975
958211AF2-115 GEN
Solar/Wind Harmer
2.469
966001AG1-469 GEN
Solar/Wind Helper
0.309
971741AH1-377 GEN
Solar/Wind Harmer
17.795
971845AH1-439 GEN
Solar/Wind Harmer
14.956
972003AH1-546 GEN
Solar/Wind Harmer
17.278
972185AH1-677 GEN
50/50
3.717
972187AH1-678 GEN
50/50
1.901
972205AH1-687 GEN
50/50
19.776
NYPJM->LTFIMP_NY
CLTF
0.46
CPLELTFEXP_CPLE->PJM
CLTF
2.723
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.143
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.397
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.215
LAGNLTFEXP_LAGN->PJM
CLTF
0.137
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.62
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.077
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.752

Details for 6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.32 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:924.15
MW Contribution:3.08
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.8
3147133PAMPLIN
Solar/Wind Harmer
1.646
3147133PAMPLIN
Solar/Wind Harmer
0.524
3147133PAMPLIN
Solar/Wind Harmer
0.419
3143336POWHATN
Solar/Wind Harmer
2.402
3143336POWHATN
Solar/Wind Harmer
2.042
3146776BUCKING
Solar/Wind Harmer
3.583
3146776BUCKING
Solar/Wind Harmer
0.358
3146776BUCKING
Solar/Wind Harmer
0.322
3146776BUCKING
Solar/Wind Harmer
0.29
3146926FARMVIL
Solar/Wind Harmer
0.424
3146926FARMVIL
Solar/Wind Harmer
0.424
316303AF2-085
50/50
1.738
315616AA1-038_C
Solar/Wind Helper
1.534
315760AF1-028 GEN
50/50
Charging
15.049
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.831
316499AE2-029_GEN
Solar/Wind Helper
1.21
315657AE1-056 GEN
Solar/Wind Harmer
6.292
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.518
316322AB2-045
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
29.223
946301AF1-294 GEN
Solar/Wind Harmer
4.049
959311AF2-222 GEN
Solar/Wind Harmer
13.93
961791AG1-021 GEN
Solar/Wind Harmer
1.975
963041AG1-153 GEN
50/50
4.194
963171AG1-166 GEN
Solar/Wind Harmer
1.975
963181AG1-167 GEN
Solar/Wind Harmer
1.481
963191AG1-168 GEN
Solar/Wind Harmer
1.481
970117AG2-086 GEN
50/50
Charging
1.192
970119AG2-088 GEN
50/50
13.036
970221AG2-151 GEN
Solar/Wind Harmer
19.866
970257AG2-171 GEN
Solar/Wind Harmer
0.159
970285AG2-188 GEN
Solar/Wind Harmer
23.783
970301AG2-198 GEN
Solar/Wind Harmer
8.523
970323AG2-213 GEN
Solar/Wind Harmer
6.46
970413AG2-270 GEN
50/50
12.353
970531AG2-338 GEN
50/50
2.179
970533AG2-339 GEN
50/50
5.446
970535AG2-341 GEN
50/50
4.562
970603AG2-384 GEN
50/50
3.082
970681AG2-440 GEN
Solar/Wind Harmer
9.003
970683AG2-441 GEN
Solar/Wind Harmer
11.253
970685AG2-442 GEN
Solar/Wind Harmer
12.604
970909AG2-566 GEN
Solar/Wind Harmer
5.51
970937AG2-583 GEN
Solar/Wind Harmer
21.3
971193AH1-056 GEN
Solar/Wind Harmer
10.486
971377AH1-170 GEN
Solar/Wind Harmer
3.973
971447AH1-217 GEN
Solar/Wind Harmer
10.342
971489AH1-241 GEN
Solar/Wind Harmer
19.866
971563AH1-280 GEN
Solar/Wind Harmer
1.975
958211AF2-115 GEN
Solar/Wind Harmer
2.469
966001AG1-469 GEN
Solar/Wind Helper
0.309
971741AH1-377 GEN
Solar/Wind Harmer
17.795
971845AH1-439 GEN
Solar/Wind Harmer
14.956
972003AH1-546 GEN
Solar/Wind Harmer
17.278
972185AH1-677 GEN
50/50
3.717
972187AH1-678 GEN
50/50
1.901
972205AH1-687 GEN
50/50
19.776
NYPJM->LTFIMP_NY
CLTF
0.46
CPLELTFEXP_CPLE->PJM
CLTF
2.723
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.143
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.397
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.215
LAGNLTFEXP_LAGN->PJM
CLTF
0.137
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.62
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.077
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.752

