AG2-411 Phase I Study Report

v1.00 released 2025-10-29 22:08

Statler Hill 115 kV

40.7 MW Capacity / 63.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Iris Energy LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Mid-Atlantic Interstate Transmission, LLC.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the Mid-Atlantic Interstate Transmission, LLC zone — Somerset County, Pennsylvania. The installed facilities will have a total capability of 63.0 MW with 40.7 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-411
Project Name:
Statler Hill 115 kV
Project Developer Name:
Iris Energy LLC
State:
Pennsylvania
County:
Somerset
Transmission Owner:
Mid-Atlantic Interstate Transmission, LLC
MFO:
63.0
MWE:
63.0
MWC:
40.7
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-411 will interconnect on the Mid-Atlantic Interstate Transmission, LLC transmission system at the Statler Hill 115 kV substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-411 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-411Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$823,627$0
Other Scope$59,600$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$3,550,485$3,550,485
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$10,098,813$10,098,813
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$14,532,525$13,649,298

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-411

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-411 Project due at DP1
ABA - B
AG2-411$1,364,930$252,000$1,112,930

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Construction of one (1) span of conductor from the existing substation to the developer owned dead end structure at the Point of Change in Ownership.$761,047 $761,047
(Pending)Integrate interconnection facilities protection and controls to the Transmission Owner system.$62,580 $62,580
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Expand the existing Statler Hill substation, and add one (1) new circuit breaker with SCADA controls.$3,550,485 $3,550,485
Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Install 115 kV revenue metering within existing substation.$59,600 $59,600

Based on the scope of work for the Interconnection Facilities, it is expected to take 38 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

FE performed an analysis of its underlying transmission system <100 kV. New Service Request Project AG2-411 did not contribute to any overloads on the FE transmission <100 kV system.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. FirstEnergy interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-411 was evaluated as a 63.0 MW (40.7 MW Capacity) injection in the PENELEC area.

AG2-411 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 63.0 MW (63.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
PN_P2-3_PN-345-997-DRT-031_SRT-SL
BreakerAC102.96 %659.0B678.54.08
GD2AP
01CARLOS-01DANSMTN 138.0 kV Ckt 1 line
AP_P2-3_MP-138-150_SRT-A
BreakerAC102.79 %206.0B211.753.96
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT45_SRT-SL
BreakerAC139.19 %192.0B267.243.03
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-138-338_SRT-A
BreakerAC138.63 %192.0B266.173.48
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-138-18201_SRT-A
BreakerAC136.64 %192.0B262.362.84
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-138-182_SRT-A
BreakerAC136.64 %192.0B262.362.84
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-3_WP-138-181T_SRT-A
BreakerAC136.64 %192.0B262.362.84
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-2_WP-138-0582-1_SRT-A
BusAC136.63 %192.0B262.322.84
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC134.28 %192.0B257.823.29
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-050_SRT-A
TowerAC130.89 %192.0B251.32.98
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P2-2_MP-138-100_SRT-A
BusAC126.79 %192.0B243.443.0
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
PN_P2-2_PN-115-001B_SRT-A
BusAC123.4 %192.0B236.933.0
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P1-2_WP-500-008_SRT-A
SingleAC122.67 %192.0B235.522.27
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
PN_P2-2_PN-115-021_SRT-A
BusAC118.41 %192.0B227.352.72
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P1-2_WP-138-056_SRT-A
SingleAC113.79 %192.0B218.472.62
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC113.53 %192.0B217.982.79
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
PN_P2-3_PN-230-0252-C_SRT-A
BreakerAC116.04 %179.0B207.716.01
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
PN_P2-3_PN-230-0252-B_SRT-A
BreakerAC116.04 %179.0B207.716.01
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P2-3_PE-500-014_SRT-SL
BreakerAC113.79 %179.0B203.695.5
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC112.74 %179.0B201.85.5
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
PN_P2-2_PN-500-001T_SRT-A
BusAC112.69 %179.0B201.725.98
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P7-1_MP-138-018_SRT-SL
TowerAC109.24 %179.0B195.535.38
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
PN_P2-3_PN-230-0183-209_SRT-A
BreakerAC108.31 %179.0B193.876.17
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P2-2_MP-138-001_SRT-A
BusAC106.53 %179.0B190.695.41
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P2-2_WP-500-DRT16_SRT-SL
BusAC105.65 %179.0B189.125.6
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
PN_P2-2_PN-115-073_SRT-A
BusAC105.11 %179.0B188.155.33
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P2-2_WP-138-033T_SRT-A
BusAC104.92 %179.0B187.85.67
GD2AP
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
AP_P7-1_MP-138-056_SRT-A-1
TowerAC104.77 %179.0B187.535.45
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT45_SRT-SL
BreakerAC143.1 %192.0B274.743.03
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-138-338_SRT-A
BreakerAC142.49 %192.0B273.573.48
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-138-18201_SRT-A
BreakerAC141.35 %192.0B271.392.84
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-138-182_SRT-A
BreakerAC141.35 %192.0B271.392.84
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-3_WP-138-181T_SRT-A
BreakerAC141.35 %192.0B271.382.84
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-2_WP-138-0582-1_SRT-A
BusAC141.33 %192.0B271.362.84
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC137.05 %192.0B263.143.29
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-2_MP-138-100_SRT-A
BusAC130.29 %192.0B250.153.0
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P1-2_WP-500-008_SRT-A
SingleAC126.74 %192.0B243.342.27
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
PN_P2-2_PN-115-021_SRT-A
BusAC121.77 %192.0B233.82.72
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P1-2_WP-138-056_SRT-A
SingleAC117.96 %192.0B226.472.62
GD2AP/PENELEC
26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC114.88 %294.0B337.745.91
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-B_SRT-A
BreakerAC106.31 %1001.0B1064.1717.12
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-C_SRT-A
BreakerAC106.31 %1001.0B1064.1717.12
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0252-A_SRT-A
BreakerAC106.31 %1001.0B1064.1617.12
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC104.94 %1001.0B1050.4217.02
GD2PENELEC/PJM
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
PN_P2-3_PN-230-0183-208_SRT-A
BreakerAC103.22 %1001.0B1033.2615.93
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC127.67 %160.0B204.275.5
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT19_SRT-SL
BreakerAC126.37 %160.0B202.195.5
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC125.63 %160.0B201.015.98
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT45_SRT-SL
BreakerAC123.77 %160.0B198.035.63
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P7-1_MP-138-018_SRT-SL
TowerAC121.88 %160.0B195.05.38
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_MP-138-150_SRT-A
BreakerAC119.76 %160.0B191.614.17
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-115-3A2_SRT-A
BreakerAC119.35 %160.0B190.975.87
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-2_MP-138-001_SRT-A
BusAC118.65 %160.0B189.835.41
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT16_SRT-SL
BusAC117.75 %160.0B188.45.6
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-2_PN-115-073_SRT-A
BusAC117.15 %160.0B187.445.33
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-2_WP-138-033T_SRT-A
BusAC116.93 %160.0B187.085.67
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P7-1_MP-138-056_SRT-A-1
TowerAC116.71 %160.0B186.735.45
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Base Case
SingleAC108.67 %133.0A144.534.13
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-2
SingleAC106.19 %160.0B169.914.13
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P1-2_PE-500-004_SRT-SL-1
SingleAC104.91 %160.0B167.864.13
GD2PENELEC
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-C_SRT-A
BreakerAC104.58 %179.0B187.216.01
GD2PENELEC
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-A_SRT-A
BreakerAC104.58 %179.0B187.216.01
GD2PENELEC
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-B_SRT-A
BreakerAC104.58 %179.0B187.216.01
GD2PENELEC
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC103.93 %179.0B186.036.01
GD2PENELEC
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC103.27 %179.0B184.855.51
GD2PENELEC
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC101.4 %179.0B181.515.99
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-2_SRT-A
BreakerAC132.2 %980.0B1295.5517.56
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-500-003JT_SRT-A
BreakerAC131.02 %980.0B1284.0218.03
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC131.02 %980.0B1284.0218.03
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-A_SRT-A
BreakerAC131.01 %980.0B1283.8516.66
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC121.6 %980.0B1191.6413.97
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC121.6 %980.0B1191.6413.97
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P2-2_WP-138-059_SRT-A
BusAC112.4 %980.0B1101.5113.56
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P2-2_PN-115-016A_SRT-A
BusAC109.01 %980.0B1068.2915.02
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC108.9 %980.0B1067.213.29
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P2-2_MP-138-100_SRT-A
BusAC108.04 %980.0B1058.7514.34
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT18_SRT-A
BusAC106.12 %980.0B1040.0112.91
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC105.44 %980.0B1033.2713.55
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC105.43 %980.0B1033.2513.55
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-051A_SRT-A
TowerAC104.72 %980.0B1026.2213.05
GD2PENELEC
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Base Case
SingleAC100.25 %809.0A811.029.71
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-DRT27_SRT-SL
BreakerAC118.81 %639.0B759.2310.29
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-004-DRT-003_SRT-SL
BreakerAC118.81 %639.0B759.2310.29
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-DRT26_SRT-SL
BreakerAC118.75 %639.0B758.8110.29
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-004-DRT-004_SRT-SL
BreakerAC118.75 %639.0B758.810.29
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-2_PN-500-004A-DRT_SRT-SL
BusAC112.01 %639.0B715.7710.3
GD2PENELEC
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
PN_P2-3_PN-500-DRT33_SRT-SL
BreakerAC111.27 %639.0B711.029.71
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-A_SRT-A
BreakerAC156.72 %618.0B968.545.2
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-B_SRT-A
BreakerAC156.7 %618.0B968.435.21
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT31_SRT-SL
BreakerAC155.32 %618.0B959.885.19
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-008_SRT-SL
BreakerAC155.32 %618.0B959.885.19
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-3_PN-115-0331-D_SRT-A
BreakerAC154.64 %618.0B955.665.2
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-115-030_SRT-A
BusAC149.64 %618.0B924.755.22
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-115-031_SRT-A
BusAC144.8 %618.0B894.875.09
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC142.79 %618.0B882.466.02
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
AP_P2-2_WP-138-074_SRT-A
BusAC136.41 %618.0B843.024.79
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_08_P22_102799_SRT-A
BusAC136.19 %618.0B841.644.67
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_48_P71_102649_SRT-A
TowerAC135.55 %618.0B837.694.67
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT
TowerAC135.09 %618.0B834.834.67
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Base Case
SingleAC131.72 %493.0A649.43.51
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PN_P1-2_PN-115-094_A_SRT-A
SingleAC127.45 %618.0B787.653.91
GD2PENELEC/PL
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
PL_10_P12_000085_SRT-A
SingleAC127.27 %618.0B786.53.71
GD2PENELEC
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-B_SRT-A
BreakerAC104.96 %179.0B187.886.01
GD2PENELEC
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-C_SRT-A
BreakerAC104.96 %179.0B187.886.01
GD2PENELEC
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0252-A_SRT-A
BreakerAC104.96 %179.0B187.886.01
GD2PENELEC
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
PN_P2-3_PN-230-0201A-20_SRT-A
BreakerAC104.3 %179.0B186.76.0
GD2PENELEC
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
AP_P2-3_PE-500-014_SRT-SL
BreakerAC103.66 %179.0B185.565.51
GD2PENELEC
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC101.77 %179.0B182.175.99
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-2_SRT-A
BreakerAC133.95 %980.0B1312.7119.09
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-500-003JT_SRT-A
BreakerAC133.46 %980.0B1307.8819.3
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-2_PN-500-001T_SRT-A
BusAC133.46 %980.0B1307.8819.3
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P2-3_PN-230-0347-A_SRT-A
BreakerAC133.4 %980.0B1307.3418.49
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041D_SRT-A
BreakerAC122.69 %980.0B1202.415.01
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
ATSI_P2-3_CEI-345-041E_SRT-A
BreakerAC122.69 %980.0B1202.415.01
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_WP-138-033T_SRT-A
BusAC110.79 %980.0B1085.7715.45
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_WP-138-059_SRT-A
BusAC110.5 %980.0B1082.9314.45
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_MP-138-100_SRT-A
BusAC108.43 %980.0B1062.6115.45
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P2-2_WP-138-036_SRT-A
BusAC108.01 %980.0B1058.4814.49
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-053A_SRT-A
TowerAC107.82 %980.0B1056.614.26
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
AP_P7-1_WPP-138-083_SRT-A
TowerAC105.56 %980.0B1034.4614.49
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-2_PN-230-025_SRT-A
SingleAC104.25 %980.0B1021.6514.5
GD2PENELEC
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
PN_P1-3_PN-500-003_SRT-A
SingleAC104.25 %980.0B1021.6314.5
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-DRT27_SRT-SL
BreakerAC119.18 %639.0B761.5910.29
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-004-DRT-003_SRT-SL
BreakerAC119.18 %639.0B761.5810.29
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-DRT26_SRT-SL
BreakerAC119.09 %639.0B761.010.29
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-004-DRT-004_SRT-SL
BreakerAC119.09 %639.0B760.9910.29
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-2_PN-500-004A-DRT_SRT-SL
BusAC112.2 %639.0B716.9910.3
GD2PENELEC/PJM
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
PN_P2-3_PN-500-DRT33_SRT-SL
BreakerAC111.54 %639.0B712.749.71
GD2AP/PJM
KEYSTONE-01CABOT 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT45_SRT-SL
BreakerAC108.06 %2844.0B3073.329.34
GD2AP/PJM
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT32_SRT-A
BreakerAC107.79 %2078.0B2239.819.3
GD2AP/PJM
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-002_SRT-SL
BreakerAC107.79 %2078.0B2239.819.3

Details for 01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer l/o PN_P2-3_PN-345-997-DRT-031_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01ARMSTRONG-01ARMSTR 345.0/138.0 kV Ckt 2 transformer
Contingency Name:
PN_P2-3_PN-345-997-DRT-031_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.96 %
Rating:659.0 MVA
Rating Type:B
MVA to Mitigate:678.5
MW Contribution:4.08
Bus #Bus NameTypeMW Contribution
20082926HNSMLK 2
50/50
21.026
20083126HNSMLK 4
50/50
21.026
20334926Z1-069 C
Solar/Wind Harmer
1.642
944411AF1-106 GEN
Solar/Wind Harmer
0.163
971703AH1-357 GEN
Solar/Wind Harmer
1.356
971707AH1-359 GEN
Solar/Wind Harmer
1.356
203841AF2-001_GEN
Solar/Wind Harmer
1.306
970335AG2-220 GEN
Solar/Wind Harmer
2.006
971127AH1-005 GEN
Solar/Wind Harmer
1.294
971879AH1-460 GEN
Solar/Wind Harmer
4.261
970125AG2-091 GEN
Solar/Wind Harmer
0.384
971419AH1-201 GEN
Solar/Wind Harmer
1.842
20079426CONEMAGH
Adder
0.668
20328326MANOR_T86
Adder
0.068
20089126CSLMN_L13
Solar/Wind Harmer
0.422
20089026BF_G21_K23
Solar/Wind Harmer
0.334
20335126GROZ1-110
Adder
1.058
20335226CANZ2-011
Adder
1.028
959441AF2-235 GEN
Solar/Wind Helper
0.184
20080926SITHE
50/50
0.239
20398826ARMNA MT
Solar/Wind Harmer
1.738
203859AF2-294 C
Solar/Wind Harmer
1.155
972077AH1-588 GEN
Solar/Wind Harmer
16.27
972079AH1-589 GEN
Solar/Wind Harmer
13.4
970715AG2-457 GEN
Solar/Wind Harmer
5.423
203839AF1-321 GEN
Solar/Wind Harmer
1.306
20084626FORWARD
Solar/Wind Harmer
0.513
970313AG2-206 GEN
Solar/Wind Harmer
3.085
203857AF2-221 C
Solar/Wind Harmer
0.96
970123AG2-090 GEN
Solar/Wind Harmer
0.896
20088626ARWF_N39
Solar/Wind Harmer
1.105
20303426NA_O38_P22
Solar/Wind Harmer
0.894
20088926STNY CRK
Solar/Wind Harmer
0.709
971427AH1-205 GEN
Solar/Wind Harmer
0.857
20083426SW_E13_K22
Solar/Wind Harmer
0.171
203940AF1-140 C
Solar/Wind Harmer
0.275
971441AH1-212 GEN
Solar/Wind Harmer
1.004
972075AH1-587 GEN
Solar/Wind Harmer
9.648
944781AF1-143 GEN
Solar/Wind Harmer
1.447
946381AF1-302 GEN
Solar/Wind Helper
0.342
238217AF1-153 C O1
Solar/Wind Helper
0.126
20082826HNSMLK 1
50/50
21.026
20083026HNSMLK 3
50/50
21.026
20335026MILZ1-092
Adder
1.649
944411AF1-106 GEN
Solar/Wind Harmer
1.519
20326126BLOSSBCT
Adder
1.564
970713AG2-456 GEN
Solar/Wind Harmer
5.423
971705AH1-358 GEN
Solar/Wind Harmer
1.577
971709AH1-360 GEN
Solar/Wind Harmer
1.577
959471AF2-238 GEN
Solar/Wind Harmer
0.397
970337AG2-221 GEN
Solar/Wind Harmer
1.313
203843AF2-002_GEN
Solar/Wind Harmer
0.653
970631AG2-411 GEN
Solar/Wind Harmer
4.085
970511AG2-327 GEN
Solar/Wind Harmer
0.643
957561AF2-050 GEN
Solar/Wind Harmer
3.149
20088826HIGHLAND
Solar/Wind Harmer
0.983
971423AH1-203 GEN
Solar/Wind Harmer
4.045
964201AG1-281 GEN
Solar/Wind Harmer
0.315
20089226LOOKOUT
Solar/Wind Harmer
0.411
203860AG1-193 C
Solar/Wind Helper
0.159
20083226HNSMLK 5
50/50
21.026
20083926HOMER C3
50/50
137.1
20083826HOMER C2
50/50
129.507
20083726HOMER C1
50/50
74.399
940863AE2-074 GEN
Solar/Wind Harmer
1.3
970555AG2-356 GEN
Solar/Wind Harmer
1.313
203961AE2-224 GEN
Solar/Wind Harmer
1.908
20092526R32
Solar/Wind Harmer
1.054
203844AF2-092 C
Solar/Wind Harmer
0.698
203850AG1-041 C
Solar/Wind Harmer
0.692
203926AA2-133 GEN
Adder
1.045
20091526CHSTN_FL
Solar/Wind Harmer
0.391
203846AF2-130 C
Solar/Wind Helper
0.558
961581Q1080_CY23
External Queue
23.753013610839844
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.387
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.201
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
8.066
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.14
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.728
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.196
G-007ALTFEXP_G-007A->PJM
CMTX
2.924
CBM NorthLTFEXP_CBM-N->PJM
CBM
19.877
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01CARLOS-01DANSMTN 138.0 kV Ckt 1 line l/o AP_P2-3_MP-138-150_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01CARLOS-01DANSMTN 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-150_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.79 %
Rating:206.0 MVA
Rating Type:B
MVA to Mitigate:211.75
MW Contribution:3.96
Bus #Bus NameTypeMW Contribution
20084126DEEPCRK2
50/50
0.302
20084026DEEPCRK1
50/50
0.299
203955AF1-039 C O1
Solar/Wind Harmer
1.321
944781AF1-143 GEN
Solar/Wind Harmer
5.901
238120AE2-309 GEN
Solar/Wind Harmer
0.812
20083426SW_E13_K22
Solar/Wind Harmer
0.351
971427AH1-205 GEN
Solar/Wind Harmer
1.387
20088926STNY CRK
Solar/Wind Harmer
1.138
203839AF1-321 GEN
Solar/Wind Harmer
1.27
20084626FORWARD
Solar/Wind Harmer
0.496
203857AF2-221 C
Solar/Wind Harmer
0.781
970123AG2-090 GEN
Solar/Wind Harmer
0.729
203940AF1-140 C
Solar/Wind Harmer
0.22
203844AF2-092 C
Solar/Wind Harmer
0.716
203850AG1-041 C
Solar/Wind Harmer
0.678
20092526R32
Solar/Wind Harmer
0.751
20083726HOMER C1
Adder
13.149
202652Y1-033 WT C
Solar/Wind Harmer
2.713
20089126CSLMN_L13
Solar/Wind Harmer
1.722
20089026BF_G21_K23
Solar/Wind Harmer
1.363
971419AH1-201 GEN
Solar/Wind Harmer
2.982
203841AF2-001_GEN
Solar/Wind Harmer
1.27
971879AH1-460 GEN
Solar/Wind Harmer
3.761
970125AG2-091 GEN
Solar/Wind Harmer
0.313
238127S14_GEN_2
Solar/Wind Helper
1.202
238118U2-030_1
Solar/Wind Helper
0.299
20081326YOUGH
50/50
0.129
970995AG2-615 GEN
Solar/Wind Harmer
55.364
20089226LOOKOUT
Solar/Wind Harmer
1.676
971423AH1-203 GEN
Solar/Wind Harmer
7.119
203843AF2-002_GEN
Solar/Wind Harmer
0.635
970631AG2-411 GEN
Solar/Wind Harmer
3.955
20088826HIGHLAND
Solar/Wind Harmer
0.7
235531U2-073 GEN
Solar/Wind Helper
2.858
238117U2-030
Solar/Wind Helper
0.299
20083926HOMER C3
Adder
11.468
20083826HOMER C2
Adder
10.833
238126S14_GEN_1
Solar/Wind Helper
1.202
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.047
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.149
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.854
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.078
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.25
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.144
G-007ALTFEXP_G-007A->PJM
CMTX
0.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.581
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT45_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT45_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.19 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:267.24
MW Contribution:3.03
Bus #Bus NameTypeMW Contribution
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
69.932
971321AH1-140 GEN
Solar/Wind Harmer
13.553
20092526R32
Solar/Wind Harmer
0.862
203850AG1-041 C
Solar/Wind Harmer
0.565
203844AF2-092 C
Solar/Wind Harmer
0.563
20091526CHSTN_FL
Solar/Wind Harmer
0.389
20083726HOMER C1
Adder
27.064
20083926HOMER C3
Adder
24.703
20083826HOMER C2
Adder
23.335
971279AH1-102 GEN
Solar/Wind Harmer
5.111
20094526CT_V3-030
Solar/Wind Harmer
0.379
20088826HIGHLAND
Solar/Wind Harmer
0.804
203843AF2-002_GEN
Solar/Wind Harmer
0.485
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.778
971541AH1-268 GEN
Solar/Wind Harmer
2.175
970899AG2-561 GEN
Solar/Wind Harmer
1.206
203818AF1-086 GEN
Solar/Wind Harmer
1.326
970125AG2-091 GEN
Solar/Wind Harmer
0.297
971879AH1-460 GEN
Solar/Wind Harmer
3.239
203841AF2-001_GEN
Solar/Wind Harmer
0.971
945751AF1-240 GEN
Solar/Wind Harmer
0.705
971419AH1-201 GEN
Solar/Wind Harmer
1.401
960051AF2-296 GEN
Solar/Wind Harmer
0.864
237043AE2-125 C
Solar/Wind Helper
0.299
946071AF1-272 GEN
Solar/Wind Harmer
2.794
971441AH1-212 GEN
Solar/Wind Harmer
1.002
203857AF2-221 C
Solar/Wind Harmer
0.742
970123AG2-090 GEN
Solar/Wind Harmer
0.693
203839AF1-321 GEN
Solar/Wind Harmer
0.971
20084626FORWARD
Solar/Wind Harmer
0.38
203940AF1-140 C
Solar/Wind Harmer
0.235
20088926STNY CRK
Solar/Wind Harmer
0.54
971427AH1-205 GEN
Solar/Wind Harmer
0.652
203853AF1-134 C O1
Solar/Wind Harmer
0.261
972077AH1-588 GEN
Solar/Wind Harmer
6.53
972079AH1-589 GEN
Solar/Wind Harmer
5.378
23652301WDPWR_K20
Solar/Wind Helper
0.123
970631AG2-411 GEN
Solar/Wind Harmer
3.028
964201AG1-281 GEN
Solar/Wind Harmer
0.27
971423AH1-203 GEN
Solar/Wind Harmer
3.042
237046AF1-021 C
Solar/Wind Helper
0.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.326
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.013
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.538
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.479
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.304
G-007ALTFEXP_G-007A->PJM
CMTX
2.369
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.192
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-338_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-338_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:138.63 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:266.17
MW Contribution:3.48
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.03
20079426CONEMAGH
Adder
0.939
971541AH1-268 GEN
Solar/Wind Harmer
2.587
970899AG2-561 GEN
Solar/Wind Harmer
1.408
203818AF1-086 GEN
Solar/Wind Harmer
1.502
970125AG2-091 GEN
Solar/Wind Harmer
0.342
971879AH1-460 GEN
Solar/Wind Harmer
3.731
203841AF2-001_GEN
Solar/Wind Harmer
1.12
971419AH1-201 GEN
Solar/Wind Harmer
1.628
960051AF2-296 GEN
Solar/Wind Harmer
0.934
945751AF1-240 GEN
Solar/Wind Harmer
0.714
237043AE2-125 C
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Harmer
3.5
971441AH1-212 GEN
Solar/Wind Harmer
1.146
203857AF2-221 C
Solar/Wind Harmer
0.854
970123AG2-090 GEN
Solar/Wind Harmer
0.797
203839AF1-321 GEN
Solar/Wind Harmer
1.12
20084626FORWARD
Solar/Wind Harmer
0.437
203940AF1-140 C
Solar/Wind Harmer
0.268
20088926STNY CRK
Solar/Wind Harmer
0.627
971427AH1-205 GEN
Solar/Wind Harmer
0.757
20083426SW_E13_K22
Solar/Wind Harmer
0.147
203853AF1-134 C O1
Solar/Wind Harmer
0.282
972077AH1-588 GEN
Solar/Wind Harmer
5.735
972079AH1-589 GEN
Solar/Wind Harmer
4.724
23652301WDPWR_K20
Solar/Wind Helper
0.095
20215826CON.GEN1
50/50
0.014
20063626IUP CO-G
50/50
0.08
971321AH1-140 GEN
Solar/Wind Harmer
81.927
971321AH1-140 GEN
Solar/Wind Harmer
15.877
20092526R32
Solar/Wind Harmer
0.986
203850AG1-041 C
Solar/Wind Harmer
0.647
203844AF2-092 C
Solar/Wind Harmer
0.646
20091526CHSTN_FL
Solar/Wind Harmer
0.432
203961AE2-224 GEN
Solar/Wind Harmer
1.305
20083726HOMER C1
Adder
27.287
20083926HOMER C3
Adder
22.644
20083826HOMER C2
Adder
21.39
971279AH1-102 GEN
Solar/Wind Harmer
6.08
20094526CT_V3-030
Solar/Wind Harmer
0.435
20088826HIGHLAND
Solar/Wind Harmer
0.92
203843AF2-002_GEN
Solar/Wind Harmer
0.56
970631AG2-411 GEN
Solar/Wind Harmer
3.485
971423AH1-203 GEN
Solar/Wind Harmer
3.547
964201AG1-281 GEN
Solar/Wind Harmer
0.303
957561AF2-050 GEN
Solar/Wind Harmer
2.154
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.243
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.757
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.494
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.12
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.094
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
G-007ALTFEXP_G-007A->PJM
CMTX
1.63
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-18201_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-18201_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.36
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-182_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-182_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.36
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-181T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-181T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:136.64 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.36
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-0582-1_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-0582-1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.63 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:262.32
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:134.28 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:257.82
MW Contribution:3.29
Bus #Bus NameTypeMW Contribution
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
70.772
971321AH1-140 GEN
Solar/Wind Harmer
13.716
20092526R32
Solar/Wind Harmer
0.942
203850AG1-041 C
Solar/Wind Harmer
0.616
203844AF2-092 C
Solar/Wind Harmer
0.614
20091526CHSTN_FL
Solar/Wind Harmer
0.418
203961AE2-224 GEN
Solar/Wind Harmer
1.35
20083726HOMER C1
Adder
28.212
20083926HOMER C3
Adder
25.532
20083826HOMER C2
Adder
24.118
971279AH1-102 GEN
Solar/Wind Harmer
5.453
20094526CT_V3-030
Solar/Wind Harmer
0.401
20088826HIGHLAND
Solar/Wind Harmer
0.879
203843AF2-002_GEN
Solar/Wind Harmer
0.528
970631AG2-411 GEN
Solar/Wind Harmer
3.294
964201AG1-281 GEN
Solar/Wind Harmer
0.292
971423AH1-203 GEN
Solar/Wind Harmer
3.344
957561AF2-050 GEN
Solar/Wind Harmer
2.229
237046AF1-021 C
Solar/Wind Helper
0.227
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.846
971541AH1-268 GEN
Solar/Wind Harmer
2.321
970899AG2-561 GEN
Solar/Wind Harmer
1.254
970125AG2-091 GEN
Solar/Wind Harmer
0.324
203818AF1-086 GEN
Solar/Wind Harmer
1.374
971879AH1-460 GEN
Solar/Wind Harmer
3.532
203841AF2-001_GEN
Solar/Wind Harmer
1.057
971419AH1-201 GEN
Solar/Wind Harmer
1.538
945751AF1-240 GEN
Solar/Wind Harmer
0.726
960051AF2-296 GEN
Solar/Wind Harmer
0.887
237043AE2-125 C
Solar/Wind Helper
0.286
946071AF1-272 GEN
Solar/Wind Harmer
2.821
971441AH1-212 GEN
Solar/Wind Harmer
1.086
203857AF2-221 C
Solar/Wind Harmer
0.811
970123AG2-090 GEN
Solar/Wind Harmer
0.756
203839AF1-321 GEN
Solar/Wind Harmer
1.057
20084626FORWARD
Solar/Wind Harmer
0.413
203940AF1-140 C
Solar/Wind Harmer
0.256
20088926STNY CRK
Solar/Wind Harmer
0.592
971427AH1-205 GEN
Solar/Wind Harmer
0.715
20083426SW_E13_K22
Solar/Wind Harmer
0.138
203853AF1-134 C O1
Solar/Wind Harmer
0.268
972077AH1-588 GEN
Solar/Wind Harmer
6.628
972079AH1-589 GEN
Solar/Wind Harmer
5.459
23652301WDPWR_K20
Solar/Wind Helper
0.111
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.17
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.529
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.926
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.102
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.769
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.164
G-007ALTFEXP_G-007A->PJM
CMTX
1.046
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-050_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-050_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.89 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:251.3
MW Contribution:2.98
Bus #Bus NameTypeMW Contribution
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
71.495
971321AH1-140 GEN
Solar/Wind Harmer
13.856
20092526R32
Solar/Wind Harmer
0.847
203850AG1-041 C
Solar/Wind Harmer
0.557
203844AF2-092 C
Solar/Wind Harmer
0.556
20091526CHSTN_FL
Solar/Wind Harmer
0.384
20083726HOMER C1
Adder
25.766
20083926HOMER C3
Adder
25.516
20083826HOMER C2
Adder
24.102
20216026CON.GEN2
50/50
0.023
20079426CONEMAGH
Adder
0.774
971541AH1-268 GEN
Solar/Wind Harmer
2.196
970899AG2-561 GEN
Solar/Wind Harmer
1.241
203818AF1-086 GEN
Solar/Wind Harmer
1.365
945751AF1-240 GEN
Solar/Wind Harmer
0.777
970125AG2-091 GEN
Solar/Wind Harmer
0.292
971879AH1-460 GEN
Solar/Wind Harmer
3.19
203841AF2-001_GEN
Solar/Wind Harmer
0.957
960051AF2-296 GEN
Solar/Wind Harmer
0.892
971419AH1-201 GEN
Solar/Wind Harmer
1.389
237043AE2-125 C
Solar/Wind Helper
0.286
971279AH1-102 GEN
Solar/Wind Harmer
5.159
20094526CT_V3-030
Solar/Wind Harmer
0.382
971865AH1-452 GEN
Solar/Wind Harmer
0.821
20088826HIGHLAND
Solar/Wind Harmer
0.79
203843AF2-002_GEN
Solar/Wind Harmer
0.479
970631AG2-411 GEN
Solar/Wind Harmer
2.985
964201AG1-281 GEN
Solar/Wind Harmer
0.265
971423AH1-203 GEN
Solar/Wind Harmer
3.02
237046AF1-021 C
Solar/Wind Helper
0.238
946071AF1-272 GEN
Solar/Wind Harmer
2.834
971441AH1-212 GEN
Solar/Wind Harmer
0.99
203857AF2-221 C
Solar/Wind Harmer
0.73
970123AG2-090 GEN
Solar/Wind Harmer
0.681
203839AF1-321 GEN
Solar/Wind Harmer
0.957
20084626FORWARD
Solar/Wind Harmer
0.374
203940AF1-140 C
Solar/Wind Harmer
0.232
203853AF1-134 C O1
Solar/Wind Harmer
0.27
20088926STNY CRK
Solar/Wind Harmer
0.535
971427AH1-205 GEN
Solar/Wind Harmer
0.646
972077AH1-588 GEN
Solar/Wind Harmer
6.901
972079AH1-589 GEN
Solar/Wind Harmer
5.684
23652301WDPWR_K20
Solar/Wind Helper
0.114
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.233
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.725
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.43
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.124
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.05
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.194
G-007ALTFEXP_G-007A->PJM
CMTX
1.602
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.211
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P2-2_MP-138-100_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-100_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:126.79 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:243.44
MW Contribution:3.0
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.73
971541AH1-268 GEN
Solar/Wind Harmer
2.035
970899AG2-561 GEN
Solar/Wind Harmer
1.124
203841AF2-001_GEN
Solar/Wind Harmer
0.964
971879AH1-460 GEN
Solar/Wind Harmer
3.168
203818AF1-086 GEN
Solar/Wind Harmer
1.224
970125AG2-091 GEN
Solar/Wind Harmer
0.287
20089126CSLMN_L13
Solar/Wind Harmer
0.42
20089026BF_G21_K23
Solar/Wind Harmer
0.333
202652Y1-033 WT C
Solar/Wind Harmer
0.442
971419AH1-201 GEN
Solar/Wind Harmer
1.502
237043AE2-125 C
Solar/Wind Helper
0.288
946071AF1-272 GEN
Solar/Wind Harmer
2.634
203839AF1-321 GEN
Solar/Wind Harmer
0.964
20083426SW_E13_K22
Solar/Wind Harmer
0.143
203857AF2-221 C
Solar/Wind Harmer
0.718
970123AG2-090 GEN
Solar/Wind Harmer
0.67
944781AF1-143 GEN
Solar/Wind Harmer
1.44
20084626FORWARD
Solar/Wind Harmer
0.377
203955AF1-039 C O1
Solar/Wind Harmer
0.215
971427AH1-205 GEN
Solar/Wind Harmer
0.699
20088926STNY CRK
Solar/Wind Harmer
0.578
971441AH1-212 GEN
Solar/Wind Harmer
0.932
203940AF1-140 C
Solar/Wind Harmer
0.224
972077AH1-588 GEN
Solar/Wind Harmer
5.605
972079AH1-589 GEN
Solar/Wind Harmer
4.616
23652301WDPWR_K20
Solar/Wind Helper
0.113
971279AH1-102 GEN
Solar/Wind Harmer
4.781
20094526CT_V3-030
Solar/Wind Harmer
0.352
203843AF2-002_GEN
Solar/Wind Harmer
0.482
20089226LOOKOUT
Solar/Wind Harmer
0.409
970631AG2-411 GEN
Solar/Wind Harmer
3.001
971423AH1-203 GEN
Solar/Wind Harmer
3.325
20088826HIGHLAND
Solar/Wind Harmer
0.762
237046AF1-021 C
Solar/Wind Helper
0.233
971321AH1-140 GEN
Solar/Wind Harmer
70.391
971321AH1-140 GEN
Solar/Wind Harmer
13.642
20092526R32
Solar/Wind Harmer
0.817
203844AF2-092 C
Solar/Wind Harmer
0.556
203850AG1-041 C
Solar/Wind Harmer
0.554
20083726HOMER C1
Adder
23.014
20083926HOMER C3
Adder
21.167
20083826HOMER C2
Adder
19.995
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.196
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.61
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.113
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.887
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
G-007ALTFEXP_G-007A->PJM
CMTX
1.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.874
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o PN_P2-2_PN-115-001B_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-001B_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:123.4 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:236.93
MW Contribution:3.0
Bus #Bus NameTypeMW Contribution
946071AF1-272 GEN
Solar/Wind Harmer
2.636
203839AF1-321 GEN
Solar/Wind Harmer
0.965
20083426SW_E13_K22
Solar/Wind Harmer
0.143
203857AF2-221 C
Solar/Wind Harmer
0.718
970123AG2-090 GEN
Solar/Wind Harmer
0.67
20084626FORWARD
Solar/Wind Harmer
0.377
971427AH1-205 GEN
Solar/Wind Harmer
0.699
20088926STNY CRK
Solar/Wind Harmer
0.578
971441AH1-212 GEN
Solar/Wind Harmer
0.932
203940AF1-140 C
Solar/Wind Harmer
0.224
972077AH1-588 GEN
Solar/Wind Harmer
5.614
972079AH1-589 GEN
Solar/Wind Harmer
4.624
23652301WDPWR_K20
Solar/Wind Helper
0.112
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.73
971541AH1-268 GEN
Solar/Wind Harmer
2.036
970899AG2-561 GEN
Solar/Wind Harmer
1.125
203841AF2-001_GEN
Solar/Wind Harmer
0.965
971879AH1-460 GEN
Solar/Wind Harmer
3.17
203818AF1-086 GEN
Solar/Wind Harmer
1.225
970125AG2-091 GEN
Solar/Wind Harmer
0.287
971419AH1-201 GEN
Solar/Wind Harmer
1.503
237043AE2-125 C
Solar/Wind Helper
0.288
971279AH1-102 GEN
Solar/Wind Harmer
4.784
20094526CT_V3-030
Solar/Wind Harmer
0.352
203843AF2-002_GEN
Solar/Wind Harmer
0.482
970631AG2-411 GEN
Solar/Wind Harmer
3.003
971423AH1-203 GEN
Solar/Wind Harmer
3.328
20088826HIGHLAND
Solar/Wind Harmer
0.763
237046AF1-021 C
Solar/Wind Helper
0.233
971321AH1-140 GEN
Solar/Wind Harmer
70.4
971321AH1-140 GEN
Solar/Wind Harmer
13.643
20092526R32
Solar/Wind Harmer
0.818
203844AF2-092 C
Solar/Wind Harmer
0.556
203850AG1-041 C
Solar/Wind Harmer
0.554
20083726HOMER C1
Adder
23.041
20083926HOMER C3
Adder
21.196
20083826HOMER C2
Adder
20.022
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.193
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.601
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.58
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.111
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.874
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.177
G-007ALTFEXP_G-007A->PJM
CMTX
1.292
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.888
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P1-2_WP-500-008_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-500-008_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.67 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:235.52
MW Contribution:2.27
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
50/50
0.826
20083326SEWRDB34
50/50
1.492
971541AH1-268 GEN
Solar/Wind Harmer
2.667
970899AG2-561 GEN
Solar/Wind Harmer
0.841
203818AF1-086 GEN
Solar/Wind Harmer
0.312
972323AH1-746 GEN
Solar/Wind Harmer
1.206
970125AG2-091 GEN
Solar/Wind Harmer
0.207
971879AH1-460 GEN
Solar/Wind Harmer
2.26
203841AF2-001_GEN
Solar/Wind Harmer
0.677
945751AF1-240 GEN
Solar/Wind Harmer
0.572
971419AH1-201 GEN
Solar/Wind Harmer
1.232
960051AF2-296 GEN
Solar/Wind Harmer
0.603
237043AE2-125 C
Solar/Wind Helper
0.299
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.699
203857AF2-221 C
Solar/Wind Harmer
0.362
970123AG2-090 GEN
Solar/Wind Harmer
0.483
203839AF1-321 GEN
Solar/Wind Harmer
0.677
20084626FORWARD
Solar/Wind Harmer
0
203940AF1-140 C
Solar/Wind Harmer
0
20088926STNY CRK
Solar/Wind Harmer
0.059
971427AH1-205 GEN
Solar/Wind Harmer
0.821
972077AH1-588 GEN
Solar/Wind Harmer
4.556
972079AH1-589 GEN
Solar/Wind Harmer
5.378
23652301WDPWR_K20
Solar/Wind Helper
0.123
20215826CON.GEN1
50/50
0.011
20063626IUP CO-G
50/50
0.065
20050326C.SLOPE
50/50
0.162
971321AH1-140 GEN
Solar/Wind Harmer
50.091
971321AH1-140 GEN
Solar/Wind Harmer
13.914
20092526R32
Solar/Wind Harmer
0.104
203850AG1-041 C
Solar/Wind Harmer
0.394
203844AF2-092 C
Solar/Wind Harmer
0.393
20091526CHSTN_FL
Solar/Wind Harmer
0.055
20083726HOMER C1
Adder
27.064
20083926HOMER C3
Adder
24.703
20083826HOMER C2
Adder
23.335
20080526COLVER13
50/50
0.422
971279AH1-102 GEN
Solar/Wind Harmer
4.619
20094526CT_V3-030
Solar/Wind Harmer
0.063
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.339
970631AG2-411 GEN
Solar/Wind Harmer
2.274
971423AH1-203 GEN
Solar/Wind Harmer
2.122
237046AF1-021 C
Solar/Wind Helper
0.266
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.326
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.013
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.538
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.479
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.304
G-007ALTFEXP_G-007A->PJM
CMTX
2.369
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.192
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o PN_P2-2_PN-115-021_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-021_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.41 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:227.35
MW Contribution:2.72
Bus #Bus NameTypeMW Contribution
946071AF1-272 GEN
Solar/Wind Harmer
2.751
971441AH1-212 GEN
Solar/Wind Harmer
0.913
203857AF2-221 C
Solar/Wind Harmer
0.666
970123AG2-090 GEN
Solar/Wind Harmer
0.621
203839AF1-321 GEN
Solar/Wind Harmer
0.872
20084626FORWARD
Solar/Wind Harmer
0.341
972077AH1-588 GEN
Solar/Wind Harmer
5.275
972079AH1-589 GEN
Solar/Wind Harmer
4.345
23652301WDPWR_K20
Solar/Wind Helper
0.112
20216026CON.GEN2
50/50
0.022
970899AG2-561 GEN
Solar/Wind Harmer
1.278
971541AH1-268 GEN
Solar/Wind Harmer
2.139
20079426CONEMAGH
Adder
0.721
203818AF1-086 GEN
Solar/Wind Harmer
1.354
970125AG2-091 GEN
Solar/Wind Harmer
0.266
971879AH1-460 GEN
Solar/Wind Harmer
2.907
203841AF2-001_GEN
Solar/Wind Harmer
0.872
237043AE2-125 C
Solar/Wind Helper
0.288
971279AH1-102 GEN
Solar/Wind Harmer
5.026
20094526CT_V3-030
Solar/Wind Harmer
0.371
20088826HIGHLAND
Solar/Wind Harmer
0.721
203843AF2-002_GEN
Solar/Wind Harmer
0.436
970631AG2-411 GEN
Solar/Wind Harmer
2.717
237046AF1-021 C
Solar/Wind Helper
0.23
971321AH1-140 GEN
Solar/Wind Harmer
70.379
971321AH1-140 GEN
Solar/Wind Harmer
13.639
20092526R32
Solar/Wind Harmer
0.772
20083726HOMER C1
Adder
22.212
20083926HOMER C3
Adder
20.102
20083826HOMER C2
Adder
18.988
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.192
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.596
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.503
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.866
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.169
G-007ALTFEXP_G-007A->PJM
CMTX
1.265
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.617
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-056_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-056_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.79 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:218.47
MW Contribution:2.62
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.03
20079426CONEMAGH
50/50
0.996
20083326SEWRDB34
50/50
1.61
971541AH1-268 GEN
Solar/Wind Harmer
3.172
970899AG2-561 GEN
Solar/Wind Harmer
0.982
203818AF1-086 GEN
Solar/Wind Harmer
0.353
972323AH1-746 GEN
Solar/Wind Harmer
1.366
970125AG2-091 GEN
Solar/Wind Harmer
0.238
971879AH1-460 GEN
Solar/Wind Harmer
2.603
203841AF2-001_GEN
Solar/Wind Harmer
0.782
971419AH1-201 GEN
Solar/Wind Harmer
1.432
960051AF2-296 GEN
Solar/Wind Harmer
0.652
945751AF1-240 GEN
Solar/Wind Harmer
0.58
237043AE2-125 C
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.8
203857AF2-221 C
Solar/Wind Harmer
0.417
970123AG2-090 GEN
Solar/Wind Harmer
0.556
203839AF1-321 GEN
Solar/Wind Harmer
0.782
20084626FORWARD
Solar/Wind Harmer
0
203940AF1-140 C
Solar/Wind Harmer
0
20088926STNY CRK
Solar/Wind Harmer
0.069
971427AH1-205 GEN
Solar/Wind Harmer
0.954
23652301WDPWR_K20
Solar/Wind Helper
0.095
20215826CON.GEN1
50/50
0.014
20063626IUP CO-G
50/50
0.08
20050326C.SLOPE
50/50
0.186
971321AH1-140 GEN
Solar/Wind Harmer
58.683
971321AH1-140 GEN
Solar/Wind Harmer
16.301
20092526R32
Solar/Wind Harmer
0.119
203850AG1-041 C
Solar/Wind Harmer
0.452
203844AF2-092 C
Solar/Wind Harmer
0.451
20091526CHSTN_FL
Solar/Wind Harmer
0.062
203961AE2-224 GEN
Solar/Wind Harmer
0.002
20083726HOMER C1
Adder
27.287
20083926HOMER C3
Adder
22.644
20083826HOMER C2
Adder
21.39
20080526COLVER13
50/50
0.493
971279AH1-102 GEN
Solar/Wind Harmer
5.495
20094526CT_V3-030
Solar/Wind Harmer
0.072
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.391
970631AG2-411 GEN
Solar/Wind Harmer
2.618
971423AH1-203 GEN
Solar/Wind Harmer
2.474
957561AF2-050 GEN
Solar/Wind Harmer
1.503
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.243
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.757
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.494
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.12
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.094
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
G-007ALTFEXP_G-007A->PJM
CMTX
1.63
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.53 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:217.98
MW Contribution:2.79
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.023
20079426CONEMAGH
Adder
0.745
971541AH1-268 GEN
Solar/Wind Harmer
2.07
970899AG2-561 GEN
Solar/Wind Harmer
1.137
203818AF1-086 GEN
Solar/Wind Harmer
1.224
970125AG2-091 GEN
Solar/Wind Harmer
0.274
971879AH1-460 GEN
Solar/Wind Harmer
2.992
203841AF2-001_GEN
Solar/Wind Harmer
0.898
237043AE2-125 C
Solar/Wind Helper
0.277
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
72.644
971321AH1-140 GEN
Solar/Wind Harmer
14.078
20092526R32
Solar/Wind Harmer
0.793
203850AG1-041 C
Solar/Wind Harmer
0.52
203844AF2-092 C
Solar/Wind Harmer
0.519
20083726HOMER C1
Adder
22.696
20083926HOMER C3
Adder
19.683
20083826HOMER C2
Adder
18.592
971279AH1-102 GEN
Solar/Wind Harmer
4.864
20094526CT_V3-030
Solar/Wind Harmer
0.352
20088826HIGHLAND
Solar/Wind Harmer
0.74
203843AF2-002_GEN
Solar/Wind Harmer
0.449
970631AG2-411 GEN
Solar/Wind Harmer
2.794
237046AF1-021 C
Solar/Wind Helper
0.228
946071AF1-272 GEN
Solar/Wind Harmer
2.762
971441AH1-212 GEN
Solar/Wind Harmer
0.923
203857AF2-221 C
Solar/Wind Harmer
0.685
970123AG2-090 GEN
Solar/Wind Harmer
0.639
203839AF1-321 GEN
Solar/Wind Harmer
0.898
20084626FORWARD
Solar/Wind Harmer
0.351
203940AF1-140 C
Solar/Wind Harmer
0.216
23652301WDPWR_K20
Solar/Wind Helper
0.109
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.21
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.654
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.003
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.111
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.948
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.173
G-007ALTFEXP_G-007A->PJM
CMTX
1.45
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.791
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o PN_P2-3_PN-230-0252-C_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
PN_P2-3_PN-230-0252-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.04 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:207.71
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
203844AF2-092 C
Solar/Wind Harmer
1.086
203850AG1-041 C
Solar/Wind Harmer
1.033
20092526R32
Solar/Wind Harmer
1.176
20091526CHSTN_FL
Solar/Wind Harmer
0.442
20083726HOMER C1
Adder
25.742
202652Y1-033 WT C
Solar/Wind Harmer
3.834
20089126CSLMN_L13
Solar/Wind Harmer
2.457
20089026BF_G21_K23
Solar/Wind Harmer
1.945
971419AH1-201 GEN
Solar/Wind Harmer
4.389
203841AF2-001_GEN
Solar/Wind Harmer
1.928
971879AH1-460 GEN
Solar/Wind Harmer
5.756
970125AG2-091 GEN
Solar/Wind Harmer
0.482
20079426CONEMAGH
Adder
0.572
238127S14_GEN_2
Solar/Wind Helper
0.455
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.392
971423AH1-203 GEN
Solar/Wind Harmer
10.434
203843AF2-002_GEN
Solar/Wind Harmer
0.964
970631AG2-411 GEN
Solar/Wind Harmer
6.007
20088826HIGHLAND
Solar/Wind Harmer
1.098
964201AG1-281 GEN
Solar/Wind Harmer
0.354
20094526CT_V3-030
Solar/Wind Harmer
0.306
20083926HOMER C3
Adder
21.909
20083826HOMER C2
Adder
20.696
238126S14_GEN_1
Solar/Wind Helper
0.455
20084126DEEPCRK2
50/50
0.424
20084026DEEPCRK1
50/50
0.419
203955AF1-039 C O1
Solar/Wind Harmer
1.866
944781AF1-143 GEN
Solar/Wind Harmer
8.422
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.041
20088926STNY CRK
Solar/Wind Harmer
1.676
203839AF1-321 GEN
Solar/Wind Harmer
1.928
20084626FORWARD
Solar/Wind Harmer
0.754
203857AF2-221 C
Solar/Wind Harmer
1.205
970123AG2-090 GEN
Solar/Wind Harmer
1.125
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.031
972077AH1-588 GEN
Solar/Wind Harmer
5.419
972079AH1-589 GEN
Solar/Wind Harmer
4.464
238120AE2-309 GEN
Solar/Wind Helper
0.223
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.147
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.459
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.294
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.117
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.197
G-007ALTFEXP_G-007A->PJM
CMTX
0.812
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.141
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o PN_P2-3_PN-230-0252-B_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
PN_P2-3_PN-230-0252-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.04 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:207.71
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.834
20089126CSLMN_L13
Solar/Wind Harmer
2.457
20089026BF_G21_K23
Solar/Wind Harmer
1.945
971419AH1-201 GEN
Solar/Wind Harmer
4.389
203841AF2-001_GEN
Solar/Wind Harmer
1.928
971879AH1-460 GEN
Solar/Wind Harmer
5.756
970125AG2-091 GEN
Solar/Wind Harmer
0.482
20079426CONEMAGH
Adder
0.572
238127S14_GEN_2
Solar/Wind Helper
0.455
203844AF2-092 C
Solar/Wind Harmer
1.086
203850AG1-041 C
Solar/Wind Harmer
1.033
20092526R32
Solar/Wind Harmer
1.176
20091526CHSTN_FL
Solar/Wind Harmer
0.442
20083726HOMER C1
Adder
25.742
20083926HOMER C3
Adder
21.909
20083826HOMER C2
Adder
20.696
238126S14_GEN_1
Solar/Wind Helper
0.455
20084126DEEPCRK2
50/50
0.424
20084026DEEPCRK1
50/50
0.419
203955AF1-039 C O1
Solar/Wind Harmer
1.866
944781AF1-143 GEN
Solar/Wind Harmer
8.422
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.041
20088926STNY CRK
Solar/Wind Harmer
1.676
203839AF1-321 GEN
Solar/Wind Harmer
1.928
20084626FORWARD
Solar/Wind Harmer
0.754
203857AF2-221 C
Solar/Wind Harmer
1.205
970123AG2-090 GEN
Solar/Wind Harmer
1.125
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.031
972077AH1-588 GEN
Solar/Wind Harmer
5.419
972079AH1-589 GEN
Solar/Wind Harmer
4.464
238120AE2-309 GEN
Solar/Wind Helper
0.223
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.392
971423AH1-203 GEN
Solar/Wind Harmer
10.434
203843AF2-002_GEN
Solar/Wind Harmer
0.964
970631AG2-411 GEN
Solar/Wind Harmer
6.007
20088826HIGHLAND
Solar/Wind Harmer
1.098
964201AG1-281 GEN
Solar/Wind Harmer
0.354
20094526CT_V3-030
Solar/Wind Harmer
0.306
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.147
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.459
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.294
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.117
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.197
G-007ALTFEXP_G-007A->PJM
CMTX
0.812
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.141
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_PE-500-014_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.79 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:203.69
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
20084126DEEPCRK2
50/50
0.422
203844AF2-092 C
Solar/Wind Harmer
0.996
203850AG1-041 C
Solar/Wind Harmer
0.943
20092526R32
Solar/Wind Harmer
1.042
20091526CHSTN_FL
Solar/Wind Harmer
0.382
20083726HOMER C1
Adder
18.071
20083926HOMER C3
Adder
15.634
20083826HOMER C2
Adder
14.768
238126S14_GEN_1
Solar/Wind Helper
0.468
202652Y1-033 WT C
Solar/Wind Harmer
3.788
20089126CSLMN_L13
Solar/Wind Harmer
2.403
20089026BF_G21_K23
Solar/Wind Harmer
1.902
971419AH1-201 GEN
Solar/Wind Harmer
4.154
203841AF2-001_GEN
Solar/Wind Harmer
1.767
971879AH1-460 GEN
Solar/Wind Harmer
5.228
970125AG2-091 GEN
Solar/Wind Harmer
0.434
238127S14_GEN_2
Solar/Wind Helper
0.468
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
1.844
944781AF1-143 GEN
Solar/Wind Harmer
8.235
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.339
971423AH1-203 GEN
Solar/Wind Harmer
9.921
203843AF2-002_GEN
Solar/Wind Harmer
0.883
970631AG2-411 GEN
Solar/Wind Harmer
5.501
20088826HIGHLAND
Solar/Wind Harmer
0.973
964201AG1-281 GEN
Solar/Wind Harmer
0.312
20083426SW_E13_K22
Solar/Wind Harmer
0.49
971427AH1-205 GEN
Solar/Wind Harmer
1.932
20088926STNY CRK
Solar/Wind Harmer
1.586
203839AF1-321 GEN
Solar/Wind Harmer
1.767
20084626FORWARD
Solar/Wind Harmer
0.69
203857AF2-221 C
Solar/Wind Harmer
1.086
970123AG2-090 GEN
Solar/Wind Harmer
1.013
203940AF1-140 C
Solar/Wind Harmer
0.305
971441AH1-212 GEN
Solar/Wind Harmer
0.888
238120AE2-309 GEN
Solar/Wind Helper
0.231
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.129
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.402
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.046
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.609
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.193
G-007ALTFEXP_G-007A->PJM
CMTX
0.723
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.988
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P2-3_WP-500-DRT19_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.74 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:201.8
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
20084126DEEPCRK2
50/50
0.422
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
1.844
944781AF1-143 GEN
Solar/Wind Harmer
8.235
20083426SW_E13_K22
Solar/Wind Harmer
0.49
971427AH1-205 GEN
Solar/Wind Harmer
1.932
20088926STNY CRK
Solar/Wind Harmer
1.586
202652Y1-033 WT C
Solar/Wind Harmer
3.788
20089126CSLMN_L13
Solar/Wind Harmer
2.403
20089026BF_G21_K23
Solar/Wind Harmer
1.902
971419AH1-201 GEN
Solar/Wind Harmer
4.155
203841AF2-001_GEN
Solar/Wind Harmer
1.767
971879AH1-460 GEN
Solar/Wind Harmer
5.229
970125AG2-091 GEN
Solar/Wind Harmer
0.434
238127S14_GEN_2
Solar/Wind Helper
0.468
203839AF1-321 GEN
Solar/Wind Harmer
1.767
20084626FORWARD
Solar/Wind Harmer
0.69
203857AF2-221 C
Solar/Wind Harmer
1.086
970123AG2-090 GEN
Solar/Wind Harmer
1.013
203940AF1-140 C
Solar/Wind Harmer
0.305
971441AH1-212 GEN
Solar/Wind Harmer
0.888
238120AE2-309 GEN
Solar/Wind Helper
0.231
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.339
971423AH1-203 GEN
Solar/Wind Harmer
9.921
203843AF2-002_GEN
Solar/Wind Harmer
0.883
970631AG2-411 GEN
Solar/Wind Harmer
5.502
20088826HIGHLAND
Solar/Wind Harmer
0.973
964201AG1-281 GEN
Solar/Wind Harmer
0.312
203844AF2-092 C
Solar/Wind Harmer
0.996
203850AG1-041 C
Solar/Wind Harmer
0.943
20092526R32
Solar/Wind Harmer
1.042
20091526CHSTN_FL
Solar/Wind Harmer
0.383
20083726HOMER C1
Adder
18.078
20083926HOMER C3
Adder
15.642
20083826HOMER C2
Adder
14.776
238126S14_GEN_1
Solar/Wind Helper
0.468
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.128
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.606
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.192
G-007ALTFEXP_G-007A->PJM
CMTX
0.725
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.994
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.69 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:201.72
MW Contribution:5.98
Bus #Bus NameTypeMW Contribution
203844AF2-092 C
Solar/Wind Harmer
1.087
203850AG1-041 C
Solar/Wind Harmer
1.034
20092526R32
Solar/Wind Harmer
1.183
20091526CHSTN_FL
Solar/Wind Harmer
0.444
20083726HOMER C1
Adder
22.65
20083926HOMER C3
Adder
19.468
20083826HOMER C2
Adder
18.39
238126S14_GEN_1
Solar/Wind Helper
0.454
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.391
971423AH1-203 GEN
Solar/Wind Harmer
10.422
203843AF2-002_GEN
Solar/Wind Harmer
0.96
970631AG2-411 GEN
Solar/Wind Harmer
5.982
20088826HIGHLAND
Solar/Wind Harmer
1.104
964201AG1-281 GEN
Solar/Wind Harmer
0.356
20094526CT_V3-030
Solar/Wind Harmer
0.306
202652Y1-033 WT C
Solar/Wind Harmer
3.834
20089126CSLMN_L13
Solar/Wind Harmer
2.456
20089026BF_G21_K23
Solar/Wind Harmer
1.944
971419AH1-201 GEN
Solar/Wind Harmer
4.384
203841AF2-001_GEN
Solar/Wind Harmer
1.92
971879AH1-460 GEN
Solar/Wind Harmer
5.747
970125AG2-091 GEN
Solar/Wind Harmer
0.482
20079426CONEMAGH
Adder
0.589
238127S14_GEN_2
Solar/Wind Helper
0.454
20084126DEEPCRK2
50/50
0.424
20084026DEEPCRK1
50/50
0.42
203955AF1-039 C O1
Solar/Wind Harmer
1.866
944781AF1-143 GEN
Solar/Wind Harmer
8.417
20083426SW_E13_K22
Solar/Wind Harmer
0.51
971427AH1-205 GEN
Solar/Wind Harmer
2.039
20088926STNY CRK
Solar/Wind Harmer
1.674
203839AF1-321 GEN
Solar/Wind Harmer
1.92
20084626FORWARD
Solar/Wind Harmer
0.751
203857AF2-221 C
Solar/Wind Harmer
1.206
970123AG2-090 GEN
Solar/Wind Harmer
1.125
203940AF1-140 C
Solar/Wind Harmer
0.343
971441AH1-212 GEN
Solar/Wind Harmer
1.042
972077AH1-588 GEN
Solar/Wind Harmer
4.943
972079AH1-589 GEN
Solar/Wind Harmer
4.071
238120AE2-309 GEN
Solar/Wind Helper
0.222
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.131
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.409
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.941
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.614
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.186
G-007ALTFEXP_G-007A->PJM
CMTX
0.682
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.579
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P7-1_MP-138-018_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P7-1_MP-138-018_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.24 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:195.53
MW Contribution:5.38
Bus #Bus NameTypeMW Contribution
20084126DEEPCRK2
50/50
0.416
20084026DEEPCRK1
50/50
0.411
203955AF1-039 C O1
Solar/Wind Harmer
1.814
944781AF1-143 GEN
Solar/Wind Harmer
8.093
20083426SW_E13_K22
Solar/Wind Harmer
0.48
971427AH1-205 GEN
Solar/Wind Harmer
1.895
20088926STNY CRK
Solar/Wind Harmer
1.555
203839AF1-321 GEN
Solar/Wind Harmer
1.728
20084626FORWARD
Solar/Wind Harmer
0.675
203857AF2-221 C
Solar/Wind Harmer
1.06
970123AG2-090 GEN
Solar/Wind Harmer
0.99
203940AF1-140 C
Solar/Wind Harmer
0.298
971441AH1-212 GEN
Solar/Wind Harmer
0.863
238120AE2-309 GEN
Solar/Wind Helper
0.257
23585401KL_K28_T16
Solar/Wind Helper
0.628
203844AF2-092 C
Solar/Wind Harmer
0.974
203850AG1-041 C
Solar/Wind Harmer
0.922
20092526R32
Solar/Wind Harmer
1.017
20083726HOMER C1
Adder
17.398
20083926HOMER C3
Adder
15
20083826HOMER C2
Adder
14.169
238126S14_GEN_1
Solar/Wind Helper
0.513
202652Y1-033 WT C
Solar/Wind Harmer
3.726
20089126CSLMN_L13
Solar/Wind Harmer
2.361
20089026BF_G21_K23
Solar/Wind Harmer
1.869
971419AH1-201 GEN
Solar/Wind Harmer
4.074
203841AF2-001_GEN
Solar/Wind Harmer
1.728
971879AH1-460 GEN
Solar/Wind Harmer
5.11
970125AG2-091 GEN
Solar/Wind Harmer
0.424
238127S14_GEN_2
Solar/Wind Helper
0.513
238118U2-030_1
Solar/Wind Helper
0.144
20081326YOUGH
50/50
0.178
20089226LOOKOUT
Solar/Wind Harmer
2.299
971423AH1-203 GEN
Solar/Wind Harmer
9.731
203843AF2-002_GEN
Solar/Wind Harmer
0.864
970631AG2-411 GEN
Solar/Wind Harmer
5.381
20088826HIGHLAND
Solar/Wind Harmer
0.949
964201AG1-281 GEN
Solar/Wind Harmer
0.304
235531U2-073 GEN
Solar/Wind Helper
1.401
238117U2-030
Solar/Wind Helper
0.144
235054AD2-180 GEN
Solar/Wind Helper
0.761
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.125
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.388
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.103
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.585
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
G-007ALTFEXP_G-007A->PJM
CMTX
0.721
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.857
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o PN_P2-3_PN-230-0183-209_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
PN_P2-3_PN-230-0183-209_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.31 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:193.87
MW Contribution:6.17
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.848
20089126CSLMN_L13
Solar/Wind Harmer
2.474
20089026BF_G21_K23
Solar/Wind Harmer
1.959
971419AH1-201 GEN
Solar/Wind Harmer
4.461
203841AF2-001_GEN
Solar/Wind Harmer
1.98
971879AH1-460 GEN
Solar/Wind Harmer
5.925
970125AG2-091 GEN
Solar/Wind Harmer
0.497
20079426CONEMAGH
Adder
0.591
238127S14_GEN_2
Solar/Wind Helper
0.453
20081326YOUGH
50/50
0.183
20089226LOOKOUT
Solar/Wind Harmer
2.409
971423AH1-203 GEN
Solar/Wind Harmer
10.593
203843AF2-002_GEN
Solar/Wind Harmer
0.99
970631AG2-411 GEN
Solar/Wind Harmer
6.171
20088826HIGHLAND
Solar/Wind Harmer
1.135
964201AG1-281 GEN
Solar/Wind Harmer
0.365
203844AF2-092 C
Solar/Wind Harmer
1.112
203850AG1-041 C
Solar/Wind Harmer
1.059
20092526R32
Solar/Wind Harmer
1.216
20091526CHSTN_FL
Solar/Wind Harmer
0.453
20083726HOMER C1
Adder
29.295
20083926HOMER C3
Adder
16.069
20083826HOMER C2
Adder
15.179
238126S14_GEN_1
Solar/Wind Helper
0.453
20084126DEEPCRK2
50/50
0.424
20084026DEEPCRK1
50/50
0.42
203955AF1-039 C O1
Solar/Wind Harmer
1.873
944781AF1-143 GEN
Solar/Wind Harmer
8.481
20083426SW_E13_K22
Solar/Wind Harmer
0.518
971427AH1-205 GEN
Solar/Wind Harmer
2.075
20088926STNY CRK
Solar/Wind Harmer
1.704
203839AF1-321 GEN
Solar/Wind Harmer
1.98
20084626FORWARD
Solar/Wind Harmer
0.774
203857AF2-221 C
Solar/Wind Harmer
1.243
970123AG2-090 GEN
Solar/Wind Harmer
1.16
203940AF1-140 C
Solar/Wind Harmer
0.352
971441AH1-212 GEN
Solar/Wind Harmer
1.061
238120AE2-309 GEN
Solar/Wind Helper
0.222
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.156
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.487
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.477
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.118
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.727
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.198
G-007ALTFEXP_G-007A->PJM
CMTX
0.884
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.354
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P2-2_MP-138-001_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-2_MP-138-001_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.53 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:190.69
MW Contribution:5.41
Bus #Bus NameTypeMW Contribution
20084126DEEPCRK2
50/50
0.415
20084026DEEPCRK1
50/50
0.41
203955AF1-039 C O1
Solar/Wind Harmer
1.81
944781AF1-143 GEN
Solar/Wind Harmer
8.085
20083426SW_E13_K22
Solar/Wind Harmer
0.481
971427AH1-205 GEN
Solar/Wind Harmer
1.898
20088926STNY CRK
Solar/Wind Harmer
1.558
203839AF1-321 GEN
Solar/Wind Harmer
1.736
20084626FORWARD
Solar/Wind Harmer
0.678
203857AF2-221 C
Solar/Wind Harmer
1.067
970123AG2-090 GEN
Solar/Wind Harmer
0.996
203940AF1-140 C
Solar/Wind Harmer
0.3
971441AH1-212 GEN
Solar/Wind Harmer
0.873
238120AE2-309 GEN
Solar/Wind Helper
0.261
23585401KL_K28_T16
Solar/Wind Helper
0.656
202652Y1-033 WT C
Solar/Wind Harmer
3.719
20089126CSLMN_L13
Solar/Wind Harmer
2.359
20089026BF_G21_K23
Solar/Wind Harmer
1.867
971419AH1-201 GEN
Solar/Wind Harmer
4.081
203841AF2-001_GEN
Solar/Wind Harmer
1.736
971879AH1-460 GEN
Solar/Wind Harmer
5.138
970125AG2-091 GEN
Solar/Wind Harmer
0.427
238127S14_GEN_2
Solar/Wind Helper
0.518
238118U2-030_1
Solar/Wind Helper
0.143
203844AF2-092 C
Solar/Wind Harmer
0.979
203850AG1-041 C
Solar/Wind Harmer
0.927
20092526R32
Solar/Wind Harmer
1.025
20083726HOMER C1
Adder
17.789
20083926HOMER C3
Adder
15.413
20083826HOMER C2
Adder
14.559
238126S14_GEN_1
Solar/Wind Helper
0.518
20081326YOUGH
50/50
0.177
20089226LOOKOUT
Solar/Wind Harmer
2.297
971423AH1-203 GEN
Solar/Wind Harmer
9.744
203843AF2-002_GEN
Solar/Wind Harmer
0.868
970631AG2-411 GEN
Solar/Wind Harmer
5.406
20088826HIGHLAND
Solar/Wind Harmer
0.956
964201AG1-281 GEN
Solar/Wind Harmer
0.307
235531U2-073 GEN
Solar/Wind Helper
1.401
238117U2-030
Solar/Wind Helper
0.143
235054AD2-180 GEN
Solar/Wind Helper
0.793
23751201ROTHROCK
Solar/Wind Helper
0.342
238185AF2-356 C
Solar/Wind Helper
0.968
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.132
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.41
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.135
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.111
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.618
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.19
G-007ALTFEXP_G-007A->PJM
CMTX
0.757
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.998
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P2-2_WP-500-DRT16_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-2_WP-500-DRT16_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.65 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:189.12
MW Contribution:5.6
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.798
20089126CSLMN_L13
Solar/Wind Harmer
2.414
20089026BF_G21_K23
Solar/Wind Harmer
1.91
971419AH1-201 GEN
Solar/Wind Harmer
4.201
203841AF2-001_GEN
Solar/Wind Harmer
1.797
971879AH1-460 GEN
Solar/Wind Harmer
5.331
970125AG2-091 GEN
Solar/Wind Harmer
0.444
238127S14_GEN_2
Solar/Wind Helper
0.463
20084126DEEPCRK2
50/50
0.423
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
1.849
944781AF1-143 GEN
Solar/Wind Harmer
8.272
20083426SW_E13_K22
Solar/Wind Harmer
0.494
971427AH1-205 GEN
Solar/Wind Harmer
1.954
20088926STNY CRK
Solar/Wind Harmer
1.604
203839AF1-321 GEN
Solar/Wind Harmer
1.797
20084626FORWARD
Solar/Wind Harmer
0.702
203857AF2-221 C
Solar/Wind Harmer
1.109
970123AG2-090 GEN
Solar/Wind Harmer
1.035
203940AF1-140 C
Solar/Wind Harmer
0.313
971441AH1-212 GEN
Solar/Wind Harmer
0.919
238120AE2-309 GEN
Solar/Wind Helper
0.228
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.35
971423AH1-203 GEN
Solar/Wind Harmer
10.022
203843AF2-002_GEN
Solar/Wind Harmer
0.899
970631AG2-411 GEN
Solar/Wind Harmer
5.598
20088826HIGHLAND
Solar/Wind Harmer
0.998
964201AG1-281 GEN
Solar/Wind Harmer
0.321
203844AF2-092 C
Solar/Wind Harmer
1.014
203850AG1-041 C
Solar/Wind Harmer
0.961
20092526R32
Solar/Wind Harmer
1.07
20091526CHSTN_FL
Solar/Wind Harmer
0.396
20083726HOMER C1
Adder
19.201
20083926HOMER C3
Adder
16.692
20083826HOMER C2
Adder
15.768
238126S14_GEN_1
Solar/Wind Helper
0.463
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.167
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.521
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.781
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.781
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.225
G-007ALTFEXP_G-007A->PJM
CMTX
0.992
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.599
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o PN_P2-2_PN-115-073_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
PN_P2-2_PN-115-073_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:105.11 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:188.15
MW Contribution:5.33
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.893
20089126CSLMN_L13
Solar/Wind Harmer
2.528
20089026BF_G21_K23
Solar/Wind Harmer
2.001
971419AH1-201 GEN
Solar/Wind Harmer
5.754
203841AF2-001_GEN
Solar/Wind Harmer
1.814
971879AH1-460 GEN
Solar/Wind Harmer
5.293
20084126DEEPCRK2
50/50
0.426
20084026DEEPCRK1
50/50
0.421
203955AF1-039 C O1
Solar/Wind Harmer
1.895
944781AF1-143 GEN
Solar/Wind Harmer
8.666
20088926STNY CRK
Solar/Wind Harmer
2.214
971427AH1-205 GEN
Solar/Wind Harmer
2.676
20083426SW_E13_K22
Solar/Wind Harmer
0.539
203839AF1-321 GEN
Solar/Wind Harmer
1.814
20084626FORWARD
Solar/Wind Harmer
0.669
203857AF2-221 C
Solar/Wind Harmer
1.085
970123AG2-090 GEN
Solar/Wind Harmer
1.012
203940AF1-140 C
Solar/Wind Harmer
0.25
238120AE2-309 GEN
Solar/Wind Helper
0.219
203844AF2-092 C
Solar/Wind Harmer
0.732
203850AG1-041 C
Solar/Wind Harmer
0.706
20092526R32
Solar/Wind Harmer
0.949
20083726HOMER C1
Adder
17.674
20083926HOMER C3
Adder
15.223
20083826HOMER C2
Adder
14.38
238126S14_GEN_1
Solar/Wind Helper
0.447
970125AG2-091 GEN
Solar/Wind Harmer
0.434
238127S14_GEN_2
Solar/Wind Helper
0.447
20081326YOUGH
50/50
0.185
20089226LOOKOUT
Solar/Wind Harmer
2.462
971423AH1-203 GEN
Solar/Wind Harmer
12.687
203843AF2-002_GEN
Solar/Wind Harmer
0.907
970631AG2-411 GEN
Solar/Wind Harmer
5.335
20088826HIGHLAND
Solar/Wind Harmer
0.886
964201AG1-281 GEN
Solar/Wind Harmer
0.262
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.433
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.203
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.648
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
G-007ALTFEXP_G-007A->PJM
CMTX
0.784
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.971
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P2-2_WP-138-033T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-2_WP-138-033T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.92 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.8
MW Contribution:5.67
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.805
20089126CSLMN_L13
Solar/Wind Harmer
2.421
20089026BF_G21_K23
Solar/Wind Harmer
1.917
971419AH1-201 GEN
Solar/Wind Harmer
4.234
203841AF2-001_GEN
Solar/Wind Harmer
1.82
971879AH1-460 GEN
Solar/Wind Harmer
5.405
970125AG2-091 GEN
Solar/Wind Harmer
0.45
20079426CONEMAGH
Adder
0.526
238127S14_GEN_2
Solar/Wind Helper
0.458
20084126DEEPCRK2
50/50
0.423
20084026DEEPCRK1
50/50
0.419
203955AF1-039 C O1
Solar/Wind Harmer
1.852
944781AF1-143 GEN
Solar/Wind Harmer
8.299
20083426SW_E13_K22
Solar/Wind Harmer
0.497
971427AH1-205 GEN
Solar/Wind Harmer
1.969
20088926STNY CRK
Solar/Wind Harmer
1.616
203839AF1-321 GEN
Solar/Wind Harmer
1.82
20084626FORWARD
Solar/Wind Harmer
0.711
203857AF2-221 C
Solar/Wind Harmer
1.126
970123AG2-090 GEN
Solar/Wind Harmer
1.051
203940AF1-140 C
Solar/Wind Harmer
0.318
971441AH1-212 GEN
Solar/Wind Harmer
0.941
238120AE2-309 GEN
Solar/Wind Helper
0.224
203844AF2-092 C
Solar/Wind Harmer
1.027
203850AG1-041 C
Solar/Wind Harmer
0.974
20092526R32
Solar/Wind Harmer
1.089
20091526CHSTN_FL
Solar/Wind Harmer
0.403
20083726HOMER C1
Adder
19.24
20083926HOMER C3
Adder
16.514
20083826HOMER C2
Adder
15.599
238126S14_GEN_1
Solar/Wind Helper
0.458
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.358
971423AH1-203 GEN
Solar/Wind Harmer
10.094
203843AF2-002_GEN
Solar/Wind Harmer
0.91
970631AG2-411 GEN
Solar/Wind Harmer
5.667
20088826HIGHLAND
Solar/Wind Harmer
1.016
964201AG1-281 GEN
Solar/Wind Harmer
0.326
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.483
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.518
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.117
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.197
G-007ALTFEXP_G-007A->PJM
CMTX
0.899
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.397
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer l/o AP_P7-1_MP-138-056_SRT-A-1


Base Case Flowgate

Area:AP
Facility Description:
01GARRET-01GARRET 115.0/138.0 kV Ckt 1 transformer
Contingency Name:
AP_P7-1_MP-138-056_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.77 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.53
MW Contribution:5.45
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.749
20089126CSLMN_L13
Solar/Wind Harmer
2.378
20089026BF_G21_K23
Solar/Wind Harmer
1.882
971419AH1-201 GEN
Solar/Wind Harmer
4.113
203841AF2-001_GEN
Solar/Wind Harmer
1.749
971879AH1-460 GEN
Solar/Wind Harmer
5.177
970125AG2-091 GEN
Solar/Wind Harmer
0.43
20084126DEEPCRK2
50/50
0.418
20084026DEEPCRK1
50/50
0.413
203955AF1-039 C O1
Solar/Wind Harmer
1.825
944781AF1-143 GEN
Solar/Wind Harmer
8.149
20083426SW_E13_K22
Solar/Wind Harmer
0.485
971427AH1-205 GEN
Solar/Wind Harmer
1.913
20088926STNY CRK
Solar/Wind Harmer
1.57
203839AF1-321 GEN
Solar/Wind Harmer
1.749
20084626FORWARD
Solar/Wind Harmer
0.683
203857AF2-221 C
Solar/Wind Harmer
1.075
970123AG2-090 GEN
Solar/Wind Harmer
1.003
238127S14_GEN_2
Solar/Wind Helper
0.508
238118U2-030_1
Solar/Wind Helper
0.153
203844AF2-092 C
Solar/Wind Harmer
0.986
203850AG1-041 C
Solar/Wind Harmer
0.934
20092526R32
Solar/Wind Harmer
1.032
20083726HOMER C1
Adder
17.909
20083926HOMER C3
Adder
15.516
20083826HOMER C2
Adder
14.657
238126S14_GEN_1
Solar/Wind Helper
0.508
20081326YOUGH
50/50
0.179
20089226LOOKOUT
Solar/Wind Harmer
2.315
971423AH1-203 GEN
Solar/Wind Harmer
9.82
203843AF2-002_GEN
Solar/Wind Harmer
0.875
970631AG2-411 GEN
Solar/Wind Harmer
5.447
20088826HIGHLAND
Solar/Wind Harmer
0.963
964201AG1-281 GEN
Solar/Wind Harmer
0.309
238117U2-030
Solar/Wind Helper
0.153
235531U2-073 GEN
Solar/Wind Helper
1.461
203940AF1-140 C
Solar/Wind Harmer
0.303
971441AH1-212 GEN
Solar/Wind Harmer
0.88
238120AE2-309 GEN
Solar/Wind Helper
0.254
23585401KL_K28_T16
Solar/Wind Helper
0.572
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.169
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.113
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.632
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.193
G-007ALTFEXP_G-007A->PJM
CMTX
0.769
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.036
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT45_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT45_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.1 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:274.74
MW Contribution:3.03
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.778
946071AF1-272 GEN
Solar/Wind Harmer
2.794
971441AH1-212 GEN
Solar/Wind Harmer
1.002
203857AF2-221 C
Solar/Wind Harmer
0.742
970123AG2-090 GEN
Solar/Wind Harmer
0.693
203839AF1-321 GEN
Solar/Wind Harmer
0.971
20084626FORWARD
Solar/Wind Harmer
0.38
203940AF1-140 C
Solar/Wind Harmer
0.235
20088926STNY CRK
Solar/Wind Harmer
0.54
971427AH1-205 GEN
Solar/Wind Harmer
0.652
203853AF1-134 C O1
Solar/Wind Harmer
0.261
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
69.932
971321AH1-140 GEN
Solar/Wind Harmer
13.553
20092526R32
Solar/Wind Harmer
0.862
203850AG1-041 C
Solar/Wind Harmer
0.565
203844AF2-092 C
Solar/Wind Harmer
0.563
20091526CHSTN_FL
Solar/Wind Harmer
0.389
20083726HOMER C1
Adder
27.064
20083926HOMER C3
Adder
24.703
20083826HOMER C2
Adder
23.335
971541AH1-268 GEN
Solar/Wind Harmer
2.175
970899AG2-561 GEN
Solar/Wind Harmer
1.206
203818AF1-086 GEN
Solar/Wind Harmer
1.326
970125AG2-091 GEN
Solar/Wind Harmer
0.297
971879AH1-460 GEN
Solar/Wind Harmer
3.239
203841AF2-001_GEN
Solar/Wind Harmer
0.971
945751AF1-240 GEN
Solar/Wind Harmer
0.705
971419AH1-201 GEN
Solar/Wind Harmer
1.401
960051AF2-296 GEN
Solar/Wind Harmer
0.864
237043AE2-125 C
Solar/Wind Helper
0.299
971279AH1-102 GEN
Solar/Wind Harmer
5.111
20094526CT_V3-030
Solar/Wind Harmer
0.379
20088826HIGHLAND
Solar/Wind Harmer
0.804
203843AF2-002_GEN
Solar/Wind Harmer
0.485
970631AG2-411 GEN
Solar/Wind Harmer
3.028
964201AG1-281 GEN
Solar/Wind Harmer
0.27
971423AH1-203 GEN
Solar/Wind Harmer
3.042
237046AF1-021 C
Solar/Wind Helper
0.266
972077AH1-588 GEN
Solar/Wind Harmer
6.53
972079AH1-589 GEN
Solar/Wind Harmer
5.378
23652301WDPWR_K20
Solar/Wind Helper
0.123
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.326
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.013
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.538
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.479
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.304
G-007ALTFEXP_G-007A->PJM
CMTX
2.369
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.192
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-338_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-338_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.49 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:273.57
MW Contribution:3.48
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.03
20079426CONEMAGH
Adder
0.939
971541AH1-268 GEN
Solar/Wind Harmer
2.587
970899AG2-561 GEN
Solar/Wind Harmer
1.408
203818AF1-086 GEN
Solar/Wind Harmer
1.502
970125AG2-091 GEN
Solar/Wind Harmer
0.342
971879AH1-460 GEN
Solar/Wind Harmer
3.731
203841AF2-001_GEN
Solar/Wind Harmer
1.12
971419AH1-201 GEN
Solar/Wind Harmer
1.628
960051AF2-296 GEN
Solar/Wind Harmer
0.934
945751AF1-240 GEN
Solar/Wind Harmer
0.714
237043AE2-125 C
Solar/Wind Helper
0.241
946071AF1-272 GEN
Solar/Wind Harmer
3.5
971441AH1-212 GEN
Solar/Wind Harmer
1.146
203857AF2-221 C
Solar/Wind Harmer
0.854
970123AG2-090 GEN
Solar/Wind Harmer
0.797
203839AF1-321 GEN
Solar/Wind Harmer
1.12
20084626FORWARD
Solar/Wind Harmer
0.437
203940AF1-140 C
Solar/Wind Harmer
0.268
20088926STNY CRK
Solar/Wind Harmer
0.627
971427AH1-205 GEN
Solar/Wind Harmer
0.757
20083426SW_E13_K22
Solar/Wind Harmer
0.147
203853AF1-134 C O1
Solar/Wind Harmer
0.282
972077AH1-588 GEN
Solar/Wind Harmer
5.735
972079AH1-589 GEN
Solar/Wind Harmer
4.724
23652301WDPWR_K20
Solar/Wind Helper
0.095
20215826CON.GEN1
50/50
0.014
20063626IUP CO-G
50/50
0.08
971321AH1-140 GEN
Solar/Wind Harmer
81.927
971321AH1-140 GEN
Solar/Wind Harmer
15.877
20092526R32
Solar/Wind Harmer
0.986
203850AG1-041 C
Solar/Wind Harmer
0.647
203844AF2-092 C
Solar/Wind Harmer
0.646
20091526CHSTN_FL
Solar/Wind Harmer
0.432
203961AE2-224 GEN
Solar/Wind Harmer
1.305
20083726HOMER C1
Adder
27.287
20083926HOMER C3
Adder
22.644
20083826HOMER C2
Adder
21.39
971279AH1-102 GEN
Solar/Wind Harmer
6.08
20094526CT_V3-030
Solar/Wind Harmer
0.435
20088826HIGHLAND
Solar/Wind Harmer
0.92
203843AF2-002_GEN
Solar/Wind Harmer
0.56
970631AG2-411 GEN
Solar/Wind Harmer
3.485
971423AH1-203 GEN
Solar/Wind Harmer
3.547
964201AG1-281 GEN
Solar/Wind Harmer
0.303
957561AF2-050 GEN
Solar/Wind Harmer
2.154
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.243
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.757
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.494
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.12
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.094
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
G-007ALTFEXP_G-007A->PJM
CMTX
1.63
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-18201_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-18201_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.35 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.39
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-182_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-182_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.35 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.39
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.566
20083826HOMER C2
Adder
23.205
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-3_WP-138-181T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-138-181T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:141.35 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.38
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-2_WP-138-0582-1_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-0582-1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:141.33 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:271.36
MW Contribution:2.84
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.738
971541AH1-268 GEN
Solar/Wind Harmer
2.096
970899AG2-561 GEN
Solar/Wind Harmer
1.187
203818AF1-086 GEN
Solar/Wind Harmer
1.307
945751AF1-240 GEN
Solar/Wind Harmer
0.751
970125AG2-091 GEN
Solar/Wind Harmer
0.278
971279AH1-102 GEN
Solar/Wind Harmer
4.925
971865AH1-452 GEN
Solar/Wind Harmer
0.928
20094526CT_V3-030
Solar/Wind Harmer
0.365
20088826HIGHLAND
Solar/Wind Harmer
0.753
203843AF2-002_GEN
Solar/Wind Harmer
0.455
970631AG2-411 GEN
Solar/Wind Harmer
2.84
237046AF1-021 C
Solar/Wind Helper
0.28
971321AH1-140 GEN
Solar/Wind Harmer
68.429
971321AH1-140 GEN
Solar/Wind Harmer
13.261
20092526R32
Solar/Wind Harmer
0.807
203850AG1-041 C
Solar/Wind Harmer
0.531
203844AF2-092 C
Solar/Wind Harmer
0.529
20083726HOMER C1
Adder
24.719
20083926HOMER C3
Adder
24.565
20083826HOMER C2
Adder
23.205
971879AH1-460 GEN
Solar/Wind Harmer
3.036
203841AF2-001_GEN
Solar/Wind Harmer
0.911
237043AE2-125 C
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Harmer
2.7
971441AH1-212 GEN
Solar/Wind Harmer
0.945
203857AF2-221 C
Solar/Wind Harmer
0.695
970123AG2-090 GEN
Solar/Wind Harmer
0.649
203839AF1-321 GEN
Solar/Wind Harmer
0.911
20084626FORWARD
Solar/Wind Harmer
0.356
203940AF1-140 C
Solar/Wind Harmer
0.221
972077AH1-588 GEN
Solar/Wind Harmer
6.674
972079AH1-589 GEN
Solar/Wind Harmer
5.497
23652301WDPWR_K20
Solar/Wind Helper
0.132
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.23
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.716
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.058
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.04
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
G-007ALTFEXP_G-007A->PJM
CMTX
1.463
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.848
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:137.05 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:263.14
MW Contribution:3.29
Bus #Bus NameTypeMW Contribution
946071AF1-272 GEN
Solar/Wind Harmer
2.821
971441AH1-212 GEN
Solar/Wind Harmer
1.086
203857AF2-221 C
Solar/Wind Harmer
0.811
970123AG2-090 GEN
Solar/Wind Harmer
0.756
203839AF1-321 GEN
Solar/Wind Harmer
1.057
20084626FORWARD
Solar/Wind Harmer
0.413
203940AF1-140 C
Solar/Wind Harmer
0.256
20088926STNY CRK
Solar/Wind Harmer
0.592
971427AH1-205 GEN
Solar/Wind Harmer
0.715
20083426SW_E13_K22
Solar/Wind Harmer
0.138
203853AF1-134 C O1
Solar/Wind Harmer
0.268
972077AH1-588 GEN
Solar/Wind Harmer
6.628
972079AH1-589 GEN
Solar/Wind Harmer
5.459
23652301WDPWR_K20
Solar/Wind Helper
0.111
20215826CON.GEN1
50/50
0.011
971321AH1-140 GEN
Solar/Wind Harmer
70.772
971321AH1-140 GEN
Solar/Wind Harmer
13.716
20092526R32
Solar/Wind Harmer
0.942
203850AG1-041 C
Solar/Wind Harmer
0.616
203844AF2-092 C
Solar/Wind Harmer
0.614
20091526CHSTN_FL
Solar/Wind Harmer
0.418
203961AE2-224 GEN
Solar/Wind Harmer
1.35
20083726HOMER C1
Adder
28.212
20083926HOMER C3
Adder
25.532
20083826HOMER C2
Adder
24.118
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.846
971541AH1-268 GEN
Solar/Wind Harmer
2.321
970899AG2-561 GEN
Solar/Wind Harmer
1.254
970125AG2-091 GEN
Solar/Wind Harmer
0.324
203818AF1-086 GEN
Solar/Wind Harmer
1.374
971879AH1-460 GEN
Solar/Wind Harmer
3.532
203841AF2-001_GEN
Solar/Wind Harmer
1.057
971419AH1-201 GEN
Solar/Wind Harmer
1.538
945751AF1-240 GEN
Solar/Wind Harmer
0.726
960051AF2-296 GEN
Solar/Wind Harmer
0.887
237043AE2-125 C
Solar/Wind Helper
0.286
971279AH1-102 GEN
Solar/Wind Harmer
5.453
20094526CT_V3-030
Solar/Wind Harmer
0.401
20088826HIGHLAND
Solar/Wind Harmer
0.879
203843AF2-002_GEN
Solar/Wind Harmer
0.528
970631AG2-411 GEN
Solar/Wind Harmer
3.294
964201AG1-281 GEN
Solar/Wind Harmer
0.292
971423AH1-203 GEN
Solar/Wind Harmer
3.344
957561AF2-050 GEN
Solar/Wind Harmer
2.229
237046AF1-021 C
Solar/Wind Helper
0.227
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.17
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.529
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.926
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.102
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.769
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.164
G-007ALTFEXP_G-007A->PJM
CMTX
1.046
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.256
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-2_MP-138-100_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-100_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.29 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:250.15
MW Contribution:3.0
Bus #Bus NameTypeMW Contribution
946071AF1-272 GEN
Solar/Wind Harmer
2.634
203839AF1-321 GEN
Solar/Wind Harmer
0.964
20083426SW_E13_K22
Solar/Wind Harmer
0.143
203857AF2-221 C
Solar/Wind Harmer
0.718
970123AG2-090 GEN
Solar/Wind Harmer
0.67
944781AF1-143 GEN
Solar/Wind Harmer
1.44
20084626FORWARD
Solar/Wind Harmer
0.377
203955AF1-039 C O1
Solar/Wind Harmer
0.215
971427AH1-205 GEN
Solar/Wind Harmer
0.699
20088926STNY CRK
Solar/Wind Harmer
0.578
971441AH1-212 GEN
Solar/Wind Harmer
0.932
203940AF1-140 C
Solar/Wind Harmer
0.224
972077AH1-588 GEN
Solar/Wind Harmer
5.605
972079AH1-589 GEN
Solar/Wind Harmer
4.616
23652301WDPWR_K20
Solar/Wind Helper
0.113
971321AH1-140 GEN
Solar/Wind Harmer
70.391
971321AH1-140 GEN
Solar/Wind Harmer
13.642
20092526R32
Solar/Wind Harmer
0.817
203844AF2-092 C
Solar/Wind Harmer
0.556
203850AG1-041 C
Solar/Wind Harmer
0.554
20083726HOMER C1
Adder
23.014
20083926HOMER C3
Adder
21.167
20083826HOMER C2
Adder
19.995
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
Adder
0.73
971541AH1-268 GEN
Solar/Wind Harmer
2.035
970899AG2-561 GEN
Solar/Wind Harmer
1.124
203841AF2-001_GEN
Solar/Wind Harmer
0.964
971879AH1-460 GEN
Solar/Wind Harmer
3.168
203818AF1-086 GEN
Solar/Wind Harmer
1.224
970125AG2-091 GEN
Solar/Wind Harmer
0.287
20089126CSLMN_L13
Solar/Wind Harmer
0.42
20089026BF_G21_K23
Solar/Wind Harmer
0.333
202652Y1-033 WT C
Solar/Wind Harmer
0.442
971419AH1-201 GEN
Solar/Wind Harmer
1.502
237043AE2-125 C
Solar/Wind Helper
0.288
971279AH1-102 GEN
Solar/Wind Harmer
4.781
20094526CT_V3-030
Solar/Wind Harmer
0.352
203843AF2-002_GEN
Solar/Wind Harmer
0.482
20089226LOOKOUT
Solar/Wind Harmer
0.409
970631AG2-411 GEN
Solar/Wind Harmer
3.001
971423AH1-203 GEN
Solar/Wind Harmer
3.325
20088826HIGHLAND
Solar/Wind Harmer
0.762
237046AF1-021 C
Solar/Wind Helper
0.233
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.196
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.61
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.566
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.113
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.887
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
G-007ALTFEXP_G-007A->PJM
CMTX
1.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.874
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P1-2_WP-500-008_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-500-008_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:126.74 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:243.34
MW Contribution:2.27
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
20079426CONEMAGH
50/50
0.826
20083326SEWRDB34
50/50
1.492
971541AH1-268 GEN
Solar/Wind Harmer
2.667
970899AG2-561 GEN
Solar/Wind Harmer
0.841
203818AF1-086 GEN
Solar/Wind Harmer
0.312
972323AH1-746 GEN
Solar/Wind Harmer
1.206
970125AG2-091 GEN
Solar/Wind Harmer
0.207
971879AH1-460 GEN
Solar/Wind Harmer
2.26
203841AF2-001_GEN
Solar/Wind Harmer
0.677
945751AF1-240 GEN
Solar/Wind Harmer
0.572
971419AH1-201 GEN
Solar/Wind Harmer
1.232
960051AF2-296 GEN
Solar/Wind Harmer
0.603
237043AE2-125 C
Solar/Wind Helper
0.299
20215826CON.GEN1
50/50
0.011
20063626IUP CO-G
50/50
0.065
20050326C.SLOPE
50/50
0.162
971321AH1-140 GEN
Solar/Wind Harmer
50.091
971321AH1-140 GEN
Solar/Wind Harmer
13.914
20092526R32
Solar/Wind Harmer
0.104
203850AG1-041 C
Solar/Wind Harmer
0.394
203844AF2-092 C
Solar/Wind Harmer
0.393
20091526CHSTN_FL
Solar/Wind Harmer
0.055
20083726HOMER C1
Adder
27.064
20083926HOMER C3
Adder
24.703
20083826HOMER C2
Adder
23.335
20080526COLVER13
50/50
0.422
971279AH1-102 GEN
Solar/Wind Harmer
4.619
20094526CT_V3-030
Solar/Wind Harmer
0.063
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.339
970631AG2-411 GEN
Solar/Wind Harmer
2.274
971423AH1-203 GEN
Solar/Wind Harmer
2.122
237046AF1-021 C
Solar/Wind Helper
0.266
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.699
203857AF2-221 C
Solar/Wind Harmer
0.362
970123AG2-090 GEN
Solar/Wind Harmer
0.483
203839AF1-321 GEN
Solar/Wind Harmer
0.677
20084626FORWARD
Solar/Wind Harmer
0
203940AF1-140 C
Solar/Wind Harmer
0
20088926STNY CRK
Solar/Wind Harmer
0.059
971427AH1-205 GEN
Solar/Wind Harmer
0.821
972077AH1-588 GEN
Solar/Wind Harmer
4.556
972079AH1-589 GEN
Solar/Wind Harmer
5.378
23652301WDPWR_K20
Solar/Wind Helper
0.123
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.326
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.013
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
6.538
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.479
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.304
G-007ALTFEXP_G-007A->PJM
CMTX
2.369
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.192
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o PN_P2-2_PN-115-021_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-021_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:121.77 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:233.8
MW Contribution:2.72
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.022
970899AG2-561 GEN
Solar/Wind Harmer
1.278
971541AH1-268 GEN
Solar/Wind Harmer
2.139
20079426CONEMAGH
Adder
0.721
203818AF1-086 GEN
Solar/Wind Harmer
1.354
970125AG2-091 GEN
Solar/Wind Harmer
0.266
971879AH1-460 GEN
Solar/Wind Harmer
2.907
203841AF2-001_GEN
Solar/Wind Harmer
0.872
237043AE2-125 C
Solar/Wind Helper
0.288
946071AF1-272 GEN
Solar/Wind Harmer
2.751
971441AH1-212 GEN
Solar/Wind Harmer
0.913
203857AF2-221 C
Solar/Wind Harmer
0.666
970123AG2-090 GEN
Solar/Wind Harmer
0.621
203839AF1-321 GEN
Solar/Wind Harmer
0.872
20084626FORWARD
Solar/Wind Harmer
0.341
972077AH1-588 GEN
Solar/Wind Harmer
5.275
972079AH1-589 GEN
Solar/Wind Harmer
4.345
23652301WDPWR_K20
Solar/Wind Helper
0.112
971279AH1-102 GEN
Solar/Wind Harmer
5.026
20094526CT_V3-030
Solar/Wind Harmer
0.371
20088826HIGHLAND
Solar/Wind Harmer
0.721
203843AF2-002_GEN
Solar/Wind Harmer
0.436
970631AG2-411 GEN
Solar/Wind Harmer
2.717
237046AF1-021 C
Solar/Wind Helper
0.23
971321AH1-140 GEN
Solar/Wind Harmer
70.379
971321AH1-140 GEN
Solar/Wind Harmer
13.639
20092526R32
Solar/Wind Harmer
0.772
20083726HOMER C1
Adder
22.212
20083926HOMER C3
Adder
20.102
20083826HOMER C2
Adder
18.988
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.192
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.596
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.503
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.866
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.169
G-007ALTFEXP_G-007A->PJM
CMTX
1.265
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.617
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P1-2_WP-138-056_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-138-056_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.96 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:226.47
MW Contribution:2.62
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.03
20079426CONEMAGH
50/50
0.996
20083326SEWRDB34
50/50
1.61
971541AH1-268 GEN
Solar/Wind Harmer
3.172
970899AG2-561 GEN
Solar/Wind Harmer
0.982
203818AF1-086 GEN
Solar/Wind Harmer
0.353
972323AH1-746 GEN
Solar/Wind Harmer
1.366
970125AG2-091 GEN
Solar/Wind Harmer
0.238
971879AH1-460 GEN
Solar/Wind Harmer
2.603
203841AF2-001_GEN
Solar/Wind Harmer
0.782
971419AH1-201 GEN
Solar/Wind Harmer
1.432
960051AF2-296 GEN
Solar/Wind Harmer
0.652
945751AF1-240 GEN
Solar/Wind Harmer
0.58
237043AE2-125 C
Solar/Wind Helper
0.241
20215826CON.GEN1
50/50
0.014
20063626IUP CO-G
50/50
0.08
20050326C.SLOPE
50/50
0.186
971321AH1-140 GEN
Solar/Wind Harmer
58.683
971321AH1-140 GEN
Solar/Wind Harmer
16.301
20092526R32
Solar/Wind Harmer
0.119
203850AG1-041 C
Solar/Wind Harmer
0.452
203844AF2-092 C
Solar/Wind Harmer
0.451
20091526CHSTN_FL
Solar/Wind Harmer
0.062
203961AE2-224 GEN
Solar/Wind Harmer
0.002
20083726HOMER C1
Adder
27.287
20083926HOMER C3
Adder
22.644
20083826HOMER C2
Adder
21.39
20080526COLVER13
50/50
0.493
971279AH1-102 GEN
Solar/Wind Harmer
5.495
20094526CT_V3-030
Solar/Wind Harmer
0.072
20088826HIGHLAND
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
0.391
970631AG2-411 GEN
Solar/Wind Harmer
2.618
971423AH1-203 GEN
Solar/Wind Harmer
2.474
957561AF2-050 GEN
Solar/Wind Harmer
1.503
946071AF1-272 GEN
Solar/Wind Harmer
0
971441AH1-212 GEN
Solar/Wind Harmer
0.8
203857AF2-221 C
Solar/Wind Harmer
0.417
970123AG2-090 GEN
Solar/Wind Harmer
0.556
203839AF1-321 GEN
Solar/Wind Harmer
0.782
20084626FORWARD
Solar/Wind Harmer
0
203940AF1-140 C
Solar/Wind Harmer
0
20088926STNY CRK
Solar/Wind Harmer
0.069
971427AH1-205 GEN
Solar/Wind Harmer
0.954
23652301WDPWR_K20
Solar/Wind Helper
0.095
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.243
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.757
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.494
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.12
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.094
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
G-007ALTFEXP_G-007A->PJM
CMTX
1.63
CBM NorthLTFEXP_CBM-N->PJM
CBM
6.534
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0201A-20_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.88 %
Rating:294.0 MVA
Rating Type:B
MVA to Mitigate:337.74
MW Contribution:5.91
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.042
20079426CONEMAGH
50/50
1.557
971541AH1-268 GEN
Solar/Wind Harmer
4.044
20215826CON.GEN1
50/50
0.022
20063626IUP CO-G
50/50
0.125
20050326C.SLOPE
50/50
0.306
20092526R32
Solar/Wind Harmer
1.644
203850AG1-041 C
Solar/Wind Harmer
1.084
203844AF2-092 C
Solar/Wind Harmer
1.083
20083726HOMER C1
Adder
56.049
20091526CHSTN_FL
Solar/Wind Harmer
0.715
946071AF1-272 GEN
Solar/Wind Harmer
5.475
203857AF2-221 C
Solar/Wind Harmer
1.433
970123AG2-090 GEN
Solar/Wind Harmer
1.338
203839AF1-321 GEN
Solar/Wind Harmer
1.895
971441AH1-212 GEN
Solar/Wind Harmer
1.875
20084626FORWARD
Solar/Wind Harmer
0.741
203940AF1-140 C
Solar/Wind Harmer
0.446
20088926STNY CRK
Solar/Wind Harmer
1.061
971427AH1-205 GEN
Solar/Wind Harmer
1.281
20083426SW_E13_K22
Solar/Wind Harmer
0.25
203853AF1-134 C O1
Solar/Wind Harmer
0.448
20088626ARWF_N39
Solar/Wind Harmer
1.36
20303426NA_O38_P22
Solar/Wind Harmer
1.101
944781AF1-143 GEN
Solar/Wind Harmer
2.099
203952AE2-129 C
Solar/Wind Harmer
0.354
203946AE2-131 C
Solar/Wind Harmer
0.353
962411AG1-090 GEN
Solar/Wind Harmer
5.546
203955AF1-039 C O1
Solar/Wind Harmer
0.234
972077AH1-588 GEN
Solar/Wind Harmer
10.442
972079AH1-589 GEN
Solar/Wind Harmer
8.6
970715AG2-457 GEN
Solar/Wind Harmer
3.481
972075AH1-587 GEN
Solar/Wind Harmer
8.637
23652301WDPWR_K20
Solar/Wind Helper
0.075
203961AE2-224 GEN
Solar/Wind Harmer
2.291
20090526Q36
Solar/Wind Harmer
1.023
203993AD2-133_GEN1
Solar/Wind Harmer
1.023
20083926HOMER C3
Adder
44.365
20083826HOMER C2
Adder
41.908
965121AG1-377 GEN
Solar/Wind Harmer
1.167
941231AE2-117 GEN
Solar/Wind Harmer
0.35
203855AF2-088 C
Solar/Wind Harmer
0.097
940863AE2-074 GEN
Solar/Wind Harmer
0.761
970899AG2-561 GEN
Solar/Wind Harmer
2.199
970125AG2-091 GEN
Solar/Wind Harmer
0.573
971879AH1-460 GEN
Solar/Wind Harmer
6.284
203841AF2-001_GEN
Solar/Wind Harmer
1.895
203818AF1-086 GEN
Solar/Wind Harmer
2.364
971419AH1-201 GEN
Solar/Wind Harmer
2.755
960051AF2-296 GEN
Solar/Wind Harmer
1.482
945751AF1-240 GEN
Solar/Wind Harmer
1.094
20089126CSLMN_L13
Solar/Wind Harmer
0.612
20089026BF_G21_K23
Solar/Wind Harmer
0.485
965131AG1-378 GEN
Solar/Wind Harmer
1.167
202652Y1-033 WT C
Solar/Wind Harmer
0.48
203854AF2-039 C
Solar/Wind Harmer
0.202
971703AH1-357 GEN
Solar/Wind Harmer
0.87
971707AH1-359 GEN
Solar/Wind Harmer
0.87
237043AE2-125 C
Solar/Wind Helper
0.184
20080526COLVER13
50/50
0.77
971279AH1-102 GEN
Solar/Wind Harmer
9.503
20094526CT_V3-030
Solar/Wind Harmer
0.696
203843AF2-002_GEN
Solar/Wind Harmer
0.948
20088826HIGHLAND
Solar/Wind Harmer
1.534
970631AG2-411 GEN
Solar/Wind Harmer
5.905
971423AH1-203 GEN
Solar/Wind Harmer
6.012
964201AG1-281 GEN
Solar/Wind Harmer
0.505
957561AF2-050 GEN
Solar/Wind Harmer
3.782
20089226LOOKOUT
Solar/Wind Harmer
0.596
203987AE2-118 C
Solar/Wind Harmer
1.237
964391AG1-301 GEN
Solar/Wind Harmer
0.344
20091326SHAW-D
Adder
0.325
972169AH1-667 GEN
Solar/Wind Harmer
0.891
203954AE2-126 C
Solar/Wind Harmer
0.272
970713AG2-456 GEN
Solar/Wind Harmer
3.481
971705AH1-358 GEN
Solar/Wind Harmer
1.012
971709AH1-360 GEN
Solar/Wind Harmer
1.012
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.313
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.971
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.519
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.149
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.401
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.227
G-007ALTFEXP_G-007A->PJM
CMTX
1.994
CBM NorthLTFEXP_CBM-N->PJM
CBM
10.59
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-B_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.17
MW Contribution:17.12
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
961581Q1080_CY23
External Queue
19.46338653564453
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-C_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.17
MW Contribution:17.12
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
961581Q1080_CY23
External Queue
19.463396072387695
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0252-A_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0252-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1064.16
MW Contribution:17.12
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.973
20079426CONEMAGH
50/50
3.839
970125AG2-091 GEN
Solar/Wind Harmer
1.686
971879AH1-460 GEN
Solar/Wind Harmer
18.323
203841AF2-001_GEN
Solar/Wind Harmer
5.463
971541AH1-268 GEN
Solar/Wind Harmer
9.119
971419AH1-201 GEN
Solar/Wind Harmer
8.045
970899AG2-561 GEN
Solar/Wind Harmer
4.318
20089126CSLMN_L13
Solar/Wind Harmer
1.818
20089026BF_G21_K23
Solar/Wind Harmer
1.439
203818AF1-086 GEN
Solar/Wind Harmer
5.067
960051AF2-296 GEN
Solar/Wind Harmer
3.498
965131AG1-378 GEN
Solar/Wind Harmer
3.44
945751AF1-240 GEN
Solar/Wind Harmer
2.663
202652Y1-033 WT C
Solar/Wind Harmer
1.481
971703AH1-357 GEN
Solar/Wind Harmer
3.133
971707AH1-359 GEN
Solar/Wind Harmer
3.133
20334926Z1-069 C
Solar/Wind Harmer
3.127
203854AF2-039 C
Solar/Wind Harmer
0.587
20082926HNSMLK 2
Adder
7.964
20083126HNSMLK 4
Adder
7.964
203932AE1-123
Adder
2.614
944411AF1-106 GEN
Solar/Wind Harmer
0.282
971185AH1-051 GEN
Solar/Wind Harmer
3.027
971355AH1-158 GEN
Solar/Wind Harmer
3.519
203856AF2-165 C
Solar/Wind Harmer
1.469
20120126WRREN CT
Adder
7.775
970647AG2-420 GEN
Solar/Wind Harmer
2.457
238202AE2-262_GEN
Solar/Wind Harmer
3.028
971627AH1-313 GEN
Solar/Wind Harmer
11.871
959441AF2-235 GEN
Solar/Wind Harmer
0.354
238219AF1-167 C
Solar/Wind Harmer
1.562
970335AG2-220 GEN
Solar/Wind Harmer
3.551
971127AH1-005 GEN
Solar/Wind Harmer
2.291
957161AF2-010 GEN
Solar/Wind Harmer
8.109
203830AF1-094 GEN
Solar/Wind Harmer
0.634
20335126GROZ1-110
Adder
2.437
20335226CANZ2-011
Adder
2.369
203948AG1-140 C
Solar/Wind Harmer
0.264
203962AF1-287 GEN
Solar/Wind Harmer
1.984
962511AG1-100 GEN
Solar/Wind Harmer
0.598
20084926LAKVU GN
Adder
0.169
20328326MANOR_T86
Adder
0.131
941421AE2-139 GEN
Solar/Wind Harmer
2.661
972271AH1-720 GEN
Adder
5.618
200917MEHOOPANY_G
Solar/Wind Harmer
2.553
970643AG2-418 GEN
Solar/Wind Harmer
1.342
970679AG2-439 GEN
Solar/Wind Harmer
0.563
20083726HOMER C1
Adder
193.829
20092526R32
Solar/Wind Harmer
4.894
203961AE2-224 GEN
Solar/Wind Harmer
8.457
203850AG1-041 C
Solar/Wind Harmer
3.185
203844AF2-092 C
Solar/Wind Harmer
3.179
20091526CHSTN_FL
Solar/Wind Harmer
2.132
20083926HOMER C3
Adder
161.864
20083826HOMER C2
Adder
152.9
20090526Q36
Solar/Wind Harmer
3.041
203993AD2-133_GEN1
Solar/Wind Harmer
3.041
941231AE2-117 GEN
Solar/Wind Harmer
1.103
965121AG1-377 GEN
Solar/Wind Harmer
3.44
940863AE2-074 GEN
Solar/Wind Harmer
2.681
203804AE2-113_GEN
Solar/Wind Harmer
7.123
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
7.964
203846AF2-130 C
Solar/Wind Harmer
0.732
970663AG2-429 GEN
Solar/Wind Harmer
8.336
970663AG2-429 GEN
Solar/Wind Harmer
1.357
970555AG2-356 GEN
Solar/Wind Harmer
2.378
970677AG2-438 GEN
Solar/Wind Harmer
1.047
966771AG1-548 GEN
Solar/Wind Harmer
15.177
966771AG1-548 GEN
Solar/Wind Harmer
2.941
20084926LAKVU GN
Adder
0.19
203926AA2-133 GEN
Adder
1.93
971321AH1-140 GEN
Solar/Wind Harmer
11.594
971321AH1-140 GEN
Solar/Wind Harmer
2.247
20334726NME_Y1-047
Adder
1.715
20390726Y2-042
Adder
1.347
971055AG2-654 GEN
Solar/Wind Harmer
0.603
20080926SITHE
50/50
0.661
203857AF2-221 C
Solar/Wind Harmer
4.215
970123AG2-090 GEN
Solar/Wind Harmer
3.934
203839AF1-321 GEN
Solar/Wind Harmer
5.463
20084626FORWARD
Solar/Wind Harmer
2.148
203940AF1-140 C
Solar/Wind Harmer
1.318
971441AH1-212 GEN
Solar/Wind Harmer
5.335
20088626ARWF_N39
Solar/Wind Harmer
4.945
20303426NA_O38_P22
Solar/Wind Harmer
4.004
20088926STNY CRK
Solar/Wind Harmer
3.099
971427AH1-205 GEN
Solar/Wind Harmer
3.742
20083426SW_E13_K22
Solar/Wind Harmer
0.728
944781AF1-143 GEN
Solar/Wind Harmer
6.232
946071AF1-272 GEN
Solar/Wind Harmer
6.657
203853AF1-134 C O1
Solar/Wind Harmer
1.058
203952AE2-129 C
Solar/Wind Harmer
1.042
203946AE2-131 C
Solar/Wind Harmer
1.04
962411AG1-090 GEN
Solar/Wind Harmer
16.342
203955AF1-039 C O1
Solar/Wind Harmer
0.721
972077AH1-588 GEN
Solar/Wind Harmer
37.594
972079AH1-589 GEN
Solar/Wind Harmer
30.964
970715AG2-457 GEN
Solar/Wind Harmer
12.531
972075AH1-587 GEN
Solar/Wind Harmer
30.232
203848AF2-166 C
Solar/Wind Harmer
2.561
20398826ARMNA MT
Solar/Wind Harmer
2.971
238217AF1-153 C O1
Solar/Wind Harmer
0.767
946381AF1-302 GEN
Solar/Wind Harmer
2.655
970305AG2-200 GEN
Solar/Wind Harmer
2.459
203859AF2-294 C
Solar/Wind Harmer
1.952
970313AG2-206 GEN
Solar/Wind Harmer
5.471
216419AE2-001 C
Solar/Wind Harmer
2.246
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.094
203980AG1-197 GEN
Solar/Wind Harmer
0.474
203963AG1-253 GEN
Solar/Wind Harmer
0.403
971931AH1-490 GEN
Solar/Wind Harmer
1.979
203947AF1-006 C
Solar/Wind Harmer
0.525
20088826HIGHLAND
Solar/Wind Harmer
4.568
957561AF2-050 GEN
Solar/Wind Harmer
13.961
203843AF2-002_GEN
Solar/Wind Harmer
2.731
970631AG2-411 GEN
Solar/Wind Harmer
17.122
971279AH1-102 GEN
Solar/Wind Harmer
21.427
964201AG1-281 GEN
Solar/Wind Harmer
1.53
971423AH1-203 GEN
Solar/Wind Harmer
17.541
20094526CT_V3-030
Solar/Wind Harmer
1.693
20089226LOOKOUT
Solar/Wind Harmer
1.77
203987AE2-118 C
Solar/Wind Harmer
3.953
964391AG1-301 GEN
Solar/Wind Harmer
1.089
970713AG2-456 GEN
Solar/Wind Harmer
12.531
971705AH1-358 GEN
Solar/Wind Harmer
3.643
971709AH1-360 GEN
Solar/Wind Harmer
3.643
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.586
203954AE2-126 C
Solar/Wind Harmer
0.847
20082826HNSMLK 1
Adder
7.964
20083026HNSMLK 3
Adder
7.964
20072226SHAWVL 2
Adder
17.581
20326126BLOSSBCT
Adder
2.901
238183AE2-316 GEN
Solar/Wind Harmer
5.307
20335026MILZ1-092
Adder
2.848
944411AF1-106 GEN
Solar/Wind Harmer
2.624
971183AH1-050 GEN
Solar/Wind Harmer
5.044
970647AG2-420 GEN
Solar/Wind Harmer
0.286
203860AG1-193 C
Solar/Wind Harmer
0.363
959471AF2-238 GEN
Solar/Wind Harmer
0.719
970337AG2-221 GEN
Solar/Wind Harmer
2.378
238206AE2-263_GEN
Solar/Wind Harmer
2.822
970511AG2-327 GEN
Solar/Wind Harmer
1.14
238215AE2-248 C
Solar/Wind Harmer
1.78
970267AG2-176 GEN
Solar/Wind Harmer
16.502
961971AG1-040 GEN
Solar/Wind Harmer
0.626
203835AF1-098 GEN
Solar/Wind Harmer
2.489
203813AE2-344_GEN
Solar/Wind Harmer
11.51
20084926LAKVU GN
Adder
0.169
970643AG2-418 GEN
Solar/Wind Harmer
0.624
971865AH1-452 GEN
Solar/Wind Harmer
0.952
24035802GEN-Y1-012
Adder
0.204
961581Q1080_CY23
External Queue
19.463396072387695
LAGNLTFEXP_LAGN->PJM
CLTF
0.522
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.006
TVALTFEXP_TVA->PJM
CLTF
0.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.69
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.015
MECLTFEXP_MEC->PJM
CLTF
0.671
SIGELTFEXP_SIGE->PJM
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.259
WECLTFEXP_WEC->PJM
CLTF
0.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.034
CBM NorthLTFEXP_CBM-N->PJM
CBM
22.366
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.305

