AG2-550 Phase I Study Report

v1.00 released 2025-10-29 20:49

Bluff Point - Randolph 138 kV

60.0 MW Capacity / 100.0 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Riverstart Solar Park VI LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Randolph County, Indiana. The installed facilities will have a total capability of 100.0 MW with 60.0 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-550
Project Name:
Bluff Point - Randolph 138 kV
Project Developer Name:
Riverstart Solar Park VI LLC
State:
Indiana
County:
Randolph
Transmission Owner:
American Electric Power
MFO:
100.0
MWE:
100.0
MWC:
60.0
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-550 will interconnect on the American Electric Power transmission system by tapping the Bluff - Randolph 138 kV Line.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-550 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-550Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$352,000$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$0$0
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$22,737,374$22,737,374
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$254,423$254,423
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$23,343,797$22,991,797

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-550

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-550 Project due at DP1
ABA - B
AG2-550$2,299,180$400,000$1,899,180

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Physical Interconnection
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will procure and install revenue submetering equipment for settlement between the generators behind the Point of Interconnection$352,000 $352,000

Based on the scope of work for the Interconnection Facilities, it is expected to take 6 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

Transmission Owner Identified Network Impacts

There were no network impacts to Distribution facilities identified by the Transmission Owner.

The Transmission Owner identified network impacts to Sub-Regional facilities as follows:

Transmission Owner Identified System Reinforcements on Sub-Regional Facilities
Overloaded ElementContingencyRating [MVA]Final Cycle Loading %Contribution [MW]
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#14047_05DESOTO 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1                  / 243278 05DESOTO 138 243340 05MEDFOR 138 1

END
71.0156.36 %7.43
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0156.35 %7.43
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-1
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0156.35 %7.43
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-2
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'  

  OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1                  / 946030 AF1-268 TP 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1                  / 964610 AG1-324 TP 138 247837 05PERCH 138 1

END
71.0144.04 %7.43
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-3
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-3'  

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

END
71.0134.52 %7.43
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#15176_05JAY 138_E2_SRT-A
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2                  / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2                  / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2                  / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2

  REMOVE SWSHUNT FROM BUS 243319                                   / 243319 05JAY 138

END
71.0126.04 %7.13
246005 053-M 69.0 - 245974 05HARTF CT 69.0 CKT 1 AEP_P4_#15023_05JAY 138_E_SRT-A
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'  

  OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4                  / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4                  / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4                  / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

END
71.0120.49 %6.9
246014 05BLUFFPNT 69.0 - 246022 05PORTLAND 69.0 CKT 1 AEP_P4_#10531_05JAY 138_D_SRT-A
CONTINGENCY 'AEP_P4_#10531_05JAY 138_D_SRT-A'  

  OPEN BRANCH FROM BUS 243237 TO BUS 270019 CKT 1                  / 243237 05ADAM 138 270019 AE2-089 TAP 138 1

  OPEN BRANCH FROM BUS 270019 TO BUS 243358 CKT 1                  / 270019 AE2-089 TAP 138 243358 05PENNVI 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 243358 CKT 1                  / 243319 05JAY 138 243358 05PENNVI 138 1

  OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1                  / 243253 05BLUFFP 138 243319 05JAY 138 1

END
86.0125.97 %24.66
246014 05BLUFFPNT 69.0 - 246022 05PORTLAND 69.0 CKT 1 AEP_P4_#15175_05JAY 138_D2_SRT-A
CONTINGENCY 'AEP_P4_#15175_05JAY 138_D2_SRT-A'  

  OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1                  / 243253 05BLUFFP 138 243319 05JAY 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2                  / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2                  / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2                  / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2

  REMOVE SWSHUNT FROM BUS 243319                                   / 243319 05JAY 138

END
86.0123.47 %24.26
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#17621_SRT-A-3
CONTINGENCY 'AEP_P1-2_#17621_SRT-A-3'  

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

END
50.0160.78 %8.78
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#17624_05HAYES 138_A_SRT-A
CONTINGENCY 'AEP_P4_#17624_05HAYES 138_A_SRT-A'  

/  OPEN BRANCH FROM BUS 244587 TO BUS 290085 CKT 1                  / 244587 05RANDOLPH2 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP(05RANDOLPH2) 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 290084 CKT 1                  / 243310 05HODGIN 138 290084 05HAYES 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 243400 CKT 1                  / 243310 05HODGIN 138 243400 05HODGIN 69.0 1

END
50.0160.63 %8.78
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#17625_05HAYES 138_B_SRT-A-1
CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A-1'  

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1                  / 253290 09BLAZER 138 290084 05HAYES 138 1

END
50.0159.25 %8.77
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#17621_SRT-A-2
CONTINGENCY 'AEP_P1-2_#17621_SRT-A-2'  

  OPEN BRANCH FROM BUS 971028 TO BUS 971672 CKT 1                  / 971028 AG2-637 TP 138 971672 AH1-337 TP 138 1

END
50.0151.09 %8.78
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-1
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
50.0131.9 %7.01
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
50.0131.9 %7.01
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#14047_05DESOTO 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1                  / 243278 05DESOTO 138 243340 05MEDFOR 138 1

END
50.0131.37 %7.01
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-2
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'  

  OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1                  / 946030 AF1-268 TP 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1                  / 964610 AG1-324 TP 138 247837 05PERCH 138 1

END
50.0124.85 %7.01
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P4_#15023_05JAY 138_E_SRT-A
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'  

  OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4                  / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4                  / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4                  / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

END
50.0121.38 %7.07
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P1-2_#17621_SRT-A-1
CONTINGENCY 'AEP_P1-2_#17621_SRT-A-1'  

  OPEN BRANCH FROM BUS 244587 TO BUS 971028 CKT 1                  / 244587 05RANDOLPH2 138 971028 AG2-637 TP 138 1

END
50.0119.44 %8.78
246079 05PRICE 69.0 - 246076 05ANCHORHO 69.0 CKT 1 AEP_P7-1_#11037___SRT-A
CONTINGENCY 'AEP_P7-1_#11037___SRT-A'  

  OPEN BRANCH FROM BUS 243278 TO BUS 243373 CKT 1                  / 243278 05DESOTO 138 243373 05SELMAP 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 246629 CKT 1                  / 243278 05DESOTO 138 246629 05SELMA P_BP 138 1

  OPEN BRANCH FROM BUS 246629 TO BUS 270378 CKT 1                  / 246629 05SELMA P_BP 138 270378 AD1-128 TAP 138 1

  OPEN BRANCH FROM BUS 243344 TO BUS 270378 CKT 1                  / 243344 05MODOC 138 270378 AD1-128 TAP 138 1

END
50.0108.07 %4.23
246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
CONTINGENCY 'AEP_P4_#10527_05BLUFFP 138_E2_SRT-A'  

  OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1                  / 243253 05BLUFFP 138 243319 05JAY 138 1

  OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1                  / 243253 05BLUFFP 138 246014 05BLUFFPNT 69.0 1

END
86.0109.1 %20.35
246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 AEP_P4_#17624_05HAYES 138_A_SRT-A
CONTINGENCY 'AEP_P4_#17624_05HAYES 138_A_SRT-A'  

/  OPEN BRANCH FROM BUS 244587 TO BUS 290085 CKT 1                  / 244587 05RANDOLPH2 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP(05RANDOLPH2) 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 290084 CKT 1                  / 243310 05HODGIN 138 290084 05HAYES 138 1

  OPEN BRANCH FROM BUS 243310 TO BUS 243400 CKT 1                  / 243310 05HODGIN 138 243400 05HODGIN 69.0 1

END
86.0103.56 %13.41
246087 05RANDOLPH 69.0 - 246079 05PRICE 69.0 CKT 1 AEP_P4_#17625_05HAYES 138_B_SRT-A-1
CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A-1'  

  OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1                  / 971672 AH1-337 TP 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1                  / 290084 05HAYES 138 290085 05HODGIN_BP 138 1

  OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1                  / 253290 09BLAZER 138 290084 05HAYES 138 1

END
86.0102.47 %13.41
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#14047_05DESOTO 138_F_SRT-A
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1                  / 243278 05DESOTO 138 243340 05MEDFOR 138 1

END
71.0163.87 %7.43
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0163.86 %7.43
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-1
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'  

  OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1                  / 243278 05DESOTO 138 946030 AF1-268 TP 138 1

END
71.0163.85 %7.43
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-2
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'  

  OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1                  / 946030 AF1-268 TP 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1                  / 964610 AG1-324 TP 138 247837 05PERCH 138 1

END
71.0151.56 %7.43
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P1-2_#15020_SRT-A-3
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-3'  

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

END
71.0141.68 %7.43
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15176_05JAY 138_E2_SRT-A
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'  

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2                  / 243319 05JAY 138 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2                  / 246016 05JAY 69.0 290130 05JAY 2EQ 1.00 2

  OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2                  / 290130 05JAY 2EQ 1.00 290132 05JAY T2 13.0 2

  REMOVE SWSHUNT FROM BUS 243319                                   / 243319 05JAY 138

END
71.0133.0 %7.13
247883 05FULKERSNSS 69.0 - 246005 053-M 69.0 CKT 1 AEP_P4_#15023_05JAY 138_E_SRT-A
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'  

  OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4                  / 243319 05JAY 138 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4                  / 246016 05JAY 69.0 246018 05JAY 4EQ 1.00 4

  OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4                  / 246015 05JAY 34.5 246018 05JAY 4EQ 1.00 4

/*  OPEN BRANCH FROM BUS 243319 TO BUS 247837 CKT 1                  / 243319 05JAY 138 247837 05PERCH 138 1

  OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1                  / 243319 05JAY 138 964610 AG1-324 TP 138 1

/*  OPEN BRANCH FROM BUS 243278 TO BUS 247837 CKT 1                  / 243278 05DESOTO 138 247837 05PERCH 138 1

END
71.0126.71 %6.9
Transmission Owner Identified System Reinforcements
AG2-550 Transmission Owner Identified System Reinforcements Cost Breakdown:
TORTEP ID / TO IDCategoryTitleMW ImpactPercent AllocationAllocated Cost ($USD)
AEP(Pending) / TC2-AEP-191SubRegionalHartford City - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.7.4 MW22.8%$91,306
AEP(Pending) / TC2-AEP-192SubRegionalBluff Point - Portland: Replace Bluff Point 69 kV 300 MCM CU 37 Str riser, Replace the Portland 69 kV 600 A switch, sag study and mitigation ~7.5 miles of the conductor 556.5 ACSR 26/724.7 MW35.9%$71,811
AEP(Pending) / TC2-AEP-203SubRegionalRandolph - Price: Summer emergency rating is 142 MVA.20.4 MW33.0%$0
AEP(Pending) / TC2-AEP-194SubRegionalFulkerson Switch - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.7.4 MW22.8%$91,306
Grand Total:$254,423

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-191
Category
SubRegional
Title
Hartford City - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
Description
Hartford City - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
Total Cost
$400,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-5507.4 MW22.8%$91,306
AG2-5516.8 MW20.7%$82,949
AG2-6378.9 MW27.4%$109,616
AH1-3086.9 MW21.2%$84,916
AH1-3372.5 MW7.8%$31,214

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-192
Category
SubRegional
Title
Bluff Point - Portland: Replace Bluff Point 69 kV 300 MCM CU 37 Str riser, Replace the Portland 69 kV 600 A switch, sag study and mitigation ~7.5 miles of the conductor 556.5 ACSR 26/7
Description
Bluff Point - Portland: Replace Bluff Point 69 kV 300 MCM CU 37 Str riser, Replace the Portland 69 kV 600 A switch, sag study and mitigation ~7.5 miles of the conductor 556.5 ACSR 26/7
Total Cost
$200,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-55024.7 MW35.9%$71,811
AG2-5515.7 MW8.4%$16,715
AG2-63729.8 MW43.3%$86,692
AH1-3378.5 MW12.4%$24,782

System Reinforcement: s1508
TO
AEP
RTEP ID / TO ID
s1508
Category
SubRegional
Title
s1508 (In service)
Description
Rebuild from Structure 1 near Anchor Hocking Station to structure 139A near Price station (~6.5 miles) using 556.5 ACSR 26/7 (SN:102 SE:141 WN:129 WE:159)
Total Cost
$0
Contingent

Note: Although Queue Project AG2-550 may not have cost responsibility for this upgrade, Queue Project AG2-550 may need this upgrade in-service to be deliverable to the PJM system. If Queue Project AG2-550 comes into service prior to completion of the upgrade, Queue Project AG2-550 will need an interim study.


System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-203
Category
SubRegional
Title
Randolph - Price: Summer emergency rating is 142 MVA.
Description
Randolph - Price: Summer emergency rating is 142 MVA.
Total Cost
$0
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-55020.4 MW33.0%$0
AG2-5514.7 MW7.7%$0
AG2-63728.5 MW46.2%$0
AH1-3378.1 MW13.1%$0

System Reinforcement
TO
AEP
RTEP ID / TO ID
(Pending) / TC2-AEP-194
Category
SubRegional
Title
Fulkerson Switch - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
Description
Fulkerson Switch - 3M: Perform relay upgrades to increase 3M CT thermal limit and relay thermal limit. Replace three 477 AAC 19-Str station conductor at 3M station.
Total Cost
$400,000
Contributor
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-5507.4 MW22.8%$91,306
AG2-5516.8 MW20.7%$82,949
AG2-6378.9 MW27.4%$109,616
AH1-3086.9 MW21.2%$84,916
AH1-3372.5 MW7.8%$31,214

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-550 was evaluated as a 100.0 MW (60.0 MW Capacity) injection in the AEP area.

AG2-550 was evaluated as part of a plant. The plant consists of AG2-550, AG2-551. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (120.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC121.47 %3792.0B4606.269.52
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC121.45 %3792.0B4605.389.48
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC121.43 %3792.0B4604.689.48
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC120.65 %3792.0B4574.966.62
GD2AP
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC120.64 %3792.0B4574.636.62
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
BreakerAC139.97 %3792.0B5307.799.21
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT7A_SRT-SL
BreakerAC139.96 %3792.0B5307.19.21
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P2-3_WP-500-DRT10A_SRT-SL
BreakerAC139.86 %3792.0B5303.439.29
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-3_MP-765-502T_SRT-A
SingleAC139.36 %3792.0B5284.616.43
GD2AP
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
AP_P1-2_MP-500-028_SRT-A
SingleAC139.32 %3792.0B5282.916.43
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-024_SRT-A
BreakerAC132.75 %3729.0B4950.2710.63
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-025_SRT-A
BreakerAC131.94 %3729.0B4919.9310.61
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-015_SRT-A
BreakerAC131.63 %3729.0B4908.4710.6
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-014_SRT-A
BreakerAC131.63 %3729.0B4908.4710.6
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-007A_SRT-A
SingleAC130.62 %3729.0B4870.987.39
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P2-3_MP-500-012_SRT-A
BreakerAC130.23 %3729.0B4856.2610.73
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_MP-500-008A_SRT-SL
SingleAC124.1 %3729.0B4627.67.12
GD2ATSI
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
ATSI_P1-2_TE-345-601_SRT-A
SingleAC113.99 %1878.0B2140.733.35
GD2AEP
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC121.78 %1737.0B2115.34.06
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
BreakerAC109.09 %1203.0B1312.325.17
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16620_05ADKINS 345_A_SRT-A
BreakerAC108.01 %1203.0B1299.365.2
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
BreakerAC108.01 %1203.0B1299.335.2
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
BreakerAC108.01 %1203.0B1299.325.2
GD2AEP
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC106.27 %1203.0B1278.45.39
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P4_1403_MIAMI FORT_SRT-A
BreakerAC114.86 %178.0B204.456.87
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
AEP_P4_#2812_05TANNER 345_T2_SRT-A
BreakerAC108.71 %178.0B193.56.88
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P4_1401_MIAMI FORT_SRT-A
BreakerAC108.59 %178.0B193.296.88
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A
TowerAC105.05 %178.0B186.996.74
GD2AEP/DEO&K
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
DEOK_P4_1301_TERMINAL_SRT-A
BreakerAC102.92 %178.0B183.26.79
GD2AEP
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC106.88 %4571.0B4885.666.87
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC123.24 %255.0B314.2765.61
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#10528_05BLUFFP 138_D_SRT-A
BreakerAC106.65 %255.0B271.9665.62
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC106.59 %255.0B271.8133.24
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#11242_05BLUFFP 138_D1_SRT-A
BreakerAC106.59 %255.0B271.865.62
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
BreakerAC106.56 %255.0B271.7433.24
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9728_05MALIS 138_L1_SRT-A
BreakerAC124.65 %1409.0B1756.354.57
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9730_05MALIS 138_P1_SRT-A
BreakerAC124.16 %1409.0B1749.364.56
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#9729_05MALIS 138_M1_SRT-A
BreakerAC124.05 %1409.0B1747.914.56
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC112.44 %1409.0B1584.274.54
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7222_05MALIS 765_D_SRT-A
BreakerAC112.42 %1409.0B1584.054.54
GD2AEP
05HYATT-05VASSEL 345.0 kV Ckt 1 line
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
BreakerAC102.74 %1409.0B1447.544.51
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-024_SRT-A
BreakerAC134.01 %3792.0B5081.5210.63
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-025_SRT-A
BreakerAC133.21 %3792.0B5051.210.61
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-015_SRT-A
BreakerAC132.9 %3792.0B5039.6910.6
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-014_SRT-A
BreakerAC132.9 %3792.0B5039.6910.6
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-007A_SRT-A
SingleAC131.92 %3792.0B5002.287.39
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P2-3_MP-500-012_SRT-A
BreakerAC131.49 %3792.0B4985.9810.73
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_MP-500-008A_SRT-SL
SingleAC125.38 %3792.0B4754.337.12
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
BreakerAC124.95 %4142.0B5175.3912.28
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-020_SRT-SL
BreakerAC120.6 %4142.0B4995.0912.45
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P2-3_MP-500-021_SRT-SL
BreakerAC120.39 %4142.0B4986.3712.41
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
BreakerAC120.3 %4142.0B4982.8212.4
GD2AEP
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
AP_P1-3_MP-765-501T_SRT-A
SingleAC118.76 %4142.0B4919.188.65
GD2AEP
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC120.12 %2246.0B2697.983.86
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC145.65 %4142.0B6032.938.32
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC140.14 %4142.0B5804.667.92
GD2AEP
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Base Case
SingleAC130.5 %4047.0A5281.197.15
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#17217_SRT-A
SingleAC115.67 %5523.0B6388.329.35
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Base Case
SingleAC108.86 %4558.0A4961.856.37
GD2AEP
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
AEP_P1-2_#7422_16_SRT-A
SingleAC106.56 %5523.0B5885.347.71
GD2AEP
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC132.35 %1868.0B2472.273.91
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7443_05DUMONT 765_A_SRT-A
BreakerAC116.16 %3097.0B3597.5510.71
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7442_05SORENS 765_K2_SRT-A
BreakerAC116.09 %3097.0B3595.3110.72
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
BreakerAC115.9 %3097.0B3589.5610.73
GD2AEP
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
AEP_P1-2_#7442_200545_SRT-A
SingleAC111.07 %3097.0B3439.747.48
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#709_546_SRT-A
SingleAC109.05 %5523.0B6022.778.32
GD2AEP
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
AEP_P1-2_#6463_16757_SRT-A
SingleAC104.68 %5523.0B5781.37.92
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
BusAC128.08 %2317.0B2967.7111.85
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
BreakerAC128.08 %2317.0B2967.5511.85
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC127.06 %2317.0B2944.056.0
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC124.93 %2317.0B2894.556.07
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC124.59 %2317.0B2886.845.99
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC118.23 %2317.0B2739.44.23
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
TowerAC115.91 %2317.0B2685.577.21
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P7-1_#485___SRT-A
TowerAC115.9 %2317.0B2685.447.21
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
DEOK_P4_1579_EASTBEND_SRT-A
BreakerAC110.77 %2317.0B2566.436.07
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A
SingleAC100.05 %2317.0B2318.244.24
GD2OVEC
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
DEOK_P4_1403_MIAMI FORT_SRT-A
BreakerAC104.32 %942.0B982.665.45
GD2OVEC
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
DEOK_P4_1401_MIAMI FORT_SRT-A
BreakerAC103.8 %942.0B977.755.46
GD2OVEC
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
AEP_P4_#2812_05TANNER 345_T2_SRT-A
BreakerAC103.75 %942.0B977.335.46
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC156.15 %1540.0B2404.667.18
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC154.73 %1540.0B2382.876.94
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1558_05BAKER 765_Q_SRT-A
BreakerAC153.9 %1540.0B2370.076.85
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#309_05HANG R 765_B2_SRT-A
BreakerAC153.46 %1540.0B2363.366.84
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
BreakerAC153.34 %1540.0B2361.466.83
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC145.41 %1540.0B2239.274.84
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P1-2_#309_15_SRT-A
SingleAC141.78 %1540.0B2183.344.77
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
BusAC135.59 %1540.0B2088.166.26
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34569 34598 34524_SRT-A
TowerAC132.73 %1540.0B2044.016.25
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
34524 34598_SRT-A
TowerAC132.58 %1540.0B2041.736.23
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
Base Case
SingleAC131.72 %1189.0A1566.094.33
GD2AEP/OVEC
06KYGER-05SPORN 345.0 kV Ckt 1 line
AP_P2-2_WP-500-DRT14_SRT-SL
BusAC130.87 %1540.0B2015.356.19
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#6189_05HANG R 765_D1_SRT-A
BreakerAC112.42 %1540.0B1731.236.42
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P4_#709_05HANG R 765_D2_SRT-A
BreakerAC108.09 %1540.0B1664.566.46
GD2AEP/OVEC
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
AEP_P1-2_#709_546_SRT-A
SingleAC101.36 %1540.0B1561.024.51
GD2DEO&K
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
DEOK_P_CIRCUIT3281&13803_SRT-A
TowerAC129.22 %54.0B69.782.42
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC121.36 %205.0B248.7816.77
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
BreakerAC121.32 %205.0B248.7116.76
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC110.69 %205.0B226.9117.27
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC108.84 %205.0B223.1217.05
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-2
TowerAC104.07 %205.0B213.359.01
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-1
TowerAC104.07 %205.0B213.349.01
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#17625_05HAYES 138_B_SRT-A-1
BreakerAC103.86 %205.0B212.9211.44
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P2-2_#13951_05N PORTLN 69.0_2_SRT-A
BusAC102.02 %205.0B209.139.96
GD2AEP
AF1-118 TP-05SORENS 345.0 kV Ckt 2 line
AEP_P4_#4817_05SORENS 345_B2_SRT-A
BreakerAC107.66 %971.0B1045.349.78
GD2AEP
AF1-118 TP-05SORENS 345.0 kV Ckt 2 line
AEP_P4_#7449_05SORENS 345_B_SRT-A
BreakerAC106.32 %971.0B1032.369.63
GD2AEP
AF1-118 TP-05SORENS 345.0 kV Ckt 2 line
AEP_P4_#2896_05KEYSTN 345_A_SRT-A
BreakerAC101.91 %971.0B989.549.8
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
BreakerAC118.45 %1203.0B1424.985.13
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
BreakerAC116.03 %1203.0B1395.785.16
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16620_05ADKINS 345_A_SRT-A
BreakerAC115.99 %1203.0B1395.315.16
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
BreakerAC115.99 %1203.0B1395.35.16
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC115.08 %1203.0B1384.415.34
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-2
TowerAC103.58 %1203.0B1246.025.42
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P1-2_#762_8072_SRT-A
SingleAC102.19 %1203.0B1229.313.59
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P7-1_#11019___SRT-A-1
TowerAC102.16 %1203.0B1229.045.42
GD2AEP
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
BusAC101.86 %1203.0B1225.435.02
GD2AEP
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC138.82 %1868.0B2593.183.91
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC123.32 %255.0B314.4665.61
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#10528_05BLUFFP 138_D_SRT-A
BreakerAC106.68 %255.0B272.0265.62
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC106.64 %255.0B271.9433.24
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
BreakerAC106.62 %255.0B271.8733.24
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#11242_05BLUFFP 138_D1_SRT-A
BreakerAC106.61 %255.0B271.8665.62

