AG2-481 Phase I Study Report

v1.00 released 2025-10-29 20:39

Derry Tap-Derry Bus 69 kV III

4.1 MW Capacity / 0.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Cottontail Solar 4, LLC , and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is PPL Electric Utilities Corporation.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed an uprate to a planned/existing Solar facility located in the PPL Electric Utilities Corporation zone — Northumberland County, Pennsylvania. This project is an increase to the developer’s AE2-059 project(s), which will share the same Point of Interconnection. The AG2-481 project is a 4.1 MW Capacity only uprate to the previous project(s). The total installed facilities will have a capability of 20.0 MW with 12.5 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-481
Project Name:
Derry Tap-Derry Bus 69 kV III
Project Developer Name:
Cottontail Solar 4, LLC
State:
Pennsylvania
County:
Northumberland
Transmission Owner:
PPL Electric Utilities Corporation
MFO:
20.0
MWE:
0.0
MWC:
4.1
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-481 will interconnect on the PPL Electric Utilities Corporation transmission system at Derry Tap-Derry Bus 69 kV III (AE2-059 TP).

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-481 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-481Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$0$0

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-481

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-481 Project due at DP1
ABA - B
AG2-481$0$20,000$0

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

No TO Interconnection Facilities or Physical Network Upgrades are required for this project.

Transmission Owner Analysis

No impacts identified by Transmission Owner

 

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. PPL interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-481 was evaluated as a 0.0 MW (4.1 MW Capacity) injection in the PPL area.

AG2-481 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 20.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2DVP
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
DVP_P1-2: LN 9354_SRT-A
SingleAC111.34 %3256.16B3625.260.42
GD2AP/PJM
CHAN-01DOUBS 500.0 kV Ckt 1 line
PECO_P1-2_5012_SRT-A
SingleAC107.27 %4150.0B4451.530.79
GD2PJM
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC129.83 %3098.0B4022.120.61
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
AP_P1-2_PE-500-3835T_SRT-A
SingleAC154.15 %3620.0B5580.170.86
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
SingleAC142.36 %3620.0B5153.540.54
GD2PJM
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Base Case
SingleAC128.38 %2920.0A3748.60.55

Details for AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line l/o DVP_P1-2: LN 9354_SRT-A


Base Case Flowgate

Area:DVP
Facility Description:
AH1-727 TP-8BRAMBLETON 500.0 kV Ckt 1 line
Contingency Name:
DVP_P1-2: LN 9354_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.34 %
Rating:3256.16 MVA
Rating Type:B
MVA to Mitigate:3625.26
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
1.087
200053ROCKSP 2
50/50
1.064
200054ROCKSP 3
50/50
1.098
200055ROCKSP 4
50/50
1.075
200203Y1-065-STG
50/50
2.985
200204Y1-065-CTG1
50/50
1.722
200205Y1-065-CTG2
50/50
1.722
23757701ROUTE 16
50/50
2.122
3147043LAWRENC
Solar/Wind Helper
0.224
3147133PAMPLIN
Solar/Wind Helper
1.143
3147133PAMPLIN
Solar/Wind Helper
0.291
3147133PAMPLIN
Solar/Wind Helper
0.364
20390526W1-045 C
Solar/Wind Harmer
0.074
23732901CHBRG_I12
50/50
3.111
20087026C_T85_W218
Adder
0.607
23776801DAM 4 HY
50/50
0.01
23777201MILVL HY
50/50
0.015
20486527WR_V4-052
Adder
0.606
20628028LAKEHURS
Adder
0.948
20628028LAKEHURS
Adder
0.479
20633028GILCT9
Adder
15.218
20635828PARLN1&2
Adder
1.714
20635828PARLN1&2
Adder
3.784
20635928PARLN3&4
Adder
1.714
20635928PARLN3&4
Adder
3.784
20636028O CRK C1
Adder
3.547
20636128O CRK C2
Adder
3.234
20671828STAW2-080
Solar/Wind Harmer
0
20671928W4-073
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
20674128FR_U2-059
Solar/Wind Harmer
0
20674328GAR_V4-001
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
20674828DL_W4-046
Solar/Wind Harmer
0
20674928WA_W3-044
Solar/Wind Harmer
0
20675128HRM_W1-127
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0
20675828AU_W4-064
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
20676128MHD_W3-029
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0
20676328BVR_Y1-020
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.077
20714428HOW_X1-037
Solar/Wind Harmer
0
20714528FRN_Y2-051
Solar/Wind Harmer
0
20714828MDF_W3-079
Solar/Wind Harmer
0.05
20714928UPF_X1-085
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0
20715828PEM_W1-120
Solar/Wind Harmer
0
20716028EGP_W2-019
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
20717128DIX_Z2-102
Solar/Wind Harmer
0
20720428HOL_W1-112
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20720728JCB_W1-129
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
207408W3-077 C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
1.37
213497CHSTR7-9
Adder
1.37
213497CHSTR7-9
Adder
1.37
213535CROYDN11
Adder
5.134
213560DLW11-12
Adder
1.365
213560DLW11-12
Adder
1.365
213561DLWR9-10
Adder
1.786
213561DLWR9-10
Adder
1.365
213587EDDYSTN3
Adder
40.035
213589EDDYSTN4
Adder
40.036
213611FALLS1-3
Adder
1.777
213611FALLS1-3
Adder
1.777
213611FALLS1-3
Adder
1.777
213815MOSER1-3
Adder
1.785
213815MOSER1-3
Adder
1.785
213815MOSER1-3
Adder
1.785
213942SCHUYLKILL
Adder
1.367
213942SCHUYLKILL
Adder
1.788
213957STHWK3-4
Adder
1.367
213957STHWK3-4
Adder
1.367
213958STHWK5-6
Adder
1.367
213958STHWK5-6
Adder
1.367
214067T20SOLAR
Solar/Wind Harmer
0
214194N WALES4
Adder
0.429
217213AMBOY SO C
Solar/Wind Harmer
0
231131BLOOM ENRGY
Adder
2.382
231907DC10
Adder
1.91
231917EM10
Adder
1.279
231918WEST 1
Adder
1.825
231919CHRIST1
Adder
2.401
231920CHRIST2
Adder
2.348
231940T-011
Adder
0.409
232404W1-003 C
Solar/Wind Harmer
0.355
232408W1-005 C
Solar/Wind Harmer
0.355
232410W1-006 C
Solar/Wind Harmer
0.355
232416X2-083
Adder
0.246
232417X3-008 C
Solar/Wind Harmer
0.001
232426Y1-080 FULL
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.001
232813VAUGHN
Adder
0.322
232901NORTHST
Adder
4.562
232904IR4
Adder
44.304
232907VN8
Adder
16.455
232910NRG_G1
Adder
4.727
232912OH NUG1
Adder
4.84
232913OH NUG2
Adder
4.775
232914OH NUG3
Adder
4.84
232915OH NUG4
Adder
4.808
232916OH NUG5
Adder
4.84
232917OH NUG6
Adder
4.818
232918OH NUG7
Adder
4.808
232919VN10
Adder
1.538
232920IR10
Adder
1.732
232921TASLEY2G
Adder
2.829
232926CRISFLD1
Adder
1.076
23776901DAM 5 HY
50/50
0.009
23777801MSM_W1-116
Solar/Wind Harmer
0.001
23777901MDS_W4-102
Solar/Wind Harmer
0.001
3137176SLIGO L2192
Solar/Wind Helper
1.694
3141426STAFORD
Solar/Wind Helper
0.119
3141906WESTMOR
Solar/Wind Helper
0.191
3142416OLDCHRC
Solar/Wind Helper
1.192
3142416OLDCHRC
Solar/Wind Helper
0.457
3142433PROV 92
Solar/Wind Helper
1.813
3142956BIRDNECK
Solar/Wind Helper
0.289
3143316POE
Solar/Wind Helper
1.719
3144356SAPONY
Solar/Wind Helper
0.744
3145506HICKORY
Solar/Wind Helper
1.712
3145506HICKORY
Solar/Wind Helper
1.027
3145506HICKORY
Solar/Wind Helper
0.257
3146386ELIZ CT
Solar/Wind Helper
0.422
3146776BUCKING
Solar/Wind Helper
1.48
3146776BUCKING
Solar/Wind Helper
0.12
3146776BUCKING
Solar/Wind Helper
0.133
3146776BUCKING
Solar/Wind Helper
0.148
209027LOR2_Q27
Solar/Wind Harmer
0.001
212266LOR1
Solar/Wind Harmer
0.261
217083KRNY_132
Adder
4.792
217083KRNY_132
Adder
4.823
217086KRNY_131
Adder
4.833
217086KRNY_131
Adder
4.782
217121ECCF
Adder
0.225
217146KRNY_1234
Adder
4.495
217146KRNY_1234
Adder
4.464
217147KRNY_1212
Adder
4.587
217147KRNY_1212
Adder
4.505
217167KRNY_14
Adder
4.823
217186ESSEX_G9
Adder
8.294
217197RE CRAN C
Solar/Wind Harmer
0
218404KENILWRTH C
Adder
0.676
218418LINDEN_G5
Adder
8.844
218419LINDEN_G6
Adder
8.844
218438BLK ROCK C
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
0.929
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219035LINDEN_G8
Adder
8.512
219036LINDEN_G7
Adder
8.635
219114HARTZY_C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0
219607WPEMNERT C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0
219612MATRIX C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
228202CUMB CT
Adder
8.306
228206SHRMN CT
Adder
8.336
228251CARLLS#4
Adder
0.317
228260V4-054C
Solar/Wind Harmer
0
228304LOGAN
Adder
12.168
228304LOGAN
Adder
10.944
228307PCLP GT
Adder
6.081
228309CCLP NUG
Adder
13.001
228309CCLP NUG
Adder
12.366
228711V2-041C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Harmer
0
316075AC2-137 C
Solar/Wind Helper
0.693
316077AC2-138 C
Solar/Wind Helper
0.439
20462827N BANGR8
Adder
0.384
20467927PC_Q59Y356
Adder
0.475
20478527GLRA_Q45
Adder
0.191
228728W1-130C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0
228732V1-021 C
Adder
0.095
3138133OCRAN
Solar/Wind Helper
0.137
3138133OCRAN
Solar/Wind Helper
0.274
3141766HARMONY
Solar/Wind Helper
0.091
3141783LANCAST
Solar/Wind Helper
0.274
3141783LANCAST
Solar/Wind Helper
0.183
3141813NORNECK
Solar/Wind Helper
0.467
3141913WHIT STONE
Solar/Wind Helper
0.456
3143226MDLTHAN
Solar/Wind Helper
0.454
3143873LANEXA
Solar/Wind Helper
0.272
3145273HOLLAND
Solar/Wind Helper
0.311
3146376EDENTON
Solar/Wind Helper
0.407
3146456SLIGO L269
Solar/Wind Helper
0.426
3146456SLIGO L269
Solar/Wind Helper
0.426
3146486SUNBURY
Solar/Wind Helper
0.421
3146486SUNBURY
Solar/Wind Helper
0.421
3146516WINFALL
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
1.351
3146516WINFALL
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.417
3146516WINFALL
Solar/Wind Helper
0.417
3146626S HERTFORD
Solar/Wind Helper
0.415
3146626S HERTFORD
Solar/Wind Helper
0.415
3146626S HERTFORD
Solar/Wind Helper
0.415
3146843MT LREL
Solar/Wind Helper
0.338
3146843MT LREL
Solar/Wind Helper
0.338
3146926FARMVIL
Solar/Wind Helper
0.223
3146926FARMVIL
Solar/Wind Helper
0.223
3147123OTTER R
Solar/Wind Helper
0.138
3147666LOUISA
Solar/Wind Helper
2.071
3147666LOUISA
Solar/Wind Helper
1.191
3147983MERCK5
Solar/Wind Helper
0.103
200034PCHBTM 2
50/50
8.509
200035PCHBTM 3
50/50
8.711
232406W1-004 FULL
Solar/Wind Harmer
0.355
232436AB1-176 C
Solar/Wind Harmer
0
200192DELTA CT1
50/50
0.816
200193DELTA CT2
50/50
0.816
200194DELTA CT3
50/50
0.816
200195DELTA ST
50/50
1.261
217194REDH C
Solar/Wind Harmer
0
3141726DUNNSVL
Solar/Wind Helper
1.862
3145663CRESWEL
Solar/Wind Helper
1.117
316034AC1-036 C
Solar/Wind Helper
0.376
316036AC1-147 C
Solar/Wind Helper
0.656
316059AD1-063 C
Solar/Wind Helper
0.458
316159AE1-175 C
Solar/Wind Helper
0.675
316240AF1-291 C
Solar/Wind Helper
0.596
316246AF1-032 C
Solar/Wind Helper
0.486
316248AF1-058 C
Solar/Wind Helper
0.437
316258AE1-075 C
Solar/Wind Helper
0.576
316305AF2-043 C
Solar/Wind Helper
0.571
316315AB2-025 C
Solar/Wind Helper
0.632
316316AC1-027 C
Solar/Wind Helper
0.678
316317KELFORD C
Solar/Wind Helper
0.319
316336AC2-165 C
Solar/Wind Helper
2.218
316382AG1-145 C
Solar/Wind Helper
0.599
316405AF2-144 C
Solar/Wind Helper
0.48
230415AB2-049 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0
207454AA2-184 E
Solar/Wind Harmer
0.001
207459AE1-142 C O1
Solar/Wind Harmer
0.001
208909MACR G3
Adder
85.656
209008PAXT IPP
Adder
1.197
209009PEIP 2
Adder
4.204
209010PEIP 1
Adder
1.905
209010PEIP 1
Adder
0.279
209010PEIP 1
Adder
0.346
209018SUNBIPCT
Adder
3.952
209023WIENIPP1
Adder
5.832
209025WIENIPP3
Adder
2.852
209025WIENIPP3
Adder
2.911
209026WIENIPP4
Adder
2.882
232424Y1-079 C
Solar/Wind Harmer
0
232899W1-062
Adder
5.27
232900DEMECSMY
Adder
5.055
232905CHERITON_25
Adder
1.344
218524CNTRALGAS1 C
Solar/Wind Harmer
0.393
218526CNTRALGAS2 C
Solar/Wind Harmer
0.393
233900O-025 C
Adder
0.645
233901CHERRYDALE C
Solar/Wind Harmer
0.001
233939AC1-091 C
Solar/Wind Harmer
0.001
233940AF2-379 C
Solar/Wind Harmer
0
233970AC1-092 C
Solar/Wind Harmer
0.001
233971AC1-093 C
Solar/Wind Harmer
0.024
233972AC1-094 C
Solar/Wind Harmer
0.172
233973AC2-185 C
Solar/Wind Harmer
0.001
212174INGE
Adder
0.592
212507AE2-042_GEN
Solar/Wind Harmer
0.327
219727YARDVSOLFA C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0
237025AB1-124 C
Solar/Wind Harmer
0.001
237030AB1-096 C
Solar/Wind Harmer
-0.004
237034AC2-136 C
Solar/Wind Harmer
0.001
237038AE2-054 C
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Helper
0.407
3130156CHOWAN
Solar/Wind Helper
0.407
3130156CHOWAN
Solar/Wind Helper
0.407
3145336SMITFLD
Solar/Wind Helper
1.737
3145336SMITFLD
Solar/Wind Helper
0.174
3148133STUARTS
Solar/Wind Helper
0.172
3141196NOKESVL
Solar/Wind Helper
2.668
3147243WELCO
Solar/Wind Helper
0.203
3141873WAN 176
Solar/Wind Helper
0.091
3143526WINTERP
Solar/Wind Helper
2.364
3143526WINTERP
Solar/Wind Helper
2.364
316411AF1-147_GEN1
Solar/Wind Helper
1.969
316415AF1-147_GEN2
Solar/Wind Helper
1.969
316404AE1-155 C
Solar/Wind Helper
3.912
316017AA1-139 ULT1
Solar/Wind Helper
1.948
316018AA1-139 ULT2
Solar/Wind Helper
1.833
316181AB2-040 GEN
Solar/Wind Helper
2.709
316033AB2-134 GEN
Solar/Wind Helper
1.514
228754AB1-001 C
Solar/Wind Harmer
0
316388AE2-253 GEN
Solar/Wind Helper
1.625
230422AE1-104_GEN1
Solar/Wind Harmer
6.804
230425AE1-104_GEN2
Solar/Wind Harmer
6.804
228351V2-046C
Solar/Wind Harmer
0
235062AE1-101 C1
Solar/Wind Harmer
0.005
205956AE1-196_GEN
Solar/Wind Harmer
0.022
3148013FISHERV
Solar/Wind Helper
0.165
3148013FISHERV
Solar/Wind Helper
0.287
3145176PASQUOTANK
Solar/Wind Helper
0.26
3132123MT JACKSON
Solar/Wind Helper
0.772
3132273ORANGE
Solar/Wind Helper
0.107
3142543TWELFTH
Solar/Wind Helper
0.043
3144303KENBRDG
Solar/Wind Helper
0.287
3147173SINAI
Solar/Wind Helper
0.325
3148463FAIRFLD
Solar/Wind Helper
0.247
237080AD1-060 GEN
Solar/Wind Harmer
0.001
235067AD1-061 GEN
Solar/Wind Harmer
0.442
237001AB1-127_GEN
Solar/Wind Harmer
0.001
237002AB1-128_GEN
Solar/Wind Harmer
0.001
238221AF1-254 C O1
Solar/Wind Harmer
0.001
238208AF1-136 C
Solar/Wind Harmer
0.001
238141AE2-333 GEN1
Solar/Wind Harmer
4.824
238142AE2-333 GEN2
Solar/Wind Harmer
4.824
235063AE1-101 C2
Solar/Wind Harmer
0.005
237085AD2-009_GEN
Solar/Wind Harmer
0.073
316484AD2-074 GEN
Solar/Wind Helper
0.891
316494AC1-189 GEN
Solar/Wind Helper
2.137
315616AA1-038_C
Solar/Wind Helper
1.121
316420AA1-050 GEN
Solar/Wind Helper
1.991
967451AG2-055 C O1
Solar/Wind Harmer
126.149
316005AA1-067
Solar/Wind Helper
0.405
233944AB2-135 GEN
Solar/Wind Harmer
0.003
233946AB2-136 GEN
Solar/Wind Harmer
0.002
316426AA2-053 GEN
Solar/Wind Helper
2.138
316190AA2-174 GEN
Solar/Wind Helper
0.025
316327AA2-057 GEN
Solar/Wind Helper
2.003
233994AC2-023 GEN
Solar/Wind Harmer
0.002
234033AF1-007_GEN
Solar/Wind Harmer
-0.001
315614AA2-178 GEN
Solar/Wind Helper
2.432
315816AE2-034 GEN
Solar/Wind Helper
1.824
316312AB1-027
Solar/Wind Helper
0.873
316049AB1-081 GEN
Solar/Wind Helper
2.071
316011AB1-132 GEN
Solar/Wind Helper
4.036
316369SG1_INVT
Solar/Wind Helper
2.117
315651AD1-115 GEN
Solar/Wind Helper
1.961
316023GEN1_S
Solar/Wind Helper
1.481
316365GEN2_N
Solar/Wind Helper
1.481
237061AD1-155 GEN
Solar/Wind Helper
0.044
237006AB1-125 GEN
Solar/Wind Harmer
0.001
23779801AA1-109
Solar/Wind Harmer
0
316487AF1-042 GEN
Solar/Wind Helper
0.466
316463AE2-346 GEN
Solar/Wind Helper
0.35
315839AE2-212 C
Solar/Wind Helper
0.591
233984AB2-036 GEN
Solar/Wind Harmer
3.977
233982AB2-133 GEN
Solar/Wind Harmer
0.002
233915AB1-141 GEN
Solar/Wind Harmer
0.14
233918AB1-142 GEN
Solar/Wind Harmer
0.14
315821AE2-092 GEN
Solar/Wind Helper
3.06
316499AE2-029_GEN
Solar/Wind Helper
0.882
233930AB2-032 GEN
Solar/Wind Harmer
0.524
233987AB2-037 GEN
Solar/Wind Harmer
0.006
315662AE1-191 GEN
Solar/Wind Helper
2.441
315666AE1-190 GEN
Solar/Wind Helper
0.61
315742AE1-103 GEN
Solar/Wind Helper
0.66
319010AE1-072 C
Solar/Wind Helper
4.86
315697AD1-025 GEN
Solar/Wind Helper
5.03
316185AD1-033 GEN
Solar/Wind Helper
2.017
233933AB2-153 GEN
Solar/Wind Harmer
0.001
233955AB2-172 GEN
Solar/Wind Harmer
0.002
315773AC2-141 GEN
Solar/Wind Helper
9.334
316280AD1-041 GEN
Solar/Wind Helper
1.526
233935AB2-179 C
Solar/Wind Harmer
0.751
234041AC1-190 GEN
Solar/Wind Harmer
3.993
316003AC1-222 GEN
Solar/Wind Helper
1.366
315722AD1-056 GEN
Solar/Wind Helper
1.901
315724AD1-057 GEN
Solar/Wind Helper
1.045
315732AD1-074 GEN1
Solar/Wind Helper
4.479
315733AD1-074 GEN2
Solar/Wind Helper
4.479
315735AD1-075 GEN1
Solar/Wind Helper
2.239
315737AD1-076 GEN
Solar/Wind Helper
3.831
316473AC1-191 GEN
Solar/Wind Helper
2.84
316478AD1-087 GEN
Solar/Wind Helper
1.805
316486AD2-202 GEN
Solar/Wind Helper
0.528
316447AC1-158 HLD
Solar/Wind Helper
7.174
316044AC1-158 PL1
Solar/Wind Helper
3.259
316045AC1-158 PL2
Solar/Wind Helper
10.434
316450AC1-158 RIC
Solar/Wind Helper
0.869
316468AD1-105 GEN
Solar/Wind Helper
2.386
316072AD1-144
Solar/Wind Helper
0.489
315687AD1-152 GEN
Solar/Wind Helper
1.887
316156AD2-030 GEN
Solar/Wind Helper
0.685
315785AD2-033 C
Solar/Wind Helper
4.18
316337AD2-073 GEN
Solar/Wind Helper
0.717
233968AD2-076_GEN
Solar/Wind Harmer
1.271
234012AE2-112_GEN
Solar/Wind Harmer
1.271
234014AF1-036_GEN
Solar/Wind Harmer
1.271
234015AF2-250 C
Solar/Wind Harmer
0
234036AF2-325 C
Solar/Wind Harmer
0
233990AG1-397 GEN
Solar/Wind Harmer
-0.087
233990AG1-397 GEN
Solar/Wind Harmer
0.746
207522AF2-254 C
Solar/Wind Harmer
0.465
207528AF2-192 GEN
Solar/Wind Harmer
0
207484AF2-139 C O1
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
6.346
207497AE2-000G2
Solar/Wind Harmer
6.346
207507AE2-000G3
Solar/Wind Harmer
6.346
207487AE2-000G4
Solar/Wind Harmer
6.346
207442AE1-156 GEN
Solar/Wind Harmer
0.031
207437AD2-070 GEN
Solar/Wind Harmer
0.035
209054AE2-059 GEN
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Helper
0.643
316313AB2-026
Solar/Wind Helper
0.64
207445AB1-138_GEN
Solar/Wind Harmer
0
209071AE2-133 GEN
Solar/Wind Harmer
0.001
209116AE2-175 GEN
Solar/Wind Harmer
0.004
209120AE2-241 GEN
Solar/Wind Harmer
0.863
209093AE2-110 GEN
Solar/Wind Harmer
0.863
3145513AHOSKIE
Solar/Wind Helper
0.383
3145513AHOSKIE
Solar/Wind Helper
0.172
233923SMA
Solar/Wind Harmer
0.003
230430AE1-229_GEN
Solar/Wind Harmer
0.008
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219908AB1-139 C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219304NAMERICA C
Solar/Wind Harmer
0.046
219921AF1-264
Solar/Wind Harmer
0
203975AE1-071-GEN
Solar/Wind Harmer
0.009
203982AD2-062_GEN
Solar/Wind Harmer
6.656
231902DC CT7
Adder
6.117
231906DC3 NUG
Adder
7.651
23572401GUILF2
50/50
0.373
23572301GUILF1
50/50
0.368
209045AE2-271 GEN
Solar/Wind Harmer
6.257
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.342
207530AG1-191 GEN
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
209130AF1-271A GEN
Solar/Wind Harmer
1.041
209142AF1-226 GEN
Solar/Wind Harmer
1.511
205932AD2-116_GEN
Solar/Wind Harmer
0.065
205941AD2-115 GEN
Solar/Wind Harmer
0.065
205943AE1-185 GEN
Solar/Wind Harmer
0.022
205975AE2-345_GEN
Solar/Wind Harmer
4.7
205967AE2-211_GEN
Solar/Wind Harmer
3.394
209059AE2-084 GEN
Solar/Wind Harmer
0.859
20464627HAM CT
Adder
2.074
20465427SHAW CT
Adder
2.07
20464827MOUNT CT
Adder
2.02
20464827MOUNT CT
Adder
2.082
209022WHFR IPP
Adder
1.757
270455AD2-022 GEN
Solar/Wind Helper
1.552
270457AD2-023 GEN
Solar/Wind Helper
1.022
205917AD1-020 ES
Solar/Wind Harmer
0.018
205916AD1-020 GEN
Solar/Wind Harmer
0.437
20464927ORTAN CT
Adder
2.063
270494AE1-108_GEN
Solar/Wind Helper
4.233
270016AE1-250 BESS
Solar/Wind Helper
0.84
270013AE1-250 PV
Solar/Wind Helper
0.84
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
1.412
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
3145746EVERETS
Solar/Wind Helper
0.355
3146206CASHIE
Solar/Wind Helper
0.389
3146206CASHIE
Solar/Wind Helper
0.389
3146206CASHIE
Solar/Wind Helper
0.389
3142666NORTHAMPTON
Solar/Wind Helper
0.376
3142666NORTHAMPTON
Solar/Wind Helper
0.376
3142666NORTHAMPTON
Solar/Wind Helper
0.376
3142666NORTHAMPTON
Solar/Wind Helper
0.226
3142666NORTHAMPTON
Solar/Wind Helper
0.376
316274AC1-208 GEN
Solar/Wind Helper
2.196
316349AD2-085 GEN
Solar/Wind Helper
1.951
3156021HOLLOMANSOL
Solar/Wind Helper
2.919
313506AB2-031 GEN
Solar/Wind Helper
1.714
316006AB2-029 C
Solar/Wind Helper
0.298
316322AB2-045
Solar/Wind Helper
0.413
316359AB2-059 GEN
Solar/Wind Helper
2.59
316131AB2-060 GEN
Solar/Wind Helper
2.165
316192AB2-158 GEN
Solar/Wind Helper
3.47
316174AB2-169 GEN
Solar/Wind Helper
0.949
316087AB2-174 GEN
Solar/Wind Helper
2.65
316132AB2-190 GEN1
Solar/Wind Helper
2.527
316458AB2-190 GEN2
Solar/Wind Helper
2.527
316129AC1-054 GEN
Solar/Wind Helper
1.784
316123AC1-075 GEN
Solar/Wind Helper
1.7
316210AC1-098 GEN
Solar/Wind Helper
2.927
316212AC1-099_GEN
Solar/Wind Helper
1.626
316118AC1-105 GEN
Solar/Wind Helper
1.287
316254AC1-120 GEN1
Solar/Wind Helper
2.637
316170AC1-121 GEN2
Solar/Wind Helper
0.879
316222AC1-221 GEN
Solar/Wind Helper
1.692
316375AC2-012 GEN
Solar/Wind Helper
1.127
316283AC2-100 C
Solar/Wind Helper
1.577
316339AD2-160 GEN
Solar/Wind Helper
1.625
316164AC1-076 GEN
Solar/Wind Helper
2.725
20635028RRCT1&2
Adder
6.035
20635028RRCT1&2
Adder
5.942
20635128RRCT3&4
Adder
5.003
20635128RRCT3&4
Adder
5.736
316239AB2-077_GEN
Solar/Wind Helper
0.476
316238AB2-078_GEN
Solar/Wind Helper
0.476
316237AB2-079_GEN
Solar/Wind Helper
0.476
316140AB2-099
Solar/Wind Helper
0.146
316223AC1-118
Solar/Wind Helper
0.729
316294AC1-161 GEN
Solar/Wind Helper
7.93
316381AD1-082 GEN
Solar/Wind Helper
2.235
316233AE1-074 FULL
Solar/Wind Helper
0.695
316236AE1-162_GEN
Solar/Wind Helper
0.583
315607AA1-063A GEN
Solar/Wind Helper
2.169
20465027TOLNA CT
Adder
2.024
20465027TOLNA CT
Adder
2.104
20465527S.RDG CT
Adder
1.504
20465527S.RDG CT
Adder
1.554
20466127PORT 5CT
Adder
14.179
20465127PORT CT
Adder
1.607
20465127PORT CT
Adder
2.132
20464727HUNTR CT
Adder
2.252
230434AG1-499 GEN
Solar/Wind Harmer
0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.393
3145543BTLEBRO
Solar/Wind Helper
0.272
3145543BTLEBRO
Solar/Wind Helper
0.34
3145543BTLEBRO
Solar/Wind Helper
0.34
3145543BTLEBRO
Solar/Wind Helper
0.34
3145593CAROLNA
Solar/Wind Helper
0.373
3145593CAROLNA
Solar/Wind Helper
0.373
3145683EARLEYS
Solar/Wind Helper
0.381
3145683EARLEYS
Solar/Wind Helper
0.381
3145683EARLEYS
Solar/Wind Helper
0.381
3145683EARLEYS
Solar/Wind Helper
0.762
200200DELTA2 CT1
50/50
1.461
200201DELTA2 CT2
50/50
1.461
200202DELTA2 ST
50/50
2.479
207511W3-106 GEN
Solar/Wind Harmer
0.172
208972BECR K09
Solar/Wind Harmer
0
209029WAYMART-WD
Solar/Wind Harmer
0.001
230407AD2-065 C
Solar/Wind Harmer
0
232422X3-066 FULL
Solar/Wind Harmer
0.046
232432Z2-076 GEN
Solar/Wind Harmer
0.007
232434Z2-077 GEN
Solar/Wind Harmer
0.023
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Helper
1.7
3137643SOCKMAN
Solar/Wind Helper
1.499
3138216PACIFIC
Solar/Wind Helper
0.07
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138266HYDRAULIC
Solar/Wind Helper
0.015
3138543CONSLDL
Solar/Wind Helper
0.228
3142946ENON
Solar/Wind Helper
0.045
3142946ENON
Solar/Wind Helper
0.151
3144536CHRHLND
Solar/Wind Helper
0.065
3144873MCLAUGH
Solar/Wind Helper
0.011
3145573BETHELC
Solar/Wind Helper
0.345
3145573BETHELC
Solar/Wind Helper
0.345
3145783HORNRTN
Solar/Wind Helper
0.371
3145796HORNRTN
Solar/Wind Helper
1.11
3145796HORNRTN
Solar/Wind Helper
1.221
3145796HORNRTN
Solar/Wind Helper
0.37
3145796HORNRTN
Solar/Wind Helper
0.37
3145796HORNRTN
Solar/Wind Helper
1.48
3145796HORNRTN
Solar/Wind Helper
1.184
3145796HORNRTN
Solar/Wind Helper
0.148
3145823KELFORD
Solar/Wind Helper
0.375
3145823KELFORD
Solar/Wind Helper
0.375
3145893MURPHYS
Solar/Wind Helper
0.557
3145893MURPHYS
Solar/Wind Helper
0.698
3145893MURPHYS
Solar/Wind Helper
0.139
3145893MURPHYS
Solar/Wind Helper
0.388
3145893MURPHYS
Solar/Wind Helper
1.551
3145893MURPHYS
Solar/Wind Helper
0.388
3145893MURPHYS
Solar/Wind Helper
1.047
3145933PARMELE
Solar/Wind Helper
0.723
3145933PARMELE
Solar/Wind Helper
0.361
3145933PARMELE
Solar/Wind Helper
0.361
3145963POPLR C
Solar/Wind Helper
0.376
3145963POPLR C
Solar/Wind Helper
0.376
3146033SCOT NK
Solar/Wind Helper
1.472
3146043SEABORD
Solar/Wind Helper
0.381
3146073TAR RVR
Solar/Wind Helper
0.345
3146083TARBORO
Solar/Wind Helper
0.345
3146083TARBORO
Solar/Wind Helper
0.345
3146173TUNIS
Solar/Wind Helper
0.385
3146173TUNIS
Solar/Wind Helper
0.385
3146173TUNIS
Solar/Wind Helper
0.385
3146173TUNIS
Solar/Wind Helper
0.385
3146233WITAKRS
Solar/Wind Helper
0.372
3146233WITAKRS
Solar/Wind Helper
1.376
3146233WITAKRS
Solar/Wind Helper
0.235
3146263WOODLND
Solar/Wind Helper
0.379
3146263WOODLND
Solar/Wind Helper
0.379
315611Z1-036_GEN2
Solar/Wind Helper
2.262
315800Z1-036_GEN1
Solar/Wind Helper
2.262
316320Y1-086
Solar/Wind Helper
0.188
316321Z2-027
Solar/Wind Helper
0.64
942461AE2-259 GEN
Solar/Wind Helper
2.476
945431AF1-208 GEN
Solar/Wind Harmer
3.029
946281AF1-292 GEN
Solar/Wind Helper
0.383
960671AF2-358 GEN
Solar/Wind Harmer
6.846
960921AF2-383 GEN
Solar/Wind Harmer
1.488
961541AF2-445A GEN
Solar/Wind Harmer
1.218
961671AG1-007 GEN
Solar/Wind Helper
0.248
961941AG1-037 GEN
Solar/Wind Helper
0.129
963071AG1-156 GEN
Solar/Wind Harmer
0.238
966871AG1-558 GEN
Solar/Wind Helper
0.626
966881AG1-559 GEN
Solar/Wind Helper
0.676
970025AG2-016 GEN
Solar/Wind Harmer
0.92
970095AG2-074 GEN
Solar/Wind Harmer
2.707
970277AG2-181 GEN
Solar/Wind Harmer
0.319
970279AG2-182 GEN
Solar/Wind Harmer
22.957
970429AG2-279 GEN
Solar/Wind Harmer
1.896
970453AG2-297 GEN
Solar/Wind Harmer
1.28
970545AG2-347 GEN
Solar/Wind Harmer
13.833
970597AG2-380 GEN
Solar/Wind Harmer
2.277
970651AG2-423 GEN
Solar/Wind Harmer
7.121
970665AG2-430 GEN
Solar/Wind Harmer
3.847
970695AG2-447 GEN
Solar/Wind Harmer
1.37
970753AG2-477 GEN
Solar/Wind Harmer
0.053
970755AG2-478 GEN
Solar/Wind Harmer
0.054
970757AG2-479 GEN
Solar/Wind Harmer
0.418
970761AG2-481 GEN
Solar/Wind Harmer
0.419
970997AG2-616 GEN
Solar/Wind Harmer
3.628
971007AG2-625 GEN
Solar/Wind Harmer
0.885
971009AG2-626 GEN
Solar/Wind Harmer
0.564
971011AG2-627 GEN
Solar/Wind Harmer
2.689
971149AH1-027 GEN
Solar/Wind Harmer
1.712
971189AH1-054 GEN
Solar/Wind Harmer
0.383
971195AH1-057 GEN
Solar/Wind Harmer
0.342
971519AH1-257 GEN
Solar/Wind Harmer
0.869
971521AH1-258 GEN
Solar/Wind Harmer
0.889
971535AH1-265 GEN
Solar/Wind Harmer
1.384
971553AH1-274 GEN
Solar/Wind Harmer
0.786
971667AH1-334 GEN
Solar/Wind Harmer
0.894
219221BRL12CT1
Adder
4.48
219222BRL12CT2
Adder
4.48
219223BRL12CT3
Adder
4.48
219224BRL12CT4
Adder
4.48
219912AD2-042 GEN
Solar/Wind Harmer
0
316431W1029_GEN1
Solar/Wind Helper
1.689
316433W1029_GEN2
Solar/Wind Helper
1.689
316435W1029_GEN3
Solar/Wind Helper
1.689
957601AF2-054 GEN
Solar/Wind Helper
0.609
957831AF2-077 GEN
Solar/Wind Helper
0.603
964001AG1-254 GEN
Solar/Wind Harmer
0.195
964211AG1-282 GEN
Solar/Wind Helper
0.628
964991AG1-363 GEN
Solar/Wind Harmer
4.225
964991AG1-363 GEN
Solar/Wind Harmer
0.001
965821AG1-450 GEN
Solar/Wind Harmer
2.853
966001AG1-469 GEN
Solar/Wind Helper
0.541
966111AG1-480 GEN
Solar/Wind Harmer
1.812
966131AG1-482 GEN
Solar/Wind Harmer
1.968
966181AG1-487 GEN
Solar/Wind Harmer
2.053
966421AG1-511 GEN
Solar/Wind Harmer
3.209
966461AG1-515 GEN
50/50
0.548
966621AG1-532 GEN
Solar/Wind Helper
0.347
971747AH1-380 GEN
Solar/Wind Harmer
1.37
971983AH1-536 GEN
Solar/Wind Harmer
0.967
972069AH1-584 GEN
Solar/Wind Harmer
3.424
972071AH1-585 GEN
Solar/Wind Harmer
3.424
972073AH1-586 GEN
Solar/Wind Harmer
5.136
972133AH1-634 GEN
Solar/Wind Harmer
2.02
972141AH1-641 GEN
Solar/Wind Harmer
1.682
972177AH1-672 GEN
Solar/Wind Harmer
5.581
972221AH1-695 GEN
Adder
81.348
972233AH1-701 GEN
Adder
2.11
972237AH1-703 GEN
Adder
5.248
972241AH1-705 GEN
Adder
3.087
972245AH1-707 GEN
Adder
2.897
972251AH1-710 GEN
Adder
24.445
972275AH1-722 GEN
Adder
16.258
972285AH1-727 GEN
50/50
184.072
233950AC2-186 GEN
Solar/Wind Harmer
0
233952AC2-187 GEN
Solar/Wind Harmer
0.001
233954AC2-188 GEN
Solar/Wind Harmer
0.001
972260AH1-715 GEN1
Adder
7.082
972261AH1-715 GEN2
Adder
8.266
G-007ALTFEXP_G-007A->PJM
CMTX
26.244
VTFLTFEXP_VFT->PJM
CMTX
70.149
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.473
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.353
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
9.941
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.75
BlueGrassPJM->LTFIMP_BlueG
CLTF
5.516
CBM NorthLTFEXP_CBM-N->PJM
CBM
45.782
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CHAN-01DOUBS 500.0 kV Ckt 1 line l/o PECO_P1-2_5012_SRT-A