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0201A-20_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.94 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1050.42
MW Contribution:17.02
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.883
20079426CONEMAGH
50/50
3.851
970125AG2-091 GEN
Solar/Wind Harmer
1.677
971879AH1-460 GEN
Solar/Wind Harmer
18.223
203841AF2-001_GEN
Solar/Wind Harmer
5.431
971541AH1-268 GEN
Solar/Wind Harmer
9.304
20050326C.SLOPE
50/50
0.894
20092526R32
Solar/Wind Harmer
4.874
20083726HOMER C1
Adder
189.504
203961AE2-224 GEN
Solar/Wind Harmer
8.378
203850AG1-041 C
Solar/Wind Harmer
3.171
203844AF2-092 C
Solar/Wind Harmer
3.165
20091526CHSTN_FL
Solar/Wind Harmer
2.127
20083926HOMER C3
Adder
158.653
20083826HOMER C2
Adder
149.866
20090526Q36
Solar/Wind Harmer
3.039
203993AD2-133_GEN1
Solar/Wind Harmer
3.039
941231AE2-117 GEN
Solar/Wind Harmer
1.097
965121AG1-377 GEN
Solar/Wind Harmer
3.444
940863AE2-074 GEN
Solar/Wind Harmer
2.641
203804AE2-113_GEN
Solar/Wind Harmer
7.05
203855AF2-088 C
Solar/Wind Harmer
0.284
20083226HNSMLK 5
Adder
7.863
203846AF2-130 C
Solar/Wind Harmer
0.738
970663AG2-429 GEN
Solar/Wind Harmer
8.343
970663AG2-429 GEN
Solar/Wind Harmer
1.358
970555AG2-356 GEN
Solar/Wind Harmer
2.341
970677AG2-438 GEN
Solar/Wind Harmer
1.043
966771AG1-548 GEN
Solar/Wind Harmer
15.105
966771AG1-548 GEN
Solar/Wind Harmer
2.927
20084926LAKVU GN
Adder
0.188
971321AH1-140 GEN
Solar/Wind Harmer
12.535
971321AH1-140 GEN
Solar/Wind Harmer
2.429
203926AA2-133 GEN
Adder
1.9
20334726NME_Y1-047
Adder
1.687
20390726Y2-042
Adder
1.324
971055AG2-654 GEN
Solar/Wind Harmer
0.609
20080926SITHE
50/50
0.647
203857AF2-221 C
Solar/Wind Harmer
4.193
970123AG2-090 GEN
Solar/Wind Harmer
3.913
203839AF1-321 GEN
Solar/Wind Harmer
5.431
20084626FORWARD
Solar/Wind Harmer
2.135
971441AH1-212 GEN
Solar/Wind Harmer
5.336
203940AF1-140 C
Solar/Wind Harmer
1.313
20088626ARWF_N39
Solar/Wind Harmer
4.901
20303426NA_O38_P22
Solar/Wind Harmer
3.968
20088926STNY CRK
Solar/Wind Harmer
3.084
971427AH1-205 GEN
Solar/Wind Harmer
3.723
20083426SW_E13_K22
Solar/Wind Harmer
0.724
946071AF1-272 GEN
Solar/Wind Harmer
7.688
944781AF1-143 GEN
Solar/Wind Harmer
6.199
203853AF1-134 C O1
Solar/Wind Harmer
1.085
203952AE2-129 C
Solar/Wind Harmer
1.043
203946AE2-131 C
Solar/Wind Harmer
1.041
962411AG1-090 GEN
Solar/Wind Harmer
16.36
203955AF1-039 C O1
Solar/Wind Harmer
0.717
972077AH1-588 GEN
Solar/Wind Harmer
37.067
972079AH1-589 GEN
Solar/Wind Harmer
30.53
970715AG2-457 GEN
Solar/Wind Harmer
12.356
972075AH1-587 GEN
Solar/Wind Harmer
29.887
203848AF2-166 C
Solar/Wind Harmer
2.585
238217AF1-153 C O1
Solar/Wind Harmer
0.765
946381AF1-302 GEN
Solar/Wind Harmer
2.644
20398826ARMNA MT
Solar/Wind Harmer
2.923
970305AG2-200 GEN
Solar/Wind Harmer
2.435
203859AF2-294 C
Solar/Wind Harmer
1.92
970313AG2-206 GEN
Solar/Wind Harmer
5.384
216419AE2-001 C
Solar/Wind Harmer
2.24
203979AG1-198 GEN
Solar/Wind Harmer
0.379
971933AH1-491 GEN
Solar/Wind Harmer
2.086
203980AG1-197 GEN
Solar/Wind Harmer
0.471
203963AG1-253 GEN
Solar/Wind Harmer
0.399
971931AH1-490 GEN
Solar/Wind Harmer
1.963
203947AF1-006 C
Solar/Wind Harmer
0.52
20088826HIGHLAND
Solar/Wind Harmer
4.549
957561AF2-050 GEN
Solar/Wind Harmer
13.832
203843AF2-002_GEN
Solar/Wind Harmer
2.715
970631AG2-411 GEN
Solar/Wind Harmer
17.019
971279AH1-102 GEN
Solar/Wind Harmer
21.862
964201AG1-281 GEN
Solar/Wind Harmer
1.524
971423AH1-203 GEN
Solar/Wind Harmer
17.45
20094526CT_V3-030
Solar/Wind Harmer
1.725
20089226LOOKOUT
Solar/Wind Harmer
1.761
203987AE2-118 C
Solar/Wind Harmer
3.93
964391AG1-301 GEN
Solar/Wind Harmer
1.083
970713AG2-456 GEN
Solar/Wind Harmer
12.356
971705AH1-358 GEN
Solar/Wind Harmer
3.592
971709AH1-360 GEN
Solar/Wind Harmer
3.592
20091326SHAW-D
Adder
0.949
972169AH1-667 GEN
Solar/Wind Harmer
2.597
203954AE2-126 C
Solar/Wind Harmer
0.846
20082826HNSMLK 1
Adder
7.863
20083026HNSMLK 3
Adder
7.863
20072226SHAWVL 2
Adder
17.575
238183AE2-316 GEN
Solar/Wind Harmer
5.284
971183AH1-050 GEN
Solar/Wind Harmer
5.068
20326126BLOSSBCT
Adder
2.857
970647AG2-420 GEN
Solar/Wind Harmer
0.286
20335026MILZ1-092
Adder
2.802
944411AF1-106 GEN
Solar/Wind Harmer
2.581
203860AG1-193 C
Solar/Wind Harmer
0.362
238206AE2-263_GEN
Solar/Wind Harmer
2.815
959471AF2-238 GEN
Solar/Wind Harmer
0.708
970337AG2-221 GEN
Solar/Wind Harmer
2.341
970511AG2-327 GEN
Solar/Wind Harmer
1.122
238215AE2-248 C
Solar/Wind Harmer
1.775
970267AG2-176 GEN
Solar/Wind Harmer
16.374
961971AG1-040 GEN
Solar/Wind Harmer
0.62
203835AF1-098 GEN
Solar/Wind Harmer
2.467
203813AE2-344_GEN
Solar/Wind Harmer
11.413
20084926LAKVU GN
Adder
0.167
970643AG2-418 GEN
Solar/Wind Harmer
0.619
971865AH1-452 GEN
Solar/Wind Harmer
0.967
24035802GEN-Y1-012
Adder
0.202
971419AH1-201 GEN
Solar/Wind Harmer
8.004
970899AG2-561 GEN
Solar/Wind Harmer
4.534
203818AF1-086 GEN
Solar/Wind Harmer
5.258
20089126CSLMN_L13
Solar/Wind Harmer
1.809
20089026BF_G21_K23
Solar/Wind Harmer
1.432
960051AF2-296 GEN
Solar/Wind Harmer
3.589
945751AF1-240 GEN
Solar/Wind Harmer
2.752
965131AG1-378 GEN
Solar/Wind Harmer
3.444
202652Y1-033 WT C
Solar/Wind Harmer
1.474
971703AH1-357 GEN
Solar/Wind Harmer
3.089
971707AH1-359 GEN
Solar/Wind Harmer
3.089
20334926Z1-069 C
Solar/Wind Harmer
3.079
203854AF2-039 C
Solar/Wind Harmer
0.59
203932AE1-123
Adder
2.648
20082926HNSMLK 2
Adder
7.863
20083126HNSMLK 4
Adder
7.863
971185AH1-051 GEN
Solar/Wind Harmer
3.041
971355AH1-158 GEN
Solar/Wind Harmer
3.536
203856AF2-165 C
Solar/Wind Harmer
1.475
970647AG2-420 GEN
Solar/Wind Harmer
2.464
944411AF1-106 GEN
Solar/Wind Harmer
0.277
20120126WRREN CT
Adder
7.7
238202AE2-262_GEN
Solar/Wind Harmer
3.02
971627AH1-313 GEN
Solar/Wind Harmer
11.841
959441AF2-235 GEN
Solar/Wind Harmer
0.355
238219AF1-167 C
Solar/Wind Harmer
1.567
970335AG2-220 GEN
Solar/Wind Harmer
3.494
971127AH1-005 GEN
Solar/Wind Harmer
2.254
957161AF2-010 GEN
Solar/Wind Harmer
8.077
203830AF1-094 GEN
Solar/Wind Harmer
0.632
20335126GROZ1-110
Adder
2.405
20335226CANZ2-011
Adder
2.338
203948AG1-140 C
Solar/Wind Harmer
0.261
203962AF1-287 GEN
Solar/Wind Harmer
1.968
962511AG1-100 GEN
Solar/Wind Harmer
0.593
20084926LAKVU GN
Adder
0.167
20328326MANOR_T86
Adder
0.129
941421AE2-139 GEN
Solar/Wind Harmer
2.625
972271AH1-720 GEN
Adder
5.537
200917MEHOOPANY_G
Solar/Wind Harmer
2.511
970643AG2-418 GEN
Solar/Wind Harmer
1.331
970679AG2-439 GEN
Solar/Wind Harmer
0.553
961581Q1080_CY23
External Queue
18.953319549560547
LAGNLTFEXP_LAGN->PJM
CLTF
0.542
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.029
TVALTFEXP_TVA->PJM
CLTF
0.257
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.835
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.052
MECLTFEXP_MEC->PJM
CLTF
0.688
SIGELTFEXP_SIGE->PJM
CLTF
0.02
LGEELTFEXP_LGEE->PJM
CLTF
0.266
WECLTFEXP_WEC->PJM
CLTF
0.173
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.029
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.825
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.439

Details for 26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer l/o PN_P2-3_PN-230-0183-208_SRT-A


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
26CONEMAGH-CONEM-GH 230.0/500.0 kV Ckt 3 transformer
Contingency Name:
PN_P2-3_PN-230-0183-208_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.22 %
Rating:1001.0 MVA
Rating Type:B
MVA to Mitigate:1033.26
MW Contribution:15.93
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
Adder
187.733
203961AE2-224 GEN
Solar/Wind Harmer
8.147
20092526R32
Solar/Wind Harmer
4.61
203850AG1-041 C
Solar/Wind Harmer
2.985
203844AF2-092 C
Solar/Wind Harmer
2.977
20091526CHSTN_FL
Solar/Wind Harmer
2.007
20083926HOMER C3
Adder
156.059
20083826HOMER C2
Adder
147.416
20090526Q36
Solar/Wind Harmer
2.845
203993AD2-133_GEN1
Solar/Wind Harmer
2.845
941231AE2-117 GEN
Solar/Wind Harmer
1.048
965121AG1-377 GEN
Solar/Wind Harmer
3.201
940863AE2-074 GEN
Solar/Wind Harmer
2.56
203804AE2-113_GEN
Solar/Wind Harmer
6.747
20083326SEWRDB34
50/50
11.609
20079426CONEMAGH
50/50
3.593
970125AG2-091 GEN
Solar/Wind Harmer
1.58
971879AH1-460 GEN
Solar/Wind Harmer
17.118
203841AF2-001_GEN
Solar/Wind Harmer
5.082
971419AH1-201 GEN
Solar/Wind Harmer
7.507
971541AH1-268 GEN
Solar/Wind Harmer
8.155
20089126CSLMN_L13
Solar/Wind Harmer
1.693
20089026BF_G21_K23
Solar/Wind Harmer
1.34
970899AG2-561 GEN
Solar/Wind Harmer
3.549
203818AF1-086 GEN
Solar/Wind Harmer
4.301
965131AG1-378 GEN
Solar/Wind Harmer
3.201
960051AF2-296 GEN
Solar/Wind Harmer
3.058
971703AH1-357 GEN
Solar/Wind Harmer
2.988
971707AH1-359 GEN
Solar/Wind Harmer
2.988
202652Y1-033 WT C
Solar/Wind Harmer
1.378
945751AF1-240 GEN
Solar/Wind Harmer
2.28
20334926Z1-069 C
Solar/Wind Harmer
2.988
203854AF2-039 C
Solar/Wind Harmer
0.541
20082926HNSMLK 2
Adder
7.58
20083126HNSMLK 4
Adder
7.58
944411AF1-106 GEN
Solar/Wind Harmer
0.27
203932AE1-123
Adder
2.352
20120126WRREN CT
Adder
7.362
971185AH1-051 GEN
Solar/Wind Harmer
2.776
971355AH1-158 GEN
Solar/Wind Harmer
3.228
203856AF2-165 C
Solar/Wind Harmer
1.349
970647AG2-420 GEN
Solar/Wind Harmer
2.262
238202AE2-262_GEN
Solar/Wind Harmer
2.83
971627AH1-313 GEN
Solar/Wind Harmer
11.095
970335AG2-220 GEN
Solar/Wind Harmer
3.393
971127AH1-005 GEN
Solar/Wind Harmer
2.189
959441AF2-235 GEN
Solar/Wind Harmer
0.327
238219AF1-167 C
Solar/Wind Harmer
1.437
20335126GROZ1-110
Adder
2.316
20335226CANZ2-011
Adder
2.251
957161AF2-010 GEN
Solar/Wind Harmer
7.586
203830AF1-094 GEN
Solar/Wind Harmer
0.594
203948AG1-140 C
Solar/Wind Harmer
0.25
203962AF1-287 GEN
Solar/Wind Harmer
1.875
962511AG1-100 GEN
Solar/Wind Harmer
0.565
20084926LAKVU GN
Adder
0.16
20328326MANOR_T86
Adder
0.125
941421AE2-139 GEN
Solar/Wind Harmer
2.528
972271AH1-720 GEN
Adder
5.344
200917MEHOOPANY_G
Solar/Wind Harmer
2.433
970643AG2-418 GEN
Solar/Wind Harmer
1.273
970679AG2-439 GEN
Solar/Wind Harmer
0.536
957561AF2-050 GEN
Solar/Wind Harmer
13.449
20088826HIGHLAND
Solar/Wind Harmer
4.302
203843AF2-002_GEN
Solar/Wind Harmer
2.541
20080926SITHE
50/50
0.641
203857AF2-221 C
Solar/Wind Harmer
3.95
970123AG2-090 GEN
Solar/Wind Harmer
3.686
20088626ARWF_N39
Solar/Wind Harmer
4.759
20303426NA_O38_P22
Solar/Wind Harmer
3.853
203839AF1-321 GEN
Solar/Wind Harmer
5.082
20084626FORWARD
Solar/Wind Harmer
1.999
203940AF1-140 C
Solar/Wind Harmer
1.239
971441AH1-212 GEN
Solar/Wind Harmer
4.999
20088926STNY CRK
Solar/Wind Harmer
2.892
971427AH1-205 GEN
Solar/Wind Harmer
3.492
20083426SW_E13_K22
Solar/Wind Harmer
0.678
944781AF1-143 GEN
Solar/Wind Harmer
5.802
203952AE2-129 C
Solar/Wind Harmer
0.969
203946AE2-131 C
Solar/Wind Harmer
0.968
962411AG1-090 GEN
Solar/Wind Harmer
15.203
203853AF1-134 C O1
Solar/Wind Harmer
0.925
972077AH1-588 GEN
Solar/Wind Harmer
35.86
972079AH1-589 GEN
Solar/Wind Harmer
29.536
970715AG2-457 GEN
Solar/Wind Harmer
11.953
203955AF1-039 C O1
Solar/Wind Harmer
0.671
972075AH1-587 GEN
Solar/Wind Harmer
28.698
20398826ARMNA MT
Solar/Wind Harmer
2.842
238217AF1-153 C O1
Solar/Wind Harmer
0.716
946381AF1-302 GEN
Solar/Wind Harmer
2.487
970305AG2-200 GEN
Solar/Wind Harmer
2.329
203848AF2-166 C
Solar/Wind Harmer
2.325
946071AF1-272 GEN
Solar/Wind Harmer
3.833
203859AF2-294 C
Solar/Wind Harmer
1.868
970313AG2-206 GEN
Solar/Wind Harmer
5.227
216419AE2-001 C
Solar/Wind Harmer
2.105
203980AG1-197 GEN
Solar/Wind Harmer
0.448
203979AG1-198 GEN
Solar/Wind Harmer
0.356
971933AH1-491 GEN
Solar/Wind Harmer
1.961
203963AG1-253 GEN
Solar/Wind Harmer
0.382
971931AH1-490 GEN
Solar/Wind Harmer
1.87
203947AF1-006 C
Solar/Wind Harmer
0.497
970631AG2-411 GEN
Solar/Wind Harmer
15.933
964201AG1-281 GEN
Solar/Wind Harmer
1.443
971279AH1-102 GEN
Solar/Wind Harmer
19.163
971423AH1-203 GEN
Solar/Wind Harmer
16.357
20094526CT_V3-030
Solar/Wind Harmer
1.513
20089226LOOKOUT
Solar/Wind Harmer
1.648
203987AE2-118 C
Solar/Wind Harmer
3.76
964391AG1-301 GEN
Solar/Wind Harmer
1.036
970713AG2-456 GEN
Solar/Wind Harmer
11.953
971705AH1-358 GEN
Solar/Wind Harmer
3.475
971709AH1-360 GEN
Solar/Wind Harmer
3.475
972169AH1-667 GEN
Solar/Wind Harmer
2.382
20091326SHAW-D
Adder
0.87
203954AE2-126 C
Solar/Wind Harmer
0.787
20082826HNSMLK 1
Adder
7.58
20083026HNSMLK 3
Adder
7.58
20326126BLOSSBCT
Adder
2.771
20335026MILZ1-092
Adder
2.724
944411AF1-106 GEN
Solar/Wind Harmer
2.51
20072226SHAWVL 2
Adder
16.351
238183AE2-316 GEN
Solar/Wind Harmer
4.969
971183AH1-050 GEN
Solar/Wind Harmer
4.627
959471AF2-238 GEN
Solar/Wind Harmer
0.687
970337AG2-221 GEN
Solar/Wind Harmer
2.272
970647AG2-420 GEN
Solar/Wind Harmer
0.263
203860AG1-193 C
Solar/Wind Harmer
0.338
238206AE2-263_GEN
Solar/Wind Harmer
2.637
970511AG2-327 GEN
Solar/Wind Harmer
1.089
238215AE2-248 C
Solar/Wind Harmer
1.668
970267AG2-176 GEN
Solar/Wind Harmer
15.562
961971AG1-040 GEN
Solar/Wind Harmer
0.591
203835AF1-098 GEN
Solar/Wind Harmer
2.356
203813AE2-344_GEN
Solar/Wind Harmer
10.878
20084926LAKVU GN
Adder
0.16
970643AG2-418 GEN
Solar/Wind Harmer
0.592
971865AH1-452 GEN
Solar/Wind Harmer
0.859
24035802GEN-Y1-012
Adder
0.193
203855AF2-088 C
Solar/Wind Harmer
0.261
20083226HNSMLK 5
Adder
7.58
203846AF2-130 C
Solar/Wind Harmer
0.664
970555AG2-356 GEN
Solar/Wind Harmer
2.272
970663AG2-429 GEN
Solar/Wind Harmer
7.716
970663AG2-429 GEN
Solar/Wind Harmer
1.256
970677AG2-438 GEN
Solar/Wind Harmer
0.98
966771AG1-548 GEN
Solar/Wind Harmer
14.226
966771AG1-548 GEN
Solar/Wind Harmer
2.757
20084926LAKVU GN
Adder
0.18
203926AA2-133 GEN
Adder
1.839
20334726NME_Y1-047
Adder
1.634
971321AH1-140 GEN
Solar/Wind Harmer
8.786
971321AH1-140 GEN
Solar/Wind Harmer
1.703
20390726Y2-042
Adder
1.283
971055AG2-654 GEN
Solar/Wind Harmer
0.555
961581Q1080_CY23
External Queue
19.001585006713867
LAGNLTFEXP_LAGN->PJM
CLTF
0.516
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.031
TVALTFEXP_TVA->PJM
CLTF
0.245
CBM West 1LTFEXP_CBM-W1->PJM
CBM
7.455
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.002
MECLTFEXP_MEC->PJM
CLTF
0.655
SIGELTFEXP_SIGE->PJM
CLTF
0.019
LGEELTFEXP_LGEE->PJM
CLTF
0.253
WECLTFEXP_WEC->PJM
CLTF
0.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.027
CBM NorthLTFEXP_CBM-N->PJM
CBM
21.444
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.226

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.67 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:204.27
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
203844AF2-092 C
Solar/Wind Harmer
0.996
203850AG1-041 C
Solar/Wind Harmer
0.943
20092526R32
Solar/Wind Harmer
1.042
20091526CHSTN_FL
Solar/Wind Harmer
0.382
20083726HOMER C1
Adder
18.071
20083926HOMER C3
Adder
15.634
20083826HOMER C2
Adder
14.768
238126S14_GEN_1
Solar/Wind Helper
0.468
202652Y1-033 WT C
Solar/Wind Harmer
3.788
20089126CSLMN_L13
Solar/Wind Harmer
2.403
20089026BF_G21_K23
Solar/Wind Harmer
1.902
971419AH1-201 GEN
Solar/Wind Harmer
4.154
203841AF2-001_GEN
Solar/Wind Harmer
1.767
971879AH1-460 GEN
Solar/Wind Harmer
5.228
970125AG2-091 GEN
Solar/Wind Harmer
0.434
238127S14_GEN_2
Solar/Wind Helper
0.468
20084126DEEPCRK2
50/50
0.422
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
1.844
944781AF1-143 GEN
Solar/Wind Harmer
8.235
20083426SW_E13_K22
Solar/Wind Harmer
0.49
971427AH1-205 GEN
Solar/Wind Harmer
1.932
20088926STNY CRK
Solar/Wind Harmer
1.586
203839AF1-321 GEN
Solar/Wind Harmer
1.767
20084626FORWARD
Solar/Wind Harmer
0.69
203857AF2-221 C
Solar/Wind Harmer
1.086
970123AG2-090 GEN
Solar/Wind Harmer
1.013
203940AF1-140 C
Solar/Wind Harmer
0.305
971441AH1-212 GEN
Solar/Wind Harmer
0.888
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.339
971423AH1-203 GEN
Solar/Wind Harmer
9.921
203843AF2-002_GEN
Solar/Wind Harmer
0.883
970631AG2-411 GEN
Solar/Wind Harmer
5.501
20088826HIGHLAND
Solar/Wind Harmer
0.973
964201AG1-281 GEN
Solar/Wind Harmer
0.312
238120AE2-309 GEN
Solar/Wind Helper
0.231
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.129
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.402
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.046
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.609
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.193
G-007ALTFEXP_G-007A->PJM
CMTX
0.723
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.988
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT19_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT19_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:126.37 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:202.19
MW Contribution:5.5
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.788
20089126CSLMN_L13
Solar/Wind Harmer
2.403
20089026BF_G21_K23
Solar/Wind Harmer
1.902
971419AH1-201 GEN
Solar/Wind Harmer
4.155
203841AF2-001_GEN
Solar/Wind Harmer
1.767
971879AH1-460 GEN
Solar/Wind Harmer
5.229
970125AG2-091 GEN
Solar/Wind Harmer
0.434
238127S14_GEN_2
Solar/Wind Helper
0.468
203844AF2-092 C
Solar/Wind Harmer
0.996
203850AG1-041 C
Solar/Wind Harmer
0.943
20092526R32
Solar/Wind Harmer
1.042
20091526CHSTN_FL
Solar/Wind Harmer
0.383
20083726HOMER C1
Adder
18.078
20083926HOMER C3
Adder
15.642
20083826HOMER C2
Adder
14.776
238126S14_GEN_1
Solar/Wind Helper
0.468
20084126DEEPCRK2
50/50
0.422
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
1.844
944781AF1-143 GEN
Solar/Wind Harmer
8.235
20083426SW_E13_K22
Solar/Wind Harmer
0.49
971427AH1-205 GEN
Solar/Wind Harmer
1.932
20088926STNY CRK
Solar/Wind Harmer
1.586
203839AF1-321 GEN
Solar/Wind Harmer
1.767
20084626FORWARD
Solar/Wind Harmer
0.69
203857AF2-221 C
Solar/Wind Harmer
1.086
970123AG2-090 GEN
Solar/Wind Harmer
1.013
203940AF1-140 C
Solar/Wind Harmer
0.305
971441AH1-212 GEN
Solar/Wind Harmer
0.888
238120AE2-309 GEN
Solar/Wind Helper
0.231
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.339
971423AH1-203 GEN
Solar/Wind Harmer
9.921
203843AF2-002_GEN
Solar/Wind Harmer
0.883
970631AG2-411 GEN
Solar/Wind Harmer
5.502
20088826HIGHLAND
Solar/Wind Harmer
0.973
964201AG1-281 GEN
Solar/Wind Harmer
0.312
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.128
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.606
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.192
G-007ALTFEXP_G-007A->PJM
CMTX
0.725
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.994
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:125.63 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:201.01
MW Contribution:5.98
Bus #Bus NameTypeMW Contribution
20084126DEEPCRK2
50/50
0.424
20084026DEEPCRK1
50/50
0.42
203955AF1-039 C O1
Solar/Wind Harmer
1.866
944781AF1-143 GEN
Solar/Wind Harmer
8.417
20083426SW_E13_K22
Solar/Wind Harmer
0.51
971427AH1-205 GEN
Solar/Wind Harmer
2.039
20088926STNY CRK
Solar/Wind Harmer
1.674
203839AF1-321 GEN
Solar/Wind Harmer
1.92
20084626FORWARD
Solar/Wind Harmer
0.751
203857AF2-221 C
Solar/Wind Harmer
1.206
970123AG2-090 GEN
Solar/Wind Harmer
1.125
203940AF1-140 C
Solar/Wind Harmer
0.343
971441AH1-212 GEN
Solar/Wind Harmer
1.042
972077AH1-588 GEN
Solar/Wind Harmer
4.943
972079AH1-589 GEN
Solar/Wind Harmer
4.071
238120AE2-309 GEN
Solar/Wind Helper
0.222
203844AF2-092 C
Solar/Wind Harmer
1.087
203850AG1-041 C
Solar/Wind Harmer
1.034
20092526R32
Solar/Wind Harmer
1.183
20091526CHSTN_FL
Solar/Wind Harmer
0.444
20083726HOMER C1
Adder
22.65
20083926HOMER C3
Adder
19.468
20083826HOMER C2
Adder
18.39
238126S14_GEN_1
Solar/Wind Helper
0.454
202652Y1-033 WT C
Solar/Wind Harmer
3.834
20089126CSLMN_L13
Solar/Wind Harmer
2.456
20089026BF_G21_K23
Solar/Wind Harmer
1.944
971419AH1-201 GEN
Solar/Wind Harmer
4.384
203841AF2-001_GEN
Solar/Wind Harmer
1.92
971879AH1-460 GEN
Solar/Wind Harmer
5.747
970125AG2-091 GEN
Solar/Wind Harmer
0.482
20079426CONEMAGH
Adder
0.589
238127S14_GEN_2
Solar/Wind Helper
0.454
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.391
971423AH1-203 GEN
Solar/Wind Harmer
10.422
203843AF2-002_GEN
Solar/Wind Harmer
0.96
970631AG2-411 GEN
Solar/Wind Harmer
5.982
20088826HIGHLAND
Solar/Wind Harmer
1.104
964201AG1-281 GEN
Solar/Wind Harmer
0.356
20094526CT_V3-030
Solar/Wind Harmer
0.306
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.131
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.409
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.941
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.614
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.186
G-007ALTFEXP_G-007A->PJM
CMTX
0.682
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.579
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT45_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT45_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.77 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:198.03
MW Contribution:5.63
Bus #Bus NameTypeMW Contribution
203844AF2-092 C
Solar/Wind Harmer
1.02
203850AG1-041 C
Solar/Wind Harmer
0.967
20092526R32
Solar/Wind Harmer
1.079
20091526CHSTN_FL
Solar/Wind Harmer
0.4
20083726HOMER C1
Adder
19.719
20083926HOMER C3
Adder
17.043
20083826HOMER C2
Adder
16.099
238126S14_GEN_1
Solar/Wind Helper
0.467
202652Y1-033 WT C
Solar/Wind Harmer
3.796
20089126CSLMN_L13
Solar/Wind Harmer
2.414
20089026BF_G21_K23
Solar/Wind Harmer
1.911
971419AH1-201 GEN
Solar/Wind Harmer
4.213
203841AF2-001_GEN
Solar/Wind Harmer
1.807
971879AH1-460 GEN
Solar/Wind Harmer
5.363
970125AG2-091 GEN
Solar/Wind Harmer
0.447
238127S14_GEN_2
Solar/Wind Helper
0.467
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.351
971423AH1-203 GEN
Solar/Wind Harmer
10.047
203843AF2-002_GEN
Solar/Wind Harmer
0.903
970631AG2-411 GEN
Solar/Wind Harmer
5.628
20088826HIGHLAND
Solar/Wind Harmer
1.007
964201AG1-281 GEN
Solar/Wind Harmer
0.324
20084126DEEPCRK2
50/50
0.422
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
1.848
944781AF1-143 GEN
Solar/Wind Harmer
8.275
20083426SW_E13_K22
Solar/Wind Harmer
0.495
971427AH1-205 GEN
Solar/Wind Harmer
1.96
20088926STNY CRK
Solar/Wind Harmer
1.608
203839AF1-321 GEN
Solar/Wind Harmer
1.807
20084626FORWARD
Solar/Wind Harmer
0.706
203857AF2-221 C
Solar/Wind Harmer
1.117
970123AG2-090 GEN
Solar/Wind Harmer
1.042
203940AF1-140 C
Solar/Wind Harmer
0.316
971441AH1-212 GEN
Solar/Wind Harmer
0.929
972077AH1-588 GEN
Solar/Wind Harmer
4.398
972079AH1-589 GEN
Solar/Wind Harmer
3.623
238120AE2-309 GEN
Solar/Wind Helper
0.23
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.191
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.595
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
3.376
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.141
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.886
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.235
G-007ALTFEXP_G-007A->PJM
CMTX
1.211
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.985
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P7-1_MP-138-018_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_MP-138-018_SRT-SL
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.88 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:195.0
MW Contribution:5.38
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.726
20089126CSLMN_L13
Solar/Wind Harmer
2.361
20089026BF_G21_K23
Solar/Wind Harmer
1.869
971419AH1-201 GEN
Solar/Wind Harmer
4.074
203841AF2-001_GEN
Solar/Wind Harmer
1.728
971879AH1-460 GEN
Solar/Wind Harmer
5.11
970125AG2-091 GEN
Solar/Wind Harmer
0.424
238127S14_GEN_2
Solar/Wind Helper
0.513
238118U2-030_1
Solar/Wind Helper
0.144
20084126DEEPCRK2
50/50
0.416
20084026DEEPCRK1
50/50
0.411
203955AF1-039 C O1
Solar/Wind Harmer
1.814
944781AF1-143 GEN
Solar/Wind Harmer
8.093
20083426SW_E13_K22
Solar/Wind Harmer
0.48
971427AH1-205 GEN
Solar/Wind Harmer
1.895
20088926STNY CRK
Solar/Wind Harmer
1.555
203839AF1-321 GEN
Solar/Wind Harmer
1.728
20084626FORWARD
Solar/Wind Harmer
0.675
203857AF2-221 C
Solar/Wind Harmer
1.06
970123AG2-090 GEN
Solar/Wind Harmer
0.99
203940AF1-140 C
Solar/Wind Harmer
0.298
971441AH1-212 GEN
Solar/Wind Harmer
0.863
238120AE2-309 GEN
Solar/Wind Helper
0.257
23585401KL_K28_T16
Solar/Wind Helper
0.628
203844AF2-092 C
Solar/Wind Harmer
0.974
203850AG1-041 C
Solar/Wind Harmer
0.922
20092526R32
Solar/Wind Harmer
1.017
20083726HOMER C1
Adder
17.398
20083926HOMER C3
Adder
15
20083826HOMER C2
Adder
14.169
238126S14_GEN_1
Solar/Wind Helper
0.513
20081326YOUGH
50/50
0.178
20089226LOOKOUT
Solar/Wind Harmer
2.299
971423AH1-203 GEN
Solar/Wind Harmer
9.731
203843AF2-002_GEN
Solar/Wind Harmer
0.864
970631AG2-411 GEN
Solar/Wind Harmer
5.381
20088826HIGHLAND
Solar/Wind Harmer
0.949
964201AG1-281 GEN
Solar/Wind Harmer
0.304
235531U2-073 GEN
Solar/Wind Helper
1.401
238117U2-030
Solar/Wind Helper
0.144
235054AD2-180 GEN
Solar/Wind Helper
0.761
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.125
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.388
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.103
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.585
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.176
G-007ALTFEXP_G-007A->PJM
CMTX
0.721
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.857
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_MP-138-150_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-138-150_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.76 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:191.61
MW Contribution:4.17
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
2.859
20089126CSLMN_L13
Solar/Wind Harmer
1.814
20089026BF_G21_K23
Solar/Wind Harmer
1.436
971419AH1-201 GEN
Solar/Wind Harmer
3.142
203841AF2-001_GEN
Solar/Wind Harmer
1.338
971879AH1-460 GEN
Solar/Wind Harmer
3.963
970125AG2-091 GEN
Solar/Wind Harmer
0.329
238127S14_GEN_2
Solar/Wind Helper
1.008
238118U2-030_1
Solar/Wind Helper
0.284
20081326YOUGH
50/50
0.136
20089226LOOKOUT
Solar/Wind Harmer
1.766
971423AH1-203 GEN
Solar/Wind Harmer
7.502
203843AF2-002_GEN
Solar/Wind Harmer
0.669
970631AG2-411 GEN
Solar/Wind Harmer
4.168
20088826HIGHLAND
Solar/Wind Harmer
0.738
235531U2-073 GEN
Solar/Wind Helper
2.718
238117U2-030
Solar/Wind Helper
0.284
20084126DEEPCRK2
50/50
0.319
20084026DEEPCRK1
50/50
0.315
203955AF1-039 C O1
Solar/Wind Harmer
1.392
944781AF1-143 GEN
Solar/Wind Harmer
6.218
20083426SW_E13_K22
Solar/Wind Harmer
0.37
971427AH1-205 GEN
Solar/Wind Harmer
1.461
20088926STNY CRK
Solar/Wind Harmer
1.199
203839AF1-321 GEN
Solar/Wind Harmer
1.338
20084626FORWARD
Solar/Wind Harmer
0.523
203857AF2-221 C
Solar/Wind Harmer
0.823
970123AG2-090 GEN
Solar/Wind Harmer
0.768
203940AF1-140 C
Solar/Wind Harmer
0.232
238120AE2-309 GEN
Solar/Wind Helper
0.461
203844AF2-092 C
Solar/Wind Harmer
0.754
203850AG1-041 C
Solar/Wind Harmer
0.714
20092526R32
Solar/Wind Harmer
0.791
20083726HOMER C1
Adder
13.846
20083926HOMER C3
Adder
12.072
20083826HOMER C2
Adder
11.404
238126S14_GEN_1
Solar/Wind Helper
1.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.163
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.951
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.082
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.271
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.15
G-007ALTFEXP_G-007A->PJM
CMTX
0.321
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.745
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-115-3A2_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-3A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.35 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:190.97
MW Contribution:5.87
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.914
20089126CSLMN_L13
Solar/Wind Harmer
2.554
20089026BF_G21_K23
Solar/Wind Harmer
2.022
971419AH1-201 GEN
Solar/Wind Harmer
5.865
203841AF2-001_GEN
Solar/Wind Harmer
1.895
971879AH1-460 GEN
Solar/Wind Harmer
5.458
970125AG2-091 GEN
Solar/Wind Harmer
0.442
238127S14_GEN_2
Solar/Wind Helper
0.445
20092526R32
Solar/Wind Harmer
0.88
20083726HOMER C1
Adder
17.806
20083926HOMER C3
Adder
15.295
20083826HOMER C2
Adder
14.448
238126S14_GEN_1
Solar/Wind Helper
0.445
20081326YOUGH
50/50
0.185
20089226LOOKOUT
Solar/Wind Harmer
2.487
971423AH1-203 GEN
Solar/Wind Harmer
12.931
203843AF2-002_GEN
Solar/Wind Harmer
0.947
970631AG2-411 GEN
Solar/Wind Harmer
5.871
20088826HIGHLAND
Solar/Wind Harmer
0.821
20084126DEEPCRK2
50/50
0.427
20084026DEEPCRK1
50/50
0.422
203955AF1-039 C O1
Solar/Wind Harmer
1.905
944781AF1-143 GEN
Solar/Wind Harmer
8.755
20088926STNY CRK
Solar/Wind Harmer
2.257
971427AH1-205 GEN
Solar/Wind Harmer
2.728
20083426SW_E13_K22
Solar/Wind Harmer
0.55
203839AF1-321 GEN
Solar/Wind Harmer
1.895
20084626FORWARD
Solar/Wind Harmer
0.737
203857AF2-221 C
Solar/Wind Harmer
1.105
970123AG2-090 GEN
Solar/Wind Harmer
1.031
238120AE2-309 GEN
Solar/Wind Helper
0.218
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.137
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.427
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.165
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.64
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.182
G-007ALTFEXP_G-007A->PJM
CMTX
0.771
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.94
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-2_MP-138-001_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-001_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:118.65 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:189.83
MW Contribution:5.41
Bus #Bus NameTypeMW Contribution
20081326YOUGH
50/50
0.177
20089226LOOKOUT
Solar/Wind Harmer
2.297
971423AH1-203 GEN
Solar/Wind Harmer
9.744
203843AF2-002_GEN
Solar/Wind Harmer
0.868
970631AG2-411 GEN
Solar/Wind Harmer
5.406
20088826HIGHLAND
Solar/Wind Harmer
0.956
964201AG1-281 GEN
Solar/Wind Harmer
0.307
235531U2-073 GEN
Solar/Wind Helper
1.401
238117U2-030
Solar/Wind Helper
0.143
235054AD2-180 GEN
Solar/Wind Helper
0.793
23751201ROTHROCK
Solar/Wind Helper
0.342
238185AF2-356 C
Solar/Wind Helper
0.968
203844AF2-092 C
Solar/Wind Harmer
0.979
203850AG1-041 C
Solar/Wind Harmer
0.927
20092526R32
Solar/Wind Harmer
1.025
20083726HOMER C1
Adder
17.789
20083926HOMER C3
Adder
15.413
20083826HOMER C2
Adder
14.559
238126S14_GEN_1
Solar/Wind Helper
0.518
202652Y1-033 WT C
Solar/Wind Harmer
3.719
20089126CSLMN_L13
Solar/Wind Harmer
2.359
20089026BF_G21_K23
Solar/Wind Harmer
1.867
971419AH1-201 GEN
Solar/Wind Harmer
4.081
203841AF2-001_GEN
Solar/Wind Harmer
1.736
971879AH1-460 GEN
Solar/Wind Harmer
5.138
970125AG2-091 GEN
Solar/Wind Harmer
0.427
238127S14_GEN_2
Solar/Wind Helper
0.518
238118U2-030_1
Solar/Wind Helper
0.143
20084126DEEPCRK2
50/50
0.415
20084026DEEPCRK1
50/50
0.41
203955AF1-039 C O1
Solar/Wind Harmer
1.81
944781AF1-143 GEN
Solar/Wind Harmer
8.085
20083426SW_E13_K22
Solar/Wind Harmer
0.481
971427AH1-205 GEN
Solar/Wind Harmer
1.898
20088926STNY CRK
Solar/Wind Harmer
1.558
203839AF1-321 GEN
Solar/Wind Harmer
1.736
20084626FORWARD
Solar/Wind Harmer
0.678
203857AF2-221 C
Solar/Wind Harmer
1.067
970123AG2-090 GEN
Solar/Wind Harmer
0.996
203940AF1-140 C
Solar/Wind Harmer
0.3
971441AH1-212 GEN
Solar/Wind Harmer
0.873
238120AE2-309 GEN
Solar/Wind Helper
0.261
23585401KL_K28_T16
Solar/Wind Helper
0.656
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.132
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.41
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.135
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.111
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.618
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.19
G-007ALTFEXP_G-007A->PJM
CMTX
0.757
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.998
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT16_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT16_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.75 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:188.4
MW Contribution:5.6
Bus #Bus NameTypeMW Contribution
203844AF2-092 C
Solar/Wind Harmer
1.014
203850AG1-041 C
Solar/Wind Harmer
0.961
20092526R32
Solar/Wind Harmer
1.07
20091526CHSTN_FL
Solar/Wind Harmer
0.396
20083726HOMER C1
Adder
19.201
20083926HOMER C3
Adder
16.692
20083826HOMER C2
Adder
15.768
238126S14_GEN_1
Solar/Wind Helper
0.463
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.35
971423AH1-203 GEN
Solar/Wind Harmer
10.022
203843AF2-002_GEN
Solar/Wind Harmer
0.899
970631AG2-411 GEN
Solar/Wind Harmer
5.598
20088826HIGHLAND
Solar/Wind Harmer
0.998
964201AG1-281 GEN
Solar/Wind Harmer
0.321
202652Y1-033 WT C
Solar/Wind Harmer
3.798
20089126CSLMN_L13
Solar/Wind Harmer
2.414
20089026BF_G21_K23
Solar/Wind Harmer
1.91
971419AH1-201 GEN
Solar/Wind Harmer
4.201
203841AF2-001_GEN
Solar/Wind Harmer
1.797
971879AH1-460 GEN
Solar/Wind Harmer
5.331
970125AG2-091 GEN
Solar/Wind Harmer
0.444
238127S14_GEN_2
Solar/Wind Helper
0.463
20084126DEEPCRK2
50/50
0.423
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
1.849
944781AF1-143 GEN
Solar/Wind Harmer
8.272
20083426SW_E13_K22
Solar/Wind Harmer
0.494
971427AH1-205 GEN
Solar/Wind Harmer
1.954
20088926STNY CRK
Solar/Wind Harmer
1.604
203839AF1-321 GEN
Solar/Wind Harmer
1.797
20084626FORWARD
Solar/Wind Harmer
0.702
203857AF2-221 C
Solar/Wind Harmer
1.109
970123AG2-090 GEN
Solar/Wind Harmer
1.035
203940AF1-140 C
Solar/Wind Harmer
0.313
971441AH1-212 GEN
Solar/Wind Harmer
0.919
238120AE2-309 GEN
Solar/Wind Helper
0.228
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.167
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.521
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.781
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.781
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.225
G-007ALTFEXP_G-007A->PJM
CMTX
0.992
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.599
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-2_PN-115-073_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-073_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:117.15 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:187.44
MW Contribution:5.33
Bus #Bus NameTypeMW Contribution
20081326YOUGH
50/50
0.185
20089226LOOKOUT
Solar/Wind Harmer
2.462
971423AH1-203 GEN
Solar/Wind Harmer
12.687
203843AF2-002_GEN
Solar/Wind Harmer
0.907
970631AG2-411 GEN
Solar/Wind Harmer
5.335
20088826HIGHLAND
Solar/Wind Harmer
0.886
964201AG1-281 GEN
Solar/Wind Harmer
0.262
203844AF2-092 C
Solar/Wind Harmer
0.732
203850AG1-041 C
Solar/Wind Harmer
0.706
20092526R32
Solar/Wind Harmer
0.949
20083726HOMER C1
Adder
17.674
20083926HOMER C3
Adder
15.223
20083826HOMER C2
Adder
14.38
238126S14_GEN_1
Solar/Wind Helper
0.447
202652Y1-033 WT C
Solar/Wind Harmer
3.893
20089126CSLMN_L13
Solar/Wind Harmer
2.528
20089026BF_G21_K23
Solar/Wind Harmer
2.001
971419AH1-201 GEN
Solar/Wind Harmer
5.754
203841AF2-001_GEN
Solar/Wind Harmer
1.814
971879AH1-460 GEN
Solar/Wind Harmer
5.293
970125AG2-091 GEN
Solar/Wind Harmer
0.434
238127S14_GEN_2
Solar/Wind Helper
0.447
20084126DEEPCRK2
50/50
0.426
20084026DEEPCRK1
50/50
0.421
203955AF1-039 C O1
Solar/Wind Harmer
1.895
944781AF1-143 GEN
Solar/Wind Harmer
8.666
20088926STNY CRK
Solar/Wind Harmer
2.214
971427AH1-205 GEN
Solar/Wind Harmer
2.676
20083426SW_E13_K22
Solar/Wind Harmer
0.539
203839AF1-321 GEN
Solar/Wind Harmer
1.814
20084626FORWARD
Solar/Wind Harmer
0.669
203857AF2-221 C
Solar/Wind Harmer
1.085
970123AG2-090 GEN
Solar/Wind Harmer
1.012
203940AF1-140 C
Solar/Wind Harmer
0.25
238120AE2-309 GEN
Solar/Wind Helper
0.219
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.433
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.203
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.648
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.184
G-007ALTFEXP_G-007A->PJM
CMTX
0.784
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.971
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-2_WP-138-033T_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-033T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:116.93 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:187.08
MW Contribution:5.67
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.805
20089126CSLMN_L13
Solar/Wind Harmer
2.421
20089026BF_G21_K23
Solar/Wind Harmer
1.917
971419AH1-201 GEN
Solar/Wind Harmer
4.234
203841AF2-001_GEN
Solar/Wind Harmer
1.82
971879AH1-460 GEN
Solar/Wind Harmer
5.405
970125AG2-091 GEN
Solar/Wind Harmer
0.45
20079426CONEMAGH
Adder
0.526
238127S14_GEN_2
Solar/Wind Helper
0.458
20084126DEEPCRK2
50/50
0.423
20084026DEEPCRK1
50/50
0.419
203955AF1-039 C O1
Solar/Wind Harmer
1.852
944781AF1-143 GEN
Solar/Wind Harmer
8.299
20083426SW_E13_K22
Solar/Wind Harmer
0.497
971427AH1-205 GEN
Solar/Wind Harmer
1.969
20088926STNY CRK
Solar/Wind Harmer
1.616
203839AF1-321 GEN
Solar/Wind Harmer
1.82
20084626FORWARD
Solar/Wind Harmer
0.711
203857AF2-221 C
Solar/Wind Harmer
1.126
970123AG2-090 GEN
Solar/Wind Harmer
1.051
203940AF1-140 C
Solar/Wind Harmer
0.318
971441AH1-212 GEN
Solar/Wind Harmer
0.941
238120AE2-309 GEN
Solar/Wind Helper
0.224
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.358
971423AH1-203 GEN
Solar/Wind Harmer
10.094
203843AF2-002_GEN
Solar/Wind Harmer
0.91
970631AG2-411 GEN
Solar/Wind Harmer
5.667
20088826HIGHLAND
Solar/Wind Harmer
1.016
964201AG1-281 GEN
Solar/Wind Harmer
0.326
203844AF2-092 C
Solar/Wind Harmer
1.027
203850AG1-041 C
Solar/Wind Harmer
0.974
20092526R32
Solar/Wind Harmer
1.089
20091526CHSTN_FL
Solar/Wind Harmer
0.403
20083726HOMER C1
Adder
19.24
20083926HOMER C3
Adder
16.514
20083826HOMER C2
Adder
15.599
238126S14_GEN_1
Solar/Wind Helper
0.458
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.155
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.483
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.518
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.117
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.197
G-007ALTFEXP_G-007A->PJM
CMTX
0.899
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.397
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P7-1_MP-138-056_SRT-A-1


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_MP-138-056_SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.71 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:186.73
MW Contribution:5.45
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.749
20089126CSLMN_L13
Solar/Wind Harmer
2.378
20089026BF_G21_K23
Solar/Wind Harmer
1.882
971419AH1-201 GEN
Solar/Wind Harmer
4.113
203841AF2-001_GEN
Solar/Wind Harmer
1.749
971879AH1-460 GEN
Solar/Wind Harmer
5.177
970125AG2-091 GEN
Solar/Wind Harmer
0.43
20084126DEEPCRK2
50/50
0.418
20084026DEEPCRK1
50/50
0.413
203955AF1-039 C O1
Solar/Wind Harmer
1.825
944781AF1-143 GEN
Solar/Wind Harmer
8.149
20083426SW_E13_K22
Solar/Wind Harmer
0.485
971427AH1-205 GEN
Solar/Wind Harmer
1.913
20088926STNY CRK
Solar/Wind Harmer
1.57
203839AF1-321 GEN
Solar/Wind Harmer
1.749
20084626FORWARD
Solar/Wind Harmer
0.683
203857AF2-221 C
Solar/Wind Harmer
1.075
970123AG2-090 GEN
Solar/Wind Harmer
1.003
203940AF1-140 C
Solar/Wind Harmer
0.303
971441AH1-212 GEN
Solar/Wind Harmer
0.88
203844AF2-092 C
Solar/Wind Harmer
0.986
203850AG1-041 C
Solar/Wind Harmer
0.934
20092526R32
Solar/Wind Harmer
1.032
20083726HOMER C1
Adder
17.909
20083926HOMER C3
Adder
15.516
20081326YOUGH
50/50
0.179
20089226LOOKOUT
Solar/Wind Harmer
2.315
971423AH1-203 GEN
Solar/Wind Harmer
9.82
203843AF2-002_GEN
Solar/Wind Harmer
0.875
970631AG2-411 GEN
Solar/Wind Harmer
5.447
20088826HIGHLAND
Solar/Wind Harmer
0.963
964201AG1-281 GEN
Solar/Wind Harmer
0.309
20083826HOMER C2
Adder
14.657
238126S14_GEN_1
Solar/Wind Helper
0.508
238127S14_GEN_2
Solar/Wind Helper
0.508
238118U2-030_1
Solar/Wind Helper
0.153
238117U2-030
Solar/Wind Helper
0.153
235531U2-073 GEN
Solar/Wind Helper
1.461
238120AE2-309 GEN
Solar/Wind Helper
0.254
23585401KL_K28_T16
Solar/Wind Helper
0.572
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.135
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.42
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.169
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.113
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.632
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.193
G-007ALTFEXP_G-007A->PJM
CMTX
0.769
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.036
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.67 %
Rating:133.0 MVA
Rating Type:A
MVA to Mitigate:144.53
MW Contribution:4.13
Bus #Bus NameTypeMW Contribution
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
0.361
971423AH1-203 GEN
Solar/Wind Harmer
6.919
203843AF2-002_GEN
Solar/Wind Harmer
0.615
970631AG2-411 GEN
Solar/Wind Harmer
4.126
20088826HIGHLAND
Solar/Wind Harmer
0
202652Y1-033 WT C
Solar/Wind Harmer
0.002
20089126CSLMN_L13
Solar/Wind Harmer
0.126
20089026BF_G21_K23
Solar/Wind Harmer
0.128
971419AH1-201 GEN
Solar/Wind Harmer
3.65
203841AF2-001_GEN
Solar/Wind Harmer
1.231
971879AH1-460 GEN
Solar/Wind Harmer
3.641
970125AG2-091 GEN
Solar/Wind Harmer
0.302
238127S14_GEN_2
Solar/Wind Helper
0.458
20050326C.SLOPE
50/50
0.142
203844AF2-092 C
Solar/Wind Harmer
0.694
203850AG1-041 C
Solar/Wind Harmer
0.657
20092526R32
Solar/Wind Harmer
0.125
20091526CHSTN_FL
Solar/Wind Harmer
0.054
20083726HOMER C1
Adder
17.911
20083926HOMER C3
Adder
15.469
20083826HOMER C2
Adder
14.612
238126S14_GEN_1
Solar/Wind Helper
0.458
20084126DEEPCRK2
50/50
0.423
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
0.003
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
971427AH1-205 GEN
Solar/Wind Harmer
2.433
20088926STNY CRK
Solar/Wind Harmer
0.174
203839AF1-321 GEN
Solar/Wind Harmer
1.231
20084626FORWARD
Solar/Wind Harmer
0
203857AF2-221 C
Solar/Wind Harmer
0.529
970123AG2-090 GEN
Solar/Wind Harmer
0.705
203940AF1-140 C
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
0.617
238120AE2-309 GEN
Solar/Wind Helper
0.224
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.143
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.445
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.294
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.666
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.188
G-007ALTFEXP_G-007A->PJM
CMTX
0.817
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.089
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-2


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.19 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:169.91
MW Contribution:4.13
Bus #Bus NameTypeMW Contribution
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
0.361
971423AH1-203 GEN
Solar/Wind Harmer
6.921
203843AF2-002_GEN
Solar/Wind Harmer
0.616
970631AG2-411 GEN
Solar/Wind Harmer
4.132
20088826HIGHLAND
Solar/Wind Harmer
0
202652Y1-033 WT C
Solar/Wind Harmer
0.002
20089126CSLMN_L13
Solar/Wind Harmer
0.126
20089026BF_G21_K23
Solar/Wind Harmer
0.128
971419AH1-201 GEN
Solar/Wind Harmer
3.652
203841AF2-001_GEN
Solar/Wind Harmer
1.232
971879AH1-460 GEN
Solar/Wind Harmer
3.647
970125AG2-091 GEN
Solar/Wind Harmer
0.303
238127S14_GEN_2
Solar/Wind Helper
0.468
20050326C.SLOPE
50/50
0.142
203844AF2-092 C
Solar/Wind Harmer
0.695
203850AG1-041 C
Solar/Wind Harmer
0.658
20092526R32
Solar/Wind Harmer
0.126
20091526CHSTN_FL
Solar/Wind Harmer
0.055
20083726HOMER C1
Adder
18.071
20083926HOMER C3
Adder
15.634
20083826HOMER C2
Adder
14.768
238126S14_GEN_1
Solar/Wind Helper
0.468
20084126DEEPCRK2
50/50
0.422
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
0.003
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
971427AH1-205 GEN
Solar/Wind Harmer
2.435
20088926STNY CRK
Solar/Wind Harmer
0.174
203839AF1-321 GEN
Solar/Wind Harmer
1.232
20084626FORWARD
Solar/Wind Harmer
0
203857AF2-221 C
Solar/Wind Harmer
0.53
970123AG2-090 GEN
Solar/Wind Harmer
0.707
203940AF1-140 C
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
0.619
238120AE2-309 GEN
Solar/Wind Helper
0.231
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.129
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.402
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.046
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.609
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.193
G-007ALTFEXP_G-007A->PJM
CMTX
0.723
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.988
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P1-2_PE-500-004_SRT-SL-1