Details for 6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line l/o DVP_P1-2: LN 534_SRT-L


Base Case Flowgate

Area:DVP
Facility Description:
6MTEAGLE-6CHARLVL 230.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 534_SRT-L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.71 %
Rating:808.4 MVA
Rating Type:B
MVA to Mitigate:919.25
MW Contribution:3.08
Bus #Bus NameTypeMW Contribution
3147043LAWRENC
50/50
0.8
3147133PAMPLIN
Solar/Wind Harmer
1.646
3147133PAMPLIN
Solar/Wind Harmer
0.524
3147133PAMPLIN
Solar/Wind Harmer
0.419
3143336POWHATN
Solar/Wind Harmer
2.402
3143336POWHATN
Solar/Wind Harmer
2.042
3146776BUCKING
Solar/Wind Harmer
3.583
3146776BUCKING
Solar/Wind Harmer
0.358
3146776BUCKING
Solar/Wind Harmer
0.322
3146776BUCKING
Solar/Wind Harmer
0.29
3146926FARMVIL
Solar/Wind Harmer
0.424
3146926FARMVIL
Solar/Wind Harmer
0.424
316303AF2-085
50/50
1.738
315616AA1-038_C
Solar/Wind Helper
1.534
315760AF1-028 GEN
50/50
Charging
15.049
315821AE2-092 GEN
Solar/Wind Harmer
-0.001
315779AE2-040
50/50
0.831
316499AE2-029_GEN
Solar/Wind Helper
1.21
315657AE1-056 GEN
Solar/Wind Harmer
6.292
270494AE1-108_GEN
Solar/Wind Harmer
0
3147623JAMES R
Solar/Wind Harmer
0.518
316322AB2-045
Solar/Wind Harmer
0.026
942461AE2-259 GEN
Solar/Wind Harmer
0
944641AF1-129 GEN
50/50
29.223
946301AF1-294 GEN
Solar/Wind Harmer
4.049
959311AF2-222 GEN
Solar/Wind Harmer
13.93
961791AG1-021 GEN
Solar/Wind Harmer
1.975
963041AG1-153 GEN
50/50
4.194
963171AG1-166 GEN
Solar/Wind Harmer
1.975
963181AG1-167 GEN
Solar/Wind Harmer
1.481
963191AG1-168 GEN
Solar/Wind Harmer
1.481
970117AG2-086 GEN
50/50
Charging
1.192
970119AG2-088 GEN
50/50
13.036
970221AG2-151 GEN
Solar/Wind Harmer
19.866
970257AG2-171 GEN
Solar/Wind Harmer
0.159
970285AG2-188 GEN
Solar/Wind Harmer
23.783
970301AG2-198 GEN
Solar/Wind Harmer
8.523
970323AG2-213 GEN
Solar/Wind Harmer
6.46
970413AG2-270 GEN
50/50
12.353
970531AG2-338 GEN
50/50
2.179
970533AG2-339 GEN
50/50
5.446
970535AG2-341 GEN
50/50
4.562
970603AG2-384 GEN
50/50
3.082
970681AG2-440 GEN
Solar/Wind Harmer
9.003
970683AG2-441 GEN
Solar/Wind Harmer
11.253
970685AG2-442 GEN
Solar/Wind Harmer
12.604
970909AG2-566 GEN
Solar/Wind Harmer
5.51
970937AG2-583 GEN
Solar/Wind Harmer
21.3
971193AH1-056 GEN
Solar/Wind Harmer
10.486
971377AH1-170 GEN
Solar/Wind Harmer
3.973
971447AH1-217 GEN
Solar/Wind Harmer
10.342
971489AH1-241 GEN
Solar/Wind Harmer
19.866
971563AH1-280 GEN
Solar/Wind Harmer
1.975
958211AF2-115 GEN
Solar/Wind Harmer
2.469
966001AG1-469 GEN
Solar/Wind Helper
0.309
971741AH1-377 GEN
Solar/Wind Harmer
17.795
971845AH1-439 GEN
Solar/Wind Harmer
14.956
972003AH1-546 GEN
Solar/Wind Harmer
17.278
972185AH1-677 GEN
50/50
3.717
972187AH1-678 GEN
50/50
1.901
972205AH1-687 GEN
50/50
19.776
NYPJM->LTFIMP_NY
CLTF
0.46
CPLELTFEXP_CPLE->PJM
CLTF
2.723
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.143
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.397
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.215
LAGNLTFEXP_LAGN->PJM
CLTF
0.137
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.62
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.077
MDUPJM->LTFIMP_MDU
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.752
CONTINGENCY 'DVP_P1-2: LN 534_SRT-L'
 OPEN BRANCH FROM BUS 314907 TO BUS 314910 CKT 1                /*8DOOMS       500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET POSTCONTRATING 4399 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 4157 BRANCH FROM BUS 314907 TO BUS 314926 CKT 1 /*8DOOMS       500.0 - 8VALLEY      500.0