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.47 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4606.26
MW Contribution:9.52
Bus #Bus NameTypeMW Contribution
24318905MLG2
50/50
4.888
270471AD2-092_GEN
Solar/Wind Harmer
3.8
946101AF1-275 GEN
Solar/Wind Harmer
1.564
970879AG2-548 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
6.355
971073AG2-665 GEN
Solar/Wind Harmer
4.434
24685805CER G1
Adder
8.39
24685905CER G2
Adder
8.39
942861AE2-305 GEN
Solar/Wind Harmer
7.89
270518AE2-148 GEN
Solar/Wind Harmer
12.226
24723005RIVRG1
Adder
18.943
24723105RIVRG2
Adder
18.943
970077AG2-063 GEN
Solar/Wind Harmer
5.44
972269AH1-719 GEN
Adder
2.314
962581AG1-107 GEN
Solar/Wind Harmer
4.971
961491AF2-440 GEN
Solar/Wind Harmer
2.066
253394AE2-221_GEN
Solar/Wind Harmer
4.473
253398AE2-221_GEN2
Solar/Wind Harmer
4.473
253317AC1-085 GEN4
Solar/Wind Harmer
8.238
25326109MON D
Adder
1.293
964601AG1-323 GEN
Solar/Wind Harmer
3.12
964601AG1-323 GEN
Solar/Wind Harmer
1.451
253370AE2-315 SEC1
Adder
1.967
270224U2-072_GEN2
Solar/Wind Harmer
1.941
270227U2-072_GEN3
Solar/Wind Harmer
1.941
270228U2-072_GEN4
Solar/Wind Harmer
1.941
270231U2-072_GEN5
Solar/Wind Harmer
1.941
25322209TAIT E
Adder
9.568
25322209TAIT E
Adder
9.353
270186AC1-089 GEN
Solar/Wind Harmer
5.991
972159AH1-661 GEN
Adder
0.977
938701AE1-092 GEN
Solar/Wind Harmer
20.234
25183208HLCRTG
Solar/Wind Harmer
5.927
252509AD1-136 GEN
Solar/Wind Harmer
0.25
252519AF1-045_GEN
Solar/Wind Harmer
5.924
23559101PLEAS2
50/50
11.904
23684101S70BUS1
50/50
0.301
23562301OGROV1
50/50
2.301
24721705FLATG2
Adder
24.275
962761AG1-125 GEN
Solar/Wind Harmer
36.289
970149AG2-104 GEN
Solar/Wind Harmer
44.817
970155AG2-107 GEN
Solar/Wind Harmer
15.824
270510AE1-227 GEN1
Solar/Wind Harmer
2.641
960001AF2-291 GEN
Solar/Wind Harmer
3.22
970947AG2-589 GEN
Solar/Wind Harmer
2.097
270331AC1-082 GEN3
Solar/Wind Harmer
0.474
270349AD2-093_GEN
Solar/Wind Harmer
3.8
927014AC1-188 GEN
Solar/Wind Harmer
1.647
270263AC1-001 GEN
Solar/Wind Harmer
1.075
270159DARBY CT4
Adder
8.977
24686105CER G3
Adder
8.446
24686505CER G6
Adder
8.435
253343AC1-166 GEN
Solar/Wind Harmer
1.099
253325AC1-069 GEN
Solar/Wind Harmer
1.06
24723205RIVRG3
Adder
18.943
970593AG2-378 GEN
Solar/Wind Harmer
2.015
253432AC1-085 GEN2
Solar/Wind Harmer
0.263
946171AF1-282 GEN
Solar/Wind Harmer
9.835
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
270223U2-072_GEN1
Solar/Wind Harmer
1.941
270578AF1-285 GEN2
Solar/Wind Harmer
1.187
270391AF1-285 GEN3
Solar/Wind Harmer
1.187
25326309TAIT D
Adder
1.075
960071AF2-298 GEN
Solar/Wind Harmer
4.886
252507AC2-088 GEN
Solar/Wind Harmer
1.752
25194608D.CRK4
Adder
1.598
270462AD2-086
Solar/Wind Harmer
6.754
25196808ZIMRHP
Adder
73.524
25196008MFTGT1
Adder
1.336
970333AG2-219 GEN
Solar/Wind Harmer
30.143
945681AF1-233 GEN
Solar/Wind Harmer
17.979
971995AH1-542 GEN
Solar/Wind Harmer
10.473
247536S-71 GEN
Solar/Wind Harmer
3.848
942081AE2-220 GEN
Solar/Wind Harmer
6.077
270239V3-007_GEN1
Solar/Wind Harmer
1.636
965651AG1-433 GEN
Solar/Wind Harmer
5.19
958861AF2-177 GEN
Solar/Wind Harmer
10.377
945371AF1-202 GEN
Solar/Wind Harmer
6.621
270005AE1-210 C O1
Solar/Wind Harmer
5.18
965031AG1-367 GEN
Solar/Wind Harmer
9.478
970825AG2-519 GEN
Solar/Wind Harmer
2.23
970091AG2-072 GEN
Adder
72.371
24728605AND G2
Adder
3.578
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.771
274774LINCOLN ;5U
Adder
7.771
274751CRETE EC ;1U
Adder
7.583
274754CRETE EC ;4U
Adder
7.583
274723RIVER EC ;12
Adder
16.483
274812UNIV PK N;8U
Adder
4.602
962771AG1-126 GEN
Solar/Wind Harmer
36.289
270330AC1-082 GEN2
Solar/Wind Harmer
0.803
270329AC1-082 GEN1
Solar/Wind Harmer
0.473
270054AF2-122 C O1
Solar/Wind Harmer
3.4
270520AE2-214 GEN
Solar/Wind Harmer
6.265
270459AD2-067 GEN
Solar/Wind Harmer
8.652
961821AG1-024 GEN
Solar/Wind Harmer
8.784
970879AG2-548 GEN
Solar/Wind Harmer
4.434
970689AG2-444 GEN
Solar/Wind Harmer
16.764
270432AC2-029 GEN
Solar/Wind Harmer
7.199
270269AC2-059
Solar/Wind Harmer
9.583
972203AH1-686 GEN
Adder
2.36
940611AE2-048 GEN
Solar/Wind Harmer
22.51
941391AE2-136 GEN
Solar/Wind Harmer
11.664
270284AF1-227 GEN1
Solar/Wind Harmer
5.777
270286AF1-227 GEN2
Solar/Wind Harmer
2.137
270287AF1-227 GEN3
Solar/Wind Harmer
2.137
270156DARBY CT1
Adder
9.122
270157DARBY CT2
Adder
9.1
270158DARBY CT3
Adder
8.955
945631AF1-228 GEN
Solar/Wind Harmer
4.774
253383AE2-342_GEN
Solar/Wind Harmer
0.9
241973AD2-163_GEN1
Solar/Wind Harmer
2.012
943861AF1-054 GEN
Solar/Wind Harmer
3.894
943851AF1-053 GEN
Solar/Wind Harmer
1.882
971985AH1-537 GEN
Solar/Wind Harmer
18.016
270340AC2-060 GEN
Solar/Wind Harmer
3.05
241972AD1-140 GEN
Solar/Wind Harmer
4.451
270367AC2-061_GEN
Solar/Wind Harmer
3.138
253372AE2-315 SEC3
Adder
1.861
253372AE2-315 SEC3
Adder
1.861
270578AF1-285 GEN2
Solar/Wind Harmer
0.457
25306009OHH W.
Adder
2.823
253349AC2-067 GEN
Solar/Wind Harmer
4.865
253400AC2-068 GEN
Solar/Wind Harmer
1.956
252524AE2-267 GEN
Solar/Wind Harmer
1.533
25196408WSDLE3
Adder
8.578
25196308WSDLE2
Adder
8.503
25196208WSDLE1
Adder
8.482
25196708WSDLE6
Adder
8.461
25196508WSDLE4
Adder
8.248
270302AB2-170 GEN
Solar/Wind Harmer
8.119
270317AD1-130_GEN
Solar/Wind Harmer
3.113
944031AF1-071 GEN
Solar/Wind Harmer
0.966
25196108MFTGT2
Adder
1.473
25196108MFTGT2
Adder
1.368
971673AH1-337 GEN
Solar/Wind Harmer
4.391
971029AG2-637 GEN
Solar/Wind Harmer
14.309
972163AH1-664 GEN
Solar/Wind Harmer
9.523
972165AH1-665 GEN
Solar/Wind Harmer
7.618
270543AE2-219 C
Solar/Wind Harmer
4.876
24729505KEY G4
Adder
6.165
270240V3-007_GEN2
Solar/Wind Harmer
5.881
958711AF2-162 GEN
Solar/Wind Harmer
0.961
965101AG1-375 GEN
Solar/Wind Harmer
9.494
945581AF1-223 GEN
Solar/Wind Harmer
4.304
961761AG1-017 GEN
Solar/Wind Harmer
0.406
970115AG2-085 GEN
Solar/Wind Harmer
3.786
24477305BRIDGE
Adder
0.323
274775LINCOLN ;6U
Adder
7.771
274776LINCOLN ;7U
Adder
7.771
274777LINCOLN ;8U
Adder
7.771
274814UNIV PK N;0U
Adder
4.642
274807UNIV PK N;3U
Adder
4.632
274805UNIV PK N;1U
Adder
4.612
274811UNIV PK N;7U
Adder
4.602
972037AH1-567 GEN1
Adder
0.168
972227AH1-698 GEN1
Adder
2.393
274827FISK ;RP
Adder
7.117
274687WILL CNTY;4U
Adder
25.585
274687WILL CNTY;4U
Adder
25.585
274731ELWOOD EC;2P
Adder
15.046
274733ELWOOD EC;3P
Adder
15.046
274735ELWOOD EC;4P
Adder
15.046
274728ELWOOD EC;5P
Adder
15.046
238109AE1-109 GEN2
Solar/Wind Helper
0.101
238110AE1-109 GEN3
Solar/Wind Helper
0.101
238126S14_GEN_1
Solar/Wind Helper
0.75
238152AF2-075_GEN
Solar/Wind Helper
0.615
23546401DTGZ2-030
Solar/Wind Helper
0.077
238208AF1-136 C
Solar/Wind Helper
0.191
23750501ELLIOTTS
Solar/Wind Helper
0.607
237085AD2-009_GEN
Solar/Wind Helper
1.43
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.761
316415AF1-147_GEN2
Solar/Wind Helper
0.761
270024AE2-089 GEN
Solar/Wind Harmer
0.702
23559001PLEAS1
50/50
11.904
23684201S70BUS2
50/50
0.306
23562401OGROV2
50/50
2.286
24318805MLG1
50/50
6.661
24721905FLATG4
Adder
24.275
970153AG2-106 GEN
Solar/Wind Harmer
15.824
270512AE1-227 GEN2
Solar/Wind Harmer
2.242
971191AH1-055 GEN
Solar/Wind Harmer
22.996
957541AF2-048 GEN
Solar/Wind Harmer
1.643
961921AG1-034 GEN
Solar/Wind Harmer
13.176
270291AC1-194 GEN
Solar/Wind Harmer
10.919
960801AF2-371 GEN
Solar/Wind Harmer
2.612
964871AG1-351 GEN
Solar/Wind Harmer
1.804
270273AD2-016 GEN
Solar/Wind Harmer
2.741
972173AH1-669 GEN
Solar/Wind Harmer
5.136
241955AC1-078 GEN
Solar/Wind Harmer
7.631
942051AE2-217 GEN
Solar/Wind Harmer
18.255
24686205CER G4
Adder
8.402
24686405CER G5
Adder
8.368
241974AD2-163_GEN2
Solar/Wind Harmer
2.012
253338AC1-165 GEN
Solar/Wind Harmer
1.099
253333AC1-068 GEN
Solar/Wind Harmer
1.06
970605AG2-385 GEN
Solar/Wind Harmer
5.44
253415AE1-040 GEN
Solar/Wind Harmer
1.134
253406AD2-031_GEN
Solar/Wind Harmer
1.265
253316AC1-085 GEN3
Solar/Wind Harmer
8.238
253433AC1-085 GEN1
Solar/Wind Harmer
5.23
946181AF1-283 GEN
Solar/Wind Harmer
12.786
253303V4-073 C
Solar/Wind Harmer
0.114
253370AE2-315 SEC1
Adder
1.967
253371AE2-315 SEC2
Adder
1.861
942871AE2-306 GEN
Solar/Wind Harmer
0.89
270391AF1-285 GEN3
Solar/Wind Harmer
0.457
252510AF1-249 C
Solar/Wind Harmer
0.407
25196608WSDLE5
Adder
8.333
25194608D.CRK4
Adder
1.598
270485AE1-090_GEN
Solar/Wind Harmer
0.587
270222AC2-111 GEN
Solar/Wind Harmer
7.836
25196008MFTGT1
Adder
1.294
970243AG2-164 GEN
Solar/Wind Harmer
24.663
970519AG2-331 GEN
Solar/Wind Harmer
16.569
970699AG2-449 GEN
Solar/Wind Harmer
10.961
972167AH1-666 GEN
Solar/Wind Harmer
7.633
958171AF2-111 GEN
Solar/Wind Harmer
23.849
944531AF1-118 GEN
Solar/Wind Harmer
33.274
270437AC2-090 C
Solar/Wind Harmer
5.307
962031AG1-047 GEN
Solar/Wind Harmer
2.867
957741AF2-068 GEN
Solar/Wind Harmer
14.228
946031AF1-268 GEN
Solar/Wind Harmer
7.867
958821AF2-173 GEN
Solar/Wind Harmer
13.269
270004AE1-209 GEN
Solar/Wind Harmer
5.18
270356AE2-297 GEN
Solar/Wind Harmer
4.32
24728705AND G3
Adder
7.484
24728505AND G1
Adder
3.578
24642205MAYFLWER
Adder
0.588
274772LINCOLN ;3U
Adder
7.771
274752CRETE EC ;2U
Adder
7.583
274753CRETE EC ;3U
Adder
7.583
274724RIVER EC ;11
Adder
16.291
274802UNIV PARK;5U
Adder
5.35
972228AH1-698 GEN2
Adder
3.398
274826FISK ;BP
Adder
10.043
274800UNIV PARK;3U
Adder
5.348
972038AH1-567 GEN2
Adder
0.335
274729ELWOOD EC;1P
Adder
15.046
274730ELWOOD EC;6P
Adder
15.046
316097T157 G90
Solar/Wind Helper
1.335
964991AG1-363 GEN
Solar/Wind Helper
4.295
23750701CROSSCHOOL
Solar/Wind Helper
1.345
238127S14_GEN_2
Solar/Wind Helper
0.75
238118U2-030_1
Solar/Wind Helper
0.309
238148AE2-230_GEN2
Solar/Wind Helper
0.432
237080AD1-060 GEN
Solar/Wind Helper
0.295
237038AE2-054 C
Solar/Wind Helper
0.236
235062AE1-101 C1
Solar/Wind Helper
1.439
23779801AA1-109
Solar/Wind Helper
0.167
971617AH1-308 GEN
Solar/Wind Harmer
0.869
252516AE2-318_GEN
Solar/Wind Harmer
4.519
253378AE2-206_GEN
Solar/Wind Harmer
3.5
276820AF1-078_GEN
Solar/Wind Harmer
1.555
25194408D.CRK1
Adder
7.352
25194508D.CRK3
Adder
1.375
25326509SID D
Adder
1.274
970239AG2-162 GEN
Solar/Wind Harmer
10.505
24728805RICHG1
Adder
3.601
24728905RICHG2
Adder
3.601
970883AG2-550 GEN
Solar/Wind Harmer
9.522
970885AG2-551 GEN
Solar/Wind Harmer
2.214
270383AD1-128 GEN
Solar/Wind Harmer
5.808
24379505HDWTR1G C
Solar/Wind Harmer
7.516
270209AC1-174_GEN
Solar/Wind Harmer
5.304
926881AC1-175 GEN
Solar/Wind Harmer
5.304
944541AF1-119 GEN
Solar/Wind Harmer
3.977
960971AF2-388 GEN
Solar/Wind Harmer
10.38
247621Y3-024
Adder
0.229
270201AC2-176 GEN
Solar/Wind Harmer
4.876
964611AG1-324 GEN
Solar/Wind Harmer
1.118
964611AG1-324 GEN
Solar/Wind Harmer
0.496
970825AG2-519 GEN
Solar/Wind Harmer
9.992
960441AF2-335 GEN
Solar/Wind Harmer
9.465
247620Y3-023
Adder
0.427
274770LINCOLN ;1U
Adder
7.771
274771LINCOLN ;2U
Adder
7.771
274808UNIV PK N;4U
Adder
4.582
274803UNIV PARK;6U
Adder
5.35
972259AH1-714 GEN
Adder
17.495
23585401KL_K28_T16
Solar/Wind Helper
1.401
238120AE2-309 GEN
Solar/Wind Helper
0.474
238175AF1-290_GEN
Solar/Wind Helper
0.131
238169AE2-226 GEN1
Solar/Wind Helper
0.604
238170AE2-226 GEN2
Solar/Wind Helper
0.604
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.152
235063AE1-101 C2
Solar/Wind Helper
1.439
237002AB1-128_GEN
Solar/Wind Helper
0.384
237001AB1-127_GEN
Solar/Wind Helper
0.383
237034AC2-136 C
Solar/Wind Helper
0.196
23777801MSM_W1-116
Solar/Wind Helper
0.099
237025AB1-124 C
Solar/Wind Helper
0.143
237006AB1-125 GEN
Solar/Wind Helper
0.107
274801UNIV PARK;4U
Adder
5.348
274732ELWOOD EC;7P
Adder
8.785
23751101LEADS_P59
Solar/Wind Helper
1.563
23583801GRNGAP
Solar/Wind Helper
4.994
316095T157 G97
Solar/Wind Helper
1.335
23751201ROTHROCK
Solar/Wind Helper
0.822
238185AF2-356 C
Solar/Wind Helper
2.423
23562501BACKB
Solar/Wind Helper
1.01
235054AD2-180 GEN
Solar/Wind Helper
1.889
238108AE1-109 GEN1
Solar/Wind Helper
0.101
235531U2-073 GEN
Solar/Wind Helper
2.957
238117U2-030
Solar/Wind Helper
0.309
238147AE2-230_GEN1
Solar/Wind Helper
0.431
238149AF1-291A_GEN
Solar/Wind Helper
0.123
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.237
235067AD1-061 GEN
Solar/Wind Helper
0.429
237030AB1-096 C
Solar/Wind Helper
0.061
944201AF1-088_MTX
Adder
106.917
957141AF2-008_MTX
Adder
53.458
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.934
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.919
MECLTFEXP_MEC->PJM
CLTF
14.518
SIGELTFEXP_SIGE->PJM
CLTF
0.468
CPLELTFEXP_CPLE->PJM
CLTF
1.268
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.814
LAGNLTFEXP_LAGN->PJM
CLTF
14.208
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.03
TVALTFEXP_TVA->PJM
CLTF
7.054
NYPJM->LTFIMP_NY
CLTF
4.499
LGEELTFEXP_LGEE->PJM
CLTF
6.294
WECLTFEXP_WEC->PJM
CLTF
3.447
AG2-052LTFEXP_AG2-052->PJM
LTF
0.215
AH1-155LTFEXP_AH1-155->PJM
LTF
0.322