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-004_SRT-SL-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.91 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:167.86
MW Contribution:4.13
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
0.002
20089126CSLMN_L13
Solar/Wind Harmer
0.126
20089026BF_G21_K23
Solar/Wind Harmer
0.128
971419AH1-201 GEN
Solar/Wind Harmer
3.652
203841AF2-001_GEN
Solar/Wind Harmer
1.233
971879AH1-460 GEN
Solar/Wind Harmer
3.648
970125AG2-091 GEN
Solar/Wind Harmer
0.303
238127S14_GEN_2
Solar/Wind Helper
0.468
20050326C.SLOPE
50/50
0.142
203844AF2-092 C
Solar/Wind Harmer
0.695
203850AG1-041 C
Solar/Wind Harmer
0.658
20092526R32
Solar/Wind Harmer
0.126
20091526CHSTN_FL
Solar/Wind Harmer
0.055
20083726HOMER C1
Adder
18.078
20083926HOMER C3
Adder
15.642
20083826HOMER C2
Adder
14.776
238126S14_GEN_1
Solar/Wind Helper
0.468
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
0.361
971423AH1-203 GEN
Solar/Wind Harmer
6.922
203843AF2-002_GEN
Solar/Wind Harmer
0.616
970631AG2-411 GEN
Solar/Wind Harmer
4.133
20088826HIGHLAND
Solar/Wind Harmer
0
20084126DEEPCRK2
50/50
0.422
20084026DEEPCRK1
50/50
0.418
203955AF1-039 C O1
Solar/Wind Harmer
0.003
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
971427AH1-205 GEN
Solar/Wind Harmer
2.435
20088926STNY CRK
Solar/Wind Harmer
0.175
203839AF1-321 GEN
Solar/Wind Harmer
1.233
20084626FORWARD
Solar/Wind Harmer
0
203857AF2-221 C
Solar/Wind Harmer
0.53
970123AG2-090 GEN
Solar/Wind Harmer
0.707
203940AF1-140 C
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
0.619
238120AE2-309 GEN
Solar/Wind Helper
0.231
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.128
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.4
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.054
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.606
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.192
G-007ALTFEXP_G-007A->PJM
CMTX
0.725
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.994
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-C_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.21
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.426
20083426SW_E13_K22
Solar/Wind Harmer
0.512
971427AH1-205 GEN
Solar/Wind Harmer
2.043
20088926STNY CRK
Solar/Wind Harmer
1.678
203839AF1-321 GEN
Solar/Wind Harmer
1.93
20084626FORWARD
Solar/Wind Harmer
0.755
203857AF2-221 C
Solar/Wind Harmer
1.207
970123AG2-090 GEN
Solar/Wind Harmer
1.126
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.034
972077AH1-588 GEN
Solar/Wind Harmer
5.449
972079AH1-589 GEN
Solar/Wind Harmer
4.488
238120AE2-309 GEN
Solar/Wind Helper
0.222
20089226LOOKOUT
Solar/Wind Harmer
2.394
971423AH1-203 GEN
Solar/Wind Harmer
10.443
203843AF2-002_GEN
Solar/Wind Harmer
0.965
970631AG2-411 GEN
Solar/Wind Harmer
6.015
20088826HIGHLAND
Solar/Wind Harmer
1.1
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20094526CT_V3-030
Solar/Wind Harmer
0.307
203844AF2-092 C
Solar/Wind Harmer
1.088
203850AG1-041 C
Solar/Wind Harmer
1.035
20092526R32
Solar/Wind Harmer
1.179
20091526CHSTN_FL
Solar/Wind Harmer
0.443
20083726HOMER C1
Adder
25.826
20083926HOMER C3
Adder
21.998
20083826HOMER C2
Adder
20.779
238126S14_GEN_1
Solar/Wind Helper
0.454
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20089026BF_G21_K23
Solar/Wind Harmer
1.946
971419AH1-201 GEN
Solar/Wind Harmer
4.393
203841AF2-001_GEN
Solar/Wind Harmer
1.93
971879AH1-460 GEN
Solar/Wind Harmer
5.764
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.573
238127S14_GEN_2
Solar/Wind Helper
0.454
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.649
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
G-007ALTFEXP_G-007A->PJM
CMTX
0.847
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.212
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.21
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20089026BF_G21_K23
Solar/Wind Harmer
1.946
971419AH1-201 GEN
Solar/Wind Harmer
4.393
203841AF2-001_GEN
Solar/Wind Harmer
1.93
971879AH1-460 GEN
Solar/Wind Harmer
5.764
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.573
238127S14_GEN_2
Solar/Wind Helper
0.454
20089226LOOKOUT
Solar/Wind Harmer
2.394
971423AH1-203 GEN
Solar/Wind Harmer
10.443
203843AF2-002_GEN
Solar/Wind Harmer
0.965
970631AG2-411 GEN
Solar/Wind Harmer
6.015
20088826HIGHLAND
Solar/Wind Harmer
1.1
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20094526CT_V3-030
Solar/Wind Harmer
0.307
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.426
20083426SW_E13_K22
Solar/Wind Harmer
0.512
971427AH1-205 GEN
Solar/Wind Harmer
2.043
20088926STNY CRK
Solar/Wind Harmer
1.678
203839AF1-321 GEN
Solar/Wind Harmer
1.93
20084626FORWARD
Solar/Wind Harmer
0.755
203857AF2-221 C
Solar/Wind Harmer
1.207
970123AG2-090 GEN
Solar/Wind Harmer
1.126
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.034
972077AH1-588 GEN
Solar/Wind Harmer
5.449
972079AH1-589 GEN
Solar/Wind Harmer
4.488
238120AE2-309 GEN
Solar/Wind Helper
0.222
203844AF2-092 C
Solar/Wind Harmer
1.088
203850AG1-041 C
Solar/Wind Harmer
1.035
20092526R32
Solar/Wind Harmer
1.179
20091526CHSTN_FL
Solar/Wind Harmer
0.443
20083726HOMER C1
Adder
25.826
20083926HOMER C3
Adder
21.998
20083826HOMER C2
Adder
20.779
238126S14_GEN_1
Solar/Wind Helper
0.454
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.649
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
G-007ALTFEXP_G-007A->PJM
CMTX
0.847
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.212
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-B_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.21
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.426
20083426SW_E13_K22
Solar/Wind Harmer
0.512
971427AH1-205 GEN
Solar/Wind Harmer
2.043
20088926STNY CRK
Solar/Wind Harmer
1.678
203839AF1-321 GEN
Solar/Wind Harmer
1.93
20084626FORWARD
Solar/Wind Harmer
0.755
203857AF2-221 C
Solar/Wind Harmer
1.207
970123AG2-090 GEN
Solar/Wind Harmer
1.126
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.034
972077AH1-588 GEN
Solar/Wind Harmer
5.449
972079AH1-589 GEN
Solar/Wind Harmer
4.488
238120AE2-309 GEN
Solar/Wind Helper
0.222
20089226LOOKOUT
Solar/Wind Harmer
2.394
971423AH1-203 GEN
Solar/Wind Harmer
10.443
203843AF2-002_GEN
Solar/Wind Harmer
0.965
970631AG2-411 GEN
Solar/Wind Harmer
6.015
20088826HIGHLAND
Solar/Wind Harmer
1.1
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20094526CT_V3-030
Solar/Wind Harmer
0.307
203844AF2-092 C
Solar/Wind Harmer
1.088
203850AG1-041 C
Solar/Wind Harmer
1.035
20092526R32
Solar/Wind Harmer
1.179
20091526CHSTN_FL
Solar/Wind Harmer
0.443
20083726HOMER C1
Adder
25.826
20083926HOMER C3
Adder
21.998
20083826HOMER C2
Adder
20.779
238126S14_GEN_1
Solar/Wind Helper
0.454
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20089026BF_G21_K23
Solar/Wind Harmer
1.946
971419AH1-201 GEN
Solar/Wind Harmer
4.393
203841AF2-001_GEN
Solar/Wind Harmer
1.93
971879AH1-460 GEN
Solar/Wind Harmer
5.764
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.573
238127S14_GEN_2
Solar/Wind Helper
0.454
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.388
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.649
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
G-007ALTFEXP_G-007A->PJM
CMTX
0.847
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.212
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0201A-20_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.93 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:186.03
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.423
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.042
20088926STNY CRK
Solar/Wind Harmer
1.676
203839AF1-321 GEN
Solar/Wind Harmer
1.928
20084626FORWARD
Solar/Wind Harmer
0.754
203857AF2-221 C
Solar/Wind Harmer
1.205
970123AG2-090 GEN
Solar/Wind Harmer
1.125
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.034
972077AH1-588 GEN
Solar/Wind Harmer
5.407
972079AH1-589 GEN
Solar/Wind Harmer
4.454
238120AE2-309 GEN
Solar/Wind Helper
0.222
20089226LOOKOUT
Solar/Wind Harmer
2.393
971423AH1-203 GEN
Solar/Wind Harmer
10.435
203843AF2-002_GEN
Solar/Wind Harmer
0.964
970631AG2-411 GEN
Solar/Wind Harmer
6.007
20088826HIGHLAND
Solar/Wind Harmer
1.098
203844AF2-092 C
Solar/Wind Harmer
1.087
203850AG1-041 C
Solar/Wind Harmer
1.033
20092526R32
Solar/Wind Harmer
1.177
20091526CHSTN_FL
Solar/Wind Harmer
0.442
20083726HOMER C1
Adder
25.482
20083926HOMER C3
Adder
21.742
20083826HOMER C2
Adder
20.538
238126S14_GEN_1
Solar/Wind Helper
0.454
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20089026BF_G21_K23
Solar/Wind Harmer
1.945
971419AH1-201 GEN
Solar/Wind Harmer
4.389
203841AF2-001_GEN
Solar/Wind Harmer
1.928
971879AH1-460 GEN
Solar/Wind Harmer
5.756
970125AG2-091 GEN
Solar/Wind Harmer
0.482
20079426CONEMAGH
Adder
0.574
238127S14_GEN_2
Solar/Wind Helper
0.454
964201AG1-281 GEN
Solar/Wind Harmer
0.354
20094526CT_V3-030
Solar/Wind Harmer
0.31
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.139
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.433
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.373
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.111
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.647
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.188
G-007ALTFEXP_G-007A->PJM
CMTX
0.842
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.169
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.27 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:184.85
MW Contribution:5.51
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.789
20089126CSLMN_L13
Solar/Wind Harmer
2.404
20089026BF_G21_K23
Solar/Wind Harmer
1.903
971419AH1-201 GEN
Solar/Wind Harmer
4.158
203841AF2-001_GEN
Solar/Wind Harmer
1.769
971879AH1-460 GEN
Solar/Wind Harmer
5.236
970125AG2-091 GEN
Solar/Wind Harmer
0.435
238127S14_GEN_2
Solar/Wind Helper
0.468
203955AF1-039 C O1
Solar/Wind Harmer
1.845
944781AF1-143 GEN
Solar/Wind Harmer
8.238
20083426SW_E13_K22
Solar/Wind Harmer
0.49
971427AH1-205 GEN
Solar/Wind Harmer
1.934
20088926STNY CRK
Solar/Wind Harmer
1.587
203839AF1-321 GEN
Solar/Wind Harmer
1.769
20084626FORWARD
Solar/Wind Harmer
0.691
203857AF2-221 C
Solar/Wind Harmer
1.087
970123AG2-090 GEN
Solar/Wind Harmer
1.015
203940AF1-140 C
Solar/Wind Harmer
0.306
971441AH1-212 GEN
Solar/Wind Harmer
0.89
238120AE2-309 GEN
Solar/Wind Helper
0.231
20089226LOOKOUT
Solar/Wind Harmer
2.34
971423AH1-203 GEN
Solar/Wind Harmer
9.929
203843AF2-002_GEN
Solar/Wind Harmer
0.885
970631AG2-411 GEN
Solar/Wind Harmer
5.509
20088826HIGHLAND
Solar/Wind Harmer
0.975
964201AG1-281 GEN
Solar/Wind Harmer
0.313
203844AF2-092 C
Solar/Wind Harmer
0.997
203850AG1-041 C
Solar/Wind Harmer
0.945
20092526R32
Solar/Wind Harmer
1.044
20091526CHSTN_FL
Solar/Wind Harmer
0.384
20083726HOMER C1
Adder
18.155
20083926HOMER C3
Adder
15.723
20083826HOMER C2
Adder
14.852
238126S14_GEN_1
Solar/Wind Helper
0.468
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.121
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.377
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.139
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.572
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.185
G-007ALTFEXP_G-007A->PJM
CMTX
0.757
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.059
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HIGHPOINT-26PENN-MAR 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.4 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:181.51
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.835
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.421
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.041
20088926STNY CRK
Solar/Wind Harmer
1.676
203839AF1-321 GEN
Solar/Wind Harmer
1.923
20084626FORWARD
Solar/Wind Harmer
0.752
203857AF2-221 C
Solar/Wind Harmer
1.208
970123AG2-090 GEN
Solar/Wind Harmer
1.127
203940AF1-140 C
Solar/Wind Harmer
0.344
971441AH1-212 GEN
Solar/Wind Harmer
1.045
972077AH1-588 GEN
Solar/Wind Harmer
4.973
972079AH1-589 GEN
Solar/Wind Harmer
4.096
238120AE2-309 GEN
Solar/Wind Helper
0.222
20089226LOOKOUT
Solar/Wind Harmer
2.392
971423AH1-203 GEN
Solar/Wind Harmer
10.43
203843AF2-002_GEN
Solar/Wind Harmer
0.961
970631AG2-411 GEN
Solar/Wind Harmer
5.99
20088826HIGHLAND
Solar/Wind Harmer
1.106
964201AG1-281 GEN
Solar/Wind Harmer
0.357
20094526CT_V3-030
Solar/Wind Harmer
0.307
20089126CSLMN_L13
Solar/Wind Harmer
2.457
20089026BF_G21_K23
Solar/Wind Harmer
1.945
971419AH1-201 GEN
Solar/Wind Harmer
4.388
203841AF2-001_GEN
Solar/Wind Harmer
1.923
971879AH1-460 GEN
Solar/Wind Harmer
5.755
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.59
238127S14_GEN_2
Solar/Wind Helper
0.453
203844AF2-092 C
Solar/Wind Harmer
1.088
203850AG1-041 C
Solar/Wind Harmer
1.036
20092526R32
Solar/Wind Harmer
1.186
20091526CHSTN_FL
Solar/Wind Harmer
0.445
20083726HOMER C1
Adder
22.735
20083926HOMER C3
Adder
19.557
20083826HOMER C2
Adder
18.474
238126S14_GEN_1
Solar/Wind Helper
0.453
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.384
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.034
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.104
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.576
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.178
G-007ALTFEXP_G-007A->PJM
CMTX
0.717
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.65
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.2 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1295.55
MW Contribution:17.56
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.281
970125AG2-091 GEN
Solar/Wind Harmer
1.681
971879AH1-460 GEN
Solar/Wind Harmer
18.472
203841AF2-001_GEN
Solar/Wind Harmer
5.589
971419AH1-201 GEN
Solar/Wind Harmer
8.093
20079426CONEMAGH
Adder
3.005
20089126CSLMN_L13
Solar/Wind Harmer
1.834
20089026BF_G21_K23
Solar/Wind Harmer
1.452
971703AH1-357 GEN
Solar/Wind Harmer
4.001
971707AH1-359 GEN
Solar/Wind Harmer
4.001
971541AH1-268 GEN
Solar/Wind Harmer
6.841
20334926Z1-069 C
Solar/Wind Harmer
4.066
965131AG1-378 GEN
Solar/Wind Harmer
3.45
20082926HNSMLK 2
Adder
10.051
20083126HNSMLK 4
Adder
10.051
944411AF1-106 GEN
Solar/Wind Harmer
0.373
202652Y1-033 WT C
Solar/Wind Harmer
1.48
970335AG2-220 GEN
Solar/Wind Harmer
4.687
971127AH1-005 GEN
Solar/Wind Harmer
3.024
20120126WRREN CT
Adder
9.44
203854AF2-039 C
Solar/Wind Harmer
0.6
960051AF2-296 GEN
Solar/Wind Harmer
2.87
203818AF1-086 GEN
Solar/Wind Harmer
3.609
970647AG2-420 GEN
Solar/Wind Harmer
2.671
971185AH1-051 GEN
Solar/Wind Harmer
3.237
971355AH1-158 GEN
Solar/Wind Harmer
3.764
20335126GROZ1-110
Adder
3.122
20335226CANZ2-011
Adder
3.034
203856AF2-165 C
Solar/Wind Harmer
1.577
970899AG2-561 GEN
Solar/Wind Harmer
2.635
945751AF1-240 GEN
Solar/Wind Harmer
2.06
238202AE2-262_GEN
Solar/Wind Harmer
3.32
971627AH1-313 GEN
Solar/Wind Harmer
13.017
203932AE1-123
Adder
2.564
959441AF2-235 GEN
Solar/Wind Harmer
0.387
238219AF1-167 C
Solar/Wind Harmer
1.674
203948AG1-140 C
Solar/Wind Harmer
0.321
957161AF2-010 GEN
Solar/Wind Harmer
9.338
20328326MANOR_T86
Adder
0.172
203830AF1-094 GEN
Solar/Wind Harmer
0.733
203962AF1-287 GEN
Solar/Wind Harmer
2.376
962511AG1-100 GEN
Solar/Wind Harmer
0.716
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.451
972271AH1-720 GEN
Adder
7.368
200917MEHOOPANY_G
Solar/Wind Harmer
3.45
970679AG2-439 GEN
Solar/Wind Harmer
0.782
970643AG2-418 GEN
Solar/Wind Harmer
1.486
20080926SITHE
50/50
0.921
203857AF2-221 C
Solar/Wind Harmer
4.203
970123AG2-090 GEN
Solar/Wind Harmer
3.923
203839AF1-321 GEN
Solar/Wind Harmer
5.589
20084626FORWARD
Solar/Wind Harmer
2.204
20088626ARWF_N39
Solar/Wind Harmer
5.112
20303426NA_O38_P22
Solar/Wind Harmer
4.138
203940AF1-140 C
Solar/Wind Harmer
1.284
20088926STNY CRK
Solar/Wind Harmer
3.117
971427AH1-205 GEN
Solar/Wind Harmer
3.764
971441AH1-212 GEN
Solar/Wind Harmer
4.958
20083426SW_E13_K22
Solar/Wind Harmer
0.738
944781AF1-143 GEN
Solar/Wind Harmer
6.285
972077AH1-588 GEN
Solar/Wind Harmer
48.014
972079AH1-589 GEN
Solar/Wind Harmer
39.546
970715AG2-457 GEN
Solar/Wind Harmer
16.005
972075AH1-587 GEN
Solar/Wind Harmer
37.507
203952AE2-129 C
Solar/Wind Harmer
1.045
203946AE2-131 C
Solar/Wind Harmer
1.043
962411AG1-090 GEN
Solar/Wind Harmer
16.386
20398826ARMNA MT
Solar/Wind Harmer
3.926
203955AF1-039 C O1
Solar/Wind Harmer
0.721
203859AF2-294 C
Solar/Wind Harmer
2.598
970313AG2-206 GEN
Solar/Wind Harmer
7.221
970305AG2-200 GEN
Solar/Wind Harmer
2.986
946381AF1-302 GEN
Solar/Wind Harmer
3.044
203853AF1-134 C O1
Solar/Wind Harmer
0.868
238217AF1-153 C O1
Solar/Wind Harmer
0.857
203848AF2-166 C
Solar/Wind Harmer
2.614
203980AG1-197 GEN
Solar/Wind Harmer
0.568
216419AE2-001 C
Solar/Wind Harmer
2.453
203963AG1-253 GEN
Solar/Wind Harmer
0.49
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.419
971931AH1-490 GEN
Solar/Wind Harmer
2.369
203947AF1-006 C
Solar/Wind Harmer
0.629
20083726HOMER C1
50/50
286.383
20083926HOMER C3
50/50
233.562
20083826HOMER C2
50/50
220.627
20050326C.SLOPE
50/50
0.843
203961AE2-224 GEN
Solar/Wind Harmer
8.743
20092526R32
Solar/Wind Harmer
4.774
203844AF2-092 C
Solar/Wind Harmer
3.155
203850AG1-041 C
Solar/Wind Harmer
3.148
20091526CHSTN_FL
Solar/Wind Harmer
2.073
940863AE2-074 GEN
Solar/Wind Harmer
3.456
20090526Q36
Solar/Wind Harmer
3.014
203993AD2-133_GEN1
Solar/Wind Harmer
3.014
941231AE2-117 GEN
Solar/Wind Harmer
1.126
203804AE2-113_GEN
Solar/Wind Harmer
8.719
965121AG1-377 GEN
Solar/Wind Harmer
3.45
20083226HNSMLK 5
Adder
10.051
970555AG2-356 GEN
Solar/Wind Harmer
3.124
203855AF2-088 C
Solar/Wind Harmer
0.289
970663AG2-429 GEN
Solar/Wind Harmer
9.219
970663AG2-429 GEN
Solar/Wind Harmer
1.501
203846AF2-130 C
Solar/Wind Harmer
0.747
970677AG2-438 GEN
Solar/Wind Harmer
1.209
966771AG1-548 GEN
Solar/Wind Harmer
17.6
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.229
203926AA2-133 GEN
Adder
2.573
20334726NME_Y1-047
Adder
2.318
20390726Y2-042
Adder
1.871
971055AG2-654 GEN
Solar/Wind Harmer
0.552
957561AF2-050 GEN
Solar/Wind Harmer
14.434
203843AF2-002_GEN
Solar/Wind Harmer
2.795
970631AG2-411 GEN
Solar/Wind Harmer
17.564
20088826HIGHLAND
Solar/Wind Harmer
4.455
971423AH1-203 GEN
Solar/Wind Harmer
17.686
964201AG1-281 GEN
Solar/Wind Harmer
1.503
20089226LOOKOUT
Solar/Wind Harmer
1.785
203987AE2-118 C
Solar/Wind Harmer
4.021
970713AG2-456 GEN
Solar/Wind Harmer
16.005
971705AH1-358 GEN
Solar/Wind Harmer
4.652
971709AH1-360 GEN
Solar/Wind Harmer
4.652
971279AH1-102 GEN
Solar/Wind Harmer
16.075
20094526CT_V3-030
Solar/Wind Harmer
1.376
964391AG1-301 GEN
Solar/Wind Harmer
1.116
20082826HNSMLK 1
Adder
10.051
20083026HNSMLK 3
Adder
10.051
20326126BLOSSBCT
Adder
3.791
20335026MILZ1-092
Adder
3.765
944411AF1-106 GEN
Solar/Wind Harmer
3.468
959471AF2-238 GEN
Solar/Wind Harmer
0.945
970337AG2-221 GEN
Solar/Wind Harmer
3.124
203954AE2-126 C
Solar/Wind Harmer
0.919
970511AG2-327 GEN
Solar/Wind Harmer
1.504
972169AH1-667 GEN
Solar/Wind Harmer
2.64
20091326SHAW-D
Adder
0.964
238183AE2-316 GEN
Solar/Wind Harmer
6.084
20072226SHAWVL 2
Adder
18.929
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.311
971183AH1-050 GEN
Solar/Wind Harmer
5.394
970267AG2-176 GEN
Solar/Wind Harmer
19.756
238206AE2-263_GEN
Solar/Wind Harmer
3.094
961971AG1-040 GEN
Solar/Wind Harmer
0.749
203835AF1-098 GEN
Solar/Wind Harmer
2.998
238215AE2-248 C
Solar/Wind Harmer
1.943
203813AE2-344_GEN
Solar/Wind Harmer
13.78
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.691
24035802GEN-Y1-012
Adder
0.229
971865AH1-452 GEN
Solar/Wind Harmer
0.847
961581Q1080_CY23
External Queue
28.047279357910156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.045
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.14
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.124
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.211
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.273
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.231
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.343
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-003JT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-003JT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1284.02
MW Contribution:18.03
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
8.631
20092526R32
Solar/Wind Harmer
4.886
203844AF2-092 C
Solar/Wind Harmer
3.234
203850AG1-041 C
Solar/Wind Harmer
3.226
20091526CHSTN_FL
Solar/Wind Harmer
2.112
940863AE2-074 GEN
Solar/Wind Harmer
3.438
20090526Q36
Solar/Wind Harmer
3.059
203993AD2-133_GEN1
Solar/Wind Harmer
3.059
941231AE2-117 GEN
Solar/Wind Harmer
1.128
203804AE2-113_GEN
Solar/Wind Harmer
8.698
965121AG1-377 GEN
Solar/Wind Harmer
3.495
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
3.107
203855AF2-088 C
Solar/Wind Harmer
0.292
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.724
971879AH1-460 GEN
Solar/Wind Harmer
18.965
203841AF2-001_GEN
Solar/Wind Harmer
5.747
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
8.313
20089126CSLMN_L13
Solar/Wind Harmer
1.887
20089026BF_G21_K23
Solar/Wind Harmer
1.493
971541AH1-268 GEN
Solar/Wind Harmer
7.352
971703AH1-357 GEN
Solar/Wind Harmer
3.982
971707AH1-359 GEN
Solar/Wind Harmer
3.982
20334926Z1-069 C
Solar/Wind Harmer
4.044
965131AG1-378 GEN
Solar/Wind Harmer
3.495
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
944411AF1-106 GEN
Solar/Wind Harmer
0.371
202652Y1-033 WT C
Solar/Wind Harmer
1.524
970335AG2-220 GEN
Solar/Wind Harmer
4.661
971127AH1-005 GEN
Solar/Wind Harmer
3.007
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.606
960051AF2-296 GEN
Solar/Wind Harmer
2.961
203818AF1-086 GEN
Solar/Wind Harmer
3.783
970899AG2-561 GEN
Solar/Wind Harmer
2.814
945751AF1-240 GEN
Solar/Wind Harmer
2.137
970647AG2-420 GEN
Solar/Wind Harmer
2.685
971185AH1-051 GEN
Solar/Wind Harmer
3.258
971355AH1-158 GEN
Solar/Wind Harmer
3.788
203856AF2-165 C
Solar/Wind Harmer
1.587
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
3.33
971627AH1-313 GEN
Solar/Wind Harmer
13.056
959441AF2-235 GEN
Solar/Wind Harmer
0.389
238219AF1-167 C
Solar/Wind Harmer
1.683
203948AG1-140 C
Solar/Wind Harmer
0.32
957161AF2-010 GEN
Solar/Wind Harmer
9.344
203830AF1-094 GEN
Solar/Wind Harmer
0.733
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
2.371
962511AG1-100 GEN
Solar/Wind Harmer
0.715
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.438
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
3.432
970679AG2-439 GEN
Solar/Wind Harmer
0.777
970643AG2-418 GEN
Solar/Wind Harmer
1.48
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
4.311
970123AG2-090 GEN
Solar/Wind Harmer
4.023
203839AF1-321 GEN
Solar/Wind Harmer
5.747
20084626FORWARD
Solar/Wind Harmer
2.263
20088626ARWF_N39
Solar/Wind Harmer
5.052
20303426NA_O38_P22
Solar/Wind Harmer
4.09
203940AF1-140 C
Solar/Wind Harmer
1.314
20088926STNY CRK
Solar/Wind Harmer
3.202
971427AH1-205 GEN
Solar/Wind Harmer
3.866
971441AH1-212 GEN
Solar/Wind Harmer
5.101
20083426SW_E13_K22
Solar/Wind Harmer
0.759
944781AF1-143 GEN
Solar/Wind Harmer
6.466
972077AH1-588 GEN
Solar/Wind Harmer
47.783
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
15.928
972075AH1-587 GEN
Solar/Wind Harmer
37.389
203952AE2-129 C
Solar/Wind Harmer
1.058
203946AE2-131 C
Solar/Wind Harmer
1.057
962411AG1-090 GEN
Solar/Wind Harmer
16.601
20398826ARMNA MT
Solar/Wind Harmer
3.903
203955AF1-039 C O1
Solar/Wind Harmer
0.742
203859AF2-294 C
Solar/Wind Harmer
2.582
970313AG2-206 GEN
Solar/Wind Harmer
7.181
970305AG2-200 GEN
Solar/Wind Harmer
2.979
203853AF1-134 C O1
Solar/Wind Harmer
0.895
946381AF1-302 GEN
Solar/Wind Harmer
3.047
238217AF1-153 C O1
Solar/Wind Harmer
0.859
203848AF2-166 C
Solar/Wind Harmer
2.641
203980AG1-197 GEN
Solar/Wind Harmer
0.567
216419AE2-001 C
Solar/Wind Harmer
2.458
203963AG1-253 GEN
Solar/Wind Harmer
0.488
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.42
971931AH1-490 GEN
Solar/Wind Harmer
2.364
203947AF1-006 C
Solar/Wind Harmer
0.627
970663AG2-429 GEN
Solar/Wind Harmer
9.25
970663AG2-429 GEN
Solar/Wind Harmer
1.506
203846AF2-130 C
Solar/Wind Harmer
0.755
970677AG2-438 GEN
Solar/Wind Harmer
1.21
966771AG1-548 GEN
Solar/Wind Harmer
17.603
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.556
203843AF2-002_GEN
Solar/Wind Harmer
2.873
970631AG2-411 GEN
Solar/Wind Harmer
18.033
957561AF2-050 GEN
Solar/Wind Harmer
14.249
20088826HIGHLAND
Solar/Wind Harmer
4.56
971423AH1-203 GEN
Solar/Wind Harmer
18.173
964201AG1-281 GEN
Solar/Wind Harmer
1.53
20089226LOOKOUT
Solar/Wind Harmer
1.837
971279AH1-102 GEN
Solar/Wind Harmer
17.275
203987AE2-118 C
Solar/Wind Harmer
4.027
20094526CT_V3-030
Solar/Wind Harmer
1.431
970713AG2-456 GEN
Solar/Wind Harmer
15.928
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
964391AG1-301 GEN
Solar/Wind Harmer
1.117
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.448
959471AF2-238 GEN
Solar/Wind Harmer
0.939
970337AG2-221 GEN
Solar/Wind Harmer
3.107
203954AE2-126 C
Solar/Wind Harmer
0.924
970511AG2-327 GEN
Solar/Wind Harmer
1.496
972169AH1-667 GEN
Solar/Wind Harmer
2.668
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
6.09
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
5.43
970267AG2-176 GEN
Solar/Wind Harmer
19.72
238206AE2-263_GEN
Solar/Wind Harmer
3.103
961971AG1-040 GEN
Solar/Wind Harmer
0.747
203835AF1-098 GEN
Solar/Wind Harmer
2.99
238215AE2-248 C
Solar/Wind Harmer
1.946
203813AE2-344_GEN
Solar/Wind Harmer
13.75
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.857
961581Q1080_CY23
External Queue
27.7316951751709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:131.02 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1284.02
MW Contribution:18.03
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.873
970631AG2-411 GEN
Solar/Wind Harmer
18.033
957561AF2-050 GEN
Solar/Wind Harmer
14.249
20088826HIGHLAND
Solar/Wind Harmer
4.56
971423AH1-203 GEN
Solar/Wind Harmer
18.173
964201AG1-281 GEN
Solar/Wind Harmer
1.53
20089226LOOKOUT
Solar/Wind Harmer
1.837
971279AH1-102 GEN
Solar/Wind Harmer
17.275
203987AE2-118 C
Solar/Wind Harmer
4.027
20094526CT_V3-030
Solar/Wind Harmer
1.431
970713AG2-456 GEN
Solar/Wind Harmer
15.928
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
964391AG1-301 GEN
Solar/Wind Harmer
1.117
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.448
959471AF2-238 GEN
Solar/Wind Harmer
0.939
970337AG2-221 GEN
Solar/Wind Harmer
3.107
203954AE2-126 C
Solar/Wind Harmer
0.924
970511AG2-327 GEN
Solar/Wind Harmer
1.496
972169AH1-667 GEN
Solar/Wind Harmer
2.668
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
6.09
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.416
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
5.43
970267AG2-176 GEN
Solar/Wind Harmer
19.72
238206AE2-263_GEN
Solar/Wind Harmer
3.103
961971AG1-040 GEN
Solar/Wind Harmer
0.747
203835AF1-098 GEN
Solar/Wind Harmer
2.99
238215AE2-248 C
Solar/Wind Harmer
1.946
203813AE2-344_GEN
Solar/Wind Harmer
13.75
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.857
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
8.631
20092526R32
Solar/Wind Harmer
4.886
203844AF2-092 C
Solar/Wind Harmer
3.234
203850AG1-041 C
Solar/Wind Harmer
3.226
20091526CHSTN_FL
Solar/Wind Harmer
2.112
940863AE2-074 GEN
Solar/Wind Harmer
3.438
20090526Q36
Solar/Wind Harmer
3.059
203993AD2-133_GEN1
Solar/Wind Harmer
3.059
941231AE2-117 GEN
Solar/Wind Harmer
1.128
203804AE2-113_GEN
Solar/Wind Harmer
8.698
965121AG1-377 GEN
Solar/Wind Harmer
3.495
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
3.107
203855AF2-088 C
Solar/Wind Harmer
0.292
970663AG2-429 GEN
Solar/Wind Harmer
9.25
970663AG2-429 GEN
Solar/Wind Harmer
1.506
203846AF2-130 C
Solar/Wind Harmer
0.755
970677AG2-438 GEN
Solar/Wind Harmer
1.21
966771AG1-548 GEN
Solar/Wind Harmer
17.603
966771AG1-548 GEN
Solar/Wind Harmer
3.411
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.556
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.724
971879AH1-460 GEN
Solar/Wind Harmer
18.965
203841AF2-001_GEN
Solar/Wind Harmer
5.747
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
8.313
20089126CSLMN_L13
Solar/Wind Harmer
1.887
20089026BF_G21_K23
Solar/Wind Harmer
1.493
971541AH1-268 GEN
Solar/Wind Harmer
7.352
971703AH1-357 GEN
Solar/Wind Harmer
3.982
971707AH1-359 GEN
Solar/Wind Harmer
3.982
20334926Z1-069 C
Solar/Wind Harmer
4.044
965131AG1-378 GEN
Solar/Wind Harmer
3.495
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
944411AF1-106 GEN
Solar/Wind Harmer
0.371
202652Y1-033 WT C
Solar/Wind Harmer
1.524
970335AG2-220 GEN
Solar/Wind Harmer
4.661
971127AH1-005 GEN
Solar/Wind Harmer
3.007
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.606
960051AF2-296 GEN
Solar/Wind Harmer
2.961
203818AF1-086 GEN
Solar/Wind Harmer
3.783
970899AG2-561 GEN
Solar/Wind Harmer
2.814
945751AF1-240 GEN
Solar/Wind Harmer
2.137
970647AG2-420 GEN
Solar/Wind Harmer
2.685
971185AH1-051 GEN
Solar/Wind Harmer
3.258
971355AH1-158 GEN
Solar/Wind Harmer
3.788
203856AF2-165 C
Solar/Wind Harmer
1.587
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
3.33
971627AH1-313 GEN
Solar/Wind Harmer
13.056
959441AF2-235 GEN
Solar/Wind Harmer
0.389
238219AF1-167 C
Solar/Wind Harmer
1.683
203948AG1-140 C
Solar/Wind Harmer
0.32
957161AF2-010 GEN
Solar/Wind Harmer
9.344
203830AF1-094 GEN
Solar/Wind Harmer
0.733
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
2.371
962511AG1-100 GEN
Solar/Wind Harmer
0.715
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
3.438
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
3.432
970679AG2-439 GEN
Solar/Wind Harmer
0.777
970643AG2-418 GEN
Solar/Wind Harmer
1.48
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
4.311
970123AG2-090 GEN
Solar/Wind Harmer
4.023
203839AF1-321 GEN
Solar/Wind Harmer
5.747
20084626FORWARD
Solar/Wind Harmer
2.263
20088626ARWF_N39
Solar/Wind Harmer
5.052
20303426NA_O38_P22
Solar/Wind Harmer
4.09
203940AF1-140 C
Solar/Wind Harmer
1.314
20088926STNY CRK
Solar/Wind Harmer
3.202
971427AH1-205 GEN
Solar/Wind Harmer
3.866
971441AH1-212 GEN
Solar/Wind Harmer
5.101
20083426SW_E13_K22
Solar/Wind Harmer
0.759
944781AF1-143 GEN
Solar/Wind Harmer
6.466
972077AH1-588 GEN
Solar/Wind Harmer
47.783
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
15.928
972075AH1-587 GEN
Solar/Wind Harmer
37.389
203952AE2-129 C
Solar/Wind Harmer
1.058
203946AE2-131 C
Solar/Wind Harmer
1.057
962411AG1-090 GEN
Solar/Wind Harmer
16.601
20398826ARMNA MT
Solar/Wind Harmer
3.903
203955AF1-039 C O1
Solar/Wind Harmer
0.742
203859AF2-294 C
Solar/Wind Harmer
2.582
970313AG2-206 GEN
Solar/Wind Harmer
7.181
970305AG2-200 GEN
Solar/Wind Harmer
2.979
203853AF1-134 C O1
Solar/Wind Harmer
0.895
946381AF1-302 GEN
Solar/Wind Harmer
3.047
238217AF1-153 C O1
Solar/Wind Harmer
0.859
203848AF2-166 C
Solar/Wind Harmer
2.641
203980AG1-197 GEN
Solar/Wind Harmer
0.567
216419AE2-001 C
Solar/Wind Harmer
2.458
203963AG1-253 GEN
Solar/Wind Harmer
0.488
203979AG1-198 GEN
Solar/Wind Harmer
0.44
971933AH1-491 GEN
Solar/Wind Harmer
2.42
971931AH1-490 GEN
Solar/Wind Harmer
2.364
203947AF1-006 C
Solar/Wind Harmer
0.627
961581Q1080_CY23
External Queue
27.7316951751709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1283.85
MW Contribution:16.66
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
8.898
20079426CONEMAGH
50/50
2.901
203841AF2-001_GEN
Solar/Wind Harmer
5.307
971879AH1-460 GEN
Solar/Wind Harmer
17.329
970125AG2-091 GEN
Solar/Wind Harmer
1.563
971419AH1-201 GEN
Solar/Wind Harmer
7.603
971703AH1-357 GEN
Solar/Wind Harmer
4.058
971707AH1-359 GEN
Solar/Wind Harmer
4.058
20334926Z1-069 C
Solar/Wind Harmer
4.13
20089126CSLMN_L13
Solar/Wind Harmer
1.734
20089026BF_G21_K23
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
6.238
20082926HNSMLK 2
Adder
10.267
20083126HNSMLK 4
Adder
10.267
944411AF1-106 GEN
Solar/Wind Harmer
0.379
965131AG1-378 GEN
Solar/Wind Harmer
3.229
970335AG2-220 GEN
Solar/Wind Harmer
4.75
971127AH1-005 GEN
Solar/Wind Harmer
3.064
20120126WRREN CT
Adder
9.509
202652Y1-033 WT C
Solar/Wind Harmer
1.4
203854AF2-039 C
Solar/Wind Harmer
0.573
960051AF2-296 GEN
Solar/Wind Harmer
2.698
970647AG2-420 GEN
Solar/Wind Harmer
2.687
971185AH1-051 GEN
Solar/Wind Harmer
3.25
971355AH1-158 GEN
Solar/Wind Harmer
3.779
20335126GROZ1-110
Adder
3.135
20335226CANZ2-011
Adder
3.047
203856AF2-165 C
Solar/Wind Harmer
1.584
203818AF1-086 GEN
Solar/Wind Harmer
3.348
203932AE1-123
Adder
2.548
959441AF2-235 GEN
Solar/Wind Harmer
0.389
945751AF1-240 GEN
Solar/Wind Harmer
1.977
238202AE2-262_GEN
Solar/Wind Harmer
3.19
971627AH1-313 GEN
Solar/Wind Harmer
12.507
238219AF1-167 C
Solar/Wind Harmer
1.682
203948AG1-140 C
Solar/Wind Harmer
0.326
957161AF2-010 GEN
Solar/Wind Harmer
9.444
203830AF1-094 GEN
Solar/Wind Harmer
0.741
20328326MANOR_T86
Adder
0.174
970899AG2-561 GEN
Solar/Wind Harmer
2.417
203962AF1-287 GEN
Solar/Wind Harmer
2.414
962511AG1-100 GEN
Solar/Wind Harmer
0.728
20084926LAKVU GN
Adder
0.206
941421AE2-139 GEN
Solar/Wind Harmer
3.462
972271AH1-720 GEN
Adder
7.407
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970679AG2-439 GEN
Solar/Wind Harmer
0.787
970643AG2-418 GEN
Solar/Wind Harmer
1.345
20080926SITHE
50/50
0.948
203839AF1-321 GEN
Solar/Wind Harmer
5.307
20084626FORWARD
Solar/Wind Harmer
2.09
203857AF2-221 C
Solar/Wind Harmer
3.907
970123AG2-090 GEN
Solar/Wind Harmer
3.647
20088926STNY CRK
Solar/Wind Harmer
2.928
971427AH1-205 GEN
Solar/Wind Harmer
3.536
20088626ARWF_N39
Solar/Wind Harmer
4.477
20303426NA_O38_P22
Solar/Wind Harmer
3.625
203940AF1-140 C
Solar/Wind Harmer
1.175
20083426SW_E13_K22
Solar/Wind Harmer
0.698
971441AH1-212 GEN
Solar/Wind Harmer
4.486
972077AH1-588 GEN
Solar/Wind Harmer
48.69
972079AH1-589 GEN
Solar/Wind Harmer
40.103
970715AG2-457 GEN
Solar/Wind Harmer
16.23
944781AF1-143 GEN
Solar/Wind Harmer
5.944
972075AH1-587 GEN
Solar/Wind Harmer
37.76
20398826ARMNA MT
Solar/Wind Harmer
3.987
203952AE2-129 C
Solar/Wind Harmer
0.978
203946AE2-131 C
Solar/Wind Harmer
0.976
962411AG1-090 GEN
Solar/Wind Harmer
15.339
203859AF2-294 C
Solar/Wind Harmer
2.639
970313AG2-206 GEN
Solar/Wind Harmer
7.317
970305AG2-200 GEN
Solar/Wind Harmer
3.008
203955AF1-039 C O1
Solar/Wind Harmer
0.681
946381AF1-302 GEN
Solar/Wind Harmer
3.033
238217AF1-153 C O1
Solar/Wind Harmer
0.842
203853AF1-134 C O1
Solar/Wind Harmer
0.816
203848AF2-166 C
Solar/Wind Harmer
2.611
203980AG1-197 GEN
Solar/Wind Harmer
0.577
203963AG1-253 GEN
Solar/Wind Harmer
0.498
203979AG1-198 GEN
Solar/Wind Harmer
0.445
971933AH1-491 GEN
Solar/Wind Harmer
2.447
971931AH1-490 GEN
Solar/Wind Harmer
2.408
216419AE2-001 C
Solar/Wind Harmer
2.331
203947AF1-006 C
Solar/Wind Harmer
0.639
20083726HOMER C1
50/50
294.677
20083926HOMER C3
50/50
239.758
20083826HOMER C2
50/50
226.48
20050326C.SLOPE
50/50
0.759
203961AE2-224 GEN
Solar/Wind Harmer
7.642
20092526R32
Solar/Wind Harmer
4.361
203844AF2-092 C
Solar/Wind Harmer
2.929
203850AG1-041 C
Solar/Wind Harmer
2.914
20091526CHSTN_FL
Solar/Wind Harmer
1.885
940863AE2-074 GEN
Solar/Wind Harmer
3.506
203804AE2-113_GEN
Solar/Wind Harmer
8.75
20090526Q36
Solar/Wind Harmer
2.784
203993AD2-133_GEN1
Solar/Wind Harmer
2.784
20083226HNSMLK 5
Adder
10.267
941231AE2-117 GEN
Solar/Wind Harmer
1.012
965121AG1-377 GEN
Solar/Wind Harmer
3.229
970555AG2-356 GEN
Solar/Wind Harmer
3.165
203855AF2-088 C
Solar/Wind Harmer
0.276
970663AG2-429 GEN
Solar/Wind Harmer
9.296
970663AG2-429 GEN
Solar/Wind Harmer
1.513
203846AF2-130 C
Solar/Wind Harmer
0.746
970677AG2-438 GEN
Solar/Wind Harmer
1.223
966771AG1-548 GEN
Solar/Wind Harmer
17.81
966771AG1-548 GEN
Solar/Wind Harmer
3.452
20084926LAKVU GN
Adder
0.232
203926AA2-133 GEN
Adder
2.594
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.883
971055AG2-654 GEN
Solar/Wind Harmer
0.566
203843AF2-002_GEN
Solar/Wind Harmer
2.653
970631AG2-411 GEN
Solar/Wind Harmer
16.66
957561AF2-050 GEN
Solar/Wind Harmer
12.617
20088826HIGHLAND
Solar/Wind Harmer
4.07
971423AH1-203 GEN
Solar/Wind Harmer
16.651
964201AG1-281 GEN
Solar/Wind Harmer
1.366
970713AG2-456 GEN
Solar/Wind Harmer
16.23
971705AH1-358 GEN
Solar/Wind Harmer
4.718
971709AH1-360 GEN
Solar/Wind Harmer
4.718
20089226LOOKOUT
Solar/Wind Harmer
1.689
203987AE2-118 C
Solar/Wind Harmer
3.598
971279AH1-102 GEN
Solar/Wind Harmer
14.659
20094526CT_V3-030
Solar/Wind Harmer
1.254
20082826HNSMLK 1
Adder
10.267
20083026HNSMLK 3
Adder
10.267
20335026MILZ1-092
Adder
3.824
944411AF1-106 GEN
Solar/Wind Harmer
3.523
20326126BLOSSBCT
Adder
3.84
964391AG1-301 GEN
Solar/Wind Harmer
1
959471AF2-238 GEN
Solar/Wind Harmer
0.957
970337AG2-221 GEN
Solar/Wind Harmer
3.165
970511AG2-327 GEN
Solar/Wind Harmer
1.524
203954AE2-126 C
Solar/Wind Harmer
0.895
238183AE2-316 GEN
Solar/Wind Harmer
6.061
972169AH1-667 GEN
Solar/Wind Harmer
2.525
20091326SHAW-D
Adder
0.922
203860AG1-193 C
Solar/Wind Harmer
0.421
970647AG2-420 GEN
Solar/Wind Harmer
0.312
970267AG2-176 GEN
Solar/Wind Harmer
20.083
971183AH1-050 GEN
Solar/Wind Harmer
5.417
20072226SHAWVL 2
Adder
18.247
961971AG1-040 GEN
Solar/Wind Harmer
0.761
203835AF1-098 GEN
Solar/Wind Harmer
3.037
238206AE2-263_GEN
Solar/Wind Harmer
2.973
203813AE2-344_GEN
Solar/Wind Harmer
14.003
20084926LAKVU GN
Adder
0.206
238215AE2-248 C
Solar/Wind Harmer
1.842
970643AG2-418 GEN
Solar/Wind Harmer
0.625
24035802GEN-Y1-012
Adder
0.234
971865AH1-452 GEN
Solar/Wind Harmer
0.861
961581Q1080_CY23
External Queue
29.164003372192383
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.011
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.036
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.084
MECLTFEXP_MEC->PJM
CLTF
0.022
WECLTFEXP_WEC->PJM
CLTF
0.019
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.208
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.884
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.6 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1191.64
MW Contribution:13.97
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
245.208
20083926HOMER C3
50/50
208.368
20083826HOMER C2
50/50
196.828
20050326C.SLOPE
50/50
0.643
203961AE2-224 GEN
Solar/Wind Harmer
6.518
20092526R32
Solar/Wind Harmer
3.68
203844AF2-092 C
Solar/Wind Harmer
2.47
203850AG1-041 C
Solar/Wind Harmer
2.46
940863AE2-074 GEN
Solar/Wind Harmer
3.358
20083226HNSMLK 5
Adder
11.27
20091526CHSTN_FL
Solar/Wind Harmer
1.624
203804AE2-113_GEN
Solar/Wind Harmer
8.535
20084926LAKVU GN
Adder
0.338
966771AG1-548 GEN
Solar/Wind Harmer
24.17
966771AG1-548 GEN
Solar/Wind Harmer
4.684
970677AG2-438 GEN
Solar/Wind Harmer
1.647
20090526Q36
Solar/Wind Harmer
2.487
203993AD2-133_GEN1
Solar/Wind Harmer
2.487
970555AG2-356 GEN
Solar/Wind Harmer
3.016
20083326SEWRDB34
50/50
7.576
203841AF2-001_GEN
Solar/Wind Harmer
4.446
971879AH1-460 GEN
Solar/Wind Harmer
14.541
970125AG2-091 GEN
Solar/Wind Harmer
1.313
971419AH1-201 GEN
Solar/Wind Harmer
6.387
971703AH1-357 GEN
Solar/Wind Harmer
3.963
971707AH1-359 GEN
Solar/Wind Harmer
3.963
20082926HNSMLK 2
Adder
11.27
20083126HNSMLK 4
Adder
11.27
20079426CONEMAGH
Adder
2.291
20334926Z1-069 C
Solar/Wind Harmer
3.928
20120126WRREN CT
Adder
10.942
203948AG1-140 C
Solar/Wind Harmer
0.453
962511AG1-100 GEN
Solar/Wind Harmer
1.037
203962AF1-287 GEN
Solar/Wind Harmer
3.429
20084926LAKVU GN
Adder
0.3
203830AF1-094 GEN
Solar/Wind Harmer
0.998
20089126CSLMN_L13
Solar/Wind Harmer
1.452
20089026BF_G21_K23
Solar/Wind Harmer
1.149
957161AF2-010 GEN
Solar/Wind Harmer
12.647
944411AF1-106 GEN
Solar/Wind Harmer
0.362
959441AF2-235 GEN
Solar/Wind Harmer
0.467
970647AG2-420 GEN
Solar/Wind Harmer
3.073
203856AF2-165 C
Solar/Wind Harmer
1.799
971185AH1-051 GEN
Solar/Wind Harmer
3.645
971355AH1-158 GEN
Solar/Wind Harmer
4.238
971541AH1-268 GEN
Solar/Wind Harmer
5.179
965131AG1-378 GEN
Solar/Wind Harmer
2.959
970335AG2-220 GEN
Solar/Wind Harmer
4.539
971127AH1-005 GEN
Solar/Wind Harmer
2.929
203854AF2-039 C
Solar/Wind Harmer
0.546
203932AE1-123
Adder
2.576
20335126GROZ1-110
Adder
3.04
20335226CANZ2-011
Adder
2.955
202652Y1-033 WT C
Solar/Wind Harmer
1.169
238202AE2-262_GEN
Solar/Wind Harmer
3.116
971627AH1-313 GEN
Solar/Wind Harmer
12.219
238219AF1-167 C
Solar/Wind Harmer
1.639
960051AF2-296 GEN
Solar/Wind Harmer
2.425
20328326MANOR_T86
Adder
0.17
945751AF1-240 GEN
Solar/Wind Harmer
1.833
941421AE2-139 GEN
Solar/Wind Harmer
3.413
203818AF1-086 GEN
Solar/Wind Harmer
2.867
972271AH1-720 GEN
Adder
7.308
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970899AG2-561 GEN
Solar/Wind Harmer
1.962
970679AG2-439 GEN
Solar/Wind Harmer
0.808
970643AG2-418 GEN
Solar/Wind Harmer
1.327
941231AE2-117 GEN
Solar/Wind Harmer
0.896
965121AG1-377 GEN
Solar/Wind Harmer
2.959
203846AF2-130 C
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.263
970663AG2-429 GEN
Solar/Wind Harmer
8.994
970663AG2-429 GEN
Solar/Wind Harmer
1.464
203926AA2-133 GEN
Adder
2.564
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.933
203843AF2-002_GEN
Solar/Wind Harmer
2.223
970631AG2-411 GEN
Solar/Wind Harmer
13.968
957561AF2-050 GEN
Solar/Wind Harmer
10.76
20088826HIGHLAND
Solar/Wind Harmer
3.434
971423AH1-203 GEN
Solar/Wind Harmer
13.977
970713AG2-456 GEN
Solar/Wind Harmer
15.852
971705AH1-358 GEN
Solar/Wind Harmer
4.608
971709AH1-360 GEN
Solar/Wind Harmer
4.608
964201AG1-281 GEN
Solar/Wind Harmer
1.164
20082826HNSMLK 1
Adder
11.27
20083026HNSMLK 3
Adder
11.27
970267AG2-176 GEN
Solar/Wind Harmer
26.044
961971AG1-040 GEN
Solar/Wind Harmer
1.042
203813AE2-344_GEN
Solar/Wind Harmer
19.972
203835AF1-098 GEN
Solar/Wind Harmer
4.153
20084926LAKVU GN
Adder
0.3
203860AG1-193 C
Solar/Wind Harmer
0.501
20089226LOOKOUT
Solar/Wind Harmer
1.413
20335026MILZ1-092
Adder
3.655
944411AF1-106 GEN
Solar/Wind Harmer
3.367
20326126BLOSSBCT
Adder
3.647
203987AE2-118 C
Solar/Wind Harmer
3.155
970647AG2-420 GEN
Solar/Wind Harmer
0.357
959471AF2-238 GEN
Solar/Wind Harmer
0.912
970337AG2-221 GEN
Solar/Wind Harmer
3.016
971183AH1-050 GEN
Solar/Wind Harmer
6.075
971279AH1-102 GEN
Solar/Wind Harmer
12.169
20094526CT_V3-030
Solar/Wind Harmer
1.057
964391AG1-301 GEN
Solar/Wind Harmer
0.886
970511AG2-327 GEN
Solar/Wind Harmer
1.458
203954AE2-126 C
Solar/Wind Harmer
0.872
238183AE2-316 GEN
Solar/Wind Harmer
5.9
972169AH1-667 GEN
Solar/Wind Harmer
2.403
20091326SHAW-D
Adder
0.878
20072226SHAWVL 2
Adder
17.744
238206AE2-263_GEN
Solar/Wind Harmer
2.904
238215AE2-248 C
Solar/Wind Harmer
1.792
970643AG2-418 GEN
Solar/Wind Harmer
0.617
971865AH1-452 GEN
Solar/Wind Harmer
0.778
20080926SITHE
50/50
0.789
203839AF1-321 GEN
Solar/Wind Harmer
4.446
20084626FORWARD
Solar/Wind Harmer
1.753
203857AF2-221 C
Solar/Wind Harmer
3.282
970123AG2-090 GEN
Solar/Wind Harmer
3.064
20088626ARWF_N39
Solar/Wind Harmer
3.833
20303426NA_O38_P22
Solar/Wind Harmer
3.103
203940AF1-140 C
Solar/Wind Harmer
0.995
20088926STNY CRK
Solar/Wind Harmer
2.46
971427AH1-205 GEN
Solar/Wind Harmer
2.971
972077AH1-588 GEN
Solar/Wind Harmer
47.555
972079AH1-589 GEN
Solar/Wind Harmer
39.169
970715AG2-457 GEN
Solar/Wind Harmer
15.852
20083426SW_E13_K22
Solar/Wind Harmer
0.585
971441AH1-212 GEN
Solar/Wind Harmer
3.806
972075AH1-587 GEN
Solar/Wind Harmer
36.7
970305AG2-200 GEN
Solar/Wind Harmer
3.461
203963AG1-253 GEN
Solar/Wind Harmer
0.692
203980AG1-197 GEN
Solar/Wind Harmer
0.784
971931AH1-490 GEN
Solar/Wind Harmer
3.431
203947AF1-006 C
Solar/Wind Harmer
0.954
203979AG1-198 GEN
Solar/Wind Harmer
0.599
971933AH1-491 GEN
Solar/Wind Harmer
3.295
944781AF1-143 GEN
Solar/Wind Harmer
4.975
20398826ARMNA MT
Solar/Wind Harmer
3.774
203859AF2-294 C
Solar/Wind Harmer
2.539
203952AE2-129 C
Solar/Wind Harmer
0.896
203946AE2-131 C
Solar/Wind Harmer
0.894
962411AG1-090 GEN
Solar/Wind Harmer
14.053
970313AG2-206 GEN
Solar/Wind Harmer
6.997
946381AF1-302 GEN
Solar/Wind Harmer
2.952
203848AF2-166 C
Solar/Wind Harmer
2.794
238217AF1-153 C O1
Solar/Wind Harmer
0.834
203955AF1-039 C O1
Solar/Wind Harmer
0.569
203853AF1-134 C O1
Solar/Wind Harmer
0.733
216419AE2-001 C
Solar/Wind Harmer
2.269
961581Q1080_CY23
External Queue
20.78413963317871
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.432
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.342
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.9
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.232
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.958
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.367
G-007ALTFEXP_G-007A->PJM
CMTX
2.027
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.542
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.6 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1191.64
MW Contribution:13.97
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.576
203841AF2-001_GEN
Solar/Wind Harmer
4.446
971879AH1-460 GEN
Solar/Wind Harmer
14.541
20083726HOMER C1
50/50
245.208
20083926HOMER C3
50/50
208.368
20083826HOMER C2
50/50
196.828
20050326C.SLOPE
50/50
0.643
203961AE2-224 GEN
Solar/Wind Harmer
6.518
20092526R32
Solar/Wind Harmer
3.68
203844AF2-092 C
Solar/Wind Harmer
2.47
203850AG1-041 C
Solar/Wind Harmer
2.46
940863AE2-074 GEN
Solar/Wind Harmer
3.358
20083226HNSMLK 5
Adder
11.27
20091526CHSTN_FL
Solar/Wind Harmer
1.624
203804AE2-113_GEN
Solar/Wind Harmer
8.535
20084926LAKVU GN
Adder
0.338
966771AG1-548 GEN
Solar/Wind Harmer
24.17
966771AG1-548 GEN
Solar/Wind Harmer
4.684
970677AG2-438 GEN
Solar/Wind Harmer
1.647
20090526Q36
Solar/Wind Harmer
2.487
203993AD2-133_GEN1
Solar/Wind Harmer
2.487
970555AG2-356 GEN
Solar/Wind Harmer
3.016
941231AE2-117 GEN
Solar/Wind Harmer
0.896
965121AG1-377 GEN
Solar/Wind Harmer
2.959
203846AF2-130 C
Solar/Wind Harmer
0.798
203855AF2-088 C
Solar/Wind Harmer
0.263
970663AG2-429 GEN
Solar/Wind Harmer
8.994
970663AG2-429 GEN
Solar/Wind Harmer
1.464
203926AA2-133 GEN
Adder
2.564
20334726NME_Y1-047
Adder
2.337
20390726Y2-042
Adder
1.933
970125AG2-091 GEN
Solar/Wind Harmer
1.313
971419AH1-201 GEN
Solar/Wind Harmer
6.387
971703AH1-357 GEN
Solar/Wind Harmer
3.963
971707AH1-359 GEN
Solar/Wind Harmer
3.963
20082926HNSMLK 2
Adder
11.27
20083126HNSMLK 4
Adder
11.27
20079426CONEMAGH
Adder
2.291
20334926Z1-069 C
Solar/Wind Harmer
3.928
20120126WRREN CT
Adder
10.942
203948AG1-140 C
Solar/Wind Harmer
0.453
962511AG1-100 GEN
Solar/Wind Harmer
1.037
203962AF1-287 GEN
Solar/Wind Harmer
3.429
20084926LAKVU GN
Adder
0.3
203830AF1-094 GEN
Solar/Wind Harmer
0.998
20089126CSLMN_L13
Solar/Wind Harmer
1.452
20089026BF_G21_K23
Solar/Wind Harmer
1.149
957161AF2-010 GEN
Solar/Wind Harmer
12.647
944411AF1-106 GEN
Solar/Wind Harmer
0.362
959441AF2-235 GEN
Solar/Wind Harmer
0.467
970647AG2-420 GEN
Solar/Wind Harmer
3.073
203856AF2-165 C
Solar/Wind Harmer
1.799
971185AH1-051 GEN
Solar/Wind Harmer
3.645
971355AH1-158 GEN
Solar/Wind Harmer
4.238
971541AH1-268 GEN
Solar/Wind Harmer
5.179
965131AG1-378 GEN
Solar/Wind Harmer
2.959
970335AG2-220 GEN
Solar/Wind Harmer
4.539
971127AH1-005 GEN
Solar/Wind Harmer
2.929
203854AF2-039 C
Solar/Wind Harmer
0.546
203932AE1-123
Adder
2.576
20335126GROZ1-110
Adder
3.04
20335226CANZ2-011
Adder
2.955
202652Y1-033 WT C
Solar/Wind Harmer
1.169
238202AE2-262_GEN
Solar/Wind Harmer
3.116
971627AH1-313 GEN
Solar/Wind Harmer
12.219
238219AF1-167 C
Solar/Wind Harmer
1.639
960051AF2-296 GEN
Solar/Wind Harmer
2.425
20328326MANOR_T86
Adder
0.17
945751AF1-240 GEN
Solar/Wind Harmer
1.833
941421AE2-139 GEN
Solar/Wind Harmer
3.413
203818AF1-086 GEN
Solar/Wind Harmer
2.867
972271AH1-720 GEN
Adder
7.308
200917MEHOOPANY_G
Solar/Wind Harmer
3.478
970899AG2-561 GEN
Solar/Wind Harmer
1.962
970679AG2-439 GEN
Solar/Wind Harmer
0.808
970643AG2-418 GEN
Solar/Wind Harmer
1.327
20080926SITHE
50/50
0.789
203839AF1-321 GEN
Solar/Wind Harmer
4.446
20084626FORWARD
Solar/Wind Harmer
1.753
203857AF2-221 C
Solar/Wind Harmer
3.282
970123AG2-090 GEN
Solar/Wind Harmer
3.064
20088626ARWF_N39
Solar/Wind Harmer
3.833
20303426NA_O38_P22
Solar/Wind Harmer
3.103
203940AF1-140 C
Solar/Wind Harmer
0.995
20088926STNY CRK
Solar/Wind Harmer
2.46
971427AH1-205 GEN
Solar/Wind Harmer
2.971
972077AH1-588 GEN
Solar/Wind Harmer
47.555
972079AH1-589 GEN
Solar/Wind Harmer
39.169
970715AG2-457 GEN
Solar/Wind Harmer
15.852
20083426SW_E13_K22
Solar/Wind Harmer
0.585
971441AH1-212 GEN
Solar/Wind Harmer
3.806
972075AH1-587 GEN
Solar/Wind Harmer
36.7
970305AG2-200 GEN
Solar/Wind Harmer
3.461
203963AG1-253 GEN
Solar/Wind Harmer
0.692
203980AG1-197 GEN
Solar/Wind Harmer
0.784
971931AH1-490 GEN
Solar/Wind Harmer
3.431
203947AF1-006 C
Solar/Wind Harmer
0.954
203979AG1-198 GEN
Solar/Wind Harmer
0.599
971933AH1-491 GEN
Solar/Wind Harmer
3.295
944781AF1-143 GEN
Solar/Wind Harmer
4.975
20398826ARMNA MT
Solar/Wind Harmer
3.774
203859AF2-294 C
Solar/Wind Harmer
2.539
203952AE2-129 C
Solar/Wind Harmer
0.896
203946AE2-131 C
Solar/Wind Harmer
0.894
962411AG1-090 GEN
Solar/Wind Harmer
14.053
970313AG2-206 GEN
Solar/Wind Harmer
6.997
946381AF1-302 GEN
Solar/Wind Harmer
2.952
203848AF2-166 C
Solar/Wind Harmer
2.794
238217AF1-153 C O1
Solar/Wind Harmer
0.834
203843AF2-002_GEN
Solar/Wind Harmer
2.223
970631AG2-411 GEN
Solar/Wind Harmer
13.968
957561AF2-050 GEN
Solar/Wind Harmer
10.76
20088826HIGHLAND
Solar/Wind Harmer
3.434
971423AH1-203 GEN
Solar/Wind Harmer
13.977
970713AG2-456 GEN
Solar/Wind Harmer
15.852
971705AH1-358 GEN
Solar/Wind Harmer
4.608
971709AH1-360 GEN
Solar/Wind Harmer
4.608
964201AG1-281 GEN
Solar/Wind Harmer
1.164
20082826HNSMLK 1
Adder
11.27
20083026HNSMLK 3
Adder
11.27
970267AG2-176 GEN
Solar/Wind Harmer
26.044
961971AG1-040 GEN
Solar/Wind Harmer
1.042
203813AE2-344_GEN
Solar/Wind Harmer
19.972
203835AF1-098 GEN
Solar/Wind Harmer
4.153
20084926LAKVU GN
Adder
0.3
203860AG1-193 C
Solar/Wind Harmer
0.501
20089226LOOKOUT
Solar/Wind Harmer
1.413
20335026MILZ1-092
Adder
3.655
944411AF1-106 GEN
Solar/Wind Harmer
3.367
20326126BLOSSBCT
Adder
3.647
203987AE2-118 C
Solar/Wind Harmer
3.155
970647AG2-420 GEN
Solar/Wind Harmer
0.357
959471AF2-238 GEN
Solar/Wind Harmer
0.912
970337AG2-221 GEN
Solar/Wind Harmer
3.016
971183AH1-050 GEN
Solar/Wind Harmer
6.075
971279AH1-102 GEN
Solar/Wind Harmer
12.169
20094526CT_V3-030
Solar/Wind Harmer
1.057
964391AG1-301 GEN
Solar/Wind Harmer
0.886
970511AG2-327 GEN
Solar/Wind Harmer
1.458
203954AE2-126 C
Solar/Wind Harmer
0.872
238183AE2-316 GEN
Solar/Wind Harmer
5.9
972169AH1-667 GEN
Solar/Wind Harmer
2.403
20091326SHAW-D
Adder
0.878
20072226SHAWVL 2
Adder
17.744
238206AE2-263_GEN
Solar/Wind Harmer
2.904
238215AE2-248 C
Solar/Wind Harmer
1.792
970643AG2-418 GEN
Solar/Wind Harmer
0.617
971865AH1-452 GEN
Solar/Wind Harmer
0.778
203955AF1-039 C O1
Solar/Wind Harmer
0.569
203853AF1-134 C O1
Solar/Wind Harmer
0.733
216419AE2-001 C
Solar/Wind Harmer
2.269
961581Q1080_CY23
External Queue
20.78413963317871
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.432
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.342
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
5.9
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.232
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.958
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.367
G-007ALTFEXP_G-007A->PJM
CMTX
2.027
CBM NorthLTFEXP_CBM-N->PJM
CBM
37.542
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-059_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-059_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.4 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1101.51
MW Contribution:13.56
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.16
970631AG2-411 GEN
Solar/Wind Harmer
13.565
957561AF2-050 GEN
Solar/Wind Harmer
10.435
20088826HIGHLAND
Solar/Wind Harmer
3.312
971423AH1-203 GEN
Solar/Wind Harmer
13.529
964201AG1-281 GEN
Solar/Wind Harmer
1.112
20083726HOMER C1
50/50
243.439
20083926HOMER C3
50/50
210.642
20083826HOMER C2
50/50
198.976
20050326C.SLOPE
50/50
0.616
203961AE2-224 GEN
Solar/Wind Harmer
6.321
20092526R32
Solar/Wind Harmer
3.549
203844AF2-092 C
Solar/Wind Harmer
2.38
203850AG1-041 C
Solar/Wind Harmer
2.367
940863AE2-074 GEN
Solar/Wind Harmer
3.015
20091526CHSTN_FL
Solar/Wind Harmer
1.526
20083226HNSMLK 5
Adder
10.092
203804AE2-113_GEN
Solar/Wind Harmer
7.305
20090526Q36
Solar/Wind Harmer
2.226
203993AD2-133_GEN1
Solar/Wind Harmer
2.226
970555AG2-356 GEN
Solar/Wind Harmer
2.752
941231AE2-117 GEN
Solar/Wind Harmer
0.83
965121AG1-377 GEN
Solar/Wind Harmer
2.555
203855AF2-088 C
Solar/Wind Harmer
0.215
20084926LAKVU GN
Adder
0.202
966771AG1-548 GEN
Solar/Wind Harmer
14.481
966771AG1-548 GEN
Solar/Wind Harmer
2.806
970677AG2-438 GEN
Solar/Wind Harmer
0.986
203926AA2-133 GEN
Adder
2.278
20334726NME_Y1-047
Adder
2.067
203846AF2-130 C
Solar/Wind Harmer
0.43
20390726Y2-042
Adder
1.69
20083326SEWRDB34
50/50
7.4
20079426CONEMAGH
50/50
2.323
203841AF2-001_GEN
Solar/Wind Harmer
4.32
971879AH1-460 GEN
Solar/Wind Harmer
14.111
970125AG2-091 GEN
Solar/Wind Harmer
1.273
971419AH1-201 GEN
Solar/Wind Harmer
6.178
971703AH1-357 GEN
Solar/Wind Harmer
3.475
971707AH1-359 GEN
Solar/Wind Harmer
3.475
20082926HNSMLK 2
Adder
10.092
20083126HNSMLK 4
Adder
10.092
20334926Z1-069 C
Solar/Wind Harmer
3.568
20089126CSLMN_L13
Solar/Wind Harmer
1.405
20089026BF_G21_K23
Solar/Wind Harmer
1.112
944411AF1-106 GEN
Solar/Wind Harmer
0.33
971541AH1-268 GEN
Solar/Wind Harmer
4.643
970335AG2-220 GEN
Solar/Wind Harmer
4.14
971127AH1-005 GEN
Solar/Wind Harmer
2.671
965131AG1-378 GEN
Solar/Wind Harmer
2.555
20120126WRREN CT
Adder
8.032
202652Y1-033 WT C
Solar/Wind Harmer
1.127
20335126GROZ1-110
Adder
2.696
20335226CANZ2-011
Adder
2.62
203854AF2-039 C
Solar/Wind Harmer
0.446
203948AG1-140 C
Solar/Wind Harmer
0.284
20328326MANOR_T86
Adder
0.152
962511AG1-100 GEN
Solar/Wind Harmer
0.64
203962AF1-287 GEN
Solar/Wind Harmer
2.116
20084926LAKVU GN
Adder
0.18
238202AE2-262_GEN
Solar/Wind Harmer
2.525
971627AH1-313 GEN
Solar/Wind Harmer
9.899
941421AE2-139 GEN
Solar/Wind Harmer
3
203830AF1-094 GEN
Solar/Wind Harmer
0.597
957161AF2-010 GEN
Solar/Wind Harmer
7.569
972271AH1-720 GEN
Adder
6.453
960051AF2-296 GEN
Solar/Wind Harmer
1.946
970647AG2-420 GEN
Solar/Wind Harmer
1.901
959441AF2-235 GEN
Solar/Wind Harmer
0.277
203856AF2-165 C
Solar/Wind Harmer
1.079
971185AH1-051 GEN
Solar/Wind Harmer
2.193
971355AH1-158 GEN
Solar/Wind Harmer
2.55
203818AF1-086 GEN
Solar/Wind Harmer
2.263
200917MEHOOPANY_G
Solar/Wind Harmer
3.077
970899AG2-561 GEN
Solar/Wind Harmer
1.478
970679AG2-439 GEN
Solar/Wind Harmer
0.706
945751AF1-240 GEN
Solar/Wind Harmer
1.071
203932AE1-123
Adder
1.25
970643AG2-418 GEN
Solar/Wind Harmer
1.143
970713AG2-456 GEN
Solar/Wind Harmer
13.9
971705AH1-358 GEN
Solar/Wind Harmer
4.041
971709AH1-360 GEN
Solar/Wind Harmer
4.041
20082826HNSMLK 1
Adder
10.092
20083026HNSMLK 3
Adder
10.092
20089226LOOKOUT
Solar/Wind Harmer
1.368
203987AE2-118 C
Solar/Wind Harmer
2.954
20335026MILZ1-092
Adder
3.336
944411AF1-106 GEN
Solar/Wind Harmer
3.073
20326126BLOSSBCT
Adder
3.329
959471AF2-238 GEN
Solar/Wind Harmer
0.832
970337AG2-221 GEN
Solar/Wind Harmer
2.752
964391AG1-301 GEN
Solar/Wind Harmer
0.822
971279AH1-102 GEN
Solar/Wind Harmer
10.909
970511AG2-327 GEN
Solar/Wind Harmer
1.329
20094526CT_V3-030
Solar/Wind Harmer
0.939
970267AG2-176 GEN
Solar/Wind Harmer
17.808
203954AE2-126 C
Solar/Wind Harmer
0.708
203860AG1-193 C
Solar/Wind Harmer
0.342
961971AG1-040 GEN
Solar/Wind Harmer
0.671
972169AH1-667 GEN
Solar/Wind Harmer
1.964
20091326SHAW-D
Adder
0.717
203835AF1-098 GEN
Solar/Wind Harmer
2.618
203813AE2-344_GEN
Solar/Wind Harmer
12.284
20072226SHAWVL 2
Adder
14.287
238183AE2-316 GEN
Solar/Wind Harmer
4.342
20080926SITHE
50/50
0.783
203839AF1-321 GEN
Solar/Wind Harmer
4.32
20084626FORWARD
Solar/Wind Harmer
1.702
203857AF2-221 C
Solar/Wind Harmer
3.182
970123AG2-090 GEN
Solar/Wind Harmer
2.97
20088626ARWF_N39
Solar/Wind Harmer
3.702
20303426NA_O38_P22
Solar/Wind Harmer
2.997
20088926STNY CRK
Solar/Wind Harmer
2.379
971427AH1-205 GEN
Solar/Wind Harmer
2.873
203940AF1-140 C
Solar/Wind Harmer
0.954
20083426SW_E13_K22
Solar/Wind Harmer
0.567
971441AH1-212 GEN
Solar/Wind Harmer
3.609
972077AH1-588 GEN
Solar/Wind Harmer
41.7
972079AH1-589 GEN
Solar/Wind Harmer
34.346
970715AG2-457 GEN
Solar/Wind Harmer
13.9
944781AF1-143 GEN
Solar/Wind Harmer
4.814
972075AH1-587 GEN
Solar/Wind Harmer
31.782
20398826ARMNA MT
Solar/Wind Harmer
3.475
203859AF2-294 C
Solar/Wind Harmer
2.31
970313AG2-206 GEN
Solar/Wind Harmer
6.378
203952AE2-129 C
Solar/Wind Harmer
0.774
203946AE2-131 C
Solar/Wind Harmer
0.772
962411AG1-090 GEN
Solar/Wind Harmer
12.137
970305AG2-200 GEN
Solar/Wind Harmer
2.54
203955AF1-039 C O1
Solar/Wind Harmer
0.548
203980AG1-197 GEN
Solar/Wind Harmer
0.51
203963AG1-253 GEN
Solar/Wind Harmer
0.433
971931AH1-490 GEN
Solar/Wind Harmer
2.117
946381AF1-302 GEN
Solar/Wind Harmer
2.173
238217AF1-153 C O1
Solar/Wind Harmer
0.613
203947AF1-006 C
Solar/Wind Harmer
0.558
203979AG1-198 GEN
Solar/Wind Harmer
0.359
971933AH1-491 GEN
Solar/Wind Harmer
1.973
203853AF1-134 C O1
Solar/Wind Harmer
0.588
216419AE2-001 C
Solar/Wind Harmer
1.864
203848AF2-166 C
Solar/Wind Harmer
1.507
946071AF1-272 GEN
Solar/Wind Helper
1.501
20084926LAKVU GN
Adder
0.18
238206AE2-263_GEN
Solar/Wind Harmer
2.353
970647AG2-420 GEN
Solar/Wind Harmer
0.221
238215AE2-248 C
Solar/Wind Harmer
1.476
971183AH1-050 GEN
Solar/Wind Harmer
3.655
970643AG2-418 GEN
Solar/Wind Harmer
0.531
24035802GEN-Y1-012
Adder
0.199
961581Q1080_CY23
External Queue
25.98905372619629
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.207
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.643
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.438
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.168
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.926
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
G-007ALTFEXP_G-007A->PJM
CMTX
0.762
CBM NorthLTFEXP_CBM-N->PJM
CBM
32.723
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-016A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-016A_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1068.29
MW Contribution:15.02
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.671
20079426CONEMAGH
50/50
2.697
203841AF2-001_GEN
Solar/Wind Harmer
4.807
971879AH1-460 GEN
Solar/Wind Harmer
15.62
970125AG2-091 GEN
Solar/Wind Harmer
1.404
971419AH1-201 GEN
Solar/Wind Harmer
6.844
20089126CSLMN_L13
Solar/Wind Harmer
1.564
20089026BF_G21_K23
Solar/Wind Harmer
1.238
971703AH1-357 GEN
Solar/Wind Harmer
3.267
971707AH1-359 GEN
Solar/Wind Harmer
3.267
20334926Z1-069 C
Solar/Wind Harmer
3.345
971541AH1-268 GEN
Solar/Wind Harmer
5.374
20082926HNSMLK 2
Adder
8.075
20083126HNSMLK 4
Adder
8.075
944411AF1-106 GEN
Solar/Wind Harmer
0.309
965131AG1-378 GEN
Solar/Wind Harmer
2.713
202652Y1-033 WT C
Solar/Wind Harmer
1.256
970335AG2-220 GEN
Solar/Wind Harmer
3.897
971127AH1-005 GEN
Solar/Wind Harmer
2.514
20120126WRREN CT
Adder
7.571
203854AF2-039 C
Solar/Wind Harmer
0.469
20335126GROZ1-110
Adder
2.585
20335226CANZ2-011
Adder
2.513
960051AF2-296 GEN
Solar/Wind Harmer
2.104
238202AE2-262_GEN
Solar/Wind Harmer
2.632
971627AH1-313 GEN
Solar/Wind Harmer
10.32
970647AG2-420 GEN
Solar/Wind Harmer
2.057
971185AH1-051 GEN
Solar/Wind Harmer
2.482
971355AH1-158 GEN
Solar/Wind Harmer
2.886
203856AF2-165 C
Solar/Wind Harmer
1.21
20328326MANOR_T86
Adder
0.144
959441AF2-235 GEN
Solar/Wind Harmer
0.298
203818AF1-086 GEN
Solar/Wind Harmer
2.51
203948AG1-140 C
Solar/Wind Harmer
0.255
203932AE1-123
Adder
1.915
941421AE2-139 GEN
Solar/Wind Harmer
2.882
957161AF2-010 GEN
Solar/Wind Harmer
7.302
203830AF1-094 GEN
Solar/Wind Harmer
0.573
972271AH1-720 GEN
Adder
6.174
203962AF1-287 GEN
Solar/Wind Harmer
1.874
962511AG1-100 GEN
Solar/Wind Harmer
0.565
238219AF1-167 C
Solar/Wind Harmer
1.261
945751AF1-240 GEN
Solar/Wind Harmer
1.444
20084926LAKVU GN
Adder
0.161
970899AG2-561 GEN
Solar/Wind Harmer
1.694
200917MEHOOPANY_G
Solar/Wind Harmer
2.926
970679AG2-439 GEN
Solar/Wind Harmer
0.674
970643AG2-418 GEN
Solar/Wind Harmer
1.197
20083726HOMER C1
50/50
239.414
20083926HOMER C3
50/50
193.563
20083826HOMER C2
50/50
182.843
20050326C.SLOPE
50/50
0.672
20092526R32
Solar/Wind Harmer
3.88
203844AF2-092 C
Solar/Wind Harmer
2.616
203850AG1-041 C
Solar/Wind Harmer
2.599
203961AE2-224 GEN
Solar/Wind Harmer
6.52
20091526CHSTN_FL
Solar/Wind Harmer
1.648
20080926SITHE
50/50
0.77
20081226ALY HYDR
50/50
0.182
203839AF1-321 GEN
Solar/Wind Harmer
4.807
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.509
970123AG2-090 GEN
Solar/Wind Harmer
3.275
20088926STNY CRK
Solar/Wind Harmer
2.635
971427AH1-205 GEN
Solar/Wind Harmer
3.183
20083426SW_E13_K22
Solar/Wind Harmer
0.631
203940AF1-140 C
Solar/Wind Harmer
1.043
20088626ARWF_N39
Solar/Wind Harmer
3.825
20303426NA_O38_P22
Solar/Wind Harmer
3.097
971441AH1-212 GEN
Solar/Wind Harmer
3.949
944781AF1-143 GEN
Solar/Wind Harmer
5.362
972077AH1-588 GEN
Solar/Wind Harmer
39.202
972079AH1-589 GEN
Solar/Wind Harmer
32.288
970715AG2-457 GEN
Solar/Wind Harmer
13.067
972075AH1-587 GEN
Solar/Wind Harmer
30.457
20398826ARMNA MT
Solar/Wind Harmer
3.257
203952AE2-129 C
Solar/Wind Harmer
0.822
203946AE2-131 C
Solar/Wind Harmer
0.82
962411AG1-090 GEN
Solar/Wind Harmer
12.886
203955AF1-039 C O1
Solar/Wind Harmer
0.611
203859AF2-294 C
Solar/Wind Harmer
2.162
970313AG2-206 GEN
Solar/Wind Harmer
6.005
970305AG2-200 GEN
Solar/Wind Harmer
2.395
946381AF1-302 GEN
Solar/Wind Harmer
2.384
238217AF1-153 C O1
Solar/Wind Harmer
0.675
203853AF1-134 C O1
Solar/Wind Harmer
0.636
203848AF2-166 C
Solar/Wind Harmer
1.977
203980AG1-197 GEN
Solar/Wind Harmer
0.448
203963AG1-253 GEN
Solar/Wind Harmer
0.389
216419AE2-001 C
Solar/Wind Harmer
1.945
203979AG1-198 GEN
Solar/Wind Harmer
0.344
971933AH1-491 GEN
Solar/Wind Harmer
1.893
971931AH1-490 GEN
Solar/Wind Harmer
1.868
203947AF1-006 C
Solar/Wind Harmer
0.496
946071AF1-272 GEN
Solar/Wind Helper
2.07
203843AF2-002_GEN
Solar/Wind Harmer
2.403
970631AG2-411 GEN
Solar/Wind Harmer
15.016
20088826HIGHLAND
Solar/Wind Harmer
3.621
957561AF2-050 GEN
Solar/Wind Harmer
10.764
971423AH1-203 GEN
Solar/Wind Harmer
15.011
964201AG1-281 GEN
Solar/Wind Harmer
1.202
20089226LOOKOUT
Solar/Wind Harmer
1.523
970713AG2-456 GEN
Solar/Wind Harmer
13.067
971705AH1-358 GEN
Solar/Wind Harmer
3.799
971709AH1-360 GEN
Solar/Wind Harmer
3.799
203987AE2-118 C
Solar/Wind Harmer
3.112
971279AH1-102 GEN
Solar/Wind Harmer
12.627
20094526CT_V3-030
Solar/Wind Harmer
1.037
964391AG1-301 GEN
Solar/Wind Harmer
0.865
20082826HNSMLK 1
Adder
8.075
20083026HNSMLK 3
Adder
8.075
20335026MILZ1-092
Adder
3.123
944411AF1-106 GEN
Solar/Wind Harmer
2.877
20326126BLOSSBCT
Adder
3.137
959471AF2-238 GEN
Solar/Wind Harmer
0.784
970337AG2-221 GEN
Solar/Wind Harmer
2.592
970511AG2-327 GEN
Solar/Wind Harmer
1.251
203954AE2-126 C
Solar/Wind Harmer
0.727
972169AH1-667 GEN
Solar/Wind Harmer
2.063
20091326SHAW-D
Adder
0.754
238183AE2-316 GEN
Solar/Wind Harmer
4.765
20072226SHAWVL 2
Adder
14.939
203860AG1-193 C
Solar/Wind Harmer
0.325
970267AG2-176 GEN
Solar/Wind Harmer
15.603
238206AE2-263_GEN
Solar/Wind Harmer
2.453
970647AG2-420 GEN
Solar/Wind Harmer
0.239
971183AH1-050 GEN
Solar/Wind Harmer
4.136
203835AF1-098 GEN
Solar/Wind Harmer
2.378
961971AG1-040 GEN
Solar/Wind Harmer
0.591
238215AE2-248 C
Solar/Wind Harmer
1.541
203813AE2-344_GEN
Solar/Wind Harmer
10.868
20084926LAKVU GN
Adder
0.161
970643AG2-418 GEN
Solar/Wind Harmer
0.557
940863AE2-074 GEN
Solar/Wind Harmer
2.833
20090526Q36
Solar/Wind Harmer
2.379
203993AD2-133_GEN1
Solar/Wind Harmer
2.379
203804AE2-113_GEN
Solar/Wind Harmer
7.059
941231AE2-117 GEN
Solar/Wind Harmer
0.874
20083226HNSMLK 5
Adder
8.075
965121AG1-377 GEN
Solar/Wind Harmer
2.713
970555AG2-356 GEN
Solar/Wind Harmer
2.592
203855AF2-088 C
Solar/Wind Harmer
0.226
970663AG2-429 GEN
Solar/Wind Harmer
7.026
970663AG2-429 GEN
Solar/Wind Harmer
1.144
203846AF2-130 C
Solar/Wind Harmer
0.565
970677AG2-438 GEN
Solar/Wind Harmer
0.946
966771AG1-548 GEN
Solar/Wind Harmer
13.787
966771AG1-548 GEN
Solar/Wind Harmer
2.672
203926AA2-133 GEN
Adder
2.166
20084926LAKVU GN
Adder
0.181
20334726NME_Y1-047
Adder
1.966
20390726Y2-042
Adder
1.612
961581Q1080_CY23
External Queue
23.454303741455078
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.229
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.713
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.682
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.174
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.03
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.291
G-007ALTFEXP_G-007A->PJM
CMTX
0.859
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.653
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:108.9 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1067.2
MW Contribution:13.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.225
20079426CONEMAGH
50/50
2.285
203841AF2-001_GEN
Solar/Wind Harmer
4.231
971879AH1-460 GEN
Solar/Wind Harmer
13.827
970125AG2-091 GEN
Solar/Wind Harmer
1.248
971419AH1-201 GEN
Solar/Wind Harmer
6.062
971703AH1-357 GEN
Solar/Wind Harmer
3.389
971707AH1-359 GEN
Solar/Wind Harmer
3.389
20334926Z1-069 C
Solar/Wind Harmer
3.451
20089126CSLMN_L13
Solar/Wind Harmer
1.376
20089026BF_G21_K23
Solar/Wind Harmer
1.089
20082926HNSMLK 2
Adder
8.888
20083126HNSMLK 4
Adder
8.888
944411AF1-106 GEN
Solar/Wind Harmer
0.318
971541AH1-268 GEN
Solar/Wind Harmer
4.764
965131AG1-378 GEN
Solar/Wind Harmer
2.667
970335AG2-220 GEN
Solar/Wind Harmer
4.008
971127AH1-005 GEN
Solar/Wind Harmer
2.586
20120126WRREN CT
Adder
8.023
238219AF1-167 C
Solar/Wind Harmer
1.644
971185AH1-051 GEN
Solar/Wind Harmer
2.873
971355AH1-158 GEN
Solar/Wind Harmer
3.341
970647AG2-420 GEN
Solar/Wind Harmer
2.365
202652Y1-033 WT C
Solar/Wind Harmer
1.103
203854AF2-039 C
Solar/Wind Harmer
0.481
203856AF2-165 C
Solar/Wind Harmer
1.398
203932AE1-123
Adder
2.301
20335126GROZ1-110
Adder
2.667
20335226CANZ2-011
Adder
2.592
959441AF2-235 GEN
Solar/Wind Harmer
0.34
238202AE2-262_GEN
Solar/Wind Harmer
2.732
971627AH1-313 GEN
Solar/Wind Harmer
10.713
960051AF2-296 GEN
Solar/Wind Harmer
2.134
957161AF2-010 GEN
Solar/Wind Harmer
8.095
203830AF1-094 GEN
Solar/Wind Harmer
0.635
203948AG1-140 C
Solar/Wind Harmer
0.274
20328326MANOR_T86
Adder
0.149
945751AF1-240 GEN
Solar/Wind Harmer
1.622
203962AF1-287 GEN
Solar/Wind Harmer
2.05
962511AG1-100 GEN
Solar/Wind Harmer
0.619
20084926LAKVU GN
Adder
0.174
203818AF1-086 GEN
Solar/Wind Harmer
2.522
941421AE2-139 GEN
Solar/Wind Harmer
2.971
972271AH1-720 GEN
Adder
6.359
200917MEHOOPANY_G
Solar/Wind Harmer
3.008
970899AG2-561 GEN
Solar/Wind Harmer
1.709
970679AG2-439 GEN
Solar/Wind Harmer
0.692
970643AG2-418 GEN
Solar/Wind Harmer
1.17
20083726HOMER C1
50/50
236.905
20083926HOMER C3
50/50
197.325
20083826HOMER C2
50/50
186.396
20050326C.SLOPE
50/50
0.607
203961AE2-224 GEN
Solar/Wind Harmer
6.197
20092526R32
Solar/Wind Harmer
3.488
203844AF2-092 C
Solar/Wind Harmer
2.34
203850AG1-041 C
Solar/Wind Harmer
2.329
20091526CHSTN_FL
Solar/Wind Harmer
1.52
940863AE2-074 GEN
Solar/Wind Harmer
2.929
203804AE2-113_GEN
Solar/Wind Harmer
7.361
20083226HNSMLK 5
Adder
8.888
20090526Q36
Solar/Wind Harmer
2.277
203993AD2-133_GEN1
Solar/Wind Harmer
2.277
941231AE2-117 GEN
Solar/Wind Harmer
0.831
965121AG1-377 GEN
Solar/Wind Harmer
2.667
970555AG2-356 GEN
Solar/Wind Harmer
2.667
970663AG2-429 GEN
Solar/Wind Harmer
9.078
970663AG2-429 GEN
Solar/Wind Harmer
1.478
203855AF2-088 C
Solar/Wind Harmer
0.231
203846AF2-130 C
Solar/Wind Harmer
0.666
970677AG2-438 GEN
Solar/Wind Harmer
1.048
966771AG1-548 GEN
Solar/Wind Harmer
15.227
966771AG1-548 GEN
Solar/Wind Harmer
2.951
20084926LAKVU GN
Adder
0.196
203926AA2-133 GEN
Adder
2.229
20334726NME_Y1-047
Adder
2.021
20390726Y2-042
Adder
1.655
971055AG2-654 GEN
Solar/Wind Harmer
0.64
203843AF2-002_GEN
Solar/Wind Harmer
2.116
970631AG2-411 GEN
Solar/Wind Harmer
13.291
957561AF2-050 GEN
Solar/Wind Harmer
10.23
20088826HIGHLAND
Solar/Wind Harmer
3.255
971423AH1-203 GEN
Solar/Wind Harmer
13.269
964201AG1-281 GEN
Solar/Wind Harmer
1.098
970713AG2-456 GEN
Solar/Wind Harmer
13.555
971705AH1-358 GEN
Solar/Wind Harmer
3.94
971709AH1-360 GEN
Solar/Wind Harmer
3.94
20089226LOOKOUT
Solar/Wind Harmer
1.34
20082826HNSMLK 1
Adder
8.888
20083026HNSMLK 3
Adder
8.888
203987AE2-118 C
Solar/Wind Harmer
2.942
20326126BLOSSBCT
Adder
3.229
20335026MILZ1-092
Adder
3.213
944411AF1-106 GEN
Solar/Wind Harmer
2.96
971279AH1-102 GEN
Solar/Wind Harmer
11.195
20094526CT_V3-030
Solar/Wind Harmer
0.97
964391AG1-301 GEN
Solar/Wind Harmer
0.822
238183AE2-316 GEN
Solar/Wind Harmer
5.648
959471AF2-238 GEN
Solar/Wind Harmer
0.806
970337AG2-221 GEN
Solar/Wind Harmer
2.667
970511AG2-327 GEN
Solar/Wind Harmer
1.287
203954AE2-126 C
Solar/Wind Harmer
0.756
203860AG1-193 C
Solar/Wind Harmer
0.367
971183AH1-050 GEN
Solar/Wind Harmer
4.788
970647AG2-420 GEN
Solar/Wind Harmer
0.275
972169AH1-667 GEN
Solar/Wind Harmer
2.116
20091326SHAW-D
Adder
0.773
970267AG2-176 GEN
Solar/Wind Harmer
17.249
20072226SHAWVL 2
Adder
15.552
961971AG1-040 GEN
Solar/Wind Harmer
0.65
238206AE2-263_GEN
Solar/Wind Harmer
2.547
203835AF1-098 GEN
Solar/Wind Harmer
2.563
203813AE2-344_GEN
Solar/Wind Harmer
11.887
20084926LAKVU GN
Adder
0.174
238215AE2-248 C
Solar/Wind Harmer
1.577
970643AG2-418 GEN
Solar/Wind Harmer
0.544
971865AH1-452 GEN
Solar/Wind Harmer
0.783
24035802GEN-Y1-012
Adder
0.187
20080926SITHE
50/50
0.762
203839AF1-321 GEN
Solar/Wind Harmer
4.231
20084626FORWARD
Solar/Wind Harmer
1.668
203857AF2-221 C
Solar/Wind Harmer
3.12
970123AG2-090 GEN
Solar/Wind Harmer
2.912
20088626ARWF_N39
Solar/Wind Harmer
3.636
20303426NA_O38_P22
Solar/Wind Harmer
2.943
20088926STNY CRK
Solar/Wind Harmer
2.334
971427AH1-205 GEN
Solar/Wind Harmer
2.819
203940AF1-140 C
Solar/Wind Harmer
0.941
20083426SW_E13_K22
Solar/Wind Harmer
0.556
971441AH1-212 GEN
Solar/Wind Harmer
3.578
972077AH1-588 GEN
Solar/Wind Harmer
40.664
972079AH1-589 GEN
Solar/Wind Harmer
33.493
970715AG2-457 GEN
Solar/Wind Harmer
13.555
972075AH1-587 GEN
Solar/Wind Harmer
31.692
944781AF1-143 GEN
Solar/Wind Harmer
4.717
20398826ARMNA MT
Solar/Wind Harmer
3.349
946381AF1-302 GEN
Solar/Wind Harmer
2.826
203952AE2-129 C
Solar/Wind Harmer
0.808
203946AE2-131 C
Solar/Wind Harmer
0.806
962411AG1-090 GEN
Solar/Wind Harmer
12.668
203859AF2-294 C
Solar/Wind Harmer
2.224
970313AG2-206 GEN
Solar/Wind Harmer
6.176
970305AG2-200 GEN
Solar/Wind Harmer
2.538
238217AF1-153 C O1
Solar/Wind Harmer
0.739
203955AF1-039 C O1
Solar/Wind Harmer
0.537
203848AF2-166 C
Solar/Wind Harmer
2.332
203980AG1-197 GEN
Solar/Wind Harmer
0.493
203853AF1-134 C O1
Solar/Wind Harmer
0.645
203979AG1-198 GEN
Solar/Wind Harmer
0.381
971933AH1-491 GEN
Solar/Wind Harmer
2.095
203963AG1-253 GEN
Solar/Wind Harmer
0.419
971931AH1-490 GEN
Solar/Wind Harmer
2.046
216419AE2-001 C
Solar/Wind Harmer
1.996
203947AF1-006 C
Solar/Wind Harmer
0.539
946071AF1-272 GEN
Solar/Wind Helper
1.397
961581Q1080_CY23
External Queue
23.464759826660156
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.207
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.644
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.168
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.93
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.283
G-007ALTFEXP_G-007A->PJM
CMTX
0.72
CBM NorthLTFEXP_CBM-N->PJM
CBM
31.335
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P2-2_MP-138-100_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-100_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.04 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1058.75
MW Contribution:14.34
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.282
20079426CONEMAGH
50/50
2.35
203841AF2-001_GEN
Solar/Wind Harmer
4.57
971879AH1-460 GEN
Solar/Wind Harmer
14.79
20089126CSLMN_L13
Solar/Wind Harmer
1.958
20089026BF_G21_K23
Solar/Wind Harmer
1.55
970125AG2-091 GEN
Solar/Wind Harmer
1.325
202652Y1-033 WT C
Solar/Wind Harmer
2.051
971419AH1-201 GEN
Solar/Wind Harmer
6.959
971703AH1-357 GEN
Solar/Wind Harmer
3.236
971707AH1-359 GEN
Solar/Wind Harmer
3.236
20334926Z1-069 C
Solar/Wind Harmer
3.31
971541AH1-268 GEN
Solar/Wind Harmer
4.83
20082926HNSMLK 2
Adder
8.089
20083126HNSMLK 4
Adder
8.089
944411AF1-106 GEN
Solar/Wind Harmer
0.306
965131AG1-378 GEN
Solar/Wind Harmer
2.615
970335AG2-220 GEN
Solar/Wind Harmer
3.847
971127AH1-005 GEN
Solar/Wind Harmer
2.482
20120126WRREN CT
Adder
7.527
203854AF2-039 C
Solar/Wind Harmer
0.458
20335126GROZ1-110
Adder
2.548
20335226CANZ2-011
Adder
2.476
970647AG2-420 GEN
Solar/Wind Harmer
2.074
971185AH1-051 GEN
Solar/Wind Harmer
2.504
971355AH1-158 GEN
Solar/Wind Harmer
2.911
960051AF2-296 GEN
Solar/Wind Harmer
2.054
203856AF2-165 C
Solar/Wind Harmer
1.221
238202AE2-262_GEN
Solar/Wind Harmer
2.577
971627AH1-313 GEN
Solar/Wind Harmer
10.102
20328326MANOR_T86
Adder
0.142
959441AF2-235 GEN
Solar/Wind Harmer
0.301
203932AE1-123
Adder
1.94
203948AG1-140 C
Solar/Wind Harmer
0.255
203818AF1-086 GEN
Solar/Wind Harmer
2.451
238219AF1-167 C
Solar/Wind Harmer
1.294
957161AF2-010 GEN
Solar/Wind Harmer
7.338
203830AF1-094 GEN
Solar/Wind Harmer
0.576
203962AF1-287 GEN
Solar/Wind Harmer
1.882
962511AG1-100 GEN
Solar/Wind Harmer
0.567
941421AE2-139 GEN
Solar/Wind Harmer
2.837
972271AH1-720 GEN
Adder
6.077
20084926LAKVU GN
Adder
0.161
945751AF1-240 GEN
Solar/Wind Harmer
1.446
970899AG2-561 GEN
Solar/Wind Harmer
1.668
200917MEHOOPANY_G
Solar/Wind Harmer
2.878
970679AG2-439 GEN
Solar/Wind Harmer
0.661
970643AG2-418 GEN
Solar/Wind Harmer
1.142
20083726HOMER C1
50/50
236.179
20083926HOMER C3
50/50
191.618
20083826HOMER C2
50/50
181.005
20050326C.SLOPE
50/50
0.624
203844AF2-092 C
Solar/Wind Harmer
2.526
20092526R32
Solar/Wind Harmer
3.652
203850AG1-041 C
Solar/Wind Harmer
2.501
203961AE2-224 GEN
Solar/Wind Harmer
6.239
20091526CHSTN_FL
Solar/Wind Harmer
1.558
940863AE2-074 GEN
Solar/Wind Harmer
2.804
20090526Q36
Solar/Wind Harmer
2.274
203993AD2-133_GEN1
Solar/Wind Harmer
2.274
203804AE2-113_GEN
Solar/Wind Harmer
6.982
941231AE2-117 GEN
Solar/Wind Harmer
0.834
20083226HNSMLK 5
Adder
8.089
965121AG1-377 GEN
Solar/Wind Harmer
2.615
970555AG2-356 GEN
Solar/Wind Harmer
2.56
203855AF2-088 C
Solar/Wind Harmer
0.22
970663AG2-429 GEN
Solar/Wind Harmer
7.189
970663AG2-429 GEN
Solar/Wind Harmer
1.17
203846AF2-130 C
Solar/Wind Harmer
0.571
970677AG2-438 GEN
Solar/Wind Harmer
0.951
966771AG1-548 GEN
Solar/Wind Harmer
13.849
966771AG1-548 GEN
Solar/Wind Harmer
2.684
20084926LAKVU GN
Adder
0.181
20080926SITHE
50/50
0.76
20084126DEEPCRK2
50/50
0.139
20084026DEEPCRK1
50/50
0.137
203839AF1-321 GEN
Solar/Wind Harmer
4.57
20084626FORWARD
Solar/Wind Harmer
1.799
20083426SW_E13_K22
Solar/Wind Harmer
0.666
944781AF1-143 GEN
Solar/Wind Harmer
6.712
203857AF2-221 C
Solar/Wind Harmer
3.312
970123AG2-090 GEN
Solar/Wind Harmer
3.091
203955AF1-039 C O1
Solar/Wind Harmer
0.999
971427AH1-205 GEN
Solar/Wind Harmer
3.237
20088926STNY CRK
Solar/Wind Harmer
2.676
203940AF1-140 C
Solar/Wind Harmer
0.989
20088626ARWF_N39
Solar/Wind Harmer
3.659
20303426NA_O38_P22
Solar/Wind Harmer
2.962
971441AH1-212 GEN
Solar/Wind Harmer
3.68
972077AH1-588 GEN
Solar/Wind Harmer
38.835
972079AH1-589 GEN
Solar/Wind Harmer
31.986
970715AG2-457 GEN
Solar/Wind Harmer
12.945
972075AH1-587 GEN
Solar/Wind Harmer
30.135
20398826ARMNA MT
Solar/Wind Harmer
3.218
203952AE2-129 C
Solar/Wind Harmer
0.792
203946AE2-131 C
Solar/Wind Harmer
0.79
962411AG1-090 GEN
Solar/Wind Harmer
12.419
203859AF2-294 C
Solar/Wind Harmer
2.136
970313AG2-206 GEN
Solar/Wind Harmer
5.928
970305AG2-200 GEN
Solar/Wind Harmer
2.381
946381AF1-302 GEN
Solar/Wind Harmer
2.395
238217AF1-153 C O1
Solar/Wind Harmer
0.67
203853AF1-134 C O1
Solar/Wind Harmer
0.621
203848AF2-166 C
Solar/Wind Harmer
1.999
203980AG1-197 GEN
Solar/Wind Harmer
0.45
203963AG1-253 GEN
Solar/Wind Harmer
0.39
203979AG1-198 GEN
Solar/Wind Harmer
0.346
971933AH1-491 GEN
Solar/Wind Harmer
1.902
216419AE2-001 C
Solar/Wind Harmer
1.896
971931AH1-490 GEN
Solar/Wind Harmer
1.876
203947AF1-006 C
Solar/Wind Harmer
0.498
946071AF1-272 GEN
Solar/Wind Helper
1.373
203926AA2-133 GEN
Adder
2.133
20334726NME_Y1-047
Adder
1.933
20390726Y2-042
Adder
1.582
20081326YOUGH
50/50
0.084
203843AF2-002_GEN
Solar/Wind Harmer
2.285
970631AG2-411 GEN
Solar/Wind Harmer
14.34
20089226LOOKOUT
Solar/Wind Harmer
1.907
971423AH1-203 GEN
Solar/Wind Harmer
15.451
20088826HIGHLAND
Solar/Wind Harmer
3.408
957561AF2-050 GEN
Solar/Wind Harmer
10.299
964201AG1-281 GEN
Solar/Wind Harmer
1.141
970713AG2-456 GEN
Solar/Wind Harmer
12.945
971705AH1-358 GEN
Solar/Wind Harmer
3.763
971709AH1-360 GEN
Solar/Wind Harmer
3.763
203987AE2-118 C
Solar/Wind Harmer
2.967
971279AH1-102 GEN
Solar/Wind Harmer
11.348
20082826HNSMLK 1
Adder
8.089
20083026HNSMLK 3
Adder
8.089
20094526CT_V3-030
Solar/Wind Harmer
0.981
964391AG1-301 GEN
Solar/Wind Harmer
0.825
20335026MILZ1-092
Adder
3.086
944411AF1-106 GEN
Solar/Wind Harmer
2.843
20326126BLOSSBCT
Adder
3.098
959471AF2-238 GEN
Solar/Wind Harmer
0.774
970337AG2-221 GEN
Solar/Wind Harmer
2.56
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203954AE2-126 C
Solar/Wind Harmer
0.714
238183AE2-316 GEN
Solar/Wind Harmer
4.786
972169AH1-667 GEN
Solar/Wind Harmer
2.015
20091326SHAW-D
Adder
0.736
203860AG1-193 C
Solar/Wind Harmer
0.327
20072226SHAWVL 2
Adder
14.642
970267AG2-176 GEN
Solar/Wind Harmer
15.673
970647AG2-420 GEN
Solar/Wind Harmer
0.241
971183AH1-050 GEN
Solar/Wind Harmer
4.173
238206AE2-263_GEN
Solar/Wind Harmer
2.401
203835AF1-098 GEN
Solar/Wind Harmer
2.379
961971AG1-040 GEN
Solar/Wind Harmer
0.594
238215AE2-248 C
Solar/Wind Harmer
1.501
203813AE2-344_GEN
Solar/Wind Harmer
10.913
20084926LAKVU GN
Adder
0.161
970643AG2-418 GEN
Solar/Wind Harmer
0.531
961581Q1080_CY23
External Queue
23.213441848754883
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.198
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.618
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.02
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.174
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.901
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.296
G-007ALTFEXP_G-007A->PJM
CMTX
0.613
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.012
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT18_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT18_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.12 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1040.01
MW Contribution:12.91
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.743
203839AF1-321 GEN
Solar/Wind Harmer
4.112
20084626FORWARD
Solar/Wind Harmer
1.62
203857AF2-221 C
Solar/Wind Harmer
3.029
970123AG2-090 GEN
Solar/Wind Harmer
2.827
20088626ARWF_N39
Solar/Wind Harmer
3.519
20303426NA_O38_P22
Solar/Wind Harmer
2.849
20088926STNY CRK
Solar/Wind Harmer
2.266
971427AH1-205 GEN
Solar/Wind Harmer
2.737
203940AF1-140 C
Solar/Wind Harmer
0.91
20083426SW_E13_K22
Solar/Wind Harmer
0.54
971441AH1-212 GEN
Solar/Wind Harmer
3.448
972077AH1-588 GEN
Solar/Wind Harmer
37.752
972079AH1-589 GEN
Solar/Wind Harmer
31.094
970715AG2-457 GEN
Solar/Wind Harmer
12.584
944781AF1-143 GEN
Solar/Wind Harmer
4.587
972075AH1-587 GEN
Solar/Wind Harmer
29.223
20398826ARMNA MT
Solar/Wind Harmer
3.125
20083326SEWRDB34
50/50
7.024
20079426CONEMAGH
50/50
2.216
203841AF2-001_GEN
Solar/Wind Harmer
4.112
971879AH1-460 GEN
Solar/Wind Harmer
13.433
970125AG2-091 GEN
Solar/Wind Harmer
1.212
971419AH1-201 GEN
Solar/Wind Harmer
5.884
971703AH1-357 GEN
Solar/Wind Harmer
3.146
971707AH1-359 GEN
Solar/Wind Harmer
3.146
20334926Z1-069 C
Solar/Wind Harmer
3.218
20089126CSLMN_L13
Solar/Wind Harmer
1.338
20089026BF_G21_K23
Solar/Wind Harmer
1.059
20082926HNSMLK 2
Adder
7.869
20083126HNSMLK 4
Adder
7.869
944411AF1-106 GEN
Solar/Wind Harmer
0.297
971541AH1-268 GEN
Solar/Wind Harmer
4.514
965131AG1-378 GEN
Solar/Wind Harmer
2.474
970335AG2-220 GEN
Solar/Wind Harmer
3.732
971127AH1-005 GEN
Solar/Wind Harmer
2.408
20120126WRREN CT
Adder
7.293
202652Y1-033 WT C
Solar/Wind Harmer
1.075
203854AF2-039 C
Solar/Wind Harmer
0.436
20335126GROZ1-110
Adder
2.463
20335226CANZ2-011
Adder
2.394
970647AG2-420 GEN
Solar/Wind Harmer
1.999
971185AH1-051 GEN
Solar/Wind Harmer
2.411
971355AH1-158 GEN
Solar/Wind Harmer
2.803
203856AF2-165 C
Solar/Wind Harmer
1.176
238202AE2-262_GEN
Solar/Wind Harmer
2.465
971627AH1-313 GEN
Solar/Wind Harmer
9.667
20328326MANOR_T86
Adder
0.137
960051AF2-296 GEN
Solar/Wind Harmer
1.928
959441AF2-235 GEN
Solar/Wind Harmer
0.29
203948AG1-140 C
Solar/Wind Harmer
0.248
203932AE1-123
Adder
1.856
957161AF2-010 GEN
Solar/Wind Harmer
7.097
238219AF1-167 C
Solar/Wind Harmer
1.243
203830AF1-094 GEN
Solar/Wind Harmer
0.557
203962AF1-287 GEN
Solar/Wind Harmer
1.825
962511AG1-100 GEN
Solar/Wind Harmer
0.55
203952AE2-129 C
Solar/Wind Harmer
0.749
203946AE2-131 C
Solar/Wind Harmer
0.748
962411AG1-090 GEN
Solar/Wind Harmer
11.75
203859AF2-294 C
Solar/Wind Harmer
2.073
970313AG2-206 GEN
Solar/Wind Harmer
5.75
970305AG2-200 GEN
Solar/Wind Harmer
2.307
203955AF1-039 C O1
Solar/Wind Harmer
0.523
946381AF1-302 GEN
Solar/Wind Harmer
2.308
238217AF1-153 C O1
Solar/Wind Harmer
0.644
203853AF1-134 C O1
Solar/Wind Harmer
0.583
203980AG1-197 GEN
Solar/Wind Harmer
0.437
203848AF2-166 C
Solar/Wind Harmer
1.918
203963AG1-253 GEN
Solar/Wind Harmer
0.378
203979AG1-198 GEN
Solar/Wind Harmer
0.334
971933AH1-491 GEN
Solar/Wind Harmer
1.84
971931AH1-490 GEN
Solar/Wind Harmer
1.82
216419AE2-001 C
Solar/Wind Harmer
1.812
20083726HOMER C1
50/50
231.121
20083926HOMER C3
50/50
187.218
20083826HOMER C2
50/50
176.849
20050326C.SLOPE
50/50
0.587
203961AE2-224 GEN
Solar/Wind Harmer
6.006
20092526R32
Solar/Wind Harmer
3.381
203844AF2-092 C
Solar/Wind Harmer
2.268
203850AG1-041 C
Solar/Wind Harmer
2.256
20091526CHSTN_FL
Solar/Wind Harmer
1.458
940863AE2-074 GEN
Solar/Wind Harmer
2.726
203804AE2-113_GEN
Solar/Wind Harmer
6.763
20090526Q36
Solar/Wind Harmer
2.143
203993AD2-133_GEN1
Solar/Wind Harmer
2.143
20083226HNSMLK 5
Adder
7.869
941231AE2-117 GEN
Solar/Wind Harmer
0.792
970555AG2-356 GEN
Solar/Wind Harmer
2.483
965121AG1-377 GEN
Solar/Wind Harmer
2.474
203855AF2-088 C
Solar/Wind Harmer
0.21
970663AG2-429 GEN
Solar/Wind Harmer
6.927
970663AG2-429 GEN
Solar/Wind Harmer
1.128
203846AF2-130 C
Solar/Wind Harmer
0.548
970677AG2-438 GEN
Solar/Wind Harmer
0.92
966771AG1-548 GEN
Solar/Wind Harmer
13.401
966771AG1-548 GEN
Solar/Wind Harmer
2.597
203843AF2-002_GEN
Solar/Wind Harmer
2.056
970631AG2-411 GEN
Solar/Wind Harmer
12.913
957561AF2-050 GEN
Solar/Wind Harmer
9.916
20088826HIGHLAND
Solar/Wind Harmer
3.155
971423AH1-203 GEN
Solar/Wind Harmer
12.885
964201AG1-281 GEN
Solar/Wind Harmer
1.06
970713AG2-456 GEN
Solar/Wind Harmer
12.584
971705AH1-358 GEN
Solar/Wind Harmer
3.658
971709AH1-360 GEN
Solar/Wind Harmer
3.658
20089226LOOKOUT
Solar/Wind Harmer
1.303
203987AE2-118 C
Solar/Wind Harmer
2.817
20082826HNSMLK 1
Adder
7.869
20083026HNSMLK 3
Adder
7.869
20335026MILZ1-092
Adder
2.997
944411AF1-106 GEN
Solar/Wind Harmer
2.761
20326126BLOSSBCT
Adder
3.007
971279AH1-102 GEN
Solar/Wind Harmer
10.606
964391AG1-301 GEN
Solar/Wind Harmer
0.784
20094526CT_V3-030
Solar/Wind Harmer
0.914
959471AF2-238 GEN
Solar/Wind Harmer
0.751
970337AG2-221 GEN
Solar/Wind Harmer
2.483
970511AG2-327 GEN
Solar/Wind Harmer
1.198
203954AE2-126 C
Solar/Wind Harmer
0.684
238183AE2-316 GEN
Solar/Wind Harmer
4.613
972169AH1-667 GEN
Solar/Wind Harmer
1.919
20091326SHAW-D
Adder
0.701
203860AG1-193 C
Solar/Wind Harmer
0.316
20072226SHAWVL 2
Adder
14.003
970267AG2-176 GEN
Solar/Wind Harmer
15.199
970647AG2-420 GEN
Solar/Wind Harmer
0.232
971183AH1-050 GEN
Solar/Wind Harmer
4.018
238206AE2-263_GEN
Solar/Wind Harmer
2.298
203835AF1-098 GEN
Solar/Wind Harmer
2.306
961971AG1-040 GEN
Solar/Wind Harmer
0.576
203813AE2-344_GEN
Solar/Wind Harmer
10.582
941421AE2-139 GEN
Solar/Wind Harmer
2.737
972271AH1-720 GEN
Adder
5.866
20084926LAKVU GN
Adder
0.156
203818AF1-086 GEN
Solar/Wind Harmer
2.272
945751AF1-240 GEN
Solar/Wind Harmer
1.357
200917MEHOOPANY_G
Solar/Wind Harmer
2.776
970899AG2-561 GEN
Solar/Wind Harmer
1.52
970679AG2-439 GEN
Solar/Wind Harmer
0.636
970643AG2-418 GEN
Solar/Wind Harmer
1.086
203947AF1-006 C
Solar/Wind Harmer
0.482
946071AF1-272 GEN
Solar/Wind Helper
1.553
20084926LAKVU GN
Adder
0.176
203926AA2-133 GEN
Adder
2.06
20334726NME_Y1-047
Adder
1.865
20390726Y2-042
Adder
1.521
238215AE2-248 C
Solar/Wind Harmer
1.433
20084926LAKVU GN
Adder
0.156
970643AG2-418 GEN
Solar/Wind Harmer
0.505
961581Q1080_CY23
External Queue
22.834562301635742
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.177
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.552
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.246
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.801
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.264
G-007ALTFEXP_G-007A->PJM
CMTX
0.334
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.821
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.44 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.27
MW Contribution:13.55
Bus #Bus NameTypeMW Contribution
203843AF2-002_GEN
Solar/Wind Harmer
2.005
970631AG2-411 GEN
Solar/Wind Harmer
13.547
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20088826HIGHLAND
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
7.308
20089126CSLMN_L13
Solar/Wind Harmer
0.099
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971541AH1-268 GEN
Solar/Wind Harmer
9.014
971703AH1-357 GEN
Solar/Wind Harmer
2.778
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20334926Z1-069 C
Solar/Wind Harmer
1.013
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
971127AH1-005 GEN
Solar/Wind Harmer
2.448
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.001
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
972323AH1-746 GEN
Solar/Wind Harmer
3.441
970899AG2-561 GEN
Solar/Wind Harmer
1.963
945751AF1-240 GEN
Solar/Wind Harmer
1.735
970647AG2-420 GEN
Solar/Wind Harmer
1.873
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971355AH1-158 GEN
Solar/Wind Harmer
4.678
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
9.109
238219AF1-167 C
Solar/Wind Harmer
1.173
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
20328326MANOR_T86
Adder
0.172
203962AF1-287 GEN
Solar/Wind Harmer
1.654
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
970679AG2-439 GEN
Solar/Wind Harmer
0.489
970643AG2-418 GEN
Solar/Wind Harmer
1.033
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
0.015
20092526R32
Solar/Wind Harmer
0.589
203844AF2-092 C
Solar/Wind Harmer
2.257
203850AG1-041 C
Solar/Wind Harmer
2.251
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
965121AG1-377 GEN
Solar/Wind Harmer
1.219
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
2.168
203855AF2-088 C
Solar/Wind Harmer
0.001
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.456
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.001
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
4.678
970267AG2-176 GEN
Solar/Wind Harmer
13.758
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
238215AE2-248 C
Solar/Wind Harmer
1.358
203813AE2-344_GEN
Solar/Wind Harmer
9.593
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.492
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
2.105
970123AG2-090 GEN
Solar/Wind Harmer
2.807
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203940AF1-140 C
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.352
971427AH1-205 GEN
Solar/Wind Harmer
4.872
971441AH1-212 GEN
Solar/Wind Harmer
3.559
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
972075AH1-587 GEN
Solar/Wind Harmer
26.086
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.096
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203859AF2-294 C
Solar/Wind Harmer
1.801
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203947AF1-006 C
Solar/Wind Harmer
0.053
961581Q1080_CY23
External Queue
27.7316951751709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1033.25
MW Contribution:13.55
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
10.964
970125AG2-091 GEN
Solar/Wind Harmer
1.203
971879AH1-460 GEN
Solar/Wind Harmer
13.232
203841AF2-001_GEN
Solar/Wind Harmer
4.009
20079426CONEMAGH
Adder
3.239
971419AH1-201 GEN
Solar/Wind Harmer
7.308
20089126CSLMN_L13
Solar/Wind Harmer
0.099
20089026BF_G21_K23
Solar/Wind Harmer
0.1
971541AH1-268 GEN
Solar/Wind Harmer
9.014
971703AH1-357 GEN
Solar/Wind Harmer
2.778
971707AH1-359 GEN
Solar/Wind Harmer
2.778
20334926Z1-069 C
Solar/Wind Harmer
1.013
965131AG1-378 GEN
Solar/Wind Harmer
1.219
20082926HNSMLK 2
Adder
10.005
20083126HNSMLK 4
Adder
10.005
202652Y1-033 WT C
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
3.357
971127AH1-005 GEN
Solar/Wind Harmer
2.448
20120126WRREN CT
Adder
9.417
203854AF2-039 C
Solar/Wind Harmer
0.001
960051AF2-296 GEN
Solar/Wind Harmer
2.066
203818AF1-086 GEN
Solar/Wind Harmer
0.889
972323AH1-746 GEN
Solar/Wind Harmer
3.441
970899AG2-561 GEN
Solar/Wind Harmer
1.963
945751AF1-240 GEN
Solar/Wind Harmer
1.735
970647AG2-420 GEN
Solar/Wind Harmer
1.873
971185AH1-051 GEN
Solar/Wind Harmer
2.807
971355AH1-158 GEN
Solar/Wind Harmer
4.678
20335126GROZ1-110
Adder
3.11
20335226CANZ2-011
Adder
3.022
203932AE1-123
Adder
2.599
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
9.109
238219AF1-167 C
Solar/Wind Harmer
1.173
203948AG1-140 C
Solar/Wind Harmer
0.241
957161AF2-010 GEN
Solar/Wind Harmer
6.491
203830AF1-094 GEN
Solar/Wind Harmer
0.001
20328326MANOR_T86
Adder
0.172
20083726HOMER C1
50/50
283.774
20083926HOMER C3
50/50
231.688
20083826HOMER C2
50/50
218.856
20050326C.SLOPE
50/50
0.866
203961AE2-224 GEN
Solar/Wind Harmer
0.015
20092526R32
Solar/Wind Harmer
0.589
203844AF2-092 C
Solar/Wind Harmer
2.257
203850AG1-041 C
Solar/Wind Harmer
2.251
20091526CHSTN_FL
Solar/Wind Harmer
0.301
20090526Q36
Solar/Wind Harmer
0.691
203993AD2-133_GEN1
Solar/Wind Harmer
0.684
203804AE2-113_GEN
Solar/Wind Harmer
0.01
965121AG1-377 GEN
Solar/Wind Harmer
1.219
20083226HNSMLK 5
Adder
10.005
970555AG2-356 GEN
Solar/Wind Harmer
2.168
203855AF2-088 C
Solar/Wind Harmer
0.001
970663AG2-429 GEN
Solar/Wind Harmer
6.89
970663AG2-429 GEN
Solar/Wind Harmer
1.506
970677AG2-438 GEN
Solar/Wind Harmer
0.943
966771AG1-548 GEN
Solar/Wind Harmer
2.802
966771AG1-548 GEN
Solar/Wind Harmer
3.502
20084926LAKVU GN
Adder
0.228
203926AA2-133 GEN
Adder
2.56
20334726NME_Y1-047
Adder
2.305
20390726Y2-042
Adder
1.86
971055AG2-654 GEN
Solar/Wind Harmer
0.456
203843AF2-002_GEN
Solar/Wind Harmer
2.005
970631AG2-411 GEN
Solar/Wind Harmer
13.547
957561AF2-050 GEN
Solar/Wind Harmer
9.942
20088826HIGHLAND
Solar/Wind Harmer
0.002
971423AH1-203 GEN
Solar/Wind Harmer
12.679
20089226LOOKOUT
Solar/Wind Harmer
0.283
971279AH1-102 GEN
Solar/Wind Harmer
15.614
203987AE2-118 C
Solar/Wind Harmer
2.81
20094526CT_V3-030
Solar/Wind Harmer
0.238
970713AG2-456 GEN
Solar/Wind Harmer
12.918
203962AF1-287 GEN
Solar/Wind Harmer
1.654
20084926LAKVU GN
Adder
0.203
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.336
200917MEHOOPANY_G
Solar/Wind Harmer
0.345
970679AG2-439 GEN
Solar/Wind Harmer
0.489
970643AG2-418 GEN
Solar/Wind Harmer
1.033
971705AH1-358 GEN
Solar/Wind Harmer
4.63
971709AH1-360 GEN
Solar/Wind Harmer
4.63
20082826HNSMLK 1
Adder
10.005
20083026HNSMLK 3
Adder
10.005
20326126BLOSSBCT
Adder
3.771
20335026MILZ1-092
Adder
3.743
944411AF1-106 GEN
Solar/Wind Harmer
3.819
970337AG2-221 GEN
Solar/Wind Harmer
2.385
203954AE2-126 C
Solar/Wind Harmer
0.002
970511AG2-327 GEN
Solar/Wind Harmer
1.044
972169AH1-667 GEN
Solar/Wind Harmer
1.861
20091326SHAW-D
Adder
0.974
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20072226SHAWVL 2
Adder
19.029
203860AG1-193 C
Solar/Wind Harmer
0.001
970647AG2-420 GEN
Solar/Wind Harmer
0.312
971183AH1-050 GEN
Solar/Wind Harmer
4.678
970267AG2-176 GEN
Solar/Wind Harmer
13.758
238206AE2-263_GEN
Solar/Wind Harmer
0.005
203835AF1-098 GEN
Solar/Wind Harmer
0.005
238215AE2-248 C
Solar/Wind Harmer
1.358
203813AE2-344_GEN
Solar/Wind Harmer
9.593
20084926LAKVU GN
Adder
0.203
970643AG2-418 GEN
Solar/Wind Harmer
0.689
24035802GEN-Y1-012
Adder
0.228
971865AH1-452 GEN
Solar/Wind Harmer
0.492
20080926SITHE
50/50
0.913
203857AF2-221 C
Solar/Wind Harmer
2.105
970123AG2-090 GEN
Solar/Wind Harmer
2.807
203839AF1-321 GEN
Solar/Wind Harmer
4.009
20084626FORWARD
Solar/Wind Harmer
0.001
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
203940AF1-140 C
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.352
971427AH1-205 GEN
Solar/Wind Harmer
4.872
971441AH1-212 GEN
Solar/Wind Harmer
3.559
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.337
972079AH1-589 GEN
Solar/Wind Harmer
39.356
970715AG2-457 GEN
Solar/Wind Harmer
12.918
972075AH1-587 GEN
Solar/Wind Harmer
26.086
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.096
20398826ARMNA MT
Solar/Wind Harmer
0.066
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203859AF2-294 C
Solar/Wind Harmer
1.801
970313AG2-206 GEN
Solar/Wind Harmer
5.01
970305AG2-200 GEN
Solar/Wind Harmer
2.078
203848AF2-166 C
Solar/Wind Harmer
1.843
203980AG1-197 GEN
Solar/Wind Harmer
0.001
216419AE2-001 C
Solar/Wind Harmer
1.715
203963AG1-253 GEN
Solar/Wind Harmer
0.383
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.688
971931AH1-490 GEN
Solar/Wind Harmer
1.649
203947AF1-006 C
Solar/Wind Harmer
0.053
961581Q1080_CY23
External Queue
27.7316951751709
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.039
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.121
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.39
WECLTFEXP_WEC->PJM
CLTF
0.001
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
CBM NorthLTFEXP_CBM-N->PJM
CBM
34.07
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-051A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-051A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.72 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1026.22
MW Contribution:13.05
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
233.467
20083926HOMER C3
50/50
191.631
20083826HOMER C2
50/50
181.017
20050326C.SLOPE
50/50
0.594
20083326SEWRDB34
50/50
7.099
20079426CONEMAGH
50/50
2.238
203841AF2-001_GEN
Solar/Wind Harmer
4.155
971879AH1-460 GEN
Solar/Wind Harmer
13.575
970125AG2-091 GEN
Solar/Wind Harmer
1.225
971419AH1-201 GEN
Solar/Wind Harmer
5.949
971703AH1-357 GEN
Solar/Wind Harmer
3.253
971707AH1-359 GEN
Solar/Wind Harmer
3.253
20334926Z1-069 C
Solar/Wind Harmer
3.321
20089126CSLMN_L13
Solar/Wind Harmer
1.352
20089026BF_G21_K23
Solar/Wind Harmer
1.07
20082926HNSMLK 2
Adder
8.333
20083126HNSMLK 4
Adder
8.333
944411AF1-106 GEN
Solar/Wind Harmer
0.306
971541AH1-268 GEN
Solar/Wind Harmer
4.602
965131AG1-378 GEN
Solar/Wind Harmer
2.555
970335AG2-220 GEN
Solar/Wind Harmer
3.853
971127AH1-005 GEN
Solar/Wind Harmer
2.486
20120126WRREN CT
Adder
7.621
202652Y1-033 WT C
Solar/Wind Harmer
1.085
203854AF2-039 C
Solar/Wind Harmer
0.455
20335126GROZ1-110
Adder
2.552
20335226CANZ2-011
Adder
2.481
970647AG2-420 GEN
Solar/Wind Harmer
2.163
971185AH1-051 GEN
Solar/Wind Harmer
2.617
971355AH1-158 GEN
Solar/Wind Harmer
3.044
203856AF2-165 C
Solar/Wind Harmer
1.275
203932AE1-123
Adder
2.053
238219AF1-167 C
Solar/Wind Harmer
1.404
959441AF2-235 GEN
Solar/Wind Harmer
0.313
238202AE2-262_GEN
Solar/Wind Harmer
2.582
971627AH1-313 GEN
Solar/Wind Harmer
10.123
960051AF2-296 GEN
Solar/Wind Harmer
2.013
20328326MANOR_T86
Adder
0.142
203948AG1-140 C
Solar/Wind Harmer
0.26
957161AF2-010 GEN
Solar/Wind Harmer
7.551
203830AF1-094 GEN
Solar/Wind Harmer
0.592
203962AF1-287 GEN
Solar/Wind Harmer
1.928
962511AG1-100 GEN
Solar/Wind Harmer
0.582
20084926LAKVU GN
Adder
0.164
941421AE2-139 GEN
Solar/Wind Harmer
2.84
945751AF1-240 GEN
Solar/Wind Harmer
1.47
203818AF1-086 GEN
Solar/Wind Harmer
2.371
972271AH1-720 GEN
Adder
6.081
200917MEHOOPANY_G
Solar/Wind Harmer
2.877
970899AG2-561 GEN
Solar/Wind Harmer
1.592
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.122
203843AF2-002_GEN
Solar/Wind Harmer
2.078
970631AG2-411 GEN
Solar/Wind Harmer
13.05
957561AF2-050 GEN
Solar/Wind Harmer
10.037
20088826HIGHLAND
Solar/Wind Harmer
3.191
971423AH1-203 GEN
Solar/Wind Harmer
13.025
964201AG1-281 GEN
Solar/Wind Harmer
1.074
970713AG2-456 GEN
Solar/Wind Harmer
13.014
971705AH1-358 GEN
Solar/Wind Harmer
3.783
971709AH1-360 GEN
Solar/Wind Harmer
3.783
20089226LOOKOUT
Solar/Wind Harmer
1.317
203987AE2-118 C
Solar/Wind Harmer
2.867
20082826HNSMLK 1
Adder
8.333
20083026HNSMLK 3
Adder
8.333
20335026MILZ1-092
Adder
3.092
944411AF1-106 GEN
Solar/Wind Harmer
2.848
20326126BLOSSBCT
Adder
3.104
971279AH1-102 GEN
Solar/Wind Harmer
10.813
964391AG1-301 GEN
Solar/Wind Harmer
0.8
20094526CT_V3-030
Solar/Wind Harmer
0.935
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.564
970511AG2-327 GEN
Solar/Wind Harmer
1.237
238183AE2-316 GEN
Solar/Wind Harmer
5.082
203954AE2-126 C
Solar/Wind Harmer
0.715
203860AG1-193 C
Solar/Wind Harmer
0.339
972169AH1-667 GEN
Solar/Wind Harmer
2.004
20091326SHAW-D
Adder
0.732
970647AG2-420 GEN
Solar/Wind Harmer
0.252
971183AH1-050 GEN
Solar/Wind Harmer
4.362
970267AG2-176 GEN
Solar/Wind Harmer
16.135
20072226SHAWVL 2
Adder
14.679
238206AE2-263_GEN
Solar/Wind Harmer
2.406
961971AG1-040 GEN
Solar/Wind Harmer
0.609
203835AF1-098 GEN
Solar/Wind Harmer
2.424
203813AE2-344_GEN
Solar/Wind Harmer
11.182
20084926LAKVU GN
Adder
0.164
238215AE2-248 C
Solar/Wind Harmer
1.496
970643AG2-418 GEN
Solar/Wind Harmer
0.522
20080926SITHE
50/50
0.751
203839AF1-321 GEN
Solar/Wind Harmer
4.155
20084626FORWARD
Solar/Wind Harmer
1.637
203857AF2-221 C
Solar/Wind Harmer
3.062
970123AG2-090 GEN
Solar/Wind Harmer
2.858
20088626ARWF_N39
Solar/Wind Harmer
3.564
20303426NA_O38_P22
Solar/Wind Harmer
2.886
20088926STNY CRK
Solar/Wind Harmer
2.291
971427AH1-205 GEN
Solar/Wind Harmer
2.767
203940AF1-140 C
Solar/Wind Harmer
0.921
20083426SW_E13_K22
Solar/Wind Harmer
0.546
971441AH1-212 GEN
Solar/Wind Harmer
3.496
972077AH1-588 GEN
Solar/Wind Harmer
39.042
972079AH1-589 GEN
Solar/Wind Harmer
32.156
970715AG2-457 GEN
Solar/Wind Harmer
13.014
944781AF1-143 GEN
Solar/Wind Harmer
4.635
972075AH1-587 GEN
Solar/Wind Harmer
30.314
20398826ARMNA MT
Solar/Wind Harmer
3.223
203952AE2-129 C
Solar/Wind Harmer
0.774
203946AE2-131 C
Solar/Wind Harmer
0.772
962411AG1-090 GEN
Solar/Wind Harmer
12.137
203859AF2-294 C
Solar/Wind Harmer
2.139
970313AG2-206 GEN
Solar/Wind Harmer
5.937
946381AF1-302 GEN
Solar/Wind Harmer
2.543
970305AG2-200 GEN
Solar/Wind Harmer
2.411
203955AF1-039 C O1
Solar/Wind Harmer
0.528
238217AF1-153 C O1
Solar/Wind Harmer
0.686
203848AF2-166 C
Solar/Wind Harmer
2.102
203980AG1-197 GEN
Solar/Wind Harmer
0.462
203853AF1-134 C O1
Solar/Wind Harmer
0.609
203963AG1-253 GEN
Solar/Wind Harmer
0.397
203979AG1-198 GEN
Solar/Wind Harmer
0.355
971933AH1-491 GEN
Solar/Wind Harmer
1.956
971931AH1-490 GEN
Solar/Wind Harmer
1.924
216419AE2-001 C
Solar/Wind Harmer
1.892
203947AF1-006 C
Solar/Wind Harmer
0.509
946071AF1-272 GEN
Solar/Wind Helper
1.512
203961AE2-224 GEN
Solar/Wind Harmer
6.08
20092526R32
Solar/Wind Harmer
3.419
203844AF2-092 C
Solar/Wind Harmer
2.294
203850AG1-041 C
Solar/Wind Harmer
2.283
20091526CHSTN_FL
Solar/Wind Harmer
1.482
940863AE2-074 GEN
Solar/Wind Harmer
2.816
203804AE2-113_GEN
Solar/Wind Harmer
7.027
20083226HNSMLK 5
Adder
8.333
20090526Q36
Solar/Wind Harmer
2.198
203993AD2-133_GEN1
Solar/Wind Harmer
2.198
941231AE2-117 GEN
Solar/Wind Harmer
0.808
970555AG2-356 GEN
Solar/Wind Harmer
2.564
965121AG1-377 GEN
Solar/Wind Harmer
2.555
970663AG2-429 GEN
Solar/Wind Harmer
7.896
970663AG2-429 GEN
Solar/Wind Harmer
1.285
203855AF2-088 C
Solar/Wind Harmer
0.219
203846AF2-130 C
Solar/Wind Harmer
0.601
970677AG2-438 GEN
Solar/Wind Harmer
0.978
966771AG1-548 GEN
Solar/Wind Harmer
14.232
966771AG1-548 GEN
Solar/Wind Harmer
2.758
20084926LAKVU GN
Adder
0.185
203926AA2-133 GEN
Adder
2.133
20334726NME_Y1-047
Adder
1.933
20390726Y2-042
Adder
1.579
961581Q1080_CY23
External Queue
23.09714698791504
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.176
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.548
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.687
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.154
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.792
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.262
G-007ALTFEXP_G-007A->PJM
CMTX
0.493
CBM NorthLTFEXP_CBM-N->PJM
CBM
29.912
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC
Facility Description:
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.25 %
Rating:809.0 MVA
Rating Type:A
MVA to Mitigate:811.02
MW Contribution:9.71
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.032
20079426CONEMAGH
50/50
2.219
203841AF2-001_GEN
Solar/Wind Harmer
2.872
971879AH1-460 GEN
Solar/Wind Harmer
9.383
970125AG2-091 GEN
Solar/Wind Harmer
0.846
971419AH1-201 GEN
Solar/Wind Harmer
5.18
20083726HOMER C1
50/50
231.295
20083926HOMER C3
50/50
187.4
20083826HOMER C2
50/50
177.021
20050326C.SLOPE
50/50
0.588
203961AE2-224 GEN
Solar/Wind Harmer
0.011
20092526R32
Solar/Wind Harmer
0.408
203844AF2-092 C
Solar/Wind Harmer
1.584
203850AG1-041 C
Solar/Wind Harmer
1.576
20091526CHSTN_FL
Solar/Wind Harmer
0.208
203804AE2-113_GEN
Solar/Wind Harmer
0.007
20090526Q36
Solar/Wind Harmer
0.485
203993AD2-133_GEN1
Solar/Wind Harmer
0.48
20083226HNSMLK 5
Adder
7.883
970555AG2-356 GEN
Solar/Wind Harmer
1.736
965121AG1-377 GEN
Solar/Wind Harmer
0.865
203855AF2-088 C
Solar/Wind Harmer
0
970663AG2-429 GEN
Solar/Wind Harmer
5.172
970663AG2-429 GEN
Solar/Wind Harmer
1.13
970677AG2-438 GEN
Solar/Wind Harmer
0.719
966771AG1-548 GEN
Solar/Wind Harmer
2.139
966771AG1-548 GEN
Solar/Wind Harmer
2.673
20084926LAKVU GN
Adder
0.176
203926AA2-133 GEN
Adder
2.065
20334726NME_Y1-047
Adder
1.87
20390726Y2-042
Adder
1.527
203843AF2-002_GEN
Solar/Wind Harmer
1.436
970631AG2-411 GEN
Solar/Wind Harmer
9.712
957561AF2-050 GEN
Solar/Wind Harmer
6.927
20088826HIGHLAND
Solar/Wind Harmer
0.001
971423AH1-203 GEN
Solar/Wind Harmer
9.001
970713AG2-456 GEN
Solar/Wind Harmer
10.222
971705AH1-358 GEN
Solar/Wind Harmer
3.664
971709AH1-360 GEN
Solar/Wind Harmer
3.664
20089226LOOKOUT
Solar/Wind Harmer
0.201
203987AE2-118 C
Solar/Wind Harmer
1.969
20082826HNSMLK 1
Adder
7.883
20083026HNSMLK 3
Adder
7.883
20335026MILZ1-092
Adder
3.003
944411AF1-106 GEN
Solar/Wind Harmer
3.064
20326126BLOSSBCT
Adder
3.012
971279AH1-102 GEN
Solar/Wind Harmer
9.604
20094526CT_V3-030
Solar/Wind Harmer
0.152
970337AG2-221 GEN
Solar/Wind Harmer
1.909
970511AG2-327 GEN
Solar/Wind Harmer
0.837
203954AE2-126 C
Solar/Wind Harmer
0.001
238183AE2-316 GEN
Solar/Wind Harmer
0.004
972169AH1-667 GEN
Solar/Wind Harmer
1.342
20091326SHAW-D
Adder
0.702
203860AG1-193 C
Solar/Wind Harmer
0.001
20072226SHAWVL 2
Adder
14.036
970267AG2-176 GEN
Solar/Wind Harmer
10.629
970647AG2-420 GEN
Solar/Wind Harmer
0.233
971183AH1-050 GEN
Solar/Wind Harmer
3.471
238206AE2-263_GEN
Solar/Wind Harmer
0.004
203835AF1-098 GEN
Solar/Wind Harmer
0.004
203813AE2-344_GEN
Solar/Wind Harmer
7.402
238215AE2-248 C
Solar/Wind Harmer
1.003
20084926LAKVU GN
Adder
0.157
970643AG2-418 GEN
Solar/Wind Harmer
0.507
971703AH1-357 GEN
Solar/Wind Harmer
2.198
971707AH1-359 GEN
Solar/Wind Harmer
2.198
20334926Z1-069 C
Solar/Wind Harmer
0.807
20089126CSLMN_L13
Solar/Wind Harmer
0.07
20089026BF_G21_K23
Solar/Wind Harmer
0.071
20082926HNSMLK 2
Adder
7.883
20083126HNSMLK 4
Adder
7.883
971541AH1-268 GEN
Solar/Wind Harmer
5.544
965131AG1-378 GEN
Solar/Wind Harmer
0.865
970335AG2-220 GEN
Solar/Wind Harmer
2.693
971127AH1-005 GEN
Solar/Wind Harmer
1.964
20120126WRREN CT
Adder
7.308
202652Y1-033 WT C
Solar/Wind Harmer
0.001
203854AF2-039 C
Solar/Wind Harmer
0.001
20335126GROZ1-110
Adder
2.469
20335226CANZ2-011
Adder
2.399
970647AG2-420 GEN
Solar/Wind Harmer
1.398
971185AH1-051 GEN
Solar/Wind Harmer
2.082
971355AH1-158 GEN
Solar/Wind Harmer
3.471
238202AE2-262_GEN
Solar/Wind Harmer
0.004
971627AH1-313 GEN
Solar/Wind Harmer
6.761
20328326MANOR_T86
Adder
0.138
960051AF2-296 GEN
Solar/Wind Harmer
1.349
203948AG1-140 C
Solar/Wind Harmer
0.187
203932AE1-123
Adder
1.861
957161AF2-010 GEN
Solar/Wind Harmer
4.943
238219AF1-167 C
Solar/Wind Harmer
0.869
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203962AF1-287 GEN
Solar/Wind Harmer
1.276
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
5.882
20084926LAKVU GN
Adder
0.157
203818AF1-086 GEN
Solar/Wind Harmer
0.535
972323AH1-746 GEN
Solar/Wind Harmer
2.072
945751AF1-240 GEN
Solar/Wind Harmer
1.105
200917MEHOOPANY_G
Solar/Wind Harmer
0.28
970899AG2-561 GEN
Solar/Wind Harmer
1.064
970679AG2-439 GEN
Solar/Wind Harmer
0.401
970643AG2-418 GEN
Solar/Wind Harmer
0.761
20080926SITHE
50/50
0.744
203839AF1-321 GEN
Solar/Wind Harmer
2.872
20084626FORWARD
Solar/Wind Harmer
0
203857AF2-221 C
Solar/Wind Harmer
1.481
970123AG2-090 GEN
Solar/Wind Harmer
1.975
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.002
20088926STNY CRK
Solar/Wind Harmer
0.25
971427AH1-205 GEN
Solar/Wind Harmer
3.453
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
2.409
972077AH1-588 GEN
Solar/Wind Harmer
26.379
972079AH1-589 GEN
Solar/Wind Harmer
31.142
970715AG2-457 GEN
Solar/Wind Harmer
10.222
944781AF1-143 GEN
Solar/Wind Harmer
-0.001
972075AH1-587 GEN
Solar/Wind Harmer
20.422
20398826ARMNA MT
Solar/Wind Harmer
0.053
203952AE2-129 C
Solar/Wind Harmer
0.001
962411AG1-090 GEN
Solar/Wind Harmer
4.323
203859AF2-294 C
Solar/Wind Harmer
1.449
970313AG2-206 GEN
Solar/Wind Harmer
4.019
970305AG2-200 GEN
Solar/Wind Harmer
1.613
203955AF1-039 C O1
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203848AF2-166 C
Solar/Wind Harmer
1.342
203963AG1-253 GEN
Solar/Wind Harmer
0.297
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.287
971931AH1-490 GEN
Solar/Wind Harmer
1.273
216419AE2-001 C
Solar/Wind Harmer
1.268
203947AF1-006 C
Solar/Wind Harmer
0.041
946071AF1-272 GEN
Solar/Wind Helper
1.546
961581Q1080_CY23
External Queue
22.834562301635742
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.162
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.503
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.427
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.145
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.728
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.248
G-007ALTFEXP_G-007A->PJM
CMTX
0.401
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.959
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-DRT27_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-DRT27_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:759.23
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-004-DRT-003_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.81 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:759.23
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-DRT26_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-DRT26_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.75 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:758.81
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-004-DRT-004_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-004_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.75 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:758.8
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-2_PN-500-004A-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-2_PN-500-004A-DRT_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.01 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:715.77
MW Contribution:10.3
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
161.556
20215826CON.GEN1
50/50
0.028
20080526COLVER13
50/50
1.087
203843AF2-002_GEN
Solar/Wind Harmer
1.642
970631AG2-411 GEN
Solar/Wind Harmer
10.3
20088826HIGHLAND
Solar/Wind Harmer
2.567
971279AH1-102 GEN
Solar/Wind Harmer
12.766
957561AF2-050 GEN
Solar/Wind Harmer
7.496
20094526CT_V3-030
Solar/Wind Harmer
1.056
971423AH1-203 GEN
Solar/Wind Harmer
10.375
964201AG1-281 GEN
Solar/Wind Harmer
0.864
20089226LOOKOUT
Solar/Wind Harmer
1.049
970713AG2-456 GEN
Solar/Wind Harmer
9.421
971705AH1-358 GEN
Solar/Wind Harmer
2.739
971709AH1-360 GEN
Solar/Wind Harmer
2.739
203987AE2-118 C
Solar/Wind Harmer
2.243
964391AG1-301 GEN
Solar/Wind Harmer
0.625
20082826HNSMLK 1
Adder
5.966
20083026HNSMLK 3
Adder
5.966
20326126BLOSSBCT
Adder
2.23
20091326SHAW-D
Adder
0.639
972169AH1-667 GEN
Solar/Wind Harmer
1.749
203954AE2-126 C
Solar/Wind Harmer
0.588
20335026MILZ1-092
Adder
2.205
944411AF1-106 GEN
Solar/Wind Harmer
2.032
959471AF2-238 GEN
Solar/Wind Harmer
0.556
970337AG2-221 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
3.669
238183AE2-316 GEN
Solar/Wind Harmer
3.802
970647AG2-420 GEN
Solar/Wind Harmer
0.208
20083326SEWRDB34
50/50
5.324
20079426CONEMAGH
50/50
2.015
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.284
971879AH1-460 GEN
Solar/Wind Harmer
10.772
970125AG2-091 GEN
Solar/Wind Harmer
0.975
971541AH1-268 GEN
Solar/Wind Harmer
5.433
970899AG2-561 GEN
Solar/Wind Harmer
3.104
971419AH1-201 GEN
Solar/Wind Harmer
4.744
203818AF1-086 GEN
Solar/Wind Harmer
3.548
20089126CSLMN_L13
Solar/Wind Harmer
1.077
20089026BF_G21_K23
Solar/Wind Harmer
0.853
945751AF1-240 GEN
Solar/Wind Harmer
1.918
960051AF2-296 GEN
Solar/Wind Harmer
2.42
971703AH1-357 GEN
Solar/Wind Harmer
2.355
971707AH1-359 GEN
Solar/Wind Harmer
2.355
20334926Z1-069 C
Solar/Wind Harmer
2.383
965131AG1-378 GEN
Solar/Wind Harmer
2.169
20082926HNSMLK 2
Adder
5.966
20083126HNSMLK 4
Adder
5.966
203854AF2-039 C
Solar/Wind Harmer
0.397
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.888
202652Y1-033 WT C
Solar/Wind Harmer
0.869
971185AH1-051 GEN
Solar/Wind Harmer
2.202
971355AH1-158 GEN
Solar/Wind Harmer
2.56
20120126WRREN CT
Adder
5.678
203856AF2-165 C
Solar/Wind Harmer
1.068
970647AG2-420 GEN
Solar/Wind Harmer
1.789
970335AG2-220 GEN
Solar/Wind Harmer
2.757
971127AH1-005 GEN
Solar/Wind Harmer
1.779
959441AF2-235 GEN
Solar/Wind Harmer
0.257
238219AF1-167 C
Solar/Wind Harmer
1.122
238202AE2-262_GEN
Solar/Wind Harmer
2.071
971627AH1-313 GEN
Solar/Wind Harmer
8.119
20335126GROZ1-110
Adder
1.864
20335226CANZ2-011
Adder
1.812
957161AF2-010 GEN
Solar/Wind Harmer
5.877
203830AF1-094 GEN
Solar/Wind Harmer
0.46
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.44
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.434
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.069
972271AH1-720 GEN
Adder
4.404
200917MEHOOPANY_G
Solar/Wind Harmer
2.057
970679AG2-439 GEN
Solar/Wind Harmer
0.469
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.462
20083826HOMER C2
50/50
126.07
20092526R32
Solar/Wind Harmer
2.751
203844AF2-092 C
Solar/Wind Harmer
1.843
203850AG1-041 C
Solar/Wind Harmer
1.837
203961AE2-224 GEN
Solar/Wind Harmer
4.541
20091526CHSTN_FL
Solar/Wind Harmer
1.215
20090526Q36
Solar/Wind Harmer
1.835
203993AD2-133_GEN1
Solar/Wind Harmer
1.835
940863AE2-074 GEN
Solar/Wind Harmer
2.03
203804AE2-113_GEN
Solar/Wind Harmer
5.24
965121AG1-377 GEN
Solar/Wind Harmer
2.169
941231AE2-117 GEN
Solar/Wind Harmer
0.635
20083226HNSMLK 5
Adder
5.966
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.53
970555AG2-356 GEN
Solar/Wind Harmer
1.838
970663AG2-429 GEN
Solar/Wind Harmer
6.046
970663AG2-429 GEN
Solar/Wind Harmer
0.984
970677AG2-438 GEN
Solar/Wind Harmer
0.759
966771AG1-548 GEN
Solar/Wind Harmer
10.997
966771AG1-548 GEN
Solar/Wind Harmer
2.131
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.532
20334726NME_Y1-047
Adder
1.382
971321AH1-140 GEN
Solar/Wind Harmer
8.457
971321AH1-140 GEN
Solar/Wind Harmer
1.639
20390726Y2-042
Adder
1.122
970511AG2-327 GEN
Solar/Wind Harmer
0.885
20072226SHAWVL 2
Adder
12.056
203860AG1-193 C
Solar/Wind Harmer
0.266
238206AE2-263_GEN
Solar/Wind Harmer
1.93
970267AG2-176 GEN
Solar/Wind Harmer
12.084
961971AG1-040 GEN
Solar/Wind Harmer
0.456
238215AE2-248 C
Solar/Wind Harmer
1.193
203835AF1-098 GEN
Solar/Wind Harmer
1.806
203813AE2-344_GEN
Solar/Wind Harmer
8.348
20084926LAKVU GN
Adder
0.122
20080926SITHE
50/50
0.52
946071AF1-272 GEN
Solar/Wind Harmer
6.958
203839AF1-321 GEN
Solar/Wind Harmer
3.284
20084626FORWARD
Solar/Wind Harmer
1.292
203857AF2-221 C
Solar/Wind Harmer
2.437
970123AG2-090 GEN
Solar/Wind Harmer
2.275
203940AF1-140 C
Solar/Wind Harmer
0.747
20088926STNY CRK
Solar/Wind Harmer
1.827
971441AH1-212 GEN
Solar/Wind Harmer
2.99
971427AH1-205 GEN
Solar/Wind Harmer
2.207
20083426SW_E13_K22
Solar/Wind Harmer
0.434
20088626ARWF_N39
Solar/Wind Harmer
2.671
20303426NA_O38_P22
Solar/Wind Harmer
2.162
944781AF1-143 GEN
Solar/Wind Harmer
3.692
203853AF1-134 C O1
Solar/Wind Harmer
0.732
972077AH1-588 GEN
Solar/Wind Harmer
28.263
972079AH1-589 GEN
Solar/Wind Harmer
23.279
970715AG2-457 GEN
Solar/Wind Harmer
9.421
972075AH1-587 GEN
Solar/Wind Harmer
22.395
203952AE2-129 C
Solar/Wind Harmer
0.657
203946AE2-131 C
Solar/Wind Harmer
0.656
962411AG1-090 GEN
Solar/Wind Harmer
10.305
20398826ARMNA MT
Solar/Wind Harmer
2.3
203955AF1-039 C O1
Solar/Wind Harmer
0.423
203848AF2-166 C
Solar/Wind Harmer
1.855
946381AF1-302 GEN
Solar/Wind Harmer
1.902
970305AG2-200 GEN
Solar/Wind Harmer
1.796
203859AF2-294 C
Solar/Wind Harmer
1.523
238217AF1-153 C O1
Solar/Wind Harmer
0.541
970313AG2-206 GEN
Solar/Wind Harmer
4.249
203980AG1-197 GEN
Solar/Wind Harmer
0.346
203979AG1-198 GEN
Solar/Wind Harmer
0.276
971933AH1-491 GEN
Solar/Wind Harmer
1.518
216419AE2-001 C
Solar/Wind Harmer
1.511
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.436
203947AF1-006 C
Solar/Wind Harmer
0.379
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.098
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.376
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.173
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.51
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line l/o PN_P2-3_PN-500-DRT33_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line
Contingency Name:
PN_P2-3_PN-500-DRT33_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.27 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:711.02
MW Contribution:9.71
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
153.413
20215826CON.GEN1
50/50
0.027
20063626IUP CO-G
50/50
0.154
20083926HOMER C3
50/50
126.285
20083826HOMER C2
50/50
119.291
20092526R32
Solar/Wind Harmer
2.579
203844AF2-092 C
Solar/Wind Harmer
1.732
203850AG1-041 C
Solar/Wind Harmer
1.726
203961AE2-224 GEN
Solar/Wind Harmer
4.218
20091526CHSTN_FL
Solar/Wind Harmer
1.131
20090526Q36
Solar/Wind Harmer
1.697
203993AD2-133_GEN1
Solar/Wind Harmer
1.697
940863AE2-074 GEN
Solar/Wind Harmer
1.893
203804AE2-113_GEN
Solar/Wind Harmer
4.875
965121AG1-377 GEN
Solar/Wind Harmer
2
20083226HNSMLK 5
Adder
5.623
941231AE2-117 GEN
Solar/Wind Harmer
0.579
203855AF2-088 C
Solar/Wind Harmer
0.176
203846AF2-130 C
Solar/Wind Harmer
0.494
970555AG2-356 GEN
Solar/Wind Harmer
1.677
970663AG2-429 GEN
Solar/Wind Harmer
5.593
970663AG2-429 GEN
Solar/Wind Harmer
0.911
970677AG2-438 GEN
Solar/Wind Harmer
0.713
966771AG1-548 GEN
Solar/Wind Harmer
10.331
966771AG1-548 GEN
Solar/Wind Harmer
2.002
20084926LAKVU GN
Adder
0.129
971321AH1-140 GEN
Solar/Wind Harmer
9.071
971321AH1-140 GEN
Solar/Wind Harmer
1.758
203926AA2-133 GEN
Adder
1.344
20334726NME_Y1-047
Adder
1.195
20216026CON.GEN2
50/50
0.019
20083326SEWRDB34
50/50
4.935
20079426CONEMAGH
50/50
1.887
203841AF2-001_GEN
Solar/Wind Harmer
3.098
971879AH1-460 GEN
Solar/Wind Harmer
10.144
970125AG2-091 GEN
Solar/Wind Harmer
0.917
971541AH1-268 GEN
Solar/Wind Harmer
5.102
970899AG2-561 GEN
Solar/Wind Harmer
2.926
971419AH1-201 GEN
Solar/Wind Harmer
4.481
203818AF1-086 GEN
Solar/Wind Harmer
3.327
20089126CSLMN_L13
Solar/Wind Harmer
1.031
20089026BF_G21_K23
Solar/Wind Harmer
0.816
945751AF1-240 GEN
Solar/Wind Harmer
1.798
960051AF2-296 GEN
Solar/Wind Harmer
2.253
971703AH1-357 GEN
Solar/Wind Harmer
2.204
971707AH1-359 GEN
Solar/Wind Harmer
2.204
20334926Z1-069 C
Solar/Wind Harmer
2.216
965131AG1-378 GEN
Solar/Wind Harmer
2
20082926HNSMLK 2
Adder
5.623
20083126HNSMLK 4
Adder
5.623
202652Y1-033 WT C
Solar/Wind Harmer
0.847
203854AF2-039 C
Solar/Wind Harmer
0.365
203932AE1-123
Adder
1.757
944411AF1-106 GEN
Solar/Wind Harmer
0.2
971185AH1-051 GEN
Solar/Wind Harmer
2.058
971355AH1-158 GEN
Solar/Wind Harmer
2.393
20120126WRREN CT
Adder
5.302
203856AF2-165 C
Solar/Wind Harmer
0.999
970647AG2-420 GEN
Solar/Wind Harmer
1.674
970335AG2-220 GEN
Solar/Wind Harmer
2.507
971127AH1-005 GEN
Solar/Wind Harmer
1.617
959441AF2-235 GEN
Solar/Wind Harmer
0.241
238219AF1-167 C
Solar/Wind Harmer
1.034
238202AE2-262_GEN
Solar/Wind Harmer
1.87
971627AH1-313 GEN
Solar/Wind Harmer
7.332
957161AF2-010 GEN
Solar/Wind Harmer
5.518
20335126GROZ1-110
Adder
1.677
20335226CANZ2-011
Adder
1.63
203830AF1-094 GEN
Solar/Wind Harmer
0.432
203948AG1-140 C
Solar/Wind Harmer
0.181
203962AF1-287 GEN
Solar/Wind Harmer
1.356
962511AG1-100 GEN
Solar/Wind Harmer
0.409
20084926LAKVU GN
Adder
0.115
20328326MANOR_T86
Adder
0.091
941421AE2-139 GEN
Solar/Wind Harmer
1.826
972271AH1-720 GEN
Adder
3.879
200917MEHOOPANY_G
Solar/Wind Harmer
1.778
20080526COLVER13
50/50
1.024
203843AF2-002_GEN
Solar/Wind Harmer
1.549
970631AG2-411 GEN
Solar/Wind Harmer
9.713
20088826HIGHLAND
Solar/Wind Harmer
2.407
971279AH1-102 GEN
Solar/Wind Harmer
11.989
971423AH1-203 GEN
Solar/Wind Harmer
9.809
957561AF2-050 GEN
Solar/Wind Harmer
6.963
20094526CT_V3-030
Solar/Wind Harmer
0.99
964201AG1-281 GEN
Solar/Wind Harmer
0.806
20089226LOOKOUT
Solar/Wind Harmer
1.004
970713AG2-456 GEN
Solar/Wind Harmer
8.817
971705AH1-358 GEN
Solar/Wind Harmer
2.563
971709AH1-360 GEN
Solar/Wind Harmer
2.563
203987AE2-118 C
Solar/Wind Harmer
2.054
20082826HNSMLK 1
Adder
5.623
20083026HNSMLK 3
Adder
5.623
964391AG1-301 GEN
Solar/Wind Harmer
0.569
203954AE2-126 C
Solar/Wind Harmer
0.541
20326126BLOSSBCT
Adder
2.045
20091326SHAW-D
Adder
0.586
972169AH1-667 GEN
Solar/Wind Harmer
1.605
20335026MILZ1-092
Adder
2.022
944411AF1-106 GEN
Solar/Wind Harmer
1.863
971183AH1-050 GEN
Solar/Wind Harmer
3.43
959471AF2-238 GEN
Solar/Wind Harmer
0.507
970337AG2-221 GEN
Solar/Wind Harmer
1.677
970647AG2-420 GEN
Solar/Wind Harmer
0.195
238183AE2-316 GEN
Solar/Wind Harmer
3.509
203860AG1-193 C
Solar/Wind Harmer
0.249
970511AG2-327 GEN
Solar/Wind Harmer
0.804
20072226SHAWVL 2
Adder
10.985
970267AG2-176 GEN
Solar/Wind Harmer
11.379
238206AE2-263_GEN
Solar/Wind Harmer
1.743
961971AG1-040 GEN
Solar/Wind Harmer
0.429
203835AF1-098 GEN
Solar/Wind Harmer
1.697
203813AE2-344_GEN
Solar/Wind Harmer
7.866
238215AE2-248 C
Solar/Wind Harmer
1.065
20084926LAKVU GN
Adder
0.115
20080926SITHE
50/50
0.493
946071AF1-272 GEN
Solar/Wind Harmer
6.65
203839AF1-321 GEN
Solar/Wind Harmer
3.098
20084626FORWARD
Solar/Wind Harmer
1.219
203857AF2-221 C
Solar/Wind Harmer
2.292
970123AG2-090 GEN
Solar/Wind Harmer
2.139
203940AF1-140 C
Solar/Wind Harmer
0.7
20088926STNY CRK
Solar/Wind Harmer
1.725
971427AH1-205 GEN
Solar/Wind Harmer
2.084
971441AH1-212 GEN
Solar/Wind Harmer
2.794
20083426SW_E13_K22
Solar/Wind Harmer
0.411
20088626ARWF_N39
Solar/Wind Harmer
2.475
20303426NA_O38_P22
Solar/Wind Harmer
2.004
944781AF1-143 GEN
Solar/Wind Harmer
3.533
203853AF1-134 C O1
Solar/Wind Harmer
0.681
972077AH1-588 GEN
Solar/Wind Harmer
26.452
972079AH1-589 GEN
Solar/Wind Harmer
21.787
970715AG2-457 GEN
Solar/Wind Harmer
8.817
972075AH1-587 GEN
Solar/Wind Harmer
20.869
203952AE2-129 C
Solar/Wind Harmer
0.606
203946AE2-131 C
Solar/Wind Harmer
0.605
962411AG1-090 GEN
Solar/Wind Harmer
9.501
203955AF1-039 C O1
Solar/Wind Harmer
0.412
20398826ARMNA MT
Solar/Wind Harmer
2.11
203848AF2-166 C
Solar/Wind Harmer
1.73
970305AG2-200 GEN
Solar/Wind Harmer
1.677
946381AF1-302 GEN
Solar/Wind Harmer
1.756
238217AF1-153 C O1
Solar/Wind Harmer
0.496
203859AF2-294 C
Solar/Wind Harmer
1.387
970313AG2-206 GEN
Solar/Wind Harmer
3.861
203980AG1-197 GEN
Solar/Wind Harmer
0.326
203979AG1-198 GEN
Solar/Wind Harmer
0.259
971933AH1-491 GEN
Solar/Wind Harmer
1.425
203963AG1-253 GEN
Solar/Wind Harmer
0.276
971931AH1-490 GEN
Solar/Wind Harmer
1.353
216419AE2-001 C
Solar/Wind Harmer
1.35
203947AF1-006 C
Solar/Wind Harmer
0.357
LAGNLTFEXP_LAGN->PJM
CLTF
0.299
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
TVALTFEXP_TVA->PJM
CLTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.569
MECLTFEXP_MEC->PJM
CLTF
0.336
SIGELTFEXP_SIGE->PJM
CLTF
0.01
LGEELTFEXP_LGEE->PJM
CLTF
0.128
WECLTFEXP_WEC->PJM
CLTF
0.083
CPLELTFEXP_CPLE->PJM
CLTF
0.023
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.276
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.284