END
CONTINGENCY 'DVP_P1-2: LN 553_SRT-L'
 OPEN BRANCH FROM BUS 314908 TO BUS 314910 CKT 1                /*8ELMONT      500.0 - 8CUNINGHAM   500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET POSTCONTRATING 3326 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314942 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAEAS 500.0
 SET PRECONTRATING 2962 BRANCH FROM BUS 314910 TO BUS 314943 CKT 1 /*8CUNINGHAM   500.0 - 8FLUVANNAWES 500.0
END
CONTINGENCY 'DVP_P1-2: LN 563_SRT-L'
 OPEN BRANCH FROM BUS 314902 TO BUS 314914 CKT 1                /*8CARSON      500.0 - 8MDLTHAN     500.0
 SET POSTCONTRATING 3359 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
 SET PRECONTRATING 3377 BRANCH FROM BUS 314902 TO BUS 940640 CKT 1 /*8CARSON      500.0 - AE2-051 TP   500.0
END
CONTINGENCY 'DVP_P1-2: LN 217_SRT-L'
 OPEN BRANCH FROM BUS 314225 TO BUS 314227 CKT 1                /*6CHARCTY     230.0 - 6LAKESIDE    230.0
 OPEN BRANCH FROM BUS 314225 TO BUS 314260 CKT 1                /*6CHARCTY     230.0 - 6VARINA      230.0
 OPEN BRANCH FROM BUS 314260 TO BUS 314287 CKT 1                /*6VARINA      230.0 - 6CHESTF B    230.0
 OPEN BUS 314225                                                /*6CHARCTY     230.0
 OPEN BUS 314260                                                /*6VARINA      230.0
 SET POSTCONTRATING 1092 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
 SET PRECONTRATING 1036 BRANCH FROM BUS 314287 TO BUS 314346 CKT 1 /*6CHESTF B    230.0 - 6TYLER       230.0
END
314747 to 313867 ckt 1
313867 to 313707 ckt 1
314287 to 314276 ckt 1
313707 to 313373 ckt 1
313373 to 314765 ckt 1
314765 to 314749 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-132Thelma 230kVIn Service
AB2-022Elizabeth City 34.5kVIn Service
AB2-024Correctional 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-040Brink 115kVIn Service
AB2-043Chase City 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-134Hopewell-Surry 230kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-161Waverly #2 DP 115kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-034Heartsease DP - Mayo Dunbar 115kVSuspended
AC1-036Twittys Creek 34.5kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-086Thelma 230kVSuspended
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-164Chickahominy 230kVPartially in Service - Under Construction
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-079Ivor-Oak Ridge 115kVSuspended
AC2-100Halifax-Person 230kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AD1-022Cashie-Trowbridge 230 kVEngineering & Procurement
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-088Briery-Clover 230 kVSuspended
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-151Hopewell-Surry 230 kVSuspended
AD1-152Clover-Sedge Hill 230 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-160Hickory-Moyock 230kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-056Red House-South Creek 115 kVWithdrawn
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-148Kerr Dam-Ridge Rd 115 kVActive
AE1-149Disputanta-Poe 115 kVSuspended
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-157Ladysmith CT-St. Johns 230 kVSuspended
AE1-162Smithfield 34.5 kVIn Service
AE1-173Carson-Suffolk 500 kVUnder Construction