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.45 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4605.38
MW Contribution:9.48
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
970689AG2-444 GEN
Solar/Wind Harmer
16.696
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270024AE2-089 GEN
Solar/Wind Harmer
0.699
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
971617AH1-308 GEN
Solar/Wind Harmer
0.866
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.43 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4604.68
MW Contribution:9.48
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
36.157
270330AC1-082 GEN2
Solar/Wind Harmer
0.8
270329AC1-082 GEN1
Solar/Wind Harmer
0.471
270054AF2-122 C O1
Solar/Wind Harmer
3.386
270520AE2-214 GEN
Solar/Wind Harmer
6.239
270459AD2-067 GEN
Solar/Wind Harmer
8.614
961821AG1-024 GEN
Solar/Wind Harmer
8.746
970879AG2-548 GEN
Solar/Wind Harmer
4.417
970689AG2-444 GEN
Solar/Wind Harmer
16.696
270432AC2-029 GEN
Solar/Wind Harmer
7.17
270269AC2-059
Solar/Wind Harmer
9.545
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
22.396
941391AE2-136 GEN
Solar/Wind Harmer
11.605
270284AF1-227 GEN1
Solar/Wind Harmer
5.752
270286AF1-227 GEN2
Solar/Wind Harmer
2.128
270287AF1-227 GEN3
Solar/Wind Harmer
2.128
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
4.754
253383AE2-342_GEN
Solar/Wind Harmer
0.896
241973AD2-163_GEN1
Solar/Wind Harmer
2.003
943861AF1-054 GEN
Solar/Wind Harmer
3.878
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
17.95
270340AC2-060 GEN
Solar/Wind Harmer
3.039
241972AD1-140 GEN
Solar/Wind Harmer
4.433
270367AC2-061_GEN
Solar/Wind Harmer
3.127
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
4.845
253400AC2-068 GEN
Solar/Wind Harmer
1.948
252524AE2-267 GEN
Solar/Wind Harmer
1.528
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
8.082
270317AD1-130_GEN
Solar/Wind Harmer
3.098
944031AF1-071 GEN
Solar/Wind Harmer
0.962
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.374
971029AG2-637 GEN
Solar/Wind Harmer
14.252
972163AH1-664 GEN
Solar/Wind Harmer
9.488
972165AH1-665 GEN
Solar/Wind Harmer
7.591
270543AE2-219 C
Solar/Wind Harmer
4.856
270240V3-007_GEN2
Solar/Wind Harmer
5.858
24729505KEY G4
Adder
6.141
958711AF2-162 GEN
Solar/Wind Harmer
0.957
965101AG1-375 GEN
Solar/Wind Harmer
9.456
945581AF1-223 GEN
Solar/Wind Harmer
4.286
961761AG1-017 GEN
Solar/Wind Harmer
0.404
970115AG2-085 GEN
Solar/Wind Harmer
3.771
24477305BRIDGE
Adder
0.321
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
15.766
270512AE1-227 GEN2
Solar/Wind Harmer
2.228
971191AH1-055 GEN
Solar/Wind Harmer
22.913
957541AF2-048 GEN
Solar/Wind Harmer
1.637
961921AG1-034 GEN
Solar/Wind Harmer
13.119
270291AC1-194 GEN
Solar/Wind Harmer
10.875
960801AF2-371 GEN
Solar/Wind Harmer
2.601
964871AG1-351 GEN
Solar/Wind Harmer
1.796
270273AD2-016 GEN
Solar/Wind Harmer
2.73
972173AH1-669 GEN
Solar/Wind Harmer
5.115
241955AC1-078 GEN
Solar/Wind Harmer
7.599
942051AE2-217 GEN
Solar/Wind Harmer
18.179
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
2.003
253338AC1-165 GEN
Solar/Wind Harmer
1.094
253333AC1-068 GEN
Solar/Wind Harmer
1.056
970605AG2-385 GEN
Solar/Wind Harmer
5.418
253415AE1-040 GEN
Solar/Wind Harmer
1.129
253406AD2-031_GEN
Solar/Wind Harmer
1.261
253316AC1-085 GEN3
Solar/Wind Harmer
8.207
253433AC1-085 GEN1
Solar/Wind Harmer
5.21
946181AF1-283 GEN
Solar/Wind Harmer
12.737
253303V4-073 C
Solar/Wind Harmer
0.113
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
942871AE2-306 GEN
Solar/Wind Harmer
0.886
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
252510AF1-249 C
Solar/Wind Harmer
0.405
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.584
270222AC2-111 GEN
Solar/Wind Harmer
7.805
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
24.571
970519AG2-331 GEN
Solar/Wind Harmer
16.508
970699AG2-449 GEN
Solar/Wind Harmer
10.921
972167AH1-666 GEN
Solar/Wind Harmer
7.605
958171AF2-111 GEN
Solar/Wind Harmer
23.761
944531AF1-118 GEN
Solar/Wind Harmer
33.14
270437AC2-090 C
Solar/Wind Harmer
5.286
962031AG1-047 GEN
Solar/Wind Harmer
2.855
957741AF2-068 GEN
Solar/Wind Harmer
14.171
958821AF2-173 GEN
Solar/Wind Harmer
13.216
270004AE1-209 GEN
Solar/Wind Harmer
5.159
946031AF1-268 GEN
Solar/Wind Harmer
7.836
270356AE2-297 GEN
Solar/Wind Harmer
4.303
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
24642205MAYFLWER
Adder
0.585
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
274802UNIV PARK;5U
Adder
5.329
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
36.157
970149AG2-104 GEN
Solar/Wind Harmer
44.654
970155AG2-107 GEN
Solar/Wind Harmer
15.766
960001AF2-291 GEN
Solar/Wind Harmer
3.209
270510AE1-227 GEN1
Solar/Wind Harmer
2.625
970947AG2-589 GEN
Solar/Wind Harmer
2.09
270331AC1-082 GEN3
Solar/Wind Harmer
0.472
270349AD2-093_GEN
Solar/Wind Harmer
3.785
927014AC1-188 GEN
Solar/Wind Harmer
1.641
270263AC1-001 GEN
Solar/Wind Harmer
1.071
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
1.094
253325AC1-069 GEN
Solar/Wind Harmer
1.056
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
2.007
253432AC1-085 GEN2
Solar/Wind Harmer
0.262
946171AF1-282 GEN
Solar/Wind Harmer
9.798
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
1.932
270578AF1-285 GEN2
Solar/Wind Harmer
1.182
270391AF1-285 GEN3
Solar/Wind Harmer
1.182
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
4.866
252507AC2-088 GEN
Solar/Wind Harmer
1.745
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
6.724
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
30.032
945681AF1-233 GEN
Solar/Wind Harmer
17.913
971995AH1-542 GEN
Solar/Wind Harmer
10.422
247536S-71 GEN
Solar/Wind Harmer
3.833
942081AE2-220 GEN
Solar/Wind Harmer
6.053
270239V3-007_GEN1
Solar/Wind Harmer
1.629
965651AG1-433 GEN
Solar/Wind Harmer
5.169
958861AF2-177 GEN
Solar/Wind Harmer
10.335
945371AF1-202 GEN
Solar/Wind Harmer
6.594
270005AE1-210 C O1
Solar/Wind Harmer
5.159
965031AG1-367 GEN
Solar/Wind Harmer
9.44
970825AG2-519 GEN
Solar/Wind Harmer
2.221
970091AG2-072 GEN
Adder
72.107
24728605AND G2
Adder
3.565
24639705ELKHART HY
Adder
0.142
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
274812UNIV PK N;8U
Adder
4.584
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
971617AH1-308 GEN
Solar/Wind Harmer
0.866
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
3.785
946101AF1-275 GEN
Solar/Wind Harmer
1.557
970879AG2-548 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
6.331
971073AG2-665 GEN
Solar/Wind Harmer
4.417
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
7.857
270518AE2-148 GEN
Solar/Wind Harmer
12.175
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
5.418
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
4.952
961491AF2-440 GEN
Solar/Wind Harmer
2.058
253394AE2-221_GEN
Solar/Wind Harmer
4.456
253398AE2-221_GEN2
Solar/Wind Harmer
4.456
253317AC1-085 GEN4
Solar/Wind Harmer
8.207
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
1.445
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
1.932
270227U2-072_GEN3
Solar/Wind Harmer
1.932
270228U2-072_GEN4
Solar/Wind Harmer
1.932
270231U2-072_GEN5
Solar/Wind Harmer
1.932
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
5.968
938701AE1-092 GEN
Solar/Wind Harmer
20.142
25183208HLCRTG
Solar/Wind Harmer
5.905
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.249
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
4.502
253378AE2-206_GEN
Solar/Wind Harmer
3.485
276820AF1-078_GEN
Solar/Wind Harmer
1.548
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
10.466
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
9.484
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
5.785
24379505HDWTR1G C
Solar/Wind Harmer
7.487
270209AC1-174_GEN
Solar/Wind Harmer
5.284
926881AC1-175 GEN
Solar/Wind Harmer
5.284
944541AF1-119 GEN
Solar/Wind Harmer
3.962
960971AF2-388 GEN
Solar/Wind Harmer
10.338
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
4.857
964611AG1-324 GEN
Solar/Wind Harmer
1.114
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
9.953
960441AF2-335 GEN
Solar/Wind Harmer
9.427
247620Y3-023
Adder
0.425
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
972259AH1-714 GEN
Adder
17.426
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
270024AE2-089 GEN
Solar/Wind Harmer
0.699
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.65 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.96
MW Contribution:6.62
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.64 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4574.63
MW Contribution:6.62
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
30.492
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
23559001PLEAS1
50/50
11.891
23684201S70BUS2
50/50
0.305
23562401OGROV2
50/50
2.277
24318805MLG1
50/50
6.637
24721905FLATG4
Adder
24.202
970153AG2-106 GEN
Solar/Wind Harmer
19.471
270512AE1-227 GEN2
Solar/Wind Harmer
1.892
971191AH1-055 GEN
Solar/Wind Harmer
18.65
961921AG1-034 GEN
Solar/Wind Harmer
6.407
270291AC1-194 GEN
Solar/Wind Harmer
5.661
270273AD2-016 GEN
Solar/Wind Harmer
0.74
972173AH1-669 GEN
Solar/Wind Harmer
3.569
241955AC1-078 GEN
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
12.683
24686205CER G4
Adder
8.375
24686405CER G5
Adder
8.342
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
970605AG2-385 GEN
Solar/Wind Harmer
4.258
253415AE1-040 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.512
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.886
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270391AF1-285 GEN3
Solar/Wind Harmer
0.455
970191AG2-125 GEN
Solar/Wind Harmer
1.745
252510AF1-249 C
Solar/Wind Harmer
0.052
25196608WSDLE5
Adder
8.301
25194608D.CRK4
Adder
1.592
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.385
25196008MFTGT1
Adder
1.289
970243AG2-164 GEN
Solar/Wind Harmer
3.888
970519AG2-331 GEN
Solar/Wind Harmer
17.281
970699AG2-449 GEN
Solar/Wind Harmer
1.662
972167AH1-666 GEN
Solar/Wind Harmer
5.306
958171AF2-111 GEN
Solar/Wind Harmer
16.577
944531AF1-118 GEN
Solar/Wind Harmer
29.606
270437AC2-090 C
Solar/Wind Harmer
0.003
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.887
958821AF2-173 GEN
Solar/Wind Harmer
9.221
270004AE1-209 GEN
Solar/Wind Harmer
1.427
946031AF1-268 GEN
Solar/Wind Harmer
6.268
270356AE2-297 GEN
Solar/Wind Harmer
0.009
971617AH1-308 GEN
Solar/Wind Harmer
5.478
970513AG2-328 GEN
Solar/Wind Harmer
2.844
970517AG2-330 GEN
Solar/Wind Harmer
17.067
970289AG2-191 GEN
Solar/Wind Harmer
0.722
970291AG2-192 GEN
Solar/Wind Harmer
0.656
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.199
959331AF2-224 GEN
Solar/Wind Harmer
4.573
965021AG1-366 GEN
Solar/Wind Harmer
2.178
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.042
970349AG2-230 GEN
Solar/Wind Harmer
9.745
24318905MLG2
50/50
4.855
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.448
24685805CER G1
Adder
8.364
24685905CER G2
Adder
8.364
942861AE2-305 GEN
Solar/Wind Harmer
5.482
270518AE2-148 GEN
Solar/Wind Harmer
0.606
24723005RIVRG1
Adder
18.885
24723105RIVRG2
Adder
18.885
970077AG2-063 GEN
Solar/Wind Harmer
4.025
972269AH1-719 GEN
Adder
2.302
962581AG1-107 GEN
Solar/Wind Harmer
0.001
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.288
964601AG1-323 GEN
Solar/Wind Harmer
2.731
964601AG1-323 GEN
Solar/Wind Harmer
1.82
253370AE2-315 SEC1
Adder
1.959
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
25322209TAIT E
Adder
9.53
25322209TAIT E
Adder
9.316
270186AC1-089 GEN
Solar/Wind Harmer
0.004
938701AE1-092 GEN
Solar/Wind Harmer
10.928
971655AH1-328 GEN
Solar/Wind Harmer
2.415
25183208HLCRTG
Solar/Wind Harmer
0.011
972159AH1-661 GEN
Adder
0.972
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.902
252516AE2-318_GEN
Solar/Wind Harmer
5.235
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.92
25194408D.CRK1
Adder
7.324
25194508D.CRK3
Adder
1.369
25326509SID D
Adder
1.268
970239AG2-162 GEN
Solar/Wind Harmer
1.662
24728805RICHG1
Adder
3.587
24728905RICHG2
Adder
3.587
970883AG2-550 GEN
Solar/Wind Harmer
6.617
970885AG2-551 GEN
Solar/Wind Harmer
2.206
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
944541AF1-119 GEN
Solar/Wind Harmer
0.442
960971AF2-388 GEN
Solar/Wind Harmer
3.871
247621Y3-024
Adder
0.228
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.494
970825AG2-519 GEN
Solar/Wind Harmer
7.293
960441AF2-335 GEN
Solar/Wind Harmer
6.577
270599AE1-208 GEN
Solar/Wind Harmer
6.026
270031AE2-169
Solar/Wind Harmer
3.616
942221AE2-234 GEN
Solar/Wind Harmer
0.033
971613AH1-306 GEN
Solar/Wind Harmer
3.153
970321AG2-212 GEN
Solar/Wind Harmer
2.844
970611AG2-400 GEN
Solar/Wind Harmer
6.533
970627AG2-408 GEN
Solar/Wind Harmer
1.96
246938BC-WTG3
Solar/Wind Harmer
0.235
246937BC-WTG2
Solar/Wind Harmer
0.263
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.948
970235AG2-159 GEN
Solar/Wind Harmer
2.265
971199AH1-059 GEN
Solar/Wind Harmer
2.587
339221AD2-048_GEN
Solar/Wind Harmer
0.004
966841AG1-555 GEN
Solar/Wind Harmer
0.73
965681AG1-436 GEN
Solar/Wind Harmer
8.059
965791AG1-447 GEN
Solar/Wind Harmer
5.91
270007AE1-245 C
Solar/Wind Harmer
0.002
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.425
270526AF1-158 GEN
Solar/Wind Harmer
0.008
972043AH1-570 GEN
Solar/Wind Harmer
1.674
972045AH1-571 GEN
Solar/Wind Harmer
1.341
24441505OLIV SLR
Solar/Wind Harmer
0
970241AG2-163 GEN
Solar/Wind Harmer
3.747
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
12.817
961051AF2-396 GEN
Solar/Wind Harmer
8.545
274770LINCOLN ;1U
Adder
7.74
274771LINCOLN ;2U
Adder
7.74
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.687
970623AG2-406 GEN
Solar/Wind Harmer
1.169
274808UNIV PK N;4U
Adder
4.563
274803UNIV PARK;6U
Adder
5.329
274888KELLY CRK;1U
Solar/Wind Harmer
0.375
274887GEN-1.85
Solar/Wind Harmer
0.168
276843GEN-1.7
Solar/Wind Harmer
0.206
945391AF1-204 GEN
Solar/Wind Harmer
6.775
958011AF2-095 GEN
Solar/Wind Harmer
9.182
972259AH1-714 GEN
Adder
17.426
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
2.546
970107AG2-081 GEN
Solar/Wind Harmer
1.909
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
4.195
944971AF1-162 GEN
Solar/Wind Harmer
6.345
958481AF2-142 GEN
Solar/Wind Harmer
9.506
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.857
971573AH1-285 GEN
Solar/Wind Harmer
1.18
958491AF2-143 GEN
Solar/Wind Harmer
9.485
274879MINONK ;1U
Solar/Wind Harmer
0.267
23585401KL_K28_T16
Solar/Wind Helper
1.442
238120AE2-309 GEN
Solar/Wind Helper
0.483
238175AF1-290_GEN
Solar/Wind Helper
0.13
238169AE2-226 GEN1
Solar/Wind Helper
0.6
238170AE2-226 GEN2
Solar/Wind Helper
0.6
235020AA1-095 C
Solar/Wind Helper
0.045
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.271
970879AG2-548 GEN
Solar/Wind Harmer
6.448
970689AG2-444 GEN
Solar/Wind Harmer
14.59
270432AC2-029 GEN
Solar/Wind Harmer
3.168
270269AC2-059
Solar/Wind Harmer
0.004
972203AH1-686 GEN
Adder
2.352
940611AE2-048 GEN
Solar/Wind Harmer
17.483
941391AE2-136 GEN
Solar/Wind Harmer
9.848
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
9.085
270157DARBY CT2
Adder
9.063
270158DARBY CT3
Adder
8.918
945631AF1-228 GEN
Solar/Wind Harmer
0
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.706
943851AF1-053 GEN
Solar/Wind Harmer
1.874
971985AH1-537 GEN
Solar/Wind Harmer
2.087
270340AC2-060 GEN
Solar/Wind Harmer
0.008
241972AD1-140 GEN
Solar/Wind Harmer
0.755
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.853
253372AE2-315 SEC3
Adder
1.853
270578AF1-285 GEN2
Solar/Wind Harmer
0.455
25306009OHH W.
Adder
2.812
253349AC2-067 GEN
Solar/Wind Harmer
2.136
253400AC2-068 GEN
Solar/Wind Harmer
0.859
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.545
25196308WSDLE2
Adder
8.471
25196208WSDLE1
Adder
8.45
25196708WSDLE6
Adder
8.428
25196508WSDLE4
Adder
8.216
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.01
971653AH1-327 GEN
Solar/Wind Harmer
0.947
25196108MFTGT2
Adder
1.467
25196108MFTGT2
Adder
1.362
971673AH1-337 GEN
Solar/Wind Harmer
4.312
971029AG2-637 GEN
Solar/Wind Harmer
9.944
972163AH1-664 GEN
Solar/Wind Harmer
7.37
972165AH1-665 GEN
Solar/Wind Harmer
5.903
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
6.141
965101AG1-375 GEN
Solar/Wind Harmer
6.597
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.631
270024AE2-089 GEN
Solar/Wind Harmer
0.007
971609AH1-304 GEN
Solar/Wind Harmer
1.074
270071AF1-092 GEN
Solar/Wind Harmer
12.598
270594AE1-207 GEN
Solar/Wind Harmer
7.357
970289AG2-191 GEN
Solar/Wind Harmer
1.247
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.837
965051AG1-369 GEN
Solar/Wind Harmer
3.247
971347AH1-153 GEN
Solar/Wind Harmer
9.745
965041AG1-368 GEN
Solar/Wind Harmer
6.496
957201AF2-014 GEN
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.821
971611AH1-305 GEN
Solar/Wind Harmer
3.852
958391AF2-133 GEN
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
971771AH1-392 GEN
Solar/Wind Harmer
6.442
971769AH1-391 GEN
Solar/Wind Harmer
7.189
963841AG1-237 GEN
Solar/Wind Harmer
2.789
24477305BRIDGE
Adder
0.321
971619AH1-309 GEN
Solar/Wind Harmer
2.888
274775LINCOLN ;6U
Adder
7.74
274776LINCOLN ;7U
Adder
7.74
274777LINCOLN ;8U
Adder
7.74
274814UNIV PK N;0U
Adder
4.624
274807UNIV PK N;3U
Adder
4.614
274805UNIV PK N;1U
Adder
4.594
274811UNIV PK N;7U
Adder
4.584
972037AH1-567 GEN1
Adder
0.167
960591AF2-350 GEN
Solar/Wind Harmer
6.377
972227AH1-698 GEN1
Adder
2.383
274827FISK ;RP
Adder
7.089
970179AG2-119 GEN
Solar/Wind Harmer
5.69
274687WILL CNTY;4U
Adder
25.484
274687WILL CNTY;4U
Adder
25.484
274731ELWOOD EC;2P
Adder
14.987
274733ELWOOD EC;3P
Adder
14.987
274735ELWOOD EC;4P
Adder
14.987
274728ELWOOD EC;5P
Adder
14.987
23559101PLEAS2
50/50
11.891
23684101S70BUS1
50/50
0.299
23562301OGROV1
50/50
2.291
24721705FLATG2
Adder
24.202
962761AG1-125 GEN
Solar/Wind Harmer
30.492
970149AG2-104 GEN
Solar/Wind Harmer
32.932
970155AG2-107 GEN
Solar/Wind Harmer
19.471
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
270510AE1-227 GEN1
Solar/Wind Harmer
1.892
970947AG2-589 GEN
Solar/Wind Harmer
0.243
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Harmer
0.005
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.716
270159DARBY CT4
Adder
8.94
24686105CER G3
Adder
8.419
24686505CER G6
Adder
8.408
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
24723205RIVRG3
Adder
18.885
970593AG2-378 GEN
Solar/Wind Harmer
1.575
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.836
253370AE2-315 SEC1
Adder
1.959
253371AE2-315 SEC2
Adder
1.853
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25326309TAIT D
Adder
1.071
960071AF2-298 GEN
Solar/Wind Harmer
3.39
252507AC2-088 GEN
Solar/Wind Harmer
0.308
25194608D.CRK4
Adder
1.592
25196808ZIMRHP
Adder
73.247
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.331
970333AG2-219 GEN
Solar/Wind Harmer
4.752
945681AF1-233 GEN
Solar/Wind Harmer
12.498
971995AH1-542 GEN
Solar/Wind Harmer
2.424
247536S-71 GEN
Solar/Wind Harmer
0.266
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.843
965651AG1-433 GEN
Solar/Wind Harmer
1.936
958861AF2-177 GEN
Solar/Wind Harmer
2.859
945371AF1-202 GEN
Solar/Wind Harmer
0.001
270005AE1-210 C O1
Solar/Wind Harmer
1.427
965031AG1-367 GEN
Solar/Wind Harmer
6.586
970773AG2-487 GEN
Solar/Wind Harmer
1.163
970825AG2-519 GEN
Solar/Wind Harmer
2.336
270032AE2-172
Solar/Wind Harmer
4.379
970245AG2-165 GEN
Solar/Wind Harmer
2.844
970291AG2-192 GEN
Solar/Wind Harmer
0.853
970091AG2-072 GEN
Adder
72.107
276903AD2-071 C
Solar/Wind Harmer
7.32
965011AG1-365 GEN
Solar/Wind Harmer
6.533
247521TR3_G114
Solar/Wind Harmer
0.237
270246TR4_N_V150
Solar/Wind Harmer
0.042
965421AG1-410 GEN
Solar/Wind Harmer
19.465
24728605AND G2
Adder
3.565
246936BC-WTG1
Solar/Wind Harmer
0.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.843
24695305TIMB G C
Solar/Wind Harmer
0.002
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.087
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.406
958381AF2-132 GEN
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.005
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.568
339216AC1-074 GEN
Solar/Wind Harmer
0.177
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.142
963741AG1-226 GEN
Solar/Wind Harmer
15.2
945111AF1-176 GEN
Solar/Wind Harmer
11.453
270505AE1-170 C O1
Solar/Wind Harmer
6.739
970833AG2-524 GEN
Solar/Wind Harmer
6.995
970833AG2-524 GEN
Solar/Wind Harmer
4.664
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.327
276868AE1-113 GEN
Solar/Wind Harmer
1.267
276882AE2-255 GEN
Solar/Wind Harmer
0.739
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
238126S14_GEN_1
Solar/Wind Helper
0.764
23750501ELLIOTTS
Solar/Wind Helper
0.636
238152AF2-075_GEN
Solar/Wind Helper
0.611
238208AF1-136 C
Solar/Wind Helper
0.19
23546401DTGZ2-030
Solar/Wind Helper
0.077
237085AD2-009_GEN
Solar/Wind Helper
1.425
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.754
316415AF1-147_GEN2
Solar/Wind Helper
0.754
24728705AND G3
Adder
7.455
24728505AND G1
Adder
3.565
270491AE1-102 GEN2
Solar/Wind Harmer
0.843
970031AG2-029 GEN
Solar/Wind Harmer
4.207
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.466
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.585
945111AF1-176 GEN
Solar/Wind Harmer
5.203
274772LINCOLN ;3U
Adder
7.74
274752CRETE EC ;2U
Adder
7.553
274753CRETE EC ;3U
Adder
7.553
274724RIVER EC ;11
Adder
16.226
270258AD1-119 GEN
Solar/Wind Harmer
0.002
274802UNIV PARK;5U
Adder
5.329
276806AD2-047 C O1
Solar/Wind Harmer
3.613
970193AG2-126 GEN
Solar/Wind Harmer
9.564
970941AG2-585 GEN
Solar/Wind Harmer
7.971
972228AH1-698 GEN2
Adder
3.385
274826FISK ;BP
Adder
10.003
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
274800UNIV PARK;3U
Adder
5.327
972038AH1-567 GEN2
Adder
0.333
970707AG2-453 GEN
Solar/Wind Harmer
20.817
24441205WTRV SLR C
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.252
274729ELWOOD EC;1P
Adder
14.987
274730ELWOOD EC;6P
Adder
14.987
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270053AF1-130 C
Solar/Wind Harmer
1.432
943121AE2-341 GEN
Solar/Wind Harmer
10.635
943591AF1-030 GEN
Solar/Wind Harmer
7.072
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.266
316097T157 G90
Solar/Wind Helper
1.323
23750701CROSSCHOOL
Solar/Wind Helper
1.364
238118U2-030_1
Solar/Wind Helper
0.318
238127S14_GEN_2
Solar/Wind Helper
0.764
238148AE2-230_GEN2
Solar/Wind Helper
0.429
237048AF1-022 C
Solar/Wind Helper
0.17
237080AD1-060 GEN
Solar/Wind Helper
0.294
237038AE2-054 C
Solar/Wind Helper
0.235
235062AE1-101 C1
Solar/Wind Helper
1.433
23779801AA1-109
Solar/Wind Helper
0.166
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.342
274773LINCOLN ;4U
Adder
7.74
274774LINCOLN ;5U
Adder
7.74
274751CRETE EC ;1U
Adder
7.553
274754CRETE EC ;4U
Adder
7.553
274723RIVER EC ;12
Adder
16.418
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.584
276776AD2-060 GEN
Solar/Wind Harmer
0.666
941551AE2-152 GEN
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
5.327
274732ELWOOD EC;7P
Adder
8.75
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.75
276691AA1-018 GEN1
Solar/Wind Harmer
0.768
944231AF1-091 GEN
Solar/Wind Harmer
1.688
276901AD2-066 C O1
Solar/Wind Harmer
0.006
971997AH1-543 GEN
Solar/Wind Harmer
3.315
23751101LEADS_P59
Solar/Wind Helper
1.597
23751201ROTHROCK
Solar/Wind Helper
0.849
23562501BACKB
Solar/Wind Helper
1.042
23583801GRNGAP
Solar/Wind Helper
4.948
316095T157 G97
Solar/Wind Helper
1.323
238185AF2-356 C
Solar/Wind Helper
2.474
235054AD2-180 GEN
Solar/Wind Helper
1.935
238117U2-030
Solar/Wind Helper
0.318
238108AE1-109 GEN1
Solar/Wind Helper
0.102
235531U2-073 GEN
Solar/Wind Helper
3.033
238147AE2-230_GEN1
Solar/Wind Helper
0.427
238149AF1-291A_GEN
Solar/Wind Helper
0.122
237061AD1-155 GEN
Solar/Wind Helper
0.046
238221AF1-254 C O1
Solar/Wind Helper
0.235
235067AD1-061 GEN
Solar/Wind Helper
0.427
237030AB1-096 C
Solar/Wind Helper
0.061
23777901MDS_W4-102
Solar/Wind Helper
0.151
235063AE1-101 C2
Solar/Wind Helper
1.433
237002AB1-128_GEN
Solar/Wind Helper
0.382
237001AB1-127_GEN
Solar/Wind Helper
0.381
237034AC2-136 C
Solar/Wind Helper
0.194
23777801MSM_W1-116
Solar/Wind Helper
0.098
237025AB1-124 C
Solar/Wind Helper
0.142
237006AB1-125 GEN
Solar/Wind Helper
0.106
962691AG1-118 GEN
Solar/Wind Harmer
7.548
944201AF1-088_MTX
Adder
106.522
957141AF2-008_MTX
Adder
53.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.393
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.84
MECLTFEXP_MEC->PJM
CLTF
14.465
SIGELTFEXP_SIGE->PJM
CLTF
0.467
CPLELTFEXP_CPLE->PJM
CLTF
1.288
CBM West 2LTFEXP_CBM-W2->PJM
CBM
105.476
LAGNLTFEXP_LAGN->PJM
CLTF
14.169
CBM South 2LTFEXP_CBM-S2->PJM
CBM
9.052
TVALTFEXP_TVA->PJM
CLTF
7.036
NYPJM->LTFIMP_NY
CLTF
4.491
LGEELTFEXP_LGEE->PJM
CLTF
6.272
WECLTFEXP_WEC->PJM
CLTF
3.434
AG2-052LTFEXP_AG2-052->PJM
LTF
0.214
AH1-155LTFEXP_AH1-155->PJM
LTF
0.321

