AG2-516 Phase I Study Report

v1.00 released 2025-10-29 21:23

Pecatonica 138kV

72.0 MW Capacity / 120.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is KESTREL SOLAR, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is Commonwealth Edison Company.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the Commonwealth Edison Company zone — Winnebago County, Illinois. The installed facilities will have a total capability of 120.0 MW with 72.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-516
Project Name:
Pecatonica 138kV
Project Developer Name:
KESTREL SOLAR, LLC
State:
Illinois
County:
Winnebago
Transmission Owner:
Commonwealth Edison Company
MFO:
120.0
MWE:
120.0
MWC:
72.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-516 will interconnect on the Commonwealth Edison Company  transmission system at the Pecatonica 138 kv substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-516 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-516Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$1,800,000$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$30,000,000$30,000,000
Network Upgrades$5,000,000$5,000,000
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$36,800,000$35,000,000

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-516

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-516 Project due at DP1
ABA - B
AG2-516$3,500,000$480,000$3,020,000

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

If your project relies on Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and/or Network Upgrades that will be constructed by another New Service Request and the other New Service Request withdraws, the scope and costs will be allocated to your project, unless the Transmission Owner Interconnection Facilities, Stand Alone Network Upgrades, and/or applicable Network Upgrades have been securitized in an ISA/GIA. 

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Transmission Owner Interconnection Facilities
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Transmission Owner Interconnection Facilities to interconnect developer project to ComEd facility.$1,800,000 $1,800,000
Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)New interconnection substation built to ComEd Standard breaker and a half configuration.$30,000,000 $30,000,000
Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)Transmission line work required to cut into new interconnection substation. Remote terminal work required, relaying and communication upgrades.$5,000,000 $5,000,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 60 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Notes on Cost Estimate:

  1. These estimates are order-of-magnitude estimates of the costs that ComEd would bill to the Project Developer for this interconnection. These estimates are based on a one-line electrical diagram of the project and the information provided by the Project Developer.
  2. There were no site visits performed for these estimates. There may be costs related to specific site related issues that are not identified in these estimates. The site reviews will be performed during the Facilities Study or during detailed engineering.
  3. These estimates are not a guarantee of the maximum amount payable by the Project Developer and the actual costs of ComEd's work may differ significantly from these estimates. The Project Developer will be responsible for paying actual costs of ComEd's work in accordance with the PJM Open Access Transmission Tariff.
  4. The Project Developer is responsible for all engineering, procurement, testing and construction of all equipment on the Project Developer’s side of the Point of Change in Ownership.

 

 

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. ComEd interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-516 was evaluated as a 120.0 MW (72.0 MW Capacity) injection in the ComEd area.

AG2-516 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 120.0 MW (120.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2ATSI
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-602_SRT-A
SingleAC142.52 %1683.0B2398.594.26
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.86 %1892.0B2589.313.66
GD2ATSI
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC136.39 %1892.0B2580.583.67
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.05 %1878.0B2554.953.75
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC135.68 %1878.0B2548.093.75
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.734.33
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC121.78 %1737.0B2115.35.92
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
BreakerAC107.8 %2320.0B2500.920.94
GD2AEP
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
SingleAC106.66 %2320.0B2474.483.9
GD2AEP/DVP
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC121.06 %3393.4B4107.977.38
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC135.7 %5001.0B6786.322.99
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC121.54 %5001.0B6078.0820.92
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC121.53 %5001.0B6077.922.46
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC120.42 %5001.0B6022.0320.96
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P7-1_#11046___SRT-A
TowerAC114.89 %5001.0B5745.7720.57
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
BreakerAC113.26 %5001.0B5664.1221.78
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P7-1_#11001___SRT-A
TowerAC113.17 %5001.0B5659.4520.57
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P2-2_#6229_05MERIDN 345_1_SRT-A
BusAC108.21 %5001.0B5411.4119.57
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC107.02 %5001.0B5352.1414.62
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P2-2_#702_05JEFRSO 765_2_SRT-A
BusAC106.61 %5001.0B5331.6519.2
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Base Case
SingleAC100.56 %4558.0A4583.4713.13
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC122.87 %5523.0B6786.322.99
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC110.05 %5523.0B6078.0820.92
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC110.05 %5523.0B6077.922.46
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC109.04 %5523.0B6022.0320.96
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11046___SRT-A
TowerAC104.03 %5523.0B5745.7720.57
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
BreakerAC102.56 %5523.0B5664.1221.78
GD2AEP
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
AEP_P7-1_#11001___SRT-A
TowerAC102.47 %5523.0B5659.4520.57
GD2AEP
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC132.6 %4142.0B5492.3431.64
GD2AEP
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC130.85 %4142.0B5419.7531.64
GD2AEP
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
BreakerAC120.9 %4142.0B5007.6429.02
GD2AEP
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
AEP_P4_#2976_05DUMONT 345_F_SRT-A
BreakerAC120.56 %4142.0B4993.5228.97
GD2AEP
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
BusAC114.72 %4142.0B4751.7627.57
GD2AEP
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
BusAC114.52 %4142.0B4743.2727.36
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC115.77 %1868.0B2162.57.87
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC115.77 %1868.0B2162.57.87
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC115.41 %1868.0B2155.917.35
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#671_05COOK 345_M2_SRT-A
BreakerAC105.64 %1868.0B1973.335.75
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#10997___SRT-A
TowerAC105.54 %1868.0B1971.585.75
GD2AEP
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#6560_05COOK 345_M_SRT-A
BreakerAC105.53 %1868.0B1971.35.75
GD2AEP
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC106.88 %4571.0B4885.6611.29
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC118.09 %3039.0B3588.676.57
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC127.46 %2826.0B3601.926.57
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.187.86
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC120.12 %2246.0B2697.985.67
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.8 %4142.0B5417.8610.11
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC114.0 %4142.0B4722.0610.6
GD2AEP
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Base Case
SingleAC100.2 %4142.0A4150.448.3
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#711_05MARYSV 765_A1_SRT-A
BreakerAC109.69 %3097.0B3397.15.92
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC109.6 %3097.0B3394.365.83
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC109.59 %3097.0B3394.15.83
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC109.53 %3097.0B3392.255.83
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC109.53 %3097.0B3392.065.83
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC109.5 %3097.0B3391.135.82
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#711_6224_SRT-A
SingleAC105.12 %3097.0B3255.614.13
GD2AEP
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
SingleAC104.65 %3097.0B3241.064.07
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.64 %4571.0B5971.4310.13
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#706_SRT-A
SingleAC116.18 %4571.0B5310.7710.87
GD2AEP
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Base Case
SingleAC114.73 %4047.0A4643.028.35
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC130.66 %4571.0B5972.5410.13
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
AEP_P1-2_#706_SRT-A
SingleAC116.43 %4571.0B5322.0110.87
GD2AEP
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Base Case
SingleAC114.86 %4047.0A4648.258.35
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC145.65 %4142.0B6032.9315.55
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC140.14 %4142.0B5804.6614.7
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC130.5 %4047.0A5281.1913.7
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.857.57
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.349.2
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
SingleAC106.05 %5523.0B5856.899.4
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC132.35 %1868.0B2472.275.74
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC111.07 %3097.0B3439.748.5
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC109.05 %5523.0B6022.7715.55
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC104.68 %5523.0B5781.314.7
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC118.23 %2317.0B2739.43.92
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC141.21 %1540.0B2174.623.79
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#3150_13_SRT-A
SingleAC137.97 %1540.0B2124.683.63
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.36 %1540.0B1561.023.76
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC143.98 %971.0B1398.099.39
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC143.98 %971.0B1398.089.39
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC143.68 %971.0B1395.149.32
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC142.91 %971.0B1387.639.34
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC110.12 %971.0B1069.266.55
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC110.11 %971.0B1069.226.55
GD2AEP/NIPS
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
BreakerAC102.04 %971.0B990.846.76
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC148.76 %1841.0B2738.5814.15
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC148.75 %1841.0B2738.5714.15
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC147.24 %1841.0B2710.6213.86
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC143.24 %1841.0B2637.1113.66
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
765-L11215__-S_SRT-A
SingleAC124.81 %1841.0B2297.739.88
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P1-2_#695_1681_SRT-A
SingleAC124.8 %1841.0B2297.619.88
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#11009___SRT-A-1
TowerAC118.06 %1841.0B2173.4710.64
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P7-1_#11009___SRT-A-2
TowerAC116.53 %1841.0B2145.410.65
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC109.12 %1841.0B2008.879.79
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
BusAC107.24 %1841.0B1974.38.54
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Base Case
SingleAC106.35 %1385.0A1472.965.56
GD2AEP/NIPS
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A
BusAC101.5 %1841.0B1868.78.62
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC131.35 %1046.0B1373.949.2
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC131.35 %1046.0B1373.949.2
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC131.08 %1046.0B1371.099.13
GD2AEP/NIPS
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC130.39 %1046.0B1363.919.15
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC110.0 %1635.0B1798.487.7
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC109.1 %1635.0B1783.797.73
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC108.37 %1635.0B1771.857.63
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC108.37 %1635.0B1771.857.63
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P4_#3128_05EUGENE 345_A2_SRT-A
BreakerAC107.8 %1635.0B1762.56.91
GD2AEP/AMIL
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
BusAC106.68 %1635.0B1744.267.08
GD2CE
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC103.63 %2107.0STE2183.56.09
GD2CE
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC103.62 %2107.0STE2183.366.09
GD2CE
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC103.57 %2107.0STE2182.36.09
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_144-45-BT5-8___SRT-A
BreakerAC116.91 %1837.0STE2147.6112.63
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4_144-45-BT7-8___SRT-A
BreakerAC115.82 %1837.0STE2127.5612.54
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P4-6_006-345-BT78___SRT-A
BreakerAC115.12 %1837.0STE2114.8111.0
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Base Case
SingleAC113.9 %1334.0A1519.446.57
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P2-2_141_PV-138R__1_SRT-A
BusAC101.14 %1837.0STE1858.039.77
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P2-2_154_LV-345R__3_SRT-A
BusAC101.06 %1837.0STE1856.549.62
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P2-2_116_GG-345R__2_SRT-A
BusAC101.04 %1837.0STE1856.049.41
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P2-2_116_GG-345B__4_SRT-A
BusAC100.99 %1837.0STE1855.199.35
GD2CE
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
COMED_P2-2_951_AR-345R__3_SRT-A
BusAC100.85 %1837.0STE1852.69.52
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_144-45-BT7-8___SRT-A
BreakerAC121.54 %1568.0STE1905.6723.26
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_144-45-BT5-8___SRT-A
BreakerAC121.25 %1568.0STE1901.1323.03
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4-6_006-345-BT78___SRT-A
BreakerAC114.6 %1568.0STE1796.9424.2
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345B__1_SRT-A
BusAC108.49 %1568.0STE1701.1119.52
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_111-45-L11124__SRT-A
BreakerAC108.48 %1568.0STE1701.0119.52
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P4_111-45-TR81____SRT-A
BreakerAC108.48 %1568.0STE1701.0119.52
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L92805__B-R_SRT-A-2
SingleAC107.3 %1568.0STE1682.4316.21
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
COMED_P1-2_345-L0626__B-R_SRT-A
SingleAC103.44 %1568.0STE1621.9216.21
GD2CE
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Base Case
SingleAC100.38 %1201.0A1205.5712.59
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC112.57 %1413.0B1590.639.15
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC112.57 %1413.0B1590.629.15
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC112.38 %1413.0B1587.999.08
GD2AEP
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC111.86 %1413.0B1580.579.1
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC138.82 %1868.0B2593.185.74
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC116.17 %1441.0B1673.978.76
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC115.82 %1441.0B1668.918.79
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC115.81 %1441.0B1668.798.79
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
BreakerAC115.34 %1441.0B1662.038.74
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC115.28 %1441.0B1661.128.36
GD2CE/NIPS
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC113.22 %1441.0B1631.558.36
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC121.82 %1591.0B1938.1911.05
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC119.96 %1591.0B1908.5611.05
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P4_112-65-BT3-4___SRT-A
BreakerAC112.09 %1591.0B1783.310.9
GD2CE/NIPS
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
COMED_P4_112-65-BT4-5___SRT-A
BreakerAC112.08 %1591.0B1783.2310.9
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4_144-45-BT7-8___SRT-A
BreakerAC117.47 %1568.0STE1841.9523.26
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4_144-45-BT5-8___SRT-A
BreakerAC117.23 %1568.0STE1838.1123.03
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4-6_006-345-BT78___SRT-A
BreakerAC110.49 %1568.0STE1732.5424.2
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345B__1_SRT-A
BusAC104.67 %1568.0STE1641.1519.52
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4_111-45-TR81____SRT-A
BreakerAC104.66 %1568.0STE1641.0519.52
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P4_111-45-L11124__SRT-A
BreakerAC104.66 %1568.0STE1641.0519.52
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P1-2_345-L92805__B-R_SRT-A-2
SingleAC104.46 %1568.0STE1638.016.21
GD2CE
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
COMED_P1-2_345-L0626__B-R_SRT-A
SingleAC100.61 %1568.0STE1577.4916.21
GD2CE
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
COMED_P4_167-65-BT3-4___SRT-A
BreakerAC112.09 %1469.0STE1646.669.59
GD2CE
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
COMED_P4_167-65-BT4-5___SRT-A
BreakerAC112.09 %1469.0STE1646.669.59
GD2CE
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_167-65-BT3-4___SRT-A
BreakerAC112.27 %1469.0STE1649.179.59
GD2CE
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_167-65-BT4-5___SRT-A
BreakerAC112.27 %1469.0STE1649.179.59
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Base Case
SingleAC106.4 %1201.0A1277.873.64
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4-6_111-345-R______SRT-A
BreakerAC106.31 %1568.0STE1666.986.65
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_120-45-L12002__SRT-A
BreakerAC104.58 %1568.0STE1639.845.95
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_120-38-TR82____SRT-A
BreakerAC104.24 %1568.0STE1634.436.02
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P2-2_120_LO-345R__2_SRT-A
BusAC104.22 %1568.0STE1634.135.94
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_120-45-L10322__SRT-A
BreakerAC104.22 %1568.0STE1634.15.94
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P4_120-45-L11120__SRT-A
BreakerAC104.21 %1568.0STE1633.945.94
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345R__3_SRT-A
BusAC103.45 %1568.0STE1622.095.28
GD2CE
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
COMED_P2-2_111_EJ-345B__2_SRT-A
BusAC100.02 %1568.0STE1568.248.88
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4-6_116-345-R______SRT-A
BreakerAC115.96 %2297.0STE2663.5810.07
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L11614__SRT-A
BreakerAC112.76 %2297.0STE2590.158.52
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P2-2_116_GG-345R__2_SRT-A
BusAC107.78 %2297.0STE2475.78.55
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-TR82____SRT-A
BreakerAC107.77 %2297.0STE2475.598.55
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
COMED_P4_116-45-L0303___SRT-A
BreakerAC103.98 %2297.0STE2388.458.56
GD2CE
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
AEP_P4_#2978_05DUMONT 765_B_SRT-A
BreakerAC102.92 %2297.0STE2364.1211.1
GD2CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC116.36 %1469.0STE1709.339.22
GD2CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC115.09 %1469.0STE1690.729.22
GD2CE
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC115.09 %1469.0STE1690.689.22
GD2CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC116.32 %1469.0STE1708.819.18
GD2CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC114.6 %1469.0STE1683.439.18
GD2CE
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC114.59 %1469.0STE1683.49.18
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
TowerAC124.6 %4460.0B5557.231.64
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
TowerAC122.97 %4460.0B5484.6331.64
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
BreakerAC114.03 %4460.0B5085.8529.02
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P4_#2976_05DUMONT 345_F_SRT-A
BreakerAC113.85 %4460.0B5077.6728.97
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
BusAC108.23 %4460.0B4826.9727.36
GD2AEP/CE
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
BusAC108.12 %4460.0B4822.1327.57
GD2CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC116.6 %1469.0STE1712.799.22
GD2CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC115.23 %1469.0STE1692.679.22
GD2CE
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC115.22 %1469.0STE1692.639.22
GD2CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT3-4___SRT-A
BreakerAC116.51 %1469.0STE1711.569.18
GD2CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT2-3___SRT-A
BreakerAC114.7 %1469.0STE1684.879.18
GD2CE
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
COMED_P4_023-65-BT4-5___SRT-A
BreakerAC114.69 %1469.0STE1684.849.18

Details for 02BAY SH-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-602_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-602_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:142.52 %
Rating:1683.0 MVA
Rating Type:B
MVA to Mitigate:2398.59
MW Contribution:4.26
Bus #Bus NameTypeMW Contribution
972211AH1-690 GEN
50/50
445.374
23888502TROY G1
50/50
1.526
23888602TROY G2
50/50
1.526
970817AG2-515 GEN
Solar/Wind Harmer
9.949
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
971549AH1-272 GEN
Solar/Wind Harmer
11.98
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.588
971619AH1-309 GEN
Solar/Wind Harmer
2.081
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
4.385
965041AG1-368 GEN
Solar/Wind Harmer
4.372
965051AG1-369 GEN
Solar/Wind Harmer
2.168
971989AH1-539 GEN
Solar/Wind Harmer
1.862
971769AH1-391 GEN
Solar/Wind Harmer
4.78
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.147
963791AG1-232 GEN
Solar/Wind Harmer
5.327
971567AH1-282 GEN
Solar/Wind Harmer
5.89
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270578AF1-285 GEN2
Solar/Wind Harmer
0.256
274814UNIV PK N;0U
Adder
2.746
274807UNIV PK N;3U
Adder
2.74
274805UNIV PK N;1U
Adder
2.728
274811UNIV PK N;7U
Adder
2.722
270071AF1-092 GEN
Solar/Wind Harmer
7.267
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.098
274827FISK ;RP
Adder
4.165
960591AF2-350 GEN
Solar/Wind Harmer
3.734
274775LINCOLN ;6U
Adder
4.515
274776LINCOLN ;7U
Adder
4.515
274777LINCOLN ;8U
Adder
4.515
971611AH1-305 GEN
Solar/Wind Harmer
2.222
972227AH1-698 GEN1
Adder
1.392
274687WILL CNTY;4U
Adder
14.867
274687WILL CNTY;4U
Adder
14.867
274675JOLIET 29;7U
Adder
16.292
274675JOLIET 29;7U
Adder
15.71
274728ELWOOD EC;5P
Adder
8.714
274731ELWOOD EC;2P
Adder
8.713
274733ELWOOD EC;3P
Adder
8.713
274735ELWOOD EC;4P
Adder
8.713
970833AG2-524 GEN
Solar/Wind Harmer
4.049
970833AG2-524 GEN
Solar/Wind Harmer
2.699
274746AC1-111 G10
Adder
2.931
274744AC1-111 GEN8
Adder
2.931
276868AE1-113 GEN
Solar/Wind Harmer
0.724
276882AE2-255 GEN
Solar/Wind Harmer
0.422
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270024AE2-089 GEN
Solar/Wind Harmer
0.004
971177AH1-047 GEN
Solar/Wind Harmer
2.216
971411AH1-196 GEN
Solar/Wind Harmer
5.375
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.396
971171AH1-044 GEN
Solar/Wind Harmer
7.133
274823ROCKFORD ;21
Adder
9.941
926823AC1-168 GEN
Solar/Wind Harmer
0.603
970169AG2-114 GEN
Solar/Wind Harmer
3.546
276612AE2-035 GEN
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.294
971681AH1-341 GEN
Solar/Wind Harmer
5.682
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.056
957751AF2-069 GEN
Solar/Wind Harmer
0.115
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.644
941731AE2-173 GEN
Solar/Wind Harmer
2.892
963841AG1-237 GEN
Solar/Wind Harmer
1.492
946321AF1-296 GEN
Solar/Wind Harmer
1.922
965101AG1-375 GEN
Solar/Wind Harmer
3.421
971609AH1-304 GEN
Solar/Wind Harmer
0.55
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.635
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.12
270594AE1-207 GEN
Solar/Wind Harmer
3.716
970115AG2-085 GEN
Solar/Wind Harmer
1.302
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
6.849
241982AE2-343 S C
Solar/Wind Helper
0.12
254304AE2-114 C
Solar/Wind Helper
0.114
203846AF2-130 C
Solar/Wind Helper
0.251
241997AF1-093 GEN
Solar/Wind Helper
0.132
203804AE2-113_GEN
Solar/Wind Helper
0.869
24190002OREGON_ST1
50/50
5.55
24189802OREGON_CT1
50/50
4.21
23888802TROY G4
50/50
1.526
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.659
970621AG2-405 GEN
Solar/Wind Harmer
0.944
970623AG2-406 GEN
Solar/Wind Harmer
0.885
961051AF2-396 GEN
Solar/Wind Harmer
9.384
961051AF2-396 GEN
Solar/Wind Harmer
6.256
246938BC-WTG3
Solar/Wind Harmer
0.168
246937BC-WTG2
Solar/Wind Harmer
0.188
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.296
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
4.252
970627AG2-408 GEN
Solar/Wind Harmer
1.276
965681AG1-436 GEN
Solar/Wind Harmer
5.151
965791AG1-447 GEN
Solar/Wind Harmer
3.778
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.71
274803UNIV PARK;6U
Adder
3.135
274888KELLY CRK;1U
Solar/Wind Harmer
0.219
274887GEN-1.85
Solar/Wind Harmer
0.098
276843GEN-1.7
Solar/Wind Harmer
0.121
958011AF2-095 GEN
Solar/Wind Harmer
5.377
274770LINCOLN ;1U
Adder
4.515
274771LINCOLN ;2U
Adder
4.515
972259AH1-714 GEN
Adder
10.138
274674JOLIET 9 ;6U
Adder
8.161
970321AG2-212 GEN
Solar/Wind Harmer
1.596
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.485
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.495
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971573AH1-285 GEN
Solar/Wind Harmer
0.679
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.936
274695ROCKY RD ;2P
Adder
5.799
274693ROCKY RD ;1P
Adder
5.742
274697ROCKY RD ;3P
Adder
1.575
274683WAUKEGAN ;8U
Adder
10.969
274683WAUKEGAN ;8U
Adder
9.246
958491AF2-143 GEN
Solar/Wind Harmer
5.438
962691AG1-118 GEN
Solar/Wind Harmer
10.84
274879MINONK ;1U
Solar/Wind Harmer
0.152
970921AG2-575 GEN
Solar/Wind Harmer
3.608
970921AG2-575 GEN
Solar/Wind Harmer
1.203
942991AE2-321 GEN
Solar/Wind Harmer
4.013
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.161
971335AH1-147 GEN
Solar/Wind Harmer
7.161
971341AH1-150 GEN
Solar/Wind Harmer
7.133
971343AH1-151 GEN
Solar/Wind Harmer
7.133
274856ECOGROVE ;U1
Solar/Wind Harmer
0.084
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.999
274764LEE CO EC;5U
Adder
4.704
274765LEE CO EC;6U
Adder
4.704
274762LEE CO EC;3U
Adder
4.693
274763LEE CO EC;4U
Adder
4.649
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.397
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.137
276646AC1-214 GEN2
Solar/Wind Harmer
0.137
276741O09 GEN1
Solar/Wind Harmer
0.124
276708O09 GEN2
Solar/Wind Harmer
0.124
276782AC1-033 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.231
960971AF2-388 GEN
Solar/Wind Harmer
2.024
960611AF2-352 GEN
Solar/Wind Harmer
1.144
970241AG2-163 GEN
Solar/Wind Harmer
1.972
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
3.085
270031AE2-169
Solar/Wind Harmer
1.851
964611AG1-324 GEN
Solar/Wind Harmer
0.251
971613AH1-306 GEN
Solar/Wind Harmer
1.593
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.377
960441AF2-335 GEN
Solar/Wind Harmer
3.255
970825AG2-519 GEN
Solar/Wind Harmer
3.6
203947AF1-006 C
Solar/Wind Helper
0.391
203980AG1-197 GEN
Solar/Wind Helper
0.255
203979AG1-198 GEN
Solar/Wind Helper
0.198
241801AE1-079 GEN
Solar/Wind Helper
0.134
241967AE2-285_GEN
Solar/Wind Helper
0.345
241985AE1-237 GEN
Solar/Wind Helper
0.134
962101AG1-054 GEN
Solar/Wind Helper
0.332
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
23929302BS-PKR
50/50
2.775
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.136
23906502RICHG2&3
Adder
1.343
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.521
970217AG2-149 GEN
Solar/Wind Harmer
4.693
247604X1-042
Adder
0.303
270404AC1-167 GEN
Solar/Wind Harmer
0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
3.748
270588AE1-091_GEN
Solar/Wind Harmer
3.595
24642205MAYFLWER
Adder
0.41
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.866
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.028
959331AF2-224 GEN
Solar/Wind Harmer
2.976
965021AG1-366 GEN
Solar/Wind Harmer
1.417
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970349AG2-230 GEN
Solar/Wind Harmer
6.147
270043AE2-236 GEN
Solar/Wind Harmer
2.609
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
270391AF1-285 GEN3
Solar/Wind Harmer
0.256
274752CRETE EC ;2U
Adder
4.532
274753CRETE EC ;3U
Adder
4.532
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.666
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.135
274826FISK ;BP
Adder
5.877
274800UNIV PARK;3U
Adder
3.125
972038AH1-567 GEN2
Adder
0.196
276806AD2-047 C O1
Solar/Wind Harmer
2.116
970941AG2-585 GEN
Solar/Wind Harmer
4.668
274772LINCOLN ;3U
Adder
4.515
972228AH1-698 GEN2
Adder
1.977
274676JOLIET 29;8U
Adder
15.71
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.147
274730ELWOOD EC;6P
Adder
8.714
274734ELWOOD EC;8P
Adder
8.714
274736ELWOOD EC;9P
Adder
8.714
274729ELWOOD EC;1P
Adder
8.713
970707AG2-453 GEN
Solar/Wind Harmer
12.079
970513AG2-328 GEN
Solar/Wind Harmer
1.596
970517AG2-330 GEN
Solar/Wind Harmer
9.577
943121AE2-341 GEN
Solar/Wind Harmer
6.132
943591AF1-030 GEN
Solar/Wind Harmer
4.078
276694AA1-018 GEN2
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
9.363
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.132
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.599
971617AH1-308 GEN
Solar/Wind Harmer
2.996
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.382
274855GSG-6 ;RU
Solar/Wind Harmer
0.131
274850MENDOTA H;RU
Solar/Wind Harmer
0.042
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.064
944531AF1-118 GEN
Solar/Wind Harmer
16.023
959091AF2-200 GEN
Solar/Wind Harmer
7.133
972236AH1-702 GEN2
Adder
1.116
970571AG2-364 GEN
Solar/Wind Harmer
7.107
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.693
274767LEE CO EC;8U
Adder
1.086
276157O29GEN1
Solar/Wind Harmer
0.565
274878BISHOP HL;2U
Solar/Wind Harmer
0.117
942111AE2-223 GEN
Solar/Wind Harmer
1.128
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.299
959611AF2-252 GEN
Solar/Wind Harmer
1.144
965931AG1-462 GEN
Solar/Wind Harmer
8.719
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.066
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.368
970291AG2-192 GEN
Solar/Wind Harmer
0.334
276686W4-005 GEN3
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
971993AH1-541 GEN
Solar/Wind Harmer
1.533
270377AD1-106 GEN
Solar/Wind Harmer
1.25
276621W2-048 GEN
Solar/Wind Harmer
0.166
276838X2-022 GEN2
Solar/Wind Harmer
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.103
958821AF2-173 GEN
Solar/Wind Harmer
4.521
270004AE1-209 GEN
Solar/Wind Harmer
0.7
962511AG1-100 GEN
Solar/Wind Helper
0.35
203830AF1-094 GEN
Solar/Wind Helper
0.331
959441AF2-235 GEN
Solar/Wind Helper
0.15
254305AE2-115 C
Solar/Wind Helper
0.114
20334926Z1-069 C
Solar/Wind Helper
0.646
24189902OREGON_CT2
50/50
4.125
23856402BAYSG1
50/50
1.577
23888702TROY G3
50/50
1.526
972253AH1-711 GEN
50/50
46.611
23920202STRYCT
50/50
1.928
241808AF1-120 C
Solar/Wind Harmer
0.003
241858AF1-205_GEN
Solar/Wind Harmer
3.78
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.727
23906402RICHG1
Adder
1.345
23906502RICHG2&3
Adder
1.343
270361_3
Solar/Wind Harmer
4.521
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
14.08
944231AF1-091 GEN
Solar/Wind Harmer
1.351
247522W1-056 GEN
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.47
246936BC-WTG1
Solar/Wind Harmer
0.188
270489AE1-102 GEN1
Solar/Wind Harmer
0.603
945111AF1-176 GEN
Solar/Wind Harmer
8.251
270505AE1-170 C O1
Solar/Wind Harmer
4.856
965421AG1-410 GEN
Solar/Wind Harmer
13.81
24639705ELKHART HY
Adder
0.098
24695305TIMB G C
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
247521TR3_G114
Solar/Wind Harmer
0.158
270246TR4_N_V150
Solar/Wind Harmer
0.028
965011AG1-365 GEN
Solar/Wind Harmer
4.252
270462AD2-086
Solar/Wind Harmer
0.009
970373AG2-245 GEN
Solar/Wind Harmer
8.33
270055AF2-134 C O1
Solar/Wind Harmer
0.003
270223U2-072_GEN1
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
4.532
274754CRETE EC ;4U
Adder
4.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.962
274723RIVER EC ;12
Adder
9.782
274812UNIV PK N;8U
Adder
2.722
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.125
276776AD2-060 GEN
Solar/Wind Harmer
0.39
274773LINCOLN ;4U
Adder
4.515
274774LINCOLN ;5U
Adder
4.515
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.664
274676JOLIET 29;8U
Adder
16.292
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.714
274674JOLIET 9 ;6U
Adder
8.161
970245AG2-165 GEN
Solar/Wind Harmer
1.596
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.931
276691AA1-018 GEN1
Solar/Wind Harmer
0.443
274682WAUKEGAN ;7U
Adder
9.363
274828WAUKEGAN ;BP
Adder
5.75
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.703
962781AG1-127 GEN
Solar/Wind Harmer
3.433
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.887
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.064
957471AF2-041 GEN
Solar/Wind Harmer
10.7
959081AF2-199 GEN
Solar/Wind Harmer
3.567
971067AG2-660 GEN
Solar/Wind Harmer
1.189
274822ROCKFORD ;11
Adder
10.013
972235AH1-702 GEN1
Adder
1.284
970569AG2-363 GEN
Solar/Wind Harmer
10.66
970819AG2-516 GEN
Solar/Wind Harmer
4.256
971475AH1-234 GEN
Solar/Wind Harmer
1.718
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.693
274766LEE CO EC;7U
Adder
4.638
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.117
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.858
965651AG1-433 GEN
Solar/Wind Harmer
1.012
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
1.482
963741AG1-226 GEN
Solar/Wind Harmer
7.999
972175AH1-670 GEN
Solar/Wind Harmer
2.788
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.435
274880W4-005 GEN4
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.212
963831AG1-236 GEN
Solar/Wind Harmer
1.29
247536S-71 GEN
Solar/Wind Harmer
0.132
276615X2-022 GEN
Solar/Wind Harmer
0.034
276903AD2-071 C
Solar/Wind Harmer
3.649
970825AG2-519 GEN
Solar/Wind Harmer
1.153
270005AE1-210 C O1
Solar/Wind Harmer
0.7
241885AC2-103 GEN1
Solar/Wind Helper
6.849
241807AE2-176_GEN
Solar/Wind Helper
1.64
961971AG1-040 GEN
Solar/Wind Helper
0.342
203835AF1-098 GEN
Solar/Wind Helper
1.348
203860AG1-193 C
Solar/Wind Helper
0.152
241966AE1-183 GEN
Solar/Wind Helper
0.132
254303AC2-168 GEN
Solar/Wind Helper
0.077
965031AG1-367 GEN
Solar/Wind Harmer
0.798
991177J1571 G
External Queue
15.792752265930176
991182J1586 G
External Queue
28.11846351623535
990527J1329
External Queue
2.0234405994415283
990142J1224
External Queue
14.791350364685059
NYPJM->LTFIMP_NY
CLTF
1.965
LGEELTFEXP_LGEE->PJM
CLTF
2.4
WECLTFEXP_WEC->PJM
CLTF
1.946
CPLELTFEXP_CPLE->PJM
CLTF
0.731
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.539
AG2-052LTFEXP_AG2-052->PJM
LTF
0.125
AH1-155LTFEXP_AH1-155->PJM
LTF
0.187
CBM West 1LTFEXP_CBM-W1->PJM
CBM
112.86
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.907
MECLTFEXP_MEC->PJM
CLTF
7.633
SIGELTFEXP_SIGE->PJM
CLTF
0.2
LAGNLTFEXP_LAGN->PJM
CLTF
6.061
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.4
TVALTFEXP_TVA->PJM
CLTF
2.775

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.86 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2589.31
MW Contribution:3.66
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.831
24189802OREGON_CT1
50/50
2.906
23888802TROY G4
50/50
1.904
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.863
970623AG2-406 GEN
Solar/Wind Harmer
0.804
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.176
961051AF2-396 GEN
Solar/Wind Harmer
5.45
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.749
970627AG2-408 GEN
Solar/Wind Harmer
1.125
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.465
965791AG1-447 GEN
Solar/Wind Harmer
3.275
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.34
274803UNIV PARK;6U
Adder
2.706
274888KELLY CRK;1U
Solar/Wind Harmer
0.189
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.104
958011AF2-095 GEN
Solar/Wind Harmer
4.64
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
972259AH1-714 GEN
Adder
8.743
274674JOLIET 9 ;6U
Adder
7.038
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.377
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.726
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.426
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.585
274696ROCKY RD ;4P
Adder
5.113
274695ROCKY RD ;2P
Adder
4.995
274693ROCKY RD ;1P
Adder
4.946
274697ROCKY RD ;3P
Adder
1.357
274683WAUKEGAN ;8U
Adder
9.448
274683WAUKEGAN ;8U
Adder
7.964
958491AF2-143 GEN
Solar/Wind Harmer
4.684
962691AG1-118 GEN
Solar/Wind Harmer
9.334
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.106
970921AG2-575 GEN
Solar/Wind Harmer
1.035
942991AE2-321 GEN
Solar/Wind Harmer
3.454
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.163
971335AH1-147 GEN
Solar/Wind Harmer
6.163
971341AH1-150 GEN
Solar/Wind Harmer
6.137
971343AH1-151 GEN
Solar/Wind Harmer
6.137
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.719
274764LEE CO EC;5U
Adder
4.044
274765LEE CO EC;6U
Adder
4.044
274762LEE CO EC;3U
Adder
4.035
274763LEE CO EC;4U
Adder
3.996
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
203947AF1-006 C
Solar/Wind Helper
0.381
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.341
241801AE1-079 GEN
Solar/Wind Helper
0.133
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.329
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.112
24189902OREGON_CT2
50/50
2.847
23888702TROY G3
50/50
1.904
972253AH1-711 GEN
50/50
58.156
23856402BAYSG1
50/50
1.209
23920202STRYCT
50/50
1.93
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241858AF1-205_GEN
Solar/Wind Harmer
3.878
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.656
23906402RICHG1
Adder
1.331
23906502RICHG2&3
Adder
1.328
270361_3
Solar/Wind Harmer
4.06
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.751
944231AF1-091 GEN
Solar/Wind Harmer
1.239
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.538
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.152
965421AG1-410 GEN
Solar/Wind Harmer
12.302
945111AF1-176 GEN
Solar/Wind Harmer
7.189
270505AE1-170 C O1
Solar/Wind Harmer
4.228
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.14
270246TR4_N_V150
Solar/Wind Harmer
0.025
965011AG1-365 GEN
Solar/Wind Harmer
3.749
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.209
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.916
274754CRETE EC ;4U
Adder
3.916
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.287
274723RIVER EC ;12
Adder
8.45
274812UNIV PK N;8U
Adder
2.351
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.697
276776AD2-060 GEN
Solar/Wind Harmer
0.336
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.026
274676JOLIET 29;8U
Adder
14.05
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.514
274674JOLIET 9 ;6U
Adder
7.038
970245AG2-165 GEN
Solar/Wind Harmer
1.377
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.526
276691AA1-018 GEN1
Solar/Wind Harmer
0.382
274682WAUKEGAN ;7U
Adder
8.065
274828WAUKEGAN ;BP
Adder
4.952
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.328
962781AG1-127 GEN
Solar/Wind Harmer
2.956
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.206
959081AF2-199 GEN
Solar/Wind Harmer
3.069
971067AG2-660 GEN
Solar/Wind Harmer
1.023
274822ROCKFORD ;11
Adder
8.614
972235AH1-702 GEN1
Adder
1.104
970569AG2-363 GEN
Solar/Wind Harmer
9.17
970819AG2-516 GEN
Solar/Wind Harmer
3.66
971475AH1-234 GEN
Solar/Wind Harmer
1.477
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.035
274766LEE CO EC;7U
Adder
2.419
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241807AE2-176_GEN
Solar/Wind Helper
2.238
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.318
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
23929302BS-PKR
50/50
2.128
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.129
23906502RICHG2&3
Adder
1.328
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.06
970217AG2-149 GEN
Solar/Wind Harmer
4.25
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.264
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.538
270588AE1-091_GEN
Solar/Wind Harmer
3.207
945111AF1-176 GEN
Solar/Wind Harmer
3.266
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.509
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.624
965021AG1-366 GEN
Solar/Wind Harmer
1.25
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.282
970349AG2-230 GEN
Solar/Wind Harmer
5.331
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.916
274753CRETE EC ;3U
Adder
3.916
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.349
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.706
274826FISK ;BP
Adder
5.072
274800UNIV PARK;3U
Adder
2.697
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.826
970941AG2-585 GEN
Solar/Wind Harmer
4.027
274772LINCOLN ;3U
Adder
3.895
972228AH1-698 GEN2
Adder
1.705
274676JOLIET 29;8U
Adder
13.548
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.514
274730ELWOOD EC;6P
Adder
7.514
274734ELWOOD EC;8P
Adder
7.514
274736ELWOOD EC;9P
Adder
7.514
970707AG2-453 GEN
Solar/Wind Harmer
10.416
970513AG2-328 GEN
Solar/Wind Harmer
1.377
970517AG2-330 GEN
Solar/Wind Harmer
8.26
943121AE2-341 GEN
Solar/Wind Harmer
5.284
943591AF1-030 GEN
Solar/Wind Harmer
3.514
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.61
274682WAUKEGAN ;7U
Adder
8.065
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.898
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.1
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.137
972236AH1-702 GEN2
Adder
0.96
970571AG2-364 GEN
Solar/Wind Harmer
6.113
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.035
276157O29GEN1
Solar/Wind Harmer
0.485
962511AG1-100 GEN
Solar/Wind Helper
0.342
203830AF1-094 GEN
Solar/Wind Helper
0.324
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.646
23867002DVBSG1
50/50
15.559
972211AH1-690 GEN
50/50
307.104
23888502TROY G1
50/50
1.904
23888602TROY G2
50/50
1.904
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
11.024
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.494
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.524
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.812
965041AG1-368 GEN
Solar/Wind Harmer
3.881
965051AG1-369 GEN
Solar/Wind Harmer
1.924
971989AH1-539 GEN
Solar/Wind Harmer
1.649
971771AH1-392 GEN
Solar/Wind Harmer
3.814
971769AH1-391 GEN
Solar/Wind Harmer
4.151
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.517
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.331
971567AH1-282 GEN
Solar/Wind Harmer
5.227
963791AG1-232 GEN
Solar/Wind Harmer
4.679
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.329
274814UNIV PK N;0U
Adder
2.371
274807UNIV PK N;3U
Adder
2.366
274805UNIV PK N;1U
Adder
2.356
274811UNIV PK N;7U
Adder
2.351
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.595
960591AF2-350 GEN
Solar/Wind Harmer
3.222
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
971611AH1-305 GEN
Solar/Wind Harmer
1.917
972227AH1-698 GEN1
Adder
1.201
274687WILL CNTY;4U
Adder
12.823
274687WILL CNTY;4U
Adder
12.823
274675JOLIET 29;7U
Adder
14.05
274675JOLIET 29;7U
Adder
13.548
274731ELWOOD EC;2P
Adder
7.514
274733ELWOOD EC;3P
Adder
7.514
274735ELWOOD EC;4P
Adder
7.514
274728ELWOOD EC;5P
Adder
7.514
970833AG2-524 GEN
Solar/Wind Harmer
3.49
970833AG2-524 GEN
Solar/Wind Harmer
2.327
274746AC1-111 G10
Adder
2.526
274744AC1-111 GEN8
Adder
2.526
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.623
276882AE2-255 GEN
Solar/Wind Harmer
0.363
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.907
971411AH1-196 GEN
Solar/Wind Harmer
4.626
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.202
24729505KEY G4
Adder
2.855
971171AH1-044 GEN
Solar/Wind Harmer
6.137
274823ROCKFORD ;21
Adder
8.551
926823AC1-168 GEN
Solar/Wind Harmer
0.519
970169AG2-114 GEN
Solar/Wind Harmer
3.05
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.885
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.766
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241982AE2-343 S C
Solar/Wind Helper
0.119
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.868
991177J1571 G
External Queue
15.847536087036133
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
NYPJM->LTFIMP_NY
CLTF
2.031
LGEELTFEXP_LGEE->PJM
CLTF
2.008
WECLTFEXP_WEC->PJM
CLTF
1.673
CPLELTFEXP_CPLE->PJM
CLTF
0.328
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.692
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.893
MECLTFEXP_MEC->PJM
CLTF
6.512
SIGELTFEXP_SIGE->PJM
CLTF
0.168
LAGNLTFEXP_LAGN->PJM
CLTF
4.961
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.186
TVALTFEXP_TVA->PJM
CLTF
2.246

Details for 02DAV-BE-02HAYES 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-02HAYES 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.39 %
Rating:1892.0 MVA
Rating Type:B
MVA to Mitigate:2580.58
MW Contribution:3.67
Bus #Bus NameTypeMW Contribution
24189902OREGON_CT2
50/50
2.849
23888702TROY G3
50/50
1.905
972253AH1-711 GEN
50/50
58.19
23856402BAYSG1
50/50
1.21
23920202STRYCT
50/50
1.931
241858AF1-205_GEN
Solar/Wind Harmer
3.881
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
6.662
23906402RICHG1
Adder
1.332
23906502RICHG2&3
Adder
1.329
270361_3
Solar/Wind Harmer
4.064
960841AF2-375 GEN
Solar/Wind Harmer
-0.001
970515AG2-329 GEN
Solar/Wind Harmer
12.77
944231AF1-091 GEN
Solar/Wind Harmer
1.241
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.168
270489AE1-102 GEN1
Solar/Wind Harmer
0.539
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.155
965421AG1-410 GEN
Solar/Wind Harmer
12.324
945111AF1-176 GEN
Solar/Wind Harmer
7.202
270505AE1-170 C O1
Solar/Wind Harmer
4.236
24695305TIMB G C
Solar/Wind Harmer
0.001
24639705ELKHART HY
Adder
0.086
270063AE2-323 C
Solar/Wind Harmer
0.003
247521TR3_G114
Solar/Wind Harmer
0.141
270246TR4_N_V150
Solar/Wind Harmer
0.025
965011AG1-365 GEN
Solar/Wind Harmer
3.756
270462AD2-086
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
7.224
270223U2-072_GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
3.925
274754CRETE EC ;4U
Adder
3.925
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.296
274723RIVER EC ;12
Adder
8.468
274812UNIV PK N;8U
Adder
2.356
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.703
276776AD2-060 GEN
Solar/Wind Harmer
0.337
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
274773LINCOLN ;4U
Adder
3.904
274774LINCOLN ;5U
Adder
3.904
971605AH1-302 GEN
Solar/Wind Harmer
4.035
274676JOLIET 29;8U
Adder
14.081
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.531
274674JOLIET 9 ;6U
Adder
7.053
970245AG2-165 GEN
Solar/Wind Harmer
1.38
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.532
276691AA1-018 GEN1
Solar/Wind Harmer
0.383
274682WAUKEGAN ;7U
Adder
8.083
274828WAUKEGAN ;BP
Adder
4.964
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.333
962781AG1-127 GEN
Solar/Wind Harmer
2.963
274872LEEDK;1U
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
971997AH1-543 GEN
Solar/Wind Harmer
1.628
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.227
959081AF2-199 GEN
Solar/Wind Harmer
3.076
971067AG2-660 GEN
Solar/Wind Harmer
1.025
274822ROCKFORD ;11
Adder
8.634
970569AG2-363 GEN
Solar/Wind Harmer
9.191
972235AH1-702 GEN1
Adder
1.107
970819AG2-516 GEN
Solar/Wind Harmer
3.668
971475AH1-234 GEN
Solar/Wind Harmer
1.481
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.044
274766LEE CO EC;7U
Adder
2.424
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
3.958
241807AE2-176_GEN
Solar/Wind Helper
2.236
961971AG1-040 GEN
Solar/Wind Helper
0.334
203835AF1-098 GEN
Solar/Wind Helper
1.316
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.131
254303AC2-168 GEN
Solar/Wind Helper
0.076
24190002OREGON_ST1
50/50
3.833
24189802OREGON_CT1
50/50
2.907
23888802TROY G4
50/50
1.905
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.588
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.806
246938BC-WTG3
Solar/Wind Harmer
0.15
246937BC-WTG2
Solar/Wind Harmer
0.168
270007AE1-245 C
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
8.19
961051AF2-396 GEN
Solar/Wind Harmer
5.46
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.259
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.756
970627AG2-408 GEN
Solar/Wind Harmer
1.127
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
4.474
965791AG1-447 GEN
Solar/Wind Harmer
3.281
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.345
274803UNIV PARK;6U
Adder
2.712
274888KELLY CRK;1U
Solar/Wind Harmer
0.19
274887GEN-1.85
Solar/Wind Harmer
0.085
276843GEN-1.7
Solar/Wind Harmer
0.105
958011AF2-095 GEN
Solar/Wind Harmer
4.65
274770LINCOLN ;1U
Adder
3.904
274771LINCOLN ;2U
Adder
3.904
972259AH1-714 GEN
Adder
8.763
274674JOLIET 9 ;6U
Adder
7.053
942221AE2-234 GEN
Solar/Wind Harmer
0.016
970321AG2-212 GEN
Solar/Wind Harmer
1.38
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.737
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.427
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.124
274695ROCKY RD ;2P
Adder
5.006
274693ROCKY RD ;1P
Adder
4.957
274697ROCKY RD ;3P
Adder
1.36
274683WAUKEGAN ;8U
Adder
9.469
274683WAUKEGAN ;8U
Adder
7.982
958491AF2-143 GEN
Solar/Wind Harmer
4.695
962691AG1-118 GEN
Solar/Wind Harmer
9.356
274879MINONK ;1U
Solar/Wind Harmer
0.131
970921AG2-575 GEN
Solar/Wind Harmer
3.113
970921AG2-575 GEN
Solar/Wind Harmer
1.038
942991AE2-321 GEN
Solar/Wind Harmer
3.462
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.177
971335AH1-147 GEN
Solar/Wind Harmer
6.177
971341AH1-150 GEN
Solar/Wind Harmer
6.151
971343AH1-151 GEN
Solar/Wind Harmer
6.151
274856ECOGROVE ;U1
Solar/Wind Harmer
0.072
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.723
274764LEE CO EC;5U
Adder
4.053
274765LEE CO EC;6U
Adder
4.053
274762LEE CO EC;3U
Adder
4.044
274763LEE CO EC;4U
Adder
4.006
276603SUBLETTE C
Solar/Wind Harmer
0
966841AG1-555 GEN
Solar/Wind Harmer
0.342
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.118
276646AC1-214 GEN2
Solar/Wind Harmer
0.118
276741O09 GEN1
Solar/Wind Harmer
0.107
276708O09 GEN2
Solar/Wind Harmer
0.107
276782AC1-033 GEN
Solar/Wind Harmer
0
203947AF1-006 C
Solar/Wind Helper
0.38
203980AG1-197 GEN
Solar/Wind Helper
0.249
203979AG1-198 GEN
Solar/Wind Helper
0.194
241967AE2-285_GEN
Solar/Wind Helper
0.34
241801AE1-079 GEN
Solar/Wind Helper
0.132
241985AE1-237 GEN
Solar/Wind Helper
0.132
962101AG1-054 GEN
Solar/Wind Helper
0.328
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
23929302BS-PKR
50/50
2.13
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.13
23906502RICHG2&3
Adder
1.329
270541AE2-072 C
Solar/Wind Harmer
0.008
270575GUS2 35KV
Solar/Wind Harmer
4.064
970217AG2-149 GEN
Solar/Wind Harmer
4.257
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.265
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.539
270588AE1-091_GEN
Solar/Wind Harmer
3.213
945111AF1-176 GEN
Solar/Wind Harmer
3.272
24642205MAYFLWER
Adder
0.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.514
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.025
959331AF2-224 GEN
Solar/Wind Harmer
2.629
965021AG1-366 GEN
Solar/Wind Harmer
1.252
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.287
970349AG2-230 GEN
Solar/Wind Harmer
5.341
270391AF1-285 GEN3
Solar/Wind Harmer
0.227
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
3.925
274753CRETE EC ;3U
Adder
3.925
964401AG1-302 GEN
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
8.367
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.712
274826FISK ;BP
Adder
5.083
274800UNIV PARK;3U
Adder
2.703
972038AH1-567 GEN2
Adder
0.169
276806AD2-047 C O1
Solar/Wind Harmer
1.83
970941AG2-585 GEN
Solar/Wind Harmer
4.036
274772LINCOLN ;3U
Adder
3.904
972228AH1-698 GEN2
Adder
1.709
274676JOLIET 29;8U
Adder
13.578
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.127
274729ELWOOD EC;1P
Adder
7.53
274730ELWOOD EC;6P
Adder
7.531
274734ELWOOD EC;8P
Adder
7.531
274736ELWOOD EC;9P
Adder
7.531
970707AG2-453 GEN
Solar/Wind Harmer
10.439
970513AG2-328 GEN
Solar/Wind Harmer
1.38
970517AG2-330 GEN
Solar/Wind Harmer
8.279
943121AE2-341 GEN
Solar/Wind Harmer
5.296
943591AF1-030 GEN
Solar/Wind Harmer
3.522
276694AA1-018 GEN2
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
2.616
274682WAUKEGAN ;7U
Adder
8.083
276805AD2-038 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
13.93
274872LEEDK;1U
Solar/Wind Harmer
0.114
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.107
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.113
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
959091AF2-200 GEN
Solar/Wind Harmer
6.151
970571AG2-364 GEN
Solar/Wind Harmer
6.128
972236AH1-702 GEN2
Adder
0.963
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.044
276157O29GEN1
Solar/Wind Harmer
0.487
962511AG1-100 GEN
Solar/Wind Helper
0.341
203830AF1-094 GEN
Solar/Wind Helper
0.323
959441AF2-235 GEN
Solar/Wind Helper
0.147
254305AE2-115 C
Solar/Wind Helper
0.113
20334926Z1-069 C
Solar/Wind Helper
0.645
23867002DVBSG1
50/50
15.565
972211AH1-690 GEN
50/50
307.274
23888502TROY G1
50/50
1.905
23888602TROY G2
50/50
1.905
970817AG2-515 GEN
Solar/Wind Harmer
11.031
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.026
971549AH1-272 GEN
Solar/Wind Harmer
10.508
270297AD1-101 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.525
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.815
965041AG1-368 GEN
Solar/Wind Harmer
3.888
965051AG1-369 GEN
Solar/Wind Harmer
1.928
971989AH1-539 GEN
Solar/Wind Harmer
1.652
971771AH1-392 GEN
Solar/Wind Harmer
3.821
971769AH1-391 GEN
Solar/Wind Harmer
4.158
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971653AH1-327 GEN
Solar/Wind Harmer
0.518
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
5.341
971567AH1-282 GEN
Solar/Wind Harmer
5.238
963791AG1-232 GEN
Solar/Wind Harmer
4.689
270578AF1-285 GEN2
Solar/Wind Harmer
0.227
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.342
274814UNIV PK N;0U
Adder
2.376
274807UNIV PK N;3U
Adder
2.371
274805UNIV PK N;1U
Adder
2.361
274811UNIV PK N;7U
Adder
2.356
958391AF2-133 GEN
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.602
960591AF2-350 GEN
Solar/Wind Harmer
3.229
274775LINCOLN ;6U
Adder
3.904
274776LINCOLN ;7U
Adder
3.904
274777LINCOLN ;8U
Adder
3.904
971611AH1-305 GEN
Solar/Wind Harmer
1.922
972227AH1-698 GEN1
Adder
1.203
274687WILL CNTY;4U
Adder
12.851
274687WILL CNTY;4U
Adder
12.851
274675JOLIET 29;7U
Adder
14.081
274675JOLIET 29;7U
Adder
13.578
274731ELWOOD EC;2P
Adder
7.53
274733ELWOOD EC;3P
Adder
7.53
274735ELWOOD EC;4P
Adder
7.53
274728ELWOOD EC;5P
Adder
7.531
970833AG2-524 GEN
Solar/Wind Harmer
3.498
970833AG2-524 GEN
Solar/Wind Harmer
2.332
274746AC1-111 G10
Adder
2.532
274744AC1-111 GEN8
Adder
2.532
270024AE2-089 GEN
Solar/Wind Harmer
0.003
276868AE1-113 GEN
Solar/Wind Harmer
0.625
276882AE2-255 GEN
Solar/Wind Harmer
0.364
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.911
971411AH1-196 GEN
Solar/Wind Harmer
4.636
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.204
24729505KEY G4
Adder
2.862
971171AH1-044 GEN
Solar/Wind Harmer
6.151
274823ROCKFORD ;21
Adder
8.571
926823AC1-168 GEN
Solar/Wind Harmer
0.52
970169AG2-114 GEN
Solar/Wind Harmer
3.057
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
4.897
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.771
957751AF2-069 GEN
Solar/Wind Harmer
0.099
241886AC2-103 GEN2
Solar/Wind Helper
3.958
241982AE2-343 S C
Solar/Wind Helper
0.118
254304AE2-114 C
Solar/Wind Helper
0.113
203846AF2-130 C
Solar/Wind Helper
0.248
241997AF1-093 GEN
Solar/Wind Helper
0.131
203804AE2-113_GEN
Solar/Wind Helper
0.866
991177J1571 G
External Queue
15.847536087036133
991182J1586 G
External Queue
26.137367248535156
990527J1329
External Queue
1.9070898294448853
990142J1224
External Queue
13.940826416015625
NYPJM->LTFIMP_NY
CLTF
2.024
LGEELTFEXP_LGEE->PJM
CLTF
2.015
WECLTFEXP_WEC->PJM
CLTF
1.677
CPLELTFEXP_CPLE->PJM
CLTF
0.339
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
39.829
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.485
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.932
MECLTFEXP_MEC->PJM
CLTF
6.529
SIGELTFEXP_SIGE->PJM
CLTF
0.169
LAGNLTFEXP_LAGN->PJM
CLTF
4.982
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.217
TVALTFEXP_TVA->PJM
CLTF
2.257

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2554.95
MW Contribution:3.75
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.603
24189802OREGON_CT1
50/50
2.733
23888802TROY G4
50/50
1.836
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.745
970621AG2-405 GEN
Solar/Wind Harmer
0.95
970623AG2-406 GEN
Solar/Wind Harmer
0.856
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.157
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.284
961051AF2-396 GEN
Solar/Wind Harmer
5.523
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.894
970627AG2-408 GEN
Solar/Wind Harmer
1.168
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.428
965681AG1-436 GEN
Solar/Wind Harmer
4.548
965791AG1-447 GEN
Solar/Wind Harmer
3.335
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.391
274803UNIV PARK;6U
Adder
2.765
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.193
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.742
274770LINCOLN ;1U
Adder
3.982
274771LINCOLN ;2U
Adder
3.982
972259AH1-714 GEN
Adder
8.939
274674JOLIET 9 ;6U
Adder
7.195
970321AG2-212 GEN
Solar/Wind Harmer
1.409
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.833
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.598
274696ROCKY RD ;4P
Adder
5.229
274695ROCKY RD ;2P
Adder
5.109
274693ROCKY RD ;1P
Adder
5.059
274697ROCKY RD ;3P
Adder
1.388
274683WAUKEGAN ;8U
Adder
9.663
274683WAUKEGAN ;8U
Adder
8.145
958491AF2-143 GEN
Solar/Wind Harmer
4.791
962691AG1-118 GEN
Solar/Wind Harmer
9.548
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.177
970921AG2-575 GEN
Solar/Wind Harmer
1.059
942991AE2-321 GEN
Solar/Wind Harmer
3.534
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.305
971335AH1-147 GEN
Solar/Wind Harmer
6.305
971341AH1-150 GEN
Solar/Wind Harmer
6.279
971343AH1-151 GEN
Solar/Wind Harmer
6.279
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.759
274764LEE CO EC;5U
Adder
4.139
274765LEE CO EC;6U
Adder
4.139
274762LEE CO EC;3U
Adder
4.129
274763LEE CO EC;4U
Adder
4.09
966841AG1-555 GEN
Solar/Wind Harmer
0.35
944541AF1-119 GEN
Solar/Wind Harmer
0.207
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.815
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.305
960611AF2-352 GEN
Solar/Wind Harmer
1.007
270599AE1-208 GEN
Solar/Wind Harmer
2.766
270031AE2-169
Solar/Wind Harmer
1.66
203947AF1-006 C
Solar/Wind Helper
0.409
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.363
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.141
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.706
203853AF1-134 C O1
Solar/Wind Helper
0.221
24189902OREGON_CT2
50/50
2.678
23856402BAYSG1
50/50
1.433
23888702TROY G3
50/50
1.836
972253AH1-711 GEN
50/50
56.068
23860302FRMENG 3
50/50
3.538
23920202STRYCT
50/50
2.05
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.134
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.119
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270361_3
Solar/Wind Harmer
5.343
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.687
944231AF1-091 GEN
Solar/Wind Harmer
1.299
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
965421AG1-410 GEN
Solar/Wind Harmer
12.895
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.179
970905AG2-564 GEN
Solar/Wind Harmer
2.266
945111AF1-176 GEN
Solar/Wind Harmer
7.294
270505AE1-170 C O1
Solar/Wind Harmer
4.287
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.087
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.894
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.354
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4
274754CRETE EC ;4U
Adder
4
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.381
274723RIVER EC ;12
Adder
8.632
274812UNIV PK N;8U
Adder
2.401
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.756
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.118
276776AD2-060 GEN
Solar/Wind Harmer
0.344
274773LINCOLN ;4U
Adder
3.982
274774LINCOLN ;5U
Adder
3.982
274676JOLIET 29;8U
Adder
14.364
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.682
274674JOLIET 9 ;6U
Adder
7.195
970245AG2-165 GEN
Solar/Wind Harmer
1.409
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.583
276691AA1-018 GEN1
Solar/Wind Harmer
0.39
274682WAUKEGAN ;7U
Adder
8.249
274828WAUKEGAN ;BP
Adder
5.065
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.382
962781AG1-127 GEN
Solar/Wind Harmer
3.024
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.662
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.419
959081AF2-199 GEN
Solar/Wind Harmer
3.14
971067AG2-660 GEN
Solar/Wind Harmer
1.047
274822ROCKFORD ;11
Adder
8.814
970569AG2-363 GEN
Solar/Wind Harmer
9.385
972235AH1-702 GEN1
Adder
1.13
970819AG2-516 GEN
Solar/Wind Harmer
3.745
971475AH1-234 GEN
Solar/Wind Harmer
1.512
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.129
274766LEE CO EC;7U
Adder
0.439
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.908
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.328
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.276
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
203835AF1-098 GEN
Solar/Wind Helper
1.414
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.234
23929302BS-PKR
50/50
2.523
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.267
23906502RICHG2&3
Adder
1.422
270575GUS2 35KV
Solar/Wind Harmer
5.343
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.562
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.735
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.266
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
945111AF1-176 GEN
Solar/Wind Harmer
3.313
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.362
970031AG2-029 GEN
Solar/Wind Harmer
2.571
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.726
965021AG1-366 GEN
Solar/Wind Harmer
1.298
270377AD1-106 GEN
Solar/Wind Harmer
1.42
270043AE2-236 GEN
Solar/Wind Harmer
2.353
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.434
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4
274753CRETE EC ;3U
Adder
4
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.529
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.765
274826FISK ;BP
Adder
5.184
274800UNIV PARK;3U
Adder
2.756
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.866
970941AG2-585 GEN
Solar/Wind Harmer
4.117
274772LINCOLN ;3U
Adder
3.982
972228AH1-698 GEN2
Adder
1.743
274676JOLIET 29;8U
Adder
13.851
971617AH1-308 GEN
Solar/Wind Harmer
2.722
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.129
274729ELWOOD EC;1P
Adder
7.682
274730ELWOOD EC;6P
Adder
7.682
274734ELWOOD EC;8P
Adder
7.682
274736ELWOOD EC;9P
Adder
7.682
970707AG2-453 GEN
Solar/Wind Harmer
10.65
970513AG2-328 GEN
Solar/Wind Harmer
1.409
970517AG2-330 GEN
Solar/Wind Harmer
8.456
943121AE2-341 GEN
Solar/Wind Harmer
5.404
943591AF1-030 GEN
Solar/Wind Harmer
3.594
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.389
274682WAUKEGAN ;7U
Adder
8.249
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.176
274872LEEDK;1U
Solar/Wind Harmer
0.116
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.279
970571AG2-364 GEN
Solar/Wind Harmer
6.257
972236AH1-702 GEN2
Adder
0.983
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.129
276157O29GEN1
Solar/Wind Harmer
0.497
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.993
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.58
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.061
959611AF2-252 GEN
Solar/Wind Harmer
1.007
965931AG1-462 GEN
Solar/Wind Harmer
7.661
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.367
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.158
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.691
203854AF2-039 C
Solar/Wind Helper
0.15
23867002DVBSG1
50/50
12.822
972211AH1-690 GEN
50/50
288.807
23888502TROY G1
50/50
1.836
23888602TROY G2
50/50
1.836
23860102FRMENG 1
50/50
1.733
23860202FRMENG 2
50/50
1.733
24191202EL_AA1-006
50/50
0.334
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
970817AG2-515 GEN
Solar/Wind Harmer
10.986
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.515
971989AH1-539 GEN
Solar/Wind Harmer
1.989
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971619AH1-309 GEN
Solar/Wind Harmer
1.837
965041AG1-368 GEN
Solar/Wind Harmer
4.077
965051AG1-369 GEN
Solar/Wind Harmer
2.027
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.877
971567AH1-282 GEN
Solar/Wind Harmer
5.76
971769AH1-391 GEN
Solar/Wind Harmer
4.221
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.434
963791AG1-232 GEN
Solar/Wind Harmer
4.874
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.422
274807UNIV PK N;3U
Adder
2.417
274805UNIV PK N;1U
Adder
2.407
274811UNIV PK N;7U
Adder
2.401
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.674
971611AH1-305 GEN
Solar/Wind Harmer
1.961
960591AF2-350 GEN
Solar/Wind Harmer
3.293
274775LINCOLN ;6U
Adder
3.982
274776LINCOLN ;7U
Adder
3.982
274777LINCOLN ;8U
Adder
3.982
972227AH1-698 GEN1
Adder
1.228
274687WILL CNTY;4U
Adder
13.109
274687WILL CNTY;4U
Adder
13.109
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.364
274675JOLIET 29;7U
Adder
13.851
274731ELWOOD EC;2P
Adder
7.682
274733ELWOOD EC;3P
Adder
7.682
274735ELWOOD EC;4P
Adder
7.682
274728ELWOOD EC;5P
Adder
7.682
970833AG2-524 GEN
Solar/Wind Harmer
3.569
970833AG2-524 GEN
Solar/Wind Harmer
2.379
274746AC1-111 G10
Adder
2.583
274744AC1-111 GEN8
Adder
2.583
24729505KEY G4
Adder
2.957
276868AE1-113 GEN
Solar/Wind Harmer
0.638
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.951
971411AH1-196 GEN
Solar/Wind Harmer
4.733
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.279
274823ROCKFORD ;21
Adder
8.75
970169AG2-114 GEN
Solar/Wind Harmer
3.123
926823AC1-168 GEN
Solar/Wind Harmer
0.531
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.808
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.066
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.207
941731AE2-173 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.315
971609AH1-304 GEN
Solar/Wind Harmer
0.493
946321AF1-296 GEN
Solar/Wind Harmer
1.689
945581AF1-223 GEN
Solar/Wind Harmer
0
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.266
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.928
203855AF2-088 C
Solar/Wind Helper
0.072
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
NYPJM->LTFIMP_NY
CLTF
2.164
LGEELTFEXP_LGEE->PJM
CLTF
2.094
WECLTFEXP_WEC->PJM
CLTF
1.712
CPLELTFEXP_CPLE->PJM
CLTF
0.333
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.959
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.287
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.224
MECLTFEXP_MEC->PJM
CLTF
6.679
SIGELTFEXP_SIGE->PJM
CLTF
0.174
LAGNLTFEXP_LAGN->PJM
CLTF
5.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.262
TVALTFEXP_TVA->PJM
CLTF
2.326

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.68 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2548.09
MW Contribution:3.75
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.605
24189802OREGON_CT1
50/50
2.735
23888802TROY G4
50/50
1.837
241996AE2-282_GEN
Solar/Wind Harmer
0.006
971677AH1-339 GEN
Solar/Wind Harmer
0.746
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.158
246937BC-WTG2
Solar/Wind Harmer
0.176
961051AF2-396 GEN
Solar/Wind Harmer
8.298
961051AF2-396 GEN
Solar/Wind Harmer
5.532
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.264
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.901
970627AG2-408 GEN
Solar/Wind Harmer
1.17
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965681AG1-436 GEN
Solar/Wind Harmer
4.556
965791AG1-447 GEN
Solar/Wind Harmer
3.341
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.396
274803UNIV PARK;6U
Adder
2.771
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.194
274887GEN-1.85
Solar/Wind Harmer
0.087
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.752
274770LINCOLN ;1U
Adder
3.991
274771LINCOLN ;2U
Adder
3.991
972259AH1-714 GEN
Adder
8.958
274674JOLIET 9 ;6U
Adder
7.21
970321AG2-212 GEN
Solar/Wind Harmer
1.412
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
4.844
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.437
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.6
274696ROCKY RD ;4P
Adder
5.24
274695ROCKY RD ;2P
Adder
5.12
274693ROCKY RD ;1P
Adder
5.069
274697ROCKY RD ;3P
Adder
1.391
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
958491AF2-143 GEN
Solar/Wind Harmer
4.801
962691AG1-118 GEN
Solar/Wind Harmer
9.569
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.184
970921AG2-575 GEN
Solar/Wind Harmer
1.061
942991AE2-321 GEN
Solar/Wind Harmer
3.541
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.319
971335AH1-147 GEN
Solar/Wind Harmer
6.319
971341AH1-150 GEN
Solar/Wind Harmer
6.293
971343AH1-151 GEN
Solar/Wind Harmer
6.293
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.763
274764LEE CO EC;5U
Adder
4.148
274765LEE CO EC;6U
Adder
4.148
274762LEE CO EC;3U
Adder
4.138
274763LEE CO EC;4U
Adder
4.099
966841AG1-555 GEN
Solar/Wind Harmer
0.351
944541AF1-119 GEN
Solar/Wind Harmer
0.208
276603SUBLETTE C
Solar/Wind Harmer
0
960971AF2-388 GEN
Solar/Wind Harmer
1.819
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
276741O09 GEN1
Solar/Wind Harmer
0.11
276708O09 GEN2
Solar/Wind Harmer
0.11
276782AC1-033 GEN
Solar/Wind Harmer
0
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.308
960611AF2-352 GEN
Solar/Wind Harmer
1.009
270599AE1-208 GEN
Solar/Wind Harmer
2.772
270031AE2-169
Solar/Wind Harmer
1.663
203947AF1-006 C
Solar/Wind Helper
0.408
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241967AE2-285_GEN
Solar/Wind Helper
0.362
241801AE1-079 GEN
Solar/Wind Helper
0.141
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
20398826ARMNA MT
Solar/Wind Helper
0.704
24189902OREGON_CT2
50/50
2.68
23856402BAYSG1
50/50
1.434
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
23920202STRYCT
50/50
2.052
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241858AF1-205_GEN
Solar/Wind Harmer
4.136
241808AF1-120 C
Solar/Wind Harmer
0.003
241840AF1-064_GEN
Solar/Wind Harmer
0.004
972301AH1-735 GEN
Adder
7.125
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270361_3
Solar/Wind Harmer
5.347
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
270428AC2-015 C
Solar/Wind Harmer
0.003
970515AG2-329 GEN
Solar/Wind Harmer
13.704
944231AF1-091 GEN
Solar/Wind Harmer
1.301
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
965421AG1-410 GEN
Solar/Wind Harmer
12.915
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.182
970905AG2-564 GEN
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
7.306
270505AE1-170 C O1
Solar/Wind Harmer
4.294
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.088
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
3.901
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.368
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.008
274754CRETE EC ;4U
Adder
4.008
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.39
274723RIVER EC ;12
Adder
8.649
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.126
276776AD2-060 GEN
Solar/Wind Harmer
0.345
274773LINCOLN ;4U
Adder
3.991
274774LINCOLN ;5U
Adder
3.991
274676JOLIET 29;8U
Adder
14.394
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
1.412
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.589
276691AA1-018 GEN1
Solar/Wind Harmer
0.391
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
276901AD2-066 C O1
Solar/Wind Harmer
0.003
939401AE1-172 GEN
Solar/Wind Harmer
2.387
962781AG1-127 GEN
Solar/Wind Harmer
3.03
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.665
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.057
957471AF2-041 GEN
Solar/Wind Harmer
9.44
959081AF2-199 GEN
Solar/Wind Harmer
3.147
971067AG2-660 GEN
Solar/Wind Harmer
1.049
274822ROCKFORD ;11
Adder
8.833
970569AG2-363 GEN
Solar/Wind Harmer
9.405
972235AH1-702 GEN1
Adder
1.133
970819AG2-516 GEN
Solar/Wind Harmer
3.753
971475AH1-234 GEN
Solar/Wind Harmer
1.515
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.138
274766LEE CO EC;7U
Adder
0.44
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
0.909
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.331
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.286
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
254303AC2-168 GEN
Solar/Wind Helper
0.081
203954AE2-126 C
Solar/Wind Helper
0.233
23929302BS-PKR
50/50
2.524
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.268
23906502RICHG2&3
Adder
1.423
270575GUS2 35KV
Solar/Wind Harmer
5.347
270541AE2-072 C
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
4.568
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270588AE1-091_GEN
Solar/Wind Harmer
3.741
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.267
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.026
24642205MAYFLWER
Adder
0.363
970031AG2-029 GEN
Solar/Wind Harmer
2.575
247643Z2-116 C
Solar/Wind Harmer
0
270485AE1-090_GEN
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
2.73
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270377AD1-106 GEN
Solar/Wind Harmer
1.422
270043AE2-236 GEN
Solar/Wind Harmer
2.357
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.444
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
4.008
274753CRETE EC ;3U
Adder
4.008
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
8.546
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
2.771
274826FISK ;BP
Adder
5.194
274800UNIV PARK;3U
Adder
2.762
972038AH1-567 GEN2
Adder
0.173
276806AD2-047 C O1
Solar/Wind Harmer
1.87
970941AG2-585 GEN
Solar/Wind Harmer
4.125
274772LINCOLN ;3U
Adder
3.991
972228AH1-698 GEN2
Adder
1.747
274676JOLIET 29;8U
Adder
13.879
971617AH1-308 GEN
Solar/Wind Harmer
2.727
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.13
970707AG2-453 GEN
Solar/Wind Harmer
10.672
274729ELWOOD EC;1P
Adder
7.698
274730ELWOOD EC;6P
Adder
7.698
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
1.412
970517AG2-330 GEN
Solar/Wind Harmer
8.474
943121AE2-341 GEN
Solar/Wind Harmer
5.415
943591AF1-030 GEN
Solar/Wind Harmer
3.601
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.419
274682WAUKEGAN ;7U
Adder
8.266
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.183
274872LEEDK;1U
Solar/Wind Harmer
0.117
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
959091AF2-200 GEN
Solar/Wind Harmer
6.293
970571AG2-364 GEN
Solar/Wind Harmer
6.27
972236AH1-702 GEN2
Adder
0.985
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.138
276157O29GEN1
Solar/Wind Harmer
0.498
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
942111AE2-223 GEN
Solar/Wind Harmer
0.995
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.59
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.081
959611AF2-252 GEN
Solar/Wind Harmer
1.009
965931AG1-462 GEN
Solar/Wind Harmer
7.678
247642Z2-115 C
Solar/Wind Harmer
0.001
962511AG1-100 GEN
Solar/Wind Helper
0.366
203830AF1-094 GEN
Solar/Wind Helper
0.347
959441AF2-235 GEN
Solar/Wind Helper
0.157
254305AE2-115 C
Solar/Wind Helper
0.12
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
23867002DVBSG1
50/50
12.828
972211AH1-690 GEN
50/50
288.97
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.993
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.529
971989AH1-539 GEN
Solar/Wind Harmer
1.992
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971619AH1-309 GEN
Solar/Wind Harmer
1.84
965041AG1-368 GEN
Solar/Wind Harmer
4.084
965051AG1-369 GEN
Solar/Wind Harmer
2.03
270302AB2-170 GEN
Solar/Wind Harmer
0.002
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.884
971567AH1-282 GEN
Solar/Wind Harmer
5.77
971769AH1-391 GEN
Solar/Wind Harmer
4.229
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
971347AH1-153 GEN
Solar/Wind Harmer
5.444
963791AG1-232 GEN
Solar/Wind Harmer
4.883
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.55
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.681
971611AH1-305 GEN
Solar/Wind Harmer
1.965
960591AF2-350 GEN
Solar/Wind Harmer
3.3
274775LINCOLN ;6U
Adder
3.991
274776LINCOLN ;7U
Adder
3.991
274777LINCOLN ;8U
Adder
3.991
972227AH1-698 GEN1
Adder
1.23
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274735ELWOOD EC;4P
Adder
7.698
274728ELWOOD EC;5P
Adder
7.698
970833AG2-524 GEN
Solar/Wind Harmer
3.577
970833AG2-524 GEN
Solar/Wind Harmer
2.384
274746AC1-111 G10
Adder
2.589
274744AC1-111 GEN8
Adder
2.589
24729505KEY G4
Adder
2.963
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
1.955
971411AH1-196 GEN
Solar/Wind Harmer
4.743
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.232
971171AH1-044 GEN
Solar/Wind Harmer
6.293
274823ROCKFORD ;21
Adder
8.769
970169AG2-114 GEN
Solar/Wind Harmer
3.129
926823AC1-168 GEN
Solar/Wind Harmer
0.532
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.011
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.812
957751AF2-069 GEN
Solar/Wind Harmer
0.102
965101AG1-375 GEN
Solar/Wind Harmer
3.072
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.214
941731AE2-173 GEN
Solar/Wind Harmer
2.551
963841AG1-237 GEN
Solar/Wind Harmer
1.318
971609AH1-304 GEN
Solar/Wind Harmer
0.494
946321AF1-296 GEN
Solar/Wind Harmer
1.693
945581AF1-223 GEN
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
203846AF2-130 C
Solar/Wind Helper
0.265
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
203855AF2-088 C
Solar/Wind Helper
0.072
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990527J1329
External Queue
1.8513455390930176
990142J1224
External Queue
13.53333568572998
NYPJM->LTFIMP_NY
CLTF
2.158
LGEELTFEXP_LGEE->PJM
CLTF
2.101
WECLTFEXP_WEC->PJM
CLTF
1.716
CPLELTFEXP_CPLE->PJM
CLTF
0.344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
MECLTFEXP_MEC->PJM
CLTF
6.695
SIGELTFEXP_SIGE->PJM
CLTF
0.175
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
TVALTFEXP_TVA->PJM
CLTF
2.336

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:4.33
Bus #Bus NameTypeMW Contribution
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
971549AH1-272 GEN
Solar/Wind Harmer
11.871
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.621
971989AH1-539 GEN
Solar/Wind Harmer
2.024
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965041AG1-368 GEN
Solar/Wind Harmer
4.612
965051AG1-369 GEN
Solar/Wind Harmer
2.289
971771AH1-392 GEN
Solar/Wind Harmer
4.424
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.621
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.22
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
276868AE1-113 GEN
Solar/Wind Harmer
0.736
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
971411AH1-196 GEN
Solar/Wind Harmer
5.463
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
926823AC1-168 GEN
Solar/Wind Harmer
0.613
970169AG2-114 GEN
Solar/Wind Harmer
3.606
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.09
957751AF2-069 GEN
Solar/Wind Harmer
0.117
965101AG1-375 GEN
Solar/Wind Harmer
3.538
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.709
941731AE2-173 GEN
Solar/Wind Harmer
2.944
963841AG1-237 GEN
Solar/Wind Harmer
1.521
946321AF1-296 GEN
Solar/Wind Harmer
1.955
971609AH1-304 GEN
Solar/Wind Harmer
0.569
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.655
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
970115AG2-085 GEN
Solar/Wind Harmer
1.349
270543AE2-219 C
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
0.007
971677AH1-339 GEN
Solar/Wind Harmer
0.714
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.205
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274887GEN-1.85
Solar/Wind Harmer
0.1
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
1.623
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
958491AF2-143 GEN
Solar/Wind Harmer
5.526
962691AG1-118 GEN
Solar/Wind Harmer
11.015
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
970921AG2-575 GEN
Solar/Wind Harmer
1.222
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971335AH1-147 GEN
Solar/Wind Harmer
7.279
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.412
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
966841AG1-555 GEN
Solar/Wind Harmer
0.405
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.239
960971AF2-388 GEN
Solar/Wind Harmer
2.094
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
276741O09 GEN1
Solar/Wind Harmer
0.127
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270599AE1-208 GEN
Solar/Wind Harmer
3.195
270031AE2-169
Solar/Wind Harmer
1.917
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.487
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970825AG2-519 GEN
Solar/Wind Harmer
3.73
970883AG2-550 GEN
Solar/Wind Harmer
3.346
970885AG2-551 GEN
Solar/Wind Harmer
1.115
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
241840AF1-064_GEN
Solar/Wind Harmer
0.005
270361_3
Solar/Wind Harmer
4.971
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
15.158
944231AF1-091 GEN
Solar/Wind Harmer
1.488
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
0.004
965011AG1-365 GEN
Solar/Wind Harmer
4.433
270462AD2-086
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.596
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.065
957471AF2-041 GEN
Solar/Wind Harmer
10.876
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970569AG2-363 GEN
Solar/Wind Harmer
10.839
972235AH1-702 GEN1
Adder
1.305
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.047
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
958861AF2-177 GEN
Solar/Wind Harmer
1.533
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.946
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
8.165
970291AG2-192 GEN
Solar/Wind Harmer
0.448
972175AH1-670 GEN
Solar/Wind Harmer
2.841
247536S-71 GEN
Solar/Wind Harmer
0.138
270032AE2-172
Solar/Wind Harmer
2.283
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
970825AG2-519 GEN
Solar/Wind Harmer
1.195
276615X2-022 GEN
Solar/Wind Harmer
0.035
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
0.01
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
3.901
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.03
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
2.93
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.103
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
274752CRETE EC ;2U
Adder
4.596
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276806AD2-047 C O1
Solar/Wind Harmer
2.148
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
274682WAUKEGAN ;7U
Adder
9.512
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274872LEEDK;1U
Solar/Wind Harmer
0.134
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
7.251
970571AG2-364 GEN
Solar/Wind Harmer
7.226
972236AH1-702 GEN2
Adder
1.135
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
0.229
276157O29GEN1
Solar/Wind Harmer
0.575
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.488
959611AF2-252 GEN
Solar/Wind Harmer
1.165
965931AG1-462 GEN
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
958821AF2-173 GEN
Solar/Wind Harmer
1.049
991177J1571 G
External Queue
18.513126373291016
991182J1586 G
External Queue
28.404245376586914
990527J1329
External Queue
2.100800037384033
990142J1224
External Queue
15.35684871673584
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.78 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2115.3
MW Contribution:5.92
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
2.449
970521AG2-332 GEN
50/50
11.057
24639705ELKHART HY
50/50
0.153
270143AC1-141 CT2_
50/50
2.055
24344105CKG2
50/50
6.288
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.913
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.268
270246TR4_N_V150
Solar/Wind Harmer
0.047
944231AF1-091 GEN
Solar/Wind Harmer
1.894
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.883
958861AF2-177 GEN
Solar/Wind Harmer
2.703
945111AF1-176 GEN
Solar/Wind Harmer
10.846
270505AE1-170 C O1
Solar/Wind Harmer
6.228
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.049
970245AG2-165 GEN
Solar/Wind Harmer
2.372
970373AG2-245 GEN
Solar/Wind Harmer
11.463
274751CRETE EC ;1U
Adder
6.419
274754CRETE EC ;4U
Adder
6.419
274723RIVER EC ;12
Adder
13.914
274812UNIV PK N;8U
Adder
3.858
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.474
274774LINCOLN ;5U
Adder
6.474
274801UNIV PARK;4U
Adder
4.433
276776AD2-060 GEN
Solar/Wind Harmer
0.553
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.867
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.063
274674JOLIET 9 ;6U
Adder
11.55
274732ELWOOD EC;7P
Adder
12.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.476
274745AC1-111 GEN9
Adder
4.142
276691AA1-018 GEN1
Solar/Wind Harmer
0.622
274682WAUKEGAN ;7U
Adder
13.17
970291AG2-192 GEN
Solar/Wind Harmer
0.664
274828WAUKEGAN ;BP
Adder
8.084
270005AE1-210 C O1
Solar/Wind Harmer
1.101
965031AG1-367 GEN
Solar/Wind Harmer
5.08
962781AG1-127 GEN
Solar/Wind Harmer
4.819
939401AE1-172 GEN
Solar/Wind Harmer
3.786
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.37
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.638
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.929
959081AF2-199 GEN
Solar/Wind Harmer
4.976
971067AG2-660 GEN
Solar/Wind Harmer
1.659
274822ROCKFORD ;11
Adder
13.956
970825AG2-519 GEN
Solar/Wind Harmer
1.759
972235AH1-702 GEN1
Adder
1.788
970819AG2-516 GEN
Solar/Wind Harmer
5.921
970569AG2-363 GEN
Solar/Wind Harmer
14.789
971475AH1-234 GEN
Solar/Wind Harmer
2.388
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.505
274766LEE CO EC;7U
Adder
6.428
276903AD2-071 C
Solar/Wind Harmer
5.417
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.161
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
6.647
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.748
963741AG1-226 GEN
Solar/Wind Harmer
10.683
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.3
247536S-71 GEN
Solar/Wind Harmer
0.179
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.713
276615X2-022 GEN
Solar/Wind Harmer
0.046
965911AG1-460 GEN
Solar/Wind Harmer
0.838
24728605AND G2
Adder
2.125
970773AG2-487 GEN
Solar/Wind Harmer
0.635
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.323
246936BC-WTG1
Solar/Wind Helper
10.843
270462AD2-086
Solar/Wind Helper
3.651
270223U2-072_GEN1
Solar/Wind Helper
0.855
270578AF1-285 GEN2
Solar/Wind Helper
0.579
270391AF1-285 GEN3
Solar/Wind Helper
0.579
247522W1-056 GEN
Solar/Wind Helper
1.138
960841AF2-375 GEN
Solar/Wind Helper
1.139
270349AD2-093_GEN
Solar/Wind Helper
0.817
970583AG2-370 GEN
50/50
2.859
960851AF2-376 GEN
50/50
2.155
24641605TWIN BRNCH
50/50
0.016
270142AC1-141 CT1_
50/50
2.055
24642205MAYFLWER
50/50
0.571
944961AF1-161 GEN
50/50
2.434
962601AG1-109 GEN
50/50
2.434
24344005CKG1
50/50
5.289
959331AF2-224 GEN
Solar/Wind Harmer
9.739
965021AG1-366 GEN
Solar/Wind Harmer
4.638
970031AG2-029 GEN
Solar/Wind Harmer
5.561
270043AE2-236 GEN
Solar/Wind Harmer
5.288
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.162
971617AH1-308 GEN
Solar/Wind Harmer
5.291
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.927
970349AG2-230 GEN
Solar/Wind Harmer
8.913
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.372
970517AG2-330 GEN
Solar/Wind Harmer
14.231
274752CRETE EC ;2U
Adder
6.419
274753CRETE EC ;3U
Adder
6.419
274724RIVER EC ;11
Adder
13.745
247604X1-042
Adder
0.322
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.474
274802UNIV PARK;5U
Adder
4.445
274826FISK ;BP
Adder
8.338
274800UNIV PARK;3U
Adder
4.433
972038AH1-567 GEN2
Adder
0.277
276806AD2-047 C O1
Solar/Wind Harmer
3.002
970941AG2-585 GEN
Solar/Wind Harmer
6.622
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.805
970707AG2-453 GEN
Solar/Wind Harmer
17.2
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.239
276893AG1-478 C
Solar/Wind Harmer
0.207
274729ELWOOD EC;1P
Adder
12.325
274730ELWOOD EC;6P
Adder
12.325
274734ELWOOD EC;8P
Adder
12.325
274736ELWOOD EC;9P
Adder
12.325
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.672
943591AF1-030 GEN
Solar/Wind Harmer
5.767
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
13.17
970289AG2-191 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.511
958821AF2-173 GEN
Solar/Wind Harmer
7.111
270004AE1-209 GEN
Solar/Wind Harmer
1.101
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.185
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.534
274855GSG-6 ;RU
Solar/Wind Harmer
0.184
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.09
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.985
959091AF2-200 GEN
Solar/Wind Harmer
9.953
972236AH1-702 GEN2
Adder
1.555
970571AG2-364 GEN
Solar/Wind Harmer
9.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.505
274767LEE CO EC;8U
Adder
6.428
946031AF1-268 GEN
Solar/Wind Harmer
4.635
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.294
276157O29GEN1
Solar/Wind Harmer
0.779
274878BISHOP HL;2U
Solar/Wind Harmer
0.161
942111AE2-223 GEN
Solar/Wind Harmer
1.543
965931AG1-462 GEN
Solar/Wind Harmer
11.906
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
14.002
959611AF2-252 GEN
Solar/Wind Harmer
1.556
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.161
971993AH1-541 GEN
Solar/Wind Harmer
2.041
276621W2-048 GEN
Solar/Wind Harmer
0.219
276838X2-022 GEN2
Solar/Wind Harmer
0.245
942481AE2-261 GEN
Solar/Wind Harmer
12.535
970193AG2-126 GEN
Solar/Wind Harmer
6.087
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.445
24728505AND G1
Adder
2.125
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.9
970519AG2-331 GEN
Solar/Wind Harmer
8.446
970699AG2-449 GEN
Solar/Wind Harmer
0.812
270485AE1-090_GEN
Solar/Wind Helper
0.318
942871AE2-306 GEN
Solar/Wind Helper
0.434
270541AE2-072 C
Solar/Wind Helper
0.891
971599AH1-298 GEN
50/50
10.521
24729505KEY G4
50/50
6.883
24653605MOTTVILLE
50/50
0.004
270144AC1-141 ST1_
50/50
1.82
24643105BUCHANAN
50/50
0.011
963791AG1-232 GEN
Solar/Wind Harmer
11.809
965041AG1-368 GEN
Solar/Wind Harmer
8.577
270071AF1-092 GEN
Solar/Wind Harmer
14.687
965051AG1-369 GEN
Solar/Wind Harmer
3.667
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.239
971771AH1-392 GEN
Solar/Wind Harmer
5.998
971347AH1-153 GEN
Solar/Wind Harmer
8.913
971619AH1-309 GEN
Solar/Wind Harmer
2.669
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.451
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.914
274814UNIV PK N;0U
Adder
3.891
274807UNIV PK N;3U
Adder
3.883
274805UNIV PK N;1U
Adder
3.866
274811UNIV PK N;7U
Adder
3.858
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.474
274776LINCOLN ;7U
Adder
6.474
274777LINCOLN ;8U
Adder
6.474
972037AH1-567 GEN1
Adder
0.14
274827FISK ;RP
Adder
5.909
960591AF2-350 GEN
Solar/Wind Harmer
5.298
972227AH1-698 GEN1
Adder
1.975
274687WILL CNTY;4U
Adder
21.05
274687WILL CNTY;4U
Adder
21.05
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.063
274675JOLIET 29;7U
Adder
22.239
274731ELWOOD EC;2P
Adder
12.325
274733ELWOOD EC;3P
Adder
12.325
274735ELWOOD EC;4P
Adder
12.325
274728ELWOOD EC;5P
Adder
12.325
970833AG2-524 GEN
Solar/Wind Harmer
5.728
970833AG2-524 GEN
Solar/Wind Harmer
3.819
971611AH1-305 GEN
Solar/Wind Harmer
3.084
274746AC1-111 G10
Adder
4.142
274744AC1-111 GEN8
Adder
4.142
970289AG2-191 GEN
Solar/Wind Harmer
0.971
270594AE1-207 GEN
Solar/Wind Harmer
5.661
276868AE1-113 GEN
Solar/Wind Harmer
1.012
276882AE2-255 GEN
Solar/Wind Harmer
0.59
971177AH1-047 GEN
Solar/Wind Harmer
3.102
971411AH1-196 GEN
Solar/Wind Harmer
7.515
971675AH1-338 GEN
Solar/Wind Harmer
1.952
970115AG2-085 GEN
Solar/Wind Harmer
1.996
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.953
274823ROCKFORD ;21
Adder
13.855
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.837
970169AG2-114 GEN
Solar/Wind Harmer
4.915
971681AH1-341 GEN
Solar/Wind Harmer
7.885
971549AH1-272 GEN
Solar/Wind Harmer
10.103
961011AF2-392 GEN
Solar/Wind Harmer
2.842
957751AF2-069 GEN
Solar/Wind Harmer
0.159
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.986
941731AE2-173 GEN
Solar/Wind Harmer
3.957
946321AF1-296 GEN
Solar/Wind Harmer
2.629
963841AG1-237 GEN
Solar/Wind Harmer
2.014
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.161
276848AB2-070 GEN3
Solar/Wind Harmer
0.16
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.367
971029AG2-637 GEN
Solar/Wind Harmer
5.468
971673AH1-337 GEN
Solar/Wind Harmer
2.273
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.571
270317AD1-130_GEN
Solar/Wind Helper
4.044
966831AG1-554 GEN
Solar/Wind Helper
0.856
270284AF1-227 GEN1
Solar/Wind Helper
1.824
270286AF1-227 GEN2
Solar/Wind Helper
0.669
270287AF1-227 GEN3
Solar/Wind Helper
0.669
270499AE1-146 GEN
Solar/Wind Helper
1.895
945641AF1-229 GEN
Solar/Wind Helper
0.904
970615AG2-402 GEN
50/50
4.638
24729405KEY G3
50/50
0.376
24729305KEY G2
50/50
0.369
24729205KEY G1
50/50
0.368
247620Y3-023
50/50
0.473
270102X2-052 ST
50/50
1.304
270100X2-052 CT1
50/50
1.202
270101X2-052 CT2
50/50
1.202
970611AG2-400 GEN
Solar/Wind Harmer
13.913
970627AG2-408 GEN
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.035
944541AF1-119 GEN
Solar/Wind Harmer
0.43
960971AF2-388 GEN
Solar/Wind Harmer
3.767
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.858
961051AF2-396 GEN
Solar/Wind Harmer
7.905
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.075
965791AG1-447 GEN
Solar/Wind Harmer
5.189
270599AE1-208 GEN
Solar/Wind Harmer
5.131
270031AE2-169
Solar/Wind Harmer
3.079
970321AG2-212 GEN
Solar/Wind Harmer
2.372
274808UNIV PK N;4U
Adder
3.841
274770LINCOLN ;1U
Adder
6.474
274771LINCOLN ;2U
Adder
6.474
274803UNIV PARK;6U
Adder
4.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.311
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.171
958011AF2-095 GEN
Solar/Wind Harmer
7.629
972259AH1-714 GEN
Adder
14.402
274674JOLIET 9 ;6U
Adder
11.55
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.959
958481AF2-142 GEN
Solar/Wind Harmer
7.707
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.695
274695ROCKY RD ;2P
Adder
8.163
274693ROCKY RD ;1P
Adder
8.082
274697ROCKY RD ;3P
Adder
2.217
274696ROCKY RD ;4P
Adder
8.355
274683WAUKEGAN ;8U
Adder
15.422
274683WAUKEGAN ;8U
Adder
13
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
15.227
958491AF2-143 GEN
Solar/Wind Harmer
7.614
970921AG2-575 GEN
Solar/Wind Harmer
5.064
970921AG2-575 GEN
Solar/Wind Harmer
1.688
971613AH1-306 GEN
Solar/Wind Harmer
2.426
274879MINONK ;1U
Solar/Wind Harmer
0.213
942991AE2-321 GEN
Solar/Wind Harmer
5.619
971333AH1-146 GEN
Solar/Wind Harmer
10.011
971335AH1-147 GEN
Solar/Wind Harmer
10.011
960441AF2-335 GEN
Solar/Wind Harmer
4.991
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.953
971343AH1-151 GEN
Solar/Wind Harmer
9.953
970825AG2-519 GEN
Solar/Wind Harmer
5.49
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.774
274764LEE CO EC;5U
Adder
6.52
274765LEE CO EC;6U
Adder
6.52
274762LEE CO EC;3U
Adder
6.505
274763LEE CO EC;4U
Adder
6.443
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.365
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.883
276741O09 GEN1
Solar/Wind Harmer
0.172
276708O09 GEN2
Solar/Wind Harmer
0.172
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.189
276646AC1-214 GEN2
Solar/Wind Harmer
0.189
966841AG1-555 GEN
Solar/Wind Harmer
0.542
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.165
960611AF2-352 GEN
Solar/Wind Harmer
1.556
970241AG2-163 GEN
Solar/Wind Harmer
2.633
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.003
276916AD2-100_GEN
Solar/Wind Harmer
8.729
276911AD2-131_GEN
Solar/Wind Harmer
0.575
970883AG2-550 GEN
Solar/Wind Harmer
4.063
970885AG2-551 GEN
Solar/Wind Harmer
1.354
945391AF1-204 GEN
Solar/Wind Harmer
4.312
970623AG2-406 GEN
Solar/Wind Harmer
0.709
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.538
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.812
246938BC-WTG3
Solar/Wind Helper
11.029
246937BC-WTG2
Solar/Wind Helper
10.843
270224U2-072_GEN2
Solar/Wind Helper
0.855
270227U2-072_GEN3
Solar/Wind Helper
0.855
270228U2-072_GEN4
Solar/Wind Helper
0.855
270231U2-072_GEN5
Solar/Wind Helper
0.855
270471AD2-092_GEN
Solar/Wind Helper
0.817
253378AE2-206_GEN
Solar/Wind Helper
0.657
276820AF1-078_GEN
Solar/Wind Helper
0.307
241960AC2-195 GEN
Solar/Wind Helper
0.657
944201AF1-088_MTX
Adder
57.673
957141AF2-008_MTX
Adder
8.943
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
NYPJM->LTFIMP_NY
CLTF
1.126
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
2.707
AG2-052LTFEXP_AG2-052->PJM
LTF
0.175
AH1-155LTFEXP_AH1-155->PJM
LTF
0.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.858
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.567
MECLTFEXP_MEC->PJM
CLTF
10.019
SIGELTFEXP_SIGE->PJM
CLTF
0.208
LAGNLTFEXP_LAGN->PJM
CLTF
6.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.094
TVALTFEXP_TVA->PJM
CLTF
2.49

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2500.92
MW Contribution:0.94
Bus #Bus NameTypeMW Contribution
24735205WLF2G2
Adder
4.909
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.747
971403AH1-188 GEN
Solar/Wind Harmer
9.188
971315AH1-136 GEN
Solar/Wind Harmer
1.275
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
1.013
962241AG1-070 GEN
Solar/Wind Harmer
2.607
964901AG1-354 GEN
Solar/Wind Harmer
8.682
339241AF1-083 GEN
Solar/Wind Harmer
0.951
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
5.664
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
1.077
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.669
943111AE2-339 GEN
Solar/Wind Harmer
0.467
943811AF1-049 GEN
Solar/Wind Harmer
1.99
339216AC1-074 GEN
Solar/Wind Harmer
0.86
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
9.348
270445AC2-157 GEN2
Solar/Wind Harmer
2.736
970333AG2-219 GEN
Solar/Wind Harmer
15.351
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.939
963831AG1-236 GEN
Solar/Wind Harmer
4.696
274880W4-005 GEN4
Solar/Wind Harmer
1.442
972175AH1-670 GEN
Solar/Wind Harmer
6.469
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
3.316
274877BISHOP HL;1U
Solar/Wind Harmer
1.583
276158O29GEN2
Solar/Wind Harmer
2.349
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
3.699
939741AE1-205 GEN
Solar/Wind Harmer
9.353
274857EASY ROAD;U1
Solar/Wind Harmer
2.241
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
21.031
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
10.445
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
274745AC1-111 GEN9
Adder
2.558
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
970819AG2-516 GEN
Solar/Wind Harmer
0.945
24735105WLF2G1
Adder
4.909
24734705WLF1G3
Adder
4.898
24734805WLF1G4
Adder
4.898
24734905WLF1G5
Adder
4.898
966391AG1-508 GEN
Solar/Wind Harmer
2.785
971981AH1-535 GEN
Solar/Wind Harmer
7.897
971313AH1-133 GEN
Solar/Wind Harmer
7.717
970281AG2-184 GEN
Solar/Wind Harmer
14.619
972143AH1-644 GEN
Solar/Wind Harmer
6.961
962211AG1-066 GEN
Solar/Wind Harmer
1.642
270399AC1-101 GEN
Solar/Wind Harmer
2.775
270400AC1-102 GEN
Solar/Wind Harmer
2.775
957241AF2-018 GEN
Solar/Wind Harmer
2.86
965401AG1-405 GEN
Solar/Wind Harmer
3.385
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.854
970455AG2-298 GEN
Solar/Wind Harmer
3.268
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.233
972163AH1-664 GEN
Solar/Wind Harmer
4.977
972165AH1-665 GEN
Solar/Wind Harmer
3.982
944221AF1-090 GEN
Solar/Wind Harmer
5.331
276849AB2-070 GEN2
Solar/Wind Harmer
1.072
276848AB2-070 GEN3
Solar/Wind Harmer
1.072
276785W4-005 GEN1
Solar/Wind Harmer
1.442
276174W4-005 GEN2
Solar/Wind Harmer
1.442
946321AF1-296 GEN
Solar/Wind Harmer
4.942
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
3.031
961011AF2-392 GEN
Solar/Wind Harmer
5.096
957751AF2-069 GEN
Solar/Wind Harmer
0.215
276655WTG1_EQ
Solar/Wind Harmer
4.083
276656WTG2_EQ
Solar/Wind Harmer
0.541
959341AF2-225 GEN
Solar/Wind Harmer
7.015
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
7.003
270367AC2-061_GEN
Solar/Wind Harmer
1.482
276612AE2-035 GEN
Solar/Wind Harmer
1.193
274823ROCKFORD ;21
Adder
9.057
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
7.487
274735ELWOOD EC;4P
Adder
2.023
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
270214AC2-123 GEN
Solar/Wind Harmer
2.486
971277AH1-098 GEN
Solar/Wind Harmer
3.314
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.502
971227AH1-073 GEN
Solar/Wind Harmer
1.502
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
3.284
971485AH1-239 GEN
Solar/Wind Harmer
4.843
339231AF1-038_GEN
Solar/Wind Harmer
1.082
339255AE2-071 GEN
Solar/Wind Harmer
0.618
964781AG1-341 GEN
Solar/Wind Harmer
6.173
339236AF1-050_GEN
Solar/Wind Harmer
1.045
971081AG2-670 GEN
Solar/Wind Harmer
4.298
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
2.668
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
3.502
942891AE2-308 GEN
Solar/Wind Harmer
5.447
964571AG1-320 GEN
Solar/Wind Harmer
4.432
971125AH1-004 GEN
Solar/Wind Harmer
2.1
970107AG2-081 GEN
Solar/Wind Harmer
1.575
972043AH1-570 GEN
Solar/Wind Harmer
1.293
972045AH1-571 GEN
Solar/Wind Harmer
1.035
339221AD2-048_GEN
Solar/Wind Harmer
0.789
970235AG2-159 GEN
Solar/Wind Harmer
2.014
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
2.736
970239AG2-162 GEN
Solar/Wind Harmer
5.35
276916AD2-100_GEN
Solar/Wind Harmer
10.174
276911AD2-131_GEN
Solar/Wind Harmer
2.056
957381AF2-032 GEN
Solar/Wind Harmer
0.202
276763AC1-053 GEN1
Solar/Wind Harmer
1.888
276764AC1-053 GEN2
Solar/Wind Harmer
1.888
945391AF1-204 GEN
Solar/Wind Harmer
6.653
270186AC1-089 GEN
Solar/Wind Harmer
2.887
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
1.871
276741O09 GEN1
Solar/Wind Harmer
1.678
276708O09 GEN2
Solar/Wind Harmer
1.678
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
1.333
274849CRESCENT ;1U
Solar/Wind Harmer
0.866
276645AC1-214 GEN1
Solar/Wind Harmer
0.627
276646AC1-214 GEN2
Solar/Wind Harmer
0.627
276603SUBLETTE C
Solar/Wind Harmer
0.491
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
11.684
938861AE1-114 GEN
Solar/Wind Harmer
3.828
274856ECOGROVE ;U1
Solar/Wind Harmer
1.572
276611AD2-172 GEN
Solar/Wind Harmer
1.193
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
970563AG2-360 GEN
50/50
26.913
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
9.063
960911AF2-382 GEN
Solar/Wind Harmer
5.848
971461AH1-227 GEN
Solar/Wind Harmer
3.853
972103AH1-617 GEN
Solar/Wind Harmer
13.923
270053AF1-130 C
Solar/Wind Harmer
2.393
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.326
339250AF1-203 GEN
Solar/Wind Harmer
0.353
971155AH1-034 GEN
Solar/Wind Harmer
5.827
962251AG1-071 GEN
Solar/Wind Harmer
3.186
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
2.839
966571AG1-526 GEN
Solar/Wind Harmer
12.469
970093AG2-073 GEN
Solar/Wind Harmer
5.535
270030AE2-140 GEN
Solar/Wind Harmer
10.994
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
3.962
958171AF2-111 GEN
Solar/Wind Harmer
12.227
970243AG2-164 GEN
Solar/Wind Harmer
12.56
970519AG2-331 GEN
Solar/Wind Harmer
8.438
970699AG2-449 GEN
Solar/Wind Harmer
5.582
942481AE2-261 GEN
Solar/Wind Harmer
14.457
276621W2-048 GEN
Solar/Wind Harmer
2.989
276838X2-022 GEN2
Solar/Wind Harmer
0.111
970193AG2-126 GEN
Solar/Wind Harmer
7.161
276668AB2-070 GEN1
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
1.442
971993AH1-541 GEN
Solar/Wind Harmer
4.403
965931AG1-462 GEN
Solar/Wind Harmer
12.103
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
3.387
965091AG1-374 GEN
Solar/Wind Harmer
14.098
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
1.583
276157O29GEN1
Solar/Wind Harmer
1.787
942111AE2-223 GEN
Solar/Wind Harmer
3.834
274858EASY ROAD;U2
Solar/Wind Harmer
2.241
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
274729ELWOOD EC;1P
Adder
7.487
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219

Details for 05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line l/o AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CLOV17_XFL-05CLOVRD 345.0 kV Ckt 17 line
Contingency Name:
AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.66 %
Rating:2320.0 MVA
Rating Type:B
MVA to Mitigate:2474.48
MW Contribution:3.9
Bus #Bus NameTypeMW Contribution
24735105WLF2G1
50/50
5.209
24734705WLF1G3
50/50
5.198
24734805WLF1G4
50/50
5.198
24734905WLF1G5
50/50
5.198
966391AG1-508 GEN
Solar/Wind Harmer
0.87
971981AH1-535 GEN
Solar/Wind Harmer
3.673
24735205WLF2G2
50/50
5.209
24728305BUCHG2
Adder
3.631
971687AH1-348 GEN
Solar/Wind Harmer
0.521
971403AH1-188 GEN
Solar/Wind Harmer
6.41
971315AH1-136 GEN
Solar/Wind Harmer
0.889
24723205RIVRG3
Adder
11.619
970273AG2-179 GEN
Solar/Wind Harmer
1.456
270336AE1-100 GEN
Solar/Wind Harmer
0.002
962241AG1-070 GEN
Solar/Wind Harmer
2.203
964901AG1-354 GEN
Solar/Wind Harmer
6.057
24686105CER G3
Adder
4.757
24686505CER G6
Adder
4.751
971821AH1-427 GEN
Solar/Wind Harmer
3.952
3429241JKCT 3G
Adder
6.434
971565AH1-281 GEN
Solar/Wind Harmer
0.752
3429421JKCT 10G
Adder
4.484
958131AF2-107 GEN
Solar/Wind Harmer
2.005
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
339216AC1-074 GEN
Solar/Wind Harmer
0.098
970091AG2-072 GEN
Adder
38.082
945681AF1-233 GEN
Solar/Wind Harmer
6.522
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.429
965911AG1-460 GEN
Solar/Wind Harmer
0.675
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.299
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.731
25196008MFTGT1
Adder
0.655
24728605AND G2
Adder
1.803
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
276158O29GEN2
Solar/Wind Harmer
0
25196808ZIMRHP
Adder
35.531
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.568
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.35
274766LEE CO EC;7U
Adder
4.299
963741AG1-226 GEN
Solar/Wind Harmer
7.717
24721705FLATG2
Adder
9.459
971475AH1-234 GEN
Solar/Wind Harmer
1.579
970819AG2-516 GEN
Solar/Wind Harmer
3.899
972235AH1-702 GEN1
Adder
1.172
274822ROCKFORD ;11
Adder
9.123
970569AG2-363 GEN
Solar/Wind Harmer
9.728
252507AC2-088 GEN
Solar/Wind Harmer
0.147
957471AF2-041 GEN
Solar/Wind Harmer
9.717
959081AF2-199 GEN
Solar/Wind Harmer
3.239
971067AG2-660 GEN
Solar/Wind Harmer
1.08
276861AD2-134 GEN
Solar/Wind Harmer
0.058
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.69
962781AG1-127 GEN
Solar/Wind Harmer
3.063
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
970773AG2-487 GEN
Solar/Wind Harmer
0.568
25194608D.CRK4
Adder
0.756
274828WAUKEGAN ;BP
Adder
5.081
274682WAUKEGAN ;7U
Adder
8.262
939401AE1-172 GEN
Solar/Wind Harmer
2.398
276691AA1-018 GEN1
Solar/Wind Harmer
0.387
274745AC1-111 GEN9
Adder
2.558
24791305MDL-5G
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
3.539
276776AD2-060 GEN
Solar/Wind Harmer
0.33
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
3.162
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
2.313
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.94
970291AG2-192 GEN
Solar/Wind Harmer
0.41
276164X3-005 C
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
2.098
270005AE1-210 C O1
Solar/Wind Harmer
0.68
965031AG1-367 GEN
Solar/Wind Harmer
3.137
970825AG2-519 GEN
Solar/Wind Harmer
1.113
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.07
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.002
315616AA1-038_C
Solar/Wind Helper
1.807
3148013FISHERV
Solar/Wind Helper
0.286
316499AE2-029_GEN
Solar/Wind Helper
0.937
3132273ORANGE
Solar/Wind Helper
0.03
3147666LOUISA
Solar/Wind Helper
0.335
237061AD1-155 GEN
Solar/Wind Helper
0.025
316170AC1-121 GEN2
Solar/Wind Helper
0.204
316313AB2-026
Solar/Wind Helper
0.2
316258AE1-075 C
Solar/Wind Helper
0.18
316405AF2-144 C
Solar/Wind Helper
0.15
3146776BUCKING
Solar/Wind Helper
0.045
966881AG1-559 GEN
Solar/Wind Helper
0.168
316473AC1-191 GEN
Solar/Wind Helper
0.759
23583801GRNGAP
Solar/Wind Helper
2.125
238147AE2-230_GEN1
Solar/Wind Helper
0.213
238149AF1-291A_GEN
Solar/Wind Helper
0.061
316095T157 G97
Solar/Wind Helper
0.556
316044AC1-158 PL1
Solar/Wind Helper
0.659
316450AC1-158 RIC
Solar/Wind Helper
0.176
3141906WESTMOR
Solar/Wind Helper
0.046
3142946ENON
Solar/Wind Helper
0.038
3141196NOKESVL
Solar/Wind Helper
0.452
316404AE1-155 C
Solar/Wind Helper
0.945
316484AD2-074 GEN
Solar/Wind Helper
0.215
970563AG2-360 GEN
50/50
26.913
24689505VACITY
50/50
3.172
943031AE2-326 GEN
Solar/Wind Harmer
3.913
962751AG1-124 GEN
Solar/Wind Harmer
6.207
960911AF2-382 GEN
Solar/Wind Harmer
4.08
971461AH1-227 GEN
Solar/Wind Harmer
2.688
972103AH1-617 GEN
Solar/Wind Harmer
9.714
270053AF1-130 C
Solar/Wind Harmer
1.017
972273AH1-721 GEN
Adder
50.38
970273AG2-179 GEN
Solar/Wind Harmer
2.497
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.743
962251AG1-071 GEN
Solar/Wind Harmer
2.526
24686205CER G4
Adder
4.732
24686405CER G5
Adder
4.713
960741AF2-365 GEN
Solar/Wind Harmer
1.981
966571AG1-526 GEN
Solar/Wind Harmer
8.7
970093AG2-073 GEN
Solar/Wind Harmer
3.862
270030AE2-140 GEN
Solar/Wind Harmer
7.67
3429391JKCT 9G
Adder
4.484
972167AH1-666 GEN
Solar/Wind Harmer
2.764
958171AF2-111 GEN
Solar/Wind Harmer
8.53
970243AG2-164 GEN
Solar/Wind Harmer
1.988
970519AG2-331 GEN
Solar/Wind Harmer
8.834
970699AG2-449 GEN
Solar/Wind Harmer
0.849
942481AE2-261 GEN
Solar/Wind Harmer
10.086
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.188
970193AG2-126 GEN
Solar/Wind Harmer
4.996
276668AB2-070 GEN1
Solar/Wind Harmer
0.121
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.536
965931AG1-462 GEN
Solar/Wind Harmer
8.444
25196008MFTGT1
Adder
0.634
24728705AND G3
Adder
3.77
24728505AND G1
Adder
1.803
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.836
959611AF2-252 GEN
Solar/Wind Harmer
1.093
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
276157O29GEN1
Solar/Wind Harmer
0.529
942111AE2-223 GEN
Solar/Wind Harmer
1.06
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.35
274767LEE CO EC;8U
Adder
4.299
24721905FLATG4
Adder
9.459
972236AH1-702 GEN2
Adder
1.02
970571AG2-364 GEN
Solar/Wind Harmer
6.485
959091AF2-200 GEN
Solar/Wind Harmer
6.478
274855GSG-6 ;RU
Solar/Wind Harmer
0.119
274850MENDOTA H;RU
Solar/Wind Harmer
0.038
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.058
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.345
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.118
270356AE2-297 GEN
Solar/Wind Harmer
0.004
276805AD2-038 GEN
Solar/Wind Harmer
0.001
252510AF1-249 C
Solar/Wind Harmer
0.025
25194608D.CRK4
Adder
0.756
274682WAUKEGAN ;7U
Adder
8.262
25196608WSDLE5
Adder
3.936
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.354
943591AF1-030 GEN
Solar/Wind Harmer
3.56
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.188
276893AG1-478 C
Solar/Wind Harmer
0.126
274729ELWOOD EC;1P
Adder
7.487
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.359
276806AD2-047 C O1
Solar/Wind Harmer
1.793
970941AG2-585 GEN
Solar/Wind Harmer
3.954
253316AC1-085 GEN3
Solar/Wind Harmer
0.002
253433AC1-085 GEN1
Solar/Wind Harmer
0.001
946181AF1-283 GEN
Solar/Wind Harmer
4.111
270222AC2-111 GEN
Solar/Wind Harmer
1.601
270437AC2-090 C
Solar/Wind Harmer
0.001
247642Z2-115 C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
0.347
970291AG2-192 GEN
Solar/Wind Harmer
0.315
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
958821AF2-173 GEN
Solar/Wind Harmer
4.392
270004AE1-209 GEN
Solar/Wind Harmer
0.68
964401AG1-302 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
2.971
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
253406AD2-031_GEN
Solar/Wind Harmer
0.232
971191AH1-055 GEN
Solar/Wind Harmer
7.979
3147983MERCK5
Solar/Wind Helper
0.107
316192AB2-158 GEN
Solar/Wind Helper
0.985
3147666LOUISA
Solar/Wind Helper
0.583
958121AF2-106 GEN
Solar/Wind Helper
1.048
316336AC2-165 C
Solar/Wind Helper
0.729
316254AC1-120 GEN1
Solar/Wind Helper
0.611
316322AB2-045
Solar/Wind Helper
0.14
3146776BUCKING
Solar/Wind Helper
0.05
238148AE2-230_GEN2
Solar/Wind Helper
0.214
316006AB2-029 C
Solar/Wind Helper
0.058
3142416OLDCHRC
Solar/Wind Helper
0.318
3142416OLDCHRC
Solar/Wind Helper
0.122
316097T157 G90
Solar/Wind Helper
0.556
316045AC1-158 PL2
Solar/Wind Helper
2.111
3143526WINTERP
Solar/Wind Helper
0.609
3143226MDLTHAN
Solar/Wind Helper
0.117
3142543TWELFTH
Solar/Wind Helper
0.011
316337AD2-073 GEN
Solar/Wind Helper
0.172
964211AG1-282 GEN
Solar/Wind Helper
0.152
3141726DUNNSVL
Solar/Wind Helper
0.452
3142433PROV 92
Solar/Wind Helper
0.448
3141766HARMONY
Solar/Wind Helper
0.022
971313AH1-133 GEN
Solar/Wind Harmer
5.384
970281AG2-184 GEN
Solar/Wind Harmer
10.199
972143AH1-644 GEN
Solar/Wind Harmer
5.262
270399AC1-101 GEN
Solar/Wind Harmer
1.445
270400AC1-102 GEN
Solar/Wind Harmer
1.445
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
965401AG1-405 GEN
Solar/Wind Harmer
2.362
965411AG1-406 GEN
Solar/Wind Harmer
1.519
972203AH1-686 GEN
Adder
1.34
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
2.533
3429211JKCT 2G
Adder
6.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
3.866
972165AH1-665 GEN
Solar/Wind Harmer
3.096
944221AF1-090 GEN
Solar/Wind Harmer
1.996
276849AB2-070 GEN2
Solar/Wind Harmer
0.121
276848AB2-070 GEN3
Solar/Wind Harmer
0.121
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
1.851
25196108MFTGT2
Adder
0.722
25196108MFTGT2
Adder
0.67
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
1.918
957751AF2-069 GEN
Solar/Wind Harmer
0.108
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.426
941731AE2-173 GEN
Solar/Wind Harmer
2.719
971681AH1-341 GEN
Solar/Wind Harmer
5.244
270367AC2-061_GEN
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
9.057
926823AC1-168 GEN
Solar/Wind Harmer
0.551
963841AG1-237 GEN
Solar/Wind Harmer
1.404
971171AH1-044 GEN
Solar/Wind Harmer
6.478
970169AG2-114 GEN
Solar/Wind Harmer
3.233
971675AH1-338 GEN
Solar/Wind Harmer
1.26
971411AH1-196 GEN
Solar/Wind Harmer
4.847
971177AH1-047 GEN
Solar/Wind Harmer
1.99
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
0.646
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
276882AE2-255 GEN
Solar/Wind Harmer
0.376
252524AE2-267 GEN
Solar/Wind Harmer
0.001
25196408WSDLE3
Adder
4.052
25196308WSDLE2
Adder
4.017
25196208WSDLE1
Adder
4.006
25196708WSDLE6
Adder
3.996
25196508WSDLE4
Adder
3.896
274746AC1-111 G10
Adder
2.558
274744AC1-111 GEN8
Adder
2.558
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
3.501
970833AG2-524 GEN
Solar/Wind Harmer
2.334
274731ELWOOD EC;2P
Adder
7.487
274733ELWOOD EC;3P
Adder
6.938
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
3.163
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
1.877
970289AG2-191 GEN
Solar/Wind Harmer
0.599
971985AH1-537 GEN
Solar/Wind Harmer
0.937
270594AE1-207 GEN
Solar/Wind Harmer
3.524
958391AF2-133 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
1.255
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971609AH1-304 GEN
Solar/Wind Harmer
0.508
971673AH1-337 GEN
Solar/Wind Harmer
2.018
3148463FAIRFLD
Solar/Wind Helper
0.398
3148133STUARTS
Solar/Wind Helper
0.172
3148013FISHERV
Solar/Wind Helper
0.165
3138266HYDRAULIC
Solar/Wind Helper
0.011
3138266HYDRAULIC
Solar/Wind Helper
0.007
316164AC1-076 GEN
Solar/Wind Helper
0.618
23546401DTGZ2-030
Solar/Wind Helper
0.04
238152AF2-075_GEN
Solar/Wind Helper
0.304
316312AB1-027
Solar/Wind Helper
0.233
316233AE1-074 FULL
Solar/Wind Helper
0.179
3141426STAFORD
Solar/Wind Helper
0.025
316223AC1-118
Solar/Wind Helper
0.173
3141813NORNECK
Solar/Wind Helper
0.113
3143873LANEXA
Solar/Wind Helper
0.067
316059AD1-063 C
Solar/Wind Helper
0.112
971029AG2-637 GEN
Solar/Wind Harmer
4.547
971277AH1-098 GEN
Solar/Wind Harmer
2.312
24728205BUCHG1
Adder
3.631
971225AH1-072 GEN
Solar/Wind Harmer
1.048
971227AH1-073 GEN
Solar/Wind Harmer
1.048
944971AF1-162 GEN
Solar/Wind Harmer
4.505
24723005RIVRG1
Adder
11.619
24723105RIVRG2
Adder
11.619
966021AG1-471 GEN
Solar/Wind Harmer
2.291
971485AH1-239 GEN
Solar/Wind Harmer
3.379
339255AE2-071 GEN
Solar/Wind Harmer
-0.067
964781AG1-341 GEN
Solar/Wind Harmer
4.307
971081AG2-670 GEN
Solar/Wind Harmer
2.998
24685805CER G1
Adder
4.726
24685905CER G2
Adder
4.726
970653AG2-424 GEN
Solar/Wind Harmer
1.862
970653AG2-424 GEN
Solar/Wind Harmer
0.965
960161AF2-307 GEN
Solar/Wind Harmer
2.512
942891AE2-308 GEN
Solar/Wind Harmer
3.8
964571AG1-320 GEN
Solar/Wind Harmer
3.444
971125AH1-004 GEN
Solar/Wind Harmer
1.465
970107AG2-081 GEN
Solar/Wind Harmer
1.099
972043AH1-570 GEN
Solar/Wind Harmer
0.938
972045AH1-571 GEN
Solar/Wind Harmer
0.752
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970235AG2-159 GEN
Solar/Wind Harmer
2.143
970235AG2-159 GEN
Solar/Wind Harmer
1.23
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.506
970239AG2-162 GEN
Solar/Wind Harmer
0.849
276916AD2-100_GEN
Solar/Wind Harmer
7.098
276911AD2-131_GEN
Solar/Wind Harmer
0.468
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
3.539
270186AC1-089 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
1.093
276782AC1-033 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.117
276708O09 GEN2
Solar/Wind Harmer
0.117
972267AH1-718 GEN
Adder
1.953
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.128
276646AC1-214 GEN2
Solar/Wind Harmer
0.128
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
4.36
274765LEE CO EC;6U
Adder
4.36
274762LEE CO EC;3U
Adder
4.35
274763LEE CO EC;4U
Adder
4.309
970241AG2-163 GEN
Solar/Wind Harmer
1.902
938861AE1-114 GEN
Solar/Wind Harmer
1.846
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
252509AD1-136 GEN
Solar/Wind Harmer
0.016
971341AH1-150 GEN
Solar/Wind Harmer
6.478
971343AH1-151 GEN
Solar/Wind Harmer
6.478
971333AH1-146 GEN
Solar/Wind Harmer
6.465
971335AH1-147 GEN
Solar/Wind Harmer
6.465
962581AG1-107 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
3.603
970921AG2-575 GEN
Solar/Wind Harmer
3.218
970921AG2-575 GEN
Solar/Wind Harmer
1.073
274879MINONK ;1U
Solar/Wind Harmer
0.136
966841AG1-555 GEN
Solar/Wind Harmer
0.364
962691AG1-118 GEN
Solar/Wind Harmer
9.647
958491AF2-143 GEN
Solar/Wind Harmer
4.817
252519AF1-045_GEN
Solar/Wind Harmer
2.794
252516AE2-318_GEN
Solar/Wind Harmer
2.478
25183208HLCRTG
Solar/Wind Harmer
0.005
25194408D.CRK1
Adder
3.478
25194508D.CRK3
Adder
0.65
274683WAUKEGAN ;8U
Adder
9.693
274683WAUKEGAN ;8U
Adder
8.17
274696ROCKY RD ;4P
Adder
5.238
274695ROCKY RD ;2P
Adder
5.117
274693ROCKY RD ;1P
Adder
5.067
274697ROCKY RD ;3P
Adder
1.39
971573AH1-285 GEN
Solar/Wind Harmer
0.596
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.433
958481AF2-142 GEN
Solar/Wind Harmer
4.797
24728805RICHG1
Adder
1.728
24728905RICHG2
Adder
1.728
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.555
253317AC1-085 GEN4
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
971613AH1-306 GEN
Solar/Wind Harmer
1.51
270383AD1-128 GEN
Solar/Wind Harmer
0.002
960441AF2-335 GEN
Solar/Wind Harmer
3.136
970825AG2-519 GEN
Solar/Wind Harmer
3.475
253394AE2-221_GEN
Solar/Wind Harmer
0.004
253398AE2-221_GEN2
Solar/Wind Harmer
0.004
270599AE1-208 GEN
Solar/Wind Harmer
2.851
270031AE2-169
Solar/Wind Harmer
1.71
3132123MT JACKSON
Solar/Wind Helper
0.746
315821AE2-092 GEN
Solar/Wind Helper
1.824
966001AG1-469 GEN
Solar/Wind Helper
0.172
315651AD1-115 GEN
Solar/Wind Helper
0.441
3146776BUCKING
Solar/Wind Helper
0.504
3146776BUCKING
Solar/Wind Helper
0.041
966871AG1-558 GEN
Solar/Wind Helper
0.167
316468AD1-105 GEN
Solar/Wind Helper
0.61
316447AC1-158 HLD
Solar/Wind Helper
1.451
316075AC2-137 C
Solar/Wind Helper
0.179
3143526WINTERP
Solar/Wind Helper
0.609
3142946ENON
Solar/Wind Helper
0.011
316077AC2-138 C
Solar/Wind Helper
0.106
316487AF1-042 GEN
Solar/Wind Helper
0.113
944201AF1-088_MTX
Adder
56.965
957141AF2-008_MTX
Adder
28.482
NYPJM->LTFIMP_NY
CLTF
1.478
LGEELTFEXP_LGEE->PJM
CLTF
3.565
WECLTFEXP_WEC->PJM
CLTF
1.782
CPLELTFEXP_CPLE->PJM
CLTF
3.112
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.214
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.396
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.657
MECLTFEXP_MEC->PJM
CLTF
8.32
SIGELTFEXP_SIGE->PJM
CLTF
0.271
LAGNLTFEXP_LAGN->PJM
CLTF
11.707
CBM South 2LTFEXP_CBM-S2->PJM
CBM
15.107
TVALTFEXP_TVA->PJM
CLTF
6.219

Details for 05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP/DVP
Facility Description:
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.06 %
Rating:3393.4 MVA
Rating Type:B
MVA to Mitigate:4107.97
MW Contribution:7.38
Bus #Bus NameTypeMW Contribution
970479AG2-310 GEN
50/50
20.255
270205AE1-176
50/50
0.006
24288905REUSENS
50/50
0.057
970823AG2-518 GEN
50/50
8.384
247619Y1-049
50/50
0.913
24684705SMG5
50/50
0.856
970481AG2-311 GEN
50/50
11.937
24684605SMG4
50/50
2.239
966251AG1-494 GEN
50/50
4.388
24728405LEESVG
50/50
0.297
24415905BUCK
50/50
0.034
971367AH1-164 GEN
Solar/Wind Harmer
4.886
971329AH1-144 GEN
Solar/Wind Harmer
11.568
3147312GRETNA
Solar/Wind Harmer
0.047
941821AE2-187 GEN
Solar/Wind Harmer
7.452
270197AD1-017 GEN1
Solar/Wind Harmer
1.429
270336AE1-100 GEN
Solar/Wind Harmer
0.006
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
24728305BUCHG2
Adder
6.75
270018AE2-047 C O1
Solar/Wind Harmer
0.004
958131AF2-107 GEN
Solar/Wind Harmer
5.339
24735205WLF2G2
Adder
8.023
971687AH1-348 GEN
Solar/Wind Harmer
0.948
971403AH1-188 GEN
Solar/Wind Harmer
13.153
24723205RIVRG3
Adder
22.954
971315AH1-136 GEN
Solar/Wind Harmer
1.695
24686105CER G3
Adder
9.887
24686505CER G6
Adder
9.874
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24721705FLATG2
Adder
21.686
970947AG2-589 GEN
Solar/Wind Harmer
0.249
970273AG2-179 GEN
Solar/Wind Harmer
2.581
971821AH1-427 GEN
Solar/Wind Harmer
7.218
964901AG1-354 GEN
Solar/Wind Harmer
10.814
962241AG1-070 GEN
Solar/Wind Harmer
3.92
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
3429241JKCT 3G
Adder
12.029
3429421JKCT 10G
Adder
8.402
971565AH1-281 GEN
Solar/Wind Harmer
1.396
339216AC1-074 GEN
Solar/Wind Harmer
0.187
24290605CLAY-1
50/50
0.255
24290605CLAY-1
50/50
0.255
24290705CLAY-2
50/50
0.255
24290705CLAY-2
50/50
0.255
24684405SMG2
50/50
2.224
24684505SMG3
50/50
1.376
24684305SMG1
50/50
0.806
270583AD2-179 GEN
Solar/Wind Harmer
14.457
971277AH1-098 GEN
Solar/Wind Harmer
5.177
316217AC1-145 GEN
Solar/Wind Harmer
0.003
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
5.796
24728205BUCHG1
Adder
6.75
270013AE1-250 PV
Solar/Wind Harmer
0.006
971225AH1-072 GEN
Solar/Wind Harmer
1.905
971227AH1-073 GEN
Solar/Wind Harmer
1.905
944971AF1-162 GEN
Solar/Wind Harmer
9.068
24723005RIVRG1
Adder
22.954
24723105RIVRG2
Adder
22.954
24728405LEESVG
50/50
0.295
24416005BYLLESBY
50/50
0.031
3151561HALLBR1
50/50
0.57
970563AG2-360 GEN
50/50
45.829
962751AG1-124 GEN
Solar/Wind Harmer
12.893
958121AF2-106 GEN
Solar/Wind Harmer
0.001
270173AC1-122 GEN
Solar/Wind Harmer
0.677
971331AH1-145 GEN
Solar/Wind Harmer
18.361
943031AE2-326 GEN
Solar/Wind Harmer
6.784
3147312GRETNA
Solar/Wind Harmer
0.186
3146802CHATHAM
Solar/Wind Harmer
0.175
941801AE2-185 GEN
Solar/Wind Harmer
7.452
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147123OTTER R
Solar/Wind Harmer
0.13
270346AE1-212 GEN
Solar/Wind Harmer
9.542
270030AE2-140 GEN
Solar/Wind Harmer
21.578
960911AF2-382 GEN
Solar/Wind Harmer
7.638
270016AE1-250 BESS
Solar/Wind Harmer
0.006
970913AG2-568 GEN
Solar/Wind Harmer
7.677
971461AH1-227 GEN
Solar/Wind Harmer
4.886
970223AG2-152 GEN
Solar/Wind Harmer
12.358
270053AF1-130 C
Solar/Wind Harmer
2.047
972103AH1-617 GEN
Solar/Wind Harmer
18.024
24686205CER G4
Adder
9.835
24686405CER G5
Adder
9.796
972273AH1-721 GEN
Adder
89.316
24721905FLATG4
Adder
21.686
970273AG2-179 GEN
Solar/Wind Harmer
4.425
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
8.427
962251AG1-071 GEN
Solar/Wind Harmer
4.496
966571AG1-526 GEN
Solar/Wind Harmer
15.967
970093AG2-073 GEN
Solar/Wind Harmer
7.166
960741AF2-365 GEN
Solar/Wind Harmer
3.563
3429391JKCT 9G
Adder
8.402
971543AH1-269 GEN
50/50
12.247
966391AG1-508 GEN
Solar/Wind Harmer
1.993
270069AE2-166 C O1
Solar/Wind Harmer
0.008
971313AH1-133 GEN
Solar/Wind Harmer
10.952
24734705WLF1G3
Adder
8.194
24734805WLF1G4
Adder
8.194
24734905WLF1G5
Adder
8.194
270132AB1-180 C
Adder
0.169
24735105WLF2G1
Adder
8.023
270399AC1-101 GEN
Solar/Wind Harmer
2.892
270400AC1-102 GEN
Solar/Wind Harmer
2.892
24685805CER G1
Adder
9.822
24685905CER G2
Adder
9.822
942751AE2-291 GEN
Solar/Wind Harmer
7.887
966021AG1-471 GEN
Solar/Wind Harmer
4.013
971485AH1-239 GEN
Solar/Wind Harmer
5.928
960161AF2-307 GEN
Solar/Wind Harmer
4.775
339255AE2-071 GEN
Solar/Wind Harmer
-0.119
964781AG1-341 GEN
Solar/Wind Harmer
7.653
971081AG2-670 GEN
Solar/Wind Harmer
5.396
942891AE2-308 GEN
Solar/Wind Harmer
7.099
970653AG2-424 GEN
Solar/Wind Harmer
3.405
970653AG2-424 GEN
Solar/Wind Harmer
1.764
964571AG1-320 GEN
Solar/Wind Harmer
6.361
971125AH1-004 GEN
Solar/Wind Harmer
2.777
970107AG2-081 GEN
Solar/Wind Harmer
2.083
972043AH1-570 GEN
Solar/Wind Harmer
1.796
972045AH1-571 GEN
Solar/Wind Harmer
1.439
339221AD2-048_GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
4.126
970235AG2-159 GEN
Solar/Wind Harmer
2.367
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.663
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.8
252509AD1-136 GEN
Solar/Wind Harmer
0.033
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.589
252516AE2-318_GEN
Solar/Wind Harmer
4.958
25194408D.CRK1
Adder
6.938
25194508D.CRK3
Adder
1.297
971073AG2-665 GEN
Solar/Wind Harmer
5.761
945391AF1-204 GEN
Solar/Wind Harmer
6.765
276916AD2-100_GEN
Solar/Wind Harmer
13.364
276911AD2-131_GEN
Solar/Wind Harmer
0.88
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.651
24728805RICHG1
Adder
3.384
24728905RICHG2
Adder
3.384
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
960251AF2-316 GEN
Solar/Wind Harmer
8.583
960201AF2-311 GEN
Solar/Wind Harmer
5.708
960611AF2-352 GEN
Solar/Wind Harmer
2.073
966841AG1-555 GEN
Solar/Wind Harmer
0.701
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.22
276708O09 GEN2
Solar/Wind Harmer
0.22
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.243
276646AC1-214 GEN2
Solar/Wind Harmer
0.243
972267AH1-718 GEN
Adder
3.688
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.241
274765LEE CO EC;6U
Adder
8.241
274762LEE CO EC;3U
Adder
8.222
274763LEE CO EC;4U
Adder
8.144
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
3.491
274856ECOGROVE ;U1
Solar/Wind Harmer
0.145
276611AD2-172 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
12.273
971343AH1-151 GEN
Solar/Wind Harmer
12.273
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
12.256
971335AH1-147 GEN
Solar/Wind Harmer
12.256
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.834
971613AH1-306 GEN
Solar/Wind Harmer
2.937
274879MINONK ;1U
Solar/Wind Harmer
0.258
970921AG2-575 GEN
Solar/Wind Harmer
6.111
970921AG2-575 GEN
Solar/Wind Harmer
2.037
962691AG1-118 GEN
Solar/Wind Harmer
18.322
958491AF2-143 GEN
Solar/Wind Harmer
9.158
960441AF2-335 GEN
Solar/Wind Harmer
6.106
970825AG2-519 GEN
Solar/Wind Harmer
6.767
274683WAUKEGAN ;8U
Adder
18.419
274683WAUKEGAN ;8U
Adder
15.526
274696ROCKY RD ;4P
Adder
9.957
274695ROCKY RD ;2P
Adder
9.727
274693ROCKY RD ;1P
Adder
9.632
274697ROCKY RD ;3P
Adder
2.642
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.824
958481AF2-142 GEN
Solar/Wind Harmer
9.131
971573AH1-285 GEN
Solar/Wind Harmer
1.134
3132123MT JACKSON
Solar/Wind Helper
1.389
315821AE2-092 GEN
Solar/Wind Helper
3.216
966001AG1-469 GEN
Solar/Wind Helper
0.32
315651AD1-115 GEN
Solar/Wind Helper
0.837
966871AG1-558 GEN
Solar/Wind Helper
0.306
316447AC1-158 HLD
Solar/Wind Helper
2.766
316468AD1-105 GEN
Solar/Wind Helper
1.124
945681AF1-233 GEN
Solar/Wind Harmer
12.782
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970091AG2-072 GEN
Adder
74.012
970333AG2-219 GEN
Solar/Wind Harmer
4.755
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25196808ZIMRHP
Adder
70.616
252507AC2-088 GEN
Solar/Wind Harmer
0.295
25196008MFTGT1
Adder
1.293
25194608D.CRK4
Adder
1.508
965911AG1-460 GEN
Solar/Wind Harmer
1.271
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.331
24728605AND G2
Adder
3.48
276615X2-022 GEN
Solar/Wind Harmer
0.066
963831AG1-236 GEN
Solar/Wind Harmer
2.455
274880W4-005 GEN4
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.107
963741AG1-226 GEN
Solar/Wind Harmer
14.811
972175AH1-670 GEN
Solar/Wind Harmer
5.171
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.673
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.208
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.222
274766LEE CO EC;7U
Adder
8.125
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.519
276903AD2-071 C
Solar/Wind Harmer
6.874
971475AH1-234 GEN
Solar/Wind Harmer
2.986
970819AG2-516 GEN
Solar/Wind Harmer
7.379
970569AG2-363 GEN
Solar/Wind Harmer
18.444
972235AH1-702 GEN1
Adder
2.22
24791305MDL-5G
Solar/Wind Harmer
0.001
274822ROCKFORD ;11
Adder
17.275
957471AF2-041 GEN
Solar/Wind Harmer
18.409
959081AF2-199 GEN
Solar/Wind Harmer
6.136
971067AG2-660 GEN
Solar/Wind Harmer
2.045
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.11
970291AG2-192 GEN
Solar/Wind Harmer
0.796
971997AH1-543 GEN
Solar/Wind Harmer
3.211
270032AE2-172
Solar/Wind Harmer
4.079
270263AC1-001 GEN
Solar/Wind Harmer
0.614
274872LEEDK;1U
Solar/Wind Harmer
0.004
270005AE1-210 C O1
Solar/Wind Harmer
1.324
965031AG1-367 GEN
Solar/Wind Harmer
6.111
962781AG1-127 GEN
Solar/Wind Harmer
5.815
276901AD2-066 C O1
Solar/Wind Harmer
0.006
939401AE1-172 GEN
Solar/Wind Harmer
4.568
970825AG2-519 GEN
Solar/Wind Harmer
2.167
274828WAUKEGAN ;BP
Adder
9.655
274682WAUKEGAN ;7U
Adder
15.703
276691AA1-018 GEN1
Solar/Wind Harmer
0.737
274745AC1-111 GEN9
Adder
4.87
315616AA1-038_C
Solar/Wind Helper
3.293
3148013FISHERV
Solar/Wind Helper
0.523
316499AE2-029_GEN
Solar/Wind Helper
1.725
3132273ORANGE
Solar/Wind Helper
0.056
3147666LOUISA
Solar/Wind Helper
0.625
237061AD1-155 GEN
Solar/Wind Helper
0.05
316170AC1-121 GEN2
Solar/Wind Helper
0.386
23583801GRNGAP
Solar/Wind Helper
4.287
316095T157 G97
Solar/Wind Helper
1.125
238147AE2-230_GEN1
Solar/Wind Helper
0.421
238149AF1-291A_GEN
Solar/Wind Helper
0.12
316313AB2-026
Solar/Wind Helper
0.354
316258AE1-075 C
Solar/Wind Helper
0.319
316405AF2-144 C
Solar/Wind Helper
0.265
966881AG1-559 GEN
Solar/Wind Helper
0.313
316473AC1-191 GEN
Solar/Wind Helper
1.387
316044AC1-158 PL1
Solar/Wind Helper
1.257
316450AC1-158 RIC
Solar/Wind Helper
0.335
941621AE2-160 GEN
Adder
4.285
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
970281AG2-184 GEN
Solar/Wind Harmer
18.925
972143AH1-644 GEN
Solar/Wind Harmer
9.763
971981AH1-535 GEN
Solar/Wind Harmer
5.843
971061AG2-657 GEN
Solar/Wind Harmer
5.368
24477305BRIDGE
Adder
0.419
972203AH1-686 GEN
Adder
2.704
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
965401AG1-405 GEN
Solar/Wind Harmer
4.227
965411AG1-406 GEN
Solar/Wind Harmer
2.719
339211AE2-254 GEN
Solar/Wind Harmer
0.003
3429211JKCT 2G
Adder
11.873
970455AG2-298 GEN
Solar/Wind Harmer
4.677
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
972163AH1-664 GEN
Solar/Wind Harmer
7.568
972165AH1-665 GEN
Solar/Wind Harmer
6.061
971985AH1-537 GEN
Solar/Wind Harmer
2.011
270367AC2-061_GEN
Solar/Wind Harmer
0.005
316123AC1-075 GEN
Solar/Wind Harmer
0.168
970165AG2-112 GEN
Solar/Wind Harmer
0.998
970163AG2-111 GEN
Solar/Wind Harmer
0.952
25196108MFTGT2
Adder
1.425
25196108MFTGT2
Adder
1.324
970879AG2-548 GEN
Solar/Wind Harmer
5.761
944221AF1-090 GEN
Solar/Wind Harmer
3.754
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.08
25196308WSDLE2
Adder
8.01
25196208WSDLE1
Adder
7.99
25196708WSDLE6
Adder
7.97
25196508WSDLE4
Adder
7.769
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.229
276848AB2-070 GEN3
Solar/Wind Harmer
0.228
963841AG1-237 GEN
Solar/Wind Harmer
2.698
946321AF1-296 GEN
Solar/Wind Harmer
3.483
270340AC2-060 GEN
Solar/Wind Harmer
0.007
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.505
941731AE2-173 GEN
Solar/Wind Harmer
5.162
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.204
961011AF2-392 GEN
Solar/Wind Harmer
3.623
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
9.917
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.045
970169AG2-114 GEN
Solar/Wind Harmer
6.149
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274823ROCKFORD ;21
Adder
17.15
971171AH1-044 GEN
Solar/Wind Harmer
12.273
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
2.39
971411AH1-196 GEN
Solar/Wind Harmer
9.19
970289AG2-191 GEN
Solar/Wind Harmer
1.163
971177AH1-047 GEN
Solar/Wind Harmer
3.774
270594AE1-207 GEN
Solar/Wind Harmer
6.853
276868AE1-113 GEN
Solar/Wind Harmer
1.227
276882AE2-255 GEN
Solar/Wind Harmer
0.715
970115AG2-085 GEN
Solar/Wind Harmer
2.442
971673AH1-337 GEN
Solar/Wind Harmer
3.956
274746AC1-111 G10
Adder
4.87
274744AC1-111 GEN8
Adder
4.87
25306009OHH W.
Adder
2.505
3148463FAIRFLD
Solar/Wind Helper
0.726
3148133STUARTS
Solar/Wind Helper
0.313
3148013FISHERV
Solar/Wind Helper
0.3
3138266HYDRAULIC
Solar/Wind Helper
0.02
3138266HYDRAULIC
Solar/Wind Helper
0.012
23546401DTGZ2-030
Solar/Wind Helper
0.078
316164AC1-076 GEN
Solar/Wind Helper
1.172
238152AF2-075_GEN
Solar/Wind Helper
0.602
971029AG2-637 GEN
Solar/Wind Harmer
2.803
971191AH1-055 GEN
Solar/Wind Harmer
18.055
972167AH1-666 GEN
Solar/Wind Harmer
5.419
958171AF2-111 GEN
Solar/Wind Harmer
16.681
970243AG2-164 GEN
Solar/Wind Harmer
3.891
970519AG2-331 GEN
Solar/Wind Harmer
17.292
970699AG2-449 GEN
Solar/Wind Harmer
1.663
25196008MFTGT1
Adder
1.252
252510AF1-249 C
Solar/Wind Harmer
0.05
25194608D.CRK4
Adder
1.508
25196608WSDLE5
Adder
7.849
970193AG2-126 GEN
Solar/Wind Harmer
9.55
942481AE2-261 GEN
Solar/Wind Harmer
18.997
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.231
24728705AND G3
Adder
7.277
24728505AND G1
Adder
3.48
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.229
971993AH1-541 GEN
Solar/Wind Harmer
2.905
270356AE2-297 GEN
Solar/Wind Harmer
0.008
253406AD2-031_GEN
Solar/Wind Harmer
0.467
270222AC2-111 GEN
Solar/Wind Harmer
3.158
965931AG1-462 GEN
Solar/Wind Harmer
15.879
270291AC1-194 GEN
Solar/Wind Harmer
4.924
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
18.654
959611AF2-252 GEN
Solar/Wind Harmer
2.073
942111AE2-223 GEN
Solar/Wind Harmer
2.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.208
276157O29GEN1
Solar/Wind Harmer
0.999
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.222
274767LEE CO EC;8U
Adder
8.125
270437AC2-090 C
Solar/Wind Harmer
0.003
970571AG2-364 GEN
Solar/Wind Harmer
12.296
253415AE1-040 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
1.93
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.144
959091AF2-200 GEN
Solar/Wind Harmer
12.273
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.225
274850MENDOTA H;RU
Solar/Wind Harmer
0.072
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.11
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.654
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.673
970291AG2-192 GEN
Solar/Wind Harmer
0.612
274872LEEDK;1U
Solar/Wind Harmer
0.224
958821AF2-173 GEN
Solar/Wind Harmer
8.556
270004AE1-209 GEN
Solar/Wind Harmer
1.324
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.703
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
946031AF1-268 GEN
Solar/Wind Harmer
5.79
943121AE2-341 GEN
Solar/Wind Harmer
10.192
943591AF1-030 GEN
Solar/Wind Harmer
6.778
274729ELWOOD EC;1P
Adder
13.481
3147983MERCK5
Solar/Wind Helper
0.198
316192AB2-158 GEN
Solar/Wind Helper
1.838
3147666LOUISA
Solar/Wind Helper
1.088
316254AC1-120 GEN1
Solar/Wind Helper
1.159
316097T157 G90
Solar/Wind Helper
1.125
238148AE2-230_GEN2
Solar/Wind Helper
0.423
316336AC2-165 C
Solar/Wind Helper
1.285
316006AB2-029 C
Solar/Wind Helper
0.112
316045AC1-158 PL2
Solar/Wind Helper
4.023
944201AF1-088_MTX
Adder
109.09
957141AF2-008_MTX
Adder
54.545
NYPJM->LTFIMP_NY
CLTF
3.248
LGEELTFEXP_LGEE->PJM
CLTF
6.763
WECLTFEXP_WEC->PJM
CLTF
3.371
CPLELTFEXP_CPLE->PJM
CLTF
6.226
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.111
AG2-052LTFEXP_AG2-052->PJM
LTF
0.202
AH1-155LTFEXP_AH1-155->PJM
LTF
0.303
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.415
CBM South 1LTFEXP_CBM-S1->PJM
CBM
39.315
MECLTFEXP_MEC->PJM
CLTF
15.415
SIGELTFEXP_SIGE->PJM
CLTF
0.508
LAGNLTFEXP_LAGN->PJM
CLTF
20.28
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.555
TVALTFEXP_TVA->PJM
CLTF
10.606

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:135.7 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:6786.3
MW Contribution:22.99
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
14.331
970513AG2-328 GEN
Solar/Wind Harmer
47.341
970517AG2-330 GEN
Solar/Wind Harmer
42.937
970349AG2-230 GEN
Solar/Wind Harmer
33.644
970707AG2-453 GEN
Solar/Wind Harmer
59.18
972228AH1-698 GEN2
Adder
7.649
276897AD1-100 C
Solar/Wind Harmer
59.931
939351AE1-166 GEN
Solar/Wind Harmer
12.245
276772AC2-154 GEN
Solar/Wind Harmer
5.736
276806AD2-047 C O1
Solar/Wind Harmer
22.004
970941AG2-585 GEN
Solar/Wind Harmer
25.711
274724RIVER EC ;11
Adder
36.314
274800UNIV PARK;3U
Adder
11.955
972038AH1-567 GEN2
Adder
0.748
943121AE2-341 GEN
Solar/Wind Harmer
30.756
943591AF1-030 GEN
Solar/Wind Harmer
20.504
274826FISK ;BP
Adder
22.446
274802UNIV PARK;5U
Adder
11.932
274676JOLIET 29;8U
Adder
60.528
274729ELWOOD EC;1P
Adder
33.534
274730ELWOOD EC;6P
Adder
33.533
274734ELWOOD EC;8P
Adder
33.533
274736ELWOOD EC;9P
Adder
33.533
276893AG1-478 C
Solar/Wind Harmer
0.85
972231SS25-0005
Solar/Wind Harmer
19.213
972181SS23-001
Solar/Wind Harmer
12.008
24344105CKG2
50/50
20.151
274773LINCOLN ;4U
50/50
14.331
274774LINCOLN ;5U
50/50
14.331
970245AG2-165 GEN
Solar/Wind Harmer
47.341
972207SS24-0001
Solar/Wind Harmer
48.017
941551AE2-152 GEN
Solar/Wind Harmer
9.366
276164X3-005 C
Solar/Wind Harmer
1.446
276776AD2-060 GEN
Solar/Wind Harmer
0.87
274801UNIV PARK;4U
Adder
11.955
274871GR RIDGE ;2U
Solar/Wind Harmer
15.767
274723RIVER EC ;12
Adder
36.71
274676JOLIET 29;8U
Adder
62.769
274674JOLIET 9 ;6U
Adder
31.468
274745AC1-111 GEN9
Adder
11.404
274732ELWOOD EC;7P
Adder
33.533
274812UNIV PK N;8U
Adder
10.201
274751CRETE EC ;1U
Adder
9.895
274754CRETE EC ;4U
Adder
9.895
274682WAUKEGAN ;7U
Adder
35.931
274828WAUKEGAN ;BP
Adder
22.049
960751AF2-366 GEN
Solar/Wind Harmer
5.701
962781AG1-127 GEN
Solar/Wind Harmer
18.895
276691AA1-018 GEN1
Solar/Wind Harmer
0.924
274872LEEDK;1U
Solar/Wind Harmer
16.273
274775LINCOLN ;6U
50/50
14.331
274776LINCOLN ;7U
50/50
14.331
274777LINCOLN ;8U
50/50
14.331
971347AH1-153 GEN
Solar/Wind Harmer
33.644
972227AH1-698 GEN1
Adder
5.386
960591AF2-350 GEN
Solar/Wind Harmer
20.569
970833AG2-524 GEN
Solar/Wind Harmer
17.904
970833AG2-524 GEN
Solar/Wind Harmer
8.327
274827FISK ;RP
Adder
15.907
960681AF2-359 GEN
Solar/Wind Harmer
7.733
972037AH1-567 GEN1
Adder
0.375
274675JOLIET 29;7U
Adder
62.771
274675JOLIET 29;7U
Adder
60.529
274687WILL CNTY;4U
Adder
57.132
274687WILL CNTY;4U
Adder
57.132
274746AC1-111 G10
Adder
11.404
274744AC1-111 GEN8
Adder
11.404
274731ELWOOD EC;2P
Adder
33.534
274733ELWOOD EC;3P
Adder
33.534
274735ELWOOD EC;4P
Adder
33.534
274728ELWOOD EC;5P
Adder
33.533
274814UNIV PK N;0U
Adder
10.29
274807UNIV PK N;3U
Adder
10.268
274805UNIV PK N;1U
Adder
10.223
274811UNIV PK N;7U
Adder
10.201
971177AH1-047 GEN
Solar/Wind Harmer
11.509
971675AH1-338 GEN
Solar/Wind Harmer
35.22
971411AH1-196 GEN
Solar/Wind Harmer
29.309
276868AE1-113 GEN
Solar/Wind Harmer
19.753
276882AE2-255 GEN
Solar/Wind Harmer
6.585
971171AH1-044 GEN
Solar/Wind Harmer
38.786
971769AH1-391 GEN
Solar/Wind Harmer
19.386
274863CRW1-WTG
Solar/Wind Harmer
10.817
274864CRW2-WTG
Solar/Wind Harmer
10.817
274823ROCKFORD ;21
Adder
37.601
270536AF1-215 GEN2
Solar/Wind Harmer
8.732
939401AE1-172 GEN
Solar/Wind Harmer
27.539
970333AG2-219 GEN
Solar/Wind Harmer
62.187
276901AD2-066 C O1
Solar/Wind Harmer
6.889
970373AG2-245 GEN
Solar/Wind Harmer
41.146
971997AH1-543 GEN
Solar/Wind Harmer
30.811
276861AD2-134 GEN
Solar/Wind Harmer
3.494
957471AF2-041 GEN
Solar/Wind Harmer
58.179
959081AF2-199 GEN
Solar/Wind Harmer
19.393
971067AG2-660 GEN
Solar/Wind Harmer
4.51
274822ROCKFORD ;11
Adder
37.876
972235AH1-702 GEN1
Adder
4.85
270055AF2-134 C O1
Solar/Wind Harmer
5.82
276876AE1-163_GEN2
Solar/Wind Harmer
12.894
970819AG2-516 GEN
Solar/Wind Harmer
22.991
971475AH1-234 GEN
Solar/Wind Harmer
42.761
970569AG2-363 GEN
Solar/Wind Harmer
56.806
958381AF2-132 GEN
Solar/Wind Harmer
17.135
274761LEE CO EC;2U
Adder
17.564
274766LEE CO EC;7U
Adder
17.357
970091AG2-072 GEN
Adder
126.966
24639705ELKHART HY
Adder
0.231
274857EASY ROAD;U1
Solar/Wind Harmer
8.443
274752CRETE EC ;2U
Adder
9.895
274753CRETE EC ;3U
Adder
9.895
274682WAUKEGAN ;7U
Adder
35.931
276694AA1-018 GEN2
Solar/Wind Harmer
12.526
274872LEEDK;1U
Solar/Wind Harmer
0.507
970243AG2-164 GEN
Solar/Wind Harmer
50.88
970519AG2-331 GEN
Solar/Wind Harmer
34.183
970699AG2-449 GEN
Solar/Wind Harmer
22.613
276799AD1-013 GEN
Solar/Wind Harmer
4.328
946671AF1-331 GEN
Solar/Wind Harmer
0.82
276805AD2-038 GEN
Solar/Wind Harmer
10.042
274855GSG-6 ;RU
Solar/Wind Harmer
7.224
274850MENDOTA H;RU
Solar/Wind Harmer
5.023
276602WESTBROOK C
Solar/Wind Harmer
4.158
276863AD2-134 GEN
Solar/Wind Harmer
3.494
959091AF2-200 GEN
Solar/Wind Harmer
38.786
972236AH1-702 GEN2
Adder
4.217
270535AF1-215 GEN1
Solar/Wind Harmer
8.732
276889AE2-281 GEN
Solar/Wind Harmer
3.684
970571AG2-364 GEN
Solar/Wind Harmer
37.87
964401AG1-302 GEN
Solar/Wind Harmer
17.135
274760LEE CO EC;1U
Adder
17.564
274767LEE CO EC;8U
Adder
17.357
24642205MAYFLWER
Adder
1.151
247604X1-042
Adder
0.741
274858EASY ROAD;U2
Solar/Wind Harmer
8.443
274770LINCOLN ;1U
50/50
14.331
274771LINCOLN ;2U
50/50
14.331
274661LASCO STA;2U
50/50
15.039
972259AH1-714 GEN
50/50
42.213
274660LASCO STA;1U
50/50
15.232
970321AG2-212 GEN
Solar/Wind Harmer
47.341
274888KELLY CRK;1U
Solar/Wind Harmer
12.144
274887GEN-1.85
Solar/Wind Harmer
10.964
276843GEN-1.7
Solar/Wind Harmer
1.18
958011AF2-095 GEN
Solar/Wind Harmer
29.62
274847GR RIDGE ;BU
Solar/Wind Harmer
10.372
965681AG1-436 GEN
Solar/Wind Harmer
25.586
965791AG1-447 GEN
Solar/Wind Harmer
13.09
274803UNIV PARK;6U
Adder
11.932
274674JOLIET 9 ;6U
Adder
31.468
274808UNIV PK N;4U
Adder
10.156
971573AH1-285 GEN
Solar/Wind Harmer
17.498
274695ROCKY RD ;2P
Adder
22.358
274693ROCKY RD ;1P
Adder
22.138
274697ROCKY RD ;3P
Adder
6.074
274696ROCKY RD ;4P
Adder
22.884
274683WAUKEGAN ;8U
Adder
42.064
274683WAUKEGAN ;8U
Adder
35.458
962691AG1-118 GEN
Solar/Wind Harmer
59.796
970921AG2-575 GEN
Solar/Wind Harmer
19.869
970921AG2-575 GEN
Solar/Wind Harmer
4.621
958481AF2-142 GEN
Solar/Wind Harmer
29.773
274861TOP CROP ;1U
Solar/Wind Harmer
12.015
274862TOP CROP ;2U
Solar/Wind Harmer
10.033
970239AG2-162 GEN
Solar/Wind Harmer
21.671
942991AE2-321 GEN
Solar/Wind Harmer
19.649
958491AF2-143 GEN
Solar/Wind Harmer
29.362
971333AH1-146 GEN
Solar/Wind Harmer
39.061
971335AH1-147 GEN
Solar/Wind Harmer
39.061
274879MINONK ;1U
Solar/Wind Harmer
13.17
971341AH1-150 GEN
Solar/Wind Harmer
38.786
971343AH1-151 GEN
Solar/Wind Harmer
38.786
24441505OLIV SLR
Solar/Wind Harmer
0.26
276872AE1-163_GEN1
Solar/Wind Harmer
12.894
270526AF1-158 GEN
Solar/Wind Harmer
8.708
274856ECOGROVE ;U1
Solar/Wind Harmer
6.451
276611AD2-172 GEN
Solar/Wind Harmer
4.895
938861AE1-114 GEN
Solar/Wind Harmer
15.551
274764LEE CO EC;5U
Adder
17.605
274765LEE CO EC;6U
Adder
17.605
274762LEE CO EC;3U
Adder
17.564
274763LEE CO EC;4U
Adder
17.398
972267AH1-718 GEN
Adder
7.762
247620Y3-023
Adder
0.631
276612AE2-035 GEN
Solar/Wind Harmer
4.895
926823AC1-168 GEN
Solar/Wind Harmer
8.176
971681AH1-341 GEN
Solar/Wind Harmer
28.47
970169AG2-114 GEN
Solar/Wind Harmer
18.975
944201AF1-088_MTX
Adder
159.345
957141AF2-008_MTX
Adder
47.039
NYPJM->LTFIMP_NY
CLTF
2.982
LGEELTFEXP_LGEE->PJM
CLTF
1.518
WECLTFEXP_WEC->PJM
CLTF
7.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
107.237
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.277
AG2-052LTFEXP_AG2-052->PJM
LTF
0.428
AH1-155LTFEXP_AH1-155->PJM
LTF
0.642
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.619
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.519
MECLTFEXP_MEC->PJM
CLTF
25.73
SIGELTFEXP_SIGE->PJM
CLTF
0.333
LAGNLTFEXP_LAGN->PJM
CLTF
11.754
TVALTFEXP_TVA->PJM
CLTF
3.905

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.54 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:6078.08
MW Contribution:20.92
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.089
274771LINCOLN ;2U
50/50
13.089
274661LASCO STA;2U
50/50
13.7
972259AH1-714 GEN
50/50
38.454
274660LASCO STA;1U
50/50
13.875
970321AG2-212 GEN
Solar/Wind Harmer
42.678
274772LINCOLN ;3U
50/50
13.089
970513AG2-328 GEN
Solar/Wind Harmer
42.678
274775LINCOLN ;6U
50/50
13.089
274776LINCOLN ;7U
50/50
13.089
274777LINCOLN ;8U
50/50
13.089
971347AH1-153 GEN
Solar/Wind Harmer
30.772
972227AH1-698 GEN1
Adder
4.901
960591AF2-350 GEN
Solar/Wind Harmer
18.708
970833AG2-524 GEN
Solar/Wind Harmer
16.295
970833AG2-524 GEN
Solar/Wind Harmer
7.579
274827FISK ;RP
Adder
14.467
274675JOLIET 29;7U
Adder
57.12
274675JOLIET 29;7U
Adder
55.08
972037AH1-567 GEN1
Adder
0.34
274687WILL CNTY;4U
Adder
51.979
274687WILL CNTY;4U
Adder
51.979
274746AC1-111 G10
Adder
10.386
274744AC1-111 GEN8
Adder
10.386
274731ELWOOD EC;2P
Adder
30.503
274733ELWOOD EC;3P
Adder
30.503
274735ELWOOD EC;4P
Adder
30.503
274728ELWOOD EC;5P
Adder
30.502
960681AF2-359 GEN
Solar/Wind Harmer
6.995
274814UNIV PK N;0U
Adder
9.345
274807UNIV PK N;3U
Adder
9.324
274888KELLY CRK;1U
Solar/Wind Harmer
11.045
274887GEN-1.85
Solar/Wind Harmer
9.972
276843GEN-1.7
Solar/Wind Harmer
1.073
958011AF2-095 GEN
Solar/Wind Harmer
26.939
274847GR RIDGE ;BU
Solar/Wind Harmer
9.44
274803UNIV PARK;6U
Adder
10.847
274674JOLIET 9 ;6U
Adder
28.631
971573AH1-285 GEN
Solar/Wind Harmer
15.941
965681AG1-436 GEN
Solar/Wind Harmer
23.145
965791AG1-447 GEN
Solar/Wind Harmer
11.842
274808UNIV PK N;4U
Adder
9.223
274695ROCKY RD ;2P
Adder
20.356
274693ROCKY RD ;1P
Adder
20.155
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.835
274683WAUKEGAN ;8U
Adder
38.287
274683WAUKEGAN ;8U
Adder
32.274
962691AG1-118 GEN
Solar/Wind Harmer
54.441
970921AG2-575 GEN
Solar/Wind Harmer
18.089
970921AG2-575 GEN
Solar/Wind Harmer
4.207
958481AF2-142 GEN
Solar/Wind Harmer
27.047
274861TOP CROP ;1U
Solar/Wind Harmer
10.914
274862TOP CROP ;2U
Solar/Wind Harmer
9.114
942991AE2-321 GEN
Solar/Wind Harmer
17.883
970517AG2-330 GEN
Solar/Wind Harmer
38.708
970349AG2-230 GEN
Solar/Wind Harmer
30.772
970707AG2-453 GEN
Solar/Wind Harmer
53.983
972228AH1-698 GEN2
Adder
6.96
276897AD1-100 C
Solar/Wind Harmer
54.524
939351AE1-166 GEN
Solar/Wind Harmer
11.141
971333AH1-146 GEN
Solar/Wind Harmer
35.546
971335AH1-147 GEN
Solar/Wind Harmer
35.546
958491AF2-143 GEN
Solar/Wind Harmer
26.66
274879MINONK ;1U
Solar/Wind Harmer
11.959
971341AH1-150 GEN
Solar/Wind Harmer
35.289
971343AH1-151 GEN
Solar/Wind Harmer
35.289
24441505OLIV SLR
Solar/Wind Harmer
0.235
276872AE1-163_GEN1
Solar/Wind Harmer
11.698
274856ECOGROVE ;U1
Solar/Wind Harmer
5.868
276611AD2-172 GEN
Solar/Wind Harmer
4.452
270526AF1-158 GEN
Solar/Wind Harmer
7.861
938861AE1-114 GEN
Solar/Wind Harmer
14.142
274764LEE CO EC;5U
Adder
16.009
274765LEE CO EC;6U
Adder
16.009
274762LEE CO EC;3U
Adder
15.971
274763LEE CO EC;4U
Adder
15.821
276603SUBLETTE C
Solar/Wind Harmer
1.797
972267AH1-718 GEN
Adder
7.055
276741O09 GEN1
Solar/Wind Harmer
6.029
276708O09 GEN2
Solar/Wind Harmer
6.029
274851PROVIDENC;RU
Solar/Wind Harmer
4.761
274849CRESCENT ;1U
Solar/Wind Harmer
3.091
276645AC1-214 GEN1
Solar/Wind Harmer
2.239
276646AC1-214 GEN2
Solar/Wind Harmer
2.239
276782AC1-033 GEN
Solar/Wind Harmer
6.624
247620Y3-023
Adder
0.556
24344105CKG2
50/50
18.645
274773LINCOLN ;4U
50/50
13.089
274774LINCOLN ;5U
50/50
13.089
970245AG2-165 GEN
Solar/Wind Harmer
42.678
972207SS24-0001
Solar/Wind Harmer
43.856
941551AE2-152 GEN
Solar/Wind Harmer
8.521
276164X3-005 C
Solar/Wind Harmer
1.315
276776AD2-060 GEN
Solar/Wind Harmer
0.791
274871GR RIDGE ;2U
Solar/Wind Harmer
14.351
274801UNIV PARK;4U
Adder
10.872
274676JOLIET 29;8U
Adder
57.118
274723RIVER EC ;12
Adder
33.353
274674JOLIET 9 ;6U
Adder
28.631
274745AC1-111 GEN9
Adder
10.386
274732ELWOOD EC;7P
Adder
30.502
274812UNIV PK N;8U
Adder
9.264
274751CRETE EC ;1U
Adder
8.975
274754CRETE EC ;4U
Adder
8.975
274682WAUKEGAN ;7U
Adder
32.706
274828WAUKEGAN ;BP
Adder
20.069
960751AF2-366 GEN
Solar/Wind Harmer
5.19
962781AG1-127 GEN
Solar/Wind Harmer
17.202
274872LEEDK;1U
Solar/Wind Harmer
14.814
276691AA1-018 GEN1
Solar/Wind Harmer
0.84
939401AE1-172 GEN
Solar/Wind Harmer
24.967
276901AD2-066 C O1
Solar/Wind Harmer
6.254
276861AD2-134 GEN
Solar/Wind Harmer
3.179
971997AH1-543 GEN
Solar/Wind Harmer
27.98
957471AF2-041 GEN
Solar/Wind Harmer
52.933
959081AF2-199 GEN
Solar/Wind Harmer
17.644
971067AG2-660 GEN
Solar/Wind Harmer
4.103
274822ROCKFORD ;11
Adder
34.461
972235AH1-702 GEN1
Adder
4.412
970819AG2-516 GEN
Solar/Wind Harmer
20.916
276876AE1-163_GEN2
Solar/Wind Harmer
11.698
970373AG2-245 GEN
Solar/Wind Harmer
36.568
971475AH1-234 GEN
Solar/Wind Harmer
38.902
970569AG2-363 GEN
Solar/Wind Harmer
51.507
274857EASY ROAD;U1
Solar/Wind Harmer
8.227
274761LEE CO EC;2U
Adder
15.971
274766LEE CO EC;7U
Adder
15.783
270055AF2-134 C O1
Solar/Wind Harmer
5.134
276158O29GEN2
Solar/Wind Harmer
8.441
274877BISHOP HL;1U
Solar/Wind Harmer
5.606
958381AF2-132 GEN
Solar/Wind Harmer
15.009
964861AG1-349 GEN
Solar/Wind Harmer
12.971
971917AH1-482 GEN
Solar/Wind Harmer
14.968
24639705ELKHART HY
Adder
0.206
970091AG2-072 GEN
Adder
82.257
276772AC2-154 GEN
Solar/Wind Harmer
5.217
276806AD2-047 C O1
Solar/Wind Harmer
20.013
970941AG2-585 GEN
Solar/Wind Harmer
23.385
943121AE2-341 GEN
Solar/Wind Harmer
28.026
943591AF1-030 GEN
Solar/Wind Harmer
18.684
274800UNIV PARK;3U
Adder
10.872
972038AH1-567 GEN2
Adder
0.681
274826FISK ;BP
Adder
20.413
274724RIVER EC ;11
Adder
32.998
274676JOLIET 29;8U
Adder
55.078
274802UNIV PARK;5U
Adder
10.847
274729ELWOOD EC;1P
Adder
30.503
274730ELWOOD EC;6P
Adder
30.502
274734ELWOOD EC;8P
Adder
30.502
274736ELWOOD EC;9P
Adder
30.502
276893AG1-478 C
Solar/Wind Harmer
0.773
972231SS25-0005
Solar/Wind Harmer
17.426
972181SS23-001
Solar/Wind Harmer
10.891
274752CRETE EC ;2U
Adder
8.975
274753CRETE EC ;3U
Adder
8.975
274682WAUKEGAN ;7U
Adder
32.706
274872LEEDK;1U
Solar/Wind Harmer
0.461
276694AA1-018 GEN2
Solar/Wind Harmer
11.379
276799AD1-013 GEN
Solar/Wind Harmer
3.939
946671AF1-331 GEN
Solar/Wind Harmer
0.746
274855GSG-6 ;RU
Solar/Wind Harmer
6.574
274850MENDOTA H;RU
Solar/Wind Harmer
4.571
276602WESTBROOK C
Solar/Wind Harmer
3.784
276863AD2-134 GEN
Solar/Wind Harmer
3.179
276805AD2-038 GEN
Solar/Wind Harmer
9.117
959091AF2-200 GEN
Solar/Wind Harmer
35.289
972236AH1-702 GEN2
Adder
3.837
276889AE2-281 GEN
Solar/Wind Harmer
3.342
970571AG2-364 GEN
Solar/Wind Harmer
34.338
274858EASY ROAD;U2
Solar/Wind Harmer
8.227
274760LEE CO EC;1U
Adder
15.971
274767LEE CO EC;8U
Adder
15.783
270535AF1-215 GEN1
Solar/Wind Harmer
7.701
276157O29GEN1
Solar/Wind Harmer
6.42
274878BISHOP HL;2U
Solar/Wind Harmer
5.606
964401AG1-302 GEN
Solar/Wind Harmer
15.009
24642205MAYFLWER
Adder
1.038
247604X1-042
Adder
0.67
274805UNIV PK N;1U
Adder
9.284
274811UNIV PK N;7U
Adder
9.264
971177AH1-047 GEN
Solar/Wind Harmer
10.474
971675AH1-338 GEN
Solar/Wind Harmer
32.051
971411AH1-196 GEN
Solar/Wind Harmer
26.672
276868AE1-113 GEN
Solar/Wind Harmer
17.937
276882AE2-255 GEN
Solar/Wind Harmer
5.979
971171AH1-044 GEN
Solar/Wind Harmer
35.289
274823ROCKFORD ;21
Adder
34.211
274863CRW1-WTG
Solar/Wind Harmer
9.791
274864CRW2-WTG
Solar/Wind Harmer
9.791
971769AH1-391 GEN
Solar/Wind Harmer
17.508
276612AE2-035 GEN
Solar/Wind Harmer
4.452
971681AH1-341 GEN
Solar/Wind Harmer
25.889
926823AC1-168 GEN
Solar/Wind Harmer
7.413
970169AG2-114 GEN
Solar/Wind Harmer
17.149
961011AF2-392 GEN
Solar/Wind Harmer
18.492
270536AF1-215 GEN2
Solar/Wind Harmer
7.701
957751AF2-069 GEN
Solar/Wind Harmer
0.768
274848CAMPGROVE;RU
Solar/Wind Harmer
10.663
971771AH1-392 GEN
Solar/Wind Harmer
14.813
958391AF2-133 GEN
Solar/Wind Harmer
14.818
946321AF1-296 GEN
Solar/Wind Harmer
13.918
944201AF1-088_MTX
Adder
122.902
957141AF2-008_MTX
Adder
36.281
NYPJM->LTFIMP_NY
CLTF
2.781
LGEELTFEXP_LGEE->PJM
CLTF
3.209
WECLTFEXP_WEC->PJM
CLTF
6.661
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.363
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.037
AG2-052LTFEXP_AG2-052->PJM
LTF
0.384
AH1-155LTFEXP_AH1-155->PJM
LTF
0.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.473
CBM West 1LTFEXP_CBM-W1->PJM
CBM
182.965
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.303
MECLTFEXP_MEC->PJM
CLTF
23.384
SIGELTFEXP_SIGE->PJM
CLTF
0.346
LAGNLTFEXP_LAGN->PJM
CLTF
11.194
TVALTFEXP_TVA->PJM
CLTF
3.944

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.53 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:6077.9
MW Contribution:22.46
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
20.332
274773LINCOLN ;4U
50/50
14.178
274774LINCOLN ;5U
50/50
14.178
970245AG2-165 GEN
Solar/Wind Harmer
48.228
970333AG2-219 GEN
Solar/Wind Harmer
70.389
972207SS24-0001
Solar/Wind Harmer
47.505
276164X3-005 C
Solar/Wind Harmer
1.43
941551AE2-152 GEN
Solar/Wind Harmer
9.212
276776AD2-060 GEN
Solar/Wind Harmer
0.857
274723RIVER EC ;12
Adder
36.323
274801UNIV PARK;4U
Adder
11.79
274871GR RIDGE ;2U
Solar/Wind Harmer
15.502
274676JOLIET 29;8U
Adder
61.822
274812UNIV PK N;8U
Adder
10.08
274674JOLIET 9 ;6U
Adder
30.973
274732ELWOOD EC;7P
Adder
32.993
274745AC1-111 GEN9
Adder
11.214
274751CRETE EC ;1U
Adder
9.796
274754CRETE EC ;4U
Adder
9.796
274682WAUKEGAN ;7U
Adder
35.28
274828WAUKEGAN ;BP
Adder
21.646
970373AG2-245 GEN
Solar/Wind Harmer
41.001
960751AF2-366 GEN
Solar/Wind Harmer
5.589
962781AG1-127 GEN
Solar/Wind Harmer
18.527
276691AA1-018 GEN1
Solar/Wind Harmer
0.906
274872LEEDK;1U
Solar/Wind Harmer
15.951
939401AE1-172 GEN
Solar/Wind Harmer
26.81
274775LINCOLN ;6U
50/50
14.178
274776LINCOLN ;7U
50/50
14.178
274777LINCOLN ;8U
50/50
14.178
971347AH1-153 GEN
Solar/Wind Harmer
33.88
960681AF2-359 GEN
Solar/Wind Harmer
7.738
972227AH1-698 GEN1
Adder
5.308
960591AF2-350 GEN
Solar/Wind Harmer
20.276
274827FISK ;RP
Adder
15.695
972037AH1-567 GEN1
Adder
0.37
970833AG2-524 GEN
Solar/Wind Harmer
17.604
970833AG2-524 GEN
Solar/Wind Harmer
8.188
274675JOLIET 29;7U
Adder
61.824
274675JOLIET 29;7U
Adder
59.616
274687WILL CNTY;4U
Adder
56.284
274687WILL CNTY;4U
Adder
56.284
274814UNIV PK N;0U
Adder
10.169
274807UNIV PK N;3U
Adder
10.147
274805UNIV PK N;1U
Adder
10.102
274811UNIV PK N;7U
Adder
10.08
274731ELWOOD EC;2P
Adder
32.994
274733ELWOOD EC;3P
Adder
32.994
274735ELWOOD EC;4P
Adder
32.994
274728ELWOOD EC;5P
Adder
32.993
274746AC1-111 G10
Adder
11.214
274744AC1-111 GEN8
Adder
11.214
971769AH1-391 GEN
Solar/Wind Harmer
19.439
971177AH1-047 GEN
Solar/Wind Harmer
11.274
971675AH1-338 GEN
Solar/Wind Harmer
34.47
971411AH1-196 GEN
Solar/Wind Harmer
28.694
270536AF1-215 GEN2
Solar/Wind Harmer
8.681
276868AE1-113 GEN
Solar/Wind Harmer
19.295
276882AE2-255 GEN
Solar/Wind Harmer
6.432
971171AH1-044 GEN
Solar/Wind Harmer
37.924
274823ROCKFORD ;21
Adder
36.759
274863CRW1-WTG
Solar/Wind Harmer
10.485
274864CRW2-WTG
Solar/Wind Harmer
10.485
276612AE2-035 GEN
Solar/Wind Harmer
4.779
958391AF2-133 GEN
Solar/Wind Harmer
16.826
971681AH1-341 GEN
Solar/Wind Harmer
27.764
926823AC1-168 GEN
Solar/Wind Harmer
7.939
276901AD2-066 C O1
Solar/Wind Harmer
6.729
276861AD2-134 GEN
Solar/Wind Harmer
3.419
270055AF2-134 C O1
Solar/Wind Harmer
5.786
971997AH1-543 GEN
Solar/Wind Harmer
30.065
957471AF2-041 GEN
Solar/Wind Harmer
56.885
959081AF2-199 GEN
Solar/Wind Harmer
18.962
971067AG2-660 GEN
Solar/Wind Harmer
4.41
274822ROCKFORD ;11
Adder
37.028
972235AH1-702 GEN1
Adder
4.74
958381AF2-132 GEN
Solar/Wind Harmer
16.999
970819AG2-516 GEN
Solar/Wind Harmer
22.458
276876AE1-163_GEN2
Solar/Wind Harmer
12.561
964861AG1-349 GEN
Solar/Wind Harmer
14.698
971917AH1-482 GEN
Solar/Wind Harmer
16.961
971475AH1-234 GEN
Solar/Wind Harmer
41.76
274857EASY ROAD;U1
Solar/Wind Harmer
8.818
274761LEE CO EC;2U
Adder
17.12
274766LEE CO EC;7U
Adder
16.919
24639705ELKHART HY
Adder
0.233
970569AG2-363 GEN
Solar/Wind Harmer
30.155
274770LINCOLN ;1U
50/50
14.178
274771LINCOLN ;2U
50/50
14.178
270102X2-052 ST
50/50
3.3
270100X2-052 CT1
50/50
3.041
270101X2-052 CT2
50/50
3.041
274661LASCO STA;2U
50/50
14.825
972259AH1-714 GEN
50/50
41.61
274660LASCO STA;1U
50/50
15.014
970321AG2-212 GEN
Solar/Wind Harmer
48.228
970239AG2-162 GEN
Solar/Wind Harmer
24.53
965681AG1-436 GEN
Solar/Wind Harmer
25.603
965791AG1-447 GEN
Solar/Wind Harmer
13.099
274888KELLY CRK;1U
Solar/Wind Harmer
11.971
274887GEN-1.85
Solar/Wind Harmer
10.808
276843GEN-1.7
Solar/Wind Harmer
1.163
958011AF2-095 GEN
Solar/Wind Harmer
29.198
274803UNIV PARK;6U
Adder
11.772
274847GR RIDGE ;BU
Solar/Wind Harmer
10.197
274808UNIV PK N;4U
Adder
10.036
274674JOLIET 9 ;6U
Adder
30.973
971573AH1-285 GEN
Solar/Wind Harmer
17.201
274695ROCKY RD ;2P
Adder
21.954
274693ROCKY RD ;1P
Adder
21.738
274697ROCKY RD ;3P
Adder
5.964
274696ROCKY RD ;4P
Adder
22.471
274683WAUKEGAN ;8U
Adder
41.295
274683WAUKEGAN ;8U
Adder
34.809
962691AG1-118 GEN
Solar/Wind Harmer
58.651
970921AG2-575 GEN
Solar/Wind Harmer
19.482
970921AG2-575 GEN
Solar/Wind Harmer
4.531
958481AF2-142 GEN
Solar/Wind Harmer
29.185
24441505OLIV SLR
Solar/Wind Harmer
0.26
274861TOP CROP ;1U
Solar/Wind Harmer
11.777
274862TOP CROP ;2U
Solar/Wind Harmer
9.834
942991AE2-321 GEN
Solar/Wind Harmer
19.249
270526AF1-158 GEN
Solar/Wind Harmer
8.736
958491AF2-143 GEN
Solar/Wind Harmer
28.71
971333AH1-146 GEN
Solar/Wind Harmer
38.235
971335AH1-147 GEN
Solar/Wind Harmer
38.235
274879MINONK ;1U
Solar/Wind Harmer
12.865
971341AH1-150 GEN
Solar/Wind Harmer
37.924
971343AH1-151 GEN
Solar/Wind Harmer
37.924
276872AE1-163_GEN1
Solar/Wind Harmer
12.561
274856ECOGROVE ;U1
Solar/Wind Harmer
6.299
276611AD2-172 GEN
Solar/Wind Harmer
4.779
938861AE1-114 GEN
Solar/Wind Harmer
15.166
274764LEE CO EC;5U
Adder
17.161
274765LEE CO EC;6U
Adder
17.161
274762LEE CO EC;3U
Adder
17.12
274763LEE CO EC;4U
Adder
16.959
972267AH1-718 GEN
Adder
7.553
247620Y3-023
Adder
0.638
274772LINCOLN ;3U
50/50
14.178
970513AG2-328 GEN
Solar/Wind Harmer
48.228
970517AG2-330 GEN
Solar/Wind Harmer
43.742
970349AG2-230 GEN
Solar/Wind Harmer
33.88
970243AG2-164 GEN
Solar/Wind Harmer
57.591
970519AG2-331 GEN
Solar/Wind Harmer
38.692
970699AG2-449 GEN
Solar/Wind Harmer
25.596
970707AG2-453 GEN
Solar/Wind Harmer
58.387
972228AH1-698 GEN2
Adder
7.538
276897AD1-100 C
Solar/Wind Harmer
58.944
939351AE1-166 GEN
Solar/Wind Harmer
12.044
274724RIVER EC ;11
Adder
35.931
276772AC2-154 GEN
Solar/Wind Harmer
5.654
276806AD2-047 C O1
Solar/Wind Harmer
21.691
970941AG2-585 GEN
Solar/Wind Harmer
25.345
274826FISK ;BP
Adder
22.146
274800UNIV PARK;3U
Adder
11.79
972038AH1-567 GEN2
Adder
0.738
274802UNIV PARK;5U
Adder
11.772
943121AE2-341 GEN
Solar/Wind Harmer
30.257
943591AF1-030 GEN
Solar/Wind Harmer
20.172
274676JOLIET 29;8U
Adder
59.614
274729ELWOOD EC;1P
Adder
32.994
274730ELWOOD EC;6P
Adder
32.993
274734ELWOOD EC;8P
Adder
32.993
274736ELWOOD EC;9P
Adder
32.993
972231SS25-0005
Solar/Wind Harmer
19.019
972181SS23-001
Solar/Wind Harmer
11.887
274752CRETE EC ;2U
Adder
9.796
274753CRETE EC ;3U
Adder
9.796
276893AG1-478 C
Solar/Wind Harmer
0.837
274682WAUKEGAN ;7U
Adder
35.28
276694AA1-018 GEN2
Solar/Wind Harmer
12.278
274872LEEDK;1U
Solar/Wind Harmer
0.497
276799AD1-013 GEN
Solar/Wind Harmer
4.236
946671AF1-331 GEN
Solar/Wind Harmer
0.802
276805AD2-038 GEN
Solar/Wind Harmer
9.819
274855GSG-6 ;RU
Solar/Wind Harmer
7.07
274850MENDOTA H;RU
Solar/Wind Harmer
4.916
276602WESTBROOK C
Solar/Wind Harmer
4.069
276863AD2-134 GEN
Solar/Wind Harmer
3.419
270535AF1-215 GEN1
Solar/Wind Harmer
8.681
959091AF2-200 GEN
Solar/Wind Harmer
37.924
972236AH1-702 GEN2
Adder
4.121
964401AG1-302 GEN
Solar/Wind Harmer
16.999
276889AE2-281 GEN
Solar/Wind Harmer
3.589
959141AF2-205 GEN
Solar/Wind Harmer
11.128
274858EASY ROAD;U2
Solar/Wind Harmer
8.818
274760LEE CO EC;1U
Adder
17.12
274767LEE CO EC;8U
Adder
16.919
24642205MAYFLWER
Adder
1.158
247604X1-042
Adder
0.747
970571AG2-364 GEN
Solar/Wind Harmer
20.103
944201AF1-088_MTX
Adder
102.056
957141AF2-008_MTX
Adder
51.028
NYPJM->LTFIMP_NY
CLTF
2.808
LGEELTFEXP_LGEE->PJM
CLTF
1.84
WECLTFEXP_WEC->PJM
CLTF
7.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.762
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
AG2-052LTFEXP_AG2-052->PJM
LTF
0.419
AH1-155LTFEXP_AH1-155->PJM
LTF
0.629
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.604
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.533
MECLTFEXP_MEC->PJM
CLTF
24.55
SIGELTFEXP_SIGE->PJM
CLTF
0.29
LAGNLTFEXP_LAGN->PJM
CLTF
10.673
TVALTFEXP_TVA->PJM
CLTF
3.482

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.42 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:6022.03
MW Contribution:20.96
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
13.113
274776LINCOLN ;7U
50/50
13.113
274777LINCOLN ;8U
50/50
13.113
971347AH1-153 GEN
Solar/Wind Harmer
30.827
972227AH1-698 GEN1
Adder
4.91
960591AF2-350 GEN
Solar/Wind Harmer
18.745
970833AG2-524 GEN
Solar/Wind Harmer
16.327
970833AG2-524 GEN
Solar/Wind Harmer
7.594
274827FISK ;RP
Adder
14.495
274675JOLIET 29;7U
Adder
57.233
274675JOLIET 29;7U
Adder
55.189
972037AH1-567 GEN1
Adder
0.341
274687WILL CNTY;4U
Adder
52.082
274687WILL CNTY;4U
Adder
52.082
274746AC1-111 G10
Adder
10.407
274744AC1-111 GEN8
Adder
10.407
274731ELWOOD EC;2P
Adder
30.563
274733ELWOOD EC;3P
Adder
30.563
274735ELWOOD EC;4P
Adder
30.563
274728ELWOOD EC;5P
Adder
30.562
960681AF2-359 GEN
Solar/Wind Harmer
7.009
274814UNIV PK N;0U
Adder
9.363
274807UNIV PK N;3U
Adder
9.343
274805UNIV PK N;1U
Adder
9.302
274811UNIV PK N;7U
Adder
9.282
971177AH1-047 GEN
Solar/Wind Harmer
10.496
971675AH1-338 GEN
Solar/Wind Harmer
32.118
971411AH1-196 GEN
Solar/Wind Harmer
26.727
276868AE1-113 GEN
Solar/Wind Harmer
17.974
276882AE2-255 GEN
Solar/Wind Harmer
5.992
971171AH1-044 GEN
Solar/Wind Harmer
35.362
274823ROCKFORD ;21
Adder
34.283
274863CRW1-WTG
Solar/Wind Harmer
9.812
274864CRW2-WTG
Solar/Wind Harmer
9.812
971769AH1-391 GEN
Solar/Wind Harmer
17.545
276612AE2-035 GEN
Solar/Wind Harmer
4.462
971681AH1-341 GEN
Solar/Wind Harmer
25.944
926823AC1-168 GEN
Solar/Wind Harmer
7.429
970169AG2-114 GEN
Solar/Wind Harmer
17.186
961011AF2-392 GEN
Solar/Wind Harmer
18.532
270536AF1-215 GEN2
Solar/Wind Harmer
7.718
957751AF2-069 GEN
Solar/Wind Harmer
0.769
274848CAMPGROVE;RU
Solar/Wind Harmer
10.687
971771AH1-392 GEN
Solar/Wind Harmer
14.846
958391AF2-133 GEN
Solar/Wind Harmer
14.852
946321AF1-296 GEN
Solar/Wind Harmer
13.949
274770LINCOLN ;1U
50/50
13.113
274771LINCOLN ;2U
50/50
13.113
274661LASCO STA;2U
50/50
13.726
972259AH1-714 GEN
50/50
38.528
274660LASCO STA;1U
50/50
13.902
970321AG2-212 GEN
Solar/Wind Harmer
42.744
274888KELLY CRK;1U
Solar/Wind Harmer
11.067
274887GEN-1.85
Solar/Wind Harmer
9.991
276843GEN-1.7
Solar/Wind Harmer
1.075
958011AF2-095 GEN
Solar/Wind Harmer
26.992
274847GR RIDGE ;BU
Solar/Wind Harmer
9.458
274803UNIV PARK;6U
Adder
10.868
274674JOLIET 9 ;6U
Adder
28.688
971573AH1-285 GEN
Solar/Wind Harmer
15.973
965681AG1-436 GEN
Solar/Wind Harmer
23.191
965791AG1-447 GEN
Solar/Wind Harmer
11.865
274808UNIV PK N;4U
Adder
9.241
274695ROCKY RD ;2P
Adder
20.397
274693ROCKY RD ;1P
Adder
20.196
274697ROCKY RD ;3P
Adder
5.541
274696ROCKY RD ;4P
Adder
20.877
274683WAUKEGAN ;8U
Adder
38.365
274683WAUKEGAN ;8U
Adder
32.34
962691AG1-118 GEN
Solar/Wind Harmer
54.552
970921AG2-575 GEN
Solar/Wind Harmer
18.126
970921AG2-575 GEN
Solar/Wind Harmer
4.215
958481AF2-142 GEN
Solar/Wind Harmer
27.102
274861TOP CROP ;1U
Solar/Wind Harmer
10.937
274862TOP CROP ;2U
Solar/Wind Harmer
9.133
942991AE2-321 GEN
Solar/Wind Harmer
17.92
971333AH1-146 GEN
Solar/Wind Harmer
35.62
971335AH1-147 GEN
Solar/Wind Harmer
35.62
958491AF2-143 GEN
Solar/Wind Harmer
26.715
274879MINONK ;1U
Solar/Wind Harmer
11.984
971341AH1-150 GEN
Solar/Wind Harmer
35.362
971343AH1-151 GEN
Solar/Wind Harmer
35.362
24441505OLIV SLR
Solar/Wind Harmer
0.235
276872AE1-163_GEN1
Solar/Wind Harmer
11.722
274856ECOGROVE ;U1
Solar/Wind Harmer
5.88
276611AD2-172 GEN
Solar/Wind Harmer
4.462
270526AF1-158 GEN
Solar/Wind Harmer
7.878
938861AE1-114 GEN
Solar/Wind Harmer
14.172
274764LEE CO EC;5U
Adder
16.043
274765LEE CO EC;6U
Adder
16.043
274762LEE CO EC;3U
Adder
16.006
274763LEE CO EC;4U
Adder
15.855
276603SUBLETTE C
Solar/Wind Harmer
1.801
972267AH1-718 GEN
Adder
7.071
276741O09 GEN1
Solar/Wind Harmer
6.042
276708O09 GEN2
Solar/Wind Harmer
6.042
274851PROVIDENC;RU
Solar/Wind Harmer
4.771
274849CRESCENT ;1U
Solar/Wind Harmer
3.098
276645AC1-214 GEN1
Solar/Wind Harmer
2.244
276646AC1-214 GEN2
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
6.639
247620Y3-023
Adder
0.558
24344105CKG2
50/50
18.673
274773LINCOLN ;4U
50/50
13.113
274774LINCOLN ;5U
50/50
13.113
970245AG2-165 GEN
Solar/Wind Harmer
42.744
972207SS24-0001
Solar/Wind Harmer
43.938
941551AE2-152 GEN
Solar/Wind Harmer
8.538
276164X3-005 C
Solar/Wind Harmer
1.318
276776AD2-060 GEN
Solar/Wind Harmer
0.793
274871GR RIDGE ;2U
Solar/Wind Harmer
14.379
274801UNIV PARK;4U
Adder
10.893
274676JOLIET 29;8U
Adder
57.231
274723RIVER EC ;12
Adder
33.419
274674JOLIET 9 ;6U
Adder
28.688
274745AC1-111 GEN9
Adder
10.407
274732ELWOOD EC;7P
Adder
30.562
274812UNIV PK N;8U
Adder
9.282
274751CRETE EC ;1U
Adder
8.993
274754CRETE EC ;4U
Adder
8.993
274682WAUKEGAN ;7U
Adder
32.772
274828WAUKEGAN ;BP
Adder
20.11
960751AF2-366 GEN
Solar/Wind Harmer
5.2
962781AG1-127 GEN
Solar/Wind Harmer
17.237
274872LEEDK;1U
Solar/Wind Harmer
14.845
276691AA1-018 GEN1
Solar/Wind Harmer
0.841
939401AE1-172 GEN
Solar/Wind Harmer
25.019
276901AD2-066 C O1
Solar/Wind Harmer
6.267
276861AD2-134 GEN
Solar/Wind Harmer
3.186
971997AH1-543 GEN
Solar/Wind Harmer
28.038
957471AF2-041 GEN
Solar/Wind Harmer
53.043
959081AF2-199 GEN
Solar/Wind Harmer
17.681
971067AG2-660 GEN
Solar/Wind Harmer
4.112
274822ROCKFORD ;11
Adder
34.533
972235AH1-702 GEN1
Adder
4.422
970819AG2-516 GEN
Solar/Wind Harmer
20.96
276876AE1-163_GEN2
Solar/Wind Harmer
11.722
970373AG2-245 GEN
Solar/Wind Harmer
36.646
971475AH1-234 GEN
Solar/Wind Harmer
38.984
970569AG2-363 GEN
Solar/Wind Harmer
51.618
274857EASY ROAD;U1
Solar/Wind Harmer
8.244
274761LEE CO EC;2U
Adder
16.006
274766LEE CO EC;7U
Adder
15.817
270055AF2-134 C O1
Solar/Wind Harmer
5.145
276158O29GEN2
Solar/Wind Harmer
8.459
274877BISHOP HL;1U
Solar/Wind Harmer
5.618
958381AF2-132 GEN
Solar/Wind Harmer
15.042
964861AG1-349 GEN
Solar/Wind Harmer
13
971917AH1-482 GEN
Solar/Wind Harmer
15.002
24639705ELKHART HY
Adder
0.206
970091AG2-072 GEN
Adder
82.54
274772LINCOLN ;3U
50/50
13.113
970513AG2-328 GEN
Solar/Wind Harmer
42.744
970517AG2-330 GEN
Solar/Wind Harmer
38.768
970349AG2-230 GEN
Solar/Wind Harmer
30.827
970707AG2-453 GEN
Solar/Wind Harmer
54.087
972228AH1-698 GEN2
Adder
6.973
276897AD1-100 C
Solar/Wind Harmer
54.631
939351AE1-166 GEN
Solar/Wind Harmer
11.163
276772AC2-154 GEN
Solar/Wind Harmer
5.227
276806AD2-047 C O1
Solar/Wind Harmer
20.052
970941AG2-585 GEN
Solar/Wind Harmer
23.431
943121AE2-341 GEN
Solar/Wind Harmer
28.081
943591AF1-030 GEN
Solar/Wind Harmer
18.721
274800UNIV PARK;3U
Adder
10.893
972038AH1-567 GEN2
Adder
0.682
274826FISK ;BP
Adder
20.453
274724RIVER EC ;11
Adder
33.063
274676JOLIET 29;8U
Adder
55.187
274802UNIV PARK;5U
Adder
10.868
274729ELWOOD EC;1P
Adder
30.563
274730ELWOOD EC;6P
Adder
30.562
274734ELWOOD EC;8P
Adder
30.562
274736ELWOOD EC;9P
Adder
30.562
276893AG1-478 C
Solar/Wind Harmer
0.775
972231SS25-0005
Solar/Wind Harmer
17.461
972181SS23-001
Solar/Wind Harmer
10.913
274752CRETE EC ;2U
Adder
8.993
274753CRETE EC ;3U
Adder
8.993
274682WAUKEGAN ;7U
Adder
32.772
274872LEEDK;1U
Solar/Wind Harmer
0.462
276694AA1-018 GEN2
Solar/Wind Harmer
11.402
276799AD1-013 GEN
Solar/Wind Harmer
3.947
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274855GSG-6 ;RU
Solar/Wind Harmer
6.588
274850MENDOTA H;RU
Solar/Wind Harmer
4.581
276602WESTBROOK C
Solar/Wind Harmer
3.792
276863AD2-134 GEN
Solar/Wind Harmer
3.186
276805AD2-038 GEN
Solar/Wind Harmer
9.136
959091AF2-200 GEN
Solar/Wind Harmer
35.362
972236AH1-702 GEN2
Adder
3.845
276889AE2-281 GEN
Solar/Wind Harmer
3.349
970571AG2-364 GEN
Solar/Wind Harmer
34.412
274858EASY ROAD;U2
Solar/Wind Harmer
8.244
274760LEE CO EC;1U
Adder
16.006
274767LEE CO EC;8U
Adder
15.817
270535AF1-215 GEN1
Solar/Wind Harmer
7.718
276157O29GEN1
Solar/Wind Harmer
6.434
274878BISHOP HL;2U
Solar/Wind Harmer
5.618
964401AG1-302 GEN
Solar/Wind Harmer
15.042
24642205MAYFLWER
Adder
1.04
247604X1-042
Adder
0.671
944201AF1-088_MTX
Adder
123.331
957141AF2-008_MTX
Adder
36.408
NYPJM->LTFIMP_NY
CLTF
2.757
LGEELTFEXP_LGEE->PJM
CLTF
3.235
WECLTFEXP_WEC->PJM
CLTF
6.675
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.862
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.012
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.577
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.444
MECLTFEXP_MEC->PJM
CLTF
23.446
SIGELTFEXP_SIGE->PJM
CLTF
0.348
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
TVALTFEXP_TVA->PJM
CLTF
3.981

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11046___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:114.89 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5745.77
MW Contribution:20.57
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
18.73
274773LINCOLN ;4U
50/50
13.001
274774LINCOLN ;5U
50/50
13.001
970245AG2-165 GEN
Solar/Wind Harmer
41.418
972207SS24-0001
Solar/Wind Harmer
43.561
276164X3-005 C
Solar/Wind Harmer
1.314
274723RIVER EC ;12
Adder
33.414
941551AE2-152 GEN
Solar/Wind Harmer
8.44
276776AD2-060 GEN
Solar/Wind Harmer
0.786
274801UNIV PARK;4U
Adder
10.821
274676JOLIET 29;8U
Adder
56.696
274812UNIV PK N;8U
Adder
9.252
274871GR RIDGE ;2U
Solar/Wind Harmer
14.204
274674JOLIET 9 ;6U
Adder
28.4
274732ELWOOD EC;7P
Adder
30.247
274751CRETE EC ;1U
Adder
8.994
274754CRETE EC ;4U
Adder
8.994
274745AC1-111 GEN9
Adder
10.278
274682WAUKEGAN ;7U
Adder
32.339
274828WAUKEGAN ;BP
Adder
19.841
960751AF2-366 GEN
Solar/Wind Harmer
5.122
962781AG1-127 GEN
Solar/Wind Harmer
16.977
276691AA1-018 GEN1
Solar/Wind Harmer
0.83
274872LEEDK;1U
Solar/Wind Harmer
14.615
939401AE1-172 GEN
Solar/Wind Harmer
24.491
276861AD2-134 GEN
Solar/Wind Harmer
3.132
276901AD2-066 C O1
Solar/Wind Harmer
6.158
971997AH1-543 GEN
Solar/Wind Harmer
27.509
970373AG2-245 GEN
Solar/Wind Harmer
36.682
957471AF2-041 GEN
Solar/Wind Harmer
52.109
959081AF2-199 GEN
Solar/Wind Harmer
17.37
971067AG2-660 GEN
Solar/Wind Harmer
4.039
274822ROCKFORD ;11
Adder
33.922
274770LINCOLN ;1U
50/50
13.001
274771LINCOLN ;2U
50/50
13.001
270102X2-052 ST
50/50
3.099
270100X2-052 CT1
50/50
2.855
270101X2-052 CT2
50/50
2.855
274661LASCO STA;2U
50/50
13.59
972259AH1-714 GEN
50/50
38.145
274660LASCO STA;1U
50/50
13.764
970321AG2-212 GEN
Solar/Wind Harmer
41.418
965681AG1-436 GEN
Solar/Wind Harmer
23.931
965791AG1-447 GEN
Solar/Wind Harmer
12.244
274888KELLY CRK;1U
Solar/Wind Harmer
10.983
274887GEN-1.85
Solar/Wind Harmer
9.915
276843GEN-1.7
Solar/Wind Harmer
1.067
274772LINCOLN ;3U
50/50
13.001
24344005CKG1
50/50
12.388
970513AG2-328 GEN
Solar/Wind Harmer
41.418
970517AG2-330 GEN
Solar/Wind Harmer
37.565
970349AG2-230 GEN
Solar/Wind Harmer
33.189
970707AG2-453 GEN
Solar/Wind Harmer
53.523
274724RIVER EC ;11
Adder
33.067
972228AH1-698 GEN2
Adder
6.911
276897AD1-100 C
Solar/Wind Harmer
54.005
939351AE1-166 GEN
Solar/Wind Harmer
11.035
276772AC2-154 GEN
Solar/Wind Harmer
5.188
276806AD2-047 C O1
Solar/Wind Harmer
19.9
970941AG2-585 GEN
Solar/Wind Harmer
23.253
274826FISK ;BP
Adder
20.33
274800UNIV PARK;3U
Adder
10.821
972038AH1-567 GEN2
Adder
0.677
274802UNIV PARK;5U
Adder
10.803
943121AE2-341 GEN
Solar/Wind Harmer
27.733
943591AF1-030 GEN
Solar/Wind Harmer
18.488
274676JOLIET 29;8U
Adder
54.671
274729ELWOOD EC;1P
Adder
30.248
274730ELWOOD EC;6P
Adder
30.247
274734ELWOOD EC;8P
Adder
30.247
274736ELWOOD EC;9P
Adder
30.247
972231SS25-0005
Solar/Wind Harmer
17.464
972181SS23-001
Solar/Wind Harmer
10.915
274752CRETE EC ;2U
Adder
8.994
274753CRETE EC ;3U
Adder
8.994
276893AG1-478 C
Solar/Wind Harmer
0.767
274682WAUKEGAN ;7U
Adder
32.339
276694AA1-018 GEN2
Solar/Wind Harmer
11.251
274872LEEDK;1U
Solar/Wind Harmer
0.455
276799AD1-013 GEN
Solar/Wind Harmer
3.881
946671AF1-331 GEN
Solar/Wind Harmer
0.735
274855GSG-6 ;RU
Solar/Wind Harmer
6.477
274850MENDOTA H;RU
Solar/Wind Harmer
4.503
276602WESTBROOK C
Solar/Wind Harmer
3.728
276863AD2-134 GEN
Solar/Wind Harmer
3.132
276805AD2-038 GEN
Solar/Wind Harmer
8.992
959091AF2-200 GEN
Solar/Wind Harmer
34.74
972236AH1-702 GEN2
Adder
3.775
24642205MAYFLWER
Adder
1.093
276889AE2-281 GEN
Solar/Wind Harmer
3.284
274858EASY ROAD;U2
Solar/Wind Harmer
8.076
274760LEE CO EC;1U
Adder
15.678
274767LEE CO EC;8U
Adder
15.494
970571AG2-364 GEN
Solar/Wind Harmer
33.656
270535AF1-215 GEN1
Solar/Wind Harmer
7.607
247604X1-042
Adder
0.696
24441205WTRV SLR C
Solar/Wind Harmer
0.225
276157O29GEN1
Solar/Wind Harmer
6.283
274878BISHOP HL;2U
Solar/Wind Harmer
5.463
274775LINCOLN ;6U
50/50
13.001
274776LINCOLN ;7U
50/50
13.001
274777LINCOLN ;8U
50/50
13.001
971347AH1-153 GEN
Solar/Wind Harmer
33.189
960681AF2-359 GEN
Solar/Wind Harmer
7.233
972227AH1-698 GEN1
Adder
4.866
960591AF2-350 GEN
Solar/Wind Harmer
18.602
274827FISK ;RP
Adder
14.408
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.698
274675JOLIET 29;7U
Adder
54.673
970833AG2-524 GEN
Solar/Wind Harmer
16.131
970833AG2-524 GEN
Solar/Wind Harmer
7.503
274687WILL CNTY;4U
Adder
51.628
274687WILL CNTY;4U
Adder
51.628
274814UNIV PK N;0U
Adder
9.333
274807UNIV PK N;3U
Adder
9.312
274805UNIV PK N;1U
Adder
9.272
274811UNIV PK N;7U
Adder
9.252
274731ELWOOD EC;2P
Adder
30.248
274733ELWOOD EC;3P
Adder
30.248
274735ELWOOD EC;4P
Adder
30.248
274728ELWOOD EC;5P
Adder
30.247
274746AC1-111 G10
Adder
10.278
274744AC1-111 GEN8
Adder
10.278
971769AH1-391 GEN
Solar/Wind Harmer
18.249
971177AH1-047 GEN
Solar/Wind Harmer
10.33
971675AH1-338 GEN
Solar/Wind Harmer
31.578
971411AH1-196 GEN
Solar/Wind Harmer
26.291
971771AH1-392 GEN
Solar/Wind Harmer
15.753
958011AF2-095 GEN
Solar/Wind Harmer
26.787
274803UNIV PARK;6U
Adder
10.803
274808UNIV PK N;4U
Adder
9.211
274847GR RIDGE ;BU
Solar/Wind Harmer
9.343
274674JOLIET 9 ;6U
Adder
28.4
971573AH1-285 GEN
Solar/Wind Harmer
15.764
24441505OLIV SLR
Solar/Wind Harmer
0.244
270526AF1-158 GEN
Solar/Wind Harmer
8.225
274695ROCKY RD ;2P
Adder
20.121
274693ROCKY RD ;1P
Adder
19.923
274697ROCKY RD ;3P
Adder
5.466
274696ROCKY RD ;4P
Adder
20.595
274683WAUKEGAN ;8U
Adder
37.851
274683WAUKEGAN ;8U
Adder
31.907
962691AG1-118 GEN
Solar/Wind Harmer
53.744
970921AG2-575 GEN
Solar/Wind Harmer
17.851
970921AG2-575 GEN
Solar/Wind Harmer
4.151
958481AF2-142 GEN
Solar/Wind Harmer
26.742
274861TOP CROP ;1U
Solar/Wind Harmer
10.791
274862TOP CROP ;2U
Solar/Wind Harmer
9.011
942991AE2-321 GEN
Solar/Wind Harmer
17.638
958491AF2-143 GEN
Solar/Wind Harmer
26.292
971333AH1-146 GEN
Solar/Wind Harmer
35.031
971335AH1-147 GEN
Solar/Wind Harmer
35.031
274879MINONK ;1U
Solar/Wind Harmer
11.778
971341AH1-150 GEN
Solar/Wind Harmer
34.74
971343AH1-151 GEN
Solar/Wind Harmer
34.74
276872AE1-163_GEN1
Solar/Wind Harmer
11.495
274856ECOGROVE ;U1
Solar/Wind Harmer
5.769
276611AD2-172 GEN
Solar/Wind Harmer
4.378
938861AE1-114 GEN
Solar/Wind Harmer
13.889
274764LEE CO EC;5U
Adder
15.715
274765LEE CO EC;6U
Adder
15.715
274762LEE CO EC;3U
Adder
15.678
274763LEE CO EC;4U
Adder
15.531
276603SUBLETTE C
Solar/Wind Harmer
1.764
957891AF2-083 GEN
Solar/Wind Harmer
5.61
972267AH1-718 GEN
Adder
6.915
960981AF2-389 GEN
Solar/Wind Harmer
2.508
276741O09 GEN1
Solar/Wind Harmer
5.9
276708O09 GEN2
Solar/Wind Harmer
5.9
961051AF2-396 GEN
Solar/Wind Harmer
25.906
961051AF2-396 GEN
Solar/Wind Harmer
12.049
274851PROVIDENC;RU
Solar/Wind Harmer
4.642
274849CRESCENT ;1U
Solar/Wind Harmer
3.014
276645AC1-214 GEN1
Solar/Wind Harmer
2.183
276646AC1-214 GEN2
Solar/Wind Harmer
2.183
276782AC1-033 GEN
Solar/Wind Harmer
6.456
247620Y3-023
Adder
0.559
270471AD2-092_GEN
Solar/Wind Helper
1.321
972235AH1-702 GEN1
Adder
4.342
970819AG2-516 GEN
Solar/Wind Harmer
20.573
276876AE1-163_GEN2
Solar/Wind Harmer
11.495
971475AH1-234 GEN
Solar/Wind Harmer
38.256
270505AE1-170 C O1
Solar/Wind Harmer
25.403
274857EASY ROAD;U1
Solar/Wind Harmer
8.076
274761LEE CO EC;2U
Adder
15.678
274766LEE CO EC;7U
Adder
15.494
970569AG2-363 GEN
Solar/Wind Harmer
50.484
270055AF2-134 C O1
Solar/Wind Harmer
5.07
270449AD2-020 GEN
Solar/Wind Harmer
4.651
943021AE2-325 GEN
Solar/Wind Harmer
6.043
276158O29GEN2
Solar/Wind Harmer
8.26
274877BISHOP HL;1U
Solar/Wind Harmer
5.463
24639705ELKHART HY
Adder
0.212
270349AD2-093_GEN
Solar/Wind Helper
1.321
958381AF2-132 GEN
Solar/Wind Harmer
11.606
276868AE1-113 GEN
Solar/Wind Harmer
17.665
276882AE2-255 GEN
Solar/Wind Harmer
5.889
971171AH1-044 GEN
Solar/Wind Harmer
34.74
274823ROCKFORD ;21
Adder
33.676
274863CRW1-WTG
Solar/Wind Harmer
9.567
274864CRW2-WTG
Solar/Wind Harmer
9.567
276612AE2-035 GEN
Solar/Wind Harmer
4.378
971681AH1-341 GEN
Solar/Wind Harmer
25.426
926823AC1-168 GEN
Solar/Wind Harmer
7.256
270536AF1-215 GEN2
Solar/Wind Harmer
7.607
970169AG2-114 GEN
Solar/Wind Harmer
16.689
961011AF2-392 GEN
Solar/Wind Harmer
18.128
944161AF1-084 GEN
Solar/Wind Harmer
3.666
957751AF2-069 GEN
Solar/Wind Harmer
0.748
NYPJM->LTFIMP_NY
CLTF
2.596
LGEELTFEXP_LGEE->PJM
CLTF
1.837
WECLTFEXP_WEC->PJM
CLTF
6.558
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.728
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.803
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.571
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.339
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.424
MECLTFEXP_MEC->PJM
CLTF
22.474
SIGELTFEXP_SIGE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
10.173
TVALTFEXP_TVA->PJM
CLTF
3.448

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#17234_05GRNTWN 765_N_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.26 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5664.12
MW Contribution:21.78
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
20.096
274773LINCOLN ;4U
50/50
13.854
274774LINCOLN ;5U
50/50
13.854
970245AG2-165 GEN
Solar/Wind Harmer
47.9
972207SS24-0001
Solar/Wind Harmer
46.418
276164X3-005 C
Solar/Wind Harmer
1.394
941551AE2-152 GEN
Solar/Wind Harmer
8.97
274723RIVER EC ;12
Adder
35.43
276776AD2-060 GEN
Solar/Wind Harmer
0.835
274801UNIV PARK;4U
Adder
11.489
274871GR RIDGE ;2U
Solar/Wind Harmer
15.092
274676JOLIET 29;8U
Adder
60.218
274812UNIV PK N;8U
Adder
9.827
274674JOLIET 9 ;6U
Adder
30.161
274775LINCOLN ;6U
50/50
13.854
274776LINCOLN ;7U
50/50
13.854
274777LINCOLN ;8U
50/50
13.854
971347AH1-153 GEN
Solar/Wind Harmer
33.33
960681AF2-359 GEN
Solar/Wind Harmer
7.579
972227AH1-698 GEN1
Adder
5.172
960591AF2-350 GEN
Solar/Wind Harmer
19.757
274827FISK ;RP
Adder
15.297
972037AH1-567 GEN1
Adder
0.36
970833AG2-524 GEN
Solar/Wind Harmer
17.138
970833AG2-524 GEN
Solar/Wind Harmer
7.971
274675JOLIET 29;7U
Adder
60.219
274675JOLIET 29;7U
Adder
58.069
274814UNIV PK N;0U
Adder
9.913
274807UNIV PK N;3U
Adder
9.892
274805UNIV PK N;1U
Adder
9.849
274811UNIV PK N;7U
Adder
9.827
274687WILL CNTY;4U
Adder
54.826
274687WILL CNTY;4U
Adder
54.826
274731ELWOOD EC;2P
Adder
32.123
274733ELWOOD EC;3P
Adder
32.123
274735ELWOOD EC;4P
Adder
32.123
274728ELWOOD EC;5P
Adder
32.123
274746AC1-111 G10
Adder
10.918
274744AC1-111 GEN8
Adder
10.918
971769AH1-391 GEN
Solar/Wind Harmer
19.021
971177AH1-047 GEN
Solar/Wind Harmer
10.952
270536AF1-215 GEN2
Solar/Wind Harmer
8.469
971675AH1-338 GEN
Solar/Wind Harmer
33.472
971411AH1-196 GEN
Solar/Wind Harmer
27.866
276868AE1-113 GEN
Solar/Wind Harmer
18.718
276882AE2-255 GEN
Solar/Wind Harmer
6.24
971171AH1-044 GEN
Solar/Wind Harmer
36.805
274823ROCKFORD ;21
Adder
35.67
274863CRW1-WTG
Solar/Wind Harmer
10.138
274864CRW2-WTG
Solar/Wind Harmer
10.138
276612AE2-035 GEN
Solar/Wind Harmer
4.635
958391AF2-133 GEN
Solar/Wind Harmer
16.387
274732ELWOOD EC;7P
Adder
32.123
274751CRETE EC ;1U
Adder
9.553
274754CRETE EC ;4U
Adder
9.553
274745AC1-111 GEN9
Adder
10.918
274682WAUKEGAN ;7U
Adder
34.314
970373AG2-245 GEN
Solar/Wind Harmer
40.058
274828WAUKEGAN ;BP
Adder
21.051
960751AF2-366 GEN
Solar/Wind Harmer
5.433
962781AG1-127 GEN
Solar/Wind Harmer
18.009
276691AA1-018 GEN1
Solar/Wind Harmer
0.88
274872LEEDK;1U
Solar/Wind Harmer
15.501
939401AE1-172 GEN
Solar/Wind Harmer
25.979
270055AF2-134 C O1
Solar/Wind Harmer
5.646
276861AD2-134 GEN
Solar/Wind Harmer
3.32
276901AD2-066 C O1
Solar/Wind Harmer
6.528
971997AH1-543 GEN
Solar/Wind Harmer
29.157
957471AF2-041 GEN
Solar/Wind Harmer
55.208
959081AF2-199 GEN
Solar/Wind Harmer
18.403
971067AG2-660 GEN
Solar/Wind Harmer
4.28
274822ROCKFORD ;11
Adder
35.93
958381AF2-132 GEN
Solar/Wind Harmer
16.565
972235AH1-702 GEN1
Adder
4.598
964861AG1-349 GEN
Solar/Wind Harmer
14.321
971917AH1-482 GEN
Solar/Wind Harmer
16.527
970819AG2-516 GEN
Solar/Wind Harmer
21.782
276876AE1-163_GEN2
Solar/Wind Harmer
12.169
971475AH1-234 GEN
Solar/Wind Harmer
40.498
274857EASY ROAD;U1
Solar/Wind Harmer
8.544
274761LEE CO EC;2U
Adder
16.587
274766LEE CO EC;7U
Adder
16.391
970569AG2-363 GEN
Solar/Wind Harmer
53.405
940581AE2-045 GEN
Solar/Wind Harmer
18.087
971605AH1-302 GEN
Solar/Wind Harmer
15.466
270505AE1-170 C O1
Solar/Wind Harmer
26.304
276158O29GEN2
Solar/Wind Harmer
8.731
24639705ELKHART HY
Adder
0.227
274770LINCOLN ;1U
50/50
13.854
274771LINCOLN ;2U
50/50
13.854
270102X2-052 ST
50/50
3.235
270100X2-052 CT1
50/50
2.981
270101X2-052 CT2
50/50
2.981
274661LASCO STA;2U
50/50
14.451
972259AH1-714 GEN
50/50
40.562
274660LASCO STA;1U
50/50
14.636
970321AG2-212 GEN
Solar/Wind Harmer
47.9
965681AG1-436 GEN
Solar/Wind Harmer
25.076
965791AG1-447 GEN
Solar/Wind Harmer
12.83
274888KELLY CRK;1U
Solar/Wind Harmer
11.664
274887GEN-1.85
Solar/Wind Harmer
10.531
276843GEN-1.7
Solar/Wind Harmer
1.133
958011AF2-095 GEN
Solar/Wind Harmer
28.45
274803UNIV PARK;6U
Adder
11.473
274847GR RIDGE ;BU
Solar/Wind Harmer
9.927
274808UNIV PK N;4U
Adder
9.784
274674JOLIET 9 ;6U
Adder
30.161
971573AH1-285 GEN
Solar/Wind Harmer
16.743
274695ROCKY RD ;2P
Adder
21.355
274693ROCKY RD ;1P
Adder
21.145
274697ROCKY RD ;3P
Adder
5.801
274696ROCKY RD ;4P
Adder
21.858
274683WAUKEGAN ;8U
Adder
40.16
274683WAUKEGAN ;8U
Adder
33.853
24441505OLIV SLR
Solar/Wind Harmer
0.255
962691AG1-118 GEN
Solar/Wind Harmer
57.021
970921AG2-575 GEN
Solar/Wind Harmer
18.937
970921AG2-575 GEN
Solar/Wind Harmer
4.404
958481AF2-142 GEN
Solar/Wind Harmer
28.358
274861TOP CROP ;1U
Solar/Wind Harmer
11.442
274862TOP CROP ;2U
Solar/Wind Harmer
9.555
270526AF1-158 GEN
Solar/Wind Harmer
8.548
942991AE2-321 GEN
Solar/Wind Harmer
18.7
958491AF2-143 GEN
Solar/Wind Harmer
27.862
971333AH1-146 GEN
Solar/Wind Harmer
37.128
971335AH1-147 GEN
Solar/Wind Harmer
37.128
274879MINONK ;1U
Solar/Wind Harmer
12.48
971341AH1-150 GEN
Solar/Wind Harmer
36.805
971343AH1-151 GEN
Solar/Wind Harmer
36.805
276872AE1-163_GEN1
Solar/Wind Harmer
12.169
274856ECOGROVE ;U1
Solar/Wind Harmer
6.108
276611AD2-172 GEN
Solar/Wind Harmer
4.635
938861AE1-114 GEN
Solar/Wind Harmer
14.698
274764LEE CO EC;5U
Adder
16.626
274765LEE CO EC;6U
Adder
16.626
274762LEE CO EC;3U
Adder
16.587
274763LEE CO EC;4U
Adder
16.431
276603SUBLETTE C
Solar/Wind Harmer
1.866
971771AH1-392 GEN
Solar/Wind Harmer
16.165
971681AH1-341 GEN
Solar/Wind Harmer
26.907
926823AC1-168 GEN
Solar/Wind Harmer
7.68
970169AG2-114 GEN
Solar/Wind Harmer
17.668
961011AF2-392 GEN
Solar/Wind Harmer
19.169
972267AH1-718 GEN
Adder
7.31
247620Y3-023
Adder
0.618
276741O09 GEN1
Solar/Wind Harmer
0.535
276708O09 GEN2
Solar/Wind Harmer
0.535
274772LINCOLN ;3U
50/50
13.854
970513AG2-328 GEN
Solar/Wind Harmer
47.9
970517AG2-330 GEN
Solar/Wind Harmer
43.444
970349AG2-230 GEN
Solar/Wind Harmer
33.33
970707AG2-453 GEN
Solar/Wind Harmer
56.957
972228AH1-698 GEN2
Adder
7.345
274724RIVER EC ;11
Adder
35.049
276897AD1-100 C
Solar/Wind Harmer
57.396
939351AE1-166 GEN
Solar/Wind Harmer
11.728
276772AC2-154 GEN
Solar/Wind Harmer
5.51
276806AD2-047 C O1
Solar/Wind Harmer
21.135
970941AG2-585 GEN
Solar/Wind Harmer
24.696
274826FISK ;BP
Adder
21.584
274800UNIV PARK;3U
Adder
11.489
972038AH1-567 GEN2
Adder
0.719
274802UNIV PARK;5U
Adder
11.473
943121AE2-341 GEN
Solar/Wind Harmer
29.466
943591AF1-030 GEN
Solar/Wind Harmer
19.644
274676JOLIET 29;8U
Adder
58.067
274729ELWOOD EC;1P
Adder
32.123
274730ELWOOD EC;6P
Adder
32.123
274734ELWOOD EC;8P
Adder
32.123
274736ELWOOD EC;9P
Adder
32.123
972231SS25-0005
Solar/Wind Harmer
18.548
972181SS23-001
Solar/Wind Harmer
11.593
274752CRETE EC ;2U
Adder
9.553
274753CRETE EC ;3U
Adder
9.553
276893AG1-478 C
Solar/Wind Harmer
0.814
274682WAUKEGAN ;7U
Adder
34.314
276694AA1-018 GEN2
Solar/Wind Harmer
11.931
274872LEEDK;1U
Solar/Wind Harmer
0.483
270535AF1-215 GEN1
Solar/Wind Harmer
8.469
276799AD1-013 GEN
Solar/Wind Harmer
4.114
946671AF1-331 GEN
Solar/Wind Harmer
0.779
274855GSG-6 ;RU
Solar/Wind Harmer
6.865
274850MENDOTA H;RU
Solar/Wind Harmer
4.773
276602WESTBROOK C
Solar/Wind Harmer
3.951
276863AD2-134 GEN
Solar/Wind Harmer
3.32
276805AD2-038 GEN
Solar/Wind Harmer
9.529
959091AF2-200 GEN
Solar/Wind Harmer
36.805
964401AG1-302 GEN
Solar/Wind Harmer
16.565
972236AH1-702 GEN2
Adder
3.998
276889AE2-281 GEN
Solar/Wind Harmer
3.477
959141AF2-205 GEN
Solar/Wind Harmer
10.832
274858EASY ROAD;U2
Solar/Wind Harmer
8.544
274760LEE CO EC;1U
Adder
16.587
274767LEE CO EC;8U
Adder
16.391
24642205MAYFLWER
Adder
1.132
970571AG2-364 GEN
Solar/Wind Harmer
35.603
247604X1-042
Adder
0.731
24441205WTRV SLR C
Solar/Wind Harmer
0.236
276157O29GEN1
Solar/Wind Harmer
6.641
NYPJM->LTFIMP_NY
CLTF
2.657
LGEELTFEXP_LGEE->PJM
CLTF
0.941
WECLTFEXP_WEC->PJM
CLTF
6.943
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.137
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.156
AG2-052LTFEXP_AG2-052->PJM
LTF
0.405
AH1-155LTFEXP_AH1-155->PJM
LTF
0.608
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
189.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.331
MECLTFEXP_MEC->PJM
CLTF
23.481
SIGELTFEXP_SIGE->PJM
CLTF
0.228
LAGNLTFEXP_LAGN->PJM
CLTF
9.743
TVALTFEXP_TVA->PJM
CLTF
3.055

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P7-1_#11001___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P7-1_#11001___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.17 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5659.45
MW Contribution:20.57
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
18.73
274773LINCOLN ;4U
50/50
13.001
274774LINCOLN ;5U
50/50
13.001
274772LINCOLN ;3U
50/50
13.001
274770LINCOLN ;1U
50/50
13.001
274771LINCOLN ;2U
50/50
13.001
270102X2-052 ST
50/50
3.099
270100X2-052 CT1
50/50
2.855
270101X2-052 CT2
50/50
2.855
274661LASCO STA;2U
50/50
13.59
972259AH1-714 GEN
50/50
38.145
274660LASCO STA;1U
50/50
13.764
970321AG2-212 GEN
Solar/Wind Harmer
41.418
965681AG1-436 GEN
Solar/Wind Harmer
23.931
965791AG1-447 GEN
Solar/Wind Harmer
12.244
274888KELLY CRK;1U
Solar/Wind Harmer
10.983
274887GEN-1.85
Solar/Wind Harmer
9.915
276843GEN-1.7
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
26.787
274803UNIV PARK;6U
Adder
10.803
274808UNIV PK N;4U
Adder
9.211
274847GR RIDGE ;BU
Solar/Wind Harmer
9.343
274674JOLIET 9 ;6U
Adder
28.4
971573AH1-285 GEN
Solar/Wind Harmer
15.764
24441505OLIV SLR
Solar/Wind Harmer
0.244
270526AF1-158 GEN
Solar/Wind Harmer
8.225
274695ROCKY RD ;2P
Adder
20.121
274693ROCKY RD ;1P
Adder
19.923
274697ROCKY RD ;3P
Adder
5.466
274696ROCKY RD ;4P
Adder
20.595
274683WAUKEGAN ;8U
Adder
37.851
274683WAUKEGAN ;8U
Adder
31.907
962691AG1-118 GEN
Solar/Wind Harmer
53.744
970921AG2-575 GEN
Solar/Wind Harmer
17.851
970921AG2-575 GEN
Solar/Wind Harmer
4.151
958481AF2-142 GEN
Solar/Wind Harmer
26.742
274861TOP CROP ;1U
Solar/Wind Harmer
10.791
274862TOP CROP ;2U
Solar/Wind Harmer
9.011
942991AE2-321 GEN
Solar/Wind Harmer
17.638
958491AF2-143 GEN
Solar/Wind Harmer
26.292
971333AH1-146 GEN
Solar/Wind Harmer
35.031
971335AH1-147 GEN
Solar/Wind Harmer
35.031
274879MINONK ;1U
Solar/Wind Harmer
11.778
971341AH1-150 GEN
Solar/Wind Harmer
34.74
971343AH1-151 GEN
Solar/Wind Harmer
34.74
276872AE1-163_GEN1
Solar/Wind Harmer
11.495
274856ECOGROVE ;U1
Solar/Wind Harmer
5.769
276611AD2-172 GEN
Solar/Wind Harmer
4.378
938861AE1-114 GEN
Solar/Wind Harmer
13.889
274764LEE CO EC;5U
Adder
15.715
274765LEE CO EC;6U
Adder
15.715
274762LEE CO EC;3U
Adder
15.678
274763LEE CO EC;4U
Adder
15.531
276603SUBLETTE C
Solar/Wind Harmer
1.764
957891AF2-083 GEN
Solar/Wind Harmer
5.61
972267AH1-718 GEN
Adder
6.915
960981AF2-389 GEN
Solar/Wind Harmer
2.508
276741O09 GEN1
Solar/Wind Harmer
5.9
276708O09 GEN2
Solar/Wind Harmer
5.9
961051AF2-396 GEN
Solar/Wind Harmer
25.906
961051AF2-396 GEN
Solar/Wind Harmer
12.049
274851PROVIDENC;RU
Solar/Wind Harmer
4.642
274849CRESCENT ;1U
Solar/Wind Harmer
3.014
276645AC1-214 GEN1
Solar/Wind Harmer
2.183
276646AC1-214 GEN2
Solar/Wind Harmer
2.183
276782AC1-033 GEN
Solar/Wind Harmer
6.456
247620Y3-023
Adder
0.559
270471AD2-092_GEN
Solar/Wind Helper
1.321
24344005CKG1
50/50
12.388
970513AG2-328 GEN
Solar/Wind Harmer
41.418
970517AG2-330 GEN
Solar/Wind Harmer
37.565
970349AG2-230 GEN
Solar/Wind Harmer
33.189
970707AG2-453 GEN
Solar/Wind Harmer
53.523
274724RIVER EC ;11
Adder
33.067
972228AH1-698 GEN2
Adder
6.911
276897AD1-100 C
Solar/Wind Harmer
54.005
939351AE1-166 GEN
Solar/Wind Harmer
11.035
276772AC2-154 GEN
Solar/Wind Harmer
5.188
276806AD2-047 C O1
Solar/Wind Harmer
19.9
970941AG2-585 GEN
Solar/Wind Harmer
23.253
274826FISK ;BP
Adder
20.33
274800UNIV PARK;3U
Adder
10.821
972038AH1-567 GEN2
Adder
0.677
274802UNIV PARK;5U
Adder
10.803
943121AE2-341 GEN
Solar/Wind Harmer
27.733
943591AF1-030 GEN
Solar/Wind Harmer
18.488
274676JOLIET 29;8U
Adder
54.671
274729ELWOOD EC;1P
Adder
30.248
274730ELWOOD EC;6P
Adder
30.247
274734ELWOOD EC;8P
Adder
30.247
274736ELWOOD EC;9P
Adder
30.247
972231SS25-0005
Solar/Wind Harmer
17.464
972181SS23-001
Solar/Wind Harmer
10.915
274752CRETE EC ;2U
Adder
8.994
274753CRETE EC ;3U
Adder
8.994
276893AG1-478 C
Solar/Wind Harmer
0.767
274682WAUKEGAN ;7U
Adder
32.339
276694AA1-018 GEN2
Solar/Wind Harmer
11.251
274872LEEDK;1U
Solar/Wind Harmer
0.455
276799AD1-013 GEN
Solar/Wind Harmer
3.881
946671AF1-331 GEN
Solar/Wind Harmer
0.735
274855GSG-6 ;RU
Solar/Wind Harmer
6.477
274850MENDOTA H;RU
Solar/Wind Harmer
4.503
276602WESTBROOK C
Solar/Wind Harmer
3.728
276863AD2-134 GEN
Solar/Wind Harmer
3.132
276805AD2-038 GEN
Solar/Wind Harmer
8.992
959091AF2-200 GEN
Solar/Wind Harmer
34.74
972236AH1-702 GEN2
Adder
3.775
24642205MAYFLWER
Adder
1.093
276889AE2-281 GEN
Solar/Wind Harmer
3.284
274858EASY ROAD;U2
Solar/Wind Harmer
8.076
274760LEE CO EC;1U
Adder
15.678
274767LEE CO EC;8U
Adder
15.494
970571AG2-364 GEN
Solar/Wind Harmer
33.656
270535AF1-215 GEN1
Solar/Wind Harmer
7.607
247604X1-042
Adder
0.696
24441205WTRV SLR C
Solar/Wind Harmer
0.225
276157O29GEN1
Solar/Wind Harmer
6.283
274878BISHOP HL;2U
Solar/Wind Harmer
5.463
970245AG2-165 GEN
Solar/Wind Harmer
41.418
972207SS24-0001
Solar/Wind Harmer
43.561
276164X3-005 C
Solar/Wind Harmer
1.314
274723RIVER EC ;12
Adder
33.414
941551AE2-152 GEN
Solar/Wind Harmer
8.44
276776AD2-060 GEN
Solar/Wind Harmer
0.786
274801UNIV PARK;4U
Adder
10.821
274676JOLIET 29;8U
Adder
56.696
274812UNIV PK N;8U
Adder
9.252
274871GR RIDGE ;2U
Solar/Wind Harmer
14.204
274674JOLIET 9 ;6U
Adder
28.4
274732ELWOOD EC;7P
Adder
30.247
274751CRETE EC ;1U
Adder
8.994
274754CRETE EC ;4U
Adder
8.994
274745AC1-111 GEN9
Adder
10.278
274682WAUKEGAN ;7U
Adder
32.339
274828WAUKEGAN ;BP
Adder
19.841
960751AF2-366 GEN
Solar/Wind Harmer
5.122
962781AG1-127 GEN
Solar/Wind Harmer
16.977
276691AA1-018 GEN1
Solar/Wind Harmer
0.83
274872LEEDK;1U
Solar/Wind Harmer
14.615
939401AE1-172 GEN
Solar/Wind Harmer
24.491
276861AD2-134 GEN
Solar/Wind Harmer
3.132
276901AD2-066 C O1
Solar/Wind Harmer
6.158
971997AH1-543 GEN
Solar/Wind Harmer
27.509
970373AG2-245 GEN
Solar/Wind Harmer
36.682
957471AF2-041 GEN
Solar/Wind Harmer
52.109
959081AF2-199 GEN
Solar/Wind Harmer
17.37
971067AG2-660 GEN
Solar/Wind Harmer
4.039
274822ROCKFORD ;11
Adder
33.922
972235AH1-702 GEN1
Adder
4.342
970819AG2-516 GEN
Solar/Wind Harmer
20.573
276876AE1-163_GEN2
Solar/Wind Harmer
11.495
971475AH1-234 GEN
Solar/Wind Harmer
38.256
270505AE1-170 C O1
Solar/Wind Harmer
25.403
274857EASY ROAD;U1
Solar/Wind Harmer
8.076
274761LEE CO EC;2U
Adder
15.678
274766LEE CO EC;7U
Adder
15.494
970569AG2-363 GEN
Solar/Wind Harmer
50.484
270055AF2-134 C O1
Solar/Wind Harmer
5.07
270449AD2-020 GEN
Solar/Wind Harmer
4.651
943021AE2-325 GEN
Solar/Wind Harmer
6.043
276158O29GEN2
Solar/Wind Harmer
8.26
274877BISHOP HL;1U
Solar/Wind Harmer
5.463
24639705ELKHART HY
Adder
0.212
270349AD2-093_GEN
Solar/Wind Helper
1.321
958381AF2-132 GEN
Solar/Wind Harmer
11.606
274775LINCOLN ;6U
50/50
13.001
274776LINCOLN ;7U
50/50
13.001
274777LINCOLN ;8U
50/50
13.001
971599AH1-298 GEN
50/50
16.711
971347AH1-153 GEN
Solar/Wind Harmer
33.189
960681AF2-359 GEN
Solar/Wind Harmer
7.233
972227AH1-698 GEN1
Adder
4.866
960591AF2-350 GEN
Solar/Wind Harmer
18.602
274827FISK ;RP
Adder
14.408
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.698
274675JOLIET 29;7U
Adder
54.673
970833AG2-524 GEN
Solar/Wind Harmer
16.131
970833AG2-524 GEN
Solar/Wind Harmer
7.503
274687WILL CNTY;4U
Adder
51.628
274687WILL CNTY;4U
Adder
51.628
274814UNIV PK N;0U
Adder
9.333
274807UNIV PK N;3U
Adder
9.312
274805UNIV PK N;1U
Adder
9.272
274811UNIV PK N;7U
Adder
9.252
274731ELWOOD EC;2P
Adder
30.248
274733ELWOOD EC;3P
Adder
30.248
274735ELWOOD EC;4P
Adder
30.248
274728ELWOOD EC;5P
Adder
30.247
274746AC1-111 G10
Adder
10.278
274744AC1-111 GEN8
Adder
10.278
971769AH1-391 GEN
Solar/Wind Harmer
18.249
971177AH1-047 GEN
Solar/Wind Harmer
10.33
971675AH1-338 GEN
Solar/Wind Harmer
31.578
971411AH1-196 GEN
Solar/Wind Harmer
26.291
971771AH1-392 GEN
Solar/Wind Harmer
15.753
276868AE1-113 GEN
Solar/Wind Harmer
17.665
276882AE2-255 GEN
Solar/Wind Harmer
5.889
971171AH1-044 GEN
Solar/Wind Harmer
34.74
274823ROCKFORD ;21
Adder
33.676
274863CRW1-WTG
Solar/Wind Harmer
9.567
274864CRW2-WTG
Solar/Wind Harmer
9.567
276612AE2-035 GEN
Solar/Wind Harmer
4.378
971681AH1-341 GEN
Solar/Wind Harmer
25.426
926823AC1-168 GEN
Solar/Wind Harmer
7.256
270536AF1-215 GEN2
Solar/Wind Harmer
7.607
970169AG2-114 GEN
Solar/Wind Harmer
16.689
961011AF2-392 GEN
Solar/Wind Harmer
18.128
944161AF1-084 GEN
Solar/Wind Harmer
3.666
957751AF2-069 GEN
Solar/Wind Harmer
0.748
NYPJM->LTFIMP_NY
CLTF
2.596
LGEELTFEXP_LGEE->PJM
CLTF
1.837
WECLTFEXP_WEC->PJM
CLTF
6.558
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.728
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.803
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.571
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.339
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.424
MECLTFEXP_MEC->PJM
CLTF
22.474
SIGELTFEXP_SIGE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
10.173
TVALTFEXP_TVA->PJM
CLTF
3.448

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P2-2_#6229_05MERIDN 345_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#6229_05MERIDN 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.21 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5411.41
MW Contribution:19.57
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
12.377
274776LINCOLN ;7U
50/50
12.377
274777LINCOLN ;8U
50/50
12.377
971347AH1-153 GEN
Solar/Wind Harmer
30.166
24344105CKG2
50/50
17.971
274773LINCOLN ;4U
50/50
12.377
274774LINCOLN ;5U
50/50
12.377
970245AG2-165 GEN
Solar/Wind Harmer
39.961
972207SS24-0001
Solar/Wind Harmer
41.471
276164X3-005 C
Solar/Wind Harmer
1.243
941551AE2-152 GEN
Solar/Wind Harmer
8.021
276776AD2-060 GEN
Solar/Wind Harmer
0.746
274723RIVER EC ;12
Adder
31.566
274801UNIV PARK;4U
Adder
10.257
274871GR RIDGE ;2U
Solar/Wind Harmer
13.503
274676JOLIET 29;8U
Adder
53.822
274674JOLIET 9 ;6U
Adder
26.966
274745AC1-111 GEN9
Adder
9.774
274812UNIV PK N;8U
Adder
8.752
274732ELWOOD EC;7P
Adder
28.719
274751CRETE EC ;1U
Adder
8.491
274754CRETE EC ;4U
Adder
8.491
274682WAUKEGAN ;7U
Adder
30.739
274828WAUKEGAN ;BP
Adder
18.86
960751AF2-366 GEN
Solar/Wind Harmer
4.872
962781AG1-127 GEN
Solar/Wind Harmer
16.149
276691AA1-018 GEN1
Solar/Wind Harmer
0.788
274872LEEDK;1U
Solar/Wind Harmer
13.903
939401AE1-172 GEN
Solar/Wind Harmer
23.31
276861AD2-134 GEN
Solar/Wind Harmer
2.98
276901AD2-066 C O1
Solar/Wind Harmer
5.854
971997AH1-543 GEN
Solar/Wind Harmer
26.169
957471AF2-041 GEN
Solar/Wind Harmer
49.576
959081AF2-199 GEN
Solar/Wind Harmer
16.525
971067AG2-660 GEN
Solar/Wind Harmer
3.843
274822ROCKFORD ;11
Adder
32.27
972235AH1-702 GEN1
Adder
4.131
970373AG2-245 GEN
Solar/Wind Harmer
34.373
970819AG2-516 GEN
Solar/Wind Harmer
19.573
276876AE1-163_GEN2
Solar/Wind Harmer
10.927
971475AH1-234 GEN
Solar/Wind Harmer
36.397
274857EASY ROAD;U1
Solar/Wind Harmer
7.685
274761LEE CO EC;2U
Adder
14.92
274766LEE CO EC;7U
Adder
14.744
970569AG2-363 GEN
Solar/Wind Harmer
48.014
270505AE1-170 C O1
Solar/Wind Harmer
23.82
270055AF2-134 C O1
Solar/Wind Harmer
4.77
276158O29GEN2
Solar/Wind Harmer
7.863
270449AD2-020 GEN
Solar/Wind Harmer
4.368
943021AE2-325 GEN
Solar/Wind Harmer
5.675
274877BISHOP HL;1U
Solar/Wind Harmer
5.202
24639705ELKHART HY
Adder
0.2
958381AF2-132 GEN
Solar/Wind Harmer
1.141
274770LINCOLN ;1U
50/50
12.377
274771LINCOLN ;2U
50/50
12.377
270102X2-052 ST
50/50
2.876
270100X2-052 CT1
50/50
2.65
270101X2-052 CT2
50/50
2.65
274661LASCO STA;2U
50/50
12.917
972259AH1-714 GEN
50/50
36.257
274660LASCO STA;1U
50/50
13.082
970321AG2-212 GEN
Solar/Wind Harmer
39.961
965681AG1-436 GEN
Solar/Wind Harmer
22.27
965791AG1-447 GEN
Solar/Wind Harmer
11.394
274888KELLY CRK;1U
Solar/Wind Harmer
10.416
274887GEN-1.85
Solar/Wind Harmer
9.404
276843GEN-1.7
Solar/Wind Harmer
1.012
958011AF2-095 GEN
Solar/Wind Harmer
25.406
274847GR RIDGE ;BU
Solar/Wind Harmer
8.882
274803UNIV PARK;6U
Adder
10.236
274674JOLIET 9 ;6U
Adder
26.966
274808UNIV PK N;4U
Adder
8.714
971573AH1-285 GEN
Solar/Wind Harmer
14.996
274695ROCKY RD ;2P
Adder
19.132
274693ROCKY RD ;1P
Adder
18.944
274697ROCKY RD ;3P
Adder
5.197
274696ROCKY RD ;4P
Adder
19.582
274683WAUKEGAN ;8U
Adder
35.979
274683WAUKEGAN ;8U
Adder
30.329
962691AG1-118 GEN
Solar/Wind Harmer
51.121
24441505OLIV SLR
Solar/Wind Harmer
0.228
970921AG2-575 GEN
Solar/Wind Harmer
16.981
970921AG2-575 GEN
Solar/Wind Harmer
3.949
958481AF2-142 GEN
Solar/Wind Harmer
25.391
274861TOP CROP ;1U
Solar/Wind Harmer
10.245
274862TOP CROP ;2U
Solar/Wind Harmer
8.555
270526AF1-158 GEN
Solar/Wind Harmer
7.668
942991AE2-321 GEN
Solar/Wind Harmer
16.775
971333AH1-146 GEN
Solar/Wind Harmer
33.322
971335AH1-147 GEN
Solar/Wind Harmer
33.322
958491AF2-143 GEN
Solar/Wind Harmer
24.976
274879MINONK ;1U
Solar/Wind Harmer
11.195
971341AH1-150 GEN
Solar/Wind Harmer
33.051
971343AH1-151 GEN
Solar/Wind Harmer
33.051
274856ECOGROVE ;U1
Solar/Wind Harmer
5.489
276611AD2-172 GEN
Solar/Wind Harmer
4.165
276872AE1-163_GEN1
Solar/Wind Harmer
10.927
938861AE1-114 GEN
Solar/Wind Harmer
13.217
274764LEE CO EC;5U
Adder
14.955
274765LEE CO EC;6U
Adder
14.955
274762LEE CO EC;3U
Adder
14.92
274763LEE CO EC;4U
Adder
14.78
276603SUBLETTE C
Solar/Wind Harmer
1.678
972267AH1-718 GEN
Adder
6.582
276741O09 GEN1
Solar/Wind Harmer
5.617
276708O09 GEN2
Solar/Wind Harmer
5.617
957891AF2-083 GEN
Solar/Wind Harmer
5.263
960981AF2-389 GEN
Solar/Wind Harmer
2.353
274851PROVIDENC;RU
Solar/Wind Harmer
4.42
274849CRESCENT ;1U
Solar/Wind Harmer
2.87
276645AC1-214 GEN1
Solar/Wind Harmer
2.079
276646AC1-214 GEN2
Solar/Wind Harmer
2.079
276782AC1-033 GEN
Solar/Wind Harmer
6.147
961051AF2-396 GEN
Solar/Wind Harmer
24.339
961051AF2-396 GEN
Solar/Wind Harmer
11.321
247620Y3-023
Adder
0.532
274772LINCOLN ;3U
50/50
12.377
24344005CKG1
50/50
11.686
970513AG2-328 GEN
Solar/Wind Harmer
39.961
970517AG2-330 GEN
Solar/Wind Harmer
36.243
970349AG2-230 GEN
Solar/Wind Harmer
30.166
970707AG2-453 GEN
Solar/Wind Harmer
50.932
972228AH1-698 GEN2
Adder
6.561
276897AD1-100 C
Solar/Wind Harmer
51.322
939351AE1-166 GEN
Solar/Wind Harmer
10.486
276772AC2-154 GEN
Solar/Wind Harmer
4.92
276806AD2-047 C O1
Solar/Wind Harmer
18.874
970941AG2-585 GEN
Solar/Wind Harmer
22.054
274724RIVER EC ;11
Adder
31.235
274826FISK ;BP
Adder
19.266
274800UNIV PARK;3U
Adder
10.257
972038AH1-567 GEN2
Adder
0.642
943121AE2-341 GEN
Solar/Wind Harmer
26.38
943591AF1-030 GEN
Solar/Wind Harmer
17.587
274802UNIV PARK;5U
Adder
10.236
274676JOLIET 29;8U
Adder
51.9
274729ELWOOD EC;1P
Adder
28.72
274730ELWOOD EC;6P
Adder
28.719
274734ELWOOD EC;8P
Adder
28.719
274736ELWOOD EC;9P
Adder
28.719
276893AG1-478 C
Solar/Wind Harmer
0.728
972231SS25-0005
Solar/Wind Harmer
16.487
972181SS23-001
Solar/Wind Harmer
10.304
274752CRETE EC ;2U
Adder
8.491
274753CRETE EC ;3U
Adder
8.491
274682WAUKEGAN ;7U
Adder
30.739
276694AA1-018 GEN2
Solar/Wind Harmer
10.682
274872LEEDK;1U
Solar/Wind Harmer
0.433
276799AD1-013 GEN
Solar/Wind Harmer
3.692
946671AF1-331 GEN
Solar/Wind Harmer
0.699
274855GSG-6 ;RU
Solar/Wind Harmer
6.162
274850MENDOTA H;RU
Solar/Wind Harmer
4.284
276602WESTBROOK C
Solar/Wind Harmer
3.547
276863AD2-134 GEN
Solar/Wind Harmer
2.98
276805AD2-038 GEN
Solar/Wind Harmer
8.542
959091AF2-200 GEN
Solar/Wind Harmer
33.051
972236AH1-702 GEN2
Adder
3.592
276889AE2-281 GEN
Solar/Wind Harmer
3.122
24642205MAYFLWER
Adder
1.022
274858EASY ROAD;U2
Solar/Wind Harmer
7.685
274760LEE CO EC;1U
Adder
14.92
274767LEE CO EC;8U
Adder
14.744
970571AG2-364 GEN
Solar/Wind Harmer
32.009
270535AF1-215 GEN1
Solar/Wind Harmer
7.156
247604X1-042
Adder
0.655
276157O29GEN1
Solar/Wind Harmer
5.981
24441205WTRV SLR C
Solar/Wind Harmer
0.212
274878BISHOP HL;2U
Solar/Wind Harmer
5.202
960681AF2-359 GEN
Solar/Wind Harmer
6.731
972227AH1-698 GEN1
Adder
4.62
960591AF2-350 GEN
Solar/Wind Harmer
17.643
274827FISK ;RP
Adder
13.654
970833AG2-524 GEN
Solar/Wind Harmer
15.333
970833AG2-524 GEN
Solar/Wind Harmer
7.132
972037AH1-567 GEN1
Adder
0.321
274675JOLIET 29;7U
Adder
53.824
274675JOLIET 29;7U
Adder
51.902
274687WILL CNTY;4U
Adder
48.992
274687WILL CNTY;4U
Adder
48.992
274746AC1-111 G10
Adder
9.774
274744AC1-111 GEN8
Adder
9.774
274814UNIV PK N;0U
Adder
8.829
274807UNIV PK N;3U
Adder
8.809
274805UNIV PK N;1U
Adder
8.771
274811UNIV PK N;7U
Adder
8.752
274731ELWOOD EC;2P
Adder
28.72
274733ELWOOD EC;3P
Adder
28.72
274735ELWOOD EC;4P
Adder
28.72
274728ELWOOD EC;5P
Adder
28.719
971769AH1-391 GEN
Solar/Wind Harmer
17.012
971177AH1-047 GEN
Solar/Wind Harmer
9.825
971675AH1-338 GEN
Solar/Wind Harmer
30.042
971411AH1-196 GEN
Solar/Wind Harmer
25.006
276868AE1-113 GEN
Solar/Wind Harmer
16.791
276882AE2-255 GEN
Solar/Wind Harmer
5.597
971171AH1-044 GEN
Solar/Wind Harmer
33.051
274823ROCKFORD ;21
Adder
32.036
971771AH1-392 GEN
Solar/Wind Harmer
14.693
274863CRW1-WTG
Solar/Wind Harmer
9.109
274864CRW2-WTG
Solar/Wind Harmer
9.109
276612AE2-035 GEN
Solar/Wind Harmer
4.165
971681AH1-341 GEN
Solar/Wind Harmer
24.195
926823AC1-168 GEN
Solar/Wind Harmer
6.906
970169AG2-114 GEN
Solar/Wind Harmer
15.899
961011AF2-392 GEN
Solar/Wind Harmer
17.254
270536AF1-215 GEN2
Solar/Wind Harmer
7.156
944161AF1-084 GEN
Solar/Wind Harmer
3.444
957751AF2-069 GEN
Solar/Wind Harmer
0.713
274848CAMPGROVE;RU
Solar/Wind Harmer
9.884
NYPJM->LTFIMP_NY
CLTF
2.491
LGEELTFEXP_LGEE->PJM
CLTF
1.887
WECLTFEXP_WEC->PJM
CLTF
6.237
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.753
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.119
AG2-052LTFEXP_AG2-052->PJM
LTF
0.357
AH1-155LTFEXP_AH1-155->PJM
LTF
0.536
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
169.734
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.229
MECLTFEXP_MEC->PJM
CLTF
21.449
SIGELTFEXP_SIGE->PJM
CLTF
0.25
LAGNLTFEXP_LAGN->PJM
CLTF
9.838
TVALTFEXP_TVA->PJM
CLTF
3.368

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.02 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5352.14
MW Contribution:14.62
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
17.85
274776LINCOLN ;7U
50/50
17.85
274777LINCOLN ;8U
50/50
17.85
971347AH1-153 GEN
Solar/Wind Harmer
21.507
972227AH1-698 GEN1
Adder
4.91
960591AF2-350 GEN
Solar/Wind Harmer
13.078
970833AG2-524 GEN
Solar/Wind Harmer
14.352
970833AG2-524 GEN
Solar/Wind Harmer
9.568
274827FISK ;RP
Adder
14.495
274675JOLIET 29;7U
Adder
57.233
274675JOLIET 29;7U
Adder
55.189
972037AH1-567 GEN1
Adder
0.341
274687WILL CNTY;4U
Adder
52.082
274687WILL CNTY;4U
Adder
52.082
274746AC1-111 G10
Adder
10.407
274744AC1-111 GEN8
Adder
10.407
274731ELWOOD EC;2P
Adder
30.563
274733ELWOOD EC;3P
Adder
30.563
274735ELWOOD EC;4P
Adder
30.563
274728ELWOOD EC;5P
Adder
30.562
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274814UNIV PK N;0U
Adder
9.363
274807UNIV PK N;3U
Adder
9.343
274805UNIV PK N;1U
Adder
9.302
274811UNIV PK N;7U
Adder
9.282
971177AH1-047 GEN
Solar/Wind Harmer
7.706
971675AH1-338 GEN
Solar/Wind Harmer
4.855
971411AH1-196 GEN
Solar/Wind Harmer
18.647
276868AE1-113 GEN
Solar/Wind Harmer
2.486
276882AE2-255 GEN
Solar/Wind Harmer
1.449
971171AH1-044 GEN
Solar/Wind Harmer
24.671
274823ROCKFORD ;21
Adder
34.283
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971769AH1-391 GEN
Solar/Wind Harmer
13.669
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
19.428
926823AC1-168 GEN
Solar/Wind Harmer
2.047
970169AG2-114 GEN
Solar/Wind Harmer
11.99
961011AF2-392 GEN
Solar/Wind Harmer
6.975
270536AF1-215 GEN2
Solar/Wind Harmer
0.015
957751AF2-069 GEN
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
50/50
17.85
274771LINCOLN ;2U
50/50
17.85
274661LASCO STA;2U
50/50
13.726
972259AH1-714 GEN
50/50
38.528
274660LASCO STA;1U
50/50
13.902
970321AG2-212 GEN
Solar/Wind Harmer
7.237
274888KELLY CRK;1U
Solar/Wind Harmer
0.768
274887GEN-1.85
Solar/Wind Harmer
0.344
276843GEN-1.7
Solar/Wind Harmer
0.423
958011AF2-095 GEN
Solar/Wind Harmer
18.832
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
274803UNIV PARK;6U
Adder
10.868
274674JOLIET 9 ;6U
Adder
28.688
971573AH1-285 GEN
Solar/Wind Harmer
2.415
965681AG1-436 GEN
Solar/Wind Harmer
16.18
965791AG1-447 GEN
Solar/Wind Harmer
11.865
274808UNIV PK N;4U
Adder
9.241
274695ROCKY RD ;2P
Adder
20.397
274693ROCKY RD ;1P
Adder
20.196
274697ROCKY RD ;3P
Adder
5.541
274696ROCKY RD ;4P
Adder
20.877
274683WAUKEGAN ;8U
Adder
38.365
274683WAUKEGAN ;8U
Adder
32.34
962691AG1-118 GEN
Solar/Wind Harmer
38.059
970921AG2-575 GEN
Solar/Wind Harmer
12.646
970921AG2-575 GEN
Solar/Wind Harmer
4.215
958481AF2-142 GEN
Solar/Wind Harmer
18.909
24344105CKG2
50/50
18.673
274773LINCOLN ;4U
50/50
17.85
274774LINCOLN ;5U
50/50
17.85
970245AG2-165 GEN
Solar/Wind Harmer
7.237
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
1.365
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274801UNIV PARK;4U
Adder
10.893
274676JOLIET 29;8U
Adder
57.231
274723RIVER EC ;12
Adder
33.419
274674JOLIET 9 ;6U
Adder
28.688
274745AC1-111 GEN9
Adder
10.407
274732ELWOOD EC;7P
Adder
30.562
274812UNIV PK N;8U
Adder
9.282
274751CRETE EC ;1U
Adder
15.16
274754CRETE EC ;4U
Adder
15.16
274682WAUKEGAN ;7U
Adder
32.772
274828WAUKEGAN ;BP
Adder
20.11
962781AG1-127 GEN
Solar/Wind Harmer
12.035
274872LEEDK;1U
Solar/Wind Harmer
0.008
276691AA1-018 GEN1
Solar/Wind Harmer
1.527
939401AE1-172 GEN
Solar/Wind Harmer
9.369
276901AD2-066 C O1
Solar/Wind Harmer
0.012
276861AD2-134 GEN
Solar/Wind Harmer
0.223
971997AH1-543 GEN
Solar/Wind Harmer
6.52
957471AF2-041 GEN
Solar/Wind Harmer
37.007
959081AF2-199 GEN
Solar/Wind Harmer
12.336
971067AG2-660 GEN
Solar/Wind Harmer
4.112
274822ROCKFORD ;11
Adder
34.533
972235AH1-702 GEN1
Adder
4.422
970819AG2-516 GEN
Solar/Wind Harmer
14.623
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
25.567
971475AH1-234 GEN
Solar/Wind Harmer
5.893
970569AG2-363 GEN
Solar/Wind Harmer
36.013
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.006
274766LEE CO EC;7U
Adder
15.817
270055AF2-134 C O1
Solar/Wind Harmer
0.009
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.39
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
15.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
15.902
270505AE1-170 C O1
Solar/Wind Harmer
11.776
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
13.971
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.775
945111AF1-176 GEN
Solar/Wind Harmer
18.947
972175AH1-670 GEN
Solar/Wind Harmer
8.763
24791305MDL-5G
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.936
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
276615X2-022 GEN
Solar/Wind Harmer
0.104
965911AG1-460 GEN
Solar/Wind Harmer
1.891
24639705ELKHART HY
Adder
0.206
970333AG2-219 GEN
Solar/Wind Harmer
6.645
963741AG1-226 GEN
Solar/Wind Harmer
21.75
970091AG2-072 GEN
Adder
82.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
270063AE2-323 C
Solar/Wind Harmer
0.005
274772LINCOLN ;3U
50/50
17.85
970513AG2-328 GEN
Solar/Wind Harmer
7.237
970517AG2-330 GEN
Solar/Wind Harmer
43.42
970349AG2-230 GEN
Solar/Wind Harmer
21.507
970707AG2-453 GEN
Solar/Wind Harmer
44.024
972228AH1-698 GEN2
Adder
6.973
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
276806AD2-047 C O1
Solar/Wind Harmer
7.411
970941AG2-585 GEN
Solar/Wind Harmer
16.347
943121AE2-341 GEN
Solar/Wind Harmer
21.899
943591AF1-030 GEN
Solar/Wind Harmer
14.563
274800UNIV PARK;3U
Adder
10.893
972038AH1-567 GEN2
Adder
0.682
274826FISK ;BP
Adder
20.453
274724RIVER EC ;11
Adder
33.063
274676JOLIET 29;8U
Adder
55.187
274802UNIV PARK;5U
Adder
10.868
274729ELWOOD EC;1P
Adder
30.563
274730ELWOOD EC;6P
Adder
30.562
274734ELWOOD EC;8P
Adder
30.562
274736ELWOOD EC;9P
Adder
30.562
276893AG1-478 C
Solar/Wind Harmer
0.513
274752CRETE EC ;2U
Adder
15.16
274753CRETE EC ;3U
Adder
15.16
274682WAUKEGAN ;7U
Adder
32.772
274872LEEDK;1U
Solar/Wind Harmer
0.462
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.329
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
276805AD2-038 GEN
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
24.671
972236AH1-702 GEN2
Adder
3.845
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
24.008
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.006
274767LEE CO EC;8U
Adder
15.817
270535AF1-215 GEN1
Solar/Wind Harmer
0.015
276157O29GEN1
Solar/Wind Harmer
1.906
274878BISHOP HL;2U
Solar/Wind Harmer
0.39
964401AG1-302 GEN
Solar/Wind Harmer
0.002
24642205MAYFLWER
Adder
1.04
942111AE2-223 GEN
Solar/Wind Harmer
3.691
965931AG1-462 GEN
Solar/Wind Harmer
28.855
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
247604X1-042
Adder
0.671
24441205WTRV SLR C
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
33.249
959611AF2-252 GEN
Solar/Wind Harmer
3.694
945111AF1-176 GEN
Solar/Wind Harmer
8.607
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
10.541
247643Z2-116 C
Solar/Wind Harmer
0
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.7
276668AB2-070 GEN1
Solar/Wind Harmer
0.371
276621W2-048 GEN
Solar/Wind Harmer
0.501
276838X2-022 GEN2
Solar/Wind Harmer
0.559
942481AE2-261 GEN
Solar/Wind Harmer
28.269
970243AG2-164 GEN
Solar/Wind Harmer
5.436
970519AG2-331 GEN
Solar/Wind Harmer
24.162
970699AG2-449 GEN
Solar/Wind Harmer
2.323
970193AG2-126 GEN
Solar/Wind Harmer
11.787
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
971771AH1-392 GEN
Solar/Wind Harmer
11.509
958391AF2-133 GEN
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.384
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
11.926
941731AE2-173 GEN
Solar/Wind Harmer
9.465
971619AH1-309 GEN
Solar/Wind Harmer
5.047
971611AH1-305 GEN
Solar/Wind Harmer
6.654
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.371
276848AB2-070 GEN3
Solar/Wind Harmer
0.369
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
971549AH1-272 GEN
Solar/Wind Harmer
19.837
963841AG1-237 GEN
Solar/Wind Harmer
4.152
944221AF1-090 GEN
Solar/Wind Harmer
5.24
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.704
942991AE2-321 GEN
Solar/Wind Harmer
13.961
971333AH1-146 GEN
Solar/Wind Harmer
24.851
971335AH1-147 GEN
Solar/Wind Harmer
24.851
958491AF2-143 GEN
Solar/Wind Harmer
18.638
274879MINONK ;1U
Solar/Wind Harmer
0.523
971341AH1-150 GEN
Solar/Wind Harmer
24.671
971343AH1-151 GEN
Solar/Wind Harmer
24.671
24441505OLIV SLR
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.287
276611AD2-172 GEN
Solar/Wind Harmer
0.003
270526AF1-158 GEN
Solar/Wind Harmer
0.015
938861AE1-114 GEN
Solar/Wind Harmer
6.835
274764LEE CO EC;5U
Adder
16.043
274765LEE CO EC;6U
Adder
16.043
274762LEE CO EC;3U
Adder
16.006
274763LEE CO EC;4U
Adder
15.855
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.071
276741O09 GEN1
Solar/Wind Harmer
0.42
276708O09 GEN2
Solar/Wind Harmer
0.42
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.46
276646AC1-214 GEN2
Solar/Wind Harmer
0.46
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.694
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
21.794
961051AF2-396 GEN
Solar/Wind Harmer
14.53
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.002
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
966841AG1-555 GEN
Solar/Wind Harmer
1.132
276916AD2-100_GEN
Solar/Wind Harmer
19.606
276911AD2-131_GEN
Solar/Wind Harmer
1.292
970239AG2-162 GEN
Solar/Wind Harmer
2.323
970241AG2-163 GEN
Solar/Wind Harmer
5.361
247620Y3-023
Adder
0.558
945391AF1-204 GEN
Solar/Wind Harmer
8.349
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.427
944201AF1-088_MTX
Adder
123.331
957141AF2-008_MTX
Adder
2.025
NYPJM->LTFIMP_NY
CLTF
2.757
LGEELTFEXP_LGEE->PJM
CLTF
3.235
WECLTFEXP_WEC->PJM
CLTF
6.675
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.012
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.577
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.862
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.444
MECLTFEXP_MEC->PJM
CLTF
23.446
SIGELTFEXP_SIGE->PJM
CLTF
0.348
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
TVALTFEXP_TVA->PJM
CLTF
3.981

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P2-2_#702_05JEFRSO 765_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#702_05JEFRSO 765_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.61 %
Rating:5001.0 MVA
Rating Type:B
MVA to Mitigate:5331.65
MW Contribution:19.2
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
12.157
970513AG2-328 GEN
Solar/Wind Harmer
40.061
970517AG2-330 GEN
Solar/Wind Harmer
36.334
970349AG2-230 GEN
Solar/Wind Harmer
28.779
970707AG2-453 GEN
Solar/Wind Harmer
50.003
972228AH1-698 GEN2
Adder
6.43
276897AD1-100 C
Solar/Wind Harmer
50.35
939351AE1-166 GEN
Solar/Wind Harmer
10.288
274775LINCOLN ;6U
50/50
12.157
274776LINCOLN ;7U
50/50
12.157
274777LINCOLN ;8U
50/50
12.157
971347AH1-153 GEN
Solar/Wind Harmer
28.779
972227AH1-698 GEN1
Adder
4.528
960591AF2-350 GEN
Solar/Wind Harmer
17.281
970833AG2-524 GEN
Solar/Wind Harmer
15.043
970833AG2-524 GEN
Solar/Wind Harmer
6.997
274827FISK ;RP
Adder
13.364
274675JOLIET 29;7U
Adder
52.745
274675JOLIET 29;7U
Adder
50.862
972037AH1-567 GEN1
Adder
0.314
274687WILL CNTY;4U
Adder
47.996
274687WILL CNTY;4U
Adder
47.996
274746AC1-111 G10
Adder
9.589
274744AC1-111 GEN8
Adder
9.589
960681AF2-359 GEN
Solar/Wind Harmer
6.476
274731ELWOOD EC;2P
Adder
28.15
274733ELWOOD EC;3P
Adder
28.15
274735ELWOOD EC;4P
Adder
28.15
274728ELWOOD EC;5P
Adder
28.149
274814UNIV PK N;0U
Adder
8.628
274807UNIV PK N;3U
Adder
8.61
274805UNIV PK N;1U
Adder
8.572
274811UNIV PK N;7U
Adder
8.553
971177AH1-047 GEN
Solar/Wind Harmer
9.637
971675AH1-338 GEN
Solar/Wind Harmer
29.476
971411AH1-196 GEN
Solar/Wind Harmer
24.529
276868AE1-113 GEN
Solar/Wind Harmer
16.47
276882AE2-255 GEN
Solar/Wind Harmer
5.491
971171AH1-044 GEN
Solar/Wind Harmer
32.425
971769AH1-391 GEN
Solar/Wind Harmer
16.163
274823ROCKFORD ;21
Adder
31.426
274863CRW1-WTG
Solar/Wind Harmer
8.957
274864CRW2-WTG
Solar/Wind Harmer
8.957
276612AE2-035 GEN
Solar/Wind Harmer
4.086
971681AH1-341 GEN
Solar/Wind Harmer
23.738
926823AC1-168 GEN
Solar/Wind Harmer
6.782
970169AG2-114 GEN
Solar/Wind Harmer
15.641
961011AF2-392 GEN
Solar/Wind Harmer
16.929
270536AF1-215 GEN2
Solar/Wind Harmer
7.017
957751AF2-069 GEN
Solar/Wind Harmer
0.7
971771AH1-392 GEN
Solar/Wind Harmer
13.628
274848CAMPGROVE;RU
Solar/Wind Harmer
9.71
946321AF1-296 GEN
Solar/Wind Harmer
15.506
274770LINCOLN ;1U
50/50
12.157
274771LINCOLN ;2U
50/50
12.157
274661LASCO STA;2U
50/50
12.671
972259AH1-714 GEN
50/50
35.566
274660LASCO STA;1U
50/50
12.833
970321AG2-212 GEN
Solar/Wind Harmer
40.061
274888KELLY CRK;1U
Solar/Wind Harmer
10.203
274887GEN-1.85
Solar/Wind Harmer
9.211
276843GEN-1.7
Solar/Wind Harmer
0.991
958011AF2-095 GEN
Solar/Wind Harmer
24.884
274847GR RIDGE ;BU
Solar/Wind Harmer
8.714
274803UNIV PARK;6U
Adder
10.018
274674JOLIET 9 ;6U
Adder
26.431
965681AG1-436 GEN
Solar/Wind Harmer
21.426
965791AG1-447 GEN
Solar/Wind Harmer
10.962
971573AH1-285 GEN
Solar/Wind Harmer
14.715
274808UNIV PK N;4U
Adder
8.516
274695ROCKY RD ;2P
Adder
18.767
274693ROCKY RD ;1P
Adder
18.582
274697ROCKY RD ;3P
Adder
5.098
274696ROCKY RD ;4P
Adder
19.209
274683WAUKEGAN ;8U
Adder
35.282
274683WAUKEGAN ;8U
Adder
29.741
962691AG1-118 GEN
Solar/Wind Harmer
50.156
970921AG2-575 GEN
Solar/Wind Harmer
16.66
970921AG2-575 GEN
Solar/Wind Harmer
3.874
958481AF2-142 GEN
Solar/Wind Harmer
24.887
274861TOP CROP ;1U
Solar/Wind Harmer
10.042
274862TOP CROP ;2U
Solar/Wind Harmer
8.385
942991AE2-321 GEN
Solar/Wind Harmer
16.455
971333AH1-146 GEN
Solar/Wind Harmer
32.688
971335AH1-147 GEN
Solar/Wind Harmer
32.688
958491AF2-143 GEN
Solar/Wind Harmer
24.489
274879MINONK ;1U
Solar/Wind Harmer
10.981
971341AH1-150 GEN
Solar/Wind Harmer
32.425
971343AH1-151 GEN
Solar/Wind Harmer
32.425
24441505OLIV SLR
Solar/Wind Harmer
0.217
270526AF1-158 GEN
Solar/Wind Harmer
7.252
274856ECOGROVE ;U1
Solar/Wind Harmer
5.385
276611AD2-172 GEN
Solar/Wind Harmer
4.086
276872AE1-163_GEN1
Solar/Wind Harmer
10.72
938861AE1-114 GEN
Solar/Wind Harmer
12.966
274764LEE CO EC;5U
Adder
14.672
274765LEE CO EC;6U
Adder
14.672
274762LEE CO EC;3U
Adder
14.637
274763LEE CO EC;4U
Adder
14.5
276603SUBLETTE C
Solar/Wind Harmer
1.647
972267AH1-718 GEN
Adder
6.458
276741O09 GEN1
Solar/Wind Harmer
5.512
276708O09 GEN2
Solar/Wind Harmer
5.512
274851PROVIDENC;RU
Solar/Wind Harmer
4.341
274849CRESCENT ;1U
Solar/Wind Harmer
2.819
276645AC1-214 GEN1
Solar/Wind Harmer
2.042
276646AC1-214 GEN2
Solar/Wind Harmer
2.042
276782AC1-033 GEN
Solar/Wind Harmer
6.038
247620Y3-023
Adder
0.497
970941AG2-585 GEN
Solar/Wind Harmer
21.601
276772AC2-154 GEN
Solar/Wind Harmer
4.819
276806AD2-047 C O1
Solar/Wind Harmer
18.486
943121AE2-341 GEN
Solar/Wind Harmer
25.888
943591AF1-030 GEN
Solar/Wind Harmer
17.259
274800UNIV PARK;3U
Adder
10.042
972038AH1-567 GEN2
Adder
0.629
274826FISK ;BP
Adder
18.856
274724RIVER EC ;11
Adder
30.496
274676JOLIET 29;8U
Adder
50.86
274802UNIV PARK;5U
Adder
10.018
274729ELWOOD EC;1P
Adder
28.15
274730ELWOOD EC;6P
Adder
28.149
274734ELWOOD EC;8P
Adder
28.149
274736ELWOOD EC;9P
Adder
28.149
276893AG1-478 C
Solar/Wind Harmer
0.714
972231SS25-0005
Solar/Wind Harmer
16.085
972181SS23-001
Solar/Wind Harmer
10.053
274752CRETE EC ;2U
Adder
8.285
274753CRETE EC ;3U
Adder
8.285
274682WAUKEGAN ;7U
Adder
30.143
274872LEEDK;1U
Solar/Wind Harmer
0.425
276694AA1-018 GEN2
Solar/Wind Harmer
10.47
276799AD1-013 GEN
Solar/Wind Harmer
3.623
946671AF1-331 GEN
Solar/Wind Harmer
0.686
274855GSG-6 ;RU
Solar/Wind Harmer
6.045
274850MENDOTA H;RU
Solar/Wind Harmer
4.204
276602WESTBROOK C
Solar/Wind Harmer
3.48
276863AD2-134 GEN
Solar/Wind Harmer
2.924
276805AD2-038 GEN
Solar/Wind Harmer
8.375
959091AF2-200 GEN
Solar/Wind Harmer
32.425
972236AH1-702 GEN2
Adder
3.523
276889AE2-281 GEN
Solar/Wind Harmer
3.063
274858EASY ROAD;U2
Solar/Wind Harmer
7.54
274760LEE CO EC;1U
Adder
14.637
274767LEE CO EC;8U
Adder
14.465
970571AG2-364 GEN
Solar/Wind Harmer
31.413
270535AF1-215 GEN1
Solar/Wind Harmer
7.017
276157O29GEN1
Solar/Wind Harmer
5.87
274878BISHOP HL;2U
Solar/Wind Harmer
5.109
24642205MAYFLWER
Adder
0.955
964401AG1-302 GEN
Solar/Wind Harmer
13.612
247604X1-042
Adder
0.618
24344105CKG2
50/50
17.652
274773LINCOLN ;4U
50/50
12.157
274774LINCOLN ;5U
50/50
12.157
970245AG2-165 GEN
Solar/Wind Harmer
40.061
972207SS24-0001
Solar/Wind Harmer
40.734
941551AE2-152 GEN
Solar/Wind Harmer
7.869
276164X3-005 C
Solar/Wind Harmer
1.216
276776AD2-060 GEN
Solar/Wind Harmer
0.731
274871GR RIDGE ;2U
Solar/Wind Harmer
13.248
274801UNIV PARK;4U
Adder
10.042
274723RIVER EC ;12
Adder
30.821
274676JOLIET 29;8U
Adder
52.744
274674JOLIET 9 ;6U
Adder
26.431
274745AC1-111 GEN9
Adder
9.589
274732ELWOOD EC;7P
Adder
28.149
274812UNIV PK N;8U
Adder
8.553
274751CRETE EC ;1U
Adder
8.285
274754CRETE EC ;4U
Adder
8.285
274682WAUKEGAN ;7U
Adder
30.143
274828WAUKEGAN ;BP
Adder
18.494
960751AF2-366 GEN
Solar/Wind Harmer
4.78
962781AG1-127 GEN
Solar/Wind Harmer
15.844
274872LEEDK;1U
Solar/Wind Harmer
13.64
276691AA1-018 GEN1
Solar/Wind Harmer
0.772
939401AE1-172 GEN
Solar/Wind Harmer
22.907
276861AD2-134 GEN
Solar/Wind Harmer
2.924
276901AD2-066 C O1
Solar/Wind Harmer
5.744
971997AH1-543 GEN
Solar/Wind Harmer
25.69
957471AF2-041 GEN
Solar/Wind Harmer
48.638
959081AF2-199 GEN
Solar/Wind Harmer
16.213
971067AG2-660 GEN
Solar/Wind Harmer
3.77
274822ROCKFORD ;11
Adder
31.655
972235AH1-702 GEN1
Adder
4.052
970819AG2-516 GEN
Solar/Wind Harmer
19.2
276876AE1-163_GEN2
Solar/Wind Harmer
10.72
970373AG2-245 GEN
Solar/Wind Harmer
33.487
971475AH1-234 GEN
Solar/Wind Harmer
35.702
274857EASY ROAD;U1
Solar/Wind Harmer
7.54
274761LEE CO EC;2U
Adder
14.637
274766LEE CO EC;7U
Adder
14.465
970569AG2-363 GEN
Solar/Wind Harmer
47.12
270055AF2-134 C O1
Solar/Wind Harmer
4.677
276158O29GEN2
Solar/Wind Harmer
7.717
274877BISHOP HL;1U
Solar/Wind Harmer
5.109
958381AF2-132 GEN
Solar/Wind Harmer
13.612
964861AG1-349 GEN
Solar/Wind Harmer
11.758
971917AH1-482 GEN
Solar/Wind Harmer
13.568
24639705ELKHART HY
Adder
0.186
958391AF2-133 GEN
Solar/Wind Harmer
10.605
NYPJM->LTFIMP_NY
CLTF
2.42
LGEELTFEXP_LGEE->PJM
CLTF
0.777
WECLTFEXP_WEC->PJM
CLTF
6.116
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.742
CBM West 2LTFEXP_CBM-W2->PJM
CBM
81.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.348
AH1-155LTFEXP_AH1-155->PJM
LTF
0.522
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
164.13
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.364
MECLTFEXP_MEC->PJM
CLTF
21.02
SIGELTFEXP_SIGE->PJM
CLTF
0.217
LAGNLTFEXP_LAGN->PJM
CLTF
9.407
TVALTFEXP_TVA->PJM
CLTF
3.118

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.56 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4583.47
MW Contribution:13.13
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
16.207
970513AG2-328 GEN
Solar/Wind Harmer
6.588
970517AG2-330 GEN
Solar/Wind Harmer
39.528
970349AG2-230 GEN
Solar/Wind Harmer
19.648
970707AG2-453 GEN
Solar/Wind Harmer
39.858
972228AH1-698 GEN2
Adder
6.293
276897AD1-100 C
Solar/Wind Harmer
0.016
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
276806AD2-047 C O1
Solar/Wind Harmer
6.686
970941AG2-585 GEN
Solar/Wind Harmer
14.748
943121AE2-341 GEN
Solar/Wind Harmer
19.773
943591AF1-030 GEN
Solar/Wind Harmer
13.149
274826FISK ;BP
Adder
18.452
274800UNIV PARK;3U
Adder
9.826
972038AH1-567 GEN2
Adder
0.615
274724RIVER EC ;11
Adder
29.828
274676JOLIET 29;8U
Adder
49.786
274802UNIV PARK;5U
Adder
9.801
274729ELWOOD EC;1P
Adder
27.554
274730ELWOOD EC;6P
Adder
27.553
274734ELWOOD EC;8P
Adder
27.553
274736ELWOOD EC;9P
Adder
27.553
276893AG1-478 C
Solar/Wind Harmer
0.462
274752CRETE EC ;2U
Adder
13.652
274753CRETE EC ;3U
Adder
13.652
274682WAUKEGAN ;7U
Adder
29.523
274872LEEDK;1U
Solar/Wind Harmer
0.416
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.195
274855GSG-6 ;RU
Solar/Wind Harmer
0.41
274850MENDOTA H;RU
Solar/Wind Harmer
0.132
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.201
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959091AF2-200 GEN
Solar/Wind Harmer
22.166
972236AH1-702 GEN2
Adder
3.453
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
14.347
274767LEE CO EC;8U
Adder
14.178
970571AG2-364 GEN
Solar/Wind Harmer
21.461
276157O29GEN1
Solar/Wind Harmer
1.704
270535AF1-215 GEN1
Solar/Wind Harmer
0.013
274878BISHOP HL;2U
Solar/Wind Harmer
0.348
24642205MAYFLWER
Adder
0.931
247604X1-042
Adder
0.603
964401AG1-302 GEN
Solar/Wind Harmer
0.002
965931AG1-462 GEN
Solar/Wind Harmer
25.726
24441205WTRV SLR C
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
3.258
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24344105CKG2
50/50
17.317
274773LINCOLN ;4U
50/50
16.207
274774LINCOLN ;5U
50/50
16.207
970245AG2-165 GEN
Solar/Wind Harmer
6.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
1.232
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274801UNIV PARK;4U
Adder
9.826
274676JOLIET 29;8U
Adder
51.63
274723RIVER EC ;12
Adder
30.145
274674JOLIET 9 ;6U
Adder
25.873
274745AC1-111 GEN9
Adder
9.39
274732ELWOOD EC;7P
Adder
27.553
274812UNIV PK N;8U
Adder
8.365
274751CRETE EC ;1U
Adder
13.652
274754CRETE EC ;4U
Adder
13.652
274682WAUKEGAN ;7U
Adder
29.523
274828WAUKEGAN ;BP
Adder
18.114
962781AG1-127 GEN
Solar/Wind Harmer
10.836
274872LEEDK;1U
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.373
939401AE1-172 GEN
Solar/Wind Harmer
8.394
276861AD2-134 GEN
Solar/Wind Harmer
0.201
276901AD2-066 C O1
Solar/Wind Harmer
0.011
971997AH1-543 GEN
Solar/Wind Harmer
5.85
957471AF2-041 GEN
Solar/Wind Harmer
33.25
959081AF2-199 GEN
Solar/Wind Harmer
11.083
971067AG2-660 GEN
Solar/Wind Harmer
3.694
274822ROCKFORD ;11
Adder
31.02
972235AH1-702 GEN1
Adder
3.971
970819AG2-516 GEN
Solar/Wind Harmer
13.127
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
971475AH1-234 GEN
Solar/Wind Harmer
5.289
970373AG2-245 GEN
Solar/Wind Harmer
22.658
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
29.234
959611AF2-252 GEN
Solar/Wind Harmer
3.248
945111AF1-176 GEN
Solar/Wind Harmer
7.662
247643Z2-116 C
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.96
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.071
276668AB2-070 GEN1
Solar/Wind Harmer
0.321
276621W2-048 GEN
Solar/Wind Harmer
0.432
276838X2-022 GEN2
Solar/Wind Harmer
0.483
942481AE2-261 GEN
Solar/Wind Harmer
24.202
970243AG2-164 GEN
Solar/Wind Harmer
3.754
970519AG2-331 GEN
Solar/Wind Harmer
16.686
970699AG2-449 GEN
Solar/Wind Harmer
1.604
970193AG2-126 GEN
Solar/Wind Harmer
9.444
274770LINCOLN ;1U
50/50
16.207
274771LINCOLN ;2U
50/50
16.207
274661LASCO STA;2U
50/50
12.405
972259AH1-714 GEN
50/50
34.82
274660LASCO STA;1U
50/50
12.564
970321AG2-212 GEN
Solar/Wind Harmer
6.588
274888KELLY CRK;1U
Solar/Wind Harmer
0.693
274887GEN-1.85
Solar/Wind Harmer
0.311
276843GEN-1.7
Solar/Wind Harmer
0.382
958011AF2-095 GEN
Solar/Wind Harmer
16.99
274847GR RIDGE ;BU
Solar/Wind Harmer
0.004
274803UNIV PARK;6U
Adder
9.801
274674JOLIET 9 ;6U
Adder
25.873
971573AH1-285 GEN
Solar/Wind Harmer
2.179
965681AG1-436 GEN
Solar/Wind Harmer
14.586
965791AG1-447 GEN
Solar/Wind Harmer
10.696
274808UNIV PK N;4U
Adder
8.329
274695ROCKY RD ;2P
Adder
18.381
274693ROCKY RD ;1P
Adder
18.201
274697ROCKY RD ;3P
Adder
4.993
274696ROCKY RD ;4P
Adder
18.814
274683WAUKEGAN ;8U
Adder
34.557
274683WAUKEGAN ;8U
Adder
29.13
962691AG1-118 GEN
Solar/Wind Harmer
34.279
970921AG2-575 GEN
Solar/Wind Harmer
11.387
970921AG2-575 GEN
Solar/Wind Harmer
3.796
958481AF2-142 GEN
Solar/Wind Harmer
16.996
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.531
942991AE2-321 GEN
Solar/Wind Harmer
12.559
971333AH1-146 GEN
Solar/Wind Harmer
22.345
971335AH1-147 GEN
Solar/Wind Harmer
22.345
958491AF2-143 GEN
Solar/Wind Harmer
16.726
274879MINONK ;1U
Solar/Wind Harmer
0.469
971341AH1-150 GEN
Solar/Wind Harmer
22.166
971343AH1-151 GEN
Solar/Wind Harmer
22.166
24441505OLIV SLR
Solar/Wind Harmer
0
274761LEE CO EC;2U
Adder
14.347
274766LEE CO EC;7U
Adder
14.178
970569AG2-363 GEN
Solar/Wind Harmer
32.191
276158O29GEN2
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.008
274877BISHOP HL;1U
Solar/Wind Harmer
0.348
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
13.088
270505AE1-170 C O1
Solar/Wind Harmer
10.544
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
14.034
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.167
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
12.069
945111AF1-176 GEN
Solar/Wind Harmer
16.867
972175AH1-670 GEN
Solar/Wind Harmer
7.647
24791305MDL-5G
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.406
276615X2-022 GEN
Solar/Wind Harmer
0.09
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
24639705ELKHART HY
Adder
0.181
965911AG1-460 GEN
Solar/Wind Harmer
1.619
963741AG1-226 GEN
Solar/Wind Harmer
18.007
970333AG2-219 GEN
Solar/Wind Harmer
4.589
274775LINCOLN ;6U
50/50
16.207
274776LINCOLN ;7U
50/50
16.207
274777LINCOLN ;8U
50/50
16.207
971347AH1-153 GEN
Solar/Wind Harmer
19.648
972227AH1-698 GEN1
Adder
4.431
960591AF2-350 GEN
Solar/Wind Harmer
11.798
970833AG2-524 GEN
Solar/Wind Harmer
12.946
970833AG2-524 GEN
Solar/Wind Harmer
8.631
274827FISK ;RP
Adder
13.077
274675JOLIET 29;7U
Adder
51.632
274675JOLIET 29;7U
Adder
49.788
274687WILL CNTY;4U
Adder
46.979
274687WILL CNTY;4U
Adder
46.979
972037AH1-567 GEN1
Adder
0.308
274746AC1-111 G10
Adder
9.39
274744AC1-111 GEN8
Adder
9.39
274731ELWOOD EC;2P
Adder
27.554
274733ELWOOD EC;3P
Adder
27.554
274735ELWOOD EC;4P
Adder
27.554
274728ELWOOD EC;5P
Adder
27.553
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274814UNIV PK N;0U
Adder
8.438
274807UNIV PK N;3U
Adder
8.42
274805UNIV PK N;1U
Adder
8.384
274811UNIV PK N;7U
Adder
8.365
971177AH1-047 GEN
Solar/Wind Harmer
6.932
971675AH1-338 GEN
Solar/Wind Harmer
4.366
971411AH1-196 GEN
Solar/Wind Harmer
16.767
276868AE1-113 GEN
Solar/Wind Harmer
2.231
276882AE2-255 GEN
Solar/Wind Harmer
1.3
971171AH1-044 GEN
Solar/Wind Harmer
22.166
274823ROCKFORD ;21
Adder
30.795
274856ECOGROVE ;U1
Solar/Wind Harmer
0.257
276611AD2-172 GEN
Solar/Wind Harmer
0.003
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
270526AF1-158 GEN
Solar/Wind Harmer
0.014
938861AE1-114 GEN
Solar/Wind Harmer
6.129
274764LEE CO EC;5U
Adder
14.381
274765LEE CO EC;6U
Adder
14.381
274762LEE CO EC;3U
Adder
14.347
274763LEE CO EC;4U
Adder
14.212
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
6.33
276741O09 GEN1
Solar/Wind Harmer
0.375
276708O09 GEN2
Solar/Wind Harmer
0.375
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.41
276646AC1-214 GEN2
Solar/Wind Harmer
0.41
276782AC1-033 GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
3.248
961051AF2-396 GEN
Solar/Wind Harmer
19.465
961051AF2-396 GEN
Solar/Wind Harmer
12.976
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.952
276916AD2-100_GEN
Solar/Wind Harmer
16.743
276911AD2-131_GEN
Solar/Wind Harmer
1.103
970241AG2-163 GEN
Solar/Wind Harmer
4.438
247620Y3-023
Adder
0.483
970239AG2-162 GEN
Solar/Wind Harmer
1.604
945391AF1-204 GEN
Solar/Wind Harmer
6.689
971769AH1-391 GEN
Solar/Wind Harmer
12.285
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
17.421
926823AC1-168 GEN
Solar/Wind Harmer
1.83
970169AG2-114 GEN
Solar/Wind Harmer
10.676
961011AF2-392 GEN
Solar/Wind Harmer
6.245
270536AF1-215 GEN2
Solar/Wind Harmer
0.013
957751AF2-069 GEN
Solar/Wind Harmer
0.344
971771AH1-392 GEN
Solar/Wind Harmer
10.304
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
5.695
971619AH1-309 GEN
Solar/Wind Harmer
4.519
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
10.525
941731AE2-173 GEN
Solar/Wind Harmer
8.353
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
5.748
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.321
276848AB2-070 GEN3
Solar/Wind Harmer
0.32
971549AH1-272 GEN
Solar/Wind Harmer
17.65
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.464
944221AF1-090 GEN
Solar/Wind Harmer
4.433
NYPJM->LTFIMP_NY
CLTF
2.408
LGEELTFEXP_LGEE->PJM
CLTF
1.951
WECLTFEXP_WEC->PJM
CLTF
5.994
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.442
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.701
AG2-052LTFEXP_AG2-052->PJM
LTF
0.34
AH1-155LTFEXP_AH1-155->PJM
LTF
0.51
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.284
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.728
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.182
MECLTFEXP_MEC->PJM
CLTF
20.685
SIGELTFEXP_SIGE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
9.627
TVALTFEXP_TVA->PJM
CLTF
3.333