Base Case Flowgate

Area:AP/PJM
Facility Description:
CHAN-01DOUBS 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5012_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.27 %
Rating:4150.0 MVA
Rating Type:B
MVA to Mitigate:4451.53
MW Contribution:0.79
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
2.849
200053ROCKSP 2
50/50
2.789
200054ROCKSP 3
50/50
2.878
200055ROCKSP 4
50/50
2.817
200203Y1-065-STG
50/50
7.823
200204Y1-065-CTG1
50/50
4.512
200205Y1-065-CTG2
50/50
4.512
3147043LAWRENC
Solar/Wind Helper
0.156
3147133PAMPLIN
Solar/Wind Helper
0.819
3147133PAMPLIN
Solar/Wind Helper
0.209
3147133PAMPLIN
Solar/Wind Helper
0.261
20328326MANOR_T86
Adder
0.126
20334726NME_Y1-047
Adder
2.451
20390726Y2-042
Adder
2.77
23546401DTGZ2-030
Solar/Wind Helper
0.089
20486527WR_V4-052
Adder
1.062
20628028LAKEHURS
Adder
2.083
20628028LAKEHURS
Adder
1.053
20633028GILCT9
Adder
30.801
20635828PARLN1&2
Adder
3.69
20635828PARLN1&2
Adder
8.147
20635928PARLN3&4
Adder
3.69
20635928PARLN3&4
Adder
8.147
20636028O CRK C1
Adder
7.835
20636128O CRK C2
Adder
7.144
20671828STAW2-080
Solar/Wind Harmer
0
20671928W4-073
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
20674128FR_U2-059
Solar/Wind Harmer
0
20674328GAR_V4-001
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
20674828DL_W4-046
Solar/Wind Harmer
0
20674928WA_W3-044
Solar/Wind Harmer
0.001
20675128HRM_W1-127
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
20675828AU_W4-064
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
20676128MHD_W3-029
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.168
20714428HOW_X1-037
Solar/Wind Harmer
0.001
20714528FRN_Y2-051
Solar/Wind Harmer
0
20714828MDF_W3-079
Solar/Wind Harmer
0.109
20714928UPF_X1-085
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
20716028EGP_W2-019
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
20717128DIX_Z2-102
Solar/Wind Harmer
0
20720428HOL_W1-112
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20720728JCB_W1-129
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
207408W3-077 C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
3.069
213497CHSTR7-9
Adder
3.069
213497CHSTR7-9
Adder
3.069
213535CROYDN11
Adder
11.416
213560DLW11-12
Adder
3.039
213560DLW11-12
Adder
3.039
213561DLWR9-10
Adder
3.975
213561DLWR9-10
Adder
3.039
213587EDDYSTN3
Adder
89.611
213589EDDYSTN4
Adder
89.617
213611FALLS1-3
Adder
3.929
213611FALLS1-3
Adder
3.929
213611FALLS1-3
Adder
3.929
213815MOSER1-3
Adder
3.964
213815MOSER1-3
Adder
3.964
213815MOSER1-3
Adder
3.964
213942SCHUYLKILL
Adder
3.048
213942SCHUYLKILL
Adder
3.986
213957STHWK3-4
Adder
3.048
213957STHWK3-4
Adder
3.048
213958STHWK5-6
Adder
3.048
213958STHWK5-6
Adder
3.048
214067T20SOLAR
Solar/Wind Harmer
0
214194N WALES4
Adder
0.947
217213AMBOY SO C
Solar/Wind Harmer
0
231131BLOOM ENRGY
Adder
5.629
231907DC10
Adder
4.514
231917EM10
Adder
2.963
231918WEST 1
Adder
4.241
231919CHRIST1
Adder
5.579
231920CHRIST2
Adder
5.455
231940T-011
Adder
0.973
232404W1-003 C
Solar/Wind Harmer
0.845
232408W1-005 C
Solar/Wind Harmer
0.845
232410W1-006 C
Solar/Wind Harmer
0.845
232416X2-083
Adder
0.576
232417X3-008 C
Solar/Wind Harmer
0.002
232426Y1-080 FULL
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.002
232813VAUGHN
Adder
0.766
232901NORTHST
Adder
10.877
232904IR4
Adder
105.52
232907VN8
Adder
39.168
232910NRG_G1
Adder
11.214
232912OH NUG1
Adder
11.524
232913OH NUG2
Adder
11.37
232914OH NUG3
Adder
11.524
232915OH NUG4
Adder
11.447
232916OH NUG5
Adder
11.524
232917OH NUG6
Adder
11.473
232918OH NUG7
Adder
11.447
232919VN10
Adder
3.659
232920IR10
Adder
4.124
232921TASLEY2G
Adder
6.735
232926CRISFLD1
Adder
2.561
23777901MDS_W4-102
Solar/Wind Helper
0.17
3137176SLIGO L2192
Solar/Wind Helper
1.083
3141426STAFORD
Solar/Wind Helper
0.066
3141906WESTMOR
Solar/Wind Helper
0.114
3142416OLDCHRC
Solar/Wind Helper
0.729
3142416OLDCHRC
Solar/Wind Helper
0.279
3142433PROV 92
Solar/Wind Helper
1.116
3142956BIRDNECK
Solar/Wind Helper
0.184
3143316POE
Solar/Wind Helper
1.085
3144356SAPONY
Solar/Wind Helper
0.483
3145506HICKORY
Solar/Wind Helper
1.091
3145506HICKORY
Solar/Wind Helper
0.654
3145506HICKORY
Solar/Wind Helper
0.164
3146386ELIZ CT
Solar/Wind Helper
0.271
3146776BUCKING
Solar/Wind Helper
1.06
3146776BUCKING
Solar/Wind Helper
0.086
3146776BUCKING
Solar/Wind Helper
0.095
3146776BUCKING
Solar/Wind Helper
0.106
209027LOR2_Q27
Solar/Wind Harmer
0.001
212266LOR1
Solar/Wind Harmer
0.497
217083KRNY_132
Adder
10.126
217083KRNY_132
Adder
10.191
217086KRNY_131
Adder
10.212
217086KRNY_131
Adder
10.104
217121ECCF
Adder
0.476
217146KRNY_1234
Adder
9.498
217146KRNY_1234
Adder
9.433
217147KRNY_1212
Adder
9.693
217147KRNY_1212
Adder
9.52
217167KRNY_14
Adder
10.191
217186ESSEX_G9
Adder
17.527
217197RE CRAN C
Solar/Wind Harmer
0
218404KENILWRTH C
Adder
1.432
218418LINDEN_G5
Adder
18.869
218419LINDEN_G6
Adder
18.869
218438BLK ROCK C
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
2
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219035LINDEN_G8
Adder
18.1
219036LINDEN_G7
Adder
18.362
219114HARTZY_C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0.001
219607WPEMNERT C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0.001
219612MATRIX C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
228202CUMB CT
Adder
18.994
228206SHRMN CT
Adder
19.049
228251CARLLS#4
Adder
0.723
228260V4-054C
Solar/Wind Harmer
0
228304LOGAN
Adder
27.574
228304LOGAN
Adder
24.8
228307PCLP GT
Adder
13.798
228309CCLP NUG
Adder
29.607
228309CCLP NUG
Adder
28.163
228711V2-041C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.051
316075AC2-137 C
Solar/Wind Helper
0.426
316077AC2-138 C
Solar/Wind Helper
0.265
20462827N BANGR8
Adder
0.78
20467927PC_Q59Y356
Adder
0.836
20478527GLRA_Q45
Adder
0.304
228728W1-130C
Solar/Wind Harmer
0.001
228729W2-030 C
Solar/Wind Harmer
0.001
228732V1-021 C
Adder
0.217
3138133OCRAN
Solar/Wind Helper
0.084
3138133OCRAN
Solar/Wind Helper
0.168
3141766HARMONY
Solar/Wind Helper
0.056
3141783LANCAST
Solar/Wind Helper
0.168
3141783LANCAST
Solar/Wind Helper
0.112
3141813NORNECK
Solar/Wind Helper
0.282
3141913WHIT STONE
Solar/Wind Helper
0.28
3143226MDLTHAN
Solar/Wind Helper
0.279
3143873LANEXA
Solar/Wind Helper
0.167
3145273HOLLAND
Solar/Wind Helper
0.202
3146376EDENTON
Solar/Wind Helper
0.268
3146456SLIGO L269
Solar/Wind Helper
0.272
3146456SLIGO L269
Solar/Wind Helper
0.272
3146486SUNBURY
Solar/Wind Helper
0.271
3146486SUNBURY
Solar/Wind Helper
0.271
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.875
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146516WINFALL
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3146626S HERTFORD
Solar/Wind Helper
0.27
3146843MT LREL
Solar/Wind Helper
0.253
3146843MT LREL
Solar/Wind Helper
0.253
3146926FARMVIL
Solar/Wind Helper
0.158
3146926FARMVIL
Solar/Wind Helper
0.158
3147123OTTER R
Solar/Wind Helper
0.138
3147312GRETNA
Solar/Wind Helper
0.046
3147312GRETNA
Solar/Wind Helper
0.183
3147666LOUISA
Solar/Wind Helper
1.161
3147666LOUISA
Solar/Wind Helper
0.668
3147983MERCK5
Solar/Wind Helper
0.105
200034PCHBTM 2
50/50
22.699
200035PCHBTM 3
50/50
23.2
232406W1-004 FULL
Solar/Wind Harmer
0.845
232436AB1-176 C
Solar/Wind Harmer
0
200192DELTA CT1
50/50
2.178
200193DELTA CT2
50/50
2.178
200194DELTA CT3
50/50
2.178
200195DELTA ST
50/50
3.366
217194REDH C
Solar/Wind Harmer
0
3141726DUNNSVL
Solar/Wind Helper
1.128
3145663CRESWEL
Solar/Wind Helper
0.745
316034AC1-036 C
Solar/Wind Helper
0.271
316036AC1-147 C
Solar/Wind Helper
0.416
316059AD1-063 C
Solar/Wind Helper
0.281
316159AE1-175 C
Solar/Wind Helper
0.42
316240AF1-291 C
Solar/Wind Helper
0.372
316246AF1-032 C
Solar/Wind Helper
0.311
316248AF1-058 C
Solar/Wind Helper
0.336
316258AE1-075 C
Solar/Wind Helper
0.375
316305AF2-043 C
Solar/Wind Helper
0.366
316315AB2-025 C
Solar/Wind Helper
0.411
316316AC1-027 C
Solar/Wind Helper
0.431
316317KELFORD C
Solar/Wind Helper
0.222
316336AC2-165 C
Solar/Wind Helper
1.47
316382AG1-145 C
Solar/Wind Helper
0.372
316405AF2-144 C
Solar/Wind Helper
0.313
230415AB2-049 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
207454AA2-184 E
Solar/Wind Harmer
0.001
207459AE1-142 C O1
Solar/Wind Harmer
0.001
208909MACR G3
Adder
173.279
209008PAXT IPP
Adder
1.813
209009PEIP 2
Adder
8.081
209010PEIP 1
Adder
3.661
209010PEIP 1
Adder
0.536
209010PEIP 1
Adder
0.666
209018SUNBIPCT
Adder
7.379
209023WIENIPP1
Adder
11.334
209025WIENIPP3
Adder
5.543
209025WIENIPP3
Adder
5.658
209026WIENIPP4
Adder
5.601
232424Y1-079 C
Solar/Wind Harmer
0.001
232899W1-062
Adder
12.553
232900DEMECSMY
Adder
12.04
232905CHERITON_25
Adder
3.201
218524CNTRALGAS1 C
Solar/Wind Harmer
0.841
218526CNTRALGAS2 C
Solar/Wind Harmer
0.843
226910AB2-157 C
Solar/Wind Helper
0.014
233900O-025 C
Adder
1.536
233901CHERRYDALE C
Solar/Wind Harmer
0.002
233939AC1-091 C
Solar/Wind Harmer
0.002
233940AF2-379 C
Solar/Wind Harmer
0
233970AC1-092 C
Solar/Wind Harmer
0.002
233971AC1-093 C
Solar/Wind Harmer
0.056
233972AC1-094 C
Solar/Wind Harmer
0.411
233973AC2-185 C
Solar/Wind Harmer
0.002
212174INGE
Adder
1.123
212507AE2-042_GEN
Solar/Wind Harmer
0.614
219727YARDVSOLFA C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
237034AC2-136 C
Solar/Wind Helper
0.207
237038AE2-054 C
Solar/Wind Helper
0.229
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3130156CHOWAN
Solar/Wind Helper
0.268
3145336SMITFLD
Solar/Wind Helper
1.097
3145336SMITFLD
Solar/Wind Helper
0.11
3148133STUARTS
Solar/Wind Helper
0.156
3146802CHATHAM
Solar/Wind Helper
0.172
3141196NOKESVL
Solar/Wind Helper
1.258
3147243WELCO
Solar/Wind Helper
0.156
3141873WAN 176
Solar/Wind Helper
0.056
3143526WINTERP
Solar/Wind Helper
1.451
3143526WINTERP
Solar/Wind Helper
1.451
316411AF1-147_GEN1
Solar/Wind Helper
1.09
316415AF1-147_GEN2
Solar/Wind Helper
1.09
316404AE1-155 C
Solar/Wind Helper
2.376
316017AA1-139 ULT1
Solar/Wind Helper
1.244
316018AA1-139 ULT2
Solar/Wind Helper
1.171
316181AB2-040 GEN
Solar/Wind Helper
1.875
316033AB2-134 GEN
Solar/Wind Helper
0.948
228754AB1-001 C
Solar/Wind Harmer
0
316388AE2-253 GEN
Solar/Wind Helper
1.037
230422AE1-104_GEN1
Solar/Wind Harmer
15.494
230425AE1-104_GEN2
Solar/Wind Harmer
15.494
228351V2-046C
Solar/Wind Harmer
0.001
203926AA2-133 GEN
Adder
2.264
3148013FISHERV
Solar/Wind Helper
0.149
3148013FISHERV
Solar/Wind Helper
0.26
3145176PASQUOTANK
Solar/Wind Helper
0.168
3132123MT JACKSON
Solar/Wind Helper
0.835
3132273ORANGE
Solar/Wind Helper
0.058
3142543TWELFTH
Solar/Wind Helper
0.027
3144303KENBRDG
Solar/Wind Helper
0.207
3147173SINAI
Solar/Wind Helper
0.25
3148463FAIRFLD
Solar/Wind Helper
0.251
237080AD1-060 GEN
Solar/Wind Helper
0.298
235067AD1-061 GEN
Solar/Wind Helper
0.416
237002AB1-128_GEN
Solar/Wind Helper
0.363
238152AF2-075_GEN
Solar/Wind Helper
0.701
238149AF1-291A_GEN
Solar/Wind Helper
0.14
238175AF1-290_GEN
Solar/Wind Helper
0.158
238221AF1-254 C O1
Solar/Wind Helper
0.248
238208AF1-136 C
Solar/Wind Helper
0.196
238147AE2-230_GEN1
Solar/Wind Helper
0.491
238148AE2-230_GEN2
Solar/Wind Helper
0.493
238169AE2-226 GEN1
Solar/Wind Helper
0.722
238170AE2-226 GEN2
Solar/Wind Helper
0.722
238108AE1-109 GEN1
Solar/Wind Helper
0.094
238109AE1-109 GEN2
Solar/Wind Helper
0.094
238110AE1-109 GEN3
Solar/Wind Helper
0.094
237085AD2-009_GEN
Solar/Wind Helper
1.357
316484AD2-074 GEN
Solar/Wind Helper
0.542
316494AC1-189 GEN
Solar/Wind Helper
1.555
315616AA1-038_C
Solar/Wind Helper
1.138
316420AA1-050 GEN
Solar/Wind Helper
1.456
967451AG2-055 C O1
Solar/Wind Harmer
273.543
316005AA1-067
Solar/Wind Helper
0.292
233944AB2-135 GEN
Solar/Wind Harmer
0.006
233946AB2-136 GEN
Solar/Wind Harmer
0.005
316426AA2-053 GEN
Solar/Wind Helper
1.486
316190AA2-174 GEN
Solar/Wind Helper
0.017
316327AA2-057 GEN
Solar/Wind Helper
1.454
233994AC2-023 GEN
Solar/Wind Harmer
0.005
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
315614AA2-178 GEN
Solar/Wind Helper
1.621
315816AE2-034 GEN
Solar/Wind Helper
1.216
316312AB1-027
Solar/Wind Helper
0.534
316049AB1-081 GEN
Solar/Wind Helper
1.537
316011AB1-132 GEN
Solar/Wind Helper
2.803
316369SG1_INVT
Solar/Wind Helper
1.326
315651AD1-115 GEN
Solar/Wind Helper
1.005
316023GEN1_S
Solar/Wind Helper
1.004
316365GEN2_N
Solar/Wind Helper
1.004
237061AD1-155 GEN
Solar/Wind Helper
0.053
316487AF1-042 GEN
Solar/Wind Helper
0.284
316463AE2-346 GEN
Solar/Wind Helper
0.24
315839AE2-212 C
Solar/Wind Helper
0.37
233984AB2-036 GEN
Solar/Wind Harmer
9.417
233982AB2-133 GEN
Solar/Wind Harmer
0.005
233915AB1-141 GEN
Solar/Wind Harmer
0.331
233918AB1-142 GEN
Solar/Wind Harmer
0.331
315821AE2-092 GEN
Solar/Wind Helper
2.433
316499AE2-029_GEN
Solar/Wind Helper
0.881
23583801GRNGAP
Solar/Wind Helper
4.398
233930AB2-032 GEN
Solar/Wind Harmer
1.235
233987AB2-037 GEN
Solar/Wind Harmer
0.014
315662AE1-191 GEN
Solar/Wind Helper
1.5
315666AE1-190 GEN
Solar/Wind Helper
0.375
315742AE1-103 GEN
Solar/Wind Helper
0.433
319010AE1-072 C
Solar/Wind Helper
3.109
315697AD1-025 GEN
Solar/Wind Helper
3.151
316185AD1-033 GEN
Solar/Wind Helper
1.283
233933AB2-153 GEN
Solar/Wind Harmer
0.002
233955AB2-172 GEN
Solar/Wind Harmer
0.004
315773AC2-141 GEN
Solar/Wind Helper
5.898
316280AD1-041 GEN
Solar/Wind Helper
0.938
233935AB2-179 C
Solar/Wind Harmer
1.748
234041AC1-190 GEN
Solar/Wind Harmer
9.496
316003AC1-222 GEN
Solar/Wind Helper
1.076
315722AD1-056 GEN
Solar/Wind Helper
1.374
315724AD1-057 GEN
Solar/Wind Helper
0.756
315732AD1-074 GEN1
Solar/Wind Helper
3.021
315733AD1-074 GEN2
Solar/Wind Helper
3.021
315735AD1-075 GEN1
Solar/Wind Helper
1.51
315737AD1-076 GEN
Solar/Wind Helper
2.584
316473AC1-191 GEN
Solar/Wind Helper
1.722
316478AD1-087 GEN
Solar/Wind Helper
1.27
316486AD2-202 GEN
Solar/Wind Helper
0.372
316447AC1-158 HLD
Solar/Wind Helper
3.655
316044AC1-158 PL1
Solar/Wind Helper
1.661
316045AC1-158 PL2
Solar/Wind Helper
5.316
316450AC1-158 RIC
Solar/Wind Helper
0.443
316468AD1-105 GEN
Solar/Wind Helper
1.419
316072AD1-144
Solar/Wind Helper
0.312
315687AD1-152 GEN
Solar/Wind Helper
1.374
316156AD2-030 GEN
Solar/Wind Helper
0.421
315785AD2-033 C
Solar/Wind Helper
3.016
316337AD2-073 GEN
Solar/Wind Helper
0.43
233968AD2-076_GEN
Solar/Wind Harmer
3.004
234012AE2-112_GEN
Solar/Wind Harmer
3.004
234014AF1-036_GEN
Solar/Wind Harmer
3.004
234015AF2-250 C
Solar/Wind Harmer
0
234036AF2-325 C
Solar/Wind Harmer
0.001
233990AG1-397 GEN
Solar/Wind Harmer
-0.208
233990AG1-397 GEN
Solar/Wind Harmer
1.776
207522AF2-254 C
Solar/Wind Harmer
1.029
207528AF2-192 GEN
Solar/Wind Harmer
0.001
207484AF2-139 C O1
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
14.018
207497AE2-000G2
Solar/Wind Harmer
14.018
207507AE2-000G3
Solar/Wind Harmer
14.018
207487AE2-000G4
Solar/Wind Harmer
14.018
207442AE1-156 GEN
Solar/Wind Harmer
0.066
226929AD2-058 GEN
Solar/Wind Helper
0.099
207437AD2-070 GEN
Solar/Wind Harmer
0.072
209054AE2-059 GEN
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Helper
0.413
316313AB2-026
Solar/Wind Helper
0.417
207445AB1-138_GEN
Solar/Wind Harmer
0.001
209071AE2-133 GEN
Solar/Wind Harmer
0.001
209116AE2-175 GEN
Solar/Wind Harmer
0.008
209120AE2-241 GEN
Solar/Wind Harmer
1.637
209093AE2-110 GEN
Solar/Wind Harmer
1.637
3145513AHOSKIE
Solar/Wind Helper
0.262
3145513AHOSKIE
Solar/Wind Helper
0.118
233923SMA
Solar/Wind Harmer
0.007
230430AE1-229_GEN
Solar/Wind Harmer
0.019
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219908AB1-139 C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0.001
219906AC1-017 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0.001
219304NAMERICA C
Solar/Wind Harmer
0.102
219921AF1-264
Solar/Wind Harmer
0
231902DC CT7
Adder
14.455
231906DC3 NUG
Adder
18.081
209045AE2-271 GEN
Solar/Wind Harmer
11.828
211065PSPA IPP
Solar/Wind Harmer
0.001
211065PSPA IPP
Solar/Wind Harmer
0.001
208862AG1-362 C
Solar/Wind Harmer
0.572
207530AG1-191 GEN
Solar/Wind Harmer
0.001
270197AD1-017 GEN1
Solar/Wind Helper
1.223
270173AC1-122 GEN
Solar/Wind Helper
1.452
230511AF1-262
Solar/Wind Harmer
0
209130AF1-271A GEN
Solar/Wind Harmer
1.943
209142AF1-226 GEN
Solar/Wind Harmer
2.865
205941AD2-115 GEN
Solar/Wind Harmer
0.119
205967AE2-211_GEN
Solar/Wind Harmer
3.731
209059AE2-084 GEN
Solar/Wind Harmer
1.611
20465427SHAW CT
Adder
4.194
209022WHFR IPP
Adder
3.354
270455AD2-022 GEN
Solar/Wind Helper
1.374
270457AD2-023 GEN
Solar/Wind Helper
0.905
270494AE1-108_GEN
Solar/Wind Helper
3.41
270016AE1-250 BESS
Solar/Wind Helper
0.845
270013AE1-250 PV
Solar/Wind Helper
0.845
270018AE2-047 C O1
Solar/Wind Helper
0.79
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
1.018
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
3145746EVERETS
Solar/Wind Helper
0.256
209067AE2-060 GEN
Solar/Wind Harmer
0.001
209137AF2-361 C
Solar/Wind Harmer
0.004
3146206CASHIE
Solar/Wind Helper
0.264
3146206CASHIE
Solar/Wind Helper
0.264
3146206CASHIE
Solar/Wind Helper
0.264
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.261
3142666NORTHAMPTON
Solar/Wind Helper
0.156
3142666NORTHAMPTON
Solar/Wind Helper
0.261
316274AC1-208 GEN
Solar/Wind Helper
1.567
316349AD2-085 GEN
Solar/Wind Helper
1.246
3156021HOLLOMANSOL
Solar/Wind Helper
1.997
313506AB2-031 GEN
Solar/Wind Helper
1.186
316006AB2-029 C
Solar/Wind Helper
0.146
316322AB2-045
Solar/Wind Helper
0.295
316359AB2-059 GEN
Solar/Wind Helper
1.922
316131AB2-060 GEN
Solar/Wind Helper
1.568
316192AB2-158 GEN
Solar/Wind Helper
1.949
316174AB2-169 GEN
Solar/Wind Helper
0.662
316087AB2-174 GEN
Solar/Wind Helper
1.83
316132AB2-190 GEN1
Solar/Wind Helper
1.578
316458AB2-190 GEN2
Solar/Wind Helper
1.578
316129AC1-054 GEN
Solar/Wind Helper
1.276
316123AC1-075 GEN
Solar/Wind Helper
1.467
316210AC1-098 GEN
Solar/Wind Helper
2.079
316212AC1-099_GEN
Solar/Wind Helper
1.155
316118AC1-105 GEN
Solar/Wind Helper
0.977
316254AC1-120 GEN1
Solar/Wind Helper
1.368
316170AC1-121 GEN2
Solar/Wind Helper
0.456
316222AC1-221 GEN
Solar/Wind Helper
1.387
316375AC2-012 GEN
Solar/Wind Helper
0.716
316283AC2-100 C
Solar/Wind Helper
1.295
316339AD2-160 GEN
Solar/Wind Helper
1.037
316164AC1-076 GEN
Solar/Wind Helper
1.419
20635028RRCT1&2
Adder
12.969
20635028RRCT1&2
Adder
12.769
20635128RRCT3&4
Adder
10.752
20635128RRCT3&4
Adder
12.326
316239AB2-077_GEN
Solar/Wind Helper
0.345
316238AB2-078_GEN
Solar/Wind Helper
0.345
316237AB2-079_GEN
Solar/Wind Helper
0.345
316140AB2-099
Solar/Wind Helper
0.1
316197AC1-042 GEN
Solar/Wind Helper
0.215
316223AC1-118
Solar/Wind Helper
0.434
316294AC1-161 GEN
Solar/Wind Helper
5.011
316381AD1-082 GEN
Solar/Wind Helper
1.417
316233AE1-074 FULL
Solar/Wind Helper
0.426
316236AE1-162_GEN
Solar/Wind Helper
0.369
315607AA1-063A GEN
Solar/Wind Helper
1.494
20465527S.RDG CT
Adder
2.633
20465527S.RDG CT
Adder
2.721
20466127PORT 5CT
Adder
28.867
20465127PORT CT
Adder
3.271
20465127PORT CT
Adder
4.34
230434AG1-499 GEN
Solar/Wind Harmer
0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.265
3145543BTLEBRO
Solar/Wind Helper
0.202
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
3145543BTLEBRO
Solar/Wind Helper
0.252
3145593CAROLNA
Solar/Wind Helper
0.26
3145593CAROLNA
Solar/Wind Helper
0.26
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.262
3145683EARLEYS
Solar/Wind Helper
0.524
200200DELTA2 CT1
50/50
3.899
200201DELTA2 CT2
50/50
3.899
200202DELTA2 ST
50/50
6.616
207511W3-106 GEN
Solar/Wind Harmer
0.357
208972BECR K09
Solar/Wind Harmer
0.001
209029WAYMART-WD
Solar/Wind Harmer
0.001
230407AD2-065 C
Solar/Wind Harmer
0
232422X3-066 FULL
Solar/Wind Harmer
0.108
232432Z2-076 GEN
Solar/Wind Harmer
0.017
232434Z2-077 GEN
Solar/Wind Harmer
0.055
233996TM1833_GEN
Solar/Wind Harmer
0.002
233997TMININ_4.2
Solar/Wind Harmer
0.002
233998TM1NIN_3.36
Solar/Wind Harmer
0.002
3130086AYDLETT
Solar/Wind Helper
1.088
3137643SOCKMAN
Solar/Wind Helper
1.042
3138216PACIFIC
Solar/Wind Helper
0.054
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.012
3138543CONSLDL
Solar/Wind Helper
0.167
3142946ENON
Solar/Wind Helper
0.028
3142946ENON
Solar/Wind Helper
0.093
3144536CHRHLND
Solar/Wind Helper
0.041
3144873MCLAUGH
Solar/Wind Helper
0.007
3145573BETHELC
Solar/Wind Helper
0.254
3145573BETHELC
Solar/Wind Helper
0.254
3145783HORNRTN
Solar/Wind Helper
0.26
3145796HORNRTN
Solar/Wind Helper
0.778
3145796HORNRTN
Solar/Wind Helper
0.856
3145796HORNRTN
Solar/Wind Helper
0.259
3145796HORNRTN
Solar/Wind Helper
0.259
3145796HORNRTN
Solar/Wind Helper
1.037
3145796HORNRTN
Solar/Wind Helper
0.83
3145796HORNRTN
Solar/Wind Helper
0.104
3145823KELFORD
Solar/Wind Helper
0.26
3145823KELFORD
Solar/Wind Helper
0.26
3145893MURPHYS
Solar/Wind Helper
0.378
3145893MURPHYS
Solar/Wind Helper
0.474
3145893MURPHYS
Solar/Wind Helper
0.094
3145893MURPHYS
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
1.054
3145893MURPHYS
Solar/Wind Helper
0.264
3145893MURPHYS
Solar/Wind Helper
0.711
3145933PARMELE
Solar/Wind Helper
0.514
3145933PARMELE
Solar/Wind Helper
0.257
3145933PARMELE
Solar/Wind Helper
0.257
3145963POPLR C
Solar/Wind Helper
0.261
3145963POPLR C
Solar/Wind Helper
0.261
3146033SCOT NK
Solar/Wind Helper
1.036
3146043SEABORD
Solar/Wind Helper
0.262
3146073TAR RVR
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3146083TARBORO
Solar/Wind Helper
0.254
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
3146173TUNIS
Solar/Wind Helper
0.263
3146233WITAKRS
Solar/Wind Helper
0.273
3146233WITAKRS
Solar/Wind Helper
1.01
3146233WITAKRS
Solar/Wind Helper
0.172
3146263WOODLND
Solar/Wind Helper
0.261
3146263WOODLND
Solar/Wind Helper
0.261
315611Z1-036_GEN2
Solar/Wind Helper
1.479
315800Z1-036_GEN1
Solar/Wind Helper
1.479
316095T157 G97
Solar/Wind Helper
1.209
316097T157 G90
Solar/Wind Helper
1.209
316320Y1-086
Solar/Wind Helper
0.121
316321Z2-027
Solar/Wind Helper
0.413
942461AE2-259 GEN
Solar/Wind Helper
1.768
945431AF1-208 GEN
Solar/Wind Harmer
6.903
946281AF1-292 GEN
Solar/Wind Helper
0.263
960671AF2-358 GEN
Solar/Wind Harmer
16.289
961541AF2-445A GEN
Solar/Wind Harmer
2.325
961671AG1-007 GEN
Solar/Wind Helper
0.182
961941AG1-037 GEN
Solar/Wind Helper
0.088
963071AG1-156 GEN
Solar/Wind Harmer
0.46
966871AG1-558 GEN
Solar/Wind Helper
0.38
966881AG1-559 GEN
Solar/Wind Helper
0.389
970025AG2-016 GEN
Solar/Wind Harmer
2.028
970095AG2-074 GEN
Solar/Wind Harmer
5.242
970277AG2-181 GEN
Solar/Wind Harmer
0.76
970453AG2-297 GEN
Solar/Wind Harmer
2.931
970545AG2-347 GEN
Solar/Wind Harmer
32.946
970597AG2-380 GEN
Solar/Wind Harmer
5.38
970665AG2-430 GEN
Solar/Wind Harmer
7.182
970695AG2-447 GEN
Solar/Wind Harmer
3.266
970757AG2-479 GEN
Solar/Wind Harmer
0.781
970761AG2-481 GEN
Solar/Wind Harmer
0.786
970997AG2-616 GEN
Solar/Wind Harmer
8.26
971007AG2-625 GEN
Solar/Wind Harmer
1.811
971009AG2-626 GEN
Solar/Wind Harmer
1.155
971011AG2-627 GEN
Solar/Wind Harmer
6.11
971149AH1-027 GEN
Solar/Wind Harmer
4.083
971189AH1-054 GEN
Solar/Wind Harmer
0.845
971195AH1-057 GEN
Solar/Wind Harmer
0.815
971519AH1-257 GEN
Solar/Wind Harmer
1.777
971521AH1-258 GEN
Solar/Wind Harmer
1.928
971535AH1-265 GEN
Solar/Wind Harmer
3.144
971553AH1-274 GEN
Solar/Wind Harmer
1.793
971667AH1-334 GEN
Solar/Wind Harmer
1.966
219221BRL12CT1
Adder
9.966
219222BRL12CT2
Adder
9.966
219223BRL12CT3
Adder
9.966
219224BRL12CT4
Adder
9.966
219912AD2-042 GEN
Solar/Wind Harmer
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.335
316431W1029_GEN1
Solar/Wind Helper
1.092
316433W1029_GEN2
Solar/Wind Helper
1.092
316435W1029_GEN3
Solar/Wind Helper
1.092
957601AF2-054 GEN
Solar/Wind Helper
0.374
957831AF2-077 GEN
Solar/Wind Helper
0.374
964001AG1-254 GEN
Solar/Wind Harmer
0.444
964211AG1-282 GEN
Solar/Wind Helper
0.38
964991AG1-363 GEN
Solar/Wind Helper
3.503
965821AG1-450 GEN
Solar/Wind Harmer
6.787
966001AG1-469 GEN
Solar/Wind Helper
0.309
966111AG1-480 GEN
Solar/Wind Harmer
3.673
966181AG1-487 GEN
Solar/Wind Harmer
4.156
966421AG1-511 GEN
Solar/Wind Harmer
6.538
966621AG1-532 GEN
Solar/Wind Helper
0.239
971747AH1-380 GEN
Solar/Wind Harmer
3.261
971983AH1-536 GEN
Solar/Wind Harmer
2.28
972069AH1-584 GEN
Solar/Wind Harmer
8.152
972071AH1-585 GEN
Solar/Wind Harmer
8.152
972073AH1-586 GEN
Solar/Wind Harmer
12.229
972133AH1-634 GEN