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AEP_P4_#8975_05KAMMER 765_MM2_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#8975_05KAMMER 765_MM2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.97 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.79
MW Contribution:9.21
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT7A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT7A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.96 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5307.1
MW Contribution:9.21
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
15.25
270512AE1-227 GEN2
Solar/Wind Harmer
2.245
971191AH1-055 GEN
Solar/Wind Harmer
22.406
957541AF2-048 GEN
Solar/Wind Harmer
1.601
270291AC1-194 GEN
Solar/Wind Harmer
10.629
961921AG1-034 GEN
Solar/Wind Harmer
12.731
960801AF2-371 GEN
Solar/Wind Harmer
2.533
964871AG1-351 GEN
Solar/Wind Harmer
1.749
270273AD2-016 GEN
Solar/Wind Harmer
2.659
972173AH1-669 GEN
Solar/Wind Harmer
4.984
241955AC1-078 GEN
Solar/Wind Harmer
7.382
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
17.654
253338AC1-165 GEN
Solar/Wind Harmer
1.064
253333AC1-068 GEN
Solar/Wind Harmer
1.027
241974AD2-163_GEN2
Solar/Wind Harmer
1.944
253415AE1-040 GEN
Solar/Wind Harmer
1.1
970605AG2-385 GEN
Solar/Wind Harmer
5.262
253406AD2-031_GEN
Solar/Wind Harmer
1.228
253316AC1-085 GEN3
Solar/Wind Harmer
7.992
253433AC1-085 GEN1
Solar/Wind Harmer
5.073
946181AF1-283 GEN
Solar/Wind Harmer
12.404
253303V4-073 C
Solar/Wind Harmer
0.11
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
942871AE2-306 GEN
Solar/Wind Harmer
0.858
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
34.974
970149AG2-104 GEN
Solar/Wind Harmer
43.193
970155AG2-107 GEN
Solar/Wind Harmer
15.25
270510AE1-227 GEN1
Solar/Wind Harmer
2.645
960001AF2-291 GEN
Solar/Wind Harmer
3.152
970947AG2-589 GEN
Solar/Wind Harmer
2.059
270331AC1-082 GEN3
Solar/Wind Harmer
0.466
927014AC1-188 GEN
Solar/Wind Harmer
1.606
270349AD2-093_GEN
Solar/Wind Harmer
3.665
270263AC1-001 GEN
Solar/Wind Harmer
1.044
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
1.064
253325AC1-069 GEN
Solar/Wind Harmer
1.027
970593AG2-378 GEN
Solar/Wind Harmer
1.949
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.541
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
4.732
252507AC2-088 GEN
Solar/Wind Harmer
1.7
270223U2-072_GEN1
Solar/Wind Harmer
1.871
270578AF1-285 GEN2
Solar/Wind Harmer
1.144
270391AF1-285 GEN3
Solar/Wind Harmer
1.144
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
6.509
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
29.222
945681AF1-233 GEN
Solar/Wind Harmer
17.467
942081AE2-220 GEN
Solar/Wind Harmer
5.883
270239V3-007_GEN1
Solar/Wind Harmer
1.584
247536S-71 GEN
Solar/Wind Harmer
3.724
965651AG1-433 GEN
Solar/Wind Harmer
5.019
958861AF2-177 GEN
Solar/Wind Harmer
10.036
945371AF1-202 GEN
Solar/Wind Harmer
6.405
971995AH1-542 GEN
Solar/Wind Harmer
10.093
270005AE1-210 C O1
Solar/Wind Harmer
5.013
965031AG1-367 GEN
Solar/Wind Harmer
9.173
970825AG2-519 GEN
Solar/Wind Harmer
2.158
970091AG2-072 GEN
Adder
70.193
24728605AND G2
Adder
3.466
24639705ELKHART HY
Adder
0.137
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
274812UNIV PK N;8U
Adder
4.45
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
962771AG1-126 GEN
Solar/Wind Harmer
34.974
270330AC1-082 GEN2
Solar/Wind Harmer
0.789
270329AC1-082 GEN1
Solar/Wind Harmer
0.465
270054AF2-122 C O1
Solar/Wind Harmer
3.29
970879AG2-548 GEN
Solar/Wind Harmer
4.317
940611AE2-048 GEN
Solar/Wind Harmer
22.053
941391AE2-136 GEN
Solar/Wind Harmer
11.427
270520AE2-214 GEN
Solar/Wind Harmer
6.059
270459AD2-067 GEN
Solar/Wind Harmer
8.36
961821AG1-024 GEN
Solar/Wind Harmer
8.487
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
6.982
970689AG2-444 GEN
Solar/Wind Harmer
16.256
270269AC2-059
Solar/Wind Harmer
9.3
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
4.621
270284AF1-227 GEN1
Solar/Wind Harmer
5.57
270286AF1-227 GEN2
Solar/Wind Harmer
2.061
270287AF1-227 GEN3
Solar/Wind Harmer
2.061
971985AH1-537 GEN
Solar/Wind Harmer
17.522
253383AE2-342_GEN
Solar/Wind Harmer
0.869
241973AD2-163_GEN1
Solar/Wind Harmer
1.944
943861AF1-054 GEN
Solar/Wind Harmer
3.765
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
2.96
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
4.309
270367AC2-061_GEN
Solar/Wind Harmer
3.048
253372AE2-315 SEC3
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
252510AF1-249 C
Solar/Wind Harmer
0.395
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.566
270222AC2-111 GEN
Solar/Wind Harmer
7.593
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
23.909
970519AG2-331 GEN
Solar/Wind Harmer
16.063
970699AG2-449 GEN
Solar/Wind Harmer
10.626
972167AH1-666 GEN
Solar/Wind Harmer
7.416
958171AF2-111 GEN
Solar/Wind Harmer
23.159
270437AC2-090 C
Solar/Wind Harmer
5.138
944531AF1-118 GEN
Solar/Wind Harmer
32.165
962031AG1-047 GEN
Solar/Wind Harmer
2.774
957741AF2-068 GEN
Solar/Wind Harmer
13.765
270356AE2-297 GEN
Solar/Wind Harmer
4.184
946031AF1-268 GEN
Solar/Wind Harmer
7.613
958821AF2-173 GEN
Solar/Wind Harmer
12.842
270004AE1-209 GEN
Solar/Wind Harmer
5.013
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
24642205MAYFLWER
Adder
0.568
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
4.712
253400AC2-068 GEN
Solar/Wind Harmer
1.895
252524AE2-267 GEN
Solar/Wind Harmer
1.487
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
7.824
270317AD1-130_GEN
Solar/Wind Harmer
3
944031AF1-071 GEN
Solar/Wind Harmer
0.936
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
9.252
972165AH1-665 GEN
Solar/Wind Harmer
7.402
971673AH1-337 GEN
Solar/Wind Harmer
4.251
971029AG2-637 GEN
Solar/Wind Harmer
13.852
270543AE2-219 C
Solar/Wind Harmer
4.719
270240V3-007_GEN2
Solar/Wind Harmer
5.693
24729505KEY G4
Adder
5.961
958711AF2-162 GEN
Solar/Wind Harmer
0.929
965101AG1-375 GEN
Solar/Wind Harmer
9.182
945581AF1-223 GEN
Solar/Wind Harmer
4.163
961761AG1-017 GEN
Solar/Wind Harmer
0.393
970115AG2-085 GEN
Solar/Wind Harmer
3.664
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
3.665
970879AG2-548 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
6.188
971073AG2-665 GEN
Solar/Wind Harmer
4.317
946101AF1-275 GEN
Solar/Wind Harmer
1.512
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
7.629
270518AE2-148 GEN
Solar/Wind Harmer
11.837
970077AG2-063 GEN
Solar/Wind Harmer
5.262
962581AG1-107 GEN
Solar/Wind Harmer
4.827
961491AF2-440 GEN
Solar/Wind Harmer
2.006
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
4.338
253398AE2-221_GEN2
Solar/Wind Harmer
4.338
253317AC1-085 GEN4
Solar/Wind Harmer
7.992
270186AC1-089 GEN
Solar/Wind Harmer
5.819
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
5.751
964601AG1-323 GEN
Solar/Wind Harmer
3.011
964601AG1-323 GEN
Solar/Wind Harmer
1.401
252509AD1-136 GEN
Solar/Wind Harmer
0.243
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
4.385
270224U2-072_GEN2
Solar/Wind Harmer
1.871
270227U2-072_GEN3
Solar/Wind Harmer
1.871
270228U2-072_GEN4
Solar/Wind Harmer
1.871
270231U2-072_GEN5
Solar/Wind Harmer
1.871
938701AE1-092 GEN
Solar/Wind Harmer
19.52
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
3.382
276820AF1-078_GEN
Solar/Wind Harmer
1.502
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
10.183
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
9.215
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
5.623
24379505HDWTR1G C
Solar/Wind Harmer
7.277
270209AC1-174_GEN
Solar/Wind Harmer
5.136
926881AC1-175 GEN
Solar/Wind Harmer
5.136
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
3.847
960971AF2-388 GEN
Solar/Wind Harmer
10.038
270201AC2-176 GEN
Solar/Wind Harmer
4.717
964611AG1-324 GEN
Solar/Wind Harmer
1.082
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
9.671
960441AF2-335 GEN
Solar/Wind Harmer
9.16
247620Y3-023
Adder
0.412
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
270599AE1-208 GEN
Solar/Wind Harmer
0.76
270031AE2-169
Solar/Wind Harmer
0.76
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P2-3_WP-500-DRT10A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_WP-500-DRT10A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:139.86 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5303.43
MW Contribution:9.29
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
35.245
270330AC1-082 GEN2
Solar/Wind Harmer
0.795
270329AC1-082 GEN1
Solar/Wind Harmer
0.468
270054AF2-122 C O1
Solar/Wind Harmer
3.32
940611AE2-048 GEN
Solar/Wind Harmer
22.287
941391AE2-136 GEN
Solar/Wind Harmer
11.549
970879AG2-548 GEN
Solar/Wind Harmer
4.353
270520AE2-214 GEN
Solar/Wind Harmer
6.113
270459AD2-067 GEN
Solar/Wind Harmer
8.438
961821AG1-024 GEN
Solar/Wind Harmer
8.566
270432AC2-029 GEN
Solar/Wind Harmer
7.042
970689AG2-444 GEN
Solar/Wind Harmer
16.397
270269AC2-059
Solar/Wind Harmer
9.378
972203AH1-686 GEN
Adder
2.313
270156DARBY CT1
Adder
8.909
270157DARBY CT2
Adder
8.887
270158DARBY CT3
Adder
8.745
945631AF1-228 GEN
Solar/Wind Harmer
4.662
270284AF1-227 GEN1
Solar/Wind Harmer
5.621
270286AF1-227 GEN2
Solar/Wind Harmer
2.079
270287AF1-227 GEN3
Solar/Wind Harmer
2.079
253383AE2-342_GEN
Solar/Wind Harmer
0.877
971985AH1-537 GEN
Solar/Wind Harmer
17.658
241973AD2-163_GEN1
Solar/Wind Harmer
1.962
943861AF1-054 GEN
Solar/Wind Harmer
3.799
943851AF1-053 GEN
Solar/Wind Harmer
1.836
270340AC2-060 GEN
Solar/Wind Harmer
2.985
24477305BRIDGE
Adder
0.341
241972AD1-140 GEN
Solar/Wind Harmer
4.346
270367AC2-061_GEN
Solar/Wind Harmer
3.072
253372AE2-315 SEC3
Adder
1.818
253372AE2-315 SEC3
Adder
1.818
25306009OHH W.
Adder
2.758
270578AF1-285 GEN2
Solar/Wind Harmer
0.444
253349AC2-067 GEN
Solar/Wind Harmer
4.752
253400AC2-068 GEN
Solar/Wind Harmer
1.911
252524AE2-267 GEN
Solar/Wind Harmer
1.499
970935AG2-582 GEN
50/50
1215.723
24318905MLG2
50/50
4.724
270471AD2-092_GEN
Solar/Wind Harmer
3.698
970879AG2-548 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
6.239
971073AG2-665 GEN
Solar/Wind Harmer
4.353
946101AF1-275 GEN
Solar/Wind Harmer
1.525
972269AH1-719 GEN
Adder
2.293
24685805CER G1
Adder
8.254
24685905CER G2
Adder
8.254
24723005RIVRG1
Adder
18.592
24723105RIVRG2
Adder
18.592
942861AE2-305 GEN
Solar/Wind Harmer
7.696
270518AE2-148 GEN
Solar/Wind Harmer
11.94
970077AG2-063 GEN
Solar/Wind Harmer
5.308
962581AG1-107 GEN
Solar/Wind Harmer
4.865
961491AF2-440 GEN
Solar/Wind Harmer
2.022
972159AH1-661 GEN
Adder
0.962
253394AE2-221_GEN
Solar/Wind Harmer
4.373
253398AE2-221_GEN2
Solar/Wind Harmer
4.373
253317AC1-085 GEN4
Solar/Wind Harmer
8.057
25326109MON D
Adder
1.263
270186AC1-089 GEN
Solar/Wind Harmer
5.865
253370AE2-315 SEC1
Adder
1.922
25322209TAIT E
Adder
9.347
25322209TAIT E
Adder
9.137
964601AG1-323 GEN
Solar/Wind Harmer
3.04
964601AG1-323 GEN
Solar/Wind Harmer
1.414
25183208HLCRTG
Solar/Wind Harmer
5.797
270224U2-072_GEN2
Solar/Wind Harmer
1.889
270227U2-072_GEN3
Solar/Wind Harmer
1.889
270228U2-072_GEN4
Solar/Wind Harmer
1.889
270231U2-072_GEN5
Solar/Wind Harmer
1.889
252509AD1-136 GEN
Solar/Wind Harmer
0.245
252519AF1-045_GEN
Solar/Wind Harmer
5.794
252516AE2-318_GEN
Solar/Wind Harmer
4.42
938701AE1-092 GEN
Solar/Wind Harmer
19.71
25194408D.CRK1
Adder
7.189
25194508D.CRK3
Adder
1.344
253378AE2-206_GEN
Solar/Wind Harmer
3.413
276820AF1-078_GEN
Solar/Wind Harmer
1.516
25326509SID D
Adder
1.242
970239AG2-162 GEN
Solar/Wind Harmer
10.263
24728805RICHG1
Adder
3.517
24728905RICHG2
Adder
3.517
970883AG2-550 GEN
Solar/Wind Harmer
9.293
970885AG2-551 GEN
Solar/Wind Harmer
2.161
270383AD1-128 GEN
Solar/Wind Harmer
5.669
23559101PLEAS2
50/50
11.24
23684101S70BUS1
50/50
0.316
23562301OGROV1
50/50
2.447
24721705FLATG2
Adder
23.592
962761AG1-125 GEN
Solar/Wind Harmer
35.245
970149AG2-104 GEN
Solar/Wind Harmer
43.528
970155AG2-107 GEN
Solar/Wind Harmer
15.368
270510AE1-227 GEN1
Solar/Wind Harmer
2.678
960001AF2-291 GEN
Solar/Wind Harmer
3.176
970947AG2-589 GEN
Solar/Wind Harmer
2.074
23559001PLEAS1
50/50
11.24
23684201S70BUS2
50/50
0.322
23562401OGROV2
50/50
2.431
24318805MLG1
50/50
6.369
23534401HANNIB
50/50
0.15
24721905FLATG4
Adder
23.592
970153AG2-106 GEN
Solar/Wind Harmer
15.368
270512AE1-227 GEN2
Solar/Wind Harmer
2.273
971191AH1-055 GEN
Solar/Wind Harmer
22.576
957541AF2-048 GEN
Solar/Wind Harmer
1.614
270291AC1-194 GEN
Solar/Wind Harmer
10.719
961921AG1-034 GEN
Solar/Wind Harmer
12.85
960801AF2-371 GEN
Solar/Wind Harmer
2.556
964871AG1-351 GEN
Solar/Wind Harmer
1.765
270273AD2-016 GEN
Solar/Wind Harmer
2.682
972173AH1-669 GEN
Solar/Wind Harmer
5.026
241955AC1-078 GEN
Solar/Wind Harmer
7.448
24686205CER G4
Adder
8.265
24686405CER G5
Adder
8.232
942051AE2-217 GEN
Solar/Wind Harmer
17.81
253338AC1-165 GEN
Solar/Wind Harmer
1.074
253333AC1-068 GEN
Solar/Wind Harmer
1.035
241974AD2-163_GEN2
Solar/Wind Harmer
1.962
253415AE1-040 GEN
Solar/Wind Harmer
1.109
970605AG2-385 GEN
Solar/Wind Harmer
5.308
253406AD2-031_GEN
Solar/Wind Harmer
1.238
253316AC1-085 GEN3
Solar/Wind Harmer
8.057
253433AC1-085 GEN1
Solar/Wind Harmer
5.115
25196408WSDLE3
Adder
8.387
25196308WSDLE2
Adder
8.314
25196208WSDLE1
Adder
8.294
25196708WSDLE6
Adder
8.273
25196508WSDLE4
Adder
8.064
270302AB2-170 GEN
Solar/Wind Harmer
7.9
270317AD1-130_GEN
Solar/Wind Harmer
3.028
944031AF1-071 GEN
Solar/Wind Harmer
0.944
25196108MFTGT2
Adder
1.44
25196108MFTGT2
Adder
1.337
972163AH1-664 GEN
Solar/Wind Harmer
9.324
972165AH1-665 GEN
Solar/Wind Harmer
7.459
971673AH1-337 GEN
Solar/Wind Harmer
4.287
971029AG2-637 GEN
Solar/Wind Harmer
13.968
270543AE2-219 C
Solar/Wind Harmer
4.759
270240V3-007_GEN2
Solar/Wind Harmer
5.741
24729505KEY G4
Adder
6.012
958711AF2-162 GEN
Solar/Wind Harmer
0.937
965101AG1-375 GEN
Solar/Wind Harmer
9.26
945581AF1-223 GEN
Solar/Wind Harmer
4.198
961761AG1-017 GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
3.695
274775LINCOLN ;6U
Adder
7.577
274776LINCOLN ;7U
Adder
7.577
274777LINCOLN ;8U
Adder
7.577
274814UNIV PK N;0U
Adder
4.526
274807UNIV PK N;3U
Adder
4.517
274805UNIV PK N;1U
Adder
4.497
274811UNIV PK N;7U
Adder
0.593
238152AF2-075_GEN
Solar/Wind Helper
0.602
23546401DTGZ2-030
Solar/Wind Helper
0.076
238208AF1-136 C
Solar/Wind Helper
0.181
238109AE1-109 GEN2
Solar/Wind Helper
0.087
238110AE1-109 GEN3
Solar/Wind Helper
0.087
237085AD2-009_GEN
Solar/Wind Helper
1.378
3138216PACIFIC
Solar/Wind Helper
0.038
316411AF1-147_GEN1
Solar/Wind Helper
0.751
316415AF1-147_GEN2
Solar/Wind Helper
0.751
270331AC1-082 GEN3
Solar/Wind Harmer
0.469
927014AC1-188 GEN
Solar/Wind Harmer
1.618
270349AD2-093_GEN
Solar/Wind Harmer
3.698
270263AC1-001 GEN
Solar/Wind Harmer
1.052
270159DARBY CT4
Adder
8.767
24686105CER G3
Adder
8.308
24686505CER G6
Adder
8.298
24723205RIVRG3
Adder
18.592
253343AC1-166 GEN
Solar/Wind Harmer
1.074
253325AC1-069 GEN
Solar/Wind Harmer
1.035
970593AG2-378 GEN
Solar/Wind Harmer
1.966
253432AC1-085 GEN2
Solar/Wind Harmer
0.257
946171AF1-282 GEN
Solar/Wind Harmer
9.619
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
25326309TAIT D
Adder
1.05
960071AF2-298 GEN
Solar/Wind Harmer
4.772
270223U2-072_GEN1
Solar/Wind Harmer
1.889
252507AC2-088 GEN
Solar/Wind Harmer
1.713
270578AF1-285 GEN2
Solar/Wind Harmer
1.155
270391AF1-285 GEN3
Solar/Wind Harmer
1.155
25194608D.CRK4
Adder
1.563
25196808ZIMRHP
Adder
71.915
270462AD2-086
Solar/Wind Harmer
6.572
25196008MFTGT1
Adder
1.306
970333AG2-219 GEN
Solar/Wind Harmer
29.451
945681AF1-233 GEN
Solar/Wind Harmer
17.602
247536S-71 GEN
Solar/Wind Harmer
3.755
942081AE2-220 GEN
Solar/Wind Harmer
5.932
270239V3-007_GEN1
Solar/Wind Harmer
1.597
971995AH1-542 GEN
Solar/Wind Harmer
10.198
965651AG1-433 GEN
Solar/Wind Harmer
5.062
958861AF2-177 GEN
Solar/Wind Harmer
10.121
945371AF1-202 GEN
Solar/Wind Harmer
6.459
270005AE1-210 C O1
Solar/Wind Harmer
5.055
965031AG1-367 GEN
Solar/Wind Harmer
9.249
970825AG2-519 GEN
Solar/Wind Harmer
2.176
970091AG2-072 GEN
Adder
70.733
24728605AND G2
Adder
3.494
24639705ELKHART HY
Adder
0.139
274773LINCOLN ;4U
Adder
7.577
274774LINCOLN ;5U
Adder
7.577
274751CRETE EC ;1U
Adder
7.394
274754CRETE EC ;4U
Adder
7.394
274723RIVER EC ;12
Adder
16.072
274812UNIV PK N;8U
Adder
4.487
23583801GRNGAP
Solar/Wind Helper
4.952
316095T157 G97
Solar/Wind Helper
1.324
238147AE2-230_GEN1
Solar/Wind Helper
0.422
238149AF1-291A_GEN
Solar/Wind Helper
0.12
237061AD1-155 GEN
Solar/Wind Helper
0.045
238221AF1-254 C O1
Solar/Wind Helper
0.23
238108AE1-109 GEN1
Solar/Wind Helper
0.087
235067AD1-061 GEN
Solar/Wind Helper
0.416
946181AF1-283 GEN
Solar/Wind Harmer
12.504
253303V4-073 C
Solar/Wind Harmer
0.111
253370AE2-315 SEC1
Adder
1.922
253371AE2-315 SEC2
Adder
1.818
942871AE2-306 GEN
Solar/Wind Harmer
0.866
270391AF1-285 GEN3
Solar/Wind Harmer
0.444
252510AF1-249 C
Solar/Wind Harmer
0.398
25194608D.CRK4
Adder
1.563
25196608WSDLE5
Adder
8.148
270485AE1-090_GEN
Solar/Wind Harmer
0.571
270222AC2-111 GEN
Solar/Wind Harmer
7.655
25196008MFTGT1
Adder
1.265
970243AG2-164 GEN
Solar/Wind Harmer
24.096
970519AG2-331 GEN
Solar/Wind Harmer
16.189
970699AG2-449 GEN
Solar/Wind Harmer
10.709
972167AH1-666 GEN
Solar/Wind Harmer
7.473
958171AF2-111 GEN
Solar/Wind Harmer
23.339
270437AC2-090 C
Solar/Wind Harmer
5.18
944531AF1-118 GEN
Solar/Wind Harmer
32.44
962031AG1-047 GEN
Solar/Wind Harmer
2.797
957741AF2-068 GEN
Solar/Wind Harmer
13.882
946031AF1-268 GEN
Solar/Wind Harmer
7.677
958821AF2-173 GEN
Solar/Wind Harmer
12.949
270004AE1-209 GEN
Solar/Wind Harmer
5.055
270356AE2-297 GEN
Solar/Wind Harmer
4.219
24728705AND G3
Adder
7.308
24728505AND G1
Adder
3.494
24642205MAYFLWER
Adder
0.573
274772LINCOLN ;3U
Adder
7.577
274752CRETE EC ;2U
Adder
7.394
274753CRETE EC ;3U
Adder
7.394
274724RIVER EC ;11
Adder
15.884
316097T157 G90
Solar/Wind Helper
1.324
964991AG1-363 GEN
Solar/Wind Helper
4.195
238148AE2-230_GEN2
Solar/Wind Helper
0.423
237080AD1-060 GEN
Solar/Wind Helper
0.287
23750701CROSSCHOOL
Solar/Wind Helper
1.116
237038AE2-054 C
Solar/Wind Helper
0.228
235062AE1-101 C1
Solar/Wind Helper
1.393
23779801AA1-109
Solar/Wind Helper
0.164
24379505HDWTR1G C
Solar/Wind Harmer
7.337
270209AC1-174_GEN
Solar/Wind Harmer
5.178
926881AC1-175 GEN
Solar/Wind Harmer
5.178
247621Y3-024
Adder
0.223
944541AF1-119 GEN
Solar/Wind Harmer
3.879
960971AF2-388 GEN
Solar/Wind Harmer
10.123
270201AC2-176 GEN
Solar/Wind Harmer
4.758
964611AG1-324 GEN
Solar/Wind Harmer
1.091
964611AG1-324 GEN
Solar/Wind Harmer
0.484
970825AG2-519 GEN
Solar/Wind Harmer
9.752
960441AF2-335 GEN
Solar/Wind Harmer
9.237
247620Y3-023
Adder
0.416
274770LINCOLN ;1U
Adder
7.577
274771LINCOLN ;2U
Adder
7.577
238175AF1-290_GEN
Solar/Wind Helper
0.128
238169AE2-226 GEN1
Solar/Wind Helper
0.591
238170AE2-226 GEN2
Solar/Wind Helper
0.591
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.148
237034AC2-136 C
Solar/Wind Helper
0.192
237002AB1-128_GEN
Solar/Wind Helper
0.372
237001AB1-127_GEN
Solar/Wind Helper
0.372
235063AE1-101 C2
Solar/Wind Helper
1.393
23777801MSM_W1-116
Solar/Wind Helper
0.097
237025AB1-124 C
Solar/Wind Helper
0.14
237006AB1-125 GEN
Solar/Wind Helper
0.105
270599AE1-208 GEN
Solar/Wind Harmer
0.766
270031AE2-169
Solar/Wind Harmer
0.766
237030AB1-096 C
Solar/Wind Helper
0.06
944201AF1-088_MTX
Adder
104.45
957141AF2-008_MTX
Adder
52.225
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.724
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.351
MECLTFEXP_MEC->PJM
CLTF
14.175
SIGELTFEXP_SIGE->PJM
CLTF
0.458
CPLELTFEXP_CPLE->PJM
CLTF
1.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
103.491
LAGNLTFEXP_LAGN->PJM
CLTF
13.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.88
TVALTFEXP_TVA->PJM
CLTF
6.914
NYPJM->LTFIMP_NY
CLTF
4.434
LGEELTFEXP_LGEE->PJM
CLTF
6.157
WECLTFEXP_WEC->PJM
CLTF
3.363
AG2-052LTFEXP_AG2-052->PJM
LTF
0.21
AH1-155LTFEXP_AH1-155->PJM
LTF
0.314