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-A_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.72 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:968.54
MW Contribution:5.2
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.551
238202AE2-262_GEN
Solar/Wind Harmer
6.642
971627AH1-313 GEN
Solar/Wind Harmer
26.043
203854AF2-039 C
Solar/Wind Harmer
0.84
965131AG1-378 GEN
Solar/Wind Harmer
3.897
960051AF2-296 GEN
Solar/Wind Harmer
3.17
203818AF1-086 GEN
Solar/Wind Harmer
3.162
20120126WRREN CT
Adder
6.343
971703AH1-357 GEN
Solar/Wind Harmer
1.992
971707AH1-359 GEN
Solar/Wind Harmer
1.992
970899AG2-561 GEN
Solar/Wind Harmer
1.806
20335126GROZ1-110
Adder
2.098
20335226CANZ2-011
Adder
2.04
20334926Z1-069 C
Solar/Wind Harmer
1.817
970125AG2-091 GEN
Solar/Wind Harmer
0.515
971419AH1-201 GEN
Solar/Wind Harmer
2.682
971541AH1-268 GEN
Solar/Wind Harmer
2.916
971879AH1-460 GEN
Solar/Wind Harmer
5.499
945751AF1-240 GEN
Solar/Wind Harmer
1.26
203841AF2-001_GEN
Solar/Wind Harmer
1.597
20079426CONEMAGH
Adder
0.952
941421AE2-139 GEN
Solar/Wind Harmer
2.261
203932AE1-123
Adder
1.419
238219AF1-167 C
Solar/Wind Harmer
0.957
970335AG2-220 GEN
Solar/Wind Harmer
2.16
971127AH1-005 GEN
Solar/Wind Harmer
1.394
944411AF1-106 GEN
Solar/Wind Harmer
0.157
972271AH1-720 GEN
Adder
4.391
971185AH1-051 GEN
Solar/Wind Harmer
1.605
971355AH1-158 GEN
Solar/Wind Harmer
1.866
203856AF2-165 C
Solar/Wind Harmer
0.786
959441AF2-235 GEN
Solar/Wind Harmer
0.197
970647AG2-420 GEN
Solar/Wind Harmer
1.3
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.563
20089026BF_G21_K23
Solar/Wind Harmer
0.446
957161AF2-010 GEN
Solar/Wind Harmer
4.846
203830AF1-094 GEN
Solar/Wind Harmer
0.381
203948AG1-140 C
Solar/Wind Harmer
0.164
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.458
20083126HNSMLK 4
Adder
3.458
203962AF1-287 GEN
Solar/Wind Harmer
1.168
962511AG1-100 GEN
Solar/Wind Harmer
0.348
202652Y1-033 WT C
Solar/Wind Harmer
0.468
200917MEHOOPANY_G
Solar/Wind Harmer
1.647
200642SENECA#1
50/50
1.72
203975AE1-071-GEN
Solar/Wind Harmer
13.301
941231AE2-117 GEN
Solar/Wind Harmer
1.738
203855AF2-088 C
Solar/Wind Harmer
0.404
965121AG1-377 GEN
Solar/Wind Harmer
3.897
20090526Q36
Solar/Wind Harmer
2.895
203993AD2-133_GEN1
Solar/Wind Harmer
2.895
203961AE2-224 GEN
Solar/Wind Harmer
4.729
20091526CHSTN_FL
Solar/Wind Harmer
1.356
203804AE2-113_GEN
Solar/Wind Harmer
6.224
203850AG1-041 C
Solar/Wind Harmer
1.233
203844AF2-092 C
Solar/Wind Harmer
1.201
20092526R32
Solar/Wind Harmer
1.725
940863AE2-074 GEN
Solar/Wind Harmer
1.638
970555AG2-356 GEN
Solar/Wind Harmer
1.499
203846AF2-130 C
Solar/Wind Harmer
0.396
970663AG2-429 GEN
Solar/Wind Harmer
4.749
970663AG2-429 GEN
Solar/Wind Harmer
0.773
20083926HOMER C3
Adder
48.654
20083826HOMER C2
Adder
45.959
20083726HOMER C1
Adder
45.378
970677AG2-438 GEN
Solar/Wind Harmer
0.628
966771AG1-548 GEN
Solar/Wind Harmer
9.155
966771AG1-548 GEN
Solar/Wind Harmer
1.774
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.458
203926AA2-133 GEN
Adder
1.313
20334726NME_Y1-047
Adder
1.107
20072226SHAWVL 2
50/50
32.684
20091326SHAW-D
50/50
1.433
20064926PENNTECH
50/50
0.443
200643SENECA#2
50/50
1.604
970643AG2-418 GEN
Solar/Wind Harmer
4.443
238215AE2-248 C
Solar/Wind Harmer
5.151
964391AG1-301 GEN
Solar/Wind Harmer
1.797
203987AE2-118 C
Solar/Wind Harmer
5.347
238206AE2-263_GEN
Solar/Wind Harmer
6.191
972169AH1-667 GEN
Solar/Wind Harmer
3.697
203954AE2-126 C
Solar/Wind Harmer
1.11
957561AF2-050 GEN
Solar/Wind Harmer
7.807
964201AG1-281 GEN
Solar/Wind Harmer
0.898
238183AE2-316 GEN
Solar/Wind Harmer
5.501
20094526CT_V3-030
Solar/Wind Harmer
0.812
970713AG2-456 GEN
Solar/Wind Harmer
7.967
971705AH1-358 GEN
Solar/Wind Harmer
2.316
971709AH1-360 GEN
Solar/Wind Harmer
2.316
20088826HIGHLAND
Solar/Wind Harmer
1.61
971279AH1-102 GEN
Solar/Wind Harmer
6.852
970631AG2-411 GEN
Solar/Wind Harmer
5.204
971423AH1-203 GEN
Solar/Wind Harmer
5.698
20326126BLOSSBCT
Adder
1.863
203843AF2-002_GEN
Solar/Wind Harmer
0.799
959471AF2-238 GEN
Solar/Wind Harmer
0.453
970337AG2-221 GEN
Solar/Wind Harmer
1.499
970511AG2-327 GEN
Solar/Wind Harmer
0.696
20335026MILZ1-092
Adder
1.584
944411AF1-106 GEN
Solar/Wind Harmer
1.459
203835AF1-098 GEN
Solar/Wind Harmer
1.684
971183AH1-050 GEN
Solar/Wind Harmer
2.674
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.548
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.458
20083026HNSMLK 3
Adder
3.458
203813AE2-344_GEN
Solar/Wind Harmer
6.77
970267AG2-176 GEN
Solar/Wind Harmer
8.701
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.084
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.491
20066526SHAWVL 3
50/50
2.472
20071526SHAWVL 1
50/50
1.675
216419AE2-001 C
Solar/Wind Harmer
6.264
203952AE2-129 C
Solar/Wind Harmer
1.18
203946AE2-131 C
Solar/Wind Harmer
1.178
962411AG1-090 GEN
Solar/Wind Harmer
18.509
20088626ARWF_N39
Solar/Wind Harmer
3.372
20303426NA_O38_P22
Solar/Wind Harmer
2.73
238217AF1-153 C O1
Solar/Wind Harmer
1.027
203853AF1-134 C O1
Solar/Wind Harmer
0.958
946381AF1-302 GEN
Solar/Wind Harmer
2.753
972075AH1-587 GEN
Solar/Wind Harmer
24.236
971441AH1-212 GEN
Solar/Wind Harmer
2.406
203940AF1-140 C
Solar/Wind Harmer
0.558
970305AG2-200 GEN
Solar/Wind Harmer
2.006
972077AH1-588 GEN
Solar/Wind Harmer
23.902
972079AH1-589 GEN
Solar/Wind Harmer
19.687
970715AG2-457 GEN
Solar/Wind Harmer
7.967
203857AF2-221 C
Solar/Wind Harmer
1.289
970123AG2-090 GEN
Solar/Wind Harmer
1.203
20088926STNY CRK
Solar/Wind Harmer
1.036
971427AH1-205 GEN
Solar/Wind Harmer
1.247
20084626FORWARD
Solar/Wind Harmer
0.653
203839AF1-321 GEN
Solar/Wind Harmer
1.597
20083426SW_E13_K22
Solar/Wind Harmer
0.223
20398826ARMNA MT
Solar/Wind Harmer
1.678
970313AG2-206 GEN
Solar/Wind Harmer
3.34
946071AF1-272 GEN
Solar/Wind Harmer
2.309
203848AF2-166 C
Solar/Wind Harmer
1.385
944781AF1-143 GEN
Solar/Wind Harmer
1.93
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.256
203963AG1-253 GEN
Solar/Wind Harmer
0.251
203859AF2-294 C
Solar/Wind Harmer
1.047
203947AF1-006 C
Solar/Wind Harmer
0.325
203980AG1-197 GEN
Solar/Wind Harmer
0.262
971931AH1-490 GEN
Solar/Wind Harmer
1.15
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.407
LAGNLTFEXP_LAGN->PJM
CLTF
1.332
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.995
TVALTFEXP_TVA->PJM
CLTF
0.652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.591
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.561
MECLTFEXP_MEC->PJM
CLTF
1.38
SIGELTFEXP_SIGE->PJM
CLTF
0.043
LGEELTFEXP_LGEE->PJM
CLTF
0.561
WECLTFEXP_WEC->PJM
CLTF
0.331
CPLELTFEXP_CPLE->PJM
CLTF
0.213
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.847
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.861

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-B_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.7 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:968.43
MW Contribution:5.21
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.555
238202AE2-262_GEN
Solar/Wind Harmer
6.645
971627AH1-313 GEN
Solar/Wind Harmer
26.055
203854AF2-039 C
Solar/Wind Harmer
0.84
965131AG1-378 GEN
Solar/Wind Harmer
3.899
960051AF2-296 GEN
Solar/Wind Harmer
3.172
203818AF1-086 GEN
Solar/Wind Harmer
3.164
20120126WRREN CT
Adder
6.346
971703AH1-357 GEN
Solar/Wind Harmer
1.993
971707AH1-359 GEN
Solar/Wind Harmer
1.993
970899AG2-561 GEN
Solar/Wind Harmer
1.807
20335126GROZ1-110
Adder
2.101
20335226CANZ2-011
Adder
2.042
20334926Z1-069 C
Solar/Wind Harmer
1.818
970125AG2-091 GEN
Solar/Wind Harmer
0.516
971419AH1-201 GEN
Solar/Wind Harmer
2.683
971541AH1-268 GEN
Solar/Wind Harmer
2.918
971879AH1-460 GEN
Solar/Wind Harmer
5.502
945751AF1-240 GEN
Solar/Wind Harmer
1.261
203841AF2-001_GEN
Solar/Wind Harmer
1.598
20079426CONEMAGH
Adder
0.952
941421AE2-139 GEN
Solar/Wind Harmer
2.265
203932AE1-123
Adder
1.42
238219AF1-167 C
Solar/Wind Harmer
0.957
970335AG2-220 GEN
Solar/Wind Harmer
2.164
971127AH1-005 GEN
Solar/Wind Harmer
1.396
944411AF1-106 GEN
Solar/Wind Harmer
0.157
972271AH1-720 GEN
Adder
4.399
971185AH1-051 GEN
Solar/Wind Harmer
1.605
971355AH1-158 GEN
Solar/Wind Harmer
1.867
203856AF2-165 C
Solar/Wind Harmer
0.786
959441AF2-235 GEN
Solar/Wind Harmer
0.197
970647AG2-420 GEN
Solar/Wind Harmer
1.3
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.563
20089026BF_G21_K23
Solar/Wind Harmer
0.446
957161AF2-010 GEN
Solar/Wind Harmer
4.848
203830AF1-094 GEN
Solar/Wind Harmer
0.381
203948AG1-140 C
Solar/Wind Harmer
0.164
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.459
20083126HNSMLK 4
Adder
3.459
203962AF1-287 GEN
Solar/Wind Harmer
1.168
962511AG1-100 GEN
Solar/Wind Harmer
0.348
202652Y1-033 WT C
Solar/Wind Harmer
0.468
200917MEHOOPANY_G
Solar/Wind Harmer
1.652
200642SENECA#1
50/50
1.721
203975AE1-071-GEN
Solar/Wind Harmer
13.306
941231AE2-117 GEN
Solar/Wind Harmer
1.739
203855AF2-088 C
Solar/Wind Harmer
0.405
965121AG1-377 GEN
Solar/Wind Harmer
3.899
20090526Q36
Solar/Wind Harmer
2.897
203993AD2-133_GEN1
Solar/Wind Harmer
2.897
203961AE2-224 GEN
Solar/Wind Harmer
4.732
20091526CHSTN_FL
Solar/Wind Harmer
1.357
203804AE2-113_GEN
Solar/Wind Harmer
6.227
203850AG1-041 C
Solar/Wind Harmer
1.234
203844AF2-092 C
Solar/Wind Harmer
1.201
20092526R32
Solar/Wind Harmer
1.726
940863AE2-074 GEN
Solar/Wind Harmer
1.639
970555AG2-356 GEN
Solar/Wind Harmer
1.501
203846AF2-130 C
Solar/Wind Harmer
0.396
970663AG2-429 GEN
Solar/Wind Harmer
4.752
970663AG2-429 GEN
Solar/Wind Harmer
0.774
20083926HOMER C3
Adder
48.691
20083826HOMER C2
Adder
45.994
20083726HOMER C1
Adder
45.416
970677AG2-438 GEN
Solar/Wind Harmer
0.628
966771AG1-548 GEN
Solar/Wind Harmer
9.158
966771AG1-548 GEN
Solar/Wind Harmer
1.775
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.459
203926AA2-133 GEN
Adder
1.316
20334726NME_Y1-047
Adder
1.11
20072226SHAWVL 2
50/50
32.7
20091326SHAW-D
50/50
1.433
20064926PENNTECH
50/50
0.444
200643SENECA#2
50/50
1.605
970643AG2-418 GEN
Solar/Wind Harmer
4.444
238215AE2-248 C
Solar/Wind Harmer
5.154
964391AG1-301 GEN
Solar/Wind Harmer
1.798
203987AE2-118 C
Solar/Wind Harmer
5.349
238206AE2-263_GEN
Solar/Wind Harmer
6.194
972169AH1-667 GEN
Solar/Wind Harmer
3.699
203954AE2-126 C
Solar/Wind Harmer
1.111
957561AF2-050 GEN
Solar/Wind Harmer
7.812
964201AG1-281 GEN
Solar/Wind Harmer
0.898
238183AE2-316 GEN
Solar/Wind Harmer
5.504
20094526CT_V3-030
Solar/Wind Harmer
0.812
970713AG2-456 GEN
Solar/Wind Harmer
7.972
971705AH1-358 GEN
Solar/Wind Harmer
2.318
971709AH1-360 GEN
Solar/Wind Harmer
2.318
20088826HIGHLAND
Solar/Wind Harmer
1.611
971279AH1-102 GEN
Solar/Wind Harmer
6.857
970631AG2-411 GEN
Solar/Wind Harmer
5.207
20326126BLOSSBCT
Adder
1.865
971423AH1-203 GEN
Solar/Wind Harmer
5.7
203843AF2-002_GEN
Solar/Wind Harmer
0.799
959471AF2-238 GEN
Solar/Wind Harmer
0.454
970337AG2-221 GEN
Solar/Wind Harmer
1.501
970511AG2-327 GEN
Solar/Wind Harmer
0.697
20335026MILZ1-092
Adder
1.586
944411AF1-106 GEN
Solar/Wind Harmer
1.461
203835AF1-098 GEN
Solar/Wind Harmer
1.684
971183AH1-050 GEN
Solar/Wind Harmer
2.676
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.548
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.459
20083026HNSMLK 3
Adder
3.459
203813AE2-344_GEN
Solar/Wind Harmer
6.772
970267AG2-176 GEN
Solar/Wind Harmer
8.703
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.083
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.492
20066526SHAWVL 3
50/50
2.473
20071526SHAWVL 1
50/50
1.676
216419AE2-001 C
Solar/Wind Harmer
6.267
203952AE2-129 C
Solar/Wind Harmer
1.181
203946AE2-131 C
Solar/Wind Harmer
1.179
962411AG1-090 GEN
Solar/Wind Harmer
18.518
20088626ARWF_N39
Solar/Wind Harmer
3.374
20303426NA_O38_P22
Solar/Wind Harmer
2.731
238217AF1-153 C O1
Solar/Wind Harmer
1.028
203853AF1-134 C O1
Solar/Wind Harmer
0.959
946381AF1-302 GEN
Solar/Wind Harmer
2.754
972075AH1-587 GEN
Solar/Wind Harmer
24.25
971441AH1-212 GEN
Solar/Wind Harmer
2.407
203940AF1-140 C
Solar/Wind Harmer
0.559
970305AG2-200 GEN
Solar/Wind Harmer
2.007
972077AH1-588 GEN
Solar/Wind Harmer
23.917
972079AH1-589 GEN
Solar/Wind Harmer
19.699
970715AG2-457 GEN
Solar/Wind Harmer
7.972
203857AF2-221 C
Solar/Wind Harmer
1.289
970123AG2-090 GEN
Solar/Wind Harmer
1.203
20088926STNY CRK
Solar/Wind Harmer
1.036
971427AH1-205 GEN
Solar/Wind Harmer
1.248
20084626FORWARD
Solar/Wind Harmer
0.653
203839AF1-321 GEN
Solar/Wind Harmer
1.598
20083426SW_E13_K22
Solar/Wind Harmer
0.223
20398826ARMNA MT
Solar/Wind Harmer
1.68
970313AG2-206 GEN
Solar/Wind Harmer
3.345
946071AF1-272 GEN
Solar/Wind Harmer
2.31
203848AF2-166 C
Solar/Wind Harmer
1.386
944781AF1-143 GEN
Solar/Wind Harmer
1.93
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.257
203963AG1-253 GEN
Solar/Wind Harmer
0.251
203859AF2-294 C
Solar/Wind Harmer
1.049
203947AF1-006 C
Solar/Wind Harmer
0.325
203980AG1-197 GEN
Solar/Wind Harmer
0.263
971931AH1-490 GEN
Solar/Wind Harmer
1.151
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.402
LAGNLTFEXP_LAGN->PJM
CLTF
1.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.969
TVALTFEXP_TVA->PJM
CLTF
0.645
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.495
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.533
MECLTFEXP_MEC->PJM
CLTF
1.368
SIGELTFEXP_SIGE->PJM
CLTF
0.042
LGEELTFEXP_LGEE->PJM
CLTF
0.556
WECLTFEXP_WEC->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.203
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.934
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.764

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT31_SRT-SL


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT31_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.32 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:959.88
MW Contribution:5.19
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.208
970643AG2-418 GEN
Solar/Wind Harmer
6.622
238202AE2-262_GEN
Solar/Wind Harmer
6.045
971627AH1-313 GEN
Solar/Wind Harmer
23.703
203854AF2-039 C
Solar/Wind Harmer
0.772
965131AG1-378 GEN
Solar/Wind Harmer
3.597
960051AF2-296 GEN
Solar/Wind Harmer
2.963
203818AF1-086 GEN
Solar/Wind Harmer
3.016
20120126WRREN CT
Adder
6.03
971703AH1-357 GEN
Solar/Wind Harmer
1.9
971707AH1-359 GEN
Solar/Wind Harmer
1.9
970899AG2-561 GEN
Solar/Wind Harmer
1.781
970125AG2-091 GEN
Solar/Wind Harmer
0.512
971419AH1-201 GEN
Solar/Wind Harmer
2.657
971541AH1-268 GEN
Solar/Wind Harmer
2.896
971879AH1-460 GEN
Solar/Wind Harmer
5.479
20334926Z1-069 C
Solar/Wind Harmer
1.712
203841AF2-001_GEN
Solar/Wind Harmer
1.6
20335126GROZ1-110
Adder
1.866
20335226CANZ2-011
Adder
1.813
945751AF1-240 GEN
Solar/Wind Harmer
1.245
20079426CONEMAGH
Adder
0.951
203932AE1-123
Adder
1.406
238219AF1-167 C
Solar/Wind Harmer
0.947
971185AH1-051 GEN
Solar/Wind Harmer
1.598
971355AH1-158 GEN
Solar/Wind Harmer
1.858
203856AF2-165 C
Solar/Wind Harmer
0.782
20089126CSLMN_L13
Solar/Wind Harmer
0.571
20089026BF_G21_K23
Solar/Wind Harmer
0.452
970647AG2-420 GEN
Solar/Wind Harmer
1.296
959441AF2-235 GEN
Solar/Wind Harmer
0.196
941421AE2-139 GEN
Solar/Wind Harmer
1.952
944411AF1-106 GEN
Solar/Wind Harmer
0.143
970335AG2-220 GEN
Solar/Wind Harmer
1.935
971127AH1-005 GEN
Solar/Wind Harmer
1.248
957161AF2-010 GEN
Solar/Wind Harmer
4.803
203830AF1-094 GEN
Solar/Wind Harmer
0.377
203948AG1-140 C
Solar/Wind Harmer
0.162
20084926LAKVU GN
Adder
0.106
20082926HNSMLK 2
Adder
3.5
20083126HNSMLK 4
Adder
3.5
203962AF1-287 GEN
Solar/Wind Harmer
1.165
962511AG1-100 GEN
Solar/Wind Harmer
0.347
972271AH1-720 GEN
Adder
3.751
20328326MANOR_T86
Adder
0.079
202652Y1-033 WT C
Solar/Wind Harmer
0.485
209071AE2-133 GEN
Solar/Wind Helper
0.041
946731AF1-337 GEN
Solar/Wind Helper
0.224
212507AE2-042_GEN
Solar/Wind Helper
0.784
200642SENECA#1
50/50
1.622
941231AE2-117 GEN
Solar/Wind Harmer
1.585
203855AF2-088 C
Solar/Wind Harmer
0.372
965121AG1-377 GEN
Solar/Wind Harmer
3.597
20090526Q36
Solar/Wind Harmer
2.684
203993AD2-133_GEN1
Solar/Wind Harmer
2.684
203975AE1-071-GEN
Solar/Wind Harmer
4.801
203961AE2-224 GEN
Solar/Wind Harmer
4.461
20091526CHSTN_FL
Solar/Wind Harmer
1.276
203804AE2-113_GEN
Solar/Wind Harmer
5.831
959381AF2-229 GEN
Solar/Wind Harmer
0.8
203850AG1-041 C
Solar/Wind Harmer
1.2
203844AF2-092 C
Solar/Wind Harmer
1.171
20092526R32
Solar/Wind Harmer
1.686
940863AE2-074 GEN
Solar/Wind Harmer
1.552
20087026C_T85_W218
Adder
0.483
20083726HOMER C1
Adder
47.661
20083926HOMER C3
Adder
49.71
20083826HOMER C2
Adder
46.957
203846AF2-130 C
Solar/Wind Harmer
0.393
970663AG2-429 GEN
Solar/Wind Harmer
4.719
970663AG2-429 GEN
Solar/Wind Harmer
0.768
970555AG2-356 GEN
Solar/Wind Harmer
1.352
970677AG2-438 GEN
Solar/Wind Harmer
0.623
966771AG1-548 GEN
Solar/Wind Harmer
9.071
966771AG1-548 GEN
Solar/Wind Harmer
1.758
20084926LAKVU GN
Adder
0.119
20083226HNSMLK 5
Adder
3.5
203926AA2-133 GEN
Adder
1.099
23732901CHBRG_I12
Adder
1.106
959431AF2-234 GEN
Solar/Wind Helper
0.45
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.225
20072226SHAWVL 2
50/50
29.887
20091326SHAW-D
50/50
1.316
20064926PENNTECH
50/50
0.411
200643SENECA#2
50/50
1.513
970643AG2-418 GEN
Solar/Wind Harmer
3.08
238215AE2-248 C
Solar/Wind Harmer
4.671
964391AG1-301 GEN
Solar/Wind Harmer
1.636
203987AE2-118 C
Solar/Wind Harmer
4.892
238206AE2-263_GEN
Solar/Wind Harmer
5.634
972169AH1-667 GEN
Solar/Wind Harmer
3.397
203954AE2-126 C
Solar/Wind Harmer
1.024
957561AF2-050 GEN
Solar/Wind Harmer
7.364
964201AG1-281 GEN
Solar/Wind Harmer
0.848
238183AE2-316 GEN
Solar/Wind Harmer
5.164
20094526CT_V3-030
Solar/Wind Harmer
0.782
20088826HIGHLAND
Solar/Wind Harmer
1.573
970713AG2-456 GEN
Solar/Wind Harmer
7.6
971705AH1-358 GEN
Solar/Wind Harmer
2.209
971709AH1-360 GEN
Solar/Wind Harmer
2.209
971279AH1-102 GEN
Solar/Wind Harmer
6.806
970631AG2-411 GEN
Solar/Wind Harmer
5.192
971423AH1-203 GEN
Solar/Wind Harmer
5.667
203843AF2-002_GEN
Solar/Wind Harmer
0.8
20326126BLOSSBCT
Adder
1.701
203835AF1-098 GEN
Solar/Wind Harmer
1.646
959471AF2-238 GEN
Solar/Wind Harmer
0.409
970337AG2-221 GEN
Solar/Wind Harmer
1.352
971183AH1-050 GEN
Solar/Wind Harmer
2.664
20089226LOOKOUT
Solar/Wind Harmer
0.556
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20335026MILZ1-092
Adder
1.445
944411AF1-106 GEN
Solar/Wind Harmer
1.331
970511AG2-327 GEN
Solar/Wind Harmer
0.623
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.106
20082826HNSMLK 1
Adder
3.5
20083026HNSMLK 3
Adder
3.5
970267AG2-176 GEN
Solar/Wind Harmer
8.732
203813AE2-344_GEN
Solar/Wind Harmer
6.753
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.1
946691AF1-333 GEN
Solar/Wind Helper
0.224
946741AF1-338 GEN
Solar/Wind Helper
0.224
20081226ALY HYDR
50/50
0.387
20066626SHAWVL 4
50/50
2.277
20066526SHAWVL 3
50/50
2.261
20071526SHAWVL 1
50/50
1.535
216419AE2-001 C
Solar/Wind Harmer
5.683
203952AE2-129 C
Solar/Wind Harmer
1.089
203946AE2-131 C
Solar/Wind Harmer
1.087
962411AG1-090 GEN
Solar/Wind Harmer
17.085
20088626ARWF_N39
Solar/Wind Harmer
3.152
20303426NA_O38_P22
Solar/Wind Harmer
2.552
238217AF1-153 C O1
Solar/Wind Harmer
0.95
203853AF1-134 C O1
Solar/Wind Harmer
0.896
946381AF1-302 GEN
Solar/Wind Harmer
2.584
971441AH1-212 GEN
Solar/Wind Harmer
2.308
972075AH1-587 GEN
Solar/Wind Harmer
22.794
20390526W1-045 C
Solar/Wind Harmer
0.412
203940AF1-140 C
Solar/Wind Harmer
0.538
970305AG2-200 GEN
Solar/Wind Harmer
1.907
972077AH1-588 GEN
Solar/Wind Harmer
22.799
972079AH1-589 GEN
Solar/Wind Harmer
18.778
970715AG2-457 GEN
Solar/Wind Harmer
7.6
203857AF2-221 C
Solar/Wind Harmer
1.279
970123AG2-090 GEN
Solar/Wind Harmer
1.194
20088926STNY CRK
Solar/Wind Harmer
1.026
203982AD2-062_GEN
Solar/Wind Harmer
6.895
971427AH1-205 GEN
Solar/Wind Harmer
1.236
20084626FORWARD
Solar/Wind Harmer
0.651
203839AF1-321 GEN
Solar/Wind Harmer
1.6
20083426SW_E13_K22
Solar/Wind Harmer
0.224
946071AF1-272 GEN
Solar/Wind Harmer
2.407
203848AF2-166 C
Solar/Wind Harmer
1.375
20398826ARMNA MT
Solar/Wind Harmer
1.531
944781AF1-143 GEN
Solar/Wind Harmer
1.958
970313AG2-206 GEN
Solar/Wind Harmer
2.989
203979AG1-198 GEN
Solar/Wind Harmer
0.226
971933AH1-491 GEN
Solar/Wind Harmer
1.245
203963AG1-253 GEN
Solar/Wind Harmer
0.247
203980AG1-197 GEN
Solar/Wind Harmer
0.263
203947AF1-006 C
Solar/Wind Harmer
0.323
971931AH1-490 GEN
Solar/Wind Harmer
1.149
203859AF2-294 C
Solar/Wind Harmer
0.938
203955AF1-039 C O1
Solar/Wind Harmer
0.236
209137AF2-361 C
Solar/Wind Helper
1.684
946751AF1-339 GEN
Solar/Wind Helper
0.224
209054AE2-059 GEN
Solar/Wind Helper
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
1.978
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.914
TVALTFEXP_TVA->PJM
CLTF
0.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.779
MECLTFEXP_MEC->PJM
CLTF
1.925
SIGELTFEXP_SIGE->PJM
CLTF
0.06
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.786
WECLTFEXP_WEC->PJM
CLTF
0.456
CPLELTFEXP_CPLE->PJM
CLTF
0.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.199

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-008_SRT-SL


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-008_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:155.32 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:959.88
MW Contribution:5.19
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.208
970643AG2-418 GEN
Solar/Wind Harmer
6.622
238202AE2-262_GEN
Solar/Wind Harmer
6.045
971627AH1-313 GEN
Solar/Wind Harmer
23.703
203854AF2-039 C
Solar/Wind Harmer
0.772
965131AG1-378 GEN
Solar/Wind Harmer
3.597
960051AF2-296 GEN
Solar/Wind Harmer
2.963
203818AF1-086 GEN
Solar/Wind Harmer
3.016
20120126WRREN CT
Adder
6.03
971703AH1-357 GEN
Solar/Wind Harmer
1.9
971707AH1-359 GEN
Solar/Wind Harmer
1.9
970899AG2-561 GEN
Solar/Wind Harmer
1.781
970125AG2-091 GEN
Solar/Wind Harmer
0.512
971419AH1-201 GEN
Solar/Wind Harmer
2.657
971541AH1-268 GEN
Solar/Wind Harmer
2.896
971879AH1-460 GEN
Solar/Wind Harmer
5.479
20334926Z1-069 C
Solar/Wind Harmer
1.712
203841AF2-001_GEN
Solar/Wind Harmer
1.6
20335126GROZ1-110
Adder
1.866
20335226CANZ2-011
Adder
1.813
945751AF1-240 GEN
Solar/Wind Harmer
1.245
20079426CONEMAGH
Adder
0.951
203932AE1-123
Adder
1.406
238219AF1-167 C
Solar/Wind Harmer
0.947
971185AH1-051 GEN
Solar/Wind Harmer
1.598
971355AH1-158 GEN
Solar/Wind Harmer
1.858
203856AF2-165 C
Solar/Wind Harmer
0.782
20089126CSLMN_L13
Solar/Wind Harmer
0.571
20089026BF_G21_K23
Solar/Wind Harmer
0.452
970647AG2-420 GEN
Solar/Wind Harmer
1.296
959441AF2-235 GEN
Solar/Wind Harmer
0.196
941421AE2-139 GEN
Solar/Wind Harmer
1.952
944411AF1-106 GEN
Solar/Wind Harmer
0.143
970335AG2-220 GEN
Solar/Wind Harmer
1.935
971127AH1-005 GEN
Solar/Wind Harmer
1.248
957161AF2-010 GEN
Solar/Wind Harmer
4.803
203830AF1-094 GEN
Solar/Wind Harmer
0.377
203948AG1-140 C
Solar/Wind Harmer
0.162
20084926LAKVU GN
Adder
0.106
20082926HNSMLK 2
Adder
3.5
20083126HNSMLK 4
Adder
3.5
203962AF1-287 GEN
Solar/Wind Harmer
1.165
962511AG1-100 GEN
Solar/Wind Harmer
0.347
972271AH1-720 GEN
Adder
3.751
20328326MANOR_T86
Adder
0.079
202652Y1-033 WT C
Solar/Wind Harmer
0.485
209071AE2-133 GEN
Solar/Wind Helper
0.041
946731AF1-337 GEN
Solar/Wind Helper
0.224
212507AE2-042_GEN
Solar/Wind Helper
0.784
200642SENECA#1
50/50
1.622
941231AE2-117 GEN
Solar/Wind Harmer
1.585
203855AF2-088 C
Solar/Wind Harmer
0.372
965121AG1-377 GEN
Solar/Wind Harmer
3.597
20090526Q36
Solar/Wind Harmer
2.684
203993AD2-133_GEN1
Solar/Wind Harmer
2.684
203975AE1-071-GEN
Solar/Wind Harmer
4.801
203961AE2-224 GEN
Solar/Wind Harmer
4.461
20091526CHSTN_FL
Solar/Wind Harmer
1.276
203804AE2-113_GEN
Solar/Wind Harmer
5.831
959381AF2-229 GEN
Solar/Wind Harmer
0.8
203850AG1-041 C
Solar/Wind Harmer
1.2
203844AF2-092 C
Solar/Wind Harmer
1.171
20092526R32
Solar/Wind Harmer
1.686
940863AE2-074 GEN
Solar/Wind Harmer
1.552
20087026C_T85_W218
Adder
0.483
20083726HOMER C1
Adder
47.661
20083926HOMER C3
Adder
49.71
20083826HOMER C2
Adder
46.957
203846AF2-130 C
Solar/Wind Harmer
0.393
970663AG2-429 GEN
Solar/Wind Harmer
4.719
970663AG2-429 GEN
Solar/Wind Harmer
0.768
970555AG2-356 GEN
Solar/Wind Harmer
1.352
970677AG2-438 GEN
Solar/Wind Harmer
0.623
966771AG1-548 GEN
Solar/Wind Harmer
9.071
966771AG1-548 GEN
Solar/Wind Harmer
1.758
20084926LAKVU GN
Adder
0.119
20083226HNSMLK 5
Adder
3.5
203926AA2-133 GEN
Adder
1.099
23732901CHBRG_I12
Adder
1.106
959431AF2-234 GEN
Solar/Wind Helper
0.45
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.225
20072226SHAWVL 2
50/50
29.887
20091326SHAW-D
50/50
1.316
20064926PENNTECH
50/50
0.411
200643SENECA#2
50/50
1.513
970643AG2-418 GEN
Solar/Wind Harmer
3.08
238215AE2-248 C
Solar/Wind Harmer
4.671
964391AG1-301 GEN
Solar/Wind Harmer
1.636
203987AE2-118 C
Solar/Wind Harmer
4.892
238206AE2-263_GEN
Solar/Wind Harmer
5.634
972169AH1-667 GEN
Solar/Wind Harmer
3.397
203954AE2-126 C
Solar/Wind Harmer
1.024
957561AF2-050 GEN
Solar/Wind Harmer
7.364
964201AG1-281 GEN
Solar/Wind Harmer
0.848
238183AE2-316 GEN
Solar/Wind Harmer
5.164
20094526CT_V3-030
Solar/Wind Harmer
0.782
20088826HIGHLAND
Solar/Wind Harmer
1.573
970713AG2-456 GEN
Solar/Wind Harmer
7.6
971705AH1-358 GEN
Solar/Wind Harmer
2.209
971709AH1-360 GEN
Solar/Wind Harmer
2.209
971279AH1-102 GEN
Solar/Wind Harmer
6.806
970631AG2-411 GEN
Solar/Wind Harmer
5.192
971423AH1-203 GEN
Solar/Wind Harmer
5.667
203843AF2-002_GEN
Solar/Wind Harmer
0.8
20326126BLOSSBCT
Adder
1.701
203835AF1-098 GEN
Solar/Wind Harmer
1.646
959471AF2-238 GEN
Solar/Wind Harmer
0.409
970337AG2-221 GEN
Solar/Wind Harmer
1.352
971183AH1-050 GEN
Solar/Wind Harmer
2.664
20089226LOOKOUT
Solar/Wind Harmer
0.556
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20335026MILZ1-092
Adder
1.445
944411AF1-106 GEN
Solar/Wind Harmer
1.331
970511AG2-327 GEN
Solar/Wind Harmer
0.623
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.106
20082826HNSMLK 1
Adder
3.5
20083026HNSMLK 3
Adder
3.5
970267AG2-176 GEN
Solar/Wind Harmer
8.732
203813AE2-344_GEN
Solar/Wind Harmer
6.753
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.1
946691AF1-333 GEN
Solar/Wind Helper
0.224
946741AF1-338 GEN
Solar/Wind Helper
0.224
20081226ALY HYDR
50/50
0.387
20066626SHAWVL 4
50/50
2.277
20066526SHAWVL 3
50/50
2.261
20071526SHAWVL 1
50/50
1.535
216419AE2-001 C
Solar/Wind Harmer
5.683
203952AE2-129 C
Solar/Wind Harmer
1.089
203946AE2-131 C
Solar/Wind Harmer
1.087
962411AG1-090 GEN
Solar/Wind Harmer
17.085
20088626ARWF_N39
Solar/Wind Harmer
3.152
20303426NA_O38_P22
Solar/Wind Harmer
2.552
238217AF1-153 C O1
Solar/Wind Harmer
0.95
203853AF1-134 C O1
Solar/Wind Harmer
0.896
946381AF1-302 GEN
Solar/Wind Harmer
2.584
971441AH1-212 GEN
Solar/Wind Harmer
2.308
972075AH1-587 GEN
Solar/Wind Harmer
22.794
20390526W1-045 C
Solar/Wind Harmer
0.412
203940AF1-140 C
Solar/Wind Harmer
0.538
970305AG2-200 GEN
Solar/Wind Harmer
1.907
972077AH1-588 GEN
Solar/Wind Harmer
22.799
972079AH1-589 GEN
Solar/Wind Harmer
18.778
970715AG2-457 GEN
Solar/Wind Harmer
7.6
203857AF2-221 C
Solar/Wind Harmer
1.279
970123AG2-090 GEN
Solar/Wind Harmer
1.194
20088926STNY CRK
Solar/Wind Harmer
1.026
203982AD2-062_GEN
Solar/Wind Harmer
6.895
971427AH1-205 GEN
Solar/Wind Harmer
1.236
20084626FORWARD
Solar/Wind Harmer
0.651
203839AF1-321 GEN
Solar/Wind Harmer
1.6
20083426SW_E13_K22
Solar/Wind Harmer
0.224
946071AF1-272 GEN
Solar/Wind Harmer
2.407
203848AF2-166 C
Solar/Wind Harmer
1.375
20398826ARMNA MT
Solar/Wind Harmer
1.531
944781AF1-143 GEN
Solar/Wind Harmer
1.958
970313AG2-206 GEN
Solar/Wind Harmer
2.989
203979AG1-198 GEN
Solar/Wind Harmer
0.226
971933AH1-491 GEN
Solar/Wind Harmer
1.245
203963AG1-253 GEN
Solar/Wind Harmer
0.247
203980AG1-197 GEN
Solar/Wind Harmer
0.263
203947AF1-006 C
Solar/Wind Harmer
0.323
971931AH1-490 GEN
Solar/Wind Harmer
1.149
203859AF2-294 C
Solar/Wind Harmer
0.938
203955AF1-039 C O1
Solar/Wind Harmer
0.236
209137AF2-361 C
Solar/Wind Helper
1.684
946751AF1-339 GEN
Solar/Wind Helper
0.224
209054AE2-059 GEN
Solar/Wind Helper
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
1.978
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.914
TVALTFEXP_TVA->PJM
CLTF
0.976
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.779
MECLTFEXP_MEC->PJM
CLTF
1.925
SIGELTFEXP_SIGE->PJM
CLTF
0.06
NYPJM->LTFIMP_NY
CLTF
0.167
LGEELTFEXP_LGEE->PJM
CLTF
0.786
WECLTFEXP_WEC->PJM
CLTF
0.456
CPLELTFEXP_CPLE->PJM
CLTF
0.537
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.199

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-3_PN-115-0331-D_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-0331-D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.64 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:955.66
MW Contribution:5.2
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.719
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.55
238202AE2-262_GEN
Solar/Wind Harmer
6.641
971627AH1-313 GEN
Solar/Wind Harmer
26.037
203854AF2-039 C
Solar/Wind Harmer
0.84
965131AG1-378 GEN
Solar/Wind Harmer
3.895
960051AF2-296 GEN
Solar/Wind Harmer
3.169
203818AF1-086 GEN
Solar/Wind Harmer
3.16
20120126WRREN CT
Adder
6.339
971703AH1-357 GEN
Solar/Wind Harmer
1.991
971707AH1-359 GEN
Solar/Wind Harmer
1.991
970899AG2-561 GEN
Solar/Wind Harmer
1.805
20335126GROZ1-110
Adder
2.097
20335226CANZ2-011
Adder
2.038
20334926Z1-069 C
Solar/Wind Harmer
1.816
970125AG2-091 GEN
Solar/Wind Harmer
0.515
971419AH1-201 GEN
Solar/Wind Harmer
2.68
971541AH1-268 GEN
Solar/Wind Harmer
2.914
971879AH1-460 GEN
Solar/Wind Harmer
5.495
945751AF1-240 GEN
Solar/Wind Harmer
1.259
203841AF2-001_GEN
Solar/Wind Harmer
1.596
20079426CONEMAGH
Adder
0.951
941421AE2-139 GEN
Solar/Wind Harmer
2.26
203932AE1-123
Adder
1.418
238219AF1-167 C
Solar/Wind Harmer
0.956
970335AG2-220 GEN
Solar/Wind Harmer
2.159
971127AH1-005 GEN
Solar/Wind Harmer
1.393
944411AF1-106 GEN
Solar/Wind Harmer
0.157
20072226SHAWVL 2
50/50
32.675
20091326SHAW-D
50/50
1.432
972271AH1-720 GEN
Adder
4.387
971185AH1-051 GEN
Solar/Wind Harmer
1.603
971355AH1-158 GEN
Solar/Wind Harmer
1.864
203856AF2-165 C
Solar/Wind Harmer
0.785
959441AF2-235 GEN
Solar/Wind Harmer
0.197
970647AG2-420 GEN
Solar/Wind Harmer
1.299
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.563
20089026BF_G21_K23
Solar/Wind Harmer
0.445
957161AF2-010 GEN
Solar/Wind Harmer
4.842
203830AF1-094 GEN
Solar/Wind Harmer
0.38
203948AG1-140 C
Solar/Wind Harmer
0.164
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.454
20083126HNSMLK 4
Adder
3.454
203962AF1-287 GEN
Solar/Wind Harmer
1.167
962511AG1-100 GEN
Solar/Wind Harmer
0.347
202652Y1-033 WT C
Solar/Wind Harmer
0.468
200917MEHOOPANY_G
Solar/Wind Harmer
1.645
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.49
20066526SHAWVL 3
50/50
2.472
20071526SHAWVL 1
50/50
1.674
20390526W1-045 C
Solar/Wind Harmer
1.791
216419AE2-001 C
Solar/Wind Harmer
6.263
203952AE2-129 C
Solar/Wind Harmer
1.18
203946AE2-131 C
Solar/Wind Harmer
1.178
962411AG1-090 GEN
Solar/Wind Harmer
18.503
20088626ARWF_N39
Solar/Wind Harmer
3.371
20303426NA_O38_P22
Solar/Wind Harmer
2.729
238217AF1-153 C O1
Solar/Wind Harmer
1.027
203853AF1-134 C O1
Solar/Wind Harmer
0.958
946381AF1-302 GEN
Solar/Wind Harmer
2.752
972075AH1-587 GEN
Solar/Wind Harmer
24.224
971441AH1-212 GEN
Solar/Wind Harmer
2.405
203940AF1-140 C
Solar/Wind Harmer
0.558
970305AG2-200 GEN
Solar/Wind Harmer
2.005
972077AH1-588 GEN
Solar/Wind Harmer
23.888
972079AH1-589 GEN
Solar/Wind Harmer
19.675
970715AG2-457 GEN
Solar/Wind Harmer
7.963
203857AF2-221 C
Solar/Wind Harmer
1.288
970123AG2-090 GEN
Solar/Wind Harmer
1.202
20088926STNY CRK
Solar/Wind Harmer
1.035
971427AH1-205 GEN
Solar/Wind Harmer
1.246
20084626FORWARD
Solar/Wind Harmer
0.652
203839AF1-321 GEN
Solar/Wind Harmer
1.596
20083426SW_E13_K22
Solar/Wind Harmer
0.223
20398826ARMNA MT
Solar/Wind Harmer
1.677
970313AG2-206 GEN
Solar/Wind Harmer
3.337
946071AF1-272 GEN
Solar/Wind Harmer
2.307
203848AF2-166 C
Solar/Wind Harmer
1.384
944781AF1-143 GEN
Solar/Wind Harmer
1.929
203979AG1-198 GEN
Solar/Wind Harmer
0.228
971933AH1-491 GEN
Solar/Wind Harmer
1.255
203963AG1-253 GEN
Solar/Wind Harmer
0.251
203859AF2-294 C
Solar/Wind Harmer
1.046
203947AF1-006 C
Solar/Wind Harmer
0.324
203980AG1-197 GEN
Solar/Wind Harmer
0.262
971931AH1-490 GEN
Solar/Wind Harmer
1.149
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.408
203975AE1-071-GEN
Solar/Wind Harmer
13.299
959381AF2-229 GEN
Solar/Wind Harmer
3.476
941231AE2-117 GEN
Solar/Wind Harmer
1.738
203855AF2-088 C
Solar/Wind Harmer
0.404
965121AG1-377 GEN
Solar/Wind Harmer
3.895
20090526Q36
Solar/Wind Harmer
2.894
203993AD2-133_GEN1
Solar/Wind Harmer
2.894
203961AE2-224 GEN
Solar/Wind Harmer
4.727
20091526CHSTN_FL
Solar/Wind Harmer
1.355
203804AE2-113_GEN
Solar/Wind Harmer
6.221
203850AG1-041 C
Solar/Wind Harmer
1.233
203844AF2-092 C
Solar/Wind Harmer
1.2
20092526R32
Solar/Wind Harmer
1.724
940863AE2-074 GEN
Solar/Wind Harmer
1.637
970555AG2-356 GEN
Solar/Wind Harmer
1.497
203846AF2-130 C
Solar/Wind Harmer
0.395
970663AG2-429 GEN
Solar/Wind Harmer
4.745
970663AG2-429 GEN
Solar/Wind Harmer
0.772
20083926HOMER C3
Adder
48.613
20083826HOMER C2
Adder
45.92
20083726HOMER C1
Adder
45.338
970677AG2-438 GEN
Solar/Wind Harmer
0.628
966771AG1-548 GEN
Solar/Wind Harmer
9.147
966771AG1-548 GEN
Solar/Wind Harmer
1.773
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.454
203926AA2-133 GEN
Adder
1.312
20334726NME_Y1-047
Adder
1.105
20064926PENNTECH
50/50
0.443
200643SENECA#2
50/50
1.604
970643AG2-418 GEN
Solar/Wind Harmer
4.442
238215AE2-248 C
Solar/Wind Harmer
5.15
964391AG1-301 GEN
Solar/Wind Harmer
1.796
203987AE2-118 C
Solar/Wind Harmer
5.345
238206AE2-263_GEN
Solar/Wind Harmer
6.189
972169AH1-667 GEN
Solar/Wind Harmer
3.696
203954AE2-126 C
Solar/Wind Harmer
1.11
957561AF2-050 GEN
Solar/Wind Harmer
7.804
964201AG1-281 GEN
Solar/Wind Harmer
0.897
238183AE2-316 GEN
Solar/Wind Harmer
5.499
20094526CT_V3-030
Solar/Wind Harmer
0.811
970713AG2-456 GEN
Solar/Wind Harmer
7.963
971705AH1-358 GEN
Solar/Wind Harmer
2.315
971709AH1-360 GEN
Solar/Wind Harmer
2.315
20088826HIGHLAND
Solar/Wind Harmer
1.609
971279AH1-102 GEN
Solar/Wind Harmer
6.847
970631AG2-411 GEN
Solar/Wind Harmer
5.2
971423AH1-203 GEN
Solar/Wind Harmer
5.694
20326126BLOSSBCT
Adder
1.862
203843AF2-002_GEN
Solar/Wind Harmer
0.798
959471AF2-238 GEN
Solar/Wind Harmer
0.453
970337AG2-221 GEN
Solar/Wind Harmer
1.497
970511AG2-327 GEN
Solar/Wind Harmer
0.695
20335026MILZ1-092
Adder
1.583
944411AF1-106 GEN
Solar/Wind Harmer
1.458
203835AF1-098 GEN
Solar/Wind Harmer
1.682
971183AH1-050 GEN
Solar/Wind Harmer
2.672
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.548
203860AG1-193 C
Solar/Wind Harmer
0.185
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.454
20083026HNSMLK 3
Adder
3.454
203813AE2-344_GEN
Solar/Wind Harmer
6.763
970267AG2-176 GEN
Solar/Wind Harmer
8.692
961971AG1-040 GEN
Solar/Wind Harmer
0.35
209067AE2-060 GEN
Solar/Wind Helper
0.084
LAGNLTFEXP_LAGN->PJM
CLTF
1.32
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.978
TVALTFEXP_TVA->PJM
CLTF
0.647
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.506
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.539
MECLTFEXP_MEC->PJM
CLTF
1.37
SIGELTFEXP_SIGE->PJM
CLTF
0.042
LGEELTFEXP_LGEE->PJM
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.206
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.814
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.783

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-030_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-030_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:149.64 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:924.75
MW Contribution:5.22
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.726
20091326SHAW-D
50/50
1.435
20064926PENNTECH
50/50
0.444
200643SENECA#2
50/50
1.608
970643AG2-418 GEN
Solar/Wind Harmer
4.449
238215AE2-248 C
Solar/Wind Harmer
5.157
964391AG1-301 GEN
Solar/Wind Harmer
1.799
203987AE2-118 C
Solar/Wind Harmer
5.352
238206AE2-263_GEN
Solar/Wind Harmer
6.198
972169AH1-667 GEN
Solar/Wind Harmer
3.702
203954AE2-126 C
Solar/Wind Harmer
1.112
957561AF2-050 GEN
Solar/Wind Harmer
7.821
964201AG1-281 GEN
Solar/Wind Harmer
0.899
238183AE2-316 GEN
Solar/Wind Harmer
5.512
20094526CT_V3-030
Solar/Wind Harmer
0.813
970713AG2-456 GEN
Solar/Wind Harmer
7.987
971705AH1-358 GEN
Solar/Wind Harmer
2.322
971709AH1-360 GEN
Solar/Wind Harmer
2.322
20088826HIGHLAND
Solar/Wind Harmer
1.614
971279AH1-102 GEN
Solar/Wind Harmer
6.871
970631AG2-411 GEN
Solar/Wind Harmer
5.218
20326126BLOSSBCT
Adder
1.87
971423AH1-203 GEN
Solar/Wind Harmer
5.712
203843AF2-002_GEN
Solar/Wind Harmer
0.801
959471AF2-238 GEN
Solar/Wind Harmer
0.455
970337AG2-221 GEN
Solar/Wind Harmer
1.504
970511AG2-327 GEN
Solar/Wind Harmer
0.699
20335026MILZ1-092
Adder
1.59
944411AF1-106 GEN
Solar/Wind Harmer
1.465
203835AF1-098 GEN
Solar/Wind Harmer
1.688
971183AH1-050 GEN
Solar/Wind Harmer
2.683
970647AG2-420 GEN
Solar/Wind Harmer
0.152
20089226LOOKOUT
Solar/Wind Harmer
0.55
203860AG1-193 C
Solar/Wind Harmer
0.186
20084926LAKVU GN
Adder
0.108
20082826HNSMLK 1
Adder
3.47
20083026HNSMLK 3
Adder
3.47
203813AE2-344_GEN
Solar/Wind Harmer
6.793
970267AG2-176 GEN
Solar/Wind Harmer
8.73
961971AG1-040 GEN
Solar/Wind Harmer
0.351
209067AE2-060 GEN
Solar/Wind Helper
0.083
200642SENECA#1
50/50
1.724
941231AE2-117 GEN
Solar/Wind Harmer
1.74
203855AF2-088 C
Solar/Wind Harmer
0.405
965121AG1-377 GEN
Solar/Wind Harmer
3.902
20090526Q36
Solar/Wind Harmer
2.9
203993AD2-133_GEN1
Solar/Wind Harmer
2.9
203961AE2-224 GEN
Solar/Wind Harmer
4.737
20091526CHSTN_FL
Solar/Wind Harmer
1.358
203804AE2-113_GEN
Solar/Wind Harmer
6.236
203850AG1-041 C
Solar/Wind Harmer
1.236
203844AF2-092 C
Solar/Wind Harmer
1.204
20092526R32
Solar/Wind Harmer
1.729
940863AE2-074 GEN
Solar/Wind Harmer
1.642
970555AG2-356 GEN
Solar/Wind Harmer
1.504
203846AF2-130 C
Solar/Wind Harmer
0.397
970663AG2-429 GEN
Solar/Wind Harmer
4.764
970663AG2-429 GEN
Solar/Wind Harmer
0.776
20083926HOMER C3
Adder
48.819
20083826HOMER C2
Adder
46.115
20083726HOMER C1
Adder
45.538
970677AG2-438 GEN
Solar/Wind Harmer
0.63
966771AG1-548 GEN
Solar/Wind Harmer
9.185
966771AG1-548 GEN
Solar/Wind Harmer
1.78
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.47
203926AA2-133 GEN
Adder
1.32
20334726NME_Y1-047
Adder
1.114
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
9.566
238202AE2-262_GEN
Solar/Wind Harmer
6.65
971627AH1-313 GEN
Solar/Wind Harmer
26.074
203854AF2-039 C
Solar/Wind Harmer
0.841
965131AG1-378 GEN
Solar/Wind Harmer
3.902
960051AF2-296 GEN
Solar/Wind Harmer
3.175
203818AF1-086 GEN
Solar/Wind Harmer
3.168
20120126WRREN CT
Adder
6.357
971703AH1-357 GEN
Solar/Wind Harmer
1.997
971707AH1-359 GEN
Solar/Wind Harmer
1.997
970899AG2-561 GEN
Solar/Wind Harmer
1.811
20335126GROZ1-110
Adder
2.105
20335226CANZ2-011
Adder
2.046
20334926Z1-069 C
Solar/Wind Harmer
1.822
970125AG2-091 GEN
Solar/Wind Harmer
0.517
971419AH1-201 GEN
Solar/Wind Harmer
2.689
971541AH1-268 GEN
Solar/Wind Harmer
2.924
971879AH1-460 GEN
Solar/Wind Harmer
5.514
945751AF1-240 GEN
Solar/Wind Harmer
1.263
203841AF2-001_GEN
Solar/Wind Harmer
1.602
20079426CONEMAGH
Adder
0.955
941421AE2-139 GEN
Solar/Wind Harmer
2.271
203932AE1-123
Adder
1.423
238219AF1-167 C
Solar/Wind Harmer
0.96
970335AG2-220 GEN
Solar/Wind Harmer
2.169
971127AH1-005 GEN
Solar/Wind Harmer
1.4
944411AF1-106 GEN
Solar/Wind Harmer
0.158
972271AH1-720 GEN
Adder
4.411
971185AH1-051 GEN
Solar/Wind Harmer
1.61
971355AH1-158 GEN
Solar/Wind Harmer
1.872
203856AF2-165 C
Solar/Wind Harmer
0.788
959441AF2-235 GEN
Solar/Wind Harmer
0.198
970647AG2-420 GEN
Solar/Wind Harmer
1.304
20328326MANOR_T86
Adder
0.093
20089126CSLMN_L13
Solar/Wind Harmer
0.565
20089026BF_G21_K23
Solar/Wind Harmer
0.447
957161AF2-010 GEN
Solar/Wind Harmer
4.862
203830AF1-094 GEN
Solar/Wind Harmer
0.382
203948AG1-140 C
Solar/Wind Harmer
0.165
20084926LAKVU GN
Adder
0.108
20082926HNSMLK 2
Adder
3.47
20083126HNSMLK 4
Adder
3.47
203962AF1-287 GEN
Solar/Wind Harmer
1.172
962511AG1-100 GEN
Solar/Wind Harmer
0.349
202652Y1-033 WT C
Solar/Wind Harmer
0.469
200917MEHOOPANY_G
Solar/Wind Harmer
1.659
20081226ALY HYDR
50/50
0.426
20066626SHAWVL 4
50/50
2.494
20066526SHAWVL 3
50/50
2.475
20071526SHAWVL 1
50/50
1.677
216419AE2-001 C
Solar/Wind Harmer
6.27
203952AE2-129 C
Solar/Wind Harmer
1.182
203946AE2-131 C
Solar/Wind Harmer
1.18
962411AG1-090 GEN
Solar/Wind Harmer
18.535
20088626ARWF_N39
Solar/Wind Harmer
3.377
20303426NA_O38_P22
Solar/Wind Harmer
2.734
238217AF1-153 C O1
Solar/Wind Harmer
1.029
203853AF1-134 C O1
Solar/Wind Harmer
0.96
946381AF1-302 GEN
Solar/Wind Harmer
2.758
972075AH1-587 GEN
Solar/Wind Harmer
24.286
971441AH1-212 GEN
Solar/Wind Harmer
2.411
203940AF1-140 C
Solar/Wind Harmer
0.559
970305AG2-200 GEN
Solar/Wind Harmer
2.011
972077AH1-588 GEN
Solar/Wind Harmer
23.96
972079AH1-589 GEN
Solar/Wind Harmer
19.735
970715AG2-457 GEN
Solar/Wind Harmer
7.987
203857AF2-221 C
Solar/Wind Harmer
1.292
970123AG2-090 GEN
Solar/Wind Harmer
1.206
20088926STNY CRK
Solar/Wind Harmer
1.038
971427AH1-205 GEN
Solar/Wind Harmer
1.25
20084626FORWARD
Solar/Wind Harmer
0.655
203839AF1-321 GEN
Solar/Wind Harmer
1.602
20083426SW_E13_K22
Solar/Wind Harmer
0.224
20398826ARMNA MT
Solar/Wind Harmer
1.685
970313AG2-206 GEN
Solar/Wind Harmer
3.354
946071AF1-272 GEN
Solar/Wind Harmer
2.316
203848AF2-166 C
Solar/Wind Harmer
1.389
944781AF1-143 GEN
Solar/Wind Harmer
1.935
203979AG1-198 GEN
Solar/Wind Harmer
0.229
971933AH1-491 GEN
Solar/Wind Harmer
1.26
203963AG1-253 GEN
Solar/Wind Harmer
0.252
203859AF2-294 C
Solar/Wind Harmer
1.052
203947AF1-006 C
Solar/Wind Harmer
0.326
203980AG1-197 GEN
Solar/Wind Harmer
0.263
971931AH1-490 GEN
Solar/Wind Harmer
1.154
203955AF1-039 C O1
Solar/Wind Harmer
0.228
209137AF2-361 C
Solar/Wind Helper
1.399
LAGNLTFEXP_LAGN->PJM
CLTF
1.353
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.024
TVALTFEXP_TVA->PJM
CLTF
0.663
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.758
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.602
MECLTFEXP_MEC->PJM
CLTF
1.398
SIGELTFEXP_SIGE->PJM
CLTF
0.043
LGEELTFEXP_LGEE->PJM
CLTF
0.569
WECLTFEXP_WEC->PJM
CLTF
0.335
CPLELTFEXP_CPLE->PJM
CLTF
0.223
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.037
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.007

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-115-031_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-115-031_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:144.8 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:894.87
MW Contribution:5.09
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.216
238202AE2-262_GEN
Solar/Wind Harmer
6.504
971627AH1-313 GEN
Solar/Wind Harmer
25.5
203854AF2-039 C
Solar/Wind Harmer
0.822
965131AG1-378 GEN
Solar/Wind Harmer
3.812
960051AF2-296 GEN
Solar/Wind Harmer
3.103
203818AF1-086 GEN
Solar/Wind Harmer
3.094
20120126WRREN CT
Adder
6.211
971703AH1-357 GEN
Solar/Wind Harmer
1.949
971707AH1-359 GEN
Solar/Wind Harmer
1.949
970899AG2-561 GEN
Solar/Wind Harmer
1.767
20335126GROZ1-110
Adder
2.048
20335226CANZ2-011
Adder
1.991
20334926Z1-069 C
Solar/Wind Harmer
1.776
970125AG2-091 GEN
Solar/Wind Harmer
0.504
971419AH1-201 GEN
Solar/Wind Harmer
2.624
971541AH1-268 GEN
Solar/Wind Harmer
2.852
971879AH1-460 GEN
Solar/Wind Harmer
5.378
945751AF1-240 GEN
Solar/Wind Harmer
1.233
203841AF2-001_GEN
Solar/Wind Harmer
1.562
20079426CONEMAGH
Adder
0.931
941421AE2-139 GEN
Solar/Wind Harmer
2.204
203932AE1-123
Adder
1.389
238219AF1-167 C
Solar/Wind Harmer
0.937
970335AG2-220 GEN
Solar/Wind Harmer
2.107
971127AH1-005 GEN
Solar/Wind Harmer
1.359
944411AF1-106 GEN
Solar/Wind Harmer
0.153
972271AH1-720 GEN
Adder
4.276
971185AH1-051 GEN
Solar/Wind Harmer
1.571
971355AH1-158 GEN
Solar/Wind Harmer
1.827
203856AF2-165 C
Solar/Wind Harmer
0.77
959441AF2-235 GEN
Solar/Wind Harmer
0.193
970647AG2-420 GEN
Solar/Wind Harmer
1.273
20328326MANOR_T86
Adder
0.09
20089126CSLMN_L13
Solar/Wind Harmer
0.552
20089026BF_G21_K23
Solar/Wind Harmer
0.437
957161AF2-010 GEN
Solar/Wind Harmer
4.749
203830AF1-094 GEN
Solar/Wind Harmer
0.373
203948AG1-140 C
Solar/Wind Harmer
0.161
20084926LAKVU GN
Adder
0.105
20082926HNSMLK 2
Adder
3.386
20083126HNSMLK 4
Adder
3.386
203962AF1-287 GEN
Solar/Wind Harmer
1.145
962511AG1-100 GEN
Solar/Wind Harmer
0.341
202652Y1-033 WT C
Solar/Wind Harmer
0.46
200917MEHOOPANY_G
Solar/Wind Harmer
1.599
970643AG2-418 GEN
Solar/Wind Harmer
0.876
20081226ALY HYDR
50/50
0.416
20066626SHAWVL 4
50/50
2.438
20066526SHAWVL 3
50/50
2.42
20071526SHAWVL 1
50/50
1.64
216419AE2-001 C
Solar/Wind Harmer
6.134
203952AE2-129 C
Solar/Wind Harmer
1.154
203946AE2-131 C
Solar/Wind Harmer
1.152
962411AG1-090 GEN
Solar/Wind Harmer
18.107
20088626ARWF_N39
Solar/Wind Harmer
3.299
20303426NA_O38_P22
Solar/Wind Harmer
2.671
238217AF1-153 C O1
Solar/Wind Harmer
1.006
203853AF1-134 C O1
Solar/Wind Harmer
0.938
946381AF1-302 GEN
Solar/Wind Harmer
2.695
972075AH1-587 GEN
Solar/Wind Harmer
23.718
971441AH1-212 GEN
Solar/Wind Harmer
2.353
203940AF1-140 C
Solar/Wind Harmer
0.546
970305AG2-200 GEN
Solar/Wind Harmer
1.965
972077AH1-588 GEN
Solar/Wind Harmer
23.389
972079AH1-589 GEN
Solar/Wind Harmer
19.264
970715AG2-457 GEN
Solar/Wind Harmer
7.796
203857AF2-221 C
Solar/Wind Harmer
1.26
970123AG2-090 GEN
Solar/Wind Harmer
1.176
20088926STNY CRK
Solar/Wind Harmer
1.013
971427AH1-205 GEN
Solar/Wind Harmer
1.221
20084626FORWARD
Solar/Wind Harmer
0.639
203839AF1-321 GEN
Solar/Wind Harmer
1.562
20083426SW_E13_K22
Solar/Wind Harmer
0.218
20398826ARMNA MT
Solar/Wind Harmer
1.637
946071AF1-272 GEN
Solar/Wind Harmer
2.258
970313AG2-206 GEN
Solar/Wind Harmer
3.257
203848AF2-166 C
Solar/Wind Harmer
1.356
944781AF1-143 GEN
Solar/Wind Harmer
1.893
203979AG1-198 GEN
Solar/Wind Harmer
0.224
971933AH1-491 GEN
Solar/Wind Harmer
1.231
203963AG1-253 GEN
Solar/Wind Harmer
0.246
203859AF2-294 C
Solar/Wind Harmer
1.02
203947AF1-006 C
Solar/Wind Harmer
0.318
203980AG1-197 GEN
Solar/Wind Harmer
0.257
971931AH1-490 GEN
Solar/Wind Harmer
1.128
203955AF1-039 C O1
Solar/Wind Harmer
0.224
209137AF2-361 C
Solar/Wind Helper
1.43
20072226SHAWVL 2
50/50
31.998
20091326SHAW-D
50/50
1.402
20064926PENNTECH
50/50
0.434
200643SENECA#2
50/50
1.571
238215AE2-248 C
Solar/Wind Harmer
5.045
964391AG1-301 GEN
Solar/Wind Harmer
1.749
203987AE2-118 C
Solar/Wind Harmer
5.213
238206AE2-263_GEN
Solar/Wind Harmer
6.062
972169AH1-667 GEN
Solar/Wind Harmer
3.619
203954AE2-126 C
Solar/Wind Harmer
1.087
957561AF2-050 GEN
Solar/Wind Harmer
7.637
964201AG1-281 GEN
Solar/Wind Harmer
0.878
238183AE2-316 GEN
Solar/Wind Harmer
5.386
20094526CT_V3-030
Solar/Wind Harmer
0.794
970713AG2-456 GEN
Solar/Wind Harmer
7.796
971705AH1-358 GEN
Solar/Wind Harmer
2.266
971709AH1-360 GEN
Solar/Wind Harmer
2.266
20088826HIGHLAND
Solar/Wind Harmer
1.574
971279AH1-102 GEN
Solar/Wind Harmer
6.701
970631AG2-411 GEN
Solar/Wind Harmer
5.09
971423AH1-203 GEN
Solar/Wind Harmer
5.576
20326126BLOSSBCT
Adder
1.819
203843AF2-002_GEN
Solar/Wind Harmer
0.781
959471AF2-238 GEN
Solar/Wind Harmer
0.442
970337AG2-221 GEN
Solar/Wind Harmer
1.462
203835AF1-098 GEN
Solar/Wind Harmer
1.65
970511AG2-327 GEN
Solar/Wind Harmer
0.679
20335026MILZ1-092
Adder
1.546
944411AF1-106 GEN
Solar/Wind Harmer
1.424
971183AH1-050 GEN
Solar/Wind Harmer
2.619
970647AG2-420 GEN
Solar/Wind Harmer
0.148
20089226LOOKOUT
Solar/Wind Harmer
0.538
203860AG1-193 C
Solar/Wind Harmer
0.182
20084926LAKVU GN
Adder
0.105
20082826HNSMLK 1
Adder
3.386
20083026HNSMLK 3
Adder
3.386
203813AE2-344_GEN
Solar/Wind Harmer
6.636
970267AG2-176 GEN
Solar/Wind Harmer
8.526
961971AG1-040 GEN
Solar/Wind Harmer
0.343
970643AG2-418 GEN
Solar/Wind Harmer
0.407
209067AE2-060 GEN
Solar/Wind Helper
0.085
200642SENECA#1
50/50
1.684
941231AE2-117 GEN
Solar/Wind Harmer
1.693
203855AF2-088 C
Solar/Wind Harmer
0.396
965121AG1-377 GEN
Solar/Wind Harmer
3.812
20090526Q36
Solar/Wind Harmer
2.831
203993AD2-133_GEN1
Solar/Wind Harmer
2.831
203961AE2-224 GEN
Solar/Wind Harmer
4.626
20091526CHSTN_FL
Solar/Wind Harmer
1.326
203804AE2-113_GEN
Solar/Wind Harmer
6.091
203850AG1-041 C
Solar/Wind Harmer
1.206
203844AF2-092 C
Solar/Wind Harmer
1.174
20092526R32
Solar/Wind Harmer
1.687
940863AE2-074 GEN
Solar/Wind Harmer
1.602
970555AG2-356 GEN
Solar/Wind Harmer
1.462
203846AF2-130 C
Solar/Wind Harmer
0.387
970663AG2-429 GEN
Solar/Wind Harmer
4.65
970663AG2-429 GEN
Solar/Wind Harmer
0.757
20083926HOMER C3
Adder
47.576
20083826HOMER C2
Adder
44.941
20083726HOMER C1
Adder
44.35
970677AG2-438 GEN
Solar/Wind Harmer
0.616
966771AG1-548 GEN
Solar/Wind Harmer
8.972
966771AG1-548 GEN
Solar/Wind Harmer
1.739
20084926LAKVU GN
Adder
0.118
20083226HNSMLK 5
Adder
3.386
203926AA2-133 GEN
Adder
1.277
20334726NME_Y1-047
Adder
1.074
LAGNLTFEXP_LAGN->PJM
CLTF
1.381
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.108
TVALTFEXP_TVA->PJM
CLTF
0.678
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.801
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.652
MECLTFEXP_MEC->PJM
CLTF
1.41
SIGELTFEXP_SIGE->PJM
CLTF
0.044
LGEELTFEXP_LGEE->PJM
CLTF
0.574
WECLTFEXP_WEC->PJM
CLTF
0.337
CPLELTFEXP_CPLE->PJM
CLTF
0.259
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.54
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.153

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:142.79 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:882.46
MW Contribution:6.02
Bus #Bus NameTypeMW Contribution
970643AG2-418 GEN
Solar/Wind Harmer
6.781
238202AE2-262_GEN
Solar/Wind Harmer
6.24
971627AH1-313 GEN
Solar/Wind Harmer
24.467
203854AF2-039 C
Solar/Wind Harmer
0.804
965131AG1-378 GEN
Solar/Wind Harmer
3.79
960051AF2-296 GEN
Solar/Wind Harmer
3.134
203818AF1-086 GEN
Solar/Wind Harmer
3.247
971703AH1-357 GEN
Solar/Wind Harmer
2.011
971707AH1-359 GEN
Solar/Wind Harmer
2.011
970125AG2-091 GEN
Solar/Wind Harmer
0.598
20120126WRREN CT
Adder
6.281
970899AG2-561 GEN
Solar/Wind Harmer
1.963
971879AH1-460 GEN
Solar/Wind Harmer
6.395
971541AH1-268 GEN
Solar/Wind Harmer
3.363
971419AH1-201 GEN
Solar/Wind Harmer
3.056
20079426CONEMAGH
Adder
1.155
203841AF2-001_GEN
Solar/Wind Harmer
1.865
20334926Z1-069 C
Solar/Wind Harmer
1.839
20335126GROZ1-110
Adder
2.027
20335226CANZ2-011
Adder
1.97
945751AF1-240 GEN
Solar/Wind Harmer
1.338
203932AE1-123
Adder
1.472
20089126CSLMN_L13
Solar/Wind Harmer
0.656
20089026BF_G21_K23
Solar/Wind Harmer
0.519
238219AF1-167 C
Solar/Wind Harmer
0.976
941421AE2-139 GEN
Solar/Wind Harmer
2.164
944411AF1-106 GEN
Solar/Wind Harmer
0.158
970335AG2-220 GEN
Solar/Wind Harmer
2.142
971127AH1-005 GEN
Solar/Wind Harmer
1.382
971185AH1-051 GEN
Solar/Wind Harmer
1.668
971355AH1-158 GEN
Solar/Wind Harmer
1.939
203856AF2-165 C
Solar/Wind Harmer
0.816
970647AG2-420 GEN
Solar/Wind Harmer
1.351
959441AF2-235 GEN
Solar/Wind Harmer
0.204
957161AF2-010 GEN
Solar/Wind Harmer
4.964
203830AF1-094 GEN
Solar/Wind Harmer
0.39
972271AH1-720 GEN
Adder
4.21
203948AG1-140 C
Solar/Wind Harmer
0.167
20082926HNSMLK 2
Adder
3.672
20083126HNSMLK 4
Adder
3.672
20328326MANOR_T86
Adder
0.089
20084926LAKVU GN
Adder
0.109
203962AF1-287 GEN
Solar/Wind Harmer
1.198
962511AG1-100 GEN
Solar/Wind Harmer
0.357
202652Y1-033 WT C
Solar/Wind Harmer
0.549
200917MEHOOPANY_G
Solar/Wind Harmer
1.57
20072226SHAWVL 2
50/50
30.97
20091326SHAW-D
50/50
1.372
20064926PENNTECH
50/50
0.428
970643AG2-418 GEN
Solar/Wind Harmer
3.154
238215AE2-248 C
Solar/Wind Harmer
4.803
964391AG1-301 GEN
Solar/Wind Harmer
1.711
203987AE2-118 C
Solar/Wind Harmer
5.15
238206AE2-263_GEN
Solar/Wind Harmer
5.816
972169AH1-667 GEN
Solar/Wind Harmer
3.54
203954AE2-126 C
Solar/Wind Harmer
1.067
957561AF2-050 GEN
Solar/Wind Harmer
8.182
964201AG1-281 GEN
Solar/Wind Harmer
0.934
238183AE2-316 GEN
Solar/Wind Harmer
5.355
20094526CT_V3-030
Solar/Wind Harmer
0.867
20088826HIGHLAND
Solar/Wind Harmer
1.817
970713AG2-456 GEN
Solar/Wind Harmer
8.043
971705AH1-358 GEN
Solar/Wind Harmer
2.338
971709AH1-360 GEN
Solar/Wind Harmer
2.338
971279AH1-102 GEN
Solar/Wind Harmer
7.901
970631AG2-411 GEN
Solar/Wind Harmer
6.024
971423AH1-203 GEN
Solar/Wind Harmer
6.528
203843AF2-002_GEN
Solar/Wind Harmer
0.933
20326126BLOSSBCT
Adder
1.852
20089226LOOKOUT
Solar/Wind Harmer
0.639
959471AF2-238 GEN
Solar/Wind Harmer
0.449
970337AG2-221 GEN
Solar/Wind Harmer
1.486
203835AF1-098 GEN
Solar/Wind Harmer
1.7
20335026MILZ1-092
Adder
1.592
944411AF1-106 GEN
Solar/Wind Harmer
1.467
970511AG2-327 GEN
Solar/Wind Harmer
0.69
971183AH1-050 GEN
Solar/Wind Harmer
2.779
970647AG2-420 GEN
Solar/Wind Harmer
0.157
203860AG1-193 C
Solar/Wind Harmer
0.194
20082826HNSMLK 1
Adder
3.672
20083026HNSMLK 3
Adder
3.672
20084926LAKVU GN
Adder
0.109
970267AG2-176 GEN
Solar/Wind Harmer
9.037
961971AG1-040 GEN
Solar/Wind Harmer
0.361
203813AE2-344_GEN
Solar/Wind Harmer
6.947
209067AE2-060 GEN
Solar/Wind Helper
0.091
20050326C.SLOPE
50/50
0.379
941231AE2-117 GEN
Solar/Wind Harmer
1.659
203855AF2-088 C
Solar/Wind Harmer
0.387
965121AG1-377 GEN
Solar/Wind Harmer
3.79
20090526Q36
Solar/Wind Harmer
2.856
203993AD2-133_GEN1
Solar/Wind Harmer
2.856
203975AE1-071-GEN
Solar/Wind Harmer
4.947
203961AE2-224 GEN
Solar/Wind Harmer
4.956
20091526CHSTN_FL
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
6.118
203850AG1-041 C
Solar/Wind Harmer
1.366
959381AF2-229 GEN
Solar/Wind Harmer
0.831
20092526R32
Solar/Wind Harmer
1.947
203844AF2-092 C
Solar/Wind Harmer
1.335
940863AE2-074 GEN
Solar/Wind Harmer
1.655
20087026C_T85_W218
Adder
0.509
20083726HOMER C1
Adder
53.523
20083926HOMER C3
Adder
54.511
20083826HOMER C2
Adder
51.492
970555AG2-356 GEN
Solar/Wind Harmer
1.486
203846AF2-130 C
Solar/Wind Harmer
0.411
970663AG2-429 GEN
Solar/Wind Harmer
4.882
970663AG2-429 GEN
Solar/Wind Harmer
0.795
970677AG2-438 GEN
Solar/Wind Harmer
0.643
966771AG1-548 GEN
Solar/Wind Harmer
9.367
966771AG1-548 GEN
Solar/Wind Harmer
1.815
20083226HNSMLK 5
Adder
3.672
20084926LAKVU GN
Adder
0.123
203926AA2-133 GEN
Adder
1.263
23732901CHBRG_I12
Adder
1.154
20334726NME_Y1-047
Adder
1.055
20081226ALY HYDR
50/50
0.403
20066626SHAWVL 4
50/50
2.36
20066526SHAWVL 3
50/50
2.343
20071526SHAWVL 1
50/50
1.595
216419AE2-001 C
Solar/Wind Harmer
5.846
203952AE2-129 C
Solar/Wind Harmer
1.148
203946AE2-131 C
Solar/Wind Harmer
1.146
962411AG1-090 GEN
Solar/Wind Harmer
18.003
20088626ARWF_N39
Solar/Wind Harmer
3.448
20303426NA_O38_P22
Solar/Wind Harmer
2.791
238217AF1-153 C O1
Solar/Wind Harmer
0.985
203853AF1-134 C O1
Solar/Wind Harmer
0.947
971441AH1-212 GEN
Solar/Wind Harmer
2.601
946381AF1-302 GEN
Solar/Wind Harmer
2.679
203940AF1-140 C
Solar/Wind Harmer
0.609
972075AH1-587 GEN
Solar/Wind Harmer
23.976
20390526W1-045 C
Solar/Wind Harmer
0.428
972077AH1-588 GEN
Solar/Wind Harmer
24.128
972079AH1-589 GEN
Solar/Wind Harmer
19.873
970715AG2-457 GEN
Solar/Wind Harmer
8.043
203857AF2-221 C
Solar/Wind Harmer
1.495
970123AG2-090 GEN
Solar/Wind Harmer
1.395
970305AG2-200 GEN
Solar/Wind Harmer
1.987
20088926STNY CRK
Solar/Wind Harmer
1.18
971427AH1-205 GEN
Solar/Wind Harmer
1.421
20084626FORWARD
Solar/Wind Harmer
0.756
203839AF1-321 GEN
Solar/Wind Harmer
1.865
203982AD2-062_GEN
Solar/Wind Harmer
7.157
20083426SW_E13_K22
Solar/Wind Harmer
0.259
946071AF1-272 GEN
Solar/Wind Harmer
2.555
944781AF1-143 GEN
Solar/Wind Harmer
2.249
20398826ARMNA MT
Solar/Wind Harmer
1.685
203848AF2-166 C
Solar/Wind Harmer
1.437
970313AG2-206 GEN
Solar/Wind Harmer
3.31
203979AG1-198 GEN
Solar/Wind Harmer
0.234
971933AH1-491 GEN
Solar/Wind Harmer
1.286
203963AG1-253 GEN
Solar/Wind Harmer
0.255
203859AF2-294 C
Solar/Wind Harmer
1.049
203980AG1-197 GEN
Solar/Wind Harmer
0.271
203947AF1-006 C
Solar/Wind Harmer
0.331
971931AH1-490 GEN
Solar/Wind Harmer
1.182
203955AF1-039 C O1
Solar/Wind Harmer
0.267
209137AF2-361 C
Solar/Wind Helper
1.538
LAGNLTFEXP_LAGN->PJM
CLTF
1.555
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.43
TVALTFEXP_TVA->PJM
CLTF
0.765
CBM West 1LTFEXP_CBM-W1->PJM
CBM
14.855
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.973
MECLTFEXP_MEC->PJM
CLTF
1.538
SIGELTFEXP_SIGE->PJM
CLTF
0.048
LGEELTFEXP_LGEE->PJM
CLTF
0.626
WECLTFEXP_WEC->PJM
CLTF
0.365
CPLELTFEXP_CPLE->PJM
CLTF
0.386
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.224
CBM West 2LTFEXP_CBM-W2->PJM
CBM
11.244

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-074_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-074_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.41 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:843.02
MW Contribution:4.79
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
30.209
20091326SHAW-D
50/50
1.324
20064926PENNTECH
50/50
0.409
200643SENECA#2
50/50
1.48
970643AG2-418 GEN
Solar/Wind Harmer
3.352
238215AE2-248 C
Solar/Wind Harmer
4.767
964391AG1-301 GEN
Solar/Wind Harmer
1.658
203987AE2-118 C
Solar/Wind Harmer
4.936
238206AE2-263_GEN
Solar/Wind Harmer
5.725
972169AH1-667 GEN
Solar/Wind Harmer
3.416
203954AE2-126 C
Solar/Wind Harmer
1.026
957561AF2-050 GEN
Solar/Wind Harmer
7.202
964201AG1-281 GEN
Solar/Wind Harmer
0.828
238183AE2-316 GEN
Solar/Wind Harmer
5.077
20094526CT_V3-030
Solar/Wind Harmer
0.748
970713AG2-456 GEN
Solar/Wind Harmer
7.335
971705AH1-358 GEN
Solar/Wind Harmer
2.132
971709AH1-360 GEN
Solar/Wind Harmer
2.132
20088826HIGHLAND
Solar/Wind Harmer
1.482
971279AH1-102 GEN
Solar/Wind Harmer
6.298
970631AG2-411 GEN
Solar/Wind Harmer
4.787
971423AH1-203 GEN
Solar/Wind Harmer
5.251
20326126BLOSSBCT
Adder
1.702
203843AF2-002_GEN
Solar/Wind Harmer
0.735
959471AF2-238 GEN
Solar/Wind Harmer
0.413
970337AG2-221 GEN
Solar/Wind Harmer
1.365
20087026C_T85_W218
50/50
0.852
200642SENECA#1
50/50
1.586
941231AE2-117 GEN
Solar/Wind Harmer
1.604
203975AE1-071-GEN
Solar/Wind Harmer
6.398
203855AF2-088 C
Solar/Wind Harmer
0.374
965121AG1-377 GEN
Solar/Wind Harmer
3.599
959381AF2-229 GEN
Solar/Wind Harmer
1.268
20090526Q36
Solar/Wind Harmer
2.673
203993AD2-133_GEN1
Solar/Wind Harmer
2.673
203961AE2-224 GEN
Solar/Wind Harmer
4.362
20091526CHSTN_FL
Solar/Wind Harmer
1.251
203804AE2-113_GEN
Solar/Wind Harmer
5.739
203850AG1-041 C
Solar/Wind Harmer
1.136
203844AF2-092 C
Solar/Wind Harmer
1.106
20092526R32
Solar/Wind Harmer
1.588
940863AE2-074 GEN
Solar/Wind Harmer
1.505
970555AG2-356 GEN
Solar/Wind Harmer
1.365
203846AF2-130 C
Solar/Wind Harmer
0.364
970663AG2-429 GEN
Solar/Wind Harmer
4.371
970663AG2-429 GEN
Solar/Wind Harmer
0.711
20083926HOMER C3
Adder
44.619
20083826HOMER C2
Adder
42.148
20083726HOMER C1
Adder
41.558
970677AG2-438 GEN
Solar/Wind Harmer
0.579
966771AG1-548 GEN
Solar/Wind Harmer
8.442
966771AG1-548 GEN
Solar/Wind Harmer
1.636
20084926LAKVU GN
Adder
0.111
20083226HNSMLK 5
Adder
3.182
203926AA2-133 GEN
Adder
1.181
200644SENECA#3
50/50
0.204
970643AG2-418 GEN
Solar/Wind Harmer
7.207
238202AE2-262_GEN
Solar/Wind Harmer
6.142
971627AH1-313 GEN
Solar/Wind Harmer
24.082
203854AF2-039 C
Solar/Wind Harmer
0.776
965131AG1-378 GEN
Solar/Wind Harmer
3.599
960051AF2-296 GEN
Solar/Wind Harmer
2.926
203818AF1-086 GEN
Solar/Wind Harmer
2.915
20120126WRREN CT
Adder
5.851
971703AH1-357 GEN
Solar/Wind Harmer
1.834
971707AH1-359 GEN
Solar/Wind Harmer
1.834
970899AG2-561 GEN
Solar/Wind Harmer
1.662
20335126GROZ1-110
Adder
1.915
20335226CANZ2-011
Adder
1.862
20334926Z1-069 C
Solar/Wind Harmer
1.666
970125AG2-091 GEN
Solar/Wind Harmer
0.474
971419AH1-201 GEN
Solar/Wind Harmer
2.471
971541AH1-268 GEN
Solar/Wind Harmer
2.68
971879AH1-460 GEN
Solar/Wind Harmer
5.058
945751AF1-240 GEN
Solar/Wind Harmer
1.16
203841AF2-001_GEN
Solar/Wind Harmer
1.469
20079426CONEMAGH
Adder
0.874
941421AE2-139 GEN
Solar/Wind Harmer
2.052
203932AE1-123
Adder
1.306
238219AF1-167 C
Solar/Wind Harmer
0.881
970335AG2-220 GEN
Solar/Wind Harmer
1.964
971127AH1-005 GEN
Solar/Wind Harmer
1.267
944411AF1-106 GEN
Solar/Wind Harmer
0.143
971185AH1-051 GEN
Solar/Wind Harmer
1.478
971355AH1-158 GEN
Solar/Wind Harmer
1.718
203856AF2-165 C
Solar/Wind Harmer
0.724
972271AH1-720 GEN
Adder
3.972
959441AF2-235 GEN
Solar/Wind Harmer
0.182
970647AG2-420 GEN
Solar/Wind Harmer
1.197
20089126CSLMN_L13
Solar/Wind Harmer
0.521
20089026BF_G21_K23
Solar/Wind Harmer
0.412
20328326MANOR_T86
Adder
0.083
957161AF2-010 GEN
Solar/Wind Harmer
4.468
203830AF1-094 GEN
Solar/Wind Harmer
0.351
203948AG1-140 C
Solar/Wind Harmer
0.152
20084926LAKVU GN
Adder
0.099
20082926HNSMLK 2
Adder
3.182
20083126HNSMLK 4
Adder
3.182
203962AF1-287 GEN
Solar/Wind Harmer
1.077
962511AG1-100 GEN
Solar/Wind Harmer
0.321
202652Y1-033 WT C
Solar/Wind Harmer
0.436
20081226ALY HYDR
50/50
0.393
20066626SHAWVL 4
50/50
2.302
20066526SHAWVL 3
50/50
2.285
20071526SHAWVL 1
50/50
1.548
216419AE2-001 C
Solar/Wind Harmer
5.796
203952AE2-129 C
Solar/Wind Harmer
1.09
203946AE2-131 C
Solar/Wind Harmer
1.088
962411AG1-090 GEN
Solar/Wind Harmer
17.095
20390526W1-045 C
Solar/Wind Harmer
0.653
203982AD2-062_GEN
Solar/Wind Harmer
14.042
20088626ARWF_N39
Solar/Wind Harmer
3.113
20303426NA_O38_P22
Solar/Wind Harmer
2.52
238217AF1-153 C O1
Solar/Wind Harmer
0.949
203853AF1-134 C O1
Solar/Wind Harmer
0.885
946381AF1-302 GEN
Solar/Wind Harmer
2.541
972075AH1-587 GEN
Solar/Wind Harmer
22.338
971441AH1-212 GEN
Solar/Wind Harmer
2.217
203940AF1-140 C
Solar/Wind Harmer
0.514
970305AG2-200 GEN
Solar/Wind Harmer
1.851
972077AH1-588 GEN
Solar/Wind Harmer
22.004
972079AH1-589 GEN
Solar/Wind Harmer
18.124
970715AG2-457 GEN
Solar/Wind Harmer
7.335
203857AF2-221 C
Solar/Wind Harmer
1.185
970123AG2-090 GEN
Solar/Wind Harmer
1.106
20088926STNY CRK
Solar/Wind Harmer
0.954
971427AH1-205 GEN
Solar/Wind Harmer
1.149
20084626FORWARD
Solar/Wind Harmer
0.601
203839AF1-321 GEN
Solar/Wind Harmer
1.469
20083426SW_E13_K22
Solar/Wind Harmer
0.206
20398826ARMNA MT
Solar/Wind Harmer
1.528
203848AF2-166 C
Solar/Wind Harmer
1.275
946071AF1-272 GEN
Solar/Wind Harmer
2.118
970313AG2-206 GEN
Solar/Wind Harmer
3.036
944781AF1-143 GEN
Solar/Wind Harmer
1.786
203979AG1-198 GEN
Solar/Wind Harmer
0.211
971933AH1-491 GEN
Solar/Wind Harmer
1.158
203963AG1-253 GEN
Solar/Wind Harmer
0.231
203859AF2-294 C
Solar/Wind Harmer
0.949
203947AF1-006 C
Solar/Wind Harmer
0.3
203980AG1-197 GEN
Solar/Wind Harmer
0.242
971931AH1-490 GEN
Solar/Wind Harmer
1.061
203955AF1-039 C O1
Solar/Wind Harmer
0.212
209137AF2-361 C
Solar/Wind Helper
1.486
203835AF1-098 GEN
Solar/Wind Harmer
1.553
20335026MILZ1-092
Adder
1.442
944411AF1-106 GEN
Solar/Wind Harmer
1.329
970511AG2-327 GEN
Solar/Wind Harmer
0.632
971183AH1-050 GEN
Solar/Wind Harmer
2.463
970647AG2-420 GEN
Solar/Wind Harmer
0.139
20089226LOOKOUT
Solar/Wind Harmer
0.507
20084926LAKVU GN
Adder
0.099
203860AG1-193 C
Solar/Wind Harmer
0.171
20082826HNSMLK 1
Adder
3.182
20083026HNSMLK 3
Adder
3.182
203813AE2-344_GEN
Solar/Wind Harmer
6.244
970267AG2-176 GEN
Solar/Wind Harmer
8.019
961971AG1-040 GEN
Solar/Wind Harmer
0.323
209067AE2-060 GEN
Solar/Wind Helper
0.088
LAGNLTFEXP_LAGN->PJM
CLTF
1.368
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.174
TVALTFEXP_TVA->PJM
CLTF
0.672
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.369
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.621
MECLTFEXP_MEC->PJM
CLTF
1.376
SIGELTFEXP_SIGE->PJM
CLTF
0.043
LGEELTFEXP_LGEE->PJM
CLTF
0.56
WECLTFEXP_WEC->PJM
CLTF
0.328
CPLELTFEXP_CPLE->PJM
CLTF
0.296
CBM NorthLTFEXP_CBM-N->PJM
CBM
1.695
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.976