Solar/Wind Harmer
4.811
972141AH1-641 GEN
Solar/Wind Harmer
3.83
972177AH1-672 GEN
Solar/Wind Harmer
13.29
972221AH1-695 GEN
Adder
123.484
972233AH1-701 GEN
Adder
4.775
972237AH1-703 GEN
Adder
11.093
972241AH1-705 GEN
Adder
5.64
972245AH1-707 GEN
Adder
5.462
972251AH1-710 GEN
Adder
57.775
972275AH1-722 GEN
Adder
34.688
200917MEHOOPANY_G
Solar/Wind Harmer
0.367
970679AG2-439 GEN
Solar/Wind Harmer
0.728
970767AG2-484 GEN
Solar/Wind Harmer
0.618
972271AH1-720 GEN
Adder
6.105
941421AE2-139 GEN
Solar/Wind Harmer
0
233950AC2-186 GEN
Solar/Wind Harmer
0.001
233952AC2-187 GEN
Solar/Wind Harmer
0.002
233954AC2-188 GEN
Solar/Wind Harmer
0.002
972260AH1-715 GEN1
Adder
15.109
972261AH1-715 GEN2
Adder
17.577
G-007ALTFEXP_G-007A->PJM
CMTX
56.398
VTFLTFEXP_VFT->PJM
CMTX
148.565
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.987
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.493
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
21.603
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.56
BlueGrassPJM->LTFIMP_BlueG
CLTF
14.213
CBM NorthLTFEXP_CBM-N->PJM
CBM
83.022
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for CNASTONE-BRIGHTON 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
CNASTONE-BRIGHTON 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:129.83 %
Rating:3098.0 MVA
Rating Type:B
MVA to Mitigate:4022.12
MW Contribution:0.61
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
2.054
200053ROCKSP 2
50/50
2.01
200054ROCKSP 3
50/50
2.074
200055ROCKSP 4
50/50
2.031
200203Y1-065-STG
50/50
5.638
200204Y1-065-CTG1
50/50
3.252
200205Y1-065-CTG2
50/50
3.252
3147043LAWRENC
Solar/Wind Helper
0.137
3147133PAMPLIN
Solar/Wind Helper
0.716
3147133PAMPLIN
Solar/Wind Helper
0.182
3147133PAMPLIN
Solar/Wind Helper
0.228
20334726NME_Y1-047
Adder
2.067
20390726Y2-042
Adder
2.28
23546401DTGZ2-030
Solar/Wind Helper
0.076
20486527WR_V4-052
Adder
0.883
20628028LAKEHURS
Adder
1.568
20628028LAKEHURS
Adder
0.793
20633028GILCT9
Adder
23.692
20635828PARLN1&2
Adder
2.789
20635828PARLN1&2
Adder
6.157
20635928PARLN3&4
Adder
2.789
20635928PARLN3&4
Adder
6.157
20636028O CRK C1
Adder
5.895
20636128O CRK C2
Adder
5.374
20671828STAW2-080
Solar/Wind Harmer
0
20671928W4-073
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
20674128FR_U2-059
Solar/Wind Harmer
0
20674328GAR_V4-001
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
20674828DL_W4-046
Solar/Wind Harmer
0
20674928WA_W3-044
Solar/Wind Harmer
0.001
20675128HRM_W1-127
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
20675828AU_W4-064
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
20676128MHD_W3-029
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.127
20714428HOW_X1-037
Solar/Wind Harmer
0.001
20714528FRN_Y2-051
Solar/Wind Harmer
0
20714828MDF_W3-079
Solar/Wind Harmer
0.082
20714928UPF_X1-085
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
20716028EGP_W2-019
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
20717128DIX_Z2-102
Solar/Wind Harmer
0
20720428HOL_W1-112
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20720728JCB_W1-129
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
207408W3-077 C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
2.326
213497CHSTR7-9
Adder
2.326
213497CHSTR7-9
Adder
2.326
213535CROYDN11
Adder
8.595
213560DLW11-12
Adder
2.295
213560DLW11-12
Adder
2.295
213561DLWR9-10
Adder
3.001
213561DLWR9-10
Adder
2.295
213587EDDYSTN3
Adder
67.934
213589EDDYSTN4
Adder
67.939
213611FALLS1-3
Adder
2.961
213611FALLS1-3
Adder
2.961
213611FALLS1-3
Adder
2.961
213815MOSER1-3
Adder
2.984
213815MOSER1-3
Adder
2.984
213815MOSER1-3
Adder
2.984
213942SCHUYLKILL
Adder
2.307
213942SCHUYLKILL
Adder
3.017
213957STHWK3-4
Adder
2.306
213957STHWK3-4
Adder
2.306
213958STHWK5-6
Adder
2.306
213958STHWK5-6
Adder
2.306
214067T20SOLAR
Solar/Wind Harmer
0
214194N WALES4
Adder
0.713
217213AMBOY SO C
Solar/Wind Harmer
0
231131BLOOM ENRGY
Adder
4.204
231907DC10
Adder
3.372
231917EM10
Adder
2.23
231918WEST 1
Adder
3.189
231919CHRIST1
Adder
4.194
231920CHRIST2
Adder
4.101
231940T-011
Adder
0.724
232404W1-003 C
Solar/Wind Harmer
0.628
232408W1-005 C
Solar/Wind Harmer
0.628
232410W1-006 C
Solar/Wind Harmer
0.628
232416X2-083
Adder
0.432
232417X3-008 C
Solar/Wind Harmer
0.001
232426Y1-080 FULL
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.001
232813VAUGHN
Adder
0.57
232901NORTHST
Adder
8.077
232904IR4
Adder
78.439
232907VN8
Adder
29.134
232910NRG_G1
Adder
8.355
232912OH NUG1
Adder
8.569
232913OH NUG2
Adder
8.455
232914OH NUG3
Adder
8.569
232915OH NUG4
Adder
8.512
232916OH NUG5
Adder
8.569
232917OH NUG6
Adder
8.531
232918OH NUG7
Adder
8.512
232919VN10
Adder
2.722
232920IR10
Adder
3.066
232921TASLEY2G
Adder
5.008
232926CRISFLD1
Adder
1.904
23777901MDS_W4-102
Solar/Wind Helper
0.141
3137176SLIGO L2192
Solar/Wind Helper
0.963
3141426STAFORD
Solar/Wind Helper
0.062
3141906WESTMOR
Solar/Wind Helper
0.103
3142416OLDCHRC
Solar/Wind Helper
0.655
3142416OLDCHRC
Solar/Wind Helper
0.251
3142433PROV 92
Solar/Wind Helper
1.001
3142956BIRDNECK
Solar/Wind Helper
0.164
3143316POE
Solar/Wind Helper
0.967
3144356SAPONY
Solar/Wind Helper
0.429
3145506HICKORY
Solar/Wind Helper
0.971
3145506HICKORY
Solar/Wind Helper
0.582
3145506HICKORY
Solar/Wind Helper
0.146
3146386ELIZ CT
Solar/Wind Helper
0.241
3146776BUCKING
Solar/Wind Helper
0.929
3146776BUCKING
Solar/Wind Helper
0.075
3146776BUCKING
Solar/Wind Helper
0.084
3146776BUCKING
Solar/Wind Helper
0.093
209027LOR2_Q27
Solar/Wind Harmer
0.001
212266LOR1
Solar/Wind Harmer
0.386
217083KRNY_132
Adder
7.683
217083KRNY_132
Adder
7.733
217086KRNY_131
Adder
7.749
217086KRNY_131
Adder
7.667
217121ECCF
Adder
0.361
217146KRNY_1234
Adder
7.207
217146KRNY_1234
Adder
7.158
217147KRNY_1212
Adder
7.355
217147KRNY_1212
Adder
7.224
217167KRNY_14
Adder
7.733
217186ESSEX_G9
Adder
13.299
217197RE CRAN C
Solar/Wind Harmer
0
218404KENILWRTH C
Adder
1.086
218418LINDEN_G5
Adder
14.287
218419LINDEN_G6
Adder
14.287
218438BLK ROCK C
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
1.511
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219035LINDEN_G8
Adder
13.715
219036LINDEN_G7
Adder
13.914
219114HARTZY_C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0.001
219607WPEMNERT C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0.001
219612MATRIX C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
228202CUMB CT
Adder
14.203
228206SHRMN CT
Adder
14.248
228251CARLLS#4
Adder
0.541
228260V4-054C
Solar/Wind Harmer
0
228304LOGAN
Adder
20.69
228304LOGAN
Adder
18.608
228307PCLP GT
Adder
10.349
228309CCLP NUG
Adder
22.178
228309CCLP NUG
Adder
21.097
228711V2-041C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.042
316075AC2-137 C
Solar/Wind Helper
0.382
316077AC2-138 C
Solar/Wind Helper
0.24
20462827N BANGR8
Adder
0.598
20467927PC_Q59Y356
Adder
0.693
20478527GLRA_Q45
Adder
0.262
228728W1-130C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0.001
228732V1-021 C
Adder
0.162
3138133OCRAN
Solar/Wind Helper
0.075
3138133OCRAN
Solar/Wind Helper
0.151
3141766HARMONY
Solar/Wind Helper
0.05
3141783LANCAST
Solar/Wind Helper
0.151
3141783LANCAST
Solar/Wind Helper
0.101
3141813NORNECK
Solar/Wind Helper
0.255
3141913WHIT STONE
Solar/Wind Helper
0.251
3143226MDLTHAN
Solar/Wind Helper
0.25
3143873LANEXA
Solar/Wind Helper
0.15
3145273HOLLAND
Solar/Wind Helper
0.179
3146376EDENTON
Solar/Wind Helper
0.237
3146456SLIGO L269
Solar/Wind Helper
0.242
3146456SLIGO L269
Solar/Wind Helper
0.242
3146486SUNBURY
Solar/Wind Helper
0.241
3146486SUNBURY
Solar/Wind Helper
0.241
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.777
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146516WINFALL
Solar/Wind Helper
0.24
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146626S HERTFORD
Solar/Wind Helper
0.239
3146926FARMVIL
Solar/Wind Helper
0.139
3146926FARMVIL
Solar/Wind Helper
0.139
3147666LOUISA
Solar/Wind Helper
1.042
3147666LOUISA
Solar/Wind Helper
0.599
3147983MERCK5
Solar/Wind Helper
0.09
200034PCHBTM 2
50/50
16.275
200035PCHBTM 3
50/50
16.401
232406W1-004 FULL
Solar/Wind Harmer
0.628
232436AB1-176 C
Solar/Wind Harmer
0
200192DELTA CT1
50/50
1.562
200193DELTA CT2
50/50
1.562
200194DELTA CT3
50/50
1.562
200195DELTA ST
50/50
2.413
217194REDH C
Solar/Wind Harmer
0
3141726DUNNSVL
Solar/Wind Helper
1.018
3145663CRESWEL
Solar/Wind Helper
0.658
316034AC1-036 C
Solar/Wind Helper
0.237
316036AC1-147 C
Solar/Wind Helper
0.371
316059AD1-063 C
Solar/Wind Helper
0.253
316159AE1-175 C
Solar/Wind Helper
0.376
316240AF1-291 C
Solar/Wind Helper
0.332
316246AF1-032 C
Solar/Wind Helper
0.276
316258AE1-075 C
Solar/Wind Helper
0.333
316305AF2-043 C
Solar/Wind Helper
0.325
316315AB2-025 C
Solar/Wind Helper
0.364
316316AC1-027 C
Solar/Wind Helper
0.384
316317KELFORD C
Solar/Wind Helper
0.195
316336AC2-165 C
Solar/Wind Helper
1.302
316382AG1-145 C
Solar/Wind Helper
0.333
316405AF2-144 C
Solar/Wind Helper
0.278
230415AB2-049 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
207454AA2-184 E
Solar/Wind Harmer
0.001
207459AE1-142 C O1
Solar/Wind Harmer
0.001
208835TUHI V3-051
Solar/Wind Harmer
0.073
208835TUHI V3-051
Solar/Wind Harmer
0.073
208909MACR G3
Adder
132.886
208923BUSO V4-027
Solar/Wind Harmer
0
209008PAXT IPP
Adder
1.594
209009PEIP 2
Adder
6.269
209010PEIP 1
Adder
2.84
209010PEIP 1
Adder
0.416
209010PEIP 1
Adder
0.516
209018SUNBIPCT
Adder
5.762
209023WIENIPP1
Adder
8.764
209025WIENIPP3
Adder
4.286
209025WIENIPP3
Adder
4.375
209026WIENIPP4
Adder
4.331
209030FRFA O01
Adder
0.191
232424Y1-079 C
Solar/Wind Harmer
0.001
232899W1-062
Adder
9.327
232900DEMECSMY
Adder
8.946
232905CHERITON_25
Adder
2.38
218524CNTRALGAS1 C
Solar/Wind Harmer
0.636
218526CNTRALGAS2 C
Solar/Wind Harmer
0.637
226910AB2-157 C
Solar/Wind Helper
0.017
233900O-025 C
Adder
1.142
233901CHERRYDALE C
Solar/Wind Harmer
0.001
233939AC1-091 C
Solar/Wind Harmer
0.001
233940AF2-379 C
Solar/Wind Harmer
0
233970AC1-092 C
Solar/Wind Harmer
0.001
233971AC1-093 C
Solar/Wind Harmer
0.042
233972AC1-094 C
Solar/Wind Harmer
0.305
233973AC2-185 C
Solar/Wind Harmer
0.001
212174INGE
Adder
0.873
212507AE2-042_GEN
Solar/Wind Harmer
0.479
219727YARDVSOLFA C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3145336SMITFLD
Solar/Wind Helper
0.978
3145336SMITFLD
Solar/Wind Helper
0.098
3148133STUARTS
Solar/Wind Helper
0.134
3141196NOKESVL
Solar/Wind Helper
1.131
3141873WAN 176
Solar/Wind Helper
0.05
3143526WINTERP
Solar/Wind Helper
1.3
3143526WINTERP
Solar/Wind Helper
1.3
316411AF1-147_GEN1
Solar/Wind Helper
0.975
316415AF1-147_GEN2
Solar/Wind Helper
0.975
316404AE1-155 C
Solar/Wind Helper
2.142
316017AA1-139 ULT1
Solar/Wind Helper
1.107
316018AA1-139 ULT2
Solar/Wind Helper
1.042
316181AB2-040 GEN
Solar/Wind Helper
1.645
316033AB2-134 GEN
Solar/Wind Helper
0.847
228754AB1-001 C
Solar/Wind Harmer
0
316388AE2-253 GEN
Solar/Wind Helper
0.923
230422AE1-104_GEN1
Solar/Wind Harmer
11.594
230425AE1-104_GEN2
Solar/Wind Harmer
11.594
228351V2-046C
Solar/Wind Harmer
0.001
205956AE1-196_GEN
Solar/Wind Harmer
0.025
3148013FISHERV
Solar/Wind Helper
0.129
3148013FISHERV
Solar/Wind Helper
0.224
3145176PASQUOTANK
Solar/Wind Helper
0.149
3132123MT JACKSON
Solar/Wind Helper
0.716
3132273ORANGE
Solar/Wind Helper
0.052
3142543TWELFTH
Solar/Wind Helper
0.024
3144303KENBRDG
Solar/Wind Helper
0.181
238152AF2-075_GEN
Solar/Wind Helper
0.6
238149AF1-291A_GEN
Solar/Wind Helper
0.12
238175AF1-290_GEN
Solar/Wind Helper
0.135
238147AE2-230_GEN1
Solar/Wind Helper
0.42
238148AE2-230_GEN2
Solar/Wind Helper
0.422
238169AE2-226 GEN1
Solar/Wind Helper
0.616
238170AE2-226 GEN2
Solar/Wind Helper
0.616
316484AD2-074 GEN
Solar/Wind Helper
0.489
967451AG2-055 C O1
Solar/Wind Harmer
206.325
316005AA1-067
Solar/Wind Helper
0.255
233944AB2-135 GEN
Solar/Wind Harmer
0.005
233946AB2-136 GEN
Solar/Wind Harmer
0.004
316426AA2-053 GEN
Solar/Wind Helper
1.303
316190AA2-174 GEN
Solar/Wind Helper
0.015
233994AC2-023 GEN
Solar/Wind Harmer
0.004
234033AF1-007_GEN
Solar/Wind Harmer
-0.001
315614AA2-178 GEN
Solar/Wind Helper
1.431
315816AE2-034 GEN
Solar/Wind Helper
1.074
316312AB1-027
Solar/Wind Helper
0.48
316011AB1-132 GEN
Solar/Wind Helper
2.458
316369SG1_INVT
Solar/Wind Helper
1.184
315651AD1-115 GEN
Solar/Wind Helper
0.904
316023GEN1_S
Solar/Wind Helper
0.884
316365GEN2_N
Solar/Wind Helper
0.884
237061AD1-155 GEN
Solar/Wind Helper
0.046
316487AF1-042 GEN
Solar/Wind Helper
0.256
316463AE2-346 GEN
Solar/Wind Helper
0.211
315839AE2-212 C
Solar/Wind Helper
0.331
233984AB2-036 GEN
Solar/Wind Harmer
7.028
233982AB2-133 GEN
Solar/Wind Harmer
0.004
233915AB1-141 GEN
Solar/Wind Harmer
0.247
233918AB1-142 GEN
Solar/Wind Harmer
0.247
315821AE2-092 GEN
Solar/Wind Helper
2.114
316499AE2-029_GEN
Solar/Wind Helper
0.756
233930AB2-032 GEN
Solar/Wind Harmer
0.925
233987AB2-037 GEN
Solar/Wind Harmer
0.01
315662AE1-191 GEN
Solar/Wind Helper
1.348
315666AE1-190 GEN
Solar/Wind Helper
0.337
315742AE1-103 GEN
Solar/Wind Helper
0.383
319010AE1-072 C
Solar/Wind Helper
2.765
315697AD1-025 GEN
Solar/Wind Helper
2.814
316185AD1-033 GEN
Solar/Wind Helper
1.142
233933AB2-153 GEN
Solar/Wind Harmer
0.001
233955AB2-172 GEN
Solar/Wind Harmer
0.003
315773AC2-141 GEN
Solar/Wind Helper
5.257
316280AD1-041 GEN
Solar/Wind Helper
0.842
233935AB2-179 C
Solar/Wind Harmer
1.318
234041AC1-190 GEN
Solar/Wind Harmer
7.067
315732AD1-074 GEN1
Solar/Wind Helper
2.662
315733AD1-074 GEN2
Solar/Wind Helper
2.662
315735AD1-075 GEN1
Solar/Wind Helper
1.331
315737AD1-076 GEN
Solar/Wind Helper
2.277
316473AC1-191 GEN
Solar/Wind Helper
1.551
316478AD1-087 GEN
Solar/Wind Helper
1.112
316486AD2-202 GEN
Solar/Wind Helper
0.326
316447AC1-158 HLD
Solar/Wind Helper
3.301
316044AC1-158 PL1
Solar/Wind Helper
1.5
316045AC1-158 PL2
Solar/Wind Helper
4.801
316450AC1-158 RIC
Solar/Wind Helper
0.4
316468AD1-105 GEN
Solar/Wind Helper
1.287
316072AD1-144
Solar/Wind Helper
0.277
316156AD2-030 GEN
Solar/Wind Helper
0.378
315785AD2-033 C
Solar/Wind Helper
2.632
316337AD2-073 GEN
Solar/Wind Helper
0.39
233968AD2-076_GEN
Solar/Wind Harmer
2.245
234012AE2-112_GEN
Solar/Wind Harmer
2.245
234014AF1-036_GEN
Solar/Wind Harmer
2.245
234015AF2-250 C
Solar/Wind Harmer
0
234036AF2-325 C
Solar/Wind Harmer
0.001
233990AG1-397 GEN
Solar/Wind Harmer
-0.155
233990AG1-397 GEN
Solar/Wind Harmer
1.321
207522AF2-254 C
Solar/Wind Harmer
0.774
207528AF2-192 GEN
Solar/Wind Harmer
0.001
207484AF2-139 C O1
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
10.546
207497AE2-000G2
Solar/Wind Harmer
10.546
207507AE2-000G3
Solar/Wind Harmer
10.546
207487AE2-000G4
Solar/Wind Harmer
10.546
207442AE1-156 GEN
Solar/Wind Harmer
0.05
226929AD2-058 GEN
Solar/Wind Helper
0.119
207437AD2-070 GEN
Solar/Wind Harmer
0.055
209054AE2-059 GEN
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Helper
0.367
316313AB2-026
Solar/Wind Helper
0.37
207445AB1-138_GEN
Solar/Wind Harmer
0.001
209071AE2-133 GEN
Solar/Wind Harmer
0.001
209116AE2-175 GEN
Solar/Wind Harmer
0.006
209120AE2-241 GEN
Solar/Wind Harmer
1.273
209093AE2-110 GEN
Solar/Wind Harmer
1.273
3145513AHOSKIE
Solar/Wind Helper
0.231
3145513AHOSKIE
Solar/Wind Helper
0.103
233923SMA
Solar/Wind Harmer
0.005
230430AE1-229_GEN
Solar/Wind Harmer
0.014
208856AE1-226 GEN
Solar/Wind Harmer
0.966
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219908AB1-139 C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219304NAMERICA C
Solar/Wind Harmer
0.077
219921AF1-264
Solar/Wind Harmer
0
231902DC CT7
Adder
10.797
231906DC3 NUG
Adder
13.506
209045AE2-271 GEN
Solar/Wind Harmer
9.207
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
208862AG1-362 C
Solar/Wind Harmer
0.49
207530AG1-191 GEN
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
209130AF1-271A GEN
Solar/Wind Harmer
1.517
209142AF1-226 GEN
Solar/Wind Harmer
2.228
205932AD2-116_GEN
Solar/Wind Harmer
0.073
205941AD2-115 GEN
Solar/Wind Harmer
0.096
205943AE1-185 GEN
Solar/Wind Harmer
0.025
205967AE2-211_GEN
Solar/Wind Harmer
3.969
209059AE2-084 GEN
Solar/Wind Harmer
1.257
20465427SHAW CT
Adder
3.214
20464827MOUNT CT
Adder
1.876
20464827MOUNT CT
Adder
1.933
209022WHFR IPP
Adder
2.605
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.887
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
3145746EVERETS
Solar/Wind Helper
0.223
209067AE2-060 GEN
Solar/Wind Harmer
0.001
209137AF2-361 C
Solar/Wind Harmer
0.003
3146206CASHIE
Solar/Wind Helper
0.232
3146206CASHIE
Solar/Wind Helper
0.232
3146206CASHIE
Solar/Wind Helper
0.232
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.229
3142666NORTHAMPTON
Solar/Wind Helper
0.137
3142666NORTHAMPTON
Solar/Wind Helper
0.229
316274AC1-208 GEN
Solar/Wind Helper
1.368
316349AD2-085 GEN
Solar/Wind Helper
1.108
3156021HOLLOMANSOL
Solar/Wind Helper
1.756
313506AB2-031 GEN
Solar/Wind Helper
1.041
316006AB2-029 C
Solar/Wind Helper
0.131
316322AB2-045
Solar/Wind Helper
0.259
316131AB2-060 GEN
Solar/Wind Helper
1.367
316192AB2-158 GEN
Solar/Wind Helper
1.749
316174AB2-169 GEN
Solar/Wind Helper
0.58
316087AB2-174 GEN
Solar/Wind Helper
1.606
316132AB2-190 GEN1
Solar/Wind Helper
1.41
316458AB2-190 GEN2
Solar/Wind Helper
1.41
316129AC1-054 GEN
Solar/Wind Helper
1.114
316210AC1-098 GEN
Solar/Wind Helper
1.817
316212AC1-099_GEN
Solar/Wind Helper
1.01
316254AC1-120 GEN1
Solar/Wind Helper
1.229
316170AC1-121 GEN2
Solar/Wind Helper
0.41
316375AC2-012 GEN
Solar/Wind Helper
0.638
316339AD2-160 GEN
Solar/Wind Helper
0.923
316164AC1-076 GEN
Solar/Wind Helper
1.279
20635028RRCT1&2
Adder
9.805
20635028RRCT1&2
Adder
9.654
20635128RRCT3&4
Adder
8.129
20635128RRCT3&4
Adder
9.319
316239AB2-077_GEN
Solar/Wind Helper
0.301
316238AB2-078_GEN
Solar/Wind Helper
0.301
316237AB2-079_GEN
Solar/Wind Helper
0.301
316140AB2-099
Solar/Wind Helper
0.088
316223AC1-118
Solar/Wind Helper
0.394
316294AC1-161 GEN
Solar/Wind Helper
4.467
316381AD1-082 GEN
Solar/Wind Helper
1.262
316233AE1-074 FULL
Solar/Wind Helper
0.382
316236AE1-162_GEN
Solar/Wind Helper
0.329
315607AA1-063A GEN
Solar/Wind Helper
1.312
20465027TOLNA CT
Adder
2.276
20465027TOLNA CT
Adder
2.366
20465527S.RDG CT
Adder
2.192
20465527S.RDG CT
Adder
2.265
20466127PORT 5CT
Adder
22.104
20465127PORT CT
Adder
2.505
20465127PORT CT
Adder
3.325
230434AG1-499 GEN
Solar/Wind Harmer
0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.228
3145593CAROLNA
Solar/Wind Helper
0.228
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.23
3145683EARLEYS
Solar/Wind Helper
0.46
200200DELTA2 CT1
50/50
2.795
200201DELTA2 CT2
50/50
2.795
200202DELTA2 ST
50/50
4.743
207511W3-106 GEN
Solar/Wind Harmer
0.272
208972BECR K09
Solar/Wind Harmer
0
209029WAYMART-WD
Solar/Wind Harmer
0.001
230407AD2-065 C
Solar/Wind Harmer
0
232422X3-066 FULL
Solar/Wind Harmer
0.081
232432Z2-076 GEN
Solar/Wind Harmer
0.013
232434Z2-077 GEN
Solar/Wind Harmer
0.041
233996TM1833_GEN
Solar/Wind Harmer
0.001
233997TMININ_4.2
Solar/Wind Harmer
0.001
233998TM1NIN_3.36
Solar/Wind Harmer
0.001
3130086AYDLETT
Solar/Wind Helper
0.968
3137643SOCKMAN
Solar/Wind Helper
0.914
3138216PACIFIC
Solar/Wind Helper
0.049
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.01
3142946ENON
Solar/Wind Helper
0.025
3142946ENON
Solar/Wind Helper
0.083
3144536CHRHLND
Solar/Wind Helper
0.037
3144873MCLAUGH
Solar/Wind Helper
0.006
3145783HORNRTN
Solar/Wind Helper
0.228
3145796HORNRTN
Solar/Wind Helper
0.681
3145796HORNRTN
Solar/Wind Helper
0.749
3145796HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.227
3145796HORNRTN
Solar/Wind Helper
0.908
3145796HORNRTN
Solar/Wind Helper
0.727
3145796HORNRTN
Solar/Wind Helper
0.091
3145823KELFORD
Solar/Wind Helper
0.228
3145823KELFORD
Solar/Wind Helper
0.228
3145893MURPHYS
Solar/Wind Helper
0.333
3145893MURPHYS
Solar/Wind Helper
0.418
3145893MURPHYS
Solar/Wind Helper
0.083
3145893MURPHYS
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.928
3145893MURPHYS
Solar/Wind Helper
0.232
3145893MURPHYS
Solar/Wind Helper
0.626
3145933PARMELE
Solar/Wind Helper
0.449
3145933PARMELE
Solar/Wind Helper
0.225
3145933PARMELE
Solar/Wind Helper
0.225
3145963POPLR C
Solar/Wind Helper
0.229
3145963POPLR C
Solar/Wind Helper
0.229
3146033SCOT NK
Solar/Wind Helper
0.906
3146043SEABORD
Solar/Wind Helper
0.23
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146173TUNIS
Solar/Wind Helper
0.231
3146263WOODLND
Solar/Wind Helper
0.23
3146263WOODLND
Solar/Wind Helper
0.23
315611Z1-036_GEN2
Solar/Wind Helper
1.31
315800Z1-036_GEN1
Solar/Wind Helper
1.31
316320Y1-086
Solar/Wind Helper
0.108
316321Z2-027
Solar/Wind Helper
0.367
942461AE2-259 GEN
Solar/Wind Helper
1.547
945431AF1-208 GEN
Solar/Wind Harmer
5.168
946281AF1-292 GEN
Solar/Wind Helper
0.231
960671AF2-358 GEN
Solar/Wind Harmer
12.119
960921AF2-383 GEN
Solar/Wind Harmer
1.674
961541AF2-445A GEN
Solar/Wind Harmer
1.806
961941AG1-037 GEN
Solar/Wind Helper
0.078
963071AG1-156 GEN
Solar/Wind Harmer
0.356
966871AG1-558 GEN
Solar/Wind Helper
0.342
966881AG1-559 GEN
Solar/Wind Helper
0.354
970025AG2-016 GEN
Solar/Wind Harmer
1.527
970095AG2-074 GEN
Solar/Wind Harmer
4.058
970277AG2-181 GEN
Solar/Wind Harmer
0.566
970453AG2-297 GEN
Solar/Wind Harmer
2.191
970545AG2-347 GEN
Solar/Wind Harmer
24.491
970597AG2-380 GEN
Solar/Wind Harmer
4.021
970665AG2-430 GEN
Solar/Wind Harmer
5.608
970695AG2-447 GEN
Solar/Wind Harmer
2.425
970753AG2-477 GEN
Solar/Wind Harmer
0.06
970755AG2-478 GEN
Solar/Wind Harmer
0.059
970757AG2-479 GEN
Solar/Wind Harmer
0.61
970761AG2-481 GEN
Solar/Wind Harmer
0.613
970997AG2-616 GEN
Solar/Wind Harmer
6.187
971007AG2-625 GEN
Solar/Wind Harmer
1.386
971009AG2-626 GEN
Solar/Wind Harmer
0.884
971011AG2-627 GEN
Solar/Wind Harmer
4.58
971149AH1-027 GEN
Solar/Wind Harmer
3.032
971189AH1-054 GEN
Solar/Wind Harmer
0.636
971195AH1-057 GEN
Solar/Wind Harmer
0.606
971519AH1-257 GEN
Solar/Wind Harmer
1.361
971521AH1-258 GEN
Solar/Wind Harmer
1.455
971535AH1-265 GEN
Solar/Wind Harmer
2.355
971553AH1-274 GEN
Solar/Wind Harmer
1.342
971667AH1-334 GEN
Solar/Wind Harmer
1.48
219221BRL12CT1
Adder
7.501
219222BRL12CT2
Adder
7.501
219223BRL12CT3
Adder
7.501
219224BRL12CT4
Adder
7.501
219912AD2-042 GEN
Solar/Wind Harmer
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.415
316431W1029_GEN1
Solar/Wind Helper
0.97
316433W1029_GEN2
Solar/Wind Helper
0.97
316435W1029_GEN3
Solar/Wind Helper
0.97
957601AF2-054 GEN
Solar/Wind Helper
0.336
957831AF2-077 GEN
Solar/Wind Helper
0.335
964001AG1-254 GEN
Solar/Wind Harmer
0.333
964211AG1-282 GEN
Solar/Wind Helper
0.343
965821AG1-450 GEN
Solar/Wind Harmer
5.05
966001AG1-469 GEN
Solar/Wind Helper
0.276
966111AG1-480 GEN
Solar/Wind Harmer
2.815
966181AG1-487 GEN
Solar/Wind Harmer
3.196
966421AG1-511 GEN
Solar/Wind Harmer
5.005
966621AG1-532 GEN
Solar/Wind Helper
0.21
971747AH1-380 GEN
Solar/Wind Harmer
2.425
971983AH1-536 GEN
Solar/Wind Harmer
1.706
972069AH1-584 GEN
Solar/Wind Harmer
6.062
972071AH1-585 GEN
Solar/Wind Harmer
6.062
972073AH1-586 GEN
Solar/Wind Harmer
9.093
972133AH1-634 GEN
Solar/Wind Harmer
3.577
972141AH1-641 GEN
Solar/Wind Harmer
2.869
972177AH1-672 GEN
Solar/Wind Harmer
9.879
972221AH1-695 GEN
Adder
108.167
972233AH1-701 GEN
Adder
3.584
972237AH1-703 GEN
Adder
8.417
972241AH1-705 GEN
Adder
4.428
972245AH1-707 GEN
Adder
4.254
972251AH1-710 GEN
Adder
42.853
972275AH1-722 GEN
Adder
26.265
200917MEHOOPANY_G
Solar/Wind Harmer
0.309
970679AG2-439 GEN
Solar/Wind Harmer
0.599
970767AG2-484 GEN
Solar/Wind Harmer
0.521
972281AH1-725 GEN
50/50
137.48
233950AC2-186 GEN
Solar/Wind Harmer
0.001
233952AC2-187 GEN
Solar/Wind Harmer
0.001
233954AC2-188 GEN
Solar/Wind Harmer
0.001
972260AH1-715 GEN1
Adder
11.44
972261AH1-715 GEN2
Adder
13.319
G-007ALTFEXP_G-007A->PJM
CMTX
42.641
VTFLTFEXP_VFT->PJM
CMTX
112.673
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.035
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.896
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.673
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.483
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.864
CBM NorthLTFEXP_CBM-N->PJM
CBM
65.685
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o AP_P1-2_PE-500-3835T_SRT-A