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:122.87 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6786.3
MW Contribution:22.99
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
14.331
274771LINCOLN ;2U
50/50
14.331
274661LASCO STA;2U
50/50
15.039
972259AH1-714 GEN
50/50
42.213
274660LASCO STA;1U
50/50
15.232
970321AG2-212 GEN
Solar/Wind Harmer
47.341
274888KELLY CRK;1U
Solar/Wind Harmer
12.144
274887GEN-1.85
Solar/Wind Harmer
10.964
276843GEN-1.7
Solar/Wind Harmer
1.18
958011AF2-095 GEN
Solar/Wind Harmer
29.62
274847GR RIDGE ;BU
Solar/Wind Harmer
10.372
965681AG1-436 GEN
Solar/Wind Harmer
25.586
965791AG1-447 GEN
Solar/Wind Harmer
13.09
274803UNIV PARK;6U
Adder
11.932
274674JOLIET 9 ;6U
Adder
31.468
274808UNIV PK N;4U
Adder
10.156
971573AH1-285 GEN
Solar/Wind Harmer
17.498
274695ROCKY RD ;2P
Adder
22.358
274693ROCKY RD ;1P
Adder
22.138
274697ROCKY RD ;3P
Adder
6.074
274696ROCKY RD ;4P
Adder
22.884
274683WAUKEGAN ;8U
Adder
42.064
274683WAUKEGAN ;8U
Adder
35.458
962691AG1-118 GEN
Solar/Wind Harmer
59.796
970921AG2-575 GEN
Solar/Wind Harmer
19.869
970921AG2-575 GEN
Solar/Wind Harmer
4.621
958481AF2-142 GEN
Solar/Wind Harmer
29.773
274861TOP CROP ;1U
Solar/Wind Harmer
12.015
274862TOP CROP ;2U
Solar/Wind Harmer
10.033
970239AG2-162 GEN
Solar/Wind Harmer
21.671
942991AE2-321 GEN
Solar/Wind Harmer
19.649
958491AF2-143 GEN
Solar/Wind Harmer
29.362
971333AH1-146 GEN
Solar/Wind Harmer
39.061
971335AH1-147 GEN
Solar/Wind Harmer
39.061
274879MINONK ;1U
Solar/Wind Harmer
13.17
971341AH1-150 GEN
Solar/Wind Harmer
38.786
971343AH1-151 GEN
Solar/Wind Harmer
38.786
24441505OLIV SLR
Solar/Wind Harmer
0.26
276872AE1-163_GEN1
Solar/Wind Harmer
12.894
270526AF1-158 GEN
Solar/Wind Harmer
8.708
274856ECOGROVE ;U1
Solar/Wind Harmer
6.451
276611AD2-172 GEN
Solar/Wind Harmer
4.895
938861AE1-114 GEN
Solar/Wind Harmer
15.551
274764LEE CO EC;5U
Adder
17.605
274765LEE CO EC;6U
Adder
17.605
274762LEE CO EC;3U
Adder
17.564
274763LEE CO EC;4U
Adder
17.398
972267AH1-718 GEN
Adder
7.762
247620Y3-023
Adder
0.631
274772LINCOLN ;3U
50/50
14.331
970513AG2-328 GEN
Solar/Wind Harmer
47.341
970517AG2-330 GEN
Solar/Wind Harmer
42.937
970349AG2-230 GEN
Solar/Wind Harmer
33.644
970707AG2-453 GEN
Solar/Wind Harmer
59.18
972228AH1-698 GEN2
Adder
7.649
276897AD1-100 C
Solar/Wind Harmer
59.931
939351AE1-166 GEN
Solar/Wind Harmer
12.245
276772AC2-154 GEN
Solar/Wind Harmer
5.736
276806AD2-047 C O1
Solar/Wind Harmer
22.004
970941AG2-585 GEN
Solar/Wind Harmer
25.711
274724RIVER EC ;11
Adder
36.314
274800UNIV PARK;3U
Adder
11.955
972038AH1-567 GEN2
Adder
0.748
943121AE2-341 GEN
Solar/Wind Harmer
30.756
943591AF1-030 GEN
Solar/Wind Harmer
20.504
274826FISK ;BP
Adder
22.446
274802UNIV PARK;5U
Adder
11.932
274676JOLIET 29;8U
Adder
60.528
274729ELWOOD EC;1P
Adder
33.534
274730ELWOOD EC;6P
Adder
33.533
274734ELWOOD EC;8P
Adder
33.533
274736ELWOOD EC;9P
Adder
33.533
276893AG1-478 C
Solar/Wind Harmer
0.85
972231SS25-0005
Solar/Wind Harmer
19.213
972181SS23-001
Solar/Wind Harmer
12.008
274752CRETE EC ;2U
Adder
9.895
274753CRETE EC ;3U
Adder
9.895
274682WAUKEGAN ;7U
Adder
35.931
276694AA1-018 GEN2
Solar/Wind Harmer
12.526
274872LEEDK;1U
Solar/Wind Harmer
0.507
970243AG2-164 GEN
Solar/Wind Harmer
50.88
970519AG2-331 GEN
Solar/Wind Harmer
34.183
970699AG2-449 GEN
Solar/Wind Harmer
22.613
276799AD1-013 GEN
Solar/Wind Harmer
4.328
946671AF1-331 GEN
Solar/Wind Harmer
0.82
276805AD2-038 GEN
Solar/Wind Harmer
10.042
274855GSG-6 ;RU
Solar/Wind Harmer
7.224
274850MENDOTA H;RU
Solar/Wind Harmer
5.023
276602WESTBROOK C
Solar/Wind Harmer
4.158
276863AD2-134 GEN
Solar/Wind Harmer
3.494
959091AF2-200 GEN
Solar/Wind Harmer
38.786
972236AH1-702 GEN2
Adder
4.217
270535AF1-215 GEN1
Solar/Wind Harmer
8.732
276889AE2-281 GEN
Solar/Wind Harmer
3.684
970571AG2-364 GEN
Solar/Wind Harmer
37.87
964401AG1-302 GEN
Solar/Wind Harmer
17.135
274760LEE CO EC;1U
Adder
17.564
274767LEE CO EC;8U
Adder
17.357
24642205MAYFLWER
Adder
1.151
247604X1-042
Adder
0.741
274858EASY ROAD;U2
Solar/Wind Harmer
8.443
24344105CKG2
50/50
20.151
274773LINCOLN ;4U
50/50
14.331
274774LINCOLN ;5U
50/50
14.331
970245AG2-165 GEN
Solar/Wind Harmer
47.341
972207SS24-0001
Solar/Wind Harmer
48.017
941551AE2-152 GEN
Solar/Wind Harmer
9.366
276164X3-005 C
Solar/Wind Harmer
1.446
276776AD2-060 GEN
Solar/Wind Harmer
0.87
274801UNIV PARK;4U
Adder
11.955
274871GR RIDGE ;2U
Solar/Wind Harmer
15.767
274723RIVER EC ;12
Adder
36.71
274676JOLIET 29;8U
Adder
62.769
274674JOLIET 9 ;6U
Adder
31.468
274745AC1-111 GEN9
Adder
11.404
274732ELWOOD EC;7P
Adder
33.533
274812UNIV PK N;8U
Adder
10.201
274751CRETE EC ;1U
Adder
9.895
274754CRETE EC ;4U
Adder
9.895
274682WAUKEGAN ;7U
Adder
35.931
274828WAUKEGAN ;BP
Adder
22.049
960751AF2-366 GEN
Solar/Wind Harmer
5.701
962781AG1-127 GEN
Solar/Wind Harmer
18.895
276691AA1-018 GEN1
Solar/Wind Harmer
0.924
274872LEEDK;1U
Solar/Wind Harmer
16.273
939401AE1-172 GEN
Solar/Wind Harmer
27.539
970333AG2-219 GEN
Solar/Wind Harmer
62.187
276901AD2-066 C O1
Solar/Wind Harmer
6.889
970373AG2-245 GEN
Solar/Wind Harmer
41.146
971997AH1-543 GEN
Solar/Wind Harmer
30.811
276861AD2-134 GEN
Solar/Wind Harmer
3.494
957471AF2-041 GEN
Solar/Wind Harmer
58.179
959081AF2-199 GEN
Solar/Wind Harmer
19.393
971067AG2-660 GEN
Solar/Wind Harmer
4.51
274822ROCKFORD ;11
Adder
37.876
972235AH1-702 GEN1
Adder
4.85
270055AF2-134 C O1
Solar/Wind Harmer
5.82
276876AE1-163_GEN2
Solar/Wind Harmer
12.894
970819AG2-516 GEN
Solar/Wind Harmer
22.991
971475AH1-234 GEN
Solar/Wind Harmer
42.761
970569AG2-363 GEN
Solar/Wind Harmer
56.806
958381AF2-132 GEN
Solar/Wind Harmer
17.135
274761LEE CO EC;2U
Adder
17.564
274766LEE CO EC;7U
Adder
17.357
970091AG2-072 GEN
Adder
126.966
24639705ELKHART HY
Adder
0.231
274857EASY ROAD;U1
Solar/Wind Harmer
8.443
274775LINCOLN ;6U
50/50
14.331
274776LINCOLN ;7U
50/50
14.331
274777LINCOLN ;8U
50/50
14.331
971347AH1-153 GEN
Solar/Wind Harmer
33.644
972227AH1-698 GEN1
Adder
5.386
960591AF2-350 GEN
Solar/Wind Harmer
20.569
970833AG2-524 GEN
Solar/Wind Harmer
17.904
970833AG2-524 GEN
Solar/Wind Harmer
8.327
274827FISK ;RP
Adder
15.907
960681AF2-359 GEN
Solar/Wind Harmer
7.733
972037AH1-567 GEN1
Adder
0.375
274675JOLIET 29;7U
Adder
62.771
274675JOLIET 29;7U
Adder
60.529
274687WILL CNTY;4U
Adder
57.132
274687WILL CNTY;4U
Adder
57.132
274746AC1-111 G10
Adder
11.404
274744AC1-111 GEN8
Adder
11.404
274731ELWOOD EC;2P
Adder
33.534
274733ELWOOD EC;3P
Adder
33.534
274735ELWOOD EC;4P
Adder
33.534
274728ELWOOD EC;5P
Adder
33.533
274814UNIV PK N;0U
Adder
10.29
274807UNIV PK N;3U
Adder
10.268
274805UNIV PK N;1U
Adder
10.223
274811UNIV PK N;7U
Adder
10.201
971177AH1-047 GEN
Solar/Wind Harmer
11.509
971675AH1-338 GEN
Solar/Wind Harmer
35.22
971411AH1-196 GEN
Solar/Wind Harmer
29.309
276868AE1-113 GEN
Solar/Wind Harmer
19.753
276882AE2-255 GEN
Solar/Wind Harmer
6.585
971171AH1-044 GEN
Solar/Wind Harmer
38.786
971769AH1-391 GEN
Solar/Wind Harmer
19.386
274863CRW1-WTG
Solar/Wind Harmer
10.817
274864CRW2-WTG
Solar/Wind Harmer
10.817
274823ROCKFORD ;21
Adder
37.601
270536AF1-215 GEN2
Solar/Wind Harmer
8.732
276612AE2-035 GEN
Solar/Wind Harmer
4.895
926823AC1-168 GEN
Solar/Wind Harmer
8.176
971681AH1-341 GEN
Solar/Wind Harmer
28.47
970169AG2-114 GEN
Solar/Wind Harmer
18.975
944201AF1-088_MTX
Adder
159.345
957141AF2-008_MTX
Adder
47.039
NYPJM->LTFIMP_NY
CLTF
2.982
LGEELTFEXP_LGEE->PJM
CLTF
1.518
WECLTFEXP_WEC->PJM
CLTF
7.321
CBM West 2LTFEXP_CBM-W2->PJM
CBM
107.237
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.277
AG2-052LTFEXP_AG2-052->PJM
LTF
0.428
AH1-155LTFEXP_AH1-155->PJM
LTF
0.642
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.619
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.012
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.519
MECLTFEXP_MEC->PJM
CLTF
25.73
SIGELTFEXP_SIGE->PJM
CLTF
0.333
LAGNLTFEXP_LAGN->PJM
CLTF
11.754
TVALTFEXP_TVA->PJM
CLTF
3.905

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6078.08
MW Contribution:20.92
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
18.645
274773LINCOLN ;4U
50/50
13.089
274774LINCOLN ;5U
50/50
13.089
970245AG2-165 GEN
Solar/Wind Harmer
42.678
972207SS24-0001
Solar/Wind Harmer
43.856
941551AE2-152 GEN
Solar/Wind Harmer
8.521
276164X3-005 C
Solar/Wind Harmer
1.315
276776AD2-060 GEN
Solar/Wind Harmer
0.791
274871GR RIDGE ;2U
Solar/Wind Harmer
14.351
274801UNIV PARK;4U
Adder
10.872
274676JOLIET 29;8U
Adder
57.118
274723RIVER EC ;12
Adder
33.353
274674JOLIET 9 ;6U
Adder
28.631
274745AC1-111 GEN9
Adder
10.386
274732ELWOOD EC;7P
Adder
30.502
274812UNIV PK N;8U
Adder
9.264
274751CRETE EC ;1U
Adder
8.975
274754CRETE EC ;4U
Adder
8.975
274682WAUKEGAN ;7U
Adder
32.706
274828WAUKEGAN ;BP
Adder
20.069
960751AF2-366 GEN
Solar/Wind Harmer
5.19
962781AG1-127 GEN
Solar/Wind Harmer
17.202
274872LEEDK;1U
Solar/Wind Harmer
14.814
276691AA1-018 GEN1
Solar/Wind Harmer
0.84
939401AE1-172 GEN
Solar/Wind Harmer
24.967
276901AD2-066 C O1
Solar/Wind Harmer
6.254
276861AD2-134 GEN
Solar/Wind Harmer
3.179
971997AH1-543 GEN
Solar/Wind Harmer
27.98
957471AF2-041 GEN
Solar/Wind Harmer
52.933
959081AF2-199 GEN
Solar/Wind Harmer
17.644
971067AG2-660 GEN
Solar/Wind Harmer
4.103
274822ROCKFORD ;11
Adder
34.461
972235AH1-702 GEN1
Adder
4.412
970819AG2-516 GEN
Solar/Wind Harmer
20.916
276876AE1-163_GEN2
Solar/Wind Harmer
11.698
970373AG2-245 GEN
Solar/Wind Harmer
36.568
971475AH1-234 GEN
Solar/Wind Harmer
38.902
970569AG2-363 GEN
Solar/Wind Harmer
51.507
274857EASY ROAD;U1
Solar/Wind Harmer
8.227
274761LEE CO EC;2U
Adder
15.971
274766LEE CO EC;7U
Adder
15.783
270055AF2-134 C O1
Solar/Wind Harmer
5.134
276158O29GEN2
Solar/Wind Harmer
8.441
274877BISHOP HL;1U
Solar/Wind Harmer
5.606
958381AF2-132 GEN
Solar/Wind Harmer
15.009
964861AG1-349 GEN
Solar/Wind Harmer
12.971
971917AH1-482 GEN
Solar/Wind Harmer
14.968
24639705ELKHART HY
Adder
0.206
970091AG2-072 GEN
Adder
82.257
274775LINCOLN ;6U
50/50
13.089
274776LINCOLN ;7U
50/50
13.089
274777LINCOLN ;8U
50/50
13.089
971347AH1-153 GEN
Solar/Wind Harmer
30.772
972227AH1-698 GEN1
Adder
4.901
960591AF2-350 GEN
Solar/Wind Harmer
18.708
970833AG2-524 GEN
Solar/Wind Harmer
16.295
970833AG2-524 GEN
Solar/Wind Harmer
7.579
274827FISK ;RP
Adder
14.467
274675JOLIET 29;7U
Adder
57.12
274675JOLIET 29;7U
Adder
55.08
972037AH1-567 GEN1
Adder
0.34
274687WILL CNTY;4U
Adder
51.979
274687WILL CNTY;4U
Adder
51.979
274746AC1-111 G10
Adder
10.386
274744AC1-111 GEN8
Adder
10.386
274731ELWOOD EC;2P
Adder
30.503
274733ELWOOD EC;3P
Adder
30.503
274735ELWOOD EC;4P
Adder
30.503
274728ELWOOD EC;5P
Adder
30.502
960681AF2-359 GEN
Solar/Wind Harmer
6.995
274814UNIV PK N;0U
Adder
9.345
274807UNIV PK N;3U
Adder
9.324
274805UNIV PK N;1U
Adder
9.284
274811UNIV PK N;7U
Adder
9.264
971177AH1-047 GEN
Solar/Wind Harmer
10.474
971675AH1-338 GEN
Solar/Wind Harmer
32.051
971411AH1-196 GEN
Solar/Wind Harmer
26.672
276868AE1-113 GEN
Solar/Wind Harmer
17.937
276882AE2-255 GEN
Solar/Wind Harmer
5.979
971171AH1-044 GEN
Solar/Wind Harmer
35.289
274823ROCKFORD ;21
Adder
34.211
274863CRW1-WTG
Solar/Wind Harmer
9.791
274864CRW2-WTG
Solar/Wind Harmer
9.791
971769AH1-391 GEN
Solar/Wind Harmer
17.508
276612AE2-035 GEN
Solar/Wind Harmer
4.452
971681AH1-341 GEN
Solar/Wind Harmer
25.889
926823AC1-168 GEN
Solar/Wind Harmer
7.413
970169AG2-114 GEN
Solar/Wind Harmer
17.149
961011AF2-392 GEN
Solar/Wind Harmer
18.492
270536AF1-215 GEN2
Solar/Wind Harmer
7.701
957751AF2-069 GEN
Solar/Wind Harmer
0.768
274848CAMPGROVE;RU
Solar/Wind Harmer
10.663
971771AH1-392 GEN
Solar/Wind Harmer
14.813
958391AF2-133 GEN
Solar/Wind Harmer
14.818
946321AF1-296 GEN
Solar/Wind Harmer
13.918
274770LINCOLN ;1U
50/50
13.089
274771LINCOLN ;2U
50/50
13.089
274661LASCO STA;2U
50/50
13.7
972259AH1-714 GEN
50/50
38.454
274660LASCO STA;1U
50/50
13.875
970321AG2-212 GEN
Solar/Wind Harmer
42.678
274888KELLY CRK;1U
Solar/Wind Harmer
11.045
274887GEN-1.85
Solar/Wind Harmer
9.972
276843GEN-1.7
Solar/Wind Harmer
1.073
958011AF2-095 GEN
Solar/Wind Harmer
26.939
274847GR RIDGE ;BU
Solar/Wind Harmer
9.44
274803UNIV PARK;6U
Adder
10.847
274674JOLIET 9 ;6U
Adder
28.631
971573AH1-285 GEN
Solar/Wind Harmer
15.941
965681AG1-436 GEN
Solar/Wind Harmer
23.145
965791AG1-447 GEN
Solar/Wind Harmer
11.842
274808UNIV PK N;4U
Adder
9.223
274695ROCKY RD ;2P
Adder
20.356
274693ROCKY RD ;1P
Adder
20.155
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.835
274683WAUKEGAN ;8U
Adder
38.287
274683WAUKEGAN ;8U
Adder
32.274
962691AG1-118 GEN
Solar/Wind Harmer
54.441
970921AG2-575 GEN
Solar/Wind Harmer
18.089
970921AG2-575 GEN
Solar/Wind Harmer
4.207
958481AF2-142 GEN
Solar/Wind Harmer
27.047
274861TOP CROP ;1U
Solar/Wind Harmer
10.914
274862TOP CROP ;2U
Solar/Wind Harmer
9.114
942991AE2-321 GEN
Solar/Wind Harmer
17.883
971333AH1-146 GEN
Solar/Wind Harmer
35.546
971335AH1-147 GEN
Solar/Wind Harmer
35.546
958491AF2-143 GEN
Solar/Wind Harmer
26.66
274879MINONK ;1U
Solar/Wind Harmer
11.959
971341AH1-150 GEN
Solar/Wind Harmer
35.289
971343AH1-151 GEN
Solar/Wind Harmer
35.289
24441505OLIV SLR
Solar/Wind Harmer
0.235
276872AE1-163_GEN1
Solar/Wind Harmer
11.698
274856ECOGROVE ;U1
Solar/Wind Harmer
5.868
276611AD2-172 GEN
Solar/Wind Harmer
4.452
270526AF1-158 GEN
Solar/Wind Harmer
7.861
938861AE1-114 GEN
Solar/Wind Harmer
14.142
274764LEE CO EC;5U
Adder
16.009
274765LEE CO EC;6U
Adder
16.009
274762LEE CO EC;3U
Adder
15.971
274763LEE CO EC;4U
Adder
15.821
276603SUBLETTE C
Solar/Wind Harmer
1.797
972267AH1-718 GEN
Adder
7.055
276741O09 GEN1
Solar/Wind Harmer
6.029
276708O09 GEN2
Solar/Wind Harmer
6.029
274851PROVIDENC;RU
Solar/Wind Harmer
4.761
274849CRESCENT ;1U
Solar/Wind Harmer
3.091
276645AC1-214 GEN1
Solar/Wind Harmer
2.239
276646AC1-214 GEN2
Solar/Wind Harmer
2.239
276782AC1-033 GEN
Solar/Wind Harmer
6.624
247620Y3-023
Adder
0.556
274772LINCOLN ;3U
50/50
13.089
970513AG2-328 GEN
Solar/Wind Harmer
42.678
970517AG2-330 GEN
Solar/Wind Harmer
38.708
970349AG2-230 GEN
Solar/Wind Harmer
30.772
970707AG2-453 GEN
Solar/Wind Harmer
53.983
972228AH1-698 GEN2
Adder
6.96
276897AD1-100 C
Solar/Wind Harmer
54.524
939351AE1-166 GEN
Solar/Wind Harmer
11.141
276772AC2-154 GEN
Solar/Wind Harmer
5.217
276806AD2-047 C O1
Solar/Wind Harmer
20.013
970941AG2-585 GEN
Solar/Wind Harmer
23.385
943121AE2-341 GEN
Solar/Wind Harmer
28.026
943591AF1-030 GEN
Solar/Wind Harmer
18.684
274800UNIV PARK;3U
Adder
10.872
972038AH1-567 GEN2
Adder
0.681
274826FISK ;BP
Adder
20.413
274724RIVER EC ;11
Adder
32.998
274676JOLIET 29;8U
Adder
55.078
274802UNIV PARK;5U
Adder
10.847
274729ELWOOD EC;1P
Adder
30.503
274730ELWOOD EC;6P
Adder
30.502
274734ELWOOD EC;8P
Adder
30.502
274736ELWOOD EC;9P
Adder
30.502
276893AG1-478 C
Solar/Wind Harmer
0.773
972231SS25-0005
Solar/Wind Harmer
17.426
972181SS23-001
Solar/Wind Harmer
10.891
274752CRETE EC ;2U
Adder
8.975
274753CRETE EC ;3U
Adder
8.975
274682WAUKEGAN ;7U
Adder
32.706
274872LEEDK;1U
Solar/Wind Harmer
0.461
276694AA1-018 GEN2
Solar/Wind Harmer
11.379
276799AD1-013 GEN
Solar/Wind Harmer
3.939
946671AF1-331 GEN
Solar/Wind Harmer
0.746
274855GSG-6 ;RU
Solar/Wind Harmer
6.574
274850MENDOTA H;RU
Solar/Wind Harmer
4.571
276602WESTBROOK C
Solar/Wind Harmer
3.784
276863AD2-134 GEN
Solar/Wind Harmer
3.179
276805AD2-038 GEN
Solar/Wind Harmer
9.117
959091AF2-200 GEN
Solar/Wind Harmer
35.289
972236AH1-702 GEN2
Adder
3.837
276889AE2-281 GEN
Solar/Wind Harmer
3.342
970571AG2-364 GEN
Solar/Wind Harmer
34.338
274858EASY ROAD;U2
Solar/Wind Harmer
8.227
274760LEE CO EC;1U
Adder
15.971
274767LEE CO EC;8U
Adder
15.783
270535AF1-215 GEN1
Solar/Wind Harmer
7.701
276157O29GEN1
Solar/Wind Harmer
6.42
274878BISHOP HL;2U
Solar/Wind Harmer
5.606
964401AG1-302 GEN
Solar/Wind Harmer
15.009
24642205MAYFLWER
Adder
1.038
247604X1-042
Adder
0.67
944201AF1-088_MTX
Adder
122.902
957141AF2-008_MTX
Adder
36.281
NYPJM->LTFIMP_NY
CLTF
2.781
LGEELTFEXP_LGEE->PJM
CLTF
3.209
WECLTFEXP_WEC->PJM
CLTF
6.661
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.363
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.037
AG2-052LTFEXP_AG2-052->PJM
LTF
0.384
AH1-155LTFEXP_AH1-155->PJM
LTF
0.576
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.473
CBM West 1LTFEXP_CBM-W1->PJM
CBM
182.965
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.303
MECLTFEXP_MEC->PJM
CLTF
23.384
SIGELTFEXP_SIGE->PJM
CLTF
0.346
LAGNLTFEXP_LAGN->PJM
CLTF
11.194
TVALTFEXP_TVA->PJM
CLTF
3.944

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6077.9
MW Contribution:22.46
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
14.178
274771LINCOLN ;2U
50/50
14.178
270102X2-052 ST
50/50
3.3
270100X2-052 CT1
50/50
3.041
270101X2-052 CT2
50/50
3.041
274661LASCO STA;2U
50/50
14.825
972259AH1-714 GEN
50/50
41.61
274660LASCO STA;1U
50/50
15.014
970321AG2-212 GEN
Solar/Wind Harmer
48.228
970239AG2-162 GEN
Solar/Wind Harmer
24.53
965681AG1-436 GEN
Solar/Wind Harmer
25.603
965791AG1-447 GEN
Solar/Wind Harmer
13.099
274888KELLY CRK;1U
Solar/Wind Harmer
11.971
274887GEN-1.85
Solar/Wind Harmer
10.808
276843GEN-1.7
Solar/Wind Harmer
1.163
958011AF2-095 GEN
Solar/Wind Harmer
29.198
274803UNIV PARK;6U
Adder
11.772
274847GR RIDGE ;BU
Solar/Wind Harmer
10.197
274808UNIV PK N;4U
Adder
10.036
274674JOLIET 9 ;6U
Adder
30.973
971573AH1-285 GEN
Solar/Wind Harmer
17.201
274695ROCKY RD ;2P
Adder
21.954
274693ROCKY RD ;1P
Adder
21.738
274697ROCKY RD ;3P
Adder
5.964
274696ROCKY RD ;4P
Adder
22.471
274683WAUKEGAN ;8U
Adder
41.295
274683WAUKEGAN ;8U
Adder
34.809
962691AG1-118 GEN
Solar/Wind Harmer
58.651
970921AG2-575 GEN
Solar/Wind Harmer
19.482
970921AG2-575 GEN
Solar/Wind Harmer
4.531
958481AF2-142 GEN
Solar/Wind Harmer
29.185
24441505OLIV SLR
Solar/Wind Harmer
0.26
274861TOP CROP ;1U
Solar/Wind Harmer
11.777
274862TOP CROP ;2U
Solar/Wind Harmer
9.834
942991AE2-321 GEN
Solar/Wind Harmer
19.249
270526AF1-158 GEN
Solar/Wind Harmer
8.736
958491AF2-143 GEN
Solar/Wind Harmer
28.71
971333AH1-146 GEN
Solar/Wind Harmer
38.235
971335AH1-147 GEN
Solar/Wind Harmer
38.235
274879MINONK ;1U
Solar/Wind Harmer
12.865
971341AH1-150 GEN
Solar/Wind Harmer
37.924
971343AH1-151 GEN
Solar/Wind Harmer
37.924
276872AE1-163_GEN1
Solar/Wind Harmer
12.561
274856ECOGROVE ;U1
Solar/Wind Harmer
6.299
276611AD2-172 GEN
Solar/Wind Harmer
4.779
938861AE1-114 GEN
Solar/Wind Harmer
15.166
274764LEE CO EC;5U
Adder
17.161
274765LEE CO EC;6U
Adder
17.161
274762LEE CO EC;3U
Adder
17.12
274763LEE CO EC;4U
Adder
16.959
972267AH1-718 GEN
Adder
7.553
247620Y3-023
Adder
0.638
274772LINCOLN ;3U
50/50
14.178
970513AG2-328 GEN
Solar/Wind Harmer
48.228
970517AG2-330 GEN
Solar/Wind Harmer
43.742
970349AG2-230 GEN
Solar/Wind Harmer
33.88
970243AG2-164 GEN
Solar/Wind Harmer
57.591
970519AG2-331 GEN
Solar/Wind Harmer
38.692
970699AG2-449 GEN
Solar/Wind Harmer
25.596
970707AG2-453 GEN
Solar/Wind Harmer
58.387
972228AH1-698 GEN2
Adder
7.538
276897AD1-100 C
Solar/Wind Harmer
58.944
939351AE1-166 GEN
Solar/Wind Harmer
12.044
274724RIVER EC ;11
Adder
35.931
276772AC2-154 GEN
Solar/Wind Harmer
5.654
276806AD2-047 C O1
Solar/Wind Harmer
21.691
970941AG2-585 GEN
Solar/Wind Harmer
25.345
274826FISK ;BP
Adder
22.146
274800UNIV PARK;3U
Adder
11.79
972038AH1-567 GEN2
Adder
0.738
274802UNIV PARK;5U
Adder
11.772
943121AE2-341 GEN
Solar/Wind Harmer
30.257
943591AF1-030 GEN
Solar/Wind Harmer
20.172
274676JOLIET 29;8U
Adder
59.614
274729ELWOOD EC;1P
Adder
32.994
274730ELWOOD EC;6P
Adder
32.993
274734ELWOOD EC;8P
Adder
32.993
274736ELWOOD EC;9P
Adder
32.993
972231SS25-0005
Solar/Wind Harmer
19.019
972181SS23-001
Solar/Wind Harmer
11.887
274752CRETE EC ;2U
Adder
9.796
274753CRETE EC ;3U
Adder
9.796
276893AG1-478 C
Solar/Wind Harmer
0.837
274682WAUKEGAN ;7U
Adder
35.28
276694AA1-018 GEN2
Solar/Wind Harmer
12.278
274872LEEDK;1U
Solar/Wind Harmer
0.497
276799AD1-013 GEN
Solar/Wind Harmer
4.236
946671AF1-331 GEN
Solar/Wind Harmer
0.802
276805AD2-038 GEN
Solar/Wind Harmer
9.819
274855GSG-6 ;RU
Solar/Wind Harmer
7.07
274850MENDOTA H;RU
Solar/Wind Harmer
4.916
276602WESTBROOK C
Solar/Wind Harmer
4.069
276863AD2-134 GEN
Solar/Wind Harmer
3.419
270535AF1-215 GEN1
Solar/Wind Harmer
8.681
959091AF2-200 GEN
Solar/Wind Harmer
37.924
972236AH1-702 GEN2
Adder
4.121
964401AG1-302 GEN
Solar/Wind Harmer
16.999
276889AE2-281 GEN
Solar/Wind Harmer
3.589
959141AF2-205 GEN
Solar/Wind Harmer
11.128
274858EASY ROAD;U2
Solar/Wind Harmer
8.818
274760LEE CO EC;1U
Adder
17.12
274767LEE CO EC;8U
Adder
16.919
24642205MAYFLWER
Adder
1.158
247604X1-042
Adder
0.747
970571AG2-364 GEN
Solar/Wind Harmer
20.103
24344105CKG2
50/50
20.332
274773LINCOLN ;4U
50/50
14.178
274774LINCOLN ;5U
50/50
14.178
970245AG2-165 GEN
Solar/Wind Harmer
48.228
970333AG2-219 GEN
Solar/Wind Harmer
70.389
972207SS24-0001
Solar/Wind Harmer
47.505
276164X3-005 C
Solar/Wind Harmer
1.43
941551AE2-152 GEN
Solar/Wind Harmer
9.212
276776AD2-060 GEN
Solar/Wind Harmer
0.857
274723RIVER EC ;12
Adder
36.323
274801UNIV PARK;4U
Adder
11.79
274871GR RIDGE ;2U
Solar/Wind Harmer
15.502
274676JOLIET 29;8U
Adder
61.822
274812UNIV PK N;8U
Adder
10.08
274674JOLIET 9 ;6U
Adder
30.973
274775LINCOLN ;6U
50/50
14.178
274776LINCOLN ;7U
50/50
14.178
274777LINCOLN ;8U
50/50
14.178
971347AH1-153 GEN
Solar/Wind Harmer
33.88
960681AF2-359 GEN
Solar/Wind Harmer
7.738
972227AH1-698 GEN1
Adder
5.308
960591AF2-350 GEN
Solar/Wind Harmer
20.276
274827FISK ;RP
Adder
15.695
972037AH1-567 GEN1
Adder
0.37
970833AG2-524 GEN
Solar/Wind Harmer
17.604
970833AG2-524 GEN
Solar/Wind Harmer
8.188
274675JOLIET 29;7U
Adder
61.824
274675JOLIET 29;7U
Adder
59.616
274687WILL CNTY;4U
Adder
56.284
274687WILL CNTY;4U
Adder
56.284
274814UNIV PK N;0U
Adder
10.169
274807UNIV PK N;3U
Adder
10.147
274805UNIV PK N;1U
Adder
10.102
274811UNIV PK N;7U
Adder
10.08
274731ELWOOD EC;2P
Adder
32.994
274733ELWOOD EC;3P
Adder
32.994
274735ELWOOD EC;4P
Adder
32.994
274728ELWOOD EC;5P
Adder
32.993
274746AC1-111 G10
Adder
11.214
274744AC1-111 GEN8
Adder
11.214
971769AH1-391 GEN
Solar/Wind Harmer
19.439
971177AH1-047 GEN
Solar/Wind Harmer
11.274
971675AH1-338 GEN
Solar/Wind Harmer
34.47
971411AH1-196 GEN
Solar/Wind Harmer
28.694
270536AF1-215 GEN2
Solar/Wind Harmer
8.681
276868AE1-113 GEN
Solar/Wind Harmer
19.295
276882AE2-255 GEN
Solar/Wind Harmer
6.432
971171AH1-044 GEN
Solar/Wind Harmer
37.924
274823ROCKFORD ;21
Adder
36.759
274863CRW1-WTG
Solar/Wind Harmer
10.485
274864CRW2-WTG
Solar/Wind Harmer
10.485
276612AE2-035 GEN
Solar/Wind Harmer
4.779
958391AF2-133 GEN
Solar/Wind Harmer
16.826
971681AH1-341 GEN
Solar/Wind Harmer
27.764
926823AC1-168 GEN
Solar/Wind Harmer
7.939
274732ELWOOD EC;7P
Adder
32.993
274745AC1-111 GEN9
Adder
11.214
274751CRETE EC ;1U
Adder
9.796
274754CRETE EC ;4U
Adder
9.796
274682WAUKEGAN ;7U
Adder
35.28
274828WAUKEGAN ;BP
Adder
21.646
970373AG2-245 GEN
Solar/Wind Harmer
41.001
960751AF2-366 GEN
Solar/Wind Harmer
5.589
962781AG1-127 GEN
Solar/Wind Harmer
18.527
276691AA1-018 GEN1
Solar/Wind Harmer
0.906
274872LEEDK;1U
Solar/Wind Harmer
15.951
939401AE1-172 GEN
Solar/Wind Harmer
26.81
276901AD2-066 C O1
Solar/Wind Harmer
6.729
276861AD2-134 GEN
Solar/Wind Harmer
3.419
270055AF2-134 C O1
Solar/Wind Harmer
5.786
971997AH1-543 GEN
Solar/Wind Harmer
30.065
957471AF2-041 GEN
Solar/Wind Harmer
56.885
959081AF2-199 GEN
Solar/Wind Harmer
18.962
971067AG2-660 GEN
Solar/Wind Harmer
4.41
274822ROCKFORD ;11
Adder
37.028
972235AH1-702 GEN1
Adder
4.74
958381AF2-132 GEN
Solar/Wind Harmer
16.999
970819AG2-516 GEN
Solar/Wind Harmer
22.458
276876AE1-163_GEN2
Solar/Wind Harmer
12.561
964861AG1-349 GEN
Solar/Wind Harmer
14.698
971917AH1-482 GEN
Solar/Wind Harmer
16.961
971475AH1-234 GEN
Solar/Wind Harmer
41.76
274857EASY ROAD;U1
Solar/Wind Harmer
8.818
274761LEE CO EC;2U
Adder
17.12
274766LEE CO EC;7U
Adder
16.919
24639705ELKHART HY
Adder
0.233
970569AG2-363 GEN
Solar/Wind Harmer
30.155
944201AF1-088_MTX
Adder
102.056
957141AF2-008_MTX
Adder
51.028
NYPJM->LTFIMP_NY
CLTF
2.808
LGEELTFEXP_LGEE->PJM
CLTF
1.84
WECLTFEXP_WEC->PJM
CLTF
7.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
95.762
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.234
AG2-052LTFEXP_AG2-052->PJM
LTF
0.419
AH1-155LTFEXP_AH1-155->PJM
LTF
0.629
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.604
CBM West 1LTFEXP_CBM-W1->PJM
CBM
197.048
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.533
MECLTFEXP_MEC->PJM
CLTF
24.55
SIGELTFEXP_SIGE->PJM
CLTF
0.29
LAGNLTFEXP_LAGN->PJM
CLTF
10.673
TVALTFEXP_TVA->PJM
CLTF
3.482

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.04 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6022.03
MW Contribution:20.96
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.113
274771LINCOLN ;2U
50/50
13.113
274661LASCO STA;2U
50/50
13.726
972259AH1-714 GEN
50/50
38.528
274660LASCO STA;1U
50/50
13.902
970321AG2-212 GEN
Solar/Wind Harmer
42.744
274888KELLY CRK;1U
Solar/Wind Harmer
11.067
274887GEN-1.85
Solar/Wind Harmer
9.991
276843GEN-1.7
Solar/Wind Harmer
1.075
958011AF2-095 GEN
Solar/Wind Harmer
26.992
274847GR RIDGE ;BU
Solar/Wind Harmer
9.458
274803UNIV PARK;6U
Adder
10.868
274674JOLIET 9 ;6U
Adder
28.688
971573AH1-285 GEN
Solar/Wind Harmer
15.973
965681AG1-436 GEN
Solar/Wind Harmer
23.191
965791AG1-447 GEN
Solar/Wind Harmer
11.865
274808UNIV PK N;4U
Adder
9.241
274695ROCKY RD ;2P
Adder
20.397
274693ROCKY RD ;1P
Adder
20.196
274697ROCKY RD ;3P
Adder
5.541
274696ROCKY RD ;4P
Adder
20.877
274683WAUKEGAN ;8U
Adder
38.365
274683WAUKEGAN ;8U
Adder
32.34
962691AG1-118 GEN
Solar/Wind Harmer
54.552
970921AG2-575 GEN
Solar/Wind Harmer
18.126
970921AG2-575 GEN
Solar/Wind Harmer
4.215
958481AF2-142 GEN
Solar/Wind Harmer
27.102
274861TOP CROP ;1U
Solar/Wind Harmer
10.937
274862TOP CROP ;2U
Solar/Wind Harmer
9.133
942991AE2-321 GEN
Solar/Wind Harmer
17.92
971333AH1-146 GEN
Solar/Wind Harmer
35.62
971335AH1-147 GEN
Solar/Wind Harmer
35.62
958491AF2-143 GEN
Solar/Wind Harmer
26.715
274879MINONK ;1U
Solar/Wind Harmer
11.984
971341AH1-150 GEN
Solar/Wind Harmer
35.362
971343AH1-151 GEN
Solar/Wind Harmer
35.362
24441505OLIV SLR
Solar/Wind Harmer
0.235
276872AE1-163_GEN1
Solar/Wind Harmer
11.722
274856ECOGROVE ;U1
Solar/Wind Harmer
5.88
276611AD2-172 GEN
Solar/Wind Harmer
4.462
270526AF1-158 GEN
Solar/Wind Harmer
7.878
938861AE1-114 GEN
Solar/Wind Harmer
14.172
274764LEE CO EC;5U
Adder
16.043
274765LEE CO EC;6U
Adder
16.043
274762LEE CO EC;3U
Adder
16.006
274763LEE CO EC;4U
Adder
15.855
276603SUBLETTE C
Solar/Wind Harmer
1.801
972267AH1-718 GEN
Adder
7.071
276741O09 GEN1
Solar/Wind Harmer
6.042
276708O09 GEN2
Solar/Wind Harmer
6.042
274851PROVIDENC;RU
Solar/Wind Harmer
4.771
274849CRESCENT ;1U
Solar/Wind Harmer
3.098
274772LINCOLN ;3U
50/50
13.113
970513AG2-328 GEN
Solar/Wind Harmer
42.744
970517AG2-330 GEN
Solar/Wind Harmer
38.768
970349AG2-230 GEN
Solar/Wind Harmer
30.827
970707AG2-453 GEN
Solar/Wind Harmer
54.087
972228AH1-698 GEN2
Adder
6.973
276897AD1-100 C
Solar/Wind Harmer
54.631
939351AE1-166 GEN
Solar/Wind Harmer
11.163
276772AC2-154 GEN
Solar/Wind Harmer
5.227
276806AD2-047 C O1
Solar/Wind Harmer
20.052
970941AG2-585 GEN
Solar/Wind Harmer
23.431
943121AE2-341 GEN
Solar/Wind Harmer
28.081
943591AF1-030 GEN
Solar/Wind Harmer
18.721
274800UNIV PARK;3U
Adder
10.893
972038AH1-567 GEN2
Adder
0.682
274826FISK ;BP
Adder
20.453
274724RIVER EC ;11
Adder
33.063
274676JOLIET 29;8U
Adder
55.187
274802UNIV PARK;5U
Adder
10.868
274729ELWOOD EC;1P
Adder
30.563
274730ELWOOD EC;6P
Adder
30.562
274734ELWOOD EC;8P
Adder
30.562
274736ELWOOD EC;9P
Adder
30.562
276893AG1-478 C
Solar/Wind Harmer
0.775
972231SS25-0005
Solar/Wind Harmer
17.461
972181SS23-001
Solar/Wind Harmer
10.913
274752CRETE EC ;2U
Adder
8.993
274753CRETE EC ;3U
Adder
8.993
274682WAUKEGAN ;7U
Adder
32.772
274872LEEDK;1U
Solar/Wind Harmer
0.462
276694AA1-018 GEN2
Solar/Wind Harmer
11.402
276799AD1-013 GEN
Solar/Wind Harmer
3.947
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274855GSG-6 ;RU
Solar/Wind Harmer
6.588
274850MENDOTA H;RU
Solar/Wind Harmer
4.581
276602WESTBROOK C
Solar/Wind Harmer
3.792
276863AD2-134 GEN
Solar/Wind Harmer
3.186
276805AD2-038 GEN
Solar/Wind Harmer
9.136
959091AF2-200 GEN
Solar/Wind Harmer
35.362
972236AH1-702 GEN2
Adder
3.845
276889AE2-281 GEN
Solar/Wind Harmer
3.349
970571AG2-364 GEN
Solar/Wind Harmer
34.412
274858EASY ROAD;U2
Solar/Wind Harmer
8.244
274760LEE CO EC;1U
Adder
16.006
274767LEE CO EC;8U
Adder
15.817
270535AF1-215 GEN1
Solar/Wind Harmer
7.718
276157O29GEN1
Solar/Wind Harmer
6.434
274878BISHOP HL;2U
Solar/Wind Harmer
5.618
964401AG1-302 GEN
Solar/Wind Harmer
15.042
24642205MAYFLWER
Adder
1.04
247604X1-042
Adder
0.671
24344105CKG2
50/50
18.673
274773LINCOLN ;4U
50/50
13.113
274774LINCOLN ;5U
50/50
13.113
970245AG2-165 GEN
Solar/Wind Harmer
42.744
972207SS24-0001
Solar/Wind Harmer
43.938
941551AE2-152 GEN
Solar/Wind Harmer
8.538
276164X3-005 C
Solar/Wind Harmer
1.318
276776AD2-060 GEN
Solar/Wind Harmer
0.793
274871GR RIDGE ;2U
Solar/Wind Harmer
14.379
274801UNIV PARK;4U
Adder
10.893
274676JOLIET 29;8U
Adder
57.231
274723RIVER EC ;12
Adder
33.419
274674JOLIET 9 ;6U
Adder
28.688
274745AC1-111 GEN9
Adder
10.407
274732ELWOOD EC;7P
Adder
30.562
274812UNIV PK N;8U
Adder
9.282
276645AC1-214 GEN1
Solar/Wind Harmer
2.244
276646AC1-214 GEN2
Solar/Wind Harmer
2.244
276782AC1-033 GEN
Solar/Wind Harmer
6.639
247620Y3-023
Adder
0.558
274751CRETE EC ;1U
Adder
8.993
274754CRETE EC ;4U
Adder
8.993
274682WAUKEGAN ;7U
Adder
32.772
274828WAUKEGAN ;BP
Adder
20.11
960751AF2-366 GEN
Solar/Wind Harmer
5.2
962781AG1-127 GEN
Solar/Wind Harmer
17.237
274872LEEDK;1U
Solar/Wind Harmer
14.845
276691AA1-018 GEN1
Solar/Wind Harmer
0.841
939401AE1-172 GEN
Solar/Wind Harmer
25.019
276901AD2-066 C O1
Solar/Wind Harmer
6.267
276861AD2-134 GEN
Solar/Wind Harmer
3.186
971997AH1-543 GEN
Solar/Wind Harmer
28.038
957471AF2-041 GEN
Solar/Wind Harmer
53.043
959081AF2-199 GEN
Solar/Wind Harmer
17.681
971067AG2-660 GEN
Solar/Wind Harmer
4.112
274822ROCKFORD ;11
Adder
34.533
972235AH1-702 GEN1
Adder
4.422
970819AG2-516 GEN
Solar/Wind Harmer
20.96
276876AE1-163_GEN2
Solar/Wind Harmer
11.722
970373AG2-245 GEN
Solar/Wind Harmer
36.646
971475AH1-234 GEN
Solar/Wind Harmer
38.984
970569AG2-363 GEN
Solar/Wind Harmer
51.618
274857EASY ROAD;U1
Solar/Wind Harmer
8.244
274761LEE CO EC;2U
Adder
16.006
274766LEE CO EC;7U
Adder
15.817
270055AF2-134 C O1
Solar/Wind Harmer
5.145
276158O29GEN2
Solar/Wind Harmer
8.459
274877BISHOP HL;1U
Solar/Wind Harmer
5.618
958381AF2-132 GEN
Solar/Wind Harmer
15.042
964861AG1-349 GEN
Solar/Wind Harmer
13
971917AH1-482 GEN
Solar/Wind Harmer
15.002
24639705ELKHART HY
Adder
0.206
970091AG2-072 GEN
Adder
82.54
274775LINCOLN ;6U
50/50
13.113
274776LINCOLN ;7U
50/50
13.113
274777LINCOLN ;8U
50/50
13.113
971347AH1-153 GEN
Solar/Wind Harmer
30.827
972227AH1-698 GEN1
Adder
4.91
960591AF2-350 GEN
Solar/Wind Harmer
18.745
970833AG2-524 GEN
Solar/Wind Harmer
16.327
970833AG2-524 GEN
Solar/Wind Harmer
7.594
274827FISK ;RP
Adder
14.495
274675JOLIET 29;7U
Adder
57.233
274675JOLIET 29;7U
Adder
55.189
972037AH1-567 GEN1
Adder
0.341
274687WILL CNTY;4U
Adder
52.082
274687WILL CNTY;4U
Adder
52.082
274746AC1-111 G10
Adder
10.407
274744AC1-111 GEN8
Adder
10.407
274731ELWOOD EC;2P
Adder
30.563
274733ELWOOD EC;3P
Adder
30.563
274735ELWOOD EC;4P
Adder
30.563
274728ELWOOD EC;5P
Adder
30.562
960681AF2-359 GEN
Solar/Wind Harmer
7.009
274814UNIV PK N;0U
Adder
9.363
274807UNIV PK N;3U
Adder
9.343
274805UNIV PK N;1U
Adder
9.302
274811UNIV PK N;7U
Adder
9.282
971177AH1-047 GEN
Solar/Wind Harmer
10.496
971675AH1-338 GEN
Solar/Wind Harmer
32.118
971411AH1-196 GEN
Solar/Wind Harmer
26.727
276868AE1-113 GEN
Solar/Wind Harmer
17.974
276882AE2-255 GEN
Solar/Wind Harmer
5.992
971171AH1-044 GEN
Solar/Wind Harmer
35.362
274823ROCKFORD ;21
Adder
34.283
274863CRW1-WTG
Solar/Wind Harmer
9.812
274864CRW2-WTG
Solar/Wind Harmer
9.812
971769AH1-391 GEN
Solar/Wind Harmer
17.545
276612AE2-035 GEN
Solar/Wind Harmer
4.462
971681AH1-341 GEN
Solar/Wind Harmer
25.944
926823AC1-168 GEN
Solar/Wind Harmer
7.429
970169AG2-114 GEN
Solar/Wind Harmer
17.186
961011AF2-392 GEN
Solar/Wind Harmer
18.532
270536AF1-215 GEN2
Solar/Wind Harmer
7.718
957751AF2-069 GEN
Solar/Wind Harmer
0.769
274848CAMPGROVE;RU
Solar/Wind Harmer
10.687
971771AH1-392 GEN
Solar/Wind Harmer
14.846
958391AF2-133 GEN
Solar/Wind Harmer
14.852
946321AF1-296 GEN
Solar/Wind Harmer
13.949
944201AF1-088_MTX
Adder
123.331
957141AF2-008_MTX
Adder
36.408
NYPJM->LTFIMP_NY
CLTF
2.757
LGEELTFEXP_LGEE->PJM
CLTF
3.235
WECLTFEXP_WEC->PJM
CLTF
6.675
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.862
AG2-052LTFEXP_AG2-052->PJM
LTF
0.385
AH1-155LTFEXP_AH1-155->PJM
LTF
0.577
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
183.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
15.444
MECLTFEXP_MEC->PJM
CLTF
23.446
SIGELTFEXP_SIGE->PJM
CLTF
0.348
LAGNLTFEXP_LAGN->PJM
CLTF
11.269
TVALTFEXP_TVA->PJM
CLTF
3.981

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11046___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11046___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.03 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5745.77
MW Contribution:20.57
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.001
274771LINCOLN ;2U
50/50
13.001
270102X2-052 ST
50/50
3.099
270100X2-052 CT1
50/50
2.855
270101X2-052 CT2
50/50
2.855
274661LASCO STA;2U
50/50
13.59
972259AH1-714 GEN
50/50
38.145
274660LASCO STA;1U
50/50
13.764
970321AG2-212 GEN
Solar/Wind Harmer
41.418
965681AG1-436 GEN
Solar/Wind Harmer
23.931
965791AG1-447 GEN
Solar/Wind Harmer
12.244
274888KELLY CRK;1U
Solar/Wind Harmer
10.983
274887GEN-1.85
Solar/Wind Harmer
9.915
276843GEN-1.7
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
26.787
274803UNIV PARK;6U
Adder
10.803
274808UNIV PK N;4U
Adder
9.211
274847GR RIDGE ;BU
Solar/Wind Harmer
9.343
274674JOLIET 9 ;6U
Adder
28.4
971573AH1-285 GEN
Solar/Wind Harmer
15.764
24441505OLIV SLR
Solar/Wind Harmer
0.244
270526AF1-158 GEN
Solar/Wind Harmer
8.225
274695ROCKY RD ;2P
Adder
20.121
274693ROCKY RD ;1P
Adder
19.923
274697ROCKY RD ;3P
Adder
5.466
274696ROCKY RD ;4P
Adder
20.595
274683WAUKEGAN ;8U
Adder
37.851
274683WAUKEGAN ;8U
Adder
31.907
962691AG1-118 GEN
Solar/Wind Harmer
53.744
970921AG2-575 GEN
Solar/Wind Harmer
17.851
970921AG2-575 GEN
Solar/Wind Harmer
4.151
958481AF2-142 GEN
Solar/Wind Harmer
26.742
274861TOP CROP ;1U
Solar/Wind Harmer
10.791
274862TOP CROP ;2U
Solar/Wind Harmer
9.011
942991AE2-321 GEN
Solar/Wind Harmer
17.638
958491AF2-143 GEN
Solar/Wind Harmer
26.292
971333AH1-146 GEN
Solar/Wind Harmer
35.031
971335AH1-147 GEN
Solar/Wind Harmer
35.031
274879MINONK ;1U
Solar/Wind Harmer
11.778
971341AH1-150 GEN
Solar/Wind Harmer
34.74
971343AH1-151 GEN
Solar/Wind Harmer
34.74
276872AE1-163_GEN1
Solar/Wind Harmer
11.495
274856ECOGROVE ;U1
Solar/Wind Harmer
5.769
276611AD2-172 GEN
Solar/Wind Harmer
4.378
938861AE1-114 GEN
Solar/Wind Harmer
13.889
274764LEE CO EC;5U
Adder
15.715
274765LEE CO EC;6U
Adder
15.715
274762LEE CO EC;3U
Adder
15.678
274763LEE CO EC;4U
Adder
15.531
276603SUBLETTE C
Solar/Wind Harmer
1.764
957891AF2-083 GEN
Solar/Wind Harmer
5.61
972267AH1-718 GEN
Adder
6.915
960981AF2-389 GEN
Solar/Wind Harmer
2.508
276741O09 GEN1
Solar/Wind Harmer
5.9
276708O09 GEN2
Solar/Wind Harmer
5.9
961051AF2-396 GEN
Solar/Wind Harmer
25.906
961051AF2-396 GEN
Solar/Wind Harmer
12.049
274851PROVIDENC;RU
Solar/Wind Harmer
4.642
274849CRESCENT ;1U
Solar/Wind Harmer
3.014
276645AC1-214 GEN1
Solar/Wind Harmer
2.183
276646AC1-214 GEN2
Solar/Wind Harmer
2.183
276782AC1-033 GEN
Solar/Wind Harmer
6.456
247620Y3-023
Adder
0.559
270471AD2-092_GEN
Solar/Wind Helper
1.321
274772LINCOLN ;3U
50/50
13.001
24344005CKG1
50/50
12.388
970513AG2-328 GEN
Solar/Wind Harmer
41.418
970517AG2-330 GEN
Solar/Wind Harmer
37.565
970349AG2-230 GEN
Solar/Wind Harmer
33.189
970707AG2-453 GEN
Solar/Wind Harmer
53.523
274724RIVER EC ;11
Adder
33.067
972228AH1-698 GEN2
Adder
6.911
276897AD1-100 C
Solar/Wind Harmer
54.005
939351AE1-166 GEN
Solar/Wind Harmer
11.035
276772AC2-154 GEN
Solar/Wind Harmer
5.188
276806AD2-047 C O1
Solar/Wind Harmer
19.9
970941AG2-585 GEN
Solar/Wind Harmer
23.253
274826FISK ;BP
Adder
20.33
274800UNIV PARK;3U
Adder
10.821
972038AH1-567 GEN2
Adder
0.677
274802UNIV PARK;5U
Adder
10.803
943121AE2-341 GEN
Solar/Wind Harmer
27.733
943591AF1-030 GEN
Solar/Wind Harmer
18.488
274676JOLIET 29;8U
Adder
54.671
274729ELWOOD EC;1P
Adder
30.248
274730ELWOOD EC;6P
Adder
30.247
274734ELWOOD EC;8P
Adder
30.247
274736ELWOOD EC;9P
Adder
30.247
972231SS25-0005
Solar/Wind Harmer
17.464
972181SS23-001
Solar/Wind Harmer
10.915
274752CRETE EC ;2U
Adder
8.994
274753CRETE EC ;3U
Adder
8.994
276893AG1-478 C
Solar/Wind Harmer
0.767
274682WAUKEGAN ;7U
Adder
32.339
276694AA1-018 GEN2
Solar/Wind Harmer
11.251
274872LEEDK;1U
Solar/Wind Harmer
0.455
276799AD1-013 GEN
Solar/Wind Harmer
3.881
946671AF1-331 GEN
Solar/Wind Harmer
0.735
274855GSG-6 ;RU
Solar/Wind Harmer
6.477
274850MENDOTA H;RU
Solar/Wind Harmer
4.503
276602WESTBROOK C
Solar/Wind Harmer
3.728
276863AD2-134 GEN
Solar/Wind Harmer
3.132
276805AD2-038 GEN
Solar/Wind Harmer
8.992
959091AF2-200 GEN
Solar/Wind Harmer
34.74
972236AH1-702 GEN2
Adder
3.775
24642205MAYFLWER
Adder
1.093
276889AE2-281 GEN
Solar/Wind Harmer
3.284
274858EASY ROAD;U2
Solar/Wind Harmer
8.076
274760LEE CO EC;1U
Adder
15.678
274767LEE CO EC;8U
Adder
15.494
970571AG2-364 GEN
Solar/Wind Harmer
33.656
270535AF1-215 GEN1
Solar/Wind Harmer
7.607
247604X1-042
Adder
0.696
24441205WTRV SLR C
Solar/Wind Harmer
0.225
276157O29GEN1
Solar/Wind Harmer
6.283
274878BISHOP HL;2U
Solar/Wind Harmer
5.463
24344105CKG2
50/50
18.73
274773LINCOLN ;4U
50/50
13.001
274774LINCOLN ;5U
50/50
13.001
970245AG2-165 GEN
Solar/Wind Harmer
41.418
972207SS24-0001
Solar/Wind Harmer
43.561
276164X3-005 C
Solar/Wind Harmer
1.314
274723RIVER EC ;12
Adder
33.414
941551AE2-152 GEN
Solar/Wind Harmer
8.44
276776AD2-060 GEN
Solar/Wind Harmer
0.786
274801UNIV PARK;4U
Adder
10.821
274676JOLIET 29;8U
Adder
56.696
274812UNIV PK N;8U
Adder
9.252
274871GR RIDGE ;2U
Solar/Wind Harmer
14.204
274674JOLIET 9 ;6U
Adder
28.4
274732ELWOOD EC;7P
Adder
30.247
274751CRETE EC ;1U
Adder
8.994
274754CRETE EC ;4U
Adder
8.994
274745AC1-111 GEN9
Adder
10.278
274682WAUKEGAN ;7U
Adder
32.339
274828WAUKEGAN ;BP
Adder
19.841
960751AF2-366 GEN
Solar/Wind Harmer
5.122
962781AG1-127 GEN
Solar/Wind Harmer
16.977
276691AA1-018 GEN1
Solar/Wind Harmer
0.83
274872LEEDK;1U
Solar/Wind Harmer
14.615
939401AE1-172 GEN
Solar/Wind Harmer
24.491
276861AD2-134 GEN
Solar/Wind Harmer
3.132
276901AD2-066 C O1
Solar/Wind Harmer
6.158
971997AH1-543 GEN
Solar/Wind Harmer
27.509
970373AG2-245 GEN
Solar/Wind Harmer
36.682
957471AF2-041 GEN
Solar/Wind Harmer
52.109
959081AF2-199 GEN
Solar/Wind Harmer
17.37
971067AG2-660 GEN
Solar/Wind Harmer
4.039
274822ROCKFORD ;11
Adder
33.922
972235AH1-702 GEN1
Adder
4.342
970819AG2-516 GEN
Solar/Wind Harmer
20.573
276876AE1-163_GEN2
Solar/Wind Harmer
11.495
971475AH1-234 GEN
Solar/Wind Harmer
38.256
270505AE1-170 C O1
Solar/Wind Harmer
25.403
274857EASY ROAD;U1
Solar/Wind Harmer
8.076
274761LEE CO EC;2U
Adder
15.678
274766LEE CO EC;7U
Adder
15.494
970569AG2-363 GEN
Solar/Wind Harmer
50.484
270055AF2-134 C O1
Solar/Wind Harmer
5.07
270449AD2-020 GEN
Solar/Wind Harmer
4.651
943021AE2-325 GEN
Solar/Wind Harmer
6.043
276158O29GEN2
Solar/Wind Harmer
8.26
274877BISHOP HL;1U
Solar/Wind Harmer
5.463
24639705ELKHART HY
Adder
0.212
270349AD2-093_GEN
Solar/Wind Helper
1.321
958381AF2-132 GEN
Solar/Wind Harmer
11.606
274775LINCOLN ;6U
50/50
13.001
274776LINCOLN ;7U
50/50
13.001
274777LINCOLN ;8U
50/50
13.001
971347AH1-153 GEN
Solar/Wind Harmer
33.189
960681AF2-359 GEN
Solar/Wind Harmer
7.233
972227AH1-698 GEN1
Adder
4.866
960591AF2-350 GEN
Solar/Wind Harmer
18.602
274827FISK ;RP
Adder
14.408
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.698
274675JOLIET 29;7U
Adder
54.673
970833AG2-524 GEN
Solar/Wind Harmer
16.131
970833AG2-524 GEN
Solar/Wind Harmer
7.503
274687WILL CNTY;4U
Adder
51.628
274687WILL CNTY;4U
Adder
51.628
274814UNIV PK N;0U
Adder
9.333
274807UNIV PK N;3U
Adder
9.312
274805UNIV PK N;1U
Adder
9.272
274811UNIV PK N;7U
Adder
9.252
274731ELWOOD EC;2P
Adder
30.248
274733ELWOOD EC;3P
Adder
30.248
274735ELWOOD EC;4P
Adder
30.248
274728ELWOOD EC;5P
Adder
30.247
274746AC1-111 G10
Adder
10.278
274744AC1-111 GEN8
Adder
10.278
971769AH1-391 GEN
Solar/Wind Harmer
18.249
971177AH1-047 GEN
Solar/Wind Harmer
10.33
971675AH1-338 GEN
Solar/Wind Harmer
31.578
971411AH1-196 GEN
Solar/Wind Harmer
26.291
971771AH1-392 GEN
Solar/Wind Harmer
15.753
276868AE1-113 GEN
Solar/Wind Harmer
17.665
276882AE2-255 GEN
Solar/Wind Harmer
5.889
971171AH1-044 GEN
Solar/Wind Harmer
34.74
274823ROCKFORD ;21
Adder
33.676
274863CRW1-WTG
Solar/Wind Harmer
9.567
274864CRW2-WTG
Solar/Wind Harmer
9.567
276612AE2-035 GEN
Solar/Wind Harmer
4.378
971681AH1-341 GEN
Solar/Wind Harmer
25.426
926823AC1-168 GEN
Solar/Wind Harmer
7.256
270536AF1-215 GEN2
Solar/Wind Harmer
7.607
970169AG2-114 GEN
Solar/Wind Harmer
16.689
961011AF2-392 GEN
Solar/Wind Harmer
18.128
944161AF1-084 GEN
Solar/Wind Harmer
3.666
957751AF2-069 GEN
Solar/Wind Harmer
0.748
NYPJM->LTFIMP_NY
CLTF
2.596
LGEELTFEXP_LGEE->PJM
CLTF
1.837
WECLTFEXP_WEC->PJM
CLTF
6.558
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.728
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.803
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.571
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.339
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.424
MECLTFEXP_MEC->PJM
CLTF
22.474
SIGELTFEXP_SIGE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
10.173
TVALTFEXP_TVA->PJM
CLTF
3.448

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P4_#17234_05GRNTWN 765_N_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17234_05GRNTWN 765_N_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5664.12
MW Contribution:21.78
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
13.854
274776LINCOLN ;7U
50/50
13.854
274777LINCOLN ;8U
50/50
13.854
971347AH1-153 GEN
Solar/Wind Harmer
33.33
960681AF2-359 GEN
Solar/Wind Harmer
7.579
972227AH1-698 GEN1
Adder
5.172
960591AF2-350 GEN
Solar/Wind Harmer
19.757
274827FISK ;RP
Adder
15.297
972037AH1-567 GEN1
Adder
0.36
970833AG2-524 GEN
Solar/Wind Harmer
17.138
970833AG2-524 GEN
Solar/Wind Harmer
7.971
274675JOLIET 29;7U
Adder
60.219
274675JOLIET 29;7U
Adder
58.069
274814UNIV PK N;0U
Adder
9.913
274807UNIV PK N;3U
Adder
9.892
274805UNIV PK N;1U
Adder
9.849
274811UNIV PK N;7U
Adder
9.827
274687WILL CNTY;4U
Adder
54.826
274687WILL CNTY;4U
Adder
54.826
274731ELWOOD EC;2P
Adder
32.123
274733ELWOOD EC;3P
Adder
32.123
274735ELWOOD EC;4P
Adder
32.123
274728ELWOOD EC;5P
Adder
32.123
274746AC1-111 G10
Adder
10.918
274770LINCOLN ;1U
50/50
13.854
274771LINCOLN ;2U
50/50
13.854
270102X2-052 ST
50/50
3.235
270100X2-052 CT1
50/50
2.981
270101X2-052 CT2
50/50
2.981
274661LASCO STA;2U
50/50
14.451
972259AH1-714 GEN
50/50
40.562
274660LASCO STA;1U
50/50
14.636
970321AG2-212 GEN
Solar/Wind Harmer
47.9
965681AG1-436 GEN
Solar/Wind Harmer
25.076
965791AG1-447 GEN
Solar/Wind Harmer
12.83
274888KELLY CRK;1U
Solar/Wind Harmer
11.664
24344105CKG2
50/50
20.096
274773LINCOLN ;4U
50/50
13.854
274774LINCOLN ;5U
50/50
13.854
970245AG2-165 GEN
Solar/Wind Harmer
47.9
972207SS24-0001
Solar/Wind Harmer
46.418
276164X3-005 C
Solar/Wind Harmer
1.394
941551AE2-152 GEN
Solar/Wind Harmer
8.97
274723RIVER EC ;12
Adder
35.43
276776AD2-060 GEN
Solar/Wind Harmer
0.835
274801UNIV PARK;4U
Adder
11.489
274871GR RIDGE ;2U
Solar/Wind Harmer
15.092
274676JOLIET 29;8U
Adder
60.218
274744AC1-111 GEN8
Adder
10.918
971769AH1-391 GEN
Solar/Wind Harmer
19.021
971177AH1-047 GEN
Solar/Wind Harmer
10.952
270536AF1-215 GEN2
Solar/Wind Harmer
8.469
971675AH1-338 GEN
Solar/Wind Harmer
33.472
971411AH1-196 GEN
Solar/Wind Harmer
27.866
276868AE1-113 GEN
Solar/Wind Harmer
18.718
276882AE2-255 GEN
Solar/Wind Harmer
6.24
971171AH1-044 GEN
Solar/Wind Harmer
36.805
274823ROCKFORD ;21
Adder
35.67
274863CRW1-WTG
Solar/Wind Harmer
10.138
274812UNIV PK N;8U
Adder
9.827
274674JOLIET 9 ;6U
Adder
30.161
274732ELWOOD EC;7P
Adder
32.123
274751CRETE EC ;1U
Adder
9.553
274754CRETE EC ;4U
Adder
9.553
274745AC1-111 GEN9
Adder
10.918
274682WAUKEGAN ;7U
Adder
34.314
970373AG2-245 GEN
Solar/Wind Harmer
40.058
274828WAUKEGAN ;BP
Adder
21.051
960751AF2-366 GEN
Solar/Wind Harmer
5.433
962781AG1-127 GEN
Solar/Wind Harmer
18.009
276691AA1-018 GEN1
Solar/Wind Harmer
0.88
274872LEEDK;1U
Solar/Wind Harmer
15.501
939401AE1-172 GEN
Solar/Wind Harmer
25.979
270055AF2-134 C O1
Solar/Wind Harmer
5.646
276861AD2-134 GEN
Solar/Wind Harmer
3.32
276901AD2-066 C O1
Solar/Wind Harmer
6.528
971997AH1-543 GEN
Solar/Wind Harmer
29.157
957471AF2-041 GEN
Solar/Wind Harmer
55.208
959081AF2-199 GEN
Solar/Wind Harmer
18.403
971067AG2-660 GEN
Solar/Wind Harmer
4.28
274822ROCKFORD ;11
Adder
35.93
958381AF2-132 GEN
Solar/Wind Harmer
16.565
972235AH1-702 GEN1
Adder
4.598
964861AG1-349 GEN
Solar/Wind Harmer
14.321
971917AH1-482 GEN
Solar/Wind Harmer
16.527
970819AG2-516 GEN
Solar/Wind Harmer
21.782
276876AE1-163_GEN2
Solar/Wind Harmer
12.169
971475AH1-234 GEN
Solar/Wind Harmer
40.498
274857EASY ROAD;U1
Solar/Wind Harmer
8.544
274761LEE CO EC;2U
Adder
16.587
274766LEE CO EC;7U
Adder
16.391
970569AG2-363 GEN
Solar/Wind Harmer
53.405
940581AE2-045 GEN
Solar/Wind Harmer
18.087
971605AH1-302 GEN
Solar/Wind Harmer
15.466
270505AE1-170 C O1
Solar/Wind Harmer
26.304
276158O29GEN2
Solar/Wind Harmer
8.731
24639705ELKHART HY
Adder
0.227
274887GEN-1.85
Solar/Wind Harmer
10.531
276843GEN-1.7
Solar/Wind Harmer
1.133
958011AF2-095 GEN
Solar/Wind Harmer
28.45
274803UNIV PARK;6U
Adder
11.473
274847GR RIDGE ;BU
Solar/Wind Harmer
9.927
274808UNIV PK N;4U
Adder
9.784
274674JOLIET 9 ;6U
Adder
30.161
971573AH1-285 GEN
Solar/Wind Harmer
16.743
274695ROCKY RD ;2P
Adder
21.355
274693ROCKY RD ;1P
Adder
21.145
274697ROCKY RD ;3P
Adder
5.801
274696ROCKY RD ;4P
Adder
21.858
274683WAUKEGAN ;8U
Adder
40.16
274683WAUKEGAN ;8U
Adder
33.853
24441505OLIV SLR
Solar/Wind Harmer
0.255
962691AG1-118 GEN
Solar/Wind Harmer
57.021
970921AG2-575 GEN
Solar/Wind Harmer
18.937
970921AG2-575 GEN
Solar/Wind Harmer
4.404
958481AF2-142 GEN
Solar/Wind Harmer
28.358
274861TOP CROP ;1U
Solar/Wind Harmer
11.442
274862TOP CROP ;2U
Solar/Wind Harmer
9.555
270526AF1-158 GEN
Solar/Wind Harmer
8.548
942991AE2-321 GEN
Solar/Wind Harmer
18.7
958491AF2-143 GEN
Solar/Wind Harmer
27.862
971333AH1-146 GEN
Solar/Wind Harmer
37.128
971335AH1-147 GEN
Solar/Wind Harmer
37.128
274879MINONK ;1U
Solar/Wind Harmer
12.48
971341AH1-150 GEN
Solar/Wind Harmer
36.805
971343AH1-151 GEN
Solar/Wind Harmer
36.805
276872AE1-163_GEN1
Solar/Wind Harmer
12.169
274856ECOGROVE ;U1
Solar/Wind Harmer
6.108
276611AD2-172 GEN
Solar/Wind Harmer
4.635
938861AE1-114 GEN
Solar/Wind Harmer
14.698
274764LEE CO EC;5U
Adder
16.626
274765LEE CO EC;6U
Adder
16.626
274762LEE CO EC;3U
Adder
16.587
274763LEE CO EC;4U
Adder
16.431
276603SUBLETTE C
Solar/Wind Harmer
1.866
972267AH1-718 GEN
Adder
7.31
247620Y3-023
Adder
0.618
276741O09 GEN1
Solar/Wind Harmer
0.535
276708O09 GEN2
Solar/Wind Harmer
0.535
274864CRW2-WTG
Solar/Wind Harmer
10.138
276612AE2-035 GEN
Solar/Wind Harmer
4.635
958391AF2-133 GEN
Solar/Wind Harmer
16.387
971771AH1-392 GEN
Solar/Wind Harmer
16.165
971681AH1-341 GEN
Solar/Wind Harmer
26.907
926823AC1-168 GEN
Solar/Wind Harmer
7.68
970169AG2-114 GEN
Solar/Wind Harmer
17.668
961011AF2-392 GEN
Solar/Wind Harmer
19.169
274772LINCOLN ;3U
50/50
13.854
970513AG2-328 GEN
Solar/Wind Harmer
47.9
970517AG2-330 GEN
Solar/Wind Harmer
43.444
970349AG2-230 GEN
Solar/Wind Harmer
33.33
970707AG2-453 GEN
Solar/Wind Harmer
56.957
972228AH1-698 GEN2
Adder
7.345
274724RIVER EC ;11
Adder
35.049
276897AD1-100 C
Solar/Wind Harmer
57.396
939351AE1-166 GEN
Solar/Wind Harmer
11.728
276772AC2-154 GEN
Solar/Wind Harmer
5.51
276806AD2-047 C O1
Solar/Wind Harmer
21.135
970941AG2-585 GEN
Solar/Wind Harmer
24.696
274826FISK ;BP
Adder
21.584
274800UNIV PARK;3U
Adder
11.489
972038AH1-567 GEN2
Adder
0.719
274802UNIV PARK;5U
Adder
11.473
943121AE2-341 GEN
Solar/Wind Harmer
29.466
943591AF1-030 GEN
Solar/Wind Harmer
19.644
274676JOLIET 29;8U
Adder
58.067
274729ELWOOD EC;1P
Adder
32.123
274730ELWOOD EC;6P
Adder
32.123
274734ELWOOD EC;8P
Adder
32.123
274736ELWOOD EC;9P
Adder
32.123
972231SS25-0005
Solar/Wind Harmer
18.548
972181SS23-001
Solar/Wind Harmer
11.593
274752CRETE EC ;2U
Adder
9.553
274753CRETE EC ;3U
Adder
9.553
276893AG1-478 C
Solar/Wind Harmer
0.814
274682WAUKEGAN ;7U
Adder
34.314
276694AA1-018 GEN2
Solar/Wind Harmer
11.931
274872LEEDK;1U
Solar/Wind Harmer
0.483
270535AF1-215 GEN1
Solar/Wind Harmer
8.469
276799AD1-013 GEN
Solar/Wind Harmer
4.114
946671AF1-331 GEN
Solar/Wind Harmer
0.779
274855GSG-6 ;RU
Solar/Wind Harmer
6.865
274850MENDOTA H;RU
Solar/Wind Harmer
4.773
276602WESTBROOK C
Solar/Wind Harmer
3.951
276863AD2-134 GEN
Solar/Wind Harmer
3.32
276805AD2-038 GEN
Solar/Wind Harmer
9.529
959091AF2-200 GEN
Solar/Wind Harmer
36.805
964401AG1-302 GEN
Solar/Wind Harmer
16.565
972236AH1-702 GEN2
Adder
3.998
276889AE2-281 GEN
Solar/Wind Harmer
3.477
959141AF2-205 GEN
Solar/Wind Harmer
10.832
274858EASY ROAD;U2
Solar/Wind Harmer
8.544
274760LEE CO EC;1U
Adder
16.587
274767LEE CO EC;8U
Adder
16.391
24642205MAYFLWER
Adder
1.132
970571AG2-364 GEN
Solar/Wind Harmer
35.603
247604X1-042
Adder
0.731
24441205WTRV SLR C
Solar/Wind Harmer
0.236
276157O29GEN1
Solar/Wind Harmer
6.641
NYPJM->LTFIMP_NY
CLTF
2.657
LGEELTFEXP_LGEE->PJM
CLTF
0.941
WECLTFEXP_WEC->PJM
CLTF
6.943
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.156
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.137
AG2-052LTFEXP_AG2-052->PJM
LTF
0.405
AH1-155LTFEXP_AH1-155->PJM
LTF
0.608
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.554
CBM West 1LTFEXP_CBM-W1->PJM
CBM
189.664
CBM South 1LTFEXP_CBM-S1->PJM
CBM
10.331
MECLTFEXP_MEC->PJM
CLTF
23.481
SIGELTFEXP_SIGE->PJM
CLTF
0.228
LAGNLTFEXP_LAGN->PJM
CLTF
9.743
TVALTFEXP_TVA->PJM
CLTF
3.055

Details for 05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line l/o AEP_P7-1_#11001___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RS-05SORENS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11001___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.47 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5659.45
MW Contribution:20.57
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
13.001
274771LINCOLN ;2U
50/50
13.001
270102X2-052 ST
50/50
3.099
270100X2-052 CT1
50/50
2.855
270101X2-052 CT2
50/50
2.855
274661LASCO STA;2U
50/50
13.59
972259AH1-714 GEN
50/50
38.145
274660LASCO STA;1U
50/50
13.764
970321AG2-212 GEN
Solar/Wind Harmer
41.418
965681AG1-436 GEN
Solar/Wind Harmer
23.931
965791AG1-447 GEN
Solar/Wind Harmer
12.244
274888KELLY CRK;1U
Solar/Wind Harmer
10.983
274887GEN-1.85
Solar/Wind Harmer
9.915
276843GEN-1.7
Solar/Wind Harmer
1.067
958011AF2-095 GEN
Solar/Wind Harmer
26.787
274803UNIV PARK;6U
Adder
10.803
274808UNIV PK N;4U
Adder
9.211
274847GR RIDGE ;BU
Solar/Wind Harmer
9.343
274674JOLIET 9 ;6U
Adder
28.4
971573AH1-285 GEN
Solar/Wind Harmer
15.764
24441505OLIV SLR
Solar/Wind Harmer
0.244
270526AF1-158 GEN
Solar/Wind Harmer
8.225
274695ROCKY RD ;2P
Adder
20.121
274693ROCKY RD ;1P
Adder
19.923
274697ROCKY RD ;3P
Adder
5.466
274696ROCKY RD ;4P
Adder
20.595
274683WAUKEGAN ;8U
Adder
37.851
274683WAUKEGAN ;8U
Adder
31.907
962691AG1-118 GEN
Solar/Wind Harmer
53.744
970921AG2-575 GEN
Solar/Wind Harmer
17.851
970921AG2-575 GEN
Solar/Wind Harmer
4.151
958481AF2-142 GEN
Solar/Wind Harmer
26.742
274861TOP CROP ;1U
Solar/Wind Harmer
10.791
274862TOP CROP ;2U
Solar/Wind Harmer
9.011
942991AE2-321 GEN
Solar/Wind Harmer
17.638
958491AF2-143 GEN
Solar/Wind Harmer
26.292
971333AH1-146 GEN
Solar/Wind Harmer
35.031
971335AH1-147 GEN
Solar/Wind Harmer
35.031
274879MINONK ;1U
Solar/Wind Harmer
11.778
274772LINCOLN ;3U
50/50
13.001
24344005CKG1
50/50
12.388
970513AG2-328 GEN
Solar/Wind Harmer
41.418
24344105CKG2
50/50
18.73
274773LINCOLN ;4U
50/50
13.001
274774LINCOLN ;5U
50/50
13.001
970245AG2-165 GEN
Solar/Wind Harmer
41.418
972207SS24-0001
Solar/Wind Harmer
43.561
276164X3-005 C
Solar/Wind Harmer
1.314
274723RIVER EC ;12
Adder
33.414
941551AE2-152 GEN
Solar/Wind Harmer
8.44
276776AD2-060 GEN
Solar/Wind Harmer
0.786
274801UNIV PARK;4U
Adder
10.821
274676JOLIET 29;8U
Adder
56.696
274812UNIV PK N;8U
Adder
9.252
274871GR RIDGE ;2U
Solar/Wind Harmer
14.204
274674JOLIET 9 ;6U
Adder
28.4
274732ELWOOD EC;7P
Adder
30.247
274751CRETE EC ;1U
Adder
8.994
274754CRETE EC ;4U
Adder
8.994
274745AC1-111 GEN9
Adder
10.278
274682WAUKEGAN ;7U
Adder
32.339
274828WAUKEGAN ;BP
Adder
19.841
960751AF2-366 GEN
Solar/Wind Harmer
5.122
962781AG1-127 GEN
Solar/Wind Harmer
16.977
276691AA1-018 GEN1
Solar/Wind Harmer
0.83
274872LEEDK;1U
Solar/Wind Harmer
14.615
939401AE1-172 GEN
Solar/Wind Harmer
24.491
276861AD2-134 GEN
Solar/Wind Harmer
3.132
276901AD2-066 C O1
Solar/Wind Harmer
6.158
971997AH1-543 GEN
Solar/Wind Harmer
27.509
970373AG2-245 GEN
Solar/Wind Harmer
36.682
957471AF2-041 GEN
Solar/Wind Harmer
52.109
959081AF2-199 GEN
Solar/Wind Harmer
17.37
971067AG2-660 GEN
Solar/Wind Harmer
4.039
274822ROCKFORD ;11
Adder
33.922
972235AH1-702 GEN1
Adder
4.342
970819AG2-516 GEN
Solar/Wind Harmer
20.573
276876AE1-163_GEN2
Solar/Wind Harmer
11.495
971475AH1-234 GEN
Solar/Wind Harmer
38.256
270505AE1-170 C O1
Solar/Wind Harmer
25.403
274857EASY ROAD;U1
Solar/Wind Harmer
8.076
274761LEE CO EC;2U
Adder
15.678
274766LEE CO EC;7U
Adder
15.494
970569AG2-363 GEN
Solar/Wind Harmer
50.484
270055AF2-134 C O1
Solar/Wind Harmer
5.07
270449AD2-020 GEN
Solar/Wind Harmer
4.651
943021AE2-325 GEN
Solar/Wind Harmer
6.043
276158O29GEN2
Solar/Wind Harmer
8.26
274877BISHOP HL;1U
Solar/Wind Harmer
5.463
24639705ELKHART HY
Adder
0.212
270349AD2-093_GEN
Solar/Wind Helper
1.321
958381AF2-132 GEN
Solar/Wind Harmer
11.606
274775LINCOLN ;6U
50/50
13.001
274776LINCOLN ;7U
50/50
13.001
274777LINCOLN ;8U
50/50
13.001
971599AH1-298 GEN
50/50
16.711
971347AH1-153 GEN
Solar/Wind Harmer
33.189
960681AF2-359 GEN
Solar/Wind Harmer
7.233
972227AH1-698 GEN1
Adder
4.866
960591AF2-350 GEN
Solar/Wind Harmer
18.602
274827FISK ;RP
Adder
14.408
972037AH1-567 GEN1
Adder
0.339
274675JOLIET 29;7U
Adder
56.698
274675JOLIET 29;7U
Adder
54.673
970833AG2-524 GEN
Solar/Wind Harmer
16.131
970833AG2-524 GEN
Solar/Wind Harmer
7.503
274687WILL CNTY;4U
Adder
51.628
274687WILL CNTY;4U
Adder
51.628
274814UNIV PK N;0U
Adder
9.333
274807UNIV PK N;3U
Adder
9.312
274805UNIV PK N;1U
Adder
9.272
274811UNIV PK N;7U
Adder
9.252
274731ELWOOD EC;2P
Adder
30.248
274733ELWOOD EC;3P
Adder
30.248
274735ELWOOD EC;4P
Adder
30.248
274728ELWOOD EC;5P
Adder
30.247
274746AC1-111 G10
Adder
10.278
274744AC1-111 GEN8
Adder
10.278
971769AH1-391 GEN
Solar/Wind Harmer
18.249
971177AH1-047 GEN
Solar/Wind Harmer
10.33
971675AH1-338 GEN
Solar/Wind Harmer
31.578
971411AH1-196 GEN
Solar/Wind Harmer
26.291
971771AH1-392 GEN
Solar/Wind Harmer
15.753
276868AE1-113 GEN
Solar/Wind Harmer
17.665
276882AE2-255 GEN
Solar/Wind Harmer
5.889
971171AH1-044 GEN
Solar/Wind Harmer
34.74
274823ROCKFORD ;21
Adder
33.676
274863CRW1-WTG
Solar/Wind Harmer
9.567
274864CRW2-WTG
Solar/Wind Harmer
9.567
276612AE2-035 GEN
Solar/Wind Harmer
4.378
971681AH1-341 GEN
Solar/Wind Harmer
25.426
926823AC1-168 GEN
Solar/Wind Harmer
7.256
270536AF1-215 GEN2
Solar/Wind Harmer
7.607
970169AG2-114 GEN
Solar/Wind Harmer
16.689
961011AF2-392 GEN
Solar/Wind Harmer
18.128
944161AF1-084 GEN
Solar/Wind Harmer
3.666
957751AF2-069 GEN
Solar/Wind Harmer
0.748
971341AH1-150 GEN
Solar/Wind Harmer
34.74
971343AH1-151 GEN
Solar/Wind Harmer
34.74
276872AE1-163_GEN1
Solar/Wind Harmer
11.495
274856ECOGROVE ;U1
Solar/Wind Harmer
5.769
276611AD2-172 GEN
Solar/Wind Harmer
4.378
938861AE1-114 GEN
Solar/Wind Harmer
13.889
274764LEE CO EC;5U
Adder
15.715
274765LEE CO EC;6U
Adder
15.715
274762LEE CO EC;3U
Adder
15.678
274763LEE CO EC;4U
Adder
15.531
276603SUBLETTE C
Solar/Wind Harmer
1.764
957891AF2-083 GEN
Solar/Wind Harmer
5.61
972267AH1-718 GEN
Adder
6.915
960981AF2-389 GEN
Solar/Wind Harmer
2.508
276741O09 GEN1
Solar/Wind Harmer
5.9
276708O09 GEN2
Solar/Wind Harmer
5.9
961051AF2-396 GEN
Solar/Wind Harmer
25.906
961051AF2-396 GEN
Solar/Wind Harmer
12.049
274851PROVIDENC;RU
Solar/Wind Harmer
4.642
274849CRESCENT ;1U
Solar/Wind Harmer
3.014
276645AC1-214 GEN1
Solar/Wind Harmer
2.183
276646AC1-214 GEN2
Solar/Wind Harmer
2.183
276782AC1-033 GEN
Solar/Wind Harmer
6.456
247620Y3-023
Adder
0.559
270471AD2-092_GEN
Solar/Wind Helper
1.321
970517AG2-330 GEN
Solar/Wind Harmer
37.565
970349AG2-230 GEN
Solar/Wind Harmer
33.189
970707AG2-453 GEN
Solar/Wind Harmer
53.523
274724RIVER EC ;11
Adder
33.067
972228AH1-698 GEN2
Adder
6.911
276897AD1-100 C
Solar/Wind Harmer
54.005
939351AE1-166 GEN
Solar/Wind Harmer
11.035
276772AC2-154 GEN
Solar/Wind Harmer
5.188
276806AD2-047 C O1
Solar/Wind Harmer
19.9
970941AG2-585 GEN
Solar/Wind Harmer
23.253
274826FISK ;BP
Adder
20.33
274800UNIV PARK;3U
Adder
10.821
972038AH1-567 GEN2
Adder
0.677
274802UNIV PARK;5U
Adder
10.803
943121AE2-341 GEN
Solar/Wind Harmer
27.733
943591AF1-030 GEN
Solar/Wind Harmer
18.488
274676JOLIET 29;8U
Adder
54.671
274729ELWOOD EC;1P
Adder
30.248
274730ELWOOD EC;6P
Adder
30.247
274734ELWOOD EC;8P
Adder
30.247
274736ELWOOD EC;9P
Adder
30.247
972231SS25-0005
Solar/Wind Harmer
17.464
972181SS23-001
Solar/Wind Harmer
10.915
274752CRETE EC ;2U
Adder
8.994
274753CRETE EC ;3U
Adder
8.994
276893AG1-478 C
Solar/Wind Harmer
0.767
274682WAUKEGAN ;7U
Adder
32.339
276694AA1-018 GEN2
Solar/Wind Harmer
11.251
274872LEEDK;1U
Solar/Wind Harmer
0.455
276799AD1-013 GEN
Solar/Wind Harmer
3.881
946671AF1-331 GEN
Solar/Wind Harmer
0.735
274855GSG-6 ;RU
Solar/Wind Harmer
6.477
274850MENDOTA H;RU
Solar/Wind Harmer
4.503
276602WESTBROOK C
Solar/Wind Harmer
3.728
276863AD2-134 GEN
Solar/Wind Harmer
3.132
276805AD2-038 GEN
Solar/Wind Harmer
8.992
959091AF2-200 GEN
Solar/Wind Harmer
34.74
972236AH1-702 GEN2
Adder
3.775
24642205MAYFLWER
Adder
1.093
276889AE2-281 GEN
Solar/Wind Harmer
3.284
274858EASY ROAD;U2
Solar/Wind Harmer
8.076
274760LEE CO EC;1U
Adder
15.678
274767LEE CO EC;8U
Adder
15.494
970571AG2-364 GEN
Solar/Wind Harmer
33.656
270535AF1-215 GEN1
Solar/Wind Harmer
7.607
247604X1-042
Adder
0.696
24441205WTRV SLR C
Solar/Wind Harmer
0.225
276157O29GEN1
Solar/Wind Harmer
6.283
274878BISHOP HL;2U
Solar/Wind Harmer
5.463
NYPJM->LTFIMP_NY
CLTF
2.596
LGEELTFEXP_LGEE->PJM
CLTF
1.837
WECLTFEXP_WEC->PJM
CLTF
6.558
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.803
CBM West 2LTFEXP_CBM-W2->PJM
CBM
86.728
AG2-052LTFEXP_AG2-052->PJM
LTF
0.381
AH1-155LTFEXP_AH1-155->PJM
LTF
0.571
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.339
CBM West 1LTFEXP_CBM-W1->PJM
CBM
178.31
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.424
MECLTFEXP_MEC->PJM
CLTF
22.474
SIGELTFEXP_SIGE->PJM
CLTF
0.251
LAGNLTFEXP_LAGN->PJM
CLTF
10.173
TVALTFEXP_TVA->PJM
CLTF
3.448

Details for 05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.6 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5492.34
MW Contribution:31.64
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
22.27
274774LINCOLN ;5U
50/50
22.27
274710KENDALL ;4C
50/50
3.516
274705KENDALL ;1S
50/50
2.163
972207SS24-0001
Solar/Wind Harmer
74.619
274745AC1-111 GEN9
Adder
16.369
274871GR RIDGE ;2U
Solar/Wind Harmer
22.472
941551AE2-152 GEN
Solar/Wind Harmer
13.134
960751AF2-366 GEN
Solar/Wind Harmer
8.072
962781AG1-127 GEN
Solar/Wind Harmer
26.756
274676JOLIET 29;8U
Adder
86.152
274872LEEDK;1U
Solar/Wind Harmer
23.004
274732ELWOOD EC;7P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
274828WAUKEGAN ;BP
Adder
30.754
274674JOLIET 9 ;6U
Adder
42.82
274751CRETE EC ;1U
Adder
13.493
274754CRETE EC ;4U
Adder
13.493
274812UNIV PK N;8U
Adder
13.776
276861AD2-134 GEN
Solar/Wind Harmer
4.891
957471AF2-041 GEN
Solar/Wind Harmer
80.791
959081AF2-199 GEN
Solar/Wind Harmer
26.93
971067AG2-660 GEN
Solar/Wind Harmer
6.263
276776AD2-060 GEN
Solar/Wind Harmer
1.137
971997AH1-543 GEN
Solar/Wind Harmer
42.004
939401AE1-172 GEN
Solar/Wind Harmer
37.187
274822ROCKFORD ;11
Adder
52.349
972235AH1-702 GEN1
Adder
6.693
970819AG2-516 GEN
Solar/Wind Harmer
31.637
276691AA1-018 GEN1
Solar/Wind Harmer
1.223
971475AH1-234 GEN
Solar/Wind Harmer
58.741
276901AD2-066 C O1
Solar/Wind Harmer
9.209
274801UNIV PARK;4U
Adder
15.181
274857EASY ROAD;U1
Solar/Wind Harmer
12.328
274761LEE CO EC;2U
Adder
23.934
274766LEE CO EC;7U
Adder
23.652
276876AE1-163_GEN2
Solar/Wind Harmer
16.854
276158O29GEN2
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
73.878
276164X3-005 C
Solar/Wind Harmer
1.663
274877BISHOP HL;1U
Solar/Wind Harmer
7.982
276726Z2-087_GEN
Solar/Wind Harmer
17.13
939741AE1-205 GEN
Solar/Wind Harmer
43.316
274854TWINGROVE;U2
Solar/Wind Harmer
14.538
274723RIVER EC ;12
Adder
36.664
972175AH1-670 GEN
Solar/Wind Harmer
25.367
274880W4-005 GEN4
Solar/Wind Harmer
5.072
963831AG1-236 GEN
Solar/Wind Harmer
16.191
276615X2-022 GEN
Solar/Wind Harmer
3.121
274770LINCOLN ;1U
50/50
22.27
274771LINCOLN ;2U
50/50
22.27
274709KENDALL ;3S
50/50
2.347
274711KENDALL ;4S
50/50
2.347
274661LASCO STA;2U
50/50
21.82
972259AH1-714 GEN
50/50
61.247
274660LASCO STA;1U
50/50
22.099
971573AH1-285 GEN
Solar/Wind Harmer
25.349
274847GR RIDGE ;BU
Solar/Wind Harmer
14.782
274695ROCKY RD ;2P
Adder
31.631
274693ROCKY RD ;1P
Adder
31.319
274697ROCKY RD ;3P
Adder
8.593
274696ROCKY RD ;4P
Adder
32.374
962691AG1-118 GEN
Solar/Wind Harmer
84.831
970921AG2-575 GEN
Solar/Wind Harmer
28.134
970921AG2-575 GEN
Solar/Wind Harmer
6.543
274683WAUKEGAN ;8U
Adder
58.671
274683WAUKEGAN ;8U
Adder
49.457
274674JOLIET 9 ;6U
Adder
42.82
274808UNIV PK N;4U
Adder
13.716
942991AE2-321 GEN
Solar/Wind Harmer
27.42
971333AH1-146 GEN
Solar/Wind Harmer
54.429
971335AH1-147 GEN
Solar/Wind Harmer
54.429
971341AH1-150 GEN
Solar/Wind Harmer
53.86
971343AH1-151 GEN
Solar/Wind Harmer
53.86
274888KELLY CRK;1U
Solar/Wind Harmer
15.872
274887GEN-1.85
Solar/Wind Harmer
14.329
276843GEN-1.7
Solar/Wind Harmer
1.542
958011AF2-095 GEN
Solar/Wind Harmer
38.712
274803UNIV PARK;6U
Adder
15.613
274861TOP CROP ;1U
Solar/Wind Harmer
15.922
274862TOP CROP ;2U
Solar/Wind Harmer
13.295
274856ECOGROVE ;U1
Solar/Wind Harmer
8.862
276611AD2-172 GEN
Solar/Wind Harmer
6.724
958481AF2-142 GEN
Solar/Wind Harmer
39.387
274879MINONK ;1U
Solar/Wind Harmer
17.567
938861AE1-114 GEN
Solar/Wind Harmer
21.245
958491AF2-143 GEN
Solar/Wind Harmer
38.653
274764LEE CO EC;5U
Adder
23.99
274765LEE CO EC;6U
Adder
23.99
274762LEE CO EC;3U
Adder
23.934
274763LEE CO EC;4U
Adder
23.708
276603SUBLETTE C
Solar/Wind Harmer
2.688
972267AH1-718 GEN
Adder
10.486
276872AE1-163_GEN1
Solar/Wind Harmer
16.854
276741O09 GEN1
Solar/Wind Harmer
8.861
276708O09 GEN2
Solar/Wind Harmer
8.861
274851PROVIDENC;RU
Solar/Wind Harmer
6.782
274849CRESCENT ;1U
Solar/Wind Harmer
4.403
276645AC1-214 GEN1
Solar/Wind Harmer
3.19
276646AC1-214 GEN2
Solar/Wind Harmer
3.19
276782AC1-033 GEN
Solar/Wind Harmer
9.432
960611AF2-352 GEN
Solar/Wind Harmer
4.791
276763AC1-053 GEN1
Solar/Wind Harmer
6.509
276764AC1-053 GEN2
Solar/Wind Harmer
6.509
274772LINCOLN ;3U
50/50
22.27
274707KENDALL ;2S
50/50
2.163
970707AG2-453 GEN
Solar/Wind Harmer
89.854
943121AE2-341 GEN
Solar/Wind Harmer
44.875
943591AF1-030 GEN
Solar/Wind Harmer
29.917
276897AD1-100 C
Solar/Wind Harmer
84.043
939351AE1-166 GEN
Solar/Wind Harmer
17.172
972228AH1-698 GEN2
Adder
10.617
274676JOLIET 29;8U
Adder
83.076
274872LEEDK;1U
Solar/Wind Harmer
0.716
274729ELWOOD EC;1P
Adder
45.944
274730ELWOOD EC;6P
Adder
45.935
274734ELWOOD EC;8P
Adder
45.935
274736ELWOOD EC;9P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
972231SS25-0005
Solar/Wind Harmer
26.198
972181SS23-001
Solar/Wind Harmer
16.374
274752CRETE EC ;2U
Adder
13.493
274753CRETE EC ;3U
Adder
13.493
276799AD1-013 GEN
Solar/Wind Harmer
6.064
946671AF1-331 GEN
Solar/Wind Harmer
1.148
274855GSG-6 ;RU
Solar/Wind Harmer
10.113
274850MENDOTA H;RU
Solar/Wind Harmer
7.032
276602WESTBROOK C
Solar/Wind Harmer
5.821
276863AD2-134 GEN
Solar/Wind Harmer
4.891
276893AG1-478 C
Solar/Wind Harmer
1.142
959091AF2-200 GEN
Solar/Wind Harmer
53.86
276772AC2-154 GEN
Solar/Wind Harmer
7.497
276806AD2-047 C O1
Solar/Wind Harmer
28.759
970941AG2-585 GEN
Solar/Wind Harmer
33.604
274802UNIV PARK;5U
Adder
15.613
972236AH1-702 GEN2
Adder
5.82
276694AA1-018 GEN2
Solar/Wind Harmer
16.571
274800UNIV PARK;3U
Adder
15.181
972038AH1-567 GEN2
Adder
0.95
274826FISK ;BP
Adder
28.388
276805AD2-038 GEN
Solar/Wind Harmer
13.219
274858EASY ROAD;U2
Solar/Wind Harmer
12.328
274760LEE CO EC;1U
Adder
23.934
274767LEE CO EC;8U
Adder
23.652
276889AE2-281 GEN
Solar/Wind Harmer
4.816
276157O29GEN1
Solar/Wind Harmer
9.436
970571AG2-364 GEN
Solar/Wind Harmer
49.252
274878BISHOP HL;2U
Solar/Wind Harmer
7.982
965931AG1-462 GEN
Solar/Wind Harmer
59.553
942111AE2-223 GEN
Solar/Wind Harmer
17.755
274724RIVER EC ;11
Adder
36.677
274853TWINGROVE;U1
Solar/Wind Harmer
14.849
965091AG1-374 GEN
Solar/Wind Harmer
61.805
959611AF2-252 GEN
Solar/Wind Harmer
4.791
276686W4-005 GEN3
Solar/Wind Harmer
5.072
971993AH1-541 GEN
Solar/Wind Harmer
15.492
274775LINCOLN ;6U
50/50
22.27
274776LINCOLN ;7U
50/50
22.27
274777LINCOLN ;8U
50/50
22.27
274708KENDALL ;3C
50/50
3.543
274704KENDALL ;1C
50/50
3.239
274706KENDALL ;2C
50/50
3.239
274746AC1-111 G10
Adder
16.369
274744AC1-111 GEN8
Adder
16.369
970833AG2-524 GEN
Solar/Wind Harmer
25.435
970833AG2-524 GEN
Solar/Wind Harmer
11.83
972227AH1-698 GEN1
Adder
7.478
274675JOLIET 29;7U
Adder
86.159
274675JOLIET 29;7U
Adder
83.082
274731ELWOOD EC;2P
Adder
45.944
274733ELWOOD EC;3P
Adder
45.944
274735ELWOOD EC;4P
Adder
45.944
274728ELWOOD EC;5P
Adder
45.935
274687WILL CNTY;4U
Adder
77.13
274687WILL CNTY;4U
Adder
77.13
274814UNIV PK N;0U
Adder
13.897
274807UNIV PK N;3U
Adder
13.867
274805UNIV PK N;1U
Adder
13.806
274811UNIV PK N;7U
Adder
13.776
971177AH1-047 GEN
Solar/Wind Harmer
16.058
971675AH1-338 GEN
Solar/Wind Harmer
49.322
971411AH1-196 GEN
Solar/Wind Harmer
40.764
971171AH1-044 GEN
Solar/Wind Harmer
53.86
960591AF2-350 GEN
Solar/Wind Harmer
26.883
972037AH1-567 GEN1
Adder
0.49
274823ROCKFORD ;21
Adder
51.969
276612AE2-035 GEN
Solar/Wind Harmer
6.724
276868AE1-113 GEN
Solar/Wind Harmer
26.349
276882AE2-255 GEN
Solar/Wind Harmer
8.784
971681AH1-341 GEN
Solar/Wind Harmer
38.904
274827FISK ;RP
Adder
20.119
274863CRW1-WTG
Solar/Wind Harmer
14.274
274864CRW2-WTG
Solar/Wind Harmer
14.274
961011AF2-392 GEN
Solar/Wind Harmer
27.512
926823AC1-168 GEN
Solar/Wind Harmer
10.809
970169AG2-114 GEN
Solar/Wind Harmer
24.498
957751AF2-069 GEN
Solar/Wind Harmer
1.093
946321AF1-296 GEN
Solar/Wind Harmer
24.654
274848CAMPGROVE;RU
Solar/Wind Harmer
15.052
276655WTG1_EQ
Solar/Wind Harmer
18.909
276656WTG2_EQ
Solar/Wind Harmer
2.504
959341AF2-225 GEN
Solar/Wind Harmer
32.487
941731AE2-173 GEN
Solar/Wind Harmer
12.592
276785W4-005 GEN1
Solar/Wind Harmer
5.072
276174W4-005 GEN2
Solar/Wind Harmer
5.072
276849AB2-070 GEN2
Solar/Wind Harmer
3.758
276848AB2-070 GEN3
Solar/Wind Harmer
3.758
276668AB2-070 GEN1
Solar/Wind Harmer
3.758
276621W2-048 GEN
Solar/Wind Harmer
9.939
276838X2-022 GEN2
Solar/Wind Harmer
0.371
990512J1326
External Queue
13.405387878417969
990727J1377 G
External Queue
9.246102333068848
991092J1477
External Queue
7.122580528259277
990407J1304
External Queue
10.39168643951416
NYPJM->LTFIMP_NY
CLTF
2.49
WECLTFEXP_WEC->PJM
CLTF
10.032
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.996
AG2-052LTFEXP_AG2-052->PJM
LTF
0.071
AH1-155LTFEXP_AH1-155->PJM
LTF
0.107
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
166.639
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.837
MECLTFEXP_MEC->PJM
CLTF
31.333
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.433
LAGNLTFEXP_LAGN->PJM
CLTF
10.191
TVALTFEXP_TVA->PJM
CLTF
2.55

Details for 05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:130.85 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5419.75
MW Contribution:31.64
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
22.27
274774LINCOLN ;5U
50/50
22.27
274710KENDALL ;4C
50/50
3.516
274705KENDALL ;1S
50/50
2.163
972207SS24-0001
Solar/Wind Harmer
74.619
274745AC1-111 GEN9
Adder
16.369
274871GR RIDGE ;2U
Solar/Wind Harmer
22.472
941551AE2-152 GEN
Solar/Wind Harmer
13.134
960751AF2-366 GEN
Solar/Wind Harmer
8.072
962781AG1-127 GEN
Solar/Wind Harmer
26.756
274676JOLIET 29;8U
Adder
86.152
274872LEEDK;1U
Solar/Wind Harmer
23.004
274732ELWOOD EC;7P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
274828WAUKEGAN ;BP
Adder
30.754
274674JOLIET 9 ;6U
Adder
42.82
274812UNIV PK N;8U
Adder
13.776
276861AD2-134 GEN
Solar/Wind Harmer
4.891
957471AF2-041 GEN
Solar/Wind Harmer
80.791
959081AF2-199 GEN
Solar/Wind Harmer
26.93
971067AG2-660 GEN
Solar/Wind Harmer
6.263
276776AD2-060 GEN
Solar/Wind Harmer
1.137
971997AH1-543 GEN
Solar/Wind Harmer
42.004
939401AE1-172 GEN
Solar/Wind Harmer
37.187
274822ROCKFORD ;11
Adder
52.349
972235AH1-702 GEN1
Adder
6.693
970819AG2-516 GEN
Solar/Wind Harmer
31.637
276691AA1-018 GEN1
Solar/Wind Harmer
1.223
971475AH1-234 GEN
Solar/Wind Harmer
58.741
276901AD2-066 C O1
Solar/Wind Harmer
9.209
274801UNIV PARK;4U
Adder
15.181
274857EASY ROAD;U1
Solar/Wind Harmer
12.328
274761LEE CO EC;2U
Adder
23.934
274766LEE CO EC;7U
Adder
23.652
276876AE1-163_GEN2
Solar/Wind Harmer
16.854
276158O29GEN2
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
73.878
276164X3-005 C
Solar/Wind Harmer
1.663
274877BISHOP HL;1U
Solar/Wind Harmer
7.982
276726Z2-087_GEN
Solar/Wind Harmer
17.13
939741AE1-205 GEN
Solar/Wind Harmer
43.316
274854TWINGROVE;U2
Solar/Wind Harmer
14.538
274723RIVER EC ;12
Adder
36.664
972175AH1-670 GEN
Solar/Wind Harmer
25.367
274880W4-005 GEN4
Solar/Wind Harmer
5.072
963831AG1-236 GEN
Solar/Wind Harmer
16.191
276615X2-022 GEN
Solar/Wind Harmer
3.121
274770LINCOLN ;1U
50/50
22.27
274771LINCOLN ;2U
50/50
22.27
274709KENDALL ;3S
50/50
2.347
274711KENDALL ;4S
50/50
2.347
274661LASCO STA;2U
50/50
21.82
972259AH1-714 GEN
50/50
61.247
274660LASCO STA;1U
50/50
22.099
971573AH1-285 GEN
Solar/Wind Harmer
25.349
274847GR RIDGE ;BU
Solar/Wind Harmer
14.782
274695ROCKY RD ;2P
Adder
31.631
274693ROCKY RD ;1P
Adder
31.319
274697ROCKY RD ;3P
Adder
8.593
274696ROCKY RD ;4P
Adder
32.374
962691AG1-118 GEN
Solar/Wind Harmer
84.831
970921AG2-575 GEN
Solar/Wind Harmer
28.134
970921AG2-575 GEN
Solar/Wind Harmer
6.543
274683WAUKEGAN ;8U
Adder
58.671
274683WAUKEGAN ;8U
Adder
49.457
274674JOLIET 9 ;6U
Adder
42.82
274808UNIV PK N;4U
Adder
13.716
942991AE2-321 GEN
Solar/Wind Harmer
27.42
971333AH1-146 GEN
Solar/Wind Harmer
54.429
971335AH1-147 GEN
Solar/Wind Harmer
54.429
971341AH1-150 GEN
Solar/Wind Harmer
53.86
971343AH1-151 GEN
Solar/Wind Harmer
53.86
274888KELLY CRK;1U
Solar/Wind Harmer
15.872
274887GEN-1.85
Solar/Wind Harmer
14.329
276843GEN-1.7
Solar/Wind Harmer
1.542
958011AF2-095 GEN
Solar/Wind Harmer
38.712
274803UNIV PARK;6U
Adder
15.613
274861TOP CROP ;1U
Solar/Wind Harmer
15.922
274862TOP CROP ;2U
Solar/Wind Harmer
13.295
274856ECOGROVE ;U1
Solar/Wind Harmer
8.862
276611AD2-172 GEN
Solar/Wind Harmer
6.724
958481AF2-142 GEN
Solar/Wind Harmer
39.387
274879MINONK ;1U
Solar/Wind Harmer
17.567
938861AE1-114 GEN
Solar/Wind Harmer
21.245
958491AF2-143 GEN
Solar/Wind Harmer
38.653
274764LEE CO EC;5U
Adder
23.99
274765LEE CO EC;6U
Adder
23.99
274762LEE CO EC;3U
Adder
23.934
274763LEE CO EC;4U
Adder
23.708
276603SUBLETTE C
Solar/Wind Harmer
2.688
972267AH1-718 GEN
Adder
10.486
276872AE1-163_GEN1
Solar/Wind Harmer
16.854
276741O09 GEN1
Solar/Wind Harmer
8.861
276708O09 GEN2
Solar/Wind Harmer
8.861
274851PROVIDENC;RU
Solar/Wind Harmer
6.782
274849CRESCENT ;1U
Solar/Wind Harmer
4.403
276645AC1-214 GEN1
Solar/Wind Harmer
3.19
276646AC1-214 GEN2
Solar/Wind Harmer
3.19
276782AC1-033 GEN
Solar/Wind Harmer
9.432
960611AF2-352 GEN
Solar/Wind Harmer
4.791
276763AC1-053 GEN1
Solar/Wind Harmer
6.509
276764AC1-053 GEN2
Solar/Wind Harmer
6.509
274775LINCOLN ;6U
50/50
22.27
274776LINCOLN ;7U
50/50
22.27
274777LINCOLN ;8U
50/50
22.27
274708KENDALL ;3C
50/50
3.543
274704KENDALL ;1C
50/50
3.239
274706KENDALL ;2C
50/50
3.239
274746AC1-111 G10
Adder
16.369
274744AC1-111 GEN8
Adder
16.369
970833AG2-524 GEN
Solar/Wind Harmer
25.435
970833AG2-524 GEN
Solar/Wind Harmer
11.83
972227AH1-698 GEN1
Adder
7.478
274675JOLIET 29;7U
Adder
86.159
274675JOLIET 29;7U
Adder
83.082
274731ELWOOD EC;2P
Adder
45.944
274733ELWOOD EC;3P
Adder
45.944
274735ELWOOD EC;4P
Adder
45.944
274728ELWOOD EC;5P
Adder
45.935
274687WILL CNTY;4U
Adder
77.13
274687WILL CNTY;4U
Adder
77.13
274814UNIV PK N;0U
Adder
13.897
274807UNIV PK N;3U
Adder
13.867
274805UNIV PK N;1U
Adder
13.806
274811UNIV PK N;7U
Adder
13.776
971177AH1-047 GEN
Solar/Wind Harmer
16.058
971675AH1-338 GEN
Solar/Wind Harmer
49.322
971411AH1-196 GEN
Solar/Wind Harmer
40.764
971171AH1-044 GEN
Solar/Wind Harmer
53.86
960591AF2-350 GEN
Solar/Wind Harmer
26.883
972037AH1-567 GEN1
Adder
0.49
274823ROCKFORD ;21
Adder
51.969
276612AE2-035 GEN
Solar/Wind Harmer
6.724
274772LINCOLN ;3U
50/50
22.27
274707KENDALL ;2S
50/50
2.163
970707AG2-453 GEN
Solar/Wind Harmer
89.854
943121AE2-341 GEN
Solar/Wind Harmer
44.875
943591AF1-030 GEN
Solar/Wind Harmer
29.917
276897AD1-100 C
Solar/Wind Harmer
84.043
939351AE1-166 GEN
Solar/Wind Harmer
17.172
972228AH1-698 GEN2
Adder
10.617
274676JOLIET 29;8U
Adder
83.076
274872LEEDK;1U
Solar/Wind Harmer
0.716
274729ELWOOD EC;1P
Adder
45.944
274730ELWOOD EC;6P
Adder
45.935
274734ELWOOD EC;8P
Adder
45.935
274736ELWOOD EC;9P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
276799AD1-013 GEN
Solar/Wind Harmer
6.064
946671AF1-331 GEN
Solar/Wind Harmer
1.148
274855GSG-6 ;RU
Solar/Wind Harmer
10.113
274850MENDOTA H;RU
Solar/Wind Harmer
7.032
276602WESTBROOK C
Solar/Wind Harmer
5.821
276863AD2-134 GEN
Solar/Wind Harmer
4.891
276893AG1-478 C
Solar/Wind Harmer
1.142
959091AF2-200 GEN
Solar/Wind Harmer
53.86
276772AC2-154 GEN
Solar/Wind Harmer
7.497
276806AD2-047 C O1
Solar/Wind Harmer
28.759
970941AG2-585 GEN
Solar/Wind Harmer
33.604
274802UNIV PARK;5U
Adder
15.613
972236AH1-702 GEN2
Adder
5.82
276694AA1-018 GEN2
Solar/Wind Harmer
16.571
274800UNIV PARK;3U
Adder
15.181
972038AH1-567 GEN2
Adder
0.95
274826FISK ;BP
Adder
28.388
276805AD2-038 GEN
Solar/Wind Harmer
13.219
274858EASY ROAD;U2
Solar/Wind Harmer
12.328
274760LEE CO EC;1U
Adder
23.934
274767LEE CO EC;8U
Adder
23.652
276889AE2-281 GEN
Solar/Wind Harmer
4.816
276157O29GEN1
Solar/Wind Harmer
9.436
970571AG2-364 GEN
Solar/Wind Harmer
49.252
274878BISHOP HL;2U
Solar/Wind Harmer
7.982
965931AG1-462 GEN
Solar/Wind Harmer
59.553
942111AE2-223 GEN
Solar/Wind Harmer
17.755
274724RIVER EC ;11
Adder
36.677
274853TWINGROVE;U1
Solar/Wind Harmer
14.849
965091AG1-374 GEN
Solar/Wind Harmer
61.805
959611AF2-252 GEN
Solar/Wind Harmer
4.791
276686W4-005 GEN3
Solar/Wind Harmer
5.072
971993AH1-541 GEN
Solar/Wind Harmer
15.492
276668AB2-070 GEN1
Solar/Wind Harmer
3.758
276621W2-048 GEN
Solar/Wind Harmer
9.939
276838X2-022 GEN2
Solar/Wind Harmer
0.371
276868AE1-113 GEN
Solar/Wind Harmer
26.349
276882AE2-255 GEN
Solar/Wind Harmer
8.784
971681AH1-341 GEN
Solar/Wind Harmer
38.904
274827FISK ;RP
Adder
20.119
274863CRW1-WTG
Solar/Wind Harmer
14.274
274864CRW2-WTG
Solar/Wind Harmer
14.274
961011AF2-392 GEN
Solar/Wind Harmer
27.512
926823AC1-168 GEN
Solar/Wind Harmer
10.809
970169AG2-114 GEN
Solar/Wind Harmer
24.498
957751AF2-069 GEN
Solar/Wind Harmer
1.093
946321AF1-296 GEN
Solar/Wind Harmer
24.654
274848CAMPGROVE;RU
Solar/Wind Harmer
15.052
276655WTG1_EQ
Solar/Wind Harmer
18.909
276656WTG2_EQ
Solar/Wind Harmer
2.504
959341AF2-225 GEN
Solar/Wind Harmer
32.487
941731AE2-173 GEN
Solar/Wind Harmer
12.592
276785W4-005 GEN1
Solar/Wind Harmer
5.072
276174W4-005 GEN2
Solar/Wind Harmer
5.072
276849AB2-070 GEN2
Solar/Wind Harmer
3.758
276848AB2-070 GEN3
Solar/Wind Harmer
3.758
990512J1326
External Queue
13.405387878417969
990117J1214
External Queue
17.517770767211914
990727J1377 G
External Queue
15.634285926818848
991092J1477
External Queue
7.122580528259277
990407J1304
External Queue
10.39168643951416
NYPJM->LTFIMP_NY
CLTF
2.49
WECLTFEXP_WEC->PJM
CLTF
10.032
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.996
AG2-052LTFEXP_AG2-052->PJM
LTF
0.071
AH1-155LTFEXP_AH1-155->PJM
LTF
0.107
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
166.639
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.837
MECLTFEXP_MEC->PJM
CLTF
31.333
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.433
LAGNLTFEXP_LAGN->PJM
CLTF
10.191
TVALTFEXP_TVA->PJM
CLTF
2.55

Details for 05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line l/o AEP_P4_#2973_05DUMONT 345_F1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.9 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5007.64
MW Contribution:29.02
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
21.157
274771LINCOLN ;2U
50/50
21.157
274709KENDALL ;3S
50/50
2.16
274711KENDALL ;4S
50/50
2.16
274661LASCO STA;2U
50/50
19.909
972259AH1-714 GEN
50/50
55.882
274660LASCO STA;1U
50/50
20.163
971573AH1-285 GEN
Solar/Wind Harmer
23.377
274847GR RIDGE ;BU
Solar/Wind Harmer
13.499
274695ROCKY RD ;2P
Adder
29.021
274693ROCKY RD ;1P
Adder
28.736
274697ROCKY RD ;3P
Adder
7.884
274696ROCKY RD ;4P
Adder
29.703
962691AG1-118 GEN
Solar/Wind Harmer
78.028
970921AG2-575 GEN
Solar/Wind Harmer
25.876
970921AG2-575 GEN
Solar/Wind Harmer
6.018
274674JOLIET 9 ;6U
Adder
39.35
274683WAUKEGAN ;8U
Adder
53.641
274683WAUKEGAN ;8U
Adder
45.217
942991AE2-321 GEN
Solar/Wind Harmer
25.147
274773LINCOLN ;4U
50/50
21.157
274774LINCOLN ;5U
50/50
21.157
274710KENDALL ;4C
50/50
3.236
274705KENDALL ;1S
50/50
1.96
972207SS24-0001
Solar/Wind Harmer
70.889
274745AC1-111 GEN9
Adder
15.051
274871GR RIDGE ;2U
Solar/Wind Harmer
20.522
941551AE2-152 GEN
Solar/Wind Harmer
12.084
960751AF2-366 GEN
Solar/Wind Harmer
7.424
962781AG1-127 GEN
Solar/Wind Harmer
24.608
274872LEEDK;1U
Solar/Wind Harmer
21.16
274674JOLIET 9 ;6U
Adder
39.35
274682WAUKEGAN ;7U
Adder
45.848
274828WAUKEGAN ;BP
Adder
28.118
274676JOLIET 29;8U
Adder
77.975
274732ELWOOD EC;7P
Adder
41.564
276861AD2-134 GEN
Solar/Wind Harmer
4.496
276776AD2-060 GEN
Solar/Wind Harmer
1.053
957471AF2-041 GEN
Solar/Wind Harmer
74.193
959081AF2-199 GEN
Solar/Wind Harmer
24.731
971067AG2-660 GEN
Solar/Wind Harmer
5.751
274772LINCOLN ;3U
50/50
21.157
274707KENDALL ;2S
50/50
1.96
970707AG2-453 GEN
Solar/Wind Harmer
83.143
943121AE2-341 GEN
Solar/Wind Harmer
41.418
943591AF1-030 GEN
Solar/Wind Harmer
27.612
276897AD1-100 C
Solar/Wind Harmer
77.321
939351AE1-166 GEN
Solar/Wind Harmer
15.799
274872LEEDK;1U
Solar/Wind Harmer
0.659
972228AH1-698 GEN2
Adder
9.531
274682WAUKEGAN ;7U
Adder
45.848
274676JOLIET 29;8U
Adder
75.19
274729ELWOOD EC;1P
Adder
41.578
274730ELWOOD EC;6P
Adder
41.564
274734ELWOOD EC;8P
Adder
41.564
274736ELWOOD EC;9P
Adder
41.564
276799AD1-013 GEN
Solar/Wind Harmer
5.575
946671AF1-331 GEN
Solar/Wind Harmer
1.056
274855GSG-6 ;RU
Solar/Wind Harmer
9.297
274850MENDOTA H;RU
Solar/Wind Harmer
6.465
276602WESTBROOK C
Solar/Wind Harmer
5.352
276863AD2-134 GEN
Solar/Wind Harmer
4.496
276893AG1-478 C
Solar/Wind Harmer
1.045
276772AC2-154 GEN
Solar/Wind Harmer
6.946
276806AD2-047 C O1
Solar/Wind Harmer
26.644
970941AG2-585 GEN
Solar/Wind Harmer
31.134
959091AF2-200 GEN
Solar/Wind Harmer
49.462
972236AH1-702 GEN2
Adder
5.34
274800UNIV PARK;3U
Adder
14.189
972038AH1-567 GEN2
Adder
0.888
274826FISK ;BP
Adder
26.389
276694AA1-018 GEN2
Solar/Wind Harmer
14.959
274858EASY ROAD;U2
Solar/Wind Harmer
11.314
274760LEE CO EC;1U
Adder
21.966
274767LEE CO EC;8U
Adder
21.707
274802UNIV PARK;5U
Adder
13.721
276805AD2-038 GEN
Solar/Wind Harmer
11.959
276889AE2-281 GEN
Solar/Wind Harmer
4.37
276157O29GEN1
Solar/Wind Harmer
8.657
970571AG2-364 GEN
Solar/Wind Harmer
44.793
274724RIVER EC ;11
Adder
38.714
274878BISHOP HL;2U
Solar/Wind Harmer
7.314
965931AG1-462 GEN
Solar/Wind Harmer
54.666
942111AE2-223 GEN
Solar/Wind Harmer
16.454
274853TWINGROVE;U1
Solar/Wind Harmer
13.768
965091AG1-374 GEN
Solar/Wind Harmer
57.308
959611AF2-252 GEN
Solar/Wind Harmer
4.442
972231SS25-0005
Solar/Wind Harmer
17.505
972181SS23-001
Solar/Wind Harmer
10.941
274752CRETE EC ;2U
Adder
9.016
274753CRETE EC ;3U
Adder
9.016
276686W4-005 GEN3
Solar/Wind Harmer
4.717
971993AH1-541 GEN
Solar/Wind Harmer
14.41
276668AB2-070 GEN1
Solar/Wind Harmer
3.495
276621W2-048 GEN
Solar/Wind Harmer
9.246
276838X2-022 GEN2
Solar/Wind Harmer
0.345
939401AE1-172 GEN
Solar/Wind Harmer
34.433
274822ROCKFORD ;11
Adder
48.026
971997AH1-543 GEN
Solar/Wind Harmer
38.509
972235AH1-702 GEN1
Adder
6.141
274801UNIV PARK;4U
Adder
14.189
970819AG2-516 GEN
Solar/Wind Harmer
29.024
971475AH1-234 GEN
Solar/Wind Harmer
53.881
276901AD2-066 C O1
Solar/Wind Harmer
8.402
276691AA1-018 GEN1
Solar/Wind Harmer
1.104
274857EASY ROAD;U1
Solar/Wind Harmer
11.314
274761LEE CO EC;2U
Adder
21.966
274766LEE CO EC;7U
Adder
21.707
276164X3-005 C
Solar/Wind Harmer
1.649
276876AE1-163_GEN2
Solar/Wind Harmer
15.294
276158O29GEN2
Solar/Wind Harmer
11.382
970569AG2-363 GEN
Solar/Wind Harmer
67.19
274723RIVER EC ;12
Adder
39.002
274877BISHOP HL;1U
Solar/Wind Harmer
7.314
274812UNIV PK N;8U
Adder
10.613
276726Z2-087_GEN
Solar/Wind Harmer
15.875
939741AE1-205 GEN
Solar/Wind Harmer
40.143
274854TWINGROVE;U2
Solar/Wind Harmer
13.48
274751CRETE EC ;1U
Adder
9.016
274754CRETE EC ;4U
Adder
9.016
972175AH1-670 GEN
Solar/Wind Harmer
23.556
274880W4-005 GEN4
Solar/Wind Harmer
4.717
963831AG1-236 GEN
Solar/Wind Harmer
15.059
276615X2-022 GEN
Solar/Wind Harmer
2.903
274775LINCOLN ;6U
50/50
21.157
274776LINCOLN ;7U
50/50
21.157
274777LINCOLN ;8U
50/50
21.157
274708KENDALL ;3C
50/50
3.26
274704KENDALL ;1C
50/50
2.936
274706KENDALL ;2C
50/50
2.936
274746AC1-111 G10
Adder
15.051
274744AC1-111 GEN8
Adder
15.051
970833AG2-524 GEN
Solar/Wind Harmer
23.244
970833AG2-524 GEN
Solar/Wind Harmer
10.811
972227AH1-698 GEN1
Adder
6.713
274675JOLIET 29;7U
Adder
77.983
274675JOLIET 29;7U
Adder
75.198
274731ELWOOD EC;2P
Adder
41.578
274733ELWOOD EC;3P
Adder
41.578
274735ELWOOD EC;4P
Adder
41.578
274728ELWOOD EC;5P
Adder
41.564
971675AH1-338 GEN
Solar/Wind Harmer
45.346
971177AH1-047 GEN
Solar/Wind Harmer
14.728
274687WILL CNTY;4U
Adder
70.005
274687WILL CNTY;4U
Adder
70.005
971411AH1-196 GEN
Solar/Wind Harmer
37.385
960591AF2-350 GEN
Solar/Wind Harmer
24.907
971171AH1-044 GEN
Solar/Wind Harmer
49.462
274823ROCKFORD ;21
Adder
47.678
274827FISK ;RP
Adder
18.702
276612AE2-035 GEN
Solar/Wind Harmer
6.17
971681AH1-341 GEN
Solar/Wind Harmer
35.709
274863CRW1-WTG
Solar/Wind Harmer
13.216
274864CRW2-WTG
Solar/Wind Harmer
13.216
276868AE1-113 GEN
Solar/Wind Harmer
23.946
276882AE2-255 GEN
Solar/Wind Harmer
7.983
972037AH1-567 GEN1
Adder
0.431
961011AF2-392 GEN
Solar/Wind Harmer
25.254
926823AC1-168 GEN
Solar/Wind Harmer
9.892
970169AG2-114 GEN
Solar/Wind Harmer
22.646
957751AF2-069 GEN
Solar/Wind Harmer
1.002
946321AF1-296 GEN
Solar/Wind Harmer
22.629
274848CAMPGROVE;RU
Solar/Wind Harmer
13.793
274814UNIV PK N;0U
Adder
10.706
274807UNIV PK N;3U
Adder
10.683
274805UNIV PK N;1U
Adder
10.637
274811UNIV PK N;7U
Adder
10.613
276655WTG1_EQ
Solar/Wind Harmer
17.524
276656WTG2_EQ
Solar/Wind Harmer
2.32
959341AF2-225 GEN
Solar/Wind Harmer
30.107
941731AE2-173 GEN
Solar/Wind Harmer
11.669
276785W4-005 GEN1
Solar/Wind Harmer
4.717
276174W4-005 GEN2
Solar/Wind Harmer
4.717
276849AB2-070 GEN2
Solar/Wind Harmer
3.495
276848AB2-070 GEN3
Solar/Wind Harmer
3.495
971333AH1-146 GEN
Solar/Wind Harmer
49.953
971335AH1-147 GEN
Solar/Wind Harmer
49.953
274888KELLY CRK;1U
Solar/Wind Harmer
14.705
274887GEN-1.85
Solar/Wind Harmer
13.276
276843GEN-1.7
Solar/Wind Harmer
1.428
958011AF2-095 GEN
Solar/Wind Harmer
35.866
971341AH1-150 GEN
Solar/Wind Harmer
49.462
971343AH1-151 GEN
Solar/Wind Harmer
49.462
274856ECOGROVE ;U1
Solar/Wind Harmer
8.131
276611AD2-172 GEN
Solar/Wind Harmer
6.17
938861AE1-114 GEN
Solar/Wind Harmer
19.498
958481AF2-142 GEN
Solar/Wind Harmer
35.557
274879MINONK ;1U
Solar/Wind Harmer
15.966
274764LEE CO EC;5U
Adder
22.018
274765LEE CO EC;6U
Adder
22.018
274762LEE CO EC;3U
Adder
21.966
274763LEE CO EC;4U
Adder
21.759
274861TOP CROP ;1U
Solar/Wind Harmer
14.292
274862TOP CROP ;2U
Solar/Wind Harmer
11.934
274803UNIV PARK;6U
Adder
13.721
276603SUBLETTE C
Solar/Wind Harmer
2.468
958491AF2-143 GEN
Solar/Wind Harmer
34.969
972267AH1-718 GEN
Adder
9.625
276872AE1-163_GEN1
Solar/Wind Harmer
15.294
276741O09 GEN1
Solar/Wind Harmer
8.13
276708O09 GEN2
Solar/Wind Harmer
8.13
274851PROVIDENC;RU
Solar/Wind Harmer
6.213
274849CRESCENT ;1U
Solar/Wind Harmer
4.034
276645AC1-214 GEN1
Solar/Wind Harmer
2.922
276646AC1-214 GEN2
Solar/Wind Harmer
2.922
276782AC1-033 GEN
Solar/Wind Harmer
8.643
274808UNIV PK N;4U
Adder
10.567
960611AF2-352 GEN
Solar/Wind Harmer
4.442
276763AC1-053 GEN1
Solar/Wind Harmer
6.054
276764AC1-053 GEN2
Solar/Wind Harmer
6.054
990512J1326
External Queue
12.000266075134277
990727J1377 G
External Queue
8.28534984588623
991092J1477
External Queue
6.35044002532959
990407J1304
External Queue
9.309322357177734
NYPJM->LTFIMP_NY
CLTF
2.297
WECLTFEXP_WEC->PJM
CLTF
9.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.822
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.958
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.612
MECLTFEXP_MEC->PJM
CLTF
28.811
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.049
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.934
LAGNLTFEXP_LAGN->PJM
CLTF
9.519
TVALTFEXP_TVA->PJM
CLTF
2.426

Details for 05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line l/o AEP_P4_#2976_05DUMONT 345_F_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2976_05DUMONT 345_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.56 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4993.52
MW Contribution:28.97
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
21.122
274776LINCOLN ;7U
50/50
21.122
274777LINCOLN ;8U
50/50
21.122
274708KENDALL ;3C
50/50
3.255
274704KENDALL ;1C
50/50
2.931
274706KENDALL ;2C
50/50
2.931
274746AC1-111 G10
Adder
15.025
274744AC1-111 GEN8
Adder
15.025
970833AG2-524 GEN
Solar/Wind Harmer
23.203
970833AG2-524 GEN
Solar/Wind Harmer
10.792
972227AH1-698 GEN1
Adder
6.701
274675JOLIET 29;7U
Adder
77.846
274675JOLIET 29;7U
Adder
75.065
274731ELWOOD EC;2P
Adder
41.504
274733ELWOOD EC;3P
Adder
41.504
274735ELWOOD EC;4P
Adder
41.504
274728ELWOOD EC;5P
Adder
41.49
971675AH1-338 GEN
Solar/Wind Harmer
45.265
971177AH1-047 GEN
Solar/Wind Harmer
14.702
274687WILL CNTY;4U
Adder
69.882
274687WILL CNTY;4U
Adder
69.882
971411AH1-196 GEN
Solar/Wind Harmer
37.319
960591AF2-350 GEN
Solar/Wind Harmer
24.863
971171AH1-044 GEN
Solar/Wind Harmer
49.374
274823ROCKFORD ;21
Adder
47.593
274827FISK ;RP
Adder
18.67
276612AE2-035 GEN
Solar/Wind Harmer
6.159
971681AH1-341 GEN
Solar/Wind Harmer
35.645
274863CRW1-WTG
Solar/Wind Harmer
13.191
274864CRW2-WTG
Solar/Wind Harmer
13.191
276868AE1-113 GEN
Solar/Wind Harmer
23.903
276882AE2-255 GEN
Solar/Wind Harmer
7.968
972037AH1-567 GEN1
Adder
0.43
961011AF2-392 GEN
Solar/Wind Harmer
25.208
926823AC1-168 GEN
Solar/Wind Harmer
9.873
970169AG2-114 GEN
Solar/Wind Harmer
22.604
957751AF2-069 GEN
Solar/Wind Harmer
1
946321AF1-296 GEN
Solar/Wind Harmer
22.587
274848CAMPGROVE;RU
Solar/Wind Harmer
13.767
274814UNIV PK N;0U
Adder
10.685
274807UNIV PK N;3U
Adder
10.662
274805UNIV PK N;1U
Adder
10.615
274811UNIV PK N;7U
Adder
10.592
276655WTG1_EQ
Solar/Wind Harmer
17.489
276656WTG2_EQ
Solar/Wind Harmer
2.316
959341AF2-225 GEN
Solar/Wind Harmer
30.048
941731AE2-173 GEN
Solar/Wind Harmer
11.646
276785W4-005 GEN1
Solar/Wind Harmer
4.707
276174W4-005 GEN2
Solar/Wind Harmer
4.707
276849AB2-070 GEN2
Solar/Wind Harmer
3.488
276848AB2-070 GEN3
Solar/Wind Harmer
3.488
274770LINCOLN ;1U
50/50
21.122
274771LINCOLN ;2U
50/50
21.122
274709KENDALL ;3S
50/50
2.157
274711KENDALL ;4S
50/50
2.157
274661LASCO STA;2U
50/50
19.875
972259AH1-714 GEN
50/50
55.786
274660LASCO STA;1U
50/50
20.128
971573AH1-285 GEN
Solar/Wind Harmer
23.337
274847GR RIDGE ;BU
Solar/Wind Harmer
13.476
274695ROCKY RD ;2P
Adder
28.97
274693ROCKY RD ;1P
Adder
28.685
274697ROCKY RD ;3P
Adder
7.87
274696ROCKY RD ;4P
Adder
29.651
962691AG1-118 GEN
Solar/Wind Harmer
77.891
970921AG2-575 GEN
Solar/Wind Harmer
25.831
970921AG2-575 GEN
Solar/Wind Harmer
6.007
274674JOLIET 9 ;6U
Adder
39.281
274683WAUKEGAN ;8U
Adder
53.547
274683WAUKEGAN ;8U
Adder
45.137
942991AE2-321 GEN
Solar/Wind Harmer
25.103
971333AH1-146 GEN
Solar/Wind Harmer
49.864
971335AH1-147 GEN
Solar/Wind Harmer
49.864
958011AF2-095 GEN
Solar/Wind Harmer
35.804
274888KELLY CRK;1U
Solar/Wind Harmer
14.679
274887GEN-1.85
Solar/Wind Harmer
13.253
276843GEN-1.7
Solar/Wind Harmer
1.426
971341AH1-150 GEN
Solar/Wind Harmer
49.374
971343AH1-151 GEN
Solar/Wind Harmer
49.374
274856ECOGROVE ;U1
Solar/Wind Harmer
8.116
276611AD2-172 GEN
Solar/Wind Harmer
6.159
938861AE1-114 GEN
Solar/Wind Harmer
19.463
958481AF2-142 GEN
Solar/Wind Harmer
35.492
274879MINONK ;1U
Solar/Wind Harmer
15.937
274764LEE CO EC;5U
Adder
21.978
274765LEE CO EC;6U
Adder
21.978
274762LEE CO EC;3U
Adder
21.926
274763LEE CO EC;4U
Adder
21.719
274861TOP CROP ;1U
Solar/Wind Harmer
14.266
274862TOP CROP ;2U
Solar/Wind Harmer
11.913
274803UNIV PARK;6U
Adder
13.696
276603SUBLETTE C
Solar/Wind Harmer
2.463
958491AF2-143 GEN
Solar/Wind Harmer
34.905
972267AH1-718 GEN
Adder
9.607
276872AE1-163_GEN1
Solar/Wind Harmer
15.266
276741O09 GEN1
Solar/Wind Harmer
8.115
276708O09 GEN2
Solar/Wind Harmer
8.115
274851PROVIDENC;RU
Solar/Wind Harmer
6.202
274849CRESCENT ;1U
Solar/Wind Harmer
4.026
276645AC1-214 GEN1
Solar/Wind Harmer
2.917
276646AC1-214 GEN2
Solar/Wind Harmer
2.917
276782AC1-033 GEN
Solar/Wind Harmer
8.627
274808UNIV PK N;4U
Adder
10.546
960611AF2-352 GEN
Solar/Wind Harmer
4.434
276763AC1-053 GEN1
Solar/Wind Harmer
6.04
276764AC1-053 GEN2
Solar/Wind Harmer
6.04
274773LINCOLN ;4U
50/50
21.122
274774LINCOLN ;5U
50/50
21.122
274710KENDALL ;4C
50/50
3.23
274705KENDALL ;1S
50/50
1.957
972207SS24-0001
Solar/Wind Harmer
70.774
274745AC1-111 GEN9
Adder
15.025
274871GR RIDGE ;2U
Solar/Wind Harmer
20.487
941551AE2-152 GEN
Solar/Wind Harmer
12.063
960751AF2-366 GEN
Solar/Wind Harmer
7.411
962781AG1-127 GEN
Solar/Wind Harmer
24.565
274872LEEDK;1U
Solar/Wind Harmer
21.122
274674JOLIET 9 ;6U
Adder
39.281
274682WAUKEGAN ;7U
Adder
45.767
274828WAUKEGAN ;BP
Adder
28.068
274676JOLIET 29;8U
Adder
77.837
274732ELWOOD EC;7P
Adder
41.49
276861AD2-134 GEN
Solar/Wind Harmer
4.488
276776AD2-060 GEN
Solar/Wind Harmer
1.051
957471AF2-041 GEN
Solar/Wind Harmer
74.06
959081AF2-199 GEN
Solar/Wind Harmer
24.687
971067AG2-660 GEN
Solar/Wind Harmer
5.741
939401AE1-172 GEN
Solar/Wind Harmer
34.371
274822ROCKFORD ;11
Adder
47.94
971997AH1-543 GEN
Solar/Wind Harmer
38.44
972235AH1-702 GEN1
Adder
6.13
274801UNIV PARK;4U
Adder
14.165
970819AG2-516 GEN
Solar/Wind Harmer
28.972
971475AH1-234 GEN
Solar/Wind Harmer
53.784
276901AD2-066 C O1
Solar/Wind Harmer
8.387
276691AA1-018 GEN1
Solar/Wind Harmer
1.102
274857EASY ROAD;U1
Solar/Wind Harmer
11.294
274761LEE CO EC;2U
Adder
21.926
274766LEE CO EC;7U
Adder
21.668
276164X3-005 C
Solar/Wind Harmer
1.646
276876AE1-163_GEN2
Solar/Wind Harmer
15.266
276158O29GEN2
Solar/Wind Harmer
11.361
970569AG2-363 GEN
Solar/Wind Harmer
67.065
274723RIVER EC ;12
Adder
38.937
274877BISHOP HL;1U
Solar/Wind Harmer
7.3
274812UNIV PK N;8U
Adder
10.592
276726Z2-087_GEN
Solar/Wind Harmer
15.844
939741AE1-205 GEN
Solar/Wind Harmer
40.064
274854TWINGROVE;U2
Solar/Wind Harmer
13.453
274751CRETE EC ;1U
Adder
8.996
274754CRETE EC ;4U
Adder
8.996
972175AH1-670 GEN
Solar/Wind Harmer
23.506
274880W4-005 GEN4
Solar/Wind Harmer
4.707
963831AG1-236 GEN
Solar/Wind Harmer
15.025
276615X2-022 GEN
Solar/Wind Harmer
2.896
274772LINCOLN ;3U
50/50
21.122
274707KENDALL ;2S
50/50
1.957
970707AG2-453 GEN
Solar/Wind Harmer
83.003
943121AE2-341 GEN
Solar/Wind Harmer
41.346
943591AF1-030 GEN
Solar/Wind Harmer
27.564
276897AD1-100 C
Solar/Wind Harmer
77.187
939351AE1-166 GEN
Solar/Wind Harmer
15.771
274872LEEDK;1U
Solar/Wind Harmer
0.658
972228AH1-698 GEN2
Adder
9.514
274682WAUKEGAN ;7U
Adder
45.767
274676JOLIET 29;8U
Adder
75.057
274729ELWOOD EC;1P
Adder
41.504
274730ELWOOD EC;6P
Adder
41.49
274734ELWOOD EC;8P
Adder
41.49
274736ELWOOD EC;9P
Adder
41.49
276799AD1-013 GEN
Solar/Wind Harmer
5.565
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274855GSG-6 ;RU
Solar/Wind Harmer
9.281
274850MENDOTA H;RU
Solar/Wind Harmer
6.453
276602WESTBROOK C
Solar/Wind Harmer
5.342
276863AD2-134 GEN
Solar/Wind Harmer
4.488
276893AG1-478 C
Solar/Wind Harmer
1.044
276772AC2-154 GEN
Solar/Wind Harmer
6.934
276806AD2-047 C O1
Solar/Wind Harmer
26.598
970941AG2-585 GEN
Solar/Wind Harmer
31.079
959091AF2-200 GEN
Solar/Wind Harmer
49.374
972236AH1-702 GEN2
Adder
5.33
274800UNIV PARK;3U
Adder
14.165
972038AH1-567 GEN2
Adder
0.887
274826FISK ;BP
Adder
26.343
276694AA1-018 GEN2
Solar/Wind Harmer
14.932
274858EASY ROAD;U2
Solar/Wind Harmer
11.294
274760LEE CO EC;1U
Adder
21.926
274767LEE CO EC;8U
Adder
21.668
274802UNIV PARK;5U
Adder
13.696
276805AD2-038 GEN
Solar/Wind Harmer
11.938
276889AE2-281 GEN
Solar/Wind Harmer
4.362
276157O29GEN1
Solar/Wind Harmer
8.642
970571AG2-364 GEN
Solar/Wind Harmer
44.71
274724RIVER EC ;11
Adder
38.651
274878BISHOP HL;2U
Solar/Wind Harmer
7.3
965931AG1-462 GEN
Solar/Wind Harmer
54.563
942111AE2-223 GEN
Solar/Wind Harmer
16.421
274853TWINGROVE;U1
Solar/Wind Harmer
13.74
965091AG1-374 GEN
Solar/Wind Harmer
57.192
959611AF2-252 GEN
Solar/Wind Harmer
4.434
972231SS25-0005
Solar/Wind Harmer
17.466
972181SS23-001
Solar/Wind Harmer
10.916
274752CRETE EC ;2U
Adder
8.996
274753CRETE EC ;3U
Adder
8.996
276686W4-005 GEN3
Solar/Wind Harmer
4.707
971993AH1-541 GEN
Solar/Wind Harmer
14.377
276668AB2-070 GEN1
Solar/Wind Harmer
3.488
276621W2-048 GEN
Solar/Wind Harmer
9.225
276838X2-022 GEN2
Solar/Wind Harmer
0.344
990512J1326
External Queue
11.96206283569336
990727J1377 G
External Queue
8.25949764251709
991092J1477
External Queue
6.326850414276123
990407J1304
External Queue
9.280413627624512
NYPJM->LTFIMP_NY
CLTF
2.293
WECLTFEXP_WEC->PJM
CLTF
9.166
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.961
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.555
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.479
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.559
MECLTFEXP_MEC->PJM
CLTF
28.752
SIGELTFEXP_SIGE->PJM
CLTF
0.042
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.057
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.96
LAGNLTFEXP_LAGN->PJM
CLTF
9.484
TVALTFEXP_TVA->PJM
CLTF
2.412

Details for 05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line l/o AEP_P2-2_#286_05EUGENE 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.72 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4751.76
MW Contribution:27.57
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
20.274
274771LINCOLN ;2U
50/50
20.274
274709KENDALL ;3S
50/50
2.051
274711KENDALL ;4S
50/50
2.051
274661LASCO STA;2U
50/50
18.869
972259AH1-714 GEN
50/50
52.964
274660LASCO STA;1U
50/50
19.11
971573AH1-285 GEN
Solar/Wind Harmer
22.248
274847GR RIDGE ;BU
Solar/Wind Harmer
12.807
962691AG1-118 GEN
Solar/Wind Harmer
74.159
274695ROCKY RD ;2P
Adder
27.515
274693ROCKY RD ;1P
Adder
27.244
274697ROCKY RD ;3P
Adder
7.474
274696ROCKY RD ;4P
Adder
28.16
970921AG2-575 GEN
Solar/Wind Harmer
24.596
970921AG2-575 GEN
Solar/Wind Harmer
5.72
274683WAUKEGAN ;8U
Adder
50.694
274683WAUKEGAN ;8U
Adder
42.733
274674JOLIET 9 ;6U
Adder
36.856
942991AE2-321 GEN
Solar/Wind Harmer
23.854
971333AH1-146 GEN
Solar/Wind Harmer
47.432
971335AH1-147 GEN
Solar/Wind Harmer
47.432
971341AH1-150 GEN
Solar/Wind Harmer
47.017
971343AH1-151 GEN
Solar/Wind Harmer
47.017
958011AF2-095 GEN
Solar/Wind Harmer
33.203
274888KELLY CRK;1U
Solar/Wind Harmer
13.613
274887GEN-1.85
Solar/Wind Harmer
12.29
276843GEN-1.7
Solar/Wind Harmer
1.322
274856ECOGROVE ;U1
Solar/Wind Harmer
7.727
276611AD2-172 GEN
Solar/Wind Harmer
5.863
938861AE1-114 GEN
Solar/Wind Harmer
18.545
274764LEE CO EC;5U
Adder
20.944
274765LEE CO EC;6U
Adder
20.944
274762LEE CO EC;3U
Adder
20.895
274763LEE CO EC;4U
Adder
20.698
276603SUBLETTE C
Solar/Wind Harmer
2.349
274879MINONK ;1U
Solar/Wind Harmer
15.083
958481AF2-142 GEN
Solar/Wind Harmer
33.285
274772LINCOLN ;3U
50/50
20.274
274707KENDALL ;2S
50/50
1.839
970707AG2-453 GEN
Solar/Wind Harmer
79.501
943121AE2-341 GEN
Solar/Wind Harmer
39.431
943591AF1-030 GEN
Solar/Wind Harmer
26.287
276897AD1-100 C
Solar/Wind Harmer
73.15
939351AE1-166 GEN
Solar/Wind Harmer
14.946
274872LEEDK;1U
Solar/Wind Harmer
0.627
972228AH1-698 GEN2
Adder
8.938
274682WAUKEGAN ;7U
Adder
43.324
276799AD1-013 GEN
Solar/Wind Harmer
5.302
946671AF1-331 GEN
Solar/Wind Harmer
1.004
274855GSG-6 ;RU
Solar/Wind Harmer
8.842
274850MENDOTA H;RU
Solar/Wind Harmer
6.148
276602WESTBROOK C
Solar/Wind Harmer
5.09
276863AD2-134 GEN
Solar/Wind Harmer
4.276
274676JOLIET 29;8U
Adder
70.373
274729ELWOOD EC;1P
Adder
38.993
274730ELWOOD EC;6P
Adder
38.976
274734ELWOOD EC;8P
Adder
38.976
274736ELWOOD EC;9P
Adder
38.976
959091AF2-200 GEN
Solar/Wind Harmer
47.017
276893AG1-478 C
Solar/Wind Harmer
0.977
972236AH1-702 GEN2
Adder
5.073
276772AC2-154 GEN
Solar/Wind Harmer
6.43
274775LINCOLN ;6U
50/50
20.274
274776LINCOLN ;7U
50/50
20.274
274777LINCOLN ;8U
50/50
20.274
274708KENDALL ;3C
50/50
3.095
274704KENDALL ;1C
50/50
2.755
274706KENDALL ;2C
50/50
2.755
274746AC1-111 G10
Adder
14.288
274744AC1-111 GEN8
Adder
14.288
970833AG2-524 GEN
Solar/Wind Harmer
22.034
970833AG2-524 GEN
Solar/Wind Harmer
10.248
972227AH1-698 GEN1
Adder
6.296
971675AH1-338 GEN
Solar/Wind Harmer
43.125
971177AH1-047 GEN
Solar/Wind Harmer
13.972
274675JOLIET 29;7U
Adder
72.988
274675JOLIET 29;7U
Adder
70.381
274731ELWOOD EC;2P
Adder
38.993
274733ELWOOD EC;3P
Adder
38.993
274735ELWOOD EC;4P
Adder
38.993
274728ELWOOD EC;5P
Adder
38.976
971411AH1-196 GEN
Solar/Wind Harmer
35.471
971171AH1-044 GEN
Solar/Wind Harmer
47.017
274687WILL CNTY;4U
Adder
65.236
274687WILL CNTY;4U
Adder
65.236
274823ROCKFORD ;21
Adder
45.277
960591AF2-350 GEN
Solar/Wind Harmer
23.057
276612AE2-035 GEN
Solar/Wind Harmer
5.863
274863CRW1-WTG
Solar/Wind Harmer
12.748
274864CRW2-WTG
Solar/Wind Harmer
12.748
971681AH1-341 GEN
Solar/Wind Harmer
33.97
276868AE1-113 GEN
Solar/Wind Harmer
22.622
276882AE2-255 GEN
Solar/Wind Harmer
7.541
961011AF2-392 GEN
Solar/Wind Harmer
24.049
274827FISK ;RP
Adder
17.127
926823AC1-168 GEN
Solar/Wind Harmer
9.458
970169AG2-114 GEN
Solar/Wind Harmer
21.957
972037AH1-567 GEN1
Adder
0.396
957751AF2-069 GEN
Solar/Wind Harmer
0.96
946321AF1-296 GEN
Solar/Wind Harmer
21.59
274848CAMPGROVE;RU
Solar/Wind Harmer
13.236
276655WTG1_EQ
Solar/Wind Harmer
17.271
276656WTG2_EQ
Solar/Wind Harmer
2.287
959341AF2-225 GEN
Solar/Wind Harmer
29.672
941731AE2-173 GEN
Solar/Wind Harmer
11.501
274814UNIV PK N;0U
Adder
9.754
274807UNIV PK N;3U
Adder
9.733
274805UNIV PK N;1U
Adder
9.691
274811UNIV PK N;7U
Adder
9.67
276785W4-005 GEN1
Solar/Wind Harmer
4.789
276174W4-005 GEN2
Solar/Wind Harmer
4.789
276849AB2-070 GEN2
Solar/Wind Harmer
3.551
276848AB2-070 GEN3
Solar/Wind Harmer
3.551
274773LINCOLN ;4U
50/50
20.274
274774LINCOLN ;5U
50/50
20.274
274710KENDALL ;4C
50/50
3.072
274705KENDALL ;1S
50/50
1.839
972207SS24-0001
Solar/Wind Harmer
67.931
274745AC1-111 GEN9
Adder
14.288
274871GR RIDGE ;2U
Solar/Wind Harmer
19.469
941551AE2-152 GEN
Solar/Wind Harmer
11.432
960751AF2-366 GEN
Solar/Wind Harmer
7.057
962781AG1-127 GEN
Solar/Wind Harmer
23.391
274872LEEDK;1U
Solar/Wind Harmer
20.118
274682WAUKEGAN ;7U
Adder
43.324
274828WAUKEGAN ;BP
Adder
26.573
276861AD2-134 GEN
Solar/Wind Harmer
4.276
274674JOLIET 9 ;6U
Adder
36.856
274676JOLIET 29;8U
Adder
72.979
939401AE1-172 GEN
Solar/Wind Harmer
33.053
274732ELWOOD EC;7P
Adder
38.976
957471AF2-041 GEN
Solar/Wind Harmer
70.526
959081AF2-199 GEN
Solar/Wind Harmer
23.509
971067AG2-660 GEN
Solar/Wind Harmer
5.467
971997AH1-543 GEN
Solar/Wind Harmer
36.681
274822ROCKFORD ;11
Adder
45.607
972235AH1-702 GEN1
Adder
5.834
276776AD2-060 GEN
Solar/Wind Harmer
0.975
970819AG2-516 GEN
Solar/Wind Harmer
27.572
971475AH1-234 GEN
Solar/Wind Harmer
51.175
276901AD2-066 C O1
Solar/Wind Harmer
7.96
274857EASY ROAD;U1
Solar/Wind Harmer
10.763
274761LEE CO EC;2U
Adder
20.895
274766LEE CO EC;7U
Adder
20.649
274801UNIV PARK;4U
Adder
13.03
276691AA1-018 GEN1
Solar/Wind Harmer
1.033
276158O29GEN2
Solar/Wind Harmer
10.855
276876AE1-163_GEN2
Solar/Wind Harmer
14.453
970569AG2-363 GEN
Solar/Wind Harmer
63.748
276164X3-005 C
Solar/Wind Harmer
1.478
274877BISHOP HL;1U
Solar/Wind Harmer
7.008
276726Z2-087_GEN
Solar/Wind Harmer
15.646
939741AE1-205 GEN
Solar/Wind Harmer
39.563
274812UNIV PK N;8U
Adder
9.67
274723RIVER EC ;12
Adder
33.905
274854TWINGROVE;U2
Solar/Wind Harmer
13.328
972175AH1-670 GEN
Solar/Wind Harmer
23.591
274751CRETE EC ;1U
Adder
8.062
274754CRETE EC ;4U
Adder
8.062
274880W4-005 GEN4
Solar/Wind Harmer
4.789
963831AG1-236 GEN
Solar/Wind Harmer
15.298
276615X2-022 GEN
Solar/Wind Harmer
2.948
276806AD2-047 C O1
Solar/Wind Harmer
24.666
970941AG2-585 GEN
Solar/Wind Harmer
28.822
274858EASY ROAD;U2
Solar/Wind Harmer
10.763
274760LEE CO EC;1U
Adder
20.895
274767LEE CO EC;8U
Adder
20.649
274800UNIV PARK;3U
Adder
13.03
972038AH1-567 GEN2
Adder
0.816
276694AA1-018 GEN2
Solar/Wind Harmer
14.003
274826FISK ;BP
Adder
24.166
276805AD2-038 GEN
Solar/Wind Harmer
11.239
276157O29GEN1
Solar/Wind Harmer
8.257
274802UNIV PARK;5U
Adder
12.61
276889AE2-281 GEN
Solar/Wind Harmer
4.13
970571AG2-364 GEN
Solar/Wind Harmer
42.499
274878BISHOP HL;2U
Solar/Wind Harmer
7.008
965931AG1-462 GEN
Solar/Wind Harmer
52.169
942111AE2-223 GEN
Solar/Wind Harmer
16.216
274724RIVER EC ;11
Adder
33.588
274853TWINGROVE;U1
Solar/Wind Harmer
13.613
965091AG1-374 GEN
Solar/Wind Harmer
56.662
959611AF2-252 GEN
Solar/Wind Harmer
4.392
972231SS25-0005
Solar/Wind Harmer
15.653
972181SS23-001
Solar/Wind Harmer
9.783
274752CRETE EC ;2U
Adder
8.062
274753CRETE EC ;3U
Adder
8.062
276686W4-005 GEN3
Solar/Wind Harmer
4.789
971993AH1-541 GEN
Solar/Wind Harmer
14.63
276668AB2-070 GEN1
Solar/Wind Harmer
3.551
276621W2-048 GEN
Solar/Wind Harmer
9.391
276838X2-022 GEN2
Solar/Wind Harmer
0.35
274861TOP CROP ;1U
Solar/Wind Harmer
13.377
274862TOP CROP ;2U
Solar/Wind Harmer
11.171
972267AH1-718 GEN
Adder
9.165
958491AF2-143 GEN
Solar/Wind Harmer
32.862
276741O09 GEN1
Solar/Wind Harmer
7.754
276708O09 GEN2
Solar/Wind Harmer
7.754
274803UNIV PARK;6U
Adder
12.61
276872AE1-163_GEN1
Solar/Wind Harmer
14.453
274851PROVIDENC;RU
Solar/Wind Harmer
5.955
274849CRESCENT ;1U
Solar/Wind Harmer
3.866
276645AC1-214 GEN1
Solar/Wind Harmer
2.801
276646AC1-214 GEN2
Solar/Wind Harmer
2.801
276782AC1-033 GEN
Solar/Wind Harmer
8.281
274808UNIV PK N;4U
Adder
9.627
960611AF2-352 GEN
Solar/Wind Harmer
4.392
276763AC1-053 GEN1
Solar/Wind Harmer
6.15
276764AC1-053 GEN2
Solar/Wind Harmer
6.15
957381AF2-032 GEN
Solar/Wind Harmer
0.572
990512J1326
External Queue
11.444344520568848
990727J1377 G
External Queue
7.3309478759765625
991092J1477
External Queue
6.13206148147583
990407J1304
External Queue
8.867903709411621
NYPJM->LTFIMP_NY
CLTF
2.17
WECLTFEXP_WEC->PJM
CLTF
8.7
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.461
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.445
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.385
MECLTFEXP_MEC->PJM
CLTF
27.615
SIGELTFEXP_SIGE->PJM
CLTF
0.031
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.094
LAGNLTFEXP_LAGN->PJM
CLTF
9.262
TVALTFEXP_TVA->PJM
CLTF
2.37

Details for 05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT_RW-05DUMONT 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:114.52 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4743.27
MW Contribution:27.36
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
20.173
274776LINCOLN ;7U
50/50
20.173
274777LINCOLN ;8U
50/50
20.173
274708KENDALL ;3C
50/50
3.082
274704KENDALL ;1C
50/50
2.746
274706KENDALL ;2C
50/50
2.746
274746AC1-111 G10
Adder
14.216
274744AC1-111 GEN8
Adder
14.216
970833AG2-524 GEN
Solar/Wind Harmer
21.915
970833AG2-524 GEN
Solar/Wind Harmer
10.193
972227AH1-698 GEN1
Adder
6.285
971675AH1-338 GEN
Solar/Wind Harmer
42.811
274675JOLIET 29;7U
Adder
72.865
274675JOLIET 29;7U
Adder
70.263
971177AH1-047 GEN
Solar/Wind Harmer
13.883
274731ELWOOD EC;2P
Adder
38.878
274733ELWOOD EC;3P
Adder
38.878
274735ELWOOD EC;4P
Adder
38.878
274728ELWOOD EC;5P
Adder
38.863
971411AH1-196 GEN
Solar/Wind Harmer
35.236
971171AH1-044 GEN
Solar/Wind Harmer
46.661
274687WILL CNTY;4U
Adder
65.158
274687WILL CNTY;4U
Adder
65.158
274823ROCKFORD ;21
Adder
44.942
960591AF2-350 GEN
Solar/Wind Harmer
23.02
276612AE2-035 GEN
Solar/Wind Harmer
5.816
971681AH1-341 GEN
Solar/Wind Harmer
33.665
274863CRW1-WTG
Solar/Wind Harmer
12.469
274864CRW2-WTG
Solar/Wind Harmer
12.469
276868AE1-113 GEN
Solar/Wind Harmer
22.431
276882AE2-255 GEN
Solar/Wind Harmer
7.478
274827FISK ;RP
Adder
17.137
961011AF2-392 GEN
Solar/Wind Harmer
23.805
972037AH1-567 GEN1
Adder
0.397
926823AC1-168 GEN
Solar/Wind Harmer
9.311
970169AG2-114 GEN
Solar/Wind Harmer
21.375
957751AF2-069 GEN
Solar/Wind Harmer
0.942
946321AF1-296 GEN
Solar/Wind Harmer
21.32
274848CAMPGROVE;RU
Solar/Wind Harmer
12.976
274814UNIV PK N;0U
Adder
9.899
274807UNIV PK N;3U
Adder
9.877
274805UNIV PK N;1U
Adder
9.834
274811UNIV PK N;7U
Adder
9.813
276655WTG1_EQ
Solar/Wind Harmer
16.537
276656WTG2_EQ
Solar/Wind Harmer
2.19
959341AF2-225 GEN
Solar/Wind Harmer
28.412
941731AE2-173 GEN
Solar/Wind Harmer
11.012
276785W4-005 GEN1
Solar/Wind Harmer
4.451
276174W4-005 GEN2
Solar/Wind Harmer
4.451
276849AB2-070 GEN2
Solar/Wind Harmer
3.298
276848AB2-070 GEN3
Solar/Wind Harmer
3.298
274773LINCOLN ;4U
50/50
20.173
274774LINCOLN ;5U
50/50
20.173
274710KENDALL ;4C
50/50
3.059
274705KENDALL ;1S
50/50
1.834
972207SS24-0001
Solar/Wind Harmer
67.591
274745AC1-111 GEN9
Adder
14.216
274871GR RIDGE ;2U
Solar/Wind Harmer
19.363
941551AE2-152 GEN
Solar/Wind Harmer
11.363
960751AF2-366 GEN
Solar/Wind Harmer
7.012
962781AG1-127 GEN
Solar/Wind Harmer
23.243
274872LEEDK;1U
Solar/Wind Harmer
19.986
274682WAUKEGAN ;7U
Adder
43.121
274828WAUKEGAN ;BP
Adder
26.446
274674JOLIET 9 ;6U
Adder
36.733
276861AD2-134 GEN
Solar/Wind Harmer
4.245
274676JOLIET 29;8U
Adder
72.857
274732ELWOOD EC;7P
Adder
38.863
957471AF2-041 GEN
Solar/Wind Harmer
69.992
959081AF2-199 GEN
Solar/Wind Harmer
23.331
971067AG2-660 GEN
Solar/Wind Harmer
5.426
939401AE1-172 GEN
Solar/Wind Harmer
32.483
274822ROCKFORD ;11
Adder
45.27
971997AH1-543 GEN
Solar/Wind Harmer
36.28
276776AD2-060 GEN
Solar/Wind Harmer
0.973
972235AH1-702 GEN1
Adder
5.789
970819AG2-516 GEN
Solar/Wind Harmer
27.357
971475AH1-234 GEN
Solar/Wind Harmer
50.778
276901AD2-066 C O1
Solar/Wind Harmer
7.878
274801UNIV PARK;4U
Adder
13.022
274857EASY ROAD;U1
Solar/Wind Harmer
10.665
274761LEE CO EC;2U
Adder
20.706
274766LEE CO EC;7U
Adder
20.462
276691AA1-018 GEN1
Solar/Wind Harmer
1.028
276158O29GEN2
Solar/Wind Harmer
10.723
276876AE1-163_GEN2
Solar/Wind Harmer
14.306
276164X3-005 C
Solar/Wind Harmer
1.479
970569AG2-363 GEN
Solar/Wind Harmer
62.951
274877BISHOP HL;1U
Solar/Wind Harmer
6.882
274812UNIV PK N;8U
Adder
9.813
274723RIVER EC ;12
Adder
34.022
276726Z2-087_GEN
Solar/Wind Harmer
14.981
939741AE1-205 GEN
Solar/Wind Harmer
37.882
274854TWINGROVE;U2
Solar/Wind Harmer
12.721
274751CRETE EC ;1U
Adder
8.31
274754CRETE EC ;4U
Adder
8.31
972175AH1-670 GEN
Solar/Wind Harmer
22.229
274880W4-005 GEN4
Solar/Wind Harmer
4.451
963831AG1-236 GEN
Solar/Wind Harmer
14.208
276615X2-022 GEN
Solar/Wind Harmer
2.739
274772LINCOLN ;3U
50/50
20.173
274707KENDALL ;2S
50/50
1.834
970707AG2-453 GEN
Solar/Wind Harmer
79.14
943121AE2-341 GEN
Solar/Wind Harmer
39.228
943591AF1-030 GEN
Solar/Wind Harmer
26.152
276897AD1-100 C
Solar/Wind Harmer
72.706
939351AE1-166 GEN
Solar/Wind Harmer
14.856
274872LEEDK;1U
Solar/Wind Harmer
0.622
972228AH1-698 GEN2
Adder
8.923
274682WAUKEGAN ;7U
Adder
43.121
276799AD1-013 GEN
Solar/Wind Harmer
5.264
946671AF1-331 GEN
Solar/Wind Harmer
0.997
274855GSG-6 ;RU
Solar/Wind Harmer
8.778
274850MENDOTA H;RU
Solar/Wind Harmer
6.103
276602WESTBROOK C
Solar/Wind Harmer
5.052
276863AD2-134 GEN
Solar/Wind Harmer
4.245
274676JOLIET 29;8U
Adder
70.255
274729ELWOOD EC;1P
Adder
38.878
274730ELWOOD EC;6P
Adder
38.863
274734ELWOOD EC;8P
Adder
38.863
274736ELWOOD EC;9P
Adder
38.863
959091AF2-200 GEN
Solar/Wind Harmer
46.661
276893AG1-478 C
Solar/Wind Harmer
0.974
970941AG2-585 GEN
Solar/Wind Harmer
28.775
276772AC2-154 GEN
Solar/Wind Harmer
6.419
276806AD2-047 C O1
Solar/Wind Harmer
24.626
972236AH1-702 GEN2
Adder
5.034
274800UNIV PARK;3U
Adder
13.022
972038AH1-567 GEN2
Adder
0.815
274858EASY ROAD;U2
Solar/Wind Harmer
10.665
274760LEE CO EC;1U
Adder
20.706
274767LEE CO EC;8U
Adder
20.462
274826FISK ;BP
Adder
24.181
276694AA1-018 GEN2
Solar/Wind Harmer
13.937
276805AD2-038 GEN
Solar/Wind Harmer
11.16
274802UNIV PARK;5U
Adder
12.653
276157O29GEN1
Solar/Wind Harmer
8.157
276889AE2-281 GEN
Solar/Wind Harmer
4.087
970571AG2-364 GEN
Solar/Wind Harmer
41.967
274878BISHOP HL;2U
Solar/Wind Harmer
6.882
965931AG1-462 GEN
Solar/Wind Harmer
51.499
274724RIVER EC ;11
Adder
33.679
942111AE2-223 GEN
Solar/Wind Harmer
15.527
274853TWINGROVE;U1
Solar/Wind Harmer
12.993
965091AG1-374 GEN
Solar/Wind Harmer
54.08
959611AF2-252 GEN
Solar/Wind Harmer
4.192
972231SS25-0005
Solar/Wind Harmer
16.135
972181SS23-001
Solar/Wind Harmer
10.085
274752CRETE EC ;2U
Adder
8.31
274753CRETE EC ;3U
Adder
8.31
276686W4-005 GEN3
Solar/Wind Harmer
4.451
274770LINCOLN ;1U
50/50
20.173
274771LINCOLN ;2U
50/50
20.173
274709KENDALL ;3S
50/50
2.042
274711KENDALL ;4S
50/50
2.042
274661LASCO STA;2U
50/50
18.804
972259AH1-714 GEN
50/50
52.779
274660LASCO STA;1U
50/50
19.043
971573AH1-285 GEN
Solar/Wind Harmer
22.127
274847GR RIDGE ;BU
Solar/Wind Harmer
12.737
274695ROCKY RD ;2P
Adder
27.369
274693ROCKY RD ;1P
Adder
27.1
274697ROCKY RD ;3P
Adder
7.435
274696ROCKY RD ;4P
Adder
28.011
962691AG1-118 GEN
Solar/Wind Harmer
73.702
970921AG2-575 GEN
Solar/Wind Harmer
24.44
970921AG2-575 GEN
Solar/Wind Harmer
5.684
274683WAUKEGAN ;8U
Adder
50.452
274683WAUKEGAN ;8U
Adder
42.529
274674JOLIET 9 ;6U
Adder
36.733
942991AE2-321 GEN
Solar/Wind Harmer
23.703
971333AH1-146 GEN
Solar/Wind Harmer
47.107
971335AH1-147 GEN
Solar/Wind Harmer
47.107
971341AH1-150 GEN
Solar/Wind Harmer
46.661
971343AH1-151 GEN
Solar/Wind Harmer
46.661
274888KELLY CRK;1U
Solar/Wind Harmer
13.591
274887GEN-1.85
Solar/Wind Harmer
12.27
276843GEN-1.7
Solar/Wind Harmer
1.32
958011AF2-095 GEN
Solar/Wind Harmer
33.148
274856ECOGROVE ;U1
Solar/Wind Harmer
7.664
276611AD2-172 GEN
Solar/Wind Harmer
5.816
938861AE1-114 GEN
Solar/Wind Harmer
18.38
274764LEE CO EC;5U
Adder
20.755
274765LEE CO EC;6U
Adder
20.755
274762LEE CO EC;3U
Adder
20.706
274763LEE CO EC;4U
Adder
20.511
276603SUBLETTE C
Solar/Wind Harmer
2.327
274879MINONK ;1U
Solar/Wind Harmer
14.955
958481AF2-142 GEN
Solar/Wind Harmer
33.128
274861TOP CROP ;1U
Solar/Wind Harmer
13.317
274862TOP CROP ;2U
Solar/Wind Harmer
11.12
972267AH1-718 GEN
Adder
9.073
958491AF2-143 GEN
Solar/Wind Harmer
32.633
274803UNIV PARK;6U
Adder
12.653
276741O09 GEN1
Solar/Wind Harmer
7.66
276708O09 GEN2
Solar/Wind Harmer
7.66
276872AE1-163_GEN1
Solar/Wind Harmer
14.306
274851PROVIDENC;RU
Solar/Wind Harmer
5.845
274849CRESCENT ;1U
Solar/Wind Harmer
3.795
276645AC1-214 GEN1
Solar/Wind Harmer
2.749
276646AC1-214 GEN2
Solar/Wind Harmer
2.749
276782AC1-033 GEN
Solar/Wind Harmer
8.132
274808UNIV PK N;4U
Adder
9.77
960611AF2-352 GEN
Solar/Wind Harmer
4.192
276763AC1-053 GEN1
Solar/Wind Harmer
5.712
276764AC1-053 GEN2
Solar/Wind Harmer
5.712
971993AH1-541 GEN
Solar/Wind Harmer
13.597
276668AB2-070 GEN1
Solar/Wind Harmer
3.298
276621W2-048 GEN
Solar/Wind Harmer
8.723
276838X2-022 GEN2
Solar/Wind Harmer
0.325
990512J1326
External Queue
11.370098114013672
990727J1377 G
External Queue
7.85197639465332
991092J1477
External Queue
6.023608684539795
990407J1304
External Queue
8.819581985473633
NYPJM->LTFIMP_NY
CLTF
2.188
WECLTFEXP_WEC->PJM
CLTF
8.641
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.929
CBM West 2LTFEXP_CBM-W2->PJM
CBM
65.661
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.464
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.622
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.136
MECLTFEXP_MEC->PJM
CLTF
27.127
SIGELTFEXP_SIGE->PJM
CLTF
0.04
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.009
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.826
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
TVALTFEXP_TVA->PJM
CLTF
2.262

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.77 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2162.5
MW Contribution:7.87
Bus #Bus NameTypeMW Contribution
274814UNIV PK N;0U
50/50
4.795
274807UNIV PK N;3U
50/50
4.785
274805UNIV PK N;1U
50/50
4.764
274811UNIV PK N;7U
50/50
4.753
960681AF2-359 GEN
Solar/Wind Harmer
10.343
270536AF1-215 GEN2
Solar/Wind Harmer
8.204
971769AH1-391 GEN
Solar/Wind Harmer
15.172
958391AF2-133 GEN
Solar/Wind Harmer
12.315
972037AH1-567 GEN1
Adder
0.142
972227AH1-698 GEN1
Adder
1.957
274675JOLIET 29;7U
Adder
22.546
274675JOLIET 29;7U
Adder
21.74
274687WILL CNTY;4U
Adder
20.505
274687WILL CNTY;4U
Adder
20.505
274728ELWOOD EC;5P
Adder
12.014
274731ELWOOD EC;2P
Adder
12.012
274733ELWOOD EC;3P
Adder
12.012
274735ELWOOD EC;4P
Adder
12.012
274827FISK ;RP
Adder
5.62
960591AF2-350 GEN
Solar/Wind Harmer
7.237
970833AG2-524 GEN
Solar/Wind Harmer
6.264
970833AG2-524 GEN
Solar/Wind Harmer
2.914
274775LINCOLN ;6U
Adder
4.422
274776LINCOLN ;7U
Adder
4.422
274777LINCOLN ;8U
Adder
4.422
274746AC1-111 G10
Adder
3.944
274751CRETE EC ;1U
50/50
5.251
274754CRETE EC ;4U
50/50
5.251
274813UNIV PK N;9U
50/50
0.26
274809UNIV PK N;5U
50/50
0.259
274812UNIV PK N;8U
50/50
4.753
966431AG1-512 GEN
50/50
1.664
970373AG2-245 GEN
Solar/Wind Harmer
45.027
270055AF2-134 C O1
Solar/Wind Harmer
5.469
958381AF2-132 GEN
Solar/Wind Harmer
13.706
964861AG1-349 GEN
Solar/Wind Harmer
11.629
971917AH1-482 GEN
Solar/Wind Harmer
13.42
940581AE2-045 GEN
Solar/Wind Harmer
11.219
971605AH1-302 GEN
Solar/Wind Harmer
9.593
274676JOLIET 29;8U
Adder
22.546
274732ELWOOD EC;7P
Adder
12.014
276776AD2-060 GEN
Solar/Wind Harmer
0.306
941551AE2-152 GEN
Solar/Wind Harmer
3.256
274871GR RIDGE ;2U
Solar/Wind Harmer
5.518
274674JOLIET 9 ;6U
Adder
11.046
274801UNIV PARK;4U
Adder
4.178
972207SS24-0001
Solar/Wind Harmer
15.723
274773LINCOLN ;4U
Adder
4.422
274774LINCOLN ;5U
Adder
4.422
276691AA1-018 GEN1
Solar/Wind Harmer
0.33
274745AC1-111 GEN9
Adder
3.944
274682WAUKEGAN ;7U
Adder
12.544
274828WAUKEGAN ;BP
Adder
7.693
276164X3-005 C
Solar/Wind Harmer
0.482
960751AF2-366 GEN
Solar/Wind Harmer
1.957
962781AG1-127 GEN
Solar/Wind Harmer
6.485
276901AD2-066 C O1
Solar/Wind Harmer
2.39
274872LEEDK;1U
Solar/Wind Harmer
5.58
971997AH1-543 GEN
Solar/Wind Harmer
10.544
276861AD2-134 GEN
Solar/Wind Harmer
1.195
276876AE1-163_GEN2
Solar/Wind Harmer
4.491
957471AF2-041 GEN
Solar/Wind Harmer
19.905
959081AF2-199 GEN
Solar/Wind Harmer
6.635
971067AG2-660 GEN
Solar/Wind Harmer
1.543
939401AE1-172 GEN
Solar/Wind Harmer
9.23
274723RIVER EC ;12
Adder
11.861
274822ROCKFORD ;11
Adder
12.982
972235AH1-702 GEN1
Adder
1.66
970819AG2-516 GEN
Solar/Wind Harmer
7.865
971475AH1-234 GEN
Solar/Wind Harmer
14.625
970569AG2-363 GEN
Solar/Wind Harmer
19.57
24791305MDL-5G
Solar/Wind Harmer
1.573
274857EASY ROAD;U1
Solar/Wind Harmer
3.077
274761LEE CO EC;2U
Adder
5.973
270102X2-052 ST
50/50
5.022
270100X2-052 CT1
50/50
4.627
270101X2-052 CT2
50/50
4.627
274808UNIV PK N;4U
50/50
4.733
965681AG1-436 GEN
Solar/Wind Harmer
34.222
965791AG1-447 GEN
Solar/Wind Harmer
17.509
24441505OLIV SLR
Solar/Wind Harmer
0.203
270526AF1-158 GEN
Solar/Wind Harmer
5.948
274803UNIV PARK;6U
Adder
4.513
972259AH1-714 GEN
Adder
14.013
274888KELLY CRK;1U
Solar/Wind Harmer
4.272
274887GEN-1.85
Solar/Wind Harmer
3.857
276843GEN-1.7
Solar/Wind Harmer
0.415
958011AF2-095 GEN
Solar/Wind Harmer
10.421
274847GR RIDGE ;BU
Solar/Wind Harmer
3.63
274674JOLIET 9 ;6U
Adder
11.046
274770LINCOLN ;1U
Adder
4.422
274771LINCOLN ;2U
Adder
4.422
274861TOP CROP ;1U
Solar/Wind Harmer
4.321
274862TOP CROP ;2U
Solar/Wind Harmer
3.608
958481AF2-142 GEN
Solar/Wind Harmer
10.643
945421AF1-207 GEN
Solar/Wind Harmer
9.915
957841AF2-078 GEN
Solar/Wind Harmer
4.267
971573AH1-285 GEN
Solar/Wind Harmer
6.003
274683WAUKEGAN ;8U
Adder
14.677
274683WAUKEGAN ;8U
Adder
12.372
274696ROCKY RD ;4P
Adder
7.926
274695ROCKY RD ;2P
Adder
7.743
274693ROCKY RD ;1P
Adder
7.667
274697ROCKY RD ;3P
Adder
2.103
958491AF2-143 GEN
Solar/Wind Harmer
10.386
962691AG1-118 GEN
Solar/Wind Harmer
20.538
970921AG2-575 GEN
Solar/Wind Harmer
6.82
970921AG2-575 GEN
Solar/Wind Harmer
1.586
274879MINONK ;1U
Solar/Wind Harmer
4.6
942991AE2-321 GEN
Solar/Wind Harmer
6.774
971333AH1-146 GEN
Solar/Wind Harmer
13.417
971335AH1-147 GEN
Solar/Wind Harmer
13.417
276872AE1-163_GEN1
Solar/Wind Harmer
4.491
971341AH1-150 GEN
Solar/Wind Harmer
13.27
274744AC1-111 GEN8
Adder
3.944
276868AE1-113 GEN
Solar/Wind Harmer
6.9
276882AE2-255 GEN
Solar/Wind Harmer
2.3
971177AH1-047 GEN
Solar/Wind Harmer
3.966
971411AH1-196 GEN
Solar/Wind Harmer
10.088
971675AH1-338 GEN
Solar/Wind Harmer
12.047
971171AH1-044 GEN
Solar/Wind Harmer
13.27
274823ROCKFORD ;21
Adder
12.888
276612AE2-035 GEN
Solar/Wind Harmer
1.672
24690905MDL-1G C
Solar/Wind Harmer
5.237
270180AB1-006 GEN1
Solar/Wind Harmer
4.691
946581AF1-322 GEN
Solar/Wind Harmer
6.674
24691005MDL-2G C
Solar/Wind Harmer
2.412
24697605MDL-3G C
Solar/Wind Harmer
2.405
24697905MDL-4G C
Solar/Wind Harmer
1.497
270181AB1-006 GEN2
Solar/Wind Harmer
0.467
971681AH1-341 GEN
Solar/Wind Harmer
9.691
926823AC1-168 GEN
Solar/Wind Harmer
2.776
274863CRW1-WTG
Solar/Wind Harmer
3.59
274864CRW2-WTG
Solar/Wind Harmer
3.59
961011AF2-392 GEN
Solar/Wind Harmer
6.893
970169AG2-114 GEN
Solar/Wind Harmer
6.244
957751AF2-069 GEN
Solar/Wind Harmer
0.284
274848CAMPGROVE;RU
Solar/Wind Harmer
3.933
946321AF1-296 GEN
Solar/Wind Harmer
6.269
971343AH1-151 GEN
Solar/Wind Harmer
13.27
274856ECOGROVE ;U1
Solar/Wind Harmer
2.204
276611AD2-172 GEN
Solar/Wind Harmer
1.672
938861AE1-114 GEN
Solar/Wind Harmer
5.296
274764LEE CO EC;5U
Adder
5.987
274765LEE CO EC;6U
Adder
5.987
274762LEE CO EC;3U
Adder
5.973
274763LEE CO EC;4U
Adder
5.917
276603SUBLETTE C
Solar/Wind Harmer
0.671
972267AH1-718 GEN
Adder
2.628
276741O09 GEN1
Solar/Wind Harmer
2.241
276708O09 GEN2
Solar/Wind Harmer
2.241
274851PROVIDENC;RU
Solar/Wind Harmer
1.764
274849CRESCENT ;1U
Solar/Wind Harmer
1.145
276645AC1-214 GEN1
Solar/Wind Harmer
0.83
276646AC1-214 GEN2
Solar/Wind Harmer
0.83
276782AC1-033 GEN
Solar/Wind Harmer
2.45
274766LEE CO EC;7U
Adder
5.903
276158O29GEN2
Solar/Wind Harmer
3.138
274877BISHOP HL;1U
Solar/Wind Harmer
2.073
971087AG2-675 GEN
Solar/Wind Harmer
0
274752CRETE EC ;2U
50/50
5.251
274753CRETE EC ;3U
50/50
5.251
274806UNIV PK N;2U
50/50
0.266
274815UNIV PK N;XU
50/50
0.261
274816UNIV PK N;YU
50/50
0.26
274810UNIV PK N;6U
50/50
0.26
270535AF1-215 GEN1
Solar/Wind Harmer
8.204
964401AG1-302 GEN
Solar/Wind Harmer
13.706
959141AF2-205 GEN
Solar/Wind Harmer
7.516
972231SS25-0005
Solar/Wind Harmer
9.609
972181SS23-001
Solar/Wind Harmer
6.006
274802UNIV PARK;5U
Adder
4.513
972228AH1-698 GEN2
Adder
2.78
274676JOLIET 29;8U
Adder
21.741
274730ELWOOD EC;6P
Adder
12.014
274734ELWOOD EC;8P
Adder
12.014
274736ELWOOD EC;9P
Adder
12.014
274729ELWOOD EC;1P
Adder
12.012
274826FISK ;BP
Adder
7.93
276772AC2-154 GEN
Solar/Wind Harmer
2.018
276806AD2-047 C O1
Solar/Wind Harmer
7.742
970941AG2-585 GEN
Solar/Wind Harmer
9.046
970707AG2-453 GEN
Solar/Wind Harmer
20.23
276893AG1-478 C
Solar/Wind Harmer
0.301
276897AD1-100 C
Solar/Wind Harmer
20.837
939351AE1-166 GEN
Solar/Wind Harmer
4.258
274800UNIV PARK;3U
Adder
4.178
972038AH1-567 GEN2
Adder
0.262
274772LINCOLN ;3U
Adder
4.422
276694AA1-018 GEN2
Solar/Wind Harmer
4.478
943121AE2-341 GEN
Solar/Wind Harmer
10.55
943591AF1-030 GEN
Solar/Wind Harmer
7.033
274682WAUKEGAN ;7U
Adder
12.544
276805AD2-038 GEN
Solar/Wind Harmer
3.552
274872LEEDK;1U
Solar/Wind Harmer
0.174
276799AD1-013 GEN
Solar/Wind Harmer
1.481
946671AF1-331 GEN
Solar/Wind Harmer
0.28
274855GSG-6 ;RU
Solar/Wind Harmer
2.471
274850MENDOTA H;RU
Solar/Wind Harmer
1.718
276602WESTBROOK C
Solar/Wind Harmer
1.422
276863AD2-134 GEN
Solar/Wind Harmer
1.195
276889AE2-281 GEN
Solar/Wind Harmer
1.283
959091AF2-200 GEN
Solar/Wind Harmer
13.27
972236AH1-702 GEN2
Adder
1.444
970571AG2-364 GEN
Solar/Wind Harmer
13.047
24755605MDL-5G
Solar/Wind Harmer
1.573
970781AG2-491 GEN
Solar/Wind Harmer
6.522
274724RIVER EC ;11
Adder
11.53
274858EASY ROAD;U2
Solar/Wind Harmer
3.077
274760LEE CO EC;1U
Adder
5.973
274767LEE CO EC;8U
Adder
5.903
276157O29GEN1
Solar/Wind Harmer
2.387
274878BISHOP HL;2U
Solar/Wind Harmer
2.073
24642205MAYFLWER
Adder
0.304
965931AG1-462 GEN
Solar/Wind Harmer
6.629
990662J1358
External Queue
6.744036674499512
NYPJM->LTFIMP_NY
CLTF
0.912
WECLTFEXP_WEC->PJM
CLTF
2.521
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.324
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.414
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.164
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.448
MECLTFEXP_MEC->PJM
CLTF
8.249
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.163
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.377
LAGNLTFEXP_LAGN->PJM
CLTF
3.009
TVALTFEXP_TVA->PJM
CLTF
0.829

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.77 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2162.5
MW Contribution:7.87
Bus #Bus NameTypeMW Contribution
274814UNIV PK N;0U
50/50
4.795
274807UNIV PK N;3U
50/50
4.785
274805UNIV PK N;1U
50/50
4.764
274811UNIV PK N;7U
50/50
4.753
960681AF2-359 GEN
Solar/Wind Harmer
10.343
270536AF1-215 GEN2
Solar/Wind Harmer
8.204
971769AH1-391 GEN
Solar/Wind Harmer
15.172
958391AF2-133 GEN
Solar/Wind Harmer
12.315
972037AH1-567 GEN1
Adder
0.142
972227AH1-698 GEN1
Adder
1.957
274675JOLIET 29;7U
Adder
22.546
274675JOLIET 29;7U
Adder
21.74
274687WILL CNTY;4U
Adder
20.505
274687WILL CNTY;4U
Adder
20.505
274728ELWOOD EC;5P
Adder
12.014
274731ELWOOD EC;2P
Adder
12.012
274733ELWOOD EC;3P
Adder
12.012
274735ELWOOD EC;4P
Adder
12.012
274827FISK ;RP
Adder
5.62
960591AF2-350 GEN
Solar/Wind Harmer
7.237
970833AG2-524 GEN
Solar/Wind Harmer
6.264
970833AG2-524 GEN
Solar/Wind Harmer
2.914
274775LINCOLN ;6U
Adder
4.422
274776LINCOLN ;7U
Adder
4.422
274777LINCOLN ;8U
Adder
4.422
274746AC1-111 G10
Adder
3.944
274744AC1-111 GEN8
Adder
3.944
276868AE1-113 GEN
Solar/Wind Harmer
6.9
276882AE2-255 GEN
Solar/Wind Harmer
2.3
971177AH1-047 GEN
Solar/Wind Harmer
3.966
971411AH1-196 GEN
Solar/Wind Harmer
10.088
971675AH1-338 GEN
Solar/Wind Harmer
12.047
971171AH1-044 GEN
Solar/Wind Harmer
13.27
274823ROCKFORD ;21
Adder
12.888
276612AE2-035 GEN
Solar/Wind Harmer
1.672
24690905MDL-1G C
Solar/Wind Harmer
5.237
270180AB1-006 GEN1
Solar/Wind Harmer
4.691
946581AF1-322 GEN
Solar/Wind Harmer
6.674
24691005MDL-2G C
Solar/Wind Harmer
2.412
24697605MDL-3G C
Solar/Wind Harmer
2.405
24697905MDL-4G C
Solar/Wind Harmer
1.497
270181AB1-006 GEN2
Solar/Wind Harmer
0.467
971681AH1-341 GEN
Solar/Wind Harmer
9.691
926823AC1-168 GEN
Solar/Wind Harmer
2.776
274863CRW1-WTG
Solar/Wind Harmer
3.59
274864CRW2-WTG
Solar/Wind Harmer
3.59
961011AF2-392 GEN
Solar/Wind Harmer
6.893
970169AG2-114 GEN
Solar/Wind Harmer
6.244
957751AF2-069 GEN
Solar/Wind Harmer
0.284
274848CAMPGROVE;RU
Solar/Wind Harmer
3.933
946321AF1-296 GEN
Solar/Wind Harmer
6.269
274751CRETE EC ;1U
50/50
5.251
274754CRETE EC ;4U
50/50
5.251
274813UNIV PK N;9U
50/50
0.26
274809UNIV PK N;5U
50/50
0.259
274812UNIV PK N;8U
50/50
4.753
966431AG1-512 GEN
50/50
1.664
970373AG2-245 GEN
Solar/Wind Harmer
45.027
270055AF2-134 C O1
Solar/Wind Harmer
5.469
958381AF2-132 GEN
Solar/Wind Harmer
13.706
964861AG1-349 GEN
Solar/Wind Harmer
11.629
971917AH1-482 GEN
Solar/Wind Harmer
13.42
940581AE2-045 GEN
Solar/Wind Harmer
11.219
971605AH1-302 GEN
Solar/Wind Harmer
9.593
274676JOLIET 29;8U
Adder
22.546
274732ELWOOD EC;7P
Adder
12.014
276776AD2-060 GEN
Solar/Wind Harmer
0.306
941551AE2-152 GEN
Solar/Wind Harmer
3.256
274871GR RIDGE ;2U
Solar/Wind Harmer
5.518
274674JOLIET 9 ;6U
Adder
11.046
274801UNIV PARK;4U
Adder
4.178
972207SS24-0001
Solar/Wind Harmer
15.723
274773LINCOLN ;4U
Adder
4.422
274774LINCOLN ;5U
Adder
4.422
276691AA1-018 GEN1
Solar/Wind Harmer
0.33
274745AC1-111 GEN9
Adder
3.944
274682WAUKEGAN ;7U
Adder
12.544
274828WAUKEGAN ;BP
Adder
7.693
276164X3-005 C
Solar/Wind Harmer
0.482
960751AF2-366 GEN
Solar/Wind Harmer
1.957
962781AG1-127 GEN
Solar/Wind Harmer
6.485
276901AD2-066 C O1
Solar/Wind Harmer
2.39
274872LEEDK;1U
Solar/Wind Harmer
5.58
971997AH1-543 GEN
Solar/Wind Harmer
10.544
276861AD2-134 GEN
Solar/Wind Harmer
1.195
276876AE1-163_GEN2
Solar/Wind Harmer
4.491
957471AF2-041 GEN
Solar/Wind Harmer
19.905
959081AF2-199 GEN
Solar/Wind Harmer
6.635
971067AG2-660 GEN
Solar/Wind Harmer
1.543
939401AE1-172 GEN
Solar/Wind Harmer
9.23
274723RIVER EC ;12
Adder
11.861
274822ROCKFORD ;11
Adder
12.982
972235AH1-702 GEN1
Adder
1.66
970819AG2-516 GEN
Solar/Wind Harmer
7.865
971475AH1-234 GEN
Solar/Wind Harmer
14.625
970569AG2-363 GEN
Solar/Wind Harmer
19.57
24791305MDL-5G
Solar/Wind Harmer
1.573
274857EASY ROAD;U1
Solar/Wind Harmer
3.077
274761LEE CO EC;2U
Adder
5.973
274766LEE CO EC;7U
Adder
5.903
276158O29GEN2
Solar/Wind Harmer
3.138
274877BISHOP HL;1U
Solar/Wind Harmer
2.073
971087AG2-675 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
5.022
270100X2-052 CT1
50/50
4.627
270101X2-052 CT2
50/50
4.627
274808UNIV PK N;4U
50/50
4.733
965681AG1-436 GEN
Solar/Wind Harmer
34.222
965791AG1-447 GEN
Solar/Wind Harmer
17.509
24441505OLIV SLR
Solar/Wind Harmer
0.203
270526AF1-158 GEN
Solar/Wind Harmer
5.948
274803UNIV PARK;6U
Adder
4.513
972259AH1-714 GEN
Adder
14.013
274888KELLY CRK;1U
Solar/Wind Harmer
4.272
274887GEN-1.85
Solar/Wind Harmer
3.857
276843GEN-1.7
Solar/Wind Harmer
0.415
958011AF2-095 GEN
Solar/Wind Harmer
10.421
274847GR RIDGE ;BU
Solar/Wind Harmer
3.63
274674JOLIET 9 ;6U
Adder
11.046
274770LINCOLN ;1U
Adder
4.422
274771LINCOLN ;2U
Adder
4.422
274861TOP CROP ;1U
Solar/Wind Harmer
4.321
274862TOP CROP ;2U
Solar/Wind Harmer
3.608
958481AF2-142 GEN
Solar/Wind Harmer
10.643
945421AF1-207 GEN
Solar/Wind Harmer
9.915
957841AF2-078 GEN
Solar/Wind Harmer
4.267
971573AH1-285 GEN
Solar/Wind Harmer
6.003
274683WAUKEGAN ;8U
Adder
14.677
274683WAUKEGAN ;8U
Adder
12.372
274696ROCKY RD ;4P
Adder
7.926
274695ROCKY RD ;2P
Adder
7.743
274693ROCKY RD ;1P
Adder
7.667
274697ROCKY RD ;3P
Adder
2.103
958491AF2-143 GEN
Solar/Wind Harmer
10.386
962691AG1-118 GEN
Solar/Wind Harmer
20.538
970921AG2-575 GEN
Solar/Wind Harmer
6.82
970921AG2-575 GEN
Solar/Wind Harmer
1.586
274879MINONK ;1U
Solar/Wind Harmer
4.6
942991AE2-321 GEN
Solar/Wind Harmer
6.774
971333AH1-146 GEN
Solar/Wind Harmer
13.417
971335AH1-147 GEN
Solar/Wind Harmer
13.417
276872AE1-163_GEN1
Solar/Wind Harmer
4.491
971341AH1-150 GEN
Solar/Wind Harmer
13.27
971343AH1-151 GEN
Solar/Wind Harmer
13.27
274856ECOGROVE ;U1
Solar/Wind Harmer
2.204
276611AD2-172 GEN
Solar/Wind Harmer
1.672
938861AE1-114 GEN
Solar/Wind Harmer
5.296
274764LEE CO EC;5U
Adder
5.987
274765LEE CO EC;6U
Adder
5.987
274762LEE CO EC;3U
Adder
5.973
274763LEE CO EC;4U
Adder
5.917
276603SUBLETTE C
Solar/Wind Harmer
0.671
972267AH1-718 GEN
Adder
2.628
276741O09 GEN1
Solar/Wind Harmer
2.241
276708O09 GEN2
Solar/Wind Harmer
2.241
274851PROVIDENC;RU
Solar/Wind Harmer
1.764
274849CRESCENT ;1U
Solar/Wind Harmer
1.145
276645AC1-214 GEN1
Solar/Wind Harmer
0.83
276646AC1-214 GEN2
Solar/Wind Harmer
0.83
276782AC1-033 GEN
Solar/Wind Harmer
2.45
274752CRETE EC ;2U
50/50
5.251
274753CRETE EC ;3U
50/50
5.251
274806UNIV PK N;2U
50/50
0.266
274815UNIV PK N;XU
50/50
0.261
274816UNIV PK N;YU
50/50
0.26
274810UNIV PK N;6U
50/50
0.26
270535AF1-215 GEN1
Solar/Wind Harmer
8.204
964401AG1-302 GEN
Solar/Wind Harmer
13.706
959141AF2-205 GEN
Solar/Wind Harmer
7.516
972231SS25-0005
Solar/Wind Harmer
9.609
972181SS23-001
Solar/Wind Harmer
6.006
274802UNIV PARK;5U
Adder
4.513
972228AH1-698 GEN2
Adder
2.78
274676JOLIET 29;8U
Adder
21.741
274730ELWOOD EC;6P
Adder
12.014
274734ELWOOD EC;8P
Adder
12.014
274736ELWOOD EC;9P
Adder
12.014
274729ELWOOD EC;1P
Adder
12.012
274826FISK ;BP
Adder
7.93
276772AC2-154 GEN
Solar/Wind Harmer
2.018
276806AD2-047 C O1
Solar/Wind Harmer
7.742
970941AG2-585 GEN
Solar/Wind Harmer
9.046
970707AG2-453 GEN
Solar/Wind Harmer
20.23
276893AG1-478 C
Solar/Wind Harmer
0.301
276897AD1-100 C
Solar/Wind Harmer
20.837
939351AE1-166 GEN
Solar/Wind Harmer
4.258
274800UNIV PARK;3U
Adder
4.178
972038AH1-567 GEN2
Adder
0.262
274772LINCOLN ;3U
Adder
4.422
276694AA1-018 GEN2
Solar/Wind Harmer
4.478
943121AE2-341 GEN
Solar/Wind Harmer
10.55
943591AF1-030 GEN
Solar/Wind Harmer
7.033
274682WAUKEGAN ;7U
Adder
12.544
276805AD2-038 GEN
Solar/Wind Harmer
3.552
274872LEEDK;1U
Solar/Wind Harmer
0.174
276799AD1-013 GEN
Solar/Wind Harmer
1.481
946671AF1-331 GEN
Solar/Wind Harmer
0.28
274855GSG-6 ;RU
Solar/Wind Harmer
2.471
274850MENDOTA H;RU
Solar/Wind Harmer
1.718
276602WESTBROOK C
Solar/Wind Harmer
1.422
276863AD2-134 GEN
Solar/Wind Harmer
1.195
276889AE2-281 GEN
Solar/Wind Harmer
1.283
959091AF2-200 GEN
Solar/Wind Harmer
13.27
972236AH1-702 GEN2
Adder
1.444
970571AG2-364 GEN
Solar/Wind Harmer
13.047
24755605MDL-5G
Solar/Wind Harmer
1.573
970781AG2-491 GEN
Solar/Wind Harmer
6.522
274724RIVER EC ;11
Adder
11.53
274858EASY ROAD;U2
Solar/Wind Harmer
3.077
274760LEE CO EC;1U
Adder
5.973
274767LEE CO EC;8U
Adder
5.903
276157O29GEN1
Solar/Wind Harmer
2.387
274878BISHOP HL;2U
Solar/Wind Harmer
2.073
24642205MAYFLWER
Adder
0.304
965931AG1-462 GEN
Solar/Wind Harmer
6.629
990662J1358
External Queue
6.744027137756348
NYPJM->LTFIMP_NY
CLTF
0.912
WECLTFEXP_WEC->PJM
CLTF
2.521
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.324
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.414
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.164
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.448
MECLTFEXP_MEC->PJM
CLTF
8.249
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.163
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.377
LAGNLTFEXP_LAGN->PJM
CLTF
3.009
TVALTFEXP_TVA->PJM
CLTF
0.829

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.41 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2155.91
MW Contribution:7.35
Bus #Bus NameTypeMW Contribution
960681AF2-359 GEN
Solar/Wind Harmer
9.735
270536AF1-215 GEN2
Solar/Wind Harmer
8.292
958391AF2-133 GEN
Solar/Wind Harmer
13.145
971769AH1-391 GEN
Solar/Wind Harmer
13.415
24690905MDL-1G C
Solar/Wind Harmer
6.805
270180AB1-006 GEN1
Solar/Wind Harmer
6.096
946581AF1-322 GEN
Solar/Wind Harmer
8.671
24691005MDL-2G C
Solar/Wind Harmer
3.135
24697605MDL-3G C
Solar/Wind Harmer
3.125
24697905MDL-4G C
Solar/Wind Harmer
1.945
270181AB1-006 GEN2
Solar/Wind Harmer
0.606
274814UNIV PK N;0U
Adder
4.113
274807UNIV PK N;3U
Adder
4.104
274805UNIV PK N;1U
Adder
4.086
274811UNIV PK N;7U
Adder
4.077
24386205FR-12G C
Solar/Wind Harmer
3.25
24386405FR-21G C
Solar/Wind Harmer
3.261
24386605FR-22G C
Solar/Wind Harmer
3.261
24387005FR-3G C
Solar/Wind Harmer
2.999
972037AH1-567 GEN1
Adder
0.128
963841AG1-237 GEN
Solar/Wind Harmer
7.586
972227AH1-698 GEN1
Adder
1.785
274675JOLIET 29;7U
Adder
20.565
274675JOLIET 29;7U
Adder
19.831
274728ELWOOD EC;5P
Adder
10.987
274731ELWOOD EC;2P
Adder
10.985
274733ELWOOD EC;3P
Adder
10.985
274735ELWOOD EC;4P
Adder
10.985
274687WILL CNTY;4U
Adder
18.656
274687WILL CNTY;4U
Adder
18.656
270102X2-052 ST
50/50
4.742
270100X2-052 CT1
50/50
4.369
270101X2-052 CT2
50/50
4.369
965681AG1-436 GEN
Solar/Wind Harmer
32.211
965791AG1-447 GEN
Solar/Wind Harmer
16.48
24441505OLIV SLR
Solar/Wind Harmer
0.18
270526AF1-158 GEN
Solar/Wind Harmer
5.13
945421AF1-207 GEN
Solar/Wind Harmer
12.672
957841AF2-078 GEN
Solar/Wind Harmer
5.453
274808UNIV PK N;4U
Adder
4.059
966841AG1-555 GEN
Solar/Wind Harmer
1.902
274803UNIV PARK;6U
Adder
4.085
972259AH1-714 GEN
Adder
12.817
274847GR RIDGE ;BU
Solar/Wind Harmer
3.338
274751CRETE EC ;1U
50/50
4.79
274754CRETE EC ;4U
50/50
4.79
970373AG2-245 GEN
Solar/Wind Harmer
44.292
270055AF2-134 C O1
Solar/Wind Harmer
5.528
958381AF2-132 GEN
Solar/Wind Harmer
14.312
964861AG1-349 GEN
Solar/Wind Harmer
12.194
971917AH1-482 GEN
Solar/Wind Harmer
14.072
940581AE2-045 GEN
Solar/Wind Harmer
12.574
971605AH1-302 GEN
Solar/Wind Harmer
10.752
24791305MDL-5G
Solar/Wind Harmer
2.044
274812UNIV PK N;8U
Adder
4.077
24385905FR-11G C
Solar/Wind Harmer
6.302
24387305FR-4G C
Solar/Wind Harmer
3.853
274676JOLIET 29;8U
Adder
20.565
274732ELWOOD EC;7P
Adder
10.987
274871GR RIDGE ;2U
Solar/Wind Harmer
5.075
941551AE2-152 GEN
Solar/Wind Harmer
2.985
274674JOLIET 9 ;6U
Adder
10.076
276776AD2-060 GEN
Solar/Wind Harmer
0.277
276691AA1-018 GEN1
Solar/Wind Harmer
0.304
274745AC1-111 GEN9
Adder
3.628
972207SS24-0001
Solar/Wind Harmer
14.291
274773LINCOLN ;4U
Adder
4.02
274774LINCOLN ;5U
Adder
4.02
274801UNIV PARK;4U
Adder
3.76
274682WAUKEGAN ;7U
Adder
11.562
274828WAUKEGAN ;BP
Adder
7.094
963741AG1-226 GEN
Solar/Wind Harmer
28.579
276901AD2-066 C O1
Solar/Wind Harmer
2.226
960751AF2-366 GEN
Solar/Wind Harmer
1.813
962781AG1-127 GEN
Solar/Wind Harmer
6.009
274872LEEDK;1U
Solar/Wind Harmer
5.175
971997AH1-543 GEN
Solar/Wind Harmer
9.86
276876AE1-163_GEN2
Solar/Wind Harmer
4.202
939401AE1-172 GEN
Solar/Wind Harmer
8.679
276861AD2-134 GEN
Solar/Wind Harmer
1.112
957471AF2-041 GEN
Solar/Wind Harmer
18.562
959081AF2-199 GEN
Solar/Wind Harmer
6.187
971067AG2-660 GEN
Solar/Wind Harmer
1.439
274822ROCKFORD ;11
Adder
12.109
972235AH1-702 GEN1
Adder
1.55
970569AG2-363 GEN
Solar/Wind Harmer
18.433
970819AG2-516 GEN
Solar/Wind Harmer
7.351
971475AH1-234 GEN
Solar/Wind Harmer
13.678
274761LEE CO EC;2U
Adder
5.612
274766LEE CO EC;7U
Adder
5.546
274723RIVER EC ;12
Adder
10.286
274752CRETE EC ;2U
50/50
4.79
274753CRETE EC ;3U
50/50
4.79
270535AF1-215 GEN1
Solar/Wind Harmer
8.292
964401AG1-302 GEN
Solar/Wind Harmer
14.312
959141AF2-205 GEN
Solar/Wind Harmer
8.18
972231SS25-0005
Solar/Wind Harmer
8.764
972181SS23-001
Solar/Wind Harmer
5.477
24755605MDL-5G
Solar/Wind Harmer
2.044
970781AG2-491 GEN
Solar/Wind Harmer
8.474
274802UNIV PARK;5U
Adder
4.085
972228AH1-698 GEN2
Adder
2.536
274676JOLIET 29;8U
Adder
19.831
274730ELWOOD EC;6P
Adder
10.987
274734ELWOOD EC;8P
Adder
10.987
970833AG2-524 GEN
Solar/Wind Harmer
5.758
970833AG2-524 GEN
Solar/Wind Harmer
2.678
960591AF2-350 GEN
Solar/Wind Harmer
6.544
274827FISK ;RP
Adder
5.052
274746AC1-111 G10
Adder
3.628
274744AC1-111 GEN8
Adder
3.628
274775LINCOLN ;6U
Adder
4.02
274776LINCOLN ;7U
Adder
4.02
274777LINCOLN ;8U
Adder
4.02
276868AE1-113 GEN
Solar/Wind Harmer
6.42
276882AE2-255 GEN
Solar/Wind Harmer
2.14
971177AH1-047 GEN
Solar/Wind Harmer
3.681
971411AH1-196 GEN
Solar/Wind Harmer
9.375
971675AH1-338 GEN
Solar/Wind Harmer
11.212
971171AH1-044 GEN
Solar/Wind Harmer
12.375
274823ROCKFORD ;21
Adder
12.021
276612AE2-035 GEN
Solar/Wind Harmer
1.565
274863CRW1-WTG
Solar/Wind Harmer
3.411
274864CRW2-WTG
Solar/Wind Harmer
3.411
926823AC1-168 GEN
Solar/Wind Harmer
2.626
971681AH1-341 GEN
Solar/Wind Harmer
2.594
274861TOP CROP ;1U
Solar/Wind Harmer
3.981
274862TOP CROP ;2U
Solar/Wind Harmer
3.324
274674JOLIET 9 ;6U
Adder
10.076
274888KELLY CRK;1U
Solar/Wind Harmer
3.864
274887GEN-1.85
Solar/Wind Harmer
3.488
276843GEN-1.7
Solar/Wind Harmer
0.375
958011AF2-095 GEN
Solar/Wind Harmer
9.423
958481AF2-142 GEN
Solar/Wind Harmer
9.802
274770LINCOLN ;1U
Adder
4.02
274771LINCOLN ;2U
Adder
4.02
971573AH1-285 GEN
Solar/Wind Harmer
5.533
274683WAUKEGAN ;8U
Adder
13.534
274683WAUKEGAN ;8U
Adder
11.408
958491AF2-143 GEN
Solar/Wind Harmer
9.627
274695ROCKY RD ;2P
Adder
7.144
274693ROCKY RD ;1P
Adder
7.074
274697ROCKY RD ;3P
Adder
1.941
274696ROCKY RD ;4P
Adder
7.312
970241AG2-163 GEN
Solar/Wind Harmer
15.877
274879MINONK ;1U
Solar/Wind Harmer
4.28
962691AG1-118 GEN
Solar/Wind Harmer
19.015
970921AG2-575 GEN
Solar/Wind Harmer
6.319
970921AG2-575 GEN
Solar/Wind Harmer
1.47
942991AE2-321 GEN
Solar/Wind Harmer
6.285
276872AE1-163_GEN1
Solar/Wind Harmer
4.202
971333AH1-146 GEN
Solar/Wind Harmer
12.477
971335AH1-147 GEN
Solar/Wind Harmer
12.477
971341AH1-150 GEN
Solar/Wind Harmer
12.375
971343AH1-151 GEN
Solar/Wind Harmer
12.375
274856ECOGROVE ;U1
Solar/Wind Harmer
2.062
276611AD2-172 GEN
Solar/Wind Harmer
1.565
274764LEE CO EC;5U
Adder
5.625
274765LEE CO EC;6U
Adder
5.625
274762LEE CO EC;3U
Adder
5.612
274763LEE CO EC;4U
Adder
5.559
972267AH1-718 GEN
Adder
2.48
274736ELWOOD EC;9P
Adder
10.987
274729ELWOOD EC;1P
Adder
10.985
970707AG2-453 GEN
Solar/Wind Harmer
18.533
276897AD1-100 C
Solar/Wind Harmer
19.101
939351AE1-166 GEN
Solar/Wind Harmer
3.903
276893AG1-478 C
Solar/Wind Harmer
0.274
276772AC2-154 GEN
Solar/Wind Harmer
1.825
276806AD2-047 C O1
Solar/Wind Harmer
7.001
970941AG2-585 GEN
Solar/Wind Harmer
8.18
276694AA1-018 GEN2
Solar/Wind Harmer
4.124
274826FISK ;BP
Adder
7.129
274772LINCOLN ;3U
Adder
4.02
943121AE2-341 GEN
Solar/Wind Harmer
9.708
943591AF1-030 GEN
Solar/Wind Harmer
6.472
274800UNIV PARK;3U
Adder
3.76
972038AH1-567 GEN2
Adder
0.235
274682WAUKEGAN ;7U
Adder
11.562
276805AD2-038 GEN
Solar/Wind Harmer
3.292
274872LEEDK;1U
Solar/Wind Harmer
0.161
276889AE2-281 GEN
Solar/Wind Harmer
1.201
276799AD1-013 GEN
Solar/Wind Harmer
1.378
946671AF1-331 GEN
Solar/Wind Harmer
0.261
274855GSG-6 ;RU
Solar/Wind Harmer
2.3
274850MENDOTA H;RU
Solar/Wind Harmer
1.599
276602WESTBROOK C
Solar/Wind Harmer
1.324
276863AD2-134 GEN
Solar/Wind Harmer
1.112
959091AF2-200 GEN
Solar/Wind Harmer
12.375
972236AH1-702 GEN2
Adder
1.348
970571AG2-364 GEN
Solar/Wind Harmer
12.289
274760LEE CO EC;1U
Adder
5.612
274767LEE CO EC;8U
Adder
5.546
274724RIVER EC ;11
Adder
9.963
NYPJM->LTFIMP_NY
CLTF
0.908
LGEELTFEXP_LGEE->PJM
CLTF
0.683
WECLTFEXP_WEC->PJM
CLTF
2.351
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.164
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.179
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.001
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.086
MECLTFEXP_MEC->PJM
CLTF
8.227
SIGELTFEXP_SIGE->PJM
CLTF
0.101
LAGNLTFEXP_LAGN->PJM
CLTF
4.035
TVALTFEXP_TVA->PJM
CLTF
1.433

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#671_05COOK 345_M2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#671_05COOK 345_M2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.64 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1973.33
MW Contribution:5.75
Bus #Bus NameTypeMW Contribution
274751CRETE EC ;1U
50/50
5.653
274754CRETE EC ;4U
50/50
5.653
970023AG2-014 GEN
50/50
2.198
970783AG2-492 GEN
50/50
2.198
274813UNIV PK N;9U
50/50
0.256
274809UNIV PK N;5U
50/50
0.254
274812UNIV PK N;8U
50/50
4.665
966431AG1-512 GEN
50/50
1.633
970373AG2-245 GEN
Solar/Wind Harmer
60.799
270055AF2-134 C O1
Solar/Wind Harmer
7.433
958381AF2-132 GEN
Solar/Wind Harmer
18.779
964861AG1-349 GEN
Solar/Wind Harmer
15.95
971917AH1-482 GEN
Solar/Wind Harmer
18.406
940581AE2-045 GEN
Solar/Wind Harmer
15.653
971605AH1-302 GEN
Solar/Wind Harmer
13.385
24791305MDL-5G
Solar/Wind Harmer
2.28
24385905FR-11G C
Solar/Wind Harmer
6.872
24387305FR-4G C
Solar/Wind Harmer
4.201
963741AG1-226 GEN
Solar/Wind Harmer
29.887
274723RIVER EC ;12
Adder
10.823
274801UNIV PARK;4U
Adder
3.427
276164X3-005 C
Solar/Wind Harmer
0.41
276776AD2-060 GEN
Solar/Wind Harmer
0.245
276691AA1-018 GEN1
Solar/Wind Harmer
0.267
274676JOLIET 29;8U
Adder
17.609
274732ELWOOD EC;7P
Adder
9.373
274674JOLIET 9 ;6U
Adder
8.449
276876AE1-163_GEN2
Solar/Wind Harmer
3.571
276901AD2-066 C O1
Solar/Wind Harmer
1.841
941551AE2-152 GEN
Solar/Wind Harmer
2.364
274871GR RIDGE ;2U
Solar/Wind Harmer
3.966
970569AG2-363 GEN
Solar/Wind Harmer
15.441
274682WAUKEGAN ;7U
Adder
9.249
274828WAUKEGAN ;BP
Adder
5.674
971997AH1-543 GEN
Solar/Wind Harmer
7.782
274745AC1-111 GEN9
Adder
2.759
274822ROCKFORD ;11
Adder
9.459
960751AF2-366 GEN
Solar/Wind Harmer
1.381
962781AG1-127 GEN
Solar/Wind Harmer
4.577
972235AH1-702 GEN1
Adder
1.21
274872LEEDK;1U
Solar/Wind Harmer
3.941
970819AG2-516 GEN
Solar/Wind Harmer
5.749
957471AF2-041 GEN
Solar/Wind Harmer
14.369
959081AF2-199 GEN
Solar/Wind Harmer
4.79
971067AG2-660 GEN
Solar/Wind Harmer
1.114
939401AE1-172 GEN
Solar/Wind Harmer
6.667
971475AH1-234 GEN
Solar/Wind Harmer
10.714
274761LEE CO EC;2U
Adder
4.388
274766LEE CO EC;7U
Adder
4.336
276861AD2-134 GEN
Solar/Wind Harmer
0.169
274814UNIV PK N;0U
50/50
4.706
274807UNIV PK N;3U
50/50
4.696
274805UNIV PK N;1U
50/50
4.675
274811UNIV PK N;7U
50/50
4.665
960681AF2-359 GEN
Solar/Wind Harmer
13.729
270536AF1-215 GEN2
Solar/Wind Harmer
11.151
971769AH1-391 GEN
Solar/Wind Harmer
19.638
958391AF2-133 GEN
Solar/Wind Harmer
16.967
24690905MDL-1G C
Solar/Wind Harmer
7.591
270180AB1-006 GEN1
Solar/Wind Harmer
6.8
946581AF1-322 GEN
Solar/Wind Harmer
9.674
24691005MDL-2G C
Solar/Wind Harmer
3.497
24697605MDL-3G C
Solar/Wind Harmer
3.486
24697905MDL-4G C
Solar/Wind Harmer
2.17
270181AB1-006 GEN2
Solar/Wind Harmer
0.676
24386205FR-12G C
Solar/Wind Harmer
3.543
24386405FR-21G C
Solar/Wind Harmer
3.556
24386605FR-22G C
Solar/Wind Harmer
3.556
24387005FR-3G C
Solar/Wind Harmer
3.271
963841AG1-237 GEN
Solar/Wind Harmer
8.11
972037AH1-567 GEN1
Adder
0.124
274827FISK ;RP
Adder
4.686
972227AH1-698 GEN1
Adder
1.531
274687WILL CNTY;4U
Adder
16.302
274687WILL CNTY;4U
Adder
16.302
960591AF2-350 GEN
Solar/Wind Harmer
5.799
274675JOLIET 29;7U
Adder
17.607
274675JOLIET 29;7U
Adder
16.978
274728ELWOOD EC;5P
Adder
9.373
274731ELWOOD EC;2P
Adder
9.366
274733ELWOOD EC;3P
Adder
9.366
274735ELWOOD EC;4P
Adder
9.366
971771AH1-392 GEN
Solar/Wind Harmer
4.903
276868AE1-113 GEN
Solar/Wind Harmer
5.379
276882AE2-255 GEN
Solar/Wind Harmer
1.793
970833AG2-524 GEN
Solar/Wind Harmer
4.52
970833AG2-524 GEN
Solar/Wind Harmer
2.102
274746AC1-111 G10
Adder
2.759
274744AC1-111 GEN8
Adder
2.759
971177AH1-047 GEN
Solar/Wind Harmer
2.874
926823AC1-168 GEN
Solar/Wind Harmer
2.105
971411AH1-196 GEN
Solar/Wind Harmer
7.331
274823ROCKFORD ;21
Adder
9.39
971171AH1-044 GEN
Solar/Wind Harmer
9.58
276612AE2-035 GEN
Solar/Wind Harmer
1.223
971675AH1-338 GEN
Solar/Wind Harmer
8.592
270102X2-052 ST
50/50
6.583
270100X2-052 CT1
50/50
6.066
270101X2-052 CT2
50/50
6.066
274808UNIV PK N;4U
50/50
4.645
965681AG1-436 GEN
Solar/Wind Harmer
45.424
965791AG1-447 GEN
Solar/Wind Harmer
23.24
24441505OLIV SLR
Solar/Wind Harmer
0.263
270526AF1-158 GEN
Solar/Wind Harmer
7.652
945421AF1-207 GEN
Solar/Wind Harmer
14.345
957841AF2-078 GEN
Solar/Wind Harmer
6.173
966841AG1-555 GEN
Solar/Wind Harmer
2.074
274803UNIV PARK;6U
Adder
3.936
970241AG2-163 GEN
Solar/Wind Harmer
16.604
274861TOP CROP ;1U
Solar/Wind Harmer
3.519
274862TOP CROP ;2U
Solar/Wind Harmer
2.939
274888KELLY CRK;1U
Solar/Wind Harmer
3.424
274887GEN-1.85
Solar/Wind Harmer
3.091
276843GEN-1.7
Solar/Wind Harmer
0.333
958011AF2-095 GEN
Solar/Wind Harmer
8.35
958481AF2-142 GEN
Solar/Wind Harmer
8.609
958491AF2-143 GEN
Solar/Wind Harmer
8.343
274674JOLIET 9 ;6U
Adder
8.449
276872AE1-163_GEN1
Solar/Wind Harmer
3.571
274879MINONK ;1U
Solar/Wind Harmer
3.586
972259AH1-714 GEN
Adder
9.926
274847GR RIDGE ;BU
Solar/Wind Harmer
2.609
274683WAUKEGAN ;8U
Adder
10.824
274683WAUKEGAN ;8U
Adder
9.124
274696ROCKY RD ;4P
Adder
5.674
274695ROCKY RD ;2P
Adder
5.542
274693ROCKY RD ;1P
Adder
5.488
274697ROCKY RD ;3P
Adder
1.506
942991AE2-321 GEN
Solar/Wind Harmer
4.91
971333AH1-146 GEN
Solar/Wind Harmer
9.696
971335AH1-147 GEN
Solar/Wind Harmer
9.696
962691AG1-118 GEN
Solar/Wind Harmer
14.47
970921AG2-575 GEN
Solar/Wind Harmer
4.813
970921AG2-575 GEN
Solar/Wind Harmer
1.119
971341AH1-150 GEN
Solar/Wind Harmer
9.58
971343AH1-151 GEN
Solar/Wind Harmer
9.58
274856ECOGROVE ;U1
Solar/Wind Harmer
1.612
276611AD2-172 GEN
Solar/Wind Harmer
1.223
274764LEE CO EC;5U
Adder
4.398
274765LEE CO EC;6U
Adder
4.398
274762LEE CO EC;3U
Adder
4.388
274763LEE CO EC;4U
Adder
4.347
972267AH1-718 GEN
Adder
1.941
274752CRETE EC ;2U
50/50
5.653
274753CRETE EC ;3U
50/50
5.653
274806UNIV PK N;2U
50/50
0.261
274815UNIV PK N;XU
50/50
0.256
274816UNIV PK N;YU
50/50
0.256
274810UNIV PK N;6U
50/50
0.255
270535AF1-215 GEN1
Solar/Wind Harmer
11.151
964401AG1-302 GEN
Solar/Wind Harmer
18.779
959141AF2-205 GEN
Solar/Wind Harmer
10.407
972231SS25-0005
Solar/Wind Harmer
10.343
972181SS23-001
Solar/Wind Harmer
6.464
24755605MDL-5G
Solar/Wind Harmer
2.28
970781AG2-491 GEN
Solar/Wind Harmer
9.453
274802UNIV PARK;5U
Adder
3.936
274826FISK ;BP
Adder
6.612
274724RIVER EC ;11
Adder
10.456
274800UNIV PARK;3U
Adder
3.427
972038AH1-567 GEN2
Adder
0.215
972228AH1-698 GEN2
Adder
2.176
276772AC2-154 GEN
Solar/Wind Harmer
1.617
276806AD2-047 C O1
Solar/Wind Harmer
6.204
970941AG2-585 GEN
Solar/Wind Harmer
7.249
276694AA1-018 GEN2
Solar/Wind Harmer
3.622
274676JOLIET 29;8U
Adder
16.98
274730ELWOOD EC;6P
Adder
9.373
274734ELWOOD EC;8P
Adder
9.373
274736ELWOOD EC;9P
Adder
9.373
274729ELWOOD EC;1P
Adder
9.366
276893AG1-478 C
Solar/Wind Harmer
0.236
276805AD2-038 GEN
Solar/Wind Harmer
2.853
276889AE2-281 GEN
Solar/Wind Harmer
1.02
276897AD1-100 C
Solar/Wind Harmer
15.126
939351AE1-166 GEN
Solar/Wind Harmer
3.091
970571AG2-364 GEN
Solar/Wind Harmer
10.294
274682WAUKEGAN ;7U
Adder
9.249
972236AH1-702 GEN2
Adder
1.052
274872LEEDK;1U
Solar/Wind Harmer
0.123
959091AF2-200 GEN
Solar/Wind Harmer
9.58
276799AD1-013 GEN
Solar/Wind Harmer
1.056
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274760LEE CO EC;1U
Adder
4.388
274767LEE CO EC;8U
Adder
4.336
24642205MAYFLWER
Adder
0.295
274855GSG-6 ;RU
Solar/Wind Harmer
0.35
276863AD2-134 GEN
Solar/Wind Harmer
0.169
991312J1772
External Queue
15.900324821472168
990762J1386
External Queue
8.400053977966309
991332J1785
External Queue
7.063979625701904
990577J1339
External Queue
12.615545272827148
990582J1340
External Queue
12.615545272827148
990662J1358
External Queue
11.088888168334961
991247J1684 G
External Queue
10.119192123413086
NYPJM->LTFIMP_NY
CLTF
0.796
LGEELTFEXP_LGEE->PJM
CLTF
0.311
WECLTFEXP_WEC->PJM
CLTF
1.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.605
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.22
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.409
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.464
MECLTFEXP_MEC->PJM
CLTF
6.512
SIGELTFEXP_SIGE->PJM
CLTF
0.074
LAGNLTFEXP_LAGN->PJM
CLTF
3.032
TVALTFEXP_TVA->PJM
CLTF
1.026

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#10997___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#10997___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.54 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1971.58
MW Contribution:5.75
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
6.583
270100X2-052 CT1
50/50
6.066
270101X2-052 CT2
50/50
6.066
274808UNIV PK N;4U
50/50
4.644
965681AG1-436 GEN
Solar/Wind Harmer
45.423
965791AG1-447 GEN
Solar/Wind Harmer
23.239
24441505OLIV SLR
Solar/Wind Harmer
0.263
270526AF1-158 GEN
Solar/Wind Harmer
7.65
945421AF1-207 GEN
Solar/Wind Harmer
14.344
957841AF2-078 GEN
Solar/Wind Harmer
6.173
966841AG1-555 GEN
Solar/Wind Harmer
2.074
274803UNIV PARK;6U
Adder
3.935
970241AG2-163 GEN
Solar/Wind Harmer
16.603
274861TOP CROP ;1U
Solar/Wind Harmer
3.519
274862TOP CROP ;2U
Solar/Wind Harmer
2.938
274888KELLY CRK;1U
Solar/Wind Harmer
3.423
274887GEN-1.85
Solar/Wind Harmer
3.091
274752CRETE EC ;2U
50/50
5.652
274753CRETE EC ;3U
50/50
5.652
274806UNIV PK N;2U
50/50
0.261
274815UNIV PK N;XU
50/50
0.256
274816UNIV PK N;YU
50/50
0.256
274810UNIV PK N;6U
50/50
0.255
270535AF1-215 GEN1
Solar/Wind Harmer
11.15
276843GEN-1.7
Solar/Wind Harmer
0.333
958011AF2-095 GEN
Solar/Wind Harmer
8.349
958481AF2-142 GEN
Solar/Wind Harmer
8.608
958491AF2-143 GEN
Solar/Wind Harmer
8.342
274674JOLIET 9 ;6U
Adder
8.448
276872AE1-163_GEN1
Solar/Wind Harmer
3.57
274751CRETE EC ;1U
50/50
5.652
274754CRETE EC ;4U
50/50
5.652
970023AG2-014 GEN
50/50
2.198
970783AG2-492 GEN
50/50
2.198
274813UNIV PK N;9U
50/50
0.256
274809UNIV PK N;5U
50/50
0.254
274812UNIV PK N;8U
50/50
4.665
966431AG1-512 GEN
50/50
1.633
970373AG2-245 GEN
Solar/Wind Harmer
60.796
270055AF2-134 C O1
Solar/Wind Harmer
7.433
958381AF2-132 GEN
Solar/Wind Harmer
18.778
964861AG1-349 GEN
Solar/Wind Harmer
15.949
971917AH1-482 GEN
Solar/Wind Harmer
18.405
940581AE2-045 GEN
Solar/Wind Harmer
15.652
971605AH1-302 GEN
Solar/Wind Harmer
13.384
24791305MDL-5G
Solar/Wind Harmer
2.28
24385905FR-11G C
Solar/Wind Harmer
6.871
24387305FR-4G C
Solar/Wind Harmer
4.201
963741AG1-226 GEN
Solar/Wind Harmer
29.885
274723RIVER EC ;12
Adder
10.822
274801UNIV PARK;4U
Adder
3.427
276164X3-005 C
Solar/Wind Harmer
0.41
276776AD2-060 GEN
Solar/Wind Harmer
0.245
276691AA1-018 GEN1
Solar/Wind Harmer
0.267
274676JOLIET 29;8U
Adder
17.607
274732ELWOOD EC;7P
Adder
9.372
274674JOLIET 9 ;6U
Adder
8.448
276876AE1-163_GEN2
Solar/Wind Harmer
3.57
276901AD2-066 C O1
Solar/Wind Harmer
1.84
941551AE2-152 GEN
Solar/Wind Harmer
2.364
274871GR RIDGE ;2U
Solar/Wind Harmer
3.966
970569AG2-363 GEN
Solar/Wind Harmer
15.439
274682WAUKEGAN ;7U
Adder
9.248
274828WAUKEGAN ;BP
Adder
5.673
971997AH1-543 GEN
Solar/Wind Harmer
7.781
274745AC1-111 GEN9
Adder
2.759
274822ROCKFORD ;11
Adder
9.458
960751AF2-366 GEN
Solar/Wind Harmer
1.381
962781AG1-127 GEN
Solar/Wind Harmer
4.576
972235AH1-702 GEN1
Adder
1.21
274872LEEDK;1U
Solar/Wind Harmer
3.941
970819AG2-516 GEN
Solar/Wind Harmer
5.748
957471AF2-041 GEN
Solar/Wind Harmer
14.368
959081AF2-199 GEN
Solar/Wind Harmer
4.789
971067AG2-660 GEN
Solar/Wind Harmer
1.114
939401AE1-172 GEN
Solar/Wind Harmer
6.666
971475AH1-234 GEN
Solar/Wind Harmer
10.713
274761LEE CO EC;2U
Adder
4.387
274766LEE CO EC;7U
Adder
4.336
276861AD2-134 GEN
Solar/Wind Harmer
0.169
274814UNIV PK N;0U
50/50
4.705
274807UNIV PK N;3U
50/50
4.695
274805UNIV PK N;1U
50/50
4.675
274811UNIV PK N;7U
50/50
4.665
960681AF2-359 GEN
Solar/Wind Harmer
13.728
270536AF1-215 GEN2
Solar/Wind Harmer
11.15
971769AH1-391 GEN
Solar/Wind Harmer
19.635
958391AF2-133 GEN
Solar/Wind Harmer
16.966
24690905MDL-1G C
Solar/Wind Harmer
7.591
270180AB1-006 GEN1
Solar/Wind Harmer
6.8
946581AF1-322 GEN
Solar/Wind Harmer
9.673
24691005MDL-2G C
Solar/Wind Harmer
3.497
24697605MDL-3G C
Solar/Wind Harmer
3.486
24697905MDL-4G C
Solar/Wind Harmer
2.17
270181AB1-006 GEN2
Solar/Wind Harmer
0.676
24386205FR-12G C
Solar/Wind Harmer
3.543
24386405FR-21G C
Solar/Wind Harmer
3.556
24386605FR-22G C
Solar/Wind Harmer
3.556
24387005FR-3G C
Solar/Wind Harmer
3.27
963841AG1-237 GEN
Solar/Wind Harmer
8.11
972037AH1-567 GEN1
Adder
0.124
274827FISK ;RP
Adder
4.686
972227AH1-698 GEN1
Adder
1.531
274687WILL CNTY;4U
Adder
16.3
274687WILL CNTY;4U
Adder
16.3
960591AF2-350 GEN
Solar/Wind Harmer
5.798
274675JOLIET 29;7U
Adder
17.605
274675JOLIET 29;7U
Adder
16.976
274728ELWOOD EC;5P
Adder
9.372
274731ELWOOD EC;2P
Adder
9.365
274733ELWOOD EC;3P
Adder
9.365
274735ELWOOD EC;4P
Adder
9.365
971771AH1-392 GEN
Solar/Wind Harmer
4.895
276868AE1-113 GEN
Solar/Wind Harmer
5.378
276882AE2-255 GEN
Solar/Wind Harmer
1.793
970833AG2-524 GEN
Solar/Wind Harmer
4.52
970833AG2-524 GEN
Solar/Wind Harmer
2.102
274746AC1-111 G10
Adder
2.759
274744AC1-111 GEN8
Adder
2.759
971177AH1-047 GEN
Solar/Wind Harmer
2.874
926823AC1-168 GEN
Solar/Wind Harmer
2.105
971411AH1-196 GEN
Solar/Wind Harmer
7.33
274823ROCKFORD ;21
Adder
9.389
971171AH1-044 GEN
Solar/Wind Harmer
9.578
276612AE2-035 GEN
Solar/Wind Harmer
1.223
971675AH1-338 GEN
Solar/Wind Harmer
8.591
274879MINONK ;1U
Solar/Wind Harmer
3.586
972259AH1-714 GEN
Adder
9.925
274847GR RIDGE ;BU
Solar/Wind Harmer
2.609
274683WAUKEGAN ;8U
Adder
10.823
274683WAUKEGAN ;8U
Adder
9.123
274696ROCKY RD ;4P
Adder
5.673
274695ROCKY RD ;2P
Adder
5.542
274693ROCKY RD ;1P
Adder
5.487
274697ROCKY RD ;3P
Adder
1.505
942991AE2-321 GEN
Solar/Wind Harmer
4.909
971333AH1-146 GEN
Solar/Wind Harmer
9.695
971335AH1-147 GEN
Solar/Wind Harmer
9.695
962691AG1-118 GEN
Solar/Wind Harmer
14.468
970921AG2-575 GEN
Solar/Wind Harmer
4.812
970921AG2-575 GEN
Solar/Wind Harmer
1.119
971341AH1-150 GEN
Solar/Wind Harmer
9.578
971343AH1-151 GEN
Solar/Wind Harmer
9.578
274856ECOGROVE ;U1
Solar/Wind Harmer
1.612
276611AD2-172 GEN
Solar/Wind Harmer
1.223
274764LEE CO EC;5U
Adder
4.398
274765LEE CO EC;6U
Adder
4.398
274762LEE CO EC;3U
Adder
4.387
274763LEE CO EC;4U
Adder
4.346
972267AH1-718 GEN
Adder
1.941
964401AG1-302 GEN
Solar/Wind Harmer
18.778
959141AF2-205 GEN
Solar/Wind Harmer
10.406
972231SS25-0005
Solar/Wind Harmer
10.342
972181SS23-001
Solar/Wind Harmer
6.464
24755605MDL-5G
Solar/Wind Harmer
2.28
970781AG2-491 GEN
Solar/Wind Harmer
9.453
274802UNIV PARK;5U
Adder
3.935
274826FISK ;BP
Adder
6.612
274724RIVER EC ;11
Adder
10.454
274800UNIV PARK;3U
Adder
3.427
972038AH1-567 GEN2
Adder
0.214
972228AH1-698 GEN2
Adder
2.175
276772AC2-154 GEN
Solar/Wind Harmer
1.617
276806AD2-047 C O1
Solar/Wind Harmer
6.203
970941AG2-585 GEN
Solar/Wind Harmer
7.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.622
274676JOLIET 29;8U
Adder
16.978
274730ELWOOD EC;6P
Adder
9.372
274734ELWOOD EC;8P
Adder
9.372
274736ELWOOD EC;9P
Adder
9.372
274729ELWOOD EC;1P
Adder
9.365
276893AG1-478 C
Solar/Wind Harmer
0.236
276805AD2-038 GEN
Solar/Wind Harmer
2.853
276889AE2-281 GEN
Solar/Wind Harmer
1.02
276897AD1-100 C
Solar/Wind Harmer
15.124
939351AE1-166 GEN
Solar/Wind Harmer
3.09
970571AG2-364 GEN
Solar/Wind Harmer
10.292
274682WAUKEGAN ;7U
Adder
9.248
972236AH1-702 GEN2
Adder
1.052
274872LEEDK;1U
Solar/Wind Harmer
0.123
959091AF2-200 GEN
Solar/Wind Harmer
9.578
276799AD1-013 GEN
Solar/Wind Harmer
1.055
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274760LEE CO EC;1U
Adder
4.387
274767LEE CO EC;8U
Adder
4.336
24642205MAYFLWER
Adder
0.295
274855GSG-6 ;RU
Solar/Wind Harmer
0.35
276863AD2-134 GEN
Solar/Wind Harmer
0.169
991312J1772
External Queue
15.898972511291504
990762J1386
External Queue
8.398957252502441
991332J1785
External Queue
7.061891555786133
990577J1339
External Queue
12.613447189331055
990582J1340
External Queue
12.613447189331055
990662J1358
External Queue
11.08640193939209
991247J1684 G
External Queue
10.117010116577148
NYPJM->LTFIMP_NY
CLTF
0.796
LGEELTFEXP_LGEE->PJM
CLTF
0.31
WECLTFEXP_WEC->PJM
CLTF
1.87
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.22
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.6
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.463
MECLTFEXP_MEC->PJM
CLTF
6.511
SIGELTFEXP_SIGE->PJM
CLTF
0.074
LAGNLTFEXP_LAGN->PJM
CLTF
3.032
TVALTFEXP_TVA->PJM
CLTF
1.025

Details for 05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#6560_05COOK 345_M_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ELDERBERRY-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6560_05COOK 345_M_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.53 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:1971.3
MW Contribution:5.75
Bus #Bus NameTypeMW Contribution
274751CRETE EC ;1U
50/50
5.652
274754CRETE EC ;4U
50/50
5.652
970023AG2-014 GEN
50/50
2.198
970783AG2-492 GEN
50/50
2.198
274813UNIV PK N;9U
50/50
0.256
274809UNIV PK N;5U
50/50
0.254
274812UNIV PK N;8U
50/50
4.665
966431AG1-512 GEN
50/50
1.633
970373AG2-245 GEN
Solar/Wind Harmer
60.796
270055AF2-134 C O1
Solar/Wind Harmer
7.433
958381AF2-132 GEN
Solar/Wind Harmer
18.778
964861AG1-349 GEN
Solar/Wind Harmer
15.949
971917AH1-482 GEN
Solar/Wind Harmer
18.405
940581AE2-045 GEN
Solar/Wind Harmer
15.652
971605AH1-302 GEN
Solar/Wind Harmer
13.384
24791305MDL-5G
Solar/Wind Harmer
2.28
24385905FR-11G C
Solar/Wind Harmer
6.871
24387305FR-4G C
Solar/Wind Harmer
4.201
963741AG1-226 GEN
Solar/Wind Harmer
29.885
274723RIVER EC ;12
Adder
10.822
274801UNIV PARK;4U
Adder
3.427
276164X3-005 C
Solar/Wind Harmer
0.41
276776AD2-060 GEN
Solar/Wind Harmer
0.245
276691AA1-018 GEN1
Solar/Wind Harmer
0.267
274676JOLIET 29;8U
Adder
17.607
274732ELWOOD EC;7P
Adder
9.372
274674JOLIET 9 ;6U
Adder
8.448
276876AE1-163_GEN2
Solar/Wind Harmer
3.57
276901AD2-066 C O1
Solar/Wind Harmer
1.84
270102X2-052 ST
50/50
6.583
270100X2-052 CT1
50/50
6.066
270101X2-052 CT2
50/50
6.066
274808UNIV PK N;4U
50/50
4.644
965681AG1-436 GEN
Solar/Wind Harmer
45.423
965791AG1-447 GEN
Solar/Wind Harmer
23.239
24441505OLIV SLR
Solar/Wind Harmer
0.263
270526AF1-158 GEN
Solar/Wind Harmer
7.65
945421AF1-207 GEN
Solar/Wind Harmer
14.344
957841AF2-078 GEN
Solar/Wind Harmer
6.173
966841AG1-555 GEN
Solar/Wind Harmer
2.074
274803UNIV PARK;6U
Adder
3.935
970241AG2-163 GEN
Solar/Wind Harmer
16.603
274861TOP CROP ;1U
Solar/Wind Harmer
3.519
274862TOP CROP ;2U
Solar/Wind Harmer
2.938
274888KELLY CRK;1U
Solar/Wind Harmer
3.423
274887GEN-1.85
Solar/Wind Harmer
3.091
276843GEN-1.7
Solar/Wind Harmer
0.333
958011AF2-095 GEN
Solar/Wind Harmer
8.349
958481AF2-142 GEN
Solar/Wind Harmer
8.608
958491AF2-143 GEN
Solar/Wind Harmer
8.342
274674JOLIET 9 ;6U
Adder
8.448
276872AE1-163_GEN1
Solar/Wind Harmer
3.57
274879MINONK ;1U
Solar/Wind Harmer
3.586
972259AH1-714 GEN
Adder
9.925
274847GR RIDGE ;BU
Solar/Wind Harmer
2.609
274683WAUKEGAN ;8U
Adder
10.823
274683WAUKEGAN ;8U
Adder
9.123
274696ROCKY RD ;4P
Adder
5.673
274695ROCKY RD ;2P
Adder
5.542
274693ROCKY RD ;1P
Adder
5.487
274697ROCKY RD ;3P
Adder
1.505
942991AE2-321 GEN
Solar/Wind Harmer
4.909
274752CRETE EC ;2U
50/50
5.652
274753CRETE EC ;3U
50/50
5.652
274806UNIV PK N;2U
50/50
0.261
274815UNIV PK N;XU
50/50
0.256
274816UNIV PK N;YU
50/50
0.256
274810UNIV PK N;6U
50/50
0.255
270535AF1-215 GEN1
Solar/Wind Harmer
11.15
964401AG1-302 GEN
Solar/Wind Harmer
18.778
959141AF2-205 GEN
Solar/Wind Harmer
10.406
972231SS25-0005
Solar/Wind Harmer
10.342
972181SS23-001
Solar/Wind Harmer
6.464
24755605MDL-5G
Solar/Wind Harmer
2.28
970781AG2-491 GEN
Solar/Wind Harmer
9.453
274802UNIV PARK;5U
Adder
3.935
274826FISK ;BP
Adder
6.612
274724RIVER EC ;11
Adder
10.454
274800UNIV PARK;3U
Adder
3.427
972038AH1-567 GEN2
Adder
0.214
972228AH1-698 GEN2
Adder
2.175
276772AC2-154 GEN
Solar/Wind Harmer
1.617
276806AD2-047 C O1
Solar/Wind Harmer
6.203
970941AG2-585 GEN
Solar/Wind Harmer
7.248
276694AA1-018 GEN2
Solar/Wind Harmer
3.622
274676JOLIET 29;8U
Adder
16.978
274730ELWOOD EC;6P
Adder
9.372
274734ELWOOD EC;8P
Adder
9.372
274736ELWOOD EC;9P
Adder
9.372
274729ELWOOD EC;1P
Adder
9.365
276893AG1-478 C
Solar/Wind Harmer
0.236
276805AD2-038 GEN
Solar/Wind Harmer
2.853
276889AE2-281 GEN
Solar/Wind Harmer
1.02
276897AD1-100 C
Solar/Wind Harmer
15.124
939351AE1-166 GEN
Solar/Wind Harmer
3.09
970571AG2-364 GEN
Solar/Wind Harmer
10.292
274682WAUKEGAN ;7U
Adder
9.248
972236AH1-702 GEN2
Adder
1.052
274872LEEDK;1U
Solar/Wind Harmer
0.123
959091AF2-200 GEN
Solar/Wind Harmer
9.578
276799AD1-013 GEN
Solar/Wind Harmer
1.055
946671AF1-331 GEN
Solar/Wind Harmer
0.2
274760LEE CO EC;1U
Adder
4.387
274767LEE CO EC;8U
Adder
4.336
24642205MAYFLWER
Adder
0.295
274855GSG-6 ;RU
Solar/Wind Harmer
0.35
276863AD2-134 GEN
Solar/Wind Harmer
0.169
274814UNIV PK N;0U
50/50
4.705
274807UNIV PK N;3U
50/50
4.695
274805UNIV PK N;1U
50/50
4.675
274811UNIV PK N;7U
50/50
4.665
960681AF2-359 GEN
Solar/Wind Harmer
13.728
270536AF1-215 GEN2
Solar/Wind Harmer
11.15
971769AH1-391 GEN
Solar/Wind Harmer
19.635
958391AF2-133 GEN
Solar/Wind Harmer
16.966
24690905MDL-1G C
Solar/Wind Harmer
7.591
270180AB1-006 GEN1
Solar/Wind Harmer
6.8
946581AF1-322 GEN
Solar/Wind Harmer
9.673
24691005MDL-2G C
Solar/Wind Harmer
3.497
24697605MDL-3G C
Solar/Wind Harmer
3.486
24697905MDL-4G C
Solar/Wind Harmer
2.17
270181AB1-006 GEN2
Solar/Wind Harmer
0.676
24386205FR-12G C
Solar/Wind Harmer
3.543
24386405FR-21G C
Solar/Wind Harmer
3.556
24386605FR-22G C
Solar/Wind Harmer
3.556
24387005FR-3G C
Solar/Wind Harmer
3.27
963841AG1-237 GEN
Solar/Wind Harmer
8.11
972037AH1-567 GEN1
Adder
0.124
274827FISK ;RP
Adder
4.686
972227AH1-698 GEN1
Adder
1.531
274687WILL CNTY;4U
Adder
16.3
274687WILL CNTY;4U
Adder
16.3
960591AF2-350 GEN
Solar/Wind Harmer
5.798
274675JOLIET 29;7U
Adder
17.605
274675JOLIET 29;7U
Adder
16.976
274728ELWOOD EC;5P
Adder
9.372
274731ELWOOD EC;2P
Adder
9.365
274733ELWOOD EC;3P
Adder
9.365
274735ELWOOD EC;4P
Adder
9.365
971771AH1-392 GEN
Solar/Wind Harmer
4.895
276868AE1-113 GEN
Solar/Wind Harmer
5.378
276882AE2-255 GEN
Solar/Wind Harmer
1.793
970833AG2-524 GEN
Solar/Wind Harmer
4.52
970833AG2-524 GEN
Solar/Wind Harmer
2.102
274746AC1-111 G10
Adder
2.759
274744AC1-111 GEN8
Adder
2.759
971177AH1-047 GEN
Solar/Wind Harmer
2.874
926823AC1-168 GEN
Solar/Wind Harmer
2.105
971411AH1-196 GEN
Solar/Wind Harmer
7.33
274823ROCKFORD ;21
Adder
9.389
971171AH1-044 GEN
Solar/Wind Harmer
9.578
276612AE2-035 GEN
Solar/Wind Harmer
1.223
971675AH1-338 GEN
Solar/Wind Harmer
8.591
971333AH1-146 GEN
Solar/Wind Harmer
9.695
971335AH1-147 GEN
Solar/Wind Harmer
9.695
962691AG1-118 GEN
Solar/Wind Harmer
14.468
970921AG2-575 GEN
Solar/Wind Harmer
4.812
970921AG2-575 GEN
Solar/Wind Harmer
1.119
971341AH1-150 GEN
Solar/Wind Harmer
9.578
971343AH1-151 GEN
Solar/Wind Harmer
9.578
274856ECOGROVE ;U1
Solar/Wind Harmer
1.612
276611AD2-172 GEN
Solar/Wind Harmer
1.223
274764LEE CO EC;5U
Adder
4.398
274765LEE CO EC;6U
Adder
4.398
274762LEE CO EC;3U
Adder
4.387
274763LEE CO EC;4U
Adder
4.346
972267AH1-718 GEN
Adder
1.941
941551AE2-152 GEN
Solar/Wind Harmer
2.364
274871GR RIDGE ;2U
Solar/Wind Harmer
3.966
970569AG2-363 GEN
Solar/Wind Harmer
15.439
274682WAUKEGAN ;7U
Adder
9.248
274828WAUKEGAN ;BP
Adder
5.673
971997AH1-543 GEN
Solar/Wind Harmer
7.781
274745AC1-111 GEN9
Adder
2.759
274822ROCKFORD ;11
Adder
9.458
960751AF2-366 GEN
Solar/Wind Harmer
1.381
962781AG1-127 GEN
Solar/Wind Harmer
4.576
972235AH1-702 GEN1
Adder
1.21
274872LEEDK;1U
Solar/Wind Harmer
3.941
970819AG2-516 GEN
Solar/Wind Harmer
5.748
957471AF2-041 GEN
Solar/Wind Harmer
14.368
959081AF2-199 GEN
Solar/Wind Harmer
4.789
971067AG2-660 GEN
Solar/Wind Harmer
1.114
939401AE1-172 GEN
Solar/Wind Harmer
6.666
971475AH1-234 GEN
Solar/Wind Harmer
10.713
274761LEE CO EC;2U
Adder
4.387
274766LEE CO EC;7U
Adder
4.336
276861AD2-134 GEN
Solar/Wind Harmer
0.169
991312J1772
External Queue
15.898972511291504
990762J1386
External Queue
8.398957252502441
991332J1785
External Queue
7.061891555786133
990577J1339
External Queue
12.613447189331055
990582J1340
External Queue
12.613447189331055
990662J1358
External Queue
11.08640193939209
991247J1684 G
External Queue
10.117010116577148
NYPJM->LTFIMP_NY
CLTF
0.796
LGEELTFEXP_LGEE->PJM
CLTF
0.31
WECLTFEXP_WEC->PJM
CLTF
1.87
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.6
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.22
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.091
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.412
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.463
MECLTFEXP_MEC->PJM
CLTF
6.511
SIGELTFEXP_SIGE->PJM
CLTF
0.074
LAGNLTFEXP_LAGN->PJM
CLTF
3.032
TVALTFEXP_TVA->PJM
CLTF
1.025

Details for 05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.88 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4885.66
MW Contribution:11.29
Bus #Bus NameTypeMW Contribution
24344205RKG1
50/50
10.236
24344205RKG1
50/50
10.215
24344305RKG2
50/50
10.196
270393AB1-087 CT1
50/50
3.172
270394AB1-087 ST1
50/50
3.172
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.805
971611AH1-305 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.002
270536AF1-215 GEN2
Solar/Wind Harmer
0.013
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971347AH1-153 GEN
Solar/Wind Harmer
14.79
274775LINCOLN ;6U
Adder
11.903
274776LINCOLN ;7U
Adder
11.903
274777LINCOLN ;8U
Adder
11.903
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.288
941731AE2-173 GEN
Solar/Wind Harmer
8.165
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
9.776
972227AH1-698 GEN1
Adder
3.652
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
7.072
274807UNIV PK N;3U
Adder
7.056
274805UNIV PK N;1U
Adder
7.026
274811UNIV PK N;7U
Adder
7.01
960591AF2-350 GEN
Solar/Wind Harmer
9.764
276849AB2-070 GEN2
Solar/Wind Harmer
0.356
276848AB2-070 GEN3
Solar/Wind Harmer
0.354
972037AH1-567 GEN1
Adder
0.256
274827FISK ;RP
Adder
10.835
970833AG2-524 GEN
Solar/Wind Harmer
10.702
970833AG2-524 GEN
Solar/Wind Harmer
7.134
274731ELWOOD EC;2P
Adder
22.909
274733ELWOOD EC;3P
Adder
22.909
274735ELWOOD EC;4P
Adder
22.909
274728ELWOOD EC;5P
Adder
22.908
274687WILL CNTY;4U
Adder
38.91
274687WILL CNTY;4U
Adder
38.91
274675JOLIET 29;7U
Adder
42.703
274675JOLIET 29;7U
Adder
41.178
971769AH1-391 GEN
Solar/Wind Harmer
10.786
274746AC1-111 G10
Adder
7.736
274744AC1-111 GEN8
Adder
7.736
944221AF1-090 GEN
Solar/Wind Harmer
5.66
276868AE1-113 GEN
Solar/Wind Harmer
1.928
276882AE2-255 GEN
Solar/Wind Harmer
1.124
926823AC1-168 GEN
Solar/Wind Harmer
1.627
971177AH1-047 GEN
Solar/Wind Harmer
5.86
971675AH1-338 GEN
Solar/Wind Harmer
3.702
957751AF2-069 GEN
Solar/Wind Harmer
0.313
971771AH1-392 GEN
Solar/Wind Harmer
9.483
971411AH1-196 GEN
Solar/Wind Harmer
14.224
971171AH1-044 GEN
Solar/Wind Harmer
18.922
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.796
274823ROCKFORD ;21
Adder
26.341
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
15.111
961011AF2-392 GEN
Solar/Wind Harmer
5.479
971619AH1-309 GEN
Solar/Wind Harmer
4.175
270071AF1-092 GEN
Solar/Wind Harmer
17.687
946321AF1-296 GEN
Solar/Wind Harmer
5.141
270594AE1-207 GEN
Solar/Wind Harmer
10.19
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
17.277
971609AH1-304 GEN
Solar/Wind Harmer
1.338
965101AG1-375 GEN
Solar/Wind Harmer
8.167
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.229
270240V3-007_GEN2
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
10.035
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270543AE2-219 C
Solar/Wind Harmer
0.004
965041AG1-368 GEN
Solar/Wind Harmer
6.799
971029AG2-637 GEN
Solar/Wind Harmer
9.99
971673AH1-337 GEN
Solar/Wind Harmer
4.275
965051AG1-369 GEN
Solar/Wind Harmer
3.198
970455AG2-298 GEN
Solar/Wind Harmer
4.116
970091AG2-072 GEN
50/50
198.882
270407AB1-088 ST1
50/50
3.172
970333AG2-219 GEN
Solar/Wind Harmer
12.809
270445AC2-157 GEN2
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
4.889
942601AE2-276 GEN
50/50
10.552
970239AG2-162 GEN
Solar/Wind Harmer
4.479
270444AC2-157 GEN1
Solar/Wind Harmer
0.006
971587AH1-292 GEN
Solar/Wind Harmer
9.286
970321AG2-212 GEN
Solar/Wind Harmer
4.889
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
1.266
970241AG2-163 GEN
Solar/Wind Harmer
6.413
945391AF1-204 GEN
Solar/Wind Harmer
11.343
965681AG1-436 GEN
Solar/Wind Harmer
12.338
965791AG1-447 GEN
Solar/Wind Harmer
9.048
274770LINCOLN ;1U
Adder
11.903
274771LINCOLN ;2U
Adder
11.903
960611AF2-352 GEN
Solar/Wind Harmer
3.259
274808UNIV PK N;4U
Adder
6.98
274888KELLY CRK;1U
Solar/Wind Harmer
0.573
274887GEN-1.85
Solar/Wind Harmer
0.257
276843GEN-1.7
Solar/Wind Harmer
0.316
958011AF2-095 GEN
Solar/Wind Harmer
14.061
972259AH1-714 GEN
Adder
26.685
274803UNIV PARK;6U
Adder
8.15
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274674JOLIET 9 ;6U
Adder
21.442
24441505OLIV SLR
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.489
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.307
276916AD2-100_GEN
Solar/Wind Harmer
20.263
276911AD2-131_GEN
Solar/Wind Harmer
1.335
971573AH1-285 GEN
Solar/Wind Harmer
1.794
958491AF2-143 GEN
Solar/Wind Harmer
14.439
270526AF1-158 GEN
Solar/Wind Harmer
0.012
274879MINONK ;1U
Solar/Wind Harmer
0.405
274696ROCKY RD ;4P
Adder
15.67
274695ROCKY RD ;2P
Adder
15.309
274693ROCKY RD ;1P
Adder
15.158
274697ROCKY RD ;3P
Adder
4.159
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274683WAUKEGAN ;8U
Adder
28.915
274683WAUKEGAN ;8U
Adder
24.374
962691AG1-118 GEN
Solar/Wind Harmer
28.676
970921AG2-575 GEN
Solar/Wind Harmer
9.546
970921AG2-575 GEN
Solar/Wind Harmer
3.182
942991AE2-321 GEN
Solar/Wind Harmer
10.614
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.373
276646AC1-214 GEN2
Solar/Wind Harmer
0.373
971333AH1-146 GEN
Solar/Wind Harmer
18.962
971335AH1-147 GEN
Solar/Wind Harmer
18.962
971341AH1-150 GEN
Solar/Wind Harmer
18.922
971343AH1-151 GEN
Solar/Wind Harmer
18.922
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.222
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
5.315
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
12.51
274765LEE CO EC;6U
Adder
9.439
276741O09 GEN1
Solar/Wind Harmer
0.333
276708O09 GEN2
Solar/Wind Harmer
0.333
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
18.41
24344305RKG2
50/50
10.006
270406AB1-088 CT1
50/50
3.172
970243AG2-164 GEN
Solar/Wind Harmer
10.48
970519AG2-331 GEN
Solar/Wind Harmer
46.579
970699AG2-449 GEN
Solar/Wind Harmer
4.479
970513AG2-328 GEN
Solar/Wind Harmer
4.889
970517AG2-330 GEN
Solar/Wind Harmer
29.332
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
11.21
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
16.013
270535AF1-215 GEN1
Solar/Wind Harmer
0.013
970349AG2-230 GEN
Solar/Wind Harmer
14.79
274772LINCOLN ;3U
Adder
11.903
942111AE2-223 GEN
Solar/Wind Harmer
3.184
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
11.551
274753CRETE EC ;3U
Adder
11.551
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
29.335
959611AF2-252 GEN
Solar/Wind Harmer
3.259
274724RIVER EC ;11
Adder
24.801
972228AH1-698 GEN2
Adder
5.187
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.513
276806AD2-047 C O1
Solar/Wind Harmer
5.533
970941AG2-585 GEN
Solar/Wind Harmer
12.205
276668AB2-070 GEN1
Solar/Wind Harmer
0.356
970707AG2-453 GEN
Solar/Wind Harmer
31.865
274802UNIV PARK;5U
Adder
8.15
274800UNIV PARK;3U
Adder
8.146
972038AH1-567 GEN2
Adder
0.51
274826FISK ;BP
Adder
15.289
274729ELWOOD EC;1P
Adder
22.909
274730ELWOOD EC;6P
Adder
22.908
274734ELWOOD EC;8P
Adder
22.908
274736ELWOOD EC;9P
Adder
22.908
276893AG1-478 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
0.49
276838X2-022 GEN2
Solar/Wind Harmer
0.547
274676JOLIET 29;8U
Adder
41.178
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
16.19
943591AF1-030 GEN
Solar/Wind Harmer
10.767
942481AE2-261 GEN
Solar/Wind Harmer
28.852
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274682WAUKEGAN ;7U
Adder
24.679
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
19.097
274872LEEDK;1U
Solar/Wind Harmer
0.35
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.013
274855GSG-6 ;RU
Solar/Wind Harmer
0.348
274850MENDOTA H;RU
Solar/Wind Harmer
0.112
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.17
959091AF2-200 GEN
Solar/Wind Harmer
18.922
970289AG2-191 GEN
Solar/Wind Harmer
1.04
970291AG2-192 GEN
Solar/Wind Harmer
0.945
274878BISHOP HL;2U
Solar/Wind Harmer
0.317
972236AH1-702 GEN2
Adder
2.96
24642205MAYFLWER
Adder
0.856
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.512
247643Z2-116 C
Solar/Wind Harmer
0
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
26.02
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
13.725
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
13.986
958381AF2-132 GEN
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
21.781
274773LINCOLN ;4U
Adder
11.903
274774LINCOLN ;5U
Adder
11.903
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
13.718
939401AE1-172 GEN
Solar/Wind Harmer
7.325
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274751CRETE EC ;1U
Adder
11.551
274754CRETE EC ;4U
Adder
11.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
8.079
274723RIVER EC ;12
Adder
25.097
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.01
276776AD2-060 GEN
Solar/Wind Harmer
1.019
274801UNIV PARK;4U
Adder
8.146
963831AG1-236 GEN
Solar/Wind Harmer
3.802
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
22.908
276615X2-022 GEN
Solar/Wind Harmer
0.102
274674JOLIET 9 ;6U
Adder
21.442
274676JOLIET 29;8U
Adder
42.703
276691AA1-018 GEN1
Solar/Wind Harmer
1.17
274745AC1-111 GEN9
Adder
7.736
965911AG1-460 GEN
Solar/Wind Harmer
1.93
276901AD2-066 C O1
Solar/Wind Harmer
0.01
971997AH1-543 GEN
Solar/Wind Harmer
5.053
274682WAUKEGAN ;7U
Adder
24.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274828WAUKEGAN ;BP
Adder
15.157
970569AG2-363 GEN
Solar/Wind Harmer
28.645
962781AG1-127 GEN
Solar/Wind Harmer
9.085
274872LEEDK;1U
Solar/Wind Harmer
0.006
276861AD2-134 GEN
Solar/Wind Harmer
0.17
957471AF2-041 GEN
Solar/Wind Harmer
28.383
959081AF2-199 GEN
Solar/Wind Harmer
9.461
971067AG2-660 GEN
Solar/Wind Harmer
3.154
970291AG2-192 GEN
Solar/Wind Harmer
1.229
274877BISHOP HL;1U
Solar/Wind Harmer
0.317
274822ROCKFORD ;11
Adder
26.534
972235AH1-702 GEN1
Adder
3.404
970819AG2-516 GEN
Solar/Wind Harmer
11.285
971475AH1-234 GEN
Solar/Wind Harmer
4.553
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
9.741
945111AF1-176 GEN
Solar/Wind Harmer
16.452
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.8
270032AE2-172
Solar/Wind Harmer
6.065
276903AD2-071 C
Solar/Wind Harmer
10.136
270063AE2-323 C
Solar/Wind Harmer
0.007
965651AG1-433 GEN
Solar/Wind Harmer
2.403
958861AF2-177 GEN
Solar/Wind Harmer
3.539
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.846
270005AE1-210 C O1
Solar/Wind Harmer
1.734
965031AG1-367 GEN
Solar/Wind Harmer
8.001
970773AG2-487 GEN
Solar/Wind Harmer
1.37
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.665
965011AG1-365 GEN
Solar/Wind Harmer
7.456
247536S-71 GEN
Solar/Wind Harmer
0.284
944231AF1-091 GEN
Solar/Wind Harmer
1.864
971565AH1-281 GEN
Solar/Wind Harmer
1.306
247521TR3_G114
Solar/Wind Harmer
0.234
270246TR4_N_V150
Solar/Wind Harmer
0.041
24695305TIMB G C
Solar/Wind Harmer
0.002
945111AF1-176 GEN
Solar/Wind Harmer
7.473
965931AG1-462 GEN
Solar/Wind Harmer
23.338
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
5.542
970031AG2-029 GEN
Solar/Wind Harmer
5.595
944531AF1-118 GEN
Solar/Wind Harmer
37.201
958821AF2-173 GEN
Solar/Wind Harmer
11.202
270004AE1-209 GEN
Solar/Wind Harmer
1.734
946031AF1-268 GEN
Solar/Wind Harmer
7.423
270356AE2-297 GEN
Solar/Wind Harmer
0.01
270437AC2-090 C
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.219
965021AG1-366 GEN
Solar/Wind Harmer
2.485
971617AH1-308 GEN
Solar/Wind Harmer
6.14
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.942
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
961051AF2-396 GEN
Solar/Wind Harmer
12.273
971613AH1-306 GEN
Solar/Wind Harmer
4.367
944541AF1-119 GEN
Solar/Wind Harmer
0.549
960971AF2-388 GEN
Solar/Wind Harmer
4.806
270599AE1-208 GEN
Solar/Wind Harmer
7.51
270031AE2-169
Solar/Wind Harmer
4.506
960441AF2-335 GEN
Solar/Wind Harmer
8.073
970825AG2-519 GEN
Solar/Wind Harmer
8.886
942221AE2-234 GEN
Solar/Wind Harmer
0.04
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.456
970627AG2-408 GEN
Solar/Wind Harmer
2.237
270383AD1-128 GEN
Solar/Wind Harmer
0.005
964611AG1-324 GEN
Solar/Wind Harmer
0.555
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970883AG2-550 GEN
Solar/Wind Harmer
6.873
970885AG2-551 GEN
Solar/Wind Harmer
2.291
964571AG1-320 GEN
Solar/Wind Harmer
6.134
970235AG2-159 GEN
Solar/Wind Harmer
3.809
970235AG2-159 GEN
Solar/Wind Harmer
2.185
970653AG2-424 GEN
Solar/Wind Harmer
2.907
970653AG2-424 GEN
Solar/Wind Harmer
1.506
944201AF1-088_MTX
50/50
211.042
957141AF2-008_MTX
50/50
105.521
NYPJM->LTFIMP_NY
CLTF
2.584
LGEELTFEXP_LGEE->PJM
CLTF
8.153
WECLTFEXP_WEC->PJM
CLTF
5.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
121.55
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.335
AH1-155LTFEXP_AH1-155->PJM
LTF
0.503
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.289
MECLTFEXP_MEC->PJM
CLTF
20.301
SIGELTFEXP_SIGE->PJM
CLTF
0.641
LAGNLTFEXP_LAGN->PJM
CLTF
11.815
TVALTFEXP_TVA->PJM
CLTF
4.631