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_08_P22_102799_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_08_P22_102799_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:136.19 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:841.64
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
200642SENECA#1
50/50
1.549
941231AE2-117 GEN
Solar/Wind Harmer
1.569
203855AF2-088 C
Solar/Wind Harmer
0.365
965121AG1-377 GEN
Solar/Wind Harmer
3.518
203975AE1-071-GEN
Solar/Wind Harmer
4.874
20090526Q36
Solar/Wind Harmer
2.613
203993AD2-133_GEN1
Solar/Wind Harmer
2.613
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
6.674
238202AE2-262_GEN
Solar/Wind Harmer
6.009
971627AH1-313 GEN
Solar/Wind Harmer
23.56
203854AF2-039 C
Solar/Wind Harmer
0.759
965131AG1-378 GEN
Solar/Wind Harmer
3.518
960051AF2-296 GEN
Solar/Wind Harmer
2.859
203818AF1-086 GEN
Solar/Wind Harmer
2.845
20120126WRREN CT
Adder
5.712
971703AH1-357 GEN
Solar/Wind Harmer
1.787
971707AH1-359 GEN
Solar/Wind Harmer
1.787
970899AG2-561 GEN
Solar/Wind Harmer
1.619
20335126GROZ1-110
Adder
1.853
20335226CANZ2-011
Adder
1.802
20334926Z1-069 C
Solar/Wind Harmer
1.619
970125AG2-091 GEN
Solar/Wind Harmer
0.462
971419AH1-201 GEN
Solar/Wind Harmer
2.411
971541AH1-268 GEN
Solar/Wind Harmer
2.609
971879AH1-460 GEN
Solar/Wind Harmer
4.928
945751AF1-240 GEN
Solar/Wind Harmer
1.13
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.251
20066526SHAWVL 3
50/50
2.235
20071526SHAWVL 1
50/50
1.514
216419AE2-001 C
Solar/Wind Harmer
5.673
203952AE2-129 C
Solar/Wind Harmer
1.065
203946AE2-131 C
Solar/Wind Harmer
1.064
962411AG1-090 GEN
Solar/Wind Harmer
16.711
20088626ARWF_N39
Solar/Wind Harmer
3.041
20303426NA_O38_P22
Solar/Wind Harmer
2.462
238217AF1-153 C O1
Solar/Wind Harmer
0.927
203853AF1-134 C O1
Solar/Wind Harmer
0.864
946381AF1-302 GEN
Solar/Wind Harmer
2.482
20390526W1-045 C
Solar/Wind Harmer
0.422
972075AH1-587 GEN
Solar/Wind Harmer
21.795
971441AH1-212 GEN
Solar/Wind Harmer
2.163
203940AF1-140 C
Solar/Wind Harmer
0.502
970305AG2-200 GEN
Solar/Wind Harmer
1.807
972077AH1-588 GEN
Solar/Wind Harmer
21.45
972079AH1-589 GEN
Solar/Wind Harmer
17.667
970715AG2-457 GEN
Solar/Wind Harmer
7.15
203982AD2-062_GEN
Solar/Wind Harmer
7.066
203857AF2-221 C
Solar/Wind Harmer
1.155
203961AE2-224 GEN
Solar/Wind Harmer
4.26
20091526CHSTN_FL
Solar/Wind Harmer
1.222
203804AE2-113_GEN
Solar/Wind Harmer
5.601
959381AF2-229 GEN
Solar/Wind Harmer
0.82
203850AG1-041 C
Solar/Wind Harmer
1.108
203844AF2-092 C
Solar/Wind Harmer
1.079
20092526R32
Solar/Wind Harmer
1.548
940863AE2-074 GEN
Solar/Wind Harmer
1.465
20087026C_T85_W218
Adder
0.503
970555AG2-356 GEN
Solar/Wind Harmer
1.318
203846AF2-130 C
Solar/Wind Harmer
0.355
970663AG2-429 GEN
Solar/Wind Harmer
4.26
970663AG2-429 GEN
Solar/Wind Harmer
0.693
20083926HOMER C3
Adder
43.363
20083826HOMER C2
Adder
40.962
20083726HOMER C1
Adder
40.346
970677AG2-438 GEN
Solar/Wind Harmer
0.565
966771AG1-548 GEN
Solar/Wind Harmer
8.24
966771AG1-548 GEN
Solar/Wind Harmer
1.597
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.101
203926AA2-133 GEN
Adder
1.127
23732901CHBRG_I12
Adder
1.143
20072226SHAWVL 2
50/50
29.543
20091326SHAW-D
50/50
1.294
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.445
970643AG2-418 GEN
Solar/Wind Harmer
3.104
238215AE2-248 C
Solar/Wind Harmer
4.666
964391AG1-301 GEN
Solar/Wind Harmer
1.622
203987AE2-118 C
Solar/Wind Harmer
4.828
238206AE2-263_GEN
Solar/Wind Harmer
5.6
972169AH1-667 GEN
Solar/Wind Harmer
3.34
203954AE2-126 C
Solar/Wind Harmer
1.002
957561AF2-050 GEN
Solar/Wind Harmer
7.033
964201AG1-281 GEN
Solar/Wind Harmer
0.809
238183AE2-316 GEN
Solar/Wind Harmer
4.96
20094526CT_V3-030
Solar/Wind Harmer
0.729
970713AG2-456 GEN
Solar/Wind Harmer
7.15
971705AH1-358 GEN
Solar/Wind Harmer
2.078
971709AH1-360 GEN
Solar/Wind Harmer
2.078
20088826HIGHLAND
Solar/Wind Harmer
1.444
971279AH1-102 GEN
Solar/Wind Harmer
6.131
970631AG2-411 GEN
Solar/Wind Harmer
4.665
971423AH1-203 GEN
Solar/Wind Harmer
5.124
20326126BLOSSBCT
Adder
1.647
203843AF2-002_GEN
Solar/Wind Harmer
0.716
959471AF2-238 GEN
Solar/Wind Harmer
0.399
970337AG2-221 GEN
Solar/Wind Harmer
1.318
203835AF1-098 GEN
Solar/Wind Harmer
1.516
20335026MILZ1-092
Adder
1.392
944411AF1-106 GEN
Solar/Wind Harmer
1.283
970511AG2-327 GEN
Solar/Wind Harmer
0.61
971183AH1-050 GEN
Solar/Wind Harmer
2.402
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.497
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
3.101
20083026HNSMLK 3
Adder
3.101
203813AE2-344_GEN
Solar/Wind Harmer
6.096
970267AG2-176 GEN
Solar/Wind Harmer
7.824
961971AG1-040 GEN
Solar/Wind Harmer
0.315
209067AE2-060 GEN
Solar/Wind Helper
0.091
203841AF2-001_GEN
Solar/Wind Harmer
1.431
20079426CONEMAGH
Adder
0.85
941421AE2-139 GEN
Solar/Wind Harmer
1.976
203932AE1-123
Adder
1.274
238219AF1-167 C
Solar/Wind Harmer
0.859
944411AF1-106 GEN
Solar/Wind Harmer
0.138
970335AG2-220 GEN
Solar/Wind Harmer
1.893
971127AH1-005 GEN
Solar/Wind Harmer
1.221
971185AH1-051 GEN
Solar/Wind Harmer
1.441
971355AH1-158 GEN
Solar/Wind Harmer
1.675
203856AF2-165 C
Solar/Wind Harmer
0.706
959441AF2-235 GEN
Solar/Wind Harmer
0.177
970647AG2-420 GEN
Solar/Wind Harmer
1.167
972271AH1-720 GEN
Adder
3.813
20089126CSLMN_L13
Solar/Wind Harmer
0.51
20089026BF_G21_K23
Solar/Wind Harmer
0.404
957161AF2-010 GEN
Solar/Wind Harmer
4.361
203830AF1-094 GEN
Solar/Wind Harmer
0.342
203948AG1-140 C
Solar/Wind Harmer
0.148
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.101
20083126HNSMLK 4
Adder
3.101
203962AF1-287 GEN
Solar/Wind Harmer
1.052
962511AG1-100 GEN
Solar/Wind Harmer
0.313
202652Y1-033 WT C
Solar/Wind Harmer
0.43
970123AG2-090 GEN
Solar/Wind Harmer
1.078
20088926STNY CRK
Solar/Wind Harmer
0.931
971427AH1-205 GEN
Solar/Wind Harmer
1.122
20084626FORWARD
Solar/Wind Harmer
0.585
203839AF1-321 GEN
Solar/Wind Harmer
1.431
20083426SW_E13_K22
Solar/Wind Harmer
0.201
20398826ARMNA MT
Solar/Wind Harmer
1.476
203848AF2-166 C
Solar/Wind Harmer
1.243
946071AF1-272 GEN
Solar/Wind Harmer
2.06
970313AG2-206 GEN
Solar/Wind Harmer
2.926
944781AF1-143 GEN
Solar/Wind Harmer
1.749
203979AG1-198 GEN
Solar/Wind Harmer
0.205
971933AH1-491 GEN
Solar/Wind Harmer
1.131
203963AG1-253 GEN
Solar/Wind Harmer
0.226
203859AF2-294 C
Solar/Wind Harmer
0.913
203947AF1-006 C
Solar/Wind Harmer
0.292
203980AG1-197 GEN
Solar/Wind Harmer
0.236
971931AH1-490 GEN
Solar/Wind Harmer
1.036
203955AF1-039 C O1
Solar/Wind Harmer
0.209
209137AF2-361 C
Solar/Wind Helper
1.536
LAGNLTFEXP_LAGN->PJM
CLTF
1.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.327
TVALTFEXP_TVA->PJM
CLTF
0.707
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.667
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.747
MECLTFEXP_MEC->PJM
CLTF
1.419
SIGELTFEXP_SIGE->PJM
CLTF
0.044
LGEELTFEXP_LGEE->PJM
CLTF
0.578
WECLTFEXP_WEC->PJM
CLTF
0.337
CPLELTFEXP_CPLE->PJM
CLTF
0.359
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.762
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.382

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_48_P71_102649_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_48_P71_102649_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.55 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:837.69
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.251
20066526SHAWVL 3
50/50
2.235
20071526SHAWVL 1
50/50
1.514
216419AE2-001 C
Solar/Wind Harmer
5.673
203952AE2-129 C
Solar/Wind Harmer
1.066
203946AE2-131 C
Solar/Wind Harmer
1.064
962411AG1-090 GEN
Solar/Wind Harmer
16.713
20088626ARWF_N39
Solar/Wind Harmer
3.042
20303426NA_O38_P22
Solar/Wind Harmer
2.463
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203853AF1-134 C O1
Solar/Wind Harmer
0.864
946381AF1-302 GEN
Solar/Wind Harmer
2.482
20072226SHAWVL 2
50/50
29.547
20091326SHAW-D
50/50
1.294
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.445
970643AG2-418 GEN
Solar/Wind Harmer
3.105
238215AE2-248 C
Solar/Wind Harmer
4.666
964391AG1-301 GEN
Solar/Wind Harmer
1.622
203987AE2-118 C
Solar/Wind Harmer
4.829
238206AE2-263_GEN
Solar/Wind Harmer
5.601
972169AH1-667 GEN
Solar/Wind Harmer
3.341
203954AE2-126 C
Solar/Wind Harmer
1.003
957561AF2-050 GEN
Solar/Wind Harmer
7.034
964201AG1-281 GEN
Solar/Wind Harmer
0.809
238183AE2-316 GEN
Solar/Wind Harmer
4.961
20094526CT_V3-030
Solar/Wind Harmer
0.73
970713AG2-456 GEN
Solar/Wind Harmer
7.152
971705AH1-358 GEN
Solar/Wind Harmer
2.079
971709AH1-360 GEN
Solar/Wind Harmer
2.079
20088826HIGHLAND
Solar/Wind Harmer
1.445
971279AH1-102 GEN
Solar/Wind Harmer
6.133
970631AG2-411 GEN
Solar/Wind Harmer
4.666
971423AH1-203 GEN
Solar/Wind Harmer
5.126
20326126BLOSSBCT
Adder
1.648
203843AF2-002_GEN
Solar/Wind Harmer
0.716
959471AF2-238 GEN
Solar/Wind Harmer
0.399
970337AG2-221 GEN
Solar/Wind Harmer
1.319
203835AF1-098 GEN
Solar/Wind Harmer
1.517
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
6.675
238202AE2-262_GEN
Solar/Wind Harmer
6.009
971627AH1-313 GEN
Solar/Wind Harmer
23.562
203854AF2-039 C
Solar/Wind Harmer
0.759
965131AG1-378 GEN
Solar/Wind Harmer
3.519
960051AF2-296 GEN
Solar/Wind Harmer
2.859
203818AF1-086 GEN
Solar/Wind Harmer
2.846
20120126WRREN CT
Adder
5.714
971703AH1-357 GEN
Solar/Wind Harmer
1.788
971707AH1-359 GEN
Solar/Wind Harmer
1.788
970899AG2-561 GEN
Solar/Wind Harmer
1.62
20335126GROZ1-110
Adder
1.854
20335226CANZ2-011
Adder
1.802
20334926Z1-069 C
Solar/Wind Harmer
1.619
970125AG2-091 GEN
Solar/Wind Harmer
0.462
971419AH1-201 GEN
Solar/Wind Harmer
2.412
971541AH1-268 GEN
Solar/Wind Harmer
2.61
971879AH1-460 GEN
Solar/Wind Harmer
4.929
945751AF1-240 GEN
Solar/Wind Harmer
1.13
203841AF2-001_GEN
Solar/Wind Harmer
1.432
20079426CONEMAGH
Adder
0.85
941421AE2-139 GEN
Solar/Wind Harmer
1.977
203932AE1-123
Adder
1.274
238219AF1-167 C
Solar/Wind Harmer
0.859
200642SENECA#1
50/50
1.549
941231AE2-117 GEN
Solar/Wind Harmer
1.57
203855AF2-088 C
Solar/Wind Harmer
0.365
965121AG1-377 GEN
Solar/Wind Harmer
3.519
203975AE1-071-GEN
Solar/Wind Harmer
4.875
20090526Q36
Solar/Wind Harmer
2.613
203993AD2-133_GEN1
Solar/Wind Harmer
2.613
203961AE2-224 GEN
Solar/Wind Harmer
4.261
20091526CHSTN_FL
Solar/Wind Harmer
1.222
203804AE2-113_GEN
Solar/Wind Harmer
5.603
959381AF2-229 GEN
Solar/Wind Harmer
0.82
203850AG1-041 C
Solar/Wind Harmer
1.109
203844AF2-092 C
Solar/Wind Harmer
1.079
20092526R32
Solar/Wind Harmer
1.548
940863AE2-074 GEN
Solar/Wind Harmer
1.465
20087026C_T85_W218
Adder
0.503
970555AG2-356 GEN
Solar/Wind Harmer
1.319
203846AF2-130 C
Solar/Wind Harmer
0.355
970663AG2-429 GEN
Solar/Wind Harmer
4.261
970663AG2-429 GEN
Solar/Wind Harmer
0.694
20083926HOMER C3
Adder
43.379
20083826HOMER C2
Adder
40.977
20083726HOMER C1
Adder
40.361
970677AG2-438 GEN
Solar/Wind Harmer
0.566
966771AG1-548 GEN
Solar/Wind Harmer
8.243
966771AG1-548 GEN
Solar/Wind Harmer
1.597
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.102
203926AA2-133 GEN
Adder
1.128
23732901CHBRG_I12
Adder
1.144
20390526W1-045 C
Solar/Wind Harmer
0.423
972075AH1-587 GEN
Solar/Wind Harmer
21.8
971441AH1-212 GEN
Solar/Wind Harmer
2.163
203940AF1-140 C
Solar/Wind Harmer
0.502
970305AG2-200 GEN
Solar/Wind Harmer
1.807
972077AH1-588 GEN
Solar/Wind Harmer
21.455
972079AH1-589 GEN
Solar/Wind Harmer
17.672
970715AG2-457 GEN
Solar/Wind Harmer
7.152
203982AD2-062_GEN
Solar/Wind Harmer
7.067
203857AF2-221 C
Solar/Wind Harmer
1.155
970123AG2-090 GEN
Solar/Wind Harmer
1.078
20088926STNY CRK
Solar/Wind Harmer
0.931
971427AH1-205 GEN
Solar/Wind Harmer
1.122
20084626FORWARD
Solar/Wind Harmer
0.586
203839AF1-321 GEN
Solar/Wind Harmer
1.432
20083426SW_E13_K22
Solar/Wind Harmer
0.201
20398826ARMNA MT
Solar/Wind Harmer
1.477
203848AF2-166 C
Solar/Wind Harmer
1.244
946071AF1-272 GEN
Solar/Wind Harmer
2.061
944411AF1-106 GEN
Solar/Wind Harmer
0.138
970335AG2-220 GEN
Solar/Wind Harmer
1.894
971127AH1-005 GEN
Solar/Wind Harmer
1.222
971185AH1-051 GEN
Solar/Wind Harmer
1.441
971355AH1-158 GEN
Solar/Wind Harmer
1.676
203856AF2-165 C
Solar/Wind Harmer
0.706
959441AF2-235 GEN
Solar/Wind Harmer
0.177
970647AG2-420 GEN
Solar/Wind Harmer
1.168
972271AH1-720 GEN
Adder
3.815
20089126CSLMN_L13
Solar/Wind Harmer
0.511
20089026BF_G21_K23
Solar/Wind Harmer
0.404
957161AF2-010 GEN
Solar/Wind Harmer
4.362
203830AF1-094 GEN
Solar/Wind Harmer
0.343
203948AG1-140 C
Solar/Wind Harmer
0.148
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.102
20083126HNSMLK 4
Adder
3.102
203962AF1-287 GEN
Solar/Wind Harmer
1.052
962511AG1-100 GEN
Solar/Wind Harmer
0.313
202652Y1-033 WT C
Solar/Wind Harmer
0.43
20335026MILZ1-092
Adder
1.393
944411AF1-106 GEN
Solar/Wind Harmer
1.283
970511AG2-327 GEN
Solar/Wind Harmer
0.61
971183AH1-050 GEN
Solar/Wind Harmer
2.402
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.497
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
3.102
20083026HNSMLK 3
Adder
3.102
203813AE2-344_GEN
Solar/Wind Harmer
6.098
970267AG2-176 GEN
Solar/Wind Harmer
7.827
961971AG1-040 GEN
Solar/Wind Harmer
0.315
209067AE2-060 GEN
Solar/Wind Helper
0.091
970313AG2-206 GEN
Solar/Wind Harmer
2.928
944781AF1-143 GEN
Solar/Wind Harmer
1.75
203979AG1-198 GEN
Solar/Wind Harmer
0.206
971933AH1-491 GEN
Solar/Wind Harmer
1.131
203963AG1-253 GEN
Solar/Wind Harmer
0.226
203859AF2-294 C
Solar/Wind Harmer
0.913
203947AF1-006 C
Solar/Wind Harmer
0.293
203980AG1-197 GEN
Solar/Wind Harmer
0.236
971931AH1-490 GEN
Solar/Wind Harmer
1.036
203955AF1-039 C O1
Solar/Wind Harmer
0.209
209137AF2-361 C
Solar/Wind Helper
1.535
LAGNLTFEXP_LAGN->PJM
CLTF
1.441
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.334
TVALTFEXP_TVA->PJM
CLTF
0.71
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.7
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.755
MECLTFEXP_MEC->PJM
CLTF
1.422
SIGELTFEXP_SIGE->PJM
CLTF
0.044
LGEELTFEXP_LGEE->PJM
CLTF
0.579
WECLTFEXP_WEC->PJM
CLTF
0.338
CPLELTFEXP_CPLE->PJM
CLTF
0.361
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.779
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.412

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PECO_P7-1_220-9091_SRT-A/* $ BUCKS $ PECO_P7-1_220-9091 $ DCT
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:135.09 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:834.83
MW Contribution:4.67
Bus #Bus NameTypeMW Contribution
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
6.676
238202AE2-262_GEN
Solar/Wind Harmer
6.01
971627AH1-313 GEN
Solar/Wind Harmer
23.565
203854AF2-039 C
Solar/Wind Harmer
0.759
965131AG1-378 GEN
Solar/Wind Harmer
3.519
960051AF2-296 GEN
Solar/Wind Harmer
2.86
203818AF1-086 GEN
Solar/Wind Harmer
2.846
20120126WRREN CT
Adder
5.716
971703AH1-357 GEN
Solar/Wind Harmer
1.789
971707AH1-359 GEN
Solar/Wind Harmer
1.789
970899AG2-561 GEN
Solar/Wind Harmer
1.62
20335126GROZ1-110
Adder
1.855
20335226CANZ2-011
Adder
1.803
20334926Z1-069 C
Solar/Wind Harmer
1.62
970125AG2-091 GEN
Solar/Wind Harmer
0.462
971419AH1-201 GEN
Solar/Wind Harmer
2.413
971541AH1-268 GEN
Solar/Wind Harmer
2.611
971879AH1-460 GEN
Solar/Wind Harmer
4.931
945751AF1-240 GEN
Solar/Wind Harmer
1.131
203841AF2-001_GEN
Solar/Wind Harmer
1.432
20079426CONEMAGH
Adder
0.851
941421AE2-139 GEN
Solar/Wind Harmer
1.977
203932AE1-123
Adder
1.275
238219AF1-167 C
Solar/Wind Harmer
0.859
944411AF1-106 GEN
Solar/Wind Harmer
0.138
970335AG2-220 GEN
Solar/Wind Harmer
1.895
971127AH1-005 GEN
Solar/Wind Harmer
1.222
971185AH1-051 GEN
Solar/Wind Harmer
1.442
971355AH1-158 GEN
Solar/Wind Harmer
1.677
203856AF2-165 C
Solar/Wind Harmer
0.706
959441AF2-235 GEN
Solar/Wind Harmer
0.177
970647AG2-420 GEN
Solar/Wind Harmer
1.168
972271AH1-720 GEN
Adder
3.817
20089126CSLMN_L13
Solar/Wind Harmer
0.511
20089026BF_G21_K23
Solar/Wind Harmer
0.404
957161AF2-010 GEN
Solar/Wind Harmer
4.365
203830AF1-094 GEN
Solar/Wind Harmer
0.343
203948AG1-140 C
Solar/Wind Harmer
0.148
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.104
20083126HNSMLK 4
Adder
3.104
203962AF1-287 GEN
Solar/Wind Harmer
1.053
962511AG1-100 GEN
Solar/Wind Harmer
0.313
202652Y1-033 WT C
Solar/Wind Harmer
0.43
200642SENECA#1
50/50
1.55
941231AE2-117 GEN
Solar/Wind Harmer
1.57
203855AF2-088 C
Solar/Wind Harmer
0.365
965121AG1-377 GEN
Solar/Wind Harmer
3.519
203975AE1-071-GEN
Solar/Wind Harmer
4.876
20090526Q36
Solar/Wind Harmer
2.614
203993AD2-133_GEN1
Solar/Wind Harmer
2.614
203961AE2-224 GEN
Solar/Wind Harmer
4.262
20091526CHSTN_FL
Solar/Wind Harmer
1.222
203804AE2-113_GEN
Solar/Wind Harmer
5.604
959381AF2-229 GEN
Solar/Wind Harmer
0.82
203850AG1-041 C
Solar/Wind Harmer
1.109
203844AF2-092 C
Solar/Wind Harmer
1.08
20092526R32
Solar/Wind Harmer
1.549
940863AE2-074 GEN
Solar/Wind Harmer
1.466
20087026C_T85_W218
Adder
0.503
970555AG2-356 GEN
Solar/Wind Harmer
1.32
203846AF2-130 C
Solar/Wind Harmer
0.356
970663AG2-429 GEN
Solar/Wind Harmer
4.263
970663AG2-429 GEN
Solar/Wind Harmer
0.694
20083926HOMER C3
Adder
43.401
20083826HOMER C2
Adder
40.997
20083726HOMER C1
Adder
40.382
970677AG2-438 GEN
Solar/Wind Harmer
0.566
966771AG1-548 GEN
Solar/Wind Harmer
8.247
966771AG1-548 GEN
Solar/Wind Harmer
1.598
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.104
203926AA2-133 GEN
Adder
1.129
23732901CHBRG_I12
Adder
1.144
20072226SHAWVL 2
50/50
29.551
20091326SHAW-D
50/50
1.295
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.446
970643AG2-418 GEN
Solar/Wind Harmer
3.105
238215AE2-248 C
Solar/Wind Harmer
4.667
964391AG1-301 GEN
Solar/Wind Harmer
1.623
203987AE2-118 C
Solar/Wind Harmer
4.829
238206AE2-263_GEN
Solar/Wind Harmer
5.602
972169AH1-667 GEN
Solar/Wind Harmer
3.341
203954AE2-126 C
Solar/Wind Harmer
1.003
957561AF2-050 GEN
Solar/Wind Harmer
7.035
964201AG1-281 GEN
Solar/Wind Harmer
0.809
238183AE2-316 GEN
Solar/Wind Harmer
4.962
20094526CT_V3-030
Solar/Wind Harmer
0.73
970713AG2-456 GEN
Solar/Wind Harmer
7.154
971705AH1-358 GEN
Solar/Wind Harmer
2.08
971709AH1-360 GEN
Solar/Wind Harmer
2.08
20088826HIGHLAND
Solar/Wind Harmer
1.445
971279AH1-102 GEN
Solar/Wind Harmer
6.136
970631AG2-411 GEN
Solar/Wind Harmer
4.668
971423AH1-203 GEN
Solar/Wind Harmer
5.128
20326126BLOSSBCT
Adder
1.648
203843AF2-002_GEN
Solar/Wind Harmer
0.716
959471AF2-238 GEN
Solar/Wind Harmer
0.399
970337AG2-221 GEN
Solar/Wind Harmer
1.32
203835AF1-098 GEN
Solar/Wind Harmer
1.517
20335026MILZ1-092
Adder
1.394
944411AF1-106 GEN
Solar/Wind Harmer
1.284
970511AG2-327 GEN
Solar/Wind Harmer
0.61
971183AH1-050 GEN
Solar/Wind Harmer
2.404
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.497
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0.167
20082826HNSMLK 1
Adder
3.104
20083026HNSMLK 3
Adder
3.104
203813AE2-344_GEN
Solar/Wind Harmer
6.102
970267AG2-176 GEN
Solar/Wind Harmer
7.832
961971AG1-040 GEN
Solar/Wind Harmer
0.315
209067AE2-060 GEN
Solar/Wind Helper
0.091
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.252
20066526SHAWVL 3
50/50
2.235
20071526SHAWVL 1
50/50
1.514
216419AE2-001 C
Solar/Wind Harmer
5.674
203952AE2-129 C
Solar/Wind Harmer
1.066
203946AE2-131 C
Solar/Wind Harmer
1.064
962411AG1-090 GEN
Solar/Wind Harmer
16.716
20088626ARWF_N39
Solar/Wind Harmer
3.042
20303426NA_O38_P22
Solar/Wind Harmer
2.463
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203853AF1-134 C O1
Solar/Wind Harmer
0.865
946381AF1-302 GEN
Solar/Wind Harmer
2.483
20390526W1-045 C
Solar/Wind Harmer
0.423
972075AH1-587 GEN
Solar/Wind Harmer
21.806
971441AH1-212 GEN
Solar/Wind Harmer
2.164
203940AF1-140 C
Solar/Wind Harmer
0.502
970305AG2-200 GEN
Solar/Wind Harmer
1.808
972077AH1-588 GEN
Solar/Wind Harmer
21.463
972079AH1-589 GEN
Solar/Wind Harmer
17.678
970715AG2-457 GEN
Solar/Wind Harmer
7.154
203982AD2-062_GEN
Solar/Wind Harmer
7.07
203857AF2-221 C
Solar/Wind Harmer
1.155
970123AG2-090 GEN
Solar/Wind Harmer
1.078
20088926STNY CRK
Solar/Wind Harmer
0.932
971427AH1-205 GEN
Solar/Wind Harmer
1.122
20084626FORWARD
Solar/Wind Harmer
0.586
203839AF1-321 GEN
Solar/Wind Harmer
1.432
20083426SW_E13_K22
Solar/Wind Harmer
0.201
20398826ARMNA MT
Solar/Wind Harmer
1.478
203848AF2-166 C
Solar/Wind Harmer
1.245
946071AF1-272 GEN
Solar/Wind Harmer
2.062
970313AG2-206 GEN
Solar/Wind Harmer
2.929
944781AF1-143 GEN
Solar/Wind Harmer
1.751
203979AG1-198 GEN
Solar/Wind Harmer
0.206
971933AH1-491 GEN
Solar/Wind Harmer
1.132
203963AG1-253 GEN
Solar/Wind Harmer
0.226
203859AF2-294 C
Solar/Wind Harmer
0.914
203947AF1-006 C
Solar/Wind Harmer
0.293
203980AG1-197 GEN
Solar/Wind Harmer
0.236
971931AH1-490 GEN
Solar/Wind Harmer
1.037
203955AF1-039 C O1
Solar/Wind Harmer
0.209
209137AF2-361 C
Solar/Wind Helper
1.535
LAGNLTFEXP_LAGN->PJM
CLTF
1.448
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.343
TVALTFEXP_TVA->PJM
CLTF
0.713
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.745
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.767
MECLTFEXP_MEC->PJM
CLTF
1.428
SIGELTFEXP_SIGE->PJM
CLTF
0.044
LGEELTFEXP_LGEE->PJM
CLTF
0.581
WECLTFEXP_WEC->PJM
CLTF
0.339
CPLELTFEXP_CPLE->PJM
CLTF
0.365
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.792
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.454

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:493.0 MVA
Rating Type:A
MVA to Mitigate:649.4
MW Contribution:3.51
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
29.573
20091326SHAW-D
50/50
1.296
20064926PENNTECH
50/50
0.4
200643SENECA#2
50/50
1.448
970643AG2-418 GEN
Solar/Wind Harmer
3.106
238215AE2-248 C
Solar/Wind Harmer
3.258
203987AE2-118 C
Solar/Wind Harmer
3.371
238206AE2-263_GEN
Solar/Wind Harmer
0.01
972169AH1-667 GEN
Solar/Wind Harmer
2.333
203954AE2-126 C
Solar/Wind Harmer
0.002
957561AF2-050 GEN
Solar/Wind Harmer
4.914
238183AE2-316 GEN
Solar/Wind Harmer
0.004
20094526CT_V3-030
Solar/Wind Harmer
0.122
970713AG2-456 GEN
Solar/Wind Harmer
5.812
971705AH1-358 GEN
Solar/Wind Harmer
2.083
971709AH1-360 GEN
Solar/Wind Harmer
2.083
20088826HIGHLAND
Solar/Wind Harmer
0.001
971279AH1-102 GEN
Solar/Wind Harmer
5.556
970631AG2-411 GEN
Solar/Wind Harmer
3.514
971423AH1-203 GEN
Solar/Wind Harmer
3.585
20326126BLOSSBCT
Adder
1.652
203843AF2-002_GEN
Solar/Wind Harmer
0.501
970337AG2-221 GEN
Solar/Wind Harmer
1.015
203835AF1-098 GEN
Solar/Wind Harmer
0.003
20335026MILZ1-092
Adder
1.397
944411AF1-106 GEN
Solar/Wind Harmer
1.425
970511AG2-327 GEN
Solar/Wind Harmer
0.427
971183AH1-050 GEN
Solar/Wind Harmer
2.076
970647AG2-420 GEN
Solar/Wind Harmer
0.136
20089226LOOKOUT
Solar/Wind Harmer
0.077
20084926LAKVU GN
Adder
0.097
203860AG1-193 C
Solar/Wind Harmer
0
20082826HNSMLK 1
Adder
3.113
20083026HNSMLK 3
Adder
3.113
203813AE2-344_GEN
Solar/Wind Harmer
4.269
970267AG2-176 GEN
Solar/Wind Harmer
5.48
209067AE2-060 GEN
Solar/Wind Helper
0.091
200644SENECA#3
50/50
0.199
970643AG2-418 GEN
Solar/Wind Harmer
4.659
238202AE2-262_GEN
Solar/Wind Harmer
0.01
971627AH1-313 GEN
Solar/Wind Harmer
16.451
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.229
960051AF2-296 GEN
Solar/Wind Harmer
1.997
203818AF1-086 GEN
Solar/Wind Harmer
0.67
972323AH1-746 GEN
Solar/Wind Harmer
2.592
20120126WRREN CT
Adder
5.725
971703AH1-357 GEN
Solar/Wind Harmer
1.25
971707AH1-359 GEN
Solar/Wind Harmer
1.25
970899AG2-561 GEN
Solar/Wind Harmer
1.133
20335126GROZ1-110
Adder
1.858
20335226CANZ2-011
Adder
1.806
20334926Z1-069 C
Solar/Wind Harmer
0.406
970125AG2-091 GEN
Solar/Wind Harmer
0.323
971419AH1-201 GEN
Solar/Wind Harmer
2.125
971541AH1-268 GEN
Solar/Wind Harmer
3.208
971879AH1-460 GEN
Solar/Wind Harmer
3.447
945751AF1-240 GEN
Solar/Wind Harmer
0.92
203841AF2-001_GEN
Solar/Wind Harmer
1.001
20079426CONEMAGH
Adder
0.853
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.278
238219AF1-167 C
Solar/Wind Harmer
0.6
970335AG2-220 GEN
Solar/Wind Harmer
1.368
971127AH1-005 GEN
Solar/Wind Harmer
0.997
971185AH1-051 GEN
Solar/Wind Harmer
1.246
971355AH1-158 GEN
Solar/Wind Harmer
2.076
970647AG2-420 GEN
Solar/Wind Harmer
0.817
972271AH1-720 GEN
Adder
3.827
20089126CSLMN_L13
Solar/Wind Harmer
0.027
20089026BF_G21_K23
Solar/Wind Harmer
0.027
957161AF2-010 GEN
Solar/Wind Harmer
3.04
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.112
20328326MANOR_T86
Adder
0.08
20084926LAKVU GN
Adder
0.097
20082926HNSMLK 2
Adder
3.113
20083126HNSMLK 4
Adder
3.113
203962AF1-287 GEN
Solar/Wind Harmer
0.736
202652Y1-033 WT C
Solar/Wind Harmer
0
200642SENECA#1
50/50
1.552
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.229
203975AE1-071-GEN
Solar/Wind Harmer
0.016
20090526Q36
Solar/Wind Harmer
0.591
203993AD2-133_GEN1
Solar/Wind Harmer
0.585
203961AE2-224 GEN
Solar/Wind Harmer
0.008
20091526CHSTN_FL
Solar/Wind Harmer
0.174
203804AE2-113_GEN
Solar/Wind Harmer
0.006
203850AG1-041 C
Solar/Wind Harmer
0.775
203844AF2-092 C
Solar/Wind Harmer
0.754
20092526R32
Solar/Wind Harmer
0.187
20087026C_T85_W218
Adder
0.504
970555AG2-356 GEN
Solar/Wind Harmer
0.923
970663AG2-429 GEN
Solar/Wind Harmer
3.183
970663AG2-429 GEN
Solar/Wind Harmer
0.696
20083926HOMER C3
Adder
43.507
20083826HOMER C2
Adder
41.097
20083726HOMER C1
Adder
40.483
970677AG2-438 GEN
Solar/Wind Harmer
0.442
966771AG1-548 GEN
Solar/Wind Harmer
1.316
966771AG1-548 GEN
Solar/Wind Harmer
1.645
20084926LAKVU GN
Adder
0.109
20083226HNSMLK 5
Adder
3.113
203926AA2-133 GEN
Adder
1.132
23732901CHBRG_I12
Adder
1.148
20081226ALY HYDR
50/50
0.385
20066626SHAWVL 4
50/50
2.253
20066526SHAWVL 3
50/50
2.237
20071526SHAWVL 1
50/50
1.515
216419AE2-001 C
Solar/Wind Harmer
3.961
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.143
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
20390526W1-045 C
Solar/Wind Harmer
0.083
972075AH1-587 GEN
Solar/Wind Harmer
15.234
971441AH1-212 GEN
Solar/Wind Harmer
1.512
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.263
972077AH1-588 GEN
Solar/Wind Harmer
14.999
972079AH1-589 GEN
Solar/Wind Harmer
17.707
970715AG2-457 GEN
Solar/Wind Harmer
5.812
203982AD2-062_GEN
Solar/Wind Harmer
5.363
203857AF2-221 C
Solar/Wind Harmer
0.565
970123AG2-090 GEN
Solar/Wind Harmer
0.754
20088926STNY CRK
Solar/Wind Harmer
0.103
971427AH1-205 GEN
Solar/Wind Harmer
1.417
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.001
20398826ARMNA MT
Solar/Wind Harmer
0.025
203848AF2-166 C
Solar/Wind Harmer
0.87
946071AF1-272 GEN
Solar/Wind Harmer
0
970313AG2-206 GEN
Solar/Wind Harmer
2.048
944781AF1-143 GEN
Solar/Wind Harmer
0
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.792
203963AG1-253 GEN
Solar/Wind Harmer
0.178
203859AF2-294 C
Solar/Wind Harmer
0.639
203947AF1-006 C
Solar/Wind Harmer
0.025
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.726
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.532
LAGNLTFEXP_LAGN->PJM
CLTF
1.478
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.388
TVALTFEXP_TVA->PJM
CLTF
0.728
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.963
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.824
MECLTFEXP_MEC->PJM
CLTF
1.453
SIGELTFEXP_SIGE->PJM
CLTF
0.045
LGEELTFEXP_LGEE->PJM
CLTF
0.592
WECLTFEXP_WEC->PJM
CLTF
0.345
CPLELTFEXP_CPLE->PJM
CLTF
0.381
CBM NorthLTFEXP_CBM-N->PJM
CBM
0.877
CBM West 2LTFEXP_CBM-W2->PJM
CBM
10.655

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PN_P1-2_PN-115-094_A_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-115-094_A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.45 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:787.65
MW Contribution:3.91
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
32.7
20091326SHAW-D
50/50
1.433
20064926PENNTECH
50/50
0.444
200643SENECA#2
50/50
1.605
970643AG2-418 GEN
Solar/Wind Harmer
4.444
238215AE2-248 C
Solar/Wind Harmer
3.596
203987AE2-118 C
Solar/Wind Harmer
3.732
238206AE2-263_GEN
Solar/Wind Harmer
0.011
972169AH1-667 GEN
Solar/Wind Harmer
2.581
203954AE2-126 C
Solar/Wind Harmer
0.002
957561AF2-050 GEN
Solar/Wind Harmer
5.45
238183AE2-316 GEN
Solar/Wind Harmer
0.005
20094526CT_V3-030
Solar/Wind Harmer
0.135
970713AG2-456 GEN
Solar/Wind Harmer
6.466
971705AH1-358 GEN
Solar/Wind Harmer
2.318
971709AH1-360 GEN
Solar/Wind Harmer
2.318
20088826HIGHLAND
Solar/Wind Harmer
0.001
971279AH1-102 GEN
Solar/Wind Harmer
6.197
970631AG2-411 GEN
Solar/Wind Harmer
3.911
20326126BLOSSBCT
Adder
1.865
971423AH1-203 GEN
Solar/Wind Harmer
3.977
203843AF2-002_GEN
Solar/Wind Harmer
0.558
970337AG2-221 GEN
Solar/Wind Harmer
1.152
970511AG2-327 GEN
Solar/Wind Harmer
0.486
20335026MILZ1-092
Adder
1.586
944411AF1-106 GEN
Solar/Wind Harmer
1.618
203835AF1-098 GEN
Solar/Wind Harmer
0.003
971183AH1-050 GEN
Solar/Wind Harmer
2.305
970647AG2-420 GEN
Solar/Wind Harmer
0.151
20089226LOOKOUT
Solar/Wind Harmer
0.084
203860AG1-193 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.107
20082826HNSMLK 1
Adder
3.459
20083026HNSMLK 3
Adder
3.459
203813AE2-344_GEN
Solar/Wind Harmer
4.724
970267AG2-176 GEN
Solar/Wind Harmer
6.072
209067AE2-060 GEN
Solar/Wind Helper
0.083
200644SENECA#3
50/50
0.221
970643AG2-418 GEN
Solar/Wind Harmer
6.667
238202AE2-262_GEN
Solar/Wind Harmer
0.012
971627AH1-313 GEN
Solar/Wind Harmer
18.178
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.36
960051AF2-296 GEN
Solar/Wind Harmer
2.213
203818AF1-086 GEN
Solar/Wind Harmer
0.743
972323AH1-746 GEN
Solar/Wind Harmer
2.877
20120126WRREN CT
Adder
6.346
971703AH1-357 GEN
Solar/Wind Harmer
1.391
971707AH1-359 GEN
Solar/Wind Harmer
1.391
970899AG2-561 GEN
Solar/Wind Harmer
1.261
20335126GROZ1-110
Adder
2.101
20335226CANZ2-011
Adder
2.042
20334926Z1-069 C
Solar/Wind Harmer
0.455
970125AG2-091 GEN
Solar/Wind Harmer
0.36
971419AH1-201 GEN
Solar/Wind Harmer
2.358
971541AH1-268 GEN
Solar/Wind Harmer
3.577
971879AH1-460 GEN
Solar/Wind Harmer
3.839
945751AF1-240 GEN
Solar/Wind Harmer
1.024
203841AF2-001_GEN
Solar/Wind Harmer
1.115
20079426CONEMAGH
Adder
0.952
941421AE2-139 GEN
Solar/Wind Harmer
0
203932AE1-123
Adder
1.42
238219AF1-167 C
Solar/Wind Harmer
0.667
970335AG2-220 GEN
Solar/Wind Harmer
1.558
971127AH1-005 GEN
Solar/Wind Harmer
1.136
972271AH1-720 GEN
Adder
4.399
971185AH1-051 GEN
Solar/Wind Harmer
1.383
971355AH1-158 GEN
Solar/Wind Harmer
2.305
970647AG2-420 GEN
Solar/Wind Harmer
0.907
20328326MANOR_T86
Adder
0.092
20089126CSLMN_L13
Solar/Wind Harmer
0.03
20089026BF_G21_K23
Solar/Wind Harmer
0.03
957161AF2-010 GEN
Solar/Wind Harmer
3.367
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.124
20084926LAKVU GN
Adder
0.107
20082926HNSMLK 2
Adder
3.459
20083126HNSMLK 4
Adder
3.459
203962AF1-287 GEN
Solar/Wind Harmer
0.815
202652Y1-033 WT C
Solar/Wind Harmer
0
200917MEHOOPANY_G
Solar/Wind Harmer
0.166
200642SENECA#1
50/50
1.721
203975AE1-071-GEN
Solar/Wind Harmer
0.044
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.36
20090526Q36
Solar/Wind Harmer
0.654
203993AD2-133_GEN1
Solar/Wind Harmer
0.648
203961AE2-224 GEN
Solar/Wind Harmer
0.008
20091526CHSTN_FL
Solar/Wind Harmer
0.193
203804AE2-113_GEN
Solar/Wind Harmer
0.007
203850AG1-041 C
Solar/Wind Harmer
0.861
203844AF2-092 C
Solar/Wind Harmer
0.838
20092526R32
Solar/Wind Harmer
0.208
970555AG2-356 GEN
Solar/Wind Harmer
1.047
970663AG2-429 GEN
Solar/Wind Harmer
3.539
970663AG2-429 GEN
Solar/Wind Harmer
0.774
20083926HOMER C3
Adder
48.691
20083826HOMER C2
Adder
45.994
20083726HOMER C1
Adder
45.416
970677AG2-438 GEN
Solar/Wind Harmer
0.49
966771AG1-548 GEN
Solar/Wind Harmer
1.458
966771AG1-548 GEN
Solar/Wind Harmer
1.822
20084926LAKVU GN
Adder
0.121
20083226HNSMLK 5
Adder
3.459
203926AA2-133 GEN
Adder
1.316
20334726NME_Y1-047
Adder
1.11
20081226ALY HYDR
50/50
0.425
20066626SHAWVL 4
50/50
2.492
20066526SHAWVL 3
50/50
2.473
20071526SHAWVL 1
50/50
1.676
216419AE2-001 C
Solar/Wind Harmer
4.372
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.8
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
972075AH1-587 GEN
Solar/Wind Harmer
16.919
971441AH1-212 GEN
Solar/Wind Harmer
1.68
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.4
972077AH1-588 GEN
Solar/Wind Harmer
16.686
972079AH1-589 GEN
Solar/Wind Harmer
19.699
970715AG2-457 GEN
Solar/Wind Harmer
6.466
203857AF2-221 C
Solar/Wind Harmer
0.63
970123AG2-090 GEN
Solar/Wind Harmer
0.84
20088926STNY CRK
Solar/Wind Harmer
0.114
971427AH1-205 GEN
Solar/Wind Harmer
1.572
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.115
20398826ARMNA MT
Solar/Wind Harmer
0.028
970313AG2-206 GEN
Solar/Wind Harmer
2.334
946071AF1-272 GEN
Solar/Wind Harmer
0
203848AF2-166 C
Solar/Wind Harmer
0.967
944781AF1-143 GEN
Solar/Wind Harmer
0
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.877
203963AG1-253 GEN
Solar/Wind Harmer
0.197
203859AF2-294 C
Solar/Wind Harmer
0.732
203947AF1-006 C
Solar/Wind Harmer
0.028
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.803
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.402
LAGNLTFEXP_LAGN->PJM
CLTF
1.316
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.969
TVALTFEXP_TVA->PJM
CLTF
0.645
CBM West 1LTFEXP_CBM-W1->PJM
CBM
13.494
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.533
MECLTFEXP_MEC->PJM
CLTF
1.368
SIGELTFEXP_SIGE->PJM
CLTF
0.042
LGEELTFEXP_LGEE->PJM
CLTF
0.556
WECLTFEXP_WEC->PJM
CLTF
0.329
CPLELTFEXP_CPLE->PJM
CLTF
0.203
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.935
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.763

Details for 26LEWISTWN-JUNI 230.0 kV Ckt 1 line l/o PL_10_P12_000085_SRT-A


Base Case Flowgate

Area:PENELEC/PL
Facility Description:
26LEWISTWN-JUNI 230.0 kV Ckt 1 line
Contingency Name:
PL_10_P12_000085_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.27 %
Rating:618.0 MVA
Rating Type:B
MVA to Mitigate:786.5
MW Contribution:3.71
Bus #Bus NameTypeMW Contribution
20072226SHAWVL 2
50/50
29.562
20091326SHAW-D
50/50
1.299
20064926PENNTECH
50/50
0.404
200643SENECA#2
50/50
1.48
970643AG2-418 GEN
Solar/Wind Harmer
3.069
238215AE2-248 C
Solar/Wind Harmer
3.237
203987AE2-118 C
Solar/Wind Harmer
3.373
238206AE2-263_GEN
Solar/Wind Harmer
0.01
972169AH1-667 GEN
Solar/Wind Harmer
2.339
203954AE2-126 C
Solar/Wind Harmer
0.002
957561AF2-050 GEN
Solar/Wind Harmer
5.007
238183AE2-316 GEN
Solar/Wind Harmer
0.004
20094526CT_V3-030
Solar/Wind Harmer
0.126
20088826HIGHLAND
Solar/Wind Harmer
0.001
970713AG2-456 GEN
Solar/Wind Harmer
5.973
971705AH1-358 GEN
Solar/Wind Harmer
2.141
971709AH1-360 GEN
Solar/Wind Harmer
2.141
971279AH1-102 GEN
Solar/Wind Harmer
5.865
970631AG2-411 GEN
Solar/Wind Harmer
3.708
971423AH1-203 GEN
Solar/Wind Harmer
3.774
203843AF2-002_GEN
Solar/Wind Harmer
0.53
20326126BLOSSBCT
Adder
1.644
203835AF1-098 GEN
Solar/Wind Harmer
0.003
970337AG2-221 GEN
Solar/Wind Harmer
1.002
971183AH1-050 GEN
Solar/Wind Harmer
2.218
970647AG2-420 GEN
Solar/Wind Harmer
0.146
20089226LOOKOUT
Solar/Wind Harmer
0.082
20335026MILZ1-092
Adder
1.389
944411AF1-106 GEN
Solar/Wind Harmer
1.417
970511AG2-327 GEN
Solar/Wind Harmer
0.419
203860AG1-193 C
Solar/Wind Harmer
0
20084926LAKVU GN
Adder
0.103
20082826HNSMLK 1
Adder
3.354
20083026HNSMLK 3
Adder
3.354
970267AG2-176 GEN
Solar/Wind Harmer
5.887
203813AE2-344_GEN
Solar/Wind Harmer
4.571
209067AE2-060 GEN
Solar/Wind Helper
0.1
946691AF1-333 GEN
Solar/Wind Helper
0.225
946741AF1-338 GEN
Solar/Wind Helper
0.225
200644SENECA#3
50/50
0.204
970643AG2-418 GEN
Solar/Wind Harmer
4.603
238202AE2-262_GEN
Solar/Wind Harmer
0.01
971627AH1-313 GEN
Solar/Wind Harmer
16.392
203854AF2-039 C
Solar/Wind Harmer
0.001
965131AG1-378 GEN
Solar/Wind Harmer
1.236
960051AF2-296 GEN
Solar/Wind Harmer
2.025
203818AF1-086 GEN
Solar/Wind Harmer
0.688
972323AH1-746 GEN
Solar/Wind Harmer
2.662
20120126WRREN CT
Adder
5.889
971703AH1-357 GEN
Solar/Wind Harmer
1.285
971707AH1-359 GEN
Solar/Wind Harmer
1.285
970899AG2-561 GEN
Solar/Wind Harmer
1.189
970125AG2-091 GEN
Solar/Wind Harmer
0.34
971419AH1-201 GEN
Solar/Wind Harmer
2.232
971541AH1-268 GEN
Solar/Wind Harmer
3.386
971879AH1-460 GEN
Solar/Wind Harmer
3.636
20334926Z1-069 C
Solar/Wind Harmer
0.414
20335126GROZ1-110
Adder
1.817
20335226CANZ2-011
Adder
1.766
945751AF1-240 GEN
Solar/Wind Harmer
0.973
203841AF2-001_GEN
Solar/Wind Harmer
1.059
20079426CONEMAGH
Adder
0.904
203932AE1-123
Adder
1.36
238219AF1-167 C
Solar/Wind Harmer
0.641
971185AH1-051 GEN
Solar/Wind Harmer
1.331
971355AH1-158 GEN
Solar/Wind Harmer
2.218
970647AG2-420 GEN
Solar/Wind Harmer
0.874
941421AE2-139 GEN
Solar/Wind Harmer
0
20089126CSLMN_L13
Solar/Wind Harmer
0.029
20089026BF_G21_K23
Solar/Wind Harmer
0.029
957161AF2-010 GEN
Solar/Wind Harmer
3.237
203830AF1-094 GEN
Solar/Wind Harmer
0.001
970335AG2-220 GEN
Solar/Wind Harmer
1.343
971127AH1-005 GEN
Solar/Wind Harmer
0.979
203948AG1-140 C
Solar/Wind Harmer
0.119
20084926LAKVU GN
Adder
0.103
20082926HNSMLK 2
Adder
3.354
20083126HNSMLK 4
Adder
3.354
203962AF1-287 GEN
Solar/Wind Harmer
0.788
972271AH1-720 GEN
Adder
3.634
20328326MANOR_T86
Adder
0.077
202652Y1-033 WT C
Solar/Wind Harmer
0
209071AE2-133 GEN
Solar/Wind Helper
0.041
946731AF1-337 GEN
Solar/Wind Helper
0.225
212507AE2-042_GEN
Solar/Wind Helper
0.788
200642SENECA#1
50/50
1.586
203855AF2-088 C
Solar/Wind Harmer
0.001
965121AG1-377 GEN
Solar/Wind Harmer
1.236
203975AE1-071-GEN
Solar/Wind Harmer
0.016
20090526Q36
Solar/Wind Harmer
0.596
203993AD2-133_GEN1
Solar/Wind Harmer
0.59
203961AE2-224 GEN
Solar/Wind Harmer
0.008
20091526CHSTN_FL
Solar/Wind Harmer
0.178
203804AE2-113_GEN
Solar/Wind Harmer
0.006
203850AG1-041 C
Solar/Wind Harmer
0.805
203844AF2-092 C
Solar/Wind Harmer
0.785
20092526R32
Solar/Wind Harmer
0.195
20087026C_T85_W218
Adder
0.48
970663AG2-429 GEN
Solar/Wind Harmer
3.405
970663AG2-429 GEN
Solar/Wind Harmer
0.744
20083926HOMER C3
Adder
46.584
20083826HOMER C2
Adder
44.004
970555AG2-356 GEN
Solar/Wind Harmer
0.911
20083726HOMER C1
Adder
43.869
970677AG2-438 GEN
Solar/Wind Harmer
0.471
966771AG1-548 GEN
Solar/Wind Harmer
1.401
966771AG1-548 GEN
Solar/Wind Harmer
1.752
20084926LAKVU GN
Adder
0.116
20083226HNSMLK 5
Adder
3.354
203926AA2-133 GEN
Adder
1.058
23732901CHBRG_I12
Adder
1.103
959431AF2-234 GEN
Solar/Wind Helper
0.452
964051AG1-259 GEN
Solar/Wind Helper
0.034
964061AG1-260 GEN
Solar/Wind Helper
0.034
959421AF2-233 GEN
Solar/Wind Helper
0.226
20081226ALY HYDR
50/50
0.384
20066626SHAWVL 4
50/50
2.253
20066526SHAWVL 3
50/50
2.236
20071526SHAWVL 1
50/50
1.517
216419AE2-001 C
Solar/Wind Harmer
3.937
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.178
20088626ARWF_N39
Solar/Wind Harmer
0.002
20303426NA_O38_P22
Solar/Wind Harmer
0.001
971441AH1-212 GEN
Solar/Wind Harmer
1.558
972075AH1-587 GEN
Solar/Wind Harmer
15.512
20390526W1-045 C
Solar/Wind Harmer
0.08
203940AF1-140 C
Solar/Wind Harmer
0.001
970305AG2-200 GEN
Solar/Wind Harmer
1.3
972077AH1-588 GEN
Solar/Wind Harmer
15.415
972079AH1-589 GEN
Solar/Wind Harmer
18.198
970715AG2-457 GEN
Solar/Wind Harmer
5.973
203982AD2-062_GEN
Solar/Wind Harmer
5.202
203857AF2-221 C
Solar/Wind Harmer
0.595
970123AG2-090 GEN
Solar/Wind Harmer
0.794
20088926STNY CRK
Solar/Wind Harmer
0.108
971427AH1-205 GEN
Solar/Wind Harmer
1.488
20084626FORWARD
Solar/Wind Harmer
0
203839AF1-321 GEN
Solar/Wind Harmer
1.059
946071AF1-272 GEN
Solar/Wind Harmer
0
203848AF2-166 C
Solar/Wind Harmer
0.928
20398826ARMNA MT
Solar/Wind Harmer
0.025
944781AF1-143 GEN
Solar/Wind Harmer
0
203979AG1-198 GEN
Solar/Wind Harmer
0
971933AH1-491 GEN
Solar/Wind Harmer
0.843
203963AG1-253 GEN
Solar/Wind Harmer
0.188
970313AG2-206 GEN
Solar/Wind Harmer
2.009
203947AF1-006 C
Solar/Wind Harmer
0.027
203980AG1-197 GEN
Solar/Wind Harmer
0
971931AH1-490 GEN
Solar/Wind Harmer
0.778
203859AF2-294 C
Solar/Wind Harmer
0.627
203955AF1-039 C O1
Solar/Wind Harmer
0
209137AF2-361 C
Solar/Wind Helper
1.69
946751AF1-339 GEN
Solar/Wind Helper
0.225
209054AE2-059 GEN
Solar/Wind Helper
0.04
LAGNLTFEXP_LAGN->PJM
CLTF
1.999
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.946
TVALTFEXP_TVA->PJM
CLTF
0.986
CBM West 1LTFEXP_CBM-W1->PJM
CBM
18.461
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.818
MECLTFEXP_MEC->PJM
CLTF
1.942
SIGELTFEXP_SIGE->PJM
CLTF
0.06
NYPJM->LTFIMP_NY
CLTF
0.234
LGEELTFEXP_LGEE->PJM
CLTF
0.793
WECLTFEXP_WEC->PJM
CLTF
0.459
CPLELTFEXP_CPLE->PJM
CLTF
0.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
14.334

Details for 26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-B_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.96 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.88
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20089026BF_G21_K23
Solar/Wind Harmer
1.946
971419AH1-201 GEN
Solar/Wind Harmer
4.392
203841AF2-001_GEN
Solar/Wind Harmer
1.93
971879AH1-460 GEN
Solar/Wind Harmer
5.763
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.573
238127S14_GEN_2
Solar/Wind Helper
0.455
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.393
971423AH1-203 GEN
Solar/Wind Harmer
10.441
203843AF2-002_GEN
Solar/Wind Harmer
0.965
970631AG2-411 GEN
Solar/Wind Harmer
6.013
20088826HIGHLAND
Solar/Wind Harmer
1.099
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20094526CT_V3-030
Solar/Wind Harmer
0.307
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.425
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.043
20088926STNY CRK
Solar/Wind Harmer
1.677
203839AF1-321 GEN
Solar/Wind Harmer
1.93
20084626FORWARD
Solar/Wind Harmer
0.754
203857AF2-221 C
Solar/Wind Harmer
1.206
970123AG2-090 GEN
Solar/Wind Harmer
1.126
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.033
972077AH1-588 GEN
Solar/Wind Harmer
5.442
972079AH1-589 GEN
Solar/Wind Harmer
4.482
238120AE2-309 GEN
Solar/Wind Helper
0.223
203844AF2-092 C
Solar/Wind Harmer
1.087
203850AG1-041 C
Solar/Wind Harmer
1.034
20092526R32
Solar/Wind Harmer
1.178
20091526CHSTN_FL
Solar/Wind Harmer
0.442
20083726HOMER C1
Adder
25.807
20083926HOMER C3
Adder
21.977
20083826HOMER C2
Adder
20.76
238126S14_GEN_1
Solar/Wind Helper
0.455
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.44
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.366
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.113
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.658
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.191
G-007ALTFEXP_G-007A->PJM
CMTX
0.839
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.195
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-C_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-C_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.96 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.88
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
203844AF2-092 C
Solar/Wind Harmer
1.087
203850AG1-041 C
Solar/Wind Harmer
1.034
20092526R32
Solar/Wind Harmer
1.178
20091526CHSTN_FL
Solar/Wind Harmer
0.442
20083726HOMER C1
Adder
25.807
20083926HOMER C3
Adder
21.977
20083826HOMER C2
Adder
20.76
238126S14_GEN_1
Solar/Wind Helper
0.455
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20089026BF_G21_K23
Solar/Wind Harmer
1.946
971419AH1-201 GEN
Solar/Wind Harmer
4.392
203841AF2-001_GEN
Solar/Wind Harmer
1.93
971879AH1-460 GEN
Solar/Wind Harmer
5.763
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.573
238127S14_GEN_2
Solar/Wind Helper
0.455
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.393
971423AH1-203 GEN
Solar/Wind Harmer
10.441
203843AF2-002_GEN
Solar/Wind Harmer
0.965
970631AG2-411 GEN
Solar/Wind Harmer
6.013
20088826HIGHLAND
Solar/Wind Harmer
1.099
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20094526CT_V3-030
Solar/Wind Harmer
0.307
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.425
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.043
20088926STNY CRK
Solar/Wind Harmer
1.677
203839AF1-321 GEN
Solar/Wind Harmer
1.93
20084626FORWARD
Solar/Wind Harmer
0.754
203857AF2-221 C
Solar/Wind Harmer
1.206
970123AG2-090 GEN
Solar/Wind Harmer
1.126
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.033
972077AH1-588 GEN
Solar/Wind Harmer
5.442
972079AH1-589 GEN
Solar/Wind Harmer
4.482
238120AE2-309 GEN
Solar/Wind Helper
0.223
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.44
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.366
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.113
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.658
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.191
G-007ALTFEXP_G-007A->PJM
CMTX
0.839
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.195
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0252-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0252-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.96 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:187.88
MW Contribution:6.01
Bus #Bus NameTypeMW Contribution
203844AF2-092 C
Solar/Wind Harmer
1.087
203850AG1-041 C
Solar/Wind Harmer
1.034
20092526R32
Solar/Wind Harmer
1.178
20091526CHSTN_FL
Solar/Wind Harmer
0.442
20083726HOMER C1
Adder
25.807
20083926HOMER C3
Adder
21.977
20083826HOMER C2
Adder
20.76
238126S14_GEN_1
Solar/Wind Helper
0.455
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.458
20089026BF_G21_K23
Solar/Wind Harmer
1.946
971419AH1-201 GEN
Solar/Wind Harmer
4.392
203841AF2-001_GEN
Solar/Wind Harmer
1.93
971879AH1-460 GEN
Solar/Wind Harmer
5.763
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.573
238127S14_GEN_2
Solar/Wind Helper
0.455
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.393
971423AH1-203 GEN
Solar/Wind Harmer
10.441
203843AF2-002_GEN
Solar/Wind Harmer
0.965
970631AG2-411 GEN
Solar/Wind Harmer
6.013
20088826HIGHLAND
Solar/Wind Harmer
1.099
964201AG1-281 GEN
Solar/Wind Harmer
0.355
20094526CT_V3-030
Solar/Wind Harmer
0.307
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.425
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.043
20088926STNY CRK
Solar/Wind Harmer
1.677
203839AF1-321 GEN
Solar/Wind Harmer
1.93
20084626FORWARD
Solar/Wind Harmer
0.754
203857AF2-221 C
Solar/Wind Harmer
1.206
970123AG2-090 GEN
Solar/Wind Harmer
1.126
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.033
972077AH1-588 GEN
Solar/Wind Harmer
5.442
972079AH1-589 GEN
Solar/Wind Harmer
4.482
238120AE2-309 GEN
Solar/Wind Helper
0.223
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.44
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.366
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.113
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.658
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.191
G-007ALTFEXP_G-007A->PJM
CMTX
0.839
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.195
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0201A-20_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0201A-20_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.3 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:186.7
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.457
20089026BF_G21_K23
Solar/Wind Harmer
1.945
971419AH1-201 GEN
Solar/Wind Harmer
4.389
203841AF2-001_GEN
Solar/Wind Harmer
1.927
971879AH1-460 GEN
Solar/Wind Harmer
5.755
970125AG2-091 GEN
Solar/Wind Harmer
0.482
20079426CONEMAGH
Adder
0.574
238127S14_GEN_2
Solar/Wind Helper
0.455
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.422
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.041
20088926STNY CRK
Solar/Wind Harmer
1.676
203839AF1-321 GEN
Solar/Wind Harmer
1.927
20084626FORWARD
Solar/Wind Harmer
0.753
203857AF2-221 C
Solar/Wind Harmer
1.205
970123AG2-090 GEN
Solar/Wind Harmer
1.124
203940AF1-140 C
Solar/Wind Harmer
0.342
971441AH1-212 GEN
Solar/Wind Harmer
1.033
972077AH1-588 GEN
Solar/Wind Harmer
5.4
972079AH1-589 GEN
Solar/Wind Harmer
4.448
238120AE2-309 GEN
Solar/Wind Helper
0.223
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.393
971423AH1-203 GEN
Solar/Wind Harmer
10.433
203843AF2-002_GEN
Solar/Wind Harmer
0.964
970631AG2-411 GEN
Solar/Wind Harmer
6.005
20088826HIGHLAND
Solar/Wind Harmer
1.098
964201AG1-281 GEN
Solar/Wind Harmer
0.354
20094526CT_V3-030
Solar/Wind Harmer
0.31
203844AF2-092 C
Solar/Wind Harmer
1.086
203850AG1-041 C
Solar/Wind Harmer
1.033
20092526R32
Solar/Wind Harmer
1.176
20091526CHSTN_FL
Solar/Wind Harmer
0.442
20083726HOMER C1
Adder
25.462
20083926HOMER C3
Adder
21.721
20083826HOMER C2
Adder
20.518
238126S14_GEN_1
Solar/Wind Helper
0.455
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.141
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.438
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.351
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.112
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.655
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.19
G-007ALTFEXP_G-007A->PJM
CMTX
0.834
CBM NorthLTFEXP_CBM-N->PJM
CBM
5.152
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line l/o AP_P2-3_PE-500-014_SRT-SL