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-3_MP-765-502T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-3_MP-765-502T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.36 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5284.61
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-028_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01FLINTRUN-01HARRSN 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-028_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:139.32 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5282.91
MW Contribution:6.43
Bus #Bus NameTypeMW Contribution
970935AG2-582 GEN
50/50
1217.062
24318905MLG2
50/50
4.656
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971073AG2-665 GEN
Solar/Wind Harmer
6.304
24685805CER G1
Adder
8.199
24685905CER G2
Adder
8.199
972269AH1-719 GEN
Adder
2.268
24723005RIVRG1
Adder
18.473
24723105RIVRG2
Adder
18.473
942861AE2-305 GEN
Solar/Wind Harmer
5.322
270518AE2-148 GEN
Solar/Wind Harmer
0.589
970077AG2-063 GEN
Solar/Wind Harmer
3.909
962581AG1-107 GEN
Solar/Wind Harmer
0.001
972159AH1-661 GEN
Adder
0.952
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
25326109MON D
Adder
1.252
253370AE2-315 SEC1
Adder
1.906
25322209TAIT E
Adder
9.269
25322209TAIT E
Adder
9.061
25183208HLCRTG
Solar/Wind Harmer
0.01
964601AG1-323 GEN
Solar/Wind Harmer
2.647
964601AG1-323 GEN
Solar/Wind Harmer
1.765
252509AD1-136 GEN
Solar/Wind Harmer
0.033
252519AF1-045_GEN
Solar/Wind Harmer
5.748
252516AE2-318_GEN
Solar/Wind Harmer
5.098
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
10.591
971655AH1-328 GEN
Solar/Wind Harmer
2.34
25194408D.CRK1
Adder
7.132
25194508D.CRK3
Adder
1.333
253378AE2-206_GEN
Solar/Wind Harmer
0.003
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
2.833
25326509SID D
Adder
1.231
970239AG2-162 GEN
Solar/Wind Harmer
1.617
24728805RICHG1
Adder
3.489
24728905RICHG2
Adder
3.489
970883AG2-550 GEN
Solar/Wind Harmer
6.429
970885AG2-551 GEN
Solar/Wind Harmer
2.143
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
962771AG1-126 GEN
Solar/Wind Harmer
29.494
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270054AF2-122 C O1
Solar/Wind Harmer
0.006
970879AG2-548 GEN
Solar/Wind Harmer
6.304
940611AE2-048 GEN
Solar/Wind Harmer
17.215
941391AE2-136 GEN
Solar/Wind Harmer
9.698
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
4.145
972203AH1-686 GEN
Adder
2.298
270432AC2-029 GEN
Solar/Wind Harmer
3.085
970689AG2-444 GEN
Solar/Wind Harmer
14.206
270269AC2-059
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
8.832
270157DARBY CT2
Adder
8.81
270158DARBY CT3
Adder
8.67
945631AF1-228 GEN
Solar/Wind Harmer
0
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
971985AH1-537 GEN
Solar/Wind Harmer
2.037
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.627
943851AF1-053 GEN
Solar/Wind Harmer
1.82
270340AC2-060 GEN
Solar/Wind Harmer
0.008
24477305BRIDGE
Adder
0.338
241972AD1-140 GEN
Solar/Wind Harmer
0.734
270367AC2-061_GEN
Solar/Wind Harmer
0.005
253372AE2-315 SEC3
Adder
1.803
253372AE2-315 SEC3
Adder
1.803
25306009OHH W.
Adder
2.735
270578AF1-285 GEN2
Solar/Wind Harmer
0.44
253349AC2-067 GEN
Solar/Wind Harmer
2.077
253400AC2-068 GEN
Solar/Wind Harmer
0.835
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
8.32
25196308WSDLE2
Adder
8.248
25196208WSDLE1
Adder
8.227
25196708WSDLE6
Adder
8.207
25196508WSDLE4
Adder
8
270302AB2-170 GEN
Solar/Wind Harmer
0.004
270317AD1-130_GEN
Solar/Wind Harmer
0.009
23559001PLEAS1
50/50
11.213
23684201S70BUS2
50/50
0.319
23562401OGROV2
50/50
2.411
24318805MLG1
50/50
6.319
24721905FLATG4
Adder
23.442
970153AG2-106 GEN
Solar/Wind Harmer
18.834
270512AE1-227 GEN2
Solar/Wind Harmer
1.907
971191AH1-055 GEN
Solar/Wind Harmer
18.237
270291AC1-194 GEN
Solar/Wind Harmer
5.533
961921AG1-034 GEN
Solar/Wind Harmer
6.218
270273AD2-016 GEN
Solar/Wind Harmer
0.721
972173AH1-669 GEN
Solar/Wind Harmer
3.478
241955AC1-078 GEN
Solar/Wind Harmer
0.006
24686205CER G4
Adder
8.21
24686405CER G5
Adder
8.177
942051AE2-217 GEN
Solar/Wind Harmer
12.316
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.011
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970605AG2-385 GEN
Solar/Wind Harmer
4.136
253406AD2-031_GEN
Solar/Wind Harmer
0.499
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.654
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
270391AF1-285 GEN3
Solar/Wind Harmer
0.44
970191AG2-125 GEN
Solar/Wind Harmer
1.697
252510AF1-249 C
Solar/Wind Harmer
0.051
25196608WSDLE5
Adder
8.083
25194608D.CRK4
Adder
1.55
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270222AC2-111 GEN
Solar/Wind Harmer
3.293
25196008MFTGT1
Adder
1.255
970243AG2-164 GEN
Solar/Wind Harmer
3.783
970519AG2-331 GEN
Solar/Wind Harmer
16.815
970699AG2-449 GEN
Solar/Wind Harmer
1.617
972167AH1-666 GEN
Solar/Wind Harmer
5.174
958171AF2-111 GEN
Solar/Wind Harmer
16.157
270437AC2-090 C
Solar/Wind Harmer
0.003
944531AF1-118 GEN
Solar/Wind Harmer
28.735
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.603
270356AE2-297 GEN
Solar/Wind Harmer
0.009
946031AF1-268 GEN
Solar/Wind Harmer
6.09
958821AF2-173 GEN
Solar/Wind Harmer
8.959
270004AE1-209 GEN
Solar/Wind Harmer
1.387
971617AH1-308 GEN
Solar/Wind Harmer
5.319
970289AG2-191 GEN
Solar/Wind Harmer
0.701
970291AG2-192 GEN
Solar/Wind Harmer
0.638
970513AG2-328 GEN
Solar/Wind Harmer
2.761
970517AG2-330 GEN
Solar/Wind Harmer
16.566
247642Z2-115 C
Solar/Wind Harmer
0.003
270043AE2-236 GEN
Solar/Wind Harmer
4.072
959331AF2-224 GEN
Solar/Wind Harmer
4.433
965021AG1-366 GEN
Solar/Wind Harmer
2.111
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
24728705AND G3
Adder
7.25
24728505AND G1
Adder
3.466
970349AG2-230 GEN
Solar/Wind Harmer
9.454
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.281
270491AE1-102 GEN2
Solar/Wind Harmer
0.817
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970031AG2-029 GEN
Solar/Wind Harmer
4.079
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
270053AF1-130 C
Solar/Wind Harmer
1.414
247643Z2-116 C
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.568
945111AF1-176 GEN
Solar/Wind Harmer
5.045
274772LINCOLN ;3U
Adder
7.514
274752CRETE EC ;2U
Adder
7.332
274753CRETE EC ;3U
Adder
7.332
274724RIVER EC ;11
Adder
15.751
970193AG2-126 GEN
Solar/Wind Harmer
9.3
276806AD2-047 C O1
Solar/Wind Harmer
3.508
970941AG2-585 GEN
Solar/Wind Harmer
7.739
276897AD1-100 C
Solar/Wind Harmer
0.008
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
20.212
270258AD1-119 GEN
Solar/Wind Harmer
0.002
276893AG1-478 C
Solar/Wind Harmer
0.245
24441205WTRV SLR C
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
10.327
943591AF1-030 GEN
Solar/Wind Harmer
6.867
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270404AC1-167 GEN
Solar/Wind Harmer
0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.002
316097T157 G90
Solar/Wind Helper
1.299
964991AG1-363 GEN
Solar/Wind Helper
4.135
238148AE2-230_GEN2
Solar/Wind Helper
0.417
23750701CROSSCHOOL
Solar/Wind Helper
1.155
237080AD1-060 GEN
Solar/Wind Helper
0.284
237038AE2-054 C
Solar/Wind Helper
0.226
235062AE1-101 C1
Solar/Wind Helper
1.38
238127S14_GEN_2
Solar/Wind Helper
0.641
23779801AA1-109
Solar/Wind Helper
0.162
238118U2-030_1
Solar/Wind Helper
0.26
971653AH1-327 GEN
Solar/Wind Harmer
0.917
25196108MFTGT2
Adder
1.429
25196108MFTGT2
Adder
1.327
972163AH1-664 GEN
Solar/Wind Harmer
7.187
972165AH1-665 GEN
Solar/Wind Harmer
5.756
971673AH1-337 GEN
Solar/Wind Harmer
4.191
971029AG2-637 GEN
Solar/Wind Harmer
9.664
270543AE2-219 C
Solar/Wind Harmer
0.004
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
5.961
965101AG1-375 GEN
Solar/Wind Harmer
6.406
945581AF1-223 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
2.556
971609AH1-304 GEN
Solar/Wind Harmer
1.043
270024AE2-089 GEN
Solar/Wind Harmer
0.007
270594AE1-207 GEN
Solar/Wind Harmer
7.147
270071AF1-092 GEN
Solar/Wind Harmer
12.224
970289AG2-191 GEN
Solar/Wind Harmer
1.211
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
8.573
965051AG1-369 GEN
Solar/Wind Harmer
3.147
971347AH1-153 GEN
Solar/Wind Harmer
9.454
965041AG1-368 GEN
Solar/Wind Harmer
6.297
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.74
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270435AC2-044 GEN
Solar/Wind Harmer
0.796
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
963841AG1-237 GEN
Solar/Wind Harmer
2.71
971771AH1-392 GEN
Solar/Wind Harmer
6.248
971769AH1-391 GEN
Solar/Wind Harmer
6.974
247607V1-011 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
2.801
274775LINCOLN ;6U
Adder
7.514
274776LINCOLN ;7U
Adder
7.514
274777LINCOLN ;8U
Adder
7.514
274814UNIV PK N;0U
Adder
4.489
274807UNIV PK N;3U
Adder
4.479
274805UNIV PK N;1U
Adder
4.459
274811UNIV PK N;7U
Adder
0.697
960591AF2-350 GEN
Solar/Wind Harmer
6.191
270399AC1-101 GEN
Solar/Wind Harmer
1.957
270400AC1-102 GEN
Solar/Wind Harmer
1.957
970833AG2-524 GEN
Solar/Wind Harmer
6.792
970833AG2-524 GEN
Solar/Wind Harmer
4.528
970179AG2-119 GEN
Solar/Wind Harmer
5.506
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
970169AG2-114 GEN
Solar/Wind Harmer
6.145
276868AE1-113 GEN
Solar/Wind Harmer
1.231
276882AE2-255 GEN
Solar/Wind Harmer
0.717
238152AF2-075_GEN
Solar/Wind Helper
0.593
23546401DTGZ2-030
Solar/Wind Helper
0.075
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
238208AF1-136 C
Solar/Wind Helper
0.18
237085AD2-009_GEN
Solar/Wind Helper
1.367
238126S14_GEN_1
Solar/Wind Helper
0.641
23559101PLEAS2
50/50
11.213
23684101S70BUS1
50/50
0.313
23562301OGROV1
50/50
2.427
24721705FLATG2
Adder
23.442
962761AG1-125 GEN
Solar/Wind Harmer
29.494
970149AG2-104 GEN
Solar/Wind Harmer
31.855
970155AG2-107 GEN
Solar/Wind Harmer
18.834
270510AE1-227 GEN1
Solar/Wind Harmer
1.907
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.239
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
927014AC1-188 GEN
Solar/Wind Harmer
0.004
270349AD2-093_GEN
Solar/Wind Harmer
0.005
270263AC1-001 GEN
Solar/Wind Harmer
0.698
24686105CER G3
Adder
8.253
24686505CER G6
Adder
8.242
270159DARBY CT4
Adder
8.691
24723205RIVRG3
Adder
18.473
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.011
970593AG2-378 GEN
Solar/Wind Harmer
1.53
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.657
253370AE2-315 SEC1
Adder
1.906
253371AE2-315 SEC2
Adder
1.803
25326309TAIT D
Adder
1.041
960071AF2-298 GEN
Solar/Wind Harmer
3.297
252507AC2-088 GEN
Solar/Wind Harmer
0.3
270223U2-072_GEN1
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.55
25196808ZIMRHP
Adder
71.347
270462AD2-086
Solar/Wind Harmer
0.014
25196008MFTGT1
Adder
1.296
970333AG2-219 GEN
Solar/Wind Harmer
4.624
945681AF1-233 GEN
Solar/Wind Harmer
12.186
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.707
247536S-71 GEN
Solar/Wind Harmer
0.258
965651AG1-433 GEN
Solar/Wind Harmer
1.879
958861AF2-177 GEN
Solar/Wind Harmer
2.776
945371AF1-202 GEN
Solar/Wind Harmer
0.001
971995AH1-542 GEN
Solar/Wind Harmer
2.347
970773AG2-487 GEN
Solar/Wind Harmer
1.131
270005AE1-210 C O1
Solar/Wind Harmer
1.387
965031AG1-367 GEN
Solar/Wind Harmer
6.4
970825AG2-519 GEN
Solar/Wind Harmer
2.27
970091AG2-072 GEN
Adder
70.193
270032AE2-172
Solar/Wind Harmer
4.254
970291AG2-192 GEN
Solar/Wind Harmer
0.829
970245AG2-165 GEN
Solar/Wind Harmer
2.761
276903AD2-071 C
Solar/Wind Harmer
7.113
965011AG1-365 GEN
Solar/Wind Harmer
6.333
247521TR3_G114
Solar/Wind Harmer
0.23
270246TR4_N_V150
Solar/Wind Harmer
0.041
24728605AND G2
Adder
3.466
339216AC1-074 GEN
Solar/Wind Harmer
0.172
965421AG1-410 GEN
Solar/Wind Harmer
18.858
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.853
246936BC-WTG1
Solar/Wind Harmer
0.255
24791305MDL-5G
Solar/Wind Harmer
0.001
270489AE1-102 GEN1
Solar/Wind Harmer
0.817
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.162
24695305TIMB G C
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.005
970373AG2-245 GEN
Solar/Wind Harmer
13.169
270063AE2-323 C
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
24639705ELKHART HY
Adder
0.137
963741AG1-226 GEN
Solar/Wind Harmer
14.772
945111AF1-176 GEN
Solar/Wind Harmer
11.105
270505AE1-170 C O1
Solar/Wind Harmer
6.535
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
274773LINCOLN ;4U
Adder
7.514
274774LINCOLN ;5U
Adder
7.514
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.241
274751CRETE EC ;1U
Adder
7.332
274754CRETE EC ;4U
Adder
7.332
274723RIVER EC ;12
Adder
15.938
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.45
276776AD2-060 GEN
Solar/Wind Harmer
0.646
941551AE2-152 GEN
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
4.613
276691AA1-018 GEN1
Solar/Wind Harmer
0.745
276901AD2-066 C O1
Solar/Wind Harmer
0.006
944231AF1-091 GEN
Solar/Wind Harmer
1.635
971997AH1-543 GEN
Solar/Wind Harmer
3.22
23583801GRNGAP
Solar/Wind Helper
4.858
316095T157 G97
Solar/Wind Helper
1.299
238147AE2-230_GEN1
Solar/Wind Helper
0.415
238149AF1-291A_GEN
Solar/Wind Helper
0.119
238108AE1-109 GEN1
Solar/Wind Helper
0.088
237061AD1-155 GEN
Solar/Wind Helper
0.045
238185AF2-356 C
Solar/Wind Helper
1.996
238221AF1-254 C O1
Solar/Wind Helper
0.228
235067AD1-061 GEN
Solar/Wind Helper
0.412
235531U2-073 GEN
Solar/Wind Helper
2.523
238117U2-030
Solar/Wind Helper
0.26
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.222
944541AF1-119 GEN
Solar/Wind Harmer
0.429
960971AF2-388 GEN
Solar/Wind Harmer
3.759
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.48
970825AG2-519 GEN
Solar/Wind Harmer
7.086
960441AF2-335 GEN
Solar/Wind Harmer
6.391
270599AE1-208 GEN
Solar/Wind Harmer
5.854
270031AE2-169
Solar/Wind Harmer
3.512
971613AH1-306 GEN
Solar/Wind Harmer
3.063
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.761
970611AG2-400 GEN
Solar/Wind Harmer
6.333
970627AG2-408 GEN
Solar/Wind Harmer
1.9
970235AG2-159 GEN
Solar/Wind Harmer
3.847
970235AG2-159 GEN
Solar/Wind Harmer
2.207
339221AD2-048_GEN
Solar/Wind Harmer
0.004
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971199AH1-059 GEN
Solar/Wind Harmer
2.513
246938BC-WTG3
Solar/Wind Harmer
0.228
246937BC-WTG2
Solar/Wind Harmer
0.255
972043AH1-570 GEN
Solar/Wind Harmer
1.633
972045AH1-571 GEN
Solar/Wind Harmer
1.308
966841AG1-555 GEN
Solar/Wind Harmer
0.709
944971AF1-162 GEN
Solar/Wind Harmer
6.265
965681AG1-436 GEN
Solar/Wind Harmer
7.82
965791AG1-447 GEN
Solar/Wind Harmer
5.734
270216AD2-079_GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.412
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
270007AE1-245 C
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.641
957891AF2-083 GEN
Solar/Wind Harmer
0.001
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
4.56
961051AF2-396 GEN
Solar/Wind Harmer
12.428
961051AF2-396 GEN
Solar/Wind Harmer
8.285
274770LINCOLN ;1U
Adder
7.514
274771LINCOLN ;2U
Adder
7.514
971125AH1-004 GEN
Solar/Wind Harmer
2.483
970107AG2-081 GEN
Solar/Wind Harmer
1.862
960161AF2-307 GEN
Solar/Wind Harmer
4.096
945391AF1-204 GEN
Solar/Wind Harmer
6.587
274888KELLY CRK;1U
Solar/Wind Harmer
0.364
274887GEN-1.85
Solar/Wind Harmer
0.163
276843GEN-1.7
Solar/Wind Harmer
0.2
958011AF2-095 GEN
Solar/Wind Harmer
8.915
970623AG2-406 GEN
Solar/Wind Harmer
1.132
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
241960AC2-195 GEN
Solar/Wind Harmer
0.005
958481AF2-142 GEN
Solar/Wind Harmer
9.231
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.833
971573AH1-285 GEN
Solar/Wind Harmer
1.146
958491AF2-143 GEN
Solar/Wind Harmer
9.212
274879MINONK ;1U
Solar/Wind Harmer
0.259
238175AF1-290_GEN
Solar/Wind Helper
0.126
238169AE2-226 GEN1
Solar/Wind Helper
0.582
238170AE2-226 GEN2
Solar/Wind Helper
0.582
235020AA1-095 C
Solar/Wind Helper
0.044
23777901MDS_W4-102
Solar/Wind Helper
0.146
238120AE2-309 GEN
Solar/Wind Helper
0.406
237034AC2-136 C
Solar/Wind Helper
0.189
237002AB1-128_GEN
Solar/Wind Helper
0.369
235063AE1-101 C2
Solar/Wind Helper
1.38
237001AB1-127_GEN
Solar/Wind Helper
0.368
23777801MSM_W1-116
Solar/Wind Helper
0.096
962691AG1-118 GEN
Solar/Wind Harmer
3.447
944201AF1-088_MTX
Adder
103.64
957141AF2-008_MTX
Adder
51.82
CBM West 1LTFEXP_CBM-W1->PJM
CBM
122.614
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.188
MECLTFEXP_MEC->PJM
CLTF
14.066
SIGELTFEXP_SIGE->PJM
CLTF
0.455
CPLELTFEXP_CPLE->PJM
CLTF
1.286
CBM West 2LTFEXP_CBM-W2->PJM
CBM
102.798
LAGNLTFEXP_LAGN->PJM
CLTF
13.832
CBM South 2LTFEXP_CBM-S2->PJM
CBM
8.925
TVALTFEXP_TVA->PJM
CLTF
6.876
NYPJM->LTFIMP_NY
CLTF
4.417
LGEELTFEXP_LGEE->PJM
CLTF
6.111
WECLTFEXP_WEC->PJM
CLTF
3.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.208
AH1-155LTFEXP_AH1-155->PJM
LTF
0.312