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.09 %
Rating:3039.0 MVA
Rating Type:B
MVA to Mitigate:3588.67
MW Contribution:6.57
Bus #Bus NameTypeMW Contribution
24344205RKG1
50/50
11.244
24344205RKG1
50/50
11.22
24344305RKG2
50/50
11.199
270393AB1-087 CT1
50/50
2.508
270394AB1-087 ST1
50/50
2.508
970541AG2-344 GEN
50/50
10.209
970539AG2-343 GEN
50/50
9.364
970543AG2-345 GEN
50/50
4.682
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.647
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.256
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.104
274775LINCOLN ;6U
Adder
7.237
274776LINCOLN ;7U
Adder
7.237
274777LINCOLN ;8U
Adder
7.237
971769AH1-391 GEN
Solar/Wind Harmer
6.648
274814UNIV PK N;0U
Adder
4.294
274807UNIV PK N;3U
Adder
4.285
274805UNIV PK N;1U
Adder
4.266
274811UNIV PK N;7U
Adder
4.257
972227AH1-698 GEN1
Adder
2.206
960591AF2-350 GEN
Solar/Wind Harmer
5.898
972037AH1-567 GEN1
Adder
0.155
274827FISK ;RP
Adder
6.544
274687WILL CNTY;4U
Adder
23.403
274687WILL CNTY;4U
Adder
23.403
274731ELWOOD EC;2P
Adder
13.765
274733ELWOOD EC;3P
Adder
13.765
274735ELWOOD EC;4P
Adder
13.765
274728ELWOOD EC;5P
Adder
13.765
970833AG2-524 GEN
Solar/Wind Harmer
6.424
970833AG2-524 GEN
Solar/Wind Harmer
4.282
274675JOLIET 29;7U
Adder
25.664
274675JOLIET 29;7U
Adder
24.747
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
5.784
274746AC1-111 G10
Adder
4.62
274744AC1-111 GEN8
Adder
4.62
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.036
941731AE2-173 GEN
Solar/Wind Harmer
4.79
971771AH1-392 GEN
Solar/Wind Harmer
5.725
276868AE1-113 GEN
Solar/Wind Harmer
1.14
276882AE2-255 GEN
Solar/Wind Harmer
0.664
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.205
276848AB2-070 GEN3
Solar/Wind Harmer
0.204
926823AC1-168 GEN
Solar/Wind Harmer
0.954
971177AH1-047 GEN
Solar/Wind Harmer
3.447
971675AH1-338 GEN
Solar/Wind Harmer
2.173
971411AH1-196 GEN
Solar/Wind Harmer
8.347
971619AH1-309 GEN
Solar/Wind Harmer
2.5
971171AH1-044 GEN
Solar/Wind Harmer
11.069
274823ROCKFORD ;21
Adder
15.377
957751AF2-069 GEN
Solar/Wind Harmer
0.182
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.765
944221AF1-090 GEN
Solar/Wind Harmer
3.172
961011AF2-392 GEN
Solar/Wind Harmer
3.16
946321AF1-296 GEN
Solar/Wind Harmer
2.912
971549AH1-272 GEN
Solar/Wind Harmer
10.16
270071AF1-092 GEN
Solar/Wind Harmer
8.874
970289AG2-191 GEN
Solar/Wind Harmer
0.714
252524AE2-267 GEN
Solar/Wind Helper
0.465
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339211AE2-254 GEN
Solar/Wind Helper
0.447
270367AC2-061_GEN
Solar/Wind Helper
1.692
270340AC2-060 GEN
Solar/Wind Helper
1.094
241972AD1-140 GEN
Solar/Wind Helper
2.07
970091AG2-072 GEN
50/50
218.455
270407AB1-088 ST1
50/50
2.508
970023AG2-014 GEN
50/50
2.686
970783AG2-492 GEN
50/50
2.686
24344105CKG2
50/50
6.851
970333AG2-219 GEN
Solar/Wind Harmer
14.81
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970245AG2-165 GEN
Solar/Wind Harmer
3.606
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.756
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.732
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
963741AG1-226 GEN
Solar/Wind Harmer
17.046
970373AG2-245 GEN
Solar/Wind Harmer
14.55
274773LINCOLN ;4U
Adder
7.237
274774LINCOLN ;5U
Adder
7.237
274751CRETE EC ;1U
Adder
7.047
274754CRETE EC ;4U
Adder
7.047
274723RIVER EC ;12
Adder
15.25
274812UNIV PK N;8U
Adder
4.257
276164X3-005 C
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.616
274801UNIV PARK;4U
Adder
4.918
939401AE1-172 GEN
Solar/Wind Harmer
4.373
274732ELWOOD EC;7P
Adder
13.765
274674JOLIET 9 ;6U
Adder
12.881
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
25.663
274745AC1-111 GEN9
Adder
4.62
276691AA1-018 GEN1
Solar/Wind Harmer
0.697
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.048
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
2.988
274682WAUKEGAN ;7U
Adder
14.638
274828WAUKEGAN ;BP
Adder
8.984
972175AH1-670 GEN
Solar/Wind Harmer
4.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.364
274872LEEDK;1U
Solar/Wind Harmer
0.003
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.181
970569AG2-363 GEN
Solar/Wind Harmer
16.771
276861AD2-134 GEN
Solar/Wind Harmer
0.1
270505AE1-170 C O1
Solar/Wind Harmer
5.832
276615X2-022 GEN
Solar/Wind Harmer
0.058
957471AF2-041 GEN
Solar/Wind Harmer
16.603
959081AF2-199 GEN
Solar/Wind Harmer
5.534
971067AG2-660 GEN
Solar/Wind Harmer
1.845
274822ROCKFORD ;11
Adder
1.007
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.872
945111AF1-176 GEN
Solar/Wind Harmer
9.771
970819AG2-516 GEN
Solar/Wind Harmer
6.568
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971475AH1-234 GEN
Solar/Wind Harmer
2.645
965911AG1-460 GEN
Solar/Wind Harmer
1.09
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
24344305RKG2
50/50
10.991
270406AB1-088 CT1
50/50
2.508
970243AG2-164 GEN
Solar/Wind Harmer
12.117
970519AG2-331 GEN
Solar/Wind Harmer
53.854
970699AG2-449 GEN
Solar/Wind Harmer
5.178
970513AG2-328 GEN
Solar/Wind Harmer
3.606
970517AG2-330 GEN
Solar/Wind Harmer
21.635
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.058
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
970193AG2-126 GEN
Solar/Wind Harmer
9.211
970349AG2-230 GEN
Solar/Wind Harmer
9.104
274772LINCOLN ;3U
Adder
7.237
274752CRETE EC ;2U
Adder
7.047
274753CRETE EC ;3U
Adder
7.047
274724RIVER EC ;11
Adder
15.065
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.132
276806AD2-047 C O1
Solar/Wind Harmer
3.342
970941AG2-585 GEN
Solar/Wind Harmer
7.373
274802UNIV PARK;5U
Adder
4.928
274800UNIV PARK;3U
Adder
4.918
972038AH1-567 GEN2
Adder
0.308
274826FISK ;BP
Adder
9.234
970707AG2-453 GEN
Solar/Wind Harmer
19.213
274729ELWOOD EC;1P
Adder
13.765
274730ELWOOD EC;6P
Adder
13.765
274734ELWOOD EC;8P
Adder
13.765
274736ELWOOD EC;9P
Adder
13.765
276893AG1-478 C
Solar/Wind Harmer
0.231
274676JOLIET 29;8U
Adder
24.747
943121AE2-341 GEN
Solar/Wind Harmer
9.668
943591AF1-030 GEN
Solar/Wind Harmer
6.429
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.868
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
17.118
959611AF2-252 GEN
Solar/Wind Harmer
1.902
274682WAUKEGAN ;7U
Adder
14.638
24642205MAYFLWER
Adder
0.516
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.206
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.205
970571AG2-364 GEN
Solar/Wind Harmer
11.181
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.595
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276621W2-048 GEN
Solar/Wind Harmer
0.28
276838X2-022 GEN2
Solar/Wind Harmer
0.313
959091AF2-200 GEN
Solar/Wind Harmer
11.069
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.439
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
942481AE2-261 GEN
Solar/Wind Harmer
16.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.872
965931AG1-462 GEN
Solar/Wind Harmer
13.177
247642Z2-115 C
Solar/Wind Harmer
0.002
970031AG2-029 GEN
Solar/Wind Harmer
2.905
270043AE2-236 GEN
Solar/Wind Harmer
2.56
970289AG2-191 GEN
Solar/Wind Harmer
0.413
970291AG2-192 GEN
Solar/Wind Harmer
0.376
959331AF2-224 GEN
Solar/Wind Harmer
2.131
965021AG1-366 GEN
Solar/Wind Harmer
1.015
252510AF1-249 C
Solar/Wind Helper
0.376
253406AD2-031_GEN
Solar/Wind Helper
0.712
253415AE1-040 GEN
Solar/Wind Helper
0.483
339250AF1-203 GEN
Solar/Wind Helper
0.118
253338AC1-165 GEN
Solar/Wind Helper
0.467
253333AC1-068 GEN
Solar/Wind Helper
0.484
270063AE2-323 C
Solar/Wind Harmer
0.004
970291AG2-192 GEN
Solar/Wind Harmer
0.488
965011AG1-365 GEN
Solar/Wind Harmer
3.044
944231AF1-091 GEN
Solar/Wind Harmer
0.807
252507AC2-088 GEN
Solar/Wind Helper
1.471
339216AC1-074 GEN
Solar/Wind Helper
1.461
943111AE2-339 GEN
Solar/Wind Helper
0.643
339241AF1-083 GEN
Solar/Wind Helper
0.405
253343AC1-166 GEN
Solar/Wind Helper
0.467
253325AC1-069 GEN
Solar/Wind Helper
0.484
942601AE2-276 GEN
50/50
8.344
270102X2-052 ST
50/50
1.424
270100X2-052 CT1
50/50
1.312
270101X2-052 CT2
50/50
1.312
970239AG2-162 GEN
Solar/Wind Harmer
5.178
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.343
970321AG2-212 GEN
Solar/Wind Harmer
3.606
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.888
970241AG2-163 GEN
Solar/Wind Harmer
4.202
965681AG1-436 GEN
Solar/Wind Harmer
7.741
965791AG1-447 GEN
Solar/Wind Harmer
5.677
945391AF1-204 GEN
Solar/Wind Harmer
6.524
274770LINCOLN ;1U
Adder
7.237
274771LINCOLN ;2U
Adder
7.237
24441505OLIV SLR
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.239
270526AF1-158 GEN
Solar/Wind Harmer
0.007
274888KELLY CRK;1U
Solar/Wind Harmer
0.346
274887GEN-1.85
Solar/Wind Harmer
0.155
276843GEN-1.7
Solar/Wind Harmer
0.191
958011AF2-095 GEN
Solar/Wind Harmer
8.493
274803UNIV PARK;6U
Adder
4.928
972259AH1-714 GEN
Adder
16.092
274674JOLIET 9 ;6U
Adder
12.881
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958481AF2-142 GEN
Solar/Wind Harmer
8.633
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.778
971573AH1-285 GEN
Solar/Wind Harmer
1.068
958491AF2-143 GEN
Solar/Wind Harmer
8.559
960611AF2-352 GEN
Solar/Wind Harmer
1.902
274695ROCKY RD ;2P
Adder
9.087
274693ROCKY RD ;1P
Adder
8.997
274697ROCKY RD ;3P
Adder
2.468
274696ROCKY RD ;4P
Adder
9.301
274879MINONK ;1U
Solar/Wind Harmer
0.24
274683WAUKEGAN ;8U
Adder
17.139
274683WAUKEGAN ;8U
Adder
14.447
962691AG1-118 GEN
Solar/Wind Harmer
16.954
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
970921AG2-575 GEN
Solar/Wind Harmer
5.636
970921AG2-575 GEN
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.244
971333AH1-146 GEN
Solar/Wind Harmer
11.124
971335AH1-147 GEN
Solar/Wind Harmer
11.124
957891AF2-083 GEN
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.069
971343AH1-151 GEN
Solar/Wind Harmer
11.069
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.216
276646AC1-214 GEN2
Solar/Wind Harmer
0.216
961051AF2-396 GEN
Solar/Wind Harmer
10.985
961051AF2-396 GEN
Solar/Wind Harmer
7.324
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.129
276611AD2-172 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
11.423
276911AD2-131_GEN
Solar/Wind Harmer
0.752
938861AE1-114 GEN
Solar/Wind Harmer
3.082
276603SUBLETTE C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.192
276708O09 GEN2
Solar/Wind Harmer
0.192
970611AG2-400 GEN
Solar/Wind Harmer
3.044
970627AG2-408 GEN
Solar/Wind Harmer
0.913
252509AD1-136 GEN
Solar/Wind Helper
0.21
339221AD2-048_GEN
Solar/Wind Helper
1.206
25183208HLCRTG
Solar/Wind Helper
2.027
270186AC1-089 GEN
Solar/Wind Helper
0.821
253394AE2-221_GEN
Solar/Wind Helper
1.236
253398AE2-221_GEN2
Solar/Wind Helper
1.236
962581AG1-107 GEN
Solar/Wind Helper
0.907
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.406
339231AF1-038_GEN
Solar/Wind Helper
0.396
339255AE2-071 GEN
Solar/Wind Helper
0.206
270518AE2-148 GEN
Solar/Wind Helper
5.626
944201AF1-088_MTX
50/50
166.885
957141AF2-008_MTX
50/50
83.443
991112J1481
External Queue
17.5482177734375
991312J1772
External Queue
12.355378150939941
955142J992
External Queue
11.408185005187988
990742J1381
External Queue
17.5482177734375
950011AG9-010
External Queue
6.204055309295654
991082J1475 G
External Queue
6.161812782287598
NYPJM->LTFIMP_NY
CLTF
1.043
WECLTFEXP_WEC->PJM
CLTF
2.99
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.2
AH1-155LTFEXP_AH1-155->PJM
LTF
0.301
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.176
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.126
MECLTFEXP_MEC->PJM
CLTF
10.584
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.981
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.246
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:127.46 %
Rating:2826.0 MVA
Rating Type:B
MVA to Mitigate:3601.92
MW Contribution:6.57
Bus #Bus NameTypeMW Contribution
24344205RKG1
50/50
11.244
24344205RKG1
50/50
11.22
24344305RKG2
50/50
11.199
270393AB1-087 CT1
50/50
2.508
270394AB1-087 ST1
50/50
2.508
970541AG2-344 GEN
50/50
10.209
970539AG2-343 GEN
50/50
9.364
970543AG2-345 GEN
50/50
4.682
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.647
958391AF2-133 GEN
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.256
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.104
274775LINCOLN ;6U
Adder
7.237
274776LINCOLN ;7U
Adder
7.237
274777LINCOLN ;8U
Adder
7.237
971769AH1-391 GEN
Solar/Wind Harmer
6.648
274814UNIV PK N;0U
Adder
4.294
274807UNIV PK N;3U
Adder
4.285
274805UNIV PK N;1U
Adder
4.266
274811UNIV PK N;7U
Adder
4.257
972227AH1-698 GEN1
Adder
2.206
960591AF2-350 GEN
Solar/Wind Harmer
5.898
972037AH1-567 GEN1
Adder
0.155
274827FISK ;RP
Adder
6.544
274687WILL CNTY;4U
Adder
23.403
274687WILL CNTY;4U
Adder
23.403
274731ELWOOD EC;2P
Adder
13.765
274733ELWOOD EC;3P
Adder
13.765
274735ELWOOD EC;4P
Adder
13.765
274728ELWOOD EC;5P
Adder
13.765
970833AG2-524 GEN
Solar/Wind Harmer
6.424
970833AG2-524 GEN
Solar/Wind Harmer
4.282
274675JOLIET 29;7U
Adder
25.664
274675JOLIET 29;7U
Adder
24.747
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
5.784
274746AC1-111 G10
Adder
4.62
274744AC1-111 GEN8
Adder
4.62
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.036
941731AE2-173 GEN
Solar/Wind Harmer
4.79
971771AH1-392 GEN
Solar/Wind Harmer
5.725
276868AE1-113 GEN
Solar/Wind Harmer
1.14
276882AE2-255 GEN
Solar/Wind Harmer
0.664
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.205
276848AB2-070 GEN3
Solar/Wind Harmer
0.204
926823AC1-168 GEN
Solar/Wind Harmer
0.954
971177AH1-047 GEN
Solar/Wind Harmer
3.447
971675AH1-338 GEN
Solar/Wind Harmer
2.173
971411AH1-196 GEN
Solar/Wind Harmer
8.347
971619AH1-309 GEN
Solar/Wind Harmer
2.5
971171AH1-044 GEN
Solar/Wind Harmer
11.069
274823ROCKFORD ;21
Adder
15.377
957751AF2-069 GEN
Solar/Wind Harmer
0.182
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.765
944221AF1-090 GEN
Solar/Wind Harmer
3.172
961011AF2-392 GEN
Solar/Wind Harmer
3.16
946321AF1-296 GEN
Solar/Wind Harmer
2.912
971549AH1-272 GEN
Solar/Wind Harmer
10.16
270071AF1-092 GEN
Solar/Wind Harmer
8.874
970289AG2-191 GEN
Solar/Wind Harmer
0.714
252524AE2-267 GEN
Solar/Wind Helper
0.465
339243AC2-075 GEN1
Solar/Wind Helper
0.336
339211AE2-254 GEN
Solar/Wind Helper
0.447
270367AC2-061_GEN
Solar/Wind Helper
1.692
270340AC2-060 GEN
Solar/Wind Helper
1.094
241972AD1-140 GEN
Solar/Wind Helper
2.07
942601AE2-276 GEN
50/50
8.344
270102X2-052 ST
50/50
1.424
270100X2-052 CT1
50/50
1.312
270101X2-052 CT2
50/50
1.312
970091AG2-072 GEN
50/50
218.455
270407AB1-088 ST1
50/50
2.508
970023AG2-014 GEN
50/50
2.686
970783AG2-492 GEN
50/50
2.686
24344105CKG2
50/50
6.851
970333AG2-219 GEN
Solar/Wind Harmer
14.81
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970245AG2-165 GEN
Solar/Wind Harmer
3.606
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.756
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.732
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
963741AG1-226 GEN
Solar/Wind Harmer
17.046
970373AG2-245 GEN
Solar/Wind Harmer
14.55
274773LINCOLN ;4U
Adder
7.237
274774LINCOLN ;5U
Adder
7.237
274751CRETE EC ;1U
Adder
7.047
274754CRETE EC ;4U
Adder
7.047
274723RIVER EC ;12
Adder
15.25
274812UNIV PK N;8U
Adder
4.257
276164X3-005 C
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.616
274801UNIV PARK;4U
Adder
4.918
939401AE1-172 GEN
Solar/Wind Harmer
4.373
274732ELWOOD EC;7P
Adder
13.765
274674JOLIET 9 ;6U
Adder
12.881
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
25.663
274745AC1-111 GEN9
Adder
4.62
276691AA1-018 GEN1
Solar/Wind Harmer
0.697
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
8.048
276901AD2-066 C O1
Solar/Wind Harmer
0.006
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
2.988
274682WAUKEGAN ;7U
Adder
14.638
274828WAUKEGAN ;BP
Adder
8.984
972175AH1-670 GEN
Solar/Wind Harmer
4.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
5.364
274872LEEDK;1U
Solar/Wind Harmer
0.003
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.181
970569AG2-363 GEN
Solar/Wind Harmer
16.771
276861AD2-134 GEN
Solar/Wind Harmer
0.1
270505AE1-170 C O1
Solar/Wind Harmer
5.832
276615X2-022 GEN
Solar/Wind Harmer
0.058
957471AF2-041 GEN
Solar/Wind Harmer
16.603
959081AF2-199 GEN
Solar/Wind Harmer
5.534
971067AG2-660 GEN
Solar/Wind Harmer
1.845
274822ROCKFORD ;11
Adder
1.007
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.872
945111AF1-176 GEN
Solar/Wind Harmer
9.771
970819AG2-516 GEN
Solar/Wind Harmer
6.568
274877BISHOP HL;1U
Solar/Wind Harmer
0.183
971475AH1-234 GEN
Solar/Wind Harmer
2.645
965911AG1-460 GEN
Solar/Wind Harmer
1.09
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.004
970291AG2-192 GEN
Solar/Wind Harmer
0.488
965011AG1-365 GEN
Solar/Wind Harmer
3.044
944231AF1-091 GEN
Solar/Wind Harmer
0.807
252507AC2-088 GEN
Solar/Wind Helper
1.471
339216AC1-074 GEN
Solar/Wind Helper
1.461
943111AE2-339 GEN
Solar/Wind Helper
0.643
339241AF1-083 GEN
Solar/Wind Helper
0.405
253343AC1-166 GEN
Solar/Wind Helper
0.467
253325AC1-069 GEN
Solar/Wind Helper
0.484
24344305RKG2
50/50
10.991
270406AB1-088 CT1
50/50
2.508
970243AG2-164 GEN
Solar/Wind Harmer
12.117
970519AG2-331 GEN
Solar/Wind Harmer
53.854
970699AG2-449 GEN
Solar/Wind Harmer
5.178
970513AG2-328 GEN
Solar/Wind Harmer
3.606
970517AG2-330 GEN
Solar/Wind Harmer
21.635
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.058
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
970193AG2-126 GEN
Solar/Wind Harmer
9.211
970349AG2-230 GEN
Solar/Wind Harmer
9.104
274772LINCOLN ;3U
Adder
7.237
274752CRETE EC ;2U
Adder
7.047
274753CRETE EC ;3U
Adder
7.047
274724RIVER EC ;11
Adder
15.065
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
972228AH1-698 GEN2
Adder
3.132
276806AD2-047 C O1
Solar/Wind Harmer
3.342
970941AG2-585 GEN
Solar/Wind Harmer
7.373
274802UNIV PARK;5U
Adder
4.928
274800UNIV PARK;3U
Adder
4.918
972038AH1-567 GEN2
Adder
0.308
274826FISK ;BP
Adder
9.234
970707AG2-453 GEN
Solar/Wind Harmer
19.213
274729ELWOOD EC;1P
Adder
13.765
274730ELWOOD EC;6P
Adder
13.765
274734ELWOOD EC;8P
Adder
13.765
274736ELWOOD EC;9P
Adder
13.765
276893AG1-478 C
Solar/Wind Harmer
0.231
274676JOLIET 29;8U
Adder
24.747
943121AE2-341 GEN
Solar/Wind Harmer
9.668
943591AF1-030 GEN
Solar/Wind Harmer
6.429
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.868
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
17.118
959611AF2-252 GEN
Solar/Wind Harmer
1.902
274682WAUKEGAN ;7U
Adder
14.638
24642205MAYFLWER
Adder
0.516
276889AE2-281 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.206
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.595
276668AB2-070 GEN1
Solar/Wind Harmer
0.205
970571AG2-364 GEN
Solar/Wind Harmer
11.181
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.595
274855GSG-6 ;RU
Solar/Wind Harmer
0.204
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276621W2-048 GEN
Solar/Wind Harmer
0.28
276838X2-022 GEN2
Solar/Wind Harmer
0.313
959091AF2-200 GEN
Solar/Wind Harmer
11.069
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.439
274878BISHOP HL;2U
Solar/Wind Harmer
0.183
942481AE2-261 GEN
Solar/Wind Harmer
16.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.872
965931AG1-462 GEN
Solar/Wind Harmer
13.177
247642Z2-115 C
Solar/Wind Harmer
0.002
970031AG2-029 GEN
Solar/Wind Harmer
2.905
270043AE2-236 GEN
Solar/Wind Harmer
2.56
970289AG2-191 GEN
Solar/Wind Harmer
0.413
970291AG2-192 GEN
Solar/Wind Harmer
0.376
959331AF2-224 GEN
Solar/Wind Harmer
2.131
965021AG1-366 GEN
Solar/Wind Harmer
1.015
252510AF1-249 C
Solar/Wind Helper
0.376
253406AD2-031_GEN
Solar/Wind Helper
0.712
253415AE1-040 GEN
Solar/Wind Helper
0.483
339250AF1-203 GEN
Solar/Wind Helper
0.118
253338AC1-165 GEN
Solar/Wind Helper
0.467
253333AC1-068 GEN
Solar/Wind Helper
0.484
970239AG2-162 GEN
Solar/Wind Harmer
5.178
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.343
970321AG2-212 GEN
Solar/Wind Harmer
3.606
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.888
970241AG2-163 GEN
Solar/Wind Harmer
4.202
965681AG1-436 GEN
Solar/Wind Harmer
7.741
965791AG1-447 GEN
Solar/Wind Harmer
5.677
945391AF1-204 GEN
Solar/Wind Harmer
6.524
274770LINCOLN ;1U
Adder
7.237
274771LINCOLN ;2U
Adder
7.237
24441505OLIV SLR
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
4.239
270526AF1-158 GEN
Solar/Wind Harmer
0.007
274888KELLY CRK;1U
Solar/Wind Harmer
0.346
274887GEN-1.85
Solar/Wind Harmer
0.155
276843GEN-1.7
Solar/Wind Harmer
0.191
958011AF2-095 GEN
Solar/Wind Harmer
8.493
274803UNIV PARK;6U
Adder
4.928
972259AH1-714 GEN
Adder
16.092
274674JOLIET 9 ;6U
Adder
12.881
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958481AF2-142 GEN
Solar/Wind Harmer
8.633
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.778
971573AH1-285 GEN
Solar/Wind Harmer
1.068
958491AF2-143 GEN
Solar/Wind Harmer
8.559
960611AF2-352 GEN
Solar/Wind Harmer
1.902
274695ROCKY RD ;2P
Adder
9.087
274693ROCKY RD ;1P
Adder
8.997
274697ROCKY RD ;3P
Adder
2.468
274696ROCKY RD ;4P
Adder
9.301
274879MINONK ;1U
Solar/Wind Harmer
0.24
274683WAUKEGAN ;8U
Adder
17.139
274683WAUKEGAN ;8U
Adder
14.447
962691AG1-118 GEN
Solar/Wind Harmer
16.954
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
970921AG2-575 GEN
Solar/Wind Harmer
5.636
970921AG2-575 GEN
Solar/Wind Harmer
1.879
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942991AE2-321 GEN
Solar/Wind Harmer
6.244
971333AH1-146 GEN
Solar/Wind Harmer
11.124
971335AH1-147 GEN
Solar/Wind Harmer
11.124
957891AF2-083 GEN
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.069
971343AH1-151 GEN
Solar/Wind Harmer
11.069
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.216
276646AC1-214 GEN2
Solar/Wind Harmer
0.216
961051AF2-396 GEN
Solar/Wind Harmer
10.985
961051AF2-396 GEN
Solar/Wind Harmer
7.324
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.129
276611AD2-172 GEN
Solar/Wind Harmer
0.001
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
11.423
276911AD2-131_GEN
Solar/Wind Harmer
0.752
938861AE1-114 GEN
Solar/Wind Harmer
3.082
276603SUBLETTE C
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.192
276708O09 GEN2
Solar/Wind Harmer
0.192
970611AG2-400 GEN
Solar/Wind Harmer
3.044
970627AG2-408 GEN
Solar/Wind Harmer
0.913
252509AD1-136 GEN
Solar/Wind Helper
0.21
339221AD2-048_GEN
Solar/Wind Helper
1.206
25183208HLCRTG
Solar/Wind Helper
2.027
270186AC1-089 GEN
Solar/Wind Helper
0.821
253394AE2-221_GEN
Solar/Wind Helper
1.236
253398AE2-221_GEN2
Solar/Wind Helper
1.236
962581AG1-107 GEN
Solar/Wind Helper
0.907
961491AF2-440 GEN
Solar/Wind Helper
0.037
339236AF1-050_GEN
Solar/Wind Helper
0.406
339231AF1-038_GEN
Solar/Wind Helper
0.396
339255AE2-071 GEN
Solar/Wind Helper
0.206
270518AE2-148 GEN
Solar/Wind Helper
5.626
944201AF1-088_MTX
50/50
166.885
957141AF2-008_MTX
50/50
83.443
991112J1481
External Queue
17.5482177734375
991312J1772
External Queue
12.355378150939941
955142J992
External Queue
11.408185005187988
990742J1381
External Queue
17.5482177734375
950011AG9-010
External Queue
6.204055309295654
991082J1475 G
External Queue
6.161812782287598
NYPJM->LTFIMP_NY
CLTF
1.043
WECLTFEXP_WEC->PJM
CLTF
2.99
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.2
AH1-155LTFEXP_AH1-155->PJM
LTF
0.301
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.176
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.745
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.126
MECLTFEXP_MEC->PJM
CLTF
10.584
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
9.981
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.615
LAGNLTFEXP_LAGN->PJM
CLTF
2.246
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:7.86
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.38
241972AD1-140 GEN
Solar/Wind Harmer
1.032
970689AG2-444 GEN
Solar/Wind Harmer
19.097
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
965101AG1-375 GEN
Solar/Wind Harmer
8.831
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
32.303
961921AG1-034 GEN
Solar/Wind Harmer
9.935
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
270485AE1-090_GEN
Solar/Wind Harmer
0.001
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
972173AH1-669 GEN
Solar/Wind Harmer
4.474
270043AE2-236 GEN
Solar/Wind Harmer
5.712
959331AF2-224 GEN
Solar/Wind Harmer
6.217
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
970191AG2-125 GEN
Solar/Wind Harmer
2.269
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.056
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
8.226
253406AD2-031_GEN
Solar/Wind Harmer
0.643
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
0.009
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970077AG2-063 GEN
Solar/Wind Harmer
5.8
270518AE2-148 GEN
Solar/Wind Harmer
0.847
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
971655AH1-328 GEN
Solar/Wind Harmer
3.428
253378AE2-206_GEN
Solar/Wind Harmer
0.005
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970627AG2-408 GEN
Solar/Wind Harmer
2.664
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
0.594
960971AF2-388 GEN
Solar/Wind Harmer
5.197
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
270599AE1-208 GEN
Solar/Wind Harmer
7.961
270031AE2-169
Solar/Wind Harmer
4.777
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
8.648
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
9.566
960441AF2-335 GEN
Solar/Wind Harmer
8.628
971613AH1-306 GEN
Solar/Wind Harmer
4.135
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
10.743
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
274887GEN-1.85
Solar/Wind Harmer
0.224
276843GEN-1.7
Solar/Wind Harmer
0.275
972259AH1-714 GEN
Adder
23.234
958011AF2-095 GEN
Solar/Wind Harmer
12.235
274803UNIV PARK;6U
Adder
7.1
957891AF2-083 GEN
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
50.586
970149AG2-104 GEN
Solar/Wind Harmer
54.635
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
270462AD2-086
Solar/Wind Harmer
0.021
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.015
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
4.426
965011AG1-365 GEN
Solar/Wind Harmer
8.881
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
970245AG2-165 GEN
Solar/Wind Harmer
3.83
958861AF2-177 GEN
Solar/Wind Harmer
3.827
971995AH1-542 GEN
Solar/Wind Harmer
3.236
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
247536S-71 GEN
Solar/Wind Harmer
0.349
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.654
270063AE2-323 C
Solar/Wind Harmer
0.007
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270263AC1-001 GEN
Solar/Wind Harmer
0.865
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.119
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
276903AD2-071 C
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
970373AG2-245 GEN
Solar/Wind Harmer
17.958
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
276164X3-005 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.064
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
971573AH1-285 GEN
Solar/Wind Harmer
1.571
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
962691AG1-118 GEN
Solar/Wind Harmer
25.162
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
971335AH1-147 GEN
Solar/Wind Harmer
16.689
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
946181AF1-283 GEN
Solar/Wind Harmer
11.138
274772LINCOLN ;3U
Adder
10.354
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276806AD2-047 C O1
Solar/Wind Harmer
4.815
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
2.778
253400AC2-068 GEN
Solar/Wind Harmer
1.117
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
11.841
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
965041AG1-368 GEN
Solar/Wind Harmer
8.719
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
12.951
971673AH1-337 GEN
Solar/Wind Harmer
5.609
970115AG2-085 GEN
Solar/Wind Harmer
3.451
270594AE1-207 GEN
Solar/Wind Harmer
9.648
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270240V3-007_GEN2
Solar/Wind Harmer
0.003
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
247607V1-011 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
276882AE2-255 GEN
Solar/Wind Harmer
0.979
970169AG2-114 GEN
Solar/Wind Harmer
8.358
971177AH1-047 GEN
Solar/Wind Harmer
5.154
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
963841AG1-237 GEN
Solar/Wind Harmer
3.615
971171AH1-044 GEN
Solar/Wind Harmer
16.66
926823AC1-168 GEN
Solar/Wind Harmer
1.415
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
274801UNIV PARK;4U
Adder
7.097
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
274745AC1-111 GEN9
Adder
6.762
24791305MDL-5G
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
939401AE1-172 GEN
Solar/Wind Harmer
6.298
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
962781AG1-127 GEN
Solar/Wind Harmer
7.975
971997AH1-543 GEN
Solar/Wind Harmer
4.396
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.005
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.15
957471AF2-041 GEN
Solar/Wind Harmer
24.989
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
970569AG2-363 GEN
Solar/Wind Harmer
24.96
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
963741AG1-226 GEN
Solar/Wind Harmer
19.652
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
970819AG2-516 GEN
Solar/Wind Harmer
7.858
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
276897AD1-100 C
Solar/Wind Harmer
0.011
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
270356AE2-297 GEN
Solar/Wind Harmer
0.011
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
276805AD2-038 GEN
Solar/Wind Harmer
0.002
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.307
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.12 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2697.98
MW Contribution:5.67
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.301
960861AF2-377 GEN
50/50
2.381
970521AG2-332 GEN
50/50
10.716
24639705ELKHART HY
50/50
0.148
246936BC-WTG1
Solar/Wind Harmer
1.161
270489AE1-102 GEN1
Solar/Wind Harmer
3.72
965421AG1-410 GEN
Solar/Wind Harmer
81.572
965011AG1-365 GEN
Solar/Wind Harmer
13.709
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.26
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.84
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.823
965431AG1-411 GEN
50/50
45.318
24727105RPMNG2
50/50
3.312
970583AG2-370 GEN
50/50
2.791
270491AE1-102 GEN2
Solar/Wind Harmer
3.72
959331AF2-224 GEN
Solar/Wind Harmer
9.596
965021AG1-366 GEN
Solar/Wind Harmer
4.57
970031AG2-029 GEN
Solar/Wind Harmer
5.428
270043AE2-236 GEN
Solar/Wind Harmer
5.157
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.245
971617AH1-308 GEN
Solar/Wind Harmer
5.12
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.761
24727205RPMNG3
50/50
3.285
971599AH1-298 GEN
50/50
10.265
24729505KEY G4
50/50
6.681
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.625
963791AG1-232 GEN
Solar/Wind Harmer
11.533
965041AG1-368 GEN
Solar/Wind Harmer
8.372
270071AF1-092 GEN
Solar/Wind Harmer
14.295
965051AG1-369 GEN
Solar/Wind Harmer
3.565
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.034
971771AH1-392 GEN
Solar/Wind Harmer
5.793
971347AH1-153 GEN
Solar/Wind Harmer
8.606
971619AH1-309 GEN
Solar/Wind Harmer
2.577
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.222
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.881
274814UNIV PK N;0U
Adder
3.743
274807UNIV PK N;3U
Adder
3.735
274805UNIV PK N;1U
Adder
3.719
274811UNIV PK N;7U
Adder
3.711
270536AF1-215 GEN2
Solar/Wind Harmer
0.006
274775LINCOLN ;6U
Adder
6.227
274776LINCOLN ;7U
Adder
6.227
274777LINCOLN ;8U
Adder
6.227
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.682
960591AF2-350 GEN
Solar/Wind Harmer
5.093
972227AH1-698 GEN1
Adder
1.898
274687WILL CNTY;4U
Adder
20.23
274687WILL CNTY;4U
Adder
20.23
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.163
274675JOLIET 29;7U
Adder
21.371
274731ELWOOD EC;2P
Adder
11.842
274733ELWOOD EC;3P
Adder
11.842
274735ELWOOD EC;4P
Adder
11.842
274728ELWOOD EC;5P
Adder
11.843
970833AG2-524 GEN
Solar/Wind Harmer
5.503
970833AG2-524 GEN
Solar/Wind Harmer
3.669
971611AH1-305 GEN
Solar/Wind Harmer
2.963
274746AC1-111 G10
Adder
3.978
274744AC1-111 GEN8
Adder
3.978
970289AG2-191 GEN
Solar/Wind Harmer
0.932
270594AE1-207 GEN
Solar/Wind Harmer
5.432
276868AE1-113 GEN
Solar/Wind Harmer
0.971
276882AE2-255 GEN
Solar/Wind Harmer
0.566
971177AH1-047 GEN
Solar/Wind Harmer
2.975
971411AH1-196 GEN
Solar/Wind Harmer
7.208
971675AH1-338 GEN
Solar/Wind Harmer
1.873
970115AG2-085 GEN
Solar/Wind Harmer
1.915
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.543
274823ROCKFORD ;21
Adder
13.283
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.802
970169AG2-114 GEN
Solar/Wind Harmer
4.71
971681AH1-341 GEN
Solar/Wind Harmer
7.556
971549AH1-272 GEN
Solar/Wind Harmer
9.681
961011AF2-392 GEN
Solar/Wind Harmer
2.722
957751AF2-069 GEN
Solar/Wind Harmer
0.152
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.771
941731AE2-173 GEN
Solar/Wind Harmer
3.786
946321AF1-296 GEN
Solar/Wind Harmer
2.514
963841AG1-237 GEN
Solar/Wind Harmer
1.925
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.154
276848AB2-070 GEN3
Solar/Wind Harmer
0.153
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.247
971029AG2-637 GEN
Solar/Wind Harmer
5.161
971673AH1-337 GEN
Solar/Wind Harmer
2.14
247607V1-011 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Helper
4.139
966831AG1-554 GEN
Solar/Wind Helper
0.884
270284AF1-227 GEN1
Solar/Wind Helper
1.894
270286AF1-227 GEN2
Solar/Wind Helper
0.695
270287AF1-227 GEN3
Solar/Wind Helper
0.695
270499AE1-146 GEN
Solar/Wind Helper
1.973
945641AF1-229 GEN
Solar/Wind Helper
0.949
958861AF2-177 GEN
Solar/Wind Harmer
2.615
945111AF1-176 GEN
Solar/Wind Harmer
10.481
270505AE1-170 C O1
Solar/Wind Harmer
6.013
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.942
970245AG2-165 GEN
Solar/Wind Harmer
2.283
970373AG2-245 GEN
Solar/Wind Harmer
11.033
970349AG2-230 GEN
Solar/Wind Harmer
8.606
24642205MAYFLWER
Adder
0.519
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.283
970517AG2-330 GEN
Solar/Wind Harmer
13.699
274752CRETE EC ;2U
Adder
6.177
274753CRETE EC ;3U
Adder
6.177
274724RIVER EC ;11
Adder
13.226
247604X1-042
Adder
0.309
270535AF1-215 GEN1
Solar/Wind Harmer
0.006
274772LINCOLN ;3U
Adder
6.227
274751CRETE EC ;1U
Adder
6.177
274754CRETE EC ;4U
Adder
6.177
274723RIVER EC ;12
Adder
13.388
274812UNIV PK N;8U
Adder
3.711
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.227
274774LINCOLN ;5U
Adder
6.227
274801UNIV PARK;4U
Adder
4.262
276776AD2-060 GEN
Solar/Wind Harmer
0.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.6
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.162
274674JOLIET 9 ;6U
Adder
11.098
274732ELWOOD EC;7P
Adder
11.843
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.22
274745AC1-111 GEN9
Adder
3.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.598
274682WAUKEGAN ;7U
Adder
12.642
970291AG2-192 GEN
Solar/Wind Harmer
0.638
274828WAUKEGAN ;BP
Adder
7.76
270005AE1-210 C O1
Solar/Wind Harmer
1.056
965031AG1-367 GEN
Solar/Wind Harmer
4.875
962781AG1-127 GEN
Solar/Wind Harmer
4.624
939401AE1-172 GEN
Solar/Wind Harmer
3.633
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.233
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.531
276861AD2-134 GEN
Solar/Wind Harmer
0.086
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.315
959081AF2-199 GEN
Solar/Wind Harmer
4.772
971067AG2-660 GEN
Solar/Wind Harmer
1.591
274822ROCKFORD ;11
Adder
13.38
970825AG2-519 GEN
Solar/Wind Harmer
1.686
972235AH1-702 GEN1
Adder
1.714
970819AG2-516 GEN
Solar/Wind Harmer
5.675
970569AG2-363 GEN
Solar/Wind Harmer
14.175
274802UNIV PARK;5U
Adder
4.274
274826FISK ;BP
Adder
8.017
274800UNIV PARK;3U
Adder
4.262
972038AH1-567 GEN2
Adder
0.267
276806AD2-047 C O1
Solar/Wind Harmer
2.886
970941AG2-585 GEN
Solar/Wind Harmer
6.366
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.696
970707AG2-453 GEN
Solar/Wind Harmer
16.532
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.371
276893AG1-478 C
Solar/Wind Harmer
0.199
274729ELWOOD EC;1P
Adder
11.842
274730ELWOOD EC;6P
Adder
11.843
274734ELWOOD EC;8P
Adder
11.843
274736ELWOOD EC;9P
Adder
11.843
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.328
943591AF1-030 GEN
Solar/Wind Harmer
5.538
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.642
970289AG2-191 GEN
Solar/Wind Harmer
0.539
970291AG2-192 GEN
Solar/Wind Harmer
0.49
958821AF2-173 GEN
Solar/Wind Harmer
6.825
270004AE1-209 GEN
Solar/Wind Harmer
1.056
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.178
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
0.176
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.086
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.78
959091AF2-200 GEN
Solar/Wind Harmer
9.543
972236AH1-702 GEN2
Adder
1.491
970571AG2-364 GEN
Solar/Wind Harmer
9.45
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.232
274767LEE CO EC;8U
Adder
6.158
946031AF1-268 GEN
Solar/Wind Harmer
4.44
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
6.987
276157O29GEN1
Solar/Wind Harmer
0.746
274878BISHOP HL;2U
Solar/Wind Harmer
0.154
942111AE2-223 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
11.384
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.388
959611AF2-252 GEN
Solar/Wind Harmer
1.488
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.154
971993AH1-541 GEN
Solar/Wind Harmer
1.946
276621W2-048 GEN
Solar/Wind Harmer
0.209
276838X2-022 GEN2
Solar/Wind Harmer
0.233
942481AE2-261 GEN
Solar/Wind Harmer
11.923
970193AG2-126 GEN
Solar/Wind Harmer
5.78
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.21
24728505AND G1
Adder
2.013
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.781
970519AG2-331 GEN
Solar/Wind Harmer
7.913
970699AG2-449 GEN
Solar/Wind Harmer
0.761
270485AE1-090_GEN
Solar/Wind Helper
0.325
942871AE2-306 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.947
970615AG2-402 GEN
50/50
4.57
24729405KEY G3
50/50
0.365
24729305KEY G2
50/50
0.359
24729205KEY G1
50/50
0.357
247620Y3-023
50/50
0.459
246938BC-WTG3
Solar/Wind Harmer
1.037
246937BC-WTG2
Solar/Wind Harmer
1.161
970611AG2-400 GEN
Solar/Wind Harmer
13.709
970627AG2-408 GEN
Solar/Wind Harmer
4.113
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.416
960971AF2-388 GEN
Solar/Wind Harmer
3.647
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.449
961051AF2-396 GEN
Solar/Wind Harmer
7.632
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.819
965791AG1-447 GEN
Solar/Wind Harmer
5.001
270599AE1-208 GEN
Solar/Wind Harmer
4.943
270031AE2-169
Solar/Wind Harmer
2.966
970321AG2-212 GEN
Solar/Wind Harmer
2.283
274808UNIV PK N;4U
Adder
3.694
274770LINCOLN ;1U
Adder
6.227
274771LINCOLN ;2U
Adder
6.227
274803UNIV PARK;6U
Adder
4.274
274888KELLY CRK;1U
Solar/Wind Harmer
0.299
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.165
958011AF2-095 GEN
Solar/Wind Harmer
7.334
972259AH1-714 GEN
Adder
13.842
274674JOLIET 9 ;6U
Adder
11.098
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.921
958481AF2-142 GEN
Solar/Wind Harmer
7.4
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.667
274696ROCKY RD ;4P
Adder
8.021
274695ROCKY RD ;2P
Adder
7.836
274693ROCKY RD ;1P
Adder
7.759
274697ROCKY RD ;3P
Adder
2.129
274683WAUKEGAN ;8U
Adder
14.804
274683WAUKEGAN ;8U
Adder
12.479
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.613
958491AF2-143 GEN
Solar/Wind Harmer
7.306
970921AG2-575 GEN
Solar/Wind Harmer
4.859
970921AG2-575 GEN
Solar/Wind Harmer
1.62
971613AH1-306 GEN
Solar/Wind Harmer
2.328
274879MINONK ;1U
Solar/Wind Harmer
0.204
942991AE2-321 GEN
Solar/Wind Harmer
5.39
971333AH1-146 GEN
Solar/Wind Harmer
9.601
971335AH1-147 GEN
Solar/Wind Harmer
9.601
960441AF2-335 GEN
Solar/Wind Harmer
4.786
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.543
971343AH1-151 GEN
Solar/Wind Harmer
9.543
970825AG2-519 GEN
Solar/Wind Harmer
5.263
274856ECOGROVE ;U1
Solar/Wind Harmer
0.111
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.658
274764LEE CO EC;5U
Adder
6.246
274765LEE CO EC;6U
Adder
6.246
274762LEE CO EC;3U
Adder
6.232
274763LEE CO EC;4U
Adder
6.173
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.349
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.761
276741O09 GEN1
Solar/Wind Harmer
0.164
276708O09 GEN2
Solar/Wind Harmer
0.164
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.181
276646AC1-214 GEN2
Solar/Wind Harmer
0.181
966841AG1-555 GEN
Solar/Wind Harmer
0.519
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.158
960611AF2-352 GEN
Solar/Wind Harmer
1.488
970241AG2-163 GEN
Solar/Wind Harmer
2.514
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.299
276911AD2-131_GEN
Solar/Wind Harmer
0.547
970883AG2-550 GEN
Solar/Wind Harmer
3.858
970885AG2-551 GEN
Solar/Wind Harmer
1.286
945391AF1-204 GEN
Solar/Wind Harmer
4.094
970623AG2-406 GEN
Solar/Wind Harmer
0.671
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.387
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.761
270224U2-072_GEN2
Solar/Wind Helper
0.877
270227U2-072_GEN3
Solar/Wind Helper
0.877
270228U2-072_GEN4
Solar/Wind Helper
0.877
270231U2-072_GEN5
Solar/Wind Helper
0.877
270471AD2-092_GEN
Solar/Wind Helper
0.862
253378AE2-206_GEN
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.324
241960AC2-195 GEN
Solar/Wind Helper
0.702
971475AH1-234 GEN
Solar/Wind Harmer
2.289
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.232
274766LEE CO EC;7U
Adder
6.158
276903AD2-071 C
Solar/Wind Harmer
5.188
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.154
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.361
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.579
963741AG1-226 GEN
Solar/Wind Harmer
10.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.15
247536S-71 GEN
Solar/Wind Harmer
0.171
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.633
276615X2-022 GEN
Solar/Wind Harmer
0.043
965911AG1-460 GEN
Solar/Wind Harmer
0.798
24728605AND G2
Adder
2.013
970773AG2-487 GEN
Solar/Wind Harmer
0.599
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.176
270462AD2-086
Solar/Wind Helper
3.736
270223U2-072_GEN1
Solar/Wind Helper
0.877
270578AF1-285 GEN2
Solar/Wind Helper
0.594
270391AF1-285 GEN3
Solar/Wind Helper
0.594
247522W1-056 GEN
Solar/Wind Helper
1.179
960841AF2-375 GEN
Solar/Wind Helper
1.188
270349AD2-093_GEN
Solar/Wind Helper
0.862
944201AF1-088_MTX
Adder
54.26
957141AF2-008_MTX
Adder
17.407
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
NYPJM->LTFIMP_NY
CLTF
1.315
LGEELTFEXP_LGEE->PJM
CLTF
1.728
WECLTFEXP_WEC->PJM
CLTF
2.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.893
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.448
MECLTFEXP_MEC->PJM
CLTF
9.525
SIGELTFEXP_SIGE->PJM
CLTF
0.193
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
TVALTFEXP_TVA->PJM
CLTF
2.191

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.8 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5417.86
MW Contribution:10.11
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.721
24721705FLATG2
50/50
31.554
24344105CKG2
50/50
10.231
962761AG1-125 GEN
Solar/Wind Harmer
74.429
970149AG2-104 GEN
Solar/Wind Harmer
80.386
970155AG2-107 GEN
Solar/Wind Harmer
47.528
970245AG2-165 GEN
Solar/Wind Harmer
4.024
274773LINCOLN ;4U
Adder
10.698
274774LINCOLN ;5U
Adder
10.698
274723RIVER EC ;12
Adder
22.511
24639705ELKHART HY
Adder
0.193
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.335
274754CRETE EC ;4U
Adder
10.335
274812UNIV PK N;8U
Adder
6.269
270063AE2-323 C
Solar/Wind Harmer
0.007
270505AE1-170 C O1
Solar/Wind Harmer
9.167
276776AD2-060 GEN
Solar/Wind Harmer
0.91
274801UNIV PARK;4U
Adder
7.282
970373AG2-245 GEN
Solar/Wind Harmer
18.295
945111AF1-176 GEN
Solar/Wind Harmer
15.535
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
38.179
274674JOLIET 9 ;6U
Adder
19.145
274732ELWOOD EC;7P
Adder
20.43
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.514
270102X2-052 ST
50/50
2.042
270100X2-052 CT1
50/50
1.881
270101X2-052 CT2
50/50
1.881
970321AG2-212 GEN
Solar/Wind Harmer
4.024
965681AG1-436 GEN
Solar/Wind Harmer
11.102
965791AG1-447 GEN
Solar/Wind Harmer
8.141
274770LINCOLN ;1U
Adder
10.698
274771LINCOLN ;2U
Adder
10.698
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
6.922
270055AF2-134 C O1
Solar/Wind Harmer
0.007
24722005FLATG5
50/50
1.721
24721905FLATG4
50/50
31.554
970153AG2-106 GEN
Solar/Wind Harmer
47.528
970513AG2-328 GEN
Solar/Wind Harmer
4.024
970517AG2-330 GEN
Solar/Wind Harmer
24.143
970349AG2-230 GEN
Solar/Wind Harmer
13.852
270043AE2-236 GEN
Solar/Wind Harmer
5.825
274772LINCOLN ;3U
Adder
10.698
944531AF1-118 GEN
Solar/Wind Harmer
39.627
247643Z2-116 C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
22.251
24642205MAYFLWER
Adder
0.798
274752CRETE EC ;2U
Adder
10.335
274753CRETE EC ;3U
Adder
10.335
970707AG2-453 GEN
Solar/Wind Harmer
28.578
274826FISK ;BP
Adder
13.679
274802UNIV PARK;5U
Adder
7.284
276806AD2-047 C O1
Solar/Wind Harmer
4.94
970941AG2-585 GEN
Solar/Wind Harmer
10.896
972228AH1-698 GEN2
Adder
4.628
274800UNIV PARK;3U
Adder
7.282
972038AH1-567 GEN2
Adder
0.456
945111AF1-176 GEN
Solar/Wind Harmer
7.057
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970031AG2-029 GEN
Solar/Wind Harmer
5.65
274676JOLIET 29;8U
Adder
36.815
274729ELWOOD EC;1P
Adder
20.43
274730ELWOOD EC;6P
Adder
20.43
274734ELWOOD EC;8P
Adder
20.43
274736ELWOOD EC;9P
Adder
20.43
276893AG1-478 C
Solar/Wind Harmer
0.344
943121AE2-341 GEN
Solar/Wind Harmer
14.504
943591AF1-030 GEN
Solar/Wind Harmer
9.645
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
24721605FLATG1
50/50
1.721
971599AH1-298 GEN
50/50
12.006
962771AG1-126 GEN
Solar/Wind Harmer
74.429
971347AH1-153 GEN
Solar/Wind Harmer
13.852
270071AF1-092 GEN
Solar/Wind Harmer
17.275
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
274775LINCOLN ;6U
Adder
10.698
274776LINCOLN ;7U
Adder
10.698
274777LINCOLN ;8U
Adder
10.698
971771AH1-392 GEN
Solar/Wind Harmer
8.844
971769AH1-391 GEN
Solar/Wind Harmer
9.861
24729505KEY G4
Adder
8.122
274814UNIV PK N;0U
Adder
6.324
274807UNIV PK N;3U
Adder
6.31
274805UNIV PK N;1U
Adder
6.283
274811UNIV PK N;7U
Adder
6.269
971619AH1-309 GEN
Solar/Wind Harmer
3.929
274827FISK ;RP
Adder
9.695
972037AH1-567 GEN1
Adder
0.229
960591AF2-350 GEN
Solar/Wind Harmer
8.717
972227AH1-698 GEN1
Adder
3.259
274687WILL CNTY;4U
Adder
34.788
274687WILL CNTY;4U
Adder
34.788
274675JOLIET 29;7U
Adder
38.179
274675JOLIET 29;7U
Adder
36.815
274731ELWOOD EC;2P
Adder
20.43
274733ELWOOD EC;3P
Adder
20.43
274735ELWOOD EC;4P
Adder
20.43
274728ELWOOD EC;5P
Adder
20.43
970833AG2-524 GEN
Solar/Wind Harmer
9.537
970833AG2-524 GEN
Solar/Wind Harmer
6.358
274746AC1-111 G10
Adder
6.922
274744AC1-111 GEN8
Adder
6.922
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.708
276882AE2-255 GEN
Solar/Wind Harmer
0.995
971177AH1-047 GEN
Solar/Wind Harmer
5.247
971675AH1-338 GEN
Solar/Wind Harmer
3.312
971411AH1-196 GEN
Solar/Wind Harmer
12.736
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.049
971171AH1-044 GEN
Solar/Wind Harmer
16.925
274823ROCKFORD ;21
Adder
23.589
970169AG2-114 GEN
Solar/Wind Harmer
8.416
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.43
971681AH1-341 GEN
Solar/Wind Harmer
13.508
961011AF2-392 GEN
Solar/Wind Harmer
4.894
965101AG1-375 GEN
Solar/Wind Harmer
8.339
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
957751AF2-069 GEN
Solar/Wind Harmer
0.274
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.681
941731AE2-173 GEN
Solar/Wind Harmer
6.89
946321AF1-296 GEN
Solar/Wind Harmer
4.595
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.958
963841AG1-237 GEN
Solar/Wind Harmer
3.497
965041AG1-368 GEN
Solar/Wind Harmer
8.037
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970289AG2-191 GEN
Solar/Wind Harmer
1.512
971549AH1-272 GEN
Solar/Wind Harmer
16.344
971609AH1-304 GEN
Solar/Wind Harmer
1.291
270594AE1-207 GEN
Solar/Wind Harmer
8.813
965051AG1-369 GEN
Solar/Wind Harmer
3.913
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270024AE2-089 GEN
Solar/Wind Harmer
0.008
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.485
970115AG2-085 GEN
Solar/Wind Harmer
3.056
965011AG1-365 GEN
Solar/Wind Harmer
8.612
276691AA1-018 GEN1
Solar/Wind Harmer
1.04
274682WAUKEGAN ;7U
Adder
22.097
274828WAUKEGAN ;BP
Adder
13.572
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.134
939401AE1-172 GEN
Solar/Wind Harmer
6.393
962781AG1-127 GEN
Solar/Wind Harmer
8.132
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
971997AH1-543 GEN
Solar/Wind Harmer
4.464
276861AD2-134 GEN
Solar/Wind Harmer
0.152
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.6
957471AF2-041 GEN
Solar/Wind Harmer
25.388
959081AF2-199 GEN
Solar/Wind Harmer
8.463
971067AG2-660 GEN
Solar/Wind Harmer
2.821
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
23.761
965651AG1-433 GEN
Solar/Wind Harmer
2.475
972235AH1-702 GEN1
Adder
3.048
970819AG2-516 GEN
Solar/Wind Harmer
10.106
970569AG2-363 GEN
Solar/Wind Harmer
25.226
971475AH1-234 GEN
Solar/Wind Harmer
4.081
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.164
274766LEE CO EC;7U
Adder
11.032
958861AF2-177 GEN
Solar/Wind Harmer
3.614
24791305MDL-5G
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
270349AD2-093_GEN
Solar/Wind Harmer
0.006
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.575
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
945371AF1-202 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
6.679
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.86
970291AG2-192 GEN
Solar/Wind Harmer
1.034
963831AG1-236 GEN
Solar/Wind Harmer
3.102
276615X2-022 GEN
Solar/Wind Harmer
0.083
270032AE2-172
Solar/Wind Harmer
5.246
247521TR3_G114
Solar/Wind Harmer
0.286
270246TR4_N_V150
Solar/Wind Harmer
0.051
965911AG1-460 GEN
Solar/Wind Harmer
1.556
276903AD2-071 C
Solar/Wind Harmer
8.661
270005AE1-210 C O1
Solar/Wind Harmer
1.672
965031AG1-367 GEN
Solar/Wind Harmer
7.718
944231AF1-091 GEN
Solar/Wind Harmer
2.052
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
2.704
970333AG2-219 GEN
Solar/Wind Harmer
1.862
274808UNIV PK N;4U
Adder
6.241
957891AF2-083 GEN
Solar/Wind Harmer
0.001
972259AH1-714 GEN
Adder
23.861
247620Y3-023
Adder
0.576
274803UNIV PARK;6U
Adder
7.284
274888KELLY CRK;1U
Solar/Wind Harmer
0.512
274887GEN-1.85
Solar/Wind Harmer
0.23
276843GEN-1.7
Solar/Wind Harmer
0.282
958011AF2-095 GEN
Solar/Wind Harmer
12.553
274674JOLIET 9 ;6U
Adder
19.145
961051AF2-396 GEN
Solar/Wind Harmer
17.339
961051AF2-396 GEN
Solar/Wind Harmer
11.56
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.607
970611AG2-400 GEN
Solar/Wind Harmer
8.612
970627AG2-408 GEN
Solar/Wind Harmer
2.584
274695ROCKY RD ;2P
Adder
13.703
274693ROCKY RD ;1P
Adder
13.569
274697ROCKY RD ;3P
Adder
3.723
274696ROCKY RD ;4P
Adder
14.027
958481AF2-142 GEN
Solar/Wind Harmer
12.872
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.161
274683WAUKEGAN ;8U
Adder
25.892
274683WAUKEGAN ;8U
Adder
21.826
962691AG1-118 GEN
Solar/Wind Harmer
25.667
970921AG2-575 GEN
Solar/Wind Harmer
8.545
970921AG2-575 GEN
Solar/Wind Harmer
2.848
958491AF2-143 GEN
Solar/Wind Harmer
12.795
274879MINONK ;1U
Solar/Wind Harmer
0.359
942991AE2-321 GEN
Solar/Wind Harmer
9.503
971333AH1-146 GEN
Solar/Wind Harmer
16.975
971335AH1-147 GEN
Solar/Wind Harmer
16.975
971341AH1-150 GEN
Solar/Wind Harmer
16.925
971343AH1-151 GEN
Solar/Wind Harmer
16.925
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.565
960971AF2-388 GEN
Solar/Wind Harmer
4.95
274856ECOGROVE ;U1
Solar/Wind Harmer
0.198
276611AD2-172 GEN
Solar/Wind Harmer
0.002
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.753
274764LEE CO EC;5U
Adder
11.19
274765LEE CO EC;6U
Adder
11.19
274762LEE CO EC;3U
Adder
11.164
274763LEE CO EC;4U
Adder
11.058
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.971
276741O09 GEN1
Solar/Wind Harmer
0.296
276708O09 GEN2
Solar/Wind Harmer
0.296
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
960611AF2-352 GEN
Solar/Wind Harmer
2.732
966841AG1-555 GEN
Solar/Wind Harmer
0.926
942221AE2-234 GEN
Solar/Wind Harmer
0.041
970241AG2-163 GEN
Solar/Wind Harmer
4.649
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.244
270031AE2-169
Solar/Wind Harmer
4.346
971613AH1-306 GEN
Solar/Wind Harmer
3.777
276916AD2-100_GEN
Solar/Wind Harmer
16.273
276911AD2-131_GEN
Solar/Wind Harmer
1.072
960441AF2-335 GEN
Solar/Wind Harmer
7.639
945391AF1-204 GEN
Solar/Wind Harmer
8.098
970825AG2-519 GEN
Solar/Wind Harmer
8.443
970239AG2-162 GEN
Solar/Wind Harmer
0.651
959331AF2-224 GEN
Solar/Wind Harmer
6.029
965021AG1-366 GEN
Solar/Wind Harmer
2.871
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.097
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.313
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.906
274855GSG-6 ;RU
Solar/Wind Harmer
0.311
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.152
959091AF2-200 GEN
Solar/Wind Harmer
16.925
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.65
247604X1-042
Adder
0.502
970571AG2-364 GEN
Solar/Wind Harmer
16.817
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.164
274767LEE CO EC;8U
Adder
11.032
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.324
276157O29GEN1
Solar/Wind Harmer
1.345
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
942111AE2-223 GEN
Solar/Wind Harmer
2.687
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.591
959611AF2-252 GEN
Solar/Wind Harmer
2.732
965931AG1-462 GEN
Solar/Wind Harmer
20.863
247642Z2-115 C
Solar/Wind Harmer
0.003
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.685
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
970289AG2-191 GEN
Solar/Wind Harmer
0.875
970291AG2-192 GEN
Solar/Wind Harmer
0.796
276621W2-048 GEN
Solar/Wind Harmer
0.399
276838X2-022 GEN2
Solar/Wind Harmer
0.445
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.051
942481AE2-261 GEN
Solar/Wind Harmer
23.26
958821AF2-173 GEN
Solar/Wind Harmer
10.805
270004AE1-209 GEN
Solar/Wind Harmer
1.672
971617AH1-308 GEN
Solar/Wind Harmer
6.396
970193AG2-126 GEN
Solar/Wind Harmer
11.433
946031AF1-268 GEN
Solar/Wind Harmer
7.175
970243AG2-164 GEN
Solar/Wind Harmer
1.523
970519AG2-331 GEN
Solar/Wind Harmer
6.77
970699AG2-449 GEN
Solar/Wind Harmer
0.651
944201AF1-088_MTX
Adder
121.789
957141AF2-008_MTX
Adder
33.652
NYPJM->LTFIMP_NY
CLTF
3.894
LGEELTFEXP_LGEE->PJM
CLTF
5.997
WECLTFEXP_WEC->PJM
CLTF
4.617
CPLELTFEXP_CPLE->PJM
CLTF
3.263
CBM West 2LTFEXP_CBM-W2->PJM
CBM
123.519
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.427
CBM West 1LTFEXP_CBM-W1->PJM
CBM
148.673
CBM South 1LTFEXP_CBM-S1->PJM
CBM
30.42
MECLTFEXP_MEC->PJM
CLTF
18.605
SIGELTFEXP_SIGE->PJM
CLTF
0.498
LAGNLTFEXP_LAGN->PJM
CLTF
16.714
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.261
TVALTFEXP_TVA->PJM
CLTF
7.962

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4722.06
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
4.694
971599AH1-298 GEN
50/50
14.063
270144AC1-141 ST1_
50/50
3.051
24653605MOTTVILLE
50/50
0.005
24643105BUCHANAN
50/50
0.018
270036AE2-216 BAT
50/50
8.975
962771AG1-126 GEN
Solar/Wind Harmer
109.549
270284AF1-227 GEN1
Solar/Wind Harmer
0.015
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
15.658
270578AF1-285 GEN2
Solar/Wind Harmer
0.683
270071AF1-092 GEN
Solar/Wind Harmer
19.582
971771AH1-392 GEN
Solar/Wind Harmer
10.018
971619AH1-309 GEN
Solar/Wind Harmer
4.486
971769AH1-391 GEN
Solar/Wind Harmer
11.066
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.377
24729505KEY G4
Adder
9.092
965041AG1-368 GEN
Solar/Wind Harmer
9.739
274775LINCOLN ;6U
Adder
11.607
274776LINCOLN ;7U
Adder
11.607
274777LINCOLN ;8U
Adder
11.607
965051AG1-369 GEN
Solar/Wind Harmer
4.783
274814UNIV PK N;0U
Adder
6.852
274807UNIV PK N;3U
Adder
6.837
274805UNIV PK N;1U
Adder
6.807
274811UNIV PK N;7U
Adder
6.792
972037AH1-567 GEN1
Adder
0.247
274827FISK ;RP
Adder
10.465
960591AF2-350 GEN
Solar/Wind Harmer
9.401
972227AH1-698 GEN1
Adder
3.512
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.189
963791AG1-232 GEN
Solar/Wind Harmer
12.652
24722005FLATG5
50/50
4.694
24721905FLATG4
50/50
86.059
270475AD2-096_GEN
50/50
10.488
270142AC1-141 CT1_
50/50
3.444
24641605TWIN BRNCH
50/50
0.025
24344005CKG1
50/50
9.376
24642205MAYFLWER
50/50
0.961
944961AF1-161 GEN
50/50
4.122
962601AG1-109 GEN
50/50
4.122
970153AG2-106 GEN
Solar/Wind Harmer
69.955
270043AE2-236 GEN
Solar/Wind Harmer
6.761
970349AG2-230 GEN
Solar/Wind Harmer
15.658
959331AF2-224 GEN
Solar/Wind Harmer
7.221
965021AG1-366 GEN
Solar/Wind Harmer
3.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.683
970513AG2-328 GEN
Solar/Wind Harmer
4.403
970517AG2-330 GEN
Solar/Wind Harmer
26.415
970031AG2-029 GEN
Solar/Wind Harmer
6.551
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
44.632
945111AF1-176 GEN
Solar/Wind Harmer
8.066
270485AE1-090_GEN
Solar/Wind Harmer
0.001
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.578
274772LINCOLN ;3U
Adder
11.607
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
274724RIVER EC ;11
Adder
24.177
274752CRETE EC ;2U
Adder
11.24
274753CRETE EC ;3U
Adder
11.24
970707AG2-453 GEN
Solar/Wind Harmer
30.794
274802UNIV PARK;5U
Adder
7.866
274826FISK ;BP
Adder
14.766
276806AD2-047 C O1
Solar/Wind Harmer
5.327
970941AG2-585 GEN
Solar/Wind Harmer
11.751
274800UNIV PARK;3U
Adder
7.856
972038AH1-567 GEN2
Adder
0.492
972228AH1-698 GEN2
Adder
4.987
270491AE1-102 GEN2
Solar/Wind Harmer
1.22
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
39.557
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
274729ELWOOD EC;1P
Adder
21.93
274730ELWOOD EC;6P
Adder
21.93
274734ELWOOD EC;8P
Adder
21.93
274736ELWOOD EC;9P
Adder
21.93
276893AG1-478 C
Solar/Wind Harmer
0.369
943121AE2-341 GEN
Solar/Wind Harmer
15.511
943591AF1-030 GEN
Solar/Wind Harmer
10.315
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
23.511
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.331
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.956
274855GSG-6 ;RU
Solar/Wind Harmer
0.329
274850MENDOTA H;RU
Solar/Wind Harmer
0.106
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.161
959091AF2-200 GEN
Solar/Wind Harmer
17.815
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.783
270258AD1-119 GEN
Solar/Wind Harmer
0.002
970571AG2-364 GEN
Solar/Wind Harmer
17.623
270404AC1-167 GEN
Solar/Wind Harmer
0.004
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.654
274767LEE CO EC;8U
Adder
11.517
276157O29GEN1
Solar/Wind Harmer
1.397
24755605MDL-5G
Solar/Wind Harmer
0.001
970615AG2-402 GEN
50/50
3.439
247620Y3-023
50/50
0.701
270102X2-052 ST
50/50
2.279
270100X2-052 CT1
50/50
2.1
270101X2-052 CT2
50/50
2.1
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.316
970627AG2-408 GEN
Solar/Wind Harmer
3.095
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
4.403
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.012
961051AF2-396 GEN
Solar/Wind Harmer
19.83
961051AF2-396 GEN
Solar/Wind Harmer
13.22
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
12.351
965791AG1-447 GEN
Solar/Wind Harmer
9.057
274770LINCOLN ;1U
Adder
11.607
274771LINCOLN ;2U
Adder
11.607
274808UNIV PK N;4U
Adder
6.763
274803UNIV PARK;6U
Adder
7.866
274888KELLY CRK;1U
Solar/Wind Harmer
0.552
274887GEN-1.85
Solar/Wind Harmer
0.248
276843GEN-1.7
Solar/Wind Harmer
0.304
958011AF2-095 GEN
Solar/Wind Harmer
13.537
972259AH1-714 GEN
Adder
25.697
246938BC-WTG3
Solar/Wind Harmer
0.34
246937BC-WTG2
Solar/Wind Harmer
0.381
274674JOLIET 9 ;6U
Adder
20.555
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
944541AF1-119 GEN
Solar/Wind Harmer
0.622
960971AF2-388 GEN
Solar/Wind Harmer
5.442
971573AH1-285 GEN
Solar/Wind Harmer
1.715
958481AF2-142 GEN
Solar/Wind Harmer
13.715
274696ROCKY RD ;4P
Adder
14.93
274695ROCKY RD ;2P
Adder
14.586
274693ROCKY RD ;1P
Adder
14.442
274697ROCKY RD ;3P
Adder
3.962
274687WILL CNTY;4U
Adder
37.406
274687WILL CNTY;4U
Adder
37.406
274675JOLIET 29;7U
Adder
41.022
274675JOLIET 29;7U
Adder
39.557
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
274731ELWOOD EC;2P
Adder
21.93
274733ELWOOD EC;3P
Adder
21.93
274735ELWOOD EC;4P
Adder
21.93
274728ELWOOD EC;5P
Adder
21.93
970833AG2-524 GEN
Solar/Wind Harmer
10.224
970833AG2-524 GEN
Solar/Wind Harmer
6.816
971549AH1-272 GEN
Solar/Wind Harmer
19.16
274746AC1-111 G10
Adder
7.401
274744AC1-111 GEN8
Adder
7.401
965101AG1-375 GEN
Solar/Wind Harmer
9.112
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.807
24721805FLATG3
50/50
4.694
24721705FLATG2
50/50
86.059
24344105CKG2
50/50
11.607
270143AC1-141 CT2_
50/50
3.444
24639705ELKHART HY
50/50
0.234
970521AG2-332 GEN
50/50
16.668
24307105BERRINSP G
50/50
0.031
962761AG1-125 GEN
Solar/Wind Harmer
109.549
970149AG2-104 GEN
Solar/Wind Harmer
118.317
970155AG2-107 GEN
Solar/Wind Harmer
69.955
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.316
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.403
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.468
945111AF1-176 GEN
Solar/Wind Harmer
17.757
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.164
270462AD2-086
Solar/Wind Harmer
0.02
274773LINCOLN ;4U
Adder
11.607
274774LINCOLN ;5U
Adder
11.607
247521TR3_G114
Solar/Wind Harmer
0.349
270246TR4_N_V150
Solar/Wind Harmer
0.062
274723RIVER EC ;12
Adder
24.46
274751CRETE EC ;1U
Adder
11.24
274754CRETE EC ;4U
Adder
11.24
970373AG2-245 GEN
Solar/Wind Harmer
19.935
276164X3-005 C
Solar/Wind Harmer
0
965421AG1-410 GEN
Solar/Wind Harmer
28.417
274812UNIV PK N;8U
Adder
6.792
24695305TIMB G C
Solar/Wind Harmer
0.002
276776AD2-060 GEN
Solar/Wind Harmer
0.981
274801UNIV PARK;4U
Adder
7.856
246936BC-WTG1
Solar/Wind Harmer
0.381
270489AE1-102 GEN1
Solar/Wind Harmer
1.22
941551AE2-152 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.492
274676JOLIET 29;8U
Adder
41.022
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274674JOLIET 9 ;6U
Adder
20.555
274732ELWOOD EC;7P
Adder
21.93
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.721
274745AC1-111 GEN9
Adder
7.401
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.896
276691AA1-018 GEN1
Solar/Wind Harmer
1.108
274682WAUKEGAN ;7U
Adder
23.511
274828WAUKEGAN ;BP
Adder
14.433
958861AF2-177 GEN
Solar/Wind Harmer
3.948
962781AG1-127 GEN
Solar/Wind Harmer
8.621
939401AE1-172 GEN
Solar/Wind Harmer
6.775
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.718
276861AD2-134 GEN
Solar/Wind Harmer
0.161
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.195
957471AF2-041 GEN
Solar/Wind Harmer
26.723
959081AF2-199 GEN
Solar/Wind Harmer
8.908
971067AG2-660 GEN
Solar/Wind Harmer
2.969
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
24.978
972235AH1-702 GEN1
Adder
3.201
970819AG2-516 GEN
Solar/Wind Harmer
10.6
970569AG2-363 GEN
Solar/Wind Harmer
26.435
971475AH1-234 GEN
Solar/Wind Harmer
4.275
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.654
274766LEE CO EC;7U
Adder
11.517
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.289
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.942
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
970291AG2-192 GEN
Solar/Wind Harmer
1.078
270032AE2-172
Solar/Wind Harmer
5.467
972175AH1-670 GEN
Solar/Wind Harmer
6.757
270005AE1-210 C O1
Solar/Wind Harmer
1.747
965031AG1-367 GEN
Solar/Wind Harmer
8.064
276903AD2-071 C
Solar/Wind Harmer
8.911
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
18.836
970825AG2-519 GEN
Solar/Wind Harmer
2.823
963831AG1-236 GEN
Solar/Wind Harmer
3.095
970781AG2-491 GEN
Solar/Wind Harmer
8.621
274878BISHOP HL;2U
Solar/Wind Harmer
0.289
942111AE2-223 GEN
Solar/Wind Harmer
2.772
971617AH1-308 GEN
Solar/Wind Harmer
7.081
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.189
959611AF2-252 GEN
Solar/Wind Harmer
2.799
965931AG1-462 GEN
Solar/Wind Harmer
21.385
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.912
970291AG2-192 GEN
Solar/Wind Harmer
0.829
958821AF2-173 GEN
Solar/Wind Harmer
11.29
270004AE1-209 GEN
Solar/Wind Harmer
1.747
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.686
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.901
946031AF1-268 GEN
Solar/Wind Harmer
7.527
276621W2-048 GEN
Solar/Wind Harmer
0.396
276838X2-022 GEN2
Solar/Wind Harmer
0.442
942481AE2-261 GEN
Solar/Wind Harmer
22.745
24728705AND G3
Adder
7.997
24728505AND G1
Adder
3.824
276615X2-022 GEN
Solar/Wind Harmer
0.082
965911AG1-460 GEN
Solar/Wind Harmer
1.521
247536S-71 GEN
Solar/Wind Harmer
0.305
24728605AND G2
Adder
3.824
276882AE2-255 GEN
Solar/Wind Harmer
1.053
971177AH1-047 GEN
Solar/Wind Harmer
5.547
247607V1-011 GEN
Solar/Wind Harmer
0.001
971411AH1-196 GEN
Solar/Wind Harmer
13.442
971675AH1-338 GEN
Solar/Wind Harmer
3.495
971611AH1-305 GEN
Solar/Wind Harmer
5.332
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
17.815
274823ROCKFORD ;21
Adder
24.797
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.498
970169AG2-114 GEN
Solar/Wind Harmer
8.81
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
14.125
961011AF2-392 GEN
Solar/Wind Harmer
5.094
957751AF2-069 GEN
Solar/Wind Harmer
0.285
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.957
941731AE2-173 GEN
Solar/Wind Harmer
7.108
270024AE2-089 GEN
Solar/Wind Harmer
0.009
946321AF1-296 GEN
Solar/Wind Harmer
4.721
971609AH1-304 GEN
Solar/Wind Harmer
1.376
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
970289AG2-191 GEN
Solar/Wind Harmer
1.575
270594AE1-207 GEN
Solar/Wind Harmer
9.184
963841AG1-237 GEN
Solar/Wind Harmer
3.53
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.191
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.29
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.237
274683WAUKEGAN ;8U
Adder
27.535
274683WAUKEGAN ;8U
Adder
23.211
962691AG1-118 GEN
Solar/Wind Harmer
27.238
942221AE2-234 GEN
Solar/Wind Harmer
0.045
970921AG2-575 GEN
Solar/Wind Harmer
9.059
970921AG2-575 GEN
Solar/Wind Harmer
3.02
958491AF2-143 GEN
Solar/Wind Harmer
13.566
274879MINONK ;1U
Solar/Wind Harmer
0.38
942991AE2-321 GEN
Solar/Wind Harmer
10.048
270007AE1-245 C
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
17.91
971335AH1-147 GEN
Solar/Wind Harmer
17.91
971341AH1-150 GEN
Solar/Wind Harmer
17.815
971343AH1-151 GEN
Solar/Wind Harmer
17.815
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.621
274856ECOGROVE ;U1
Solar/Wind Harmer
0.208
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.97
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
274764LEE CO EC;5U
Adder
11.682
274765LEE CO EC;6U
Adder
11.682
274762LEE CO EC;3U
Adder
11.654
274763LEE CO EC;4U
Adder
11.544
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.169
276741O09 GEN1
Solar/Wind Harmer
0.308
276708O09 GEN2
Solar/Wind Harmer
0.308
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.339
276646AC1-214 GEN2
Solar/Wind Harmer
0.339
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
7.723
270031AE2-169
Solar/Wind Harmer
4.634
960611AF2-352 GEN
Solar/Wind Harmer
2.799
966841AG1-555 GEN
Solar/Wind Harmer
0.944
971613AH1-306 GEN
Solar/Wind Harmer
3.936
960441AF2-335 GEN
Solar/Wind Harmer
7.977
970241AG2-163 GEN
Solar/Wind Harmer
4.643
970825AG2-519 GEN
Solar/Wind Harmer
8.815
970621AG2-405 GEN
Solar/Wind Harmer
1.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.595
247621Y3-024
Adder
0.268
276916AD2-100_GEN
Solar/Wind Harmer
12.804
276911AD2-131_GEN
Solar/Wind Harmer
0.843
944201AF1-088_MTX
Adder
80.786
NYPJM->LTFIMP_NY
CLTF
3.072
LGEELTFEXP_LGEE->PJM
CLTF
4.553
WECLTFEXP_WEC->PJM
CLTF
4.843
CBM West 2LTFEXP_CBM-W2->PJM
CBM
98.823
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.157
AG2-052LTFEXP_AG2-052->PJM
LTF
0.305
AH1-155LTFEXP_AH1-155->PJM
LTF
0.457
CBM West 1LTFEXP_CBM-W1->PJM
CBM
159.327
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.302
MECLTFEXP_MEC->PJM
CLTF
18.121
SIGELTFEXP_SIGE->PJM
CLTF
0.416
LAGNLTFEXP_LAGN->PJM
CLTF
11.481
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.982
TVALTFEXP_TVA->PJM
CLTF
4.813

Details for 05MALIS-05VASSEL 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MALIS-05VASSEL 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.2 %
Rating:4142.0 MVA
Rating Type:A
MVA to Mitigate:4150.44
MW Contribution:8.3
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
2.576
24641605TWIN BRNCH
50/50
0.019
270475AD2-096_GEN
50/50
6.265
24344005CKG1
50/50
7.016
24642205MAYFLWER
50/50
0.721
970153AG2-106 GEN
Solar/Wind Harmer
43.566
24344105CKG2
50/50
8.761
270143AC1-141 CT2_
50/50
2.576
24639705ELKHART HY
50/50
0.174
970521AG2-332 GEN
50/50
12.426
962761AG1-125 GEN
Solar/Wind Harmer
68.224
970149AG2-104 GEN
Solar/Wind Harmer
73.684
970155AG2-107 GEN
Solar/Wind Harmer
43.566
970245AG2-165 GEN
Solar/Wind Harmer
3.385
270349AD2-093_GEN
Solar/Wind Harmer
0.006
270063AE2-323 C
Solar/Wind Harmer
0.006
270505AE1-170 C O1
Solar/Wind Harmer
7.821
965011AG1-365 GEN
Solar/Wind Harmer
7.432
945111AF1-176 GEN
Solar/Wind Harmer
13.254
274773LINCOLN ;4U
Adder
8.941
274774LINCOLN ;5U
Adder
8.941
270449AD2-020 GEN
Solar/Wind Harmer
0.001
270102X2-052 ST
50/50
1.727
270100X2-052 CT1
50/50
1.592
270101X2-052 CT2
50/50
1.592
247620Y3-023
50/50
0.521
970615AG2-402 GEN
50/50
2.477
970321AG2-212 GEN
Solar/Wind Harmer
3.385
270216AD2-079_GEN
Solar/Wind Harmer
0.001
270471AD2-092_GEN
Solar/Wind Harmer
0.006
965681AG1-436 GEN
Solar/Wind Harmer
9.376
965791AG1-447 GEN
Solar/Wind Harmer
6.876
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.432
970627AG2-408 GEN
Solar/Wind Harmer
2.23
961051AF2-396 GEN
Solar/Wind Harmer
14.796
961051AF2-396 GEN
Solar/Wind Harmer
9.864
274770LINCOLN ;1U
Adder
8.941
274771LINCOLN ;2U
Adder
8.941
274808UNIV PK N;4U
Adder
5.207
972259AH1-714 GEN
Adder
19.859
274803UNIV PARK;6U
Adder
6.068
274888KELLY CRK;1U
Solar/Wind Harmer
0.426
274887GEN-1.85
Solar/Wind Harmer
0.191
276843GEN-1.7
Solar/Wind Harmer
0.235
958011AF2-095 GEN
Solar/Wind Harmer
10.451
274674JOLIET 9 ;6U
Adder
15.907
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.332
274695ROCKY RD ;2P
Adder
11.339
274693ROCKY RD ;1P
Adder
11.227
274697ROCKY RD ;3P
Adder
3.08
274696ROCKY RD ;4P
Adder
11.606
958481AF2-142 GEN
Solar/Wind Harmer
10.652
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.96
274683WAUKEGAN ;8U
Adder
21.414
274683WAUKEGAN ;8U
Adder
18.051
962691AG1-118 GEN
Solar/Wind Harmer
21.207
970921AG2-575 GEN
Solar/Wind Harmer
7.056
970921AG2-575 GEN
Solar/Wind Harmer
2.352
958491AF2-143 GEN
Solar/Wind Harmer
10.561
942991AE2-321 GEN
Solar/Wind Harmer
7.837
274879MINONK ;1U
Solar/Wind Harmer
0.296
971333AH1-146 GEN
Solar/Wind Harmer
13.985
971335AH1-147 GEN
Solar/Wind Harmer
13.985
944541AF1-119 GEN
Solar/Wind Harmer
0.468
970349AG2-230 GEN
Solar/Wind Harmer
11.817
970513AG2-328 GEN
Solar/Wind Harmer
3.385
970517AG2-330 GEN
Solar/Wind Harmer
20.307
270043AE2-236 GEN
Solar/Wind Harmer
5
247643Z2-116 C
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
33.376
970031AG2-029 GEN
Solar/Wind Harmer
4.834
959331AF2-224 GEN
Solar/Wind Harmer
5.202
965021AG1-366 GEN
Solar/Wind Harmer
2.477
945111AF1-176 GEN
Solar/Wind Harmer
6.021
274772LINCOLN ;3U
Adder
8.941
274724RIVER EC ;11
Adder
18.592
274752CRETE EC ;2U
Adder
8.637
274753CRETE EC ;3U
Adder
8.637
970707AG2-453 GEN
Solar/Wind Harmer
23.798
274826FISK ;BP
Adder
11.395
274802UNIV PARK;5U
Adder
6.068
276806AD2-047 C O1
Solar/Wind Harmer
4.113
970941AG2-585 GEN
Solar/Wind Harmer
9.072
274800UNIV PARK;3U
Adder
6.064
972038AH1-567 GEN2
Adder
0.38
972228AH1-698 GEN2
Adder
3.852
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.6
274729ELWOOD EC;1P
Adder
16.971
274730ELWOOD EC;6P
Adder
16.972
274734ELWOOD EC;8P
Adder
16.972
274736ELWOOD EC;9P
Adder
16.972
276893AG1-478 C
Solar/Wind Harmer
0.285
247604X1-042
Adder
0.429
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
12.031
943591AF1-030 GEN
Solar/Wind Harmer
8
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.28
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.258
276805AD2-038 GEN
Solar/Wind Harmer
0.002
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.747
274855GSG-6 ;RU
Solar/Wind Harmer
0.257
274850MENDOTA H;RU
Solar/Wind Harmer
0.082
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.125
959091AF2-200 GEN
Solar/Wind Harmer
13.927
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.178
970571AG2-364 GEN
Solar/Wind Harmer
13.8
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.148
274767LEE CO EC;8U
Adder
9.041
276157O29GEN1
Solar/Wind Harmer
1.1
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.767
274878BISHOP HL;2U
Solar/Wind Harmer
0.227
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.043
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.944
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.925
959611AF2-252 GEN
Solar/Wind Harmer
2.214
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.704
970291AG2-192 GEN
Solar/Wind Harmer
0.64
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.949
270491AE1-102 GEN2
Solar/Wind Harmer
0.83
276668AB2-070 GEN1
Solar/Wind Harmer
0.233
276621W2-048 GEN
Solar/Wind Harmer
0.318
276838X2-022 GEN2
Solar/Wind Harmer
0.355
971617AH1-308 GEN
Solar/Wind Harmer
5.233
24721905FLATG4
Adder
18.123
270391AF1-285 GEN3
Solar/Wind Harmer
0.412
958821AF2-173 GEN
Solar/Wind Harmer
8.644
270004AE1-209 GEN
Solar/Wind Harmer
1.338
942481AE2-261 GEN
Solar/Wind Harmer
18.406
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270404AC1-167 GEN
Solar/Wind Harmer
0.003
946031AF1-268 GEN
Solar/Wind Harmer
5.724
943021AE2-325 GEN
Solar/Wind Harmer
3.852
274723RIVER EC ;12
Adder
18.809
274751CRETE EC ;1U
Adder
8.637
274754CRETE EC ;4U
Adder
8.637
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.23
970373AG2-245 GEN
Solar/Wind Harmer
15.278
276776AD2-060 GEN
Solar/Wind Harmer
0.758
274801UNIV PARK;4U
Adder
6.064
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.733
274674JOLIET 9 ;6U
Adder
15.907
274732ELWOOD EC;7P
Adder
16.972
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274745AC1-111 GEN9
Adder
5.741
276691AA1-018 GEN1
Solar/Wind Harmer
0.86
274682WAUKEGAN ;7U
Adder
18.28
274828WAUKEGAN ;BP
Adder
11.225
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.202
962781AG1-127 GEN
Solar/Wind Harmer
6.715
939401AE1-172 GEN
Solar/Wind Harmer
5.274
274872LEEDK;1U
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.679
276861AD2-134 GEN
Solar/Wind Harmer
0.125
965651AG1-433 GEN
Solar/Wind Harmer
2.05
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.708
957471AF2-041 GEN
Solar/Wind Harmer
20.89
959081AF2-199 GEN
Solar/Wind Harmer
6.963
971067AG2-660 GEN
Solar/Wind Harmer
2.321
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.54
972235AH1-702 GEN1
Adder
2.505
970819AG2-516 GEN
Solar/Wind Harmer
8.301
971475AH1-234 GEN
Solar/Wind Harmer
3.35
970569AG2-363 GEN
Solar/Wind Harmer
20.699
958861AF2-177 GEN
Solar/Wind Harmer
2.981
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.148
274766LEE CO EC;7U
Adder
9.041
276158O29GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.227
247521TR3_G114
Solar/Wind Harmer
0.245
270246TR4_N_V150
Solar/Wind Harmer
0.043
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.414
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.771
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24695305TIMB G C
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
5.377
965421AG1-410 GEN
Solar/Wind Harmer
19.447
970291AG2-192 GEN
Solar/Wind Harmer
0.832
274880W4-005 GEN4
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.259
270489AE1-102 GEN1
Solar/Wind Harmer
0.83
963831AG1-236 GEN
Solar/Wind Harmer
2.479
963741AG1-226 GEN
Solar/Wind Harmer
15.028
270032AE2-172
Solar/Wind Harmer
4.213
276615X2-022 GEN
Solar/Wind Harmer
0.066
24721705FLATG2
Adder
18.123
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
6.907
270005AE1-210 C O1
Solar/Wind Harmer
1.338
965031AG1-367 GEN
Solar/Wind Harmer
6.174
965911AG1-460 GEN
Solar/Wind Harmer
1.231
970825AG2-519 GEN
Solar/Wind Harmer
2.158
960971AF2-388 GEN
Solar/Wind Harmer
4.1
971341AH1-150 GEN
Solar/Wind Harmer
13.927
971343AH1-151 GEN
Solar/Wind Harmer
13.927
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.163
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.898
274764LEE CO EC;5U
Adder
9.17
274765LEE CO EC;6U
Adder
9.17
274762LEE CO EC;3U
Adder
9.148
274763LEE CO EC;4U
Adder
9.062
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.066
276741O09 GEN1
Solar/Wind Harmer
0.242
276708O09 GEN2
Solar/Wind Harmer
0.242
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.267
276646AC1-214 GEN2
Solar/Wind Harmer
0.267
276782AC1-033 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.034
960611AF2-352 GEN
Solar/Wind Harmer
2.214
966841AG1-555 GEN
Solar/Wind Harmer
0.746
270599AE1-208 GEN
Solar/Wind Harmer
5.869
270031AE2-169
Solar/Wind Harmer
3.522
246938BC-WTG3
Solar/Wind Harmer
0.231
246937BC-WTG2
Solar/Wind Harmer
0.259
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.704
971613AH1-306 GEN
Solar/Wind Harmer
3.033
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
270007AE1-245 C
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
12.852
276911AD2-131_GEN
Solar/Wind Harmer
0.847
960441AF2-335 GEN
Solar/Wind Harmer
6.101
970623AG2-406 GEN
Solar/Wind Harmer
1.115
970825AG2-519 GEN
Solar/Wind Harmer
6.738
971599AH1-298 GEN
50/50
10.4
270144AC1-141 ST1_
50/50
2.281
24653605MOTTVILLE
50/50
0.004
24643105BUCHANAN
50/50
0.014
962771AG1-126 GEN
Solar/Wind Harmer
68.224
971347AH1-153 GEN
Solar/Wind Harmer
11.817
270071AF1-092 GEN
Solar/Wind Harmer
14.657
971771AH1-392 GEN
Solar/Wind Harmer
7.525
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.356
971619AH1-309 GEN
Solar/Wind Harmer
3.352
274775LINCOLN ;6U
Adder
8.941
274776LINCOLN ;7U
Adder
8.941
274777LINCOLN ;8U
Adder
8.941
24729505KEY G4
Adder
6.812
274814UNIV PK N;0U
Adder
5.276
274807UNIV PK N;3U
Adder
5.265
274805UNIV PK N;1U
Adder
5.242
274811UNIV PK N;7U
Adder
5.23
274827FISK ;RP
Adder
8.075
972037AH1-567 GEN1
Adder
0.19
960591AF2-350 GEN
Solar/Wind Harmer
7.258
972227AH1-698 GEN1
Adder
2.712
274687WILL CNTY;4U
Adder
28.924
274687WILL CNTY;4U
Adder
28.924
274675JOLIET 29;7U
Adder
31.734
274675JOLIET 29;7U
Adder
30.6
274731ELWOOD EC;2P
Adder
16.971
274733ELWOOD EC;3P
Adder
16.971
274735ELWOOD EC;4P
Adder
16.971
274728ELWOOD EC;5P
Adder
16.972
970833AG2-524 GEN
Solar/Wind Harmer
7.918
970833AG2-524 GEN
Solar/Wind Harmer
5.279
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
274746AC1-111 G10
Adder
5.741
274744AC1-111 GEN8
Adder
5.741
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.408
276882AE2-255 GEN
Solar/Wind Harmer
0.821
971177AH1-047 GEN
Solar/Wind Harmer
4.327
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971675AH1-338 GEN
Solar/Wind Harmer
2.729
971411AH1-196 GEN
Solar/Wind Harmer
10.494
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971611AH1-305 GEN
Solar/Wind Harmer
4.147
971171AH1-044 GEN
Solar/Wind Harmer
13.927
274823ROCKFORD ;21
Adder
19.398
276612AE2-035 GEN
Solar/Wind Harmer
0.002
965041AG1-368 GEN
Solar/Wind Harmer
6.907
926823AC1-168 GEN
Solar/Wind Harmer
1.173
970169AG2-114 GEN
Solar/Wind Harmer
6.898
971681AH1-341 GEN
Solar/Wind Harmer
11.079
965101AG1-375 GEN
Solar/Wind Harmer
6.878
963791AG1-232 GEN
Solar/Wind Harmer
9.223
961011AF2-392 GEN
Solar/Wind Harmer
4.004
957751AF2-069 GEN
Solar/Wind Harmer
0.224
971549AH1-272 GEN
Solar/Wind Harmer
14.025
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
965051AG1-369 GEN
Solar/Wind Harmer
3.359
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.736
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.803
970289AG2-191 GEN
Solar/Wind Harmer
1.217
971609AH1-304 GEN
Solar/Wind Harmer
1.046
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.808
276849AB2-070 GEN2
Solar/Wind Harmer
0.233
276848AB2-070 GEN3
Solar/Wind Harmer
0.232
270594AE1-207 GEN
Solar/Wind Harmer
7.078
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270578AF1-285 GEN2
Solar/Wind Harmer
0.412
247607V1-011 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.44
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
NYPJM->LTFIMP_NY
CLTF
2.707
LGEELTFEXP_LGEE->PJM
CLTF
4.102
WECLTFEXP_WEC->PJM
CLTF
3.793
CPLELTFEXP_CPLE->PJM
CLTF
1.403
CBM West 2LTFEXP_CBM-W2->PJM
CBM
89.76
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.353
CBM West 1LTFEXP_CBM-W1->PJM
CBM
121.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.264
MECLTFEXP_MEC->PJM
CLTF
14.753
SIGELTFEXP_SIGE->PJM
CLTF
0.361
LAGNLTFEXP_LAGN->PJM
CLTF
11.568
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.749
TVALTFEXP_TVA->PJM
CLTF
5.27

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#711_05MARYSV 765_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#711_05MARYSV 765_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.69 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3397.1
MW Contribution:5.92
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.845
274770LINCOLN ;1U
Adder
3.364
274771LINCOLN ;2U
Adder
3.364
965681AG1-436 GEN
Solar/Wind Harmer
6.595
965791AG1-447 GEN
Solar/Wind Harmer
3.374
972259AH1-714 GEN
Adder
10.035
24721805FLATG3
50/50
1.058
24721705FLATG2
50/50
19.393
962761AG1-125 GEN
Solar/Wind Harmer
78.213
970149AG2-104 GEN
Solar/Wind Harmer
96.593
970155AG2-107 GEN
Solar/Wind Harmer
34.105
970245AG2-165 GEN
Solar/Wind Harmer
10.845
972207SS24-0001
Solar/Wind Harmer
11.962
274773LINCOLN ;4U
Adder
3.364
274774LINCOLN ;5U
Adder
3.364
276164X3-005 C
Solar/Wind Harmer
0.369
274723RIVER EC ;12
Adder
9.397
276776AD2-060 GEN
Solar/Wind Harmer
0.221
941551AE2-152 GEN
Solar/Wind Harmer
2.366
274801UNIV PARK;4U
Adder
3.041
274812UNIV PK N;8U
Adder
2.608
274751CRETE EC ;1U
Adder
2.543
274754CRETE EC ;4U
Adder
2.543
274676JOLIET 29;8U
Adder
15.941
274871GR RIDGE ;2U
Solar/Wind Harmer
3.99
274674JOLIET 9 ;6U
Adder
7.988
274732ELWOOD EC;7P
Adder
8.515
274745AC1-111 GEN9
Adder
2.891
274682WAUKEGAN ;7U
Adder
9.164
274828WAUKEGAN ;BP
Adder
5.626
276691AA1-018 GEN1
Solar/Wind Harmer
0.236
960751AF2-366 GEN
Solar/Wind Harmer
1.454
962781AG1-127 GEN
Solar/Wind Harmer
4.821
274872LEEDK;1U
Solar/Wind Harmer
4.155
970373AG2-245 GEN
Solar/Wind Harmer
10.535
939401AE1-172 GEN
Solar/Wind Harmer
6.99
276901AD2-066 C O1
Solar/Wind Harmer
1.76
276861AD2-134 GEN
Solar/Wind Harmer
0.895
971997AH1-543 GEN
Solar/Wind Harmer
7.867
957471AF2-041 GEN
Solar/Wind Harmer
14.934
959081AF2-199 GEN
Solar/Wind Harmer
4.978
971067AG2-660 GEN
Solar/Wind Harmer
1.158
274822ROCKFORD ;11
Adder
9.739
972235AH1-702 GEN1
Adder
1.248
970819AG2-516 GEN
Solar/Wind Harmer
5.922
276876AE1-163_GEN2
Solar/Wind Harmer
3.313
971475AH1-234 GEN
Solar/Wind Harmer
11.028
270055AF2-134 C O1
Solar/Wind Harmer
1.486
274857EASY ROAD;U1
Solar/Wind Harmer
2.338
274761LEE CO EC;2U
Adder
4.539
274766LEE CO EC;7U
Adder
4.486
24639705ELKHART HY
Adder
0.072
270349AD2-093_GEN
Solar/Wind Helper
4.665
270223U2-072_GEN1
Solar/Wind Helper
1.522
270578AF1-285 GEN2
Solar/Wind Helper
1.031
270391AF1-285 GEN3
Solar/Wind Helper
1.031
270462AD2-086
Solar/Wind Helper
5.319
247522W1-056 GEN
Solar/Wind Helper
1.149
253343AC1-166 GEN
Solar/Wind Helper
0.826
253325AC1-069 GEN
Solar/Wind Helper
0.856
960841AF2-375 GEN
Solar/Wind Helper
1.143
958961AF2-187 GEN
Solar/Wind Helper
1.121
270263AC1-001 GEN
Solar/Wind Helper
0.539
241840AF1-064_GEN
Solar/Wind Helper
0.473
241807AE2-176_GEN
Solar/Wind Helper
0.695
970569AG2-363 GEN
Solar/Wind Harmer
9.509
24721605FLATG1
50/50
1.058
962771AG1-126 GEN
Solar/Wind Harmer
78.213
971347AH1-153 GEN
Solar/Wind Harmer
8.723
274775LINCOLN ;6U
Adder
3.364
274776LINCOLN ;7U
Adder
3.364
274777LINCOLN ;8U
Adder
3.364
960681AF2-359 GEN
Solar/Wind Harmer
1.993
972227AH1-698 GEN1
Adder
1.364
960591AF2-350 GEN
Solar/Wind Harmer
5.222
274827FISK ;RP
Adder
4.049
972037AH1-567 GEN1
Adder
0.095
274814UNIV PK N;0U
Adder
2.631
274807UNIV PK N;3U
Adder
2.626
274805UNIV PK N;1U
Adder
2.614
274811UNIV PK N;7U
Adder
2.608
274687WILL CNTY;4U
Adder
14.52
274687WILL CNTY;4U
Adder
14.52
274675JOLIET 29;7U
Adder
15.941
274675JOLIET 29;7U
Adder
15.372
970833AG2-524 GEN
Solar/Wind Harmer
4.531
970833AG2-524 GEN
Solar/Wind Harmer
2.108
274731ELWOOD EC;2P
Adder
8.515
274733ELWOOD EC;3P
Adder
8.515
274735ELWOOD EC;4P
Adder
8.515
274728ELWOOD EC;5P
Adder
8.515
274746AC1-111 G10
Adder
2.891
274744AC1-111 GEN8
Adder
2.891
971769AH1-391 GEN
Solar/Wind Harmer
5.121
971771AH1-392 GEN
Solar/Wind Harmer
4.539
971177AH1-047 GEN
Solar/Wind Harmer
2.946
971675AH1-338 GEN
Solar/Wind Harmer
9.019
971411AH1-196 GEN
Solar/Wind Harmer
7.513
276868AE1-113 GEN
Solar/Wind Harmer
5.057
276882AE2-255 GEN
Solar/Wind Harmer
1.686
971171AH1-044 GEN
Solar/Wind Harmer
9.956
274823ROCKFORD ;21
Adder
9.668
274863CRW1-WTG
Solar/Wind Harmer
2.753
274864CRW2-WTG
Solar/Wind Harmer
2.753
276612AE2-035 GEN
Solar/Wind Harmer
1.261
270536AF1-215 GEN2
Solar/Wind Harmer
2.23
971681AH1-341 GEN
Solar/Wind Harmer
7.347
926823AC1-168 GEN
Solar/Wind Harmer
2.1
270284AF1-227 GEN1
Solar/Wind Helper
6.336
270286AF1-227 GEN2
Solar/Wind Helper
2.323
270287AF1-227 GEN3
Solar/Wind Helper
2.323
270317AD1-130_GEN
Solar/Wind Helper
5.891
253383AE2-342_GEN
Solar/Wind Helper
1.103
241973AD2-163_GEN1
Solar/Wind Helper
2.393
270520AE2-214 GEN
Solar/Wind Helper
6.251
270054AF2-122 C O1
Solar/Wind Helper
1.45
945631AF1-228 GEN
Solar/Wind Helper
1.86
966831AG1-554 GEN
Solar/Wind Helper
0.856
241972AD1-140 GEN
Solar/Wind Helper
3.072
945641AF1-229 GEN
Solar/Wind Helper
1.093
270499AE1-146 GEN
Solar/Wind Helper
1.872
270340AC2-060 GEN
Solar/Wind Helper
0.963
274888KELLY CRK;1U
Solar/Wind Harmer
3.083
274887GEN-1.85
Solar/Wind Harmer
2.783
276843GEN-1.7
Solar/Wind Harmer
0.299
958011AF2-095 GEN
Solar/Wind Harmer
7.52
274803UNIV PARK;6U
Adder
3.039
274808UNIV PK N;4U
Adder
2.597
274847GR RIDGE ;BU
Solar/Wind Harmer
2.625
274674JOLIET 9 ;6U
Adder
7.988
971573AH1-285 GEN
Solar/Wind Harmer
4.438
24441505OLIV SLR
Solar/Wind Harmer
0.069
274696ROCKY RD ;4P
Adder
5.826
274695ROCKY RD ;2P
Adder
5.692
274693ROCKY RD ;1P
Adder
5.636
274697ROCKY RD ;3P
Adder
1.546
270526AF1-158 GEN
Solar/Wind Harmer
2.32
274683WAUKEGAN ;8U
Adder
10.733
274683WAUKEGAN ;8U
Adder
9.047
962691AG1-118 GEN
Solar/Wind Harmer
15.245
958481AF2-142 GEN
Solar/Wind Harmer
7.607
970921AG2-575 GEN
Solar/Wind Harmer
5.069
970921AG2-575 GEN
Solar/Wind Harmer
1.179
274861TOP CROP ;1U
Solar/Wind Harmer
3.071
274862TOP CROP ;2U
Solar/Wind Harmer
2.564
942991AE2-321 GEN
Solar/Wind Harmer
5.03
958491AF2-143 GEN
Solar/Wind Harmer
7.519
971333AH1-146 GEN
Solar/Wind Harmer
10.012
971335AH1-147 GEN
Solar/Wind Harmer
10.012
274879MINONK ;1U
Solar/Wind Harmer
3.372
971341AH1-150 GEN
Solar/Wind Harmer
9.956
971343AH1-151 GEN
Solar/Wind Harmer
9.956
276872AE1-163_GEN1
Solar/Wind Harmer
3.313
274856ECOGROVE ;U1
Solar/Wind Harmer
1.662
276611AD2-172 GEN
Solar/Wind Harmer
1.261
938861AE1-114 GEN
Solar/Wind Harmer
4.014
274764LEE CO EC;5U
Adder
4.55
274765LEE CO EC;6U
Adder
4.55
274762LEE CO EC;3U
Adder
4.539
274763LEE CO EC;4U
Adder
4.497
972267AH1-718 GEN
Adder
2.012
247620Y3-023
Adder
0.206
270471AD2-092_GEN
Solar/Wind Helper
4.665
270224U2-072_GEN2
Solar/Wind Helper
1.522
270227U2-072_GEN3
Solar/Wind Helper
1.522
270228U2-072_GEN4
Solar/Wind Helper
1.522
270231U2-072_GEN5
Solar/Wind Helper
1.522
946101AF1-275 GEN
Solar/Wind Helper
0.783
241960AC2-195 GEN
Solar/Wind Helper
1.825
253378AE2-206_GEN
Solar/Wind Helper
1.285
276820AF1-078_GEN
Solar/Wind Helper
0.6
270518AE2-148 GEN
Solar/Wind Helper
10.557
24722005FLATG5
50/50
1.058
24721905FLATG4
50/50
19.393
970153AG2-106 GEN
Solar/Wind Harmer
34.105
970513AG2-328 GEN
Solar/Wind Harmer
10.845
970517AG2-330 GEN
Solar/Wind Harmer
9.837
970349AG2-230 GEN
Solar/Wind Harmer
8.723
274772LINCOLN ;3U
Adder
3.364
970707AG2-453 GEN
Solar/Wind Harmer
14.859
274724RIVER EC ;11
Adder
9.292
972228AH1-698 GEN2
Adder
1.937
276772AC2-154 GEN
Solar/Wind Harmer
1.456
276806AD2-047 C O1
Solar/Wind Harmer
5.586
970941AG2-585 GEN
Solar/Wind Harmer
6.528
274826FISK ;BP
Adder
5.714
276897AD1-100 C
Solar/Wind Harmer
15.138
939351AE1-166 GEN
Solar/Wind Harmer
3.093
274800UNIV PARK;3U
Adder
3.041
972038AH1-567 GEN2
Adder
0.19
274802UNIV PARK;5U
Adder
3.039
972231SS25-0005
Solar/Wind Harmer
4.937
972181SS23-001
Solar/Wind Harmer
3.086
274752CRETE EC ;2U
Adder
2.543
274753CRETE EC ;3U
Adder
2.543
274676JOLIET 29;8U
Adder
15.371
943121AE2-341 GEN
Solar/Wind Harmer
7.785
943591AF1-030 GEN
Solar/Wind Harmer
5.19
274729ELWOOD EC;1P
Adder
8.515
274730ELWOOD EC;6P
Adder
8.515
274734ELWOOD EC;8P
Adder
8.515
274736ELWOOD EC;9P
Adder
8.515
276893AG1-478 C
Solar/Wind Harmer
0.216
274682WAUKEGAN ;7U
Adder
9.164
276694AA1-018 GEN2
Solar/Wind Harmer
3.2
274872LEEDK;1U
Solar/Wind Harmer
0.129
276805AD2-038 GEN
Solar/Wind Harmer
2.572
276799AD1-013 GEN
Solar/Wind Harmer
1.108
946671AF1-331 GEN
Solar/Wind Harmer
0.21
274855GSG-6 ;RU
Solar/Wind Harmer
1.85
274850MENDOTA H;RU
Solar/Wind Harmer
1.286
276602WESTBROOK C
Solar/Wind Harmer
1.065
276863AD2-134 GEN
Solar/Wind Harmer
0.895
959091AF2-200 GEN
Solar/Wind Harmer
9.956
972236AH1-702 GEN2
Adder
1.085
276889AE2-281 GEN
Solar/Wind Harmer
0.947
24642205MAYFLWER
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
2.23
247643Z2-116 C
Solar/Wind Harmer
0.034
274858EASY ROAD;U2
Solar/Wind Harmer
2.338
274760LEE CO EC;1U
Adder
4.539
274767LEE CO EC;8U
Adder
4.486
247604X1-042
Adder
0.185
942871AE2-306 GEN
Solar/Wind Helper
0.773
270485AE1-090_GEN
Solar/Wind Helper
0.463
241974AD2-163_GEN2
Solar/Wind Helper
2.393
241955AC1-078 GEN
Solar/Wind Helper
2.378
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253338AC1-165 GEN
Solar/Wind Helper
0.826
253333AC1-068 GEN
Solar/Wind Helper
0.856
270273AD2-016 GEN
Solar/Wind Helper
1.657
270541AE2-072 C
Solar/Wind Helper
1.102
253415AE1-040 GEN
Solar/Wind Helper
0.453
970571AG2-364 GEN
Solar/Wind Harmer
6.339
NYPJM->LTFIMP_NY
CLTF
0.939
LGEELTFEXP_LGEE->PJM
CLTF
0.854
WECLTFEXP_WEC->PJM
CLTF
1.888
CPLELTFEXP_CPLE->PJM
CLTF
1.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.966
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.373
MECLTFEXP_MEC->PJM
CLTF
7.095
SIGELTFEXP_SIGE->PJM
CLTF
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
5.489
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.243
TVALTFEXP_TVA->PJM
CLTF
2.447

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:109.6 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3394.36
MW Contribution:5.83
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.698
274770LINCOLN ;1U
Adder
3.314
274771LINCOLN ;2U
Adder
3.314
965681AG1-436 GEN
Solar/Wind Harmer
6.493
965791AG1-447 GEN
Solar/Wind Harmer
3.322
972259AH1-714 GEN
Adder
9.882
274888KELLY CRK;1U
Solar/Wind Harmer
3.036
274887GEN-1.85
Solar/Wind Harmer
2.741
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.404
274803UNIV PARK;6U
Adder
2.992
274808UNIV PK N;4U
Adder
2.557
274847GR RIDGE ;BU
Solar/Wind Harmer
2.584
274674JOLIET 9 ;6U
Adder
7.865
971573AH1-285 GEN
Solar/Wind Harmer
4.369
24441505OLIV SLR
Solar/Wind Harmer
0.068
274696ROCKY RD ;4P
Adder
5.736
274695ROCKY RD ;2P
Adder
5.604
274693ROCKY RD ;1P
Adder
5.549
274697ROCKY RD ;3P
Adder
1.522
270526AF1-158 GEN
Solar/Wind Harmer
2.283
274683WAUKEGAN ;8U
Adder
10.566
274683WAUKEGAN ;8U
Adder
8.906
962691AG1-118 GEN
Solar/Wind Harmer
15.007
958481AF2-142 GEN
Solar/Wind Harmer
7.488
970921AG2-575 GEN
Solar/Wind Harmer
4.99
970921AG2-575 GEN
Solar/Wind Harmer
1.161
274861TOP CROP ;1U
Solar/Wind Harmer
3.023
24721605FLATG1
50/50
1.054
962771AG1-126 GEN
Solar/Wind Harmer
77.929
971347AH1-153 GEN
Solar/Wind Harmer
8.598
274775LINCOLN ;6U
Adder
3.314
274776LINCOLN ;7U
Adder
3.314
274777LINCOLN ;8U
Adder
3.314
960681AF2-359 GEN
Solar/Wind Harmer
1.962
972227AH1-698 GEN1
Adder
1.343
960591AF2-350 GEN
Solar/Wind Harmer
5.142
274827FISK ;RP
Adder
3.987
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.591
274807UNIV PK N;3U
Adder
2.585
274805UNIV PK N;1U
Adder
2.574
274811UNIV PK N;7U
Adder
2.568
274675JOLIET 29;7U
Adder
15.696
274675JOLIET 29;7U
Adder
15.135
274687WILL CNTY;4U
Adder
14.296
274687WILL CNTY;4U
Adder
14.296
970833AG2-524 GEN
Solar/Wind Harmer
4.461
970833AG2-524 GEN
Solar/Wind Harmer
2.075
274731ELWOOD EC;2P
Adder
8.383
274733ELWOOD EC;3P
Adder
8.383
274735ELWOOD EC;4P
Adder
8.383
274728ELWOOD EC;5P
Adder
8.383
274746AC1-111 G10
Adder
2.846
274744AC1-111 GEN8
Adder
2.846
971769AH1-391 GEN
Solar/Wind Harmer
5.039
971771AH1-392 GEN
Solar/Wind Harmer
4.464
971177AH1-047 GEN
Solar/Wind Harmer
2.9
971675AH1-338 GEN
Solar/Wind Harmer
8.877
971411AH1-196 GEN
Solar/Wind Harmer
7.395
276868AE1-113 GEN
Solar/Wind Harmer
4.977
276882AE2-255 GEN
Solar/Wind Harmer
1.659
971171AH1-044 GEN
Solar/Wind Harmer
9.799
274823ROCKFORD ;21
Adder
9.515
274863CRW1-WTG
Solar/Wind Harmer
2.709
274864CRW2-WTG
Solar/Wind Harmer
2.709
276612AE2-035 GEN
Solar/Wind Harmer
1.241
270536AF1-215 GEN2
Solar/Wind Harmer
2.193
971681AH1-341 GEN
Solar/Wind Harmer
7.23
926823AC1-168 GEN
Solar/Wind Harmer
2.067
270284AF1-227 GEN1
Solar/Wind Helper
6.373
24722005FLATG5
50/50
1.054
24721905FLATG4
50/50
19.316
970153AG2-106 GEN
Solar/Wind Harmer
33.981
970513AG2-328 GEN
Solar/Wind Harmer
10.698
970517AG2-330 GEN
Solar/Wind Harmer
9.703
970349AG2-230 GEN
Solar/Wind Harmer
8.598
274772LINCOLN ;3U
Adder
3.314
970707AG2-453 GEN
Solar/Wind Harmer
14.634
274724RIVER EC ;11
Adder
9.15
972228AH1-698 GEN2
Adder
1.907
276772AC2-154 GEN
Solar/Wind Harmer
1.434
276806AD2-047 C O1
Solar/Wind Harmer
5.5
970941AG2-585 GEN
Solar/Wind Harmer
6.427
274826FISK ;BP
Adder
5.626
276897AD1-100 C
Solar/Wind Harmer
14.905
939351AE1-166 GEN
Solar/Wind Harmer
3.046
274800UNIV PARK;3U
Adder
2.994
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.992
972231SS25-0005
Solar/Wind Harmer
4.861
972181SS23-001
Solar/Wind Harmer
3.038
274752CRETE EC ;2U
Adder
2.503
274753CRETE EC ;3U
Adder
2.503
274676JOLIET 29;8U
Adder
15.135
943121AE2-341 GEN
Solar/Wind Harmer
7.665
943591AF1-030 GEN
Solar/Wind Harmer
5.11
274729ELWOOD EC;1P
Adder
8.383
274730ELWOOD EC;6P
Adder
8.383
274734ELWOOD EC;8P
Adder
8.383
274736ELWOOD EC;9P
Adder
8.383
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.022
276694AA1-018 GEN2
Solar/Wind Harmer
3.15
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.091
946671AF1-331 GEN
Solar/Wind Harmer
0.207
276805AD2-038 GEN
Solar/Wind Harmer
2.531
274855GSG-6 ;RU
Solar/Wind Harmer
1.821
274850MENDOTA H;RU
Solar/Wind Harmer
1.266
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.881
959091AF2-200 GEN
Solar/Wind Harmer
9.799
972236AH1-702 GEN2
Adder
1.068
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.308
270535AF1-215 GEN1
Solar/Wind Harmer
2.193
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.301
274760LEE CO EC;1U
Adder
4.467
274767LEE CO EC;8U
Adder
4.414
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.428
241955AC1-078 GEN
Solar/Wind Helper
2.425
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.698
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.237
270286AF1-227 GEN2
Solar/Wind Helper
2.337
270287AF1-227 GEN3
Solar/Wind Helper
2.337
270317AD1-130_GEN
Solar/Wind Helper
5.933
253383AE2-342_GEN
Solar/Wind Helper
1.119
241973AD2-163_GEN1
Solar/Wind Helper
2.428
270520AE2-214 GEN
Solar/Wind Helper
6.383
270054AF2-122 C O1
Solar/Wind Helper
1.467
945631AF1-228 GEN
Solar/Wind Helper
1.9
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.134
945641AF1-229 GEN
Solar/Wind Helper
1.104
270499AE1-146 GEN
Solar/Wind Helper
1.892
270340AC2-060 GEN
Solar/Wind Helper
0.99
274862TOP CROP ;2U
Solar/Wind Harmer
2.524
942991AE2-321 GEN
Solar/Wind Harmer
4.951
958491AF2-143 GEN
Solar/Wind Harmer
7.4
971333AH1-146 GEN
Solar/Wind Harmer
9.855
971335AH1-147 GEN
Solar/Wind Harmer
9.855
274879MINONK ;1U
Solar/Wind Harmer
3.318
971341AH1-150 GEN
Solar/Wind Harmer
9.799
971343AH1-151 GEN
Solar/Wind Harmer
9.799
276872AE1-163_GEN1
Solar/Wind Harmer
3.26
274856ECOGROVE ;U1
Solar/Wind Harmer
1.636
276611AD2-172 GEN
Solar/Wind Harmer
1.241
938861AE1-114 GEN
Solar/Wind Harmer
3.95
274764LEE CO EC;5U
Adder
4.477
274765LEE CO EC;6U
Adder
4.477
274762LEE CO EC;3U
Adder
4.467
274763LEE CO EC;4U
Adder
4.425
972267AH1-718 GEN
Adder
1.98
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.69
270224U2-072_GEN2
Solar/Wind Helper
1.532
270227U2-072_GEN3
Solar/Wind Helper
1.532
270228U2-072_GEN4
Solar/Wind Helper
1.532
270231U2-072_GEN5
Solar/Wind Helper
1.532
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.845
253378AE2-206_GEN
Solar/Wind Helper
1.302
276820AF1-078_GEN
Solar/Wind Helper
0.608
270518AE2-148 GEN
Solar/Wind Helper
10.792
24721805FLATG3
50/50
1.054
24721705FLATG2
50/50
19.316
962761AG1-125 GEN
Solar/Wind Harmer
77.929
970149AG2-104 GEN
Solar/Wind Harmer
96.242
970155AG2-107 GEN
Solar/Wind Harmer
33.981
970245AG2-165 GEN
Solar/Wind Harmer
10.698
972207SS24-0001
Solar/Wind Harmer
11.784
274773LINCOLN ;4U
Adder
3.314
274774LINCOLN ;5U
Adder
3.314
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.252
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.329
274801UNIV PARK;4U
Adder
2.994
274812UNIV PK N;8U
Adder
2.568
274751CRETE EC ;1U
Adder
2.503
274754CRETE EC ;4U
Adder
2.503
274676JOLIET 29;8U
Adder
15.695
274871GR RIDGE ;2U
Solar/Wind Harmer
3.929
274674JOLIET 9 ;6U
Adder
7.865
274732ELWOOD EC;7P
Adder
8.383
274745AC1-111 GEN9
Adder
2.846
274682WAUKEGAN ;7U
Adder
9.022
274828WAUKEGAN ;BP
Adder
5.538
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.432
962781AG1-127 GEN
Solar/Wind Harmer
4.746
274872LEEDK;1U
Solar/Wind Harmer
4.09
939401AE1-172 GEN
Solar/Wind Harmer
6.878
970373AG2-245 GEN
Solar/Wind Harmer
10.364
276901AD2-066 C O1
Solar/Wind Harmer
1.733
276861AD2-134 GEN
Solar/Wind Harmer
0.881
971997AH1-543 GEN
Solar/Wind Harmer
7.742
957471AF2-041 GEN
Solar/Wind Harmer
14.698
959081AF2-199 GEN
Solar/Wind Harmer
4.899
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.585
972235AH1-702 GEN1
Adder
1.228
970819AG2-516 GEN
Solar/Wind Harmer
5.828
276876AE1-163_GEN2
Solar/Wind Harmer
3.26
971475AH1-234 GEN
Solar/Wind Harmer
10.852
270055AF2-134 C O1
Solar/Wind Harmer
1.462
274857EASY ROAD;U1
Solar/Wind Harmer
2.301
274761LEE CO EC;2U
Adder
4.467
274766LEE CO EC;7U
Adder
4.414
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.69
270223U2-072_GEN1
Solar/Wind Helper
1.532
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.357
247522W1-056 GEN
Solar/Wind Helper
1.161
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.156
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.355
NYPJM->LTFIMP_NY
CLTF
0.911
LGEELTFEXP_LGEE->PJM
CLTF
0.799
WECLTFEXP_WEC->PJM
CLTF
1.858
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.096
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.154
MECLTFEXP_MEC->PJM
CLTF
6.971
SIGELTFEXP_SIGE->PJM
CLTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
5.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.184
TVALTFEXP_TVA->PJM
CLTF
2.393

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.59 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3394.1
MW Contribution:5.83
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.054
24721705FLATG2
50/50
19.316
962761AG1-125 GEN
Solar/Wind Harmer
77.929
970149AG2-104 GEN
Solar/Wind Harmer
96.242
970155AG2-107 GEN
Solar/Wind Harmer
33.981
970245AG2-165 GEN
Solar/Wind Harmer
10.698
972207SS24-0001
Solar/Wind Harmer
11.784
274773LINCOLN ;4U
Adder
3.314
274774LINCOLN ;5U
Adder
3.314
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.252
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.329
274801UNIV PARK;4U
Adder
2.994
274812UNIV PK N;8U
Adder
2.568
274751CRETE EC ;1U
Adder
2.503
274754CRETE EC ;4U
Adder
2.503
274676JOLIET 29;8U
Adder
15.695
274871GR RIDGE ;2U
Solar/Wind Harmer
3.929
274674JOLIET 9 ;6U
Adder
7.865
274732ELWOOD EC;7P
Adder
8.383
274745AC1-111 GEN9
Adder
2.846
274682WAUKEGAN ;7U
Adder
9.022
274828WAUKEGAN ;BP
Adder
5.538
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.432
962781AG1-127 GEN
Solar/Wind Harmer
4.746
274872LEEDK;1U
Solar/Wind Harmer
4.09
939401AE1-172 GEN
Solar/Wind Harmer
6.878
970373AG2-245 GEN
Solar/Wind Harmer
10.364
276901AD2-066 C O1
Solar/Wind Harmer
1.733
276861AD2-134 GEN
Solar/Wind Harmer
0.881
971997AH1-543 GEN
Solar/Wind Harmer
7.742
957471AF2-041 GEN
Solar/Wind Harmer
14.698
959081AF2-199 GEN
Solar/Wind Harmer
4.899
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.585
972235AH1-702 GEN1
Adder
1.228
970819AG2-516 GEN
Solar/Wind Harmer
5.828
276876AE1-163_GEN2
Solar/Wind Harmer
3.26
971475AH1-234 GEN
Solar/Wind Harmer
10.852
270055AF2-134 C O1
Solar/Wind Harmer
1.462
274857EASY ROAD;U1
Solar/Wind Harmer
2.301
274761LEE CO EC;2U
Adder
4.467
274766LEE CO EC;7U
Adder
4.414
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.69
270223U2-072_GEN1
Solar/Wind Helper
1.532
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.357
247522W1-056 GEN
Solar/Wind Helper
1.161
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.156
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.355
24721605FLATG1
50/50
1.054
962771AG1-126 GEN
Solar/Wind Harmer
77.929
971347AH1-153 GEN
Solar/Wind Harmer
8.598
274775LINCOLN ;6U
Adder
3.314
274776LINCOLN ;7U
Adder
3.314
274777LINCOLN ;8U
Adder
3.314
960681AF2-359 GEN
Solar/Wind Harmer
1.962
972227AH1-698 GEN1
Adder
1.343
960591AF2-350 GEN
Solar/Wind Harmer
5.142
274827FISK ;RP
Adder
3.987
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.591
274807UNIV PK N;3U
Adder
2.585
274805UNIV PK N;1U
Adder
2.574
274811UNIV PK N;7U
Adder
2.568
274675JOLIET 29;7U
Adder
15.696
274675JOLIET 29;7U
Adder
15.135
274687WILL CNTY;4U
Adder
14.296
274687WILL CNTY;4U
Adder
14.296
970833AG2-524 GEN
Solar/Wind Harmer
4.461
970833AG2-524 GEN
Solar/Wind Harmer
2.075
274731ELWOOD EC;2P
Adder
8.383
274733ELWOOD EC;3P
Adder
8.383
274735ELWOOD EC;4P
Adder
8.383
274728ELWOOD EC;5P
Adder
8.383
274746AC1-111 G10
Adder
2.846
274744AC1-111 GEN8
Adder
2.846
971769AH1-391 GEN
Solar/Wind Harmer
5.039
971771AH1-392 GEN
Solar/Wind Harmer
4.464
971177AH1-047 GEN
Solar/Wind Harmer
2.9
971675AH1-338 GEN
Solar/Wind Harmer
8.877
971411AH1-196 GEN
Solar/Wind Harmer
7.395
276868AE1-113 GEN
Solar/Wind Harmer
4.977
276882AE2-255 GEN
Solar/Wind Harmer
1.659
971171AH1-044 GEN
Solar/Wind Harmer
9.799
274823ROCKFORD ;21
Adder
9.515
274863CRW1-WTG
Solar/Wind Harmer
2.709
274864CRW2-WTG
Solar/Wind Harmer
2.709
276612AE2-035 GEN
Solar/Wind Harmer
1.241
270536AF1-215 GEN2
Solar/Wind Harmer
2.193
971681AH1-341 GEN
Solar/Wind Harmer
7.23
926823AC1-168 GEN
Solar/Wind Harmer
2.067
270284AF1-227 GEN1
Solar/Wind Helper
6.373
270286AF1-227 GEN2
Solar/Wind Helper
2.337
270287AF1-227 GEN3
Solar/Wind Helper
2.337
270317AD1-130_GEN
Solar/Wind Helper
5.933
253383AE2-342_GEN
Solar/Wind Helper
1.119
241973AD2-163_GEN1
Solar/Wind Helper
2.428
270520AE2-214 GEN
Solar/Wind Helper
6.383
270054AF2-122 C O1
Solar/Wind Helper
1.467
945631AF1-228 GEN
Solar/Wind Helper
1.9
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.134
945641AF1-229 GEN
Solar/Wind Helper
1.104
270499AE1-146 GEN
Solar/Wind Helper
1.892
270340AC2-060 GEN
Solar/Wind Helper
0.99
970321AG2-212 GEN
Solar/Wind Harmer
10.698
274770LINCOLN ;1U
Adder
3.314
274771LINCOLN ;2U
Adder
3.314
965681AG1-436 GEN
Solar/Wind Harmer
6.493
965791AG1-447 GEN
Solar/Wind Harmer
3.322
972259AH1-714 GEN
Adder
9.882
274888KELLY CRK;1U
Solar/Wind Harmer
3.036
274887GEN-1.85
Solar/Wind Harmer
2.741
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.404
274803UNIV PARK;6U
Adder
2.992
274808UNIV PK N;4U
Adder
2.557
274847GR RIDGE ;BU
Solar/Wind Harmer
2.584
274674JOLIET 9 ;6U
Adder
7.865
971573AH1-285 GEN
Solar/Wind Harmer
4.369
24441505OLIV SLR
Solar/Wind Harmer
0.068
274696ROCKY RD ;4P
Adder
5.736
274695ROCKY RD ;2P
Adder
5.604
274693ROCKY RD ;1P
Adder
5.549
274697ROCKY RD ;3P
Adder
1.522
270526AF1-158 GEN
Solar/Wind Harmer
2.283
274683WAUKEGAN ;8U
Adder
10.566
274683WAUKEGAN ;8U
Adder
8.906
962691AG1-118 GEN
Solar/Wind Harmer
15.007
958481AF2-142 GEN
Solar/Wind Harmer
7.488
970921AG2-575 GEN
Solar/Wind Harmer
4.99
970921AG2-575 GEN
Solar/Wind Harmer
1.161
274861TOP CROP ;1U
Solar/Wind Harmer
3.023
274862TOP CROP ;2U
Solar/Wind Harmer
2.524
942991AE2-321 GEN
Solar/Wind Harmer
4.951
958491AF2-143 GEN
Solar/Wind Harmer
7.4
971333AH1-146 GEN
Solar/Wind Harmer
9.855
971335AH1-147 GEN
Solar/Wind Harmer
9.855
274879MINONK ;1U
Solar/Wind Harmer
3.318
971341AH1-150 GEN
Solar/Wind Harmer
9.799
971343AH1-151 GEN
Solar/Wind Harmer
9.799
276872AE1-163_GEN1
Solar/Wind Harmer
3.26
274856ECOGROVE ;U1
Solar/Wind Harmer
1.636
276611AD2-172 GEN
Solar/Wind Harmer
1.241
938861AE1-114 GEN
Solar/Wind Harmer
3.95
274764LEE CO EC;5U
Adder
4.477
274765LEE CO EC;6U
Adder
4.477
274762LEE CO EC;3U
Adder
4.467
274763LEE CO EC;4U
Adder
4.425
972267AH1-718 GEN
Adder
1.98
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.69
270224U2-072_GEN2
Solar/Wind Helper
1.532
270227U2-072_GEN3
Solar/Wind Helper
1.532
270228U2-072_GEN4
Solar/Wind Helper
1.532
270231U2-072_GEN5
Solar/Wind Helper
1.532
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.845
253378AE2-206_GEN
Solar/Wind Helper
1.302
276820AF1-078_GEN
Solar/Wind Helper
0.608
270518AE2-148 GEN
Solar/Wind Helper
10.792
24722005FLATG5
50/50
1.054
24721905FLATG4
50/50
19.316
970153AG2-106 GEN
Solar/Wind Harmer
33.981
970513AG2-328 GEN
Solar/Wind Harmer
10.698
970517AG2-330 GEN
Solar/Wind Harmer
9.703
970349AG2-230 GEN
Solar/Wind Harmer
8.598
274772LINCOLN ;3U
Adder
3.314
970707AG2-453 GEN
Solar/Wind Harmer
14.634
274724RIVER EC ;11
Adder
9.15
972228AH1-698 GEN2
Adder
1.907
276772AC2-154 GEN
Solar/Wind Harmer
1.434
276806AD2-047 C O1
Solar/Wind Harmer
5.5
970941AG2-585 GEN
Solar/Wind Harmer
6.427
274826FISK ;BP
Adder
5.626
276897AD1-100 C
Solar/Wind Harmer
14.905
939351AE1-166 GEN
Solar/Wind Harmer
3.046
274800UNIV PARK;3U
Adder
2.994
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.992
972231SS25-0005
Solar/Wind Harmer
4.861
972181SS23-001
Solar/Wind Harmer
3.038
274752CRETE EC ;2U
Adder
2.503
274753CRETE EC ;3U
Adder
2.503
274676JOLIET 29;8U
Adder
15.135
943121AE2-341 GEN
Solar/Wind Harmer
7.665
943591AF1-030 GEN
Solar/Wind Harmer
5.11
274729ELWOOD EC;1P
Adder
8.383
274730ELWOOD EC;6P
Adder
8.383
274734ELWOOD EC;8P
Adder
8.383
274736ELWOOD EC;9P
Adder
8.383
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.022
276694AA1-018 GEN2
Solar/Wind Harmer
3.15
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.091
946671AF1-331 GEN
Solar/Wind Harmer
0.207
276805AD2-038 GEN
Solar/Wind Harmer
2.531
274855GSG-6 ;RU
Solar/Wind Harmer
1.821
274850MENDOTA H;RU
Solar/Wind Harmer
1.266
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.881
959091AF2-200 GEN
Solar/Wind Harmer
9.799
972236AH1-702 GEN2
Adder
1.068
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.308
270535AF1-215 GEN1
Solar/Wind Harmer
2.193
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.301
274760LEE CO EC;1U
Adder
4.467
274767LEE CO EC;8U
Adder
4.414
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.428
241955AC1-078 GEN
Solar/Wind Helper
2.425
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.698
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.237
NYPJM->LTFIMP_NY
CLTF
0.911
LGEELTFEXP_LGEE->PJM
CLTF
0.799
WECLTFEXP_WEC->PJM
CLTF
1.858
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.096
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.154
MECLTFEXP_MEC->PJM
CLTF
6.971
SIGELTFEXP_SIGE->PJM
CLTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
5.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.184
TVALTFEXP_TVA->PJM
CLTF
2.393

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3392.25
MW Contribution:5.83
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.053
24721705FLATG2
50/50
19.313
962761AG1-125 GEN
Solar/Wind Harmer
77.914
970149AG2-104 GEN
Solar/Wind Harmer
96.223
970155AG2-107 GEN
Solar/Wind Harmer
33.974
970245AG2-165 GEN
Solar/Wind Harmer
10.693
972207SS24-0001
Solar/Wind Harmer
11.777
274773LINCOLN ;4U
Adder
3.312
274774LINCOLN ;5U
Adder
3.312
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.247
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.328
274801UNIV PARK;4U
Adder
2.992
274812UNIV PK N;8U
Adder
2.567
274751CRETE EC ;1U
Adder
2.502
274754CRETE EC ;4U
Adder
2.502
274676JOLIET 29;8U
Adder
15.686
274871GR RIDGE ;2U
Solar/Wind Harmer
3.926
274674JOLIET 9 ;6U
Adder
7.861
274732ELWOOD EC;7P
Adder
8.378
274745AC1-111 GEN9
Adder
2.845
274682WAUKEGAN ;7U
Adder
9.017
274828WAUKEGAN ;BP
Adder
5.535
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.431
962781AG1-127 GEN
Solar/Wind Harmer
4.743
274872LEEDK;1U
Solar/Wind Harmer
4.087
939401AE1-172 GEN
Solar/Wind Harmer
6.874
970373AG2-245 GEN
Solar/Wind Harmer
10.358
276901AD2-066 C O1
Solar/Wind Harmer
1.732
276861AD2-134 GEN
Solar/Wind Harmer
0.88
971997AH1-543 GEN
Solar/Wind Harmer
7.738
957471AF2-041 GEN
Solar/Wind Harmer
14.689
959081AF2-199 GEN
Solar/Wind Harmer
4.896
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.579
972235AH1-702 GEN1
Adder
1.227
970819AG2-516 GEN
Solar/Wind Harmer
5.825
276876AE1-163_GEN2
Solar/Wind Harmer
3.258
971475AH1-234 GEN
Solar/Wind Harmer
10.846
270055AF2-134 C O1
Solar/Wind Harmer
1.461
274857EASY ROAD;U1
Solar/Wind Harmer
2.299
274761LEE CO EC;2U
Adder
4.464
274766LEE CO EC;7U
Adder
4.412
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.692
270223U2-072_GEN1
Solar/Wind Helper
1.533
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.359
247522W1-056 GEN
Solar/Wind Helper
1.162
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.157
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.35
24721605FLATG1
50/50
1.053
962771AG1-126 GEN
Solar/Wind Harmer
77.914
971347AH1-153 GEN
Solar/Wind Harmer
8.593
274775LINCOLN ;6U
Adder
3.312
274776LINCOLN ;7U
Adder
3.312
274777LINCOLN ;8U
Adder
3.312
960681AF2-359 GEN
Solar/Wind Harmer
1.961
972227AH1-698 GEN1
Adder
1.342
960591AF2-350 GEN
Solar/Wind Harmer
5.139
274827FISK ;RP
Adder
3.985
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.589
274807UNIV PK N;3U
Adder
2.583
274805UNIV PK N;1U
Adder
2.572
274811UNIV PK N;7U
Adder
2.567
274687WILL CNTY;4U
Adder
14.288
274687WILL CNTY;4U
Adder
14.288
274675JOLIET 29;7U
Adder
15.686
274675JOLIET 29;7U
Adder
15.126
970833AG2-524 GEN
Solar/Wind Harmer
4.459
970833AG2-524 GEN
Solar/Wind Harmer
2.074
274731ELWOOD EC;2P
Adder
8.379
274733ELWOOD EC;3P
Adder
8.379
274735ELWOOD EC;4P
Adder
8.379
274728ELWOOD EC;5P
Adder
8.378
274746AC1-111 G10
Adder
2.845
274744AC1-111 GEN8
Adder
2.845
971769AH1-391 GEN
Solar/Wind Harmer
5.036
971771AH1-392 GEN
Solar/Wind Harmer
4.462
971177AH1-047 GEN
Solar/Wind Harmer
2.899
971675AH1-338 GEN
Solar/Wind Harmer
8.872
971411AH1-196 GEN
Solar/Wind Harmer
7.391
276868AE1-113 GEN
Solar/Wind Harmer
4.974
276882AE2-255 GEN
Solar/Wind Harmer
1.658
971171AH1-044 GEN
Solar/Wind Harmer
9.793
274823ROCKFORD ;21
Adder
9.51
274863CRW1-WTG
Solar/Wind Harmer
2.707
274864CRW2-WTG
Solar/Wind Harmer
2.707
276612AE2-035 GEN
Solar/Wind Harmer
1.241
270536AF1-215 GEN2
Solar/Wind Harmer
2.192
971681AH1-341 GEN
Solar/Wind Harmer
7.225
926823AC1-168 GEN
Solar/Wind Harmer
2.065
270284AF1-227 GEN1
Solar/Wind Helper
6.375
270286AF1-227 GEN2
Solar/Wind Helper
2.338
270287AF1-227 GEN3
Solar/Wind Helper
2.338
270317AD1-130_GEN
Solar/Wind Helper
5.935
253383AE2-342_GEN
Solar/Wind Helper
1.12
241973AD2-163_GEN1
Solar/Wind Helper
2.43
270520AE2-214 GEN
Solar/Wind Helper
6.387
270054AF2-122 C O1
Solar/Wind Helper
1.465
945631AF1-228 GEN
Solar/Wind Helper
1.901
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.137
945641AF1-229 GEN
Solar/Wind Helper
1.105
270499AE1-146 GEN
Solar/Wind Helper
1.893
270340AC2-060 GEN
Solar/Wind Helper
0.99
970321AG2-212 GEN
Solar/Wind Harmer
10.693
274770LINCOLN ;1U
Adder
3.312
274771LINCOLN ;2U
Adder
3.312
965681AG1-436 GEN
Solar/Wind Harmer
6.489
965791AG1-447 GEN
Solar/Wind Harmer
3.32
972259AH1-714 GEN
Adder
9.876
274888KELLY CRK;1U
Solar/Wind Harmer
3.034
274887GEN-1.85
Solar/Wind Harmer
2.739
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.4
274803UNIV PARK;6U
Adder
2.99
274808UNIV PK N;4U
Adder
2.555
274847GR RIDGE ;BU
Solar/Wind Harmer
2.583
274674JOLIET 9 ;6U
Adder
7.861
971573AH1-285 GEN
Solar/Wind Harmer
4.367
24441505OLIV SLR
Solar/Wind Harmer
0.067
274696ROCKY RD ;4P
Adder
5.733
274695ROCKY RD ;2P
Adder
5.601
274693ROCKY RD ;1P
Adder
5.545
274697ROCKY RD ;3P
Adder
1.521
270526AF1-158 GEN
Solar/Wind Harmer
2.281
274683WAUKEGAN ;8U
Adder
10.559
274683WAUKEGAN ;8U
Adder
8.901
962691AG1-118 GEN
Solar/Wind Harmer
14.999
958481AF2-142 GEN
Solar/Wind Harmer
7.483
970921AG2-575 GEN
Solar/Wind Harmer
4.988
970921AG2-575 GEN
Solar/Wind Harmer
1.16
274861TOP CROP ;1U
Solar/Wind Harmer
3.021
274862TOP CROP ;2U
Solar/Wind Harmer
2.523
942991AE2-321 GEN
Solar/Wind Harmer
4.948
958491AF2-143 GEN
Solar/Wind Harmer
7.396
971333AH1-146 GEN
Solar/Wind Harmer
9.849
971335AH1-147 GEN
Solar/Wind Harmer
9.849
274879MINONK ;1U
Solar/Wind Harmer
3.316
971341AH1-150 GEN
Solar/Wind Harmer
9.793
971343AH1-151 GEN
Solar/Wind Harmer
9.793
276872AE1-163_GEN1
Solar/Wind Harmer
3.258
274856ECOGROVE ;U1
Solar/Wind Harmer
1.635
276611AD2-172 GEN
Solar/Wind Harmer
1.241
938861AE1-114 GEN
Solar/Wind Harmer
3.948
274764LEE CO EC;5U
Adder
4.475
274765LEE CO EC;6U
Adder
4.475
274762LEE CO EC;3U
Adder
4.464
274763LEE CO EC;4U
Adder
4.422
972267AH1-718 GEN
Adder
1.979
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.692
270224U2-072_GEN2
Solar/Wind Helper
1.533
270227U2-072_GEN3
Solar/Wind Helper
1.533
270228U2-072_GEN4
Solar/Wind Helper
1.533
270231U2-072_GEN5
Solar/Wind Helper
1.533
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.846
253378AE2-206_GEN
Solar/Wind Helper
1.303
276820AF1-078_GEN
Solar/Wind Helper
0.609
270518AE2-148 GEN
Solar/Wind Helper
10.796
24722005FLATG5
50/50
1.053
24721905FLATG4
50/50
19.313
970153AG2-106 GEN
Solar/Wind Harmer
33.974
970513AG2-328 GEN
Solar/Wind Harmer
10.693
970517AG2-330 GEN
Solar/Wind Harmer
9.698
970349AG2-230 GEN
Solar/Wind Harmer
8.593
274772LINCOLN ;3U
Adder
3.312
970707AG2-453 GEN
Solar/Wind Harmer
14.626
274724RIVER EC ;11
Adder
9.144
972228AH1-698 GEN2
Adder
1.906
276772AC2-154 GEN
Solar/Wind Harmer
1.433
276806AD2-047 C O1
Solar/Wind Harmer
5.497
970941AG2-585 GEN
Solar/Wind Harmer
6.423
274826FISK ;BP
Adder
5.622
276897AD1-100 C
Solar/Wind Harmer
14.897
939351AE1-166 GEN
Solar/Wind Harmer
3.044
274800UNIV PARK;3U
Adder
2.992
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.99
972231SS25-0005
Solar/Wind Harmer
4.858
972181SS23-001
Solar/Wind Harmer
3.036
274752CRETE EC ;2U
Adder
2.502
274753CRETE EC ;3U
Adder
2.502
274676JOLIET 29;8U
Adder
15.126
943121AE2-341 GEN
Solar/Wind Harmer
7.661
943591AF1-030 GEN
Solar/Wind Harmer
5.107
274729ELWOOD EC;1P
Adder
8.379
274730ELWOOD EC;6P
Adder
8.378
274734ELWOOD EC;8P
Adder
8.378
274736ELWOOD EC;9P
Adder
8.378
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.017
276694AA1-018 GEN2
Solar/Wind Harmer
3.148
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.09
946671AF1-331 GEN
Solar/Wind Harmer
0.206
276805AD2-038 GEN
Solar/Wind Harmer
2.529
274855GSG-6 ;RU
Solar/Wind Harmer
1.82
274850MENDOTA H;RU
Solar/Wind Harmer
1.266
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.88
959091AF2-200 GEN
Solar/Wind Harmer
9.793
972236AH1-702 GEN2
Adder
1.067
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.307
270535AF1-215 GEN1
Solar/Wind Harmer
2.192
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.299
274760LEE CO EC;1U
Adder
4.464
274767LEE CO EC;8U
Adder
4.412
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.43
241955AC1-078 GEN
Solar/Wind Helper
2.426
960801AF2-371 GEN
Solar/Wind Helper
0.868
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.697
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.233
NYPJM->LTFIMP_NY
CLTF
0.91
LGEELTFEXP_LGEE->PJM
CLTF
0.797
WECLTFEXP_WEC->PJM
CLTF
1.857
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.07
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.864
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.148
MECLTFEXP_MEC->PJM
CLTF
6.967
SIGELTFEXP_SIGE->PJM
CLTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
5.375
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.182
TVALTFEXP_TVA->PJM
CLTF
2.392

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.53 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3392.06
MW Contribution:5.83
Bus #Bus NameTypeMW Contribution
970321AG2-212 GEN
Solar/Wind Harmer
10.692
274770LINCOLN ;1U
Adder
3.312
274771LINCOLN ;2U
Adder
3.312
965681AG1-436 GEN
Solar/Wind Harmer
6.489
965791AG1-447 GEN
Solar/Wind Harmer
3.32
972259AH1-714 GEN
Adder
9.875
274888KELLY CRK;1U
Solar/Wind Harmer
3.034
274887GEN-1.85
Solar/Wind Harmer
2.739
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.399
274803UNIV PARK;6U
Adder
2.99
274808UNIV PK N;4U
Adder
2.555
274847GR RIDGE ;BU
Solar/Wind Harmer
2.583
274674JOLIET 9 ;6U
Adder
7.86
971573AH1-285 GEN
Solar/Wind Harmer
4.366
24441505OLIV SLR
Solar/Wind Harmer
0.067
274696ROCKY RD ;4P
Adder
5.732
274695ROCKY RD ;2P
Adder
5.6
274693ROCKY RD ;1P
Adder
5.545
274697ROCKY RD ;3P
Adder
1.521
270526AF1-158 GEN
Solar/Wind Harmer
2.281
274683WAUKEGAN ;8U
Adder
10.559
274683WAUKEGAN ;8U
Adder
8.9
962691AG1-118 GEN
Solar/Wind Harmer
14.997
958481AF2-142 GEN
Solar/Wind Harmer
7.483
970921AG2-575 GEN
Solar/Wind Harmer
4.987
970921AG2-575 GEN
Solar/Wind Harmer
1.16
274861TOP CROP ;1U
Solar/Wind Harmer
3.021
274862TOP CROP ;2U
Solar/Wind Harmer
2.522
942991AE2-321 GEN
Solar/Wind Harmer
4.948
958491AF2-143 GEN
Solar/Wind Harmer
7.395
971333AH1-146 GEN
Solar/Wind Harmer
9.848
971335AH1-147 GEN
Solar/Wind Harmer
9.848
274879MINONK ;1U
Solar/Wind Harmer
3.316
971341AH1-150 GEN
Solar/Wind Harmer
9.792
971343AH1-151 GEN
Solar/Wind Harmer
9.792
276872AE1-163_GEN1
Solar/Wind Harmer
3.257
274856ECOGROVE ;U1
Solar/Wind Harmer
1.635
276611AD2-172 GEN
Solar/Wind Harmer
1.24
938861AE1-114 GEN
Solar/Wind Harmer
3.947
274764LEE CO EC;5U
Adder
4.474
274765LEE CO EC;6U
Adder
4.474
274762LEE CO EC;3U
Adder
4.464
274763LEE CO EC;4U
Adder
4.422
972267AH1-718 GEN
Adder
1.978
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.692
270224U2-072_GEN2
Solar/Wind Helper
1.533
270227U2-072_GEN3
Solar/Wind Helper
1.533
270228U2-072_GEN4
Solar/Wind Helper
1.533
270231U2-072_GEN5
Solar/Wind Helper
1.533
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.846
253378AE2-206_GEN
Solar/Wind Helper
1.303
276820AF1-078_GEN
Solar/Wind Helper
0.609
270518AE2-148 GEN
Solar/Wind Helper
10.796
24722005FLATG5
50/50
1.053
24721905FLATG4
50/50
19.313
970153AG2-106 GEN
Solar/Wind Harmer
33.973
970513AG2-328 GEN
Solar/Wind Harmer
10.692
970517AG2-330 GEN
Solar/Wind Harmer
9.698
970349AG2-230 GEN
Solar/Wind Harmer
8.593
274772LINCOLN ;3U
Adder
3.312
970707AG2-453 GEN
Solar/Wind Harmer
14.625
274724RIVER EC ;11
Adder
9.144
972228AH1-698 GEN2
Adder
1.906
276772AC2-154 GEN
Solar/Wind Harmer
1.433
276806AD2-047 C O1
Solar/Wind Harmer
5.497
970941AG2-585 GEN
Solar/Wind Harmer
6.423
274826FISK ;BP
Adder
5.622
276897AD1-100 C
Solar/Wind Harmer
14.896
939351AE1-166 GEN
Solar/Wind Harmer
3.044
274800UNIV PARK;3U
Adder
2.992
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.99
972231SS25-0005
Solar/Wind Harmer
4.857
972181SS23-001
Solar/Wind Harmer
3.036
274752CRETE EC ;2U
Adder
2.502
274753CRETE EC ;3U
Adder
2.502
274676JOLIET 29;8U
Adder
15.125
943121AE2-341 GEN
Solar/Wind Harmer
7.66
943591AF1-030 GEN
Solar/Wind Harmer
5.107
274729ELWOOD EC;1P
Adder
8.378
274730ELWOOD EC;6P
Adder
8.378
274734ELWOOD EC;8P
Adder
8.378
274736ELWOOD EC;9P
Adder
8.378
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.016
276694AA1-018 GEN2
Solar/Wind Harmer
3.148
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
1.09
946671AF1-331 GEN
Solar/Wind Harmer
0.206
276805AD2-038 GEN
Solar/Wind Harmer
2.529
274855GSG-6 ;RU
Solar/Wind Harmer
1.82
274850MENDOTA H;RU
Solar/Wind Harmer
1.265
276602WESTBROOK C
Solar/Wind Harmer
1.048
276863AD2-134 GEN
Solar/Wind Harmer
0.88
959091AF2-200 GEN
Solar/Wind Harmer
9.792
972236AH1-702 GEN2
Adder
1.067
276889AE2-281 GEN
Solar/Wind Harmer
0.931
24642205MAYFLWER
Adder
0.307
270535AF1-215 GEN1
Solar/Wind Harmer
2.191
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.299
274760LEE CO EC;1U
Adder
4.464
274767LEE CO EC;8U
Adder
4.411
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.43
241955AC1-078 GEN
Solar/Wind Helper
2.426
960801AF2-371 GEN
Solar/Wind Helper
0.868
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.697
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.233
24721605FLATG1
50/50
1.053
962771AG1-126 GEN
Solar/Wind Harmer
77.912
971347AH1-153 GEN
Solar/Wind Harmer
8.593
274775LINCOLN ;6U
Adder
3.312
274776LINCOLN ;7U
Adder
3.312
24721805FLATG3
50/50
1.053
24721705FLATG2
50/50
19.313
962761AG1-125 GEN
Solar/Wind Harmer
77.912
970149AG2-104 GEN
Solar/Wind Harmer
96.221
970155AG2-107 GEN
Solar/Wind Harmer
33.973
970245AG2-165 GEN
Solar/Wind Harmer
10.692
972207SS24-0001
Solar/Wind Harmer
11.776
274773LINCOLN ;4U
Adder
3.312
274774LINCOLN ;5U
Adder
3.312
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.246
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.328
274801UNIV PARK;4U
Adder
2.992
274812UNIV PK N;8U
Adder
2.566
274751CRETE EC ;1U
Adder
2.502
274754CRETE EC ;4U
Adder
2.502
274676JOLIET 29;8U
Adder
15.685
274871GR RIDGE ;2U
Solar/Wind Harmer
3.926
274674JOLIET 9 ;6U
Adder
7.86
274732ELWOOD EC;7P
Adder
8.378
274745AC1-111 GEN9
Adder
2.845
274682WAUKEGAN ;7U
Adder
9.016
274828WAUKEGAN ;BP
Adder
5.535
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.431
962781AG1-127 GEN
Solar/Wind Harmer
4.743
274872LEEDK;1U
Solar/Wind Harmer
4.087
939401AE1-172 GEN
Solar/Wind Harmer
6.874
970373AG2-245 GEN
Solar/Wind Harmer
10.357
276901AD2-066 C O1
Solar/Wind Harmer
1.731
276861AD2-134 GEN
Solar/Wind Harmer
0.88
971997AH1-543 GEN
Solar/Wind Harmer
7.737
957471AF2-041 GEN
Solar/Wind Harmer
14.688
959081AF2-199 GEN
Solar/Wind Harmer
4.896
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.578
972235AH1-702 GEN1
Adder
1.227
970819AG2-516 GEN
Solar/Wind Harmer
5.825
276876AE1-163_GEN2
Solar/Wind Harmer
3.257
971475AH1-234 GEN
Solar/Wind Harmer
10.845
270055AF2-134 C O1
Solar/Wind Harmer
1.461
274857EASY ROAD;U1
Solar/Wind Harmer
2.299
274761LEE CO EC;2U
Adder
4.464
274766LEE CO EC;7U
Adder
4.411
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.692
270223U2-072_GEN1
Solar/Wind Helper
1.533
270578AF1-285 GEN2
Solar/Wind Helper
1.039
270391AF1-285 GEN3
Solar/Wind Helper
1.039
270462AD2-086
Solar/Wind Helper
5.359
247522W1-056 GEN
Solar/Wind Helper
1.162
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.157
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
970569AG2-363 GEN
Solar/Wind Harmer
9.349
274777LINCOLN ;8U
Adder
3.312
960681AF2-359 GEN
Solar/Wind Harmer
1.961
972227AH1-698 GEN1
Adder
1.342
960591AF2-350 GEN
Solar/Wind Harmer
5.138
274827FISK ;RP
Adder
3.984
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.589
274807UNIV PK N;3U
Adder
2.583
274805UNIV PK N;1U
Adder
2.572
274811UNIV PK N;7U
Adder
2.566
274687WILL CNTY;4U
Adder
14.287
274687WILL CNTY;4U
Adder
14.287
274675JOLIET 29;7U
Adder
15.685
274675JOLIET 29;7U
Adder
15.125
970833AG2-524 GEN
Solar/Wind Harmer
4.458
970833AG2-524 GEN
Solar/Wind Harmer
2.074
274731ELWOOD EC;2P
Adder
8.378
274733ELWOOD EC;3P
Adder
8.378
274735ELWOOD EC;4P
Adder
8.378
274728ELWOOD EC;5P
Adder
8.378
274746AC1-111 G10
Adder
2.845
274744AC1-111 GEN8
Adder
2.845
971769AH1-391 GEN
Solar/Wind Harmer
5.036
971771AH1-392 GEN
Solar/Wind Harmer
4.461
971177AH1-047 GEN
Solar/Wind Harmer
2.898
971675AH1-338 GEN
Solar/Wind Harmer
8.872
971411AH1-196 GEN
Solar/Wind Harmer
7.39
276868AE1-113 GEN
Solar/Wind Harmer
4.974
276882AE2-255 GEN
Solar/Wind Harmer
1.658
971171AH1-044 GEN
Solar/Wind Harmer
9.792
274823ROCKFORD ;21
Adder
9.509
274863CRW1-WTG
Solar/Wind Harmer
2.707
274864CRW2-WTG
Solar/Wind Harmer
2.707
276612AE2-035 GEN
Solar/Wind Harmer
1.24
270536AF1-215 GEN2
Solar/Wind Harmer
2.191
971681AH1-341 GEN
Solar/Wind Harmer
7.225
926823AC1-168 GEN
Solar/Wind Harmer
2.065
270284AF1-227 GEN1
Solar/Wind Helper
6.375
270286AF1-227 GEN2
Solar/Wind Helper
2.338
270287AF1-227 GEN3
Solar/Wind Helper
2.338
270317AD1-130_GEN
Solar/Wind Helper
5.936
253383AE2-342_GEN
Solar/Wind Helper
1.121
241973AD2-163_GEN1
Solar/Wind Helper
2.43
270520AE2-214 GEN
Solar/Wind Helper
6.387
270054AF2-122 C O1
Solar/Wind Helper
1.465
945631AF1-228 GEN
Solar/Wind Helper
1.901
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.137
945641AF1-229 GEN
Solar/Wind Helper
1.105
270499AE1-146 GEN
Solar/Wind Helper
1.893
270340AC2-060 GEN
Solar/Wind Helper
0.99
NYPJM->LTFIMP_NY
CLTF
0.91
LGEELTFEXP_LGEE->PJM
CLTF
0.797
WECLTFEXP_WEC->PJM
CLTF
1.857
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.066
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.859
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.148
MECLTFEXP_MEC->PJM
CLTF
6.966
SIGELTFEXP_SIGE->PJM
CLTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
5.374
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.182
TVALTFEXP_TVA->PJM
CLTF
2.391

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.5 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3391.13
MW Contribution:5.82
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.053
24721705FLATG2
50/50
19.311
962761AG1-125 GEN
Solar/Wind Harmer
77.904
970149AG2-104 GEN
Solar/Wind Harmer
96.211
970155AG2-107 GEN
Solar/Wind Harmer
33.97
970245AG2-165 GEN
Solar/Wind Harmer
10.689
972207SS24-0001
Solar/Wind Harmer
11.773
274773LINCOLN ;4U
Adder
3.311
274774LINCOLN ;5U
Adder
3.311
276164X3-005 C
Solar/Wind Harmer
0.363
274723RIVER EC ;12
Adder
9.243
276776AD2-060 GEN
Solar/Wind Harmer
0.217
941551AE2-152 GEN
Solar/Wind Harmer
2.327
274801UNIV PARK;4U
Adder
2.991
274812UNIV PK N;8U
Adder
2.566
274751CRETE EC ;1U
Adder
2.501
274754CRETE EC ;4U
Adder
2.501
274676JOLIET 29;8U
Adder
15.68
274871GR RIDGE ;2U
Solar/Wind Harmer
3.925
274674JOLIET 9 ;6U
Adder
7.858
274732ELWOOD EC;7P
Adder
8.375
274745AC1-111 GEN9
Adder
2.844
274682WAUKEGAN ;7U
Adder
9.013
274828WAUKEGAN ;BP
Adder
5.533
276691AA1-018 GEN1
Solar/Wind Harmer
0.232
960751AF2-366 GEN
Solar/Wind Harmer
1.43
962781AG1-127 GEN
Solar/Wind Harmer
4.741
274872LEEDK;1U
Solar/Wind Harmer
4.086
939401AE1-172 GEN
Solar/Wind Harmer
6.872
970373AG2-245 GEN
Solar/Wind Harmer
10.354
276901AD2-066 C O1
Solar/Wind Harmer
1.731
276861AD2-134 GEN
Solar/Wind Harmer
0.88
971997AH1-543 GEN
Solar/Wind Harmer
7.735
957471AF2-041 GEN
Solar/Wind Harmer
14.684
959081AF2-199 GEN
Solar/Wind Harmer
4.895
971067AG2-660 GEN
Solar/Wind Harmer
1.138
274822ROCKFORD ;11
Adder
9.575
972235AH1-702 GEN1
Adder
1.227
970819AG2-516 GEN
Solar/Wind Harmer
5.823
276876AE1-163_GEN2
Solar/Wind Harmer
3.256
971475AH1-234 GEN
Solar/Wind Harmer
10.842
270055AF2-134 C O1
Solar/Wind Harmer
1.46
274857EASY ROAD;U1
Solar/Wind Harmer
2.299
274761LEE CO EC;2U
Adder
4.462
274766LEE CO EC;7U
Adder
4.41
24639705ELKHART HY
Adder
0.07
270349AD2-093_GEN
Solar/Wind Helper
4.693
270223U2-072_GEN1
Solar/Wind Helper
1.533
270578AF1-285 GEN2
Solar/Wind Helper
1.039
270391AF1-285 GEN3
Solar/Wind Helper
1.039
270462AD2-086
Solar/Wind Helper
5.36
247522W1-056 GEN
Solar/Wind Helper
1.162
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.157
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.701
970569AG2-363 GEN
Solar/Wind Harmer
9.346
24721605FLATG1
50/50
1.053
962771AG1-126 GEN
Solar/Wind Harmer
77.904
971347AH1-153 GEN
Solar/Wind Harmer
8.59
274775LINCOLN ;6U
Adder
3.311
274776LINCOLN ;7U
Adder
3.311
274777LINCOLN ;8U
Adder
3.311
960681AF2-359 GEN
Solar/Wind Harmer
1.96
972227AH1-698 GEN1
Adder
1.342
960591AF2-350 GEN
Solar/Wind Harmer
5.137
274827FISK ;RP
Adder
3.983
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.588
274807UNIV PK N;3U
Adder
2.582
274805UNIV PK N;1U
Adder
2.571
274811UNIV PK N;7U
Adder
2.566
274687WILL CNTY;4U
Adder
14.282
274687WILL CNTY;4U
Adder
14.282
274675JOLIET 29;7U
Adder
15.681
274675JOLIET 29;7U
Adder
15.121
970833AG2-524 GEN
Solar/Wind Harmer
4.457
970833AG2-524 GEN
Solar/Wind Harmer
2.073
274731ELWOOD EC;2P
Adder
8.375
274733ELWOOD EC;3P
Adder
8.375
274735ELWOOD EC;4P
Adder
8.375
274728ELWOOD EC;5P
Adder
8.375
274746AC1-111 G10
Adder
2.844
274744AC1-111 GEN8
Adder
2.844
971769AH1-391 GEN
Solar/Wind Harmer
5.034
971771AH1-392 GEN
Solar/Wind Harmer
4.46
971177AH1-047 GEN
Solar/Wind Harmer
2.897
971675AH1-338 GEN
Solar/Wind Harmer
8.869
971411AH1-196 GEN
Solar/Wind Harmer
7.388
276868AE1-113 GEN
Solar/Wind Harmer
4.972
276882AE2-255 GEN
Solar/Wind Harmer
1.658
971171AH1-044 GEN
Solar/Wind Harmer
9.789
274823ROCKFORD ;21
Adder
9.506
274863CRW1-WTG
Solar/Wind Harmer
2.706
274864CRW2-WTG
Solar/Wind Harmer
2.706
276612AE2-035 GEN
Solar/Wind Harmer
1.24
270536AF1-215 GEN2
Solar/Wind Harmer
2.191
971681AH1-341 GEN
Solar/Wind Harmer
7.223
926823AC1-168 GEN
Solar/Wind Harmer
2.065
270284AF1-227 GEN1
Solar/Wind Helper
6.376
270286AF1-227 GEN2
Solar/Wind Helper
2.338
270287AF1-227 GEN3
Solar/Wind Helper
2.338
270317AD1-130_GEN
Solar/Wind Helper
5.937
253383AE2-342_GEN
Solar/Wind Helper
1.121
241973AD2-163_GEN1
Solar/Wind Helper
2.431
270520AE2-214 GEN
Solar/Wind Helper
6.39
270054AF2-122 C O1
Solar/Wind Helper
1.464
945631AF1-228 GEN
Solar/Wind Helper
1.901
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.138
945641AF1-229 GEN
Solar/Wind Helper
1.105
270499AE1-146 GEN
Solar/Wind Helper
1.894
270340AC2-060 GEN
Solar/Wind Helper
0.99
970321AG2-212 GEN
Solar/Wind Harmer
10.689
274770LINCOLN ;1U
Adder
3.311
274771LINCOLN ;2U
Adder
3.311
965681AG1-436 GEN
Solar/Wind Harmer
6.486
965791AG1-447 GEN
Solar/Wind Harmer
3.319
972259AH1-714 GEN
Adder
9.872
274888KELLY CRK;1U
Solar/Wind Harmer
3.033
274887GEN-1.85
Solar/Wind Harmer
2.738
276843GEN-1.7
Solar/Wind Harmer
0.295
958011AF2-095 GEN
Solar/Wind Harmer
7.397
274803UNIV PARK;6U
Adder
2.989
274808UNIV PK N;4U
Adder
2.554
274847GR RIDGE ;BU
Solar/Wind Harmer
2.582
274674JOLIET 9 ;6U
Adder
7.858
971573AH1-285 GEN
Solar/Wind Harmer
4.365
24441505OLIV SLR
Solar/Wind Harmer
0.067
274695ROCKY RD ;2P
Adder
5.598
274693ROCKY RD ;1P
Adder
5.543
274697ROCKY RD ;3P
Adder
1.521
274696ROCKY RD ;4P
Adder
5.73
270526AF1-158 GEN
Solar/Wind Harmer
2.28
274683WAUKEGAN ;8U
Adder
10.555
274683WAUKEGAN ;8U
Adder
8.898
962691AG1-118 GEN
Solar/Wind Harmer
14.993
958481AF2-142 GEN
Solar/Wind Harmer
7.48
970921AG2-575 GEN
Solar/Wind Harmer
4.986
970921AG2-575 GEN
Solar/Wind Harmer
1.159
274861TOP CROP ;1U
Solar/Wind Harmer
3.02
274862TOP CROP ;2U
Solar/Wind Harmer
2.522
942991AE2-321 GEN
Solar/Wind Harmer
4.946
958491AF2-143 GEN
Solar/Wind Harmer
7.393
971333AH1-146 GEN
Solar/Wind Harmer
9.845
971335AH1-147 GEN
Solar/Wind Harmer
9.845
274879MINONK ;1U
Solar/Wind Harmer
3.315
971341AH1-150 GEN
Solar/Wind Harmer
9.789
971343AH1-151 GEN
Solar/Wind Harmer
9.789
276872AE1-163_GEN1
Solar/Wind Harmer
3.256
274856ECOGROVE ;U1
Solar/Wind Harmer
1.634
276611AD2-172 GEN
Solar/Wind Harmer
1.24
938861AE1-114 GEN
Solar/Wind Harmer
3.946
274764LEE CO EC;5U
Adder
4.473
274765LEE CO EC;6U
Adder
4.473
274762LEE CO EC;3U
Adder
4.462
274763LEE CO EC;4U
Adder
4.42
972267AH1-718 GEN
Adder
1.978
247620Y3-023
Adder
0.201
270471AD2-092_GEN
Solar/Wind Helper
4.693
270224U2-072_GEN2
Solar/Wind Helper
1.533
270227U2-072_GEN3
Solar/Wind Helper
1.533
270228U2-072_GEN4
Solar/Wind Helper
1.533
270231U2-072_GEN5
Solar/Wind Helper
1.533
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.847
253378AE2-206_GEN
Solar/Wind Helper
1.303
276820AF1-078_GEN
Solar/Wind Helper
0.609
270518AE2-148 GEN
Solar/Wind Helper
10.798
24722005FLATG5
50/50
1.053
24721905FLATG4
50/50
19.311
970153AG2-106 GEN
Solar/Wind Harmer
33.97
970513AG2-328 GEN
Solar/Wind Harmer
10.689
970517AG2-330 GEN
Solar/Wind Harmer
9.695
970349AG2-230 GEN
Solar/Wind Harmer
8.59
274772LINCOLN ;3U
Adder
3.311
970707AG2-453 GEN
Solar/Wind Harmer
14.62
274724RIVER EC ;11
Adder
9.141
972228AH1-698 GEN2
Adder
1.905
276772AC2-154 GEN
Solar/Wind Harmer
1.432
276806AD2-047 C O1
Solar/Wind Harmer
5.495
970941AG2-585 GEN
Solar/Wind Harmer
6.421
274826FISK ;BP
Adder
5.62
276897AD1-100 C
Solar/Wind Harmer
14.891
939351AE1-166 GEN
Solar/Wind Harmer
3.043
274800UNIV PARK;3U
Adder
2.991
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.989
972231SS25-0005
Solar/Wind Harmer
4.856
972181SS23-001
Solar/Wind Harmer
3.035
274752CRETE EC ;2U
Adder
2.501
274753CRETE EC ;3U
Adder
2.501
274676JOLIET 29;8U
Adder
15.12
943121AE2-341 GEN
Solar/Wind Harmer
7.658
943591AF1-030 GEN
Solar/Wind Harmer
5.105
274729ELWOOD EC;1P
Adder
8.375
274730ELWOOD EC;6P
Adder
8.375
274734ELWOOD EC;8P
Adder
8.375
274736ELWOOD EC;9P
Adder
8.375
276893AG1-478 C
Solar/Wind Harmer
0.213
274682WAUKEGAN ;7U
Adder
9.013
276694AA1-018 GEN2
Solar/Wind Harmer
3.147
274872LEEDK;1U
Solar/Wind Harmer
0.127
276805AD2-038 GEN
Solar/Wind Harmer
2.528
276799AD1-013 GEN
Solar/Wind Harmer
1.09
946671AF1-331 GEN
Solar/Wind Harmer
0.206
274855GSG-6 ;RU
Solar/Wind Harmer
1.819
274850MENDOTA H;RU
Solar/Wind Harmer
1.265
276602WESTBROOK C
Solar/Wind Harmer
1.047
276863AD2-134 GEN
Solar/Wind Harmer
0.88
959091AF2-200 GEN
Solar/Wind Harmer
9.789
972236AH1-702 GEN2
Adder
1.067
276889AE2-281 GEN
Solar/Wind Harmer
0.93
24642205MAYFLWER
Adder
0.307
270535AF1-215 GEN1
Solar/Wind Harmer
2.191
247643Z2-116 C
Solar/Wind Harmer
0.033
274858EASY ROAD;U2
Solar/Wind Harmer
2.299
274760LEE CO EC;1U
Adder
4.462
274767LEE CO EC;8U
Adder
4.41
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.431
241955AC1-078 GEN
Solar/Wind Helper
2.426
960801AF2-371 GEN
Solar/Wind Helper
0.868
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.697
270541AE2-072 C
Solar/Wind Helper
1.119
253415AE1-040 GEN
Solar/Wind Helper
0.466
970571AG2-364 GEN
Solar/Wind Harmer
6.231
NYPJM->LTFIMP_NY
CLTF
0.909
LGEELTFEXP_LGEE->PJM
CLTF
0.796
WECLTFEXP_WEC->PJM
CLTF
1.857
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.052
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.839
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.144
MECLTFEXP_MEC->PJM
CLTF
6.964
SIGELTFEXP_SIGE->PJM
CLTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
5.373
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.182
TVALTFEXP_TVA->PJM
CLTF
2.391

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#711_6224_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#711_6224_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:105.12 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3255.61
MW Contribution:4.13
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.058
24721705FLATG2
50/50
19.393
24344105CKG2
50/50
4.731
243186AF1-051 GEN
50/50
3.125
24318705GVG2
50/50
2.909
962761AG1-125 GEN
Solar/Wind Harmer
65.959
970149AG2-104 GEN
Solar/Wind Harmer
71.237
970155AG2-107 GEN
Solar/Wind Harmer
42.119
970245AG2-165 GEN
Solar/Wind Harmer
1.836
274773LINCOLN ;4U
Adder
4.58
274774LINCOLN ;5U
Adder
4.58
276164X3-005 C
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
9.397
276776AD2-060 GEN
Solar/Wind Harmer
0.38
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.041
274812UNIV PK N;8U
Adder
2.608
274751CRETE EC ;1U
Adder
4.287
274754CRETE EC ;4U
Adder
4.287
274676JOLIET 29;8U
Adder
15.941
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.988
274732ELWOOD EC;7P
Adder
8.515
274745AC1-111 GEN9
Adder
2.891
274682WAUKEGAN ;7U
Adder
9.164
274828WAUKEGAN ;BP
Adder
5.626
276691AA1-018 GEN1
Solar/Wind Harmer
0.429
962781AG1-127 GEN
Solar/Wind Harmer
3.366
274872LEEDK;1U
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
7.35
939401AE1-172 GEN
Solar/Wind Harmer
2.617
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276861AD2-134 GEN
Solar/Wind Harmer
0.063
971997AH1-543 GEN
Solar/Wind Harmer
1.83
957471AF2-041 GEN
Solar/Wind Harmer
10.419
959081AF2-199 GEN
Solar/Wind Harmer
3.473
971067AG2-660 GEN
Solar/Wind Harmer
1.158
274822ROCKFORD ;11
Adder
9.739
972235AH1-702 GEN1
Adder
1.248
970819AG2-516 GEN
Solar/Wind Harmer
4.132
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971475AH1-234 GEN
Solar/Wind Harmer
1.667
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.539
274766LEE CO EC;7U
Adder
4.486
970569AG2-363 GEN
Solar/Wind Harmer
10.206
270505AE1-170 C O1
Solar/Wind Harmer
3.548
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.356
274877BISHOP HL;1U
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
5.901
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.718
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.081
24639705ELKHART HY
Adder
0.072
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.535
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.538
270349AD2-093_GEN
Solar/Wind Helper
4.665
270223U2-072_GEN1
Solar/Wind Helper
1.522
270578AF1-285 GEN2
Solar/Wind Helper
1.031
270391AF1-285 GEN3
Solar/Wind Helper
1.031
270462AD2-086
Solar/Wind Helper
5.319
247522W1-056 GEN
Solar/Wind Helper
1.149
253343AC1-166 GEN
Solar/Wind Helper
0.826
253325AC1-069 GEN
Solar/Wind Helper
0.856
960841AF2-375 GEN
Solar/Wind Helper
1.143
958961AF2-187 GEN
Solar/Wind Helper
1.121
270263AC1-001 GEN
Solar/Wind Helper
0.539
241840AF1-064_GEN
Solar/Wind Helper
0.473
241807AE2-176_GEN
Solar/Wind Helper
0.695
24722005FLATG5
50/50
1.058
24721905FLATG4
50/50
19.393
24318705GVG2
50/50
2.909
970153AG2-106 GEN
Solar/Wind Harmer
42.119
970513AG2-328 GEN
Solar/Wind Harmer
1.836
970517AG2-330 GEN
Solar/Wind Harmer
11.017
970349AG2-230 GEN
Solar/Wind Harmer
6.085
274772LINCOLN ;3U
Adder
4.58
970707AG2-453 GEN
Solar/Wind Harmer
12.094
274724RIVER EC ;11
Adder
9.292
972228AH1-698 GEN2
Adder
1.937
276806AD2-047 C O1
Solar/Wind Harmer
2.065
970941AG2-585 GEN
Solar/Wind Harmer
4.554
274826FISK ;BP
Adder
5.714
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
3.041
972038AH1-567 GEN2
Adder
0.19
274802UNIV PARK;5U
Adder
3.039
274752CRETE EC ;2U
Adder
4.287
274753CRETE EC ;3U
Adder
4.287
274676JOLIET 29;8U
Adder
15.371
943121AE2-341 GEN
Solar/Wind Harmer
6.071
943591AF1-030 GEN
Solar/Wind Harmer
4.037
274729ELWOOD EC;1P
Adder
8.515
274730ELWOOD EC;6P
Adder
8.515
274734ELWOOD EC;8P
Adder
8.515
274736ELWOOD EC;9P
Adder
8.515
276893AG1-478 C
Solar/Wind Harmer
0.143
274682WAUKEGAN ;7U
Adder
9.164
276694AA1-018 GEN2
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.129
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.063
959091AF2-200 GEN
Solar/Wind Harmer
6.946
972236AH1-702 GEN2
Adder
1.085
276889AE2-281 GEN
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.539
274767LEE CO EC;8U
Adder
4.486
970571AG2-364 GEN
Solar/Wind Harmer
6.804
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.543
274878BISHOP HL;2U
Solar/Wind Harmer
0.111
945111AF1-176 GEN
Solar/Wind Harmer
2.681
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
965931AG1-462 GEN
Solar/Wind Harmer
8.314
942111AE2-223 GEN
Solar/Wind Harmer
1.053
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.533
959611AF2-252 GEN
Solar/Wind Harmer
1.059
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
2.016
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.112
247604X1-042
Adder
0.185
944531AF1-118 GEN
Solar/Wind Harmer
13.488
942871AE2-306 GEN
Solar/Wind Helper
0.773
270485AE1-090_GEN
Solar/Wind Helper
0.463
241974AD2-163_GEN2
Solar/Wind Helper
2.393
241955AC1-078 GEN
Solar/Wind Helper
2.378
960801AF2-371 GEN
Solar/Wind Helper
0.85
964871AG1-351 GEN
Solar/Wind Helper
0.587
253338AC1-165 GEN
Solar/Wind Helper
0.826
253333AC1-068 GEN
Solar/Wind Helper
0.856
270273AD2-016 GEN
Solar/Wind Helper
1.657
270541AE2-072 C
Solar/Wind Helper
1.102
253415AE1-040 GEN
Solar/Wind Helper
0.453
24721605FLATG1
50/50
1.058
971599AH1-298 GEN
50/50
4.831
962771AG1-126 GEN
Solar/Wind Harmer
65.959
971347AH1-153 GEN
Solar/Wind Harmer
6.085
274775LINCOLN ;6U
Adder
4.58
274776LINCOLN ;7U
Adder
4.58
274777LINCOLN ;8U
Adder
4.58
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.364
960591AF2-350 GEN
Solar/Wind Harmer
3.643
274827FISK ;RP
Adder
4.049
972037AH1-567 GEN1
Adder
0.095
274814UNIV PK N;0U
Adder
2.631
274807UNIV PK N;3U
Adder
2.626
274805UNIV PK N;1U
Adder
2.614
274811UNIV PK N;7U
Adder
2.608
274687WILL CNTY;4U
Adder
14.52
274687WILL CNTY;4U
Adder
14.52
274675JOLIET 29;7U
Adder
15.941
274675JOLIET 29;7U
Adder
15.372
970833AG2-524 GEN
Solar/Wind Harmer
3.983
970833AG2-524 GEN
Solar/Wind Harmer
2.655
274731ELWOOD EC;2P
Adder
8.515
274733ELWOOD EC;3P
Adder
8.515
274735ELWOOD EC;4P
Adder
8.515
274728ELWOOD EC;5P
Adder
8.515
274746AC1-111 G10
Adder
2.891
274744AC1-111 GEN8
Adder
2.891
971769AH1-391 GEN
Solar/Wind Harmer
3.99
971771AH1-392 GEN
Solar/Wind Harmer
3.518
971177AH1-047 GEN
Solar/Wind Harmer
2.163
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971411AH1-196 GEN
Solar/Wind Harmer
5.242
276868AE1-113 GEN
Solar/Wind Harmer
0.7
276882AE2-255 GEN
Solar/Wind Harmer
0.408
971171AH1-044 GEN
Solar/Wind Harmer
6.946
274823ROCKFORD ;21
Adder
9.668
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971681AH1-341 GEN
Solar/Wind Harmer
5.502
926823AC1-168 GEN
Solar/Wind Harmer
0.579
970169AG2-114 GEN
Solar/Wind Harmer
3.38
961011AF2-392 GEN
Solar/Wind Harmer
1.983
971619AH1-309 GEN
Solar/Wind Harmer
1.52
957751AF2-069 GEN
Solar/Wind Harmer
0.11
958391AF2-133 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.836
971611AH1-305 GEN
Solar/Wind Harmer
1.944
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.401
941731AE2-173 GEN
Solar/Wind Harmer
2.699
270071AF1-092 GEN
Solar/Wind Harmer
6.128
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Helper
6.336
270286AF1-227 GEN2
Solar/Wind Helper
2.323
270287AF1-227 GEN3
Solar/Wind Helper
2.323
270317AD1-130_GEN
Solar/Wind Helper
5.891
253383AE2-342_GEN
Solar/Wind Helper
1.103
241973AD2-163_GEN1
Solar/Wind Helper
2.393
270520AE2-214 GEN
Solar/Wind Helper
6.251
270054AF2-122 C O1
Solar/Wind Helper
1.45
945631AF1-228 GEN
Solar/Wind Helper
1.86
966831AG1-554 GEN
Solar/Wind Helper
0.856
241972AD1-140 GEN
Solar/Wind Helper
3.072
945641AF1-229 GEN
Solar/Wind Helper
1.093
270499AE1-146 GEN
Solar/Wind Helper
1.872
270340AC2-060 GEN
Solar/Wind Helper
0.963
243186AF1-051 GEN
50/50
3.125
970321AG2-212 GEN
Solar/Wind Harmer
1.836
274770LINCOLN ;1U
Adder
4.58
274771LINCOLN ;2U
Adder
4.58
965681AG1-436 GEN
Solar/Wind Harmer
4.601
965791AG1-447 GEN
Solar/Wind Harmer
3.374
972259AH1-714 GEN
Adder
10.035
274888KELLY CRK;1U
Solar/Wind Harmer
0.214
274887GEN-1.85
Solar/Wind Harmer
0.096
276843GEN-1.7
Solar/Wind Harmer
0.118
958011AF2-095 GEN
Solar/Wind Harmer
5.246
274803UNIV PARK;6U
Adder
3.039
274808UNIV PK N;4U
Adder
2.597
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.988
971573AH1-285 GEN
Solar/Wind Harmer
0.671
24441505OLIV SLR
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.826
274695ROCKY RD ;2P
Adder
5.692
274693ROCKY RD ;1P
Adder
5.636
274697ROCKY RD ;3P
Adder
1.546
270526AF1-158 GEN
Solar/Wind Harmer
0.004
274683WAUKEGAN ;8U
Adder
10.733
274683WAUKEGAN ;8U
Adder
9.047
962691AG1-118 GEN
Solar/Wind Harmer
10.636
958481AF2-142 GEN
Solar/Wind Harmer
5.307
970921AG2-575 GEN
Solar/Wind Harmer
3.537
970921AG2-575 GEN
Solar/Wind Harmer
1.179
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.478
942991AE2-321 GEN
Solar/Wind Harmer
3.919
958491AF2-143 GEN
Solar/Wind Harmer
5.246
971333AH1-146 GEN
Solar/Wind Harmer
6.985
971335AH1-147 GEN
Solar/Wind Harmer
6.985
274879MINONK ;1U
Solar/Wind Harmer
0.147
971341AH1-150 GEN
Solar/Wind Harmer
6.946
971343AH1-151 GEN
Solar/Wind Harmer
6.946
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.081
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.936
274764LEE CO EC;5U
Adder
4.55
274765LEE CO EC;6U
Adder
4.55
274762LEE CO EC;3U
Adder
4.539
274763LEE CO EC;4U
Adder
4.497
276603SUBLETTE C
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.012
957891AF2-083 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.12
276708O09 GEN2
Solar/Wind Harmer
0.12
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.131
276646AC1-214 GEN2
Solar/Wind Harmer
0.131
276782AC1-033 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.595
961051AF2-396 GEN
Solar/Wind Harmer
4.397
960611AF2-352 GEN
Solar/Wind Harmer
1.059
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
247620Y3-023
Adder
0.206
270471AD2-092_GEN
Solar/Wind Helper
4.665
270224U2-072_GEN2
Solar/Wind Helper
1.522
270227U2-072_GEN3
Solar/Wind Helper
1.522
270228U2-072_GEN4
Solar/Wind Helper
1.522
270231U2-072_GEN5
Solar/Wind Helper
1.522
946101AF1-275 GEN
Solar/Wind Helper
0.783
241960AC2-195 GEN
Solar/Wind Helper
1.825
253378AE2-206_GEN
Solar/Wind Helper
1.285
276820AF1-078_GEN
Solar/Wind Helper
0.6
270518AE2-148 GEN
Solar/Wind Helper
10.557
NYPJM->LTFIMP_NY
CLTF
0.939
LGEELTFEXP_LGEE->PJM
CLTF
0.854
WECLTFEXP_WEC->PJM
CLTF
1.888
CPLELTFEXP_CPLE->PJM
CLTF
1.524
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.966
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.979
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.373
MECLTFEXP_MEC->PJM
CLTF
7.095
SIGELTFEXP_SIGE->PJM
CLTF
0.116
LAGNLTFEXP_LAGN->PJM
CLTF
5.489
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.243
TVALTFEXP_TVA->PJM
CLTF
2.447

Details for 05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-3_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.65 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3241.06
MW Contribution:4.07
Bus #Bus NameTypeMW Contribution
24721805FLATG3
50/50
1.054
24721705FLATG2
50/50
19.316
24344105CKG2
50/50
4.668
243186AF1-051 GEN
50/50
3.112
24318705GVG2
50/50
2.897
962761AG1-125 GEN
Solar/Wind Harmer
65.719
970149AG2-104 GEN
Solar/Wind Harmer
70.979
970155AG2-107 GEN
Solar/Wind Harmer
41.966
970245AG2-165 GEN
Solar/Wind Harmer
1.811
274773LINCOLN ;4U
Adder
4.511
274774LINCOLN ;5U
Adder
4.511
276164X3-005 C
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
9.252
276776AD2-060 GEN
Solar/Wind Harmer
0.375
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.994
274812UNIV PK N;8U
Adder
2.568
274751CRETE EC ;1U
Adder
4.22
274754CRETE EC ;4U
Adder
4.22
274676JOLIET 29;8U
Adder
15.695
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274674JOLIET 9 ;6U
Adder
7.865
274732ELWOOD EC;7P
Adder
8.383
274745AC1-111 GEN9
Adder
2.846
274682WAUKEGAN ;7U
Adder
9.022
274828WAUKEGAN ;BP
Adder
5.538
276691AA1-018 GEN1
Solar/Wind Harmer
0.422
962781AG1-127 GEN
Solar/Wind Harmer
3.313
274872LEEDK;1U
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
2.576
970373AG2-245 GEN
Solar/Wind Harmer
7.231
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276861AD2-134 GEN
Solar/Wind Harmer
0.062
971997AH1-543 GEN
Solar/Wind Harmer
1.801
957471AF2-041 GEN
Solar/Wind Harmer
10.254
959081AF2-199 GEN
Solar/Wind Harmer
3.418
971067AG2-660 GEN
Solar/Wind Harmer
1.139
274822ROCKFORD ;11
Adder
9.585
972235AH1-702 GEN1
Adder
1.228
970819AG2-516 GEN
Solar/Wind Harmer
4.066
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971475AH1-234 GEN
Solar/Wind Harmer
1.64
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.467
274766LEE CO EC;7U
Adder
4.414
970569AG2-363 GEN
Solar/Wind Harmer
10.041
270505AE1-170 C O1
Solar/Wind Harmer
3.488
276158O29GEN2
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.282
274877BISHOP HL;1U
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
5.799
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.689
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.011
24639705ELKHART HY
Adder
0.07
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.458
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.493
270349AD2-093_GEN
Solar/Wind Helper
4.69
270223U2-072_GEN1
Solar/Wind Helper
1.532
270578AF1-285 GEN2
Solar/Wind Helper
1.038
270391AF1-285 GEN3
Solar/Wind Helper
1.038
270462AD2-086
Solar/Wind Helper
5.357
247522W1-056 GEN
Solar/Wind Helper
1.161
253343AC1-166 GEN
Solar/Wind Helper
0.845
253325AC1-069 GEN
Solar/Wind Helper
0.876
960841AF2-375 GEN
Solar/Wind Helper
1.156
270263AC1-001 GEN
Solar/Wind Helper
0.553
958961AF2-187 GEN
Solar/Wind Helper
1.122
241840AF1-064_GEN
Solar/Wind Helper
0.48
241807AE2-176_GEN
Solar/Wind Helper
0.7
24722005FLATG5
50/50
1.054
24721905FLATG4
50/50
19.316
24318705GVG2
50/50
2.897
970153AG2-106 GEN
Solar/Wind Harmer
41.966
970513AG2-328 GEN
Solar/Wind Harmer
1.811
970517AG2-330 GEN
Solar/Wind Harmer
10.868
970349AG2-230 GEN
Solar/Wind Harmer
5.999
274772LINCOLN ;3U
Adder
4.511
970707AG2-453 GEN
Solar/Wind Harmer
11.912
274724RIVER EC ;11
Adder
9.15
972228AH1-698 GEN2
Adder
1.907
276806AD2-047 C O1
Solar/Wind Harmer
2.033
970941AG2-585 GEN
Solar/Wind Harmer
4.484
274826FISK ;BP
Adder
5.626
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
2.994
972038AH1-567 GEN2
Adder
0.187
274802UNIV PARK;5U
Adder
2.992
274752CRETE EC ;2U
Adder
4.22
274753CRETE EC ;3U
Adder
4.22
274676JOLIET 29;8U
Adder
15.135
943121AE2-341 GEN
Solar/Wind Harmer
5.978
943591AF1-030 GEN
Solar/Wind Harmer
3.975
274729ELWOOD EC;1P
Adder
8.383
274730ELWOOD EC;6P
Adder
8.383
274734ELWOOD EC;8P
Adder
8.383
274736ELWOOD EC;9P
Adder
8.383
276893AG1-478 C
Solar/Wind Harmer
0.141
274682WAUKEGAN ;7U
Adder
9.022
276694AA1-018 GEN2
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.127
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.367
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.126
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.062
959091AF2-200 GEN
Solar/Wind Harmer
6.836
972236AH1-702 GEN2
Adder
1.068
276889AE2-281 GEN
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.308
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.467
274767LEE CO EC;8U
Adder
4.414
970571AG2-364 GEN
Solar/Wind Harmer
6.694
276157O29GEN1
Solar/Wind Harmer
0.534
964401AG1-302 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
0.11
945111AF1-176 GEN
Solar/Wind Harmer
2.634
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
965931AG1-462 GEN
Solar/Wind Harmer
8.178
942111AE2-223 GEN
Solar/Wind Harmer
1.035
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.369
959611AF2-252 GEN
Solar/Wind Harmer
1.041
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
1.976
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.055
247604X1-042
Adder
0.181
942871AE2-306 GEN
Solar/Wind Helper
0.779
270485AE1-090_GEN
Solar/Wind Helper
0.466
241974AD2-163_GEN2
Solar/Wind Helper
2.428
241955AC1-078 GEN
Solar/Wind Helper
2.425
960801AF2-371 GEN
Solar/Wind Helper
0.869
964871AG1-351 GEN
Solar/Wind Helper
0.6
253338AC1-165 GEN
Solar/Wind Helper
0.845
253333AC1-068 GEN
Solar/Wind Helper
0.876
270273AD2-016 GEN
Solar/Wind Helper
1.698
270541AE2-072 C
Solar/Wind Helper
1.118
253415AE1-040 GEN
Solar/Wind Helper
0.466
24721605FLATG1
50/50
1.054
971599AH1-298 GEN
50/50
4.754
962771AG1-126 GEN
Solar/Wind Harmer
65.719
971347AH1-153 GEN
Solar/Wind Harmer
5.999
274775LINCOLN ;6U
Adder
4.511
274776LINCOLN ;7U
Adder
4.511
274777LINCOLN ;8U
Adder
4.511
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.343
960591AF2-350 GEN
Solar/Wind Harmer
3.587
274827FISK ;RP
Adder
3.987
972037AH1-567 GEN1
Adder
0.094
274814UNIV PK N;0U
Adder
2.591
274807UNIV PK N;3U
Adder
2.585
274805UNIV PK N;1U
Adder
2.574
274811UNIV PK N;7U
Adder
2.568
274675JOLIET 29;7U
Adder
15.696
274675JOLIET 29;7U
Adder
15.135
274687WILL CNTY;4U
Adder
14.296
274687WILL CNTY;4U
Adder
14.296
970833AG2-524 GEN
Solar/Wind Harmer
3.922
970833AG2-524 GEN
Solar/Wind Harmer
2.615
274731ELWOOD EC;2P
Adder
8.383
274733ELWOOD EC;3P
Adder
8.383
274735ELWOOD EC;4P
Adder
8.383
274728ELWOOD EC;5P
Adder
8.383
274746AC1-111 G10
Adder
2.846
274744AC1-111 GEN8
Adder
2.846
971769AH1-391 GEN
Solar/Wind Harmer
3.926
971771AH1-392 GEN
Solar/Wind Harmer
3.461
971177AH1-047 GEN
Solar/Wind Harmer
2.129
971675AH1-338 GEN
Solar/Wind Harmer
1.342
971411AH1-196 GEN
Solar/Wind Harmer
5.159
276868AE1-113 GEN
Solar/Wind Harmer
0.688
276882AE2-255 GEN
Solar/Wind Harmer
0.401
971171AH1-044 GEN
Solar/Wind Harmer
6.836
274823ROCKFORD ;21
Adder
9.515
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
971681AH1-341 GEN
Solar/Wind Harmer
5.414
926823AC1-168 GEN
Solar/Wind Harmer
0.57
970169AG2-114 GEN
Solar/Wind Harmer
3.325
961011AF2-392 GEN
Solar/Wind Harmer
1.951
971619AH1-309 GEN
Solar/Wind Harmer
1.495
957751AF2-069 GEN
Solar/Wind Harmer
0.108
958391AF2-133 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.806
971611AH1-305 GEN
Solar/Wind Harmer
1.91
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.343
941731AE2-173 GEN
Solar/Wind Harmer
2.653
270071AF1-092 GEN
Solar/Wind Harmer
6.011
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Helper
6.373
270286AF1-227 GEN2
Solar/Wind Helper
2.337
270287AF1-227 GEN3
Solar/Wind Helper
2.337
270317AD1-130_GEN
Solar/Wind Helper
5.933
253383AE2-342_GEN
Solar/Wind Helper
1.119
241973AD2-163_GEN1
Solar/Wind Helper
2.428
270520AE2-214 GEN
Solar/Wind Helper
6.383
270054AF2-122 C O1
Solar/Wind Helper
1.467
945631AF1-228 GEN
Solar/Wind Helper
1.9
966831AG1-554 GEN
Solar/Wind Helper
0.865
241972AD1-140 GEN
Solar/Wind Helper
3.134
945641AF1-229 GEN
Solar/Wind Helper
1.104
270499AE1-146 GEN
Solar/Wind Helper
1.892
270340AC2-060 GEN
Solar/Wind Helper
0.99
243186AF1-051 GEN
50/50
3.112
970321AG2-212 GEN
Solar/Wind Harmer
1.811
274770LINCOLN ;1U
Adder
4.511
274771LINCOLN ;2U
Adder
4.511
965681AG1-436 GEN
Solar/Wind Harmer
4.53
965791AG1-447 GEN
Solar/Wind Harmer
3.322
972259AH1-714 GEN
Adder
9.882
274888KELLY CRK;1U
Solar/Wind Harmer
0.211
274887GEN-1.85
Solar/Wind Harmer
0.094
276843GEN-1.7
Solar/Wind Harmer
0.116
958011AF2-095 GEN
Solar/Wind Harmer
5.166
274803UNIV PARK;6U
Adder
2.992
274808UNIV PK N;4U
Adder
2.557
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.865
971573AH1-285 GEN
Solar/Wind Harmer
0.66
24441505OLIV SLR
Solar/Wind Harmer
0
274696ROCKY RD ;4P
Adder
5.736
274695ROCKY RD ;2P
Adder
5.604
274693ROCKY RD ;1P
Adder
5.549
274697ROCKY RD ;3P
Adder
1.522
270526AF1-158 GEN
Solar/Wind Harmer
0.004
274683WAUKEGAN ;8U
Adder
10.566
274683WAUKEGAN ;8U
Adder
8.906
962691AG1-118 GEN
Solar/Wind Harmer
10.47
958481AF2-142 GEN
Solar/Wind Harmer
5.224
970921AG2-575 GEN
Solar/Wind Harmer
3.482
970921AG2-575 GEN
Solar/Wind Harmer
1.161
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.471
942991AE2-321 GEN
Solar/Wind Harmer
3.857
958491AF2-143 GEN
Solar/Wind Harmer
5.163
971333AH1-146 GEN
Solar/Wind Harmer
6.875
971335AH1-147 GEN
Solar/Wind Harmer
6.875
274879MINONK ;1U
Solar/Wind Harmer
0.145
971341AH1-150 GEN
Solar/Wind Harmer
6.836
971343AH1-151 GEN
Solar/Wind Harmer
6.836
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.08
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.905
274764LEE CO EC;5U
Adder
4.477
274765LEE CO EC;6U
Adder
4.477
274762LEE CO EC;3U
Adder
4.467
274763LEE CO EC;4U
Adder
4.425
276603SUBLETTE C
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
1.98
957891AF2-083 GEN
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.118
276708O09 GEN2
Solar/Wind Harmer
0.118
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.129
276646AC1-214 GEN2
Solar/Wind Harmer
0.129
276782AC1-033 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.481
961051AF2-396 GEN
Solar/Wind Harmer
4.32
960611AF2-352 GEN
Solar/Wind Harmer
1.041
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
247620Y3-023
Adder
0.202
270471AD2-092_GEN
Solar/Wind Helper
4.69
270224U2-072_GEN2
Solar/Wind Helper
1.532
270227U2-072_GEN3
Solar/Wind Helper
1.532
270228U2-072_GEN4
Solar/Wind Helper
1.532
270231U2-072_GEN5
Solar/Wind Helper
1.532
946101AF1-275 GEN
Solar/Wind Helper
0.8
241960AC2-195 GEN
Solar/Wind Helper
1.845
253378AE2-206_GEN
Solar/Wind Helper
1.302
276820AF1-078_GEN
Solar/Wind Helper
0.608
270518AE2-148 GEN
Solar/Wind Helper
10.792
NYPJM->LTFIMP_NY
CLTF
0.911
LGEELTFEXP_LGEE->PJM
CLTF
0.799
WECLTFEXP_WEC->PJM
CLTF
1.858
CPLELTFEXP_CPLE->PJM
CLTF
1.514
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.096
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
41.902
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.154
MECLTFEXP_MEC->PJM
CLTF
6.971
SIGELTFEXP_SIGE->PJM
CLTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
5.378
CBM South 2LTFEXP_CBM-S2->PJM
CBM
5.184
TVALTFEXP_TVA->PJM
CLTF
2.393

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.64 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5971.43
MW Contribution:10.13
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
CPLELTFEXP_CPLE->PJM
CLTF
3.24
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.18 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5310.77
MW Contribution:10.87
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56

Details for 05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.73 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4643.02
MW Contribution:8.35
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
CPLELTFEXP_CPLE->PJM
CLTF
1.429
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.66 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5972.54
MW Contribution:10.13
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.06
270100X2-052 CT1
50/50
1.898
270101X2-052 CT2
50/50
1.898
970321AG2-212 GEN
Solar/Wind Harmer
4.074
965681AG1-436 GEN
Solar/Wind Harmer
11.195
965791AG1-447 GEN
Solar/Wind Harmer
8.21
274770LINCOLN ;1U
Adder
10.782
274771LINCOLN ;2U
Adder
10.782
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.281
972259AH1-714 GEN
Adder
24.011
274803UNIV PARK;6U
Adder
7.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.515
274887GEN-1.85
Solar/Wind Harmer
0.231
276843GEN-1.7
Solar/Wind Harmer
0.284
958011AF2-095 GEN
Solar/Wind Harmer
12.628
247620Y3-023
Adder
0.578
961051AF2-396 GEN
Solar/Wind Harmer
17.455
961051AF2-396 GEN
Solar/Wind Harmer
11.637
274674JOLIET 9 ;6U
Adder
19.252
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.615
274696ROCKY RD ;4P
Adder
14.093
274695ROCKY RD ;2P
Adder
13.768
274693ROCKY RD ;1P
Adder
13.632
274697ROCKY RD ;3P
Adder
3.74
958481AF2-142 GEN
Solar/Wind Harmer
12.927
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.166
274683WAUKEGAN ;8U
Adder
26.009
274683WAUKEGAN ;8U
Adder
21.925
962691AG1-118 GEN
Solar/Wind Harmer
25.779
970921AG2-575 GEN
Solar/Wind Harmer
8.581
970921AG2-575 GEN
Solar/Wind Harmer
2.86
958491AF2-143 GEN
Solar/Wind Harmer
12.84
970611AG2-400 GEN
Solar/Wind Harmer
8.544
970627AG2-408 GEN
Solar/Wind Harmer
2.563
942991AE2-321 GEN
Solar/Wind Harmer
9.539
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
17.035
971335AH1-147 GEN
Solar/Wind Harmer
17.035
971341AH1-150 GEN
Solar/Wind Harmer
16.979
971343AH1-151 GEN
Solar/Wind Harmer
16.979
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.199
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.764
274764LEE CO EC;5U
Adder
11.213
274765LEE CO EC;6U
Adder
11.213
274762LEE CO EC;3U
Adder
11.187
274763LEE CO EC;4U
Adder
11.081
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
972267AH1-718 GEN
Adder
4.979
276741O09 GEN1
Solar/Wind Harmer
0.297
276708O09 GEN2
Solar/Wind Harmer
0.297
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.327
276646AC1-214 GEN2
Solar/Wind Harmer
0.327
944541AF1-119 GEN
Solar/Wind Harmer
0.557
960971AF2-388 GEN
Solar/Wind Harmer
4.876
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.724
966841AG1-555 GEN
Solar/Wind Harmer
0.919
942221AE2-234 GEN
Solar/Wind Harmer
0.04
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.592
270599AE1-208 GEN
Solar/Wind Harmer
7.039
270031AE2-169
Solar/Wind Harmer
4.223
276916AD2-100_GEN
Solar/Wind Harmer
16.09
276911AD2-131_GEN
Solar/Wind Harmer
1.06
971613AH1-306 GEN
Solar/Wind Harmer
3.675
945391AF1-204 GEN
Solar/Wind Harmer
7.93
960441AF2-335 GEN
Solar/Wind Harmer
7.358
970239AG2-162 GEN
Solar/Wind Harmer
1.646
24721805FLATG3
50/50
1.795
24721705FLATG2
50/50
32.905
24344105CKG2
50/50
10.4
962761AG1-125 GEN
Solar/Wind Harmer
80.781
970149AG2-104 GEN
Solar/Wind Harmer
87.246
970155AG2-107 GEN
Solar/Wind Harmer
51.584
970245AG2-165 GEN
Solar/Wind Harmer
4.074
274773LINCOLN ;4U
Adder
10.782
274774LINCOLN ;5U
Adder
10.782
274723RIVER EC ;12
Adder
22.661
24639705ELKHART HY
Adder
0.194
276164X3-005 C
Solar/Wind Harmer
0
274751CRETE EC ;1U
Adder
10.401
274754CRETE EC ;4U
Adder
10.401
270505AE1-170 C O1
Solar/Wind Harmer
9.235
274812UNIV PK N;8U
Adder
6.308
276776AD2-060 GEN
Solar/Wind Harmer
0.916
274801UNIV PARK;4U
Adder
7.326
945111AF1-176 GEN
Solar/Wind Harmer
15.639
270063AE2-323 C
Solar/Wind Harmer
0.007
941551AE2-152 GEN
Solar/Wind Harmer
0.001
970373AG2-245 GEN
Solar/Wind Harmer
18.378
274676JOLIET 29;8U
Adder
38.397
274674JOLIET 9 ;6U
Adder
19.252
274732ELWOOD EC;7P
Adder
20.542
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.544
274745AC1-111 GEN9
Adder
6.959
270055AF2-134 C O1
Solar/Wind Harmer
0.007
276691AA1-018 GEN1
Solar/Wind Harmer
1.044
274682WAUKEGAN ;7U
Adder
22.199
274828WAUKEGAN ;BP
Adder
13.634
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
8.166
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.147
939401AE1-172 GEN
Solar/Wind Harmer
6.413
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
965011AG1-365 GEN
Solar/Wind Harmer
8.544
971997AH1-543 GEN
Solar/Wind Harmer
4.478
276861AD2-134 GEN
Solar/Wind Harmer
0.153
957471AF2-041 GEN
Solar/Wind Harmer
25.469
959081AF2-199 GEN
Solar/Wind Harmer
8.49
971067AG2-660 GEN
Solar/Wind Harmer
2.83
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.593
274822ROCKFORD ;11
Adder
23.833
972235AH1-702 GEN1
Adder
3.057
970819AG2-516 GEN
Solar/Wind Harmer
10.134
971475AH1-234 GEN
Solar/Wind Harmer
4.092
970569AG2-363 GEN
Solar/Wind Harmer
25.271
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.187
274766LEE CO EC;7U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
2.438
274877BISHOP HL;1U
Solar/Wind Harmer
0.279
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
11.552
958861AF2-177 GEN
Solar/Wind Harmer
3.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.643
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.078
963741AG1-226 GEN
Solar/Wind Harmer
18.629
276615X2-022 GEN
Solar/Wind Harmer
0.082
970291AG2-192 GEN
Solar/Wind Harmer
1.01
965911AG1-460 GEN
Solar/Wind Harmer
1.539
270032AE2-172
Solar/Wind Harmer
5.104
247521TR3_G114
Solar/Wind Harmer
0.277
270246TR4_N_V150
Solar/Wind Harmer
0.049
944231AF1-091 GEN
Solar/Wind Harmer
2.021
276903AD2-071 C
Solar/Wind Harmer
8.405
270005AE1-210 C O1
Solar/Wind Harmer
1.614
965031AG1-367 GEN
Solar/Wind Harmer
7.45
24695305TIMB G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.707
24722005FLATG5
50/50
1.795
24721905FLATG4
50/50
32.905
970153AG2-106 GEN
Solar/Wind Harmer
51.584
970513AG2-328 GEN
Solar/Wind Harmer
4.074
970517AG2-330 GEN
Solar/Wind Harmer
24.444
970349AG2-230 GEN
Solar/Wind Harmer
14.036
270043AE2-236 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
10.782
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.804
274724RIVER EC ;11
Adder
22.4
970707AG2-453 GEN
Solar/Wind Harmer
28.77
274752CRETE EC ;2U
Adder
10.401
274753CRETE EC ;3U
Adder
10.401
944531AF1-118 GEN
Solar/Wind Harmer
39.427
274826FISK ;BP
Adder
13.763
274802UNIV PARK;5U
Adder
7.329
276806AD2-047 C O1
Solar/Wind Harmer
4.97
970941AG2-585 GEN
Solar/Wind Harmer
10.962
972228AH1-698 GEN2
Adder
4.656
274800UNIV PARK;3U
Adder
7.326
972038AH1-567 GEN2
Adder
0.459
945111AF1-176 GEN
Solar/Wind Harmer
7.104
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
37.026
274729ELWOOD EC;1P
Adder
20.542
274730ELWOOD EC;6P
Adder
20.542
274734ELWOOD EC;8P
Adder
20.542
274736ELWOOD EC;9P
Adder
20.542
276893AG1-478 C
Solar/Wind Harmer
0.345
970031AG2-029 GEN
Solar/Wind Harmer
5.657
943121AE2-341 GEN
Solar/Wind Harmer
14.583
943591AF1-030 GEN
Solar/Wind Harmer
9.698
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.199
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.314
276805AD2-038 GEN
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.981
965021AG1-366 GEN
Solar/Wind Harmer
2.848
24441205WTRV SLR C
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.909
274855GSG-6 ;RU
Solar/Wind Harmer
0.313
274850MENDOTA H;RU
Solar/Wind Harmer
0.1
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.153
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
16.979
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.658
247604X1-042
Adder
0.505
970571AG2-364 GEN
Solar/Wind Harmer
16.847
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.187
274767LEE CO EC;8U
Adder
11.055
276157O29GEN1
Solar/Wind Harmer
1.347
274878BISHOP HL;2U
Solar/Wind Harmer
0.279
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.289
942111AE2-223 GEN
Solar/Wind Harmer
2.682
965931AG1-462 GEN
Solar/Wind Harmer
20.855
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
24.514
959611AF2-252 GEN
Solar/Wind Harmer
2.724
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.657
276668AB2-070 GEN1
Solar/Wind Harmer
0.289
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.395
276838X2-022 GEN2
Solar/Wind Harmer
0.442
970289AG2-191 GEN
Solar/Wind Harmer
0.855
970291AG2-192 GEN
Solar/Wind Harmer
0.777
942481AE2-261 GEN
Solar/Wind Harmer
23.013
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.049
970193AG2-126 GEN
Solar/Wind Harmer
11.195
958821AF2-173 GEN
Solar/Wind Harmer
10.43
270004AE1-209 GEN
Solar/Wind Harmer
1.614
971617AH1-308 GEN
Solar/Wind Harmer
6.153
970243AG2-164 GEN
Solar/Wind Harmer
3.851
970519AG2-331 GEN
Solar/Wind Harmer
17.115
970699AG2-449 GEN
Solar/Wind Harmer
1.646
24721605FLATG1
50/50
1.795
971599AH1-298 GEN
50/50
12.157
962771AG1-126 GEN
Solar/Wind Harmer
80.781
971347AH1-153 GEN
Solar/Wind Harmer
14.036
270071AF1-092 GEN
Solar/Wind Harmer
17.319
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.916
274775LINCOLN ;6U
Adder
10.782
274776LINCOLN ;7U
Adder
10.782
274777LINCOLN ;8U
Adder
10.782
971769AH1-391 GEN
Solar/Wind Harmer
9.94
971619AH1-309 GEN
Solar/Wind Harmer
3.958
274814UNIV PK N;0U
Adder
6.363
274807UNIV PK N;3U
Adder
6.35
274805UNIV PK N;1U
Adder
6.322
274811UNIV PK N;7U
Adder
6.308
274827FISK ;RP
Adder
9.754
972037AH1-567 GEN1
Adder
0.23
960591AF2-350 GEN
Solar/Wind Harmer
8.77
972227AH1-698 GEN1
Adder
3.278
274687WILL CNTY;4U
Adder
34.988
274687WILL CNTY;4U
Adder
34.988
274675JOLIET 29;7U
Adder
38.397
274675JOLIET 29;7U
Adder
37.026
274731ELWOOD EC;2P
Adder
20.542
274733ELWOOD EC;3P
Adder
20.542
274735ELWOOD EC;4P
Adder
20.542
274728ELWOOD EC;5P
Adder
20.542
970833AG2-524 GEN
Solar/Wind Harmer
9.589
970833AG2-524 GEN
Solar/Wind Harmer
6.393
274746AC1-111 G10
Adder
6.959
274744AC1-111 GEN8
Adder
6.959
24729505KEY G4
Adder
8.06
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
5.267
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971675AH1-338 GEN
Solar/Wind Harmer
3.323
971411AH1-196 GEN
Solar/Wind Harmer
12.781
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971171AH1-044 GEN
Solar/Wind Harmer
16.979
971611AH1-305 GEN
Solar/Wind Harmer
5.045
274823ROCKFORD ;21
Adder
23.66
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.432
970169AG2-114 GEN
Solar/Wind Harmer
8.423
971681AH1-341 GEN
Solar/Wind Harmer
13.539
961011AF2-392 GEN
Solar/Wind Harmer
4.902
957751AF2-069 GEN
Solar/Wind Harmer
0.275
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.664
941731AE2-173 GEN
Solar/Wind Harmer
6.876
946321AF1-296 GEN
Solar/Wind Harmer
4.594
965101AG1-375 GEN
Solar/Wind Harmer
8.195
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.463
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
10.716
971549AH1-272 GEN
Solar/Wind Harmer
16.349
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.289
276848AB2-070 GEN3
Solar/Wind Harmer
0.287
965041AG1-368 GEN
Solar/Wind Harmer
7.862
970289AG2-191 GEN
Solar/Wind Harmer
1.476
971609AH1-304 GEN
Solar/Wind Harmer
1.254
270594AE1-207 GEN
Solar/Wind Harmer
8.574
965051AG1-369 GEN
Solar/Wind Harmer
3.795
944221AF1-090 GEN
Solar/Wind Harmer
4.425
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.008
970115AG2-085 GEN
Solar/Wind Harmer
2.943
270054AF2-122 C O1
Solar/Wind Helper
1.539
944201AF1-088_MTX
Adder
118.46
957141AF2-008_MTX
Adder
32.732
NYPJM->LTFIMP_NY
CLTF
3.756
LGEELTFEXP_LGEE->PJM
CLTF
5.526
WECLTFEXP_WEC->PJM
CLTF
4.63
CPLELTFEXP_CPLE->PJM
CLTF
3.24
CBM West 2LTFEXP_CBM-W2->PJM
CBM
120.262
AG2-052LTFEXP_AG2-052->PJM
LTF
0.285
AH1-155LTFEXP_AH1-155->PJM
LTF
0.428
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.812
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.167
MECLTFEXP_MEC->PJM
CLTF
18.496
SIGELTFEXP_SIGE->PJM
CLTF
0.474
LAGNLTFEXP_LAGN->PJM
CLTF
16.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
13.027
TVALTFEXP_TVA->PJM
CLTF
7.706

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o AEP_P1-2_#706_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#706_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:116.43 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:5322.01
MW Contribution:10.87
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
3.512
247620Y3-023
50/50
0.722
270102X2-052 ST
50/50
2.354
270100X2-052 CT1
50/50
2.169
270101X2-052 CT2
50/50
2.169
270471AD2-092_GEN
Solar/Wind Harmer
0.009
970611AG2-400 GEN
Solar/Wind Harmer
10.537
970627AG2-408 GEN
Solar/Wind Harmer
3.161
970321AG2-212 GEN
Solar/Wind Harmer
4.559
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270526AF1-158 GEN
Solar/Wind Harmer
0.013
24441505OLIV SLR
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
20.46
961051AF2-396 GEN
Solar/Wind Harmer
13.64
24721605FLATG1
50/50
5.145
971599AH1-298 GEN
50/50
14.587
270144AC1-141 ST1_
50/50
3.152
24653605MOTTVILLE
50/50
0.006
24643105BUCHANAN
50/50
0.019
962771AG1-126 GEN
Solar/Wind Harmer
120.047
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
16.236
270071AF1-092 GEN
Solar/Wind Harmer
20.132
971771AH1-392 GEN
Solar/Wind Harmer
10.346
971619AH1-309 GEN
Solar/Wind Harmer
4.631
971769AH1-391 GEN
Solar/Wind Harmer
11.424
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
24729505KEY G4
Adder
9.267
274775LINCOLN ;6U
Adder
11.972
274776LINCOLN ;7U
Adder
11.972
274777LINCOLN ;8U
Adder
11.972
965041AG1-368 GEN
Solar/Wind Harmer
9.847
270578AF1-285 GEN2
Solar/Wind Harmer
0.651
274814UNIV PK N;0U
Adder
7.057
274807UNIV PK N;3U
Adder
7.042
274805UNIV PK N;1U
Adder
7.011
274811UNIV PK N;7U
Adder
6.996
972037AH1-567 GEN1
Adder
0.254
274827FISK ;RP
Adder
10.776
960591AF2-350 GEN
Solar/Wind Harmer
9.68
972227AH1-698 GEN1
Adder
3.616
965051AG1-369 GEN
Solar/Wind Harmer
4.807
274687WILL CNTY;4U
Adder
38.503
274687WILL CNTY;4U
Adder
38.503
274675JOLIET 29;7U
Adder
42.223
274675JOLIET 29;7U
Adder
40.715
274728ELWOOD EC;5P
Adder
22.567
274731ELWOOD EC;2P
Adder
22.566
274733ELWOOD EC;3P
Adder
22.566
274735ELWOOD EC;4P
Adder
22.566
270536AF1-215 GEN2
Solar/Wind Harmer
0.012
970833AG2-524 GEN
Solar/Wind Harmer
10.52
970833AG2-524 GEN
Solar/Wind Harmer
7.013
971549AH1-272 GEN
Solar/Wind Harmer
19.681
274746AC1-111 G10
Adder
7.614
274744AC1-111 GEN8
Adder
7.614
963791AG1-232 GEN
Solar/Wind Harmer
12.76
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.183
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.013
971653AH1-327 GEN
Solar/Wind Harmer
1.314
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.855
276882AE2-255 GEN
Solar/Wind Harmer
1.081
971177AH1-047 GEN
Solar/Wind Harmer
5.697
965101AG1-375 GEN
Solar/Wind Harmer
9.202
971411AH1-196 GEN
Solar/Wind Harmer
13.802
971675AH1-338 GEN
Solar/Wind Harmer
3.588
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
971611AH1-305 GEN
Solar/Wind Harmer
5.454
971171AH1-044 GEN
Solar/Wind Harmer
18.285
274823ROCKFORD ;21
Adder
25.447
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.535
970169AG2-114 GEN
Solar/Wind Harmer
9.023
971681AH1-341 GEN
Solar/Wind Harmer
14.483
247607V1-011 GEN
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
5.219
945581AF1-223 GEN
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.292
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.145
941731AE2-173 GEN
Solar/Wind Harmer
7.258
946321AF1-296 GEN
Solar/Wind Harmer
4.827
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
270024AE2-089 GEN
Solar/Wind Harmer
0.009
971609AH1-304 GEN
Solar/Wind Harmer
1.375
970289AG2-191 GEN
Solar/Wind Harmer
1.578
963841AG1-237 GEN
Solar/Wind Harmer
3.575
270594AE1-207 GEN
Solar/Wind Harmer
9.172
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.295
276848AB2-070 GEN3
Solar/Wind Harmer
0.294
970115AG2-085 GEN
Solar/Wind Harmer
3.159
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
24721805FLATG3
50/50
5.145
24721705FLATG2
50/50
94.33
24344105CKG2
50/50
12.069
270143AC1-141 CT2_
50/50
3.558
24639705ELKHART HY
50/50
0.241
970521AG2-332 GEN
50/50
17.184
24307105BERRINSP G
50/50
0.032
962761AG1-125 GEN
Solar/Wind Harmer
120.047
970149AG2-104 GEN
Solar/Wind Harmer
129.655
970155AG2-107 GEN
Solar/Wind Harmer
76.659
270349AD2-093_GEN
Solar/Wind Harmer
0.009
965011AG1-365 GEN
Solar/Wind Harmer
10.537
970245AG2-165 GEN
Solar/Wind Harmer
4.559
270063AE2-323 C
Solar/Wind Harmer
0.008
270505AE1-170 C O1
Solar/Wind Harmer
10.806
945111AF1-176 GEN
Solar/Wind Harmer
18.321
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
5.329
274773LINCOLN ;4U
Adder
11.972
274774LINCOLN ;5U
Adder
11.972
274723RIVER EC ;12
Adder
25.205
274751CRETE EC ;1U
Adder
11.58
274754CRETE EC ;4U
Adder
11.58
270223U2-072_GEN1
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
20.506
274812UNIV PK N;8U
Adder
6.996
274801UNIV PARK;4U
Adder
8.089
276776AD2-060 GEN
Solar/Wind Harmer
1.011
247521TR3_G114
Solar/Wind Harmer
0.351
270246TR4_N_V150
Solar/Wind Harmer
0.062
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
42.222
274674JOLIET 9 ;6U
Adder
21.154
274732ELWOOD EC;7P
Adder
22.567
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.614
944231AF1-091 GEN
Solar/Wind Harmer
2.532
24695305TIMB G C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
28.36
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.138
965651AG1-433 GEN
Solar/Wind Harmer
2.755
274682WAUKEGAN ;7U
Adder
24.169
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
12.195
274828WAUKEGAN ;BP
Adder
14.836
246936BC-WTG1
Solar/Wind Harmer
0.379
270489AE1-102 GEN1
Solar/Wind Harmer
1.214
270462AD2-086
Solar/Wind Harmer
0.02
962781AG1-127 GEN
Solar/Wind Harmer
8.858
939401AE1-172 GEN
Solar/Wind Harmer
6.954
274872LEEDK;1U
Solar/Wind Harmer
0.006
276901AD2-066 C O1
Solar/Wind Harmer
0.009
971997AH1-543 GEN
Solar/Wind Harmer
4.843
958861AF2-177 GEN
Solar/Wind Harmer
3.987
276861AD2-134 GEN
Solar/Wind Harmer
0.165
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.452
957471AF2-041 GEN
Solar/Wind Harmer
27.428
959081AF2-199 GEN
Solar/Wind Harmer
9.143
971067AG2-660 GEN
Solar/Wind Harmer
3.048
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
25.633
972235AH1-702 GEN1
Adder
3.284
970819AG2-516 GEN
Solar/Wind Harmer
10.874
971475AH1-234 GEN
Solar/Wind Harmer
4.385
970569AG2-363 GEN
Solar/Wind Harmer
27.095
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
11.947
274766LEE CO EC;7U
Adder
11.806
276158O29GEN2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.295
24791305MDL-5G
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.194
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
6.873
970291AG2-192 GEN
Solar/Wind Harmer
1.08
270032AE2-172
Solar/Wind Harmer
5.46
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.14
963741AG1-226 GEN
Solar/Wind Harmer
19.026
270005AE1-210 C O1
Solar/Wind Harmer
1.733
965031AG1-367 GEN
Solar/Wind Harmer
8
276615X2-022 GEN
Solar/Wind Harmer
0.084
276903AD2-071 C
Solar/Wind Harmer
8.872
970825AG2-519 GEN
Solar/Wind Harmer
2.793
965911AG1-460 GEN
Solar/Wind Harmer
1.538
24728605AND G2
Adder
3.739
965681AG1-436 GEN
Solar/Wind Harmer
12.752
965791AG1-447 GEN
Solar/Wind Harmer
9.351
274770LINCOLN ;1U
Adder
11.972
274771LINCOLN ;2U
Adder
11.972
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
274808UNIV PK N;4U
Adder
6.965
274803UNIV PARK;6U
Adder
8.1
274888KELLY CRK;1U
Solar/Wind Harmer
0.568
274887GEN-1.85
Solar/Wind Harmer
0.255
276843GEN-1.7
Solar/Wind Harmer
0.313
958011AF2-095 GEN
Solar/Wind Harmer
13.939
972259AH1-714 GEN
Adder
26.463
274674JOLIET 9 ;6U
Adder
21.154
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.764
958481AF2-142 GEN
Solar/Wind Harmer
14.096
274695ROCKY RD ;2P
Adder
14.996
274693ROCKY RD ;1P
Adder
14.848
274697ROCKY RD ;3P
Adder
4.074
274696ROCKY RD ;4P
Adder
15.349
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.271
944541AF1-119 GEN
Solar/Wind Harmer
0.629
960971AF2-388 GEN
Solar/Wind Harmer
5.509
274683WAUKEGAN ;8U
Adder
28.303
274683WAUKEGAN ;8U
Adder
23.858
246938BC-WTG3
Solar/Wind Harmer
0.338
246937BC-WTG2
Solar/Wind Harmer
0.379
962691AG1-118 GEN
Solar/Wind Harmer
27.992
970921AG2-575 GEN
Solar/Wind Harmer
9.308
970921AG2-575 GEN
Solar/Wind Harmer
3.103
958491AF2-143 GEN
Solar/Wind Harmer
13.931
274879MINONK ;1U
Solar/Wind Harmer
0.39
942991AE2-321 GEN
Solar/Wind Harmer
10.32
971333AH1-146 GEN
Solar/Wind Harmer
18.389
971335AH1-147 GEN
Solar/Wind Harmer
18.389
971341AH1-150 GEN
Solar/Wind Harmer
18.285
971343AH1-151 GEN
Solar/Wind Harmer
18.285
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
942221AE2-234 GEN
Solar/Wind Harmer
0.046
274856ECOGROVE ;U1
Solar/Wind Harmer
0.213
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
5.096
274764LEE CO EC;5U
Adder
11.975
274765LEE CO EC;6U
Adder
11.975
274762LEE CO EC;3U
Adder
11.947
274763LEE CO EC;4U
Adder
11.834
276603SUBLETTE C
Solar/Wind Harmer
0
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270007AE1-245 C
Solar/Wind Harmer
0.002
972267AH1-718 GEN
Adder
5.295
276741O09 GEN1
Solar/Wind Harmer
0.315
276708O09 GEN2
Solar/Wind Harmer
0.315
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.347
276646AC1-214 GEN2
Solar/Wind Harmer
0.347
970623AG2-406 GEN
Solar/Wind Harmer
1.614
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.854
966841AG1-555 GEN
Solar/Wind Harmer
0.959
270599AE1-208 GEN
Solar/Wind Harmer
7.715
270031AE2-169
Solar/Wind Harmer
4.629
971613AH1-306 GEN
Solar/Wind Harmer
3.931
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
4.69
960441AF2-335 GEN
Solar/Wind Harmer
7.897
970825AG2-519 GEN
Solar/Wind Harmer
8.719
964611AG1-324 GEN
Solar/Wind Harmer
0.584
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970621AG2-405 GEN
Solar/Wind Harmer
1.413
247621Y3-024
Adder
0.262
276916AD2-100_GEN
Solar/Wind Harmer
13.41
276911AD2-131_GEN
Solar/Wind Harmer
0.883
24722005FLATG5
50/50
5.145
24721905FLATG4
50/50
94.33
270475AD2-096_GEN
50/50
10.026
270142AC1-141 CT1_
50/50
3.558
24641605TWIN BRNCH
50/50
0.026
24344005CKG1
50/50
9.691
24642205MAYFLWER
50/50
0.992
944961AF1-161 GEN
50/50
4.253
962601AG1-109 GEN
50/50
4.253
247604X1-042
50/50
0.632
970153AG2-106 GEN
Solar/Wind Harmer
76.659
270043AE2-236 GEN
Solar/Wind Harmer
6.969
970349AG2-230 GEN
Solar/Wind Harmer
16.236
959331AF2-224 GEN
Solar/Wind Harmer
7.376
965021AG1-366 GEN
Solar/Wind Harmer
3.512
970513AG2-328 GEN
Solar/Wind Harmer
4.559
970517AG2-330 GEN
Solar/Wind Harmer
27.357
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
6.732
945111AF1-176 GEN
Solar/Wind Harmer
8.323
944531AF1-118 GEN
Solar/Wind Harmer
45.595
24441205WTRV SLR C
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
11.972
274724RIVER EC ;11
Adder
24.913
274752CRETE EC ;2U
Adder
11.58
274753CRETE EC ;3U
Adder
11.58
270391AF1-285 GEN3
Solar/Wind Harmer
0.651
970707AG2-453 GEN
Solar/Wind Harmer
31.724
274802UNIV PARK;5U
Adder
8.1
274826FISK ;BP
Adder
15.205
274800UNIV PARK;3U
Adder
8.089
972038AH1-567 GEN2
Adder
0.506
276806AD2-047 C O1
Solar/Wind Harmer
5.485
970941AG2-585 GEN
Solar/Wind Harmer
12.1
972228AH1-698 GEN2
Adder
5.135
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.062
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
40.714
274730ELWOOD EC;6P
Adder
22.567
274734ELWOOD EC;8P
Adder
22.567
274736ELWOOD EC;9P
Adder
22.567
274729ELWOOD EC;1P
Adder
22.566
276893AG1-478 C
Solar/Wind Harmer
0.379
270535AF1-215 GEN1
Solar/Wind Harmer
0.012
943121AE2-341 GEN
Solar/Wind Harmer
15.96
943591AF1-030 GEN
Solar/Wind Harmer
10.614
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
24.169
270491AE1-102 GEN2
Solar/Wind Harmer
1.214
270485AE1-090_GEN
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.341
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.982
274855GSG-6 ;RU
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.165
959091AF2-200 GEN
Solar/Wind Harmer
18.285
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.856
970571AG2-364 GEN
Solar/Wind Harmer
18.064
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
11.947
274767LEE CO EC;8U
Adder
11.806
276157O29GEN1
Solar/Wind Harmer
1.431
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274878BISHOP HL;2U
Solar/Wind Harmer
0.295
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.785
270404AC1-167 GEN
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
2.831
965931AG1-462 GEN
Solar/Wind Harmer
21.861
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
25.685
959611AF2-252 GEN
Solar/Wind Harmer
2.854
971617AH1-308 GEN
Solar/Wind Harmer
7.03
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
0.914
970291AG2-192 GEN
Solar/Wind Harmer
0.831
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.74
276668AB2-070 GEN1
Solar/Wind Harmer
0.295
958821AF2-173 GEN
Solar/Wind Harmer
11.2
270004AE1-209 GEN
Solar/Wind Harmer
1.733
276621W2-048 GEN
Solar/Wind Harmer
0.401
276838X2-022 GEN2
Solar/Wind Harmer
0.448
946031AF1-268 GEN
Solar/Wind Harmer
7.422
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
11.672
942481AE2-261 GEN
Solar/Wind Harmer
22.986
24728705AND G3
Adder
7.82
24728505AND G1
Adder
3.739
944201AF1-088_MTX
Adder
85.667
NYPJM->LTFIMP_NY
CLTF
2.99
LGEELTFEXP_LGEE->PJM
CLTF
4.155
WECLTFEXP_WEC->PJM
CLTF
4.968
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.286
AG2-052LTFEXP_AG2-052->PJM
LTF
0.312
AH1-155LTFEXP_AH1-155->PJM
LTF
0.469
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.989
CBM West 1LTFEXP_CBM-W1->PJM
CBM
161.402
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.132
MECLTFEXP_MEC->PJM
CLTF
18.394
SIGELTFEXP_SIGE->PJM
CLTF
0.399
LAGNLTFEXP_LAGN->PJM
CLTF
11.144
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.328
TVALTFEXP_TVA->PJM
CLTF
4.56

Details for 05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RM-05MALIS 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:114.86 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:4648.25
MW Contribution:8.35
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.558
270144AC1-141 ST1_
50/50
2.306
24643105BUCHANAN
50/50
0.014
24653605MOTTVILLE
50/50
0.004
274775LINCOLN ;6U
50/50
9.593
274776LINCOLN ;7U
50/50
9.593
274777LINCOLN ;8U
50/50
9.593
962771AG1-126 GEN
Solar/Wind Harmer
74.603
971347AH1-153 GEN
Solar/Wind Harmer
12.013
270071AF1-092 GEN
Solar/Wind Harmer
14.717
971771AH1-392 GEN
Solar/Wind Harmer
7.604
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
8.444
971619AH1-309 GEN
Solar/Wind Harmer
3.384
274814UNIV PK N;0U
Adder
5.324
274807UNIV PK N;3U
Adder
5.313
274805UNIV PK N;1U
Adder
5.29
274811UNIV PK N;7U
Adder
5.278
274827FISK ;RP
Adder
8.149
972037AH1-567 GEN1
Adder
0.192
960591AF2-350 GEN
Solar/Wind Harmer
7.323
972227AH1-698 GEN1
Adder
2.737
274687WILL CNTY;4U
Adder
29.176
274687WILL CNTY;4U
Adder
29.176
274675JOLIET 29;7U
Adder
32.008
274675JOLIET 29;7U
Adder
30.865
24729505KEY G4
Adder
6.759
274731ELWOOD EC;2P
Adder
17.114
274733ELWOOD EC;3P
Adder
17.114
274735ELWOOD EC;4P
Adder
17.114
274728ELWOOD EC;5P
Adder
17.114
970833AG2-524 GEN
Solar/Wind Harmer
7.985
970833AG2-524 GEN
Solar/Wind Harmer
5.323
274746AC1-111 G10
Adder
5.788
274744AC1-111 GEN8
Adder
5.788
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
971177AH1-047 GEN
Solar/Wind Harmer
4.355
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.417
276882AE2-255 GEN
Solar/Wind Harmer
0.825
971675AH1-338 GEN
Solar/Wind Harmer
2.746
971411AH1-196 GEN
Solar/Wind Harmer
10.56
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971171AH1-044 GEN
Solar/Wind Harmer
14.009
274823ROCKFORD ;21
Adder
19.51
971611AH1-305 GEN
Solar/Wind Harmer
4.152
276612AE2-035 GEN
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.178
970169AG2-114 GEN
Solar/Wind Harmer
6.92
971681AH1-341 GEN
Solar/Wind Harmer
11.133
961011AF2-392 GEN
Solar/Wind Harmer
4.021
957751AF2-069 GEN
Solar/Wind Harmer
0.225
971549AH1-272 GEN
Solar/Wind Harmer
14.034
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
6.746
965041AG1-368 GEN
Solar/Wind Harmer
6.733
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.06
941731AE2-173 GEN
Solar/Wind Harmer
5.603
946321AF1-296 GEN
Solar/Wind Harmer
3.744
963791AG1-232 GEN
Solar/Wind Harmer
8.989
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
945581AF1-223 GEN
Solar/Wind Harmer
0
965051AG1-369 GEN
Solar/Wind Harmer
3.241
963841AG1-237 GEN
Solar/Wind Harmer
2.776
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.231
276848AB2-070 GEN3
Solar/Wind Harmer
0.23
970289AG2-191 GEN
Solar/Wind Harmer
1.184
971609AH1-304 GEN
Solar/Wind Harmer
1.011
270594AE1-207 GEN
Solar/Wind Harmer
6.856
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.765
270284AF1-227 GEN1
Solar/Wind Harmer
0.008
270286AF1-227 GEN2
Solar/Wind Harmer
0.003
270287AF1-227 GEN3
Solar/Wind Harmer
0.003
270054AF2-122 C O1
Solar/Wind Helper
1.65
24344105CKG2
50/50
8.939
270143AC1-141 CT2_
50/50
2.603
24639705ELKHART HY
50/50
0.176
970521AG2-332 GEN
50/50
12.519
274773LINCOLN ;4U
50/50
9.593
274774LINCOLN ;5U
50/50
9.593
962761AG1-125 GEN
Solar/Wind Harmer
74.603
970149AG2-104 GEN
Solar/Wind Harmer
80.573
970155AG2-107 GEN
Solar/Wind Harmer
47.639
970245AG2-165 GEN
Solar/Wind Harmer
3.44
270505AE1-170 C O1
Solar/Wind Harmer
7.896
270063AE2-323 C
Solar/Wind Harmer
0.006
945111AF1-176 GEN
Solar/Wind Harmer
13.37
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
3.886
274723RIVER EC ;12
Adder
18.99
274751CRETE EC ;1U
Adder
8.717
274754CRETE EC ;4U
Adder
8.717
276164X3-005 C
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
7.366
274812UNIV PK N;8U
Adder
5.278
970373AG2-245 GEN
Solar/Wind Harmer
15.386
276776AD2-060 GEN
Solar/Wind Harmer
0.765
274801UNIV PARK;4U
Adder
6.118
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
32.008
274674JOLIET 9 ;6U
Adder
16.042
274732ELWOOD EC;7P
Adder
17.114
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.788
270055AF2-134 C O1
Solar/Wind Harmer
0.006
276691AA1-018 GEN1
Solar/Wind Harmer
0.866
274682WAUKEGAN ;7U
Adder
18.416
274828WAUKEGAN ;BP
Adder
11.308
958381AF2-132 GEN
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
6.763
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.233
274872LEEDK;1U
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
5.304
276901AD2-066 C O1
Solar/Wind Harmer
0.007
971997AH1-543 GEN
Solar/Wind Harmer
3.701
276861AD2-134 GEN
Solar/Wind Harmer
0.126
957471AF2-041 GEN
Solar/Wind Harmer
21.014
959081AF2-199 GEN
Solar/Wind Harmer
7.005
971067AG2-660 GEN
Solar/Wind Harmer
2.335
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
19.652
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.717
972235AH1-702 GEN1
Adder
2.519
970819AG2-516 GEN
Solar/Wind Harmer
8.346
971475AH1-234 GEN
Solar/Wind Harmer
3.368
970569AG2-363 GEN
Solar/Wind Harmer
20.788
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.191
274766LEE CO EC;7U
Adder
9.083
965651AG1-433 GEN
Solar/Wind Harmer
2.017
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.228
24721705FLATG2
Adder
19.64
24791305MDL-5G
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
2.923
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.413
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
944231AF1-091 GEN
Solar/Wind Harmer
1.739
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
972175AH1-670 GEN
Solar/Wind Harmer
5.355
270349AD2-093_GEN
Solar/Wind Harmer
0.005
24695305TIMB G C
Solar/Wind Harmer
0.002
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.462
963741AG1-226 GEN
Solar/Wind Harmer
14.839
276615X2-022 GEN
Solar/Wind Harmer
0.066
970291AG2-192 GEN
Solar/Wind Harmer
0.81
965421AG1-410 GEN
Solar/Wind Harmer
18.496
270032AE2-172
Solar/Wind Harmer
4.081
965911AG1-460 GEN
Solar/Wind Harmer
1.218
246936BC-WTG1
Solar/Wind Harmer
0.245
270489AE1-102 GEN1
Solar/Wind Harmer
0.785
270102X2-052 ST
50/50
1.747
270100X2-052 CT1
50/50
1.61
270101X2-052 CT2
50/50
1.61
247620Y3-023
50/50
0.525
274770LINCOLN ;1U
50/50
9.593
274771LINCOLN ;2U
50/50
9.593
970321AG2-212 GEN
Solar/Wind Harmer
3.44
270216AD2-079_GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
9.481
965791AG1-447 GEN
Solar/Wind Harmer
6.953
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.924
961051AF2-396 GEN
Solar/Wind Harmer
9.95
970611AG2-400 GEN
Solar/Wind Harmer
7.366
970627AG2-408 GEN
Solar/Wind Harmer
2.21
274808UNIV PK N;4U
Adder
5.255
972259AH1-714 GEN
Adder
20.044
274803UNIV PARK;6U
Adder
6.123
274888KELLY CRK;1U
Solar/Wind Harmer
0.43
274887GEN-1.85
Solar/Wind Harmer
0.193
276843GEN-1.7
Solar/Wind Harmer
0.237
958011AF2-095 GEN
Solar/Wind Harmer
10.545
274674JOLIET 9 ;6U
Adder
16.042
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
971573AH1-285 GEN
Solar/Wind Harmer
1.342
274695ROCKY RD ;2P
Adder
11.425
274693ROCKY RD ;1P
Adder
11.312
274697ROCKY RD ;3P
Adder
3.104
274696ROCKY RD ;4P
Adder
11.694
958481AF2-142 GEN
Solar/Wind Harmer
10.727
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.967
274683WAUKEGAN ;8U
Adder
21.572
274683WAUKEGAN ;8U
Adder
18.184
962691AG1-118 GEN
Solar/Wind Harmer
21.36
970921AG2-575 GEN
Solar/Wind Harmer
7.106
970921AG2-575 GEN
Solar/Wind Harmer
2.369
958491AF2-143 GEN
Solar/Wind Harmer
10.627
942991AE2-321 GEN
Solar/Wind Harmer
7.889
274879MINONK ;1U
Solar/Wind Harmer
0.298
971333AH1-146 GEN
Solar/Wind Harmer
14.073
971335AH1-147 GEN
Solar/Wind Harmer
14.073
971341AH1-150 GEN
Solar/Wind Harmer
14.009
971343AH1-151 GEN
Solar/Wind Harmer
14.009
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.164
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
3.917
274764LEE CO EC;5U
Adder
9.213
274765LEE CO EC;6U
Adder
9.213
274762LEE CO EC;3U
Adder
9.191
274763LEE CO EC;4U
Adder
9.105
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.461
960971AF2-388 GEN
Solar/Wind Harmer
4.033
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972267AH1-718 GEN
Adder
4.082
276741O09 GEN1
Solar/Wind Harmer
0.243
276708O09 GEN2
Solar/Wind Harmer
0.243
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.268
276646AC1-214 GEN2
Solar/Wind Harmer
0.268
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.211
942221AE2-234 GEN
Solar/Wind Harmer
0.033
966841AG1-555 GEN
Solar/Wind Harmer
0.741
270471AD2-092_GEN
Solar/Wind Harmer
0.005
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970241AG2-163 GEN
Solar/Wind Harmer
3.657
270599AE1-208 GEN
Solar/Wind Harmer
5.676
270031AE2-169
Solar/Wind Harmer
3.406
971613AH1-306 GEN
Solar/Wind Harmer
2.938
276916AD2-100_GEN
Solar/Wind Harmer
12.71
276911AD2-131_GEN
Solar/Wind Harmer
0.837
246938BC-WTG3
Solar/Wind Harmer
0.219
246937BC-WTG2
Solar/Wind Harmer
0.245
270142AC1-141 CT1_
50/50
2.603
24641605TWIN BRNCH
50/50
0.019
24344005CKG1
50/50
7.096
24642205MAYFLWER
50/50
0.728
274772LINCOLN ;3U
50/50
9.593
970153AG2-106 GEN
Solar/Wind Harmer
47.639
970349AG2-230 GEN
Solar/Wind Harmer
12.013
970513AG2-328 GEN
Solar/Wind Harmer
3.44
970517AG2-330 GEN
Solar/Wind Harmer
20.64
270043AE2-236 GEN
Solar/Wind Harmer
5.033
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
6.073
970031AG2-029 GEN
Solar/Wind Harmer
4.844
944531AF1-118 GEN
Solar/Wind Harmer
33.218
274724RIVER EC ;11
Adder
18.771
274752CRETE EC ;2U
Adder
8.717
274753CRETE EC ;3U
Adder
8.717
959331AF2-224 GEN
Solar/Wind Harmer
5.157
965021AG1-366 GEN
Solar/Wind Harmer
2.455
970707AG2-453 GEN
Solar/Wind Harmer
24.03
274826FISK ;BP
Adder
11.498
274802UNIV PARK;5U
Adder
6.123
276806AD2-047 C O1
Solar/Wind Harmer
4.15
970941AG2-585 GEN
Solar/Wind Harmer
9.154
274800UNIV PARK;3U
Adder
6.118
972038AH1-567 GEN2
Adder
0.383
972228AH1-698 GEN2
Adder
3.887
24441205WTRV SLR C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
30.865
274729ELWOOD EC;1P
Adder
17.114
274730ELWOOD EC;6P
Adder
17.114
274734ELWOOD EC;8P
Adder
17.114
274736ELWOOD EC;9P
Adder
17.114
276893AG1-478 C
Solar/Wind Harmer
0.288
943121AE2-341 GEN
Solar/Wind Harmer
12.132
943591AF1-030 GEN
Solar/Wind Harmer
8.068
247604X1-042
Adder
0.432
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.416
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
0.002
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.751
274855GSG-6 ;RU
Solar/Wind Harmer
0.258
274850MENDOTA H;RU
Solar/Wind Harmer
0.083
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.126
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
959091AF2-200 GEN
Solar/Wind Harmer
14.009
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.191
970571AG2-364 GEN
Solar/Wind Harmer
13.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.191
274767LEE CO EC;8U
Adder
9.083
276157O29GEN1
Solar/Wind Harmer
1.104
274878BISHOP HL;2U
Solar/Wind Harmer
0.228
24721905FLATG4
Adder
19.64
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.747
942111AE2-223 GEN
Solar/Wind Harmer
2.185
965931AG1-462 GEN
Solar/Wind Harmer
16.976
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.897
959611AF2-252 GEN
Solar/Wind Harmer
2.211
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.93
276668AB2-070 GEN1
Solar/Wind Harmer
0.231
247642Z2-115 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.316
276838X2-022 GEN2
Solar/Wind Harmer
0.352
970289AG2-191 GEN
Solar/Wind Harmer
0.686
970291AG2-192 GEN
Solar/Wind Harmer
0.623
942481AE2-261 GEN
Solar/Wind Harmer
18.215
270491AE1-102 GEN2
Solar/Wind Harmer
0.785
NYPJM->LTFIMP_NY
CLTF
2.589
LGEELTFEXP_LGEE->PJM
CLTF
3.659
WECLTFEXP_WEC->PJM
CLTF
3.814
CPLELTFEXP_CPLE->PJM
CLTF
1.429
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.023
AG2-052LTFEXP_AG2-052->PJM
LTF
0.236
AH1-155LTFEXP_AH1-155->PJM
LTF
0.355
CBM West 1LTFEXP_CBM-W1->PJM
CBM
120.019
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.189
MECLTFEXP_MEC->PJM
CLTF
14.69
SIGELTFEXP_SIGE->PJM
CLTF
0.339
LAGNLTFEXP_LAGN->PJM
CLTF
11.239
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.669
TVALTFEXP_TVA->PJM
CLTF
5.062

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.65 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6032.93
MW Contribution:15.55
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.14 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5804.66
MW Contribution:14.7
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.5 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:5281.19
MW Contribution:13.7
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
2.992
270100X2-052 CT1
50/50
2.757
270101X2-052 CT2
50/50
2.757
247620Y3-023
50/50
0.89
970321AG2-212 GEN
Solar/Wind Harmer
5.915
270216AD2-079_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
16.197
965791AG1-447 GEN
Solar/Wind Harmer
11.878
270526AF1-158 GEN
Solar/Wind Harmer
0.016
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
25.575
961051AF2-396 GEN
Solar/Wind Harmer
17.05
274770LINCOLN ;1U
Adder
15.292
274771LINCOLN ;2U
Adder
15.292
274808UNIV PK N;4U
Adder
8.838
972259AH1-714 GEN
Adder
33.646
274803UNIV PARK;6U
Adder
10.281
971599AH1-298 GEN
50/50
18.435
270144AC1-141 ST1_
50/50
3.968
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
20.909
971771AH1-392 GEN
Solar/Wind Harmer
13.038
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971769AH1-391 GEN
Solar/Wind Harmer
14.442
270071AF1-092 GEN
Solar/Wind Harmer
24.752
971619AH1-309 GEN
Solar/Wind Harmer
5.808
274775LINCOLN ;6U
Adder
15.292
274776LINCOLN ;7U
Adder
15.292
274777LINCOLN ;8U
Adder
15.292
274814UNIV PK N;0U
Adder
8.954
274807UNIV PK N;3U
Adder
8.935
274805UNIV PK N;1U
Adder
8.896
274811UNIV PK N;7U
Adder
8.876
972037AH1-567 GEN1
Adder
0.323
274827FISK ;RP
Adder
13.681
960591AF2-350 GEN
Solar/Wind Harmer
12.291
972227AH1-698 GEN1
Adder
4.592
274687WILL CNTY;4U
Adder
48.86
274687WILL CNTY;4U
Adder
48.86
274675JOLIET 29;7U
Adder
53.583
274675JOLIET 29;7U
Adder
51.669
274728ELWOOD EC;5P
Adder
28.626
274731ELWOOD EC;2P
Adder
28.625
274733ELWOOD EC;3P
Adder
28.625
274735ELWOOD EC;4P
Adder
28.625
24729505KEY G4
Adder
11.296
24344105CKG2
50/50
15.732
270143AC1-141 CT2_
50/50
4.479
24639705ELKHART HY
50/50
0.3
970521AG2-332 GEN
50/50
21.293
24307105BERRINSP G
50/50
0.04
970245AG2-165 GEN
Solar/Wind Harmer
5.915
270505AE1-170 C O1
Solar/Wind Harmer
13.553
945111AF1-176 GEN
Solar/Wind Harmer
22.888
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.663
274773LINCOLN ;4U
Adder
15.292
274774LINCOLN ;5U
Adder
15.292
270063AE2-323 C
Solar/Wind Harmer
0.01
274723RIVER EC ;12
Adder
32.009
274751CRETE EC ;1U
Adder
14.685
274754CRETE EC ;4U
Adder
14.685
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
8.876
970373AG2-245 GEN
Solar/Wind Harmer
25.833
276776AD2-060 GEN
Solar/Wind Harmer
1.283
274801UNIV PARK;4U
Adder
10.269
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.582
274674JOLIET 9 ;6U
Adder
26.84
274732ELWOOD EC;7P
Adder
28.626
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
9.659
270055AF2-134 C O1
Solar/Wind Harmer
0.009
276691AA1-018 GEN1
Solar/Wind Harmer
1.44
274682WAUKEGAN ;7U
Adder
30.6
274828WAUKEGAN ;BP
Adder
18.78
962781AG1-127 GEN
Solar/Wind Harmer
11.207
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.007
939401AE1-172 GEN
Solar/Wind Harmer
8.779
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
15.25
276901AD2-066 C O1
Solar/Wind Harmer
0.012
971997AH1-543 GEN
Solar/Wind Harmer
6.112
276861AD2-134 GEN
Solar/Wind Harmer
0.208
965011AG1-365 GEN
Solar/Wind Harmer
11.612
24344005CKG1
50/50
12.252
270142AC1-141 CT1_
50/50
4.479
24641605TWIN BRNCH
50/50
0.032
24642205MAYFLWER
50/50
1.247
944961AF1-161 GEN
50/50
5.318
962601AG1-109 GEN
50/50
5.318
970349AG2-230 GEN
Solar/Wind Harmer
20.909
970513AG2-328 GEN
Solar/Wind Harmer
5.915
970517AG2-330 GEN
Solar/Wind Harmer
35.487
270043AE2-236 GEN
Solar/Wind Harmer
8.538
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
10.397
274772LINCOLN ;3U
Adder
15.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
31.641
944531AF1-118 GEN
Solar/Wind Harmer
55.84
274752CRETE EC ;2U
Adder
14.685
274753CRETE EC ;3U
Adder
14.685
970031AG2-029 GEN
Solar/Wind Harmer
8.073
247604X1-042
Adder
0.74
970707AG2-453 GEN
Solar/Wind Harmer
40.394
274802UNIV PARK;5U
Adder
10.281
274826FISK ;BP
Adder
19.304
276806AD2-047 C O1
Solar/Wind Harmer
6.965
970941AG2-585 GEN
Solar/Wind Harmer
15.363
274800UNIV PARK;3U
Adder
10.269
972038AH1-567 GEN2
Adder
0.643
972228AH1-698 GEN2
Adder
6.522
276897AD1-100 C
Solar/Wind Harmer
0.016
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
51.668
274730ELWOOD EC;6P
Adder
28.626
274734ELWOOD EC;8P
Adder
28.626
274736ELWOOD EC;9P
Adder
28.626
274729ELWOOD EC;1P
Adder
28.625
276893AG1-478 C
Solar/Wind Harmer
0.481
943121AE2-341 GEN
Solar/Wind Harmer
20.258
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274746AC1-111 G10
Adder
9.659
274744AC1-111 GEN8
Adder
9.659
270536AF1-215 GEN2
Solar/Wind Harmer
0.015
971177AH1-047 GEN
Solar/Wind Harmer
7.198
276868AE1-113 GEN
Solar/Wind Harmer
2.341
276882AE2-255 GEN
Solar/Wind Harmer
1.364
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
4.532
971411AH1-196 GEN
Solar/Wind Harmer
17.431
971549AH1-272 GEN
Solar/Wind Harmer
23.961
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
23.073
274823ROCKFORD ;21
Adder
32.096
971611AH1-305 GEN
Solar/Wind Harmer
6.79
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
1.931
970169AG2-114 GEN
Solar/Wind Harmer
11.331
971681AH1-341 GEN
Solar/Wind Harmer
18.233
961011AF2-392 GEN
Solar/Wind Harmer
6.56
957751AF2-069 GEN
Solar/Wind Harmer
0.366
965101AG1-375 GEN
Solar/Wind Harmer
11.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
11.407
941731AE2-173 GEN
Solar/Wind Harmer
9.053
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.04
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
13.932
963841AG1-237 GEN
Solar/Wind Harmer
4.358
965041AG1-368 GEN
Solar/Wind Harmer
10.015
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.361
970289AG2-191 GEN
Solar/Wind Harmer
1.856
971609AH1-304 GEN
Solar/Wind Harmer
1.589
270594AE1-207 GEN
Solar/Wind Harmer
10.691
965051AG1-369 GEN
Solar/Wind Harmer
4.577
270024AE2-089 GEN
Solar/Wind Harmer
0.01
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.587
944221AF1-090 GEN
Solar/Wind Harmer
5.246
270240V3-007_GEN2
Solar/Wind Harmer
0.002
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.91
270543AE2-219 C
Solar/Wind Harmer
0.004
971029AG2-637 GEN
Solar/Wind Harmer
9.925
971673AH1-337 GEN
Solar/Wind Harmer
4.175
957471AF2-041 GEN
Solar/Wind Harmer
34.609
959081AF2-199 GEN
Solar/Wind Harmer
11.536
971067AG2-660 GEN
Solar/Wind Harmer
3.845
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
32.33
972235AH1-702 GEN1
Adder
4.141
970819AG2-516 GEN
Solar/Wind Harmer
13.704
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
14.256
971475AH1-234 GEN
Solar/Wind Harmer
5.525
970569AG2-363 GEN
Solar/Wind Harmer
34.072
965651AG1-433 GEN
Solar/Wind Harmer
3.31
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
15.031
274766LEE CO EC;7U
Adder
14.854
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.37
958861AF2-177 GEN
Solar/Wind Harmer
4.768
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
15.209
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
945371AF1-202 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
944231AF1-091 GEN
Solar/Wind Harmer
2.757
972175AH1-670 GEN
Solar/Wind Harmer
8.498
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.857
970291AG2-192 GEN
Solar/Wind Harmer
1.27
276615X2-022 GEN
Solar/Wind Harmer
0.102
963741AG1-226 GEN
Solar/Wind Harmer
23.062
270032AE2-172
Solar/Wind Harmer
6.364
965911AG1-460 GEN
Solar/Wind Harmer
1.873
276903AD2-071 C
Solar/Wind Harmer
10.292
270005AE1-210 C O1
Solar/Wind Harmer
1.994
965031AG1-367 GEN
Solar/Wind Harmer
9.202
247521TR3_G114
Solar/Wind Harmer
0.334
270246TR4_N_V150
Solar/Wind Harmer
0.059
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.164
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.065
24728605AND G2
Adder
4.198
247536S-71 GEN
Solar/Wind Harmer
0.307
965421AG1-410 GEN
Solar/Wind Harmer
22.83
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
970333AG2-219 GEN
Solar/Wind Harmer
5.143
246936BC-WTG1
Solar/Wind Harmer
0.291
270489AE1-102 GEN1
Solar/Wind Harmer
0.934
970773AG2-487 GEN
Solar/Wind Harmer
1.226
270349AD2-093_GEN
Solar/Wind Helper
1.564
943591AF1-030 GEN
Solar/Wind Harmer
13.472
270535AF1-215 GEN1
Solar/Wind Harmer
0.015
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
30.6
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.431
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.24
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.128
965021AG1-366 GEN
Solar/Wind Harmer
3.871
959091AF2-200 GEN
Solar/Wind Harmer
23.073
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.601
970571AG2-364 GEN
Solar/Wind Harmer
22.715
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
15.031
274767LEE CO EC;8U
Adder
14.854
276157O29GEN1
Solar/Wind Harmer
1.797
274878BISHOP HL;2U
Solar/Wind Harmer
0.37
942111AE2-223 GEN
Solar/Wind Harmer
3.531
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
10.846
965931AG1-462 GEN
Solar/Wind Harmer
27.328
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
31.938
959611AF2-252 GEN
Solar/Wind Harmer
3.549
247642Z2-115 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.599
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
970289AG2-191 GEN
Solar/Wind Harmer
1.074
970291AG2-192 GEN
Solar/Wind Harmer
0.977
276621W2-048 GEN
Solar/Wind Harmer
0.492
276838X2-022 GEN2
Solar/Wind Harmer
0.549
942481AE2-261 GEN
Solar/Wind Harmer
27.997
958821AF2-173 GEN
Solar/Wind Harmer
12.883
270004AE1-209 GEN
Solar/Wind Harmer
1.994
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.059
971617AH1-308 GEN
Solar/Wind Harmer
7.545
946031AF1-268 GEN
Solar/Wind Harmer
8.268
970193AG2-126 GEN
Solar/Wind Harmer
13.029
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.308
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
8.781
24728505AND G1
Adder
4.198
970243AG2-164 GEN
Solar/Wind Harmer
4.208
970519AG2-331 GEN
Solar/Wind Harmer
18.702
970699AG2-449 GEN
Solar/Wind Harmer
1.798
270491AE1-102 GEN2
Solar/Wind Harmer
0.934
270356AE2-297 GEN
Solar/Wind Harmer
0.009
274888KELLY CRK;1U
Solar/Wind Harmer
0.722
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
17.698
274674JOLIET 9 ;6U
Adder
26.84
274847GR RIDGE ;BU
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
2.237
274695ROCKY RD ;2P
Adder
18.993
274693ROCKY RD ;1P
Adder
18.806
274697ROCKY RD ;3P
Adder
5.159
274696ROCKY RD ;4P
Adder
19.441
958481AF2-142 GEN
Solar/Wind Harmer
17.825
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.607
274683WAUKEGAN ;8U
Adder
35.828
274683WAUKEGAN ;8U
Adder
30.201
962691AG1-118 GEN
Solar/Wind Harmer
35.425
970921AG2-575 GEN
Solar/Wind Harmer
11.776
970921AG2-575 GEN
Solar/Wind Harmer
3.925
958491AF2-143 GEN
Solar/Wind Harmer
17.589
942991AE2-321 GEN
Solar/Wind Harmer
13.041
274879MINONK ;1U
Solar/Wind Harmer
0.492
970611AG2-400 GEN
Solar/Wind Harmer
11.612
970627AG2-408 GEN
Solar/Wind Harmer
3.484
971333AH1-146 GEN
Solar/Wind Harmer
23.223
971335AH1-147 GEN
Solar/Wind Harmer
23.223
971341AH1-150 GEN
Solar/Wind Harmer
23.073
971343AH1-151 GEN
Solar/Wind Harmer
23.073
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.269
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.415
944541AF1-119 GEN
Solar/Wind Harmer
0.756
960971AF2-388 GEN
Solar/Wind Harmer
6.621
274764LEE CO EC;5U
Adder
15.066
274765LEE CO EC;6U
Adder
15.066
274762LEE CO EC;3U
Adder
15.031
274763LEE CO EC;4U
Adder
14.889
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
6.653
276741O09 GEN1
Solar/Wind Harmer
0.396
276708O09 GEN2
Solar/Wind Harmer
0.396
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.436
276646AC1-214 GEN2
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.549
942221AE2-234 GEN
Solar/Wind Harmer
0.052
966841AG1-555 GEN
Solar/Wind Harmer
1.176
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
5.684
270599AE1-208 GEN
Solar/Wind Harmer
8.918
270031AE2-169
Solar/Wind Harmer
5.351
971613AH1-306 GEN
Solar/Wind Harmer
4.582
276916AD2-100_GEN
Solar/Wind Harmer
19.464
276911AD2-131_GEN
Solar/Wind Harmer
1.282
960441AF2-335 GEN
Solar/Wind Harmer
8.968
970825AG2-519 GEN
Solar/Wind Harmer
9.877
945391AF1-204 GEN
Solar/Wind Harmer
9.229
964611AG1-324 GEN
Solar/Wind Harmer
0.623
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.274
970623AG2-406 GEN
Solar/Wind Harmer
1.433
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.417
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.798
246938BC-WTG3
Solar/Wind Harmer
0.26
246937BC-WTG2
Solar/Wind Harmer
0.291
970883AG2-550 GEN
Solar/Wind Harmer
7.146
970885AG2-551 GEN
Solar/Wind Harmer
2.382
270471AD2-092_GEN
Solar/Wind Helper
1.564
944201AF1-088_MTX
Adder
123.107
957141AF2-008_MTX
Adder
33.614
NYPJM->LTFIMP_NY
CLTF
2.955
LGEELTFEXP_LGEE->PJM
CLTF
4
WECLTFEXP_WEC->PJM
CLTF
6.262
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.586
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.805
AG2-052LTFEXP_AG2-052->PJM
LTF
0.392
AH1-155LTFEXP_AH1-155->PJM
LTF
0.587
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
190.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.117
MECLTFEXP_MEC->PJM
CLTF
22.614
SIGELTFEXP_SIGE->PJM
CLTF
0.431
LAGNLTFEXP_LAGN->PJM
CLTF
12.118
TVALTFEXP_TVA->PJM
CLTF
4.605

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:7.57
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:9.2
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
CPLELTFEXP_CPLE->PJM
CLTF
7.791
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-3_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-3_#7222_05MALIS 765_1_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5856.89
MW Contribution:9.4
Bus #Bus NameTypeMW Contribution
24289405MTG1
50/50
11.329
243186AF1-051 GEN
50/50
12.367
24318705GVG2
50/50
11.512
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.756
24723205RIVRG3
Adder
34.405
24686105CER G3
Adder
14.787
24686505CER G6
Adder
14.768
971403AH1-188 GEN
Solar/Wind Harmer
16.066
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
24289405MTG1
50/50
11.329
24318705GVG2
50/50
11.512
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.756
24686205CER G4
Adder
14.71
24686405CER G5
Adder
14.651
270053AF1-130 C
Solar/Wind Harmer
2.615
970153AG2-106 GEN
Solar/Wind Harmer
27.615
970913AG2-568 GEN
Solar/Wind Harmer
8.49
971191AH1-055 GEN
Solar/Wind Harmer
26.405
960911AF2-382 GEN
Solar/Wind Harmer
7.681
972103AH1-617 GEN
Solar/Wind Harmer
20.328
971461AH1-227 GEN
Solar/Wind Harmer
5.14
270346AE1-212 GEN
Solar/Wind Harmer
8.194
970243AG2-164 GEN
Solar/Wind Harmer
5.292
970519AG2-331 GEN
Solar/Wind Harmer
23.519
970699AG2-449 GEN
Solar/Wind Harmer
2.261
943031AE2-326 GEN
Solar/Wind Harmer
4.718
971331AH1-145 GEN
Solar/Wind Harmer
11.446
247619Y1-049
Adder
0.52
972273AH1-721 GEN
Adder
100.06
970093AG2-073 GEN
Solar/Wind Harmer
8.384
966571AG1-526 GEN
Solar/Wind Harmer
18.569
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.188
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270399AC1-101 GEN
Solar/Wind Harmer
3.619
270400AC1-102 GEN
Solar/Wind Harmer
3.619
24477305BRIDGE
Adder
0.568
962771AG1-126 GEN
Solar/Wind Harmer
43.245
941621AE2-160 GEN
Adder
4.884
970281AG2-184 GEN
Solar/Wind Harmer
21.344
972143AH1-644 GEN
Solar/Wind Harmer
11.011
970273AG2-179 GEN
Solar/Wind Harmer
4.976
3429391JKCT 9G
Adder
9.882
958121AF2-106 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
4.111
972167AH1-666 GEN
Solar/Wind Harmer
6.57
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
9.558
962251AG1-071 GEN
Solar/Wind Harmer
5.114
970193AG2-126 GEN
Solar/Wind Harmer
12.225
25196008MFTGT1
Adder
1.556
24728705AND G3
Adder
9.226
24728505AND G1
Adder
4.411
970513AG2-328 GEN
Solar/Wind Harmer
3.475
970517AG2-330 GEN
Solar/Wind Harmer
20.852
942481AE2-261 GEN
Solar/Wind Harmer
23.934
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.999
958171AF2-111 GEN
Solar/Wind Harmer
19.994
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.684
276668AB2-070 GEN1
Solar/Wind Harmer
0.291
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.781
959611AF2-252 GEN
Solar/Wind Harmer
2.642
247642Z2-115 C
Solar/Wind Harmer
0.003
270356AE2-297 GEN
Solar/Wind Harmer
0.011
942111AE2-223 GEN
Solar/Wind Harmer
2.572
970289AG2-191 GEN
Solar/Wind Harmer
0.869
970291AG2-192 GEN
Solar/Wind Harmer
0.79
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
252510AF1-249 C
Solar/Wind Harmer
0.061
274878BISHOP HL;2U
Solar/Wind Harmer
0.264
25194608D.CRK4
Adder
1.851
965931AG1-462 GEN
Solar/Wind Harmer
20.02
270437AC2-090 C
Solar/Wind Harmer
0.003
964401AG1-302 GEN
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
1.269
970571AG2-364 GEN
Solar/Wind Harmer
15.689
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.448
274767LEE CO EC;8U
Adder
10.325
25196608WSDLE5
Adder
9.621
972236AH1-702 GEN2
Adder
2.459
959091AF2-200 GEN
Solar/Wind Harmer
15.658
274855GSG-6 ;RU
Solar/Wind Harmer
0.287
274850MENDOTA H;RU
Solar/Wind Harmer
0.092
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.14
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.835
274872LEEDK;1U
Solar/Wind Harmer
0.287
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
20.129
274772LINCOLN ;3U
Adder
9.447
237048AF1-022 C
Solar/Wind Helper
0.191
237043AE2-125 C
Solar/Wind Helper
0.174
235058AG1-386 C
Solar/Wind Helper
0.436
23750701CROSSCHOOL
Solar/Wind Helper
1.181
964991AG1-363 GEN
Solar/Wind Helper
3.632
202652Y1-033 WT C
Solar/Wind Helper
0.547
238118U2-030_1
Solar/Wind Helper
0.284
254305AE2-115 C
Solar/Wind Helper
0.203
20089126CSLMN_L13
Solar/Wind Helper
0.571
20089026BF_G21_K23
Solar/Wind Helper
0.452
238127S14_GEN_2
Solar/Wind Helper
0.669
203818AF1-086 GEN
Solar/Wind Helper
1.58
943121AE2-341 GEN
Solar/Wind Harmer
12.241
943591AF1-030 GEN
Solar/Wind Harmer
8.14
970947AG2-589 GEN
Solar/Wind Harmer
0.379
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
962761AG1-125 GEN
Solar/Wind Harmer
43.245
970149AG2-104 GEN
Solar/Wind Harmer
46.706
970155AG2-107 GEN
Solar/Wind Harmer
27.615
971315AH1-136 GEN
Solar/Wind Harmer
2.04
24728305BUCHG2
Adder
6.555
971687AH1-348 GEN
Solar/Wind Harmer
1.002
24735205WLF2G2
Adder
7.624
927014AC1-188 GEN
Solar/Wind Harmer
0.005
970333AG2-219 GEN
Solar/Wind Harmer
6.468
970091AG2-072 GEN
Adder
99.087
971329AH1-144 GEN
Solar/Wind Harmer
7.211
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971821AH1-427 GEN
Solar/Wind Harmer
8.366
971565AH1-281 GEN
Solar/Wind Harmer
1.67
3429241JKCT 3G
Adder
14.135
970273AG2-179 GEN
Solar/Wind Harmer
2.902
3429421JKCT 10G
Adder
9.882
339216AC1-074 GEN
Solar/Wind Harmer
0.225
945681AF1-233 GEN
Solar/Wind Harmer
15.497
964901AG1-354 GEN
Solar/Wind Harmer
12.33
962241AG1-070 GEN
Solar/Wind Harmer
4.459
963741AG1-226 GEN
Solar/Wind Harmer
19.126
25196008MFTGT1
Adder
1.607
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
252507AC2-088 GEN
Solar/Wind Harmer
0.365
24728605AND G2
Adder
4.411
970245AG2-165 GEN
Solar/Wind Harmer
3.475
965911AG1-460 GEN
Solar/Wind Harmer
1.601
24791305MDL-5G
Solar/Wind Harmer
0.001
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.111
274880W4-005 GEN4
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
6.574
25196808ZIMRHP
Adder
86.412
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
970773AG2-487 GEN
Solar/Wind Harmer
1.4
276726Z2-087_GEN
Solar/Wind Harmer
0.003
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
939741AE1-205 GEN
Solar/Wind Harmer
11.079
971605AH1-302 GEN
Solar/Wind Harmer
9.892
276903AD2-071 C
Solar/Wind Harmer
8.823
970291AG2-192 GEN
Solar/Wind Harmer
1.027
270032AE2-172
Solar/Wind Harmer
5.246
274877BISHOP HL;1U
Solar/Wind Harmer
0.264
25194608D.CRK4
Adder
1.851
939401AE1-172 GEN
Solar/Wind Harmer
5.873
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.207
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.756
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
23.534
971997AH1-543 GEN
Solar/Wind Harmer
4.113
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.448
274766LEE CO EC;7U
Adder
10.325
276901AD2-066 C O1
Solar/Wind Harmer
0.008
971475AH1-234 GEN
Solar/Wind Harmer
3.8
970819AG2-516 GEN
Solar/Wind Harmer
9.396
972235AH1-702 GEN1
Adder
2.828
957471AF2-041 GEN
Solar/Wind Harmer
23.486
959081AF2-199 GEN
Solar/Wind Harmer
7.829
971067AG2-660 GEN
Solar/Wind Harmer
2.61
274822ROCKFORD ;11
Adder
22.02
276861AD2-134 GEN
Solar/Wind Harmer
0.14
274872LEEDK;1U
Solar/Wind Harmer
0.005
962781AG1-127 GEN
Solar/Wind Harmer
7.445
274745AC1-111 GEN9
Adder
6.26
274682WAUKEGAN ;7U
Adder
20.129
274828WAUKEGAN ;BP
Adder
12.373
274773LINCOLN ;4U
Adder
9.447
274774LINCOLN ;5U
Adder
9.447
237046AF1-021 C
Solar/Wind Helper
0.484
238185AF2-356 C
Solar/Wind Helper
2.169
23751201ROTHROCK
Solar/Wind Helper
0.732
235054AD2-180 GEN
Solar/Wind Helper
1.687
23562501BACKB
Solar/Wind Helper
0.892
254303AC2-168 GEN
Solar/Wind Helper
0.147
238117U2-030
Solar/Wind Helper
0.284
241966AE1-183 GEN
Solar/Wind Helper
0.238
20089226LOOKOUT
Solar/Wind Helper
0.556
235531U2-073 GEN
Solar/Wind Helper
2.67
23751101LEADS_P59
Solar/Wind Helper
1.234
20088826HIGHLAND
Solar/Wind Helper
0.845
20094526CT_V3-030
Solar/Wind Helper
0.443
964201AG1-281 GEN
Solar/Wind Helper
0.454
238108AE1-109 GEN1
Solar/Wind Helper
0.084
971313AH1-133 GEN
Solar/Wind Harmer
9.994
270132AB1-180 C
Adder
0.166
24734705WLF1G3
Adder
7.759
24734805WLF1G4
Adder
7.759
24734905WLF1G5
Adder
7.759
971061AG2-657 GEN
Solar/Wind Harmer
5.861
971985AH1-537 GEN
Solar/Wind Harmer
2.765
24735105WLF2G1
Adder
7.624
966391AG1-508 GEN
Solar/Wind Harmer
1.393
971981AH1-535 GEN
Solar/Wind Harmer
5.649
965401AG1-405 GEN
Solar/Wind Harmer
4.782
965411AG1-406 GEN
Solar/Wind Harmer
3.076
339211AE2-254 GEN
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
5.553
3429211JKCT 2G
Adder
13.952
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
9.178
972165AH1-665 GEN
Solar/Wind Harmer
7.351
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
3.493
25196108MFTGT2
Adder
1.772
25196108MFTGT2
Adder
1.645
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
4.714
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.291
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
970879AG2-548 GEN
Solar/Wind Harmer
7.141
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.309
941731AE2-173 GEN
Solar/Wind Harmer
6.595
971611AH1-305 GEN
Solar/Wind Harmer
4.711
970289AG2-191 GEN
Solar/Wind Harmer
1.501
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
7.879
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
8.813
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.259
926823AC1-168 GEN
Solar/Wind Harmer
1.335
946321AF1-296 GEN
Solar/Wind Harmer
4.396
270240V3-007_GEN2
Solar/Wind Harmer
0.002
961011AF2-392 GEN
Solar/Wind Harmer
4.599
971681AH1-341 GEN
Solar/Wind Harmer
12.614
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.904
25196308WSDLE2
Adder
9.818
25196208WSDLE1
Adder
9.794
25196708WSDLE6
Adder
9.769
25196508WSDLE4
Adder
9.523
276612AE2-035 GEN
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.571
276882AE2-255 GEN
Solar/Wind Harmer
0.915
971171AH1-044 GEN
Solar/Wind Harmer
15.658
274823ROCKFORD ;21
Adder
21.86
971675AH1-338 GEN
Solar/Wind Harmer
3.053
971411AH1-196 GEN
Solar/Wind Harmer
11.736
971177AH1-047 GEN
Solar/Wind Harmer
4.824
274746AC1-111 G10
Adder
6.26
274744AC1-111 GEN8
Adder
6.26
274775LINCOLN ;6U
Adder
9.447
274776LINCOLN ;7U
Adder
1.661
23750501ELLIOTTS
Solar/Wind Helper
0.66
254304AE2-114 C
Solar/Wind Helper
0.203
241997AF1-093 GEN
Solar/Wind Helper
0.238
241982AE2-343 S C
Solar/Wind Helper
0.207
238126S14_GEN_1
Solar/Wind Helper
0.669
20092526R32
Solar/Wind Helper
1.095
203961AE2-224 GEN
Solar/Wind Helper
2.258
20091526CHSTN_FL
Solar/Wind Helper
0.546
20090526Q36
Solar/Wind Helper
0.975
203993AD2-133_GEN1
Solar/Wind Helper
0.975
203846AF2-130 C
Solar/Wind Helper
0.42
238109AE1-109 GEN2
Solar/Wind Helper
0.084
238110AE1-109 GEN3
Solar/Wind Helper
0.084
941231AE2-117 GEN
Solar/Wind Helper
0.441
243186AF1-051 GEN
50/50
12.367
24723005RIVRG1
Adder
34.405
24723105RIVRG2
Adder
34.405
24685805CER G1
Adder
14.69
24685905CER G2
Adder
14.69
944971AF1-162 GEN
Solar/Wind Harmer
11.585
24728205BUCHG1
Adder
6.555
971225AH1-072 GEN
Solar/Wind Harmer
2.004
971227AH1-073 GEN
Solar/Wind Harmer
2.004
970239AG2-162 GEN
Solar/Wind Harmer
2.261
971277AH1-098 GEN
Solar/Wind Harmer
3.569
960161AF2-307 GEN
Solar/Wind Harmer
5.717
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.207
942891AE2-308 GEN
Solar/Wind Harmer
8.355
970235AG2-159 GEN
Solar/Wind Harmer
5.075
970235AG2-159 GEN
Solar/Wind Harmer
2.912
964571AG1-320 GEN
Solar/Wind Harmer
7.59
970653AG2-424 GEN
Solar/Wind Harmer
4.005
970653AG2-424 GEN
Solar/Wind Harmer
2.075
270186AC1-089 GEN
Solar/Wind Harmer
0.005
972043AH1-570 GEN
Solar/Wind Harmer
2.155
972045AH1-571 GEN
Solar/Wind Harmer
1.727
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971081AG2-670 GEN
Solar/Wind Harmer
6.201
270583AD2-179 GEN
Solar/Wind Harmer
8.263
971125AH1-004 GEN
Solar/Wind Harmer
3.305
970107AG2-081 GEN
Solar/Wind Harmer
2.479
966021AG1-471 GEN
Solar/Wind Harmer
4.451
971485AH1-239 GEN
Solar/Wind Harmer
6.59
339255AE2-071 GEN
Solar/Wind Harmer
-0.134
964781AG1-341 GEN
Solar/Wind Harmer
8.684
945391AF1-204 GEN
Solar/Wind Harmer
8.659
962581AG1-107 GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
4.714
966841AG1-555 GEN
Solar/Wind Harmer
0.91
252509AD1-136 GEN
Solar/Wind Harmer
0.041
970321AG2-212 GEN
Solar/Wind Harmer
3.475
276916AD2-100_GEN
Solar/Wind Harmer
16.824
276911AD2-131_GEN
Solar/Wind Harmer
1.108
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
971073AG2-665 GEN
Solar/Wind Harmer
7.141
960611AF2-352 GEN
Solar/Wind Harmer
2.642
971613AH1-306 GEN
Solar/Wind Harmer
3.777
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.309
276646AC1-214 GEN2
Solar/Wind Harmer
0.309
25194408D.CRK1
Adder
8.517
25194508D.CRK3
Adder
1.592
252519AF1-045_GEN
Solar/Wind Harmer
6.83
252516AE2-318_GEN
Solar/Wind Harmer
6.058
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
276741O09 GEN1
Solar/Wind Harmer
0.279
276708O09 GEN2
Solar/Wind Harmer
0.279
972267AH1-718 GEN
Adder
4.679
276603SUBLETTE C
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274764LEE CO EC;5U
Adder
10.473
274765LEE CO EC;6U
Adder
10.473
274762LEE CO EC;3U
Adder
10.448
274763LEE CO EC;4U
Adder
10.35
938861AE1-114 GEN
Solar/Wind Harmer
4.439
274856ECOGROVE ;U1
Solar/Wind Harmer
0.185
276611AD2-172 GEN
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.33
971341AH1-150 GEN
Solar/Wind Harmer
15.658
971343AH1-151 GEN
Solar/Wind Harmer
15.658
971333AH1-146 GEN
Solar/Wind Harmer
15.65
971335AH1-147 GEN
Solar/Wind Harmer
15.65
958491AF2-143 GEN
Solar/Wind Harmer
11.735
942991AE2-321 GEN
Solar/Wind Harmer
8.735
970921AG2-575 GEN
Solar/Wind Harmer
7.823
970921AG2-575 GEN
Solar/Wind Harmer
2.608
962691AG1-118 GEN
Solar/Wind Harmer
23.465
971573AH1-285 GEN
Solar/Wind Harmer
1.457
274696ROCKY RD ;4P
Adder
12.769
274695ROCKY RD ;2P
Adder
12.475
274693ROCKY RD ;1P
Adder
12.352
274697ROCKY RD ;3P
Adder
3.389
274683WAUKEGAN ;8U
Adder
23.604
274683WAUKEGAN ;8U
Adder
19.897
274770LINCOLN ;1U
Adder
9.447
274771LINCOLN ;2U
Adder
9.447
23652301WDPWR_K20
Solar/Wind Helper
0.141
23585401KL_K28_T16
Solar/Wind Helper
1.274
203955AF1-039 C O1
Solar/Wind Helper
0.36
962101AG1-054 GEN
Solar/Wind Helper
0.609
241985AE1-237 GEN
Solar/Wind Helper
0.231
241967AE2-285_GEN
Solar/Wind Helper
0.593
241801AE1-079 GEN
Solar/Wind Helper
0.231
944781AF1-143 GEN
Solar/Wind Helper
2.369
238120AE2-309 GEN
Solar/Wind Helper
0.419
20083426SW_E13_K22
Solar/Wind Helper
0.053
946071AF1-272 GEN
Solar/Wind Helper
2.555
20088926STNY CRK
Solar/Wind Helper
0.775
20084626FORWARD
Solar/Wind Helper
0.336
203940AF1-140 C
Solar/Wind Helper
0.373
20088626ARWF_N39
Solar/Wind Helper
1.136
20303426NA_O38_P22
Solar/Wind Helper
0.931
203853AF1-134 C O1
Solar/Wind Helper
0.446
946381AF1-302 GEN
Solar/Wind Helper
0.207
203952AE2-129 C
Solar/Wind Helper
0.442
203946AE2-131 C
Solar/Wind Helper
0.442
944201AF1-088_MTX
Adder
141.066
957141AF2-008_MTX
Adder
70.533
NYPJM->LTFIMP_NY
CLTF
5.171
LGEELTFEXP_LGEE->PJM
CLTF
8.351
WECLTFEXP_WEC->PJM
CLTF
4.291
CPLELTFEXP_CPLE->PJM
CLTF
6.692
CBM West 2LTFEXP_CBM-W2->PJM
CBM
152.177
AG2-052LTFEXP_AG2-052->PJM
LTF
0.261
AH1-155LTFEXP_AH1-155->PJM
LTF
0.391
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.051
CBM South 1LTFEXP_CBM-S1->PJM
CBM
43.304
MECLTFEXP_MEC->PJM
CLTF
18.986
SIGELTFEXP_SIGE->PJM
CLTF
0.624
LAGNLTFEXP_LAGN->PJM
CLTF
22.306
CBM South 2LTFEXP_CBM-S2->PJM
CBM
24.638
TVALTFEXP_TVA->PJM
CLTF
11.394

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.35 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2472.27
MW Contribution:5.74
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
960851AF2-376 GEN
50/50
2.105
24641605TWIN BRNCH
50/50
0.015
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
22.101
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.07 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3439.74
MW Contribution:8.5
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
12.697
970627AG2-408 GEN
Solar/Wind Harmer
3.809
944541AF1-119 GEN
Solar/Wind Harmer
0.831
960971AF2-388 GEN
Solar/Wind Harmer
7.274
942221AE2-234 GEN
Solar/Wind Harmer
0.055
270599AE1-208 GEN
Solar/Wind Harmer
9.209
270031AE2-169
Solar/Wind Harmer
5.525
270216AD2-079_GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
9.138
970825AG2-519 GEN
Solar/Wind Harmer
10.102
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
17.858
961051AF2-396 GEN
Solar/Wind Harmer
11.905
971613AH1-306 GEN
Solar/Wind Harmer
4.228
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.561
965681AG1-436 GEN
Solar/Wind Harmer
10.414
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
0.3
246937BC-WTG2
Solar/Wind Harmer
0.336
270007AE1-245 C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
9.237
274771LINCOLN ;2U
Adder
9.237
970321AG2-212 GEN
Solar/Wind Harmer
3.303
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
274887GEN-1.85
Solar/Wind Harmer
0.2
276843GEN-1.7
Solar/Wind Harmer
0.246
958011AF2-095 GEN
Solar/Wind Harmer
10.963
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
7.476
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
958481AF2-142 GEN
Solar/Wind Harmer
11.087
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1
971573AH1-285 GEN
Solar/Wind Harmer
1.373
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
25.362
965101AG1-375 GEN
Solar/Wind Harmer
12.025
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
14.93
965041AG1-368 GEN
Solar/Wind Harmer
10.949
965051AG1-369 GEN
Solar/Wind Harmer
5.056
971609AH1-304 GEN
Solar/Wind Harmer
1.641
270024AE2-089 GEN
Solar/Wind Harmer
0.01
970115AG2-085 GEN
Solar/Wind Harmer
3.655
971771AH1-392 GEN
Solar/Wind Harmer
8.953
971619AH1-309 GEN
Solar/Wind Harmer
4.017
270594AE1-207 GEN
Solar/Wind Harmer
9.866
971347AH1-153 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
1.658
270240V3-007_GEN2
Solar/Wind Harmer
0.003
971769AH1-391 GEN
Solar/Wind Harmer
9.572
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.048
247607V1-011 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
16.964
270536AF1-215 GEN2
Solar/Wind Harmer
0.01
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
9.237
274776LINCOLN ;7U
Adder
9.237
274777LINCOLN ;8U
Adder
9.237
960591AF2-350 GEN
Solar/Wind Harmer
7.613
972227AH1-698 GEN1
Adder
2.835
971611AH1-305 GEN
Solar/Wind Harmer
4.511
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
0.005
970833AG2-524 GEN
Solar/Wind Harmer
8.217
970833AG2-524 GEN
Solar/Wind Harmer
5.478
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276868AE1-113 GEN
Solar/Wind Harmer
1.457
276882AE2-255 GEN
Solar/Wind Harmer
0.849
971177AH1-047 GEN
Solar/Wind Harmer
4.45
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
10.784
971675AH1-338 GEN
Solar/Wind Harmer
2.801
971171AH1-044 GEN
Solar/Wind Harmer
14.285
274823ROCKFORD ;21
Adder
19.887
970169AG2-114 GEN
Solar/Wind Harmer
7.099
926823AC1-168 GEN
Solar/Wind Harmer
1.205
276612AE2-035 GEN
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
11.326
961011AF2-392 GEN
Solar/Wind Harmer
4.084
957751AF2-069 GEN
Solar/Wind Harmer
0.229
971029AG2-637 GEN
Solar/Wind Harmer
10.391
276655WTG1_EQ
Solar/Wind Harmer
0.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.234
941731AE2-173 GEN
Solar/Wind Harmer
5.741
963841AG1-237 GEN
Solar/Wind Harmer
2.984
946321AF1-296 GEN
Solar/Wind Harmer
3.782
971673AH1-337 GEN
Solar/Wind Harmer
4.373
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.236
276848AB2-070 GEN3
Solar/Wind Harmer
0.235
944221AF1-090 GEN
Solar/Wind Harmer
3.489
270297AD1-101 GEN
Solar/Wind Harmer
0.001
945411AF1-206 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
0.778
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
960861AF2-377 GEN
50/50
3.377
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.046
965011AG1-365 GEN
Solar/Wind Harmer
12.697
965651AG1-433 GEN
Solar/Wind Harmer
3.637
958861AF2-177 GEN
Solar/Wind Harmer
5.211
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.856
270063AE2-323 C
Solar/Wind Harmer
0.009
247521TR3_G114
Solar/Wind Harmer
0.369
270246TR4_N_V150
Solar/Wind Harmer
0.065
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.091
965031AG1-367 GEN
Solar/Wind Harmer
9.65
970825AG2-519 GEN
Solar/Wind Harmer
3.236
945111AF1-176 GEN
Solar/Wind Harmer
16.201
270505AE1-170 C O1
Solar/Wind Harmer
9.372
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.135
965421AG1-410 GEN
Solar/Wind Harmer
26.1
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.336
276903AD2-071 C
Solar/Wind Harmer
9.392
246936BC-WTG1
Solar/Wind Harmer
0.336
270489AE1-102 GEN1
Solar/Wind Harmer
1.076
970373AG2-245 GEN
Solar/Wind Harmer
16.85
247536S-71 GEN
Solar/Wind Harmer
0.321
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274751CRETE EC ;1U
Adder
9.273
274754CRETE EC ;4U
Adder
9.273
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
9.237
274774LINCOLN ;5U
Adder
9.237
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
3.303
276776AD2-060 GEN
Solar/Wind Harmer
0.795
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.936
276691AA1-018 GEN1
Solar/Wind Harmer
0.895
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
24791305MDL-5G
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
5.451
276901AD2-066 C O1
Solar/Wind Harmer
0.007
962781AG1-127 GEN
Solar/Wind Harmer
6.91
274872LEEDK;1U
Solar/Wind Harmer
0.004
971997AH1-543 GEN
Solar/Wind Harmer
3.793
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.129
957471AF2-041 GEN
Solar/Wind Harmer
21.427
959081AF2-199 GEN
Solar/Wind Harmer
7.142
971067AG2-660 GEN
Solar/Wind Harmer
2.381
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
970569AG2-363 GEN
Solar/Wind Harmer
21.31
970819AG2-516 GEN
Solar/Wind Harmer
8.5
971475AH1-234 GEN
Solar/Wind Harmer
3.428
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.645
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24728605AND G2
Adder
3.7
963741AG1-226 GEN
Solar/Wind Harmer
15.923
970773AG2-487 GEN
Solar/Wind Harmer
1.185
972175AH1-670 GEN
Solar/Wind Harmer
5.466
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.507
276615X2-022 GEN
Solar/Wind Harmer
0.067
965911AG1-460 GEN
Solar/Wind Harmer
1.231
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
3.324
241808AF1-120 C
Solar/Wind Harmer
0.001
241858AF1-205_GEN
Solar/Wind Harmer
1.342
241840AF1-064_GEN
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Helper
1.077
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
958491AF2-143 GEN
Solar/Wind Harmer
10.958
962691AG1-118 GEN
Solar/Wind Harmer
21.835
970921AG2-575 GEN
Solar/Wind Harmer
7.261
970921AG2-575 GEN
Solar/Wind Harmer
2.42
274879MINONK ;1U
Solar/Wind Harmer
0.306
942991AE2-321 GEN
Solar/Wind Harmer
8.062
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
14.365
971335AH1-147 GEN
Solar/Wind Harmer
14.365
971341AH1-150 GEN
Solar/Wind Harmer
14.285
971343AH1-151 GEN
Solar/Wind Harmer
14.285
274856ECOGROVE ;U1
Solar/Wind Harmer
0.167
276611AD2-172 GEN
Solar/Wind Harmer
0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.798
938861AE1-114 GEN
Solar/Wind Harmer
3.985
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
276603SUBLETTE C
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.273
276646AC1-214 GEN2
Solar/Wind Harmer
0.273
972267AH1-718 GEN
Adder
4.143
276741O09 GEN1
Solar/Wind Harmer
0.247
276708O09 GEN2
Solar/Wind Harmer
0.247
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.261
970241AG2-163 GEN
Solar/Wind Harmer
3.925
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
6.577
276916AD2-100_GEN
Solar/Wind Harmer
12.826
276911AD2-131_GEN
Solar/Wind Harmer
0.845
970621AG2-405 GEN
Solar/Wind Harmer
1.049
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.833
970239AG2-162 GEN
Solar/Wind Harmer
1.162
241996AE2-282_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
62.505
270043AE2-236 GEN
Solar/Wind Harmer
8.778
959331AF2-224 GEN
Solar/Wind Harmer
8.888
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
7.468
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.065
958821AF2-173 GEN
Solar/Wind Harmer
13.51
270004AE1-209 GEN
Solar/Wind Harmer
2.091
971617AH1-308 GEN
Solar/Wind Harmer
7.972
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
8.54
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.871
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.076
270535AF1-215 GEN1
Solar/Wind Harmer
0.01
274752CRETE EC ;2U
Adder
9.273
274753CRETE EC ;3U
Adder
9.273
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274772LINCOLN ;3U
Adder
9.237
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
3.303
970517AG2-330 GEN
Solar/Wind Harmer
19.816
276806AD2-047 C O1
Solar/Wind Harmer
4.314
970941AG2-585 GEN
Solar/Wind Harmer
9.516
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
24.591
276893AG1-478 C
Solar/Wind Harmer
0.298
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
943121AE2-341 GEN
Solar/Wind Harmer
12.419
943591AF1-030 GEN
Solar/Wind Harmer
8.259
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.895
276805AD2-038 GEN
Solar/Wind Harmer
0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.294
274872LEEDK;1U
Solar/Wind Harmer
0.266
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.766
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.263
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.129
959091AF2-200 GEN
Solar/Wind Harmer
14.285
972236AH1-702 GEN2
Adder
2.232
970571AG2-364 GEN
Solar/Wind Harmer
14.206
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
276157O29GEN1
Solar/Wind Harmer
1.121
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
942111AE2-223 GEN
Solar/Wind Harmer
2.239
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
20.348
959611AF2-252 GEN
Solar/Wind Harmer
2.261
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
965931AG1-462 GEN
Solar/Wind Harmer
17.128
270356AE2-297 GEN
Solar/Wind Harmer
0.009
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.985
276668AB2-070 GEN1
Solar/Wind Harmer
0.236
276621W2-048 GEN
Solar/Wind Harmer
0.321
276838X2-022 GEN2
Solar/Wind Harmer
0.358
970193AG2-126 GEN
Solar/Wind Harmer
9.285
942481AE2-261 GEN
Solar/Wind Harmer
18.401
270222AC2-111 GEN
Solar/Wind Harmer
2.367
970243AG2-164 GEN
Solar/Wind Harmer
2.719
970519AG2-331 GEN
Solar/Wind Harmer
12.086
970699AG2-449 GEN
Solar/Wind Harmer
1.162
270541AE2-072 C
Solar/Wind Harmer
0.005
241832AE2-181_GEN
Solar/Wind Harmer
0.001
958321AF2-126 GEN
Solar/Wind Harmer
0.444
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
29.672
990792J1392
External Queue
6.540774822235107
991297J1743
External Queue
3.431180715560913
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6022.77
MW Contribution:15.55
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5781.3
MW Contribution:14.7
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.23 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2739.4
MW Contribution:3.92
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.157
24726605LAWG1S
50/50
5.152
24726705LAWG2A
50/50
3.467
24726505LAWG1B
50/50
3.443
24726805LAWG2B
50/50
3.432
24729505KEY G4
50/50
6.086
270240V3-007_GEN2
Solar/Wind Harmer
0.003
945581AF1-223 GEN
Solar/Wind Harmer
0.001
965101AG1-375 GEN
Solar/Wind Harmer
7.011
970115AG2-085 GEN
Solar/Wind Harmer
2.799
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.048
270594AE1-207 GEN
Solar/Wind Harmer
6.851
970289AG2-191 GEN
Solar/Wind Harmer
1.096
270024AE2-089 GEN
Solar/Wind Harmer
0.005
270543AE2-219 C
Solar/Wind Harmer
0.003
270071AF1-092 GEN
Solar/Wind Harmer
7.808
971029AG2-637 GEN
Solar/Wind Harmer
5.775
963841AG1-237 GEN
Solar/Wind Harmer
1.631
963791AG1-232 GEN
Solar/Wind Harmer
5.031
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
971673AH1-337 GEN
Solar/Wind Harmer
2.397
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.115
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.125
276848AB2-070 GEN3
Solar/Wind Harmer
0.125
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.6
941731AE2-173 GEN
Solar/Wind Harmer
2.857
971347AH1-153 GEN
Solar/Wind Harmer
5.141
970169AG2-114 GEN
Solar/Wind Harmer
3.406
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274775LINCOLN ;6U
Adder
4.104
274776LINCOLN ;7U
Adder
4.104
274777LINCOLN ;8U
Adder
4.104
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.263
944221AF1-090 GEN
Solar/Wind Harmer
1.982
960591AF2-350 GEN
Solar/Wind Harmer
3.378
274814UNIV PK N;0U
Adder
2.444
274807UNIV PK N;3U
Adder
2.439
274805UNIV PK N;1U
Adder
2.428
274811UNIV PK N;7U
Adder
2.423
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.748
970833AG2-524 GEN
Solar/Wind Harmer
3.704
970833AG2-524 GEN
Solar/Wind Harmer
2.47
274731ELWOOD EC;2P
Adder
7.93
274733ELWOOD EC;3P
Adder
7.93
274735ELWOOD EC;4P
Adder
7.93
274728ELWOOD EC;5P
Adder
7.929
274687WILL CNTY;4U
Adder
13.464
274687WILL CNTY;4U
Adder
13.464
274675JOLIET 29;7U
Adder
14.777
274675JOLIET 29;7U
Adder
14.249
274746AC1-111 G10
Adder
2.679
274744AC1-111 GEN8
Adder
2.679
971769AH1-391 GEN
Solar/Wind Harmer
3.73
276868AE1-113 GEN
Solar/Wind Harmer
0.67
276882AE2-255 GEN
Solar/Wind Harmer
0.39
926823AC1-168 GEN
Solar/Wind Harmer
0.566
971771AH1-392 GEN
Solar/Wind Harmer
3.324
957751AF2-069 GEN
Solar/Wind Harmer
0.109
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
2.035
971675AH1-338 GEN
Solar/Wind Harmer
1.286
971411AH1-196 GEN
Solar/Wind Harmer
4.94
971171AH1-044 GEN
Solar/Wind Harmer
6.576
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.259
961011AF2-392 GEN
Solar/Wind Harmer
1.909
971619AH1-309 GEN
Solar/Wind Harmer
1.46
946321AF1-296 GEN
Solar/Wind Harmer
1.796
252524AE2-267 GEN
Solar/Wind Helper
1.054
241972AD1-140 GEN
Solar/Wind Helper
3.429
270367AC2-061_GEN
Solar/Wind Helper
1.955
253383AE2-342_GEN
Solar/Wind Helper
0.463
270340AC2-060 GEN
Solar/Wind Helper
1.177
945631AF1-228 GEN
Solar/Wind Helper
1.077
241973AD2-163_GEN1
Solar/Wind Helper
1.018
24726405LAWG1A
50/50
3.336
961171AF2-408 GEN
50/50
9.412
960791AF2-370 GEN
50/50
2.332
24728605AND G2
50/50
3.373
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.702
970773AG2-487 GEN
Solar/Wind Harmer
1.765
270005AE1-210 C O1
Solar/Wind Harmer
1.806
965031AG1-367 GEN
Solar/Wind Harmer
8.337
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.512
958861AF2-177 GEN
Solar/Wind Harmer
3.038
965651AG1-433 GEN
Solar/Wind Harmer
1.996
276903AD2-071 C
Solar/Wind Harmer
7.007
270032AE2-172
Solar/Wind Harmer
4.078
970291AG2-192 GEN
Solar/Wind Harmer
0.75
247536S-71 GEN
Solar/Wind Harmer
0.183
963741AG1-226 GEN
Solar/Wind Harmer
9.071
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.442
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.575
958381AF2-132 GEN
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
1.517
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
7.265
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.835
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.8
963831AG1-236 GEN
Solar/Wind Harmer
1.336
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276615X2-022 GEN
Solar/Wind Harmer
0.036
939401AE1-172 GEN
Solar/Wind Harmer
2.544
274773LINCOLN ;4U
Adder
4.104
274774LINCOLN ;5U
Adder
4.104
941551AE2-152 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.677
274723RIVER EC ;12
Adder
8.679
276776AD2-060 GEN
Solar/Wind Harmer
0.353
274751CRETE EC ;1U
Adder
3.99
274754CRETE EC ;4U
Adder
3.99
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.423
274801UNIV PARK;4U
Adder
2.818
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.929
274674JOLIET 9 ;6U
Adder
7.422
274676JOLIET 29;8U
Adder
14.777
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276691AA1-018 GEN1
Solar/Wind Harmer
0.406
971997AH1-543 GEN
Solar/Wind Harmer
1.755
274745AC1-111 GEN9
Adder
2.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
9.966
274682WAUKEGAN ;7U
Adder
8.557
274828WAUKEGAN ;BP
Adder
5.256
962781AG1-127 GEN
Solar/Wind Harmer
3.152
274872LEEDK;1U
Solar/Wind Harmer
0.002
970091AG2-072 GEN
Adder
34.24
276861AD2-134 GEN
Solar/Wind Harmer
0.059
274877BISHOP HL;1U
Solar/Wind Harmer
0.111
957471AF2-041 GEN
Solar/Wind Harmer
9.864
959081AF2-199 GEN
Solar/Wind Harmer
3.288
971067AG2-660 GEN
Solar/Wind Harmer
1.096
970819AG2-516 GEN
Solar/Wind Harmer
3.925
971475AH1-234 GEN
Solar/Wind Harmer
1.584
276158O29GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
3.407
945111AF1-176 GEN
Solar/Wind Harmer
5.786
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.673
970333AG2-219 GEN
Solar/Wind Harmer
2.279
252507AC2-088 GEN
Solar/Wind Helper
1.361
253343AC1-166 GEN
Solar/Wind Helper
0.58
253325AC1-069 GEN
Solar/Wind Helper
0.601
964351AG1-297 GEN
50/50
13.747
961161AF2-407 GEN
50/50
35.482
24728705AND G3
50/50
7.054
24728505AND G1
50/50
3.373
270437AC2-090 C
Solar/Wind Harmer
0.005
270356AE2-297 GEN
Solar/Wind Harmer
0.013
958821AF2-173 GEN
Solar/Wind Harmer
11.671
270004AE1-209 GEN
Solar/Wind Harmer
1.806
946031AF1-268 GEN
Solar/Wind Harmer
6.483
944531AF1-118 GEN
Solar/Wind Harmer
26.617
970289AG2-191 GEN
Solar/Wind Harmer
0.635
970291AG2-192 GEN
Solar/Wind Harmer
0.577
247642Z2-115 C
Solar/Wind Harmer
0.002
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.517
971617AH1-308 GEN
Solar/Wind Harmer
3.776
970193AG2-126 GEN
Solar/Wind Harmer
6.096
270043AE2-236 GEN
Solar/Wind Harmer
2.401
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.622
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.517
970517AG2-330 GEN
Solar/Wind Harmer
9.105
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.587
276668AB2-070 GEN1
Solar/Wind Harmer
0.125
942111AE2-223 GEN
Solar/Wind Harmer
1.114
970349AG2-230 GEN
Solar/Wind Harmer
5.141
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.269
959611AF2-252 GEN
Solar/Wind Harmer
1.141
276621W2-048 GEN
Solar/Wind Harmer
0.172
276838X2-022 GEN2
Solar/Wind Harmer
0.192
274772LINCOLN ;3U
Adder
4.104
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
10.124
274724RIVER EC ;11
Adder
8.577
972228AH1-698 GEN2
Adder
1.794
276806AD2-047 C O1
Solar/Wind Harmer
1.914
970941AG2-585 GEN
Solar/Wind Harmer
4.222
274752CRETE EC ;2U
Adder
3.99
274753CRETE EC ;3U
Adder
3.99
274802UNIV PARK;5U
Adder
2.819
274800UNIV PARK;3U
Adder
2.818
972038AH1-567 GEN2
Adder
0.176
274826FISK ;BP
Adder
5.288
970707AG2-453 GEN
Solar/Wind Harmer
11.009
276893AG1-478 C
Solar/Wind Harmer
0.133
274729ELWOOD EC;1P
Adder
7.93
274730ELWOOD EC;6P
Adder
7.929
274734ELWOOD EC;8P
Adder
7.929
274736ELWOOD EC;9P
Adder
7.929
274676JOLIET 29;8U
Adder
14.249
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.605
943591AF1-030 GEN
Solar/Wind Harmer
3.727
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.644
274682WAUKEGAN ;7U
Adder
8.557
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.153
274872LEEDK;1U
Solar/Wind Harmer
0.121
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.352
274855GSG-6 ;RU
Solar/Wind Harmer
0.121
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.059
274878BISHOP HL;2U
Solar/Wind Harmer
0.111
959091AF2-200 GEN
Solar/Wind Harmer
6.576
276157O29GEN1
Solar/Wind Harmer
0.527
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
2.628
965931AG1-462 GEN
Solar/Wind Harmer
8.158
270222AC2-111 GEN
Solar/Wind Harmer
1.616
970243AG2-164 GEN
Solar/Wind Harmer
1.864
970519AG2-331 GEN
Solar/Wind Harmer
8.287
970699AG2-449 GEN
Solar/Wind Harmer
0.797
24441205WTRV SLR C
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Helper
0.648
253406AD2-031_GEN
Solar/Wind Helper
0.903
253415AE1-040 GEN
Solar/Wind Helper
0.547
253338AC1-165 GEN
Solar/Wind Helper
0.58
253333AC1-068 GEN
Solar/Wind Helper
0.601
241974AD2-163_GEN2
Solar/Wind Helper
1.018
241955AC1-078 GEN
Solar/Wind Helper
0.969
25194708EBND2
50/50
6.266
24729405KEY G3
50/50
0.332
24729305KEY G2
50/50
0.327
24729205KEY G1
50/50
0.325
247621Y3-024
50/50
0.169
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.843
960441AF2-335 GEN
Solar/Wind Harmer
6.997
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
3.991
270599AE1-208 GEN
Solar/Wind Harmer
5.883
270031AE2-169
Solar/Wind Harmer
3.53
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
2.936
964611AG1-324 GEN
Solar/Wind Harmer
0.405
270201AC2-176 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.024
970883AG2-550 GEN
Solar/Wind Harmer
4.232
970885AG2-551 GEN
Solar/Wind Harmer
1.411
945391AF1-204 GEN
Solar/Wind Harmer
4.318
970241AG2-163 GEN
Solar/Wind Harmer
2.236
966841AG1-555 GEN
Solar/Wind Harmer
0.418
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.691
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.517
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.141
274770LINCOLN ;1U
Adder
4.104
274771LINCOLN ;2U
Adder
4.104
276916AD2-100_GEN
Solar/Wind Harmer
7.107
276911AD2-131_GEN
Solar/Wind Harmer
0.468
965681AG1-436 GEN
Solar/Wind Harmer
4.229
965791AG1-447 GEN
Solar/Wind Harmer
3.101
274888KELLY CRK;1U
Solar/Wind Harmer
0.198
274887GEN-1.85
Solar/Wind Harmer
0.089
276843GEN-1.7
Solar/Wind Harmer
0.109
958011AF2-095 GEN
Solar/Wind Harmer
4.864
274808UNIV PK N;4U
Adder
2.412
972259AH1-714 GEN
Adder
9.225
274803UNIV PARK;6U
Adder
2.819
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.422
24728805RICHG1
Adder
1.818
24728905RICHG2
Adder
1.818
958481AF2-142 GEN
Solar/Wind Harmer
5.024
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.453
958491AF2-143 GEN
Solar/Wind Harmer
5.012
24441505OLIV SLR
Solar/Wind Harmer
0
274879MINONK ;1U
Solar/Wind Harmer
0.141
270526AF1-158 GEN
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
0.621
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274696ROCKY RD ;4P
Adder
5.432
274695ROCKY RD ;2P
Adder
5.307
274693ROCKY RD ;1P
Adder
5.255
274697ROCKY RD ;3P
Adder
1.442
274683WAUKEGAN ;8U
Adder
10.027
274683WAUKEGAN ;8U
Adder
8.452
962691AG1-118 GEN
Solar/Wind Harmer
9.946
970921AG2-575 GEN
Solar/Wind Harmer
3.312
970921AG2-575 GEN
Solar/Wind Harmer
1.104
270216AD2-079_GEN
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.13
276646AC1-214 GEN2
Solar/Wind Harmer
0.13
942991AE2-321 GEN
Solar/Wind Harmer
3.685
276782AC1-033 GEN
Solar/Wind Harmer
0
971333AH1-146 GEN
Solar/Wind Harmer
6.586
971335AH1-147 GEN
Solar/Wind Harmer
6.586
971341AH1-150 GEN
Solar/Wind Harmer
6.576
971343AH1-151 GEN
Solar/Wind Harmer
6.576
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.85
276741O09 GEN1
Solar/Wind Harmer
0.116
276708O09 GEN2
Solar/Wind Harmer
0.116
276603SUBLETTE C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.438
961051AF2-396 GEN
Solar/Wind Harmer
4.292
970239AG2-162 GEN
Solar/Wind Harmer
0.797
25183208HLCRTG
Solar/Wind Helper
2.467
252509AD1-136 GEN
Solar/Wind Helper
0.194
253394AE2-221_GEN
Solar/Wind Helper
1.592
253398AE2-221_GEN2
Solar/Wind Helper
1.592
253378AE2-206_GEN
Solar/Wind Helper
0.968
276820AF1-078_GEN
Solar/Wind Helper
0.452
962581AG1-107 GEN
Solar/Wind Helper
1.007
961491AF2-440 GEN
Solar/Wind Helper
0.041
270186AC1-089 GEN
Solar/Wind Helper
0.814
270518AE2-148 GEN
Solar/Wind Helper
8.413
944201AF1-088_MTX
Adder
61.158
957141AF2-008_MTX
Adder
30.579
NYPJM->LTFIMP_NY
CLTF
0.653
LGEELTFEXP_LGEE->PJM
CLTF
1.404
WECLTFEXP_WEC->PJM
CLTF
1.789
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.453
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.258
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.271
MECLTFEXP_MEC->PJM
CLTF
7.181
SIGELTFEXP_SIGE->PJM
CLTF
0.234
LAGNLTFEXP_LAGN->PJM
CLTF
4.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.507
TVALTFEXP_TVA->PJM
CLTF
1.913