AE1-175Light Foot 34.5 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE2-005Harmony Village-Shackleford 115 kVUnder Construction
AE2-027Harrowgate-Locks 115kVUnder Construction
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-033Clubhouse-Sapony 230 kVSuspended
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-040Sapony 34.5 kVPartially in Service - Under Construction
AE2-041Harmony Village 230 kVEngineering & Procurement
AE2-051Carson-Septa 500 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-094Carson-Rogers Road 500 kVEngineering & Procurement
AE2-104Suffolk 115 kVSuspended
AE2-156Yadkin 115 kVActive
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-346Ahoskie 34.5 kVIn Service
AF1-014Harmony Village-Shackleford 115 kVUnder Construction
AF1-017Myrtle-Windsor 115 kVEngineering & Procurement
AF1-018Harmony Village 230 kVEngineering & Procurement
AF1-028Endless Caverns 115 kVUnder Construction
AF1-032Suffolk 34.5 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-058Welco 34.5 kVIn Service
AF1-069Carson-Rogers Rd 500 kVEngineering & Procurement
AF1-114Oak Grove-Dahlgren 230 kVEngineering & Procurement
AF1-123Harper 230 kVActive
AF1-124Harper 230 kVActive
AF1-125Harper 230 kVActive
AF1-128Chesterfield 230 kVActive
AF1-129Chesterfield 230 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-292Fields 34.5kVEngineering & Procurement
AF1-294Jetersville-Ponton 115 kVActive
AF2-035St. Johns 115 kVActive
AF2-042Clover-Rawlings 500 kVActive
AF2-043Suffolk 34.5 kVIn Service
AF2-046Tunis-Mapleton 115 kVActive
AF2-054Wan 34.5 kVIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-080Chinquapin-Everetts 230 kVActive
AF2-081Moyock 230 kVActive
AF2-085Midlothian 34.5 kVIn Service
AF2-110Suffolk 115 kVSuspended
AF2-115Jetersville-Ponton 115 kVActive
AF2-120Garner-Northern Neck 115 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-222Madisonville DP-Twitty's Creek 115 kVActive
AF2-297Sedge Hill 115 kVActive
AF2-299Fields 34.5 kVActive
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-008Tunis-Mapleton 115 kVActive
AG1-021Jetersville-Ponton 115 kVActive
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-038Garner DP-Lancaster 115 kVEngineering & Procurement
AG1-082Ahoskie 34.5 kVActive
AG1-098Briery-Clover 230 kVActive
AG1-105Mount Laurel-Barnes Junction 115 kVActive
AG1-106Thelma 230 kVActive
AG1-135Garner-Lancaster 115 kVActive
AG1-145Lightfoot 34.5 kVIn Service
AG1-146Garner DP-Lancaster 115 kVActive
AG1-147Garner DP-Lancaster 115 kVActive
AG1-153Heritage 500 kVActive
AG1-166Lone Pine 115 kVActive
AG1-167Lone Pine 115 kVActive
AG1-168Lone Pine 115 kVActive
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-285Chase City-Central 115 kVActive
AG1-342Dryburg 115 kVActive
AG1-393Sapony 34.5 kVActive
AG1-394Boykins 34.5 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-551Parmele 34.5 kVActive
AG1-552Carolina 34.5 kVActive
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-005Garner DP-Lancaster 115 kVActive
AG2-068Heritage - Wake 500 kVActive
AG2-069Heritage - Wake 500 kVActive
AG2-077Clover-Rawlings 500 kVActive
AG2-086Mt. Jackson DP-Mt. Jackson 115 kVActive
AG2-088Midlothian 230 kVActive
AG2-093Colonial Trail-Hopewell 230 kVActive
AG2-095Hopewell 34.5 kV (Circuit 313)Active
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-120Everetts 34.5 kVActive
AG2-124Shackleford-Harmony 115 kVActive