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.75 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4950.27
MW Contribution:10.63
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.94 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4919.93
MW Contribution:10.61
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.63 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4908.47
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.62 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4870.98
MW Contribution:7.39
Bus #Bus NameTypeMW Contribution
962771AG1-126 GEN
Solar/Wind Harmer
34.524
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:130.23 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4856.26
MW Contribution:10.73
Bus #Bus NameTypeMW Contribution
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:124.1 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:4627.6
MW Contribution:7.12
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line l/o ATSI_P1-2_TE-345-601_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02LEMOYN-02DAV-BE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_TE-345-601_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.99 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2140.73
MW Contribution:3.35
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
50/50
1.747
241832AE2-181_GEN
Solar/Wind Harmer
0.004
958321AF2-126 GEN
Solar/Wind Harmer
1.413
23929302BS-PKR
Adder
1.959
270541AE2-072 C
Solar/Wind Harmer
0.01
270575GUS2 35KV
Solar/Wind Harmer
4.971
970217AG2-149 GEN
Solar/Wind Harmer
5.053
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
247604X1-042
Adder
0.302
270588AE1-091_GEN
Solar/Wind Harmer
3.901
24441205WTRV SLR C
Solar/Wind Harmer
0
270491AE1-102 GEN2
Solar/Wind Harmer
0.637
945111AF1-176 GEN
Solar/Wind Harmer
3.77
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.03
24642205MAYFLWER
Adder
0.413
970031AG2-029 GEN
Solar/Wind Harmer
2.93
247643Z2-116 C
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
3.103
965021AG1-366 GEN
Solar/Wind Harmer
1.478
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.692
970349AG2-230 GEN
Solar/Wind Harmer
6.22
270391AF1-285 GEN3
Solar/Wind Harmer
0.274
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
274752CRETE EC ;2U
Adder
4.596
274753CRETE EC ;3U
Adder
4.596
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274724RIVER EC ;11
Adder
9.806
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274802UNIV PARK;5U
Adder
3.182
274826FISK ;BP
Adder
5.966
274800UNIV PARK;3U
Adder
3.173
972038AH1-567 GEN2
Adder
0.199
276806AD2-047 C O1
Solar/Wind Harmer
2.148
970941AG2-585 GEN
Solar/Wind Harmer
4.739
274772LINCOLN ;3U
Adder
4.584
972228AH1-698 GEN2
Adder
2.007
274676JOLIET 29;8U
Adder
15.952
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.149
274729ELWOOD EC;1P
Adder
8.848
274730ELWOOD EC;6P
Adder
8.849
274734ELWOOD EC;8P
Adder
8.849
274736ELWOOD EC;9P
Adder
8.849
970707AG2-453 GEN
Solar/Wind Harmer
12.267
23888502TROY G1
50/50
2.643
23888602TROY G2
50/50
2.643
972211AH1-690 GEN
50/50
234.282
23906902RICHG6
50/50
1.04
23906702RICHG4
50/50
1.037
23906802RICHG5
50/50
0.758
970817AG2-515 GEN
Solar/Wind Harmer
14.376
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
945641AF1-229 GEN
Solar/Wind Harmer
0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.032
971549AH1-272 GEN
Solar/Wind Harmer
11.871
270297AD1-101 GEN
Solar/Wind Harmer
0.001
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0
971617AH1-308 GEN
Solar/Wind Harmer
3.125
970513AG2-328 GEN
Solar/Wind Harmer
1.623
970517AG2-330 GEN
Solar/Wind Harmer
9.737
943121AE2-341 GEN
Solar/Wind Harmer
6.229
943591AF1-030 GEN
Solar/Wind Harmer
4.142
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
16.565
274682WAUKEGAN ;7U
Adder
9.512
276805AD2-038 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.663
274872LEEDK;1U
Solar/Wind Harmer
0.134
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.388
274855GSG-6 ;RU
Solar/Wind Harmer
0.133
274850MENDOTA H;RU
Solar/Wind Harmer
0.043
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.065
959091AF2-200 GEN
Solar/Wind Harmer
7.251
970571AG2-364 GEN
Solar/Wind Harmer
7.226
972236AH1-702 GEN2
Adder
1.135
270377AD1-106 GEN
Solar/Wind Harmer
1.364
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
4.772
274767LEE CO EC;8U
Adder
0.229
276157O29GEN1
Solar/Wind Harmer
0.575
274878BISHOP HL;2U
Solar/Wind Harmer
0.119
942111AE2-223 GEN
Solar/Wind Harmer
1.148
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.278
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.488
959611AF2-252 GEN
Solar/Wind Harmer
1.165
965931AG1-462 GEN
Solar/Wind Harmer
8.873
247642Z2-115 C
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
0.379
970291AG2-192 GEN
Solar/Wind Harmer
0.345
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.563
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
946031AF1-268 GEN
Solar/Wind Harmer
3.219
276621W2-048 GEN
Solar/Wind Harmer
0.169
276838X2-022 GEN2
Solar/Wind Harmer
0.189
962511AG1-100 GEN
Solar/Wind Helper
0.361
203830AF1-094 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.154
254305AE2-115 C
Solar/Wind Helper
0.117
20334926Z1-069 C
Solar/Wind Helper
0.662
958821AF2-173 GEN
Solar/Wind Harmer
1.049
270435AC2-044 GEN
Solar/Wind Harmer
0.621
971989AH1-539 GEN
Solar/Wind Harmer
2.024
971619AH1-309 GEN
Solar/Wind Harmer
2.091
965041AG1-368 GEN
Solar/Wind Harmer
4.612
965051AG1-369 GEN
Solar/Wind Harmer
2.289
971771AH1-392 GEN
Solar/Wind Harmer
4.424
270302AB2-170 GEN
Solar/Wind Harmer
0.003
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971653AH1-327 GEN
Solar/Wind Harmer
0.621
971769AH1-391 GEN
Solar/Wind Harmer
4.822
971567AH1-282 GEN
Solar/Wind Harmer
6.357
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971347AH1-153 GEN
Solar/Wind Harmer
6.22
963791AG1-232 GEN
Solar/Wind Harmer
5.569
270578AF1-285 GEN2
Solar/Wind Harmer
0.274
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
270071AF1-092 GEN
Solar/Wind Harmer
7.505
274814UNIV PK N;0U
Adder
2.786
274807UNIV PK N;3U
Adder
2.78
274805UNIV PK N;1U
Adder
2.768
274811UNIV PK N;7U
Adder
2.762
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.1
274827FISK ;RP
Adder
4.228
971611AH1-305 GEN
Solar/Wind Harmer
2.257
960591AF2-350 GEN
Solar/Wind Harmer
3.791
274775LINCOLN ;6U
Adder
4.584
274776LINCOLN ;7U
Adder
4.584
274777LINCOLN ;8U
Adder
4.584
972227AH1-698 GEN1
Adder
1.413
274687WILL CNTY;4U
Adder
15.095
274687WILL CNTY;4U
Adder
15.095
274675JOLIET 29;7U
Adder
16.543
274675JOLIET 29;7U
Adder
15.952
274731ELWOOD EC;2P
Adder
8.848
274733ELWOOD EC;3P
Adder
8.848
274735ELWOOD EC;4P
Adder
8.848
274728ELWOOD EC;5P
Adder
8.849
270024AE2-089 GEN
Solar/Wind Harmer
0.004
970833AG2-524 GEN
Solar/Wind Harmer
4.112
970833AG2-524 GEN
Solar/Wind Harmer
2.741
274746AC1-111 G10
Adder
2.978
274744AC1-111 GEN8
Adder
2.978
276868AE1-113 GEN
Solar/Wind Harmer
0.736
276882AE2-255 GEN
Solar/Wind Harmer
0.429
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
24729505KEY G4
Adder
3.405
971177AH1-047 GEN
Solar/Wind Harmer
2.252
971411AH1-196 GEN
Solar/Wind Harmer
5.463
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
971675AH1-338 GEN
Solar/Wind Harmer
1.419
971171AH1-044 GEN
Solar/Wind Harmer
7.251
274823ROCKFORD ;21
Adder
10.105
926823AC1-168 GEN
Solar/Wind Harmer
0.613
970169AG2-114 GEN
Solar/Wind Harmer
3.606
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.777
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
961011AF2-392 GEN
Solar/Wind Harmer
2.09
957751AF2-069 GEN
Solar/Wind Harmer
0.117
965101AG1-375 GEN
Solar/Wind Harmer
3.538
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.709
941731AE2-173 GEN
Solar/Wind Harmer
2.944
963841AG1-237 GEN
Solar/Wind Harmer
1.521
946321AF1-296 GEN
Solar/Wind Harmer
1.955
971609AH1-304 GEN
Solar/Wind Harmer
0.569
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.655
270594AE1-207 GEN
Solar/Wind Harmer
3.835
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.123
970115AG2-085 GEN
Solar/Wind Harmer
1.349
270543AE2-219 C
Solar/Wind Harmer
0.002
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0
241886AC2-103 GEN2
Solar/Wind Helper
7.083
241982AE2-343 S C
Solar/Wind Helper
0.123
254304AE2-114 C
Solar/Wind Helper
0.117
203846AF2-130 C
Solar/Wind Helper
0.257
241997AF1-093 GEN
Solar/Wind Helper
0.136
203804AE2-113_GEN
Solar/Wind Helper
0.892
23888802TROY G4
50/50
2.643
24190002OREGON_ST1
50/50
2.928
24189802OREGON_CT1
50/50
2.221
241996AE2-282_GEN
Solar/Wind Harmer
0.007
971677AH1-339 GEN
Solar/Wind Harmer
0.714
970621AG2-405 GEN
Solar/Wind Harmer
1.043
970623AG2-406 GEN
Solar/Wind Harmer
0.966
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.178
246937BC-WTG2
Solar/Wind Harmer
0.199
961051AF2-396 GEN
Solar/Wind Harmer
9.419
961051AF2-396 GEN
Solar/Wind Harmer
6.28
957891AF2-083 GEN
Solar/Wind Harmer
0.001
247620Y3-023
Adder
0.301
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
4.433
970627AG2-408 GEN
Solar/Wind Harmer
1.33
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
5.205
965791AG1-447 GEN
Solar/Wind Harmer
3.817
270224U2-072_GEN2
Solar/Wind Harmer
0
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274808UNIV PK N;4U
Adder
2.75
274803UNIV PARK;6U
Adder
3.182
942221AE2-234 GEN
Solar/Wind Harmer
0.019
274888KELLY CRK;1U
Solar/Wind Harmer
0.223
274887GEN-1.85
Solar/Wind Harmer
0.1
276843GEN-1.7
Solar/Wind Harmer
0.123
958011AF2-095 GEN
Solar/Wind Harmer
5.459
274770LINCOLN ;1U
Adder
4.584
274771LINCOLN ;2U
Adder
4.584
972259AH1-714 GEN
Adder
10.294
274674JOLIET 9 ;6U
Adder
8.288
970321AG2-212 GEN
Solar/Wind Harmer
1.623
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.572
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.503
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.69
274695ROCKY RD ;2P
Adder
5.891
274693ROCKY RD ;1P
Adder
5.833
274697ROCKY RD ;3P
Adder
1.6
274696ROCKY RD ;4P
Adder
6.03
274683WAUKEGAN ;8U
Adder
11.144
274683WAUKEGAN ;8U
Adder
9.394
958491AF2-143 GEN
Solar/Wind Harmer
5.526
962691AG1-118 GEN
Solar/Wind Harmer
11.015
274879MINONK ;1U
Solar/Wind Harmer
0.155
970921AG2-575 GEN
Solar/Wind Harmer
3.666
970921AG2-575 GEN
Solar/Wind Harmer
1.222
942991AE2-321 GEN
Solar/Wind Harmer
4.078
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
7.279
971335AH1-147 GEN
Solar/Wind Harmer
7.279
971341AH1-150 GEN
Solar/Wind Harmer
7.251
971343AH1-151 GEN
Solar/Wind Harmer
7.251
274856ECOGROVE ;U1
Solar/Wind Harmer
0.085
276611AD2-172 GEN
Solar/Wind Harmer
0.001
971231AH1-075 GEN
Solar/Wind Harmer
0.412
938861AE1-114 GEN
Solar/Wind Harmer
2.033
274764LEE CO EC;5U
Adder
4.784
274765LEE CO EC;6U
Adder
4.784
274762LEE CO EC;3U
Adder
4.772
274763LEE CO EC;4U
Adder
4.727
966841AG1-555 GEN
Solar/Wind Harmer
0.405
276603SUBLETTE C
Solar/Wind Harmer
0
944541AF1-119 GEN
Solar/Wind Harmer
0.239
960971AF2-388 GEN
Solar/Wind Harmer
2.094
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.14
276646AC1-214 GEN2
Solar/Wind Harmer
0.14
276741O09 GEN1
Solar/Wind Harmer
0.127
276708O09 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.165
964611AG1-324 GEN
Solar/Wind Harmer
0.262
270599AE1-208 GEN
Solar/Wind Harmer
3.195
270031AE2-169
Solar/Wind Harmer
1.917
970241AG2-163 GEN
Solar/Wind Harmer
2.013
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.487
971613AH1-306 GEN
Solar/Wind Harmer
1.644
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
3.372
970825AG2-519 GEN
Solar/Wind Harmer
3.73
970883AG2-550 GEN
Solar/Wind Harmer
3.346
970885AG2-551 GEN
Solar/Wind Harmer
1.115
203947AF1-006 C
Solar/Wind Helper
0.402
203980AG1-197 GEN
Solar/Wind Helper
0.262
203979AG1-198 GEN
Solar/Wind Helper
0.204
241967AE2-285_GEN
Solar/Wind Helper
0.354
241801AE1-079 GEN
Solar/Wind Helper
0.138
241985AE1-237 GEN
Solar/Wind Helper
0.137
962101AG1-054 GEN
Solar/Wind Helper
0.34
946381AF1-302 GEN
Solar/Wind Helper
0.108
238217AF1-153 C O1
Solar/Wind Helper
0.114
23888702TROY G3
50/50
2.643
972253AH1-711 GEN
50/50
80.741
23920202STRYCT
50/50
2.39
24189902OREGON_CT2
50/50
2.176
972301AH1-735 GEN
50/50
8.755
23906402RICHG1
50/50
1.751
23906502RICHG2&3
50/50
1.747
241858AF1-205_GEN
Solar/Wind Harmer
4.885
241808AF1-120 C
Solar/Wind Harmer
0.004
241840AF1-064_GEN
Solar/Wind Harmer
0.005
270361_3
Solar/Wind Harmer
4.971
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
970515AG2-329 GEN
Solar/Wind Harmer
15.158
944231AF1-091 GEN
Solar/Wind Harmer
1.488
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.199
270489AE1-102 GEN1
Solar/Wind Harmer
0.637
965421AG1-410 GEN
Solar/Wind Harmer
14.575
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.476
24695305TIMB G C
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
8.299
270505AE1-170 C O1
Solar/Wind Harmer
4.878
247521TR3_G114
Solar/Wind Harmer
0.167
270246TR4_N_V150
Solar/Wind Harmer
0.03
24639705ELKHART HY
Adder
0.1
270063AE2-323 C
Solar/Wind Harmer
0.004
965011AG1-365 GEN
Solar/Wind Harmer
4.433
270462AD2-086
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
8.434
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274751CRETE EC ;1U
Adder
4.596
274754CRETE EC ;4U
Adder
4.596
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
5.035
274723RIVER EC ;12
Adder
9.924
274812UNIV PK N;8U
Adder
2.762
276164X3-005 C
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
3.173
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.739
276776AD2-060 GEN
Solar/Wind Harmer
0.396
274773LINCOLN ;4U
Adder
4.584
274774LINCOLN ;5U
Adder
4.584
274676JOLIET 29;8U
Adder
16.543
941551AE2-152 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
8.849
274674JOLIET 9 ;6U
Adder
8.288
970245AG2-165 GEN
Solar/Wind Harmer
1.623
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.45
274682WAUKEGAN ;7U
Adder
9.512
274828WAUKEGAN ;BP
Adder
5.841
276901AD2-066 C O1
Solar/Wind Harmer
0.004
939401AE1-172 GEN
Solar/Wind Harmer
2.747
962781AG1-127 GEN
Solar/Wind Harmer
3.489
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
971997AH1-543 GEN
Solar/Wind Harmer
1.918
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276861AD2-134 GEN
Solar/Wind Harmer
0.065
957471AF2-041 GEN
Solar/Wind Harmer
10.876
959081AF2-199 GEN
Solar/Wind Harmer
3.625
971067AG2-660 GEN
Solar/Wind Harmer
1.208
274822ROCKFORD ;11
Adder
10.179
970569AG2-363 GEN
Solar/Wind Harmer
10.839
972235AH1-702 GEN1
Adder
1.305
970819AG2-516 GEN
Solar/Wind Harmer
4.326
971475AH1-234 GEN
Solar/Wind Harmer
1.747
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
4.772
274766LEE CO EC;7U
Adder
4.716
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
965651AG1-433 GEN
Solar/Wind Harmer
1.047
276158O29GEN2
Solar/Wind Harmer
0
274877BISHOP HL;1U
Solar/Wind Harmer
0.119
958861AF2-177 GEN
Solar/Wind Harmer
1.533
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.946
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
945371AF1-202 GEN
Solar/Wind Harmer
0
963741AG1-226 GEN
Solar/Wind Harmer
8.165
970291AG2-192 GEN
Solar/Wind Harmer
0.448
972175AH1-670 GEN
Solar/Wind Harmer
2.841
247536S-71 GEN
Solar/Wind Harmer
0.138
270032AE2-172
Solar/Wind Harmer
2.283
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.315
276903AD2-071 C
Solar/Wind Harmer
3.766
970825AG2-519 GEN
Solar/Wind Harmer
1.195
276615X2-022 GEN
Solar/Wind Harmer
0.035
241885AC2-103 GEN1
Solar/Wind Helper
7.083
241807AE2-176_GEN
Solar/Wind Helper
1.701
961971AG1-040 GEN
Solar/Wind Helper
0.352
203835AF1-098 GEN
Solar/Wind Helper
1.388
203860AG1-193 C
Solar/Wind Helper
0.156
241966AE1-183 GEN
Solar/Wind Helper
0.136
254303AC2-168 GEN
Solar/Wind Helper
0.079
203954AE2-126 C
Solar/Wind Helper
0.223
991177J1571 G
External Queue
18.513126373291016
990142J1224
External Queue
15.35684871673584
990527J1329
External Queue
2.100800037384033
991182J1586 G
External Queue
28.404245376586914
CBM West 1LTFEXP_CBM-W1->PJM
CBM
107.191
CBM South 1LTFEXP_CBM-S1->PJM
CBM
11.28
MECLTFEXP_MEC->PJM
CLTF
7.783
SIGELTFEXP_SIGE->PJM
CLTF
0.206
CPLELTFEXP_CPLE->PJM
CLTF
0.787
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.86
LAGNLTFEXP_LAGN->PJM
CLTF
6.243
CBM South 2LTFEXP_CBM-S2->PJM
CBM
3.59
TVALTFEXP_TVA->PJM
CLTF
2.868
NYPJM->LTFIMP_NY
CLTF
2.006
LGEELTFEXP_LGEE->PJM
CLTF
2.487
WECLTFEXP_WEC->PJM
CLTF
1.978
AG2-052LTFEXP_AG2-052->PJM
LTF
0.127
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 05ALLEN-05RPMONE 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05ALLEN-05RPMONE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.78 %
Rating:1737.0 MVA
Rating Type:B
MVA to Mitigate:2115.3
MW Contribution:4.06
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
10.521
24729505KEY G4
50/50
6.883
24653605MOTTVILLE
50/50
0.004
270144AC1-141 ST1_
50/50
1.82
24643105BUCHANAN
50/50
0.011
963791AG1-232 GEN
Solar/Wind Harmer
11.809
965041AG1-368 GEN
Solar/Wind Harmer
8.577
270071AF1-092 GEN
Solar/Wind Harmer
14.687
965051AG1-369 GEN
Solar/Wind Harmer
3.667
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.239
971771AH1-392 GEN
Solar/Wind Harmer
5.998
971347AH1-153 GEN
Solar/Wind Harmer
8.913
971619AH1-309 GEN
Solar/Wind Harmer
2.669
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.451
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
970583AG2-370 GEN
50/50
2.859
960851AF2-376 GEN
50/50
2.155
24641605TWIN BRNCH
50/50
0.016
270142AC1-141 CT1_
50/50
2.055
24642205MAYFLWER
50/50
0.571
944961AF1-161 GEN
50/50
2.434
962601AG1-109 GEN
50/50
2.434
24344005CKG1
50/50
5.289
959331AF2-224 GEN
Solar/Wind Harmer
9.739
965021AG1-366 GEN
Solar/Wind Harmer
4.638
970031AG2-029 GEN
Solar/Wind Harmer
5.561
270043AE2-236 GEN
Solar/Wind Harmer
5.288
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
944531AF1-118 GEN
Solar/Wind Harmer
32.162
971617AH1-308 GEN
Solar/Wind Harmer
5.291
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.927
970349AG2-230 GEN
Solar/Wind Harmer
8.913
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.372
970517AG2-330 GEN
Solar/Wind Harmer
14.231
274752CRETE EC ;2U
Adder
6.419
274753CRETE EC ;3U
Adder
6.419
274724RIVER EC ;11
Adder
13.745
247604X1-042
Adder
0.322
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.474
274802UNIV PARK;5U
Adder
4.445
274826FISK ;BP
Adder
8.338
274800UNIV PARK;3U
Adder
4.433
972038AH1-567 GEN2
Adder
0.277
276806AD2-047 C O1
Solar/Wind Harmer
3.002
970941AG2-585 GEN
Solar/Wind Harmer
6.622
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.805
970707AG2-453 GEN
Solar/Wind Harmer
17.2
276897AD1-100 C
Solar/Wind Harmer
0.007
970615AG2-402 GEN
50/50
4.638
24729405KEY G3
50/50
0.376
24729305KEY G2
50/50
0.369
24729205KEY G1
50/50
0.368
247620Y3-023
50/50
0.473
270102X2-052 ST
50/50
1.304
270100X2-052 CT1
50/50
1.202
270101X2-052 CT2
50/50
1.202
970611AG2-400 GEN
Solar/Wind Harmer
13.913
970627AG2-408 GEN
Solar/Wind Harmer
4.174
942221AE2-234 GEN
Solar/Wind Harmer
0.035
944541AF1-119 GEN
Solar/Wind Harmer
0.43
960971AF2-388 GEN
Solar/Wind Harmer
3.767
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.858
961051AF2-396 GEN
Solar/Wind Harmer
7.905
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
7.075
965791AG1-447 GEN
Solar/Wind Harmer
5.189
270599AE1-208 GEN
Solar/Wind Harmer
5.131
270031AE2-169
Solar/Wind Harmer
3.079
970321AG2-212 GEN
Solar/Wind Harmer
2.372
274808UNIV PK N;4U
Adder
3.841
274770LINCOLN ;1U
Adder
6.474
274771LINCOLN ;2U
Adder
6.474
274803UNIV PARK;6U
Adder
4.445
274888KELLY CRK;1U
Solar/Wind Harmer
0.311
274887GEN-1.85
Solar/Wind Harmer
0.139
276843GEN-1.7
Solar/Wind Harmer
0.171
958011AF2-095 GEN
Solar/Wind Harmer
7.629
972259AH1-714 GEN
Adder
14.402
274674JOLIET 9 ;6U
Adder
11.55
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.959
958481AF2-142 GEN
Solar/Wind Harmer
7.707
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.695
274695ROCKY RD ;2P
Adder
8.163
274693ROCKY RD ;1P
Adder
8.082
274697ROCKY RD ;3P
Adder
2.217
274696ROCKY RD ;4P
Adder
8.355
274683WAUKEGAN ;8U
Adder
15.422
274683WAUKEGAN ;8U
Adder
13
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
15.227
958491AF2-143 GEN
Solar/Wind Harmer
7.614
970921AG2-575 GEN
Solar/Wind Harmer
5.064
970921AG2-575 GEN
Solar/Wind Harmer
1.688
971613AH1-306 GEN
Solar/Wind Harmer
2.426
274879MINONK ;1U
Solar/Wind Harmer
0.213
942991AE2-321 GEN
Solar/Wind Harmer
5.619
971333AH1-146 GEN
Solar/Wind Harmer
10.011
971335AH1-147 GEN
Solar/Wind Harmer
10.011
960441AF2-335 GEN
Solar/Wind Harmer
4.991
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.953
971343AH1-151 GEN
Solar/Wind Harmer
9.953
970825AG2-519 GEN
Solar/Wind Harmer
5.49
274856ECOGROVE ;U1
Solar/Wind Harmer
0.116
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.774
274764LEE CO EC;5U
Adder
6.52
274765LEE CO EC;6U
Adder
6.52
274762LEE CO EC;3U
Adder
6.505
274763LEE CO EC;4U
Adder
6.443
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.365
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.883
276741O09 GEN1
Solar/Wind Harmer
0.172
276708O09 GEN2
Solar/Wind Harmer
0.172
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.189
276646AC1-214 GEN2
Solar/Wind Harmer
0.189
966841AG1-555 GEN
Solar/Wind Harmer
0.542
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.165
960611AF2-352 GEN
Solar/Wind Harmer
1.556
970241AG2-163 GEN
Solar/Wind Harmer
2.633
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.003
276916AD2-100_GEN
Solar/Wind Harmer
8.729
276911AD2-131_GEN
Solar/Wind Harmer
0.575
970883AG2-550 GEN
Solar/Wind Harmer
4.063
970885AG2-551 GEN
Solar/Wind Harmer
1.354
945391AF1-204 GEN
Solar/Wind Harmer
4.312
970623AG2-406 GEN
Solar/Wind Harmer
0.709
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.538
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.812
246938BC-WTG3
Solar/Wind Helper
11.029
246937BC-WTG2
Solar/Wind Helper
10.843
270224U2-072_GEN2
Solar/Wind Helper
0.855
270227U2-072_GEN3
Solar/Wind Helper
0.855
270228U2-072_GEN4
Solar/Wind Helper
0.855
270231U2-072_GEN5
Solar/Wind Helper
0.855
270471AD2-092_GEN
Solar/Wind Helper
0.817
253378AE2-206_GEN
Solar/Wind Helper
0.657
276820AF1-078_GEN
Solar/Wind Helper
0.307
241960AC2-195 GEN
Solar/Wind Helper
0.657
971609AH1-304 GEN
Solar/Wind Harmer
0.914
274814UNIV PK N;0U
Adder
3.891
274807UNIV PK N;3U
Adder
3.883
274805UNIV PK N;1U
Adder
3.866
274811UNIV PK N;7U
Adder
3.858
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.474
274776LINCOLN ;7U
Adder
6.474
274777LINCOLN ;8U
Adder
6.474
972037AH1-567 GEN1
Adder
0.14
274827FISK ;RP
Adder
5.909
960591AF2-350 GEN
Solar/Wind Harmer
5.298
972227AH1-698 GEN1
Adder
1.975
274687WILL CNTY;4U
Adder
21.05
274687WILL CNTY;4U
Adder
21.05
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
23.063
274675JOLIET 29;7U
Adder
22.239
274731ELWOOD EC;2P
Adder
12.325
274733ELWOOD EC;3P
Adder
12.325
274735ELWOOD EC;4P
Adder
12.325
274728ELWOOD EC;5P
Adder
12.325
970833AG2-524 GEN
Solar/Wind Harmer
5.728
970833AG2-524 GEN
Solar/Wind Harmer
3.819
971611AH1-305 GEN
Solar/Wind Harmer
3.084
274746AC1-111 G10
Adder
4.142
274744AC1-111 GEN8
Adder
4.142
970289AG2-191 GEN
Solar/Wind Harmer
0.971
270594AE1-207 GEN
Solar/Wind Harmer
5.661
276868AE1-113 GEN
Solar/Wind Harmer
1.012
276882AE2-255 GEN
Solar/Wind Harmer
0.59
971177AH1-047 GEN
Solar/Wind Harmer
3.102
971411AH1-196 GEN
Solar/Wind Harmer
7.515
971675AH1-338 GEN
Solar/Wind Harmer
1.952
970115AG2-085 GEN
Solar/Wind Harmer
1.996
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.953
274823ROCKFORD ;21
Adder
13.855
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.837
970169AG2-114 GEN
Solar/Wind Harmer
4.915
971681AH1-341 GEN
Solar/Wind Harmer
7.885
971549AH1-272 GEN
Solar/Wind Harmer
10.103
961011AF2-392 GEN
Solar/Wind Harmer
2.842
957751AF2-069 GEN
Solar/Wind Harmer
0.159
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.986
941731AE2-173 GEN
Solar/Wind Harmer
3.957
946321AF1-296 GEN
Solar/Wind Harmer
2.629
963841AG1-237 GEN
Solar/Wind Harmer
2.014
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.161
276848AB2-070 GEN3
Solar/Wind Harmer
0.16
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.367
971029AG2-637 GEN
Solar/Wind Harmer
5.468
971673AH1-337 GEN
Solar/Wind Harmer
2.273
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.571
270317AD1-130_GEN
Solar/Wind Helper
4.044
966831AG1-554 GEN
Solar/Wind Helper
0.856
270284AF1-227 GEN1
Solar/Wind Helper
1.824
270286AF1-227 GEN2
Solar/Wind Helper
0.669
270287AF1-227 GEN3
Solar/Wind Helper
0.669
270499AE1-146 GEN
Solar/Wind Helper
1.895
945641AF1-229 GEN
Solar/Wind Helper
0.904
960861AF2-377 GEN
50/50
2.449
970521AG2-332 GEN
50/50
11.057
24639705ELKHART HY
50/50
0.153
270143AC1-141 CT2_
50/50
2.055
24344105CKG2
50/50
6.288
24307105BERRINSP G
50/50
0.018
965011AG1-365 GEN
Solar/Wind Harmer
13.913
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.268
270246TR4_N_V150
Solar/Wind Harmer
0.047
944231AF1-091 GEN
Solar/Wind Harmer
1.894
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.883
958861AF2-177 GEN
Solar/Wind Harmer
2.703
945111AF1-176 GEN
Solar/Wind Harmer
10.846
270505AE1-170 C O1
Solar/Wind Harmer
6.228
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.049
970245AG2-165 GEN
Solar/Wind Harmer
2.372
970373AG2-245 GEN
Solar/Wind Harmer
11.463
274751CRETE EC ;1U
Adder
6.419
274754CRETE EC ;4U
Adder
6.419
274723RIVER EC ;12
Adder
13.914
274812UNIV PK N;8U
Adder
3.858
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.474
274774LINCOLN ;5U
Adder
6.474
274801UNIV PARK;4U
Adder
4.433
276776AD2-060 GEN
Solar/Wind Harmer
0.553
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.867
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
23.063
274674JOLIET 9 ;6U
Adder
11.55
274732ELWOOD EC;7P
Adder
12.325
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.476
274745AC1-111 GEN9
Adder
4.142
276691AA1-018 GEN1
Solar/Wind Harmer
0.622
274682WAUKEGAN ;7U
Adder
13.17
970291AG2-192 GEN
Solar/Wind Harmer
0.664
274828WAUKEGAN ;BP
Adder
8.084
270005AE1-210 C O1
Solar/Wind Harmer
1.101
965031AG1-367 GEN
Solar/Wind Harmer
5.08
962781AG1-127 GEN
Solar/Wind Harmer
4.819
939401AE1-172 GEN
Solar/Wind Harmer
3.786
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.37
274872LEEDK;1U
Solar/Wind Harmer
0.003
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.239
276893AG1-478 C
Solar/Wind Harmer
0.207
274729ELWOOD EC;1P
Adder
12.325
274730ELWOOD EC;6P
Adder
12.325
274734ELWOOD EC;8P
Adder
12.325
274736ELWOOD EC;9P
Adder
12.325
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.672
943591AF1-030 GEN
Solar/Wind Harmer
5.767
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
13.17
970289AG2-191 GEN
Solar/Wind Harmer
0.562
970291AG2-192 GEN
Solar/Wind Harmer
0.511
958821AF2-173 GEN
Solar/Wind Harmer
7.111
270004AE1-209 GEN
Solar/Wind Harmer
1.101
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.185
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.534
274855GSG-6 ;RU
Solar/Wind Harmer
0.184
274850MENDOTA H;RU
Solar/Wind Harmer
0.059
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.09
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.985
959091AF2-200 GEN
Solar/Wind Harmer
9.953
972236AH1-702 GEN2
Adder
1.555
970571AG2-364 GEN
Solar/Wind Harmer
9.859
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.505
274767LEE CO EC;8U
Adder
6.428
946031AF1-268 GEN
Solar/Wind Harmer
4.635
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.294
276157O29GEN1
Solar/Wind Harmer
0.779
274878BISHOP HL;2U
Solar/Wind Harmer
0.161
942111AE2-223 GEN
Solar/Wind Harmer
1.543
965931AG1-462 GEN
Solar/Wind Harmer
11.906
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
14.002
959611AF2-252 GEN
Solar/Wind Harmer
1.556
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.161
971993AH1-541 GEN
Solar/Wind Harmer
2.041
276621W2-048 GEN
Solar/Wind Harmer
0.219
276838X2-022 GEN2
Solar/Wind Harmer
0.245
942481AE2-261 GEN
Solar/Wind Harmer
12.535
970193AG2-126 GEN
Solar/Wind Harmer
6.087
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.445
24728505AND G1
Adder
2.125
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.9
970519AG2-331 GEN
Solar/Wind Harmer
8.446
970699AG2-449 GEN
Solar/Wind Harmer
0.812
270485AE1-090_GEN
Solar/Wind Helper
0.318
942871AE2-306 GEN
Solar/Wind Helper
0.434
270541AE2-072 C
Solar/Wind Helper
0.891
971997AH1-543 GEN
Solar/Wind Harmer
2.638
276861AD2-134 GEN
Solar/Wind Harmer
0.09
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.929
959081AF2-199 GEN
Solar/Wind Harmer
4.976
971067AG2-660 GEN
Solar/Wind Harmer
1.659
274822ROCKFORD ;11
Adder
13.956
970825AG2-519 GEN
Solar/Wind Harmer
1.759
972235AH1-702 GEN1
Adder
1.788
970819AG2-516 GEN
Solar/Wind Harmer
5.921
970569AG2-363 GEN
Solar/Wind Harmer
14.789
971475AH1-234 GEN
Solar/Wind Harmer
2.388
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.505
274766LEE CO EC;7U
Adder
6.428
276903AD2-071 C
Solar/Wind Harmer
5.417
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.161
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
6.647
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.748
963741AG1-226 GEN
Solar/Wind Harmer
10.683
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.3
247536S-71 GEN
Solar/Wind Harmer
0.179
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.713
276615X2-022 GEN
Solar/Wind Harmer
0.046
965911AG1-460 GEN
Solar/Wind Harmer
0.838
24728605AND G2
Adder
2.125
970773AG2-487 GEN
Solar/Wind Harmer
0.635
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.323
246936BC-WTG1
Solar/Wind Helper
10.843
270462AD2-086
Solar/Wind Helper
3.651
270223U2-072_GEN1
Solar/Wind Helper
0.855
270578AF1-285 GEN2
Solar/Wind Helper
0.579
270391AF1-285 GEN3
Solar/Wind Helper
0.579
247522W1-056 GEN
Solar/Wind Helper
1.138
960841AF2-375 GEN
Solar/Wind Helper
1.139
270349AD2-093_GEN
Solar/Wind Helper
0.817
944201AF1-088_MTX
Adder
57.673
957141AF2-008_MTX
Adder
8.943
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.466
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.567
MECLTFEXP_MEC->PJM
CLTF
10.019
SIGELTFEXP_SIGE->PJM
CLTF
0.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.858
LAGNLTFEXP_LAGN->PJM
CLTF
6.132
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.094
TVALTFEXP_TVA->PJM
CLTF
2.49
NYPJM->LTFIMP_NY
CLTF
1.126
LGEELTFEXP_LGEE->PJM
CLTF
1.931
WECLTFEXP_WEC->PJM
CLTF
2.707
AG2-052LTFEXP_AG2-052->PJM
LTF
0.175
AH1-155LTFEXP_AH1-155->PJM
LTF
0.263