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_PE-500-3835T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:154.15 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5580.17
MW Contribution:0.86
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
4.055
200053ROCKSP 2
50/50
3.968
200054ROCKSP 3
50/50
4.095
200055ROCKSP 4
50/50
4.009
200203Y1-065-STG
50/50
11.132
200204Y1-065-CTG1
50/50
6.42
200205Y1-065-CTG2
50/50
6.42
3147043LAWRENC
Solar/Wind Helper
0.167
3147133PAMPLIN
Solar/Wind Helper
0.872
3147133PAMPLIN
Solar/Wind Helper
0.222
3147133PAMPLIN
Solar/Wind Helper
0.278
20328326MANOR_T86
Adder
0.124
20334726NME_Y1-047
Adder
2.528
20390726Y2-042
Adder
2.938
23546401DTGZ2-030
Solar/Wind Helper
0.09
23750701CROSSCHOOL
Solar/Wind Helper
1.106
20486527WR_V4-052
Adder
1.043
20628028LAKEHURS
Adder
2.588
20628028LAKEHURS
Adder
1.308
20633028GILCT9
Adder
35.545
20635828PARLN1&2
Adder
4.502
20635828PARLN1&2
Adder
9.94
20635928PARLN3&4
Adder
4.502
20635928PARLN3&4
Adder
9.94
20636028O CRK C1
Adder
9.778
20636128O CRK C2
Adder
8.916
20671828STAW2-080
Solar/Wind Harmer
0
20671928W4-073
Solar/Wind Harmer
0.001
20673628F1S_V4-069
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0.001
20674128FR_U2-059
Solar/Wind Harmer
0
20674328GAR_V4-001
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0.001
20674628WNG_W3-110
Solar/Wind Harmer
0.001
20674828DL_W4-046
Solar/Wind Harmer
0.001
20674928WA_W3-044
Solar/Wind Harmer
0.001
20675128HRM_W1-127
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
20675828AU_W4-064
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
20676128MHD_W3-029
Solar/Wind Harmer
0.001
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0.001
20676728BRNX1-095
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.207
20714428HOW_X1-037
Solar/Wind Harmer
0.001
20714528FRN_Y2-051
Solar/Wind Harmer
0
20714828MDF_W3-079
Solar/Wind Harmer
0.135
20714928UPF_X1-085
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0.001
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
20716028EGP_W2-019
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0.001
20716428NHV_W2-082
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0.001
20717128DIX_Z2-102
Solar/Wind Harmer
0.001
20720428HOL_W1-112
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20720728JCB_W1-129
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0.001
207408W3-077 C
Solar/Wind Harmer
0.001
213497CHSTR7-9
Adder
3.88
213497CHSTR7-9
Adder
3.88
213497CHSTR7-9
Adder
3.88
213535CROYDN11
Adder
14.318
213560DLW11-12
Adder
3.814
213560DLW11-12
Adder
3.814
213561DLWR9-10
Adder
4.987
213561DLWR9-10
Adder
3.814
213587EDDYSTN3
Adder
113.181
213589EDDYSTN4
Adder
113.194
213611FALLS1-3
Adder
4.903
213611FALLS1-3
Adder
4.903
213611FALLS1-3
Adder
4.903
213815MOSER1-3
Adder
4.947
213815MOSER1-3
Adder
4.947
213815MOSER1-3
Adder
4.947
213942SCHUYLKILL
Adder
3.832
213942SCHUYLKILL
Adder
5.011
213957STHWK3-4
Adder
3.832
213957STHWK3-4
Adder
3.832
213958STHWK5-6
Adder
3.832
213958STHWK5-6
Adder
3.832
214067T20SOLAR
Solar/Wind Harmer
0
214194N WALES4
Adder
1.175
217213AMBOY SO C
Solar/Wind Harmer
0
231131BLOOM ENRGY
Adder
7.452
231907DC10
Adder
5.976
231917EM10
Adder
3.861
231918WEST 1
Adder
5.541
231919CHRIST1
Adder
7.288
231920CHRIST2
Adder
7.126
231940T-011
Adder
1.295
232404W1-003 C
Solar/Wind Harmer
1.124
232408W1-005 C
Solar/Wind Harmer
1.124
232410W1-006 C
Solar/Wind Harmer
1.124
232416X2-083
Adder
0.758
232417X3-008 C
Solar/Wind Harmer
0.002
232426Y1-080 FULL
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.003
232813VAUGHN
Adder
1.017
232901NORTHST
Adder
14.486
232904IR4
Adder
140.44
232907VN8
Adder
52.113
232910NRG_G1
Adder
14.885
232912OH NUG1
Adder
15.335
232913OH NUG2
Adder
15.13
232914OH NUG3
Adder
15.335
232915OH NUG4
Adder
15.233
232916OH NUG5
Adder
15.335
232917OH NUG6
Adder
15.267
232918OH NUG7
Adder
15.233
232919VN10
Adder
4.868
232920IR10
Adder
5.489
232921TASLEY2G
Adder
8.962
232926CRISFLD1
Adder
3.408
23777801MSM_W1-116
Solar/Wind Helper
0.107
23777901MDS_W4-102
Solar/Wind Helper
0.173
3137176SLIGO L2192
Solar/Wind Helper
1.149
3141426STAFORD
Solar/Wind Helper
0.07
3141906WESTMOR
Solar/Wind Helper
0.121
3142416OLDCHRC
Solar/Wind Helper
0.771
3142416OLDCHRC
Solar/Wind Helper
0.295
3142433PROV 92
Solar/Wind Helper
1.181
3142956BIRDNECK
Solar/Wind Helper
0.195
3143316POE
Solar/Wind Helper
1.15
3144356SAPONY
Solar/Wind Helper
0.513
3145506HICKORY
Solar/Wind Helper
1.157
3145506HICKORY
Solar/Wind Helper
0.694
3145506HICKORY
Solar/Wind Helper
0.173
3146386ELIZ CT
Solar/Wind Helper
0.288
3146776BUCKING
Solar/Wind Helper
1.123
3146776BUCKING
Solar/Wind Helper
0.091
3146776BUCKING
Solar/Wind Helper
0.101
3146776BUCKING
Solar/Wind Helper
0.112
209027LOR2_Q27
Solar/Wind Harmer
0.001
212266LOR1
Solar/Wind Harmer
0.55
217083KRNY_132
Adder
12.159
217083KRNY_132
Adder
12.237
217086KRNY_131
Adder
12.263
217086KRNY_131
Adder
12.133
217121ECCF
Adder
0.572
217146KRNY_1234
Adder
11.405
217146KRNY_1234
Adder
11.327
217147KRNY_1212
Adder
11.639
217147KRNY_1212
Adder
11.431
217167KRNY_14
Adder
12.237
217186ESSEX_G9
Adder
21.048
217197RE CRAN C
Solar/Wind Harmer
0
218404KENILWRTH C
Adder
1.722
218418LINDEN_G5
Adder
22.839
218419LINDEN_G6
Adder
22.839
218438BLK ROCK C
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
2.438
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219035LINDEN_G8
Adder
21.848
219036LINDEN_G7
Adder
22.165
219114HARTZY_C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0.001
219287REEVESEAST C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0.001
219607WPEMNERT C
Solar/Wind Harmer
0.001
219610FLORENCE C
Solar/Wind Harmer
0.001
219612MATRIX C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
228202CUMB CT
Adder
24.423
228206SHRMN CT
Adder
24.48
228251CARLLS#4
Adder
0.928
228260V4-054C
Solar/Wind Harmer
0
228304LOGAN
Adder
35.175
228304LOGAN
Adder
31.636
228307PCLP GT
Adder
17.621
228309CCLP NUG
Adder
37.932
228309CCLP NUG
Adder
36.082
228711V2-041C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.051
316075AC2-137 C
Solar/Wind Helper
0.45
316077AC2-138 C
Solar/Wind Helper
0.281
20462827N BANGR8
Adder
0.904
20467927PC_Q59Y356
Adder
0.825
20478527GLRA_Q45
Adder
0.267
228728W1-130C
Solar/Wind Harmer
0.001
228729W2-030 C
Solar/Wind Harmer
0.001
228732V1-021 C
Adder
0.279
3138133OCRAN
Solar/Wind Helper
0.089
3138133OCRAN
Solar/Wind Helper
0.178
3141766HARMONY
Solar/Wind Helper
0.059
3141783LANCAST
Solar/Wind Helper
0.178
3141783LANCAST
Solar/Wind Helper
0.119
3141813NORNECK
Solar/Wind Helper
0.299
3141913WHIT STONE
Solar/Wind Helper
0.296
3143226MDLTHAN
Solar/Wind Helper
0.294
3143873LANEXA
Solar/Wind Helper
0.177
3145273HOLLAND
Solar/Wind Helper
0.215
3146376EDENTON
Solar/Wind Helper
0.285
3146456SLIGO L269
Solar/Wind Helper
0.289
3146456SLIGO L269
Solar/Wind Helper
0.289
3146486SUNBURY
Solar/Wind Helper
0.288
3146486SUNBURY
Solar/Wind Helper
0.288
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.929
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146516WINFALL
Solar/Wind Helper
0.287
3146626S HERTFORD
Solar/Wind Helper
0.286
3146626S HERTFORD
Solar/Wind Helper
0.286
3146626S HERTFORD
Solar/Wind Helper
0.286
3146843MT LREL
Solar/Wind Helper
0.271
3146843MT LREL
Solar/Wind Helper
0.271
3146926FARMVIL
Solar/Wind Helper
0.168
3146926FARMVIL
Solar/Wind Helper
0.168
3147123OTTER R
Solar/Wind Helper
0.15
3147312GRETNA
Solar/Wind Helper
0.05
3147312GRETNA
Solar/Wind Helper
0.199
3147666LOUISA
Solar/Wind Helper
1.21
3147666LOUISA
Solar/Wind Helper
0.696
3147983MERCK5
Solar/Wind Helper
0.11
200034PCHBTM 2
50/50
32.671
200035PCHBTM 3
50/50
32.699
232406W1-004 FULL
Solar/Wind Harmer
1.124
232436AB1-176 C
Solar/Wind Harmer
0
200192DELTA CT1
50/50
3.136
200193DELTA CT2
50/50
3.136
200194DELTA CT3
50/50
3.136
200195DELTA ST
50/50
4.847
217194REDH C
Solar/Wind Harmer
0
3141726DUNNSVL
Solar/Wind Helper
1.194
3145663CRESWEL
Solar/Wind Helper
0.793
316034AC1-036 C
Solar/Wind Helper
0.289
316036AC1-147 C
Solar/Wind Helper
0.441
316059AD1-063 C
Solar/Wind Helper
0.298
316159AE1-175 C
Solar/Wind Helper
0.445
316240AF1-291 C
Solar/Wind Helper
0.393
316246AF1-032 C
Solar/Wind Helper
0.33
316248AF1-058 C
Solar/Wind Helper
0.361
316258AE1-075 C
Solar/Wind Helper
0.397
316305AF2-043 C
Solar/Wind Helper
0.388
316315AB2-025 C
Solar/Wind Helper
0.436
316316AC1-027 C
Solar/Wind Helper
0.457
316317KELFORD C
Solar/Wind Helper
0.237
316336AC2-165 C
Solar/Wind Helper
1.553
316382AG1-145 C
Solar/Wind Helper
0.394
316405AF2-144 C
Solar/Wind Helper
0.33
223402AF1-300 C
Solar/Wind Helper
0.531
230415AB2-049 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
207454AA2-184 E
Solar/Wind Harmer
0.002
207459AE1-142 C O1
Solar/Wind Harmer
0.002
208909MACR G3
Adder
199.958
209008PAXT IPP
Adder
1.514
209009PEIP 2
Adder
9.121
209010PEIP 1
Adder
4.133
209010PEIP 1
Adder
0.605
209010PEIP 1
Adder
0.751
209018SUNBIPCT
Adder
8.007
209023WIENIPP1
Adder
12.731
209025WIENIPP3
Adder
6.227
209025WIENIPP3
Adder
6.355
209026WIENIPP4
Adder
6.291
232424Y1-079 C
Solar/Wind Harmer
0.001
232899W1-062
Adder
16.706
232900DEMECSMY
Adder
16.024
232905CHERITON_25
Adder
4.26
218524CNTRALGAS1 C
Solar/Wind Harmer
1.022
218526CNTRALGAS2 C
Solar/Wind Harmer
1.024
226910AB2-157 C
Solar/Wind Helper
0.021
233900O-025 C
Adder
2.044
233901CHERRYDALE C
Solar/Wind Harmer
0.002
233939AC1-091 C
Solar/Wind Harmer
0.003
233940AF2-379 C
Solar/Wind Harmer
0
233970AC1-092 C
Solar/Wind Harmer
0.003
233971AC1-093 C
Solar/Wind Harmer
0.075
233972AC1-094 C
Solar/Wind Harmer
0.547
233973AC2-185 C
Solar/Wind Harmer
0.003
212174INGE
Adder
1.236
212507AE2-042_GEN
Solar/Wind Harmer
0.669
219727YARDVSOLFA C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
237025AB1-124 C
Solar/Wind Helper
0.144
237030AB1-096 C
Solar/Wind Helper
0.062
237034AC2-136 C
Solar/Wind Helper
0.222
237038AE2-054 C
Solar/Wind Helper
0.243
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
3130156CHOWAN
Solar/Wind Helper
0.285
3145336SMITFLD
Solar/Wind Helper
1.162
3145336SMITFLD
Solar/Wind Helper
0.116
3148133STUARTS
Solar/Wind Helper
0.164
3146802CHATHAM
Solar/Wind Helper
0.187
3141196NOKESVL
Solar/Wind Helper
1.272
3147243WELCO
Solar/Wind Helper
0.168
3141873WAN 176
Solar/Wind Helper
0.059
3143526WINTERP
Solar/Wind Helper
1.533
3143526WINTERP
Solar/Wind Helper
1.533
316411AF1-147_GEN1
Solar/Wind Helper
1.084
316415AF1-147_GEN2
Solar/Wind Helper
1.084
316404AE1-155 C
Solar/Wind Helper
2.516
316017AA1-139 ULT1
Solar/Wind Helper
1.32
316018AA1-139 ULT2
Solar/Wind Helper
1.242
316181AB2-040 GEN
Solar/Wind Helper
2
316033AB2-134 GEN
Solar/Wind Helper
1.004
228754AB1-001 C
Solar/Wind Harmer
0
316388AE2-253 GEN
Solar/Wind Helper
1.1
230422AE1-104_GEN1
Solar/Wind Harmer
19.852
230425AE1-104_GEN2
Solar/Wind Harmer
19.852
228351V2-046C
Solar/Wind Harmer
0.001
235062AE1-101 C1
Solar/Wind Helper
1.424
203926AA2-133 GEN
Adder
2.286
3148013FISHERV
Solar/Wind Helper
0.157
3148013FISHERV
Solar/Wind Helper
0.274
3145176PASQUOTANK
Solar/Wind Helper
0.178
3132123MT JACKSON
Solar/Wind Helper
0.866
3132273ORANGE
Solar/Wind Helper
0.061
3142543TWELFTH
Solar/Wind Helper
0.028
3144303KENBRDG
Solar/Wind Helper
0.221
3147173SINAI
Solar/Wind Helper
0.268
3148463FAIRFLD
Solar/Wind Helper
0.266
238185AF2-356 C
Solar/Wind Helper
1.918
237080AD1-060 GEN
Solar/Wind Helper
0.313
235067AD1-061 GEN
Solar/Wind Helper
0.44
237001AB1-127_GEN
Solar/Wind Helper
0.386
237002AB1-128_GEN
Solar/Wind Helper
0.389
238152AF2-075_GEN
Solar/Wind Helper
0.707
238149AF1-291A_GEN
Solar/Wind Helper
0.141
238175AF1-290_GEN
Solar/Wind Helper
0.156
238221AF1-254 C O1
Solar/Wind Helper
0.258
238208AF1-136 C
Solar/Wind Helper
0.2
238120AE2-309 GEN
Solar/Wind Helper
0.406
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238148AE2-230_GEN2
Solar/Wind Helper
0.497
238169AE2-226 GEN1
Solar/Wind Helper
0.718
238170AE2-226 GEN2
Solar/Wind Helper
0.718
238108AE1-109 GEN1
Solar/Wind Helper
0.095
238109AE1-109 GEN2
Solar/Wind Helper
0.095
238110AE1-109 GEN3
Solar/Wind Helper
0.095
235063AE1-101 C2
Solar/Wind Helper
1.424
237085AD2-009_GEN
Solar/Wind Helper
1.438
316484AD2-074 GEN
Solar/Wind Helper
0.575
316494AC1-189 GEN
Solar/Wind Helper
1.667
315616AA1-038_C
Solar/Wind Helper
1.206
316420AA1-050 GEN
Solar/Wind Helper
1.561
967451AG2-055 C O1
Solar/Wind Harmer
335.566
316005AA1-067
Solar/Wind Helper
0.313
233944AB2-135 GEN
Solar/Wind Harmer
0.008
233946AB2-136 GEN
Solar/Wind Harmer
0.007
316426AA2-053 GEN
Solar/Wind Helper
1.587
316190AA2-174 GEN
Solar/Wind Helper
0.018
316327AA2-057 GEN
Solar/Wind Helper
1.558
233994AC2-023 GEN
Solar/Wind Harmer
0.007
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
315614AA2-178 GEN
Solar/Wind Helper
1.725
315816AE2-034 GEN
Solar/Wind Helper
1.294
316312AB1-027
Solar/Wind Helper
0.564
316049AB1-081 GEN
Solar/Wind Helper
1.65
316011AB1-132 GEN
Solar/Wind Helper
2.993
316369SG1_INVT
Solar/Wind Helper
1.404
235054AD2-180 GEN
Solar/Wind Helper
1.519
315651AD1-115 GEN
Solar/Wind Helper
1.035
316023GEN1_S
Solar/Wind Helper
1.07
316365GEN2_N
Solar/Wind Helper
1.07
237061AD1-155 GEN
Solar/Wind Helper
0.054
235531U2-073 GEN
Solar/Wind Helper
2.539
237006AB1-125 GEN
Solar/Wind Helper
0.108
23779801AA1-109
Solar/Wind Helper
0.184
316487AF1-042 GEN
Solar/Wind Helper
0.301
316463AE2-346 GEN
Solar/Wind Helper
0.256
315839AE2-212 C
Solar/Wind Helper
0.392
233984AB2-036 GEN
Solar/Wind Harmer
12.488
233982AB2-133 GEN
Solar/Wind Harmer
0.007
233915AB1-141 GEN
Solar/Wind Harmer
0.437
233918AB1-142 GEN
Solar/Wind Harmer
0.437
315821AE2-092 GEN
Solar/Wind Helper
2.57
316499AE2-029_GEN
Solar/Wind Helper
0.923
23583801GRNGAP
Solar/Wind Helper
4.529
233930AB2-032 GEN
Solar/Wind Harmer
1.633
233987AB2-037 GEN
Solar/Wind Harmer
0.019
315662AE1-191 GEN
Solar/Wind Helper
1.589
315666AE1-190 GEN
Solar/Wind Helper
0.397
315742AE1-103 GEN
Solar/Wind Helper
0.46
319010AE1-072 C
Solar/Wind Helper
3.298
315697AD1-025 GEN
Solar/Wind Helper
3.337
316185AD1-033 GEN
Solar/Wind Helper
1.361
233933AB2-153 GEN
Solar/Wind Harmer
0.002
233955AB2-172 GEN
Solar/Wind Harmer
0.005
315773AC2-141 GEN
Solar/Wind Helper
6.25
316280AD1-041 GEN
Solar/Wind Helper
0.993
233935AB2-179 C
Solar/Wind Harmer
2.292
234041AC1-190 GEN
Solar/Wind Harmer
12.626
316003AC1-222 GEN
Solar/Wind Helper
1.156
315722AD1-056 GEN
Solar/Wind Helper
1.472
315724AD1-057 GEN
Solar/Wind Helper
0.81
315732AD1-074 GEN1
Solar/Wind Helper
3.218
315733AD1-074 GEN2
Solar/Wind Helper
3.218
315735AD1-075 GEN1
Solar/Wind Helper
1.609
315737AD1-076 GEN
Solar/Wind Helper
2.753
316473AC1-191 GEN
Solar/Wind Helper
1.82
316478AD1-087 GEN
Solar/Wind Helper
1.355
316486AD2-202 GEN
Solar/Wind Helper
0.397
316447AC1-158 HLD
Solar/Wind Helper
3.78
316044AC1-158 PL1
Solar/Wind Helper
1.717
316045AC1-158 PL2
Solar/Wind Helper
5.498
316450AC1-158 RIC
Solar/Wind Helper
0.458
316468AD1-105 GEN
Solar/Wind Helper
1.502
316072AD1-144
Solar/Wind Helper
0.331
315687AD1-152 GEN
Solar/Wind Helper
1.47
316156AD2-030 GEN
Solar/Wind Helper
0.446
315785AD2-033 C
Solar/Wind Helper
3.217
316337AD2-073 GEN
Solar/Wind Helper
0.456
233968AD2-076_GEN
Solar/Wind Harmer
3.977
234012AE2-112_GEN
Solar/Wind Harmer
3.977
234014AF1-036_GEN
Solar/Wind Harmer
3.977
234015AF2-250 C
Solar/Wind Harmer
0
234036AF2-325 C
Solar/Wind Harmer
0.001
233990AG1-397 GEN
Solar/Wind Harmer
-0.276
233990AG1-397 GEN
Solar/Wind Harmer
2.364
207522AF2-254 C
Solar/Wind Harmer
1.285
207528AF2-192 GEN
Solar/Wind Harmer
0.001
207484AF2-139 C O1
Solar/Wind Harmer
0.001
207510AF2-138 C
Solar/Wind Harmer
0.002
207500AE2-000G1
Solar/Wind Harmer
17.494
207497AE2-000G2
Solar/Wind Harmer
17.494
207507AE2-000G3
Solar/Wind Harmer
17.494
207487AE2-000G4
Solar/Wind Harmer
17.494
207442AE1-156 GEN
Solar/Wind Harmer
0.08
226929AD2-058 GEN
Solar/Wind Helper
0.145
207437AD2-070 GEN
Solar/Wind Harmer
0.083
209054AE2-059 GEN
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Helper
0.439
316313AB2-026
Solar/Wind Helper
0.441
207445AB1-138_GEN
Solar/Wind Harmer
0.001
209071AE2-133 GEN
Solar/Wind Harmer
0.001
209116AE2-175 GEN
Solar/Wind Harmer
0.009
209120AE2-241 GEN
Solar/Wind Harmer
1.801
209093AE2-110 GEN
Solar/Wind Harmer
1.801
3145513AHOSKIE
Solar/Wind Helper
0.28
3145513AHOSKIE
Solar/Wind Helper
0.125
233923SMA
Solar/Wind Harmer
0.009
230430AE1-229_GEN
Solar/Wind Harmer
0.025
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219908AB1-139 C
Solar/Wind Harmer
0.001
219904AC1-010 C
Solar/Wind Harmer
0.001
219906AC1-017 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0.001
219304NAMERICA C
Solar/Wind Harmer
0.128
219921AF1-264
Solar/Wind Harmer
0
238127S14_GEN_2
Solar/Wind Helper
0.637
238126S14_GEN_1
Solar/Wind Helper
0.637
231902DC CT7
Adder
19.137
231906DC3 NUG
Adder
23.938
238117U2-030
Solar/Wind Helper
0.261
238118U2-030_1
Solar/Wind Helper
0.261
209045AE2-271 GEN
Solar/Wind Harmer