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.21 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2174.62
MW Contribution:3.79
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.124
24802806KYGER 2HP
50/50
4.1
24802906KYGER 2LP
50/50
2.411
252509AD1-136 GEN
Solar/Wind Harmer
0.041
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.564
252516AE2-318_GEN
Solar/Wind Harmer
5.822
25194408D.CRK1
Adder
7.931
25194508D.CRK3
Adder
1.483
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
970235AG2-159 GEN
Solar/Wind Harmer
3.857
970235AG2-159 GEN
Solar/Wind Harmer
2.213
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.547
972045AH1-571 GEN
Solar/Wind Harmer
1.239
971125AH1-004 GEN
Solar/Wind Harmer
2.32
970107AG2-081 GEN
Solar/Wind Harmer
1.74
253370AE2-315 SEC1
Adder
1.649
25322209TAIT E
Adder
7.765
25322209TAIT E
Adder
7.591
24728805RICHG1
Adder
2.942
24728905RICHG2
Adder
2.942
25326109MON D
Adder
1.02
942891AE2-308 GEN
Solar/Wind Harmer
5.216
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.205
970883AG2-550 GEN
Solar/Wind Harmer
4.71
970885AG2-551 GEN
Solar/Wind Harmer
1.57
970239AG2-162 GEN
Solar/Wind Harmer
1.175
964571AG1-320 GEN
Solar/Wind Harmer
4.203
970825AG2-519 GEN
Solar/Wind Harmer
5.003
960441AF2-335 GEN
Solar/Wind Harmer
4.491
247621Y3-024
Adder
0.153
970653AG2-424 GEN
Solar/Wind Harmer
2.124
970653AG2-424 GEN
Solar/Wind Harmer
1.101
964611AG1-324 GEN
Solar/Wind Harmer
0.327
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.178
270201AC2-176 GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
2.055
270599AE1-208 GEN
Solar/Wind Harmer
3.884
270031AE2-169
Solar/Wind Harmer
2.33
945391AF1-204 GEN
Solar/Wind Harmer
4.317
971081AG2-670 GEN
Solar/Wind Harmer
2.994
270518AE2-148 GEN
Solar/Wind Harmer
0.344
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.326
25326509SID D
Adder
0.727
970241AG2-163 GEN
Solar/Wind Harmer
2.246
942221AE2-234 GEN
Solar/Wind Harmer
0.019
966841AG1-555 GEN
Solar/Wind Harmer
0.421
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
339255AE2-071 GEN
Solar/Wind Harmer
-0.058
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.538
964781AG1-341 GEN
Solar/Wind Harmer
3.771
276916AD2-100_GEN
Solar/Wind Harmer
7.444
276911AD2-131_GEN
Solar/Wind Harmer
0.49
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970077AG2-063 GEN
Solar/Wind Harmer
1.932
971485AH1-239 GEN
Solar/Wind Harmer
2.635
970321AG2-212 GEN
Solar/Wind Harmer
1.415
966021AG1-471 GEN
Solar/Wind Harmer
1.759
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.135
958491AF2-143 GEN
Solar/Wind Harmer
4.784
276741O09 GEN1
Solar/Wind Harmer
0.113
276708O09 GEN2
Solar/Wind Harmer
0.113
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.767
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.89
938861AE1-114 GEN
Solar/Wind Harmer
1.792
274764LEE CO EC;5U
Adder
4.227
274765LEE CO EC;6U
Adder
4.227
274762LEE CO EC;3U
Adder
4.217
274763LEE CO EC;4U
Adder
4.177
24802606KYGER 1HP
50/50
4.148
24802706KYGER 1LP
50/50
2.435
24803506KYGER 5LP
50/50
2.378
25016408BKJDB1
50/50
0.282
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
5.794
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.254
25196308WSDLE2
Adder
9.174
25196208WSDLE1
Adder
9.151
25196708WSDLE6
Adder
9.128
25196508WSDLE4
Adder
8.898
25196108MFTGT2
Adder
1.544
25196108MFTGT2
Adder
1.434
972163AH1-664 GEN
Solar/Wind Harmer
7.142
972165AH1-665 GEN
Solar/Wind Harmer
5.72
270367AC2-061_GEN
Solar/Wind Harmer
0.005
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.56
253372AE2-315 SEC3
Adder
1.56
25306009OHH W.
Adder
2.334
253349AC2-067 GEN
Solar/Wind Harmer
1.738
253400AC2-068 GEN
Solar/Wind Harmer
0.699
3429211JKCT 2G
Adder
8.896
970689AG2-444 GEN
Solar/Wind Harmer
10.729
971673AH1-337 GEN
Solar/Wind Harmer
3.222
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.342
270543AE2-219 C
Solar/Wind Harmer
0.003
270432AC2-029 GEN
Solar/Wind Harmer
2.087
970455AG2-298 GEN
Solar/Wind Harmer
3.135
241972AD1-140 GEN
Solar/Wind Harmer
0.511
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.796
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.796
971609AH1-304 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.797
965101AG1-375 GEN
Solar/Wind Harmer
4.045
965401AG1-405 GEN
Solar/Wind Harmer
2.261
965411AG1-406 GEN
Solar/Wind Harmer
1.454
270024AE2-089 GEN
Solar/Wind Harmer
0.004
963841AG1-237 GEN
Solar/Wind Harmer
1.641
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.458
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.105
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
971611AH1-305 GEN
Solar/Wind Harmer
2.078
270156DARBY CT1
Adder
4.453
270157DARBY CT2
Adder
4.442
270158DARBY CT3
Adder
4.371
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.32
971343AH1-151 GEN
Solar/Wind Harmer
6.32
274856ECOGROVE ;U1
Solar/Wind Harmer
0.075
276611AD2-172 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
6.97
971333AH1-146 GEN
Solar/Wind Harmer
6.312
971335AH1-147 GEN
Solar/Wind Harmer
6.312
274888KELLY CRK;1U
Solar/Wind Harmer
0.185
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.544
970921AG2-575 GEN
Solar/Wind Harmer
3.156
970921AG2-575 GEN
Solar/Wind Harmer
1.052
962691AG1-118 GEN
Solar/Wind Harmer
9.466
972259AH1-714 GEN
Adder
8.624
274696ROCKY RD ;4P
Adder
5.152
274695ROCKY RD ;2P
Adder
5.033
274693ROCKY RD ;1P
Adder
4.983
274697ROCKY RD ;3P
Adder
1.367
237033AB1-150 GEN
Solar/Wind Helper
0.407
959341AF2-225 GEN
Solar/Wind Harmer
3.544
941731AE2-173 GEN
Solar/Wind Harmer
2.813
963791AG1-232 GEN
Solar/Wind Harmer
4.514
945631AF1-228 GEN
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
970169AG2-114 GEN
Solar/Wind Harmer
3.3
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
6.21
957751AF2-069 GEN
Solar/Wind Harmer
0.107
926823AC1-168 GEN
Solar/Wind Harmer
0.548
276868AE1-113 GEN
Solar/Wind Harmer
0.641
276882AE2-255 GEN
Solar/Wind Harmer
0.373
946321AF1-296 GEN
Solar/Wind Harmer
1.775
961011AF2-392 GEN
Solar/Wind Harmer
1.859
970833AG2-524 GEN
Solar/Wind Harmer
3.484
970833AG2-524 GEN
Solar/Wind Harmer
2.323
971681AH1-341 GEN
Solar/Wind Harmer
5.094
274731ELWOOD EC;2P
Adder
7.45
274733ELWOOD EC;3P
Adder
7.45
274735ELWOOD EC;4P
Adder
7.45
274728ELWOOD EC;5P
Adder
7.45
971171AH1-044 GEN
Solar/Wind Harmer
6.32
971675AH1-338 GEN
Solar/Wind Harmer
1.232
972227AH1-698 GEN1
Adder
1.181
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
8.814
960591AF2-350 GEN
Solar/Wind Harmer
3.156
274746AC1-111 G10
Adder
2.527
274744AC1-111 GEN8
Adder
2.527
274675JOLIET 29;7U
Adder
13.865
274675JOLIET 29;7U
Adder
0.85
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.209
971411AH1-196 GEN
Solar/Wind Harmer
0.519
24803406KYGER 5HP
50/50
4.078
24803206KYGER 4HP
50/50
4.075
252507AC2-088 GEN
Solar/Wind Harmer
0.367
25196808ZIMRHP
Adder
80.97
25194608D.CRK4
Adder
1.724
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.127
25196008MFTGT1
Adder
1.401
945681AF1-233 GEN
Solar/Wind Harmer
12.229
339216AC1-074 GEN
Solar/Wind Harmer
0.17
270263AC1-001 GEN
Solar/Wind Harmer
0.594
253370AE2-315 SEC1
Adder
1.649
253371AE2-315 SEC2
Adder
1.56
25326309TAIT D
Adder
0.872
960071AF2-298 GEN
Solar/Wind Harmer
2.739
3429421JKCT 10G
Adder
6.526
3429241JKCT 3G
Adder
9.013
970773AG2-487 GEN
Solar/Wind Harmer
0.928
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.628
971565AH1-281 GEN
Solar/Wind Harmer
0.973
970091AG2-072 GEN
Adder
52.877
24728605AND G2
Adder
2.601
970333AG2-219 GEN
Solar/Wind Harmer
3.361
971821AH1-427 GEN
Solar/Wind Harmer
4.564
270005AE1-210 C O1
Solar/Wind Harmer
0.988
965031AG1-367 GEN
Solar/Wind Harmer
4.558
247536S-71 GEN
Solar/Wind Harmer
0.183
970825AG2-519 GEN
Solar/Wind Harmer
1.602
276903AD2-071 C
Solar/Wind Harmer
4.881
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
270032AE2-172
Solar/Wind Harmer
2.855
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.546
958861AF2-177 GEN
Solar/Wind Harmer
1.753
965651AG1-433 GEN
Solar/Wind Harmer
1.163
963741AG1-226 GEN
Solar/Wind Harmer
9.112
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.578
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.264
962241AG1-070 GEN
Solar/Wind Harmer
1.948
965911AG1-460 GEN
Solar/Wind Harmer
0.707
276615X2-022 GEN
Solar/Wind Harmer
0.037
963831AG1-236 GEN
Solar/Wind Harmer
1.363
274880W4-005 GEN4
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.362
270159DARBY CT4
Adder
4.382
972175AH1-670 GEN
Solar/Wind Harmer
2.852
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.423
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
958381AF2-132 GEN
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.726
970593AG2-378 GEN
Solar/Wind Harmer
0.756
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970245AG2-165 GEN
Solar/Wind Harmer
1.415
970373AG2-245 GEN
Solar/Wind Harmer
6.824
939401AE1-172 GEN
Solar/Wind Harmer
2.429
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
970569AG2-363 GEN
Solar/Wind Harmer
9.647
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.681
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276158O29GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.45
274761LEE CO EC;2U
Adder
4.217
274766LEE CO EC;7U
Adder
4.167
957471AF2-041 GEN
Solar/Wind Harmer
9.481
959081AF2-199 GEN
Solar/Wind Harmer
3.16
971067AG2-660 GEN
Solar/Wind Harmer
1.053
276861AD2-134 GEN
Solar/Wind Harmer
0.057
274674JOLIET 9 ;6U
Adder
6.97
972235AH1-702 GEN1
Adder
1.141
274872LEEDK;1U
Solar/Wind Harmer
0.002
970819AG2-516 GEN
Solar/Wind Harmer
3.788
276776AD2-060 GEN
Solar/Wind Harmer
0.329
274822ROCKFORD ;11
Adder
8.878
962781AG1-127 GEN
Solar/Wind Harmer
3.003
274745AC1-111 GEN9
Adder
2.527
274676JOLIET 29;8U
Adder
13.865
960001AF2-291 GEN
Solar/Wind Helper
1.732
270331AC1-082 GEN3
Solar/Wind Helper
0.208
24803106KYGER 3LP
50/50
2.428
24803306KYGER 4LP
50/50
2.378
971191AH1-055 GEN
Solar/Wind Harmer
68.522
25196608WSDLE5
Adder
8.99
25194608D.CRK4
Adder
1.724
252510AF1-249 C
Solar/Wind Harmer
0.056
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.265
25196008MFTGT1
Adder
1.357
958171AF2-111 GEN
Solar/Wind Harmer
17.326
972167AH1-666 GEN
Solar/Wind Harmer
5.211
253406AD2-031_GEN
Solar/Wind Harmer
0.471
972173AH1-669 GEN
Solar/Wind Harmer
3.114
270273AD2-016 GEN
Solar/Wind Harmer
0.618
253415AE1-040 GEN
Solar/Wind Harmer
0.002
270222AC2-111 GEN
Solar/Wind Harmer
2.968
253370AE2-315 SEC1
Adder
1.649
253371AE2-315 SEC2
Adder
1.56
970191AG2-125 GEN
Solar/Wind Harmer
1.42
3429391JKCT 9G
Adder
6.526
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970093AG2-073 GEN
Solar/Wind Harmer
4.983
270437AC2-090 C
Solar/Wind Harmer
0.002
966571AG1-526 GEN
Solar/Wind Harmer
10.726
24728705AND G3
Adder
5.44
24728505AND G1
Adder
2.601
970243AG2-164 GEN
Solar/Wind Harmer
2.75
970519AG2-331 GEN
Solar/Wind Harmer
12.22
970699AG2-449 GEN
Solar/Wind Harmer
1.175
958821AF2-173 GEN
Solar/Wind Harmer
6.381
270004AE1-209 GEN
Solar/Wind Harmer
0.988
946031AF1-268 GEN
Solar/Wind Harmer
4.297
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.485
970289AG2-191 GEN
Solar/Wind Harmer
0.462
970291AG2-192 GEN
Solar/Wind Harmer
0.42
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.094
971617AH1-308 GEN
Solar/Wind Harmer
3.288
960741AF2-365 GEN
Solar/Wind Harmer
1.942
972273AH1-721 GEN
Adder
44.027
944531AF1-118 GEN
Solar/Wind Harmer
16.271
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.627
970273AG2-179 GEN
Solar/Wind Harmer
2.166
962251AG1-071 GEN
Solar/Wind Harmer
2.234
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.144
942481AE2-261 GEN
Solar/Wind Harmer
10.562
276621W2-048 GEN
Solar/Wind Harmer
0.177
276838X2-022 GEN2
Solar/Wind Harmer
0.197
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.614
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.197
959611AF2-252 GEN
Solar/Wind Harmer
1.133
964401AG1-302 GEN
Solar/Wind Harmer
0.001
942111AE2-223 GEN
Solar/Wind Harmer
1.097
970605AG2-385 GEN
Solar/Wind Harmer
2.043
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.415
970517AG2-330 GEN
Solar/Wind Harmer
8.489
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
970571AG2-364 GEN
Solar/Wind Harmer
6.432
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.515
276694AA1-018 GEN2
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
8.083
276893AG1-478 C
Solar/Wind Harmer
0.125
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
7.45
274730ELWOOD EC;6P
Adder
7.45
274734ELWOOD EC;8P
Adder
7.45
274736ELWOOD EC;9P
Adder
7.45
274760LEE CO EC;1U
Adder
4.217
274767LEE CO EC;8U
Adder
4.167
959091AF2-200 GEN
Solar/Wind Harmer
6.32
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
972228AH1-698 GEN2
Adder
1.677
972236AH1-702 GEN2
Adder
0.992
274872LEEDK;1U
Solar/Wind Harmer
0.116
276806AD2-047 C O1
Solar/Wind Harmer
1.788
970941AG2-585 GEN
Solar/Wind Harmer
3.945
235780M24_1
Solar/Wind Helper
1.009
944201AF1-088_MTX
Adder
72.238
957141AF2-008_MTX
Adder
36.119
NYPJM->LTFIMP_NY
CLTF
1.588
LGEELTFEXP_LGEE->PJM
CLTF
5.37
WECLTFEXP_WEC->PJM
CLTF
1.725
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.352
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.499
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
67.313
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.642
MECLTFEXP_MEC->PJM
CLTF
7.485
SIGELTFEXP_SIGE->PJM
CLTF
0.339
LAGNLTFEXP_LAGN->PJM
CLTF
6.342
TVALTFEXP_TVA->PJM
CLTF
3.038

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#3150_13_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#3150_13_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:137.97 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2124.68
MW Contribution:3.63
Bus #Bus NameTypeMW Contribution
24803006KYGER 3HP
50/50
4.159
24802806KYGER 2HP
50/50
4.134
24802906KYGER 2LP
50/50
2.431
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.721
252516AE2-318_GEN
Solar/Wind Harmer
5.962
25194408D.CRK1
Adder
8.079
25194508D.CRK3
Adder
1.51
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
3.893
970235AG2-159 GEN
Solar/Wind Harmer
2.234
962581AG1-107 GEN
Solar/Wind Harmer
0.001
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.588
972045AH1-571 GEN
Solar/Wind Harmer
1.272
971125AH1-004 GEN
Solar/Wind Harmer
2.377
970107AG2-081 GEN
Solar/Wind Harmer
1.783
253370AE2-315 SEC1
Adder
1.689
25322209TAIT E
Adder
7.943
25322209TAIT E
Adder
7.765
25326109MON D
Adder
1.044
24728805RICHG1
Adder
2.948
24728905RICHG2
Adder
2.948
942891AE2-308 GEN
Solar/Wind Harmer
5.353
960161AF2-307 GEN
Solar/Wind Harmer
3.328
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
24802606KYGER 1HP
50/50
4.183
24802706KYGER 1LP
50/50
2.455
24803506KYGER 5LP
50/50
2.397
25016408BKJDB1
50/50
0.287
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
5.862
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.421
25196308WSDLE2
Adder
9.339
25196208WSDLE1
Adder
9.316
25196708WSDLE6
Adder
9.293
25196508WSDLE4
Adder
9.059
25196108MFTGT2
Adder
1.562
25196108MFTGT2
Adder
1.45
972163AH1-664 GEN
Solar/Wind Harmer
7.386
972165AH1-665 GEN
Solar/Wind Harmer
5.915
270367AC2-061_GEN
Solar/Wind Harmer
0.005
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.004
253372AE2-315 SEC3
Adder
1.597
253372AE2-315 SEC3
Adder
1.597
25306009OHH W.
Adder
2.386
253349AC2-067 GEN
Solar/Wind Harmer
1.772
253400AC2-068 GEN
Solar/Wind Harmer
0.712
970689AG2-444 GEN
Solar/Wind Harmer
11.449
3429211JKCT 2G
Adder
9.139
270432AC2-029 GEN
Solar/Wind Harmer
2.231
971673AH1-337 GEN
Solar/Wind Harmer
3.221
24803106KYGER 3LP
50/50
2.448
24803306KYGER 4LP
50/50
2.397
971191AH1-055 GEN
Solar/Wind Harmer
69.967
25194608D.CRK4
Adder
1.756
25196608WSDLE5
Adder
9.152
252510AF1-249 C
Solar/Wind Harmer
0.058
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.605
958171AF2-111 GEN
Solar/Wind Harmer
17.899
25196008MFTGT1
Adder
1.372
972167AH1-666 GEN
Solar/Wind Harmer
5.389
972173AH1-669 GEN
Solar/Wind Harmer
3.325
253406AD2-031_GEN
Solar/Wind Harmer
0.488
270273AD2-016 GEN
Solar/Wind Harmer
0.66
253415AE1-040 GEN
Solar/Wind Harmer
0.002
270222AC2-111 GEN
Solar/Wind Harmer
2.992
253370AE2-315 SEC1
Adder
1.689
253371AE2-315 SEC2
Adder
1.597
970191AG2-125 GEN
Solar/Wind Harmer
1.447
3429391JKCT 9G
Adder
6.703
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970093AG2-073 GEN
Solar/Wind Harmer
5.117
966571AG1-526 GEN
Solar/Wind Harmer
10.964
270437AC2-090 C
Solar/Wind Harmer
0.002
24728705AND G3
Adder
5.35
24728505AND G1
Adder
2.558
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
958821AF2-173 GEN
Solar/Wind Harmer
6.306
270004AE1-209 GEN
Solar/Wind Harmer
0.976
946031AF1-268 GEN
Solar/Wind Harmer
4.249
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.42
24803406KYGER 5HP
50/50
4.112
24803206KYGER 4HP
50/50
4.109
252507AC2-088 GEN
Solar/Wind Harmer
0.376
25196808ZIMRHP
Adder
82.892
25194608D.CRK4
Adder
1.756
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.388
25196008MFTGT1
Adder
1.417
945681AF1-233 GEN
Solar/Wind Harmer
12.648
339216AC1-074 GEN
Solar/Wind Harmer
0.174
270263AC1-001 GEN
Solar/Wind Harmer
0.637
253370AE2-315 SEC1
Adder
1.689
253371AE2-315 SEC2
Adder
1.597
25326309TAIT D
Adder
0.892
960071AF2-298 GEN
Solar/Wind Harmer
2.798
3429421JKCT 10G
Adder
6.703
3429241JKCT 3G
Adder
9.259
970773AG2-487 GEN
Solar/Wind Harmer
0.923
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.602
971565AH1-281 GEN
Solar/Wind Harmer
0.976
971821AH1-427 GEN
Solar/Wind Harmer
4.663
24728605AND G2
Adder
2.558
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
247536S-71 GEN
Solar/Wind Harmer
0.181
270005AE1-210 C O1
Solar/Wind Harmer
0.976
965031AG1-367 GEN
Solar/Wind Harmer
4.504
970883AG2-550 GEN
Solar/Wind Harmer
4.692
970885AG2-551 GEN
Solar/Wind Harmer
1.564
964571AG1-320 GEN
Solar/Wind Harmer
4.207
970825AG2-519 GEN
Solar/Wind Harmer
4.939
960441AF2-335 GEN
Solar/Wind Harmer
4.431
970653AG2-424 GEN
Solar/Wind Harmer
2.138
970653AG2-424 GEN
Solar/Wind Harmer
1.108
247621Y3-024
Adder
0.152
964611AG1-324 GEN
Solar/Wind Harmer
0.324
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
1.068
971613AH1-306 GEN
Solar/Wind Harmer
2.006
270599AE1-208 GEN
Solar/Wind Harmer
3.82
270031AE2-169
Solar/Wind Harmer
2.292
270518AE2-148 GEN
Solar/Wind Harmer
0.356
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.006
971081AG2-670 GEN
Solar/Wind Harmer
3.039
25326509SID D
Adder
0.738
945391AF1-204 GEN
Solar/Wind Harmer
4.142
944541AF1-119 GEN
Solar/Wind Harmer
0.261
960971AF2-388 GEN
Solar/Wind Harmer
2.284
942221AE2-234 GEN
Solar/Wind Harmer
0.018
970241AG2-163 GEN
Solar/Wind Harmer
2.14
339255AE2-071 GEN
Solar/Wind Harmer
-0.059
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.562
964781AG1-341 GEN
Solar/Wind Harmer
3.828
966841AG1-555 GEN
Solar/Wind Harmer
0.399
970077AG2-063 GEN
Solar/Wind Harmer
1.99
276916AD2-100_GEN
Solar/Wind Harmer
7.16
276911AD2-131_GEN
Solar/Wind Harmer
0.472
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971485AH1-239 GEN
Solar/Wind Harmer
2.706
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
966021AG1-471 GEN
Solar/Wind Harmer
1.81
960611AF2-352 GEN
Solar/Wind Harmer
1.085
942861AE2-305 GEN
Solar/Wind Harmer
2.483
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.122
276646AC1-214 GEN2
Solar/Wind Harmer
0.122
276782AC1-033 GEN
Solar/Wind Harmer
0
970321AG2-212 GEN
Solar/Wind Harmer
1.329
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.129
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
958491AF2-143 GEN
Solar/Wind Harmer
4.573
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.411
972267AH1-718 GEN
Adder
1.812
276603SUBLETTE C
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
4.554
274764LEE CO EC;5U
Adder
4.052
274765LEE CO EC;6U
Adder
4.052
274762LEE CO EC;3U
Adder
4.042
274763LEE CO EC;4U
Adder
4.004
938861AE1-114 GEN
Solar/Wind Harmer
1.718
274856ECOGROVE ;U1
Solar/Wind Harmer
0.071
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.051
971343AH1-151 GEN
Solar/Wind Harmer
6.051
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.041
971335AH1-147 GEN
Solar/Wind Harmer
6.041
942991AE2-321 GEN
Solar/Wind Harmer
3.37
970921AG2-575 GEN
Solar/Wind Harmer
3.018
970921AG2-575 GEN
Solar/Wind Harmer
1.006
274674JOLIET 9 ;6U
Adder
6.651
274696ROCKY RD ;4P
Adder
4.923
274695ROCKY RD ;2P
Adder
4.81
274693ROCKY RD ;1P
Adder
4.762
274697ROCKY RD ;3P
Adder
1.307
274683WAUKEGAN ;8U
Adder
9.1
274683WAUKEGAN ;8U
Adder
7.671
237033AB1-150 GEN
Solar/Wind Helper
0.417
962691AG1-118 GEN
Solar/Wind Harmer
7.52
970825AG2-519 GEN
Solar/Wind Harmer
1.582
970091AG2-072 GEN
Adder
48.538
276903AD2-071 C
Solar/Wind Harmer
4.771
970333AG2-219 GEN
Solar/Wind Harmer
3.054
270032AE2-172
Solar/Wind Harmer
2.787
945371AF1-202 GEN
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970291AG2-192 GEN
Solar/Wind Harmer
0.53
958861AF2-177 GEN
Solar/Wind Harmer
1.723
965651AG1-433 GEN
Solar/Wind Harmer
1.142
964901AG1-354 GEN
Solar/Wind Harmer
5.661
970273AG2-179 GEN
Solar/Wind Harmer
1.295
963741AG1-226 GEN
Solar/Wind Harmer
8.683
270159DARBY CT4
Adder
4.589
962241AG1-070 GEN
Solar/Wind Harmer
1.975
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
0.779
24791305MDL-5G
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276615X2-022 GEN
Solar/Wind Harmer
0.035
963831AG1-236 GEN
Solar/Wind Harmer
1.309
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.735
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.127
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.525
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.187
958381AF2-132 GEN
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
2.32
274877BISHOP HL;1U
Solar/Wind Harmer
0.104
970373AG2-245 GEN
Solar/Wind Harmer
6.466
970569AG2-363 GEN
Solar/Wind Harmer
9.236
970245AG2-165 GEN
Solar/Wind Harmer
1.329
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.607
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276158O29GEN2
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.368
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.042
274766LEE CO EC;7U
Adder
3.995
941551AE2-152 GEN
Solar/Wind Harmer
0
957471AF2-041 GEN
Solar/Wind Harmer
9.076
959081AF2-199 GEN
Solar/Wind Harmer
3.025
971067AG2-660 GEN
Solar/Wind Harmer
1.008
970819AG2-516 GEN
Solar/Wind Harmer
3.628
972235AH1-702 GEN1
Adder
1.092
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276861AD2-134 GEN
Solar/Wind Harmer
0.054
971475AH1-234 GEN
Solar/Wind Harmer
1.467
274822ROCKFORD ;11
Adder
8.501
274872LEEDK;1U
Solar/Wind Harmer
0.002
274732ELWOOD EC;7P
Adder
7.109
962781AG1-127 GEN
Solar/Wind Harmer
2.872
274674JOLIET 9 ;6U
Adder
6.651
274828WAUKEGAN ;BP
Adder
4.77
274682WAUKEGAN ;7U
Adder
7.76
274745AC1-111 GEN9
Adder
2.413
960001AF2-291 GEN
Solar/Wind Helper
1.728
270331AC1-082 GEN3
Solar/Wind Helper
0.211
970243AG2-164 GEN
Solar/Wind Harmer
2.498
970519AG2-331 GEN
Solar/Wind Harmer
11.104
970699AG2-449 GEN
Solar/Wind Harmer
1.068
970289AG2-191 GEN
Solar/Wind Harmer
0.449
970291AG2-192 GEN
Solar/Wind Harmer
0.408
247642Z2-115 C
Solar/Wind Harmer
0.002
960741AF2-365 GEN
Solar/Wind Harmer
1.961
970193AG2-126 GEN
Solar/Wind Harmer
5.847
971617AH1-308 GEN
Solar/Wind Harmer
3.242
972273AH1-721 GEN
Adder
45.379
970273AG2-179 GEN
Solar/Wind Harmer
2.22
962251AG1-071 GEN
Solar/Wind Harmer
2.265
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
4.209
944531AF1-118 GEN
Solar/Wind Harmer
15.904
970605AG2-385 GEN
Solar/Wind Harmer
2.105
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.432
942481AE2-261 GEN
Solar/Wind Harmer
10.156
276621W2-048 GEN
Solar/Wind Harmer
0.17
276838X2-022 GEN2
Solar/Wind Harmer
0.189
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.549
276668AB2-070 GEN1
Solar/Wind Harmer
0.122
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.769
959611AF2-252 GEN
Solar/Wind Harmer
1.085
942111AE2-223 GEN
Solar/Wind Harmer
1.05
964401AG1-302 GEN
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
274878BISHOP HL;2U
Solar/Wind Harmer
0.104
970571AG2-364 GEN
Solar/Wind Harmer
6.157
970513AG2-328 GEN
Solar/Wind Harmer
1.329
970517AG2-330 GEN
Solar/Wind Harmer
7.976
276889AE2-281 GEN
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.494
276805AD2-038 GEN
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.768
276694AA1-018 GEN2
Solar/Wind Harmer
0
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.042
274767LEE CO EC;8U
Adder
3.995
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
6.051
972236AH1-702 GEN2
Adder
0.95
274855GSG-6 ;RU
Solar/Wind Harmer
0.111
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.054
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.322
274872LEEDK;1U
Solar/Wind Harmer
0.111
276893AG1-478 C
Solar/Wind Harmer
0.12
274729ELWOOD EC;1P
Adder
7.11
274730ELWOOD EC;6P
Adder
7.109
274734ELWOOD EC;8P
Adder
7.109
274736ELWOOD EC;9P
Adder
7.109
972228AH1-698 GEN2
Adder
1.599
274682WAUKEGAN ;7U
Adder
7.76
235780M24_1
Solar/Wind Helper
1.032
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.332
241972AD1-140 GEN
Solar/Wind Harmer
0.524
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
3.155
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.772
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.682
971609AH1-304 GEN
Solar/Wind Harmer
0.681
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.327
965411AG1-406 GEN
Solar/Wind Harmer
1.497
970289AG2-191 GEN
Solar/Wind Harmer
0.775
965101AG1-375 GEN
Solar/Wind Harmer
3.976
270024AE2-089 GEN
Solar/Wind Harmer
0.004
24729505KEY G4
Adder
3.385
270156DARBY CT1
Adder
4.663
270157DARBY CT2
Adder
4.652
270158DARBY CT3
Adder
4.577
963841AG1-237 GEN
Solar/Wind Harmer
1.561
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
945631AF1-228 GEN
Solar/Wind Harmer
0
972203AH1-686 GEN
Adder
1.144
944221AF1-090 GEN
Solar/Wind Harmer
2.026
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.122
276848AB2-070 GEN3
Solar/Wind Harmer
0.122
971611AH1-305 GEN
Solar/Wind Harmer
1.965
963791AG1-232 GEN
Solar/Wind Harmer
4.412
958391AF2-133 GEN
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.393
941731AE2-173 GEN
Solar/Wind Harmer
2.693
943861AF1-054 GEN
Solar/Wind Harmer
1.226
943851AF1-053 GEN
Solar/Wind Harmer
0.849
970169AG2-114 GEN
Solar/Wind Harmer
3.156
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
270071AF1-092 GEN
Solar/Wind Harmer
5.964
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.102
926823AC1-168 GEN
Solar/Wind Harmer
0.525
276868AE1-113 GEN
Solar/Wind Harmer
0.613
276882AE2-255 GEN
Solar/Wind Harmer
0.357
946321AF1-296 GEN
Solar/Wind Harmer
1.705
961011AF2-392 GEN
Solar/Wind Harmer
1.782
971681AH1-341 GEN
Solar/Wind Harmer
4.881
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
6.051
971675AH1-338 GEN
Solar/Wind Harmer
1.179
970833AG2-524 GEN
Solar/Wind Harmer
3.325
970833AG2-524 GEN
Solar/Wind Harmer
2.217
274823ROCKFORD ;21
Adder
8.44
971411AH1-196 GEN
Solar/Wind Harmer
4.529
971177AH1-047 GEN
Solar/Wind Harmer
1.861
274731ELWOOD EC;2P
Adder
7.11
274733ELWOOD EC;3P
Adder
7.11
274735ELWOOD EC;4P
Adder
7.11
274728ELWOOD EC;5P
Adder
7.109
972227AH1-698 GEN1
Adder
1.126
274746AC1-111 G10
Adder
2.321
270330AC1-082 GEN2
Solar/Wind Helper
0.044
270329AC1-082 GEN1
Solar/Wind Helper
0.212
944201AF1-088_MTX
Adder
68.311
957141AF2-008_MTX
Adder
34.155
NYPJM->LTFIMP_NY
CLTF
1.58
LGEELTFEXP_LGEE->PJM
CLTF
5.332
WECLTFEXP_WEC->PJM
CLTF
1.653
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.211
CBM West 2LTFEXP_CBM-W2->PJM
CBM
57.054
AG2-052LTFEXP_AG2-052->PJM
LTF
0.107
AH1-155LTFEXP_AH1-155->PJM
LTF
0.16
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.959
MECLTFEXP_MEC->PJM
CLTF
7.25
SIGELTFEXP_SIGE->PJM
CLTF
0.334
LAGNLTFEXP_LAGN->PJM
CLTF
6.463
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.116
TVALTFEXP_TVA->PJM
CLTF
3.153

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1561.02
MW Contribution:3.76
Bus #Bus NameTypeMW Contribution
25196008MFTGT1
Adder
1.414
25194608D.CRK4
Adder
1.625
252507AC2-088 GEN
Solar/Wind Harmer
0.307
25196808ZIMRHP
Adder
62.29
970773AG2-487 GEN
Solar/Wind Harmer
0.942
970091AG2-072 GEN
Adder
56.565
970333AG2-219 GEN
Solar/Wind Harmer
3.629
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.697
24728605AND G2
Adder
2.615
270005AE1-210 C O1
Solar/Wind Harmer
0.997
965031AG1-367 GEN
Solar/Wind Harmer
4.603
970825AG2-519 GEN
Solar/Wind Harmer
1.603
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
4.926
247536S-71 GEN
Solar/Wind Harmer
0.176
270032AE2-172
Solar/Wind Harmer
2.877
970291AG2-192 GEN
Solar/Wind Harmer
0.551
971565AH1-281 GEN
Solar/Wind Harmer
0.847
945371AF1-202 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.113
960071AF2-298 GEN
Solar/Wind Harmer
2.043
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
25326309TAIT D
Adder
0.64
958861AF2-177 GEN
Solar/Wind Harmer
1.761
965651AG1-433 GEN
Solar/Wind Harmer
1.167
963741AG1-226 GEN
Solar/Wind Harmer
9.29
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
25196008MFTGT1
Adder
1.37
25196608WSDLE5
Adder
8.603
25194608D.CRK4
Adder
1.625
252510AF1-249 C
Solar/Wind Harmer
0.052
270222AC2-111 GEN
Solar/Wind Harmer
2.803
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970243AG2-164 GEN
Solar/Wind Harmer
2.969
970519AG2-331 GEN
Solar/Wind Harmer
13.197
970699AG2-449 GEN
Solar/Wind Harmer
1.269
270437AC2-090 C
Solar/Wind Harmer
0.002
24728705AND G3
Adder
5.469
24728505AND G1
Adder
2.615
958821AF2-173 GEN
Solar/Wind Harmer
6.444
270004AE1-209 GEN
Solar/Wind Harmer
0.997
946031AF1-268 GEN
Solar/Wind Harmer
4.275
970191AG2-125 GEN
Solar/Wind Harmer
1.095
970289AG2-191 GEN
Solar/Wind Harmer
0.466
970291AG2-192 GEN
Solar/Wind Harmer
0.424
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.308
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.187
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
971617AH1-308 GEN
Solar/Wind Harmer
3.198
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.711
944531AF1-118 GEN
Solar/Wind Harmer
16.26
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.525
276621W2-048 GEN
Solar/Wind Harmer
0.176
276838X2-022 GEN2
Solar/Wind Harmer
0.197
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.613
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
964401AG1-302 GEN
Solar/Wind Harmer
0.001
966571AG1-526 GEN
Solar/Wind Harmer
7.577
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.199
959611AF2-252 GEN
Solar/Wind Harmer
1.133
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
1.098
970513AG2-328 GEN
Solar/Wind Harmer
1.448
970517AG2-330 GEN
Solar/Wind Harmer
8.688
960741AF2-365 GEN
Solar/Wind Harmer
1.664
3429391JKCT 9G
Adder
3.902
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
970571AG2-364 GEN
Solar/Wind Harmer
6.41
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
3.181
276694AA1-018 GEN2
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.125
274729ELWOOD EC;1P
Adder
7.457
972228AH1-698 GEN2
Adder
1.68
274730ELWOOD EC;6P
Adder
7.457
274734ELWOOD EC;8P
Adder
7.457
274736ELWOOD EC;9P
Adder
7.457
276806AD2-047 C O1
Solar/Wind Harmer
1.792
970941AG2-585 GEN
Solar/Wind Harmer
3.953
276157O29GEN1
Solar/Wind Harmer
0.511
274800UNIV PARK;3U
Adder
2.637
972038AH1-567 GEN2
Adder
0.165
274676JOLIET 29;8U
Adder
13.378
274802UNIV PARK;5U
Adder
2.636
274826FISK ;BP
Adder
4.945
970707AG2-453 GEN
Solar/Wind Harmer
10.286
943121AE2-341 GEN
Solar/Wind Harmer
5.278
943591AF1-030 GEN
Solar/Wind Harmer
3.51
274772LINCOLN ;3U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.115
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.056
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.335
959091AF2-200 GEN
Solar/Wind Harmer
6.288
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.987
962251AG1-071 GEN
Solar/Wind Harmer
1.885
958171AF2-111 GEN
Solar/Wind Harmer
7.532
970349AG2-230 GEN
Solar/Wind Harmer
4.502
957541AF2-048 GEN
Solar/Wind Helper
0.879
270273AD2-016 GEN
Solar/Wind Helper
1.449
971605AH1-302 GEN
Solar/Wind Harmer
4.455
965911AG1-460 GEN
Solar/Wind Harmer
0.704
276615X2-022 GEN
Solar/Wind Harmer
0.037
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.362
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.508
958381AF2-132 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
2.851
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.729
970245AG2-165 GEN
Solar/Wind Harmer
1.448
971821AH1-427 GEN
Solar/Wind Harmer
3.331
970373AG2-245 GEN
Solar/Wind Harmer
6.927
3429421JKCT 10G
Adder
3.902
939401AE1-172 GEN
Solar/Wind Harmer
2.433
3429241JKCT 3G
Adder
5.47
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
970569AG2-363 GEN
Solar/Wind Harmer
9.614
971997AH1-543 GEN
Solar/Wind Harmer
1.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.457
276776AD2-060 GEN
Solar/Wind Harmer
0.33
274674JOLIET 9 ;6U
Adder
6.975
276158O29GEN2
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.637
274676JOLIET 29;8U
Adder
13.874
274745AC1-111 GEN9
Adder
2.525
274812UNIV PK N;8U
Adder
2.261
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.805
274774LINCOLN ;5U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.056
962781AG1-127 GEN
Solar/Wind Harmer
2.993
957471AF2-041 GEN
Solar/Wind Harmer
9.432
959081AF2-199 GEN
Solar/Wind Harmer
3.144
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
970819AG2-516 GEN
Solar/Wind Harmer
3.764
971475AH1-234 GEN
Solar/Wind Harmer
1.52
964901AG1-354 GEN
Solar/Wind Harmer
4.633
962241AG1-070 GEN
Solar/Wind Harmer
1.643
927014AC1-188 GEN
Solar/Wind Helper
0.876
270263AC1-001 GEN
Solar/Wind Helper
0.622
270331AC1-082 GEN3
Solar/Wind Helper
0.099
960001AF2-291 GEN
Solar/Wind Helper
0.551
25016408BKJDB1
50/50
0.315
25196108MFTGT2
Adder
1.559
25196108MFTGT2
Adder
1.448
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.856
25196308WSDLE2
Adder
8.779
25196208WSDLE1
Adder
8.757
25196708WSDLE6
Adder
8.735
25196508WSDLE4
Adder
8.515
971985AH1-537 GEN
Solar/Wind Harmer
2.063
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971673AH1-337 GEN
Solar/Wind Harmer
3.056
971029AG2-637 GEN
Solar/Wind Harmer
6.982
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.798
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.833
253349AC2-067 GEN
Solar/Wind Harmer
1.341
253400AC2-068 GEN
Solar/Wind Harmer
0.539
970289AG2-191 GEN
Solar/Wind Harmer
0.806
971609AH1-304 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
0
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
25306009OHH W.
Adder
1.706
253372AE2-315 SEC3
Adder
1.113
253372AE2-315 SEC3
Adder
1.113
965101AG1-375 GEN
Solar/Wind Harmer
4.064
970455AG2-298 GEN
Solar/Wind Harmer
2.674
963841AG1-237 GEN
Solar/Wind Harmer
1.675
270024AE2-089 GEN
Solar/Wind Harmer
0.004
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.46
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.096
971611AH1-305 GEN
Solar/Wind Harmer
2.122
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.547
941731AE2-173 GEN
Solar/Wind Harmer
2.815
339211AE2-254 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
3.303
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
4.381
270071AF1-092 GEN
Solar/Wind Harmer
6.208
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
5.399
957751AF2-069 GEN
Solar/Wind Harmer
0.106
926823AC1-168 GEN
Solar/Wind Harmer
0.547
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.373
970833AG2-524 GEN
Solar/Wind Harmer
3.487
970833AG2-524 GEN
Solar/Wind Harmer
2.324
274731ELWOOD EC;2P
Adder
7.457
274733ELWOOD EC;3P
Adder
7.457
274735ELWOOD EC;4P
Adder
7.457
972227AH1-698 GEN1
Adder
1.183
274728ELWOOD EC;5P
Adder
7.457
960591AF2-350 GEN
Solar/Wind Harmer
3.162
274675JOLIET 29;7U
Adder
13.874
274675JOLIET 29;7U
Adder
13.378
274687WILL CNTY;4U
Adder
12.634
274687WILL CNTY;4U
Adder
12.634
25194408D.CRK1
Adder
7.477
25194508D.CRK3
Adder
1.398
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.274
252516AE2-318_GEN
Solar/Wind Harmer
4.678
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
24728805RICHG1
Adder
2.818
24728905RICHG2
Adder
2.818
970239AG2-162 GEN
Solar/Wind Harmer
1.269
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.007
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.005
970883AG2-550 GEN
Solar/Wind Harmer
4.51
970885AG2-551 GEN
Solar/Wind Harmer
1.503
960441AF2-335 GEN
Solar/Wind Harmer
4.495
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.281
971613AH1-306 GEN
Solar/Wind Harmer
2.071
247621Y3-024
Adder
0.148
964611AG1-324 GEN
Solar/Wind Harmer
0.32
270599AE1-208 GEN
Solar/Wind Harmer
3.883
270031AE2-169
Solar/Wind Harmer
2.33
270201AC2-176 GEN
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
4.382
964571AG1-320 GEN
Solar/Wind Harmer
3.758
253370AE2-315 SEC1
Adder
1.177
25322209TAIT E
Adder
5.698
25322209TAIT E
Adder
5.57
944541AF1-119 GEN
Solar/Wind Harmer
0.267
960971AF2-388 GEN
Solar/Wind Harmer
2.335
25326109MON D
Adder
0.742
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
2.29
966841AG1-555 GEN
Solar/Wind Harmer
0.43
970653AG2-424 GEN
Solar/Wind Harmer
1.834
970653AG2-424 GEN
Solar/Wind Harmer
0.95
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971125AH1-004 GEN
Solar/Wind Harmer
1.469
970107AG2-081 GEN
Solar/Wind Harmer
1.102
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972043AH1-570 GEN
Solar/Wind Harmer
0.949
972045AH1-571 GEN
Solar/Wind Harmer
0.76
276916AD2-100_GEN
Solar/Wind Harmer
7.418
276911AD2-131_GEN
Solar/Wind Harmer
0.489
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970321AG2-212 GEN
Solar/Wind Harmer
1.448
942891AE2-308 GEN
Solar/Wind Harmer
3.277
971081AG2-670 GEN
Solar/Wind Harmer
2.441
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.134
958491AF2-143 GEN
Solar/Wind Harmer
4.777
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.764
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.553
274674JOLIET 9 ;6U
Adder
6.975
276741O09 GEN1
Solar/Wind Harmer
0.113
276708O09 GEN2
Solar/Wind Harmer
0.113
972259AH1-714 GEN
Adder
8.636
274803UNIV PARK;6U
Adder
2.636
274808UNIV PK N;4U
Adder
2.251
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.14
274695ROCKY RD ;2P
Adder
5.022
274693ROCKY RD ;1P
Adder
4.972
274697ROCKY RD ;3P
Adder
1.364
962691AG1-118 GEN
Solar/Wind Harmer
9.438
274770LINCOLN ;1U
Adder
3.805
274771LINCOLN ;2U
Adder
3.805
970921AG2-575 GEN
Solar/Wind Harmer
3.145
970921AG2-575 GEN
Solar/Wind Harmer
1.048
276603SUBLETTE C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.288
971343AH1-151 GEN
Solar/Wind Harmer
6.288
942991AE2-321 GEN
Solar/Wind Harmer
3.508
971333AH1-146 GEN
Solar/Wind Harmer
6.283
971335AH1-147 GEN
Solar/Wind Harmer
6.283
938861AE1-114 GEN
Solar/Wind Harmer
1.78
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
3.864
965791AG1-447 GEN
Solar/Wind Harmer
2.834
24441505OLIV SLR
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0.004
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.505
274746AC1-111 G10
Adder
2.525
274744AC1-111 GEN8
Adder
2.525
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.261
274775LINCOLN ;6U
Adder
3.805
274776LINCOLN ;7U
Adder
3.805
274777LINCOLN ;8U
Adder
1.515
971675AH1-338 GEN
Solar/Wind Harmer
1.227
971171AH1-044 GEN
Solar/Wind Harmer
6.288
961011AF2-392 GEN
Solar/Wind Harmer
1.844
971681AH1-341 GEN
Solar/Wind Harmer
5.059
971177AH1-047 GEN
Solar/Wind Harmer
1.937
971411AH1-196 GEN
Solar/Wind Harmer
4.711
276612AE2-035 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.755
241972AD1-140 GEN
Solar/Wind Harmer
0.34
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
3.38
971347AH1-153 GEN
Solar/Wind Harmer
4.502
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.099
944201AF1-088_MTX
Adder
74.561
957141AF2-008_MTX
Adder
37.28
NYPJM->LTFIMP_NY
CLTF
1.072
LGEELTFEXP_LGEE->PJM
CLTF
5.218
WECLTFEXP_WEC->PJM
CLTF
1.713
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.307
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.651
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.478
MECLTFEXP_MEC->PJM
CLTF
7.273
SIGELTFEXP_SIGE->PJM
CLTF
0.331
LAGNLTFEXP_LAGN->PJM
CLTF
5.322
TVALTFEXP_TVA->PJM
CLTF
2.383

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.98 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1398.09
MW Contribution:9.39
Bus #Bus NameTypeMW Contribution
274806UNIV PK N;2U
50/50
0.42
274815UNIV PK N;XU
50/50
0.413
274816UNIV PK N;YU
50/50
0.412
274810UNIV PK N;6U
50/50
0.411
274802UNIV PARK;5U
50/50
6.592
274799UNIV PARK;2U
50/50
0.254
274800UNIV PARK;3U
50/50
5.664
972038AH1-567 GEN2
50/50
0.355
972228AH1-698 GEN2
50/50
3.594
274654BRAIDWOOD;1U
50/50
6.967
274826FISK ;BP
50/50
10.438
276772AC2-154 GEN
Solar/Wind Harmer
2.528
276806AD2-047 C O1
Solar/Wind Harmer
9.698
970941AG2-585 GEN
Solar/Wind Harmer
11.332
274676JOLIET 29;8U
Adder
26.498
276893AG1-478 C
Solar/Wind Harmer
0.371
276694AA1-018 GEN2
Solar/Wind Harmer
5.599
274729ELWOOD EC;1P
Adder
14.578
274730ELWOOD EC;6P
Adder
14.571
274734ELWOOD EC;8P
Adder
14.571
274736ELWOOD EC;9P
Adder
14.571
970707AG2-453 GEN
Solar/Wind Harmer
24.572
274772LINCOLN ;3U
Adder
5.427
276897AD1-100 C
Solar/Wind Harmer
25.29
939351AE1-166 GEN
Solar/Wind Harmer
5.167
943121AE2-341 GEN
Solar/Wind Harmer
12.792
943591AF1-030 GEN
Solar/Wind Harmer
8.528
276805AD2-038 GEN
Solar/Wind Harmer
4.369
274682WAUKEGAN ;7U
Adder
15.149
274724RIVER EC ;11
Adder
14.721
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
1.776
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274855GSG-6 ;RU
Solar/Wind Harmer
2.963
274850MENDOTA H;RU
Solar/Wind Harmer
2.06
276602WESTBROOK C
Solar/Wind Harmer
1.705
276863AD2-134 GEN
Solar/Wind Harmer
1.433
276889AE2-281 GEN
Solar/Wind Harmer
1.539
959091AF2-200 GEN
Solar/Wind Harmer
15.88
972236AH1-702 GEN2
Adder
1.726
970571AG2-364 GEN
Solar/Wind Harmer
15.364
274858EASY ROAD;U2
Solar/Wind Harmer
3.658
274760LEE CO EC;1U
Adder
7.101
274767LEE CO EC;8U
Adder
7.018
276157O29GEN1
Solar/Wind Harmer
2.812
274878BISHOP HL;2U
Solar/Wind Harmer
2.408
972231SS25-0005
Solar/Wind Harmer
6.764
972181SS23-001
Solar/Wind Harmer
4.227
274752CRETE EC ;2U
Adder
3.483
274753CRETE EC ;3U
Adder
3.483
965931AG1-462 GEN
Solar/Wind Harmer
17.758
942111AE2-223 GEN
Solar/Wind Harmer
5.197
274853TWINGROVE;U1
Solar/Wind Harmer
4.348
965091AG1-374 GEN
Solar/Wind Harmer
18.097
274813UNIV PK N;9U
50/50
0.412
274809UNIV PK N;5U
50/50
0.41
274812UNIV PK N;8U
50/50
7.514
966431AG1-512 GEN
50/50
2.631
274801UNIV PARK;4U
50/50
5.664
274655BRAIDWOOD;2U
50/50
6.565
276776AD2-060 GEN
Solar/Wind Harmer
0.383
274676JOLIET 29;8U
Adder
27.48
276691AA1-018 GEN1
Solar/Wind Harmer
0.413
274732ELWOOD EC;7P
Adder
14.571
274674JOLIET 9 ;6U
Adder
13.645
972207SS24-0001
Solar/Wind Harmer
19.295
274773LINCOLN ;4U
Adder
5.427
274774LINCOLN ;5U
Adder
5.427
941551AE2-152 GEN
Solar/Wind Harmer
3.952
276164X3-005 C
Solar/Wind Harmer
0.612
274871GR RIDGE ;2U
Solar/Wind Harmer
6.678
274745AC1-111 GEN9
Adder
4.779
274723RIVER EC ;12
Adder
15.297
274682WAUKEGAN ;7U
Adder
15.149
274828WAUKEGAN ;BP
Adder
9.288
960751AF2-366 GEN
Solar/Wind Harmer
2.356
962781AG1-127 GEN
Solar/Wind Harmer
7.81
274872LEEDK;1U
Solar/Wind Harmer
6.714
276901AD2-066 C O1
Solar/Wind Harmer
2.866
276876AE1-163_GEN2
Solar/Wind Harmer
5.388
276861AD2-134 GEN
Solar/Wind Harmer
1.433
971997AH1-543 GEN
Solar/Wind Harmer
12.542
957471AF2-041 GEN
Solar/Wind Harmer
23.82
959081AF2-199 GEN
Solar/Wind Harmer
7.94
971067AG2-660 GEN
Solar/Wind Harmer
1.846
274822ROCKFORD ;11
Adder
15.533
972235AH1-702 GEN1
Adder
1.985
970819AG2-516 GEN
Solar/Wind Harmer
9.394
939401AE1-172 GEN
Solar/Wind Harmer
10.872
971475AH1-234 GEN
Solar/Wind Harmer
17.463
970569AG2-363 GEN
Solar/Wind Harmer
23.046
274857EASY ROAD;U1
Solar/Wind Harmer
3.658
274761LEE CO EC;2U
Adder
7.101
274766LEE CO EC;7U
Adder
7.018
276158O29GEN2
Solar/Wind Harmer
3.697
274877BISHOP HL;1U
Solar/Wind Harmer
2.408
274751CRETE EC ;1U
Adder
3.483
274754CRETE EC ;4U
Adder
3.483
276726Z2-087_GEN
Solar/Wind Harmer
5.014
939741AE1-205 GEN
Solar/Wind Harmer
12.679
274854TWINGROVE;U2
Solar/Wind Harmer
4.257
270055AF2-134 C O1
Solar/Wind Helper
0.603
972175AH1-670 GEN
Solar/Wind Harmer
5.635
274814UNIV PK N;0U
50/50
7.579
274807UNIV PK N;3U
50/50
7.563
274805UNIV PK N;1U
50/50
7.53
274811UNIV PK N;7U
50/50
7.514
972037AH1-567 GEN1
50/50
0.207
972227AH1-698 GEN1
50/50
2.527
274827FISK ;RP
50/50
7.398
960591AF2-350 GEN
Solar/Wind Harmer
9.065
274675JOLIET 29;7U
Adder
27.486
274675JOLIET 29;7U
Adder
26.504
274731ELWOOD EC;2P
Adder
14.578
274733ELWOOD EC;3P
Adder
14.578
274735ELWOOD EC;4P
Adder
14.578
274728ELWOOD EC;5P
Adder
14.571
274687WILL CNTY;4U
Adder
24.725
274687WILL CNTY;4U
Adder
24.725
274775LINCOLN ;6U
Adder
5.427
274776LINCOLN ;7U
Adder
5.427
274777LINCOLN ;8U
Adder
5.427
970833AG2-524 GEN
Solar/Wind Harmer
7.599
970833AG2-524 GEN
Solar/Wind Harmer
3.534
274746AC1-111 G10
Adder
4.779
274744AC1-111 GEN8
Adder
4.779
971177AH1-047 GEN
Solar/Wind Harmer
4.765
276868AE1-113 GEN
Solar/Wind Harmer
8.223
276882AE2-255 GEN
Solar/Wind Harmer
2.741
971411AH1-196 GEN
Solar/Wind Harmer
12.107
971675AH1-338 GEN
Solar/Wind Harmer
14.448
971171AH1-044 GEN
Solar/Wind Harmer
15.88
274823ROCKFORD ;21
Adder
15.421
276612AE2-035 GEN
Solar/Wind Harmer
1.996
971681AH1-341 GEN
Solar/Wind Harmer
11.532
926823AC1-168 GEN
Solar/Wind Harmer
3.259
961011AF2-392 GEN
Solar/Wind Harmer
8.166
274863CRW1-WTG
Solar/Wind Harmer
4.174
274864CRW2-WTG
Solar/Wind Harmer
4.174
957751AF2-069 GEN
Solar/Wind Harmer
0.33
970169AG2-114 GEN
Solar/Wind Harmer
7.167
274808UNIV PK N;4U
50/50
7.481
274803UNIV PARK;6U
50/50
6.592
274798UNIV PARK;1U
50/50
0.247
274888KELLY CRK;1U
Solar/Wind Harmer
5.352
274887GEN-1.85
Solar/Wind Harmer
4.832
276843GEN-1.7
Solar/Wind Harmer
0.52
958011AF2-095 GEN
Solar/Wind Harmer
13.054
972259AH1-714 GEN
Adder
17.032
958481AF2-142 GEN
Solar/Wind Harmer
13.309
274674JOLIET 9 ;6U
Adder
13.645
274770LINCOLN ;1U
Adder
5.427
274771LINCOLN ;2U
Adder
5.427
274847GR RIDGE ;BU
Solar/Wind Harmer
4.393
958491AF2-143 GEN
Solar/Wind Harmer
12.774
971573AH1-285 GEN
Solar/Wind Harmer
7.267
274683WAUKEGAN ;8U
Adder
17.718
274683WAUKEGAN ;8U
Adder
14.936
274696ROCKY RD ;4P
Adder
9.57
274695ROCKY RD ;2P
Adder
9.35
274693ROCKY RD ;1P
Adder
9.258
274697ROCKY RD ;3P
Adder
2.54
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
962691AG1-118 GEN
Solar/Wind Harmer
24.752
970921AG2-575 GEN
Solar/Wind Harmer
8.212
970921AG2-575 GEN
Solar/Wind Harmer
1.91
942991AE2-321 GEN
Solar/Wind Harmer
8.14
274879MINONK ;1U
Solar/Wind Harmer
5.482
971333AH1-146 GEN
Solar/Wind Harmer
16.095
971335AH1-147 GEN
Solar/Wind Harmer
16.095
274848CAMPGROVE;RU
Solar/Wind Harmer
4.547
946321AF1-296 GEN
Solar/Wind Harmer
7.348
276655WTG1_EQ
Solar/Wind Harmer
5.535
276656WTG2_EQ
Solar/Wind Harmer
0.733
959341AF2-225 GEN
Solar/Wind Harmer
9.509
941731AE2-173 GEN
Solar/Wind Harmer
3.686
960681AF2-359 GEN
Solar/Wind Helper
0.941
270536AF1-215 GEN2
Solar/Wind Helper
0.905
276872AE1-163_GEN1
Solar/Wind Harmer
5.388
971341AH1-150 GEN
Solar/Wind Harmer
15.88
971343AH1-151 GEN
Solar/Wind Harmer
15.88
274856ECOGROVE ;U1
Solar/Wind Harmer
2.63
276611AD2-172 GEN
Solar/Wind Harmer
1.996
938861AE1-114 GEN
Solar/Wind Harmer
6.302
274764LEE CO EC;5U
Adder
7.118
274765LEE CO EC;6U
Adder
7.118
274762LEE CO EC;3U
Adder
7.101
274763LEE CO EC;4U
Adder
7.035
276603SUBLETTE C
Solar/Wind Harmer
0.797
972267AH1-718 GEN
Adder
3.112
276741O09 GEN1
Solar/Wind Harmer
2.641
276708O09 GEN2
Solar/Wind Harmer
2.641
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
276782AC1-033 GEN
Solar/Wind Harmer
2.846
960611AF2-352 GEN
Solar/Wind Harmer
1.403
959611AF2-252 GEN
Solar/Wind Harmer
1.403
270535AF1-215 GEN1
Solar/Wind Helper
0.905
990512J1326
External Queue
4.091670036315918
990762J1386
External Queue
10.569272994995117
990577J1339
External Queue
12.789687156677246
990582J1340
External Queue
12.789687156677246
991247J1684 G
External Queue
11.124269485473633
NYPJM->LTFIMP_NY
CLTF
0.711
WECLTFEXP_WEC->PJM
CLTF
3.017
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.272
AG2-052LTFEXP_AG2-052->PJM
LTF
0.065
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.067
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.132
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.695
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.162
MECLTFEXP_MEC->PJM
CLTF
9.375
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.33
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.932
LAGNLTFEXP_LAGN->PJM
CLTF
3.091
TVALTFEXP_TVA->PJM
CLTF
0.791

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.98 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1398.08
MW Contribution:9.39
Bus #Bus NameTypeMW Contribution
274813UNIV PK N;9U
50/50
0.412
274809UNIV PK N;5U
50/50
0.41
274812UNIV PK N;8U
50/50
7.514
966431AG1-512 GEN
50/50
2.631
274801UNIV PARK;4U
50/50
5.664
274655BRAIDWOOD;2U
50/50
6.565
276776AD2-060 GEN
Solar/Wind Harmer
0.383
274676JOLIET 29;8U
Adder
27.48
276691AA1-018 GEN1
Solar/Wind Harmer
0.413
274732ELWOOD EC;7P
Adder
14.571
274674JOLIET 9 ;6U
Adder
13.645
972207SS24-0001
Solar/Wind Harmer
19.297
274773LINCOLN ;4U
Adder
5.427
274774LINCOLN ;5U
Adder
5.427
941551AE2-152 GEN
Solar/Wind Harmer
3.952
276164X3-005 C
Solar/Wind Harmer
0.612
274871GR RIDGE ;2U
Solar/Wind Harmer
6.678
274745AC1-111 GEN9
Adder
4.779
274723RIVER EC ;12
Adder
15.297
274682WAUKEGAN ;7U
Adder
15.148
274828WAUKEGAN ;BP
Adder
9.287
960751AF2-366 GEN
Solar/Wind Harmer
2.356
962781AG1-127 GEN
Solar/Wind Harmer
7.81
274872LEEDK;1U
Solar/Wind Harmer
6.714
276901AD2-066 C O1
Solar/Wind Harmer
2.866
276876AE1-163_GEN2
Solar/Wind Harmer
5.388
276861AD2-134 GEN
Solar/Wind Harmer
1.433
971997AH1-543 GEN
Solar/Wind Harmer
12.542
957471AF2-041 GEN
Solar/Wind Harmer
23.819
959081AF2-199 GEN
Solar/Wind Harmer
7.94
971067AG2-660 GEN
Solar/Wind Harmer
1.846
274822ROCKFORD ;11
Adder
15.533
972235AH1-702 GEN1
Adder
1.985
970819AG2-516 GEN
Solar/Wind Harmer
9.393
939401AE1-172 GEN
Solar/Wind Harmer
10.873
274814UNIV PK N;0U
50/50
7.579
274807UNIV PK N;3U
50/50
7.563
274805UNIV PK N;1U
50/50
7.53
274811UNIV PK N;7U
50/50
7.514
972037AH1-567 GEN1
50/50
0.207
972227AH1-698 GEN1
50/50
2.527
274827FISK ;RP
50/50
7.398
960591AF2-350 GEN
Solar/Wind Harmer
9.065
274675JOLIET 29;7U
Adder
27.486
274675JOLIET 29;7U
Adder
26.504
274731ELWOOD EC;2P
Adder
14.578
274733ELWOOD EC;3P
Adder
14.578
274735ELWOOD EC;4P
Adder
14.578
274728ELWOOD EC;5P
Adder
14.571
274687WILL CNTY;4U
Adder
24.725
274687WILL CNTY;4U
Adder
24.725
274775LINCOLN ;6U
Adder
5.427
274776LINCOLN ;7U
Adder
5.427
274777LINCOLN ;8U
Adder
5.427
970833AG2-524 GEN
Solar/Wind Harmer
7.599
970833AG2-524 GEN
Solar/Wind Harmer
3.534
274746AC1-111 G10
Adder
4.779
274744AC1-111 GEN8
Adder
4.779
971177AH1-047 GEN
Solar/Wind Harmer
4.765
276868AE1-113 GEN
Solar/Wind Harmer
8.223
276882AE2-255 GEN
Solar/Wind Harmer
2.741
971411AH1-196 GEN
Solar/Wind Harmer
12.107
971675AH1-338 GEN
Solar/Wind Harmer
14.448
971171AH1-044 GEN
Solar/Wind Harmer
15.88
274823ROCKFORD ;21
Adder
15.421
276612AE2-035 GEN
Solar/Wind Harmer
1.996
274808UNIV PK N;4U
50/50
7.481
274803UNIV PARK;6U
50/50
6.592
274798UNIV PARK;1U
50/50
0.247
274888KELLY CRK;1U
Solar/Wind Harmer
5.352
274887GEN-1.85
Solar/Wind Harmer
4.832
276843GEN-1.7
Solar/Wind Harmer
0.52
958011AF2-095 GEN
Solar/Wind Harmer
13.054
972259AH1-714 GEN
Adder
17.031
958481AF2-142 GEN
Solar/Wind Harmer
13.309
274674JOLIET 9 ;6U
Adder
13.645
274770LINCOLN ;1U
Adder
5.427
274771LINCOLN ;2U
Adder
5.427
274847GR RIDGE ;BU
Solar/Wind Harmer
4.393
958491AF2-143 GEN
Solar/Wind Harmer
12.774
971573AH1-285 GEN
Solar/Wind Harmer
7.266
274683WAUKEGAN ;8U
Adder
17.718
274683WAUKEGAN ;8U
Adder
14.935
274696ROCKY RD ;4P
Adder
9.57
274695ROCKY RD ;2P
Adder
9.35
274693ROCKY RD ;1P
Adder
9.258
274697ROCKY RD ;3P
Adder
2.54
274861TOP CROP ;1U
Solar/Wind Harmer
5.001
274862TOP CROP ;2U
Solar/Wind Harmer
4.176
962691AG1-118 GEN
Solar/Wind Harmer
24.752
970921AG2-575 GEN
Solar/Wind Harmer
8.212
970921AG2-575 GEN
Solar/Wind Harmer
1.91
942991AE2-321 GEN
Solar/Wind Harmer
8.14
274879MINONK ;1U
Solar/Wind Harmer
5.482
971333AH1-146 GEN
Solar/Wind Harmer
16.094
971335AH1-147 GEN
Solar/Wind Harmer
16.094
276872AE1-163_GEN1
Solar/Wind Harmer
5.388
971341AH1-150 GEN
Solar/Wind Harmer
15.88
971343AH1-151 GEN
Solar/Wind Harmer
15.88
274856ECOGROVE ;U1
Solar/Wind Harmer
2.63
276611AD2-172 GEN
Solar/Wind Harmer
1.996
938861AE1-114 GEN
Solar/Wind Harmer
6.302
274764LEE CO EC;5U
Adder
7.118
274765LEE CO EC;6U
Adder
7.118
274762LEE CO EC;3U
Adder
7.101
274763LEE CO EC;4U
Adder
7.034
276603SUBLETTE C
Solar/Wind Harmer
0.797
972267AH1-718 GEN
Adder
3.112
276741O09 GEN1
Solar/Wind Harmer
2.641
276708O09 GEN2
Solar/Wind Harmer
2.641
274851PROVIDENC;RU
Solar/Wind Harmer
2.05
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.964
276646AC1-214 GEN2
Solar/Wind Harmer
0.964
276782AC1-033 GEN
Solar/Wind Harmer
2.846
960611AF2-352 GEN
Solar/Wind Harmer
1.403
971681AH1-341 GEN
Solar/Wind Harmer
11.532
926823AC1-168 GEN
Solar/Wind Harmer
3.259
961011AF2-392 GEN
Solar/Wind Harmer
8.166
274863CRW1-WTG
Solar/Wind Harmer
4.174
274864CRW2-WTG
Solar/Wind Harmer
4.174
957751AF2-069 GEN
Solar/Wind Harmer
0.33
970169AG2-114 GEN
Solar/Wind Harmer
7.167
274848CAMPGROVE;RU
Solar/Wind Harmer
4.547
946321AF1-296 GEN
Solar/Wind Harmer
7.348
276655WTG1_EQ
Solar/Wind Harmer
5.535
276656WTG2_EQ
Solar/Wind Harmer
0.733
959341AF2-225 GEN
Solar/Wind Harmer
9.509
941731AE2-173 GEN
Solar/Wind Harmer
3.686
960681AF2-359 GEN
Solar/Wind Helper
0.941
270536AF1-215 GEN2
Solar/Wind Helper
0.905
971475AH1-234 GEN
Solar/Wind Harmer
17.463
970569AG2-363 GEN
Solar/Wind Harmer
23.045
274857EASY ROAD;U1
Solar/Wind Harmer
3.658
274761LEE CO EC;2U
Adder
7.101
274766LEE CO EC;7U
Adder
7.018
276158O29GEN2
Solar/Wind Harmer
3.697
274877BISHOP HL;1U
Solar/Wind Harmer
2.408
274751CRETE EC ;1U
Adder
3.484
274754CRETE EC ;4U
Adder
3.484
276726Z2-087_GEN
Solar/Wind Harmer
5.014
939741AE1-205 GEN
Solar/Wind Harmer
12.679
274854TWINGROVE;U2
Solar/Wind Harmer
4.257
270055AF2-134 C O1
Solar/Wind Helper
0.603
972175AH1-670 GEN
Solar/Wind Harmer
5.635
274806UNIV PK N;2U
50/50
0.42
274815UNIV PK N;XU
50/50
0.413
274816UNIV PK N;YU
50/50
0.412
274810UNIV PK N;6U
50/50
0.411
274802UNIV PARK;5U
50/50
6.592
274799UNIV PARK;2U
50/50
0.254
274800UNIV PARK;3U
50/50
5.664
972038AH1-567 GEN2
50/50
0.355
972228AH1-698 GEN2
50/50
3.594
274654BRAIDWOOD;1U
50/50
6.967
274826FISK ;BP
50/50
10.438
276772AC2-154 GEN
Solar/Wind Harmer
2.528
276806AD2-047 C O1
Solar/Wind Harmer
9.698
970941AG2-585 GEN
Solar/Wind Harmer
11.332
274676JOLIET 29;8U
Adder
26.498
276893AG1-478 C
Solar/Wind Harmer
0.371
276694AA1-018 GEN2
Solar/Wind Harmer
5.599
274729ELWOOD EC;1P
Adder
14.578
274730ELWOOD EC;6P
Adder
14.571
274734ELWOOD EC;8P
Adder
14.571
274736ELWOOD EC;9P
Adder
14.571
970707AG2-453 GEN
Solar/Wind Harmer
24.571
274772LINCOLN ;3U
Adder
5.427
276897AD1-100 C
Solar/Wind Harmer
25.29
939351AE1-166 GEN
Solar/Wind Harmer
5.167
943121AE2-341 GEN
Solar/Wind Harmer
12.792
943591AF1-030 GEN
Solar/Wind Harmer
8.528
276805AD2-038 GEN
Solar/Wind Harmer
4.369
274682WAUKEGAN ;7U
Adder
15.148
274724RIVER EC ;11
Adder
14.721
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
1.776
946671AF1-331 GEN
Solar/Wind Harmer
0.336
276889AE2-281 GEN
Solar/Wind Harmer
1.539
274855GSG-6 ;RU
Solar/Wind Harmer
2.963
274850MENDOTA H;RU
Solar/Wind Harmer
2.06
276602WESTBROOK C
Solar/Wind Harmer
1.705
276863AD2-134 GEN
Solar/Wind Harmer
1.433
959091AF2-200 GEN
Solar/Wind Harmer
15.88
972236AH1-702 GEN2
Adder
1.726
970571AG2-364 GEN
Solar/Wind Harmer
15.364
274858EASY ROAD;U2
Solar/Wind Harmer
3.658
274760LEE CO EC;1U
Adder
7.101
274767LEE CO EC;8U
Adder
7.018
276157O29GEN1
Solar/Wind Harmer
2.812
274878BISHOP HL;2U
Solar/Wind Harmer
2.408
972231SS25-0005
Solar/Wind Harmer
6.764
972181SS23-001
Solar/Wind Harmer
4.227
274752CRETE EC ;2U
Adder
3.484
274753CRETE EC ;3U
Adder
3.484
965931AG1-462 GEN
Solar/Wind Harmer
17.757
942111AE2-223 GEN
Solar/Wind Harmer
5.197
274853TWINGROVE;U1
Solar/Wind Harmer
4.348
965091AG1-374 GEN
Solar/Wind Harmer
18.097
959611AF2-252 GEN
Solar/Wind Harmer
1.403
270535AF1-215 GEN1
Solar/Wind Helper
0.905
990512J1326
External Queue
4.09160041809082
990762J1386
External Queue
10.569356918334961
990577J1339
External Queue
12.789840698242188
990582J1340
External Queue
12.789840698242188
991247J1684 G
External Queue
11.124429702758789
NYPJM->LTFIMP_NY
CLTF
0.711
WECLTFEXP_WEC->PJM
CLTF
3.017
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.067
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.272
AG2-052LTFEXP_AG2-052->PJM
LTF
0.065
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.132
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.694
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.162
MECLTFEXP_MEC->PJM
CLTF
9.375
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.33
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.932
LAGNLTFEXP_LAGN->PJM
CLTF
3.091
TVALTFEXP_TVA->PJM
CLTF
0.791

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.68 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1395.14
MW Contribution:9.32
Bus #Bus NameTypeMW Contribution
274806UNIV PK N;2U
50/50
0.416
274815UNIV PK N;XU
50/50
0.409
274816UNIV PK N;YU
50/50
0.408
274810UNIV PK N;6U
50/50
0.407
274802UNIV PARK;5U
50/50
6.523
274799UNIV PARK;2U
50/50
0.251
274800UNIV PARK;3U
50/50
5.597
972038AH1-567 GEN2
50/50
0.35
972228AH1-698 GEN2
50/50
3.555
274654BRAIDWOOD;1U
50/50
6.89
274826FISK ;BP
50/50
10.309
276772AC2-154 GEN
Solar/Wind Harmer
2.499
276806AD2-047 C O1
Solar/Wind Harmer
9.585
970941AG2-585 GEN
Solar/Wind Harmer
11.199
274676JOLIET 29;8U
Adder
26.21
276694AA1-018 GEN2
Solar/Wind Harmer
5.545
276893AG1-478 C
Solar/Wind Harmer
0.367
274729ELWOOD EC;1P
Adder
14.423
274730ELWOOD EC;6P
Adder
14.416
274734ELWOOD EC;8P
Adder
14.416
274736ELWOOD EC;9P
Adder
14.416
970707AG2-453 GEN
Solar/Wind Harmer
24.323
274772LINCOLN ;3U
Adder
5.362
276897AD1-100 C
Solar/Wind Harmer
25.021
939351AE1-166 GEN
Solar/Wind Harmer
5.113
274813UNIV PK N;9U
50/50
0.408
274809UNIV PK N;5U
50/50
0.406
274812UNIV PK N;8U
50/50
7.449
966431AG1-512 GEN
50/50
2.608
274801UNIV PARK;4U
50/50
5.597
274655BRAIDWOOD;2U
50/50
6.493
276776AD2-060 GEN
Solar/Wind Harmer
0.379
274676JOLIET 29;8U
Adder
27.181
276691AA1-018 GEN1
Solar/Wind Harmer
0.409
274732ELWOOD EC;7P
Adder
14.416
274674JOLIET 9 ;6U
Adder
13.499
972207SS24-0001
Solar/Wind Harmer
19.066
274773LINCOLN ;4U
Adder
5.362
274774LINCOLN ;5U
Adder
5.362
941551AE2-152 GEN
Solar/Wind Harmer
3.91
274871GR RIDGE ;2U
Solar/Wind Harmer
6.612
276164X3-005 C
Solar/Wind Harmer
0.603
274745AC1-111 GEN9
Adder
4.732
274723RIVER EC ;12
Adder
15.056
274682WAUKEGAN ;7U
Adder
15.002
274814UNIV PK N;0U
50/50
7.514
274807UNIV PK N;3U
50/50
7.497
274805UNIV PK N;1U
50/50
7.465
274811UNIV PK N;7U
50/50
7.449
972037AH1-567 GEN1
50/50
0.205
972227AH1-698 GEN1
50/50
2.499
274827FISK ;RP
50/50
7.306
960591AF2-350 GEN
Solar/Wind Harmer
8.959
274675JOLIET 29;7U
Adder
27.187
274675JOLIET 29;7U
Adder
26.216
274731ELWOOD EC;2P
Adder
14.423
274733ELWOOD EC;3P
Adder
14.423
274735ELWOOD EC;4P
Adder
14.423
274728ELWOOD EC;5P
Adder
14.416
274687WILL CNTY;4U
Adder
24.446
274687WILL CNTY;4U
Adder
24.446
274775LINCOLN ;6U
Adder
5.362
274776LINCOLN ;7U
Adder
5.362
274777LINCOLN ;8U
Adder
5.362
970833AG2-524 GEN
Solar/Wind Harmer
7.523
970833AG2-524 GEN
Solar/Wind Harmer
3.499
943121AE2-341 GEN
Solar/Wind Harmer
12.668
943591AF1-030 GEN
Solar/Wind Harmer
8.445
276805AD2-038 GEN
Solar/Wind Harmer
4.329
274682WAUKEGAN ;7U
Adder
15.002
274724RIVER EC ;11
Adder
14.481
274872LEEDK;1U
Solar/Wind Harmer
0.207
276799AD1-013 GEN
Solar/Wind Harmer
1.761
946671AF1-331 GEN
Solar/Wind Harmer
0.333
276889AE2-281 GEN
Solar/Wind Harmer
1.527
274855GSG-6 ;RU
Solar/Wind Harmer
2.938
274850MENDOTA H;RU
Solar/Wind Harmer
2.043
276602WESTBROOK C
Solar/Wind Harmer
1.691
276863AD2-134 GEN
Solar/Wind Harmer
1.421
959091AF2-200 GEN
Solar/Wind Harmer
15.747
972236AH1-702 GEN2
Adder
1.712
970571AG2-364 GEN
Solar/Wind Harmer
15.25
274858EASY ROAD;U2
Solar/Wind Harmer
3.63
274760LEE CO EC;1U
Adder
7.048
274767LEE CO EC;8U
Adder
6.965
276157O29GEN1
Solar/Wind Harmer
2.794
274878BISHOP HL;2U
Solar/Wind Harmer
2.395
972231SS25-0005
Solar/Wind Harmer
6.635
972181SS23-001
Solar/Wind Harmer
4.147
274752CRETE EC ;2U
Adder
3.417
274753CRETE EC ;3U
Adder
3.417
965931AG1-462 GEN
Solar/Wind Harmer
17.661
942111AE2-223 GEN
Solar/Wind Harmer
5.19
274853TWINGROVE;U1
Solar/Wind Harmer
4.349
965091AG1-374 GEN
Solar/Wind Harmer
18.101
959611AF2-252 GEN
Solar/Wind Harmer
1.403
270535AF1-215 GEN1
Solar/Wind Helper
0.899
274828WAUKEGAN ;BP
Adder
9.198
960751AF2-366 GEN
Solar/Wind Harmer
2.335
962781AG1-127 GEN
Solar/Wind Harmer
7.74
274872LEEDK;1U
Solar/Wind Harmer
6.654
276901AD2-066 C O1
Solar/Wind Harmer
2.841
276876AE1-163_GEN2
Solar/Wind Harmer
5.344
276861AD2-134 GEN
Solar/Wind Harmer
1.421
971997AH1-543 GEN
Solar/Wind Harmer
12.44
957471AF2-041 GEN
Solar/Wind Harmer
23.621
959081AF2-199 GEN
Solar/Wind Harmer
7.874
971067AG2-660 GEN
Solar/Wind Harmer
1.831
274822ROCKFORD ;11
Adder
15.404
972235AH1-702 GEN1
Adder
1.968
970819AG2-516 GEN
Solar/Wind Harmer
9.317
939401AE1-172 GEN
Solar/Wind Harmer
10.787
971475AH1-234 GEN
Solar/Wind Harmer
17.322
970569AG2-363 GEN
Solar/Wind Harmer
22.875
274857EASY ROAD;U1
Solar/Wind Harmer
3.63
274761LEE CO EC;2U
Adder
7.048
274766LEE CO EC;7U
Adder
6.965
276158O29GEN2
Solar/Wind Harmer
3.673
274877BISHOP HL;1U
Solar/Wind Harmer
2.395
274751CRETE EC ;1U
Adder
3.417
274754CRETE EC ;4U
Adder
3.417
276726Z2-087_GEN
Solar/Wind Harmer
5.007
939741AE1-205 GEN
Solar/Wind Harmer
12.661
274854TWINGROVE;U2
Solar/Wind Harmer
4.258
972175AH1-670 GEN
Solar/Wind Harmer
7.462
270055AF2-134 C O1
Solar/Wind Helper
0.6
274808UNIV PK N;4U
50/50
7.416
274803UNIV PARK;6U
50/50
6.523
274798UNIV PARK;1U
50/50
0.244
274888KELLY CRK;1U
Solar/Wind Harmer
5.29
274887GEN-1.85
Solar/Wind Harmer
4.776
276843GEN-1.7
Solar/Wind Harmer
0.514
958011AF2-095 GEN
Solar/Wind Harmer
12.901
972259AH1-714 GEN
Adder
16.853
958481AF2-142 GEN
Solar/Wind Harmer
13.181
274674JOLIET 9 ;6U
Adder
13.499
274770LINCOLN ;1U
Adder
5.362
274771LINCOLN ;2U
Adder
5.362
274847GR RIDGE ;BU
Solar/Wind Harmer
4.349
958491AF2-143 GEN
Solar/Wind Harmer
12.659
971573AH1-285 GEN
Solar/Wind Harmer
7.197
274683WAUKEGAN ;8U
Adder
17.548
274746AC1-111 G10
Adder
4.732
274744AC1-111 GEN8
Adder
4.732
971177AH1-047 GEN
Solar/Wind Harmer
4.723
276868AE1-113 GEN
Solar/Wind Harmer
8.151
276882AE2-255 GEN
Solar/Wind Harmer
2.717
971411AH1-196 GEN
Solar/Wind Harmer
12.002
971675AH1-338 GEN
Solar/Wind Harmer
14.325
971171AH1-044 GEN
Solar/Wind Harmer
15.747
274823ROCKFORD ;21
Adder
15.292
276612AE2-035 GEN
Solar/Wind Harmer
1.98
971681AH1-341 GEN
Solar/Wind Harmer
11.444
926823AC1-168 GEN
Solar/Wind Harmer
3.237
961011AF2-392 GEN
Solar/Wind Harmer
8.107
274863CRW1-WTG
Solar/Wind Harmer
4.147
274864CRW2-WTG
Solar/Wind Harmer
4.147
957751AF2-069 GEN
Solar/Wind Harmer
0.329
970169AG2-114 GEN
Solar/Wind Harmer
7.129
274848CAMPGROVE;RU
Solar/Wind Harmer
4.524
946321AF1-296 GEN
Solar/Wind Harmer
7.306
276655WTG1_EQ
Solar/Wind Harmer
5.527
276656WTG2_EQ
Solar/Wind Harmer
0.732
959341AF2-225 GEN
Solar/Wind Harmer
9.496
941731AE2-173 GEN
Solar/Wind Harmer
3.681
960681AF2-359 GEN
Solar/Wind Helper
0.98
270536AF1-215 GEN2
Solar/Wind Helper
0.899
274683WAUKEGAN ;8U
Adder
14.792
274696ROCKY RD ;4P
Adder
9.479
274695ROCKY RD ;2P
Adder
9.261
274693ROCKY RD ;1P
Adder
9.17
274697ROCKY RD ;3P
Adder
2.516
962691AG1-118 GEN
Solar/Wind Harmer
24.527
274861TOP CROP ;1U
Solar/Wind Harmer
4.949
274862TOP CROP ;2U
Solar/Wind Harmer
4.133
970921AG2-575 GEN
Solar/Wind Harmer
8.138
970921AG2-575 GEN
Solar/Wind Harmer
1.893
942991AE2-321 GEN
Solar/Wind Harmer
8.067
274879MINONK ;1U
Solar/Wind Harmer
5.434
971333AH1-146 GEN
Solar/Wind Harmer
15.955
971335AH1-147 GEN
Solar/Wind Harmer
15.955
276872AE1-163_GEN1
Solar/Wind Harmer
5.344
971341AH1-150 GEN
Solar/Wind Harmer
15.747
971343AH1-151 GEN
Solar/Wind Harmer
15.747
274856ECOGROVE ;U1
Solar/Wind Harmer
2.609
276611AD2-172 GEN
Solar/Wind Harmer
1.98
938861AE1-114 GEN
Solar/Wind Harmer
6.254
274764LEE CO EC;5U
Adder
7.065
274765LEE CO EC;6U
Adder
7.065
274762LEE CO EC;3U
Adder
7.048
274763LEE CO EC;4U
Adder
6.982
276603SUBLETTE C
Solar/Wind Harmer
0.791
972267AH1-718 GEN
Adder
3.09
276741O09 GEN1
Solar/Wind Harmer
2.623
276708O09 GEN2
Solar/Wind Harmer
2.623
274851PROVIDENC;RU
Solar/Wind Harmer
2.038
274849CRESCENT ;1U
Solar/Wind Harmer
1.323
276645AC1-214 GEN1
Solar/Wind Harmer
0.959
276646AC1-214 GEN2
Solar/Wind Harmer
0.959
276782AC1-033 GEN
Solar/Wind Harmer
2.83
960611AF2-352 GEN
Solar/Wind Harmer
1.403
990512J1326
External Queue
4.058994293212891
990762J1386
External Queue
10.426873207092285
990577J1339
External Queue
12.542115211486816
990582J1340
External Queue
12.542115211486816
991247J1684 G
External Queue
9.0523099899292
NYPJM->LTFIMP_NY
CLTF
0.71
WECLTFEXP_WEC->PJM
CLTF
2.992
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.234
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.414
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.107
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.463
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.563
MECLTFEXP_MEC->PJM
CLTF
9.373
SIGELTFEXP_SIGE->PJM
CLTF
0.019
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.204
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.549
LAGNLTFEXP_LAGN->PJM
CLTF
3.247
TVALTFEXP_TVA->PJM
CLTF
0.883

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.91 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1387.63
MW Contribution:9.34
Bus #Bus NameTypeMW Contribution
274808UNIV PK N;4U
50/50
7.45
274803UNIV PARK;6U
50/50
6.556
274798UNIV PARK;1U
50/50
0.245
274888KELLY CRK;1U
Solar/Wind Harmer
5.319
274887GEN-1.85
Solar/Wind Harmer
4.802
276843GEN-1.7
Solar/Wind Harmer
0.517
958011AF2-095 GEN
Solar/Wind Harmer
12.972
972259AH1-714 GEN
Adder
16.931
958481AF2-142 GEN
Solar/Wind Harmer
13.23
274674JOLIET 9 ;6U
Adder
13.563
274770LINCOLN ;1U
Adder
5.389
274771LINCOLN ;2U
Adder
5.389
274847GR RIDGE ;BU
Solar/Wind Harmer
4.367
958491AF2-143 GEN
Solar/Wind Harmer
12.698
971573AH1-285 GEN
Solar/Wind Harmer
7.224
274683WAUKEGAN ;8U
Adder
17.613
274683WAUKEGAN ;8U
Adder
14.847
274695ROCKY RD ;2P
Adder
9.295
274693ROCKY RD ;1P
Adder
9.203
274697ROCKY RD ;3P
Adder
2.525
274696ROCKY RD ;4P
Adder
9.514
962691AG1-118 GEN
Solar/Wind Harmer
24.607
274861TOP CROP ;1U
Solar/Wind Harmer
4.969
274862TOP CROP ;2U
Solar/Wind Harmer
4.15
970921AG2-575 GEN
Solar/Wind Harmer
8.164
970921AG2-575 GEN
Solar/Wind Harmer
1.899
942991AE2-321 GEN
Solar/Wind Harmer
8.092
274879MINONK ;1U
Solar/Wind Harmer
5.449
971333AH1-146 GEN
Solar/Wind Harmer
16
971335AH1-147 GEN
Solar/Wind Harmer
16
276872AE1-163_GEN1
Solar/Wind Harmer
5.356
971341AH1-150 GEN
Solar/Wind Harmer
15.786
971343AH1-151 GEN
Solar/Wind Harmer
15.786
274856ECOGROVE ;U1
Solar/Wind Harmer
2.614
276611AD2-172 GEN
Solar/Wind Harmer
1.984
938861AE1-114 GEN
Solar/Wind Harmer
6.265
274764LEE CO EC;5U
Adder
7.076
274765LEE CO EC;6U
Adder
7.076
274762LEE CO EC;3U
Adder
7.059
274763LEE CO EC;4U
Adder
6.993
276603SUBLETTE C
Solar/Wind Harmer
0.792
972267AH1-718 GEN
Adder
3.094
276741O09 GEN1
Solar/Wind Harmer
2.625
276708O09 GEN2
Solar/Wind Harmer
2.625
274851PROVIDENC;RU
Solar/Wind Harmer
2.038
274849CRESCENT ;1U
Solar/Wind Harmer
1.323
276645AC1-214 GEN1
Solar/Wind Harmer
0.958
276646AC1-214 GEN2
Solar/Wind Harmer
0.958
276782AC1-033 GEN
Solar/Wind Harmer
2.829
960611AF2-352 GEN
Solar/Wind Harmer
1.394
274806UNIV PK N;2U
50/50
0.418
274815UNIV PK N;XU
50/50
0.411
274816UNIV PK N;YU
50/50
0.41
274810UNIV PK N;6U
50/50
0.409
274802UNIV PARK;5U
50/50
6.556
274799UNIV PARK;2U
50/50
0.253
274800UNIV PARK;3U
50/50
5.629
972038AH1-567 GEN2
50/50
0.352
972228AH1-698 GEN2
50/50
3.572
274654BRAIDWOOD;1U
50/50
6.925
274826FISK ;BP
50/50
10.371
276772AC2-154 GEN
Solar/Wind Harmer
2.512
276806AD2-047 C O1
Solar/Wind Harmer
9.637
970941AG2-585 GEN
Solar/Wind Harmer
11.261
274676JOLIET 29;8U
Adder
26.339
276893AG1-478 C
Solar/Wind Harmer
0.368
276694AA1-018 GEN2
Solar/Wind Harmer
5.566
274729ELWOOD EC;1P
Adder
14.49
274730ELWOOD EC;6P
Adder
14.483
274734ELWOOD EC;8P
Adder
14.483
274736ELWOOD EC;9P
Adder
14.483
970707AG2-453 GEN
Solar/Wind Harmer
24.431
274772LINCOLN ;3U
Adder
5.389
276897AD1-100 C
Solar/Wind Harmer
25.129
939351AE1-166 GEN
Solar/Wind Harmer
5.135
943121AE2-341 GEN
Solar/Wind Harmer
12.718
943591AF1-030 GEN
Solar/Wind Harmer
8.479
276805AD2-038 GEN
Solar/Wind Harmer
4.343
274682WAUKEGAN ;7U
Adder
15.058
274724RIVER EC ;11
Adder
14.609
274872LEEDK;1U
Solar/Wind Harmer
0.208
276799AD1-013 GEN
Solar/Wind Harmer
1.766
946671AF1-331 GEN
Solar/Wind Harmer
0.334
274855GSG-6 ;RU
Solar/Wind Harmer
2.945
274850MENDOTA H;RU
Solar/Wind Harmer
2.048
276602WESTBROOK C
Solar/Wind Harmer
1.695
276863AD2-134 GEN
Solar/Wind Harmer
1.424
276889AE2-281 GEN
Solar/Wind Harmer
1.53
959091AF2-200 GEN
Solar/Wind Harmer
15.786
972236AH1-702 GEN2
Adder
1.716
970571AG2-364 GEN
Solar/Wind Harmer
15.271
274858EASY ROAD;U2
Solar/Wind Harmer
3.636
274760LEE CO EC;1U
Adder
7.059
274767LEE CO EC;8U
Adder
6.976
276157O29GEN1
Solar/Wind Harmer
2.796
274878BISHOP HL;2U
Solar/Wind Harmer
2.394
972231SS25-0005
Solar/Wind Harmer
6.706
972181SS23-001
Solar/Wind Harmer
4.191
274752CRETE EC ;2U
Adder
3.454
274753CRETE EC ;3U
Adder
3.454
965931AG1-462 GEN
Solar/Wind Harmer
17.652
942111AE2-223 GEN
Solar/Wind Harmer
5.164
274853TWINGROVE;U1
Solar/Wind Harmer
4.32
965091AG1-374 GEN
Solar/Wind Harmer
17.983
959611AF2-252 GEN
Solar/Wind Harmer
1.394
270535AF1-215 GEN1
Solar/Wind Helper
0.913
274814UNIV PK N;0U
50/50
7.548
274807UNIV PK N;3U
50/50
7.531
274805UNIV PK N;1U
50/50
7.499
274811UNIV PK N;7U
50/50
7.482
972037AH1-567 GEN1
50/50
0.206
972227AH1-698 GEN1
50/50
2.511
274827FISK ;RP
50/50
7.35
960591AF2-350 GEN
Solar/Wind Harmer
9.008
274675JOLIET 29;7U
Adder
27.32
274675JOLIET 29;7U
Adder
26.345
274731ELWOOD EC;2P
Adder
14.49
274733ELWOOD EC;3P
Adder
14.49
274735ELWOOD EC;4P
Adder
14.49
274728ELWOOD EC;5P
Adder
14.483
274687WILL CNTY;4U
Adder
24.572
274687WILL CNTY;4U
Adder
24.572
274775LINCOLN ;6U
Adder
5.389
274776LINCOLN ;7U
Adder
5.389
274777LINCOLN ;8U
Adder
5.389
970833AG2-524 GEN
Solar/Wind Harmer
7.554
970833AG2-524 GEN
Solar/Wind Harmer
3.513
274746AC1-111 G10
Adder
4.751
274744AC1-111 GEN8
Adder
4.751
971177AH1-047 GEN
Solar/Wind Harmer
4.737
276868AE1-113 GEN
Solar/Wind Harmer
8.173
276882AE2-255 GEN
Solar/Wind Harmer
2.725
971411AH1-196 GEN
Solar/Wind Harmer
12.036
971675AH1-338 GEN
Solar/Wind Harmer
14.363
971171AH1-044 GEN
Solar/Wind Harmer
15.786
274823ROCKFORD ;21
Adder
15.33
276612AE2-035 GEN
Solar/Wind Harmer
1.984
971681AH1-341 GEN
Solar/Wind Harmer
11.464
926823AC1-168 GEN
Solar/Wind Harmer
3.24
961011AF2-392 GEN
Solar/Wind Harmer
8.117
274863CRW1-WTG
Solar/Wind Harmer
4.148
274864CRW2-WTG
Solar/Wind Harmer
4.148
957751AF2-069 GEN
Solar/Wind Harmer
0.328
970169AG2-114 GEN
Solar/Wind Harmer
7.122
274848CAMPGROVE;RU
Solar/Wind Harmer
4.52
946321AF1-296 GEN
Solar/Wind Harmer
7.304
276655WTG1_EQ
Solar/Wind Harmer
5.5
276656WTG2_EQ
Solar/Wind Harmer
0.728
959341AF2-225 GEN
Solar/Wind Harmer
9.45
941731AE2-173 GEN
Solar/Wind Harmer
3.663
960681AF2-359 GEN
Solar/Wind Helper
0.953
270536AF1-215 GEN2
Solar/Wind Helper
0.913
274813UNIV PK N;9U
50/50
0.41
274809UNIV PK N;5U
50/50
0.408
274812UNIV PK N;8U
50/50
7.482
966431AG1-512 GEN
50/50
2.62
274801UNIV PARK;4U
50/50
5.629
274655BRAIDWOOD;2U
50/50
6.525
276776AD2-060 GEN
Solar/Wind Harmer
0.381
274676JOLIET 29;8U
Adder
27.314
276691AA1-018 GEN1
Solar/Wind Harmer
0.411
274732ELWOOD EC;7P
Adder
14.483
274674JOLIET 9 ;6U
Adder
13.563
972207SS24-0001
Solar/Wind Harmer
19.162
274773LINCOLN ;4U
Adder
5.389
274774LINCOLN ;5U
Adder
5.389
941551AE2-152 GEN
Solar/Wind Harmer
3.927
276164X3-005 C
Solar/Wind Harmer
0.607
274871GR RIDGE ;2U
Solar/Wind Harmer
6.638
274745AC1-111 GEN9
Adder
4.751
274723RIVER EC ;12
Adder
15.184
274682WAUKEGAN ;7U
Adder
15.058
274828WAUKEGAN ;BP
Adder
9.232
960751AF2-366 GEN
Solar/Wind Harmer
2.342
962781AG1-127 GEN
Solar/Wind Harmer
7.764
274872LEEDK;1U
Solar/Wind Harmer
6.675
276901AD2-066 C O1
Solar/Wind Harmer
2.849
276861AD2-134 GEN
Solar/Wind Harmer
1.424
276876AE1-163_GEN2
Solar/Wind Harmer
5.356
971997AH1-543 GEN
Solar/Wind Harmer
12.467
957471AF2-041 GEN
Solar/Wind Harmer
23.679
959081AF2-199 GEN
Solar/Wind Harmer
7.893
971067AG2-660 GEN
Solar/Wind Harmer
1.836
274822ROCKFORD ;11
Adder
15.442
972235AH1-702 GEN1
Adder
1.973
970819AG2-516 GEN
Solar/Wind Harmer
9.338
939401AE1-172 GEN
Solar/Wind Harmer
10.803
971475AH1-234 GEN
Solar/Wind Harmer
17.36
970569AG2-363 GEN
Solar/Wind Harmer
22.906
274857EASY ROAD;U1
Solar/Wind Harmer
3.636
274761LEE CO EC;2U
Adder
7.059
274766LEE CO EC;7U
Adder
6.976
276158O29GEN2
Solar/Wind Harmer
3.675
274877BISHOP HL;1U
Solar/Wind Harmer
2.394
274751CRETE EC ;1U
Adder
3.454
274754CRETE EC ;4U
Adder
3.454
276726Z2-087_GEN
Solar/Wind Harmer
4.983
939741AE1-205 GEN
Solar/Wind Harmer
12.599
274854TWINGROVE;U2
Solar/Wind Harmer
4.23
270055AF2-134 C O1
Solar/Wind Helper
0.609
972175AH1-670 GEN
Solar/Wind Harmer
5.599
990512J1326
External Queue
4.075714588165283
990762J1386
External Queue
10.529337882995605
990577J1339
External Queue
12.716029167175293
990582J1340
External Queue
12.716029167175293
991247J1684 G
External Queue
11.04224681854248
NYPJM->LTFIMP_NY
CLTF
0.705
WECLTFEXP_WEC->PJM
CLTF
2.999
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.268
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.095
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.943
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.13
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.213
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.158
MECLTFEXP_MEC->PJM
CLTF
9.319
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.326
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.92
LAGNLTFEXP_LAGN->PJM
CLTF
3.075
TVALTFEXP_TVA->PJM
CLTF
0.789

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.12 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1069.26
MW Contribution:6.55
Bus #Bus NameTypeMW Contribution
274814UNIV PK N;0U
50/50
7.579
274807UNIV PK N;3U
50/50
7.563
274805UNIV PK N;1U
50/50
7.53
274811UNIV PK N;7U
50/50
7.513
972037AH1-567 GEN1
50/50
0.207
972227AH1-698 GEN1
50/50
2.527
274827FISK ;RP
50/50
7.397
960591AF2-350 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
27.488
274675JOLIET 29;7U
Adder
26.506
274731ELWOOD EC;2P
Adder
14.579
274733ELWOOD EC;3P
Adder
14.579
274735ELWOOD EC;4P
Adder
14.579
274728ELWOOD EC;5P
Adder
14.572
274687WILL CNTY;4U
Adder
24.727
274687WILL CNTY;4U
Adder
24.727
274775LINCOLN ;6U
Adder
7.383
274776LINCOLN ;7U
Adder
7.383
274777LINCOLN ;8U
Adder
7.383
970833AG2-524 GEN
Solar/Wind Harmer
6.681
970833AG2-524 GEN
Solar/Wind Harmer
4.454
274746AC1-111 G10
Adder
4.78
274744AC1-111 GEN8
Adder
4.78
971177AH1-047 GEN
Solar/Wind Harmer
3.499
276868AE1-113 GEN
Solar/Wind Harmer
1.137
276882AE2-255 GEN
Solar/Wind Harmer
0.663
971411AH1-196 GEN
Solar/Wind Harmer
8.449
971675AH1-338 GEN
Solar/Wind Harmer
2.185
971171AH1-044 GEN
Solar/Wind Harmer
11.081
274823ROCKFORD ;21
Adder
15.424
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.637
926823AC1-168 GEN
Solar/Wind Harmer
0.898
961011AF2-392 GEN
Solar/Wind Harmer
3.074
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.166
970169AG2-114 GEN
Solar/Wind Harmer
5
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
2.752
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.644
941731AE2-173 GEN
Solar/Wind Harmer
3.686
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.125
276848AB2-070 GEN3
Solar/Wind Harmer
0.124
960681AF2-359 GEN
Solar/Wind Helper
0.941
270536AF1-215 GEN2
Solar/Wind Helper
0.905
274813UNIV PK N;9U
50/50
0.412
274809UNIV PK N;5U
50/50
0.41
274812UNIV PK N;8U
50/50
7.513
966431AG1-512 GEN
50/50
2.631
274808UNIV PK N;4U
50/50
7.481
274803UNIV PARK;6U
50/50
6.592
274798UNIV PARK;1U
50/50
0.247
274888KELLY CRK;1U
Solar/Wind Harmer
0.371
274887GEN-1.85
Solar/Wind Harmer
0.167
276843GEN-1.7
Solar/Wind Harmer
0.205
958011AF2-095 GEN
Solar/Wind Harmer
9.107
972259AH1-714 GEN
Adder
17.034
958481AF2-142 GEN
Solar/Wind Harmer
9.285
274674JOLIET 9 ;6U
Adder
13.646
274770LINCOLN ;1U
Adder
7.383
274771LINCOLN ;2U
Adder
7.383
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
8.912
971573AH1-285 GEN
Solar/Wind Harmer
1.099
274683WAUKEGAN ;8U
Adder
17.721
274683WAUKEGAN ;8U
Adder
14.938
274695ROCKY RD ;2P
Adder
9.352
274693ROCKY RD ;1P
Adder
9.26
274697ROCKY RD ;3P
Adder
2.54
274696ROCKY RD ;4P
Adder
9.572
962691AG1-118 GEN
Solar/Wind Harmer
17.273
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.779
970921AG2-575 GEN
Solar/Wind Harmer
5.731
970921AG2-575 GEN
Solar/Wind Harmer
1.91
942991AE2-321 GEN
Solar/Wind Harmer
6.343
274879MINONK ;1U
Solar/Wind Harmer
0.239
971333AH1-146 GEN
Solar/Wind Harmer
11.231
971335AH1-147 GEN
Solar/Wind Harmer
11.231
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.081
971343AH1-151 GEN
Solar/Wind Harmer
11.081
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
3.04
274764LEE CO EC;5U
Adder
7.12
274765LEE CO EC;6U
Adder
7.12
274762LEE CO EC;3U
Adder
7.103
274763LEE CO EC;4U
Adder
7.036
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.113
276741O09 GEN1
Solar/Wind Harmer
0.184
276708O09 GEN2
Solar/Wind Harmer
0.184
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.197
276646AC1-214 GEN2
Solar/Wind Harmer
0.197
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.403
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
274806UNIV PK N;2U
50/50
0.42
274815UNIV PK N;XU
50/50
0.413
274816UNIV PK N;YU
50/50
0.412
274810UNIV PK N;6U
50/50
0.411
274802UNIV PARK;5U
50/50
6.592
274799UNIV PARK;2U
50/50
0.254
274800UNIV PARK;3U
50/50
5.664
972038AH1-567 GEN2
50/50
0.355
972228AH1-698 GEN2
50/50
3.594
274654BRAIDWOOD;1U
50/50
6.967
274826FISK ;BP
50/50
10.438
276806AD2-047 C O1
Solar/Wind Harmer
3.584
970941AG2-585 GEN
Solar/Wind Harmer
7.905
274676JOLIET 29;8U
Adder
26.501
276893AG1-478 C
Solar/Wind Harmer
0.245
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
14.579
274730ELWOOD EC;6P
Adder
14.572
274734ELWOOD EC;8P
Adder
14.572
274801UNIV PARK;4U
50/50
5.664
274655BRAIDWOOD;2U
50/50
6.565
276776AD2-060 GEN
Solar/Wind Harmer
0.66
274676JOLIET 29;8U
Adder
27.482
276691AA1-018 GEN1
Solar/Wind Harmer
0.75
274732ELWOOD EC;7P
Adder
14.572
274674JOLIET 9 ;6U
Adder
13.646
274773LINCOLN ;4U
Adder
7.383
274774LINCOLN ;5U
Adder
7.383
941551AE2-152 GEN
Solar/Wind Harmer
0
276164X3-005 C
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
4.78
274723RIVER EC ;12
Adder
15.295
274682WAUKEGAN ;7U
Adder
15.151
274828WAUKEGAN ;BP
Adder
9.289
962781AG1-127 GEN
Solar/Wind Harmer
5.454
274872LEEDK;1U
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.006
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
2.917
957471AF2-041 GEN
Solar/Wind Harmer
16.622
959081AF2-199 GEN
Solar/Wind Harmer
5.541
971067AG2-660 GEN
Solar/Wind Harmer
1.847
274822ROCKFORD ;11
Adder
15.537
972235AH1-702 GEN1
Adder
1.985
970819AG2-516 GEN
Solar/Wind Harmer
6.555
939401AE1-172 GEN
Solar/Wind Harmer
4.071
971475AH1-234 GEN
Solar/Wind Harmer
2.64
970569AG2-363 GEN
Solar/Wind Harmer
16.08
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
7.103
274766LEE CO EC;7U
Adder
7.019
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.167
274751CRETE EC ;1U
Adder
5.872
274754CRETE EC ;4U
Adder
5.872
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.192
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.138
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276615X2-022 GEN
Solar/Wind Harmer
0.034
270055AF2-134 C O1
Solar/Wind Helper
0.603
274736ELWOOD EC;9P
Adder
14.572
970707AG2-453 GEN
Solar/Wind Harmer
20.008
274772LINCOLN ;3U
Adder
7.383
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
9.979
943591AF1-030 GEN
Solar/Wind Harmer
6.636
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.151
274724RIVER EC ;11
Adder
14.719
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.598
274855GSG-6 ;RU
Solar/Wind Harmer
0.205
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276889AE2-281 GEN
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
11.081
972236AH1-702 GEN2
Adder
1.726
970571AG2-364 GEN
Solar/Wind Harmer
10.72
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
7.103
274767LEE CO EC;8U
Adder
7.019
276157O29GEN1
Solar/Wind Harmer
0.833
274878BISHOP HL;2U
Solar/Wind Harmer
0.167
274752CRETE EC ;2U
Adder
5.872
274753CRETE EC ;3U
Adder
5.872
965931AG1-462 GEN
Solar/Wind Harmer
12.391
942111AE2-223 GEN
Solar/Wind Harmer
1.437
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
12.626
959611AF2-252 GEN
Solar/Wind Harmer
1.403
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.585
276668AB2-070 GEN1
Solar/Wind Harmer
0.125
276621W2-048 GEN
Solar/Wind Harmer
0.165
276838X2-022 GEN2
Solar/Wind Harmer
0.184
270535AF1-215 GEN1
Solar/Wind Helper
0.905
990562J1336 G
External Queue
9.401391983032227
990512J1326
External Queue
4.092521667480469
990117J1214
External Queue
14.07827377319336
990727J1377 G
External Queue
4.75508451461792
990552J1334 G
External Queue
9.401391983032227
991303J1755 G
External Queue
3.5311484336853027
990762J1386
External Queue
10.568368911743164
990547J1333 G
External Queue
9.401391983032227
990557J1335 G
External Queue
9.401391983032227
990577J1339
External Queue
12.787979125976562
990582J1340
External Queue
12.787979125976562
991777J1629 G
External Queue
9.288150787353516
991247J1684 G
External Queue
11.122491836547852
990407J1304
External Queue
3.1668004989624023
NYPJM->LTFIMP_NY
CLTF
0.711
WECLTFEXP_WEC->PJM
CLTF
3.018
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.272
AG2-052LTFEXP_AG2-052->PJM
LTF
0.065
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.068
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.132
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.703
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.162
MECLTFEXP_MEC->PJM
CLTF
9.376
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.331
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.933
LAGNLTFEXP_LAGN->PJM
CLTF
3.091
TVALTFEXP_TVA->PJM
CLTF
0.791

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.11 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1069.22
MW Contribution:6.55
Bus #Bus NameTypeMW Contribution
274806UNIV PK N;2U
50/50
0.42
274815UNIV PK N;XU
50/50
0.413
274816UNIV PK N;YU
50/50
0.412
274810UNIV PK N;6U
50/50
0.411
274802UNIV PARK;5U
50/50
6.592
274799UNIV PARK;2U
50/50
0.254
274800UNIV PARK;3U
50/50
5.664
972038AH1-567 GEN2
50/50
0.355
972228AH1-698 GEN2
50/50
3.594
274654BRAIDWOOD;1U
50/50
6.967
274826FISK ;BP
50/50
10.438
276806AD2-047 C O1
Solar/Wind Harmer
3.584
970941AG2-585 GEN
Solar/Wind Harmer
7.905
274676JOLIET 29;8U
Adder
26.501
276893AG1-478 C
Solar/Wind Harmer
0.245
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274729ELWOOD EC;1P
Adder
14.579
274730ELWOOD EC;6P
Adder
14.572
274734ELWOOD EC;8P
Adder
14.572
274736ELWOOD EC;9P
Adder
14.572
970707AG2-453 GEN
Solar/Wind Harmer
20.008
274772LINCOLN ;3U
Adder
7.383
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
9.979
943591AF1-030 GEN
Solar/Wind Harmer
6.636
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
15.151
274724RIVER EC ;11
Adder
14.719
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.598
274855GSG-6 ;RU
Solar/Wind Harmer
0.205
274850MENDOTA H;RU
Solar/Wind Harmer
0.066
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.1
276889AE2-281 GEN
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
11.081
972236AH1-702 GEN2
Adder
1.726
970571AG2-364 GEN
Solar/Wind Harmer
10.72
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
7.103
274767LEE CO EC;8U
Adder
7.019
276157O29GEN1
Solar/Wind Harmer
0.833
274878BISHOP HL;2U
Solar/Wind Harmer
0.167
274752CRETE EC ;2U
Adder
5.872
274753CRETE EC ;3U
Adder
5.872
965931AG1-462 GEN
Solar/Wind Harmer
12.391
942111AE2-223 GEN
Solar/Wind Harmer
1.437
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
12.626
959611AF2-252 GEN
Solar/Wind Harmer
1.403
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.585
276668AB2-070 GEN1
Solar/Wind Harmer
0.125
276621W2-048 GEN
Solar/Wind Harmer
0.165
276838X2-022 GEN2
Solar/Wind Harmer
0.184
270535AF1-215 GEN1
Solar/Wind Helper
0.905
274813UNIV PK N;9U
50/50
0.412
274809UNIV PK N;5U
50/50
0.41
274812UNIV PK N;8U
50/50
7.513
966431AG1-512 GEN
50/50
2.631
274801UNIV PARK;4U
50/50
5.664
274655BRAIDWOOD;2U
50/50
6.565
276776AD2-060 GEN
Solar/Wind Harmer
0.66
274676JOLIET 29;8U
Adder
27.482
276691AA1-018 GEN1
Solar/Wind Harmer
0.75
274732ELWOOD EC;7P
Adder
14.572
274674JOLIET 9 ;6U
Adder
13.646
274773LINCOLN ;4U
Adder
7.383
274774LINCOLN ;5U
Adder
7.383
941551AE2-152 GEN
Solar/Wind Harmer
0
276164X3-005 C
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
4.78
274723RIVER EC ;12
Adder
15.295
274682WAUKEGAN ;7U
Adder
15.151
274828WAUKEGAN ;BP
Adder
9.289
962781AG1-127 GEN
Solar/Wind Harmer
5.454
274872LEEDK;1U
Solar/Wind Harmer
0.004
276901AD2-066 C O1
Solar/Wind Harmer
0.006
276861AD2-134 GEN
Solar/Wind Harmer
0.1
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
2.917
957471AF2-041 GEN
Solar/Wind Harmer
16.622
959081AF2-199 GEN
Solar/Wind Harmer
5.541
971067AG2-660 GEN
Solar/Wind Harmer
1.847
274822ROCKFORD ;11
Adder
15.537
972235AH1-702 GEN1
Adder
1.985
970819AG2-516 GEN
Solar/Wind Harmer
6.555
939401AE1-172 GEN
Solar/Wind Harmer
4.071
971475AH1-234 GEN
Solar/Wind Harmer
2.64
970569AG2-363 GEN
Solar/Wind Harmer
16.08
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
7.103
274766LEE CO EC;7U
Adder
7.019
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.167
274751CRETE EC ;1U
Adder
5.872
274754CRETE EC ;4U
Adder
5.872
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.192
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.138
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276615X2-022 GEN
Solar/Wind Harmer
0.034
270055AF2-134 C O1
Solar/Wind Helper
0.603
274814UNIV PK N;0U
50/50
7.579
274807UNIV PK N;3U
50/50
7.563
274805UNIV PK N;1U
50/50
7.53
274811UNIV PK N;7U
50/50
7.513
972037AH1-567 GEN1
50/50
0.207
972227AH1-698 GEN1
50/50
2.527
274827FISK ;RP
50/50
7.397
960591AF2-350 GEN
Solar/Wind Harmer
6.324
274675JOLIET 29;7U
Adder
27.488
274675JOLIET 29;7U
Adder
26.506
274731ELWOOD EC;2P
Adder
14.579
274733ELWOOD EC;3P
Adder
14.579
274735ELWOOD EC;4P
Adder
14.579
274728ELWOOD EC;5P
Adder
14.572
274687WILL CNTY;4U
Adder
24.727
274687WILL CNTY;4U
Adder
24.727
274775LINCOLN ;6U
Adder
7.383
274776LINCOLN ;7U
Adder
7.383
274777LINCOLN ;8U
Adder
7.383
970833AG2-524 GEN
Solar/Wind Harmer
6.681
970833AG2-524 GEN
Solar/Wind Harmer
4.454
274746AC1-111 G10
Adder
4.78
274744AC1-111 GEN8
Adder
4.78
971177AH1-047 GEN
Solar/Wind Harmer
3.499
276868AE1-113 GEN
Solar/Wind Harmer
1.137
276882AE2-255 GEN
Solar/Wind Harmer
0.663
971411AH1-196 GEN
Solar/Wind Harmer
8.449
971675AH1-338 GEN
Solar/Wind Harmer
2.185
971171AH1-044 GEN
Solar/Wind Harmer
11.081
274823ROCKFORD ;21
Adder
15.424
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
8.637
926823AC1-168 GEN
Solar/Wind Harmer
0.898
961011AF2-392 GEN
Solar/Wind Harmer
3.074
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.166
970169AG2-114 GEN
Solar/Wind Harmer
5
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
2.752
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.644
941731AE2-173 GEN
Solar/Wind Harmer
3.686
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.125
276848AB2-070 GEN3
Solar/Wind Harmer
0.124
960681AF2-359 GEN
Solar/Wind Helper
0.941
270536AF1-215 GEN2
Solar/Wind Helper
0.905
274808UNIV PK N;4U
50/50
7.481
274803UNIV PARK;6U
50/50
6.592
274798UNIV PARK;1U
50/50
0.247
274888KELLY CRK;1U
Solar/Wind Harmer
0.371
274887GEN-1.85
Solar/Wind Harmer
0.167
276843GEN-1.7
Solar/Wind Harmer
0.205
958011AF2-095 GEN
Solar/Wind Harmer
9.107
972259AH1-714 GEN
Adder
17.034
958481AF2-142 GEN
Solar/Wind Harmer
9.285
274674JOLIET 9 ;6U
Adder
13.646
274770LINCOLN ;1U
Adder
7.383
274771LINCOLN ;2U
Adder
7.383
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
958491AF2-143 GEN
Solar/Wind Harmer
8.912
971573AH1-285 GEN
Solar/Wind Harmer
1.099
274683WAUKEGAN ;8U
Adder
17.721
274683WAUKEGAN ;8U
Adder
14.938
274695ROCKY RD ;2P
Adder
9.352
274693ROCKY RD ;1P
Adder
9.26
274697ROCKY RD ;3P
Adder
2.54
274696ROCKY RD ;4P
Adder
9.572
962691AG1-118 GEN
Solar/Wind Harmer
17.273
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.779
970921AG2-575 GEN
Solar/Wind Harmer
5.731
970921AG2-575 GEN
Solar/Wind Harmer
1.91
942991AE2-321 GEN
Solar/Wind Harmer
6.343
274879MINONK ;1U
Solar/Wind Harmer
0.239
971333AH1-146 GEN
Solar/Wind Harmer
11.231
971335AH1-147 GEN
Solar/Wind Harmer
11.231
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
11.081
971343AH1-151 GEN
Solar/Wind Harmer
11.081
274856ECOGROVE ;U1
Solar/Wind Harmer
0.128
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
3.04
274764LEE CO EC;5U
Adder
7.12
274765LEE CO EC;6U
Adder
7.12
274762LEE CO EC;3U
Adder
7.103
274763LEE CO EC;4U
Adder
7.036
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.113
276741O09 GEN1
Solar/Wind Harmer
0.184
276708O09 GEN2
Solar/Wind Harmer
0.184
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.197
276646AC1-214 GEN2
Solar/Wind Harmer
0.197
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.403
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
990562J1336 G
External Queue
9.401391983032227
990512J1326
External Queue
4.092521667480469
990117J1214
External Queue
14.07827377319336
990727J1377 G
External Queue
4.75508451461792
990552J1334 G
External Queue
9.401391983032227
991303J1755 G
External Queue
3.5311484336853027
990762J1386
External Queue
10.568368911743164
990547J1333 G
External Queue
9.401391983032227
990557J1335 G
External Queue
9.401391983032227
990577J1339
External Queue
12.787979125976562
990582J1340
External Queue
12.787979125976562
991777J1629 G
External Queue
9.288150787353516
991247J1684 G
External Queue
11.122491836547852
990407J1304
External Queue
3.1668004989624023
NYPJM->LTFIMP_NY
CLTF
0.711
WECLTFEXP_WEC->PJM
CLTF
3.018
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.068
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.272
AG2-052LTFEXP_AG2-052->PJM
LTF
0.065
AH1-155LTFEXP_AH1-155->PJM
LTF
0.097
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.132
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.703
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.162
MECLTFEXP_MEC->PJM
CLTF
9.376
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.331
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.933
LAGNLTFEXP_LAGN->PJM
CLTF
3.091
TVALTFEXP_TVA->PJM
CLTF
0.791

Details for 17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2973_05DUMONT 345_F1_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17P9700-EAST-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.04 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:990.84
MW Contribution:6.76
Bus #Bus NameTypeMW Contribution
274806UNIV PK N;2U
50/50
0.376
274815UNIV PK N;XU
50/50
0.37
274816UNIV PK N;YU
50/50
0.369
274810UNIV PK N;6U
50/50
0.368
274802UNIV PARK;5U
50/50
5.509
274800UNIV PARK;3U
Adder
4.29
972038AH1-567 GEN2
Adder
0.269
274724RIVER EC ;11
Adder
13.005
274826FISK ;BP
Adder
7.921
276772AC2-154 GEN
Solar/Wind Harmer
1.986
276806AD2-047 C O1
Solar/Wind Harmer
7.617
970941AG2-585 GEN
Solar/Wind Harmer
8.899
274814UNIV PK N;0U
50/50
6.786
274807UNIV PK N;3U
50/50
6.772
274805UNIV PK N;1U
50/50
6.742
274811UNIV PK N;7U
50/50
6.728
972037AH1-567 GEN1
50/50
0.173
274827FISK ;RP
Adder
5.614
960591AF2-350 GEN
Solar/Wind Harmer
7.119
972228AH1-698 GEN2
Adder
2.573
276694AA1-018 GEN2
Solar/Wind Harmer
4.371
274676JOLIET 29;8U
Adder
20.153
276893AG1-478 C
Solar/Wind Harmer
0.284
274729ELWOOD EC;1P
Adder
11.051
274730ELWOOD EC;6P
Adder
11.047
274734ELWOOD EC;8P
Adder
11.047
274736ELWOOD EC;9P
Adder
11.047
276805AD2-038 GEN
Solar/Wind Harmer
3.374
276897AD1-100 C
Solar/Wind Harmer
18.376
939351AE1-166 GEN
Solar/Wind Harmer
3.755
274682WAUKEGAN ;7U
Adder
11.061
276889AE2-281 GEN
Solar/Wind Harmer
1.169
972231SS25-0005
Solar/Wind Harmer
5.716
972181SS23-001
Solar/Wind Harmer
3.573
274752CRETE EC ;2U
Adder
2.944
274753CRETE EC ;3U
Adder
2.944
943121AE2-341 GEN
Solar/Wind Harmer
8.883
943591AF1-030 GEN
Solar/Wind Harmer
5.922
970707AG2-453 GEN
Solar/Wind Harmer
16.422
274872LEEDK;1U
Solar/Wind Harmer
0.148
970571AG2-364 GEN
Solar/Wind Harmer
11.52
276799AD1-013 GEN
Solar/Wind Harmer
1.264
946671AF1-331 GEN
Solar/Wind Harmer
0.239
274855GSG-6 ;RU
Solar/Wind Harmer
2.109
274850MENDOTA H;RU
Solar/Wind Harmer
1.466
276602WESTBROOK C
Solar/Wind Harmer
1.214
276863AD2-134 GEN
Solar/Wind Harmer
1.02
959091AF2-200 GEN
Solar/Wind Harmer
11.367
972236AH1-702 GEN2
Adder
1.242
274772LINCOLN ;3U
Adder
3.419
274858EASY ROAD;U2
Solar/Wind Harmer
2.633
274760LEE CO EC;1U
Adder
5.112
274767LEE CO EC;8U
Adder
5.052
276157O29GEN1
Solar/Wind Harmer
2.033
274878BISHOP HL;2U
Solar/Wind Harmer
1.759
965931AG1-462 GEN
Solar/Wind Harmer
12.847
942111AE2-223 GEN
Solar/Wind Harmer
3.711
270535AF1-215 GEN1
Solar/Wind Helper
0.869
274808UNIV PK N;4U
50/50
6.698
274803UNIV PARK;6U
50/50
5.509
274888KELLY CRK;1U
Solar/Wind Harmer
4.203
274887GEN-1.85
Solar/Wind Harmer
3.795
276843GEN-1.7
Solar/Wind Harmer
0.408
958011AF2-095 GEN
Solar/Wind Harmer
10.252
958481AF2-142 GEN
Solar/Wind Harmer
10.389
274674JOLIET 9 ;6U
Adder
10.324
958491AF2-143 GEN
Solar/Wind Harmer
9.865
972259AH1-714 GEN
Adder
12.183
274861TOP CROP ;1U
Solar/Wind Harmer
3.829
274862TOP CROP ;2U
Solar/Wind Harmer
3.198
274847GR RIDGE ;BU
Solar/Wind Harmer
3.16
274683WAUKEGAN ;8U
Adder
12.935
274683WAUKEGAN ;8U
Adder
10.904
276872AE1-163_GEN1
Solar/Wind Harmer
4.092
274879MINONK ;1U
Solar/Wind Harmer
4.111
274696ROCKY RD ;4P
Adder
6.863
274695ROCKY RD ;2P
Adder
6.705
274693ROCKY RD ;1P
Adder
6.639
274697ROCKY RD ;3P
Adder
1.821
971573AH1-285 GEN
Solar/Wind Harmer
5.072
942991AE2-321 GEN
Solar/Wind Harmer
5.86
962691AG1-118 GEN
Solar/Wind Harmer
17.552
970921AG2-575 GEN
Solar/Wind Harmer
5.826
970921AG2-575 GEN
Solar/Wind Harmer
1.355
971333AH1-146 GEN
Solar/Wind Harmer
11.549
971335AH1-147 GEN
Solar/Wind Harmer
11.549
971341AH1-150 GEN
Solar/Wind Harmer
11.367
971343AH1-151 GEN
Solar/Wind Harmer
11.367
274856ECOGROVE ;U1
Solar/Wind Harmer
1.893
276611AD2-172 GEN
Solar/Wind Harmer
1.437
938861AE1-114 GEN
Solar/Wind Harmer
4.536
274770LINCOLN ;1U
Adder
3.419
274771LINCOLN ;2U
Adder
3.419
274764LEE CO EC;5U
Adder
5.124
274765LEE CO EC;6U
Adder
5.124
274762LEE CO EC;3U
Adder
5.112
274763LEE CO EC;4U
Adder
5.064
276603SUBLETTE C
Solar/Wind Harmer
0.573
972267AH1-718 GEN
Adder
2.242
276741O09 GEN1
Solar/Wind Harmer
1.909
276708O09 GEN2
Solar/Wind Harmer
1.909
274851PROVIDENC;RU
Solar/Wind Harmer
1.499
274849CRESCENT ;1U
Solar/Wind Harmer
0.973
276645AC1-214 GEN1
Solar/Wind Harmer
0.705
276646AC1-214 GEN2
Solar/Wind Harmer
0.705
276782AC1-033 GEN
Solar/Wind Harmer
2.079
972227AH1-698 GEN1
Adder
1.808
274675JOLIET 29;7U
Adder
20.904
274675JOLIET 29;7U
Adder
20.158
274687WILL CNTY;4U
Adder
18.989
274687WILL CNTY;4U
Adder
18.989
274731ELWOOD EC;2P
Adder
11.051
274733ELWOOD EC;3P
Adder
11.051
274735ELWOOD EC;4P
Adder
11.051
274728ELWOOD EC;5P
Adder
11.047
970833AG2-524 GEN
Solar/Wind Harmer
5.487
970833AG2-524 GEN
Solar/Wind Harmer
2.552
276868AE1-113 GEN
Solar/Wind Harmer
6.166
276882AE2-255 GEN
Solar/Wind Harmer
2.055
274746AC1-111 G10
Adder
3.389
274744AC1-111 GEN8
Adder
3.389
971177AH1-047 GEN
Solar/Wind Harmer
3.43
971411AH1-196 GEN
Solar/Wind Harmer
8.72
971675AH1-338 GEN
Solar/Wind Harmer
10.283
274823ROCKFORD ;21
Adder
11.099
971171AH1-044 GEN
Solar/Wind Harmer
11.367
276612AE2-035 GEN
Solar/Wind Harmer
1.437
971681AH1-341 GEN
Solar/Wind Harmer
8.295
926823AC1-168 GEN
Solar/Wind Harmer
2.377
274775LINCOLN ;6U
Adder
3.419
274776LINCOLN ;7U
Adder
3.419
274777LINCOLN ;8U
Adder
3.419
961011AF2-392 GEN
Solar/Wind Harmer
5.881
274863CRW1-WTG
Solar/Wind Harmer
2.969
274864CRW2-WTG
Solar/Wind Harmer
2.969
957751AF2-069 GEN
Solar/Wind Harmer
0.242
274848CAMPGROVE;RU
Solar/Wind Harmer
3.326
970169AG2-114 GEN
Solar/Wind Harmer
5.103
946321AF1-296 GEN
Solar/Wind Harmer
5.313
276655WTG1_EQ
Solar/Wind Harmer
3.953
276656WTG2_EQ
Solar/Wind Harmer
0.523
960681AF2-359 GEN
Solar/Wind Helper
0.952
270536AF1-215 GEN2
Solar/Wind Helper
0.869
959341AF2-225 GEN
Solar/Wind Harmer
0.13
274813UNIV PK N;9U
50/50
0.369
274809UNIV PK N;5U
50/50
0.367
274812UNIV PK N;8U
50/50
6.728
966431AG1-512 GEN
50/50
2.355
274723RIVER EC ;12
Adder
13.527
274801UNIV PARK;4U
Adder
4.29
276164X3-005 C
Solar/Wind Harmer
0.51
276776AD2-060 GEN
Solar/Wind Harmer
0.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.322
274676JOLIET 29;8U
Adder
20.9
274732ELWOOD EC;7P
Adder
11.047
274674JOLIET 9 ;6U
Adder
10.324
941551AE2-152 GEN
Solar/Wind Harmer
2.872
274871GR RIDGE ;2U
Solar/Wind Harmer
4.804
274682WAUKEGAN ;7U
Adder
11.061
274828WAUKEGAN ;BP
Adder
6.78
276876AE1-163_GEN2
Solar/Wind Harmer
4.092
276901AD2-066 C O1
Solar/Wind Harmer
2.138
274745AC1-111 GEN9
Adder
3.389
274751CRETE EC ;1U
Adder
2.944
274754CRETE EC ;4U
Adder
2.944
960751AF2-366 GEN
Solar/Wind Harmer
1.671
962781AG1-127 GEN
Solar/Wind Harmer
5.54
274872LEEDK;1U
Solar/Wind Harmer
4.762
971997AH1-543 GEN
Solar/Wind Harmer
9.071
970569AG2-363 GEN
Solar/Wind Harmer
17.28
276861AD2-134 GEN
Solar/Wind Harmer
1.02
274822ROCKFORD ;11
Adder
11.18
957471AF2-041 GEN
Solar/Wind Harmer
17.051
959081AF2-199 GEN
Solar/Wind Harmer
5.684
971067AG2-660 GEN
Solar/Wind Harmer
1.322
972235AH1-702 GEN1
Adder
1.428
970819AG2-516 GEN
Solar/Wind Harmer
6.765
971475AH1-234 GEN
Solar/Wind Harmer
12.59
939401AE1-172 GEN
Solar/Wind Harmer
7.726
972207SS24-0001
Solar/Wind Harmer
12.157
274773LINCOLN ;4U
Adder
3.419
274774LINCOLN ;5U
Adder
3.419
274857EASY ROAD;U1
Solar/Wind Harmer
2.633
274761LEE CO EC;2U
Adder
5.112
274766LEE CO EC;7U
Adder
5.052
276158O29GEN2
Solar/Wind Harmer
2.673
274877BISHOP HL;1U
Solar/Wind Harmer
1.759
276726Z2-087_GEN
Solar/Wind Harmer
3.581
939741AE1-205 GEN
Solar/Wind Harmer
9.054
270055AF2-134 C O1
Solar/Wind Helper
0.579
990562J1336 G
External Queue
13.238182067871094
990552J1334 G
External Queue
13.238182067871094
990762J1386
External Queue
11.196856498718262
990547J1333 G
External Queue
13.238182067871094
990557J1335 G
External Queue
13.238182067871094
990577J1339
External Queue
15.133350372314453
990582J1340
External Queue
15.133350372314453
991247J1684 G
External Queue
14.221319198608398
NYPJM->LTFIMP_NY
CLTF
0.507
WECLTFEXP_WEC->PJM
CLTF
2.196
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.179
CBM West 2LTFEXP_CBM-W2->PJM
CBM
16.248
AG2-052LTFEXP_AG2-052->PJM
LTF
0.114
AH1-155LTFEXP_AH1-155->PJM
LTF
0.172
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
34.836
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.665
MECLTFEXP_MEC->PJM
CLTF
6.812
SIGELTFEXP_SIGE->PJM
CLTF
0.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.602
LAGNLTFEXP_LAGN->PJM
CLTF
2.283
TVALTFEXP_TVA->PJM
CLTF
0.598

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.76 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2738.58
MW Contribution:14.15
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
31.815
957371AF2-031 GEN
50/50
1.575
274826FISK ;BP
50/50
16.789
274800UNIV PARK;3U
Adder
8.394
972038AH1-567 GEN2
Adder
0.525
276772AC2-154 GEN
Solar/Wind Harmer
3.929
276806AD2-047 C O1
Solar/Wind Harmer
15.071
970941AG2-585 GEN
Solar/Wind Harmer
17.61
274802UNIV PARK;5U
Adder
8.077
274772LINCOLN ;3U
Adder
8.543
276893AG1-478 C
Solar/Wind Harmer
0.562
972228AH1-698 GEN2
Adder
4.963
274676JOLIET 29;8U
Adder
39.569
274730ELWOOD EC;6P
Adder
21.769
274734ELWOOD EC;8P
Adder
21.769
274736ELWOOD EC;9P
Adder
21.769
274729ELWOOD EC;1P
Adder
21.766
276897AD1-100 C
Solar/Wind Harmer
38.391
939351AE1-166 GEN
Solar/Wind Harmer
7.844
970707AG2-453 GEN
Solar/Wind Harmer
36.666
276694AA1-018 GEN2
Solar/Wind Harmer
8.087
943121AE2-341 GEN
Solar/Wind Harmer
19.202
943591AF1-030 GEN
Solar/Wind Harmer
12.801
274682WAUKEGAN ;7U
Adder
22.761
972231SS25-0005
Solar/Wind Harmer
11.874
972181SS23-001
Solar/Wind Harmer
7.421
274752CRETE EC ;2U
Adder
6.116
274753CRETE EC ;3U
Adder
6.116
276805AD2-038 GEN
Solar/Wind Harmer
6.386
274872LEEDK;1U
Solar/Wind Harmer
0.314
276799AD1-013 GEN
Solar/Wind Harmer
2.673
946671AF1-331 GEN
Solar/Wind Harmer
0.506
274855GSG-6 ;RU
Solar/Wind Harmer
4.459
274850MENDOTA H;RU
Solar/Wind Harmer
3.101
276602WESTBROOK C
Solar/Wind Harmer
2.567
276863AD2-134 GEN
Solar/Wind Harmer
2.157
959091AF2-200 GEN
Solar/Wind Harmer
23.909
274723RIVER EC ;12
50/50
31.785
972179AH1-673 GEN
50/50
16.453
276164X3-005 C
Solar/Wind Harmer
1.103
274801UNIV PARK;4U
Adder
8.394
276776AD2-060 GEN
Solar/Wind Harmer
0.596
972207SS24-0001
Solar/Wind Harmer
30.372
274773LINCOLN ;4U
Adder
8.543
274774LINCOLN ;5U
Adder
8.543
274674JOLIET 9 ;6U
Adder
20.703
274676JOLIET 29;8U
Adder
41.034
274732ELWOOD EC;7P
Adder
21.769
941551AE2-152 GEN
Solar/Wind Harmer
6
274812UNIV PK N;8U
Adder
6.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.918
274745AC1-111 GEN9
Adder
7.173
276691AA1-018 GEN1
Solar/Wind Harmer
0.597
274682WAUKEGAN ;7U
Adder
22.761
274828WAUKEGAN ;BP
Adder
13.956
274751CRETE EC ;1U
Adder
6.116
274754CRETE EC ;4U
Adder
6.116
960751AF2-366 GEN
Solar/Wind Harmer
3.543
962781AG1-127 GEN
Solar/Wind Harmer
11.742
274872LEEDK;1U
Solar/Wind Harmer
10.097
276901AD2-066 C O1
Solar/Wind Harmer
4.301
276861AD2-134 GEN
Solar/Wind Harmer
2.157
971997AH1-543 GEN
Solar/Wind Harmer
18.889
939401AE1-172 GEN
Solar/Wind Harmer
16.677
957471AF2-041 GEN
Solar/Wind Harmer
35.864
959081AF2-199 GEN
Solar/Wind Harmer
11.955
971067AG2-660 GEN
Solar/Wind Harmer
2.78
276876AE1-163_GEN2
Solar/Wind Harmer
8.019
274822ROCKFORD ;11
Adder
23.394
972235AH1-702 GEN1
Adder
2.99
970819AG2-516 GEN
Solar/Wind Harmer
14.154
971475AH1-234 GEN
Solar/Wind Harmer
26.315
961501AF2-441 GEN
50/50
15.121
274827FISK ;RP
50/50
11.898
960591AF2-350 GEN
Solar/Wind Harmer
14.088
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
8.543
274776LINCOLN ;7U
Adder
8.543
274777LINCOLN ;8U
Adder
8.543
274687WILL CNTY;4U
Adder
37.907
274687WILL CNTY;4U
Adder
37.907
972227AH1-698 GEN1
Adder
3.494
274675JOLIET 29;7U
Adder
41.035
274675JOLIET 29;7U
Adder
39.569
274728ELWOOD EC;5P
Adder
21.769
274731ELWOOD EC;2P
Adder
21.766
274733ELWOOD EC;3P
Adder
21.766
274735ELWOOD EC;4P
Adder
21.766
274888KELLY CRK;1U
Solar/Wind Harmer
8.317
274887GEN-1.85
Solar/Wind Harmer
7.509
276843GEN-1.7
Solar/Wind Harmer
0.808
958011AF2-095 GEN
Solar/Wind Harmer
20.287
274803UNIV PARK;6U
Adder
8.077
274770LINCOLN ;1U
Adder
8.543
274771LINCOLN ;2U
Adder
8.543
274674JOLIET 9 ;6U
Adder
20.703
972259AH1-714 GEN
Adder
25.2
274808UNIV PK N;4U
Adder
6.518
274847GR RIDGE ;BU
Solar/Wind Harmer
6.524
958481AF2-142 GEN
Solar/Wind Harmer
19.223
274861TOP CROP ;1U
Solar/Wind Harmer
7.739
274862TOP CROP ;2U
Solar/Wind Harmer
6.462
971573AH1-285 GEN
Solar/Wind Harmer
10.912
274683WAUKEGAN ;8U
Adder
26.624
274683WAUKEGAN ;8U
Adder
22.443
274695ROCKY RD ;2P
Adder
14.045
274693ROCKY RD ;1P
Adder
13.907
274697ROCKY RD ;3P
Adder
3.815
274696ROCKY RD ;4P
Adder
14.376
958491AF2-143 GEN
Solar/Wind Harmer
18.672
962691AG1-118 GEN
Solar/Wind Harmer
37.207
970921AG2-575 GEN
Solar/Wind Harmer
12.347
970921AG2-575 GEN
Solar/Wind Harmer
2.871
942991AE2-321 GEN
Solar/Wind Harmer
12.244
274879MINONK ;1U
Solar/Wind Harmer
8.253
971333AH1-146 GEN
Solar/Wind Harmer
24.221
971335AH1-147 GEN
Solar/Wind Harmer
24.221
971341AH1-150 GEN
Solar/Wind Harmer
23.909
971343AH1-151 GEN
Solar/Wind Harmer
23.909
276872AE1-163_GEN1
Solar/Wind Harmer
8.019
274856ECOGROVE ;U1
Solar/Wind Harmer
3.964
276611AD2-172 GEN
Solar/Wind Harmer
3.007
938861AE1-114 GEN
Solar/Wind Harmer
9.505
274764LEE CO EC;5U
Adder
10.738
274765LEE CO EC;6U
Adder
10.738
274762LEE CO EC;3U
Adder
10.713
274763LEE CO EC;4U
Adder
10.612
276603SUBLETTE C
Solar/Wind Harmer
1.202
972267AH1-718 GEN
Adder
4.7
276741O09 GEN1
Solar/Wind Harmer
3.992
276708O09 GEN2
Solar/Wind Harmer
3.992
274851PROVIDENC;RU
Solar/Wind Harmer
3.106
274849CRESCENT ;1U
Solar/Wind Harmer
2.016
276645AC1-214 GEN1
Solar/Wind Harmer
1.461
276646AC1-214 GEN2
Solar/Wind Harmer
1.461
276782AC1-033 GEN
Solar/Wind Harmer
4.314
276889AE2-281 GEN
Solar/Wind Harmer
2.291
972236AH1-702 GEN2
Adder
2.6
970571AG2-364 GEN
Solar/Wind Harmer
23.178
274858EASY ROAD;U2
Solar/Wind Harmer
5.518
274760LEE CO EC;1U
Adder
10.713
274767LEE CO EC;8U
Adder
10.587
276157O29GEN1
Solar/Wind Harmer
4.251
274878BISHOP HL;2U
Solar/Wind Harmer
3.65
965931AG1-462 GEN
Solar/Wind Harmer
26.907
274814UNIV PK N;0U
Adder
6.604
274807UNIV PK N;3U
Adder
6.59
274805UNIV PK N;1U
Adder
6.561
274811UNIV PK N;7U
Adder
6.547
970833AG2-524 GEN
Solar/Wind Harmer
11.298
970833AG2-524 GEN
Solar/Wind Harmer
5.255
274746AC1-111 G10
Adder
7.173
274744AC1-111 GEN8
Adder
7.173
971177AH1-047 GEN
Solar/Wind Harmer
7.169
276868AE1-113 GEN
Solar/Wind Harmer
12.378
276882AE2-255 GEN
Solar/Wind Harmer
4.126
971411AH1-196 GEN
Solar/Wind Harmer
18.219
971675AH1-338 GEN
Solar/Wind Harmer
21.746
971171AH1-044 GEN
Solar/Wind Harmer
23.909
274823ROCKFORD ;21
Adder
23.224
276612AE2-035 GEN
Solar/Wind Harmer
3.007
971681AH1-341 GEN
Solar/Wind Harmer
17.392
274863CRW1-WTG
Solar/Wind Harmer
6.413
274864CRW2-WTG
Solar/Wind Harmer
6.413
926823AC1-168 GEN
Solar/Wind Harmer
4.911
961011AF2-392 GEN
Solar/Wind Harmer
12.329
970169AG2-114 GEN
Solar/Wind Harmer
10.984
957751AF2-069 GEN
Solar/Wind Harmer
0.501
274848CAMPGROVE;RU
Solar/Wind Harmer
6.902
946321AF1-296 GEN
Solar/Wind Harmer
11.128
276655WTG1_EQ
Solar/Wind Harmer
8.592
276656WTG2_EQ
Solar/Wind Harmer
1.138
941731AE2-173 GEN
Solar/Wind Harmer
4.097
970569AG2-363 GEN
Solar/Wind Harmer
34.768
274857EASY ROAD;U1
Solar/Wind Harmer
5.518
274761LEE CO EC;2U
Adder
10.713
274766LEE CO EC;7U
Adder
10.587
276158O29GEN2
Solar/Wind Harmer
5.589
274877BISHOP HL;1U
Solar/Wind Harmer
3.65
276726Z2-087_GEN
Solar/Wind Harmer
7.783
939741AE1-205 GEN
Solar/Wind Harmer
14.093
990562J1336 G
External Queue
34.17172622680664
990512J1326
External Queue
5.457309722900391
990552J1334 G
External Queue
34.17172622680664
991092J1477
External Queue
2.8719847202301025
990762J1386
External Queue
10.366711616516113
991332J1785
External Queue
12.019579887390137
990547J1333 G
External Queue
34.17172622680664
990557J1335 G
External Queue
34.17172622680664
990577J1339
External Queue
21.826017379760742
990647J1355
External Queue
42.77540969848633
990582J1340
External Queue
21.826017379760742
990662J1358
External Queue
15.149626731872559
991247J1684 G
External Queue
28.069046020507812
NYPJM->LTFIMP_NY
CLTF
1.15
WECLTFEXP_WEC->PJM
CLTF
4.545
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.199
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.551
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.854
MECLTFEXP_MEC->PJM
CLTF
14.34
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.385
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.032
LAGNLTFEXP_LAGN->PJM
CLTF
4.984
TVALTFEXP_TVA->PJM
CLTF
1.346

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:148.75 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2738.57
MW Contribution:14.15
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
31.816
957371AF2-031 GEN
50/50
1.575
274826FISK ;BP
50/50
16.789
274800UNIV PARK;3U
Adder
8.394
972038AH1-567 GEN2
Adder
0.525
276772AC2-154 GEN
Solar/Wind Harmer
3.929
276806AD2-047 C O1
Solar/Wind Harmer
15.071
970941AG2-585 GEN
Solar/Wind Harmer
17.61
274802UNIV PARK;5U
Adder
8.077
274772LINCOLN ;3U
Adder
8.544
276893AG1-478 C
Solar/Wind Harmer
0.562
972228AH1-698 GEN2
Adder
4.963
274676JOLIET 29;8U
Adder
39.568
274730ELWOOD EC;6P
Adder
21.769
274734ELWOOD EC;8P
Adder
21.769
274736ELWOOD EC;9P
Adder
21.769
274729ELWOOD EC;1P
Adder
21.766
276897AD1-100 C
Solar/Wind Harmer
38.391
939351AE1-166 GEN
Solar/Wind Harmer
7.844
970707AG2-453 GEN
Solar/Wind Harmer
36.665
276694AA1-018 GEN2
Solar/Wind Harmer
8.087
943121AE2-341 GEN
Solar/Wind Harmer
19.201
943591AF1-030 GEN
Solar/Wind Harmer
12.801
274682WAUKEGAN ;7U
Adder
22.761
972231SS25-0005
Solar/Wind Harmer
11.874
972181SS23-001
Solar/Wind Harmer
7.421
274752CRETE EC ;2U
Adder
6.116
274753CRETE EC ;3U
Adder
6.116
276805AD2-038 GEN
Solar/Wind Harmer
6.386
274872LEEDK;1U
Solar/Wind Harmer
0.314
276799AD1-013 GEN
Solar/Wind Harmer
2.673
946671AF1-331 GEN
Solar/Wind Harmer
0.506
274855GSG-6 ;RU
Solar/Wind Harmer
4.459
274850MENDOTA H;RU
Solar/Wind Harmer
3.101
276602WESTBROOK C
Solar/Wind Harmer
2.567
276863AD2-134 GEN
Solar/Wind Harmer
2.157
959091AF2-200 GEN
Solar/Wind Harmer
23.909
276889AE2-281 GEN
Solar/Wind Harmer
2.291
972236AH1-702 GEN2
Adder
2.6
970571AG2-364 GEN
Solar/Wind Harmer
23.178
274858EASY ROAD;U2
Solar/Wind Harmer
5.518
274760LEE CO EC;1U
Adder
10.713
274767LEE CO EC;8U
Adder
10.586
276157O29GEN1
Solar/Wind Harmer
4.251
274878BISHOP HL;2U
Solar/Wind Harmer
3.65
965931AG1-462 GEN
Solar/Wind Harmer
26.907
274723RIVER EC ;12
50/50
31.785
972179AH1-673 GEN
50/50
16.453
276164X3-005 C
Solar/Wind Harmer
1.103
274801UNIV PARK;4U
Adder
8.394
276776AD2-060 GEN
Solar/Wind Harmer
0.596
972207SS24-0001
Solar/Wind Harmer
30.377
274773LINCOLN ;4U
Adder
8.544
274774LINCOLN ;5U
Adder
8.544
274674JOLIET 9 ;6U
Adder
20.703
274676JOLIET 29;8U
Adder
41.034
274732ELWOOD EC;7P
Adder
21.769
941551AE2-152 GEN
Solar/Wind Harmer
6
274812UNIV PK N;8U
Adder
6.547
274871GR RIDGE ;2U
Solar/Wind Harmer
9.918
274745AC1-111 GEN9
Adder
7.173
276691AA1-018 GEN1
Solar/Wind Harmer
0.597
274682WAUKEGAN ;7U
Adder
22.761
274828WAUKEGAN ;BP
Adder
13.956
274751CRETE EC ;1U
Adder
6.116
274754CRETE EC ;4U
Adder
6.116
960751AF2-366 GEN
Solar/Wind Harmer
3.542
962781AG1-127 GEN
Solar/Wind Harmer
11.742
274872LEEDK;1U
Solar/Wind Harmer
10.096
276901AD2-066 C O1
Solar/Wind Harmer
4.301
276861AD2-134 GEN
Solar/Wind Harmer
2.157
971997AH1-543 GEN
Solar/Wind Harmer
18.888
939401AE1-172 GEN
Solar/Wind Harmer
16.677
957471AF2-041 GEN
Solar/Wind Harmer
35.864
959081AF2-199 GEN
Solar/Wind Harmer
11.955
971067AG2-660 GEN
Solar/Wind Harmer
2.78
276876AE1-163_GEN2
Solar/Wind Harmer
8.019
274822ROCKFORD ;11
Adder
23.393
972235AH1-702 GEN1
Adder
2.99
970819AG2-516 GEN
Solar/Wind Harmer
14.154
971475AH1-234 GEN
Solar/Wind Harmer
26.315
970569AG2-363 GEN
Solar/Wind Harmer
34.767
274857EASY ROAD;U1
Solar/Wind Harmer
5.518
274761LEE CO EC;2U
Adder
10.713
274766LEE CO EC;7U
Adder
10.586
276158O29GEN2
Solar/Wind Harmer
5.589
274877BISHOP HL;1U
Solar/Wind Harmer
3.65
276726Z2-087_GEN
Solar/Wind Harmer
7.783
939741AE1-205 GEN
Solar/Wind Harmer
14.093
274888KELLY CRK;1U
Solar/Wind Harmer
8.317
274887GEN-1.85
Solar/Wind Harmer
7.509
276843GEN-1.7
Solar/Wind Harmer
0.808
958011AF2-095 GEN
Solar/Wind Harmer
20.287
274803UNIV PARK;6U
Adder
8.077
274770LINCOLN ;1U
Adder
8.544
274771LINCOLN ;2U
Adder
8.544
274674JOLIET 9 ;6U
Adder
20.703
972259AH1-714 GEN
Adder
25.2
274808UNIV PK N;4U
Adder
6.518
274847GR RIDGE ;BU
Solar/Wind Harmer
6.524
958481AF2-142 GEN
Solar/Wind Harmer
19.223
274861TOP CROP ;1U
Solar/Wind Harmer
7.739
274862TOP CROP ;2U
Solar/Wind Harmer
6.462
971573AH1-285 GEN
Solar/Wind Harmer
10.912
274683WAUKEGAN ;8U
Adder
26.624
274683WAUKEGAN ;8U
Adder
22.443
274695ROCKY RD ;2P
Adder
14.045
274693ROCKY RD ;1P
Adder
13.907
274697ROCKY RD ;3P
Adder
3.815
274696ROCKY RD ;4P
Adder
14.376
958491AF2-143 GEN
Solar/Wind Harmer
18.672
962691AG1-118 GEN
Solar/Wind Harmer
37.207
970921AG2-575 GEN
Solar/Wind Harmer
12.347
970921AG2-575 GEN
Solar/Wind Harmer
2.871
942991AE2-321 GEN
Solar/Wind Harmer
12.244
274879MINONK ;1U
Solar/Wind Harmer
8.253
971333AH1-146 GEN
Solar/Wind Harmer
24.22
971335AH1-147 GEN
Solar/Wind Harmer
24.22
971341AH1-150 GEN
Solar/Wind Harmer
23.909
971343AH1-151 GEN
Solar/Wind Harmer
23.909
276872AE1-163_GEN1
Solar/Wind Harmer
8.019
274856ECOGROVE ;U1
Solar/Wind Harmer
3.964
276611AD2-172 GEN
Solar/Wind Harmer
3.007
938861AE1-114 GEN
Solar/Wind Harmer
9.504
274764LEE CO EC;5U
Adder
10.738
274765LEE CO EC;6U
Adder
10.738
274762LEE CO EC;3U
Adder
10.713
274763LEE CO EC;4U
Adder
10.612
276603SUBLETTE C
Solar/Wind Harmer
1.202
972267AH1-718 GEN
Adder
4.7
276741O09 GEN1
Solar/Wind Harmer
3.992
276708O09 GEN2
Solar/Wind Harmer
3.992
274851PROVIDENC;RU
Solar/Wind Harmer
3.106
274849CRESCENT ;1U
Solar/Wind Harmer
2.016
276645AC1-214 GEN1
Solar/Wind Harmer
1.461
276646AC1-214 GEN2
Solar/Wind Harmer
1.461
276782AC1-033 GEN
Solar/Wind Harmer
4.314
961501AF2-441 GEN
50/50
15.121
274827FISK ;RP
50/50
11.898
960591AF2-350 GEN
Solar/Wind Harmer
14.088
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
8.544
274776LINCOLN ;7U
Adder
8.544
274777LINCOLN ;8U
Adder
8.544
274687WILL CNTY;4U
Adder
37.907
274687WILL CNTY;4U
Adder
37.907
972227AH1-698 GEN1
Adder
3.493
274675JOLIET 29;7U
Adder
41.035
274675JOLIET 29;7U
Adder
39.569
274728ELWOOD EC;5P
Adder
21.769
274731ELWOOD EC;2P
Adder
21.766
274733ELWOOD EC;3P
Adder
21.766
274735ELWOOD EC;4P
Adder
21.766
274814UNIV PK N;0U
Adder
6.604
274807UNIV PK N;3U
Adder
6.59
274805UNIV PK N;1U
Adder
6.561
274811UNIV PK N;7U
Adder
6.547
970833AG2-524 GEN
Solar/Wind Harmer
11.298
970833AG2-524 GEN
Solar/Wind Harmer
5.255
274746AC1-111 G10
Adder
7.173
274744AC1-111 GEN8
Adder
7.173
971177AH1-047 GEN
Solar/Wind Harmer
7.169
276868AE1-113 GEN
Solar/Wind Harmer
12.378
276882AE2-255 GEN
Solar/Wind Harmer
4.126
971411AH1-196 GEN
Solar/Wind Harmer
18.219
971675AH1-338 GEN
Solar/Wind Harmer
21.745
971171AH1-044 GEN
Solar/Wind Harmer
23.909
274823ROCKFORD ;21
Adder
23.224
276612AE2-035 GEN
Solar/Wind Harmer
3.007
971681AH1-341 GEN
Solar/Wind Harmer
17.392
274863CRW1-WTG
Solar/Wind Harmer
6.412
274864CRW2-WTG
Solar/Wind Harmer
6.412
926823AC1-168 GEN
Solar/Wind Harmer
4.911
961011AF2-392 GEN
Solar/Wind Harmer
12.329
970169AG2-114 GEN
Solar/Wind Harmer
10.984
957751AF2-069 GEN
Solar/Wind Harmer
0.501
274848CAMPGROVE;RU
Solar/Wind Harmer
6.902
946321AF1-296 GEN
Solar/Wind Harmer
11.128
276655WTG1_EQ
Solar/Wind Harmer
8.591
276656WTG2_EQ
Solar/Wind Harmer
1.138
941731AE2-173 GEN
Solar/Wind Harmer
4.097
990562J1336 G
External Queue
34.1719856262207
990512J1326
External Queue
5.457244396209717
990552J1334 G
External Queue
34.1719856262207
991092J1477
External Queue
2.871951103210449
990762J1386
External Queue
10.366846084594727
991332J1785
External Queue
12.01968002319336
990547J1333 G
External Queue
34.1719856262207
990557J1335 G
External Queue
34.1719856262207
990577J1339
External Queue
21.826255798339844
990647J1355
External Queue
42.775543212890625
990582J1340
External Queue
21.826255798339844
990662J1358
External Queue
15.149800300598145
991247J1684 G
External Queue
28.06928825378418
NYPJM->LTFIMP_NY
CLTF
1.15
WECLTFEXP_WEC->PJM
CLTF
4.545
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.199
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.551
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.854
MECLTFEXP_MEC->PJM
CLTF
14.339
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.385
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.032
LAGNLTFEXP_LAGN->PJM
CLTF
4.984
TVALTFEXP_TVA->PJM
CLTF
1.346

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:147.24 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2710.62
MW Contribution:13.86
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
30.79
957371AF2-031 GEN
50/50
1.524
274826FISK ;BP
50/50
16.268
274800UNIV PARK;3U
Adder
8.139
972038AH1-567 GEN2
Adder
0.509
276772AC2-154 GEN
Solar/Wind Harmer
3.81
276806AD2-047 C O1
Solar/Wind Harmer
14.615
970941AG2-585 GEN
Solar/Wind Harmer
17.077
274802UNIV PARK;5U
Adder
7.816
274772LINCOLN ;3U
Adder
8.27
276893AG1-478 C
Solar/Wind Harmer
0.546
972228AH1-698 GEN2
Adder
4.813
274676JOLIET 29;8U
Adder
38.421
274730ELWOOD EC;6P
Adder
21.152
274734ELWOOD EC;8P
Adder
21.152
274736ELWOOD EC;9P
Adder
21.152
274729ELWOOD EC;1P
Adder
21.149
276897AD1-100 C
Solar/Wind Harmer
37.296
939351AE1-166 GEN
Solar/Wind Harmer
7.62
970707AG2-453 GEN
Solar/Wind Harmer
35.702
943121AE2-341 GEN
Solar/Wind Harmer
18.718
943591AF1-030 GEN
Solar/Wind Harmer
12.479
276694AA1-018 GEN2
Solar/Wind Harmer
7.872
274682WAUKEGAN ;7U
Adder
22.183
276805AD2-038 GEN
Solar/Wind Harmer
6.229
274872LEEDK;1U
Solar/Wind Harmer
0.307
972231SS25-0005
Solar/Wind Harmer
11.357
972181SS23-001
Solar/Wind Harmer
7.098
274752CRETE EC ;2U
Adder
5.849
274753CRETE EC ;3U
Adder
5.849
276799AD1-013 GEN
Solar/Wind Harmer
2.613
946671AF1-331 GEN
Solar/Wind Harmer
0.495
274723RIVER EC ;12
50/50
30.754
972179AH1-673 GEN
50/50
15.92
276164X3-005 C
Solar/Wind Harmer
1.068
274801UNIV PARK;4U
Adder
8.139
276776AD2-060 GEN
Solar/Wind Harmer
0.578
972207SS24-0001
Solar/Wind Harmer
29.403
274773LINCOLN ;4U
Adder
8.27
274774LINCOLN ;5U
Adder
8.27
274674JOLIET 9 ;6U
Adder
20.123
274676JOLIET 29;8U
Adder
39.844
274732ELWOOD EC;7P
Adder
21.152
941551AE2-152 GEN
Solar/Wind Harmer
5.829
274812UNIV PK N;8U
Adder
6.301
274871GR RIDGE ;2U
Solar/Wind Harmer
9.656
274745AC1-111 GEN9
Adder
6.989
276691AA1-018 GEN1
Solar/Wind Harmer
0.581
274682WAUKEGAN ;7U
Adder
22.183
274828WAUKEGAN ;BP
Adder
13.603
960751AF2-366 GEN
Solar/Wind Harmer
3.46
962781AG1-127 GEN
Solar/Wind Harmer
11.467
274872LEEDK;1U
Solar/Wind Harmer
9.863
274751CRETE EC ;1U
Adder
5.849
274754CRETE EC ;4U
Adder
5.849
276901AD2-066 C O1
Solar/Wind Harmer
4.203
276861AD2-134 GEN
Solar/Wind Harmer
2.109
971997AH1-543 GEN
Solar/Wind Harmer
18.488
939401AE1-172 GEN
Solar/Wind Harmer
16.327
957471AF2-041 GEN
Solar/Wind Harmer
35.087
959081AF2-199 GEN
Solar/Wind Harmer
11.696
971067AG2-660 GEN
Solar/Wind Harmer
2.72
276876AE1-163_GEN2
Solar/Wind Harmer
7.846
274822ROCKFORD ;11
Adder
22.887
972235AH1-702 GEN1
Adder
2.926
970819AG2-516 GEN
Solar/Wind Harmer
13.856
971475AH1-234 GEN
Solar/Wind Harmer
25.766
970569AG2-363 GEN
Solar/Wind Harmer
34.09
274857EASY ROAD;U1
Solar/Wind Harmer
5.41
274761LEE CO EC;2U
Adder
10.504
274766LEE CO EC;7U
Adder
10.38
276158O29GEN2
Solar/Wind Harmer
5.493
274877BISHOP HL;1U
Solar/Wind Harmer
3.598
276726Z2-087_GEN
Solar/Wind Harmer
7.754
939741AE1-205 GEN
Solar/Wind Harmer
19.607
270449AD2-020 GEN
Solar/Wind Helper
0.694
958011AF2-095 GEN
Solar/Wind Harmer
19.673
274888KELLY CRK;1U
Solar/Wind Harmer
8.066
274887GEN-1.85
Solar/Wind Harmer
7.282
276843GEN-1.7
Solar/Wind Harmer
0.783
274803UNIV PARK;6U
Adder
7.816
274770LINCOLN ;1U
Adder
8.27
274771LINCOLN ;2U
Adder
8.27
274674JOLIET 9 ;6U
Adder
20.123
972259AH1-714 GEN
Adder
24.494
274808UNIV PK N;4U
Adder
6.273
274847GR RIDGE ;BU
Solar/Wind Harmer
6.352
961501AF2-441 GEN
50/50
14.64
274827FISK ;RP
50/50
11.53
960591AF2-350 GEN
Solar/Wind Harmer
13.662
972037AH1-567 GEN1
Adder
0.245
274775LINCOLN ;6U
Adder
8.27
274776LINCOLN ;7U
Adder
8.27
274777LINCOLN ;8U
Adder
8.27
274687WILL CNTY;4U
Adder
36.789
274687WILL CNTY;4U
Adder
36.789
972227AH1-698 GEN1
Adder
3.388
274675JOLIET 29;7U
Adder
39.845
274675JOLIET 29;7U
Adder
38.422
274728ELWOOD EC;5P
Adder
21.152
274731ELWOOD EC;2P
Adder
21.149
274733ELWOOD EC;3P
Adder
21.149
274735ELWOOD EC;4P
Adder
21.149
970833AG2-524 GEN
Solar/Wind Harmer
10.999
970833AG2-524 GEN
Solar/Wind Harmer
5.116
274814UNIV PK N;0U
Adder
6.356
274807UNIV PK N;3U
Adder
6.342
274805UNIV PK N;1U
Adder
6.315
274811UNIV PK N;7U
Adder
6.301
274746AC1-111 G10
Adder
6.989
274744AC1-111 GEN8
Adder
6.989
971177AH1-047 GEN
Solar/Wind Harmer
7.003
276868AE1-113 GEN
Solar/Wind Harmer
12.091
276882AE2-255 GEN
Solar/Wind Harmer
4.031
971411AH1-196 GEN
Solar/Wind Harmer
17.804
971675AH1-338 GEN
Solar/Wind Harmer
21.263
971171AH1-044 GEN
Solar/Wind Harmer
23.391
274823ROCKFORD ;21
Adder
22.721
276612AE2-035 GEN
Solar/Wind Harmer
2.945
971681AH1-341 GEN
Solar/Wind Harmer
17.046
274863CRW1-WTG
Solar/Wind Harmer
6.3
274864CRW2-WTG
Solar/Wind Harmer
6.3
926823AC1-168 GEN
Solar/Wind Harmer
4.823
961011AF2-392 GEN
Solar/Wind Harmer
12.101
970169AG2-114 GEN
Solar/Wind Harmer
10.835
957751AF2-069 GEN
Solar/Wind Harmer
0.493
274848CAMPGROVE;RU
Solar/Wind Harmer
6.811
946321AF1-296 GEN
Solar/Wind Harmer
10.965
276655WTG1_EQ
Solar/Wind Harmer
8.559
276656WTG2_EQ
Solar/Wind Harmer
1.133
944161AF1-084 GEN
Solar/Wind Helper
0.656
959341AF2-225 GEN
Solar/Wind Harmer
0.282
274855GSG-6 ;RU
Solar/Wind Harmer
4.361
274850MENDOTA H;RU
Solar/Wind Harmer
3.032
276602WESTBROOK C
Solar/Wind Harmer
2.51
276863AD2-134 GEN
Solar/Wind Harmer
2.109
959091AF2-200 GEN
Solar/Wind Harmer
23.391
276889AE2-281 GEN
Solar/Wind Harmer
2.242
958481AF2-142 GEN
Solar/Wind Harmer
18.712
274861TOP CROP ;1U
Solar/Wind Harmer
7.533
274862TOP CROP ;2U
Solar/Wind Harmer
6.29
971573AH1-285 GEN
Solar/Wind Harmer
10.642
274683WAUKEGAN ;8U
Adder
25.952
274683WAUKEGAN ;8U
Adder
21.876
274695ROCKY RD ;2P
Adder
13.696
274693ROCKY RD ;1P
Adder
13.562
274697ROCKY RD ;3P
Adder
3.721
274696ROCKY RD ;4P
Adder
14.019
958491AF2-143 GEN
Solar/Wind Harmer
18.213
962691AG1-118 GEN
Solar/Wind Harmer
36.326
970921AG2-575 GEN
Solar/Wind Harmer
12.058
970921AG2-575 GEN
Solar/Wind Harmer
2.804
942991AE2-321 GEN
Solar/Wind Harmer
11.96
274879MINONK ;1U
Solar/Wind Harmer
8.062
971333AH1-146 GEN
Solar/Wind Harmer
23.675
971335AH1-147 GEN
Solar/Wind Harmer
23.675
971341AH1-150 GEN
Solar/Wind Harmer
23.391
971343AH1-151 GEN
Solar/Wind Harmer
23.391
276872AE1-163_GEN1
Solar/Wind Harmer
7.846
274856ECOGROVE ;U1
Solar/Wind Harmer
3.881
276611AD2-172 GEN
Solar/Wind Harmer
2.945
938861AE1-114 GEN
Solar/Wind Harmer
9.315
274764LEE CO EC;5U
Adder
10.528
274765LEE CO EC;6U
Adder
10.528
274762LEE CO EC;3U
Adder
10.504
274763LEE CO EC;4U
Adder
10.405
276603SUBLETTE C
Solar/Wind Harmer
1.179
972267AH1-718 GEN
Adder
4.614
276741O09 GEN1
Solar/Wind Harmer
3.923
276708O09 GEN2
Solar/Wind Harmer
3.923
274851PROVIDENC;RU
Solar/Wind Harmer
3.06
274849CRESCENT ;1U
Solar/Wind Harmer
1.987
276645AC1-214 GEN1
Solar/Wind Harmer
1.439
276646AC1-214 GEN2
Solar/Wind Harmer
1.439
276782AC1-033 GEN
Solar/Wind Harmer
4.252
270216AD2-079_GEN
Solar/Wind Helper
0.122
960981AF2-389 GEN
Solar/Wind Helper
0.286
957891AF2-083 GEN
Solar/Wind Helper
1.378
972236AH1-702 GEN2
Adder
2.544
970571AG2-364 GEN
Solar/Wind Harmer
22.727
274858EASY ROAD;U2
Solar/Wind Harmer
5.41
274760LEE CO EC;1U
Adder
10.504
274767LEE CO EC;8U
Adder
10.38
276157O29GEN1
Solar/Wind Harmer
4.178
274878BISHOP HL;2U
Solar/Wind Harmer
3.598
965931AG1-462 GEN
Solar/Wind Harmer
26.532
942111AE2-223 GEN
Solar/Wind Harmer
8.037
247643Z2-116 C
Solar/Wind Helper
0.028
24441205WTRV SLR C
Solar/Wind Helper
0.04
990562J1336 G
External Queue
32.91541290283203
990512J1326
External Queue
5.329690456390381
990552J1334 G
External Queue
32.91541290283203
991092J1477
External Queue
2.8509562015533447
991332J1785
External Queue
11.147284507751465
990547J1333 G
External Queue
32.91541290283203
990557J1335 G
External Queue
32.91541290283203
990577J1339
External Queue
20.82658576965332
990647J1355
External Queue
41.498023986816406
990582J1340
External Queue
20.82658576965332
990662J1358
External Queue
14.046708106994629
991247J1684 G
External Queue
26.93834686279297
NYPJM->LTFIMP_NY
CLTF
1.148
LGEELTFEXP_LGEE->PJM
CLTF
0.185
WECLTFEXP_WEC->PJM
CLTF
4.445
CBM West 2LTFEXP_CBM-W2->PJM
CBM
42.605
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.278
AG2-052LTFEXP_AG2-052->PJM
LTF
0.548
AH1-155LTFEXP_AH1-155->PJM
LTF
0.822
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
81.645
CBM South 1LTFEXP_CBM-S1->PJM
CBM
5.461
MECLTFEXP_MEC->PJM
CLTF
14.337
SIGELTFEXP_SIGE->PJM
CLTF
0.07
LAGNLTFEXP_LAGN->PJM
CLTF
5.611
TVALTFEXP_TVA->PJM
CLTF
1.715

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:143.24 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2637.11
MW Contribution:13.66
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
30.74
972179AH1-673 GEN
50/50
15.911
276164X3-005 C
Solar/Wind Harmer
1.066
274801UNIV PARK;4U
Adder
8.103
276776AD2-060 GEN
Solar/Wind Harmer
0.575
972207SS24-0001
Solar/Wind Harmer
29.211
274773LINCOLN ;4U
Adder
8.216
274774LINCOLN ;5U
Adder
8.216
274674JOLIET 9 ;6U
Adder
19.981
274676JOLIET 29;8U
Adder
39.581
274732ELWOOD EC;7P
Adder
20.997
941551AE2-152 GEN
Solar/Wind Harmer
5.78
274812UNIV PK N;8U
Adder
6.289
274871GR RIDGE ;2U
Solar/Wind Harmer
9.57
274745AC1-111 GEN9
Adder
6.926
276691AA1-018 GEN1
Solar/Wind Harmer
0.575
274682WAUKEGAN ;7U
Adder
21.969
274828WAUKEGAN ;BP
Adder
13.47
274751CRETE EC ;1U
Adder
5.854
274754CRETE EC ;4U
Adder
5.854
960751AF2-366 GEN
Solar/Wind Harmer
3.421
962781AG1-127 GEN
Solar/Wind Harmer
11.338
274872LEEDK;1U
Solar/Wind Harmer
9.749
276901AD2-066 C O1
Solar/Wind Harmer
4.15
276861AD2-134 GEN
Solar/Wind Harmer
2.082
971997AH1-543 GEN
Solar/Wind Harmer
18.231
957471AF2-041 GEN
Solar/Wind Harmer
34.627
959081AF2-199 GEN
Solar/Wind Harmer
11.542
971067AG2-660 GEN
Solar/Wind Harmer
2.684
939401AE1-172 GEN
Solar/Wind Harmer
16.071
276876AE1-163_GEN2
Solar/Wind Harmer
7.736
274822ROCKFORD ;11
Adder
22.585
972235AH1-702 GEN1
Adder
2.886
970819AG2-516 GEN
Solar/Wind Harmer
13.665
971475AH1-234 GEN
Solar/Wind Harmer
25.406
970569AG2-363 GEN
Solar/Wind Harmer
33.543
274857EASY ROAD;U1
Solar/Wind Harmer
5.327
274761LEE CO EC;2U
Adder
10.343
274766LEE CO EC;7U
Adder
10.221
276158O29GEN2
Solar/Wind Harmer
5.395
274877BISHOP HL;1U
Solar/Wind Harmer
3.523
276726Z2-087_GEN
Solar/Wind Harmer
7.506
939741AE1-205 GEN
Solar/Wind Harmer
13.592
961501AF2-441 GEN
50/50
14.62
274827FISK ;RP
50/50
11.483
960591AF2-350 GEN
Solar/Wind Harmer
13.59
972037AH1-567 GEN1
Adder
0.244
274775LINCOLN ;6U
Adder
8.216
274776LINCOLN ;7U
Adder
8.216
274777LINCOLN ;8U
Adder
8.216
274687WILL CNTY;4U
Adder
36.565
274687WILL CNTY;4U
Adder
36.565
972227AH1-698 GEN1
Adder
3.367
274675JOLIET 29;7U
Adder
39.582
274675JOLIET 29;7U
Adder
38.168
274728ELWOOD EC;5P
Adder
20.997
274731ELWOOD EC;2P
Adder
20.994
274733ELWOOD EC;3P
Adder
20.994
274735ELWOOD EC;4P
Adder
20.994
274814UNIV PK N;0U
Adder
6.344
274807UNIV PK N;3U
Adder
6.33
274805UNIV PK N;1U
Adder
6.302
274811UNIV PK N;7U
Adder
6.289
970833AG2-524 GEN
Solar/Wind Harmer
10.903
970833AG2-524 GEN
Solar/Wind Harmer
5.071
274746AC1-111 G10
Adder
6.926
274744AC1-111 GEN8
Adder
6.926
971177AH1-047 GEN
Solar/Wind Harmer
6.921
276868AE1-113 GEN
Solar/Wind Harmer
11.941
276882AE2-255 GEN
Solar/Wind Harmer
3.981
971411AH1-196 GEN
Solar/Wind Harmer
17.589
971675AH1-338 GEN
Solar/Wind Harmer
20.997
971171AH1-044 GEN
Solar/Wind Harmer
23.085
274823ROCKFORD ;21
Adder
22.421
276612AE2-035 GEN
Solar/Wind Harmer
2.904
971681AH1-341 GEN
Solar/Wind Harmer
16.791
274863CRW1-WTG
Solar/Wind Harmer
6.181
274864CRW2-WTG
Solar/Wind Harmer
6.181
926823AC1-168 GEN
Solar/Wind Harmer
4.739
961011AF2-392 GEN
Solar/Wind Harmer
11.903
970169AG2-114 GEN
Solar/Wind Harmer
10.595
957751AF2-069 GEN
Solar/Wind Harmer
0.483
274848CAMPGROVE;RU
Solar/Wind Harmer
6.662
946321AF1-296 GEN
Solar/Wind Harmer
10.744
276655WTG1_EQ
Solar/Wind Harmer
8.286
276656WTG2_EQ
Solar/Wind Harmer
1.097
941731AE2-173 GEN
Solar/Wind Harmer
3.951
958011AF2-095 GEN
Solar/Wind Harmer
19.57
274888KELLY CRK;1U
Solar/Wind Harmer
8.024
274887GEN-1.85
Solar/Wind Harmer
7.244
276843GEN-1.7
Solar/Wind Harmer
0.779
274803UNIV PARK;6U
Adder
7.784
274770LINCOLN ;1U
Adder
8.216
274771LINCOLN ;2U
Adder
8.216
274674JOLIET 9 ;6U
Adder
19.981
972259AH1-714 GEN
Adder
24.316
274808UNIV PK N;4U
Adder
6.261
274847GR RIDGE ;BU
Solar/Wind Harmer
6.295
958481AF2-142 GEN
Solar/Wind Harmer
18.537
274861TOP CROP ;1U
Solar/Wind Harmer
7.462
274862TOP CROP ;2U
Solar/Wind Harmer
6.231
971573AH1-285 GEN
Solar/Wind Harmer
10.539
274683WAUKEGAN ;8U
Adder
25.698
274683WAUKEGAN ;8U
Adder
21.662
274695ROCKY RD ;2P
Adder
13.56
274693ROCKY RD ;1P
Adder
13.426
274697ROCKY RD ;3P
Adder
3.684
274696ROCKY RD ;4P
Adder
13.879
958491AF2-143 GEN
Solar/Wind Harmer
18.008
962691AG1-118 GEN
Solar/Wind Harmer
35.927
970921AG2-575 GEN
Solar/Wind Harmer
11.923
970921AG2-575 GEN
Solar/Wind Harmer
2.773
942991AE2-321 GEN
Solar/Wind Harmer
11.821
274879MINONK ;1U
Solar/Wind Harmer
7.962
971333AH1-146 GEN
Solar/Wind Harmer
23.384
971335AH1-147 GEN
Solar/Wind Harmer
23.384
971341AH1-150 GEN
Solar/Wind Harmer
23.085
971343AH1-151 GEN
Solar/Wind Harmer
23.085
276872AE1-163_GEN1
Solar/Wind Harmer
7.736
274856ECOGROVE ;U1
Solar/Wind Harmer
3.827
276611AD2-172 GEN
Solar/Wind Harmer
2.904
938861AE1-114 GEN
Solar/Wind Harmer
9.176
274764LEE CO EC;5U
Adder
10.367
274765LEE CO EC;6U
Adder
10.367
274762LEE CO EC;3U
Adder
10.343
274763LEE CO EC;4U
Adder
10.245
276603SUBLETTE C
Solar/Wind Harmer
1.161
972267AH1-718 GEN
Adder
4.538
276741O09 GEN1
Solar/Wind Harmer
3.854
276708O09 GEN2
Solar/Wind Harmer
3.854
274851PROVIDENC;RU
Solar/Wind Harmer
2.997
274849CRESCENT ;1U
Solar/Wind Harmer
1.946
276645AC1-214 GEN1
Solar/Wind Harmer
1.41
276646AC1-214 GEN2
Solar/Wind Harmer
1.41
276782AC1-033 GEN
Solar/Wind Harmer
4.163
274724RIVER EC ;11
50/50
30.779
957371AF2-031 GEN
50/50
1.524
274826FISK ;BP
50/50
16.202
274800UNIV PARK;3U
Adder
8.103
972038AH1-567 GEN2
Adder
0.507
276772AC2-154 GEN
Solar/Wind Harmer
3.79
276806AD2-047 C O1
Solar/Wind Harmer
14.538
970941AG2-585 GEN
Solar/Wind Harmer
16.988
274802UNIV PARK;5U
Adder
7.784
274772LINCOLN ;3U
Adder
8.216
276893AG1-478 C
Solar/Wind Harmer
0.542
972228AH1-698 GEN2
Adder
4.783
274676JOLIET 29;8U
Adder
38.167
274730ELWOOD EC;6P
Adder
20.997
274734ELWOOD EC;8P
Adder
20.997
274736ELWOOD EC;9P
Adder
20.997
274729ELWOOD EC;1P
Adder
20.994
276897AD1-100 C
Solar/Wind Harmer
36.988
939351AE1-166 GEN
Solar/Wind Harmer
7.558
970707AG2-453 GEN
Solar/Wind Harmer
35.422
943121AE2-341 GEN
Solar/Wind Harmer
18.546
943591AF1-030 GEN
Solar/Wind Harmer
12.364
276694AA1-018 GEN2
Solar/Wind Harmer
7.799
274682WAUKEGAN ;7U
Adder
21.969
276805AD2-038 GEN
Solar/Wind Harmer
6.159
972231SS25-0005
Solar/Wind Harmer
11.367
972181SS23-001
Solar/Wind Harmer
7.104
274752CRETE EC ;2U
Adder
5.854
274753CRETE EC ;3U
Adder
5.854
274872LEEDK;1U
Solar/Wind Harmer
0.304
276799AD1-013 GEN
Solar/Wind Harmer
2.581
946671AF1-331 GEN
Solar/Wind Harmer
0.489
274855GSG-6 ;RU
Solar/Wind Harmer
4.306
274850MENDOTA H;RU
Solar/Wind Harmer
2.994
276602WESTBROOK C
Solar/Wind Harmer
2.479
276863AD2-134 GEN
Solar/Wind Harmer
2.082
959091AF2-200 GEN
Solar/Wind Harmer
23.085
276889AE2-281 GEN
Solar/Wind Harmer
2.21
972236AH1-702 GEN2
Adder
2.51
970571AG2-364 GEN
Solar/Wind Harmer
22.362
274858EASY ROAD;U2
Solar/Wind Harmer
5.327
274760LEE CO EC;1U
Adder
10.343
274767LEE CO EC;8U
Adder
10.221
276157O29GEN1
Solar/Wind Harmer
4.104
274878BISHOP HL;2U
Solar/Wind Harmer
3.523
965931AG1-462 GEN
Solar/Wind Harmer
25.979
990562J1336 G
External Queue
33.3844108581543
990512J1326
External Queue
5.3167853355407715
990552J1334 G
External Queue
33.3844108581543
991092J1477
External Queue
2.8052659034729004
990762J1386
External Queue
10.017333030700684
991332J1785
External Queue
11.59352970123291
990547J1333 G
External Queue
33.3844108581543
990557J1335 G
External Queue
33.3844108581543
990577J1339
External Queue
21.181657791137695
990647J1355
External Queue
42.006256103515625
990582J1340
External Queue
21.181657791137695
990662J1358
External Queue
14.583775520324707
991247J1684 G
External Queue
27.351411819458008
NYPJM->LTFIMP_NY
CLTF
1.102
WECLTFEXP_WEC->PJM
CLTF
4.387
CBM West 2LTFEXP_CBM-W2->PJM
CBM
36.11
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.396
AG2-052LTFEXP_AG2-052->PJM
LTF
0.543
AH1-155LTFEXP_AH1-155->PJM
LTF
0.815
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.186
CBM West 1LTFEXP_CBM-W1->PJM
CBM
82.324
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.814
MECLTFEXP_MEC->PJM
CLTF
13.851
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.347
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.921
LAGNLTFEXP_LAGN->PJM
CLTF
4.851
TVALTFEXP_TVA->PJM
CLTF
1.322

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o 765-L11215__-S_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
765-L11215__-S_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.81 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2297.73
MW Contribution:9.88
Bus #Bus NameTypeMW Contribution
961501AF2-441 GEN
50/50
15.114
274827FISK ;RP
50/50
11.896
960591AF2-350 GEN
Solar/Wind Harmer
9.826
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
11.59
274776LINCOLN ;7U
Adder
11.59
274777LINCOLN ;8U
Adder
11.59
274687WILL CNTY;4U
Adder
37.915
274687WILL CNTY;4U
Adder
37.915
972227AH1-698 GEN1
Adder
3.493
274675JOLIET 29;7U
Adder
41.051
274675JOLIET 29;7U
Adder
39.585
274728ELWOOD EC;5P
Adder
21.778
274731ELWOOD EC;2P
Adder
21.774
274733ELWOOD EC;3P
Adder
21.774
274723RIVER EC ;12
50/50
31.772
972179AH1-673 GEN
50/50
16.446
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
8.394
276776AD2-060 GEN
Solar/Wind Harmer
1.026
274773LINCOLN ;4U
Adder
11.59
274774LINCOLN ;5U
Adder
11.59
274674JOLIET 9 ;6U
Adder
20.714
274676JOLIET 29;8U
Adder
41.051
274732ELWOOD EC;7P
Adder
21.778
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
6.546
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.182
276691AA1-018 GEN1
Solar/Wind Harmer
1.083
274682WAUKEGAN ;7U
Adder
22.781
274828WAUKEGAN ;BP
Adder
13.969
274751CRETE EC ;1U
Adder
10.307
274754CRETE EC ;4U
Adder
10.307
962781AG1-127 GEN
Solar/Wind Harmer
8.208
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
276861AD2-134 GEN
Solar/Wind Harmer
0.151
971997AH1-543 GEN
Solar/Wind Harmer
4.397
957471AF2-041 GEN
Solar/Wind Harmer
25.05
959081AF2-199 GEN
Solar/Wind Harmer
8.35
971067AG2-660 GEN
Solar/Wind Harmer
2.783
939401AE1-172 GEN
Solar/Wind Harmer
6.239
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
23.418
972235AH1-702 GEN1
Adder
2.993
970819AG2-516 GEN
Solar/Wind Harmer
9.885
971475AH1-234 GEN
Solar/Wind Harmer
3.982
970569AG2-363 GEN
Solar/Wind Harmer
24.267
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.724
274766LEE CO EC;7U
Adder
10.598
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.254
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.61
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
4.931
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.091
276615X2-022 GEN
Solar/Wind Harmer
0.055
965911AG1-460 GEN
Solar/Wind Harmer
0.941
274724RIVER EC ;11
50/50
31.802
957371AF2-031 GEN
50/50
1.574
274826FISK ;BP
50/50
16.786
274800UNIV PARK;3U
Adder
8.394
972038AH1-567 GEN2
Adder
0.525
276806AD2-047 C O1
Solar/Wind Harmer
5.568
970941AG2-585 GEN
Solar/Wind Harmer
12.282
274802UNIV PARK;5U
Adder
8.076
274772LINCOLN ;3U
Adder
11.59
276893AG1-478 C
Solar/Wind Harmer
0.372
972228AH1-698 GEN2
Adder
4.962
274676JOLIET 29;8U
Adder
39.585
274730ELWOOD EC;6P
Adder
21.778
274734ELWOOD EC;8P
Adder
21.778
274736ELWOOD EC;9P
Adder
21.778
274729ELWOOD EC;1P
Adder
21.774
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
29.902
943121AE2-341 GEN
Solar/Wind Harmer
14.998
943591AF1-030 GEN
Solar/Wind Harmer
9.974
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.781
274752CRETE EC ;2U
Adder
10.307
274753CRETE EC ;3U
Adder
10.307
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.315
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.901
274855GSG-6 ;RU
Solar/Wind Harmer
0.309
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.151
959091AF2-200 GEN
Solar/Wind Harmer
16.7
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.603
970571AG2-364 GEN
Solar/Wind Harmer
16.178
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.724
274767LEE CO EC;8U
Adder
10.598
276157O29GEN1
Solar/Wind Harmer
1.26
274878BISHOP HL;2U
Solar/Wind Harmer
0.254
965931AG1-462 GEN
Solar/Wind Harmer
18.79
942111AE2-223 GEN
Solar/Wind Harmer
2.231
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.661
959611AF2-252 GEN
Solar/Wind Harmer
2.185
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.515
276668AB2-070 GEN1
Solar/Wind Harmer
0.198
276621W2-048 GEN
Solar/Wind Harmer
0.262
276838X2-022 GEN2
Solar/Wind Harmer
0.293
942481AE2-261 GEN
Solar/Wind Harmer
14.075
274735ELWOOD EC;4P
Adder
21.774
274814UNIV PK N;0U
Adder
6.603
274807UNIV PK N;3U
Adder
6.589
274805UNIV PK N;1U
Adder
6.56
274811UNIV PK N;7U
Adder
6.546
970833AG2-524 GEN
Solar/Wind Harmer
9.94
970833AG2-524 GEN
Solar/Wind Harmer
6.627
274746AC1-111 G10
Adder
7.182
274744AC1-111 GEN8
Adder
7.182
971177AH1-047 GEN
Solar/Wind Harmer
5.269
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971411AH1-196 GEN
Solar/Wind Harmer
12.725
971675AH1-338 GEN
Solar/Wind Harmer
3.291
971171AH1-044 GEN
Solar/Wind Harmer
16.7
274823ROCKFORD ;21
Adder
23.249
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
13.037
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.354
961011AF2-392 GEN
Solar/Wind Harmer
4.645
970169AG2-114 GEN
Solar/Wind Harmer
7.664
957751AF2-069 GEN
Solar/Wind Harmer
0.251
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
4.171
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.208
941731AE2-173 GEN
Solar/Wind Harmer
5.72
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.198
276848AB2-070 GEN3
Solar/Wind Harmer
0.197
944221AF1-090 GEN
Solar/Wind Harmer
2.406
274888KELLY CRK;1U
Solar/Wind Harmer
0.577
274887GEN-1.85
Solar/Wind Harmer
0.259
276843GEN-1.7
Solar/Wind Harmer
0.318
958011AF2-095 GEN
Solar/Wind Harmer
14.149
274803UNIV PARK;6U
Adder
8.076
274770LINCOLN ;1U
Adder
11.59
274771LINCOLN ;2U
Adder
11.59
274674JOLIET 9 ;6U
Adder
20.714
972259AH1-714 GEN
Adder
25.222
274808UNIV PK N;4U
Adder
6.517
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
958481AF2-142 GEN
Solar/Wind Harmer
13.413
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.206
971573AH1-285 GEN
Solar/Wind Harmer
1.652
274683WAUKEGAN ;8U
Adder
26.649
274683WAUKEGAN ;8U
Adder
22.464
274696ROCKY RD ;4P
Adder
14.393
274695ROCKY RD ;2P
Adder
14.061
274693ROCKY RD ;1P
Adder
13.923
274697ROCKY RD ;3P
Adder
3.82
958491AF2-143 GEN
Solar/Wind Harmer
13.029
962691AG1-118 GEN
Solar/Wind Harmer
25.992
970921AG2-575 GEN
Solar/Wind Harmer
8.625
970921AG2-575 GEN
Solar/Wind Harmer
2.875
942991AE2-321 GEN
Solar/Wind Harmer
9.55
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
16.917
971335AH1-147 GEN
Solar/Wind Harmer
16.917
971341AH1-150 GEN
Solar/Wind Harmer
16.7
971343AH1-151 GEN
Solar/Wind Harmer
16.7
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.194
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.589
274764LEE CO EC;5U
Adder
10.749
274765LEE CO EC;6U
Adder
10.749
274762LEE CO EC;3U
Adder
10.724
274763LEE CO EC;4U
Adder
10.623
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.705
276741O09 GEN1
Solar/Wind Harmer
0.278
276708O09 GEN2
Solar/Wind Harmer
0.278
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.299
276646AC1-214 GEN2
Solar/Wind Harmer
0.299
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.185
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
9.598
276911AD2-131_GEN
Solar/Wind Harmer
0.632
990562J1336 G
External Queue
34.15701675415039
990512J1326
External Queue
5.464118957519531
991337J1802
External Queue
7.676261901855469
990117J1214
External Queue
18.796567916870117
990727J1377 G
External Queue
6.363696098327637
990552J1334 G
External Queue
34.15701675415039
991092J1477
External Queue
2.8750312328338623
991303J1755 G
External Queue
4.699468612670898
990762J1386
External Queue
10.359478950500488
991332J1785
External Queue
12.013145446777344
990547J1333 G
External Queue
34.15701675415039
990557J1335 G
External Queue
34.15701675415039
990577J1339
External Queue
21.8123722076416
990647J1355
External Queue
42.76608657836914
990582J1340
External Queue
21.8123722076416
990662J1358
External Queue
15.139077186584473
991777J1629 G
External Queue
12.388229370117188
991247J1684 G
External Queue
28.054828643798828
990407J1304
External Queue
4.24149227142334
NYPJM->LTFIMP_NY
CLTF
1.15
WECLTFEXP_WEC->PJM
CLTF
4.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.212
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.618
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.855
MECLTFEXP_MEC->PJM
CLTF
14.351
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.386
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.034
LAGNLTFEXP_LAGN->PJM
CLTF
4.987
TVALTFEXP_TVA->PJM
CLTF
1.346

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P1-2_#695_1681_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#695_1681_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.8 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2297.61
MW Contribution:9.88
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
31.772
972179AH1-673 GEN
50/50
16.446
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
8.394
276776AD2-060 GEN
Solar/Wind Harmer
1.026
274773LINCOLN ;4U
Adder
11.59
274774LINCOLN ;5U
Adder
11.59
274674JOLIET 9 ;6U
Adder
20.714
274676JOLIET 29;8U
Adder
41.051
274732ELWOOD EC;7P
Adder
21.778
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
6.546
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
7.182
276691AA1-018 GEN1
Solar/Wind Harmer
1.083
274682WAUKEGAN ;7U
Adder
22.781
274828WAUKEGAN ;BP
Adder
13.969
274751CRETE EC ;1U
Adder
10.307
274754CRETE EC ;4U
Adder
10.307
962781AG1-127 GEN
Solar/Wind Harmer
8.208
274872LEEDK;1U
Solar/Wind Harmer
0.005
276901AD2-066 C O1
Solar/Wind Harmer
0.008
276861AD2-134 GEN
Solar/Wind Harmer
0.151
971997AH1-543 GEN
Solar/Wind Harmer
4.397
957471AF2-041 GEN
Solar/Wind Harmer
25.05
959081AF2-199 GEN
Solar/Wind Harmer
8.35
971067AG2-660 GEN
Solar/Wind Harmer
2.783
939401AE1-172 GEN
Solar/Wind Harmer
6.239
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
274822ROCKFORD ;11
Adder
23.418
972235AH1-702 GEN1
Adder
2.993
970819AG2-516 GEN
Solar/Wind Harmer
9.885
971475AH1-234 GEN
Solar/Wind Harmer
3.982
970569AG2-363 GEN
Solar/Wind Harmer
24.267
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.724
274766LEE CO EC;7U
Adder
10.598
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.254
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.61
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
972175AH1-670 GEN
Solar/Wind Harmer
4.931
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.091
276615X2-022 GEN
Solar/Wind Harmer
0.055
965911AG1-460 GEN
Solar/Wind Harmer
0.941
274888KELLY CRK;1U
Solar/Wind Harmer
0.577
274887GEN-1.85
Solar/Wind Harmer
0.259
276843GEN-1.7
Solar/Wind Harmer
0.318
958011AF2-095 GEN
Solar/Wind Harmer
14.149
274803UNIV PARK;6U
Adder
8.076
274770LINCOLN ;1U
Adder
11.59
274724RIVER EC ;11
50/50
31.802
957371AF2-031 GEN
50/50
1.574
274826FISK ;BP
50/50
16.786
274800UNIV PARK;3U
Adder
8.394
972038AH1-567 GEN2
Adder
0.525
276806AD2-047 C O1
Solar/Wind Harmer
5.568
970941AG2-585 GEN
Solar/Wind Harmer
12.282
274802UNIV PARK;5U
Adder
8.076
274772LINCOLN ;3U
Adder
11.59
276893AG1-478 C
Solar/Wind Harmer
0.372
972228AH1-698 GEN2
Adder
4.962
274676JOLIET 29;8U
Adder
39.585
274730ELWOOD EC;6P
Adder
21.778
274734ELWOOD EC;8P
Adder
21.778
274736ELWOOD EC;9P
Adder
21.778
274729ELWOOD EC;1P
Adder
21.774
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
29.902
943121AE2-341 GEN
Solar/Wind Harmer
14.998
943591AF1-030 GEN
Solar/Wind Harmer
9.974
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
22.781
274752CRETE EC ;2U
Adder
10.307
274753CRETE EC ;3U
Adder
10.307
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274872LEEDK;1U
Solar/Wind Harmer
0.315
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.901
274855GSG-6 ;RU
Solar/Wind Harmer
0.309
274850MENDOTA H;RU
Solar/Wind Harmer
0.099
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.151
959091AF2-200 GEN
Solar/Wind Harmer
16.7
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
2.603
970571AG2-364 GEN
Solar/Wind Harmer
16.178
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.724
274767LEE CO EC;8U
Adder
10.598
276157O29GEN1
Solar/Wind Harmer
1.26
274878BISHOP HL;2U
Solar/Wind Harmer
0.254
965931AG1-462 GEN
Solar/Wind Harmer
18.79
942111AE2-223 GEN
Solar/Wind Harmer
2.231
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.661
959611AF2-252 GEN
Solar/Wind Harmer
2.185
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.515
276668AB2-070 GEN1
Solar/Wind Harmer
0.198
276621W2-048 GEN
Solar/Wind Harmer
0.262
276838X2-022 GEN2
Solar/Wind Harmer
0.293
942481AE2-261 GEN
Solar/Wind Harmer
14.075
274771LINCOLN ;2U
Adder
11.59
274674JOLIET 9 ;6U
Adder
20.714
972259AH1-714 GEN
Adder
25.222
274808UNIV PK N;4U
Adder
6.517
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
958481AF2-142 GEN
Solar/Wind Harmer
13.413
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.206
971573AH1-285 GEN
Solar/Wind Harmer
1.652
274683WAUKEGAN ;8U
Adder
26.649
274683WAUKEGAN ;8U
Adder
22.464
274696ROCKY RD ;4P
Adder
14.393
274695ROCKY RD ;2P
Adder
14.061
274693ROCKY RD ;1P
Adder
13.923
274697ROCKY RD ;3P
Adder
3.82
958491AF2-143 GEN
Solar/Wind Harmer
13.029
962691AG1-118 GEN
Solar/Wind Harmer
25.992
970921AG2-575 GEN
Solar/Wind Harmer
8.625
970921AG2-575 GEN
Solar/Wind Harmer
2.875
942991AE2-321 GEN
Solar/Wind Harmer
9.55
274879MINONK ;1U
Solar/Wind Harmer
0.36
971333AH1-146 GEN
Solar/Wind Harmer
16.917
971335AH1-147 GEN
Solar/Wind Harmer
16.917
971341AH1-150 GEN
Solar/Wind Harmer
16.7
971343AH1-151 GEN
Solar/Wind Harmer
16.7
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274856ECOGROVE ;U1
Solar/Wind Harmer
0.194
276611AD2-172 GEN
Solar/Wind Harmer
0.002
938861AE1-114 GEN
Solar/Wind Harmer
4.589
274764LEE CO EC;5U
Adder
10.749
274765LEE CO EC;6U
Adder
10.749
274762LEE CO EC;3U
Adder
10.724
274763LEE CO EC;4U
Adder
10.623
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.705
276741O09 GEN1
Solar/Wind Harmer
0.278
276708O09 GEN2
Solar/Wind Harmer
0.278
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.299
276646AC1-214 GEN2
Solar/Wind Harmer
0.299
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.185
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
276916AD2-100_GEN
Solar/Wind Harmer
9.598
276911AD2-131_GEN
Solar/Wind Harmer
0.632
961501AF2-441 GEN
50/50
15.114
274827FISK ;RP
50/50
11.896
960591AF2-350 GEN
Solar/Wind Harmer
9.826
972037AH1-567 GEN1
Adder
0.254
274775LINCOLN ;6U
Adder
11.59
274776LINCOLN ;7U
Adder
11.59
274777LINCOLN ;8U
Adder
11.59
274687WILL CNTY;4U
Adder
37.915
274687WILL CNTY;4U
Adder
37.915
972227AH1-698 GEN1
Adder
3.493
274675JOLIET 29;7U
Adder
41.051
274675JOLIET 29;7U
Adder
39.585
274728ELWOOD EC;5P
Adder
21.778
274731ELWOOD EC;2P
Adder
21.774
274733ELWOOD EC;3P
Adder
21.774
274735ELWOOD EC;4P
Adder
21.774
274814UNIV PK N;0U
Adder
6.603
274807UNIV PK N;3U
Adder
6.589
274805UNIV PK N;1U
Adder
6.56
274811UNIV PK N;7U
Adder
6.546
970833AG2-524 GEN
Solar/Wind Harmer
9.94
970833AG2-524 GEN
Solar/Wind Harmer
6.627
274746AC1-111 G10
Adder
7.182
274744AC1-111 GEN8
Adder
7.182
971177AH1-047 GEN
Solar/Wind Harmer
5.269
276868AE1-113 GEN
Solar/Wind Harmer
1.713
276882AE2-255 GEN
Solar/Wind Harmer
0.998
971411AH1-196 GEN
Solar/Wind Harmer
12.725
971675AH1-338 GEN
Solar/Wind Harmer
3.291
971171AH1-044 GEN
Solar/Wind Harmer
16.7
274823ROCKFORD ;21
Adder
23.249
276612AE2-035 GEN
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
13.037
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
926823AC1-168 GEN
Solar/Wind Harmer
1.354
961011AF2-392 GEN
Solar/Wind Harmer
4.645
970169AG2-114 GEN
Solar/Wind Harmer
7.664
957751AF2-069 GEN
Solar/Wind Harmer
0.251
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
4.171
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.208
941731AE2-173 GEN
Solar/Wind Harmer
5.72
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.198
276848AB2-070 GEN3
Solar/Wind Harmer
0.197
944221AF1-090 GEN
Solar/Wind Harmer
2.406
990562J1336 G
External Queue
34.15701675415039
990512J1326
External Queue
5.464118957519531
991337J1802
External Queue
7.676261901855469
990117J1214
External Queue
18.796567916870117
990727J1377 G
External Queue
6.363696098327637
990552J1334 G
External Queue
34.15701675415039
991092J1477
External Queue
2.8750312328338623
991303J1755 G
External Queue
4.699468612670898
990762J1386
External Queue
10.359478950500488
991332J1785
External Queue
12.013145446777344
990547J1333 G
External Queue
34.15701675415039
990557J1335 G
External Queue
34.15701675415039
990577J1339
External Queue
21.8123722076416
990647J1355
External Queue
42.76608657836914
990582J1340
External Queue
21.8123722076416
990662J1358
External Queue
15.139077186584473
991777J1629 G
External Queue
12.388229370117188
991247J1684 G
External Queue
28.054828643798828
990407J1304
External Queue
4.24149227142334
NYPJM->LTFIMP_NY
CLTF
1.15
WECLTFEXP_WEC->PJM
CLTF
4.549
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.212
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.43
AG2-052LTFEXP_AG2-052->PJM
LTF
0.556
AH1-155LTFEXP_AH1-155->PJM
LTF
0.834
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.205
CBM West 1LTFEXP_CBM-W1->PJM
CBM
86.618
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.855
MECLTFEXP_MEC->PJM
CLTF
14.351
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.386
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.034
LAGNLTFEXP_LAGN->PJM
CLTF
4.987
TVALTFEXP_TVA->PJM
CLTF
1.346

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#11009___SRT-A-1


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:118.06 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2173.47
MW Contribution:10.64
Bus #Bus NameTypeMW Contribution
274808UNIV PK N;4U
50/50
6.662
965681AG1-436 GEN
Solar/Wind Harmer
18.282
965791AG1-447 GEN
Solar/Wind Harmer
9.353
274803UNIV PARK;6U
Adder
7.024
274724RIVER EC ;11
50/50
28.7
957371AF2-031 GEN
50/50
1.421
274752CRETE EC ;2U
50/50
6.972
274753CRETE EC ;3U
50/50
6.972
274806UNIV PK N;2U
50/50
0.374
274815UNIV PK N;XU
50/50
0.368
274816UNIV PK N;YU
50/50
0.367
274810UNIV PK N;6U
50/50
0.366
274826FISK ;BP
50/50
14.243
972231SS25-0005
Solar/Wind Harmer
12.757
972181SS23-001
Solar/Wind Harmer
7.973
274800UNIV PARK;3U
Adder
7.042
972038AH1-567 GEN2
Adder
0.441
274802UNIV PARK;5U
Adder
7.024
276772AC2-154 GEN
Solar/Wind Harmer
3.232
276806AD2-047 C O1
Solar/Wind Harmer
12.398
970941AG2-585 GEN
Solar/Wind Harmer
14.487
276893AG1-478 C
Solar/Wind Harmer
0.451
972228AH1-698 GEN2
Adder
3.966
274676JOLIET 29;8U
Adder
31.669
274730ELWOOD EC;6P
Adder
17.371
274734ELWOOD EC;8P
Adder
17.371
274736ELWOOD EC;9P
Adder
17.371
274729ELWOOD EC;1P
Adder
17.362
276694AA1-018 GEN2
Solar/Wind Harmer
6.592
276805AD2-038 GEN
Solar/Wind Harmer
5.156
276897AD1-100 C
Solar/Wind Harmer
29.097
939351AE1-166 GEN
Solar/Wind Harmer
5.945
274682WAUKEGAN ;7U
Adder
17.388
276889AE2-281 GEN
Solar/Wind Harmer
1.824
943121AE2-341 GEN
Solar/Wind Harmer
13.826
943591AF1-030 GEN
Solar/Wind Harmer
9.217
970571AG2-364 GEN
Solar/Wind Harmer
18.258
274872LEEDK;1U
Solar/Wind Harmer
0.232
970707AG2-453 GEN
Solar/Wind Harmer
25.251
276799AD1-013 GEN
Solar/Wind Harmer
1.981
946671AF1-331 GEN
Solar/Wind Harmer
0.375
274855GSG-6 ;RU
Solar/Wind Harmer
3.306
274850MENDOTA H;RU
Solar/Wind Harmer
2.299
276602WESTBROOK C
Solar/Wind Harmer
1.903
276863AD2-134 GEN
Solar/Wind Harmer
1.599
959091AF2-200 GEN
Solar/Wind Harmer
17.845
972236AH1-702 GEN2
Adder
1.952
274772LINCOLN ;3U
Adder
5.515
274858EASY ROAD;U2
Solar/Wind Harmer
4.146
274760LEE CO EC;1U
Adder
8.049
274767LEE CO EC;8U
Adder
7.954
276157O29GEN1
Solar/Wind Harmer
3.209
274878BISHOP HL;2U
Solar/Wind Harmer
2.788
965931AG1-462 GEN
Solar/Wind Harmer
20.332
274723RIVER EC ;12
50/50
28.753
972179AH1-673 GEN
50/50
14.849
274751CRETE EC ;1U
50/50
6.972
274754CRETE EC ;4U
50/50
6.972
274813UNIV PK N;9U
50/50
0.367
274809UNIV PK N;5U
50/50
0.365
274812UNIV PK N;8U
50/50
6.692
966431AG1-512 GEN
50/50
2.343
276164X3-005 C
Solar/Wind Harmer
0.958
274801UNIV PARK;4U
Adder
7.042
276776AD2-060 GEN
Solar/Wind Harmer
0.49
274676JOLIET 29;8U
Adder
32.842
274674JOLIET 9 ;6U
Adder
16.382
274732ELWOOD EC;7P
Adder
17.371
276691AA1-018 GEN1
Solar/Wind Harmer
0.486
941551AE2-152 GEN
Solar/Wind Harmer
4.547
274682WAUKEGAN ;7U
Adder
17.388
274871GR RIDGE ;2U
Solar/Wind Harmer
7.436
274828WAUKEGAN ;BP
Adder
10.66
961501AF2-441 GEN
50/50
13.333
274814UNIV PK N;0U
50/50
6.75
274807UNIV PK N;3U
50/50
6.736
274805UNIV PK N;1U
50/50
6.706
274811UNIV PK N;7U
50/50
6.692
274827FISK ;RP
50/50
10.094
960681AF2-359 GEN
Solar/Wind Harmer
5.525
972037AH1-567 GEN1
Adder
0.22
960591AF2-350 GEN
Solar/Wind Harmer
11.589
274687WILL CNTY;4U
Adder
30.801
274687WILL CNTY;4U
Adder
30.801
274675JOLIET 29;7U
Adder
32.84
274675JOLIET 29;7U
Adder
31.667
972227AH1-698 GEN1
Adder
2.791
274728ELWOOD EC;5P
Adder
17.371
274731ELWOOD EC;2P
Adder
17.362
274733ELWOOD EC;3P
Adder
17.362
274735ELWOOD EC;4P
Adder
17.362
970833AG2-524 GEN
Solar/Wind Harmer
8.503
970833AG2-524 GEN
Solar/Wind Harmer
3.955
276868AE1-113 GEN
Solar/Wind Harmer
9.754
276882AE2-255 GEN
Solar/Wind Harmer
3.252
274746AC1-111 G10
Adder
5.294
274744AC1-111 GEN8
Adder
5.294
971177AH1-047 GEN
Solar/Wind Harmer
5.384
971411AH1-196 GEN
Solar/Wind Harmer
13.697
971675AH1-338 GEN
Solar/Wind Harmer
16.12
274823ROCKFORD ;21
Adder
17.445
971171AH1-044 GEN
Solar/Wind Harmer
17.845
274775LINCOLN ;6U
Adder
5.515
274776LINCOLN ;7U
Adder
5.515
274777LINCOLN ;8U
Adder
5.515
276612AE2-035 GEN
Solar/Wind Harmer
2.26
276901AD2-066 C O1
Solar/Wind Harmer
3.358
276876AE1-163_GEN2
Solar/Wind Harmer
6.384
274745AC1-111 GEN9
Adder
5.294
970569AG2-363 GEN
Solar/Wind Harmer
27.387
960751AF2-366 GEN
Solar/Wind Harmer
2.616
962781AG1-127 GEN
Solar/Wind Harmer
8.671
274872LEEDK;1U
Solar/Wind Harmer
7.455
971997AH1-543 GEN
Solar/Wind Harmer
14.261
274822ROCKFORD ;11
Adder
17.573
276861AD2-134 GEN
Solar/Wind Harmer
1.599
957471AF2-041 GEN
Solar/Wind Harmer
26.767
959081AF2-199 GEN
Solar/Wind Harmer
8.922
971067AG2-660 GEN
Solar/Wind Harmer
2.075
972235AH1-702 GEN1
Adder
2.245
972207SS24-0001
Solar/Wind Harmer
19.609
274773LINCOLN ;4U
Adder
5.515
274774LINCOLN ;5U
Adder
5.515
970819AG2-516 GEN
Solar/Wind Harmer
10.64
939401AE1-172 GEN
Solar/Wind Harmer
12.327
971475AH1-234 GEN
Solar/Wind Harmer
19.807
274857EASY ROAD;U1
Solar/Wind Harmer
4.146
274761LEE CO EC;2U
Adder
8.049
274766LEE CO EC;7U
Adder
7.954
276158O29GEN2
Solar/Wind Harmer
4.219
274877BISHOP HL;1U
Solar/Wind Harmer
2.788
276726Z2-087_GEN
Solar/Wind Harmer
3.571
971681AH1-341 GEN
Solar/Wind Harmer
13.054
926823AC1-168 GEN
Solar/Wind Harmer
3.743
961011AF2-392 GEN
Solar/Wind Harmer
9.267
274863CRW1-WTG
Solar/Wind Harmer
4.746
274864CRW2-WTG
Solar/Wind Harmer
4.746
957751AF2-069 GEN
Solar/Wind Harmer
0.383
274848CAMPGROVE;RU
Solar/Wind Harmer
5.28
970169AG2-114 GEN
Solar/Wind Harmer
8.142
946321AF1-296 GEN
Solar/Wind Harmer
8.404
276655WTG1_EQ
Solar/Wind Harmer
6.393
958011AF2-095 GEN
Solar/Wind Harmer
16.689
274888KELLY CRK;1U
Solar/Wind Harmer
6.842
274887GEN-1.85
Solar/Wind Harmer
6.177
276843GEN-1.7
Solar/Wind Harmer
0.665
274674JOLIET 9 ;6U
Adder
16.382
274861TOP CROP ;1U
Solar/Wind Harmer
6.332
274862TOP CROP ;2U
Solar/Wind Harmer
5.287
958481AF2-142 GEN
Solar/Wind Harmer
15.669
958491AF2-143 GEN
Solar/Wind Harmer
15.077
972259AH1-714 GEN
Adder
18.776
274847GR RIDGE ;BU
Solar/Wind Harmer
4.892
274683WAUKEGAN ;8U
Adder
20.336
274683WAUKEGAN ;8U
Adder
17.142
274879MINONK ;1U
Solar/Wind Harmer
6.503
276872AE1-163_GEN1
Solar/Wind Harmer
6.384
274696ROCKY RD ;4P
Adder
10.753
274695ROCKY RD ;2P
Adder
10.505
274693ROCKY RD ;1P
Adder
10.402
274697ROCKY RD ;3P
Adder
2.854
942991AE2-321 GEN
Solar/Wind Harmer
9.2
971573AH1-285 GEN
Solar/Wind Harmer
7.905
962691AG1-118 GEN
Solar/Wind Harmer
27.46
970921AG2-575 GEN
Solar/Wind Harmer
9.117
970921AG2-575 GEN
Solar/Wind Harmer
2.12
971333AH1-146 GEN
Solar/Wind Harmer
18.129
971335AH1-147 GEN
Solar/Wind Harmer
18.129
971341AH1-150 GEN
Solar/Wind Harmer
17.845
971343AH1-151 GEN
Solar/Wind Harmer
17.845
274770LINCOLN ;1U
Adder
5.515
274771LINCOLN ;2U
Adder
5.515
274856ECOGROVE ;U1
Solar/Wind Harmer
2.978
276611AD2-172 GEN
Solar/Wind Harmer
2.26
938861AE1-114 GEN
Solar/Wind Harmer
7.139
274764LEE CO EC;5U
Adder
8.068
274765LEE CO EC;6U
Adder
8.068
274762LEE CO EC;3U
Adder
8.049
274763LEE CO EC;4U
Adder
7.973
276603SUBLETTE C
Solar/Wind Harmer
0.903
972267AH1-718 GEN
Adder
3.533
276741O09 GEN1
Solar/Wind Harmer
3.013
276708O09 GEN2
Solar/Wind Harmer
3.013
274851PROVIDENC;RU
Solar/Wind Harmer
2.375
274849CRESCENT ;1U
Solar/Wind Harmer
1.542
276645AC1-214 GEN1
Solar/Wind Harmer
1.117
276646AC1-214 GEN2
Solar/Wind Harmer
1.117
276782AC1-033 GEN
Solar/Wind Harmer
3.295
990562J1336 G
External Queue
37.6640739440918
990512J1326
External Queue
4.073311805725098
990552J1334 G
External Queue
37.6640739440918
990762J1386
External Queue
13.060995101928711
991332J1785
External Queue
12.545342445373535
990547J1333 G
External Queue
37.6640739440918
990557J1335 G
External Queue
37.6640739440918
990577J1339
External Queue
26.695417404174805
990647J1355
External Queue
44.529808044433594
990582J1340
External Queue
26.695417404174805
990662J1358
External Queue
16.238128662109375
991247J1684 G
External Queue
32.260398864746094
NYPJM->LTFIMP_NY
CLTF
0.863
WECLTFEXP_WEC->PJM
CLTF
3.459
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.298
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.639
AG2-052LTFEXP_AG2-052->PJM
LTF
0.555
AH1-155LTFEXP_AH1-155->PJM
LTF
0.832
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.138
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.38
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.084
MECLTFEXP_MEC->PJM
CLTF
10.891
SIGELTFEXP_SIGE->PJM
CLTF
0.029
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.249
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.654
LAGNLTFEXP_LAGN->PJM
CLTF
3.848
TVALTFEXP_TVA->PJM
CLTF
1.06

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P7-1_#11009___SRT-A-2


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11009___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:116.53 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2145.4
MW Contribution:10.65
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
28.716
957371AF2-031 GEN
50/50
1.422
274752CRETE EC ;2U
50/50
6.976
274753CRETE EC ;3U
50/50
6.976
274806UNIV PK N;2U
50/50
0.374
274815UNIV PK N;XU
50/50
0.368
274816UNIV PK N;YU
50/50
0.367
274810UNIV PK N;6U
50/50
0.366
274826FISK ;BP
50/50
14.253
972231SS25-0005
Solar/Wind Harmer
12.765
972181SS23-001
Solar/Wind Harmer
7.978
274800UNIV PARK;3U
Adder
7.047
972038AH1-567 GEN2
Adder
0.441
274802UNIV PARK;5U
Adder
7.029
970941AG2-585 GEN
Solar/Wind Harmer
14.498
276772AC2-154 GEN
Solar/Wind Harmer
3.234
276806AD2-047 C O1
Solar/Wind Harmer
12.407
276893AG1-478 C
Solar/Wind Harmer
0.452
972228AH1-698 GEN2
Adder
3.969
274676JOLIET 29;8U
Adder
31.695
274730ELWOOD EC;6P
Adder
17.386
274734ELWOOD EC;8P
Adder
17.386
274736ELWOOD EC;9P
Adder
17.386
274729ELWOOD EC;1P
Adder
17.376
276694AA1-018 GEN2
Solar/Wind Harmer
6.598
276805AD2-038 GEN
Solar/Wind Harmer
5.161
276897AD1-100 C
Solar/Wind Harmer
29.122
939351AE1-166 GEN
Solar/Wind Harmer
5.95
274682WAUKEGAN ;7U
Adder
17.404
276889AE2-281 GEN
Solar/Wind Harmer
1.826
943121AE2-341 GEN
Solar/Wind Harmer
13.839
943591AF1-030 GEN
Solar/Wind Harmer
9.226
970571AG2-364 GEN
Solar/Wind Harmer
18.275
274872LEEDK;1U
Solar/Wind Harmer
0.232
970707AG2-453 GEN
Solar/Wind Harmer
25.276
276799AD1-013 GEN
Solar/Wind Harmer
1.983
946671AF1-331 GEN
Solar/Wind Harmer
0.375
274855GSG-6 ;RU
Solar/Wind Harmer
3.31
274850MENDOTA H;RU
Solar/Wind Harmer
2.301
276602WESTBROOK C
Solar/Wind Harmer
1.905
276863AD2-134 GEN
Solar/Wind Harmer
1.601
959091AF2-200 GEN
Solar/Wind Harmer
17.862
274723RIVER EC ;12
50/50
28.77
972179AH1-673 GEN
50/50
14.858
274751CRETE EC ;1U
50/50
6.976
274754CRETE EC ;4U
50/50
6.976
274813UNIV PK N;9U
50/50
0.367
274809UNIV PK N;5U
50/50
0.365
274812UNIV PK N;8U
50/50
6.696
966431AG1-512 GEN
50/50
2.344
276164X3-005 C
Solar/Wind Harmer
0.959
274801UNIV PARK;4U
Adder
7.047
276776AD2-060 GEN
Solar/Wind Harmer
0.49
274676JOLIET 29;8U
Adder
32.869
274674JOLIET 9 ;6U
Adder
16.396
274732ELWOOD EC;7P
Adder
17.386
276691AA1-018 GEN1
Solar/Wind Harmer
0.487
941551AE2-152 GEN
Solar/Wind Harmer
4.551
274682WAUKEGAN ;7U
Adder
17.404
274871GR RIDGE ;2U
Solar/Wind Harmer
7.443
274828WAUKEGAN ;BP
Adder
10.669
276901AD2-066 C O1
Solar/Wind Harmer
3.361
276876AE1-163_GEN2
Solar/Wind Harmer
6.39
274745AC1-111 GEN9
Adder
5.299
970569AG2-363 GEN
Solar/Wind Harmer
27.413
960751AF2-366 GEN
Solar/Wind Harmer
2.618
962781AG1-127 GEN
Solar/Wind Harmer
8.679
274872LEEDK;1U
Solar/Wind Harmer
7.462
971997AH1-543 GEN
Solar/Wind Harmer
14.275
274822ROCKFORD ;11
Adder
17.59
276861AD2-134 GEN
Solar/Wind Harmer
1.601
957471AF2-041 GEN
Solar/Wind Harmer
26.794
959081AF2-199 GEN
Solar/Wind Harmer
8.931
971067AG2-660 GEN
Solar/Wind Harmer
2.077
972235AH1-702 GEN1
Adder
2.247
972207SS24-0001
Solar/Wind Harmer
19.628
274773LINCOLN ;4U
Adder
5.521
274774LINCOLN ;5U
Adder
5.521
970819AG2-516 GEN
Solar/Wind Harmer
10.65
939401AE1-172 GEN
Solar/Wind Harmer
12.339
971475AH1-234 GEN
Solar/Wind Harmer
19.826
274857EASY ROAD;U1
Solar/Wind Harmer
4.15
274761LEE CO EC;2U
Adder
8.057
274766LEE CO EC;7U
Adder
7.962
276158O29GEN2
Solar/Wind Harmer
4.223
274877BISHOP HL;1U
Solar/Wind Harmer
2.791
276726Z2-087_GEN
Solar/Wind Harmer
5.798
939741AE1-205 GEN
Solar/Wind Harmer
10.499
961501AF2-441 GEN
50/50
13.341
274814UNIV PK N;0U
50/50
6.755
274807UNIV PK N;3U
50/50
6.74
274805UNIV PK N;1U
50/50
6.711
274811UNIV PK N;7U
50/50
6.696
274827FISK ;RP
50/50
10.102
972037AH1-567 GEN1
Adder
0.221
960591AF2-350 GEN
Solar/Wind Harmer
11.598
274687WILL CNTY;4U
Adder
30.826
274687WILL CNTY;4U
Adder
30.826
274675JOLIET 29;7U
Adder
32.867
274675JOLIET 29;7U
Adder
31.693
972227AH1-698 GEN1
Adder
2.793
274728ELWOOD EC;5P
Adder
17.386
274731ELWOOD EC;2P
Adder
17.376
274733ELWOOD EC;3P
Adder
17.376
274735ELWOOD EC;4P
Adder
17.376
970833AG2-524 GEN
Solar/Wind Harmer
8.511
970833AG2-524 GEN
Solar/Wind Harmer
3.958
276868AE1-113 GEN
Solar/Wind Harmer
9.763
276882AE2-255 GEN
Solar/Wind Harmer
3.255
274746AC1-111 G10
Adder
5.299
274744AC1-111 GEN8
Adder
5.299
971177AH1-047 GEN
Solar/Wind Harmer
5.389
971411AH1-196 GEN
Solar/Wind Harmer
13.71
971675AH1-338 GEN
Solar/Wind Harmer
16.136
274823ROCKFORD ;21
Adder
17.462
971171AH1-044 GEN
Solar/Wind Harmer
17.862
274775LINCOLN ;6U
Adder
5.521
274776LINCOLN ;7U
Adder
5.521
274777LINCOLN ;8U
Adder
5.521
276612AE2-035 GEN
Solar/Wind Harmer
2.262
971681AH1-341 GEN
Solar/Wind Harmer
13.067
926823AC1-168 GEN
Solar/Wind Harmer
3.747
961011AF2-392 GEN
Solar/Wind Harmer
9.277
274863CRW1-WTG
Solar/Wind Harmer
4.751
274864CRW2-WTG
Solar/Wind Harmer
4.751
957751AF2-069 GEN
Solar/Wind Harmer
0.383
274848CAMPGROVE;RU
Solar/Wind Harmer
5.286
970169AG2-114 GEN
Solar/Wind Harmer
8.151
946321AF1-296 GEN
Solar/Wind Harmer
8.413
276655WTG1_EQ
Solar/Wind Harmer
6.4
276656WTG2_EQ
Solar/Wind Harmer
0.847
960681AF2-359 GEN
Solar/Wind Helper
0.815
941731AE2-173 GEN
Solar/Wind Harmer
3.052
274808UNIV PK N;4U
50/50
6.667
274803UNIV PARK;6U
Adder
7.029
274888KELLY CRK;1U
Solar/Wind Harmer
6.847
274887GEN-1.85
Solar/Wind Harmer
6.182
276843GEN-1.7
Solar/Wind Harmer
0.665
958011AF2-095 GEN
Solar/Wind Harmer
16.701
274674JOLIET 9 ;6U
Adder
16.396
274861TOP CROP ;1U
Solar/Wind Harmer
6.337
274862TOP CROP ;2U
Solar/Wind Harmer
5.291
958481AF2-142 GEN
Solar/Wind Harmer
15.682
958491AF2-143 GEN
Solar/Wind Harmer
15.09
972259AH1-714 GEN
Adder
18.793
972236AH1-702 GEN2
Adder
1.954
274772LINCOLN ;3U
Adder
5.521
274858EASY ROAD;U2
Solar/Wind Harmer
4.15
274760LEE CO EC;1U
Adder
8.057
274767LEE CO EC;8U
Adder
7.962
276157O29GEN1
Solar/Wind Harmer
3.212
274878BISHOP HL;2U
Solar/Wind Harmer
2.791
965931AG1-462 GEN
Solar/Wind Harmer
20.355
274847GR RIDGE ;BU
Solar/Wind Harmer
4.896
274683WAUKEGAN ;8U
Adder
20.354
274683WAUKEGAN ;8U
Adder
17.158
274879MINONK ;1U
Solar/Wind Harmer
6.509
276872AE1-163_GEN1
Solar/Wind Harmer
6.39
274696ROCKY RD ;4P
Adder
10.763
274695ROCKY RD ;2P
Adder
10.515
274693ROCKY RD ;1P
Adder
10.411
274697ROCKY RD ;3P
Adder
2.856
942991AE2-321 GEN
Solar/Wind Harmer
9.209
971573AH1-285 GEN
Solar/Wind Harmer
7.912
962691AG1-118 GEN
Solar/Wind Harmer
27.486
970921AG2-575 GEN
Solar/Wind Harmer
9.126
970921AG2-575 GEN
Solar/Wind Harmer
2.122
971333AH1-146 GEN
Solar/Wind Harmer
18.147
971335AH1-147 GEN
Solar/Wind Harmer
18.147
971341AH1-150 GEN
Solar/Wind Harmer
17.862
971343AH1-151 GEN
Solar/Wind Harmer
17.862
274770LINCOLN ;1U
Adder
5.521
274771LINCOLN ;2U
Adder
5.521
274856ECOGROVE ;U1
Solar/Wind Harmer
2.981
276611AD2-172 GEN
Solar/Wind Harmer
2.262
938861AE1-114 GEN
Solar/Wind Harmer
7.146
274764LEE CO EC;5U
Adder
8.076
274765LEE CO EC;6U
Adder
8.076
274762LEE CO EC;3U
Adder
8.057
274763LEE CO EC;4U
Adder
7.981
276603SUBLETTE C
Solar/Wind Harmer
0.903
972267AH1-718 GEN
Adder
3.537
276741O09 GEN1
Solar/Wind Harmer
3.017
276708O09 GEN2
Solar/Wind Harmer
3.017
274851PROVIDENC;RU
Solar/Wind Harmer
2.377
274849CRESCENT ;1U
Solar/Wind Harmer
1.543
276645AC1-214 GEN1
Solar/Wind Harmer
1.118
276646AC1-214 GEN2
Solar/Wind Harmer
1.118
276782AC1-033 GEN
Solar/Wind Harmer
3.298
990562J1336 G
External Queue
37.6640739440918
990512J1326
External Queue
4.073311805725098
990552J1334 G
External Queue
37.6640739440918
990762J1386
External Queue
13.060995101928711
991332J1785
External Queue
12.545342445373535
990547J1333 G
External Queue
37.6640739440918
990557J1335 G
External Queue
37.6640739440918
990577J1339
External Queue
26.695417404174805
990647J1355
External Queue
44.529808044433594
990582J1340
External Queue
26.695417404174805
990662J1358
External Queue
16.238128662109375
991247J1684 G
External Queue
32.260398864746094
NYPJM->LTFIMP_NY
CLTF
0.857
WECLTFEXP_WEC->PJM
CLTF
3.463
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.292
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.757
AG2-052LTFEXP_AG2-052->PJM
LTF
0.555
AH1-155LTFEXP_AH1-155->PJM
LTF
0.832
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.135
CBM West 1LTFEXP_CBM-W1->PJM
CBM
66.508
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.118
MECLTFEXP_MEC->PJM
CLTF
10.905
SIGELTFEXP_SIGE->PJM
CLTF
0.029
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.244
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.636
LAGNLTFEXP_LAGN->PJM
CLTF
3.866
TVALTFEXP_TVA->PJM
CLTF
1.069

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.12 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:2008.87
MW Contribution:9.79
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
24.885
972179AH1-673 GEN
50/50
12.84
276164X3-005 C
Solar/Wind Harmer
0.819
274801UNIV PARK;4U
Adder
6.047
276776AD2-060 GEN
Solar/Wind Harmer
0.415
274812UNIV PK N;8U
Adder
4.79
274751CRETE EC ;1U
Adder
4.635
274754CRETE EC ;4U
Adder
4.635
274674JOLIET 9 ;6U
Adder
14.509
274676JOLIET 29;8U
Adder
28.61
274732ELWOOD EC;7P
Adder
15.12
276691AA1-018 GEN1
Solar/Wind Harmer
0.415
274745AC1-111 GEN9
Adder
4.955
274682WAUKEGAN ;7U
Adder
15.783
274871GR RIDGE ;2U
Solar/Wind Harmer
6.749
274828WAUKEGAN ;BP
Adder
9.677
960751AF2-366 GEN
Solar/Wind Harmer
2.447
962781AG1-127 GEN
Solar/Wind Harmer
8.111
274872LEEDK;1U
Solar/Wind Harmer
6.973
276901AD2-066 C O1
Solar/Wind Harmer
2.973
276861AD2-134 GEN
Solar/Wind Harmer
1.489
276876AE1-163_GEN2
Solar/Wind Harmer
5.557
941551AE2-152 GEN
Solar/Wind Harmer
3.752
957471AF2-041 GEN
Solar/Wind Harmer
24.78
959081AF2-199 GEN
Solar/Wind Harmer
8.26
971067AG2-660 GEN
Solar/Wind Harmer
1.921
971997AH1-543 GEN
Solar/Wind Harmer
12.986
274822ROCKFORD ;11
Adder
16.175
972235AH1-702 GEN1
Adder
2.067
970819AG2-516 GEN
Solar/Wind Harmer
9.785
971475AH1-234 GEN
Solar/Wind Harmer
18.197
970569AG2-363 GEN
Solar/Wind Harmer
24.043
274857EASY ROAD;U1
Solar/Wind Harmer
3.813
274761LEE CO EC;2U
Adder
7.402
274766LEE CO EC;7U
Adder
7.315
276158O29GEN2
Solar/Wind Harmer
3.855
274877BISHOP HL;1U
Solar/Wind Harmer
2.51
939401AE1-172 GEN
Solar/Wind Harmer
10.332
972207SS24-0001
Solar/Wind Harmer
14.568
274773LINCOLN ;4U
Adder
4.097
961501AF2-441 GEN
50/50
11.515
274827FISK ;RP
50/50
8.583
972037AH1-567 GEN1
Adder
0.182
960591AF2-350 GEN
Solar/Wind Harmer
9.823
274814UNIV PK N;0U
Adder
4.832
274807UNIV PK N;3U
Adder
4.821
274805UNIV PK N;1U
Adder
4.8
274811UNIV PK N;7U
Adder
4.79
274687WILL CNTY;4U
Adder
26.582
274687WILL CNTY;4U
Adder
26.582
274675JOLIET 29;7U
Adder
28.61
274675JOLIET 29;7U
Adder
27.588
274728ELWOOD EC;5P
Adder
15.12
274731ELWOOD EC;2P
Adder
15.116
274733ELWOOD EC;3P
Adder
15.116
274735ELWOOD EC;4P
Adder
15.116
972227AH1-698 GEN1
Adder
2.352
274746AC1-111 G10
Adder
4.955
274744AC1-111 GEN8
Adder
4.955
970833AG2-524 GEN
Solar/Wind Harmer
7.714
970833AG2-524 GEN
Solar/Wind Harmer
3.588
276868AE1-113 GEN
Solar/Wind Harmer
8.577
276882AE2-255 GEN
Solar/Wind Harmer
2.859
971177AH1-047 GEN
Solar/Wind Harmer
4.959
971411AH1-196 GEN
Solar/Wind Harmer
12.602
971675AH1-338 GEN
Solar/Wind Harmer
15.019
971171AH1-044 GEN
Solar/Wind Harmer
16.52
274823ROCKFORD ;21
Adder
16.058
276612AE2-035 GEN
Solar/Wind Harmer
2.079
971681AH1-341 GEN
Solar/Wind Harmer
12.015
961011AF2-392 GEN
Solar/Wind Harmer
8.514
926823AC1-168 GEN
Solar/Wind Harmer
3.364
957751AF2-069 GEN
Solar/Wind Harmer
0.344
946321AF1-296 GEN
Solar/Wind Harmer
7.682
274848CAMPGROVE;RU
Solar/Wind Harmer
4.743
274863CRW1-WTG
Solar/Wind Harmer
4.029
274864CRW2-WTG
Solar/Wind Harmer
4.029
970169AG2-114 GEN
Solar/Wind Harmer
7.185
274775LINCOLN ;6U
Adder
4.097
274776LINCOLN ;7U
Adder
4.097
274777LINCOLN ;8U
Adder
4.097
276655WTG1_EQ
Solar/Wind Harmer
5.587
276656WTG2_EQ
Solar/Wind Harmer
0.74
941731AE2-173 GEN
Solar/Wind Harmer
0.502
274803UNIV PARK;6U
Adder
5.796
274888KELLY CRK;1U
Solar/Wind Harmer
5.8
274887GEN-1.85
Solar/Wind Harmer
5.236
276843GEN-1.7
Solar/Wind Harmer
0.563
958011AF2-095 GEN
Solar/Wind Harmer
14.146
274808UNIV PK N;4U
Adder
4.769
274674JOLIET 9 ;6U
Adder
14.509
972259AH1-714 GEN
Adder
17.081
958481AF2-142 GEN
Solar/Wind Harmer
13.381
274861TOP CROP ;1U
Solar/Wind Harmer
5.388
274862TOP CROP ;2U
Solar/Wind Harmer
4.499
274847GR RIDGE ;BU
Solar/Wind Harmer
4.439
274683WAUKEGAN ;8U
Adder
18.461
274683WAUKEGAN ;8U
Adder
15.562
971573AH1-285 GEN
Solar/Wind Harmer
7.528
274695ROCKY RD ;2P
Adder
9.715
274693ROCKY RD ;1P
Adder
9.619
274697ROCKY RD ;3P
Adder
2.639
274696ROCKY RD ;4P
Adder
9.944
958491AF2-143 GEN
Solar/Wind Harmer
12.974
962691AG1-118 GEN
Solar/Wind Harmer
25.701
970921AG2-575 GEN
Solar/Wind Harmer
8.529
970921AG2-575 GEN
Solar/Wind Harmer
1.983
274879MINONK ;1U
Solar/Wind Harmer
5.719
942991AE2-321 GEN
Solar/Wind Harmer
8.47
971333AH1-146 GEN
Solar/Wind Harmer
16.744
971335AH1-147 GEN
Solar/Wind Harmer
16.744
276872AE1-163_GEN1
Solar/Wind Harmer
5.557
971341AH1-150 GEN
Solar/Wind Harmer
16.52
971343AH1-151 GEN
Solar/Wind Harmer
16.52
274856ECOGROVE ;U1
Solar/Wind Harmer
2.74
276611AD2-172 GEN
Solar/Wind Harmer
2.079
938861AE1-114 GEN
Solar/Wind Harmer
6.567
274764LEE CO EC;5U
Adder
7.419
274765LEE CO EC;6U
Adder
7.419
274762LEE CO EC;3U
Adder
7.402
274763LEE CO EC;4U
Adder
7.332
276603SUBLETTE C
Solar/Wind Harmer
0.83
972267AH1-718 GEN
Adder
3.246
276741O09 GEN1
Solar/Wind Harmer
2.754
276708O09 GEN2
Solar/Wind Harmer
2.754
274851PROVIDENC;RU
Solar/Wind Harmer
2.133
274849CRESCENT ;1U
Solar/Wind Harmer
1.385
276645AC1-214 GEN1
Solar/Wind Harmer
1.003
276646AC1-214 GEN2
Solar/Wind Harmer
1.003
276782AC1-033 GEN
Solar/Wind Harmer
2.966
274770LINCOLN ;1U
Adder
4.097
274771LINCOLN ;2U
Adder
4.097
274724RIVER EC ;11
50/50
24.978
957371AF2-031 GEN
50/50
1.237
274826FISK ;BP
50/50
12.111
274800UNIV PARK;3U
Adder
6.047
972038AH1-567 GEN2
Adder
0.379
274802UNIV PARK;5U
Adder
5.796
276772AC2-154 GEN
Solar/Wind Harmer
2.739
276806AD2-047 C O1
Solar/Wind Harmer
10.508
970941AG2-585 GEN
Solar/Wind Harmer
12.279
972231SS25-0005
Solar/Wind Harmer
9
972181SS23-001
Solar/Wind Harmer
5.625
274752CRETE EC ;2U
Adder
4.635
274753CRETE EC ;3U
Adder
4.635
276893AG1-478 C
Solar/Wind Harmer
0.391
274676JOLIET 29;8U
Adder
27.588
274730ELWOOD EC;6P
Adder
15.12
274734ELWOOD EC;8P
Adder
15.12
274736ELWOOD EC;9P
Adder
15.12
274729ELWOOD EC;1P
Adder
15.116
972228AH1-698 GEN2
Adder
3.343
970707AG2-453 GEN
Solar/Wind Harmer
24.989
276694AA1-018 GEN2
Solar/Wind Harmer
5.63
943121AE2-341 GEN
Solar/Wind Harmer
13.243
943591AF1-030 GEN
Solar/Wind Harmer
8.829
274682WAUKEGAN ;7U
Adder
15.783
276805AD2-038 GEN
Solar/Wind Harmer
4.437
274872LEEDK;1U
Solar/Wind Harmer
0.217
276799AD1-013 GEN
Solar/Wind Harmer
1.846
946671AF1-331 GEN
Solar/Wind Harmer
0.35
274855GSG-6 ;RU
Solar/Wind Harmer
3.08
274850MENDOTA H;RU
Solar/Wind Harmer
2.142
276602WESTBROOK C
Solar/Wind Harmer
1.773
276863AD2-134 GEN
Solar/Wind Harmer
1.489
276897AD1-100 C
Solar/Wind Harmer
24.008
939351AE1-166 GEN
Solar/Wind Harmer
4.905
276889AE2-281 GEN
Solar/Wind Harmer
1.588
959091AF2-200 GEN
Solar/Wind Harmer
16.52
972236AH1-702 GEN2
Adder
1.797
970571AG2-364 GEN
Solar/Wind Harmer
16.028
274858EASY ROAD;U2
Solar/Wind Harmer
3.813
274760LEE CO EC;1U
Adder
7.402
274767LEE CO EC;8U
Adder
7.315
276157O29GEN1
Solar/Wind Harmer
2.932
274878BISHOP HL;2U
Solar/Wind Harmer
2.51
965931AG1-462 GEN
Solar/Wind Harmer
18.575
274772LINCOLN ;3U
Adder
4.097
274774LINCOLN ;5U
Adder
4.097
276726Z2-087_GEN
Solar/Wind Harmer
5.061
939741AE1-205 GEN
Solar/Wind Harmer
1.728
990562J1336 G
External Queue
33.37971496582031
991337J1802
External Queue
9.793804168701172
990552J1334 G
External Queue
33.37971496582031
990762J1386
External Queue
9.419135093688965
991332J1785
External Queue
13.058797836303711
990547J1333 G
External Queue
33.37971496582031
990557J1335 G
External Queue
33.37971496582031
990577J1339
External Queue
21.04810905456543
990647J1355
External Queue
44.93280029296875
990582J1340
External Queue
21.04810905456543
990662J1358
External Queue
15.27561092376709
991247J1684 G
External Queue
27.28211784362793
NYPJM->LTFIMP_NY
CLTF
0.789
WECLTFEXP_WEC->PJM
CLTF
3.148
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.279
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.034
AG2-052LTFEXP_AG2-052->PJM
LTF
0.534
AH1-155LTFEXP_AH1-155->PJM
LTF
0.801
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.131
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.624
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.795
MECLTFEXP_MEC->PJM
CLTF
9.903
SIGELTFEXP_SIGE->PJM
CLTF
0.028
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.222
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.577
LAGNLTFEXP_LAGN->PJM
CLTF
3.486
TVALTFEXP_TVA->PJM
CLTF
0.959

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.24 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1974.3
MW Contribution:8.54
Bus #Bus NameTypeMW Contribution
274724RIVER EC ;11
50/50
24.848
957371AF2-031 GEN
50/50
1.23
274826FISK ;BP
50/50
11.719
274752CRETE EC ;2U
50/50
5.221
274753CRETE EC ;3U
50/50
5.221
972231SS25-0005
Solar/Wind Harmer
9.553
972181SS23-001
Solar/Wind Harmer
5.971
274800UNIV PARK;3U
Adder
5.803
972038AH1-567 GEN2
Adder
0.363
274802UNIV PARK;5U
Adder
5.65
970941AG2-585 GEN
Solar/Wind Harmer
11.843
961501AF2-441 GEN
50/50
11.401
274827FISK ;RP
50/50
8.305
274814UNIV PK N;0U
Adder
4.904
274807UNIV PK N;3U
Adder
4.894
274805UNIV PK N;1U
Adder
4.872
274811UNIV PK N;7U
Adder
4.862
972037AH1-567 GEN1
Adder
0.177
960591AF2-350 GEN
Solar/Wind Harmer
9.475
274687WILL CNTY;4U
Adder
24.874
274687WILL CNTY;4U
Adder
24.874
274675JOLIET 29;7U
Adder
26.39
274675JOLIET 29;7U
Adder
25.448
972227AH1-698 GEN1
Adder
2.231
274728ELWOOD EC;5P
Adder
13.956
274731ELWOOD EC;2P
Adder
13.948
274733ELWOOD EC;3P
Adder
13.948
274735ELWOOD EC;4P
Adder
13.948
970833AG2-524 GEN
Solar/Wind Harmer
6.795
970833AG2-524 GEN
Solar/Wind Harmer
3.16
276868AE1-113 GEN
Solar/Wind Harmer
7.862
276882AE2-255 GEN
Solar/Wind Harmer
2.621
274746AC1-111 G10
Adder
4.23
274744AC1-111 GEN8
Adder
4.23
971177AH1-047 GEN
Solar/Wind Harmer
4.317
971411AH1-196 GEN
Solar/Wind Harmer
10.985
274823ROCKFORD ;21
Adder
14.001
971675AH1-338 GEN
Solar/Wind Harmer
12.917
971171AH1-044 GEN
Solar/Wind Harmer
14.313
274775LINCOLN ;6U
Adder
4.396
274776LINCOLN ;7U
Adder
4.396
274777LINCOLN ;8U
Adder
4.396
276612AE2-035 GEN
Solar/Wind Harmer
1.815
926823AC1-168 GEN
Solar/Wind Harmer
3.02
971681AH1-341 GEN
Solar/Wind Harmer
10.49
274863CRW1-WTG
Solar/Wind Harmer
3.846
274864CRW2-WTG
Solar/Wind Harmer
3.846
961011AF2-392 GEN
Solar/Wind Harmer
7.457
957751AF2-069 GEN
Solar/Wind Harmer
0.31
274848CAMPGROVE;RU
Solar/Wind Harmer
4.279
970169AG2-114 GEN
Solar/Wind Harmer
6.61
946321AF1-296 GEN
Solar/Wind Harmer
6.782
276655WTG1_EQ
Solar/Wind Harmer
5.245
276656WTG2_EQ
Solar/Wind Harmer
0.694
941731AE2-173 GEN
Solar/Wind Harmer
0.471
274723RIVER EC ;12
50/50
24.793
972179AH1-673 GEN
50/50
12.786
274751CRETE EC ;1U
50/50
5.221
274754CRETE EC ;4U
50/50
5.221
276164X3-005 C
Solar/Wind Harmer
0.81
274801UNIV PARK;4U
Adder
5.803
274812UNIV PK N;8U
Adder
4.862
276776AD2-060 GEN
Solar/Wind Harmer
0.401
274674JOLIET 9 ;6U
Adder
13.259
274676JOLIET 29;8U
Adder
26.392
274732ELWOOD EC;7P
Adder
13.956
276691AA1-018 GEN1
Solar/Wind Harmer
0.392
941551AE2-152 GEN
Solar/Wind Harmer
3.655
274682WAUKEGAN ;7U
Adder
13.945
274828WAUKEGAN ;BP
Adder
8.549
274871GR RIDGE ;2U
Solar/Wind Harmer
5.935
276901AD2-066 C O1
Solar/Wind Harmer
2.709
276876AE1-163_GEN2
Solar/Wind Harmer
5.157
274745AC1-111 GEN9
Adder
4.23
970569AG2-363 GEN
Solar/Wind Harmer
22.135
960751AF2-366 GEN
Solar/Wind Harmer
2.093
962781AG1-127 GEN
Solar/Wind Harmer
6.939
971997AH1-543 GEN
Solar/Wind Harmer
11.469
274872LEEDK;1U
Solar/Wind Harmer
5.967
274822ROCKFORD ;11
Adder
14.104
276861AD2-134 GEN
Solar/Wind Harmer
1.281
957471AF2-041 GEN
Solar/Wind Harmer
21.47
959081AF2-199 GEN
Solar/Wind Harmer
7.157
971067AG2-660 GEN
Solar/Wind Harmer
1.664
972235AH1-702 GEN1
Adder
1.802
939401AE1-172 GEN
Solar/Wind Harmer
9.961
970819AG2-516 GEN
Solar/Wind Harmer
8.544
971475AH1-234 GEN
Solar/Wind Harmer
15.907
972207SS24-0001
Solar/Wind Harmer
15.629
274773LINCOLN ;4U
Adder
4.396
274774LINCOLN ;5U
Adder
4.396
274857EASY ROAD;U1
Solar/Wind Harmer
3.333
274761LEE CO EC;2U
Adder
6.471
274766LEE CO EC;7U
Adder
6.394
276158O29GEN2
Solar/Wind Harmer
3.4
274877BISHOP HL;1U
Solar/Wind Harmer
2.257
276726Z2-087_GEN
Solar/Wind Harmer
4.751
939741AE1-205 GEN
Solar/Wind Harmer
1.622
276772AC2-154 GEN
Solar/Wind Harmer
2.642
276806AD2-047 C O1
Solar/Wind Harmer
10.136
276893AG1-478 C
Solar/Wind Harmer
0.366
274676JOLIET 29;8U
Adder
25.45
972228AH1-698 GEN2
Adder
3.17
274730ELWOOD EC;6P
Adder
13.956
274734ELWOOD EC;8P
Adder
13.956
274736ELWOOD EC;9P
Adder
13.956
274729ELWOOD EC;1P
Adder
13.948
276694AA1-018 GEN2
Solar/Wind Harmer
5.317
276805AD2-038 GEN
Solar/Wind Harmer
4.161
276897AD1-100 C
Solar/Wind Harmer
23.39
939351AE1-166 GEN
Solar/Wind Harmer
4.779
274682WAUKEGAN ;7U
Adder
13.945
276889AE2-281 GEN
Solar/Wind Harmer
1.473
970571AG2-364 GEN
Solar/Wind Harmer
14.756
943121AE2-341 GEN
Solar/Wind Harmer
11.02
943591AF1-030 GEN
Solar/Wind Harmer
7.347
274872LEEDK;1U
Solar/Wind Harmer
0.186
276799AD1-013 GEN
Solar/Wind Harmer
1.587
946671AF1-331 GEN
Solar/Wind Harmer
0.301
274855GSG-6 ;RU
Solar/Wind Harmer
2.649
274850MENDOTA H;RU
Solar/Wind Harmer
1.842
276602WESTBROOK C
Solar/Wind Harmer
1.525
276863AD2-134 GEN
Solar/Wind Harmer
1.281
959091AF2-200 GEN
Solar/Wind Harmer
14.313
274808UNIV PK N;4U
Adder
4.841
274803UNIV PARK;6U
Adder
5.65
274888KELLY CRK;1U
Solar/Wind Harmer
5.594
274887GEN-1.85
Solar/Wind Harmer
5.05
276843GEN-1.7
Solar/Wind Harmer
0.543
958011AF2-095 GEN
Solar/Wind Harmer
13.644
274674JOLIET 9 ;6U
Adder
13.259
958481AF2-142 GEN
Solar/Wind Harmer
12.638
274861TOP CROP ;1U
Solar/Wind Harmer
5.1
274862TOP CROP ;2U
Solar/Wind Harmer
4.259
958491AF2-143 GEN
Solar/Wind Harmer
12.168
972259AH1-714 GEN
Adder
14.938
274879MINONK ;1U
Solar/Wind Harmer
5.242
274683WAUKEGAN ;8U
Adder
16.31
274683WAUKEGAN ;8U
Adder
13.748
274847GR RIDGE ;BU
Solar/Wind Harmer
3.904
276872AE1-163_GEN1
Solar/Wind Harmer
5.157
274696ROCKY RD ;4P
Adder
8.608
274695ROCKY RD ;2P
Adder
8.409
274693ROCKY RD ;1P
Adder
8.326
274697ROCKY RD ;3P
Adder
2.284
942991AE2-321 GEN
Solar/Wind Harmer
7.376
971573AH1-285 GEN
Solar/Wind Harmer
6.307
962691AG1-118 GEN
Solar/Wind Harmer
21.97
970921AG2-575 GEN
Solar/Wind Harmer
7.296
970921AG2-575 GEN
Solar/Wind Harmer
1.697
971333AH1-146 GEN
Solar/Wind Harmer
14.536
971335AH1-147 GEN
Solar/Wind Harmer
14.536
971341AH1-150 GEN
Solar/Wind Harmer
14.313
971343AH1-151 GEN
Solar/Wind Harmer
14.313
274770LINCOLN ;1U
Adder
4.396
274771LINCOLN ;2U
Adder
4.396
274856ECOGROVE ;U1
Solar/Wind Harmer
2.392
276611AD2-172 GEN
Solar/Wind Harmer
1.815
938861AE1-114 GEN
Solar/Wind Harmer
5.738
274764LEE CO EC;5U
Adder
6.486
274765LEE CO EC;6U
Adder
6.486
274762LEE CO EC;3U
Adder
6.471
274763LEE CO EC;4U
Adder
6.41
276603SUBLETTE C
Solar/Wind Harmer
0.726
972267AH1-718 GEN
Adder
2.843
276741O09 GEN1
Solar/Wind Harmer
2.429
276708O09 GEN2
Solar/Wind Harmer
2.429
274851PROVIDENC;RU
Solar/Wind Harmer
1.923
274849CRESCENT ;1U
Solar/Wind Harmer
1.248
276645AC1-214 GEN1
Solar/Wind Harmer
0.904
276646AC1-214 GEN2
Solar/Wind Harmer
0.904
276782AC1-033 GEN
Solar/Wind Harmer
2.667
972236AH1-702 GEN2
Adder
1.567
970707AG2-453 GEN
Solar/Wind Harmer
19.957
274772LINCOLN ;3U
Adder
4.396
274858EASY ROAD;U2
Solar/Wind Harmer
3.333
274760LEE CO EC;1U
Adder
6.471
274767LEE CO EC;8U
Adder
6.394
276157O29GEN1
Solar/Wind Harmer
2.586
274878BISHOP HL;2U
Solar/Wind Harmer
2.257
965931AG1-462 GEN
Solar/Wind Harmer
16.418
990562J1336 G
External Queue
34.311134338378906
991337J1802
External Queue
10.868054389953613
990552J1334 G
External Queue
34.311134338378906
990762J1386
External Queue
10.402356147766113
991332J1785
External Queue
14.410825729370117
990547J1333 G
External Queue
34.311134338378906
990557J1335 G
External Queue
34.311134338378906
990577J1339
External Queue
22.734060287475586
990647J1355
External Queue
44.96678161621094
990582J1340
External Queue
22.734060287475586
990662J1358
External Queue
17.02812957763672
991247J1684 G
External Queue
28.594083786010742
NYPJM->LTFIMP_NY
CLTF
0.758
WECLTFEXP_WEC->PJM
CLTF
2.779
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.269
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.007
AG2-052LTFEXP_AG2-052->PJM
LTF
0.533
AH1-155LTFEXP_AH1-155->PJM
LTF
0.799
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
57.616
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.731
MECLTFEXP_MEC->PJM
CLTF
8.864
SIGELTFEXP_SIGE->PJM
CLTF
0.033
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.153
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.365
LAGNLTFEXP_LAGN->PJM
CLTF
3.24
TVALTFEXP_TVA->PJM
CLTF
0.917

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.35 %
Rating:1385.0 MVA
Rating Type:A
MVA to Mitigate:1472.96
MW Contribution:5.56
Bus #Bus NameTypeMW Contribution
274723RIVER EC ;12
50/50
23.648
972179AH1-673 GEN
50/50
12.191
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.454
276776AD2-060 GEN
Solar/Wind Harmer
0.647
274751CRETE EC ;1U
Adder
7.24
274754CRETE EC ;4U
Adder
7.24
274812UNIV PK N;8U
Adder
4.364
274674JOLIET 9 ;6U
Adder
12.404
274676JOLIET 29;8U
Adder
24.584
274732ELWOOD EC;7P
Adder
12.994
276691AA1-018 GEN1
Solar/Wind Harmer
0.662
941551AE2-152 GEN
Solar/Wind Harmer
0
274682WAUKEGAN ;7U
Adder
13.016
274828WAUKEGAN ;BP
Adder
7.98
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.005
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
3.958
970569AG2-363 GEN
Solar/Wind Harmer
14.342
962781AG1-127 GEN
Solar/Wind Harmer
4.529
971997AH1-543 GEN
Solar/Wind Harmer
2.486
274872LEEDK;1U
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
5.693
274774LINCOLN ;5U
Adder
5.693
274822ROCKFORD ;11
Adder
13.162
276861AD2-134 GEN
Solar/Wind Harmer
0.084
957471AF2-041 GEN
Solar/Wind Harmer
13.983
959081AF2-199 GEN
Solar/Wind Harmer
4.661
971067AG2-660 GEN
Solar/Wind Harmer
1.554
939401AE1-172 GEN
Solar/Wind Harmer
3.483
972235AH1-702 GEN1
Adder
1.681
970819AG2-516 GEN
Solar/Wind Harmer
5.561
971475AH1-234 GEN
Solar/Wind Harmer
2.243
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.033
274766LEE CO EC;7U
Adder
5.962
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.146
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
5.426
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
2.813
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.205
276615X2-022 GEN
Solar/Wind Harmer
0.032
274724RIVER EC ;11
50/50
23.754
957371AF2-031 GEN
50/50
1.176
274826FISK ;BP
50/50
10.998
274800UNIV PARK;3U
Adder
5.454
972038AH1-567 GEN2
Adder
0.341
274802UNIV PARK;5U
Adder
5.231
276806AD2-047 C O1
Solar/Wind Harmer
3.512
970941AG2-585 GEN
Solar/Wind Harmer
7.747
274752CRETE EC ;2U
Adder
7.24
274753CRETE EC ;3U
Adder
7.24
276893AG1-478 C
Solar/Wind Harmer
0.226
274676JOLIET 29;8U
Adder
23.706
972228AH1-698 GEN2
Adder
2.946
274730ELWOOD EC;6P
Adder
12.994
274734ELWOOD EC;8P
Adder
12.994
274736ELWOOD EC;9P
Adder
12.994
274729ELWOOD EC;1P
Adder
12.987
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
13.016
276889AE2-281 GEN
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
8.053
943591AF1-030 GEN
Solar/Wind Harmer
5.355
970571AG2-364 GEN
Solar/Wind Harmer
9.561
274872LEEDK;1U
Solar/Wind Harmer
0.174
274772LINCOLN ;3U
Adder
5.693
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.499
274855GSG-6 ;RU
Solar/Wind Harmer
0.172
274850MENDOTA H;RU
Solar/Wind Harmer
0.055
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.084
970707AG2-453 GEN
Solar/Wind Harmer
15.258
959091AF2-200 GEN
Solar/Wind Harmer
9.322
972236AH1-702 GEN2
Adder
1.462
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.033
274767LEE CO EC;8U
Adder
5.962
276157O29GEN1
Solar/Wind Harmer
0.713
274878BISHOP HL;2U
Solar/Wind Harmer
0.146
965931AG1-462 GEN
Solar/Wind Harmer
10.656
942111AE2-223 GEN
Solar/Wind Harmer
1.26
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
11.132
959611AF2-252 GEN
Solar/Wind Harmer
1.237
276686W4-005 GEN3
Solar/Wind Harmer
0
276668AB2-070 GEN1
Solar/Wind Harmer
0.114
971993AH1-541 GEN
Solar/Wind Harmer
1.446
276621W2-048 GEN
Solar/Wind Harmer
0.152
276838X2-022 GEN2
Solar/Wind Harmer
0.169
961501AF2-441 GEN
50/50
10.865
274827FISK ;RP
50/50
7.795
972037AH1-567 GEN1
Adder
0.164
960591AF2-350 GEN
Solar/Wind Harmer
6.198
274814UNIV PK N;0U
Adder
4.402
274807UNIV PK N;3U
Adder
4.392
274805UNIV PK N;1U
Adder
4.373
274811UNIV PK N;7U
Adder
4.364
274687WILL CNTY;4U
Adder
23.197
274687WILL CNTY;4U
Adder
23.197
274675JOLIET 29;7U
Adder
24.583
274675JOLIET 29;7U
Adder
23.705
972227AH1-698 GEN1
Adder
2.073
274728ELWOOD EC;5P
Adder
12.994
274731ELWOOD EC;2P
Adder
12.987
274733ELWOOD EC;3P
Adder
12.987
274735ELWOOD EC;4P
Adder
12.987
970833AG2-524 GEN
Solar/Wind Harmer
5.575
970833AG2-524 GEN
Solar/Wind Harmer
3.717
276868AE1-113 GEN
Solar/Wind Harmer
1.012
276882AE2-255 GEN
Solar/Wind Harmer
0.589
274746AC1-111 G10
Adder
3.958
274744AC1-111 GEN8
Adder
3.958
971177AH1-047 GEN
Solar/Wind Harmer
2.959
971411AH1-196 GEN
Solar/Wind Harmer
7.155
274775LINCOLN ;6U
Adder
5.693
274776LINCOLN ;7U
Adder
5.693
274777LINCOLN ;8U
Adder
5.693
274823ROCKFORD ;21
Adder
13.066
971675AH1-338 GEN
Solar/Wind Harmer
1.824
971171AH1-044 GEN
Solar/Wind Harmer
9.322
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.774
971681AH1-341 GEN
Solar/Wind Harmer
7.326
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.615
957751AF2-069 GEN
Solar/Wind Harmer
0.144
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
4.287
946321AF1-296 GEN
Solar/Wind Harmer
2.364
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.07
941731AE2-173 GEN
Solar/Wind Harmer
3.23
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.114
276848AB2-070 GEN3
Solar/Wind Harmer
0.114
274803UNIV PARK;6U
Adder
5.231
958011AF2-095 GEN
Solar/Wind Harmer
8.925
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.201
274808UNIV PK N;4U
Adder
4.345
274674JOLIET 9 ;6U
Adder
12.404
958481AF2-142 GEN
Solar/Wind Harmer
8.196
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.738
958491AF2-143 GEN
Solar/Wind Harmer
7.889
972259AH1-714 GEN
Adder
13.947
274879MINONK ;1U
Solar/Wind Harmer
0.213
274683WAUKEGAN ;8U
Adder
15.223
274683WAUKEGAN ;8U
Adder
12.832
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274696ROCKY RD ;4P
Adder
8.044
274695ROCKY RD ;2P
Adder
7.858
274693ROCKY RD ;1P
Adder
7.781
274697ROCKY RD ;3P
Adder
2.135
942991AE2-321 GEN
Solar/Wind Harmer
5.365
971573AH1-285 GEN
Solar/Wind Harmer
0.893
962691AG1-118 GEN
Solar/Wind Harmer
14.331
970921AG2-575 GEN
Solar/Wind Harmer
4.759
970921AG2-575 GEN
Solar/Wind Harmer
1.586
971333AH1-146 GEN
Solar/Wind Harmer
9.469
971335AH1-147 GEN
Solar/Wind Harmer
9.469
274770LINCOLN ;1U
Adder
5.693
274771LINCOLN ;2U
Adder
5.693
971341AH1-150 GEN
Solar/Wind Harmer
9.322
971343AH1-151 GEN
Solar/Wind Harmer
9.322
274856ECOGROVE ;U1
Solar/Wind Harmer
0.109
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.58
274764LEE CO EC;5U
Adder
6.048
274765LEE CO EC;6U
Adder
6.048
274762LEE CO EC;3U
Adder
6.033
274763LEE CO EC;4U
Adder
5.977
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
2.65
276741O09 GEN1
Solar/Wind Harmer
0.157
276708O09 GEN2
Solar/Wind Harmer
0.157
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.172
276646AC1-214 GEN2
Solar/Wind Harmer
0.172
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.237
276763AC1-053 GEN1
Solar/Wind Harmer
0
276764AC1-053 GEN2
Solar/Wind Harmer
0
990562J1336 G
External Queue
33.825042724609375
991337J1802
External Queue
10.729607582092285
990552J1334 G
External Queue
33.825042724609375
990762J1386
External Queue
9.490592002868652
991332J1785
External Queue
13.620012283325195
990547J1333 G
External Queue
33.825042724609375
990557J1335 G
External Queue
33.825042724609375
990577J1339
External Queue
21.449987411499023
990647J1355
External Queue
45.918251037597656
990582J1340
External Queue
21.449987411499023
990662J1358
External Queue
15.778422355651855
991247J1684 G
External Queue
27.706777572631836
NYPJM->LTFIMP_NY
CLTF
0.662
WECLTFEXP_WEC->PJM
CLTF
2.592
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.496
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.223
AG2-052LTFEXP_AG2-052->PJM
LTF
0.532
AH1-155LTFEXP_AH1-155->PJM
LTF
0.798
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.102
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.34
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.481
MECLTFEXP_MEC->PJM
CLTF
8.217
SIGELTFEXP_SIGE->PJM
CLTF
0.027
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.154
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.383
LAGNLTFEXP_LAGN->PJM
CLTF
2.975
TVALTFEXP_TVA->PJM
CLTF
0.838

Details for 17STILLWELL-05DUMONT 345.0 kV Ckt 1 line l/o AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STILLWELL-05DUMONT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.5 %
Rating:1841.0 MVA
Rating Type:B
MVA to Mitigate:1868.7
MW Contribution:8.62
Bus #Bus NameTypeMW Contribution
961501AF2-441 GEN
50/50
11.457
274827FISK ;RP
50/50
8.354
274814UNIV PK N;0U
Adder
4.934
274807UNIV PK N;3U
Adder
4.924
274805UNIV PK N;1U
Adder
4.902
274811UNIV PK N;7U
Adder
4.892
972037AH1-567 GEN1
Adder
0.178
960591AF2-350 GEN
Solar/Wind Harmer
9.534
274687WILL CNTY;4U
Adder
25.041
274687WILL CNTY;4U
Adder
25.041
274675JOLIET 29;7U
Adder
26.573
274675JOLIET 29;7U
Adder
25.624
972227AH1-698 GEN1
Adder
2.246
274728ELWOOD EC;5P
Adder
14.054
274731ELWOOD EC;2P
Adder
14.046
274733ELWOOD EC;3P
Adder
14.046
274735ELWOOD EC;4P
Adder
14.046
970833AG2-524 GEN
Solar/Wind Harmer
6.847
970833AG2-524 GEN
Solar/Wind Harmer
3.184
276868AE1-113 GEN
Solar/Wind Harmer
7.922
276882AE2-255 GEN
Solar/Wind Harmer
2.641
274746AC1-111 G10
Adder
4.264
274744AC1-111 GEN8
Adder
4.264
971177AH1-047 GEN
Solar/Wind Harmer
4.352
971411AH1-196 GEN
Solar/Wind Harmer
11.075
274823ROCKFORD ;21
Adder
14.117
971675AH1-338 GEN
Solar/Wind Harmer
13.024
971171AH1-044 GEN
Solar/Wind Harmer
14.432
274775LINCOLN ;6U
Adder
4.433
274776LINCOLN ;7U
Adder
4.433
274777LINCOLN ;8U
Adder
4.433
276612AE2-035 GEN
Solar/Wind Harmer
1.83
926823AC1-168 GEN
Solar/Wind Harmer
3.046
971681AH1-341 GEN
Solar/Wind Harmer
10.58
274863CRW1-WTG
Solar/Wind Harmer
3.879
274864CRW2-WTG
Solar/Wind Harmer
3.879
961011AF2-392 GEN
Solar/Wind Harmer
7.521
957751AF2-069 GEN
Solar/Wind Harmer
0.313
274848CAMPGROVE;RU
Solar/Wind Harmer
4.318
970169AG2-114 GEN
Solar/Wind Harmer
6.669
946321AF1-296 GEN
Solar/Wind Harmer
6.845
276655WTG1_EQ
Solar/Wind Harmer
5.297
276656WTG2_EQ
Solar/Wind Harmer
0.701
941731AE2-173 GEN
Solar/Wind Harmer
0.476
274723RIVER EC ;12
50/50
24.906
972179AH1-673 GEN
50/50
12.845
274751CRETE EC ;1U
50/50
5.252
274754CRETE EC ;4U
50/50
5.252
276164X3-005 C
Solar/Wind Harmer
0.814
274801UNIV PARK;4U
Adder
5.838
274812UNIV PK N;8U
Adder
4.892
276776AD2-060 GEN
Solar/Wind Harmer
0.403
274674JOLIET 9 ;6U
Adder
13.35
274676JOLIET 29;8U
Adder
26.575
274732ELWOOD EC;7P
Adder
14.054
276691AA1-018 GEN1
Solar/Wind Harmer
0.395
941551AE2-152 GEN
Solar/Wind Harmer
3.682
274682WAUKEGAN ;7U
Adder
14.052
274828WAUKEGAN ;BP
Adder
8.615
274871GR RIDGE ;2U
Solar/Wind Harmer
5.981
276901AD2-066 C O1
Solar/Wind Harmer
2.73
276876AE1-163_GEN2
Solar/Wind Harmer
5.197
274745AC1-111 GEN9
Adder
4.264
970569AG2-363 GEN
Solar/Wind Harmer
22.313
960751AF2-366 GEN
Solar/Wind Harmer
2.11
962781AG1-127 GEN
Solar/Wind Harmer
6.995
971997AH1-543 GEN
Solar/Wind Harmer
11.562
274872LEEDK;1U
Solar/Wind Harmer
6.016
274822ROCKFORD ;11
Adder
14.221
276861AD2-134 GEN
Solar/Wind Harmer
1.292
957471AF2-041 GEN
Solar/Wind Harmer
21.648
959081AF2-199 GEN
Solar/Wind Harmer
7.216
971067AG2-660 GEN
Solar/Wind Harmer
1.678
972235AH1-702 GEN1
Adder
1.817
939401AE1-172 GEN
Solar/Wind Harmer
10.044
970819AG2-516 GEN
Solar/Wind Harmer
8.615
971475AH1-234 GEN
Solar/Wind Harmer
16.041
972207SS24-0001
Solar/Wind Harmer
15.761
274773LINCOLN ;4U
Adder
4.433
274774LINCOLN ;5U
Adder
4.433
274857EASY ROAD;U1
Solar/Wind Harmer
3.361
274761LEE CO EC;2U
Adder
6.526
274766LEE CO EC;7U
Adder
6.449
276158O29GEN2
Solar/Wind Harmer
3.43
274877BISHOP HL;1U
Solar/Wind Harmer
2.277
276726Z2-087_GEN
Solar/Wind Harmer
4.798
939741AE1-205 GEN
Solar/Wind Harmer
1.638
274808UNIV PK N;4U
Adder
4.87
274803UNIV PARK;6U
Adder
5.685
274888KELLY CRK;1U
Solar/Wind Harmer
5.629
274887GEN-1.85
Solar/Wind Harmer
5.082
276843GEN-1.7
Solar/Wind Harmer
0.547
958011AF2-095 GEN
Solar/Wind Harmer
13.73
274674JOLIET 9 ;6U
Adder
13.35
958481AF2-142 GEN
Solar/Wind Harmer
12.728
274861TOP CROP ;1U
Solar/Wind Harmer
5.137
274862TOP CROP ;2U
Solar/Wind Harmer
4.289
958491AF2-143 GEN
Solar/Wind Harmer
12.257
972259AH1-714 GEN
Adder
15.051
274879MINONK ;1U
Solar/Wind Harmer
5.282
274683WAUKEGAN ;8U
Adder
16.435
274683WAUKEGAN ;8U
Adder
13.854
274847GR RIDGE ;BU
Solar/Wind Harmer
3.934
276872AE1-163_GEN1
Solar/Wind Harmer
5.197
274696ROCKY RD ;4P
Adder
8.676
274695ROCKY RD ;2P
Adder
8.475
274693ROCKY RD ;1P
Adder
8.392
274697ROCKY RD ;3P
Adder
2.302
942991AE2-321 GEN
Solar/Wind Harmer
7.435
971573AH1-285 GEN
Solar/Wind Harmer
6.358
962691AG1-118 GEN
Solar/Wind Harmer
22.149
970921AG2-575 GEN
Solar/Wind Harmer
7.356
970921AG2-575 GEN
Solar/Wind Harmer
1.711
971333AH1-146 GEN
Solar/Wind Harmer
14.655
971335AH1-147 GEN
Solar/Wind Harmer
14.655
971341AH1-150 GEN
Solar/Wind Harmer
14.432
971343AH1-151 GEN
Solar/Wind Harmer
14.432
274770LINCOLN ;1U
Adder
4.433
274771LINCOLN ;2U
Adder
4.433
274856ECOGROVE ;U1
Solar/Wind Harmer
2.412
276611AD2-172 GEN
Solar/Wind Harmer
1.83
938861AE1-114 GEN
Solar/Wind Harmer
5.786
274764LEE CO EC;5U
Adder
6.541
274765LEE CO EC;6U
Adder
6.541
274762LEE CO EC;3U
Adder
6.526
274763LEE CO EC;4U
Adder
6.465
276603SUBLETTE C
Solar/Wind Harmer
0.732
972267AH1-718 GEN
Adder
2.868
276741O09 GEN1
Solar/Wind Harmer
2.45
276708O09 GEN2
Solar/Wind Harmer
2.45
274851PROVIDENC;RU
Solar/Wind Harmer
1.94
274849CRESCENT ;1U
Solar/Wind Harmer
1.259
276645AC1-214 GEN1
Solar/Wind Harmer
0.912
276646AC1-214 GEN2
Solar/Wind Harmer
0.912
276782AC1-033 GEN
Solar/Wind Harmer
2.691
274724RIVER EC ;11
50/50
24.96
957371AF2-031 GEN
50/50
1.236
274826FISK ;BP
50/50
11.788
274752CRETE EC ;2U
50/50
5.252
274753CRETE EC ;3U
50/50
5.252
972231SS25-0005
Solar/Wind Harmer
9.61
972181SS23-001
Solar/Wind Harmer
6.006
274800UNIV PARK;3U
Adder
5.838
972038AH1-567 GEN2
Adder
0.365
274802UNIV PARK;5U
Adder
5.685
276772AC2-154 GEN
Solar/Wind Harmer
2.659
276806AD2-047 C O1
Solar/Wind Harmer
10.199
970941AG2-585 GEN
Solar/Wind Harmer
11.918
276893AG1-478 C
Solar/Wind Harmer
0.368
274676JOLIET 29;8U
Adder
25.626
972228AH1-698 GEN2
Adder
3.192
274730ELWOOD EC;6P
Adder
14.054
274734ELWOOD EC;8P
Adder
14.054
274736ELWOOD EC;9P
Adder
14.054
274729ELWOOD EC;1P
Adder
14.046
276694AA1-018 GEN2
Solar/Wind Harmer
5.355
276805AD2-038 GEN
Solar/Wind Harmer
4.192
276897AD1-100 C
Solar/Wind Harmer
23.563
939351AE1-166 GEN
Solar/Wind Harmer
4.814
274682WAUKEGAN ;7U
Adder
14.052
276889AE2-281 GEN
Solar/Wind Harmer
1.485
970571AG2-364 GEN
Solar/Wind Harmer
14.876
943121AE2-341 GEN
Solar/Wind Harmer
11.109
943591AF1-030 GEN
Solar/Wind Harmer
7.406
274872LEEDK;1U
Solar/Wind Harmer
0.187
276799AD1-013 GEN
Solar/Wind Harmer
1.601
946671AF1-331 GEN
Solar/Wind Harmer
0.303
274855GSG-6 ;RU
Solar/Wind Harmer
2.671
274850MENDOTA H;RU
Solar/Wind Harmer
1.858
276602WESTBROOK C
Solar/Wind Harmer
1.538
276863AD2-134 GEN
Solar/Wind Harmer
1.292
959091AF2-200 GEN
Solar/Wind Harmer
14.432
972236AH1-702 GEN2
Adder
1.58
970707AG2-453 GEN
Solar/Wind Harmer
20.124
274772LINCOLN ;3U
Adder
4.433
274858EASY ROAD;U2
Solar/Wind Harmer
3.361
274760LEE CO EC;1U
Adder
6.526
274767LEE CO EC;8U
Adder
6.449
276157O29GEN1
Solar/Wind Harmer
2.609
274878BISHOP HL;2U
Solar/Wind Harmer
2.277
965931AG1-462 GEN
Solar/Wind Harmer
16.57
990562J1336 G
External Queue
34.311134338378906
991337J1802
External Queue
10.868054389953613
990552J1334 G
External Queue
34.311134338378906
990762J1386
External Queue
10.402356147766113
991332J1785
External Queue
14.410825729370117
990547J1333 G
External Queue
34.311134338378906
990557J1335 G
External Queue
34.311134338378906
990577J1339
External Queue
22.734060287475586
990647J1355
External Queue
44.96678161621094
990582J1340
External Queue
22.734060287475586
990662J1358
External Queue
17.02812957763672
991247J1684 G
External Queue
28.594083786010742
NYPJM->LTFIMP_NY
CLTF
0.719
WECLTFEXP_WEC->PJM
CLTF
2.802
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.229
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.812
AG2-052LTFEXP_AG2-052->PJM
LTF
0.534
AH1-155LTFEXP_AH1-155->PJM
LTF
0.801
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.488
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.958
MECLTFEXP_MEC->PJM
CLTF
8.964
SIGELTFEXP_SIGE->PJM
CLTF
0.037
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.114
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.245
LAGNLTFEXP_LAGN->PJM
CLTF
3.361
TVALTFEXP_TVA->PJM
CLTF
0.977