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:109.09 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1312.32
MW Contribution:5.17
Bus #Bus NameTypeMW Contribution
25326109MON D
50/50
2.072
253370AE2-315 SEC1
50/50
3.048
25322209TAIT E
50/50
14.544
25322209TAIT E
50/50
14.217
270518AE2-148 GEN
Solar/Wind Harmer
58.824
253394AE2-221_GEN
Solar/Wind Harmer
6.204
253398AE2-221_GEN2
Solar/Wind Harmer
6.204
253317AC1-085 GEN4
Solar/Wind Harmer
9.666
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.13
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.847
961491AF2-440 GEN
Solar/Wind Harmer
1.599
25326509SID D
Adder
0.983
270186AC1-089 GEN
Solar/Wind Harmer
4.107
253378AE2-206_GEN
Solar/Wind Harmer
2.352
276820AF1-078_GEN
Solar/Wind Harmer
1.045
24728805RICHG1
Adder
2.35
24728905RICHG2
Adder
2.35
339221AD2-048_GEN
Solar/Wind Harmer
0.897
972043AH1-570 GEN
Solar/Wind Harmer
1.438
972045AH1-571 GEN
Solar/Wind Harmer
1.15
971125AH1-004 GEN
Solar/Wind Harmer
2.22
970107AG2-081 GEN
Solar/Wind Harmer
1.665
970235AG2-159 GEN
Solar/Wind Harmer
2.18
970235AG2-159 GEN
Solar/Wind Harmer
1.331
970883AG2-550 GEN
Solar/Wind Harmer
5.173
970885AG2-551 GEN
Solar/Wind Harmer
1.203
942891AE2-308 GEN
Solar/Wind Harmer
5.018
960161AF2-307 GEN
Solar/Wind Harmer
3.198
270383AD1-128 GEN
Solar/Wind Harmer
2.932
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.854
253370AE2-315 SEC1
50/50
3.048
253371AE2-315 SEC2
50/50
2.883
25322309TAIT W
50/50
0.714
25322209TAIT E
50/50
0.706
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.506
253316AC1-085 GEN3
Solar/Wind Harmer
9.666
253433AC1-085 GEN1
Solar/Wind Harmer
6.136
946181AF1-283 GEN
Solar/Wind Harmer
15.002
25196608WSDLE5
Adder
7.75
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.941
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.028
958171AF2-111 GEN
Solar/Wind Harmer
17.743
25196008MFTGT1
Adder
0.952
972167AH1-666 GEN
Solar/Wind Harmer
5.337
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.419
970093AG2-073 GEN
Solar/Wind Harmer
4.788
270356AE2-297 GEN
Solar/Wind Harmer
2.179
966571AG1-526 GEN
Solar/Wind Harmer
9.998
960801AF2-371 GEN
Solar/Wind Helper
0.809
964871AG1-351 GEN
Solar/Wind Helper
0.558
241955AC1-078 GEN
Solar/Wind Helper
1.486
270273AD2-016 GEN
Solar/Wind Helper
1.381
253372AE2-315 SEC3
50/50
2.883
253372AE2-315 SEC3
50/50
2.883
25322309TAIT W
50/50
0.723
963581AG1-207 GEN
50/50
13.107
25306009OHH W.
50/50
4.035
253349AC2-067 GEN
Solar/Wind Harmer
6.045
253400AC2-068 GEN
Solar/Wind Harmer
2.431
241972AD1-140 GEN
Solar/Wind Harmer
5.065
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.978
25196308WSDLE2
Adder
7.909
25196208WSDLE1
Adder
7.889
25196708WSDLE6
Adder
7.869
25196508WSDLE4
Adder
7.671
270156DARBY CT1
Adder
7.427
270157DARBY CT2
Adder
7.409
270158DARBY CT3
Adder
7.29
944031AF1-071 GEN
Solar/Wind Harmer
0.743
25196108MFTGT2
Adder
1.084
25196108MFTGT2
Adder
1.006
270367AC2-061_GEN
Solar/Wind Harmer
2.232
972163AH1-664 GEN
Solar/Wind Harmer
6.559
972165AH1-665 GEN
Solar/Wind Harmer
5.247
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
971673AH1-337 GEN
Solar/Wind Harmer
2.683
971029AG2-637 GEN
Solar/Wind Harmer
8.486
270543AE2-219 C
Solar/Wind Harmer
2.649
3429211JKCT 2G
Adder
6.017
270340AC2-060 GEN
Solar/Wind Harmer
1.553
945631AF1-228 GEN
Solar/Wind Helper
5.272
270520AE2-214 GEN
Solar/Wind Helper
6.82
270054AF2-122 C O1
Solar/Wind Helper
0.9
253370AE2-315 SEC1
50/50
3.048
253371AE2-315 SEC2
50/50
2.883
25322309TAIT W
50/50
0.714
25322209TAIT E
50/50
0.714
25326309TAIT D
50/50
1.634
960071AF2-298 GEN
Solar/Wind Harmer
6.591
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.54
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.941
253325AC1-069 GEN
Solar/Wind Harmer
0.907
270159DARBY CT4
Adder
7.309
25196808ZIMRHP
Adder
60.521
252507AC2-088 GEN
Solar/Wind Harmer
1.402
25196008MFTGT1
Adder
0.983
945681AF1-233 GEN
Solar/Wind Harmer
12.524
339216AC1-074 GEN
Solar/Wind Harmer
0.989
943111AE2-339 GEN
Solar/Wind Harmer
0.484
3429421JKCT 10G
Adder
4.419
3429241JKCT 3G
Adder
6.096
247536S-71 GEN
Solar/Wind Harmer
1.917
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.342
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.887
MECLTFEXP_MEC->PJM
CLTF
3.237
SIGELTFEXP_SIGE->PJM
CLTF
0.182
CPLELTFEXP_CPLE->PJM
CLTF
0.208
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.657
LAGNLTFEXP_LAGN->PJM
CLTF
3.725
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.571
TVALTFEXP_TVA->PJM
CLTF
1.934
NYPJM->LTFIMP_NY
CLTF
0.843
LGEELTFEXP_LGEE->PJM
CLTF
2.977
WECLTFEXP_WEC->PJM
CLTF
0.663

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16620_05ADKINS 345_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16620_05ADKINS 345_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1299.36
MW Contribution:5.2
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.897
253372AE2-315 SEC3
50/50
2.897
25322309TAIT W
50/50
0.726
963581AG1-207 GEN
50/50
13.168
25306009OHH W.
50/50
4.055
253349AC2-067 GEN
Solar/Wind Harmer
6.074
253400AC2-068 GEN
Solar/Wind Harmer
2.443
241972AD1-140 GEN
Solar/Wind Harmer
5.052
252524AE2-267 GEN
Solar/Wind Harmer
1.434
25196408WSDLE3
Adder
8.021
25196308WSDLE2
Adder
7.952
25196208WSDLE1
Adder
7.932
25196708WSDLE6
Adder
7.912
25196508WSDLE4
Adder
7.712
944031AF1-071 GEN
Solar/Wind Harmer
0.747
25196108MFTGT2
Adder
1.09
25196108MFTGT2
Adder
1.012
270367AC2-061_GEN
Solar/Wind Harmer
2.241
972163AH1-664 GEN
Solar/Wind Harmer
6.594
972165AH1-665 GEN
Solar/Wind Harmer
5.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
971673AH1-337 GEN
Solar/Wind Harmer
2.698
971029AG2-637 GEN
Solar/Wind Harmer
8.535
270543AE2-219 C
Solar/Wind Harmer
2.665
3429211JKCT 2G
Adder
6.051
270340AC2-060 GEN
Solar/Wind Harmer
1.549
339211AE2-254 GEN
Solar/Wind Harmer
0.654
270240V3-007_GEN2
Solar/Wind Harmer
2.665
945631AF1-228 GEN
Solar/Wind Helper
5.197
270520AE2-214 GEN
Solar/Wind Helper
6.706
270054AF2-122 C O1
Solar/Wind Helper
0.903
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.709
253303V4-073 C
Solar/Wind Harmer
0.167
253406AD2-031_GEN
Solar/Wind Harmer
1.513
253316AC1-085 GEN3
Solar/Wind Harmer
9.718
253433AC1-085 GEN1
Solar/Wind Harmer
6.169
946181AF1-283 GEN
Solar/Wind Harmer
15.082
25196608WSDLE5
Adder
7.792
25194608D.CRK4
Adder
1.464
252510AF1-249 C
Solar/Wind Harmer
0.37
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253333AC1-068 GEN
Solar/Wind Harmer
0.911
270222AC2-111 GEN
Solar/Wind Harmer
6.061
958171AF2-111 GEN
Solar/Wind Harmer
17.839
25196008MFTGT1
Adder
0.958
972167AH1-666 GEN
Solar/Wind Harmer
5.365
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.444
970093AG2-073 GEN
Solar/Wind Harmer
4.816
270356AE2-297 GEN
Solar/Wind Harmer
2.192
966571AG1-526 GEN
Solar/Wind Harmer
10.057
270437AC2-090 C
Solar/Wind Harmer
2.405
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
241955AC1-078 GEN
Solar/Wind Helper
1.661
270273AD2-016 GEN
Solar/Wind Helper
1.449
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.718
25326309TAIT D
50/50
1.641
960071AF2-298 GEN
Solar/Wind Harmer
6.623
253432AC1-085 GEN2
Solar/Wind Harmer
0.311
946171AF1-282 GEN
Solar/Wind Harmer
11.602
25194608D.CRK4
Adder
1.464
253343AC1-166 GEN
Solar/Wind Harmer
0.945
253325AC1-069 GEN
Solar/Wind Harmer
0.911
25196808ZIMRHP
Adder
60.849
252507AC2-088 GEN
Solar/Wind Harmer
1.41
25196008MFTGT1
Adder
0.989
945681AF1-233 GEN
Solar/Wind Harmer
12.592
339216AC1-074 GEN
Solar/Wind Harmer
0.995
943111AE2-339 GEN
Solar/Wind Harmer
0.487
3429421JKCT 10G
Adder
4.444
3429241JKCT 3G
Adder
6.131
247536S-71 GEN
Solar/Wind Harmer
1.929
942081AE2-220 GEN
Solar/Wind Harmer
2.754
270239V3-007_GEN1
Solar/Wind Harmer
0.741
25326109MON D
50/50
2.081
253370AE2-315 SEC1
50/50
3.063
25322209TAIT E
50/50
14.612
25322209TAIT E
50/50
14.284
270518AE2-148 GEN
Solar/Wind Harmer
59.189
253394AE2-221_GEN
Solar/Wind Harmer
6.237
253398AE2-221_GEN2
Solar/Wind Harmer
6.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.718
25183208HLCRTG
Solar/Wind Harmer
5.477
252519AF1-045_GEN
Solar/Wind Harmer
5.444
252516AE2-318_GEN
Solar/Wind Harmer
4.153
25194408D.CRK1
Adder
6.733
25194508D.CRK3
Adder
1.259
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.862
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
0.989
270186AC1-089 GEN
Solar/Wind Harmer
4.124
253378AE2-206_GEN
Solar/Wind Harmer
2.363
276820AF1-078_GEN
Solar/Wind Harmer
1.05
24728805RICHG1
Adder
2.364
24728905RICHG2
Adder
2.364
339221AD2-048_GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.446
972045AH1-571 GEN
Solar/Wind Harmer
1.157
971125AH1-004 GEN
Solar/Wind Harmer
2.233
970107AG2-081 GEN
Solar/Wind Harmer
1.674
970235AG2-159 GEN
Solar/Wind Harmer
2.193
970235AG2-159 GEN
Solar/Wind Harmer
1.339
970883AG2-550 GEN
Solar/Wind Harmer
5.204
970885AG2-551 GEN
Solar/Wind Harmer
1.21
942891AE2-308 GEN
Solar/Wind Harmer
5.047
960161AF2-307 GEN
Solar/Wind Harmer
3.216
270383AD1-128 GEN
Solar/Wind Harmer
2.95
247621Y3-024
Adder
0.109
24379505HDWTR1G C
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.404
926881AC1-175 GEN
Solar/Wind Harmer
2.404
946101AF1-275 GEN
Solar/Wind Helper
0.84
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.951
MECLTFEXP_MEC->PJM
CLTF
3.265
SIGELTFEXP_SIGE->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.889
LAGNLTFEXP_LAGN->PJM
CLTF
3.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.596
TVALTFEXP_TVA->PJM
CLTF
1.949
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.995
WECLTFEXP_WEC->PJM
CLTF
0.669

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16621_05ADKINS 345_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1299.33
MW Contribution:5.2
Bus #Bus NameTypeMW Contribution
25326109MON D
50/50
2.081
253370AE2-315 SEC1
50/50
3.063
25322209TAIT E
50/50
14.612
25322209TAIT E
50/50
14.284
270518AE2-148 GEN
Solar/Wind Harmer
59.189
253394AE2-221_GEN
Solar/Wind Harmer
6.237
253398AE2-221_GEN2
Solar/Wind Harmer
6.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.718
25183208HLCRTG
Solar/Wind Harmer
5.477
252519AF1-045_GEN
Solar/Wind Harmer
5.444
252516AE2-318_GEN
Solar/Wind Harmer
4.153
25194408D.CRK1
Adder
6.733
25194508D.CRK3
Adder
1.259
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.862
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
0.989
270186AC1-089 GEN
Solar/Wind Harmer
4.124
253378AE2-206_GEN
Solar/Wind Harmer
2.363
276820AF1-078_GEN
Solar/Wind Harmer
1.05
24728805RICHG1
Adder
2.364
24728905RICHG2
Adder
2.364
339221AD2-048_GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.446
972045AH1-571 GEN
Solar/Wind Harmer
1.157
971125AH1-004 GEN
Solar/Wind Harmer
2.233
970107AG2-081 GEN
Solar/Wind Harmer
1.674
970235AG2-159 GEN
Solar/Wind Harmer
2.193
970235AG2-159 GEN
Solar/Wind Harmer
1.339
970883AG2-550 GEN
Solar/Wind Harmer
5.204
970885AG2-551 GEN
Solar/Wind Harmer
1.21
942891AE2-308 GEN
Solar/Wind Harmer
5.047
960161AF2-307 GEN
Solar/Wind Harmer
3.216
270383AD1-128 GEN
Solar/Wind Harmer
2.95
247621Y3-024
Adder
0.109
24379505HDWTR1G C
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.404
926881AC1-175 GEN
Solar/Wind Harmer
2.404
946101AF1-275 GEN
Solar/Wind Helper
0.84
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.709
253303V4-073 C
Solar/Wind Harmer
0.167
253406AD2-031_GEN
Solar/Wind Harmer
1.513
253316AC1-085 GEN3
Solar/Wind Harmer
9.718
253433AC1-085 GEN1
Solar/Wind Harmer
6.169
946181AF1-283 GEN
Solar/Wind Harmer
15.082
25196608WSDLE5
Adder
7.792
25194608D.CRK4
Adder
1.464
252510AF1-249 C
Solar/Wind Harmer
0.37
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253333AC1-068 GEN
Solar/Wind Harmer
0.911
270222AC2-111 GEN
Solar/Wind Harmer
6.061
958171AF2-111 GEN
Solar/Wind Harmer
17.839
25196008MFTGT1
Adder
0.958
972167AH1-666 GEN
Solar/Wind Harmer
5.365
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.444
970093AG2-073 GEN
Solar/Wind Harmer
4.816
270356AE2-297 GEN
Solar/Wind Harmer
2.192
966571AG1-526 GEN
Solar/Wind Harmer
10.057
270437AC2-090 C
Solar/Wind Harmer
2.405
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
241955AC1-078 GEN
Solar/Wind Helper
1.661
270273AD2-016 GEN
Solar/Wind Helper
1.449
253372AE2-315 SEC3
50/50
2.897
253372AE2-315 SEC3
50/50
2.897
25322309TAIT W
50/50
0.726
963581AG1-207 GEN
50/50
13.168
25306009OHH W.
50/50
4.055
253349AC2-067 GEN
Solar/Wind Harmer
6.074
253400AC2-068 GEN
Solar/Wind Harmer
2.443
241972AD1-140 GEN
Solar/Wind Harmer
5.052
252524AE2-267 GEN
Solar/Wind Harmer
1.434
25196408WSDLE3
Adder
8.021
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.718
25326309TAIT D
50/50
1.641
960071AF2-298 GEN
Solar/Wind Harmer
6.623
253432AC1-085 GEN2
Solar/Wind Harmer
0.311
946171AF1-282 GEN
Solar/Wind Harmer
11.602
25194608D.CRK4
Adder
1.464
253343AC1-166 GEN
Solar/Wind Harmer
0.945
253325AC1-069 GEN
Solar/Wind Harmer
0.911
25196808ZIMRHP
Adder
60.849
252507AC2-088 GEN
Solar/Wind Harmer
1.41
25196008MFTGT1
Adder
0.989
945681AF1-233 GEN
Solar/Wind Harmer
12.592
339216AC1-074 GEN
Solar/Wind Harmer
0.995
943111AE2-339 GEN
Solar/Wind Harmer
0.487
3429421JKCT 10G
Adder
4.444
3429241JKCT 3G
Adder
6.131
247536S-71 GEN
Solar/Wind Harmer
1.929
942081AE2-220 GEN
Solar/Wind Harmer
2.754
270239V3-007_GEN1
Solar/Wind Harmer
0.741
25196308WSDLE2
Adder
7.952
25196208WSDLE1
Adder
7.932
25196708WSDLE6
Adder
7.912
25196508WSDLE4
Adder
7.712
944031AF1-071 GEN
Solar/Wind Harmer
0.747
25196108MFTGT2
Adder
1.09
25196108MFTGT2
Adder
1.012
270367AC2-061_GEN
Solar/Wind Harmer
2.241
972163AH1-664 GEN
Solar/Wind Harmer
6.594
972165AH1-665 GEN
Solar/Wind Harmer
5.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
971673AH1-337 GEN
Solar/Wind Harmer
2.698
971029AG2-637 GEN
Solar/Wind Harmer
8.535
270543AE2-219 C
Solar/Wind Harmer
2.665
3429211JKCT 2G
Adder
6.051
270340AC2-060 GEN
Solar/Wind Harmer
1.549
339211AE2-254 GEN
Solar/Wind Harmer
0.654
270240V3-007_GEN2
Solar/Wind Harmer
2.665
945631AF1-228 GEN
Solar/Wind Helper
5.197
270520AE2-214 GEN
Solar/Wind Helper
6.706
270054AF2-122 C O1
Solar/Wind Helper
0.903
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.951
MECLTFEXP_MEC->PJM
CLTF
3.265
SIGELTFEXP_SIGE->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.889
LAGNLTFEXP_LAGN->PJM
CLTF
3.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.596
TVALTFEXP_TVA->PJM
CLTF
1.949
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.995
WECLTFEXP_WEC->PJM
CLTF
0.669

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#16622_05ADKINS 345_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.01 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1299.32
MW Contribution:5.2
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.718
25326309TAIT D
50/50
1.641
960071AF2-298 GEN
Solar/Wind Harmer
6.623
253432AC1-085 GEN2
Solar/Wind Harmer
0.311
946171AF1-282 GEN
Solar/Wind Harmer
11.602
25194608D.CRK4
Adder
1.464
253343AC1-166 GEN
Solar/Wind Harmer
0.945
253325AC1-069 GEN
Solar/Wind Harmer
0.911
25196808ZIMRHP
Adder
60.849
252507AC2-088 GEN
Solar/Wind Harmer
1.41
25196008MFTGT1
Adder
0.989
945681AF1-233 GEN
Solar/Wind Harmer
12.592
339216AC1-074 GEN
Solar/Wind Harmer
0.995
943111AE2-339 GEN
Solar/Wind Harmer
0.487
3429421JKCT 10G
Adder
4.444
3429241JKCT 3G
Adder
6.131
247536S-71 GEN
Solar/Wind Harmer
1.929
942081AE2-220 GEN
Solar/Wind Harmer
2.754
270239V3-007_GEN1
Solar/Wind Harmer
0.741
25326109MON D
50/50
2.081
253370AE2-315 SEC1
50/50
3.063
25322209TAIT E
50/50
14.612
25322209TAIT E
50/50
14.284
270518AE2-148 GEN
Solar/Wind Harmer
59.189
253394AE2-221_GEN
Solar/Wind Harmer
6.237
253398AE2-221_GEN2
Solar/Wind Harmer
6.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.718
25183208HLCRTG
Solar/Wind Harmer
5.477
252519AF1-045_GEN
Solar/Wind Harmer
5.444
252516AE2-318_GEN
Solar/Wind Harmer
4.153
25194408D.CRK1
Adder
6.733
25194508D.CRK3
Adder
1.259
252509AD1-136 GEN
Solar/Wind Harmer
0.201
962581AG1-107 GEN
Solar/Wind Harmer
3.862
961491AF2-440 GEN
Solar/Wind Harmer
1.605
25326509SID D
Adder
0.989
270186AC1-089 GEN
Solar/Wind Harmer
4.124
253378AE2-206_GEN
Solar/Wind Harmer
2.363
276820AF1-078_GEN
Solar/Wind Harmer
1.05
24728805RICHG1
Adder
2.364
24728905RICHG2
Adder
2.364
339221AD2-048_GEN
Solar/Wind Harmer
0.902
972043AH1-570 GEN
Solar/Wind Harmer
1.446
972045AH1-571 GEN
Solar/Wind Harmer
1.157
971125AH1-004 GEN
Solar/Wind Harmer
2.233
970107AG2-081 GEN
Solar/Wind Harmer
1.674
970235AG2-159 GEN
Solar/Wind Harmer
2.193
970235AG2-159 GEN
Solar/Wind Harmer
1.339
970883AG2-550 GEN
Solar/Wind Harmer
5.204
970885AG2-551 GEN
Solar/Wind Harmer
1.21
942891AE2-308 GEN
Solar/Wind Harmer
5.047
960161AF2-307 GEN
Solar/Wind Harmer
3.216
270383AD1-128 GEN
Solar/Wind Harmer
2.95
247621Y3-024
Adder
0.109
24379505HDWTR1G C
Solar/Wind Harmer
3.406
270209AC1-174_GEN
Solar/Wind Harmer
2.404
926881AC1-175 GEN
Solar/Wind Harmer
2.404
946101AF1-275 GEN
Solar/Wind Helper
0.84
253372AE2-315 SEC3
50/50
2.897
253372AE2-315 SEC3
50/50
2.897
25322309TAIT W
50/50
0.726
963581AG1-207 GEN
50/50
13.168
25306009OHH W.
50/50
4.055
253349AC2-067 GEN
Solar/Wind Harmer
6.074
253400AC2-068 GEN
Solar/Wind Harmer
2.443
241972AD1-140 GEN
Solar/Wind Harmer
5.052
252524AE2-267 GEN
Solar/Wind Harmer
1.434
25196408WSDLE3
Adder
8.021
25196308WSDLE2
Adder
7.952
25196208WSDLE1
Adder
7.932
25196708WSDLE6
Adder
7.912
25196508WSDLE4
Adder
7.712
944031AF1-071 GEN
Solar/Wind Harmer
0.747
25196108MFTGT2
Adder
1.09
25196108MFTGT2
Adder
1.012
270367AC2-061_GEN
Solar/Wind Harmer
2.241
972163AH1-664 GEN
Solar/Wind Harmer
6.594
972165AH1-665 GEN
Solar/Wind Harmer
5.275
339243AC2-075 GEN1
Solar/Wind Harmer
0.269
971673AH1-337 GEN
Solar/Wind Harmer
2.698
971029AG2-637 GEN
Solar/Wind Harmer
8.535
270543AE2-219 C
Solar/Wind Harmer
2.665
3429211JKCT 2G
Adder
6.051
270340AC2-060 GEN
Solar/Wind Harmer
1.549
339211AE2-254 GEN
Solar/Wind Harmer
0.654
270240V3-007_GEN2
Solar/Wind Harmer
2.665
945631AF1-228 GEN
Solar/Wind Helper
5.197
270520AE2-214 GEN
Solar/Wind Helper
6.706
270054AF2-122 C O1
Solar/Wind Helper
0.903
253370AE2-315 SEC1
50/50
3.063
253371AE2-315 SEC2
50/50
2.897
25322309TAIT W
50/50
0.717
25322209TAIT E
50/50
0.709
253303V4-073 C
Solar/Wind Harmer
0.167
253406AD2-031_GEN
Solar/Wind Harmer
1.513
253316AC1-085 GEN3
Solar/Wind Harmer
9.718
253433AC1-085 GEN1
Solar/Wind Harmer
6.169
946181AF1-283 GEN
Solar/Wind Harmer
15.082
25196608WSDLE5
Adder
7.792
25194608D.CRK4
Adder
1.464
252510AF1-249 C
Solar/Wind Harmer
0.37
253338AC1-165 GEN
Solar/Wind Harmer
0.945
253333AC1-068 GEN
Solar/Wind Harmer
0.911
270222AC2-111 GEN
Solar/Wind Harmer
6.061
958171AF2-111 GEN
Solar/Wind Harmer
17.839
25196008MFTGT1
Adder
0.958
972167AH1-666 GEN
Solar/Wind Harmer
5.365
253415AE1-040 GEN
Solar/Wind Harmer
0.715
3429391JKCT 9G
Adder
4.444
970093AG2-073 GEN
Solar/Wind Harmer
4.816
270356AE2-297 GEN
Solar/Wind Harmer
2.192
966571AG1-526 GEN
Solar/Wind Harmer
10.057
270437AC2-090 C
Solar/Wind Harmer
2.405
960801AF2-371 GEN
Solar/Wind Helper
0.86
964871AG1-351 GEN
Solar/Wind Helper
0.594
241955AC1-078 GEN
Solar/Wind Helper
1.661
270273AD2-016 GEN
Solar/Wind Helper
1.449
CBM West 1LTFEXP_CBM-W1->PJM
CBM
20.556
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.951
MECLTFEXP_MEC->PJM
CLTF
3.265
SIGELTFEXP_SIGE->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.215
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.889
LAGNLTFEXP_LAGN->PJM
CLTF
3.755
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.596
TVALTFEXP_TVA->PJM
CLTF
1.949
NYPJM->LTFIMP_NY
CLTF
0.842
LGEELTFEXP_LGEE->PJM
CLTF
2.995
WECLTFEXP_WEC->PJM
CLTF
0.669