12.981
211065PSPA IPP
Solar/Wind Harmer
0.001
211065PSPA IPP
Solar/Wind Harmer
0.001
208862AG1-362 C
Solar/Wind Harmer
0.524
207530AG1-191 GEN
Solar/Wind Harmer
0.001
270197AD1-017 GEN1
Solar/Wind Helper
1.333
270173AC1-122 GEN
Solar/Wind Helper
1.584
230511AF1-262
Solar/Wind Harmer
0
209130AF1-271A GEN
Solar/Wind Harmer
2.109
209142AF1-226 GEN
Solar/Wind Harmer
3.151
205941AD2-115 GEN
Solar/Wind Harmer
0.122
270214AC2-123 GEN
Solar/Wind Helper
0.811
209059AE2-084 GEN
Solar/Wind Harmer
1.756
20465427SHAW CT
Adder
4.864
209022WHFR IPP
Adder
3.707
270455AD2-022 GEN
Solar/Wind Helper
1.49
270457AD2-023 GEN
Solar/Wind Helper
0.982
270336AE1-100 GEN
Solar/Wind Helper
1.035
270494AE1-108_GEN
Solar/Wind Helper
3.631
270016AE1-250 BESS
Solar/Wind Helper
0.92
270013AE1-250 PV
Solar/Wind Helper
0.92
270018AE2-047 C O1
Solar/Wind Helper
0.865
270069AE2-166 C O1
Solar/Wind Helper
1.061
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
1.09
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
3145746EVERETS
Solar/Wind Helper
0.274
209067AE2-060 GEN
Solar/Wind Harmer
0.001
209137AF2-361 C
Solar/Wind Harmer
0.004
3146206CASHIE
Solar/Wind Helper
0.281
3146206CASHIE
Solar/Wind Helper
0.281
3146206CASHIE
Solar/Wind Helper
0.281
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.278
3142666NORTHAMPTON
Solar/Wind Helper
0.167
3142666NORTHAMPTON
Solar/Wind Helper
0.278
316274AC1-208 GEN
Solar/Wind Helper
1.676
316349AD2-085 GEN
Solar/Wind Helper
1.321
3156021HOLLOMANSOL
Solar/Wind Helper
2.13
313506AB2-031 GEN
Solar/Wind Helper
1.265
316006AB2-029 C
Solar/Wind Helper
0.149
316322AB2-045
Solar/Wind Helper
0.313
316359AB2-059 GEN
Solar/Wind Helper
2.063
316131AB2-060 GEN
Solar/Wind Helper
1.675
316192AB2-158 GEN
Solar/Wind Helper
2.03
316174AB2-169 GEN
Solar/Wind Helper
0.707
316087AB2-174 GEN
Solar/Wind Helper
1.952
316132AB2-190 GEN1
Solar/Wind Helper
1.671
316458AB2-190 GEN2
Solar/Wind Helper
1.671
316129AC1-054 GEN
Solar/Wind Helper
1.363
316123AC1-075 GEN
Solar/Wind Helper
1.584
316210AC1-098 GEN
Solar/Wind Helper
2.224
316212AC1-099_GEN
Solar/Wind Helper
1.236
316118AC1-105 GEN
Solar/Wind Helper
1.048
316254AC1-120 GEN1
Solar/Wind Helper
1.411
316170AC1-121 GEN2
Solar/Wind Helper
0.47
316222AC1-221 GEN
Solar/Wind Helper
1.498
316375AC2-012 GEN
Solar/Wind Helper
0.759
316283AC2-100 C
Solar/Wind Helper
1.399
316339AD2-160 GEN
Solar/Wind Helper
1.1
316164AC1-076 GEN
Solar/Wind Helper
1.468
20635028RRCT1&2
Adder
15.796
20635028RRCT1&2
Adder
15.553
20635128RRCT3&4
Adder
13.096
20635128RRCT3&4
Adder
15.013
316239AB2-077_GEN
Solar/Wind Helper
0.369
316238AB2-078_GEN
Solar/Wind Helper
0.369
316237AB2-079_GEN
Solar/Wind Helper
0.369
316140AB2-099
Solar/Wind Helper
0.107
316197AC1-042 GEN
Solar/Wind Helper
0.234
316223AC1-118
Solar/Wind Helper
0.46
316294AC1-161 GEN
Solar/Wind Helper
5.311
316381AD1-082 GEN
Solar/Wind Helper
1.502
316233AE1-074 FULL
Solar/Wind Helper
0.45
316236AE1-162_GEN
Solar/Wind Helper
0.391
315607AA1-063A GEN
Solar/Wind Helper
1.593
20465527S.RDG CT
Adder
2.577
20465527S.RDG CT
Adder
2.664
20466127PORT 5CT
Adder
33.54
20465127PORT CT
Adder
3.797
20465127PORT CT
Adder
5.039
230434AG1-499 GEN
Solar/Wind Harmer
0.002
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.282
3145543BTLEBRO
Solar/Wind Helper
0.217
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
3145543BTLEBRO
Solar/Wind Helper
0.271
3145593CAROLNA
Solar/Wind Helper
0.278
3145593CAROLNA
Solar/Wind Helper
0.278
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.279
3145683EARLEYS
Solar/Wind Helper
0.559
200200DELTA2 CT1
50/50
5.613
200201DELTA2 CT2
50/50
5.613
200202DELTA2 ST
50/50
9.525
207511W3-106 GEN
Solar/Wind Harmer
0.421
208972BECR K09
Solar/Wind Harmer
0.001
209029WAYMART-WD
Solar/Wind Harmer
0.001
223401AF1-299 GEN
Solar/Wind Helper
0.531
230407AD2-065 C
Solar/Wind Harmer
0
232422X3-066 FULL
Solar/Wind Harmer
0.143
232432Z2-076 GEN
Solar/Wind Harmer
0.023
232434Z2-077 GEN
Solar/Wind Harmer
0.073
233996TM1833_GEN
Solar/Wind Harmer
0.003
233997TMININ_4.2
Solar/Wind Harmer
0.003
233998TM1NIN_3.36
Solar/Wind Harmer
0.003
3130086AYDLETT
Solar/Wind Helper
1.154
3137643SOCKMAN
Solar/Wind Helper
1.112
3138216PACIFIC
Solar/Wind Helper
0.054
3138266HYDRAULIC
Solar/Wind Helper
0.008
3138266HYDRAULIC
Solar/Wind Helper
0.013
3138543CONSLDL
Solar/Wind Helper
0.179
3142946ENON
Solar/Wind Helper
0.03
3142946ENON
Solar/Wind Helper
0.098
3144536CHRHLND
Solar/Wind Helper
0.044
3144873MCLAUGH
Solar/Wind Helper
0.007
3145573BETHELC
Solar/Wind Helper
0.272
3145573BETHELC
Solar/Wind Helper
0.272
3145783HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
0.831
3145796HORNRTN
Solar/Wind Helper
0.914
3145796HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
0.277
3145796HORNRTN
Solar/Wind Helper
1.108
3145796HORNRTN
Solar/Wind Helper
0.886
3145796HORNRTN
Solar/Wind Helper
0.111
3145823KELFORD
Solar/Wind Helper
0.278
3145823KELFORD
Solar/Wind Helper
0.278
3145893MURPHYS
Solar/Wind Helper
0.403
3145893MURPHYS
Solar/Wind Helper
0.506
3145893MURPHYS
Solar/Wind Helper
0.101
3145893MURPHYS
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
1.123
3145893MURPHYS
Solar/Wind Helper
0.281
3145893MURPHYS
Solar/Wind Helper
0.758
3145933PARMELE
Solar/Wind Helper
0.55
3145933PARMELE
Solar/Wind Helper
0.275
3145933PARMELE
Solar/Wind Helper
0.275
3145963POPLR C
Solar/Wind Helper
0.278
3145963POPLR C
Solar/Wind Helper
0.278
3146033SCOT NK
Solar/Wind Helper
1.107
3146043SEABORD
Solar/Wind Helper
0.28
3146073TAR RVR
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3146083TARBORO
Solar/Wind Helper
0.272
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
3146173TUNIS
Solar/Wind Helper
0.28
3146233WITAKRS
Solar/Wind Helper
0.293
3146233WITAKRS
Solar/Wind Helper
1.082
3146233WITAKRS
Solar/Wind Helper
0.185
3146263WOODLND
Solar/Wind Helper
0.279
3146263WOODLND
Solar/Wind Helper
0.279
315611Z1-036_GEN2
Solar/Wind Helper
1.571
315800Z1-036_GEN1
Solar/Wind Helper
1.571
316095T157 G97
Solar/Wind Helper
1.23
316097T157 G90
Solar/Wind Helper
1.23
316320Y1-086
Solar/Wind Helper
0.129
316321Z2-027
Solar/Wind Helper
0.438
942461AE2-259 GEN
Solar/Wind Helper
1.879
943811AF1-049 GEN
Solar/Wind Helper
1.493
945431AF1-208 GEN
Solar/Wind Harmer
8.85
946281AF1-292 GEN
Solar/Wind Helper
0.281
960671AF2-358 GEN
Solar/Wind Harmer
21.666
961541AF2-445A GEN
Solar/Wind Harmer
2.57
961671AG1-007 GEN
Solar/Wind Helper
0.195
961941AG1-037 GEN
Solar/Wind Helper
0.094
963071AG1-156 GEN
Solar/Wind Harmer
0.518
966871AG1-558 GEN
Solar/Wind Helper
0.402
966881AG1-559 GEN
Solar/Wind Helper
0.411
970025AG2-016 GEN
Solar/Wind Harmer
2.527
970095AG2-074 GEN
Solar/Wind Harmer
5.901
970277AG2-181 GEN
Solar/Wind Harmer
1.011
970453AG2-297 GEN
Solar/Wind Harmer
3.772
970545AG2-347 GEN
Solar/Wind Harmer
43.85
970597AG2-380 GEN
Solar/Wind Harmer
7.123
970665AG2-430 GEN
Solar/Wind Harmer
7.793
970695AG2-447 GEN
Solar/Wind Harmer
4.35
970757AG2-479 GEN
Solar/Wind Harmer
0.848
970761AG2-481 GEN
Solar/Wind Harmer
0.857
970997AG2-616 GEN
Solar/Wind Harmer
10.581
971007AG2-625 GEN
Solar/Wind Harmer
2.112
971009AG2-626 GEN
Solar/Wind Harmer
1.347
971011AG2-627 GEN
Solar/Wind Harmer
7.811
971149AH1-027 GEN
Solar/Wind Harmer
5.438
971189AH1-054 GEN
Solar/Wind Harmer
1.052
971195AH1-057 GEN
Solar/Wind Harmer
1.085
971519AH1-257 GEN
Solar/Wind Harmer
2.07
971521AH1-258 GEN
Solar/Wind Harmer
2.368
971535AH1-265 GEN
Solar/Wind Harmer
4.02
971553AH1-274 GEN
Solar/Wind Harmer
2.303
971667AH1-334 GEN
Solar/Wind Harmer
2.444
219221BRL12CT1
Adder
12.506
219222BRL12CT2
Adder
12.506
219223BRL12CT3
Adder
12.506
219224BRL12CT4
Adder
12.506
219912AD2-042 GEN
Solar/Wind Harmer
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.512
316431W1029_GEN1
Solar/Wind Helper
1.16
316433W1029_GEN2
Solar/Wind Helper
1.16
316435W1029_GEN3
Solar/Wind Helper
1.16
957601AF2-054 GEN
Solar/Wind Helper
0.396
957831AF2-077 GEN
Solar/Wind Helper
0.396
964001AG1-254 GEN
Solar/Wind Harmer
0.568
964211AG1-282 GEN
Solar/Wind Helper
0.402
964991AG1-363 GEN
Solar/Wind Helper
3.563
965821AG1-450 GEN
Solar/Wind Harmer
9.028
966001AG1-469 GEN
Solar/Wind Helper
0.321
966111AG1-480 GEN
Solar/Wind Harmer
4.26
966181AG1-487 GEN
Solar/Wind Harmer
4.796
966421AG1-511 GEN
Solar/Wind Harmer
7.613
966621AG1-532 GEN
Solar/Wind Helper
0.254
971747AH1-380 GEN
Solar/Wind Harmer
4.339
971983AH1-536 GEN
Solar/Wind Harmer
3.013
972069AH1-584 GEN
Solar/Wind Harmer
10.849
972071AH1-585 GEN
Solar/Wind Harmer
10.849
972073AH1-586 GEN
Solar/Wind Harmer
16.273
972133AH1-634 GEN
Solar/Wind Harmer
6.404
972141AH1-641 GEN
Solar/Wind Harmer
4.906
972177AH1-672 GEN
Solar/Wind Harmer
17.686
972221AH1-695 GEN
Adder
101.353
972233AH1-701 GEN
Adder
6.085
972237AH1-703 GEN
Adder
13.322
972241AH1-705 GEN
Adder
5.998
972245AH1-707 GEN
Adder
5.98
972251AH1-710 GEN
Adder
76.344
972275AH1-722 GEN
Adder
41.987
958121AF2-106 GEN
Solar/Wind Helper
1.718
200917MEHOOPANY_G
Solar/Wind Harmer
0.378
970679AG2-439 GEN
Solar/Wind Harmer
0.772
970767AG2-484 GEN
Solar/Wind Harmer
0.566
972271AH1-720 GEN
Adder
6.089
941421AE2-139 GEN
Solar/Wind Harmer
0
233950AC2-186 GEN
Solar/Wind Harmer
0.001
233952AC2-187 GEN
Solar/Wind Harmer
0.002
233954AC2-188 GEN
Solar/Wind Harmer
0.002
972260AH1-715 GEN1
Adder
18.289
972261AH1-715 GEN2
Adder
21.217
G-007ALTFEXP_G-007A->PJM
CMTX
68.692
VTFLTFEXP_VFT->PJM
CMTX
178.729
HAMLETPJM->LTFIMP_HAMLET
CLTF
6.525
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.834
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
24.671
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
5.232
BlueGrassPJM->LTFIMP_BlueG
CLTF
16.303
CBM NorthLTFEXP_CBM-N->PJM
CBM
95.157
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
PECO_P1-2_5007_SRT-A/* $ CHESCO $ PECO_P1-2_5007 $ L
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.36 %
Rating:3620.0 MVA
Rating Type:B
MVA to Mitigate:5153.54
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
4.692
200053ROCKSP 2
50/50
4.592
200054ROCKSP 3
50/50
4.739
200055ROCKSP 4
50/50
4.639
200203Y1-065-STG
50/50
12.882
200204Y1-065-CTG1
50/50
7.429
200205Y1-065-CTG2
50/50
7.429
3147043LAWRENC
Solar/Wind Helper
0.14
3147133PAMPLIN
Solar/Wind Helper
0.73
3147133PAMPLIN
Solar/Wind Helper
0.186
3147133PAMPLIN
Solar/Wind Helper
0.232
23546401DTGZ2-030
Solar/Wind Helper
0.074
20628028LAKEHURS
Adder
2.422
20628028LAKEHURS
Adder
1.224
20633028GILCT9
Adder
27.831
20635828PARLN1&2
Adder
4.035
20635828PARLN1&2
Adder
8.908
20635928PARLN3&4
Adder
4.035
20635928PARLN3&4
Adder
8.908
20636028O CRK C1
Adder
9.242
20636128O CRK C2
Adder
8.427
20671828STAW2-080
Solar/Wind Harmer
0
20671928W4-073
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
20674128FR_U2-059
Solar/Wind Harmer
0
20674328GAR_V4-001
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
20674828DL_W4-046
Solar/Wind Harmer
0
20674928WA_W3-044
Solar/Wind Harmer
0.001
20675128HRM_W1-127
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
20675828AU_W4-064
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
20676128MHD_W3-029
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.19
20714428HOW_X1-037
Solar/Wind Harmer
0.001
20714528FRN_Y2-051
Solar/Wind Harmer
0
20714828MDF_W3-079
Solar/Wind Harmer
0.125
20714928UPF_X1-085
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0.001
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
20716028EGP_W2-019
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0.001
20716428NHV_W2-082
Solar/Wind Harmer
0.001
20716928W4-060COL
Solar/Wind Harmer
0.001
20717128DIX_Z2-102
Solar/Wind Harmer
0.001
20720428HOL_W1-112
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20720728JCB_W1-129
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0.001
207408W3-077 C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
3.912
213497CHSTR7-9
Adder
3.912
213497CHSTR7-9
Adder
3.912
213535CROYDN11
Adder
13.821
213560DLW11-12
Adder
3.737
213560DLW11-12
Adder
3.737
213561DLWR9-10
Adder
4.887
213561DLWR9-10
Adder
3.737
213587EDDYSTN3
Adder
114.001
213589EDDYSTN4
Adder
114.034
213611FALLS1-3
Adder
4.678
213611FALLS1-3
Adder
4.678
213611FALLS1-3
Adder
4.678
213815MOSER1-3
Adder
4.776
213815MOSER1-3
Adder
4.776
213815MOSER1-3
Adder
4.776
213942SCHUYLKILL
Adder
3.803
213942SCHUYLKILL
Adder
4.973
213957STHWK3-4
Adder
3.798
213957STHWK3-4
Adder
3.798
213958STHWK5-6
Adder
3.798
213958STHWK5-6
Adder
3.798
214067T20SOLAR
Solar/Wind Harmer
0
214194N WALES4
Adder
1.114
217213AMBOY SO C
Solar/Wind Harmer
0
231131BLOOM ENRGY
Adder
8
231907DC10
Adder
6.418
231917EM10
Adder
4.08
231918WEST 1
Adder
5.882
231919CHRIST1
Adder
7.728
231920CHRIST2
Adder
7.556
231940T-011
Adder
1.392
232404W1-003 C
Solar/Wind Harmer
1.209
232408W1-005 C
Solar/Wind Harmer
1.209
232410W1-006 C
Solar/Wind Harmer
1.209
232416X2-083
Adder
0.81
232417X3-008 C
Solar/Wind Harmer
0.002
232426Y1-080 FULL
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.003
232813VAUGHN
Adder
1.092
232901NORTHST
Adder
15.55
232904IR4
Adder
150.928
232907VN8
Adder
56.047
232910NRG_G1
Adder
15.986
232912OH NUG1
Adder
16.486
232913OH NUG2
Adder
16.266
232914OH NUG3
Adder
16.486
232915OH NUG4
Adder
16.376
232916OH NUG5
Adder
16.486
232917OH NUG6
Adder
16.412
232918OH NUG7
Adder
16.376
232919VN10
Adder
5.234
232920IR10
Adder
5.899
232921TASLEY2G
Adder
9.635
232926CRISFLD1
Adder
3.663
23777801MSM_W1-116
Solar/Wind Helper
0.099
23777901MDS_W4-102
Solar/Wind Helper
0.145
3137176SLIGO L2192
Solar/Wind Helper
0.95
3141426STAFORD
Solar/Wind Helper
0.056
3141906WESTMOR
Solar/Wind Helper
0.099
3142416OLDCHRC
Solar/Wind Helper
0.632
3142416OLDCHRC
Solar/Wind Helper
0.242
3142433PROV 92
Solar/Wind Helper
0.97
3142956BIRDNECK
Solar/Wind Helper
0.161
3143316POE
Solar/Wind Helper
0.949
3144356SAPONY
Solar/Wind Helper
0.426
3145506HICKORY
Solar/Wind Helper
0.956
3145506HICKORY
Solar/Wind Helper
0.574
3145506HICKORY
Solar/Wind Helper
0.143
3146386ELIZ CT
Solar/Wind Helper
0.238
3146776BUCKING
Solar/Wind Helper
0.936
3146776BUCKING
Solar/Wind Helper
0.076
3146776BUCKING
Solar/Wind Helper
0.084
3146776BUCKING
Solar/Wind Helper
0.094
209027LOR2_Q27
Solar/Wind Harmer
0.001
212266LOR1
Solar/Wind Harmer
0.365
217083KRNY_132
Adder
10.474
217083KRNY_132
Adder
10.541
217086KRNY_131
Adder
10.563
217086KRNY_131
Adder
10.451
217121ECCF
Adder
0.493
217146KRNY_1234
Adder
9.825
217146KRNY_1234
Adder
9.758
217147KRNY_1212
Adder
10.026
217147KRNY_1212
Adder
9.847
217167KRNY_14
Adder
10.541
217186ESSEX_G9
Adder
18.134
217197RE CRAN C
Solar/Wind Harmer
0
218404KENILWRTH C
Adder
1.489
218418LINDEN_G5
Adder
20.073
218419LINDEN_G6
Adder
20.073
218438BLK ROCK C
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
2.181
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219035LINDEN_G8
Adder
19.071
219036LINDEN_G7
Adder
19.347
219114HARTZY_C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0.001
219287REEVESEAST C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0.001
219607WPEMNERT C
Solar/Wind Harmer
0.001
219610FLORENCE C
Solar/Wind Harmer
0.001
219612MATRIX C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
228202CUMB CT
Adder
24.596
228206SHRMN CT
Adder
24.635
228251CARLLS#4
Adder
0.932
228260V4-054C
Solar/Wind Harmer
0
228304LOGAN
Adder
35.125
228304LOGAN
Adder
31.591
228307PCLP GT
Adder
17.621
228309CCLP NUG
Adder
38.086
228309CCLP NUG
Adder
36.229
228711V2-041C
Solar/Wind Harmer
0
235020AA1-095 C
Solar/Wind Helper
0.043
316075AC2-137 C
Solar/Wind Helper
0.369
316077AC2-138 C
Solar/Wind Helper
0.23
20462827N BANGR8
Adder
0.708
20467927PC_Q59Y356
Adder
0.451
228728W1-130C
Solar/Wind Harmer
0.001
228729W2-030 C
Solar/Wind Harmer
0.001
228732V1-021 C
Adder
0.28
3138133OCRAN
Solar/Wind Helper
0.073
3138133OCRAN
Solar/Wind Helper
0.146
3141766HARMONY
Solar/Wind Helper
0.049
3141783LANCAST
Solar/Wind Helper
0.146
3141783LANCAST
Solar/Wind Helper
0.097
3141813NORNECK
Solar/Wind Helper
0.245
3141913WHIT STONE
Solar/Wind Helper
0.243
3143226MDLTHAN
Solar/Wind Helper
0.242
3143873LANEXA
Solar/Wind Helper
0.145
3145273HOLLAND
Solar/Wind Helper
0.178
3146376EDENTON
Solar/Wind Helper
0.237
3146456SLIGO L269
Solar/Wind Helper
0.239
3146456SLIGO L269
Solar/Wind Helper
0.239
3146486SUNBURY
Solar/Wind Helper
0.238
3146486SUNBURY
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.77
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146516WINFALL
Solar/Wind Helper
0.238
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
3146626S HERTFORD
Solar/Wind Helper
0.237
3146843MT LREL
Solar/Wind Helper
0.229
3146843MT LREL
Solar/Wind Helper
0.229
3146926FARMVIL
Solar/Wind Helper
0.14
3146926FARMVIL
Solar/Wind Helper
0.14
3147666LOUISA
Solar/Wind Helper
0.983
3147666LOUISA
Solar/Wind Helper
0.565
3147983MERCK5
Solar/Wind Helper
0.092
200034PCHBTM 2
50/50
38.283
200035PCHBTM 3
50/50
38.641
232406W1-004 FULL
Solar/Wind Harmer
1.209
232436AB1-176 C
Solar/Wind Harmer