AG2-151Trices Lake - James River Tap 115 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-171Lunenburg-Nutbush 115 kVActive
AG2-188Farmville - Buckingham 230 kVActive
AG2-193Turner 34.5 kVActive
AG2-198Briery - Finneywood 230 kVActive
AG2-208Greenwood DP - St. Johns DP 115 kVActive
AG2-213Gary D.P Tap - Gary D.P 115 kVActive
AG2-215Garner DP-Lancaster 115 kVActive
AG2-262Dryburg 115 kVActive
AG2-270Clover 230 kVActive
AG2-338Rogers Road - Carson 500 kVActive
AG2-339Rogers Road - Carson 500 kVActive
AG2-341Ridge Road 115 kVActive
AG2-369Heritage - Wake 500 kVActive
AG2-382Cashie 230 kVActive
AG2-426Wakefield - Waverly 115 kVActive
AG2-427Waverly 115 kVActive
AG2-428Wakefield 115 kVActive
AG2-436Carson - Rogers Road 500 kVActive
AG2-440Twittys Creek - Madisonville 115 kVActive
AG2-441Twittys Creek - Madisonville 115 kVActive
AG2-442Twittys Creek - Madisonville 115 kVActive
AG2-469Westmoreland – Oak Grove 230 kVActive
AG2-522Five Forks DP 115 kVActive
AG2-541Perth - Crystal Hill 115 kVActive
AG2-566Briery - Finneywood 230 kVActive
AG2-570Heritage - Wake 500 kVActive
AG2-571Heritage - Wake 500 kVActive
AG2-581Rawlings-Clover 500 kVActive
AG2-583Bremo - Cartersville 230 kVActive
AG2-646Chesterfield 230 kVActive
AG2-659Kerr Dam – Hawtree 115 kVActive
AG2-661Hopewell - Colonial Trail 230 kVActive
AH1-012Louisa - North Anna 230 kVActive
AH1-033Sligo 34.5 kVActive
AH1-035Plymouth 34.5 kVActive
AH1-040Mackeys - Creswell 115 kVActive
AH1-042Providence Forge-Turner 115kVActive
AH1-056Red House DP 115kVActive
AH1-065Hopewell 34.5kVActive
AH1-066Hopewell 34.5kVActive
AH1-071Midlothian 34.5 kVActive
AH1-106Winterpock 34.5kVActive
AH1-107Winterpock 34.5kVActive
AH1-108Spruance NUG 230 kVActive
AH1-138Penniman 34.5 kVActive
AH1-170Columbia DP 115kVActive
AH1-215Central VA-Twitty 115 kVActive
AH1-216Smithfield-Surry 230 kVActive
AH1-217Kidds Store - Fork Union 115 kV IIActive
AH1-241Cobbs Creek - James River Industrial 115kVActive
AH1-251Todds Tavern- Spotsylvania/Goldsdale 115kVActive
AH1-263Chancellor 115 kVActive
AH1-271Cashie 230 kVActive
AH1-280Jetersville-Ponton 115 kVActive
AH1-311Heartsease DP - Mayo Dunbar 115kVActive
AH1-323Elmont 230 kVActive
AH1-324Colonial Trail – Surry 230 kVActive
AH1-343Crystal Hill DP- Perth 115kVActive
AH1-377Clover- Farmville 230kVActive
AH1-396Gary 24.94 kVActive
AH1-397Shacklesford 34.5 kVActive
AH1-399North Doswell 12.5 kVActive
AH1-408Freeman DP – Lawrenceville 115 kVActive
AH1-439Buckingham- Farmville 230kVActive
AH1-528Rawlings - Unity 500 kVActive
AH1-546Bremo - Buckingham 230 kVActive
AH1-637Oak Grove 34.5 kVActive
AH1-676Gordonsville 230 kVActive
AH1-677Rogers Road 500 kVActive
AH1-678Heritage 500 kVActive
AH1-679Four Rivers 230 kVActive
AH1-681Cunningham 500 kVActive
AH1-682Ladysmith CT 230 kVActive
AH1-683Ladysmith CT 230 kVActive
AH1-687Bear Garden 230kVActive
AH1-691Ladysmith CT 230 kVActive
AH1-692Ladysmith CT 230 kVActive
AH1-694Ladysmith CT 230 kVActive
AH1-712Cunningham 500 kVActive
AH1-716Surry-Skiffes Creek 500kVActive
AH1-717Surry 230kVActive
AH1-723Cunningham 500 kVActive
V4-068Murphy's 34.5kVIn Service
Y1-086Morgans CornerIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-044Whitakers 34.5kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-384 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
Dominion(Pending) / TC2-PH1-DOM-0048Replace 2-1590 AAC line lead on Line 259 at Basin 230 kV$43,897
Grand Total:$43,897