Base Case Flowgate

Area:PENELEC
Facility Description:
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_PE-500-014_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.66 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:185.56
MW Contribution:5.51
Bus #Bus NameTypeMW Contribution
202652Y1-033 WT C
Solar/Wind Harmer
3.789
20089126CSLMN_L13
Solar/Wind Harmer
2.403
20089026BF_G21_K23
Solar/Wind Harmer
1.902
971419AH1-201 GEN
Solar/Wind Harmer
4.158
20081326YOUGH
50/50
0.181
20089226LOOKOUT
Solar/Wind Harmer
2.34
971423AH1-203 GEN
Solar/Wind Harmer
9.927
203843AF2-002_GEN
Solar/Wind Harmer
0.884
970631AG2-411 GEN
Solar/Wind Harmer
5.507
203955AF1-039 C O1
Solar/Wind Harmer
1.845
944781AF1-143 GEN
Solar/Wind Harmer
8.237
20083426SW_E13_K22
Solar/Wind Harmer
0.49
971427AH1-205 GEN
Solar/Wind Harmer
1.934
20088826HIGHLAND
Solar/Wind Harmer
0.974
964201AG1-281 GEN
Solar/Wind Harmer
0.312
203844AF2-092 C
Solar/Wind Harmer
0.997
203850AG1-041 C
Solar/Wind Harmer
0.944
20092526R32
Solar/Wind Harmer
1.044
20091526CHSTN_FL
Solar/Wind Harmer
0.383
20083726HOMER C1
Adder
18.135
20083926HOMER C3
Adder
15.702
20083826HOMER C2
Adder
14.833
238126S14_GEN_1
Solar/Wind Helper
0.468
203841AF2-001_GEN
Solar/Wind Harmer
1.768
971879AH1-460 GEN
Solar/Wind Harmer
5.234
970125AG2-091 GEN
Solar/Wind Harmer
0.435
238127S14_GEN_2
Solar/Wind Helper
0.468
20088926STNY CRK
Solar/Wind Harmer
1.587
203839AF1-321 GEN
Solar/Wind Harmer
1.768
20084626FORWARD
Solar/Wind Harmer
0.691
203857AF2-221 C
Solar/Wind Harmer
1.087
970123AG2-090 GEN
Solar/Wind Harmer
1.015
203940AF1-140 C
Solar/Wind Harmer
0.306
971441AH1-212 GEN
Solar/Wind Harmer
0.889
238120AE2-309 GEN
Solar/Wind Helper
0.231
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.383
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.118
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.58
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.187
G-007ALTFEXP_G-007A->PJM
CMTX
0.749
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.042
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.77 %
Rating:179.0 MVA
Rating Type:B
MVA to Mitigate:182.17
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
203955AF1-039 C O1
Solar/Wind Harmer
1.867
944781AF1-143 GEN
Solar/Wind Harmer
8.42
20083426SW_E13_K22
Solar/Wind Harmer
0.511
971427AH1-205 GEN
Solar/Wind Harmer
2.041
20088926STNY CRK
Solar/Wind Harmer
1.675
203839AF1-321 GEN
Solar/Wind Harmer
1.922
20084626FORWARD
Solar/Wind Harmer
0.751
203857AF2-221 C
Solar/Wind Harmer
1.207
970123AG2-090 GEN
Solar/Wind Harmer
1.127
203940AF1-140 C
Solar/Wind Harmer
0.344
971441AH1-212 GEN
Solar/Wind Harmer
1.044
972077AH1-588 GEN
Solar/Wind Harmer
4.966
972079AH1-589 GEN
Solar/Wind Harmer
4.09
238120AE2-309 GEN
Solar/Wind Helper
0.222
203844AF2-092 C
Solar/Wind Harmer
1.088
203850AG1-041 C
Solar/Wind Harmer
1.035
20092526R32
Solar/Wind Harmer
1.185
20091526CHSTN_FL
Solar/Wind Harmer
0.445
20083726HOMER C1
Adder
22.715
20083926HOMER C3
Adder
19.536
20083826HOMER C2
Adder
18.454
238126S14_GEN_1
Solar/Wind Helper
0.453
202652Y1-033 WT C
Solar/Wind Harmer
3.835
20089126CSLMN_L13
Solar/Wind Harmer
2.457
20089026BF_G21_K23
Solar/Wind Harmer
1.945
971419AH1-201 GEN
Solar/Wind Harmer
4.387
203841AF2-001_GEN
Solar/Wind Harmer
1.922
971879AH1-460 GEN
Solar/Wind Harmer
5.754
970125AG2-091 GEN
Solar/Wind Harmer
0.483
20079426CONEMAGH
Adder
0.59
238127S14_GEN_2
Solar/Wind Helper
0.453
20081326YOUGH
50/50
0.182
20089226LOOKOUT
Solar/Wind Harmer
2.392
971423AH1-203 GEN
Solar/Wind Harmer
10.428
203843AF2-002_GEN
Solar/Wind Harmer
0.961
970631AG2-411 GEN
Solar/Wind Harmer
5.988
20088826HIGHLAND
Solar/Wind Harmer
1.106
964201AG1-281 GEN
Solar/Wind Harmer
0.357
20094526CT_V3-030
Solar/Wind Harmer
0.307
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.125
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.389
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
2.012
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.105
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.585
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.18
G-007ALTFEXP_G-007A->PJM
CMTX
0.709
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.633
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-2_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.95 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1312.71
MW Contribution:19.09
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.475
20216026CON.GEN2
50/50
0.034
970125AG2-091 GEN
Solar/Wind Harmer
1.837
971879AH1-460 GEN
Solar/Wind Harmer
20.153
20079426CONEMAGH
Adder
3.673
203841AF2-001_GEN
Solar/Wind Harmer
6.086
971541AH1-268 GEN
Solar/Wind Harmer
10.099
971419AH1-201 GEN
Solar/Wind Harmer
8.865
970899AG2-561 GEN
Solar/Wind Harmer
5.475
203818AF1-086 GEN
Solar/Wind Harmer
6.305
20089126CSLMN_L13
Solar/Wind Harmer
2.008
20089026BF_G21_K23
Solar/Wind Harmer
1.589
960051AF2-296 GEN
Solar/Wind Harmer
4.314
945751AF1-240 GEN
Solar/Wind Harmer
3.376
971703AH1-357 GEN
Solar/Wind Harmer
4.068
971707AH1-359 GEN
Solar/Wind Harmer
4.068
965131AG1-378 GEN
Solar/Wind Harmer
3.983
20334926Z1-069 C
Solar/Wind Harmer
4.096
20082926HNSMLK 2
Adder
10.319
20083126HNSMLK 4
Adder
10.319
203854AF2-039 C
Solar/Wind Harmer
0.712
202652Y1-033 WT C
Solar/Wind Harmer
1.626
203932AE1-123
Adder
3.315
944411AF1-106 GEN
Solar/Wind Harmer
0.373
971185AH1-051 GEN
Solar/Wind Harmer
3.853
971355AH1-158 GEN
Solar/Wind Harmer
4.48
203856AF2-165 C
Solar/Wind Harmer
1.87
20120126WRREN CT
Adder
9.907
970647AG2-420 GEN
Solar/Wind Harmer
3.129
970335AG2-220 GEN
Solar/Wind Harmer
4.71
971127AH1-005 GEN
Solar/Wind Harmer
3.038
959441AF2-235 GEN
Solar/Wind Harmer
0.45
238219AF1-167 C
Solar/Wind Harmer
1.972
238202AE2-262_GEN
Solar/Wind Harmer
3.699
971627AH1-313 GEN
Solar/Wind Harmer
14.502
20335126GROZ1-110
Adder
3.201
20335226CANZ2-011
Adder
3.111
957161AF2-010 GEN
Solar/Wind Harmer
10.289
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.336
203962AF1-287 GEN
Solar/Wind Harmer
2.519
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.532
972271AH1-720 GEN
Adder
7.499
200917MEHOOPANY_G
Solar/Wind Harmer
3.471
970679AG2-439 GEN
Solar/Wind Harmer
0.783
970643AG2-418 GEN
Solar/Wind Harmer
1.57
237043AE2-125 C
Solar/Wind Harmer
0.185
20080926SITHE
50/50
0.884
946071AF1-272 GEN
Solar/Wind Harmer
11.274
203857AF2-221 C
Solar/Wind Harmer
4.592
970123AG2-090 GEN
Solar/Wind Harmer
4.286
203839AF1-321 GEN
Solar/Wind Harmer
6.086
20084626FORWARD
Solar/Wind Harmer
2.396
203940AF1-140 C
Solar/Wind Harmer
1.422
971441AH1-212 GEN
Solar/Wind Harmer
5.714
20088626ARWF_N39
Solar/Wind Harmer
5.246
20303426NA_O38_P22
Solar/Wind Harmer
4.247
20088926STNY CRK
Solar/Wind Harmer
3.415
971427AH1-205 GEN
Solar/Wind Harmer
4.123
20083426SW_E13_K22
Solar/Wind Harmer
0.807
944781AF1-143 GEN
Solar/Wind Harmer
6.882
203853AF1-134 C O1
Solar/Wind Harmer
1.304
972077AH1-588 GEN
Solar/Wind Harmer
48.81
972079AH1-589 GEN
Solar/Wind Harmer
40.202
970715AG2-457 GEN
Solar/Wind Harmer
16.27
203952AE2-129 C
Solar/Wind Harmer
1.206
203946AE2-131 C
Solar/Wind Harmer
1.204
962411AG1-090 GEN
Solar/Wind Harmer
18.919
972075AH1-587 GEN
Solar/Wind Harmer
38.875
203955AF1-039 C O1
Solar/Wind Harmer
0.791
20398826ARMNA MT
Solar/Wind Harmer
3.933
203848AF2-166 C
Solar/Wind Harmer
3.252
946381AF1-302 GEN
Solar/Wind Harmer
3.343
238217AF1-153 C O1
Solar/Wind Harmer
0.955
970305AG2-200 GEN
Solar/Wind Harmer
3.134
203859AF2-294 C
Solar/Wind Harmer
2.597
970313AG2-206 GEN
Solar/Wind Harmer
7.257
216419AE2-001 C
Solar/Wind Harmer
2.715
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.657
203963AG1-253 GEN
Solar/Wind Harmer
0.513
971931AH1-490 GEN
Solar/Wind Harmer
2.512
203947AF1-006 C
Solar/Wind Harmer
0.664
20083726HOMER C1
50/50
274.812
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.267
20083926HOMER C3
50/50
227.884
20083826HOMER C2
50/50
215.262
20092526R32
Solar/Wind Harmer
5.249
203961AE2-224 GEN
Solar/Wind Harmer
8.943
203844AF2-092 C
Solar/Wind Harmer
3.471
203850AG1-041 C
Solar/Wind Harmer
3.468
20091526CHSTN_FL
Solar/Wind Harmer
2.312
20090526Q36
Solar/Wind Harmer
3.421
203993AD2-133_GEN1
Solar/Wind Harmer
3.421
940863AE2-074 GEN
Solar/Wind Harmer
3.497
941231AE2-117 GEN
Solar/Wind Harmer
1.21
965121AG1-377 GEN
Solar/Wind Harmer
3.983
203804AE2-113_GEN
Solar/Wind Harmer
9.118
20083226HNSMLK 5
Adder
10.319
203855AF2-088 C
Solar/Wind Harmer
0.343
203846AF2-130 C
Solar/Wind Harmer
0.929
970555AG2-356 GEN
Solar/Wind Harmer
3.145
970663AG2-429 GEN
Solar/Wind Harmer
10.588
970663AG2-429 GEN
Solar/Wind Harmer
1.724
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.253
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.597
971321AH1-140 GEN
Solar/Wind Harmer
14.986
971321AH1-140 GEN
Solar/Wind Harmer
2.904
20334726NME_Y1-047
Adder
2.332
20390726Y2-042
Adder
1.874
971055AG2-654 GEN
Solar/Wind Harmer
0.689
203843AF2-002_GEN
Solar/Wind Harmer
3.043
970631AG2-411 GEN
Solar/Wind Harmer
19.093
20088826HIGHLAND
Solar/Wind Harmer
4.899
957561AF2-050 GEN
Solar/Wind Harmer
14.764
971279AH1-102 GEN
Solar/Wind Harmer
23.731
971423AH1-203 GEN
Solar/Wind Harmer
19.36
20094526CT_V3-030
Solar/Wind Harmer
1.946
964201AG1-281 GEN
Solar/Wind Harmer
1.65
20089226LOOKOUT
Solar/Wind Harmer
1.955
203987AE2-118 C
Solar/Wind Harmer
4.298
970713AG2-456 GEN
Solar/Wind Harmer
16.27
971705AH1-358 GEN
Solar/Wind Harmer
4.73
971709AH1-360 GEN
Solar/Wind Harmer
4.73
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.319
20083026HNSMLK 3
Adder
10.319
20091326SHAW-D
Adder
1.146
972169AH1-667 GEN
Solar/Wind Harmer
3.136
203954AE2-126 C
Solar/Wind Harmer
1.044
20326126BLOSSBCT
Adder
3.822
20335026MILZ1-092
Adder
3.771
944411AF1-106 GEN
Solar/Wind Harmer
3.474
238183AE2-316 GEN
Solar/Wind Harmer
6.681
971183AH1-050 GEN
Solar/Wind Harmer
6.421
959471AF2-238 GEN
Solar/Wind Harmer
0.951
970337AG2-221 GEN
Solar/Wind Harmer
3.145
20072226SHAWVL 2
Adder
21.511
970647AG2-420 GEN
Solar/Wind Harmer
0.364
203860AG1-193 C
Solar/Wind Harmer
0.463
970511AG2-327 GEN
Solar/Wind Harmer
1.512
238206AE2-263_GEN
Solar/Wind Harmer
3.447
970267AG2-176 GEN
Solar/Wind Harmer
21.074
238215AE2-248 C
Solar/Wind Harmer
2.148
961971AG1-040 GEN
Solar/Wind Harmer
0.796
203835AF1-098 GEN
Solar/Wind Harmer
3.159
203813AE2-344_GEN
Solar/Wind Harmer
14.605
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.73
971865AH1-452 GEN
Solar/Wind Harmer
1.131
24035802GEN-Y1-012
Adder
0.244
961581Q1080_CY23
External Queue
26.21918487548828
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.809
MECLTFEXP_MEC->PJM
CLTF
0.089
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LGEELTFEXP_LGEE->PJM
CLTF
0.012
WECLTFEXP_WEC->PJM
CLTF
0.035
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.214
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.23
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-500-003JT_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-003JT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.46 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.88
MW Contribution:19.3
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.856
971879AH1-460 GEN
Solar/Wind Harmer
20.37
203841AF2-001_GEN
Solar/Wind Harmer
6.155
971541AH1-268 GEN
Solar/Wind Harmer
10.324
971419AH1-201 GEN
Solar/Wind Harmer
8.962
970899AG2-561 GEN
Solar/Wind Harmer
5.553
203818AF1-086 GEN
Solar/Wind Harmer
6.382
20089126CSLMN_L13
Solar/Wind Harmer
2.031
20089026BF_G21_K23
Solar/Wind Harmer
1.608
960051AF2-296 GEN
Solar/Wind Harmer
4.354
945751AF1-240 GEN
Solar/Wind Harmer
3.41
971703AH1-357 GEN
Solar/Wind Harmer
4.059
971707AH1-359 GEN
Solar/Wind Harmer
4.059
965131AG1-378 GEN
Solar/Wind Harmer
4.003
20334926Z1-069 C
Solar/Wind Harmer
4.086
202652Y1-033 WT C
Solar/Wind Harmer
1.645
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.715
203932AE1-123
Adder
3.33
944411AF1-106 GEN
Solar/Wind Harmer
0.372
971185AH1-051 GEN
Solar/Wind Harmer
3.862
971355AH1-158 GEN
Solar/Wind Harmer
4.491
203856AF2-165 C
Solar/Wind Harmer
1.874
970647AG2-420 GEN
Solar/Wind Harmer
3.135
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
4.698
971127AH1-005 GEN
Solar/Wind Harmer
3.031
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.976
238202AE2-262_GEN
Solar/Wind Harmer
3.703
971627AH1-313 GEN
Solar/Wind Harmer
14.519
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
10.291
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.335
203962AF1-287 GEN
Solar/Wind Harmer
2.516
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.526
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
3.463
970679AG2-439 GEN
Solar/Wind Harmer
0.781
970643AG2-418 GEN
Solar/Wind Harmer
1.568
237043AE2-125 C
Solar/Wind Harmer
0.188
203843AF2-002_GEN
Solar/Wind Harmer
3.078
970631AG2-411 GEN
Solar/Wind Harmer
19.3
20088826HIGHLAND
Solar/Wind Harmer
4.945
971279AH1-102 GEN
Solar/Wind Harmer
24.258
957561AF2-050 GEN
Solar/Wind Harmer
14.683
971423AH1-203 GEN
Solar/Wind Harmer
19.574
20094526CT_V3-030
Solar/Wind Harmer
1.97
964201AG1-281 GEN
Solar/Wind Harmer
1.661
20089226LOOKOUT
Solar/Wind Harmer
1.977
203987AE2-118 C
Solar/Wind Harmer
4.301
970713AG2-456 GEN
Solar/Wind Harmer
16.236
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
3.148
203954AE2-126 C
Solar/Wind Harmer
1.047
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.465
971183AH1-050 GEN
Solar/Wind Harmer
6.437
238183AE2-316 GEN
Solar/Wind Harmer
6.683
20072226SHAWVL 2
Adder
21.555
959471AF2-238 GEN
Solar/Wind Harmer
0.949
970337AG2-221 GEN
Solar/Wind Harmer
3.138
970647AG2-420 GEN
Solar/Wind Harmer
0.365
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
5.299
203961AE2-224 GEN
Solar/Wind Harmer
8.894
203844AF2-092 C
Solar/Wind Harmer
3.506
203850AG1-041 C
Solar/Wind Harmer
3.502
20091526CHSTN_FL
Solar/Wind Harmer
2.329
20090526Q36
Solar/Wind Harmer
3.441
203993AD2-133_GEN1
Solar/Wind Harmer
3.441
941231AE2-117 GEN
Solar/Wind Harmer
1.211
940863AE2-074 GEN
Solar/Wind Harmer
3.489
965121AG1-377 GEN
Solar/Wind Harmer
4.003
203804AE2-113_GEN
Solar/Wind Harmer
9.109
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.344
203846AF2-130 C
Solar/Wind Harmer
0.933
970555AG2-356 GEN
Solar/Wind Harmer
3.138
970663AG2-429 GEN
Solar/Wind Harmer
10.602
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.254
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
15.211
971321AH1-140 GEN
Solar/Wind Harmer
2.948
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.691
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
11.357
203857AF2-221 C
Solar/Wind Harmer
4.639
970123AG2-090 GEN
Solar/Wind Harmer
4.33
203839AF1-321 GEN
Solar/Wind Harmer
6.155
20084626FORWARD
Solar/Wind Harmer
2.422
203940AF1-140 C
Solar/Wind Harmer
1.435
971441AH1-212 GEN
Solar/Wind Harmer
5.776
20088926STNY CRK
Solar/Wind Harmer
3.452
971427AH1-205 GEN
Solar/Wind Harmer
4.168
20088626ARWF_N39
Solar/Wind Harmer
5.22
20303426NA_O38_P22
Solar/Wind Harmer
4.225
20083426SW_E13_K22
Solar/Wind Harmer
0.816
944781AF1-143 GEN
Solar/Wind Harmer
6.961
203853AF1-134 C O1
Solar/Wind Harmer
1.316
972077AH1-588 GEN
Solar/Wind Harmer
48.709
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
16.236
203952AE2-129 C
Solar/Wind Harmer
1.212
203946AE2-131 C
Solar/Wind Harmer
1.21
962411AG1-090 GEN
Solar/Wind Harmer
19.014
972075AH1-587 GEN
Solar/Wind Harmer
38.823
203955AF1-039 C O1
Solar/Wind Harmer
0.801
20398826ARMNA MT
Solar/Wind Harmer
3.922
203848AF2-166 C
Solar/Wind Harmer
3.264
946381AF1-302 GEN
Solar/Wind Harmer
3.344
238217AF1-153 C O1
Solar/Wind Harmer
0.956
970305AG2-200 GEN
Solar/Wind Harmer
3.131
203859AF2-294 C
Solar/Wind Harmer
2.59
970313AG2-206 GEN
Solar/Wind Harmer
7.24
216419AE2-001 C
Solar/Wind Harmer
2.717
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.658
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203963AG1-253 GEN
Solar/Wind Harmer
0.512
971931AH1-490 GEN
Solar/Wind Harmer
2.51
203947AF1-006 C
Solar/Wind Harmer
0.663
203860AG1-193 C
Solar/Wind Harmer
0.464
970511AG2-327 GEN
Solar/Wind Harmer
1.508
238206AE2-263_GEN
Solar/Wind Harmer
3.451
970267AG2-176 GEN
Solar/Wind Harmer
21.058
238215AE2-248 C
Solar/Wind Harmer
2.149
961971AG1-040 GEN
Solar/Wind Harmer
0.795
203835AF1-098 GEN
Solar/Wind Harmer
3.156
203813AE2-344_GEN
Solar/Wind Harmer
14.592
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
1.135
24035802GEN-Y1-012
Adder
0.244
961581Q1080_CY23
External Queue
26.08061408996582
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-2_PN-500-001T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-2_PN-500-001T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:133.46 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.88
MW Contribution:19.3
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
11.357
203857AF2-221 C
Solar/Wind Harmer
4.639
970123AG2-090 GEN
Solar/Wind Harmer
4.33
203839AF1-321 GEN
Solar/Wind Harmer
6.155
20084626FORWARD
Solar/Wind Harmer
2.422
203940AF1-140 C
Solar/Wind Harmer
1.435
971441AH1-212 GEN
Solar/Wind Harmer
5.776
20088926STNY CRK
Solar/Wind Harmer
3.452
971427AH1-205 GEN
Solar/Wind Harmer
4.168
20088626ARWF_N39
Solar/Wind Harmer
5.22
20303426NA_O38_P22
Solar/Wind Harmer
4.225
20083426SW_E13_K22
Solar/Wind Harmer
0.816
944781AF1-143 GEN
Solar/Wind Harmer
6.961
203853AF1-134 C O1
Solar/Wind Harmer
1.316
972077AH1-588 GEN
Solar/Wind Harmer
48.709
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
16.236
203952AE2-129 C
Solar/Wind Harmer
1.212
203946AE2-131 C
Solar/Wind Harmer
1.21
962411AG1-090 GEN
Solar/Wind Harmer
19.014
972075AH1-587 GEN
Solar/Wind Harmer
38.823
203955AF1-039 C O1
Solar/Wind Harmer
0.801
20398826ARMNA MT
Solar/Wind Harmer
3.922
203848AF2-166 C
Solar/Wind Harmer
3.264
946381AF1-302 GEN
Solar/Wind Harmer
3.344
238217AF1-153 C O1
Solar/Wind Harmer
0.956
970305AG2-200 GEN
Solar/Wind Harmer
3.131
203859AF2-294 C
Solar/Wind Harmer
2.59
970313AG2-206 GEN
Solar/Wind Harmer
7.24
216419AE2-001 C
Solar/Wind Harmer
2.717
203979AG1-198 GEN
Solar/Wind Harmer
0.483
971933AH1-491 GEN
Solar/Wind Harmer
2.658
203980AG1-197 GEN
Solar/Wind Harmer
0.604
203963AG1-253 GEN
Solar/Wind Harmer
0.512
971931AH1-490 GEN
Solar/Wind Harmer
2.51
203947AF1-006 C
Solar/Wind Harmer
0.663
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
5.299
203961AE2-224 GEN
Solar/Wind Harmer
8.894
203844AF2-092 C
Solar/Wind Harmer
3.506
203850AG1-041 C
Solar/Wind Harmer
3.502
20091526CHSTN_FL
Solar/Wind Harmer
2.329
20090526Q36
Solar/Wind Harmer
3.441
203993AD2-133_GEN1
Solar/Wind Harmer
3.441
941231AE2-117 GEN
Solar/Wind Harmer
1.211
940863AE2-074 GEN
Solar/Wind Harmer
3.489
965121AG1-377 GEN
Solar/Wind Harmer
4.003
203804AE2-113_GEN
Solar/Wind Harmer
9.109
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.344
203846AF2-130 C
Solar/Wind Harmer
0.933
970555AG2-356 GEN
Solar/Wind Harmer
3.138
970663AG2-429 GEN
Solar/Wind Harmer
10.602
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.329
966771AG1-548 GEN
Solar/Wind Harmer
19.254
966771AG1-548 GEN
Solar/Wind Harmer
3.731
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
15.211
971321AH1-140 GEN
Solar/Wind Harmer
2.948
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.691
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.856
971879AH1-460 GEN
Solar/Wind Harmer
20.37
203841AF2-001_GEN
Solar/Wind Harmer
6.155
971541AH1-268 GEN
Solar/Wind Harmer
10.324
971419AH1-201 GEN
Solar/Wind Harmer
8.962
970899AG2-561 GEN
Solar/Wind Harmer
5.553
203818AF1-086 GEN
Solar/Wind Harmer
6.382
20089126CSLMN_L13
Solar/Wind Harmer
2.031
20089026BF_G21_K23
Solar/Wind Harmer
1.608
960051AF2-296 GEN
Solar/Wind Harmer
4.354
945751AF1-240 GEN
Solar/Wind Harmer
3.41
971703AH1-357 GEN
Solar/Wind Harmer
4.059
971707AH1-359 GEN
Solar/Wind Harmer
4.059
965131AG1-378 GEN
Solar/Wind Harmer
4.003
20334926Z1-069 C
Solar/Wind Harmer
4.086
202652Y1-033 WT C
Solar/Wind Harmer
1.645
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.715
203932AE1-123
Adder
3.33
944411AF1-106 GEN
Solar/Wind Harmer
0.372
971185AH1-051 GEN
Solar/Wind Harmer
3.862
971355AH1-158 GEN
Solar/Wind Harmer
4.491
203856AF2-165 C
Solar/Wind Harmer
1.874
970647AG2-420 GEN
Solar/Wind Harmer
3.135
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
4.698
971127AH1-005 GEN
Solar/Wind Harmer
3.031
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.976
238202AE2-262_GEN
Solar/Wind Harmer
3.703
971627AH1-313 GEN
Solar/Wind Harmer
14.519
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
10.291
203830AF1-094 GEN
Solar/Wind Harmer
0.805
203948AG1-140 C
Solar/Wind Harmer
0.335
203962AF1-287 GEN
Solar/Wind Harmer
2.516
962511AG1-100 GEN
Solar/Wind Harmer
0.759
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
3.526
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
3.463
970679AG2-439 GEN
Solar/Wind Harmer
0.781
970643AG2-418 GEN
Solar/Wind Harmer
1.568
237043AE2-125 C
Solar/Wind Harmer
0.188
203843AF2-002_GEN
Solar/Wind Harmer
3.078
970631AG2-411 GEN
Solar/Wind Harmer
19.3
20088826HIGHLAND
Solar/Wind Harmer
4.945
971279AH1-102 GEN
Solar/Wind Harmer
24.258
957561AF2-050 GEN
Solar/Wind Harmer
14.683
971423AH1-203 GEN
Solar/Wind Harmer
19.574
20094526CT_V3-030
Solar/Wind Harmer
1.97
964201AG1-281 GEN
Solar/Wind Harmer
1.661
20089226LOOKOUT
Solar/Wind Harmer
1.977
203987AE2-118 C
Solar/Wind Harmer
4.301
970713AG2-456 GEN
Solar/Wind Harmer
16.236
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
964391AG1-301 GEN
Solar/Wind Harmer
1.193
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
3.148
203954AE2-126 C
Solar/Wind Harmer
1.047
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.465
971183AH1-050 GEN
Solar/Wind Harmer
6.437
238183AE2-316 GEN
Solar/Wind Harmer
6.683
20072226SHAWVL 2
Adder
21.555
959471AF2-238 GEN
Solar/Wind Harmer
0.949
970337AG2-221 GEN
Solar/Wind Harmer
3.138
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.464
970511AG2-327 GEN
Solar/Wind Harmer
1.508
238206AE2-263_GEN
Solar/Wind Harmer
3.451
970267AG2-176 GEN
Solar/Wind Harmer
21.058
238215AE2-248 C
Solar/Wind Harmer
2.149
961971AG1-040 GEN
Solar/Wind Harmer
0.795
203835AF1-098 GEN
Solar/Wind Harmer
3.156
203813AE2-344_GEN
Solar/Wind Harmer
14.592
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
1.135
24035802GEN-Y1-012
Adder
0.244
961581Q1080_CY23
External Queue
26.08061408996582
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P2-3_PN-230-0347-A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-230-0347-A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.4 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1307.34
MW Contribution:18.49
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
280.069
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.263
20083926HOMER C3
50/50
231.8
20083826HOMER C2
50/50
218.961
20092526R32
Solar/Wind Harmer
4.991
203844AF2-092 C
Solar/Wind Harmer
3.326
203850AG1-041 C
Solar/Wind Harmer
3.319
203961AE2-224 GEN
Solar/Wind Harmer
8.313
20091526CHSTN_FL
Solar/Wind Harmer
2.196
20090526Q36
Solar/Wind Harmer
3.279
203993AD2-133_GEN1
Solar/Wind Harmer
3.279
940863AE2-074 GEN
Solar/Wind Harmer
3.529
965121AG1-377 GEN
Solar/Wind Harmer
3.847
203804AE2-113_GEN
Solar/Wind Harmer
9.139
941231AE2-117 GEN
Solar/Wind Harmer
1.142
20083226HNSMLK 5
Adder
10.453
203855AF2-088 C
Solar/Wind Harmer
0.335
203846AF2-130 C
Solar/Wind Harmer
0.927
970555AG2-356 GEN
Solar/Wind Harmer
3.171
970663AG2-429 GEN
Solar/Wind Harmer
10.629
970663AG2-429 GEN
Solar/Wind Harmer
1.73
970677AG2-438 GEN
Solar/Wind Harmer
1.337
966771AG1-548 GEN
Solar/Wind Harmer
19.376
966771AG1-548 GEN
Solar/Wind Harmer
3.755
20084926LAKVU GN
Adder
0.243
203926AA2-133 GEN
Adder
2.612
971321AH1-140 GEN
Solar/Wind Harmer
14.65
971321AH1-140 GEN
Solar/Wind Harmer
2.839
20334726NME_Y1-047
Adder
2.345
20390726Y2-042
Adder
1.882
971055AG2-654 GEN
Solar/Wind Harmer
0.697
20083326SEWRDB34
50/50
10.123
20216026CON.GEN2
50/50
0.033
203841AF2-001_GEN
Solar/Wind Harmer
5.897
971879AH1-460 GEN
Solar/Wind Harmer
19.409
970125AG2-091 GEN
Solar/Wind Harmer
1.761
20079426CONEMAGH
Adder
3.479
971541AH1-268 GEN
Solar/Wind Harmer
9.67
971419AH1-201 GEN
Solar/Wind Harmer
8.545
970899AG2-561 GEN
Solar/Wind Harmer
5.321
203818AF1-086 GEN
Solar/Wind Harmer
6.126
20089126CSLMN_L13
Solar/Wind Harmer
1.942
20089026BF_G21_K23
Solar/Wind Harmer
1.537
945751AF1-240 GEN
Solar/Wind Harmer
3.316
960051AF2-296 GEN
Solar/Wind Harmer
4.2
971703AH1-357 GEN
Solar/Wind Harmer
4.103
971707AH1-359 GEN
Solar/Wind Harmer
4.103
20334926Z1-069 C
Solar/Wind Harmer
4.137
965131AG1-378 GEN
Solar/Wind Harmer
3.847
20082926HNSMLK 2
Adder
10.453
20083126HNSMLK 4
Adder
10.453
203854AF2-039 C
Solar/Wind Harmer
0.696
202652Y1-033 WT C
Solar/Wind Harmer
1.572
203932AE1-123
Adder
3.3
944411AF1-106 GEN
Solar/Wind Harmer
0.377
971185AH1-051 GEN
Solar/Wind Harmer
3.857
971355AH1-158 GEN
Solar/Wind Harmer
4.485
20120126WRREN CT
Adder
9.95
203856AF2-165 C
Solar/Wind Harmer
1.872
970647AG2-420 GEN
Solar/Wind Harmer
3.136
970335AG2-220 GEN
Solar/Wind Harmer
4.75
971127AH1-005 GEN
Solar/Wind Harmer
3.065
959441AF2-235 GEN
Solar/Wind Harmer
0.451
238219AF1-167 C
Solar/Wind Harmer
1.975
238202AE2-262_GEN
Solar/Wind Harmer
3.621
971627AH1-313 GEN
Solar/Wind Harmer
14.197
20335126GROZ1-110
Adder
3.21
20335226CANZ2-011
Adder
3.12
957161AF2-010 GEN
Solar/Wind Harmer
10.35
203830AF1-094 GEN
Solar/Wind Harmer
0.81
203948AG1-140 C
Solar/Wind Harmer
0.339
203962AF1-287 GEN
Solar/Wind Harmer
2.542
962511AG1-100 GEN
Solar/Wind Harmer
0.767
20328326MANOR_T86
Adder
0.175
20084926LAKVU GN
Adder
0.216
941421AE2-139 GEN
Solar/Wind Harmer
3.541
972271AH1-720 GEN
Adder
7.526
200917MEHOOPANY_G
Solar/Wind Harmer
3.49
970679AG2-439 GEN
Solar/Wind Harmer
0.787
970643AG2-418 GEN
Solar/Wind Harmer
1.488
237043AE2-125 C
Solar/Wind Harmer
0.181
203843AF2-002_GEN
Solar/Wind Harmer
2.948
970631AG2-411 GEN
Solar/Wind Harmer
18.493
20088826HIGHLAND
Solar/Wind Harmer
4.657
971279AH1-102 GEN
Solar/Wind Harmer
22.722
957561AF2-050 GEN
Solar/Wind Harmer
13.724
971423AH1-203 GEN
Solar/Wind Harmer
18.68
20094526CT_V3-030
Solar/Wind Harmer
1.866
964201AG1-281 GEN
Solar/Wind Harmer
1.565
20089226LOOKOUT
Solar/Wind Harmer
1.89
970713AG2-456 GEN
Solar/Wind Harmer
16.414
971705AH1-358 GEN
Solar/Wind Harmer
4.771
971709AH1-360 GEN
Solar/Wind Harmer
4.771
203987AE2-118 C
Solar/Wind Harmer
4.049
964391AG1-301 GEN
Solar/Wind Harmer
1.125
20082826HNSMLK 1
Adder
10.453
20083026HNSMLK 3
Adder
10.453
20091326SHAW-D
Adder
1.119
972169AH1-667 GEN
Solar/Wind Harmer
3.064
203954AE2-126 C
Solar/Wind Harmer
1.029
20326126BLOSSBCT
Adder
3.854
20335026MILZ1-092
Adder
3.809
944411AF1-106 GEN
Solar/Wind Harmer
3.509
971183AH1-050 GEN
Solar/Wind Harmer
6.429
959471AF2-238 GEN
Solar/Wind Harmer
0.959
970337AG2-221 GEN
Solar/Wind Harmer
3.171
238183AE2-316 GEN
Solar/Wind Harmer
6.666
970647AG2-420 GEN
Solar/Wind Harmer
0.365
20080926SITHE
50/50
0.901
946071AF1-272 GEN
Solar/Wind Harmer
11.144
203839AF1-321 GEN
Solar/Wind Harmer
5.897
20084626FORWARD
Solar/Wind Harmer
2.32
203857AF2-221 C
Solar/Wind Harmer
4.403
970123AG2-090 GEN
Solar/Wind Harmer
4.109
203940AF1-140 C
Solar/Wind Harmer
1.353
971441AH1-212 GEN
Solar/Wind Harmer
5.415
20088926STNY CRK
Solar/Wind Harmer
3.291
971427AH1-205 GEN
Solar/Wind Harmer
3.974
20083426SW_E13_K22
Solar/Wind Harmer
0.78
20088626ARWF_N39
Solar/Wind Harmer
4.882
20303426NA_O38_P22
Solar/Wind Harmer
3.952
944781AF1-143 GEN
Solar/Wind Harmer
6.655
203853AF1-134 C O1
Solar/Wind Harmer
1.27
972077AH1-588 GEN
Solar/Wind Harmer
49.242
972079AH1-589 GEN
Solar/Wind Harmer
40.557
970715AG2-457 GEN
Solar/Wind Harmer
16.414
972075AH1-587 GEN
Solar/Wind Harmer
39.041
203952AE2-129 C
Solar/Wind Harmer
1.165
203946AE2-131 C
Solar/Wind Harmer
1.163
962411AG1-090 GEN
Solar/Wind Harmer
18.273
20398826ARMNA MT
Solar/Wind Harmer
3.972
203955AF1-039 C O1
Solar/Wind Harmer
0.765
203848AF2-166 C
Solar/Wind Harmer
3.246
946381AF1-302 GEN
Solar/Wind Harmer
3.336
970305AG2-200 GEN
Solar/Wind Harmer
3.147
238217AF1-153 C O1
Solar/Wind Harmer
0.946
203859AF2-294 C
Solar/Wind Harmer
2.624
970313AG2-206 GEN
Solar/Wind Harmer
7.319
203980AG1-197 GEN
Solar/Wind Harmer
0.61
203979AG1-198 GEN
Solar/Wind Harmer
0.486
971933AH1-491 GEN
Solar/Wind Harmer
2.673
216419AE2-001 C
Solar/Wind Harmer
2.642
203963AG1-253 GEN
Solar/Wind Harmer
0.517
971931AH1-490 GEN
Solar/Wind Harmer
2.536
203947AF1-006 C
Solar/Wind Harmer
0.67
20072226SHAWVL 2
Adder
21.096
203860AG1-193 C
Solar/Wind Harmer
0.466
970511AG2-327 GEN
Solar/Wind Harmer
1.525
238206AE2-263_GEN
Solar/Wind Harmer
3.375
970267AG2-176 GEN
Solar/Wind Harmer
21.271
961971AG1-040 GEN
Solar/Wind Harmer
0.803
203835AF1-098 GEN
Solar/Wind Harmer
3.183
238215AE2-248 C
Solar/Wind Harmer
2.088
203813AE2-344_GEN
Solar/Wind Harmer
14.741
20084926LAKVU GN
Adder
0.216
970643AG2-418 GEN
Solar/Wind Harmer
0.692
971865AH1-452 GEN
Solar/Wind Harmer
1.138
24035802GEN-Y1-012
Adder
0.247
961581Q1080_CY23
External Queue
26.921693801879883
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.268
MECLTFEXP_MEC->PJM
CLTF
0.139
SIGELTFEXP_SIGE->PJM
CLTF
0.003
LGEELTFEXP_LGEE->PJM
CLTF
0.032
WECLTFEXP_WEC->PJM
CLTF
0.047
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.201
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.588
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.097
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041D_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.69 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1202.4
MW Contribution:15.01
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
7.766
20079426CONEMAGH
50/50
2.946
20216026CON.GEN2
50/50
0.029
203841AF2-001_GEN
Solar/Wind Harmer
4.784
971879AH1-460 GEN
Solar/Wind Harmer
15.704
970125AG2-091 GEN
Solar/Wind Harmer
1.422
970899AG2-561 GEN
Solar/Wind Harmer
4.654
971541AH1-268 GEN
Solar/Wind Harmer
8.031
971419AH1-201 GEN
Solar/Wind Harmer
6.931
203818AF1-086 GEN
Solar/Wind Harmer
5.413
971703AH1-357 GEN
Solar/Wind Harmer
4.032
971707AH1-359 GEN
Solar/Wind Harmer
4.032
20082926HNSMLK 2
Adder
11.599
20083126HNSMLK 4
Adder
11.599
945751AF1-240 GEN
Solar/Wind Harmer
3.086
960051AF2-296 GEN
Solar/Wind Harmer
3.786
20334926Z1-069 C
Solar/Wind Harmer
3.957
20120126WRREN CT
Adder
11.468
962511AG1-100 GEN
Solar/Wind Harmer
1.094
203948AG1-140 C
Solar/Wind Harmer
0.474
203962AF1-287 GEN
Solar/Wind Harmer
3.616
20084926LAKVU GN
Adder
0.315
20089126CSLMN_L13
Solar/Wind Harmer
1.572
20089026BF_G21_K23
Solar/Wind Harmer
1.245
203830AF1-094 GEN
Solar/Wind Harmer
1.08
957161AF2-010 GEN
Solar/Wind Harmer
13.717
970647AG2-420 GEN
Solar/Wind Harmer
3.534
959441AF2-235 GEN
Solar/Wind Harmer
0.532
203856AF2-165 C
Solar/Wind Harmer
2.091
971185AH1-051 GEN
Solar/Wind Harmer
4.258
971355AH1-158 GEN
Solar/Wind Harmer
4.951
965131AG1-378 GEN
Solar/Wind Harmer
3.434
203932AE1-123
Adder
3.299
944411AF1-106 GEN
Solar/Wind Harmer
0.363
203854AF2-039 C
Solar/Wind Harmer
0.651
970335AG2-220 GEN
Solar/Wind Harmer
4.563
971127AH1-005 GEN
Solar/Wind Harmer
2.944
238219AF1-167 C
Solar/Wind Harmer
1.927
238202AE2-262_GEN
Solar/Wind Harmer
3.473
971627AH1-313 GEN
Solar/Wind Harmer
13.615
202652Y1-033 WT C
Solar/Wind Harmer
1.27
20335126GROZ1-110
Adder
3.117
20335226CANZ2-011
Adder
3.029
20328326MANOR_T86
Adder
0.172
941421AE2-139 GEN
Solar/Wind Harmer
3.495
972271AH1-720 GEN
Adder
7.443
200917MEHOOPANY_G
Solar/Wind Harmer
3.506
970679AG2-439 GEN
Solar/Wind Harmer
0.812
970643AG2-418 GEN
Solar/Wind Harmer
1.404
20080926SITHE
50/50
0.749
946071AF1-272 GEN
Solar/Wind Harmer
10.016
203839AF1-321 GEN
Solar/Wind Harmer
4.784
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.555
970123AG2-090 GEN
Solar/Wind Harmer
3.318
203940AF1-140 C
Solar/Wind Harmer
1.099
971441AH1-212 GEN
Solar/Wind Harmer
4.41
20088926STNY CRK
Solar/Wind Harmer
2.669
971427AH1-205 GEN
Solar/Wind Harmer
3.224
20083426SW_E13_K22
Solar/Wind Harmer
0.632
20088626ARWF_N39
Solar/Wind Harmer
3.934
20303426NA_O38_P22
Solar/Wind Harmer
3.185
972077AH1-588 GEN
Solar/Wind Harmer
48.381
972079AH1-589 GEN
Solar/Wind Harmer
39.849
970715AG2-457 GEN
Solar/Wind Harmer
16.127
972075AH1-587 GEN
Solar/Wind Harmer
38.03
203853AF1-134 C O1
Solar/Wind Harmer
1.144
203980AG1-197 GEN
Solar/Wind Harmer
0.829
970305AG2-200 GEN
Solar/Wind Harmer
3.627
971931AH1-490 GEN
Solar/Wind Harmer
3.618
203963AG1-253 GEN
Solar/Wind Harmer
0.724
203947AF1-006 C
Solar/Wind Harmer
1.003
20083726HOMER C1
50/50
232.962
20215826CON.GEN1
50/50
0.04
20063626IUP CO-G
50/50
0.235
20083926HOMER C3
50/50
202.334
20083826HOMER C2
50/50
191.128
20092526R32
Solar/Wind Harmer
4.027
203844AF2-092 C
Solar/Wind Harmer
2.7
203850AG1-041 C
Solar/Wind Harmer
2.694
203961AE2-224 GEN
Solar/Wind Harmer
6.665
20091526CHSTN_FL
Solar/Wind Harmer
1.814
20083226HNSMLK 5
Adder
11.599
940863AE2-074 GEN
Solar/Wind Harmer
3.399
203804AE2-113_GEN
Solar/Wind Harmer
8.922
944781AF1-143 GEN
Solar/Wind Harmer
5.389
203979AG1-198 GEN
Solar/Wind Harmer
0.648
971933AH1-491 GEN
Solar/Wind Harmer
3.565
203952AE2-129 C
Solar/Wind Harmer
1.04
203946AE2-131 C
Solar/Wind Harmer
1.038
962411AG1-090 GEN
Solar/Wind Harmer
16.312
203848AF2-166 C
Solar/Wind Harmer
3.417
20398826ARMNA MT
Solar/Wind Harmer
3.781
946381AF1-302 GEN
Solar/Wind Harmer
3.239
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203859AF2-294 C
Solar/Wind Harmer
2.541
970313AG2-206 GEN
Solar/Wind Harmer
7.034
203955AF1-039 C O1
Solar/Wind Harmer
0.618
216419AE2-001 C
Solar/Wind Harmer
2.514
20090526Q36
Solar/Wind Harmer
2.835
203993AD2-133_GEN1
Solar/Wind Harmer
2.835
20084926LAKVU GN
Adder
0.354
966771AG1-548 GEN
Solar/Wind Harmer
26.067
966771AG1-548 GEN
Solar/Wind Harmer
5.052
970677AG2-438 GEN
Solar/Wind Harmer
1.783
965121AG1-377 GEN
Solar/Wind Harmer
3.434
203846AF2-130 C
Solar/Wind Harmer
0.976
941231AE2-117 GEN
Solar/Wind Harmer
0.965
203855AF2-088 C
Solar/Wind Harmer
0.313
970555AG2-356 GEN
Solar/Wind Harmer
3.037
970663AG2-429 GEN
Solar/Wind Harmer
10.314
970663AG2-429 GEN
Solar/Wind Harmer
1.679
203926AA2-133 GEN
Adder
2.591
20334726NME_Y1-047
Adder
2.355
971321AH1-140 GEN
Solar/Wind Harmer
12.539
971321AH1-140 GEN
Solar/Wind Harmer
2.43
20390726Y2-042
Adder
1.942
971055AG2-654 GEN
Solar/Wind Harmer
0.656
20080526COLVER13
50/50
1.629
203843AF2-002_GEN
Solar/Wind Harmer
2.392
970631AG2-411 GEN
Solar/Wind Harmer
15.013
971279AH1-102 GEN
Solar/Wind Harmer
18.871
20088826HIGHLAND
Solar/Wind Harmer
3.758
20094526CT_V3-030
Solar/Wind Harmer
1.576
957561AF2-050 GEN
Solar/Wind Harmer
11.004
971423AH1-203 GEN
Solar/Wind Harmer
15.149
964201AG1-281 GEN
Solar/Wind Harmer
1.276
970713AG2-456 GEN
Solar/Wind Harmer
16.127
971705AH1-358 GEN
Solar/Wind Harmer
4.688
971709AH1-360 GEN
Solar/Wind Harmer
4.688
20082826HNSMLK 1
Adder
11.599
20083026HNSMLK 3
Adder
11.599
970267AG2-176 GEN
Solar/Wind Harmer
27.615
961971AG1-040 GEN
Solar/Wind Harmer
1.101
203860AG1-193 C
Solar/Wind Harmer
0.551
203813AE2-344_GEN
Solar/Wind Harmer
21.054
203835AF1-098 GEN
Solar/Wind Harmer
4.363
20084926LAKVU GN
Adder
0.315
20089226LOOKOUT
Solar/Wind Harmer
1.531
970647AG2-420 GEN
Solar/Wind Harmer
0.411
971183AH1-050 GEN
Solar/Wind Harmer
7.097
203987AE2-118 C
Solar/Wind Harmer
3.38
203954AE2-126 C
Solar/Wind Harmer
0.989
20335026MILZ1-092
Adder
3.662
944411AF1-106 GEN
Solar/Wind Harmer
3.374
20326126BLOSSBCT
Adder
3.678
20091326SHAW-D
Adder
1.047
972169AH1-667 GEN
Solar/Wind Harmer
2.865
964391AG1-301 GEN
Solar/Wind Harmer
0.95
238183AE2-316 GEN
Solar/Wind Harmer
6.472
959471AF2-238 GEN
Solar/Wind Harmer
0.918
970337AG2-221 GEN
Solar/Wind Harmer
3.037
20072226SHAWVL 2
Adder
20.17
970511AG2-327 GEN
Solar/Wind Harmer
1.465
238206AE2-263_GEN
Solar/Wind Harmer
3.236
238215AE2-248 C
Solar/Wind Harmer
1.984
970643AG2-418 GEN
Solar/Wind Harmer
0.653
971865AH1-452 GEN
Solar/Wind Harmer
1.05
961581Q1080_CY23
External Queue
18.789121627807617
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.393
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.223
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.268
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.224
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.791
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.358
G-007ALTFEXP_G-007A->PJM
CMTX
1.421
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.685
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o ATSI_P2-3_CEI-345-041E_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_CEI-345-041E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.69 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1202.4
MW Contribution:15.01
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
232.962
20215826CON.GEN1
50/50
0.04
20083326SEWRDB34
50/50
7.766
20079426CONEMAGH
50/50
2.946
20216026CON.GEN2
50/50
0.029
203841AF2-001_GEN
Solar/Wind Harmer
4.784
971879AH1-460 GEN
Solar/Wind Harmer
15.704
970125AG2-091 GEN
Solar/Wind Harmer
1.422
970899AG2-561 GEN
Solar/Wind Harmer
4.654
20063626IUP CO-G
50/50
0.235
20083926HOMER C3
50/50
202.334
20083826HOMER C2
50/50
191.128
20092526R32
Solar/Wind Harmer
4.027
203844AF2-092 C
Solar/Wind Harmer
2.7
203850AG1-041 C
Solar/Wind Harmer
2.694
203961AE2-224 GEN
Solar/Wind Harmer
6.665
20091526CHSTN_FL
Solar/Wind Harmer
1.814
20083226HNSMLK 5
Adder
11.599
940863AE2-074 GEN
Solar/Wind Harmer
3.399
203804AE2-113_GEN
Solar/Wind Harmer
8.922
20090526Q36
Solar/Wind Harmer
2.835
203993AD2-133_GEN1
Solar/Wind Harmer
2.835
20084926LAKVU GN
Adder
0.354
966771AG1-548 GEN
Solar/Wind Harmer
26.067
966771AG1-548 GEN
Solar/Wind Harmer
5.052
970677AG2-438 GEN
Solar/Wind Harmer
1.783
965121AG1-377 GEN
Solar/Wind Harmer
3.434
203846AF2-130 C
Solar/Wind Harmer
0.976
941231AE2-117 GEN
Solar/Wind Harmer
0.965
971541AH1-268 GEN
Solar/Wind Harmer
8.031
971419AH1-201 GEN
Solar/Wind Harmer
6.931
203818AF1-086 GEN
Solar/Wind Harmer
5.413
971703AH1-357 GEN
Solar/Wind Harmer
4.032
971707AH1-359 GEN
Solar/Wind Harmer
4.032
20082926HNSMLK 2
Adder
11.599
20083126HNSMLK 4
Adder
11.599
945751AF1-240 GEN
Solar/Wind Harmer
3.086
960051AF2-296 GEN
Solar/Wind Harmer
3.786
20334926Z1-069 C
Solar/Wind Harmer
3.957
20120126WRREN CT
Adder
11.468
962511AG1-100 GEN
Solar/Wind Harmer
1.094
203948AG1-140 C
Solar/Wind Harmer
0.474
203962AF1-287 GEN
Solar/Wind Harmer
3.616
20084926LAKVU GN
Adder
0.315
20089126CSLMN_L13
Solar/Wind Harmer
1.572
20089026BF_G21_K23
Solar/Wind Harmer
1.245
203830AF1-094 GEN
Solar/Wind Harmer
1.08
957161AF2-010 GEN
Solar/Wind Harmer
13.717
970647AG2-420 GEN
Solar/Wind Harmer
3.534
959441AF2-235 GEN
Solar/Wind Harmer
0.532
203856AF2-165 C
Solar/Wind Harmer
2.091
971185AH1-051 GEN
Solar/Wind Harmer
4.258
971355AH1-158 GEN
Solar/Wind Harmer
4.951
965131AG1-378 GEN
Solar/Wind Harmer
3.434
203932AE1-123
Adder
3.299
944411AF1-106 GEN
Solar/Wind Harmer
0.363
203854AF2-039 C
Solar/Wind Harmer
0.651
970335AG2-220 GEN
Solar/Wind Harmer
4.563
971127AH1-005 GEN
Solar/Wind Harmer
2.944
238219AF1-167 C
Solar/Wind Harmer
1.927
238202AE2-262_GEN
Solar/Wind Harmer
3.473
971627AH1-313 GEN
Solar/Wind Harmer
13.615
202652Y1-033 WT C
Solar/Wind Harmer
1.27
20335126GROZ1-110
Adder
3.117
20335226CANZ2-011
Adder
3.029
20328326MANOR_T86
Adder
0.172
941421AE2-139 GEN
Solar/Wind Harmer
3.495
972271AH1-720 GEN
Adder
7.443
200917MEHOOPANY_G
Solar/Wind Harmer
3.506
970679AG2-439 GEN
Solar/Wind Harmer
0.812
970643AG2-418 GEN
Solar/Wind Harmer
1.404
20080526COLVER13
50/50
1.629
203843AF2-002_GEN
Solar/Wind Harmer
2.392
970631AG2-411 GEN
Solar/Wind Harmer
15.013
971279AH1-102 GEN
Solar/Wind Harmer
18.871
20088826HIGHLAND
Solar/Wind Harmer
3.758
20094526CT_V3-030
Solar/Wind Harmer
1.576
957561AF2-050 GEN
Solar/Wind Harmer
11.004
971423AH1-203 GEN
Solar/Wind Harmer
15.149
964201AG1-281 GEN
Solar/Wind Harmer
1.276
970713AG2-456 GEN
Solar/Wind Harmer
16.127
971705AH1-358 GEN
Solar/Wind Harmer
4.688
971709AH1-360 GEN
Solar/Wind Harmer
4.688
20082826HNSMLK 1
Adder
11.599
20083026HNSMLK 3
Adder
11.599
970267AG2-176 GEN
Solar/Wind Harmer
27.615
961971AG1-040 GEN
Solar/Wind Harmer
1.101
203860AG1-193 C
Solar/Wind Harmer
0.551
203813AE2-344_GEN
Solar/Wind Harmer
21.054
203835AF1-098 GEN
Solar/Wind Harmer
4.363
20084926LAKVU GN
Adder
0.315
20089226LOOKOUT
Solar/Wind Harmer
1.531
970647AG2-420 GEN
Solar/Wind Harmer
0.411
971183AH1-050 GEN
Solar/Wind Harmer
7.097
203987AE2-118 C
Solar/Wind Harmer
3.38
203954AE2-126 C
Solar/Wind Harmer
0.989
20335026MILZ1-092
Adder
3.662
944411AF1-106 GEN
Solar/Wind Harmer
3.374
20326126BLOSSBCT
Adder
3.678
20091326SHAW-D
Adder
1.047
972169AH1-667 GEN
Solar/Wind Harmer
2.865
964391AG1-301 GEN
Solar/Wind Harmer
0.95
238183AE2-316 GEN
Solar/Wind Harmer
6.472
959471AF2-238 GEN
Solar/Wind Harmer
0.918
970337AG2-221 GEN
Solar/Wind Harmer
3.037
20072226SHAWVL 2
Adder
20.17
970511AG2-327 GEN
Solar/Wind Harmer
1.465
238206AE2-263_GEN
Solar/Wind Harmer
3.236
238215AE2-248 C
Solar/Wind Harmer
1.984
970643AG2-418 GEN
Solar/Wind Harmer
0.653
971865AH1-452 GEN
Solar/Wind Harmer
1.05
20080926SITHE
50/50
0.749
946071AF1-272 GEN
Solar/Wind Harmer
10.016
203839AF1-321 GEN
Solar/Wind Harmer
4.784
20084626FORWARD
Solar/Wind Harmer
1.884
203857AF2-221 C
Solar/Wind Harmer
3.555
970123AG2-090 GEN
Solar/Wind Harmer
3.318
203940AF1-140 C
Solar/Wind Harmer
1.099
971441AH1-212 GEN
Solar/Wind Harmer
4.41
20088926STNY CRK
Solar/Wind Harmer
2.669
971427AH1-205 GEN
Solar/Wind Harmer
3.224
20083426SW_E13_K22
Solar/Wind Harmer
0.632
20088626ARWF_N39
Solar/Wind Harmer
3.934
20303426NA_O38_P22
Solar/Wind Harmer
3.185
972077AH1-588 GEN
Solar/Wind Harmer
48.381
972079AH1-589 GEN
Solar/Wind Harmer
39.849
970715AG2-457 GEN
Solar/Wind Harmer
16.127
972075AH1-587 GEN
Solar/Wind Harmer
38.03
203853AF1-134 C O1
Solar/Wind Harmer
1.144
203980AG1-197 GEN
Solar/Wind Harmer
0.829
970305AG2-200 GEN
Solar/Wind Harmer
3.627
971931AH1-490 GEN
Solar/Wind Harmer
3.618
203963AG1-253 GEN
Solar/Wind Harmer
0.724
203947AF1-006 C
Solar/Wind Harmer
1.003
944781AF1-143 GEN
Solar/Wind Harmer
5.389
203979AG1-198 GEN
Solar/Wind Harmer
0.648
971933AH1-491 GEN
Solar/Wind Harmer
3.565
203952AE2-129 C
Solar/Wind Harmer
1.04
203946AE2-131 C
Solar/Wind Harmer
1.038
962411AG1-090 GEN
Solar/Wind Harmer
16.312
203848AF2-166 C
Solar/Wind Harmer
3.417
20398826ARMNA MT
Solar/Wind Harmer
3.781
946381AF1-302 GEN
Solar/Wind Harmer
3.239
238217AF1-153 C O1
Solar/Wind Harmer
0.928
203859AF2-294 C
Solar/Wind Harmer
2.541
970313AG2-206 GEN
Solar/Wind Harmer
7.034
203955AF1-039 C O1
Solar/Wind Harmer
0.618
216419AE2-001 C
Solar/Wind Harmer
2.514
203855AF2-088 C
Solar/Wind Harmer
0.313
970555AG2-356 GEN
Solar/Wind Harmer
3.037
970663AG2-429 GEN
Solar/Wind Harmer
10.314
970663AG2-429 GEN
Solar/Wind Harmer
1.679
203926AA2-133 GEN
Adder
2.591
20334726NME_Y1-047
Adder
2.355
971321AH1-140 GEN
Solar/Wind Harmer
12.539
971321AH1-140 GEN
Solar/Wind Harmer
2.43
20390726Y2-042
Adder
1.942
971055AG2-654 GEN
Solar/Wind Harmer
0.656
961581Q1080_CY23
External Queue
18.789121627807617
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.393
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.223
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
4.268
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.224
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.791
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.358
G-007ALTFEXP_G-007A->PJM
CMTX
1.421
CBM NorthLTFEXP_CBM-N->PJM
CBM
36.685
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-033T_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-033T_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.79 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1085.77
MW Contribution:15.45
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.04
20079426CONEMAGH
50/50
3.164
20083326SEWRDB34
50/50
7.896
203841AF2-001_GEN
Solar/Wind Harmer
4.93
971879AH1-460 GEN
Solar/Wind Harmer
16.196
970125AG2-091 GEN
Solar/Wind Harmer
1.467
971541AH1-268 GEN
Solar/Wind Harmer
8.477
970899AG2-561 GEN
Solar/Wind Harmer
4.805
971419AH1-201 GEN
Solar/Wind Harmer
7.128
203818AF1-086 GEN
Solar/Wind Harmer
5.441
960051AF2-296 GEN
Solar/Wind Harmer
3.667
20089126CSLMN_L13
Solar/Wind Harmer
1.613
20089026BF_G21_K23
Solar/Wind Harmer
1.277
945751AF1-240 GEN
Solar/Wind Harmer
2.88
971703AH1-357 GEN
Solar/Wind Harmer
3.369
971707AH1-359 GEN
Solar/Wind Harmer
3.369
20334926Z1-069 C
Solar/Wind Harmer
3.414
965131AG1-378 GEN
Solar/Wind Harmer
3.23
203854AF2-039 C
Solar/Wind Harmer
0.588
20082926HNSMLK 2
Adder
8.406
20083126HNSMLK 4
Adder
8.406
944411AF1-106 GEN
Solar/Wind Harmer
0.314
202652Y1-033 WT C
Solar/Wind Harmer
1.296
203932AE1-123
Adder
2.724
971185AH1-051 GEN
Solar/Wind Harmer
3.15
971355AH1-158 GEN
Solar/Wind Harmer
3.662
20120126WRREN CT
Adder
8.111
970335AG2-220 GEN
Solar/Wind Harmer
3.975
971127AH1-005 GEN
Solar/Wind Harmer
2.565
203856AF2-165 C
Solar/Wind Harmer
1.528
970647AG2-420 GEN
Solar/Wind Harmer
2.555
959441AF2-235 GEN
Solar/Wind Harmer
0.367
238202AE2-262_GEN
Solar/Wind Harmer
3.041
971627AH1-313 GEN
Solar/Wind Harmer
11.922
238219AF1-167 C
Solar/Wind Harmer
1.571
20335126GROZ1-110
Adder
2.703
20335226CANZ2-011
Adder
2.627
957161AF2-010 GEN
Solar/Wind Harmer
8.34
203830AF1-094 GEN
Solar/Wind Harmer
0.652
20328326MANOR_T86
Adder
0.149
203948AG1-140 C
Solar/Wind Harmer
0.272
203962AF1-287 GEN
Solar/Wind Harmer
2.032
962511AG1-100 GEN
Solar/Wind Harmer
0.612
941421AE2-139 GEN
Solar/Wind Harmer
3.012
20084926LAKVU GN
Adder
0.172
972271AH1-720 GEN
Adder
6.411
200917MEHOOPANY_G
Solar/Wind Harmer
3.003
970679AG2-439 GEN
Solar/Wind Harmer
0.69
970643AG2-418 GEN
Solar/Wind Harmer
1.293
20080926SITHE
50/50
0.742
946071AF1-272 GEN
Solar/Wind Harmer
10.956
203839AF1-321 GEN
Solar/Wind Harmer
4.93
20084626FORWARD
Solar/Wind Harmer
1.939
203857AF2-221 C
Solar/Wind Harmer
3.668
970123AG2-090 GEN
Solar/Wind Harmer
3.424
203940AF1-140 C
Solar/Wind Harmer
1.128
971441AH1-212 GEN
Solar/Wind Harmer
4.542
20088926STNY CRK
Solar/Wind Harmer
2.745
971427AH1-205 GEN
Solar/Wind Harmer
3.315
20083426SW_E13_K22
Solar/Wind Harmer
0.651
20088626ARWF_N39
Solar/Wind Harmer
3.947
20303426NA_O38_P22
Solar/Wind Harmer
3.195
203853AF1-134 C O1
Solar/Wind Harmer
1.109
944781AF1-143 GEN
Solar/Wind Harmer
5.53
972077AH1-588 GEN
Solar/Wind Harmer
40.423
972079AH1-589 GEN
Solar/Wind Harmer
33.294
970715AG2-457 GEN
Solar/Wind Harmer
13.474
203952AE2-129 C
Solar/Wind Harmer
0.978
203946AE2-131 C
Solar/Wind Harmer
0.977
962411AG1-090 GEN
Solar/Wind Harmer
15.344
972075AH1-587 GEN
Solar/Wind Harmer
32.161
20398826ARMNA MT
Solar/Wind Harmer
3.307
203955AF1-039 C O1
Solar/Wind Harmer
0.631
203848AF2-166 C
Solar/Wind Harmer
2.666
238217AF1-153 C O1
Solar/Wind Harmer
0.781
203859AF2-294 C
Solar/Wind Harmer
2.193
970305AG2-200 GEN
Solar/Wind Harmer
2.566
946381AF1-302 GEN
Solar/Wind Harmer
2.696
970313AG2-206 GEN
Solar/Wind Harmer
6.127
216419AE2-001 C
Solar/Wind Harmer
2.228
203979AG1-198 GEN
Solar/Wind Harmer
0.391
971933AH1-491 GEN
Solar/Wind Harmer
2.153
203980AG1-197 GEN
Solar/Wind Harmer
0.488
203963AG1-253 GEN
Solar/Wind Harmer
0.415
971931AH1-490 GEN
Solar/Wind Harmer
2.026
203947AF1-006 C
Solar/Wind Harmer
0.534
20080526COLVER13
50/50
1.682
203843AF2-002_GEN
Solar/Wind Harmer
2.465
970631AG2-411 GEN
Solar/Wind Harmer
15.45
971279AH1-102 GEN
Solar/Wind Harmer
19.918
20088826HIGHLAND
Solar/Wind Harmer
3.872
20094526CT_V3-030
Solar/Wind Harmer
1.616
971423AH1-203 GEN
Solar/Wind Harmer
15.583
957561AF2-050 GEN
Solar/Wind Harmer
11.064
964201AG1-281 GEN
Solar/Wind Harmer
1.3
20089226LOOKOUT
Solar/Wind Harmer
1.571
970713AG2-456 GEN
Solar/Wind Harmer
13.474
971705AH1-358 GEN
Solar/Wind Harmer
3.917
971709AH1-360 GEN
Solar/Wind Harmer
3.917
203987AE2-118 C
Solar/Wind Harmer
3.348
964391AG1-301 GEN
Solar/Wind Harmer
0.933
20091326SHAW-D
Adder
0.945
972169AH1-667 GEN
Solar/Wind Harmer
2.587
20082826HNSMLK 1
Adder
8.406
20083026HNSMLK 3
Adder
8.406
203954AE2-126 C
Solar/Wind Harmer
0.861
20326126BLOSSBCT
Adder
3.21
20335026MILZ1-092
Adder
3.17
944411AF1-106 GEN
Solar/Wind Harmer
2.921
959471AF2-238 GEN
Solar/Wind Harmer
0.801
970337AG2-221 GEN
Solar/Wind Harmer
2.649
971183AH1-050 GEN
Solar/Wind Harmer
5.249
20072226SHAWVL 2
Adder
17.701
238183AE2-316 GEN
Solar/Wind Harmer
5.388
970647AG2-420 GEN
Solar/Wind Harmer
0.297
970511AG2-327 GEN
Solar/Wind Harmer
1.276
203860AG1-193 C
Solar/Wind Harmer
0.377
238206AE2-263_GEN
Solar/Wind Harmer
2.834
970267AG2-176 GEN
Solar/Wind Harmer
17.067
238215AE2-248 C
Solar/Wind Harmer
1.762
961971AG1-040 GEN
Solar/Wind Harmer
0.643
203835AF1-098 GEN
Solar/Wind Harmer
2.559
203813AE2-344_GEN
Solar/Wind Harmer
11.778
20084926LAKVU GN
Adder
0.172
970643AG2-418 GEN
Solar/Wind Harmer
0.601
24035802GEN-Y1-012
Adder
0.184
20215826CON.GEN1
50/50
0.045
20083726HOMER C1
50/50
230.721
20063626IUP CO-G
50/50
0.254
20083926HOMER C3
50/50
190.005
20083826HOMER C2
50/50
179.482
20092526R32
Solar/Wind Harmer
4.149
203844AF2-092 C
Solar/Wind Harmer
2.774
203850AG1-041 C
Solar/Wind Harmer
2.767
203961AE2-224 GEN
Solar/Wind Harmer
6.702
20091526CHSTN_FL
Solar/Wind Harmer
1.829
20090526Q36
Solar/Wind Harmer
2.744
203993AD2-133_GEN1
Solar/Wind Harmer
2.744
940863AE2-074 GEN
Solar/Wind Harmer
2.907
965121AG1-377 GEN
Solar/Wind Harmer
3.23
203804AE2-113_GEN
Solar/Wind Harmer
7.536
941231AE2-117 GEN
Solar/Wind Harmer
0.948
203855AF2-088 C
Solar/Wind Harmer
0.283
20083226HNSMLK 5
Adder
8.406
203846AF2-130 C
Solar/Wind Harmer
0.762
970555AG2-356 GEN
Solar/Wind Harmer
2.649
970663AG2-429 GEN
Solar/Wind Harmer
8.45
970663AG2-429 GEN
Solar/Wind Harmer
1.376
970677AG2-438 GEN
Solar/Wind Harmer
1.077
966771AG1-548 GEN
Solar/Wind Harmer
15.594
966771AG1-548 GEN
Solar/Wind Harmer
3.022
20084926LAKVU GN
Adder
0.194
203926AA2-133 GEN
Adder
2.229
20334726NME_Y1-047
Adder
2.018
20390726Y2-042
Adder
1.652
961581Q1080_CY23
External Queue
21.849340438842773
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.217
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.677
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
1.563
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.181
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.982
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.307
G-007ALTFEXP_G-007A->PJM
CMTX
0.44
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.391
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-059_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-059_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:110.5 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1082.93
MW Contribution:14.45
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.735
946071AF1-272 GEN
Solar/Wind Harmer
9.451
203839AF1-321 GEN
Solar/Wind Harmer
4.608
20084626FORWARD
Solar/Wind Harmer
1.813
20083326SEWRDB34
50/50
7.501
20079426CONEMAGH
50/50
2.811
20216026CON.GEN2
50/50
0.027
203857AF2-221 C
Solar/Wind Harmer
3.418
970123AG2-090 GEN
Solar/Wind Harmer
3.19
203940AF1-140 C
Solar/Wind Harmer
1.046
20088926STNY CRK
Solar/Wind Harmer
2.561
971427AH1-205 GEN
Solar/Wind Harmer
3.093
971441AH1-212 GEN
Solar/Wind Harmer
4.171
20083426SW_E13_K22
Solar/Wind Harmer
0.608
20088626ARWF_N39
Solar/Wind Harmer
3.759
20303426NA_O38_P22
Solar/Wind Harmer
3.043
972077AH1-588 GEN
Solar/Wind Harmer
41.421
972079AH1-589 GEN
Solar/Wind Harmer
34.116
970715AG2-457 GEN
Solar/Wind Harmer
13.807
944781AF1-143 GEN
Solar/Wind Harmer
5.173
203853AF1-134 C O1
Solar/Wind Harmer
0.993
972075AH1-587 GEN
Solar/Wind Harmer
32.353
203952AE2-129 C
Solar/Wind Harmer
0.908
203946AE2-131 C
Solar/Wind Harmer
0.906
962411AG1-090 GEN
Solar/Wind Harmer
14.236
20398826ARMNA MT
Solar/Wind Harmer
3.393
203859AF2-294 C
Solar/Wind Harmer
2.251
970305AG2-200 GEN
Solar/Wind Harmer
2.617
970313AG2-206 GEN
Solar/Wind Harmer
6.254
203955AF1-039 C O1
Solar/Wind Harmer
0.592
946381AF1-302 GEN
Solar/Wind Harmer
2.467
238217AF1-153 C O1
Solar/Wind Harmer
0.705
203980AG1-197 GEN
Solar/Wind Harmer
0.527
203963AG1-253 GEN
Solar/Wind Harmer
0.442
971931AH1-490 GEN
Solar/Wind Harmer
2.182
203848AF2-166 C
Solar/Wind Harmer
2.163
203979AG1-198 GEN
Solar/Wind Harmer
0.392
971933AH1-491 GEN
Solar/Wind Harmer
2.157
216419AE2-001 C
Solar/Wind Harmer
2.082
203947AF1-006 C
Solar/Wind Harmer
0.573
203841AF2-001_GEN
Solar/Wind Harmer
4.608
971879AH1-460 GEN
Solar/Wind Harmer
15.111
970125AG2-091 GEN
Solar/Wind Harmer
1.367
971541AH1-268 GEN
Solar/Wind Harmer
7.445
971419AH1-201 GEN
Solar/Wind Harmer
6.65
970899AG2-561 GEN
Solar/Wind Harmer
4.158
203818AF1-086 GEN
Solar/Wind Harmer
4.785
971703AH1-357 GEN
Solar/Wind Harmer
3.452
971707AH1-359 GEN
Solar/Wind Harmer
3.452
20089126CSLMN_L13
Solar/Wind Harmer
1.509
20089026BF_G21_K23
Solar/Wind Harmer
1.195
20082926HNSMLK 2
Adder
9.882
20083126HNSMLK 4
Adder
9.882
20334926Z1-069 C
Solar/Wind Harmer
3.506
960051AF2-296 GEN
Solar/Wind Harmer
3.283
965131AG1-378 GEN
Solar/Wind Harmer
2.997
945751AF1-240 GEN
Solar/Wind Harmer
2.353
944411AF1-106 GEN
Solar/Wind Harmer
0.323
203854AF2-039 C
Solar/Wind Harmer
0.545
970335AG2-220 GEN
Solar/Wind Harmer
4.059
971127AH1-005 GEN
Solar/Wind Harmer
2.618
20120126WRREN CT
Adder
8.274
202652Y1-033 WT C
Solar/Wind Harmer
1.216
970647AG2-420 GEN
Solar/Wind Harmer
2.331
20335126GROZ1-110
Adder
2.708
20335226CANZ2-011
Adder
2.632
971185AH1-051 GEN
Solar/Wind Harmer
2.79
971355AH1-158 GEN
Solar/Wind Harmer
3.244
203856AF2-165 C
Solar/Wind Harmer
1.361
238202AE2-262_GEN
Solar/Wind Harmer
2.845
971627AH1-313 GEN
Solar/Wind Harmer
11.155
959441AF2-235 GEN
Solar/Wind Harmer
0.336
203948AG1-140 C
Solar/Wind Harmer
0.289
962511AG1-100 GEN
Solar/Wind Harmer
0.66
203962AF1-287 GEN
Solar/Wind Harmer
2.182
957161AF2-010 GEN
Solar/Wind Harmer
8.315
203830AF1-094 GEN
Solar/Wind Harmer
0.653
20328326MANOR_T86
Adder
0.15
20084926LAKVU GN
Adder
0.184
203932AE1-123
Adder
2.047
941421AE2-139 GEN
Solar/Wind Harmer
3.007
972271AH1-720 GEN
Adder
6.426
200917MEHOOPANY_G
Solar/Wind Harmer
3.022
238219AF1-167 C
Solar/Wind Harmer
0.965
970679AG2-439 GEN
Solar/Wind Harmer
0.69
970643AG2-418 GEN
Solar/Wind Harmer
1.201
203843AF2-002_GEN
Solar/Wind Harmer
2.304
970631AG2-411 GEN
Solar/Wind Harmer
14.452
20088826HIGHLAND
Solar/Wind Harmer
3.597
971279AH1-102 GEN
Solar/Wind Harmer
17.493
957561AF2-050 GEN
Solar/Wind Harmer
10.553
971423AH1-203 GEN
Solar/Wind Harmer
14.544
20094526CT_V3-030
Solar/Wind Harmer
1.447
964201AG1-281 GEN
Solar/Wind Harmer
1.21
970713AG2-456 GEN
Solar/Wind Harmer
13.807
971705AH1-358 GEN
Solar/Wind Harmer
4.014
971709AH1-360 GEN
Solar/Wind Harmer
4.014
20089226LOOKOUT
Solar/Wind Harmer
1.469
20082826HNSMLK 1
Adder
9.882
20083026HNSMLK 3
Adder
9.882
203987AE2-118 C
Solar/Wind Harmer
3.142
964391AG1-301 GEN
Solar/Wind Harmer
0.875
20326126BLOSSBCT
Adder
3.276
20335026MILZ1-092
Adder
3.257
944411AF1-106 GEN
Solar/Wind Harmer
3
959471AF2-238 GEN
Solar/Wind Harmer
0.817
970337AG2-221 GEN
Solar/Wind Harmer
2.703
203954AE2-126 C
Solar/Wind Harmer
0.814
20091326SHAW-D
Adder
0.876
972169AH1-667 GEN
Solar/Wind Harmer
2.399
970511AG2-327 GEN
Solar/Wind Harmer
1.303
203860AG1-193 C
Solar/Wind Harmer
0.379
970267AG2-176 GEN
Solar/Wind Harmer
18.45
20072226SHAWVL 2
Adder
16.516
238183AE2-316 GEN
Solar/Wind Harmer
4.93
970647AG2-420 GEN
Solar/Wind Harmer
0.271
971183AH1-050 GEN
Solar/Wind Harmer
4.649
961971AG1-040 GEN
Solar/Wind Harmer
0.694
238206AE2-263_GEN
Solar/Wind Harmer
2.652
203835AF1-098 GEN
Solar/Wind Harmer
2.694
203813AE2-344_GEN
Solar/Wind Harmer
12.663
20084926LAKVU GN
Adder
0.184
238215AE2-248 C
Solar/Wind Harmer
1.646
970643AG2-418 GEN
Solar/Wind Harmer
0.558
24035802GEN-Y1-012
Adder
0.206
20083726HOMER C1
50/50
228.436
20215826CON.GEN1
50/50
0.038
20063626IUP CO-G
50/50
0.219
20083926HOMER C3
50/50
199.576
20083826HOMER C2
50/50
188.522
20050326C.SLOPE
50/50
0.687
20092526R32
Solar/Wind Harmer
3.855
203844AF2-092 C
Solar/Wind Harmer
2.582
203850AG1-041 C
Solar/Wind Harmer
2.574
203961AE2-224 GEN
Solar/Wind Harmer
6.392
20091526CHSTN_FL
Solar/Wind Harmer
1.697
940863AE2-074 GEN
Solar/Wind Harmer
2.979
20083226HNSMLK 5
Adder
9.882
20090526Q36
Solar/Wind Harmer
2.547
203993AD2-133_GEN1
Solar/Wind Harmer
2.547
203804AE2-113_GEN
Solar/Wind Harmer
7.523
965121AG1-377 GEN
Solar/Wind Harmer
2.997
941231AE2-117 GEN
Solar/Wind Harmer
0.888
970555AG2-356 GEN
Solar/Wind Harmer
2.703
203855AF2-088 C
Solar/Wind Harmer
0.262
203846AF2-130 C
Solar/Wind Harmer
0.618
970677AG2-438 GEN
Solar/Wind Harmer
1.078
966771AG1-548 GEN
Solar/Wind Harmer
15.723
966771AG1-548 GEN
Solar/Wind Harmer
3.047
20084926LAKVU GN
Adder
0.207
203926AA2-133 GEN
Adder
2.246
20334726NME_Y1-047
Adder
2.031
971321AH1-140 GEN
Solar/Wind Harmer
10.681
971321AH1-140 GEN
Solar/Wind Harmer
2.07
20390726Y2-042
Adder
1.652
970663AG2-429 GEN
Solar/Wind Harmer
4.712
970663AG2-429 GEN
Solar/Wind Harmer
0.767
961581Q1080_CY23
External Queue
23.519622802734375
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.149
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.463
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.433
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.152
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.671
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.264
G-007ALTFEXP_G-007A->PJM
CMTX
0.023
CBM NorthLTFEXP_CBM-N->PJM
CBM
30.83
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_MP-138-100_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_MP-138-100_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.43 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1062.61
MW Contribution:15.45
Bus #Bus NameTypeMW Contribution
20079426CONEMAGH
50/50
2.866
20083326SEWRDB34
50/50
7.468
20216026CON.GEN2
50/50
0.027
203841AF2-001_GEN
Solar/Wind Harmer
4.929
971879AH1-460 GEN
Solar/Wind Harmer
16.011
20089126CSLMN_L13
Solar/Wind Harmer
2.122
20080926SITHE
50/50
0.719
20084126DEEPCRK2
50/50
0.151
20084026DEEPCRK1
50/50
0.149
946071AF1-272 GEN
Solar/Wind Harmer
9.629
203839AF1-321 GEN
Solar/Wind Harmer
4.929
20084626FORWARD
Solar/Wind Harmer
1.938
20083426SW_E13_K22
Solar/Wind Harmer
0.722
944781AF1-143 GEN
Solar/Wind Harmer
7.273
203857AF2-221 C
Solar/Wind Harmer
3.595
970123AG2-090 GEN
Solar/Wind Harmer
3.356
203955AF1-039 C O1
Solar/Wind Harmer
1.083
971427AH1-205 GEN
Solar/Wind Harmer
3.518
20088926STNY CRK
Solar/Wind Harmer
2.909
20081326YOUGH
50/50
0.092
203843AF2-002_GEN
Solar/Wind Harmer
2.465
970631AG2-411 GEN
Solar/Wind Harmer
15.449
20089226LOOKOUT
Solar/Wind Harmer
2.066
971423AH1-203 GEN
Solar/Wind Harmer
16.774
20088826HIGHLAND
Solar/Wind Harmer
3.74
971279AH1-102 GEN
Solar/Wind Harmer
18.04
957561AF2-050 GEN
Solar/Wind Harmer
10.536
20094526CT_V3-030
Solar/Wind Harmer
1.499
964201AG1-281 GEN
Solar/Wind Harmer
1.255
970713AG2-456 GEN
Solar/Wind Harmer
13.107
971705AH1-358 GEN
Solar/Wind Harmer
3.81
971709AH1-360 GEN
Solar/Wind Harmer
3.81
203987AE2-118 C
Solar/Wind Harmer
3.189
964391AG1-301 GEN
Solar/Wind Harmer
0.888
20082826HNSMLK 1
Adder
8.288
20083026HNSMLK 3
Adder
8.288
20091326SHAW-D
Adder
0.9
972169AH1-667 GEN
Solar/Wind Harmer
2.463
203954AE2-126 C
Solar/Wind Harmer
0.826
20326126BLOSSBCT
Adder
3.108
20335026MILZ1-092
Adder
3.072
944411AF1-106 GEN
Solar/Wind Harmer
2.83
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.563
971183AH1-050 GEN
Solar/Wind Harmer
5.118
238183AE2-316 GEN
Solar/Wind Harmer
5.316
970647AG2-420 GEN
Solar/Wind Harmer
0.29
20072226SHAWVL 2
Adder
16.955
970511AG2-327 GEN
Solar/Wind Harmer
1.234
20089026BF_G21_K23
Solar/Wind Harmer
1.68
970125AG2-091 GEN
Solar/Wind Harmer
1.438
202652Y1-033 WT C
Solar/Wind Harmer
2.225
971419AH1-201 GEN
Solar/Wind Harmer
7.565
971541AH1-268 GEN
Solar/Wind Harmer
7.677
970899AG2-561 GEN
Solar/Wind Harmer
4.351
203818AF1-086 GEN
Solar/Wind Harmer
4.985
945751AF1-240 GEN
Solar/Wind Harmer
2.685
960051AF2-296 GEN
Solar/Wind Harmer
3.403
971703AH1-357 GEN
Solar/Wind Harmer
3.277
971707AH1-359 GEN
Solar/Wind Harmer
3.277
20334926Z1-069 C
Solar/Wind Harmer
3.316
965131AG1-378 GEN
Solar/Wind Harmer
3.08
20082926HNSMLK 2
Adder
8.288
20083126HNSMLK 4
Adder
8.288
203854AF2-039 C
Solar/Wind Harmer
0.56
944411AF1-106 GEN
Solar/Wind Harmer
0.304
203932AE1-123
Adder
2.638
971185AH1-051 GEN
Solar/Wind Harmer
3.071
971355AH1-158 GEN
Solar/Wind Harmer
3.571
20120126WRREN CT
Adder
7.914
203856AF2-165 C
Solar/Wind Harmer
1.49
970647AG2-420 GEN
Solar/Wind Harmer
2.494
970335AG2-220 GEN
Solar/Wind Harmer
3.845
971127AH1-005 GEN
Solar/Wind Harmer
2.481
959441AF2-235 GEN
Solar/Wind Harmer
0.358
238219AF1-167 C
Solar/Wind Harmer
1.568
238202AE2-262_GEN
Solar/Wind Harmer
2.913
971627AH1-313 GEN
Solar/Wind Harmer
11.421
20335126GROZ1-110
Adder
2.606
20335226CANZ2-011
Adder
2.533
957161AF2-010 GEN
Solar/Wind Harmer
8.186
203830AF1-094 GEN
Solar/Wind Harmer
0.64
203948AG1-140 C
Solar/Wind Harmer
0.267
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.003
962511AG1-100 GEN
Solar/Wind Harmer
0.604
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.897
972271AH1-720 GEN
Adder
6.165
200917MEHOOPANY_G
Solar/Wind Harmer
2.882
970679AG2-439 GEN
Solar/Wind Harmer
0.659
970643AG2-418 GEN
Solar/Wind Harmer
1.212
20083726HOMER C1
50/50
223.712
20215826CON.GEN1
50/50
0.039
20063626IUP CO-G
50/50
0.225
20083926HOMER C3
50/50
185.007
20083826HOMER C2
50/50
174.761
20050326C.SLOPE
50/50
0.703
203844AF2-092 C
Solar/Wind Harmer
2.767
20092526R32
Solar/Wind Harmer
4.007
203850AG1-041 C
Solar/Wind Harmer
2.745
203961AE2-224 GEN
Solar/Wind Harmer
6.382
20091526CHSTN_FL
Solar/Wind Harmer
1.749
20090526Q36
Solar/Wind Harmer
2.618
203993AD2-133_GEN1
Solar/Wind Harmer
2.618
940863AE2-074 GEN
Solar/Wind Harmer
2.824
965121AG1-377 GEN
Solar/Wind Harmer
3.08
203804AE2-113_GEN
Solar/Wind Harmer
7.308
941231AE2-117 GEN
Solar/Wind Harmer
0.902
20083226HNSMLK 5
Adder
8.288
203855AF2-088 C
Solar/Wind Harmer
0.269
203846AF2-130 C
Solar/Wind Harmer
0.74
970555AG2-356 GEN
Solar/Wind Harmer
2.563
970663AG2-429 GEN
Solar/Wind Harmer
8.44
970663AG2-429 GEN
Solar/Wind Harmer
1.374
970677AG2-438 GEN
Solar/Wind Harmer
1.057
966771AG1-548 GEN
Solar/Wind Harmer
15.316
966771AG1-548 GEN
Solar/Wind Harmer
2.968
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.144
20334726NME_Y1-047
Adder
1.937
971321AH1-140 GEN
Solar/Wind Harmer
11.795
971321AH1-140 GEN
Solar/Wind Harmer
2.286
20390726Y2-042
Adder
1.578
203940AF1-140 C
Solar/Wind Harmer
1.095
971441AH1-212 GEN
Solar/Wind Harmer
4.287
20088626ARWF_N39
Solar/Wind Harmer
3.758
20303426NA_O38_P22
Solar/Wind Harmer
3.042
203853AF1-134 C O1
Solar/Wind Harmer
1.029
972077AH1-588 GEN
Solar/Wind Harmer
39.32
972079AH1-589 GEN
Solar/Wind Harmer
32.386
970715AG2-457 GEN
Solar/Wind Harmer
13.107
972075AH1-587 GEN
Solar/Wind Harmer
31.212
203952AE2-129 C
Solar/Wind Harmer
0.933
203946AE2-131 C
Solar/Wind Harmer
0.931
962411AG1-090 GEN
Solar/Wind Harmer
14.63
20398826ARMNA MT
Solar/Wind Harmer
3.204
203848AF2-166 C
Solar/Wind Harmer
2.59
946381AF1-302 GEN
Solar/Wind Harmer
2.66
238217AF1-153 C O1
Solar/Wind Harmer
0.758
970305AG2-200 GEN
Solar/Wind Harmer
2.503
203859AF2-294 C
Solar/Wind Harmer
2.123
970313AG2-206 GEN
Solar/Wind Harmer
5.926
216419AE2-001 C
Solar/Wind Harmer
2.128
203980AG1-197 GEN
Solar/Wind Harmer
0.481
203979AG1-198 GEN
Solar/Wind Harmer
0.384
971933AH1-491 GEN
Solar/Wind Harmer
2.114
203963AG1-253 GEN
Solar/Wind Harmer
0.408
971931AH1-490 GEN
Solar/Wind Harmer
1.998
203947AF1-006 C
Solar/Wind Harmer
0.527
203860AG1-193 C
Solar/Wind Harmer
0.37
238206AE2-263_GEN
Solar/Wind Harmer
2.715
970267AG2-176 GEN
Solar/Wind Harmer
16.811
238215AE2-248 C
Solar/Wind Harmer
1.682
961971AG1-040 GEN
Solar/Wind Harmer
0.634
203835AF1-098 GEN
Solar/Wind Harmer
2.515
203813AE2-344_GEN
Solar/Wind Harmer
11.616
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.873
24035802GEN-Y1-012
Adder
0.187
961581Q1080_CY23
External Queue
21.336383819580078
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.238
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.164
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.693
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.287
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.865
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P2-2_WP-138-036_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-138-036_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1058.48
MW Contribution:14.49
Bus #Bus NameTypeMW Contribution
20080926SITHE
50/50
0.718
946071AF1-272 GEN
Solar/Wind Harmer
9.957
203839AF1-321 GEN
Solar/Wind Harmer
4.621
20084626FORWARD
Solar/Wind Harmer
1.818
203857AF2-221 C
Solar/Wind Harmer
3.433
970123AG2-090 GEN
Solar/Wind Harmer
3.204
203940AF1-140 C
Solar/Wind Harmer
1.054
971441AH1-212 GEN
Solar/Wind Harmer
4.228
20088926STNY CRK
Solar/Wind Harmer
2.571
971427AH1-205 GEN
Solar/Wind Harmer
3.105
20083426SW_E13_K22
Solar/Wind Harmer
0.61
20088626ARWF_N39
Solar/Wind Harmer
3.74
20303426NA_O38_P22
Solar/Wind Harmer
3.028
203853AF1-134 C O1
Solar/Wind Harmer
1.038
944781AF1-143 GEN
Solar/Wind Harmer
5.181
972077AH1-588 GEN
Solar/Wind Harmer
39.352
972079AH1-589 GEN
Solar/Wind Harmer
32.412
970715AG2-457 GEN
Solar/Wind Harmer
13.117
972075AH1-587 GEN
Solar/Wind Harmer
31.245
203952AE2-129 C
Solar/Wind Harmer
0.926
203946AE2-131 C
Solar/Wind Harmer
0.925
962411AG1-090 GEN
Solar/Wind Harmer
14.53
20398826ARMNA MT
Solar/Wind Harmer
3.206
203848AF2-166 C
Solar/Wind Harmer
2.619
203955AF1-039 C O1
Solar/Wind Harmer
0.591
946381AF1-302 GEN
Solar/Wind Harmer
2.68
238217AF1-153 C O1
Solar/Wind Harmer
0.76
970305AG2-200 GEN
Solar/Wind Harmer
2.507
203859AF2-294 C
Solar/Wind Harmer
2.124
970313AG2-206 GEN
Solar/Wind Harmer
5.93
216419AE2-001 C
Solar/Wind Harmer
2.129
203980AG1-197 GEN
Solar/Wind Harmer
0.483
203979AG1-198 GEN
Solar/Wind Harmer
0.386
971933AH1-491 GEN
Solar/Wind Harmer
2.123
203963AG1-253 GEN
Solar/Wind Harmer
0.409
971931AH1-490 GEN
Solar/Wind Harmer
2.003
203947AF1-006 C
Solar/Wind Harmer
0.528
20216026CON.GEN2
50/50
0.031
20079426CONEMAGH
50/50
2.883
20083326SEWRDB34
50/50
7.462
203841AF2-001_GEN
Solar/Wind Harmer
4.621
971879AH1-460 GEN
Solar/Wind Harmer
15.165
970125AG2-091 GEN
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
7.762
970899AG2-561 GEN
Solar/Wind Harmer
4.428
971419AH1-201 GEN
Solar/Wind Harmer
6.675
203818AF1-086 GEN
Solar/Wind Harmer
5.049
945751AF1-240 GEN
Solar/Wind Harmer
2.727
960051AF2-296 GEN
Solar/Wind Harmer
3.433
20089126CSLMN_L13
Solar/Wind Harmer
1.512
20089026BF_G21_K23
Solar/Wind Harmer
1.197
971703AH1-357 GEN
Solar/Wind Harmer
3.279
971707AH1-359 GEN
Solar/Wind Harmer
3.279
20334926Z1-069 C
Solar/Wind Harmer
3.318
965131AG1-378 GEN
Solar/Wind Harmer
3.059
20082926HNSMLK 2
Adder
8.318
20083126HNSMLK 4
Adder
8.318
203854AF2-039 C
Solar/Wind Harmer
0.56
203932AE1-123
Adder
2.672
944411AF1-106 GEN
Solar/Wind Harmer
0.304
202652Y1-033 WT C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
3.099
971355AH1-158 GEN
Solar/Wind Harmer
3.603
203856AF2-165 C
Solar/Wind Harmer
1.503
970647AG2-420 GEN
Solar/Wind Harmer
2.516
20120126WRREN CT
Adder
7.925
970335AG2-220 GEN
Solar/Wind Harmer
3.848
971127AH1-005 GEN
Solar/Wind Harmer
2.482
959441AF2-235 GEN
Solar/Wind Harmer
0.361
238219AF1-167 C
Solar/Wind Harmer
1.591
238202AE2-262_GEN
Solar/Wind Harmer
2.916
971627AH1-313 GEN
Solar/Wind Harmer
11.433
20335126GROZ1-110
Adder
2.609
20335226CANZ2-011
Adder
2.536
957161AF2-010 GEN
Solar/Wind Harmer
8.223
203830AF1-094 GEN
Solar/Wind Harmer
0.643
203948AG1-140 C
Solar/Wind Harmer
0.268
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.008
962511AG1-100 GEN
Solar/Wind Harmer
0.606
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.9
972271AH1-720 GEN
Adder
6.172
200917MEHOOPANY_G
Solar/Wind Harmer
2.886
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.213
20080526COLVER13
50/50
1.55
203843AF2-002_GEN
Solar/Wind Harmer
2.31
970631AG2-411 GEN
Solar/Wind Harmer
14.488
971279AH1-102 GEN
Solar/Wind Harmer
18.239
20088826HIGHLAND
Solar/Wind Harmer
3.619
20094526CT_V3-030
Solar/Wind Harmer
1.499
957561AF2-050 GEN
Solar/Wind Harmer
10.491
971423AH1-203 GEN
Solar/Wind Harmer
14.595
964201AG1-281 GEN
Solar/Wind Harmer
1.218
20089226LOOKOUT
Solar/Wind Harmer
1.472
970713AG2-456 GEN
Solar/Wind Harmer
13.117
971705AH1-358 GEN
Solar/Wind Harmer
3.813
971709AH1-360 GEN
Solar/Wind Harmer
3.813
20215826CON.GEN1
50/50
0.04
20083726HOMER C1
50/50
223.377
20063626IUP CO-G
50/50
0.232
20083926HOMER C3
50/50
185.01
20083826HOMER C2
50/50
174.763
20092526R32
Solar/Wind Harmer
3.878
203844AF2-092 C
Solar/Wind Harmer
2.596
203850AG1-041 C
Solar/Wind Harmer
2.589
203961AE2-224 GEN
Solar/Wind Harmer
6.355
20091526CHSTN_FL
Solar/Wind Harmer
1.714
971321AH1-140 GEN
Solar/Wind Harmer
26.397
971321AH1-140 GEN
Solar/Wind Harmer
5.116
20090526Q36
Solar/Wind Harmer
2.587
203993AD2-133_GEN1
Solar/Wind Harmer
2.587
940863AE2-074 GEN
Solar/Wind Harmer
2.826
965121AG1-377 GEN
Solar/Wind Harmer
3.059
203804AE2-113_GEN
Solar/Wind Harmer
7.317
941231AE2-117 GEN
Solar/Wind Harmer
0.893
20083226HNSMLK 5
Adder
8.318
203855AF2-088 C
Solar/Wind Harmer
0.27
203846AF2-130 C
Solar/Wind Harmer
0.748
970555AG2-356 GEN
Solar/Wind Harmer
2.565
970663AG2-429 GEN
Solar/Wind Harmer
8.551
970663AG2-429 GEN
Solar/Wind Harmer
1.392
970677AG2-438 GEN
Solar/Wind Harmer
1.062
966771AG1-548 GEN
Solar/Wind Harmer
15.378
966771AG1-548 GEN
Solar/Wind Harmer
2.98
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.146
20334726NME_Y1-047
Adder
1.939
20390726Y2-042
Adder
1.58
971055AG2-654 GEN
Solar/Wind Harmer
0.556
203987AE2-118 C
Solar/Wind Harmer
3.155
964391AG1-301 GEN
Solar/Wind Harmer
0.879
20082826HNSMLK 1
Adder
8.318
20083026HNSMLK 3
Adder
8.318
20091326SHAW-D
Adder
0.901
972169AH1-667 GEN
Solar/Wind Harmer
2.466
203954AE2-126 C
Solar/Wind Harmer
0.827
20326126BLOSSBCT
Adder
3.11
20335026MILZ1-092
Adder
3.074
944411AF1-106 GEN
Solar/Wind Harmer
2.832
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.565
971183AH1-050 GEN
Solar/Wind Harmer
5.165
238183AE2-316 GEN
Solar/Wind Harmer
5.355
970647AG2-420 GEN
Solar/Wind Harmer
0.293
20072226SHAWVL 2
Adder
16.977
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203860AG1-193 C
Solar/Wind Harmer
0.372
238206AE2-263_GEN
Solar/Wind Harmer
2.718
970267AG2-176 GEN
Solar/Wind Harmer
16.875
961971AG1-040 GEN
Solar/Wind Harmer
0.636
238215AE2-248 C
Solar/Wind Harmer
1.682
203835AF1-098 GEN
Solar/Wind Harmer
2.519
203813AE2-344_GEN
Solar/Wind Harmer
11.645
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.935
24035802GEN-Y1-012
Adder
0.187
961581Q1080_CY23
External Queue
21.315889358520508
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.27
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.923
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-053A_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-053A_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:107.82 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1056.6
MW Contribution:14.26
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
223.475
20215826CON.GEN1
50/50
0.039
20063626IUP CO-G
50/50
0.224
20083926HOMER C3
50/50
189.284
20083826HOMER C2
50/50
178.8
20092526R32
Solar/Wind Harmer
3.812
203844AF2-092 C
Solar/Wind Harmer
2.555
203850AG1-041 C
Solar/Wind Harmer
2.548
203961AE2-224 GEN
Solar/Wind Harmer
6.304
20091526CHSTN_FL
Solar/Wind Harmer
1.696
940863AE2-074 GEN
Solar/Wind Harmer
2.921
20090526Q36
Solar/Wind Harmer
2.597
203993AD2-133_GEN1
Solar/Wind Harmer
2.597
203804AE2-113_GEN
Solar/Wind Harmer
7.605
965121AG1-377 GEN
Solar/Wind Harmer
3.102
20083326SEWRDB34
50/50
7.372
20079426CONEMAGH
50/50
2.786
20216026CON.GEN2
50/50
0.027
203841AF2-001_GEN
Solar/Wind Harmer
4.544
971879AH1-460 GEN
Solar/Wind Harmer
14.908
970125AG2-091 GEN
Solar/Wind Harmer
1.349
970899AG2-561 GEN
Solar/Wind Harmer
4.363
971541AH1-268 GEN
Solar/Wind Harmer
7.566
971419AH1-201 GEN
Solar/Wind Harmer
6.568
203818AF1-086 GEN
Solar/Wind Harmer
5.016
945751AF1-240 GEN
Solar/Wind Harmer
2.826
960051AF2-296 GEN
Solar/Wind Harmer
3.452
971703AH1-357 GEN
Solar/Wind Harmer
3.396
971707AH1-359 GEN
Solar/Wind Harmer
3.396
20089126CSLMN_L13
Solar/Wind Harmer
1.489
20089026BF_G21_K23
Solar/Wind Harmer
1.178
20334926Z1-069 C
Solar/Wind Harmer
3.425
965131AG1-378 GEN
Solar/Wind Harmer
3.102
20080526COLVER13
50/50
1.527
203843AF2-002_GEN
Solar/Wind Harmer
2.272
970631AG2-411 GEN
Solar/Wind Harmer
14.256
20088826HIGHLAND
Solar/Wind Harmer
3.558
971279AH1-102 GEN
Solar/Wind Harmer
17.777
957561AF2-050 GEN
Solar/Wind Harmer
10.408
20094526CT_V3-030
Solar/Wind Harmer
1.478
971423AH1-203 GEN
Solar/Wind Harmer
14.36
964201AG1-281 GEN
Solar/Wind Harmer
1.202
970713AG2-456 GEN
Solar/Wind Harmer
13.583
971705AH1-358 GEN
Solar/Wind Harmer
3.949
971709AH1-360 GEN
Solar/Wind Harmer
3.949
20089226LOOKOUT
Solar/Wind Harmer
1.449
203987AE2-118 C
Solar/Wind Harmer
3.141
20082926HNSMLK 2
Adder
8.956
20083126HNSMLK 4
Adder
8.956
203932AE1-123
Adder
2.943
203854AF2-039 C
Solar/Wind Harmer
0.576
971185AH1-051 GEN
Solar/Wind Harmer
3.381
971355AH1-158 GEN
Solar/Wind Harmer
3.931
944411AF1-106 GEN
Solar/Wind Harmer
0.314
238219AF1-167 C
Solar/Wind Harmer
1.869
203856AF2-165 C
Solar/Wind Harmer
1.638
970647AG2-420 GEN
Solar/Wind Harmer
2.739
20120126WRREN CT
Adder
8.311
959441AF2-235 GEN
Solar/Wind Harmer
0.392
202652Y1-033 WT C
Solar/Wind Harmer
1.199
970335AG2-220 GEN
Solar/Wind Harmer
3.968
971127AH1-005 GEN
Solar/Wind Harmer
2.56
238202AE2-262_GEN
Solar/Wind Harmer
3.032
971627AH1-313 GEN
Solar/Wind Harmer
11.888
20335126GROZ1-110
Adder
2.697
20335226CANZ2-011
Adder
2.622
957161AF2-010 GEN
Solar/Wind Harmer
8.813
203830AF1-094 GEN
Solar/Wind Harmer
0.689
203948AG1-140 C
Solar/Wind Harmer
0.283
203962AF1-287 GEN
Solar/Wind Harmer
2.142
962511AG1-100 GEN
Solar/Wind Harmer
0.646
20328326MANOR_T86
Adder
0.148
20084926LAKVU GN
Adder
0.18
941421AE2-139 GEN
Solar/Wind Harmer
2.999
972271AH1-720 GEN
Adder
6.38
200917MEHOOPANY_G
Solar/Wind Harmer
2.981
970679AG2-439 GEN
Solar/Wind Harmer
0.682
970643AG2-418 GEN
Solar/Wind Harmer
1.229
20080926SITHE
50/50
0.719
946071AF1-272 GEN
Solar/Wind Harmer
9.57
203839AF1-321 GEN
Solar/Wind Harmer
4.544
20084626FORWARD
Solar/Wind Harmer
1.789
203857AF2-221 C
Solar/Wind Harmer
3.373
970123AG2-090 GEN
Solar/Wind Harmer
3.149
203940AF1-140 C
Solar/Wind Harmer
1.038
971441AH1-212 GEN
Solar/Wind Harmer
4.156
20088926STNY CRK
Solar/Wind Harmer
2.53
971427AH1-205 GEN
Solar/Wind Harmer
3.055
20083426SW_E13_K22
Solar/Wind Harmer
0.6
20088626ARWF_N39
Solar/Wind Harmer
3.713
20303426NA_O38_P22
Solar/Wind Harmer
3.005
203853AF1-134 C O1
Solar/Wind Harmer
1.044
972077AH1-588 GEN
Solar/Wind Harmer
40.749
972079AH1-589 GEN
Solar/Wind Harmer
33.563
970715AG2-457 GEN
Solar/Wind Harmer
13.583
944781AF1-143 GEN
Solar/Wind Harmer
5.102
972075AH1-587 GEN
Solar/Wind Harmer
32.43
203952AE2-129 C
Solar/Wind Harmer
0.939
203946AE2-131 C
Solar/Wind Harmer
0.938
962411AG1-090 GEN
Solar/Wind Harmer
14.732
946381AF1-302 GEN
Solar/Wind Harmer
3.026
203848AF2-166 C
Solar/Wind Harmer
2.871
20398826ARMNA MT
Solar/Wind Harmer
3.303
238217AF1-153 C O1
Solar/Wind Harmer
0.814
970305AG2-200 GEN
Solar/Wind Harmer
2.629
203859AF2-294 C
Solar/Wind Harmer
2.19
203955AF1-039 C O1
Solar/Wind Harmer
0.584
970313AG2-206 GEN
Solar/Wind Harmer
6.115
203980AG1-197 GEN
Solar/Wind Harmer
0.517
203979AG1-198 GEN
Solar/Wind Harmer
0.413
971933AH1-491 GEN
Solar/Wind Harmer
2.274
216419AE2-001 C
Solar/Wind Harmer
2.202
203963AG1-253 GEN
Solar/Wind Harmer
0.432
971931AH1-490 GEN
Solar/Wind Harmer
2.138
203947AF1-006 C
Solar/Wind Harmer
0.561
20083226HNSMLK 5
Adder
8.956
941231AE2-117 GEN
Solar/Wind Harmer
0.892
970663AG2-429 GEN
Solar/Wind Harmer
10.063
970663AG2-429 GEN
Solar/Wind Harmer
1.638
203846AF2-130 C
Solar/Wind Harmer
0.82
203855AF2-088 C
Solar/Wind Harmer
0.277
970555AG2-356 GEN
Solar/Wind Harmer
2.645
970677AG2-438 GEN
Solar/Wind Harmer
1.137
966771AG1-548 GEN
Solar/Wind Harmer
16.455
966771AG1-548 GEN
Solar/Wind Harmer
3.189
20084926LAKVU GN
Adder
0.203
203926AA2-133 GEN
Adder
2.216
20334726NME_Y1-047
Adder
2.003
971321AH1-140 GEN
Solar/Wind Harmer
10.527
971321AH1-140 GEN
Solar/Wind Harmer
2.04
20390726Y2-042
Adder
1.633
971055AG2-654 GEN
Solar/Wind Harmer
0.739
20082826HNSMLK 1
Adder
8.956
20083026HNSMLK 3
Adder
8.956
964391AG1-301 GEN
Solar/Wind Harmer
0.878
238183AE2-316 GEN
Solar/Wind Harmer
6.048
203954AE2-126 C
Solar/Wind Harmer
0.858
20091326SHAW-D
Adder
0.927
972169AH1-667 GEN
Solar/Wind Harmer
2.536
20326126BLOSSBCT
Adder
3.208
971183AH1-050 GEN
Solar/Wind Harmer
5.635
20335026MILZ1-092
Adder
3.169
944411AF1-106 GEN
Solar/Wind Harmer
2.919
970647AG2-420 GEN
Solar/Wind Harmer
0.318
203860AG1-193 C
Solar/Wind Harmer
0.403
959471AF2-238 GEN
Solar/Wind Harmer
0.8
970337AG2-221 GEN
Solar/Wind Harmer
2.645
20072226SHAWVL 2
Adder
17.649
970511AG2-327 GEN
Solar/Wind Harmer
1.274
970267AG2-176 GEN
Solar/Wind Harmer
18.122
238206AE2-263_GEN
Solar/Wind Harmer
2.826
961971AG1-040 GEN
Solar/Wind Harmer
0.68
203835AF1-098 GEN
Solar/Wind Harmer
2.664
238215AE2-248 C
Solar/Wind Harmer
1.738
203813AE2-344_GEN
Solar/Wind Harmer
12.418
20084926LAKVU GN
Adder
0.18
970643AG2-418 GEN
Solar/Wind Harmer
0.572
971865AH1-452 GEN
Solar/Wind Harmer
1.032
24035802GEN-Y1-012
Adder
0.198
961581Q1080_CY23
External Queue
21.48957061767578
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.476
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.415
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.154
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.691
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.266
G-007ALTFEXP_G-007A->PJM
CMTX
0.017
CBM NorthLTFEXP_CBM-N->PJM
CBM
29.854
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o AP_P7-1_WPP-138-083_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
AP_P7-1_WPP-138-083_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.56 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1034.46
MW Contribution:14.49
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.031
20079426CONEMAGH
50/50
2.883
20083326SEWRDB34
50/50
7.462
203841AF2-001_GEN
Solar/Wind Harmer
4.621
971879AH1-460 GEN
Solar/Wind Harmer
15.165
20215826CON.GEN1
50/50
0.04
20083726HOMER C1
50/50
223.377
20063626IUP CO-G
50/50
0.232
20083926HOMER C3
50/50
185.01
20083826HOMER C2
50/50
174.763
20080526COLVER13
50/50
1.55
203843AF2-002_GEN
Solar/Wind Harmer
2.31
970631AG2-411 GEN
Solar/Wind Harmer
14.488
20080926SITHE
50/50
0.718
946071AF1-272 GEN
Solar/Wind Harmer
9.957
203839AF1-321 GEN
Solar/Wind Harmer
4.621
20084626FORWARD
Solar/Wind Harmer
1.818
20092526R32
Solar/Wind Harmer
3.878
970125AG2-091 GEN
Solar/Wind Harmer
1.373
971541AH1-268 GEN
Solar/Wind Harmer
7.762
970899AG2-561 GEN
Solar/Wind Harmer
4.428
971419AH1-201 GEN
Solar/Wind Harmer
6.675
203818AF1-086 GEN
Solar/Wind Harmer
5.049
945751AF1-240 GEN
Solar/Wind Harmer
2.727
960051AF2-296 GEN
Solar/Wind Harmer
3.433
20089126CSLMN_L13
Solar/Wind Harmer
1.512
20089026BF_G21_K23
Solar/Wind Harmer
1.197
971703AH1-357 GEN
Solar/Wind Harmer
3.279
971707AH1-359 GEN
Solar/Wind Harmer
3.279
20334926Z1-069 C
Solar/Wind Harmer
3.318
965131AG1-378 GEN
Solar/Wind Harmer
3.059
20082926HNSMLK 2
Adder
8.318
20083126HNSMLK 4
Adder
8.318
203854AF2-039 C
Solar/Wind Harmer
0.56
203932AE1-123
Adder
2.672
944411AF1-106 GEN
Solar/Wind Harmer
0.304
202652Y1-033 WT C
Solar/Wind Harmer
1.215
971185AH1-051 GEN
Solar/Wind Harmer
3.099
971355AH1-158 GEN
Solar/Wind Harmer
3.603
203856AF2-165 C
Solar/Wind Harmer
1.503
970647AG2-420 GEN
Solar/Wind Harmer
2.516
20120126WRREN CT
Adder
7.926
970335AG2-220 GEN
Solar/Wind Harmer
3.848
971127AH1-005 GEN
Solar/Wind Harmer
2.482
959441AF2-235 GEN
Solar/Wind Harmer
0.361
238219AF1-167 C
Solar/Wind Harmer
1.591
238202AE2-262_GEN
Solar/Wind Harmer
2.916
971627AH1-313 GEN
Solar/Wind Harmer
11.433
20335126GROZ1-110
Adder
2.609
20335226CANZ2-011
Adder
2.536
957161AF2-010 GEN
Solar/Wind Harmer
8.223
203830AF1-094 GEN
Solar/Wind Harmer
0.643
203948AG1-140 C
Solar/Wind Harmer
0.268
20328326MANOR_T86
Adder
0.143
203962AF1-287 GEN
Solar/Wind Harmer
2.008
962511AG1-100 GEN
Solar/Wind Harmer
0.606
20084926LAKVU GN
Adder
0.17
941421AE2-139 GEN
Solar/Wind Harmer
2.9
972271AH1-720 GEN
Adder
6.172
200917MEHOOPANY_G
Solar/Wind Harmer
2.886
970679AG2-439 GEN
Solar/Wind Harmer
0.66
970643AG2-418 GEN
Solar/Wind Harmer
1.213
203857AF2-221 C
Solar/Wind Harmer
3.433
970123AG2-090 GEN
Solar/Wind Harmer
3.204
203940AF1-140 C
Solar/Wind Harmer
1.054
971441AH1-212 GEN
Solar/Wind Harmer
4.228
20088926STNY CRK
Solar/Wind Harmer
2.571
971427AH1-205 GEN
Solar/Wind Harmer
3.105
20083426SW_E13_K22
Solar/Wind Harmer
0.61
20088626ARWF_N39
Solar/Wind Harmer
3.74
20303426NA_O38_P22
Solar/Wind Harmer
3.028
203853AF1-134 C O1
Solar/Wind Harmer
1.038
944781AF1-143 GEN
Solar/Wind Harmer
5.181
972077AH1-588 GEN
Solar/Wind Harmer
39.352
972079AH1-589 GEN
Solar/Wind Harmer
32.412
970715AG2-457 GEN
Solar/Wind Harmer
13.117
972075AH1-587 GEN
Solar/Wind Harmer
31.245
203952AE2-129 C
Solar/Wind Harmer
0.926
203946AE2-131 C
Solar/Wind Harmer
0.925
962411AG1-090 GEN
Solar/Wind Harmer
14.53
20398826ARMNA MT
Solar/Wind Harmer
3.206
203848AF2-166 C
Solar/Wind Harmer
2.619
203955AF1-039 C O1
Solar/Wind Harmer
0.591
946381AF1-302 GEN
Solar/Wind Harmer
2.68
238217AF1-153 C O1
Solar/Wind Harmer
0.76
970305AG2-200 GEN
Solar/Wind Harmer
2.507
203859AF2-294 C
Solar/Wind Harmer
2.124
970313AG2-206 GEN
Solar/Wind Harmer
5.93
216419AE2-001 C
Solar/Wind Harmer
2.129
203980AG1-197 GEN
Solar/Wind Harmer
0.483
203979AG1-198 GEN
Solar/Wind Harmer
0.386
971933AH1-491 GEN
Solar/Wind Harmer
2.123
203963AG1-253 GEN
Solar/Wind Harmer
0.409
971931AH1-490 GEN
Solar/Wind Harmer
2.003
203947AF1-006 C
Solar/Wind Harmer
0.528
971279AH1-102 GEN
Solar/Wind Harmer
18.239
20088826HIGHLAND
Solar/Wind Harmer
3.619
20094526CT_V3-030
Solar/Wind Harmer
1.499
957561AF2-050 GEN
Solar/Wind Harmer
10.491
971423AH1-203 GEN
Solar/Wind Harmer
14.595
964201AG1-281 GEN
Solar/Wind Harmer
1.218
20089226LOOKOUT
Solar/Wind Harmer
1.472
970713AG2-456 GEN
Solar/Wind Harmer
13.117
971705AH1-358 GEN
Solar/Wind Harmer
3.813
971709AH1-360 GEN
Solar/Wind Harmer
3.813
203987AE2-118 C
Solar/Wind Harmer
3.155
964391AG1-301 GEN
Solar/Wind Harmer
0.879
20082826HNSMLK 1
Adder
8.318
20083026HNSMLK 3
Adder
8.318
20091326SHAW-D
Adder
0.901
972169AH1-667 GEN
Solar/Wind Harmer
2.466
203954AE2-126 C
Solar/Wind Harmer
0.827
20326126BLOSSBCT
Adder
3.11
20335026MILZ1-092
Adder
3.074
944411AF1-106 GEN
Solar/Wind Harmer
2.832
959471AF2-238 GEN
Solar/Wind Harmer
0.775
970337AG2-221 GEN
Solar/Wind Harmer
2.565
971183AH1-050 GEN
Solar/Wind Harmer
5.165
238183AE2-316 GEN
Solar/Wind Harmer
5.356
970647AG2-420 GEN
Solar/Wind Harmer
0.293
20072226SHAWVL 2
Adder
16.977
970511AG2-327 GEN
Solar/Wind Harmer
1.235
203860AG1-193 C
Solar/Wind Harmer
0.372
238206AE2-263_GEN
Solar/Wind Harmer
2.718
970267AG2-176 GEN
Solar/Wind Harmer
16.875
961971AG1-040 GEN
Solar/Wind Harmer
0.636
238215AE2-248 C
Solar/Wind Harmer
1.682
203835AF1-098 GEN
Solar/Wind Harmer
2.519
203813AE2-344_GEN
Solar/Wind Harmer
11.645
20084926LAKVU GN
Adder
0.17
970643AG2-418 GEN
Solar/Wind Harmer
0.564
971865AH1-452 GEN
Solar/Wind Harmer
0.935
24035802GEN-Y1-012
Adder
0.187
203844AF2-092 C
Solar/Wind Harmer
2.596
203850AG1-041 C
Solar/Wind Harmer
2.589
203961AE2-224 GEN
Solar/Wind Harmer
6.355
20091526CHSTN_FL
Solar/Wind Harmer
1.714
20090526Q36
Solar/Wind Harmer
2.587
203993AD2-133_GEN1
Solar/Wind Harmer
2.587
940863AE2-074 GEN
Solar/Wind Harmer
2.826
965121AG1-377 GEN
Solar/Wind Harmer
3.059
203804AE2-113_GEN
Solar/Wind Harmer
7.317
941231AE2-117 GEN
Solar/Wind Harmer
0.893
20083226HNSMLK 5
Adder
8.318
203855AF2-088 C
Solar/Wind Harmer
0.27
203846AF2-130 C
Solar/Wind Harmer
0.748
970555AG2-356 GEN
Solar/Wind Harmer
2.565
970663AG2-429 GEN
Solar/Wind Harmer
8.551
970663AG2-429 GEN
Solar/Wind Harmer
1.392
970677AG2-438 GEN
Solar/Wind Harmer
1.062
966771AG1-548 GEN
Solar/Wind Harmer
15.378
966771AG1-548 GEN
Solar/Wind Harmer
2.98
20084926LAKVU GN
Adder
0.191
203926AA2-133 GEN
Adder
2.146
20334726NME_Y1-047
Adder
1.939
20390726Y2-042
Adder
1.58
971055AG2-654 GEN
Solar/Wind Harmer
0.556
961581Q1080_CY23
External Queue
21.315900802612305
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.151
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.471
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
0.326
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.155
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.687
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.27
CBM NorthLTFEXP_CBM-N->PJM
CBM
28.923
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-2_PN-230-025_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-025_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.65
MW Contribution:14.5
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
0.638
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
203850AG1-041 C
Solar/Wind Harmer
2.443
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.001
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.567
20083326SEWRDB34
50/50
11.336
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
971419AH1-201 GEN
Solar/Wind Harmer
7.878
970899AG2-561 GEN
Solar/Wind Harmer
3.875
203818AF1-086 GEN
Solar/Wind Harmer
1.499
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20089026BF_G21_K23
Solar/Wind Harmer
0.108
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20334926Z1-069 C
Solar/Wind Harmer
1.023
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971355AH1-158 GEN
Solar/Wind Harmer
5.546
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
971127AH1-005 GEN
Solar/Wind Harmer
2.467
238219AF1-167 C
Solar/Wind Harmer
1.377
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
10.129
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
203962AF1-287 GEN
Solar/Wind Harmer
1.756
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
970679AG2-439 GEN
Solar/Wind Harmer
0.491
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
203843AF2-002_GEN
Solar/Wind Harmer
2.147
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20088826HIGHLAND
Solar/Wind Harmer
0.002
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20094526CT_V3-030
Solar/Wind Harmer
0.328
20089226LOOKOUT
Solar/Wind Harmer
0.305
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
2.196
203954AE2-126 C
Solar/Wind Harmer
0.002
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.837
971183AH1-050 GEN
Solar/Wind Harmer
5.546
238183AE2-316 GEN
Solar/Wind Harmer
0.006
20072226SHAWVL 2
Adder
21.555
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.001
970511AG2-327 GEN
Solar/Wind Harmer
1.052
238206AE2-263_GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
238215AE2-248 C
Solar/Wind Harmer
1.499
203835AF1-098 GEN
Solar/Wind Harmer
0.006
203813AE2-344_GEN
Solar/Wind Harmer
10.181
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
24035802GEN-Y1-012
Adder
0.244
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203857AF2-221 C
Solar/Wind Harmer
2.266
970123AG2-090 GEN
Solar/Wind Harmer
3.021
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
4.03
20088926STNY CRK
Solar/Wind Harmer
0.38
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.982
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
203859AF2-294 C
Solar/Wind Harmer
1.807
970313AG2-206 GEN
Solar/Wind Harmer
5.051
216419AE2-001 C
Solar/Wind Harmer
1.896
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.402
971931AH1-490 GEN
Solar/Wind Harmer
1.751
203947AF1-006 C
Solar/Wind Harmer
0.056
961581Q1080_CY23
External Queue
26.08061408996582
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line l/o PN_P1-3_PN-500-003_SRT-A


Base Case Flowgate

Area:PENELEC
Facility Description:
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line
Contingency Name:
PN_P1-3_PN-500-003_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.25 %
Rating:980.0 MVA
Rating Type:B
MVA to Mitigate:1021.63
MW Contribution:14.5
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
11.336
20080926SITHE
50/50
0.88
946071AF1-272 GEN
Solar/Wind Harmer
0.001
203857AF2-221 C
Solar/Wind Harmer
2.266
970123AG2-090 GEN
Solar/Wind Harmer
3.021
203839AF1-321 GEN
Solar/Wind Harmer
4.294
20084626FORWARD
Solar/Wind Harmer
0.001
203940AF1-140 C
Solar/Wind Harmer
0.002
971441AH1-212 GEN
Solar/Wind Harmer
4.03
20088926STNY CRK
Solar/Wind Harmer
0.38
971427AH1-205 GEN
Solar/Wind Harmer
5.252
20088626ARWF_N39
Solar/Wind Harmer
0.003
20303426NA_O38_P22
Solar/Wind Harmer
0.002
944781AF1-143 GEN
Solar/Wind Harmer
-0.002
972077AH1-588 GEN
Solar/Wind Harmer
33.983
972079AH1-589 GEN
Solar/Wind Harmer
40.119
970715AG2-457 GEN
Solar/Wind Harmer
13.168
203952AE2-129 C
Solar/Wind Harmer
0.002
962411AG1-090 GEN
Solar/Wind Harmer
6.982
20216026CON.GEN2
50/50
0.034
20079426CONEMAGH
Adder
3.775
970125AG2-091 GEN
Solar/Wind Harmer
1.295
971879AH1-460 GEN
Solar/Wind Harmer
14.212
203841AF2-001_GEN
Solar/Wind Harmer
4.294
971541AH1-268 GEN
Solar/Wind Harmer
12.657
971419AH1-201 GEN
Solar/Wind Harmer
7.878
970899AG2-561 GEN
Solar/Wind Harmer
3.875
203818AF1-086 GEN
Solar/Wind Harmer
1.499
972323AH1-746 GEN
Solar/Wind Harmer
5.804
20089126CSLMN_L13
Solar/Wind Harmer
0.107
20089026BF_G21_K23
Solar/Wind Harmer
0.108
960051AF2-296 GEN
Solar/Wind Harmer
3.038
945751AF1-240 GEN
Solar/Wind Harmer
2.769
971703AH1-357 GEN
Solar/Wind Harmer
2.832
971707AH1-359 GEN
Solar/Wind Harmer
2.832
965131AG1-378 GEN
Solar/Wind Harmer
1.396
20334926Z1-069 C
Solar/Wind Harmer
1.023
202652Y1-033 WT C
Solar/Wind Harmer
0.001
20082926HNSMLK 2
Adder
10.299
20083126HNSMLK 4
Adder
10.299
203854AF2-039 C
Solar/Wind Harmer
0.001
203932AE1-123
Adder
3.33
971185AH1-051 GEN
Solar/Wind Harmer
3.328
971355AH1-158 GEN
Solar/Wind Harmer
5.546
970647AG2-420 GEN
Solar/Wind Harmer
2.187
20120126WRREN CT
Adder
9.897
970335AG2-220 GEN
Solar/Wind Harmer
3.383
971127AH1-005 GEN
Solar/Wind Harmer
2.467
238219AF1-167 C
Solar/Wind Harmer
1.377
238202AE2-262_GEN
Solar/Wind Harmer
0.006
971627AH1-313 GEN
Solar/Wind Harmer
10.129
20335126GROZ1-110
Adder
3.195
20335226CANZ2-011
Adder
3.106
957161AF2-010 GEN
Solar/Wind Harmer
7.149
203830AF1-094 GEN
Solar/Wind Harmer
0.001
203948AG1-140 C
Solar/Wind Harmer
0.253
203962AF1-287 GEN
Solar/Wind Harmer
1.756
20328326MANOR_T86
Adder
0.174
20084926LAKVU GN
Adder
0.214
941421AE2-139 GEN
Solar/Wind Harmer
0
972271AH1-720 GEN
Adder
7.484
200917MEHOOPANY_G
Solar/Wind Harmer
0.348
970679AG2-439 GEN
Solar/Wind Harmer
0.491
970643AG2-418 GEN
Solar/Wind Harmer
1.094
237043AE2-125 C
Solar/Wind Harmer
0
20083726HOMER C1
50/50
273.666
20215826CON.GEN1
50/50
0.045
20063626IUP CO-G
50/50
0.269
20083926HOMER C3
50/50
227.06
20083826HOMER C2
50/50
214.485
20092526R32
Solar/Wind Harmer
0.638
203961AE2-224 GEN
Solar/Wind Harmer
0.016
203844AF2-092 C
Solar/Wind Harmer
2.446
203850AG1-041 C
Solar/Wind Harmer
2.443
20091526CHSTN_FL
Solar/Wind Harmer
0.332
20090526Q36
Solar/Wind Harmer
0.777
203993AD2-133_GEN1
Solar/Wind Harmer
0.769
965121AG1-377 GEN
Solar/Wind Harmer
1.396
203804AE2-113_GEN
Solar/Wind Harmer
0.01
20083226HNSMLK 5
Adder
10.299
203855AF2-088 C
Solar/Wind Harmer
0.001
970555AG2-356 GEN
Solar/Wind Harmer
2.189
970663AG2-429 GEN
Solar/Wind Harmer
7.897
970663AG2-429 GEN
Solar/Wind Harmer
1.726
970677AG2-438 GEN
Solar/Wind Harmer
1.035
966771AG1-548 GEN
Solar/Wind Harmer
3.065
966771AG1-548 GEN
Solar/Wind Harmer
3.831
20084926LAKVU GN
Adder
0.24
203926AA2-133 GEN
Adder
2.591
971321AH1-140 GEN
Solar/Wind Harmer
10.895
971321AH1-140 GEN
Solar/Wind Harmer
3.026
20334726NME_Y1-047
Adder
2.326
20390726Y2-042
Adder
1.869
971055AG2-654 GEN
Solar/Wind Harmer
0.567
203843AF2-002_GEN
Solar/Wind Harmer
2.147
970631AG2-411 GEN
Solar/Wind Harmer
14.498
20088826HIGHLAND
Solar/Wind Harmer
0.002
971279AH1-102 GEN
Solar/Wind Harmer
21.925
957561AF2-050 GEN
Solar/Wind Harmer
10.244
971423AH1-203 GEN
Solar/Wind Harmer
13.656
20094526CT_V3-030
Solar/Wind Harmer
0.328
20089226LOOKOUT
Solar/Wind Harmer
0.305
203987AE2-118 C
Solar/Wind Harmer
3.001
970713AG2-456 GEN
Solar/Wind Harmer
13.168
971705AH1-358 GEN
Solar/Wind Harmer
4.72
971709AH1-360 GEN
Solar/Wind Harmer
4.72
20082826HNSMLK 1
Adder
10.299
20083026HNSMLK 3
Adder
10.299
20091326SHAW-D
Adder
1.15
972169AH1-667 GEN
Solar/Wind Harmer
2.196
203954AE2-126 C
Solar/Wind Harmer
0.002
20326126BLOSSBCT
Adder
3.813
20335026MILZ1-092
Adder
3.761
944411AF1-106 GEN
Solar/Wind Harmer
3.837
971183AH1-050 GEN
Solar/Wind Harmer
5.546
238183AE2-316 GEN
Solar/Wind Harmer
0.006
20072226SHAWVL 2
Adder
21.555
970337AG2-221 GEN
Solar/Wind Harmer
2.408
970647AG2-420 GEN
Solar/Wind Harmer
0.365
203860AG1-193 C
Solar/Wind Harmer
0.001
970511AG2-327 GEN
Solar/Wind Harmer
1.052
238206AE2-263_GEN
Solar/Wind Harmer
0.006
970267AG2-176 GEN
Solar/Wind Harmer
14.691
238215AE2-248 C
Solar/Wind Harmer
1.499
203835AF1-098 GEN
Solar/Wind Harmer
0.006
203813AE2-344_GEN
Solar/Wind Harmer
10.181
20084926LAKVU GN
Adder
0.214
970643AG2-418 GEN
Solar/Wind Harmer
0.729
971865AH1-452 GEN
Solar/Wind Harmer
0.652
24035802GEN-Y1-012
Adder
0.244
972075AH1-587 GEN
Solar/Wind Harmer
27.086
203955AF1-039 C O1
Solar/Wind Harmer
0.001
20398826ARMNA MT
Solar/Wind Harmer
0.066
203848AF2-166 C
Solar/Wind Harmer
2.277
970305AG2-200 GEN
Solar/Wind Harmer
2.184
203859AF2-294 C
Solar/Wind Harmer
1.807
970313AG2-206 GEN
Solar/Wind Harmer
5.051
216419AE2-001 C
Solar/Wind Harmer
1.896
203979AG1-198 GEN
Solar/Wind Harmer
0.001
971933AH1-491 GEN
Solar/Wind Harmer
1.854
203980AG1-197 GEN
Solar/Wind Harmer
0.001
203963AG1-253 GEN
Solar/Wind Harmer
0.402
971931AH1-490 GEN
Solar/Wind Harmer
1.751
203947AF1-006 C
Solar/Wind Harmer
0.056
961581Q1080_CY23
External Queue
26.08061408996582
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.86
MECLTFEXP_MEC->PJM
CLTF
0.096
SIGELTFEXP_SIGE->PJM
CLTF
0.001
LGEELTFEXP_LGEE->PJM
CLTF
0.014
WECLTFEXP_WEC->PJM
CLTF
0.037
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CBM NorthLTFEXP_CBM-N->PJM
CBM
33.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-DRT27_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-DRT27_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.18 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:761.59
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-004-DRT-003_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-004-DRT-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.18 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:761.58
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.287
20083826HOMER C2
50/50
125.905
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-DRT26_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-DRT26_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.09 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:761.0
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
203948AG1-140 C
Solar/Wind Harmer
0.192
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-004-DRT-004_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-004-DRT-004_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:119.09 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:760.99
MW Contribution:10.29
Bus #Bus NameTypeMW Contribution
20083326SEWRDB34
50/50
5.316
20079426CONEMAGH
50/50
2.012
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.279
971879AH1-460 GEN
Solar/Wind Harmer
10.757
970125AG2-091 GEN
Solar/Wind Harmer
0.973
971541AH1-268 GEN
Solar/Wind Harmer
5.425
970899AG2-561 GEN
Solar/Wind Harmer
3.099
971419AH1-201 GEN
Solar/Wind Harmer
4.737
203818AF1-086 GEN
Solar/Wind Harmer
3.543
20089126CSLMN_L13
Solar/Wind Harmer
1.075
20089026BF_G21_K23
Solar/Wind Harmer
0.851
945751AF1-240 GEN
Solar/Wind Harmer
1.915
960051AF2-296 GEN
Solar/Wind Harmer
2.416
971703AH1-357 GEN
Solar/Wind Harmer
2.351
971707AH1-359 GEN
Solar/Wind Harmer
2.351
20334926Z1-069 C
Solar/Wind Harmer
2.378
965131AG1-378 GEN
Solar/Wind Harmer
2.165
20082926HNSMLK 2
Adder
5.952
20083126HNSMLK 4
Adder
5.952
203854AF2-039 C
Solar/Wind Harmer
0.396
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.884
202652Y1-033 WT C
Solar/Wind Harmer
0.867
971185AH1-051 GEN
Solar/Wind Harmer
2.196
971355AH1-158 GEN
Solar/Wind Harmer
2.554
20120126WRREN CT
Adder
5.663
203856AF2-165 C
Solar/Wind Harmer
1.066
970647AG2-420 GEN
Solar/Wind Harmer
1.784
970335AG2-220 GEN
Solar/Wind Harmer
2.75
971127AH1-005 GEN
Solar/Wind Harmer
1.774
20083726HOMER C1
50/50
161.388
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.286
20083826HOMER C2
50/50
125.904
20092526R32
Solar/Wind Harmer
2.747
203844AF2-092 C
Solar/Wind Harmer
1.84
203850AG1-041 C
Solar/Wind Harmer
1.835
203961AE2-224 GEN
Solar/Wind Harmer
4.534
20091526CHSTN_FL
Solar/Wind Harmer
1.213
20090526Q36
Solar/Wind Harmer
1.831
203993AD2-133_GEN1
Solar/Wind Harmer
1.831
940863AE2-074 GEN
Solar/Wind Harmer
2.026
203804AE2-113_GEN
Solar/Wind Harmer
5.229
965121AG1-377 GEN
Solar/Wind Harmer
2.165
941231AE2-117 GEN
Solar/Wind Harmer
0.633
20083226HNSMLK 5
Adder
5.952
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.529
970555AG2-356 GEN
Solar/Wind Harmer
1.834
20080526COLVER13
50/50
1.085
203843AF2-002_GEN
Solar/Wind Harmer
1.64
970631AG2-411 GEN
Solar/Wind Harmer
10.286
20088826HIGHLAND
Solar/Wind Harmer
2.563
971279AH1-102 GEN
Solar/Wind Harmer
12.747
957561AF2-050 GEN
Solar/Wind Harmer
7.484
20094526CT_V3-030
Solar/Wind Harmer
1.054
971423AH1-203 GEN
Solar/Wind Harmer
10.358
964201AG1-281 GEN
Solar/Wind Harmer
0.863
20089226LOOKOUT
Solar/Wind Harmer
1.047
970713AG2-456 GEN
Solar/Wind Harmer
9.402
971705AH1-358 GEN
Solar/Wind Harmer
2.733
971709AH1-360 GEN
Solar/Wind Harmer
2.733
203987AE2-118 C
Solar/Wind Harmer
2.238
964391AG1-301 GEN
Solar/Wind Harmer
0.624
20082826HNSMLK 1
Adder
5.952
20083026HNSMLK 3
Adder
5.952
20326126BLOSSBCT
Adder
2.225
20091326SHAW-D
Adder
0.637
972169AH1-667 GEN
Solar/Wind Harmer
1.745
203954AE2-126 C
Solar/Wind Harmer
0.587
20335026MILZ1-092
Adder
2.2
944411AF1-106 GEN
Solar/Wind Harmer
2.027
959471AF2-238 GEN
Solar/Wind Harmer
0.554
970337AG2-221 GEN
Solar/Wind Harmer
1.834
971183AH1-050 GEN
Solar/Wind Harmer
3.66
238183AE2-316 GEN
Solar/Wind Harmer
3.792
970647AG2-420 GEN
Solar/Wind Harmer
0.207
959441AF2-235 GEN
Solar/Wind Harmer
0.256
238219AF1-167 C
Solar/Wind Harmer
1.119
238202AE2-262_GEN
Solar/Wind Harmer
2.065
971627AH1-313 GEN
Solar/Wind Harmer
8.096
20335126GROZ1-110
Adder
1.859
20335226CANZ2-011
Adder
1.807
957161AF2-010 GEN
Solar/Wind Harmer
5.859
203830AF1-094 GEN
Solar/Wind Harmer
0.458
20080926SITHE
50/50
0.519
946071AF1-272 GEN
Solar/Wind Harmer
6.95
203839AF1-321 GEN
Solar/Wind Harmer
3.279
20084626FORWARD
Solar/Wind Harmer
1.291
203857AF2-221 C
Solar/Wind Harmer
2.433
970123AG2-090 GEN
Solar/Wind Harmer
2.271
203940AF1-140 C
Solar/Wind Harmer
0.746
20088926STNY CRK
Solar/Wind Harmer
1.824
971441AH1-212 GEN
Solar/Wind Harmer
2.985
971427AH1-205 GEN
Solar/Wind Harmer
2.203
20083426SW_E13_K22
Solar/Wind Harmer
0.433
20088626ARWF_N39
Solar/Wind Harmer
2.667
20303426NA_O38_P22
Solar/Wind Harmer
2.159
944781AF1-143 GEN
Solar/Wind Harmer
3.685
203853AF1-134 C O1
Solar/Wind Harmer
0.73
972077AH1-588 GEN
Solar/Wind Harmer
28.207
972079AH1-589 GEN
Solar/Wind Harmer
23.233
970715AG2-457 GEN
Solar/Wind Harmer
9.402
972075AH1-587 GEN
Solar/Wind Harmer
22.348
203952AE2-129 C
Solar/Wind Harmer
0.656
203946AE2-131 C
Solar/Wind Harmer
0.654
962411AG1-090 GEN
Solar/Wind Harmer
10.283
20398826ARMNA MT
Solar/Wind Harmer
2.294
203955AF1-039 C O1
Solar/Wind Harmer
0.422
203848AF2-166 C
Solar/Wind Harmer
1.851
946381AF1-302 GEN
Solar/Wind Harmer
1.897
970305AG2-200 GEN
Solar/Wind Harmer
1.791
203859AF2-294 C
Solar/Wind Harmer
1.519
238217AF1-153 C O1
Solar/Wind Harmer
0.539
970313AG2-206 GEN
Solar/Wind Harmer
4.238
203980AG1-197 GEN
Solar/Wind Harmer
0.345
203979AG1-198 GEN
Solar/Wind Harmer
0.275
971933AH1-491 GEN
Solar/Wind Harmer
1.513
216419AE2-001 C
Solar/Wind Harmer
1.506
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.431
203947AF1-006 C
Solar/Wind Harmer
0.378
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.435
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.433
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.062
972271AH1-720 GEN
Adder
4.389
200917MEHOOPANY_G
Solar/Wind Harmer
2.049
970679AG2-439 GEN
Solar/Wind Harmer
0.467
970511AG2-327 GEN
Solar/Wind Harmer
0.883
20072226SHAWVL 2
Adder
12.024
203860AG1-193 C
Solar/Wind Harmer
0.265
238206AE2-263_GEN
Solar/Wind Harmer
1.924
970267AG2-176 GEN
Solar/Wind Harmer
12.049
961971AG1-040 GEN
Solar/Wind Harmer
0.454
238215AE2-248 C
Solar/Wind Harmer
1.19
203835AF1-098 GEN
Solar/Wind Harmer
1.801
203813AE2-344_GEN
Solar/Wind Harmer
8.321
20084926LAKVU GN
Adder
0.122
970663AG2-429 GEN
Solar/Wind Harmer
6.03
970663AG2-429 GEN
Solar/Wind Harmer
0.982
970677AG2-438 GEN
Solar/Wind Harmer
0.757
966771AG1-548 GEN
Solar/Wind Harmer
10.963
966771AG1-548 GEN
Solar/Wind Harmer
2.125
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.526
20334726NME_Y1-047
Adder
1.377
971321AH1-140 GEN
Solar/Wind Harmer
8.423
971321AH1-140 GEN
Solar/Wind Harmer
1.632
20390726Y2-042
Adder
1.117
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.098
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.304
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.108
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.189
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.377
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-2_PN-500-004A-DRT_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-2_PN-500-004A-DRT_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.2 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:716.99
MW Contribution:10.3
Bus #Bus NameTypeMW Contribution
20083726HOMER C1
50/50
161.556
20215826CON.GEN1
50/50
0.028
20063626IUP CO-G
50/50
0.162
20083926HOMER C3
50/50
133.462
20083826HOMER C2
50/50
126.07
20092526R32
Solar/Wind Harmer
2.751
203844AF2-092 C
Solar/Wind Harmer
1.843
203850AG1-041 C
Solar/Wind Harmer
1.837
203961AE2-224 GEN
Solar/Wind Harmer
4.541
20091526CHSTN_FL
Solar/Wind Harmer
1.215
20090526Q36
Solar/Wind Harmer
1.835
203993AD2-133_GEN1
Solar/Wind Harmer
1.835
940863AE2-074 GEN
Solar/Wind Harmer
2.03
203804AE2-113_GEN
Solar/Wind Harmer
5.24
20083326SEWRDB34
50/50
5.324
20079426CONEMAGH
50/50
2.015
20216026CON.GEN2
50/50
0.02
203841AF2-001_GEN
Solar/Wind Harmer
3.284
971879AH1-460 GEN
Solar/Wind Harmer
10.772
970125AG2-091 GEN
Solar/Wind Harmer
0.975
971541AH1-268 GEN
Solar/Wind Harmer
5.433
970899AG2-561 GEN
Solar/Wind Harmer
3.104
971419AH1-201 GEN
Solar/Wind Harmer
4.744
203818AF1-086 GEN
Solar/Wind Harmer
3.548
20089126CSLMN_L13
Solar/Wind Harmer
1.077
20089026BF_G21_K23
Solar/Wind Harmer
0.853
945751AF1-240 GEN
Solar/Wind Harmer
1.918
960051AF2-296 GEN
Solar/Wind Harmer
2.42
971703AH1-357 GEN
Solar/Wind Harmer
2.355
971707AH1-359 GEN
Solar/Wind Harmer
2.355
20334926Z1-069 C
Solar/Wind Harmer
2.383
965131AG1-378 GEN
Solar/Wind Harmer
2.169
20082926HNSMLK 2
Adder
5.966
20083126HNSMLK 4
Adder
5.966
203854AF2-039 C
Solar/Wind Harmer
0.397
944411AF1-106 GEN
Solar/Wind Harmer
0.218
203932AE1-123
Adder
1.888
202652Y1-033 WT C
Solar/Wind Harmer
0.869
971185AH1-051 GEN
Solar/Wind Harmer
2.202
971355AH1-158 GEN
Solar/Wind Harmer
2.56
20120126WRREN CT
Adder
5.678
203856AF2-165 C
Solar/Wind Harmer
1.068
970647AG2-420 GEN
Solar/Wind Harmer
1.789
970335AG2-220 GEN
Solar/Wind Harmer
2.757
971127AH1-005 GEN
Solar/Wind Harmer
1.779
959441AF2-235 GEN
Solar/Wind Harmer
0.257
238219AF1-167 C
Solar/Wind Harmer
1.122
238202AE2-262_GEN
Solar/Wind Harmer
2.071
971627AH1-313 GEN
Solar/Wind Harmer
8.119
20335126GROZ1-110
Adder
1.864
20335226CANZ2-011
Adder
1.812
957161AF2-010 GEN
Solar/Wind Harmer
5.877
203830AF1-094 GEN
Solar/Wind Harmer
0.46
203948AG1-140 C
Solar/Wind Harmer
0.192
203962AF1-287 GEN
Solar/Wind Harmer
1.44
20328326MANOR_T86
Adder
0.102
962511AG1-100 GEN
Solar/Wind Harmer
0.434
20084926LAKVU GN
Adder
0.122
941421AE2-139 GEN
Solar/Wind Harmer
2.069
972271AH1-720 GEN
Adder
4.404
200917MEHOOPANY_G
Solar/Wind Harmer
2.057
970679AG2-439 GEN
Solar/Wind Harmer
0.469
965121AG1-377 GEN
Solar/Wind Harmer
2.169
941231AE2-117 GEN
Solar/Wind Harmer
0.635
20083226HNSMLK 5
Adder
5.966
203855AF2-088 C
Solar/Wind Harmer
0.191
203846AF2-130 C
Solar/Wind Harmer
0.53
970555AG2-356 GEN
Solar/Wind Harmer
1.838
970663AG2-429 GEN
Solar/Wind Harmer
6.046
970663AG2-429 GEN
Solar/Wind Harmer
0.984
970677AG2-438 GEN
Solar/Wind Harmer
0.759
966771AG1-548 GEN
Solar/Wind Harmer
10.997
966771AG1-548 GEN
Solar/Wind Harmer
2.131
20084926LAKVU GN
Adder
0.137
203926AA2-133 GEN
Adder
1.532
20334726NME_Y1-047
Adder
1.382
971321AH1-140 GEN
Solar/Wind Harmer
8.457
971321AH1-140 GEN
Solar/Wind Harmer
1.639
20390726Y2-042
Adder
1.122
20080926SITHE
50/50
0.52
946071AF1-272 GEN
Solar/Wind Harmer
6.958
203839AF1-321 GEN
Solar/Wind Harmer
3.284
20084626FORWARD
Solar/Wind Harmer
1.292
203857AF2-221 C
Solar/Wind Harmer
2.437
970123AG2-090 GEN
Solar/Wind Harmer
2.275
203940AF1-140 C
Solar/Wind Harmer
0.747
20088926STNY CRK
Solar/Wind Harmer
1.827
971441AH1-212 GEN
Solar/Wind Harmer
2.99
971427AH1-205 GEN
Solar/Wind Harmer
2.207
20083426SW_E13_K22
Solar/Wind Harmer
0.434
20088626ARWF_N39
Solar/Wind Harmer
2.671
20303426NA_O38_P22
Solar/Wind Harmer
2.162
944781AF1-143 GEN
Solar/Wind Harmer
3.692
203853AF1-134 C O1
Solar/Wind Harmer
0.732
972077AH1-588 GEN
Solar/Wind Harmer
28.263
972079AH1-589 GEN
Solar/Wind Harmer
23.279
970715AG2-457 GEN
Solar/Wind Harmer
9.421
972075AH1-587 GEN
Solar/Wind Harmer
22.395
203952AE2-129 C
Solar/Wind Harmer
0.657
203946AE2-131 C
Solar/Wind Harmer
0.656
962411AG1-090 GEN
Solar/Wind Harmer
10.305
20398826ARMNA MT
Solar/Wind Harmer
2.3
203955AF1-039 C O1
Solar/Wind Harmer
0.423
203848AF2-166 C
Solar/Wind Harmer
1.855
946381AF1-302 GEN
Solar/Wind Harmer
1.902
970305AG2-200 GEN
Solar/Wind Harmer
1.796
203859AF2-294 C
Solar/Wind Harmer
1.523
238217AF1-153 C O1
Solar/Wind Harmer
0.541
970313AG2-206 GEN
Solar/Wind Harmer
4.249
203980AG1-197 GEN
Solar/Wind Harmer
0.346
203979AG1-198 GEN
Solar/Wind Harmer
0.276
971933AH1-491 GEN
Solar/Wind Harmer
1.518
216419AE2-001 C
Solar/Wind Harmer
1.511
203963AG1-253 GEN
Solar/Wind Harmer
0.293
971931AH1-490 GEN
Solar/Wind Harmer
1.436
203947AF1-006 C
Solar/Wind Harmer
0.379
20080526COLVER13
50/50
1.087
203843AF2-002_GEN
Solar/Wind Harmer
1.642
970631AG2-411 GEN
Solar/Wind Harmer
10.3
20088826HIGHLAND
Solar/Wind Harmer
2.567
971279AH1-102 GEN
Solar/Wind Harmer
12.766
957561AF2-050 GEN
Solar/Wind Harmer
7.496
20094526CT_V3-030
Solar/Wind Harmer
1.056
971423AH1-203 GEN
Solar/Wind Harmer
10.375
964201AG1-281 GEN
Solar/Wind Harmer
0.864
20089226LOOKOUT
Solar/Wind Harmer
1.049
970713AG2-456 GEN
Solar/Wind Harmer
9.421
971705AH1-358 GEN
Solar/Wind Harmer
2.739
971709AH1-360 GEN
Solar/Wind Harmer
2.739
203987AE2-118 C
Solar/Wind Harmer
2.243
964391AG1-301 GEN
Solar/Wind Harmer
0.625
20082826HNSMLK 1
Adder
5.966
20083026HNSMLK 3
Adder
5.966
20326126BLOSSBCT
Adder
2.23
20091326SHAW-D
Adder
0.639
972169AH1-667 GEN
Solar/Wind Harmer
1.749
203954AE2-126 C
Solar/Wind Harmer
0.588
20335026MILZ1-092
Adder
2.205
944411AF1-106 GEN
Solar/Wind Harmer
2.032
959471AF2-238 GEN
Solar/Wind Harmer
0.556
970337AG2-221 GEN
Solar/Wind Harmer
1.838
971183AH1-050 GEN
Solar/Wind Harmer
3.669
238183AE2-316 GEN
Solar/Wind Harmer
3.802
970647AG2-420 GEN
Solar/Wind Harmer
0.208
970511AG2-327 GEN
Solar/Wind Harmer
0.885
20072226SHAWVL 2
Adder
12.056
203860AG1-193 C
Solar/Wind Harmer
0.266
238206AE2-263_GEN
Solar/Wind Harmer
1.93
970267AG2-176 GEN
Solar/Wind Harmer
12.084
961971AG1-040 GEN
Solar/Wind Harmer
0.456
238215AE2-248 C
Solar/Wind Harmer
1.193
203835AF1-098 GEN
Solar/Wind Harmer
1.806
203813AE2-344_GEN
Solar/Wind Harmer
8.348
20084926LAKVU GN
Adder
0.122
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.082
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.257
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.098
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.376
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.173
CBM NorthLTFEXP_CBM-N->PJM
CBM
20.51
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer l/o PN_P2-3_PN-500-DRT33_SRT-SL