0
200192DELTA CT1
50/50
3.676
200193DELTA CT2
50/50
3.676
200194DELTA CT3
50/50
3.676
200195DELTA ST
50/50
5.681
217194REDH C
Solar/Wind Harmer
0
3141726DUNNSVL
Solar/Wind Helper
0.978
3145663CRESWEL
Solar/Wind Helper
0.66
316034AC1-036 C
Solar/Wind Helper
0.243
316036AC1-147 C
Solar/Wind Helper
0.364
316059AD1-063 C
Solar/Wind Helper
0.245
316159AE1-175 C
Solar/Wind Helper
0.366
316240AF1-291 C
Solar/Wind Helper
0.324
316246AF1-032 C
Solar/Wind Helper
0.273
316248AF1-058 C
Solar/Wind Helper
0.306
316258AE1-075 C
Solar/Wind Helper
0.327
316305AF2-043 C
Solar/Wind Helper
0.321
316315AB2-025 C
Solar/Wind Helper
0.362
316316AC1-027 C
Solar/Wind Helper
0.377
316317KELFORD C
Solar/Wind Helper
0.198
316336AC2-165 C
Solar/Wind Helper
1.283
316382AG1-145 C
Solar/Wind Helper
0.324
316405AF2-144 C
Solar/Wind Helper
0.273
223402AF1-300 C
Solar/Wind Helper
0.483
230415AB2-049 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
207454AA2-184 E
Solar/Wind Harmer
0.002
207459AE1-142 C O1
Solar/Wind Harmer
0.002
208909MACR G3
Adder
154.619
209009PEIP 2
Adder
6.599
209010PEIP 1
Adder
2.99
209010PEIP 1
Adder
0.438
209010PEIP 1
Adder
0.544
209018SUNBIPCT
Adder
4.949
209023WIENIPP1
Adder
8.981
209025WIENIPP3
Adder
4.392
209025WIENIPP3
Adder
4.483
209026WIENIPP4
Adder
4.438
232424Y1-079 C
Solar/Wind Harmer
0.001
232899W1-062
Adder
17.93
232900DEMECSMY
Adder
17.198
232905CHERITON_25
Adder
4.579
218524CNTRALGAS1 C
Solar/Wind Harmer
0.906
218526CNTRALGAS2 C
Solar/Wind Harmer
0.91
226910AB2-157 C
Solar/Wind Helper
0.018
233900O-025 C
Adder
2.198
233901CHERRYDALE C
Solar/Wind Harmer
0.002
233939AC1-091 C
Solar/Wind Harmer
0.003
233940AF2-379 C
Solar/Wind Harmer
0
233970AC1-092 C
Solar/Wind Harmer
0.003
233971AC1-093 C
Solar/Wind Harmer
0.08
233972AC1-094 C
Solar/Wind Harmer
0.587
233973AC2-185 C
Solar/Wind Harmer
0.003
212174INGE
Adder
0.807
212507AE2-042_GEN
Solar/Wind Harmer
0.421
219727YARDVSOLFA C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
237025AB1-124 C
Solar/Wind Helper
0.141
237030AB1-096 C
Solar/Wind Helper
0.061
237034AC2-136 C
Solar/Wind Helper
0.191
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3130156CHOWAN
Solar/Wind Helper
0.237
3145336SMITFLD
Solar/Wind Helper
0.959
3145336SMITFLD
Solar/Wind Helper
0.096
3148133STUARTS
Solar/Wind Helper
0.138
3141196NOKESVL
Solar/Wind Helper
1.011
3147243WELCO
Solar/Wind Helper
0.142
3141873WAN 176
Solar/Wind Helper
0.049
3143526WINTERP
Solar/Wind Helper
1.258
3143526WINTERP
Solar/Wind Helper
1.258
316411AF1-147_GEN1
Solar/Wind Helper
0.855
316415AF1-147_GEN2
Solar/Wind Helper
0.855
316404AE1-155 C
Solar/Wind Helper
2.061
316017AA1-139 ULT1
Solar/Wind Helper
1.091
316018AA1-139 ULT2
Solar/Wind Helper
1.027
316181AB2-040 GEN
Solar/Wind Helper
1.673
316033AB2-134 GEN
Solar/Wind Helper
0.827
228754AB1-001 C
Solar/Wind Harmer
0
316388AE2-253 GEN
Solar/Wind Helper
0.909
230422AE1-104_GEN1
Solar/Wind Harmer
19.855
230425AE1-104_GEN2
Solar/Wind Harmer
19.855
228351V2-046C
Solar/Wind Harmer
0.001
3148013FISHERV
Solar/Wind Helper
0.132
3148013FISHERV
Solar/Wind Helper
0.23
3145176PASQUOTANK
Solar/Wind Helper
0.148
3132123MT JACKSON
Solar/Wind Helper
0.722
3132273ORANGE
Solar/Wind Helper
0.049
3142543TWELFTH
Solar/Wind Helper
0.023
3144303KENBRDG
Solar/Wind Helper
0.185
3147173SINAI
Solar/Wind Helper
0.227
3148463FAIRFLD
Solar/Wind Helper
0.225
238152AF2-075_GEN
Solar/Wind Helper
0.578
238149AF1-291A_GEN
Solar/Wind Helper
0.116
238175AF1-290_GEN
Solar/Wind Helper
0.126
238221AF1-254 C O1
Solar/Wind Helper
0.222
238147AE2-230_GEN1
Solar/Wind Helper
0.405
238148AE2-230_GEN2
Solar/Wind Helper
0.406
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
316484AD2-074 GEN
Solar/Wind Helper
0.471
316494AC1-189 GEN
Solar/Wind Helper
1.405
315616AA1-038_C
Solar/Wind Helper
1.022
316420AA1-050 GEN
Solar/Wind Helper
1.317
967451AG2-055 C O1
Solar/Wind Harmer
304.124
316005AA1-067
Solar/Wind Helper
0.263
233944AB2-135 GEN
Solar/Wind Harmer
0.009
233946AB2-136 GEN
Solar/Wind Harmer
0.007
316426AA2-053 GEN
Solar/Wind Helper
1.328
316190AA2-174 GEN
Solar/Wind Helper
0.015
316327AA2-057 GEN
Solar/Wind Helper
1.313
233994AC2-023 GEN
Solar/Wind Harmer
0.008
234033AF1-007_GEN
Solar/Wind Harmer
-0.002
315614AA2-178 GEN
Solar/Wind Helper
1.436
315816AE2-034 GEN
Solar/Wind Helper
1.077
316312AB1-027
Solar/Wind Helper
0.463
316049AB1-081 GEN
Solar/Wind Helper
1.394
316011AB1-132 GEN
Solar/Wind Helper
2.506
316369SG1_INVT
Solar/Wind Helper
1.157
315651AD1-115 GEN
Solar/Wind Helper
0.833
316023GEN1_S
Solar/Wind Helper
0.893
316365GEN2_N
Solar/Wind Helper
0.893
237061AD1-155 GEN
Solar/Wind Helper
0.044
237006AB1-125 GEN
Solar/Wind Helper
0.106
23779801AA1-109
Solar/Wind Helper
0.167
316487AF1-042 GEN
Solar/Wind Helper
0.246
316463AE2-346 GEN
Solar/Wind Helper
0.214
315839AE2-212 C
Solar/Wind Helper
0.323
233984AB2-036 GEN
Solar/Wind Harmer
13.43
233982AB2-133 GEN
Solar/Wind Harmer
0.007
233915AB1-141 GEN
Solar/Wind Harmer
0.47
233918AB1-142 GEN
Solar/Wind Harmer
0.47
315821AE2-092 GEN
Solar/Wind Helper
2.149
316499AE2-029_GEN
Solar/Wind Helper
0.773
23583801GRNGAP
Solar/Wind Helper
3.822
233930AB2-032 GEN
Solar/Wind Harmer
1.755
233987AB2-037 GEN
Solar/Wind Harmer
0.02
315662AE1-191 GEN
Solar/Wind Helper
1.304
315666AE1-190 GEN
Solar/Wind Helper
0.326
315742AE1-103 GEN
Solar/Wind Helper
0.382
319010AE1-072 C
Solar/Wind Helper
2.727
315697AD1-025 GEN
Solar/Wind Helper
2.749
316185AD1-033 GEN
Solar/Wind Helper
1.124
233933AB2-153 GEN
Solar/Wind Harmer
0.002
233955AB2-172 GEN
Solar/Wind Harmer
0.006
315773AC2-141 GEN
Solar/Wind Helper
5.158
316280AD1-041 GEN
Solar/Wind Helper
0.815
233935AB2-179 C
Solar/Wind Harmer
2.459
234041AC1-190 GEN
Solar/Wind Harmer
13.578
316003AC1-222 GEN
Solar/Wind Helper
0.982
315722AD1-056 GEN
Solar/Wind Helper
1.239
315724AD1-057 GEN
Solar/Wind Helper
0.682
315732AD1-074 GEN1
Solar/Wind Helper
2.683
315733AD1-074 GEN2
Solar/Wind Helper
2.683
315735AD1-075 GEN1
Solar/Wind Helper
1.341
315737AD1-076 GEN
Solar/Wind Helper
2.295
316473AC1-191 GEN
Solar/Wind Helper
1.49
316478AD1-087 GEN
Solar/Wind Helper
1.136
316486AD2-202 GEN
Solar/Wind Helper
0.333
316447AC1-158 HLD
Solar/Wind Helper
3.044
316044AC1-158 PL1
Solar/Wind Helper
1.383
316045AC1-158 PL2
Solar/Wind Helper
4.427
316450AC1-158 RIC
Solar/Wind Helper
0.369
316468AD1-105 GEN
Solar/Wind Helper
1.225
316072AD1-144
Solar/Wind Helper
0.273
315687AD1-152 GEN
Solar/Wind Helper
1.238
316156AD2-030 GEN
Solar/Wind Helper
0.366
315785AD2-033 C
Solar/Wind Helper
2.699
316337AD2-073 GEN
Solar/Wind Helper
0.373
233968AD2-076_GEN
Solar/Wind Harmer
4.275
234012AE2-112_GEN
Solar/Wind Harmer
4.275
234014AF1-036_GEN
Solar/Wind Harmer
4.275
234015AF2-250 C
Solar/Wind Harmer
0
234036AF2-325 C
Solar/Wind Harmer
0.001
233990AG1-397 GEN
Solar/Wind Harmer
-0.297
233990AG1-397 GEN
Solar/Wind Harmer
2.541
207522AF2-254 C
Solar/Wind Harmer
1.218
207528AF2-192 GEN
Solar/Wind Harmer
0.001
207484AF2-139 C O1
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
16.536
207497AE2-000G2
Solar/Wind Harmer
16.536
207507AE2-000G3
Solar/Wind Harmer
16.536
207487AE2-000G4
Solar/Wind Harmer
16.536
207442AE1-156 GEN
Solar/Wind Harmer
0.07
226929AD2-058 GEN
Solar/Wind Helper
0.12
207437AD2-070 GEN
Solar/Wind Harmer
0.066
209054AE2-059 GEN
Solar/Wind Harmer
0.001
313526AB2-022
Solar/Wind Helper
0.363
316313AB2-026
Solar/Wind Helper
0.364
207445AB1-138_GEN
Solar/Wind Harmer
0.001
209071AE2-133 GEN
Solar/Wind Harmer
0.001
209116AE2-175 GEN
Solar/Wind Harmer
0.007
209120AE2-241 GEN
Solar/Wind Harmer
1.175
209093AE2-110 GEN
Solar/Wind Harmer
1.175
3145513AHOSKIE
Solar/Wind Helper
0.234
3145513AHOSKIE
Solar/Wind Helper
0.105
233923SMA
Solar/Wind Harmer
0.009
230430AE1-229_GEN
Solar/Wind Harmer
0.025
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219908AB1-139 C
Solar/Wind Harmer
0.001
219904AC1-010 C
Solar/Wind Harmer
0.001
219906AC1-017 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0.001
219304NAMERICA C
Solar/Wind Harmer
0.124
219921AF1-264
Solar/Wind Harmer
0
231902DC CT7
Adder
20.552
231906DC3 NUG
Adder
25.708
209045AE2-271 GEN
Solar/Wind Harmer
8.4
211065PSPA IPP
Solar/Wind Harmer
0.001
211065PSPA IPP
Solar/Wind Harmer
0.001
207530AG1-191 GEN
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
209130AF1-271A GEN
Solar/Wind Harmer
1.303
209142AF1-226 GEN
Solar/Wind Harmer
2.057
205941AD2-115 GEN
Solar/Wind Harmer
0.074
209059AE2-084 GEN
Solar/Wind Harmer
1.106
20465427SHAW CT
Adder
3.815
209022WHFR IPP
Adder
2.464
270494AE1-108_GEN
Solar/Wind Helper
3.063
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.917
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
3145746EVERETS
Solar/Wind Helper
0.231
3146206CASHIE
Solar/Wind Helper
0.234
3146206CASHIE
Solar/Wind Helper
0.234
3146206CASHIE
Solar/Wind Helper
0.234
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.233
3142666NORTHAMPTON
Solar/Wind Helper
0.14
3142666NORTHAMPTON
Solar/Wind Helper
0.233
316274AC1-208 GEN
Solar/Wind Helper
1.409
316349AD2-085 GEN
Solar/Wind Helper
1.092
3156021HOLLOMANSOL
Solar/Wind Helper
1.779
313506AB2-031 GEN
Solar/Wind Helper
1.059
316006AB2-029 C
Solar/Wind Helper
0.119
316322AB2-045
Solar/Wind Helper
0.261
316359AB2-059 GEN
Solar/Wind Helper
1.743
316131AB2-060 GEN
Solar/Wind Helper
1.407
316192AB2-158 GEN
Solar/Wind Helper
1.65
316174AB2-169 GEN
Solar/Wind Helper
0.592
316087AB2-174 GEN
Solar/Wind Helper
1.632
316132AB2-190 GEN1
Solar/Wind Helper
1.376
316458AB2-190 GEN2
Solar/Wind Helper
1.376
316129AC1-054 GEN
Solar/Wind Helper
1.145
316123AC1-075 GEN
Solar/Wind Helper
1.357
316210AC1-098 GEN
Solar/Wind Helper
1.868
316212AC1-099_GEN
Solar/Wind Helper
1.038
316118AC1-105 GEN
Solar/Wind Helper
0.886
316254AC1-120 GEN1
Solar/Wind Helper
1.137
316170AC1-121 GEN2
Solar/Wind Helper
0.379
316222AC1-221 GEN
Solar/Wind Helper
1.28
316375AC2-012 GEN
Solar/Wind Helper
0.627
316283AC2-100 C
Solar/Wind Helper
1.196
316339AD2-160 GEN
Solar/Wind Helper
0.909
316164AC1-076 GEN
Solar/Wind Helper
1.184
20635028RRCT1&2
Adder
14.097
20635028RRCT1&2
Adder
13.88
20635128RRCT3&4
Adder
11.687
20635128RRCT3&4
Adder
13.398
316239AB2-077_GEN
Solar/Wind Helper
0.31
316238AB2-078_GEN
Solar/Wind Helper
0.31
316237AB2-079_GEN
Solar/Wind Helper
0.31
316140AB2-099
Solar/Wind Helper
0.089
316223AC1-118
Solar/Wind Helper
0.375
316294AC1-161 GEN
Solar/Wind Helper
4.382
316381AD1-082 GEN
Solar/Wind Helper
1.24
316233AE1-074 FULL
Solar/Wind Helper
0.37
316236AE1-162_GEN
Solar/Wind Helper
0.322
315607AA1-063A GEN
Solar/Wind Helper
1.332
20466127PORT 5CT
Adder
26.462
20465127PORT CT
Adder
2.993
20465127PORT CT
Adder
3.972
230434AG1-499 GEN
Solar/Wind Harmer
0.002
233964AF2-378 GEN
Solar/Wind Harmer
0
3130546PLYMOUTH
Solar/Wind Helper
0.235
3145543BTLEBRO
Solar/Wind Helper
0.183
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
3145543BTLEBRO
Solar/Wind Helper
0.229
3145593CAROLNA
Solar/Wind Helper
0.233
3145593CAROLNA
Solar/Wind Helper
0.233
3145683EARLEYS
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.234
3145683EARLEYS
Solar/Wind Helper
0.467
200200DELTA2 CT1
50/50
6.579
200201DELTA2 CT2
50/50
6.579
200202DELTA2 ST
50/50
11.164
207511W3-106 GEN
Solar/Wind Harmer
0.346
208972BECR K09
Solar/Wind Harmer
0
209029WAYMART-WD
Solar/Wind Harmer
0.001
223401AF1-299 GEN
Solar/Wind Helper
0.483
230407AD2-065 C
Solar/Wind Harmer
0
232422X3-066 FULL
Solar/Wind Harmer
0.154
232432Z2-076 GEN
Solar/Wind Harmer
0.025
232434Z2-077 GEN
Solar/Wind Harmer
0.079
233996TM1833_GEN
Solar/Wind Harmer
0.003
233997TMININ_4.2
Solar/Wind Harmer
0.003
233998TM1NIN_3.36
Solar/Wind Harmer
0.003
3130086AYDLETT
Solar/Wind Helper
0.955
3137643SOCKMAN
Solar/Wind Helper
0.931
3138216PACIFIC
Solar/Wind Helper
0.043
3138266HYDRAULIC
Solar/Wind Helper
0.007
3138266HYDRAULIC
Solar/Wind Helper
0.01
3138543CONSLDL
Solar/Wind Helper
0.151
3142946ENON
Solar/Wind Helper
0.024
3142946ENON
Solar/Wind Helper
0.081
3144536CHRHLND
Solar/Wind Helper
0.036
3144873MCLAUGH
Solar/Wind Helper
0.006
3145573BETHELC
Solar/Wind Helper
0.229
3145573BETHELC
Solar/Wind Helper
0.229
3145783HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.697
3145796HORNRTN
Solar/Wind Helper
0.766
3145796HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.232
3145796HORNRTN
Solar/Wind Helper
0.929
3145796HORNRTN
Solar/Wind Helper
0.743
3145796HORNRTN
Solar/Wind Helper
0.093
3145823KELFORD
Solar/Wind Helper
0.233
3145823KELFORD
Solar/Wind Helper
0.233
3145893MURPHYS
Solar/Wind Helper
0.336
3145893MURPHYS
Solar/Wind Helper
0.422
3145893MURPHYS
Solar/Wind Helper
0.084
3145893MURPHYS
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.937
3145893MURPHYS
Solar/Wind Helper
0.234
3145893MURPHYS
Solar/Wind Helper
0.633
3145933PARMELE
Solar/Wind Helper
0.462
3145933PARMELE
Solar/Wind Helper
0.231
3145933PARMELE
Solar/Wind Helper
0.231
3145963POPLR C
Solar/Wind Helper
0.233
3145963POPLR C
Solar/Wind Helper
0.233
3146033SCOT NK
Solar/Wind Helper
0.928
3146043SEABORD
Solar/Wind Helper
0.234
3146073TAR RVR
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
3146083TARBORO
Solar/Wind Helper
0.229
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146173TUNIS
Solar/Wind Helper
0.234
3146233WITAKRS
Solar/Wind Helper
0.247
3146233WITAKRS
Solar/Wind Helper
0.913
3146233WITAKRS
Solar/Wind Helper
0.156
3146263WOODLND
Solar/Wind Helper
0.233
3146263WOODLND
Solar/Wind Helper
0.233
315611Z1-036_GEN2
Solar/Wind Helper
1.304
315800Z1-036_GEN1
Solar/Wind Helper
1.304
316095T157 G97
Solar/Wind Helper
1.031
316097T157 G90
Solar/Wind Helper
1.031
316320Y1-086
Solar/Wind Helper
0.106
316321Z2-027
Solar/Wind Helper
0.363
942461AE2-259 GEN
Solar/Wind Helper
1.571
945431AF1-208 GEN
Solar/Wind Harmer
8.885
946281AF1-292 GEN
Solar/Wind Helper
0.235
960671AF2-358 GEN
Solar/Wind Harmer
23.299
961541AF2-445A GEN
Solar/Wind Harmer
1.709
961671AG1-007 GEN
Solar/Wind Helper
0.165
961941AG1-037 GEN
Solar/Wind Helper
0.079
963071AG1-156 GEN
Solar/Wind Harmer
0.37
966871AG1-558 GEN
Solar/Wind Helper
0.329
966881AG1-559 GEN
Solar/Wind Helper
0.335
970025AG2-016 GEN
Solar/Wind Harmer
2.38
970095AG2-074 GEN
Solar/Wind Harmer
4.21
970277AG2-181 GEN
Solar/Wind Harmer
1.087
970453AG2-297 GEN
Solar/Wind Harmer
3.805
970545AG2-347 GEN
Solar/Wind Harmer
47.124
970597AG2-380 GEN
Solar/Wind Harmer
7.657
970665AG2-430 GEN
Solar/Wind Harmer
4.817
970695AG2-447 GEN
Solar/Wind Harmer
4.667
970757AG2-479 GEN
Solar/Wind Harmer
0.524
970761AG2-481 GEN
Solar/Wind Harmer
0.54
970997AG2-616 GEN
Solar/Wind Harmer
10.614
971007AG2-625 GEN
Solar/Wind Harmer
1.689
971009AG2-626 GEN
Solar/Wind Harmer
1.078
971011AG2-627 GEN
Solar/Wind Harmer
7.817
971149AH1-027 GEN
Solar/Wind Harmer
5.838
971189AH1-054 GEN
Solar/Wind Harmer
0.99
971195AH1-057 GEN
Solar/Wind Harmer
1.166
971519AH1-257 GEN
Solar/Wind Harmer
1.653
971521AH1-258 GEN
Solar/Wind Harmer
2.157
971535AH1-265 GEN
Solar/Wind Harmer
4.015
971553AH1-274 GEN
Solar/Wind Harmer
2.315
971667AH1-334 GEN
Solar/Wind Harmer
2.291
219221BRL12CT1
Adder
12.077
219222BRL12CT2
Adder
12.077
219223BRL12CT3
Adder
12.077
219224BRL12CT4
Adder
12.077
219912AD2-042 GEN
Solar/Wind Harmer
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.425
316431W1029_GEN1
Solar/Wind Helper
0.961
316433W1029_GEN2
Solar/Wind Helper
0.961
316435W1029_GEN3
Solar/Wind Helper
0.961
957601AF2-054 GEN
Solar/Wind Helper
0.325
957831AF2-077 GEN
Solar/Wind Helper
0.326
964001AG1-254 GEN
Solar/Wind Harmer
0.57
964211AG1-282 GEN
Solar/Wind Helper
0.329
965821AG1-450 GEN
Solar/Wind Harmer
9.708
966001AG1-469 GEN
Solar/Wind Helper
0.262
966111AG1-480 GEN
Solar/Wind Harmer
3.341
966181AG1-487 GEN
Solar/Wind Harmer
3.755
966421AG1-511 GEN
Solar/Wind Harmer
6.043
966621AG1-532 GEN
Solar/Wind Helper
0.213
971747AH1-380 GEN
Solar/Wind Harmer
4.665
971983AH1-536 GEN
Solar/Wind Harmer
3.238
972069AH1-584 GEN
Solar/Wind Harmer
11.662
972071AH1-585 GEN
Solar/Wind Harmer
11.662
972073AH1-586 GEN
Solar/Wind Harmer
17.493
972133AH1-634 GEN
Solar/Wind Harmer
6.882
972141AH1-641 GEN
Solar/Wind Harmer
4.921
972177AH1-672 GEN
Solar/Wind Harmer
19.001
972233AH1-701 GEN
Adder
6.066
972237AH1-703 GEN
Adder
11.481
972241AH1-705 GEN
Adder
3.392
972245AH1-707 GEN
Adder
3.835
972251AH1-710 GEN
Adder
80.295
972275AH1-722 GEN
Adder
36.902
233950AC2-186 GEN
Solar/Wind Harmer
0.001
233952AC2-187 GEN
Solar/Wind Harmer
0.002
233954AC2-188 GEN
Solar/Wind Harmer
0.002
972260AH1-715 GEN1
Adder
16.074
972261AH1-715 GEN2
Adder
18.52
G-007ALTFEXP_G-007A->PJM
CMTX
61.304
VTFLTFEXP_VFT->PJM
CMTX
154.687
HAMLETPJM->LTFIMP_HAMLET
CLTF
5.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
3.365
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
22.861
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
4.88
BlueGrassPJM->LTFIMP_BlueG
CLTF
15.2
CBM NorthLTFEXP_CBM-N->PJM
CBM
75.856
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0