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.35 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1373.94
MW Contribution:9.2
Bus #Bus NameTypeMW Contribution
959351AF2-226 GEN
50/50
2.044
274861TOP CROP ;1U
Solar/Wind Harmer
5.326
274862TOP CROP ;2U
Solar/Wind Harmer
4.448
972259AH1-714 GEN
Adder
16.676
274888KELLY CRK;1U
Solar/Wind Harmer
5.045
274887GEN-1.85
Solar/Wind Harmer
4.555
276843GEN-1.7
Solar/Wind Harmer
0.49
958011AF2-095 GEN
Solar/Wind Harmer
12.306
274770LINCOLN ;1U
Adder
5.278
274771LINCOLN ;2U
Adder
5.278
274847GR RIDGE ;BU
Solar/Wind Harmer
4.289
274674JOLIET 9 ;6U
Adder
13.005
274683WAUKEGAN ;8U
Adder
17.39
274683WAUKEGAN ;8U
Adder
14.659
971573AH1-285 GEN
Solar/Wind Harmer
7.086
274696ROCKY RD ;4P
Adder
9.37
274695ROCKY RD ;2P
Adder
9.154
274693ROCKY RD ;1P
Adder
9.064
274697ROCKY RD ;3P
Adder
2.487
274803UNIV PARK;6U
Adder
4.757
958481AF2-142 GEN
Solar/Wind Harmer
12.145
962691AG1-118 GEN
Solar/Wind Harmer
24.178
970921AG2-575 GEN
Solar/Wind Harmer
8.023
970921AG2-575 GEN
Solar/Wind Harmer
1.866
274879MINONK ;1U
Solar/Wind Harmer
5.404
942991AE2-321 GEN
Solar/Wind Harmer
7.973
958491AF2-143 GEN
Solar/Wind Harmer
11.905
971333AH1-146 GEN
Solar/Wind Harmer
15.759
971335AH1-147 GEN
Solar/Wind Harmer
15.759
971341AH1-150 GEN
Solar/Wind Harmer
15.54
971343AH1-151 GEN
Solar/Wind Harmer
15.54
276872AE1-163_GEN1
Solar/Wind Harmer
5.181
274856ECOGROVE ;U1
Solar/Wind Harmer
2.576
276611AD2-172 GEN
Solar/Wind Harmer
1.954
938861AE1-114 GEN
Solar/Wind Harmer
6.171
274808UNIV PK N;4U
Adder
3.739
274764LEE CO EC;5U
Adder
6.97
274765LEE CO EC;6U
Adder
6.97
274762LEE CO EC;3U
Adder
6.954
274763LEE CO EC;4U
Adder
6.889
276603SUBLETTE C
Solar/Wind Harmer
0.78
972267AH1-718 GEN
Adder
3.048
276741O09 GEN1
Solar/Wind Harmer
2.586
276708O09 GEN2
Solar/Wind Harmer
2.586
274851PROVIDENC;RU
Solar/Wind Harmer
2.004
274849CRESCENT ;1U
Solar/Wind Harmer
1.301
276645AC1-214 GEN1
Solar/Wind Harmer
0.943
276646AC1-214 GEN2
Solar/Wind Harmer
0.943
276782AC1-033 GEN
Solar/Wind Harmer
2.785
960611AF2-352 GEN
Solar/Wind Harmer
1.369
972227AH1-698 GEN1
50/50
2.483
274687WILL CNTY;4U
50/50
26.422
274687WILL CNTY;4U
50/50
26.422
274675JOLIET 29;7U
Adder
26.947
274675JOLIET 29;7U
Adder
25.984
274827FISK ;RP
Adder
6.795
274728ELWOOD EC;5P
Adder
14.346
274731ELWOOD EC;2P
Adder
14.332
274733ELWOOD EC;3P
Adder
14.332
274735ELWOOD EC;4P
Adder
14.332
960591AF2-350 GEN
Solar/Wind Harmer
8.546
274775LINCOLN ;6U
Adder
5.278
274776LINCOLN ;7U
Adder
5.278
274777LINCOLN ;8U
Adder
5.278
970833AG2-524 GEN
Solar/Wind Harmer
7.393
970833AG2-524 GEN
Solar/Wind Harmer
3.439
274746AC1-111 G10
Adder
4.666
274744AC1-111 GEN8
Adder
4.666
972037AH1-567 GEN1
Adder
0.149
276868AE1-113 GEN
Solar/Wind Harmer
8.105
276882AE2-255 GEN
Solar/Wind Harmer
2.702
971177AH1-047 GEN
Solar/Wind Harmer
4.668
971411AH1-196 GEN
Solar/Wind Harmer
11.861
971675AH1-338 GEN
Solar/Wind Harmer
14.122
971171AH1-044 GEN
Solar/Wind Harmer
15.54
274823ROCKFORD ;21
Adder
15.103
276612AE2-035 GEN
Solar/Wind Harmer
1.954
971681AH1-341 GEN
Solar/Wind Harmer
11.29
274814UNIV PK N;0U
Adder
3.788
274807UNIV PK N;3U
Adder
3.78
274805UNIV PK N;1U
Adder
3.763
274811UNIV PK N;7U
Adder
3.755
926823AC1-168 GEN
Solar/Wind Harmer
3.184
961011AF2-392 GEN
Solar/Wind Harmer
7.995
274863CRW1-WTG
Solar/Wind Harmer
4.071
274864CRW2-WTG
Solar/Wind Harmer
4.071
957751AF2-069 GEN
Solar/Wind Harmer
0.323
970169AG2-114 GEN
Solar/Wind Harmer
6.987
946321AF1-296 GEN
Solar/Wind Harmer
7.197
274848CAMPGROVE;RU
Solar/Wind Harmer
4.452
276655WTG1_EQ
Solar/Wind Harmer
5.399
276656WTG2_EQ
Solar/Wind Harmer
0.715
959341AF2-225 GEN
Solar/Wind Harmer
9.276
941731AE2-173 GEN
Solar/Wind Harmer
3.595
276785W4-005 GEN1
Solar/Wind Harmer
1.452
276174W4-005 GEN2
Solar/Wind Harmer
1.452
960681AF2-359 GEN
Solar/Wind Helper
2.404
270536AF1-215 GEN2
Solar/Wind Helper
0.855
274751CRETE EC ;1U
50/50
8.987
274754CRETE EC ;4U
50/50
8.987
274655BRAIDWOOD;2U
50/50
6.433
274676JOLIET 29;8U
Adder
26.953
274732ELWOOD EC;7P
Adder
14.346
276776AD2-060 GEN
Solar/Wind Harmer
0.361
972207SS24-0001
Solar/Wind Harmer
18.766
274773LINCOLN ;4U
Adder
5.278
274774LINCOLN ;5U
Adder
5.278
941551AE2-152 GEN
Solar/Wind Harmer
3.856
274871GR RIDGE ;2U
Solar/Wind Harmer
6.521
274674JOLIET 9 ;6U
Adder
13.005
274801UNIV PARK;4U
Adder
4.869
274745AC1-111 GEN9
Adder
4.666
276164X3-005 C
Solar/Wind Harmer
0.585
274682WAUKEGAN ;7U
Adder
14.868
274828WAUKEGAN ;BP
Adder
9.116
276691AA1-018 GEN1
Solar/Wind Harmer
0.377
960751AF2-366 GEN
Solar/Wind Harmer
2.302
962781AG1-127 GEN
Solar/Wind Harmer
7.63
274872LEEDK;1U
Solar/Wind Harmer
6.559
274723RIVER EC ;12
Adder
14.212
276901AD2-066 C O1
Solar/Wind Harmer
2.776
276861AD2-134 GEN
Solar/Wind Harmer
1.401
971997AH1-543 GEN
Solar/Wind Harmer
12.257
957471AF2-041 GEN
Solar/Wind Harmer
23.311
959081AF2-199 GEN
Solar/Wind Harmer
7.77
971067AG2-660 GEN
Solar/Wind Harmer
1.807
274822ROCKFORD ;11
Adder
15.213
276876AE1-163_GEN2
Solar/Wind Harmer
5.181
972235AH1-702 GEN1
Adder
1.944
970819AG2-516 GEN
Solar/Wind Harmer
9.2
971475AH1-234 GEN
Solar/Wind Harmer
17.107
939401AE1-172 GEN
Solar/Wind Harmer
10.603
970569AG2-363 GEN
Solar/Wind Harmer
22.684
274812UNIV PK N;8U
Adder
3.755
274857EASY ROAD;U1
Solar/Wind Harmer
3.582
274761LEE CO EC;2U
Adder
6.954
274766LEE CO EC;7U
Adder
6.872
276158O29GEN2
Solar/Wind Harmer
3.62
274877BISHOP HL;1U
Solar/Wind Harmer
2.357
276726Z2-087_GEN
Solar/Wind Harmer
4.891
939741AE1-205 GEN
Solar/Wind Harmer
12.368
274854TWINGROVE;U2
Solar/Wind Harmer
4.153
972175AH1-670 GEN
Solar/Wind Harmer
7.255
274880W4-005 GEN4
Solar/Wind Harmer
1.452
270055AF2-134 C O1
Solar/Wind Helper
0.57
274752CRETE EC ;2U
50/50
8.987
274753CRETE EC ;3U
50/50
8.987
274654BRAIDWOOD;1U
50/50
6.846
972228AH1-698 GEN2
50/50
3.522
960281AF2-319 GEN
50/50
2.044
972231SS25-0005
Solar/Wind Harmer
16.445
972181SS23-001
Solar/Wind Harmer
10.278
274676JOLIET 29;8U
Adder
25.991
274826FISK ;BP
Adder
9.588
274730ELWOOD EC;6P
Adder
14.346
274734ELWOOD EC;8P
Adder
14.346
274736ELWOOD EC;9P
Adder
14.346
274729ELWOOD EC;1P
Adder
14.332
970707AG2-453 GEN
Solar/Wind Harmer
24.023
276772AC2-154 GEN
Solar/Wind Harmer
2.383
276806AD2-047 C O1
Solar/Wind Harmer
9.142
970941AG2-585 GEN
Solar/Wind Harmer
10.682
274772LINCOLN ;3U
Adder
5.278
276897AD1-100 C
Solar/Wind Harmer
24.675
939351AE1-166 GEN
Solar/Wind Harmer
5.042
276893AG1-478 C
Solar/Wind Harmer
0.355
274800UNIV PARK;3U
Adder
4.869
972038AH1-567 GEN2
Adder
0.305
943121AE2-341 GEN
Solar/Wind Harmer
12.468
943591AF1-030 GEN
Solar/Wind Harmer
8.312
274682WAUKEGAN ;7U
Adder
14.868
274802UNIV PARK;5U
Adder
4.757
276694AA1-018 GEN2
Solar/Wind Harmer
5.11
274872LEEDK;1U
Solar/Wind Harmer
0.204
274724RIVER EC ;11
Adder
14.06
276805AD2-038 GEN
Solar/Wind Harmer
4.071
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
959091AF2-200 GEN
Solar/Wind Harmer
15.54
276889AE2-281 GEN
Solar/Wind Harmer
1.48
972236AH1-702 GEN2
Adder
1.69
970571AG2-364 GEN
Solar/Wind Harmer
15.122
274858EASY ROAD;U2
Solar/Wind Harmer
3.582
274760LEE CO EC;1U
Adder
6.954
274767LEE CO EC;8U
Adder
6.872
276157O29GEN1
Solar/Wind Harmer
2.753
274878BISHOP HL;2U
Solar/Wind Harmer
2.357
965931AG1-462 GEN
Solar/Wind Harmer
17.395
942111AE2-223 GEN
Solar/Wind Harmer
5.07
274853TWINGROVE;U1
Solar/Wind Harmer
4.242
965091AG1-374 GEN
Solar/Wind Harmer
17.657
959611AF2-252 GEN
Solar/Wind Harmer
1.369
276686W4-005 GEN3
Solar/Wind Harmer
1.452
270535AF1-215 GEN1
Solar/Wind Helper
0.855
971993AH1-541 GEN
Solar/Wind Harmer
2.207
990512J1326
External Queue
4.003633975982666
990762J1386
External Queue
5.75543737411499
990577J1339
External Queue
10.205135345458984
990582J1340
External Queue
10.205135345458984
NYPJM->LTFIMP_NY
CLTF
0.687
WECLTFEXP_WEC->PJM
CLTF
2.96
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.658
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.26
AG2-052LTFEXP_AG2-052->PJM
LTF
0.062
AH1-155LTFEXP_AH1-155->PJM
LTF
0.093
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.901
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.142
MECLTFEXP_MEC->PJM
CLTF
9.189
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.319
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.9
LAGNLTFEXP_LAGN->PJM
CLTF
3.039
TVALTFEXP_TVA->PJM
CLTF
0.782

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.35 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1373.94
MW Contribution:9.2
Bus #Bus NameTypeMW Contribution
959351AF2-226 GEN
50/50
2.044
274861TOP CROP ;1U
Solar/Wind Harmer
5.326
274862TOP CROP ;2U
Solar/Wind Harmer
4.448
972259AH1-714 GEN
Adder
16.676
274888KELLY CRK;1U
Solar/Wind Harmer
5.045
274887GEN-1.85
Solar/Wind Harmer
4.555
276843GEN-1.7
Solar/Wind Harmer
0.49
972227AH1-698 GEN1
50/50
2.483
274687WILL CNTY;4U
50/50
26.422
274687WILL CNTY;4U
50/50
26.422
274675JOLIET 29;7U
Adder
26.947
274675JOLIET 29;7U
Adder
25.984
274827FISK ;RP
Adder
6.795
274728ELWOOD EC;5P
Adder
14.346
274731ELWOOD EC;2P
Adder
14.332
274733ELWOOD EC;3P
Adder
14.332
274735ELWOOD EC;4P
Adder
14.332
960591AF2-350 GEN
Solar/Wind Harmer
8.546
274775LINCOLN ;6U
Adder
5.278
274776LINCOLN ;7U
Adder
5.278
274777LINCOLN ;8U
Adder
5.278
970833AG2-524 GEN
Solar/Wind Harmer
7.393
970833AG2-524 GEN
Solar/Wind Harmer
3.439
274746AC1-111 G10
Adder
4.666
274744AC1-111 GEN8
Adder
4.666
972037AH1-567 GEN1
Adder
0.149
276868AE1-113 GEN
Solar/Wind Harmer
8.105
276882AE2-255 GEN
Solar/Wind Harmer
2.702
971177AH1-047 GEN
Solar/Wind Harmer
4.668
971411AH1-196 GEN
Solar/Wind Harmer
11.86
971675AH1-338 GEN
Solar/Wind Harmer
14.122
971171AH1-044 GEN
Solar/Wind Harmer
15.54
274823ROCKFORD ;21
Adder
15.103
276612AE2-035 GEN
Solar/Wind Harmer
1.954
971681AH1-341 GEN
Solar/Wind Harmer
11.29
274814UNIV PK N;0U
Adder
3.788
274807UNIV PK N;3U
Adder
3.78
274805UNIV PK N;1U
Adder
3.763
274811UNIV PK N;7U
Adder
3.755
926823AC1-168 GEN
Solar/Wind Harmer
3.184
961011AF2-392 GEN
Solar/Wind Harmer
7.995
274863CRW1-WTG
Solar/Wind Harmer
4.071
274864CRW2-WTG
Solar/Wind Harmer
4.071
957751AF2-069 GEN
Solar/Wind Harmer
0.323
970169AG2-114 GEN
Solar/Wind Harmer
6.987
946321AF1-296 GEN
Solar/Wind Harmer
7.197
274848CAMPGROVE;RU
Solar/Wind Harmer
4.452
276655WTG1_EQ
Solar/Wind Harmer
5.399
276656WTG2_EQ
Solar/Wind Harmer
0.715
959341AF2-225 GEN
Solar/Wind Harmer
9.276
941731AE2-173 GEN
Solar/Wind Harmer
3.595
276785W4-005 GEN1
Solar/Wind Harmer
1.452
276174W4-005 GEN2
Solar/Wind Harmer
1.452
960681AF2-359 GEN
Solar/Wind Helper
2.404
270536AF1-215 GEN2
Solar/Wind Helper
0.855
274752CRETE EC ;2U
50/50
8.987
274753CRETE EC ;3U
50/50
8.987
274654BRAIDWOOD;1U
50/50
6.846
972228AH1-698 GEN2
50/50
3.522
960281AF2-319 GEN
50/50
2.044
972231SS25-0005
Solar/Wind Harmer
16.445
972181SS23-001
Solar/Wind Harmer
10.278
274676JOLIET 29;8U
Adder
25.99
274826FISK ;BP
Adder
9.588
274730ELWOOD EC;6P
Adder
14.346
274734ELWOOD EC;8P
Adder
14.346
274736ELWOOD EC;9P
Adder
14.346
274729ELWOOD EC;1P
Adder
14.332
970707AG2-453 GEN
Solar/Wind Harmer
24.023
276772AC2-154 GEN
Solar/Wind Harmer
2.383
276806AD2-047 C O1
Solar/Wind Harmer
9.142
970941AG2-585 GEN
Solar/Wind Harmer
10.682
274772LINCOLN ;3U
Adder
5.278
276897AD1-100 C
Solar/Wind Harmer
24.675
939351AE1-166 GEN
Solar/Wind Harmer
5.042
276893AG1-478 C
Solar/Wind Harmer
0.355
274800UNIV PARK;3U
Adder
4.869
972038AH1-567 GEN2
Adder
0.305
943121AE2-341 GEN
Solar/Wind Harmer
12.467
943591AF1-030 GEN
Solar/Wind Harmer
8.312
274682WAUKEGAN ;7U
Adder
14.868
274802UNIV PARK;5U
Adder
4.757
276694AA1-018 GEN2
Solar/Wind Harmer
5.11
274872LEEDK;1U
Solar/Wind Harmer
0.204
274724RIVER EC ;11
Adder
14.06
276805AD2-038 GEN
Solar/Wind Harmer
4.071
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.896
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
959091AF2-200 GEN
Solar/Wind Harmer
15.54
276889AE2-281 GEN
Solar/Wind Harmer
1.48
972236AH1-702 GEN2
Adder
1.69
970571AG2-364 GEN
Solar/Wind Harmer
15.122
274858EASY ROAD;U2
Solar/Wind Harmer
3.582
274760LEE CO EC;1U
Adder
6.954
274767LEE CO EC;8U
Adder
6.872
276157O29GEN1
Solar/Wind Harmer
2.753
274878BISHOP HL;2U
Solar/Wind Harmer
2.357
965931AG1-462 GEN
Solar/Wind Harmer
17.395
942111AE2-223 GEN
Solar/Wind Harmer
5.07
274853TWINGROVE;U1
Solar/Wind Harmer
4.242
965091AG1-374 GEN
Solar/Wind Harmer
17.657
959611AF2-252 GEN
Solar/Wind Harmer
1.369
276686W4-005 GEN3
Solar/Wind Harmer
1.452
270535AF1-215 GEN1
Solar/Wind Helper
0.855
971993AH1-541 GEN
Solar/Wind Harmer
2.207
958011AF2-095 GEN
Solar/Wind Harmer
12.306
274770LINCOLN ;1U
Adder
5.278
274771LINCOLN ;2U
Adder
5.278
274847GR RIDGE ;BU
Solar/Wind Harmer
4.289
274674JOLIET 9 ;6U
Adder
13.005
274683WAUKEGAN ;8U
Adder
17.39
274683WAUKEGAN ;8U
Adder
14.659
971573AH1-285 GEN
Solar/Wind Harmer
7.086
274696ROCKY RD ;4P
Adder
9.37
274695ROCKY RD ;2P
Adder
9.154
274693ROCKY RD ;1P
Adder
9.064
274697ROCKY RD ;3P
Adder
2.487
274803UNIV PARK;6U
Adder
4.757
958481AF2-142 GEN
Solar/Wind Harmer
12.145
962691AG1-118 GEN
Solar/Wind Harmer
24.178
970921AG2-575 GEN
Solar/Wind Harmer
8.023
970921AG2-575 GEN
Solar/Wind Harmer
1.866
274879MINONK ;1U
Solar/Wind Harmer
5.404
942991AE2-321 GEN
Solar/Wind Harmer
7.973
958491AF2-143 GEN
Solar/Wind Harmer
11.905
971333AH1-146 GEN
Solar/Wind Harmer
15.759
971335AH1-147 GEN
Solar/Wind Harmer
15.759
971341AH1-150 GEN
Solar/Wind Harmer
15.54
971343AH1-151 GEN
Solar/Wind Harmer
15.54
276872AE1-163_GEN1
Solar/Wind Harmer
5.181
274856ECOGROVE ;U1
Solar/Wind Harmer
2.576
276611AD2-172 GEN
Solar/Wind Harmer
1.954
938861AE1-114 GEN
Solar/Wind Harmer
6.171
274808UNIV PK N;4U
Adder
3.739
274764LEE CO EC;5U
Adder
6.97
274765LEE CO EC;6U
Adder
6.97
274762LEE CO EC;3U
Adder
6.954
274763LEE CO EC;4U
Adder
6.889
276603SUBLETTE C
Solar/Wind Harmer
0.78
972267AH1-718 GEN
Adder
3.048
276741O09 GEN1
Solar/Wind Harmer
2.586
276708O09 GEN2
Solar/Wind Harmer
2.586
274851PROVIDENC;RU
Solar/Wind Harmer
2.004
274849CRESCENT ;1U
Solar/Wind Harmer
1.301
276645AC1-214 GEN1
Solar/Wind Harmer
0.943
276646AC1-214 GEN2
Solar/Wind Harmer
0.943
276782AC1-033 GEN
Solar/Wind Harmer
2.785
960611AF2-352 GEN
Solar/Wind Harmer
1.369
274751CRETE EC ;1U
50/50
8.987
274754CRETE EC ;4U
50/50
8.987
274655BRAIDWOOD;2U
50/50
6.433
274676JOLIET 29;8U
Adder
26.953
274732ELWOOD EC;7P
Adder
14.346
276776AD2-060 GEN
Solar/Wind Harmer
0.361
972207SS24-0001
Solar/Wind Harmer
18.766
274773LINCOLN ;4U
Adder
5.278
274774LINCOLN ;5U
Adder
5.278
941551AE2-152 GEN
Solar/Wind Harmer
3.856
274871GR RIDGE ;2U
Solar/Wind Harmer
6.521
274674JOLIET 9 ;6U
Adder
13.005
274801UNIV PARK;4U
Adder
4.869
274745AC1-111 GEN9
Adder
4.666
276164X3-005 C
Solar/Wind Harmer
0.585
274682WAUKEGAN ;7U
Adder
14.868
274828WAUKEGAN ;BP
Adder
9.115
276691AA1-018 GEN1
Solar/Wind Harmer
0.377
960751AF2-366 GEN
Solar/Wind Harmer
2.302
962781AG1-127 GEN
Solar/Wind Harmer
7.63
274872LEEDK;1U
Solar/Wind Harmer
6.559
274723RIVER EC ;12
Adder
14.212
276901AD2-066 C O1
Solar/Wind Harmer
2.776
276861AD2-134 GEN
Solar/Wind Harmer
1.401
971997AH1-543 GEN
Solar/Wind Harmer
12.257
957471AF2-041 GEN
Solar/Wind Harmer
23.31
959081AF2-199 GEN
Solar/Wind Harmer
7.77
971067AG2-660 GEN
Solar/Wind Harmer
1.807
274822ROCKFORD ;11
Adder
15.213
276876AE1-163_GEN2
Solar/Wind Harmer
5.181
972235AH1-702 GEN1
Adder
1.944
970819AG2-516 GEN
Solar/Wind Harmer
9.2
971475AH1-234 GEN
Solar/Wind Harmer
17.107
939401AE1-172 GEN
Solar/Wind Harmer
10.603
970569AG2-363 GEN
Solar/Wind Harmer
22.684
274812UNIV PK N;8U
Adder
3.755
274857EASY ROAD;U1
Solar/Wind Harmer
3.582
274761LEE CO EC;2U
Adder
6.954
274766LEE CO EC;7U
Adder
6.872
276158O29GEN2
Solar/Wind Harmer
3.62
274877BISHOP HL;1U
Solar/Wind Harmer
2.357
276726Z2-087_GEN
Solar/Wind Harmer
4.891
939741AE1-205 GEN
Solar/Wind Harmer
12.368
274854TWINGROVE;U2
Solar/Wind Harmer
4.153
972175AH1-670 GEN
Solar/Wind Harmer
7.255
274880W4-005 GEN4
Solar/Wind Harmer
1.452
270055AF2-134 C O1
Solar/Wind Helper
0.57
990512J1326
External Queue
4.003602504730225
990762J1386
External Queue
5.755461692810059
990577J1339
External Queue
10.205183982849121
990582J1340
External Queue
10.205183982849121
NYPJM->LTFIMP_NY
CLTF
0.687
WECLTFEXP_WEC->PJM
CLTF
2.96
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.26
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.658
AG2-052LTFEXP_AG2-052->PJM
LTF
0.062
AH1-155LTFEXP_AH1-155->PJM
LTF
0.093
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.125
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.901
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.142
MECLTFEXP_MEC->PJM
CLTF
9.188
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.319
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.9
LAGNLTFEXP_LAGN->PJM
CLTF
3.039
TVALTFEXP_TVA->PJM
CLTF
0.782

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.08 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1371.09
MW Contribution:9.13
Bus #Bus NameTypeMW Contribution
274751CRETE EC ;1U
50/50
8.921
274754CRETE EC ;4U
50/50
8.921
274655BRAIDWOOD;2U
50/50
6.365
274676JOLIET 29;8U
Adder
26.671
274732ELWOOD EC;7P
Adder
14.2
276776AD2-060 GEN
Solar/Wind Harmer
0.357
972207SS24-0001
Solar/Wind Harmer
18.547
274773LINCOLN ;4U
Adder
5.217
274774LINCOLN ;5U
Adder
5.217
941551AE2-152 GEN
Solar/Wind Harmer
3.817
274871GR RIDGE ;2U
Solar/Wind Harmer
6.458
274674JOLIET 9 ;6U
Adder
12.867
274745AC1-111 GEN9
Adder
4.622
274801UNIV PARK;4U
Adder
4.809
276164X3-005 C
Solar/Wind Harmer
0.576
274682WAUKEGAN ;7U
Adder
14.73
274828WAUKEGAN ;BP
Adder
9.031
276691AA1-018 GEN1
Solar/Wind Harmer
0.373
960751AF2-366 GEN
Solar/Wind Harmer
2.282
962781AG1-127 GEN
Solar/Wind Harmer
7.564
274872LEEDK;1U
Solar/Wind Harmer
6.503
276901AD2-066 C O1
Solar/Wind Harmer
2.753
274723RIVER EC ;12
Adder
13.984
276861AD2-134 GEN
Solar/Wind Harmer
1.389
971997AH1-543 GEN
Solar/Wind Harmer
12.161
957471AF2-041 GEN
Solar/Wind Harmer
23.123
959081AF2-199 GEN
Solar/Wind Harmer
7.708
971067AG2-660 GEN
Solar/Wind Harmer
1.793
274822ROCKFORD ;11
Adder
15.091
276876AE1-163_GEN2
Solar/Wind Harmer
5.14
972235AH1-702 GEN1
Adder
1.928
970819AG2-516 GEN
Solar/Wind Harmer
9.129
971475AH1-234 GEN
Solar/Wind Harmer
16.975
939401AE1-172 GEN
Solar/Wind Harmer
10.522
970569AG2-363 GEN
Solar/Wind Harmer
22.523
274857EASY ROAD;U1
Solar/Wind Harmer
3.556
274761LEE CO EC;2U
Adder
6.904
274766LEE CO EC;7U
Adder
6.822
274812UNIV PK N;8U
Adder
3.697
276158O29GEN2
Solar/Wind Harmer
3.597
274877BISHOP HL;1U
Solar/Wind Harmer
2.344
276726Z2-087_GEN
Solar/Wind Harmer
4.884
939741AE1-205 GEN
Solar/Wind Harmer
12.351
274854TWINGROVE;U2
Solar/Wind Harmer
4.154
972175AH1-670 GEN
Solar/Wind Harmer
7.283
274880W4-005 GEN4
Solar/Wind Harmer
1.464
270055AF2-134 C O1
Solar/Wind Helper
0.567
274752CRETE EC ;2U
50/50
8.921
274753CRETE EC ;3U
50/50
8.921
274654BRAIDWOOD;1U
50/50
6.774
972228AH1-698 GEN2
50/50
3.485
960281AF2-319 GEN
50/50
2.025
972231SS25-0005
Solar/Wind Harmer
16.323
972181SS23-001
Solar/Wind Harmer
10.202
274676JOLIET 29;8U
Adder
25.719
274826FISK ;BP
Adder
9.473
274730ELWOOD EC;6P
Adder
14.2
274734ELWOOD EC;8P
Adder
14.2
274736ELWOOD EC;9P
Adder
14.2
274729ELWOOD EC;1P
Adder
14.186
970707AG2-453 GEN
Solar/Wind Harmer
23.789
276772AC2-154 GEN
Solar/Wind Harmer
2.355
276806AD2-047 C O1
Solar/Wind Harmer
9.035
970941AG2-585 GEN
Solar/Wind Harmer
10.557
274772LINCOLN ;3U
Adder
5.217
276897AD1-100 C
Solar/Wind Harmer
24.421
939351AE1-166 GEN
Solar/Wind Harmer
4.99
276893AG1-478 C
Solar/Wind Harmer
0.351
274800UNIV PARK;3U
Adder
4.809
972038AH1-567 GEN2
Adder
0.301
943121AE2-341 GEN
Solar/Wind Harmer
12.351
943591AF1-030 GEN
Solar/Wind Harmer
8.234
274682WAUKEGAN ;7U
Adder
14.73
274802UNIV PARK;5U
Adder
4.696
276694AA1-018 GEN2
Solar/Wind Harmer
5.059
274872LEEDK;1U
Solar/Wind Harmer
0.203
276805AD2-038 GEN
Solar/Wind Harmer
4.034
274724RIVER EC ;11
Adder
13.834
276799AD1-013 GEN
Solar/Wind Harmer
1.722
946671AF1-331 GEN
Solar/Wind Harmer
0.326
274855GSG-6 ;RU
Solar/Wind Harmer
2.872
274850MENDOTA H;RU
Solar/Wind Harmer
1.997
276602WESTBROOK C
Solar/Wind Harmer
1.653
276863AD2-134 GEN
Solar/Wind Harmer
1.389
959091AF2-200 GEN
Solar/Wind Harmer
15.416
276889AE2-281 GEN
Solar/Wind Harmer
1.469
972236AH1-702 GEN2
Adder
1.677
970571AG2-364 GEN
Solar/Wind Harmer
15.015
274858EASY ROAD;U2
Solar/Wind Harmer
3.556
274760LEE CO EC;1U
Adder
6.904
274767LEE CO EC;8U
Adder
6.822
276157O29GEN1
Solar/Wind Harmer
2.736
274878BISHOP HL;2U
Solar/Wind Harmer
2.344
965931AG1-462 GEN
Solar/Wind Harmer
17.304
942111AE2-223 GEN
Solar/Wind Harmer
5.063
274853TWINGROVE;U1
Solar/Wind Harmer
4.243
965091AG1-374 GEN
Solar/Wind Harmer
17.661
959611AF2-252 GEN
Solar/Wind Harmer
1.369
276686W4-005 GEN3
Solar/Wind Harmer
1.464
270535AF1-215 GEN1
Solar/Wind Helper
0.85
971993AH1-541 GEN
Solar/Wind Harmer
2.224
959351AF2-226 GEN
50/50
2.025
274861TOP CROP ;1U
Solar/Wind Harmer
5.278
274862TOP CROP ;2U
Solar/Wind Harmer
4.407
972259AH1-714 GEN
Adder
16.508
274888KELLY CRK;1U
Solar/Wind Harmer
4.986
274887GEN-1.85
Solar/Wind Harmer
4.502
276843GEN-1.7
Solar/Wind Harmer
0.484
958011AF2-095 GEN
Solar/Wind Harmer
12.162
274770LINCOLN ;1U
Adder
5.217
274771LINCOLN ;2U
Adder
5.217
274847GR RIDGE ;BU
Solar/Wind Harmer
4.248
274674JOLIET 9 ;6U
Adder
12.867
274683WAUKEGAN ;8U
Adder
17.229
274683WAUKEGAN ;8U
Adder
14.523
971573AH1-285 GEN
Solar/Wind Harmer
7.021
274695ROCKY RD ;2P
Adder
9.07
274693ROCKY RD ;1P
Adder
8.981
274697ROCKY RD ;3P
Adder
2.464
274696ROCKY RD ;4P
Adder
9.284
274803UNIV PARK;6U
Adder
4.696
958481AF2-142 GEN
Solar/Wind Harmer
12.025
962691AG1-118 GEN
Solar/Wind Harmer
23.966
970921AG2-575 GEN
Solar/Wind Harmer
7.954
970921AG2-575 GEN
Solar/Wind Harmer
1.85
274879MINONK ;1U
Solar/Wind Harmer
5.359
942991AE2-321 GEN
Solar/Wind Harmer
7.905
958491AF2-143 GEN
Solar/Wind Harmer
11.796
971333AH1-146 GEN
Solar/Wind Harmer
15.628
971335AH1-147 GEN
Solar/Wind Harmer
15.628
971341AH1-150 GEN
Solar/Wind Harmer
15.416
971343AH1-151 GEN
Solar/Wind Harmer
15.416
276872AE1-163_GEN1
Solar/Wind Harmer
5.14
274856ECOGROVE ;U1
Solar/Wind Harmer
2.556
276611AD2-172 GEN
Solar/Wind Harmer
1.939
938861AE1-114 GEN
Solar/Wind Harmer
6.125
274764LEE CO EC;5U
Adder
6.92
274765LEE CO EC;6U
Adder
6.92
274762LEE CO EC;3U
Adder
6.904
274763LEE CO EC;4U
Adder
6.839
276603SUBLETTE C
Solar/Wind Harmer
0.774
274808UNIV PK N;4U
Adder
3.681
972267AH1-718 GEN
Adder
3.027
276741O09 GEN1
Solar/Wind Harmer
2.569
276708O09 GEN2
Solar/Wind Harmer
2.569
274851PROVIDENC;RU
Solar/Wind Harmer
1.993
274849CRESCENT ;1U
Solar/Wind Harmer
1.294
276645AC1-214 GEN1
Solar/Wind Harmer
0.938
276646AC1-214 GEN2
Solar/Wind Harmer
0.938
276782AC1-033 GEN
Solar/Wind Harmer
2.77
960611AF2-352 GEN
Solar/Wind Harmer
1.369
972227AH1-698 GEN1
50/50
2.457
274687WILL CNTY;4U
50/50
26.142
274687WILL CNTY;4U
50/50
26.142
274675JOLIET 29;7U
Adder
26.665
274675JOLIET 29;7U
Adder
25.713
274827FISK ;RP
Adder
6.714
274728ELWOOD EC;5P
Adder
14.2
274731ELWOOD EC;2P
Adder
14.186
274733ELWOOD EC;3P
Adder
14.186
274735ELWOOD EC;4P
Adder
14.186
960591AF2-350 GEN
Solar/Wind Harmer
8.446
274775LINCOLN ;6U
Adder
5.217
274776LINCOLN ;7U
Adder
5.217
274777LINCOLN ;8U
Adder
5.217
970833AG2-524 GEN
Solar/Wind Harmer
7.322
970833AG2-524 GEN
Solar/Wind Harmer
3.406
274746AC1-111 G10
Adder
4.622
274744AC1-111 GEN8
Adder
4.622
972037AH1-567 GEN1
Adder
0.147
276868AE1-113 GEN
Solar/Wind Harmer
8.037
276882AE2-255 GEN
Solar/Wind Harmer
2.679
971177AH1-047 GEN
Solar/Wind Harmer
4.628
971411AH1-196 GEN
Solar/Wind Harmer
11.761
971675AH1-338 GEN
Solar/Wind Harmer
14.006
971171AH1-044 GEN
Solar/Wind Harmer
15.416
274823ROCKFORD ;21
Adder
14.982
276612AE2-035 GEN
Solar/Wind Harmer
1.939
971681AH1-341 GEN
Solar/Wind Harmer
11.207
274814UNIV PK N;0U
Adder
3.73
274807UNIV PK N;3U
Adder
3.722
274805UNIV PK N;1U
Adder
3.705
274811UNIV PK N;7U
Adder
3.697
926823AC1-168 GEN
Solar/Wind Harmer
3.163
961011AF2-392 GEN
Solar/Wind Harmer
7.94
274863CRW1-WTG
Solar/Wind Harmer
4.045
274864CRW2-WTG
Solar/Wind Harmer
4.045
957751AF2-069 GEN
Solar/Wind Harmer
0.321
970169AG2-114 GEN
Solar/Wind Harmer
6.951
274848CAMPGROVE;RU
Solar/Wind Harmer
4.43
946321AF1-296 GEN
Solar/Wind Harmer
7.158
276655WTG1_EQ
Solar/Wind Harmer
5.392
276656WTG2_EQ
Solar/Wind Harmer
0.714
959341AF2-225 GEN
Solar/Wind Harmer
9.263
941731AE2-173 GEN
Solar/Wind Harmer
3.59
276785W4-005 GEN1
Solar/Wind Harmer
1.464
276174W4-005 GEN2
Solar/Wind Harmer
1.464
960681AF2-359 GEN
Solar/Wind Helper
2.441
270536AF1-215 GEN2
Solar/Wind Helper
0.85
990512J1326
External Queue
3.9728879928588867
990762J1386
External Queue
5.6209282875061035
990577J1339
External Queue
9.971273422241211
990582J1340
External Queue
9.971273422241211
NYPJM->LTFIMP_NY
CLTF
0.687
WECLTFEXP_WEC->PJM
CLTF
2.936
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.929
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.224
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.101
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.74
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.521
MECLTFEXP_MEC->PJM
CLTF
9.187
SIGELTFEXP_SIGE->PJM
CLTF
0.018
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.2
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.537
LAGNLTFEXP_LAGN->PJM
CLTF
3.186
TVALTFEXP_TVA->PJM
CLTF
0.868

Details for 17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


Base Case Flowgate

Area:AEP/NIPS
Facility Description:
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.39 %
Rating:1046.0 MVA
Rating Type:B
MVA to Mitigate:1363.91
MW Contribution:9.15
Bus #Bus NameTypeMW Contribution
274751CRETE EC ;1U
50/50
8.957
274754CRETE EC ;4U
50/50
8.957
274655BRAIDWOOD;2U
50/50
6.395
274676JOLIET 29;8U
Adder
26.795
274732ELWOOD EC;7P
Adder
14.262
276776AD2-060 GEN
Solar/Wind Harmer
0.359
972207SS24-0001
Solar/Wind Harmer
18.636
274773LINCOLN ;4U
Adder
5.242
274774LINCOLN ;5U
Adder
5.242
941551AE2-152 GEN
Solar/Wind Harmer
3.832
274871GR RIDGE ;2U
Solar/Wind Harmer
6.483
274674JOLIET 9 ;6U
Adder
12.926
274745AC1-111 GEN9
Adder
4.639
274801UNIV PARK;4U
Adder
4.837
276164X3-005 C
Solar/Wind Harmer
0.581
274682WAUKEGAN ;7U
Adder
14.782
274828WAUKEGAN ;BP
Adder
9.063
276691AA1-018 GEN1
Solar/Wind Harmer
0.375
960751AF2-366 GEN
Solar/Wind Harmer
2.289
962781AG1-127 GEN
Solar/Wind Harmer
7.586
274872LEEDK;1U
Solar/Wind Harmer
6.522
274723RIVER EC ;12
Adder
14.104
276901AD2-066 C O1
Solar/Wind Harmer
2.76
276861AD2-134 GEN
Solar/Wind Harmer
1.393
971997AH1-543 GEN
Solar/Wind Harmer
12.186
957471AF2-041 GEN
Solar/Wind Harmer
23.177
959081AF2-199 GEN
Solar/Wind Harmer
7.726
971067AG2-660 GEN
Solar/Wind Harmer
1.797
274822ROCKFORD ;11
Adder
15.126
276876AE1-163_GEN2
Solar/Wind Harmer
5.151
972235AH1-702 GEN1
Adder
1.933
970819AG2-516 GEN
Solar/Wind Harmer
9.147
971475AH1-234 GEN
Solar/Wind Harmer
17.008
939401AE1-172 GEN
Solar/Wind Harmer
10.536
970569AG2-363 GEN
Solar/Wind Harmer
22.55
274812UNIV PK N;8U
Adder
3.727
274857EASY ROAD;U1
Solar/Wind Harmer
3.561
274761LEE CO EC;2U
Adder
6.914
274766LEE CO EC;7U
Adder
6.833
276158O29GEN2
Solar/Wind Harmer
3.599
274877BISHOP HL;1U
Solar/Wind Harmer
2.343
276726Z2-087_GEN
Solar/Wind Harmer
4.861
939741AE1-205 GEN
Solar/Wind Harmer
12.292
274854TWINGROVE;U2
Solar/Wind Harmer
4.128
972175AH1-670 GEN
Solar/Wind Harmer
7.21
274880W4-005 GEN4
Solar/Wind Harmer
1.443
270055AF2-134 C O1
Solar/Wind Helper
0.576
972227AH1-698 GEN1
50/50
2.468
274687WILL CNTY;4U
50/50
26.267
274687WILL CNTY;4U
50/50
26.267
274675JOLIET 29;7U
Adder
26.789
274675JOLIET 29;7U
Adder
25.832
274827FISK ;RP
Adder
6.753
274728ELWOOD EC;5P
Adder
14.262
274731ELWOOD EC;2P
Adder
14.248
274733ELWOOD EC;3P
Adder
14.248
274735ELWOOD EC;4P
Adder
14.248
960591AF2-350 GEN
Solar/Wind Harmer
8.491
274775LINCOLN ;6U
Adder
5.242
274776LINCOLN ;7U
Adder
5.242
274777LINCOLN ;8U
Adder
5.242
970833AG2-524 GEN
Solar/Wind Harmer
7.35
970833AG2-524 GEN
Solar/Wind Harmer
3.419
274746AC1-111 G10
Adder
4.639
274744AC1-111 GEN8
Adder
4.639
972037AH1-567 GEN1
Adder
0.148
276868AE1-113 GEN
Solar/Wind Harmer
8.058
276882AE2-255 GEN
Solar/Wind Harmer
2.686
971177AH1-047 GEN
Solar/Wind Harmer
4.641
971411AH1-196 GEN
Solar/Wind Harmer
11.792
971675AH1-338 GEN
Solar/Wind Harmer
14.041
971171AH1-044 GEN
Solar/Wind Harmer
15.451
274823ROCKFORD ;21
Adder
15.016
276612AE2-035 GEN
Solar/Wind Harmer
1.943
971681AH1-341 GEN
Solar/Wind Harmer
11.225
274814UNIV PK N;0U
Adder
3.76
274807UNIV PK N;3U
Adder
3.751
274805UNIV PK N;1U
Adder
3.735
274811UNIV PK N;7U
Adder
3.727
926823AC1-168 GEN
Solar/Wind Harmer
3.165
961011AF2-392 GEN
Solar/Wind Harmer
7.948
274863CRW1-WTG
Solar/Wind Harmer
4.045
274864CRW2-WTG
Solar/Wind Harmer
4.045
957751AF2-069 GEN
Solar/Wind Harmer
0.321
970169AG2-114 GEN
Solar/Wind Harmer
6.944
946321AF1-296 GEN
Solar/Wind Harmer
7.155
274848CAMPGROVE;RU
Solar/Wind Harmer
4.426
276655WTG1_EQ
Solar/Wind Harmer
5.366
276656WTG2_EQ
Solar/Wind Harmer
0.71
959341AF2-225 GEN
Solar/Wind Harmer
9.219
941731AE2-173 GEN
Solar/Wind Harmer
3.573
276785W4-005 GEN1
Solar/Wind Harmer
1.443
276174W4-005 GEN2
Solar/Wind Harmer
1.443
960681AF2-359 GEN
Solar/Wind Helper
2.416
270536AF1-215 GEN2
Solar/Wind Helper
0.863
959351AF2-226 GEN
50/50
2.032
274861TOP CROP ;1U
Solar/Wind Harmer
5.296
274862TOP CROP ;2U
Solar/Wind Harmer
4.422
972259AH1-714 GEN
Adder
16.58
274888KELLY CRK;1U
Solar/Wind Harmer
5.013
274887GEN-1.85
Solar/Wind Harmer
4.526
276843GEN-1.7
Solar/Wind Harmer
0.487
958011AF2-095 GEN
Solar/Wind Harmer
12.227
274770LINCOLN ;1U
Adder
5.242
274771LINCOLN ;2U
Adder
5.242
274847GR RIDGE ;BU
Solar/Wind Harmer
4.264
274674JOLIET 9 ;6U
Adder
12.926
274683WAUKEGAN ;8U
Adder
17.289
274683WAUKEGAN ;8U
Adder
14.574
971573AH1-285 GEN
Solar/Wind Harmer
7.046
274696ROCKY RD ;4P
Adder
9.316
274695ROCKY RD ;2P
Adder
9.102
274693ROCKY RD ;1P
Adder
9.012
274697ROCKY RD ;3P
Adder
2.472
274803UNIV PARK;6U
Adder
4.725
958481AF2-142 GEN
Solar/Wind Harmer
12.071
962691AG1-118 GEN
Solar/Wind Harmer
24.04
970921AG2-575 GEN
Solar/Wind Harmer
7.977
970921AG2-575 GEN
Solar/Wind Harmer
1.855
274879MINONK ;1U
Solar/Wind Harmer
5.372
942991AE2-321 GEN
Solar/Wind Harmer
7.928
958491AF2-143 GEN
Solar/Wind Harmer
11.832
971333AH1-146 GEN
Solar/Wind Harmer
15.668
971335AH1-147 GEN
Solar/Wind Harmer
15.668
971341AH1-150 GEN
Solar/Wind Harmer
15.451
971343AH1-151 GEN
Solar/Wind Harmer
15.451
276872AE1-163_GEN1
Solar/Wind Harmer
5.151
274856ECOGROVE ;U1
Solar/Wind Harmer
2.561
276611AD2-172 GEN
Solar/Wind Harmer
1.943
938861AE1-114 GEN
Solar/Wind Harmer
6.135
274808UNIV PK N;4U
Adder
3.711
274764LEE CO EC;5U
Adder
6.93
274765LEE CO EC;6U
Adder
6.93
274762LEE CO EC;3U
Adder
6.914
274763LEE CO EC;4U
Adder
6.849
276603SUBLETTE C
Solar/Wind Harmer
0.776
972267AH1-718 GEN
Adder
3.03
276741O09 GEN1
Solar/Wind Harmer
2.571
276708O09 GEN2
Solar/Wind Harmer
2.571
274851PROVIDENC;RU
Solar/Wind Harmer
1.992
274849CRESCENT ;1U
Solar/Wind Harmer
1.294
276645AC1-214 GEN1
Solar/Wind Harmer
0.937
276646AC1-214 GEN2
Solar/Wind Harmer
0.937
276782AC1-033 GEN
Solar/Wind Harmer
2.769
960611AF2-352 GEN
Solar/Wind Harmer
1.36
274752CRETE EC ;2U
50/50
8.957
274753CRETE EC ;3U
50/50
8.957
274654BRAIDWOOD;1U
50/50
6.805
972228AH1-698 GEN2
50/50
3.501
960281AF2-319 GEN
50/50
2.032
972231SS25-0005
Solar/Wind Harmer
16.389
972181SS23-001
Solar/Wind Harmer
10.243
274676JOLIET 29;8U
Adder
25.838
274826FISK ;BP
Adder
9.528
274730ELWOOD EC;6P
Adder
14.262
274734ELWOOD EC;8P
Adder
14.262
274736ELWOOD EC;9P
Adder
14.262
274729ELWOOD EC;1P
Adder
14.248
970707AG2-453 GEN
Solar/Wind Harmer
23.889
276772AC2-154 GEN
Solar/Wind Harmer
2.368
276806AD2-047 C O1
Solar/Wind Harmer
9.084
970941AG2-585 GEN
Solar/Wind Harmer
10.614
274772LINCOLN ;3U
Adder
5.242
276897AD1-100 C
Solar/Wind Harmer
24.521
939351AE1-166 GEN
Solar/Wind Harmer
5.01
276893AG1-478 C
Solar/Wind Harmer
0.352
274800UNIV PARK;3U
Adder
4.837
972038AH1-567 GEN2
Adder
0.303
943121AE2-341 GEN
Solar/Wind Harmer
12.397
943591AF1-030 GEN
Solar/Wind Harmer
8.265
274682WAUKEGAN ;7U
Adder
14.782
274802UNIV PARK;5U
Adder
4.725
276694AA1-018 GEN2
Solar/Wind Harmer
5.078
274872LEEDK;1U
Solar/Wind Harmer
0.203
276805AD2-038 GEN
Solar/Wind Harmer
4.047
274724RIVER EC ;11
Adder
13.953
276799AD1-013 GEN
Solar/Wind Harmer
1.726
946671AF1-331 GEN
Solar/Wind Harmer
0.327
274855GSG-6 ;RU
Solar/Wind Harmer
2.879
274850MENDOTA H;RU
Solar/Wind Harmer
2.002
276602WESTBROOK C
Solar/Wind Harmer
1.657
276863AD2-134 GEN
Solar/Wind Harmer
1.393
959091AF2-200 GEN
Solar/Wind Harmer
15.451
276889AE2-281 GEN
Solar/Wind Harmer
1.472
972236AH1-702 GEN2
Adder
1.681
970571AG2-364 GEN
Solar/Wind Harmer
15.034
274858EASY ROAD;U2
Solar/Wind Harmer
3.561
274760LEE CO EC;1U
Adder
6.914
274767LEE CO EC;8U
Adder
6.833
276157O29GEN1
Solar/Wind Harmer
2.737
274878BISHOP HL;2U
Solar/Wind Harmer
2.343
965931AG1-462 GEN
Solar/Wind Harmer
17.294
942111AE2-223 GEN
Solar/Wind Harmer
5.038
274853TWINGROVE;U1
Solar/Wind Harmer
4.216
965091AG1-374 GEN
Solar/Wind Harmer
17.548
959611AF2-252 GEN
Solar/Wind Harmer
1.36
276686W4-005 GEN3
Solar/Wind Harmer
1.443
270535AF1-215 GEN1
Solar/Wind Helper
0.863
971993AH1-541 GEN
Solar/Wind Harmer
2.193
990512J1326
External Queue
3.9884557723999023
990762J1386
External Queue
5.717142105102539
990577J1339
External Queue
10.134504318237305
990582J1340
External Queue
10.134504318237305
NYPJM->LTFIMP_NY
CLTF
0.682
WECLTFEXP_WEC->PJM
CLTF
2.943
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.256
AG2-052LTFEXP_AG2-052->PJM
LTF
0.06
AH1-155LTFEXP_AH1-155->PJM
LTF
0.09
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.54
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.123
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.442
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.138
MECLTFEXP_MEC->PJM
CLTF
9.135
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.315
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.888
LAGNLTFEXP_LAGN->PJM
CLTF
3.024
TVALTFEXP_TVA->PJM
CLTF
0.779

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.0 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1798.48
MW Contribution:7.7
Bus #Bus NameTypeMW Contribution
274650KINCAID ;1U
50/50
4.546
274651KINCAID ;2U
50/50
4.544
276916AD2-100_GEN
Solar/Wind Harmer
28.302
276911AD2-131_GEN
Solar/Wind Harmer
5.72
957381AF2-032 GEN
Solar/Wind Harmer
0.539
276763AC1-053 GEN1
Solar/Wind Harmer
4.379
276764AC1-053 GEN2
Solar/Wind Harmer
4.379
960611AF2-352 GEN
Solar/Wind Harmer
2.157
276782AC1-033 GEN
Solar/Wind Harmer
2.957
274851PROVIDENC;RU
Solar/Wind Harmer
2.098
274849CRESCENT ;1U
Solar/Wind Harmer
1.362
276645AC1-214 GEN1
Solar/Wind Harmer
0.987
276646AC1-214 GEN2
Solar/Wind Harmer
0.987
276741O09 GEN1
Solar/Wind Harmer
2.486
276708O09 GEN2
Solar/Wind Harmer
2.486
972267AH1-718 GEN
Adder
2.823
276603SUBLETTE C
Solar/Wind Harmer
0.701
276872AE1-163_GEN1
Solar/Wind Harmer
4.457
274764LEE CO EC;5U
Adder
6.174
274765LEE CO EC;6U
Adder
6.174
274762LEE CO EC;3U
Adder
6.159
274763LEE CO EC;4U
Adder
6.101
938861AE1-114 GEN
Solar/Wind Harmer
5.389
274856ECOGROVE ;U1
Solar/Wind Harmer
2.178
276611AD2-172 GEN
Solar/Wind Harmer
1.653
274879MINONK ;1U
Solar/Wind Harmer
4.305
971341AH1-150 GEN
Solar/Wind Harmer
12.705
971343AH1-151 GEN
Solar/Wind Harmer
12.705
971333AH1-146 GEN
Solar/Wind Harmer
12.457
971335AH1-147 GEN
Solar/Wind Harmer
12.457
958491AF2-143 GEN
Solar/Wind Harmer
9.32
942991AE2-321 GEN
Solar/Wind Harmer
6.138
970921AG2-575 GEN
Solar/Wind Harmer
6.099
970921AG2-575 GEN
Solar/Wind Harmer
1.418
962691AG1-118 GEN
Solar/Wind Harmer
18.197
274696ROCKY RD ;4P
Adder
6.744
274695ROCKY RD ;2P
Adder
6.588
274693ROCKY RD ;1P
Adder
6.523
274697ROCKY RD ;3P
Adder
1.79
274861TOP CROP ;1U
Solar/Wind Harmer
3.581
274862TOP CROP ;2U
Solar/Wind Harmer
2.99
958481AF2-142 GEN
Solar/Wind Harmer
8.863
274683WAUKEGAN ;8U
Adder
12.387
274683WAUKEGAN ;8U
Adder
10.442
972259AH1-714 GEN
Adder
10.527
274674JOLIET 9 ;6U
Adder
8.485
274770LINCOLN ;1U
Adder
4.589
274771LINCOLN ;2U
Adder
4.589
274803UNIV PARK;6U
Adder
2.888
274808UNIV PK N;4U
Adder
2.241
971573AH1-285 GEN
Solar/Wind Harmer
2.867
965911AG1-460 GEN
Solar/Wind Harmer
1.82
276615X2-022 GEN
Solar/Wind Harmer
2.264
963831AG1-236 GEN
Solar/Wind Harmer
10.893
274880W4-005 GEN4
Solar/Wind Harmer
3.311
972175AH1-670 GEN
Solar/Wind Harmer
13.884
274854TWINGROVE;U2
Solar/Wind Harmer
6.546
276726Z2-087_GEN
Solar/Wind Harmer
6.809
939741AE1-205 GEN
Solar/Wind Harmer
17.219
274877BISHOP HL;1U
Solar/Wind Harmer
2.503
276158O29GEN2
Solar/Wind Harmer
3.481
970569AG2-363 GEN
Solar/Wind Harmer
20.775
939401AE1-172 GEN
Solar/Wind Harmer
9.519
276876AE1-163_GEN2
Solar/Wind Harmer
4.457
274857EASY ROAD;U1
Solar/Wind Harmer
3.172
274761LEE CO EC;2U
Adder
6.159
274766LEE CO EC;7U
Adder
6.086
971997AH1-543 GEN
Solar/Wind Harmer
10.388
971475AH1-234 GEN
Solar/Wind Harmer
14.381
970819AG2-516 GEN
Solar/Wind Harmer
7.695
972235AH1-702 GEN1
Adder
1.608
276901AD2-066 C O1
Solar/Wind Harmer
2.233
957471AF2-041 GEN
Solar/Wind Harmer
19.057
959081AF2-199 GEN
Solar/Wind Harmer
6.352
971067AG2-660 GEN
Solar/Wind Harmer
1.477
274822ROCKFORD ;11
Adder
12.436
276861AD2-134 GEN
Solar/Wind Harmer
1.122
274872LEEDK;1U
Solar/Wind Harmer
5.041
960751AF2-366 GEN
Solar/Wind Harmer
1.75
962781AG1-127 GEN
Solar/Wind Harmer
5.8
276691AA1-018 GEN1
Solar/Wind Harmer
0.275
274828WAUKEGAN ;BP
Adder
6.493
274682WAUKEGAN ;7U
Adder
10.534
274745AC1-111 GEN9
Adder
3.243
274732ELWOOD EC;7P
Adder
9.099
274674JOLIET 9 ;6U
Adder
8.485
274773LINCOLN ;4U
Adder
4.589
274774LINCOLN ;5U
Adder
4.589
274676JOLIET 29;8U
Adder
16.603
274801UNIV PARK;4U
Adder
2.967
274812UNIV PK N;8U
Adder
2.251
274723RIVER EC ;12
Adder
7.751
944221AF1-090 GEN
Solar/Wind Harmer
16.351
276785W4-005 GEN1
Solar/Wind Harmer
3.311
276174W4-005 GEN2
Solar/Wind Harmer
3.311
276849AB2-070 GEN2
Solar/Wind Harmer
2.44
276848AB2-070 GEN3
Solar/Wind Harmer
2.44
276655WTG1_EQ
Solar/Wind Harmer
7.517
276656WTG2_EQ
Solar/Wind Harmer
0.995
959341AF2-225 GEN
Solar/Wind Harmer
12.914
941731AE2-173 GEN
Solar/Wind Harmer
5.005
970169AG2-114 GEN
Solar/Wind Harmer
7.644
274848CAMPGROVE;RU
Solar/Wind Harmer
4.886
957751AF2-069 GEN
Solar/Wind Harmer
0.338
274863CRW1-WTG
Solar/Wind Harmer
4.045
274864CRW2-WTG
Solar/Wind Harmer
4.045
946321AF1-296 GEN
Solar/Wind Harmer
7.476
926823AC1-168 GEN
Solar/Wind Harmer
3.008
961011AF2-392 GEN
Solar/Wind Harmer
7.354
971681AH1-341 GEN
Solar/Wind Harmer
9.874
276612AE2-035 GEN
Solar/Wind Harmer
1.653
276868AE1-113 GEN
Solar/Wind Harmer
6.457
276882AE2-255 GEN
Solar/Wind Harmer
2.153
971171AH1-044 GEN
Solar/Wind Harmer
12.705
274823ROCKFORD ;21
Adder
12.345
971675AH1-338 GEN
Solar/Wind Harmer
11.295
971411AH1-196 GEN
Solar/Wind Harmer
9.296
971177AH1-047 GEN
Solar/Wind Harmer
3.602
274746AC1-111 G10
Adder
3.243
274744AC1-111 GEN8
Adder
3.243
274731ELWOOD EC;2P
Adder
9.103
274733ELWOOD EC;3P
Adder
9.103
274735ELWOOD EC;4P
Adder
9.103
274728ELWOOD EC;5P
Adder
9.099
274775LINCOLN ;6U
Adder
4.589
274776LINCOLN ;7U
Adder
4.589
274777LINCOLN ;8U
Adder
4.589
274675JOLIET 29;7U
Adder
16.603
274675JOLIET 29;7U
Adder
16.01
972227AH1-698 GEN1
Adder
1.397
274687WILL CNTY;4U
Adder
14.906
274687WILL CNTY;4U
Adder
14.906
274827FISK ;RP
Adder
3.883
972037AH1-567 GEN1
Adder
0.091
274814UNIV PK N;0U
Adder
2.271
274807UNIV PK N;3U
Adder
2.266
274805UNIV PK N;1U
Adder
2.256
274811UNIV PK N;7U
Adder
2.251
942481AE2-261 GEN
Solar/Wind Harmer
39.006
276621W2-048 GEN
Solar/Wind Harmer
7.212
276838X2-022 GEN2
Solar/Wind Harmer
0.269
276686W4-005 GEN3
Solar/Wind Harmer
3.311
971993AH1-541 GEN
Solar/Wind Harmer
10.113
276668AB2-070 GEN1
Solar/Wind Harmer
2.44
274853TWINGROVE;U1
Solar/Wind Harmer
6.686
965091AG1-374 GEN
Solar/Wind Harmer
27.83
959611AF2-252 GEN
Solar/Wind Harmer
2.157
942111AE2-223 GEN
Solar/Wind Harmer
7.058
274878BISHOP HL;2U
Solar/Wind Harmer
2.503
965931AG1-462 GEN
Solar/Wind Harmer
18.463
276157O29GEN1
Solar/Wind Harmer
2.648
970571AG2-364 GEN
Solar/Wind Harmer
13.85
276889AE2-281 GEN
Solar/Wind Harmer
1.273
274858EASY ROAD;U2
Solar/Wind Harmer
3.172
274760LEE CO EC;1U
Adder
6.159
274767LEE CO EC;8U
Adder
6.086
972236AH1-702 GEN2
Adder
1.398
959091AF2-200 GEN
Solar/Wind Harmer
12.705
274855GSG-6 ;RU
Solar/Wind Harmer
2.32
274850MENDOTA H;RU
Solar/Wind Harmer
1.613
276602WESTBROOK C
Solar/Wind Harmer
1.335
276863AD2-134 GEN
Solar/Wind Harmer
1.122
276799AD1-013 GEN
Solar/Wind Harmer
1.386
946671AF1-331 GEN
Solar/Wind Harmer
0.262
276805AD2-038 GEN
Solar/Wind Harmer
3.187
274872LEEDK;1U
Solar/Wind Harmer
0.157
276694AA1-018 GEN2
Solar/Wind Harmer
3.729
274682WAUKEGAN ;7U
Adder
10.534
274729ELWOOD EC;1P
Adder
9.103
274730ELWOOD EC;6P
Adder
9.099
274734ELWOOD EC;8P
Adder
9.099
274736ELWOOD EC;9P
Adder
9.099
274772LINCOLN ;3U
Adder
4.589
274676JOLIET 29;8U
Adder
16.01
972228AH1-698 GEN2
Adder
1.983
274800UNIV PARK;3U
Adder
2.967
972038AH1-567 GEN2
Adder
0.186
274826FISK ;BP
Adder
5.479
274802UNIV PARK;5U
Adder
2.888
274724RIVER EC ;11
Adder
7.686
944201AF1-088_MTX
Adder
0
991192J1610 G
External Queue
6.517440319061279
991267J1714
External Queue
14.379531860351562
991197J1626
External Queue
21.56929588317871
990272J1263 G
External Queue
55.931575775146484
990272J1263 G
External Queue
32.090484619140625
990353J1289
External Queue
6.731937885284424
991037J1464 G
External Queue
40.676658630371094
991082J1475 G
External Queue
40.78080368041992
990857J1408
External Queue
5.362168312072754
990857J1408
External Queue
2.9304873943328857
NYPJM->LTFIMP_NY
CLTF
0.345
WECLTFEXP_WEC->PJM
CLTF
2.403
CPLELTFEXP_CPLE->PJM
CLTF
0.726
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.927
AG2-052LTFEXP_AG2-052->PJM
LTF
0.062
AH1-155LTFEXP_AH1-155->PJM
LTF
0.093
CBM West 1LTFEXP_CBM-W1->PJM
CBM
64.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.588
MECLTFEXP_MEC->PJM
CLTF
13.307
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.78
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.061
LAGNLTFEXP_LAGN->PJM
CLTF
10.981
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.296
TVALTFEXP_TVA->PJM
CLTF
4.219

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.1 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1783.79
MW Contribution:7.73
Bus #Bus NameTypeMW Contribution
944221AF1-090 GEN
Solar/Wind Harmer
16.194
276785W4-005 GEN1
Solar/Wind Harmer
3.282
276174W4-005 GEN2
Solar/Wind Harmer
3.282
276849AB2-070 GEN2
Solar/Wind Harmer
2.418
276848AB2-070 GEN3
Solar/Wind Harmer
2.418
276655WTG1_EQ
Solar/Wind Harmer
7.482
276656WTG2_EQ
Solar/Wind Harmer
0.991
959341AF2-225 GEN
Solar/Wind Harmer
12.855
941731AE2-173 GEN
Solar/Wind Harmer
4.982
970169AG2-114 GEN
Solar/Wind Harmer
7.637
274848CAMPGROVE;RU
Solar/Wind Harmer
4.883
957751AF2-069 GEN
Solar/Wind Harmer
0.338
274863CRW1-WTG
Solar/Wind Harmer
4.049
274864CRW2-WTG
Solar/Wind Harmer
4.049
946321AF1-296 GEN
Solar/Wind Harmer
7.477
926823AC1-168 GEN
Solar/Wind Harmer
3.013
961011AF2-392 GEN
Solar/Wind Harmer
7.371
971681AH1-341 GEN
Solar/Wind Harmer
9.907
276612AE2-035 GEN
Solar/Wind Harmer
1.659
276868AE1-113 GEN
Solar/Wind Harmer
6.492
276882AE2-255 GEN
Solar/Wind Harmer
2.164
971171AH1-044 GEN
Solar/Wind Harmer
12.765
274823ROCKFORD ;21
Adder
12.404
971675AH1-338 GEN
Solar/Wind Harmer
11.355
971411AH1-196 GEN
Solar/Wind Harmer
9.349
971177AH1-047 GEN
Solar/Wind Harmer
3.623
274746AC1-111 G10
Adder
3.271
274744AC1-111 GEN8
Adder
3.271
274731ELWOOD EC;2P
Adder
9.202
274733ELWOOD EC;3P
Adder
9.202
274735ELWOOD EC;4P
Adder
9.202
274650KINCAID ;1U
50/50
4.504
274651KINCAID ;2U
50/50
4.502
276916AD2-100_GEN
Solar/Wind Harmer
28.038
276911AD2-131_GEN
Solar/Wind Harmer
5.667
957381AF2-032 GEN
Solar/Wind Harmer
0.534
276763AC1-053 GEN1
Solar/Wind Harmer
4.34
276764AC1-053 GEN2
Solar/Wind Harmer
4.34
960611AF2-352 GEN
Solar/Wind Harmer
2.145
276782AC1-033 GEN
Solar/Wind Harmer
2.956
274851PROVIDENC;RU
Solar/Wind Harmer
2.098
274849CRESCENT ;1U
Solar/Wind Harmer
1.362
276645AC1-214 GEN1
Solar/Wind Harmer
0.987
276646AC1-214 GEN2
Solar/Wind Harmer
0.987
276741O09 GEN1
Solar/Wind Harmer
2.49
276708O09 GEN2
Solar/Wind Harmer
2.49
972267AH1-718 GEN
Adder
2.829
276603SUBLETTE C
Solar/Wind Harmer
0.703
276872AE1-163_GEN1
Solar/Wind Harmer
4.475
274764LEE CO EC;5U
Adder
6.192
274765LEE CO EC;6U
Adder
6.192
274762LEE CO EC;3U
Adder
6.178
274763LEE CO EC;4U
Adder
6.12
938861AE1-114 GEN
Solar/Wind Harmer
5.407
274856ECOGROVE ;U1
Solar/Wind Harmer
2.187
276611AD2-172 GEN
Solar/Wind Harmer
1.659
274879MINONK ;1U
Solar/Wind Harmer
4.328
971341AH1-150 GEN
Solar/Wind Harmer
12.765
942481AE2-261 GEN
Solar/Wind Harmer
38.645
276621W2-048 GEN
Solar/Wind Harmer
7.148
276838X2-022 GEN2
Solar/Wind Harmer
0.267
276686W4-005 GEN3
Solar/Wind Harmer
3.282
971993AH1-541 GEN
Solar/Wind Harmer
10.025
276668AB2-070 GEN1
Solar/Wind Harmer
2.418
274853TWINGROVE;U1
Solar/Wind Harmer
6.649
965091AG1-374 GEN
Solar/Wind Harmer
27.676
959611AF2-252 GEN
Solar/Wind Harmer
2.145
942111AE2-223 GEN
Solar/Wind Harmer
7.025
274878BISHOP HL;2U
Solar/Wind Harmer
2.502
965931AG1-462 GEN
Solar/Wind Harmer
18.458
276157O29GEN1
Solar/Wind Harmer
2.652
970571AG2-364 GEN
Solar/Wind Harmer
13.886
276889AE2-281 GEN
Solar/Wind Harmer
1.279
274858EASY ROAD;U2
Solar/Wind Harmer
3.182
274760LEE CO EC;1U
Adder
6.178
274767LEE CO EC;8U
Adder
6.105
972236AH1-702 GEN2
Adder
1.404
959091AF2-200 GEN
Solar/Wind Harmer
12.765
274855GSG-6 ;RU
Solar/Wind Harmer
2.332
274850MENDOTA H;RU
Solar/Wind Harmer
1.621
276602WESTBROOK C
Solar/Wind Harmer
1.342
276863AD2-134 GEN
Solar/Wind Harmer
1.128
276799AD1-013 GEN
Solar/Wind Harmer
1.393
946671AF1-331 GEN
Solar/Wind Harmer
0.264
276805AD2-038 GEN
Solar/Wind Harmer
3.208
274872LEEDK;1U
Solar/Wind Harmer
0.158
276694AA1-018 GEN2
Solar/Wind Harmer
3.76
274682WAUKEGAN ;7U
Adder
10.618
274729ELWOOD EC;1P
Adder
9.202
274730ELWOOD EC;6P
Adder
9.198
274734ELWOOD EC;8P
Adder
9.198
274736ELWOOD EC;9P
Adder
9.198
274772LINCOLN ;3U
Adder
4.643
274676JOLIET 29;8U
Adder
16.199
972228AH1-698 GEN2
Adder
2.008
274800UNIV PARK;3U
Adder
3.012
972038AH1-567 GEN2
Adder
0.189
274826FISK ;BP
Adder
5.565
274802UNIV PARK;5U
Adder
2.934
274724RIVER EC ;11
Adder
7.87
274728ELWOOD EC;5P
Adder
9.198
274775LINCOLN ;6U
Adder
4.643
274776LINCOLN ;7U
Adder
4.643
274777LINCOLN ;8U
Adder
4.643
274675JOLIET 29;7U
Adder
16.799
274675JOLIET 29;7U
Adder
16.199
972227AH1-698 GEN1
Adder
1.414
274687WILL CNTY;4U
Adder
15.092
274687WILL CNTY;4U
Adder
15.092
274827FISK ;RP
Adder
3.944
972037AH1-567 GEN1
Adder
0.092
274814UNIV PK N;0U
Adder
2.317
274807UNIV PK N;3U
Adder
2.312
274805UNIV PK N;1U
Adder
2.302
274811UNIV PK N;7U
Adder
2.297
965911AG1-460 GEN
Solar/Wind Harmer
1.803
276615X2-022 GEN
Solar/Wind Harmer
2.244
963831AG1-236 GEN
Solar/Wind Harmer
10.796
274880W4-005 GEN4
Solar/Wind Harmer
3.282
972175AH1-670 GEN
Solar/Wind Harmer
13.782
274854TWINGROVE;U2
Solar/Wind Harmer
6.51
276726Z2-087_GEN
Solar/Wind Harmer
6.778
939741AE1-205 GEN
Solar/Wind Harmer
17.139
274877BISHOP HL;1U
Solar/Wind Harmer
2.502
276158O29GEN2
Solar/Wind Harmer
3.486
970569AG2-363 GEN
Solar/Wind Harmer
20.829
939401AE1-172 GEN
Solar/Wind Harmer
9.546
276876AE1-163_GEN2
Solar/Wind Harmer
4.475
274857EASY ROAD;U1
Solar/Wind Harmer
3.182
274761LEE CO EC;2U
Adder
6.178
274766LEE CO EC;7U
Adder
6.105
971997AH1-543 GEN
Solar/Wind Harmer
10.431
971475AH1-234 GEN
Solar/Wind Harmer
14.44
970819AG2-516 GEN
Solar/Wind Harmer
7.727
972235AH1-702 GEN1
Adder
1.615
276901AD2-066 C O1
Solar/Wind Harmer
2.244
957471AF2-041 GEN
Solar/Wind Harmer
19.148
959081AF2-199 GEN
Solar/Wind Harmer
6.383
971067AG2-660 GEN
Solar/Wind Harmer
1.484
274822ROCKFORD ;11
Adder
12.494
276861AD2-134 GEN
Solar/Wind Harmer
1.128
274872LEEDK;1U
Solar/Wind Harmer
5.072
960751AF2-366 GEN
Solar/Wind Harmer
1.761
962781AG1-127 GEN
Solar/Wind Harmer
5.837
276691AA1-018 GEN1
Solar/Wind Harmer
0.277
274828WAUKEGAN ;BP
Adder
6.544
274682WAUKEGAN ;7U
Adder
10.618
274745AC1-111 GEN9
Adder
3.271
274732ELWOOD EC;7P
Adder
9.198
274674JOLIET 9 ;6U
Adder
8.579
274773LINCOLN ;4U
Adder
4.643
274774LINCOLN ;5U
Adder
4.643
274676JOLIET 29;8U
Adder
16.799
971343AH1-151 GEN
Solar/Wind Harmer
12.765
971333AH1-146 GEN
Solar/Wind Harmer
12.525
971335AH1-147 GEN
Solar/Wind Harmer
12.525
958491AF2-143 GEN
Solar/Wind Harmer
9.379
942991AE2-321 GEN
Solar/Wind Harmer
6.175
970921AG2-575 GEN
Solar/Wind Harmer
6.138
970921AG2-575 GEN
Solar/Wind Harmer
1.427
962691AG1-118 GEN
Solar/Wind Harmer
18.319
274696ROCKY RD ;4P
Adder
6.796
274695ROCKY RD ;2P
Adder
6.638
274693ROCKY RD ;1P
Adder
6.573
274697ROCKY RD ;3P
Adder
1.803
274861TOP CROP ;1U
Solar/Wind Harmer
3.611
274862TOP CROP ;2U
Solar/Wind Harmer
3.015
958481AF2-142 GEN
Solar/Wind Harmer
8.937
274683WAUKEGAN ;8U
Adder
12.485
274683WAUKEGAN ;8U
Adder
10.524
972259AH1-714 GEN
Adder
10.642
274674JOLIET 9 ;6U
Adder
8.579
274770LINCOLN ;1U
Adder
4.643
274771LINCOLN ;2U
Adder
4.643
274803UNIV PARK;6U
Adder
2.934
274808UNIV PK N;4U
Adder
2.287
971573AH1-285 GEN
Solar/Wind Harmer
2.89
274801UNIV PARK;4U
Adder
3.012
274812UNIV PK N;8U
Adder
2.297
274723RIVER EC ;12
Adder
7.936
944201AF1-088_MTX
Adder
0
991192J1610 G
External Queue
6.423544406890869
991267J1714
External Queue
14.205095291137695
991197J1626
External Queue
21.307641983032227
990272J1263 G
External Queue
55.282928466796875
990272J1263 G
External Queue
31.71832847595215
990353J1289
External Queue
6.637070178985596
991037J1464 G
External Queue
40.092811584472656
991082J1475 G
External Queue
40.549625396728516
990857J1408
External Queue
5.284822463989258
990857J1408
External Queue
2.888216972351074
NYPJM->LTFIMP_NY
CLTF
0.338
WECLTFEXP_WEC->PJM
CLTF
2.414
CPLELTFEXP_CPLE->PJM
CLTF
0.655
CBM West 2LTFEXP_CBM-W2->PJM
CBM
82.91
AG2-052LTFEXP_AG2-052->PJM
LTF
0.063
AH1-155LTFEXP_AH1-155->PJM
LTF
0.094
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.404
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.029
MECLTFEXP_MEC->PJM
CLTF
13.237
SIGELTFEXP_SIGE->PJM
CLTF
0.031
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.948
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.574
LAGNLTFEXP_LAGN->PJM
CLTF
10.746
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.061
TVALTFEXP_TVA->PJM
CLTF
4.089

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.37 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1771.85
MW Contribution:7.63
Bus #Bus NameTypeMW Contribution
942481AE2-261 GEN
Solar/Wind Harmer
38.902
276621W2-048 GEN
Solar/Wind Harmer
7.188
276838X2-022 GEN2
Solar/Wind Harmer
0.268
276686W4-005 GEN3
Solar/Wind Harmer
3.298
971993AH1-541 GEN
Solar/Wind Harmer
10.076
276668AB2-070 GEN1
Solar/Wind Harmer
2.43
274853TWINGROVE;U1
Solar/Wind Harmer
6.65
965091AG1-374 GEN
Solar/Wind Harmer
27.68
959611AF2-252 GEN
Solar/Wind Harmer
2.146
942111AE2-223 GEN
Solar/Wind Harmer
7.015
274878BISHOP HL;2U
Solar/Wind Harmer
2.484
965931AG1-462 GEN
Solar/Wind Harmer
18.33
276157O29GEN1
Solar/Wind Harmer
2.627
970571AG2-364 GEN
Solar/Wind Harmer
13.731
276889AE2-281 GEN
Solar/Wind Harmer
1.262
274858EASY ROAD;U2
Solar/Wind Harmer
3.145
274760LEE CO EC;1U
Adder
6.107
274767LEE CO EC;8U
Adder
6.035
972236AH1-702 GEN2
Adder
1.385
959091AF2-200 GEN
Solar/Wind Harmer
12.588
274855GSG-6 ;RU
Solar/Wind Harmer
2.298
274850MENDOTA H;RU
Solar/Wind Harmer
1.598
276602WESTBROOK C
Solar/Wind Harmer
1.323
276863AD2-134 GEN
Solar/Wind Harmer
1.111
276799AD1-013 GEN
Solar/Wind Harmer
1.373
946671AF1-331 GEN
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
3.154
274872LEEDK;1U
Solar/Wind Harmer
0.155
276694AA1-018 GEN2
Solar/Wind Harmer
3.686
274682WAUKEGAN ;7U
Adder
10.421
274729ELWOOD EC;1P
Adder
8.99
274730ELWOOD EC;6P
Adder
8.986
274734ELWOOD EC;8P
Adder
8.986
274736ELWOOD EC;9P
Adder
8.986
274772LINCOLN ;3U
Adder
4.513
274676JOLIET 29;8U
Adder
15.805
972228AH1-698 GEN2
Adder
1.956
274800UNIV PARK;3U
Adder
2.924
972038AH1-567 GEN2
Adder
0.183
274826FISK ;BP
Adder
5.396
274802UNIV PARK;5U
Adder
2.844
944221AF1-090 GEN
Solar/Wind Harmer
16.318
276785W4-005 GEN1
Solar/Wind Harmer
3.298
276174W4-005 GEN2
Solar/Wind Harmer
3.298
276849AB2-070 GEN2
Solar/Wind Harmer
2.43
276848AB2-070 GEN3
Solar/Wind Harmer
2.43
276655WTG1_EQ
Solar/Wind Harmer
7.471
276656WTG2_EQ
Solar/Wind Harmer
0.989
959341AF2-225 GEN
Solar/Wind Harmer
12.835
941731AE2-173 GEN
Solar/Wind Harmer
4.975
970169AG2-114 GEN
Solar/Wind Harmer
7.586
274848CAMPGROVE;RU
Solar/Wind Harmer
4.851
957751AF2-069 GEN
Solar/Wind Harmer
0.336
274863CRW1-WTG
Solar/Wind Harmer
4.01
274864CRW2-WTG
Solar/Wind Harmer
4.01
946321AF1-296 GEN
Solar/Wind Harmer
7.421
926823AC1-168 GEN
Solar/Wind Harmer
2.983
961011AF2-392 GEN
Solar/Wind Harmer
7.294
971681AH1-341 GEN
Solar/Wind Harmer
9.789
276612AE2-035 GEN
Solar/Wind Harmer
1.638
276868AE1-113 GEN
Solar/Wind Harmer
6.394
276882AE2-255 GEN
Solar/Wind Harmer
2.131
971171AH1-044 GEN
Solar/Wind Harmer
12.588
274823ROCKFORD ;21
Adder
12.232
971675AH1-338 GEN
Solar/Wind Harmer
11.19
971411AH1-196 GEN
Solar/Wind Harmer
9.207
971177AH1-047 GEN
Solar/Wind Harmer
3.567
274746AC1-111 G10
Adder
3.208
274744AC1-111 GEN8
Adder
3.208
274731ELWOOD EC;2P
Adder
8.99
274733ELWOOD EC;3P
Adder
8.99
274735ELWOOD EC;4P
Adder
8.99
274728ELWOOD EC;5P
Adder
8.986
274775LINCOLN ;6U
Adder
4.513
274776LINCOLN ;7U
Adder
4.513
274777LINCOLN ;8U
Adder
4.513
274675JOLIET 29;7U
Adder
16.391
274675JOLIET 29;7U
Adder
15.805
972227AH1-698 GEN1
Adder
1.378
274687WILL CNTY;4U
Adder
14.709
274687WILL CNTY;4U
Adder
14.709
274827FISK ;RP
Adder
3.824
972037AH1-567 GEN1
Adder
0.089
274814UNIV PK N;0U
Adder
2.232
274807UNIV PK N;3U
Adder
2.227
274805UNIV PK N;1U
Adder
2.217
274811UNIV PK N;7U
Adder
2.212
274650KINCAID ;1U
50/50
4.533
274651KINCAID ;2U
50/50
4.532
276916AD2-100_GEN
Solar/Wind Harmer
28.232
276911AD2-131_GEN
Solar/Wind Harmer
5.706
957381AF2-032 GEN
Solar/Wind Harmer
0.538
276763AC1-053 GEN1
Solar/Wind Harmer
4.363
276764AC1-053 GEN2
Solar/Wind Harmer
4.363
960611AF2-352 GEN
Solar/Wind Harmer
2.146
276782AC1-033 GEN
Solar/Wind Harmer
2.935
274851PROVIDENC;RU
Solar/Wind Harmer
2.082
274849CRESCENT ;1U
Solar/Wind Harmer
1.352
276645AC1-214 GEN1
Solar/Wind Harmer
0.979
276646AC1-214 GEN2
Solar/Wind Harmer
0.979
276741O09 GEN1
Solar/Wind Harmer
2.467
276708O09 GEN2
Solar/Wind Harmer
2.467
972267AH1-718 GEN
Adder
2.8
276603SUBLETTE C
Solar/Wind Harmer
0.695
276872AE1-163_GEN1
Solar/Wind Harmer
4.415
274764LEE CO EC;5U
Adder
6.121
274765LEE CO EC;6U
Adder
6.121
274762LEE CO EC;3U
Adder
6.107
274763LEE CO EC;4U
Adder
6.049
938861AE1-114 GEN
Solar/Wind Harmer
5.342
274856ECOGROVE ;U1
Solar/Wind Harmer
2.159
276611AD2-172 GEN
Solar/Wind Harmer
1.638
274879MINONK ;1U
Solar/Wind Harmer
4.263
971341AH1-150 GEN
Solar/Wind Harmer
12.588
971343AH1-151 GEN
Solar/Wind Harmer
12.588
971333AH1-146 GEN
Solar/Wind Harmer
12.339
971335AH1-147 GEN
Solar/Wind Harmer
12.339
958491AF2-143 GEN
Solar/Wind Harmer
9.222
942991AE2-321 GEN
Solar/Wind Harmer
6.078
970921AG2-575 GEN
Solar/Wind Harmer
6.039
970921AG2-575 GEN
Solar/Wind Harmer
1.404
962691AG1-118 GEN
Solar/Wind Harmer
18.018
274696ROCKY RD ;4P
Adder
6.674
274695ROCKY RD ;2P
Adder
6.519
274693ROCKY RD ;1P
Adder
6.455
274697ROCKY RD ;3P
Adder
1.771
274861TOP CROP ;1U
Solar/Wind Harmer
3.54
274862TOP CROP ;2U
Solar/Wind Harmer
2.956
958481AF2-142 GEN
Solar/Wind Harmer
8.761
274683WAUKEGAN ;8U
Adder
12.255
274683WAUKEGAN ;8U
Adder
10.33
972259AH1-714 GEN
Adder
10.401
274674JOLIET 9 ;6U
Adder
8.38
274770LINCOLN ;1U
Adder
4.513
274771LINCOLN ;2U
Adder
4.513
274803UNIV PARK;6U
Adder
2.844
274808UNIV PK N;4U
Adder
2.203
971573AH1-285 GEN
Solar/Wind Harmer
2.838
965911AG1-460 GEN
Solar/Wind Harmer
1.815
276615X2-022 GEN
Solar/Wind Harmer
2.257
963831AG1-236 GEN
Solar/Wind Harmer
10.854
274880W4-005 GEN4
Solar/Wind Harmer
3.298
972175AH1-670 GEN
Solar/Wind Harmer
13.823
274854TWINGROVE;U2
Solar/Wind Harmer
6.511
276726Z2-087_GEN
Solar/Wind Harmer
6.768
939741AE1-205 GEN
Solar/Wind Harmer
17.114
274877BISHOP HL;1U
Solar/Wind Harmer
2.484
276158O29GEN2
Solar/Wind Harmer
3.453
970569AG2-363 GEN
Solar/Wind Harmer
20.597
939401AE1-172 GEN
Solar/Wind Harmer
9.425
276876AE1-163_GEN2
Solar/Wind Harmer
4.415
274857EASY ROAD;U1
Solar/Wind Harmer
3.145
274761LEE CO EC;2U
Adder
6.107
274766LEE CO EC;7U
Adder
6.035
971997AH1-543 GEN
Solar/Wind Harmer
10.294
971475AH1-234 GEN
Solar/Wind Harmer
14.252
970819AG2-516 GEN
Solar/Wind Harmer
7.626
972235AH1-702 GEN1
Adder
1.593
957471AF2-041 GEN
Solar/Wind Harmer
18.883
959081AF2-199 GEN
Solar/Wind Harmer
6.294
971067AG2-660 GEN
Solar/Wind Harmer
1.464
276901AD2-066 C O1
Solar/Wind Harmer
2.211
274822ROCKFORD ;11
Adder
12.321
276861AD2-134 GEN
Solar/Wind Harmer
1.111
274872LEEDK;1U
Solar/Wind Harmer
4.992
960751AF2-366 GEN
Solar/Wind Harmer
1.733
962781AG1-127 GEN
Solar/Wind Harmer
5.743
276691AA1-018 GEN1
Solar/Wind Harmer
0.272
274828WAUKEGAN ;BP
Adder
6.424
274682WAUKEGAN ;7U
Adder
10.421
274745AC1-111 GEN9
Adder
3.208
274732ELWOOD EC;7P
Adder
8.986
274674JOLIET 9 ;6U
Adder
8.38
274773LINCOLN ;4U
Adder
4.513
274774LINCOLN ;5U
Adder
4.513
274676JOLIET 29;8U
Adder
16.391
274801UNIV PARK;4U
Adder
2.924
274812UNIV PK N;8U
Adder
2.212
944201AF1-088_MTX
Adder
0
991192J1610 G
External Queue
6.51393461227417
991267J1714
External Queue
14.391900062561035
991197J1626
External Queue
21.587848663330078
990272J1263 G
External Queue
55.98657989501953
990272J1263 G
External Queue
32.12204360961914
990353J1289
External Queue
6.727969646453857
991037J1464 G
External Queue
40.6635627746582
991082J1475 G
External Queue
40.802940368652344
990857J1408
External Queue
5.360954284667969
990857J1408
External Queue
2.929823875427246
NYPJM->LTFIMP_NY
CLTF
0.338
WECLTFEXP_WEC->PJM
CLTF
2.38
CPLELTFEXP_CPLE->PJM
CLTF
0.735
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.768
AG2-052LTFEXP_AG2-052->PJM
LTF
0.06
AH1-155LTFEXP_AH1-155->PJM
LTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.722
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.582
MECLTFEXP_MEC->PJM
CLTF
13.237
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.775
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.045
LAGNLTFEXP_LAGN->PJM
CLTF
10.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.316
TVALTFEXP_TVA->PJM
CLTF
4.216

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.37 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1771.85
MW Contribution:7.63
Bus #Bus NameTypeMW Contribution
942481AE2-261 GEN
Solar/Wind Harmer
38.902
276621W2-048 GEN
Solar/Wind Harmer
7.188
276838X2-022 GEN2
Solar/Wind Harmer
0.268
276686W4-005 GEN3
Solar/Wind Harmer
3.298
971993AH1-541 GEN
Solar/Wind Harmer
10.076
276668AB2-070 GEN1
Solar/Wind Harmer
2.43
274853TWINGROVE;U1
Solar/Wind Harmer
6.65
944221AF1-090 GEN
Solar/Wind Harmer
16.318
276785W4-005 GEN1
Solar/Wind Harmer
3.298
276174W4-005 GEN2
Solar/Wind Harmer
3.298
276849AB2-070 GEN2
Solar/Wind Harmer
2.43
276848AB2-070 GEN3
Solar/Wind Harmer
2.43
276655WTG1_EQ
Solar/Wind Harmer
7.471
276656WTG2_EQ
Solar/Wind Harmer
0.989
959341AF2-225 GEN
Solar/Wind Harmer
12.835
941731AE2-173 GEN
Solar/Wind Harmer
4.975
970169AG2-114 GEN
Solar/Wind Harmer
7.586
274848CAMPGROVE;RU
Solar/Wind Harmer
4.851
957751AF2-069 GEN
Solar/Wind Harmer
0.336
274863CRW1-WTG
Solar/Wind Harmer
4.01
274864CRW2-WTG
Solar/Wind Harmer
4.01
946321AF1-296 GEN
Solar/Wind Harmer
7.421
926823AC1-168 GEN
Solar/Wind Harmer
2.983
961011AF2-392 GEN
Solar/Wind Harmer
7.294
971681AH1-341 GEN
Solar/Wind Harmer
9.789
276612AE2-035 GEN
Solar/Wind Harmer
1.638
276868AE1-113 GEN
Solar/Wind Harmer
6.393
276882AE2-255 GEN
Solar/Wind Harmer
2.131
971171AH1-044 GEN
Solar/Wind Harmer
12.588
274823ROCKFORD ;21
Adder
12.232
971675AH1-338 GEN
Solar/Wind Harmer
11.19
971411AH1-196 GEN
Solar/Wind Harmer
9.207
971177AH1-047 GEN
Solar/Wind Harmer
3.566
274746AC1-111 G10
Adder
3.208
274744AC1-111 GEN8
Adder
3.208
274731ELWOOD EC;2P
Adder
8.99
274733ELWOOD EC;3P
Adder
8.99
274735ELWOOD EC;4P
Adder
8.99
274728ELWOOD EC;5P
Adder
8.986
274775LINCOLN ;6U
Adder
4.514
274776LINCOLN ;7U
Adder
4.514
274777LINCOLN ;8U
Adder
4.514
274675JOLIET 29;7U
Adder
16.391
274675JOLIET 29;7U
Adder
15.805
972227AH1-698 GEN1
Adder
1.378
274687WILL CNTY;4U
Adder
14.709
274687WILL CNTY;4U
Adder
14.709
274827FISK ;RP
Adder
3.824
972037AH1-567 GEN1
Adder
0.089
274814UNIV PK N;0U
Adder
2.232
274807UNIV PK N;3U
Adder
2.227
274805UNIV PK N;1U
Adder
2.217
274811UNIV PK N;7U
Adder
2.212
274650KINCAID ;1U
50/50
4.533
274651KINCAID ;2U
50/50
4.532
276916AD2-100_GEN
Solar/Wind Harmer
28.232
276911AD2-131_GEN
Solar/Wind Harmer
5.706
957381AF2-032 GEN
Solar/Wind Harmer
0.538
276763AC1-053 GEN1
Solar/Wind Harmer
4.363
276764AC1-053 GEN2
Solar/Wind Harmer
4.363
960611AF2-352 GEN
Solar/Wind Harmer
2.146
276782AC1-033 GEN
Solar/Wind Harmer
2.935
274851PROVIDENC;RU
Solar/Wind Harmer
2.082
274849CRESCENT ;1U
Solar/Wind Harmer
1.352
276645AC1-214 GEN1
Solar/Wind Harmer
0.979
276646AC1-214 GEN2
Solar/Wind Harmer
0.979
276741O09 GEN1
Solar/Wind Harmer
2.467
276708O09 GEN2
Solar/Wind Harmer
2.467
972267AH1-718 GEN
Adder
2.8
276603SUBLETTE C
Solar/Wind Harmer
0.695
276872AE1-163_GEN1
Solar/Wind Harmer
4.415
274764LEE CO EC;5U
Adder
6.121
274765LEE CO EC;6U
Adder
6.121
274762LEE CO EC;3U
Adder
6.107
274763LEE CO EC;4U
Adder
6.049
938861AE1-114 GEN
Solar/Wind Harmer
5.342
274856ECOGROVE ;U1
Solar/Wind Harmer
2.158
276611AD2-172 GEN
Solar/Wind Harmer
1.638
274879MINONK ;1U
Solar/Wind Harmer
4.263
971341AH1-150 GEN
Solar/Wind Harmer
12.588
971343AH1-151 GEN
Solar/Wind Harmer
12.588
971333AH1-146 GEN
Solar/Wind Harmer
12.338
971335AH1-147 GEN
Solar/Wind Harmer
12.338
958491AF2-143 GEN
Solar/Wind Harmer
9.222
942991AE2-321 GEN
Solar/Wind Harmer
6.078
970921AG2-575 GEN
Solar/Wind Harmer
6.039
970921AG2-575 GEN
Solar/Wind Harmer
1.404
962691AG1-118 GEN
Solar/Wind Harmer
18.018
274696ROCKY RD ;4P
Adder
6.674
274695ROCKY RD ;2P
Adder
6.519
274693ROCKY RD ;1P
Adder
6.455
274697ROCKY RD ;3P
Adder
1.771
274861TOP CROP ;1U
Solar/Wind Harmer
3.54
274862TOP CROP ;2U
Solar/Wind Harmer
2.956
958481AF2-142 GEN
Solar/Wind Harmer
8.761
274683WAUKEGAN ;8U
Adder
12.255
274683WAUKEGAN ;8U
Adder
10.33
972259AH1-714 GEN
Adder
10.401
274674JOLIET 9 ;6U
Adder
8.38
274770LINCOLN ;1U
Adder
4.514
274771LINCOLN ;2U
Adder
4.514
274803UNIV PARK;6U
Adder
2.844
274808UNIV PK N;4U
Adder
2.203
971573AH1-285 GEN
Solar/Wind Harmer
2.838
965911AG1-460 GEN
Solar/Wind Harmer
1.815
276615X2-022 GEN
Solar/Wind Harmer
2.257
963831AG1-236 GEN
Solar/Wind Harmer
10.854
274880W4-005 GEN4
Solar/Wind Harmer
3.298
972175AH1-670 GEN
Solar/Wind Harmer
13.823
274854TWINGROVE;U2
Solar/Wind Harmer
6.511
276726Z2-087_GEN
Solar/Wind Harmer
6.768
939741AE1-205 GEN
Solar/Wind Harmer
17.114
274877BISHOP HL;1U
Solar/Wind Harmer
2.484
276158O29GEN2
Solar/Wind Harmer
3.453
970569AG2-363 GEN
Solar/Wind Harmer
20.596
939401AE1-172 GEN
Solar/Wind Harmer
9.425
276876AE1-163_GEN2
Solar/Wind Harmer
4.415
274857EASY ROAD;U1
Solar/Wind Harmer
3.145
274761LEE CO EC;2U
Adder
6.107
274766LEE CO EC;7U
Adder
6.035
971997AH1-543 GEN
Solar/Wind Harmer
10.294
971475AH1-234 GEN
Solar/Wind Harmer
14.252
970819AG2-516 GEN
Solar/Wind Harmer
7.626
972235AH1-702 GEN1
Adder
1.593
957471AF2-041 GEN
Solar/Wind Harmer
18.882
959081AF2-199 GEN
Solar/Wind Harmer
6.294
971067AG2-660 GEN
Solar/Wind Harmer
1.464
276901AD2-066 C O1
Solar/Wind Harmer
2.211
274822ROCKFORD ;11
Adder
12.321
276861AD2-134 GEN
Solar/Wind Harmer
1.111
274872LEEDK;1U
Solar/Wind Harmer
4.992
960751AF2-366 GEN
Solar/Wind Harmer
1.733
962781AG1-127 GEN
Solar/Wind Harmer
5.743
276691AA1-018 GEN1
Solar/Wind Harmer
0.272
274828WAUKEGAN ;BP
Adder
6.424
274682WAUKEGAN ;7U
Adder
10.421
274745AC1-111 GEN9
Adder
3.208
274732ELWOOD EC;7P
Adder
8.986
274674JOLIET 9 ;6U
Adder
8.38
274773LINCOLN ;4U
Adder
4.514
274774LINCOLN ;5U
Adder
4.514
274676JOLIET 29;8U
Adder
16.391
274801UNIV PARK;4U
Adder
2.924
274812UNIV PK N;8U
Adder
2.212
965091AG1-374 GEN
Solar/Wind Harmer
27.68
959611AF2-252 GEN
Solar/Wind Harmer
2.146
942111AE2-223 GEN
Solar/Wind Harmer
7.015
274878BISHOP HL;2U
Solar/Wind Harmer
2.484
965931AG1-462 GEN
Solar/Wind Harmer
18.33
276157O29GEN1
Solar/Wind Harmer
2.627
970571AG2-364 GEN
Solar/Wind Harmer
13.731
276889AE2-281 GEN
Solar/Wind Harmer
1.262
274858EASY ROAD;U2
Solar/Wind Harmer
3.145
274760LEE CO EC;1U
Adder
6.107
274767LEE CO EC;8U
Adder
6.035
972236AH1-702 GEN2
Adder
1.385
959091AF2-200 GEN
Solar/Wind Harmer
12.588
274855GSG-6 ;RU
Solar/Wind Harmer
2.298
274850MENDOTA H;RU
Solar/Wind Harmer
1.598
276602WESTBROOK C
Solar/Wind Harmer
1.323
276863AD2-134 GEN
Solar/Wind Harmer
1.111
276799AD1-013 GEN
Solar/Wind Harmer
1.373
946671AF1-331 GEN
Solar/Wind Harmer
0.26
276805AD2-038 GEN
Solar/Wind Harmer
3.154
274872LEEDK;1U
Solar/Wind Harmer
0.155
276694AA1-018 GEN2
Solar/Wind Harmer
3.686
274682WAUKEGAN ;7U
Adder
10.421
274729ELWOOD EC;1P
Adder
8.99
274730ELWOOD EC;6P
Adder
8.986
274734ELWOOD EC;8P
Adder
8.986
274736ELWOOD EC;9P
Adder
8.986
274772LINCOLN ;3U
Adder
4.514
274676JOLIET 29;8U
Adder
15.805
972228AH1-698 GEN2
Adder
1.956
274800UNIV PARK;3U
Adder
2.924
972038AH1-567 GEN2
Adder
0.183
274826FISK ;BP
Adder
5.396
274802UNIV PARK;5U
Adder
2.844
944201AF1-088_MTX
Adder
0
991192J1610 G
External Queue
6.51392936706543
991267J1714
External Queue
14.391907691955566
991197J1626
External Queue
21.587860107421875
990272J1263 G
External Queue
55.98662567138672
990272J1263 G
External Queue
32.1220703125
990353J1289
External Queue
6.727962017059326
991037J1464 G
External Queue
40.663536071777344
991082J1475 G
External Queue
40.80295944213867
990857J1408
External Queue
5.3609514236450195
990857J1408
External Queue
2.9298222064971924
NYPJM->LTFIMP_NY
CLTF
0.338
WECLTFEXP_WEC->PJM
CLTF
2.38
CPLELTFEXP_CPLE->PJM
CLTF
0.735
CBM West 2LTFEXP_CBM-W2->PJM
CBM
84.768
AG2-052LTFEXP_AG2-052->PJM
LTF
0.06
AH1-155LTFEXP_AH1-155->PJM
LTF
0.09
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.721
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.582
MECLTFEXP_MEC->PJM
CLTF
13.236
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.775
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.045
LAGNLTFEXP_LAGN->PJM
CLTF
10.962
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.316
TVALTFEXP_TVA->PJM
CLTF
4.216

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P4_#3128_05EUGENE 345_A2_SRT-A


Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#3128_05EUGENE 345_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.8 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1762.5
MW Contribution:6.91
Bus #Bus NameTypeMW Contribution
965911AG1-460 GEN
Solar/Wind Harmer
2.107
276615X2-022 GEN
Solar/Wind Harmer
2.687
963831AG1-236 GEN
Solar/Wind Harmer
13.068
274880W4-005 GEN4
Solar/Wind Harmer
3.981
972175AH1-670 GEN
Solar/Wind Harmer
16.349
274854TWINGROVE;U2
Solar/Wind Harmer
7.491
276726Z2-087_GEN
Solar/Wind Harmer
7.772
939741AE1-205 GEN
Solar/Wind Harmer
19.652
274877BISHOP HL;1U
Solar/Wind Harmer
2.507
970569AG2-363 GEN
Solar/Wind Harmer
20.036
939401AE1-172 GEN
Solar/Wind Harmer
9.297
276158O29GEN2
Solar/Wind Harmer
3.308
276876AE1-163_GEN2
Solar/Wind Harmer
4.212
971997AH1-543 GEN
Solar/Wind Harmer
9.636
274857EASY ROAD;U1
Solar/Wind Harmer
2.906
274761LEE CO EC;2U
Adder
5.641
274766LEE CO EC;7U
Adder
5.575
276901AD2-066 C O1
Solar/Wind Harmer
2.077
971475AH1-234 GEN
Solar/Wind Harmer
12.931
970819AG2-516 GEN
Solar/Wind Harmer
6.911
972235AH1-702 GEN1
Adder
1.438
957471AF2-041 GEN
Solar/Wind Harmer
16.947
959081AF2-199 GEN
Solar/Wind Harmer
5.649
971067AG2-660 GEN
Solar/Wind Harmer
1.314
274822ROCKFORD ;11
Adder
11.077
276861AD2-134 GEN
Solar/Wind Harmer
0.988
274872LEEDK;1U
Solar/Wind Harmer
4.356
276691AA1-018 GEN1
Solar/Wind Harmer
0.244
960751AF2-366 GEN
Solar/Wind Harmer
1.505
962781AG1-127 GEN
Solar/Wind Harmer
4.989
274828WAUKEGAN ;BP
Adder
5.533
274682WAUKEGAN ;7U
Adder
8.958
274745AC1-111 GEN9
Adder
2.688
274732ELWOOD EC;7P
Adder
7.644
274674JOLIET 9 ;6U
Adder
7.069
274676JOLIET 29;8U
Adder
13.655
24385905FR-11G C
Solar/Wind Helper
1.5
24387305FR-4G C
Solar/Wind Helper
1.924
24791305MDL-5G
Solar/Wind Helper
0.551
944221AF1-090 GEN
Solar/Wind Harmer
18.59
276785W4-005 GEN1
Solar/Wind Harmer
3.981
276174W4-005 GEN2
Solar/Wind Harmer
3.981
276849AB2-070 GEN2
Solar/Wind Harmer
2.943
276848AB2-070 GEN3
Solar/Wind Harmer
2.943
276655WTG1_EQ
Solar/Wind Harmer
8.579
276656WTG2_EQ
Solar/Wind Harmer
1.136
959341AF2-225 GEN
Solar/Wind Harmer
14.739
941731AE2-173 GEN
Solar/Wind Harmer
5.713
970169AG2-114 GEN
Solar/Wind Harmer
8.052
274848CAMPGROVE;RU
Solar/Wind Harmer
4.955
957751AF2-069 GEN
Solar/Wind Harmer
0.34
274863CRW1-WTG
Solar/Wind Harmer
4.121
274864CRW2-WTG
Solar/Wind Harmer
4.121
946321AF1-296 GEN
Solar/Wind Harmer
7.177
926823AC1-168 GEN
Solar/Wind Harmer
2.942
961011AF2-392 GEN
Solar/Wind Harmer
6.832
971681AH1-341 GEN
Solar/Wind Harmer
9.017
276868AE1-113 GEN
Solar/Wind Harmer
5.936
276882AE2-255 GEN
Solar/Wind Harmer
1.979
276612AE2-035 GEN
Solar/Wind Harmer
1.491
971171AH1-044 GEN
Solar/Wind Harmer
11.298
274823ROCKFORD ;21
Adder
10.997
971675AH1-338 GEN
Solar/Wind Harmer
9.938
971411AH1-196 GEN
Solar/Wind Harmer
8.16
971177AH1-047 GEN
Solar/Wind Harmer
3.142
274746AC1-111 G10
Adder
2.688
274744AC1-111 GEN8
Adder
2.688
274731ELWOOD EC;2P
Adder
7.648
274733ELWOOD EC;3P
Adder
7.648
274735ELWOOD EC;4P
Adder
7.648
274728ELWOOD EC;5P
Adder
7.644
274675JOLIET 29;7U
Adder
13.654
274675JOLIET 29;7U
Adder
13.166
972227AH1-698 GEN1
Adder
1.147
274687WILL CNTY;4U
Adder
12.256
274687WILL CNTY;4U
Adder
12.256
24386205FR-12G C
Solar/Wind Helper
0.876
24386405FR-21G C
Solar/Wind Helper
0.718
24386605FR-22G C
Solar/Wind Helper
0.718
24387005FR-3G C
Solar/Wind Helper
0.897
24690905MDL-1G C
Solar/Wind Helper
1.347
270180AB1-006 GEN1
Solar/Wind Helper
1.184
24691005MDL-2G C
Solar/Wind Helper
0.791
24697605MDL-3G C
Solar/Wind Helper
0.796
24697905MDL-4G C
Solar/Wind Helper
0.603
270181AB1-006 GEN2
Solar/Wind Helper
0.169
274650KINCAID ;1U
50/50
5.269
274651KINCAID ;2U
50/50
5.268
276916AD2-100_GEN
Solar/Wind Harmer
32.609
276911AD2-131_GEN
Solar/Wind Harmer
6.59
957381AF2-032 GEN
Solar/Wind Harmer
0.625
276763AC1-053 GEN1
Solar/Wind Harmer
5.254
276764AC1-053 GEN2
Solar/Wind Harmer
5.254
960611AF2-352 GEN
Solar/Wind Harmer
2.469
276782AC1-033 GEN
Solar/Wind Harmer
2.961
274851PROVIDENC;RU
Solar/Wind Harmer
2.108
274849CRESCENT ;1U
Solar/Wind Harmer
1.369
276645AC1-214 GEN1
Solar/Wind Harmer
0.992
276646AC1-214 GEN2
Solar/Wind Harmer
0.992
276741O09 GEN1
Solar/Wind Harmer
2.363
276708O09 GEN2
Solar/Wind Harmer
2.363
972267AH1-718 GEN
Adder
2.623
276872AE1-163_GEN1
Solar/Wind Harmer
4.212
276603SUBLETTE C
Solar/Wind Harmer
0.646
274764LEE CO EC;5U
Adder
5.655
274765LEE CO EC;6U
Adder
5.655
274762LEE CO EC;3U
Adder
5.641
274763LEE CO EC;4U
Adder
5.588
938861AE1-114 GEN
Solar/Wind Harmer
4.918
274879MINONK ;1U
Solar/Wind Harmer
3.958
274856ECOGROVE ;U1
Solar/Wind Harmer
1.964
276611AD2-172 GEN
Solar/Wind Harmer
1.491
958491AF2-143 GEN
Solar/Wind Harmer
8.515
971341AH1-150 GEN
Solar/Wind Harmer
11.298
971343AH1-151 GEN
Solar/Wind Harmer
11.298
971333AH1-146 GEN
Solar/Wind Harmer
10.95
971335AH1-147 GEN
Solar/Wind Harmer
10.95
942991AE2-321 GEN
Solar/Wind Harmer
5.351
274861TOP CROP ;1U
Solar/Wind Harmer
3.187
274862TOP CROP ;2U
Solar/Wind Harmer
2.661
958481AF2-142 GEN
Solar/Wind Harmer
7.873
970921AG2-575 GEN
Solar/Wind Harmer
5.247
970921AG2-575 GEN
Solar/Wind Harmer
1.22
962691AG1-118 GEN
Solar/Wind Harmer
15.589
274696ROCKY RD ;4P
Adder
5.712
274695ROCKY RD ;2P
Adder
5.58
274693ROCKY RD ;1P
Adder
5.525
274697ROCKY RD ;3P
Adder
1.516
274683WAUKEGAN ;8U
Adder
10.555
274683WAUKEGAN ;8U
Adder
8.897
274674JOLIET 9 ;6U
Adder
7.069
972259AH1-714 GEN
Adder
8.432
966841AG1-555 GEN
Solar/Wind Helper
1.639
971573AH1-285 GEN
Solar/Wind Harmer
2.377
942481AE2-261 GEN
Solar/Wind Harmer
45.14
276621W2-048 GEN
Solar/Wind Harmer
8.559
276838X2-022 GEN2
Solar/Wind Harmer
0.319
276686W4-005 GEN3
Solar/Wind Harmer
3.981
971993AH1-541 GEN
Solar/Wind Harmer
12.161
276668AB2-070 GEN1
Solar/Wind Harmer
2.943
274853TWINGROVE;U1
Solar/Wind Harmer
7.651
965091AG1-374 GEN
Solar/Wind Harmer
31.846
959611AF2-252 GEN
Solar/Wind Harmer
2.469
942111AE2-223 GEN
Solar/Wind Harmer
8.055
274878BISHOP HL;2U
Solar/Wind Harmer
2.507
965931AG1-462 GEN
Solar/Wind Harmer
17.802
970571AG2-364 GEN
Solar/Wind Harmer
13.357
276157O29GEN1
Solar/Wind Harmer
2.516
276889AE2-281 GEN
Solar/Wind Harmer
1.203
274858EASY ROAD;U2
Solar/Wind Harmer
2.906
274760LEE CO EC;1U
Adder
5.641
274767LEE CO EC;8U
Adder
5.575
972236AH1-702 GEN2
Adder
1.25
276805AD2-038 GEN
Solar/Wind Harmer
2.912
959091AF2-200 GEN
Solar/Wind Harmer
11.298
274855GSG-6 ;RU
Solar/Wind Harmer
2.042
274850MENDOTA H;RU
Solar/Wind Harmer
1.42
276602WESTBROOK C
Solar/Wind Harmer
1.176
276863AD2-134 GEN
Solar/Wind Harmer
0.988
276799AD1-013 GEN
Solar/Wind Harmer
1.218
946671AF1-331 GEN
Solar/Wind Harmer
0.231
274872LEEDK;1U
Solar/Wind Harmer
0.136
276694AA1-018 GEN2
Solar/Wind Harmer
3.312
274682WAUKEGAN ;7U
Adder
8.958
274729ELWOOD EC;1P
Adder
7.648
274730ELWOOD EC;6P
Adder
7.644
274734ELWOOD EC;8P
Adder
7.644
274736ELWOOD EC;9P
Adder
7.644
274676JOLIET 29;8U
Adder
13.167
972228AH1-698 GEN2
Adder
1.627
24755605MDL-5G
Solar/Wind Helper
0.551
944201AF1-088_MTX
Adder
0
991192J1610 G
External Queue
7.995254039764404
991267J1714
External Queue
15.754015922546387
991197J1626
External Queue
23.631025314331055
990272J1263 G
External Queue
61.94584655761719
990272J1263 G
External Queue
35.54114532470703
990353J1289
External Queue
8.001811027526855
991037J1464 G
External Queue
49.104148864746094
991082J1475 G
External Queue
39.36365509033203
990857J1408
External Queue
6.494697093963623
990857J1408
External Queue
3.5494277477264404
NYPJM->LTFIMP_NY
CLTF
0.248
WECLTFEXP_WEC->PJM
CLTF
2.141
CPLELTFEXP_CPLE->PJM
CLTF
0.987
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.027
CBM West 1LTFEXP_CBM-W1->PJM
CBM
62.089
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.334
MECLTFEXP_MEC->PJM
CLTF
13.464
SIGELTFEXP_SIGE->PJM
CLTF
0.076
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.616
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.49
LAGNLTFEXP_LAGN->PJM
CLTF
11.979
CBM South 2LTFEXP_CBM-S2->PJM
CBM
4.108
TVALTFEXP_TVA->PJM
CLTF
4.714

Details for 7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2_SRT-A


Base Case Flowgate

Area:AEP/AMIL
Facility Description:
7SNYDER-05SULLIVAN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.68 %
Rating:1635.0 MVA
Rating Type:B
MVA to Mitigate:1744.26
MW Contribution:7.08
Bus #Bus NameTypeMW Contribution
944221AF1-090 GEN
Solar/Wind Harmer
18.381
276785W4-005 GEN1
Solar/Wind Harmer
3.944
276174W4-005 GEN2
Solar/Wind Harmer
3.944
276849AB2-070 GEN2
Solar/Wind Harmer
2.916
276848AB2-070 GEN3
Solar/Wind Harmer
2.916
276655WTG1_EQ
Solar/Wind Harmer
8.578
276656WTG2_EQ
Solar/Wind Harmer
1.136
959341AF2-225 GEN
Solar/Wind Harmer
14.737
941731AE2-173 GEN
Solar/Wind Harmer
5.712
970169AG2-114 GEN
Solar/Wind Harmer
8.121
274848CAMPGROVE;RU
Solar/Wind Harmer
4.999
957751AF2-069 GEN
Solar/Wind Harmer
0.344
274863CRW1-WTG
Solar/Wind Harmer
4.175
274864CRW2-WTG
Solar/Wind Harmer
4.175
946321AF1-296 GEN
Solar/Wind Harmer
7.259
926823AC1-168 GEN
Solar/Wind Harmer
2.988
961011AF2-392 GEN
Solar/Wind Harmer
6.954
971681AH1-341 GEN
Solar/Wind Harmer
9.206
276868AE1-113 GEN
Solar/Wind Harmer
6.091
276882AE2-255 GEN
Solar/Wind Harmer
2.03
276612AE2-035 GEN
Solar/Wind Harmer
1.525
971171AH1-044 GEN
Solar/Wind Harmer
11.587
274823ROCKFORD ;21
Adder
11.275
971675AH1-338 GEN
Solar/Wind Harmer
10.21
971411AH1-196 GEN
Solar/Wind Harmer
8.392
971177AH1-047 GEN
Solar/Wind Harmer
3.235
274746AC1-111 G10
Adder
2.794
274744AC1-111 GEN8
Adder
2.794
274731ELWOOD EC;2P
Adder
7.989
274733ELWOOD EC;3P
Adder
7.989
274735ELWOOD EC;4P
Adder
7.989
274728ELWOOD EC;5P
Adder
7.985
274675JOLIET 29;7U
Adder
14.312
274675JOLIET 29;7U
Adder
13.801
972227AH1-698 GEN1
Adder
1.204
274687WILL CNTY;4U
Adder
12.867
274687WILL CNTY;4U
Adder
12.867
965911AG1-460 GEN
Solar/Wind Harmer
2.085
276615X2-022 GEN
Solar/Wind Harmer
2.662
963831AG1-236 GEN
Solar/Wind Harmer
12.95
274880W4-005 GEN4
Solar/Wind Harmer
3.944
972175AH1-670 GEN
Solar/Wind Harmer
16.245
274854TWINGROVE;U2
Solar/Wind Harmer
7.472
276726Z2-087_GEN
Solar/Wind Harmer
7.77
939741AE1-205 GEN
Solar/Wind Harmer
19.649
274877BISHOP HL;1U
Solar/Wind Harmer
2.533
970569AG2-363 GEN
Solar/Wind Harmer
20.389
939401AE1-172 GEN
Solar/Wind Harmer
9.47
276158O29GEN2
Solar/Wind Harmer
3.359
276876AE1-163_GEN2
Solar/Wind Harmer
4.304
971997AH1-543 GEN
Solar/Wind Harmer
9.857
274857EASY ROAD;U1
Solar/Wind Harmer
2.964
274761LEE CO EC;2U
Adder
5.755
274766LEE CO EC;7U
Adder
5.687
276901AD2-066 C O1
Solar/Wind Harmer
2.13
971475AH1-234 GEN
Solar/Wind Harmer
13.232
970819AG2-516 GEN
Solar/Wind Harmer
7.075
972235AH1-702 GEN1
Adder
1.473
957471AF2-041 GEN
Solar/Wind Harmer
17.381
959081AF2-199 GEN
Solar/Wind Harmer
5.794
971067AG2-660 GEN
Solar/Wind Harmer
1.347
274822ROCKFORD ;11
Adder
11.358
276861AD2-134 GEN
Solar/Wind Harmer
1.015
274872LEEDK;1U
Solar/Wind Harmer
4.49
276691AA1-018 GEN1
Solar/Wind Harmer
0.253
960751AF2-366 GEN
Solar/Wind Harmer
1.553
962781AG1-127 GEN
Solar/Wind Harmer
5.146
274828WAUKEGAN ;BP
Adder
5.73
274682WAUKEGAN ;7U
Adder
9.281
274745AC1-111 GEN9
Adder
2.794
274732ELWOOD EC;7P
Adder
7.985
274674JOLIET 9 ;6U
Adder
7.389
274676JOLIET 29;8U
Adder
14.313
274801UNIV PARK;4U
Adder
2.56
274650KINCAID ;1U
50/50
5.215
274651KINCAID ;2U
50/50
5.214
276916AD2-100_GEN
Solar/Wind Harmer
32.264
276911AD2-131_GEN
Solar/Wind Harmer
6.521
957381AF2-032 GEN
Solar/Wind Harmer
0.619
276763AC1-053 GEN1
Solar/Wind Harmer
5.206
276764AC1-053 GEN2
Solar/Wind Harmer
5.206
960611AF2-352 GEN
Solar/Wind Harmer
2.463
276782AC1-033 GEN
Solar/Wind Harmer
2.992
274851PROVIDENC;RU
Solar/Wind Harmer
2.131
274849CRESCENT ;1U
Solar/Wind Harmer
1.384
276645AC1-214 GEN1
Solar/Wind Harmer
1.002
276646AC1-214 GEN2
Solar/Wind Harmer
1.002
276741O09 GEN1
Solar/Wind Harmer
2.399
276708O09 GEN2
Solar/Wind Harmer
2.399
972267AH1-718 GEN
Adder
2.669
276872AE1-163_GEN1
Solar/Wind Harmer
4.304
276603SUBLETTE C
Solar/Wind Harmer
0.658
274764LEE CO EC;5U
Adder
5.768
274765LEE CO EC;6U
Adder
5.768
274762LEE CO EC;3U
Adder
5.755
274763LEE CO EC;4U
Adder
5.701
938861AE1-114 GEN
Solar/Wind Harmer
5.021
274879MINONK ;1U
Solar/Wind Harmer
4.061
274856ECOGROVE ;U1
Solar/Wind Harmer
2.01
276611AD2-172 GEN
Solar/Wind Harmer
1.525
958491AF2-143 GEN
Solar/Wind Harmer
8.76
971341AH1-150 GEN
Solar/Wind Harmer
11.587
971343AH1-151 GEN
Solar/Wind Harmer
11.587
971333AH1-146 GEN
Solar/Wind Harmer
11.255
971335AH1-147 GEN
Solar/Wind Harmer
11.255
942991AE2-321 GEN
Solar/Wind Harmer
5.51
274861TOP CROP ;1U
Solar/Wind Harmer
3.297
274862TOP CROP ;2U
Solar/Wind Harmer
2.753
958481AF2-142 GEN
Solar/Wind Harmer
8.147
970921AG2-575 GEN
Solar/Wind Harmer
5.412
970921AG2-575 GEN
Solar/Wind Harmer
1.258
962691AG1-118 GEN
Solar/Wind Harmer
16.092
274696ROCKY RD ;4P
Adder
5.916
274695ROCKY RD ;2P
Adder
5.778
274693ROCKY RD ;1P
Adder
5.721
274697ROCKY RD ;3P
Adder
1.57
274683WAUKEGAN ;8U
Adder
10.932
274683WAUKEGAN ;8U
Adder
9.215
274674JOLIET 9 ;6U
Adder
7.389
972259AH1-714 GEN
Adder
8.837
971573AH1-285 GEN
Solar/Wind Harmer
2.466
942481AE2-261 GEN
Solar/Wind Harmer
44.672
276621W2-048 GEN
Solar/Wind Harmer
8.479
276838X2-022 GEN2
Solar/Wind Harmer
0.316
276686W4-005 GEN3
Solar/Wind Harmer
3.944
971993AH1-541 GEN
Solar/Wind Harmer
12.049
276668AB2-070 GEN1
Solar/Wind Harmer
2.916
274853TWINGROVE;U1
Solar/Wind Harmer
7.632
965091AG1-374 GEN
Solar/Wind Harmer
31.766
959611AF2-252 GEN
Solar/Wind Harmer
2.463
942111AE2-223 GEN
Solar/Wind Harmer
8.054
274878BISHOP HL;2U
Solar/Wind Harmer
2.533
965931AG1-462 GEN
Solar/Wind Harmer
17.988
970571AG2-364 GEN
Solar/Wind Harmer
13.593
276157O29GEN1
Solar/Wind Harmer
2.555
276889AE2-281 GEN
Solar/Wind Harmer
1.23
274858EASY ROAD;U2
Solar/Wind Harmer
2.964
274760LEE CO EC;1U
Adder
5.755
274767LEE CO EC;8U
Adder
5.687
972236AH1-702 GEN2
Adder
1.281
276805AD2-038 GEN
Solar/Wind Harmer
2.996
959091AF2-200 GEN
Solar/Wind Harmer
11.587
274855GSG-6 ;RU
Solar/Wind Harmer
2.098
274850MENDOTA H;RU
Solar/Wind Harmer
1.459
276602WESTBROOK C
Solar/Wind Harmer
1.208
276863AD2-134 GEN
Solar/Wind Harmer
1.015
276799AD1-013 GEN
Solar/Wind Harmer
1.252
946671AF1-331 GEN
Solar/Wind Harmer
0.237
274872LEEDK;1U
Solar/Wind Harmer
0.14
276694AA1-018 GEN2
Solar/Wind Harmer
3.428
274682WAUKEGAN ;7U
Adder
9.281
274729ELWOOD EC;1P
Adder
7.989
274730ELWOOD EC;6P
Adder
7.985
274734ELWOOD EC;8P
Adder
7.985
274736ELWOOD EC;9P
Adder
7.985
274676JOLIET 29;8U
Adder
13.802
972228AH1-698 GEN2
Adder
1.709
274800UNIV PARK;3U
Adder
2.56
972038AH1-567 GEN2
Adder
0.16
944201AF1-088_MTX
Adder
0
991192J1610 G
External Queue
8.151901245117188
991267J1714
External Queue
15.901585578918457
991197J1626
External Queue
23.852378845214844
990272J1263 G
External Queue
61.82189178466797
990272J1263 G
External Queue
35.470027923583984
990353J1289
External Queue
8.188166618347168
991037J1464 G
External Queue
49.99164962768555
991082J1475 G
External Queue
40.654335021972656
990857J1408
External Queue
6.601410865783691
990857J1408
External Queue
3.607748031616211
NYPJM->LTFIMP_NY
CLTF
0.287
WECLTFEXP_WEC->PJM
CLTF
2.195
CPLELTFEXP_CPLE->PJM
CLTF
0.84
CBM West 2LTFEXP_CBM-W2->PJM
CBM
87.977
CBM West 1LTFEXP_CBM-W1->PJM
CBM
63.184
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.086
MECLTFEXP_MEC->PJM
CLTF
13.428
SIGELTFEXP_SIGE->PJM
CLTF
0.03
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.898
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.435
LAGNLTFEXP_LAGN->PJM
CLTF
11.491
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.636
TVALTFEXP_TVA->PJM
CLTF
4.419

Details for AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.63 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2183.5
MW Contribution:6.09
Bus #Bus NameTypeMW Contribution
972227AH1-698 GEN1
50/50
4.199
274863CRW1-WTG
Solar/Wind Harmer
12.028
274864CRW2-WTG
Solar/Wind Harmer
12.028
970169AG2-114 GEN
Solar/Wind Harmer
14.144
276655WTG1_EQ
Solar/Wind Harmer
12.263
276656WTG2_EQ
Solar/Wind Harmer
1.624
959341AF2-225 GEN
Solar/Wind Harmer
21.069
941731AE2-173 GEN
Solar/Wind Harmer
8.166
960591AF2-350 GEN
Solar/Wind Harmer
11.557
970833AG2-524 GEN
Solar/Wind Harmer
8.531
970833AG2-524 GEN
Solar/Wind Harmer
3.968
276785W4-005 GEN1
Solar/Wind Harmer
2.92
276174W4-005 GEN2
Solar/Wind Harmer
2.92
276849AB2-070 GEN2
Solar/Wind Harmer
2.11
276848AB2-070 GEN3
Solar/Wind Harmer
2.11
926823AC1-168 GEN
Solar/Wind Harmer
3.236
957751AF2-069 GEN
Solar/Wind Harmer
0.292
944221AF1-090 GEN
Solar/Wind Harmer
6.708
274655BRAIDWOOD;2U
50/50
10.821
941551AE2-152 GEN
Solar/Wind Harmer
12.186
939401AE1-172 GEN
Solar/Wind Harmer
34.481
276726Z2-087_GEN
Solar/Wind Harmer
11.109
939741AE1-205 GEN
Solar/Wind Harmer
28.092
274854TWINGROVE;U2
Solar/Wind Harmer
9.289
276776AD2-060 GEN
Solar/Wind Harmer
0.489
972175AH1-670 GEN
Solar/Wind Harmer
15.441
274871GR RIDGE ;2U
Solar/Wind Harmer
8.22
274880W4-005 GEN4
Solar/Wind Harmer
2.92
963831AG1-236 GEN
Solar/Wind Harmer
8.98
276615X2-022 GEN
Solar/Wind Harmer
1.683
965911AG1-460 GEN
Solar/Wind Harmer
1.01
276901AD2-066 C O1
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
2.039
274801UNIV PARK;4U
Adder
3.339
971997AH1-543 GEN
Solar/Wind Harmer
8.922
274674JOLIET 9 ;6U
Adder
8.705
274745AC1-111 GEN9
Adder
3.123
274872LEEDK;1U
Solar/Wind Harmer
4.562
960751AF2-366 GEN
Solar/Wind Harmer
1.59
962781AG1-127 GEN
Solar/Wind Harmer
5.271
276861AD2-134 GEN
Solar/Wind Harmer
0.977
276158O29GEN2
Solar/Wind Harmer
2.709
957471AF2-041 GEN
Solar/Wind Harmer
15.843
959081AF2-199 GEN
Solar/Wind Harmer
5.281
971067AG2-660 GEN
Solar/Wind Harmer
1.228
274857EASY ROAD;U1
Solar/Wind Harmer
2.462
274761LEE CO EC;2U
Adder
4.78
274766LEE CO EC;7U
Adder
4.724
972235AH1-702 GEN1
Adder
1.287
274822ROCKFORD ;11
Adder
9.983
970819AG2-516 GEN
Solar/Wind Harmer
6.091
971475AH1-234 GEN
Solar/Wind Harmer
11.229
274828WAUKEGAN ;BP
Adder
5.079
274682WAUKEGAN ;7U
Adder
8.253
970569AG2-363 GEN
Solar/Wind Harmer
13.755
274661LASCO STA;2U
50/50
8.762
972259AH1-714 GEN
50/50
24.593
274660LASCO STA;1U
50/50
8.872
960611AF2-352 GEN
Solar/Wind Harmer
3.061
274888KELLY CRK;1U
Solar/Wind Harmer
6.823
274887GEN-1.85
Solar/Wind Harmer
6.16
276843GEN-1.7
Solar/Wind Harmer
0.663
958011AF2-095 GEN
Solar/Wind Harmer
16.642
274847GR RIDGE ;BU
Solar/Wind Harmer
5.407
276763AC1-053 GEN1
Solar/Wind Harmer
3.61
276764AC1-053 GEN2
Solar/Wind Harmer
3.61
957381AF2-032 GEN
Solar/Wind Harmer
0.307
276916AD2-100_GEN
Solar/Wind Harmer
14.677
276911AD2-131_GEN
Solar/Wind Harmer
2.966
274851PROVIDENC;RU
Solar/Wind Harmer
1.809
274849CRESCENT ;1U
Solar/Wind Harmer
1.174
276645AC1-214 GEN1
Solar/Wind Harmer
0.851
276646AC1-214 GEN2
Solar/Wind Harmer
0.851
276782AC1-033 GEN
Solar/Wind Harmer
2.409
971573AH1-285 GEN
Solar/Wind Harmer
5.162
274674JOLIET 9 ;6U
Adder
8.705
962691AG1-118 GEN
Solar/Wind Harmer
16.679
970921AG2-575 GEN
Solar/Wind Harmer
5.543
970921AG2-575 GEN
Solar/Wind Harmer
1.289
276741O09 GEN1
Solar/Wind Harmer
1.935
276708O09 GEN2
Solar/Wind Harmer
1.935
971341AH1-150 GEN
Solar/Wind Harmer
10.562
971343AH1-151 GEN
Solar/Wind Harmer
10.562
276603SUBLETTE C
Solar/Wind Harmer
0.55
274695ROCKY RD ;2P
Adder
5.767
274693ROCKY RD ;1P
Adder
5.711
274697ROCKY RD ;3P
Adder
1.567
274696ROCKY RD ;4P
Adder
5.901
274803UNIV PARK;6U
Adder
3.016
971333AH1-146 GEN
Solar/Wind Harmer
10.347
971335AH1-147 GEN
Solar/Wind Harmer
10.347
938861AE1-114 GEN
Solar/Wind Harmer
4.24
972267AH1-718 GEN
Adder
2.148
274764LEE CO EC;5U
Adder
4.792
274765LEE CO EC;6U
Adder
4.792
274762LEE CO EC;3U
Adder
4.78
274763LEE CO EC;4U
Adder
4.735
274856ECOGROVE ;U1
Solar/Wind Harmer
1.725
276611AD2-172 GEN
Solar/Wind Harmer
1.309
942991AE2-321 GEN
Solar/Wind Harmer
5.068
274683WAUKEGAN ;8U
Adder
9.689
274683WAUKEGAN ;8U
Adder
8.167
274879MINONK ;1U
Solar/Wind Harmer
2.973
274654BRAIDWOOD;1U
50/50
11.577
972228AH1-698 GEN2
50/50
5.924
276897AD1-100 C
Solar/Wind Harmer
77.973
939351AE1-166 GEN
Solar/Wind Harmer
15.932
942111AE2-223 GEN
Solar/Wind Harmer
11.514
274853TWINGROVE;U1
Solar/Wind Harmer
9.488
965091AG1-374 GEN
Solar/Wind Harmer
39.492
959611AF2-252 GEN
Solar/Wind Harmer
3.061
276772AC2-154 GEN
Solar/Wind Harmer
3.223
276806AD2-047 C O1
Solar/Wind Harmer
12.363
970941AG2-585 GEN
Solar/Wind Harmer
14.446
276686W4-005 GEN3
Solar/Wind Harmer
2.92
971993AH1-541 GEN
Solar/Wind Harmer
8.921
970707AG2-453 GEN
Solar/Wind Harmer
26.787
276668AB2-070 GEN1
Solar/Wind Harmer
2.11
276621W2-048 GEN
Solar/Wind Harmer
5.36
276838X2-022 GEN2
Solar/Wind Harmer
0.2
276893AG1-478 C
Solar/Wind Harmer
0.311
942481AE2-261 GEN
Solar/Wind Harmer
21.64
943121AE2-341 GEN
Solar/Wind Harmer
9.225
943591AF1-030 GEN
Solar/Wind Harmer
6.15
274878BISHOP HL;2U
Solar/Wind Harmer
2.039
274800UNIV PARK;3U
Adder
3.339
972038AH1-567 GEN2
Adder
0.209
274872LEEDK;1U
Solar/Wind Harmer
0.142
276799AD1-013 GEN
Solar/Wind Harmer
1.211
946671AF1-331 GEN
Solar/Wind Harmer
0.229
274855GSG-6 ;RU
Solar/Wind Harmer
2.021
274850MENDOTA H;RU
Solar/Wind Harmer
1.405
276602WESTBROOK C
Solar/Wind Harmer
1.163
276863AD2-134 GEN
Solar/Wind Harmer
0.977
276157O29GEN1
Solar/Wind Harmer
2.06
959091AF2-200 GEN
Solar/Wind Harmer
10.562
274802UNIV PARK;5U
Adder
3.016
274858EASY ROAD;U2
Solar/Wind Harmer
2.462
274760LEE CO EC;1U
Adder
4.78
274767LEE CO EC;8U
Adder
4.724
972236AH1-702 GEN2
Adder
1.119
965931AG1-462 GEN
Solar/Wind Harmer
12.818
274682WAUKEGAN ;7U
Adder
8.253
970571AG2-364 GEN
Solar/Wind Harmer
9.17
274848CAMPGROVE;RU
Solar/Wind Harmer
3.906
274746AC1-111 G10
Adder
3.123
274744AC1-111 GEN8
Adder
3.123
971675AH1-338 GEN
Solar/Wind Harmer
9.854
971171AH1-044 GEN
Solar/Wind Harmer
10.562
961011AF2-392 GEN
Solar/Wind Harmer
5.675
971681AH1-341 GEN
Solar/Wind Harmer
7.811
972037AH1-567 GEN1
Adder
0.095
276612AE2-035 GEN
Solar/Wind Harmer
1.309
274823ROCKFORD ;21
Adder
9.91
971177AH1-047 GEN
Solar/Wind Harmer
2.976
946321AF1-296 GEN
Solar/Wind Harmer
5.295
971411AH1-196 GEN
Solar/Wind Harmer
7.583
276868AE1-113 GEN
Solar/Wind Harmer
4.459
276882AE2-255 GEN
Solar/Wind Harmer
1.486
991192J1610 G
External Queue
4.609210014343262
991037J1464 G
External Queue
12.641314506530762
990857J1408
External Queue
3.29262113571167
990857J1408
External Queue
1.7994558811187744
NYPJM->LTFIMP_NY
CLTF
0.692
WECLTFEXP_WEC->PJM
CLTF
1.783
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.768
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.202
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.796
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.04
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.143
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.317
LAGNLTFEXP_LAGN->PJM
CLTF
3.387
TVALTFEXP_TVA->PJM
CLTF
1.066

Details for AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.62 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2183.36
MW Contribution:6.09
Bus #Bus NameTypeMW Contribution
274654BRAIDWOOD;1U
50/50
11.577
972228AH1-698 GEN2
50/50
5.924
276897AD1-100 C
Solar/Wind Harmer
77.973
939351AE1-166 GEN
Solar/Wind Harmer
15.932
942111AE2-223 GEN
Solar/Wind Harmer
11.514
274853TWINGROVE;U1
Solar/Wind Harmer
9.488
965091AG1-374 GEN
Solar/Wind Harmer
39.492
959611AF2-252 GEN
Solar/Wind Harmer
3.061
276772AC2-154 GEN
Solar/Wind Harmer
3.223
276806AD2-047 C O1
Solar/Wind Harmer
12.363
970941AG2-585 GEN
Solar/Wind Harmer
14.446
276686W4-005 GEN3
Solar/Wind Harmer
2.92
971993AH1-541 GEN
Solar/Wind Harmer
8.921
970707AG2-453 GEN
Solar/Wind Harmer
26.787
276668AB2-070 GEN1
Solar/Wind Harmer
2.11
276621W2-048 GEN
Solar/Wind Harmer
5.36
276838X2-022 GEN2
Solar/Wind Harmer
0.2
276893AG1-478 C
Solar/Wind Harmer
0.311
942481AE2-261 GEN
Solar/Wind Harmer
21.64
943121AE2-341 GEN
Solar/Wind Harmer
9.225
943591AF1-030 GEN
Solar/Wind Harmer
6.15
274878BISHOP HL;2U
Solar/Wind Harmer
2.039
274800UNIV PARK;3U
Adder
3.339
972038AH1-567 GEN2
Adder
0.209
274872LEEDK;1U
Solar/Wind Harmer
0.142
276799AD1-013 GEN
Solar/Wind Harmer
1.211
946671AF1-331 GEN
Solar/Wind Harmer
0.229
274855GSG-6 ;RU
Solar/Wind Harmer
2.021
274850MENDOTA H;RU
Solar/Wind Harmer
1.405
276602WESTBROOK C
Solar/Wind Harmer
1.163
276863AD2-134 GEN
Solar/Wind Harmer
0.977
276157O29GEN1
Solar/Wind Harmer
2.06
959091AF2-200 GEN
Solar/Wind Harmer
10.562
274802UNIV PARK;5U
Adder
3.016
274858EASY ROAD;U2
Solar/Wind Harmer
2.462
274760LEE CO EC;1U
Adder
4.78
274767LEE CO EC;8U
Adder
4.724
972236AH1-702 GEN2
Adder
1.119
965931AG1-462 GEN
Solar/Wind Harmer
12.818
274682WAUKEGAN ;7U
Adder
8.253
970571AG2-364 GEN
Solar/Wind Harmer
9.17
274661LASCO STA;2U
50/50
8.762
972259AH1-714 GEN
50/50
24.593
274660LASCO STA;1U
50/50
8.872
960611AF2-352 GEN
Solar/Wind Harmer
3.061
274888KELLY CRK;1U
Solar/Wind Harmer
6.823
274887GEN-1.85
Solar/Wind Harmer
6.16
276843GEN-1.7
Solar/Wind Harmer
0.663
958011AF2-095 GEN
Solar/Wind Harmer
16.642
274847GR RIDGE ;BU
Solar/Wind Harmer
5.407
276763AC1-053 GEN1
Solar/Wind Harmer
3.61
274655BRAIDWOOD;2U
50/50
10.821
941551AE2-152 GEN
Solar/Wind Harmer
12.186
939401AE1-172 GEN
Solar/Wind Harmer
34.481
276726Z2-087_GEN
Solar/Wind Harmer
11.109
939741AE1-205 GEN
Solar/Wind Harmer
28.092
274854TWINGROVE;U2
Solar/Wind Harmer
9.289
276776AD2-060 GEN
Solar/Wind Harmer
0.489
972175AH1-670 GEN
Solar/Wind Harmer
15.441
274871GR RIDGE ;2U
Solar/Wind Harmer
8.22
274880W4-005 GEN4
Solar/Wind Harmer
2.92
963831AG1-236 GEN
Solar/Wind Harmer
8.98
276615X2-022 GEN
Solar/Wind Harmer
1.683
965911AG1-460 GEN
Solar/Wind Harmer
1.01
276901AD2-066 C O1
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
2.039
274801UNIV PARK;4U
Adder
3.339
971997AH1-543 GEN
Solar/Wind Harmer
8.922
274674JOLIET 9 ;6U
Adder
8.705
274745AC1-111 GEN9
Adder
3.123
274872LEEDK;1U
Solar/Wind Harmer
4.562
960751AF2-366 GEN
Solar/Wind Harmer
1.59
962781AG1-127 GEN
Solar/Wind Harmer
5.271
276861AD2-134 GEN
Solar/Wind Harmer
0.977
276158O29GEN2
Solar/Wind Harmer
2.709
957471AF2-041 GEN
Solar/Wind Harmer
15.843
959081AF2-199 GEN
Solar/Wind Harmer
5.281
971067AG2-660 GEN
Solar/Wind Harmer
1.228
274857EASY ROAD;U1
Solar/Wind Harmer
2.462
274761LEE CO EC;2U
Adder
4.78
274766LEE CO EC;7U
Adder
4.724
972235AH1-702 GEN1
Adder
1.287
274822ROCKFORD ;11
Adder
9.983
970819AG2-516 GEN
Solar/Wind Harmer
6.091
971475AH1-234 GEN
Solar/Wind Harmer
11.229
274828WAUKEGAN ;BP
Adder
5.079
274682WAUKEGAN ;7U
Adder
8.253
970569AG2-363 GEN
Solar/Wind Harmer
13.755
276764AC1-053 GEN2
Solar/Wind Harmer
3.61
957381AF2-032 GEN
Solar/Wind Harmer
0.307
276916AD2-100_GEN
Solar/Wind Harmer
14.677
276911AD2-131_GEN
Solar/Wind Harmer
2.966
274851PROVIDENC;RU
Solar/Wind Harmer
1.809
274849CRESCENT ;1U
Solar/Wind Harmer
1.174
276645AC1-214 GEN1
Solar/Wind Harmer
0.851
276646AC1-214 GEN2
Solar/Wind Harmer
0.851
276782AC1-033 GEN
Solar/Wind Harmer
2.409
971573AH1-285 GEN
Solar/Wind Harmer
5.162
274674JOLIET 9 ;6U
Adder
8.705
962691AG1-118 GEN
Solar/Wind Harmer
16.679
970921AG2-575 GEN
Solar/Wind Harmer
5.543
970921AG2-575 GEN
Solar/Wind Harmer
1.289
276741O09 GEN1
Solar/Wind Harmer
1.935
276708O09 GEN2
Solar/Wind Harmer
1.935
971341AH1-150 GEN
Solar/Wind Harmer
10.562
971343AH1-151 GEN
Solar/Wind Harmer
10.562
276603SUBLETTE C
Solar/Wind Harmer
0.55
274695ROCKY RD ;2P
Adder
5.767
274693ROCKY RD ;1P
Adder
5.711
274697ROCKY RD ;3P
Adder
1.567
274696ROCKY RD ;4P
Adder
5.901
274803UNIV PARK;6U
Adder
3.016
971333AH1-146 GEN
Solar/Wind Harmer
10.347
971335AH1-147 GEN
Solar/Wind Harmer
10.347
938861AE1-114 GEN
Solar/Wind Harmer
4.24
972267AH1-718 GEN
Adder
2.148
274764LEE CO EC;5U
Adder
4.792
274765LEE CO EC;6U
Adder
4.792
274762LEE CO EC;3U
Adder
4.78
274763LEE CO EC;4U
Adder
4.735
274856ECOGROVE ;U1
Solar/Wind Harmer
1.725
276611AD2-172 GEN
Solar/Wind Harmer
1.309
942991AE2-321 GEN
Solar/Wind Harmer
5.068
274683WAUKEGAN ;8U
Adder
9.689
274683WAUKEGAN ;8U
Adder
8.167
274879MINONK ;1U
Solar/Wind Harmer
2.973
972227AH1-698 GEN1
50/50
4.199
274863CRW1-WTG
Solar/Wind Harmer
12.028
274864CRW2-WTG
Solar/Wind Harmer
12.028
970169AG2-114 GEN
Solar/Wind Harmer
14.144
276655WTG1_EQ
Solar/Wind Harmer
12.263
276656WTG2_EQ
Solar/Wind Harmer
1.624
959341AF2-225 GEN
Solar/Wind Harmer
21.069
941731AE2-173 GEN
Solar/Wind Harmer
8.166
960591AF2-350 GEN
Solar/Wind Harmer
11.557
970833AG2-524 GEN
Solar/Wind Harmer
8.531
970833AG2-524 GEN
Solar/Wind Harmer
3.968
276785W4-005 GEN1
Solar/Wind Harmer
2.92
276174W4-005 GEN2
Solar/Wind Harmer
2.92
276849AB2-070 GEN2
Solar/Wind Harmer
2.11
276848AB2-070 GEN3
Solar/Wind Harmer
2.11
926823AC1-168 GEN
Solar/Wind Harmer
3.236
957751AF2-069 GEN
Solar/Wind Harmer
0.292
944221AF1-090 GEN
Solar/Wind Harmer
6.708
274848CAMPGROVE;RU
Solar/Wind Harmer
3.906
274746AC1-111 G10
Adder
3.123
274744AC1-111 GEN8
Adder
3.123
971675AH1-338 GEN
Solar/Wind Harmer
9.854
971171AH1-044 GEN
Solar/Wind Harmer
10.562
961011AF2-392 GEN
Solar/Wind Harmer
5.675
971681AH1-341 GEN
Solar/Wind Harmer
7.811
972037AH1-567 GEN1
Adder
0.095
276612AE2-035 GEN
Solar/Wind Harmer
1.309
274823ROCKFORD ;21
Adder
9.91
971177AH1-047 GEN
Solar/Wind Harmer
2.976
946321AF1-296 GEN
Solar/Wind Harmer
5.295
971411AH1-196 GEN
Solar/Wind Harmer
7.583
276868AE1-113 GEN
Solar/Wind Harmer
4.459
276882AE2-255 GEN
Solar/Wind Harmer
1.486
991192J1610 G
External Queue
4.609210014343262
991037J1464 G
External Queue
12.641314506530762
990857J1408
External Queue
3.29262113571167
990857J1408
External Queue
1.7994558811187744
NYPJM->LTFIMP_NY
CLTF
0.692
WECLTFEXP_WEC->PJM
CLTF
1.783
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.768
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.202
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.796
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.04
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.143
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.317
LAGNLTFEXP_LAGN->PJM
CLTF
3.387
TVALTFEXP_TVA->PJM
CLTF
1.066

Details for AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AD1-100 TAP1-WILTON ; B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.57 %
Rating:2107.0 MVA
Rating Type:STE
MVA to Mitigate:2182.3
MW Contribution:6.09
Bus #Bus NameTypeMW Contribution
274655BRAIDWOOD;2U
50/50
10.821
941551AE2-152 GEN
Solar/Wind Harmer
12.186
939401AE1-172 GEN
Solar/Wind Harmer
34.481
276726Z2-087_GEN
Solar/Wind Harmer
11.109
939741AE1-205 GEN
Solar/Wind Harmer
28.092
274854TWINGROVE;U2
Solar/Wind Harmer
9.289
276776AD2-060 GEN
Solar/Wind Harmer
0.489
972175AH1-670 GEN
Solar/Wind Harmer
15.441
274871GR RIDGE ;2U
Solar/Wind Harmer
8.22
274880W4-005 GEN4
Solar/Wind Harmer
2.92
963831AG1-236 GEN
Solar/Wind Harmer
8.98
276615X2-022 GEN
Solar/Wind Harmer
1.683
965911AG1-460 GEN
Solar/Wind Harmer
1.01
276901AD2-066 C O1
Solar/Wind Harmer
2.171
274877BISHOP HL;1U
Solar/Wind Harmer
2.039
274801UNIV PARK;4U
Adder
3.339
971997AH1-543 GEN
Solar/Wind Harmer
8.922
274674JOLIET 9 ;6U
Adder
8.705
274745AC1-111 GEN9
Adder
3.123
274872LEEDK;1U
Solar/Wind Harmer
4.562
960751AF2-366 GEN
Solar/Wind Harmer
1.59
962781AG1-127 GEN
Solar/Wind Harmer
5.271
276861AD2-134 GEN
Solar/Wind Harmer
0.977
276158O29GEN2
Solar/Wind Harmer
2.709
957471AF2-041 GEN
Solar/Wind Harmer
15.843
959081AF2-199 GEN
Solar/Wind Harmer
5.281
971067AG2-660 GEN
Solar/Wind Harmer
1.228
274857EASY ROAD;U1
Solar/Wind Harmer
2.462
274761LEE CO EC;2U
Adder
4.78
274766LEE CO EC;7U
Adder
4.724
972235AH1-702 GEN1
Adder
1.287
274822ROCKFORD ;11
Adder
9.983
970819AG2-516 GEN
Solar/Wind Harmer
6.091
971475AH1-234 GEN
Solar/Wind Harmer
11.229
274828WAUKEGAN ;BP
Adder
5.079
274682WAUKEGAN ;7U
Adder
8.253
970569AG2-363 GEN
Solar/Wind Harmer
13.755
972227AH1-698 GEN1
50/50
4.199
274863CRW1-WTG
Solar/Wind Harmer
12.028
274864CRW2-WTG
Solar/Wind Harmer
12.028
970169AG2-114 GEN
Solar/Wind Harmer
14.144
276655WTG1_EQ
Solar/Wind Harmer
12.263
276656WTG2_EQ
Solar/Wind Harmer
1.624
959341AF2-225 GEN
Solar/Wind Harmer
21.069
941731AE2-173 GEN
Solar/Wind Harmer
8.166
960591AF2-350 GEN
Solar/Wind Harmer
11.557
970833AG2-524 GEN
Solar/Wind Harmer
8.531
970833AG2-524 GEN
Solar/Wind Harmer
3.968
276785W4-005 GEN1
Solar/Wind Harmer
2.92
276174W4-005 GEN2
Solar/Wind Harmer
2.92
276849AB2-070 GEN2
Solar/Wind Harmer
2.11
276848AB2-070 GEN3
Solar/Wind Harmer
2.11
926823AC1-168 GEN
Solar/Wind Harmer
3.236
957751AF2-069 GEN
Solar/Wind Harmer
0.292
944221AF1-090 GEN
Solar/Wind Harmer
6.708
274848CAMPGROVE;RU
Solar/Wind Harmer
3.906
274746AC1-111 G10
Adder
3.123
274744AC1-111 GEN8
Adder
3.123
971675AH1-338 GEN
Solar/Wind Harmer
9.854
971171AH1-044 GEN
Solar/Wind Harmer
10.562
961011AF2-392 GEN
Solar/Wind Harmer
5.675
971681AH1-341 GEN
Solar/Wind Harmer
7.811
972037AH1-567 GEN1
Adder
0.095
276612AE2-035 GEN
Solar/Wind Harmer
1.309
274823ROCKFORD ;21
Adder
9.91
971177AH1-047 GEN
Solar/Wind Harmer
2.976
946321AF1-296 GEN
Solar/Wind Harmer
5.295
971411AH1-196 GEN
Solar/Wind Harmer
7.583
276868AE1-113 GEN
Solar/Wind Harmer
4.459
276882AE2-255 GEN
Solar/Wind Harmer
1.486
274661LASCO STA;2U
50/50
8.762
972259AH1-714 GEN
50/50
24.593
274660LASCO STA;1U
50/50
8.872
960611AF2-352 GEN
Solar/Wind Harmer
3.061
274888KELLY CRK;1U
Solar/Wind Harmer
6.823
274887GEN-1.85
Solar/Wind Harmer
6.16
276843GEN-1.7
Solar/Wind Harmer
0.663
958011AF2-095 GEN
Solar/Wind Harmer
16.642
274847GR RIDGE ;BU
Solar/Wind Harmer
5.407
276763AC1-053 GEN1
Solar/Wind Harmer
3.61
276764AC1-053 GEN2
Solar/Wind Harmer
3.61
957381AF2-032 GEN
Solar/Wind Harmer
0.307
276916AD2-100_GEN
Solar/Wind Harmer
14.677
276911AD2-131_GEN
Solar/Wind Harmer
2.966
274851PROVIDENC;RU
Solar/Wind Harmer
1.809
274849CRESCENT ;1U
Solar/Wind Harmer
1.174
276645AC1-214 GEN1
Solar/Wind Harmer
0.851
276646AC1-214 GEN2
Solar/Wind Harmer
0.851
276782AC1-033 GEN
Solar/Wind Harmer
2.409
971573AH1-285 GEN
Solar/Wind Harmer
5.162
274674JOLIET 9 ;6U
Adder
8.705
962691AG1-118 GEN
Solar/Wind Harmer
16.679
970921AG2-575 GEN
Solar/Wind Harmer
5.543
970921AG2-575 GEN
Solar/Wind Harmer
1.289
276741O09 GEN1
Solar/Wind Harmer
1.935
276708O09 GEN2
Solar/Wind Harmer
1.935
971341AH1-150 GEN
Solar/Wind Harmer
10.562
971343AH1-151 GEN
Solar/Wind Harmer
10.562
276603SUBLETTE C
Solar/Wind Harmer
0.55
274695ROCKY RD ;2P
Adder
5.767
274693ROCKY RD ;1P
Adder
5.711
274697ROCKY RD ;3P
Adder
1.567
274696ROCKY RD ;4P
Adder
5.901
274803UNIV PARK;6U
Adder
3.016
971333AH1-146 GEN
Solar/Wind Harmer
10.347
971335AH1-147 GEN
Solar/Wind Harmer
10.347
938861AE1-114 GEN
Solar/Wind Harmer
4.24
972267AH1-718 GEN
Adder
2.148
274764LEE CO EC;5U
Adder
4.792
274765LEE CO EC;6U
Adder
4.792
274762LEE CO EC;3U
Adder
4.78
274763LEE CO EC;4U
Adder
4.735
274856ECOGROVE ;U1
Solar/Wind Harmer
1.725
276611AD2-172 GEN
Solar/Wind Harmer
1.309
942991AE2-321 GEN
Solar/Wind Harmer
5.068
274683WAUKEGAN ;8U
Adder
9.689
274683WAUKEGAN ;8U
Adder
8.167
274879MINONK ;1U
Solar/Wind Harmer
2.973
274654BRAIDWOOD;1U
50/50
11.577
972228AH1-698 GEN2
50/50
5.924
276897AD1-100 C
Solar/Wind Harmer
77.973
939351AE1-166 GEN
Solar/Wind Harmer
15.932
942111AE2-223 GEN
Solar/Wind Harmer
11.514
274853TWINGROVE;U1
Solar/Wind Harmer
9.488
965091AG1-374 GEN
Solar/Wind Harmer
39.492
959611AF2-252 GEN
Solar/Wind Harmer
3.061
276772AC2-154 GEN
Solar/Wind Harmer
3.223
276806AD2-047 C O1
Solar/Wind Harmer
12.363
970941AG2-585 GEN
Solar/Wind Harmer
14.446
276686W4-005 GEN3
Solar/Wind Harmer
2.92
971993AH1-541 GEN
Solar/Wind Harmer
8.921
970707AG2-453 GEN
Solar/Wind Harmer
26.787
276668AB2-070 GEN1
Solar/Wind Harmer
2.11
276621W2-048 GEN
Solar/Wind Harmer
5.36
276838X2-022 GEN2
Solar/Wind Harmer
0.2
276893AG1-478 C
Solar/Wind Harmer
0.311
942481AE2-261 GEN
Solar/Wind Harmer
21.64
943121AE2-341 GEN
Solar/Wind Harmer
9.225
943591AF1-030 GEN
Solar/Wind Harmer
6.15
274878BISHOP HL;2U
Solar/Wind Harmer
2.039
274800UNIV PARK;3U
Adder
3.339
972038AH1-567 GEN2
Adder
0.209
274872LEEDK;1U
Solar/Wind Harmer
0.142
276799AD1-013 GEN
Solar/Wind Harmer
1.211
946671AF1-331 GEN
Solar/Wind Harmer
0.229
274855GSG-6 ;RU
Solar/Wind Harmer
2.021
274850MENDOTA H;RU
Solar/Wind Harmer
1.405
276602WESTBROOK C
Solar/Wind Harmer
1.163
276863AD2-134 GEN
Solar/Wind Harmer
0.977
276157O29GEN1
Solar/Wind Harmer
2.06
959091AF2-200 GEN
Solar/Wind Harmer
10.562
274802UNIV PARK;5U
Adder
3.016
274858EASY ROAD;U2
Solar/Wind Harmer
2.462
274760LEE CO EC;1U
Adder
4.78
274767LEE CO EC;8U
Adder
4.724
972236AH1-702 GEN2
Adder
1.119
965931AG1-462 GEN
Solar/Wind Harmer
12.818
274682WAUKEGAN ;7U
Adder
8.253
970571AG2-364 GEN
Solar/Wind Harmer
9.17
991192J1610 G
External Queue
4.609210014343262
991037J1464 G
External Queue
12.641314506530762
990857J1408
External Queue
3.29262113571167
990857J1408
External Queue
1.7994558811187744
NYPJM->LTFIMP_NY
CLTF
0.692
WECLTFEXP_WEC->PJM
CLTF
1.783
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.768
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.202
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.085
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.796
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.217
MECLTFEXP_MEC->PJM
CLTF
7.343
SIGELTFEXP_SIGE->PJM
CLTF
0.04
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.143
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.317
LAGNLTFEXP_LAGN->PJM
CLTF
3.387
TVALTFEXP_TVA->PJM
CLTF
1.066

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT5-8___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.91 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2147.61
MW Contribution:12.63
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
18.142
274766LEE CO EC;7U
50/50
17.928
971087AG2-675 GEN
50/50
6.084
957471AF2-041 GEN
Solar/Wind Harmer
140.233
959081AF2-199 GEN
Solar/Wind Harmer
46.744
971067AG2-660 GEN
Solar/Wind Harmer
10.871
274857EASY ROAD;U1
Solar/Wind Harmer
8.806
276158O29GEN2
Solar/Wind Harmer
8.506
972235AH1-702 GEN1
Adder
3.082
970819AG2-516 GEN
Solar/Wind Harmer
12.631
971475AH1-234 GEN
Solar/Wind Harmer
21.981
274822ROCKFORD ;11
Adder
18.224
274877BISHOP HL;1U
Solar/Wind Harmer
2.674
276861AD2-134 GEN
Solar/Wind Harmer
1.333
274715NELSON EC;1C
50/50
2.51
274716NELSON EC;1S
50/50
1.832
274760LEE CO EC;1U
50/50
18.142
274767LEE CO EC;8U
50/50
17.928
959091AF2-200 GEN
Solar/Wind Harmer
93.489
274858EASY ROAD;U2
Solar/Wind Harmer
8.806
276157O29GEN1
Solar/Wind Harmer
6.47
965931AG1-462 GEN
Solar/Wind Harmer
41.695
972236AH1-702 GEN2
Adder
2.671
274878BISHOP HL;2U
Solar/Wind Harmer
2.674
274855GSG-6 ;RU
Solar/Wind Harmer
2.756
274850MENDOTA H;RU
Solar/Wind Harmer
1.916
276602WESTBROOK C
Solar/Wind Harmer
1.586
276863AD2-134 GEN
Solar/Wind Harmer
1.333
276799AD1-013 GEN
Solar/Wind Harmer
1.587
946671AF1-331 GEN
Solar/Wind Harmer
0.301
274717NELSON EC;2C
50/50
2.51
274718NELSON EC;2S
50/50
1.832
972267AH1-718 GEN
50/50
9.905
274764LEE CO EC;5U
50/50
18.185
971171AH1-044 GEN
Solar/Wind Harmer
93.489
961011AF2-392 GEN
Solar/Wind Harmer
21.136
946321AF1-296 GEN
Solar/Wind Harmer
16.776
971681AH1-341 GEN
Solar/Wind Harmer
22.439
276612AE2-035 GEN
Solar/Wind Harmer
3.01
274823ROCKFORD ;21
Adder
18.094
971675AH1-338 GEN
Solar/Wind Harmer
13.203
274848CAMPGROVE;RU
Solar/Wind Harmer
4.538
971411AH1-196 GEN
Solar/Wind Harmer
9.686
957751AF2-069 GEN
Solar/Wind Harmer
0.295
971177AH1-047 GEN
Solar/Wind Harmer
2.75
274765LEE CO EC;6U
50/50
18.185
274762LEE CO EC;3U
50/50
18.142
274763LEE CO EC;4U
50/50
17.971
971341AH1-150 GEN
Solar/Wind Harmer
93.489
971343AH1-151 GEN
Solar/Wind Harmer
93.489
276603SUBLETTE C
Solar/Wind Harmer
1.79
276741O09 GEN1
Solar/Wind Harmer
6.076
276708O09 GEN2
Solar/Wind Harmer
6.076
938861AE1-114 GEN
Solar/Wind Harmer
11.981
971333AH1-146 GEN
Solar/Wind Harmer
24.433
971335AH1-147 GEN
Solar/Wind Harmer
24.433
274856ECOGROVE ;U1
Solar/Wind Harmer
3.967
276611AD2-172 GEN
Solar/Wind Harmer
3.01
276782AC1-033 GEN
Solar/Wind Harmer
3.161
274851PROVIDENC;RU
Solar/Wind Harmer
1.831
274849CRESCENT ;1U
Solar/Wind Harmer
1.189
276645AC1-214 GEN1
Solar/Wind Harmer
0.861
276646AC1-214 GEN2
Solar/Wind Harmer
0.861
942991AE2-321 GEN
Solar/Wind Harmer
4.451
990512J1326
External Queue
4.585575580596924
990117J1214
External Queue
15.774378776550293
990727J1377 G
External Queue
5.941872596740723
991092J1477
External Queue
5.850008010864258
990407J1304
External Queue
3.37416672706604
NYPJM->LTFIMP_NY
CLTF
0.233
WECLTFEXP_WEC->PJM
CLTF
1.067
CPLELTFEXP_CPLE->PJM
CLTF
0.155
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.368
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.835
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.728
MECLTFEXP_MEC->PJM
CLTF
13.927
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.08
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.184
LAGNLTFEXP_LAGN->PJM
CLTF
4.253
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.881
TVALTFEXP_TVA->PJM
CLTF
1.218

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT7-8___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2127.56
MW Contribution:12.54
Bus #Bus NameTypeMW Contribution
274717NELSON EC;2C
50/50
2.518
274718NELSON EC;2S
50/50
1.839
972267AH1-718 GEN
50/50
9.941
274764LEE CO EC;5U
50/50
18.199
274765LEE CO EC;6U
50/50
18.199
274762LEE CO EC;3U
50/50
18.157
274763LEE CO EC;4U
50/50
17.986
971341AH1-150 GEN
Solar/Wind Harmer
94.055
971343AH1-151 GEN
Solar/Wind Harmer
94.055
276603SUBLETTE C
Solar/Wind Harmer
1.796
276741O09 GEN1
Solar/Wind Harmer
6.097
276708O09 GEN2
Solar/Wind Harmer
6.097
938861AE1-114 GEN
Solar/Wind Harmer
11.979
971333AH1-146 GEN
Solar/Wind Harmer
24.264
971335AH1-147 GEN
Solar/Wind Harmer
24.264
274856ECOGROVE ;U1
Solar/Wind Harmer
3.948
276611AD2-172 GEN
Solar/Wind Harmer
2.996
276782AC1-033 GEN
Solar/Wind Harmer
3.172
274851PROVIDENC;RU
Solar/Wind Harmer
1.838
274849CRESCENT ;1U
Solar/Wind Harmer
1.193
276645AC1-214 GEN1
Solar/Wind Harmer
0.865
276646AC1-214 GEN2
Solar/Wind Harmer
0.865
942991AE2-321 GEN
Solar/Wind Harmer
4.339
971171AH1-044 GEN
Solar/Wind Harmer
94.055
961011AF2-392 GEN
Solar/Wind Harmer
21.205
946321AF1-296 GEN
Solar/Wind Harmer
16.837
971681AH1-341 GEN
Solar/Wind Harmer
22.448
276612AE2-035 GEN
Solar/Wind Harmer
2.996
274823ROCKFORD ;21
Adder
17.883
971675AH1-338 GEN
Solar/Wind Harmer
13.36
274848CAMPGROVE;RU
Solar/Wind Harmer
4.554
957751AF2-069 GEN
Solar/Wind Harmer
0.296
971411AH1-196 GEN
Solar/Wind Harmer
9.2
971177AH1-047 GEN
Solar/Wind Harmer
2.685
274761LEE CO EC;2U
50/50
18.157
274766LEE CO EC;7U
50/50
17.943
971087AG2-675 GEN
50/50
6.107
957471AF2-041 GEN
Solar/Wind Harmer
141.082
959081AF2-199 GEN
Solar/Wind Harmer
47.027
971067AG2-660 GEN
Solar/Wind Harmer
10.937
274857EASY ROAD;U1
Solar/Wind Harmer
8.814
276158O29GEN2
Solar/Wind Harmer
8.536
972235AH1-702 GEN1
Adder
3.06
970819AG2-516 GEN
Solar/Wind Harmer
12.543
971475AH1-234 GEN
Solar/Wind Harmer
21.831
274822ROCKFORD ;11
Adder
18.012
274877BISHOP HL;1U
Solar/Wind Harmer
2.683
276861AD2-134 GEN
Solar/Wind Harmer
1.348
274715NELSON EC;1C
50/50
2.518
274716NELSON EC;1S
50/50
1.839
274760LEE CO EC;1U
50/50
18.157
274767LEE CO EC;8U
50/50
17.943
959091AF2-200 GEN
Solar/Wind Harmer
94.055
274858EASY ROAD;U2
Solar/Wind Harmer
8.814
276157O29GEN1
Solar/Wind Harmer
6.493
965931AG1-462 GEN
Solar/Wind Harmer
41.852
972236AH1-702 GEN2
Adder
2.653
274878BISHOP HL;2U
Solar/Wind Harmer
2.683
274855GSG-6 ;RU
Solar/Wind Harmer
2.788
274850MENDOTA H;RU
Solar/Wind Harmer
1.938
276602WESTBROOK C
Solar/Wind Harmer
1.605
276863AD2-134 GEN
Solar/Wind Harmer
1.348
276799AD1-013 GEN
Solar/Wind Harmer
1.607
946671AF1-331 GEN
Solar/Wind Harmer
0.304
990512J1326
External Queue
4.566863536834717
990117J1214
External Queue
15.710009574890137
990727J1377 G
External Queue
5.881286144256592
991092J1477
External Queue
5.861337661743164
990407J1304
External Queue
3.351433038711548
NYPJM->LTFIMP_NY
CLTF
0.234
WECLTFEXP_WEC->PJM
CLTF
1.131
CPLELTFEXP_CPLE->PJM
CLTF
0.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.443
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.741
MECLTFEXP_MEC->PJM
CLTF
13.999
SIGELTFEXP_SIGE->PJM
CLTF
0.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.081
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.187
LAGNLTFEXP_LAGN->PJM
CLTF
4.271
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.884
TVALTFEXP_TVA->PJM
CLTF
1.223

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P4-6_006-345-BT78___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.12 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:2114.81
MW Contribution:11.0
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
19.958
274766LEE CO EC;7U
50/50
19.723
971087AG2-675 GEN
50/50
6.344
957471AF2-041 GEN
Solar/Wind Harmer
143.016
959081AF2-199 GEN
Solar/Wind Harmer
47.672
971067AG2-660 GEN
Solar/Wind Harmer
11.086
971171AH1-044 GEN
Solar/Wind Harmer
95.344
961011AF2-392 GEN
Solar/Wind Harmer
22.083
946321AF1-296 GEN
Solar/Wind Harmer
17.449
971681AH1-341 GEN
Solar/Wind Harmer
22.705
276612AE2-035 GEN
Solar/Wind Harmer
2.786
274823ROCKFORD ;21
Adder
15.745
971675AH1-338 GEN
Solar/Wind Harmer
13.539
274848CAMPGROVE;RU
Solar/Wind Harmer
4.753
957751AF2-069 GEN
Solar/Wind Harmer
0.31
971411AH1-196 GEN
Solar/Wind Harmer
8.046
274857EASY ROAD;U1
Solar/Wind Harmer
9.688
276158O29GEN2
Solar/Wind Harmer
8.906
972235AH1-702 GEN1
Adder
3.802
970819AG2-516 GEN
Solar/Wind Harmer
11.004
274877BISHOP HL;1U
Solar/Wind Harmer
2.8
274822ROCKFORD ;11
Adder
15.856
971475AH1-234 GEN
Solar/Wind Harmer
17.244
276861AD2-134 GEN
Solar/Wind Harmer
1.367
274717NELSON EC;2C
50/50
2.64
274718NELSON EC;2S
50/50
1.928
972267AH1-718 GEN
50/50
10.422
274764LEE CO EC;5U
50/50
20.005
274765LEE CO EC;6U
50/50
20.005
274762LEE CO EC;3U
50/50
19.958
274763LEE CO EC;4U
50/50
19.77
971341AH1-150 GEN
Solar/Wind Harmer
95.344
971343AH1-151 GEN
Solar/Wind Harmer
95.344
276741O09 GEN1
Solar/Wind Harmer
6.362
276708O09 GEN2
Solar/Wind Harmer
6.362
276603SUBLETTE C
Solar/Wind Harmer
1.853
938861AE1-114 GEN
Solar/Wind Harmer
11.873
274856ECOGROVE ;U1
Solar/Wind Harmer
3.671
276611AD2-172 GEN
Solar/Wind Harmer
2.786
276782AC1-033 GEN
Solar/Wind Harmer
3.31
274851PROVIDENC;RU
Solar/Wind Harmer
1.921
274849CRESCENT ;1U
Solar/Wind Harmer
1.247
276645AC1-214 GEN1
Solar/Wind Harmer
0.904
276646AC1-214 GEN2
Solar/Wind Harmer
0.904
274715NELSON EC;1C
50/50
2.64
274716NELSON EC;1S
50/50
1.928
274760LEE CO EC;1U
50/50
19.958
274767LEE CO EC;8U
50/50
19.723
959091AF2-200 GEN
Solar/Wind Harmer
95.344
274858EASY ROAD;U2
Solar/Wind Harmer
9.688
276157O29GEN1
Solar/Wind Harmer
6.775
965931AG1-462 GEN
Solar/Wind Harmer
43.474
274878BISHOP HL;2U
Solar/Wind Harmer
2.8
972236AH1-702 GEN2
Adder
1.767
274855GSG-6 ;RU
Solar/Wind Harmer
2.827
274850MENDOTA H;RU
Solar/Wind Harmer
1.965
276602WESTBROOK C
Solar/Wind Harmer
1.627
276863AD2-134 GEN
Solar/Wind Harmer
1.367
276799AD1-013 GEN
Solar/Wind Harmer
1.627
946671AF1-331 GEN
Solar/Wind Harmer
0.308
990727J1377 G
External Queue
4.337488174438477
991092J1477
External Queue
6.189391613006592
NYPJM->LTFIMP_NY
CLTF
0.237
WECLTFEXP_WEC->PJM
CLTF
0.857
CPLELTFEXP_CPLE->PJM
CLTF
0.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.708
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.339
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.776
MECLTFEXP_MEC->PJM
CLTF
14.041
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.08
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.184
LAGNLTFEXP_LAGN->PJM
CLTF
4.294
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.889
TVALTFEXP_TVA->PJM
CLTF
1.234

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.9 %
Rating:1334.0 MVA
Rating Type:A
MVA to Mitigate:1519.44
MW Contribution:6.57
Bus #Bus NameTypeMW Contribution
971171AH1-044 GEN
Solar/Wind Harmer
64.55
961011AF2-392 GEN
Solar/Wind Harmer
7.26
946321AF1-296 GEN
Solar/Wind Harmer
5.727
971681AH1-341 GEN
Solar/Wind Harmer
14.612
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
12.852
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.739
957751AF2-069 GEN
Solar/Wind Harmer
0.136
274761LEE CO EC;2U
50/50
15.514
274766LEE CO EC;7U
50/50
15.331
971087AG2-675 GEN
50/50
5.563
957471AF2-041 GEN
Solar/Wind Harmer
96.826
959081AF2-199 GEN
Solar/Wind Harmer
32.275
971067AG2-660 GEN
Solar/Wind Harmer
10.758
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
2.064
970819AG2-516 GEN
Solar/Wind Harmer
6.566
274877BISHOP HL;1U
Solar/Wind Harmer
0.17
971475AH1-234 GEN
Solar/Wind Harmer
2.325
274822ROCKFORD ;11
Adder
12.944
276861AD2-134 GEN
Solar/Wind Harmer
0.081
274717NELSON EC;2C
50/50
2.313
274718NELSON EC;2S
50/50
1.688
972267AH1-718 GEN
50/50
9.128
274764LEE CO EC;5U
50/50
15.55
274765LEE CO EC;6U
50/50
15.55
274762LEE CO EC;3U
50/50
15.514
274763LEE CO EC;4U
50/50
15.367
971341AH1-150 GEN
Solar/Wind Harmer
64.55
971343AH1-151 GEN
Solar/Wind Harmer
64.55
276741O09 GEN1
Solar/Wind Harmer
0.387
276708O09 GEN2
Solar/Wind Harmer
0.387
276603SUBLETTE C
Solar/Wind Harmer
0
938861AE1-114 GEN
Solar/Wind Harmer
4.948
274856ECOGROVE ;U1
Solar/Wind Harmer
0.153
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.162
276646AC1-214 GEN2
Solar/Wind Harmer
0.162
971333AH1-146 GEN
Solar/Wind Harmer
6.856
971335AH1-147 GEN
Solar/Wind Harmer
6.856
274715NELSON EC;1C
50/50
2.313
274716NELSON EC;1S
50/50
1.688
274760LEE CO EC;1U
50/50
15.514
274767LEE CO EC;8U
50/50
15.331
959091AF2-200 GEN
Solar/Wind Harmer
64.55
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.755
965931AG1-462 GEN
Solar/Wind Harmer
26.6
972236AH1-702 GEN2
Adder
1.79
274878BISHOP HL;2U
Solar/Wind Harmer
0.17
274855GSG-6 ;RU
Solar/Wind Harmer
0.167
274850MENDOTA H;RU
Solar/Wind Harmer
0.054
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.081
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.465
991092J1477
External Queue
5.403221130371094
NYPJM->LTFIMP_NY
CLTF
0.191
WECLTFEXP_WEC->PJM
CLTF
0.825
CPLELTFEXP_CPLE->PJM
CLTF
0.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.192
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.767
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.419
MECLTFEXP_MEC->PJM
CLTF
12.387
SIGELTFEXP_SIGE->PJM
CLTF
0.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.053
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.109
LAGNLTFEXP_LAGN->PJM
CLTF
3.829
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.862
TVALTFEXP_TVA->PJM
CLTF
1.111

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P2-2_141_PV-138R__1_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_141_PV-138R__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.14 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1858.03
MW Contribution:9.77
Bus #Bus NameTypeMW Contribution
971171AH1-044 GEN
Solar/Wind Harmer
92.627
961011AF2-392 GEN
Solar/Wind Harmer
19.436
946321AF1-296 GEN
Solar/Wind Harmer
15.394
971681AH1-341 GEN
Solar/Wind Harmer
19.897
276612AE2-035 GEN
Solar/Wind Harmer
2.454
274823ROCKFORD ;21
Adder
13.655
971675AH1-338 GEN
Solar/Wind Harmer
11.776
274848CAMPGROVE;RU
Solar/Wind Harmer
4.195
971177AH1-047 GEN
Solar/Wind Harmer
3.553
957751AF2-069 GEN
Solar/Wind Harmer
0.273
971411AH1-196 GEN
Solar/Wind Harmer
6.546
274761LEE CO EC;2U
50/50
15.656
274766LEE CO EC;7U
50/50
15.472
971087AG2-675 GEN
50/50
5.597
957471AF2-041 GEN
Solar/Wind Harmer
138.941
959081AF2-199 GEN
Solar/Wind Harmer
46.314
971067AG2-660 GEN
Solar/Wind Harmer
10.771
274857EASY ROAD;U1
Solar/Wind Harmer
7.6
276158O29GEN2
Solar/Wind Harmer
7.843
972235AH1-702 GEN1
Adder
2.113
970819AG2-516 GEN
Solar/Wind Harmer
9.773
274877BISHOP HL;1U
Solar/Wind Harmer
2.47
971475AH1-234 GEN
Solar/Wind Harmer
15.858
274822ROCKFORD ;11
Adder
13.751
276861AD2-134 GEN
Solar/Wind Harmer
1.189
274717NELSON EC;2C
50/50
2.325
274718NELSON EC;2S
50/50
1.697
972267AH1-718 GEN
50/50
9.178
274764LEE CO EC;5U
50/50
15.693
274765LEE CO EC;6U
50/50
15.693
274762LEE CO EC;3U
50/50
15.656
274763LEE CO EC;4U
50/50
15.509
971341AH1-150 GEN
Solar/Wind Harmer
92.627
971343AH1-151 GEN
Solar/Wind Harmer
92.627
276741O09 GEN1
Solar/Wind Harmer
5.602
276708O09 GEN2
Solar/Wind Harmer
5.602
276603SUBLETTE C
Solar/Wind Harmer
1.629
938861AE1-114 GEN
Solar/Wind Harmer
10.449
274856ECOGROVE ;U1
Solar/Wind Harmer
3.234
276611AD2-172 GEN
Solar/Wind Harmer
2.454
276782AC1-033 GEN
Solar/Wind Harmer
2.92
274851PROVIDENC;RU
Solar/Wind Harmer
1.695
274849CRESCENT ;1U
Solar/Wind Harmer
1.101
276645AC1-214 GEN1
Solar/Wind Harmer
0.797
276646AC1-214 GEN2
Solar/Wind Harmer
0.797
971333AH1-146 GEN
Solar/Wind Harmer
10.058
971335AH1-147 GEN
Solar/Wind Harmer
10.058
274715NELSON EC;1C
50/50
2.325
274716NELSON EC;1S
50/50
1.697
274760LEE CO EC;1U
50/50
15.656
274767LEE CO EC;8U
50/50
15.472
959091AF2-200 GEN
Solar/Wind Harmer
92.627
274858EASY ROAD;U2
Solar/Wind Harmer
7.6
276157O29GEN1
Solar/Wind Harmer
5.966
965931AG1-462 GEN
Solar/Wind Harmer
38.358
972236AH1-702 GEN2
Adder
1.832
274878BISHOP HL;2U
Solar/Wind Harmer
2.47
274855GSG-6 ;RU
Solar/Wind Harmer
2.459
274850MENDOTA H;RU
Solar/Wind Harmer
1.71
276602WESTBROOK C
Solar/Wind Harmer
1.416
276863AD2-134 GEN
Solar/Wind Harmer
1.189
276799AD1-013 GEN
Solar/Wind Harmer
1.414
946671AF1-331 GEN
Solar/Wind Harmer
0.268
991092J1477
External Queue
5.43301248550415
NYPJM->LTFIMP_NY
CLTF
0.193
WECLTFEXP_WEC->PJM
CLTF
0.835
CPLELTFEXP_CPLE->PJM
CLTF
0.167
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.343
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.27
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.442
MECLTFEXP_MEC->PJM
CLTF
12.488
SIGELTFEXP_SIGE->PJM
CLTF
0.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.054
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.112
LAGNLTFEXP_LAGN->PJM
CLTF
3.858
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.866
TVALTFEXP_TVA->PJM
CLTF
1.119

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P2-2_154_LV-345R__3_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_154_LV-345R__3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.06 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1856.54
MW Contribution:9.62
Bus #Bus NameTypeMW Contribution
274715NELSON EC;1C
50/50
2.324
274716NELSON EC;1S
50/50
1.696
274760LEE CO EC;1U
50/50
15.644
274767LEE CO EC;8U
50/50
15.46
959091AF2-200 GEN
Solar/Wind Harmer
92.678
274858EASY ROAD;U2
Solar/Wind Harmer
7.594
276157O29GEN1
Solar/Wind Harmer
5.958
965931AG1-462 GEN
Solar/Wind Harmer
38.302
972236AH1-702 GEN2
Adder
1.83
274878BISHOP HL;2U
Solar/Wind Harmer
2.467
274855GSG-6 ;RU
Solar/Wind Harmer
2.443
274850MENDOTA H;RU
Solar/Wind Harmer
1.699
276602WESTBROOK C
Solar/Wind Harmer
1.406
276863AD2-134 GEN
Solar/Wind Harmer
1.182
276799AD1-013 GEN
Solar/Wind Harmer
1.405
946671AF1-331 GEN
Solar/Wind Harmer
0.266
274761LEE CO EC;2U
50/50
15.644
274766LEE CO EC;7U
50/50
15.46
971087AG2-675 GEN
50/50
5.589
957471AF2-041 GEN
Solar/Wind Harmer
139.017
959081AF2-199 GEN
Solar/Wind Harmer
46.339
971067AG2-660 GEN
Solar/Wind Harmer
10.776
274857EASY ROAD;U1
Solar/Wind Harmer
7.594
276158O29GEN2
Solar/Wind Harmer
7.833
972235AH1-702 GEN1
Adder
2.11
970819AG2-516 GEN
Solar/Wind Harmer
9.624
274877BISHOP HL;1U
Solar/Wind Harmer
2.467
971475AH1-234 GEN
Solar/Wind Harmer
15.716
274822ROCKFORD ;11
Adder
13.362
276861AD2-134 GEN
Solar/Wind Harmer
1.182
274717NELSON EC;2C
50/50
2.324
274718NELSON EC;2S
50/50
1.696
972267AH1-718 GEN
50/50
9.172
274764LEE CO EC;5U
50/50
15.681
274765LEE CO EC;6U
50/50
15.681
274762LEE CO EC;3U
50/50
15.644
274763LEE CO EC;4U
50/50
15.497
971341AH1-150 GEN
Solar/Wind Harmer
92.678
971343AH1-151 GEN
Solar/Wind Harmer
92.678
276741O09 GEN1
Solar/Wind Harmer
5.595
276708O09 GEN2
Solar/Wind Harmer
5.595
276603SUBLETTE C
Solar/Wind Harmer
1.624
938861AE1-114 GEN
Solar/Wind Harmer
10.378
274856ECOGROVE ;U1
Solar/Wind Harmer
3.191
276611AD2-172 GEN
Solar/Wind Harmer
2.422
276782AC1-033 GEN
Solar/Wind Harmer
2.916
274851PROVIDENC;RU
Solar/Wind Harmer
1.693
274849CRESCENT ;1U
Solar/Wind Harmer
1.099
276645AC1-214 GEN1
Solar/Wind Harmer
0.796
276646AC1-214 GEN2
Solar/Wind Harmer
0.796
971333AH1-146 GEN
Solar/Wind Harmer
10.173
971335AH1-147 GEN
Solar/Wind Harmer
10.173
971171AH1-044 GEN
Solar/Wind Harmer
92.678
961011AF2-392 GEN
Solar/Wind Harmer
19.403
946321AF1-296 GEN
Solar/Wind Harmer
15.367
971681AH1-341 GEN
Solar/Wind Harmer
19.727
276612AE2-035 GEN
Solar/Wind Harmer
2.422
274823ROCKFORD ;21
Adder
13.268
971675AH1-338 GEN
Solar/Wind Harmer
11.698
274848CAMPGROVE;RU
Solar/Wind Harmer
4.189
957751AF2-069 GEN
Solar/Wind Harmer
0.273
971411AH1-196 GEN
Solar/Wind Harmer
6.845
991092J1477
External Queue
5.44020414352417
NYPJM->LTFIMP_NY
CLTF
0.194
WECLTFEXP_WEC->PJM
CLTF
0.766
CPLELTFEXP_CPLE->PJM
CLTF
0.164
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.23
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.511
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.42
MECLTFEXP_MEC->PJM
CLTF
12.422
SIGELTFEXP_SIGE->PJM
CLTF
0.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.055
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.115
LAGNLTFEXP_LAGN->PJM
CLTF
3.836
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.856
TVALTFEXP_TVA->PJM
CLTF
1.112

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_116_GG-345R__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.04 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1856.04
MW Contribution:9.41
Bus #Bus NameTypeMW Contribution
274715NELSON EC;1C
50/50
2.316
274716NELSON EC;1S
50/50
1.691
274760LEE CO EC;1U
50/50
15.531
274767LEE CO EC;8U
50/50
15.348
959091AF2-200 GEN
Solar/Wind Harmer
92.522
274858EASY ROAD;U2
Solar/Wind Harmer
7.539
276157O29GEN1
Solar/Wind Harmer
5.95
965931AG1-462 GEN
Solar/Wind Harmer
38.29
972236AH1-702 GEN2
Adder
1.789
274878BISHOP HL;2U
Solar/Wind Harmer
2.503
274855GSG-6 ;RU
Solar/Wind Harmer
2.402
274850MENDOTA H;RU
Solar/Wind Harmer
1.67
276602WESTBROOK C
Solar/Wind Harmer
1.383
276863AD2-134 GEN
Solar/Wind Harmer
1.162
276799AD1-013 GEN
Solar/Wind Harmer
1.38
946671AF1-331 GEN
Solar/Wind Harmer
0.261
274717NELSON EC;2C
50/50
2.316
274718NELSON EC;2S
50/50
1.691
972267AH1-718 GEN
50/50
9.142
274764LEE CO EC;5U
50/50
15.568
274765LEE CO EC;6U
50/50
15.568
274762LEE CO EC;3U
50/50
15.531
274763LEE CO EC;4U
50/50
15.385
971341AH1-150 GEN
Solar/Wind Harmer
92.522
971343AH1-151 GEN
Solar/Wind Harmer
92.522
276741O09 GEN1
Solar/Wind Harmer
5.587
276708O09 GEN2
Solar/Wind Harmer
5.587
276603SUBLETTE C
Solar/Wind Harmer
1.615
971171AH1-044 GEN
Solar/Wind Harmer
92.522
961011AF2-392 GEN
Solar/Wind Harmer
19.327
946321AF1-296 GEN
Solar/Wind Harmer
15.354
971681AH1-341 GEN
Solar/Wind Harmer
19.54
276612AE2-035 GEN
Solar/Wind Harmer
2.378
274848CAMPGROVE;RU
Solar/Wind Harmer
4.274
274823ROCKFORD ;21
Adder
12.838
971675AH1-338 GEN
Solar/Wind Harmer
11.497
957751AF2-069 GEN
Solar/Wind Harmer
0.278
274761LEE CO EC;2U
50/50
15.531
274766LEE CO EC;7U
50/50
15.348
971087AG2-675 GEN
50/50
5.587
957471AF2-041 GEN
Solar/Wind Harmer
138.783
959081AF2-199 GEN
Solar/Wind Harmer
46.261
971067AG2-660 GEN
Solar/Wind Harmer
10.758
274857EASY ROAD;U1
Solar/Wind Harmer
7.539
276158O29GEN2
Solar/Wind Harmer
7.822
972235AH1-702 GEN1
Adder
2.063
970819AG2-516 GEN
Solar/Wind Harmer
9.409
274877BISHOP HL;1U
Solar/Wind Harmer
2.503
971475AH1-234 GEN
Solar/Wind Harmer
15.373
274822ROCKFORD ;11
Adder
12.929
276861AD2-134 GEN
Solar/Wind Harmer
1.162
938861AE1-114 GEN
Solar/Wind Harmer
10.273
274856ECOGROVE ;U1
Solar/Wind Harmer
3.135
276611AD2-172 GEN
Solar/Wind Harmer
2.378
276782AC1-033 GEN
Solar/Wind Harmer
2.959
274851PROVIDENC;RU
Solar/Wind Harmer
1.721
274849CRESCENT ;1U
Solar/Wind Harmer
1.118
276645AC1-214 GEN1
Solar/Wind Harmer
0.81
276646AC1-214 GEN2
Solar/Wind Harmer
0.81
971333AH1-146 GEN
Solar/Wind Harmer
9.798
971335AH1-147 GEN
Solar/Wind Harmer
9.798
991092J1477
External Queue
5.438880443572998
NYPJM->LTFIMP_NY
CLTF
0.194
LGEELTFEXP_LGEE->PJM
CLTF
0.001
WECLTFEXP_WEC->PJM
CLTF
0.817
CPLELTFEXP_CPLE->PJM
CLTF
0.17
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.629
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.934
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.483
MECLTFEXP_MEC->PJM
CLTF
12.489
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.052
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.102
LAGNLTFEXP_LAGN->PJM
CLTF
3.885
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.879
TVALTFEXP_TVA->PJM
CLTF
1.131

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345B__4_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_116_GG-345B__4_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.99 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1855.19
MW Contribution:9.35
Bus #Bus NameTypeMW Contribution
274715NELSON EC;1C
50/50
2.311
274716NELSON EC;1S
50/50
1.687
274760LEE CO EC;1U
50/50
15.486
274767LEE CO EC;8U
50/50
15.304
959091AF2-200 GEN
Solar/Wind Harmer
92.427
274858EASY ROAD;U2
Solar/Wind Harmer
7.517
276157O29GEN1
Solar/Wind Harmer
5.936
965931AG1-462 GEN
Solar/Wind Harmer
38.203
972236AH1-702 GEN2
Adder
1.778
274878BISHOP HL;2U
Solar/Wind Harmer
2.497
274855GSG-6 ;RU
Solar/Wind Harmer
2.386
274850MENDOTA H;RU
Solar/Wind Harmer
1.659
276602WESTBROOK C
Solar/Wind Harmer
1.373
276863AD2-134 GEN
Solar/Wind Harmer
1.154
276799AD1-013 GEN
Solar/Wind Harmer
1.37
946671AF1-331 GEN
Solar/Wind Harmer
0.259
274761LEE CO EC;2U
50/50
15.486
274766LEE CO EC;7U
50/50
15.304
971087AG2-675 GEN
50/50
5.575
957471AF2-041 GEN
Solar/Wind Harmer
138.64
959081AF2-199 GEN
Solar/Wind Harmer
46.213
971067AG2-660 GEN
Solar/Wind Harmer
10.747
274857EASY ROAD;U1
Solar/Wind Harmer
7.517
276158O29GEN2
Solar/Wind Harmer
7.804
972235AH1-702 GEN1
Adder
2.05
970819AG2-516 GEN
Solar/Wind Harmer
9.348
274877BISHOP HL;1U
Solar/Wind Harmer
2.497
971475AH1-234 GEN
Solar/Wind Harmer
15.255
274822ROCKFORD ;11
Adder
12.826
276861AD2-134 GEN
Solar/Wind Harmer
1.154
274717NELSON EC;2C
50/50
2.311
274718NELSON EC;2S
50/50
1.687
972267AH1-718 GEN
50/50
9.124
274764LEE CO EC;5U
50/50
15.523
274765LEE CO EC;6U
50/50
15.523
274762LEE CO EC;3U
50/50
15.486
274763LEE CO EC;4U
50/50
15.34
971341AH1-150 GEN
Solar/Wind Harmer
92.427
971343AH1-151 GEN
Solar/Wind Harmer
92.427
276741O09 GEN1
Solar/Wind Harmer
5.575
276708O09 GEN2
Solar/Wind Harmer
5.575
276603SUBLETTE C
Solar/Wind Harmer
1.61
938861AE1-114 GEN
Solar/Wind Harmer
10.236
274856ECOGROVE ;U1
Solar/Wind Harmer
3.118
276611AD2-172 GEN
Solar/Wind Harmer
2.366
276782AC1-033 GEN
Solar/Wind Harmer
2.952
274851PROVIDENC;RU
Solar/Wind Harmer
1.716
274849CRESCENT ;1U
Solar/Wind Harmer
1.114
276645AC1-214 GEN1
Solar/Wind Harmer
0.807
276646AC1-214 GEN2
Solar/Wind Harmer
0.807
971333AH1-146 GEN
Solar/Wind Harmer
9.691
971335AH1-147 GEN
Solar/Wind Harmer
9.691
971171AH1-044 GEN
Solar/Wind Harmer
92.427
961011AF2-392 GEN
Solar/Wind Harmer
19.282
946321AF1-296 GEN
Solar/Wind Harmer
15.317
971681AH1-341 GEN
Solar/Wind Harmer
19.472
276612AE2-035 GEN
Solar/Wind Harmer
2.366
274848CAMPGROVE;RU
Solar/Wind Harmer
4.264
274823ROCKFORD ;21
Adder
12.735
971675AH1-338 GEN
Solar/Wind Harmer
11.416
957751AF2-069 GEN
Solar/Wind Harmer
0.277
991092J1477
External Queue
5.43087100982666
NYPJM->LTFIMP_NY
CLTF
0.192
LGEELTFEXP_LGEE->PJM
CLTF
0.003
WECLTFEXP_WEC->PJM
CLTF
0.793
CPLELTFEXP_CPLE->PJM
CLTF
0.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.576
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.615
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.478
MECLTFEXP_MEC->PJM
CLTF
12.444
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.05
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.097
LAGNLTFEXP_LAGN->PJM
CLTF
3.874
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.883
TVALTFEXP_TVA->PJM
CLTF
1.129

Details for AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line l/o COMED_P2-2_951_AR-345R__3_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-041 TP-ELECT JCT;1B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_951_AR-345R__3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.85 %
Rating:1837.0 MVA
Rating Type:STE
MVA to Mitigate:1852.6
MW Contribution:9.52
Bus #Bus NameTypeMW Contribution
274761LEE CO EC;2U
50/50
15.592
274766LEE CO EC;7U
50/50
15.408
971087AG2-675 GEN
50/50
5.583
957471AF2-041 GEN
Solar/Wind Harmer
138.965
959081AF2-199 GEN
Solar/Wind Harmer
46.322
971067AG2-660 GEN
Solar/Wind Harmer
10.773
274857EASY ROAD;U1
Solar/Wind Harmer
7.569
276158O29GEN2
Solar/Wind Harmer
7.817
972235AH1-702 GEN1
Adder
2.089
970819AG2-516 GEN
Solar/Wind Harmer
9.519
274877BISHOP HL;1U
Solar/Wind Harmer
2.461
971475AH1-234 GEN
Solar/Wind Harmer
15.585
274822ROCKFORD ;11
Adder
13.131
276861AD2-134 GEN
Solar/Wind Harmer
1.171
274717NELSON EC;2C
50/50
2.32
274718NELSON EC;2S
50/50
1.694
972267AH1-718 GEN
50/50
9.157
274764LEE CO EC;5U
50/50
15.629
274765LEE CO EC;6U
50/50
15.629
274762LEE CO EC;3U
50/50
15.592
274763LEE CO EC;4U
50/50
15.445
971341AH1-150 GEN
Solar/Wind Harmer
92.644
971343AH1-151 GEN
Solar/Wind Harmer
92.644
276741O09 GEN1
Solar/Wind Harmer
5.583
276708O09 GEN2
Solar/Wind Harmer
5.583
276603SUBLETTE C
Solar/Wind Harmer
1.619
938861AE1-114 GEN
Solar/Wind Harmer
10.322
274856ECOGROVE ;U1
Solar/Wind Harmer
3.162
276611AD2-172 GEN
Solar/Wind Harmer
2.399
276782AC1-033 GEN
Solar/Wind Harmer
2.91
274851PROVIDENC;RU
Solar/Wind Harmer
1.689
274849CRESCENT ;1U
Solar/Wind Harmer
1.096
276645AC1-214 GEN1
Solar/Wind Harmer
0.794
276646AC1-214 GEN2
Solar/Wind Harmer
0.794
971333AH1-146 GEN
Solar/Wind Harmer
10.083
971335AH1-147 GEN
Solar/Wind Harmer
10.083
971171AH1-044 GEN
Solar/Wind Harmer
92.644
961011AF2-392 GEN
Solar/Wind Harmer
19.359
946321AF1-296 GEN
Solar/Wind Harmer
15.347
971681AH1-341 GEN
Solar/Wind Harmer
19.622
276612AE2-035 GEN
Solar/Wind Harmer
2.399
274823ROCKFORD ;21
Adder
13.038
274848CAMPGROVE;RU
Solar/Wind Harmer
4.179
971675AH1-338 GEN
Solar/Wind Harmer
11.596
957751AF2-069 GEN
Solar/Wind Harmer
0.272
971411AH1-196 GEN
Solar/Wind Harmer
6.486
274715NELSON EC;1C
50/50
2.32
274716NELSON EC;1S
50/50
1.694
274760LEE CO EC;1U
50/50
15.592
274767LEE CO EC;8U
50/50
15.408
959091AF2-200 GEN
Solar/Wind Harmer
92.644
274858EASY ROAD;U2
Solar/Wind Harmer
7.569
276157O29GEN1
Solar/Wind Harmer
5.946
965931AG1-462 GEN
Solar/Wind Harmer
38.258
972236AH1-702 GEN2
Adder
1.812
274878BISHOP HL;2U
Solar/Wind Harmer
2.461
274855GSG-6 ;RU
Solar/Wind Harmer
2.422
274850MENDOTA H;RU
Solar/Wind Harmer
1.684
276602WESTBROOK C
Solar/Wind Harmer
1.394
276863AD2-134 GEN
Solar/Wind Harmer
1.171
276799AD1-013 GEN
Solar/Wind Harmer
1.392
946671AF1-331 GEN
Solar/Wind Harmer
0.264
991092J1477
External Queue
5.418740749359131
NYPJM->LTFIMP_NY
CLTF
0.197
WECLTFEXP_WEC->PJM
CLTF
0.848
CPLELTFEXP_CPLE->PJM
CLTF
0.16
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.208
CBM West 1LTFEXP_CBM-W1->PJM
CBM
48.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.412
MECLTFEXP_MEC->PJM
CLTF
12.447
SIGELTFEXP_SIGE->PJM
CLTF
0.015
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.058
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.123
LAGNLTFEXP_LAGN->PJM
CLTF
3.836
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.846
TVALTFEXP_TVA->PJM
CLTF
1.11

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT7-8___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.54 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1905.67
MW Contribution:23.26
Bus #Bus NameTypeMW Contribution
971333AH1-146 GEN
Solar/Wind Harmer
43.356
971335AH1-147 GEN
Solar/Wind Harmer
43.356
274856ECOGROVE ;U1
Solar/Wind Harmer
6.101
276611AD2-172 GEN
Solar/Wind Harmer
4.629
274764LEE CO EC;5U
Adder
14.104
274765LEE CO EC;6U
Adder
14.104
274762LEE CO EC;3U
Adder
14.071
274763LEE CO EC;4U
Adder
13.938
938861AE1-114 GEN
Solar/Wind Harmer
12.173
276603SUBLETTE C
Solar/Wind Harmer
1.211
972267AH1-718 GEN
Adder
4.503
276741O09 GEN1
Solar/Wind Harmer
3.245
276708O09 GEN2
Solar/Wind Harmer
3.245
970921AG2-575 GEN
Solar/Wind Harmer
7.492
970921AG2-575 GEN
Solar/Wind Harmer
1.742
942991AE2-321 GEN
Solar/Wind Harmer
6.762
962691AG1-118 GEN
Solar/Wind Harmer
17.893
971341AH1-150 GEN
Solar/Wind Harmer
10.168
971343AH1-151 GEN
Solar/Wind Harmer
10.168
274823ROCKFORD ;21
50/50
43.598
971411AH1-196 GEN
Solar/Wind Harmer
63.72
276612AE2-035 GEN
Solar/Wind Harmer
4.629
971681AH1-341 GEN
Solar/Wind Harmer
21.411
961011AF2-392 GEN
Solar/Wind Harmer
11.886
946321AF1-296 GEN
Solar/Wind Harmer
9.234
971675AH1-338 GEN
Solar/Wind Harmer
14.566
971177AH1-047 GEN
Solar/Wind Harmer
4.41
971171AH1-044 GEN
Solar/Wind Harmer
10.168
274657BYRON ;2U
50/50
15.925
972235AH1-702 GEN1
50/50
5.799
972031AH1-564 GEN
50/50
36.781
274824ROCKFORD ;12
50/50
34.076
274822ROCKFORD ;11
50/50
43.914
971475AH1-234 GEN
Solar/Wind Harmer
44.028
970819AG2-516 GEN
Solar/Wind Harmer
23.26
274857EASY ROAD;U1
Solar/Wind Harmer
7.248
274761LEE CO EC;2U
Adder
14.071
274766LEE CO EC;7U
Adder
13.905
276158O29GEN2
Solar/Wind Harmer
4.543
276861AD2-134 GEN
Solar/Wind Harmer
1.453
960751AF2-366 GEN
Solar/Wind Harmer
2.149
962781AG1-127 GEN
Solar/Wind Harmer
7.125
274872LEEDK;1U
Solar/Wind Harmer
5.679
957471AF2-041 GEN
Solar/Wind Harmer
15.252
959081AF2-199 GEN
Solar/Wind Harmer
5.084
971067AG2-660 GEN
Solar/Wind Harmer
1.182
972236AH1-702 GEN2
50/50
5.049
274656BYRON ;1U
50/50
16.311
274858EASY ROAD;U2
Solar/Wind Harmer
7.248
274760LEE CO EC;1U
Adder
14.071
274767LEE CO EC;8U
Adder
13.905
276157O29GEN1
Solar/Wind Harmer
3.455
965931AG1-462 GEN
Solar/Wind Harmer
21.908
274855GSG-6 ;RU
Solar/Wind Harmer
3.005
274850MENDOTA H;RU
Solar/Wind Harmer
2.09
276602WESTBROOK C
Solar/Wind Harmer
1.73
276863AD2-134 GEN
Solar/Wind Harmer
1.453
276799AD1-013 GEN
Solar/Wind Harmer
1.777
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
10.168
990512J1326
External Queue
9.444316864013672
990117J1214
External Queue
32.48844909667969
990727J1377 G
External Queue
13.982793807983398
991092J1477
External Queue
2.8638265132904053
991777J1629 G
External Queue
9.207619667053223
990407J1304
External Queue
7.996669292449951
NYPJM->LTFIMP_NY
CLTF
0.236
WECLTFEXP_WEC->PJM
CLTF
0.762
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.811
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.914
MECLTFEXP_MEC->PJM
CLTF
9.246
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.412
LAGNLTFEXP_LAGN->PJM
CLTF
2.566
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.659

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT5-8___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.25 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1901.13
MW Contribution:23.03
Bus #Bus NameTypeMW Contribution
971333AH1-146 GEN
Solar/Wind Harmer
42.977
971335AH1-147 GEN
Solar/Wind Harmer
42.977
274856ECOGROVE ;U1
Solar/Wind Harmer
6.047
276611AD2-172 GEN
Solar/Wind Harmer
4.588
274764LEE CO EC;5U
Adder
14.067
274765LEE CO EC;6U
Adder
14.067
274762LEE CO EC;3U
Adder
14.034
274763LEE CO EC;4U
Adder
13.902
938861AE1-114 GEN
Solar/Wind Harmer
12.113
276603SUBLETTE C
Solar/Wind Harmer
1.212
972267AH1-718 GEN
Adder
4.528
276741O09 GEN1
Solar/Wind Harmer
3.258
276708O09 GEN2
Solar/Wind Harmer
3.258
970921AG2-575 GEN
Solar/Wind Harmer
7.577
970921AG2-575 GEN
Solar/Wind Harmer
1.762
942991AE2-321 GEN
Solar/Wind Harmer
6.399
962691AG1-118 GEN
Solar/Wind Harmer
18.291
971341AH1-150 GEN
Solar/Wind Harmer
10.904
971343AH1-151 GEN
Solar/Wind Harmer
10.904
274823ROCKFORD ;21
50/50
43.098
971411AH1-196 GEN
Solar/Wind Harmer
63.022
276612AE2-035 GEN
Solar/Wind Harmer
4.588
971681AH1-341 GEN
Solar/Wind Harmer
21.331
961011AF2-392 GEN
Solar/Wind Harmer
11.925
946321AF1-296 GEN
Solar/Wind Harmer
9.259
971675AH1-338 GEN
Solar/Wind Harmer
14.702
971177AH1-047 GEN
Solar/Wind Harmer
4.205
971171AH1-044 GEN
Solar/Wind Harmer
10.904
972236AH1-702 GEN2
50/50
5.005
274656BYRON ;1U
50/50
16.168
274858EASY ROAD;U2
Solar/Wind Harmer
7.229
274760LEE CO EC;1U
Adder
14.034
274767LEE CO EC;8U
Adder
13.869
276157O29GEN1
Solar/Wind Harmer
3.469
965931AG1-462 GEN
Solar/Wind Harmer
21.979
274855GSG-6 ;RU
Solar/Wind Harmer
3.033
274850MENDOTA H;RU
Solar/Wind Harmer
2.109
276602WESTBROOK C
Solar/Wind Harmer
1.746
276863AD2-134 GEN
Solar/Wind Harmer
1.467
276799AD1-013 GEN
Solar/Wind Harmer
1.794
946671AF1-331 GEN
Solar/Wind Harmer
0.34
274872LEEDK;1U
Solar/Wind Harmer
0.179
959091AF2-200 GEN
Solar/Wind Harmer
10.904
274657BYRON ;2U
50/50
15.786
972235AH1-702 GEN1
50/50
5.749
972031AH1-564 GEN
50/50
36.36
274824ROCKFORD ;12
50/50
33.686
274822ROCKFORD ;11
50/50
43.411
971475AH1-234 GEN
Solar/Wind Harmer
43.586
970819AG2-516 GEN
Solar/Wind Harmer
23.028
274857EASY ROAD;U1
Solar/Wind Harmer
7.229
274761LEE CO EC;2U
Adder
14.034
274766LEE CO EC;7U
Adder
13.869
276158O29GEN2
Solar/Wind Harmer
4.561
276861AD2-134 GEN
Solar/Wind Harmer
1.467
960751AF2-366 GEN
Solar/Wind Harmer
2.174
962781AG1-127 GEN
Solar/Wind Harmer
7.206
274872LEEDK;1U
Solar/Wind Harmer
5.758
957471AF2-041 GEN
Solar/Wind Harmer
16.357
959081AF2-199 GEN
Solar/Wind Harmer
5.452
971067AG2-660 GEN
Solar/Wind Harmer
1.268
990512J1326
External Queue
9.342920303344727
990117J1214
External Queue
32.139644622802734
990727J1377 G
External Queue
13.837535858154297
991092J1477
External Queue
2.8840813636779785
991777J1629 G
External Queue
9.058588027954102
990407J1304
External Queue
7.907464027404785
NYPJM->LTFIMP_NY
CLTF
0.235
WECLTFEXP_WEC->PJM
CLTF
0.729
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.907
MECLTFEXP_MEC->PJM
CLTF
9.219
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.411
LAGNLTFEXP_LAGN->PJM
CLTF
2.557
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.656

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4-6_006-345-BT78___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.6 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1796.94
MW Contribution:24.2
Bus #Bus NameTypeMW Contribution
274856ECOGROVE ;U1
Solar/Wind Harmer
6.263
276611AD2-172 GEN
Solar/Wind Harmer
4.752
938861AE1-114 GEN
Solar/Wind Harmer
12.204
274764LEE CO EC;5U
Adder
12.937
274765LEE CO EC;6U
Adder
12.937
274762LEE CO EC;3U
Adder
12.907
274763LEE CO EC;4U
Adder
12.785
276603SUBLETTE C
Solar/Wind Harmer
1.169
972267AH1-718 GEN
Adder
4.193
276741O09 GEN1
Solar/Wind Harmer
3.061
276708O09 GEN2
Solar/Wind Harmer
3.061
970921AG2-575 GEN
Solar/Wind Harmer
7.585
970921AG2-575 GEN
Solar/Wind Harmer
1.764
942991AE2-321 GEN
Solar/Wind Harmer
7.135
962691AG1-118 GEN
Solar/Wind Harmer
18.087
971341AH1-150 GEN
Solar/Wind Harmer
9.367
971343AH1-151 GEN
Solar/Wind Harmer
9.367
972236AH1-702 GEN2
50/50
5.659
274656BYRON ;1U
50/50
14.792
274858EASY ROAD;U2
Solar/Wind Harmer
6.648
274760LEE CO EC;1U
Adder
12.907
274767LEE CO EC;8U
Adder
12.755
276157O29GEN1
Solar/Wind Harmer
3.26
965931AG1-462 GEN
Solar/Wind Harmer
20.756
274855GSG-6 ;RU
Solar/Wind Harmer
2.973
274850MENDOTA H;RU
Solar/Wind Harmer
2.067
276602WESTBROOK C
Solar/Wind Harmer
1.711
276863AD2-134 GEN
Solar/Wind Harmer
1.438
276799AD1-013 GEN
Solar/Wind Harmer
1.759
946671AF1-331 GEN
Solar/Wind Harmer
0.333
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
9.367
274657BYRON ;2U
50/50
17.85
972031AH1-564 GEN
50/50
37.916
274824ROCKFORD ;12
50/50
35.129
274822ROCKFORD ;11
50/50
45.271
972235AH1-702 GEN1
50/50
5.259
971475AH1-234 GEN
Solar/Wind Harmer
46.897
970819AG2-516 GEN
Solar/Wind Harmer
24.195
274857EASY ROAD;U1
Solar/Wind Harmer
6.648
274761LEE CO EC;2U
Adder
12.907
274766LEE CO EC;7U
Adder
12.755
276158O29GEN2
Solar/Wind Harmer
4.286
276861AD2-134 GEN
Solar/Wind Harmer
1.438
960751AF2-366 GEN
Solar/Wind Harmer
2.176
962781AG1-127 GEN
Solar/Wind Harmer
7.214
274872LEEDK;1U
Solar/Wind Harmer
5.696
957471AF2-041 GEN
Solar/Wind Harmer
14.05
959081AF2-199 GEN
Solar/Wind Harmer
4.683
971067AG2-660 GEN
Solar/Wind Harmer
1.089
274823ROCKFORD ;21
50/50
44.943
971411AH1-196 GEN
Solar/Wind Harmer
64.395
276612AE2-035 GEN
Solar/Wind Harmer
4.752
971681AH1-341 GEN
Solar/Wind Harmer
21.179
961011AF2-392 GEN
Solar/Wind Harmer
11.275
946321AF1-296 GEN
Solar/Wind Harmer
8.796
971675AH1-338 GEN
Solar/Wind Harmer
14.414
971177AH1-047 GEN
Solar/Wind Harmer
4.62
971171AH1-044 GEN
Solar/Wind Harmer
9.367
990512J1326
External Queue
10.086955070495605
990117J1214
External Queue
34.69912338256836
990727J1377 G
External Queue
14.958372116088867
991092J1477
External Queue
2.650393486022949
991777J1629 G
External Queue
9.956707000732422
990407J1304
External Queue
8.578377723693848
NYPJM->LTFIMP_NY
CLTF
0.233
WECLTFEXP_WEC->PJM
CLTF
0.873
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.943
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.877
MECLTFEXP_MEC->PJM
CLTF
9.145
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.41
LAGNLTFEXP_LAGN->PJM
CLTF
2.531
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.17
TVALTFEXP_TVA->PJM
CLTF
0.647

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345B__1_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.49 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1701.11
MW Contribution:19.52
Bus #Bus NameTypeMW Contribution
972236AH1-702 GEN2
50/50
3.807
274656BYRON ;1U
50/50
12.275
274858EASY ROAD;U2
Solar/Wind Harmer
6.261
274760LEE CO EC;1U
Adder
12.155
274767LEE CO EC;8U
Adder
12.012
959091AF2-200 GEN
Solar/Wind Harmer
21.842
276157O29GEN1
Solar/Wind Harmer
3.423
965931AG1-462 GEN
Solar/Wind Harmer
21.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.751
274850MENDOTA H;RU
Solar/Wind Harmer
1.913
276602WESTBROOK C
Solar/Wind Harmer
1.583
276863AD2-134 GEN
Solar/Wind Harmer
1.33
276799AD1-013 GEN
Solar/Wind Harmer
1.623
946671AF1-331 GEN
Solar/Wind Harmer
0.307
274872LEEDK;1U
Solar/Wind Harmer
0.158
274856ECOGROVE ;U1
Solar/Wind Harmer
5.234
276611AD2-172 GEN
Solar/Wind Harmer
3.971
938861AE1-114 GEN
Solar/Wind Harmer
10.904
274764LEE CO EC;5U
Adder
12.183
274765LEE CO EC;6U
Adder
12.183
274762LEE CO EC;3U
Adder
12.155
274763LEE CO EC;4U
Adder
12.04
276603SUBLETTE C
Solar/Wind Harmer
1.154
972267AH1-718 GEN
Adder
4.55
971341AH1-150 GEN
Solar/Wind Harmer
21.842
971343AH1-151 GEN
Solar/Wind Harmer
21.842
971333AH1-146 GEN
Solar/Wind Harmer
20.489
971335AH1-147 GEN
Solar/Wind Harmer
20.489
276741O09 GEN1
Solar/Wind Harmer
3.215
276708O09 GEN2
Solar/Wind Harmer
3.215
970921AG2-575 GEN
Solar/Wind Harmer
6.564
970921AG2-575 GEN
Solar/Wind Harmer
1.527
962691AG1-118 GEN
Solar/Wind Harmer
15.751
942991AE2-321 GEN
Solar/Wind Harmer
5.127
274823ROCKFORD ;21
50/50
36.874
971411AH1-196 GEN
Solar/Wind Harmer
59.956
276612AE2-035 GEN
Solar/Wind Harmer
3.971
971681AH1-341 GEN
Solar/Wind Harmer
19.548
971171AH1-044 GEN
Solar/Wind Harmer
21.842
961011AF2-392 GEN
Solar/Wind Harmer
11.668
946321AF1-296 GEN
Solar/Wind Harmer
9.025
971675AH1-338 GEN
Solar/Wind Harmer
13.322
971177AH1-047 GEN
Solar/Wind Harmer
3.423
972031AH1-564 GEN
50/50
31.109
274824ROCKFORD ;12
50/50
28.82
274822ROCKFORD ;11
50/50
37.14
274657BYRON ;2U
50/50
12.007
972235AH1-702 GEN1
50/50
4.364
970819AG2-516 GEN
Solar/Wind Harmer
19.524
971475AH1-234 GEN
Solar/Wind Harmer
35.705
274857EASY ROAD;U1
Solar/Wind Harmer
6.261
274761LEE CO EC;2U
Adder
12.155
274766LEE CO EC;7U
Adder
12.012
957471AF2-041 GEN
Solar/Wind Harmer
32.763
959081AF2-199 GEN
Solar/Wind Harmer
10.921
971067AG2-660 GEN
Solar/Wind Harmer
2.54
276158O29GEN2
Solar/Wind Harmer
4.501
276861AD2-134 GEN
Solar/Wind Harmer
1.33
960751AF2-366 GEN
Solar/Wind Harmer
1.883
962781AG1-127 GEN
Solar/Wind Harmer
6.242
274872LEEDK;1U
Solar/Wind Harmer
5.07
990512J1326
External Queue
7.586848735809326
990117J1214
External Queue
26.098758697509766
990727J1377 G
External Queue
11.226364135742188
991092J1477
External Queue
2.9171924591064453
990407J1304
External Queue
6.372202396392822
NYPJM->LTFIMP_NY
CLTF
0.196
WECLTFEXP_WEC->PJM
CLTF
0.471
CPLELTFEXP_CPLE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.803
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.918
MECLTFEXP_MEC->PJM
CLTF
8.533
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.301
LAGNLTFEXP_LAGN->PJM
CLTF
2.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
TVALTFEXP_TVA->PJM
CLTF
0.648

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_111-45-L11124__SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.48 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1701.01
MW Contribution:19.52
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
36.874
971411AH1-196 GEN
Solar/Wind Harmer
59.956
276612AE2-035 GEN
Solar/Wind Harmer
3.971
971681AH1-341 GEN
Solar/Wind Harmer
19.548
971171AH1-044 GEN
Solar/Wind Harmer
21.842
961011AF2-392 GEN
Solar/Wind Harmer
11.668
946321AF1-296 GEN
Solar/Wind Harmer
9.025
971675AH1-338 GEN
Solar/Wind Harmer
13.322
971177AH1-047 GEN
Solar/Wind Harmer
3.423
274856ECOGROVE ;U1
Solar/Wind Harmer
5.234
276611AD2-172 GEN
Solar/Wind Harmer
3.971
938861AE1-114 GEN
Solar/Wind Harmer
10.904
274764LEE CO EC;5U
Adder
12.183
274765LEE CO EC;6U
Adder
12.183
274762LEE CO EC;3U
Adder
12.155
274763LEE CO EC;4U
Adder
12.04
276603SUBLETTE C
Solar/Wind Harmer
1.154
972267AH1-718 GEN
Adder
4.55
971341AH1-150 GEN
Solar/Wind Harmer
21.842
971343AH1-151 GEN
Solar/Wind Harmer
21.842
971333AH1-146 GEN
Solar/Wind Harmer
20.489
971335AH1-147 GEN
Solar/Wind Harmer
20.489
276741O09 GEN1
Solar/Wind Harmer
3.215
276708O09 GEN2
Solar/Wind Harmer
3.215
970921AG2-575 GEN
Solar/Wind Harmer
6.564
970921AG2-575 GEN
Solar/Wind Harmer
1.527
962691AG1-118 GEN
Solar/Wind Harmer
15.751
942991AE2-321 GEN
Solar/Wind Harmer
5.127
972236AH1-702 GEN2
50/50
3.807
274656BYRON ;1U
50/50
12.275
274858EASY ROAD;U2
Solar/Wind Harmer
6.261
274760LEE CO EC;1U
Adder
12.155
274767LEE CO EC;8U
Adder
12.012
959091AF2-200 GEN
Solar/Wind Harmer
21.842
276157O29GEN1
Solar/Wind Harmer
3.423
965931AG1-462 GEN
Solar/Wind Harmer
21.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.751
274850MENDOTA H;RU
Solar/Wind Harmer
1.913
276602WESTBROOK C
Solar/Wind Harmer
1.583
276863AD2-134 GEN
Solar/Wind Harmer
1.33
276799AD1-013 GEN
Solar/Wind Harmer
1.623
946671AF1-331 GEN
Solar/Wind Harmer
0.307
274872LEEDK;1U
Solar/Wind Harmer
0.158
972031AH1-564 GEN
50/50
31.109
274824ROCKFORD ;12
50/50
28.82
274822ROCKFORD ;11
50/50
37.14
274657BYRON ;2U
50/50
12.007
972235AH1-702 GEN1
50/50
4.364
970819AG2-516 GEN
Solar/Wind Harmer
19.524
971475AH1-234 GEN
Solar/Wind Harmer
35.705
274857EASY ROAD;U1
Solar/Wind Harmer
6.261
274761LEE CO EC;2U
Adder
12.155
274766LEE CO EC;7U
Adder
12.012
957471AF2-041 GEN
Solar/Wind Harmer
32.763
959081AF2-199 GEN
Solar/Wind Harmer
10.921
971067AG2-660 GEN
Solar/Wind Harmer
2.54
276158O29GEN2
Solar/Wind Harmer
4.501
276861AD2-134 GEN
Solar/Wind Harmer
1.33
960751AF2-366 GEN
Solar/Wind Harmer
1.883
962781AG1-127 GEN
Solar/Wind Harmer
6.242
274872LEEDK;1U
Solar/Wind Harmer
5.07
990512J1326
External Queue
7.586848735809326
990117J1214
External Queue
26.098758697509766
990727J1377 G
External Queue
11.226364135742188
991092J1477
External Queue
2.9171924591064453
990407J1304
External Queue
6.372202396392822
NYPJM->LTFIMP_NY
CLTF
0.196
WECLTFEXP_WEC->PJM
CLTF
0.471
CPLELTFEXP_CPLE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.803
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.918
MECLTFEXP_MEC->PJM
CLTF
8.533
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.301
LAGNLTFEXP_LAGN->PJM
CLTF
2.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
TVALTFEXP_TVA->PJM
CLTF
0.648

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P4_111-45-TR81____SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.48 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1701.01
MW Contribution:19.52
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
36.874
971411AH1-196 GEN
Solar/Wind Harmer
59.956
276612AE2-035 GEN
Solar/Wind Harmer
3.971
971681AH1-341 GEN
Solar/Wind Harmer
19.548
971171AH1-044 GEN
Solar/Wind Harmer
21.842
961011AF2-392 GEN
Solar/Wind Harmer
11.668
946321AF1-296 GEN
Solar/Wind Harmer
9.025
971675AH1-338 GEN
Solar/Wind Harmer
13.322
971177AH1-047 GEN
Solar/Wind Harmer
3.423
274856ECOGROVE ;U1
Solar/Wind Harmer
5.234
276611AD2-172 GEN
Solar/Wind Harmer
3.971
938861AE1-114 GEN
Solar/Wind Harmer
10.904
274764LEE CO EC;5U
Adder
12.183
274765LEE CO EC;6U
Adder
12.183
274762LEE CO EC;3U
Adder
12.155
274763LEE CO EC;4U
Adder
12.04
276603SUBLETTE C
Solar/Wind Harmer
1.154
972267AH1-718 GEN
Adder
4.55
971341AH1-150 GEN
Solar/Wind Harmer
21.842
971343AH1-151 GEN
Solar/Wind Harmer
21.842
971333AH1-146 GEN
Solar/Wind Harmer
20.489
971335AH1-147 GEN
Solar/Wind Harmer
20.489
276741O09 GEN1
Solar/Wind Harmer
3.215
276708O09 GEN2
Solar/Wind Harmer
3.215
970921AG2-575 GEN
Solar/Wind Harmer
6.564
970921AG2-575 GEN
Solar/Wind Harmer
1.527
962691AG1-118 GEN
Solar/Wind Harmer
15.751
942991AE2-321 GEN
Solar/Wind Harmer
5.127
972031AH1-564 GEN
50/50
31.109
274824ROCKFORD ;12
50/50
28.82
274822ROCKFORD ;11
50/50
37.14
274657BYRON ;2U
50/50
12.007
972235AH1-702 GEN1
50/50
4.364
970819AG2-516 GEN
Solar/Wind Harmer
19.524
971475AH1-234 GEN
Solar/Wind Harmer
35.705
274857EASY ROAD;U1
Solar/Wind Harmer
6.261
274761LEE CO EC;2U
Adder
12.155
274766LEE CO EC;7U
Adder
12.012
957471AF2-041 GEN
Solar/Wind Harmer
32.763
959081AF2-199 GEN
Solar/Wind Harmer
10.921
971067AG2-660 GEN
Solar/Wind Harmer
2.54
276158O29GEN2
Solar/Wind Harmer
4.501
276861AD2-134 GEN
Solar/Wind Harmer
1.33
960751AF2-366 GEN
Solar/Wind Harmer
1.883
962781AG1-127 GEN
Solar/Wind Harmer
6.242
274872LEEDK;1U
Solar/Wind Harmer
5.07
972236AH1-702 GEN2
50/50
3.807
274656BYRON ;1U
50/50
12.275
274858EASY ROAD;U2
Solar/Wind Harmer
6.261
274760LEE CO EC;1U
Adder
12.155
274767LEE CO EC;8U
Adder
12.012
959091AF2-200 GEN
Solar/Wind Harmer
21.842
276157O29GEN1
Solar/Wind Harmer
3.423
965931AG1-462 GEN
Solar/Wind Harmer
21.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.751
274850MENDOTA H;RU
Solar/Wind Harmer
1.913
276602WESTBROOK C
Solar/Wind Harmer
1.583
276863AD2-134 GEN
Solar/Wind Harmer
1.33
276799AD1-013 GEN
Solar/Wind Harmer
1.623
946671AF1-331 GEN
Solar/Wind Harmer
0.307
274872LEEDK;1U
Solar/Wind Harmer
0.158
990512J1326
External Queue
7.586848735809326
990117J1214
External Queue
26.098758697509766
990727J1377 G
External Queue
11.226364135742188
991092J1477
External Queue
2.9171924591064453
990407J1304
External Queue
6.372202396392822
NYPJM->LTFIMP_NY
CLTF
0.196
WECLTFEXP_WEC->PJM
CLTF
0.471
CPLELTFEXP_CPLE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.803
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.918
MECLTFEXP_MEC->PJM
CLTF
8.533
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.301
LAGNLTFEXP_LAGN->PJM
CLTF
2.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
TVALTFEXP_TVA->PJM
CLTF
0.648

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L92805__B-R_SRT-A-2


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L92805__B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.3 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1682.43
MW Contribution:16.21
Bus #Bus NameTypeMW Contribution
971333AH1-146 GEN
Solar/Wind Harmer
30.22
971335AH1-147 GEN
Solar/Wind Harmer
30.22
274856ECOGROVE ;U1
Solar/Wind Harmer
0.297
276611AD2-172 GEN
Solar/Wind Harmer
0.003
274764LEE CO EC;5U
Adder
14.092
274765LEE CO EC;6U
Adder
14.092
274762LEE CO EC;3U
Adder
14.059
274763LEE CO EC;4U
Adder
13.926
938861AE1-114 GEN
Solar/Wind Harmer
5.864
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.5
276741O09 GEN1
Solar/Wind Harmer
0.225
276708O09 GEN2
Solar/Wind Harmer
0.225
970921AG2-575 GEN
Solar/Wind Harmer
5.22
970921AG2-575 GEN
Solar/Wind Harmer
1.74
942991AE2-321 GEN
Solar/Wind Harmer
5.226
962691AG1-118 GEN
Solar/Wind Harmer
12.465
971341AH1-150 GEN
Solar/Wind Harmer
7.105
971343AH1-151 GEN
Solar/Wind Harmer
7.105
274657BYRON ;2U
50/50
15.91
972235AH1-702 GEN1
50/50
5.794
972031AH1-564 GEN
50/50
36.735
274824ROCKFORD ;12
50/50
34.034
274822ROCKFORD ;11
50/50
43.859
971475AH1-234 GEN
Solar/Wind Harmer
6.647
970819AG2-516 GEN
Solar/Wind Harmer
16.208
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
14.059
274766LEE CO EC;7U
Adder
13.893
276158O29GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.102
962781AG1-127 GEN
Solar/Wind Harmer
4.968
274872LEEDK;1U
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
10.658
959081AF2-199 GEN
Solar/Wind Harmer
3.553
971067AG2-660 GEN
Solar/Wind Harmer
1.184
274823ROCKFORD ;21
50/50
43.543
971411AH1-196 GEN
Solar/Wind Harmer
44.434
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
16.017
961011AF2-392 GEN
Solar/Wind Harmer
4.469
946321AF1-296 GEN
Solar/Wind Harmer
3.454
971675AH1-338 GEN
Solar/Wind Harmer
2.199
971177AH1-047 GEN
Solar/Wind Harmer
3.216
971171AH1-044 GEN
Solar/Wind Harmer
7.105
972236AH1-702 GEN2
50/50
5.044
274656BYRON ;1U
50/50
16.295
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
14.059
274767LEE CO EC;8U
Adder
13.893
276157O29GEN1
Solar/Wind Harmer
1.023
965931AG1-462 GEN
Solar/Wind Harmer
15.268
274855GSG-6 ;RU
Solar/Wind Harmer
0.208
274850MENDOTA H;RU
Solar/Wind Harmer
0.067
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.102
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
7.105
990512J1326
External Queue
9.427095413208008
990117J1214
External Queue
32.42920684814453
990727J1377 G
External Queue
13.966062545776367
991092J1477
External Queue
2.8649470806121826
991777J1629 G
External Queue
9.148280143737793
990407J1304
External Queue
7.983032703399658
NYPJM->LTFIMP_NY
CLTF
0.236
WECLTFEXP_WEC->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.911
MECLTFEXP_MEC->PJM
CLTF
9.223
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.411
LAGNLTFEXP_LAGN->PJM
CLTF
2.56
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.657

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0626__B-R_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.44 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1621.92
MW Contribution:16.21
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
43.543
971411AH1-196 GEN
Solar/Wind Harmer
44.434
274856ECOGROVE ;U1
Solar/Wind Harmer
0.297
276611AD2-172 GEN
Solar/Wind Harmer
0.003
274764LEE CO EC;5U
Adder
14.092
274765LEE CO EC;6U
Adder
14.092
274762LEE CO EC;3U
Adder
14.059
274763LEE CO EC;4U
Adder
13.926
938861AE1-114 GEN
Solar/Wind Harmer
5.864
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.5
276741O09 GEN1
Solar/Wind Harmer
0.225
276708O09 GEN2
Solar/Wind Harmer
0.225
970921AG2-575 GEN
Solar/Wind Harmer
5.22
970921AG2-575 GEN
Solar/Wind Harmer
1.74
942991AE2-321 GEN
Solar/Wind Harmer
5.226
962691AG1-118 GEN
Solar/Wind Harmer
12.465
971341AH1-150 GEN
Solar/Wind Harmer
7.105
971343AH1-151 GEN
Solar/Wind Harmer
7.105
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
16.017
961011AF2-392 GEN
Solar/Wind Harmer
4.469
946321AF1-296 GEN
Solar/Wind Harmer
3.454
971675AH1-338 GEN
Solar/Wind Harmer
2.199
971177AH1-047 GEN
Solar/Wind Harmer
3.216
971171AH1-044 GEN
Solar/Wind Harmer
7.105
274657BYRON ;2U
50/50
15.91
972235AH1-702 GEN1
50/50
5.794
972031AH1-564 GEN
50/50
36.735
274824ROCKFORD ;12
50/50
34.034
274822ROCKFORD ;11
50/50
43.859
971475AH1-234 GEN
Solar/Wind Harmer
6.647
970819AG2-516 GEN
Solar/Wind Harmer
16.208
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
14.059
274766LEE CO EC;7U
Adder
13.893
276158O29GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.102
962781AG1-127 GEN
Solar/Wind Harmer
4.968
274872LEEDK;1U
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
10.658
959081AF2-199 GEN
Solar/Wind Harmer
3.553
971067AG2-660 GEN
Solar/Wind Harmer
1.184
972236AH1-702 GEN2
50/50
5.044
274656BYRON ;1U
50/50
16.295
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
14.059
274767LEE CO EC;8U
Adder
13.893
276157O29GEN1
Solar/Wind Harmer
1.023
965931AG1-462 GEN
Solar/Wind Harmer
15.268
274855GSG-6 ;RU
Solar/Wind Harmer
0.208
274850MENDOTA H;RU
Solar/Wind Harmer
0.067
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.102
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
7.105
990512J1326
External Queue
9.427095413208008
990117J1214
External Queue
32.42920684814453
990727J1377 G
External Queue
13.966062545776367
991092J1477
External Queue
2.8649470806121826
991777J1629 G
External Queue
9.148280143737793
990407J1304
External Queue
7.983032703399658
NYPJM->LTFIMP_NY
CLTF
0.236
WECLTFEXP_WEC->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.911
MECLTFEXP_MEC->PJM
CLTF
9.223
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.411
LAGNLTFEXP_LAGN->PJM
CLTF
2.56
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.657

Details for AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:CE
Facility Description:
AF2-349 TP-SILVER LK; R 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.38 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1205.57
MW Contribution:12.59
Bus #Bus NameTypeMW Contribution
972236AH1-702 GEN2
50/50
3.509
274656BYRON ;1U
50/50
11.309
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.875
274767LEE CO EC;8U
Adder
9.759
276157O29GEN1
Solar/Wind Harmer
0.74
274855GSG-6 ;RU
Solar/Wind Harmer
0.163
274850MENDOTA H;RU
Solar/Wind Harmer
0.052
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.08
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.47
965931AG1-462 GEN
Solar/Wind Harmer
10.927
274872LEEDK;1U
Solar/Wind Harmer
0.143
972031AH1-564 GEN
50/50
29.295
274824ROCKFORD ;12
50/50
27.14
274822ROCKFORD ;11
50/50
34.975
274657BYRON ;2U
50/50
11.067
972235AH1-702 GEN1
50/50
4.021
970819AG2-516 GEN
Solar/Wind Harmer
12.59
971475AH1-234 GEN
Solar/Wind Harmer
5.032
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.875
274766LEE CO EC;7U
Adder
9.759
276158O29GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.08
962781AG1-127 GEN
Solar/Wind Harmer
4.064
274872LEEDK;1U
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
50/50
34.725
971411AH1-196 GEN
Solar/Wind Harmer
41.13
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
12.35
961011AF2-392 GEN
Solar/Wind Harmer
3.259
946321AF1-296 GEN
Solar/Wind Harmer
2.488
971675AH1-338 GEN
Solar/Wind Harmer
1.728
971177AH1-047 GEN
Solar/Wind Harmer
2.294
274856ECOGROVE ;U1
Solar/Wind Harmer
0.231
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
4.484
274764LEE CO EC;5U
Adder
9.898
274765LEE CO EC;6U
Adder
9.898
274762LEE CO EC;3U
Adder
9.875
274763LEE CO EC;4U
Adder
9.782
971333AH1-146 GEN
Solar/Wind Harmer
13.206
971335AH1-147 GEN
Solar/Wind Harmer
13.206
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
3.211
276741O09 GEN1
Solar/Wind Harmer
0.163
276708O09 GEN2
Solar/Wind Harmer
0.163
970921AG2-575 GEN
Solar/Wind Harmer
4.27
970921AG2-575 GEN
Solar/Wind Harmer
1.423
962691AG1-118 GEN
Solar/Wind Harmer
10.292
942991AE2-321 GEN
Solar/Wind Harmer
3.622
990512J1326
External Queue
7.093409538269043
990117J1214
External Queue
24.40132713317871
990727J1377 G
External Queue
10.617561340332031
990407J1304
External Queue
6.031682968139648
NYPJM->LTFIMP_NY
CLTF
0.165
WECLTFEXP_WEC->PJM
CLTF
0.345
CBM West 2LTFEXP_CBM-W2->PJM
CBM
9.513
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.08
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.389
MECLTFEXP_MEC->PJM
CLTF
6.605
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.1
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.282
LAGNLTFEXP_LAGN->PJM
CLTF
1.842
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.143
TVALTFEXP_TVA->PJM
CLTF
0.476

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.57 %
Rating:1413.0 MVA
Rating Type:B
MVA to Mitigate:1590.63
MW Contribution:9.15
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
8.967
274753CRETE EC ;3U
50/50
8.967
274654BRAIDWOOD;1U
50/50
6.817
972228AH1-698 GEN2
50/50
3.507
960281AF2-319 GEN
50/50
2.035
972231SS25-0005
Solar/Wind Harmer
16.408
972181SS23-001
Solar/Wind Harmer
10.255
274676JOLIET 29;8U
Adder
25.878
274826FISK ;BP
Adder
9.547
274730ELWOOD EC;6P
Adder
14.283
274734ELWOOD EC;8P
Adder
14.283
274736ELWOOD EC;9P
Adder
14.283
274729ELWOOD EC;1P
Adder
14.269
970707AG2-453 GEN
Solar/Wind Harmer
23.916
276772AC2-154 GEN
Solar/Wind Harmer
2.372
276806AD2-047 C O1
Solar/Wind Harmer
9.101
970941AG2-585 GEN
Solar/Wind Harmer
10.634
274772LINCOLN ;3U
Adder
5.254
276897AD1-100 C
Solar/Wind Harmer
24.564
939351AE1-166 GEN
Solar/Wind Harmer
5.019
276893AG1-478 C
Solar/Wind Harmer
0.353
274800UNIV PARK;3U
Adder
4.847
972038AH1-567 GEN2
Adder
0.303
943121AE2-341 GEN
Solar/Wind Harmer
12.41
943591AF1-030 GEN
Solar/Wind Harmer
8.274
274682WAUKEGAN ;7U
Adder
14.799
274802UNIV PARK;5U
Adder
4.735
276694AA1-018 GEN2
Solar/Wind Harmer
5.086
274872LEEDK;1U
Solar/Wind Harmer
0.203
274724RIVER EC ;11
Adder
13.992
276805AD2-038 GEN
Solar/Wind Harmer
4.052
276799AD1-013 GEN
Solar/Wind Harmer
1.727
946671AF1-331 GEN
Solar/Wind Harmer
0.327
274855GSG-6 ;RU
Solar/Wind Harmer
2.882
274850MENDOTA H;RU
Solar/Wind Harmer
2.004
276602WESTBROOK C
Solar/Wind Harmer
1.659
276863AD2-134 GEN
Solar/Wind Harmer
1.394
959091AF2-200 GEN
Solar/Wind Harmer
15.464
276889AE2-281 GEN
Solar/Wind Harmer
1.473
972236AH1-702 GEN2
Adder
1.682
970571AG2-364 GEN
Solar/Wind Harmer
15.046
274858EASY ROAD;U2
Solar/Wind Harmer
3.564
274760LEE CO EC;1U
Adder
6.919
274767LEE CO EC;8U
Adder
6.837
276157O29GEN1
Solar/Wind Harmer
2.739
274878BISHOP HL;2U
Solar/Wind Harmer
2.344
965931AG1-462 GEN
Solar/Wind Harmer
17.298
942111AE2-223 GEN
Solar/Wind Harmer
5.038
274853TWINGROVE;U1
Solar/Wind Harmer
4.215
965091AG1-374 GEN
Solar/Wind Harmer
17.543
959611AF2-252 GEN
Solar/Wind Harmer
1.36
270535AF1-215 GEN1
Solar/Wind Helper
0.862
274751CRETE EC ;1U
50/50
8.967
274754CRETE EC ;4U
50/50
8.967
274655BRAIDWOOD;2U
50/50
6.406
274676JOLIET 29;8U
Adder
26.836
274732ELWOOD EC;7P
Adder
14.283
276776AD2-060 GEN
Solar/Wind Harmer
0.36
972207SS24-0001
Solar/Wind Harmer
18.682
274773LINCOLN ;4U
Adder
5.254
274774LINCOLN ;5U
Adder
5.254
941551AE2-152 GEN
Solar/Wind Harmer
3.839
274871GR RIDGE ;2U
Solar/Wind Harmer
6.491
274674JOLIET 9 ;6U
Adder
12.946
274801UNIV PARK;4U
Adder
4.847
274745AC1-111 GEN9
Adder
4.645
276164X3-005 C
Solar/Wind Harmer
0.582
274682WAUKEGAN ;7U
Adder
14.799
274828WAUKEGAN ;BP
Adder
9.073
276691AA1-018 GEN1
Solar/Wind Harmer
0.375
960751AF2-366 GEN
Solar/Wind Harmer
2.291
962781AG1-127 GEN
Solar/Wind Harmer
7.594
274872LEEDK;1U
Solar/Wind Harmer
6.528
274723RIVER EC ;12
Adder
14.143
276901AD2-066 C O1
Solar/Wind Harmer
2.763
276861AD2-134 GEN
Solar/Wind Harmer
1.394
971997AH1-543 GEN
Solar/Wind Harmer
12.197
957471AF2-041 GEN
Solar/Wind Harmer
23.196
959081AF2-199 GEN
Solar/Wind Harmer
7.732
971067AG2-660 GEN
Solar/Wind Harmer
1.798
274822ROCKFORD ;11
Adder
15.138
276876AE1-163_GEN2
Solar/Wind Harmer
5.156
972235AH1-702 GEN1
Adder
1.934
970819AG2-516 GEN
Solar/Wind Harmer
9.155
971475AH1-234 GEN
Solar/Wind Harmer
17.022
939401AE1-172 GEN
Solar/Wind Harmer
10.55
970569AG2-363 GEN
Solar/Wind Harmer
22.569
274812UNIV PK N;8U
Adder
3.736
274857EASY ROAD;U1
Solar/Wind Harmer
3.564
274761LEE CO EC;2U
Adder
6.919
274766LEE CO EC;7U
Adder
6.837
276158O29GEN2
Solar/Wind Harmer
3.601
274877BISHOP HL;1U
Solar/Wind Harmer
2.344
276726Z2-087_GEN
Solar/Wind Harmer
4.861
939741AE1-205 GEN
Solar/Wind Harmer
12.292
274854TWINGROVE;U2
Solar/Wind Harmer
4.126
972175AH1-670 GEN
Solar/Wind Harmer
7.203
270055AF2-134 C O1
Solar/Wind Helper
0.575
972227AH1-698 GEN1
50/50
2.472
274687WILL CNTY;4U
50/50
26.309
274687WILL CNTY;4U
50/50
26.309
960681AF2-359 GEN
Solar/Wind Harmer
26.799
274675JOLIET 29;7U
Adder
26.83
274675JOLIET 29;7U
Adder
25.871
274827FISK ;RP
Adder
6.766
274728ELWOOD EC;5P
Adder
14.283
274731ELWOOD EC;2P
Adder
14.269
274733ELWOOD EC;3P
Adder
14.269
274735ELWOOD EC;4P
Adder
14.269
960591AF2-350 GEN
Solar/Wind Harmer
8.508
274775LINCOLN ;6U
Adder
5.254
274776LINCOLN ;7U
Adder
5.254
274777LINCOLN ;8U
Adder
5.254
970833AG2-524 GEN
Solar/Wind Harmer
7.36
970833AG2-524 GEN
Solar/Wind Harmer
3.423
274746AC1-111 G10
Adder
4.645
274744AC1-111 GEN8
Adder
4.645
972037AH1-567 GEN1
Adder
0.149
276868AE1-113 GEN
Solar/Wind Harmer
8.067
276882AE2-255 GEN
Solar/Wind Harmer
2.689
971177AH1-047 GEN
Solar/Wind Harmer
4.645
971411AH1-196 GEN
Solar/Wind Harmer
11.803
971675AH1-338 GEN
Solar/Wind Harmer
14.054
971171AH1-044 GEN
Solar/Wind Harmer
15.464
274823ROCKFORD ;21
Adder
15.029
276612AE2-035 GEN
Solar/Wind Harmer
1.945
971681AH1-341 GEN
Solar/Wind Harmer
11.233
274814UNIV PK N;0U
Adder
3.769
274807UNIV PK N;3U
Adder
3.761
274805UNIV PK N;1U
Adder
3.744
274811UNIV PK N;7U
Adder
3.736
926823AC1-168 GEN
Solar/Wind Harmer
3.168
961011AF2-392 GEN
Solar/Wind Harmer
7.953
274863CRW1-WTG
Solar/Wind Harmer
4.05
274864CRW2-WTG
Solar/Wind Harmer
4.05
957751AF2-069 GEN
Solar/Wind Harmer
0.321
970169AG2-114 GEN
Solar/Wind Harmer
6.948
946321AF1-296 GEN
Solar/Wind Harmer
7.157
274848CAMPGROVE;RU
Solar/Wind Harmer
4.427
276655WTG1_EQ
Solar/Wind Harmer
5.366
276656WTG2_EQ
Solar/Wind Harmer
0.71
959341AF2-225 GEN
Solar/Wind Harmer
9.219
941731AE2-173 GEN
Solar/Wind Harmer
3.573
270536AF1-215 GEN2
Solar/Wind Helper
0.862
959351AF2-226 GEN
50/50
2.035
965681AG1-436 GEN
Solar/Wind Harmer
88.67
965791AG1-447 GEN
Solar/Wind Harmer
45.366
274861TOP CROP ;1U
Solar/Wind Harmer
5.303
274862TOP CROP ;2U
Solar/Wind Harmer
4.428
972259AH1-714 GEN
Adder
16.603
274888KELLY CRK;1U
Solar/Wind Harmer
5.023
274887GEN-1.85
Solar/Wind Harmer
4.535
276843GEN-1.7
Solar/Wind Harmer
0.488
958011AF2-095 GEN
Solar/Wind Harmer
12.251
274770LINCOLN ;1U
Adder
5.254
274771LINCOLN ;2U
Adder
5.254
274847GR RIDGE ;BU
Solar/Wind Harmer
4.27
274674JOLIET 9 ;6U
Adder
12.946
274683WAUKEGAN ;8U
Adder
17.31
274683WAUKEGAN ;8U
Adder
14.591
971573AH1-285 GEN
Solar/Wind Harmer
7.053
274695ROCKY RD ;2P
Adder
9.112
274693ROCKY RD ;1P
Adder
9.022
274697ROCKY RD ;3P
Adder
2.475
274696ROCKY RD ;4P
Adder
9.326
274803UNIV PARK;6U
Adder
4.735
958481AF2-142 GEN
Solar/Wind Harmer
12.088
962691AG1-118 GEN
Solar/Wind Harmer
24.064
970921AG2-575 GEN
Solar/Wind Harmer
7.985
970921AG2-575 GEN
Solar/Wind Harmer
1.857
274879MINONK ;1U
Solar/Wind Harmer
5.378
942991AE2-321 GEN
Solar/Wind Harmer
7.935
958491AF2-143 GEN
Solar/Wind Harmer
11.847
971333AH1-146 GEN
Solar/Wind Harmer
15.683
971335AH1-147 GEN
Solar/Wind Harmer
15.683
971341AH1-150 GEN
Solar/Wind Harmer
15.464
971343AH1-151 GEN
Solar/Wind Harmer
15.464
276872AE1-163_GEN1
Solar/Wind Harmer
5.156
274856ECOGROVE ;U1
Solar/Wind Harmer
2.563
276611AD2-172 GEN
Solar/Wind Harmer
1.945
938861AE1-114 GEN
Solar/Wind Harmer
6.14
274808UNIV PK N;4U
Adder
3.72
274764LEE CO EC;5U
Adder
6.935
274765LEE CO EC;6U
Adder
6.935
274762LEE CO EC;3U
Adder
6.919
274763LEE CO EC;4U
Adder
6.853
276603SUBLETTE C
Solar/Wind Harmer
0.776
972267AH1-718 GEN
Adder
3.032
276741O09 GEN1
Solar/Wind Harmer
2.572
276708O09 GEN2
Solar/Wind Harmer
2.572
274851PROVIDENC;RU
Solar/Wind Harmer
1.993
274849CRESCENT ;1U
Solar/Wind Harmer
1.294
276645AC1-214 GEN1
Solar/Wind Harmer
0.938
276646AC1-214 GEN2
Solar/Wind Harmer
0.938
276782AC1-033 GEN
Solar/Wind Harmer
2.77
960611AF2-352 GEN
Solar/Wind Harmer
1.36
990512J1326
External Queue
4.003633975982666
990762J1386
External Queue
5.75543737411499
990577J1339
External Queue
10.205135345458984
990582J1340
External Queue
7.147232532501221
NYPJM->LTFIMP_NY
CLTF
0.712
WECLTFEXP_WEC->PJM
CLTF
2.945
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.143
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.343
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.997
MECLTFEXP_MEC->PJM
CLTF
9.124
SIGELTFEXP_SIGE->PJM
CLTF
0.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.976
LAGNLTFEXP_LAGN->PJM
CLTF
2.961
TVALTFEXP_TVA->PJM
CLTF
0.743

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.57 %
Rating:1413.0 MVA
Rating Type:B
MVA to Mitigate:1590.62
MW Contribution:9.15
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
8.967
274753CRETE EC ;3U
50/50
8.967
274654BRAIDWOOD;1U
50/50
6.817
972228AH1-698 GEN2
50/50
3.507
960281AF2-319 GEN
50/50
2.035
972231SS25-0005
Solar/Wind Harmer
16.408
972181SS23-001
Solar/Wind Harmer
10.255
274676JOLIET 29;8U
Adder
25.878
274826FISK ;BP
Adder
9.547
274730ELWOOD EC;6P
Adder
14.283
274734ELWOOD EC;8P
Adder
14.283
274736ELWOOD EC;9P
Adder
14.283
274729ELWOOD EC;1P
Adder
14.269
970707AG2-453 GEN
Solar/Wind Harmer
23.916
276772AC2-154 GEN
Solar/Wind Harmer
2.372
276806AD2-047 C O1
Solar/Wind Harmer
9.101
970941AG2-585 GEN
Solar/Wind Harmer
10.634
274772LINCOLN ;3U
Adder
5.254
276897AD1-100 C
Solar/Wind Harmer
24.564
939351AE1-166 GEN
Solar/Wind Harmer
5.019
276893AG1-478 C
Solar/Wind Harmer
0.353
274800UNIV PARK;3U
Adder
4.847
972038AH1-567 GEN2
Adder
0.303
943121AE2-341 GEN
Solar/Wind Harmer
12.41
943591AF1-030 GEN
Solar/Wind Harmer
8.274
274682WAUKEGAN ;7U
Adder
14.799
274802UNIV PARK;5U
Adder
4.735
276694AA1-018 GEN2
Solar/Wind Harmer
5.086
274872LEEDK;1U
Solar/Wind Harmer
0.203
274724RIVER EC ;11
Adder
13.992
276805AD2-038 GEN
Solar/Wind Harmer
4.052
276799AD1-013 GEN
Solar/Wind Harmer
1.727
946671AF1-331 GEN
Solar/Wind Harmer
0.327
274855GSG-6 ;RU
Solar/Wind Harmer
2.882
274850MENDOTA H;RU
Solar/Wind Harmer
2.004
276602WESTBROOK C
Solar/Wind Harmer
1.659
276863AD2-134 GEN
Solar/Wind Harmer
1.394
959091AF2-200 GEN
Solar/Wind Harmer
15.464
276889AE2-281 GEN
Solar/Wind Harmer
1.473
972236AH1-702 GEN2
Adder
1.682
970571AG2-364 GEN
Solar/Wind Harmer
15.046
274858EASY ROAD;U2
Solar/Wind Harmer
3.564
274760LEE CO EC;1U
Adder
6.919
274767LEE CO EC;8U
Adder
6.837
276157O29GEN1
Solar/Wind Harmer
2.739
274878BISHOP HL;2U
Solar/Wind Harmer
2.344
965931AG1-462 GEN
Solar/Wind Harmer
17.298
942111AE2-223 GEN
Solar/Wind Harmer
5.038
274853TWINGROVE;U1
Solar/Wind Harmer
4.215
965091AG1-374 GEN
Solar/Wind Harmer
17.543
959611AF2-252 GEN
Solar/Wind Harmer
1.36
270535AF1-215 GEN1
Solar/Wind Helper
0.862
274751CRETE EC ;1U
50/50
8.967
274754CRETE EC ;4U
50/50
8.967
274655BRAIDWOOD;2U
50/50
6.406
274676JOLIET 29;8U
Adder
26.836
274732ELWOOD EC;7P
Adder
14.283
276776AD2-060 GEN
Solar/Wind Harmer
0.36
972207SS24-0001
Solar/Wind Harmer
18.682
274773LINCOLN ;4U
Adder
5.254
274774LINCOLN ;5U
Adder
5.254
941551AE2-152 GEN
Solar/Wind Harmer
3.839
274871GR RIDGE ;2U
Solar/Wind Harmer
6.491
274674JOLIET 9 ;6U
Adder
12.946
274801UNIV PARK;4U
Adder
4.847
274745AC1-111 GEN9
Adder
4.645
276164X3-005 C
Solar/Wind Harmer
0.582
274682WAUKEGAN ;7U
Adder
14.799
274828WAUKEGAN ;BP
Adder
9.073
276691AA1-018 GEN1
Solar/Wind Harmer
0.375
960751AF2-366 GEN
Solar/Wind Harmer
2.291
962781AG1-127 GEN
Solar/Wind Harmer
7.594
274872LEEDK;1U
Solar/Wind Harmer
6.528
274723RIVER EC ;12
Adder
14.143
276901AD2-066 C O1
Solar/Wind Harmer
2.763
276861AD2-134 GEN
Solar/Wind Harmer
1.394
971997AH1-543 GEN
Solar/Wind Harmer
12.197
957471AF2-041 GEN
Solar/Wind Harmer
23.196
959081AF2-199 GEN
Solar/Wind Harmer
7.732
971067AG2-660 GEN
Solar/Wind Harmer
1.798
274822ROCKFORD ;11
Adder
15.138
276876AE1-163_GEN2
Solar/Wind Harmer
5.156
972235AH1-702 GEN1
Adder
1.934
970819AG2-516 GEN
Solar/Wind Harmer
9.155
971475AH1-234 GEN
Solar/Wind Harmer
17.021
939401AE1-172 GEN
Solar/Wind Harmer
10.55
970569AG2-363 GEN
Solar/Wind Harmer
22.569
274812UNIV PK N;8U
Adder
3.736
274857EASY ROAD;U1
Solar/Wind Harmer
3.564
274761LEE CO EC;2U
Adder
6.919
274766LEE CO EC;7U
Adder
6.837
276158O29GEN2
Solar/Wind Harmer
3.601
274877BISHOP HL;1U
Solar/Wind Harmer
2.344
276726Z2-087_GEN
Solar/Wind Harmer
4.861
939741AE1-205 GEN
Solar/Wind Harmer
12.292
274854TWINGROVE;U2
Solar/Wind Harmer
4.126
972175AH1-670 GEN
Solar/Wind Harmer
7.203
270055AF2-134 C O1
Solar/Wind Helper
0.575
972227AH1-698 GEN1
50/50
2.472
274687WILL CNTY;4U
50/50
26.309
274687WILL CNTY;4U
50/50
26.309
960681AF2-359 GEN
Solar/Wind Harmer
26.799
274675JOLIET 29;7U
Adder
26.83
274675JOLIET 29;7U
Adder
25.871
274827FISK ;RP
Adder
6.766
274728ELWOOD EC;5P
Adder
14.283
274731ELWOOD EC;2P
Adder
14.269
274733ELWOOD EC;3P
Adder
14.269
274735ELWOOD EC;4P
Adder
14.269
960591AF2-350 GEN
Solar/Wind Harmer
8.508
274775LINCOLN ;6U
Adder
5.254
274776LINCOLN ;7U
Adder
5.254
274777LINCOLN ;8U
Adder
5.254
970833AG2-524 GEN
Solar/Wind Harmer
7.36
970833AG2-524 GEN
Solar/Wind Harmer
3.423
274746AC1-111 G10
Adder
4.645
274744AC1-111 GEN8
Adder
4.645
972037AH1-567 GEN1
Adder
0.149
276868AE1-113 GEN
Solar/Wind Harmer
8.066
276882AE2-255 GEN
Solar/Wind Harmer
2.689
971177AH1-047 GEN
Solar/Wind Harmer
4.645
971411AH1-196 GEN
Solar/Wind Harmer
11.803
971675AH1-338 GEN
Solar/Wind Harmer
14.053
971171AH1-044 GEN
Solar/Wind Harmer
15.464
274823ROCKFORD ;21
Adder
15.029
276612AE2-035 GEN
Solar/Wind Harmer
1.945
971681AH1-341 GEN
Solar/Wind Harmer
11.233
274814UNIV PK N;0U
Adder
3.769
274807UNIV PK N;3U
Adder
3.761
274805UNIV PK N;1U
Adder
3.744
274811UNIV PK N;7U
Adder
3.736
926823AC1-168 GEN
Solar/Wind Harmer
3.168
961011AF2-392 GEN
Solar/Wind Harmer
7.953
274863CRW1-WTG
Solar/Wind Harmer
4.05
274864CRW2-WTG
Solar/Wind Harmer
4.05
957751AF2-069 GEN
Solar/Wind Harmer
0.321
970169AG2-114 GEN
Solar/Wind Harmer
6.949
946321AF1-296 GEN
Solar/Wind Harmer
7.157
274848CAMPGROVE;RU
Solar/Wind Harmer
4.427
276655WTG1_EQ
Solar/Wind Harmer
5.366
276656WTG2_EQ
Solar/Wind Harmer
0.71
959341AF2-225 GEN
Solar/Wind Harmer
9.219
941731AE2-173 GEN
Solar/Wind Harmer
3.573
270536AF1-215 GEN2
Solar/Wind Helper
0.862
959351AF2-226 GEN
50/50
2.035
965681AG1-436 GEN
Solar/Wind Harmer
88.67
965791AG1-447 GEN
Solar/Wind Harmer
45.366
274861TOP CROP ;1U
Solar/Wind Harmer
5.303
274862TOP CROP ;2U
Solar/Wind Harmer
4.428
972259AH1-714 GEN
Adder
16.603
274888KELLY CRK;1U
Solar/Wind Harmer
5.023
274887GEN-1.85
Solar/Wind Harmer
4.535
276843GEN-1.7
Solar/Wind Harmer
0.488
958011AF2-095 GEN
Solar/Wind Harmer
12.251
274770LINCOLN ;1U
Adder
5.254
274771LINCOLN ;2U
Adder
5.254
274847GR RIDGE ;BU
Solar/Wind Harmer
4.27
274674JOLIET 9 ;6U
Adder
12.946
274683WAUKEGAN ;8U
Adder
17.31
274683WAUKEGAN ;8U
Adder
14.591
971573AH1-285 GEN
Solar/Wind Harmer
7.053
274695ROCKY RD ;2P
Adder
9.112
274693ROCKY RD ;1P
Adder
9.022
274697ROCKY RD ;3P
Adder
2.475
274696ROCKY RD ;4P
Adder
9.326
274803UNIV PARK;6U
Adder
4.735
958481AF2-142 GEN
Solar/Wind Harmer
12.088
962691AG1-118 GEN
Solar/Wind Harmer
24.064
970921AG2-575 GEN
Solar/Wind Harmer
7.985
970921AG2-575 GEN
Solar/Wind Harmer
1.857
274879MINONK ;1U
Solar/Wind Harmer
5.378
942991AE2-321 GEN
Solar/Wind Harmer
7.935
958491AF2-143 GEN
Solar/Wind Harmer
11.847
971333AH1-146 GEN
Solar/Wind Harmer
15.683
971335AH1-147 GEN
Solar/Wind Harmer
15.683
971341AH1-150 GEN
Solar/Wind Harmer
15.464
971343AH1-151 GEN
Solar/Wind Harmer
15.464
276872AE1-163_GEN1
Solar/Wind Harmer
5.156
274856ECOGROVE ;U1
Solar/Wind Harmer
2.563
276611AD2-172 GEN
Solar/Wind Harmer
1.945
938861AE1-114 GEN
Solar/Wind Harmer
6.14
274808UNIV PK N;4U
Adder
3.72
274764LEE CO EC;5U
Adder
6.935
274765LEE CO EC;6U
Adder
6.935
274762LEE CO EC;3U
Adder
6.919
274763LEE CO EC;4U
Adder
6.853
276603SUBLETTE C
Solar/Wind Harmer
0.776
972267AH1-718 GEN
Adder
3.032
276741O09 GEN1
Solar/Wind Harmer
2.572
276708O09 GEN2
Solar/Wind Harmer
2.572
274851PROVIDENC;RU
Solar/Wind Harmer
1.993
274849CRESCENT ;1U
Solar/Wind Harmer
1.294
276645AC1-214 GEN1
Solar/Wind Harmer
0.938
276646AC1-214 GEN2
Solar/Wind Harmer
0.938
276782AC1-033 GEN
Solar/Wind Harmer
2.77
960611AF2-352 GEN
Solar/Wind Harmer
1.36
990512J1326
External Queue
4.003602504730225
990762J1386
External Queue
5.755461692810059
990577J1339
External Queue
10.205183982849121
990582J1340
External Queue
7.1472673416137695
NYPJM->LTFIMP_NY
CLTF
0.712
WECLTFEXP_WEC->PJM
CLTF
2.945
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.143
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
AG2-052LTFEXP_AG2-052->PJM
LTF
0.061
AH1-155LTFEXP_AH1-155->PJM
LTF
0.091
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.141
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.343
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.997
MECLTFEXP_MEC->PJM
CLTF
9.124
SIGELTFEXP_SIGE->PJM
CLTF
0.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.976
LAGNLTFEXP_LAGN->PJM
CLTF
2.961
TVALTFEXP_TVA->PJM
CLTF
0.743

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.38 %
Rating:1413.0 MVA
Rating Type:B
MVA to Mitigate:1587.99
MW Contribution:9.08
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
8.901
274753CRETE EC ;3U
50/50
8.901
274654BRAIDWOOD;1U
50/50
6.745
972228AH1-698 GEN2
50/50
3.47
960281AF2-319 GEN
50/50
2.017
972231SS25-0005
Solar/Wind Harmer
16.287
972181SS23-001
Solar/Wind Harmer
10.179
274676JOLIET 29;8U
Adder
25.606
274826FISK ;BP
Adder
9.431
274730ELWOOD EC;6P
Adder
14.137
274734ELWOOD EC;8P
Adder
14.137
274736ELWOOD EC;9P
Adder
14.137
274729ELWOOD EC;1P
Adder
14.123
970707AG2-453 GEN
Solar/Wind Harmer
23.682
276772AC2-154 GEN
Solar/Wind Harmer
2.345
276806AD2-047 C O1
Solar/Wind Harmer
8.994
970941AG2-585 GEN
Solar/Wind Harmer
10.51
274772LINCOLN ;3U
Adder
5.193
276897AD1-100 C
Solar/Wind Harmer
24.31
939351AE1-166 GEN
Solar/Wind Harmer
4.967
276893AG1-478 C
Solar/Wind Harmer
0.349
274800UNIV PARK;3U
Adder
4.787
972038AH1-567 GEN2
Adder
0.3
943121AE2-341 GEN
Solar/Wind Harmer
12.294
943591AF1-030 GEN
Solar/Wind Harmer
8.196
274682WAUKEGAN ;7U
Adder
14.661
274802UNIV PARK;5U
Adder
4.674
276694AA1-018 GEN2
Solar/Wind Harmer
5.035
274872LEEDK;1U
Solar/Wind Harmer
0.202
276805AD2-038 GEN
Solar/Wind Harmer
4.015
274724RIVER EC ;11
Adder
13.766
276799AD1-013 GEN
Solar/Wind Harmer
1.713
946671AF1-331 GEN
Solar/Wind Harmer
0.324
274855GSG-6 ;RU
Solar/Wind Harmer
2.858
274850MENDOTA H;RU
Solar/Wind Harmer
1.987
276602WESTBROOK C
Solar/Wind Harmer
1.645
276863AD2-134 GEN
Solar/Wind Harmer
1.382
959091AF2-200 GEN
Solar/Wind Harmer
15.339
276889AE2-281 GEN
Solar/Wind Harmer
1.461
972236AH1-702 GEN2
Adder
1.669
970571AG2-364 GEN
Solar/Wind Harmer
14.939
274858EASY ROAD;U2
Solar/Wind Harmer
3.538
274760LEE CO EC;1U
Adder
6.868
274767LEE CO EC;8U
Adder
6.787
276157O29GEN1
Solar/Wind Harmer
2.721
274878BISHOP HL;2U
Solar/Wind Harmer
2.331
965931AG1-462 GEN
Solar/Wind Harmer
17.207
942111AE2-223 GEN
Solar/Wind Harmer
5.031
274853TWINGROVE;U1
Solar/Wind Harmer
4.215
965091AG1-374 GEN
Solar/Wind Harmer
17.546
959611AF2-252 GEN
Solar/Wind Harmer
1.36
270535AF1-215 GEN1
Solar/Wind Helper
0.857
274751CRETE EC ;1U
50/50
8.901
274754CRETE EC ;4U
50/50
8.901
274655BRAIDWOOD;2U
50/50
6.338
274676JOLIET 29;8U
Adder
26.554
274732ELWOOD EC;7P
Adder
14.137
276776AD2-060 GEN
Solar/Wind Harmer
0.355
972207SS24-0001
Solar/Wind Harmer
18.463
274773LINCOLN ;4U
Adder
5.193
274774LINCOLN ;5U
Adder
5.193
941551AE2-152 GEN
Solar/Wind Harmer
3.799
274871GR RIDGE ;2U
Solar/Wind Harmer
6.429
274674JOLIET 9 ;6U
Adder
12.808
274745AC1-111 GEN9
Adder
4.601
274801UNIV PARK;4U
Adder
4.787
276164X3-005 C
Solar/Wind Harmer
0.574
274682WAUKEGAN ;7U
Adder
14.661
274828WAUKEGAN ;BP
Adder
8.989
276691AA1-018 GEN1
Solar/Wind Harmer
0.371
960751AF2-366 GEN
Solar/Wind Harmer
2.271
962781AG1-127 GEN
Solar/Wind Harmer
7.528
274872LEEDK;1U
Solar/Wind Harmer
6.472
276901AD2-066 C O1
Solar/Wind Harmer
2.739
274723RIVER EC ;12
Adder
13.916
276861AD2-134 GEN
Solar/Wind Harmer
1.382
971997AH1-543 GEN
Solar/Wind Harmer
12.101
957471AF2-041 GEN
Solar/Wind Harmer
23.009
959081AF2-199 GEN
Solar/Wind Harmer
7.67
971067AG2-660 GEN
Solar/Wind Harmer
1.784
274822ROCKFORD ;11
Adder
15.017
276876AE1-163_GEN2
Solar/Wind Harmer
5.115
972235AH1-702 GEN1
Adder
1.919
970819AG2-516 GEN
Solar/Wind Harmer
9.083
971475AH1-234 GEN
Solar/Wind Harmer
16.889
939401AE1-172 GEN
Solar/Wind Harmer
10.469
970569AG2-363 GEN
Solar/Wind Harmer
22.408
274857EASY ROAD;U1
Solar/Wind Harmer
3.538
274761LEE CO EC;2U
Adder
6.868
274766LEE CO EC;7U
Adder
6.787
274812UNIV PK N;8U
Adder
3.678
276158O29GEN2
Solar/Wind Harmer
3.577
274877BISHOP HL;1U
Solar/Wind Harmer
2.331
276726Z2-087_GEN
Solar/Wind Harmer
4.854
939741AE1-205 GEN
Solar/Wind Harmer
12.275
274854TWINGROVE;U2
Solar/Wind Harmer
4.127
972175AH1-670 GEN
Solar/Wind Harmer
7.231
270055AF2-134 C O1
Solar/Wind Helper
0.572
959351AF2-226 GEN
50/50
2.017
965681AG1-436 GEN
Solar/Wind Harmer
88.381
965791AG1-447 GEN
Solar/Wind Harmer
45.218
274861TOP CROP ;1U
Solar/Wind Harmer
5.255
274862TOP CROP ;2U
Solar/Wind Harmer
4.388
972259AH1-714 GEN
Adder
16.435
274888KELLY CRK;1U
Solar/Wind Harmer
4.964
274887GEN-1.85
Solar/Wind Harmer
4.481
276843GEN-1.7
Solar/Wind Harmer
0.482
958011AF2-095 GEN
Solar/Wind Harmer
12.107
274770LINCOLN ;1U
Adder
5.193
274771LINCOLN ;2U
Adder
5.193
274847GR RIDGE ;BU
Solar/Wind Harmer
4.229
274674JOLIET 9 ;6U
Adder
12.808
274683WAUKEGAN ;8U
Adder
17.149
274683WAUKEGAN ;8U
Adder
14.456
971573AH1-285 GEN
Solar/Wind Harmer
6.988
274696ROCKY RD ;4P
Adder
9.241
274695ROCKY RD ;2P
Adder
9.028
274693ROCKY RD ;1P
Adder
8.939
274697ROCKY RD ;3P
Adder
2.452
274803UNIV PARK;6U
Adder
4.674
958481AF2-142 GEN
Solar/Wind Harmer
11.968
962691AG1-118 GEN
Solar/Wind Harmer
23.852
970921AG2-575 GEN
Solar/Wind Harmer
7.915
970921AG2-575 GEN
Solar/Wind Harmer
1.841
274879MINONK ;1U
Solar/Wind Harmer
5.333
942991AE2-321 GEN
Solar/Wind Harmer
7.867
958491AF2-143 GEN
Solar/Wind Harmer
11.739
971333AH1-146 GEN
Solar/Wind Harmer
15.551
971335AH1-147 GEN
Solar/Wind Harmer
15.551
971341AH1-150 GEN
Solar/Wind Harmer
15.339
971343AH1-151 GEN
Solar/Wind Harmer
15.339
276872AE1-163_GEN1
Solar/Wind Harmer
5.115
274856ECOGROVE ;U1
Solar/Wind Harmer
2.543
276611AD2-172 GEN
Solar/Wind Harmer
1.929
938861AE1-114 GEN
Solar/Wind Harmer
6.094
274764LEE CO EC;5U
Adder
6.884
274765LEE CO EC;6U
Adder
6.884
274762LEE CO EC;3U
Adder
6.868
274763LEE CO EC;4U
Adder
6.804
274808UNIV PK N;4U
Adder
3.662
276603SUBLETTE C
Solar/Wind Harmer
0.77
972267AH1-718 GEN
Adder
3.011
276741O09 GEN1
Solar/Wind Harmer
2.555
276708O09 GEN2
Solar/Wind Harmer
2.555
274851PROVIDENC;RU
Solar/Wind Harmer
1.982
274849CRESCENT ;1U
Solar/Wind Harmer
1.287
276645AC1-214 GEN1
Solar/Wind Harmer
0.932
276646AC1-214 GEN2
Solar/Wind Harmer
0.932
276782AC1-033 GEN
Solar/Wind Harmer
2.755
960611AF2-352 GEN
Solar/Wind Harmer
1.36
972227AH1-698 GEN1
50/50
2.446
274687WILL CNTY;4U
50/50
26.029
274687WILL CNTY;4U
50/50
26.029
960681AF2-359 GEN
Solar/Wind Harmer
26.712
274675JOLIET 29;7U
Adder
26.548
274675JOLIET 29;7U
Adder
25.6
274827FISK ;RP
Adder
6.684
274728ELWOOD EC;5P
Adder
14.137
274731ELWOOD EC;2P
Adder
14.123
274733ELWOOD EC;3P
Adder
14.123
274735ELWOOD EC;4P
Adder
14.123
960591AF2-350 GEN
Solar/Wind Harmer
8.408
274775LINCOLN ;6U
Adder
5.193
274776LINCOLN ;7U
Adder
5.193
274777LINCOLN ;8U
Adder
5.193
970833AG2-524 GEN
Solar/Wind Harmer
7.289
970833AG2-524 GEN
Solar/Wind Harmer
3.39
274746AC1-111 G10
Adder
4.601
274744AC1-111 GEN8
Adder
4.601
972037AH1-567 GEN1
Adder
0.147
276868AE1-113 GEN
Solar/Wind Harmer
7.998
276882AE2-255 GEN
Solar/Wind Harmer
2.666
971177AH1-047 GEN
Solar/Wind Harmer
4.605
971411AH1-196 GEN
Solar/Wind Harmer
11.704
971675AH1-338 GEN
Solar/Wind Harmer
13.937
971171AH1-044 GEN
Solar/Wind Harmer
15.339
274823ROCKFORD ;21
Adder
14.908
276612AE2-035 GEN
Solar/Wind Harmer
1.929
971681AH1-341 GEN
Solar/Wind Harmer
11.149
274814UNIV PK N;0U
Adder
3.71
274807UNIV PK N;3U
Adder
3.702
274805UNIV PK N;1U
Adder
3.686
274811UNIV PK N;7U
Adder
3.678
926823AC1-168 GEN
Solar/Wind Harmer
3.147
961011AF2-392 GEN
Solar/Wind Harmer
7.898
274863CRW1-WTG
Solar/Wind Harmer
4.023
274864CRW2-WTG
Solar/Wind Harmer
4.023
957751AF2-069 GEN
Solar/Wind Harmer
0.32
970169AG2-114 GEN
Solar/Wind Harmer
6.913
274848CAMPGROVE;RU
Solar/Wind Harmer
4.405
946321AF1-296 GEN
Solar/Wind Harmer
7.118
276655WTG1_EQ
Solar/Wind Harmer
5.359
276656WTG2_EQ
Solar/Wind Harmer
0.709
959341AF2-225 GEN
Solar/Wind Harmer
9.206
941731AE2-173 GEN
Solar/Wind Harmer
3.568
270536AF1-215 GEN2
Solar/Wind Helper
0.857
990512J1326
External Queue
3.9728879928588867
990762J1386
External Queue
5.6209282875061035
990577J1339
External Queue
9.971273422241211
990582J1340
External Queue
6.983445644378662
NYPJM->LTFIMP_NY
CLTF
0.711
WECLTFEXP_WEC->PJM
CLTF
2.921
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.414
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.25
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.117
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.181
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.375
MECLTFEXP_MEC->PJM
CLTF
9.122
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.225
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.614
LAGNLTFEXP_LAGN->PJM
CLTF
3.108
TVALTFEXP_TVA->PJM
CLTF
0.829

Details for AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF2-359 TP-05OLIVE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:111.86 %
Rating:1413.0 MVA
Rating Type:B
MVA to Mitigate:1580.57
MW Contribution:9.1
Bus #Bus NameTypeMW Contribution
274752CRETE EC ;2U
50/50
8.937
274753CRETE EC ;3U
50/50
8.937
274654BRAIDWOOD;1U
50/50
6.776
972228AH1-698 GEN2
50/50
3.486
960281AF2-319 GEN
50/50
2.024
972231SS25-0005
Solar/Wind Harmer
16.353
972181SS23-001
Solar/Wind Harmer
10.221
274676JOLIET 29;8U
Adder
25.725
274826FISK ;BP
Adder
9.486
274730ELWOOD EC;6P
Adder
14.199
274734ELWOOD EC;8P
Adder
14.199
274736ELWOOD EC;9P
Adder
14.199
274729ELWOOD EC;1P
Adder
14.185
970707AG2-453 GEN
Solar/Wind Harmer
23.782
276772AC2-154 GEN
Solar/Wind Harmer
2.357
276806AD2-047 C O1
Solar/Wind Harmer
9.043
970941AG2-585 GEN
Solar/Wind Harmer
10.566
274772LINCOLN ;3U
Adder
5.218
276897AD1-100 C
Solar/Wind Harmer
24.41
939351AE1-166 GEN
Solar/Wind Harmer
4.988
276893AG1-478 C
Solar/Wind Harmer
0.351
274800UNIV PARK;3U
Adder
4.815
972038AH1-567 GEN2
Adder
0.301
943121AE2-341 GEN
Solar/Wind Harmer
12.34
943591AF1-030 GEN
Solar/Wind Harmer
8.226
274682WAUKEGAN ;7U
Adder
14.713
274802UNIV PARK;5U
Adder
4.703
276694AA1-018 GEN2
Solar/Wind Harmer
5.054
274872LEEDK;1U
Solar/Wind Harmer
0.202
276805AD2-038 GEN
Solar/Wind Harmer
4.027
274724RIVER EC ;11
Adder
13.885
276799AD1-013 GEN
Solar/Wind Harmer
1.717
946671AF1-331 GEN
Solar/Wind Harmer
0.325
274855GSG-6 ;RU
Solar/Wind Harmer
2.865
274850MENDOTA H;RU
Solar/Wind Harmer
1.992
276602WESTBROOK C
Solar/Wind Harmer
1.649
276863AD2-134 GEN
Solar/Wind Harmer
1.386
959091AF2-200 GEN
Solar/Wind Harmer
15.375
276889AE2-281 GEN
Solar/Wind Harmer
1.464
972236AH1-702 GEN2
Adder
1.672
970571AG2-364 GEN
Solar/Wind Harmer
14.957
274858EASY ROAD;U2
Solar/Wind Harmer
3.543
274760LEE CO EC;1U
Adder
6.879
274767LEE CO EC;8U
Adder
6.797
276157O29GEN1
Solar/Wind Harmer
2.723
274878BISHOP HL;2U
Solar/Wind Harmer
2.33
965931AG1-462 GEN
Solar/Wind Harmer
17.197
942111AE2-223 GEN
Solar/Wind Harmer
5.007
274853TWINGROVE;U1
Solar/Wind Harmer
4.188
965091AG1-374 GEN
Solar/Wind Harmer
17.434
959611AF2-252 GEN
Solar/Wind Harmer
1.351
270535AF1-215 GEN1
Solar/Wind Helper
0.87
274751CRETE EC ;1U
50/50
8.937
274754CRETE EC ;4U
50/50
8.937
274655BRAIDWOOD;2U
50/50
6.368
274676JOLIET 29;8U
Adder
26.678
274732ELWOOD EC;7P
Adder
14.199
276776AD2-060 GEN
Solar/Wind Harmer
0.357
972207SS24-0001
Solar/Wind Harmer
18.552
274773LINCOLN ;4U
Adder
5.218
274774LINCOLN ;5U
Adder
5.218
941551AE2-152 GEN
Solar/Wind Harmer
3.815
274871GR RIDGE ;2U
Solar/Wind Harmer
6.454
274674JOLIET 9 ;6U
Adder
12.868
274745AC1-111 GEN9
Adder
4.618
274801UNIV PARK;4U
Adder
4.815
276164X3-005 C
Solar/Wind Harmer
0.578
274682WAUKEGAN ;7U
Adder
14.713
274828WAUKEGAN ;BP
Adder
9.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.373
960751AF2-366 GEN
Solar/Wind Harmer
2.278
962781AG1-127 GEN
Solar/Wind Harmer
7.55
274872LEEDK;1U
Solar/Wind Harmer
6.49
274723RIVER EC ;12
Adder
14.035
276901AD2-066 C O1
Solar/Wind Harmer
2.746
276861AD2-134 GEN
Solar/Wind Harmer
1.386
971997AH1-543 GEN
Solar/Wind Harmer
12.126
957471AF2-041 GEN
Solar/Wind Harmer
23.062
959081AF2-199 GEN
Solar/Wind Harmer
7.687
971067AG2-660 GEN
Solar/Wind Harmer
1.788
274822ROCKFORD ;11
Adder
15.051
276876AE1-163_GEN2
Solar/Wind Harmer
5.125
972235AH1-702 GEN1
Adder
1.923
970819AG2-516 GEN
Solar/Wind Harmer
9.102
971475AH1-234 GEN
Solar/Wind Harmer
16.923
939401AE1-172 GEN
Solar/Wind Harmer
10.483
970569AG2-363 GEN
Solar/Wind Harmer
22.436
274812UNIV PK N;8U
Adder
3.708
274857EASY ROAD;U1
Solar/Wind Harmer
3.543
274761LEE CO EC;2U
Adder
6.879
274766LEE CO EC;7U
Adder
6.797
276158O29GEN2
Solar/Wind Harmer
3.58
274877BISHOP HL;1U
Solar/Wind Harmer
2.33
276726Z2-087_GEN
Solar/Wind Harmer
4.831
939741AE1-205 GEN
Solar/Wind Harmer
12.216
274854TWINGROVE;U2
Solar/Wind Harmer
4.101
972175AH1-670 GEN
Solar/Wind Harmer
7.158
270055AF2-134 C O1
Solar/Wind Helper
0.58
959351AF2-226 GEN
50/50
2.024
965681AG1-436 GEN
Solar/Wind Harmer
88.58
965791AG1-447 GEN
Solar/Wind Harmer
45.32
274861TOP CROP ;1U
Solar/Wind Harmer
5.273
274862TOP CROP ;2U
Solar/Wind Harmer
4.403
972259AH1-714 GEN
Adder
16.508
274888KELLY CRK;1U
Solar/Wind Harmer
4.991
274887GEN-1.85
Solar/Wind Harmer
4.506
276843GEN-1.7
Solar/Wind Harmer
0.485
958011AF2-095 GEN
Solar/Wind Harmer
12.173
274770LINCOLN ;1U
Adder
5.218
274771LINCOLN ;2U
Adder
5.218
274847GR RIDGE ;BU
Solar/Wind Harmer
4.245
274674JOLIET 9 ;6U
Adder
12.868
274683WAUKEGAN ;8U
Adder
17.209
274683WAUKEGAN ;8U
Adder
14.506
971573AH1-285 GEN
Solar/Wind Harmer
7.013
274695ROCKY RD ;2P
Adder
9.059
274693ROCKY RD ;1P
Adder
8.97
274697ROCKY RD ;3P
Adder
2.461
274696ROCKY RD ;4P
Adder
9.273
274803UNIV PARK;6U
Adder
4.703
958481AF2-142 GEN
Solar/Wind Harmer
12.013
962691AG1-118 GEN
Solar/Wind Harmer
23.925
970921AG2-575 GEN
Solar/Wind Harmer
7.939
970921AG2-575 GEN
Solar/Wind Harmer
1.846
274879MINONK ;1U
Solar/Wind Harmer
5.347
942991AE2-321 GEN
Solar/Wind Harmer
7.889
958491AF2-143 GEN
Solar/Wind Harmer
11.775
971333AH1-146 GEN
Solar/Wind Harmer
15.592
971335AH1-147 GEN
Solar/Wind Harmer
15.592
971341AH1-150 GEN
Solar/Wind Harmer
15.375
971343AH1-151 GEN
Solar/Wind Harmer
15.375
276872AE1-163_GEN1
Solar/Wind Harmer
5.125
274856ECOGROVE ;U1
Solar/Wind Harmer
2.548
276611AD2-172 GEN
Solar/Wind Harmer
1.933
938861AE1-114 GEN
Solar/Wind Harmer
6.104
274808UNIV PK N;4U
Adder
3.692
274764LEE CO EC;5U
Adder
6.895
274765LEE CO EC;6U
Adder
6.895
274762LEE CO EC;3U
Adder
6.879
274763LEE CO EC;4U
Adder
6.814
276603SUBLETTE C
Solar/Wind Harmer
0.772
972267AH1-718 GEN
Adder
3.014
276741O09 GEN1
Solar/Wind Harmer
2.557
276708O09 GEN2
Solar/Wind Harmer
2.557
274851PROVIDENC;RU
Solar/Wind Harmer
1.982
274849CRESCENT ;1U
Solar/Wind Harmer
1.286
276645AC1-214 GEN1
Solar/Wind Harmer
0.932
276646AC1-214 GEN2
Solar/Wind Harmer
0.932
276782AC1-033 GEN
Solar/Wind Harmer
2.754
960611AF2-352 GEN
Solar/Wind Harmer
1.351
972227AH1-698 GEN1
50/50
2.458
274687WILL CNTY;4U
50/50
26.154
274687WILL CNTY;4U
50/50
26.154
960681AF2-359 GEN
Solar/Wind Harmer
26.772
274675JOLIET 29;7U
Adder
26.671
274675JOLIET 29;7U
Adder
25.719
274827FISK ;RP
Adder
6.723
274728ELWOOD EC;5P
Adder
14.199
274731ELWOOD EC;2P
Adder
14.185
274733ELWOOD EC;3P
Adder
14.185
274735ELWOOD EC;4P
Adder
14.185
960591AF2-350 GEN
Solar/Wind Harmer
8.453
274775LINCOLN ;6U
Adder
5.218
274776LINCOLN ;7U
Adder
5.218
274777LINCOLN ;8U
Adder
5.218
970833AG2-524 GEN
Solar/Wind Harmer
7.317
970833AG2-524 GEN
Solar/Wind Harmer
3.403
274746AC1-111 G10
Adder
4.618
274744AC1-111 GEN8
Adder
4.618
972037AH1-567 GEN1
Adder
0.148
276868AE1-113 GEN
Solar/Wind Harmer
8.019
276882AE2-255 GEN
Solar/Wind Harmer
2.673
971177AH1-047 GEN
Solar/Wind Harmer
4.618
971411AH1-196 GEN
Solar/Wind Harmer
11.735
971675AH1-338 GEN
Solar/Wind Harmer
13.973
971171AH1-044 GEN
Solar/Wind Harmer
15.375
274823ROCKFORD ;21
Adder
14.942
276612AE2-035 GEN
Solar/Wind Harmer
1.933
971681AH1-341 GEN
Solar/Wind Harmer
11.168
274814UNIV PK N;0U
Adder
3.74
274807UNIV PK N;3U
Adder
3.732
274805UNIV PK N;1U
Adder
3.716
274811UNIV PK N;7U
Adder
3.708
926823AC1-168 GEN
Solar/Wind Harmer
3.149
961011AF2-392 GEN
Solar/Wind Harmer
7.907
274863CRW1-WTG
Solar/Wind Harmer
4.024
274864CRW2-WTG
Solar/Wind Harmer
4.024
957751AF2-069 GEN
Solar/Wind Harmer
0.319
970169AG2-114 GEN
Solar/Wind Harmer
6.906
946321AF1-296 GEN
Solar/Wind Harmer
7.116
274848CAMPGROVE;RU
Solar/Wind Harmer
4.401
276655WTG1_EQ
Solar/Wind Harmer
5.333
276656WTG2_EQ
Solar/Wind Harmer
0.706
959341AF2-225 GEN
Solar/Wind Harmer
9.162
941731AE2-173 GEN
Solar/Wind Harmer
3.551
270536AF1-215 GEN2
Solar/Wind Helper
0.87
990512J1326
External Queue
3.9884557723999023
990762J1386
External Queue
5.717142105102539
990577J1339
External Queue
10.134504318237305
990582J1340
External Queue
7.097765922546387
NYPJM->LTFIMP_NY
CLTF
0.707
WECLTFEXP_WEC->PJM
CLTF
2.928
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.282
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.024
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
45.883
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.993
MECLTFEXP_MEC->PJM
CLTF
9.071
SIGELTFEXP_SIGE->PJM
CLTF
0.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.34
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.964
LAGNLTFEXP_LAGN->PJM
CLTF
2.947
TVALTFEXP_TVA->PJM
CLTF
0.74