Base Case Flowgate

Area:PENELEC/PJM
Facility Description:
KEYSTONE _3-KEYSTONE 230.0/500.0 kV Ckt 4 transformer
Contingency Name:
PN_P2-3_PN-500-DRT33_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.54 %
Rating:639.0 MVA
Rating Type:B
MVA to Mitigate:712.74
MW Contribution:9.71
Bus #Bus NameTypeMW Contribution
20216026CON.GEN2
50/50
0.019
20083326SEWRDB34
50/50
4.935
20079426CONEMAGH
50/50
1.887
203841AF2-001_GEN
Solar/Wind Harmer
3.098
971879AH1-460 GEN
Solar/Wind Harmer
10.144
970125AG2-091 GEN
Solar/Wind Harmer
0.917
971541AH1-268 GEN
Solar/Wind Harmer
5.102
970899AG2-561 GEN
Solar/Wind Harmer
2.926
971419AH1-201 GEN
Solar/Wind Harmer
4.481
203818AF1-086 GEN
Solar/Wind Harmer
3.327
20089126CSLMN_L13
Solar/Wind Harmer
1.031
20089026BF_G21_K23
Solar/Wind Harmer
0.816
945751AF1-240 GEN
Solar/Wind Harmer
1.798
960051AF2-296 GEN
Solar/Wind Harmer
2.253
971703AH1-357 GEN
Solar/Wind Harmer
2.204
971707AH1-359 GEN
Solar/Wind Harmer
2.204
20334926Z1-069 C
Solar/Wind Harmer
2.216
965131AG1-378 GEN
Solar/Wind Harmer
2
20082926HNSMLK 2
Adder
5.623
20083126HNSMLK 4
Adder
5.623
202652Y1-033 WT C
Solar/Wind Harmer
0.847
203854AF2-039 C
Solar/Wind Harmer
0.365
203932AE1-123
Adder
1.757
944411AF1-106 GEN
Solar/Wind Harmer
0.2
971185AH1-051 GEN
Solar/Wind Harmer
2.058
971355AH1-158 GEN
Solar/Wind Harmer
2.393
20120126WRREN CT
Adder
5.302
203856AF2-165 C
Solar/Wind Harmer
0.999
970647AG2-420 GEN
Solar/Wind Harmer
1.674
970335AG2-220 GEN
Solar/Wind Harmer
2.507
971127AH1-005 GEN
Solar/Wind Harmer
1.617
959441AF2-235 GEN
Solar/Wind Harmer
0.241
238219AF1-167 C
Solar/Wind Harmer
1.034
238202AE2-262_GEN
Solar/Wind Harmer
1.87
971627AH1-313 GEN
Solar/Wind Harmer
7.332
957161AF2-010 GEN
Solar/Wind Harmer
5.518
20335126GROZ1-110
Adder
1.677
20335226CANZ2-011
Adder
1.63
203830AF1-094 GEN
Solar/Wind Harmer
0.432
203948AG1-140 C
Solar/Wind Harmer
0.181
203962AF1-287 GEN
Solar/Wind Harmer
1.356
962511AG1-100 GEN
Solar/Wind Harmer
0.409
20084926LAKVU GN
Adder
0.115
20328326MANOR_T86
Adder
0.091
941421AE2-139 GEN
Solar/Wind Harmer
1.826
972271AH1-720 GEN
Adder
3.879
200917MEHOOPANY_G
Solar/Wind Harmer
1.778
20080926SITHE
50/50
0.493
946071AF1-272 GEN
Solar/Wind Harmer
6.65
203839AF1-321 GEN
Solar/Wind Harmer
3.098
20084626FORWARD
Solar/Wind Harmer
1.219
203857AF2-221 C
Solar/Wind Harmer
2.292
970123AG2-090 GEN
Solar/Wind Harmer
2.139
203940AF1-140 C
Solar/Wind Harmer
0.7
20088926STNY CRK
Solar/Wind Harmer
1.725
971427AH1-205 GEN
Solar/Wind Harmer
2.084
971441AH1-212 GEN
Solar/Wind Harmer
2.794
20083426SW_E13_K22
Solar/Wind Harmer
0.411
20088626ARWF_N39
Solar/Wind Harmer
2.475
20303426NA_O38_P22
Solar/Wind Harmer
2.004
944781AF1-143 GEN
Solar/Wind Harmer
3.533
203853AF1-134 C O1
Solar/Wind Harmer
0.681
972077AH1-588 GEN
Solar/Wind Harmer
26.452
972079AH1-589 GEN
Solar/Wind Harmer
21.787
970715AG2-457 GEN
Solar/Wind Harmer
8.817
972075AH1-587 GEN
Solar/Wind Harmer
20.869
203952AE2-129 C
Solar/Wind Harmer
0.606
203946AE2-131 C
Solar/Wind Harmer
0.605
962411AG1-090 GEN
Solar/Wind Harmer
9.501
203955AF1-039 C O1
Solar/Wind Harmer
0.412
20398826ARMNA MT
Solar/Wind Harmer
2.11
203848AF2-166 C
Solar/Wind Harmer
1.73
970305AG2-200 GEN
Solar/Wind Harmer
1.677
946381AF1-302 GEN
Solar/Wind Harmer
1.756
238217AF1-153 C O1
Solar/Wind Harmer
0.496
203859AF2-294 C
Solar/Wind Harmer
1.387
970313AG2-206 GEN
Solar/Wind Harmer
3.861
203980AG1-197 GEN
Solar/Wind Harmer
0.326
203979AG1-198 GEN
Solar/Wind Harmer
0.259
971933AH1-491 GEN
Solar/Wind Harmer
1.425
203963AG1-253 GEN
Solar/Wind Harmer
0.276
971931AH1-490 GEN
Solar/Wind Harmer
1.353
216419AE2-001 C
Solar/Wind Harmer
1.35
203947AF1-006 C
Solar/Wind Harmer
0.357
20080526COLVER13
50/50
1.024
203843AF2-002_GEN
Solar/Wind Harmer
1.549
970631AG2-411 GEN
Solar/Wind Harmer
9.713
20088826HIGHLAND
Solar/Wind Harmer
2.407
971279AH1-102 GEN
Solar/Wind Harmer
11.989
971423AH1-203 GEN
Solar/Wind Harmer
9.809
957561AF2-050 GEN
Solar/Wind Harmer
6.963
20094526CT_V3-030
Solar/Wind Harmer
0.99
964201AG1-281 GEN
Solar/Wind Harmer
0.806
20089226LOOKOUT
Solar/Wind Harmer
1.004
970713AG2-456 GEN
Solar/Wind Harmer
8.817
971705AH1-358 GEN
Solar/Wind Harmer
2.563
971709AH1-360 GEN
Solar/Wind Harmer
2.563
203987AE2-118 C
Solar/Wind Harmer
2.054
20082826HNSMLK 1
Adder
5.623
20083026HNSMLK 3
Adder
5.623
964391AG1-301 GEN
Solar/Wind Harmer
0.569
203954AE2-126 C
Solar/Wind Harmer
0.541
20326126BLOSSBCT
Adder
2.045
20091326SHAW-D
Adder
0.586
972169AH1-667 GEN
Solar/Wind Harmer
1.605
20335026MILZ1-092
Adder
2.022
944411AF1-106 GEN
Solar/Wind Harmer
1.863
971183AH1-050 GEN
Solar/Wind Harmer
3.43
959471AF2-238 GEN
Solar/Wind Harmer
0.507
970337AG2-221 GEN
Solar/Wind Harmer
1.677
970647AG2-420 GEN
Solar/Wind Harmer
0.195
238183AE2-316 GEN
Solar/Wind Harmer
3.509
203860AG1-193 C
Solar/Wind Harmer
0.249
970511AG2-327 GEN
Solar/Wind Harmer
0.804
20072226SHAWVL 2
Adder
10.985
970267AG2-176 GEN
Solar/Wind Harmer
11.379
238206AE2-263_GEN
Solar/Wind Harmer
1.743
961971AG1-040 GEN
Solar/Wind Harmer
0.429
203835AF1-098 GEN
Solar/Wind Harmer
1.697
203813AE2-344_GEN
Solar/Wind Harmer
7.866
238215AE2-248 C
Solar/Wind Harmer
1.065
20084926LAKVU GN
Adder
0.115
20083726HOMER C1
50/50
153.413
20215826CON.GEN1
50/50
0.027
20063626IUP CO-G
50/50
0.154
20083926HOMER C3
50/50
126.285
20083826HOMER C2
50/50
119.291
20092526R32
Solar/Wind Harmer
2.579
203844AF2-092 C
Solar/Wind Harmer
1.732
203850AG1-041 C
Solar/Wind Harmer
1.726
203961AE2-224 GEN
Solar/Wind Harmer
4.218
20091526CHSTN_FL
Solar/Wind Harmer
1.131
20090526Q36
Solar/Wind Harmer
1.697
203993AD2-133_GEN1
Solar/Wind Harmer
1.697
940863AE2-074 GEN
Solar/Wind Harmer
1.893
203804AE2-113_GEN
Solar/Wind Harmer
4.875
965121AG1-377 GEN
Solar/Wind Harmer
2
20083226HNSMLK 5
Adder
5.623
941231AE2-117 GEN
Solar/Wind Harmer
0.579
203855AF2-088 C
Solar/Wind Harmer
0.176
203846AF2-130 C
Solar/Wind Harmer
0.494
970555AG2-356 GEN
Solar/Wind Harmer
1.677
970663AG2-429 GEN
Solar/Wind Harmer
5.593
970663AG2-429 GEN
Solar/Wind Harmer
0.911
970677AG2-438 GEN
Solar/Wind Harmer
0.713
966771AG1-548 GEN
Solar/Wind Harmer
10.331
966771AG1-548 GEN
Solar/Wind Harmer
2.002
20084926LAKVU GN
Adder
0.129
971321AH1-140 GEN
Solar/Wind Harmer
9.071
971321AH1-140 GEN
Solar/Wind Harmer
1.758
203926AA2-133 GEN
Adder
1.344
20334726NME_Y1-047
Adder
1.195
LAGNLTFEXP_LAGN->PJM
CLTF
0.299
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.169
TVALTFEXP_TVA->PJM
CLTF
0.144
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.737
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.569
MECLTFEXP_MEC->PJM
CLTF
0.336
SIGELTFEXP_SIGE->PJM
CLTF
0.01
LGEELTFEXP_LGEE->PJM
CLTF
0.128
WECLTFEXP_WEC->PJM
CLTF
0.083
CPLELTFEXP_CPLE->PJM
CLTF
0.023
CBM NorthLTFEXP_CBM-N->PJM
CBM
16.276
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.284

Details for KEYSTONE-01CABOT 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT45_SRT-SL


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01CABOT 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT45_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.06 %
Rating:2844.0 MVA
Rating Type:B
MVA to Mitigate:3073.32
MW Contribution:9.34
Bus #Bus NameTypeMW Contribution
200032KEYS G1
50/50
9.37
200030CONE G1
50/50
8.067
200105AA1-076 ST
50/50
6.749
20079426CONEMAGH
50/50
1.974
972241AH1-705 GEN
Adder
5.87
209071AE2-133 GEN
Solar/Wind Harmer
1.638
970665AG2-430 GEN
Solar/Wind Harmer
9.601
209018SUNBIPCT
Adder
7.207
946731AF1-337 GEN
Solar/Wind Harmer
0.966
212507AE2-042_GEN
Solar/Wind Harmer
2.88
961341AF2-425 GEN
Solar/Wind Harmer
0.946
212174INGE
Adder
1.045
212266LOR1
Solar/Wind Harmer
0.123
970237AG2-161 GEN
Solar/Wind Harmer
3.283
970125AG2-091 GEN
Solar/Wind Harmer
0.915
971879AH1-460 GEN
Solar/Wind Harmer
9.943
961301AF2-421 GEN
Solar/Wind Harmer
0.907
963151AG1-164 GEN
Solar/Wind Harmer
0.907
209023WIENIPP1
Adder
9.782
209025WIENIPP3
Adder
4.883
203841AF2-001_GEN
Solar/Wind Harmer
2.966
209010PEIP 1
Adder
0.573
208909MACR G3
Adder
132.56
20465127PORT CT
Adder
2.462
20671928W4-073
Solar/Wind Harmer
0.354
207518AF1-320_GEN
Solar/Wind Harmer
2.977
207437AD2-070 GEN
Solar/Wind Harmer
0.246
971519AH1-257 GEN
Solar/Wind Harmer
2.043
966181AG1-487 GEN
Solar/Wind Harmer
3.061
20675828AU_W4-064
Solar/Wind Harmer
0.139
207439AE1-081 C O1
Solar/Wind Harmer
0.047
20674328GAR_V4-001
Solar/Wind Harmer
0.088
217208PARK ELE C
Solar/Wind Harmer
0.019
217083KRNY_132
Adder
7.108
217121ECCF
Adder
0.332
217209CENTRL HS C
Solar/Wind Harmer
0.034
218449LINSOLAR C
Solar/Wind Harmer
0.759
20676428JCR_X2-075
Solar/Wind Harmer
0.258
207528AF2-192 GEN
Solar/Wind Harmer
0.417
200032KEYS G1
50/50
9.738
200033KEYS G2
50/50
9.354
235619AD2-113 G1
50/50
4.303
235620AD2-113 G2
50/50
4.303
200030CONE G1
50/50
7.35
957561AF2-050 GEN
Solar/Wind Harmer
8.364
209067AE2-060 GEN
Solar/Wind Harmer
1.658
946691AF1-333 GEN
Solar/Wind Harmer
0.966
946741AF1-338 GEN
Solar/Wind Harmer
0.966
972245AH1-707 GEN
Adder
5.177
961331AF2-424 GEN
Solar/Wind Harmer
0.946
961421AF2-433 GEN
Solar/Wind Harmer
0.945
957921AF2-086 GEN
Solar/Wind Harmer
0.919
209142AF1-226 GEN
Solar/Wind Harmer
5.469
209093AE2-110 GEN
Solar/Wind Harmer
2.362
209120AE2-241 GEN
Solar/Wind Harmer
3.125
209027LOR2_Q27
Solar/Wind Harmer
4.276
209022WHFR IPP
Adder
3.07
20088826HIGHLAND
Solar/Wind Harmer
2.5
963161AG1-165 GEN
Solar/Wind Harmer
0.907
209025WIENIPP3
Adder
4.784
964201AG1-281 GEN
Solar/Wind Harmer
0.904
963071AG1-156 GEN
Solar/Wind Harmer
2.485
970095AG2-074 GEN
Solar/Wind Harmer
5.639
203843AF2-002_GEN
Solar/Wind Harmer
1.483
970631AG2-411 GEN
Solar/Wind Harmer
9.336
203987AE2-118 C
Solar/Wind Harmer
2.934
964391AG1-301 GEN
Solar/Wind Harmer
0.87
200104AA1-076 CT2
50/50
5.953
200103AA1-076 CT1
50/50
5.902
20083726HOMER C1
Adder
119.436
203961AE2-224 GEN
Solar/Wind Harmer
5.066
959431AF2-234 GEN
Solar/Wind Harmer
1.935
964051AG1-259 GEN
Solar/Wind Harmer
1.298
964061AG1-260 GEN
Solar/Wind Harmer
1.298
959421AF2-233 GEN
Solar/Wind Harmer
0.968
209045AE2-271 GEN
Solar/Wind Harmer
15.932
20092526R32
Solar/Wind Harmer
2.679
209026WIENIPP4
Adder
4.833
203850AG1-041 C
Solar/Wind Harmer
1.758
203844AF2-092 C
Solar/Wind Harmer
1.75
961261AF2-417 GEN
Solar/Wind Harmer
0.878
209116AE2-175 GEN
Solar/Wind Harmer
3.49
941231AE2-117 GEN
Solar/Wind Harmer
0.862
20091526CHSTN_FL
Solar/Wind Harmer
1.261
966421AG1-511 GEN
Solar/Wind Harmer
7.075
20462827N BANGR8
Adder
0.588
20675128HRM_W1-127
Solar/Wind Harmer
0.139
200033KEYS G2
50/50
9.728
235621AD2-113 G3
50/50
4.303
235622AD2-113 G4
50/50
4.303
972299AH1-734 GEN
50/50
109.978
200031CONE G2
50/50
7.97
200031CONE G2
50/50
7.417
20088626ARWF_N39
Solar/Wind Harmer
3.078
20303426NA_O38_P22
Solar/Wind Harmer
2.492
209137AF2-361 C
Solar/Wind Harmer
3.206
209130AF1-271A GEN
Solar/Wind Harmer
2.72
946751AF1-339 GEN
Solar/Wind Harmer
0.966
209054AE2-059 GEN
Solar/Wind Harmer
1.626
209059AE2-084 GEN
Solar/Wind Harmer
2.4
961431AF2-434 GEN
Solar/Wind Harmer
0.945
961541AF2-445A GEN
Solar/Wind Harmer
3.071
203857AF2-221 C
Solar/Wind Harmer
2.286
970123AG2-090 GEN
Solar/Wind Harmer
2.134
971441AH1-212 GEN
Solar/Wind Harmer
2.981
203940AF1-140 C
Solar/Wind Harmer
0.735
208972BECR K09
Solar/Wind Harmer
0.96
203839AF1-321 GEN
Solar/Wind Harmer
2.966
20084626FORWARD
Solar/Wind Harmer
1.171
211065PSPA IPP
Solar/Wind Harmer
0.389
211065PSPA IPP
Solar/Wind Harmer
0.389
209029WAYMART-WD
Solar/Wind Harmer
2.562
209009PEIP 2
Adder
6.957
209010PEIP 1
Adder
3.152
209010PEIP 1
Adder
0.462
966111AG1-480 GEN
Solar/Wind Harmer
0.072
966111AG1-480 GEN
Solar/Wind Harmer
2.738
20465127PORT CT
Adder
3.267
20674128FR_U2-059
Solar/Wind Harmer
0.151
20634528N27_Y2-018
Solar/Wind Harmer
0.218
964851AG1-348 GEN
Solar/Wind Harmer
1.423
207471AF2-354 C
Solar/Wind Harmer
0.412
20674928WA_W3-044
Solar/Wind Harmer
0.388
20676228FRD_X1-012
Solar/Wind Harmer
0.472
946071AF1-272 GEN
Solar/Wind Harmer
4.593
217204WCALDSOLAR C
Solar/Wind Harmer
0.056
217086KRNY_131
Adder
7.123
217083KRNY_132
Adder
7.063
217206BARNGR HS C
Solar/Wind Harmer
0.024
217201HACKENSOLA C
Solar/Wind Harmer
0.056
972237AH1-703 GEN
Adder
7.734
20674528F3S_W2-016
Solar/Wind Harmer
1.079
217202FBANKSOLAR C
Solar/Wind Harmer
0.056
20671828STAW2-080
Solar/Wind Harmer
0.08
217081WEATEXAS C
Solar/Wind Harmer
0.065
219036LINDEN_G7
Adder
12.627
219035LINDEN_G8
Adder
12.447
972261AH1-715 GEN2
Adder
12.087
207442AE1-156 GEN
Solar/Wind Harmer
0.56
20676128MHD_W3-029
Solar/Wind Harmer
0.359
218418LINDEN_G5
Adder
12.876
218419LINDEN_G6
Adder
12.876
972260AH1-715 GEN1
Adder
10.31
20673828FLE_V3-070
Solar/Wind Harmer
0.343
218440SUMMTASSOC C
Solar/Wind Harmer
0.095
20088926STNY CRK
Solar/Wind Harmer
1.661
971427AH1-205 GEN
Solar/Wind Harmer
2.004
924131AB2-057 GEN
Solar/Wind Harmer
0.757
20716928W4-060COL
Solar/Wind Harmer
0.519
20720628TIN_W1-124
Solar/Wind Harmer
0.717
20641628MLH_W1-032
Solar/Wind Harmer
0.211
20465527S.RDG CT
Adder
2.192
20478527GLRA_Q45
Adder
0.279
219817TRENTONSOL C
Solar/Wind Harmer
0.788
20628028LAKEHURS
Adder
0.671
20714928UPF_X1-085
Solar/Wind Harmer
0.286
963391AG1-188 GEN
Solar/Wind Harmer
1.344
219114HARTZY_C
Solar/Wind Harmer
0.586
963401AG1-189 GEN
Solar/Wind Harmer
0.805
207500AE2-000G1
Solar/Wind Harmer
21.99
207497AE2-000G2
Solar/Wind Harmer
21.99
207507AE2-000G3
Solar/Wind Harmer
21.99
20636128O CRK C2
Adder
4.499
20716428NHV_W2-082
Solar/Wind Harmer
1.237
213535CROYDN11
Adder
7.015
219615MILLCREEK C
Solar/Wind Harmer
0.163
213815MOSER1-3
Adder
2.423
213815MOSER1-3
Adder
2.423
219921AF1-264
Solar/Wind Harmer
0.098
230407AD2-065 C
Solar/Wind Harmer
0.089
230422AE1-104_GEN1
Solar/Wind Harmer
22.608
230425AE1-104_GEN2
Solar/Wind Harmer
22.608
972233AH1-701 GEN
Adder
2.817
230433AD2-135 GEN
Solar/Wind Harmer
0.068
228304LOGAN
Adder
16.226
228307PCLP GT
Adder
8.101
20083426SW_E13_K22
Solar/Wind Harmer
0.382
228251CARLLS#4
Adder
0.421
213587EDDYSTN3
Adder
52.851
213589EDDYSTN4
Adder
52.845
233939AC1-091 C
Solar/Wind Harmer
0.603
233970AC1-092 C
Solar/Wind Harmer
0.603
971149AH1-027 GEN
Solar/Wind Harmer
2.321
232899W1-062
Adder
6.594
232416X2-083
Adder
0.309
970545AG2-347 GEN
Solar/Wind Harmer
44.807
231940T-011
Adder
0.511
20673628F1S_V4-069
Solar/Wind Harmer
0.135
20675428EAM_W2-061
Solar/Wind Harmer
0.142
972275AH1-722 GEN
Adder
23.671
217213AMBOY SO C
Solar/Wind Harmer
0.095
218428ETC SOLAR C
Solar/Wind Harmer
0.027
205941AD2-115 GEN
Solar/Wind Harmer
0.762
209008PAXT IPP
Adder
1.79
20635028RRCT1&2
Adder
8.57
20635128RRCT3&4
Adder
8.273
971419AH1-201 GEN
Solar/Wind Harmer
4.308
20635828PARLN1&2
Adder
5.444
971541AH1-268 GEN
Solar/Wind Harmer
4.702
217197RE CRAN C
Solar/Wind Harmer
0.391
20742028HF_AC1-207
Solar/Wind Harmer
0.566
20467927PC_Q59Y356
Adder
0.693
20715228NPK_W1-113
Solar/Wind Harmer
0.31
207454AA2-184 E
Solar/Wind Harmer
0.719
20465527S.RDG CT
Adder
2.266
219680HOPEWELLV C1
Solar/Wind Harmer
0.055
20714828MDF_W3-079
Solar/Wind Harmer
0.218
963711AG1-223 GEN
Solar/Wind Harmer
1.052
207445AB1-138_GEN
Solar/Wind Harmer
0.409
20628028LAKEHURS
Adder
1.326
207487AE2-000G4
Solar/Wind Harmer
21.99
207522AF2-254 C
Solar/Wind Harmer
0.999
20720728JCB_W1-129
Solar/Wind Harmer
0.208
20465427SHAW CT
Adder
3.208
20466127PORT 5CT
Adder
21.799
971007AG2-625 GEN
Solar/Wind Harmer
2.081
20633028GILCT9
Adder
23.129
966181AG1-487 GEN
Solar/Wind Harmer
0.205
20674628WNG_W3-110
Solar/Wind Harmer
0.321
207510AF2-138 C
Solar/Wind Harmer
1.414
20676728BRNX1-095
Solar/Wind Harmer
0.137
217194REDH C
Solar/Wind Harmer
0.377
217169METRODIV C
Solar/Wind Harmer
0.03
217186ESSEX_G9
Adder
12.224
217211CAMDEN ST C
Solar/Wind Harmer
0.019
20673728F2S_V4-070
Solar/Wind Harmer
0.135
219249CENTRALDIV C
Solar/Wind Harmer
0.03
219908AB1-139 C
Solar/Wind Harmer
0.284
219919AE1-041 FULL
Solar/Wind Harmer
0.03
20635028RRCT1&2
Adder
8.704
20635128RRCT3&4
Adder
7.216
20635828PARLN1&2
Adder
2.466
20635928PARLN3&4
Adder
2.466
971279AH1-102 GEN
Solar/Wind Harmer
11.049
967451AG2-055 C O1
Solar/Wind Harmer
126.059
218438BLK ROCK C
Solar/Wind Harmer
0.099
219612MATRIX C
Solar/Wind Harmer
0.134
20720528MAN_W1-024
Solar/Wind Harmer
0.183
20716228APLW2-078
Solar/Wind Harmer
0.636
219918AC2-009 C
Solar/Wind Harmer
0.044
20714528FRN_Y2-051
Solar/Wind Harmer
0.21
219276PARKLANDSO C
Solar/Wind Harmer
0.329
971423AH1-203 GEN
Solar/Wind Harmer
9.332
971667AH1-334 GEN
Solar/Wind Harmer
1.934
219727YARDVSOLFA C
Solar/Wind Harmer
0.642
20636028O CRK C1
Adder
4.934
20715028HAN_X4-015
Solar/Wind Harmer
0.208
20720828JCB_W4-025
Solar/Wind Harmer
0.315
972221AH1-695 GEN
Adder
116.247
20716028EGP_W2-019
Solar/Wind Harmer
0.323
959561AF2-247 GEN
Solar/Wind Harmer
0.337
219610FLORENCE C
Solar/Wind Harmer
0.95
219348LDSOLAR C
Solar/Wind Harmer
0.411
219221BRL12CT1
Adder
6.121
219223BRL12CT3
Adder
6.121
20094526CT_V3-030
Solar/Wind Harmer
0.928
219906AC1-017 C
Solar/Wind Harmer
0.152
213815MOSER1-3
Adder
2.423
219236SOUTHERNHQ C
Solar/Wind Harmer
0.046
219291REEVESSOUT C
Solar/Wind Harmer
0.041
219912AD2-042 GEN
Solar/Wind Harmer
0.54
219766PARADISE C
Solar/Wind Harmer
0.213
219623KINSLEYBEA C
Solar/Wind Harmer
0.289
213560DLW11-12
Adder
1.839
228729W2-030 C
Solar/Wind Harmer
0.389
230415AB2-049 C
Solar/Wind Harmer
0.127
228304LOGAN
Adder
14.593
230430AE1-229_GEN
Solar/Wind Harmer
5.888
971553AH1-274 GEN
Solar/Wind Harmer
1.618
213958STHWK5-6
Adder
1.826
228711V2-041C
Solar/Wind Harmer
0.401
228202CUMB CT
Adder
11.017
213497CHSTR7-9
Adder
1.807
972251AH1-710 GEN
Adder
31.224
233971AC1-093 C
Solar/Wind Harmer
0.538
970695AG2-447 GEN
Solar/Wind Harmer
2.458
233952AC2-187 GEN
Solar/Wind Harmer
0.771
972133AH1-634 GEN
Solar/Wind Harmer
6.789
972073AH1-586 GEN
Solar/Wind Harmer
6.416
233990AG1-397 GEN
Solar/Wind Harmer
0.785
232406W1-004 FULL
Solar/Wind Harmer
0.686
234015AF2-250 C
Solar/Wind Harmer
0.082
232914OH NUG3
Adder
6.046
232916OH NUG5
Adder
6.046
232921TASLEY2G
Adder
3.534
233900O-025 C
Adder
0.806
233996TM1833_GEN
Solar/Wind Harmer
0.867
233997TMININ_4.2
Solar/Wind Harmer
0.867
233940AF2-379 C
Solar/Wind Harmer
0.128
233994AC2-023 GEN
Solar/Wind Harmer
1.84
960671AF2-358 GEN
Solar/Wind Harmer
12.255
232907VN8
Adder
20.546
232417X3-008 C
Solar/Wind Harmer
1.369
233982AB2-133 GEN
Solar/Wind Harmer
3.33
233918AB1-142 GEN
Solar/Wind Harmer
0.677
970643AG2-418 GEN
Solar/Wind Harmer
1.116
966131AG1-482 GEN
Solar/Wind Harmer
2.281
970511AG2-327 GEN
Solar/Wind Harmer
1.088
205917AD1-020 ES
Solar/Wind Harmer
0.429
238215AE2-248 C
Solar/Wind Harmer
1.728
959471AF2-238 GEN
Solar/Wind Harmer
0.649
970337AG2-221 GEN
Solar/Wind Harmer
2.145
944411AF1-106 GEN
Solar/Wind Harmer
2.176
20089226LOOKOUT
Solar/Wind Harmer
0.866
238206AE2-263_GEN
Solar/Wind Harmer
2.297
972169AH1-667 GEN
Solar/Wind Harmer
1.705
241966AE1-183 GEN
Solar/Wind Helper
0.465
213611FALLS1-3
Adder
2.448
214194N WALES4
Adder
0.59
219304NAMERICA C
Solar/Wind Harmer
0.213
219222BRL12CT2
Adder
6.121
219287REEVESEAST C
Solar/Wind Harmer
0.914
219686LUMSOLAR_N C
Solar/Wind Harmer
0.138
219907AC1-030 C
Solar/Wind Harmer
0.095
218660EHAMPSOLAR C
Solar/Wind Harmer
0.119
219904AC1-010 C
Solar/Wind Harmer
0.256
219258KINSLEYDEP C
Solar/Wind Harmer
0.219
213560DLW11-12
Adder
1.839
228728W1-130C
Solar/Wind Harmer
0.446
230434AG1-499 GEN
Solar/Wind Harmer
0.389
230511AF1-262
Solar/Wind Harmer
0.123
228732V1-021 C
Adder
0.127
228351V2-046C
Solar/Wind Harmer
1.348
970997AG2-616 GEN
Solar/Wind Harmer
6.412
945431AF1-208 GEN
Solar/Wind Harmer
5.769
213958STHWK5-6
Adder
1.826
228206SHRMN CT
Adder
11.063
213497CHSTR7-9
Adder
1.807
213497CHSTR7-9
Adder
1.807
970679AG2-439 GEN
Solar/Wind Harmer
1.227
205967AE2-211_GEN
Solar/Wind Harmer
7.042
231917EM10
Adder
1.625
231918WEST 1
Adder
2.309
233972AC1-094 C
Solar/Wind Harmer
0.455
232901NORTHST
Adder
5.707
232900DEMECSMY
Adder
6.325
972177AH1-672 GEN
Solar/Wind Harmer
9.202
233954AC2-188 GEN
Solar/Wind Harmer
0.771
233950AC2-186 GEN
Solar/Wind Harmer
0.386
232434Z2-077 GEN
Solar/Wind Harmer
0.171
232910NRG_G1
Adder
5.912
232404W1-003 C
Solar/Wind Harmer
0.686
232917OH NUG6
Adder
6.019
232915OH NUG4
Adder
6.006
971195AH1-057 GEN
Solar/Wind Harmer
0.749
233998TM1NIN_3.36
Solar/Wind Harmer
0.867
232428Y3-058 C
Solar/Wind Harmer
0.571
965821AG1-450 GEN
Solar/Wind Harmer
3.563
232919VN10
Adder
1.92
232426Y1-080 FULL
Solar/Wind Harmer
0.131
970277AG2-181 GEN
Solar/Wind Harmer
3.431
233964AF2-378 GEN
Solar/Wind Harmer
0.087
232422X3-066 FULL
Solar/Wind Harmer
0.171
234012AE2-112_GEN
Solar/Wind Harmer
1.572
233930AB2-032 GEN
Solar/Wind Harmer
0.57
233915AB1-141 GEN
Solar/Wind Harmer
0.677
970643AG2-418 GEN
Solar/Wind Harmer
2.399
200917MEHOOPANY_G
Solar/Wind Harmer
4.185
20465027TOLNA CT
Adder
2.636
966131AG1-482 GEN
Solar/Wind Harmer
0.103
941421AE2-139 GEN
Solar/Wind Harmer
3.454
970899AG2-561 GEN
Solar/Wind Harmer
2.237
205975AE2-345_GEN
Solar/Wind Harmer
7.727
965131AG1-378 GEN
Solar/Wind Harmer
2.199
203818AF1-086 GEN
Solar/Wind Harmer
2.781
970335AG2-220 GEN
Solar/Wind Harmer
3.369
971127AH1-005 GEN
Solar/Wind Harmer
2.173
944411AF1-106 GEN
Solar/Wind Harmer
0.234
960051AF2-296 GEN
Solar/Wind Harmer
2.055
208923BUSO V4-027
Solar/Wind Harmer
0.287
208856AE1-226 GEN
Solar/Wind Harmer
2.033
20089126CSLMN_L13
Solar/Wind Harmer
0.89
20089026BF_G21_K23
Solar/Wind Harmer
0.704
238202AE2-262_GEN
Solar/Wind Harmer
2.464
971627AH1-313 GEN
Solar/Wind Harmer
9.662
203854AF2-039 C
Solar/Wind Harmer
0.387
20334926Z1-069 C
Solar/Wind Harmer
1.923
235058AG1-386 C
Solar/Wind Helper
0.618
254305AE2-115 C
Solar/Wind Helper
0.305
241832AE2-181_GEN
Solar/Wind Helper
0.592
270541AE2-072 C
Solar/Wind Helper
1.764
270485AE1-090_GEN
Solar/Wind Helper
0.227
942871AE2-306 GEN
Solar/Wind Helper
0.341
270044AE2-322 C
Solar/Wind Helper
1.116
270404AC1-167 GEN
Solar/Wind Helper
0.93
241974AD2-163_GEN2
Solar/Wind Helper
1.648
241955AC1-078 GEN
Solar/Wind Helper
1.849
960801AF2-371 GEN
Solar/Wind Helper
0.936
964871AG1-351 GEN
Solar/Wind Helper
0.646
270191TR4_S_V150
Solar/Wind Helper
0.998
270247TR4_N_V136
Solar/Wind Helper
0.457
254303AC2-168 GEN
Solar/Wind Helper
0.214
958961AF2-187 GEN
Solar/Wind Helper
2.479
241885AC2-103 GEN1
Solar/Wind Helper
2.341
241807AE2-176_GEN
Solar/Wind Helper
1.633
241808AF1-120 C
Solar/Wind Helper
0.713
241840AF1-064_GEN
Solar/Wind Helper
0.977
960841AF2-375 GEN
Solar/Wind Helper
1.571
247522W1-056 GEN
Solar/Wind Helper
1.295
270462AD2-086
Solar/Wind Helper
2.607
270223U2-072_GEN1
Solar/Wind Helper
0.671
270578AF1-285 GEN2
Solar/Wind Helper
0.455
270391AF1-285 GEN3
Solar/Wind Helper
0.455
270349AD2-093_GEN
Solar/Wind Helper
1.344
246936BC-WTG1
Solar/Wind Helper
2.128
944231AF1-091 GEN
Solar/Wind Helper
3.478
24695305TIMB G C
Solar/Wind Helper
2.317
247521TR3_G114
Solar/Wind Helper
1.808
270246TR4_N_V150
Solar/Wind Helper
0.457
207408W3-077 C
Solar/Wind Harmer
0.412
20675728RH_W2-091
Solar/Wind Harmer
0.279
207484AF2-139 C O1
Solar/Wind Harmer
0.412
971009AG2-626 GEN
Solar/Wind Harmer
1.327
20675928HOL_W4-097
Solar/Wind Harmer
0.106
20674828DL_W4-046
Solar/Wind Harmer
0.52
207511W3-106 GEN
Solar/Wind Harmer
0.523
20676328BVR_Y1-020
Solar/Wind Harmer
0.263
207530AG1-191 GEN
Solar/Wind Harmer
1.095
966261AG1-495 GEN
Solar/Wind Harmer
1.401
217167KRNY_14
Adder
7.108
217086KRNY_131
Adder
7.048
217147KRNY_1212
Adder
6.761
217147KRNY_1212
Adder
6.64
217146KRNY_1234
Adder
6.625
217146KRNY_1234
Adder
6.58
218404KENILWRTH C
Adder
0.995
218524CNTRALGAS1 C
Solar/Wind Harmer
0.275
20675528CPH_W2-050
Solar/Wind Harmer
0.348
218526CNTRALGAS2 C
Solar/Wind Harmer
0.275
218455CINNBAY_CGEN
Adder
1.337
20635928PARLN3&4
Adder
5.444
20720428HOL_W1-112
Solar/Wind Harmer
0.251
971521AH1-258 GEN
Solar/Wind Harmer
1.959
20486527WR_V4-052
Adder
0.884
20714428HOW_X1-037
Solar/Wind Harmer
0.887
20714328BYD_X4-031
Solar/Wind Harmer
0.203
219620RIDERU C
Solar/Wind Harmer
0.04
207459AE1-142 C O1
Solar/Wind Harmer
0.743
971189AH1-054 GEN
Solar/Wind Harmer
0.827
970025AG2-016 GEN
Solar/Wind Harmer
1.985
208862AG1-362 C
Solar/Wind Harmer
0.662
20715728PEM_W1-119
Solar/Wind Harmer
0.373
20715828PEM_W1-120
Solar/Wind Harmer
0.373
20717128DIX_Z2-102
Solar/Wind Harmer
0.92
214067T20SOLAR
Solar/Wind Harmer
0.175
213611FALLS1-3
Adder
2.448
213611FALLS1-3
Adder
2.448
219607WPEMNERT C
Solar/Wind Harmer
0.287
219224BRL12CT4
Adder
6.121
219688LUMSOLAR_S C
Solar/Wind Harmer
0.138
219272CLEANLIGHT C
Solar/Wind Harmer
0.124
219914AD2-027 C
Solar/Wind Harmer
0.407
213561DLWR9-10
Adder
2.405
213561DLWR9-10
Adder
1.839
227927V4-067C
Solar/Wind Harmer
0.134
228754AB1-001 C
Solar/Wind Harmer
0.094
219137THOSOLAR C
Solar/Wind Harmer
0.815
971535AH1-265 GEN
Solar/Wind Harmer
2.857
971011AG2-627 GEN
Solar/Wind Harmer
5.134
972141AH1-641 GEN
Solar/Wind Harmer
1.924
964001AG1-254 GEN
Solar/Wind Harmer
1.36
228260V4-054C
Solar/Wind Harmer
0.686
213957STHWK3-4
Adder
1.826
213957STHWK3-4
Adder
1.826
228309CCLP NUG
Adder
17.271
228309CCLP NUG
Adder
16.429
213942SCHUYLKILL
Adder
2.386
213942SCHUYLKILL
Adder
1.824
970453AG2-297 GEN
Solar/Wind Harmer
1.838
20390726Y2-042
Adder
2.937
231919CHRIST1
Adder
3.04
231920CHRIST2
Adder
2.973
205951AE1-129_GEN
Solar/Wind Harmer
9.683
233973AC2-185 C
Solar/Wind Harmer
2.479
234033AF1-007_GEN
Solar/Wind Harmer
16.012
232904IR4
Adder
55.363
232920IR10
Adder
2.164
232432Z2-076 GEN
Solar/Wind Harmer
0.09
232813VAUGHN
Adder
0.403
233990AG1-397 GEN
Solar/Wind Harmer
0.038
232912OH NUG1
Adder
6.046
232913OH NUG2
Adder
5.965
233923SMA
Solar/Wind Harmer
3.179
233955AB2-172 GEN
Solar/Wind Harmer
3.421
231906DC3 NUG
Adder
9.57
231902DC CT7
Adder
7.65
231907DC10
Adder
2.389
232436AB1-176 C
Solar/Wind Harmer
0.157
233968AD2-076_GEN
Solar/Wind Harmer
4.532
970597AG2-380 GEN
Solar/Wind Harmer
2.846
20090526Q36
Solar/Wind Harmer
1.905
203993AD2-133_GEN1
Solar/Wind Harmer
1.905
971983AH1-536 GEN
Solar/Wind Harmer
5.114
233935AB2-179 C
Solar/Wind Harmer
1.708
205932AD2-116_GEN
Solar/Wind Harmer
0.672
205956AE1-196_GEN
Solar/Wind Harmer
0.672
205943AE1-185 GEN
Solar/Wind Harmer
0.67
20334726NME_Y1-047
Adder
2.811
960921AF2-383 GEN
Solar/Wind Harmer
0.223
20465027TOLNA CT
Adder
2.74
960921AF2-383 GEN
Solar/Wind Harmer
1.716
20083926HOMER C3
Adder
84.655
20083826HOMER C2
Adder
26.837
965121AG1-377 GEN
Solar/Wind Harmer
2.199
970555AG2-356 GEN
Solar/Wind Harmer
2.145
203855AF2-088 C
Solar/Wind Harmer
0.187
203975AE1-071-GEN
Solar/Wind Harmer
2.611
241997AF1-093 GEN
Solar/Wind Helper
0.465
241982AE2-343 S C
Solar/Wind Helper
0.375
254304AE2-114 C
Solar/Wind Helper
0.305
241886AC2-103 GEN2
Solar/Wind Helper
2.341
945411AF1-206 GEN
Solar/Wind Helper
2.418
945641AF1-229 GEN
Solar/Wind Helper
1.456
270499AE1-146 GEN
Solar/Wind Helper
2.492
972069AH1-584 GEN
Solar/Wind Harmer
6.131
972071AH1-585 GEN
Solar/Wind Harmer
6.131
233901CHERRYDALE C
Solar/Wind Harmer
0.771
232408W1-005 C
Solar/Wind Harmer
0.686
232410W1-006 C
Solar/Wind Harmer
0.686
232918OH NUG7
Adder
6.006
971747AH1-380 GEN
Solar/Wind Harmer
2.452
232905CHERITON_25
Adder
1.679
232926CRISFLD1
Adder
1.343
233946AB2-136 GEN
Solar/Wind Harmer
2.731
234036AF2-325 C
Solar/Wind Harmer
0.627
234041AC1-190 GEN
Solar/Wind Harmer
6.126
231131BLOOM ENRGY
Adder
2.981
233987AB2-037 GEN
Solar/Wind Harmer
7.779
233944AB2-135 GEN
Solar/Wind Harmer
3.582
232424Y1-079 C
Solar/Wind Harmer
0.385
233984AB2-036 GEN
Solar/Wind Harmer
8.511
234014AF1-036_GEN
Solar/Wind Harmer
1.85
233933AB2-153 GEN
Solar/Wind Harmer
0.769
20464827MOUNT CT
Adder
2.671
20464827MOUNT CT
Adder
2.592
208835TUHI V3-051
Solar/Wind Harmer
0.042
208835TUHI V3-051
Solar/Wind Harmer
0.042
203952AE2-129 C
Solar/Wind Harmer
0.666
203946AE2-131 C
Solar/Wind Harmer
0.665
962411AG1-090 GEN
Solar/Wind Harmer
10.445
970313AG2-206 GEN
Solar/Wind Harmer
5.222
205916AD1-020 GEN
Solar/Wind Harmer
1.994
203859AF2-294 C
Solar/Wind Harmer
1.812
216419AE2-001 C
Solar/Wind Harmer
2.128
20398826ARMNA MT
Solar/Wind Harmer
2.479
203853AF1-134 C O1
Solar/Wind Harmer
0.621
944781AF1-143 GEN
Solar/Wind Harmer
3.05
962101AG1-054 GEN
Solar/Wind Helper
1.21
241985AE1-237 GEN
Solar/Wind Helper
0.418
241967AE2-285_GEN
Solar/Wind Helper
1.064
241801AE1-079 GEN
Solar/Wind Helper
0.414
241996AE2-282_GEN
Solar/Wind Helper
1.276
241960AC2-195 GEN
Solar/Wind Helper
1.415
270224U2-072_GEN2
Solar/Wind Helper
0.671
270227U2-072_GEN3
Solar/Wind Helper
0.671
270228U2-072_GEN4
Solar/Wind Helper
0.671
270231U2-072_GEN5
Solar/Wind Helper
0.671
270471AD2-092_GEN
Solar/Wind Helper
1.344
246938BC-WTG3
Solar/Wind Helper
2.165
246937BC-WTG2
Solar/Wind Helper
2.128
270007AE1-245 C
Solar/Wind Helper
1.986
942801AE2-298 GEN
Solar/Wind Helper
0.555
946101AF1-275 GEN
Solar/Wind Helper
0.56
253378AE2-206_GEN
Solar/Wind Helper
1.088
276820AF1-078_GEN
Solar/Wind Helper
0.508
270518AE2-148 GEN
Solar/Wind Helper
10.958
966831AG1-554 GEN
Solar/Wind Helper
0.877
270054AF2-122 C O1
Solar/Wind Helper
1.222
270317AD1-130_GEN
Solar/Wind Helper
2.887
270284AF1-227 GEN1
Solar/Wind Helper
2.108
270286AF1-227 GEN2
Solar/Wind Helper
0.773
270287AF1-227 GEN3
Solar/Wind Helper
0.773
957201AF2-014 GEN
Solar/Wind Helper
1.682
247607V1-011 GEN
Solar/Wind Helper
1.324
270520AE2-214 GEN
Solar/Wind Helper
4.474
241973AD2-163_GEN1
Solar/Wind Helper
1.648
253383AE2-342_GEN
Solar/Wind Helper
0.73
945631AF1-228 GEN
Solar/Wind Helper
1.719
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.181
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.095
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
103.105
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.085
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
23.169
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.017
G-007ALTFEXP_G-007A->PJM
CMTX
37.853
CBM NorthLTFEXP_CBM-N->PJM
CBM
70.846
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for KEYSTONE-01SOBEND 500.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT32_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT32_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:2078.0 MVA
Rating Type:B
MVA to Mitigate:2239.81
MW Contribution:9.3
Bus #Bus NameTypeMW Contribution
200104AA1-076 CT2
50/50
6.15
200103AA1-076 CT1
50/50
6.096
20083726HOMER C1
Adder
119.115
203961AE2-224 GEN
Solar/Wind Harmer
5.136
959431AF2-234 GEN
Solar/Wind Harmer
1.903
964051AG1-259 GEN
Solar/Wind Harmer
1.276
964061AG1-260 GEN
Solar/Wind Harmer
1.276
959421AF2-233 GEN
Solar/Wind Harmer
0.952
20092526R32
Solar/Wind Harmer
2.707
209045AE2-271 GEN
Solar/Wind Harmer
15.641
20091526CHSTN_FL
Solar/Wind Harmer
1.307
941231AE2-117 GEN
Solar/Wind Harmer
0.891
203850AG1-041 C
Solar/Wind Harmer
1.767
209026WIENIPP4
Adder
4.719
203844AF2-092 C
Solar/Wind Harmer
1.755
961261AF2-417 GEN
Solar/Wind Harmer
0.858
209116AE2-175 GEN
Solar/Wind Harmer
3.375
966421AG1-511 GEN
Solar/Wind Harmer
6.823
20462827N BANGR8
Adder
0.566
20675128HRM_W1-127
Solar/Wind Harmer
0.134
207408W3-077 C
Solar/Wind Harmer
0.397
20675728RH_W2-091
Solar/Wind Harmer
0.268
207484AF2-139 C O1
Solar/Wind Harmer
0.396
971009AG2-626 GEN
Solar/Wind Harmer
1.277
20675928HOL_W4-097
Solar/Wind Harmer
0.102
20674828DL_W4-046
Solar/Wind Harmer
0.5
207511W3-106 GEN
Solar/Wind Harmer
0.503
20676328BVR_Y1-020
Solar/Wind Harmer
0.252
207530AG1-191 GEN
Solar/Wind Harmer
1.052
20083926HOMER C3
Adder
95.203
20083826HOMER C2
Adder
89.93
20090526Q36
Solar/Wind Harmer
2.07
203993AD2-133_GEN1
Solar/Wind Harmer
2.07
200032KEYS G1
50/50
9.838
200030CONE G1
50/50
8.363
200105AA1-076 ST
50/50
6.971
20083326SEWRDB34
50/50
6.196
20079426CONEMAGH
50/50
2.01
972241AH1-705 GEN
Adder
5.792
209071AE2-133 GEN
Solar/Wind Harmer
1.612
970665AG2-430 GEN
Solar/Wind Harmer
9.444
209018SUNBIPCT
Adder
7.089
946731AF1-337 GEN
Solar/Wind Harmer
0.95
212507AE2-042_GEN
Solar/Wind Harmer
2.831
961341AF2-425 GEN
Solar/Wind Harmer
0.927
212174INGE
Adder
1.025
970125AG2-091 GEN
Solar/Wind Harmer
0.917
212266LOR1
Solar/Wind Harmer
0.12
970237AG2-161 GEN
Solar/Wind Harmer
3.216
971879AH1-460 GEN
Solar/Wind Harmer
9.935
203841AF2-001_GEN
Solar/Wind Harmer
2.951
961301AF2-421 GEN
Solar/Wind Harmer
0.886
963151AG1-164 GEN
Solar/Wind Harmer
0.886
209023WIENIPP1
Adder
9.55
209025WIENIPP3
Adder
4.767
971541AH1-268 GEN
Solar/Wind Harmer
4.975
209010PEIP 1
Adder
0.563
208909MACR G3
Adder
127.852
20465127PORT CT
Adder
2.371
20671928W4-073
Solar/Wind Harmer
0.341
207518AF1-320_GEN
Solar/Wind Harmer
2.865
207437AD2-070 GEN
Solar/Wind Harmer
0.236
971519AH1-257 GEN
Solar/Wind Harmer
1.965
966181AG1-487 GEN
Solar/Wind Harmer
2.943
20675828AU_W4-064
Solar/Wind Harmer
0.133
207439AE1-081 C O1
Solar/Wind Harmer
0.046
20674328GAR_V4-001
Solar/Wind Harmer
0.084
971419AH1-201 GEN
Solar/Wind Harmer
4.227
217208PARK ELE C
Solar/Wind Harmer
0.019
217083KRNY_132
Adder
6.808
217121ECCF
Adder
0.318
217209CENTRL HS C
Solar/Wind Harmer
0.033
218449LINSOLAR C
Solar/Wind Harmer
0.726
20676428JCR_X2-075
Solar/Wind Harmer
0.247
970679AG2-439 GEN
Solar/Wind Harmer
1.281
207528AF2-192 GEN
Solar/Wind Harmer
0.398
20673628F1S_V4-069
Solar/Wind Harmer
0.129
20675428EAM_W2-061
Solar/Wind Harmer
0.136
972275AH1-722 GEN
Adder
22.624
217213AMBOY SO C
Solar/Wind Harmer
0.09
218428ETC SOLAR C
Solar/Wind Harmer
0.026
205941AD2-115 GEN
Solar/Wind Harmer
0.726
209008PAXT IPP
Adder
1.707
20635028RRCT1&2
Adder
8.179
20635128RRCT3&4
Adder
7.895
20635828PARLN1&2
Adder
5.193
217197RE CRAN C
Solar/Wind Harmer
0.372
20742028HF_AC1-207
Solar/Wind Harmer
0.539
20467927PC_Q59Y356
Adder
0.659
20715228NPK_W1-113
Solar/Wind Harmer
0.295
207454AA2-184 E
Solar/Wind Harmer
0.685
20465527S.RDG CT
Adder
2.154
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
200917MEHOOPANY_G
Solar/Wind Harmer
4.452
20714828MDF_W3-079
Solar/Wind Harmer
0.207
963711AG1-223 GEN
Solar/Wind Harmer
1
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
970899AG2-561 GEN
Solar/Wind Harmer
2.52
207487AE2-000G4
Solar/Wind Harmer
20.861
207522AF2-254 C
Solar/Wind Harmer
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.197
972271AH1-720 GEN
Adder
8.193
213611FALLS1-3
Adder
2.318
214194N WALES4
Adder
0.558
965131AG1-378 GEN
Solar/Wind Harmer
2.478
20328326MANOR_T86
Adder
0.176
941421AE2-139 GEN
Solar/Wind Harmer
3.761
203818AF1-086 GEN
Solar/Wind Harmer
3.159
219304NAMERICA C
Solar/Wind Harmer
0.201
219222BRL12CT2
Adder
5.788
219287REEVESEAST C
Solar/Wind Harmer
0.863
219686LUMSOLAR_N C
Solar/Wind Harmer
0.13
219907AC1-030 C
Solar/Wind Harmer
0.089
218660EHAMPSOLAR C
Solar/Wind Harmer
0.112
219904AC1-010 C
Solar/Wind Harmer
0.241
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213560DLW11-12
Adder
1.734
228728W1-130C
Solar/Wind Harmer
0.42
970335AG2-220 GEN
Solar/Wind Harmer
3.755
971127AH1-005 GEN
Solar/Wind Harmer
2.422
230434AG1-499 GEN
Solar/Wind Harmer
0.367
230511AF1-262
Solar/Wind Harmer
0.115
228732V1-021 C
Adder
0.119
20335126GROZ1-110
Adder
2.833
20335226CANZ2-011
Adder
2.754
228351V2-046C
Solar/Wind Harmer
1.269
970997AG2-616 GEN
Solar/Wind Harmer
6.037
945431AF1-208 GEN
Solar/Wind Harmer
5.431
213958STHWK5-6
Adder
1.718
228206SHRMN CT
Adder
10.413
213497CHSTR7-9
Adder
1.697
213497CHSTR7-9
Adder
1.697
960051AF2-296 GEN
Solar/Wind Harmer
2.38
970643AG2-418 GEN
Solar/Wind Harmer
2.362
944411AF1-106 GEN
Solar/Wind Harmer
0.266
205967AE2-211_GEN
Solar/Wind Harmer
6.57
231917EM10
Adder
1.516
231918WEST 1
Adder
2.152
233972AC1-094 C
Solar/Wind Harmer
0.424
232901NORTHST
Adder
5.316
232900DEMECSMY
Adder
5.892
972177AH1-672 GEN
Solar/Wind Harmer
8.57
233954AC2-188 GEN
Solar/Wind Harmer
0.718
233950AC2-186 GEN
Solar/Wind Harmer
0.359
232434Z2-077 GEN
Solar/Wind Harmer
0.16
232910NRG_G1
Adder
5.506
232404W1-003 C
Solar/Wind Harmer
0.638
232917OH NUG6
Adder
5.605
232915OH NUG4
Adder
5.592
971195AH1-057 GEN
Solar/Wind Harmer
0.698
233998TM1NIN_3.36
Solar/Wind Harmer
0.807
232428Y3-058 C
Solar/Wind Harmer
0.532
965821AG1-450 GEN
Solar/Wind Harmer
3.317
232919VN10
Adder
1.788
232426Y1-080 FULL
Solar/Wind Harmer
0.122
970277AG2-181 GEN
Solar/Wind Harmer
3.195
233964AF2-378 GEN
Solar/Wind Harmer
0.081
232422X3-066 FULL
Solar/Wind Harmer
0.159
234012AE2-112_GEN
Solar/Wind Harmer
1.463
233930AB2-032 GEN
Solar/Wind Harmer
0.531
233915AB1-141 GEN
Solar/Wind Harmer
0.63
238202AE2-262_GEN
Solar/Wind Harmer
2.898
971627AH1-313 GEN
Solar/Wind Harmer
11.361
203854AF2-039 C
Solar/Wind Harmer
0.461
20334926Z1-069 C
Solar/Wind Harmer
2.308
966131AG1-482 GEN
Solar/Wind Harmer
0.094
205975AE2-345_GEN
Solar/Wind Harmer
6.986
971703AH1-357 GEN
Solar/Wind Harmer
1.95
971707AH1-359 GEN
Solar/Wind Harmer
1.95
208923BUSO V4-027
Solar/Wind Harmer
0.256
208856AE1-226 GEN
Solar/Wind Harmer
1.812
20089126CSLMN_L13
Solar/Wind Harmer
0.8
20089026BF_G21_K23
Solar/Wind Harmer
0.633
237048AF1-022 C
Solar/Wind Helper
0.21
237043AE2-125 C
Solar/Wind Helper
0.204
964991AG1-363 GEN
Solar/Wind Helper
3.553
235058AG1-386 C
Solar/Wind Helper
0.395
200032KEYS G1
50/50
10.224
200033KEYS G2
50/50
9.821
200030CONE G1
50/50
7.621
957561AF2-050 GEN
Solar/Wind Harmer
8.479
209067AE2-060 GEN
Solar/Wind Harmer
1.64
946691AF1-333 GEN
Solar/Wind Harmer
0.95
946741AF1-338 GEN
Solar/Wind Harmer
0.95
20088826HIGHLAND
Solar/Wind Harmer
2.526
972245AH1-707 GEN
Adder
5.084
961331AF2-424 GEN
Solar/Wind Harmer
0.927
961421AF2-433 GEN
Solar/Wind Harmer
0.927
957921AF2-086 GEN
Solar/Wind Harmer
0.901
209142AF1-226 GEN
Solar/Wind Harmer
5.365
209093AE2-110 GEN
Solar/Wind Harmer
2.317
209120AE2-241 GEN
Solar/Wind Harmer
3.066
964201AG1-281 GEN
Solar/Wind Harmer
0.92
209027LOR2_Q27
Solar/Wind Harmer
4.188
209022WHFR IPP
Adder
3.006
203987AE2-118 C
Solar/Wind Harmer
3.014
964391AG1-301 GEN
Solar/Wind Harmer
0.896
970631AG2-411 GEN
Solar/Wind Harmer
9.297
203843AF2-002_GEN
Solar/Wind Harmer
1.475
963161AG1-165 GEN
Solar/Wind Harmer
0.886
209025WIENIPP3
Adder
4.671
963071AG1-156 GEN
Solar/Wind Harmer
2.432
970095AG2-074 GEN
Solar/Wind Harmer
5.519
971279AH1-102 GEN
Solar/Wind Harmer
11.69
20094526CT_V3-030
Solar/Wind Harmer
0.992
20465427SHAW CT
Adder
3.099
20466127PORT 5CT
Adder
21.011
971007AG2-625 GEN
Solar/Wind Harmer
2.002
20633028GILCT9
Adder
22.239
966181AG1-487 GEN
Solar/Wind Harmer
0.197
20674628WNG_W3-110
Solar/Wind Harmer
0.309
207510AF2-138 C
Solar/Wind Harmer
1.359
20676728BRNX1-095
Solar/Wind Harmer
0.131
217194REDH C
Solar/Wind Harmer
0.361
217169METRODIV C
Solar/Wind Harmer
0.029
217186ESSEX_G9
Adder
11.707
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.129
219249CENTRALDIV C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.271
219919AE1-041 FULL
Solar/Wind Harmer
0.029
971423AH1-203 GEN
Solar/Wind Harmer
9.109
20635028RRCT1&2
Adder
8.307
20635128RRCT3&4
Adder
6.887
20635828PARLN1&2
Adder
2.352
20635928PARLN3&4
Adder
2.352
967451AG2-055 C O1
Solar/Wind Harmer
120.09
218438BLK ROCK C
Solar/Wind Harmer
0.095
219612MATRIX C
Solar/Wind Harmer
0.128
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20716228APLW2-078
Solar/Wind Harmer
0.605
219918AC2-009 C
Solar/Wind Harmer
0.042
20714528FRN_Y2-051
Solar/Wind Harmer
0.199
219276PARKLANDSO C
Solar/Wind Harmer
0.312
971667AH1-334 GEN
Solar/Wind Harmer
1.836
219727YARDVSOLFA C
Solar/Wind Harmer
0.61
20636028O CRK C1
Adder
4.681
20715028HAN_X4-015
Solar/Wind Harmer
0.197
20720828JCB_W4-025
Solar/Wind Harmer
0.299
20716028EGP_W2-019
Solar/Wind Harmer
0.306
972221AH1-695 GEN
Adder
110.049
959561AF2-247 GEN
Solar/Wind Harmer
0.319
219610FLORENCE C
Solar/Wind Harmer
0.898
219348LDSOLAR C
Solar/Wind Harmer
0.388
219221BRL12CT1
Adder
5.788
219223BRL12CT3
Adder
5.788
219906AC1-017 C
Solar/Wind Harmer
0.144
213815MOSER1-3
Adder
2.288
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.509
219766PARADISE C
Solar/Wind Harmer
0.201
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213560DLW11-12
Adder
1.734
228729W2-030 C
Solar/Wind Harmer
0.366
238215AE2-248 C
Solar/Wind Harmer
1.939
970511AG2-327 GEN
Solar/Wind Harmer
1.212
230415AB2-049 C
Solar/Wind Harmer
0.12
228304LOGAN
Adder
13.743
230430AE1-229_GEN
Solar/Wind Harmer
5.544
971553AH1-274 GEN
Solar/Wind Harmer
1.523
213958STHWK5-6
Adder
1.718
228711V2-041C
Solar/Wind Harmer
0.377
228202CUMB CT
Adder
10.369
959471AF2-238 GEN
Solar/Wind Harmer
0.727
970337AG2-221 GEN
Solar/Wind Harmer
2.406
213497CHSTR7-9
Adder
1.697
20326126BLOSSBCT
Adder
2.714
970643AG2-418 GEN
Solar/Wind Harmer
1.099
20335026MILZ1-092
Adder
2.683
944411AF1-106 GEN
Solar/Wind Harmer
2.472
972251AH1-710 GEN
Adder
29.207
233971AC1-093 C
Solar/Wind Harmer
0.501
970695AG2-447 GEN
Solar/Wind Harmer
2.29
233952AC2-187 GEN
Solar/Wind Harmer
0.718
972133AH1-634 GEN
Solar/Wind Harmer
6.322
972073AH1-586 GEN
Solar/Wind Harmer
5.974
233990AG1-397 GEN
Solar/Wind Harmer
0.731
232406W1-004 FULL
Solar/Wind Harmer
0.638
234015AF2-250 C
Solar/Wind Harmer
0.077
232914OH NUG3
Adder
5.63
232916OH NUG5
Adder
5.63
232921TASLEY2G
Adder
3.29
233900O-025 C
Adder
0.751
233996TM1833_GEN
Solar/Wind Harmer
0.807
233997TMININ_4.2
Solar/Wind Harmer
0.807
233940AF2-379 C
Solar/Wind Harmer
0.119
233994AC2-023 GEN
Solar/Wind Harmer
1.713
960671AF2-358 GEN
Solar/Wind Harmer
11.411
232907VN8
Adder
15.629
232417X3-008 C
Solar/Wind Harmer
1.274
233982AB2-133 GEN
Solar/Wind Harmer
3.1
233918AB1-142 GEN
Solar/Wind Harmer
0.63
238206AE2-263_GEN
Solar/Wind Harmer
2.701
972169AH1-667 GEN
Solar/Wind Harmer
2.031
203954AE2-126 C
Solar/Wind Harmer
0.634
966131AG1-482 GEN
Solar/Wind Harmer
2.083
970713AG2-456 GEN
Solar/Wind Harmer
7.799
971705AH1-358 GEN
Solar/Wind Harmer
2.267
971709AH1-360 GEN
Solar/Wind Harmer
2.267
205917AD1-020 ES
Solar/Wind Harmer
0.385
20089226LOOKOUT
Solar/Wind Harmer
0.779
237046AF1-021 C
Solar/Wind Helper
0.659
966261AG1-495 GEN
Solar/Wind Harmer
1.343
217167KRNY_14
Adder
6.808
217086KRNY_131
Adder
6.75
217147KRNY_1212
Adder
6.475
217147KRNY_1212
Adder
6.36
217146KRNY_1234
Adder
6.345
217146KRNY_1234
Adder
6.302
218404KENILWRTH C
Adder
0.952
20390726Y2-042
Adder
3.066
218524CNTRALGAS1 C
Solar/Wind Harmer
0.263
218526CNTRALGAS2 C
Solar/Wind Harmer
0.262
20675528CPH_W2-050
Solar/Wind Harmer
0.332
218455CINNBAY_CGEN
Adder
1.275
20635928PARLN3&4
Adder
5.193
20720428HOL_W1-112
Solar/Wind Harmer
0.239
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20486527WR_V4-052
Adder
0.84
20714428HOW_X1-037
Solar/Wind Harmer
0.844
20714328BYD_X4-031
Solar/Wind Harmer
0.193
20334726NME_Y1-047
Adder
2.991
219620RIDERU C
Solar/Wind Harmer
0.038
207459AE1-142 C O1
Solar/Wind Harmer
0.705
971189AH1-054 GEN
Solar/Wind Harmer
0.785
970025AG2-016 GEN
Solar/Wind Harmer
1.884
203926AA2-133 GEN
Adder
2.948
208862AG1-362 C
Solar/Wind Harmer
0.628
20715728PEM_W1-119
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.353
20717128DIX_Z2-102
Solar/Wind Harmer
0.872
214067T20SOLAR
Solar/Wind Harmer
0.166
213611FALLS1-3
Adder
2.318
213611FALLS1-3
Adder
2.318
965121AG1-377 GEN
Solar/Wind Harmer
2.478
219607WPEMNERT C
Solar/Wind Harmer
0.272
219224BRL12CT4
Adder
5.788
219688LUMSOLAR_S C
Solar/Wind Harmer
0.13
219272CLEANLIGHT C
Solar/Wind Harmer
0.117
219914AD2-027 C
Solar/Wind Harmer
0.384
213561DLWR9-10
Adder
2.268
213561DLWR9-10
Adder
1.734
227927V4-067C
Solar/Wind Harmer
0.126
228754AB1-001 C
Solar/Wind Harmer
0.088
219137THOSOLAR C
Solar/Wind Harmer
0.768
971535AH1-265 GEN
Solar/Wind Harmer
2.692
971011AG2-627 GEN
Solar/Wind Harmer
4.834
964001AG1-254 GEN
Solar/Wind Harmer
1.28
972141AH1-641 GEN
Solar/Wind Harmer
1.811
228260V4-054C
Solar/Wind Harmer
0.646
228309CCLP NUG
Adder
16.257
228309CCLP NUG
Adder
15.464
213957STHWK3-4
Adder
1.718
213957STHWK3-4
Adder
1.718
213942SCHUYLKILL
Adder
2.245
213942SCHUYLKILL
Adder
1.717
970453AG2-297 GEN
Solar/Wind Harmer
1.729
970555AG2-356 GEN
Solar/Wind Harmer
2.406
231919CHRIST1
Adder
2.835
231920CHRIST2
Adder
2.772
205951AE1-129_GEN
Solar/Wind Harmer
9.022
233973AC2-185 C
Solar/Wind Harmer
2.31
234033AF1-007_GEN
Solar/Wind Harmer
14.911
232904IR4
Adder
51.558
232920IR10
Adder
2.015
232432Z2-076 GEN
Solar/Wind Harmer
0.084
232813VAUGHN
Adder
0.375
233990AG1-397 GEN
Solar/Wind Harmer
0.035
232912OH NUG1
Adder
5.63
232913OH NUG2
Adder
5.555
233923SMA
Solar/Wind Harmer
2.96
233955AB2-172 GEN
Solar/Wind Harmer
3.185
232436AB1-176 C
Solar/Wind Harmer
0.146
233968AD2-076_GEN
Solar/Wind Harmer
4.218
970597AG2-380 GEN
Solar/Wind Harmer
2.649
971983AH1-536 GEN
Solar/Wind Harmer
4.76
233935AB2-179 C
Solar/Wind Harmer
1.589
203855AF2-088 C
Solar/Wind Harmer
0.222
205932AD2-116_GEN
Solar/Wind Harmer
0.622
205956AE1-196_GEN
Solar/Wind Harmer
0.622
205943AE1-185 GEN
Solar/Wind Harmer
0.62
960921AF2-383 GEN
Solar/Wind Harmer
0.206
960921AF2-383 GEN
Solar/Wind Harmer
1.585
940863AE2-074 GEN
Solar/Wind Harmer
1.844
203804AE2-113_GEN
Solar/Wind Harmer
4.781
23750501ELLIOTTS
Solar/Wind Helper
0.734
200033KEYS G2
50/50
10.214
200031CONE G2
50/50
8.262
200031CONE G2
50/50
7.69
20080926SITHE
50/50
0.407
20088626ARWF_N39
Solar/Wind Harmer
3.124
20303426NA_O38_P22
Solar/Wind Harmer
2.529
209137AF2-361 C
Solar/Wind Harmer
3.172
209130AF1-271A GEN
Solar/Wind Harmer
2.676
946751AF1-339 GEN
Solar/Wind Harmer
0.95
209054AE2-059 GEN
Solar/Wind Harmer
1.598
209059AE2-084 GEN
Solar/Wind Harmer
2.359
961431AF2-434 GEN
Solar/Wind Harmer
0.927
971441AH1-212 GEN
Solar/Wind Harmer
3.06
203857AF2-221 C
Solar/Wind Harmer
2.291
970123AG2-090 GEN
Solar/Wind Harmer
2.139
961541AF2-445A GEN
Solar/Wind Harmer
3.008
203940AF1-140 C
Solar/Wind Harmer
0.746
20084626FORWARD
Solar/Wind Harmer
1.167
203839AF1-321 GEN
Solar/Wind Harmer
2.951
208972BECR K09
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Harmer
2.518
209009PEIP 2
Adder
6.838
209010PEIP 1
Adder
3.098
209010PEIP 1
Adder
0.454
211065PSPA IPP
Solar/Wind Harmer
0.377
211065PSPA IPP
Solar/Wind Harmer
0.377
946071AF1-272 GEN
Solar/Wind Harmer
4.639
966111AG1-480 GEN
Solar/Wind Harmer
0.069
966111AG1-480 GEN
Solar/Wind Harmer
2.644
20465127PORT CT
Adder
3.147
20674128FR_U2-059
Solar/Wind Harmer
0.145
20634528N27_Y2-018
Solar/Wind Harmer
0.21
964851AG1-348 GEN
Solar/Wind Harmer
1.368
207471AF2-354 C
Solar/Wind Harmer
0.396
20674928WA_W3-044
Solar/Wind Harmer
0.373
20676228FRD_X1-012
Solar/Wind Harmer
0.454
20088926STNY CRK
Solar/Wind Harmer
1.63
971427AH1-205 GEN
Solar/Wind Harmer
1.966
217204WCALDSOLAR C
Solar/Wind Harmer
0.054
217086KRNY_131
Adder
6.822
217083KRNY_132
Adder
6.764
217206BARNGR HS C
Solar/Wind Harmer
0.023
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.407
217202FBANKSOLAR C
Solar/Wind Harmer
0.054
20674528F3S_W2-016
Solar/Wind Harmer
1.032
20671828STAW2-080
Solar/Wind Harmer
0.077
217081WEATEXAS C
Solar/Wind Harmer
0.062
219036LINDEN_G7
Adder
12.077
219035LINDEN_G8
Adder
11.905
972261AH1-715 GEN2
Adder
11.561
207442AE1-156 GEN
Solar/Wind Harmer
0.536
20676128MHD_W3-029
Solar/Wind Harmer
0.344
218418LINDEN_G5
Adder
12.307
218419LINDEN_G6
Adder
12.307
972260AH1-715 GEN1
Adder
9.855
20673828FLE_V3-070
Solar/Wind Harmer
0.327
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
924131AB2-057 GEN
Solar/Wind Harmer
0.722
20716928W4-060COL
Solar/Wind Harmer
0.494
20720628TIN_W1-124
Solar/Wind Harmer
0.682
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20465527S.RDG CT
Adder
2.084
20478527GLRA_Q45
Adder
0.265
219817TRENTONSOL C
Solar/Wind Harmer
0.75
20628028LAKEHURS
Adder
0.637
20714928UPF_X1-085
Solar/Wind Harmer
0.271
963391AG1-188 GEN
Solar/Wind Harmer
1.275
219114HARTZY_C
Solar/Wind Harmer
0.556
963401AG1-189 GEN
Solar/Wind Harmer
0.764
207500AE2-000G1
Solar/Wind Harmer
20.861
207497AE2-000G2
Solar/Wind Harmer
20.861
207507AE2-000G3
Solar/Wind Harmer
20.861
20636128O CRK C2
Adder
4.268
20716428NHV_W2-082
Solar/Wind Harmer
1.173
203952AE2-129 C
Solar/Wind Harmer
0.751
203946AE2-131 C
Solar/Wind Harmer
0.749
962411AG1-090 GEN
Solar/Wind Harmer
11.772
20083426SW_E13_K22
Solar/Wind Harmer
0.368
213535CROYDN11
Adder
6.633
219615MILLCREEK C
Solar/Wind Harmer
0.154
213815MOSER1-3
Adder
2.288
213815MOSER1-3
Adder
2.288
219921AF1-264
Solar/Wind Harmer
0.092
230407AD2-065 C
Solar/Wind Harmer
0.083
970313AG2-206 GEN
Solar/Wind Harmer
5.817
230422AE1-104_GEN1
Solar/Wind Harmer
21.299
230425AE1-104_GEN2
Solar/Wind Harmer
21.299
972233AH1-701 GEN
Adder
2.653
230433AD2-135 GEN
Solar/Wind Harmer
0.064
228304LOGAN
Adder
15.28
228307PCLP GT
Adder
7.628
228251CARLLS#4
Adder
0.397
216419AE2-001 C
Solar/Wind Harmer
2.402
20398826ARMNA MT
Solar/Wind Harmer
2.799
203859AF2-294 C
Solar/Wind Harmer
2.031
213587EDDYSTN3
Adder
49.629
213589EDDYSTN4
Adder
49.623
203853AF1-134 C O1
Solar/Wind Harmer
0.719
233939AC1-091 C
Solar/Wind Harmer
0.561
233970AC1-092 C
Solar/Wind Harmer
0.561
971149AH1-027 GEN
Solar/Wind Harmer
2.162
232899W1-062
Adder
6.143
232416X2-083
Adder
0.288
970545AG2-347 GEN
Solar/Wind Harmer
41.727
231940T-011
Adder
0.476
972069AH1-584 GEN
Solar/Wind Harmer
5.709
972071AH1-585 GEN
Solar/Wind Harmer
5.709
971747AH1-380 GEN
Solar/Wind Harmer
2.283
233901CHERRYDALE C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.638
232410W1-006 C
Solar/Wind Harmer
0.638
232918OH NUG7
Adder
5.592
232905CHERITON_25
Adder
1.564
232926CRISFLD1
Adder
1.251
233946AB2-136 GEN
Solar/Wind Harmer
2.543
234036AF2-325 C
Solar/Wind Harmer
0.584
234041AC1-190 GEN
Solar/Wind Harmer
5.704
233987AB2-037 GEN
Solar/Wind Harmer
7.241
233944AB2-135 GEN
Solar/Wind Harmer
3.334
232424Y1-079 C
Solar/Wind Harmer
0.358
233984AB2-036 GEN
Solar/Wind Harmer
7.922
234014AF1-036_GEN
Solar/Wind Harmer
1.722
233933AB2-153 GEN
Solar/Wind Harmer
0.716
208835TUHI V3-051
Solar/Wind Harmer
0.038
208835TUHI V3-051
Solar/Wind Harmer
0.038
972075AH1-587 GEN
Solar/Wind Harmer
20.001
972077AH1-588 GEN
Solar/Wind Harmer
23.398
972079AH1-589 GEN
Solar/Wind Harmer
19.272
970715AG2-457 GEN
Solar/Wind Harmer
7.799
205916AD1-020 GEN
Solar/Wind Harmer
1.791
944781AF1-143 GEN
Solar/Wind Harmer
2.742
238217AF1-153 C O1
Solar/Wind Harmer
0.544
23652301WDPWR_K20
Solar/Wind Helper
0.194
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.323
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.437
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
98.702
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.084
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
19.476
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.176
G-007ALTFEXP_G-007A->PJM
CMTX
36.124
CBM NorthLTFEXP_CBM-N->PJM
CBM
71.911
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for KEYSTONE-01SOBEND 500.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-002_SRT-SL


Base Case Flowgate

Area:AP/PJM
Facility Description:
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-002_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.79 %
Rating:2078.0 MVA
Rating Type:B
MVA to Mitigate:2239.81
MW Contribution:9.3
Bus #Bus NameTypeMW Contribution
200032KEYS G1
50/50
9.838
200030CONE G1
50/50
8.363
200105AA1-076 ST
50/50
6.971
20083326SEWRDB34
50/50
6.196
20079426CONEMAGH
50/50
2.01
972241AH1-705 GEN
Adder
5.792
209071AE2-133 GEN
Solar/Wind Harmer
1.612
970665AG2-430 GEN
Solar/Wind Harmer
9.444
209018SUNBIPCT
Adder
7.089
946731AF1-337 GEN
Solar/Wind Harmer
0.95
212507AE2-042_GEN
Solar/Wind Harmer
2.831
961341AF2-425 GEN
Solar/Wind Harmer
0.927
212174INGE
Adder
1.025
970125AG2-091 GEN
Solar/Wind Harmer
0.917
212266LOR1
Solar/Wind Harmer
0.12
970237AG2-161 GEN
Solar/Wind Harmer
3.216
971879AH1-460 GEN
Solar/Wind Harmer
9.935
203841AF2-001_GEN
Solar/Wind Harmer
2.951
961301AF2-421 GEN
Solar/Wind Harmer
0.886
963151AG1-164 GEN
Solar/Wind Harmer
0.886
209023WIENIPP1
Adder
9.55
209025WIENIPP3
Adder
4.767
971541AH1-268 GEN
Solar/Wind Harmer
4.975
209010PEIP 1
Adder
0.563
208909MACR G3
Adder
127.852
20465127PORT CT
Adder
2.371
20671928W4-073
Solar/Wind Harmer
0.341
207518AF1-320_GEN
Solar/Wind Harmer
2.865
207437AD2-070 GEN
Solar/Wind Harmer
0.236
971519AH1-257 GEN
Solar/Wind Harmer
1.965
966181AG1-487 GEN
Solar/Wind Harmer
2.943
20675828AU_W4-064
Solar/Wind Harmer
0.133
207439AE1-081 C O1
Solar/Wind Harmer
0.046
20674328GAR_V4-001
Solar/Wind Harmer
0.084
971419AH1-201 GEN
Solar/Wind Harmer
4.227
217208PARK ELE C
Solar/Wind Harmer
0.019
217083KRNY_132
Adder
6.808
217121ECCF
Adder
0.318
217209CENTRL HS C
Solar/Wind Harmer
0.033
218449LINSOLAR C
Solar/Wind Harmer
0.726
20676428JCR_X2-075
Solar/Wind Harmer
0.247
970679AG2-439 GEN
Solar/Wind Harmer
1.281
207528AF2-192 GEN
Solar/Wind Harmer
0.398
20673628F1S_V4-069
Solar/Wind Harmer
0.129
20675428EAM_W2-061
Solar/Wind Harmer
0.136
972275AH1-722 GEN
Adder
22.624
217213AMBOY SO C
Solar/Wind Harmer
0.09
218428ETC SOLAR C
Solar/Wind Harmer
0.026
205941AD2-115 GEN
Solar/Wind Harmer
0.726
209008PAXT IPP
Adder
1.707
20635028RRCT1&2
Adder
8.179
20635128RRCT3&4
Adder
7.895
20635828PARLN1&2
Adder
5.193
217197RE CRAN C
Solar/Wind Harmer
0.372
20742028HF_AC1-207
Solar/Wind Harmer
0.539
20467927PC_Q59Y356
Adder
0.659
200032KEYS G1
50/50
10.224
200033KEYS G2
50/50
9.821
200030CONE G1
50/50
7.621
957561AF2-050 GEN
Solar/Wind Harmer
8.479
209067AE2-060 GEN
Solar/Wind Harmer
1.64
946691AF1-333 GEN
Solar/Wind Harmer
0.95
946741AF1-338 GEN
Solar/Wind Harmer
0.95
20088826HIGHLAND
Solar/Wind Harmer
2.526
972245AH1-707 GEN
Adder
5.084
961331AF2-424 GEN
Solar/Wind Harmer
0.927
961421AF2-433 GEN
Solar/Wind Harmer
0.927
957921AF2-086 GEN
Solar/Wind Harmer
0.901
209142AF1-226 GEN
Solar/Wind Harmer
5.365
209093AE2-110 GEN
Solar/Wind Harmer
2.317
209120AE2-241 GEN
Solar/Wind Harmer
3.066
964201AG1-281 GEN
Solar/Wind Harmer
0.92
209027LOR2_Q27
Solar/Wind Harmer
4.188
209022WHFR IPP
Adder
3.006
203987AE2-118 C
Solar/Wind Harmer
3.014
964391AG1-301 GEN
Solar/Wind Harmer
0.896
970631AG2-411 GEN
Solar/Wind Harmer
9.297
203843AF2-002_GEN
Solar/Wind Harmer
1.475
963161AG1-165 GEN
Solar/Wind Harmer
0.886
209025WIENIPP3
Adder
4.671
963071AG1-156 GEN
Solar/Wind Harmer
2.432
970095AG2-074 GEN
Solar/Wind Harmer
5.519
971279AH1-102 GEN
Solar/Wind Harmer
11.69
20094526CT_V3-030
Solar/Wind Harmer
0.992
20465427SHAW CT
Adder
3.099
20466127PORT 5CT
Adder
21.011
971007AG2-625 GEN
Solar/Wind Harmer
2.002
20633028GILCT9
Adder
22.239
966181AG1-487 GEN
Solar/Wind Harmer
0.197
20674628WNG_W3-110
Solar/Wind Harmer
0.309
207510AF2-138 C
Solar/Wind Harmer
1.359
20676728BRNX1-095
Solar/Wind Harmer
0.131
217194REDH C
Solar/Wind Harmer
0.361
217169METRODIV C
Solar/Wind Harmer
0.029
217186ESSEX_G9
Adder
11.707
217211CAMDEN ST C
Solar/Wind Harmer
0.018
20673728F2S_V4-070
Solar/Wind Harmer
0.129
219249CENTRALDIV C
Solar/Wind Harmer
0.028
219908AB1-139 C
Solar/Wind Harmer
0.271
219919AE1-041 FULL
Solar/Wind Harmer
0.029
971423AH1-203 GEN
Solar/Wind Harmer
9.109
20635028RRCT1&2
Adder
8.307
20635128RRCT3&4
Adder
6.887
20635828PARLN1&2
Adder
2.352
20635928PARLN3&4
Adder
2.352
967451AG2-055 C O1
Solar/Wind Harmer
120.09
218438BLK ROCK C
Solar/Wind Harmer
0.095
219612MATRIX C
Solar/Wind Harmer
0.128
20720528MAN_W1-024
Solar/Wind Harmer
0.174
20716228APLW2-078
Solar/Wind Harmer
0.605
219918AC2-009 C
Solar/Wind Harmer
0.042
20714528FRN_Y2-051
Solar/Wind Harmer
0.199
219276PARKLANDSO C
Solar/Wind Harmer
0.312
971667AH1-334 GEN
Solar/Wind Harmer
1.836
219727YARDVSOLFA C
Solar/Wind Harmer
0.61
20636028O CRK C1
Adder
4.681
20715028HAN_X4-015
Solar/Wind Harmer
0.197
20720828JCB_W4-025
Solar/Wind Harmer
0.299
20716028EGP_W2-019
Solar/Wind Harmer
0.306
972221AH1-695 GEN
Adder
110.049
959561AF2-247 GEN
Solar/Wind Harmer
0.319
219610FLORENCE C
Solar/Wind Harmer
0.898
219348LDSOLAR C
Solar/Wind Harmer
0.388
219221BRL12CT1
Adder
5.788
219223BRL12CT3
Adder
5.788
219906AC1-017 C
Solar/Wind Harmer
0.144
213815MOSER1-3
Adder
2.288
219236SOUTHERNHQ C
Solar/Wind Harmer
0.043
219291REEVESSOUT C
Solar/Wind Harmer
0.038
219912AD2-042 GEN
Solar/Wind Harmer
0.509
219766PARADISE C
Solar/Wind Harmer
0.201
219623KINSLEYBEA C
Solar/Wind Harmer
0.272
213560DLW11-12
Adder
1.734
228729W2-030 C
Solar/Wind Harmer
0.366
238215AE2-248 C
Solar/Wind Harmer
1.939
970511AG2-327 GEN
Solar/Wind Harmer
1.212
230415AB2-049 C
Solar/Wind Harmer
0.12
228304LOGAN
Adder
13.743
230430AE1-229_GEN
Solar/Wind Harmer
5.544
971553AH1-274 GEN
Solar/Wind Harmer
1.523
213958STHWK5-6
Adder
1.718
228711V2-041C
Solar/Wind Harmer
0.377
228202CUMB CT
Adder
10.369
959471AF2-238 GEN
Solar/Wind Harmer
0.727
970337AG2-221 GEN
Solar/Wind Harmer
2.406
213497CHSTR7-9
Adder
1.697
20326126BLOSSBCT
Adder
2.714
970643AG2-418 GEN
Solar/Wind Harmer
1.099
20335026MILZ1-092
Adder
2.683
944411AF1-106 GEN
Solar/Wind Harmer
2.472
972251AH1-710 GEN
Adder
29.207
233971AC1-093 C
Solar/Wind Harmer
0.501
970695AG2-447 GEN
Solar/Wind Harmer
2.29
233952AC2-187 GEN
Solar/Wind Harmer
0.718
972133AH1-634 GEN
Solar/Wind Harmer
6.322
972073AH1-586 GEN
Solar/Wind Harmer
5.974
233990AG1-397 GEN
Solar/Wind Harmer
0.731
232406W1-004 FULL
Solar/Wind Harmer
0.638
234015AF2-250 C
Solar/Wind Harmer
0.077
232914OH NUG3
Adder
5.63
232916OH NUG5
Adder
5.63
232921TASLEY2G
Adder
3.29
233900O-025 C
Adder
0.751
233996TM1833_GEN
Solar/Wind Harmer
0.807
233997TMININ_4.2
Solar/Wind Harmer
0.807
233940AF2-379 C
Solar/Wind Harmer
0.119
233994AC2-023 GEN
Solar/Wind Harmer
1.713
960671AF2-358 GEN
Solar/Wind Harmer
11.411
232907VN8
Adder
15.629
232417X3-008 C
Solar/Wind Harmer
1.274
233982AB2-133 GEN
Solar/Wind Harmer
3.1
233918AB1-142 GEN
Solar/Wind Harmer
0.63
238206AE2-263_GEN
Solar/Wind Harmer
2.701
972169AH1-667 GEN
Solar/Wind Harmer
2.031
203954AE2-126 C
Solar/Wind Harmer
0.634
966131AG1-482 GEN
Solar/Wind Harmer
2.083
970713AG2-456 GEN
Solar/Wind Harmer
7.799
971705AH1-358 GEN
Solar/Wind Harmer
2.267
200104AA1-076 CT2
50/50
6.15
200103AA1-076 CT1
50/50
6.096
20083726HOMER C1
Adder
119.115
203961AE2-224 GEN
Solar/Wind Harmer
5.136
959431AF2-234 GEN
Solar/Wind Harmer
1.903
964051AG1-259 GEN
Solar/Wind Harmer
1.276
964061AG1-260 GEN
Solar/Wind Harmer
1.276
959421AF2-233 GEN
Solar/Wind Harmer
0.952
20092526R32
Solar/Wind Harmer
2.707
209045AE2-271 GEN
Solar/Wind Harmer
15.641
20091526CHSTN_FL
Solar/Wind Harmer
1.307
941231AE2-117 GEN
Solar/Wind Harmer
0.891
203850AG1-041 C
Solar/Wind Harmer
1.767
209026WIENIPP4
Adder
4.719
203844AF2-092 C
Solar/Wind Harmer
1.755
961261AF2-417 GEN
Solar/Wind Harmer
0.858
209116AE2-175 GEN
Solar/Wind Harmer
3.375
966421AG1-511 GEN
Solar/Wind Harmer
6.823
20462827N BANGR8
Adder
0.566
20675128HRM_W1-127
Solar/Wind Harmer
0.134
207408W3-077 C
Solar/Wind Harmer
0.397
20675728RH_W2-091
Solar/Wind Harmer
0.268
207484AF2-139 C O1
Solar/Wind Harmer
0.396
971009AG2-626 GEN
Solar/Wind Harmer
1.277
20675928HOL_W4-097
Solar/Wind Harmer
0.102
20715228NPK_W1-113
Solar/Wind Harmer
0.295
207454AA2-184 E
Solar/Wind Harmer
0.685
20465527S.RDG CT
Adder
2.154
219680HOPEWELLV C1
Solar/Wind Harmer
0.052
200917MEHOOPANY_G
Solar/Wind Harmer
4.452
20714828MDF_W3-079
Solar/Wind Harmer
0.207
963711AG1-223 GEN
Solar/Wind Harmer
1
207445AB1-138_GEN
Solar/Wind Harmer
0.388
20628028LAKEHURS
Adder
1.26
970899AG2-561 GEN
Solar/Wind Harmer
2.52
207487AE2-000G4
Solar/Wind Harmer
20.861
207522AF2-254 C
Solar/Wind Harmer
0.947
20720728JCB_W1-129
Solar/Wind Harmer
0.197
972271AH1-720 GEN
Adder
8.193
213611FALLS1-3
Adder
2.318
214194N WALES4
Adder
0.558
965131AG1-378 GEN
Solar/Wind Harmer
2.478
20328326MANOR_T86
Adder
0.176
941421AE2-139 GEN
Solar/Wind Harmer
3.761
203818AF1-086 GEN
Solar/Wind Harmer
3.159
219304NAMERICA C
Solar/Wind Harmer
0.201
219222BRL12CT2
Adder
5.788
219287REEVESEAST C
Solar/Wind Harmer
0.863
219686LUMSOLAR_N C
Solar/Wind Harmer
0.13
219907AC1-030 C
Solar/Wind Harmer
0.089
218660EHAMPSOLAR C
Solar/Wind Harmer
0.112
219904AC1-010 C
Solar/Wind Harmer
0.241
219258KINSLEYDEP C
Solar/Wind Harmer
0.206
213560DLW11-12
Adder
1.734
228728W1-130C
Solar/Wind Harmer
0.42
970335AG2-220 GEN
Solar/Wind Harmer
3.755
971127AH1-005 GEN
Solar/Wind Harmer
2.422
230434AG1-499 GEN
Solar/Wind Harmer
0.367
230511AF1-262
Solar/Wind Harmer
0.115
228732V1-021 C
Adder
0.119
20335126GROZ1-110
Adder
2.833
20335226CANZ2-011
Adder
2.754
228351V2-046C
Solar/Wind Harmer
1.269
970997AG2-616 GEN
Solar/Wind Harmer
6.037
945431AF1-208 GEN
Solar/Wind Harmer
5.431
213958STHWK5-6
Adder
1.718
228206SHRMN CT
Adder
10.413
213497CHSTR7-9
Adder
1.697
213497CHSTR7-9
Adder
1.697
960051AF2-296 GEN
Solar/Wind Harmer
2.38
970643AG2-418 GEN
Solar/Wind Harmer
2.362
944411AF1-106 GEN
Solar/Wind Harmer
0.266
205967AE2-211_GEN
Solar/Wind Harmer
6.57
231917EM10
Adder
1.516
231918WEST 1
Adder
2.152
233972AC1-094 C
Solar/Wind Harmer
0.424
232901NORTHST
Adder
5.316
232900DEMECSMY
Adder
5.892
972177AH1-672 GEN
Solar/Wind Harmer
8.57
233954AC2-188 GEN
Solar/Wind Harmer
0.718
233950AC2-186 GEN
Solar/Wind Harmer
0.359
232434Z2-077 GEN
Solar/Wind Harmer
0.16
232910NRG_G1
Adder
5.506
232404W1-003 C
Solar/Wind Harmer
0.638
232917OH NUG6
Adder
5.605
232915OH NUG4
Adder
5.592
971195AH1-057 GEN
Solar/Wind Harmer
0.698
233998TM1NIN_3.36
Solar/Wind Harmer
0.807
232428Y3-058 C
Solar/Wind Harmer
0.532
965821AG1-450 GEN
Solar/Wind Harmer
3.317
232919VN10
Adder
1.788
232426Y1-080 FULL
Solar/Wind Harmer
0.122
970277AG2-181 GEN
Solar/Wind Harmer
3.195
233964AF2-378 GEN
Solar/Wind Harmer
0.081
232422X3-066 FULL
Solar/Wind Harmer
0.159
234012AE2-112_GEN
Solar/Wind Harmer
1.463
233930AB2-032 GEN
Solar/Wind Harmer
0.531
233915AB1-141 GEN
Solar/Wind Harmer
0.63
238202AE2-262_GEN
Solar/Wind Harmer
2.898
971627AH1-313 GEN
Solar/Wind Harmer
11.361
203854AF2-039 C
Solar/Wind Harmer
0.461
20334926Z1-069 C
Solar/Wind Harmer
2.308
966131AG1-482 GEN
Solar/Wind Harmer
0.094
205975AE2-345_GEN
Solar/Wind Harmer
6.986
971703AH1-357 GEN
Solar/Wind Harmer
1.95
20674828DL_W4-046
Solar/Wind Harmer
0.5
207511W3-106 GEN
Solar/Wind Harmer
0.503
20676328BVR_Y1-020
Solar/Wind Harmer
0.252
207530AG1-191 GEN
Solar/Wind Harmer
1.052
20083926HOMER C3
Adder
95.203
20083826HOMER C2
Adder
89.93
20090526Q36
Solar/Wind Harmer
2.07
203993AD2-133_GEN1
Solar/Wind Harmer
2.07
966261AG1-495 GEN
Solar/Wind Harmer
1.343
217167KRNY_14
Adder
6.808
217086KRNY_131
Adder
6.75
217147KRNY_1212
Adder
6.475
217147KRNY_1212
Adder
6.36
217146KRNY_1234
Adder
6.345
217146KRNY_1234
Adder
6.302
218404KENILWRTH C
Adder
0.952
20390726Y2-042
Adder
3.066
218524CNTRALGAS1 C
Solar/Wind Harmer
0.263
218526CNTRALGAS2 C
Solar/Wind Harmer
0.262
20675528CPH_W2-050
Solar/Wind Harmer
0.332
218455CINNBAY_CGEN
Adder
1.275
20635928PARLN3&4
Adder
5.193
20720428HOL_W1-112
Solar/Wind Harmer
0.239
971521AH1-258 GEN
Solar/Wind Harmer
1.866
20486527WR_V4-052
Adder
0.84
20714428HOW_X1-037
Solar/Wind Harmer
0.844
20714328BYD_X4-031
Solar/Wind Harmer
0.193
20334726NME_Y1-047
Adder
2.991
219620RIDERU C
Solar/Wind Harmer
0.038
207459AE1-142 C O1
Solar/Wind Harmer
0.705
971189AH1-054 GEN
Solar/Wind Harmer
0.785
970025AG2-016 GEN
Solar/Wind Harmer
1.884
203926AA2-133 GEN
Adder
2.948
208862AG1-362 C
Solar/Wind Harmer
0.628
20715728PEM_W1-119
Solar/Wind Harmer
0.353
20715828PEM_W1-120
Solar/Wind Harmer
0.353
20717128DIX_Z2-102
Solar/Wind Harmer
0.872
214067T20SOLAR
Solar/Wind Harmer
0.166
213611FALLS1-3
Adder
2.318
213611FALLS1-3
Adder
2.318
965121AG1-377 GEN
Solar/Wind Harmer
2.478
219607WPEMNERT C
Solar/Wind Harmer
0.272
219224BRL12CT4
Adder
5.788
219688LUMSOLAR_S C
Solar/Wind Harmer
0.13
219272CLEANLIGHT C
Solar/Wind Harmer
0.117
219914AD2-027 C
Solar/Wind Harmer
0.384
213561DLWR9-10
Adder
2.268
213561DLWR9-10
Adder
1.734
227927V4-067C
Solar/Wind Harmer
0.126
228754AB1-001 C
Solar/Wind Harmer
0.088
219137THOSOLAR C
Solar/Wind Harmer
0.768
971535AH1-265 GEN
Solar/Wind Harmer
2.692
971011AG2-627 GEN
Solar/Wind Harmer
4.834
964001AG1-254 GEN
Solar/Wind Harmer
1.28
972141AH1-641 GEN
Solar/Wind Harmer
1.811
228260V4-054C
Solar/Wind Harmer
0.646
228309CCLP NUG
Adder
16.257
228309CCLP NUG
Adder
15.464
213957STHWK3-4
Adder
1.718
213957STHWK3-4
Adder
1.718
213942SCHUYLKILL
Adder
2.245
213942SCHUYLKILL
Adder
1.717
970453AG2-297 GEN
Solar/Wind Harmer
1.729
970555AG2-356 GEN
Solar/Wind Harmer
2.406
231919CHRIST1
Adder
2.835
231920CHRIST2
Adder
2.772
205951AE1-129_GEN
Solar/Wind Harmer
9.022
233973AC2-185 C
Solar/Wind Harmer
2.31
234033AF1-007_GEN
Solar/Wind Harmer
14.911
232904IR4
Adder
51.558
232920IR10
Adder
2.015
232432Z2-076 GEN
Solar/Wind Harmer
0.084
232813VAUGHN
Adder
0.375
233990AG1-397 GEN
Solar/Wind Harmer
0.035
232912OH NUG1
Adder
5.63
232913OH NUG2
Adder
5.555
233923SMA
Solar/Wind Harmer
2.96
233955AB2-172 GEN
Solar/Wind Harmer
3.185
232436AB1-176 C
Solar/Wind Harmer
0.146
233968AD2-076_GEN
Solar/Wind Harmer
4.218
971707AH1-359 GEN
Solar/Wind Harmer
1.95
208923BUSO V4-027
Solar/Wind Harmer
0.256
208856AE1-226 GEN
Solar/Wind Harmer
1.812
20089126CSLMN_L13
Solar/Wind Harmer
0.8
20089026BF_G21_K23
Solar/Wind Harmer
0.633
237048AF1-022 C
Solar/Wind Helper
0.21
237043AE2-125 C
Solar/Wind Helper
0.204
964991AG1-363 GEN
Solar/Wind Helper
3.553
235058AG1-386 C
Solar/Wind Helper
0.395
200033KEYS G2
50/50
10.214
200031CONE G2
50/50
8.262
200031CONE G2
50/50
7.69
20080926SITHE
50/50
0.407
20088626ARWF_N39
Solar/Wind Harmer
3.124
20303426NA_O38_P22
Solar/Wind Harmer
2.529
209137AF2-361 C
Solar/Wind Harmer
3.172
209130AF1-271A GEN
Solar/Wind Harmer
2.676
946751AF1-339 GEN
Solar/Wind Harmer
0.95
209054AE2-059 GEN
Solar/Wind Harmer
1.598
209059AE2-084 GEN
Solar/Wind Harmer
2.359
961431AF2-434 GEN
Solar/Wind Harmer
0.927
971441AH1-212 GEN
Solar/Wind Harmer
3.06
203857AF2-221 C
Solar/Wind Harmer
2.291
970123AG2-090 GEN
Solar/Wind Harmer
2.139
961541AF2-445A GEN
Solar/Wind Harmer
3.008
203940AF1-140 C
Solar/Wind Harmer
0.746
20084626FORWARD
Solar/Wind Harmer
1.167
203839AF1-321 GEN
Solar/Wind Harmer
2.951
208972BECR K09
Solar/Wind Harmer
0.941
209029WAYMART-WD
Solar/Wind Harmer
2.518
209009PEIP 2
Adder
6.838
209010PEIP 1
Adder
3.098
209010PEIP 1
Adder
0.454
211065PSPA IPP
Solar/Wind Harmer
0.377
211065PSPA IPP
Solar/Wind Harmer
0.377
946071AF1-272 GEN
Solar/Wind Harmer
4.639
966111AG1-480 GEN
Solar/Wind Harmer
0.069
966111AG1-480 GEN
Solar/Wind Harmer
2.644
20465127PORT CT
Adder
3.147
20674128FR_U2-059
Solar/Wind Harmer
0.145
20634528N27_Y2-018
Solar/Wind Harmer
0.21
964851AG1-348 GEN
Solar/Wind Harmer
1.368
207471AF2-354 C
Solar/Wind Harmer
0.396
20674928WA_W3-044
Solar/Wind Harmer
0.373
20676228FRD_X1-012
Solar/Wind Harmer
0.454
20088926STNY CRK
Solar/Wind Harmer
1.63
971427AH1-205 GEN
Solar/Wind Harmer
1.966
217204WCALDSOLAR C
Solar/Wind Harmer
0.054
217086KRNY_131
Adder
6.822
217083KRNY_132
Adder
6.764
217206BARNGR HS C
Solar/Wind Harmer
0.023
217201HACKENSOLA C
Solar/Wind Harmer
0.054
972237AH1-703 GEN
Adder
7.407
217202FBANKSOLAR C
Solar/Wind Harmer
0.054
20674528F3S_W2-016
Solar/Wind Harmer
1.032
20671828STAW2-080
Solar/Wind Harmer
0.077
217081WEATEXAS C
Solar/Wind Harmer
0.062
219036LINDEN_G7
Adder
12.077
219035LINDEN_G8
Adder
11.905
972261AH1-715 GEN2
Adder
11.561
207442AE1-156 GEN
Solar/Wind Harmer
0.536
20676128MHD_W3-029
Solar/Wind Harmer
0.344
218418LINDEN_G5
Adder
12.307
218419LINDEN_G6
Adder
12.307
972260AH1-715 GEN1
Adder
9.855
20673828FLE_V3-070
Solar/Wind Harmer
0.327
218440SUMMTASSOC C
Solar/Wind Harmer
0.091
924131AB2-057 GEN
Solar/Wind Harmer
0.722
20716928W4-060COL
Solar/Wind Harmer
0.494
20720628TIN_W1-124
Solar/Wind Harmer
0.682
20641628MLH_W1-032
Solar/Wind Harmer
0.201
20465527S.RDG CT
Adder
2.084
20478527GLRA_Q45
Adder
0.265
219817TRENTONSOL C
Solar/Wind Harmer
0.75
20628028LAKEHURS
Adder
0.637
20714928UPF_X1-085
Solar/Wind Harmer
0.271
963391AG1-188 GEN
Solar/Wind Harmer
1.275
219114HARTZY_C
Solar/Wind Harmer
0.556
963401AG1-189 GEN
Solar/Wind Harmer
0.764
207500AE2-000G1
Solar/Wind Harmer
20.861
207497AE2-000G2
Solar/Wind Harmer
20.861
207507AE2-000G3
Solar/Wind Harmer
20.861
20636128O CRK C2
Adder
4.268
20716428NHV_W2-082
Solar/Wind Harmer
1.173
203952AE2-129 C
Solar/Wind Harmer
0.751
203946AE2-131 C
Solar/Wind Harmer
0.749
962411AG1-090 GEN
Solar/Wind Harmer
11.772
20083426SW_E13_K22
Solar/Wind Harmer
0.368
971709AH1-360 GEN
Solar/Wind Harmer
2.267
205917AD1-020 ES
Solar/Wind Harmer
0.385
20089226LOOKOUT
Solar/Wind Harmer
0.779
237046AF1-021 C
Solar/Wind Helper
0.659
970597AG2-380 GEN
Solar/Wind Harmer
2.649
971983AH1-536 GEN
Solar/Wind Harmer
4.76
233935AB2-179 C
Solar/Wind Harmer
1.589
203855AF2-088 C
Solar/Wind Harmer
0.222
205932AD2-116_GEN
Solar/Wind Harmer
0.622
205956AE1-196_GEN
Solar/Wind Harmer
0.622
205943AE1-185 GEN
Solar/Wind Harmer
0.62
960921AF2-383 GEN
Solar/Wind Harmer
0.206
960921AF2-383 GEN
Solar/Wind Harmer
1.585
940863AE2-074 GEN
Solar/Wind Harmer
1.844
203804AE2-113_GEN
Solar/Wind Harmer
4.781
23750501ELLIOTTS
Solar/Wind Helper
0.734
213535CROYDN11
Adder
6.633
219615MILLCREEK C
Solar/Wind Harmer
0.154
213815MOSER1-3
Adder
2.288
213815MOSER1-3
Adder
2.288
219921AF1-264
Solar/Wind Harmer
0.092
230407AD2-065 C
Solar/Wind Harmer
0.083
970313AG2-206 GEN
Solar/Wind Harmer
5.817
230422AE1-104_GEN1
Solar/Wind Harmer
21.299
230425AE1-104_GEN2
Solar/Wind Harmer
21.299
972233AH1-701 GEN
Adder
2.653
230433AD2-135 GEN
Solar/Wind Harmer
0.064
228304LOGAN
Adder
15.28
228307PCLP GT
Adder
7.628
228251CARLLS#4
Adder
0.397
216419AE2-001 C
Solar/Wind Harmer
2.402
20398826ARMNA MT
Solar/Wind Harmer
2.799
203859AF2-294 C
Solar/Wind Harmer
2.031
213587EDDYSTN3
Adder
49.629
213589EDDYSTN4
Adder
49.623
203853AF1-134 C O1
Solar/Wind Harmer
0.719
233939AC1-091 C
Solar/Wind Harmer
0.561
233970AC1-092 C
Solar/Wind Harmer
0.561
971149AH1-027 GEN
Solar/Wind Harmer
2.162
232899W1-062
Adder
6.143
232416X2-083
Adder
0.288
970545AG2-347 GEN
Solar/Wind Harmer
41.727
231940T-011
Adder
0.476
972069AH1-584 GEN
Solar/Wind Harmer
5.709
972071AH1-585 GEN
Solar/Wind Harmer
5.709
971747AH1-380 GEN
Solar/Wind Harmer
2.283
233901CHERRYDALE C
Solar/Wind Harmer
0.718
232408W1-005 C
Solar/Wind Harmer
0.638
232410W1-006 C
Solar/Wind Harmer
0.638
232918OH NUG7
Adder
5.592
232905CHERITON_25
Adder
1.564
232926CRISFLD1
Adder
1.251
233946AB2-136 GEN
Solar/Wind Harmer
2.543
234036AF2-325 C
Solar/Wind Harmer
0.584
234041AC1-190 GEN
Solar/Wind Harmer
5.704
233987AB2-037 GEN
Solar/Wind Harmer
7.241
233944AB2-135 GEN
Solar/Wind Harmer
3.334
232424Y1-079 C
Solar/Wind Harmer
0.358
233984AB2-036 GEN
Solar/Wind Harmer
7.922
234014AF1-036_GEN
Solar/Wind Harmer
1.722
233933AB2-153 GEN
Solar/Wind Harmer
0.716
208835TUHI V3-051
Solar/Wind Harmer
0.038
208835TUHI V3-051
Solar/Wind Harmer
0.038
972075AH1-587 GEN
Solar/Wind Harmer
20.001
972077AH1-588 GEN
Solar/Wind Harmer
23.398
972079AH1-589 GEN
Solar/Wind Harmer
19.272
970715AG2-457 GEN
Solar/Wind Harmer
7.799
205916AD1-020 GEN
Solar/Wind Harmer
1.791
944781AF1-143 GEN
Solar/Wind Harmer
2.742
238217AF1-153 C O1
Solar/Wind Harmer
0.544
23652301WDPWR_K20
Solar/Wind Helper
0.194
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.323
BlueGrassPJM->LTFIMP_BlueG
CLTF
13.437
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
VTFLTFEXP_VFT->PJM
CMTX
98.702
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.084
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
19.476
HAMLETPJM->LTFIMP_HAMLET
CLTF
3.176
G-007ALTFEXP_G-007A->PJM
CMTX
36.124
CBM NorthLTFEXP_CBM-N->PJM
CBM
71.911
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'PN_P2-3_PN-345-997-DRT-031_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200595 TO BUS 200598 CKT 2          /*26WAYNE      345.0 - 26WAYNE      115.0
 DISCONNECT BRANCH FROM BUS 200595 TO BUS 200826 CKT 1          /*26WAYNE      345.0 - 26HANDSMLK   345.0
 SET POSTCONTRATING 1552 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W     345.0 - 26WAYNE      345.0
 SET PRECONTRATING 1269 BRANCH FROM BUS 200599 TO BUS 200595 CKT 1 /*26ERIE W     345.0 - 26WAYNE      345.0
END
CONTINGENCY 'AP_P2-3_MP-138-150_SRT-A'
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235305 CKT 1   /*01ALBRIG     138.0 - 01 106 J     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235320 CKT 1   /*01ALBRIG     138.0 - 01DENVER     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235402 CKT 1   /*01ALBRIG     138.0 - 01SNOW T     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235469 CKT 1   /*01ALBRIG     138.0 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 238184 CKT 1   /*01ALBRIG     138.0 - AF2-356 TAP  138.0
 DISCONNECT BRANCH FROM BUS 235297 TO BUS 235305 CKT 1   /*01HAZELT     138.0 - 01 106 J     138.0
 DISCONNECT BRANCH FROM BUS 238189 TO BUS 235305 CKT 1   /*AE1-106 TAP  138.0 - 01 106 J     138.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT45_SRT-SL'
 OPEN BRANCH FROM BUS 235116 TO BUS 235118 CKT 1                /*01YUKON      500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AP_P2-3_WP-138-338_SRT-A'
 DISCONNECT BRANCH FROM BUS 235241 TO BUS 235253 CKT 1   /*01SALTSB     138.0 - 01SOCIAL     138.0
 DISCONNECT BRANCH FROM BUS 235241 TO BUS 235262 CKT 1   /*01SALTSB     138.0 - 01VANDRG     138.0
 DISCONNECT BRANCH FROM BUS 235794 TO BUS 235241 CKT 2   /*01SALTSBRG    25.0 - 01SALTSB     138.0
END
CONTINGENCY 'AP_P2-3_WP-138-18201_SRT-A'
 DISCONNECT BRANCH FROM BUS 235181 TO BUS 235256 CKT 1    /*01FEDLST     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235190 TO BUS 235256 CKT 1    /*01HARWCK     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235195 TO BUS 235256 CKT 1    /*01HUNTDN     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235078 CKT ZB   /*01SPGDL      138.0 - 01SPGDL-2    138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235222 CKT 1    /*01SPGDL      138.0 - 01MURRYC     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235613 CKT 1    /*01SPGDL      138.0 - 01SPRGD4      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235614 CKT 1    /*01SPGDL      138.0 - 01SPRGD5      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254042 CKT 1    /*01SPGDL      138.0 - 15PLUM       138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254064 CKT 1    /*01SPGDL      138.0 - 15CHESWK     138.0
 OPEN BUS 235613                                          /*01SPRGD4      16.5
 OPEN BUS 235614                                          /*01SPRGD5      16.5
END
CONTINGENCY 'AP_P2-3_WP-138-182_SRT-A'
 DISCONNECT BRANCH FROM BUS 235181 TO BUS 235256 CKT 1    /*01FEDLST     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235181 TO BUS 235767 CKT 1    /*01FEDLST     138.0 - 01FEDERL S    25.0
 DISCONNECT BRANCH FROM BUS 235190 TO BUS 235256 CKT 1    /*01HARWCK     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235195 TO BUS 235256 CKT 1    /*01HUNTDN     138.0 - 01SPGDL      138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235078 CKT ZB   /*01SPGDL      138.0 - 01SPGDL-2    138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235222 CKT 1    /*01SPGDL      138.0 - 01MURRYC     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235613 CKT 1    /*01SPGDL      138.0 - 01SPRGD4      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235614 CKT 1    /*01SPGDL      138.0 - 01SPRGD5      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254042 CKT 1    /*01SPGDL      138.0 - 15PLUM       138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254064 CKT 1    /*01SPGDL      138.0 - 15CHESWK     138.0
END
CONTINGENCY 'AP_P2-3_WP-138-181T_SRT-A'
 OPEN BRANCH FROM BUS 235256 TO BUS 235181 CKT 1   /*01SPGDL      138.0 - 01FEDLST     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 235190 CKT 1   /*01SPGDL      138.0 - 01HARWCK     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 235195 CKT 1   /*01SPGDL      138.0 - 01HUNTDN     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 235222 CKT 1   /*01SPGDL      138.0 - 01MURRYC     138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 254042 CKT 1   /*01SPGDL      138.0 - 15PLUM       138.0
 OPEN BRANCH FROM BUS 235256 TO BUS 254064 CKT 1   /*01SPGDL      138.0 - 15CHESWK     138.0
 OPEN BUS 235613                                   /*01SPRGD4      16.5
 OPEN BUS 235614                                   /*01SPRGD5      16.5
END
CONTINGENCY 'AP_P2-2_WP-138-0582-1_SRT-A'
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235181 CKT 1   /*01SPGDL      138.0 - 01FEDLST     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235190 CKT 1   /*01SPGDL      138.0 - 01HARWCK     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235195 CKT 1   /*01SPGDL      138.0 - 01HUNTDN     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235222 CKT 1   /*01SPGDL      138.0 - 01MURRYC     138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235613 CKT 1   /*01SPGDL      138.0 - 01SPRGD4      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 235614 CKT 1   /*01SPGDL      138.0 - 01SPRGD5      16.5
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254042 CKT 1   /*01SPGDL      138.0 - 15PLUM       138.0
 DISCONNECT BRANCH FROM BUS 235256 TO BUS 254064 CKT 1   /*01SPGDL      138.0 - 15CHESWK     138.0
 DISCONNECT BUS 235613                                   /*01SPRGD4      16.5
 DISCONNECT BUS 235614                                   /*01SPRGD5      16.5
END
CONTINGENCY 'PN_P2-2_PN-500-001T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'AP_P7-1_WPP-138-050_SRT-A'
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235137 CKT 1    /*01BRACKENRDG 138.0 - 01BRACKENR J 138.0
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235743 CKT 1    /*01BRACKENRDG 138.0 - 01BRACKENRID  25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4E   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4W   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235825 CKT 1    /*01AL 4       138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235134 TO BUS 235139 CKT 1    /*01AL&D6      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235202 CKT 1    /*01BRACKENR J 138.0 - 01KISKIV     138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235245 CKT 1    /*01BRACKENR J 138.0 - 01SHFCRN     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1    /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1    /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235204 CKT 1    /*01AL&D6T     138.0 - 01KITTAN     138.0
END
CONTINGENCY 'AP_P2-2_MP-138-100_SRT-A'
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235469 CKT 1   /*01ALBRIG     138.0 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 235469 TO BUS 235470 CKT 1   /*01GARRET     138.0 - 01GARRET     115.0
 DISCONNECT BRANCH FROM BUS 237410 TO BUS 235469 CKT 1   /*01GARRETT     34.5 - 01GARRET     138.0
 DISCONNECT BRANCH FROM BUS 970994 TO BUS 235469 CKT 1   /*AG2-615 TP   138.0 - 01GARRET     138.0
END
CONTINGENCY 'PN_P2-2_PN-115-001B_SRT-A'
 DISCONNECT BRANCH FROM BUS 200746 TO BUS 200856 CKT 1   /*26ROCKWOOD   115.0 - 26LICK RUN   115.0
 DISCONNECT BRANCH FROM BUS 200746 TO BUS 202650 CKT 1   /*26ROCKWOOD   115.0 - 26HIGHPOINT  115.0
END
CONTINGENCY 'AP_P1-2_WP-500-008_SRT-A'
 DISCONNECT BRANCH FROM BUS 235116 TO BUS 235118 CKT 1   /*01YUKON      500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-2_PN-115-021_SRT-A'
 DISCONNECT BUS 200718   /*26TIMBLIN    115.0
END
CONTINGENCY 'AP_P1-2_WP-138-056_SRT-A'
 DISCONNECT BRANCH FROM BUS 235241 TO BUS 235794 CKT 2   /*01SALTSB     138.0 - 01SALTSBRG    25.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235241 CKT 1   /*01SOCIAL     138.0 - 01SALTSB     138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-051A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1   /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235131 TO BUS 235137 CKT 1   /*01BRACKENRDG 138.0 - 01BRACKENR J 138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235202 CKT 1   /*01BRACKENR J 138.0 - 01KISKIV     138.0
 DISCONNECT BRANCH FROM BUS 235137 TO BUS 235245 CKT 1   /*01BRACKENR J 138.0 - 01SHFCRN     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1   /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1   /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235240 TO BUS 235282 CKT 1   /*01COLMBGPN   138.0 - 01GAR RN     138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-C_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-B_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200767 CKT 1   /*26SHELOCTA   230.0 - 26HOMER CT   230.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'AP_P2-3_PE-500-014_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235103 TO BUS 964990 CKT 1          /*01BLACKO     500.0 - AG1-363 TP   500.0
 REDUCE BUS 235103 SHUNT BY 50 PERCENT                          /*01BLACKO     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235101 TO BUS 235103 CKT 1 /*01BEDNGT     500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT19_SRT-SL'
 OPEN BRANCH FROM BUS 235108 TO BUS 964990 CKT 1                /*01HATFLD     500.0 - AG1-363 TP   500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235774 CKT 1 /*01HATFLD     500.0 - 01RONCO      500.0
END
CONTINGENCY 'AP_P7-1_MP-138-018_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235338 TO BUS 235391 CKT 1          /*01GRAFTN     138.0 - 01PRNTY      138.0
 DISCONNECT BRANCH FROM BUS 235356 TO BUS 235391 CKT 1          /*01KINGWD     138.0 - 01PRNTY      138.0
 SET POSTCONTRATING 459 BRANCH FROM BUS 235112 TO BUS 235391 CKT 3 /*01PRNTY      500.0 - 01PRNTY      138.0
 SET POSTCONTRATING 459 BRANCH FROM BUS 235112 TO BUS 235391 CKT 4 /*01PRNTY      500.0 - 01PRNTY      138.0
 SET PRECONTRATING 421 BRANCH FROM BUS 235112 TO BUS 235391 CKT 4 /*01PRNTY      500.0 - 01PRNTY      138.0
 SET PRECONTRATING 459 BRANCH FROM BUS 235112 TO BUS 235391 CKT 3 /*01PRNTY      500.0 - 01PRNTY      138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-209_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200769 TO BUS 202641 CKT S /*26HOMER CT   230.0 - 26HOMER CY   345.0 - 26HOMERCITYS  23.0
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200795 CKT 1          /*26HOMER CT   230.0 - 26SHELOCTA   230.0
END
CONTINGENCY 'AP_P2-2_MP-138-001_SRT-A'
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235304 CKT 1   /*01ALBRIG     138.0 - 01BRANDN     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235356 CKT 1   /*01ALBRIG     138.0 - 01KINGWD     138.0
 DISCONNECT BRANCH FROM BUS 235120 TO BUS 235398 CKT 1   /*01ALBRIG     138.0 - 01RUTHBL     138.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT16_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235108 CKT 1                /*AB1-106 POI  500.0 - 01HATFLD     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'PN_P2-2_PN-115-073_SRT-A'
 DISCONNECT BRANCH FROM BUS 200501 TO BUS 200542 CKT 2   /*26BDFORD N   115.0 - 26BDFRD N2    23.0
 DISCONNECT BRANCH FROM BUS 200501 TO BUS 200884 CKT 1   /*26BDFORD N   115.0 - 26NEW BALT   115.0
END
CONTINGENCY 'AP_P2-2_WP-138-033T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 200763 CKT 1   /*01SOCIAL     138.0 - 26BLAIRSVL   138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235241 CKT 1   /*01SOCIAL     138.0 - 01SALTSB     138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235596 CKT 1   /*01SOCIAL     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235973 CKT 2   /*01SOCIAL     138.0 - 01SOCIAL H    25.0
 DISCONNECT BUS 235253                                   /*01SOCIAL     138.0
END
CONTINGENCY 'AP_P7-1_MP-138-056_SRT-A-1'
 DISCONNECT BRANCH FROM BUS 235122 TO BUS 235802 CKT 1   /*01LKLYNN     138.0 - 01CHEATL     138.0
 DISCONNECT BRANCH FROM BUS 235122 TO BUS 238189 CKT 1   /*01LKLYNN     138.0 - AE1-106 TAP  138.0
 DISCONNECT BRANCH FROM BUS 235802 TO BUS 237299 CKT 4   /*01CHEATL     138.0 - 01CHEAT LK    66.0
 REMOVE LOAD 2 FROM BUS 235802                           /*01CHEATL     138.0
END
CONTINGENCY 'PN_P2-3_PN-230-0201A-20_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200795 TO BUS 200810 CKT 1          /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0252-A_SRT-A'
 OPEN BRANCH FROM BUS 200795 TO BUS 200739 CKT 2   /*26SHELOCTA   230.0 - 26SHELOCTA   115.0
 OPEN BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0183-208_SRT-A'
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200768 CKT 1   /*26HOMER CT   230.0 - 26QUEMAHON   230.0
 DISCONNECT BRANCH FROM BUS 200768 TO BUS 200796 CKT 1   /*26QUEMAHON   230.0 - 26HOOVRSVL   230.0
 OPEN BRANCH FROM BUS 200767 TO BUS 200795 CKT 1         /*26HOMER CT   230.0 - 26SHELOCTA   230.0
END
CONTINGENCY 'PN_P2-3_PN-115-3A2_SRT-A'
 DISCONNECT BRANCH FROM BUS 200501 TO BUS 200542 CKT 2   /*26BDFORD N   115.0 - 26BDFRD N2    23.0
 DISCONNECT BRANCH FROM BUS 200501 TO BUS 200799 CKT 1   /*26BDFORD N   115.0 - 26CEN.CTY    115.0
 DISCONNECT BRANCH FROM BUS 200501 TO BUS 200884 CKT 1   /*26BDFORD N   115.0 - 26NEW BALT   115.0
 DISCONNECT BRANCH FROM BUS 200799 TO BUS 200800 CKT 1   /*26CEN.CTY    115.0 - 26C.CITY W    23.0
 DISCONNECT BRANCH FROM BUS 200799 TO BUS 200836 CKT 1   /*26CEN.CTY    115.0 - 26STATHILL   115.0
 REDUCE BUS 200799 SHUNT BY 100 PERCENT                  /*26CEN.CTY    115.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-2'
 DISCONNECT BRANCH FROM BUS 964990 TO BUS 235103 CKT 1   /*AG1-363 TP   500.0 - 01BLACKO     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-004_SRT-SL-1'
 DISCONNECT BRANCH FROM BUS 235108 TO BUS 964990 CKT 1   /*01HATFLD     500.0 - AG1-363 TP   500.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-2_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200741 CKT 9   /*26SEWARD 2   230.0 - 26SEWARD     115.0
 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1   /*26SEWARD 2   230.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-500-003JT_SRT-A'
 DISCONNECT BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-230-0347-A_SRT-A'
 OPEN BRANCH FROM BUS 200793 TO BUS 200767 CKT 1   /*26SEWARD 2   230.0 - 26HOMER CT   230.0
 OPEN BRANCH FROM BUS 200793 TO BUS 200912 CKT 1   /*26SEWARD 2   230.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-041E_SRT-A'
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 200599 CKT 1   /*02S8-ATT     345.0 - 26ERIE W     345.0
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 238542 CKT 9   /*02S8-ATT     345.0 - 02ASH_1      138.0
END
CONTINGENCY 'ATSI_P2-3_CEI-345-041D_SRT-A'
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 200599 CKT 1   /*02S8-ATT     345.0 - 26ERIE W     345.0
 DISCONNECT BRANCH FROM BUS 239082 TO BUS 238544 CKT 4   /*02S8-ATT     345.0 - 02ASH_3      138.0
END
CONTINGENCY 'AP_P2-2_WP-138-059_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235129 CKT 2   /*01ARMSTR     138.0 - 01ARMSTRONG  345.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235203 CKT 1   /*01ARMSTR     138.0 - 01KISSNG     138.0
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235224 CKT 1   /*01ARMSTR     138.0 - 01N BETH     138.0
END
CONTINGENCY 'PN_P2-2_PN-115-016A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200741 TO BUS 200729 CKT 8   /*26SEWARD     115.0 - 26SEWARD      23.0
 DISCONNECT BRANCH FROM BUS 200741 TO BUS 200742 CKT 1   /*26SEWARD     115.0 - 26TOWER 51   115.0
 DISCONNECT BRANCH FROM BUS 200741 TO BUS 200766 CKT 1   /*26SEWARD     115.0 - 26FLORENCE   115.0
END
CONTINGENCY 'AP_P7-1_WPP-138-053A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235121 TO BUS 235282 CKT 1    /*01ARMSTR     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4E   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235742 CKT 4W   /*01AL 4       138.0 - 01ALL L4      25.0
 DISCONNECT BRANCH FROM BUS 235132 TO BUS 235825 CKT 1    /*01AL 4       138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235134 TO BUS 235139 CKT 1    /*01AL&D6      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235079 CKT 1    /*01AL 4J      138.0 - 01SPGDL-3    138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235139 CKT 1    /*01AL 4J      138.0 - 01AL&D6T     138.0
 DISCONNECT BRANCH FROM BUS 235138 TO BUS 235825 CKT 1    /*01AL 4J      138.0 - 01ALL L4T    138.0
 DISCONNECT BRANCH FROM BUS 235139 TO BUS 235204 CKT 1    /*01AL&D6T     138.0 - 01KITTAN     138.0
 DISCONNECT BRANCH FROM BUS 235202 TO BUS 235240 CKT 1    /*01KISKIV     138.0 - 01COLMBGPN   138.0
 DISCONNECT BRANCH FROM BUS 235204 TO BUS 235282 CKT 1    /*01KITTAN     138.0 - 01GAR RN     138.0
 DISCONNECT BRANCH FROM BUS 235240 TO BUS 235282 CKT 1    /*01COLMBGPN   138.0 - 01GAR RN     138.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT18_SRT-A'
 OPEN BRANCH FROM BUS 235118 TO BUS 235619 CKT 1                /*01SOBEND     500.0 - AD2-113 G1    18.0
 OPEN BRANCH FROM BUS 235118 TO BUS 235620 CKT 1                /*01SOBEND     500.0 - AD2-113 G2    18.0
 OPEN BRANCH FROM BUS 235118 TO BUS 235621 CKT 1                /*01SOBEND     500.0 - AD2-113 G3    18.0
 OPEN BRANCH FROM BUS 235118 TO BUS 235622 CKT 1                /*01SOBEND     500.0 - AD2-113 G4    18.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235118 CKT 1 /*01YUKON      500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235118 CKT 1 /*01YUKON      500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P1-2_PN-230-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 200912 TO BUS 200793 CKT 1   /*26CONEMAGH   230.0 - 26SEWARD 2   230.0
END
CONTINGENCY 'PN_P1-3_PN-500-003_SRT-A'
 OPEN BRANCH FROM BUS 200005 TO BUS 200912 CKT 3   /*CONEM-GH     500.0 - 26CONEMAGH   230.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT27_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200033 CKT 1                /*KEYSTONE     500.0 - KEYS G2       20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-003_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3          /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 DISCONNECT BUS 200033                                          /*KEYS G2       20.0
 REMOVE MACHINE H FROM BUS 200033                               /*KEYS G2       20.0
 REMOVE MACHINE L FROM BUS 200033                               /*KEYS G2       20.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT26_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200032 CKT 1                /*KEYSTONE     500.0 - KEYS G1       20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-004_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 CKT 3          /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 DISCONNECT BUS 200032                                          /*KEYS G1       20.0
 REMOVE MACHINE H FROM BUS 200032                               /*KEYS G1       20.0
 REMOVE MACHINE L FROM BUS 200032                               /*KEYS G1       20.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-2_PN-500-004A-DRT_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT33_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 OPEN BRANCH FROM BUS 200011 TO BUS 235118 CKT 1                /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2526 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200532 CKT 2         /*26ROXBURY    115.0 - 26ROXBURY    138.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-B_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200860 CKT 3         /*26ROXBURY    115.0 - 26ROXB SB2    23.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT31_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 200009 CKT 1                /*KEYSTONE     500.0 - JUNI         500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-008_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200009 CKT 1          /*KEYSTONE     500.0 - JUNI         500.0
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 2598 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2100 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-115-0331-D_SRT-A'
 OPEN BRANCH FROM BUS 200504 TO BUS 202803 CKT 2   /*26CARLISLE   115.0 - 26CARL PK2    23.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200504 CKT 1   /*26ROXBURY    115.0 - 26CARLISLE   115.0
 OPEN BRANCH FROM BUS 200520 TO BUS 200532 CKT 2   /*26ROXBURY    115.0 - 26ROXBURY    138.0
END
CONTINGENCY 'PN_P2-2_PN-115-030_SRT-A'
 DISCONNECT BUS 200522   /*26SHADE GP   115.0
END
CONTINGENCY 'PN_P2-2_PN-115-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 200512 TO BUS 200519 CKT 1   /*26LEWISTWN   115.0 - 26REED TAP   115.0
 DISCONNECT BRANCH FROM BUS 200513 TO BUS 200512 CKT 3   /*26LEWISTWN   230.0 - 26LEWISTWN   115.0
END
CONTINGENCY 'AP_P2-2_WP-138-074_SRT-A'
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 235180 CKT 1   /*01GRANDP     138.0 - 01FAYETT     138.0
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 235189 CKT 1   /*01GRANDP     138.0 - 01GUILFD     138.0
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 235557 CKT 1   /*01GRANDP     138.0 - 01LETTER     138.0
 DISCONNECT BRANCH FROM BUS 235187 TO BUS 237331 CKT 1   /*01GRANDP     138.0 - 01GRANDPOI    69.0
 DISCONNECT BUS 235187                                   /*01GRANDP     138.0
 REDUCE BUS 235187 SHUNT BY 100 PERCENT                  /*01GRANDP     138.0
END
CONTINGENCY 'PL_08_P22_102799_SRT-A'
 DISCONNECT BUS 200080   /*HUST         500.0
END
CONTINGENCY 'PL_48_P71_102649_SRT-A'
 DISCONNECT BRANCH FROM BUS 207915 TO BUS 208113 CKT 1   /*GLBR         230.0 - SUSQ         230.0
 DISCONNECT BUS 208114                                   /*SUSQ G1      230.0
 DISCONNECT BUS 208124                                   /*SUSQ G1 TP   230.0
END
CONTINGENCY 'PECO_P7-1_220-9091_SRT-A
 DISCONNECT BUS 213616   /*FORDACT1      18.0
 DISCONNECT BUS 213617   /*FORDACT2      18.0
 DISCONNECT BUS 213618   /*FORDAST1      18.0
 DISCONNECT BUS 213619   /*FORDBCT1      18.0
 DISCONNECT BUS 213620   /*FORDBCT2      18.0
 DISCONNECT BUS 213621   /*FORDBST1      18.0
 DISCONNECT BUS 213622   /*FORDML90     230.0
 DISCONNECT BUS 213623   /*FORDML91     230.0
END
CONTINGENCY 'PN_P1-2_PN-115-094_A_SRT-A'
 DISCONNECT BRANCH FROM BUS 200520 TO BUS 203971 CKT 1   /*26ROXBURY    115.0 - AE1-071-POI  115.0
END
CONTINGENCY 'PL_10_P12_000085_SRT-A'
 DISCONNECT BRANCH FROM BUS 200009 TO BUS 200011 CKT 1   /*JUNI         500.0 - KEYSTONE     500.0
END
CONTINGENCY 'AP_P2-2_WP-138-036_SRT-A'
 DISCONNECT BRANCH FROM BUS 235618 TO BUS 235173 CKT 1    /*01LOYALH3    138.0 - 01EDGEWT     138.0
 DISCONNECT BRANCH FROM BUS 235618 TO BUS 235617 CKT ZB   /*01LOYALH3    138.0 - 01LOYALH2    138.0
END
CONTINGENCY 'AP_P7-1_WPP-138-083_SRT-A'
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 235596 CKT 1   /*01EDGEWT     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 235618 CKT 1   /*01EDGEWT     138.0 - 01LOYALH3    138.0
 DISCONNECT BRANCH FROM BUS 235173 TO BUS 236469 CKT 1   /*01EDGEWT     138.0 - 01EDGEWATR    25.0
 DISCONNECT BRANCH FROM BUS 235178 TO BUS 235264 CKT 1   /*01ETHEL      138.0 - 01VASC       138.0
 DISCONNECT BRANCH FROM BUS 235253 TO BUS 235596 CKT 1   /*01SOCIAL     138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235264 TO BUS 235596 CKT 1   /*01VASC       138.0 - 01VASC T     138.0
 DISCONNECT BRANCH FROM BUS 235264 TO BUS 235975 CKT 1   /*01VASC       138.0 - 01VASCO       25.0
 DISCONNECT BRANCH FROM BUS 235617 TO BUS 235213 CKT 1   /*01LOYALH2    138.0 - 01LUXOR      138.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT32_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 OPEN BRANCH FROM BUS 200011 TO BUS 235104 CKT 1                /*KEYSTONE     500.0 - 01CABOT      500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 235118 TO BUS 200011 CKT 1 /*01SOBEND     500.0 - KEYSTONE     500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-002_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 235104 CKT 1          /*KEYSTONE     500.0 - 01CABOT      500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2078 BRANCH FROM BUS 200011 TO BUS 235118 CKT 1 /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2426 BRANCH FROM BUS 200011 TO BUS 200009 CKT 1 /*KEYSTONE     500.0 - JUNI         500.0
END
235129 to 235121 ckt 2
235449 to 237310 ckt 1
235173 to 235618 ckt 1
235470 to 235469 ckt 1
235596 to 235173 ckt 1
200763 to 235253 ckt 1
200912 to 200005 ckt 3
200762 to 235470 ckt 1
202650 to 200747 ckt 1
200767 to 200795 ckt 1
200810 to 999278 ckt 4
200513 to 208004 ckt 1
200747 to 200762 ckt 1
200795 to 200810 ckt 1
999278 to 200011 ckt 4
200011 to 235104 ckt 1
200011 to 235118 ckt 1