Details for PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:PJM
Facility Description:
PCHBTM1S-CNASTONE 500.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.38 %
Rating:2920.0 MVA
Rating Type:A
MVA to Mitigate:3748.6
MW Contribution:0.55
Bus #Bus NameTypeMW Contribution
200052ROCKSP 1
50/50
3.132
200053ROCKSP 2
50/50
3.066
200054ROCKSP 3
50/50
3.164
200055ROCKSP 4
50/50
3.097
200203Y1-065-STG
50/50
8.6
200204Y1-065-CTG1
50/50
4.96
200205Y1-065-CTG2
50/50
4.96
20486527WR_V4-052
Adder
0.596
20628028LAKEHURS
Adder
1.83
20628028LAKEHURS
Adder
0.925
20633028GILCT9
Adder
23.745
20635828PARLN1&2
Adder
3.142
20635828PARLN1&2
Adder
6.938
20635928PARLN3&4
Adder
3.142
20635928PARLN3&4
Adder
6.938
20636028O CRK C1
Adder
6.939
20636128O CRK C2
Adder
6.327
20671828STAW2-080
Solar/Wind Harmer
0
20671928W4-073
Solar/Wind Harmer
0
20673628F1S_V4-069
Solar/Wind Harmer
0
20673728F2S_V4-070
Solar/Wind Harmer
0
20673828FLE_V3-070
Solar/Wind Harmer
0
20674128FR_U2-059
Solar/Wind Harmer
0
20674328GAR_V4-001
Solar/Wind Harmer
0
20674528F3S_W2-016
Solar/Wind Harmer
0
20674628WNG_W3-110
Solar/Wind Harmer
0
20674828DL_W4-046
Solar/Wind Harmer
0
20674928WA_W3-044
Solar/Wind Harmer
0.001
20675128HRM_W1-127
Solar/Wind Harmer
0
20675428EAM_W2-061
Solar/Wind Harmer
0
20675728RH_W2-091
Solar/Wind Harmer
0.001
20675828AU_W4-064
Solar/Wind Harmer
0
20675928HOL_W4-097
Solar/Wind Harmer
0
20676128MHD_W3-029
Solar/Wind Harmer
0
20676228FRD_X1-012
Solar/Wind Harmer
0.001
20676328BVR_Y1-020
Solar/Wind Harmer
0
20676428JCR_X2-075
Solar/Wind Harmer
0
20676728BRNX1-095
Solar/Wind Harmer
0
20714328BYD_X4-031
Solar/Wind Harmer
0.146
20714428HOW_X1-037
Solar/Wind Harmer
0.001
20714528FRN_Y2-051
Solar/Wind Harmer
0
20714828MDF_W3-079
Solar/Wind Harmer
0.095
20714928UPF_X1-085
Solar/Wind Harmer
0
20715028HAN_X4-015
Solar/Wind Harmer
0
20715228NPK_W1-113
Solar/Wind Harmer
0
20715728PEM_W1-119
Solar/Wind Harmer
0.001
20715828PEM_W1-120
Solar/Wind Harmer
0.001
20716028EGP_W2-019
Solar/Wind Harmer
0
20716228APLW2-078
Solar/Wind Harmer
0
20716428NHV_W2-082
Solar/Wind Harmer
0
20716928W4-060COL
Solar/Wind Harmer
0
20717128DIX_Z2-102
Solar/Wind Harmer
0
20720428HOL_W1-112
Solar/Wind Harmer
0
20720528MAN_W1-024
Solar/Wind Harmer
0
20720628TIN_W1-124
Solar/Wind Harmer
0.001
20720728JCB_W1-129
Solar/Wind Harmer
0
20720828JCB_W4-025
Solar/Wind Harmer
0
207408W3-077 C
Solar/Wind Harmer
0
213497CHSTR7-9
Adder
2.778
213497CHSTR7-9
Adder
2.778
213497CHSTR7-9
Adder
2.778
213535CROYDN11
Adder
10.197
213560DLW11-12
Adder
2.717
213560DLW11-12
Adder
2.717
213561DLWR9-10
Adder
3.553
213561DLWR9-10
Adder
2.717
213587EDDYSTN3
Adder
81.01
213589EDDYSTN4
Adder
81.023
213611FALLS1-3
Adder
3.479
213611FALLS1-3
Adder
3.479
213611FALLS1-3
Adder
3.479
213815MOSER1-3
Adder
3.51
213815MOSER1-3
Adder
3.51
213815MOSER1-3
Adder
3.51
213942SCHUYLKILL
Adder
2.734
213942SCHUYLKILL
Adder
3.576
213957STHWK3-4
Adder
2.734
213957STHWK3-4
Adder
2.734
213958STHWK5-6
Adder
2.734
213958STHWK5-6
Adder
2.734
214067T20SOLAR
Solar/Wind Harmer
0
214194N WALES4
Adder
0.831
217213AMBOY SO C
Solar/Wind Harmer
0
231131BLOOM ENRGY
Adder
5.507
231907DC10
Adder
4.416
231917EM10
Adder
2.823
231918WEST 1
Adder
4.059
231919CHRIST1
Adder
5.339
231920CHRIST2
Adder
5.22
231940T-011
Adder
0.96
232404W1-003 C
Solar/Wind Harmer
0.834
232408W1-005 C
Solar/Wind Harmer
0.834
232410W1-006 C
Solar/Wind Harmer
0.834
232416X2-083
Adder
0.557
232417X3-008 C
Solar/Wind Harmer
0.002
232426Y1-080 FULL
Solar/Wind Harmer
0
232428Y3-058 C
Solar/Wind Harmer
0.002
232813VAUGHN
Adder
0.753
232901NORTHST
Adder
10.747
232904IR4
Adder
104.145
232907VN8
Adder
38.637
232910NRG_G1
Adder
11.02
232912OH NUG1
Adder
11.371
232913OH NUG2
Adder
11.219
232914OH NUG3
Adder
11.371
232915OH NUG4
Adder
11.295
232916OH NUG5
Adder
11.371
232917OH NUG6
Adder
11.32
232918OH NUG7
Adder
11.295
232919VN10
Adder
3.609
232920IR10
Adder
4.07
232921TASLEY2G
Adder
6.645
232926CRISFLD1
Adder
2.527
209027LOR2_Q27
Solar/Wind Harmer
0.001
212266LOR1
Solar/Wind Harmer
0.354
217083KRNY_132
Adder
8.384
217083KRNY_132
Adder
8.438
217086KRNY_131
Adder
8.456
217086KRNY_131
Adder
8.366
217121ECCF
Adder
0.394
217146KRNY_1234
Adder
7.865
217146KRNY_1234
Adder
7.811
217147KRNY_1212
Adder
8.026
217147KRNY_1212
Adder
7.883
217167KRNY_14
Adder
8.438
217186ESSEX_G9
Adder
14.514
217197RE CRAN C
Solar/Wind Harmer
0
218404KENILWRTH C
Adder
1.189
218418LINDEN_G5
Adder
15.845
218419LINDEN_G6
Adder
15.845
218438BLK ROCK C
Solar/Wind Harmer
0
218440SUMMTASSOC C
Solar/Wind Harmer
0
218449LINSOLAR C
Solar/Wind Harmer
0
218455CINNBAY_CGEN
Adder
1.7
218660EHAMPSOLAR C
Solar/Wind Harmer
0
219035LINDEN_G8
Adder
15.126
219036LINDEN_G7
Adder
15.345
219114HARTZY_C
Solar/Wind Harmer
0
219272CLEANLIGHT C
Solar/Wind Harmer
0
219276PARKLANDSO C
Solar/Wind Harmer
0
219287REEVESEAST C
Solar/Wind Harmer
0
219348LDSOLAR C
Solar/Wind Harmer
0.001
219607WPEMNERT C
Solar/Wind Harmer
0
219610FLORENCE C
Solar/Wind Harmer
0.001
219612MATRIX C
Solar/Wind Harmer
0
219615MILLCREEK C
Solar/Wind Harmer
0
219766PARADISE C
Solar/Wind Harmer
0
227927V4-067C
Solar/Wind Harmer
0
228202CUMB CT
Adder
17.7
228206SHRMN CT
Adder
17.734
228251CARLLS#4
Adder
0.671
228260V4-054C
Solar/Wind Harmer
0
228304LOGAN
Adder
25.354
228304LOGAN
Adder
22.803
228307PCLP GT
Adder
12.711
228309CCLP NUG
Adder
27.422
228309CCLP NUG
Adder
26.085
228711V2-041C
Solar/Wind Harmer
0
20462827N BANGR8
Adder
0.606
20467927PC_Q59Y356
Adder
0.474
228728W1-130C
Solar/Wind Harmer
0
228729W2-030 C
Solar/Wind Harmer
0.001
228732V1-021 C
Adder
0.202
200034PCHBTM 2
50/50
25.408
200035PCHBTM 3
50/50
25.122
232406W1-004 FULL
Solar/Wind Harmer
0.834
232436AB1-176 C
Solar/Wind Harmer
0
200192DELTA CT1
50/50
2.439
200193DELTA CT2
50/50
2.439
200194DELTA CT3
50/50
2.439
200195DELTA ST
50/50
3.77
217194REDH C
Solar/Wind Harmer
0
223402AF1-300 C
Solar/Wind Helper
0.594
230415AB2-049 C
Solar/Wind Harmer
0
20742028HF_AC1-207
Solar/Wind Harmer
0.001
207454AA2-184 E
Solar/Wind Harmer
0.001
207459AE1-142 C O1
Solar/Wind Harmer
0.001
208909MACR G3
Adder
133.569
209009PEIP 2
Adder
5.98
209010PEIP 1
Adder
2.709
209010PEIP 1
Adder
0.397
209010PEIP 1
Adder
0.493
209018SUNBIPCT
Adder
5.067
209023WIENIPP1
Adder
8.312
209025WIENIPP3
Adder
4.065
209025WIENIPP3
Adder
4.149
209026WIENIPP4
Adder
4.107
232424Y1-079 C
Solar/Wind Harmer
0.001
232899W1-062
Adder
12.388
232900DEMECSMY
Adder
11.882
232905CHERITON_25
Adder
3.158
218524CNTRALGAS1 C
Solar/Wind Harmer
0.711
218526CNTRALGAS2 C
Solar/Wind Harmer
0.713
226910AB2-157 C
Solar/Wind Helper
0.017
233900O-025 C
Adder
1.516
233901CHERRYDALE C
Solar/Wind Harmer
0.002
233939AC1-091 C
Solar/Wind Harmer
0.002
233940AF2-379 C
Solar/Wind Harmer
0
233970AC1-092 C
Solar/Wind Harmer
0.002
233971AC1-093 C
Solar/Wind Harmer
0.055
233972AC1-094 C
Solar/Wind Harmer
0.406
233973AC2-185 C
Solar/Wind Harmer
0.002
212174INGE
Adder
0.792
212507AE2-042_GEN
Solar/Wind Harmer
0.425
219727YARDVSOLFA C
Solar/Wind Harmer
0
219907AC1-030 C
Solar/Wind Harmer
0
219914AD2-027 C
Solar/Wind Harmer
0.001
228754AB1-001 C
Solar/Wind Harmer
0
230422AE1-104_GEN1
Solar/Wind Harmer
14.353
230425AE1-104_GEN2
Solar/Wind Harmer
14.353
228351V2-046C
Solar/Wind Harmer
0.001
967451AG2-055 C O1
Solar/Wind Harmer
235.168
233944AB2-135 GEN
Solar/Wind Harmer
0.006
233946AB2-136 GEN
Solar/Wind Harmer
0.005
233994AC2-023 GEN
Solar/Wind Harmer
0.005
234033AF1-007_GEN
Solar/Wind Harmer
-0.001
233984AB2-036 GEN
Solar/Wind Harmer
9.238
233982AB2-133 GEN
Solar/Wind Harmer
0.005
233915AB1-141 GEN
Solar/Wind Harmer
0.323
233918AB1-142 GEN
Solar/Wind Harmer
0.323
233930AB2-032 GEN
Solar/Wind Harmer
1.205
233987AB2-037 GEN
Solar/Wind Harmer
0.014
233933AB2-153 GEN
Solar/Wind Harmer
0.002
233955AB2-172 GEN
Solar/Wind Harmer
0.004
233935AB2-179 C
Solar/Wind Harmer
1.683
234041AC1-190 GEN
Solar/Wind Harmer
9.357
233968AD2-076_GEN
Solar/Wind Harmer
2.939
234012AE2-112_GEN
Solar/Wind Harmer
2.939
234014AF1-036_GEN
Solar/Wind Harmer
2.939
234015AF2-250 C
Solar/Wind Harmer
0
234036AF2-325 C
Solar/Wind Harmer
0.001
233990AG1-397 GEN
Solar/Wind Harmer
-0.205
233990AG1-397 GEN
Solar/Wind Harmer
1.753
207522AF2-254 C
Solar/Wind Harmer
0.912
207528AF2-192 GEN
Solar/Wind Harmer
0.001
207484AF2-139 C O1
Solar/Wind Harmer
0
207510AF2-138 C
Solar/Wind Harmer
0.001
207500AE2-000G1
Solar/Wind Harmer
12.415
207497AE2-000G2
Solar/Wind Harmer
12.415
207507AE2-000G3
Solar/Wind Harmer
12.415
207487AE2-000G4
Solar/Wind Harmer
12.415
207442AE1-156 GEN
Solar/Wind Harmer
0.055
226929AD2-058 GEN
Solar/Wind Helper
0.113
207437AD2-070 GEN
Solar/Wind Harmer
0.056
209054AE2-059 GEN
Solar/Wind Harmer
0.001
207445AB1-138_GEN
Solar/Wind Harmer
0.001
209071AE2-133 GEN
Solar/Wind Harmer
0.001
209116AE2-175 GEN
Solar/Wind Harmer
0.006
209120AE2-241 GEN
Solar/Wind Harmer
1.154
209093AE2-110 GEN
Solar/Wind Harmer
1.154
233923SMA
Solar/Wind Harmer
0.006
230430AE1-229_GEN
Solar/Wind Harmer
0.018
219686LUMSOLAR_N C
Solar/Wind Harmer
0
219688LUMSOLAR_S C
Solar/Wind Harmer
0
219908AB1-139 C
Solar/Wind Harmer
0
219904AC1-010 C
Solar/Wind Harmer
0
219906AC1-017 C
Solar/Wind Harmer
0
219623KINSLEYBEA C
Solar/Wind Harmer
0
219258KINSLEYDEP C
Solar/Wind Harmer
0
219304NAMERICA C
Solar/Wind Harmer
0.091
219921AF1-264
Solar/Wind Harmer
0
231902DC CT7
Adder
14.142
231906DC3 NUG
Adder
17.69
209045AE2-271 GEN
Solar/Wind Harmer
8.301
211065PSPA IPP
Solar/Wind Harmer
0
211065PSPA IPP
Solar/Wind Harmer
0
207530AG1-191 GEN
Solar/Wind Harmer
0.001
230511AF1-262
Solar/Wind Harmer
0
209130AF1-271A GEN
Solar/Wind Harmer
1.334
209142AF1-226 GEN
Solar/Wind Harmer
2.019
205941AD2-115 GEN
Solar/Wind Harmer
0.073
209059AE2-084 GEN
Solar/Wind Harmer
1.116
20465427SHAW CT
Adder
3.263
209022WHFR IPP
Adder
2.386
20635028RRCT1&2
Adder
11.011
20635028RRCT1&2
Adder
10.841
20635128RRCT3&4
Adder
9.128
20635128RRCT3&4
Adder
10.465
20465527S.RDG CT
Adder
1.467
20465527S.RDG CT
Adder
1.516
20466127PORT 5CT
Adder
22.531
20465127PORT CT
Adder
2.549
20465127PORT CT
Adder
3.383
230434AG1-499 GEN
Solar/Wind Harmer
0.001
233964AF2-378 GEN
Solar/Wind Harmer
0
200200DELTA2 CT1
50/50
4.366
200201DELTA2 CT2
50/50
4.366
200202DELTA2 ST
50/50
7.408
207511W3-106 GEN
Solar/Wind Harmer
0.286
208972BECR K09
Solar/Wind Harmer
0
209029WAYMART-WD
Solar/Wind Harmer
0.001
223401AF1-299 GEN
Solar/Wind Helper
0.594
230407AD2-065 C
Solar/Wind Harmer
0
232422X3-066 FULL
Solar/Wind Harmer
0.106
232432Z2-076 GEN
Solar/Wind Harmer
0.017
232434Z2-077 GEN
Solar/Wind Harmer
0.054
233996TM1833_GEN
Solar/Wind Harmer
0.002
233997TMININ_4.2
Solar/Wind Harmer
0.002
233998TM1NIN_3.36
Solar/Wind Harmer
0.002
945431AF1-208 GEN
Solar/Wind Harmer
6.401
960671AF2-358 GEN
Solar/Wind Harmer
16.06
961541AF2-445A GEN
Solar/Wind Harmer
1.654
963071AG1-156 GEN
Solar/Wind Harmer
0.339
970025AG2-016 GEN
Solar/Wind Harmer
1.791
970095AG2-074 GEN
Solar/Wind Harmer
3.86
970277AG2-181 GEN
Solar/Wind Harmer
0.749
970453AG2-297 GEN
Solar/Wind Harmer
2.736
970545AG2-347 GEN
Solar/Wind Harmer
32.517
970597AG2-380 GEN
Solar/Wind Harmer
5.264
970665AG2-430 GEN
Solar/Wind Harmer
4.932
970695AG2-447 GEN
Solar/Wind Harmer
3.227
970757AG2-479 GEN
Solar/Wind Harmer
0.536
970761AG2-481 GEN
Solar/Wind Harmer
0.545
970997AG2-616 GEN
Solar/Wind Harmer
7.649
971007AG2-625 GEN
Solar/Wind Harmer
1.423
971009AG2-626 GEN
Solar/Wind Harmer
0.908
971011AG2-627 GEN
Solar/Wind Harmer
5.638
971149AH1-027 GEN
Solar/Wind Harmer
4.034
971189AH1-054 GEN
Solar/Wind Harmer
0.745
971195AH1-057 GEN
Solar/Wind Harmer
0.804
971519AH1-257 GEN
Solar/Wind Harmer
1.394
971521AH1-258 GEN
Solar/Wind Harmer
1.661
971535AH1-265 GEN
Solar/Wind Harmer
2.903
971553AH1-274 GEN
Solar/Wind Harmer
1.667
971667AH1-334 GEN
Solar/Wind Harmer
1.73
219221BRL12CT1
Adder
8.91
219222BRL12CT2
Adder
8.91
219223BRL12CT3
Adder
8.91
219224BRL12CT4
Adder
8.91
219912AD2-042 GEN
Solar/Wind Harmer
0.001
227287AC2-120 GEN
Solar/Wind Helper
0.412
964001AG1-254 GEN
Solar/Wind Harmer
0.411
965821AG1-450 GEN
Solar/Wind Harmer
6.692
966111AG1-480 GEN
Solar/Wind Harmer
2.857
966181AG1-487 GEN
Solar/Wind Harmer
3.204
966421AG1-511 GEN
Solar/Wind Harmer
5.123
971747AH1-380 GEN
Solar/Wind Harmer
3.217
971983AH1-536 GEN
Solar/Wind Harmer
2.225
972069AH1-584 GEN
Solar/Wind Harmer
8.044
972071AH1-585 GEN
Solar/Wind Harmer
8.044
972073AH1-586 GEN
Solar/Wind Harmer
12.066
972133AH1-634 GEN
Solar/Wind Harmer
4.749
972141AH1-641 GEN
Solar/Wind Harmer
3.547
972177AH1-672 GEN
Solar/Wind Harmer
13.114
972233AH1-701 GEN
Adder
4.382
972237AH1-703 GEN
Adder
9.187
972241AH1-705 GEN
Adder
3.724
972245AH1-707 GEN
Adder
3.816
972251AH1-710 GEN
Adder
56.349
972275AH1-722 GEN
Adder
29.13
233950AC2-186 GEN
Solar/Wind Harmer
0.001
233952AC2-187 GEN
Solar/Wind Harmer
0.002
233954AC2-188 GEN
Solar/Wind Harmer
0.002
972260AH1-715 GEN1
Adder
12.688
972261AH1-715 GEN2
Adder
14.689
G-007ALTFEXP_G-007A->PJM
CMTX
47.883
VTFLTFEXP_VFT->PJM
CMTX
123.421
HAMLETPJM->LTFIMP_HAMLET
CLTF
4.146
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
2.452
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
16.337
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
3.478
BlueGrassPJM->LTFIMP_BlueG
CLTF
10.836
CBM NorthLTFEXP_CBM-N->PJM
CBM
63.205
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CONTINGENCY 'DVP_P1-2: LN 9354_SRT-A'
 OPEN BRANCH FROM BUS 313400 TO BUS 313403 CKT 1   /*8GOLDEN      500.0 - 8ASPEN       500.0
END
CONTINGENCY 'PECO_P1-2_5012_SRT-A'
 TRIP BRANCH FROM BUS 200064 TO BUS 200004 CKT 1   /*PCHBTM1S     500.0 - CNASTONE     500.0
END
CONTINGENCY 'AP_P1-2_PE-500-3835T_SRT-A'
 DISCONNECT BRANCH FROM BUS 270095 TO BUS 235105 CKT 1   /*CHAN         500.0 - 01DOUBS      500.0
END
CONTINGENCY 'PECO_P1-2_5007_SRT-A
 TRIP BRANCH FROM BUS 200066 TO BUS 270095 CKT 1   /*PCHBTM1N     500.0 - CHAN         500.0
END
972284 to 314933 ckt 1
270095 to 235105 ckt 1
200004 to 200003 ckt 1
200064 to 200004 ckt 1