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2593.18
MW Contribution:5.74
Bus #Bus NameTypeMW Contribution
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965421AG1-410 GEN
Solar/Wind Harmer
81.734
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
965431AG1-411 GEN
50/50
45.408
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
17.696
990497J1323
External Queue
1.5914489030838013
990792J1392
External Queue
5.474584102630615
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.17 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1673.97
MW Contribution:8.76
Bus #Bus NameTypeMW Contribution
274801UNIV PARK;4U
50/50
6.258
276776AD2-060 GEN
Solar/Wind Harmer
0.388
274827FISK ;RP
50/50
8.597
274687WILL CNTY;4U
50/50
26.319
274687WILL CNTY;4U
50/50
26.319
960591AF2-350 GEN
Solar/Wind Harmer
9.171
274775LINCOLN ;6U
Adder
5.453
274776LINCOLN ;7U
Adder
5.453
274777LINCOLN ;8U
Adder
5.453
274675JOLIET 29;7U
Adder
25.5
274675JOLIET 29;7U
Adder
24.589
274728ELWOOD EC;5P
Adder
13.475
274731ELWOOD EC;2P
Adder
13.457
274733ELWOOD EC;3P
Adder
13.457
274735ELWOOD EC;4P
Adder
13.457
972037AH1-567 GEN1
Adder
0.149
972227AH1-698 GEN1
Adder
2.078
274746AC1-111 G10
Adder
4.442
274744AC1-111 GEN8
Adder
4.442
970833AG2-524 GEN
Solar/Wind Harmer
6.885
970833AG2-524 GEN
Solar/Wind Harmer
3.202
276868AE1-113 GEN
Solar/Wind Harmer
7.674
276882AE2-255 GEN
Solar/Wind Harmer
2.558
971177AH1-047 GEN
Solar/Wind Harmer
4.441
971411AH1-196 GEN
Solar/Wind Harmer
11.286
971675AH1-338 GEN
Solar/Wind Harmer
13.442
971171AH1-044 GEN
Solar/Wind Harmer
14.781
274823ROCKFORD ;21
Adder
14.373
276612AE2-035 GEN
Solar/Wind Harmer
1.86
971681AH1-341 GEN
Solar/Wind Harmer
10.744
274863CRW1-WTG
Solar/Wind Harmer
3.945
274864CRW2-WTG
Solar/Wind Harmer
3.945
961011AF2-392 GEN
Solar/Wind Harmer
7.608
926823AC1-168 GEN
Solar/Wind Harmer
3
970169AG2-114 GEN
Solar/Wind Harmer
6.724
957751AF2-069 GEN
Solar/Wind Harmer
0.307
946321AF1-296 GEN
Solar/Wind Harmer
6.852
274848CAMPGROVE;RU
Solar/Wind Harmer
4.229
276655WTG1_EQ
Solar/Wind Harmer
5.217
276656WTG2_EQ
Solar/Wind Harmer
0.691
959341AF2-225 GEN
Solar/Wind Harmer
8.963
941731AE2-173 GEN
Solar/Wind Harmer
3.474
274814UNIV PK N;0U
Adder
2.568
274807UNIV PK N;3U
Adder
2.563
274805UNIV PK N;1U
Adder
2.551
274811UNIV PK N;7U
Adder
2.546
276785W4-005 GEN1
Solar/Wind Harmer
1.407
276174W4-005 GEN2
Solar/Wind Harmer
1.407
276849AB2-070 GEN2
Solar/Wind Harmer
1.044
276848AB2-070 GEN3
Solar/Wind Harmer
1.044
972207SS24-0001
Solar/Wind Harmer
19.387
274773LINCOLN ;4U
Adder
5.453
274774LINCOLN ;5U
Adder
5.453
274674JOLIET 9 ;6U
Adder
13.348
274676JOLIET 29;8U
Adder
25.509
274732ELWOOD EC;7P
Adder
13.475
941551AE2-152 GEN
Solar/Wind Harmer
3.707
274745AC1-111 GEN9
Adder
4.442
274682WAUKEGAN ;7U
Adder
14.153
274828WAUKEGAN ;BP
Adder
8.677
274871GR RIDGE ;2U
Solar/Wind Harmer
6.012
960751AF2-366 GEN
Solar/Wind Harmer
2.191
962781AG1-127 GEN
Solar/Wind Harmer
7.263
274872LEEDK;1U
Solar/Wind Harmer
6.244
276901AD2-066 C O1
Solar/Wind Harmer
2.66
276861AD2-134 GEN
Solar/Wind Harmer
1.333
276691AA1-018 GEN1
Solar/Wind Harmer
0.344
957471AF2-041 GEN
Solar/Wind Harmer
22.172
959081AF2-199 GEN
Solar/Wind Harmer
7.391
971067AG2-660 GEN
Solar/Wind Harmer
1.719
971997AH1-543 GEN
Solar/Wind Harmer
11.632
939401AE1-172 GEN
Solar/Wind Harmer
10.292
274822ROCKFORD ;11
Adder
14.478
972235AH1-702 GEN1
Adder
1.85
970819AG2-516 GEN
Solar/Wind Harmer
8.756
971475AH1-234 GEN
Solar/Wind Harmer
16.282
276876AE1-163_GEN2
Solar/Wind Harmer
4.845
970569AG2-363 GEN
Solar/Wind Harmer
21.424
274857EASY ROAD;U1
Solar/Wind Harmer
3.409
274761LEE CO EC;2U
Adder
6.618
274766LEE CO EC;7U
Adder
6.54
276158O29GEN2
Solar/Wind Harmer
3.443
276164X3-005 C
Solar/Wind Harmer
0.47
274877BISHOP HL;1U
Solar/Wind Harmer
2.238
276726Z2-087_GEN
Solar/Wind Harmer
4.726
939741AE1-205 GEN
Solar/Wind Harmer
11.95
274854TWINGROVE;U2
Solar/Wind Harmer
4.016
972175AH1-670 GEN
Solar/Wind Harmer
7.023
274812UNIV PK N;8U
Adder
2.546
274880W4-005 GEN4
Solar/Wind Harmer
1.407
963831AG1-236 GEN
Solar/Wind Harmer
4.499
274798UNIV PARK;1U
50/50
0.272
274888KELLY CRK;1U
Solar/Wind Harmer
5.415
274887GEN-1.85
Solar/Wind Harmer
4.889
276843GEN-1.7
Solar/Wind Harmer
0.526
958011AF2-095 GEN
Solar/Wind Harmer
13.207
274770LINCOLN ;1U
Adder
5.453
274771LINCOLN ;2U
Adder
5.453
274674JOLIET 9 ;6U
Adder
13.348
274861TOP CROP ;1U
Solar/Wind Harmer
5.076
274862TOP CROP ;2U
Solar/Wind Harmer
4.239
274803UNIV PARK;6U
Adder
4.757
972259AH1-714 GEN
Adder
15.191
274683WAUKEGAN ;8U
Adder
16.554
274683WAUKEGAN ;8U
Adder
13.954
971573AH1-285 GEN
Solar/Wind Harmer
6.746
274695ROCKY RD ;2P
Adder
8.708
274693ROCKY RD ;1P
Adder
8.623
274697ROCKY RD ;3P
Adder
2.366
274696ROCKY RD ;4P
Adder
8.914
274847GR RIDGE ;BU
Solar/Wind Harmer
3.955
962691AG1-118 GEN
Solar/Wind Harmer
23.017
970921AG2-575 GEN
Solar/Wind Harmer
7.638
970921AG2-575 GEN
Solar/Wind Harmer
1.776
942991AE2-321 GEN
Solar/Wind Harmer
7.587
274879MINONK ;1U
Solar/Wind Harmer
5.117
971333AH1-146 GEN
Solar/Wind Harmer
14.992
971335AH1-147 GEN
Solar/Wind Harmer
14.992
958481AF2-142 GEN
Solar/Wind Harmer
11.093
971341AH1-150 GEN
Solar/Wind Harmer
14.781
971343AH1-151 GEN
Solar/Wind Harmer
14.781
958491AF2-143 GEN
Solar/Wind Harmer
10.979
274856ECOGROVE ;U1
Solar/Wind Harmer
2.451
276611AD2-172 GEN
Solar/Wind Harmer
1.86
276872AE1-163_GEN1
Solar/Wind Harmer
4.845
938861AE1-114 GEN
Solar/Wind Harmer
5.872
274764LEE CO EC;5U
Adder
6.633
274765LEE CO EC;6U
Adder
6.633
274762LEE CO EC;3U
Adder
6.618
274763LEE CO EC;4U
Adder
6.555
276603SUBLETTE C
Solar/Wind Harmer
0.742
972267AH1-718 GEN
Adder
2.9
276741O09 GEN1
Solar/Wind Harmer
2.459
276708O09 GEN2
Solar/Wind Harmer
2.459
274851PROVIDENC;RU
Solar/Wind Harmer
1.903
274849CRESCENT ;1U
Solar/Wind Harmer
1.236
276645AC1-214 GEN1
Solar/Wind Harmer
0.895
276646AC1-214 GEN2
Solar/Wind Harmer
0.895
276782AC1-033 GEN
Solar/Wind Harmer
2.645
960611AF2-352 GEN
Solar/Wind Harmer
1.323
274808UNIV PK N;4U
Adder
2.535
276763AC1-053 GEN1
Solar/Wind Harmer
1.808
276764AC1-053 GEN2
Solar/Wind Harmer
1.808
274826FISK ;BP
50/50
12.131
274799UNIV PARK;2U
50/50
0.281
274800UNIV PARK;3U
50/50
6.258
972038AH1-567 GEN2
50/50
0.392
970941AG2-585 GEN
Solar/Wind Harmer
11.464
276772AC2-154 GEN
Solar/Wind Harmer
2.557
276806AD2-047 C O1
Solar/Wind Harmer
9.81
274772LINCOLN ;3U
Adder
5.453
276893AG1-478 C
Solar/Wind Harmer
0.356
274676JOLIET 29;8U
Adder
24.598
274730ELWOOD EC;6P
Adder
13.475
274734ELWOOD EC;8P
Adder
13.475
274736ELWOOD EC;9P
Adder
13.475
274729ELWOOD EC;1P
Adder
13.457
276897AD1-100 C
Solar/Wind Harmer
23.718
939351AE1-166 GEN
Solar/Wind Harmer
4.846
274802UNIV PARK;5U
Adder
4.757
970707AG2-453 GEN
Solar/Wind Harmer
22.373
972228AH1-698 GEN2
Adder
2.951
943121AE2-341 GEN
Solar/Wind Harmer
11.869
943591AF1-030 GEN
Solar/Wind Harmer
7.913
274682WAUKEGAN ;7U
Adder
14.153
274872LEEDK;1U
Solar/Wind Harmer
0.194
276799AD1-013 GEN
Solar/Wind Harmer
1.652
946671AF1-331 GEN
Solar/Wind Harmer
0.313
274855GSG-6 ;RU
Solar/Wind Harmer
2.757
274850MENDOTA H;RU
Solar/Wind Harmer
1.917
276602WESTBROOK C
Solar/Wind Harmer
1.587
276863AD2-134 GEN
Solar/Wind Harmer
1.333
276694AA1-018 GEN2
Solar/Wind Harmer
4.667
959091AF2-200 GEN
Solar/Wind Harmer
14.781
972236AH1-702 GEN2
Adder
1.608
276805AD2-038 GEN
Solar/Wind Harmer
3.755
276889AE2-281 GEN
Solar/Wind Harmer
1.384
970571AG2-364 GEN
Solar/Wind Harmer
14.282
274858EASY ROAD;U2
Solar/Wind Harmer
3.409
274760LEE CO EC;1U
Adder
6.618
274767LEE CO EC;8U
Adder
6.54
276157O29GEN1
Solar/Wind Harmer
2.619
274878BISHOP HL;2U
Solar/Wind Harmer
2.238
965931AG1-462 GEN
Solar/Wind Harmer
16.564
942111AE2-223 GEN
Solar/Wind Harmer
4.898
274853TWINGROVE;U1
Solar/Wind Harmer
4.101
965091AG1-374 GEN
Solar/Wind Harmer
17.072
959611AF2-252 GEN
Solar/Wind Harmer
1.323
276686W4-005 GEN3
Solar/Wind Harmer
1.407
971993AH1-541 GEN
Solar/Wind Harmer
4.299
276668AB2-070 GEN1
Solar/Wind Harmer
1.044
990512J1326
External Queue
3.9820756912231445
990117J1214
External Queue
9.054607391357422
990727J1377 G
External Queue
4.618549346923828
990407J1304
External Queue
3.0755059719085693
NYPJM->LTFIMP_NY
CLTF
0.681
WECLTFEXP_WEC->PJM
CLTF
2.818
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
21.323
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.117
CBM West 1LTFEXP_CBM-W1->PJM
CBM
39.97
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.208
MECLTFEXP_MEC->PJM
CLTF
8.777
SIGELTFEXP_SIGE->PJM
CLTF
0.014
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.243
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.673
LAGNLTFEXP_LAGN->PJM
CLTF
2.965
TVALTFEXP_TVA->PJM
CLTF
0.782

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1668.91
MW Contribution:8.79
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
8.669
960591AF2-350 GEN
Solar/Wind Harmer
9.257
274775LINCOLN ;6U
Adder
5.55
274776LINCOLN ;7U
Adder
5.55
274777LINCOLN ;8U
Adder
5.55
274687WILL CNTY;4U
Adder
24.997
274687WILL CNTY;4U
Adder
24.997
274675JOLIET 29;7U
Adder
25.693
274675JOLIET 29;7U
Adder
24.776
274728ELWOOD EC;5P
Adder
13.576
274731ELWOOD EC;2P
Adder
13.558
274733ELWOOD EC;3P
Adder
13.558
274735ELWOOD EC;4P
Adder
13.558
972037AH1-567 GEN1
Adder
0.151
972227AH1-698 GEN1
Adder
2.098
274746AC1-111 G10
Adder
4.461
274744AC1-111 GEN8
Adder
4.461
970833AG2-524 GEN
Solar/Wind Harmer
6.925
970833AG2-524 GEN
Solar/Wind Harmer
3.221
276868AE1-113 GEN
Solar/Wind Harmer
7.718
276882AE2-255 GEN
Solar/Wind Harmer
2.573
971177AH1-047 GEN
Solar/Wind Harmer
4.46
971411AH1-196 GEN
Solar/Wind Harmer
11.332
971675AH1-338 GEN
Solar/Wind Harmer
13.489
971171AH1-044 GEN
Solar/Wind Harmer
14.834
274823ROCKFORD ;21
Adder
14.426
276612AE2-035 GEN
Solar/Wind Harmer
1.866
971681AH1-341 GEN
Solar/Wind Harmer
10.778
274863CRW1-WTG
Solar/Wind Harmer
3.972
274864CRW2-WTG
Solar/Wind Harmer
3.972
961011AF2-392 GEN
Solar/Wind Harmer
7.63
926823AC1-168 GEN
Solar/Wind Harmer
3.011
970169AG2-114 GEN
Solar/Wind Harmer
6.75
957751AF2-069 GEN
Solar/Wind Harmer
0.308
946321AF1-296 GEN
Solar/Wind Harmer
6.866
274848CAMPGROVE;RU
Solar/Wind Harmer
4.239
276655WTG1_EQ
Solar/Wind Harmer
5.225
276656WTG2_EQ
Solar/Wind Harmer
0.692
959341AF2-225 GEN
Solar/Wind Harmer
8.976
941731AE2-173 GEN
Solar/Wind Harmer
3.479
274814UNIV PK N;0U
Adder
2.616
274807UNIV PK N;3U
Adder
2.61
274805UNIV PK N;1U
Adder
2.599
274811UNIV PK N;7U
Adder
2.593
276785W4-005 GEN1
Solar/Wind Harmer
1.399
276174W4-005 GEN2
Solar/Wind Harmer
1.399
276849AB2-070 GEN2
Solar/Wind Harmer
1.037
276848AB2-070 GEN3
Solar/Wind Harmer
1.037
274798UNIV PARK;1U
50/50
0.275
274888KELLY CRK;1U
Solar/Wind Harmer
5.465
274887GEN-1.85
Solar/Wind Harmer
4.934
276843GEN-1.7
Solar/Wind Harmer
0.531
958011AF2-095 GEN
Solar/Wind Harmer
13.331
274770LINCOLN ;1U
Adder
5.55
274771LINCOLN ;2U
Adder
5.55
274674JOLIET 9 ;6U
Adder
13.438
274861TOP CROP ;1U
Solar/Wind Harmer
5.113
274862TOP CROP ;2U
Solar/Wind Harmer
4.27
274803UNIV PARK;6U
Adder
4.806
972259AH1-714 GEN
Adder
15.286
274683WAUKEGAN ;8U
Adder
16.64
274683WAUKEGAN ;8U
Adder
14.026
971573AH1-285 GEN
Solar/Wind Harmer
6.769
274847GR RIDGE ;BU
Solar/Wind Harmer
3.978
274696ROCKY RD ;4P
Adder
8.953
274695ROCKY RD ;2P
Adder
8.747
274693ROCKY RD ;1P
Adder
8.661
274697ROCKY RD ;3P
Adder
2.376
962691AG1-118 GEN
Solar/Wind Harmer
23.103
970921AG2-575 GEN
Solar/Wind Harmer
7.666
970921AG2-575 GEN
Solar/Wind Harmer
1.783
274879MINONK ;1U
Solar/Wind Harmer
5.146
942991AE2-321 GEN
Solar/Wind Harmer
7.618
971333AH1-146 GEN
Solar/Wind Harmer
15.05
971335AH1-147 GEN
Solar/Wind Harmer
15.05
958481AF2-142 GEN
Solar/Wind Harmer
11.184
971341AH1-150 GEN
Solar/Wind Harmer
14.834
971343AH1-151 GEN
Solar/Wind Harmer
14.834
958491AF2-143 GEN
Solar/Wind Harmer
11.058
274856ECOGROVE ;U1
Solar/Wind Harmer
2.46
276611AD2-172 GEN
Solar/Wind Harmer
1.866
276872AE1-163_GEN1
Solar/Wind Harmer
4.873
938861AE1-114 GEN
Solar/Wind Harmer
5.892
274764LEE CO EC;5U
Adder
6.654
274765LEE CO EC;6U
Adder
6.654
274762LEE CO EC;3U
Adder
6.639
274763LEE CO EC;4U
Adder
6.576
276603SUBLETTE C
Solar/Wind Harmer
0.745
972267AH1-718 GEN
Adder
2.908
276741O09 GEN1
Solar/Wind Harmer
2.466
276708O09 GEN2
Solar/Wind Harmer
2.466
274851PROVIDENC;RU
Solar/Wind Harmer
1.908
274849CRESCENT ;1U
Solar/Wind Harmer
1.239
276645AC1-214 GEN1
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
0.898
276782AC1-033 GEN
Solar/Wind Harmer
2.652
960611AF2-352 GEN
Solar/Wind Harmer
1.324
274808UNIV PK N;4U
Adder
2.582
276763AC1-053 GEN1
Solar/Wind Harmer
1.72
276764AC1-053 GEN2
Solar/Wind Harmer
1.72
274801UNIV PARK;4U
50/50
6.309
276776AD2-060 GEN
Solar/Wind Harmer
0.391
972207SS24-0001
Solar/Wind Harmer
19.734
274773LINCOLN ;4U
Adder
5.55
274774LINCOLN ;5U
Adder
5.55
274674JOLIET 9 ;6U
Adder
13.438
274676JOLIET 29;8U
Adder
25.703
941551AE2-152 GEN
Solar/Wind Harmer
3.748
274732ELWOOD EC;7P
Adder
13.576
274745AC1-111 GEN9
Adder
4.461
274682WAUKEGAN ;7U
Adder
14.227
274828WAUKEGAN ;BP
Adder
8.722
274871GR RIDGE ;2U
Solar/Wind Harmer
6.047
960751AF2-366 GEN
Solar/Wind Harmer
2.199
962781AG1-127 GEN
Solar/Wind Harmer
7.29
274872LEEDK;1U
Solar/Wind Harmer
6.266
276901AD2-066 C O1
Solar/Wind Harmer
2.675
276861AD2-134 GEN
Solar/Wind Harmer
1.338
276691AA1-018 GEN1
Solar/Wind Harmer
0.347
939401AE1-172 GEN
Solar/Wind Harmer
10.38
971997AH1-543 GEN
Solar/Wind Harmer
11.679
957471AF2-041 GEN
Solar/Wind Harmer
22.251
959081AF2-199 GEN
Solar/Wind Harmer
7.417
971067AG2-660 GEN
Solar/Wind Harmer
1.725
274822ROCKFORD ;11
Adder
14.531
972235AH1-702 GEN1
Adder
1.856
970819AG2-516 GEN
Solar/Wind Harmer
8.787
971475AH1-234 GEN
Solar/Wind Harmer
16.34
276876AE1-163_GEN2
Solar/Wind Harmer
4.873
970569AG2-363 GEN
Solar/Wind Harmer
21.526
274857EASY ROAD;U1
Solar/Wind Harmer
3.419
274761LEE CO EC;2U
Adder
6.639
274766LEE CO EC;7U
Adder
6.56
276158O29GEN2
Solar/Wind Harmer
3.452
276164X3-005 C
Solar/Wind Harmer
0.477
274877BISHOP HL;1U
Solar/Wind Harmer
2.244
276726Z2-087_GEN
Solar/Wind Harmer
4.733
939741AE1-205 GEN
Solar/Wind Harmer
11.968
274854TWINGROVE;U2
Solar/Wind Harmer
4.016
274812UNIV PK N;8U
Adder
2.593
972175AH1-670 GEN
Solar/Wind Harmer
7.002
274880W4-005 GEN4
Solar/Wind Harmer
1.399
274826FISK ;BP
50/50
12.232
274799UNIV PARK;2U
50/50
0.283
274800UNIV PARK;3U
50/50
6.309
972038AH1-567 GEN2
50/50
0.395
970941AG2-585 GEN
Solar/Wind Harmer
11.571
276772AC2-154 GEN
Solar/Wind Harmer
2.581
276806AD2-047 C O1
Solar/Wind Harmer
9.902
274772LINCOLN ;3U
Adder
5.55
276893AG1-478 C
Solar/Wind Harmer
0.358
274676JOLIET 29;8U
Adder
24.785
276897AD1-100 C
Solar/Wind Harmer
23.982
939351AE1-166 GEN
Solar/Wind Harmer
4.9
274730ELWOOD EC;6P
Adder
13.576
274734ELWOOD EC;8P
Adder
13.576
274736ELWOOD EC;9P
Adder
13.576
274729ELWOOD EC;1P
Adder
13.558
274802UNIV PARK;5U
Adder
4.806
972228AH1-698 GEN2
Adder
2.979
970707AG2-453 GEN
Solar/Wind Harmer
22.437
943121AE2-341 GEN
Solar/Wind Harmer
11.91
943591AF1-030 GEN
Solar/Wind Harmer
7.94
274682WAUKEGAN ;7U
Adder
14.227
274872LEEDK;1U
Solar/Wind Harmer
0.195
276799AD1-013 GEN
Solar/Wind Harmer
1.658
946671AF1-331 GEN
Solar/Wind Harmer
0.314
274855GSG-6 ;RU
Solar/Wind Harmer
2.766
274850MENDOTA H;RU
Solar/Wind Harmer
1.923
276602WESTBROOK C
Solar/Wind Harmer
1.592
276863AD2-134 GEN
Solar/Wind Harmer
1.338
276694AA1-018 GEN2
Solar/Wind Harmer
4.705
959091AF2-200 GEN
Solar/Wind Harmer
14.834
276805AD2-038 GEN
Solar/Wind Harmer
3.782
972236AH1-702 GEN2
Adder
1.614
276889AE2-281 GEN
Solar/Wind Harmer
1.392
970571AG2-364 GEN
Solar/Wind Harmer
14.35
274858EASY ROAD;U2
Solar/Wind Harmer
3.419
274760LEE CO EC;1U
Adder
6.639
274767LEE CO EC;8U
Adder
6.56
276157O29GEN1
Solar/Wind Harmer
2.626
274878BISHOP HL;2U
Solar/Wind Harmer
2.244
965931AG1-462 GEN
Solar/Wind Harmer
16.593
942111AE2-223 GEN
Solar/Wind Harmer
4.906
274853TWINGROVE;U1
Solar/Wind Harmer
4.102
965091AG1-374 GEN
Solar/Wind Harmer
17.075
959611AF2-252 GEN
Solar/Wind Harmer
1.324
276686W4-005 GEN3
Solar/Wind Harmer
1.399
971993AH1-541 GEN
Solar/Wind Harmer
4.272
276668AB2-070 GEN1
Solar/Wind Harmer
1.037
990512J1326
External Queue
3.9947307109832764
990117J1214
External Queue
13.741872787475586
990727J1377 G
External Queue
4.634629249572754
990407J1304
External Queue
3.086855411529541
NYPJM->LTFIMP_NY
CLTF
0.681
WECLTFEXP_WEC->PJM
CLTF
2.83
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.299
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.274
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.135
CBM West 1LTFEXP_CBM-W1->PJM
CBM
40.772
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.908
MECLTFEXP_MEC->PJM
CLTF
8.759
SIGELTFEXP_SIGE->PJM
CLTF
0.007
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.336
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.955
LAGNLTFEXP_LAGN->PJM
CLTF
2.844
TVALTFEXP_TVA->PJM
CLTF
0.712

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.81 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1668.79
MW Contribution:8.79
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
8.669
960591AF2-350 GEN
Solar/Wind Harmer
9.258
274775LINCOLN ;6U
Adder
5.551
274776LINCOLN ;7U
Adder
5.551
274777LINCOLN ;8U
Adder
5.551
274687WILL CNTY;4U
Adder
24.996
274687WILL CNTY;4U
Adder
24.996
274675JOLIET 29;7U
Adder
25.692
274675JOLIET 29;7U
Adder
24.774
274728ELWOOD EC;5P
Adder
13.575
274731ELWOOD EC;2P
Adder
13.557
274733ELWOOD EC;3P
Adder
13.557
274735ELWOOD EC;4P
Adder
13.557
972037AH1-567 GEN1
Adder
0.151
972227AH1-698 GEN1
Adder
2.098
274746AC1-111 G10
Adder
4.461
274744AC1-111 GEN8
Adder
4.461
970833AG2-524 GEN
Solar/Wind Harmer
6.924
970833AG2-524 GEN
Solar/Wind Harmer
3.221
276868AE1-113 GEN
Solar/Wind Harmer
7.718
276882AE2-255 GEN
Solar/Wind Harmer
2.573
971177AH1-047 GEN
Solar/Wind Harmer
4.459
971411AH1-196 GEN
Solar/Wind Harmer
11.33
971675AH1-338 GEN
Solar/Wind Harmer
13.486
971171AH1-044 GEN
Solar/Wind Harmer
14.831
274823ROCKFORD ;21
Adder
14.424
276612AE2-035 GEN
Solar/Wind Harmer
1.866
971681AH1-341 GEN
Solar/Wind Harmer
10.777
274863CRW1-WTG
Solar/Wind Harmer
3.973
274864CRW2-WTG
Solar/Wind Harmer
3.973
961011AF2-392 GEN
Solar/Wind Harmer
7.629
926823AC1-168 GEN
Solar/Wind Harmer
3.01
274798UNIV PARK;1U
50/50
0.275
958011AF2-095 GEN
Solar/Wind Harmer
13.332
274888KELLY CRK;1U
Solar/Wind Harmer
5.466
274887GEN-1.85
Solar/Wind Harmer
4.935
276843GEN-1.7
Solar/Wind Harmer
0.531
274770LINCOLN ;1U
Adder
5.551
274771LINCOLN ;2U
Adder
5.551
274674JOLIET 9 ;6U
Adder
13.438
274861TOP CROP ;1U
Solar/Wind Harmer
5.113
274862TOP CROP ;2U
Solar/Wind Harmer
4.27
274803UNIV PARK;6U
Adder
4.806
972259AH1-714 GEN
Adder
15.284
274683WAUKEGAN ;8U
Adder
16.637
274801UNIV PARK;4U
50/50
6.309
276776AD2-060 GEN
Solar/Wind Harmer
0.391
972207SS24-0001
Solar/Wind Harmer
19.736
274773LINCOLN ;4U
Adder
5.551
274774LINCOLN ;5U
Adder
5.551
274674JOLIET 9 ;6U
Adder
13.438
274676JOLIET 29;8U
Adder
25.701
941551AE2-152 GEN
Solar/Wind Harmer
3.749
274732ELWOOD EC;7P
Adder
13.575
274745AC1-111 GEN9
Adder
4.461
274682WAUKEGAN ;7U
Adder
14.225
274828WAUKEGAN ;BP
Adder
8.721
274871GR RIDGE ;2U
Solar/Wind Harmer
6.047
960751AF2-366 GEN
Solar/Wind Harmer
2.199
962781AG1-127 GEN
Solar/Wind Harmer
7.289
274872LEEDK;1U
Solar/Wind Harmer
6.265
276901AD2-066 C O1
Solar/Wind Harmer
2.675
276861AD2-134 GEN
Solar/Wind Harmer
1.337
276691AA1-018 GEN1
Solar/Wind Harmer
0.347
939401AE1-172 GEN
Solar/Wind Harmer
10.382
971997AH1-543 GEN
Solar/Wind Harmer
11.677
957471AF2-041 GEN
Solar/Wind Harmer
22.247
959081AF2-199 GEN
Solar/Wind Harmer
7.416
971067AG2-660 GEN
Solar/Wind Harmer
1.725
274822ROCKFORD ;11
Adder
14.529
972235AH1-702 GEN1
Adder
1.856
970819AG2-516 GEN
Solar/Wind Harmer
8.786
971475AH1-234 GEN
Solar/Wind Harmer
16.338
276876AE1-163_GEN2
Solar/Wind Harmer
4.873
970569AG2-363 GEN
Solar/Wind Harmer
21.524
274857EASY ROAD;U1
Solar/Wind Harmer
3.419
274761LEE CO EC;2U
Adder
6.638
274766LEE CO EC;7U
Adder
6.559
276158O29GEN2
Solar/Wind Harmer
3.452
276164X3-005 C
Solar/Wind Harmer
0.477
274877BISHOP HL;1U
Solar/Wind Harmer
2.244
276726Z2-087_GEN
Solar/Wind Harmer
4.733
939741AE1-205 GEN
Solar/Wind Harmer
11.969
970169AG2-114 GEN
Solar/Wind Harmer
6.75
957751AF2-069 GEN
Solar/Wind Harmer
0.308
946321AF1-296 GEN
Solar/Wind Harmer
6.865
274848CAMPGROVE;RU
Solar/Wind Harmer
4.238
276655WTG1_EQ
Solar/Wind Harmer
5.225
276656WTG2_EQ
Solar/Wind Harmer
0.692
959341AF2-225 GEN
Solar/Wind Harmer
8.977
941731AE2-173 GEN
Solar/Wind Harmer
3.479
274814UNIV PK N;0U
Adder
2.616
274807UNIV PK N;3U
Adder
2.61
274805UNIV PK N;1U
Adder
2.599
274811UNIV PK N;7U
Adder
2.593
276785W4-005 GEN1
Solar/Wind Harmer
1.399
276174W4-005 GEN2
Solar/Wind Harmer
1.399
276849AB2-070 GEN2
Solar/Wind Harmer
1.037
276848AB2-070 GEN3
Solar/Wind Harmer
1.037
274826FISK ;BP
50/50
12.232
274799UNIV PARK;2U
50/50
0.283
274800UNIV PARK;3U
50/50
6.309
972038AH1-567 GEN2
50/50
0.395
970941AG2-585 GEN
Solar/Wind Harmer
11.572
276772AC2-154 GEN
Solar/Wind Harmer
2.581
276806AD2-047 C O1
Solar/Wind Harmer
9.903
274772LINCOLN ;3U
Adder
5.551
276893AG1-478 C
Solar/Wind Harmer
0.358
274676JOLIET 29;8U
Adder
24.783
276897AD1-100 C
Solar/Wind Harmer
23.987
939351AE1-166 GEN
Solar/Wind Harmer
4.901
274730ELWOOD EC;6P
Adder
13.575
274734ELWOOD EC;8P
Adder
13.575
274736ELWOOD EC;9P
Adder
13.575
274729ELWOOD EC;1P
Adder
13.557
274802UNIV PARK;5U
Adder
4.806
972228AH1-698 GEN2
Adder
2.98
970707AG2-453 GEN
Solar/Wind Harmer
22.431
943121AE2-341 GEN
Solar/Wind Harmer
11.907
943591AF1-030 GEN
Solar/Wind Harmer
7.938
274682WAUKEGAN ;7U
Adder
14.225
274872LEEDK;1U
Solar/Wind Harmer
0.195
276799AD1-013 GEN
Solar/Wind Harmer
1.658
946671AF1-331 GEN
Solar/Wind Harmer
0.314
274855GSG-6 ;RU
Solar/Wind Harmer
2.766
274850MENDOTA H;RU
Solar/Wind Harmer
1.923
276602WESTBROOK C
Solar/Wind Harmer
1.592
276863AD2-134 GEN
Solar/Wind Harmer
1.337
276694AA1-018 GEN2
Solar/Wind Harmer
4.705
959091AF2-200 GEN
Solar/Wind Harmer
14.831
276805AD2-038 GEN
Solar/Wind Harmer
3.782
972236AH1-702 GEN2
Adder
1.614
276889AE2-281 GEN
Solar/Wind Harmer
1.392
970571AG2-364 GEN
Solar/Wind Harmer
14.349
274854TWINGROVE;U2
Solar/Wind Harmer
4.017
274812UNIV PK N;8U
Adder
2.593
972175AH1-670 GEN
Solar/Wind Harmer
7.003
274880W4-005 GEN4
Solar/Wind Harmer
1.399
274683WAUKEGAN ;8U
Adder
14.025
971573AH1-285 GEN
Solar/Wind Harmer
6.768
274847GR RIDGE ;BU
Solar/Wind Harmer
3.977
274695ROCKY RD ;2P
Adder
8.746
274693ROCKY RD ;1P
Adder
8.66
274697ROCKY RD ;3P
Adder
2.376
274696ROCKY RD ;4P
Adder
8.952
962691AG1-118 GEN
Solar/Wind Harmer
23.099
970921AG2-575 GEN
Solar/Wind Harmer
7.664
970921AG2-575 GEN
Solar/Wind Harmer
1.782
274879MINONK ;1U
Solar/Wind Harmer
5.146
942991AE2-321 GEN
Solar/Wind Harmer
7.617
971333AH1-146 GEN
Solar/Wind Harmer
15.048
971335AH1-147 GEN
Solar/Wind Harmer
15.048
958481AF2-142 GEN
Solar/Wind Harmer
11.184
971341AH1-150 GEN
Solar/Wind Harmer
14.831
971343AH1-151 GEN
Solar/Wind Harmer
14.831
958491AF2-143 GEN
Solar/Wind Harmer
11.058
274856ECOGROVE ;U1
Solar/Wind Harmer
2.459
276611AD2-172 GEN
Solar/Wind Harmer
1.866
276872AE1-163_GEN1
Solar/Wind Harmer
4.873
938861AE1-114 GEN
Solar/Wind Harmer
5.891
274764LEE CO EC;5U
Adder
6.653
274765LEE CO EC;6U
Adder
6.653
274762LEE CO EC;3U
Adder
6.638
274763LEE CO EC;4U
Adder
6.575
276603SUBLETTE C
Solar/Wind Harmer
0.744
972267AH1-718 GEN
Adder
2.908
276741O09 GEN1
Solar/Wind Harmer
2.466
276708O09 GEN2
Solar/Wind Harmer
2.466
274851PROVIDENC;RU
Solar/Wind Harmer
1.908
274849CRESCENT ;1U
Solar/Wind Harmer
1.239
276645AC1-214 GEN1
Solar/Wind Harmer
0.897
276646AC1-214 GEN2
Solar/Wind Harmer
0.897
276782AC1-033 GEN
Solar/Wind Harmer
2.651
960611AF2-352 GEN
Solar/Wind Harmer
1.324
274808UNIV PK N;4U
Adder
2.582
276763AC1-053 GEN1
Solar/Wind Harmer
1.72
276764AC1-053 GEN2
Solar/Wind Harmer
1.72
274858EASY ROAD;U2
Solar/Wind Harmer
3.419
274760LEE CO EC;1U
Adder
6.638
274767LEE CO EC;8U
Adder
6.559
276157O29GEN1
Solar/Wind Harmer
2.626
274878BISHOP HL;2U
Solar/Wind Harmer
2.244
965931AG1-462 GEN
Solar/Wind Harmer
16.591
942111AE2-223 GEN
Solar/Wind Harmer
4.906
274853TWINGROVE;U1
Solar/Wind Harmer
4.103
965091AG1-374 GEN
Solar/Wind Harmer
17.076
959611AF2-252 GEN
Solar/Wind Harmer
1.324
276686W4-005 GEN3
Solar/Wind Harmer
1.399
971993AH1-541 GEN
Solar/Wind Harmer
4.273
276668AB2-070 GEN1
Solar/Wind Harmer
1.037
990512J1326
External Queue
3.99412202835083
990117J1214
External Queue
13.739779472351074
990727J1377 G
External Queue
4.633896827697754
990407J1304
External Queue
3.086374282836914
NYPJM->LTFIMP_NY
CLTF
0.681
WECLTFEXP_WEC->PJM
CLTF
2.83
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.274
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.298
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.135
CBM West 1LTFEXP_CBM-W1->PJM
CBM
40.766
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.908
MECLTFEXP_MEC->PJM
CLTF
8.758
SIGELTFEXP_SIGE->PJM
CLTF
0.007
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.335
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.955
LAGNLTFEXP_LAGN->PJM
CLTF
2.844
TVALTFEXP_TVA->PJM
CLTF
0.712

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o AEP_P4_#1750_05DUMONT 765_B1_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1750_05DUMONT 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.34 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1662.03
MW Contribution:8.74
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
8.604
274687WILL CNTY;4U
50/50
26.329
274687WILL CNTY;4U
50/50
26.329
960591AF2-350 GEN
Solar/Wind Harmer
9.177
274775LINCOLN ;6U
Adder
5.454
274776LINCOLN ;7U
Adder
5.454
274777LINCOLN ;8U
Adder
5.454
274675JOLIET 29;7U
Adder
25.506
274675JOLIET 29;7U
Adder
24.595
274728ELWOOD EC;5P
Adder
13.475
274731ELWOOD EC;2P
Adder
13.457
274733ELWOOD EC;3P
Adder
13.457
274735ELWOOD EC;4P
Adder
13.457
972037AH1-567 GEN1
Adder
0.149
972227AH1-698 GEN1
Adder
2.079
274746AC1-111 G10
Adder
4.44
274744AC1-111 GEN8
Adder
4.44
970833AG2-524 GEN
Solar/Wind Harmer
6.882
970833AG2-524 GEN
Solar/Wind Harmer
3.201
276868AE1-113 GEN
Solar/Wind Harmer
7.663
276882AE2-255 GEN
Solar/Wind Harmer
2.555
971177AH1-047 GEN
Solar/Wind Harmer
4.436
274801UNIV PARK;4U
50/50
6.262
276776AD2-060 GEN
Solar/Wind Harmer
0.388
972207SS24-0001
Solar/Wind Harmer
19.391
274773LINCOLN ;4U
Adder
5.454
274774LINCOLN ;5U
Adder
5.454
274674JOLIET 9 ;6U
Adder
13.349
274676JOLIET 29;8U
Adder
25.515
274732ELWOOD EC;7P
Adder
13.475
941551AE2-152 GEN
Solar/Wind Harmer
3.706
274745AC1-111 GEN9
Adder
4.44
274682WAUKEGAN ;7U
Adder
14.144
274828WAUKEGAN ;BP
Adder
8.671
274871GR RIDGE ;2U
Solar/Wind Harmer
6.01
960751AF2-366 GEN
Solar/Wind Harmer
2.189
962781AG1-127 GEN
Solar/Wind Harmer
7.255
274872LEEDK;1U
Solar/Wind Harmer
6.236
276901AD2-066 C O1
Solar/Wind Harmer
2.656
276861AD2-134 GEN
Solar/Wind Harmer
1.331
276691AA1-018 GEN1
Solar/Wind Harmer
0.344
957471AF2-041 GEN
Solar/Wind Harmer
22.135
959081AF2-199 GEN
Solar/Wind Harmer
7.378
971067AG2-660 GEN
Solar/Wind Harmer
1.716
971997AH1-543 GEN
Solar/Wind Harmer
11.609
939401AE1-172 GEN
Solar/Wind Harmer
10.267
274822ROCKFORD ;11
Adder
14.453
972235AH1-702 GEN1
Adder
1.846
970819AG2-516 GEN
Solar/Wind Harmer
8.739
971475AH1-234 GEN
Solar/Wind Harmer
16.25
276876AE1-163_GEN2
Solar/Wind Harmer
4.836
970569AG2-363 GEN
Solar/Wind Harmer
21.368
274857EASY ROAD;U1
Solar/Wind Harmer
3.401
274761LEE CO EC;2U
Adder
6.602
274766LEE CO EC;7U
Adder
6.524
276158O29GEN2
Solar/Wind Harmer
3.432
276164X3-005 C
Solar/Wind Harmer
0.471
274877BISHOP HL;1U
Solar/Wind Harmer
2.229
276726Z2-087_GEN
Solar/Wind Harmer
4.69
939741AE1-205 GEN
Solar/Wind Harmer
11.86
274854TWINGROVE;U2
Solar/Wind Harmer
3.98
274812UNIV PK N;8U
Adder
2.553
972175AH1-670 GEN
Solar/Wind Harmer
6.94
274880W4-005 GEN4
Solar/Wind Harmer
1.386
274798UNIV PARK;1U
50/50
0.273
274888KELLY CRK;1U
Solar/Wind Harmer
5.418
274887GEN-1.85
Solar/Wind Harmer
4.891
276843GEN-1.7
Solar/Wind Harmer
0.526
958011AF2-095 GEN
Solar/Wind Harmer
13.215
274770LINCOLN ;1U
Adder
5.454
274771LINCOLN ;2U
Adder
5.454
274674JOLIET 9 ;6U
Adder
13.349
274861TOP CROP ;1U
Solar/Wind Harmer
5.073
274862TOP CROP ;2U
Solar/Wind Harmer
4.236
274803UNIV PARK;6U
Adder
4.762
972259AH1-714 GEN
Adder
15.192
274683WAUKEGAN ;8U
Adder
16.543
274683WAUKEGAN ;8U
Adder
13.945
971573AH1-285 GEN
Solar/Wind Harmer
6.741
274695ROCKY RD ;2P
Adder
8.702
971411AH1-196 GEN
Solar/Wind Harmer
11.27
971675AH1-338 GEN
Solar/Wind Harmer
13.422
971171AH1-044 GEN
Solar/Wind Harmer
14.756
274823ROCKFORD ;21
Adder
14.348
276612AE2-035 GEN
Solar/Wind Harmer
1.856
971681AH1-341 GEN
Solar/Wind Harmer
10.719
274863CRW1-WTG
Solar/Wind Harmer
3.931
274864CRW2-WTG
Solar/Wind Harmer
3.931
961011AF2-392 GEN
Solar/Wind Harmer
7.587
926823AC1-168 GEN
Solar/Wind Harmer
2.991
970169AG2-114 GEN
Solar/Wind Harmer
6.694
957751AF2-069 GEN
Solar/Wind Harmer
0.306
946321AF1-296 GEN
Solar/Wind Harmer
6.826
274848CAMPGROVE;RU
Solar/Wind Harmer
4.211
276655WTG1_EQ
Solar/Wind Harmer
5.177
276656WTG2_EQ
Solar/Wind Harmer
0.686
959341AF2-225 GEN
Solar/Wind Harmer
8.895
941731AE2-173 GEN
Solar/Wind Harmer
3.448
274814UNIV PK N;0U
Adder
2.575
274807UNIV PK N;3U
Adder
2.57
274805UNIV PK N;1U
Adder
2.559
274811UNIV PK N;7U
Adder
2.553
276785W4-005 GEN1
Solar/Wind Harmer
1.386
274693ROCKY RD ;1P
Adder
8.616
274697ROCKY RD ;3P
Adder
2.364
274847GR RIDGE ;BU
Solar/Wind Harmer
3.953
274696ROCKY RD ;4P
Adder
8.907
962691AG1-118 GEN
Solar/Wind Harmer
22.993
970921AG2-575 GEN
Solar/Wind Harmer
7.629
970921AG2-575 GEN
Solar/Wind Harmer
1.774
942991AE2-321 GEN
Solar/Wind Harmer
7.577
274879MINONK ;1U
Solar/Wind Harmer
5.109
971333AH1-146 GEN
Solar/Wind Harmer
14.971
971335AH1-147 GEN
Solar/Wind Harmer
14.971
958481AF2-142 GEN
Solar/Wind Harmer
11.086
971341AH1-150 GEN
Solar/Wind Harmer
14.756
971343AH1-151 GEN
Solar/Wind Harmer
14.756
958491AF2-143 GEN
Solar/Wind Harmer
10.966
274856ECOGROVE ;U1
Solar/Wind Harmer
2.446
276611AD2-172 GEN
Solar/Wind Harmer
1.856
276872AE1-163_GEN1
Solar/Wind Harmer
4.836
938861AE1-114 GEN
Solar/Wind Harmer
5.859
274764LEE CO EC;5U
Adder
6.618
274765LEE CO EC;6U
Adder
6.618
274762LEE CO EC;3U
Adder
6.602
274763LEE CO EC;4U
Adder
6.54
276603SUBLETTE C
Solar/Wind Harmer
0.74
972267AH1-718 GEN
Adder
2.892
276741O09 GEN1
Solar/Wind Harmer
2.452
276708O09 GEN2
Solar/Wind Harmer
2.452
274851PROVIDENC;RU
Solar/Wind Harmer
1.896
274849CRESCENT ;1U
Solar/Wind Harmer
1.231
276645AC1-214 GEN1
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
0.892
276782AC1-033 GEN
Solar/Wind Harmer
2.634
960611AF2-352 GEN
Solar/Wind Harmer
1.312
274808UNIV PK N;4U
Adder
2.542
274826FISK ;BP
50/50
12.14
276174W4-005 GEN2
Solar/Wind Harmer
1.386
276849AB2-070 GEN2
Solar/Wind Harmer
1.028
276848AB2-070 GEN3
Solar/Wind Harmer
1.028
274799UNIV PARK;2U
50/50
0.281
274800UNIV PARK;3U
50/50
6.262
972038AH1-567 GEN2
50/50
0.392
970941AG2-585 GEN
Solar/Wind Harmer
11.471
276772AC2-154 GEN
Solar/Wind Harmer
2.559
276806AD2-047 C O1
Solar/Wind Harmer
9.816
274772LINCOLN ;3U
Adder
5.454
276893AG1-478 C
Solar/Wind Harmer
0.356
274676JOLIET 29;8U
Adder
24.604
274730ELWOOD EC;6P
Adder
13.475
274734ELWOOD EC;8P
Adder
13.475
274736ELWOOD EC;9P
Adder
13.475
274729ELWOOD EC;1P
Adder
13.457
276897AD1-100 C
Solar/Wind Harmer
23.712
939351AE1-166 GEN
Solar/Wind Harmer
4.845
274802UNIV PARK;5U
Adder
4.762
970707AG2-453 GEN
Solar/Wind Harmer
22.37
972228AH1-698 GEN2
Adder
2.952
943121AE2-341 GEN
Solar/Wind Harmer
11.863
943591AF1-030 GEN
Solar/Wind Harmer
7.908
274682WAUKEGAN ;7U
Adder
14.144
274872LEEDK;1U
Solar/Wind Harmer
0.194
276799AD1-013 GEN
Solar/Wind Harmer
1.65
946671AF1-331 GEN
Solar/Wind Harmer
0.312
274855GSG-6 ;RU
Solar/Wind Harmer
2.752
274850MENDOTA H;RU
Solar/Wind Harmer
1.914
276602WESTBROOK C
Solar/Wind Harmer
1.584
276863AD2-134 GEN
Solar/Wind Harmer
1.331
276694AA1-018 GEN2
Solar/Wind Harmer
4.664
959091AF2-200 GEN
Solar/Wind Harmer
14.756
972236AH1-702 GEN2
Adder
1.606
276805AD2-038 GEN
Solar/Wind Harmer
3.75
276889AE2-281 GEN
Solar/Wind Harmer
1.382
970571AG2-364 GEN
Solar/Wind Harmer
14.246
274858EASY ROAD;U2
Solar/Wind Harmer
3.401
274760LEE CO EC;1U
Adder
6.602
274767LEE CO EC;8U
Adder
6.524
276157O29GEN1
Solar/Wind Harmer
2.611
274878BISHOP HL;2U
Solar/Wind Harmer
2.229
965931AG1-462 GEN
Solar/Wind Harmer
16.497
942111AE2-223 GEN
Solar/Wind Harmer
4.861
274853TWINGROVE;U1
Solar/Wind Harmer
4.065
965091AG1-374 GEN
Solar/Wind Harmer
16.921
959611AF2-252 GEN
Solar/Wind Harmer
1.312
276686W4-005 GEN3
Solar/Wind Harmer
1.386
971993AH1-541 GEN
Solar/Wind Harmer
4.235
276668AB2-070 GEN1
Solar/Wind Harmer
1.028
990512J1326
External Queue
3.9851877689361572
990117J1214
External Queue
13.70904541015625
990727J1377 G
External Queue
4.623714447021484
991777J1629 G
External Queue
3.4314427375793457
990407J1304
External Queue
3.0793449878692627
NYPJM->LTFIMP_NY
CLTF
0.675
WECLTFEXP_WEC->PJM
CLTF
2.814
CBM West 2LTFEXP_CBM-W2->PJM
CBM
20.16
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.269
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.133
CBM West 1LTFEXP_CBM-W1->PJM
CBM
40.256
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.904
MECLTFEXP_MEC->PJM
CLTF
8.705
SIGELTFEXP_SIGE->PJM
CLTF
0.007
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.331
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.941
LAGNLTFEXP_LAGN->PJM
CLTF
2.829
TVALTFEXP_TVA->PJM
CLTF
0.71

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.28 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1661.12
MW Contribution:8.36
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
8.615
274687WILL CNTY;4U
50/50
26.703
274687WILL CNTY;4U
50/50
26.703
972037AH1-567 GEN1
50/50
0.174
960591AF2-350 GEN
Solar/Wind Harmer
9.068
274675JOLIET 29;7U
Adder
25.79
274675JOLIET 29;7U
Adder
24.869
274728ELWOOD EC;5P
Adder
13.616
274731ELWOOD EC;2P
Adder
13.592
274733ELWOOD EC;3P
Adder
13.592
274735ELWOOD EC;4P
Adder
13.592
972227AH1-698 GEN1
Adder
2.132
274814UNIV PK N;0U
Adder
3.997
274807UNIV PK N;3U
Adder
3.988
274805UNIV PK N;1U
Adder
3.971
274811UNIV PK N;7U
Adder
3.962
970833AG2-524 GEN
Solar/Wind Harmer
6.63
274801UNIV PARK;4U
50/50
6.185
276776AD2-060 GEN
Solar/Wind Harmer
0.383
274751CRETE EC ;1U
Adder
4.387
274754CRETE EC ;4U
Adder
4.387
274674JOLIET 9 ;6U
Adder
13.085
274676JOLIET 29;8U
Adder
25.801
274732ELWOOD EC;7P
Adder
13.616
274812UNIV PK N;8U
Adder
3.962
941551AE2-152 GEN
Solar/Wind Harmer
3.544
274682WAUKEGAN ;7U
Adder
13.732
274828WAUKEGAN ;BP
Adder
8.417
276691AA1-018 GEN1
Solar/Wind Harmer
0.353
274871GR RIDGE ;2U
Solar/Wind Harmer
5.785
274745AC1-111 GEN9
Adder
4.187
276901AD2-066 C O1
Solar/Wind Harmer
2.616
972207SS24-0001
Solar/Wind Harmer
15.98
274773LINCOLN ;4U
Adder
4.494
274774LINCOLN ;5U
Adder
4.494
276876AE1-163_GEN2
Solar/Wind Harmer
4.856
960751AF2-366 GEN
Solar/Wind Harmer
2.064
962781AG1-127 GEN
Solar/Wind Harmer
6.84
274872LEEDK;1U
Solar/Wind Harmer
5.879
970569AG2-363 GEN
Solar/Wind Harmer
21.28
971997AH1-543 GEN
Solar/Wind Harmer
11.145
276861AD2-134 GEN
Solar/Wind Harmer
1.259
274822ROCKFORD ;11
Adder
13.82
957471AF2-041 GEN
Solar/Wind Harmer
21.053
959081AF2-199 GEN
Solar/Wind Harmer
7.018
971067AG2-660 GEN
Solar/Wind Harmer
1.632
972235AH1-702 GEN1
Adder
1.765
970819AG2-516 GEN
Solar/Wind Harmer
8.36
971475AH1-234 GEN
Solar/Wind Harmer
15.56
939401AE1-172 GEN
Solar/Wind Harmer
9.576
274857EASY ROAD;U1
Solar/Wind Harmer
3.25
274761LEE CO EC;2U
Adder
6.31
274766LEE CO EC;7U
Adder
6.235
276158O29GEN2
Solar/Wind Harmer
3.29
274877BISHOP HL;1U
Solar/Wind Harmer
2.156
276164X3-005 C
Solar/Wind Harmer
0.427
276726Z2-087_GEN
Solar/Wind Harmer
4.383
939741AE1-205 GEN
Solar/Wind Harmer
11.083
274854TWINGROVE;U2
Solar/Wind Harmer
3.719
972175AH1-670 GEN
Solar/Wind Harmer
6.479
274826FISK ;BP
50/50
12.156
274799UNIV PARK;2U
50/50
0.278
274800UNIV PARK;3U
50/50
6.185
972038AH1-567 GEN2
50/50
0.387
274802UNIV PARK;5U
50/50
5.55
276772AC2-154 GEN
Solar/Wind Harmer
2.529
276806AD2-047 C O1
Solar/Wind Harmer
9.701
970941AG2-585 GEN
Solar/Wind Harmer
11.336
972231SS25-0005
Solar/Wind Harmer
8.519
972181SS23-001
Solar/Wind Harmer
5.324
274752CRETE EC ;2U
Adder
4.387
274753CRETE EC ;3U
Adder
4.387
276893AG1-478 C
Solar/Wind Harmer
0.354
274676JOLIET 29;8U
Adder
24.88
274730ELWOOD EC;6P
Adder
13.616
274734ELWOOD EC;8P
Adder
13.616
274736ELWOOD EC;9P
Adder
13.616
274729ELWOOD EC;1P
Adder
13.592
972228AH1-698 GEN2
Adder
3.028
276897AD1-100 C
Solar/Wind Harmer
22.677
939351AE1-166 GEN
Solar/Wind Harmer
4.634
274682WAUKEGAN ;7U
Adder
13.732
276694AA1-018 GEN2
Solar/Wind Harmer
4.779
276805AD2-038 GEN
Solar/Wind Harmer
3.811
943121AE2-341 GEN
Solar/Wind Harmer
10.957
943591AF1-030 GEN
Solar/Wind Harmer
7.305
274772LINCOLN ;3U
Adder
4.494
276889AE2-281 GEN
Solar/Wind Harmer
1.388
970707AG2-453 GEN
Solar/Wind Harmer
20.04
274872LEEDK;1U
Solar/Wind Harmer
0.183
970571AG2-364 GEN
Solar/Wind Harmer
14.186
276799AD1-013 GEN
Solar/Wind Harmer
1.56
946671AF1-331 GEN
Solar/Wind Harmer
0.295
274855GSG-6 ;RU
Solar/Wind Harmer
2.603
274850MENDOTA H;RU
Solar/Wind Harmer
1.81
276602WESTBROOK C
Solar/Wind Harmer
1.498
276863AD2-134 GEN
Solar/Wind Harmer
1.259
959091AF2-200 GEN
Solar/Wind Harmer
14.035
972236AH1-702 GEN2
Adder
1.534
274858EASY ROAD;U2
Solar/Wind Harmer
3.25
274760LEE CO EC;1U
Adder
6.31
274767LEE CO EC;8U
Adder
6.235
276157O29GEN1
Solar/Wind Harmer
2.503
274878BISHOP HL;2U
Solar/Wind Harmer
2.156
965931AG1-462 GEN
Solar/Wind Harmer
15.811
942111AE2-223 GEN
Solar/Wind Harmer
4.543
274853TWINGROVE;U1
Solar/Wind Harmer
3.798
965091AG1-374 GEN
Solar/Wind Harmer
15.81
959611AF2-252 GEN
Solar/Wind Harmer
1.226
274798UNIV PARK;1U
50/50
0.269
274803UNIV PARK;6U
50/50
5.55
958011AF2-095 GEN
Solar/Wind Harmer
13.059
274888KELLY CRK;1U
Solar/Wind Harmer
5.354
274887GEN-1.85
Solar/Wind Harmer
4.834
276843GEN-1.7
Solar/Wind Harmer
0.52
274861TOP CROP ;1U
Solar/Wind Harmer
5.258
274862TOP CROP ;2U
Solar/Wind Harmer
4.39
274674JOLIET 9 ;6U
Adder
13.085
274808UNIV PK N;4U
Adder
3.945
972259AH1-714 GEN
Adder
14.598
274683WAUKEGAN ;8U
Adder
16.058
274683WAUKEGAN ;8U
Adder
13.536
958481AF2-142 GEN
Solar/Wind Harmer
11.36
274879MINONK ;1U
Solar/Wind Harmer
5.094
274847GR RIDGE ;BU
Solar/Wind Harmer
3.805
274696ROCKY RD ;4P
Adder
8.496
274695ROCKY RD ;2P
Adder
8.3
274693ROCKY RD ;1P
Adder
8.218
274697ROCKY RD ;3P
Adder
2.255
958491AF2-143 GEN
Solar/Wind Harmer
11.144
971573AH1-285 GEN
Solar/Wind Harmer
6.258
942991AE2-321 GEN
Solar/Wind Harmer
7.251
274770LINCOLN ;1U
Adder
4.494
274771LINCOLN ;2U
Adder
4.494
276872AE1-163_GEN1
Solar/Wind Harmer
4.856
962691AG1-118 GEN
Solar/Wind Harmer
21.67
970921AG2-575 GEN
Solar/Wind Harmer
7.193
970921AG2-575 GEN
Solar/Wind Harmer
1.673
971333AH1-146 GEN
Solar/Wind Harmer
14.277
971335AH1-147 GEN
Solar/Wind Harmer
14.277
971341AH1-150 GEN
Solar/Wind Harmer
14.035
971343AH1-151 GEN
Solar/Wind Harmer
14.035
274856ECOGROVE ;U1
Solar/Wind Harmer
2.339
276611AD2-172 GEN
Solar/Wind Harmer
1.775
938861AE1-114 GEN
Solar/Wind Harmer
5.599
274764LEE CO EC;5U
Adder
6.324
274765LEE CO EC;6U
Adder
6.324
274762LEE CO EC;3U
Adder
6.31
274763LEE CO EC;4U
Adder
6.25
276603SUBLETTE C
Solar/Wind Harmer
0.707
972267AH1-718 GEN
Adder
2.764
276741O09 GEN1
Solar/Wind Harmer
2.35
276708O09 GEN2
Solar/Wind Harmer
2.35
274851PROVIDENC;RU
Solar/Wind Harmer
1.835
274849CRESCENT ;1U
Solar/Wind Harmer
1.191
276645AC1-214 GEN1
Solar/Wind Harmer
0.863
276646AC1-214 GEN2
Solar/Wind Harmer
0.863
276782AC1-033 GEN
Solar/Wind Harmer
2.548
960611AF2-352 GEN
Solar/Wind Harmer
1.226
24441505OLIV SLR
Solar/Wind Helper
0.054
270526AF1-158 GEN
Solar/Wind Helper
0.904
970833AG2-524 GEN
Solar/Wind Harmer
3.084
276868AE1-113 GEN
Solar/Wind Harmer
7.641
276882AE2-255 GEN
Solar/Wind Harmer
2.547
274746AC1-111 G10
Adder
4.187
274744AC1-111 GEN8
Adder
4.187
274775LINCOLN ;6U
Adder
4.494
274776LINCOLN ;7U
Adder
4.494
274777LINCOLN ;8U
Adder
4.494
971177AH1-047 GEN
Solar/Wind Harmer
4.243
971411AH1-196 GEN
Solar/Wind Harmer
10.788
971675AH1-338 GEN
Solar/Wind Harmer
12.691
274823ROCKFORD ;21
Adder
13.719
971171AH1-044 GEN
Solar/Wind Harmer
14.035
276612AE2-035 GEN
Solar/Wind Harmer
1.775
971681AH1-341 GEN
Solar/Wind Harmer
10.236
926823AC1-168 GEN
Solar/Wind Harmer
2.895
961011AF2-392 GEN
Solar/Wind Harmer
7.25
274863CRW1-WTG
Solar/Wind Harmer
3.67
274864CRW2-WTG
Solar/Wind Harmer
3.67
957751AF2-069 GEN
Solar/Wind Harmer
0.296
274848CAMPGROVE;RU
Solar/Wind Harmer
4.075
946321AF1-296 GEN
Solar/Wind Harmer
6.541
970169AG2-114 GEN
Solar/Wind Harmer
6.27
276655WTG1_EQ
Solar/Wind Harmer
4.838
276656WTG2_EQ
Solar/Wind Harmer
0.641
959341AF2-225 GEN
Solar/Wind Harmer
8.312
941731AE2-173 GEN
Solar/Wind Harmer
3.222
990512J1326
External Queue
3.9395570755004883
990117J1214
External Queue
13.552075386047363
990727J1377 G
External Queue
4.557984352111816
991777J1629 G
External Queue
9.00204086303711
990407J1304
External Queue
3.040069103240967
NYPJM->LTFIMP_NY
CLTF
0.643
WECLTFEXP_WEC->PJM
CLTF
2.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.563
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.493
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.705
MECLTFEXP_MEC->PJM
CLTF
8.342
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.339
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.976
LAGNLTFEXP_LAGN->PJM
CLTF
2.654
TVALTFEXP_TVA->PJM
CLTF
0.65

Details for BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ; B-17SHEFFIELD 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.22 %
Rating:1441.0 MVA
Rating Type:B
MVA to Mitigate:1631.55
MW Contribution:8.36
Bus #Bus NameTypeMW Contribution
274826FISK ;BP
50/50
12.156
274799UNIV PARK;2U
50/50
0.278
274800UNIV PARK;3U
50/50
6.185
972038AH1-567 GEN2
50/50
0.387
274802UNIV PARK;5U
50/50
5.55
276772AC2-154 GEN
Solar/Wind Harmer
2.529
276806AD2-047 C O1
Solar/Wind Harmer
9.701
970941AG2-585 GEN
Solar/Wind Harmer
11.336
276893AG1-478 C
Solar/Wind Harmer
0.354
274676JOLIET 29;8U
Adder
24.88
274730ELWOOD EC;6P
Adder
13.616
274734ELWOOD EC;8P
Adder
13.616
274736ELWOOD EC;9P
Adder
13.616
274729ELWOOD EC;1P
Adder
13.592
972228AH1-698 GEN2
Adder
3.028
276897AD1-100 C
Solar/Wind Harmer
22.677
939351AE1-166 GEN
Solar/Wind Harmer
4.634
274682WAUKEGAN ;7U
Adder
13.732
276694AA1-018 GEN2
Solar/Wind Harmer
4.779
276805AD2-038 GEN
Solar/Wind Harmer
3.811
943121AE2-341 GEN
Solar/Wind Harmer
10.957
943591AF1-030 GEN
Solar/Wind Harmer
7.305
274772LINCOLN ;3U
Adder
4.494
276889AE2-281 GEN
Solar/Wind Harmer
1.388
970707AG2-453 GEN
Solar/Wind Harmer
20.04
274872LEEDK;1U
Solar/Wind Harmer
0.183
970571AG2-364 GEN
Solar/Wind Harmer
14.186
276799AD1-013 GEN
Solar/Wind Harmer
1.56
946671AF1-331 GEN
Solar/Wind Harmer
0.295
274855GSG-6 ;RU
Solar/Wind Harmer
2.603
274850MENDOTA H;RU
Solar/Wind Harmer
1.81
274798UNIV PARK;1U
50/50
0.269
274803UNIV PARK;6U
50/50
5.55
959351AF2-226 GEN
50/50
2.018
958011AF2-095 GEN
Solar/Wind Harmer
13.059
274888KELLY CRK;1U
Solar/Wind Harmer
5.354
274887GEN-1.85
Solar/Wind Harmer
4.834
276843GEN-1.7
Solar/Wind Harmer
0.52
274861TOP CROP ;1U
Solar/Wind Harmer
5.258
274862TOP CROP ;2U
Solar/Wind Harmer
4.39
274674JOLIET 9 ;6U
Adder
13.085
274808UNIV PK N;4U
Adder
3.945
972259AH1-714 GEN
Adder
14.598
274683WAUKEGAN ;8U
Adder
16.058
274683WAUKEGAN ;8U
Adder
13.536
958481AF2-142 GEN
Solar/Wind Harmer
11.36
274879MINONK ;1U
Solar/Wind Harmer
5.094
274847GR RIDGE ;BU
Solar/Wind Harmer
3.805
274696ROCKY RD ;4P
Adder
8.496
274695ROCKY RD ;2P
Adder
8.3
274693ROCKY RD ;1P
Adder
8.218
274697ROCKY RD ;3P
Adder
2.255
958491AF2-143 GEN
Solar/Wind Harmer
11.144
971573AH1-285 GEN
Solar/Wind Harmer
6.258
942991AE2-321 GEN
Solar/Wind Harmer
7.251
274770LINCOLN ;1U
Adder
4.494
274771LINCOLN ;2U
Adder
4.494
276872AE1-163_GEN1
Solar/Wind Harmer
4.856
962691AG1-118 GEN
Solar/Wind Harmer
21.67
970921AG2-575 GEN
Solar/Wind Harmer
7.193
970921AG2-575 GEN
Solar/Wind Harmer
1.673
971333AH1-146 GEN
Solar/Wind Harmer
14.277
971335AH1-147 GEN
Solar/Wind Harmer
14.277
971341AH1-150 GEN
Solar/Wind Harmer
14.035
971343AH1-151 GEN
Solar/Wind Harmer
14.035
274856ECOGROVE ;U1
Solar/Wind Harmer
2.339
276611AD2-172 GEN
Solar/Wind Harmer
1.775
276602WESTBROOK C
Solar/Wind Harmer
1.498
276863AD2-134 GEN
Solar/Wind Harmer
1.259
959091AF2-200 GEN
Solar/Wind Harmer
14.035
972236AH1-702 GEN2
Adder
1.534
274858EASY ROAD;U2
Solar/Wind Harmer
3.25
274760LEE CO EC;1U
Adder
6.31
274767LEE CO EC;8U
Adder
6.235
276157O29GEN1
Solar/Wind Harmer
2.503
274878BISHOP HL;2U
Solar/Wind Harmer
2.156
965931AG1-462 GEN
Solar/Wind Harmer
15.811
942111AE2-223 GEN
Solar/Wind Harmer
4.543
938861AE1-114 GEN
Solar/Wind Harmer
5.599
274764LEE CO EC;5U
Adder
6.324
274765LEE CO EC;6U
Adder
6.324
274762LEE CO EC;3U
Adder
6.31
274763LEE CO EC;4U
Adder
6.25
276603SUBLETTE C
Solar/Wind Harmer
0.707
972267AH1-718 GEN
Adder
2.764
276741O09 GEN1
Solar/Wind Harmer
2.35
276708O09 GEN2
Solar/Wind Harmer
2.35
274851PROVIDENC;RU
Solar/Wind Harmer
1.835
274849CRESCENT ;1U
Solar/Wind Harmer
1.191
276645AC1-214 GEN1
Solar/Wind Harmer
0.863
276646AC1-214 GEN2
Solar/Wind Harmer
0.863
276782AC1-033 GEN
Solar/Wind Harmer
2.548
960611AF2-352 GEN
Solar/Wind Harmer
1.226
24441505OLIV SLR
Solar/Wind Helper
0.054
270526AF1-158 GEN
Solar/Wind Helper
0.904
274853TWINGROVE;U1
Solar/Wind Harmer
3.798
965091AG1-374 GEN
Solar/Wind Harmer
15.81
959611AF2-252 GEN
Solar/Wind Harmer
1.226
274801UNIV PARK;4U
50/50
6.185
276776AD2-060 GEN
Solar/Wind Harmer
0.383
274674JOLIET 9 ;6U
Adder
13.085
274676JOLIET 29;8U
Adder
25.801
274732ELWOOD EC;7P
Adder
13.616
274812UNIV PK N;8U
Adder
3.962
941551AE2-152 GEN
Solar/Wind Harmer
3.544
274682WAUKEGAN ;7U
Adder
13.732
274828WAUKEGAN ;BP
Adder
8.417
276691AA1-018 GEN1
Solar/Wind Harmer
0.353
274871GR RIDGE ;2U
Solar/Wind Harmer
5.785
274745AC1-111 GEN9
Adder
4.187
276901AD2-066 C O1
Solar/Wind Harmer
2.616
972207SS24-0001
Solar/Wind Harmer
15.98
274773LINCOLN ;4U
Adder
4.494
274774LINCOLN ;5U
Adder
4.494
276876AE1-163_GEN2
Solar/Wind Harmer
4.856
960751AF2-366 GEN
Solar/Wind Harmer
2.064
962781AG1-127 GEN
Solar/Wind Harmer
6.84
274872LEEDK;1U
Solar/Wind Harmer
5.879
970569AG2-363 GEN
Solar/Wind Harmer
21.28
971997AH1-543 GEN
Solar/Wind Harmer
11.145
276861AD2-134 GEN
Solar/Wind Harmer
1.259
274822ROCKFORD ;11
Adder
13.82
957471AF2-041 GEN
Solar/Wind Harmer
21.053
959081AF2-199 GEN
Solar/Wind Harmer
7.018
971067AG2-660 GEN
Solar/Wind Harmer
1.632
972235AH1-702 GEN1
Adder
1.765
970819AG2-516 GEN
Solar/Wind Harmer
8.36
971475AH1-234 GEN
Solar/Wind Harmer
15.56
939401AE1-172 GEN
Solar/Wind Harmer
9.576
274857EASY ROAD;U1
Solar/Wind Harmer
3.25
274761LEE CO EC;2U
Adder
6.31
274766LEE CO EC;7U
Adder
6.235
276158O29GEN2
Solar/Wind Harmer
3.29
274877BISHOP HL;1U
Solar/Wind Harmer
2.156
276164X3-005 C
Solar/Wind Harmer
0.427
276726Z2-087_GEN
Solar/Wind Harmer
4.383
939741AE1-205 GEN
Solar/Wind Harmer
11.083
274854TWINGROVE;U2
Solar/Wind Harmer
3.719
972175AH1-670 GEN
Solar/Wind Harmer
6.479
274827FISK ;RP
50/50
8.615
274687WILL CNTY;4U
50/50
26.703
274687WILL CNTY;4U
50/50
26.703
972037AH1-567 GEN1
50/50
0.174
960591AF2-350 GEN
Solar/Wind Harmer
9.068
274675JOLIET 29;7U
Adder
25.79
274675JOLIET 29;7U
Adder
24.869
274728ELWOOD EC;5P
Adder
13.616
274731ELWOOD EC;2P
Adder
13.592
274733ELWOOD EC;3P
Adder
13.592
274735ELWOOD EC;4P
Adder
13.592
972227AH1-698 GEN1
Adder
2.132
274814UNIV PK N;0U
Adder
3.997
274807UNIV PK N;3U
Adder
3.988
274805UNIV PK N;1U
Adder
3.971
274811UNIV PK N;7U
Adder
3.962
970833AG2-524 GEN
Solar/Wind Harmer
6.63
970833AG2-524 GEN
Solar/Wind Harmer
3.084
276868AE1-113 GEN
Solar/Wind Harmer
7.641
276882AE2-255 GEN
Solar/Wind Harmer
2.547
274746AC1-111 G10
Adder
4.187
274744AC1-111 GEN8
Adder
4.187
274775LINCOLN ;6U
Adder
4.494
274776LINCOLN ;7U
Adder
4.494
274777LINCOLN ;8U
Adder
4.494
971177AH1-047 GEN
Solar/Wind Harmer
4.243
971411AH1-196 GEN
Solar/Wind Harmer
10.788
971675AH1-338 GEN
Solar/Wind Harmer
12.691
274823ROCKFORD ;21
Adder
13.719
971171AH1-044 GEN
Solar/Wind Harmer
14.035
276612AE2-035 GEN
Solar/Wind Harmer
1.775
971681AH1-341 GEN
Solar/Wind Harmer
10.236
926823AC1-168 GEN
Solar/Wind Harmer
2.895
961011AF2-392 GEN
Solar/Wind Harmer
7.25
274863CRW1-WTG
Solar/Wind Harmer
3.67
274864CRW2-WTG
Solar/Wind Harmer
3.67
957751AF2-069 GEN
Solar/Wind Harmer
0.296
274848CAMPGROVE;RU
Solar/Wind Harmer
4.075
946321AF1-296 GEN
Solar/Wind Harmer
6.541
970169AG2-114 GEN
Solar/Wind Harmer
6.27
276655WTG1_EQ
Solar/Wind Harmer
4.838
276656WTG2_EQ
Solar/Wind Harmer
0.641
959341AF2-225 GEN
Solar/Wind Harmer
8.312
941731AE2-173 GEN
Solar/Wind Harmer
3.222
990512J1326
External Queue
3.9395570755004883
990117J1214
External Queue
13.552075386047363
990727J1377 G
External Queue
4.557984352111816
991777J1629 G
External Queue
9.00204086303711
990407J1304
External Queue
3.040069103240967
NYPJM->LTFIMP_NY
CLTF
0.643
WECLTFEXP_WEC->PJM
CLTF
2.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.258
CBM West 2LTFEXP_CBM-W2->PJM
CBM
18.563
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
36.493
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.705
MECLTFEXP_MEC->PJM
CLTF
8.342
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.339
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.976
LAGNLTFEXP_LAGN->PJM
CLTF
2.654
TVALTFEXP_TVA->PJM
CLTF
0.65

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:121.82 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1938.19
MW Contribution:11.05
Bus #Bus NameTypeMW Contribution
972179AH1-673 GEN
50/50
14.177
274723RIVER EC ;12
50/50
26.242
274813UNIV PK N;9U
50/50
0.35
274809UNIV PK N;5U
50/50
0.349
274812UNIV PK N;8U
50/50
6.393
966431AG1-512 GEN
50/50
2.238
274801UNIV PARK;4U
50/50
7.213
276164X3-005 C
Solar/Wind Harmer
0.937
276776AD2-060 GEN
Solar/Wind Harmer
0.528
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274676JOLIET 29;8U
Adder
33.992
274751CRETE EC ;1U
Adder
5.356
274754CRETE EC ;4U
Adder
5.356
274732ELWOOD EC;7P
Adder
17.945
274674JOLIET 9 ;6U
Adder
16.709
941551AE2-152 GEN
Solar/Wind Harmer
4.847
274871GR RIDGE ;2U
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
18.079
274828WAUKEGAN ;BP
Adder
11.082
972207SS24-0001
Solar/Wind Harmer
22.042
274773LINCOLN ;4U
Adder
6.2
274774LINCOLN ;5U
Adder
6.2
274745AC1-111 GEN9
Adder
5.555
276876AE1-163_GEN2
Solar/Wind Harmer
6.622
276901AD2-066 C O1
Solar/Wind Harmer
3.464
960751AF2-366 GEN
Solar/Wind Harmer
2.737
962781AG1-127 GEN
Solar/Wind Harmer
9.072
274872LEEDK;1U
Solar/Wind Harmer
7.797
971997AH1-543 GEN
Solar/Wind Harmer
14.798
970569AG2-363 GEN
Solar/Wind Harmer
28.029
276861AD2-134 GEN
Solar/Wind Harmer
1.668
939401AE1-172 GEN
Solar/Wind Harmer
13.014
274822ROCKFORD ;11
Adder
18.266
957471AF2-041 GEN
Solar/Wind Harmer
27.868
959081AF2-199 GEN
Solar/Wind Harmer
9.289
971067AG2-660 GEN
Solar/Wind Harmer
2.16
972235AH1-702 GEN1
Adder
2.333
970819AG2-516 GEN
Solar/Wind Harmer
11.049
971475AH1-234 GEN
Solar/Wind Harmer
20.56
274857EASY ROAD;U1
Solar/Wind Harmer
4.298
274761LEE CO EC;2U
Adder
8.344
274766LEE CO EC;7U
Adder
8.245
276158O29GEN2
Solar/Wind Harmer
4.354
274877BISHOP HL;1U
Solar/Wind Harmer
2.856
276726Z2-087_GEN
Solar/Wind Harmer
5.894
939741AE1-205 GEN
Solar/Wind Harmer
14.903
274854TWINGROVE;U2
Solar/Wind Harmer
4.996
972175AH1-670 GEN
Solar/Wind Harmer
8.682
274880W4-005 GEN4
Solar/Wind Harmer
0.034
274808UNIV PK N;4U
50/50
6.365
274803UNIV PARK;6U
50/50
7.353
274798UNIV PARK;1U
50/50
0.314
274888KELLY CRK;1U
Solar/Wind Harmer
7.374
274887GEN-1.85
Solar/Wind Harmer
6.657
276843GEN-1.7
Solar/Wind Harmer
0.716
958011AF2-095 GEN
Solar/Wind Harmer
17.985
958481AF2-142 GEN
Solar/Wind Harmer
16.726
274674JOLIET 9 ;6U
Adder
16.709
958491AF2-143 GEN
Solar/Wind Harmer
15.914
972259AH1-714 GEN
Adder
19.777
274861TOP CROP ;1U
Solar/Wind Harmer
6.234
274862TOP CROP ;2U
Solar/Wind Harmer
5.206
274847GR RIDGE ;BU
Solar/Wind Harmer
5.127
274683WAUKEGAN ;8U
Adder
21.142
274683WAUKEGAN ;8U
Adder
17.822
274770LINCOLN ;1U
Adder
6.2
274771LINCOLN ;2U
Adder
6.2
274879MINONK ;1U
Solar/Wind Harmer
6.679
276872AE1-163_GEN1
Solar/Wind Harmer
6.622
274696ROCKY RD ;4P
Adder
11.233
274695ROCKY RD ;2P
Adder
10.974
274693ROCKY RD ;1P
Adder
10.866
274697ROCKY RD ;3P
Adder
2.981
971573AH1-285 GEN
Solar/Wind Harmer
8.323
962691AG1-118 GEN
Solar/Wind Harmer
28.743
942991AE2-321 GEN
Solar/Wind Harmer
9.58
970921AG2-575 GEN
Solar/Wind Harmer
9.539
970921AG2-575 GEN
Solar/Wind Harmer
2.218
971333AH1-146 GEN
Solar/Wind Harmer
18.881
971335AH1-147 GEN
Solar/Wind Harmer
18.881
971341AH1-150 GEN
Solar/Wind Harmer
18.579
971343AH1-151 GEN
Solar/Wind Harmer
18.579
274856ECOGROVE ;U1
Solar/Wind Harmer
3.092
276611AD2-172 GEN
Solar/Wind Harmer
2.346
938861AE1-114 GEN
Solar/Wind Harmer
7.404
274764LEE CO EC;5U
Adder
8.363
274765LEE CO EC;6U
Adder
8.363
274762LEE CO EC;3U
Adder
8.344
274763LEE CO EC;4U
Adder
8.265
276603SUBLETTE C
Solar/Wind Harmer
0.935
972267AH1-718 GEN
Adder
3.656
276741O09 GEN1
Solar/Wind Harmer
3.11
276708O09 GEN2
Solar/Wind Harmer
3.11
274851PROVIDENC;RU
Solar/Wind Harmer
2.433
274849CRESCENT ;1U
Solar/Wind Harmer
1.58
276645AC1-214 GEN1
Solar/Wind Harmer
1.144
276646AC1-214 GEN2
Solar/Wind Harmer
1.144
276782AC1-033 GEN
Solar/Wind Harmer
3.375
960611AF2-352 GEN
Solar/Wind Harmer
1.646
24441505OLIV SLR
Solar/Wind Helper
0.062
270526AF1-158 GEN
Solar/Wind Helper
1.044
274826FISK ;BP
50/50
15.075
274806UNIV PK N;2U
50/50
0.357
274815UNIV PK N;XU
50/50
0.351
274816UNIV PK N;YU
50/50
0.35
274810UNIV PK N;6U
50/50
0.35
274802UNIV PARK;5U
50/50
7.353
274799UNIV PARK;2U
50/50
0.324
274800UNIV PARK;3U
50/50
7.213
972038AH1-567 GEN2
50/50
0.451
276772AC2-154 GEN
Solar/Wind Harmer
3.483
276806AD2-047 C O1
Solar/Wind Harmer
13.361
970941AG2-585 GEN
Solar/Wind Harmer
15.612
276893AG1-478 C
Solar/Wind Harmer
0.474
276694AA1-018 GEN2
Solar/Wind Harmer
7.037
972228AH1-698 GEN2
Adder
4.13
274676JOLIET 29;8U
Adder
32.778
972231SS25-0005
Solar/Wind Harmer
10.398
972181SS23-001
Solar/Wind Harmer
6.499
274752CRETE EC ;2U
Adder
5.356
274753CRETE EC ;3U
Adder
5.356
274729ELWOOD EC;1P
Adder
17.949
274730ELWOOD EC;6P
Adder
17.945
274734ELWOOD EC;8P
Adder
17.945
274736ELWOOD EC;9P
Adder
17.945
276897AD1-100 C
Solar/Wind Harmer
31.017
939351AE1-166 GEN
Solar/Wind Harmer
6.338
276805AD2-038 GEN
Solar/Wind Harmer
5.442
274682WAUKEGAN ;7U
Adder
18.079
274772LINCOLN ;3U
Adder
6.2
276889AE2-281 GEN
Solar/Wind Harmer
1.892
943121AE2-341 GEN
Solar/Wind Harmer
14.588
943591AF1-030 GEN
Solar/Wind Harmer
9.726
970707AG2-453 GEN
Solar/Wind Harmer
26.994
274872LEEDK;1U
Solar/Wind Harmer
0.243
276799AD1-013 GEN
Solar/Wind Harmer
2.068
946671AF1-331 GEN
Solar/Wind Harmer
0.391
970571AG2-364 GEN
Solar/Wind Harmer
18.686
274855GSG-6 ;RU
Solar/Wind Harmer
3.45
274850MENDOTA H;RU
Solar/Wind Harmer
2.399
276602WESTBROOK C
Solar/Wind Harmer
1.986
276863AD2-134 GEN
Solar/Wind Harmer
1.668
959091AF2-200 GEN
Solar/Wind Harmer
18.579
972236AH1-702 GEN2
Adder
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
4.298
274760LEE CO EC;1U
Adder
8.344
274767LEE CO EC;8U
Adder
8.245
276157O29GEN1
Solar/Wind Harmer
3.312
274878BISHOP HL;2U
Solar/Wind Harmer
2.856
965931AG1-462 GEN
Solar/Wind Harmer
20.903
942111AE2-223 GEN
Solar/Wind Harmer
6.109
274853TWINGROVE;U1
Solar/Wind Harmer
5.103
965091AG1-374 GEN
Solar/Wind Harmer
21.239
959611AF2-252 GEN
Solar/Wind Harmer
1.646
274724RIVER EC ;11
Adder
9.565
276686W4-005 GEN3
Solar/Wind Harmer
0.034
274827FISK ;RP
50/50
10.684
274814UNIV PK N;0U
50/50
6.449
274807UNIV PK N;3U
50/50
6.435
274805UNIV PK N;1U
50/50
6.407
274811UNIV PK N;7U
50/50
6.393
972037AH1-567 GEN1
50/50
0.231
960591AF2-350 GEN
Solar/Wind Harmer
12.489
972227AH1-698 GEN1
Adder
2.906
274687WILL CNTY;4U
Adder
31.015
274687WILL CNTY;4U
Adder
31.015
274675JOLIET 29;7U
Adder
33.999
274675JOLIET 29;7U
Adder
32.784
274731ELWOOD EC;2P
Adder
17.949
274733ELWOOD EC;3P
Adder
17.949
274735ELWOOD EC;4P
Adder
17.949
274728ELWOOD EC;5P
Adder
17.945
970833AG2-524 GEN
Solar/Wind Harmer
8.898
970833AG2-524 GEN
Solar/Wind Harmer
4.139
274775LINCOLN ;6U
Adder
6.2
274776LINCOLN ;7U
Adder
6.2
274777LINCOLN ;8U
Adder
6.2
274746AC1-111 G10
Adder
5.555
274744AC1-111 GEN8
Adder
5.555
276868AE1-113 GEN
Solar/Wind Harmer
10.017
276882AE2-255 GEN
Solar/Wind Harmer
3.339
971177AH1-047 GEN
Solar/Wind Harmer
5.607
971411AH1-196 GEN
Solar/Wind Harmer
14.253
971675AH1-338 GEN
Solar/Wind Harmer
16.822
274823ROCKFORD ;21
Adder
18.134
971171AH1-044 GEN
Solar/Wind Harmer
18.579
276612AE2-035 GEN
Solar/Wind Harmer
2.346
971681AH1-341 GEN
Solar/Wind Harmer
13.54
926823AC1-168 GEN
Solar/Wind Harmer
3.856
274863CRW1-WTG
Solar/Wind Harmer
4.973
274864CRW2-WTG
Solar/Wind Harmer
4.973
961011AF2-392 GEN
Solar/Wind Harmer
9.592
957751AF2-069 GEN
Solar/Wind Harmer
0.392
970169AG2-114 GEN
Solar/Wind Harmer
8.429
274848CAMPGROVE;RU
Solar/Wind Harmer
5.398
946321AF1-296 GEN
Solar/Wind Harmer
8.648
276655WTG1_EQ
Solar/Wind Harmer
6.506
276656WTG2_EQ
Solar/Wind Harmer
0.861
959341AF2-225 GEN
Solar/Wind Harmer
11.178
941731AE2-173 GEN
Solar/Wind Harmer
4.332
960681AF2-359 GEN
Solar/Wind Helper
1.016
276785W4-005 GEN1
Solar/Wind Harmer
0.034
276174W4-005 GEN2
Solar/Wind Harmer
0.034
990512J1326
External Queue
5.108882904052734
990117J1214
External Queue
17.574556350708008
990727J1377 G
External Queue
5.916489124298096
991092J1477
External Queue
2.769141674041748
991777J1629 G
External Queue
11.657174110412598
990407J1304
External Queue
3.9451146125793457
NYPJM->LTFIMP_NY
CLTF
0.854
WECLTFEXP_WEC->PJM
CLTF
3.585
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.273
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.64
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.18
MECLTFEXP_MEC->PJM
CLTF
11.015
SIGELTFEXP_SIGE->PJM
CLTF
0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.467
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.35
LAGNLTFEXP_LAGN->PJM
CLTF
3.477
TVALTFEXP_TVA->PJM
CLTF
0.842

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:119.96 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1908.56
MW Contribution:11.05
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
10.684
274814UNIV PK N;0U
50/50
6.449
274807UNIV PK N;3U
50/50
6.435
274805UNIV PK N;1U
50/50
6.407
274811UNIV PK N;7U
50/50
6.393
972037AH1-567 GEN1
50/50
0.231
960591AF2-350 GEN
Solar/Wind Harmer
12.489
972227AH1-698 GEN1
Adder
2.906
274687WILL CNTY;4U
Adder
31.015
274687WILL CNTY;4U
Adder
31.015
274675JOLIET 29;7U
Adder
33.999
274675JOLIET 29;7U
Adder
32.784
274731ELWOOD EC;2P
Adder
17.949
274733ELWOOD EC;3P
Adder
17.949
274735ELWOOD EC;4P
Adder
17.949
274728ELWOOD EC;5P
Adder
17.945
970833AG2-524 GEN
Solar/Wind Harmer
8.898
970833AG2-524 GEN
Solar/Wind Harmer
4.139
274775LINCOLN ;6U
Adder
6.2
274776LINCOLN ;7U
Adder
6.2
274777LINCOLN ;8U
Adder
6.2
274746AC1-111 G10
Adder
5.555
274744AC1-111 GEN8
Adder
5.555
276868AE1-113 GEN
Solar/Wind Harmer
10.017
276882AE2-255 GEN
Solar/Wind Harmer
3.339
971177AH1-047 GEN
Solar/Wind Harmer
5.607
971411AH1-196 GEN
Solar/Wind Harmer
14.253
971675AH1-338 GEN
Solar/Wind Harmer
16.822
274823ROCKFORD ;21
Adder
18.134
971171AH1-044 GEN
Solar/Wind Harmer
18.579
276612AE2-035 GEN
Solar/Wind Harmer
2.346
971681AH1-341 GEN
Solar/Wind Harmer
13.54
926823AC1-168 GEN
Solar/Wind Harmer
3.856
274863CRW1-WTG
Solar/Wind Harmer
4.973
274864CRW2-WTG
Solar/Wind Harmer
4.973
961011AF2-392 GEN
Solar/Wind Harmer
9.592
957751AF2-069 GEN
Solar/Wind Harmer
0.392
970169AG2-114 GEN
Solar/Wind Harmer
8.429
274848CAMPGROVE;RU
Solar/Wind Harmer
5.398
946321AF1-296 GEN
Solar/Wind Harmer
8.648
276655WTG1_EQ
Solar/Wind Harmer
6.506
276656WTG2_EQ
Solar/Wind Harmer
0.861
959341AF2-225 GEN
Solar/Wind Harmer
11.178
941731AE2-173 GEN
Solar/Wind Harmer
4.332
276785W4-005 GEN1
Solar/Wind Harmer
1.728
276174W4-005 GEN2
Solar/Wind Harmer
1.728
960681AF2-359 GEN
Solar/Wind Helper
1.016
972179AH1-673 GEN
50/50
14.177
274723RIVER EC ;12
50/50
26.242
274813UNIV PK N;9U
50/50
0.35
274809UNIV PK N;5U
50/50
0.349
274812UNIV PK N;8U
50/50
6.393
966431AG1-512 GEN
50/50
2.238
274801UNIV PARK;4U
50/50
7.213
276164X3-005 C
Solar/Wind Harmer
0.937
276776AD2-060 GEN
Solar/Wind Harmer
0.528
276691AA1-018 GEN1
Solar/Wind Harmer
0.519
274676JOLIET 29;8U
Adder
33.992
274732ELWOOD EC;7P
Adder
17.945
274674JOLIET 9 ;6U
Adder
16.709
941551AE2-152 GEN
Solar/Wind Harmer
4.847
274871GR RIDGE ;2U
Solar/Wind Harmer
7.795
274682WAUKEGAN ;7U
Adder
18.079
274828WAUKEGAN ;BP
Adder
11.082
972207SS24-0001
Solar/Wind Harmer
22.042
274773LINCOLN ;4U
Adder
6.2
274774LINCOLN ;5U
Adder
6.2
274745AC1-111 GEN9
Adder
5.555
276876AE1-163_GEN2
Solar/Wind Harmer
6.622
276901AD2-066 C O1
Solar/Wind Harmer
3.464
960751AF2-366 GEN
Solar/Wind Harmer
2.737
962781AG1-127 GEN
Solar/Wind Harmer
9.072
274872LEEDK;1U
Solar/Wind Harmer
7.797
971997AH1-543 GEN
Solar/Wind Harmer
14.798
970569AG2-363 GEN
Solar/Wind Harmer
28.029
276861AD2-134 GEN
Solar/Wind Harmer
1.668
939401AE1-172 GEN
Solar/Wind Harmer
13.014
274822ROCKFORD ;11
Adder
18.266
957471AF2-041 GEN
Solar/Wind Harmer
27.868
959081AF2-199 GEN
Solar/Wind Harmer
9.289
971067AG2-660 GEN
Solar/Wind Harmer
2.16
972235AH1-702 GEN1
Adder
2.333
970819AG2-516 GEN
Solar/Wind Harmer
11.049
971475AH1-234 GEN
Solar/Wind Harmer
20.56
274857EASY ROAD;U1
Solar/Wind Harmer
4.298
274761LEE CO EC;2U
Adder
8.344
274766LEE CO EC;7U
Adder
8.245
276158O29GEN2
Solar/Wind Harmer
4.354
274877BISHOP HL;1U
Solar/Wind Harmer
2.856
276726Z2-087_GEN
Solar/Wind Harmer
5.894
939741AE1-205 GEN
Solar/Wind Harmer
14.903
274854TWINGROVE;U2
Solar/Wind Harmer
4.996
972175AH1-670 GEN
Solar/Wind Harmer
8.682
274880W4-005 GEN4
Solar/Wind Harmer
1.728
274808UNIV PK N;4U
50/50
6.365
274803UNIV PARK;6U
50/50
7.353
274798UNIV PARK;1U
50/50
0.314
274888KELLY CRK;1U
Solar/Wind Harmer
7.374
274887GEN-1.85
Solar/Wind Harmer
6.657
276843GEN-1.7
Solar/Wind Harmer
0.716
958011AF2-095 GEN
Solar/Wind Harmer
17.985
958481AF2-142 GEN
Solar/Wind Harmer
16.726
274674JOLIET 9 ;6U
Adder
16.709
958491AF2-143 GEN
Solar/Wind Harmer
15.914
972259AH1-714 GEN
Adder
19.777
274861TOP CROP ;1U
Solar/Wind Harmer
6.234
274862TOP CROP ;2U
Solar/Wind Harmer
5.206
274847GR RIDGE ;BU
Solar/Wind Harmer
5.127
274683WAUKEGAN ;8U
Adder
21.142
274683WAUKEGAN ;8U
Adder
17.822
274770LINCOLN ;1U
Adder
6.2
274771LINCOLN ;2U
Adder
6.2
274879MINONK ;1U
Solar/Wind Harmer
6.679
276872AE1-163_GEN1
Solar/Wind Harmer
6.622
274696ROCKY RD ;4P
Adder
11.233
274695ROCKY RD ;2P
Adder
10.974
274693ROCKY RD ;1P
Adder
10.866
274697ROCKY RD ;3P
Adder
2.981
971573AH1-285 GEN
Solar/Wind Harmer
8.323
962691AG1-118 GEN
Solar/Wind Harmer
28.743
942991AE2-321 GEN
Solar/Wind Harmer
9.58
970921AG2-575 GEN
Solar/Wind Harmer
9.539
970921AG2-575 GEN
Solar/Wind Harmer
2.218
971333AH1-146 GEN
Solar/Wind Harmer
18.881
971335AH1-147 GEN
Solar/Wind Harmer
18.881
971341AH1-150 GEN
Solar/Wind Harmer
18.579
971343AH1-151 GEN
Solar/Wind Harmer
18.579
274856ECOGROVE ;U1
Solar/Wind Harmer
3.092
276611AD2-172 GEN
Solar/Wind Harmer
2.346
938861AE1-114 GEN
Solar/Wind Harmer
7.404
274764LEE CO EC;5U
Adder
8.363
274765LEE CO EC;6U
Adder
8.363
274762LEE CO EC;3U
Adder
8.344
274763LEE CO EC;4U
Adder
8.265
276603SUBLETTE C
Solar/Wind Harmer
0.935
972267AH1-718 GEN
Adder
3.656
276741O09 GEN1
Solar/Wind Harmer
3.11
276708O09 GEN2
Solar/Wind Harmer
3.11
274851PROVIDENC;RU
Solar/Wind Harmer
2.433
274849CRESCENT ;1U
Solar/Wind Harmer
1.58
276645AC1-214 GEN1
Solar/Wind Harmer
1.144
276646AC1-214 GEN2
Solar/Wind Harmer
1.144
276782AC1-033 GEN
Solar/Wind Harmer
3.375
960611AF2-352 GEN
Solar/Wind Harmer
1.646
24441505OLIV SLR
Solar/Wind Helper
0.062
270526AF1-158 GEN
Solar/Wind Helper
1.044
274826FISK ;BP
50/50
15.075
274806UNIV PK N;2U
50/50
0.357
274815UNIV PK N;XU
50/50
0.351
274816UNIV PK N;YU
50/50
0.35
274810UNIV PK N;6U
50/50
0.35
274802UNIV PARK;5U
50/50
7.353
274799UNIV PARK;2U
50/50
0.324
274800UNIV PARK;3U
50/50
7.213
972038AH1-567 GEN2
50/50
0.451
276772AC2-154 GEN
Solar/Wind Harmer
3.483
276806AD2-047 C O1
Solar/Wind Harmer
13.361
970941AG2-585 GEN
Solar/Wind Harmer
15.612
276893AG1-478 C
Solar/Wind Harmer
0.474
276694AA1-018 GEN2
Solar/Wind Harmer
7.037
972228AH1-698 GEN2
Adder
4.13
274676JOLIET 29;8U
Adder
32.778
274729ELWOOD EC;1P
Adder
17.949
274730ELWOOD EC;6P
Adder
17.945
274734ELWOOD EC;8P
Adder
17.945
274736ELWOOD EC;9P
Adder
17.945
276897AD1-100 C
Solar/Wind Harmer
31.017
939351AE1-166 GEN
Solar/Wind Harmer
6.338
276805AD2-038 GEN
Solar/Wind Harmer
5.442
274682WAUKEGAN ;7U
Adder
18.079
274772LINCOLN ;3U
Adder
6.2
276889AE2-281 GEN
Solar/Wind Harmer
1.892
943121AE2-341 GEN
Solar/Wind Harmer
14.588
943591AF1-030 GEN
Solar/Wind Harmer
9.726
970707AG2-453 GEN
Solar/Wind Harmer
26.994
274872LEEDK;1U
Solar/Wind Harmer
0.243
276799AD1-013 GEN
Solar/Wind Harmer
2.068
946671AF1-331 GEN
Solar/Wind Harmer
0.391
970571AG2-364 GEN
Solar/Wind Harmer
18.686
274855GSG-6 ;RU
Solar/Wind Harmer
3.45
274850MENDOTA H;RU
Solar/Wind Harmer
2.399
276602WESTBROOK C
Solar/Wind Harmer
1.986
276863AD2-134 GEN
Solar/Wind Harmer
1.668
959091AF2-200 GEN
Solar/Wind Harmer
18.579
972236AH1-702 GEN2
Adder
2.028
274858EASY ROAD;U2
Solar/Wind Harmer
4.298
274760LEE CO EC;1U
Adder
8.344
274767LEE CO EC;8U
Adder
8.245
276157O29GEN1
Solar/Wind Harmer
3.312
274878BISHOP HL;2U
Solar/Wind Harmer
2.856
965931AG1-462 GEN
Solar/Wind Harmer
20.903
942111AE2-223 GEN
Solar/Wind Harmer
6.109
274853TWINGROVE;U1
Solar/Wind Harmer
5.103
965091AG1-374 GEN
Solar/Wind Harmer
21.239
959611AF2-252 GEN
Solar/Wind Harmer
1.646
276686W4-005 GEN3
Solar/Wind Harmer
1.728
274724RIVER EC ;11
Adder
9.565
971993AH1-541 GEN
Solar/Wind Harmer
2.036
990512J1326
External Queue
5.108882904052734
990117J1214
External Queue
17.574556350708008
990727J1377 G
External Queue
5.916489124298096
991092J1477
External Queue
2.769141674041748
991777J1629 G
External Queue
11.657174110412598
990407J1304
External Queue
3.9451146125793457
NYPJM->LTFIMP_NY
CLTF
0.854
WECLTFEXP_WEC->PJM
CLTF
3.585
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.273
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.173
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.64
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.18
MECLTFEXP_MEC->PJM
CLTF
11.015
SIGELTFEXP_SIGE->PJM
CLTF
0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.467
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.35
LAGNLTFEXP_LAGN->PJM
CLTF
3.477
TVALTFEXP_TVA->PJM
CLTF
0.842

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.09 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1783.3
MW Contribution:10.9
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
10.217
960591AF2-350 GEN
Solar/Wind Harmer
12.073
274775LINCOLN ;6U
Adder
7.259
274776LINCOLN ;7U
Adder
7.259
274777LINCOLN ;8U
Adder
7.259
274675JOLIET 29;7U
Adder
31.65
274675JOLIET 29;7U
Adder
30.52
274687WILL CNTY;4U
Adder
28.813
274687WILL CNTY;4U
Adder
28.813
972227AH1-698 GEN1
Adder
2.662
274731ELWOOD EC;2P
Adder
16.726
274733ELWOOD EC;3P
Adder
16.726
274735ELWOOD EC;4P
Adder
16.726
274728ELWOOD EC;5P
Adder
16.713
972037AH1-567 GEN1
Adder
0.183
970833AG2-524 GEN
Solar/Wind Harmer
8.703
970833AG2-524 GEN
Solar/Wind Harmer
4.048
274746AC1-111 G10
Adder
5.561
274744AC1-111 GEN8
Adder
5.561
971177AH1-047 GEN
Solar/Wind Harmer
5.532
971411AH1-196 GEN
Solar/Wind Harmer
14.053
276868AE1-113 GEN
Solar/Wind Harmer
9.466
276882AE2-255 GEN
Solar/Wind Harmer
3.155
971675AH1-338 GEN
Solar/Wind Harmer
16.796
971171AH1-044 GEN
Solar/Wind Harmer
18.438
274823ROCKFORD ;21
Adder
17.9
274863CRW1-WTG
Solar/Wind Harmer
5.068
274864CRW2-WTG
Solar/Wind Harmer
5.068
276612AE2-035 GEN
Solar/Wind Harmer
2.316
971681AH1-341 GEN
Solar/Wind Harmer
13.385
926823AC1-168 GEN
Solar/Wind Harmer
3.758
961011AF2-392 GEN
Solar/Wind Harmer
9.475
970169AG2-114 GEN
Solar/Wind Harmer
8.538
957751AF2-069 GEN
Solar/Wind Harmer
0.383
946321AF1-296 GEN
Solar/Wind Harmer
8.521
274848CAMPGROVE;RU
Solar/Wind Harmer
5.265
276655WTG1_EQ
Solar/Wind Harmer
6.612
276656WTG2_EQ
Solar/Wind Harmer
0.875
959341AF2-225 GEN
Solar/Wind Harmer
11.36
941731AE2-173 GEN
Solar/Wind Harmer
4.403
274814UNIV PK N;0U
Adder
3.46
274807UNIV PK N;3U
Adder
3.452
274805UNIV PK N;1U
Adder
3.437
274811UNIV PK N;7U
Adder
3.43
276785W4-005 GEN1
Solar/Wind Harmer
1.759
276174W4-005 GEN2
Solar/Wind Harmer
1.759
276849AB2-070 GEN2
Solar/Wind Harmer
1.303
276848AB2-070 GEN3
Solar/Wind Harmer
1.303
972179AH1-673 GEN
50/50
15.342
274723RIVER EC ;12
50/50
28.573
276164X3-005 C
Solar/Wind Harmer
0.97
276776AD2-060 GEN
Solar/Wind Harmer
0.51
972207SS24-0001
Solar/Wind Harmer
25.81
274773LINCOLN ;4U
Adder
7.259
274774LINCOLN ;5U
Adder
7.259
274801UNIV PARK;4U
Adder
6.572
941551AE2-152 GEN
Solar/Wind Harmer
4.819
274674JOLIET 9 ;6U
Adder
16.145
274676JOLIET 29;8U
Adder
31.641
276691AA1-018 GEN1
Solar/Wind Harmer
0.478
274732ELWOOD EC;7P
Adder
16.713
274745AC1-111 GEN9
Adder
5.561
274871GR RIDGE ;2U
Solar/Wind Harmer
7.625
274682WAUKEGAN ;7U
Adder
17.565
274828WAUKEGAN ;BP
Adder
10.769
960751AF2-366 GEN
Solar/Wind Harmer
2.74
962781AG1-127 GEN
Solar/Wind Harmer
9.084
939401AE1-172 GEN
Solar/Wind Harmer
13.283
274872LEEDK;1U
Solar/Wind Harmer
7.809
276901AD2-066 C O1
Solar/Wind Harmer
3.317
276861AD2-134 GEN
Solar/Wind Harmer
1.666
276876AE1-163_GEN2
Solar/Wind Harmer
6.213
971997AH1-543 GEN
Solar/Wind Harmer
14.549
957471AF2-041 GEN
Solar/Wind Harmer
27.658
959081AF2-199 GEN
Solar/Wind Harmer
9.219
971067AG2-660 GEN
Solar/Wind Harmer
2.144
274822ROCKFORD ;11
Adder
18.03
972235AH1-702 GEN1
Adder
2.304
970819AG2-516 GEN
Solar/Wind Harmer
10.902
971475AH1-234 GEN
Solar/Wind Harmer
20.266
274857EASY ROAD;U1
Solar/Wind Harmer
4.245
958011AF2-095 GEN
Solar/Wind Harmer
17.386
274888KELLY CRK;1U
Solar/Wind Harmer
7.128
274887GEN-1.85
Solar/Wind Harmer
6.435
276843GEN-1.7
Solar/Wind Harmer
0.692
274770LINCOLN ;1U
Adder
7.259
274771LINCOLN ;2U
Adder
7.259
274674JOLIET 9 ;6U
Adder
16.145
958481AF2-142 GEN
Solar/Wind Harmer
15.409
972259AH1-714 GEN
Adder
19.364
274803UNIV PARK;6U
Adder
5.821
274847GR RIDGE ;BU
Solar/Wind Harmer
5.016
971573AH1-285 GEN
Solar/Wind Harmer
8.467
958491AF2-143 GEN
Solar/Wind Harmer
14.766
274695ROCKY RD ;2P
Adder
10.859
274693ROCKY RD ;1P
Adder
10.752
274697ROCKY RD ;3P
Adder
2.95
274696ROCKY RD ;4P
Adder
11.115
274683WAUKEGAN ;8U
Adder
20.545
274683WAUKEGAN ;8U
Adder
17.319
962691AG1-118 GEN
Solar/Wind Harmer
28.792
970921AG2-575 GEN
Solar/Wind Harmer
9.552
970921AG2-575 GEN
Solar/Wind Harmer
2.221
942991AE2-321 GEN
Solar/Wind Harmer
9.449
274879MINONK ;1U
Solar/Wind Harmer
6.311
971333AH1-146 GEN
Solar/Wind Harmer
18.687
971335AH1-147 GEN
Solar/Wind Harmer
18.687
274861TOP CROP ;1U
Solar/Wind Harmer
5.622
274862TOP CROP ;2U
Solar/Wind Harmer
4.695
276872AE1-163_GEN1
Solar/Wind Harmer
6.213
971341AH1-150 GEN
Solar/Wind Harmer
18.438
971343AH1-151 GEN
Solar/Wind Harmer
18.438
274856ECOGROVE ;U1
Solar/Wind Harmer
3.052
276611AD2-172 GEN
Solar/Wind Harmer
2.316
938861AE1-114 GEN
Solar/Wind Harmer
7.314
274764LEE CO EC;5U
Adder
8.261
274765LEE CO EC;6U
Adder
8.261
274762LEE CO EC;3U
Adder
8.241
274763LEE CO EC;4U
Adder
8.163
276603SUBLETTE C
Solar/Wind Harmer
0.925
972267AH1-718 GEN
Adder
3.611
276741O09 GEN1
Solar/Wind Harmer
3.063
276708O09 GEN2
Solar/Wind Harmer
3.063
274851PROVIDENC;RU
Solar/Wind Harmer
2.373
274849CRESCENT ;1U
Solar/Wind Harmer
1.54
276645AC1-214 GEN1
Solar/Wind Harmer
1.116
276646AC1-214 GEN2
Solar/Wind Harmer
1.116
276782AC1-033 GEN
Solar/Wind Harmer
3.295
960611AF2-352 GEN
Solar/Wind Harmer
1.674
274808UNIV PK N;4U
Adder
3.415
276763AC1-053 GEN1
Solar/Wind Harmer
2.256
276764AC1-053 GEN2
Solar/Wind Harmer
2.256
274761LEE CO EC;2U
Adder
8.241
274766LEE CO EC;7U
Adder
8.144
970569AG2-363 GEN
Solar/Wind Harmer
26.525
276158O29GEN2
Solar/Wind Harmer
4.288
274877BISHOP HL;1U
Solar/Wind Harmer
2.788
276726Z2-087_GEN
Solar/Wind Harmer
5.99
939741AE1-205 GEN
Solar/Wind Harmer
15.147
274854TWINGROVE;U2
Solar/Wind Harmer
5.078
274812UNIV PK N;8U
Adder
3.43
972175AH1-670 GEN
Solar/Wind Harmer
8.832
274880W4-005 GEN4
Solar/Wind Harmer
1.759
963831AG1-236 GEN
Solar/Wind Harmer
5.613
274826FISK ;BP
50/50
14.417
276772AC2-154 GEN
Solar/Wind Harmer
3.367
276806AD2-047 C O1
Solar/Wind Harmer
12.916
970941AG2-585 GEN
Solar/Wind Harmer
15.092
274772LINCOLN ;3U
Adder
7.259
274800UNIV PARK;3U
Adder
6.572
972038AH1-567 GEN2
Adder
0.411
276893AG1-478 C
Solar/Wind Harmer
0.452
276897AD1-100 C
Solar/Wind Harmer
30.836
939351AE1-166 GEN
Solar/Wind Harmer
6.301
274676JOLIET 29;8U
Adder
30.511
276694AA1-018 GEN2
Solar/Wind Harmer
6.483
972228AH1-698 GEN2
Adder
3.782
274729ELWOOD EC;1P
Adder
16.726
274730ELWOOD EC;6P
Adder
16.713
274734ELWOOD EC;8P
Adder
16.713
274736ELWOOD EC;9P
Adder
16.713
970707AG2-453 GEN
Solar/Wind Harmer
28.408
274802UNIV PARK;5U
Adder
5.821
943121AE2-341 GEN
Solar/Wind Harmer
14.914
943591AF1-030 GEN
Solar/Wind Harmer
9.943
276805AD2-038 GEN
Solar/Wind Harmer
5.05
274682WAUKEGAN ;7U
Adder
17.565
274872LEEDK;1U
Solar/Wind Harmer
0.243
276799AD1-013 GEN
Solar/Wind Harmer
2.065
946671AF1-331 GEN
Solar/Wind Harmer
0.391
274855GSG-6 ;RU
Solar/Wind Harmer
3.444
274850MENDOTA H;RU
Solar/Wind Harmer
2.395
276602WESTBROOK C
Solar/Wind Harmer
1.982
276863AD2-134 GEN
Solar/Wind Harmer
1.666
276889AE2-281 GEN
Solar/Wind Harmer
1.775
959091AF2-200 GEN
Solar/Wind Harmer
18.438
972236AH1-702 GEN2
Adder
2.003
274858EASY ROAD;U2
Solar/Wind Harmer
4.245
274760LEE CO EC;1U
Adder
8.241
274767LEE CO EC;8U
Adder
8.144
970571AG2-364 GEN
Solar/Wind Harmer
17.683
276157O29GEN1
Solar/Wind Harmer
3.261
274878BISHOP HL;2U
Solar/Wind Harmer
2.788
965931AG1-462 GEN
Solar/Wind Harmer
20.591
942111AE2-223 GEN
Solar/Wind Harmer
6.208
274853TWINGROVE;U1
Solar/Wind Harmer
5.187
965091AG1-374 GEN
Solar/Wind Harmer
21.591
959611AF2-252 GEN
Solar/Wind Harmer
1.674
274724RIVER EC ;11
Adder
11.404
276686W4-005 GEN3
Solar/Wind Harmer
1.759
971993AH1-541 GEN
Solar/Wind Harmer
5.375
276668AB2-070 GEN1
Solar/Wind Harmer
1.303
990512J1326
External Queue
4.853736400604248
990117J1214
External Queue
11.036625862121582
990727J1377 G
External Queue
5.637885093688965
991092J1477
External Queue
2.612919330596924
990407J1304
External Queue
3.7535388469696045
NYPJM->LTFIMP_NY
CLTF
0.848
WECLTFEXP_WEC->PJM
CLTF
3.499
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.051
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.172
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.973
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.319
MECLTFEXP_MEC->PJM
CLTF
10.858
SIGELTFEXP_SIGE->PJM
CLTF
0.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.431
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.23
LAGNLTFEXP_LAGN->PJM
CLTF
3.51
TVALTFEXP_TVA->PJM
CLTF
0.873

Details for BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line l/o COMED_P4_112-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE/NIPS
Facility Description:
BURNHAM ;0R-17MUNSTER 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_112-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.08 %
Rating:1591.0 MVA
Rating Type:B
MVA to Mitigate:1783.23
MW Contribution:10.9
Bus #Bus NameTypeMW Contribution
274827FISK ;RP
50/50
10.217
960591AF2-350 GEN
Solar/Wind Harmer
12.074
274775LINCOLN ;6U
Adder
7.264
274776LINCOLN ;7U
Adder
7.264
274777LINCOLN ;8U
Adder
7.264
274675JOLIET 29;7U
Adder
31.649
274675JOLIET 29;7U
Adder
30.519
274687WILL CNTY;4U
Adder
28.812
274687WILL CNTY;4U
Adder
28.812
972227AH1-698 GEN1
Adder
2.662
274731ELWOOD EC;2P
Adder
16.725
274733ELWOOD EC;3P
Adder
16.725
274735ELWOOD EC;4P
Adder
16.725
274728ELWOOD EC;5P
Adder
16.713
972037AH1-567 GEN1
Adder
0.183
970833AG2-524 GEN
Solar/Wind Harmer
8.702
970833AG2-524 GEN
Solar/Wind Harmer
4.047
274746AC1-111 G10
Adder
5.561
274744AC1-111 GEN8
Adder
5.561
971177AH1-047 GEN
Solar/Wind Harmer
5.531
971411AH1-196 GEN
Solar/Wind Harmer
14.052
276868AE1-113 GEN
Solar/Wind Harmer
9.465
276882AE2-255 GEN
Solar/Wind Harmer
3.155
971675AH1-338 GEN
Solar/Wind Harmer
16.793
971171AH1-044 GEN
Solar/Wind Harmer
18.436
274823ROCKFORD ;21
Adder
17.897
274863CRW1-WTG
Solar/Wind Harmer
5.068
274864CRW2-WTG
Solar/Wind Harmer
5.068
274888KELLY CRK;1U
Solar/Wind Harmer
7.128
274887GEN-1.85
Solar/Wind Harmer
6.436
276843GEN-1.7
Solar/Wind Harmer
0.692
958011AF2-095 GEN
Solar/Wind Harmer
17.386
274770LINCOLN ;1U
Adder
7.264
274771LINCOLN ;2U
Adder
7.264
274674JOLIET 9 ;6U
Adder
16.144
958481AF2-142 GEN
Solar/Wind Harmer
15.409
972259AH1-714 GEN
Adder
19.362
274803UNIV PARK;6U
Adder
5.821
274847GR RIDGE ;BU
Solar/Wind Harmer
5.015
958491AF2-143 GEN
Solar/Wind Harmer
14.766
971573AH1-285 GEN
Solar/Wind Harmer
8.466
274695ROCKY RD ;2P
Adder
10.857
274693ROCKY RD ;1P
Adder
10.751
274697ROCKY RD ;3P
Adder
2.949
274696ROCKY RD ;4P
Adder
11.113
274683WAUKEGAN ;8U
Adder
20.543
274683WAUKEGAN ;8U
Adder
17.317
962691AG1-118 GEN
Solar/Wind Harmer
28.788
970921AG2-575 GEN
Solar/Wind Harmer
9.55
970921AG2-575 GEN
Solar/Wind Harmer
2.221
942991AE2-321 GEN
Solar/Wind Harmer
9.448
274879MINONK ;1U
Solar/Wind Harmer
6.311
971333AH1-146 GEN
Solar/Wind Harmer
18.684
971335AH1-147 GEN
Solar/Wind Harmer
18.684
274861TOP CROP ;1U
Solar/Wind Harmer
5.622
274862TOP CROP ;2U
Solar/Wind Harmer
4.695
276872AE1-163_GEN1
Solar/Wind Harmer
6.213
971341AH1-150 GEN
Solar/Wind Harmer
18.436
971343AH1-151 GEN
Solar/Wind Harmer
18.436
274856ECOGROVE ;U1
Solar/Wind Harmer
3.052
276611AD2-172 GEN
Solar/Wind Harmer
2.316
938861AE1-114 GEN
Solar/Wind Harmer
7.314
274764LEE CO EC;5U
Adder
8.26
274765LEE CO EC;6U
Adder
8.26
274762LEE CO EC;3U
Adder
8.24
274763LEE CO EC;4U
Adder
8.162
276603SUBLETTE C
Solar/Wind Harmer
0.925
972267AH1-718 GEN
Adder
3.611
276741O09 GEN1
Solar/Wind Harmer
3.062
276708O09 GEN2
Solar/Wind Harmer
3.062
274851PROVIDENC;RU
Solar/Wind Harmer
2.372
274849CRESCENT ;1U
Solar/Wind Harmer
1.54
276645AC1-214 GEN1
Solar/Wind Harmer
1.116
276646AC1-214 GEN2
Solar/Wind Harmer
1.116
276782AC1-033 GEN
Solar/Wind Harmer
3.294
960611AF2-352 GEN
Solar/Wind Harmer
1.674
274808UNIV PK N;4U
Adder
3.415
276763AC1-053 GEN1
Solar/Wind Harmer
2.256
276764AC1-053 GEN2
Solar/Wind Harmer
2.256
276612AE2-035 GEN
Solar/Wind Harmer
2.316
971681AH1-341 GEN
Solar/Wind Harmer
13.383
926823AC1-168 GEN
Solar/Wind Harmer
3.758
961011AF2-392 GEN
Solar/Wind Harmer
9.474
970169AG2-114 GEN
Solar/Wind Harmer
8.537
957751AF2-069 GEN
Solar/Wind Harmer
0.382
946321AF1-296 GEN
Solar/Wind Harmer
8.52
274848CAMPGROVE;RU
Solar/Wind Harmer
5.265
276655WTG1_EQ
Solar/Wind Harmer
6.612
276656WTG2_EQ
Solar/Wind Harmer
0.875
959341AF2-225 GEN
Solar/Wind Harmer
11.36
941731AE2-173 GEN
Solar/Wind Harmer
4.403
274814UNIV PK N;0U
Adder
3.46
274807UNIV PK N;3U
Adder
3.452
274805UNIV PK N;1U
Adder
3.437
274811UNIV PK N;7U
Adder
3.43
276785W4-005 GEN1
Solar/Wind Harmer
1.759
276174W4-005 GEN2
Solar/Wind Harmer
1.759
276849AB2-070 GEN2
Solar/Wind Harmer
1.303
276848AB2-070 GEN3
Solar/Wind Harmer
1.303
972179AH1-673 GEN
50/50
15.343
274723RIVER EC ;12
50/50
28.574
276164X3-005 C
Solar/Wind Harmer
0.97
276776AD2-060 GEN
Solar/Wind Harmer
0.51
972207SS24-0001
Solar/Wind Harmer
25.827
274773LINCOLN ;4U
Adder
7.264
274774LINCOLN ;5U
Adder
7.264
274801UNIV PARK;4U
Adder
6.572
941551AE2-152 GEN
Solar/Wind Harmer
4.819
274674JOLIET 9 ;6U
Adder
16.144
274676JOLIET 29;8U
Adder
31.64
276691AA1-018 GEN1
Solar/Wind Harmer
0.478
274732ELWOOD EC;7P
Adder
16.713
274745AC1-111 GEN9
Adder
5.561
274871GR RIDGE ;2U
Solar/Wind Harmer
7.624
274682WAUKEGAN ;7U
Adder
17.564
274828WAUKEGAN ;BP
Adder
10.768
960751AF2-366 GEN
Solar/Wind Harmer
2.74
962781AG1-127 GEN
Solar/Wind Harmer
9.082
939401AE1-172 GEN
Solar/Wind Harmer
13.283
274872LEEDK;1U
Solar/Wind Harmer
7.808
276901AD2-066 C O1
Solar/Wind Harmer
3.317
276861AD2-134 GEN
Solar/Wind Harmer
1.665
276876AE1-163_GEN2
Solar/Wind Harmer
6.213
971997AH1-543 GEN
Solar/Wind Harmer
14.547
957471AF2-041 GEN
Solar/Wind Harmer
27.654
959081AF2-199 GEN
Solar/Wind Harmer
9.218
971067AG2-660 GEN
Solar/Wind Harmer
2.144
274822ROCKFORD ;11
Adder
18.028
972235AH1-702 GEN1
Adder
2.304
970819AG2-516 GEN
Solar/Wind Harmer
10.901
971475AH1-234 GEN
Solar/Wind Harmer
20.263
274857EASY ROAD;U1
Solar/Wind Harmer
4.244
274761LEE CO EC;2U
Adder
8.24
274766LEE CO EC;7U
Adder
8.143
970569AG2-363 GEN
Solar/Wind Harmer
26.523
276158O29GEN2
Solar/Wind Harmer
4.287
274877BISHOP HL;1U
Solar/Wind Harmer
2.788
276726Z2-087_GEN
Solar/Wind Harmer
5.99
939741AE1-205 GEN
Solar/Wind Harmer
15.146
274854TWINGROVE;U2
Solar/Wind Harmer
5.078
274812UNIV PK N;8U
Adder
3.43
972175AH1-670 GEN
Solar/Wind Harmer
8.832
274880W4-005 GEN4
Solar/Wind Harmer
1.759
963831AG1-236 GEN
Solar/Wind Harmer
5.613
274826FISK ;BP
50/50
14.417
970941AG2-585 GEN
Solar/Wind Harmer
15.092
276772AC2-154 GEN
Solar/Wind Harmer
3.367
276806AD2-047 C O1
Solar/Wind Harmer
12.916
274772LINCOLN ;3U
Adder
7.264
274800UNIV PARK;3U
Adder
6.572
972038AH1-567 GEN2
Adder
0.411
276893AG1-478 C
Solar/Wind Harmer
0.452
276897AD1-100 C
Solar/Wind Harmer
30.838
939351AE1-166 GEN
Solar/Wind Harmer
6.301
274676JOLIET 29;8U
Adder
30.51
276694AA1-018 GEN2
Solar/Wind Harmer
6.483
972228AH1-698 GEN2
Adder
3.782
274729ELWOOD EC;1P
Adder
16.725
274730ELWOOD EC;6P
Adder
16.713
274734ELWOOD EC;8P
Adder
16.713
274736ELWOOD EC;9P
Adder
16.713
970707AG2-453 GEN
Solar/Wind Harmer
28.402
274802UNIV PARK;5U
Adder
5.821
943121AE2-341 GEN
Solar/Wind Harmer
14.912
943591AF1-030 GEN
Solar/Wind Harmer
9.941
276805AD2-038 GEN
Solar/Wind Harmer
5.05
274682WAUKEGAN ;7U
Adder
17.564
274872LEEDK;1U
Solar/Wind Harmer
0.243
276799AD1-013 GEN
Solar/Wind Harmer
2.064
946671AF1-331 GEN
Solar/Wind Harmer
0.391
274855GSG-6 ;RU
Solar/Wind Harmer
3.444
274850MENDOTA H;RU
Solar/Wind Harmer
2.394
276602WESTBROOK C
Solar/Wind Harmer
1.982
276863AD2-134 GEN
Solar/Wind Harmer
1.665
276889AE2-281 GEN
Solar/Wind Harmer
1.775
959091AF2-200 GEN
Solar/Wind Harmer
18.436
972236AH1-702 GEN2
Adder
2.003
274858EASY ROAD;U2
Solar/Wind Harmer
4.244
274760LEE CO EC;1U
Adder
8.24
274767LEE CO EC;8U
Adder
8.143
970571AG2-364 GEN
Solar/Wind Harmer
17.682
276157O29GEN1
Solar/Wind Harmer
3.261
274878BISHOP HL;2U
Solar/Wind Harmer
2.788
965931AG1-462 GEN
Solar/Wind Harmer
20.589
942111AE2-223 GEN
Solar/Wind Harmer
6.208
274853TWINGROVE;U1
Solar/Wind Harmer
5.187
965091AG1-374 GEN
Solar/Wind Harmer
21.59
959611AF2-252 GEN
Solar/Wind Harmer
1.674
274724RIVER EC ;11
Adder
11.405
276686W4-005 GEN3
Solar/Wind Harmer
1.759
971993AH1-541 GEN
Solar/Wind Harmer
5.374
276668AB2-070 GEN1
Solar/Wind Harmer
1.303
990512J1326
External Queue
4.853159427642822
990117J1214
External Queue
11.035313606262207
990727J1377 G
External Queue
5.6371893882751465
991092J1477
External Queue
2.612651824951172
990407J1304
External Queue
3.753084421157837
NYPJM->LTFIMP_NY
CLTF
0.848
WECLTFEXP_WEC->PJM
CLTF
3.498
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.346
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.049
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.172
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.968
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.319
MECLTFEXP_MEC->PJM
CLTF
10.857
SIGELTFEXP_SIGE->PJM
CLTF
0.008
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.431
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.229
LAGNLTFEXP_LAGN->PJM
CLTF
3.51
TVALTFEXP_TVA->PJM
CLTF
0.873

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT7-8___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT7-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.47 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1841.95
MW Contribution:23.26
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
43.598
276612AE2-035 GEN
Solar/Wind Harmer
4.629
971681AH1-341 GEN
Solar/Wind Harmer
21.411
961011AF2-392 GEN
Solar/Wind Harmer
11.886
946321AF1-296 GEN
Solar/Wind Harmer
9.234
971675AH1-338 GEN
Solar/Wind Harmer
14.566
972236AH1-702 GEN2
50/50
5.049
274656BYRON ;1U
50/50
16.311
274858EASY ROAD;U2
Solar/Wind Harmer
7.248
971333AH1-146 GEN
Solar/Wind Harmer
43.356
971335AH1-147 GEN
Solar/Wind Harmer
43.356
274856ECOGROVE ;U1
Solar/Wind Harmer
6.101
276611AD2-172 GEN
Solar/Wind Harmer
4.629
274764LEE CO EC;5U
Adder
14.104
274765LEE CO EC;6U
Adder
14.104
274762LEE CO EC;3U
Adder
14.071
274763LEE CO EC;4U
Adder
13.938
938861AE1-114 GEN
Solar/Wind Harmer
12.173
276603SUBLETTE C
Solar/Wind Harmer
1.211
972267AH1-718 GEN
Adder
4.503
276741O09 GEN1
Solar/Wind Harmer
3.245
276708O09 GEN2
Solar/Wind Harmer
3.245
970921AG2-575 GEN
Solar/Wind Harmer
7.492
970921AG2-575 GEN
Solar/Wind Harmer
1.742
942991AE2-321 GEN
Solar/Wind Harmer
6.762
962691AG1-118 GEN
Solar/Wind Harmer
17.893
971341AH1-150 GEN
Solar/Wind Harmer
10.168
971343AH1-151 GEN
Solar/Wind Harmer
10.168
274657BYRON ;2U
50/50
15.925
972235AH1-702 GEN1
50/50
5.799
972031AH1-564 GEN
50/50
36.781
274824ROCKFORD ;12
50/50
34.076
274822ROCKFORD ;11
50/50
43.914
971475AH1-234 GEN
Solar/Wind Harmer
44.028
970819AG2-516 GEN
Solar/Wind Harmer
23.26
274857EASY ROAD;U1
Solar/Wind Harmer
7.248
274761LEE CO EC;2U
Adder
14.071
274766LEE CO EC;7U
Adder
13.905
276158O29GEN2
Solar/Wind Harmer
4.543
276861AD2-134 GEN
Solar/Wind Harmer
1.453
960751AF2-366 GEN
Solar/Wind Harmer
2.149
962781AG1-127 GEN
Solar/Wind Harmer
7.125
274872LEEDK;1U
Solar/Wind Harmer
5.679
274760LEE CO EC;1U
Adder
14.071
274767LEE CO EC;8U
Adder
13.905
276157O29GEN1
Solar/Wind Harmer
3.455
965931AG1-462 GEN
Solar/Wind Harmer
21.908
274855GSG-6 ;RU
Solar/Wind Harmer
3.005
274850MENDOTA H;RU
Solar/Wind Harmer
2.09
276602WESTBROOK C
Solar/Wind Harmer
1.73
276863AD2-134 GEN
Solar/Wind Harmer
1.453
276799AD1-013 GEN
Solar/Wind Harmer
1.777
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
10.168
957471AF2-041 GEN
Solar/Wind Harmer
15.252
959081AF2-199 GEN
Solar/Wind Harmer
5.084
971067AG2-660 GEN
Solar/Wind Harmer
1.182
971177AH1-047 GEN
Solar/Wind Harmer
4.41
971171AH1-044 GEN
Solar/Wind Harmer
10.168
990512J1326
External Queue
9.444316864013672
990117J1214
External Queue
32.48844909667969
990727J1377 G
External Queue
13.982793807983398
991092J1477
External Queue
2.8638265132904053
991777J1629 G
External Queue
9.207619667053223
990407J1304
External Queue
7.996669292449951
NYPJM->LTFIMP_NY
CLTF
0.236
WECLTFEXP_WEC->PJM
CLTF
0.762
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.21
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.811
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.914
MECLTFEXP_MEC->PJM
CLTF
9.246
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.412
LAGNLTFEXP_LAGN->PJM
CLTF
2.566
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.659

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4_144-45-BT5-8___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_144-45-BT5-8___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.23 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1838.11
MW Contribution:23.03
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
43.098
276612AE2-035 GEN
Solar/Wind Harmer
4.588
971681AH1-341 GEN
Solar/Wind Harmer
21.331
961011AF2-392 GEN
Solar/Wind Harmer
11.925
946321AF1-296 GEN
Solar/Wind Harmer
9.259
971675AH1-338 GEN
Solar/Wind Harmer
14.702
971177AH1-047 GEN
Solar/Wind Harmer
4.205
971171AH1-044 GEN
Solar/Wind Harmer
10.904
274657BYRON ;2U
50/50
15.786
972235AH1-702 GEN1
50/50
5.749
972031AH1-564 GEN
50/50
36.36
274824ROCKFORD ;12
50/50
33.686
274822ROCKFORD ;11
50/50
43.411
971475AH1-234 GEN
Solar/Wind Harmer
43.586
970819AG2-516 GEN
Solar/Wind Harmer
23.028
274857EASY ROAD;U1
Solar/Wind Harmer
7.229
274761LEE CO EC;2U
Adder
14.034
274766LEE CO EC;7U
Adder
13.869
276158O29GEN2
Solar/Wind Harmer
4.561
276861AD2-134 GEN
Solar/Wind Harmer
1.467
960751AF2-366 GEN
Solar/Wind Harmer
2.174
962781AG1-127 GEN
Solar/Wind Harmer
7.206
274872LEEDK;1U
Solar/Wind Harmer
5.758
957471AF2-041 GEN
Solar/Wind Harmer
16.357
959081AF2-199 GEN
Solar/Wind Harmer
5.452
971067AG2-660 GEN
Solar/Wind Harmer
1.268
971333AH1-146 GEN
Solar/Wind Harmer
42.977
971335AH1-147 GEN
Solar/Wind Harmer
42.977
274856ECOGROVE ;U1
Solar/Wind Harmer
6.047
276611AD2-172 GEN
Solar/Wind Harmer
4.588
274764LEE CO EC;5U
Adder
14.067
274765LEE CO EC;6U
Adder
14.067
274762LEE CO EC;3U
Adder
14.034
274763LEE CO EC;4U
Adder
13.902
938861AE1-114 GEN
Solar/Wind Harmer
12.113
276603SUBLETTE C
Solar/Wind Harmer
1.212
972267AH1-718 GEN
Adder
4.528
276741O09 GEN1
Solar/Wind Harmer
3.258
276708O09 GEN2
Solar/Wind Harmer
3.258
970921AG2-575 GEN
Solar/Wind Harmer
7.577
970921AG2-575 GEN
Solar/Wind Harmer
1.762
942991AE2-321 GEN
Solar/Wind Harmer
6.399
962691AG1-118 GEN
Solar/Wind Harmer
18.291
971341AH1-150 GEN
Solar/Wind Harmer
10.904
971343AH1-151 GEN
Solar/Wind Harmer
10.904
972236AH1-702 GEN2
50/50
5.005
274656BYRON ;1U
50/50
16.168
274858EASY ROAD;U2
Solar/Wind Harmer
7.229
274760LEE CO EC;1U
Adder
14.034
274767LEE CO EC;8U
Adder
13.869
276157O29GEN1
Solar/Wind Harmer
3.469
965931AG1-462 GEN
Solar/Wind Harmer
21.979
274855GSG-6 ;RU
Solar/Wind Harmer
3.033
274850MENDOTA H;RU
Solar/Wind Harmer
2.109
276602WESTBROOK C
Solar/Wind Harmer
1.746
276863AD2-134 GEN
Solar/Wind Harmer
1.467
276799AD1-013 GEN
Solar/Wind Harmer
1.794
946671AF1-331 GEN
Solar/Wind Harmer
0.34
274872LEEDK;1U
Solar/Wind Harmer
0.179
959091AF2-200 GEN
Solar/Wind Harmer
10.904
990512J1326
External Queue
9.342920303344727
990117J1214
External Queue
32.139644622802734
990727J1377 G
External Queue
13.837535858154297
991092J1477
External Queue
2.8840813636779785
991777J1629 G
External Queue
9.058588027954102
990407J1304
External Queue
7.907464027404785
NYPJM->LTFIMP_NY
CLTF
0.235
WECLTFEXP_WEC->PJM
CLTF
0.729
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.389
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.907
MECLTFEXP_MEC->PJM
CLTF
9.219
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.411
LAGNLTFEXP_LAGN->PJM
CLTF
2.557
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.656

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4-6_006-345-BT78___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_006-345-BT78___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.49 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1732.54
MW Contribution:24.2
Bus #Bus NameTypeMW Contribution
972236AH1-702 GEN2
50/50
5.659
274656BYRON ;1U
50/50
14.792
274858EASY ROAD;U2
Solar/Wind Harmer
6.648
274760LEE CO EC;1U
Adder
12.907
274767LEE CO EC;8U
Adder
12.755
276157O29GEN1
Solar/Wind Harmer
3.26
965931AG1-462 GEN
Solar/Wind Harmer
20.756
274855GSG-6 ;RU
Solar/Wind Harmer
2.973
274850MENDOTA H;RU
Solar/Wind Harmer
2.067
276602WESTBROOK C
Solar/Wind Harmer
1.711
276863AD2-134 GEN
Solar/Wind Harmer
1.438
276799AD1-013 GEN
Solar/Wind Harmer
1.759
946671AF1-331 GEN
Solar/Wind Harmer
0.333
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
9.367
274657BYRON ;2U
50/50
17.85
972031AH1-564 GEN
50/50
37.916
274824ROCKFORD ;12
50/50
35.129
274822ROCKFORD ;11
50/50
45.271
972235AH1-702 GEN1
50/50
5.259
971475AH1-234 GEN
Solar/Wind Harmer
46.897
970819AG2-516 GEN
Solar/Wind Harmer
24.195
274857EASY ROAD;U1
Solar/Wind Harmer
6.648
274761LEE CO EC;2U
Adder
12.907
274766LEE CO EC;7U
Adder
12.755
276158O29GEN2
Solar/Wind Harmer
4.286
276861AD2-134 GEN
Solar/Wind Harmer
1.438
960751AF2-366 GEN
Solar/Wind Harmer
2.176
962781AG1-127 GEN
Solar/Wind Harmer
7.214
274872LEEDK;1U
Solar/Wind Harmer
5.696
957471AF2-041 GEN
Solar/Wind Harmer
14.05
959081AF2-199 GEN
Solar/Wind Harmer
4.683
971067AG2-660 GEN
Solar/Wind Harmer
1.089
274823ROCKFORD ;21
50/50
44.943
276612AE2-035 GEN
Solar/Wind Harmer
4.752
971681AH1-341 GEN
Solar/Wind Harmer
21.179
961011AF2-392 GEN
Solar/Wind Harmer
11.275
946321AF1-296 GEN
Solar/Wind Harmer
8.796
971675AH1-338 GEN
Solar/Wind Harmer
14.414
971177AH1-047 GEN
Solar/Wind Harmer
4.62
971171AH1-044 GEN
Solar/Wind Harmer
9.367
274856ECOGROVE ;U1
Solar/Wind Harmer
6.263
276611AD2-172 GEN
Solar/Wind Harmer
4.752
938861AE1-114 GEN
Solar/Wind Harmer
12.204
274764LEE CO EC;5U
Adder
12.937
274765LEE CO EC;6U
Adder
12.937
274762LEE CO EC;3U
Adder
12.907
274763LEE CO EC;4U
Adder
12.785
276603SUBLETTE C
Solar/Wind Harmer
1.169
972267AH1-718 GEN
Adder
4.193
276741O09 GEN1
Solar/Wind Harmer
3.061
276708O09 GEN2
Solar/Wind Harmer
3.061
970921AG2-575 GEN
Solar/Wind Harmer
7.585
970921AG2-575 GEN
Solar/Wind Harmer
1.764
942991AE2-321 GEN
Solar/Wind Harmer
7.135
962691AG1-118 GEN
Solar/Wind Harmer
18.087
971341AH1-150 GEN
Solar/Wind Harmer
9.367
971343AH1-151 GEN
Solar/Wind Harmer
9.367
990512J1326
External Queue
10.086955070495605
990117J1214
External Queue
34.69912338256836
990727J1377 G
External Queue
14.958372116088867
991092J1477
External Queue
2.650393486022949
991777J1629 G
External Queue
9.956707000732422
990407J1304
External Queue
8.578377723693848
NYPJM->LTFIMP_NY
CLTF
0.233
WECLTFEXP_WEC->PJM
CLTF
0.873
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.943
CBM West 1LTFEXP_CBM-W1->PJM
CBM
46.123
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.877
MECLTFEXP_MEC->PJM
CLTF
9.145
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.41
LAGNLTFEXP_LAGN->PJM
CLTF
2.531
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.17
TVALTFEXP_TVA->PJM
CLTF
0.647

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345B__1_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.67 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1641.15
MW Contribution:19.52
Bus #Bus NameTypeMW Contribution
972031AH1-564 GEN
50/50
31.109
274824ROCKFORD ;12
50/50
28.82
274822ROCKFORD ;11
50/50
37.14
274657BYRON ;2U
50/50
12.007
972235AH1-702 GEN1
50/50
4.364
970819AG2-516 GEN
Solar/Wind Harmer
19.524
971475AH1-234 GEN
Solar/Wind Harmer
35.705
274857EASY ROAD;U1
Solar/Wind Harmer
6.261
274761LEE CO EC;2U
Adder
12.155
274766LEE CO EC;7U
Adder
12.012
957471AF2-041 GEN
Solar/Wind Harmer
32.763
959081AF2-199 GEN
Solar/Wind Harmer
10.921
971067AG2-660 GEN
Solar/Wind Harmer
2.54
276158O29GEN2
Solar/Wind Harmer
4.501
276861AD2-134 GEN
Solar/Wind Harmer
1.33
960751AF2-366 GEN
Solar/Wind Harmer
1.883
962781AG1-127 GEN
Solar/Wind Harmer
6.242
274872LEEDK;1U
Solar/Wind Harmer
5.07
274856ECOGROVE ;U1
Solar/Wind Harmer
5.234
276611AD2-172 GEN
Solar/Wind Harmer
3.971
938861AE1-114 GEN
Solar/Wind Harmer
10.904
274764LEE CO EC;5U
Adder
12.183
274765LEE CO EC;6U
Adder
12.183
274762LEE CO EC;3U
Adder
12.155
274763LEE CO EC;4U
Adder
12.04
276603SUBLETTE C
Solar/Wind Harmer
1.154
972267AH1-718 GEN
Adder
4.55
971341AH1-150 GEN
Solar/Wind Harmer
21.842
971343AH1-151 GEN
Solar/Wind Harmer
21.842
971333AH1-146 GEN
Solar/Wind Harmer
20.489
971335AH1-147 GEN
Solar/Wind Harmer
20.489
276741O09 GEN1
Solar/Wind Harmer
3.215
276708O09 GEN2
Solar/Wind Harmer
3.215
970921AG2-575 GEN
Solar/Wind Harmer
6.564
970921AG2-575 GEN
Solar/Wind Harmer
1.527
962691AG1-118 GEN
Solar/Wind Harmer
15.751
942991AE2-321 GEN
Solar/Wind Harmer
5.127
274823ROCKFORD ;21
50/50
36.874
276612AE2-035 GEN
Solar/Wind Harmer
3.971
971681AH1-341 GEN
Solar/Wind Harmer
19.548
971171AH1-044 GEN
Solar/Wind Harmer
21.842
961011AF2-392 GEN
Solar/Wind Harmer
11.668
946321AF1-296 GEN
Solar/Wind Harmer
9.025
971675AH1-338 GEN
Solar/Wind Harmer
13.322
971177AH1-047 GEN
Solar/Wind Harmer
3.423
972236AH1-702 GEN2
50/50
3.807
274656BYRON ;1U
50/50
12.275
274858EASY ROAD;U2
Solar/Wind Harmer
6.261
274760LEE CO EC;1U
Adder
12.155
274767LEE CO EC;8U
Adder
12.012
959091AF2-200 GEN
Solar/Wind Harmer
21.842
276157O29GEN1
Solar/Wind Harmer
3.423
965931AG1-462 GEN
Solar/Wind Harmer
21.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.751
274850MENDOTA H;RU
Solar/Wind Harmer
1.913
276602WESTBROOK C
Solar/Wind Harmer
1.583
276863AD2-134 GEN
Solar/Wind Harmer
1.33
276799AD1-013 GEN
Solar/Wind Harmer
1.623
946671AF1-331 GEN
Solar/Wind Harmer
0.307
274872LEEDK;1U
Solar/Wind Harmer
0.158
990512J1326
External Queue
7.586848735809326
990117J1214
External Queue
26.098758697509766
990727J1377 G
External Queue
11.226364135742188
991092J1477
External Queue
2.9171924591064453
990407J1304
External Queue
6.372202396392822
NYPJM->LTFIMP_NY
CLTF
0.196
WECLTFEXP_WEC->PJM
CLTF
0.471
CPLELTFEXP_CPLE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.803
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.918
MECLTFEXP_MEC->PJM
CLTF
8.533
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.301
LAGNLTFEXP_LAGN->PJM
CLTF
2.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
TVALTFEXP_TVA->PJM
CLTF
0.648

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4_111-45-TR81____SRT-A


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-TR81____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.66 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1641.05
MW Contribution:19.52
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
36.874
276612AE2-035 GEN
Solar/Wind Harmer
3.971
971681AH1-341 GEN
Solar/Wind Harmer
19.548
971171AH1-044 GEN
Solar/Wind Harmer
21.842
961011AF2-392 GEN
Solar/Wind Harmer
11.668
274856ECOGROVE ;U1
Solar/Wind Harmer
5.234
276611AD2-172 GEN
Solar/Wind Harmer
3.971
938861AE1-114 GEN
Solar/Wind Harmer
10.904
274764LEE CO EC;5U
Adder
12.183
274765LEE CO EC;6U
Adder
12.183
274762LEE CO EC;3U
Adder
12.155
274763LEE CO EC;4U
Adder
12.04
276603SUBLETTE C
Solar/Wind Harmer
1.154
972267AH1-718 GEN
Adder
4.55
971341AH1-150 GEN
Solar/Wind Harmer
21.842
971343AH1-151 GEN
Solar/Wind Harmer
21.842
972236AH1-702 GEN2
50/50
3.807
274656BYRON ;1U
50/50
12.275
274858EASY ROAD;U2
Solar/Wind Harmer
6.261
274760LEE CO EC;1U
Adder
12.155
274767LEE CO EC;8U
Adder
12.012
959091AF2-200 GEN
Solar/Wind Harmer
21.842
276157O29GEN1
Solar/Wind Harmer
3.423
965931AG1-462 GEN
Solar/Wind Harmer
21.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.751
274850MENDOTA H;RU
Solar/Wind Harmer
1.913
276602WESTBROOK C
Solar/Wind Harmer
1.583
276863AD2-134 GEN
Solar/Wind Harmer
1.33
276799AD1-013 GEN
Solar/Wind Harmer
1.623
946671AF1-331 GEN
Solar/Wind Harmer
0.307
274872LEEDK;1U
Solar/Wind Harmer
0.158
971333AH1-146 GEN
Solar/Wind Harmer
20.489
971335AH1-147 GEN
Solar/Wind Harmer
20.489
276741O09 GEN1
Solar/Wind Harmer
3.215
276708O09 GEN2
Solar/Wind Harmer
3.215
970921AG2-575 GEN
Solar/Wind Harmer
6.564
970921AG2-575 GEN
Solar/Wind Harmer
1.527
962691AG1-118 GEN
Solar/Wind Harmer
15.751
942991AE2-321 GEN
Solar/Wind Harmer
5.127
972031AH1-564 GEN
50/50
31.109
274824ROCKFORD ;12
50/50
28.82
274822ROCKFORD ;11
50/50
37.14
274657BYRON ;2U
50/50
12.007
972235AH1-702 GEN1
50/50
4.364
970819AG2-516 GEN
Solar/Wind Harmer
19.524
971475AH1-234 GEN
Solar/Wind Harmer
35.705
274857EASY ROAD;U1
Solar/Wind Harmer
6.261
274761LEE CO EC;2U
Adder
12.155
274766LEE CO EC;7U
Adder
12.012
957471AF2-041 GEN
Solar/Wind Harmer
32.763
959081AF2-199 GEN
Solar/Wind Harmer
10.921
971067AG2-660 GEN
Solar/Wind Harmer
2.54
276158O29GEN2
Solar/Wind Harmer
4.501
276861AD2-134 GEN
Solar/Wind Harmer
1.33
960751AF2-366 GEN
Solar/Wind Harmer
1.883
962781AG1-127 GEN
Solar/Wind Harmer
6.242
274872LEEDK;1U
Solar/Wind Harmer
5.07
946321AF1-296 GEN
Solar/Wind Harmer
9.025
971675AH1-338 GEN
Solar/Wind Harmer
13.322
971177AH1-047 GEN
Solar/Wind Harmer
3.423
990512J1326
External Queue
7.586848735809326
990117J1214
External Queue
26.098758697509766
990727J1377 G
External Queue
11.226364135742188
991092J1477
External Queue
2.9171924591064453
990407J1304
External Queue
6.372202396392822
NYPJM->LTFIMP_NY
CLTF
0.196
WECLTFEXP_WEC->PJM
CLTF
0.471
CPLELTFEXP_CPLE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.803
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.918
MECLTFEXP_MEC->PJM
CLTF
8.533
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.301
LAGNLTFEXP_LAGN->PJM
CLTF
2.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
TVALTFEXP_TVA->PJM
CLTF
0.648

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P4_111-45-L11124__SRT-A


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_111-45-L11124__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.66 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1641.05
MW Contribution:19.52
Bus #Bus NameTypeMW Contribution
972031AH1-564 GEN
50/50
31.109
274824ROCKFORD ;12
50/50
28.82
274822ROCKFORD ;11
50/50
37.14
274657BYRON ;2U
50/50
12.007
972235AH1-702 GEN1
50/50
4.364
970819AG2-516 GEN
Solar/Wind Harmer
19.524
971475AH1-234 GEN
Solar/Wind Harmer
35.705
274857EASY ROAD;U1
Solar/Wind Harmer
6.261
274761LEE CO EC;2U
Adder
12.155
274766LEE CO EC;7U
Adder
12.012
957471AF2-041 GEN
Solar/Wind Harmer
32.763
959081AF2-199 GEN
Solar/Wind Harmer
10.921
971067AG2-660 GEN
Solar/Wind Harmer
2.54
276158O29GEN2
Solar/Wind Harmer
4.501
276861AD2-134 GEN
Solar/Wind Harmer
1.33
960751AF2-366 GEN
Solar/Wind Harmer
1.883
962781AG1-127 GEN
Solar/Wind Harmer
6.242
274872LEEDK;1U
Solar/Wind Harmer
5.07
274856ECOGROVE ;U1
Solar/Wind Harmer
5.234
276611AD2-172 GEN
Solar/Wind Harmer
3.971
938861AE1-114 GEN
Solar/Wind Harmer
10.904
274764LEE CO EC;5U
Adder
12.183
274765LEE CO EC;6U
Adder
12.183
274762LEE CO EC;3U
Adder
12.155
274763LEE CO EC;4U
Adder
12.04
276603SUBLETTE C
Solar/Wind Harmer
1.154
972267AH1-718 GEN
Adder
4.55
971341AH1-150 GEN
Solar/Wind Harmer
21.842
971343AH1-151 GEN
Solar/Wind Harmer
21.842
971333AH1-146 GEN
Solar/Wind Harmer
20.489
971335AH1-147 GEN
Solar/Wind Harmer
20.489
276741O09 GEN1
Solar/Wind Harmer
3.215
276708O09 GEN2
Solar/Wind Harmer
3.215
970921AG2-575 GEN
Solar/Wind Harmer
6.564
970921AG2-575 GEN
Solar/Wind Harmer
1.527
962691AG1-118 GEN
Solar/Wind Harmer
15.751
942991AE2-321 GEN
Solar/Wind Harmer
5.127
274823ROCKFORD ;21
50/50
36.874
276612AE2-035 GEN
Solar/Wind Harmer
3.971
971681AH1-341 GEN
Solar/Wind Harmer
19.548
971171AH1-044 GEN
Solar/Wind Harmer
21.842
961011AF2-392 GEN
Solar/Wind Harmer
11.668
946321AF1-296 GEN
Solar/Wind Harmer
9.025
971675AH1-338 GEN
Solar/Wind Harmer
13.322
971177AH1-047 GEN
Solar/Wind Harmer
3.423
972236AH1-702 GEN2
50/50
3.807
274656BYRON ;1U
50/50
12.275
274858EASY ROAD;U2
Solar/Wind Harmer
6.261
274760LEE CO EC;1U
Adder
12.155
274767LEE CO EC;8U
Adder
12.012
959091AF2-200 GEN
Solar/Wind Harmer
21.842
276157O29GEN1
Solar/Wind Harmer
3.423
965931AG1-462 GEN
Solar/Wind Harmer
21.597
274855GSG-6 ;RU
Solar/Wind Harmer
2.751
274850MENDOTA H;RU
Solar/Wind Harmer
1.913
276602WESTBROOK C
Solar/Wind Harmer
1.583
276863AD2-134 GEN
Solar/Wind Harmer
1.33
276799AD1-013 GEN
Solar/Wind Harmer
1.623
946671AF1-331 GEN
Solar/Wind Harmer
0.307
274872LEEDK;1U
Solar/Wind Harmer
0.158
990512J1326
External Queue
7.586848735809326
990117J1214
External Queue
26.098758697509766
990727J1377 G
External Queue
11.226364135742188
991092J1477
External Queue
2.9171924591064453
990407J1304
External Queue
6.372202396392822
NYPJM->LTFIMP_NY
CLTF
0.196
WECLTFEXP_WEC->PJM
CLTF
0.471
CPLELTFEXP_CPLE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
12.803
CBM West 1LTFEXP_CBM-W1->PJM
CBM
38.5
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.918
MECLTFEXP_MEC->PJM
CLTF
8.533
SIGELTFEXP_SIGE->PJM
CLTF
0.004
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.301
LAGNLTFEXP_LAGN->PJM
CLTF
2.437
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.275
TVALTFEXP_TVA->PJM
CLTF
0.648

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L92805__B-R_SRT-A-2


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L92805__B-R_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.46 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1638.0
MW Contribution:16.21
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
43.543
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
16.017
961011AF2-392 GEN
Solar/Wind Harmer
4.469
946321AF1-296 GEN
Solar/Wind Harmer
3.454
971675AH1-338 GEN
Solar/Wind Harmer
2.199
971177AH1-047 GEN
Solar/Wind Harmer
3.216
971171AH1-044 GEN
Solar/Wind Harmer
7.105
274657BYRON ;2U
50/50
15.91
972235AH1-702 GEN1
50/50
5.794
972031AH1-564 GEN
50/50
36.735
274824ROCKFORD ;12
50/50
34.034
274822ROCKFORD ;11
50/50
43.859
971475AH1-234 GEN
Solar/Wind Harmer
6.647
970819AG2-516 GEN
Solar/Wind Harmer
16.208
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
14.059
274766LEE CO EC;7U
Adder
13.893
971333AH1-146 GEN
Solar/Wind Harmer
30.22
971335AH1-147 GEN
Solar/Wind Harmer
30.22
274856ECOGROVE ;U1
Solar/Wind Harmer
0.297
276611AD2-172 GEN
Solar/Wind Harmer
0.003
274764LEE CO EC;5U
Adder
14.092
274765LEE CO EC;6U
Adder
14.092
274762LEE CO EC;3U
Adder
14.059
274763LEE CO EC;4U
Adder
13.926
938861AE1-114 GEN
Solar/Wind Harmer
5.864
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.5
276741O09 GEN1
Solar/Wind Harmer
0.225
276708O09 GEN2
Solar/Wind Harmer
0.225
970921AG2-575 GEN
Solar/Wind Harmer
5.22
970921AG2-575 GEN
Solar/Wind Harmer
1.74
942991AE2-321 GEN
Solar/Wind Harmer
5.226
962691AG1-118 GEN
Solar/Wind Harmer
12.465
971341AH1-150 GEN
Solar/Wind Harmer
7.105
971343AH1-151 GEN
Solar/Wind Harmer
7.105
276158O29GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.102
962781AG1-127 GEN
Solar/Wind Harmer
4.968
274872LEEDK;1U
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
10.658
959081AF2-199 GEN
Solar/Wind Harmer
3.553
971067AG2-660 GEN
Solar/Wind Harmer
1.184
972236AH1-702 GEN2
50/50
5.044
274656BYRON ;1U
50/50
16.295
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
14.059
274767LEE CO EC;8U
Adder
13.893
276157O29GEN1
Solar/Wind Harmer
1.023
965931AG1-462 GEN
Solar/Wind Harmer
15.268
274855GSG-6 ;RU
Solar/Wind Harmer
0.208
274850MENDOTA H;RU
Solar/Wind Harmer
0.067
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.102
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
7.105
990512J1326
External Queue
9.427095413208008
990117J1214
External Queue
32.42920684814453
990727J1377 G
External Queue
13.966062545776367
991092J1477
External Queue
2.8649470806121826
991777J1629 G
External Queue
9.148280143737793
990407J1304
External Queue
7.983032703399658
NYPJM->LTFIMP_NY
CLTF
0.236
WECLTFEXP_WEC->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.911
MECLTFEXP_MEC->PJM
CLTF
9.223
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.411
LAGNLTFEXP_LAGN->PJM
CLTF
2.56
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.657

Details for CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line l/o COMED_P1-2_345-L0626__B-R_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line
Contingency Name:
COMED_P1-2_345-L0626__B-R_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.61 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1577.49
MW Contribution:16.21
Bus #Bus NameTypeMW Contribution
274823ROCKFORD ;21
50/50
43.543
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
16.017
961011AF2-392 GEN
Solar/Wind Harmer
4.469
946321AF1-296 GEN
Solar/Wind Harmer
3.454
971675AH1-338 GEN
Solar/Wind Harmer
2.199
971177AH1-047 GEN
Solar/Wind Harmer
3.216
971171AH1-044 GEN
Solar/Wind Harmer
7.105
274657BYRON ;2U
50/50
15.91
972235AH1-702 GEN1
50/50
5.794
972031AH1-564 GEN
50/50
36.735
274824ROCKFORD ;12
50/50
34.034
274822ROCKFORD ;11
50/50
43.859
971475AH1-234 GEN
Solar/Wind Harmer
6.647
970819AG2-516 GEN
Solar/Wind Harmer
16.208
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
14.059
274766LEE CO EC;7U
Adder
13.893
276158O29GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.102
962781AG1-127 GEN
Solar/Wind Harmer
4.968
274872LEEDK;1U
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
10.658
959081AF2-199 GEN
Solar/Wind Harmer
3.553
971067AG2-660 GEN
Solar/Wind Harmer
1.184
274856ECOGROVE ;U1
Solar/Wind Harmer
0.297
276611AD2-172 GEN
Solar/Wind Harmer
0.003
274764LEE CO EC;5U
Adder
14.092
274765LEE CO EC;6U
Adder
14.092
274762LEE CO EC;3U
Adder
14.059
274763LEE CO EC;4U
Adder
13.926
938861AE1-114 GEN
Solar/Wind Harmer
5.864
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
4.5
276741O09 GEN1
Solar/Wind Harmer
0.225
276708O09 GEN2
Solar/Wind Harmer
0.225
970921AG2-575 GEN
Solar/Wind Harmer
5.22
970921AG2-575 GEN
Solar/Wind Harmer
1.74
942991AE2-321 GEN
Solar/Wind Harmer
5.226
962691AG1-118 GEN
Solar/Wind Harmer
12.465
971341AH1-150 GEN
Solar/Wind Harmer
7.105
971343AH1-151 GEN
Solar/Wind Harmer
7.105
972236AH1-702 GEN2
50/50
5.044
274656BYRON ;1U
50/50
16.295
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
14.059
274767LEE CO EC;8U
Adder
13.893
276157O29GEN1
Solar/Wind Harmer
1.023
965931AG1-462 GEN
Solar/Wind Harmer
15.268
274855GSG-6 ;RU
Solar/Wind Harmer
0.208
274850MENDOTA H;RU
Solar/Wind Harmer
0.067
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.102
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.597
274872LEEDK;1U
Solar/Wind Harmer
0.177
959091AF2-200 GEN
Solar/Wind Harmer
7.105
990512J1326
External Queue
9.427095413208008
990117J1214
External Queue
32.42920684814453
990727J1377 G
External Queue
13.966062545776367
991092J1477
External Queue
2.8649470806121826
991777J1629 G
External Queue
9.148280143737793
990407J1304
External Queue
7.983032703399658
NYPJM->LTFIMP_NY
CLTF
0.236
WECLTFEXP_WEC->PJM
CLTF
0.74
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.183
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.565
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.911
MECLTFEXP_MEC->PJM
CLTF
9.223
SIGELTFEXP_SIGE->PJM
CLTF
0.002
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.411
LAGNLTFEXP_LAGN->PJM
CLTF
2.56
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.176
TVALTFEXP_TVA->PJM
CLTF
0.657

Details for COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line l/o COMED_P4_167-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_167-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.09 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1646.66
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
274710KENDALL ;4C
50/50
2.08
274658DRESDEN ;2U
50/50
5.065
971997AH1-543 GEN
Solar/Wind Harmer
18.31
274732ELWOOD EC;7P
Adder
15.457
274745AC1-111 GEN9
Adder
5.026
274676JOLIET 29;8U
Adder
27.464
274674JOLIET 9 ;6U
Adder
13.181
274682WAUKEGAN ;7U
Adder
15.339
274828WAUKEGAN ;BP
Adder
9.406
960751AF2-366 GEN
Solar/Wind Harmer
2.355
962781AG1-127 GEN
Solar/Wind Harmer
7.807
274872LEEDK;1U
Solar/Wind Harmer
6.709
274822ROCKFORD ;11
Adder
15.855
972235AH1-702 GEN1
Adder
2.029
276861AD2-134 GEN
Solar/Wind Harmer
1.438
957471AF2-041 GEN
Solar/Wind Harmer
23.979
959081AF2-199 GEN
Solar/Wind Harmer
7.993
971067AG2-660 GEN
Solar/Wind Harmer
1.859
970819AG2-516 GEN
Solar/Wind Harmer
9.586
971475AH1-234 GEN
Solar/Wind Harmer
17.833
276901AD2-066 C O1
Solar/Wind Harmer
2.796
970569AG2-363 GEN
Solar/Wind Harmer
23.754
274857EASY ROAD;U1
Solar/Wind Harmer
3.731
274761LEE CO EC;2U
Adder
7.243
274766LEE CO EC;7U
Adder
7.157
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
276158O29GEN2
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.346
274877BISHOP HL;1U
Solar/Wind Harmer
2.449
274871GR RIDGE ;2U
Solar/Wind Harmer
5.502
274801UNIV PARK;4U
Adder
3.636
276726Z2-087_GEN
Solar/Wind Harmer
4.928
939741AE1-205 GEN
Solar/Wind Harmer
12.461
274854TWINGROVE;U2
Solar/Wind Harmer
4.184
972175AH1-670 GEN
Solar/Wind Harmer
7.374
274812UNIV PK N;8U
Adder
2.701
276776AD2-060 GEN
Solar/Wind Harmer
0.223
274880W4-005 GEN4
Solar/Wind Harmer
1.49
939401AE1-172 GEN
Solar/Wind Harmer
6.817
963831AG1-236 GEN
Solar/Wind Harmer
4.789
276615X2-022 GEN
Solar/Wind Harmer
0.927
276164X3-005 C
Solar/Wind Harmer
0.323
274751CRETE EC ;1U
Adder
2.11
274754CRETE EC ;4U
Adder
2.11
274708KENDALL ;3C
50/50
2.096
274837EQUISTAR ; B
50/50
0.347
274837EQUISTAR ; B
50/50
0.347
276640AD2-194 GEN1
50/50
3.701
276642AD2-194 GEN2
50/50
3.686
274731ELWOOD EC;2P
Adder
15.517
274733ELWOOD EC;3P
Adder
15.517
274735ELWOOD EC;4P
Adder
15.517
274728ELWOOD EC;5P
Adder
15.457
274746AC1-111 G10
Adder
5.026
274744AC1-111 GEN8
Adder
5.026
274675JOLIET 29;7U
Adder
27.494
274675JOLIET 29;7U
Adder
26.512
971177AH1-047 GEN
Solar/Wind Harmer
4.871
276868AE1-113 GEN
Solar/Wind Harmer
8.371
276882AE2-255 GEN
Solar/Wind Harmer
2.791
971411AH1-196 GEN
Solar/Wind Harmer
12.376
970833AG2-524 GEN
Solar/Wind Harmer
7.076
970833AG2-524 GEN
Solar/Wind Harmer
3.291
970169AG2-114 GEN
Solar/Wind Harmer
8.085
274823ROCKFORD ;21
Adder
15.74
971675AH1-338 GEN
Solar/Wind Harmer
14.497
971171AH1-044 GEN
Solar/Wind Harmer
15.986
276612AE2-035 GEN
Solar/Wind Harmer
2.035
971681AH1-341 GEN
Solar/Wind Harmer
11.731
274687WILL CNTY;4U
Adder
21.473
274687WILL CNTY;4U
Adder
21.473
961011AF2-392 GEN
Solar/Wind Harmer
8.308
957751AF2-069 GEN
Solar/Wind Harmer
0.332
926823AC1-168 GEN
Solar/Wind Harmer
3.107
274848CAMPGROVE;RU
Solar/Wind Harmer
4.656
946321AF1-296 GEN
Solar/Wind Harmer
7.516
274827FISK ;RP
Adder
4.898
276655WTG1_EQ
Solar/Wind Harmer
5.44
276656WTG2_EQ
Solar/Wind Harmer
0.72
959341AF2-225 GEN
Solar/Wind Harmer
9.346
941731AE2-173 GEN
Solar/Wind Harmer
3.622
972037AH1-567 GEN1
Adder
0.111
274863CRW1-WTG
Solar/Wind Harmer
3.099
274864CRW2-WTG
Solar/Wind Harmer
3.099
274814UNIV PK N;0U
Adder
2.724
274807UNIV PK N;3U
Adder
2.718
274805UNIV PK N;1U
Adder
2.707
274811UNIV PK N;7U
Adder
2.701
960591AF2-350 GEN
Solar/Wind Harmer
5.266
972227AH1-698 GEN1
Adder
1.357
276849AB2-070 GEN2
Solar/Wind Harmer
1.109
276848AB2-070 GEN3
Solar/Wind Harmer
1.109
276785W4-005 GEN1
Solar/Wind Harmer
1.49
276174W4-005 GEN2
Solar/Wind Harmer
1.49
274709KENDALL ;3S
50/50
1.389
274711KENDALL ;4S
50/50
1.389
276660THREERVRS;U2
50/50
3.446
274695ROCKY RD ;2P
Adder
9.606
274693ROCKY RD ;1P
Adder
9.512
274697ROCKY RD ;3P
Adder
2.61
274696ROCKY RD ;4P
Adder
9.832
274674JOLIET 9 ;6U
Adder
13.181
274683WAUKEGAN ;8U
Adder
17.944
274683WAUKEGAN ;8U
Adder
15.126
942991AE2-321 GEN
Solar/Wind Harmer
8.324
274879MINONK ;1U
Solar/Wind Harmer
5.581
971573AH1-285 GEN
Solar/Wind Harmer
7.112
971333AH1-146 GEN
Solar/Wind Harmer
16.508
971335AH1-147 GEN
Solar/Wind Harmer
16.508
962691AG1-118 GEN
Solar/Wind Harmer
24.725
970921AG2-575 GEN
Solar/Wind Harmer
8.21
970921AG2-575 GEN
Solar/Wind Harmer
1.909
971341AH1-150 GEN
Solar/Wind Harmer
15.986
971343AH1-151 GEN
Solar/Wind Harmer
15.986
274856ECOGROVE ;U1
Solar/Wind Harmer
2.682
276611AD2-172 GEN
Solar/Wind Harmer
2.035
938861AE1-114 GEN
Solar/Wind Harmer
6.417
274764LEE CO EC;5U
Adder
7.26
274765LEE CO EC;6U
Adder
7.26
274762LEE CO EC;3U
Adder
7.243
274763LEE CO EC;4U
Adder
7.174
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276603SUBLETTE C
Solar/Wind Harmer
0.81
972267AH1-718 GEN
Adder
3.169
958491AF2-143 GEN
Solar/Wind Harmer
11.361
276741O09 GEN1
Solar/Wind Harmer
2.688
276708O09 GEN2
Solar/Wind Harmer
2.688
958481AF2-142 GEN
Solar/Wind Harmer
11.14
276782AC1-033 GEN
Solar/Wind Harmer
2.894
274851PROVIDENC;RU
Solar/Wind Harmer
2.061
274849CRESCENT ;1U
Solar/Wind Harmer
1.338
276645AC1-214 GEN1
Solar/Wind Harmer
0.969
276646AC1-214 GEN2
Solar/Wind Harmer
0.969
274861TOP CROP ;1U
Solar/Wind Harmer
4.37
274862TOP CROP ;2U
Solar/Wind Harmer
3.649
274847GR RIDGE ;BU
Solar/Wind Harmer
3.619
972259AH1-714 GEN
Adder
12.185
274803UNIV PARK;6U
Adder
3.539
960611AF2-352 GEN
Solar/Wind Harmer
1.379
274808UNIV PK N;4U
Adder
2.689
274888KELLY CRK;1U
Solar/Wind Harmer
3.109
274887GEN-1.85
Solar/Wind Harmer
2.807
276843GEN-1.7
Solar/Wind Harmer
0.302
958011AF2-095 GEN
Solar/Wind Harmer
7.583
276763AC1-053 GEN1
Solar/Wind Harmer
1.925
276764AC1-053 GEN2
Solar/Wind Harmer
1.925
957381AF2-032 GEN
Solar/Wind Harmer
0.181
274659DRESDEN ;3U
50/50
8.379
276658THREERVRS;U1
50/50
5.69
274729ELWOOD EC;1P
Adder
15.517
274730ELWOOD EC;6P
Adder
15.457
274734ELWOOD EC;8P
Adder
15.457
274736ELWOOD EC;9P
Adder
15.457
274676JOLIET 29;8U
Adder
26.484
274682WAUKEGAN ;7U
Adder
15.339
943121AE2-341 GEN
Solar/Wind Harmer
12.437
943591AF1-030 GEN
Solar/Wind Harmer
8.291
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
1.782
946671AF1-331 GEN
Solar/Wind Harmer
0.337
972236AH1-702 GEN2
Adder
1.764
274855GSG-6 ;RU
Solar/Wind Harmer
2.973
274850MENDOTA H;RU
Solar/Wind Harmer
2.067
276602WESTBROOK C
Solar/Wind Harmer
1.711
276863AD2-134 GEN
Solar/Wind Harmer
1.438
959091AF2-200 GEN
Solar/Wind Harmer
15.986
970571AG2-364 GEN
Solar/Wind Harmer
15.836
274858EASY ROAD;U2
Solar/Wind Harmer
3.731
274760LEE CO EC;1U
Adder
7.243
274767LEE CO EC;8U
Adder
7.157
276889AE2-281 GEN
Solar/Wind Harmer
1.493
276805AD2-038 GEN
Solar/Wind Harmer
3.885
276157O29GEN1
Solar/Wind Harmer
2.862
276694AA1-018 GEN2
Solar/Wind Harmer
4.687
970707AG2-453 GEN
Solar/Wind Harmer
20.558
276893AG1-478 C
Solar/Wind Harmer
0.306
274878BISHOP HL;2U
Solar/Wind Harmer
2.449
965931AG1-462 GEN
Solar/Wind Harmer
18.196
274826FISK ;BP
Adder
6.912
274800UNIV PARK;3U
Adder
3.636
972038AH1-567 GEN2
Adder
0.228
942111AE2-223 GEN
Solar/Wind Harmer
5.107
274802UNIV PARK;5U
Adder
3.539
274853TWINGROVE;U1
Solar/Wind Harmer
4.273
965091AG1-374 GEN
Solar/Wind Harmer
17.788
959611AF2-252 GEN
Solar/Wind Harmer
1.379
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276806AD2-047 C O1
Solar/Wind Harmer
5.633
970941AG2-585 GEN
Solar/Wind Harmer
6.582
972228AH1-698 GEN2
Adder
1.932
276668AB2-070 GEN1
Solar/Wind Harmer
1.109
276686W4-005 GEN3
Solar/Wind Harmer
1.49
971993AH1-541 GEN
Solar/Wind Harmer
4.553
276621W2-048 GEN
Solar/Wind Harmer
2.953
276838X2-022 GEN2
Solar/Wind Harmer
0.11
972231SS25-0005
Solar/Wind Harmer
4.097
972181SS23-001
Solar/Wind Harmer
2.56
274752CRETE EC ;2U
Adder
2.11
274753CRETE EC ;3U
Adder
2.11
990512J1326
External Queue
4.053475379943848
990117J1214
External Queue
13.943954467773438
990727J1377 G
External Queue
4.715986728668213
991777J1629 G
External Queue
9.171701431274414
990407J1304
External Queue
3.1380622386932373
NYPJM->LTFIMP_NY
CLTF
0.755
WECLTFEXP_WEC->PJM
CLTF
3.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.795
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.318
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.129
MECLTFEXP_MEC->PJM
CLTF
9.633
SIGELTFEXP_SIGE->PJM
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.033
LAGNLTFEXP_LAGN->PJM
CLTF
3.144
TVALTFEXP_TVA->PJM
CLTF
0.79

Details for COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line l/o COMED_P4_167-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_167-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.09 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1646.66
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
274708KENDALL ;3C
50/50
2.096
274837EQUISTAR ; B
50/50
0.347
274837EQUISTAR ; B
50/50
0.347
276640AD2-194 GEN1
50/50
3.701
276642AD2-194 GEN2
50/50
3.686
274731ELWOOD EC;2P
Adder
15.517
274733ELWOOD EC;3P
Adder
15.517
274735ELWOOD EC;4P
Adder
15.517
274728ELWOOD EC;5P
Adder
15.457
274746AC1-111 G10
Adder
5.026
274744AC1-111 GEN8
Adder
5.026
274675JOLIET 29;7U
Adder
27.494
274675JOLIET 29;7U
Adder
26.512
971177AH1-047 GEN
Solar/Wind Harmer
4.871
276868AE1-113 GEN
Solar/Wind Harmer
8.371
276882AE2-255 GEN
Solar/Wind Harmer
2.791
971411AH1-196 GEN
Solar/Wind Harmer
12.376
970833AG2-524 GEN
Solar/Wind Harmer
7.076
970833AG2-524 GEN
Solar/Wind Harmer
3.291
970169AG2-114 GEN
Solar/Wind Harmer
8.085
274823ROCKFORD ;21
Adder
15.74
971675AH1-338 GEN
Solar/Wind Harmer
14.497
971171AH1-044 GEN
Solar/Wind Harmer
15.986
276612AE2-035 GEN
Solar/Wind Harmer
2.035
971681AH1-341 GEN
Solar/Wind Harmer
11.731
274687WILL CNTY;4U
Adder
21.473
274687WILL CNTY;4U
Adder
21.473
961011AF2-392 GEN
Solar/Wind Harmer
8.308
957751AF2-069 GEN
Solar/Wind Harmer
0.332
926823AC1-168 GEN
Solar/Wind Harmer
3.107
274848CAMPGROVE;RU
Solar/Wind Harmer
4.656
946321AF1-296 GEN
Solar/Wind Harmer
7.516
274827FISK ;RP
Adder
4.898
276655WTG1_EQ
Solar/Wind Harmer
5.44
276656WTG2_EQ
Solar/Wind Harmer
0.72
959341AF2-225 GEN
Solar/Wind Harmer
9.346
941731AE2-173 GEN
Solar/Wind Harmer
3.622
972037AH1-567 GEN1
Adder
0.111
274863CRW1-WTG
Solar/Wind Harmer
3.099
274864CRW2-WTG
Solar/Wind Harmer
3.099
274814UNIV PK N;0U
Adder
2.724
274807UNIV PK N;3U
Adder
2.718
274805UNIV PK N;1U
Adder
2.707
274811UNIV PK N;7U
Adder
2.701
960591AF2-350 GEN
Solar/Wind Harmer
5.266
972227AH1-698 GEN1
Adder
1.357
276849AB2-070 GEN2
Solar/Wind Harmer
1.109
276848AB2-070 GEN3
Solar/Wind Harmer
1.109
276785W4-005 GEN1
Solar/Wind Harmer
1.49
276174W4-005 GEN2
Solar/Wind Harmer
1.49
274710KENDALL ;4C
50/50
2.08
274658DRESDEN ;2U
50/50
5.065
971997AH1-543 GEN
Solar/Wind Harmer
18.31
274732ELWOOD EC;7P
Adder
15.457
274745AC1-111 GEN9
Adder
5.026
274676JOLIET 29;8U
Adder
27.464
274674JOLIET 9 ;6U
Adder
13.181
274682WAUKEGAN ;7U
Adder
15.339
274828WAUKEGAN ;BP
Adder
9.406
960751AF2-366 GEN
Solar/Wind Harmer
2.355
962781AG1-127 GEN
Solar/Wind Harmer
7.807
274872LEEDK;1U
Solar/Wind Harmer
6.709
274822ROCKFORD ;11
Adder
15.855
972235AH1-702 GEN1
Adder
2.029
276861AD2-134 GEN
Solar/Wind Harmer
1.438
957471AF2-041 GEN
Solar/Wind Harmer
23.979
959081AF2-199 GEN
Solar/Wind Harmer
7.993
971067AG2-660 GEN
Solar/Wind Harmer
1.859
970819AG2-516 GEN
Solar/Wind Harmer
9.586
971475AH1-234 GEN
Solar/Wind Harmer
17.833
276901AD2-066 C O1
Solar/Wind Harmer
2.796
970569AG2-363 GEN
Solar/Wind Harmer
23.754
274857EASY ROAD;U1
Solar/Wind Harmer
3.731
274761LEE CO EC;2U
Adder
7.243
274766LEE CO EC;7U
Adder
7.157
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
276158O29GEN2
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.346
274877BISHOP HL;1U
Solar/Wind Harmer
2.449
274871GR RIDGE ;2U
Solar/Wind Harmer
5.502
274801UNIV PARK;4U
Adder
3.636
276726Z2-087_GEN
Solar/Wind Harmer
4.928
939741AE1-205 GEN
Solar/Wind Harmer
12.461
274854TWINGROVE;U2
Solar/Wind Harmer
4.184
972175AH1-670 GEN
Solar/Wind Harmer
7.374
274812UNIV PK N;8U
Adder
2.701
276776AD2-060 GEN
Solar/Wind Harmer
0.223
274880W4-005 GEN4
Solar/Wind Harmer
1.49
939401AE1-172 GEN
Solar/Wind Harmer
6.817
963831AG1-236 GEN
Solar/Wind Harmer
4.789
276615X2-022 GEN
Solar/Wind Harmer
0.927
276164X3-005 C
Solar/Wind Harmer
0.323
274751CRETE EC ;1U
Adder
2.11
274754CRETE EC ;4U
Adder
2.11
274709KENDALL ;3S
50/50
1.389
274711KENDALL ;4S
50/50
1.389
276660THREERVRS;U2
50/50
3.446
274695ROCKY RD ;2P
Adder
9.606
274693ROCKY RD ;1P
Adder
9.512
274697ROCKY RD ;3P
Adder
2.61
274696ROCKY RD ;4P
Adder
9.832
274674JOLIET 9 ;6U
Adder
13.181
274683WAUKEGAN ;8U
Adder
17.944
274683WAUKEGAN ;8U
Adder
15.126
942991AE2-321 GEN
Solar/Wind Harmer
8.324
274879MINONK ;1U
Solar/Wind Harmer
5.581
971573AH1-285 GEN
Solar/Wind Harmer
7.112
971333AH1-146 GEN
Solar/Wind Harmer
16.508
971335AH1-147 GEN
Solar/Wind Harmer
16.508
962691AG1-118 GEN
Solar/Wind Harmer
24.725
970921AG2-575 GEN
Solar/Wind Harmer
8.21
970921AG2-575 GEN
Solar/Wind Harmer
1.909
971341AH1-150 GEN
Solar/Wind Harmer
15.986
971343AH1-151 GEN
Solar/Wind Harmer
15.986
274856ECOGROVE ;U1
Solar/Wind Harmer
2.682
276611AD2-172 GEN
Solar/Wind Harmer
2.035
938861AE1-114 GEN
Solar/Wind Harmer
6.417
274764LEE CO EC;5U
Adder
7.26
274765LEE CO EC;6U
Adder
7.26
274762LEE CO EC;3U
Adder
7.243
274763LEE CO EC;4U
Adder
7.174
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276603SUBLETTE C
Solar/Wind Harmer
0.81
972267AH1-718 GEN
Adder
3.169
958491AF2-143 GEN
Solar/Wind Harmer
11.361
276741O09 GEN1
Solar/Wind Harmer
2.688
276708O09 GEN2
Solar/Wind Harmer
2.688
958481AF2-142 GEN
Solar/Wind Harmer
11.14
276782AC1-033 GEN
Solar/Wind Harmer
2.894
274851PROVIDENC;RU
Solar/Wind Harmer
2.061
274849CRESCENT ;1U
Solar/Wind Harmer
1.338
276645AC1-214 GEN1
Solar/Wind Harmer
0.969
276646AC1-214 GEN2
Solar/Wind Harmer
0.969
274861TOP CROP ;1U
Solar/Wind Harmer
4.37
274862TOP CROP ;2U
Solar/Wind Harmer
3.649
274847GR RIDGE ;BU
Solar/Wind Harmer
3.619
972259AH1-714 GEN
Adder
12.185
274803UNIV PARK;6U
Adder
3.539
960611AF2-352 GEN
Solar/Wind Harmer
1.379
274808UNIV PK N;4U
Adder
2.689
274888KELLY CRK;1U
Solar/Wind Harmer
3.109
274887GEN-1.85
Solar/Wind Harmer
2.807
276843GEN-1.7
Solar/Wind Harmer
0.302
958011AF2-095 GEN
Solar/Wind Harmer
7.583
276763AC1-053 GEN1
Solar/Wind Harmer
1.925
276764AC1-053 GEN2
Solar/Wind Harmer
1.925
957381AF2-032 GEN
Solar/Wind Harmer
0.181
274659DRESDEN ;3U
50/50
8.379
276658THREERVRS;U1
50/50
5.69
274729ELWOOD EC;1P
Adder
15.517
274730ELWOOD EC;6P
Adder
15.457
274734ELWOOD EC;8P
Adder
15.457
274736ELWOOD EC;9P
Adder
15.457
274676JOLIET 29;8U
Adder
26.484
274682WAUKEGAN ;7U
Adder
15.339
943121AE2-341 GEN
Solar/Wind Harmer
12.437
943591AF1-030 GEN
Solar/Wind Harmer
8.291
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
1.782
946671AF1-331 GEN
Solar/Wind Harmer
0.337
972236AH1-702 GEN2
Adder
1.764
274855GSG-6 ;RU
Solar/Wind Harmer
2.973
274850MENDOTA H;RU
Solar/Wind Harmer
2.067
276602WESTBROOK C
Solar/Wind Harmer
1.711
276863AD2-134 GEN
Solar/Wind Harmer
1.438
959091AF2-200 GEN
Solar/Wind Harmer
15.986
970571AG2-364 GEN
Solar/Wind Harmer
15.836
274858EASY ROAD;U2
Solar/Wind Harmer
3.731
274760LEE CO EC;1U
Adder
7.243
274767LEE CO EC;8U
Adder
7.157
276889AE2-281 GEN
Solar/Wind Harmer
1.493
276805AD2-038 GEN
Solar/Wind Harmer
3.885
276157O29GEN1
Solar/Wind Harmer
2.862
276694AA1-018 GEN2
Solar/Wind Harmer
4.687
970707AG2-453 GEN
Solar/Wind Harmer
20.558
276893AG1-478 C
Solar/Wind Harmer
0.306
274878BISHOP HL;2U
Solar/Wind Harmer
2.449
965931AG1-462 GEN
Solar/Wind Harmer
18.196
274826FISK ;BP
Adder
6.912
274800UNIV PARK;3U
Adder
3.636
972038AH1-567 GEN2
Adder
0.228
942111AE2-223 GEN
Solar/Wind Harmer
5.107
274802UNIV PARK;5U
Adder
3.539
274853TWINGROVE;U1
Solar/Wind Harmer
4.273
965091AG1-374 GEN
Solar/Wind Harmer
17.788
959611AF2-252 GEN
Solar/Wind Harmer
1.379
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276806AD2-047 C O1
Solar/Wind Harmer
5.633
970941AG2-585 GEN
Solar/Wind Harmer
6.582
972228AH1-698 GEN2
Adder
1.932
276668AB2-070 GEN1
Solar/Wind Harmer
1.109
276686W4-005 GEN3
Solar/Wind Harmer
1.49
971993AH1-541 GEN
Solar/Wind Harmer
4.553
276621W2-048 GEN
Solar/Wind Harmer
2.953
276838X2-022 GEN2
Solar/Wind Harmer
0.11
972231SS25-0005
Solar/Wind Harmer
4.097
972181SS23-001
Solar/Wind Harmer
2.56
274752CRETE EC ;2U
Adder
2.11
274753CRETE EC ;3U
Adder
2.11
990512J1326
External Queue
4.053475379943848
990117J1214
External Queue
13.943954467773438
990727J1377 G
External Queue
4.715986728668213
991777J1629 G
External Queue
9.171701431274414
990407J1304
External Queue
3.1380622386932373
NYPJM->LTFIMP_NY
CLTF
0.755
WECLTFEXP_WEC->PJM
CLTF
3.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.795
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.318
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.129
MECLTFEXP_MEC->PJM
CLTF
9.633
SIGELTFEXP_SIGE->PJM
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.033
LAGNLTFEXP_LAGN->PJM
CLTF
3.144
TVALTFEXP_TVA->PJM
CLTF
0.79

Details for COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_167-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.27 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1649.17
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
274659DRESDEN ;3U
50/50
8.379
276658THREERVRS;U1
50/50
5.69
274729ELWOOD EC;1P
Adder
15.517
274730ELWOOD EC;6P
Adder
15.457
274734ELWOOD EC;8P
Adder
15.457
274736ELWOOD EC;9P
Adder
15.457
274676JOLIET 29;8U
Adder
26.484
274682WAUKEGAN ;7U
Adder
15.339
943121AE2-341 GEN
Solar/Wind Harmer
12.437
943591AF1-030 GEN
Solar/Wind Harmer
8.291
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
1.782
946671AF1-331 GEN
Solar/Wind Harmer
0.337
972236AH1-702 GEN2
Adder
1.764
274855GSG-6 ;RU
Solar/Wind Harmer
2.973
274850MENDOTA H;RU
Solar/Wind Harmer
2.067
276602WESTBROOK C
Solar/Wind Harmer
1.711
276863AD2-134 GEN
Solar/Wind Harmer
1.438
274710KENDALL ;4C
50/50
2.08
274658DRESDEN ;2U
50/50
5.065
971997AH1-543 GEN
Solar/Wind Harmer
18.31
274732ELWOOD EC;7P
Adder
15.457
274745AC1-111 GEN9
Adder
5.026
274676JOLIET 29;8U
Adder
27.464
274674JOLIET 9 ;6U
Adder
13.181
274682WAUKEGAN ;7U
Adder
15.339
274828WAUKEGAN ;BP
Adder
9.406
960751AF2-366 GEN
Solar/Wind Harmer
2.355
962781AG1-127 GEN
Solar/Wind Harmer
7.807
274872LEEDK;1U
Solar/Wind Harmer
6.709
274822ROCKFORD ;11
Adder
15.855
972235AH1-702 GEN1
Adder
2.029
276861AD2-134 GEN
Solar/Wind Harmer
1.438
957471AF2-041 GEN
Solar/Wind Harmer
23.979
959081AF2-199 GEN
Solar/Wind Harmer
7.993
971067AG2-660 GEN
Solar/Wind Harmer
1.859
970819AG2-516 GEN
Solar/Wind Harmer
9.586
971475AH1-234 GEN
Solar/Wind Harmer
17.833
276901AD2-066 C O1
Solar/Wind Harmer
2.796
970569AG2-363 GEN
Solar/Wind Harmer
23.754
274857EASY ROAD;U1
Solar/Wind Harmer
3.731
274761LEE CO EC;2U
Adder
7.243
274766LEE CO EC;7U
Adder
7.157
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
276158O29GEN2
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.346
274877BISHOP HL;1U
Solar/Wind Harmer
2.449
274871GR RIDGE ;2U
Solar/Wind Harmer
5.502
274801UNIV PARK;4U
Adder
3.636
276726Z2-087_GEN
Solar/Wind Harmer
4.928
939741AE1-205 GEN
Solar/Wind Harmer
12.461
274854TWINGROVE;U2
Solar/Wind Harmer
4.184
972175AH1-670 GEN
Solar/Wind Harmer
7.374
274812UNIV PK N;8U
Adder
2.701
276776AD2-060 GEN
Solar/Wind Harmer
0.223
274880W4-005 GEN4
Solar/Wind Harmer
1.49
939401AE1-172 GEN
Solar/Wind Harmer
6.817
963831AG1-236 GEN
Solar/Wind Harmer
4.789
276615X2-022 GEN
Solar/Wind Harmer
0.927
276164X3-005 C
Solar/Wind Harmer
0.323
274751CRETE EC ;1U
Adder
2.11
274754CRETE EC ;4U
Adder
2.11
274708KENDALL ;3C
50/50
2.096
274837EQUISTAR ; B
50/50
0.347
274837EQUISTAR ; B
50/50
0.347
276640AD2-194 GEN1
50/50
3.701
276642AD2-194 GEN2
50/50
3.686
274731ELWOOD EC;2P
Adder
15.517
274733ELWOOD EC;3P
Adder
15.517
274735ELWOOD EC;4P
Adder
15.517
274728ELWOOD EC;5P
Adder
15.457
274746AC1-111 G10
Adder
5.026
274744AC1-111 GEN8
Adder
5.026
274675JOLIET 29;7U
Adder
27.494
274675JOLIET 29;7U
Adder
26.512
971177AH1-047 GEN
Solar/Wind Harmer
4.871
276868AE1-113 GEN
Solar/Wind Harmer
8.371
276882AE2-255 GEN
Solar/Wind Harmer
2.791
971411AH1-196 GEN
Solar/Wind Harmer
12.376
970833AG2-524 GEN
Solar/Wind Harmer
7.076
970833AG2-524 GEN
Solar/Wind Harmer
3.291
970169AG2-114 GEN
Solar/Wind Harmer
8.085
274823ROCKFORD ;21
Adder
15.74
971675AH1-338 GEN
Solar/Wind Harmer
14.497
971171AH1-044 GEN
Solar/Wind Harmer
15.986
276612AE2-035 GEN
Solar/Wind Harmer
2.035
971681AH1-341 GEN
Solar/Wind Harmer
11.731
274687WILL CNTY;4U
Adder
21.473
274687WILL CNTY;4U
Adder
21.473
961011AF2-392 GEN
Solar/Wind Harmer
8.308
957751AF2-069 GEN
Solar/Wind Harmer
0.332
926823AC1-168 GEN
Solar/Wind Harmer
3.107
274848CAMPGROVE;RU
Solar/Wind Harmer
4.656
946321AF1-296 GEN
Solar/Wind Harmer
7.516
274827FISK ;RP
Adder
4.898
276655WTG1_EQ
Solar/Wind Harmer
5.44
276656WTG2_EQ
Solar/Wind Harmer
0.72
959341AF2-225 GEN
Solar/Wind Harmer
9.346
941731AE2-173 GEN
Solar/Wind Harmer
3.622
972037AH1-567 GEN1
Adder
0.111
274863CRW1-WTG
Solar/Wind Harmer
3.099
274864CRW2-WTG
Solar/Wind Harmer
3.099
274814UNIV PK N;0U
Adder
2.724
274807UNIV PK N;3U
Adder
2.718
274805UNIV PK N;1U
Adder
2.707
274811UNIV PK N;7U
Adder
2.701
960591AF2-350 GEN
Solar/Wind Harmer
5.266
972227AH1-698 GEN1
Adder
1.357
276849AB2-070 GEN2
Solar/Wind Harmer
1.109
276848AB2-070 GEN3
Solar/Wind Harmer
1.109
276785W4-005 GEN1
Solar/Wind Harmer
1.49
276174W4-005 GEN2
Solar/Wind Harmer
1.49
274709KENDALL ;3S
50/50
1.389
274711KENDALL ;4S
50/50
1.389
276660THREERVRS;U2
50/50
3.446
274695ROCKY RD ;2P
Adder
9.606
274693ROCKY RD ;1P
Adder
9.512
274697ROCKY RD ;3P
Adder
2.61
274696ROCKY RD ;4P
Adder
9.832
274674JOLIET 9 ;6U
Adder
13.181
274683WAUKEGAN ;8U
Adder
17.944
274683WAUKEGAN ;8U
Adder
15.126
942991AE2-321 GEN
Solar/Wind Harmer
8.324
274879MINONK ;1U
Solar/Wind Harmer
5.581
971573AH1-285 GEN
Solar/Wind Harmer
7.112
971333AH1-146 GEN
Solar/Wind Harmer
16.508
971335AH1-147 GEN
Solar/Wind Harmer
16.508
962691AG1-118 GEN
Solar/Wind Harmer
24.725
970921AG2-575 GEN
Solar/Wind Harmer
8.21
970921AG2-575 GEN
Solar/Wind Harmer
1.909
971341AH1-150 GEN
Solar/Wind Harmer
15.986
971343AH1-151 GEN
Solar/Wind Harmer
15.986
274856ECOGROVE ;U1
Solar/Wind Harmer
2.682
276611AD2-172 GEN
Solar/Wind Harmer
2.035
938861AE1-114 GEN
Solar/Wind Harmer
6.417
274764LEE CO EC;5U
Adder
7.26
274765LEE CO EC;6U
Adder
7.26
274762LEE CO EC;3U
Adder
7.243
274763LEE CO EC;4U
Adder
7.174
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276603SUBLETTE C
Solar/Wind Harmer
0.81
972267AH1-718 GEN
Adder
3.169
958491AF2-143 GEN
Solar/Wind Harmer
11.361
276741O09 GEN1
Solar/Wind Harmer
2.688
276708O09 GEN2
Solar/Wind Harmer
2.688
958481AF2-142 GEN
Solar/Wind Harmer
11.14
276782AC1-033 GEN
Solar/Wind Harmer
2.894
274851PROVIDENC;RU
Solar/Wind Harmer
2.061
274849CRESCENT ;1U
Solar/Wind Harmer
1.338
276645AC1-214 GEN1
Solar/Wind Harmer
0.969
276646AC1-214 GEN2
Solar/Wind Harmer
0.969
274861TOP CROP ;1U
Solar/Wind Harmer
4.37
274862TOP CROP ;2U
Solar/Wind Harmer
3.649
274847GR RIDGE ;BU
Solar/Wind Harmer
3.619
972259AH1-714 GEN
Adder
12.185
274803UNIV PARK;6U
Adder
3.539
960611AF2-352 GEN
Solar/Wind Harmer
1.379
274808UNIV PK N;4U
Adder
2.689
274888KELLY CRK;1U
Solar/Wind Harmer
3.109
274887GEN-1.85
Solar/Wind Harmer
2.807
276843GEN-1.7
Solar/Wind Harmer
0.302
958011AF2-095 GEN
Solar/Wind Harmer
7.583
276763AC1-053 GEN1
Solar/Wind Harmer
1.925
276764AC1-053 GEN2
Solar/Wind Harmer
1.925
957381AF2-032 GEN
Solar/Wind Harmer
0.181
959091AF2-200 GEN
Solar/Wind Harmer
15.986
970571AG2-364 GEN
Solar/Wind Harmer
15.836
274858EASY ROAD;U2
Solar/Wind Harmer
3.731
274760LEE CO EC;1U
Adder
7.243
274767LEE CO EC;8U
Adder
7.157
276889AE2-281 GEN
Solar/Wind Harmer
1.493
276805AD2-038 GEN
Solar/Wind Harmer
3.885
276157O29GEN1
Solar/Wind Harmer
2.862
276694AA1-018 GEN2
Solar/Wind Harmer
4.687
970707AG2-453 GEN
Solar/Wind Harmer
20.558
276893AG1-478 C
Solar/Wind Harmer
0.306
274878BISHOP HL;2U
Solar/Wind Harmer
2.449
965931AG1-462 GEN
Solar/Wind Harmer
18.196
274826FISK ;BP
Adder
6.912
274800UNIV PARK;3U
Adder
3.636
972038AH1-567 GEN2
Adder
0.228
942111AE2-223 GEN
Solar/Wind Harmer
5.107
274802UNIV PARK;5U
Adder
3.539
274853TWINGROVE;U1
Solar/Wind Harmer
4.273
965091AG1-374 GEN
Solar/Wind Harmer
17.788
959611AF2-252 GEN
Solar/Wind Harmer
1.379
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276806AD2-047 C O1
Solar/Wind Harmer
5.633
970941AG2-585 GEN
Solar/Wind Harmer
6.582
972228AH1-698 GEN2
Adder
1.932
276668AB2-070 GEN1
Solar/Wind Harmer
1.109
276686W4-005 GEN3
Solar/Wind Harmer
1.49
971993AH1-541 GEN
Solar/Wind Harmer
4.553
276621W2-048 GEN
Solar/Wind Harmer
2.953
276838X2-022 GEN2
Solar/Wind Harmer
0.11
972231SS25-0005
Solar/Wind Harmer
4.097
972181SS23-001
Solar/Wind Harmer
2.56
274752CRETE EC ;2U
Adder
2.11
274753CRETE EC ;3U
Adder
2.11
990512J1326
External Queue
4.053475379943848
990117J1214
External Queue
13.943954467773438
990727J1377 G
External Queue
4.715986728668213
991777J1629 G
External Queue
9.171701431274414
990407J1304
External Queue
3.1380622386932373
NYPJM->LTFIMP_NY
CLTF
0.755
WECLTFEXP_WEC->PJM
CLTF
3.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.795
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.318
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.129
MECLTFEXP_MEC->PJM
CLTF
9.633
SIGELTFEXP_SIGE->PJM
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.033
LAGNLTFEXP_LAGN->PJM
CLTF
3.144
TVALTFEXP_TVA->PJM
CLTF
0.79

Details for COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_167-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
COLLINS ;2M-COLLINS ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_167-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.27 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1649.17
MW Contribution:9.59
Bus #Bus NameTypeMW Contribution
274708KENDALL ;3C
50/50
2.096
274837EQUISTAR ; B
50/50
0.347
274837EQUISTAR ; B
50/50
0.347
276640AD2-194 GEN1
50/50
3.701
276642AD2-194 GEN2
50/50
3.686
274731ELWOOD EC;2P
Adder
15.517
274733ELWOOD EC;3P
Adder
15.517
274735ELWOOD EC;4P
Adder
15.517
274728ELWOOD EC;5P
Adder
15.457
274746AC1-111 G10
Adder
5.026
274744AC1-111 GEN8
Adder
5.026
274675JOLIET 29;7U
Adder
27.494
274675JOLIET 29;7U
Adder
26.512
971177AH1-047 GEN
Solar/Wind Harmer
4.871
276868AE1-113 GEN
Solar/Wind Harmer
8.371
276882AE2-255 GEN
Solar/Wind Harmer
2.791
971411AH1-196 GEN
Solar/Wind Harmer
12.376
970833AG2-524 GEN
Solar/Wind Harmer
7.076
970833AG2-524 GEN
Solar/Wind Harmer
3.291
970169AG2-114 GEN
Solar/Wind Harmer
8.085
274823ROCKFORD ;21
Adder
15.74
971675AH1-338 GEN
Solar/Wind Harmer
14.497
971171AH1-044 GEN
Solar/Wind Harmer
15.986
276612AE2-035 GEN
Solar/Wind Harmer
2.035
971681AH1-341 GEN
Solar/Wind Harmer
11.731
274687WILL CNTY;4U
Adder
21.473
274687WILL CNTY;4U
Adder
21.473
961011AF2-392 GEN
Solar/Wind Harmer
8.308
957751AF2-069 GEN
Solar/Wind Harmer
0.332
926823AC1-168 GEN
Solar/Wind Harmer
3.107
274848CAMPGROVE;RU
Solar/Wind Harmer
4.656
946321AF1-296 GEN
Solar/Wind Harmer
7.516
274827FISK ;RP
Adder
4.898
276655WTG1_EQ
Solar/Wind Harmer
5.44
276656WTG2_EQ
Solar/Wind Harmer
0.72
959341AF2-225 GEN
Solar/Wind Harmer
9.346
941731AE2-173 GEN
Solar/Wind Harmer
3.622
972037AH1-567 GEN1
Adder
0.111
274863CRW1-WTG
Solar/Wind Harmer
3.099
274864CRW2-WTG
Solar/Wind Harmer
3.099
274814UNIV PK N;0U
Adder
2.724
274807UNIV PK N;3U
Adder
2.718
274805UNIV PK N;1U
Adder
2.707
274811UNIV PK N;7U
Adder
2.701
960591AF2-350 GEN
Solar/Wind Harmer
5.266
972227AH1-698 GEN1
Adder
1.357
276849AB2-070 GEN2
Solar/Wind Harmer
1.109
276848AB2-070 GEN3
Solar/Wind Harmer
1.109
276785W4-005 GEN1
Solar/Wind Harmer
1.49
276174W4-005 GEN2
Solar/Wind Harmer
1.49
274709KENDALL ;3S
50/50
1.389
274711KENDALL ;4S
50/50
1.389
276660THREERVRS;U2
50/50
3.446
274695ROCKY RD ;2P
Adder
9.606
274693ROCKY RD ;1P
Adder
9.512
274697ROCKY RD ;3P
Adder
2.61
274696ROCKY RD ;4P
Adder
9.832
274674JOLIET 9 ;6U
Adder
13.181
274683WAUKEGAN ;8U
Adder
17.944
274683WAUKEGAN ;8U
Adder
15.126
942991AE2-321 GEN
Solar/Wind Harmer
8.324
274879MINONK ;1U
Solar/Wind Harmer
5.581
971573AH1-285 GEN
Solar/Wind Harmer
7.112
971333AH1-146 GEN
Solar/Wind Harmer
16.508
971335AH1-147 GEN
Solar/Wind Harmer
16.508
962691AG1-118 GEN
Solar/Wind Harmer
24.725
970921AG2-575 GEN
Solar/Wind Harmer
8.21
970921AG2-575 GEN
Solar/Wind Harmer
1.909
971341AH1-150 GEN
Solar/Wind Harmer
15.986
971343AH1-151 GEN
Solar/Wind Harmer
15.986
274856ECOGROVE ;U1
Solar/Wind Harmer
2.682
276611AD2-172 GEN
Solar/Wind Harmer
2.035
938861AE1-114 GEN
Solar/Wind Harmer
6.417
274764LEE CO EC;5U
Adder
7.26
274765LEE CO EC;6U
Adder
7.26
274762LEE CO EC;3U
Adder
7.243
274763LEE CO EC;4U
Adder
7.174
276872AE1-163_GEN1
Solar/Wind Harmer
5.224
276603SUBLETTE C
Solar/Wind Harmer
0.81
972267AH1-718 GEN
Adder
3.169
958491AF2-143 GEN
Solar/Wind Harmer
11.361
276741O09 GEN1
Solar/Wind Harmer
2.688
276708O09 GEN2
Solar/Wind Harmer
2.688
958481AF2-142 GEN
Solar/Wind Harmer
11.14
276782AC1-033 GEN
Solar/Wind Harmer
2.894
274851PROVIDENC;RU
Solar/Wind Harmer
2.061
274849CRESCENT ;1U
Solar/Wind Harmer
1.338
276645AC1-214 GEN1
Solar/Wind Harmer
0.969
276646AC1-214 GEN2
Solar/Wind Harmer
0.969
274861TOP CROP ;1U
Solar/Wind Harmer
4.37
274862TOP CROP ;2U
Solar/Wind Harmer
3.649
274847GR RIDGE ;BU
Solar/Wind Harmer
3.619
972259AH1-714 GEN
Adder
12.185
274803UNIV PARK;6U
Adder
3.539
960611AF2-352 GEN
Solar/Wind Harmer
1.379
274808UNIV PK N;4U
Adder
2.689
274888KELLY CRK;1U
Solar/Wind Harmer
3.109
274887GEN-1.85
Solar/Wind Harmer
2.807
276843GEN-1.7
Solar/Wind Harmer
0.302
958011AF2-095 GEN
Solar/Wind Harmer
7.583
276763AC1-053 GEN1
Solar/Wind Harmer
1.925
276764AC1-053 GEN2
Solar/Wind Harmer
1.925
957381AF2-032 GEN
Solar/Wind Harmer
0.181
274710KENDALL ;4C
50/50
2.08
274658DRESDEN ;2U
50/50
5.065
971997AH1-543 GEN
Solar/Wind Harmer
18.31
274732ELWOOD EC;7P
Adder
15.457
274745AC1-111 GEN9
Adder
5.026
274676JOLIET 29;8U
Adder
27.464
274674JOLIET 9 ;6U
Adder
13.181
274682WAUKEGAN ;7U
Adder
15.339
274828WAUKEGAN ;BP
Adder
9.406
960751AF2-366 GEN
Solar/Wind Harmer
2.355
962781AG1-127 GEN
Solar/Wind Harmer
7.807
274872LEEDK;1U
Solar/Wind Harmer
6.709
274822ROCKFORD ;11
Adder
15.855
972235AH1-702 GEN1
Adder
2.029
276861AD2-134 GEN
Solar/Wind Harmer
1.438
957471AF2-041 GEN
Solar/Wind Harmer
23.979
959081AF2-199 GEN
Solar/Wind Harmer
7.993
971067AG2-660 GEN
Solar/Wind Harmer
1.859
970819AG2-516 GEN
Solar/Wind Harmer
9.586
971475AH1-234 GEN
Solar/Wind Harmer
17.833
276901AD2-066 C O1
Solar/Wind Harmer
2.796
970569AG2-363 GEN
Solar/Wind Harmer
23.754
274857EASY ROAD;U1
Solar/Wind Harmer
3.731
274761LEE CO EC;2U
Adder
7.243
274766LEE CO EC;7U
Adder
7.157
276876AE1-163_GEN2
Solar/Wind Harmer
5.224
276158O29GEN2
Solar/Wind Harmer
3.763
276691AA1-018 GEN1
Solar/Wind Harmer
0.346
274877BISHOP HL;1U
Solar/Wind Harmer
2.449
274871GR RIDGE ;2U
Solar/Wind Harmer
5.502
274801UNIV PARK;4U
Adder
3.636
276726Z2-087_GEN
Solar/Wind Harmer
4.928
939741AE1-205 GEN
Solar/Wind Harmer
12.461
274854TWINGROVE;U2
Solar/Wind Harmer
4.184
972175AH1-670 GEN
Solar/Wind Harmer
7.374
274812UNIV PK N;8U
Adder
2.701
276776AD2-060 GEN
Solar/Wind Harmer
0.223
274880W4-005 GEN4
Solar/Wind Harmer
1.49
939401AE1-172 GEN
Solar/Wind Harmer
6.817
963831AG1-236 GEN
Solar/Wind Harmer
4.789
276615X2-022 GEN
Solar/Wind Harmer
0.927
276164X3-005 C
Solar/Wind Harmer
0.323
274751CRETE EC ;1U
Adder
2.11
274754CRETE EC ;4U
Adder
2.11
274659DRESDEN ;3U
50/50
8.379
276658THREERVRS;U1
50/50
5.69
274729ELWOOD EC;1P
Adder
15.517
274730ELWOOD EC;6P
Adder
15.457
274734ELWOOD EC;8P
Adder
15.457
274736ELWOOD EC;9P
Adder
15.457
274676JOLIET 29;8U
Adder
26.484
274682WAUKEGAN ;7U
Adder
15.339
943121AE2-341 GEN
Solar/Wind Harmer
12.437
943591AF1-030 GEN
Solar/Wind Harmer
8.291
274872LEEDK;1U
Solar/Wind Harmer
0.209
276799AD1-013 GEN
Solar/Wind Harmer
1.782
946671AF1-331 GEN
Solar/Wind Harmer
0.337
972236AH1-702 GEN2
Adder
1.764
274855GSG-6 ;RU
Solar/Wind Harmer
2.973
274850MENDOTA H;RU
Solar/Wind Harmer
2.067
276602WESTBROOK C
Solar/Wind Harmer
1.711
276863AD2-134 GEN
Solar/Wind Harmer
1.438
959091AF2-200 GEN
Solar/Wind Harmer
15.986
970571AG2-364 GEN
Solar/Wind Harmer
15.836
274858EASY ROAD;U2
Solar/Wind Harmer
3.731
274760LEE CO EC;1U
Adder
7.243
274767LEE CO EC;8U
Adder
7.157
276889AE2-281 GEN
Solar/Wind Harmer
1.493
276805AD2-038 GEN
Solar/Wind Harmer
3.885
276157O29GEN1
Solar/Wind Harmer
2.862
276694AA1-018 GEN2
Solar/Wind Harmer
4.687
970707AG2-453 GEN
Solar/Wind Harmer
20.558
276893AG1-478 C
Solar/Wind Harmer
0.306
274878BISHOP HL;2U
Solar/Wind Harmer
2.449
965931AG1-462 GEN
Solar/Wind Harmer
18.196
274826FISK ;BP
Adder
6.912
274800UNIV PARK;3U
Adder
3.636
972038AH1-567 GEN2
Adder
0.228
942111AE2-223 GEN
Solar/Wind Harmer
5.107
274802UNIV PARK;5U
Adder
3.539
274853TWINGROVE;U1
Solar/Wind Harmer
4.273
965091AG1-374 GEN
Solar/Wind Harmer
17.788
959611AF2-252 GEN
Solar/Wind Harmer
1.379
276772AC2-154 GEN
Solar/Wind Harmer
1.469
276806AD2-047 C O1
Solar/Wind Harmer
5.633
970941AG2-585 GEN
Solar/Wind Harmer
6.582
972228AH1-698 GEN2
Adder
1.932
276668AB2-070 GEN1
Solar/Wind Harmer
1.109
276686W4-005 GEN3
Solar/Wind Harmer
1.49
971993AH1-541 GEN
Solar/Wind Harmer
4.553
276621W2-048 GEN
Solar/Wind Harmer
2.953
276838X2-022 GEN2
Solar/Wind Harmer
0.11
972231SS25-0005
Solar/Wind Harmer
4.097
972181SS23-001
Solar/Wind Harmer
2.56
274752CRETE EC ;2U
Adder
2.11
274753CRETE EC ;3U
Adder
2.11
990512J1326
External Queue
4.053475379943848
990117J1214
External Queue
13.943954467773438
990727J1377 G
External Queue
4.715986728668213
991777J1629 G
External Queue
9.171701431274414
990407J1304
External Queue
3.1380622386932373
NYPJM->LTFIMP_NY
CLTF
0.755
WECLTFEXP_WEC->PJM
CLTF
3.065
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.795
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.316
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
51.318
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.129
MECLTFEXP_MEC->PJM
CLTF
9.633
SIGELTFEXP_SIGE->PJM
CLTF
0.011
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.366
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.033
LAGNLTFEXP_LAGN->PJM
CLTF
3.144
TVALTFEXP_TVA->PJM
CLTF
0.79

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.4 %
Rating:1201.0 MVA
Rating Type:A
MVA to Mitigate:1277.87
MW Contribution:3.64
Bus #Bus NameTypeMW Contribution
274743AC1-111 GEN7
50/50
0.167
274745AC1-111 GEN9
50/50
3.062
276890AG1-513 C
50/50
0.24
957471AF2-041 GEN
Solar/Wind Harmer
25.095
959081AF2-199 GEN
Solar/Wind Harmer
8.365
971067AG2-660 GEN
Solar/Wind Harmer
2.788
962781AG1-127 GEN
Solar/Wind Harmer
5.247
274872LEEDK;1U
Solar/Wind Harmer
0.003
276861AD2-134 GEN
Solar/Wind Harmer
0.093
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
5.499
274766LEE CO EC;7U
Adder
5.434
276158O29GEN2
Solar/Wind Harmer
0
972235AH1-702 GEN1
Adder
1.232
970819AG2-516 GEN
Solar/Wind Harmer
3.637
274822ROCKFORD ;11
Adder
8.519
274741AC1-111 GEN5
50/50
0.167
959091AF2-200 GEN
Solar/Wind Harmer
16.73
274872LEEDK;1U
Solar/Wind Harmer
0.202
943121AE2-341 GEN
Solar/Wind Harmer
8.952
943591AF1-030 GEN
Solar/Wind Harmer
5.953
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.555
274855GSG-6 ;RU
Solar/Wind Harmer
0.19
274850MENDOTA H;RU
Solar/Wind Harmer
0.061
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.093
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
5.499
274767LEE CO EC;8U
Adder
5.434
276157O29GEN1
Solar/Wind Harmer
0.598
972236AH1-702 GEN2
Adder
1.068
965931AG1-462 GEN
Solar/Wind Harmer
8.404
972029AH1-563 GEN
50/50
9.006
274746AC1-111 G10
50/50
3.062
274744AC1-111 GEN8
50/50
3.062
971171AH1-044 GEN
Solar/Wind Harmer
16.73
971675AH1-338 GEN
Solar/Wind Harmer
2.025
961011AF2-392 GEN
Solar/Wind Harmer
2.541
971681AH1-341 GEN
Solar/Wind Harmer
6.413
946321AF1-296 GEN
Solar/Wind Harmer
1.865
276612AE2-035 GEN
Solar/Wind Harmer
0.001
274823ROCKFORD ;21
Adder
8.46
274738AURORA EC;3P
50/50
1.4
274740AURORA EC;4P
50/50
1.4
274742AC1-111 GEN6
50/50
0.167
971341AH1-150 GEN
Solar/Wind Harmer
16.73
971343AH1-151 GEN
Solar/Wind Harmer
16.73
962691AG1-118 GEN
Solar/Wind Harmer
17.758
970921AG2-575 GEN
Solar/Wind Harmer
5.514
970921AG2-575 GEN
Solar/Wind Harmer
1.838
971573AH1-285 GEN
Solar/Wind Harmer
1.008
972267AH1-718 GEN
Adder
2.741
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
5.512
274765LEE CO EC;6U
Adder
5.512
274762LEE CO EC;3U
Adder
5.499
274763LEE CO EC;4U
Adder
5.447
971333AH1-146 GEN
Solar/Wind Harmer
7.632
971335AH1-147 GEN
Solar/Wind Harmer
7.632
938861AE1-114 GEN
Solar/Wind Harmer
2.141
276741O09 GEN1
Solar/Wind Harmer
0.132
276708O09 GEN2
Solar/Wind Harmer
0.132
274695ROCKY RD ;2P
Adder
5.327
274693ROCKY RD ;1P
Adder
5.275
274697ROCKY RD ;3P
Adder
1.447
274696ROCKY RD ;4P
Adder
5.428
274856ECOGROVE ;U1
Solar/Wind Harmer
0.078
276611AD2-172 GEN
Solar/Wind Harmer
0.001
NYPJM->LTFIMP_NY
CLTF
0.151
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.757
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.05
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.023
CBM West 1LTFEXP_CBM-W1->PJM
CBM
8.633
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.535
MECLTFEXP_MEC->PJM
CLTF
3.632
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.109
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.321
LAGNLTFEXP_LAGN->PJM
CLTF
0.91
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.206

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4-6_111-345-R______SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_111-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.31 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1666.98
MW Contribution:6.65
Bus #Bus NameTypeMW Contribution
274741AC1-111 GEN5
50/50
0.35
274739AURORA EC;2P
50/50
1.024
959091AF2-200 GEN
Solar/Wind Harmer
26.301
943121AE2-341 GEN
Solar/Wind Harmer
14.555
943591AF1-030 GEN
Solar/Wind Harmer
9.703
274872LEEDK;1U
Solar/Wind Harmer
0.246
276799AD1-013 GEN
Solar/Wind Harmer
1.994
946671AF1-331 GEN
Solar/Wind Harmer
0.378
274855GSG-6 ;RU
Solar/Wind Harmer
3.312
274850MENDOTA H;RU
Solar/Wind Harmer
2.303
276602WESTBROOK C
Solar/Wind Harmer
1.907
276863AD2-134 GEN
Solar/Wind Harmer
1.602
274858EASY ROAD;U2
Solar/Wind Harmer
3.385
274760LEE CO EC;1U
Adder
6.572
274767LEE CO EC;8U
Adder
6.494
972236AH1-702 GEN2
Adder
1.372
276157O29GEN1
Solar/Wind Harmer
2.326
970707AG2-453 GEN
Solar/Wind Harmer
15.509
965931AG1-462 GEN
Solar/Wind Harmer
13.862
274738AURORA EC;3P
50/50
1.619
274740AURORA EC;4P
50/50
1.619
274742AC1-111 GEN6
50/50
0.35
971341AH1-150 GEN
Solar/Wind Harmer
26.301
971343AH1-151 GEN
Solar/Wind Harmer
26.301
962691AG1-118 GEN
Solar/Wind Harmer
30.866
971573AH1-285 GEN
Solar/Wind Harmer
8.369
970921AG2-575 GEN
Solar/Wind Harmer
9.646
970921AG2-575 GEN
Solar/Wind Harmer
2.243
972267AH1-718 GEN
Adder
3.157
971333AH1-146 GEN
Solar/Wind Harmer
14.63
971335AH1-147 GEN
Solar/Wind Harmer
14.63
276603SUBLETTE C
Solar/Wind Harmer
0.756
274764LEE CO EC;5U
Adder
6.587
274765LEE CO EC;6U
Adder
6.587
274762LEE CO EC;3U
Adder
6.572
274763LEE CO EC;4U
Adder
6.51
274695ROCKY RD ;2P
Adder
7.776
274693ROCKY RD ;1P
Adder
7.7
274697ROCKY RD ;3P
Adder
2.112
274696ROCKY RD ;4P
Adder
7.923
938861AE1-114 GEN
Solar/Wind Harmer
5.367
276741O09 GEN1
Solar/Wind Harmer
2.185
276708O09 GEN2
Solar/Wind Harmer
2.185
274856ECOGROVE ;U1
Solar/Wind Harmer
2
276611AD2-172 GEN
Solar/Wind Harmer
1.518
942991AE2-321 GEN
Solar/Wind Harmer
5.137
274743AC1-111 GEN7
50/50
0.35
274745AC1-111 GEN9
50/50
6.398
276890AG1-513 C
50/50
0.502
274737AURORA EC;1P
50/50
1.024
957471AF2-041 GEN
Solar/Wind Harmer
39.452
959081AF2-199 GEN
Solar/Wind Harmer
13.151
971067AG2-660 GEN
Solar/Wind Harmer
3.058
960751AF2-366 GEN
Solar/Wind Harmer
2.767
962781AG1-127 GEN
Solar/Wind Harmer
9.173
274872LEEDK;1U
Solar/Wind Harmer
7.885
276861AD2-134 GEN
Solar/Wind Harmer
1.602
274857EASY ROAD;U1
Solar/Wind Harmer
3.385
274761LEE CO EC;2U
Adder
6.572
274766LEE CO EC;7U
Adder
6.494
972235AH1-702 GEN1
Adder
1.582
276158O29GEN2
Solar/Wind Harmer
3.058
274822ROCKFORD ;11
Adder
11.046
970819AG2-516 GEN
Solar/Wind Harmer
6.653
971475AH1-234 GEN
Solar/Wind Harmer
10.987
972029AH1-563 GEN
50/50
18.818
274746AC1-111 G10
50/50
6.398
274744AC1-111 GEN8
50/50
6.398
971171AH1-044 GEN
Solar/Wind Harmer
26.301
971675AH1-338 GEN
Solar/Wind Harmer
16.183
961011AF2-392 GEN
Solar/Wind Harmer
7.849
971681AH1-341 GEN
Solar/Wind Harmer
10.29
276612AE2-035 GEN
Solar/Wind Harmer
1.518
274823ROCKFORD ;21
Adder
10.969
946321AF1-296 GEN
Solar/Wind Harmer
5.753
971177AH1-047 GEN
Solar/Wind Harmer
3.083
971411AH1-196 GEN
Solar/Wind Harmer
7.549
NYPJM->LTFIMP_NY
CLTF
0.185
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.074
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.761
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.908
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.478
MECLTFEXP_MEC->PJM
CLTF
4.217
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.434
LAGNLTFEXP_LAGN->PJM
CLTF
0.979
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.199

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L12002__SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L12002__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.58 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1639.84
MW Contribution:5.95
Bus #Bus NameTypeMW Contribution
957471AF2-041 GEN
Solar/Wind Harmer
37.419
959081AF2-199 GEN
Solar/Wind Harmer
12.473
971067AG2-660 GEN
Solar/Wind Harmer
2.901
960751AF2-366 GEN
Solar/Wind Harmer
2.508
962781AG1-127 GEN
Solar/Wind Harmer
8.312
274872LEEDK;1U
Solar/Wind Harmer
7.157
276861AD2-134 GEN
Solar/Wind Harmer
1.459
274745AC1-111 GEN9
Adder
4.372
274857EASY ROAD;U1
Solar/Wind Harmer
3.107
274761LEE CO EC;2U
Adder
6.033
274766LEE CO EC;7U
Adder
5.962
276158O29GEN2
Solar/Wind Harmer
2.859
972235AH1-702 GEN1
Adder
1.411
274822ROCKFORD ;11
Adder
9.817
970819AG2-516 GEN
Solar/Wind Harmer
5.951
971475AH1-234 GEN
Solar/Wind Harmer
9.766
971171AH1-044 GEN
Solar/Wind Harmer
24.946
971675AH1-338 GEN
Solar/Wind Harmer
14.742
274746AC1-111 G10
Adder
4.372
274744AC1-111 GEN8
Adder
4.372
961011AF2-392 GEN
Solar/Wind Harmer
7.29
971681AH1-341 GEN
Solar/Wind Harmer
9.425
276612AE2-035 GEN
Solar/Wind Harmer
1.368
946321AF1-296 GEN
Solar/Wind Harmer
5.375
274823ROCKFORD ;21
Adder
9.748
971177AH1-047 GEN
Solar/Wind Harmer
2.679
971411AH1-196 GEN
Solar/Wind Harmer
6.602
274738AURORA EC;3P
50/50
1.494
274740AURORA EC;4P
50/50
1.494
971341AH1-150 GEN
Solar/Wind Harmer
24.946
971343AH1-151 GEN
Solar/Wind Harmer
24.946
962691AG1-118 GEN
Solar/Wind Harmer
28.02
971573AH1-285 GEN
Solar/Wind Harmer
7.517
970921AG2-575 GEN
Solar/Wind Harmer
8.74
970921AG2-575 GEN
Solar/Wind Harmer
2.033
972267AH1-718 GEN
Adder
2.943
276603SUBLETTE C
Solar/Wind Harmer
0.698
274764LEE CO EC;5U
Adder
6.047
274765LEE CO EC;6U
Adder
6.047
274762LEE CO EC;3U
Adder
6.033
274763LEE CO EC;4U
Adder
5.976
971333AH1-146 GEN
Solar/Wind Harmer
12.839
971335AH1-147 GEN
Solar/Wind Harmer
12.839
938861AE1-114 GEN
Solar/Wind Harmer
4.904
274695ROCKY RD ;2P
Adder
6.576
274693ROCKY RD ;1P
Adder
6.511
274697ROCKY RD ;3P
Adder
1.786
274696ROCKY RD ;4P
Adder
6.701
276741O09 GEN1
Solar/Wind Harmer
2.042
276708O09 GEN2
Solar/Wind Harmer
2.042
274856ECOGROVE ;U1
Solar/Wind Harmer
1.802
276611AD2-172 GEN
Solar/Wind Harmer
1.368
942991AE2-321 GEN
Solar/Wind Harmer
4.451
959091AF2-200 GEN
Solar/Wind Harmer
24.946
274872LEEDK;1U
Solar/Wind Harmer
0.223
943121AE2-341 GEN
Solar/Wind Harmer
13.029
943591AF1-030 GEN
Solar/Wind Harmer
8.686
276799AD1-013 GEN
Solar/Wind Harmer
1.816
946671AF1-331 GEN
Solar/Wind Harmer
0.344
274855GSG-6 ;RU
Solar/Wind Harmer
3.018
274850MENDOTA H;RU
Solar/Wind Harmer
2.098
276602WESTBROOK C
Solar/Wind Harmer
1.737
276863AD2-134 GEN
Solar/Wind Harmer
1.459
274858EASY ROAD;U2
Solar/Wind Harmer
3.107
274760LEE CO EC;1U
Adder
6.033
274767LEE CO EC;8U
Adder
5.962
276157O29GEN1
Solar/Wind Harmer
2.175
972236AH1-702 GEN2
Adder
1.224
970707AG2-453 GEN
Solar/Wind Harmer
14.525
965931AG1-462 GEN
Solar/Wind Harmer
12.977
NYPJM->LTFIMP_NY
CLTF
0.173
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.23
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.751
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.573
MECLTFEXP_MEC->PJM
CLTF
3.976
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.365
LAGNLTFEXP_LAGN->PJM
CLTF
0.995
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.222

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_120-38-TR82____SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-38-TR82____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.24 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1634.43
MW Contribution:6.02
Bus #Bus NameTypeMW Contribution
957471AF2-041 GEN
Solar/Wind Harmer
37.5
959081AF2-199 GEN
Solar/Wind Harmer
12.5
971067AG2-660 GEN
Solar/Wind Harmer
2.907
960751AF2-366 GEN
Solar/Wind Harmer
2.517
962781AG1-127 GEN
Solar/Wind Harmer
8.344
274872LEEDK;1U
Solar/Wind Harmer
7.183
276861AD2-134 GEN
Solar/Wind Harmer
1.466
274745AC1-111 GEN9
Adder
4.387
274857EASY ROAD;U1
Solar/Wind Harmer
3.13
274761LEE CO EC;2U
Adder
6.076
274766LEE CO EC;7U
Adder
6.004
276158O29GEN2
Solar/Wind Harmer
2.876
972235AH1-702 GEN1
Adder
1.425
274822ROCKFORD ;11
Adder
9.941
970819AG2-516 GEN
Solar/Wind Harmer
6.024
971475AH1-234 GEN
Solar/Wind Harmer
9.912
971171AH1-044 GEN
Solar/Wind Harmer
25
971675AH1-338 GEN
Solar/Wind Harmer
14.803
274746AC1-111 G10
Adder
4.387
274744AC1-111 GEN8
Adder
4.387
961011AF2-392 GEN
Solar/Wind Harmer
7.333
971681AH1-341 GEN
Solar/Wind Harmer
9.494
276612AE2-035 GEN
Solar/Wind Harmer
1.382
946321AF1-296 GEN
Solar/Wind Harmer
5.413
274823ROCKFORD ;21
Adder
9.871
971177AH1-047 GEN
Solar/Wind Harmer
2.721
971411AH1-196 GEN
Solar/Wind Harmer
6.711
274738AURORA EC;3P
50/50
1.496
274740AURORA EC;4P
50/50
1.496
971341AH1-150 GEN
Solar/Wind Harmer
25
971343AH1-151 GEN
Solar/Wind Harmer
25
962691AG1-118 GEN
Solar/Wind Harmer
28.113
970921AG2-575 GEN
Solar/Wind Harmer
8.774
970921AG2-575 GEN
Solar/Wind Harmer
2.04
971573AH1-285 GEN
Solar/Wind Harmer
7.535
972267AH1-718 GEN
Adder
2.959
276603SUBLETTE C
Solar/Wind Harmer
0.703
274764LEE CO EC;5U
Adder
6.09
274765LEE CO EC;6U
Adder
6.09
274762LEE CO EC;3U
Adder
6.076
274763LEE CO EC;4U
Adder
6.019
971333AH1-146 GEN
Solar/Wind Harmer
12.95
971335AH1-147 GEN
Solar/Wind Harmer
12.95
938861AE1-114 GEN
Solar/Wind Harmer
4.944
274695ROCKY RD ;2P
Adder
6.649
274693ROCKY RD ;1P
Adder
6.584
274697ROCKY RD ;3P
Adder
1.806
274696ROCKY RD ;4P
Adder
6.776
276741O09 GEN1
Solar/Wind Harmer
2.054
276708O09 GEN2
Solar/Wind Harmer
2.054
274856ECOGROVE ;U1
Solar/Wind Harmer
1.822
276611AD2-172 GEN
Solar/Wind Harmer
1.382
942991AE2-321 GEN
Solar/Wind Harmer
4.524
959091AF2-200 GEN
Solar/Wind Harmer
25
274872LEEDK;1U
Solar/Wind Harmer
0.224
943121AE2-341 GEN
Solar/Wind Harmer
13.055
943591AF1-030 GEN
Solar/Wind Harmer
8.703
276799AD1-013 GEN
Solar/Wind Harmer
1.823
946671AF1-331 GEN
Solar/Wind Harmer
0.345
274855GSG-6 ;RU
Solar/Wind Harmer
3.03
274850MENDOTA H;RU
Solar/Wind Harmer
2.107
276602WESTBROOK C
Solar/Wind Harmer
1.744
276863AD2-134 GEN
Solar/Wind Harmer
1.466
274858EASY ROAD;U2
Solar/Wind Harmer
3.13
274760LEE CO EC;1U
Adder
6.076
274767LEE CO EC;8U
Adder
6.004
276157O29GEN1
Solar/Wind Harmer
2.187
972236AH1-702 GEN2
Adder
1.237
970707AG2-453 GEN
Solar/Wind Harmer
14.537
965931AG1-462 GEN
Solar/Wind Harmer
13.068
NYPJM->LTFIMP_NY
CLTF
0.174
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.059
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.315
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
10.266
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.586
MECLTFEXP_MEC->PJM
CLTF
4.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.124
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.367
LAGNLTFEXP_LAGN->PJM
CLTF
1.011
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.227

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P2-2_120_LO-345R__2_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_120_LO-345R__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.22 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1634.13
MW Contribution:5.94
Bus #Bus NameTypeMW Contribution
959091AF2-200 GEN
Solar/Wind Harmer
24.938
274872LEEDK;1U
Solar/Wind Harmer
0.223
943121AE2-341 GEN
Solar/Wind Harmer
13.027
943591AF1-030 GEN
Solar/Wind Harmer
8.685
276799AD1-013 GEN
Solar/Wind Harmer
1.815
946671AF1-331 GEN
Solar/Wind Harmer
0.344
274855GSG-6 ;RU
Solar/Wind Harmer
3.016
274850MENDOTA H;RU
Solar/Wind Harmer
2.097
276602WESTBROOK C
Solar/Wind Harmer
1.736
276863AD2-134 GEN
Solar/Wind Harmer
1.459
274858EASY ROAD;U2
Solar/Wind Harmer
3.104
274760LEE CO EC;1U
Adder
6.026
274767LEE CO EC;8U
Adder
5.955
276157O29GEN1
Solar/Wind Harmer
2.173
972236AH1-702 GEN2
Adder
1.222
970707AG2-453 GEN
Solar/Wind Harmer
14.524
957471AF2-041 GEN
Solar/Wind Harmer
37.407
959081AF2-199 GEN
Solar/Wind Harmer
12.469
971067AG2-660 GEN
Solar/Wind Harmer
2.9
960751AF2-366 GEN
Solar/Wind Harmer
2.506
962781AG1-127 GEN
Solar/Wind Harmer
8.308
274872LEEDK;1U
Solar/Wind Harmer
7.153
276861AD2-134 GEN
Solar/Wind Harmer
1.459
274745AC1-111 GEN9
Adder
4.37
274857EASY ROAD;U1
Solar/Wind Harmer
3.104
274761LEE CO EC;2U
Adder
6.026
274766LEE CO EC;7U
Adder
5.955
276158O29GEN2
Solar/Wind Harmer
2.857
972235AH1-702 GEN1
Adder
1.409
274822ROCKFORD ;11
Adder
9.798
970819AG2-516 GEN
Solar/Wind Harmer
5.939
971475AH1-234 GEN
Solar/Wind Harmer
9.743
274738AURORA EC;3P
50/50
1.493
274740AURORA EC;4P
50/50
1.493
971341AH1-150 GEN
Solar/Wind Harmer
24.938
971343AH1-151 GEN
Solar/Wind Harmer
24.938
962691AG1-118 GEN
Solar/Wind Harmer
28.008
971573AH1-285 GEN
Solar/Wind Harmer
7.516
970921AG2-575 GEN
Solar/Wind Harmer
8.736
970921AG2-575 GEN
Solar/Wind Harmer
2.032
972267AH1-718 GEN
Adder
2.94
276603SUBLETTE C
Solar/Wind Harmer
0.698
274764LEE CO EC;5U
Adder
6.04
274765LEE CO EC;6U
Adder
6.04
274762LEE CO EC;3U
Adder
6.026
274763LEE CO EC;4U
Adder
5.969
971333AH1-146 GEN
Solar/Wind Harmer
12.822
971335AH1-147 GEN
Solar/Wind Harmer
12.822
938861AE1-114 GEN
Solar/Wind Harmer
4.898
274695ROCKY RD ;2P
Adder
6.565
274693ROCKY RD ;1P
Adder
6.5
274697ROCKY RD ;3P
Adder
1.783
274696ROCKY RD ;4P
Adder
6.689
276741O09 GEN1
Solar/Wind Harmer
2.041
276708O09 GEN2
Solar/Wind Harmer
2.041
274856ECOGROVE ;U1
Solar/Wind Harmer
1.8
276611AD2-172 GEN
Solar/Wind Harmer
1.365
942991AE2-321 GEN
Solar/Wind Harmer
4.439
965931AG1-462 GEN
Solar/Wind Harmer
12.963
971171AH1-044 GEN
Solar/Wind Harmer
24.938
971675AH1-338 GEN
Solar/Wind Harmer
14.733
274746AC1-111 G10
Adder
4.37
274744AC1-111 GEN8
Adder
4.37
961011AF2-392 GEN
Solar/Wind Harmer
7.284
971681AH1-341 GEN
Solar/Wind Harmer
9.414
276612AE2-035 GEN
Solar/Wind Harmer
1.365
946321AF1-296 GEN
Solar/Wind Harmer
5.369
274823ROCKFORD ;21
Adder
9.73
971177AH1-047 GEN
Solar/Wind Harmer
2.672
971411AH1-196 GEN
Solar/Wind Harmer
6.585
NYPJM->LTFIMP_NY
CLTF
0.172
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.216
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.571
MECLTFEXP_MEC->PJM
CLTF
3.967
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
0.992
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.222

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L10322__SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L10322__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.22 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1634.1
MW Contribution:5.94
Bus #Bus NameTypeMW Contribution
957471AF2-041 GEN
Solar/Wind Harmer
37.407
959081AF2-199 GEN
Solar/Wind Harmer
12.469
971067AG2-660 GEN
Solar/Wind Harmer
2.9
274738AURORA EC;3P
50/50
1.493
274740AURORA EC;4P
50/50
1.493
971341AH1-150 GEN
Solar/Wind Harmer
24.938
971343AH1-151 GEN
Solar/Wind Harmer
24.938
962691AG1-118 GEN
Solar/Wind Harmer
28.008
971573AH1-285 GEN
Solar/Wind Harmer
7.516
970921AG2-575 GEN
Solar/Wind Harmer
8.736
970921AG2-575 GEN
Solar/Wind Harmer
2.032
972267AH1-718 GEN
Adder
2.94
276603SUBLETTE C
Solar/Wind Harmer
0.698
274764LEE CO EC;5U
Adder
6.04
274765LEE CO EC;6U
Adder
6.04
274762LEE CO EC;3U
Adder
6.026
274763LEE CO EC;4U
Adder
5.969
971333AH1-146 GEN
Solar/Wind Harmer
12.822
971335AH1-147 GEN
Solar/Wind Harmer
12.822
938861AE1-114 GEN
Solar/Wind Harmer
4.898
274695ROCKY RD ;2P
Adder
6.565
274693ROCKY RD ;1P
Adder
6.5
274697ROCKY RD ;3P
Adder
1.783
274696ROCKY RD ;4P
Adder
6.689
276741O09 GEN1
Solar/Wind Harmer
2.041
276708O09 GEN2
Solar/Wind Harmer
2.041
274856ECOGROVE ;U1
Solar/Wind Harmer
1.8
276611AD2-172 GEN
Solar/Wind Harmer
1.365
942991AE2-321 GEN
Solar/Wind Harmer
4.439
960751AF2-366 GEN
Solar/Wind Harmer
2.506
962781AG1-127 GEN
Solar/Wind Harmer
8.308
274872LEEDK;1U
Solar/Wind Harmer
7.153
276861AD2-134 GEN
Solar/Wind Harmer
1.459
274745AC1-111 GEN9
Adder
4.37
274857EASY ROAD;U1
Solar/Wind Harmer
3.104
274761LEE CO EC;2U
Adder
6.026
274766LEE CO EC;7U
Adder
5.955
276158O29GEN2
Solar/Wind Harmer
2.857
972235AH1-702 GEN1
Adder
1.409
274822ROCKFORD ;11
Adder
9.798
970819AG2-516 GEN
Solar/Wind Harmer
5.939
971475AH1-234 GEN
Solar/Wind Harmer
9.743
971171AH1-044 GEN
Solar/Wind Harmer
24.938
971675AH1-338 GEN
Solar/Wind Harmer
14.733
274746AC1-111 G10
Adder
4.37
274744AC1-111 GEN8
Adder
4.37
961011AF2-392 GEN
Solar/Wind Harmer
7.284
971681AH1-341 GEN
Solar/Wind Harmer
9.414
276612AE2-035 GEN
Solar/Wind Harmer
1.365
946321AF1-296 GEN
Solar/Wind Harmer
5.369
274823ROCKFORD ;21
Adder
9.73
971177AH1-047 GEN
Solar/Wind Harmer
2.672
971411AH1-196 GEN
Solar/Wind Harmer
6.585
959091AF2-200 GEN
Solar/Wind Harmer
24.938
274872LEEDK;1U
Solar/Wind Harmer
0.223
943121AE2-341 GEN
Solar/Wind Harmer
13.027
943591AF1-030 GEN
Solar/Wind Harmer
8.685
276799AD1-013 GEN
Solar/Wind Harmer
1.815
946671AF1-331 GEN
Solar/Wind Harmer
0.344
274855GSG-6 ;RU
Solar/Wind Harmer
3.016
274850MENDOTA H;RU
Solar/Wind Harmer
2.097
276602WESTBROOK C
Solar/Wind Harmer
1.736
276863AD2-134 GEN
Solar/Wind Harmer
1.459
274858EASY ROAD;U2
Solar/Wind Harmer
3.104
274760LEE CO EC;1U
Adder
6.026
274767LEE CO EC;8U
Adder
5.955
276157O29GEN1
Solar/Wind Harmer
2.173
972236AH1-702 GEN2
Adder
1.222
970707AG2-453 GEN
Solar/Wind Harmer
14.524
965931AG1-462 GEN
Solar/Wind Harmer
12.963
NYPJM->LTFIMP_NY
CLTF
0.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.216
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.571
MECLTFEXP_MEC->PJM
CLTF
3.967
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
0.992
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.222

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P4_120-45-L11120__SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_120-45-L11120__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.21 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1633.94
MW Contribution:5.94
Bus #Bus NameTypeMW Contribution
959091AF2-200 GEN
Solar/Wind Harmer
24.938
274872LEEDK;1U
Solar/Wind Harmer
0.223
943121AE2-341 GEN
Solar/Wind Harmer
13.027
943591AF1-030 GEN
Solar/Wind Harmer
8.685
276799AD1-013 GEN
Solar/Wind Harmer
1.815
946671AF1-331 GEN
Solar/Wind Harmer
0.344
274855GSG-6 ;RU
Solar/Wind Harmer
3.016
274850MENDOTA H;RU
Solar/Wind Harmer
2.097
276602WESTBROOK C
Solar/Wind Harmer
1.736
276863AD2-134 GEN
Solar/Wind Harmer
1.459
274858EASY ROAD;U2
Solar/Wind Harmer
3.104
274760LEE CO EC;1U
Adder
6.026
274767LEE CO EC;8U
Adder
5.955
276157O29GEN1
Solar/Wind Harmer
2.173
972236AH1-702 GEN2
Adder
1.222
970707AG2-453 GEN
Solar/Wind Harmer
14.524
965931AG1-462 GEN
Solar/Wind Harmer
12.963
274738AURORA EC;3P
50/50
1.493
274740AURORA EC;4P
50/50
1.493
971341AH1-150 GEN
Solar/Wind Harmer
24.938
971343AH1-151 GEN
Solar/Wind Harmer
24.938
962691AG1-118 GEN
Solar/Wind Harmer
28.008
971573AH1-285 GEN
Solar/Wind Harmer
7.516
970921AG2-575 GEN
Solar/Wind Harmer
8.736
970921AG2-575 GEN
Solar/Wind Harmer
2.032
972267AH1-718 GEN
Adder
2.94
276603SUBLETTE C
Solar/Wind Harmer
0.698
274764LEE CO EC;5U
Adder
6.04
274765LEE CO EC;6U
Adder
6.04
274762LEE CO EC;3U
Adder
6.026
274763LEE CO EC;4U
Adder
5.969
971333AH1-146 GEN
Solar/Wind Harmer
12.822
971335AH1-147 GEN
Solar/Wind Harmer
12.822
938861AE1-114 GEN
Solar/Wind Harmer
4.898
274695ROCKY RD ;2P
Adder
6.565
274693ROCKY RD ;1P
Adder
6.5
274697ROCKY RD ;3P
Adder
1.783
274696ROCKY RD ;4P
Adder
6.689
276741O09 GEN1
Solar/Wind Harmer
2.041
276708O09 GEN2
Solar/Wind Harmer
2.041
274856ECOGROVE ;U1
Solar/Wind Harmer
1.8
276611AD2-172 GEN
Solar/Wind Harmer
1.365
942991AE2-321 GEN
Solar/Wind Harmer
4.439
957471AF2-041 GEN
Solar/Wind Harmer
37.407
959081AF2-199 GEN
Solar/Wind Harmer
12.469
971067AG2-660 GEN
Solar/Wind Harmer
2.9
960751AF2-366 GEN
Solar/Wind Harmer
2.506
962781AG1-127 GEN
Solar/Wind Harmer
8.308
274872LEEDK;1U
Solar/Wind Harmer
7.153
276861AD2-134 GEN
Solar/Wind Harmer
1.459
274745AC1-111 GEN9
Adder
4.37
274857EASY ROAD;U1
Solar/Wind Harmer
3.104
274761LEE CO EC;2U
Adder
6.026
274766LEE CO EC;7U
Adder
5.955
276158O29GEN2
Solar/Wind Harmer
2.857
972235AH1-702 GEN1
Adder
1.409
274822ROCKFORD ;11
Adder
9.798
970819AG2-516 GEN
Solar/Wind Harmer
5.939
971475AH1-234 GEN
Solar/Wind Harmer
9.743
971171AH1-044 GEN
Solar/Wind Harmer
24.938
971675AH1-338 GEN
Solar/Wind Harmer
14.733
274746AC1-111 G10
Adder
4.37
274744AC1-111 GEN8
Adder
4.37
961011AF2-392 GEN
Solar/Wind Harmer
7.284
971681AH1-341 GEN
Solar/Wind Harmer
9.414
276612AE2-035 GEN
Solar/Wind Harmer
1.365
946321AF1-296 GEN
Solar/Wind Harmer
5.369
274823ROCKFORD ;21
Adder
9.73
971177AH1-047 GEN
Solar/Wind Harmer
2.672
971411AH1-196 GEN
Solar/Wind Harmer
6.585
NYPJM->LTFIMP_NY
CLTF
0.172
CBM West 2LTFEXP_CBM-W2->PJM
CBM
5.216
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.028
CBM West 1LTFEXP_CBM-W1->PJM
CBM
9.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.571
MECLTFEXP_MEC->PJM
CLTF
3.967
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.123
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.364
LAGNLTFEXP_LAGN->PJM
CLTF
0.992
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.222

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345R__3_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345R__3_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.45 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1622.09
MW Contribution:5.28
Bus #Bus NameTypeMW Contribution
957471AF2-041 GEN
Solar/Wind Harmer
36.637
959081AF2-199 GEN
Solar/Wind Harmer
12.212
971067AG2-660 GEN
Solar/Wind Harmer
2.84
960751AF2-366 GEN
Solar/Wind Harmer
2.436
274738AURORA EC;3P
50/50
1.478
274740AURORA EC;4P
50/50
1.478
971341AH1-150 GEN
Solar/Wind Harmer
24.425
971343AH1-151 GEN
Solar/Wind Harmer
24.425
962691AG1-118 GEN
Solar/Wind Harmer
27.359
971573AH1-285 GEN
Solar/Wind Harmer
7.447
970921AG2-575 GEN
Solar/Wind Harmer
8.491
970921AG2-575 GEN
Solar/Wind Harmer
1.975
972267AH1-718 GEN
Adder
2.793
276603SUBLETTE C
Solar/Wind Harmer
0.66
274764LEE CO EC;5U
Adder
5.643
274765LEE CO EC;6U
Adder
5.643
274762LEE CO EC;3U
Adder
5.629
274763LEE CO EC;4U
Adder
5.576
971333AH1-146 GEN
Solar/Wind Harmer
11.752
971335AH1-147 GEN
Solar/Wind Harmer
11.752
938861AE1-114 GEN
Solar/Wind Harmer
4.538
276741O09 GEN1
Solar/Wind Harmer
1.933
276708O09 GEN2
Solar/Wind Harmer
1.933
274695ROCKY RD ;2P
Adder
5.892
274693ROCKY RD ;1P
Adder
5.834
274697ROCKY RD ;3P
Adder
1.601
274696ROCKY RD ;4P
Adder
5.998
274856ECOGROVE ;U1
Solar/Wind Harmer
1.626
276611AD2-172 GEN
Solar/Wind Harmer
1.234
971171AH1-044 GEN
Solar/Wind Harmer
24.425
274746AC1-111 G10
Adder
4.46
274744AC1-111 GEN8
Adder
4.46
971675AH1-338 GEN
Solar/Wind Harmer
14.255
961011AF2-392 GEN
Solar/Wind Harmer
6.901
971681AH1-341 GEN
Solar/Wind Harmer
8.795
276612AE2-035 GEN
Solar/Wind Harmer
1.234
946321AF1-296 GEN
Solar/Wind Harmer
5.022
274823ROCKFORD ;21
Adder
8.62
959091AF2-200 GEN
Solar/Wind Harmer
24.425
943121AE2-341 GEN
Solar/Wind Harmer
12.984
943591AF1-030 GEN
Solar/Wind Harmer
8.656
274872LEEDK;1U
Solar/Wind Harmer
0.217
276799AD1-013 GEN
Solar/Wind Harmer
1.756
946671AF1-331 GEN
Solar/Wind Harmer
0.333
274855GSG-6 ;RU
Solar/Wind Harmer
2.917
274850MENDOTA H;RU
Solar/Wind Harmer
2.029
276602WESTBROOK C
Solar/Wind Harmer
1.679
276863AD2-134 GEN
Solar/Wind Harmer
1.411
274858EASY ROAD;U2
Solar/Wind Harmer
2.9
274760LEE CO EC;1U
Adder
5.629
274767LEE CO EC;8U
Adder
5.563
276157O29GEN1
Solar/Wind Harmer
2.059
970707AG2-453 GEN
Solar/Wind Harmer
14.733
972236AH1-702 GEN2
Adder
1.104
965931AG1-462 GEN
Solar/Wind Harmer
12.131
962781AG1-127 GEN
Solar/Wind Harmer
8.075
274872LEEDK;1U
Solar/Wind Harmer
6.962
274745AC1-111 GEN9
Adder
4.46
276861AD2-134 GEN
Solar/Wind Harmer
1.411
274857EASY ROAD;U1
Solar/Wind Harmer
2.9
274761LEE CO EC;2U
Adder
5.629
274766LEE CO EC;7U
Adder
5.563
276158O29GEN2
Solar/Wind Harmer
2.706
972235AH1-702 GEN1
Adder
1.273
274822ROCKFORD ;11
Adder
8.68
970819AG2-516 GEN
Solar/Wind Harmer
5.278
NYPJM->LTFIMP_NY
CLTF
0.161
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.062
CBM West 2LTFEXP_CBM-W2->PJM
CBM
4.42
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.245
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.449
MECLTFEXP_MEC->PJM
CLTF
3.443
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.118
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.349
LAGNLTFEXP_LAGN->PJM
CLTF
0.838
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TVALTFEXP_TVA->PJM
CLTF
0.181

Details for ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line l/o COMED_P2-2_111_EJ-345B__2_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_111_EJ-345B__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:100.02 %
Rating:1568.0 MVA
Rating Type:STE
MVA to Mitigate:1568.24
MW Contribution:8.88
Bus #Bus NameTypeMW Contribution
274738AURORA EC;3P
50/50
2.447
274740AURORA EC;4P
50/50
2.447
971341AH1-150 GEN
Solar/Wind Harmer
60.513
971343AH1-151 GEN
Solar/Wind Harmer
60.513
972267AH1-718 GEN
Adder
6.122
962691AG1-118 GEN
Solar/Wind Harmer
40.175
276603SUBLETTE C
Solar/Wind Harmer
1.317
970921AG2-575 GEN
Solar/Wind Harmer
12.278
970921AG2-575 GEN
Solar/Wind Harmer
2.855
274764LEE CO EC;5U
Adder
11.095
274765LEE CO EC;6U
Adder
11.095
274762LEE CO EC;3U
Adder
11.069
274763LEE CO EC;4U
Adder
10.965
276741O09 GEN1
Solar/Wind Harmer
4.098
276708O09 GEN2
Solar/Wind Harmer
4.098
938861AE1-114 GEN
Solar/Wind Harmer
8.622
971573AH1-285 GEN
Solar/Wind Harmer
7.903
274856ECOGROVE ;U1
Solar/Wind Harmer
2.842
276611AD2-172 GEN
Solar/Wind Harmer
2.157
971333AH1-146 GEN
Solar/Wind Harmer
12.19
971335AH1-147 GEN
Solar/Wind Harmer
12.19
276782AC1-033 GEN
Solar/Wind Harmer
2.111
942991AE2-321 GEN
Solar/Wind Harmer
4.615
274851PROVIDENC;RU
Solar/Wind Harmer
1.234
274849CRESCENT ;1U
Solar/Wind Harmer
0.801
276645AC1-214 GEN1
Solar/Wind Harmer
0.581
276646AC1-214 GEN2
Solar/Wind Harmer
0.581
959091AF2-200 GEN
Solar/Wind Harmer
60.513
274855GSG-6 ;RU
Solar/Wind Harmer
4.608
274850MENDOTA H;RU
Solar/Wind Harmer
3.204
276602WESTBROOK C
Solar/Wind Harmer
2.653
276863AD2-134 GEN
Solar/Wind Harmer
2.229
276799AD1-013 GEN
Solar/Wind Harmer
2.758
946671AF1-331 GEN
Solar/Wind Harmer
0.522
274872LEEDK;1U
Solar/Wind Harmer
0.318
274858EASY ROAD;U2
Solar/Wind Harmer
5.701
274760LEE CO EC;1U
Adder
11.069
274767LEE CO EC;8U
Adder
10.939
276157O29GEN1
Solar/Wind Harmer
4.364
965931AG1-462 GEN
Solar/Wind Harmer
27.216
943121AE2-341 GEN
Solar/Wind Harmer
12.072
943591AF1-030 GEN
Solar/Wind Harmer
8.048
972236AH1-702 GEN2
Adder
1.668
274878BISHOP HL;2U
Solar/Wind Harmer
1.786
957471AF2-041 GEN
Solar/Wind Harmer
90.77
959081AF2-199 GEN
Solar/Wind Harmer
30.257
971067AG2-660 GEN
Solar/Wind Harmer
7.036
276861AD2-134 GEN
Solar/Wind Harmer
2.229
274872LEEDK;1U
Solar/Wind Harmer
10.223
960751AF2-366 GEN
Solar/Wind Harmer
3.523
962781AG1-127 GEN
Solar/Wind Harmer
11.676
274857EASY ROAD;U1
Solar/Wind Harmer
5.701
274761LEE CO EC;2U
Adder
11.069
274766LEE CO EC;7U
Adder
10.939
276158O29GEN2
Solar/Wind Harmer
5.737
972235AH1-702 GEN1
Adder
1.922
970819AG2-516 GEN
Solar/Wind Harmer
8.876
274822ROCKFORD ;11
Adder
13.465
971475AH1-234 GEN
Solar/Wind Harmer
14.381
274877BISHOP HL;1U
Solar/Wind Harmer
1.786
274745AC1-111 GEN9
Adder
2.656
971171AH1-044 GEN
Solar/Wind Harmer
60.513
961011AF2-392 GEN
Solar/Wind Harmer
14.518
971675AH1-338 GEN
Solar/Wind Harmer
22.455
971681AH1-341 GEN
Solar/Wind Harmer
16.675
946321AF1-296 GEN
Solar/Wind Harmer
11.102
276612AE2-035 GEN
Solar/Wind Harmer
2.157
274823ROCKFORD ;21
Adder
13.372
971411AH1-196 GEN
Solar/Wind Harmer
7.611
971177AH1-047 GEN
Solar/Wind Harmer
2.861
274746AC1-111 G10
Adder
2.656
274744AC1-111 GEN8
Adder
2.656
274848CAMPGROVE;RU
Solar/Wind Harmer
3.009
957751AF2-069 GEN
Solar/Wind Harmer
0.199
991092J1477
External Queue
3.8961522579193115
NYPJM->LTFIMP_NY
CLTF
0.212
WECLTFEXP_WEC->PJM
CLTF
0.479
CBM West 2LTFEXP_CBM-W2->PJM
CBM
13.935
CBM West 1LTFEXP_CBM-W1->PJM
CBM
33.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.07
MECLTFEXP_MEC->PJM
CLTF
8.898
SIGELTFEXP_SIGE->PJM
CLTF
0.005
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.112
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.307
LAGNLTFEXP_LAGN->PJM
CLTF
2.574
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.293
TVALTFEXP_TVA->PJM
CLTF
0.698

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4-6_116-345-R______SRT-A


Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4-6_116-345-R______SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.96 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2663.58
MW Contribution:10.07
Bus #Bus NameTypeMW Contribution
276642AD2-194 GEN2
50/50
7.617
276640AD2-194 GEN1
50/50
7.578
274728ELWOOD EC;5P
Adder
31.94
274731ELWOOD EC;2P
Adder
31.775
274733ELWOOD EC;3P
Adder
31.775
274735ELWOOD EC;4P
Adder
31.775
276868AE1-113 GEN
Solar/Wind Harmer
14.493
276882AE2-255 GEN
Solar/Wind Harmer
4.831
274675JOLIET 29;7U
Adder
40.394
274675JOLIET 29;7U
Adder
38.951
971177AH1-047 GEN
Solar/Wind Harmer
5.058
971411AH1-196 GEN
Solar/Wind Harmer
12.938
274823ROCKFORD ;21
Adder
16.448
274848CAMPGROVE;RU
Solar/Wind Harmer
5.429
276612AE2-035 GEN
Solar/Wind Harmer
2.138
971171AH1-044 GEN
Solar/Wind Harmer
16.558
971681AH1-341 GEN
Solar/Wind Harmer
12.318
961011AF2-392 GEN
Solar/Wind Harmer
8.856
274746AC1-111 G10
Adder
4.521
274744AC1-111 GEN8
Adder
4.521
946321AF1-296 GEN
Solar/Wind Harmer
8.29
957751AF2-069 GEN
Solar/Wind Harmer
0.364
971675AH1-338 GEN
Solar/Wind Harmer
14.051
926823AC1-168 GEN
Solar/Wind Harmer
2.675
970169AG2-114 GEN
Solar/Wind Harmer
5.593
960681AF2-359 GEN
Solar/Wind Helper
1.072
274732ELWOOD EC;7P
Adder
31.94
970569AG2-363 GEN
Solar/Wind Harmer
40.948
276876AE1-163_GEN2
Solar/Wind Harmer
9.066
274676JOLIET 29;8U
Adder
40.54
276691AA1-018 GEN1
Solar/Wind Harmer
0.611
971997AH1-543 GEN
Solar/Wind Harmer
18.463
274682WAUKEGAN ;7U
Adder
17.05
274828WAUKEGAN ;BP
Adder
10.455
276901AD2-066 C O1
Solar/Wind Harmer
3.151
274822ROCKFORD ;11
Adder
16.569
972235AH1-702 GEN1
Adder
2.121
971475AH1-234 GEN
Solar/Wind Harmer
18.844
970819AG2-516 GEN
Solar/Wind Harmer
10.075
957471AF2-041 GEN
Solar/Wind Harmer
24.838
959081AF2-199 GEN
Solar/Wind Harmer
8.279
971067AG2-660 GEN
Solar/Wind Harmer
1.925
274857EASY ROAD;U1
Solar/Wind Harmer
3.957
959351AF2-226 GEN
50/50
5.869
274861TOP CROP ;1U
Solar/Wind Harmer
15.293
274862TOP CROP ;2U
Solar/Wind Harmer
12.77
274879MINONK ;1U
Solar/Wind Harmer
9.663
276872AE1-163_GEN1
Solar/Wind Harmer
9.066
958491AF2-143 GEN
Solar/Wind Harmer
19.916
958481AF2-142 GEN
Solar/Wind Harmer
19.677
274683WAUKEGAN ;8U
Adder
19.946
274683WAUKEGAN ;8U
Adder
16.813
274696ROCKY RD ;4P
Adder
9.932
274695ROCKY RD ;2P
Adder
9.7
274693ROCKY RD ;1P
Adder
9.605
274697ROCKY RD ;3P
Adder
2.635
942991AE2-321 GEN
Solar/Wind Harmer
8.657
971333AH1-146 GEN
Solar/Wind Harmer
16.949
971335AH1-147 GEN
Solar/Wind Harmer
16.949
274856ECOGROVE ;U1
Solar/Wind Harmer
2.818
276611AD2-172 GEN
Solar/Wind Harmer
2.138
971341AH1-150 GEN
Solar/Wind Harmer
16.558
971343AH1-151 GEN
Solar/Wind Harmer
16.558
274764LEE CO EC;5U
Adder
7.7
274765LEE CO EC;6U
Adder
7.7
274762LEE CO EC;3U
Adder
7.681
274763LEE CO EC;4U
Adder
7.609
938861AE1-114 GEN
Solar/Wind Harmer
6.761
276782AC1-033 GEN
Solar/Wind Harmer
3.284
276741O09 GEN1
Solar/Wind Harmer
2.918
276708O09 GEN2
Solar/Wind Harmer
2.918
972267AH1-718 GEN
Adder
3.394
276603SUBLETTE C
Solar/Wind Harmer
0.853
274851PROVIDENC;RU
Solar/Wind Harmer
2.256
274849CRESCENT ;1U
Solar/Wind Harmer
1.465
276645AC1-214 GEN1
Solar/Wind Harmer
1.061
276646AC1-214 GEN2
Solar/Wind Harmer
1.061
970921AG2-575 GEN
Solar/Wind Harmer
7.725
970921AG2-575 GEN
Solar/Wind Harmer
1.797
962691AG1-118 GEN
Solar/Wind Harmer
23.144
971573AH1-285 GEN
Solar/Wind Harmer
5.91
960281AF2-319 GEN
50/50
5.869
274730ELWOOD EC;6P
Adder
31.94
274734ELWOOD EC;8P
Adder
31.94
274736ELWOOD EC;9P
Adder
31.94
274729ELWOOD EC;1P
Adder
31.775
970571AG2-364 GEN
Solar/Wind Harmer
27.299
276889AE2-281 GEN
Solar/Wind Harmer
2.59
276805AD2-038 GEN
Solar/Wind Harmer
6.811
274676JOLIET 29;8U
Adder
39.092
276694AA1-018 GEN2
Solar/Wind Harmer
8.278
274682WAUKEGAN ;7U
Adder
17.05
972236AH1-702 GEN2
Adder
1.845
959091AF2-200 GEN
Solar/Wind Harmer
16.558
274858EASY ROAD;U2
Solar/Wind Harmer
3.957
274760LEE CO EC;1U
Adder
7.681
274767LEE CO EC;8U
Adder
7.591
274878BISHOP HL;2U
Solar/Wind Harmer
2.78
276157O29GEN1
Solar/Wind Harmer
3.108
965931AG1-462 GEN
Solar/Wind Harmer
20.241
274855GSG-6 ;RU
Solar/Wind Harmer
2.885
274850MENDOTA H;RU
Solar/Wind Harmer
2.006
276602WESTBROOK C
Solar/Wind Harmer
1.661
276863AD2-134 GEN
Solar/Wind Harmer
1.395
276799AD1-013 GEN
Solar/Wind Harmer
1.725
946671AF1-331 GEN
Solar/Wind Harmer
0.327
274872LEEDK;1U
Solar/Wind Harmer
0.197
943121AE2-341 GEN
Solar/Wind Harmer
9.895
943591AF1-030 GEN
Solar/Wind Harmer
6.597
276893AG1-478 C
Solar/Wind Harmer
0.265
274761LEE CO EC;2U
Adder
7.681
274766LEE CO EC;7U
Adder
7.591
274877BISHOP HL;1U
Solar/Wind Harmer
2.78
276158O29GEN2
Solar/Wind Harmer
4.086
274745AC1-111 GEN9
Adder
4.521
276861AD2-134 GEN
Solar/Wind Harmer
1.395
960751AF2-366 GEN
Solar/Wind Harmer
2.216
962781AG1-127 GEN
Solar/Wind Harmer
7.347
274872LEEDK;1U
Solar/Wind Harmer
6.32
990512J1326
External Queue
4.515472412109375
991278J1725 G
External Queue
2.4823219776153564
990752J1383
External Queue
7.158767223358154
990117J1214
External Queue
15.533224105834961
990727J1377 G
External Queue
5.164198398590088
991092J1477
External Queue
2.687922477722168
991303J1755 G
External Queue
3.7893033027648926
991777J1629 G
External Queue
10.490921020507812
990407J1304
External Queue
3.4600954055786133
NYPJM->LTFIMP_NY
CLTF
0.615
WECLTFEXP_WEC->PJM
CLTF
3.382
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.162
CBM West 2LTFEXP_CBM-W2->PJM
CBM
24.722
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.065
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.641
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.782
MECLTFEXP_MEC->PJM
CLTF
10.846
SIGELTFEXP_SIGE->PJM
CLTF
0.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.303
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.852
LAGNLTFEXP_LAGN->PJM
CLTF
3.663
TVALTFEXP_TVA->PJM
CLTF
0.983

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L11614__SRT-A


Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L11614__SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.76 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2590.15
MW Contribution:8.52
Bus #Bus NameTypeMW Contribution
959351AF2-226 GEN
50/50
5.953
274861TOP CROP ;1U
Solar/Wind Harmer
15.513
274862TOP CROP ;2U
Solar/Wind Harmer
12.954
274879MINONK ;1U
Solar/Wind Harmer
9.271
276872AE1-163_GEN1
Solar/Wind Harmer
8.821
958491AF2-143 GEN
Solar/Wind Harmer
19.401
958481AF2-142 GEN
Solar/Wind Harmer
19.187
274683WAUKEGAN ;8U
Adder
16.204
274732ELWOOD EC;7P
Adder
31.429
970569AG2-363 GEN
Solar/Wind Harmer
39.804
276876AE1-163_GEN2
Solar/Wind Harmer
8.821
276691AA1-018 GEN1
Solar/Wind Harmer
0.596
971997AH1-543 GEN
Solar/Wind Harmer
17.345
274676JOLIET 29;8U
Adder
29.563
276901AD2-066 C O1
Solar/Wind Harmer
2.902
274682WAUKEGAN ;7U
Adder
13.837
274828WAUKEGAN ;BP
Adder
8.494
274877BISHOP HL;1U
Solar/Wind Harmer
2.562
276158O29GEN2
Solar/Wind Harmer
3.598
274822ROCKFORD ;11
Adder
13.973
972235AH1-702 GEN1
Adder
1.794
970819AG2-516 GEN
Solar/Wind Harmer
8.523
971475AH1-234 GEN
Solar/Wind Harmer
15.903
274857EASY ROAD;U1
Solar/Wind Harmer
3.391
274761LEE CO EC;2U
Adder
6.584
274766LEE CO EC;7U
Adder
6.506
957471AF2-041 GEN
Solar/Wind Harmer
21.191
959081AF2-199 GEN
Solar/Wind Harmer
7.064
971067AG2-660 GEN
Solar/Wind Harmer
1.643
274745AC1-111 GEN9
Adder
3.801
276861AD2-134 GEN
Solar/Wind Harmer
1.19
960751AF2-366 GEN
Solar/Wind Harmer
1.878
962781AG1-127 GEN
Solar/Wind Harmer
6.225
274872LEEDK;1U
Solar/Wind Harmer
5.367
972207SS24-0001
Solar/Wind Harmer
11.773
274773LINCOLN ;4U
Adder
3.311
274774LINCOLN ;5U
Adder
3.311
276642AD2-194 GEN2
50/50
7.495
276640AD2-194 GEN1
50/50
7.453
274728ELWOOD EC;5P
Adder
31.429
274731ELWOOD EC;2P
Adder
31.252
274733ELWOOD EC;3P
Adder
31.252
274735ELWOOD EC;4P
Adder
31.252
276868AE1-113 GEN
Solar/Wind Harmer
13.905
276882AE2-255 GEN
Solar/Wind Harmer
4.635
274675JOLIET 29;7U
Adder
29.338
274675JOLIET 29;7U
Adder
28.29
274848CAMPGROVE;RU
Solar/Wind Harmer
5.04
957751AF2-069 GEN
Solar/Wind Harmer
0.336
971411AH1-196 GEN
Solar/Wind Harmer
10.832
971177AH1-047 GEN
Solar/Wind Harmer
4.229
274823ROCKFORD ;21
Adder
13.872
276612AE2-035 GEN
Solar/Wind Harmer
1.815
971171AH1-044 GEN
Solar/Wind Harmer
14.127
961011AF2-392 GEN
Solar/Wind Harmer
7.668
971681AH1-341 GEN
Solar/Wind Harmer
10.565
946321AF1-296 GEN
Solar/Wind Harmer
7.274
274746AC1-111 G10
Adder
3.801
274744AC1-111 GEN8
Adder
3.801
971675AH1-338 GEN
Solar/Wind Harmer
11.984
926823AC1-168 GEN
Solar/Wind Harmer
2.479
970169AG2-114 GEN
Solar/Wind Harmer
5.435
274775LINCOLN ;6U
Adder
3.311
274776LINCOLN ;7U
Adder
3.311
274777LINCOLN ;8U
Adder
3.311
960681AF2-359 GEN
Solar/Wind Helper
1.028
960281AF2-319 GEN
50/50
5.953
274730ELWOOD EC;6P
Adder
31.429
274734ELWOOD EC;8P
Adder
31.429
274736ELWOOD EC;9P
Adder
31.429
274729ELWOOD EC;1P
Adder
31.252
970571AG2-364 GEN
Solar/Wind Harmer
26.536
274683WAUKEGAN ;8U
Adder
13.66
276782AC1-033 GEN
Solar/Wind Harmer
3.028
274851PROVIDENC;RU
Solar/Wind Harmer
2.085
274849CRESCENT ;1U
Solar/Wind Harmer
1.353
276645AC1-214 GEN1
Solar/Wind Harmer
0.981
276646AC1-214 GEN2
Solar/Wind Harmer
0.981
274696ROCKY RD ;4P
Adder
8.255
274695ROCKY RD ;2P
Adder
8.062
274693ROCKY RD ;1P
Adder
7.983
274697ROCKY RD ;3P
Adder
2.19
942991AE2-321 GEN
Solar/Wind Harmer
7.233
276741O09 GEN1
Solar/Wind Harmer
2.57
276708O09 GEN2
Solar/Wind Harmer
2.57
971333AH1-146 GEN
Solar/Wind Harmer
14.277
971335AH1-147 GEN
Solar/Wind Harmer
14.277
274856ECOGROVE ;U1
Solar/Wind Harmer
2.392
276611AD2-172 GEN
Solar/Wind Harmer
1.815
274764LEE CO EC;5U
Adder
6.6
274765LEE CO EC;6U
Adder
6.6
274762LEE CO EC;3U
Adder
6.584
274763LEE CO EC;4U
Adder
6.522
971341AH1-150 GEN
Solar/Wind Harmer
14.127
971343AH1-151 GEN
Solar/Wind Harmer
14.127
938861AE1-114 GEN
Solar/Wind Harmer
5.788
972267AH1-718 GEN
Adder
2.935
276603SUBLETTE C
Solar/Wind Harmer
0.737
970921AG2-575 GEN
Solar/Wind Harmer
6.546
970921AG2-575 GEN
Solar/Wind Harmer
1.522
962691AG1-118 GEN
Solar/Wind Harmer
19.604
971573AH1-285 GEN
Solar/Wind Harmer
5.011
274770LINCOLN ;1U
Adder
3.311
274771LINCOLN ;2U
Adder
3.311
276889AE2-281 GEN
Solar/Wind Harmer
2.52
276805AD2-038 GEN
Solar/Wind Harmer
6.635
276694AA1-018 GEN2
Solar/Wind Harmer
8.072
274676JOLIET 29;8U
Adder
28.507
274682WAUKEGAN ;7U
Adder
13.837
274878BISHOP HL;2U
Solar/Wind Harmer
2.562
276157O29GEN1
Solar/Wind Harmer
2.737
972236AH1-702 GEN2
Adder
1.56
274858EASY ROAD;U2
Solar/Wind Harmer
3.391
274760LEE CO EC;1U
Adder
6.584
274767LEE CO EC;8U
Adder
6.506
959091AF2-200 GEN
Solar/Wind Harmer
14.127
965931AG1-462 GEN
Solar/Wind Harmer
17.801
274855GSG-6 ;RU
Solar/Wind Harmer
2.461
274850MENDOTA H;RU
Solar/Wind Harmer
1.711
276602WESTBROOK C
Solar/Wind Harmer
1.417
276863AD2-134 GEN
Solar/Wind Harmer
1.19
276799AD1-013 GEN
Solar/Wind Harmer
1.471
946671AF1-331 GEN
Solar/Wind Harmer
0.278
274872LEEDK;1U
Solar/Wind Harmer
0.167
276893AG1-478 C
Solar/Wind Harmer
0.236
943121AE2-341 GEN
Solar/Wind Harmer
8.389
943591AF1-030 GEN
Solar/Wind Harmer
5.593
274772LINCOLN ;3U
Adder
3.311
990512J1326
External Queue
3.7746224403381348
991278J1725 G
External Queue
2.5369720458984375
990752J1383
External Queue
7.193099021911621
990117J1214
External Queue
12.984700202941895
990727J1377 G
External Queue
4.313429355621338
991303J1755 G
External Queue
3.670668125152588
991777J1629 G
External Queue
8.684924125671387
990407J1304
External Queue
2.875648260116577
NYPJM->LTFIMP_NY
CLTF
0.557
WECLTFEXP_WEC->PJM
CLTF
2.796
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.898
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.086
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.586
MECLTFEXP_MEC->PJM
CLTF
9.583
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.263
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.737
LAGNLTFEXP_LAGN->PJM
CLTF
3.328
TVALTFEXP_TVA->PJM
CLTF
0.908

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P2-2_116_GG-345R__2_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P2-2_116_GG-345R__2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.78 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2475.7
MW Contribution:8.55
Bus #Bus NameTypeMW Contribution
274732ELWOOD EC;7P
Adder
31.52
970569AG2-363 GEN
Solar/Wind Harmer
39.848
276876AE1-163_GEN2
Solar/Wind Harmer
8.832
276691AA1-018 GEN1
Solar/Wind Harmer
0.597
971997AH1-543 GEN
Solar/Wind Harmer
17.305
274676JOLIET 29;8U
Adder
30.023
276901AD2-066 C O1
Solar/Wind Harmer
2.92
274682WAUKEGAN ;7U
Adder
13.954
274828WAUKEGAN ;BP
Adder
8.565
274877BISHOP HL;1U
Solar/Wind Harmer
2.558
276158O29GEN2
Solar/Wind Harmer
3.6
274822ROCKFORD ;11
Adder
14.022
972235AH1-702 GEN1
Adder
1.8
970819AG2-516 GEN
Solar/Wind Harmer
8.551
971475AH1-234 GEN
Solar/Wind Harmer
15.959
274857EASY ROAD;U1
Solar/Wind Harmer
3.399
274761LEE CO EC;2U
Adder
6.599
274766LEE CO EC;7U
Adder
6.521
957471AF2-041 GEN
Solar/Wind Harmer
21.235
959081AF2-199 GEN
Solar/Wind Harmer
7.078
971067AG2-660 GEN
Solar/Wind Harmer
1.646
274745AC1-111 GEN9
Adder
3.81
276861AD2-134 GEN
Solar/Wind Harmer
1.192
960751AF2-366 GEN
Solar/Wind Harmer
1.881
962781AG1-127 GEN
Solar/Wind Harmer
6.236
274872LEEDK;1U
Solar/Wind Harmer
5.375
959351AF2-226 GEN
50/50
5.974
274861TOP CROP ;1U
Solar/Wind Harmer
15.566
274862TOP CROP ;2U
Solar/Wind Harmer
12.998
274879MINONK ;1U
Solar/Wind Harmer
9.299
276872AE1-163_GEN1
Solar/Wind Harmer
8.832
958491AF2-143 GEN
Solar/Wind Harmer
19.432
958481AF2-142 GEN
Solar/Wind Harmer
19.221
274683WAUKEGAN ;8U
Adder
16.34
274683WAUKEGAN ;8U
Adder
13.773
276782AC1-033 GEN
Solar/Wind Harmer
3.022
274851PROVIDENC;RU
Solar/Wind Harmer
2.08
274849CRESCENT ;1U
Solar/Wind Harmer
1.351
276645AC1-214 GEN1
Solar/Wind Harmer
0.979
276646AC1-214 GEN2
Solar/Wind Harmer
0.979
274696ROCKY RD ;4P
Adder
8.29
274695ROCKY RD ;2P
Adder
8.097
274693ROCKY RD ;1P
Adder
8.017
274697ROCKY RD ;3P
Adder
2.199
942991AE2-321 GEN
Solar/Wind Harmer
7.264
276741O09 GEN1
Solar/Wind Harmer
2.572
276708O09 GEN2
Solar/Wind Harmer
2.572
971333AH1-146 GEN
Solar/Wind Harmer
14.322
971335AH1-147 GEN
Solar/Wind Harmer
14.322
274856ECOGROVE ;U1
Solar/Wind Harmer
2.399
276611AD2-172 GEN
Solar/Wind Harmer
1.821
274764LEE CO EC;5U
Adder
6.614
274765LEE CO EC;6U
Adder
6.614
274762LEE CO EC;3U
Adder
6.599
274763LEE CO EC;4U
Adder
6.537
971341AH1-150 GEN
Solar/Wind Harmer
14.156
971343AH1-151 GEN
Solar/Wind Harmer
14.156
938861AE1-114 GEN
Solar/Wind Harmer
5.802
972267AH1-718 GEN
Adder
2.94
276603SUBLETTE C
Solar/Wind Harmer
0.738
970921AG2-575 GEN
Solar/Wind Harmer
6.557
970921AG2-575 GEN
Solar/Wind Harmer
1.525
962691AG1-118 GEN
Solar/Wind Harmer
19.64
971573AH1-285 GEN
Solar/Wind Harmer
5.006
960281AF2-319 GEN
50/50
5.974
274730ELWOOD EC;6P
Adder
31.52
274734ELWOOD EC;8P
Adder
31.52
274736ELWOOD EC;9P
Adder
31.52
274729ELWOOD EC;1P
Adder
31.341
970571AG2-364 GEN
Solar/Wind Harmer
26.565
276889AE2-281 GEN
Solar/Wind Harmer
2.524
276805AD2-038 GEN
Solar/Wind Harmer
6.646
276694AA1-018 GEN2
Solar/Wind Harmer
8.087
274676JOLIET 29;8U
Adder
28.951
274682WAUKEGAN ;7U
Adder
13.954
274878BISHOP HL;2U
Solar/Wind Harmer
2.558
276157O29GEN1
Solar/Wind Harmer
2.739
972236AH1-702 GEN2
Adder
1.565
274858EASY ROAD;U2
Solar/Wind Harmer
3.399
274760LEE CO EC;1U
Adder
6.599
274767LEE CO EC;8U
Adder
6.521
959091AF2-200 GEN
Solar/Wind Harmer
14.156
965931AG1-462 GEN
Solar/Wind Harmer
17.814
274855GSG-6 ;RU
Solar/Wind Harmer
2.465
274850MENDOTA H;RU
Solar/Wind Harmer
1.714
276602WESTBROOK C
Solar/Wind Harmer
1.419
276863AD2-134 GEN
Solar/Wind Harmer
1.192
276799AD1-013 GEN
Solar/Wind Harmer
1.473
946671AF1-331 GEN
Solar/Wind Harmer
0.279
274872LEEDK;1U
Solar/Wind Harmer
0.167
276893AG1-478 C
Solar/Wind Harmer
0.243
943121AE2-341 GEN
Solar/Wind Harmer
8.373
943591AF1-030 GEN
Solar/Wind Harmer
5.582
276642AD2-194 GEN2
50/50
7.517
276640AD2-194 GEN1
50/50
7.474
274728ELWOOD EC;5P
Adder
31.52
274731ELWOOD EC;2P
Adder
31.341
274733ELWOOD EC;3P
Adder
31.341
274735ELWOOD EC;4P
Adder
31.341
276868AE1-113 GEN
Solar/Wind Harmer
13.946
276882AE2-255 GEN
Solar/Wind Harmer
4.649
274675JOLIET 29;7U
Adder
29.799
274675JOLIET 29;7U
Adder
28.734
274848CAMPGROVE;RU
Solar/Wind Harmer
5.029
957751AF2-069 GEN
Solar/Wind Harmer
0.335
971411AH1-196 GEN
Solar/Wind Harmer
10.877
971177AH1-047 GEN
Solar/Wind Harmer
4.247
274823ROCKFORD ;21
Adder
13.92
276612AE2-035 GEN
Solar/Wind Harmer
1.821
971171AH1-044 GEN
Solar/Wind Harmer
14.156
961011AF2-392 GEN
Solar/Wind Harmer
7.68
971681AH1-341 GEN
Solar/Wind Harmer
10.588
946321AF1-296 GEN
Solar/Wind Harmer
7.28
274746AC1-111 G10
Adder
3.81
274744AC1-111 GEN8
Adder
3.81
971675AH1-338 GEN
Solar/Wind Harmer
12.003
926823AC1-168 GEN
Solar/Wind Harmer
2.467
970169AG2-114 GEN
Solar/Wind Harmer
5.202
960681AF2-359 GEN
Solar/Wind Helper
1.001
990512J1326
External Queue
3.78334903717041
991278J1725 G
External Queue
2.4970827102661133
990752J1383
External Queue
7.11613655090332
990117J1214
External Queue
13.01471996307373
990727J1377 G
External Queue
4.322795867919922
991303J1755 G
External Queue
3.644385576248169
991777J1629 G
External Queue
8.716980934143066
990407J1304
External Queue
2.883793592453003
NYPJM->LTFIMP_NY
CLTF
0.558
WECLTFEXP_WEC->PJM
CLTF
2.814
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.147
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.605
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.535
MECLTFEXP_MEC->PJM
CLTF
9.578
SIGELTFEXP_SIGE->PJM
CLTF
0.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.754
LAGNLTFEXP_LAGN->PJM
CLTF
3.297
TVALTFEXP_TVA->PJM
CLTF
0.893