Winter Peak Analysis

The New Service Request AG2-411 was evaluated as a 63.0 MW (40.7 MW Capacity) injection in the PENELEC area.

AG2-411 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 63.0 MW (63.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-411 was evaluated as a 63.0 MW injection

AG2-411 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 63.0 MW (63.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
PN_P1-2_PN-230-038_SRT-A
SingleAC116.83 %192.0B224.312.24
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT33_SRT-SL
BreakerAC103.17 %192.0B198.091.99
GD2AP
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-006_SRT-SL
BreakerAC103.13 %192.0B198.011.98
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
PN_P1-2_PN-230-038_SRT-A
SingleAC122.46 %192.0B235.122.24
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT33_SRT-SL
BreakerAC109.23 %192.0B209.721.99
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-006_SRT-SL
BreakerAC109.18 %192.0B209.631.98
GD2AP
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT17_SRT-SL
BusAC102.41 %192.0B196.621.87
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Base Case
SingleAC103.41 %133.0A137.533.42
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-115-35E_SRT-A
BreakerAC102.73 %160.0B164.362.99
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P7-1_PN-230-001_SRT-A
TowerAC102.66 %160.0B164.255.28
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-500-DRT33_SRT-SL
BreakerAC100.74 %160.0B161.193.58
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
PN_P2-3_PN-500-004-DRT-006_SRT-SL
BreakerAC100.74 %160.0B161.193.57
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT17_SRT-SL
BusAC100.73 %160.0B161.163.5
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_WP-500-707T_SRT-A
BreakerAC100.7 %160.0B161.123.5
GD2AP/PENELEC
26GARRETT-01GARRET 115.0 kV Ckt 1 line
AP_P2-3_WP-500-696_SRT-A
BreakerAC100.7 %160.0B161.113.5

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o PN_P1-2_PN-230-038_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-038_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.83 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:224.31
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
971321AH1-140 GEN
Solar/Wind Harmer
46.631
970123AG2-090 GEN
Solar/Wind Harmer
0.508
203841AF2-001_GEN
Solar/Wind Harmer
0.719
203961AE2-224 GEN
Solar/Wind Harmer
0
971321AH1-140 GEN
Solar/Wind Harmer
14.131
20094526CT_V3-030
Solar/Wind Harmer
0.731
970631AG2-411 GEN
Solar/Wind Harmer
2.242
20088626ARWF_N39
Solar/Wind Harmer
1.428
203844AF2-092 C
Solar/Wind Harmer
0.412
20088926STNY CRK
Solar/Wind Harmer
1.083
20091526CHSTN_FL
Solar/Wind Harmer
0.753
945751AF1-240 GEN
Solar/Wind Harmer
0.501
203818AF1-086 GEN
Solar/Wind Harmer
2.548
971423AH1-203 GEN
Solar/Wind Harmer
2.262
960051AF2-296 GEN
Solar/Wind Harmer
0.61
20303426NA_O38_P22
Solar/Wind Harmer
1.162
203857AF2-221 C
Solar/Wind Harmer
0.544
957561AF2-050 GEN
Solar/Wind Harmer
1.475
237046AF1-021 C
Solar/Wind Helper
0.264
20083726HOMER C1
50/50
38
20083926HOMER C3
50/50
29.068
237043AE2-125 C
Solar/Wind Helper
0.704
970899AG2-561 GEN
Solar/Wind Harmer
0.859
972077AH1-588 GEN
Solar/Wind Harmer
4.94
971441AH1-212 GEN
Solar/Wind Harmer
0.718
20083426SW_E13_K22
Solar/Wind Harmer
0.178
23652301WDPWR_K20
Solar/Wind Helper
0.378
20088826HIGHLAND
Solar/Wind Harmer
1.468
20084626FORWARD
Solar/Wind Harmer
0.659
203850AG1-041 C
Solar/Wind Harmer
0.413
972079AH1-589 GEN
Solar/Wind Harmer
6.48
946071AF1-272 GEN
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
0.218
971879AH1-460 GEN
Solar/Wind Harmer
2.385
203839AF1-321 GEN
Solar/Wind Harmer
0.719
203843AF2-002_GEN
Solar/Wind Harmer
0.359
20092526R32
Solar/Wind Harmer
1.694
VFTLTFEXP_VFT->PJM
CMTX
2.919
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.057
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.724
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.194
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.224
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.233
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
1.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT33_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT33_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.17 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:198.09
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
971541AH1-268 GEN
Solar/Wind Harmer
4.381
971321AH1-140 GEN
Solar/Wind Harmer
45.954
970123AG2-090 GEN
Solar/Wind Harmer
0.455
203841AF2-001_GEN
Solar/Wind Harmer
0.639
971321AH1-140 GEN
Solar/Wind Harmer
13.925
20094526CT_V3-030
Solar/Wind Harmer
0.668
970631AG2-411 GEN
Solar/Wind Harmer
1.992
203844AF2-092 C
Solar/Wind Harmer
0.37
20088926STNY CRK
Solar/Wind Harmer
0.959
971427AH1-205 GEN
Solar/Wind Harmer
1.394
20091526CHSTN_FL
Solar/Wind Harmer
0.687
971419AH1-201 GEN
Solar/Wind Harmer
0.753
945751AF1-240 GEN
Solar/Wind Harmer
0.457
203818AF1-086 GEN
Solar/Wind Harmer
2.331
971423AH1-203 GEN
Solar/Wind Harmer
1.998
960051AF2-296 GEN
Solar/Wind Harmer
0.56
203857AF2-221 C
Solar/Wind Harmer
0.487
237046AF1-021 C
Solar/Wind Helper
0.306
237043AE2-125 C
Solar/Wind Helper
0.738
971279AH1-102 GEN
Solar/Wind Harmer
3.154
970899AG2-561 GEN
Solar/Wind Harmer
0.784
972077AH1-588 GEN
Solar/Wind Harmer
4.309
971441AH1-212 GEN
Solar/Wind Harmer
0.654
20083426SW_E13_K22
Solar/Wind Harmer
0.157
23652301WDPWR_K20
Solar/Wind Helper
0.416
20088826HIGHLAND
Solar/Wind Harmer
1.324
20084626FORWARD
Solar/Wind Harmer
0.585
203850AG1-041 C
Solar/Wind Harmer
0.371
972079AH1-589 GEN
Solar/Wind Harmer
5.652
946071AF1-272 GEN
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
0.195
20092526R32
Solar/Wind Harmer
1.528
971879AH1-460 GEN
Solar/Wind Harmer
2.128
203839AF1-321 GEN
Solar/Wind Harmer
0.639
203843AF2-002_GEN
Solar/Wind Harmer
0.319
VFTLTFEXP_VFT->PJM
CMTX
5.758
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.734
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.185
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.024
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.363
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
2.078
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.226
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-006_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.13 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:198.01
MW Contribution:1.98
Bus #Bus NameTypeMW Contribution
971541AH1-268 GEN
Solar/Wind Harmer
4.366
971321AH1-140 GEN
Solar/Wind Harmer
45.945
970123AG2-090 GEN
Solar/Wind Harmer
0.453
203841AF2-001_GEN
Solar/Wind Harmer
0.636
971321AH1-140 GEN
Solar/Wind Harmer
13.923
20094526CT_V3-030
Solar/Wind Harmer
0.665
970631AG2-411 GEN
Solar/Wind Harmer
1.983
203844AF2-092 C
Solar/Wind Harmer
0.368
20088926STNY CRK
Solar/Wind Harmer
0.955
971427AH1-205 GEN
Solar/Wind Harmer
1.388
20091526CHSTN_FL
Solar/Wind Harmer
0.684
971419AH1-201 GEN
Solar/Wind Harmer
0.749
945751AF1-240 GEN
Solar/Wind Harmer
0.455
203818AF1-086 GEN
Solar/Wind Harmer
2.323
971423AH1-203 GEN
Solar/Wind Harmer
1.989
960051AF2-296 GEN
Solar/Wind Harmer
0.558
203857AF2-221 C
Solar/Wind Harmer
0.485
237046AF1-021 C
Solar/Wind Helper
0.306
237043AE2-125 C
Solar/Wind Helper
0.738
971279AH1-102 GEN
Solar/Wind Harmer
3.144
970899AG2-561 GEN
Solar/Wind Harmer
0.781
972077AH1-588 GEN
Solar/Wind Harmer
4.284
971441AH1-212 GEN
Solar/Wind Harmer
0.652
20083426SW_E13_K22
Solar/Wind Harmer
0.156
23652301WDPWR_K20
Solar/Wind Helper
0.416
20088826HIGHLAND
Solar/Wind Harmer
1.319
20084626FORWARD
Solar/Wind Harmer
0.583
203850AG1-041 C
Solar/Wind Harmer
0.369
972079AH1-589 GEN
Solar/Wind Harmer
5.62
946071AF1-272 GEN
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
0.194
20092526R32
Solar/Wind Harmer
1.522
971879AH1-460 GEN
Solar/Wind Harmer
2.119
203839AF1-321 GEN
Solar/Wind Harmer
0.636
203843AF2-002_GEN
Solar/Wind Harmer
0.318
VFTLTFEXP_VFT->PJM
CMTX
5.766
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.735
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.185
CBM NorthLTFEXP_CBM-N->PJM
CBM
8
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.363
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
2.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.226
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o PN_P1-2_PN-230-038_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
PN_P1-2_PN-230-038_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:122.46 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:235.12
MW Contribution:2.24
Bus #Bus NameTypeMW Contribution
971321AH1-140 GEN
Solar/Wind Harmer
46.631
970123AG2-090 GEN
Solar/Wind Harmer
0.508
203841AF2-001_GEN
Solar/Wind Harmer
0.719
203961AE2-224 GEN
Solar/Wind Harmer
0
971321AH1-140 GEN
Solar/Wind Harmer
14.131
20094526CT_V3-030
Solar/Wind Harmer
0.731
970631AG2-411 GEN
Solar/Wind Harmer
2.242
20088626ARWF_N39
Solar/Wind Harmer
1.428
203844AF2-092 C
Solar/Wind Harmer
0.412
20088926STNY CRK
Solar/Wind Harmer
1.083
20091526CHSTN_FL
Solar/Wind Harmer
0.753
945751AF1-240 GEN
Solar/Wind Harmer
0.501
203818AF1-086 GEN
Solar/Wind Harmer
2.548
971423AH1-203 GEN
Solar/Wind Harmer
2.262
960051AF2-296 GEN
Solar/Wind Harmer
0.61
20303426NA_O38_P22
Solar/Wind Harmer
1.162
203857AF2-221 C
Solar/Wind Harmer
0.544
957561AF2-050 GEN
Solar/Wind Harmer
1.475
237046AF1-021 C
Solar/Wind Helper
0.264
20083726HOMER C1
50/50
38
20083926HOMER C3
50/50
29.068
237043AE2-125 C
Solar/Wind Helper
0.704
970899AG2-561 GEN
Solar/Wind Harmer
0.859
972077AH1-588 GEN
Solar/Wind Harmer
4.94
971441AH1-212 GEN
Solar/Wind Harmer
0.718
20083426SW_E13_K22
Solar/Wind Harmer
0.178
23652301WDPWR_K20
Solar/Wind Helper
0.378
20088826HIGHLAND
Solar/Wind Harmer
1.468
20084626FORWARD
Solar/Wind Harmer
0.659
203850AG1-041 C
Solar/Wind Harmer
0.413
972079AH1-589 GEN
Solar/Wind Harmer
6.48
946071AF1-272 GEN
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
0.218
971879AH1-460 GEN
Solar/Wind Harmer
2.385
203839AF1-321 GEN
Solar/Wind Harmer
0.719
203843AF2-002_GEN
Solar/Wind Harmer
0.359
20092526R32
Solar/Wind Harmer
1.694
VFTLTFEXP_VFT->PJM
CMTX
2.919
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.057
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.724
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.194
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.224
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.233
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
1.039
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT33_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT33_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.23 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:209.72
MW Contribution:1.99
Bus #Bus NameTypeMW Contribution
971541AH1-268 GEN
Solar/Wind Harmer
4.381
971321AH1-140 GEN
Solar/Wind Harmer
45.954
970123AG2-090 GEN
Solar/Wind Harmer
0.455
203841AF2-001_GEN
Solar/Wind Harmer
0.639
971321AH1-140 GEN
Solar/Wind Harmer
13.925
20094526CT_V3-030
Solar/Wind Harmer
0.668
970631AG2-411 GEN
Solar/Wind Harmer
1.992
203844AF2-092 C
Solar/Wind Harmer
0.37
20088926STNY CRK
Solar/Wind Harmer
0.959
971427AH1-205 GEN
Solar/Wind Harmer
1.394
20091526CHSTN_FL
Solar/Wind Harmer
0.687
971419AH1-201 GEN
Solar/Wind Harmer
0.753
945751AF1-240 GEN
Solar/Wind Harmer
0.457
203818AF1-086 GEN
Solar/Wind Harmer
2.331
971423AH1-203 GEN
Solar/Wind Harmer
1.998
960051AF2-296 GEN
Solar/Wind Harmer
0.56
203857AF2-221 C
Solar/Wind Harmer
0.487
237046AF1-021 C
Solar/Wind Helper
0.306
237043AE2-125 C
Solar/Wind Helper
0.738
971279AH1-102 GEN
Solar/Wind Harmer
3.154
970899AG2-561 GEN
Solar/Wind Harmer
0.784
972077AH1-588 GEN
Solar/Wind Harmer
4.309
971441AH1-212 GEN
Solar/Wind Harmer
0.654
20083426SW_E13_K22
Solar/Wind Harmer
0.157
23652301WDPWR_K20
Solar/Wind Helper
0.416
20088826HIGHLAND
Solar/Wind Harmer
1.324
20084626FORWARD
Solar/Wind Harmer
0.585
203850AG1-041 C
Solar/Wind Harmer
0.371
972079AH1-589 GEN
Solar/Wind Harmer
5.652
946071AF1-272 GEN
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
0.195
20092526R32
Solar/Wind Harmer
1.528
971879AH1-460 GEN
Solar/Wind Harmer
2.128
203839AF1-321 GEN
Solar/Wind Harmer
0.639
203843AF2-002_GEN
Solar/Wind Harmer
0.319
VFTLTFEXP_VFT->PJM
CMTX
5.758
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.734
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.185
CBM NorthLTFEXP_CBM-N->PJM
CBM
8.024
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.363
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
2.078
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.226
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-006_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.18 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:209.63
MW Contribution:1.98
Bus #Bus NameTypeMW Contribution
971541AH1-268 GEN
Solar/Wind Harmer
4.366
971321AH1-140 GEN
Solar/Wind Harmer
45.945
970123AG2-090 GEN
Solar/Wind Harmer
0.453
203841AF2-001_GEN
Solar/Wind Harmer
0.636
971321AH1-140 GEN
Solar/Wind Harmer
13.923
20094526CT_V3-030
Solar/Wind Harmer
0.665
970631AG2-411 GEN
Solar/Wind Harmer
1.983
203844AF2-092 C
Solar/Wind Harmer
0.368
20088926STNY CRK
Solar/Wind Harmer
0.955
971427AH1-205 GEN
Solar/Wind Harmer
1.388
20091526CHSTN_FL
Solar/Wind Harmer
0.684
971419AH1-201 GEN
Solar/Wind Harmer
0.749
945751AF1-240 GEN
Solar/Wind Harmer
0.455
203818AF1-086 GEN
Solar/Wind Harmer
2.323
971423AH1-203 GEN
Solar/Wind Harmer
1.989
960051AF2-296 GEN
Solar/Wind Harmer
0.558
203857AF2-221 C
Solar/Wind Harmer
0.485
237046AF1-021 C
Solar/Wind Helper
0.306
237043AE2-125 C
Solar/Wind Helper
0.738
971279AH1-102 GEN
Solar/Wind Harmer
3.144
970899AG2-561 GEN
Solar/Wind Harmer
0.781
972077AH1-588 GEN
Solar/Wind Harmer
4.284
971441AH1-212 GEN
Solar/Wind Harmer
0.652
20083426SW_E13_K22
Solar/Wind Harmer
0.156
23652301WDPWR_K20
Solar/Wind Helper
0.416
20088826HIGHLAND
Solar/Wind Harmer
1.319
20084626FORWARD
Solar/Wind Harmer
0.583
203850AG1-041 C
Solar/Wind Harmer
0.369
972079AH1-589 GEN
Solar/Wind Harmer
5.62
946071AF1-272 GEN
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
0.194
20092526R32
Solar/Wind Harmer
1.522
971879AH1-460 GEN
Solar/Wind Harmer
2.119
203839AF1-321 GEN
Solar/Wind Harmer
0.636
203843AF2-002_GEN
Solar/Wind Harmer
0.318
VFTLTFEXP_VFT->PJM
CMTX
5.766
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.735
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.185
CBM NorthLTFEXP_CBM-N->PJM
CBM
8
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.363
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.381
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
2.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.226
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 01VASC T-01EDGEWT 138.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT17_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01VASC T-01EDGEWT 138.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT17_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.41 %
Rating:192.0 MVA
Rating Type:B
MVA to Mitigate:196.62
MW Contribution:1.87
Bus #Bus NameTypeMW Contribution
971541AH1-268 GEN
Solar/Wind Harmer
4.176
971321AH1-140 GEN
Solar/Wind Harmer
45.831
970123AG2-090 GEN
Solar/Wind Harmer
0.427
203841AF2-001_GEN
Solar/Wind Harmer
0.598
971321AH1-140 GEN
Solar/Wind Harmer
13.888
20094526CT_V3-030
Solar/Wind Harmer
0.633
970631AG2-411 GEN
Solar/Wind Harmer
1.866
203844AF2-092 C
Solar/Wind Harmer
0.347
20088926STNY CRK
Solar/Wind Harmer
0.899
971427AH1-205 GEN
Solar/Wind Harmer
1.306
20091526CHSTN_FL
Solar/Wind Harmer
0.647
971419AH1-201 GEN
Solar/Wind Harmer
0.705
945751AF1-240 GEN
Solar/Wind Harmer
0.434
203818AF1-086 GEN
Solar/Wind Harmer
2.215
203857AF2-221 C
Solar/Wind Harmer
0.458
237046AF1-021 C
Solar/Wind Helper
0.307
237043AE2-125 C
Solar/Wind Helper
0.741
971279AH1-102 GEN
Solar/Wind Harmer
3.007
970899AG2-561 GEN
Solar/Wind Harmer
0.746
971441AH1-212 GEN
Solar/Wind Harmer
0.618
23652301WDPWR_K20
Solar/Wind Helper
0.418
20088826HIGHLAND
Solar/Wind Harmer
1.246
20084626FORWARD
Solar/Wind Harmer
0.548
203850AG1-041 C
Solar/Wind Harmer
0.348
946071AF1-272 GEN
Solar/Wind Harmer
0
970125AG2-091 GEN
Solar/Wind Harmer
0.183
20092526R32
Solar/Wind Harmer
1.438
971879AH1-460 GEN
Solar/Wind Harmer
1.997
203839AF1-321 GEN
Solar/Wind Harmer
0.598
203843AF2-002_GEN
Solar/Wind Harmer
0.299
VFTLTFEXP_VFT->PJM
CMTX
5.873
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.746
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.192
CBM NorthLTFEXP_CBM-N->PJM
CBM
7.689
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.364
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.383
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
2.122
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.227
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.41 %
Rating:133.0 MVA
Rating Type:A
MVA to Mitigate:137.53
MW Contribution:3.42
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
4.075
203841AF2-001_GEN
Solar/Wind Harmer
1.1
970123AG2-090 GEN
Solar/Wind Harmer
0.63
20083526ARN_Z1-066
50/50
1.897
970631AG2-411 GEN
Solar/Wind Harmer
3.425
20088926STNY CRK
Solar/Wind Harmer
2.68
203844AF2-092 C
Solar/Wind Harmer
0.62
238120AE2-309 GEN
Solar/Wind Helper
0.342
971423AH1-203 GEN
Solar/Wind Harmer
6.2
203857AF2-221 C
Solar/Wind Harmer
0.675
238126S14_GEN_1
Solar/Wind Helper
0.694
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
3.967
202652Y1-033 WT C
Solar/Wind Harmer
6.142
20083426SW_E13_K22
Solar/Wind Harmer
0.583
971441AH1-212 GEN
Solar/Wind Harmer
0.548
20089026BF_G21_K23
Solar/Wind Harmer
3.225
20084626FORWARD
Solar/Wind Harmer
1.006
203850AG1-041 C
Solar/Wind Harmer
0.587
20088826HIGHLAND
Solar/Wind Harmer
1.515
238127S14_GEN_2
Solar/Wind Helper
0.694
203839AF1-321 GEN
Solar/Wind Harmer
1.1
203843AF2-002_GEN
Solar/Wind Harmer
0.55
971879AH1-460 GEN
Solar/Wind Harmer
3.252
970125AG2-091 GEN
Solar/Wind Harmer
0.27
20092526R32
Solar/Wind Harmer
1.749
VFTLTFEXP_VFT->PJM
CMTX
1.844
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.846
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.566
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.749
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.228
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.182
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.65
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.136
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-115-35E_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-115-35E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.73 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:164.36
MW Contribution:2.99
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
7.207
203841AF2-001_GEN
Solar/Wind Harmer
0.796
20083526ARN_Z1-066
50/50
3.356
970631AG2-411 GEN
Solar/Wind Harmer
2.991
20088926STNY CRK
Solar/Wind Harmer
5.91
203844AF2-092 C
Solar/Wind Harmer
0.914
971427AH1-205 GEN
Solar/Wind Harmer
8.717
971419AH1-201 GEN
Solar/Wind Harmer
4.707
971423AH1-203 GEN
Solar/Wind Harmer
14.43
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
7.017
202652Y1-033 WT C
Solar/Wind Harmer
8.586
20083426SW_E13_K22
Solar/Wind Harmer
1.464
20089026BF_G21_K23
Solar/Wind Harmer
5.705
203850AG1-041 C
Solar/Wind Harmer
0.835
20084626FORWARD
Solar/Wind Harmer
0.879
20088826HIGHLAND
Solar/Wind Harmer
1.25
203839AF1-321 GEN
Solar/Wind Harmer
0.796
203843AF2-002_GEN
Solar/Wind Harmer
0.398
20092526R32
Solar/Wind Harmer
1.443
VFTLTFEXP_VFT->PJM
CMTX
0.898
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.708
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.474
CBM NorthLTFEXP_CBM-N->PJM
CBM
2.244
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.182
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.152
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.31
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.109
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P7-1_PN-230-001_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P7-1_PN-230-001_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.66 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:164.25
MW Contribution:5.28
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
5.152
203841AF2-001_GEN
Solar/Wind Harmer
2.414
970123AG2-090 GEN
Solar/Wind Harmer
1.247
20083526ARN_Z1-066
50/50
2.399
970631AG2-411 GEN
Solar/Wind Harmer
5.282
20088926STNY CRK
Solar/Wind Harmer
4.067
203844AF2-092 C
Solar/Wind Harmer
0.934
971427AH1-205 GEN
Solar/Wind Harmer
5.966
20091526CHSTN_FL
Solar/Wind Harmer
0.85
238120AE2-309 GEN
Solar/Wind Helper
0.301
971419AH1-201 GEN
Solar/Wind Harmer
3.222
971423AH1-203 GEN
Solar/Wind Harmer
9.413
203857AF2-221 C
Solar/Wind Harmer
1.336
238126S14_GEN_1
Solar/Wind Helper
0.612
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
5.016
202652Y1-033 WT C
Solar/Wind Harmer
6.982
20083426SW_E13_K22
Solar/Wind Harmer
0.886
971441AH1-212 GEN
Solar/Wind Harmer
0.69
20089026BF_G21_K23
Solar/Wind Harmer
4.078
20084626FORWARD
Solar/Wind Harmer
1.552
203850AG1-041 C
Solar/Wind Harmer
0.881
20088826HIGHLAND
Solar/Wind Harmer
2.451
238127S14_GEN_2
Solar/Wind Helper
0.612
203839AF1-321 GEN
Solar/Wind Harmer
2.414
203843AF2-002_GEN
Solar/Wind Harmer
1.207
971879AH1-460 GEN
Solar/Wind Harmer
6.772
970125AG2-091 GEN
Solar/Wind Harmer
0.534
20092526R32
Solar/Wind Harmer
2.828
VFTLTFEXP_VFT->PJM
CMTX
1.617
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.841
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.564
CBM NorthLTFEXP_CBM-N->PJM
CBM
3.153
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.219
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.181
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.569
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-500-DRT33_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-DRT33_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.74 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:161.19
MW Contribution:3.58
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
4.111
203841AF2-001_GEN
Solar/Wind Harmer
1.148
970123AG2-090 GEN
Solar/Wind Harmer
0.663
20083526ARN_Z1-066
50/50
1.914
970631AG2-411 GEN
Solar/Wind Harmer
3.575
235531U2-073 GEN
Solar/Wind Helper
1.877
20088926STNY CRK
Solar/Wind Harmer
2.751
203844AF2-092 C
Solar/Wind Harmer
0.647
971427AH1-205 GEN
Solar/Wind Harmer
4.035
20091526CHSTN_FL
Solar/Wind Harmer
0.691
238120AE2-309 GEN
Solar/Wind Helper
0.35
971419AH1-201 GEN
Solar/Wind Harmer
2.179
971423AH1-203 GEN
Solar/Wind Harmer
6.347
203857AF2-221 C
Solar/Wind Harmer
0.711
238126S14_GEN_1
Solar/Wind Helper
0.707
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
4.003
202652Y1-033 WT C
Solar/Wind Harmer
6.164
20083426SW_E13_K22
Solar/Wind Harmer
0.594
971441AH1-212 GEN
Solar/Wind Harmer
0.594
20089026BF_G21_K23
Solar/Wind Harmer
3.254
20084626FORWARD
Solar/Wind Harmer
1.05
203850AG1-041 C
Solar/Wind Harmer
0.614
20088826HIGHLAND
Solar/Wind Harmer
1.613
238127S14_GEN_2
Solar/Wind Helper
0.707
203839AF1-321 GEN
Solar/Wind Harmer
1.148
203843AF2-002_GEN
Solar/Wind Harmer
0.574
971879AH1-460 GEN
Solar/Wind Harmer
3.41
970125AG2-091 GEN
Solar/Wind Harmer
0.284
20092526R32
Solar/Wind Harmer
1.862
VFTLTFEXP_VFT->PJM
CMTX
2.766
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.099
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.738
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.758
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.284
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.237
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.984
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.17
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o PN_P2-3_PN-500-004-DRT-006_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
PN_P2-3_PN-500-004-DRT-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.74 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:161.19
MW Contribution:3.57
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
4.11
203841AF2-001_GEN
Solar/Wind Harmer
1.146
970123AG2-090 GEN
Solar/Wind Harmer
0.662
20083526ARN_Z1-066
50/50
1.914
970631AG2-411 GEN
Solar/Wind Harmer
3.57
235531U2-073 GEN
Solar/Wind Helper
1.877
20088926STNY CRK
Solar/Wind Harmer
2.749
203844AF2-092 C
Solar/Wind Harmer
0.647
971427AH1-205 GEN
Solar/Wind Harmer
4.031
20091526CHSTN_FL
Solar/Wind Harmer
0.69
238120AE2-309 GEN
Solar/Wind Helper
0.351
971419AH1-201 GEN
Solar/Wind Harmer
2.177
971423AH1-203 GEN
Solar/Wind Harmer
6.342
203857AF2-221 C
Solar/Wind Harmer
0.71
238126S14_GEN_1
Solar/Wind Helper
0.707
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
4.001
202652Y1-033 WT C
Solar/Wind Harmer
6.163
20083426SW_E13_K22
Solar/Wind Harmer
0.594
971441AH1-212 GEN
Solar/Wind Harmer
0.593
20089026BF_G21_K23
Solar/Wind Harmer
3.253
20084626FORWARD
Solar/Wind Harmer
1.049
203850AG1-041 C
Solar/Wind Harmer
0.613
20088826HIGHLAND
Solar/Wind Harmer
1.61
238127S14_GEN_2
Solar/Wind Helper
0.707
203839AF1-321 GEN
Solar/Wind Harmer
1.146
203843AF2-002_GEN
Solar/Wind Harmer
0.573
971879AH1-460 GEN
Solar/Wind Harmer
3.405
970125AG2-091 GEN
Solar/Wind Harmer
0.284
20092526R32
Solar/Wind Harmer
1.858
VFTLTFEXP_VFT->PJM
CMTX
2.771
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.099
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.738
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.745
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.284
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.237
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
0.986
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.17
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT17_SRT-SL


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT17_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.73 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:161.16
MW Contribution:3.5
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
4.091
203841AF2-001_GEN
Solar/Wind Harmer
1.125
970123AG2-090 GEN
Solar/Wind Harmer
0.648
20083526ARN_Z1-066
50/50
1.905
970631AG2-411 GEN
Solar/Wind Harmer
3.505
235531U2-073 GEN
Solar/Wind Helper
1.881
20088926STNY CRK
Solar/Wind Harmer
2.718
203844AF2-092 C
Solar/Wind Harmer
0.635
971427AH1-205 GEN
Solar/Wind Harmer
3.986
20091526CHSTN_FL
Solar/Wind Harmer
0.669
238120AE2-309 GEN
Solar/Wind Helper
0.351
971419AH1-201 GEN
Solar/Wind Harmer
2.153
971423AH1-203 GEN
Solar/Wind Harmer
6.277
203857AF2-221 C
Solar/Wind Harmer
0.694
238126S14_GEN_1
Solar/Wind Helper
0.709
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
3.983
202652Y1-033 WT C
Solar/Wind Harmer
6.148
20083426SW_E13_K22
Solar/Wind Harmer
0.589
971441AH1-212 GEN
Solar/Wind Harmer
0.574
20089026BF_G21_K23
Solar/Wind Harmer
3.239
20084626FORWARD
Solar/Wind Harmer
1.03
203850AG1-041 C
Solar/Wind Harmer
0.602
20088826HIGHLAND
Solar/Wind Harmer
1.57
238127S14_GEN_2
Solar/Wind Helper
0.709
203839AF1-321 GEN
Solar/Wind Harmer
1.125
203843AF2-002_GEN
Solar/Wind Harmer
0.563
971879AH1-460 GEN
Solar/Wind Harmer
3.338
970125AG2-091 GEN
Solar/Wind Harmer
0.278
20092526R32
Solar/Wind Harmer
1.812
VFTLTFEXP_VFT->PJM
CMTX
2.831
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.742
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.572
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.284
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.238
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
1.008
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.171
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_WP-500-707T_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-707T_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.7 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:161.12
MW Contribution:3.5
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
4.091
203841AF2-001_GEN
Solar/Wind Harmer
1.125
970123AG2-090 GEN
Solar/Wind Harmer
0.648
20083526ARN_Z1-066
50/50
1.905
970631AG2-411 GEN
Solar/Wind Harmer
3.505
235531U2-073 GEN
Solar/Wind Helper
1.881
20088926STNY CRK
Solar/Wind Harmer
2.718
203844AF2-092 C
Solar/Wind Harmer
0.635
971427AH1-205 GEN
Solar/Wind Harmer
3.986
20091526CHSTN_FL
Solar/Wind Harmer
0.669
238120AE2-309 GEN
Solar/Wind Helper
0.351
971419AH1-201 GEN
Solar/Wind Harmer
2.153
971423AH1-203 GEN
Solar/Wind Harmer
6.277
203857AF2-221 C
Solar/Wind Harmer
0.694
238126S14_GEN_1
Solar/Wind Helper
0.709
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
3.983
202652Y1-033 WT C
Solar/Wind Harmer
6.148
20083426SW_E13_K22
Solar/Wind Harmer
0.589
971441AH1-212 GEN
Solar/Wind Harmer
0.574
20089026BF_G21_K23
Solar/Wind Harmer
3.239
20084626FORWARD
Solar/Wind Harmer
1.03
203850AG1-041 C
Solar/Wind Harmer
0.602
20088826HIGHLAND
Solar/Wind Harmer
1.57
238127S14_GEN_2
Solar/Wind Helper
0.709
203839AF1-321 GEN
Solar/Wind Harmer
1.125
203843AF2-002_GEN
Solar/Wind Harmer
0.563
971879AH1-460 GEN
Solar/Wind Harmer
3.338
970125AG2-091 GEN
Solar/Wind Harmer
0.278
20092526R32
Solar/Wind Harmer
1.812
VFTLTFEXP_VFT->PJM
CMTX
2.831
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.742
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.572
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.284
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.238
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
1.008
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.171
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 26GARRETT-01GARRET 115.0 kV Ckt 1 line l/o AP_P2-3_WP-500-696_SRT-A


Base Case Flowgate

Area:AP/PENELEC
Facility Description:
26GARRETT-01GARRET 115.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-696_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.7 %
Rating:160.0 MVA
Rating Type:B
MVA to Mitigate:161.11
MW Contribution:3.5
Bus #Bus NameTypeMW Contribution
20089126CSLMN_L13
Solar/Wind Harmer
4.091
203841AF2-001_GEN
Solar/Wind Harmer
1.125
970123AG2-090 GEN
Solar/Wind Harmer
0.648
20083526ARN_Z1-066
50/50
1.905
970631AG2-411 GEN
Solar/Wind Harmer
3.505
235531U2-073 GEN
Solar/Wind Helper
1.881
20088926STNY CRK
Solar/Wind Harmer
2.718
203844AF2-092 C
Solar/Wind Harmer
0.635
971427AH1-205 GEN
Solar/Wind Harmer
3.986
20091526CHSTN_FL
Solar/Wind Harmer
0.669
238120AE2-309 GEN
Solar/Wind Helper
0.351
971419AH1-201 GEN
Solar/Wind Harmer
2.153
971423AH1-203 GEN
Solar/Wind Harmer
6.277
203857AF2-221 C
Solar/Wind Harmer
0.694
238126S14_GEN_1
Solar/Wind Helper
0.709
944781AF1-143 GEN
Solar/Wind Harmer
0
20089226LOOKOUT
Solar/Wind Harmer
3.983
202652Y1-033 WT C
Solar/Wind Harmer
6.148
20083426SW_E13_K22
Solar/Wind Harmer
0.589
971441AH1-212 GEN
Solar/Wind Harmer
0.574
20089026BF_G21_K23
Solar/Wind Harmer
3.239
20084626FORWARD
Solar/Wind Harmer
1.03
203850AG1-041 C
Solar/Wind Harmer
0.602
20088826HIGHLAND
Solar/Wind Harmer
1.57
238127S14_GEN_2
Solar/Wind Helper
0.709
203839AF1-321 GEN
Solar/Wind Harmer
1.125
203843AF2-002_GEN
Solar/Wind Harmer
0.563
971879AH1-460 GEN
Solar/Wind Harmer
3.338
970125AG2-091 GEN
Solar/Wind Harmer
0.278
20092526R32
Solar/Wind Harmer
1.812
VFTLTFEXP_VFT->PJM
CMTX
2.831
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.105
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.742
CBM NorthLTFEXP_CBM-N->PJM
CBM
4.572
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.284
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.238
MDUPJM->LTFIMP_MDU
CLTF
0
G-007ALTFEXP_G-007A->PJM
CMTX
1.008
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.171
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CONTINGENCY 'PN_P1-2_PN-230-038_SRT-A'
 DISCONNECT BRANCH FROM BUS 200795 TO BUS 200810 CKT 1   /*26SHELOCTA   230.0 - 26KEYSTONE   230.0
END
CONTINGENCY 'PN_P2-3_PN-500-DRT33_SRT-SL'
 OPEN BRANCH FROM BUS 200011 TO BUS 200810 CKT 3                /*KEYSTONE     500.0 - 26KEYSTONE   230.0
 OPEN BRANCH FROM BUS 200011 TO BUS 235118 CKT 1                /*KEYSTONE     500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2526 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'PN_P2-3_PN-500-004-DRT-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 200810 TO BUS 200907 CKT 4 /*KEYSTONE     500.0 - 26KEYSTONE   230.0 - 26KEYSTN#4    20.0
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 235118 CKT 1          /*KEYSTONE     500.0 - 01SOBEND     500.0
 REDUCE BUS 200011 SHUNT BY 100 PERCENT                         /*KEYSTONE     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET POSTCONTRATING 2771 BRANCH FROM BUS 200011 TO BUS 200009 CKT 1 /*KEYSTONE     500.0 - JUNI         500.0
 SET POSTCONTRATING 2844 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
 SET PRECONTRATING 2482 BRANCH FROM BUS 200005 TO BUS 200011 CKT 1 /*CONEM-GH     500.0 - KEYSTONE     500.0
 SET PRECONTRATING 2482 BRANCH FROM BUS 200011 TO BUS 200009 CKT 1 /*KEYSTONE     500.0 - JUNI         500.0
 SET PRECONTRATING 2526 BRANCH FROM BUS 200011 TO BUS 235104 CKT 1 /*KEYSTONE     500.0 - 01CABOT      500.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT17_SRT-SL'
 OPEN BRANCH FROM BUS 235118 TO BUS 200011 CKT 1                /*01SOBEND     500.0 - KEYSTONE     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235118 CKT 1 /*01YUKON      500.0 - 01SOBEND     500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235118 CKT 1 /*01YUKON      500.0 - 01SOBEND     500.0
END
CONTINGENCY 'PN_P2-3_PN-115-35E_SRT-A'
 DISCONNECT BRANCH FROM BUS 200742 TO BUS 200902 CKT 1    /*26TOWER 51   115.0 - 26HOOVRSV2   115.0
 DISCONNECT BRANCH FROM BUS 200743 TO BUS 200776 CKT 1    /*26HOOVRSV1   115.0 - 26HOOVER#1    23.0
 DISCONNECT BRANCH FROM BUS 200743 TO BUS 200802 CKT 1    /*26HOOVRSV1   115.0 - 26RALPHTON   115.0
 DISCONNECT BRANCH FROM BUS 200743 TO BUS 200902 CKT ZB   /*26HOOVRSV1   115.0 - 26HOOVRSV2   115.0
 DISCONNECT BRANCH FROM BUS 200902 TO BUS 200744 CKT 1    /*26HOOVRSV2   115.0 - 26SOMERST    115.0
 DISCONNECT BRANCH FROM BUS 200902 TO BUS 200789 CKT 2    /*26HOOVRSV2   115.0 - 26HOOVER#2    23.0
 DISCONNECT BRANCH FROM BUS 971878 TO BUS 200743 CKT 1    /*AH1-460 TP   115.0 - 26HOOVRSV1   115.0
END
CONTINGENCY 'PN_P7-1_PN-230-001_SRT-A'
 DISCONNECT BRANCH FROM BUS 200741 TO BUS 200742 CKT 1    /*26SEWARD     115.0 - 26TOWER 51   115.0
 DISCONNECT BRANCH FROM BUS 200743 TO BUS 200903 CKT ZB   /*26HOOVRSV1   115.0 - 26HOOVERSV3  115.0
 DISCONNECT BRANCH FROM BUS 200767 TO BUS 200768 CKT 1    /*26HOMER CT   230.0 - 26QUEMAHON   230.0
 DISCONNECT BRANCH FROM BUS 200768 TO BUS 200796 CKT 1    /*26QUEMAHON   230.0 - 26HOOVRSVL   230.0
 DISCONNECT BRANCH FROM BUS 200903 TO BUS 200796 CKT 3    /*26HOOVERSV3  115.0 - 26HOOVRSVL   230.0
END
CONTINGENCY 'AP_P2-3_WP-500-707T_SRT-A'
 DISCONNECT BRANCH FROM BUS 200011 TO BUS 235118 CKT 1   /*KEYSTONE     500.0 - 01SOBEND     500.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235619 CKT 1   /*01SOBEND     500.0 - AD2-113 G1    18.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235620 CKT 1   /*01SOBEND     500.0 - AD2-113 G2    18.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235621 CKT 1   /*01SOBEND     500.0 - AD2-113 G3    18.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235622 CKT 1   /*01SOBEND     500.0 - AD2-113 G4    18.0
 REMOVE MACHINE 1 FROM BUS 235619                        /*AD2-113 G1    18.0
 REMOVE MACHINE 1 FROM BUS 235620                        /*AD2-113 G2    18.0
 REMOVE MACHINE 1 FROM BUS 235621                        /*AD2-113 G3    18.0
 REMOVE MACHINE 1 FROM BUS 235622                        /*AD2-113 G4    18.0
END
CONTINGENCY 'AP_P2-3_WP-500-696_SRT-A'
 DISCONNECT BRANCH FROM BUS 235116 TO BUS 235118 CKT 1   /*01YUKON      500.0 - 01SOBEND     500.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235619 CKT 1   /*01SOBEND     500.0 - AD2-113 G1    18.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235620 CKT 1   /*01SOBEND     500.0 - AD2-113 G2    18.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235621 CKT 1   /*01SOBEND     500.0 - AD2-113 G3    18.0
 DISCONNECT BRANCH FROM BUS 235118 TO BUS 235622 CKT 1   /*01SOBEND     500.0 - AD2-113 G4    18.0
 REMOVE MACHINE 1 FROM BUS 235619                        /*AD2-113 G1    18.0
 REMOVE MACHINE 1 FROM BUS 235620                        /*AD2-113 G2    18.0
 REMOVE MACHINE 1 FROM BUS 235621                        /*AD2-113 G3    18.0
 REMOVE MACHINE 1 FROM BUS 235622                        /*AD2-113 G4    18.0
END
235173 to 235618 ckt 1
235596 to 235173 ckt 1
200762 to 235470 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-076Hunterstown-Conemaugh 500kVIn Service
AA2-133Wyalusing 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-032Church-Wye Mills 138 kVIn Service
AB2-036Church - Oil City 138kVSuspended
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-057Brunswick 26kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-172Todd 69kVIn Service
AB2-179Townsend 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-167Mark Center 69kVUnder Construction
AC1-190East New Market 69kVSuspended
AC2-009Pennington 13 kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-168Clinton 23kVIn Service
AC2-185Cedar Creek 138kV IIEngineering & Procurement
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-130Hardin Switch 345 kVIn Service
AD2-027Camden Switch 26 kVIn Service
AD2-042Camden Switch 26 kV IIIn Service
AD2-062Roxbury-Greene 138 kVSuspended
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-076Carville 138 kVSuspended
AD2-086Hardin Switch 345 kVIn Service
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-113South Bend 500kVIn Service
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-133Eagle Valley 115kVIn Service
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-104BL England 138 kVSuspended
AE1-123Emlenton 34.5 kVIn Service
AE1-129Zion View - Middletown 115 kVSuspended
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-226Face Rock-Kinzer #13 69 kVWithdrawn
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE2-001Nittany-Zion 46 kVSuspended
AE2-042Milton 69 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-074Potter 46 kVUnder Construction
AE2-084Derry Tap-Derry Bus 69 kVEngineering & Procurement
AE2-110Columbia-West Bloomsburg 69 kVSuspended
AE2-112Carville 138 kV IISuspended
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-118ABW Tap-Williamsburg 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-211Jackson-Three Mile Island 230 kVSuspended
AE2-214Cole 345 kVEngineering & Procurement
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-241Bloomsburg-Columbia 69 kVSuspended
AE2-248Fillmore-Thompson Farm 46 kVSuspended
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-271Montour 230 kVWithdrawn
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVEngineering & Procurement
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-316Brookville-Squab Hollow 138 kVUnder Construction
AE2-322Mark Center 69 kVUnder Construction
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AE2-344Edinboro South-Venango Junction 115 kVSuspended
AE2-345Hunterstown-Texas Eastern Tap 115 kVSuspended
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-036Carville 138 kV IIISuspended
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-064Weston 69 kVUnder Construction
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-106East Sayre 34.5 kVWithdrawn
AF1-120East Fayette 2 138 kVIn Service
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-167West Freedom-C&K Coal 25 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-208Laurel-Roadstown 69 kVWithdrawn
AF1-226Bowmans Mill-Scott 69 kVSuspended
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-240Timblin 34.5 kVActive
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-271AGratz 69 kVSuspended
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-287Edinboro South 34.5 kV IISuspended
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-321Hooversville 115 kV ISuspended
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-001Hooversville 115 kV IISuspended
AF2-002Hooversville 115 kV IIISuspended
AF2-010Union City-Titusville 115 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-050Bear Rock-Johnstown 230 kVActive
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-092Snake Spring-Bedford Area 23 kVSuspended
AF2-122Kirk 138 kVUnder Construction
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-165Clark Summit-Emlenton 34.5 kVIn Service
AF2-166Emlenton 34.5 kVWithdrawn
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-221Scalp Level 22.9 kVSuspended
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-254Cookstown-New Lisbon 34.5 kVSuspended
AF2-294Thompson 34.5 kVSuspended
AF2-296Madera 34.5 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-358Airey-Vienna 69 kVActive
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-445AFishbach-Port Carbon 69 kVSuspended
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-041Osterburg-Bedford North 23 kVWithdrawn
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-090Philipsburg 115 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-140Union City 34.5 kVSuspended
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-253Erie East-Union City 34.5 kVSuspended
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-362Wernersville 12.47 kVSuspended
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-377Philipsburg 115 kVActive
AG1-378Philipsburg 115 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-450Airey-Vienna 69 kV IIActive
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-487Gilbert 230 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-511Kittatinny 230 kVEngineering & Procurement
AG1-548Erie South-Union City 115 kVActive
AG1-554South Kenton 138 kVEngineering & Procurement
AG2-016Oyster Creek-Whitings 34.5 kVActive
AG2-055Deans 500 kVWithdrawn
AG2-074Meckesville Tap 69kVActive
AG2-090Scalp Level 23 kV IVActive
AG2-091Scalp Level 23 kV VActive
AG2-161Wheelabrator Frackville-Gilberton 69 kVActive
AG2-176Geneva 115 kVActive
AG2-181Airey - Golden Hill 69 kVActive
AG2-200North Warren–Russell 34.5 kVActive
AG2-206Tennessee Gas-East Towanda 115 kVActive
AG2-220East Towanda-South Troy 115 kVActive
AG2-221South Troy - North Towanda 34.5 kVActive
AG2-297Cumberland 230 kVActive
AG2-327Tennessee Gas-East Towanda 115 kVActive
AG2-347Indian River 230 kV IIActive
AG2-356South Troy - Canton 34.5 kVActive
AG2-380Carville 138 kV IVActive
AG2-418Blain 115 kVActive
AG2-420Eclipse #2 34.5 kVActive
AG2-429Burma - Armstrong 138 kVActive
AG2-430Sunbury-Dalmatia 69 kV IIActive
AG2-438Union City 34.5 kVActive
AG2-439Oxbow 34.5 kVActive
AG2-447Cedar Creek 138 kV VIIActive
AG2-456Pierce Brook-Lewis Run 230 kVActive
AG2-457Pierce Brook - Lewis Run 230 kVActive
AG2-561Glory - Glen Campbell 34.5 kVActive
AG2-615Carlos Junction-Garrett 138 kVActive
AG2-616Churchtown - Upper Pittsgrove 138 kVActive
AG2-625Pequest River-Furnace Brook Tap 34.5 kV IIActive
AG2-626Pequest River-Furnace Brook Tap 34.5 kV IIIActive
AG2-627Woodstown-High Street 69 kVActive
AG2-654Craigsville - Leards Crossing 12 kVActive
AH1-005East Towanda-South Troy 115 kV IIActive
AH1-027Cartanza 230 kVActive
AH1-050Eclipse-Piney 115 kVActive
AH1-051Eclipse-Piney 115 kV IIActive
AH1-054Upton-Whitings 34.5 kVActive
AH1-057Edgewood 12.47 kVActive
AH1-102Seward-Glory 115 kVActive
AH1-140Vasco 138 kVActive
AH1-158Eclipse-Piney 115 kV IIIActive
AH1-201Allegheny-New Baltimore 115kVActive
AH1-203Allegheny-Somerset 115 kVActive
AH1-205Allegheny-New Baltimore 115kVActive
AH1-212Bethlehem - Lilly 46 kVActive
AH1-257Broadway - Washington 34.5 kVActive
AH1-258Belford - Keansburg 34.5 kVActive
AH1-265Winslow - Monroe 69kVActive
AH1-268Seward-Glory 115 kV IIActive
AH1-274Butler 69 kVActive
AH1-313Moshannon-Milesburg 230 kV VIIActive
AH1-334Lakehurst - Whitings 34.5 kVActive
AH1-357Pierce Brook-Lewis Run 230kVActive
AH1-358Pierce Brook-Lewis Run 230kVActive
AH1-359Pierce Brook - Lewis Run 230 kVActive
AH1-360Pierce Brook - Lewis Run 230 kVActive
AH1-380Mt Olive - Kenny 69kVActive
AH1-452Clementine-Clementine Jct. 25 kVActive
AH1-460Hooversville - Scalp Level 115 kVActive
AH1-490Venango Junction 34.5 kVActive
AH1-491Union City 34.5 kVActive
AH1-536Church-Oil City 138kVActive
AH1-584Nelson-Indian River 138kVActive
AH1-585Nelson-Indian River 138kVActive
AH1-586Nelson-Indian River 138kVActive
AH1-587Farmers Valley – Ridgeway 115 kVActive
AH1-588Lewis Run - Pierce Brook 230 kVActive
AH1-589Lewis Run - Pierce Brook 230 kVActive
AH1-634Indian River 230kV IActive
AH1-641Churchtown - Upper Pittsgrove 138kVActive
AH1-667Philipsburg-Shawville 34.5 kVActive
AH1-672Farmview 138 kVActive
AH1-695Three Mile Island 230 kVActive
AH1-701Valero 69 kVActive
AH1-703Bergen 230kVActive
AH1-705Sunbury #1 500kVActive
AH1-707Saegers 230 kVActive
AH1-710Salem 500kVActive
AH1-715Linden 230kVActive
AH1-720East Towanda 230 kVActive
AH1-722Linden 230kVActive
AH1-734South Bend 500 kVActive
AH1-746Madera - Westover South 115 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V1-021Cape May County 12kVIn Service
V2-041Clayville 12kVIn Service
V2-046Pilesgrove Township 12kVIn Service
V4-054Fairfield Township 12kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-062Clayton 138kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W3-106Sussex-Wykertown 34.5kVIn Service
X2-083Newark 12kVIn Service
X3-008Todd 69kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-411 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
PENELEC(Pending) / PN-AF2-F-0039BRebuild 4.67 miles of the Penn Mar - High Point 115 kV Line.$2,705,304
PENELEC(Pending) / TC2-PN-011Replace 500/230 kV Conemaugh #3 Transformer$1,706,593
PENELECn8281Replace the Keystone #4 500/230 kV transformer with a larger unit and install a high side breaker$1,572,439
APS(Pending) / TC1-PH1-066Reconductor (Possible Rebuild) ~4.8 miles of Blairsville - Social Hall 138 kV line including (2) T-line drops at Social Hall.$1,534,022
PENELECn6858.1Reconductor 1.76 miles of the Garrett - Penn Mar 115 kV line.$1,070,543
APSn7191.1Reconductor the Garrett - Garrett Tap 115 kV Line (~2.0 miles)$982,690
PENELECn9118.0 / TC1-PN-001.gReplace disconnect switches and leads at Shelocta Substation (Homer City-Shelocta 230kV line terminal)$98,262
PENELECn9127.0 / TC1-PN-003.gReplace disconnect switches and leads at Shelocta Substation (Keystone-Shelocta 230kV line terminal)$93,548
PENELECn9117.0 / TC1-PN-001.fReplace disconnect switches at Homer City Substation (Homer City-Shelocta 230kV line terminal)$69,137
PENELECn9125.0 / TC1-PN-003.fReplace disconnect switches at Keystone Substation (Keystone-Shelocta 230kV line terminal)$65,820
PENELECn9124.0 / TC1-PN-003.eReplace bus conductor at Keystone Substation (Keystone-Shelocta 230kV line terminal)$57,948
PENELEC(Pending) / TC2-PN-005.aReplace Sub conductor at Shelocta Substation (Homer City-Shelocta 230kV line terminal)$47,925
APS(Pending) / TC2-APS-013Upgrade 138 kV Bus Risers at Garrett$41,051
PENELEC(Pending) / TC2-PN-007.bReplace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)$13,805
PENELECn9121.0 / TC1-PN-003.dReplace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)$13,521
PENELECn9120.0 / TC1-PN-003.cReplace substation conductor at Keystone substation (Keystone-Shelocta 230kV line terminal)$9,849
PENELECn9126.0 / TC1-PN-003.hReplace breaker leads at Keystone Substation (Keystone-Shelocta 230kV line terminal)$8,014
PENELEC(Pending) / TC2-PN-007.aAdjust relay settings at Keystone and Shelocta$5,430
PENELEC(Pending) / TC2-PN-005.bAdjust Relays at Shelocta Substation (Homer City-Shelocta 230kV line terminal)$2,912
Grand Total:$10,098,813

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / PN-AF2-F-0039B
Title
Rebuild 4.67 miles of the Penn Mar - High Point 115 kV Line.
Description
Total Cost ($USD)
$17,358,473
Allocated Cost ($USD)
$2,705,304
Time Estimate
20 Months

Contributor

FacilityContingency
26PENN-MAR-26HIGHPOINT 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-411
6.0 MW15.6%$2,705,304
AH1-201
4.4 MW11.4%$1,975,794
AH1-203
10.4 MW27.1%$4,696,840
AH1-205
2.0 MW5.3%$918,859
AH1-460
5.8 MW14.9%$2,592,415
AH1-588
5.4 MW14.1%$2,450,740
AH1-589
4.5 MW11.6%$2,018,521

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-011
Title
Replace 500/230 kV Conemaugh #3 Transformer
Description
Replace 500/230 kV Conemaugh #3 Transformer
Total Cost ($USD)
$28,558,871
Allocated Cost ($USD)
$1,706,593
Time Estimate
66 Months

Contributor

FacilityContingency
CONEM-GH-26CONEMAGH 500.0/230.0 kV Ckt 3 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
16.5 MW5.8%$1,644,796
AG2-411
17.1 MW6.0%$1,706,593
AG2-456
12.5 MW4.4%$1,248,996
AG2-457
12.5 MW4.4%$1,248,996
AH1-050
5.0 MW1.8%$502,748
AH1-051
3.0 MW1.1%$301,709
AH1-102
21.4 MW7.5%$2,135,683
AH1-140
13.8 MW4.8%$1,379,567
AH1-158
3.5 MW1.2%$350,748
AH1-201
8.0 MW2.8%$801,866
AH1-203
17.5 MW6.1%$1,748,356
AH1-205
3.7 MW1.3%$372,975
AH1-268
9.1 MW3.2%$908,914
AH1-313
11.9 MW4.1%$1,183,213
AH1-357
3.1 MW1.1%$312,274
AH1-358
3.6 MW1.3%$363,107
AH1-359
3.1 MW1.1%$312,274
AH1-360
3.6 MW1.3%$363,107
AH1-460
18.3 MW6.4%$1,826,300
AH1-587
30.2 MW10.6%$3,013,300
AH1-588
37.6 MW13.1%$3,747,089
AH1-589
31.0 MW10.8%$3,086,260

System Reinforcement: n8281
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n8281
Title
Replace the Keystone #4 500/230 kV transformer with a larger unit and install a high side breaker
Description
Replace the #4 500/230 kV transformer with a larger unit and install a high side breaker. Install a 230-20 kV transformer and high side breaker to serve load currently fed from existing transformer tertiary. Estimated Summer Ratings: 910/1086/1141 MVA
Total Cost ($USD)
$31,322,503
Allocated Cost ($USD)
$1,572,439
Time Estimate
67 Months

Contributor

FacilityContingency
KEYSTONE-KEYSTONE _3 500.0/230.0 kV Ckt 4 transformer(Any)
26KEYSTONE-KEYSTONE _3 230.0 kV Ckt 4 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
24.1 MW5.9%$1,841,952
AG2-411
20.6 MW5.0%$1,572,439
AG2-429
14.0 MW3.4%$1,071,784
AG2-456
18.8 MW4.6%$1,437,300
AG2-457
18.8 MW4.6%$1,437,300
AH1-050
7.3 MW1.8%$559,511
AH1-051
4.4 MW1.1%$335,706
AH1-102
25.5 MW6.2%$1,948,656
AH1-140
20.1 MW4.9%$1,537,125
AH1-158
5.1 MW1.2%$390,434
AH1-201
9.5 MW2.3%$724,153
AH1-203
20.7 MW5.1%$1,583,446
AH1-205
4.4 MW1.1%$336,776
AH1-268
10.8 MW2.6%$829,329
AH1-313
16.2 MW4.0%$1,237,650
AH1-357
4.7 MW1.1%$359,401
AH1-358
5.5 MW1.3%$417,798
AH1-359
4.7 MW1.1%$359,401
AH1-360
5.5 MW1.3%$417,798
AH1-460
21.5 MW5.3%$1,644,441
AH1-587
44.7 MW10.9%$3,416,378
AH1-588
56.4 MW13.8%$4,312,053
AH1-589
46.5 MW11.3%$3,551,669

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC1-PH1-066
Title
Reconductor (Possible Rebuild) ~4.8 miles of Blairsville - Social Hall 138 kV line including (2) T-line drops at Social Hall.
Description
Reconductor (Possible Rebuild) ~4.8 miles of Blairsville - Social Hall 138 kV line including (2) T-line drops at Social Hall.
Total Cost ($USD)
$18,224,602
Allocated Cost ($USD)
$1,534,022
Time Estimate
20 Months

Contributor

FacilityContingency
26BLAIRSVL-01SOCIAL 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-411
5.9 MW8.4%$1,534,022
AG2-456
3.5 MW5.0%$904,307
AG2-457
3.5 MW5.0%$904,307
AH1-102
9.5 MW13.5%$2,468,724
AH1-203
6.0 MW8.6%$1,561,819
AH1-268
4.0 MW5.8%$1,050,565
AH1-357
0.9 MW1.2%$226,012
AH1-358
1.0 MW1.4%$262,901
AH1-359
0.9 MW1.2%$226,012
AH1-360
1.0 MW1.4%$262,901
AH1-460
6.3 MW9.0%$1,632,480
AH1-587
8.6 MW12.3%$2,243,751
AH1-588
10.4 MW14.9%$2,712,661
AH1-589
8.6 MW12.3%$2,234,139

System Reinforcement: n6858.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6858.1
Title
Reconductor 1.76 miles of the Garrett - Penn Mar 115 kV line.
Description
Total Cost ($USD)
$6,867,997
Allocated Cost ($USD)
$1,070,543
Time Estimate
37 Months

Contributor

FacilityContingency
26PENN-MAR-26GARRETT 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-411
6.0 MW15.6%$1,070,543
AH1-201
4.4 MW11.4%$781,943
AH1-203
10.4 MW27.1%$1,858,896
AH1-205
2.0 MW5.3%$363,732
AH1-460
5.8 MW14.9%$1,026,033
AH1-588
5.4 MW14.1%$968,883
AH1-589
4.5 MW11.6%$797,967

System Reinforcement: n7191.1
Type
Load Flow
TO
APS
RTEP ID / TO ID
n7191.1
Title
Reconductor the Garrett - Garrett Tap 115 kV Line (~2.0 miles)
Description
Reconductor the Garrett - Garrett Tap 115 kV Line (~2.0 miles) using 795 kcmil ACSR
Total Cost ($USD)
$7,972,991
Allocated Cost ($USD)
$982,690
Time Estimate
37 Months

Contributor

FacilityContingency
26GARRETT-01GARRET 115.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-411
5.5 MW12.3%$982,690
AH1-201
4.7 MW10.5%$840,851
AH1-203
9.9 MW22.2%$1,772,272
AH1-205
8.7 MW19.5%$1,557,191
AH1-460
6.8 MW15.2%$1,209,740
AH1-588
4.9 MW11.1%$883,010
AH1-589
4.1 MW9.1%$727,237

System Reinforcement: n9118.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9118.0 / TC1-PN-001.g
Title
Replace disconnect switches and leads at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Note: Due to shared breaker arrangements, this cost is split 50/50 with TC1-PN-003.g (Keystone-Shelocta 230kV line terminal)
Total Cost ($USD)
$1,783,345
Allocated Cost ($USD)
$98,262
Time Estimate
26 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$110,525
AG2-411
17.6 MW5.5%$98,262
AG2-429
10.7 MW3.4%$59,973
AG2-456
16.0 MW5.0%$89,540
AG2-457
16.0 MW5.0%$89,540
AH1-050
5.4 MW1.7%$30,177
AH1-051
3.2 MW1.0%$18,109
AH1-102
16.1 MW5.0%$89,932
AH1-158
3.8 MW1.2%$21,058
AH1-201
8.1 MW2.5%$45,277
AH1-203
17.7 MW5.5%$98,945
AH1-205
3.8 MW1.2%$21,058
AH1-268
6.8 MW2.1%$38,272
AH1-313
13.0 MW4.1%$72,824
AH1-357
4.0 MW1.3%$22,384
AH1-358
4.7 MW1.5%$26,026
AH1-359
4.0 MW1.3%$22,384
AH1-360
4.7 MW1.5%$26,026
AH1-460
18.5 MW5.8%$103,342
AH1-587
37.5 MW11.8%$209,834
AH1-588
48.0 MW15.1%$268,616
AH1-589
39.5 MW12.4%$221,241

System Reinforcement: n9127.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9127.0 / TC1-PN-003.g
Title
Replace disconnect switches and leads at Shelocta Substation (Keystone-Shelocta 230kV line terminal)
Description
Note: Due to shared breaker arrangements, this cost is split 50/50 with TC1-PN-001.g (Homer City-Shelocta 230kV line) terminal)
Total Cost ($USD)
$1,783,345
Allocated Cost ($USD)
$93,548
Time Estimate
26 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$103,254
AG2-411
19.1 MW5.2%$93,548
AG2-429
12.3 MW3.4%$60,324
AG2-456
16.3 MW4.5%$79,716
AG2-457
16.3 MW4.5%$79,716
AH1-050
6.4 MW1.8%$31,460
AH1-051
3.9 MW1.1%$18,878
AH1-102
23.7 MW6.5%$116,272
AH1-140
17.9 MW4.9%$87,654
AH1-158
4.5 MW1.2%$21,950
AH1-201
8.9 MW2.4%$43,435
AH1-203
19.4 MW5.3%$94,856
AH1-205
4.1 MW1.1%$20,201
AH1-268
10.1 MW2.8%$49,481
AH1-313
14.5 MW4.0%$71,054
AH1-357
4.1 MW1.1%$19,932
AH1-358
4.7 MW1.3%$23,175
AH1-359
4.1 MW1.1%$19,932
AH1-360
4.7 MW1.3%$23,175
AH1-460
20.2 MW5.5%$98,741
AH1-587
38.9 MW10.7%$190,471
AH1-588
48.8 MW13.4%$239,149
AH1-589
40.2 MW11.0%$196,973

System Reinforcement: n9117.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9117.0 / TC1-PN-001.f
Title
Replace disconnect switches at Homer City Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$1,254,760
Allocated Cost ($USD)
$69,137
Time Estimate
24 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$77,766
AG2-411
17.6 MW5.5%$69,137
AG2-429
10.7 MW3.4%$42,197
AG2-456
16.0 MW5.0%$63,001
AG2-457
16.0 MW5.0%$63,001
AH1-050
5.4 MW1.7%$21,232
AH1-051
3.2 MW1.0%$12,742
AH1-102
16.1 MW5.0%$63,276
AH1-158
3.8 MW1.2%$14,816
AH1-201
8.1 MW2.5%$31,857
AH1-203
17.7 MW5.5%$69,617
AH1-205
3.8 MW1.2%$14,816
AH1-268
6.8 MW2.1%$26,928
AH1-313
13.0 MW4.1%$51,239
AH1-357
4.0 MW1.3%$15,749
AH1-358
4.7 MW1.5%$18,312
AH1-359
4.0 MW1.3%$15,749
AH1-360
4.7 MW1.5%$18,312
AH1-460
18.5 MW5.8%$72,711
AH1-587
37.5 MW11.8%$147,639
AH1-588
48.0 MW15.1%$188,998
AH1-589
39.5 MW12.4%$155,665

System Reinforcement: n9125.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9125.0 / TC1-PN-003.f
Title
Replace disconnect switches at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$1,254,762
Allocated Cost ($USD)
$65,820
Time Estimate
24 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$72,649
AG2-411
19.1 MW5.2%$65,820
AG2-429
12.3 MW3.4%$42,444
AG2-456
16.3 MW4.5%$56,088
AG2-457
16.3 MW4.5%$56,088
AH1-050
6.4 MW1.8%$22,135
AH1-051
3.9 MW1.1%$13,283
AH1-102
23.7 MW6.5%$81,809
AH1-140
17.9 MW4.9%$61,673
AH1-158
4.5 MW1.2%$15,444
AH1-201
8.9 MW2.4%$30,561
AH1-203
19.4 MW5.3%$66,741
AH1-205
4.1 MW1.1%$14,213
AH1-268
10.1 MW2.8%$34,815
AH1-313
14.5 MW4.0%$49,993
AH1-357
4.1 MW1.1%$14,024
AH1-358
4.7 MW1.3%$16,306
AH1-359
4.1 MW1.1%$14,024
AH1-360
4.7 MW1.3%$16,306
AH1-460
20.2 MW5.5%$69,474
AH1-587
38.9 MW10.7%$134,016
AH1-588
48.8 MW13.4%$168,265
AH1-589
40.2 MW11.0%$138,590

System Reinforcement: n9124.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9124.0 / TC1-PN-003.e
Title
Replace bus conductor at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$1,104,686
Allocated Cost ($USD)
$57,948
Time Estimate
13 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$63,960
AG2-411
19.1 MW5.2%$57,948
AG2-429
12.3 MW3.4%$37,367
AG2-456
16.3 MW4.5%$49,380
AG2-457
16.3 MW4.5%$49,380
AH1-050
6.4 MW1.8%$19,488
AH1-051
3.9 MW1.1%$11,694
AH1-102
23.7 MW6.5%$72,024
AH1-140
17.9 MW4.9%$54,297
AH1-158
4.5 MW1.2%$13,597
AH1-201
8.9 MW2.4%$26,906
AH1-203
19.4 MW5.3%$58,758
AH1-205
4.1 MW1.1%$12,513
AH1-268
10.1 MW2.8%$30,651
AH1-313
14.5 MW4.0%$44,014
AH1-357
4.1 MW1.1%$12,346
AH1-358
4.7 MW1.3%$14,356
AH1-359
4.1 MW1.1%$12,346
AH1-360
4.7 MW1.3%$14,356
AH1-460
20.2 MW5.5%$61,165
AH1-587
38.9 MW10.7%$117,987
AH1-588
48.8 MW13.4%$148,140
AH1-589
40.2 MW11.0%$122,014

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-005.a
Title
Replace Sub conductor at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$869,783
Allocated Cost ($USD)
$47,925
Time Estimate
13 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$53,906
AG2-411
17.6 MW5.5%$47,925
AG2-429
10.7 MW3.4%$29,251
AG2-456
16.0 MW5.0%$43,671
AG2-457
16.0 MW5.0%$43,671
AH1-050
5.4 MW1.7%$14,718
AH1-051
3.2 MW1.0%$8,832
AH1-102
16.1 MW5.0%$43,862
AH1-158
3.8 MW1.2%$10,270
AH1-201
8.1 MW2.5%$22,083
AH1-203
17.7 MW5.5%$48,258
AH1-205
3.8 MW1.2%$10,270
AH1-268
6.8 MW2.1%$18,666
AH1-313
13.0 MW4.1%$35,518
AH1-357
4.0 MW1.3%$10,917
AH1-358
4.7 MW1.5%$12,693
AH1-359
4.0 MW1.3%$10,917
AH1-360
4.7 MW1.5%$12,693
AH1-460
18.5 MW5.8%$50,403
AH1-587
37.5 MW11.8%$102,341
AH1-588
48.0 MW15.1%$131,011
AH1-589
39.5 MW12.4%$107,905

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-013
Title
Upgrade 138 kV Bus Risers at Garrett
Description
Upgrade 138 kV Bus Risers at Garrett
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$41,051
Time Estimate
12 Months

Contributor

FacilityContingency
01GARRET-01GARRET 138.0/115.0 kV Ckt 1 transformer(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-411
6.0 MW15.6%$41,051
AH1-201
4.4 MW11.4%$29,993
AH1-203
10.4 MW27.1%$71,304
AH1-205
2.0 MW5.3%$13,948
AH1-460
5.8 MW14.9%$39,335
AH1-588
5.4 MW14.1%$37,032
AH1-589
4.5 MW11.6%$30,506

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-007.b
Title
Replace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$13,805
Time Estimate
12 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$15,237
AG2-411
19.1 MW5.2%$13,805
AG2-429
12.3 MW3.4%$8,902
AG2-456
16.3 MW4.5%$11,764
AG2-457
16.3 MW4.5%$11,764
AH1-050
6.4 MW1.8%$4,643
AH1-051
3.9 MW1.1%$2,786
AH1-102
23.7 MW6.5%$17,158
AH1-140
17.9 MW4.9%$12,935
AH1-158
4.5 MW1.2%$3,239
AH1-201
8.9 MW2.4%$6,410
AH1-203
19.4 MW5.3%$13,998
AH1-205
4.1 MW1.1%$2,981
AH1-268
10.1 MW2.8%$7,302
AH1-313
14.5 MW4.0%$10,485
AH1-357
4.1 MW1.1%$2,941
AH1-358
4.7 MW1.3%$3,420
AH1-359
4.1 MW1.1%$2,941
AH1-360
4.7 MW1.3%$3,420
AH1-460
20.2 MW5.5%$14,571
AH1-587
38.9 MW10.7%$28,108
AH1-588
48.8 MW13.4%$35,291
AH1-589
40.2 MW11.0%$29,067

System Reinforcement: n9121.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9121.0 / TC1-PN-003.d
Title
Replace line drops at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$13,521
Time Estimate
11 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$14,924
AG2-411
19.1 MW5.2%$13,521
AG2-429
12.3 MW3.4%$8,719
AG2-456
16.3 MW4.5%$11,522
AG2-457
16.3 MW4.5%$11,522
AH1-050
6.4 MW1.8%$4,547
AH1-051
3.9 MW1.1%$2,729
AH1-102
23.7 MW6.5%$16,806
AH1-140
17.9 MW4.9%$12,669
AH1-158
4.5 MW1.2%$3,173
AH1-201
8.9 MW2.4%$6,278
AH1-203
19.4 MW5.3%$13,710
AH1-205
4.1 MW1.1%$2,920
AH1-268
10.1 MW2.8%$7,152
AH1-313
14.5 MW4.0%$10,270
AH1-357
4.1 MW1.1%$2,881
AH1-358
4.7 MW1.3%$3,350
AH1-359
4.1 MW1.1%$2,881
AH1-360
4.7 MW1.3%$3,350
AH1-460
20.2 MW5.5%$14,272
AH1-587
38.9 MW10.7%$27,530
AH1-588
48.8 MW13.4%$34,566
AH1-589
40.2 MW11.0%$28,470

System Reinforcement: n9120.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9120.0 / TC1-PN-003.c
Title
Replace substation conductor at Keystone substation (Keystone-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$187,749
Allocated Cost ($USD)
$9,849
Time Estimate
12 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$10,870
AG2-411
19.1 MW5.2%$9,849
AG2-429
12.3 MW3.4%$6,351
AG2-456
16.3 MW4.5%$8,392
AG2-457
16.3 MW4.5%$8,392
AH1-050
6.4 MW1.8%$3,312
AH1-051
3.9 MW1.1%$1,987
AH1-102
23.7 MW6.5%$12,241
AH1-140
17.9 MW4.9%$9,228
AH1-158
4.5 MW1.2%$2,311
AH1-201
8.9 MW2.4%$4,573
AH1-203
19.4 MW5.3%$9,986
AH1-205
4.1 MW1.1%$2,127
AH1-268
10.1 MW2.8%$5,209
AH1-313
14.5 MW4.0%$7,480
AH1-357
4.1 MW1.1%$2,098
AH1-358
4.7 MW1.3%$2,440
AH1-359
4.1 MW1.1%$2,098
AH1-360
4.7 MW1.3%$2,440
AH1-460
20.2 MW5.5%$10,395
AH1-587
38.9 MW10.7%$20,053
AH1-588
48.8 MW13.4%$25,177
AH1-589
40.2 MW11.0%$20,737

System Reinforcement: n9126.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9126.0 / TC1-PN-003.h
Title
Replace breaker leads at Keystone Substation (Keystone-Shelocta 230kV line terminal)
Description
None
Total Cost ($USD)
$152,770
Allocated Cost ($USD)
$8,014
Time Estimate
12 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$8,845
AG2-411
19.1 MW5.2%$8,014
AG2-429
12.3 MW3.4%$5,168
AG2-456
16.3 MW4.5%$6,829
AG2-457
16.3 MW4.5%$6,829
AH1-050
6.4 MW1.8%$2,695
AH1-051
3.9 MW1.1%$1,617
AH1-102
23.7 MW6.5%$9,960
AH1-140
17.9 MW4.9%$7,509
AH1-158
4.5 MW1.2%$1,880
AH1-201
8.9 MW2.4%$3,721
AH1-203
19.4 MW5.3%$8,126
AH1-205
4.1 MW1.1%$1,731
AH1-268
10.1 MW2.8%$4,239
AH1-313
14.5 MW4.0%$6,087
AH1-357
4.1 MW1.1%$1,707
AH1-358
4.7 MW1.3%$1,985
AH1-359
4.1 MW1.1%$1,707
AH1-360
4.7 MW1.3%$1,985
AH1-460
20.2 MW5.5%$8,459
AH1-587
38.9 MW10.7%$16,317
AH1-588
48.8 MW13.4%$20,487
AH1-589
40.2 MW11.0%$16,874

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-007.a
Title
Adjust relay settings at Keystone and Shelocta
Description
Total Cost ($USD)
$103,523
Allocated Cost ($USD)
$5,430
Time Estimate
11 Months

Contributor

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
21.1 MW5.8%$5,994
AG2-411
19.1 MW5.2%$5,430
AG2-429
12.3 MW3.4%$3,502
AG2-456
16.3 MW4.5%$4,628
AG2-457
16.3 MW4.5%$4,628
AH1-050
6.4 MW1.8%$1,826
AH1-051
3.9 MW1.1%$1,096
AH1-102
23.7 MW6.5%$6,750
AH1-140
17.9 MW4.9%$5,088
AH1-158
4.5 MW1.2%$1,274
AH1-201
8.9 MW2.4%$2,521
AH1-203
19.4 MW5.3%$5,506
AH1-205
4.1 MW1.1%$1,173
AH1-268
10.1 MW2.8%$2,872
AH1-313
14.5 MW4.0%$4,125
AH1-357
4.1 MW1.1%$1,157
AH1-358
4.7 MW1.3%$1,345
AH1-359
4.1 MW1.1%$1,157
AH1-360
4.7 MW1.3%$1,345
AH1-460
20.2 MW5.5%$5,732
AH1-587
38.9 MW10.7%$11,057
AH1-588
48.8 MW13.4%$13,883
AH1-589
40.2 MW11.0%$11,434

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending) / TC2-PN-005.b
Title
Adjust Relays at Shelocta Substation (Homer City-Shelocta 230kV line terminal)
Description
Total Cost ($USD)
$52,848
Allocated Cost ($USD)
$2,912
Time Estimate
12 Months

Contributor

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-176
19.8 MW6.2%$3,275
AG2-411
17.6 MW5.5%$2,912
AG2-429
10.7 MW3.4%$1,777
AG2-456
16.0 MW5.0%$2,653
AG2-457
16.0 MW5.0%$2,653
AH1-050
5.4 MW1.7%$894
AH1-051
3.2 MW1.0%$537
AH1-102
16.1 MW5.0%$2,665
AH1-158
3.8 MW1.2%$624
AH1-201
8.1 MW2.5%$1,342
AH1-203
17.7 MW5.5%$2,932
AH1-205
3.8 MW1.2%$624
AH1-268
6.8 MW2.1%$1,134
AH1-313
13.0 MW4.1%$2,158
AH1-357
4.0 MW1.3%$663
AH1-358
4.7 MW1.5%$771
AH1-359
4.0 MW1.3%$663
AH1-360
4.7 MW1.5%$771
AH1-460
18.5 MW5.8%$3,062
AH1-587
37.5 MW11.8%$6,218
AH1-588
48.0 MW15.1%$7,960
AH1-589
39.5 MW12.4%$6,556

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-036.b
Title
Upgrade 345/138 kV #2 Transformer at Armstrong
Description
Upgrade 345/138 kV #2 Transformer at Armstrong
Total Cost ($USD)
$13,326,308
Allocated Cost ($USD)
$0
Time Estimate
65 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 is a potential Aggregate Pool Contributor.

FacilityContingency
01ARMSTR-01ARMSTRONG 138.0/345.0 kV Ckt 2 transformer(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-036.a
Title
Upgrade/Replace (6) 138kV Substation Conductors [(2) ACSR 954 45/7 & (4) AAC 1000 37]
Description
Upgrade/Replace (6) 138kV Substation Conductors [(2) ACSR 954 45/7 & (4) AAC 1000 37]
Total Cost ($USD)
$1,084,903
Allocated Cost ($USD)
$0
Time Estimate
15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 is a potential Aggregate Pool Contributor.

FacilityContingency
01ARMSTR-01ARMSTRONG 138.0/345.0 kV Ckt 2 transformer(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-021
Title
Replace 138 kV Disc Switch at Carlos Jct T
Description
Replace 138 kV Disc Switch at Carlos Jct T
Total Cost ($USD)
$432,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 may need this upgrade in-service to be deliverable to the PJM system. If AG2-411 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01CARLOS-01DANSMTN 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / TC2-APS-018
Title
Reconductor (Possible Rebuild) ~1.18 miles of Loyalhanna - Edgewater transmission line including (3) T-line Drops at Loyalhanna
Description
Reconductor (Possible Rebuild) ~1.18 miles of Loyalhanna - Edgewater transmission line including (3) T-line Drops at Loyalhanna
Total Cost ($USD)
$5,581,666
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 may need this upgrade in-service to be deliverable to the PJM system. If AG2-411 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01EDGEWT-01LOYALH3 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / WP-AF2-F-0010
Title
Reconductor 5.1 miles of Edgewater Tap - Vasco Tap 138 kV line
Description
Reconductor 5.1 miles of Edgewater Tap - Vasco Tap 138 kV line
Total Cost ($USD)
$19,555,226
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 may need this upgrade in-service to be deliverable to the PJM system. If AG2-411 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
01EDGEWT-01VASC T 138.0 kV Ckt 1 line(Any)

System Reinforcement: n9116.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9116.0 / TC1-PN-001.d
Title
Rebuild approximately 11 miles of the Homer City-Shelocta 230 kV line with double bundled 795 kcmil 26/7 ACSS conductor
Description
Rebuild the Homer City – Shelocta 230 kV Line, approximately 11 miles, with double bunded 795 kcmil 26/7 ACSS conductor. Terminate new conductor at Homer City substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$39,312,233
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 may need this upgrade in-service to be deliverable to the PJM system. If AG2-411 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9225.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9225.0 / TC1-PN-001.e
Title
Replace 230 kV substation conductor and line drops at Shelocta substation for the Homer City-Shelocta 230 kV line terminal
Description
Replace 230 kV substation conductor and line drops at Shelocta substation for the Homer City-Shelocta 230 kV line terminal
Total Cost ($USD)
$107,569
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 may need this upgrade in-service to be deliverable to the PJM system. If AG2-411 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
26HOMER CT-26SHELOCTA 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6817.1
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n6817.1
Title
Rebuild 24.59 miles of the Lewistown-Juniata 230kV transmission line
Description
Total Cost ($USD)
$122,656,404
Allocated Cost ($USD)
$0
Time Estimate
81 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)

System Reinforcement: s0945.1
Type
Load Flow
TO
PPL
RTEP ID / TO ID
s0945.1
Title
Rebuild the Juniata 230/69 kV Substation
Description
None
Cost Information
Time Estimate
Dec 31 2025

Contingent

Note: Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 may need this upgrade in-service to be deliverable to the PJM system. If AG2-411 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)

System Reinforcement: n6818
Type
Load Flow
TO
PPL
RTEP ID / TO ID
n6818
Title
Rebuild PPL's ~0.9 miles LEWI-JUNI 230kV Line with a summer normal rating of at least 3000 Amps.
Description
The FE portion of the line is rated at 546/666 MVA SN/SE. The PPL portion is limiting, which requires n6818. Reinforcement scope no longer includes any substation scope as Juniata 230kV substation is being rebuilt under S0945.1. Actual PPL facility ratings after upgrade: 1245/1431 MVA SN/SE (FE facilities are more limiting)
Total Cost ($USD)
$3,600,000
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 is a potential Aggregate Pool Contributor.

FacilityContingency
26LEWISTWN-JUNI 230.0 kV Ckt 1 line(Any)

System Reinforcement: n9119.0
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
n9119.0 / TC1-PN-003.b
Title
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor
Description
Reconductor/Rebuild the Shelocta – Keystone 230 kV Line, approximately 2.5 miles, with 1272 kcmil 45/7 ACSR 2-conductor. Terminate new conductor at Keystone substation. Terminate new conductor at Shelocta substation.
Total Cost ($USD)
$9,533,592
Allocated Cost ($USD)
$0
Time Estimate
23 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 may need this upgrade in-service to be deliverable to the PJM system. If AG2-411 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
26SHELOCTA-26KEYSTONE 230.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
APS
RTEP ID / TO ID
(Pending) / WP-AF1-F-0001
Title
Replace Wave Trap at Keystone
Description
Upgrade/Replace Wave Trap at Keystone on the Keystone-Cabot 500kV line.
Total Cost ($USD)
$364,562
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-411 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-411 could receive cost allocation. Although AG2-411 may not presently have cost responsibility for this upgrade, AG2-411 is a potential Aggregate Pool Contributor.

FacilityContingency
KEYSTONE-01CABOT 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
PENELEC
RTEP ID / TO ID
(Pending)
Title
Single Element Derate - Eliminated by end of 2025
Description
FirstEnergy has an active internal project that will address the single element derate on the Keystone-South Bend 500kV line. This impacts the following contignencies: PN_P2-3_PN-500-DRT32_SRT-A [Breaker] and PN_P2-3_PN-500-004-DRT-002_SRT-SL [Breaker]
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
KEYSTONE-01SOBEND 500.0 kV Ckt 1 line(Any)
          New Baltimore 115kV sub - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-201, AH1-205
        
          New AG2-456 230kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AG2-456, AG2-457, AH1-357, AH1-358, AH1-359, AH1-360, AH1-588, AH1-589
        
          New AH1-050 115kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-050, AH1-051, AH1-158
        
          New AH1-102 115kV swyd - Penelec: This project's cost allocation eligibility was based on the grouped impact of all New Service Requests which shared this POI within this cycle. 
          
          The following projects shared this POI:
          AH1-102, AH1-268
        

Attachments

AG2-411 One Line Diagram

AG2-411 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.