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0048
Title
Replace 2-1590 AAC line lead on Line 259 at Basin 230 kV
Description
Replace 2-1590 AAC line lead on Line 259 at Basin 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$43,897
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-068
5.7 MW3.5%$17,255
AG2-069
8.5 MW5.2%$25,884
AG2-077
9.9 MW6.0%$29,905
AG2-093
11.1 MW6.7%$33,604
AG2-384
14.5 MW8.8%$43,897
AG2-427
8.7 MW5.3%$26,484
AG2-428
15.8 MW9.6%$47,860
AG2-436
31.1 MW18.9%$94,366
AG2-570
22.9 MW13.9%$69,363
AG2-571
2.9 MW1.8%$8,781
AG2-581
8.5 MW5.2%$25,760
AH1-528
17.9 MW10.9%$54,374
AH1-717
7.4 MW4.5%$22,467

System Reinforcement: n9112.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9112.0 / TC1-PH2-DOM-063
Title
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Description
Wreck and Rebuild 12.4 miles of 230 kV line 259 with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @ 250 degrees C and replace line lead at Chesterfield.
Total Cost ($USD)
$87,030,447
Allocated Cost ($USD)
$0
Time Estimate
46 to 47 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9265.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9265.0 / TC1-PH2-DOM-064
Title
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Description
Replace 230 kV wave trap 259WT at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$396,021
Allocated Cost ($USD)
$0
Time Estimate
14 to 15 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9266.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9266.0 / TC1-PH2-DOM-065
Title
Replace switches 25944 and 25945 at Basin 230 kV (Basin - Chesterfield B).
Description
Replace switches 25944 and 25945 at Basin 230 kV (Basin - Chesterfield B).
Total Cost ($USD)
$701,120
Allocated Cost ($USD)
$0
Time Estimate
38 to 39 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 may need this upgrade in-service to be deliverable to the PJM system. If AG2-384 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
6BASIN-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2065
Title
Replace switches 219324 and 219325 at Bremo 230 kV
Description
Replace switches 219324 and 219325 at Bremo 230 kV
Total Cost ($USD)
$800,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n8238
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8238 / dom-294
Title
Wreck and rebuild 1.41 miles of 230 kV Line 217 between Charles City Road and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 1.41 miles of 230 kV Line 217 between Charles City Road and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$5,358,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARCTY-6VARINA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7568
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7568 / dom-369-TC2
Title
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Description
Wreck and rebuild 6.47 miles of 230 kV transmission line 2028 between Charlottesville and Mt. Eagle with (2) 768.2 ACSS/TW (20/7) ""Maumee"" @ 250C and replace line lead at Mt. Eagle.
Total Cost ($USD)
$36,802,018
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC1-PH3-DOM-007
Title
Replace Wave Trap 2028WT at Charlottesville
Description
Replace Wave Trap 2028WT at Charlottesville
Total Cost ($USD)
$400,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-2072
Title
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Description
Replace 2500 ACAR line lead on line 2028 at Charlottesville 230 kV
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHARLVL-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0050
Title
Wreck and rebuild 13.78 miles of 230 kV Line 287 between Chesterfield and Chickahominy with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 13.78 miles of 230 kV Line 287 between Chesterfield and Chickahominy with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$52,364,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6CHCKAHM-6CHESTF A 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9203.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9203.0 / TC1-PH2-DOM-008-TC2
Title
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Description
Wreck and rebuild 10.74 miles of line 2028 between Fork Union and Cunningham (Grape Vine) with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C.
Total Cost ($USD)
$29,539,973
Allocated Cost ($USD)
$0
Time Estimate
45 to 46 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6FORK UNION 230.0 kV Ckt 1 line(Any)

System Reinforcement: n7569
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n7569 / dom-490-TC2
Title
Upgrade a 3.78 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine Substations at structure 2080/73.
Description
Uograde 3.78 miles of transmission line 2028 between Mt. Eagle and Grape Vine with (2) 768.2 ACSS/TW (20/7) ""MAUMEE"". The segment runs from Mt Eagle to structure 2080/73.
Total Cost ($USD)
$13,360,242
Allocated Cost ($USD)
$0
Time Estimate
43 to 44 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9644.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9644.0 / TC1-PH3-DOM-006-TC2
Title
Upgrade a 2.73 mile segment of 230kV transmission line 2028 between Mt. Eagle and Grape Vine. This segment runs from Grape Vine substation to structure 2080/73.
Description
Rebuild a 2.73 mile segment of 230kV line 2028 between Mt. Eagle and Grape Vinew with (2) 768.2 ACSS/TW (20/7) "MAUMEE" conductor @250 degrees C.
Total Cost ($USD)
$8,415,380
Allocated Cost ($USD)
$0
Time Estimate
Mar 31 2029