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-TR82____SRT-A


Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-TR82____SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.77 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2475.59
MW Contribution:8.55
Bus #Bus NameTypeMW Contribution
960281AF2-319 GEN
50/50
5.974
274730ELWOOD EC;6P
Adder
31.52
274734ELWOOD EC;8P
Adder
31.52
274736ELWOOD EC;9P
Adder
31.52
274729ELWOOD EC;1P
Adder
31.341
970571AG2-364 GEN
Solar/Wind Harmer
26.565
276889AE2-281 GEN
Solar/Wind Harmer
2.524
276805AD2-038 GEN
Solar/Wind Harmer
6.646
276694AA1-018 GEN2
Solar/Wind Harmer
8.087
274676JOLIET 29;8U
Adder
28.951
274682WAUKEGAN ;7U
Adder
13.954
274878BISHOP HL;2U
Solar/Wind Harmer
2.558
276157O29GEN1
Solar/Wind Harmer
2.739
972236AH1-702 GEN2
Adder
1.565
274858EASY ROAD;U2
Solar/Wind Harmer
3.399
959351AF2-226 GEN
50/50
5.974
274861TOP CROP ;1U
Solar/Wind Harmer
15.566
274862TOP CROP ;2U
Solar/Wind Harmer
12.998
274879MINONK ;1U
Solar/Wind Harmer
9.299
276872AE1-163_GEN1
Solar/Wind Harmer
8.832
958491AF2-143 GEN
Solar/Wind Harmer
19.432
958481AF2-142 GEN
Solar/Wind Harmer
19.221
274683WAUKEGAN ;8U
Adder
16.34
274683WAUKEGAN ;8U
Adder
13.773
276782AC1-033 GEN
Solar/Wind Harmer
3.022
274851PROVIDENC;RU
Solar/Wind Harmer
2.08
274849CRESCENT ;1U
Solar/Wind Harmer
1.351
276645AC1-214 GEN1
Solar/Wind Harmer
0.979
276646AC1-214 GEN2
Solar/Wind Harmer
0.979
274696ROCKY RD ;4P
Adder
8.29
274695ROCKY RD ;2P
Adder
8.097
274693ROCKY RD ;1P
Adder
8.017
274697ROCKY RD ;3P
Adder
2.199
942991AE2-321 GEN
Solar/Wind Harmer
7.264
276741O09 GEN1
Solar/Wind Harmer
2.572
276708O09 GEN2
Solar/Wind Harmer
2.572
971333AH1-146 GEN
Solar/Wind Harmer
14.322
971335AH1-147 GEN
Solar/Wind Harmer
14.322
274856ECOGROVE ;U1
Solar/Wind Harmer
2.399
276611AD2-172 GEN
Solar/Wind Harmer
1.821
274764LEE CO EC;5U
Adder
6.614
274765LEE CO EC;6U
Adder
6.614
274762LEE CO EC;3U
Adder
6.599
274763LEE CO EC;4U
Adder
6.537
971341AH1-150 GEN
Solar/Wind Harmer
14.156
971343AH1-151 GEN
Solar/Wind Harmer
14.156
938861AE1-114 GEN
Solar/Wind Harmer
5.802
972267AH1-718 GEN
Adder
2.94
276603SUBLETTE C
Solar/Wind Harmer
0.738
970921AG2-575 GEN
Solar/Wind Harmer
6.557
970921AG2-575 GEN
Solar/Wind Harmer
1.525
962691AG1-118 GEN
Solar/Wind Harmer
19.64
971573AH1-285 GEN
Solar/Wind Harmer
5.006
274760LEE CO EC;1U
Adder
6.599
274767LEE CO EC;8U
Adder
6.521
959091AF2-200 GEN
Solar/Wind Harmer
14.156
965931AG1-462 GEN
Solar/Wind Harmer
17.814
274855GSG-6 ;RU
Solar/Wind Harmer
2.465
274850MENDOTA H;RU
Solar/Wind Harmer
1.714
276602WESTBROOK C
Solar/Wind Harmer
1.419
276863AD2-134 GEN
Solar/Wind Harmer
1.192
276799AD1-013 GEN
Solar/Wind Harmer
1.473
946671AF1-331 GEN
Solar/Wind Harmer
0.279
274872LEEDK;1U
Solar/Wind Harmer
0.167
276893AG1-478 C
Solar/Wind Harmer
0.243
943121AE2-341 GEN
Solar/Wind Harmer
8.373
943591AF1-030 GEN
Solar/Wind Harmer
5.582
274732ELWOOD EC;7P
Adder
31.52
970569AG2-363 GEN
Solar/Wind Harmer
39.848
276876AE1-163_GEN2
Solar/Wind Harmer
8.832
276691AA1-018 GEN1
Solar/Wind Harmer
0.597
971997AH1-543 GEN
Solar/Wind Harmer
17.305
274676JOLIET 29;8U
Adder
30.023
276901AD2-066 C O1
Solar/Wind Harmer
2.92
274682WAUKEGAN ;7U
Adder
13.954
274828WAUKEGAN ;BP
Adder
8.565
274877BISHOP HL;1U
Solar/Wind Harmer
2.558
276158O29GEN2
Solar/Wind Harmer
3.6
274822ROCKFORD ;11
Adder
14.022
972235AH1-702 GEN1
Adder
1.8
970819AG2-516 GEN
Solar/Wind Harmer
8.551
971475AH1-234 GEN
Solar/Wind Harmer
15.959
274857EASY ROAD;U1
Solar/Wind Harmer
3.399
274761LEE CO EC;2U
Adder
6.599
274766LEE CO EC;7U
Adder
6.521
957471AF2-041 GEN
Solar/Wind Harmer
21.235
959081AF2-199 GEN
Solar/Wind Harmer
7.078
971067AG2-660 GEN
Solar/Wind Harmer
1.646
274745AC1-111 GEN9
Adder
3.81
276861AD2-134 GEN
Solar/Wind Harmer
1.192
960751AF2-366 GEN
Solar/Wind Harmer
1.881
962781AG1-127 GEN
Solar/Wind Harmer
6.236
274872LEEDK;1U
Solar/Wind Harmer
5.375
276642AD2-194 GEN2
50/50
7.517
276640AD2-194 GEN1
50/50
7.474
274728ELWOOD EC;5P
Adder
31.52
274731ELWOOD EC;2P
Adder
31.341
274733ELWOOD EC;3P
Adder
31.341
274735ELWOOD EC;4P
Adder
31.341
276868AE1-113 GEN
Solar/Wind Harmer
13.946
276882AE2-255 GEN
Solar/Wind Harmer
4.649
274675JOLIET 29;7U
Adder
29.799
274675JOLIET 29;7U
Adder
28.734
274848CAMPGROVE;RU
Solar/Wind Harmer
5.029
957751AF2-069 GEN
Solar/Wind Harmer
0.335
971411AH1-196 GEN
Solar/Wind Harmer
10.877
971177AH1-047 GEN
Solar/Wind Harmer
4.247
274823ROCKFORD ;21
Adder
13.92
276612AE2-035 GEN
Solar/Wind Harmer
1.821
971171AH1-044 GEN
Solar/Wind Harmer
14.156
961011AF2-392 GEN
Solar/Wind Harmer
7.68
971681AH1-341 GEN
Solar/Wind Harmer
10.588
946321AF1-296 GEN
Solar/Wind Harmer
7.28
274746AC1-111 G10
Adder
3.81
274744AC1-111 GEN8
Adder
3.81
971675AH1-338 GEN
Solar/Wind Harmer
12.003
926823AC1-168 GEN
Solar/Wind Harmer
2.467
970169AG2-114 GEN
Solar/Wind Harmer
5.202
960681AF2-359 GEN
Solar/Wind Helper
1.001
990512J1326
External Queue
3.783348798751831
991278J1725 G
External Queue
2.497082471847534
990752J1383
External Queue
7.116136074066162
990117J1214
External Queue
13.014719009399414
990727J1377 G
External Queue
4.322795391082764
991303J1755 G
External Queue
3.644385576248169
991777J1629 G
External Queue
8.71697998046875
990407J1304
External Queue
2.883793354034424
NYPJM->LTFIMP_NY
CLTF
0.558
WECLTFEXP_WEC->PJM
CLTF
2.814
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.605
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.147
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.058
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.646
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.535
MECLTFEXP_MEC->PJM
CLTF
9.578
SIGELTFEXP_SIGE->PJM
CLTF
0.009
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.269
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.754
LAGNLTFEXP_LAGN->PJM
CLTF
3.297
TVALTFEXP_TVA->PJM
CLTF
0.893

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o COMED_P4_116-45-L0303___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_116-45-L0303___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.98 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2388.45
MW Contribution:8.56
Bus #Bus NameTypeMW Contribution
274732ELWOOD EC;7P
Adder
31.532
970569AG2-363 GEN
Solar/Wind Harmer
39.87
971997AH1-543 GEN
Solar/Wind Harmer
17.316
274676JOLIET 29;8U
Adder
30.046
276901AD2-066 C O1
Solar/Wind Harmer
2.922
274682WAUKEGAN ;7U
Adder
13.968
274828WAUKEGAN ;BP
Adder
8.573
274877BISHOP HL;1U
Solar/Wind Harmer
2.561
276158O29GEN2
Solar/Wind Harmer
3.604
274822ROCKFORD ;11
Adder
14.037
972235AH1-702 GEN1
Adder
1.802
970819AG2-516 GEN
Solar/Wind Harmer
8.56
971475AH1-234 GEN
Solar/Wind Harmer
15.976
274857EASY ROAD;U1
Solar/Wind Harmer
3.402
274761LEE CO EC;2U
Adder
6.606
274766LEE CO EC;7U
Adder
6.528
957471AF2-041 GEN
Solar/Wind Harmer
21.257
959081AF2-199 GEN
Solar/Wind Harmer
7.086
971067AG2-660 GEN
Solar/Wind Harmer
1.648
274745AC1-111 GEN9
Adder
3.814
276861AD2-134 GEN
Solar/Wind Harmer
1.193
960751AF2-366 GEN
Solar/Wind Harmer
1.883
962781AG1-127 GEN
Solar/Wind Harmer
6.243
274872LEEDK;1U
Solar/Wind Harmer
5.381
276642AD2-194 GEN2
50/50
7.52
276640AD2-194 GEN1
50/50
7.477
274728ELWOOD EC;5P
Adder
31.532
274731ELWOOD EC;2P
Adder
31.354
274733ELWOOD EC;3P
Adder
31.354
274735ELWOOD EC;4P
Adder
31.354
276868AE1-113 GEN
Solar/Wind Harmer
13.954
276882AE2-255 GEN
Solar/Wind Harmer
4.652
274675JOLIET 29;7U
Adder
29.821
274675JOLIET 29;7U
Adder
28.756
274848CAMPGROVE;RU
Solar/Wind Harmer
5.034
957751AF2-069 GEN
Solar/Wind Harmer
0.336
971411AH1-196 GEN
Solar/Wind Harmer
10.888
971177AH1-047 GEN
Solar/Wind Harmer
4.251
274823ROCKFORD ;21
Adder
13.935
276612AE2-035 GEN
Solar/Wind Harmer
1.823
971171AH1-044 GEN
Solar/Wind Harmer
14.171
961011AF2-392 GEN
Solar/Wind Harmer
7.688
971681AH1-341 GEN
Solar/Wind Harmer
10.599
946321AF1-296 GEN
Solar/Wind Harmer
7.288
274746AC1-111 G10
Adder
3.814
274744AC1-111 GEN8
Adder
3.814
971675AH1-338 GEN
Solar/Wind Harmer
12.017
926823AC1-168 GEN
Solar/Wind Harmer
2.47
970169AG2-114 GEN
Solar/Wind Harmer
5.209
960681AF2-359 GEN
Solar/Wind Helper
1
959351AF2-226 GEN
50/50
5.975
274861TOP CROP ;1U
Solar/Wind Harmer
15.57
274862TOP CROP ;2U
Solar/Wind Harmer
13.002
274879MINONK ;1U
Solar/Wind Harmer
9.304
274683WAUKEGAN ;8U
Adder
16.355
274683WAUKEGAN ;8U
Adder
13.787
276782AC1-033 GEN
Solar/Wind Harmer
3.025
274851PROVIDENC;RU
Solar/Wind Harmer
2.083
274849CRESCENT ;1U
Solar/Wind Harmer
1.352
276645AC1-214 GEN1
Solar/Wind Harmer
0.98
276646AC1-214 GEN2
Solar/Wind Harmer
0.98
274696ROCKY RD ;4P
Adder
8.298
274695ROCKY RD ;2P
Adder
8.105
274693ROCKY RD ;1P
Adder
8.025
274697ROCKY RD ;3P
Adder
2.202
942991AE2-321 GEN
Solar/Wind Harmer
7.271
276741O09 GEN1
Solar/Wind Harmer
2.574
276708O09 GEN2
Solar/Wind Harmer
2.574
971333AH1-146 GEN
Solar/Wind Harmer
14.337
971335AH1-147 GEN
Solar/Wind Harmer
14.337
274856ECOGROVE ;U1
Solar/Wind Harmer
2.402
276611AD2-172 GEN
Solar/Wind Harmer
1.823
274764LEE CO EC;5U
Adder
6.621
274765LEE CO EC;6U
Adder
6.621
274762LEE CO EC;3U
Adder
6.606
274763LEE CO EC;4U
Adder
6.543
971341AH1-150 GEN
Solar/Wind Harmer
14.171
971343AH1-151 GEN
Solar/Wind Harmer
14.171
938861AE1-114 GEN
Solar/Wind Harmer
5.808
972267AH1-718 GEN
Adder
2.943
276603SUBLETTE C
Solar/Wind Harmer
0.739
970921AG2-575 GEN
Solar/Wind Harmer
6.565
970921AG2-575 GEN
Solar/Wind Harmer
1.527
962691AG1-118 GEN
Solar/Wind Harmer
19.662
971573AH1-285 GEN
Solar/Wind Harmer
5.012
960281AF2-319 GEN
50/50
5.975
274730ELWOOD EC;6P
Adder
31.532
274734ELWOOD EC;8P
Adder
31.532
274736ELWOOD EC;9P
Adder
31.532
274729ELWOOD EC;1P
Adder
31.354
970571AG2-364 GEN
Solar/Wind Harmer
26.58
274676JOLIET 29;8U
Adder
28.973
274682WAUKEGAN ;7U
Adder
13.968
274878BISHOP HL;2U
Solar/Wind Harmer
2.561
276157O29GEN1
Solar/Wind Harmer
2.741
972236AH1-702 GEN2
Adder
1.567
274858EASY ROAD;U2
Solar/Wind Harmer
3.402
274760LEE CO EC;1U
Adder
6.606
274767LEE CO EC;8U
Adder
6.528
959091AF2-200 GEN
Solar/Wind Harmer
14.171
965931AG1-462 GEN
Solar/Wind Harmer
17.833
274855GSG-6 ;RU
Solar/Wind Harmer
2.468
274850MENDOTA H;RU
Solar/Wind Harmer
1.716
276602WESTBROOK C
Solar/Wind Harmer
1.42
276863AD2-134 GEN
Solar/Wind Harmer
1.193
276799AD1-013 GEN
Solar/Wind Harmer
1.475
946671AF1-331 GEN
Solar/Wind Harmer
0.279
274872LEEDK;1U
Solar/Wind Harmer
0.168
276893AG1-478 C
Solar/Wind Harmer
0.243
943121AE2-341 GEN
Solar/Wind Harmer
8.384
943591AF1-030 GEN
Solar/Wind Harmer
5.589
990512J1326
External Queue
3.78334903717041
991278J1725 G
External Queue
2.4970827102661133
990752J1383
External Queue
7.11613655090332
990117J1214
External Queue
13.01471996307373
990727J1377 G
External Queue
4.322795867919922
991303J1755 G
External Queue
3.644385576248169
991777J1629 G
External Queue
8.716980934143066
990407J1304
External Queue
2.883793592453003
NYPJM->LTFIMP_NY
CLTF
0.553
WECLTFEXP_WEC->PJM
CLTF
2.817
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.705
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.142
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
44.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.563
MECLTFEXP_MEC->PJM
CLTF
9.59
SIGELTFEXP_SIGE->PJM
CLTF
0.01
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.264
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.739
LAGNLTFEXP_LAGN->PJM
CLTF
3.312
TVALTFEXP_TVA->PJM
CLTF
0.901

Details for GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line l/o AEP_P4_#2978_05DUMONT 765_B_SRT-A


Base Case Flowgate

Area:CE
Facility Description:
GOODINGS ;4B-GOODINGS ;3B 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2978_05DUMONT 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:2297.0 MVA
Rating Type:STE
MVA to Mitigate:2364.12
MW Contribution:11.1
Bus #Bus NameTypeMW Contribution
274732ELWOOD EC;7P
Adder
26.12
274676JOLIET 29;8U
Adder
40.818
970569AG2-363 GEN
Solar/Wind Harmer
37.689
276642AD2-194 GEN2
50/50
6.229
276640AD2-194 GEN1
50/50
6.148
274728ELWOOD EC;5P
Adder
26.12
274731ELWOOD EC;2P
Adder
25.778
274733ELWOOD EC;3P
Adder
25.778
274735ELWOOD EC;4P
Adder
25.778
276868AE1-113 GEN
Solar/Wind Harmer
13.484
276882AE2-255 GEN
Solar/Wind Harmer
4.495
274675JOLIET 29;7U
Adder
40.618
274675JOLIET 29;7U
Adder
39.168
971177AH1-047 GEN
Solar/Wind Harmer
5.611
971411AH1-196 GEN
Solar/Wind Harmer
14.317
959351AF2-226 GEN
50/50
6.262
274861TOP CROP ;1U
Solar/Wind Harmer
16.318
274862TOP CROP ;2U
Solar/Wind Harmer
13.626
274879MINONK ;1U
Solar/Wind Harmer
8.99
276872AE1-163_GEN1
Solar/Wind Harmer
7.21
274683WAUKEGAN ;8U
Adder
21.972
274683WAUKEGAN ;8U
Adder
18.522
274696ROCKY RD ;4P
Adder
11.101
274695ROCKY RD ;2P
Adder
10.843
274693ROCKY RD ;1P
Adder
10.736
274697ROCKY RD ;3P
Adder
2.945
942991AE2-321 GEN
Solar/Wind Harmer
9.599
971333AH1-146 GEN
Solar/Wind Harmer
18.785
971335AH1-147 GEN
Solar/Wind Harmer
18.785
274856ECOGROVE ;U1
Solar/Wind Harmer
3.102
276611AD2-172 GEN
Solar/Wind Harmer
2.354
971341AH1-150 GEN
Solar/Wind Harmer
18.315
971343AH1-151 GEN
Solar/Wind Harmer
18.315
938861AE1-114 GEN
Solar/Wind Harmer
7.419
274764LEE CO EC;5U
Adder
8.422
274765LEE CO EC;6U
Adder
8.422
274762LEE CO EC;3U
Adder
8.402
274763LEE CO EC;4U
Adder
8.323
276603SUBLETTE C
Solar/Wind Harmer
0.934
962691AG1-118 GEN
Solar/Wind Harmer
26.703
970921AG2-575 GEN
Solar/Wind Harmer
8.896
970921AG2-575 GEN
Solar/Wind Harmer
2.069
972267AH1-718 GEN
Adder
3.692
276741O09 GEN1
Solar/Wind Harmer
3.139
276708O09 GEN2
Solar/Wind Harmer
3.139
276782AC1-033 GEN
Solar/Wind Harmer
3.418
971573AH1-285 GEN
Solar/Wind Harmer
7.209
274851PROVIDENC;RU
Solar/Wind Harmer
2.373
274849CRESCENT ;1U
Solar/Wind Harmer
1.54
276645AC1-214 GEN1
Solar/Wind Harmer
1.116
276646AC1-214 GEN2
Solar/Wind Harmer
1.116
958491AF2-143 GEN
Solar/Wind Harmer
12.109
274770LINCOLN ;1U
Adder
4.633
274771LINCOLN ;2U
Adder
4.633
958481AF2-142 GEN
Solar/Wind Harmer
9.228
274674JOLIET 9 ;6U
Adder
9.104
960611AF2-352 GEN
Solar/Wind Harmer
1.198
276763AC1-053 GEN1
Solar/Wind Harmer
1.859
276764AC1-053 GEN2
Solar/Wind Harmer
1.859
957381AF2-032 GEN
Solar/Wind Harmer
0.186
960281AF2-319 GEN
50/50
6.262
274730ELWOOD EC;6P
Adder
26.12
274734ELWOOD EC;8P
Adder
26.12
274736ELWOOD EC;9P
Adder
26.12
274729ELWOOD EC;1P
Adder
25.778
274676JOLIET 29;8U
Adder
39.36
970571AG2-364 GEN
Solar/Wind Harmer
25.126
276889AE2-281 GEN
Solar/Wind Harmer
2.06
274682WAUKEGAN ;7U
Adder
18.785
972236AH1-702 GEN2
Adder
2.034
959091AF2-200 GEN
Solar/Wind Harmer
18.315
274858EASY ROAD;U2
Solar/Wind Harmer
4.328
274760LEE CO EC;1U
Adder
8.402
274767LEE CO EC;8U
Adder
8.303
274855GSG-6 ;RU
Solar/Wind Harmer
3.275
274850MENDOTA H;RU
Solar/Wind Harmer
2.278
276602WESTBROOK C
Solar/Wind Harmer
1.885
276863AD2-134 GEN
Solar/Wind Harmer
1.584
276799AD1-013 GEN
Solar/Wind Harmer
1.96
946671AF1-331 GEN
Solar/Wind Harmer
0.371
274872LEEDK;1U
Solar/Wind Harmer
0.226
276157O29GEN1
Solar/Wind Harmer
3.343
274878BISHOP HL;2U
Solar/Wind Harmer
2.893
965931AG1-462 GEN
Solar/Wind Harmer
21.632
943121AE2-341 GEN
Solar/Wind Harmer
12.329
943591AF1-030 GEN
Solar/Wind Harmer
8.219
276805AD2-038 GEN
Solar/Wind Harmer
4.141
276893AG1-478 C
Solar/Wind Harmer
0.314
274772LINCOLN ;3U
Adder
4.633
276694AA1-018 GEN2
Solar/Wind Harmer
3.882
942111AE2-223 GEN
Solar/Wind Harmer
4.353
274853TWINGROVE;U1
Solar/Wind Harmer
3.713
965091AG1-374 GEN
Solar/Wind Harmer
15.453
959611AF2-252 GEN
Solar/Wind Harmer
1.198
276668AB2-070 GEN1
Solar/Wind Harmer
1.062
970707AG2-453 GEN
Solar/Wind Harmer
13.216
276621W2-048 GEN
Solar/Wind Harmer
2.908
276838X2-022 GEN2
Solar/Wind Harmer
0.108
276686W4-005 GEN3
Solar/Wind Harmer
1.408
971993AH1-541 GEN
Solar/Wind Harmer
4.3
942481AE2-261 GEN
Solar/Wind Harmer
13.113
274823ROCKFORD ;21
Adder
18.171
274746AC1-111 G10
Adder
5.178
274744AC1-111 GEN8
Adder
5.178
276612AE2-035 GEN
Solar/Wind Harmer
2.354
971171AH1-044 GEN
Solar/Wind Harmer
18.315
971681AH1-341 GEN
Solar/Wind Harmer
13.527
961011AF2-392 GEN
Solar/Wind Harmer
9.646
971675AH1-338 GEN
Solar/Wind Harmer
15.961
274848CAMPGROVE;RU
Solar/Wind Harmer
5.585
946321AF1-296 GEN
Solar/Wind Harmer
8.891
957751AF2-069 GEN
Solar/Wind Harmer
0.383
274775LINCOLN ;6U
Adder
4.633
274776LINCOLN ;7U
Adder
4.633
274777LINCOLN ;8U
Adder
4.633
926823AC1-168 GEN
Solar/Wind Harmer
3.053
970169AG2-114 GEN
Solar/Wind Harmer
6.471
276655WTG1_EQ
Solar/Wind Harmer
4.636
276656WTG2_EQ
Solar/Wind Harmer
0.614
959341AF2-225 GEN
Solar/Wind Harmer
7.964
941731AE2-173 GEN
Solar/Wind Harmer
3.087
276849AB2-070 GEN2
Solar/Wind Harmer
1.062
276848AB2-070 GEN3
Solar/Wind Harmer
1.062
276785W4-005 GEN1
Solar/Wind Harmer
1.408
276174W4-005 GEN2
Solar/Wind Harmer
1.408
274863CRW1-WTG
Solar/Wind Harmer
2.563
274864CRW2-WTG
Solar/Wind Harmer
2.563
970833AG2-524 GEN
Solar/Wind Harmer
3.816
970833AG2-524 GEN
Solar/Wind Harmer
1.775
960681AF2-359 GEN
Solar/Wind Helper
0.927
971997AH1-543 GEN
Solar/Wind Harmer
17.341
276876AE1-163_GEN2
Solar/Wind Harmer
7.21
274682WAUKEGAN ;7U
Adder
18.785
274828WAUKEGAN ;BP
Adder
11.518
274822ROCKFORD ;11
Adder
18.304
276901AD2-066 C O1
Solar/Wind Harmer
3.277
972235AH1-702 GEN1
Adder
2.339
274745AC1-111 GEN9
Adder
5.178
971475AH1-234 GEN
Solar/Wind Harmer
20.743
970819AG2-516 GEN
Solar/Wind Harmer
11.101
957471AF2-041 GEN
Solar/Wind Harmer
27.473
959081AF2-199 GEN
Solar/Wind Harmer
9.158
971067AG2-660 GEN
Solar/Wind Harmer
2.13
274857EASY ROAD;U1
Solar/Wind Harmer
4.328
274761LEE CO EC;2U
Adder
8.402
274766LEE CO EC;7U
Adder
8.303
960751AF2-366 GEN
Solar/Wind Harmer
2.552
962781AG1-127 GEN
Solar/Wind Harmer
8.461
276861AD2-134 GEN
Solar/Wind Harmer
1.584
274872LEEDK;1U
Solar/Wind Harmer
7.272
276158O29GEN2
Solar/Wind Harmer
4.395
274877BISHOP HL;1U
Solar/Wind Harmer
2.893
972207SS24-0001
Solar/Wind Harmer
16.471
274773LINCOLN ;4U
Adder
4.633
274774LINCOLN ;5U
Adder
4.633
276691AA1-018 GEN1
Solar/Wind Harmer
0.286
274674JOLIET 9 ;6U
Adder
9.104
276726Z2-087_GEN
Solar/Wind Harmer
4.199
939741AE1-205 GEN
Solar/Wind Harmer
10.619
274854TWINGROVE;U2
Solar/Wind Harmer
3.635
972175AH1-670 GEN
Solar/Wind Harmer
6.677
963831AG1-236 GEN
Solar/Wind Harmer
4.625
276615X2-022 GEN
Solar/Wind Harmer
0.913
274880W4-005 GEN4
Solar/Wind Harmer
1.408
965911AG1-460 GEN
Solar/Wind Harmer
0.612
990512J1326
External Queue
4.900748252868652
990752J1383
External Queue
6.595722198486328
990117J1214
External Queue
16.85857391357422
990727J1377 G
External Queue
5.630285739898682
991092J1477
External Queue
2.747962713241577
991303J1755 G
External Queue
3.8608200550079346
991777J1629 G
External Queue
11.35527229309082
990407J1304
External Queue
3.77290678024292
NYPJM->LTFIMP_NY
CLTF
0.705
WECLTFEXP_WEC->PJM
CLTF
3.711
CBM West 2LTFEXP_CBM-W2->PJM
CBM
27.318
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.192
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.078
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.305
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.136
MECLTFEXP_MEC->PJM
CLTF
11.571
SIGELTFEXP_SIGE->PJM
CLTF
0.017
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.261
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.715
LAGNLTFEXP_LAGN->PJM
CLTF
3.969
TVALTFEXP_TVA->PJM
CLTF
1.084

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.36 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1709.33
MW Contribution:9.22
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.144
274771LINCOLN ;2U
50/50
10.144
274660LASCO STA;1U
50/50
6.585
274661LASCO STA;2U
50/50
6.502
972259AH1-714 GEN
50/50
18.251
274888KELLY CRK;1U
Solar/Wind Harmer
5.386
274887GEN-1.85
Solar/Wind Harmer
4.863
276843GEN-1.7
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
13.137
274847GR RIDGE ;BU
Solar/Wind Harmer
4.414
274674JOLIET 9 ;6U
Adder
13.126
274803UNIV PARK;6U
Adder
4.863
958481AF2-142 GEN
Solar/Wind Harmer
12.415
971573AH1-285 GEN
Solar/Wind Harmer
7.114
274861TOP CROP ;1U
Solar/Wind Harmer
5.002
274862TOP CROP ;2U
Solar/Wind Harmer
4.177
274695ROCKY RD ;2P
Adder
9.128
274693ROCKY RD ;1P
Adder
9.038
274697ROCKY RD ;3P
Adder
2.48
274696ROCKY RD ;4P
Adder
9.343
274683WAUKEGAN ;8U
Adder
17.239
274683WAUKEGAN ;8U
Adder
14.531
962691AG1-118 GEN
Solar/Wind Harmer
24.231
958491AF2-143 GEN
Solar/Wind Harmer
12.102
970921AG2-575 GEN
Solar/Wind Harmer
8.042
970921AG2-575 GEN
Solar/Wind Harmer
1.87
942991AE2-321 GEN
Solar/Wind Harmer
7.961
274879MINONK ;1U
Solar/Wind Harmer
5.37
971333AH1-146 GEN
Solar/Wind Harmer
15.765
971335AH1-147 GEN
Solar/Wind Harmer
15.765
971341AH1-150 GEN
Solar/Wind Harmer
15.58
971343AH1-151 GEN
Solar/Wind Harmer
15.58
276872AE1-163_GEN1
Solar/Wind Harmer
5.225
274856ECOGROVE ;U1
Solar/Wind Harmer
2.582
276611AD2-172 GEN
Solar/Wind Harmer
1.959
938861AE1-114 GEN
Solar/Wind Harmer
6.198
274764LEE CO EC;5U
Adder
7.003
274765LEE CO EC;6U
Adder
7.003
274762LEE CO EC;3U
Adder
6.986
274763LEE CO EC;4U
Adder
6.92
276603SUBLETTE C
Solar/Wind Harmer
0.785
274808UNIV PK N;4U
Adder
3.73
972267AH1-718 GEN
Adder
3.068
276741O09 GEN1
Solar/Wind Harmer
2.616
276708O09 GEN2
Solar/Wind Harmer
2.616
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
276782AC1-033 GEN
Solar/Wind Harmer
2.854
960611AF2-352 GEN
Solar/Wind Harmer
1.623
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
957381AF2-032 GEN
Solar/Wind Harmer
0.199
274775LINCOLN ;6U
50/50
10.144
274776LINCOLN ;7U
50/50
10.144
274777LINCOLN ;8U
50/50
10.144
972227AH1-698 GEN1
50/50
2.589
274687WILL CNTY;4U
50/50
25.533
274687WILL CNTY;4U
50/50
25.533
274863CRW1-WTG
Solar/Wind Harmer
5.114
274864CRW2-WTG
Solar/Wind Harmer
5.114
960591AF2-350 GEN
Solar/Wind Harmer
9.123
970833AG2-524 GEN
Solar/Wind Harmer
7.585
970833AG2-524 GEN
Solar/Wind Harmer
3.528
274827FISK ;RP
Adder
6.662
274675JOLIET 29;7U
Adder
26.336
274675JOLIET 29;7U
Adder
25.395
274731ELWOOD EC;2P
Adder
14.096
274773LINCOLN ;4U
50/50
10.144
274774LINCOLN ;5U
50/50
10.144
274655BRAIDWOOD;2U
50/50
6.709
972207SS24-0001
Solar/Wind Harmer
33.99
941551AE2-152 GEN
Solar/Wind Harmer
4.841
939401AE1-172 GEN
Solar/Wind Harmer
13.646
276776AD2-060 GEN
Solar/Wind Harmer
0.386
274871GR RIDGE ;2U
Solar/Wind Harmer
6.71
276164X3-005 C
Solar/Wind Harmer
0.608
274801UNIV PARK;4U
Adder
5.005
274676JOLIET 29;8U
Adder
26.335
274732ELWOOD EC;7P
Adder
14.096
274674JOLIET 9 ;6U
Adder
13.126
274745AC1-111 GEN9
Adder
4.669
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.735
274828WAUKEGAN ;BP
Adder
9.036
960751AF2-366 GEN
Solar/Wind Harmer
2.307
962781AG1-127 GEN
Solar/Wind Harmer
7.648
276901AD2-066 C O1
Solar/Wind Harmer
2.814
274872LEEDK;1U
Solar/Wind Harmer
6.578
971997AH1-543 GEN
Solar/Wind Harmer
12.448
276861AD2-134 GEN
Solar/Wind Harmer
1.406
957471AF2-041 GEN
Solar/Wind Harmer
23.37
959081AF2-199 GEN
Solar/Wind Harmer
7.79
971067AG2-660 GEN
Solar/Wind Harmer
1.812
276876AE1-163_GEN2
Solar/Wind Harmer
5.225
274723RIVER EC ;12
Adder
13.916
274822ROCKFORD ;11
Adder
15.226
972235AH1-702 GEN1
Adder
1.947
970819AG2-516 GEN
Solar/Wind Harmer
9.216
971475AH1-234 GEN
Solar/Wind Harmer
17.128
970569AG2-363 GEN
Solar/Wind Harmer
22.74
274857EASY ROAD;U1
Solar/Wind Harmer
3.599
274733ELWOOD EC;3P
Adder
14.096
274735ELWOOD EC;4P
Adder
14.096
274728ELWOOD EC;5P
Adder
14.096
274746AC1-111 G10
Adder
4.669
274744AC1-111 GEN8
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.092
276868AE1-113 GEN
Solar/Wind Harmer
8.054
276882AE2-255 GEN
Solar/Wind Harmer
2.685
971177AH1-047 GEN
Solar/Wind Harmer
4.661
971411AH1-196 GEN
Solar/Wind Harmer
11.848
971675AH1-338 GEN
Solar/Wind Harmer
14.175
971171AH1-044 GEN
Solar/Wind Harmer
15.58
274823ROCKFORD ;21
Adder
15.116
276612AE2-035 GEN
Solar/Wind Harmer
1.959
926823AC1-168 GEN
Solar/Wind Harmer
3.278
971681AH1-341 GEN
Solar/Wind Harmer
11.345
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274805UNIV PK N;1U
Adder
3.754
274811UNIV PK N;7U
Adder
3.746
961011AF2-392 GEN
Solar/Wind Harmer
8.052
276655WTG1_EQ
Solar/Wind Harmer
6.416
276656WTG2_EQ
Solar/Wind Harmer
0.85
959341AF2-225 GEN
Solar/Wind Harmer
11.023
941731AE2-173 GEN
Solar/Wind Harmer
4.273
957751AF2-069 GEN
Solar/Wind Harmer
0.332
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
946321AF1-296 GEN
Solar/Wind Harmer
7.279
276785W4-005 GEN1
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276849AB2-070 GEN2
Solar/Wind Harmer
1.253
276848AB2-070 GEN3
Solar/Wind Harmer
1.253
274772LINCOLN ;3U
50/50
10.144
274654BRAIDWOOD;1U
50/50
7.139
972228AH1-698 GEN2
50/50
3.673
276897AD1-100 C
Solar/Wind Harmer
30.978
939351AE1-166 GEN
Solar/Wind Harmer
6.33
276772AC2-154 GEN
Solar/Wind Harmer
2.544
276806AD2-047 C O1
Solar/Wind Harmer
9.759
970941AG2-585 GEN
Solar/Wind Harmer
11.403
970707AG2-453 GEN
Solar/Wind Harmer
24.504
276893AG1-478 C
Solar/Wind Harmer
0.363
274826FISK ;BP
Adder
9.4
274800UNIV PARK;3U
Adder
5.005
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.395
274729ELWOOD EC;1P
Adder
14.096
274730ELWOOD EC;6P
Adder
14.096
274734ELWOOD EC;8P
Adder
14.096
274736ELWOOD EC;9P
Adder
14.096
943121AE2-341 GEN
Solar/Wind Harmer
12.521
943591AF1-030 GEN
Solar/Wind Harmer
8.348
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
274682WAUKEGAN ;7U
Adder
14.735
276805AD2-038 GEN
Solar/Wind Harmer
4.139
274872LEEDK;1U
Solar/Wind Harmer
0.205
276799AD1-013 GEN
Solar/Wind Harmer
1.742
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
276863AD2-134 GEN
Solar/Wind Harmer
1.406
274724RIVER EC ;11
Adder
13.808
959091AF2-200 GEN
Solar/Wind Harmer
15.58
276889AE2-281 GEN
Solar/Wind Harmer
1.493
972236AH1-702 GEN2
Adder
1.693
970571AG2-364 GEN
Solar/Wind Harmer
15.16
274858EASY ROAD;U2
Solar/Wind Harmer
3.599
274760LEE CO EC;1U
Adder
6.986
274767LEE CO EC;8U
Adder
6.904
942111AE2-223 GEN
Solar/Wind Harmer
6.024
276157O29GEN1
Solar/Wind Harmer
2.785
274878BISHOP HL;2U
Solar/Wind Harmer
2.415
274853TWINGROVE;U1
Solar/Wind Harmer
5.03
965091AG1-374 GEN
Solar/Wind Harmer
20.937
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.6
972231SS25-0005
Solar/Wind Harmer
6.138
972181SS23-001
Solar/Wind Harmer
3.836
274752CRETE EC ;2U
Adder
3.161
274753CRETE EC ;3U
Adder
3.161
276686W4-005 GEN3
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.184
276668AB2-070 GEN1
Solar/Wind Harmer
1.253
276621W2-048 GEN
Solar/Wind Harmer
3.298
276838X2-022 GEN2
Solar/Wind Harmer
0.123
942481AE2-261 GEN
Solar/Wind Harmer
5.353
274761LEE CO EC;2U
Adder
6.986
274766LEE CO EC;7U
Adder
6.904
274812UNIV PK N;8U
Adder
3.746
276726Z2-087_GEN
Solar/Wind Harmer
5.812
939741AE1-205 GEN
Solar/Wind Harmer
14.698
276158O29GEN2
Solar/Wind Harmer
3.662
274877BISHOP HL;1U
Solar/Wind Harmer
2.415
274854TWINGROVE;U2
Solar/Wind Harmer
4.925
274751CRETE EC ;1U
Adder
3.161
274754CRETE EC ;4U
Adder
3.161
972175AH1-670 GEN
Solar/Wind Harmer
8.543
274880W4-005 GEN4
Solar/Wind Harmer
1.697
963831AG1-236 GEN
Solar/Wind Harmer
5.391
276615X2-022 GEN
Solar/Wind Harmer
1.035
965911AG1-460 GEN
Solar/Wind Harmer
0.25
990512J1326
External Queue
3.7948038578033447
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
9.38
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.959
LAGNLTFEXP_LAGN->PJM
CLTF
3.176
TVALTFEXP_TVA->PJM
CLTF
0.822

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.09 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1690.72
MW Contribution:9.22
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.144
274771LINCOLN ;2U
50/50
10.144
274775LINCOLN ;6U
50/50
10.144
274776LINCOLN ;7U
50/50
10.144
274777LINCOLN ;8U
50/50
10.144
972227AH1-698 GEN1
50/50
2.589
274687WILL CNTY;4U
50/50
25.533
274687WILL CNTY;4U
50/50
25.533
274660LASCO STA;1U
50/50
6.585
274661LASCO STA;2U
50/50
6.502
972259AH1-714 GEN
50/50
18.251
274888KELLY CRK;1U
Solar/Wind Harmer
5.386
274887GEN-1.85
Solar/Wind Harmer
4.863
276843GEN-1.7
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
13.137
274847GR RIDGE ;BU
Solar/Wind Harmer
4.414
274674JOLIET 9 ;6U
Adder
13.126
274803UNIV PARK;6U
Adder
4.863
958481AF2-142 GEN
Solar/Wind Harmer
12.415
971573AH1-285 GEN
Solar/Wind Harmer
7.114
274861TOP CROP ;1U
Solar/Wind Harmer
5.002
274862TOP CROP ;2U
Solar/Wind Harmer
4.177
274695ROCKY RD ;2P
Adder
9.128
274693ROCKY RD ;1P
Adder
9.038
274697ROCKY RD ;3P
Adder
2.48
274696ROCKY RD ;4P
Adder
9.343
274683WAUKEGAN ;8U
Adder
17.239
274683WAUKEGAN ;8U
Adder
14.531
962691AG1-118 GEN
Solar/Wind Harmer
24.231
958491AF2-143 GEN
Solar/Wind Harmer
12.102
970921AG2-575 GEN
Solar/Wind Harmer
8.042
970921AG2-575 GEN
Solar/Wind Harmer
1.87
942991AE2-321 GEN
Solar/Wind Harmer
7.961
274879MINONK ;1U
Solar/Wind Harmer
5.37
971333AH1-146 GEN
Solar/Wind Harmer
15.765
971335AH1-147 GEN
Solar/Wind Harmer
15.765
971341AH1-150 GEN
Solar/Wind Harmer
15.58
971343AH1-151 GEN
Solar/Wind Harmer
15.58
276872AE1-163_GEN1
Solar/Wind Harmer
5.225
274856ECOGROVE ;U1
Solar/Wind Harmer
2.582
276611AD2-172 GEN
Solar/Wind Harmer
1.959
938861AE1-114 GEN
Solar/Wind Harmer
6.198
274764LEE CO EC;5U
Adder
7.003
274765LEE CO EC;6U
Adder
7.003
274762LEE CO EC;3U
Adder
6.986
274763LEE CO EC;4U
Adder
6.92
276603SUBLETTE C
Solar/Wind Harmer
0.785
274808UNIV PK N;4U
Adder
3.73
972267AH1-718 GEN
Adder
3.068
276741O09 GEN1
Solar/Wind Harmer
2.616
276708O09 GEN2
Solar/Wind Harmer
2.616
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
276782AC1-033 GEN
Solar/Wind Harmer
2.854
960611AF2-352 GEN
Solar/Wind Harmer
1.623
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
957381AF2-032 GEN
Solar/Wind Harmer
0.199
274863CRW1-WTG
Solar/Wind Harmer
5.114
274864CRW2-WTG
Solar/Wind Harmer
5.114
960591AF2-350 GEN
Solar/Wind Harmer
9.123
970833AG2-524 GEN
Solar/Wind Harmer
7.585
970833AG2-524 GEN
Solar/Wind Harmer
3.528
274827FISK ;RP
Adder
6.662
274675JOLIET 29;7U
Adder
26.336
274675JOLIET 29;7U
Adder
25.395
274731ELWOOD EC;2P
Adder
14.096
274733ELWOOD EC;3P
Adder
14.096
274735ELWOOD EC;4P
Adder
14.096
274728ELWOOD EC;5P
Adder
14.096
274746AC1-111 G10
Adder
4.669
274744AC1-111 GEN8
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.092
276868AE1-113 GEN
Solar/Wind Harmer
8.054
276882AE2-255 GEN
Solar/Wind Harmer
2.685
971177AH1-047 GEN
Solar/Wind Harmer
4.661
971411AH1-196 GEN
Solar/Wind Harmer
11.848
971675AH1-338 GEN
Solar/Wind Harmer
14.175
971171AH1-044 GEN
Solar/Wind Harmer
15.58
274823ROCKFORD ;21
Adder
15.116
276612AE2-035 GEN
Solar/Wind Harmer
1.959
926823AC1-168 GEN
Solar/Wind Harmer
3.278
971681AH1-341 GEN
Solar/Wind Harmer
11.345
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274805UNIV PK N;1U
Adder
3.754
274811UNIV PK N;7U
Adder
3.746
961011AF2-392 GEN
Solar/Wind Harmer
8.052
276655WTG1_EQ
Solar/Wind Harmer
6.416
276656WTG2_EQ
Solar/Wind Harmer
0.85
959341AF2-225 GEN
Solar/Wind Harmer
11.023
941731AE2-173 GEN
Solar/Wind Harmer
4.273
957751AF2-069 GEN
Solar/Wind Harmer
0.332
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
946321AF1-296 GEN
Solar/Wind Harmer
7.279
276785W4-005 GEN1
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276849AB2-070 GEN2
Solar/Wind Harmer
1.253
276848AB2-070 GEN3
Solar/Wind Harmer
1.253
274772LINCOLN ;3U
50/50
10.144
274654BRAIDWOOD;1U
50/50
7.139
972228AH1-698 GEN2
50/50
3.673
276897AD1-100 C
Solar/Wind Harmer
30.978
939351AE1-166 GEN
Solar/Wind Harmer
6.33
276772AC2-154 GEN
Solar/Wind Harmer
2.544
276806AD2-047 C O1
Solar/Wind Harmer
9.759
970941AG2-585 GEN
Solar/Wind Harmer
11.403
970707AG2-453 GEN
Solar/Wind Harmer
24.504
276893AG1-478 C
Solar/Wind Harmer
0.363
274826FISK ;BP
Adder
9.4
274800UNIV PARK;3U
Adder
5.005
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.395
274729ELWOOD EC;1P
Adder
14.096
274730ELWOOD EC;6P
Adder
14.096
274734ELWOOD EC;8P
Adder
14.096
274736ELWOOD EC;9P
Adder
14.096
274773LINCOLN ;4U
50/50
10.144
274774LINCOLN ;5U
50/50
10.144
274655BRAIDWOOD;2U
50/50
6.709
972207SS24-0001
Solar/Wind Harmer
33.99
941551AE2-152 GEN
Solar/Wind Harmer
4.841
939401AE1-172 GEN
Solar/Wind Harmer
13.646
276776AD2-060 GEN
Solar/Wind Harmer
0.386
274871GR RIDGE ;2U
Solar/Wind Harmer
6.71
276164X3-005 C
Solar/Wind Harmer
0.608
274801UNIV PARK;4U
Adder
5.005
274676JOLIET 29;8U
Adder
26.335
274732ELWOOD EC;7P
Adder
14.096
274674JOLIET 9 ;6U
Adder
13.126
274745AC1-111 GEN9
Adder
4.669
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.735
274828WAUKEGAN ;BP
Adder
9.036
960751AF2-366 GEN
Solar/Wind Harmer
2.307
962781AG1-127 GEN
Solar/Wind Harmer
7.648
276901AD2-066 C O1
Solar/Wind Harmer
2.814
274872LEEDK;1U
Solar/Wind Harmer
6.578
971997AH1-543 GEN
Solar/Wind Harmer
12.448
276861AD2-134 GEN
Solar/Wind Harmer
1.406
957471AF2-041 GEN
Solar/Wind Harmer
23.37
959081AF2-199 GEN
Solar/Wind Harmer
7.79
971067AG2-660 GEN
Solar/Wind Harmer
1.812
276876AE1-163_GEN2
Solar/Wind Harmer
5.225
274723RIVER EC ;12
Adder
13.916
274822ROCKFORD ;11
Adder
15.226
972235AH1-702 GEN1
Adder
1.947
970819AG2-516 GEN
Solar/Wind Harmer
9.216
971475AH1-234 GEN
Solar/Wind Harmer
17.128
970569AG2-363 GEN
Solar/Wind Harmer
22.74
274857EASY ROAD;U1
Solar/Wind Harmer
3.599
274761LEE CO EC;2U
Adder
6.986
274766LEE CO EC;7U
Adder
6.904
274812UNIV PK N;8U
Adder
3.746
276726Z2-087_GEN
Solar/Wind Harmer
5.812
939741AE1-205 GEN
Solar/Wind Harmer
14.698
276158O29GEN2
Solar/Wind Harmer
3.662
274877BISHOP HL;1U
Solar/Wind Harmer
2.415
274854TWINGROVE;U2
Solar/Wind Harmer
4.925
274751CRETE EC ;1U
Adder
3.161
274754CRETE EC ;4U
Adder
3.161
972175AH1-670 GEN
Solar/Wind Harmer
8.543
274880W4-005 GEN4
Solar/Wind Harmer
1.697
963831AG1-236 GEN
Solar/Wind Harmer
5.391
276615X2-022 GEN
Solar/Wind Harmer
1.035
965911AG1-460 GEN
Solar/Wind Harmer
0.25
943121AE2-341 GEN
Solar/Wind Harmer
12.521
943591AF1-030 GEN
Solar/Wind Harmer
8.348
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
274682WAUKEGAN ;7U
Adder
14.735
276805AD2-038 GEN
Solar/Wind Harmer
4.139
274872LEEDK;1U
Solar/Wind Harmer
0.205
276799AD1-013 GEN
Solar/Wind Harmer
1.742
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
276863AD2-134 GEN
Solar/Wind Harmer
1.406
274724RIVER EC ;11
Adder
13.808
959091AF2-200 GEN
Solar/Wind Harmer
15.58
276889AE2-281 GEN
Solar/Wind Harmer
1.493
972236AH1-702 GEN2
Adder
1.693
970571AG2-364 GEN
Solar/Wind Harmer
15.16
274858EASY ROAD;U2
Solar/Wind Harmer
3.599
274760LEE CO EC;1U
Adder
6.986
274767LEE CO EC;8U
Adder
6.904
942111AE2-223 GEN
Solar/Wind Harmer
6.024
276157O29GEN1
Solar/Wind Harmer
2.785
274878BISHOP HL;2U
Solar/Wind Harmer
2.415
274853TWINGROVE;U1
Solar/Wind Harmer
5.03
965091AG1-374 GEN
Solar/Wind Harmer
20.937
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.6
972231SS25-0005
Solar/Wind Harmer
6.138
972181SS23-001
Solar/Wind Harmer
3.836
274752CRETE EC ;2U
Adder
3.161
274753CRETE EC ;3U
Adder
3.161
276686W4-005 GEN3
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.184
276668AB2-070 GEN1
Solar/Wind Harmer
1.253
276621W2-048 GEN
Solar/Wind Harmer
3.298
276838X2-022 GEN2
Solar/Wind Harmer
0.123
942481AE2-261 GEN
Solar/Wind Harmer
5.353
990512J1326
External Queue
3.7948038578033447
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
9.38
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.959
LAGNLTFEXP_LAGN->PJM
CLTF
3.176
TVALTFEXP_TVA->PJM
CLTF
0.822

Details for WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.09 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1690.68
MW Contribution:9.22
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.144
274771LINCOLN ;2U
50/50
10.144
274660LASCO STA;1U
50/50
6.585
274661LASCO STA;2U
50/50
6.502
972259AH1-714 GEN
50/50
18.251
274888KELLY CRK;1U
Solar/Wind Harmer
5.386
274887GEN-1.85
Solar/Wind Harmer
4.863
276843GEN-1.7
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
13.137
274847GR RIDGE ;BU
Solar/Wind Harmer
4.414
274674JOLIET 9 ;6U
Adder
13.126
274803UNIV PARK;6U
Adder
4.863
958481AF2-142 GEN
Solar/Wind Harmer
12.415
971573AH1-285 GEN
Solar/Wind Harmer
7.114
274861TOP CROP ;1U
Solar/Wind Harmer
5.002
274862TOP CROP ;2U
Solar/Wind Harmer
4.177
274695ROCKY RD ;2P
Adder
9.128
274693ROCKY RD ;1P
Adder
9.038
274697ROCKY RD ;3P
Adder
2.48
274696ROCKY RD ;4P
Adder
9.343
274683WAUKEGAN ;8U
Adder
17.239
274683WAUKEGAN ;8U
Adder
14.531
962691AG1-118 GEN
Solar/Wind Harmer
24.231
958491AF2-143 GEN
Solar/Wind Harmer
12.102
970921AG2-575 GEN
Solar/Wind Harmer
8.042
970921AG2-575 GEN
Solar/Wind Harmer
1.87
942991AE2-321 GEN
Solar/Wind Harmer
7.961
274879MINONK ;1U
Solar/Wind Harmer
5.37
971333AH1-146 GEN
Solar/Wind Harmer
15.765
971335AH1-147 GEN
Solar/Wind Harmer
15.765
971341AH1-150 GEN
Solar/Wind Harmer
15.58
274775LINCOLN ;6U
50/50
10.144
274776LINCOLN ;7U
50/50
10.144
274777LINCOLN ;8U
50/50
10.144
972227AH1-698 GEN1
50/50
2.589
274687WILL CNTY;4U
50/50
25.533
274687WILL CNTY;4U
50/50
25.533
274863CRW1-WTG
Solar/Wind Harmer
5.114
274864CRW2-WTG
Solar/Wind Harmer
5.114
960591AF2-350 GEN
Solar/Wind Harmer
9.123
970833AG2-524 GEN
Solar/Wind Harmer
7.585
970833AG2-524 GEN
Solar/Wind Harmer
3.528
274827FISK ;RP
Adder
6.662
274675JOLIET 29;7U
Adder
26.336
274675JOLIET 29;7U
Adder
25.395
274731ELWOOD EC;2P
Adder
14.096
274733ELWOOD EC;3P
Adder
14.096
274735ELWOOD EC;4P
Adder
14.096
274728ELWOOD EC;5P
Adder
14.096
274746AC1-111 G10
Adder
4.669
274744AC1-111 GEN8
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.092
276868AE1-113 GEN
Solar/Wind Harmer
8.054
276882AE2-255 GEN
Solar/Wind Harmer
2.685
971177AH1-047 GEN
Solar/Wind Harmer
4.661
971411AH1-196 GEN
Solar/Wind Harmer
11.848
971675AH1-338 GEN
Solar/Wind Harmer
14.175
971171AH1-044 GEN
Solar/Wind Harmer
15.58
274823ROCKFORD ;21
Adder
15.116
276612AE2-035 GEN
Solar/Wind Harmer
1.959
926823AC1-168 GEN
Solar/Wind Harmer
3.278
971681AH1-341 GEN
Solar/Wind Harmer
11.345
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274805UNIV PK N;1U
Adder
3.754
274811UNIV PK N;7U
Adder
3.746
961011AF2-392 GEN
Solar/Wind Harmer
8.052
276655WTG1_EQ
Solar/Wind Harmer
6.416
276656WTG2_EQ
Solar/Wind Harmer
0.85
959341AF2-225 GEN
Solar/Wind Harmer
11.023
941731AE2-173 GEN
Solar/Wind Harmer
4.273
957751AF2-069 GEN
Solar/Wind Harmer
0.332
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
946321AF1-296 GEN
Solar/Wind Harmer
7.279
276785W4-005 GEN1
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276849AB2-070 GEN2
Solar/Wind Harmer
1.253
276848AB2-070 GEN3
Solar/Wind Harmer
1.253
971343AH1-151 GEN
Solar/Wind Harmer
15.58
276872AE1-163_GEN1
Solar/Wind Harmer
5.225
274856ECOGROVE ;U1
Solar/Wind Harmer
2.582
276611AD2-172 GEN
Solar/Wind Harmer
1.959
938861AE1-114 GEN
Solar/Wind Harmer
6.198
274764LEE CO EC;5U
Adder
7.003
274765LEE CO EC;6U
Adder
7.003
274762LEE CO EC;3U
Adder
6.986
274763LEE CO EC;4U
Adder
6.92
276603SUBLETTE C
Solar/Wind Harmer
0.785
274808UNIV PK N;4U
Adder
3.73
972267AH1-718 GEN
Adder
3.068
276741O09 GEN1
Solar/Wind Harmer
2.616
276708O09 GEN2
Solar/Wind Harmer
2.616
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
276782AC1-033 GEN
Solar/Wind Harmer
2.854
960611AF2-352 GEN
Solar/Wind Harmer
1.623
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
957381AF2-032 GEN
Solar/Wind Harmer
0.199
274773LINCOLN ;4U
50/50
10.144
274774LINCOLN ;5U
50/50
10.144
274655BRAIDWOOD;2U
50/50
6.709
972207SS24-0001
Solar/Wind Harmer
33.99
941551AE2-152 GEN
Solar/Wind Harmer
4.841
939401AE1-172 GEN
Solar/Wind Harmer
13.646
276776AD2-060 GEN
Solar/Wind Harmer
0.386
274871GR RIDGE ;2U
Solar/Wind Harmer
6.71
276164X3-005 C
Solar/Wind Harmer
0.608
274801UNIV PARK;4U
Adder
5.005
274676JOLIET 29;8U
Adder
26.335
274732ELWOOD EC;7P
Adder
14.096
274674JOLIET 9 ;6U
Adder
13.126
274745AC1-111 GEN9
Adder
4.669
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.735
274828WAUKEGAN ;BP
Adder
9.036
960751AF2-366 GEN
Solar/Wind Harmer
2.307
962781AG1-127 GEN
Solar/Wind Harmer
7.648
276901AD2-066 C O1
Solar/Wind Harmer
2.814
274872LEEDK;1U
Solar/Wind Harmer
6.578
971997AH1-543 GEN
Solar/Wind Harmer
12.448
276861AD2-134 GEN
Solar/Wind Harmer
1.406
957471AF2-041 GEN
Solar/Wind Harmer
23.37
959081AF2-199 GEN
Solar/Wind Harmer
7.79
971067AG2-660 GEN
Solar/Wind Harmer
1.812
276876AE1-163_GEN2
Solar/Wind Harmer
5.225
274723RIVER EC ;12
Adder
13.916
274822ROCKFORD ;11
Adder
15.226
972235AH1-702 GEN1
Adder
1.947
970819AG2-516 GEN
Solar/Wind Harmer
9.216
971475AH1-234 GEN
Solar/Wind Harmer
17.128
970569AG2-363 GEN
Solar/Wind Harmer
22.74
274857EASY ROAD;U1
Solar/Wind Harmer
3.599
274761LEE CO EC;2U
Adder
6.986
274766LEE CO EC;7U
Adder
6.904
274812UNIV PK N;8U
Adder
3.746
276726Z2-087_GEN
Solar/Wind Harmer
5.812
939741AE1-205 GEN
Solar/Wind Harmer
14.698
276158O29GEN2
Solar/Wind Harmer
3.662
274877BISHOP HL;1U
Solar/Wind Harmer
2.415
274854TWINGROVE;U2
Solar/Wind Harmer
4.925
274751CRETE EC ;1U
Adder
3.161
274754CRETE EC ;4U
Adder
3.161
972175AH1-670 GEN
Solar/Wind Harmer
8.543
274880W4-005 GEN4
Solar/Wind Harmer
1.697
963831AG1-236 GEN
Solar/Wind Harmer
5.391
276615X2-022 GEN
Solar/Wind Harmer
1.035
965911AG1-460 GEN
Solar/Wind Harmer
0.25
274772LINCOLN ;3U
50/50
10.144
274654BRAIDWOOD;1U
50/50
7.139
972228AH1-698 GEN2
50/50
3.673
276897AD1-100 C
Solar/Wind Harmer
30.978
939351AE1-166 GEN
Solar/Wind Harmer
6.33
276772AC2-154 GEN
Solar/Wind Harmer
2.544
276806AD2-047 C O1
Solar/Wind Harmer
9.759
970941AG2-585 GEN
Solar/Wind Harmer
11.403
970707AG2-453 GEN
Solar/Wind Harmer
24.504
276893AG1-478 C
Solar/Wind Harmer
0.363
274826FISK ;BP
Adder
9.4
274800UNIV PARK;3U
Adder
5.005
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.395
274729ELWOOD EC;1P
Adder
14.096
274730ELWOOD EC;6P
Adder
14.096
274734ELWOOD EC;8P
Adder
14.096
274736ELWOOD EC;9P
Adder
14.096
943121AE2-341 GEN
Solar/Wind Harmer
12.521
943591AF1-030 GEN
Solar/Wind Harmer
8.348
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
274682WAUKEGAN ;7U
Adder
14.735
276805AD2-038 GEN
Solar/Wind Harmer
4.139
274872LEEDK;1U
Solar/Wind Harmer
0.205
276799AD1-013 GEN
Solar/Wind Harmer
1.742
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
276863AD2-134 GEN
Solar/Wind Harmer
1.406
274724RIVER EC ;11
Adder
13.808
959091AF2-200 GEN
Solar/Wind Harmer
15.58
276889AE2-281 GEN
Solar/Wind Harmer
1.493
972236AH1-702 GEN2
Adder
1.693
970571AG2-364 GEN
Solar/Wind Harmer
15.16
274858EASY ROAD;U2
Solar/Wind Harmer
3.599
274760LEE CO EC;1U
Adder
6.986
274767LEE CO EC;8U
Adder
6.904
942111AE2-223 GEN
Solar/Wind Harmer
6.024
276157O29GEN1
Solar/Wind Harmer
2.785
274878BISHOP HL;2U
Solar/Wind Harmer
2.415
274853TWINGROVE;U1
Solar/Wind Harmer
5.03
965091AG1-374 GEN
Solar/Wind Harmer
20.937
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.6
972231SS25-0005
Solar/Wind Harmer
6.138
972181SS23-001
Solar/Wind Harmer
3.836
274752CRETE EC ;2U
Adder
3.161
274753CRETE EC ;3U
Adder
3.161
276686W4-005 GEN3
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.184
276668AB2-070 GEN1
Solar/Wind Harmer
1.253
276621W2-048 GEN
Solar/Wind Harmer
3.298
276838X2-022 GEN2
Solar/Wind Harmer
0.123
942481AE2-261 GEN
Solar/Wind Harmer
5.353
990512J1326
External Queue
3.7948038578033447
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
9.38
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.959
LAGNLTFEXP_LAGN->PJM
CLTF
3.176
TVALTFEXP_TVA->PJM
CLTF
0.822

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.32 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1708.81
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.317
274771LINCOLN ;2U
50/50
10.317
274661LASCO STA;2U
50/50
6.468
972259AH1-714 GEN
50/50
18.154
274660LASCO STA;1U
50/50
6.55
274888KELLY CRK;1U
Solar/Wind Harmer
5.359
274887GEN-1.85
Solar/Wind Harmer
4.838
276843GEN-1.7
Solar/Wind Harmer
0.521
958011AF2-095 GEN
Solar/Wind Harmer
13.071
274847GR RIDGE ;BU
Solar/Wind Harmer
4.392
274674JOLIET 9 ;6U
Adder
13.08
274803UNIV PARK;6U
Adder
4.849
958481AF2-142 GEN
Solar/Wind Harmer
12.397
971573AH1-285 GEN
Solar/Wind Harmer
7.088
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274862TOP CROP ;2U
Solar/Wind Harmer
4.161
274695ROCKY RD ;2P
Adder
9.097
274693ROCKY RD ;1P
Adder
9.008
274697ROCKY RD ;3P
Adder
2.471
274696ROCKY RD ;4P
Adder
9.312
274683WAUKEGAN ;8U
Adder
17.184
274683WAUKEGAN ;8U
Adder
14.485
958491AF2-143 GEN
Solar/Wind Harmer
12.078
962691AG1-118 GEN
Solar/Wind Harmer
24.147
970921AG2-575 GEN
Solar/Wind Harmer
8.014
970921AG2-575 GEN
Solar/Wind Harmer
1.864
942991AE2-321 GEN
Solar/Wind Harmer
7.934
274879MINONK ;1U
Solar/Wind Harmer
5.353
971333AH1-146 GEN
Solar/Wind Harmer
15.712
971335AH1-147 GEN
Solar/Wind Harmer
15.712
971341AH1-150 GEN
Solar/Wind Harmer
15.526
971343AH1-151 GEN
Solar/Wind Harmer
15.526
276872AE1-163_GEN1
Solar/Wind Harmer
5.211
274856ECOGROVE ;U1
Solar/Wind Harmer
2.573
276611AD2-172 GEN
Solar/Wind Harmer
1.952
938861AE1-114 GEN
Solar/Wind Harmer
6.177
274764LEE CO EC;5U
Adder
6.978
274765LEE CO EC;6U
Adder
6.978
274762LEE CO EC;3U
Adder
6.962
274763LEE CO EC;4U
Adder
6.896
274808UNIV PK N;4U
Adder
3.723
276603SUBLETTE C
Solar/Wind Harmer
0.782
972267AH1-718 GEN
Adder
3.057
276741O09 GEN1
Solar/Wind Harmer
2.606
276708O09 GEN2
Solar/Wind Harmer
2.606
274851PROVIDENC;RU
Solar/Wind Harmer
2.051
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.965
276646AC1-214 GEN2
Solar/Wind Harmer
0.965
276782AC1-033 GEN
Solar/Wind Harmer
2.842
960611AF2-352 GEN
Solar/Wind Harmer
1.612
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
957381AF2-032 GEN
Solar/Wind Harmer
0.198
274775LINCOLN ;6U
50/50
10.317
274776LINCOLN ;7U
50/50
10.317
274777LINCOLN ;8U
50/50
10.317
972227AH1-698 GEN1
50/50
2.574
274863CRW1-WTG
Solar/Wind Harmer
5.073
274864CRW2-WTG
Solar/Wind Harmer
5.073
960591AF2-350 GEN
Solar/Wind Harmer
9.077
970833AG2-524 GEN
Solar/Wind Harmer
7.549
970833AG2-524 GEN
Solar/Wind Harmer
3.511
274687WILL CNTY;4U
Adder
23.987
274687WILL CNTY;4U
Adder
23.987
274827FISK ;RP
Adder
6.648
274675JOLIET 29;7U
Adder
26.268
274675JOLIET 29;7U
Adder
25.33
274731ELWOOD EC;2P
Adder
14.057
274733ELWOOD EC;3P
Adder
14.057
274735ELWOOD EC;4P
Adder
14.057
274728ELWOOD EC;5P
Adder
14.057
274746AC1-111 G10
Adder
4.653
274744AC1-111 GEN8
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970169AG2-114 GEN
Solar/Wind Harmer
8.04
276868AE1-113 GEN
Solar/Wind Harmer
8.028
276882AE2-255 GEN
Solar/Wind Harmer
2.676
971177AH1-047 GEN
Solar/Wind Harmer
4.646
971411AH1-196 GEN
Solar/Wind Harmer
11.808
971675AH1-338 GEN
Solar/Wind Harmer
14.125
971171AH1-044 GEN
Solar/Wind Harmer
15.526
274823ROCKFORD ;21
Adder
15.064
276612AE2-035 GEN
Solar/Wind Harmer
1.952
926823AC1-168 GEN
Solar/Wind Harmer
3.264
971681AH1-341 GEN
Solar/Wind Harmer
11.305
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274805UNIV PK N;1U
Adder
3.747
274811UNIV PK N;7U
Adder
3.739
961011AF2-392 GEN
Solar/Wind Harmer
8.024
276655WTG1_EQ
Solar/Wind Harmer
6.372
276656WTG2_EQ
Solar/Wind Harmer
0.844
959341AF2-225 GEN
Solar/Wind Harmer
10.948
941731AE2-173 GEN
Solar/Wind Harmer
4.243
957751AF2-069 GEN
Solar/Wind Harmer
0.331
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
946321AF1-296 GEN
Solar/Wind Harmer
7.252
276785W4-005 GEN1
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276849AB2-070 GEN2
Solar/Wind Harmer
1.245
276848AB2-070 GEN3
Solar/Wind Harmer
1.245
274772LINCOLN ;3U
50/50
10.317
274654BRAIDWOOD;1U
50/50
7.096
972228AH1-698 GEN2
50/50
3.651
276897AD1-100 C
Solar/Wind Harmer
30.712
939351AE1-166 GEN
Solar/Wind Harmer
6.275
276772AC2-154 GEN
Solar/Wind Harmer
2.531
276806AD2-047 C O1
Solar/Wind Harmer
9.71
970941AG2-585 GEN
Solar/Wind Harmer
11.346
970707AG2-453 GEN
Solar/Wind Harmer
24.392
276893AG1-478 C
Solar/Wind Harmer
0.361
274826FISK ;BP
Adder
9.38
274676JOLIET 29;8U
Adder
25.329
274800UNIV PARK;3U
Adder
4.987
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.057
274730ELWOOD EC;6P
Adder
14.057
274734ELWOOD EC;8P
Adder
14.057
274736ELWOOD EC;9P
Adder
14.057
274802UNIV PARK;5U
Adder
4.849
943121AE2-341 GEN
Solar/Wind Harmer
12.476
943591AF1-030 GEN
Solar/Wind Harmer
8.318
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
274682WAUKEGAN ;7U
Adder
14.689
276805AD2-038 GEN
Solar/Wind Harmer
4.131
274872LEEDK;1U
Solar/Wind Harmer
0.204
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.897
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
274724RIVER EC ;11
Adder
13.758
959091AF2-200 GEN
Solar/Wind Harmer
15.526
276889AE2-281 GEN
Solar/Wind Harmer
1.489
972236AH1-702 GEN2
Adder
1.687
970571AG2-364 GEN
Solar/Wind Harmer
15.11
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.962
274767LEE CO EC;8U
Adder
6.88
942111AE2-223 GEN
Solar/Wind Harmer
5.983
276157O29GEN1
Solar/Wind Harmer
2.775
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
274853TWINGROVE;U1
Solar/Wind Harmer
4.996
965091AG1-374 GEN
Solar/Wind Harmer
20.795
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.537
972231SS25-0005
Solar/Wind Harmer
6.114
972181SS23-001
Solar/Wind Harmer
3.821
274752CRETE EC ;2U
Adder
3.149
274753CRETE EC ;3U
Adder
3.149
276686W4-005 GEN3
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.152
276668AB2-070 GEN1
Solar/Wind Harmer
1.245
276621W2-048 GEN
Solar/Wind Harmer
3.278
276838X2-022 GEN2
Solar/Wind Harmer
0.122
942481AE2-261 GEN
Solar/Wind Harmer
5.321
274773LINCOLN ;4U
50/50
10.317
274774LINCOLN ;5U
50/50
10.317
274655BRAIDWOOD;2U
50/50
6.669
972207SS24-0001
Solar/Wind Harmer
34.568
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.528
276776AD2-060 GEN
Solar/Wind Harmer
0.384
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
276164X3-005 C
Solar/Wind Harmer
0.607
274676JOLIET 29;8U
Adder
26.267
274801UNIV PARK;4U
Adder
4.987
274732ELWOOD EC;7P
Adder
14.057
274674JOLIET 9 ;6U
Adder
13.08
274745AC1-111 GEN9
Adder
4.653
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.689
274828WAUKEGAN ;BP
Adder
9.008
960751AF2-366 GEN
Solar/Wind Harmer
2.299
962781AG1-127 GEN
Solar/Wind Harmer
7.622
274872LEEDK;1U
Solar/Wind Harmer
6.555
276901AD2-066 C O1
Solar/Wind Harmer
2.804
971997AH1-543 GEN
Solar/Wind Harmer
12.404
276861AD2-134 GEN
Solar/Wind Harmer
1.401
957471AF2-041 GEN
Solar/Wind Harmer
23.29
959081AF2-199 GEN
Solar/Wind Harmer
7.763
971067AG2-660 GEN
Solar/Wind Harmer
1.805
274723RIVER EC ;12
Adder
13.906
276876AE1-163_GEN2
Solar/Wind Harmer
5.211
274822ROCKFORD ;11
Adder
15.174
972235AH1-702 GEN1
Adder
1.94
970819AG2-516 GEN
Solar/Wind Harmer
9.184
971475AH1-234 GEN
Solar/Wind Harmer
17.07
970569AG2-363 GEN
Solar/Wind Harmer
22.665
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.962
274766LEE CO EC;7U
Adder
6.88
274812UNIV PK N;8U
Adder
3.739
276726Z2-087_GEN
Solar/Wind Harmer
5.772
939741AE1-205 GEN
Solar/Wind Harmer
14.597
276158O29GEN2
Solar/Wind Harmer
3.648
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
274854TWINGROVE;U2
Solar/Wind Harmer
4.891
274751CRETE EC ;1U
Adder
3.149
274754CRETE EC ;4U
Adder
3.149
972175AH1-670 GEN
Solar/Wind Harmer
8.487
274880W4-005 GEN4
Solar/Wind Harmer
1.686
963831AG1-236 GEN
Solar/Wind Harmer
5.357
276615X2-022 GEN
Solar/Wind Harmer
1.029
965911AG1-460 GEN
Solar/Wind Harmer
0.248
990512J1326
External Queue
3.782650947570801
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.596
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.239
MECLTFEXP_MEC->PJM
CLTF
9.345
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.161
TVALTFEXP_TVA->PJM
CLTF
0.817

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT2-3___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.6 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1683.43
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.317
274771LINCOLN ;2U
50/50
10.317
274661LASCO STA;2U
50/50
6.468
972259AH1-714 GEN
50/50
18.154
274660LASCO STA;1U
50/50
6.55
274888KELLY CRK;1U
Solar/Wind Harmer
5.359
274887GEN-1.85
Solar/Wind Harmer
4.838
276843GEN-1.7
Solar/Wind Harmer
0.521
958011AF2-095 GEN
Solar/Wind Harmer
13.071
274847GR RIDGE ;BU
Solar/Wind Harmer
4.392
274674JOLIET 9 ;6U
Adder
13.08
274803UNIV PARK;6U
Adder
4.849
958481AF2-142 GEN
Solar/Wind Harmer
12.397
971573AH1-285 GEN
Solar/Wind Harmer
7.088
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274862TOP CROP ;2U
Solar/Wind Harmer
4.161
274695ROCKY RD ;2P
Adder
9.097
274693ROCKY RD ;1P
Adder
9.008
274697ROCKY RD ;3P
Adder
2.471
274696ROCKY RD ;4P
Adder
9.312
274683WAUKEGAN ;8U
Adder
17.184
274683WAUKEGAN ;8U
Adder
14.485
958491AF2-143 GEN
Solar/Wind Harmer
12.078
962691AG1-118 GEN
Solar/Wind Harmer
24.147
970921AG2-575 GEN
Solar/Wind Harmer
8.014
970921AG2-575 GEN
Solar/Wind Harmer
1.864
942991AE2-321 GEN
Solar/Wind Harmer
7.934
274879MINONK ;1U
Solar/Wind Harmer
5.353
971333AH1-146 GEN
Solar/Wind Harmer
15.712
971335AH1-147 GEN
Solar/Wind Harmer
15.712
971341AH1-150 GEN
Solar/Wind Harmer
15.526
971343AH1-151 GEN
Solar/Wind Harmer
15.526
276872AE1-163_GEN1
Solar/Wind Harmer
5.211
274856ECOGROVE ;U1
Solar/Wind Harmer
2.573
276611AD2-172 GEN
Solar/Wind Harmer
1.952
938861AE1-114 GEN
Solar/Wind Harmer
6.177
274764LEE CO EC;5U
Adder
6.978
274765LEE CO EC;6U
Adder
6.978
274762LEE CO EC;3U
Adder
6.962
274763LEE CO EC;4U
Adder
6.896
274808UNIV PK N;4U
Adder
3.723
276603SUBLETTE C
Solar/Wind Harmer
0.782
972267AH1-718 GEN
Adder
3.057
276741O09 GEN1
Solar/Wind Harmer
2.606
276708O09 GEN2
Solar/Wind Harmer
2.606
274851PROVIDENC;RU
Solar/Wind Harmer
2.051
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.965
276646AC1-214 GEN2
Solar/Wind Harmer
0.965
276782AC1-033 GEN
Solar/Wind Harmer
2.842
960611AF2-352 GEN
Solar/Wind Harmer
1.612
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
957381AF2-032 GEN
Solar/Wind Harmer
0.198
274775LINCOLN ;6U
50/50
10.317
274776LINCOLN ;7U
50/50
10.317
274777LINCOLN ;8U
50/50
10.317
972227AH1-698 GEN1
50/50
2.574
274863CRW1-WTG
Solar/Wind Harmer
5.073
274864CRW2-WTG
Solar/Wind Harmer
5.073
960591AF2-350 GEN
Solar/Wind Harmer
9.077
970833AG2-524 GEN
Solar/Wind Harmer
7.549
970833AG2-524 GEN
Solar/Wind Harmer
3.511
274687WILL CNTY;4U
Adder
23.987
274687WILL CNTY;4U
Adder
23.987
274827FISK ;RP
Adder
6.648
274675JOLIET 29;7U
Adder
26.268
274675JOLIET 29;7U
Adder
25.33
274731ELWOOD EC;2P
Adder
14.057
274733ELWOOD EC;3P
Adder
14.057
274735ELWOOD EC;4P
Adder
14.057
274728ELWOOD EC;5P
Adder
14.057
274746AC1-111 G10
Adder
4.653
274744AC1-111 GEN8
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970169AG2-114 GEN
Solar/Wind Harmer
8.04
276868AE1-113 GEN
Solar/Wind Harmer
8.028
276882AE2-255 GEN
Solar/Wind Harmer
2.676
971177AH1-047 GEN
Solar/Wind Harmer
4.646
971411AH1-196 GEN
Solar/Wind Harmer
11.808
971675AH1-338 GEN
Solar/Wind Harmer
14.125
971171AH1-044 GEN
Solar/Wind Harmer
15.526
274823ROCKFORD ;21
Adder
15.064
276612AE2-035 GEN
Solar/Wind Harmer
1.952
926823AC1-168 GEN
Solar/Wind Harmer
3.264
971681AH1-341 GEN
Solar/Wind Harmer
11.305
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274805UNIV PK N;1U
Adder
3.747
274811UNIV PK N;7U
Adder
3.739
961011AF2-392 GEN
Solar/Wind Harmer
8.024
276655WTG1_EQ
Solar/Wind Harmer
6.372
276656WTG2_EQ
Solar/Wind Harmer
0.844
959341AF2-225 GEN
Solar/Wind Harmer
10.948
941731AE2-173 GEN
Solar/Wind Harmer
4.243
957751AF2-069 GEN
Solar/Wind Harmer
0.331
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
946321AF1-296 GEN
Solar/Wind Harmer
7.252
276785W4-005 GEN1
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276849AB2-070 GEN2
Solar/Wind Harmer
1.245
276848AB2-070 GEN3
Solar/Wind Harmer
1.245
274772LINCOLN ;3U
50/50
10.317
274654BRAIDWOOD;1U
50/50
7.096
972228AH1-698 GEN2
50/50
3.651
276897AD1-100 C
Solar/Wind Harmer
30.712
939351AE1-166 GEN
Solar/Wind Harmer
6.275
276772AC2-154 GEN
Solar/Wind Harmer
2.531
276806AD2-047 C O1
Solar/Wind Harmer
9.71
970941AG2-585 GEN
Solar/Wind Harmer
11.346
970707AG2-453 GEN
Solar/Wind Harmer
24.392
276893AG1-478 C
Solar/Wind Harmer
0.361
274826FISK ;BP
Adder
9.38
274676JOLIET 29;8U
Adder
25.329
274800UNIV PARK;3U
Adder
4.987
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.057
274730ELWOOD EC;6P
Adder
14.057
274734ELWOOD EC;8P
Adder
14.057
274736ELWOOD EC;9P
Adder
14.057
274802UNIV PARK;5U
Adder
4.849
943121AE2-341 GEN
Solar/Wind Harmer
12.476
943591AF1-030 GEN
Solar/Wind Harmer
8.318
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
274682WAUKEGAN ;7U
Adder
14.689
276805AD2-038 GEN
Solar/Wind Harmer
4.131
274872LEEDK;1U
Solar/Wind Harmer
0.204
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.897
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
274724RIVER EC ;11
Adder
13.758
959091AF2-200 GEN
Solar/Wind Harmer
15.526
276889AE2-281 GEN
Solar/Wind Harmer
1.489
972236AH1-702 GEN2
Adder
1.687
970571AG2-364 GEN
Solar/Wind Harmer
15.11
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.962
274767LEE CO EC;8U
Adder
6.88
942111AE2-223 GEN
Solar/Wind Harmer
5.983
276157O29GEN1
Solar/Wind Harmer
2.775
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
274853TWINGROVE;U1
Solar/Wind Harmer
4.996
965091AG1-374 GEN
Solar/Wind Harmer
20.795
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.537
972231SS25-0005
Solar/Wind Harmer
6.114
972181SS23-001
Solar/Wind Harmer
3.821
274752CRETE EC ;2U
Adder
3.149
274753CRETE EC ;3U
Adder
3.149
276686W4-005 GEN3
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.152
276668AB2-070 GEN1
Solar/Wind Harmer
1.245
276621W2-048 GEN
Solar/Wind Harmer
3.278
276838X2-022 GEN2
Solar/Wind Harmer
0.122
942481AE2-261 GEN
Solar/Wind Harmer
5.321
274773LINCOLN ;4U
50/50
10.317
274774LINCOLN ;5U
50/50
10.317
274655BRAIDWOOD;2U
50/50
6.669
972207SS24-0001
Solar/Wind Harmer
34.568
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.528
276776AD2-060 GEN
Solar/Wind Harmer
0.384
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
276164X3-005 C
Solar/Wind Harmer
0.607
274676JOLIET 29;8U
Adder
26.267
274801UNIV PARK;4U
Adder
4.987
274732ELWOOD EC;7P
Adder
14.057
274674JOLIET 9 ;6U
Adder
13.08
274745AC1-111 GEN9
Adder
4.653
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.689
274828WAUKEGAN ;BP
Adder
9.008
960751AF2-366 GEN
Solar/Wind Harmer
2.299
962781AG1-127 GEN
Solar/Wind Harmer
7.622
274872LEEDK;1U
Solar/Wind Harmer
6.555
276901AD2-066 C O1
Solar/Wind Harmer
2.804
971997AH1-543 GEN
Solar/Wind Harmer
12.404
276861AD2-134 GEN
Solar/Wind Harmer
1.401
957471AF2-041 GEN
Solar/Wind Harmer
23.29
959081AF2-199 GEN
Solar/Wind Harmer
7.763
971067AG2-660 GEN
Solar/Wind Harmer
1.805
274723RIVER EC ;12
Adder
13.906
276876AE1-163_GEN2
Solar/Wind Harmer
5.211
274822ROCKFORD ;11
Adder
15.174
972235AH1-702 GEN1
Adder
1.94
970819AG2-516 GEN
Solar/Wind Harmer
9.184
971475AH1-234 GEN
Solar/Wind Harmer
17.07
970569AG2-363 GEN
Solar/Wind Harmer
22.665
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.962
274766LEE CO EC;7U
Adder
6.88
274812UNIV PK N;8U
Adder
3.739
276726Z2-087_GEN
Solar/Wind Harmer
5.772
939741AE1-205 GEN
Solar/Wind Harmer
14.597
276158O29GEN2
Solar/Wind Harmer
3.648
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
274854TWINGROVE;U2
Solar/Wind Harmer
4.891
274751CRETE EC ;1U
Adder
3.149
274754CRETE EC ;4U
Adder
3.149
972175AH1-670 GEN
Solar/Wind Harmer
8.487
274880W4-005 GEN4
Solar/Wind Harmer
1.686
963831AG1-236 GEN
Solar/Wind Harmer
5.357
276615X2-022 GEN
Solar/Wind Harmer
1.029
965911AG1-460 GEN
Solar/Wind Harmer
0.248
990512J1326
External Queue
3.7826504707336426
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.596
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.239
MECLTFEXP_MEC->PJM
CLTF
9.345
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.161
TVALTFEXP_TVA->PJM
CLTF
0.817

Details for WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line l/o COMED_P4_023-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.59 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1683.4
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
10.317
274776LINCOLN ;7U
50/50
10.317
274777LINCOLN ;8U
50/50
10.317
972227AH1-698 GEN1
50/50
2.574
274863CRW1-WTG
Solar/Wind Harmer
5.073
274864CRW2-WTG
Solar/Wind Harmer
5.073
960591AF2-350 GEN
Solar/Wind Harmer
9.077
970833AG2-524 GEN
Solar/Wind Harmer
7.549
970833AG2-524 GEN
Solar/Wind Harmer
3.511
274687WILL CNTY;4U
Adder
23.987
274687WILL CNTY;4U
Adder
23.987
274827FISK ;RP
Adder
6.648
274675JOLIET 29;7U
Adder
26.268
274675JOLIET 29;7U
Adder
25.33
274731ELWOOD EC;2P
Adder
14.057
274733ELWOOD EC;3P
Adder
14.057
274735ELWOOD EC;4P
Adder
14.057
274728ELWOOD EC;5P
Adder
14.057
274746AC1-111 G10
Adder
4.653
274744AC1-111 GEN8
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970169AG2-114 GEN
Solar/Wind Harmer
8.04
276868AE1-113 GEN
Solar/Wind Harmer
8.028
276882AE2-255 GEN
Solar/Wind Harmer
2.676
971177AH1-047 GEN
Solar/Wind Harmer
4.646
971411AH1-196 GEN
Solar/Wind Harmer
11.808
971675AH1-338 GEN
Solar/Wind Harmer
14.125
971171AH1-044 GEN
Solar/Wind Harmer
15.526
274823ROCKFORD ;21
Adder
15.064
276612AE2-035 GEN
Solar/Wind Harmer
1.952
926823AC1-168 GEN
Solar/Wind Harmer
3.264
971681AH1-341 GEN
Solar/Wind Harmer
11.305
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274805UNIV PK N;1U
Adder
3.747
274811UNIV PK N;7U
Adder
3.739
961011AF2-392 GEN
Solar/Wind Harmer
8.024
276655WTG1_EQ
Solar/Wind Harmer
6.372
276656WTG2_EQ
Solar/Wind Harmer
0.844
959341AF2-225 GEN
Solar/Wind Harmer
10.948
941731AE2-173 GEN
Solar/Wind Harmer
4.243
957751AF2-069 GEN
Solar/Wind Harmer
0.331
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
946321AF1-296 GEN
Solar/Wind Harmer
7.252
276785W4-005 GEN1
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276849AB2-070 GEN2
Solar/Wind Harmer
1.245
276848AB2-070 GEN3
Solar/Wind Harmer
1.245
274770LINCOLN ;1U
50/50
10.317
274771LINCOLN ;2U
50/50
10.317
274661LASCO STA;2U
50/50
6.468
972259AH1-714 GEN
50/50
18.154
274660LASCO STA;1U
50/50
6.55
274888KELLY CRK;1U
Solar/Wind Harmer
5.359
274887GEN-1.85
Solar/Wind Harmer
4.838
276843GEN-1.7
Solar/Wind Harmer
0.521
958011AF2-095 GEN
Solar/Wind Harmer
13.071
274847GR RIDGE ;BU
Solar/Wind Harmer
4.392
274674JOLIET 9 ;6U
Adder
13.08
274803UNIV PARK;6U
Adder
4.849
958481AF2-142 GEN
Solar/Wind Harmer
12.397
971573AH1-285 GEN
Solar/Wind Harmer
7.088
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274862TOP CROP ;2U
Solar/Wind Harmer
4.161
274695ROCKY RD ;2P
Adder
9.097
274693ROCKY RD ;1P
Adder
9.008
274697ROCKY RD ;3P
Adder
2.471
274696ROCKY RD ;4P
Adder
9.312
274683WAUKEGAN ;8U
Adder
17.184
274683WAUKEGAN ;8U
Adder
14.485
958491AF2-143 GEN
Solar/Wind Harmer
12.078
962691AG1-118 GEN
Solar/Wind Harmer
24.147
970921AG2-575 GEN
Solar/Wind Harmer
8.014
970921AG2-575 GEN
Solar/Wind Harmer
1.864
942991AE2-321 GEN
Solar/Wind Harmer
7.934
274879MINONK ;1U
Solar/Wind Harmer
5.353
971333AH1-146 GEN
Solar/Wind Harmer
15.712
971335AH1-147 GEN
Solar/Wind Harmer
15.712
971341AH1-150 GEN
Solar/Wind Harmer
15.526
971343AH1-151 GEN
Solar/Wind Harmer
15.526
276872AE1-163_GEN1
Solar/Wind Harmer
5.211
274856ECOGROVE ;U1
Solar/Wind Harmer
2.573
276611AD2-172 GEN
Solar/Wind Harmer
1.952
938861AE1-114 GEN
Solar/Wind Harmer
6.177
274764LEE CO EC;5U
Adder
6.978
274765LEE CO EC;6U
Adder
6.978
274762LEE CO EC;3U
Adder
6.962
274763LEE CO EC;4U
Adder
6.896
274808UNIV PK N;4U
Adder
3.723
276603SUBLETTE C
Solar/Wind Harmer
0.782
972267AH1-718 GEN
Adder
3.057
276741O09 GEN1
Solar/Wind Harmer
2.606
276708O09 GEN2
Solar/Wind Harmer
2.606
274851PROVIDENC;RU
Solar/Wind Harmer
2.051
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.965
276646AC1-214 GEN2
Solar/Wind Harmer
0.965
276782AC1-033 GEN
Solar/Wind Harmer
2.842
960611AF2-352 GEN
Solar/Wind Harmer
1.612
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
957381AF2-032 GEN
Solar/Wind Harmer
0.198
274773LINCOLN ;4U
50/50
10.317
274774LINCOLN ;5U
50/50
10.317
274655BRAIDWOOD;2U
50/50
6.669
972207SS24-0001
Solar/Wind Harmer
34.568
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.528
276776AD2-060 GEN
Solar/Wind Harmer
0.384
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
276164X3-005 C
Solar/Wind Harmer
0.607
274676JOLIET 29;8U
Adder
26.267
274801UNIV PARK;4U
Adder
4.987
274732ELWOOD EC;7P
Adder
14.057
274674JOLIET 9 ;6U
Adder
13.08
274745AC1-111 GEN9
Adder
4.653
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.689
274828WAUKEGAN ;BP
Adder
9.008
960751AF2-366 GEN
Solar/Wind Harmer
2.299
962781AG1-127 GEN
Solar/Wind Harmer
7.622
274872LEEDK;1U
Solar/Wind Harmer
6.555
276901AD2-066 C O1
Solar/Wind Harmer
2.804
971997AH1-543 GEN
Solar/Wind Harmer
12.404
276861AD2-134 GEN
Solar/Wind Harmer
1.401
957471AF2-041 GEN
Solar/Wind Harmer
23.29
959081AF2-199 GEN
Solar/Wind Harmer
7.763
971067AG2-660 GEN
Solar/Wind Harmer
1.805
274723RIVER EC ;12
Adder
13.906
276876AE1-163_GEN2
Solar/Wind Harmer
5.211
274822ROCKFORD ;11
Adder
15.174
972235AH1-702 GEN1
Adder
1.94
970819AG2-516 GEN
Solar/Wind Harmer
9.184
971475AH1-234 GEN
Solar/Wind Harmer
17.07
970569AG2-363 GEN
Solar/Wind Harmer
22.665
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.962
274766LEE CO EC;7U
Adder
6.88
274812UNIV PK N;8U
Adder
3.739
276726Z2-087_GEN
Solar/Wind Harmer
5.772
939741AE1-205 GEN
Solar/Wind Harmer
14.597
276158O29GEN2
Solar/Wind Harmer
3.648
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
274854TWINGROVE;U2
Solar/Wind Harmer
4.891
274751CRETE EC ;1U
Adder
3.149
274754CRETE EC ;4U
Adder
3.149
972175AH1-670 GEN
Solar/Wind Harmer
8.487
274880W4-005 GEN4
Solar/Wind Harmer
1.686
963831AG1-236 GEN
Solar/Wind Harmer
5.357
276615X2-022 GEN
Solar/Wind Harmer
1.029
965911AG1-460 GEN
Solar/Wind Harmer
0.248
274772LINCOLN ;3U
50/50
10.317
274654BRAIDWOOD;1U
50/50
7.096
972228AH1-698 GEN2
50/50
3.651
276897AD1-100 C
Solar/Wind Harmer
30.712
939351AE1-166 GEN
Solar/Wind Harmer
6.275
276772AC2-154 GEN
Solar/Wind Harmer
2.531
276806AD2-047 C O1
Solar/Wind Harmer
9.71
970941AG2-585 GEN
Solar/Wind Harmer
11.346
970707AG2-453 GEN
Solar/Wind Harmer
24.392
276893AG1-478 C
Solar/Wind Harmer
0.361
274826FISK ;BP
Adder
9.38
274676JOLIET 29;8U
Adder
25.329
274800UNIV PARK;3U
Adder
4.987
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.057
274730ELWOOD EC;6P
Adder
14.057
274734ELWOOD EC;8P
Adder
14.057
274736ELWOOD EC;9P
Adder
14.057
274802UNIV PARK;5U
Adder
4.849
943121AE2-341 GEN
Solar/Wind Harmer
12.476
943591AF1-030 GEN
Solar/Wind Harmer
8.318
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
274682WAUKEGAN ;7U
Adder
14.689
276805AD2-038 GEN
Solar/Wind Harmer
4.131
274872LEEDK;1U
Solar/Wind Harmer
0.204
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.897
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
274724RIVER EC ;11
Adder
13.758
959091AF2-200 GEN
Solar/Wind Harmer
15.526
276889AE2-281 GEN
Solar/Wind Harmer
1.489
972236AH1-702 GEN2
Adder
1.687
970571AG2-364 GEN
Solar/Wind Harmer
15.11
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.962
274767LEE CO EC;8U
Adder
6.88
942111AE2-223 GEN
Solar/Wind Harmer
5.983
276157O29GEN1
Solar/Wind Harmer
2.775
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
274853TWINGROVE;U1
Solar/Wind Harmer
4.996
965091AG1-374 GEN
Solar/Wind Harmer
20.795
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.537
972231SS25-0005
Solar/Wind Harmer
6.114
972181SS23-001
Solar/Wind Harmer
3.821
274752CRETE EC ;2U
Adder
3.149
274753CRETE EC ;3U
Adder
3.149
276686W4-005 GEN3
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.152
276668AB2-070 GEN1
Solar/Wind Harmer
1.245
276621W2-048 GEN
Solar/Wind Harmer
3.278
276838X2-022 GEN2
Solar/Wind Harmer
0.122
942481AE2-261 GEN
Solar/Wind Harmer
5.321
990512J1326
External Queue
3.782650947570801
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.939
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.596
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.239
MECLTFEXP_MEC->PJM
CLTF
9.345
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.161
TVALTFEXP_TVA->PJM
CLTF
0.817

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:124.6 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5557.2
MW Contribution:31.64
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
22.27
274774LINCOLN ;5U
50/50
22.27
274710KENDALL ;4C
50/50
3.516
274705KENDALL ;1S
50/50
2.163
972207SS24-0001
Solar/Wind Harmer
74.619
274745AC1-111 GEN9
Adder
16.369
274871GR RIDGE ;2U
Solar/Wind Harmer
22.472
941551AE2-152 GEN
Solar/Wind Harmer
13.134
960751AF2-366 GEN
Solar/Wind Harmer
8.072
962781AG1-127 GEN
Solar/Wind Harmer
26.756
274676JOLIET 29;8U
Adder
86.152
274872LEEDK;1U
Solar/Wind Harmer
23.004
274732ELWOOD EC;7P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
274828WAUKEGAN ;BP
Adder
30.754
274674JOLIET 9 ;6U
Adder
42.82
274751CRETE EC ;1U
Adder
13.493
274754CRETE EC ;4U
Adder
13.493
274812UNIV PK N;8U
Adder
13.776
276861AD2-134 GEN
Solar/Wind Harmer
4.891
957471AF2-041 GEN
Solar/Wind Harmer
80.791
959081AF2-199 GEN
Solar/Wind Harmer
26.93
971067AG2-660 GEN
Solar/Wind Harmer
6.263
276776AD2-060 GEN
Solar/Wind Harmer
1.137
971997AH1-543 GEN
Solar/Wind Harmer
42.004
939401AE1-172 GEN
Solar/Wind Harmer
37.187
274822ROCKFORD ;11
Adder
52.349
972235AH1-702 GEN1
Adder
6.693
970819AG2-516 GEN
Solar/Wind Harmer
31.637
274770LINCOLN ;1U
50/50
22.27
274771LINCOLN ;2U
50/50
22.27
274709KENDALL ;3S
50/50
2.347
274711KENDALL ;4S
50/50
2.347
274661LASCO STA;2U
50/50
21.82
972259AH1-714 GEN
50/50
61.247
274660LASCO STA;1U
50/50
22.099
971573AH1-285 GEN
Solar/Wind Harmer
25.349
274847GR RIDGE ;BU
Solar/Wind Harmer
14.782
274695ROCKY RD ;2P
Adder
31.631
274693ROCKY RD ;1P
Adder
31.319
274697ROCKY RD ;3P
Adder
8.593
274696ROCKY RD ;4P
Adder
32.374
962691AG1-118 GEN
Solar/Wind Harmer
84.831
970921AG2-575 GEN
Solar/Wind Harmer
28.134
970921AG2-575 GEN
Solar/Wind Harmer
6.543
274683WAUKEGAN ;8U
Adder
58.671
274683WAUKEGAN ;8U
Adder
49.457
274674JOLIET 9 ;6U
Adder
42.82
274808UNIV PK N;4U
Adder
13.716
942991AE2-321 GEN
Solar/Wind Harmer
27.42
971333AH1-146 GEN
Solar/Wind Harmer
54.429
971335AH1-147 GEN
Solar/Wind Harmer
54.429
971341AH1-150 GEN
Solar/Wind Harmer
53.86
971343AH1-151 GEN
Solar/Wind Harmer
53.86
274888KELLY CRK;1U
Solar/Wind Harmer
15.872
274887GEN-1.85
Solar/Wind Harmer
14.329
276843GEN-1.7
Solar/Wind Harmer
1.542
958011AF2-095 GEN
Solar/Wind Harmer
38.712
274803UNIV PARK;6U
Adder
15.613
274861TOP CROP ;1U
Solar/Wind Harmer
15.922
274862TOP CROP ;2U
Solar/Wind Harmer
13.295
274856ECOGROVE ;U1
Solar/Wind Harmer
8.862
276611AD2-172 GEN
Solar/Wind Harmer
6.724
958481AF2-142 GEN
Solar/Wind Harmer
39.387
274879MINONK ;1U
Solar/Wind Harmer
17.567
938861AE1-114 GEN
Solar/Wind Harmer
21.245
958491AF2-143 GEN
Solar/Wind Harmer
38.653
274764LEE CO EC;5U
Adder
23.99
274765LEE CO EC;6U
Adder
23.99
274762LEE CO EC;3U
Adder
23.934
274763LEE CO EC;4U
Adder
23.708
276603SUBLETTE C
Solar/Wind Harmer
2.688
972267AH1-718 GEN
Adder
10.486
276872AE1-163_GEN1
Solar/Wind Harmer
16.854
276741O09 GEN1
Solar/Wind Harmer
8.861
276708O09 GEN2
Solar/Wind Harmer
8.861
274851PROVIDENC;RU
Solar/Wind Harmer
6.782
274849CRESCENT ;1U
Solar/Wind Harmer
4.403
276645AC1-214 GEN1
Solar/Wind Harmer
3.19
276646AC1-214 GEN2
Solar/Wind Harmer
3.19
276782AC1-033 GEN
Solar/Wind Harmer
9.432
960611AF2-352 GEN
Solar/Wind Harmer
4.791
276763AC1-053 GEN1
Solar/Wind Harmer
6.509
276764AC1-053 GEN2
Solar/Wind Harmer
6.509
274772LINCOLN ;3U
50/50
22.27
274707KENDALL ;2S
50/50
2.163
970707AG2-453 GEN
Solar/Wind Harmer
89.854
943121AE2-341 GEN
Solar/Wind Harmer
44.875
943591AF1-030 GEN
Solar/Wind Harmer
29.917
276897AD1-100 C
Solar/Wind Harmer
84.043
939351AE1-166 GEN
Solar/Wind Harmer
17.172
972228AH1-698 GEN2
Adder
10.617
274676JOLIET 29;8U
Adder
83.076
274775LINCOLN ;6U
50/50
22.27
274776LINCOLN ;7U
50/50
22.27
274777LINCOLN ;8U
50/50
22.27
274708KENDALL ;3C
50/50
3.543
274704KENDALL ;1C
50/50
3.239
274706KENDALL ;2C
50/50
3.239
274746AC1-111 G10
Adder
16.369
274744AC1-111 GEN8
Adder
16.369
970833AG2-524 GEN
Solar/Wind Harmer
25.435
970833AG2-524 GEN
Solar/Wind Harmer
11.83
972227AH1-698 GEN1
Adder
7.478
274675JOLIET 29;7U
Adder
86.159
274675JOLIET 29;7U
Adder
83.082
274731ELWOOD EC;2P
Adder
45.944
274733ELWOOD EC;3P
Adder
45.944
274735ELWOOD EC;4P
Adder
45.944
274728ELWOOD EC;5P
Adder
45.935
274687WILL CNTY;4U
Adder
77.13
274687WILL CNTY;4U
Adder
77.13
274814UNIV PK N;0U
Adder
13.897
274807UNIV PK N;3U
Adder
13.867
274805UNIV PK N;1U
Adder
13.806
274811UNIV PK N;7U
Adder
13.776
971177AH1-047 GEN
Solar/Wind Harmer
16.058
971675AH1-338 GEN
Solar/Wind Harmer
49.322
971411AH1-196 GEN
Solar/Wind Harmer
40.764
971171AH1-044 GEN
Solar/Wind Harmer
53.86
960591AF2-350 GEN
Solar/Wind Harmer
26.883
972037AH1-567 GEN1
Adder
0.49
274823ROCKFORD ;21
Adder
51.969
276612AE2-035 GEN
Solar/Wind Harmer
6.724
276868AE1-113 GEN
Solar/Wind Harmer
26.349
276882AE2-255 GEN
Solar/Wind Harmer
8.784
971681AH1-341 GEN
Solar/Wind Harmer
38.904
274827FISK ;RP
Adder
20.119
274863CRW1-WTG
Solar/Wind Harmer
14.274
274864CRW2-WTG
Solar/Wind Harmer
14.274
961011AF2-392 GEN
Solar/Wind Harmer
27.512
926823AC1-168 GEN
Solar/Wind Harmer
10.809
274872LEEDK;1U
Solar/Wind Harmer
0.716
274729ELWOOD EC;1P
Adder
45.944
274730ELWOOD EC;6P
Adder
45.935
274734ELWOOD EC;8P
Adder
45.935
274736ELWOOD EC;9P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
972231SS25-0005
Solar/Wind Harmer
26.198
972181SS23-001
Solar/Wind Harmer
16.374
274752CRETE EC ;2U
Adder
13.493
274753CRETE EC ;3U
Adder
13.493
276799AD1-013 GEN
Solar/Wind Harmer
6.064
946671AF1-331 GEN
Solar/Wind Harmer
1.148
274855GSG-6 ;RU
Solar/Wind Harmer
10.113
274850MENDOTA H;RU
Solar/Wind Harmer
7.032
276602WESTBROOK C
Solar/Wind Harmer
5.821
276863AD2-134 GEN
Solar/Wind Harmer
4.891
276893AG1-478 C
Solar/Wind Harmer
1.142
959091AF2-200 GEN
Solar/Wind Harmer
53.86
276772AC2-154 GEN
Solar/Wind Harmer
7.497
276806AD2-047 C O1
Solar/Wind Harmer
28.759
970941AG2-585 GEN
Solar/Wind Harmer
33.604
274802UNIV PARK;5U
Adder
15.613
972236AH1-702 GEN2
Adder
5.82
276694AA1-018 GEN2
Solar/Wind Harmer
16.571
274800UNIV PARK;3U
Adder
15.181
972038AH1-567 GEN2
Adder
0.95
274826FISK ;BP
Adder
28.388
276805AD2-038 GEN
Solar/Wind Harmer
13.219
274858EASY ROAD;U2
Solar/Wind Harmer
12.328
274760LEE CO EC;1U
Adder
23.934
274767LEE CO EC;8U
Adder
23.652
276889AE2-281 GEN
Solar/Wind Harmer
4.816
276157O29GEN1
Solar/Wind Harmer
9.436
970571AG2-364 GEN
Solar/Wind Harmer
49.252
274878BISHOP HL;2U
Solar/Wind Harmer
7.982
965931AG1-462 GEN
Solar/Wind Harmer
59.553
942111AE2-223 GEN
Solar/Wind Harmer
17.755
274724RIVER EC ;11
Adder
36.677
274853TWINGROVE;U1
Solar/Wind Harmer
14.849
965091AG1-374 GEN
Solar/Wind Harmer
61.805
959611AF2-252 GEN
Solar/Wind Harmer
4.791
276686W4-005 GEN3
Solar/Wind Harmer
5.072
971993AH1-541 GEN
Solar/Wind Harmer
15.492
276668AB2-070 GEN1
Solar/Wind Harmer
3.758
276621W2-048 GEN
Solar/Wind Harmer
9.939
276838X2-022 GEN2
Solar/Wind Harmer
0.371
276691AA1-018 GEN1
Solar/Wind Harmer
1.223
971475AH1-234 GEN
Solar/Wind Harmer
58.741
276901AD2-066 C O1
Solar/Wind Harmer
9.209
274801UNIV PARK;4U
Adder
15.181
274857EASY ROAD;U1
Solar/Wind Harmer
12.328
274761LEE CO EC;2U
Adder
23.934
274766LEE CO EC;7U
Adder
23.652
276876AE1-163_GEN2
Solar/Wind Harmer
16.854
276158O29GEN2
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
73.878
276164X3-005 C
Solar/Wind Harmer
1.663
274877BISHOP HL;1U
Solar/Wind Harmer
7.982
276726Z2-087_GEN
Solar/Wind Harmer
17.13
939741AE1-205 GEN
Solar/Wind Harmer
43.316
274854TWINGROVE;U2
Solar/Wind Harmer
14.538
274723RIVER EC ;12
Adder
36.664
972175AH1-670 GEN
Solar/Wind Harmer
25.367
274880W4-005 GEN4
Solar/Wind Harmer
5.072
963831AG1-236 GEN
Solar/Wind Harmer
16.191
276615X2-022 GEN
Solar/Wind Harmer
3.121
970169AG2-114 GEN
Solar/Wind Harmer
24.498
957751AF2-069 GEN
Solar/Wind Harmer
1.093
946321AF1-296 GEN
Solar/Wind Harmer
24.654
274848CAMPGROVE;RU
Solar/Wind Harmer
15.052
276655WTG1_EQ
Solar/Wind Harmer
18.909
276656WTG2_EQ
Solar/Wind Harmer
2.504
959341AF2-225 GEN
Solar/Wind Harmer
32.487
941731AE2-173 GEN
Solar/Wind Harmer
12.592
276785W4-005 GEN1
Solar/Wind Harmer
5.072
276174W4-005 GEN2
Solar/Wind Harmer
5.072
276849AB2-070 GEN2
Solar/Wind Harmer
3.758
276848AB2-070 GEN3
Solar/Wind Harmer
3.758
990512J1326
External Queue
13.405387878417969
990727J1377 G
External Queue
9.246102333068848
991092J1477
External Queue
7.122580528259277
990407J1304
External Queue
10.39168643951416
NYPJM->LTFIMP_NY
CLTF
2.49
WECLTFEXP_WEC->PJM
CLTF
10.032
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.996
AG2-052LTFEXP_AG2-052->PJM
LTF
0.071
AH1-155LTFEXP_AH1-155->PJM
LTF
0.107
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
166.639
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.837
MECLTFEXP_MEC->PJM
CLTF
31.333
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.433
LAGNLTFEXP_LAGN->PJM
CLTF
10.191
TVALTFEXP_TVA->PJM
CLTF
2.55

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A


Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:122.97 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5484.63
MW Contribution:31.64
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
22.27
274776LINCOLN ;7U
50/50
22.27
274777LINCOLN ;8U
50/50
22.27
274708KENDALL ;3C
50/50
3.543
274704KENDALL ;1C
50/50
3.239
274706KENDALL ;2C
50/50
3.239
274746AC1-111 G10
Adder
16.369
274744AC1-111 GEN8
Adder
16.369
970833AG2-524 GEN
Solar/Wind Harmer
25.435
970833AG2-524 GEN
Solar/Wind Harmer
11.83
972227AH1-698 GEN1
Adder
7.478
274675JOLIET 29;7U
Adder
86.159
274675JOLIET 29;7U
Adder
83.082
274731ELWOOD EC;2P
Adder
45.944
274733ELWOOD EC;3P
Adder
45.944
274735ELWOOD EC;4P
Adder
45.944
274728ELWOOD EC;5P
Adder
45.935
274687WILL CNTY;4U
Adder
77.13
274687WILL CNTY;4U
Adder
77.13
274814UNIV PK N;0U
Adder
13.897
274807UNIV PK N;3U
Adder
13.867
274805UNIV PK N;1U
Adder
13.806
274811UNIV PK N;7U
Adder
13.776
971177AH1-047 GEN
Solar/Wind Harmer
16.058
971675AH1-338 GEN
Solar/Wind Harmer
49.322
971411AH1-196 GEN
Solar/Wind Harmer
40.764
971171AH1-044 GEN
Solar/Wind Harmer
53.86
960591AF2-350 GEN
Solar/Wind Harmer
26.883
972037AH1-567 GEN1
Adder
0.49
274823ROCKFORD ;21
Adder
51.969
276612AE2-035 GEN
Solar/Wind Harmer
6.724
276868AE1-113 GEN
Solar/Wind Harmer
26.349
276882AE2-255 GEN
Solar/Wind Harmer
8.784
971681AH1-341 GEN
Solar/Wind Harmer
38.904
274827FISK ;RP
Adder
20.119
274863CRW1-WTG
Solar/Wind Harmer
14.274
274864CRW2-WTG
Solar/Wind Harmer
14.274
961011AF2-392 GEN
Solar/Wind Harmer
27.512
926823AC1-168 GEN
Solar/Wind Harmer
10.809
970169AG2-114 GEN
Solar/Wind Harmer
24.498
957751AF2-069 GEN
Solar/Wind Harmer
1.093
946321AF1-296 GEN
Solar/Wind Harmer
24.654
274848CAMPGROVE;RU
Solar/Wind Harmer
15.052
276655WTG1_EQ
Solar/Wind Harmer
18.909
276656WTG2_EQ
Solar/Wind Harmer
2.504
959341AF2-225 GEN
Solar/Wind Harmer
32.487
941731AE2-173 GEN
Solar/Wind Harmer
12.592
276785W4-005 GEN1
Solar/Wind Harmer
5.072
276174W4-005 GEN2
Solar/Wind Harmer
5.072
276849AB2-070 GEN2
Solar/Wind Harmer
3.758
276848AB2-070 GEN3
Solar/Wind Harmer
3.758
274773LINCOLN ;4U
50/50
22.27
274774LINCOLN ;5U
50/50
22.27
274710KENDALL ;4C
50/50
3.516
274705KENDALL ;1S
50/50
2.163
972207SS24-0001
Solar/Wind Harmer
74.619
274745AC1-111 GEN9
Adder
16.369
274871GR RIDGE ;2U
Solar/Wind Harmer
22.472
941551AE2-152 GEN
Solar/Wind Harmer
13.134
960751AF2-366 GEN
Solar/Wind Harmer
8.072
962781AG1-127 GEN
Solar/Wind Harmer
26.756
274676JOLIET 29;8U
Adder
86.152
274872LEEDK;1U
Solar/Wind Harmer
23.004
274732ELWOOD EC;7P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
274828WAUKEGAN ;BP
Adder
30.754
274674JOLIET 9 ;6U
Adder
42.82
274812UNIV PK N;8U
Adder
13.776
276861AD2-134 GEN
Solar/Wind Harmer
4.891
957471AF2-041 GEN
Solar/Wind Harmer
80.791
959081AF2-199 GEN
Solar/Wind Harmer
26.93
971067AG2-660 GEN
Solar/Wind Harmer
6.263
276776AD2-060 GEN
Solar/Wind Harmer
1.137
971997AH1-543 GEN
Solar/Wind Harmer
42.004
939401AE1-172 GEN
Solar/Wind Harmer
37.187
274822ROCKFORD ;11
Adder
52.349
972235AH1-702 GEN1
Adder
6.693
970819AG2-516 GEN
Solar/Wind Harmer
31.637
276691AA1-018 GEN1
Solar/Wind Harmer
1.223
971475AH1-234 GEN
Solar/Wind Harmer
58.741
276901AD2-066 C O1
Solar/Wind Harmer
9.209
274801UNIV PARK;4U
Adder
15.181
274857EASY ROAD;U1
Solar/Wind Harmer
12.328
274761LEE CO EC;2U
Adder
23.934
274766LEE CO EC;7U
Adder
23.652
276876AE1-163_GEN2
Solar/Wind Harmer
16.854
276158O29GEN2
Solar/Wind Harmer
12.405
970569AG2-363 GEN
Solar/Wind Harmer
73.878
276164X3-005 C
Solar/Wind Harmer
1.663
274877BISHOP HL;1U
Solar/Wind Harmer
7.982
276726Z2-087_GEN
Solar/Wind Harmer
17.13
939741AE1-205 GEN
Solar/Wind Harmer
43.316
274854TWINGROVE;U2
Solar/Wind Harmer
14.538
274723RIVER EC ;12
Adder
36.664
972175AH1-670 GEN
Solar/Wind Harmer
25.367
274880W4-005 GEN4
Solar/Wind Harmer
5.072
963831AG1-236 GEN
Solar/Wind Harmer
16.191
276615X2-022 GEN
Solar/Wind Harmer
3.121
274770LINCOLN ;1U
50/50
22.27
274771LINCOLN ;2U
50/50
22.27
274709KENDALL ;3S
50/50
2.347
274711KENDALL ;4S
50/50
2.347
274661LASCO STA;2U
50/50
21.82
972259AH1-714 GEN
50/50
61.247
274660LASCO STA;1U
50/50
22.099
971573AH1-285 GEN
Solar/Wind Harmer
25.349
274847GR RIDGE ;BU
Solar/Wind Harmer
14.782
274695ROCKY RD ;2P
Adder
31.631
274693ROCKY RD ;1P
Adder
31.319
274697ROCKY RD ;3P
Adder
8.593
274696ROCKY RD ;4P
Adder
32.374
962691AG1-118 GEN
Solar/Wind Harmer
84.831
970921AG2-575 GEN
Solar/Wind Harmer
28.134
970921AG2-575 GEN
Solar/Wind Harmer
6.543
274683WAUKEGAN ;8U
Adder
58.671
274683WAUKEGAN ;8U
Adder
49.457
274674JOLIET 9 ;6U
Adder
42.82
274808UNIV PK N;4U
Adder
13.716
942991AE2-321 GEN
Solar/Wind Harmer
27.42
971333AH1-146 GEN
Solar/Wind Harmer
54.429
971335AH1-147 GEN
Solar/Wind Harmer
54.429
971341AH1-150 GEN
Solar/Wind Harmer
53.86
971343AH1-151 GEN
Solar/Wind Harmer
53.86
274888KELLY CRK;1U
Solar/Wind Harmer
15.872
274887GEN-1.85
Solar/Wind Harmer
14.329
276843GEN-1.7
Solar/Wind Harmer
1.542
958011AF2-095 GEN
Solar/Wind Harmer
38.712
274803UNIV PARK;6U
Adder
15.613
274861TOP CROP ;1U
Solar/Wind Harmer
15.922
274862TOP CROP ;2U
Solar/Wind Harmer
13.295
274856ECOGROVE ;U1
Solar/Wind Harmer
8.862
276611AD2-172 GEN
Solar/Wind Harmer
6.724
958481AF2-142 GEN
Solar/Wind Harmer
39.387
274879MINONK ;1U
Solar/Wind Harmer
17.567
938861AE1-114 GEN
Solar/Wind Harmer
21.245
958491AF2-143 GEN
Solar/Wind Harmer
38.653
274764LEE CO EC;5U
Adder
23.99
274765LEE CO EC;6U
Adder
23.99
274762LEE CO EC;3U
Adder
23.934
274763LEE CO EC;4U
Adder
23.708
276603SUBLETTE C
Solar/Wind Harmer
2.688
972267AH1-718 GEN
Adder
10.486
276872AE1-163_GEN1
Solar/Wind Harmer
16.854
276741O09 GEN1
Solar/Wind Harmer
8.861
276708O09 GEN2
Solar/Wind Harmer
8.861
274851PROVIDENC;RU
Solar/Wind Harmer
6.782
274849CRESCENT ;1U
Solar/Wind Harmer
4.403
276645AC1-214 GEN1
Solar/Wind Harmer
3.19
276646AC1-214 GEN2
Solar/Wind Harmer
3.19
276782AC1-033 GEN
Solar/Wind Harmer
9.432
960611AF2-352 GEN
Solar/Wind Harmer
4.791
274772LINCOLN ;3U
50/50
22.27
274707KENDALL ;2S
50/50
2.163
970707AG2-453 GEN
Solar/Wind Harmer
89.854
943121AE2-341 GEN
Solar/Wind Harmer
44.875
943591AF1-030 GEN
Solar/Wind Harmer
29.917
276897AD1-100 C
Solar/Wind Harmer
84.043
939351AE1-166 GEN
Solar/Wind Harmer
17.172
972228AH1-698 GEN2
Adder
10.617
274676JOLIET 29;8U
Adder
83.076
274872LEEDK;1U
Solar/Wind Harmer
0.716
274729ELWOOD EC;1P
Adder
45.944
274730ELWOOD EC;6P
Adder
45.935
274734ELWOOD EC;8P
Adder
45.935
274736ELWOOD EC;9P
Adder
45.935
274682WAUKEGAN ;7U
Adder
50.15
276799AD1-013 GEN
Solar/Wind Harmer
6.064
946671AF1-331 GEN
Solar/Wind Harmer
1.148
274855GSG-6 ;RU
Solar/Wind Harmer
10.113
274850MENDOTA H;RU
Solar/Wind Harmer
7.032
276602WESTBROOK C
Solar/Wind Harmer
5.821
276863AD2-134 GEN
Solar/Wind Harmer
4.891
276893AG1-478 C
Solar/Wind Harmer
1.142
959091AF2-200 GEN
Solar/Wind Harmer
53.86
276772AC2-154 GEN
Solar/Wind Harmer
7.497
276806AD2-047 C O1
Solar/Wind Harmer
28.759
970941AG2-585 GEN
Solar/Wind Harmer
33.604
274802UNIV PARK;5U
Adder
15.613
972236AH1-702 GEN2
Adder
5.82
276694AA1-018 GEN2
Solar/Wind Harmer
16.571
274800UNIV PARK;3U
Adder
15.181
972038AH1-567 GEN2
Adder
0.95
274826FISK ;BP
Adder
28.388
276805AD2-038 GEN
Solar/Wind Harmer
13.219
274858EASY ROAD;U2
Solar/Wind Harmer
12.328
274760LEE CO EC;1U
Adder
23.934
274767LEE CO EC;8U
Adder
23.652
276889AE2-281 GEN
Solar/Wind Harmer
4.816
276157O29GEN1
Solar/Wind Harmer
9.436
970571AG2-364 GEN
Solar/Wind Harmer
49.252
274878BISHOP HL;2U
Solar/Wind Harmer
7.982
965931AG1-462 GEN
Solar/Wind Harmer
59.553
942111AE2-223 GEN
Solar/Wind Harmer
17.755
274724RIVER EC ;11
Adder
36.677
274853TWINGROVE;U1
Solar/Wind Harmer
14.849
965091AG1-374 GEN
Solar/Wind Harmer
61.805
959611AF2-252 GEN
Solar/Wind Harmer
4.791
276686W4-005 GEN3
Solar/Wind Harmer
5.072
971993AH1-541 GEN
Solar/Wind Harmer
15.492
276668AB2-070 GEN1
Solar/Wind Harmer
3.758
276621W2-048 GEN
Solar/Wind Harmer
9.939
276838X2-022 GEN2
Solar/Wind Harmer
0.371
276763AC1-053 GEN1
Solar/Wind Harmer
6.509
276764AC1-053 GEN2
Solar/Wind Harmer
6.509
990512J1326
External Queue
13.405387878417969
990117J1214
External Queue
17.517770767211914
990727J1377 G
External Queue
15.634285926818848
991092J1477
External Queue
7.122580528259277
990407J1304
External Queue
10.39168643951416
NYPJM->LTFIMP_NY
CLTF
2.49
WECLTFEXP_WEC->PJM
CLTF
10.032
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.053
CBM West 2LTFEXP_CBM-W2->PJM
CBM
73.996
AG2-052LTFEXP_AG2-052->PJM
LTF
0.071
AH1-155LTFEXP_AH1-155->PJM
LTF
0.107
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.527
CBM West 1LTFEXP_CBM-W1->PJM
CBM
166.639
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.837
MECLTFEXP_MEC->PJM
CLTF
31.333
SIGELTFEXP_SIGE->PJM
CLTF
0.035
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.215
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.433
LAGNLTFEXP_LAGN->PJM
CLTF
10.191
TVALTFEXP_TVA->PJM
CLTF
2.55

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P4_#2973_05DUMONT 345_F1_SRT-A


Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2973_05DUMONT 345_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.03 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5085.85
MW Contribution:29.02
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
21.157
274774LINCOLN ;5U
50/50
21.157
274710KENDALL ;4C
50/50
3.236
274705KENDALL ;1S
50/50
1.96
972207SS24-0001
Solar/Wind Harmer
70.889
274745AC1-111 GEN9
Adder
15.051
274871GR RIDGE ;2U
Solar/Wind Harmer
20.522
941551AE2-152 GEN
Solar/Wind Harmer
12.084
960751AF2-366 GEN
Solar/Wind Harmer
7.424
962781AG1-127 GEN
Solar/Wind Harmer
24.608
274872LEEDK;1U
Solar/Wind Harmer
21.16
274674JOLIET 9 ;6U
Adder
39.35
274682WAUKEGAN ;7U
Adder
45.848
274828WAUKEGAN ;BP
Adder
28.118
274676JOLIET 29;8U
Adder
77.975
274732ELWOOD EC;7P
Adder
41.564
276861AD2-134 GEN
Solar/Wind Harmer
4.496
276776AD2-060 GEN
Solar/Wind Harmer
1.053
957471AF2-041 GEN
Solar/Wind Harmer
74.193
959081AF2-199 GEN
Solar/Wind Harmer
24.731
971067AG2-660 GEN
Solar/Wind Harmer
5.751
939401AE1-172 GEN
Solar/Wind Harmer
34.433
274822ROCKFORD ;11
Adder
48.026
971997AH1-543 GEN
Solar/Wind Harmer
38.509
972235AH1-702 GEN1
Adder
6.141
274801UNIV PARK;4U
Adder
14.189
970819AG2-516 GEN
Solar/Wind Harmer
29.024
971475AH1-234 GEN
Solar/Wind Harmer
53.881
276901AD2-066 C O1
Solar/Wind Harmer
8.402
276691AA1-018 GEN1
Solar/Wind Harmer
1.104
274857EASY ROAD;U1
Solar/Wind Harmer
11.314
274761LEE CO EC;2U
Adder
21.966
274766LEE CO EC;7U
Adder
21.707
276164X3-005 C
Solar/Wind Harmer
1.649
276876AE1-163_GEN2
Solar/Wind Harmer
15.294
276158O29GEN2
Solar/Wind Harmer
11.382
970569AG2-363 GEN
Solar/Wind Harmer
67.19
274723RIVER EC ;12
Adder
39.002
274877BISHOP HL;1U
Solar/Wind Harmer
7.314
274812UNIV PK N;8U
Adder
10.613
276726Z2-087_GEN
Solar/Wind Harmer
15.875
939741AE1-205 GEN
Solar/Wind Harmer
40.143
274854TWINGROVE;U2
Solar/Wind Harmer
13.48
274751CRETE EC ;1U
Adder
9.016
274754CRETE EC ;4U
Adder
9.016
972175AH1-670 GEN
Solar/Wind Harmer
23.556
274880W4-005 GEN4
Solar/Wind Harmer
4.717
963831AG1-236 GEN
Solar/Wind Harmer
15.059
276615X2-022 GEN
Solar/Wind Harmer
2.903
274775LINCOLN ;6U
50/50
21.157
274776LINCOLN ;7U
50/50
21.157
274777LINCOLN ;8U
50/50
21.157
274708KENDALL ;3C
50/50
3.26
274704KENDALL ;1C
50/50
2.936
274706KENDALL ;2C
50/50
2.936
274746AC1-111 G10
Adder
15.051
274744AC1-111 GEN8
Adder
15.051
970833AG2-524 GEN
Solar/Wind Harmer
23.244
970833AG2-524 GEN
Solar/Wind Harmer
10.811
972227AH1-698 GEN1
Adder
6.713
274675JOLIET 29;7U
Adder
77.983
274675JOLIET 29;7U
Adder
75.198
274731ELWOOD EC;2P
Adder
41.578
274733ELWOOD EC;3P
Adder
41.578
274735ELWOOD EC;4P
Adder
41.578
274728ELWOOD EC;5P
Adder
41.564
971675AH1-338 GEN
Solar/Wind Harmer
45.346
971177AH1-047 GEN
Solar/Wind Harmer
14.728
274687WILL CNTY;4U
Adder
70.005
274687WILL CNTY;4U
Adder
70.005
971411AH1-196 GEN
Solar/Wind Harmer
37.385
960591AF2-350 GEN
Solar/Wind Harmer
24.907
971171AH1-044 GEN
Solar/Wind Harmer
49.462
274823ROCKFORD ;21
Adder
47.678
274827FISK ;RP
Adder
18.702
276612AE2-035 GEN
Solar/Wind Harmer
6.17
971681AH1-341 GEN
Solar/Wind Harmer
35.709
274863CRW1-WTG
Solar/Wind Harmer
13.216
274864CRW2-WTG
Solar/Wind Harmer
13.216
276868AE1-113 GEN
Solar/Wind Harmer
23.946
276882AE2-255 GEN
Solar/Wind Harmer
7.983
972037AH1-567 GEN1
Adder
0.431
961011AF2-392 GEN
Solar/Wind Harmer
25.254
926823AC1-168 GEN
Solar/Wind Harmer
9.892
970169AG2-114 GEN
Solar/Wind Harmer
22.646
957751AF2-069 GEN
Solar/Wind Harmer
1.002
946321AF1-296 GEN
Solar/Wind Harmer
22.629
274848CAMPGROVE;RU
Solar/Wind Harmer
13.793
274814UNIV PK N;0U
Adder
10.706
274807UNIV PK N;3U
Adder
10.683
274805UNIV PK N;1U
Adder
10.637
274811UNIV PK N;7U
Adder
10.613
276655WTG1_EQ
Solar/Wind Harmer
17.524
276656WTG2_EQ
Solar/Wind Harmer
2.32
959341AF2-225 GEN
Solar/Wind Harmer
30.107
941731AE2-173 GEN
Solar/Wind Harmer
11.669
276785W4-005 GEN1
Solar/Wind Harmer
4.717
276174W4-005 GEN2
Solar/Wind Harmer
4.717
276849AB2-070 GEN2
Solar/Wind Harmer
3.495
276848AB2-070 GEN3
Solar/Wind Harmer
3.495
274770LINCOLN ;1U
50/50
21.157
274771LINCOLN ;2U
50/50
21.157
274709KENDALL ;3S
50/50
2.16
274711KENDALL ;4S
50/50
2.16
274661LASCO STA;2U
50/50
19.909
972259AH1-714 GEN
50/50
55.882
274660LASCO STA;1U
50/50
20.163
971573AH1-285 GEN
Solar/Wind Harmer
23.377
274847GR RIDGE ;BU
Solar/Wind Harmer
13.499
274695ROCKY RD ;2P
Adder
29.021
274693ROCKY RD ;1P
Adder
28.736
274697ROCKY RD ;3P
Adder
7.884
274696ROCKY RD ;4P
Adder
29.703
962691AG1-118 GEN
Solar/Wind Harmer
78.028
970921AG2-575 GEN
Solar/Wind Harmer
25.876
970921AG2-575 GEN
Solar/Wind Harmer
6.018
274674JOLIET 9 ;6U
Adder
39.35
274683WAUKEGAN ;8U
Adder
53.641
274683WAUKEGAN ;8U
Adder
45.217
942991AE2-321 GEN
Solar/Wind Harmer
25.147
971333AH1-146 GEN
Solar/Wind Harmer
49.953
971335AH1-147 GEN
Solar/Wind Harmer
49.953
274888KELLY CRK;1U
Solar/Wind Harmer
14.705
274887GEN-1.85
Solar/Wind Harmer
13.276
276843GEN-1.7
Solar/Wind Harmer
1.428
958011AF2-095 GEN
Solar/Wind Harmer
35.866
971341AH1-150 GEN
Solar/Wind Harmer
49.462
971343AH1-151 GEN
Solar/Wind Harmer
49.462
274856ECOGROVE ;U1
Solar/Wind Harmer
8.131
276611AD2-172 GEN
Solar/Wind Harmer
6.17
938861AE1-114 GEN
Solar/Wind Harmer
19.498
958481AF2-142 GEN
Solar/Wind Harmer
35.557
274879MINONK ;1U
Solar/Wind Harmer
15.966
274764LEE CO EC;5U
Adder
22.018
274765LEE CO EC;6U
Adder
22.018
274762LEE CO EC;3U
Adder
21.966
274763LEE CO EC;4U
Adder
21.759
274861TOP CROP ;1U
Solar/Wind Harmer
14.292
274862TOP CROP ;2U
Solar/Wind Harmer
11.934
274803UNIV PARK;6U
Adder
13.721
276603SUBLETTE C
Solar/Wind Harmer
2.468
958491AF2-143 GEN
Solar/Wind Harmer
34.969
972267AH1-718 GEN
Adder
9.625
276872AE1-163_GEN1
Solar/Wind Harmer
15.294
276741O09 GEN1
Solar/Wind Harmer
8.13
276708O09 GEN2
Solar/Wind Harmer
8.13
274851PROVIDENC;RU
Solar/Wind Harmer
6.213
274849CRESCENT ;1U
Solar/Wind Harmer
4.034
276645AC1-214 GEN1
Solar/Wind Harmer
2.922
276646AC1-214 GEN2
Solar/Wind Harmer
2.922
276782AC1-033 GEN
Solar/Wind Harmer
8.643
274808UNIV PK N;4U
Adder
10.567
960611AF2-352 GEN
Solar/Wind Harmer
4.442
276763AC1-053 GEN1
Solar/Wind Harmer
6.054
276764AC1-053 GEN2
Solar/Wind Harmer
6.054
274772LINCOLN ;3U
50/50
21.157
274707KENDALL ;2S
50/50
1.96
970707AG2-453 GEN
Solar/Wind Harmer
83.143
943121AE2-341 GEN
Solar/Wind Harmer
41.418
943591AF1-030 GEN
Solar/Wind Harmer
27.612
276897AD1-100 C
Solar/Wind Harmer
77.321
939351AE1-166 GEN
Solar/Wind Harmer
15.799
274872LEEDK;1U
Solar/Wind Harmer
0.659
972228AH1-698 GEN2
Adder
9.531
274682WAUKEGAN ;7U
Adder
45.848
274676JOLIET 29;8U
Adder
75.19
274729ELWOOD EC;1P
Adder
41.578
274730ELWOOD EC;6P
Adder
41.564
274734ELWOOD EC;8P
Adder
41.564
274736ELWOOD EC;9P
Adder
41.564
276799AD1-013 GEN
Solar/Wind Harmer
5.575
946671AF1-331 GEN
Solar/Wind Harmer
1.056
274855GSG-6 ;RU
Solar/Wind Harmer
9.297
274850MENDOTA H;RU
Solar/Wind Harmer
6.465
276602WESTBROOK C
Solar/Wind Harmer
5.352
276863AD2-134 GEN
Solar/Wind Harmer
4.496
276893AG1-478 C
Solar/Wind Harmer
1.045
276772AC2-154 GEN
Solar/Wind Harmer
6.946
276806AD2-047 C O1
Solar/Wind Harmer
26.644
970941AG2-585 GEN
Solar/Wind Harmer
31.134
959091AF2-200 GEN
Solar/Wind Harmer
49.462
972236AH1-702 GEN2
Adder
5.34
274800UNIV PARK;3U
Adder
14.189
972038AH1-567 GEN2
Adder
0.888
274826FISK ;BP
Adder
26.389
276694AA1-018 GEN2
Solar/Wind Harmer
14.959
274858EASY ROAD;U2
Solar/Wind Harmer
11.314
274760LEE CO EC;1U
Adder
21.966
274767LEE CO EC;8U
Adder
21.707
274802UNIV PARK;5U
Adder
13.721
276805AD2-038 GEN
Solar/Wind Harmer
11.959
276889AE2-281 GEN
Solar/Wind Harmer
4.37
276157O29GEN1
Solar/Wind Harmer
8.657
970571AG2-364 GEN
Solar/Wind Harmer
44.793
274724RIVER EC ;11
Adder
38.714
274878BISHOP HL;2U
Solar/Wind Harmer
7.314
965931AG1-462 GEN
Solar/Wind Harmer
54.666
942111AE2-223 GEN
Solar/Wind Harmer
16.454
274853TWINGROVE;U1
Solar/Wind Harmer
13.768
965091AG1-374 GEN
Solar/Wind Harmer
57.308
959611AF2-252 GEN
Solar/Wind Harmer
4.442
972231SS25-0005
Solar/Wind Harmer
17.505
972181SS23-001
Solar/Wind Harmer
10.941
274752CRETE EC ;2U
Adder
9.016
274753CRETE EC ;3U
Adder
9.016
276686W4-005 GEN3
Solar/Wind Harmer
4.717
971993AH1-541 GEN
Solar/Wind Harmer
14.41
276668AB2-070 GEN1
Solar/Wind Harmer
3.495
276621W2-048 GEN
Solar/Wind Harmer
9.246
276838X2-022 GEN2
Solar/Wind Harmer
0.345
990512J1326
External Queue
12.000266075134277
990727J1377 G
External Queue
8.28534984588623
991092J1477
External Queue
6.35044002532959
990407J1304
External Queue
9.309322357177734
NYPJM->LTFIMP_NY
CLTF
2.297
WECLTFEXP_WEC->PJM
CLTF
9.183
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.822
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.958
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.476
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.51
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.612
MECLTFEXP_MEC->PJM
CLTF
28.811
SIGELTFEXP_SIGE->PJM
CLTF
0.043
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.049
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.934
LAGNLTFEXP_LAGN->PJM
CLTF
9.519
TVALTFEXP_TVA->PJM
CLTF
2.426

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P4_#2976_05DUMONT 345_F_SRT-A


Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2976_05DUMONT 345_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.85 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:5077.67
MW Contribution:28.97
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
21.122
274774LINCOLN ;5U
50/50
21.122
274710KENDALL ;4C
50/50
3.23
274705KENDALL ;1S
50/50
1.957
972207SS24-0001
Solar/Wind Harmer
70.774
274745AC1-111 GEN9
Adder
15.025
274871GR RIDGE ;2U
Solar/Wind Harmer
20.487
941551AE2-152 GEN
Solar/Wind Harmer
12.063
960751AF2-366 GEN
Solar/Wind Harmer
7.411
962781AG1-127 GEN
Solar/Wind Harmer
24.565
274872LEEDK;1U
Solar/Wind Harmer
21.122
274674JOLIET 9 ;6U
Adder
39.281
274682WAUKEGAN ;7U
Adder
45.767
274828WAUKEGAN ;BP
Adder
28.068
274676JOLIET 29;8U
Adder
77.837
274732ELWOOD EC;7P
Adder
41.49
276861AD2-134 GEN
Solar/Wind Harmer
4.488
276776AD2-060 GEN
Solar/Wind Harmer
1.051
957471AF2-041 GEN
Solar/Wind Harmer
74.06
959081AF2-199 GEN
Solar/Wind Harmer
24.687
971067AG2-660 GEN
Solar/Wind Harmer
5.741
939401AE1-172 GEN
Solar/Wind Harmer
34.371
274822ROCKFORD ;11
Adder
47.94
971997AH1-543 GEN
Solar/Wind Harmer
38.44
972235AH1-702 GEN1
Adder
6.13
274801UNIV PARK;4U
Adder
14.165
970819AG2-516 GEN
Solar/Wind Harmer
28.972
971475AH1-234 GEN
Solar/Wind Harmer
53.784
276901AD2-066 C O1
Solar/Wind Harmer
8.387
276691AA1-018 GEN1
Solar/Wind Harmer
1.102
274857EASY ROAD;U1
Solar/Wind Harmer
11.294
274761LEE CO EC;2U
Adder
21.926
274766LEE CO EC;7U
Adder
21.668
276164X3-005 C
Solar/Wind Harmer
1.646
276876AE1-163_GEN2
Solar/Wind Harmer
15.266
276158O29GEN2
Solar/Wind Harmer
11.361
970569AG2-363 GEN
Solar/Wind Harmer
67.065
274723RIVER EC ;12
Adder
38.937
274877BISHOP HL;1U
Solar/Wind Harmer
7.3
274812UNIV PK N;8U
Adder
10.592
276726Z2-087_GEN
Solar/Wind Harmer
15.844
939741AE1-205 GEN
Solar/Wind Harmer
40.064
274854TWINGROVE;U2
Solar/Wind Harmer
13.453
274751CRETE EC ;1U
Adder
8.996
274754CRETE EC ;4U
Adder
8.996
972175AH1-670 GEN
Solar/Wind Harmer
23.506
274880W4-005 GEN4
Solar/Wind Harmer
4.707
963831AG1-236 GEN
Solar/Wind Harmer
15.025
276615X2-022 GEN
Solar/Wind Harmer
2.896
274775LINCOLN ;6U
50/50
21.122
274776LINCOLN ;7U
50/50
21.122
274777LINCOLN ;8U
50/50
21.122
274708KENDALL ;3C
50/50
3.255
274704KENDALL ;1C
50/50
2.931
274706KENDALL ;2C
50/50
2.931
274746AC1-111 G10
Adder
15.025
274744AC1-111 GEN8
Adder
15.025
970833AG2-524 GEN
Solar/Wind Harmer
23.203
970833AG2-524 GEN
Solar/Wind Harmer
10.792
972227AH1-698 GEN1
Adder
6.701
274675JOLIET 29;7U
Adder
77.846
274675JOLIET 29;7U
Adder
75.065
274731ELWOOD EC;2P
Adder
41.504
274733ELWOOD EC;3P
Adder
41.504
274735ELWOOD EC;4P
Adder
41.504
274728ELWOOD EC;5P
Adder
41.49
971675AH1-338 GEN
Solar/Wind Harmer
45.265
971177AH1-047 GEN
Solar/Wind Harmer
14.702
274687WILL CNTY;4U
Adder
69.882
274687WILL CNTY;4U
Adder
69.882
971411AH1-196 GEN
Solar/Wind Harmer
37.319
960591AF2-350 GEN
Solar/Wind Harmer
24.863
971171AH1-044 GEN
Solar/Wind Harmer
49.374
274823ROCKFORD ;21
Adder
47.593
274827FISK ;RP
Adder
18.67
276612AE2-035 GEN
Solar/Wind Harmer
6.159
971681AH1-341 GEN
Solar/Wind Harmer
35.645
274863CRW1-WTG
Solar/Wind Harmer
13.191
274864CRW2-WTG
Solar/Wind Harmer
13.191
276868AE1-113 GEN
Solar/Wind Harmer
23.903
276882AE2-255 GEN
Solar/Wind Harmer
7.968
972037AH1-567 GEN1
Adder
0.43
961011AF2-392 GEN
Solar/Wind Harmer
25.208
926823AC1-168 GEN
Solar/Wind Harmer
9.873
970169AG2-114 GEN
Solar/Wind Harmer
22.604
957751AF2-069 GEN
Solar/Wind Harmer
1
946321AF1-296 GEN
Solar/Wind Harmer
22.587
274848CAMPGROVE;RU
Solar/Wind Harmer
13.767
274814UNIV PK N;0U
Adder
10.685
274807UNIV PK N;3U
Adder
10.662
274805UNIV PK N;1U
Adder
10.615
274811UNIV PK N;7U
Adder
10.592
276655WTG1_EQ
Solar/Wind Harmer
17.489
276656WTG2_EQ
Solar/Wind Harmer
2.316
959341AF2-225 GEN
Solar/Wind Harmer
30.048
941731AE2-173 GEN
Solar/Wind Harmer
11.646
276785W4-005 GEN1
Solar/Wind Harmer
4.707
276174W4-005 GEN2
Solar/Wind Harmer
4.707
276849AB2-070 GEN2
Solar/Wind Harmer
3.488
276848AB2-070 GEN3
Solar/Wind Harmer
3.488
274770LINCOLN ;1U
50/50
21.122
274771LINCOLN ;2U
50/50
21.122
274709KENDALL ;3S
50/50
2.157
274711KENDALL ;4S
50/50
2.157
274661LASCO STA;2U
50/50
19.875
972259AH1-714 GEN
50/50
55.786
274660LASCO STA;1U
50/50
20.128
971573AH1-285 GEN
Solar/Wind Harmer
23.337
274847GR RIDGE ;BU
Solar/Wind Harmer
13.476
274695ROCKY RD ;2P
Adder
28.97
274693ROCKY RD ;1P
Adder
28.685
274697ROCKY RD ;3P
Adder
7.87
274696ROCKY RD ;4P
Adder
29.651
962691AG1-118 GEN
Solar/Wind Harmer
77.891
970921AG2-575 GEN
Solar/Wind Harmer
25.831
970921AG2-575 GEN
Solar/Wind Harmer
6.007
274674JOLIET 9 ;6U
Adder
39.281
274683WAUKEGAN ;8U
Adder
53.547
274683WAUKEGAN ;8U
Adder
45.137
942991AE2-321 GEN
Solar/Wind Harmer
25.103
971333AH1-146 GEN
Solar/Wind Harmer
49.864
971335AH1-147 GEN
Solar/Wind Harmer
49.864
958011AF2-095 GEN
Solar/Wind Harmer
35.804
274888KELLY CRK;1U
Solar/Wind Harmer
14.679
274887GEN-1.85
Solar/Wind Harmer
13.253
276843GEN-1.7
Solar/Wind Harmer
1.426
971341AH1-150 GEN
Solar/Wind Harmer
49.374
971343AH1-151 GEN
Solar/Wind Harmer
49.374
274856ECOGROVE ;U1
Solar/Wind Harmer
8.116
276611AD2-172 GEN
Solar/Wind Harmer
6.159
938861AE1-114 GEN
Solar/Wind Harmer
19.463
958481AF2-142 GEN
Solar/Wind Harmer
35.492
274879MINONK ;1U
Solar/Wind Harmer
15.937
274764LEE CO EC;5U
Adder
21.978
274765LEE CO EC;6U
Adder
21.978
274762LEE CO EC;3U
Adder
21.926
274763LEE CO EC;4U
Adder
21.719
274861TOP CROP ;1U
Solar/Wind Harmer
14.266
274862TOP CROP ;2U
Solar/Wind Harmer
11.913
274803UNIV PARK;6U
Adder
13.696
276603SUBLETTE C
Solar/Wind Harmer
2.463
958491AF2-143 GEN
Solar/Wind Harmer
34.905
972267AH1-718 GEN
Adder
9.607
276872AE1-163_GEN1
Solar/Wind Harmer
15.266
276741O09 GEN1
Solar/Wind Harmer
8.115
276708O09 GEN2
Solar/Wind Harmer
8.115
274851PROVIDENC;RU
Solar/Wind Harmer
6.202
274849CRESCENT ;1U
Solar/Wind Harmer
4.026
276645AC1-214 GEN1
Solar/Wind Harmer
2.917
276646AC1-214 GEN2
Solar/Wind Harmer
2.917
276782AC1-033 GEN
Solar/Wind Harmer
8.627
274808UNIV PK N;4U
Adder
10.546
960611AF2-352 GEN
Solar/Wind Harmer
4.434
276763AC1-053 GEN1
Solar/Wind Harmer
6.04
276764AC1-053 GEN2
Solar/Wind Harmer
6.04
274772LINCOLN ;3U
50/50
21.122
274707KENDALL ;2S
50/50
1.957
970707AG2-453 GEN
Solar/Wind Harmer
83.003
943121AE2-341 GEN
Solar/Wind Harmer
41.346
943591AF1-030 GEN
Solar/Wind Harmer
27.564
276897AD1-100 C
Solar/Wind Harmer
77.187
939351AE1-166 GEN
Solar/Wind Harmer
15.771
274872LEEDK;1U
Solar/Wind Harmer
0.658
972228AH1-698 GEN2
Adder
9.514
274682WAUKEGAN ;7U
Adder
45.767
274676JOLIET 29;8U
Adder
75.057
274729ELWOOD EC;1P
Adder
41.504
274730ELWOOD EC;6P
Adder
41.49
274734ELWOOD EC;8P
Adder
41.49
274736ELWOOD EC;9P
Adder
41.49
276799AD1-013 GEN
Solar/Wind Harmer
5.565
946671AF1-331 GEN
Solar/Wind Harmer
1.054
274855GSG-6 ;RU
Solar/Wind Harmer
9.281
274850MENDOTA H;RU
Solar/Wind Harmer
6.453
276602WESTBROOK C
Solar/Wind Harmer
5.342
276863AD2-134 GEN
Solar/Wind Harmer
4.488
276893AG1-478 C
Solar/Wind Harmer
1.044
276772AC2-154 GEN
Solar/Wind Harmer
6.934
276806AD2-047 C O1
Solar/Wind Harmer
26.598
970941AG2-585 GEN
Solar/Wind Harmer
31.079
959091AF2-200 GEN
Solar/Wind Harmer
49.374
972236AH1-702 GEN2
Adder
5.33
274800UNIV PARK;3U
Adder
14.165
972038AH1-567 GEN2
Adder
0.887
274826FISK ;BP
Adder
26.343
276694AA1-018 GEN2
Solar/Wind Harmer
14.932
274858EASY ROAD;U2
Solar/Wind Harmer
11.294
274760LEE CO EC;1U
Adder
21.926
274767LEE CO EC;8U
Adder
21.668
274802UNIV PARK;5U
Adder
13.696
276805AD2-038 GEN
Solar/Wind Harmer
11.938
276889AE2-281 GEN
Solar/Wind Harmer
4.362
276157O29GEN1
Solar/Wind Harmer
8.642
970571AG2-364 GEN
Solar/Wind Harmer
44.71
274724RIVER EC ;11
Adder
38.651
274878BISHOP HL;2U
Solar/Wind Harmer
7.3
965931AG1-462 GEN
Solar/Wind Harmer
54.563
942111AE2-223 GEN
Solar/Wind Harmer
16.421
274853TWINGROVE;U1
Solar/Wind Harmer
13.74
965091AG1-374 GEN
Solar/Wind Harmer
57.192
959611AF2-252 GEN
Solar/Wind Harmer
4.434
972231SS25-0005
Solar/Wind Harmer
17.466
972181SS23-001
Solar/Wind Harmer
10.916
274752CRETE EC ;2U
Adder
8.996
274753CRETE EC ;3U
Adder
8.996
276686W4-005 GEN3
Solar/Wind Harmer
4.707
971993AH1-541 GEN
Solar/Wind Harmer
14.377
276668AB2-070 GEN1
Solar/Wind Harmer
3.488
276621W2-048 GEN
Solar/Wind Harmer
9.225
276838X2-022 GEN2
Solar/Wind Harmer
0.344
990512J1326
External Queue
11.96206283569336
990727J1377 G
External Queue
8.25949764251709
991092J1477
External Queue
6.326850414276123
990407J1304
External Queue
9.280413627624512
NYPJM->LTFIMP_NY
CLTF
2.293
WECLTFEXP_WEC->PJM
CLTF
9.166
CBM West 2LTFEXP_CBM-W2->PJM
CBM
69.555
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.961
AG2-052LTFEXP_AG2-052->PJM
LTF
0.239
AH1-155LTFEXP_AH1-155->PJM
LTF
0.358
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.479
CBM West 1LTFEXP_CBM-W1->PJM
CBM
158.704
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.559
MECLTFEXP_MEC->PJM
CLTF
28.752
SIGELTFEXP_SIGE->PJM
CLTF
0.042
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.057
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.96
LAGNLTFEXP_LAGN->PJM
CLTF
9.484
TVALTFEXP_TVA->PJM
CLTF
2.412

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A


Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.23 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4826.97
MW Contribution:27.36
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
20.173
274776LINCOLN ;7U
50/50
20.173
274777LINCOLN ;8U
50/50
20.173
274708KENDALL ;3C
50/50
3.082
274704KENDALL ;1C
50/50
2.746
274706KENDALL ;2C
50/50
2.746
274746AC1-111 G10
Adder
14.216
274744AC1-111 GEN8
Adder
14.216
970833AG2-524 GEN
Solar/Wind Harmer
21.915
970833AG2-524 GEN
Solar/Wind Harmer
10.193
972227AH1-698 GEN1
Adder
6.285
971675AH1-338 GEN
Solar/Wind Harmer
42.811
274675JOLIET 29;7U
Adder
72.865
274675JOLIET 29;7U
Adder
70.263
971177AH1-047 GEN
Solar/Wind Harmer
13.883
274731ELWOOD EC;2P
Adder
38.878
274733ELWOOD EC;3P
Adder
38.878
274735ELWOOD EC;4P
Adder
38.878
274728ELWOOD EC;5P
Adder
38.863
971411AH1-196 GEN
Solar/Wind Harmer
35.236
971171AH1-044 GEN
Solar/Wind Harmer
46.661
274687WILL CNTY;4U
Adder
65.158
274687WILL CNTY;4U
Adder
65.158
274823ROCKFORD ;21
Adder
44.942
960591AF2-350 GEN
Solar/Wind Harmer
23.02
276612AE2-035 GEN
Solar/Wind Harmer
5.816
971681AH1-341 GEN
Solar/Wind Harmer
33.665
274863CRW1-WTG
Solar/Wind Harmer
12.469
274864CRW2-WTG
Solar/Wind Harmer
12.469
276868AE1-113 GEN
Solar/Wind Harmer
22.431
276882AE2-255 GEN
Solar/Wind Harmer
7.478
274827FISK ;RP
Adder
17.137
961011AF2-392 GEN
Solar/Wind Harmer
23.805
972037AH1-567 GEN1
Adder
0.397
926823AC1-168 GEN
Solar/Wind Harmer
9.311
970169AG2-114 GEN
Solar/Wind Harmer
21.375
957751AF2-069 GEN
Solar/Wind Harmer
0.942
946321AF1-296 GEN
Solar/Wind Harmer
21.32
274848CAMPGROVE;RU
Solar/Wind Harmer
12.976
274814UNIV PK N;0U
Adder
9.899
274807UNIV PK N;3U
Adder
9.877
274805UNIV PK N;1U
Adder
9.834
274811UNIV PK N;7U
Adder
9.813
276655WTG1_EQ
Solar/Wind Harmer
16.537
276656WTG2_EQ
Solar/Wind Harmer
2.19
959341AF2-225 GEN
Solar/Wind Harmer
28.412
941731AE2-173 GEN
Solar/Wind Harmer
11.012
276785W4-005 GEN1
Solar/Wind Harmer
4.451
276174W4-005 GEN2
Solar/Wind Harmer
4.451
276849AB2-070 GEN2
Solar/Wind Harmer
3.298
276848AB2-070 GEN3
Solar/Wind Harmer
3.298
274773LINCOLN ;4U
50/50
20.173
274774LINCOLN ;5U
50/50
20.173
274710KENDALL ;4C
50/50
3.059
274705KENDALL ;1S
50/50
1.834
972207SS24-0001
Solar/Wind Harmer
67.591
274745AC1-111 GEN9
Adder
14.216
274871GR RIDGE ;2U
Solar/Wind Harmer
19.363
941551AE2-152 GEN
Solar/Wind Harmer
11.363
960751AF2-366 GEN
Solar/Wind Harmer
7.012
962781AG1-127 GEN
Solar/Wind Harmer
23.243
274872LEEDK;1U
Solar/Wind Harmer
19.986
274682WAUKEGAN ;7U
Adder
43.121
274828WAUKEGAN ;BP
Adder
26.446
274674JOLIET 9 ;6U
Adder
36.733
276861AD2-134 GEN
Solar/Wind Harmer
4.245
274676JOLIET 29;8U
Adder
72.857
274732ELWOOD EC;7P
Adder
38.863
957471AF2-041 GEN
Solar/Wind Harmer
69.992
959081AF2-199 GEN
Solar/Wind Harmer
23.331
971067AG2-660 GEN
Solar/Wind Harmer
5.426
939401AE1-172 GEN
Solar/Wind Harmer
32.483
274822ROCKFORD ;11
Adder
45.27
971997AH1-543 GEN
Solar/Wind Harmer
36.28
276776AD2-060 GEN
Solar/Wind Harmer
0.973
972235AH1-702 GEN1
Adder
5.789
970819AG2-516 GEN
Solar/Wind Harmer
27.357
971475AH1-234 GEN
Solar/Wind Harmer
50.778
276901AD2-066 C O1
Solar/Wind Harmer
7.878
274801UNIV PARK;4U
Adder
13.022
274857EASY ROAD;U1
Solar/Wind Harmer
10.665
274761LEE CO EC;2U
Adder
20.706
274766LEE CO EC;7U
Adder
20.462
276691AA1-018 GEN1
Solar/Wind Harmer
1.028
276158O29GEN2
Solar/Wind Harmer
10.723
276876AE1-163_GEN2
Solar/Wind Harmer
14.306
276164X3-005 C
Solar/Wind Harmer
1.479
970569AG2-363 GEN
Solar/Wind Harmer
62.951
274877BISHOP HL;1U
Solar/Wind Harmer
6.882
274812UNIV PK N;8U
Adder
9.813
274723RIVER EC ;12
Adder
34.022
276726Z2-087_GEN
Solar/Wind Harmer
14.981
939741AE1-205 GEN
Solar/Wind Harmer
37.882
274854TWINGROVE;U2
Solar/Wind Harmer
12.721
274751CRETE EC ;1U
Adder
8.31
274754CRETE EC ;4U
Adder
8.31
972175AH1-670 GEN
Solar/Wind Harmer
22.229
274880W4-005 GEN4
Solar/Wind Harmer
4.451
963831AG1-236 GEN
Solar/Wind Harmer
14.208
276615X2-022 GEN
Solar/Wind Harmer
2.739
274770LINCOLN ;1U
50/50
20.173
274771LINCOLN ;2U
50/50
20.173
274709KENDALL ;3S
50/50
2.042
274711KENDALL ;4S
50/50
2.042
274661LASCO STA;2U
50/50
18.804
972259AH1-714 GEN
50/50
52.779
274660LASCO STA;1U
50/50
19.043
971573AH1-285 GEN
Solar/Wind Harmer
22.127
274847GR RIDGE ;BU
Solar/Wind Harmer
12.737
274695ROCKY RD ;2P
Adder
27.369
274693ROCKY RD ;1P
Adder
27.1
274697ROCKY RD ;3P
Adder
7.435
274696ROCKY RD ;4P
Adder
28.011
962691AG1-118 GEN
Solar/Wind Harmer
73.702
970921AG2-575 GEN
Solar/Wind Harmer
24.44
970921AG2-575 GEN
Solar/Wind Harmer
5.684
274683WAUKEGAN ;8U
Adder
50.452
274683WAUKEGAN ;8U
Adder
42.529
274674JOLIET 9 ;6U
Adder
36.733
942991AE2-321 GEN
Solar/Wind Harmer
23.703
971333AH1-146 GEN
Solar/Wind Harmer
47.107
971335AH1-147 GEN
Solar/Wind Harmer
47.107
971341AH1-150 GEN
Solar/Wind Harmer
46.661
971343AH1-151 GEN
Solar/Wind Harmer
46.661
274888KELLY CRK;1U
Solar/Wind Harmer
13.591
274887GEN-1.85
Solar/Wind Harmer
12.27
276843GEN-1.7
Solar/Wind Harmer
1.32
958011AF2-095 GEN
Solar/Wind Harmer
33.148
274856ECOGROVE ;U1
Solar/Wind Harmer
7.664
276611AD2-172 GEN
Solar/Wind Harmer
5.816
938861AE1-114 GEN
Solar/Wind Harmer
18.38
274764LEE CO EC;5U
Adder
20.755
274765LEE CO EC;6U
Adder
20.755
274762LEE CO EC;3U
Adder
20.706
274763LEE CO EC;4U
Adder
20.511
276603SUBLETTE C
Solar/Wind Harmer
2.327
274879MINONK ;1U
Solar/Wind Harmer
14.955
958481AF2-142 GEN
Solar/Wind Harmer
33.128
274861TOP CROP ;1U
Solar/Wind Harmer
13.317
274862TOP CROP ;2U
Solar/Wind Harmer
11.12
972267AH1-718 GEN
Adder
9.073
958491AF2-143 GEN
Solar/Wind Harmer
32.633
274803UNIV PARK;6U
Adder
12.653
276741O09 GEN1
Solar/Wind Harmer
7.66
276708O09 GEN2
Solar/Wind Harmer
7.66
276872AE1-163_GEN1
Solar/Wind Harmer
14.306
274851PROVIDENC;RU
Solar/Wind Harmer
5.845
274849CRESCENT ;1U
Solar/Wind Harmer
3.795
276645AC1-214 GEN1
Solar/Wind Harmer
2.749
276646AC1-214 GEN2
Solar/Wind Harmer
2.749
276782AC1-033 GEN
Solar/Wind Harmer
8.132
274808UNIV PK N;4U
Adder
9.77
960611AF2-352 GEN
Solar/Wind Harmer
4.192
276763AC1-053 GEN1
Solar/Wind Harmer
5.712
276764AC1-053 GEN2
Solar/Wind Harmer
5.712
274772LINCOLN ;3U
50/50
20.173
274707KENDALL ;2S
50/50
1.834
970707AG2-453 GEN
Solar/Wind Harmer
79.14
943121AE2-341 GEN
Solar/Wind Harmer
39.228
943591AF1-030 GEN
Solar/Wind Harmer
26.152
276897AD1-100 C
Solar/Wind Harmer
72.706
939351AE1-166 GEN
Solar/Wind Harmer
14.856
274872LEEDK;1U
Solar/Wind Harmer
0.622
972228AH1-698 GEN2
Adder
8.923
274682WAUKEGAN ;7U
Adder
43.121
276799AD1-013 GEN
Solar/Wind Harmer
5.264
946671AF1-331 GEN
Solar/Wind Harmer
0.997
274855GSG-6 ;RU
Solar/Wind Harmer
8.778
274850MENDOTA H;RU
Solar/Wind Harmer
6.103
276602WESTBROOK C
Solar/Wind Harmer
5.052
276863AD2-134 GEN
Solar/Wind Harmer
4.245
274676JOLIET 29;8U
Adder
70.255
274729ELWOOD EC;1P
Adder
38.878
274730ELWOOD EC;6P
Adder
38.863
274734ELWOOD EC;8P
Adder
38.863
274736ELWOOD EC;9P
Adder
38.863
959091AF2-200 GEN
Solar/Wind Harmer
46.661
276893AG1-478 C
Solar/Wind Harmer
0.974
970941AG2-585 GEN
Solar/Wind Harmer
28.775
276772AC2-154 GEN
Solar/Wind Harmer
6.419
276806AD2-047 C O1
Solar/Wind Harmer
24.626
972236AH1-702 GEN2
Adder
5.034
274800UNIV PARK;3U
Adder
13.022
972038AH1-567 GEN2
Adder
0.815
274858EASY ROAD;U2
Solar/Wind Harmer
10.665
274760LEE CO EC;1U
Adder
20.706
274767LEE CO EC;8U
Adder
20.462
274826FISK ;BP
Adder
24.181
276694AA1-018 GEN2
Solar/Wind Harmer
13.937
276805AD2-038 GEN
Solar/Wind Harmer
11.16
274802UNIV PARK;5U
Adder
12.653
276157O29GEN1
Solar/Wind Harmer
8.157
276889AE2-281 GEN
Solar/Wind Harmer
4.087
970571AG2-364 GEN
Solar/Wind Harmer
41.967
274878BISHOP HL;2U
Solar/Wind Harmer
6.882
965931AG1-462 GEN
Solar/Wind Harmer
51.499
274724RIVER EC ;11
Adder
33.679
942111AE2-223 GEN
Solar/Wind Harmer
15.527
274853TWINGROVE;U1
Solar/Wind Harmer
12.993
965091AG1-374 GEN
Solar/Wind Harmer
54.08
959611AF2-252 GEN
Solar/Wind Harmer
4.192
972231SS25-0005
Solar/Wind Harmer
16.135
972181SS23-001
Solar/Wind Harmer
10.085
274752CRETE EC ;2U
Adder
8.31
274753CRETE EC ;3U
Adder
8.31
276686W4-005 GEN3
Solar/Wind Harmer
4.451
971993AH1-541 GEN
Solar/Wind Harmer
13.597
276668AB2-070 GEN1
Solar/Wind Harmer
3.298
276621W2-048 GEN
Solar/Wind Harmer
8.723
276838X2-022 GEN2
Solar/Wind Harmer
0.325
990512J1326
External Queue
11.370098114013672
990727J1377 G
External Queue
7.85197639465332
991092J1477
External Queue
6.023608684539795
990407J1304
External Queue
8.819581985473633
NYPJM->LTFIMP_NY
CLTF
2.188
WECLTFEXP_WEC->PJM
CLTF
8.641
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.929
CBM West 2LTFEXP_CBM-W2->PJM
CBM
65.661
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.158
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.464
CBM West 1LTFEXP_CBM-W1->PJM
CBM
147.622
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.136
MECLTFEXP_MEC->PJM
CLTF
27.127
SIGELTFEXP_SIGE->PJM
CLTF
0.04
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.009
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.826
LAGNLTFEXP_LAGN->PJM
CLTF
8.928
TVALTFEXP_TVA->PJM
CLTF
2.262

Details for WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line l/o AEP_P2-2_#286_05EUGENE 345_2_SRT-A


Base Case Flowgate

Area:AEP/CE
Facility Description:
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#286_05EUGENE 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:108.12 %
Rating:4460.0 MVA
Rating Type:B
MVA to Mitigate:4822.13
MW Contribution:27.57
Bus #Bus NameTypeMW Contribution
274772LINCOLN ;3U
50/50
20.274
274707KENDALL ;2S
50/50
1.839
970707AG2-453 GEN
Solar/Wind Harmer
79.501
943121AE2-341 GEN
Solar/Wind Harmer
39.431
943591AF1-030 GEN
Solar/Wind Harmer
26.287
276897AD1-100 C
Solar/Wind Harmer
73.15
939351AE1-166 GEN
Solar/Wind Harmer
14.946
274872LEEDK;1U
Solar/Wind Harmer
0.627
972228AH1-698 GEN2
Adder
8.938
274682WAUKEGAN ;7U
Adder
43.324
276799AD1-013 GEN
Solar/Wind Harmer
5.302
946671AF1-331 GEN
Solar/Wind Harmer
1.004
274855GSG-6 ;RU
Solar/Wind Harmer
8.842
274850MENDOTA H;RU
Solar/Wind Harmer
6.148
276602WESTBROOK C
Solar/Wind Harmer
5.09
276863AD2-134 GEN
Solar/Wind Harmer
4.276
274676JOLIET 29;8U
Adder
70.373
274729ELWOOD EC;1P
Adder
38.993
274730ELWOOD EC;6P
Adder
38.976
274734ELWOOD EC;8P
Adder
38.976
274736ELWOOD EC;9P
Adder
38.976
959091AF2-200 GEN
Solar/Wind Harmer
47.017
276893AG1-478 C
Solar/Wind Harmer
0.977
972236AH1-702 GEN2
Adder
5.073
276772AC2-154 GEN
Solar/Wind Harmer
6.43
276806AD2-047 C O1
Solar/Wind Harmer
24.666
970941AG2-585 GEN
Solar/Wind Harmer
28.822
274858EASY ROAD;U2
Solar/Wind Harmer
10.763
274760LEE CO EC;1U
Adder
20.895
274767LEE CO EC;8U
Adder
20.649
274800UNIV PARK;3U
Adder
13.03
972038AH1-567 GEN2
Adder
0.816
276694AA1-018 GEN2
Solar/Wind Harmer
14.003
274826FISK ;BP
Adder
24.166
276805AD2-038 GEN
Solar/Wind Harmer
11.239
276157O29GEN1
Solar/Wind Harmer
8.257
274802UNIV PARK;5U
Adder
12.61
276889AE2-281 GEN
Solar/Wind Harmer
4.13
970571AG2-364 GEN
Solar/Wind Harmer
42.499
274878BISHOP HL;2U
Solar/Wind Harmer
7.008
965931AG1-462 GEN
Solar/Wind Harmer
52.169
942111AE2-223 GEN
Solar/Wind Harmer
16.216
274724RIVER EC ;11
Adder
33.588
274853TWINGROVE;U1
Solar/Wind Harmer
13.613
965091AG1-374 GEN
Solar/Wind Harmer
56.662
959611AF2-252 GEN
Solar/Wind Harmer
4.392
972231SS25-0005
Solar/Wind Harmer
15.653
972181SS23-001
Solar/Wind Harmer
9.783
274752CRETE EC ;2U
Adder
8.062
274753CRETE EC ;3U
Adder
8.062
276686W4-005 GEN3
Solar/Wind Harmer
4.789
971993AH1-541 GEN
Solar/Wind Harmer
14.63
276668AB2-070 GEN1
Solar/Wind Harmer
3.551
276621W2-048 GEN
Solar/Wind Harmer
9.391
276838X2-022 GEN2
Solar/Wind Harmer
0.35
274775LINCOLN ;6U
50/50
20.274
274776LINCOLN ;7U
50/50
20.274
274777LINCOLN ;8U
50/50
20.274
274708KENDALL ;3C
50/50
3.095
274704KENDALL ;1C
50/50
2.755
274706KENDALL ;2C
50/50
2.755
274746AC1-111 G10
Adder
14.288
274744AC1-111 GEN8
Adder
14.288
970833AG2-524 GEN
Solar/Wind Harmer
22.034
970833AG2-524 GEN
Solar/Wind Harmer
10.248
972227AH1-698 GEN1
Adder
6.296
971675AH1-338 GEN
Solar/Wind Harmer
43.125
971177AH1-047 GEN
Solar/Wind Harmer
13.972
274675JOLIET 29;7U
Adder
72.988
274675JOLIET 29;7U
Adder
70.381
274731ELWOOD EC;2P
Adder
38.993
274733ELWOOD EC;3P
Adder
38.993
274735ELWOOD EC;4P
Adder
38.993
274728ELWOOD EC;5P
Adder
38.976
971411AH1-196 GEN
Solar/Wind Harmer
35.471
971171AH1-044 GEN
Solar/Wind Harmer
47.017
274687WILL CNTY;4U
Adder
65.236
274687WILL CNTY;4U
Adder
65.236
274823ROCKFORD ;21
Adder
45.277
960591AF2-350 GEN
Solar/Wind Harmer
23.057
276612AE2-035 GEN
Solar/Wind Harmer
5.863
274863CRW1-WTG
Solar/Wind Harmer
12.748
274864CRW2-WTG
Solar/Wind Harmer
12.748
971681AH1-341 GEN
Solar/Wind Harmer
33.97
276868AE1-113 GEN
Solar/Wind Harmer
22.622
276882AE2-255 GEN
Solar/Wind Harmer
7.541
961011AF2-392 GEN
Solar/Wind Harmer
24.049
274827FISK ;RP
Adder
17.127
926823AC1-168 GEN
Solar/Wind Harmer
9.458
970169AG2-114 GEN
Solar/Wind Harmer
21.957
972037AH1-567 GEN1
Adder
0.396
957751AF2-069 GEN
Solar/Wind Harmer
0.96
946321AF1-296 GEN
Solar/Wind Harmer
21.59
274848CAMPGROVE;RU
Solar/Wind Harmer
13.236
276655WTG1_EQ
Solar/Wind Harmer
17.271
276656WTG2_EQ
Solar/Wind Harmer
2.287
959341AF2-225 GEN
Solar/Wind Harmer
29.672
941731AE2-173 GEN
Solar/Wind Harmer
11.501
274814UNIV PK N;0U
Adder
9.754
274807UNIV PK N;3U
Adder
9.733
274805UNIV PK N;1U
Adder
9.691
274811UNIV PK N;7U
Adder
9.67
276785W4-005 GEN1
Solar/Wind Harmer
4.789
276174W4-005 GEN2
Solar/Wind Harmer
4.789
276849AB2-070 GEN2
Solar/Wind Harmer
3.551
276848AB2-070 GEN3
Solar/Wind Harmer
3.551
274773LINCOLN ;4U
50/50
20.274
274774LINCOLN ;5U
50/50
20.274
274710KENDALL ;4C
50/50
3.072
274705KENDALL ;1S
50/50
1.839
972207SS24-0001
Solar/Wind Harmer
67.931
274745AC1-111 GEN9
Adder
14.288
274871GR RIDGE ;2U
Solar/Wind Harmer
19.469
941551AE2-152 GEN
Solar/Wind Harmer
11.432
960751AF2-366 GEN
Solar/Wind Harmer
7.057
962781AG1-127 GEN
Solar/Wind Harmer
23.391
274872LEEDK;1U
Solar/Wind Harmer
20.118
274682WAUKEGAN ;7U
Adder
43.324
274828WAUKEGAN ;BP
Adder
26.573
276861AD2-134 GEN
Solar/Wind Harmer
4.276
274674JOLIET 9 ;6U
Adder
36.856
274676JOLIET 29;8U
Adder
72.979
939401AE1-172 GEN
Solar/Wind Harmer
33.053
274732ELWOOD EC;7P
Adder
38.976
957471AF2-041 GEN
Solar/Wind Harmer
70.526
959081AF2-199 GEN
Solar/Wind Harmer
23.509
971067AG2-660 GEN
Solar/Wind Harmer
5.467
971997AH1-543 GEN
Solar/Wind Harmer
36.681
274822ROCKFORD ;11
Adder
45.607
972235AH1-702 GEN1
Adder
5.834
276776AD2-060 GEN
Solar/Wind Harmer
0.975
970819AG2-516 GEN
Solar/Wind Harmer
27.572
971475AH1-234 GEN
Solar/Wind Harmer
51.175
276901AD2-066 C O1
Solar/Wind Harmer
7.96
274857EASY ROAD;U1
Solar/Wind Harmer
10.763
274761LEE CO EC;2U
Adder
20.895
274766LEE CO EC;7U
Adder
20.649
274801UNIV PARK;4U
Adder
13.03
276691AA1-018 GEN1
Solar/Wind Harmer
1.033
276158O29GEN2
Solar/Wind Harmer
10.855
276876AE1-163_GEN2
Solar/Wind Harmer
14.453
970569AG2-363 GEN
Solar/Wind Harmer
63.748
276164X3-005 C
Solar/Wind Harmer
1.478
274877BISHOP HL;1U
Solar/Wind Harmer
7.008
276726Z2-087_GEN
Solar/Wind Harmer
15.646
939741AE1-205 GEN
Solar/Wind Harmer
39.563
274812UNIV PK N;8U
Adder
9.67
274723RIVER EC ;12
Adder
33.905
274854TWINGROVE;U2
Solar/Wind Harmer
13.328
972175AH1-670 GEN
Solar/Wind Harmer
23.591
274751CRETE EC ;1U
Adder
8.062
274754CRETE EC ;4U
Adder
8.062
274880W4-005 GEN4
Solar/Wind Harmer
4.789
963831AG1-236 GEN
Solar/Wind Harmer
15.298
276615X2-022 GEN
Solar/Wind Harmer
2.948
274770LINCOLN ;1U
50/50
20.274
274771LINCOLN ;2U
50/50
20.274
274709KENDALL ;3S
50/50
2.051
274711KENDALL ;4S
50/50
2.051
274661LASCO STA;2U
50/50
18.869
972259AH1-714 GEN
50/50
52.964
274660LASCO STA;1U
50/50
19.11
971573AH1-285 GEN
Solar/Wind Harmer
22.248
274847GR RIDGE ;BU
Solar/Wind Harmer
12.807
962691AG1-118 GEN
Solar/Wind Harmer
74.159
274695ROCKY RD ;2P
Adder
27.515
274693ROCKY RD ;1P
Adder
27.244
274697ROCKY RD ;3P
Adder
7.474
274696ROCKY RD ;4P
Adder
28.16
970921AG2-575 GEN
Solar/Wind Harmer
24.596
970921AG2-575 GEN
Solar/Wind Harmer
5.72
274683WAUKEGAN ;8U
Adder
50.694
274683WAUKEGAN ;8U
Adder
42.733
274674JOLIET 9 ;6U
Adder
36.856
942991AE2-321 GEN
Solar/Wind Harmer
23.854
971333AH1-146 GEN
Solar/Wind Harmer
47.432
971335AH1-147 GEN
Solar/Wind Harmer
47.432
971341AH1-150 GEN
Solar/Wind Harmer
47.017
971343AH1-151 GEN
Solar/Wind Harmer
47.017
958011AF2-095 GEN
Solar/Wind Harmer
33.203
274888KELLY CRK;1U
Solar/Wind Harmer
13.613
274887GEN-1.85
Solar/Wind Harmer
12.29
276843GEN-1.7
Solar/Wind Harmer
1.322
274856ECOGROVE ;U1
Solar/Wind Harmer
7.727
276611AD2-172 GEN
Solar/Wind Harmer
5.863
938861AE1-114 GEN
Solar/Wind Harmer
18.545
274764LEE CO EC;5U
Adder
20.944
274765LEE CO EC;6U
Adder
20.944
274762LEE CO EC;3U
Adder
20.895
274763LEE CO EC;4U
Adder
20.698
276603SUBLETTE C
Solar/Wind Harmer
2.349
274879MINONK ;1U
Solar/Wind Harmer
15.083
958481AF2-142 GEN
Solar/Wind Harmer
33.285
274861TOP CROP ;1U
Solar/Wind Harmer
13.377
274862TOP CROP ;2U
Solar/Wind Harmer
11.171
972267AH1-718 GEN
Adder
9.165
958491AF2-143 GEN
Solar/Wind Harmer
32.862
276741O09 GEN1
Solar/Wind Harmer
7.754
276708O09 GEN2
Solar/Wind Harmer
7.754
274803UNIV PARK;6U
Adder
12.61
276872AE1-163_GEN1
Solar/Wind Harmer
14.453
274851PROVIDENC;RU
Solar/Wind Harmer
5.955
274849CRESCENT ;1U
Solar/Wind Harmer
3.866
276645AC1-214 GEN1
Solar/Wind Harmer
2.801
276646AC1-214 GEN2
Solar/Wind Harmer
2.801
276782AC1-033 GEN
Solar/Wind Harmer
8.281
274808UNIV PK N;4U
Adder
9.627
960611AF2-352 GEN
Solar/Wind Harmer
4.392
276763AC1-053 GEN1
Solar/Wind Harmer
6.15
276764AC1-053 GEN2
Solar/Wind Harmer
6.15
957381AF2-032 GEN
Solar/Wind Harmer
0.572
990512J1326
External Queue
11.444344520568848
990727J1377 G
External Queue
7.3309478759765625
991092J1477
External Queue
6.13206148147583
990407J1304
External Queue
8.867903709411621
NYPJM->LTFIMP_NY
CLTF
2.17
WECLTFEXP_WEC->PJM
CLTF
8.7
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.899
CBM West 2LTFEXP_CBM-W2->PJM
CBM
67.461
AG2-052LTFEXP_AG2-052->PJM
LTF
0.105
AH1-155LTFEXP_AH1-155->PJM
LTF
0.157
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.445
CBM West 1LTFEXP_CBM-W1->PJM
CBM
149.111
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.385
MECLTFEXP_MEC->PJM
CLTF
27.615
SIGELTFEXP_SIGE->PJM
CLTF
0.031
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
1.094
BlueGrassPJM->LTFIMP_BlueG
CLTF
3.094
LAGNLTFEXP_LAGN->PJM
CLTF
9.262
TVALTFEXP_TVA->PJM
CLTF
2.37

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.6 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1712.79
MW Contribution:9.22
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
10.144
274774LINCOLN ;5U
50/50
10.144
274655BRAIDWOOD;2U
50/50
6.709
972207SS24-0001
Solar/Wind Harmer
33.99
941551AE2-152 GEN
Solar/Wind Harmer
4.841
939401AE1-172 GEN
Solar/Wind Harmer
13.646
276776AD2-060 GEN
Solar/Wind Harmer
0.386
274871GR RIDGE ;2U
Solar/Wind Harmer
6.71
276164X3-005 C
Solar/Wind Harmer
0.608
274801UNIV PARK;4U
Adder
5.005
274676JOLIET 29;8U
Adder
26.335
274732ELWOOD EC;7P
Adder
14.096
274674JOLIET 9 ;6U
Adder
13.126
274745AC1-111 GEN9
Adder
4.669
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.735
274828WAUKEGAN ;BP
Adder
9.036
960751AF2-366 GEN
Solar/Wind Harmer
2.307
962781AG1-127 GEN
Solar/Wind Harmer
7.648
276901AD2-066 C O1
Solar/Wind Harmer
2.814
274872LEEDK;1U
Solar/Wind Harmer
6.578
971997AH1-543 GEN
Solar/Wind Harmer
12.448
276861AD2-134 GEN
Solar/Wind Harmer
1.406
957471AF2-041 GEN
Solar/Wind Harmer
23.37
959081AF2-199 GEN
Solar/Wind Harmer
7.79
971067AG2-660 GEN
Solar/Wind Harmer
1.812
276876AE1-163_GEN2
Solar/Wind Harmer
5.225
274723RIVER EC ;12
Adder
13.916
274822ROCKFORD ;11
Adder
15.226
972235AH1-702 GEN1
Adder
1.947
970819AG2-516 GEN
Solar/Wind Harmer
9.216
971475AH1-234 GEN
Solar/Wind Harmer
17.128
970569AG2-363 GEN
Solar/Wind Harmer
22.74
274857EASY ROAD;U1
Solar/Wind Harmer
3.599
274761LEE CO EC;2U
Adder
6.986
274766LEE CO EC;7U
Adder
6.904
274812UNIV PK N;8U
Adder
3.746
276726Z2-087_GEN
Solar/Wind Harmer
5.812
939741AE1-205 GEN
Solar/Wind Harmer
14.698
276158O29GEN2
Solar/Wind Harmer
3.662
274877BISHOP HL;1U
Solar/Wind Harmer
2.415
274854TWINGROVE;U2
Solar/Wind Harmer
4.925
274751CRETE EC ;1U
Adder
3.161
274754CRETE EC ;4U
Adder
3.161
972175AH1-670 GEN
Solar/Wind Harmer
8.543
274880W4-005 GEN4
Solar/Wind Harmer
1.697
963831AG1-236 GEN
Solar/Wind Harmer
5.391
276615X2-022 GEN
Solar/Wind Harmer
1.035
965911AG1-460 GEN
Solar/Wind Harmer
0.25
274772LINCOLN ;3U
50/50
10.144
274654BRAIDWOOD;1U
50/50
7.139
972228AH1-698 GEN2
50/50
3.673
276897AD1-100 C
Solar/Wind Harmer
30.978
939351AE1-166 GEN
Solar/Wind Harmer
6.33
276772AC2-154 GEN
Solar/Wind Harmer
2.544
276806AD2-047 C O1
Solar/Wind Harmer
9.759
970941AG2-585 GEN
Solar/Wind Harmer
11.403
970707AG2-453 GEN
Solar/Wind Harmer
24.504
276893AG1-478 C
Solar/Wind Harmer
0.363
274826FISK ;BP
Adder
9.4
274800UNIV PARK;3U
Adder
5.005
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.395
274729ELWOOD EC;1P
Adder
14.096
274730ELWOOD EC;6P
Adder
14.096
274734ELWOOD EC;8P
Adder
14.096
274736ELWOOD EC;9P
Adder
14.096
943121AE2-341 GEN
Solar/Wind Harmer
12.521
943591AF1-030 GEN
Solar/Wind Harmer
8.348
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
274682WAUKEGAN ;7U
Adder
14.735
276805AD2-038 GEN
Solar/Wind Harmer
4.139
274872LEEDK;1U
Solar/Wind Harmer
0.205
276799AD1-013 GEN
Solar/Wind Harmer
1.742
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
276863AD2-134 GEN
Solar/Wind Harmer
1.406
274724RIVER EC ;11
Adder
13.808
959091AF2-200 GEN
Solar/Wind Harmer
15.58
276889AE2-281 GEN
Solar/Wind Harmer
1.493
972236AH1-702 GEN2
Adder
1.693
970571AG2-364 GEN
Solar/Wind Harmer
15.16
274858EASY ROAD;U2
Solar/Wind Harmer
3.599
274760LEE CO EC;1U
Adder
6.986
274767LEE CO EC;8U
Adder
6.904
942111AE2-223 GEN
Solar/Wind Harmer
6.024
274775LINCOLN ;6U
50/50
10.144
274776LINCOLN ;7U
50/50
10.144
274777LINCOLN ;8U
50/50
10.144
972227AH1-698 GEN1
50/50
2.589
274687WILL CNTY;4U
50/50
25.533
274687WILL CNTY;4U
50/50
25.533
274863CRW1-WTG
Solar/Wind Harmer
5.114
274864CRW2-WTG
Solar/Wind Harmer
5.114
960591AF2-350 GEN
Solar/Wind Harmer
9.123
970833AG2-524 GEN
Solar/Wind Harmer
7.585
970833AG2-524 GEN
Solar/Wind Harmer
3.528
274827FISK ;RP
Adder
6.662
274675JOLIET 29;7U
Adder
26.336
274675JOLIET 29;7U
Adder
25.395
274731ELWOOD EC;2P
Adder
14.096
274733ELWOOD EC;3P
Adder
14.096
274735ELWOOD EC;4P
Adder
14.096
274728ELWOOD EC;5P
Adder
14.096
274746AC1-111 G10
Adder
4.669
274744AC1-111 GEN8
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.092
276868AE1-113 GEN
Solar/Wind Harmer
8.054
276882AE2-255 GEN
Solar/Wind Harmer
2.685
971177AH1-047 GEN
Solar/Wind Harmer
4.661
971411AH1-196 GEN
Solar/Wind Harmer
11.848
971675AH1-338 GEN
Solar/Wind Harmer
14.175
971171AH1-044 GEN
Solar/Wind Harmer
15.58
274823ROCKFORD ;21
Adder
15.116
276612AE2-035 GEN
Solar/Wind Harmer
1.959
926823AC1-168 GEN
Solar/Wind Harmer
3.278
971681AH1-341 GEN
Solar/Wind Harmer
11.345
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274805UNIV PK N;1U
Adder
3.754
274811UNIV PK N;7U
Adder
3.746
961011AF2-392 GEN
Solar/Wind Harmer
8.052
276655WTG1_EQ
Solar/Wind Harmer
6.416
276656WTG2_EQ
Solar/Wind Harmer
0.85
959341AF2-225 GEN
Solar/Wind Harmer
11.023
941731AE2-173 GEN
Solar/Wind Harmer
4.273
957751AF2-069 GEN
Solar/Wind Harmer
0.332
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
946321AF1-296 GEN
Solar/Wind Harmer
7.279
276785W4-005 GEN1
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276849AB2-070 GEN2
Solar/Wind Harmer
1.253
276848AB2-070 GEN3
Solar/Wind Harmer
1.253
274770LINCOLN ;1U
50/50
10.144
274771LINCOLN ;2U
50/50
10.144
274660LASCO STA;1U
50/50
6.585
274661LASCO STA;2U
50/50
6.502
972259AH1-714 GEN
50/50
18.251
274888KELLY CRK;1U
Solar/Wind Harmer
5.386
274887GEN-1.85
Solar/Wind Harmer
4.863
276843GEN-1.7
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
13.137
274847GR RIDGE ;BU
Solar/Wind Harmer
4.414
274674JOLIET 9 ;6U
Adder
13.126
274803UNIV PARK;6U
Adder
4.863
958481AF2-142 GEN
Solar/Wind Harmer
12.415
971573AH1-285 GEN
Solar/Wind Harmer
7.114
274861TOP CROP ;1U
Solar/Wind Harmer
5.002
274862TOP CROP ;2U
Solar/Wind Harmer
4.177
274695ROCKY RD ;2P
Adder
9.128
274693ROCKY RD ;1P
Adder
9.038
274697ROCKY RD ;3P
Adder
2.48
274696ROCKY RD ;4P
Adder
9.343
274683WAUKEGAN ;8U
Adder
17.239
274683WAUKEGAN ;8U
Adder
14.531
962691AG1-118 GEN
Solar/Wind Harmer
24.231
958491AF2-143 GEN
Solar/Wind Harmer
12.102
970921AG2-575 GEN
Solar/Wind Harmer
8.042
970921AG2-575 GEN
Solar/Wind Harmer
1.87
942991AE2-321 GEN
Solar/Wind Harmer
7.961
274879MINONK ;1U
Solar/Wind Harmer
5.37
971333AH1-146 GEN
Solar/Wind Harmer
15.765
971335AH1-147 GEN
Solar/Wind Harmer
15.765
971341AH1-150 GEN
Solar/Wind Harmer
15.58
971343AH1-151 GEN
Solar/Wind Harmer
15.58
276872AE1-163_GEN1
Solar/Wind Harmer
5.225
274856ECOGROVE ;U1
Solar/Wind Harmer
2.582
276611AD2-172 GEN
Solar/Wind Harmer
1.959
938861AE1-114 GEN
Solar/Wind Harmer
6.198
274764LEE CO EC;5U
Adder
7.003
274765LEE CO EC;6U
Adder
7.003
274762LEE CO EC;3U
Adder
6.986
274763LEE CO EC;4U
Adder
6.92
276603SUBLETTE C
Solar/Wind Harmer
0.785
274808UNIV PK N;4U
Adder
3.73
972267AH1-718 GEN
Adder
3.068
276741O09 GEN1
Solar/Wind Harmer
2.616
276708O09 GEN2
Solar/Wind Harmer
2.616
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
276782AC1-033 GEN
Solar/Wind Harmer
2.854
960611AF2-352 GEN
Solar/Wind Harmer
1.623
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
957381AF2-032 GEN
Solar/Wind Harmer
0.199
276157O29GEN1
Solar/Wind Harmer
2.785
274878BISHOP HL;2U
Solar/Wind Harmer
2.415
274853TWINGROVE;U1
Solar/Wind Harmer
5.03
965091AG1-374 GEN
Solar/Wind Harmer
20.937
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.6
972231SS25-0005
Solar/Wind Harmer
6.138
972181SS23-001
Solar/Wind Harmer
3.836
274752CRETE EC ;2U
Adder
3.161
274753CRETE EC ;3U
Adder
3.161
276686W4-005 GEN3
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.184
276668AB2-070 GEN1
Solar/Wind Harmer
1.253
276621W2-048 GEN
Solar/Wind Harmer
3.298
276838X2-022 GEN2
Solar/Wind Harmer
0.123
942481AE2-261 GEN
Solar/Wind Harmer
5.353
990512J1326
External Queue
3.7948038578033447
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
9.38
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.959
LAGNLTFEXP_LAGN->PJM
CLTF
3.176
TVALTFEXP_TVA->PJM
CLTF
0.822

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT2-3___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.23 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1692.67
MW Contribution:9.22
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
10.144
274774LINCOLN ;5U
50/50
10.144
274655BRAIDWOOD;2U
50/50
6.709
972207SS24-0001
Solar/Wind Harmer
33.99
274775LINCOLN ;6U
50/50
10.144
274776LINCOLN ;7U
50/50
10.144
274777LINCOLN ;8U
50/50
10.144
972227AH1-698 GEN1
50/50
2.589
274687WILL CNTY;4U
50/50
25.533
274687WILL CNTY;4U
50/50
25.533
274863CRW1-WTG
Solar/Wind Harmer
5.114
274864CRW2-WTG
Solar/Wind Harmer
5.114
960591AF2-350 GEN
Solar/Wind Harmer
9.123
970833AG2-524 GEN
Solar/Wind Harmer
7.585
970833AG2-524 GEN
Solar/Wind Harmer
3.528
274827FISK ;RP
Adder
6.662
274675JOLIET 29;7U
Adder
26.336
274675JOLIET 29;7U
Adder
25.395
274731ELWOOD EC;2P
Adder
14.096
274733ELWOOD EC;3P
Adder
14.096
274735ELWOOD EC;4P
Adder
14.096
274728ELWOOD EC;5P
Adder
14.096
274746AC1-111 G10
Adder
4.669
274744AC1-111 GEN8
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.092
276868AE1-113 GEN
Solar/Wind Harmer
8.054
276882AE2-255 GEN
Solar/Wind Harmer
2.685
971177AH1-047 GEN
Solar/Wind Harmer
4.661
971411AH1-196 GEN
Solar/Wind Harmer
11.848
971675AH1-338 GEN
Solar/Wind Harmer
14.175
274770LINCOLN ;1U
50/50
10.144
274771LINCOLN ;2U
50/50
10.144
274660LASCO STA;1U
50/50
6.585
274661LASCO STA;2U
50/50
6.502
972259AH1-714 GEN
50/50
18.251
274888KELLY CRK;1U
Solar/Wind Harmer
5.386
274887GEN-1.85
Solar/Wind Harmer
4.863
276843GEN-1.7
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
13.137
274847GR RIDGE ;BU
Solar/Wind Harmer
4.414
274674JOLIET 9 ;6U
Adder
13.126
274803UNIV PARK;6U
Adder
4.863
958481AF2-142 GEN
Solar/Wind Harmer
12.415
971573AH1-285 GEN
Solar/Wind Harmer
7.114
274861TOP CROP ;1U
Solar/Wind Harmer
5.002
274862TOP CROP ;2U
Solar/Wind Harmer
4.177
274695ROCKY RD ;2P
Adder
9.128
274693ROCKY RD ;1P
Adder
9.038
274697ROCKY RD ;3P
Adder
2.48
274696ROCKY RD ;4P
Adder
9.343
274683WAUKEGAN ;8U
Adder
17.239
274683WAUKEGAN ;8U
Adder
14.531
962691AG1-118 GEN
Solar/Wind Harmer
24.231
958491AF2-143 GEN
Solar/Wind Harmer
12.102
970921AG2-575 GEN
Solar/Wind Harmer
8.042
970921AG2-575 GEN
Solar/Wind Harmer
1.87
942991AE2-321 GEN
Solar/Wind Harmer
7.961
274879MINONK ;1U
Solar/Wind Harmer
5.37
971333AH1-146 GEN
Solar/Wind Harmer
15.765
971335AH1-147 GEN
Solar/Wind Harmer
15.765
971341AH1-150 GEN
Solar/Wind Harmer
15.58
971343AH1-151 GEN
Solar/Wind Harmer
15.58
276872AE1-163_GEN1
Solar/Wind Harmer
5.225
274856ECOGROVE ;U1
Solar/Wind Harmer
2.582
276611AD2-172 GEN
Solar/Wind Harmer
1.959
938861AE1-114 GEN
Solar/Wind Harmer
6.198
274764LEE CO EC;5U
Adder
7.003
274765LEE CO EC;6U
Adder
7.003
274762LEE CO EC;3U
Adder
6.986
274763LEE CO EC;4U
Adder
6.92
276603SUBLETTE C
Solar/Wind Harmer
0.785
274808UNIV PK N;4U
Adder
3.73
972267AH1-718 GEN
Adder
3.068
276741O09 GEN1
Solar/Wind Harmer
2.616
276708O09 GEN2
Solar/Wind Harmer
2.616
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
276782AC1-033 GEN
Solar/Wind Harmer
2.854
960611AF2-352 GEN
Solar/Wind Harmer
1.623
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
957381AF2-032 GEN
Solar/Wind Harmer
0.199
941551AE2-152 GEN
Solar/Wind Harmer
4.841
939401AE1-172 GEN
Solar/Wind Harmer
13.646
276776AD2-060 GEN
Solar/Wind Harmer
0.386
274871GR RIDGE ;2U
Solar/Wind Harmer
6.71
276164X3-005 C
Solar/Wind Harmer
0.608
274801UNIV PARK;4U
Adder
5.005
274676JOLIET 29;8U
Adder
26.335
274732ELWOOD EC;7P
Adder
14.096
274674JOLIET 9 ;6U
Adder
13.126
274745AC1-111 GEN9
Adder
4.669
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.735
274828WAUKEGAN ;BP
Adder
9.036
960751AF2-366 GEN
Solar/Wind Harmer
2.307
962781AG1-127 GEN
Solar/Wind Harmer
7.648
276901AD2-066 C O1
Solar/Wind Harmer
2.814
274872LEEDK;1U
Solar/Wind Harmer
6.578
971997AH1-543 GEN
Solar/Wind Harmer
12.448
276861AD2-134 GEN
Solar/Wind Harmer
1.406
957471AF2-041 GEN
Solar/Wind Harmer
23.37
959081AF2-199 GEN
Solar/Wind Harmer
7.79
971067AG2-660 GEN
Solar/Wind Harmer
1.812
276876AE1-163_GEN2
Solar/Wind Harmer
5.225
274723RIVER EC ;12
Adder
13.916
274822ROCKFORD ;11
Adder
15.226
972235AH1-702 GEN1
Adder
1.947
970819AG2-516 GEN
Solar/Wind Harmer
9.216
971475AH1-234 GEN
Solar/Wind Harmer
17.128
970569AG2-363 GEN
Solar/Wind Harmer
22.74
274857EASY ROAD;U1
Solar/Wind Harmer
3.599
274761LEE CO EC;2U
Adder
6.986
274766LEE CO EC;7U
Adder
6.904
274812UNIV PK N;8U
Adder
3.746
276726Z2-087_GEN
Solar/Wind Harmer
5.812
939741AE1-205 GEN
Solar/Wind Harmer
14.698
276158O29GEN2
Solar/Wind Harmer
3.662
274877BISHOP HL;1U
Solar/Wind Harmer
2.415
274854TWINGROVE;U2
Solar/Wind Harmer
4.925
274751CRETE EC ;1U
Adder
3.161
274754CRETE EC ;4U
Adder
3.161
972175AH1-670 GEN
Solar/Wind Harmer
8.543
274880W4-005 GEN4
Solar/Wind Harmer
1.697
963831AG1-236 GEN
Solar/Wind Harmer
5.391
276615X2-022 GEN
Solar/Wind Harmer
1.035
965911AG1-460 GEN
Solar/Wind Harmer
0.25
971171AH1-044 GEN
Solar/Wind Harmer
15.58
274823ROCKFORD ;21
Adder
15.116
276612AE2-035 GEN
Solar/Wind Harmer
1.959
926823AC1-168 GEN
Solar/Wind Harmer
3.278
971681AH1-341 GEN
Solar/Wind Harmer
11.345
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274805UNIV PK N;1U
Adder
3.754
274811UNIV PK N;7U
Adder
3.746
961011AF2-392 GEN
Solar/Wind Harmer
8.052
276655WTG1_EQ
Solar/Wind Harmer
6.416
276656WTG2_EQ
Solar/Wind Harmer
0.85
959341AF2-225 GEN
Solar/Wind Harmer
11.023
941731AE2-173 GEN
Solar/Wind Harmer
4.273
957751AF2-069 GEN
Solar/Wind Harmer
0.332
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
946321AF1-296 GEN
Solar/Wind Harmer
7.279
276785W4-005 GEN1
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276849AB2-070 GEN2
Solar/Wind Harmer
1.253
276848AB2-070 GEN3
Solar/Wind Harmer
1.253
274772LINCOLN ;3U
50/50
10.144
274654BRAIDWOOD;1U
50/50
7.139
972228AH1-698 GEN2
50/50
3.673
276897AD1-100 C
Solar/Wind Harmer
30.978
939351AE1-166 GEN
Solar/Wind Harmer
6.33
276772AC2-154 GEN
Solar/Wind Harmer
2.544
276806AD2-047 C O1
Solar/Wind Harmer
9.759
970941AG2-585 GEN
Solar/Wind Harmer
11.403
970707AG2-453 GEN
Solar/Wind Harmer
24.504
276893AG1-478 C
Solar/Wind Harmer
0.363
274826FISK ;BP
Adder
9.4
274800UNIV PARK;3U
Adder
5.005
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.395
274729ELWOOD EC;1P
Adder
14.096
274730ELWOOD EC;6P
Adder
14.096
274734ELWOOD EC;8P
Adder
14.096
274736ELWOOD EC;9P
Adder
14.096
943121AE2-341 GEN
Solar/Wind Harmer
12.521
943591AF1-030 GEN
Solar/Wind Harmer
8.348
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
274682WAUKEGAN ;7U
Adder
14.735
276805AD2-038 GEN
Solar/Wind Harmer
4.139
274872LEEDK;1U
Solar/Wind Harmer
0.205
276799AD1-013 GEN
Solar/Wind Harmer
1.742
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
276863AD2-134 GEN
Solar/Wind Harmer
1.406
274724RIVER EC ;11
Adder
13.808
959091AF2-200 GEN
Solar/Wind Harmer
15.58
276889AE2-281 GEN
Solar/Wind Harmer
1.493
972236AH1-702 GEN2
Adder
1.693
970571AG2-364 GEN
Solar/Wind Harmer
15.16
274858EASY ROAD;U2
Solar/Wind Harmer
3.599
274760LEE CO EC;1U
Adder
6.986
274767LEE CO EC;8U
Adder
6.904
942111AE2-223 GEN
Solar/Wind Harmer
6.024
276157O29GEN1
Solar/Wind Harmer
2.785
274878BISHOP HL;2U
Solar/Wind Harmer
2.415
274853TWINGROVE;U1
Solar/Wind Harmer
5.03
965091AG1-374 GEN
Solar/Wind Harmer
20.937
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.6
972231SS25-0005
Solar/Wind Harmer
6.138
972181SS23-001
Solar/Wind Harmer
3.836
274752CRETE EC ;2U
Adder
3.161
274753CRETE EC ;3U
Adder
3.161
276686W4-005 GEN3
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.184
276668AB2-070 GEN1
Solar/Wind Harmer
1.253
276621W2-048 GEN
Solar/Wind Harmer
3.298
276838X2-022 GEN2
Solar/Wind Harmer
0.123
942481AE2-261 GEN
Solar/Wind Harmer
5.353
990512J1326
External Queue
3.7948038578033447
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.949
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
9.38
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.959
LAGNLTFEXP_LAGN->PJM
CLTF
3.176
TVALTFEXP_TVA->PJM
CLTF
0.822

Details for WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ;3M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.22 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1692.63
MW Contribution:9.22
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.144
274771LINCOLN ;2U
50/50
10.144
274660LASCO STA;1U
50/50
6.585
274661LASCO STA;2U
50/50
6.502
972259AH1-714 GEN
50/50
18.251
274888KELLY CRK;1U
Solar/Wind Harmer
5.386
274887GEN-1.85
Solar/Wind Harmer
4.863
276843GEN-1.7
Solar/Wind Harmer
0.523
958011AF2-095 GEN
Solar/Wind Harmer
13.137
274772LINCOLN ;3U
50/50
10.144
274654BRAIDWOOD;1U
50/50
7.139
972228AH1-698 GEN2
50/50
3.673
276897AD1-100 C
Solar/Wind Harmer
30.978
939351AE1-166 GEN
Solar/Wind Harmer
6.33
276772AC2-154 GEN
Solar/Wind Harmer
2.544
276806AD2-047 C O1
Solar/Wind Harmer
9.759
970941AG2-585 GEN
Solar/Wind Harmer
11.403
970707AG2-453 GEN
Solar/Wind Harmer
24.504
276893AG1-478 C
Solar/Wind Harmer
0.363
274826FISK ;BP
Adder
9.4
274800UNIV PARK;3U
Adder
5.005
972038AH1-567 GEN2
Adder
0.313
274676JOLIET 29;8U
Adder
25.395
274729ELWOOD EC;1P
Adder
14.096
274730ELWOOD EC;6P
Adder
14.096
274734ELWOOD EC;8P
Adder
14.096
274736ELWOOD EC;9P
Adder
14.096
943121AE2-341 GEN
Solar/Wind Harmer
12.521
943591AF1-030 GEN
Solar/Wind Harmer
8.348
274802UNIV PARK;5U
Adder
4.863
276694AA1-018 GEN2
Solar/Wind Harmer
5.223
274682WAUKEGAN ;7U
Adder
14.735
276805AD2-038 GEN
Solar/Wind Harmer
4.139
274872LEEDK;1U
Solar/Wind Harmer
0.205
276799AD1-013 GEN
Solar/Wind Harmer
1.742
946671AF1-331 GEN
Solar/Wind Harmer
0.33
274855GSG-6 ;RU
Solar/Wind Harmer
2.907
274850MENDOTA H;RU
Solar/Wind Harmer
2.021
276602WESTBROOK C
Solar/Wind Harmer
1.673
276863AD2-134 GEN
Solar/Wind Harmer
1.406
274724RIVER EC ;11
Adder
13.808
959091AF2-200 GEN
Solar/Wind Harmer
15.58
276889AE2-281 GEN
Solar/Wind Harmer
1.493
972236AH1-702 GEN2
Adder
1.693
970571AG2-364 GEN
Solar/Wind Harmer
15.16
274858EASY ROAD;U2
Solar/Wind Harmer
3.599
274760LEE CO EC;1U
Adder
6.986
274767LEE CO EC;8U
Adder
6.904
942111AE2-223 GEN
Solar/Wind Harmer
6.024
276157O29GEN1
Solar/Wind Harmer
2.785
274878BISHOP HL;2U
Solar/Wind Harmer
2.415
274853TWINGROVE;U1
Solar/Wind Harmer
5.03
965091AG1-374 GEN
Solar/Wind Harmer
20.937
959611AF2-252 GEN
Solar/Wind Harmer
1.623
965931AG1-462 GEN
Solar/Wind Harmer
17.6
972231SS25-0005
Solar/Wind Harmer
6.138
972181SS23-001
Solar/Wind Harmer
3.836
274752CRETE EC ;2U
Adder
3.161
274753CRETE EC ;3U
Adder
3.161
276686W4-005 GEN3
Solar/Wind Harmer
1.697
971993AH1-541 GEN
Solar/Wind Harmer
5.184
276668AB2-070 GEN1
Solar/Wind Harmer
1.253
276621W2-048 GEN
Solar/Wind Harmer
3.298
276838X2-022 GEN2
Solar/Wind Harmer
0.123
942481AE2-261 GEN
Solar/Wind Harmer
5.353
274773LINCOLN ;4U
50/50
10.144
274774LINCOLN ;5U
50/50
10.144
274655BRAIDWOOD;2U
50/50
6.709
972207SS24-0001
Solar/Wind Harmer
33.99
941551AE2-152 GEN
Solar/Wind Harmer
4.841
939401AE1-172 GEN
Solar/Wind Harmer
13.646
276776AD2-060 GEN
Solar/Wind Harmer
0.386
274871GR RIDGE ;2U
Solar/Wind Harmer
6.71
276164X3-005 C
Solar/Wind Harmer
0.608
274801UNIV PARK;4U
Adder
5.005
274676JOLIET 29;8U
Adder
26.335
274732ELWOOD EC;7P
Adder
14.096
274674JOLIET 9 ;6U
Adder
13.126
274745AC1-111 GEN9
Adder
4.669
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.735
274828WAUKEGAN ;BP
Adder
9.036
960751AF2-366 GEN
Solar/Wind Harmer
2.307
962781AG1-127 GEN
Solar/Wind Harmer
7.648
276901AD2-066 C O1
Solar/Wind Harmer
2.814
274872LEEDK;1U
Solar/Wind Harmer
6.578
971997AH1-543 GEN
Solar/Wind Harmer
12.448
276861AD2-134 GEN
Solar/Wind Harmer
1.406
957471AF2-041 GEN
Solar/Wind Harmer
23.37
959081AF2-199 GEN
Solar/Wind Harmer
7.79
971067AG2-660 GEN
Solar/Wind Harmer
1.812
276876AE1-163_GEN2
Solar/Wind Harmer
5.225
274723RIVER EC ;12
Adder
13.916
274822ROCKFORD ;11
Adder
15.226
972235AH1-702 GEN1
Adder
1.947
970819AG2-516 GEN
Solar/Wind Harmer
9.216
971475AH1-234 GEN
Solar/Wind Harmer
17.128
970569AG2-363 GEN
Solar/Wind Harmer
22.74
274857EASY ROAD;U1
Solar/Wind Harmer
3.599
274761LEE CO EC;2U
Adder
6.986
274766LEE CO EC;7U
Adder
6.904
274812UNIV PK N;8U
Adder
3.746
276726Z2-087_GEN
Solar/Wind Harmer
5.812
939741AE1-205 GEN
Solar/Wind Harmer
14.698
276158O29GEN2
Solar/Wind Harmer
3.662
274877BISHOP HL;1U
Solar/Wind Harmer
2.415
274854TWINGROVE;U2
Solar/Wind Harmer
4.925
274751CRETE EC ;1U
Adder
3.161
274754CRETE EC ;4U
Adder
3.161
972175AH1-670 GEN
Solar/Wind Harmer
8.543
274880W4-005 GEN4
Solar/Wind Harmer
1.697
963831AG1-236 GEN
Solar/Wind Harmer
5.391
276615X2-022 GEN
Solar/Wind Harmer
1.035
965911AG1-460 GEN
Solar/Wind Harmer
0.25
274775LINCOLN ;6U
50/50
10.144
274776LINCOLN ;7U
50/50
10.144
274777LINCOLN ;8U
50/50
10.144
972227AH1-698 GEN1
50/50
2.589
274687WILL CNTY;4U
50/50
25.533
274687WILL CNTY;4U
50/50
25.533
274863CRW1-WTG
Solar/Wind Harmer
5.114
274864CRW2-WTG
Solar/Wind Harmer
5.114
960591AF2-350 GEN
Solar/Wind Harmer
9.123
970833AG2-524 GEN
Solar/Wind Harmer
7.585
970833AG2-524 GEN
Solar/Wind Harmer
3.528
274827FISK ;RP
Adder
6.662
274675JOLIET 29;7U
Adder
26.336
274675JOLIET 29;7U
Adder
25.395
274731ELWOOD EC;2P
Adder
14.096
274733ELWOOD EC;3P
Adder
14.096
274735ELWOOD EC;4P
Adder
14.096
274728ELWOOD EC;5P
Adder
14.096
274746AC1-111 G10
Adder
4.669
274744AC1-111 GEN8
Adder
4.669
972037AH1-567 GEN1
Adder
0.153
970169AG2-114 GEN
Solar/Wind Harmer
8.092
276868AE1-113 GEN
Solar/Wind Harmer
8.054
276882AE2-255 GEN
Solar/Wind Harmer
2.685
971177AH1-047 GEN
Solar/Wind Harmer
4.661
971411AH1-196 GEN
Solar/Wind Harmer
11.848
971675AH1-338 GEN
Solar/Wind Harmer
14.175
971171AH1-044 GEN
Solar/Wind Harmer
15.58
274823ROCKFORD ;21
Adder
15.116
276612AE2-035 GEN
Solar/Wind Harmer
1.959
926823AC1-168 GEN
Solar/Wind Harmer
3.278
971681AH1-341 GEN
Solar/Wind Harmer
11.345
274814UNIV PK N;0U
Adder
3.779
274807UNIV PK N;3U
Adder
3.771
274805UNIV PK N;1U
Adder
3.754
274811UNIV PK N;7U
Adder
3.746
961011AF2-392 GEN
Solar/Wind Harmer
8.052
276655WTG1_EQ
Solar/Wind Harmer
6.416
276656WTG2_EQ
Solar/Wind Harmer
0.85
959341AF2-225 GEN
Solar/Wind Harmer
11.023
941731AE2-173 GEN
Solar/Wind Harmer
4.273
957751AF2-069 GEN
Solar/Wind Harmer
0.332
274848CAMPGROVE;RU
Solar/Wind Harmer
4.573
946321AF1-296 GEN
Solar/Wind Harmer
7.279
276785W4-005 GEN1
Solar/Wind Harmer
1.697
276174W4-005 GEN2
Solar/Wind Harmer
1.697
276849AB2-070 GEN2
Solar/Wind Harmer
1.253
276848AB2-070 GEN3
Solar/Wind Harmer
1.253
274847GR RIDGE ;BU
Solar/Wind Harmer
4.414
274674JOLIET 9 ;6U
Adder
13.126
274803UNIV PARK;6U
Adder
4.863
958481AF2-142 GEN
Solar/Wind Harmer
12.415
971573AH1-285 GEN
Solar/Wind Harmer
7.114
274861TOP CROP ;1U
Solar/Wind Harmer
5.002
274862TOP CROP ;2U
Solar/Wind Harmer
4.177
274695ROCKY RD ;2P
Adder
9.128
274693ROCKY RD ;1P
Adder
9.038
274697ROCKY RD ;3P
Adder
2.48
274696ROCKY RD ;4P
Adder
9.343
274683WAUKEGAN ;8U
Adder
17.239
274683WAUKEGAN ;8U
Adder
14.531
962691AG1-118 GEN
Solar/Wind Harmer
24.231
958491AF2-143 GEN
Solar/Wind Harmer
12.102
970921AG2-575 GEN
Solar/Wind Harmer
8.042
970921AG2-575 GEN
Solar/Wind Harmer
1.87
942991AE2-321 GEN
Solar/Wind Harmer
7.961
274879MINONK ;1U
Solar/Wind Harmer
5.37
971333AH1-146 GEN
Solar/Wind Harmer
15.765
971335AH1-147 GEN
Solar/Wind Harmer
15.765
971341AH1-150 GEN
Solar/Wind Harmer
15.58
971343AH1-151 GEN
Solar/Wind Harmer
15.58
276872AE1-163_GEN1
Solar/Wind Harmer
5.225
274856ECOGROVE ;U1
Solar/Wind Harmer
2.582
276611AD2-172 GEN
Solar/Wind Harmer
1.959
938861AE1-114 GEN
Solar/Wind Harmer
6.198
274764LEE CO EC;5U
Adder
7.003
274765LEE CO EC;6U
Adder
7.003
274762LEE CO EC;3U
Adder
6.986
274763LEE CO EC;4U
Adder
6.92
276603SUBLETTE C
Solar/Wind Harmer
0.785
274808UNIV PK N;4U
Adder
3.73
972267AH1-718 GEN
Adder
3.068
276741O09 GEN1
Solar/Wind Harmer
2.616
276708O09 GEN2
Solar/Wind Harmer
2.616
274851PROVIDENC;RU
Solar/Wind Harmer
2.059
274849CRESCENT ;1U
Solar/Wind Harmer
1.337
276645AC1-214 GEN1
Solar/Wind Harmer
0.968
276646AC1-214 GEN2
Solar/Wind Harmer
0.968
276782AC1-033 GEN
Solar/Wind Harmer
2.854
960611AF2-352 GEN
Solar/Wind Harmer
1.623
276763AC1-053 GEN1
Solar/Wind Harmer
2.167
276764AC1-053 GEN2
Solar/Wind Harmer
2.167
957381AF2-032 GEN
Solar/Wind Harmer
0.199
990512J1326
External Queue
3.7948038578033447
NYPJM->LTFIMP_NY
CLTF
0.764
WECLTFEXP_WEC->PJM
CLTF
2.949
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.713
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.158
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.559
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.251
MECLTFEXP_MEC->PJM
CLTF
9.38
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.344
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.959
LAGNLTFEXP_LAGN->PJM
CLTF
3.176
TVALTFEXP_TVA->PJM
CLTF
0.822

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT3-4___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT3-4___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.51 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1711.56
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
274775LINCOLN ;6U
50/50
10.317
274776LINCOLN ;7U
50/50
10.317
274777LINCOLN ;8U
50/50
10.317
972227AH1-698 GEN1
50/50
2.574
274863CRW1-WTG
Solar/Wind Harmer
5.073
274864CRW2-WTG
Solar/Wind Harmer
5.073
960591AF2-350 GEN
Solar/Wind Harmer
9.077
970833AG2-524 GEN
Solar/Wind Harmer
7.549
970833AG2-524 GEN
Solar/Wind Harmer
3.511
274687WILL CNTY;4U
Adder
23.987
274687WILL CNTY;4U
Adder
23.987
274827FISK ;RP
Adder
6.648
274675JOLIET 29;7U
Adder
26.268
274675JOLIET 29;7U
Adder
25.33
274731ELWOOD EC;2P
Adder
14.057
274733ELWOOD EC;3P
Adder
14.057
274735ELWOOD EC;4P
Adder
14.057
274728ELWOOD EC;5P
Adder
14.057
274746AC1-111 G10
Adder
4.653
274744AC1-111 GEN8
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970169AG2-114 GEN
Solar/Wind Harmer
8.04
276868AE1-113 GEN
Solar/Wind Harmer
8.028
276882AE2-255 GEN
Solar/Wind Harmer
2.676
971177AH1-047 GEN
Solar/Wind Harmer
4.646
971411AH1-196 GEN
Solar/Wind Harmer
11.808
971675AH1-338 GEN
Solar/Wind Harmer
14.125
971171AH1-044 GEN
Solar/Wind Harmer
15.526
274823ROCKFORD ;21
Adder
15.064
276612AE2-035 GEN
Solar/Wind Harmer
1.952
926823AC1-168 GEN
Solar/Wind Harmer
3.264
971681AH1-341 GEN
Solar/Wind Harmer
11.305
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274805UNIV PK N;1U
Adder
3.747
274811UNIV PK N;7U
Adder
3.739
961011AF2-392 GEN
Solar/Wind Harmer
8.024
276655WTG1_EQ
Solar/Wind Harmer
6.372
276656WTG2_EQ
Solar/Wind Harmer
0.844
959341AF2-225 GEN
Solar/Wind Harmer
10.948
941731AE2-173 GEN
Solar/Wind Harmer
4.243
957751AF2-069 GEN
Solar/Wind Harmer
0.331
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
946321AF1-296 GEN
Solar/Wind Harmer
7.252
276785W4-005 GEN1
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276849AB2-070 GEN2
Solar/Wind Harmer
1.245
276848AB2-070 GEN3
Solar/Wind Harmer
1.245
274773LINCOLN ;4U
50/50
10.317
274774LINCOLN ;5U
50/50
10.317
274655BRAIDWOOD;2U
50/50
6.669
972207SS24-0001
Solar/Wind Harmer
34.568
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.528
276776AD2-060 GEN
Solar/Wind Harmer
0.384
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
276164X3-005 C
Solar/Wind Harmer
0.607
274676JOLIET 29;8U
Adder
26.267
274801UNIV PARK;4U
Adder
4.987
274732ELWOOD EC;7P
Adder
14.057
274674JOLIET 9 ;6U
Adder
13.08
274745AC1-111 GEN9
Adder
4.653
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.689
274828WAUKEGAN ;BP
Adder
9.008
960751AF2-366 GEN
Solar/Wind Harmer
2.299
962781AG1-127 GEN
Solar/Wind Harmer
7.622
274872LEEDK;1U
Solar/Wind Harmer
6.555
276901AD2-066 C O1
Solar/Wind Harmer
2.804
971997AH1-543 GEN
Solar/Wind Harmer
12.404
276861AD2-134 GEN
Solar/Wind Harmer
1.401
957471AF2-041 GEN
Solar/Wind Harmer
23.29
959081AF2-199 GEN
Solar/Wind Harmer
7.763
971067AG2-660 GEN
Solar/Wind Harmer
1.805
274723RIVER EC ;12
Adder
13.906
276876AE1-163_GEN2
Solar/Wind Harmer
5.211
274822ROCKFORD ;11
Adder
15.174
972235AH1-702 GEN1
Adder
1.94
970819AG2-516 GEN
Solar/Wind Harmer
9.184
971475AH1-234 GEN
Solar/Wind Harmer
17.07
970569AG2-363 GEN
Solar/Wind Harmer
22.665
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.962
274766LEE CO EC;7U
Adder
6.88
274812UNIV PK N;8U
Adder
3.739
276726Z2-087_GEN
Solar/Wind Harmer
5.772
939741AE1-205 GEN
Solar/Wind Harmer
14.597
276158O29GEN2
Solar/Wind Harmer
3.648
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
274854TWINGROVE;U2
Solar/Wind Harmer
4.891
274751CRETE EC ;1U
Adder
3.149
274754CRETE EC ;4U
Adder
3.149
972175AH1-670 GEN
Solar/Wind Harmer
8.487
274880W4-005 GEN4
Solar/Wind Harmer
1.686
963831AG1-236 GEN
Solar/Wind Harmer
5.357
276615X2-022 GEN
Solar/Wind Harmer
1.029
965911AG1-460 GEN
Solar/Wind Harmer
0.248
274770LINCOLN ;1U
50/50
10.317
274771LINCOLN ;2U
50/50
10.317
274661LASCO STA;2U
50/50
6.468
972259AH1-714 GEN
50/50
18.154
274660LASCO STA;1U
50/50
6.55
274888KELLY CRK;1U
Solar/Wind Harmer
5.359
274887GEN-1.85
Solar/Wind Harmer
4.838
276843GEN-1.7
Solar/Wind Harmer
0.521
958011AF2-095 GEN
Solar/Wind Harmer
13.071
274847GR RIDGE ;BU
Solar/Wind Harmer
4.392
274674JOLIET 9 ;6U
Adder
13.08
274803UNIV PARK;6U
Adder
4.849
958481AF2-142 GEN
Solar/Wind Harmer
12.397
971573AH1-285 GEN
Solar/Wind Harmer
7.088
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274862TOP CROP ;2U
Solar/Wind Harmer
4.161
274695ROCKY RD ;2P
Adder
9.097
274693ROCKY RD ;1P
Adder
9.008
274697ROCKY RD ;3P
Adder
2.471
274696ROCKY RD ;4P
Adder
9.312
274683WAUKEGAN ;8U
Adder
17.184
274683WAUKEGAN ;8U
Adder
14.485
958491AF2-143 GEN
Solar/Wind Harmer
12.078
962691AG1-118 GEN
Solar/Wind Harmer
24.147
970921AG2-575 GEN
Solar/Wind Harmer
8.014
970921AG2-575 GEN
Solar/Wind Harmer
1.864
942991AE2-321 GEN
Solar/Wind Harmer
7.934
274879MINONK ;1U
Solar/Wind Harmer
5.353
971333AH1-146 GEN
Solar/Wind Harmer
15.712
971335AH1-147 GEN
Solar/Wind Harmer
15.712
971341AH1-150 GEN
Solar/Wind Harmer
15.526
971343AH1-151 GEN
Solar/Wind Harmer
15.526
276872AE1-163_GEN1
Solar/Wind Harmer
5.211
274856ECOGROVE ;U1
Solar/Wind Harmer
2.573
276611AD2-172 GEN
Solar/Wind Harmer
1.952
938861AE1-114 GEN
Solar/Wind Harmer
6.177
274764LEE CO EC;5U
Adder
6.978
274765LEE CO EC;6U
Adder
6.978
274762LEE CO EC;3U
Adder
6.962
274763LEE CO EC;4U
Adder
6.896
274808UNIV PK N;4U
Adder
3.723
276603SUBLETTE C
Solar/Wind Harmer
0.782
972267AH1-718 GEN
Adder
3.057
276741O09 GEN1
Solar/Wind Harmer
2.606
276708O09 GEN2
Solar/Wind Harmer
2.606
274851PROVIDENC;RU
Solar/Wind Harmer
2.051
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.965
276646AC1-214 GEN2
Solar/Wind Harmer
0.965
276782AC1-033 GEN
Solar/Wind Harmer
2.842
960611AF2-352 GEN
Solar/Wind Harmer
1.612
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
957381AF2-032 GEN
Solar/Wind Harmer
0.198
274772LINCOLN ;3U
50/50
10.317
274654BRAIDWOOD;1U
50/50
7.096
972228AH1-698 GEN2
50/50
3.651
276897AD1-100 C
Solar/Wind Harmer
30.712
939351AE1-166 GEN
Solar/Wind Harmer
6.275
276772AC2-154 GEN
Solar/Wind Harmer
2.531
276806AD2-047 C O1
Solar/Wind Harmer
9.71
970941AG2-585 GEN
Solar/Wind Harmer
11.346
970707AG2-453 GEN
Solar/Wind Harmer
24.392
276893AG1-478 C
Solar/Wind Harmer
0.361
274826FISK ;BP
Adder
9.38
274676JOLIET 29;8U
Adder
25.329
274800UNIV PARK;3U
Adder
4.987
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.057
274730ELWOOD EC;6P
Adder
14.057
274734ELWOOD EC;8P
Adder
14.057
274736ELWOOD EC;9P
Adder
14.057
274802UNIV PARK;5U
Adder
4.849
943121AE2-341 GEN
Solar/Wind Harmer
12.476
943591AF1-030 GEN
Solar/Wind Harmer
8.318
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
274682WAUKEGAN ;7U
Adder
14.689
276805AD2-038 GEN
Solar/Wind Harmer
4.131
274872LEEDK;1U
Solar/Wind Harmer
0.204
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.897
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
274724RIVER EC ;11
Adder
13.758
959091AF2-200 GEN
Solar/Wind Harmer
15.526
276889AE2-281 GEN
Solar/Wind Harmer
1.489
972236AH1-702 GEN2
Adder
1.687
970571AG2-364 GEN
Solar/Wind Harmer
15.11
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.962
274767LEE CO EC;8U
Adder
6.88
942111AE2-223 GEN
Solar/Wind Harmer
5.983
276157O29GEN1
Solar/Wind Harmer
2.775
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
274853TWINGROVE;U1
Solar/Wind Harmer
4.996
965091AG1-374 GEN
Solar/Wind Harmer
20.795
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.537
972231SS25-0005
Solar/Wind Harmer
6.114
972181SS23-001
Solar/Wind Harmer
3.821
274752CRETE EC ;2U
Adder
3.149
274753CRETE EC ;3U
Adder
3.149
276686W4-005 GEN3
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.152
276668AB2-070 GEN1
Solar/Wind Harmer
1.245
276621W2-048 GEN
Solar/Wind Harmer
3.278
276838X2-022 GEN2
Solar/Wind Harmer
0.122
942481AE2-261 GEN
Solar/Wind Harmer
5.321
990512J1326
External Queue
3.782650947570801
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.939
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.596
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.239
MECLTFEXP_MEC->PJM
CLTF
9.345
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.161
TVALTFEXP_TVA->PJM
CLTF
0.817

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT2-3___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT2-3___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.7 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1684.87
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
10.317
274774LINCOLN ;5U
50/50
10.317
274655BRAIDWOOD;2U
50/50
6.669
972207SS24-0001
Solar/Wind Harmer
34.568
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.528
276776AD2-060 GEN
Solar/Wind Harmer
0.384
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
276164X3-005 C
Solar/Wind Harmer
0.607
274676JOLIET 29;8U
Adder
26.267
274801UNIV PARK;4U
Adder
4.987
274732ELWOOD EC;7P
Adder
14.057
274674JOLIET 9 ;6U
Adder
13.08
274745AC1-111 GEN9
Adder
4.653
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.689
274828WAUKEGAN ;BP
Adder
9.008
960751AF2-366 GEN
Solar/Wind Harmer
2.299
962781AG1-127 GEN
Solar/Wind Harmer
7.622
274872LEEDK;1U
Solar/Wind Harmer
6.555
276901AD2-066 C O1
Solar/Wind Harmer
2.804
971997AH1-543 GEN
Solar/Wind Harmer
12.404
276861AD2-134 GEN
Solar/Wind Harmer
1.401
957471AF2-041 GEN
Solar/Wind Harmer
23.29
959081AF2-199 GEN
Solar/Wind Harmer
7.763
971067AG2-660 GEN
Solar/Wind Harmer
1.805
274723RIVER EC ;12
Adder
13.906
276876AE1-163_GEN2
Solar/Wind Harmer
5.211
274822ROCKFORD ;11
Adder
15.174
972235AH1-702 GEN1
Adder
1.94
970819AG2-516 GEN
Solar/Wind Harmer
9.184
971475AH1-234 GEN
Solar/Wind Harmer
17.07
970569AG2-363 GEN
Solar/Wind Harmer
22.665
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.962
274766LEE CO EC;7U
Adder
6.88
274812UNIV PK N;8U
Adder
3.739
276726Z2-087_GEN
Solar/Wind Harmer
5.772
939741AE1-205 GEN
Solar/Wind Harmer
14.597
276158O29GEN2
Solar/Wind Harmer
3.648
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
274854TWINGROVE;U2
Solar/Wind Harmer
4.891
274751CRETE EC ;1U
Adder
3.149
274754CRETE EC ;4U
Adder
3.149
972175AH1-670 GEN
Solar/Wind Harmer
8.487
274880W4-005 GEN4
Solar/Wind Harmer
1.686
963831AG1-236 GEN
Solar/Wind Harmer
5.357
276615X2-022 GEN
Solar/Wind Harmer
1.029
965911AG1-460 GEN
Solar/Wind Harmer
0.248
274775LINCOLN ;6U
50/50
10.317
274776LINCOLN ;7U
50/50
10.317
274777LINCOLN ;8U
50/50
10.317
972227AH1-698 GEN1
50/50
2.574
274863CRW1-WTG
Solar/Wind Harmer
5.073
274864CRW2-WTG
Solar/Wind Harmer
5.073
960591AF2-350 GEN
Solar/Wind Harmer
9.077
970833AG2-524 GEN
Solar/Wind Harmer
7.549
970833AG2-524 GEN
Solar/Wind Harmer
3.511
274687WILL CNTY;4U
Adder
23.987
274687WILL CNTY;4U
Adder
23.987
274827FISK ;RP
Adder
6.648
274675JOLIET 29;7U
Adder
26.268
274675JOLIET 29;7U
Adder
25.33
274731ELWOOD EC;2P
Adder
14.057
274733ELWOOD EC;3P
Adder
14.057
274735ELWOOD EC;4P
Adder
14.057
274728ELWOOD EC;5P
Adder
14.057
274746AC1-111 G10
Adder
4.653
274744AC1-111 GEN8
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970169AG2-114 GEN
Solar/Wind Harmer
8.04
276868AE1-113 GEN
Solar/Wind Harmer
8.028
276882AE2-255 GEN
Solar/Wind Harmer
2.676
971177AH1-047 GEN
Solar/Wind Harmer
4.646
971411AH1-196 GEN
Solar/Wind Harmer
11.808
971675AH1-338 GEN
Solar/Wind Harmer
14.125
971171AH1-044 GEN
Solar/Wind Harmer
15.526
274823ROCKFORD ;21
Adder
15.064
276612AE2-035 GEN
Solar/Wind Harmer
1.952
926823AC1-168 GEN
Solar/Wind Harmer
3.264
971681AH1-341 GEN
Solar/Wind Harmer
11.305
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274805UNIV PK N;1U
Adder
3.747
274811UNIV PK N;7U
Adder
3.739
961011AF2-392 GEN
Solar/Wind Harmer
8.024
276655WTG1_EQ
Solar/Wind Harmer
6.372
276656WTG2_EQ
Solar/Wind Harmer
0.844
959341AF2-225 GEN
Solar/Wind Harmer
10.948
941731AE2-173 GEN
Solar/Wind Harmer
4.243
957751AF2-069 GEN
Solar/Wind Harmer
0.331
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
946321AF1-296 GEN
Solar/Wind Harmer
7.252
276785W4-005 GEN1
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276849AB2-070 GEN2
Solar/Wind Harmer
1.245
276848AB2-070 GEN3
Solar/Wind Harmer
1.245
274770LINCOLN ;1U
50/50
10.317
274771LINCOLN ;2U
50/50
10.317
274661LASCO STA;2U
50/50
6.468
972259AH1-714 GEN
50/50
18.154
274660LASCO STA;1U
50/50
6.55
274888KELLY CRK;1U
Solar/Wind Harmer
5.359
274887GEN-1.85
Solar/Wind Harmer
4.838
276843GEN-1.7
Solar/Wind Harmer
0.521
958011AF2-095 GEN
Solar/Wind Harmer
13.071
274847GR RIDGE ;BU
Solar/Wind Harmer
4.392
274674JOLIET 9 ;6U
Adder
13.08
274803UNIV PARK;6U
Adder
4.849
958481AF2-142 GEN
Solar/Wind Harmer
12.397
971573AH1-285 GEN
Solar/Wind Harmer
7.088
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274862TOP CROP ;2U
Solar/Wind Harmer
4.161
274695ROCKY RD ;2P
Adder
9.097
274693ROCKY RD ;1P
Adder
9.008
274697ROCKY RD ;3P
Adder
2.471
274696ROCKY RD ;4P
Adder
9.312
274683WAUKEGAN ;8U
Adder
17.184
274683WAUKEGAN ;8U
Adder
14.485
958491AF2-143 GEN
Solar/Wind Harmer
12.078
962691AG1-118 GEN
Solar/Wind Harmer
24.147
970921AG2-575 GEN
Solar/Wind Harmer
8.014
970921AG2-575 GEN
Solar/Wind Harmer
1.864
942991AE2-321 GEN
Solar/Wind Harmer
7.934
274879MINONK ;1U
Solar/Wind Harmer
5.353
971333AH1-146 GEN
Solar/Wind Harmer
15.712
971335AH1-147 GEN
Solar/Wind Harmer
15.712
971341AH1-150 GEN
Solar/Wind Harmer
15.526
971343AH1-151 GEN
Solar/Wind Harmer
15.526
276872AE1-163_GEN1
Solar/Wind Harmer
5.211
274856ECOGROVE ;U1
Solar/Wind Harmer
2.573
276611AD2-172 GEN
Solar/Wind Harmer
1.952
938861AE1-114 GEN
Solar/Wind Harmer
6.177
274764LEE CO EC;5U
Adder
6.978
274765LEE CO EC;6U
Adder
6.978
274762LEE CO EC;3U
Adder
6.962
274763LEE CO EC;4U
Adder
6.896
274808UNIV PK N;4U
Adder
3.723
276603SUBLETTE C
Solar/Wind Harmer
0.782
972267AH1-718 GEN
Adder
3.057
276741O09 GEN1
Solar/Wind Harmer
2.606
276708O09 GEN2
Solar/Wind Harmer
2.606
274851PROVIDENC;RU
Solar/Wind Harmer
2.051
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.965
276646AC1-214 GEN2
Solar/Wind Harmer
0.965
276782AC1-033 GEN
Solar/Wind Harmer
2.842
960611AF2-352 GEN
Solar/Wind Harmer
1.612
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
957381AF2-032 GEN
Solar/Wind Harmer
0.198
274772LINCOLN ;3U
50/50
10.317
274654BRAIDWOOD;1U
50/50
7.096
972228AH1-698 GEN2
50/50
3.651
276897AD1-100 C
Solar/Wind Harmer
30.712
939351AE1-166 GEN
Solar/Wind Harmer
6.275
276772AC2-154 GEN
Solar/Wind Harmer
2.531
276806AD2-047 C O1
Solar/Wind Harmer
9.71
970941AG2-585 GEN
Solar/Wind Harmer
11.346
970707AG2-453 GEN
Solar/Wind Harmer
24.392
276893AG1-478 C
Solar/Wind Harmer
0.361
274826FISK ;BP
Adder
9.38
274676JOLIET 29;8U
Adder
25.329
274800UNIV PARK;3U
Adder
4.987
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.057
274730ELWOOD EC;6P
Adder
14.057
274734ELWOOD EC;8P
Adder
14.057
274736ELWOOD EC;9P
Adder
14.057
274802UNIV PARK;5U
Adder
4.849
943121AE2-341 GEN
Solar/Wind Harmer
12.476
943591AF1-030 GEN
Solar/Wind Harmer
8.318
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
274682WAUKEGAN ;7U
Adder
14.689
276805AD2-038 GEN
Solar/Wind Harmer
4.131
274872LEEDK;1U
Solar/Wind Harmer
0.204
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.897
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
274724RIVER EC ;11
Adder
13.758
959091AF2-200 GEN
Solar/Wind Harmer
15.526
276889AE2-281 GEN
Solar/Wind Harmer
1.489
972236AH1-702 GEN2
Adder
1.687
970571AG2-364 GEN
Solar/Wind Harmer
15.11
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.962
274767LEE CO EC;8U
Adder
6.88
942111AE2-223 GEN
Solar/Wind Harmer
5.983
276157O29GEN1
Solar/Wind Harmer
2.775
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
274853TWINGROVE;U1
Solar/Wind Harmer
4.996
965091AG1-374 GEN
Solar/Wind Harmer
20.795
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.537
972231SS25-0005
Solar/Wind Harmer
6.114
972181SS23-001
Solar/Wind Harmer
3.821
274752CRETE EC ;2U
Adder
3.149
274753CRETE EC ;3U
Adder
3.149
276686W4-005 GEN3
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.152
276668AB2-070 GEN1
Solar/Wind Harmer
1.245
276621W2-048 GEN
Solar/Wind Harmer
3.278
276838X2-022 GEN2
Solar/Wind Harmer
0.122
942481AE2-261 GEN
Solar/Wind Harmer
5.321
990512J1326
External Queue
3.7826504707336426
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.939
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.596
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.239
MECLTFEXP_MEC->PJM
CLTF
9.345
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.161
TVALTFEXP_TVA->PJM
CLTF
0.817

Details for WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer l/o COMED_P4_023-65-BT4-5___SRT-A


Base Case Flowgate

Area:CE
Facility Description:
WILTON ;4M-WILTON ; 345.0/765.0 kV Ckt 1 transformer
Contingency Name:
COMED_P4_023-65-BT4-5___SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.69 %
Rating:1469.0 MVA
Rating Type:STE
MVA to Mitigate:1684.84
MW Contribution:9.18
Bus #Bus NameTypeMW Contribution
274770LINCOLN ;1U
50/50
10.317
274771LINCOLN ;2U
50/50
10.317
274661LASCO STA;2U
50/50
6.468
972259AH1-714 GEN
50/50
18.154
274660LASCO STA;1U
50/50
6.55
274888KELLY CRK;1U
Solar/Wind Harmer
5.359
274887GEN-1.85
Solar/Wind Harmer
4.838
276843GEN-1.7
Solar/Wind Harmer
0.521
958011AF2-095 GEN
Solar/Wind Harmer
13.071
274847GR RIDGE ;BU
Solar/Wind Harmer
4.392
274674JOLIET 9 ;6U
Adder
13.08
274803UNIV PARK;6U
Adder
4.849
958481AF2-142 GEN
Solar/Wind Harmer
12.397
971573AH1-285 GEN
Solar/Wind Harmer
7.088
274861TOP CROP ;1U
Solar/Wind Harmer
4.983
274862TOP CROP ;2U
Solar/Wind Harmer
4.161
274695ROCKY RD ;2P
Adder
9.097
274693ROCKY RD ;1P
Adder
9.008
274697ROCKY RD ;3P
Adder
2.471
274696ROCKY RD ;4P
Adder
9.312
274683WAUKEGAN ;8U
Adder
17.184
274683WAUKEGAN ;8U
Adder
14.485
958491AF2-143 GEN
Solar/Wind Harmer
12.078
962691AG1-118 GEN
Solar/Wind Harmer
24.147
970921AG2-575 GEN
Solar/Wind Harmer
8.014
970921AG2-575 GEN
Solar/Wind Harmer
1.864
942991AE2-321 GEN
Solar/Wind Harmer
7.934
274879MINONK ;1U
Solar/Wind Harmer
5.353
971333AH1-146 GEN
Solar/Wind Harmer
15.712
971335AH1-147 GEN
Solar/Wind Harmer
15.712
971341AH1-150 GEN
Solar/Wind Harmer
15.526
971343AH1-151 GEN
Solar/Wind Harmer
15.526
276872AE1-163_GEN1
Solar/Wind Harmer
5.211
274856ECOGROVE ;U1
Solar/Wind Harmer
2.573
276611AD2-172 GEN
Solar/Wind Harmer
1.952
938861AE1-114 GEN
Solar/Wind Harmer
6.177
274764LEE CO EC;5U
Adder
6.978
274765LEE CO EC;6U
Adder
6.978
274762LEE CO EC;3U
Adder
6.962
274763LEE CO EC;4U
Adder
6.896
274808UNIV PK N;4U
Adder
3.723
276603SUBLETTE C
Solar/Wind Harmer
0.782
972267AH1-718 GEN
Adder
3.057
276741O09 GEN1
Solar/Wind Harmer
2.606
276708O09 GEN2
Solar/Wind Harmer
2.606
274851PROVIDENC;RU
Solar/Wind Harmer
2.051
274849CRESCENT ;1U
Solar/Wind Harmer
1.331
276645AC1-214 GEN1
Solar/Wind Harmer
0.965
276646AC1-214 GEN2
Solar/Wind Harmer
0.965
276782AC1-033 GEN
Solar/Wind Harmer
2.842
960611AF2-352 GEN
Solar/Wind Harmer
1.612
276763AC1-053 GEN1
Solar/Wind Harmer
2.154
276764AC1-053 GEN2
Solar/Wind Harmer
2.154
957381AF2-032 GEN
Solar/Wind Harmer
0.198
274775LINCOLN ;6U
50/50
10.317
274776LINCOLN ;7U
50/50
10.317
274777LINCOLN ;8U
50/50
10.317
972227AH1-698 GEN1
50/50
2.574
274863CRW1-WTG
Solar/Wind Harmer
5.073
274864CRW2-WTG
Solar/Wind Harmer
5.073
960591AF2-350 GEN
Solar/Wind Harmer
9.077
970833AG2-524 GEN
Solar/Wind Harmer
7.549
970833AG2-524 GEN
Solar/Wind Harmer
3.511
274687WILL CNTY;4U
Adder
23.987
274687WILL CNTY;4U
Adder
23.987
274827FISK ;RP
Adder
6.648
274675JOLIET 29;7U
Adder
26.268
274675JOLIET 29;7U
Adder
25.33
274731ELWOOD EC;2P
Adder
14.057
274733ELWOOD EC;3P
Adder
14.057
274735ELWOOD EC;4P
Adder
14.057
274728ELWOOD EC;5P
Adder
14.057
274746AC1-111 G10
Adder
4.653
274744AC1-111 GEN8
Adder
4.653
972037AH1-567 GEN1
Adder
0.152
970169AG2-114 GEN
Solar/Wind Harmer
8.04
276868AE1-113 GEN
Solar/Wind Harmer
8.028
276882AE2-255 GEN
Solar/Wind Harmer
2.676
971177AH1-047 GEN
Solar/Wind Harmer
4.646
971411AH1-196 GEN
Solar/Wind Harmer
11.808
971675AH1-338 GEN
Solar/Wind Harmer
14.125
971171AH1-044 GEN
Solar/Wind Harmer
15.526
274823ROCKFORD ;21
Adder
15.064
276612AE2-035 GEN
Solar/Wind Harmer
1.952
926823AC1-168 GEN
Solar/Wind Harmer
3.264
971681AH1-341 GEN
Solar/Wind Harmer
11.305
274814UNIV PK N;0U
Adder
3.772
274807UNIV PK N;3U
Adder
3.764
274805UNIV PK N;1U
Adder
3.747
274811UNIV PK N;7U
Adder
3.739
961011AF2-392 GEN
Solar/Wind Harmer
8.024
276655WTG1_EQ
Solar/Wind Harmer
6.372
276656WTG2_EQ
Solar/Wind Harmer
0.844
959341AF2-225 GEN
Solar/Wind Harmer
10.948
941731AE2-173 GEN
Solar/Wind Harmer
4.243
957751AF2-069 GEN
Solar/Wind Harmer
0.331
274848CAMPGROVE;RU
Solar/Wind Harmer
4.555
946321AF1-296 GEN
Solar/Wind Harmer
7.252
276785W4-005 GEN1
Solar/Wind Harmer
1.686
276174W4-005 GEN2
Solar/Wind Harmer
1.686
276849AB2-070 GEN2
Solar/Wind Harmer
1.245
276848AB2-070 GEN3
Solar/Wind Harmer
1.245
274773LINCOLN ;4U
50/50
10.317
274774LINCOLN ;5U
50/50
10.317
274655BRAIDWOOD;2U
50/50
6.669
972207SS24-0001
Solar/Wind Harmer
34.568
941551AE2-152 GEN
Solar/Wind Harmer
4.8
939401AE1-172 GEN
Solar/Wind Harmer
13.528
276776AD2-060 GEN
Solar/Wind Harmer
0.384
274871GR RIDGE ;2U
Solar/Wind Harmer
6.677
276164X3-005 C
Solar/Wind Harmer
0.607
274676JOLIET 29;8U
Adder
26.267
274801UNIV PARK;4U
Adder
4.987
274732ELWOOD EC;7P
Adder
14.057
274674JOLIET 9 ;6U
Adder
13.08
274745AC1-111 GEN9
Adder
4.653
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274682WAUKEGAN ;7U
Adder
14.689
274828WAUKEGAN ;BP
Adder
9.008
960751AF2-366 GEN
Solar/Wind Harmer
2.299
962781AG1-127 GEN
Solar/Wind Harmer
7.622
274872LEEDK;1U
Solar/Wind Harmer
6.555
276901AD2-066 C O1
Solar/Wind Harmer
2.804
971997AH1-543 GEN
Solar/Wind Harmer
12.404
276861AD2-134 GEN
Solar/Wind Harmer
1.401
957471AF2-041 GEN
Solar/Wind Harmer
23.29
959081AF2-199 GEN
Solar/Wind Harmer
7.763
971067AG2-660 GEN
Solar/Wind Harmer
1.805
274723RIVER EC ;12
Adder
13.906
276876AE1-163_GEN2
Solar/Wind Harmer
5.211
274822ROCKFORD ;11
Adder
15.174
972235AH1-702 GEN1
Adder
1.94
970819AG2-516 GEN
Solar/Wind Harmer
9.184
274772LINCOLN ;3U
50/50
10.317
274654BRAIDWOOD;1U
50/50
7.096
972228AH1-698 GEN2
50/50
3.651
276897AD1-100 C
Solar/Wind Harmer
30.712
939351AE1-166 GEN
Solar/Wind Harmer
6.275
276772AC2-154 GEN
Solar/Wind Harmer
2.531
276806AD2-047 C O1
Solar/Wind Harmer
9.71
970941AG2-585 GEN
Solar/Wind Harmer
11.346
970707AG2-453 GEN
Solar/Wind Harmer
24.392
276893AG1-478 C
Solar/Wind Harmer
0.361
274826FISK ;BP
Adder
9.38
274676JOLIET 29;8U
Adder
25.329
274800UNIV PARK;3U
Adder
4.987
972038AH1-567 GEN2
Adder
0.312
274729ELWOOD EC;1P
Adder
14.057
274730ELWOOD EC;6P
Adder
14.057
274734ELWOOD EC;8P
Adder
14.057
274736ELWOOD EC;9P
Adder
14.057
274802UNIV PARK;5U
Adder
4.849
943121AE2-341 GEN
Solar/Wind Harmer
12.476
943591AF1-030 GEN
Solar/Wind Harmer
8.318
276694AA1-018 GEN2
Solar/Wind Harmer
5.215
274682WAUKEGAN ;7U
Adder
14.689
276805AD2-038 GEN
Solar/Wind Harmer
4.131
274872LEEDK;1U
Solar/Wind Harmer
0.204
276799AD1-013 GEN
Solar/Wind Harmer
1.736
946671AF1-331 GEN
Solar/Wind Harmer
0.329
274855GSG-6 ;RU
Solar/Wind Harmer
2.897
274850MENDOTA H;RU
Solar/Wind Harmer
2.014
276602WESTBROOK C
Solar/Wind Harmer
1.667
276863AD2-134 GEN
Solar/Wind Harmer
1.401
274724RIVER EC ;11
Adder
13.758
959091AF2-200 GEN
Solar/Wind Harmer
15.526
276889AE2-281 GEN
Solar/Wind Harmer
1.489
972236AH1-702 GEN2
Adder
1.687
970571AG2-364 GEN
Solar/Wind Harmer
15.11
274858EASY ROAD;U2
Solar/Wind Harmer
3.586
274760LEE CO EC;1U
Adder
6.962
274767LEE CO EC;8U
Adder
6.88
942111AE2-223 GEN
Solar/Wind Harmer
5.983
276157O29GEN1
Solar/Wind Harmer
2.775
274878BISHOP HL;2U
Solar/Wind Harmer
2.405
274853TWINGROVE;U1
Solar/Wind Harmer
4.996
965091AG1-374 GEN
Solar/Wind Harmer
20.795
959611AF2-252 GEN
Solar/Wind Harmer
1.612
965931AG1-462 GEN
Solar/Wind Harmer
17.537
972231SS25-0005
Solar/Wind Harmer
6.114
972181SS23-001
Solar/Wind Harmer
3.821
274752CRETE EC ;2U
Adder
3.149
274753CRETE EC ;3U
Adder
3.149
276686W4-005 GEN3
Solar/Wind Harmer
1.686
971993AH1-541 GEN
Solar/Wind Harmer
5.152
276668AB2-070 GEN1
Solar/Wind Harmer
1.245
276621W2-048 GEN
Solar/Wind Harmer
3.278
276838X2-022 GEN2
Solar/Wind Harmer
0.122
942481AE2-261 GEN
Solar/Wind Harmer
5.321
971475AH1-234 GEN
Solar/Wind Harmer
17.07
970569AG2-363 GEN
Solar/Wind Harmer
22.665
274857EASY ROAD;U1
Solar/Wind Harmer
3.586
274761LEE CO EC;2U
Adder
6.962
274766LEE CO EC;7U
Adder
6.88
274812UNIV PK N;8U
Adder
3.739
276726Z2-087_GEN
Solar/Wind Harmer
5.772
939741AE1-205 GEN
Solar/Wind Harmer
14.597
276158O29GEN2
Solar/Wind Harmer
3.648
274877BISHOP HL;1U
Solar/Wind Harmer
2.405
274854TWINGROVE;U2
Solar/Wind Harmer
4.891
274751CRETE EC ;1U
Adder
3.149
274754CRETE EC ;4U
Adder
3.149
972175AH1-670 GEN
Solar/Wind Harmer
8.487
274880W4-005 GEN4
Solar/Wind Harmer
1.686
963831AG1-236 GEN
Solar/Wind Harmer
5.357
276615X2-022 GEN
Solar/Wind Harmer
1.029
965911AG1-460 GEN
Solar/Wind Harmer
0.248
990512J1326
External Queue
3.782650947570801
NYPJM->LTFIMP_NY
CLTF
0.761
WECLTFEXP_WEC->PJM
CLTF
2.939
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.317
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.596
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.157
CBM West 1LTFEXP_CBM-W1->PJM
CBM
50.392
CBM South 1LTFEXP_CBM-S1->PJM
CBM
2.239
MECLTFEXP_MEC->PJM
CLTF
9.345
SIGELTFEXP_SIGE->PJM
CLTF
0.016
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.343
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.956
LAGNLTFEXP_LAGN->PJM
CLTF
3.161
TVALTFEXP_TVA->PJM
CLTF
0.817
CONTINGENCY 'ATSI_P1-2_TE-345-602_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238889 CKT 1   /*02DAV-BE     345.0 - 02LEMOYN     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7421_05CLOVRD 765_BB2_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AEP_P1-3_#7421_05CLOVRD 765_14_SRT-A'
 OPEN BRANCH FROM BUS 242512 TO BUS 242519 CKT 14   /*05CLOVRD     765.0 - 05CLOVRD     500.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 970238 TO BUS 290599 CKT 1    /*AG2-162 TP   765.0 - 05JEFFRSN_RG 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P7-1_#11046___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY 'AEP_P4_#17234_05GRNTWN 765_N_SRT-A'
 OPEN BRANCH FROM BUS 243207 TO BUS 290222 CKT 3    /*05GRNTWN     765.0 - 05GRNTWN 3EQ   1.0
 OPEN BRANCH FROM BUS 243207 TO BUS 290598 CKT Z1   /*05GRNTWN     765.0 - 05GREENTW_RJ 765.0
 OPEN BRANCH FROM BUS 244658 TO BUS 290221 CKT 3    /*05GRNTWN     138.0 - 05GRNTW3_XFL 138.0
 OPEN BRANCH FROM BUS 290221 TO BUS 290222 CKT 3    /*05GRNTW3_XFL 138.0 - 05GRNTWN 3EQ   1.0
 OPEN BRANCH FROM BUS 290222 TO BUS 290223 CKT 3    /*05GRNTWN 3EQ   1.0 - 05GRNTWN T3   13.8
 OPEN BRANCH FROM BUS 290598 TO BUS 970238 CKT 1    /*05GREENTW_RJ 765.0 - AG2-162 TP   765.0
END
CONTINGENCY 'AEP_P7-1_#11001___SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 246955 CKT 1   /*05DUMONT     345.0 - 05OLIVE_BP   345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243232 CKT 1   /*05MERIDN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 243232 TO BUS 246955 CKT 1   /*05SORENS     345.0 - 05OLIVE_BP   345.0
END
CONTINGENCY 'AEP_P2-2_#6229_05MERIDN 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243228 TO BUS 243232 CKT 1   /*05MERIDN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243234 CKT 1   /*05MERIDN     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243783 CKT 1   /*05MERIDN     345.0 - 05EWHTLY     345.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P2-2_#702_05JEFRSO 765_2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2   /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1   /*05JEFRSO     345.0 - 06CLIFTY     345.0
END
CONTINGENCY 'COMED_P7-1_345-L94507_B-S_+_345-L97008_R-S_SRT-A'
 TRIP BRANCH FROM BUS 274750 TO BUS 255112 CKT 1   /*CRETE EC ;BP 345.0 - 17STJOHN     345.0
 TRIP BRANCH FROM BUS 274804 TO BUS 255201 CKT 1   /*UNIV PK N;RP 345.0 - 17P9701-WEST 345.0
END
CONTINGENCY 'COMED_P7-1_345-L6607__B-S_+_345-L97008_R-S_SRT-A'
 TRIP BRANCH FROM BUS 270728 TO BUS 274750 CKT 1   /*E FRANKFO; B 345.0 - CRETE EC ;BP 345.0
 TRIP BRANCH FROM BUS 274804 TO BUS 255201 CKT 1   /*UNIV PK N;RP 345.0 - 17P9701-WEST 345.0
END
CONTINGENCY 'AEP_P4_#2973_05DUMONT 345_F1_SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 255113 CKT 1   /*05DUMONT     345.0 - 17STILLWELL  345.0
END
CONTINGENCY 'AEP_P4_#2976_05DUMONT 345_F_SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 243234 CKT 1   /*05DUMONT     345.0 - 05TWIN B     345.0
 OPEN BRANCH FROM BUS 243219 TO BUS 255113 CKT 1   /*05DUMONT     345.0 - 17STILLWELL  345.0
END
CONTINGENCY 'AEP_P2-2_#286_05EUGENE 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1   /*05EUGENE     345.0 - 7BUNSONVILLE 345.0
END
CONTINGENCY 'AEP_P2-2_#15388_05ELDERBERRY 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243219 TO BUS 243918 CKT 1   /*05DUMONT     345.0 - 05ELDERBERRY 345.0
END
CONTINGENCY 'COMED_P4_112-65-BT4-5___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270644 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275233 TO BUS 270927 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 275233 TO BUS 275333 CKT 1   /*WILTON   ;4M 345.0 - WILTON   ;4C  33.0
END
CONTINGENCY 'COMED_P4_112-65-BT3-4___SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270644 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;   765.0
 TRIP BRANCH FROM BUS 275232 TO BUS 270926 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ; B 345.0
 TRIP BRANCH FROM BUS 275232 TO BUS 275332 CKT 1   /*WILTON   ;3M 345.0 - WILTON   ;3C  33.0
END
CONTINGENCY 'AEP_P4_#2978_05DUMONT 765_B_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290597 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RG  765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 970244 TO BUS 290597 CKT 1    /*AG2-165 TP   765.0 - 05DUMONT_RG  765.0
END
CONTINGENCY 'AEP_P4_#671_05COOK 345_M2_SRT-A'
 OPEN BRANCH FROM BUS 243215 TO BUS 243229 CKT 1   /*05COOK       345.0 - 05OLIVE      345.0
END
CONTINGENCY 'AEP_P7-1_#10997___SRT-A'
 OPEN BRANCH FROM BUS 243215 TO BUS 243223 CKT 1   /*05COOK       345.0 - 05JACKSON RD 345.0
 OPEN BRANCH FROM BUS 243215 TO BUS 243229 CKT 1   /*05COOK       345.0 - 05OLIVE      345.0
END
CONTINGENCY 'AEP_P4_#6560_05COOK 345_M_SRT-A'
 OPEN BRANCH FROM BUS 243215 TO BUS 243223 CKT 1   /*05COOK       345.0 - 05JACKSON RD 345.0
 OPEN BRANCH FROM BUS 243215 TO BUS 243229 CKT 1   /*05COOK       345.0 - 05OLIVE      345.0
END
CONTINGENCY 'AEP_P1-2_#706_SRT-A'
 OPEN BRANCH FROM BUS 242922 TO BUS 290622 CKT 1    /*05FLTLCK     765.0 - 05GAVIN_RF   765.0
 OPEN BRANCH FROM BUS 242923 TO BUS 290622 CKT Z1   /*05GAVIN      765.0 - 05GAVIN_RF   765.0
END
CONTINGENCY 'AEP_P4_#711_05MARYSV 765_A1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#711_6224_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
END
CONTINGENCY 'AEP_P1-3_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P1-2_#6463_16757_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#3150_13_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 242929 CKT 1   /*05HANG R     765.0 - 05NPROCT     765.0
END
CONTINGENCY 'AEP_P4_#1750_05DUMONT 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243219 CKT 3    /*05DUMONT     765.0 - 05DUMONT     345.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'AEP_P1-2_#695_1681_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290602 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RW  765.0
 OPEN BRANCH FROM BUS 270644 TO BUS 290602 CKT 1    /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY '765-L11215__-S_SRT-A'
 REMOVE SHUNT 1 FROM BUS 270644                    /*WILTON   ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 290602 CKT 1   /*WILTON   ;   765.0 - 05DUMONT_RW  765.0
END
CONTINGENCY 'AEP_P7-1_#11009___SRT-A-1'
 OPEN BRANCH FROM BUS 243229 TO BUS 255199 CKT 1   /*05OLIVE      345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 243229 TO BUS 960680 CKT 1   /*05OLIVE      345.0 - AF2-359 TP   345.0
 OPEN BRANCH FROM BUS 255104 TO BUS 255199 CKT 1   /*17GREEN_ACRE 345.0 - 17P9700-EAST 345.0
END
CONTINGENCY 'AEP_P7-1_#11009___SRT-A-2'
 OPEN BRANCH FROM BUS 243229 TO BUS 255199 CKT 1   /*05OLIVE      345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 255104 TO BUS 255199 CKT 1   /*17GREEN_ACRE 345.0 - 17P9700-EAST 345.0
 OPEN BRANCH FROM BUS 960680 TO BUS 255112 CKT 1   /*AF2-359 TP   345.0 - 17STJOHN     345.0
END
CONTINGENCY 'COMED_P4_023-65-BT3-4___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ; R 345.0
 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;2C  33.0
END
CONTINGENCY 'AEP_P2-2_#15389_05ELDERBERRY 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243229 TO BUS 243918 CKT 1   /*05OLIVE      345.0 - 05ELDERBERRY 345.0
END
CONTINGENCY 'AEP_P4_#3128_05EUGENE 345_A2_SRT-A'
 OPEN BRANCH FROM BUS 243221 TO BUS 249504 CKT 1   /*05EUGENE     345.0 - 08CAYSUB     345.0
 OPEN BRANCH FROM BUS 243221 TO BUS 348885 CKT 1   /*05EUGENE     345.0 - 7BUNSONVILLE 345.0
END
CONTINGENCY 'COMED_P4_023-65-BT2-3___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
END
CONTINGENCY 'COMED_P4_023-65-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270644 TO BUS 270607 CKT 1   /*WILTON   ;   765.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270607 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;   765.0
 TRIP BRANCH FROM BUS 275168 TO BUS 270697 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ; R 345.0
 TRIP BRANCH FROM BUS 275168 TO BUS 275268 CKT 1   /*COLLINS  ;2M 345.0 - COLLINS  ;2C  33.0
END
CONTINGENCY 'COMED_P4_144-45-BT5-8___SRT-A'
 TRIP BRANCH FROM BUS 270916 TO BUS 270917 CKT Z1   /*WAYNE    ; B 345.0 - WAYNE    ; R 345.0
 TRIP BRANCH FROM BUS 971332 TO BUS 270916 CKT 1    /*AH1-146 TP   345.0 - WAYNE    ; B 345.0
END
CONTINGENCY 'COMED_P4_144-45-BT7-8___SRT-A'
 TRIP BRANCH FROM BUS 270916 TO BUS 270900 CKT 1   /*WAYNE    ; B 345.0 - TOLLWAY ; B  345.0
 TRIP BRANCH FROM BUS 275228 TO BUS 270916 CKT 1   /*WAYNE    ;1M 138.0 - WAYNE    ; B 345.0
 TRIP BRANCH FROM BUS 275228 TO BUS 272740 CKT 1   /*WAYNE    ;1M 138.0 - WAYNE    ; B 138.0
 TRIP BRANCH FROM BUS 275228 TO BUS 275328 CKT 1   /*WAYNE    ;1M 138.0 - WAYNE    ;1C  34.5
 TRIP BRANCH FROM BUS 971332 TO BUS 270916 CKT 1   /*AH1-146 TP   345.0 - WAYNE    ; B 345.0
END
CONTINGENCY 'COMED_P4-6_006-345-BT78___SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 270679 CKT Z1   /*BYRON    ; B 345.0 - BYRON    ; R 345.0
 TRIP BRANCH FROM BUS 270678 TO BUS 971332 CKT 1    /*BYRON    ; B 345.0 - AH1-146 TP   345.0
END
CONTINGENCY 'COMED_P2-2_141_PV-138R__1_SRT-A'
 REMOVE SWSHUNT FROM BUS 272257                                 /*PL VALLEY; R 138.0
 TRIP BRANCH FROM BUS 270851 TO BUS 272257 TO BUS 275309 CKT 1  /*PL VALLEY; R 345.0 - PL VALLEY; R 138.0 - PL VALLEY;1C  34.5
 TRIP BRANCH FROM BUS 272257 TO BUS 271677 CKT 1                /*PL VALLEY; R 138.0 - HUNTLEY  ; R 138.0
 TRIP BRANCH FROM BUS 272257 TO BUS 271975 CKT 1                /*PL VALLEY; R 138.0 - MARENGO  ;RT 138.0
END
CONTINGENCY 'COMED_P2-2_154_LV-345R__3_SRT-A'
 DISCONNECT BUS 275194                             /*LIBERTYVI;1M 138.0
 TRIP BRANCH FROM BUS 270807 TO BUS 270883 CKT 1   /*LIBERTYVI; R 345.0 - SILVER LK; R 345.0
END
CONTINGENCY 'COMED_P2-2_116_GG-345R__2_SRT-A'
 DISCONNECT BUS 270769   /*GOODINGS ;2R 345.0
END
CONTINGENCY 'COMED_P2-2_116_GG-345B__4_SRT-A'
 DISCONNECT BUS 270770   /*GOODINGS ;4B 345.0
END
CONTINGENCY 'COMED_P2-2_951_AR-345R__3_SRT-A'
 DISCONNECT BUS 274749   /*AURORA EC;RP 345.0
END
CONTINGENCY 'COMED_P2-2_111_EJ-345B__1_SRT-A'
 DISCONNECT BUS 270732   /*ELECT JCT;1B 345.0
END
CONTINGENCY 'COMED_P4_111-45-L11124__SRT-A'
 DISCONNECT BUS 270732                             /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 270732 TO BUS 270814 CKT 1   /*ELECT JCT;1B 345.0 - LOMBARD  ;4B 345.0
END
CONTINGENCY 'COMED_P4_111-45-TR81____SRT-A'
 DISCONNECT BUS 270732                             /*ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 275182 TO BUS 270732 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1B 345.0
 TRIP BRANCH FROM BUS 275182 TO BUS 271392 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1B 138.0
 TRIP BRANCH FROM BUS 275182 TO BUS 275282 CKT 1   /*ELECT JCT;1M 138.0 - ELECT JCT;1C  34.5
END
CONTINGENCY 'COMED_P1-2_345-L92805__B-R_SRT-A-2'
 TRIP BRANCH FROM BUS 971332 TO BUS 270916 CKT 1   /*AH1-146 TP   345.0 - WAYNE    ; B 345.0
END
CONTINGENCY 'COMED_P1-2_345-L0626__B-R_SRT-A'
 TRIP BRANCH FROM BUS 270678 TO BUS 971332 CKT 1   /*BYRON    ; B 345.0 - AH1-146 TP   345.0
END
CONTINGENCY 'COMED_P4_167-65-BT3-4___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275207 TO BUS 270630 CKT 1   /*PLANO    ;3M 345.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275207 TO BUS 270846 CKT 1   /*PLANO    ;3M 345.0 - PLANO    ; B 345.0
 TRIP BRANCH FROM BUS 275207 TO BUS 275307 CKT 1   /*PLANO    ;3M 345.0 - PLANO    ;3C  33.0
END
CONTINGENCY 'COMED_P4_167-65-BT4-5___SRT-A'
 TRIP BRANCH FROM BUS 270607 TO BUS 270630 CKT 1   /*COLLINS  ;   765.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275208 TO BUS 270630 CKT 1   /*PLANO    ;4M 345.0 - PLANO    ;   765.0
 TRIP BRANCH FROM BUS 275208 TO BUS 270847 CKT 1   /*PLANO    ;4M 345.0 - PLANO    ; R 345.0
 TRIP BRANCH FROM BUS 275208 TO BUS 275308 CKT 1   /*PLANO    ;4M 345.0 - PLANO    ;4C  33.0
END
CONTINGENCY 'COMED_P4-6_111-345-R______SRT-A'
 DISCONNECT BUS 270731   /*ELECT JCT;4R 345.0
 DISCONNECT BUS 270733   /*ELECT JCT;3R 345.0
 DISCONNECT BUS 275183   /*ELECT JCT;3M 138.0
 DISCONNECT BUS 275184   /*ELECT JCT;4M 138.0
END
CONTINGENCY 'COMED_P4_120-45-L12002__SRT-A'
 DISCONNECT BUS 270813                             /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198                             /*LOMBARD  ;2M 138.0
 TRIP BRANCH FROM BUS 275191 TO BUS 270781 CKT 1   /*ITASCA   ;2M 138.0 - ITASCA   ; R 345.0
 TRIP BRANCH FROM BUS 275191 TO BUS 271735 CKT 1   /*ITASCA   ;2M 138.0 - ITASCA   ; R 138.0
 TRIP BRANCH FROM BUS 275191 TO BUS 275291 CKT 1   /*ITASCA   ;2M 138.0 - ITASCA   ;2C  34.5
END
CONTINGENCY 'COMED_P4_120-38-TR82____SRT-A'
 CLOSE LINE FROM BUS 272252 TO BUS 272253 CKT Z1    /*PL HILL  ; B 138.0 - PL HILL  ; R 138.0
 CLOSE LINE FROM BUS 273236 TO BUS 273237 CKT Z1    /*LOMBARD  ;13  13.2 - LOMBARD  ;46  13.2
 DISCONNECT BUS 270813                              /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198                              /*LOMBARD  ;2M 138.0
 TRIP BRANCH FROM BUS 271923 TO BUS 271569 CKT 1    /*LOMBARD  ; R 138.0 - GRACE    ; R 138.0
 TRIP BRANCH FROM BUS 271923 TO BUS 271925 CKT Z1   /*LOMBARD  ; R 138.0 - LOMBARD  ;2R 138.0
 TRIP BRANCH FROM BUS 271923 TO BUS 272253 CKT 1    /*LOMBARD  ; R 138.0 - PL HILL  ; R 138.0
 TRIP BRANCH FROM BUS 271923 TO BUS 273237 CKT 2    /*LOMBARD  ; R 138.0 - LOMBARD  ;46  13.2
 TRIP BRANCH FROM BUS 271925 TO BUS 275198 CKT 1    /*LOMBARD  ;2R 138.0 - LOMBARD  ;2M 138.0
END
CONTINGENCY 'COMED_P2-2_120_LO-345R__2_SRT-A'
 DISCONNECT BUS 270813   /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198   /*LOMBARD  ;2M 138.0
END
CONTINGENCY 'COMED_P4_120-45-L10322__SRT-A'
 DISCONNECT BUS 270813   /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198   /*LOMBARD  ;2M 138.0
END
CONTINGENCY 'COMED_P4_120-45-L11120__SRT-A'
 DISCONNECT BUS 270813                                 /*LOMBARD  ;2R 345.0
 DISCONNECT BUS 275198                                 /*LOMBARD  ;2M 138.0
 MOVE 100 PERCENT LOAD FROM BUS 270749 TO BUS 270751   /*ESS W407M; R 345.0 - ESS W407M;9T 345.0
 TRIP BRANCH FROM BUS 270733 TO BUS 270747 CKT 1       /*ELECT JCT;3R 345.0 - ESS W407K;0T 345.0
 TRIP BRANCH FROM BUS 270747 TO BUS 270753 CKT 1       /*ESS W407K;0T 345.0 - ESS W407M;0T 345.0
 TRIP BRANCH FROM BUS 270753 TO BUS 270749 CKT 1       /*ESS W407M;0T 345.0 - ESS W407M; R 345.0
END
CONTINGENCY 'COMED_P2-2_111_EJ-345R__3_SRT-A'
 DISCONNECT BUS 270733   /*ELECT JCT;3R 345.0
 DISCONNECT BUS 275183   /*ELECT JCT;3M 138.0
END
CONTINGENCY 'COMED_P2-2_111_EJ-345B__2_SRT-A'
 DISCONNECT BUS 270730                                          /*ELECT JCT;2B 345.0
 TRIP BRANCH FROM BUS 270928 TO BUS 272794 TO BUS 275334 CKT 1  /*WOLFS    ; B 345.0 - WOLFS    ; B 138.0 - WOLFS    ;1C  34.5
END
CONTINGENCY 'COMED_P4-6_116-345-R______SRT-A'
 DISCONNECT BUS 270767                                          /*GOODINGS ;1R 345.0
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 DISCONNECT BUS 275240                                          /*GOODINGS ;1M 138.0
 TRIP BRANCH FROM BUS 270729 TO BUS 271385 TO BUS 275351 CKT 1  /*E FRANKFO; R 345.0 - E FRANKFO; R 138.0 - E FRANKFO;3C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L11614__SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270665 CKT 1   /*BLUE ISL ;RT 345.0 - BLUE ISL ; R 345.0
 TRIP BRANCH FROM BUS 270667 TO BUS 270927 CKT 1   /*BLUE ISL ;RT 345.0 - WILTON   ; R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 270667 CKT 1   /*GOODINGS ;2R 345.0 - BLUE ISL ;RT 345.0
END
CONTINGENCY 'COMED_P4_116-45-TR82____SRT-A'
 DISCONNECT BUS 270769                                          /*GOODINGS ;2R 345.0
 TRIP BRANCH FROM BUS 270769 TO BUS 271565 TO BUS 275324 CKT 1  /*GOODINGS ;2R 345.0 - GOODINGS ; R 138.0 - GOODINGS ;2C  34.5
END
CONTINGENCY 'COMED_P4_116-45-L0303___SRT-A'
 DISCONNECT BUS 270769                             /*GOODINGS ;2R 345.0
 REMOVE SWSHUNT FROM BUS 270827                    /*NEVADA   ; R 345.0
 TRIP BRANCH FROM BUS 270854 TO BUS 276883 CKT 1   /*POWERTON ; B 345.0 - AE2-281 TAP  345.0
END
238563 to 238654 ckt 1
238654 to 239289 ckt 1
239289 to 238569 ckt 1
238889 to 238654 ckt 1
243211 to 242933 ckt 1
247977 to 242524 ckt 17
242519 to 314912 ckt 1
243206 to 290606 ckt Z1
290606 to 246999 ckt 1
290602 to 243206 ckt Z1
243918 to 243219 ckt 1
290618 to 242924 ckt Z1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
290623 to 242925 ckt Z1
246929 to 242935 ckt 1
242926 to 246751 ckt 1
242928 to 242939 ckt 2
242928 to 290620 ckt Z1
290620 to 242926 ckt 1
290608 to 242928 ckt Z1
242516 to 242920 ckt 1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
243233 to 249567 ckt 1
248005 to 242528 ckt 1
248013 to 242938 ckt 1
255199 to 243229 ckt 1
255113 to 243219 ckt 1
255112 to 960680 ckt 1
346810 to 247712 ckt 1
276896 to 270926 ckt 1
957470 to 270732 ckt 1
960580 to 270883 ckt 1
960680 to 243229 ckt 1
965420 to 246929 ckt 1
270674 to 255111 ckt 1
270677 to 255109 ckt 1
270694 to 960580 ckt 1
270697 to 275168 ckt 1
275168 to 270607 ckt 1
270732 to 270814 ckt 1
270770 to 270766 ckt 1
270926 to 275232 ckt 1
270927 to 275233 ckt 1
270644 to 290602 ckt 1
275232 to 270644 ckt 1
275233 to 270644 ckt 1

Winter Peak Analysis

The New Service Request AG2-516 was evaluated as a 120.0 MW (72.0 MW Capacity) injection in the ComEd area.