Winter Peak Analysis

The New Service Request AG2-481 was evaluated as a 0.0 MW (4.1 MW Capacity) injection in the PPL area.

AG2-481 was evaluated as part of a plant. The plant consists of AG2-481. The total Energy output of the plant was evaluated at its maximum seasonal capability of 20.0 MW (0.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-481 was evaluated as a 0.0 MW injection

AG2-481 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 20.0 MW (0.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage analysis is not performed as part of the Phase I System Impact Study. Steady State Voltage analysis will commence in the Phase II System Impact Study.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-038Lexington-Low Moor 230kVUnder Construction
AA1-050Tarboro-Everetts 230kVIn Service
AA1-063ACarolina–Seaboard 115kVIn Service
AA1-067Everetts 34.5kVIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA1-139Hickory-Shawboro 230kVIn Service
AA2-053Carolina-Jackson 115kVIn Service
AA2-057Hornertown-Whitakers 115kVIn Service
AA2-133Wyalusing 34.5kVIn Service
AA2-174Carolina-Jackson 115kVIn Service
AA2-178Mackeys 230kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-081Anaconda-Mayo Dunbar 115kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-132Thelma 230kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB2-022Elizabeth City 34.5kVIn Service
AB2-025Sapony 34.5kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-031Brink-Trego 115kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-036Church - Oil City 138kVSuspended
AB2-037Keeney-Steele 230kVUnder Construction
AB2-040Brink 115kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-049Gloucester Township 12kVIn Service
AB2-059Benson-Dunbar 115kVIn Service
AB2-060Chase City-Lunenburg 115kVIn Service
AB2-077Buggs Island-Chase City 115kVIn Service
AB2-078Buggs Island-Chase City 115kVIn Service
AB2-079Buggs Island-Chase City 115kVIn Service
AB2-099Ahoskie 34.5kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-134Hopewell-Surry 230kVIn Service
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-169Pantago-Five Points 115kVIn Service
AB2-172Todd 69kVIn Service
AB2-174Emporia-Trego 115kVIn Service
AB2-179Townsend 138kVIn Service
AB2-190Hopewell-Surry 230kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-027Pendleton 34.5kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-036Twittys Creek 34.5kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-054Kerr Dam–Eatons Ferry 115 kVIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-098Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-099Dawson-South Justice 115kVPartially in Service - Under Construction
AC1-105Halifax-Mt. Laurel 115kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-147Grassfield 34.5kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-161Septa 500kVIn Service
AC1-189Chinquapin-Everetts 230kVUnder Construction
AC1-190East New Market 69kVSuspended
AC1-191Elmont 115kVEngineering & Procurement
AC1-208Cox-Whitakers 115kVUnder Construction
AC1-221Halifax-Person 230kVIn Service
AC1-222Crystal Hill-Halifax 115kVIn Service
AC2-012Grassfield-Great Bridge 115kVIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-100Halifax-Person 230kVIn Service
AC2-120Ripley 69kVIn Service
AC2-123Jacksons Ferry 138kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-141Septa 500kVEngineering & Procurement
AC2-165Bremo-Powhatan 230kVSuspended
AC2-185Cedar Creek 138kV IIEngineering & Procurement
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-025Hopewell-Surry 230 kVUnder Construction
AD1-033Fentress-Landstown 230 kVIn Service
AD1-041Harmony Village-Shackleford 115 kVIn Service
AD1-056Hornertown-Hathaway 230 kVSuspended
AD1-057Hornertown-Hathaway 230 kVSuspended
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-074Trowbridge 230 kVEngineering & Procurement
AD1-075Trowbridge 230 kVEngineering & Procurement
AD1-076Trowbridge 230 kVEngineering & Procurement
AD1-082Bakers Pond-Ivor 115kVIn Service
AD1-087Clover-Sedge Hill 230 kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-144Kings Fork 34.5 kVIn Service
AD1-152Clover-Sedge Hill 230 kVIn Service
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-022East Danville - Roxborough 230 kVEngineering & Procurement
AD2-023East Danville - Roxborough 230 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-030Wan 34.5 kVIn Service
AD2-033Chase City-Lunenburg 115 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-058St. Barnabas 13 kVIn Service
AD2-062Roxbury-Greene 138 kVSuspended
AD2-065Atco 12 kVIn Service
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-076Carville 138 kVSuspended
AD2-085Myrtle-Windsor DP 115kVEngineering & Procurement
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-160Hickory-Moyock 230kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AD2-202Clover-Sedge Hill 230kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-072Shawboro-Sligo 230 kVUnder Construction
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-103Holland-Union Camp 115 kVUnder Construction
AE1-104BL England 138 kVSuspended
AE1-108Bremo-Scottsville 138 kVEngineering & Procurement
AE1-109Frenchs Mill 34 kVIn Service
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-162Smithfield 34.5 kVIn Service
AE1-175Light Foot 34.5 kVIn Service
AE1-185Hokes-Jackson 69 kVIn Service
AE1-190Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-191Harmony Village-Shackleford 115 kVPartially in Service - Under Construction
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-226Face Rock-Kinzer #13 69 kVWithdrawn
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-034Mackeys 230 kVPartially in Service - Under Construction
AE2-042Milton 69 kVIn Service
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-084Derry Tap-Derry Bus 69 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-110Columbia-West Bloomsburg 69 kVSuspended
AE2-112Carville 138 kV IISuspended
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-211Jackson-Three Mile Island 230 kVSuspended
AE2-212Harrowgate 34 kVEngineering & Procurement
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-241Bloomsburg-Columbia 69 kVSuspended
AE2-253Hickory-Moyock 230 kVIn Service
AE2-259Curdsville-Willis Mtn 115 kVEngineering & Procurement
AE2-271Montour 230 kVWithdrawn
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-333Bedington 138 kVSuspended
AE2-345Hunterstown-Texas Eastern Tap 115 kVSuspended
AE2-346Ahoskie 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-032Suffolk 34.5 kVIn Service
AF1-036Carville 138 kV IIISuspended
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-049Berry Hill 138 kVUnder Construction
AF1-058Welco 34.5 kVIn Service
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-208Laurel-Roadstown 69 kVWithdrawn
AF1-226Bowmans Mill-Scott 69 kVSuspended
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-271AGratz 69 kVSuspended
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291Tyler 34.5 kVEngineering & Procurement
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-292Fields 34.5kVEngineering & Procurement
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF2-043Suffolk 34.5 kVIn Service
AF2-054Wan 34.5 kVIn Service
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-077White Marsh 34.5 kVIn Service
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-144Powhatan 34.5 kVIn Service
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-250Edgewood 12 kV IIIIn Service
AF2-254Cookstown-New Lisbon 34.5 kVSuspended
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-358Airey-Vienna 69 kVActive
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-383Tolna 115 kVWithdrawn
AF2-445AFishbach-Port Carbon 69 kVSuspended
AG1-007Tar River 12.5 kVEngineering & Procurement
AG1-037Ahoskie 34.5 kVEngineering & Procurement
AG1-145Lightfoot 34.5 kVIn Service
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-362Wernersville 12.47 kVSuspended
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-397Walston 12 kVWithdrawn
AG1-450Airey-Vienna 69 kV IIActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-487Gilbert 230 kVWithdrawn
AG1-499Lambs 12.47 kVUnder Construction
AG1-511Kittatinny 230 kVEngineering & Procurement
AG1-515Guilford 138 kVWithdrawn
AG1-532Fields 34.5 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-016Oyster Creek-Whitings 34.5 kVActive
AG2-055Deans 500 kVWithdrawn
AG2-074Meckesville Tap 69kVActive
AG2-181Airey - Golden Hill 69 kVActive
AG2-182Doubs-Bismark 500 kVActive
AG2-279Hagerstown-Conservit 34.5 kVActive
AG2-297Cumberland 230 kVActive
AG2-347Indian River 230 kV IIActive
AG2-380Carville 138 kV IVActive
AG2-423Cherry Run–Harmony 138 kVActive
AG2-430Sunbury-Dalmatia 69 kV IIActive
AG2-439Oxbow 34.5 kVActive
AG2-447Cedar Creek 138 kV VIIActive
AG2-477Hokes-Jackson 69 kV IIIActive
AG2-478Hokes-Jackson 69 kV IVActive
AG2-479Penns Tap-Richfield Tie 69 kV IIActive
AG2-484Mifflintown Bus-Mifflintown Tap 69 kV IIActive
AG2-616Churchtown - Upper Pittsgrove 138 kVActive
AG2-625Pequest River-Furnace Brook Tap 34.5 kV IIActive
AG2-626Pequest River-Furnace Brook Tap 34.5 kV IIIActive
AG2-627Woodstown-High Street 69 kVActive
AH1-027Cartanza 230 kVActive
AH1-054Upton-Whitings 34.5 kVActive
AH1-057Edgewood 12.47 kVActive
AH1-257Broadway - Washington 34.5 kVActive
AH1-258Belford - Keansburg 34.5 kVActive
AH1-265Winslow - Monroe 69kVActive
AH1-274Butler 69 kVActive
AH1-334Lakehurst - Whitings 34.5 kVActive
AH1-380Mt Olive - Kenny 69kVActive
AH1-536Church-Oil City 138kVActive
AH1-584Nelson-Indian River 138kVActive
AH1-585Nelson-Indian River 138kVActive
AH1-586Nelson-Indian River 138kVActive
AH1-634Indian River 230kV IActive
AH1-641Churchtown - Upper Pittsgrove 138kVActive
AH1-672Farmview 138 kVActive
AH1-695Three Mile Island 230 kVActive
AH1-701Valero 69 kVActive
AH1-703Bergen 230kVActive
AH1-705Sunbury #1 500kVActive
AH1-707Saegers 230 kVActive
AH1-710Salem 500kVActive
AH1-715Linden 230kVActive
AH1-720East Towanda 230 kVActive
AH1-722Linden 230kVActive
AH1-725Conastone 500 kVActive
AH1-727Brambleton-Goose Creek 500kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-021Cape May County 12kVIn Service
V2-041Clayville 12kVIn Service
V2-046Pilesgrove Township 12kVIn Service
V4-054Fairfield Township 12kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-062Clayton 138kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W3-106Sussex-Wykertown 34.5kVIn Service
X2-083Newark 12kVIn Service
X3-008Todd 69kVIn Service
X3-066Church Hill 69kVIn Service
Y1-065Rock Springs 500kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y1-086Morgans CornerIn Service
Y3-058Rockawalkin 69kVIn Service
Z1-036WinFall-Chowan 230kVIn Service
Z2-027Pasquotank 34.5kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.50
Title
Bring the Peach Bottom-Delta Power Plant 500 kV line “in and out” of North Delta
Description
Bring the Peach Bottom-Delta Power Plant 500 kV line “in and out” of North Delta by constructing a new Peach Bottom-North Delta 500 kV (0.3 miles) cut-in and cut-out lines.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.11
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3780.11
Title
Brighton Statcom and Capacitor (Projected ISD 12/31/2028)
Description
Brighton Statcom and capacitor New STATCOM rating: 350 MVAR New capacitor rating: 350 MVAR
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.5
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.5
Title
Build Solley Road substation + Statcom (Projected ISD 12/31/2028)
Description
Build Solley Road substation + Statcom. New STATCOM rating: 350 MVAR Add 4x 230 kV breakers bays.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.26
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.26
Title
Build High Ridge 500 kV substation - Three bay breaker and half configuration (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.27
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.27
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) - Waugh Chapel side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.29
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.29
Title
High Ridge termination for the North Delta-High Ridge 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.30
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.30
Title
High Ridge - Install two 500/230 kV transformers (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.31
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.31
Title
Build new North Delta-High Ridge 500 kV line - PECO Portion (Projected ISD 12/1/2030)
Description
None
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.32
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.32
Title
Build new North Delta-High Ridge 500 kV line - BGE Portion (Projected ISD 12/31/2030)
Description
Build new North Delta-High Ridge 500 kV line. (~59 miles)
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.48
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.48
Title
North Delta termination for the North Delta-High Ridge 500 line (Transource work).
Description
None
Cost Information
Time Estimate
Dec 15 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.49
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.49
Title
North Delta 500 kV termination for the Calpine generator (Calpine/Transource work).
Description
None
Cost Information
Time Estimate
Oct 06 2027

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.44
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.44
Title
North Delta termination for the North Delta-High Ridge 500 line (PECO work).
Description
None
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.13
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.13
Title
Batavia Road to Riverside 230 kV reconductor
Description
Batavia Road to Riverside 230 kV reconductor New rating: 1941 MVA SN / 2181 MVA SE
Cost Information
Time Estimate
Dec 31 2027

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.36
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.36
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton BGE) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.343
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.343
Title
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Description
Uprate bus at Brambleton to support 500kV Line #558 (Aspen to Brambleton) uprate.
Cost Information
Time Estimate
Nov 28 2025

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
8BRAMBLETON-AH1-727 TP 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.40
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.40
Title
Conastone-Brighton 500 kV (5011 circuit) - Replace terminal equipment limitations at Brighton 500 kV.
Description
Conastone-Brighton 500 kV (5011 circuit) - Replace terminal equipment limitations at Brighton 500 kV. Requires terminal equipment upgrades under b3800.41 to achieve higher line ratings.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.41
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.41
Title
Conastone-Brighton 500 kV (5011 circuit) - Replace terminal equipment limitations at Conastone 500 kV.
Description
Requires terminal equipment upgrades under b3800.40 to achieve higher line ratings.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.33
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.33
Title
Replace terminal equipment limitations at Brighton 500 kV - on the existing Brighton-Waugh Chapel 500 kV (5053) or new Brighton-High Ridge 500 kV.
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.1
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.1
Title
Peach Bottom North upgrades – substation work (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breakers to form a breaker-and-a-half bay.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.15
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.15
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.17
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.17
Title
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV sub (Transource)
Description
Cut in 5012 Peach Bottom-Conastone 500 kV line into North Delta 500/230 kV substation by rebuilding 5012 between new terminal at Peach Bottom South and North Delta on single circuit structures and terminating at North Delta (Transource Scope).
Cost Information
Time Estimate
May 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.8
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.8
Title
Graceton 500 kV substation expansion (Projected ISD 12/31/2028)
Description
Add 3x 500 kV breaker bays, 2x 500/230 kV auto transformer, 1x 500 kV caps
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.34
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.34
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV and cut into North Delta 500kV (Projected ISD 12/31/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new Graceton-Conastone) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.35
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.35
Title
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV (Projected ISD 12/1/2030)
Description
Rebuild 5012 (existing Peach Bottom-Conastone) (new North Delta-Graceton PECO) 500 kV line on single circuit structures within existing ROW and cut into North Delta 500 kV and Gracetone 500 kV stations.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.37
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.37
Title
Replace terminal equipment limitations at Conastone 500 kV - on the (existing Peach Bottom-Conastone) or (new Graceton-Conastone) 500 kV line (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.14
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.14
Title
Reconfigure Cooper transmission feeds by establishing new Cooper-North Delta 230 kV line and rerouting existing transmissions lines by Cooper.
Description
None
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.16
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.16
Title
Terminate new Cooper-North Delta 230 kV line (Transource Scope) at North Delta 230 kV
Description
None
Cost Information
Time Estimate
Oct 15 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.6
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.6
Title
Build Granite substation + Statcom (Projected ISD 12/31/2028)
Description
Build Granite substation + Statcom. New STATCOM rating: 350 MVAR. Add 4x 230 kV breaker bays.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.7
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.7
Title
Build new Batavia Road substation (Projected ISD 12/31/2028)
Description
Build Batavia Road substation. Add 4 x 230kV breaker bays
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.9
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.9
Title
Graceton to Batavia Road 230 kV double circuit pole line (Projected ISD 12/31/2028)
Description
Graceton to Batavia Road 230 kV double circuit pole line New rating: 1331 MVA SN/ 1594 MVA SE
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.28
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3800.28
Title
High Ridge 500 kV substation (cut into Brighton-Waugh Chapel 500 kV line) -Brighton side (Projected ISD 12/31/2030)
Description
None
Cost Information
Time Estimate
Dec 31 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3737.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3737.47
Title
Build New North Delta 500 kV substation (Four bay breaker and half configuration)
Description
Build New North Delta 500 kV substation (four bay breaker and half configuration) - the substation will include 12 - 500kV breakers and one 500/230 kV transformer, will allow the termination of six - 500 kV lines
Cost Information
Time Estimate
Oct 15 2027

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.50
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.50
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Jan 23 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.42
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.42
Title
Peach Bottom 500kV North bus upgrade (Projected ISD 12/1/2030)
Description
Peach Bottom 500kV North bus upgrade - Replace 11 – Instances of strain bus conductor used for breaker drops or CT drops, 7 – 500 kV disconnect switches, 7 – Free Standing CTs, 1 – 500 kV breaker, 2 – Breaker relays or meters.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.52
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.52
Title
Reconfigure Peach Bottom North and South 500 kV yards (Projected ISD 12/1/2030)
Description
Reconfigure Peach Bottom North and South yards to allow for termination of 500 kV lines from Peach Bottom to North Delta. North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line.
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.2
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3780.2
Title
Peach Bottom to Graceton (PECO Portion) – New 500kV Line
Description
Peach Bottom to Graceton (PECO Portion) – New 500kV Line. New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3780.4
Type
Load Flow
TO
BGE
RTEP ID / TO ID
b3780.4
Title
Peach Bottom to Graceton (BGE Portion) – New 500kV Line
Description
New rating: 4503 MVA SN/ 5022 MVA SE. This is a baseline identified for the announced Brandon Shores deactivation.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.45
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.45
Title
North Delta 500 kV termination for the Rock Springs 500 kV line (5034/5014 line) (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.46
Type
Load Flow
TO
PEPCO
RTEP ID / TO ID
b3800.46
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (PECO work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.47
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.47
Title
Build new Peach Bottom South-North Delta 500 kV line (Projected ISD 12/1/2030)
Description
Build new Peach Bottom South-North Delta 500 kV line – cut in to Peach Bottom tie No. 1 and extending line to North Delta (~1.25 miles new ROW).
Cost Information
Time Estimate
Dec 01 2030

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)

System Reinforcement: b3800.51
Type
Load Flow
TO
PECO
RTEP ID / TO ID
b3800.51
Title
North Delta 500 kV termination for the new Peach Bottom-North Delta 500 kV line (Transource work).
Description
Loops in the 500kV line from Peach Bottom to Rock Springs into the new North Delta (Bramah) sub
Cost Information
Time Estimate
May 31 2028

Not Contingent

Note: AG2-481 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-481 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01DOUBS-CHAN 500.0 kV Ckt 1 line(Any)
CNASTONE-PCHBTM1S 500.0 kV Ckt 1 line(Any)
BRIGHTON-CNASTONE 500.0 kV Ckt 1 line(Any)

Attachments

AG2-481 One Line Diagram

AG2-481 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.