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6GRAPEVINE-6MTEAGLE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0049
Title
Wreck and rebuild 12.98 miles of 230 kV Line 283 between Elmont and Northeast with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees
Description
Wreck and rebuild 12.98 miles of 230 kV Line 283 between Elmont and Northeast with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees
Total Cost ($USD)
$49,324,000
Allocated Cost ($USD)
$0
Time Estimate
42 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6ELMONT-6NRTHEST 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9199.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9199.0 / TC1-PH2-DOM-004
Title
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Description
Wreck and rebuild 1.63 miles of line 2193 between Fork Union and Bremo with (2) 768.2 ACSS/TW (20/7) "MAUMEE" @ 250C and replace line lead at Bremo.
Total Cost ($USD)
$7,947,612
Allocated Cost ($USD)
$0
Time Estimate
42 to 43 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9198.0
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n9198.0 / TC1-PH2-DOM-003-TC2
Title
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Description
Replace Circuit Breaker 219322 and Circuit Breaker Lead at Bremo 230 kV (Bremo - Fork Union).
Total Cost ($USD)
$2,113,879
Allocated Cost ($USD)
$0
Time Estimate
40 to 41 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6FORK UNION-6BREMODIST 230.0 kV Ckt 1 line(Any)
6BREMODIST-6BREMO 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: n8239
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
n8239 / dom-300
Title
Wreck and rebuild 8.84 miles of 230 kV Line 217 between Chesterfield and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Description
Wreck and rebuild 8.84 miles of 230 kV Line 217 between Chesterfield and Varina with (2) 768.2 ACSS/TW (20/7) "MAUMEE" at 250 degrees C.
Total Cost ($USD)
$33,592,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
6VARINA-6CHESTF B 230.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0075
Title
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Description
Wreck and rebuild 18.75 miles of 500 kV Line 594 between Spotsylvania and Morrisville with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN"
Total Cost ($USD)
$110,625,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P2-2: MORRISVILLE B1_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: 545T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H1T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P4-2: H3T552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 550_SRT-A

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0076
Title
Replace Wave Trap 594WT at Morrisville 500 KV
Description
Replace Wave Trap 594WT at Morrisville 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0077
Title
Replace Wave Trap 594WT at Spotsylvania 500 KV
Description
Replace Wave Trap 594WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0078
Title
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Description
Replace 3-1590 AAC 61 line lead on Line 594 at Morrisville 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-384 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-384 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 line(Any)
8MORRSVL-8SPOTSYL 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0071
Title
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Description
Wreck and rebuild 14.02 miles of 500 kV Line 573 between Spotsylvania and North Anna with (3) 1351.5 ACSS TW/HS285 (42/19) "MARTIN".
Total Cost ($USD)
$82,718,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 552_SRT-S
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0072
Title
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Description
Replace 2-2500 ACAR 84/7 line lead on Line 573 at North Anna 500 kV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
12 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S

System Reinforcement
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
(Pending) / TC2-PH1-DOM-0073
Title
Replace Wave Trap 573WT at Spotsylvania 500 KV
Description
Replace Wave Trap 573WT at Spotsylvania 500 KV
Total Cost ($USD)
$600,000
Allocated Cost ($USD)
$0
Time Estimate
16 to 18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-384 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-384 could receive cost allocation. Although AG2-384 may not presently have cost responsibility for this upgrade, AG2-384 is a potential Aggregate Pool Contributor.

FacilityContingency
8NO ANNA-8SPOTSYL 500.0 kV Ckt 1 lineDVP_P1-2: LN 581_SRT-S
          AG2-068 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-068, AG2-069, AG2-369
        
          AG2-570 500 kV - Dominion: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-570, AG2-571
        

Attachments

AG2-384 One Line Diagram

AG2-384 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.