AG2-516 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 120.0 MW (120.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC120.08 %1737.0B2085.730.48
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC117.93 %1737.0B2048.410.48
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC115.82 %1737.0B2011.720.48
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC115.73 %1737.0B2010.180.47
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC115.1 %5133.0B5908.331.33
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC102.6 %5133.0B5266.311.21
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC102.42 %5133.0B5257.211.3
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC101.4 %5133.0B5204.921.21
GD2AEP
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.4 %5133.0B5204.831.21
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC112.15 %3276.0B3674.00.54
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P1-2_#709_546_SRT-A
SingleAC110.76 %3276.0B3628.460.54
GD2AEP
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC110.76 %3276.0B3628.460.54
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC121.71 %2991.0B3640.250.54
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC120.0 %2991.0B3589.250.54
GD2AEP/OVEC
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC120.0 %2991.0B3589.240.54
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
BreakerAC114.0 %4961.0B5655.611.41
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC104.24 %4961.0B5171.461.3
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC102.76 %4961.0B5098.141.31
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC102.76 %4961.0B5098.111.31
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
BreakerAC100.41 %4961.0B4981.371.38
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC103.24 %2219.0B2290.850.48
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC105.42 %2219.0B2339.210.48
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC102.19 %2219.0B2267.590.48
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC102.19 %2219.0B2267.560.48
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC101.94 %2219.0B2262.150.47

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.08 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2085.73
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
960851AF2-376 GEN
50/50
2.066
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
6.161
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
241847AF2-150_GEN
Solar/Wind Helper
0.259
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
1.01
957141AF2-008_MTX
Adder
27.929
944201AF1-088_MTX
Adder
55.858
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398
NYPJM->LTFIMP_NY
CLTF
1.242
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.632
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
MECLTFEXP_MEC->PJM
CLTF
9.671
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.93 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2048.41
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
960851AF2-376 GEN
50/50
2.119
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
944961AF1-161 GEN
50/50
2.389
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
247620Y3-023
50/50
0.466
270144AC1-141 ST1_
50/50
1.789
24642205MAYFLWER
50/50
0.618
962601AG1-109 GEN
50/50
2.389
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
270102X2-052 ST
50/50
1.277
970901AG2-562 GEN
50/50
4.84
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
1.153
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
24639705ELKHART HY
50/50
0.15
270142AC1-141 CT1_
50/50
2.02
270143AC1-141 CT2_
50/50
2.02
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24344105CKG2
50/50
6.335
270101X2-052 CT2
50/50
1.18
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
7.034
24641605TWIN BRNCH
50/50
0.015
24643105BUCHANAN
50/50
0.011
24344005CKG1
50/50
7.905
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
24653605MOTTVILLE
50/50
0.003
270100X2-052 CT1
50/50
1.18
24307105BERRINSP G
50/50
0.017
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
957141AF2-008_MTX
Adder
27.935
944201AF1-088_MTX
Adder
55.87
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
TVALTFEXP_TVA->PJM
CLTF
2.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
NYPJM->LTFIMP_NY
CLTF
1.226
LGEELTFEXP_LGEE->PJM
CLTF
1.819
WECLTFEXP_WEC->PJM
CLTF
2.651
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
MECLTFEXP_MEC->PJM
CLTF
9.7
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.82 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2011.72
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
960851AF2-376 GEN
50/50
2.119
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
1.153
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
7.034
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
957141AF2-008_MTX
Adder
27.935
944201AF1-088_MTX
Adder
55.87
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
TVALTFEXP_TVA->PJM
CLTF
2.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
NYPJM->LTFIMP_NY
CLTF
1.226
LGEELTFEXP_LGEE->PJM
CLTF
1.819
WECLTFEXP_WEC->PJM
CLTF
2.651
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
MECLTFEXP_MEC->PJM
CLTF
9.7
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.73 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2010.18
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
972181SS23-001
Solar/Wind Harmer
0.429
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.267
970289AG2-191 GEN
Solar/Wind Harmer
0.076
24755605MDL-5G
Solar/Wind Harmer
3.247
959091AF2-200 GEN
Solar/Wind Harmer
0.783
946031AF1-268 GEN
Solar/Wind Harmer
0.315
965651AG1-433 GEN
Solar/Wind Harmer
7.934
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
943121AE2-341 GEN
Solar/Wind Harmer
0.611
970291AG2-192 GEN
Solar/Wind Harmer
0.052
970289AG2-191 GEN
Solar/Wind Harmer
0.529
957471AF2-041 GEN
Solar/Wind Harmer
1.175
274848CAMPGROVE;RU
Solar/Wind Harmer
6.827
960851AF2-376 GEN
50/50
2.006
965021AG1-366 GEN
Solar/Wind Harmer
4.505
958861AF2-177 GEN
Solar/Wind Harmer
15.401
945371AF1-202 GEN
Solar/Wind Harmer
7.254
276893AG1-478 C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.199
957841AF2-078 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.634
270032AE2-172
Solar/Wind Harmer
3.17
971997AH1-543 GEN
Solar/Wind Harmer
0.623
276863AD2-134 GEN
Solar/Wind Harmer
2.419
274863CRW1-WTG
Solar/Wind Harmer
7.421
276889AE2-281 GEN
Solar/Wind Harmer
2.513
24691005MDL-2G C
Solar/Wind Harmer
4.926
274856ECOGROVE ;U1
Solar/Wind Harmer
4.543
971549AH1-272 GEN
Solar/Wind Harmer
0.704
276158O29GEN2
Solar/Wind Harmer
5.536
276708O09 GEN2
Solar/Wind Harmer
4.66
246937BC-WTG2
Solar/Wind Helper
5.567
270485AE1-090_GEN
Solar/Wind Helper
0.16
971617AH1-308 GEN
Solar/Wind Harmer
4.999
943021AE2-325 GEN
Solar/Wind Harmer
2.884
958011AF2-095 GEN
Solar/Wind Harmer
0.601
971573AH1-285 GEN
Solar/Wind Harmer
0.349
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
942991AE2-321 GEN
Solar/Wind Harmer
0.396
971333AH1-146 GEN
Solar/Wind Harmer
0.788
24697905MDL-4G C
Solar/Wind Harmer
3.247
970819AG2-516 GEN
Solar/Wind Harmer
0.466
274851PROVIDENC;RU
Solar/Wind Harmer
3.588
964611AG1-324 GEN
Solar/Wind Harmer
0.34
270201AC2-176 GEN
Solar/Wind Harmer
6.374
274878BISHOP HL;2U
Solar/Wind Harmer
4.366
24699105WLD G1 C
Solar/Wind Harmer
4.824
965931AG1-462 GEN
Solar/Wind Harmer
0.935
270499AE1-146 GEN
Solar/Wind Helper
0.547
24729205KEY G1
50/50
6.542
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.904
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
7.977
270004AE1-209 GEN
Solar/Wind Harmer
6.21
274872LEEDK;1U
Solar/Wind Harmer
0.175
270180AB1-006 GEN1
Solar/Wind Harmer
9.228
24791305MDL-5G
Solar/Wind Harmer
3.247
959081AF2-199 GEN
Solar/Wind Harmer
0.392
971475AH1-234 GEN
Solar/Wind Harmer
0.867
276646AC1-214 GEN2
Solar/Wind Harmer
1.624
24386205FR-12G C
Solar/Wind Harmer
3.066
276726Z2-087_GEN
Solar/Wind Harmer
9.698
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.942
270246TR4_N_V150
Solar/Wind Harmer
1.13
24695305TIMB G C
Solar/Wind Harmer
9.393
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.408
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.398
971343AH1-151 GEN
Solar/Wind Harmer
0.783
970169AG2-114 GEN
Solar/Wind Harmer
0.387
961011AF2-392 GEN
Solar/Wind Harmer
11.826
270227U2-072_GEN3
Solar/Wind Helper
0.148
270228U2-072_GEN4
Solar/Wind Helper
0.148
276820AF1-078_GEN
Solar/Wind Helper
0.158
960971AF2-388 GEN
Solar/Wind Harmer
15.869
970349AG2-230 GEN
Solar/Wind Harmer
0.705
971347AH1-153 GEN
Solar/Wind Harmer
0.705
961051AF2-396 GEN
Solar/Wind Harmer
0.936
961051AF2-396 GEN
Solar/Wind Harmer
7.484
270599AE1-208 GEN
Solar/Wind Harmer
0.359
970245AG2-165 GEN
Solar/Wind Harmer
0.864
972231SS25-0005
Solar/Wind Harmer
0.686
274862TOP CROP ;2U
Solar/Wind Harmer
6.626
970921AG2-575 GEN
Solar/Wind Harmer
0.399
970921AG2-575 GEN
Solar/Wind Harmer
1.595
274879MINONK ;1U
Solar/Wind Harmer
9.334
971411AH1-196 GEN
Solar/Wind Harmer
0.592
274855GSG-6 ;RU
Solar/Wind Harmer
5.004
24386405FR-21G C
Solar/Wind Harmer
2.937
942871AE2-306 GEN
Solar/Wind Helper
0.222
945641AF1-229 GEN
Solar/Wind Helper
0.452
270541AE2-072 C
Solar/Wind Helper
0.467
970583AG2-370 GEN
50/50
2.718
970031AG2-029 GEN
Solar/Wind Harmer
2.053
270247TR4_N_V136
Solar/Wind Harmer
1.13
965051AG1-369 GEN
Solar/Wind Harmer
0.287
960591AF2-350 GEN
Solar/Wind Harmer
0.418
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
7.81
939401AE1-172 GEN
Solar/Wind Harmer
15.852
276876AE1-163_GEN2
Solar/Wind Harmer
8.794
274857EASY ROAD;U1
Solar/Wind Harmer
6.016
961761AG1-017 GEN
Solar/Wind Harmer
0.372
276656WTG2_EQ
Solar/Wind Harmer
0.85
941731AE2-173 GEN
Solar/Wind Harmer
3.73
270462AD2-086
Solar/Wind Helper
1.844
270317AD1-130_GEN
Solar/Wind Helper
1.203
270287AF1-227 GEN3
Solar/Wind Helper
0.376
944531AF1-118 GEN
Solar/Wind Harmer
1.998
274887GEN-1.85
Solar/Wind Harmer
7.789
970707AG2-453 GEN
Solar/Wind Harmer
1.162
970833AG2-524 GEN
Solar/Wind Harmer
3.611
958481AF2-142 GEN
Solar/Wind Harmer
0.607
276868AE1-113 GEN
Solar/Wind Harmer
13.346
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
960791AF2-370 GEN
Solar/Wind Harmer
1.562
276903AD2-071 C
Solar/Wind Harmer
0.38
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.04
270224U2-072_GEN2
Solar/Wind Helper
0.148
270391AF1-285 GEN3
Solar/Wind Helper
0.296
241847AF2-150_GEN
Solar/Wind Helper
0.259
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.857
945111AF1-176 GEN
Solar/Wind Harmer
4.67
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
42.42
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.232
970571AG2-364 GEN
Solar/Wind Harmer
0.776
970825AG2-519 GEN
Solar/Wind Harmer
0.43
970825AG2-519 GEN
Solar/Wind Harmer
1.65
971681AH1-341 GEN
Solar/Wind Harmer
0.578
938861AE1-114 GEN
Solar/Wind Harmer
9.013
276603SUBLETTE C
Solar/Wind Harmer
1.309
253378AE2-206_GEN
Solar/Wind Helper
0.35
970615AG2-402 GEN
50/50
4.505
24729405KEY G3
50/50
6.653
24729505KEY G4
50/50
6.542
270043AE2-236 GEN
Solar/Wind Harmer
0.362
971771AH1-392 GEN
Solar/Wind Harmer
0.427
270505AE1-170 C O1
Solar/Wind Harmer
0.702
274888KELLY CRK;1U
Solar/Wind Harmer
8.479
970941AG2-585 GEN
Solar/Wind Harmer
0.522
971605AH1-302 GEN
Solar/Wind Harmer
6.121
276805AD2-038 GEN
Solar/Wind Harmer
7.241
274850MENDOTA H;RU
Solar/Wind Harmer
3.544
276861AD2-134 GEN
Solar/Wind Harmer
2.419
274864CRW2-WTG
Solar/Wind Harmer
7.421
970569AG2-363 GEN
Solar/Wind Harmer
1.163
274858EASY ROAD;U2
Solar/Wind Harmer
6.016
276157O29GEN1
Solar/Wind Harmer
5.536
957751AF2-069 GEN
Solar/Wind Harmer
0.496
939741AE1-205 GEN
Solar/Wind Harmer
0.746
246938BC-WTG3
Solar/Wind Helper
5.504
246936BC-WTG1
Solar/Wind Helper
5.567
970521AG2-332 GEN
50/50
10.52
247521TR3_G114
Solar/Wind Harmer
8.362
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.864
970517AG2-330 GEN
Solar/Wind Harmer
13.48
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
958821AF2-173 GEN
Solar/Wind Harmer
0.557
971335AH1-147 GEN
Solar/Wind Harmer
0.788
24697605MDL-3G C
Solar/Wind Harmer
4.918
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.783
926823AC1-168 GEN
Solar/Wind Harmer
4.753
24385905FR-11G C
Solar/Wind Harmer
5.774
276782AC1-033 GEN
Solar/Wind Harmer
4.932
24725505WLD G2 C
Solar/Wind Harmer
4.854
946321AF1-296 GEN
Solar/Wind Harmer
10.986
958581AF2-149 GEN
Solar/Wind Helper
0.21
960611AF2-352 GEN
Solar/Wind Harmer
0.98
247620Y3-023
50/50
0.451
965041AG1-368 GEN
Solar/Wind Harmer
0.679
270191TR4_S_V150
Solar/Wind Harmer
6.235
965101AG1-375 GEN
Solar/Wind Harmer
0.494
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.359
971917AH1-482 GEN
Solar/Wind Harmer
6.492
276691AA1-018 GEN1
Solar/Wind Harmer
0.436
276872AE1-163_GEN1
Solar/Wind Harmer
8.794
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.326
971067AG2-660 GEN
Solar/Wind Harmer
1.567
970115AG2-085 GEN
Solar/Wind Harmer
0.156
276741O09 GEN1
Solar/Wind Harmer
4.66
276655WTG1_EQ
Solar/Wind Harmer
6.423
270578AF1-285 GEN2
Solar/Wind Helper
0.296
270286AF1-227 GEN2
Solar/Wind Helper
0.376
247522W1-056 GEN
Solar/Wind Helper
1.925
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.292
959331AF2-224 GEN
Solar/Wind Harmer
1.126
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.913
276843GEN-1.7
Solar/Wind Harmer
0.69
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.537
276882AE2-255 GEN
Solar/Wind Harmer
4.21
960441AF2-335 GEN
Solar/Wind Harmer
0.39
270223U2-072_GEN1
Solar/Wind Helper
0.148
966831AG1-554 GEN
Solar/Wind Helper
0.282
274854TWINGROVE;U2
Solar/Wind Harmer
5.982
971599AH1-298 GEN
50/50
10.098
960861AF2-377 GEN
50/50
2.301
24729305KEY G2
50/50
6.653
970611AG2-400 GEN
Solar/Wind Harmer
1.126
270071AF1-092 GEN
Solar/Wind Harmer
0.917
970321AG2-212 GEN
Solar/Wind Harmer
0.864
270005AE1-210 C O1
Solar/Wind Harmer
6.21
276602WESTBROOK C
Solar/Wind Harmer
2.759
276645AC1-214 GEN1
Solar/Wind Harmer
1.624
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.566
24387305FR-4G C
Solar/Wind Harmer
4.405
24386605FR-22G C
Solar/Wind Harmer
2.937
24387005FR-3G C
Solar/Wind Harmer
2.908
942111AE2-223 GEN
Solar/Wind Harmer
8.728
960841AF2-375 GEN
Solar/Wind Helper
0.566
276806AD2-047 C O1
Solar/Wind Harmer
12.864
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.313
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.481
971341AH1-150 GEN
Solar/Wind Harmer
0.783
270302AB2-170 GEN
Solar/Wind Helper
1.203
270231U2-072_GEN5
Solar/Wind Helper
0.148
270471AD2-092_GEN
Solar/Wind Helper
0.507
274849CRESCENT ;1U
Solar/Wind Harmer
2.48
274877BISHOP HL;1U
Solar/Wind Harmer
4.366
270349AD2-093_GEN
Solar/Wind Helper
0.507
959341AF2-225 GEN
Solar/Wind Harmer
0.56
957201AF2-014 GEN
Solar/Wind Helper
3.962
270284AF1-227 GEN1
Solar/Wind Helper
1.019
270428AC2-015 C
Solar/Wind Helper
0.368
253383AE2-342_GEN
Solar/Wind Helper
0.101
957141AF2-008_MTX
Adder
26.838
944201AF1-088_MTX
Adder
53.676
LAGNLTFEXP_LAGN->PJM
CLTF
5.561
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.712
TVALTFEXP_TVA->PJM
CLTF
2.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.277
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.26
NYPJM->LTFIMP_NY
CLTF
1.178
LGEELTFEXP_LGEE->PJM
CLTF
1.703
WECLTFEXP_WEC->PJM
CLTF
2.559
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.912
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.562
MECLTFEXP_MEC->PJM
CLTF
9.361
SIGELTFEXP_SIGE->PJM
CLTF
0.191

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.1 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5908.33
MW Contribution:1.33
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
19.431
972259AH1-714 GEN
50/50
40.808
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.461
970239AG2-162 GEN
Solar/Wind Harmer
1.313
971997AH1-543 GEN
Solar/Wind Harmer
1.783
276863AD2-134 GEN
Solar/Wind Harmer
6.95
274863CRW1-WTG
Solar/Wind Harmer
21.192
276889AE2-281 GEN
Solar/Wind Harmer
7.109
274856ECOGROVE ;U1
Solar/Wind Harmer
12.97
276158O29GEN2
Solar/Wind Harmer
15.685
276708O09 GEN2
Solar/Wind Harmer
13.202
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
12.791
274880W4-005 GEN4
Solar/Wind Harmer
9.383
971993AH1-541 GEN
Solar/Wind Harmer
0.872
276838X2-022 GEN2
Solar/Wind Harmer
0.749
274661LASCO STA;2U
50/50
15.733
958011AF2-095 GEN
Solar/Wind Harmer
1.715
971573AH1-285 GEN
Solar/Wind Harmer
1.013
942991AE2-321 GEN
Solar/Wind Harmer
1.138
958491AF2-143 GEN
Solar/Wind Harmer
1.699
971333AH1-146 GEN
Solar/Wind Harmer
2.261
970819AG2-516 GEN
Solar/Wind Harmer
1.331
274851PROVIDENC;RU
Solar/Wind Harmer
10.117
274878BISHOP HL;2U
Solar/Wind Harmer
12.298
945421AF1-207 GEN
Solar/Wind Harmer
0
965931AG1-462 GEN
Solar/Wind Harmer
2.627
965091AG1-374 GEN
Solar/Wind Harmer
3.063
24697905MDL-4G C
Solar/Wind Harmer
8.432
943021AE2-325 GEN
Solar/Wind Harmer
6.363
274776LINCOLN ;7U
50/50
19.431
274861TOP CROP ;1U
Solar/Wind Harmer
22.631
274872LEEDK;1U
Solar/Wind Harmer
0.505
970373AG2-245 GEN
Solar/Wind Harmer
2.382
959081AF2-199 GEN
Solar/Wind Harmer
1.122
270526AF1-158 GEN
Solar/Wind Harmer
0
971475AH1-234 GEN
Solar/Wind Harmer
2.475
964401AG1-302 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
4.58
276726Z2-087_GEN
Solar/Wind Harmer
27.164
270180AB1-006 GEN1
Solar/Wind Harmer
23.962
24791305MDL-5G
Solar/Wind Harmer
8.432
24386205FR-12G C
Solar/Wind Harmer
7.899
276764AC1-053 GEN2
Solar/Wind Harmer
12.172
963741AG1-226 GEN
Solar/Wind Harmer
3.747
943591AF1-030 GEN
Solar/Wind Harmer
1.187
965681AG1-436 GEN
Solar/Wind Harmer
1.481
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.245
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
970169AG2-114 GEN
Solar/Wind Harmer
1.098
961011AF2-392 GEN
Solar/Wind Harmer
33.596
276785W4-005 GEN1
Solar/Wind Harmer
9.383
274777LINCOLN ;8U
50/50
19.431
970245AG2-165 GEN
Solar/Wind Harmer
3.073
970349AG2-230 GEN
Solar/Wind Harmer
1.949
971347AH1-153 GEN
Solar/Wind Harmer
1.949
972231SS25-0005
Solar/Wind Harmer
1.875
970921AG2-575 GEN
Solar/Wind Harmer
1.15
970921AG2-575 GEN
Solar/Wind Harmer
4.601
274862TOP CROP ;2U
Solar/Wind Harmer
18.798
274855GSG-6 ;RU
Solar/Wind Harmer
14.378
971411AH1-196 GEN
Solar/Wind Harmer
1.697
274879MINONK ;1U
Solar/Wind Harmer
26.545
961051AF2-396 GEN
Solar/Wind Harmer
2.004
961051AF2-396 GEN
Solar/Wind Harmer
16.031
24386405FR-21G C
Solar/Wind Harmer
7.566
276763AC1-053 GEN1
Solar/Wind Harmer
12.172
274775LINCOLN ;6U
50/50
19.431
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.191
276694AA1-018 GEN2
Solar/Wind Harmer
22.17
939401AE1-172 GEN
Solar/Wind Harmer
45.502
970519AG2-331 GEN
Solar/Wind Harmer
35.63
276876AE1-163_GEN2
Solar/Wind Harmer
24.881
958381AF2-132 GEN
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
17.129
276656WTG2_EQ
Solar/Wind Harmer
2.382
941731AE2-173 GEN
Solar/Wind Harmer
10.448
970707AG2-453 GEN
Solar/Wind Harmer
3.427
274887GEN-1.85
Solar/Wind Harmer
22.209
970833AG2-524 GEN
Solar/Wind Harmer
10.449
958481AF2-142 GEN
Solar/Wind Harmer
1.723
274770LINCOLN ;1U
50/50
19.431
274771LINCOLN ;2U
50/50
19.431
276897AD1-100 C
Solar/Wind Harmer
122.673
971177AH1-047 GEN
Solar/Wind Harmer
0.666
971769AH1-391 GEN
Solar/Wind Harmer
1.122
971681AH1-341 GEN
Solar/Wind Harmer
1.647
938861AE1-114 GEN
Solar/Wind Harmer
25.688
970571AG2-364 GEN
Solar/Wind Harmer
2.191
964861AG1-349 GEN
Solar/Wind Harmer
0
276603SUBLETTE C
Solar/Wind Harmer
3.725
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
38.217
945111AF1-176 GEN
Solar/Wind Harmer
1.746
945111AF1-176 GEN
Solar/Wind Harmer
9.517
276174W4-005 GEN2
Solar/Wind Harmer
9.383
276621W2-048 GEN
Solar/Wind Harmer
19.919
274772LINCOLN ;3U
50/50
19.431
274774LINCOLN ;5U
50/50
19.431
274660LASCO STA;1U
50/50
15.692
274888KELLY CRK;1U
Solar/Wind Harmer
24.176
970941AG2-585 GEN
Solar/Wind Harmer
1.489
970243AG2-164 GEN
Solar/Wind Harmer
3.083
276805AD2-038 GEN
Solar/Wind Harmer
20.528
274850MENDOTA H;RU
Solar/Wind Harmer
10.183
276861AD2-134 GEN
Solar/Wind Harmer
6.95
274864CRW2-WTG
Solar/Wind Harmer
21.192
970569AG2-363 GEN
Solar/Wind Harmer
3.287
274858EASY ROAD;U2
Solar/Wind Harmer
17.129
276157O29GEN1
Solar/Wind Harmer
15.685
971605AH1-302 GEN
Solar/Wind Harmer
16.002
957751AF2-069 GEN
Solar/Wind Harmer
1.398
971771AH1-392 GEN
Solar/Wind Harmer
0.951
939741AE1-205 GEN
Solar/Wind Harmer
2.09
270505AE1-170 C O1
Solar/Wind Harmer
1.544
276668AB2-070 GEN1
Solar/Wind Harmer
7.133
970241AG2-163 GEN
Solar/Wind Harmer
2.082
970699AG2-449 GEN
Solar/Wind Harmer
1.37
971675AH1-338 GEN
Solar/Wind Harmer
2.038
276868AE1-113 GEN
Solar/Wind Harmer
37.954
274853TWINGROVE;U1
Solar/Wind Harmer
25.187
970781AG2-491 GEN
Solar/Wind Harmer
1.018
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
6.313
970513AG2-328 GEN
Solar/Wind Harmer
3.073
970517AG2-330 GEN
Solar/Wind Harmer
47.935
970833AG2-524 GEN
Solar/Wind Harmer
1.306
962781AG1-127 GEN
Solar/Wind Harmer
1.094
971335AH1-147 GEN
Solar/Wind Harmer
2.261
971171AH1-044 GEN
Solar/Wind Harmer
2.245
926823AC1-168 GEN
Solar/Wind Harmer
13.49
959141AF2-205 GEN
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
13.894
946321AF1-296 GEN
Solar/Wind Harmer
30.921
959611AF2-252 GEN
Solar/Wind Harmer
4.084
960611AF2-352 GEN
Solar/Wind Harmer
4.084
24697605MDL-3G C
Solar/Wind Harmer
12.77
270181AB1-006 GEN2
Solar/Wind Harmer
1.589
24385905FR-11G C
Solar/Wind Harmer
14.875
963831AG1-236 GEN
Solar/Wind Harmer
26.291
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.237
971067AG2-660 GEN
Solar/Wind Harmer
4.489
276872AE1-163_GEN1
Solar/Wind Harmer
24.881
971917AH1-482 GEN
Solar/Wind Harmer
17.025
276741O09 GEN1
Solar/Wind Harmer
13.202
276655WTG1_EQ
Solar/Wind Harmer
17.991
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
26.816
276686W4-005 GEN3
Solar/Wind Harmer
9.383
963841AG1-237 GEN
Solar/Wind Harmer
28.974
24344105CKG2
50/50
20.623
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.967
965791AG1-447 GEN
Solar/Wind Harmer
13.036
274872LEEDK;1U
Solar/Wind Harmer
33.259
276882AE2-255 GEN
Solar/Wind Harmer
11.974
274854TWINGROVE;U2
Solar/Wind Harmer
24.922
970321AG2-212 GEN
Solar/Wind Harmer
3.073
970333AG2-219 GEN
Solar/Wind Harmer
3.769
276602WESTBROOK C
Solar/Wind Harmer
7.928
276645AC1-214 GEN1
Solar/Wind Harmer
4.58
942111AE2-223 GEN
Solar/Wind Harmer
24.448
24387305FR-4G C
Solar/Wind Harmer
11.35
24386605FR-22G C
Solar/Wind Harmer
7.566
24387005FR-3G C
Solar/Wind Harmer
7.491
276806AD2-047 C O1
Solar/Wind Harmer
36.681
274847GR RIDGE ;BU
Solar/Wind Harmer
21.169
971341AH1-150 GEN
Solar/Wind Harmer
2.245
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
7.135
972207SS24-0001
Solar/Wind Harmer
3.785
972181SS23-001
Solar/Wind Harmer
1.172
959091AF2-200 GEN
Solar/Wind Harmer
2.245
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
6.992
274877BISHOP HL;1U
Solar/Wind Harmer
12.298
24755605MDL-5G
Solar/Wind Harmer
8.432
943121AE2-341 GEN
Solar/Wind Harmer
1.781
274871GR RIDGE ;2U
Solar/Wind Harmer
27.664
957471AF2-041 GEN
Solar/Wind Harmer
3.367
274848CAMPGROVE;RU
Solar/Wind Harmer
19.198
959341AF2-225 GEN
Solar/Wind Harmer
1.567
270449AD2-020 GEN
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
7.133
957141AF2-008_MTX
Adder
79.174
944201AF1-088_MTX
Adder
158.348
LAGNLTFEXP_LAGN->PJM
CLTF
11.371
TVALTFEXP_TVA->PJM
CLTF
3.759
CBM West 2LTFEXP_CBM-W2->PJM
CBM
107.27
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
80.045
NYPJM->LTFIMP_NY
CLTF
3.036
LGEELTFEXP_LGEE->PJM
CLTF
1.376
WECLTFEXP_WEC->PJM
CLTF
7.298
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.33
AG2-052LTFEXP_AG2-052->PJM
LTF
0.418
AH1-155LTFEXP_AH1-155->PJM
LTF
0.626
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.652
CBM West 1LTFEXP_CBM-W1->PJM
CBM
203.922
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.94
MECLTFEXP_MEC->PJM
CLTF
25.385
SIGELTFEXP_SIGE->PJM
CLTF
0.329

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.6 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5266.31
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
17.743
972259AH1-714 GEN
50/50
37.165
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.151
276863AD2-134 GEN
Solar/Wind Harmer
6.323
971997AH1-543 GEN
Solar/Wind Harmer
1.619
274863CRW1-WTG
Solar/Wind Harmer
19.177
276889AE2-281 GEN
Solar/Wind Harmer
6.448
274856ECOGROVE ;U1
Solar/Wind Harmer
11.794
276158O29GEN2
Solar/Wind Harmer
14.241
276708O09 GEN2
Solar/Wind Harmer
11.987
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
10.946
274880W4-005 GEN4
Solar/Wind Harmer
8.359
971993AH1-541 GEN
Solar/Wind Harmer
0.777
276838X2-022 GEN2
Solar/Wind Harmer
0.667
971549AH1-272 GEN
Solar/Wind Harmer
1.468
942481AE2-261 GEN
Solar/Wind Harmer
2.334
970239AG2-162 GEN
Solar/Wind Harmer
0.809
970513AG2-328 GEN
Solar/Wind Harmer
2.77
970517AG2-330 GEN
Solar/Wind Harmer
43.205
970833AG2-524 GEN
Solar/Wind Harmer
1.188
962781AG1-127 GEN
Solar/Wind Harmer
0.996
971335AH1-147 GEN
Solar/Wind Harmer
2.057
971171AH1-044 GEN
Solar/Wind Harmer
2.042
926823AC1-168 GEN
Solar/Wind Harmer
12.228
276782AC1-033 GEN
Solar/Wind Harmer
12.583
946321AF1-296 GEN
Solar/Wind Harmer
28.079
959141AF2-205 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.666
960611AF2-352 GEN
Solar/Wind Harmer
3.666
24697605MDL-3G C
Solar/Wind Harmer
10.929
270181AB1-006 GEN2
Solar/Wind Harmer
1.36
963831AG1-236 GEN
Solar/Wind Harmer
23.413
24385905FR-11G C
Solar/Wind Harmer
12.68
274777LINCOLN ;8U
50/50
17.743
970245AG2-165 GEN
Solar/Wind Harmer
2.77
970349AG2-230 GEN
Solar/Wind Harmer
1.782
24344105CKG2
50/50
19.079
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.789
965791AG1-447 GEN
Solar/Wind Harmer
11.789
274872LEEDK;1U
Solar/Wind Harmer
30.269
276882AE2-255 GEN
Solar/Wind Harmer
10.87
274854TWINGROVE;U2
Solar/Wind Harmer
22.37
274776LINCOLN ;7U
50/50
17.743
274872LEEDK;1U
Solar/Wind Harmer
0.459
274861TOP CROP ;1U
Solar/Wind Harmer
20.552
959081AF2-199 GEN
Solar/Wind Harmer
1.021
970373AG2-245 GEN
Solar/Wind Harmer
2.116
971475AH1-234 GEN
Solar/Wind Harmer
2.251
270526AF1-158 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
4.147
964401AG1-302 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
24.426
270180AB1-006 GEN1
Solar/Wind Harmer
20.507
24791305MDL-5G
Solar/Wind Harmer
7.216
276764AC1-053 GEN2
Solar/Wind Harmer
10.839
24386205FR-12G C
Solar/Wind Harmer
6.733
276911AD2-131_GEN
Solar/Wind Harmer
0.385
971347AH1-153 GEN
Solar/Wind Harmer
1.782
972231SS25-0005
Solar/Wind Harmer
1.7
970921AG2-575 GEN
Solar/Wind Harmer
1.047
970921AG2-575 GEN
Solar/Wind Harmer
4.187
274862TOP CROP ;2U
Solar/Wind Harmer
17.071
274855GSG-6 ;RU
Solar/Wind Harmer
13.081
971411AH1-196 GEN
Solar/Wind Harmer
1.544
274879MINONK ;1U
Solar/Wind Harmer
24.098
961051AF2-396 GEN
Solar/Wind Harmer
1.802
961051AF2-396 GEN
Solar/Wind Harmer
14.419
276763AC1-053 GEN1
Solar/Wind Harmer
10.839
24386405FR-21G C
Solar/Wind Harmer
6.45
274772LINCOLN ;3U
50/50
17.743
274774LINCOLN ;5U
50/50
17.743
274660LASCO STA;1U
50/50
14.291
274888KELLY CRK;1U
Solar/Wind Harmer
21.983
970941AG2-585 GEN
Solar/Wind Harmer
1.354
274850MENDOTA H;RU
Solar/Wind Harmer
9.265
276861AD2-134 GEN
Solar/Wind Harmer
6.323
276805AD2-038 GEN
Solar/Wind Harmer
18.633
274864CRW2-WTG
Solar/Wind Harmer
19.177
274858EASY ROAD;U2
Solar/Wind Harmer
15.572
970569AG2-363 GEN
Solar/Wind Harmer
2.979
276157O29GEN1
Solar/Wind Harmer
14.241
957751AF2-069 GEN
Solar/Wind Harmer
1.266
971771AH1-392 GEN
Solar/Wind Harmer
0.857
939741AE1-205 GEN
Solar/Wind Harmer
1.879
270505AE1-170 C O1
Solar/Wind Harmer
1.392
971605AH1-302 GEN
Solar/Wind Harmer
13.868
276668AB2-070 GEN1
Solar/Wind Harmer
6.355
970243AG2-164 GEN
Solar/Wind Harmer
1.9
970321AG2-212 GEN
Solar/Wind Harmer
2.77
276602WESTBROOK C
Solar/Wind Harmer
7.213
276645AC1-214 GEN1
Solar/Wind Harmer
4.147
942111AE2-223 GEN
Solar/Wind Harmer
21.983
24387305FR-4G C
Solar/Wind Harmer
9.674
24386605FR-22G C
Solar/Wind Harmer
6.45
24387005FR-3G C
Solar/Wind Harmer
6.385
970333AG2-219 GEN
Solar/Wind Harmer
2.322
972207SS24-0001
Solar/Wind Harmer
3.457
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.124
971067AG2-660 GEN
Solar/Wind Harmer
4.083
276872AE1-163_GEN1
Solar/Wind Harmer
22.567
276741O09 GEN1
Solar/Wind Harmer
11.987
274770LINCOLN ;1U
50/50
17.743
274771LINCOLN ;2U
50/50
17.743
276897AD1-100 C
Solar/Wind Harmer
111.579
971177AH1-047 GEN
Solar/Wind Harmer
0.606
971769AH1-391 GEN
Solar/Wind Harmer
1.013
971681AH1-341 GEN
Solar/Wind Harmer
1.498
938861AE1-114 GEN
Solar/Wind Harmer
23.354
970571AG2-364 GEN
Solar/Wind Harmer
1.986
276603SUBLETTE C
Solar/Wind Harmer
3.386
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.567
945111AF1-176 GEN
Solar/Wind Harmer
8.54
972175AH1-670 GEN
Solar/Wind Harmer
34.173
276174W4-005 GEN2
Solar/Wind Harmer
8.359
276621W2-048 GEN
Solar/Wind Harmer
17.721
970707AG2-453 GEN
Solar/Wind Harmer
3.125
274887GEN-1.85
Solar/Wind Harmer
20.194
970833AG2-524 GEN
Solar/Wind Harmer
9.508
958481AF2-142 GEN
Solar/Wind Harmer
1.565
971675AH1-338 GEN
Solar/Wind Harmer
1.855
276868AE1-113 GEN
Solar/Wind Harmer
34.455
274853TWINGROVE;U1
Solar/Wind Harmer
22.608
970781AG2-491 GEN
Solar/Wind Harmer
0.872
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.617
965911AG1-460 GEN
Solar/Wind Harmer
1.874
970699AG2-449 GEN
Solar/Wind Harmer
0.844
274775LINCOLN ;6U
50/50
17.743
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.083
276694AA1-018 GEN2
Solar/Wind Harmer
20.135
939401AE1-172 GEN
Solar/Wind Harmer
41.242
276876AE1-163_GEN2
Solar/Wind Harmer
22.567
274857EASY ROAD;U1
Solar/Wind Harmer
15.572
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.142
941731AE2-173 GEN
Solar/Wind Harmer
9.395
970519AG2-331 GEN
Solar/Wind Harmer
21.953
972181SS23-001
Solar/Wind Harmer
1.063
959091AF2-200 GEN
Solar/Wind Harmer
2.042
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
6.331
274877BISHOP HL;1U
Solar/Wind Harmer
11.138
24755605MDL-5G
Solar/Wind Harmer
7.216
276916AD2-100_GEN
Solar/Wind Harmer
1.619
943591AF1-030 GEN
Solar/Wind Harmer
1.081
965681AG1-436 GEN
Solar/Wind Harmer
1.34
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.042
970169AG2-114 GEN
Solar/Wind Harmer
0.992
961011AF2-392 GEN
Solar/Wind Harmer
30.53
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
8.359
276806AD2-047 C O1
Solar/Wind Harmer
33.354
274847GR RIDGE ;BU
Solar/Wind Harmer
19.263
971341AH1-150 GEN
Solar/Wind Harmer
2.042
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.357
971917AH1-482 GEN
Solar/Wind Harmer
14.894
276655WTG1_EQ
Solar/Wind Harmer
16.177
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
22.949
276686W4-005 GEN3
Solar/Wind Harmer
8.359
963841AG1-237 GEN
Solar/Wind Harmer
24.696
943121AE2-341 GEN
Solar/Wind Harmer
1.622
274871GR RIDGE ;2U
Solar/Wind Harmer
25.172
957471AF2-041 GEN
Solar/Wind Harmer
3.063
274848CAMPGROVE;RU
Solar/Wind Harmer
17.376
959341AF2-225 GEN
Solar/Wind Harmer
1.409
270449AD2-020 GEN
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
6.355
274661LASCO STA;2U
50/50
14.329
958011AF2-095 GEN
Solar/Wind Harmer
1.559
971573AH1-285 GEN
Solar/Wind Harmer
0.923
942991AE2-321 GEN
Solar/Wind Harmer
1.035
971333AH1-146 GEN
Solar/Wind Harmer
2.057
958491AF2-143 GEN
Solar/Wind Harmer
1.543
970819AG2-516 GEN
Solar/Wind Harmer
1.21
274851PROVIDENC;RU
Solar/Wind Harmer
9.161
274878BISHOP HL;2U
Solar/Wind Harmer
11.138
965931AG1-462 GEN
Solar/Wind Harmer
2.385
965091AG1-374 GEN
Solar/Wind Harmer
2.75
943021AE2-325 GEN
Solar/Wind Harmer
5.731
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
7.216
957141AF2-008_MTX
Adder
60.972
944201AF1-088_MTX
Adder
121.944
LAGNLTFEXP_LAGN->PJM
CLTF
10.841
TVALTFEXP_TVA->PJM
CLTF
3.804
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.217
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
70.836
NYPJM->LTFIMP_NY
CLTF
2.833
LGEELTFEXP_LGEE->PJM
CLTF
3.145
WECLTFEXP_WEC->PJM
CLTF
6.639
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.089
AG2-052LTFEXP_AG2-052->PJM
LTF
0.372
AH1-155LTFEXP_AH1-155->PJM
LTF
0.557
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.505
CBM West 1LTFEXP_CBM-W1->PJM
CBM
185.896
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.805
MECLTFEXP_MEC->PJM
CLTF
23.06
SIGELTFEXP_SIGE->PJM
CLTF
0.342

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.42 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5257.21
MW Contribution:1.3
Bus #Bus NameTypeMW Contribution
274773LINCOLN ;4U
50/50
19.255
972259AH1-714 GEN
50/50
40.292
970239AG2-162 GEN
Solar/Wind Harmer
1.49
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.401
276863AD2-134 GEN
Solar/Wind Harmer
6.814
971997AH1-543 GEN
Solar/Wind Harmer
1.743
274863CRW1-WTG
Solar/Wind Harmer
20.578
276889AE2-281 GEN
Solar/Wind Harmer
6.938
274856ECOGROVE ;U1
Solar/Wind Harmer
12.687
276158O29GEN2
Solar/Wind Harmer
15.263
276708O09 GEN2
Solar/Wind Harmer
12.847
970513AG2-328 GEN
Solar/Wind Harmer
3.135
970517AG2-330 GEN
Solar/Wind Harmer
48.901
970833AG2-524 GEN
Solar/Wind Harmer
1.286
962781AG1-127 GEN
Solar/Wind Harmer
1.074
971335AH1-147 GEN
Solar/Wind Harmer
2.217
971171AH1-044 GEN
Solar/Wind Harmer
2.199
926823AC1-168 GEN
Solar/Wind Harmer
13.121
959141AF2-205 GEN
Solar/Wind Harmer
0
276782AC1-033 GEN
Solar/Wind Harmer
13.453
946321AF1-296 GEN
Solar/Wind Harmer
30.005
24344105CKG2
50/50
20.836
270101X2-052 CT2
50/50
3.036
965791AG1-447 GEN
Solar/Wind Harmer
13.067
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.943
274872LEEDK;1U
Solar/Wind Harmer
32.656
276882AE2-255 GEN
Solar/Wind Harmer
11.717
274854TWINGROVE;U2
Solar/Wind Harmer
23.669
274776LINCOLN ;7U
50/50
19.255
970373AG2-245 GEN
Solar/Wind Harmer
2.378
274861TOP CROP ;1U
Solar/Wind Harmer
22.22
274872LEEDK;1U
Solar/Wind Harmer
0.495
270526AF1-158 GEN
Solar/Wind Harmer
0
959081AF2-199 GEN
Solar/Wind Harmer
1.099
964401AG1-302 GEN
Solar/Wind Harmer
0
971475AH1-234 GEN
Solar/Wind Harmer
2.422
276646AC1-214 GEN2
Solar/Wind Harmer
4.436
276726Z2-087_GEN
Solar/Wind Harmer
25.946
270180AB1-006 GEN1
Solar/Wind Harmer
23.431
24791305MDL-5G
Solar/Wind Harmer
8.245
24386205FR-12G C
Solar/Wind Harmer
7.542
276764AC1-053 GEN2
Solar/Wind Harmer
11.302
963741AG1-226 GEN
Solar/Wind Harmer
2.492
274777LINCOLN ;8U
50/50
19.255
270102X2-052 ST
50/50
3.287
970901AG2-562 GEN
50/50
12.454
970245AG2-165 GEN
Solar/Wind Harmer
3.135
970349AG2-230 GEN
Solar/Wind Harmer
1.965
971347AH1-153 GEN
Solar/Wind Harmer
1.965
972231SS25-0005
Solar/Wind Harmer
1.859
970921AG2-575 GEN
Solar/Wind Harmer
1.13
970921AG2-575 GEN
Solar/Wind Harmer
4.519
274862TOP CROP ;2U
Solar/Wind Harmer
18.457
274855GSG-6 ;RU
Solar/Wind Harmer
14.096
971411AH1-196 GEN
Solar/Wind Harmer
1.664
274879MINONK ;1U
Solar/Wind Harmer
25.976
961051AF2-396 GEN
Solar/Wind Harmer
2.024
961051AF2-396 GEN
Solar/Wind Harmer
16.191
24386405FR-21G C
Solar/Wind Harmer
7.224
276763AC1-053 GEN1
Solar/Wind Harmer
11.302
970321AG2-212 GEN
Solar/Wind Harmer
3.135
970333AG2-219 GEN
Solar/Wind Harmer
4.275
276602WESTBROOK C
Solar/Wind Harmer
7.773
276645AC1-214 GEN1
Solar/Wind Harmer
4.436
942111AE2-223 GEN
Solar/Wind Harmer
23.351
24387305FR-4G C
Solar/Wind Harmer
10.836
24386605FR-22G C
Solar/Wind Harmer
7.224
24387005FR-3G C
Solar/Wind Harmer
7.152
274770LINCOLN ;1U
50/50
19.255
274771LINCOLN ;2U
50/50
19.255
270100X2-052 CT1
50/50
3.036
276897AD1-100 C
Solar/Wind Harmer
120.857
971769AH1-391 GEN
Solar/Wind Harmer
1.127
971177AH1-047 GEN
Solar/Wind Harmer
0.654
964861AG1-349 GEN
Solar/Wind Harmer
0
971681AH1-341 GEN
Solar/Wind Harmer
1.61
938861AE1-114 GEN
Solar/Wind Harmer
25.097
970571AG2-364 GEN
Solar/Wind Harmer
2.133
276603SUBLETTE C
Solar/Wind Harmer
3.635
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.764
945111AF1-176 GEN
Solar/Wind Harmer
9.614
972175AH1-670 GEN
Solar/Wind Harmer
35.909
276174W4-005 GEN2
Solar/Wind Harmer
8.725
276621W2-048 GEN
Solar/Wind Harmer
18.423
274772LINCOLN ;3U
50/50
19.255
274774LINCOLN ;5U
50/50
19.255
274660LASCO STA;1U
50/50
15.494
970243AG2-164 GEN
Solar/Wind Harmer
3.497
274888KELLY CRK;1U
Solar/Wind Harmer
23.873
970941AG2-585 GEN
Solar/Wind Harmer
1.47
274850MENDOTA H;RU
Solar/Wind Harmer
9.983
276861AD2-134 GEN
Solar/Wind Harmer
6.814
276805AD2-038 GEN
Solar/Wind Harmer
20.107
274864CRW2-WTG
Solar/Wind Harmer
20.578
274858EASY ROAD;U2
Solar/Wind Harmer
16.727
970569AG2-363 GEN
Solar/Wind Harmer
3.199
971771AH1-392 GEN
Solar/Wind Harmer
0.959
971605AH1-302 GEN
Solar/Wind Harmer
15.855
276157O29GEN1
Solar/Wind Harmer
15.263
270505AE1-170 C O1
Solar/Wind Harmer
1.559
957751AF2-069 GEN
Solar/Wind Harmer
1.354
939741AE1-205 GEN
Solar/Wind Harmer
1.996
276668AB2-070 GEN1
Solar/Wind Harmer
6.635
970241AG2-163 GEN
Solar/Wind Harmer
1.384
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
12.507
971549AH1-272 GEN
Solar/Wind Harmer
1.657
274880W4-005 GEN4
Solar/Wind Harmer
8.725
971993AH1-541 GEN
Solar/Wind Harmer
0.811
276838X2-022 GEN2
Solar/Wind Harmer
0.693
970699AG2-449 GEN
Solar/Wind Harmer
1.554
970707AG2-453 GEN
Solar/Wind Harmer
3.386
274887GEN-1.85
Solar/Wind Harmer
21.93
970833AG2-524 GEN
Solar/Wind Harmer
10.292
958481AF2-142 GEN
Solar/Wind Harmer
1.692
971675AH1-338 GEN
Solar/Wind Harmer
1.999
276868AE1-113 GEN
Solar/Wind Harmer
37.14
970781AG2-491 GEN
Solar/Wind Harmer
0.996
274853TWINGROVE;U1
Solar/Wind Harmer
23.921
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.839
24697605MDL-3G C
Solar/Wind Harmer
12.487
270181AB1-006 GEN2
Solar/Wind Harmer
1.553
959611AF2-252 GEN
Solar/Wind Harmer
3.879
960611AF2-352 GEN
Solar/Wind Harmer
3.879
24385905FR-11G C
Solar/Wind Harmer
14.202
963831AG1-236 GEN
Solar/Wind Harmer
24.413
274775LINCOLN ;6U
50/50
19.255
970519AG2-331 GEN
Solar/Wind Harmer
40.415
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.176
276694AA1-018 GEN2
Solar/Wind Harmer
21.77
939401AE1-172 GEN
Solar/Wind Harmer
44.375
958381AF2-132 GEN
Solar/Wind Harmer
0
276876AE1-163_GEN2
Solar/Wind Harmer
24.282
274857EASY ROAD;U1
Solar/Wind Harmer
16.727
276656WTG2_EQ
Solar/Wind Harmer
2.275
941731AE2-173 GEN
Solar/Wind Harmer
9.979
972207SS24-0001
Solar/Wind Harmer
3.751
972181SS23-001
Solar/Wind Harmer
1.162
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.199
274849CRESCENT ;1U
Solar/Wind Harmer
6.772
274877BISHOP HL;1U
Solar/Wind Harmer
11.908
24755605MDL-5G
Solar/Wind Harmer
8.245
965681AG1-436 GEN
Solar/Wind Harmer
1.485
943591AF1-030 GEN
Solar/Wind Harmer
1.17
276901AD2-066 C O1
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.199
970169AG2-114 GEN
Solar/Wind Harmer
1.062
961011AF2-392 GEN
Solar/Wind Harmer
32.759
276785W4-005 GEN1
Solar/Wind Harmer
8.725
276806AD2-047 C O1
Solar/Wind Harmer
36.221
274847GR RIDGE ;BU
Solar/Wind Harmer
20.848
971341AH1-150 GEN
Solar/Wind Harmer
2.199
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.637
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.215
971067AG2-660 GEN
Solar/Wind Harmer
4.397
971917AH1-482 GEN
Solar/Wind Harmer
16.916
276872AE1-163_GEN1
Solar/Wind Harmer
24.282
276741O09 GEN1
Solar/Wind Harmer
12.847
276655WTG1_EQ
Solar/Wind Harmer
17.184
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
26.221
276686W4-005 GEN3
Solar/Wind Harmer
8.725
963841AG1-237 GEN
Solar/Wind Harmer
27.26
943121AE2-341 GEN
Solar/Wind Harmer
1.755
274661LASCO STA;2U
50/50
15.534
958011AF2-095 GEN
Solar/Wind Harmer
1.693
971573AH1-285 GEN
Solar/Wind Harmer
0.998
942991AE2-321 GEN
Solar/Wind Harmer
1.116
958491AF2-143 GEN
Solar/Wind Harmer
1.664
971333AH1-146 GEN
Solar/Wind Harmer
2.217
970819AG2-516 GEN
Solar/Wind Harmer
1.302
274851PROVIDENC;RU
Solar/Wind Harmer
9.799
945421AF1-207 GEN
Solar/Wind Harmer
0
274878BISHOP HL;2U
Solar/Wind Harmer
11.908
943021AE2-325 GEN
Solar/Wind Harmer
6.426
965931AG1-462 GEN
Solar/Wind Harmer
2.547
24697905MDL-4G C
Solar/Wind Harmer
8.245
965091AG1-374 GEN
Solar/Wind Harmer
2.909
274871GR RIDGE ;2U
Solar/Wind Harmer
27.244
957471AF2-041 GEN
Solar/Wind Harmer
3.298
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
18.56
959341AF2-225 GEN
Solar/Wind Harmer
1.497
276849AB2-070 GEN2
Solar/Wind Harmer
6.635
957141AF2-008_MTX
Adder
50.735
944201AF1-088_MTX
Adder
101.469
LAGNLTFEXP_LAGN->PJM
CLTF
10.375
TVALTFEXP_TVA->PJM
CLTF
3.376
CBM West 2LTFEXP_CBM-W2->PJM
CBM
96.378
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
82.361
NYPJM->LTFIMP_NY
CLTF
2.839
LGEELTFEXP_LGEE->PJM
CLTF
1.755
WECLTFEXP_WEC->PJM
CLTF
7.148
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.265
AG2-052LTFEXP_AG2-052->PJM
LTF
0.408
AH1-155LTFEXP_AH1-155->PJM
LTF
0.612
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.623
CBM West 1LTFEXP_CBM-W1->PJM
CBM
199.823
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.128
MECLTFEXP_MEC->PJM
CLTF
24.248
SIGELTFEXP_SIGE->PJM
CLTF
0.288

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.4 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5204.92
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
19.112
274776LINCOLN ;7U
50/50
17.782
274872LEEDK;1U
Solar/Wind Harmer
0.46
274861TOP CROP ;1U
Solar/Wind Harmer
20.601
959081AF2-199 GEN
Solar/Wind Harmer
1.023
970373AG2-245 GEN
Solar/Wind Harmer
2.121
971475AH1-234 GEN
Solar/Wind Harmer
2.257
270526AF1-158 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
4.158
964401AG1-302 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
24.491
270180AB1-006 GEN1
Solar/Wind Harmer
20.566
24791305MDL-5G
Solar/Wind Harmer
7.237
276764AC1-053 GEN2
Solar/Wind Harmer
10.872
24386205FR-12G C
Solar/Wind Harmer
6.754
276911AD2-131_GEN
Solar/Wind Harmer
0.387
274777LINCOLN ;8U
50/50
17.782
970245AG2-165 GEN
Solar/Wind Harmer
2.775
970349AG2-230 GEN
Solar/Wind Harmer
1.786
971347AH1-153 GEN
Solar/Wind Harmer
1.786
972231SS25-0005
Solar/Wind Harmer
1.704
970921AG2-575 GEN
Solar/Wind Harmer
1.049
970921AG2-575 GEN
Solar/Wind Harmer
4.197
274862TOP CROP ;2U
Solar/Wind Harmer
17.112
274855GSG-6 ;RU
Solar/Wind Harmer
13.113
971411AH1-196 GEN
Solar/Wind Harmer
1.547
274879MINONK ;1U
Solar/Wind Harmer
24.157
961051AF2-396 GEN
Solar/Wind Harmer
1.807
961051AF2-396 GEN
Solar/Wind Harmer
14.459
276763AC1-053 GEN1
Solar/Wind Harmer
10.872
24386405FR-21G C
Solar/Wind Harmer
6.469
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.793
965791AG1-447 GEN
Solar/Wind Harmer
11.817
274872LEEDK;1U
Solar/Wind Harmer
30.342
276882AE2-255 GEN
Solar/Wind Harmer
10.896
274854TWINGROVE;U2
Solar/Wind Harmer
22.431
970321AG2-212 GEN
Solar/Wind Harmer
2.775
276602WESTBROOK C
Solar/Wind Harmer
7.231
276645AC1-214 GEN1
Solar/Wind Harmer
4.158
942111AE2-223 GEN
Solar/Wind Harmer
22.042
24387305FR-4G C
Solar/Wind Harmer
9.704
24386605FR-22G C
Solar/Wind Harmer
6.469
24387005FR-3G C
Solar/Wind Harmer
6.404
970333AG2-219 GEN
Solar/Wind Harmer
2.329
274770LINCOLN ;1U
50/50
17.782
274771LINCOLN ;2U
50/50
17.782
276897AD1-100 C
Solar/Wind Harmer
111.834
971177AH1-047 GEN
Solar/Wind Harmer
0.608
971769AH1-391 GEN
Solar/Wind Harmer
1.016
971681AH1-341 GEN
Solar/Wind Harmer
1.501
938861AE1-114 GEN
Solar/Wind Harmer
23.412
970571AG2-364 GEN
Solar/Wind Harmer
1.991
276603SUBLETTE C
Solar/Wind Harmer
3.394
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.571
945111AF1-176 GEN
Solar/Wind Harmer
8.564
972175AH1-670 GEN
Solar/Wind Harmer
34.27
276174W4-005 GEN2
Solar/Wind Harmer
8.384
276621W2-048 GEN
Solar/Wind Harmer
17.775
274772LINCOLN ;3U
50/50
17.782
274774LINCOLN ;5U
50/50
17.782
274660LASCO STA;1U
50/50
14.324
274888KELLY CRK;1U
Solar/Wind Harmer
22.034
970941AG2-585 GEN
Solar/Wind Harmer
1.357
274850MENDOTA H;RU
Solar/Wind Harmer
9.287
276861AD2-134 GEN
Solar/Wind Harmer
6.339
276805AD2-038 GEN
Solar/Wind Harmer
18.679
274864CRW2-WTG
Solar/Wind Harmer
19.224
274858EASY ROAD;U2
Solar/Wind Harmer
15.611
970569AG2-363 GEN
Solar/Wind Harmer
2.987
276157O29GEN1
Solar/Wind Harmer
14.278
957751AF2-069 GEN
Solar/Wind Harmer
1.269
971771AH1-392 GEN
Solar/Wind Harmer
0.859
939741AE1-205 GEN
Solar/Wind Harmer
1.884
270505AE1-170 C O1
Solar/Wind Harmer
1.395
971605AH1-302 GEN
Solar/Wind Harmer
13.905
276668AB2-070 GEN1
Solar/Wind Harmer
6.374
970243AG2-164 GEN
Solar/Wind Harmer
1.906
274773LINCOLN ;4U
50/50
17.782
972259AH1-714 GEN
50/50
37.249
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.158
276863AD2-134 GEN
Solar/Wind Harmer
6.339
971997AH1-543 GEN
Solar/Wind Harmer
1.623
274863CRW1-WTG
Solar/Wind Harmer
19.224
276889AE2-281 GEN
Solar/Wind Harmer
6.464
274856ECOGROVE ;U1
Solar/Wind Harmer
11.824
276158O29GEN2
Solar/Wind Harmer
14.278
276708O09 GEN2
Solar/Wind Harmer
12.017
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
10.978
274880W4-005 GEN4
Solar/Wind Harmer
8.384
971993AH1-541 GEN
Solar/Wind Harmer
0.779
276838X2-022 GEN2
Solar/Wind Harmer
0.669
971549AH1-272 GEN
Solar/Wind Harmer
1.473
942481AE2-261 GEN
Solar/Wind Harmer
2.342
970239AG2-162 GEN
Solar/Wind Harmer
0.812
970707AG2-453 GEN
Solar/Wind Harmer
3.132
274887GEN-1.85
Solar/Wind Harmer
20.241
970833AG2-524 GEN
Solar/Wind Harmer
9.53
958481AF2-142 GEN
Solar/Wind Harmer
1.569
971675AH1-338 GEN
Solar/Wind Harmer
1.859
276868AE1-113 GEN
Solar/Wind Harmer
34.539
274853TWINGROVE;U1
Solar/Wind Harmer
22.67
970781AG2-491 GEN
Solar/Wind Harmer
0.874
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.634
965911AG1-460 GEN
Solar/Wind Harmer
1.88
970699AG2-449 GEN
Solar/Wind Harmer
0.847
970513AG2-328 GEN
Solar/Wind Harmer
2.775
970517AG2-330 GEN
Solar/Wind Harmer
43.283
970833AG2-524 GEN
Solar/Wind Harmer
1.191
962781AG1-127 GEN
Solar/Wind Harmer
0.998
971335AH1-147 GEN
Solar/Wind Harmer
2.062
971171AH1-044 GEN
Solar/Wind Harmer
2.047
926823AC1-168 GEN
Solar/Wind Harmer
12.258
276782AC1-033 GEN
Solar/Wind Harmer
12.616
946321AF1-296 GEN
Solar/Wind Harmer
28.153
959141AF2-205 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.676
960611AF2-352 GEN
Solar/Wind Harmer
3.676
24697605MDL-3G C
Solar/Wind Harmer
10.96
270181AB1-006 GEN2
Solar/Wind Harmer
1.363
963831AG1-236 GEN
Solar/Wind Harmer
23.483
24385905FR-11G C
Solar/Wind Harmer
12.718
274775LINCOLN ;6U
50/50
17.782
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.085
276694AA1-018 GEN2
Solar/Wind Harmer
20.183
939401AE1-172 GEN
Solar/Wind Harmer
41.341
276876AE1-163_GEN2
Solar/Wind Harmer
22.622
274857EASY ROAD;U1
Solar/Wind Harmer
15.611
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.148
941731AE2-173 GEN
Solar/Wind Harmer
9.419
970519AG2-331 GEN
Solar/Wind Harmer
22.024
972207SS24-0001
Solar/Wind Harmer
3.464
972181SS23-001
Solar/Wind Harmer
1.065
959091AF2-200 GEN
Solar/Wind Harmer
2.047
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
6.347
274877BISHOP HL;1U
Solar/Wind Harmer
11.167
24755605MDL-5G
Solar/Wind Harmer
7.237
276916AD2-100_GEN
Solar/Wind Harmer
1.624
943591AF1-030 GEN
Solar/Wind Harmer
1.084
965681AG1-436 GEN
Solar/Wind Harmer
1.343
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.047
970169AG2-114 GEN
Solar/Wind Harmer
0.995
961011AF2-392 GEN
Solar/Wind Harmer
30.607
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
8.384
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.126
971067AG2-660 GEN
Solar/Wind Harmer
4.093
276872AE1-163_GEN1
Solar/Wind Harmer
22.622
276741O09 GEN1
Solar/Wind Harmer
12.017
971917AH1-482 GEN
Solar/Wind Harmer
14.933
276655WTG1_EQ
Solar/Wind Harmer
16.22
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
23.015
276686W4-005 GEN3
Solar/Wind Harmer
8.384
963841AG1-237 GEN
Solar/Wind Harmer
24.774
276806AD2-047 C O1
Solar/Wind Harmer
33.431
274847GR RIDGE ;BU
Solar/Wind Harmer
19.307
971341AH1-150 GEN
Solar/Wind Harmer
2.047
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.375
274661LASCO STA;2U
50/50
14.361
958011AF2-095 GEN
Solar/Wind Harmer
1.563
971573AH1-285 GEN
Solar/Wind Harmer
0.925
942991AE2-321 GEN
Solar/Wind Harmer
1.037
971333AH1-146 GEN
Solar/Wind Harmer
2.062
958491AF2-143 GEN
Solar/Wind Harmer
1.546
970819AG2-516 GEN
Solar/Wind Harmer
1.213
274851PROVIDENC;RU
Solar/Wind Harmer
9.184
274878BISHOP HL;2U
Solar/Wind Harmer
11.167
965931AG1-462 GEN
Solar/Wind Harmer
2.392
965091AG1-374 GEN
Solar/Wind Harmer
2.757
943021AE2-325 GEN
Solar/Wind Harmer
5.747
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
7.237
943121AE2-341 GEN
Solar/Wind Harmer
1.626
274871GR RIDGE ;2U
Solar/Wind Harmer
25.23
957471AF2-041 GEN
Solar/Wind Harmer
3.07
274848CAMPGROVE;RU
Solar/Wind Harmer
17.422
959341AF2-225 GEN
Solar/Wind Harmer
1.413
270449AD2-020 GEN
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
6.374
957141AF2-008_MTX
Adder
61.221
944201AF1-088_MTX
Adder
122.442
LAGNLTFEXP_LAGN->PJM
CLTF
10.929
TVALTFEXP_TVA->PJM
CLTF
3.848
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.796
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
70.836
NYPJM->LTFIMP_NY
CLTF
2.805
LGEELTFEXP_LGEE->PJM
CLTF
3.175
WECLTFEXP_WEC->PJM
CLTF
6.655
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.06
AG2-052LTFEXP_AG2-052->PJM
LTF
0.373
AH1-155LTFEXP_AH1-155->PJM
LTF
0.559
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.487
CBM West 1LTFEXP_CBM-W1->PJM
CBM
186.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.969
MECLTFEXP_MEC->PJM
CLTF
23.133
SIGELTFEXP_SIGE->PJM
CLTF
0.344

Details for 05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.4 %
Rating:5133.0 MVA
Rating Type:B
MVA to Mitigate:5204.83
MW Contribution:1.21
Bus #Bus NameTypeMW Contribution
274776LINCOLN ;7U
50/50
17.782
274872LEEDK;1U
Solar/Wind Harmer
0.46
274861TOP CROP ;1U
Solar/Wind Harmer
20.601
959081AF2-199 GEN
Solar/Wind Harmer
1.023
970373AG2-245 GEN
Solar/Wind Harmer
2.121
971475AH1-234 GEN
Solar/Wind Harmer
2.257
270526AF1-158 GEN
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
4.158
964401AG1-302 GEN
Solar/Wind Harmer
0
276726Z2-087_GEN
Solar/Wind Harmer
24.491
270180AB1-006 GEN1
Solar/Wind Harmer
20.566
24791305MDL-5G
Solar/Wind Harmer
7.237
276764AC1-053 GEN2
Solar/Wind Harmer
10.872
274773LINCOLN ;4U
50/50
17.782
972259AH1-714 GEN
50/50
37.249
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.158
276863AD2-134 GEN
Solar/Wind Harmer
6.339
971997AH1-543 GEN
Solar/Wind Harmer
1.623
274863CRW1-WTG
Solar/Wind Harmer
19.224
276889AE2-281 GEN
Solar/Wind Harmer
6.464
274856ECOGROVE ;U1
Solar/Wind Harmer
11.824
276158O29GEN2
Solar/Wind Harmer
14.278
276708O09 GEN2
Solar/Wind Harmer
12.017
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
10.978
274880W4-005 GEN4
Solar/Wind Harmer
8.384
971993AH1-541 GEN
Solar/Wind Harmer
0.779
276838X2-022 GEN2
Solar/Wind Harmer
0.669
971549AH1-272 GEN
Solar/Wind Harmer
1.473
942481AE2-261 GEN
Solar/Wind Harmer
2.342
970321AG2-212 GEN
Solar/Wind Harmer
2.775
276602WESTBROOK C
Solar/Wind Harmer
7.231
276645AC1-214 GEN1
Solar/Wind Harmer
4.158
942111AE2-223 GEN
Solar/Wind Harmer
22.042
24387305FR-4G C
Solar/Wind Harmer
9.704
24386605FR-22G C
Solar/Wind Harmer
6.469
24387005FR-3G C
Solar/Wind Harmer
6.404
970333AG2-219 GEN
Solar/Wind Harmer
2.329
972207SS24-0001
Solar/Wind Harmer
3.464
972181SS23-001
Solar/Wind Harmer
1.065
959091AF2-200 GEN
Solar/Wind Harmer
2.047
270055AF2-134 C O1
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
6.347
274877BISHOP HL;1U
Solar/Wind Harmer
11.167
24755605MDL-5G
Solar/Wind Harmer
7.237
276916AD2-100_GEN
Solar/Wind Harmer
1.624
943121AE2-341 GEN
Solar/Wind Harmer
1.626
274871GR RIDGE ;2U
Solar/Wind Harmer
25.23
957471AF2-041 GEN
Solar/Wind Harmer
3.07
274848CAMPGROVE;RU
Solar/Wind Harmer
17.422
959341AF2-225 GEN
Solar/Wind Harmer
1.413
270449AD2-020 GEN
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
6.374
24386205FR-12G C
Solar/Wind Harmer
6.754
276911AD2-131_GEN
Solar/Wind Harmer
0.387
274777LINCOLN ;8U
50/50
17.782
970245AG2-165 GEN
Solar/Wind Harmer
2.775
970349AG2-230 GEN
Solar/Wind Harmer
1.786
971347AH1-153 GEN
Solar/Wind Harmer
1.786
972231SS25-0005
Solar/Wind Harmer
1.704
970921AG2-575 GEN
Solar/Wind Harmer
1.049
970921AG2-575 GEN
Solar/Wind Harmer
4.197
274862TOP CROP ;2U
Solar/Wind Harmer
17.112
274855GSG-6 ;RU
Solar/Wind Harmer
13.113
971411AH1-196 GEN
Solar/Wind Harmer
1.547
274879MINONK ;1U
Solar/Wind Harmer
24.157
961051AF2-396 GEN
Solar/Wind Harmer
1.807
961051AF2-396 GEN
Solar/Wind Harmer
14.459
276763AC1-053 GEN1
Solar/Wind Harmer
10.872
24386405FR-21G C
Solar/Wind Harmer
6.469
970513AG2-328 GEN
Solar/Wind Harmer
2.775
970517AG2-330 GEN
Solar/Wind Harmer
43.283
970833AG2-524 GEN
Solar/Wind Harmer
1.191
962781AG1-127 GEN
Solar/Wind Harmer
0.998
971335AH1-147 GEN
Solar/Wind Harmer
2.062
971171AH1-044 GEN
Solar/Wind Harmer
2.047
926823AC1-168 GEN
Solar/Wind Harmer
12.258
276782AC1-033 GEN
Solar/Wind Harmer
12.616
946321AF1-296 GEN
Solar/Wind Harmer
28.153
959141AF2-205 GEN
Solar/Wind Harmer
0
959611AF2-252 GEN
Solar/Wind Harmer
3.676
960611AF2-352 GEN
Solar/Wind Harmer
3.676
24697605MDL-3G C
Solar/Wind Harmer
10.96
270181AB1-006 GEN2
Solar/Wind Harmer
1.363
963831AG1-236 GEN
Solar/Wind Harmer
23.483
24385905FR-11G C
Solar/Wind Harmer
12.718
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
1.126
971067AG2-660 GEN
Solar/Wind Harmer
4.093
276872AE1-163_GEN1
Solar/Wind Harmer
22.622
276741O09 GEN1
Solar/Wind Harmer
12.017
971917AH1-482 GEN
Solar/Wind Harmer
14.933
276655WTG1_EQ
Solar/Wind Harmer
16.22
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
23.015
276686W4-005 GEN3
Solar/Wind Harmer
8.384
963841AG1-237 GEN
Solar/Wind Harmer
24.774
274661LASCO STA;2U
50/50
14.361
958011AF2-095 GEN
Solar/Wind Harmer
1.563
971573AH1-285 GEN
Solar/Wind Harmer
0.925
942991AE2-321 GEN
Solar/Wind Harmer
1.037
971333AH1-146 GEN
Solar/Wind Harmer
2.062
958491AF2-143 GEN
Solar/Wind Harmer
1.546
970819AG2-516 GEN
Solar/Wind Harmer
1.213
274851PROVIDENC;RU
Solar/Wind Harmer
9.184
274878BISHOP HL;2U
Solar/Wind Harmer
11.167
965931AG1-462 GEN
Solar/Wind Harmer
2.392
965091AG1-374 GEN
Solar/Wind Harmer
2.757
943021AE2-325 GEN
Solar/Wind Harmer
5.747
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
7.237
274772LINCOLN ;3U
50/50
17.782
274774LINCOLN ;5U
50/50
17.782
274660LASCO STA;1U
50/50
14.324
274888KELLY CRK;1U
Solar/Wind Harmer
22.034
970941AG2-585 GEN
Solar/Wind Harmer
1.357
274850MENDOTA H;RU
Solar/Wind Harmer
9.287
276861AD2-134 GEN
Solar/Wind Harmer
6.339
276805AD2-038 GEN
Solar/Wind Harmer
18.679
274864CRW2-WTG
Solar/Wind Harmer
19.224
274858EASY ROAD;U2
Solar/Wind Harmer
15.611
970569AG2-363 GEN
Solar/Wind Harmer
2.987
276157O29GEN1
Solar/Wind Harmer
14.278
970239AG2-162 GEN
Solar/Wind Harmer
0.812
274775LINCOLN ;6U
50/50
17.782
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.085
276694AA1-018 GEN2
Solar/Wind Harmer
20.183
939401AE1-172 GEN
Solar/Wind Harmer
41.341
276876AE1-163_GEN2
Solar/Wind Harmer
22.622
274857EASY ROAD;U1
Solar/Wind Harmer
15.611
958381AF2-132 GEN
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
2.148
941731AE2-173 GEN
Solar/Wind Harmer
9.419
970519AG2-331 GEN
Solar/Wind Harmer
22.024
970707AG2-453 GEN
Solar/Wind Harmer
3.132
274887GEN-1.85
Solar/Wind Harmer
20.241
970833AG2-524 GEN
Solar/Wind Harmer
9.53
958481AF2-142 GEN
Solar/Wind Harmer
1.569
971675AH1-338 GEN
Solar/Wind Harmer
1.859
276868AE1-113 GEN
Solar/Wind Harmer
34.539
274853TWINGROVE;U1
Solar/Wind Harmer
22.67
970781AG2-491 GEN
Solar/Wind Harmer
0.874
966841AG1-555 GEN
Solar/Wind Harmer
0
276615X2-022 GEN
Solar/Wind Harmer
5.634
965911AG1-460 GEN
Solar/Wind Harmer
1.88
970699AG2-449 GEN
Solar/Wind Harmer
0.847
274770LINCOLN ;1U
50/50
17.782
274771LINCOLN ;2U
50/50
17.782
24344105CKG2
50/50
19.112
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
1.793
965791AG1-447 GEN
Solar/Wind Harmer
11.817
274872LEEDK;1U
Solar/Wind Harmer
30.342
276882AE2-255 GEN
Solar/Wind Harmer
10.896
274854TWINGROVE;U2
Solar/Wind Harmer
22.431
943591AF1-030 GEN
Solar/Wind Harmer
1.084
965681AG1-436 GEN
Solar/Wind Harmer
1.343
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.047
970169AG2-114 GEN
Solar/Wind Harmer
0.995
961011AF2-392 GEN
Solar/Wind Harmer
30.607
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
8.384
276897AD1-100 C
Solar/Wind Harmer
111.834
971177AH1-047 GEN
Solar/Wind Harmer
0.608
971769AH1-391 GEN
Solar/Wind Harmer
1.016
971681AH1-341 GEN
Solar/Wind Harmer
1.501
938861AE1-114 GEN
Solar/Wind Harmer
23.412
970571AG2-364 GEN
Solar/Wind Harmer
1.991
276603SUBLETTE C
Solar/Wind Harmer
3.394
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
1.571
945111AF1-176 GEN
Solar/Wind Harmer
8.564
972175AH1-670 GEN
Solar/Wind Harmer
34.27
276174W4-005 GEN2
Solar/Wind Harmer
8.384
276621W2-048 GEN
Solar/Wind Harmer
17.775
957751AF2-069 GEN
Solar/Wind Harmer
1.269
971771AH1-392 GEN
Solar/Wind Harmer
0.859
939741AE1-205 GEN
Solar/Wind Harmer
1.884
270505AE1-170 C O1
Solar/Wind Harmer
1.395
971605AH1-302 GEN
Solar/Wind Harmer
13.905
276668AB2-070 GEN1
Solar/Wind Harmer
6.374
970243AG2-164 GEN
Solar/Wind Harmer
1.906
276806AD2-047 C O1
Solar/Wind Harmer
33.431
274847GR RIDGE ;BU
Solar/Wind Harmer
19.307
971341AH1-150 GEN
Solar/Wind Harmer
2.047
958391AF2-133 GEN
Solar/Wind Harmer
0
276848AB2-070 GEN3
Solar/Wind Harmer
6.375
957141AF2-008_MTX
Adder
61.221
944201AF1-088_MTX
Adder
122.442
LAGNLTFEXP_LAGN->PJM
CLTF
10.929
TVALTFEXP_TVA->PJM
CLTF
3.848
CBM West 2LTFEXP_CBM-W2->PJM
CBM
99.796
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
70.836
NYPJM->LTFIMP_NY
CLTF
2.805
LGEELTFEXP_LGEE->PJM
CLTF
3.175
WECLTFEXP_WEC->PJM
CLTF
6.655
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.06
AG2-052LTFEXP_AG2-052->PJM
LTF
0.373
AH1-155LTFEXP_AH1-155->PJM
LTF
0.559
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.487
CBM West 1LTFEXP_CBM-W1->PJM
CBM
186.523
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.969
MECLTFEXP_MEC->PJM
CLTF
23.133
SIGELTFEXP_SIGE->PJM
CLTF
0.344

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.15 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3674.0
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
970239AG2-162 GEN
Solar/Wind Harmer
1.98
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
8.379
276893AG1-478 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
9.084
971997AH1-543 GEN
Solar/Wind Harmer
0.74
962691AG1-118 GEN
Solar/Wind Harmer
1.4
276889AE2-281 GEN
Solar/Wind Harmer
2.978
274880W4-005 GEN4
Solar/Wind Harmer
4.61
971993AH1-541 GEN
Solar/Wind Harmer
0.428
276863AD2-134 GEN
Solar/Wind Harmer
2.823
276838X2-022 GEN2
Solar/Wind Harmer
0.372
274856ECOGROVE ;U1
Solar/Wind Harmer
5.289
942481AE2-261 GEN
Solar/Wind Harmer
1.344
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
5.524
958011AF2-095 GEN
Solar/Wind Harmer
0.701
971573AH1-285 GEN
Solar/Wind Harmer
0.407
965091AG1-374 GEN
Solar/Wind Harmer
1.413
958491AF2-143 GEN
Solar/Wind Harmer
0.707
942991AE2-321 GEN
Solar/Wind Harmer
0.462
971333AH1-146 GEN
Solar/Wind Harmer
0.918
943021AE2-325 GEN
Solar/Wind Harmer
2.845
274851PROVIDENC;RU
Solar/Wind Harmer
4.303
970819AG2-516 GEN
Solar/Wind Harmer
0.542
274878BISHOP HL;2U
Solar/Wind Harmer
5.22
339206AE1-143 GEN
Solar/Wind Helper
0.343
241972AD1-140 GEN
Solar/Wind Helper
0.525
253325AC1-069 GEN
Solar/Wind Helper
0.13
270180AB1-006 GEN1
Solar/Wind Harmer
15.697
24791305MDL-5G
Solar/Wind Harmer
5.524
24386205FR-12G C
Solar/Wind Harmer
5.294
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.681
970373AG2-245 GEN
Solar/Wind Harmer
1.203
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
9.366
276726Z2-087_GEN
Solar/Wind Harmer
12.339
274872LEEDK;1U
Solar/Wind Harmer
0.204
276764AC1-053 GEN2
Solar/Wind Harmer
6
959081AF2-199 GEN
Solar/Wind Harmer
0.457
276646AC1-214 GEN2
Solar/Wind Harmer
1.948
971475AH1-234 GEN
Solar/Wind Harmer
1.008
970541AG2-344 GEN
50/50
10.141
970543AG2-345 GEN
50/50
4.648
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.64
970169AG2-114 GEN
Solar/Wind Harmer
0.478
943591AF1-030 GEN
Solar/Wind Harmer
0.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
4.61
971343AH1-151 GEN
Solar/Wind Harmer
0.913
253303V4-073 C
Solar/Wind Helper
0.007
24344205RKG1
50/50
11.535
270102X2-052 ST
50/50
1.41
970901AG2-562 GEN
50/50
5.341
970245AG2-165 GEN
Solar/Wind Harmer
1.378
24386405FR-21G C
Solar/Wind Harmer
5.071
970349AG2-230 GEN
Solar/Wind Harmer
0.752
971347AH1-153 GEN
Solar/Wind Harmer
0.752
972231SS25-0005
Solar/Wind Harmer
0.788
274862TOP CROP ;2U
Solar/Wind Harmer
7.78
274879MINONK ;1U
Solar/Wind Harmer
11.023
970921AG2-575 GEN
Solar/Wind Harmer
0.465
970921AG2-575 GEN
Solar/Wind Harmer
1.861
276763AC1-053 GEN1
Solar/Wind Harmer
6
274855GSG-6 ;RU
Solar/Wind Harmer
5.839
971411AH1-196 GEN
Solar/Wind Harmer
0.689
961051AF2-396 GEN
Solar/Wind Harmer
0.907
961051AF2-396 GEN
Solar/Wind Harmer
7.254
270393AB1-087 CT1
50/50
2.61
270406AB1-088 CT1
50/50
2.61
970519AG2-331 GEN
Solar/Wind Harmer
53.719
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.487
939401AE1-172 GEN
Solar/Wind Harmer
19.205
276694AA1-018 GEN2
Solar/Wind Harmer
9.17
276656WTG2_EQ
Solar/Wind Harmer
1.082
941731AE2-173 GEN
Solar/Wind Harmer
4.746
276876AE1-163_GEN2
Solar/Wind Harmer
10.422
274857EASY ROAD;U1
Solar/Wind Harmer
7.006
252507AC2-088 GEN
Solar/Wind Helper
0.372
253406AD2-031_GEN
Solar/Wind Helper
0.181
276158O29GEN2
Solar/Wind Harmer
6.495
270367AC2-061_GEN
Solar/Wind Helper
0.459
962581AG1-107 GEN
Solar/Wind Helper
0.564
276708O09 GEN2
Solar/Wind Harmer
0.509
270100X2-052 CT1
50/50
1.302
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.492
276897AD1-100 C
Solar/Wind Harmer
50.03
972175AH1-670 GEN
Solar/Wind Harmer
18.216
276174W4-005 GEN2
Solar/Wind Harmer
4.61
971177AH1-047 GEN
Solar/Wind Harmer
0.27
970571AG2-364 GEN
Solar/Wind Harmer
0.923
276621W2-048 GEN
Solar/Wind Harmer
9.894
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.807
945111AF1-176 GEN
Solar/Wind Harmer
4.397
971681AH1-341 GEN
Solar/Wind Harmer
0.674
938861AE1-114 GEN
Solar/Wind Harmer
10.503
276603SUBLETTE C
Solar/Wind Harmer
1.527
942601AE2-276 GEN
50/50
8.301
970243AG2-164 GEN
Solar/Wind Harmer
4.649
971605AH1-302 GEN
Solar/Wind Harmer
9.691
970241AG2-163 GEN
Solar/Wind Harmer
1.49
274888KELLY CRK;1U
Solar/Wind Harmer
9.889
970941AG2-585 GEN
Solar/Wind Harmer
0.609
274864CRW2-WTG
Solar/Wind Harmer
9.084
939741AE1-205 GEN
Solar/Wind Harmer
0.949
971771AH1-392 GEN
Solar/Wind Harmer
0.425
276805AD2-038 GEN
Solar/Wind Harmer
8.535
276668AB2-070 GEN1
Solar/Wind Harmer
3.504
970569AG2-363 GEN
Solar/Wind Harmer
1.384
274850MENDOTA H;RU
Solar/Wind Harmer
4.136
276861AD2-134 GEN
Solar/Wind Harmer
2.823
270505AE1-170 C O1
Solar/Wind Harmer
0.688
957751AF2-069 GEN
Solar/Wind Harmer
0.595
274858EASY ROAD;U2
Solar/Wind Harmer
7.006
276157O29GEN1
Solar/Wind Harmer
6.495
961491AF2-440 GEN
Solar/Wind Helper
0.188
276911AD2-131_GEN
Solar/Wind Harmer
0.224
25183208HLCRTG
Solar/Wind Helper
0.934
970699AG2-449 GEN
Solar/Wind Harmer
2.066
970781AG2-491 GEN
Solar/Wind Harmer
0.667
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
20.182
274887GEN-1.85
Solar/Wind Harmer
9.084
970707AG2-453 GEN
Solar/Wind Harmer
1.36
970833AG2-524 GEN
Solar/Wind Harmer
4.244
958481AF2-142 GEN
Solar/Wind Harmer
0.713
274853TWINGROVE;U1
Solar/Wind Harmer
11.619
276868AE1-113 GEN
Solar/Wind Harmer
15.761
971675AH1-338 GEN
Solar/Wind Harmer
0.828
276615X2-022 GEN
Solar/Wind Harmer
3.136
965911AG1-460 GEN
Solar/Wind Harmer
1.079
339211AE2-254 GEN
Solar/Wind Helper
0.206
24344205RKG1
50/50
11.535
970513AG2-328 GEN
Solar/Wind Harmer
1.378
970517AG2-330 GEN
Solar/Wind Harmer
21.5
24697605MDL-3G C
Solar/Wind Harmer
8.366
270181AB1-006 GEN2
Solar/Wind Harmer
1.041
24385905FR-11G C
Solar/Wind Harmer
9.968
959141AF2-205 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
0.761
970833AG2-524 GEN
Solar/Wind Harmer
0.53
959611AF2-252 GEN
Solar/Wind Harmer
1.884
960611AF2-352 GEN
Solar/Wind Harmer
1.884
962781AG1-127 GEN
Solar/Wind Harmer
0.443
926823AC1-168 GEN
Solar/Wind Harmer
5.686
963831AG1-236 GEN
Solar/Wind Harmer
12.96
971335AH1-147 GEN
Solar/Wind Harmer
0.918
971171AH1-044 GEN
Solar/Wind Harmer
0.913
276782AC1-033 GEN
Solar/Wind Harmer
5.897
339216AC1-074 GEN
Solar/Wind Helper
0.389
253415AE1-040 GEN
Solar/Wind Helper
0.146
944031AF1-071 GEN
Solar/Wind Helper
0.052
970091AG2-072 GEN
50/50
217.845
270394AB1-087 ST1
50/50
2.61
970783AG2-492 GEN
50/50
2.668
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
17.566
963841AG1-237 GEN
Solar/Wind Harmer
19.403
971917AH1-482 GEN
Solar/Wind Harmer
9.665
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.512
276655WTG1_EQ
Solar/Wind Harmer
8.172
276872AE1-163_GEN1
Solar/Wind Harmer
10.422
276686W4-005 GEN3
Solar/Wind Harmer
4.61
971067AG2-660 GEN
Solar/Wind Harmer
1.827
252509AD1-136 GEN
Solar/Wind Helper
0.053
339243AC2-075 GEN1
Solar/Wind Helper
0.097
270186AC1-089 GEN
Solar/Wind Helper
0.595
339231AF1-038_GEN
Solar/Wind Helper
0.182
339250AF1-203 GEN
Solar/Wind Helper
0.055
276741O09 GEN1
Solar/Wind Harmer
0.509
270407AB1-088 ST1
50/50
2.61
970023AG2-014 GEN
50/50
2.668
24344105CKG2
50/50
6.976
270101X2-052 CT2
50/50
1.302
965791AG1-447 GEN
Solar/Wind Harmer
5.629
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.805
274854TWINGROVE;U2
Solar/Wind Harmer
11.497
276882AE2-255 GEN
Solar/Wind Harmer
4.972
274872LEEDK;1U
Solar/Wind Harmer
13.465
944221AF1-090 GEN
Solar/Wind Harmer
13.919
339221AD2-048_GEN
Solar/Wind Helper
0.336
270340AC2-060 GEN
Solar/Wind Helper
0.363
339255AE2-071 GEN
Solar/Wind Helper
0.096
270518AE2-148 GEN
Solar/Wind Helper
1.508
970333AG2-219 GEN
Solar/Wind Harmer
5.682
970321AG2-212 GEN
Solar/Wind Harmer
1.378
24387305FR-4G C
Solar/Wind Harmer
7.606
24386605FR-22G C
Solar/Wind Harmer
5.071
24387005FR-3G C
Solar/Wind Harmer
5.02
942111AE2-223 GEN
Solar/Wind Harmer
11.105
276602WESTBROOK C
Solar/Wind Harmer
3.22
276645AC1-214 GEN1
Solar/Wind Harmer
1.948
252510AF1-249 C
Solar/Wind Helper
0.1
253394AE2-221_GEN
Solar/Wind Helper
0.571
253398AE2-221_GEN2
Solar/Wind Helper
0.571
339236AF1-050_GEN
Solar/Wind Helper
0.187
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
15.004
274847GR RIDGE ;BU
Solar/Wind Harmer
8.595
276848AB2-070 GEN3
Solar/Wind Harmer
3.504
971341AH1-150 GEN
Solar/Wind Harmer
0.913
253316AC1-085 GEN3
Solar/Wind Helper
0.584
253433AC1-085 GEN1
Solar/Wind Helper
0.37
253338AC1-165 GEN
Solar/Wind Helper
0.13
24344305RKG2
50/50
11.164
24344305RKG2
50/50
11.059
24755605MDL-5G
Solar/Wind Harmer
5.524
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.483
972181SS23-001
Solar/Wind Harmer
0.493
959091AF2-200 GEN
Solar/Wind Harmer
0.913
274849CRESCENT ;1U
Solar/Wind Harmer
2.974
274877BISHOP HL;1U
Solar/Wind Harmer
5.22
276916AD2-100_GEN
Solar/Wind Harmer
0.942
943111AE2-339 GEN
Solar/Wind Helper
0.18
339241AF1-083 GEN
Solar/Wind Helper
0.187
253343AC1-166 GEN
Solar/Wind Helper
0.13
962211AG1-066 GEN
Solar/Wind Helper
0.203
970539AG2-343 GEN
50/50
9.296
274871GR RIDGE ;2U
Solar/Wind Harmer
11.232
943121AE2-341 GEN
Solar/Wind Harmer
0.714
959341AF2-225 GEN
Solar/Wind Harmer
0.712
276849AB2-070 GEN2
Solar/Wind Harmer
3.504
957471AF2-041 GEN
Solar/Wind Harmer
1.37
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
8.2
252524AE2-267 GEN
Solar/Wind Helper
0.251
253317AC1-085 GEN4
Solar/Wind Helper
0.584
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253333AC1-068 GEN
Solar/Wind Helper
0.13
957141AF2-008_MTX
50/50
83.006
944201AF1-088_MTX
50/50
166.013
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
990742J1381
External Queue
1.0042113065719604
950031AG9-013
External Queue
6.4584832191467285
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.03
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.766
LAGNLTFEXP_LAGN->PJM
CLTF
1.981
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.191
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675
NYPJM->LTFIMP_NY
CLTF
1.09
WECLTFEXP_WEC->PJM
CLTF
2.966
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.774
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.147
MECLTFEXP_MEC->PJM
CLTF
10.384

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3628.46
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
24791305MDL-5G
Solar/Wind Harmer
5.539
24386205FR-12G C
Solar/Wind Harmer
5.309
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.69
970373AG2-245 GEN
Solar/Wind Harmer
1.207
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
276726Z2-087_GEN
Solar/Wind Harmer
12.389
274872LEEDK;1U
Solar/Wind Harmer
0.205
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
959081AF2-199 GEN
Solar/Wind Harmer
0.459
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
971475AH1-234 GEN
Solar/Wind Harmer
1.012
276911AD2-131_GEN
Solar/Wind Harmer
0.225
25183208HLCRTG
Solar/Wind Helper
0.93
970239AG2-162 GEN
Solar/Wind Harmer
1.982
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
8.403
276893AG1-478 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
9.12
971997AH1-543 GEN
Solar/Wind Harmer
0.743
962691AG1-118 GEN
Solar/Wind Harmer
1.405
276889AE2-281 GEN
Solar/Wind Harmer
2.99
274880W4-005 GEN4
Solar/Wind Harmer
4.629
971993AH1-541 GEN
Solar/Wind Harmer
0.43
276863AD2-134 GEN
Solar/Wind Harmer
2.834
276838X2-022 GEN2
Solar/Wind Harmer
0.374
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
942481AE2-261 GEN
Solar/Wind Harmer
1.35
276158O29GEN2
Solar/Wind Harmer
6.523
270367AC2-061_GEN
Solar/Wind Helper
0.457
962581AG1-107 GEN
Solar/Wind Helper
0.562
276708O09 GEN2
Solar/Wind Harmer
0.511
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970321AG2-212 GEN
Solar/Wind Harmer
1.382
24387305FR-4G C
Solar/Wind Harmer
7.628
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
942111AE2-223 GEN
Solar/Wind Harmer
11.15
276602WESTBROOK C
Solar/Wind Harmer
3.233
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
252510AF1-249 C
Solar/Wind Helper
0.1
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
339236AF1-050_GEN
Solar/Wind Helper
0.186
942601AE2-276 GEN
50/50
8.32
970243AG2-164 GEN
Solar/Wind Harmer
4.654
971605AH1-302 GEN
Solar/Wind Harmer
9.72
970241AG2-163 GEN
Solar/Wind Harmer
1.494
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
970941AG2-585 GEN
Solar/Wind Harmer
0.611
274864CRW2-WTG
Solar/Wind Harmer
9.12
939741AE1-205 GEN
Solar/Wind Harmer
0.953
971771AH1-392 GEN
Solar/Wind Harmer
0.427
276805AD2-038 GEN
Solar/Wind Harmer
8.569
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
970569AG2-363 GEN
Solar/Wind Harmer
1.39
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
24755605MDL-5G
Solar/Wind Harmer
5.539
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.489
972181SS23-001
Solar/Wind Harmer
0.495
959091AF2-200 GEN
Solar/Wind Harmer
0.917
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
276916AD2-100_GEN
Solar/Wind Harmer
0.946
943111AE2-339 GEN
Solar/Wind Helper
0.179
339241AF1-083 GEN
Solar/Wind Helper
0.186
253343AC1-166 GEN
Solar/Wind Helper
0.129
962211AG1-066 GEN
Solar/Wind Helper
0.201
970539AG2-343 GEN
50/50
9.325
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
943121AE2-341 GEN
Solar/Wind Harmer
0.717
959341AF2-225 GEN
Solar/Wind Harmer
0.715
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
957471AF2-041 GEN
Solar/Wind Harmer
1.376
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
252524AE2-267 GEN
Solar/Wind Helper
0.25
253317AC1-085 GEN4
Solar/Wind Helper
0.581
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253333AC1-068 GEN
Solar/Wind Helper
0.129
970091AG2-072 GEN
50/50
218.112
270394AB1-087 ST1
50/50
2.616
970783AG2-492 GEN
50/50
2.676
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
17.617
963841AG1-237 GEN
Solar/Wind Harmer
19.463
971917AH1-482 GEN
Solar/Wind Harmer
9.694
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276655WTG1_EQ
Solar/Wind Harmer
8.205
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276686W4-005 GEN3
Solar/Wind Harmer
4.629
971067AG2-660 GEN
Solar/Wind Harmer
1.835
252509AD1-136 GEN
Solar/Wind Helper
0.053
339243AC2-075 GEN1
Solar/Wind Helper
0.097
270186AC1-089 GEN
Solar/Wind Helper
0.592
339231AF1-038_GEN
Solar/Wind Helper
0.181
339250AF1-203 GEN
Solar/Wind Helper
0.054
276741O09 GEN1
Solar/Wind Harmer
0.511
24344205RKG1
50/50
11.55
270102X2-052 ST
50/50
1.415
970901AG2-562 GEN
50/50
5.361
970245AG2-165 GEN
Solar/Wind Harmer
1.382
24386405FR-21G C
Solar/Wind Harmer
5.085
970349AG2-230 GEN
Solar/Wind Harmer
0.755
971347AH1-153 GEN
Solar/Wind Harmer
0.755
972231SS25-0005
Solar/Wind Harmer
0.792
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274879MINONK ;1U
Solar/Wind Harmer
11.068
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
971411AH1-196 GEN
Solar/Wind Harmer
0.692
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
24344205RKG1
50/50
11.55
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
24697605MDL-3G C
Solar/Wind Harmer
8.389
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
24385905FR-11G C
Solar/Wind Harmer
9.998
959141AF2-205 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970833AG2-524 GEN
Solar/Wind Harmer
0.533
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
962781AG1-127 GEN
Solar/Wind Harmer
0.444
926823AC1-168 GEN
Solar/Wind Harmer
5.709
963831AG1-236 GEN
Solar/Wind Harmer
13.013
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971171AH1-044 GEN
Solar/Wind Harmer
0.917
276782AC1-033 GEN
Solar/Wind Harmer
5.922
339216AC1-074 GEN
Solar/Wind Helper
0.388
253415AE1-040 GEN
Solar/Wind Helper
0.145
944031AF1-071 GEN
Solar/Wind Helper
0.051
270393AB1-087 CT1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
970519AG2-331 GEN
Solar/Wind Harmer
53.778
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
939401AE1-172 GEN
Solar/Wind Harmer
19.281
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
276656WTG2_EQ
Solar/Wind Harmer
1.086
941731AE2-173 GEN
Solar/Wind Harmer
4.765
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
252507AC2-088 GEN
Solar/Wind Helper
0.371
253406AD2-031_GEN
Solar/Wind Helper
0.18
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
970169AG2-114 GEN
Solar/Wind Harmer
0.48
943591AF1-030 GEN
Solar/Wind Harmer
0.478
276901AD2-066 C O1
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
4.629
971343AH1-151 GEN
Solar/Wind Harmer
0.917
253303V4-073 C
Solar/Wind Helper
0.007
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
5.539
958011AF2-095 GEN
Solar/Wind Harmer
0.704
971573AH1-285 GEN
Solar/Wind Harmer
0.409
965091AG1-374 GEN
Solar/Wind Harmer
1.419
958491AF2-143 GEN
Solar/Wind Harmer
0.709
942991AE2-321 GEN
Solar/Wind Harmer
0.464
971333AH1-146 GEN
Solar/Wind Harmer
0.922
943021AE2-325 GEN
Solar/Wind Harmer
2.857
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
970819AG2-516 GEN
Solar/Wind Harmer
0.544
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
339206AE1-143 GEN
Solar/Wind Helper
0.341
241972AD1-140 GEN
Solar/Wind Helper
0.522
253325AC1-069 GEN
Solar/Wind Helper
0.129
276861AD2-134 GEN
Solar/Wind Harmer
2.834
270505AE1-170 C O1
Solar/Wind Harmer
0.691
957751AF2-069 GEN
Solar/Wind Harmer
0.597
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
276157O29GEN1
Solar/Wind Harmer
6.523
961491AF2-440 GEN
Solar/Wind Helper
0.187
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
20.258
274887GEN-1.85
Solar/Wind Harmer
9.12
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970833AG2-524 GEN
Solar/Wind Harmer
4.261
958481AF2-142 GEN
Solar/Wind Harmer
0.716
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
276868AE1-113 GEN
Solar/Wind Harmer
15.825
971675AH1-338 GEN
Solar/Wind Harmer
0.831
276615X2-022 GEN
Solar/Wind Harmer
3.149
965911AG1-460 GEN
Solar/Wind Harmer
1.083
339211AE2-254 GEN
Solar/Wind Helper
0.205
270100X2-052 CT1
50/50
1.307
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.494
276897AD1-100 C
Solar/Wind Harmer
50.226
972175AH1-670 GEN
Solar/Wind Harmer
18.29
276174W4-005 GEN2
Solar/Wind Harmer
4.629
971177AH1-047 GEN
Solar/Wind Harmer
0.272
970571AG2-364 GEN
Solar/Wind Harmer
0.926
276621W2-048 GEN
Solar/Wind Harmer
9.936
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
971681AH1-341 GEN
Solar/Wind Harmer
0.677
938861AE1-114 GEN
Solar/Wind Harmer
10.548
276603SUBLETTE C
Solar/Wind Harmer
1.533
270407AB1-088 ST1
50/50
2.616
970023AG2-014 GEN
50/50
2.676
24344105CKG2
50/50
7.002
270101X2-052 CT2
50/50
1.307
965791AG1-447 GEN
Solar/Wind Harmer
5.65
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.808
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
276882AE2-255 GEN
Solar/Wind Harmer
4.992
274872LEEDK;1U
Solar/Wind Harmer
13.52
944221AF1-090 GEN
Solar/Wind Harmer
13.979
339221AD2-048_GEN
Solar/Wind Helper
0.335
270340AC2-060 GEN
Solar/Wind Helper
0.361
339255AE2-071 GEN
Solar/Wind Helper
0.095
270518AE2-148 GEN
Solar/Wind Helper
1.497
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
15.063
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
971341AH1-150 GEN
Solar/Wind Harmer
0.917
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253338AC1-165 GEN
Solar/Wind Helper
0.129
957141AF2-008_MTX
50/50
83.197
944201AF1-088_MTX
50/50
166.394
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
990742J1381
External Queue
1.0042113065719604
950031AG9-013
External Queue
6.4584832191467285
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
MECLTFEXP_MEC->PJM
CLTF
10.439

Details for 05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05JEFRSO-05JEFRSO 765.0/345.0 kV Ckt 2 transformer
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.76 %
Rating:3276.0 MVA
Rating Type:B
MVA to Mitigate:3628.46
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
5.539
958011AF2-095 GEN
Solar/Wind Harmer
0.704
971573AH1-285 GEN
Solar/Wind Harmer
0.409
965091AG1-374 GEN
Solar/Wind Harmer
1.419
958491AF2-143 GEN
Solar/Wind Harmer
0.709
942991AE2-321 GEN
Solar/Wind Harmer
0.464
971333AH1-146 GEN
Solar/Wind Harmer
0.922
943021AE2-325 GEN
Solar/Wind Harmer
2.857
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
970819AG2-516 GEN
Solar/Wind Harmer
0.544
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
339206AE1-143 GEN
Solar/Wind Helper
0.341
241972AD1-140 GEN
Solar/Wind Helper
0.522
253325AC1-069 GEN
Solar/Wind Helper
0.129
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
970169AG2-114 GEN
Solar/Wind Harmer
0.48
943591AF1-030 GEN
Solar/Wind Harmer
0.478
276901AD2-066 C O1
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
4.629
971343AH1-151 GEN
Solar/Wind Harmer
0.917
253303V4-073 C
Solar/Wind Helper
0.007
24344205RKG1
50/50
11.55
270102X2-052 ST
50/50
1.415
970901AG2-562 GEN
50/50
5.361
970245AG2-165 GEN
Solar/Wind Harmer
1.382
24386405FR-21G C
Solar/Wind Harmer
5.085
970349AG2-230 GEN
Solar/Wind Harmer
0.755
971347AH1-153 GEN
Solar/Wind Harmer
0.755
972231SS25-0005
Solar/Wind Harmer
0.792
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274879MINONK ;1U
Solar/Wind Harmer
11.068
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
971411AH1-196 GEN
Solar/Wind Harmer
0.692
270393AB1-087 CT1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
970519AG2-331 GEN
Solar/Wind Harmer
53.778
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
939401AE1-172 GEN
Solar/Wind Harmer
19.281
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
276656WTG2_EQ
Solar/Wind Harmer
1.086
941731AE2-173 GEN
Solar/Wind Harmer
4.765
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
252507AC2-088 GEN
Solar/Wind Helper
0.371
253406AD2-031_GEN
Solar/Wind Helper
0.18
970239AG2-162 GEN
Solar/Wind Harmer
1.982
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
8.403
276893AG1-478 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
9.12
971997AH1-543 GEN
Solar/Wind Harmer
0.743
962691AG1-118 GEN
Solar/Wind Harmer
1.405
276889AE2-281 GEN
Solar/Wind Harmer
2.99
274880W4-005 GEN4
Solar/Wind Harmer
4.629
971993AH1-541 GEN
Solar/Wind Harmer
0.43
276863AD2-134 GEN
Solar/Wind Harmer
2.834
276838X2-022 GEN2
Solar/Wind Harmer
0.374
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
942481AE2-261 GEN
Solar/Wind Harmer
1.35
276158O29GEN2
Solar/Wind Harmer
6.523
270367AC2-061_GEN
Solar/Wind Helper
0.457
962581AG1-107 GEN
Solar/Wind Helper
0.562
276708O09 GEN2
Solar/Wind Harmer
0.511
270100X2-052 CT1
50/50
1.307
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.494
276897AD1-100 C
Solar/Wind Harmer
50.226
972175AH1-670 GEN
Solar/Wind Harmer
18.29
276174W4-005 GEN2
Solar/Wind Harmer
4.629
971177AH1-047 GEN
Solar/Wind Harmer
0.272
970571AG2-364 GEN
Solar/Wind Harmer
0.926
276621W2-048 GEN
Solar/Wind Harmer
9.936
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
971681AH1-341 GEN
Solar/Wind Harmer
0.677
938861AE1-114 GEN
Solar/Wind Harmer
10.548
276603SUBLETTE C
Solar/Wind Harmer
1.533
942601AE2-276 GEN
50/50
8.32
970243AG2-164 GEN
Solar/Wind Harmer
4.654
971605AH1-302 GEN
Solar/Wind Harmer
9.72
970241AG2-163 GEN
Solar/Wind Harmer
1.494
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
970941AG2-585 GEN
Solar/Wind Harmer
0.611
274864CRW2-WTG
Solar/Wind Harmer
9.12
939741AE1-205 GEN
Solar/Wind Harmer
0.953
971771AH1-392 GEN
Solar/Wind Harmer
0.427
276805AD2-038 GEN
Solar/Wind Harmer
8.569
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
970569AG2-363 GEN
Solar/Wind Harmer
1.39
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
276861AD2-134 GEN
Solar/Wind Harmer
2.834
270505AE1-170 C O1
Solar/Wind Harmer
0.691
957751AF2-069 GEN
Solar/Wind Harmer
0.597
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
276157O29GEN1
Solar/Wind Harmer
6.523
961491AF2-440 GEN
Solar/Wind Helper
0.187
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
24791305MDL-5G
Solar/Wind Harmer
5.539
24386205FR-12G C
Solar/Wind Harmer
5.309
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.69
970373AG2-245 GEN
Solar/Wind Harmer
1.207
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
276726Z2-087_GEN
Solar/Wind Harmer
12.389
274872LEEDK;1U
Solar/Wind Harmer
0.205
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
959081AF2-199 GEN
Solar/Wind Harmer
0.459
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
971475AH1-234 GEN
Solar/Wind Harmer
1.012
276911AD2-131_GEN
Solar/Wind Harmer
0.225
25183208HLCRTG
Solar/Wind Helper
0.93
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
20.258
274887GEN-1.85
Solar/Wind Harmer
9.12
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970833AG2-524 GEN
Solar/Wind Harmer
4.261
958481AF2-142 GEN
Solar/Wind Harmer
0.716
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
276868AE1-113 GEN
Solar/Wind Harmer
15.825
971675AH1-338 GEN
Solar/Wind Harmer
0.831
276615X2-022 GEN
Solar/Wind Harmer
3.149
965911AG1-460 GEN
Solar/Wind Harmer
1.083
339211AE2-254 GEN
Solar/Wind Helper
0.205
24344205RKG1
50/50
11.55
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
24697605MDL-3G C
Solar/Wind Harmer
8.389
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
24385905FR-11G C
Solar/Wind Harmer
9.998
959141AF2-205 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970833AG2-524 GEN
Solar/Wind Harmer
0.533
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
962781AG1-127 GEN
Solar/Wind Harmer
0.444
926823AC1-168 GEN
Solar/Wind Harmer
5.709
963831AG1-236 GEN
Solar/Wind Harmer
13.013
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971171AH1-044 GEN
Solar/Wind Harmer
0.917
276782AC1-033 GEN
Solar/Wind Harmer
5.922
339216AC1-074 GEN
Solar/Wind Helper
0.388
253415AE1-040 GEN
Solar/Wind Helper
0.145
944031AF1-071 GEN
Solar/Wind Helper
0.051
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
970091AG2-072 GEN
50/50
218.112
270394AB1-087 ST1
50/50
2.616
970783AG2-492 GEN
50/50
2.676
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
17.617
963841AG1-237 GEN
Solar/Wind Harmer
19.463
971917AH1-482 GEN
Solar/Wind Harmer
9.694
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276655WTG1_EQ
Solar/Wind Harmer
8.205
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276686W4-005 GEN3
Solar/Wind Harmer
4.629
270407AB1-088 ST1
50/50
2.616
970023AG2-014 GEN
50/50
2.676
24344105CKG2
50/50
7.002
270101X2-052 CT2
50/50
1.307
965791AG1-447 GEN
Solar/Wind Harmer
5.65
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.808
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
276882AE2-255 GEN
Solar/Wind Harmer
4.992
274872LEEDK;1U
Solar/Wind Harmer
13.52
944221AF1-090 GEN
Solar/Wind Harmer
13.979
339221AD2-048_GEN
Solar/Wind Helper
0.335
270340AC2-060 GEN
Solar/Wind Helper
0.361
339255AE2-071 GEN
Solar/Wind Helper
0.095
270518AE2-148 GEN
Solar/Wind Helper
1.497
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970321AG2-212 GEN
Solar/Wind Harmer
1.382
24387305FR-4G C
Solar/Wind Harmer
7.628
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
942111AE2-223 GEN
Solar/Wind Harmer
11.15
276602WESTBROOK C
Solar/Wind Harmer
3.233
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
252510AF1-249 C
Solar/Wind Helper
0.1
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
339236AF1-050_GEN
Solar/Wind Helper
0.186
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
15.063
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
24755605MDL-5G
Solar/Wind Harmer
5.539
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.489
972181SS23-001
Solar/Wind Harmer
0.495
959091AF2-200 GEN
Solar/Wind Harmer
0.917
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
276916AD2-100_GEN
Solar/Wind Harmer
0.946
943111AE2-339 GEN
Solar/Wind Helper
0.179
339241AF1-083 GEN
Solar/Wind Helper
0.186
253343AC1-166 GEN
Solar/Wind Helper
0.129
962211AG1-066 GEN
Solar/Wind Helper
0.201
971067AG2-660 GEN
Solar/Wind Harmer
1.835
252509AD1-136 GEN
Solar/Wind Helper
0.053
339243AC2-075 GEN1
Solar/Wind Helper
0.097
270186AC1-089 GEN
Solar/Wind Helper
0.592
339231AF1-038_GEN
Solar/Wind Helper
0.181
339250AF1-203 GEN
Solar/Wind Helper
0.054
276741O09 GEN1
Solar/Wind Harmer
0.511
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
971341AH1-150 GEN
Solar/Wind Harmer
0.917
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253338AC1-165 GEN
Solar/Wind Helper
0.129
970539AG2-343 GEN
50/50
9.325
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
943121AE2-341 GEN
Solar/Wind Harmer
0.717
959341AF2-225 GEN
Solar/Wind Harmer
0.715
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
957471AF2-041 GEN
Solar/Wind Harmer
1.376
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
252524AE2-267 GEN
Solar/Wind Helper
0.25
253317AC1-085 GEN4
Solar/Wind Helper
0.581
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253333AC1-068 GEN
Solar/Wind Helper
0.129
957141AF2-008_MTX
50/50
83.197
944201AF1-088_MTX
50/50
166.394
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
990742J1381
External Queue
1.0042113065719604
950031AG9-013
External Queue
6.4584832191467285
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
MECLTFEXP_MEC->PJM
CLTF
10.439

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.71 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3640.25
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
970333AG2-219 GEN
Solar/Wind Harmer
5.682
970321AG2-212 GEN
Solar/Wind Harmer
1.378
24387305FR-4G C
Solar/Wind Harmer
7.606
24386605FR-22G C
Solar/Wind Harmer
5.071
24387005FR-3G C
Solar/Wind Harmer
5.02
942111AE2-223 GEN
Solar/Wind Harmer
11.105
276602WESTBROOK C
Solar/Wind Harmer
3.22
276645AC1-214 GEN1
Solar/Wind Harmer
1.948
252510AF1-249 C
Solar/Wind Helper
0.1
253394AE2-221_GEN
Solar/Wind Helper
0.571
253398AE2-221_GEN2
Solar/Wind Helper
0.571
339236AF1-050_GEN
Solar/Wind Helper
0.187
24344305RKG2
50/50
11.164
24344305RKG2
50/50
11.059
24755605MDL-5G
Solar/Wind Harmer
5.524
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.483
972181SS23-001
Solar/Wind Harmer
0.493
959091AF2-200 GEN
Solar/Wind Harmer
0.913
274849CRESCENT ;1U
Solar/Wind Harmer
2.974
274877BISHOP HL;1U
Solar/Wind Harmer
5.22
276916AD2-100_GEN
Solar/Wind Harmer
0.942
943111AE2-339 GEN
Solar/Wind Helper
0.18
339241AF1-083 GEN
Solar/Wind Helper
0.187
253343AC1-166 GEN
Solar/Wind Helper
0.13
962211AG1-066 GEN
Solar/Wind Helper
0.203
970539AG2-343 GEN
50/50
9.296
274871GR RIDGE ;2U
Solar/Wind Harmer
11.232
943121AE2-341 GEN
Solar/Wind Harmer
0.714
959341AF2-225 GEN
Solar/Wind Harmer
0.712
276849AB2-070 GEN2
Solar/Wind Harmer
3.504
957471AF2-041 GEN
Solar/Wind Harmer
1.37
270180AB1-006 GEN1
Solar/Wind Harmer
15.697
24791305MDL-5G
Solar/Wind Harmer
5.524
24386205FR-12G C
Solar/Wind Harmer
5.294
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.681
970373AG2-245 GEN
Solar/Wind Harmer
1.203
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
9.366
276726Z2-087_GEN
Solar/Wind Harmer
12.339
274872LEEDK;1U
Solar/Wind Harmer
0.204
276764AC1-053 GEN2
Solar/Wind Harmer
6
959081AF2-199 GEN
Solar/Wind Harmer
0.457
276646AC1-214 GEN2
Solar/Wind Harmer
1.948
971475AH1-234 GEN
Solar/Wind Harmer
1.008
276911AD2-131_GEN
Solar/Wind Harmer
0.224
25183208HLCRTG
Solar/Wind Helper
0.934
24344205RKG1
50/50
11.535
270102X2-052 ST
50/50
1.41
970901AG2-562 GEN
50/50
5.341
970245AG2-165 GEN
Solar/Wind Harmer
1.378
24386405FR-21G C
Solar/Wind Harmer
5.071
970349AG2-230 GEN
Solar/Wind Harmer
0.752
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
8.2
252524AE2-267 GEN
Solar/Wind Helper
0.251
253317AC1-085 GEN4
Solar/Wind Helper
0.584
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253333AC1-068 GEN
Solar/Wind Helper
0.13
970091AG2-072 GEN
50/50
217.845
270394AB1-087 ST1
50/50
2.61
970783AG2-492 GEN
50/50
2.668
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
17.566
963841AG1-237 GEN
Solar/Wind Harmer
19.403
971917AH1-482 GEN
Solar/Wind Harmer
9.665
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.512
276655WTG1_EQ
Solar/Wind Harmer
8.172
276872AE1-163_GEN1
Solar/Wind Harmer
10.422
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
5.524
958011AF2-095 GEN
Solar/Wind Harmer
0.701
971573AH1-285 GEN
Solar/Wind Harmer
0.407
965091AG1-374 GEN
Solar/Wind Harmer
1.413
958491AF2-143 GEN
Solar/Wind Harmer
0.707
942991AE2-321 GEN
Solar/Wind Harmer
0.462
971333AH1-146 GEN
Solar/Wind Harmer
0.918
943021AE2-325 GEN
Solar/Wind Harmer
2.845
274851PROVIDENC;RU
Solar/Wind Harmer
4.303
970819AG2-516 GEN
Solar/Wind Harmer
0.542
274878BISHOP HL;2U
Solar/Wind Harmer
5.22
339206AE1-143 GEN
Solar/Wind Helper
0.343
241972AD1-140 GEN
Solar/Wind Helper
0.525
253325AC1-069 GEN
Solar/Wind Helper
0.13
970239AG2-162 GEN
Solar/Wind Harmer
1.98
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
8.379
276893AG1-478 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
9.084
971997AH1-543 GEN
Solar/Wind Harmer
0.74
962691AG1-118 GEN
Solar/Wind Harmer
1.4
276889AE2-281 GEN
Solar/Wind Harmer
2.978
274880W4-005 GEN4
Solar/Wind Harmer
4.61
971993AH1-541 GEN
Solar/Wind Harmer
0.428
276863AD2-134 GEN
Solar/Wind Harmer
2.823
276838X2-022 GEN2
Solar/Wind Harmer
0.372
274856ECOGROVE ;U1
Solar/Wind Harmer
5.289
942481AE2-261 GEN
Solar/Wind Harmer
1.344
276158O29GEN2
Solar/Wind Harmer
6.495
270367AC2-061_GEN
Solar/Wind Helper
0.459
962581AG1-107 GEN
Solar/Wind Helper
0.564
276708O09 GEN2
Solar/Wind Harmer
0.509
270393AB1-087 CT1
50/50
2.61
270406AB1-088 CT1
50/50
2.61
970519AG2-331 GEN
Solar/Wind Harmer
53.719
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.487
939401AE1-172 GEN
Solar/Wind Harmer
19.205
276694AA1-018 GEN2
Solar/Wind Harmer
9.17
276656WTG2_EQ
Solar/Wind Harmer
1.082
941731AE2-173 GEN
Solar/Wind Harmer
4.746
276876AE1-163_GEN2
Solar/Wind Harmer
10.422
274857EASY ROAD;U1
Solar/Wind Harmer
7.006
252507AC2-088 GEN
Solar/Wind Helper
0.372
253406AD2-031_GEN
Solar/Wind Helper
0.181
970699AG2-449 GEN
Solar/Wind Harmer
2.066
970781AG2-491 GEN
Solar/Wind Harmer
0.667
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
20.182
274887GEN-1.85
Solar/Wind Harmer
9.084
970707AG2-453 GEN
Solar/Wind Harmer
1.36
970833AG2-524 GEN
Solar/Wind Harmer
4.244
958481AF2-142 GEN
Solar/Wind Harmer
0.713
274853TWINGROVE;U1
Solar/Wind Harmer
11.619
276868AE1-113 GEN
Solar/Wind Harmer
15.761
971675AH1-338 GEN
Solar/Wind Harmer
0.828
276615X2-022 GEN
Solar/Wind Harmer
3.136
965911AG1-460 GEN
Solar/Wind Harmer
1.079
339211AE2-254 GEN
Solar/Wind Helper
0.206
270407AB1-088 ST1
50/50
2.61
970023AG2-014 GEN
50/50
2.668
24344105CKG2
50/50
6.976
270101X2-052 CT2
50/50
1.302
965791AG1-447 GEN
Solar/Wind Harmer
5.629
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.805
274854TWINGROVE;U2
Solar/Wind Harmer
11.497
276882AE2-255 GEN
Solar/Wind Harmer
4.972
274872LEEDK;1U
Solar/Wind Harmer
13.465
944221AF1-090 GEN
Solar/Wind Harmer
13.919
339221AD2-048_GEN
Solar/Wind Helper
0.336
270340AC2-060 GEN
Solar/Wind Helper
0.363
339255AE2-071 GEN
Solar/Wind Helper
0.096
270518AE2-148 GEN
Solar/Wind Helper
1.508
970541AG2-344 GEN
50/50
10.141
970543AG2-345 GEN
50/50
4.648
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.64
970169AG2-114 GEN
Solar/Wind Harmer
0.478
943591AF1-030 GEN
Solar/Wind Harmer
0.476
276901AD2-066 C O1
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
4.61
971343AH1-151 GEN
Solar/Wind Harmer
0.913
253303V4-073 C
Solar/Wind Helper
0.007
971347AH1-153 GEN
Solar/Wind Harmer
0.752
972231SS25-0005
Solar/Wind Harmer
0.788
274862TOP CROP ;2U
Solar/Wind Harmer
7.78
274879MINONK ;1U
Solar/Wind Harmer
11.023
970921AG2-575 GEN
Solar/Wind Harmer
0.465
970921AG2-575 GEN
Solar/Wind Harmer
1.861
276763AC1-053 GEN1
Solar/Wind Harmer
6
274855GSG-6 ;RU
Solar/Wind Harmer
5.839
971411AH1-196 GEN
Solar/Wind Harmer
0.689
961051AF2-396 GEN
Solar/Wind Harmer
0.907
961051AF2-396 GEN
Solar/Wind Harmer
7.254
270100X2-052 CT1
50/50
1.302
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.492
276897AD1-100 C
Solar/Wind Harmer
50.03
972175AH1-670 GEN
Solar/Wind Harmer
18.216
276174W4-005 GEN2
Solar/Wind Harmer
4.61
971177AH1-047 GEN
Solar/Wind Harmer
0.27
970571AG2-364 GEN
Solar/Wind Harmer
0.923
276621W2-048 GEN
Solar/Wind Harmer
9.894
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.807
945111AF1-176 GEN
Solar/Wind Harmer
4.397
971681AH1-341 GEN
Solar/Wind Harmer
0.674
938861AE1-114 GEN
Solar/Wind Harmer
10.503
276603SUBLETTE C
Solar/Wind Harmer
1.527
942601AE2-276 GEN
50/50
8.301
970243AG2-164 GEN
Solar/Wind Harmer
4.649
971605AH1-302 GEN
Solar/Wind Harmer
9.691
970241AG2-163 GEN
Solar/Wind Harmer
1.49
274888KELLY CRK;1U
Solar/Wind Harmer
9.889
970941AG2-585 GEN
Solar/Wind Harmer
0.609
274864CRW2-WTG
Solar/Wind Harmer
9.084
939741AE1-205 GEN
Solar/Wind Harmer
0.949
971771AH1-392 GEN
Solar/Wind Harmer
0.425
276805AD2-038 GEN
Solar/Wind Harmer
8.535
276668AB2-070 GEN1
Solar/Wind Harmer
3.504
970569AG2-363 GEN
Solar/Wind Harmer
1.384
274850MENDOTA H;RU
Solar/Wind Harmer
4.136
276861AD2-134 GEN
Solar/Wind Harmer
2.823
270505AE1-170 C O1
Solar/Wind Harmer
0.688
957751AF2-069 GEN
Solar/Wind Harmer
0.595
274858EASY ROAD;U2
Solar/Wind Harmer
7.006
276157O29GEN1
Solar/Wind Harmer
6.495
961491AF2-440 GEN
Solar/Wind Helper
0.188
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
15.004
274847GR RIDGE ;BU
Solar/Wind Harmer
8.595
276848AB2-070 GEN3
Solar/Wind Harmer
3.504
971341AH1-150 GEN
Solar/Wind Harmer
0.913
253316AC1-085 GEN3
Solar/Wind Helper
0.584
253433AC1-085 GEN1
Solar/Wind Helper
0.37
253338AC1-165 GEN
Solar/Wind Helper
0.13
276686W4-005 GEN3
Solar/Wind Harmer
4.61
971067AG2-660 GEN
Solar/Wind Harmer
1.827
252509AD1-136 GEN
Solar/Wind Helper
0.053
339243AC2-075 GEN1
Solar/Wind Helper
0.097
270186AC1-089 GEN
Solar/Wind Helper
0.595
339231AF1-038_GEN
Solar/Wind Helper
0.182
339250AF1-203 GEN
Solar/Wind Helper
0.055
276741O09 GEN1
Solar/Wind Harmer
0.509
24344205RKG1
50/50
11.535
970513AG2-328 GEN
Solar/Wind Harmer
1.378
970517AG2-330 GEN
Solar/Wind Harmer
21.5
24697605MDL-3G C
Solar/Wind Harmer
8.366
270181AB1-006 GEN2
Solar/Wind Harmer
1.041
24385905FR-11G C
Solar/Wind Harmer
9.968
959141AF2-205 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
0.761
970833AG2-524 GEN
Solar/Wind Harmer
0.53
959611AF2-252 GEN
Solar/Wind Harmer
1.884
960611AF2-352 GEN
Solar/Wind Harmer
1.884
962781AG1-127 GEN
Solar/Wind Harmer
0.443
926823AC1-168 GEN
Solar/Wind Harmer
5.686
963831AG1-236 GEN
Solar/Wind Harmer
12.96
971335AH1-147 GEN
Solar/Wind Harmer
0.918
971171AH1-044 GEN
Solar/Wind Harmer
0.913
276782AC1-033 GEN
Solar/Wind Harmer
5.897
339216AC1-074 GEN
Solar/Wind Helper
0.389
253415AE1-040 GEN
Solar/Wind Helper
0.146
944031AF1-071 GEN
Solar/Wind Helper
0.052
957141AF2-008_MTX
50/50
83.006
944201AF1-088_MTX
50/50
166.013
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
990742J1381
External Queue
1.0042113065719604
950031AG9-013
External Queue
6.4584832191467285
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.03
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.766
LAGNLTFEXP_LAGN->PJM
CLTF
1.981
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.191
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675
NYPJM->LTFIMP_NY
CLTF
1.09
WECLTFEXP_WEC->PJM
CLTF
2.966
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.274
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.311
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.774
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.147
MECLTFEXP_MEC->PJM
CLTF
10.384

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3589.25
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970321AG2-212 GEN
Solar/Wind Harmer
1.382
24387305FR-4G C
Solar/Wind Harmer
7.628
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
942111AE2-223 GEN
Solar/Wind Harmer
11.15
276602WESTBROOK C
Solar/Wind Harmer
3.233
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
252510AF1-249 C
Solar/Wind Helper
0.1
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
339236AF1-050_GEN
Solar/Wind Helper
0.186
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
24755605MDL-5G
Solar/Wind Harmer
5.539
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.489
972181SS23-001
Solar/Wind Harmer
0.495
959091AF2-200 GEN
Solar/Wind Harmer
0.917
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
276916AD2-100_GEN
Solar/Wind Harmer
0.946
943111AE2-339 GEN
Solar/Wind Helper
0.179
339241AF1-083 GEN
Solar/Wind Helper
0.186
253343AC1-166 GEN
Solar/Wind Helper
0.129
962211AG1-066 GEN
Solar/Wind Helper
0.201
970539AG2-343 GEN
50/50
9.325
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
943121AE2-341 GEN
Solar/Wind Harmer
0.717
959341AF2-225 GEN
Solar/Wind Harmer
0.715
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
957471AF2-041 GEN
Solar/Wind Harmer
1.376
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
252524AE2-267 GEN
Solar/Wind Helper
0.25
253317AC1-085 GEN4
Solar/Wind Helper
0.581
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253333AC1-068 GEN
Solar/Wind Helper
0.129
270393AB1-087 CT1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
970519AG2-331 GEN
Solar/Wind Harmer
53.778
970239AG2-162 GEN
Solar/Wind Harmer
1.982
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
8.403
276893AG1-478 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
9.12
971997AH1-543 GEN
Solar/Wind Harmer
0.743
962691AG1-118 GEN
Solar/Wind Harmer
1.405
276889AE2-281 GEN
Solar/Wind Harmer
2.99
274880W4-005 GEN4
Solar/Wind Harmer
4.629
971993AH1-541 GEN
Solar/Wind Harmer
0.43
276863AD2-134 GEN
Solar/Wind Harmer
2.834
276838X2-022 GEN2
Solar/Wind Harmer
0.374
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
942481AE2-261 GEN
Solar/Wind Harmer
1.35
276158O29GEN2
Solar/Wind Harmer
6.523
270367AC2-061_GEN
Solar/Wind Helper
0.457
962581AG1-107 GEN
Solar/Wind Helper
0.562
276708O09 GEN2
Solar/Wind Harmer
0.511
270407AB1-088 ST1
50/50
2.616
970023AG2-014 GEN
50/50
2.676
24344105CKG2
50/50
7.002
270101X2-052 CT2
50/50
1.307
965791AG1-447 GEN
Solar/Wind Harmer
5.65
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.808
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
276882AE2-255 GEN
Solar/Wind Harmer
4.992
274872LEEDK;1U
Solar/Wind Harmer
13.52
944221AF1-090 GEN
Solar/Wind Harmer
13.979
339221AD2-048_GEN
Solar/Wind Helper
0.335
270340AC2-060 GEN
Solar/Wind Helper
0.361
339255AE2-071 GEN
Solar/Wind Helper
0.095
270518AE2-148 GEN
Solar/Wind Helper
1.497
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
5.539
958011AF2-095 GEN
Solar/Wind Harmer
0.704
971573AH1-285 GEN
Solar/Wind Harmer
0.409
965091AG1-374 GEN
Solar/Wind Harmer
1.419
958491AF2-143 GEN
Solar/Wind Harmer
0.709
942991AE2-321 GEN
Solar/Wind Harmer
0.464
971333AH1-146 GEN
Solar/Wind Harmer
0.922
943021AE2-325 GEN
Solar/Wind Harmer
2.857
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
970819AG2-516 GEN
Solar/Wind Harmer
0.544
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
339206AE1-143 GEN
Solar/Wind Helper
0.341
241972AD1-140 GEN
Solar/Wind Helper
0.522
253325AC1-069 GEN
Solar/Wind Helper
0.129
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
24791305MDL-5G
Solar/Wind Harmer
5.539
24386205FR-12G C
Solar/Wind Harmer
5.309
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.69
970373AG2-245 GEN
Solar/Wind Harmer
1.207
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
276726Z2-087_GEN
Solar/Wind Harmer
12.389
274872LEEDK;1U
Solar/Wind Harmer
0.205
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
959081AF2-199 GEN
Solar/Wind Harmer
0.459
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
971475AH1-234 GEN
Solar/Wind Harmer
1.012
276911AD2-131_GEN
Solar/Wind Harmer
0.225
25183208HLCRTG
Solar/Wind Helper
0.93
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
970169AG2-114 GEN
Solar/Wind Harmer
0.48
943591AF1-030 GEN
Solar/Wind Harmer
0.478
276901AD2-066 C O1
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
4.629
971343AH1-151 GEN
Solar/Wind Harmer
0.917
253303V4-073 C
Solar/Wind Helper
0.007
24344205RKG1
50/50
11.55
270102X2-052 ST
50/50
1.415
970901AG2-562 GEN
50/50
5.361
970245AG2-165 GEN
Solar/Wind Harmer
1.382
24386405FR-21G C
Solar/Wind Harmer
5.085
970349AG2-230 GEN
Solar/Wind Harmer
0.755
971347AH1-153 GEN
Solar/Wind Harmer
0.755
972231SS25-0005
Solar/Wind Harmer
0.792
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274879MINONK ;1U
Solar/Wind Harmer
11.068
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
971411AH1-196 GEN
Solar/Wind Harmer
0.692
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
939401AE1-172 GEN
Solar/Wind Harmer
19.281
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
276656WTG2_EQ
Solar/Wind Harmer
1.086
941731AE2-173 GEN
Solar/Wind Harmer
4.765
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
252507AC2-088 GEN
Solar/Wind Helper
0.371
253406AD2-031_GEN
Solar/Wind Helper
0.18
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
20.258
274887GEN-1.85
Solar/Wind Harmer
9.12
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970833AG2-524 GEN
Solar/Wind Harmer
4.261
958481AF2-142 GEN
Solar/Wind Harmer
0.716
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
276868AE1-113 GEN
Solar/Wind Harmer
15.825
971675AH1-338 GEN
Solar/Wind Harmer
0.831
276615X2-022 GEN
Solar/Wind Harmer
3.149
965911AG1-460 GEN
Solar/Wind Harmer
1.083
339211AE2-254 GEN
Solar/Wind Helper
0.205
270100X2-052 CT1
50/50
1.307
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.494
276897AD1-100 C
Solar/Wind Harmer
50.226
972175AH1-670 GEN
Solar/Wind Harmer
18.29
276174W4-005 GEN2
Solar/Wind Harmer
4.629
971177AH1-047 GEN
Solar/Wind Harmer
0.272
970571AG2-364 GEN
Solar/Wind Harmer
0.926
276621W2-048 GEN
Solar/Wind Harmer
9.936
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
971681AH1-341 GEN
Solar/Wind Harmer
0.677
938861AE1-114 GEN
Solar/Wind Harmer
10.548
276603SUBLETTE C
Solar/Wind Harmer
1.533
942601AE2-276 GEN
50/50
8.32
970243AG2-164 GEN
Solar/Wind Harmer
4.654
971605AH1-302 GEN
Solar/Wind Harmer
9.72
970241AG2-163 GEN
Solar/Wind Harmer
1.494
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
970941AG2-585 GEN
Solar/Wind Harmer
0.611
274864CRW2-WTG
Solar/Wind Harmer
9.12
939741AE1-205 GEN
Solar/Wind Harmer
0.953
971771AH1-392 GEN
Solar/Wind Harmer
0.427
276805AD2-038 GEN
Solar/Wind Harmer
8.569
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
970569AG2-363 GEN
Solar/Wind Harmer
1.39
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
276861AD2-134 GEN
Solar/Wind Harmer
2.834
270505AE1-170 C O1
Solar/Wind Harmer
0.691
957751AF2-069 GEN
Solar/Wind Harmer
0.597
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
276157O29GEN1
Solar/Wind Harmer
6.523
961491AF2-440 GEN
Solar/Wind Helper
0.187
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
15.063
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
971341AH1-150 GEN
Solar/Wind Harmer
0.917
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253338AC1-165 GEN
Solar/Wind Helper
0.129
970091AG2-072 GEN
50/50
218.112
270394AB1-087 ST1
50/50
2.616
970783AG2-492 GEN
50/50
2.676
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
17.617
963841AG1-237 GEN
Solar/Wind Harmer
19.463
971917AH1-482 GEN
Solar/Wind Harmer
9.694
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276655WTG1_EQ
Solar/Wind Harmer
8.205
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276686W4-005 GEN3
Solar/Wind Harmer
4.629
971067AG2-660 GEN
Solar/Wind Harmer
1.835
252509AD1-136 GEN
Solar/Wind Helper
0.053
339243AC2-075 GEN1
Solar/Wind Helper
0.097
270186AC1-089 GEN
Solar/Wind Helper
0.592
339231AF1-038_GEN
Solar/Wind Helper
0.181
339250AF1-203 GEN
Solar/Wind Helper
0.054
276741O09 GEN1
Solar/Wind Harmer
0.511
24344205RKG1
50/50
11.55
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
24697605MDL-3G C
Solar/Wind Harmer
8.389
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
24385905FR-11G C
Solar/Wind Harmer
9.998
959141AF2-205 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970833AG2-524 GEN
Solar/Wind Harmer
0.533
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
962781AG1-127 GEN
Solar/Wind Harmer
0.444
926823AC1-168 GEN
Solar/Wind Harmer
5.709
963831AG1-236 GEN
Solar/Wind Harmer
13.013
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971171AH1-044 GEN
Solar/Wind Harmer
0.917
276782AC1-033 GEN
Solar/Wind Harmer
5.922
339216AC1-074 GEN
Solar/Wind Helper
0.388
253415AE1-040 GEN
Solar/Wind Helper
0.145
944031AF1-071 GEN
Solar/Wind Helper
0.051
957141AF2-008_MTX
50/50
83.197
944201AF1-088_MTX
50/50
166.394
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
990742J1381
External Queue
1.0042113065719604
950031AG9-013
External Queue
6.4584832191467285
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
MECLTFEXP_MEC->PJM
CLTF
10.439

Details for 05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.0 %
Rating:2991.0 MVA
Rating Type:B
MVA to Mitigate:3589.24
MW Contribution:0.54
Bus #Bus NameTypeMW Contribution
270180AB1-006 GEN1
Solar/Wind Harmer
15.742
24791305MDL-5G
Solar/Wind Harmer
5.539
24386205FR-12G C
Solar/Wind Harmer
5.309
964401AG1-302 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
2.69
970373AG2-245 GEN
Solar/Wind Harmer
1.207
270526AF1-158 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
9.404
276726Z2-087_GEN
Solar/Wind Harmer
12.389
274872LEEDK;1U
Solar/Wind Harmer
0.205
276764AC1-053 GEN2
Solar/Wind Harmer
6.025
959081AF2-199 GEN
Solar/Wind Harmer
0.459
276646AC1-214 GEN2
Solar/Wind Harmer
1.956
971475AH1-234 GEN
Solar/Wind Harmer
1.012
276911AD2-131_GEN
Solar/Wind Harmer
0.225
25183208HLCRTG
Solar/Wind Helper
0.93
970239AG2-162 GEN
Solar/Wind Harmer
1.982
957841AF2-078 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
8.403
276893AG1-478 C
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
9.12
971997AH1-543 GEN
Solar/Wind Harmer
0.743
962691AG1-118 GEN
Solar/Wind Harmer
1.405
276889AE2-281 GEN
Solar/Wind Harmer
2.99
274880W4-005 GEN4
Solar/Wind Harmer
4.629
971993AH1-541 GEN
Solar/Wind Harmer
0.43
276863AD2-134 GEN
Solar/Wind Harmer
2.834
276838X2-022 GEN2
Solar/Wind Harmer
0.374
274856ECOGROVE ;U1
Solar/Wind Harmer
5.312
942481AE2-261 GEN
Solar/Wind Harmer
1.35
276158O29GEN2
Solar/Wind Harmer
6.523
270367AC2-061_GEN
Solar/Wind Helper
0.457
962581AG1-107 GEN
Solar/Wind Helper
0.562
276708O09 GEN2
Solar/Wind Harmer
0.511
970333AG2-219 GEN
Solar/Wind Harmer
5.688
970321AG2-212 GEN
Solar/Wind Harmer
1.382
24387305FR-4G C
Solar/Wind Harmer
7.628
24386605FR-22G C
Solar/Wind Harmer
5.085
24387005FR-3G C
Solar/Wind Harmer
5.035
942111AE2-223 GEN
Solar/Wind Harmer
11.15
276602WESTBROOK C
Solar/Wind Harmer
3.233
276645AC1-214 GEN1
Solar/Wind Harmer
1.956
252510AF1-249 C
Solar/Wind Helper
0.1
253394AE2-221_GEN
Solar/Wind Helper
0.568
253398AE2-221_GEN2
Solar/Wind Helper
0.568
339236AF1-050_GEN
Solar/Wind Helper
0.186
942601AE2-276 GEN
50/50
8.32
970243AG2-164 GEN
Solar/Wind Harmer
4.654
971605AH1-302 GEN
Solar/Wind Harmer
9.72
970241AG2-163 GEN
Solar/Wind Harmer
1.494
274888KELLY CRK;1U
Solar/Wind Harmer
9.928
970941AG2-585 GEN
Solar/Wind Harmer
0.611
274864CRW2-WTG
Solar/Wind Harmer
9.12
939741AE1-205 GEN
Solar/Wind Harmer
0.953
971771AH1-392 GEN
Solar/Wind Harmer
0.427
276805AD2-038 GEN
Solar/Wind Harmer
8.569
276668AB2-070 GEN1
Solar/Wind Harmer
3.518
970569AG2-363 GEN
Solar/Wind Harmer
1.39
274850MENDOTA H;RU
Solar/Wind Harmer
4.153
276861AD2-134 GEN
Solar/Wind Harmer
2.834
270505AE1-170 C O1
Solar/Wind Harmer
0.691
957751AF2-069 GEN
Solar/Wind Harmer
0.597
274858EASY ROAD;U2
Solar/Wind Harmer
7.036
276157O29GEN1
Solar/Wind Harmer
6.523
961491AF2-440 GEN
Solar/Wind Helper
0.187
24344305RKG2
50/50
11.178
24344305RKG2
50/50
11.072
24755605MDL-5G
Solar/Wind Harmer
5.539
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.489
972181SS23-001
Solar/Wind Harmer
0.495
959091AF2-200 GEN
Solar/Wind Harmer
0.917
274849CRESCENT ;1U
Solar/Wind Harmer
2.986
274877BISHOP HL;1U
Solar/Wind Harmer
5.242
276916AD2-100_GEN
Solar/Wind Harmer
0.946
943111AE2-339 GEN
Solar/Wind Helper
0.179
339241AF1-083 GEN
Solar/Wind Helper
0.186
253343AC1-166 GEN
Solar/Wind Helper
0.129
962211AG1-066 GEN
Solar/Wind Helper
0.201
970539AG2-343 GEN
50/50
9.325
274871GR RIDGE ;2U
Solar/Wind Harmer
11.277
943121AE2-341 GEN
Solar/Wind Harmer
0.717
959341AF2-225 GEN
Solar/Wind Harmer
0.715
276849AB2-070 GEN2
Solar/Wind Harmer
3.518
957471AF2-041 GEN
Solar/Wind Harmer
1.376
270449AD2-020 GEN
Solar/Wind Harmer
0
274848CAMPGROVE;RU
Solar/Wind Harmer
8.235
252524AE2-267 GEN
Solar/Wind Helper
0.25
253317AC1-085 GEN4
Solar/Wind Helper
0.581
253432AC1-085 GEN2
Solar/Wind Helper
0.019
253333AC1-068 GEN
Solar/Wind Helper
0.129
970091AG2-072 GEN
50/50
218.112
270394AB1-087 ST1
50/50
2.616
970783AG2-492 GEN
50/50
2.676
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
17.617
963841AG1-237 GEN
Solar/Wind Harmer
19.463
971917AH1-482 GEN
Solar/Wind Harmer
9.694
960681AF2-359 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.514
276655WTG1_EQ
Solar/Wind Harmer
8.205
276872AE1-163_GEN1
Solar/Wind Harmer
10.464
276686W4-005 GEN3
Solar/Wind Harmer
4.629
971067AG2-660 GEN
Solar/Wind Harmer
1.835
252509AD1-136 GEN
Solar/Wind Helper
0.053
339243AC2-075 GEN1
Solar/Wind Helper
0.097
270186AC1-089 GEN
Solar/Wind Helper
0.592
339231AF1-038_GEN
Solar/Wind Helper
0.181
339250AF1-203 GEN
Solar/Wind Helper
0.054
276741O09 GEN1
Solar/Wind Harmer
0.511
24344205RKG1
50/50
11.55
270102X2-052 ST
50/50
1.415
970901AG2-562 GEN
50/50
5.361
970245AG2-165 GEN
Solar/Wind Harmer
1.382
24386405FR-21G C
Solar/Wind Harmer
5.085
970349AG2-230 GEN
Solar/Wind Harmer
0.755
971347AH1-153 GEN
Solar/Wind Harmer
0.755
972231SS25-0005
Solar/Wind Harmer
0.792
274862TOP CROP ;2U
Solar/Wind Harmer
7.811
274879MINONK ;1U
Solar/Wind Harmer
11.068
970921AG2-575 GEN
Solar/Wind Harmer
0.467
970921AG2-575 GEN
Solar/Wind Harmer
1.869
276763AC1-053 GEN1
Solar/Wind Harmer
6.025
274855GSG-6 ;RU
Solar/Wind Harmer
5.863
971411AH1-196 GEN
Solar/Wind Harmer
0.692
961051AF2-396 GEN
Solar/Wind Harmer
0.911
961051AF2-396 GEN
Solar/Wind Harmer
7.285
24344205RKG1
50/50
11.55
970513AG2-328 GEN
Solar/Wind Harmer
1.382
970517AG2-330 GEN
Solar/Wind Harmer
21.56
24697605MDL-3G C
Solar/Wind Harmer
8.389
270181AB1-006 GEN2
Solar/Wind Harmer
1.044
24385905FR-11G C
Solar/Wind Harmer
9.998
959141AF2-205 GEN
Solar/Wind Harmer
0
970193AG2-126 GEN
Solar/Wind Harmer
0.764
970833AG2-524 GEN
Solar/Wind Harmer
0.533
959611AF2-252 GEN
Solar/Wind Harmer
1.892
960611AF2-352 GEN
Solar/Wind Harmer
1.892
962781AG1-127 GEN
Solar/Wind Harmer
0.444
926823AC1-168 GEN
Solar/Wind Harmer
5.709
963831AG1-236 GEN
Solar/Wind Harmer
13.013
971335AH1-147 GEN
Solar/Wind Harmer
0.922
971171AH1-044 GEN
Solar/Wind Harmer
0.917
276782AC1-033 GEN
Solar/Wind Harmer
5.922
339216AC1-074 GEN
Solar/Wind Helper
0.388
253415AE1-040 GEN
Solar/Wind Helper
0.145
944031AF1-071 GEN
Solar/Wind Helper
0.051
270393AB1-087 CT1
50/50
2.616
270406AB1-088 CT1
50/50
2.616
970519AG2-331 GEN
Solar/Wind Harmer
53.778
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.489
939401AE1-172 GEN
Solar/Wind Harmer
19.281
276694AA1-018 GEN2
Solar/Wind Harmer
9.207
276656WTG2_EQ
Solar/Wind Harmer
1.086
941731AE2-173 GEN
Solar/Wind Harmer
4.765
276876AE1-163_GEN2
Solar/Wind Harmer
10.464
274857EASY ROAD;U1
Solar/Wind Harmer
7.036
252507AC2-088 GEN
Solar/Wind Helper
0.371
253406AD2-031_GEN
Solar/Wind Helper
0.18
970541AG2-344 GEN
50/50
10.171
970543AG2-345 GEN
50/50
4.663
270445AC2-157 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.642
970169AG2-114 GEN
Solar/Wind Harmer
0.48
943591AF1-030 GEN
Solar/Wind Harmer
0.478
276901AD2-066 C O1
Solar/Wind Harmer
0
276785W4-005 GEN1
Solar/Wind Harmer
4.629
971343AH1-151 GEN
Solar/Wind Harmer
0.917
253303V4-073 C
Solar/Wind Helper
0.007
945421AF1-207 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
5.539
958011AF2-095 GEN
Solar/Wind Harmer
0.704
971573AH1-285 GEN
Solar/Wind Harmer
0.409
965091AG1-374 GEN
Solar/Wind Harmer
1.419
958491AF2-143 GEN
Solar/Wind Harmer
0.709
942991AE2-321 GEN
Solar/Wind Harmer
0.464
971333AH1-146 GEN
Solar/Wind Harmer
0.922
943021AE2-325 GEN
Solar/Wind Harmer
2.857
274851PROVIDENC;RU
Solar/Wind Harmer
4.321
970819AG2-516 GEN
Solar/Wind Harmer
0.544
274878BISHOP HL;2U
Solar/Wind Harmer
5.242
339206AE1-143 GEN
Solar/Wind Helper
0.341
241972AD1-140 GEN
Solar/Wind Helper
0.522
253325AC1-069 GEN
Solar/Wind Helper
0.129
270407AB1-088 ST1
50/50
2.616
970023AG2-014 GEN
50/50
2.676
24344105CKG2
50/50
7.002
270101X2-052 CT2
50/50
1.307
965791AG1-447 GEN
Solar/Wind Harmer
5.65
941551AE2-152 GEN
Solar/Wind Harmer
0
276843GEN-1.7
Solar/Wind Harmer
0.808
274854TWINGROVE;U2
Solar/Wind Harmer
11.544
276882AE2-255 GEN
Solar/Wind Harmer
4.992
274872LEEDK;1U
Solar/Wind Harmer
13.52
944221AF1-090 GEN
Solar/Wind Harmer
13.979
339221AD2-048_GEN
Solar/Wind Helper
0.335
270340AC2-060 GEN
Solar/Wind Helper
0.361
339255AE2-071 GEN
Solar/Wind Helper
0.095
270518AE2-148 GEN
Solar/Wind Helper
1.497
970699AG2-449 GEN
Solar/Wind Harmer
2.068
970781AG2-491 GEN
Solar/Wind Harmer
0.669
966841AG1-555 GEN
Solar/Wind Harmer
0
945391AF1-204 GEN
Solar/Wind Harmer
20.258
274887GEN-1.85
Solar/Wind Harmer
9.12
970707AG2-453 GEN
Solar/Wind Harmer
1.365
970833AG2-524 GEN
Solar/Wind Harmer
4.261
958481AF2-142 GEN
Solar/Wind Harmer
0.716
274853TWINGROVE;U1
Solar/Wind Harmer
11.667
276868AE1-113 GEN
Solar/Wind Harmer
15.825
971675AH1-338 GEN
Solar/Wind Harmer
0.831
276615X2-022 GEN
Solar/Wind Harmer
3.149
965911AG1-460 GEN
Solar/Wind Harmer
1.083
339211AE2-254 GEN
Solar/Wind Helper
0.205
270100X2-052 CT1
50/50
1.307
940581AE2-045 GEN
Solar/Wind Harmer
0
964861AG1-349 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.494
276897AD1-100 C
Solar/Wind Harmer
50.226
972175AH1-670 GEN
Solar/Wind Harmer
18.29
276174W4-005 GEN2
Solar/Wind Harmer
4.629
971177AH1-047 GEN
Solar/Wind Harmer
0.272
970571AG2-364 GEN
Solar/Wind Harmer
0.926
276621W2-048 GEN
Solar/Wind Harmer
9.936
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.81
945111AF1-176 GEN
Solar/Wind Harmer
4.415
971681AH1-341 GEN
Solar/Wind Harmer
0.677
938861AE1-114 GEN
Solar/Wind Harmer
10.548
276603SUBLETTE C
Solar/Wind Harmer
1.533
270444AC2-157 GEN1
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
276806AD2-047 C O1
Solar/Wind Harmer
15.063
274847GR RIDGE ;BU
Solar/Wind Harmer
8.629
276848AB2-070 GEN3
Solar/Wind Harmer
3.519
971341AH1-150 GEN
Solar/Wind Harmer
0.917
253316AC1-085 GEN3
Solar/Wind Helper
0.581
253433AC1-085 GEN1
Solar/Wind Helper
0.368
253338AC1-165 GEN
Solar/Wind Helper
0.129
957141AF2-008_MTX
50/50
83.197
944201AF1-088_MTX
50/50
166.394
991082J1475 G
External Queue
0.3522087037563324
991112J1481
External Queue
1.0042113065719604
990742J1381
External Queue
1.0042113065719604
950031AG9-013
External Queue
6.4584832191467285
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
10.008
BlueGrassPJM->LTFIMP_BlueG
CLTF
28.7
LAGNLTFEXP_LAGN->PJM
CLTF
2.048
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.635
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.675
NYPJM->LTFIMP_NY
CLTF
1.069
WECLTFEXP_WEC->PJM
CLTF
2.979
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.252
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.761
CBM West 1LTFEXP_CBM-W1->PJM
CBM
80.627
MECLTFEXP_MEC->PJM
CLTF
10.439

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#7334_05JEFRSO 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#7334_05JEFRSO 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.0 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5655.61
MW Contribution:1.41
Bus #Bus NameTypeMW Contribution
274776LINCOLN ;7U
50/50
19.802
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.694
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
24.007
274872LEEDK;1U
Solar/Wind Harmer
0.529
270180AB1-006 GEN1
Solar/Wind Harmer
28.214
24791305MDL-5G
Solar/Wind Harmer
9.928
959081AF2-199 GEN
Solar/Wind Harmer
1.183
971475AH1-234 GEN
Solar/Wind Harmer
2.618
24386205FR-12G C
Solar/Wind Harmer
9.441
276646AC1-214 GEN2
Solar/Wind Harmer
4.919
276726Z2-087_GEN
Solar/Wind Harmer
29.618
963741AG1-226 GEN
Solar/Wind Harmer
4.923
276764AC1-053 GEN2
Solar/Wind Harmer
9.884
274773LINCOLN ;4U
50/50
19.802
276893AG1-478 C
Solar/Wind Harmer
-0.001
970239AG2-162 GEN
Solar/Wind Harmer
1.408
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.627
24691005MDL-2G C
Solar/Wind Harmer
15.061
971997AH1-543 GEN
Solar/Wind Harmer
1.886
274863CRW1-WTG
Solar/Wind Harmer
22.565
276863AD2-134 GEN
Solar/Wind Harmer
7.313
276889AE2-281 GEN
Solar/Wind Harmer
7.582
274856ECOGROVE ;U1
Solar/Wind Harmer
13.719
971549AH1-272 GEN
Solar/Wind Harmer
2.146
276158O29GEN2
Solar/Wind Harmer
16.728
276708O09 GEN2
Solar/Wind Harmer
14.08
965021AG1-366 GEN
Solar/Wind Harmer
4.46
274880W4-005 GEN4
Solar/Wind Harmer
10.58
971993AH1-541 GEN
Solar/Wind Harmer
0.983
971599AH1-298 GEN
50/50
20.938
970321AG2-212 GEN
Solar/Wind Harmer
2.856
270071AF1-092 GEN
Solar/Wind Harmer
1.913
970333AG2-219 GEN
Solar/Wind Harmer
4.04
276602WESTBROOK C
Solar/Wind Harmer
8.341
24387305FR-4G C
Solar/Wind Harmer
13.565
24386605FR-22G C
Solar/Wind Harmer
9.043
24387005FR-3G C
Solar/Wind Harmer
8.953
276645AC1-214 GEN1
Solar/Wind Harmer
4.919
942111AE2-223 GEN
Solar/Wind Harmer
26.656
970611AG2-400 GEN
Solar/Wind Harmer
1.115
972207SS24-0001
Solar/Wind Harmer
3.857
972181SS23-001
Solar/Wind Harmer
1.268
270055AF2-134 C O1
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
9.928
959091AF2-200 GEN
Solar/Wind Harmer
2.367
274849CRESCENT ;1U
Solar/Wind Harmer
7.509
274877BISHOP HL;1U
Solar/Wind Harmer
13.215
270349AD2-093_GEN
Solar/Wind Helper
0.709
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
28.905
943121AE2-341 GEN
Solar/Wind Harmer
1.851
957471AF2-041 GEN
Solar/Wind Harmer
3.55
959341AF2-225 GEN
Solar/Wind Harmer
1.709
274848CAMPGROVE;RU
Solar/Wind Harmer
20.674
965651AG1-433 GEN
Solar/Wind Harmer
16.774
276849AB2-070 GEN2
Solar/Wind Harmer
8.046
270144AC1-141 ST1_
50/50
4.757
24642205MAYFLWER
50/50
1.656
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.542
276691AA1-018 GEN1
Solar/Wind Harmer
1.312
946581AF1-322 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3.632
970901AG2-562 GEN
50/50
13.762
274777LINCOLN ;8U
50/50
19.802
970245AG2-165 GEN
Solar/Wind Harmer
2.856
970349AG2-230 GEN
Solar/Wind Harmer
2.086
971347AH1-153 GEN
Solar/Wind Harmer
2.086
961051AF2-396 GEN
Solar/Wind Harmer
2.556
961051AF2-396 GEN
Solar/Wind Harmer
20.451
972231SS25-0005
Solar/Wind Harmer
2.028
274862TOP CROP ;2U
Solar/Wind Harmer
19.941
970921AG2-575 GEN
Solar/Wind Harmer
1.206
970921AG2-575 GEN
Solar/Wind Harmer
4.823
274879MINONK ;1U
Solar/Wind Harmer
28.171
971411AH1-196 GEN
Solar/Wind Harmer
1.787
274855GSG-6 ;RU
Solar/Wind Harmer
15.127
24386405FR-21G C
Solar/Wind Harmer
9.043
960971AF2-388 GEN
Solar/Wind Harmer
33.549
270054AF2-122 C O1
Solar/Wind Helper
0.54
276763AC1-053 GEN1
Solar/Wind Harmer
9.884
970513AG2-328 GEN
Solar/Wind Harmer
2.856
970517AG2-330 GEN
Solar/Wind Harmer
44.557
959141AF2-205 GEN
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.365
962781AG1-127 GEN
Solar/Wind Harmer
1.147
24697605MDL-3G C
Solar/Wind Harmer
15.036
270181AB1-006 GEN2
Solar/Wind Harmer
1.871
971335AH1-147 GEN
Solar/Wind Harmer
2.381
971171AH1-044 GEN
Solar/Wind Harmer
2.367
926823AC1-168 GEN
Solar/Wind Harmer
14.39
24385905FR-11G C
Solar/Wind Harmer
17.778
276782AC1-033 GEN
Solar/Wind Harmer
14.93
959611AF2-252 GEN
Solar/Wind Harmer
4.483
960611AF2-352 GEN
Solar/Wind Harmer
4.483
946321AF1-296 GEN
Solar/Wind Harmer
33.152
24690905MDL-1G C
Solar/Wind Harmer
31.574
276872AE1-163_GEN1
Solar/Wind Harmer
26.538
971067AG2-660 GEN
Solar/Wind Harmer
4.734
276741O09 GEN1
Solar/Wind Harmer
14.08
276655WTG1_EQ
Solar/Wind Harmer
19.616
963841AG1-237 GEN
Solar/Wind Harmer
35.114
276686W4-005 GEN3
Solar/Wind Harmer
10.58
943021AE2-325 GEN
Solar/Wind Harmer
7.995
958011AF2-095 GEN
Solar/Wind Harmer
1.807
971573AH1-285 GEN
Solar/Wind Harmer
1.055
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
1.806
24697905MDL-4G C
Solar/Wind Harmer
9.928
942991AE2-321 GEN
Solar/Wind Harmer
1.197
971333AH1-146 GEN
Solar/Wind Harmer
2.381
970819AG2-516 GEN
Solar/Wind Harmer
1.407
274851PROVIDENC;RU
Solar/Wind Harmer
10.865
274878BISHOP HL;2U
Solar/Wind Harmer
13.215
965091AG1-374 GEN
Solar/Wind Harmer
3.362
965931AG1-462 GEN
Solar/Wind Harmer
2.821
274772LINCOLN ;3U
50/50
19.802
274774LINCOLN ;5U
50/50
19.802
971771AH1-392 GEN
Solar/Wind Harmer
1.176
270505AE1-170 C O1
Solar/Wind Harmer
1.935
270043AE2-236 GEN
Solar/Wind Harmer
0.707
274888KELLY CRK;1U
Solar/Wind Harmer
25.475
970941AG2-585 GEN
Solar/Wind Harmer
1.569
971605AH1-302 GEN
Solar/Wind Harmer
18.534
970243AG2-164 GEN
Solar/Wind Harmer
3.306
276805AD2-038 GEN
Solar/Wind Harmer
21.819
274864CRW2-WTG
Solar/Wind Harmer
22.565
274850MENDOTA H;RU
Solar/Wind Harmer
10.714
276861AD2-134 GEN
Solar/Wind Harmer
7.313
970569AG2-363 GEN
Solar/Wind Harmer
3.514
274858EASY ROAD;U2
Solar/Wind Harmer
18.167
957751AF2-069 GEN
Solar/Wind Harmer
1.501
276157O29GEN1
Solar/Wind Harmer
16.728
939741AE1-205 GEN
Solar/Wind Harmer
2.278
970241AG2-163 GEN
Solar/Wind Harmer
2.735
276668AB2-070 GEN1
Solar/Wind Harmer
8.046
274775LINCOLN ;6U
50/50
19.802
960591AF2-350 GEN
Solar/Wind Harmer
1.255
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
970519AG2-331 GEN
Solar/Wind Harmer
38.197
970031AG2-029 GEN
Solar/Wind Harmer
3.667
276694AA1-018 GEN2
Solar/Wind Harmer
23.507
939401AE1-172 GEN
Solar/Wind Harmer
48.146
276876AE1-163_GEN2
Solar/Wind Harmer
26.538
274857EASY ROAD;U1
Solar/Wind Harmer
18.167
276656WTG2_EQ
Solar/Wind Harmer
2.597
941731AE2-173 GEN
Solar/Wind Harmer
11.391
24344005CKG1
50/50
22.413
24641605TWIN BRNCH
50/50
0.039
24643105BUCHANAN
50/50
0.028
970707AG2-453 GEN
Solar/Wind Harmer
3.529
274887GEN-1.85
Solar/Wind Harmer
23.402
970833AG2-524 GEN
Solar/Wind Harmer
10.921
970699AG2-449 GEN
Solar/Wind Harmer
1.469
958481AF2-142 GEN
Solar/Wind Harmer
1.827
970781AG2-491 GEN
Solar/Wind Harmer
1.199
276868AE1-113 GEN
Solar/Wind Harmer
40.278
971675AH1-338 GEN
Solar/Wind Harmer
2.144
944531AF1-118 GEN
Solar/Wind Harmer
4.133
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
27.647
270100X2-052 CT1
50/50
3.356
274770LINCOLN ;1U
50/50
19.802
274771LINCOLN ;2U
50/50
19.802
971769AH1-391 GEN
Solar/Wind Harmer
1.305
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.286
945111AF1-176 GEN
Solar/Wind Harmer
12.464
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
128.268
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.701
970571AG2-364 GEN
Solar/Wind Harmer
2.343
971681AH1-341 GEN
Solar/Wind Harmer
1.746
938861AE1-114 GEN
Solar/Wind Harmer
27.221
276603SUBLETTE C
Solar/Wind Harmer
3.953
965011AG1-365 GEN
Solar/Wind Harmer
1.115
972175AH1-670 GEN
Solar/Wind Harmer
42.535
276174W4-005 GEN2
Solar/Wind Harmer
10.58
24344105CKG2
50/50
19.281
270101X2-052 CT2
50/50
3.356
965791AG1-447 GEN
Solar/Wind Harmer
14.461
276843GEN-1.7
Solar/Wind Harmer
2.073
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
34.888
276882AE2-255 GEN
Solar/Wind Harmer
12.707
274854TWINGROVE;U2
Solar/Wind Harmer
27.356
959331AF2-224 GEN
Solar/Wind Harmer
1.115
944541AF1-119 GEN
Solar/Wind Harmer
0
270142AC1-141 CT1_
50/50
5.371
270143AC1-141 CT2_
50/50
5.371
24639705ELKHART HY
50/50
0.358
965681AG1-436 GEN
Solar/Wind Harmer
1.643
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.234
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.367
970169AG2-114 GEN
Solar/Wind Harmer
1.177
961011AF2-392 GEN
Solar/Wind Harmer
35.715
276785W4-005 GEN1
Solar/Wind Harmer
10.58
276806AD2-047 C O1
Solar/Wind Harmer
38.651
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
22.119
971341AH1-150 GEN
Solar/Wind Harmer
2.367
276848AB2-070 GEN3
Solar/Wind Harmer
8.048
270471AD2-092_GEN
Solar/Wind Helper
0.709
957141AF2-008_MTX
Adder
97.945
944201AF1-088_MTX
Adder
195.89
LAGNLTFEXP_LAGN->PJM
CLTF
14.593
TVALTFEXP_TVA->PJM
CLTF
5.396
CBM West 2LTFEXP_CBM-W2->PJM
CBM
140.353
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
50.705
NYPJM->LTFIMP_NY
CLTF
3.498
LGEELTFEXP_LGEE->PJM
CLTF
4.156
WECLTFEXP_WEC->PJM
CLTF
7.718
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.329
AG2-052LTFEXP_AG2-052->PJM
LTF
0.481
AH1-155LTFEXP_AH1-155->PJM
LTF
0.721
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.601
CBM West 1LTFEXP_CBM-W1->PJM
CBM
237.091
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.703
MECLTFEXP_MEC->PJM
CLTF
28.039
SIGELTFEXP_SIGE->PJM
CLTF
0.546

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.24 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5171.46
MW Contribution:1.3
Bus #Bus NameTypeMW Contribution
943021AE2-325 GEN
Solar/Wind Harmer
7.445
958011AF2-095 GEN
Solar/Wind Harmer
1.672
971573AH1-285 GEN
Solar/Wind Harmer
0.977
958491AF2-143 GEN
Solar/Wind Harmer
1.67
942991AE2-321 GEN
Solar/Wind Harmer
1.107
971333AH1-146 GEN
Solar/Wind Harmer
2.203
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.302
24697905MDL-4G C
Solar/Wind Harmer
8.873
274851PROVIDENC;RU
Solar/Wind Harmer
10.033
274878BISHOP HL;2U
Solar/Wind Harmer
12.205
270142AC1-141 CT1_
50/50
5.003
270143AC1-141 CT2_
50/50
5.003
24639705ELKHART HY
50/50
0.334
965681AG1-436 GEN
Solar/Wind Harmer
1.52
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.142
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.19
970169AG2-114 GEN
Solar/Wind Harmer
1.084
961011AF2-392 GEN
Solar/Wind Harmer
33.045
276785W4-005 GEN1
Solar/Wind Harmer
9.69
274775LINCOLN ;6U
50/50
18.334
960591AF2-350 GEN
Solar/Wind Harmer
1.161
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.451
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.736
939401AE1-172 GEN
Solar/Wind Harmer
44.44
276876AE1-163_GEN2
Solar/Wind Harmer
24.524
274857EASY ROAD;U1
Solar/Wind Harmer
16.811
276656WTG2_EQ
Solar/Wind Harmer
2.388
941731AE2-173 GEN
Solar/Wind Harmer
10.475
274773LINCOLN ;4U
50/50
18.334
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.356
971997AH1-543 GEN
Solar/Wind Harmer
1.743
276863AD2-134 GEN
Solar/Wind Harmer
6.767
274863CRW1-WTG
Solar/Wind Harmer
20.812
276889AE2-281 GEN
Solar/Wind Harmer
7.007
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.696
971549AH1-272 GEN
Solar/Wind Harmer
2
24691005MDL-2G C
Solar/Wind Harmer
13.46
965021AG1-366 GEN
Solar/Wind Harmer
4.261
276158O29GEN2
Solar/Wind Harmer
15.471
276708O09 GEN2
Solar/Wind Harmer
13.022
958861AF2-177 GEN
Solar/Wind Harmer
32.122
945371AF1-202 GEN
Solar/Wind Harmer
15.376
274880W4-005 GEN4
Solar/Wind Harmer
9.69
971993AH1-541 GEN
Solar/Wind Harmer
0.9
274772LINCOLN ;3U
50/50
18.334
274774LINCOLN ;5U
50/50
18.334
270043AE2-236 GEN
Solar/Wind Harmer
0.672
971771AH1-392 GEN
Solar/Wind Harmer
1.094
270505AE1-170 C O1
Solar/Wind Harmer
1.802
274888KELLY CRK;1U
Solar/Wind Harmer
23.567
970941AG2-585 GEN
Solar/Wind Harmer
1.451
276805AD2-038 GEN
Solar/Wind Harmer
20.171
971605AH1-302 GEN
Solar/Wind Harmer
16.681
274850MENDOTA H;RU
Solar/Wind Harmer
9.914
276861AD2-134 GEN
Solar/Wind Harmer
6.767
274864CRW2-WTG
Solar/Wind Harmer
20.812
970569AG2-363 GEN
Solar/Wind Harmer
3.247
274858EASY ROAD;U2
Solar/Wind Harmer
16.811
276157O29GEN1
Solar/Wind Harmer
15.471
957751AF2-069 GEN
Solar/Wind Harmer
1.386
939741AE1-205 GEN
Solar/Wind Harmer
2.095
970241AG2-163 GEN
Solar/Wind Harmer
2.45
276668AB2-070 GEN1
Solar/Wind Harmer
7.368
274776LINCOLN ;7U
50/50
18.334
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.463
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.199
274872LEEDK;1U
Solar/Wind Harmer
0.49
959081AF2-199 GEN
Solar/Wind Harmer
1.095
971475AH1-234 GEN
Solar/Wind Harmer
2.423
270180AB1-006 GEN1
Solar/Wind Harmer
25.216
24791305MDL-5G
Solar/Wind Harmer
8.873
276646AC1-214 GEN2
Solar/Wind Harmer
4.542
276726Z2-087_GEN
Solar/Wind Harmer
27.235
24386205FR-12G C
Solar/Wind Harmer
8.429
963741AG1-226 GEN
Solar/Wind Harmer
4.409
276764AC1-053 GEN2
Solar/Wind Harmer
5.055
24344005CKG1
50/50
20.846
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.267
274887GEN-1.85
Solar/Wind Harmer
21.649
944531AF1-118 GEN
Solar/Wind Harmer
4.019
970833AG2-524 GEN
Solar/Wind Harmer
10.102
958481AF2-142 GEN
Solar/Wind Harmer
1.69
276868AE1-113 GEN
Solar/Wind Harmer
37.233
971675AH1-338 GEN
Solar/Wind Harmer
1.984
970781AG2-491 GEN
Solar/Wind Harmer
1.072
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.403
970513AG2-328 GEN
Solar/Wind Harmer
2.593
970517AG2-330 GEN
Solar/Wind Harmer
40.453
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.263
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.061
971335AH1-147 GEN
Solar/Wind Harmer
2.203
971171AH1-044 GEN
Solar/Wind Harmer
2.19
926823AC1-168 GEN
Solar/Wind Harmer
13.291
24697605MDL-3G C
Solar/Wind Harmer
13.438
270181AB1-006 GEN2
Solar/Wind Harmer
1.672
276782AC1-033 GEN
Solar/Wind Harmer
13.789
24385905FR-11G C
Solar/Wind Harmer
15.873
946321AF1-296 GEN
Solar/Wind Harmer
30.676
959611AF2-252 GEN
Solar/Wind Harmer
4.119
960611AF2-352 GEN
Solar/Wind Harmer
4.119
945581AF1-223 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3.361
970901AG2-562 GEN
50/50
12.734
274777LINCOLN ;8U
50/50
18.334
970245AG2-165 GEN
Solar/Wind Harmer
2.593
970349AG2-230 GEN
Solar/Wind Harmer
1.941
971347AH1-153 GEN
Solar/Wind Harmer
1.941
961051AF2-396 GEN
Solar/Wind Harmer
2.381
961051AF2-396 GEN
Solar/Wind Harmer
19.048
972231SS25-0005
Solar/Wind Harmer
1.876
274862TOP CROP ;2U
Solar/Wind Harmer
18.439
970921AG2-575 GEN
Solar/Wind Harmer
1.116
970921AG2-575 GEN
Solar/Wind Harmer
4.463
274879MINONK ;1U
Solar/Wind Harmer
26.041
971411AH1-196 GEN
Solar/Wind Harmer
1.654
274855GSG-6 ;RU
Solar/Wind Harmer
13.998
960971AF2-388 GEN
Solar/Wind Harmer
32.84
24386405FR-21G C
Solar/Wind Harmer
8.074
276763AC1-053 GEN1
Solar/Wind Harmer
5.055
24344105CKG2
50/50
17.939
270101X2-052 CT2
50/50
3.105
965791AG1-447 GEN
Solar/Wind Harmer
13.376
276843GEN-1.7
Solar/Wind Harmer
1.918
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.286
276882AE2-255 GEN
Solar/Wind Harmer
11.746
959331AF2-224 GEN
Solar/Wind Harmer
1.065
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.135
971599AH1-298 GEN
50/50
20.056
970321AG2-212 GEN
Solar/Wind Harmer
2.593
270071AF1-092 GEN
Solar/Wind Harmer
1.802
276602WESTBROOK C
Solar/Wind Harmer
7.719
970611AG2-400 GEN
Solar/Wind Harmer
1.065
276645AC1-214 GEN1
Solar/Wind Harmer
4.542
942111AE2-223 GEN
Solar/Wind Harmer
24.512
24387305FR-4G C
Solar/Wind Harmer
12.111
24386605FR-22G C
Solar/Wind Harmer
8.074
24387005FR-3G C
Solar/Wind Harmer
7.993
270100X2-052 CT1
50/50
3.105
274770LINCOLN ;1U
50/50
18.334
274771LINCOLN ;2U
50/50
18.334
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.21
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.13
945111AF1-176 GEN
Solar/Wind Harmer
11.613
276897AD1-100 C
Solar/Wind Harmer
118.617
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.649
970571AG2-364 GEN
Solar/Wind Harmer
2.164
971681AH1-341 GEN
Solar/Wind Harmer
1.615
938861AE1-114 GEN
Solar/Wind Harmer
25.188
276603SUBLETTE C
Solar/Wind Harmer
3.658
965011AG1-365 GEN
Solar/Wind Harmer
1.065
972175AH1-670 GEN
Solar/Wind Harmer
39.016
276174W4-005 GEN2
Solar/Wind Harmer
9.69
972207SS24-0001
Solar/Wind Harmer
3.572
972181SS23-001
Solar/Wind Harmer
1.173
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.19
24755605MDL-5G
Solar/Wind Harmer
8.873
274849CRESCENT ;1U
Solar/Wind Harmer
6.934
274877BISHOP HL;1U
Solar/Wind Harmer
12.205
270349AD2-093_GEN
Solar/Wind Helper
0.7
270144AC1-141 ST1_
50/50
4.431
24642205MAYFLWER
50/50
1.54
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.692
276691AA1-018 GEN1
Solar/Wind Harmer
1.213
971067AG2-660 GEN
Solar/Wind Harmer
4.38
276872AE1-163_GEN1
Solar/Wind Harmer
24.524
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.218
276741O09 GEN1
Solar/Wind Harmer
13.022
276655WTG1_EQ
Solar/Wind Harmer
18.038
965101AG1-375 GEN
Solar/Wind Harmer
1.03
963841AG1-237 GEN
Solar/Wind Harmer
31.4
276686W4-005 GEN3
Solar/Wind Harmer
9.69
970521AG2-332 GEN
50/50
23.771
276806AD2-047 C O1
Solar/Wind Harmer
35.756
274847GR RIDGE ;BU
Solar/Wind Harmer
20.461
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.19
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.37
270471AD2-092_GEN
Solar/Wind Helper
0.7
965091AG1-374 GEN
Solar/Wind Harmer
3.089
965931AG1-462 GEN
Solar/Wind Harmer
2.61
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.738
943121AE2-341 GEN
Solar/Wind Harmer
1.714
957471AF2-041 GEN
Solar/Wind Harmer
3.285
965651AG1-433 GEN
Solar/Wind Harmer
16.42
274848CAMPGROVE;RU
Solar/Wind Harmer
19.088
959341AF2-225 GEN
Solar/Wind Harmer
1.571
276849AB2-070 GEN2
Solar/Wind Harmer
7.368
957141AF2-008_MTX
Adder
82.17
944201AF1-088_MTX
Adder
164.341
LAGNLTFEXP_LAGN->PJM
CLTF
14.106
TVALTFEXP_TVA->PJM
CLTF
5.42
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.208
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769
NYPJM->LTFIMP_NY
CLTF
3.333
LGEELTFEXP_LGEE->PJM
CLTF
5.67
WECLTFEXP_WEC->PJM
CLTF
7.144
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.132
AG2-052LTFEXP_AG2-052->PJM
LTF
0.441
AH1-155LTFEXP_AH1-155->PJM
LTF
0.661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.48
CBM West 1LTFEXP_CBM-W1->PJM
CBM
221.335
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.252
MECLTFEXP_MEC->PJM
CLTF
26.01
SIGELTFEXP_SIGE->PJM
CLTF
0.556

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.14
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
24639705ELKHART HY
50/50
0.335
965681AG1-436 GEN
Solar/Wind Harmer
1.524
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.145
276901AD2-066 C O1
Solar/Wind Harmer
0
274773LINCOLN ;4U
50/50
18.381
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.365
971997AH1-543 GEN
Solar/Wind Harmer
1.748
276863AD2-134 GEN
Solar/Wind Harmer
6.785
274863CRW1-WTG
Solar/Wind Harmer
20.869
276889AE2-281 GEN
Solar/Wind Harmer
7.026
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
971549AH1-272 GEN
Solar/Wind Harmer
2.005
24691005MDL-2G C
Solar/Wind Harmer
13.498
965021AG1-366 GEN
Solar/Wind Harmer
4.273
276158O29GEN2
Solar/Wind Harmer
15.515
276708O09 GEN2
Solar/Wind Harmer
13.059
958861AF2-177 GEN
Solar/Wind Harmer
32.216
945371AF1-202 GEN
Solar/Wind Harmer
15.423
274880W4-005 GEN4
Solar/Wind Harmer
9.72
971993AH1-541 GEN
Solar/Wind Harmer
0.903
274772LINCOLN ;3U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
270043AE2-236 GEN
Solar/Wind Harmer
0.674
971771AH1-392 GEN
Solar/Wind Harmer
1.097
270505AE1-170 C O1
Solar/Wind Harmer
1.807
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
970941AG2-585 GEN
Solar/Wind Harmer
1.455
276805AD2-038 GEN
Solar/Wind Harmer
20.225
971605AH1-302 GEN
Solar/Wind Harmer
16.727
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276861AD2-134 GEN
Solar/Wind Harmer
6.785
274864CRW2-WTG
Solar/Wind Harmer
20.869
970569AG2-363 GEN
Solar/Wind Harmer
3.256
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
971343AH1-151 GEN
Solar/Wind Harmer
2.196
970513AG2-328 GEN
Solar/Wind Harmer
2.599
970517AG2-330 GEN
Solar/Wind Harmer
40.548
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.266
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.064
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971171AH1-044 GEN
Solar/Wind Harmer
2.196
926823AC1-168 GEN
Solar/Wind Harmer
13.329
24697605MDL-3G C
Solar/Wind Harmer
13.476
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276782AC1-033 GEN
Solar/Wind Harmer
13.828
24385905FR-11G C
Solar/Wind Harmer
15.919
946321AF1-296 GEN
Solar/Wind Harmer
30.766
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
945581AF1-223 GEN
Solar/Wind Harmer
0
270102X2-052 ST
50/50
3.369
970901AG2-562 GEN
50/50
12.765
274777LINCOLN ;8U
50/50
18.381
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
1.946
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
972231SS25-0005
Solar/Wind Harmer
1.881
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
274879MINONK ;1U
Solar/Wind Harmer
26.112
971411AH1-196 GEN
Solar/Wind Harmer
1.658
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
960971AF2-388 GEN
Solar/Wind Harmer
32.934
24386405FR-21G C
Solar/Wind Harmer
8.098
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
24344105CKG2
50/50
17.979
270101X2-052 CT2
50/50
3.113
965791AG1-447 GEN
Solar/Wind Harmer
13.41
276843GEN-1.7
Solar/Wind Harmer
1.923
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.374
276882AE2-255 GEN
Solar/Wind Harmer
11.778
959331AF2-224 GEN
Solar/Wind Harmer
1.068
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
274776LINCOLN ;7U
50/50
18.381
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274872LEEDK;1U
Solar/Wind Harmer
0.491
959081AF2-199 GEN
Solar/Wind Harmer
1.098
971475AH1-234 GEN
Solar/Wind Harmer
2.43
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
24791305MDL-5G
Solar/Wind Harmer
8.898
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276726Z2-087_GEN
Solar/Wind Harmer
27.314
24386205FR-12G C
Solar/Wind Harmer
8.454
963741AG1-226 GEN
Solar/Wind Harmer
4.423
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
24344005CKG1
50/50
20.898
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.275
274887GEN-1.85
Solar/Wind Harmer
21.706
944531AF1-118 GEN
Solar/Wind Harmer
4.029
276157O29GEN1
Solar/Wind Harmer
15.515
957751AF2-069 GEN
Solar/Wind Harmer
1.39
939741AE1-205 GEN
Solar/Wind Harmer
2.101
970241AG2-163 GEN
Solar/Wind Harmer
2.457
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
971599AH1-298 GEN
50/50
20.101
970321AG2-212 GEN
Solar/Wind Harmer
2.599
270071AF1-092 GEN
Solar/Wind Harmer
1.806
276602WESTBROOK C
Solar/Wind Harmer
7.74
970611AG2-400 GEN
Solar/Wind Harmer
1.068
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
942111AE2-223 GEN
Solar/Wind Harmer
24.582
24387305FR-4G C
Solar/Wind Harmer
12.146
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
270100X2-052 CT1
50/50
3.113
274770LINCOLN ;1U
50/50
18.381
274771LINCOLN ;2U
50/50
18.381
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.213
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
972207SS24-0001
Solar/Wind Harmer
3.581
972181SS23-001
Solar/Wind Harmer
1.176
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.196
24755605MDL-5G
Solar/Wind Harmer
8.898
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
270349AD2-093_GEN
Solar/Wind Helper
0.697
270144AC1-141 ST1_
50/50
4.442
24642205MAYFLWER
50/50
1.544
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
971067AG2-660 GEN
Solar/Wind Harmer
4.392
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.298
276741O09 GEN1
Solar/Wind Harmer
13.059
276655WTG1_EQ
Solar/Wind Harmer
18.09
965101AG1-375 GEN
Solar/Wind Harmer
1.033
963841AG1-237 GEN
Solar/Wind Harmer
31.494
276686W4-005 GEN3
Solar/Wind Harmer
9.72
276897AD1-100 C
Solar/Wind Harmer
118.927
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.65
970571AG2-364 GEN
Solar/Wind Harmer
2.17
971681AH1-341 GEN
Solar/Wind Harmer
1.62
938861AE1-114 GEN
Solar/Wind Harmer
25.259
276603SUBLETTE C
Solar/Wind Harmer
3.668
965011AG1-365 GEN
Solar/Wind Harmer
1.068
972175AH1-670 GEN
Solar/Wind Harmer
39.134
276174W4-005 GEN2
Solar/Wind Harmer
9.72
970833AG2-524 GEN
Solar/Wind Harmer
10.129
958481AF2-142 GEN
Solar/Wind Harmer
1.694
276868AE1-113 GEN
Solar/Wind Harmer
37.335
971675AH1-338 GEN
Solar/Wind Harmer
1.99
970781AG2-491 GEN
Solar/Wind Harmer
1.075
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
274775LINCOLN ;6U
50/50
18.381
960591AF2-350 GEN
Solar/Wind Harmer
1.164
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.46
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
939401AE1-172 GEN
Solar/Wind Harmer
44.561
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
276656WTG2_EQ
Solar/Wind Harmer
2.395
941731AE2-173 GEN
Solar/Wind Harmer
10.505
970169AG2-114 GEN
Solar/Wind Harmer
1.087
961011AF2-392 GEN
Solar/Wind Harmer
33.139
276785W4-005 GEN1
Solar/Wind Harmer
9.72
970521AG2-332 GEN
50/50
23.831
276806AD2-047 C O1
Solar/Wind Harmer
35.85
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.196
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
270471AD2-092_GEN
Solar/Wind Helper
0.697
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
943121AE2-341 GEN
Solar/Wind Harmer
1.718
957471AF2-041 GEN
Solar/Wind Harmer
3.294
965651AG1-433 GEN
Solar/Wind Harmer
16.467
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
959341AF2-225 GEN
Solar/Wind Harmer
1.576
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
943021AE2-325 GEN
Solar/Wind Harmer
7.464
958011AF2-095 GEN
Solar/Wind Harmer
1.676
971573AH1-285 GEN
Solar/Wind Harmer
0.979
958491AF2-143 GEN
Solar/Wind Harmer
1.674
942991AE2-321 GEN
Solar/Wind Harmer
1.111
971333AH1-146 GEN
Solar/Wind Harmer
2.209
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.306
24697905MDL-4G C
Solar/Wind Harmer
8.898
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
957141AF2-008_MTX
Adder
82.473
944201AF1-088_MTX
Adder
164.946
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
TVALTFEXP_TVA->PJM
CLTF
5.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769
NYPJM->LTFIMP_NY
CLTF
3.299
LGEELTFEXP_LGEE->PJM
CLTF
5.706
WECLTFEXP_WEC->PJM
CLTF
7.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
MECLTFEXP_MEC->PJM
CLTF
26.098
SIGELTFEXP_SIGE->PJM
CLTF
0.559

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.76 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:5098.11
MW Contribution:1.31
Bus #Bus NameTypeMW Contribution
274776LINCOLN ;7U
50/50
18.381
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.469
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
22.259
274872LEEDK;1U
Solar/Wind Harmer
0.491
959081AF2-199 GEN
Solar/Wind Harmer
1.098
971475AH1-234 GEN
Solar/Wind Harmer
2.43
270180AB1-006 GEN1
Solar/Wind Harmer
25.287
24791305MDL-5G
Solar/Wind Harmer
8.898
276646AC1-214 GEN2
Solar/Wind Harmer
4.555
276726Z2-087_GEN
Solar/Wind Harmer
27.314
24386205FR-12G C
Solar/Wind Harmer
8.454
963741AG1-226 GEN
Solar/Wind Harmer
4.423
276764AC1-053 GEN2
Solar/Wind Harmer
5.071
274773LINCOLN ;4U
50/50
18.381
276893AG1-478 C
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
3.365
971997AH1-543 GEN
Solar/Wind Harmer
1.748
276863AD2-134 GEN
Solar/Wind Harmer
6.785
274863CRW1-WTG
Solar/Wind Harmer
20.869
276889AE2-281 GEN
Solar/Wind Harmer
7.026
957841AF2-078 GEN
Solar/Wind Harmer
0
274856ECOGROVE ;U1
Solar/Wind Harmer
12.731
971549AH1-272 GEN
Solar/Wind Harmer
2.005
24691005MDL-2G C
Solar/Wind Harmer
13.498
965021AG1-366 GEN
Solar/Wind Harmer
4.273
276158O29GEN2
Solar/Wind Harmer
15.515
276708O09 GEN2
Solar/Wind Harmer
13.059
958861AF2-177 GEN
Solar/Wind Harmer
32.216
945371AF1-202 GEN
Solar/Wind Harmer
15.423
274880W4-005 GEN4
Solar/Wind Harmer
9.72
971993AH1-541 GEN
Solar/Wind Harmer
0.903
971599AH1-298 GEN
50/50
20.101
970321AG2-212 GEN
Solar/Wind Harmer
2.599
270071AF1-092 GEN
Solar/Wind Harmer
1.806
276602WESTBROOK C
Solar/Wind Harmer
7.74
970611AG2-400 GEN
Solar/Wind Harmer
1.068
276645AC1-214 GEN1
Solar/Wind Harmer
4.555
942111AE2-223 GEN
Solar/Wind Harmer
24.582
24387305FR-4G C
Solar/Wind Harmer
12.146
24386605FR-22G C
Solar/Wind Harmer
8.098
24387005FR-3G C
Solar/Wind Harmer
8.017
972207SS24-0001
Solar/Wind Harmer
3.581
972181SS23-001
Solar/Wind Harmer
1.176
270055AF2-134 C O1
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
2.196
24755605MDL-5G
Solar/Wind Harmer
8.898
274849CRESCENT ;1U
Solar/Wind Harmer
6.954
274877BISHOP HL;1U
Solar/Wind Harmer
12.24
270349AD2-093_GEN
Solar/Wind Helper
0.697
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
26.808
943121AE2-341 GEN
Solar/Wind Harmer
1.718
957471AF2-041 GEN
Solar/Wind Harmer
3.294
965651AG1-433 GEN
Solar/Wind Harmer
16.467
274848CAMPGROVE;RU
Solar/Wind Harmer
19.143
959341AF2-225 GEN
Solar/Wind Harmer
1.576
276849AB2-070 GEN2
Solar/Wind Harmer
7.391
270144AC1-141 ST1_
50/50
4.442
24642205MAYFLWER
50/50
1.544
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
17.74
276691AA1-018 GEN1
Solar/Wind Harmer
1.216
971067AG2-660 GEN
Solar/Wind Harmer
4.392
276872AE1-163_GEN1
Solar/Wind Harmer
24.592
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
28.298
276741O09 GEN1
Solar/Wind Harmer
13.059
276655WTG1_EQ
Solar/Wind Harmer
18.09
965101AG1-375 GEN
Solar/Wind Harmer
1.033
963841AG1-237 GEN
Solar/Wind Harmer
31.494
270102X2-052 ST
50/50
3.369
970901AG2-562 GEN
50/50
12.765
274777LINCOLN ;8U
50/50
18.381
970245AG2-165 GEN
Solar/Wind Harmer
2.599
970349AG2-230 GEN
Solar/Wind Harmer
1.946
971347AH1-153 GEN
Solar/Wind Harmer
1.946
961051AF2-396 GEN
Solar/Wind Harmer
2.387
961051AF2-396 GEN
Solar/Wind Harmer
19.097
972231SS25-0005
Solar/Wind Harmer
1.881
274862TOP CROP ;2U
Solar/Wind Harmer
18.489
970921AG2-575 GEN
Solar/Wind Harmer
1.119
970921AG2-575 GEN
Solar/Wind Harmer
4.476
274879MINONK ;1U
Solar/Wind Harmer
26.112
971411AH1-196 GEN
Solar/Wind Harmer
1.658
274855GSG-6 ;RU
Solar/Wind Harmer
14.037
960971AF2-388 GEN
Solar/Wind Harmer
32.934
24386405FR-21G C
Solar/Wind Harmer
8.098
276763AC1-053 GEN1
Solar/Wind Harmer
5.071
970513AG2-328 GEN
Solar/Wind Harmer
2.599
970517AG2-330 GEN
Solar/Wind Harmer
40.548
270063AE2-323 C
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.266
959141AF2-205 GEN
Solar/Wind Harmer
0
962781AG1-127 GEN
Solar/Wind Harmer
1.064
971335AH1-147 GEN
Solar/Wind Harmer
2.209
971171AH1-044 GEN
Solar/Wind Harmer
2.196
926823AC1-168 GEN
Solar/Wind Harmer
13.329
24697605MDL-3G C
Solar/Wind Harmer
13.476
270181AB1-006 GEN2
Solar/Wind Harmer
1.676
276782AC1-033 GEN
Solar/Wind Harmer
13.828
24385905FR-11G C
Solar/Wind Harmer
15.919
946321AF1-296 GEN
Solar/Wind Harmer
30.766
959611AF2-252 GEN
Solar/Wind Harmer
4.131
960611AF2-352 GEN
Solar/Wind Harmer
4.131
945581AF1-223 GEN
Solar/Wind Harmer
0
274775LINCOLN ;6U
50/50
18.381
960591AF2-350 GEN
Solar/Wind Harmer
1.164
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.46
958381AF2-132 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
21.795
939401AE1-172 GEN
Solar/Wind Harmer
44.561
276876AE1-163_GEN2
Solar/Wind Harmer
24.592
270142AC1-141 CT1_
50/50
5.015
270143AC1-141 CT2_
50/50
5.015
24639705ELKHART HY
50/50
0.335
965681AG1-436 GEN
Solar/Wind Harmer
1.524
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.145
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.196
970169AG2-114 GEN
Solar/Wind Harmer
1.087
276686W4-005 GEN3
Solar/Wind Harmer
9.72
943021AE2-325 GEN
Solar/Wind Harmer
7.464
958011AF2-095 GEN
Solar/Wind Harmer
1.676
971573AH1-285 GEN
Solar/Wind Harmer
0.979
958491AF2-143 GEN
Solar/Wind Harmer
1.674
942991AE2-321 GEN
Solar/Wind Harmer
1.111
971333AH1-146 GEN
Solar/Wind Harmer
2.209
945421AF1-207 GEN
Solar/Wind Harmer
0
970819AG2-516 GEN
Solar/Wind Harmer
1.306
24697905MDL-4G C
Solar/Wind Harmer
8.898
274851PROVIDENC;RU
Solar/Wind Harmer
10.062
274878BISHOP HL;2U
Solar/Wind Harmer
12.24
965091AG1-374 GEN
Solar/Wind Harmer
3.098
965931AG1-462 GEN
Solar/Wind Harmer
2.618
274772LINCOLN ;3U
50/50
18.381
274774LINCOLN ;5U
50/50
18.381
270043AE2-236 GEN
Solar/Wind Harmer
0.674
971771AH1-392 GEN
Solar/Wind Harmer
1.097
270505AE1-170 C O1
Solar/Wind Harmer
1.807
274888KELLY CRK;1U
Solar/Wind Harmer
23.628
970941AG2-585 GEN
Solar/Wind Harmer
1.455
276805AD2-038 GEN
Solar/Wind Harmer
20.225
971605AH1-302 GEN
Solar/Wind Harmer
16.727
274850MENDOTA H;RU
Solar/Wind Harmer
9.942
276861AD2-134 GEN
Solar/Wind Harmer
6.785
274864CRW2-WTG
Solar/Wind Harmer
20.869
970569AG2-363 GEN
Solar/Wind Harmer
3.256
274858EASY ROAD;U2
Solar/Wind Harmer
16.859
276157O29GEN1
Solar/Wind Harmer
15.515
957751AF2-069 GEN
Solar/Wind Harmer
1.39
939741AE1-205 GEN
Solar/Wind Harmer
2.101
970241AG2-163 GEN
Solar/Wind Harmer
2.457
276668AB2-070 GEN1
Solar/Wind Harmer
7.391
274857EASY ROAD;U1
Solar/Wind Harmer
16.859
276656WTG2_EQ
Solar/Wind Harmer
2.395
941731AE2-173 GEN
Solar/Wind Harmer
10.505
24344005CKG1
50/50
20.898
24641605TWIN BRNCH
50/50
0.036
24643105BUCHANAN
50/50
0.026
970707AG2-453 GEN
Solar/Wind Harmer
3.275
274887GEN-1.85
Solar/Wind Harmer
21.706
944531AF1-118 GEN
Solar/Wind Harmer
4.029
970833AG2-524 GEN
Solar/Wind Harmer
10.129
958481AF2-142 GEN
Solar/Wind Harmer
1.694
276868AE1-113 GEN
Solar/Wind Harmer
37.335
971675AH1-338 GEN
Solar/Wind Harmer
1.99
970781AG2-491 GEN
Solar/Wind Harmer
1.075
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
25.477
270100X2-052 CT1
50/50
3.113
274770LINCOLN ;1U
50/50
18.381
274771LINCOLN ;2U
50/50
18.381
24653605MOTTVILLE
50/50
0.007
971769AH1-391 GEN
Solar/Wind Harmer
1.213
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.136
945111AF1-176 GEN
Solar/Wind Harmer
11.643
276897AD1-100 C
Solar/Wind Harmer
118.927
964861AG1-349 GEN
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.65
970571AG2-364 GEN
Solar/Wind Harmer
2.17
971681AH1-341 GEN
Solar/Wind Harmer
1.62
938861AE1-114 GEN
Solar/Wind Harmer
25.259
276603SUBLETTE C
Solar/Wind Harmer
3.668
965011AG1-365 GEN
Solar/Wind Harmer
1.068
972175AH1-670 GEN
Solar/Wind Harmer
39.134
276174W4-005 GEN2
Solar/Wind Harmer
9.72
24344105CKG2
50/50
17.979
270101X2-052 CT2
50/50
3.113
965791AG1-447 GEN
Solar/Wind Harmer
13.41
276843GEN-1.7
Solar/Wind Harmer
1.923
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
32.374
276882AE2-255 GEN
Solar/Wind Harmer
11.778
959331AF2-224 GEN
Solar/Wind Harmer
1.068
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
25.209
961011AF2-392 GEN
Solar/Wind Harmer
33.139
276785W4-005 GEN1
Solar/Wind Harmer
9.72
970521AG2-332 GEN
50/50
23.831
276806AD2-047 C O1
Solar/Wind Harmer
35.85
274847GR RIDGE ;BU
Solar/Wind Harmer
20.515
958391AF2-133 GEN
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
2.196
247642Z2-115 C
Solar/Wind Harmer
-0.001
276848AB2-070 GEN3
Solar/Wind Harmer
7.393
270471AD2-092_GEN
Solar/Wind Helper
0.697
957141AF2-008_MTX
Adder
82.473
944201AF1-088_MTX
Adder
164.946
LAGNLTFEXP_LAGN->PJM
CLTF
14.212
TVALTFEXP_TVA->PJM
CLTF
5.473
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.912
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
42.769
NYPJM->LTFIMP_NY
CLTF
3.299
LGEELTFEXP_LGEE->PJM
CLTF
5.706
WECLTFEXP_WEC->PJM
CLTF
7.164
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.097
AG2-052LTFEXP_AG2-052->PJM
LTF
0.442
AH1-155LTFEXP_AH1-155->PJM
LTF
0.663
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.459
CBM West 1LTFEXP_CBM-W1->PJM
CBM
222.098
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.451
MECLTFEXP_MEC->PJM
CLTF
26.098
SIGELTFEXP_SIGE->PJM
CLTF
0.559

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P4_#1760_05JEFRSO 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#1760_05JEFRSO 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.41 %
Rating:4961.0 MVA
Rating Type:B
MVA to Mitigate:4981.37
MW Contribution:1.38
Bus #Bus NameTypeMW Contribution
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
2.675
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
23.557
274872LEEDK;1U
Solar/Wind Harmer
0.519
270180AB1-006 GEN1
Solar/Wind Harmer
27.585
24791305MDL-5G
Solar/Wind Harmer
9.707
270102X2-052 ST
50/50
3.624
970901AG2-562 GEN
50/50
13.732
970245AG2-165 GEN
Solar/Wind Harmer
2.888
970349AG2-230 GEN
Solar/Wind Harmer
2.09
971347AH1-153 GEN
Solar/Wind Harmer
2.09
961051AF2-396 GEN
Solar/Wind Harmer
2.561
961051AF2-396 GEN
Solar/Wind Harmer
20.485
972231SS25-0005
Solar/Wind Harmer
2.005
274862TOP CROP ;2U
Solar/Wind Harmer
19.567
970921AG2-575 GEN
Solar/Wind Harmer
1.183
970921AG2-575 GEN
Solar/Wind Harmer
4.733
274879MINONK ;1U
Solar/Wind Harmer
27.571
971411AH1-196 GEN
Solar/Wind Harmer
1.752
274855GSG-6 ;RU
Solar/Wind Harmer
14.825
24386405FR-21G C
Solar/Wind Harmer
8.703
960971AF2-388 GEN
Solar/Wind Harmer
33.741
959081AF2-199 GEN
Solar/Wind Harmer
1.159
971475AH1-234 GEN
Solar/Wind Harmer
2.562
24386205FR-12G C
Solar/Wind Harmer
9.086
276646AC1-214 GEN2
Solar/Wind Harmer
4.778
276726Z2-087_GEN
Solar/Wind Harmer
28.481
963741AG1-226 GEN
Solar/Wind Harmer
4.654
24344105CKG2
50/50
19.362
270101X2-052 CT2
50/50
3.348
965791AG1-447 GEN
Solar/Wind Harmer
14.413
276843GEN-1.7
Solar/Wind Harmer
2.043
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
34.229
276882AE2-255 GEN
Solar/Wind Harmer
12.436
959331AF2-224 GEN
Solar/Wind Harmer
1.123
944541AF1-119 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
26.202
971599AH1-298 GEN
50/50
21.036
970321AG2-212 GEN
Solar/Wind Harmer
2.888
970333AG2-219 GEN
Solar/Wind Harmer
4.372
270071AF1-092 GEN
Solar/Wind Harmer
1.926
276602WESTBROOK C
Solar/Wind Harmer
8.175
970611AG2-400 GEN
Solar/Wind Harmer
1.123
24387305FR-4G C
Solar/Wind Harmer
13.054
24386605FR-22G C
Solar/Wind Harmer
8.703
24387005FR-3G C
Solar/Wind Harmer
8.616
276645AC1-214 GEN1
Solar/Wind Harmer
4.778
942111AE2-223 GEN
Solar/Wind Harmer
25.633
270100X2-052 CT1
50/50
3.348
24653605MOTTVILLE
50/50
0.008
24307105BERRINSP G
50/50
0.048
971769AH1-391 GEN
Solar/Wind Harmer
1.303
957891AF2-083 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
2.29
945111AF1-176 GEN
Solar/Wind Harmer
12.484
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
126.162
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.687
970571AG2-364 GEN
Solar/Wind Harmer
2.284
971681AH1-341 GEN
Solar/Wind Harmer
1.706
938861AE1-114 GEN
Solar/Wind Harmer
26.61
276603SUBLETTE C
Solar/Wind Harmer
3.862
965011AG1-365 GEN
Solar/Wind Harmer
1.123
972175AH1-670 GEN
Solar/Wind Harmer
40.448
276174W4-005 GEN2
Solar/Wind Harmer
7.56
944961AF1-161 GEN
50/50
6.392
970243AG2-164 GEN
Solar/Wind Harmer
3.577
971771AH1-392 GEN
Solar/Wind Harmer
1.176
270505AE1-170 C O1
Solar/Wind Harmer
1.938
270043AE2-236 GEN
Solar/Wind Harmer
0.71
274888KELLY CRK;1U
Solar/Wind Harmer
25.103
970941AG2-585 GEN
Solar/Wind Harmer
1.546
971605AH1-302 GEN
Solar/Wind Harmer
18.291
276805AD2-038 GEN
Solar/Wind Harmer
21.371
274850MENDOTA H;RU
Solar/Wind Harmer
10.5
276861AD2-134 GEN
Solar/Wind Harmer
7.166
274864CRW2-WTG
Solar/Wind Harmer
21.955
970569AG2-363 GEN
Solar/Wind Harmer
3.426
274858EASY ROAD;U2
Solar/Wind Harmer
17.754
276157O29GEN1
Solar/Wind Harmer
16.305
957751AF2-069 GEN
Solar/Wind Harmer
1.458
939741AE1-205 GEN
Solar/Wind Harmer
2.191
970241AG2-163 GEN
Solar/Wind Harmer
2.585
970239AG2-162 GEN
Solar/Wind Harmer
1.524
276893AG1-478 C
Solar/Wind Harmer
-0.001
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
3.56
24691005MDL-2G C
Solar/Wind Harmer
14.724
971997AH1-543 GEN
Solar/Wind Harmer
1.844
276863AD2-134 GEN
Solar/Wind Harmer
7.166
971549AH1-272 GEN
Solar/Wind Harmer
2.153
274863CRW1-WTG
Solar/Wind Harmer
21.955
276889AE2-281 GEN
Solar/Wind Harmer
7.407
274856ECOGROVE ;U1
Solar/Wind Harmer
13.423
965021AG1-366 GEN
Solar/Wind Harmer
4.491
276158O29GEN2
Solar/Wind Harmer
16.305
276708O09 GEN2
Solar/Wind Harmer
13.724
958861AF2-177 GEN
Solar/Wind Harmer
32.945
945371AF1-202 GEN
Solar/Wind Harmer
15.713
274880W4-005 GEN4
Solar/Wind Harmer
7.56
24344005CKG1
50/50
22.459
24641605TWIN BRNCH
50/50
0.039
24643105BUCHANAN
50/50
0.028
970699AG2-449 GEN
Solar/Wind Harmer
1.59
970707AG2-453 GEN
Solar/Wind Harmer
3.479
274887GEN-1.85
Solar/Wind Harmer
23.06
970833AG2-524 GEN
Solar/Wind Harmer
10.74
958481AF2-142 GEN
Solar/Wind Harmer
1.793
944531AF1-118 GEN
Solar/Wind Harmer
4.156
276868AE1-113 GEN
Solar/Wind Harmer
39.421
970781AG2-491 GEN
Solar/Wind Harmer
1.172
971675AH1-338 GEN
Solar/Wind Harmer
2.102
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
26.481
970513AG2-328 GEN
Solar/Wind Harmer
2.888
970517AG2-330 GEN
Solar/Wind Harmer
45.053
270063AE2-323 C
Solar/Wind Harmer
0
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
1.342
962781AG1-127 GEN
Solar/Wind Harmer
1.125
24697605MDL-3G C
Solar/Wind Harmer
14.701
270181AB1-006 GEN2
Solar/Wind Harmer
1.829
971335AH1-147 GEN
Solar/Wind Harmer
2.334
971171AH1-044 GEN
Solar/Wind Harmer
2.318
926823AC1-168 GEN
Solar/Wind Harmer
14.021
24385905FR-11G C
Solar/Wind Harmer
17.109
276782AC1-033 GEN
Solar/Wind Harmer
14.5
946321AF1-296 GEN
Solar/Wind Harmer
32.251
959611AF2-252 GEN
Solar/Wind Harmer
4.294
960611AF2-352 GEN
Solar/Wind Harmer
4.294
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970519AG2-331 GEN
Solar/Wind Harmer
41.339
958381AF2-132 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
1.237
939351AE1-166 GEN
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
3.677
276694AA1-018 GEN2
Solar/Wind Harmer
23.067
939401AE1-172 GEN
Solar/Wind Harmer
46.994
276876AE1-163_GEN2
Solar/Wind Harmer
25.923
274857EASY ROAD;U1
Solar/Wind Harmer
17.754
276656WTG2_EQ
Solar/Wind Harmer
2.498
941731AE2-173 GEN
Solar/Wind Harmer
10.954
972207SS24-0001
Solar/Wind Harmer
3.811
270055AF2-134 C O1
Solar/Wind Harmer
0
972181SS23-001
Solar/Wind Harmer
1.253
24755605MDL-5G
Solar/Wind Harmer
9.707
959091AF2-200 GEN
Solar/Wind Harmer
2.318
274849CRESCENT ;1U
Solar/Wind Harmer
7.294
274877BISHOP HL;1U
Solar/Wind Harmer
12.834
970289AG2-191 GEN
Solar/Wind Harmer
0.195
270349AD2-093_GEN
Solar/Wind Helper
0.687
270142AC1-141 CT1_
50/50
5.381
270143AC1-141 CT2_
50/50
5.381
24639705ELKHART HY
50/50
0.359
965681AG1-436 GEN
Solar/Wind Harmer
1.638
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
1.214
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
2.318
970169AG2-114 GEN
Solar/Wind Harmer
1.141
961011AF2-392 GEN
Solar/Wind Harmer
34.864
963791AG1-232 GEN
Solar/Wind Harmer
1.357
276785W4-005 GEN1
Solar/Wind Harmer
7.56
270144AC1-141 ST1_
50/50
4.766
24642205MAYFLWER
50/50
1.656
962601AG1-109 GEN
50/50
6.392
960681AF2-359 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
19.33
276691AA1-018 GEN1
Solar/Wind Harmer
1.287
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
30.87
971067AG2-660 GEN
Solar/Wind Harmer
4.636
276872AE1-163_GEN1
Solar/Wind Harmer
25.923
276741O09 GEN1
Solar/Wind Harmer
13.724
276655WTG1_EQ
Solar/Wind Harmer
18.863
963841AG1-237 GEN
Solar/Wind Harmer
33.488
965101AG1-375 GEN
Solar/Wind Harmer
1.056
276686W4-005 GEN3
Solar/Wind Harmer
7.56
970521AG2-332 GEN
50/50
25.509
276806AD2-047 C O1
Solar/Wind Harmer
38.087
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
21.75
971341AH1-150 GEN
Solar/Wind Harmer
2.318
247642Z2-115 C
Solar/Wind Harmer
-0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.229
270471AD2-092_GEN
Solar/Wind Helper
0.687
943021AE2-325 GEN
Solar/Wind Harmer
8.008
958011AF2-095 GEN
Solar/Wind Harmer
1.781
971573AH1-285 GEN
Solar/Wind Harmer
1.038
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
1.769
942991AE2-321 GEN
Solar/Wind Harmer
1.174
24697905MDL-4G C
Solar/Wind Harmer
9.707
971333AH1-146 GEN
Solar/Wind Harmer
2.334
970819AG2-516 GEN
Solar/Wind Harmer
1.377
274851PROVIDENC;RU
Solar/Wind Harmer
10.555
274878BISHOP HL;2U
Solar/Wind Harmer
12.834
965931AG1-462 GEN
Solar/Wind Harmer
2.743
965091AG1-374 GEN
Solar/Wind Harmer
3.22
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
28.423
943121AE2-341 GEN
Solar/Wind Harmer
1.821
957471AF2-041 GEN
Solar/Wind Harmer
3.477
274848CAMPGROVE;RU
Solar/Wind Harmer
20.056
959341AF2-225 GEN
Solar/Wind Harmer
1.643
965651AG1-433 GEN
Solar/Wind Harmer
16.87
970291AG2-192 GEN
Solar/Wind Harmer
0.133
970289AG2-191 GEN
Solar/Wind Harmer
1.352
957141AF2-008_MTX
Adder
74.064
944201AF1-088_MTX
Adder
148.128
LAGNLTFEXP_LAGN->PJM
CLTF
13.768
TVALTFEXP_TVA->PJM
CLTF
5.095
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.171
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
52.01
NYPJM->LTFIMP_NY
CLTF
3.326
LGEELTFEXP_LGEE->PJM
CLTF
4.567
WECLTFEXP_WEC->PJM
CLTF
7.559
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.261
AG2-052LTFEXP_AG2-052->PJM
LTF
0.47
AH1-155LTFEXP_AH1-155->PJM
LTF
0.706
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.568
CBM West 1LTFEXP_CBM-W1->PJM
CBM
232.762
CBM South 1LTFEXP_CBM-S1->PJM
CBM
20.173
MECLTFEXP_MEC->PJM
CLTF
26.993
SIGELTFEXP_SIGE->PJM
CLTF
0.513

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.24 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2290.85
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
68.465
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
960851AF2-376 GEN
50/50
2.066
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
24729205KEY G1
50/50
6.679
24641605TWIN BRNCH
50/50
0.015
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
1.01
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
6.161
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
241847AF2-150_GEN
Solar/Wind Helper
0.259
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
24727005RPMNG1
50/50
68.465
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
24727105RPMNG2
50/50
68.465
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
957141AF2-008_MTX
Adder
27.929
944201AF1-088_MTX
Adder
55.858
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398
NYPJM->LTFIMP_NY
CLTF
1.242
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.632
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
MECLTFEXP_MEC->PJM
CLTF
9.671
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.42 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2339.21
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
971617AH1-308 GEN
Solar/Wind Harmer
5.12
943021AE2-325 GEN
Solar/Wind Harmer
2.954
958011AF2-095 GEN
Solar/Wind Harmer
0.618
971573AH1-285 GEN
Solar/Wind Harmer
0.358
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.616
942991AE2-321 GEN
Solar/Wind Harmer
0.407
971333AH1-146 GEN
Solar/Wind Harmer
0.81
24697905MDL-4G C
Solar/Wind Harmer
3.34
970819AG2-516 GEN
Solar/Wind Harmer
0.479
274851PROVIDENC;RU
Solar/Wind Harmer
3.693
964611AG1-324 GEN
Solar/Wind Harmer
0.35
270201AC2-176 GEN
Solar/Wind Harmer
6.57
274878BISHOP HL;2U
Solar/Wind Harmer
4.493
24699105WLD G1 C
Solar/Wind Harmer
4.967
965931AG1-462 GEN
Solar/Wind Harmer
0.963
270499AE1-146 GEN
Solar/Wind Helper
0.534
965431AG1-411 GEN
50/50
45.157
24727205RPMNG3
50/50
68.465
24639705ELKHART HY
50/50
0.149
963791AG1-232 GEN
Solar/Wind Harmer
0.959
270246TR4_N_V150
Solar/Wind Harmer
1.16
24695305TIMB G C
Solar/Wind Harmer
9.67
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.572
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.419
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.409
971343AH1-151 GEN
Solar/Wind Harmer
0.805
970169AG2-114 GEN
Solar/Wind Harmer
0.398
961011AF2-392 GEN
Solar/Wind Harmer
12.167
270227U2-072_GEN3
Solar/Wind Helper
0.141
270228U2-072_GEN4
Solar/Wind Helper
0.141
276820AF1-078_GEN
Solar/Wind Helper
0.151
970583AG2-370 GEN
50/50
2.775
970031AG2-029 GEN
Solar/Wind Harmer
2.089
270247TR4_N_V136
Solar/Wind Harmer
1.16
965051AG1-369 GEN
Solar/Wind Harmer
0.295
960591AF2-350 GEN
Solar/Wind Harmer
0.429
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.024
939401AE1-172 GEN
Solar/Wind Harmer
16.293
276876AE1-163_GEN2
Solar/Wind Harmer
9.042
274857EASY ROAD;U1
Solar/Wind Harmer
6.189
961761AG1-017 GEN
Solar/Wind Harmer
0.383
276656WTG2_EQ
Solar/Wind Harmer
0.876
941731AE2-173 GEN
Solar/Wind Harmer
3.84
270462AD2-086
Solar/Wind Helper
1.767
270317AD1-130_GEN
Solar/Wind Helper
1.153
270287AF1-227 GEN3
Solar/Wind Helper
0.344
965021AG1-366 GEN
Solar/Wind Harmer
4.56
958861AF2-177 GEN
Solar/Wind Harmer
15.756
945371AF1-202 GEN
Solar/Wind Harmer
7.43
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.232
270594AE1-207 GEN
Solar/Wind Harmer
0.652
270032AE2-172
Solar/Wind Harmer
3.259
971997AH1-543 GEN
Solar/Wind Harmer
0.64
276863AD2-134 GEN
Solar/Wind Harmer
2.487
274863CRW1-WTG
Solar/Wind Harmer
7.63
276889AE2-281 GEN
Solar/Wind Harmer
2.583
24691005MDL-2G C
Solar/Wind Harmer
5.066
274856ECOGROVE ;U1
Solar/Wind Harmer
4.672
971549AH1-272 GEN
Solar/Wind Harmer
0.724
276158O29GEN2
Solar/Wind Harmer
5.697
276708O09 GEN2
Solar/Wind Harmer
4.795
246937BC-WTG2
Solar/Wind Helper
5.531
270485AE1-090_GEN
Solar/Wind Helper
0.154
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.14
945111AF1-176 GEN
Solar/Wind Harmer
0.877
945111AF1-176 GEN
Solar/Wind Harmer
4.78
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.467
970615AG2-402 GEN
50/50
4.56
24729405KEY G3
50/50
6.792
24729505KEY G4
50/50
6.679
270043AE2-236 GEN
Solar/Wind Harmer
0.369
971771AH1-392 GEN
Solar/Wind Harmer
0.437
270505AE1-170 C O1
Solar/Wind Harmer
0.719
274888KELLY CRK;1U
Solar/Wind Harmer
8.705
970941AG2-585 GEN
Solar/Wind Harmer
0.536
971605AH1-302 GEN
Solar/Wind Harmer
6.289
276805AD2-038 GEN
Solar/Wind Harmer
7.442
274850MENDOTA H;RU
Solar/Wind Harmer
3.644
276861AD2-134 GEN
Solar/Wind Harmer
2.487
274864CRW2-WTG
Solar/Wind Harmer
7.63
970569AG2-363 GEN
Solar/Wind Harmer
1.196
274858EASY ROAD;U2
Solar/Wind Harmer
6.189
276157O29GEN1
Solar/Wind Harmer
5.697
957751AF2-069 GEN
Solar/Wind Harmer
0.51
939741AE1-205 GEN
Solar/Wind Harmer
0.768
246938BC-WTG3
Solar/Wind Helper
5.468
246936BC-WTG1
Solar/Wind Helper
5.531
24729205KEY G1
50/50
6.679
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.927
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.196
270004AE1-209 GEN
Solar/Wind Harmer
6.381
274872LEEDK;1U
Solar/Wind Harmer
0.18
270180AB1-006 GEN1
Solar/Wind Harmer
9.491
24791305MDL-5G
Solar/Wind Harmer
3.34
959081AF2-199 GEN
Solar/Wind Harmer
0.403
971475AH1-234 GEN
Solar/Wind Harmer
0.892
276646AC1-214 GEN2
Solar/Wind Harmer
1.672
24386205FR-12G C
Solar/Wind Harmer
3.157
276726Z2-087_GEN
Solar/Wind Harmer
9.984
944531AF1-118 GEN
Solar/Wind Harmer
2.039
274887GEN-1.85
Solar/Wind Harmer
7.997
970707AG2-453 GEN
Solar/Wind Harmer
1.193
970833AG2-524 GEN
Solar/Wind Harmer
3.709
958481AF2-142 GEN
Solar/Wind Harmer
0.624
276868AE1-113 GEN
Solar/Wind Harmer
13.718
971675AH1-338 GEN
Solar/Wind Harmer
0.729
970781AG2-491 GEN
Solar/Wind Harmer
0.403
960791AF2-370 GEN
Solar/Wind Harmer
1.606
276903AD2-071 C
Solar/Wind Harmer
0.391
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.31
270224U2-072_GEN2
Solar/Wind Helper
0.141
270391AF1-285 GEN3
Solar/Wind Helper
0.282
241847AF2-150_GEN
Solar/Wind Helper
0.259
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.887
970517AG2-330 GEN
Solar/Wind Harmer
13.834
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.464
962781AG1-127 GEN
Solar/Wind Harmer
0.39
958821AF2-173 GEN
Solar/Wind Harmer
0.573
971335AH1-147 GEN
Solar/Wind Harmer
0.81
24697605MDL-3G C
Solar/Wind Harmer
5.058
270181AB1-006 GEN2
Solar/Wind Harmer
0.629
971171AH1-044 GEN
Solar/Wind Harmer
0.805
926823AC1-168 GEN
Solar/Wind Harmer
4.888
24385905FR-11G C
Solar/Wind Harmer
5.945
276782AC1-033 GEN
Solar/Wind Harmer
5.076
24725505WLD G2 C
Solar/Wind Harmer
4.997
946321AF1-296 GEN
Solar/Wind Harmer
11.312
958581AF2-149 GEN
Solar/Wind Helper
0.216
960611AF2-352 GEN
Solar/Wind Harmer
0.85
960971AF2-388 GEN
Solar/Wind Harmer
16.226
970349AG2-230 GEN
Solar/Wind Harmer
0.722
971347AH1-153 GEN
Solar/Wind Harmer
0.722
961051AF2-396 GEN
Solar/Wind Harmer
0.958
961051AF2-396 GEN
Solar/Wind Harmer
7.664
270599AE1-208 GEN
Solar/Wind Harmer
0.368
970245AG2-165 GEN
Solar/Wind Harmer
0.887
972231SS25-0005
Solar/Wind Harmer
0.704
274862TOP CROP ;2U
Solar/Wind Harmer
6.808
970921AG2-575 GEN
Solar/Wind Harmer
0.41
970921AG2-575 GEN
Solar/Wind Harmer
1.639
274879MINONK ;1U
Solar/Wind Harmer
9.594
971411AH1-196 GEN
Solar/Wind Harmer
0.608
274855GSG-6 ;RU
Solar/Wind Harmer
5.144
24386405FR-21G C
Solar/Wind Harmer
3.024
942871AE2-306 GEN
Solar/Wind Helper
0.211
945641AF1-229 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.447
959331AF2-224 GEN
Solar/Wind Harmer
1.14
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.037
276843GEN-1.7
Solar/Wind Harmer
0.708
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.858
276882AE2-255 GEN
Solar/Wind Harmer
4.328
960441AF2-335 GEN
Solar/Wind Harmer
0.402
270223U2-072_GEN1
Solar/Wind Helper
0.141
966831AG1-554 GEN
Solar/Wind Helper
0.276
274854TWINGROVE;U2
Solar/Wind Harmer
5.188
971599AH1-298 GEN
50/50
10.28
960861AF2-377 GEN
50/50
2.361
24729305KEY G2
50/50
6.792
970611AG2-400 GEN
Solar/Wind Harmer
1.14
270071AF1-092 GEN
Solar/Wind Harmer
0.935
970321AG2-212 GEN
Solar/Wind Harmer
0.887
270005AE1-210 C O1
Solar/Wind Harmer
6.381
276602WESTBROOK C
Solar/Wind Harmer
2.837
276645AC1-214 GEN1
Solar/Wind Harmer
1.672
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.583
24387305FR-4G C
Solar/Wind Harmer
4.536
24386605FR-22G C
Solar/Wind Harmer
3.024
24387005FR-3G C
Solar/Wind Harmer
2.994
942111AE2-223 GEN
Solar/Wind Harmer
8.986
960841AF2-375 GEN
Solar/Wind Helper
0.553
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.563
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.239
970571AG2-364 GEN
Solar/Wind Harmer
0.798
970825AG2-519 GEN
Solar/Wind Harmer
0.442
970825AG2-519 GEN
Solar/Wind Harmer
1.697
971681AH1-341 GEN
Solar/Wind Harmer
0.594
938861AE1-114 GEN
Solar/Wind Harmer
9.271
276603SUBLETTE C
Solar/Wind Harmer
1.346
253378AE2-206_GEN
Solar/Wind Helper
0.334
965421AG1-410 GEN
Solar/Wind Harmer
6.773
972181SS23-001
Solar/Wind Harmer
0.44
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.3
970289AG2-191 GEN
Solar/Wind Harmer
0.078
24755605MDL-5G
Solar/Wind Harmer
3.34
959091AF2-200 GEN
Solar/Wind Harmer
0.805
946031AF1-268 GEN
Solar/Wind Harmer
0.324
274849CRESCENT ;1U
Solar/Wind Harmer
2.552
274877BISHOP HL;1U
Solar/Wind Harmer
4.493
270349AD2-093_GEN
Solar/Wind Helper
0.444
24727005RPMNG1
50/50
68.465
247620Y3-023
50/50
0.46
965041AG1-368 GEN
Solar/Wind Harmer
0.694
270191TR4_S_V150
Solar/Wind Harmer
6.398
965101AG1-375 GEN
Solar/Wind Harmer
0.505
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.368
971917AH1-482 GEN
Solar/Wind Harmer
6.668
276691AA1-018 GEN1
Solar/Wind Harmer
0.448
276872AE1-163_GEN1
Solar/Wind Harmer
9.042
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.622
971067AG2-660 GEN
Solar/Wind Harmer
1.611
970115AG2-085 GEN
Solar/Wind Harmer
0.161
276741O09 GEN1
Solar/Wind Harmer
4.795
276655WTG1_EQ
Solar/Wind Harmer
6.613
270578AF1-285 GEN2
Solar/Wind Helper
0.282
247522W1-056 GEN
Solar/Wind Helper
1.885
270286AF1-227 GEN2
Solar/Wind Helper
0.344
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.289
970521AG2-332 GEN
50/50
10.75
247521TR3_G114
Solar/Wind Harmer
8.58
276806AD2-047 C O1
Solar/Wind Harmer
13.208
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.511
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.495
971341AH1-150 GEN
Solar/Wind Harmer
0.805
270302AB2-170 GEN
Solar/Wind Helper
1.153
270231U2-072_GEN5
Solar/Wind Helper
0.141
270471AD2-092_GEN
Solar/Wind Helper
0.444
24727105RPMNG2
50/50
68.465
965651AG1-433 GEN
Solar/Wind Harmer
8.113
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.816
943121AE2-341 GEN
Solar/Wind Harmer
0.628
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.544
957471AF2-041 GEN
Solar/Wind Harmer
1.208
274848CAMPGROVE;RU
Solar/Wind Harmer
7.026
959341AF2-225 GEN
Solar/Wind Harmer
0.576
957201AF2-014 GEN
Solar/Wind Helper
3.936
270284AF1-227 GEN1
Solar/Wind Helper
0.932
270428AC2-015 C
Solar/Wind Helper
0.365
957141AF2-008_MTX
Adder
27.929
944201AF1-088_MTX
Adder
55.858
LAGNLTFEXP_LAGN->PJM
CLTF
5.9
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.085
TVALTFEXP_TVA->PJM
CLTF
2.406
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.626
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.398
NYPJM->LTFIMP_NY
CLTF
1.242
LGEELTFEXP_LGEE->PJM
CLTF
1.821
WECLTFEXP_WEC->PJM
CLTF
2.632
AG2-052LTFEXP_AG2-052->PJM
LTF
0.166
AH1-155LTFEXP_AH1-155->PJM
LTF
0.248
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.501
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.201
MECLTFEXP_MEC->PJM
CLTF
9.671
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2267.59
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
6.054
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
0.992
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
965421AG1-410 GEN
Solar/Wind Harmer
6.822
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
965431AG1-411 GEN
50/50
45.479
24727205RPMNG3
50/50
68.971
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
24727005RPMNG1
50/50
68.971
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
24727105RPMNG2
50/50
68.971
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
957141AF2-008_MTX
Adder
27.935
944201AF1-088_MTX
Adder
55.87
990497J1323
External Queue
0
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
TVALTFEXP_TVA->PJM
CLTF
2.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
NYPJM->LTFIMP_NY
CLTF
1.226
LGEELTFEXP_LGEE->PJM
CLTF
1.819
WECLTFEXP_WEC->PJM
CLTF
2.651
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
MECLTFEXP_MEC->PJM
CLTF
9.7
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2267.56
MW Contribution:0.48
Bus #Bus NameTypeMW Contribution
24729205KEY G1
50/50
6.754
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.936
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
8.261
270004AE1-209 GEN
Solar/Wind Harmer
6.463
274872LEEDK;1U
Solar/Wind Harmer
0.181
270180AB1-006 GEN1
Solar/Wind Harmer
9.562
24791305MDL-5G
Solar/Wind Harmer
3.365
959081AF2-199 GEN
Solar/Wind Harmer
0.406
971475AH1-234 GEN
Solar/Wind Harmer
0.898
276646AC1-214 GEN2
Solar/Wind Harmer
1.683
24386205FR-12G C
Solar/Wind Harmer
3.179
276726Z2-087_GEN
Solar/Wind Harmer
10.052
965021AG1-366 GEN
Solar/Wind Harmer
4.602
958861AF2-177 GEN
Solar/Wind Harmer
15.941
945371AF1-202 GEN
Solar/Wind Harmer
7.519
276893AG1-478 C
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.242
270594AE1-207 GEN
Solar/Wind Harmer
0.66
270032AE2-172
Solar/Wind Harmer
3.298
971997AH1-543 GEN
Solar/Wind Harmer
0.645
276863AD2-134 GEN
Solar/Wind Harmer
2.505
274863CRW1-WTG
Solar/Wind Harmer
7.688
276889AE2-281 GEN
Solar/Wind Harmer
2.603
24691005MDL-2G C
Solar/Wind Harmer
5.104
274856ECOGROVE ;U1
Solar/Wind Harmer
4.705
971549AH1-272 GEN
Solar/Wind Harmer
0.738
276158O29GEN2
Solar/Wind Harmer
5.735
276708O09 GEN2
Solar/Wind Harmer
4.827
246937BC-WTG2
Solar/Wind Helper
5.496
270485AE1-090_GEN
Solar/Wind Helper
0.147
971599AH1-298 GEN
50/50
10.386
960861AF2-377 GEN
50/50
2.413
24729305KEY G2
50/50
6.868
970611AG2-400 GEN
Solar/Wind Harmer
1.15
270071AF1-092 GEN
Solar/Wind Harmer
0.944
970321AG2-212 GEN
Solar/Wind Harmer
0.894
270005AE1-210 C O1
Solar/Wind Harmer
6.463
276602WESTBROOK C
Solar/Wind Harmer
2.858
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.594
276645AC1-214 GEN1
Solar/Wind Harmer
1.683
24387305FR-4G C
Solar/Wind Harmer
4.568
24386605FR-22G C
Solar/Wind Harmer
3.045
24387005FR-3G C
Solar/Wind Harmer
3.015
942111AE2-223 GEN
Solar/Wind Harmer
9.047
960841AF2-375 GEN
Solar/Wind Helper
0.529
965421AG1-410 GEN
Solar/Wind Harmer
6.822
972181SS23-001
Solar/Wind Harmer
0.444
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.311
970289AG2-191 GEN
Solar/Wind Harmer
0.079
24755605MDL-5G
Solar/Wind Harmer
3.365
959091AF2-200 GEN
Solar/Wind Harmer
0.811
946031AF1-268 GEN
Solar/Wind Harmer
0.329
274849CRESCENT ;1U
Solar/Wind Harmer
2.569
274877BISHOP HL;1U
Solar/Wind Harmer
4.523
270349AD2-093_GEN
Solar/Wind Helper
0.383
24727105RPMNG2
50/50
68.971
965651AG1-433 GEN
Solar/Wind Harmer
8.207
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.896
943121AE2-341 GEN
Solar/Wind Harmer
0.633
970291AG2-192 GEN
Solar/Wind Harmer
0.054
970289AG2-191 GEN
Solar/Wind Harmer
0.55
957471AF2-041 GEN
Solar/Wind Harmer
1.217
274848CAMPGROVE;RU
Solar/Wind Harmer
7.073
959341AF2-225 GEN
Solar/Wind Harmer
0.58
957201AF2-014 GEN
Solar/Wind Helper
3.911
270284AF1-227 GEN1
Solar/Wind Helper
0.847
270428AC2-015 C
Solar/Wind Helper
0.344
960971AF2-388 GEN
Solar/Wind Harmer
16.413
970349AG2-230 GEN
Solar/Wind Harmer
0.729
971347AH1-153 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
0.97
961051AF2-396 GEN
Solar/Wind Harmer
7.761
270599AE1-208 GEN
Solar/Wind Harmer
0.373
970245AG2-165 GEN
Solar/Wind Harmer
0.894
972231SS25-0005
Solar/Wind Harmer
0.71
274862TOP CROP ;2U
Solar/Wind Harmer
6.862
970921AG2-575 GEN
Solar/Wind Harmer
0.413
970921AG2-575 GEN
Solar/Wind Harmer
1.652
274879MINONK ;1U
Solar/Wind Harmer
9.667
971411AH1-196 GEN
Solar/Wind Harmer
0.613
274855GSG-6 ;RU
Solar/Wind Harmer
5.182
24386405FR-21G C
Solar/Wind Harmer
3.045
942871AE2-306 GEN
Solar/Wind Helper
0.2
945641AF1-229 GEN
Solar/Wind Helper
0.422
270541AE2-072 C
Solar/Wind Helper
0.42
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.894
970517AG2-330 GEN
Solar/Wind Harmer
13.95
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.467
958821AF2-173 GEN
Solar/Wind Harmer
0.58
962781AG1-127 GEN
Solar/Wind Harmer
0.393
971335AH1-147 GEN
Solar/Wind Harmer
0.816
24697605MDL-3G C
Solar/Wind Harmer
5.096
270181AB1-006 GEN2
Solar/Wind Harmer
0.634
971171AH1-044 GEN
Solar/Wind Harmer
0.811
926823AC1-168 GEN
Solar/Wind Harmer
4.923
24385905FR-11G C
Solar/Wind Harmer
5.987
276782AC1-033 GEN
Solar/Wind Harmer
5.11
24725505WLD G2 C
Solar/Wind Harmer
5.056
946321AF1-296 GEN
Solar/Wind Harmer
11.381
960611AF2-352 GEN
Solar/Wind Harmer
0.992
24727005RPMNG1
50/50
68.971
247620Y3-023
50/50
0.466
965041AG1-368 GEN
Solar/Wind Harmer
0.706
270191TR4_S_V150
Solar/Wind Harmer
6.54
965101AG1-375 GEN
Solar/Wind Harmer
0.511
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.373
971917AH1-482 GEN
Solar/Wind Harmer
6.726
276691AA1-018 GEN1
Solar/Wind Harmer
0.451
970115AG2-085 GEN
Solar/Wind Harmer
0.163
276872AE1-163_GEN1
Solar/Wind Harmer
9.109
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.701
971067AG2-660 GEN
Solar/Wind Harmer
1.622
276741O09 GEN1
Solar/Wind Harmer
4.827
276655WTG1_EQ
Solar/Wind Harmer
6.657
270578AF1-285 GEN2
Solar/Wind Helper
0.267
247522W1-056 GEN
Solar/Wind Helper
1.806
270286AF1-227 GEN2
Solar/Wind Helper
0.313
961961AG1-039 GEN
Solar/Wind Helper
0.152
241960AC2-195 GEN
Solar/Wind Helper
0.26
971617AH1-308 GEN
Solar/Wind Harmer
5.201
943021AE2-325 GEN
Solar/Wind Harmer
2.992
958011AF2-095 GEN
Solar/Wind Harmer
0.623
971573AH1-285 GEN
Solar/Wind Harmer
0.361
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.621
942991AE2-321 GEN
Solar/Wind Harmer
0.41
971333AH1-146 GEN
Solar/Wind Harmer
0.816
24697905MDL-4G C
Solar/Wind Harmer
3.365
970819AG2-516 GEN
Solar/Wind Harmer
0.483
964611AG1-324 GEN
Solar/Wind Harmer
0.357
270201AC2-176 GEN
Solar/Wind Harmer
6.697
274851PROVIDENC;RU
Solar/Wind Harmer
3.718
274878BISHOP HL;2U
Solar/Wind Harmer
4.523
24699105WLD G1 C
Solar/Wind Harmer
5.025
270499AE1-146 GEN
Solar/Wind Helper
0.511
970615AG2-402 GEN
50/50
4.602
24729405KEY G3
50/50
6.868
24729505KEY G4
50/50
6.754
270043AE2-236 GEN
Solar/Wind Harmer
0.373
971771AH1-392 GEN
Solar/Wind Harmer
0.442
270505AE1-170 C O1
Solar/Wind Harmer
0.728
274888KELLY CRK;1U
Solar/Wind Harmer
8.779
970941AG2-585 GEN
Solar/Wind Harmer
0.541
971605AH1-302 GEN
Solar/Wind Harmer
6.341
276805AD2-038 GEN
Solar/Wind Harmer
7.5
274850MENDOTA H;RU
Solar/Wind Harmer
3.67
276861AD2-134 GEN
Solar/Wind Harmer
2.505
274864CRW2-WTG
Solar/Wind Harmer
7.688
970569AG2-363 GEN
Solar/Wind Harmer
1.205
274858EASY ROAD;U2
Solar/Wind Harmer
6.231
276157O29GEN1
Solar/Wind Harmer
5.735
957751AF2-069 GEN
Solar/Wind Harmer
0.514
939741AE1-205 GEN
Solar/Wind Harmer
0.773
246938BC-WTG3
Solar/Wind Helper
5.433
246936BC-WTG1
Solar/Wind Helper
5.496
970583AG2-370 GEN
50/50
2.823
970031AG2-029 GEN
Solar/Wind Harmer
2.112
270247TR4_N_V136
Solar/Wind Harmer
1.186
965051AG1-369 GEN
Solar/Wind Harmer
0.301
960591AF2-350 GEN
Solar/Wind Harmer
0.432
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
8.088
939401AE1-172 GEN
Solar/Wind Harmer
16.42
276876AE1-163_GEN2
Solar/Wind Harmer
9.109
274857EASY ROAD;U1
Solar/Wind Harmer
6.231
961761AG1-017 GEN
Solar/Wind Harmer
0.391
276656WTG2_EQ
Solar/Wind Harmer
0.882
941731AE2-173 GEN
Solar/Wind Harmer
3.866
270462AD2-086
Solar/Wind Helper
1.688
270317AD1-130_GEN
Solar/Wind Helper
1.101
270287AF1-227 GEN3
Solar/Wind Helper
0.313
944531AF1-118 GEN
Solar/Wind Harmer
2.062
274887GEN-1.85
Solar/Wind Harmer
8.065
970707AG2-453 GEN
Solar/Wind Harmer
1.203
970833AG2-524 GEN
Solar/Wind Harmer
3.74
958481AF2-142 GEN
Solar/Wind Harmer
0.629
276868AE1-113 GEN
Solar/Wind Harmer
13.822
971675AH1-338 GEN
Solar/Wind Harmer
0.735
960791AF2-370 GEN
Solar/Wind Harmer
1.628
970781AG2-491 GEN
Solar/Wind Harmer
0.406
276903AD2-071 C
Solar/Wind Harmer
0.395
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.371
270224U2-072_GEN2
Solar/Wind Helper
0.133
270391AF1-285 GEN3
Solar/Wind Helper
0.267
241847AF2-150_GEN
Solar/Wind Helper
0.239
965011AG1-365 GEN
Solar/Wind Harmer
1.15
945111AF1-176 GEN
Solar/Wind Harmer
0.888
945111AF1-176 GEN
Solar/Wind Harmer
4.84
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.472
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
43.926
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.24
970825AG2-519 GEN
Solar/Wind Harmer
0.448
970825AG2-519 GEN
Solar/Wind Harmer
1.72
970571AG2-364 GEN
Solar/Wind Harmer
0.803
971681AH1-341 GEN
Solar/Wind Harmer
0.599
938861AE1-114 GEN
Solar/Wind Harmer
9.335
276603SUBLETTE C
Solar/Wind Harmer
1.356
253378AE2-206_GEN
Solar/Wind Helper
0.312
959331AF2-224 GEN
Solar/Wind Harmer
1.15
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
5.09
276843GEN-1.7
Solar/Wind Harmer
0.714
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.948
276882AE2-255 GEN
Solar/Wind Harmer
4.361
960441AF2-335 GEN
Solar/Wind Harmer
0.407
270223U2-072_GEN1
Solar/Wind Helper
0.133
966831AG1-554 GEN
Solar/Wind Helper
0.265
274854TWINGROVE;U2
Solar/Wind Harmer
6.054
965431AG1-411 GEN
50/50
45.479
24727205RPMNG3
50/50
68.971
24639705ELKHART HY
50/50
0.15
963791AG1-232 GEN
Solar/Wind Harmer
0.972
270246TR4_N_V150
Solar/Wind Harmer
1.186
24695305TIMB G C
Solar/Wind Harmer
9.919
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.578
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.422
965031AG1-367 GEN
Solar/Wind Harmer
0.414
276901AD2-066 C O1
Solar/Wind Harmer
0
971343AH1-151 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
0.401
961011AF2-392 GEN
Solar/Wind Harmer
12.249
270227U2-072_GEN3
Solar/Wind Helper
0.133
270228U2-072_GEN4
Solar/Wind Helper
0.133
276820AF1-078_GEN
Solar/Wind Helper
0.141
970521AG2-332 GEN
50/50
10.877
247521TR3_G114
Solar/Wind Harmer
8.771
276806AD2-047 C O1
Solar/Wind Harmer
13.32
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.573
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.5
971341AH1-150 GEN
Solar/Wind Harmer
0.811
270302AB2-170 GEN
Solar/Wind Helper
1.101
270231U2-072_GEN5
Solar/Wind Helper
0.133
270471AD2-092_GEN
Solar/Wind Helper
0.383
957141AF2-008_MTX
Adder
27.935
944201AF1-088_MTX
Adder
55.87
990497J1323
External Queue
0
LAGNLTFEXP_LAGN->PJM
CLTF
5.747
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.599
TVALTFEXP_TVA->PJM
CLTF
2.31
CBM West 2LTFEXP_CBM-W2->PJM
CBM
51.154
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.037
NYPJM->LTFIMP_NY
CLTF
1.226
LGEELTFEXP_LGEE->PJM
CLTF
1.819
WECLTFEXP_WEC->PJM
CLTF
2.651
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.014
AG2-052LTFEXP_AG2-052->PJM
LTF
0.167
AH1-155LTFEXP_AH1-155->PJM
LTF
0.251
CBM West 1LTFEXP_CBM-W1->PJM
CBM
73.505
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.901
MECLTFEXP_MEC->PJM
CLTF
9.7
SIGELTFEXP_SIGE->PJM
CLTF
0.2

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.94 %
Rating:2219.0 MVA
Rating Type:B
MVA to Mitigate:2262.15
MW Contribution:0.47
Bus #Bus NameTypeMW Contribution
959331AF2-224 GEN
Solar/Wind Harmer
1.126
944541AF1-119 GEN
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
4.913
276843GEN-1.7
Solar/Wind Harmer
0.69
941551AE2-152 GEN
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
11.537
276882AE2-255 GEN
Solar/Wind Harmer
4.21
960441AF2-335 GEN
Solar/Wind Harmer
0.39
270223U2-072_GEN1
Solar/Wind Helper
0.148
966831AG1-554 GEN
Solar/Wind Helper
0.282
274854TWINGROVE;U2
Solar/Wind Harmer
5.038
24729205KEY G1
50/50
6.542
270526AF1-158 GEN
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
0.904
964401AG1-302 GEN
Solar/Wind Harmer
0
274861TOP CROP ;1U
Solar/Wind Harmer
7.977
270004AE1-209 GEN
Solar/Wind Harmer
6.21
274872LEEDK;1U
Solar/Wind Harmer
0.175
270180AB1-006 GEN1
Solar/Wind Harmer
9.228
24791305MDL-5G
Solar/Wind Harmer
3.247
959081AF2-199 GEN
Solar/Wind Harmer
0.392
971475AH1-234 GEN
Solar/Wind Harmer
0.867
276646AC1-214 GEN2
Solar/Wind Harmer
1.624
24386205FR-12G C
Solar/Wind Harmer
3.066
276726Z2-087_GEN
Solar/Wind Harmer
9.698
960971AF2-388 GEN
Solar/Wind Harmer
15.869
970349AG2-230 GEN
Solar/Wind Harmer
0.705
971347AH1-153 GEN
Solar/Wind Harmer
0.705
961051AF2-396 GEN
Solar/Wind Harmer
0.936
961051AF2-396 GEN
Solar/Wind Harmer
7.484
270599AE1-208 GEN
Solar/Wind Harmer
0.359
970245AG2-165 GEN
Solar/Wind Harmer
0.864
972231SS25-0005
Solar/Wind Harmer
0.686
274862TOP CROP ;2U
Solar/Wind Harmer
6.626
970921AG2-575 GEN
Solar/Wind Harmer
0.399
970921AG2-575 GEN
Solar/Wind Harmer
1.595
274879MINONK ;1U
Solar/Wind Harmer
9.334
971411AH1-196 GEN
Solar/Wind Harmer
0.592
274855GSG-6 ;RU
Solar/Wind Harmer
5.004
24386405FR-21G C
Solar/Wind Harmer
2.937
942871AE2-306 GEN
Solar/Wind Helper
0.222
945641AF1-229 GEN
Solar/Wind Helper
0.452
270541AE2-072 C
Solar/Wind Helper
0.467
24653605MOTTVILLE
50/50
0.003
965011AG1-365 GEN
Solar/Wind Harmer
1.126
945111AF1-176 GEN
Solar/Wind Harmer
0.857
945111AF1-176 GEN
Solar/Wind Harmer
4.67
957891AF2-083 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
42.42
940581AE2-045 GEN
Solar/Wind Harmer
0
971177AH1-047 GEN
Solar/Wind Harmer
0.232
970571AG2-364 GEN
Solar/Wind Harmer
0.776
970825AG2-519 GEN
Solar/Wind Harmer
0.43
970825AG2-519 GEN
Solar/Wind Harmer
1.65
971599AH1-298 GEN
50/50
10.098
960861AF2-377 GEN
50/50
2.301
24729305KEY G2
50/50
6.653
970611AG2-400 GEN
Solar/Wind Harmer
1.126
270071AF1-092 GEN
Solar/Wind Harmer
0.917
970321AG2-212 GEN
Solar/Wind Harmer
0.864
270005AE1-210 C O1
Solar/Wind Harmer
6.21
276602WESTBROOK C
Solar/Wind Harmer
2.759
276645AC1-214 GEN1
Solar/Wind Harmer
1.624
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
0.566
24387305FR-4G C
Solar/Wind Harmer
4.405
24386605FR-22G C
Solar/Wind Harmer
2.937
24387005FR-3G C
Solar/Wind Harmer
2.908
942111AE2-223 GEN
Solar/Wind Harmer
8.728
960841AF2-375 GEN
Solar/Wind Helper
0.566
971681AH1-341 GEN
Solar/Wind Harmer
0.578
938861AE1-114 GEN
Solar/Wind Harmer
9.013
276603SUBLETTE C
Solar/Wind Harmer
1.309
253378AE2-206_GEN
Solar/Wind Helper
0.35
970615AG2-402 GEN
50/50
4.505
24729405KEY G3
50/50
6.653
24729505KEY G4
50/50
6.542
270043AE2-236 GEN
Solar/Wind Harmer
0.362
971771AH1-392 GEN
Solar/Wind Harmer
0.427
270505AE1-170 C O1
Solar/Wind Harmer
0.702
274888KELLY CRK;1U
Solar/Wind Harmer
8.479
970941AG2-585 GEN
Solar/Wind Harmer
0.522
971605AH1-302 GEN
Solar/Wind Harmer
6.121
276805AD2-038 GEN
Solar/Wind Harmer
7.241
274850MENDOTA H;RU
Solar/Wind Harmer
3.544
276861AD2-134 GEN
Solar/Wind Harmer
2.419
274864CRW2-WTG
Solar/Wind Harmer
7.421
970569AG2-363 GEN
Solar/Wind Harmer
1.163
274858EASY ROAD;U2
Solar/Wind Harmer
6.016
276157O29GEN1
Solar/Wind Harmer
5.536
957751AF2-069 GEN
Solar/Wind Harmer
0.496
939741AE1-205 GEN
Solar/Wind Harmer
0.746
246938BC-WTG3
Solar/Wind Helper
5.504
246936BC-WTG1
Solar/Wind Helper
5.567
965021AG1-366 GEN
Solar/Wind Harmer
4.505
958861AF2-177 GEN
Solar/Wind Harmer
15.401
945371AF1-202 GEN
Solar/Wind Harmer
7.254
276893AG1-478 C
Solar/Wind Harmer
0
962691AG1-118 GEN
Solar/Wind Harmer
1.199
957841AF2-078 GEN
Solar/Wind Harmer
0
270594AE1-207 GEN
Solar/Wind Harmer
0.634
270032AE2-172
Solar/Wind Harmer
3.17
971997AH1-543 GEN
Solar/Wind Harmer
0.623
276863AD2-134 GEN
Solar/Wind Harmer
2.419
274863CRW1-WTG
Solar/Wind Harmer
7.421
276889AE2-281 GEN
Solar/Wind Harmer
2.513
24691005MDL-2G C
Solar/Wind Harmer
4.926
274856ECOGROVE ;U1
Solar/Wind Harmer
4.543
971549AH1-272 GEN
Solar/Wind Harmer
0.704
276158O29GEN2
Solar/Wind Harmer
5.536
276708O09 GEN2
Solar/Wind Harmer
4.66
246937BC-WTG2
Solar/Wind Helper
5.567
270485AE1-090_GEN
Solar/Wind Helper
0.16
944531AF1-118 GEN
Solar/Wind Harmer
1.998
274887GEN-1.85
Solar/Wind Harmer
7.789
970707AG2-453 GEN
Solar/Wind Harmer
1.162
970833AG2-524 GEN
Solar/Wind Harmer
3.611
958481AF2-142 GEN
Solar/Wind Harmer
0.607
276868AE1-113 GEN
Solar/Wind Harmer
13.346
971675AH1-338 GEN
Solar/Wind Harmer
0.709
970781AG2-491 GEN
Solar/Wind Harmer
0.392
960791AF2-370 GEN
Solar/Wind Harmer
1.562
276903AD2-071 C
Solar/Wind Harmer
0.38
966841AG1-555 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
9.04
270224U2-072_GEN2
Solar/Wind Helper
0.148
270391AF1-285 GEN3
Solar/Wind Helper
0.296
241847AF2-150_GEN
Solar/Wind Helper
0.259
270063AE2-323 C
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
0.864
970517AG2-330 GEN
Solar/Wind Harmer
13.48
959141AF2-205 GEN
Solar/Wind Harmer
0
970833AG2-524 GEN
Solar/Wind Harmer
0.451
962781AG1-127 GEN
Solar/Wind Harmer
0.379
958821AF2-173 GEN
Solar/Wind Harmer
0.557
971335AH1-147 GEN
Solar/Wind Harmer
0.788
24697605MDL-3G C
Solar/Wind Harmer
4.918
270181AB1-006 GEN2
Solar/Wind Harmer
0.612
971171AH1-044 GEN
Solar/Wind Harmer
0.783
926823AC1-168 GEN
Solar/Wind Harmer
4.753
24385905FR-11G C
Solar/Wind Harmer
5.774
276782AC1-033 GEN
Solar/Wind Harmer
4.932
24725505WLD G2 C
Solar/Wind Harmer
4.854
946321AF1-296 GEN
Solar/Wind Harmer
10.986
958581AF2-149 GEN
Solar/Wind Helper
0.21
960611AF2-352 GEN
Solar/Wind Harmer
0.826
970583AG2-370 GEN
50/50
2.718
970031AG2-029 GEN
Solar/Wind Harmer
2.053
270247TR4_N_V136
Solar/Wind Harmer
1.13
965051AG1-369 GEN
Solar/Wind Harmer
0.287
960591AF2-350 GEN
Solar/Wind Harmer
0.418
958381AF2-132 GEN
Solar/Wind Harmer
0
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
7.81
939401AE1-172 GEN
Solar/Wind Harmer
15.852
276876AE1-163_GEN2
Solar/Wind Harmer
8.794
274857EASY ROAD;U1
Solar/Wind Harmer
6.016
961761AG1-017 GEN
Solar/Wind Harmer
0.372
276656WTG2_EQ
Solar/Wind Harmer
0.85
941731AE2-173 GEN
Solar/Wind Harmer
3.73
270462AD2-086
Solar/Wind Helper
1.844
270317AD1-130_GEN
Solar/Wind Helper
1.203
270287AF1-227 GEN3
Solar/Wind Helper
0.376
965421AG1-410 GEN
Solar/Wind Harmer
6.722
972181SS23-001
Solar/Wind Harmer
0.429
270055AF2-134 C O1
Solar/Wind Harmer
0
972207SS24-0001
Solar/Wind Harmer
1.267
970289AG2-191 GEN
Solar/Wind Harmer
0.076
24755605MDL-5G
Solar/Wind Harmer
3.247
959091AF2-200 GEN
Solar/Wind Harmer
0.783
946031AF1-268 GEN
Solar/Wind Harmer
0.315
274849CRESCENT ;1U
Solar/Wind Harmer
2.48
274877BISHOP HL;1U
Solar/Wind Harmer
4.366
270349AD2-093_GEN
Solar/Wind Helper
0.507
965431AG1-411 GEN
50/50
44.816
24727205RPMNG3
50/50
67.91
24639705ELKHART HY
50/50
0.145
963791AG1-232 GEN
Solar/Wind Harmer
0.942
270246TR4_N_V150
Solar/Wind Harmer
1.13
24695305TIMB G C
Solar/Wind Harmer
9.393
270024AE2-089 GEN
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
0.558
270535AF1-215 GEN1
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.408
276901AD2-066 C O1
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
0.398
971343AH1-151 GEN
Solar/Wind Harmer
0.783
970169AG2-114 GEN
Solar/Wind Harmer
0.387
961011AF2-392 GEN
Solar/Wind Harmer
11.826
270227U2-072_GEN3
Solar/Wind Helper
0.148
270228U2-072_GEN4
Solar/Wind Helper
0.148
276820AF1-078_GEN
Solar/Wind Helper
0.158
970521AG2-332 GEN
50/50
10.52
247521TR3_G114
Solar/Wind Harmer
8.362
276806AD2-047 C O1
Solar/Wind Harmer
12.864
958391AF2-133 GEN
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
7.313
247642Z2-115 C
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.481
971341AH1-150 GEN
Solar/Wind Harmer
0.783
24727005RPMNG1
50/50
67.91
247620Y3-023
50/50
0.451
965041AG1-368 GEN
Solar/Wind Harmer
0.679
270191TR4_S_V150
Solar/Wind Harmer
6.235
965101AG1-375 GEN
Solar/Wind Harmer
0.494
960681AF2-359 GEN
Solar/Wind Harmer
0
270031AE2-169
Solar/Wind Harmer
0.359
971917AH1-482 GEN
Solar/Wind Harmer
6.492
276691AA1-018 GEN1
Solar/Wind Harmer
0.436
276872AE1-163_GEN1
Solar/Wind Harmer
8.794
946581AF1-322 GEN
Solar/Wind Harmer
0
24690905MDL-1G C
Solar/Wind Harmer
10.326
971067AG2-660 GEN
Solar/Wind Harmer
1.567
970115AG2-085 GEN
Solar/Wind Harmer
0.156
276741O09 GEN1
Solar/Wind Harmer
4.66
276655WTG1_EQ
Solar/Wind Harmer
6.423
270578AF1-285 GEN2
Solar/Wind Helper
0.296
270286AF1-227 GEN2
Solar/Wind Helper
0.376
247522W1-056 GEN
Solar/Wind Helper
1.925
961961AG1-039 GEN
Solar/Wind Helper
0.165
241960AC2-195 GEN
Solar/Wind Helper
0.292
270302AB2-170 GEN
Solar/Wind Helper
1.203
270231U2-072_GEN5
Solar/Wind Helper
0.148
270471AD2-092_GEN
Solar/Wind Helper
0.507
971617AH1-308 GEN
Solar/Wind Harmer
4.999
943021AE2-325 GEN
Solar/Wind Harmer
2.884
958011AF2-095 GEN
Solar/Wind Harmer
0.601
971573AH1-285 GEN
Solar/Wind Harmer
0.349
945421AF1-207 GEN
Solar/Wind Harmer
0
958491AF2-143 GEN
Solar/Wind Harmer
0.599
942991AE2-321 GEN
Solar/Wind Harmer
0.396
971333AH1-146 GEN
Solar/Wind Harmer
0.788
24697905MDL-4G C
Solar/Wind Harmer
3.247
970819AG2-516 GEN
Solar/Wind Harmer
0.466
274851PROVIDENC;RU
Solar/Wind Harmer
3.588
964611AG1-324 GEN
Solar/Wind Harmer
0.34
270201AC2-176 GEN
Solar/Wind Harmer
6.374
274878BISHOP HL;2U
Solar/Wind Harmer
4.366
24699105WLD G1 C
Solar/Wind Harmer
4.824
965931AG1-462 GEN
Solar/Wind Harmer
0.935
270499AE1-146 GEN
Solar/Wind Helper
0.547
24727105RPMNG2
50/50
67.91
965651AG1-433 GEN
Solar/Wind Harmer
7.934
270449AD2-020 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
9.557
943121AE2-341 GEN
Solar/Wind Harmer
0.611
970291AG2-192 GEN
Solar/Wind Harmer
0.052
970289AG2-191 GEN
Solar/Wind Harmer
0.529
957471AF2-041 GEN
Solar/Wind Harmer
1.175
274848CAMPGROVE;RU
Solar/Wind Harmer
6.827
959341AF2-225 GEN
Solar/Wind Harmer
0.56
957201AF2-014 GEN
Solar/Wind Helper
3.962
270284AF1-227 GEN1
Solar/Wind Helper
1.019
270428AC2-015 C
Solar/Wind Helper
0.368
253383AE2-342_GEN
Solar/Wind Helper
0.101
957141AF2-008_MTX
Adder
26.838
944201AF1-088_MTX
Adder
53.676
LAGNLTFEXP_LAGN->PJM
CLTF
5.561
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.712
TVALTFEXP_TVA->PJM
CLTF
2.237
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.277
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
23.26
NYPJM->LTFIMP_NY
CLTF
1.178
LGEELTFEXP_LGEE->PJM
CLTF
1.703
WECLTFEXP_WEC->PJM
CLTF
2.559
AG2-052LTFEXP_AG2-052->PJM
LTF
0.161
AH1-155LTFEXP_AH1-155->PJM
LTF
0.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.912
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.562
MECLTFEXP_MEC->PJM
CLTF
9.361
SIGELTFEXP_SIGE->PJM
CLTF
0.191
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7334_05JEFRSO 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 242865 TO BUS 243208 CKT 2    /*05JEFRSO     345.0 - 05JEFRSO     765.0
 OPEN BRANCH FROM BUS 242865 TO BUS 248000 CKT 1    /*05JEFRSO     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#1760_05JEFRSO 765_A_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290599 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RG 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 970238 TO BUS 290599 CKT 1    /*AG2-162 TP   765.0 - 05JEFFRSN_RG 765.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
243211 to 242933 ckt 1
243206 to 290606 ckt Z1
243208 to 242865 ckt 2
242865 to 248000 ckt 1
290608 to 242928 ckt Z1
242933 to 965420 ckt 1
965420 to 246929 ckt 1

Light Load Analysis

The New Service Request AG2-516 was evaluated as a 120.0 MW injection

AG2-516 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 120.0 MW (120.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-038Lexington-Low Moor 230kVUnder Construction
AB1-006Meadow Lake 345kVIn Service
AB1-027Old Church 34.5 KVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB1-150Grassy Falls 138kVIn Service
AB1-180Pine View 12kVIn Service
AB2-026Powhatan 34.5kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-045Buckingham 34.5kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-001Delano 138kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-075Perth-Hickory Grove 115kVIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-118Westmoreland 34.5kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-191Elmont 115kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-123Jacksons Ferry 138kVIn Service
AC2-137Elko 34.5kVIn Service
AC2-138Northern Neck 34.5kVIn Service
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-165Bremo-Powhatan 230kVSuspended
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-063Harmony Village 34.5 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-105Kings Dominion DP 115 kVUnder Construction
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-073Sanders DP 230 kVIn Service
AD2-074Garner DP-Lancaster 115 kVEngineering & Procurement
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AD2-194Elwood 345 kVPartially in Service - Under Construction
AE1-040Greenfield 69 kVIn Service
AE1-074Winterpock 34.5 kVUnder Construction
AE1-075Powhatan 34.5 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-100Axton 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-143Marion County 161 kVEngineering & Procurement
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-155Garner-Northern Neck 115 kVIn Service
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-176Roanoke-Vinton 12 kV (Niagara Hydro)In Service
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-029Grottoes-Merck 115kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-092Kidds Store-Sherwood 115 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-291Grit DP-Perth 115 kVActive
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-042Garner DP-Lancaster 115 kVEngineering & Procurement
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-031CalumetEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-107Clifford 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-144Powhatan 34.5 kVIn Service
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-187Brookside-Cloverdale 138 kVEngineering & Procurement
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-226Katydid Road 345 kVActive
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-311Gilboa-Jones Branch 138 kVEngineering & Procurement
AF2-316Gilboa-Jones Branch 138 kV IIEngineering & Procurement
AF2-319Katydid Road 345 kVActive
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-366Crego Rd 138 kVEngineering & Procurement
AF2-370Delaware-Royerton 138 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-382Hurley 69 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-407Fall Creek 345 kVActive
AF2-408Fall Creek 138 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AF2-441Burnham 138kVActive
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-066Bonnyman 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-282Dunnsville 34.5 kVEngineering & Procurement
AG1-297Hanna-Tanners Creek 345 kVActive
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-494Boxwood-Riverville 138 kVActive
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-512University Park North 345 kVWithdrawn
AG1-513Aurora 138 kVSuspended
AG1-526West Garrard 345 kVActive
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-558Buckner 34.5 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-014Meadow Lake 345 kVActive
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-111Perth 34.5 kV Substation (Circuit 408)Active
AG2-112Perth 34.5 kV Substation (Circuit 404)Active
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-152Banister-Bear Skin 138 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-310Matt Funk 138 kVActive
AG2-311Smith Mountain 138 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-343Eugene - Dequine 345 kVActive
AG2-344Dequine 345 bkVActive
AG2-345Eugene - Dequine 345 kVActive
AG2-360Broadford 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-492Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-518Tech Drive 138 kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-562Elderberry 345 kVActive
AG2-564Sulphur Springs 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AG2-675Cordova 345 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-269Claytor 138 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-563Aurora E.C. 138kVActive
AH1-564Rockford II 138 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-673State Line - River Energy Center 138 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-073Yankee 12.5kVIn Service
W1-056Ada-Dunkirk 69kVIn Service
W2-048Brokaw-LanesvilleIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)Identified Impacts

No cost allocated AFS Tie Line reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.


System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC2_18494
Title
Reconductor 2.9 miles of overhead line to 2-795 ACSS@ 250°C.
Description
Reconductor 2.9 miles of overhead line to 2-795 ACSS@ 250°C.
Total Cost ($USD)
$6,000,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9113.0
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
n9113.0 / NIPS_TC1_12093
Title
Upgrade 2000A wave trap and line switch at Green Acres substation.
Description
Upgrade wave trap and M.O. at GreenAcres substation. Current MISO end ratings are Rate A = 1195 and Rate B = 1195 MVA
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05OLIVE-17P9700-EAST 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AMIL
RTEP ID / TO ID
(Pending) / AMIL_TC2_18783
Title
Build second 345 kV line between Snyder (J1180 POI) and Sullivan
Description
Build second 345 kV line between Snyder (J1180 POI) and Sullivan. For Ameren's portion of line, river crossing needed for this upgrade. Estimating 5 miles long.
Total Cost ($USD)
$59,202,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05SULLIVAN-7SNYDER 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9133.0
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
n9133.0 / NIPS_TC1_15152
Title
NIPS SN/SE ratings of 2133/2577 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor.
Description
NIPS SN/SE ratings of 2133/2577 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor.
Total Cost ($USD)
$1,800,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
17MUNSTER-BURNHAM ;0R 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC1_15151
Title
NIPS SN/SE ratings of 1538/1877 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor and change out of 2156 ACSR conductor drop with 3000 AL conductor
Description
NIPS SN/SE ratings of 1538/1877 MVA achieved by change out of 2156 ACSR line conductor with 2-1590 ACSR conductor and change out of 2156 ACSR conductor drop with 3000 AL conductor
Total Cost ($USD)
$6,200,000
Allocated Cost ($USD)
$0
Time Estimate
TBD

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
17SHEFFIELD-BURNHAM ; B 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
NIPS
RTEP ID / TO ID
(Pending) / NIPS_TC2_18520
Title
Existing NIPS rating: SN/SE: 1538/1877 MVA
Description
Existing NIPS rating: SN/SE: 1538/1877 MVA
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line(Any)

New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Study Pending
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.a
Title
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Description
Upgrade (4) 1024.5 ACAR 24/13 sub conductors at Davis Besse
Total Cost ($USD)
$1,099,401
Allocated Cost ($USD)
$0
Time Estimate
14 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.g
Title
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV circuit breakers at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$7,786,806
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.i
Title
Upgrade B34544 CT at BAYSHORE
Description
Upgrade B34544 CT at BAYSHORE
Total Cost ($USD)
$712,356
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.d
Title
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends
Description
Reconductor (possible rebuild) 345kV 20.75 miles of transmission line and line drops at both remote ends using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$121,594,776
Allocated Cost ($USD)
$0
Time Estimate
71 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.j
Title
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Description
Upgrade (1) 1590 ACSR 45/7 sub conductor at Davis Besse
Total Cost ($USD)
$393,871
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.h
Title
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Description
Upgrade (8) 1590 AAC 61 sub conductor at BAYSHORE
Total Cost ($USD)
$211,119
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.c
Title
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Description
Upgrade 345kV 1033.5 AAC 61 sub conductors at Davis Besse substation at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.f
Title
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Description
Upgrade (2) 345kV Wave Traps at Bayshore and (2) at Davis Besse
Total Cost ($USD)
$1,215,694
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.k
Title
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Description
Upgrade the B34545 and 34562 (4) Meter and (2) Relay Thermals at Bayshore and Davis Besse
Total Cost ($USD)
$998,835
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.b
Title
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Description
Upgrade (3) 345kV bus and line side disconnect switches at Davis Besse substation at Davis Besse
Total Cost ($USD)
$1,324,127
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-002.e
Title
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Description
Upgrade 345kV 3500 SAC 127 sub conductor at Davis Besse
Total Cost ($USD)
$257,762
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BAY SH-02DAV-BE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.j
Title
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Description
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.b
Title
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Description
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.e
Title
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Description
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.d
Title
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Description
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Total Cost ($USD)
$7,937,520
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.f
Title
Upgrade the B6 CT at Hayes
Description
Upgrade the B6 CT at Hayes
Total Cost ($USD)
$727,300
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.g
Title
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)
Description
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3) using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.i
Title
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Description
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.a
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$175,902,477
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.h
Title
Upgrade the B88 and B115 CTs at Beaver
Description
Upgrade the B88 and B115 CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.c
Title
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Description
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Total Cost ($USD)
$729,124
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.i
Title
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Description
Upgrade (2) 9.6 Ohms impedance relays at Hayes and (2) 12.9 Ohms impedance relays at Davis Besse
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.h
Title
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Description
Upgrade B66 (1) meter and (1) relay thermals and B67 (1) meter thermal at Davis Besse substation
Total Cost ($USD)
$852,462
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.c
Title
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Description
Upgrade (2) Wave Traps at Davis Besse and (2) Wave Traps at Hayes
Total Cost ($USD)
$1,215,695
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.e
Title
Upgrade (2) B12 and B18 CTs at Hayes
Description
Upgrade (2) B12 and B18 CTs at Hayes
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.g
Title
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Description
Upgrade B66 and B67 circuit breakers at Davis Besse substation
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.a
Title
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line
Description
Reconductor (possible rebuild) 30.25 miles of 954 ACSR 48/7 transmission line and line drops (line drops at Davis Besse) on the Davis Besse-Hayes 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$179,916,169
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.f
Title
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Description
Upgrade (10) 1590 ACSR sub conductor (B66 and B67 breaker leads, wave trap subconductor, Overheadline-34625) at Davis Besse and B12 breaker leads at Hayes
Total Cost ($USD)
$305,149
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.d
Title
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Description
Upgrade (2) B18 & B12 345 kV Ciruit Breakers at Hayes
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.b
Title
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Description
Upgrade 3500 SAC 127 OVERHEAD PIPE to disc sw. 34625 at Davis Besse and B18 breaker leads at Hayes
Total Cost ($USD)
$284,061
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-006.j
Title
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Description
Upgrade (6) disconnect switches at Davis Besse (D27,28,29,30,34625,37) and (5) disconnect switches at Hayes (D20,19,16,13,14)
Total Cost ($USD)
$4,525,814
Allocated Cost ($USD)
$0
Time Estimate
31 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$0
Time Estimate
73 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement: n6600
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n6600 / AEPI0001a
Title
Replace Dumont Circuit Breaker B1
Description
Replace Dumont Circuit Breaker B1 [Breaker (3000A) Non oil - Dumont]
Total Cost ($USD)
$3,900,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05DUMONT_RW 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18677
Title
05DUMONT_RW 765.0 kV to 05DUMONT 765.0 kV ckt Z1 - Replace Breaker
Description
Replace 765kV CB B at Dumont
Total Cost ($USD)
$4,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05DUMONT_RW 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18798
Title
05ELDERBERRY 345kV – 05DUMONT 345kV ckt 1 - Rebuild
Description
Rebuild ~14.27 miles of 345kV line from Elderberry to Dumont utilizing 2-1590 FALCON ACSR 54/19. At Dumont, replace the 2-1700 KCM AAC 61 str station conductor and the wavetrap facing Elderberry, and CB G2. At Elderberry, replace the wavetrap facing Dumont
Total Cost ($USD)
$44,100,000
Allocated Cost ($USD)
$0
Time Estimate
60 to 72 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05ELDERBERRY 345.0 kV Ckt 1 line(Any)

System Reinforcement: n7619.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7619.1 / AEPI0032a
Title
Replace 3000A non oil Circuit Breaker at Dumont
Description
Total Cost ($USD)
$1,300,000
Allocated Cost ($USD)
$0
Time Estimate
18 to 24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05ELDERBERRY 345.0 kV Ckt 1 line(Any)

System Reinforcement: n7619.2
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7619.2 / AEPI0032b
Title
Reconductor/Rebuild 14 miles of ACSR ~ 954 ~ 45/7 ~ RAIL Dumont - Elderberry 345kV line
Description
Reconductor/Rebuild 14 miles of ACSR ~ 954 ~ 45/7 ~ RAIL Dumont - Elderberry 345kV line
Total Cost ($USD)
$28,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-05ELDERBERRY 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18670
Title
17STILLWELL 345.0 kV to 05DUMONT 345.0 kV ckt 1 - Reconductor and Replace Equipment
Description
Rebuild ~8.62 miles of AEP owned 345kV line from Dumont to Stillwell utilizing 3-954 CARDINAL ACSR 54/7. At Dumont, replace the 2-1700 KCM AAC 61 str station conductor, the wavetrap facing Stillwell, the switches for CBs F and F1, and increase the CT thermal limit above 2739.336 MVA. NIPSCO will have to address their elements below 2739.336 SE MVA.
Total Cost ($USD)
$26,060,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05DUMONT-17STILLWELL 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9678.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9678.0 / CE_NUN_L11215_1
Title
Mitigate the sag on L11215
Description
Mitigate the sag on L11215. A preliminary estimate for this work is $9M with an estimated construction timeline of 30 months. Upon completion of this work the new line ratings will be 4142/4460/5331/6368/7323 MVA (SN/SLTE/SSTE/SLD/ALDR).
Total Cost ($USD)
$9,000,000
Allocated Cost ($USD)
$0
Time Estimate
30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18686
Title
05MADDOX 345.0 kV to 05E LIMA 345.0 kV ckt 1 - String the 2nd conductor
Description
AEP owned line; string the 2nd conductor (2-bundle 954 ACSS) ~30.28 miles on the double circuit line & six wire, At East Lima station replace sub conductor & relay trip limit and at Maddox Creek replace 5.0 IPS Sch. 40 bus work, sub conductor & relay trip limit
Total Cost ($USD)
$48,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18687
Title
05HANGRCK_RJ 765.0 kV to 05HANG R 765.0 kV ckt Z1 - Replace Equipment
Description
At Hanging Rock Station replace the following equipment: D1S1 PH A, D1S1 PH B, D1S1 PH C, D1S2 PH A, D1S2 PH B, D1S2 PH C, D2S1 PH A, D2S1 PH B, D2S1 PH C, D2S2 PH A, D2S2 PH B, D2S2 PH C, Jefferson Trap PH A, Jefferson Trap PH B, Jefferson Trap PH C
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05HANG R-05HANGRCK_RJ 765.0 kV Ckt Z1 line(Any)

System Reinforcement: n9243.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9243.0 / AEPSERG13
Title
Expand Jefferson 345 kV station. Install a second 765/345 kV 750 MVA transformer. Install a second Jefferson - Clifty Creek 345 kV single circuit ~0.8 miles.
Description
At the Jefferson Station: • Expand the northeast corner of the station • Remove Circuit breaker C1 • Install one (1) new 765/345 kV transformer and associated equipment • Install one (1) new 765 kV circuit breaker with associated control relaying and breaker disconnect switches • Install one (1) new 345 kV circuit breaker with associated control relaying and breaker disconnect switches • Install a new station service center At the Clifty Creek Station: • Extend 345 kV bus 1 and 2 to make room for a new breaker string • Move a section of the 138 kV bus underground to make room for the new breaker string • Relocate circuit breaker S to the new string • Install two (2) new 345 kV circuit breakers on the new string •Remove the existing Jefferson – Clifty Creek 345 kV line •Construct a new Jefferson – Clifty Creek 345 kV double circuit line •Evaluate line settings for all appropriate lines •Install direct fiber relaying between the Jefferson and Clifty Creek station •Associated conductors (buswork, ground grid, jumpers), telecom terminal equipment, insulators, arresters, foundations, and structures
Total Cost ($USD)
$200,238,000
Allocated Cost ($USD)
$0
Time Estimate
55 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05JEFRSO-05JEFRSO 345.0/765.0 kV Ckt 2 transformer(Any)
05JEFRSO-06CLIFTY 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: n7683
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7683
Title
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Description
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Total Cost ($USD)
$18,460,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18689
Title
AG1-410 TP 345.0 kV to 05MADDOX 345.0 kV ckt 1 - string the 2nd circuit
Description
AEP owned line; string the 2nd circuit on the rebuilt double circuit line, ~ 2.85 miles of 2-bundle 1590 ACSR conductor. At Maddox Creek: Replace 345kV circuit breaker B2, subconductor, disconnect switches.
Total Cost ($USD)
$7,250,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18635
Title
05MARYSVL_RM 765.0 kV to 05MALIS 765.0 kV ckt 1 - Replace Equipment
Description
Replace wave tap at Maliszewski towards Marysville along with circuit breakers, disconnects, and Sub Conductor.
Total Cost ($USD)
$24,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05MARYSVL_RM 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18653
Title
05MALIS 765.0 kV to 05VASSEL 765.0 kV ckt 1 - Replace Equipment
Description
Replace circuit breaker B, Disconnects, and reconductor between structures 432-453 to bring rating up to the sub conductor.
Total Cost ($USD)
$153,100,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05MALIS-05VASSEL 765.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18819
Title
06PIERCE 345kV to 05MARQUIS 345kV ckt 1 - Replace Equipment
Description
At Pierce replace the following equipment: Switch 444, 446, 447, and 449, Bus, Risers, Jumpers, Wave Trap, and Line Relay At Don Marquis 345kV replace the following equipment: Circuit Breaker B2, Risers, and Line Reactor.
Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement: s2213.9
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2213.9 / (Pending)
Title
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Description
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-516 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18634
Title
05MARYSV 765.0 kV to 05MARYSV 345.0 kV ckt 2 - Add second XFMR
Description
Add secondary 765/345 kV Transformer to Marysville. Add additional breakers to accommodate new transformer.
Total Cost ($USD)
$23,320,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSV 765.0/345.0 kV Ckt 2 transformer(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18680
Title
05MARYSV 765.0 kV to 05MARYSVL_RM 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap and associated equipment on Marysville Reactor towards Maliszewski.
Total Cost ($USD)
$2,200,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05CLOVRD-05CLOV17_XFL 345.0 kV Ckt 17 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18516
Title
17P9700-EAST 345.0 kV to 05OLIVE 345.0 kV ckt 1 - AEP End Ratings
Description
AEP end rating is 1413 MVA Rate B.
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05OLIVE-17P9700-EAST 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9182.0
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n9182.0 / AEPIMJMS01
Title
Rebuild Olive - AF2-359 345kV
Description
Rebuild the ~7.3 mile 345 kV line section between Olive and AF2-359 POI. The standard conductor for 345kV lines is 2-bundle 954 ACSR 45/7 RAIL.
Total Cost ($USD)
$35,000,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05OLIVE-AF2-359 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18707
Title
05ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment
Description
At RP Mone: Replace CB B and B2 and associated disconnect switches. Replace 2 - 1700 KCM AAC station conductor. At Allen: Replace the disconnect switches for CBs C and C2 at Allen. Replace 2 - 2000 KCM AAC station conductor. B3851.1 to rebuild the Allen - RP Mone line needs to be completed. CB B is also be proposed to be replaced on another flowgate
Total Cost ($USD)
$5,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18732
Title
05RPMONE 345kV to AG1-410 TP 345kV ckt 1 - Replace Equipment
Description
At R.P. Mone: Replace 345kV circuit breakers B & B1, Bus bar 4 x 3/4 Ph C, angle bus buar 4x4x1/4 Ph B, sub conductor, disconnect switches on B and B1 breakers
Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18693
Title
Greentown 765 kV to Marysville 765 kV - Greenfield Line
Description
Construct a new greenfield 765kV line from Greentown to Marysville (~160 miles). Install 2 new 765kV breakers at Marysville and 2 new 765kV breakers at Greentown. Install 765kV shunt reactors at both Marysville and Greentown The new 765kV line reduces equipment at Dumont to be replaced to CB A2 and switch A2S2. s3442.26 replaces Dumont 765kV CB A2 and A2S2 "CONTINGENCY 'AEP_P1-2_GREENTOWN TO MARYSVILLE 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_GREENTOWN CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_MARYSVILLE CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END"
Total Cost ($USD)
$1,000,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 120 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05SORENS-05DUMONT_RS 765.0 kV Ckt 1 line(Any)
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)
05DUMONT-05DUMONT_RS 765.0 kV Ckt Z1 line(Any)
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Nov 18 2027

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: n7925.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7925.1 / AEPI0010a
Title
Reconductor ~0.41 miles of the Sullivan – West Casey (Ameren) line
Description
•Remove ~0.41 miles of 1024.5 ACAR 30/7 conductor on the Sullivan – West Casey (Ameren) 345 kV line. •Rebuild line with ACSS Cardinal 974 KCM (54/7) •Evaluate line settings
Total Cost ($USD)
$1,216,000
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05SULLIVAN-7SNYDER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18821
Title
AEP Reinforcements for DEOK New Sub and New 345kV Line from Tanner's Creek
Description
AEP Scope of Work: At Tanners Creek station- install a 345 kV circuit breaker "T", relocate Lawrenceburg #1 345 kV line (between breakers T and T2), relocate Miami Fort 345 kV line (between breakers T and T1), relocate formerly East Bend 345 kV line (to Idlewild Duke station) (between breakers S and S1), and install new Tanners Creek - Idlewild 345 kV line #2 (between breakers R and R1), ~0.35 miles of AEP install and ~2.48 miles of Duke install.
Total Cost ($USD)
$6,700,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
(Pending) / F4504
Title
DEOK New Sub and New 345kV Line from Tanner's Creek
Description
This Network Upgrade will be joint effort between DEOK & AEP to mitigate the Miami Fort - Tanner's Creek 345kV violations. DEOK Scope of Work: - DEOK will construct a new 5-breaker Ring Bus, 345kV Switching Station in Northern Kentucky called 'Idlewild'(Lat: 39° 5'15.11"N, Long: 84°49'10.14"W) - DEOK will loop the Tanner's Creek (AEP) - East Bend (DEOK) and Miami Fort (DEOK) - Terminal (DEOK) 345kV circuits into Idlewild Substation - In order to loop the Miami Fort - Terminal circuit into Idlewild Substation, DEOK will retire ~0.68 miles of the Miami Fort - Terminal circuit and add ~0.95 miles of new 345kV conductor (954ACSR 45x7, 2cond/ph, 100C). The new conductor will be built on existing DEOK easement. - DEOK will construct a new 345kV circuit from Idlewild substation to a pole that is just outside AEP's Tanner's Creek Substation. This circuit will be ~2.48 miles long with (1) Ohio River Crossing. The new 345kV circuit will be built will 954ACSS/TW, 2-conductor/phase, 200C conductor. Part of the new 345kV circuit will be built on existing DEOK easement, but DEOK will need to obtain ~1.0 mile of new easement. Line ownership for this new circuit will change at the tower which is just outside AEP's Tanner's Creek Substation in Lawrenceburg, Indiana.
Total Cost ($USD)
$72,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P1-2_#7441_100545_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7445_05MARYSV 765_B_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7441_05SORENS 765_J1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P2-2_#9456_06DEARB1 345_1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P7-1_#485___SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7446_05MARYSV 765_B2_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#9456_06DEARB1 345_DC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P4_1579_EASTBEND_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)

System Reinforcement: n8379
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n8379 / CE_NUN_L11212_NEW TR
Title
Wilton Center - Install 3rd Transformer
Description
Install 3rd Transforner 1120 MVA at TSS 112 Wilton Center. New breaker installations and bus work at 765kV and 345kV. New relay scheme, foundation work and TSS 112 control building upgrades. A preliminary estimate of $38 M with a preliminary construction timelline of 48 months. This is a resolution to the contingency thererfore the ratings will not change.
Total Cost ($USD)
$38,000,000
Allocated Cost ($USD)
$0
Time Estimate
48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
17MUNSTER-BURNHAM ;0R 345.0 kV Ckt 1 lineCOMED_P4_112-65-BT3-4___SRT-A
17MUNSTER-BURNHAM ;0R 345.0 kV Ckt 1 lineCOMED_P4_112-65-BT4-5___SRT-A
WILTON ;-WILTON ;3M 765.0/345.0 kV Ckt 1 transformer(Any)
WILTON ;-WILTON ;4M 765.0/345.0 kV Ckt 1 transformer(Any)
WILTON ;-WILTON ;4M 765.0/345.0 kV Ckt 1 transformerCOMED_P4_023-65-BT2-3__
WILTON ;-WILTON ;4M 765.0/345.0 kV Ckt 1 transformerCOMED_P4_023-65-BT2-3__
WILTON ;-WILTON ;4M 765.0/345.0 kV Ckt 1 transformerCOMED_P4_023-65-BT3-4__
WILTON ;-WILTON ;4M 765.0/345.0 kV Ckt 1 transformerCOMED_P4_023-65-BT4-5__
WILTON ;-WILTON ;4M 765.0/345.0 kV Ckt 1 transformerCOMED_P4_023-65-BT4-5__
WILTON ; B-WILTON ;3M 345.0 kV Ckt 1 line(Any)
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT3-4__
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 line(Any)
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT2-3__
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT4-5__
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT2-3__
WILTON ; R-WILTON ;4M 345.0 kV Ckt 1 lineCOMED_P4_023-65-BT4-5__

System Reinforcement
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
(Pending) / CE_NUN_L17705_1
Title
Reconductor Sheffield - Burnham and upgrade station conductor at Burnham
Description
This upgrade will be to reconductor the line and upgrade station conductor at Burnham Potential transmission tower replacement required with line reconductor. The estimate for this work will not be known until the Phase 3 system upgrade Facility Study is complete per the PJM process.
Total Cost ($USD)
$14,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
17SHEFFIELD-BURNHAM ; B 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending)
Title
AEP end ratings are 1413 MVA
Description
AEP end ratings are 1413 MVA
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
17STJOHN-AF2-359 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.351
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.351
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating Line #9517 Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.345
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.345
Title
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from a new substation called Kraken to a new substation called Yeat. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.326
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.326
Title
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Description
At Elmont substation, install/upgrade associated equipment to accommodate a 4000A line rating for the new 230kV line between Elmont - Ladysmith.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.342
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.342
Title
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Description
Remove the terminal equipment and substation work required for the termination of the Morrisville-Wishing Star 500 kV line into Vint Hill.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.355
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.355
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 69.3 miles in AEP section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.350
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.350
Title
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Description
Update relay settings at Possum Point to change the destination of 500kV line #568 from Ladysmith to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.349
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.349
Title
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Description
Update relay settings at Ladysmith to change the destination of 500kV line #568 from Possum Point to Kraken.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.357
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.357
Title
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Description
Build a new 765/500/230 kV substation called Yeat. Install (2) 765/500 kV transformers. Cut in 500 kV line Bristers-Ox and 500 kV line Meadowbrook-Vint Hill into Yeat.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.327
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.327
Title
Upgrade/install equipment at Ladysmith Substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230 kV strings of breaker and a half scheme.
Description
Upgrade/install equipment at Ladysmith substation to 4000A. Expansion will be required to accommodate a total of three (3) new 230kV strings of breaker and a half scheme.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.341
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.341
Title
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV Substation and extend approximately 0.2 miles of conductor to fly-over the site.
Description
Remove the 500 kV conductor previously planned to terminate into the Vint Hill 500 kV substation and extend approximately 0.2 miles of conductor to fly-over the site.
Cost Information
Time Estimate
Jul 13 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.348
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.348
Title
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers.
Description
Build a new 500/230kV substation called Kraken. The 500kV, 5000A ring bus will be set up for a redundant breaker configuration. Install (2) 1400MVA 500/230 kV transformers. A new redundant breaker ring will be added at Kraken to accommodate the new 500kV line from North Anna to Kraken.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.356
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.356
Title
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Description
Build a new 156 mile 765kV line from Joshua Falls – Yeat. (Roughly 86.7 miles in Dominion section).
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.346
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.346
Title
Cut-in 500kV line from Kraken substation into Yeat substation
Description
Cut-in 500kV line from Kraken substation into Yeat substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.352
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.352
Title
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Description
Cut in Line #568 Ladysmith - Possum Point into Kraken, creating new Line #568 Kraken to Possum Point.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.325
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.325
Title
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Description
Build a new 26.38mi 230kV Line from Elmont – Ladysmith on the existing 5-2 structures between the two stations. New conductor has a summer rating of 1573 MVA.
Cost Information
Time Estimate
Feb 24 2029

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.344
Type
Load Flow
TO
Dominion
RTEP ID / TO ID
b4000.344
Title
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Description
Build a 500kV line from North Anna substation (bypassing Ladysmith Substation) to a new substation called Kraken. New conductor to have a minimum summer normal rating of 4357MVA.
Cost Information
Time Estimate
Sep 16 2030

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-516 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05CLOVRD-8LEXNGTN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n3515.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n3515.1 / ce-017
Title
Cherry Valley - Garden Prarie 345 kV: Line rebuild, station bus work, & Cherry Valley 345kV breaker replacement
Description
• Rebuild entire 345kV transmission line L.15616 from TSS 156 Cherry Valley to TSS 971 Prairie (approximately 15.4 miles). • Replace static wire with dual OPGW that each contain single-mode 48 count fiber. Install two (2) 48-ct FDPs at TSS 156 Cherry Valley and TSS 971 Prairie to account for new OPGW. • Upgrade the existing substation TSS 156 Cherry Valley by upgrading existing 345kV BT 4-7 circuit breaker and associated disconnect switches. • Upgrade SCADA, relay & protection at 345kV substation TSS 156 Cherry Valley to support upgrade of 345kV L.15616.
Total Cost ($USD)
$84,712,245
Allocated Cost ($USD)
$0
Time Estimate
50 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 may need this upgrade in-service to be deliverable to the PJM system. If AG2-516 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
CHERRY VA; B-AF2-349 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
(Pending) / CE_NUN_COLLINS_TR
Title
Collins Station 23 New Transformer
Description
Installation of 2nd transformer at Station 23 Collins. Installation to include station work, new breakers, switches and supporting facilities at both 345KV & 765KV level. Possible station civil, grading and yard expansion work required. The estimate given will not include this price and time. Facility Study at Phase III will provide further information.
Total Cost ($USD)
$15,600,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 30 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
COLLINS ;-COLLINS ;2M 765.0/345.0 kV Ckt 1 transformer(Any)
COLLINS ; R-COLLINS ;2M 345.0 kV Ckt 1 line(Any)

System Reinforcement: n6639.2
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n6639.2 / CE_NUN_L15502_4
Title
Reconductor the Electric Junction 345 kV line 93407, perform sag mitigation on 345 kV line 93407, upgrade one 345 kV circuit breaker and associated motor operated disconnect switches.
Description
• Reconductor 27.2 Miles of 345kV transmission line 93407 from structure 339 to structure 454 • Perform sag mitigation on 13.5 miles of 345kV transmission line 93407 from structure 454 to TSS 111 Electric Junction • Upgrade the existing substation TSS 111 Electric Junction by replacing L.93407 CB motor-operated disconnect switches on both sides of the breaker.
Total Cost ($USD)
$146,197,759
Allocated Cost ($USD)
$0
Time Estimate
42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
ELECT JCT;1B-AF2-041 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: n7023.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n7023.1 / CE_NUN_L11124.1
Title
Reconductor the Electric Junction - Lombard line L11124 345 kV Line and perform associated station relay and protection upgrades.
Description
• Upgrade 13.5 Miles of 345kV transmission line 11124 from TSS 111 Electric Junction to TSS 120 Lombard • Upgrade relay & protection at 345kV substation TSS 111 Electric Junction & TSS 120 Lombard to support upgrade of 345kV transmission line, L1124
Total Cost ($USD)
$38,797,273
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
ELECT JCT;1B-LOMBARD ;4B 345.0 kV Ckt 1 line(Any)

System Reinforcement: n5318.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n5318.1 / ce-012a
Title
Garden Prarie - Silver Lake R 345 kV: Line rebuild, station bus work & Silver Lake 345kV Breaker Replacement
Description
• Rebuild entire 345kV transmission line L.97104 from TSS 971 Prairie to TSS 138 Silver Lake (approximately 24.7 miles). • Replace static wire with OPGW that contains single-mode 48 count fiber. Install 48-ct FDP at TSS 138 Silver Lake and TSS 971 Prairie to account for new OPGW. • Upgrade the existing substation TSS138 Silver Lake by replacing existing circuit breaker 345kV BT 3-4 & associated disconnect switches and replacing the line disconnect switch for 345kV line 97104. • Upgrade relay & protection at 345kV substation TSS 138 Silver Lake to support upgrade of 345kV transmission line, 97104.
Total Cost ($USD)
$163,968,683
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Contingent

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 may need this upgrade in-service to be deliverable to the PJM system. If AG2-516 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
SILVER LK; R-AF2-349 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: n8389
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n8389 / CE_N8389_116BT3-4_1
Title
TSS 116 Replace Station Conductor
Description
ComEd 345kV BT3-4 at TSS 116 SSTE rating is 2083 MVA. The upgrade will be to replace the station conductor at TSS 116. A preliminary estimate for the upgrade is $1M. A preliminary construction timeline is 24 months. Upon completion of the upgrade the ratings will be 2236/2874/3009/3358 MVA (SN/SLTE/SSTE/SLD.
Total Cost ($USD)
$1,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
GOODINGS ;3B-GOODINGS ;4B 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9269.0
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
n9269.0 / CE_NUN_L11212.5
Title
Reconductorthe L11212 345 kV line.
Description
• Reconductor 18.4 Miles of 345kV transmission line 11212 from TSS 112 Wilton Center to TSS 905 Essex. • Upgrade L11212 motor-operated switch and all cable conductors at line termination structure to 2-1590 kcmil ACSR.
Total Cost ($USD)
$37,989,655
Allocated Cost ($USD)
$0
Time Estimate
42 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-516 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-516 could receive cost allocation. Although AG2-516 may not presently have cost responsibility for this upgrade, AG2-516 is a potential Aggregate Pool Contributor.

FacilityContingency
WILTON ; B-AD1-100 TAP1 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / (Pending)
Title
WILTON ; 765.0 kV to 05DUMONT_RW 765.0 kV ckt 1 - AEP End Ratings
Description
Limited by non-AEP equipment, AEP End ratings: 5496.0, 6143.0, 6328.0
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
0 to 12 Months

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
WILTON ;-05DUMONT_RW 765.0 kV Ckt 1 line(Any)

System Reinforcement: n5808
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n5808 / N5808
Title
CON Upgrade_AEP: eliminate the Eugene stuck breaker contingency. (AMIL upgrade will not be required)
Description
• AEP will install two (2) new 345 kV circuit breakers into the "A1" and "B1" breaker positions at the Eugene 345 kV Station. • AEP will relocate the Bunsonville 345 kV line connection from bus #2 to bus #1. The metering associated with this line connection will also be replaced and relocated accordingly.
Total Cost ($USD)
$3,424,014
Allocated Cost ($USD)
$0
Time Estimate
May 15 2026

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a network upgrade that was securitized by a prior Queue/Cycle. AG2-516 is not contingent on this network upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)AEP_P4_#3128_05EUGENE 345_A2_SRT-A

System Reinforcement: s3011
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
s3011 / CE_S3011
Title
Replace 345kV straight bus at TSS 116 Goodings Grove with a gas insulated switchgear ("GIS") breaker and a half configuration.
Description
Replace 345 kV open air straight bus with GIS in a breaker and half configuration (34 Circuit Breakers) at Goodings Grove with 80kA capability.
Cost Information
Time Estimate
Dec 31 2028

Not Contingent

Note: AG2-516 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-516 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
(Any)COMED_P4-6_116-345-R______SRT-A
(Any)COMED_P4_116-45-TR82____SRT-A
(Any)COMED_P4_116-45-L11614__SRT-A
(Any)COMED_P2-2_116_GG-345R__2_SRT-A
(Any)COMED_P2-2_116_GG-345B__4_SRT-A

Attachments

AG2-516 One Line Diagram

AG2-516 One Line Diagram.pdf
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.