Details for 05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.27 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1278.4
MW Contribution:5.39
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
2.884
253371AE2-315 SEC2
50/50
2.728
25322309TAIT W
50/50
0.68
25322209TAIT E
50/50
0.68
25326309TAIT D
50/50
1.555
960071AF2-298 GEN
Solar/Wind Harmer
6.275
253432AC1-085 GEN2
Solar/Wind Harmer
0.241
946171AF1-282 GEN
Solar/Wind Harmer
9.018
25326109MON D
50/50
1.979
253370AE2-315 SEC1
50/50
2.884
25322209TAIT E
50/50
13.847
25322209TAIT E
50/50
13.536
270518AE2-148 GEN
Solar/Wind Harmer
59.988
253394AE2-221_GEN
Solar/Wind Harmer
5.279
253398AE2-221_GEN2
Solar/Wind Harmer
5.279
253317AC1-085 GEN4
Solar/Wind Harmer
7.554
25194408D.CRK1
Adder
6.039
25194508D.CRK3
Adder
1.129
252519AF1-045_GEN
Solar/Wind Harmer
4.592
252516AE2-318_GEN
Solar/Wind Harmer
3.503
25183208HLCRTG
Solar/Wind Harmer
4.277
25326509SID D
Adder
0.928
962581AG1-107 GEN
Solar/Wind Harmer
3.319
961491AF2-440 GEN
Solar/Wind Harmer
1.379
252509AD1-136 GEN
Solar/Wind Harmer
0.161
24728805RICHG1
Adder
2.319
24728905RICHG2
Adder
2.319
253378AE2-206_GEN
Solar/Wind Harmer
2.189
276820AF1-078_GEN
Solar/Wind Harmer
0.972
270186AC1-089 GEN
Solar/Wind Harmer
3.371
970883AG2-550 GEN
Solar/Wind Harmer
5.386
970885AG2-551 GEN
Solar/Wind Harmer
1.253
253372AE2-315 SEC3
50/50
2.728
253372AE2-315 SEC3
50/50
2.728
25322309TAIT W
50/50
0.688
963581AG1-207 GEN
50/50
12.502
25306009OHH W.
50/50
3.831
253349AC2-067 GEN
Solar/Wind Harmer
5.763
253400AC2-068 GEN
Solar/Wind Harmer
2.317
241972AD1-140 GEN
Solar/Wind Harmer
4.783
252524AE2-267 GEN
Solar/Wind Harmer
1.293
25196408WSDLE3
Adder
7.231
25196308WSDLE2
Adder
7.168
25196208WSDLE1
Adder
7.15
25196708WSDLE6
Adder
7.132
25196508WSDLE4
Adder
6.952
944031AF1-071 GEN
Solar/Wind Harmer
0.715
25196108MFTGT2
Adder
0.985
25196108MFTGT2
Adder
0.915
270367AC2-061_GEN
Solar/Wind Harmer
1.888
971673AH1-337 GEN
Solar/Wind Harmer
2.725
971029AG2-637 GEN
Solar/Wind Harmer
8.67
270543AE2-219 C
Solar/Wind Harmer
2.758
270240V3-007_GEN2
Solar/Wind Harmer
2.848
972163AH1-664 GEN
Solar/Wind Harmer
4.602
972165AH1-665 GEN
Solar/Wind Harmer
3.682
961761AG1-017 GEN
Solar/Wind Harmer
0.196
339243AC2-075 GEN1
Solar/Wind Harmer
0.205
945631AF1-228 GEN
Solar/Wind Helper
4.964
270520AE2-214 GEN
Solar/Wind Helper
6.217
270054AF2-122 C O1
Solar/Wind Helper
0.923
253370AE2-315 SEC1
50/50
2.884
253371AE2-315 SEC2
50/50
2.728
25322309TAIT W
50/50
0.68
25322209TAIT E
50/50
0.672
253303V4-073 C
Solar/Wind Harmer
0.157
253406AD2-031_GEN
Solar/Wind Harmer
1.258
253316AC1-085 GEN3
Solar/Wind Harmer
7.554
253433AC1-085 GEN1
Solar/Wind Harmer
4.795
946181AF1-283 GEN
Solar/Wind Harmer
11.724
25196608WSDLE5
Adder
7.024
25194608D.CRK4
Adder
1.313
252510AF1-249 C
Solar/Wind Harmer
0.33
270222AC2-111 GEN
Solar/Wind Harmer
5.802
25196008MFTGT1
Adder
0.866
270356AE2-297 GEN
Solar/Wind Harmer
2.238
958171AF2-111 GEN
Solar/Wind Harmer
12.086
972167AH1-666 GEN
Solar/Wind Harmer
3.72
270437AC2-090 C
Solar/Wind Harmer
2.57
962031AG1-047 GEN
Solar/Wind Harmer
1.383
957741AF2-068 GEN
Solar/Wind Harmer
6.862
946031AF1-268 GEN
Solar/Wind Harmer
3.685
960801AF2-371 GEN
Solar/Wind Helper
0.818
964871AG1-351 GEN
Solar/Wind Helper
0.565
241955AC1-078 GEN
Solar/Wind Helper
1.545
253338AC1-165 GEN
Solar/Wind Helper
0.732
253333AC1-068 GEN
Solar/Wind Helper
0.758
270273AD2-016 GEN
Solar/Wind Helper
1.443
270383AD1-128 GEN
Solar/Wind Harmer
3.09
247621Y3-024
Adder
0.116
970235AG2-159 GEN
Solar/Wind Harmer
1.899
970235AG2-159 GEN
Solar/Wind Harmer
1.159
24379505HDWTR1G C
Solar/Wind Harmer
3.64
270209AC1-174_GEN
Solar/Wind Harmer
2.569
926881AC1-175 GEN
Solar/Wind Harmer
2.569
270201AC2-176 GEN
Solar/Wind Harmer
2.352
964611AG1-324 GEN
Solar/Wind Harmer
0.536
964611AG1-324 GEN
Solar/Wind Harmer
0.238
339221AD2-048_GEN
Solar/Wind Harmer
0.69
972043AH1-570 GEN
Solar/Wind Harmer
1.097
972045AH1-571 GEN
Solar/Wind Harmer
0.877
970825AG2-519 GEN
Solar/Wind Harmer
4.567
946101AF1-275 GEN
Solar/Wind Helper
0.779
270471AD2-092_GEN
Solar/Wind Helper
0.672
25194608D.CRK4
Adder
1.313
25196808ZIMRHP
Adder
49.159
25196008MFTGT1
Adder
0.894
252507AC2-088 GEN
Solar/Wind Harmer
1.13
247536S-71 GEN
Solar/Wind Harmer
2.036
945681AF1-233 GEN
Solar/Wind Harmer
8.738
942081AE2-220 GEN
Solar/Wind Harmer
2.943
270239V3-007_GEN1
Solar/Wind Harmer
0.792
339216AC1-074 GEN
Solar/Wind Harmer
0.758
970825AG2-519 GEN
Solar/Wind Harmer
1.019
253343AC1-166 GEN
Solar/Wind Helper
0.732
253325AC1-069 GEN
Solar/Wind Helper
0.758
270349AD2-093_GEN
Solar/Wind Helper
0.672
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.088
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.916
MECLTFEXP_MEC->PJM
CLTF
4.431
SIGELTFEXP_SIGE->PJM
CLTF
0.185
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
34.43
LAGNLTFEXP_LAGN->PJM
CLTF
4.125
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.506
TVALTFEXP_TVA->PJM
CLTF
2.012
NYPJM->LTFIMP_NY
CLTF
0.948
LGEELTFEXP_LGEE->PJM
CLTF
2.761
WECLTFEXP_WEC->PJM
CLTF
1.025
AG2-052LTFEXP_AG2-052->PJM
LTF
0.065
AH1-155LTFEXP_AH1-155->PJM
LTF
0.098

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P4_1403_MIAMI FORT_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1403_MIAMI FORT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:114.86 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:204.45
MW Contribution:6.87
Bus #Bus NameTypeMW Contribution
944031AF1-071 GEN
Solar/Wind Harmer
1.906
971673AH1-337 GEN
Solar/Wind Harmer
4.09
971029AG2-637 GEN
Solar/Wind Harmer
12.541
270543AE2-219 C
Solar/Wind Harmer
3.518
24728805RICHG1
50/50
4.495
24728905RICHG2
50/50
4.495
970883AG2-550 GEN
Solar/Wind Harmer
6.871
970885AG2-551 GEN
Solar/Wind Harmer
1.598
270383AD1-128 GEN
Solar/Wind Harmer
4.041
247621Y3-024
Adder
0.119
270222AC2-111 GEN
Solar/Wind Harmer
15.462
252510AF1-249 C
Solar/Wind Helper
0.213
247536S-71 GEN
Solar/Wind Harmer
2.229
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.026
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.444
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.183
MECLTFEXP_MEC->PJM
CLTF
0.637
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.673
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.031
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.064
LAGNLTFEXP_LAGN->PJM
CLTF
0.282
TVALTFEXP_TVA->PJM
CLTF
0.079
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.052
WECLTFEXP_WEC->PJM
CLTF
0.171
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.046

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o AEP_P4_#2812_05TANNER 345_T2_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2812_05TANNER 345_T2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.71 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:193.5
MW Contribution:6.88
Bus #Bus NameTypeMW Contribution
944031AF1-071 GEN
Solar/Wind Harmer
1.906
971673AH1-337 GEN
Solar/Wind Harmer
4.093
971029AG2-637 GEN
Solar/Wind Harmer
12.55
270543AE2-219 C
Solar/Wind Harmer
3.521
270222AC2-111 GEN
Solar/Wind Harmer
15.467
252510AF1-249 C
Solar/Wind Helper
0.213
247536S-71 GEN
Solar/Wind Harmer
2.231
24728805RICHG1
50/50
4.497
24728905RICHG2
50/50
4.497
970883AG2-550 GEN
Solar/Wind Harmer
6.876
970885AG2-551 GEN
Solar/Wind Harmer
1.599
270383AD1-128 GEN
Solar/Wind Harmer
4.044
247621Y3-024
Adder
0.119
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.529
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.206
MECLTFEXP_MEC->PJM
CLTF
0.647
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.752
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.027
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.052
LAGNLTFEXP_LAGN->PJM
CLTF
0.294
TVALTFEXP_TVA->PJM
CLTF
0.085
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.173
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.042

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P4_1401_MIAMI FORT_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1401_MIAMI FORT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.59 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:193.29
MW Contribution:6.88
Bus #Bus NameTypeMW Contribution
24728805RICHG1
50/50
4.497
24728905RICHG2
50/50
4.497
970883AG2-550 GEN
Solar/Wind Harmer
6.876
970885AG2-551 GEN
Solar/Wind Harmer
1.599
270383AD1-128 GEN
Solar/Wind Harmer
4.044
247621Y3-024
Adder
0.119
270222AC2-111 GEN
Solar/Wind Harmer
15.466
252510AF1-249 C
Solar/Wind Helper
0.213
944031AF1-071 GEN
Solar/Wind Harmer
1.906
971673AH1-337 GEN
Solar/Wind Harmer
4.093
971029AG2-637 GEN
Solar/Wind Harmer
12.55
270543AE2-219 C
Solar/Wind Harmer
3.521
247536S-71 GEN
Solar/Wind Harmer
2.231
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.024
CBM West 1LTFEXP_CBM-W1->PJM
CBM
5.54
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.212
MECLTFEXP_MEC->PJM
CLTF
0.649
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.772
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.025
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.046
LAGNLTFEXP_LAGN->PJM
CLTF
0.296
TVALTFEXP_TVA->PJM
CLTF
0.086
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.173
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.041

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.05 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:186.99
MW Contribution:6.74
Bus #Bus NameTypeMW Contribution
944031AF1-071 GEN
Solar/Wind Harmer
1.889
971673AH1-337 GEN
Solar/Wind Harmer
4.031
971029AG2-637 GEN
Solar/Wind Harmer
12.346
270543AE2-219 C
Solar/Wind Harmer
3.449
270222AC2-111 GEN
Solar/Wind Harmer
15.325
252510AF1-249 C
Solar/Wind Helper
0.216
24728805RICHG1
50/50
4.446
24728905RICHG2
50/50
4.446
970883AG2-550 GEN
Solar/Wind Harmer
6.736
970885AG2-551 GEN
Solar/Wind Harmer
1.567
270383AD1-128 GEN
Solar/Wind Harmer
3.921
247621Y3-024
Adder
0.115
247536S-71 GEN
Solar/Wind Harmer
2.173
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.03
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.636
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.082
MECLTFEXP_MEC->PJM
CLTF
0.527
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.88
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.064
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.159
LAGNLTFEXP_LAGN->PJM
CLTF
0.204
TVALTFEXP_TVA->PJM
CLTF
0.048
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.048
WECLTFEXP_WEC->PJM
CLTF
0.144
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.051

Details for 05COLLEGE C-08COLINV 138.0 kV Ckt 1 line l/o DEOK_P4_1301_TERMINAL_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1301_TERMINAL_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.92 %
Rating:178.0 MVA
Rating Type:B
MVA to Mitigate:183.2
MW Contribution:6.79
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
2.193
24728805RICHG1
50/50
4.473
24728905RICHG2
50/50
4.473
970883AG2-550 GEN
Solar/Wind Harmer
6.792
970885AG2-551 GEN
Solar/Wind Harmer
1.58
270383AD1-128 GEN
Solar/Wind Harmer
3.955
247621Y3-024
Adder
0.117
270222AC2-111 GEN
Solar/Wind Harmer
15.414
252510AF1-249 C
Solar/Wind Helper
0.199
944031AF1-071 GEN
Solar/Wind Harmer
1.9
971673AH1-337 GEN
Solar/Wind Harmer
4.061
971029AG2-637 GEN
Solar/Wind Harmer
12.441
270543AE2-219 C
Solar/Wind Harmer
3.478
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.031
CBM West 1LTFEXP_CBM-W1->PJM
CBM
4.783
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.059
MECLTFEXP_MEC->PJM
CLTF
0.539
SIGELTFEXP_SIGE->PJM
CLTF
0.012
CBM West 2LTFEXP_CBM-W2->PJM
CBM
2.914
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.07
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.181
LAGNLTFEXP_LAGN->PJM
CLTF
0.203
TVALTFEXP_TVA->PJM
CLTF
0.045
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.046
WECLTFEXP_WEC->PJM
CLTF
0.148
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.052

Details for 05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HANGRCK_RJ-05HANG R 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.88 %
Rating:4571.0 MVA
Rating Type:B
MVA to Mitigate:4885.66
MW Contribution:6.87
Bus #Bus NameTypeMW Contribution
942601AE2-276 GEN
50/50
10.552
970239AG2-162 GEN
Solar/Wind Harmer
4.479
270444AC2-157 GEN1
Solar/Wind Harmer
0.006
971587AH1-292 GEN
Solar/Wind Harmer
9.286
970321AG2-212 GEN
Solar/Wind Harmer
4.889
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
966841AG1-555 GEN
Solar/Wind Harmer
1.266
970241AG2-163 GEN
Solar/Wind Harmer
6.413
945391AF1-204 GEN
Solar/Wind Harmer
11.343
965681AG1-436 GEN
Solar/Wind Harmer
12.338
965791AG1-447 GEN
Solar/Wind Harmer
9.048
24344205RKG1
50/50
10.236
24344205RKG1
50/50
10.215
24344305RKG2
50/50
10.196
270393AB1-087 CT1
50/50
3.172
270394AB1-087 ST1
50/50
3.172
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.805
971611AH1-305 GEN
Solar/Wind Harmer
6.537
958391AF2-133 GEN
Solar/Wind Harmer
0.002
270536AF1-215 GEN2
Solar/Wind Harmer
0.013
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971347AH1-153 GEN
Solar/Wind Harmer
14.79
274775LINCOLN ;6U
Adder
11.903
274776LINCOLN ;7U
Adder
11.903
274777LINCOLN ;8U
Adder
11.903
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
10.288
941731AE2-173 GEN
Solar/Wind Harmer
8.165
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
970169AG2-114 GEN
Solar/Wind Harmer
9.776
972227AH1-698 GEN1
Adder
3.652
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
7.072
274807UNIV PK N;3U
Adder
7.056
274805UNIV PK N;1U
Adder
7.026
274811UNIV PK N;7U
Adder
7.01
960591AF2-350 GEN
Solar/Wind Harmer
9.764
276849AB2-070 GEN2
Solar/Wind Harmer
0.356
276848AB2-070 GEN3
Solar/Wind Harmer
0.354
972037AH1-567 GEN1
Adder
0.256
274827FISK ;RP
Adder
10.835
970833AG2-524 GEN
Solar/Wind Harmer
10.702
970833AG2-524 GEN
Solar/Wind Harmer
7.134
274731ELWOOD EC;2P
Adder
22.909
274733ELWOOD EC;3P
Adder
22.909
274735ELWOOD EC;4P
Adder
22.909
274728ELWOOD EC;5P
Adder
22.908
274687WILL CNTY;4U
Adder
38.91
274687WILL CNTY;4U
Adder
38.91
274675JOLIET 29;7U
Adder
42.703
274675JOLIET 29;7U
Adder
41.178
971769AH1-391 GEN
Solar/Wind Harmer
10.786
274746AC1-111 G10
Adder
7.736
274744AC1-111 GEN8
Adder
7.736
944221AF1-090 GEN
Solar/Wind Harmer
5.66
276868AE1-113 GEN
Solar/Wind Harmer
1.928
276882AE2-255 GEN
Solar/Wind Harmer
1.124
926823AC1-168 GEN
Solar/Wind Harmer
1.627
971177AH1-047 GEN
Solar/Wind Harmer
5.86
971675AH1-338 GEN
Solar/Wind Harmer
3.702
957751AF2-069 GEN
Solar/Wind Harmer
0.313
971771AH1-392 GEN
Solar/Wind Harmer
9.483
971411AH1-196 GEN
Solar/Wind Harmer
14.224
971171AH1-044 GEN
Solar/Wind Harmer
18.922
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.796
274823ROCKFORD ;21
Adder
26.341
276612AE2-035 GEN
Solar/Wind Harmer
0.003
971681AH1-341 GEN
Solar/Wind Harmer
15.111
961011AF2-392 GEN
Solar/Wind Harmer
5.479
971619AH1-309 GEN
Solar/Wind Harmer
4.175
270071AF1-092 GEN
Solar/Wind Harmer
17.687
946321AF1-296 GEN
Solar/Wind Harmer
5.141
270594AE1-207 GEN
Solar/Wind Harmer
10.19
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
17.277
971609AH1-304 GEN
Solar/Wind Harmer
1.338
965101AG1-375 GEN
Solar/Wind Harmer
8.167
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.229
270240V3-007_GEN2
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
10.035
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270543AE2-219 C
Solar/Wind Harmer
0.004
965041AG1-368 GEN
Solar/Wind Harmer
6.799
971029AG2-637 GEN
Solar/Wind Harmer
9.99
971673AH1-337 GEN
Solar/Wind Harmer
4.275
965051AG1-369 GEN
Solar/Wind Harmer
3.198
970455AG2-298 GEN
Solar/Wind Harmer
4.116
24344305RKG2
50/50
10.006
270406AB1-088 CT1
50/50
3.172
970243AG2-164 GEN
Solar/Wind Harmer
10.48
970519AG2-331 GEN
Solar/Wind Harmer
46.579
970699AG2-449 GEN
Solar/Wind Harmer
4.479
970513AG2-328 GEN
Solar/Wind Harmer
4.889
970517AG2-330 GEN
Solar/Wind Harmer
29.332
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
11.21
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
964401AG1-302 GEN
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
16.013
270535AF1-215 GEN1
Solar/Wind Harmer
0.013
970349AG2-230 GEN
Solar/Wind Harmer
14.79
274772LINCOLN ;3U
Adder
11.903
942111AE2-223 GEN
Solar/Wind Harmer
3.184
276897AD1-100 C
Solar/Wind Harmer
0.013
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247642Z2-115 C
Solar/Wind Harmer
0.004
274752CRETE EC ;2U
Adder
11.551
274753CRETE EC ;3U
Adder
11.551
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
29.335
959611AF2-252 GEN
Solar/Wind Harmer
3.259
274724RIVER EC ;11
Adder
24.801
972228AH1-698 GEN2
Adder
5.187
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.513
276806AD2-047 C O1
Solar/Wind Harmer
5.533
970941AG2-585 GEN
Solar/Wind Harmer
12.205
276668AB2-070 GEN1
Solar/Wind Harmer
0.356
970707AG2-453 GEN
Solar/Wind Harmer
31.865
274802UNIV PARK;5U
Adder
8.15
274800UNIV PARK;3U
Adder
8.146
972038AH1-567 GEN2
Adder
0.51
274826FISK ;BP
Adder
15.289
274729ELWOOD EC;1P
Adder
22.909
274730ELWOOD EC;6P
Adder
22.908
274734ELWOOD EC;8P
Adder
22.908
274736ELWOOD EC;9P
Adder
22.908
276893AG1-478 C
Solar/Wind Harmer
0.385
276621W2-048 GEN
Solar/Wind Harmer
0.49
276838X2-022 GEN2
Solar/Wind Harmer
0.547
274676JOLIET 29;8U
Adder
41.178
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
16.19
943591AF1-030 GEN
Solar/Wind Harmer
10.767
942481AE2-261 GEN
Solar/Wind Harmer
28.852
276805AD2-038 GEN
Solar/Wind Harmer
0.003
274682WAUKEGAN ;7U
Adder
24.679
276889AE2-281 GEN
Solar/Wind Harmer
0.001
970571AG2-364 GEN
Solar/Wind Harmer
19.097
274872LEEDK;1U
Solar/Wind Harmer
0.35
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.013
274855GSG-6 ;RU
Solar/Wind Harmer
0.348
274850MENDOTA H;RU
Solar/Wind Harmer
0.112
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.17
959091AF2-200 GEN
Solar/Wind Harmer
18.922
970289AG2-191 GEN
Solar/Wind Harmer
1.04
970291AG2-192 GEN
Solar/Wind Harmer
0.945
274878BISHOP HL;2U
Solar/Wind Harmer
0.317
972236AH1-702 GEN2
Adder
2.96
24642205MAYFLWER
Adder
0.856
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
276157O29GEN1
Solar/Wind Harmer
1.512
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.473
965931AG1-462 GEN
Solar/Wind Harmer
23.338
24441205WTRV SLR C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
5.542
970031AG2-029 GEN
Solar/Wind Harmer
5.595
944531AF1-118 GEN
Solar/Wind Harmer
37.201
958821AF2-173 GEN
Solar/Wind Harmer
11.202
270004AE1-209 GEN
Solar/Wind Harmer
1.734
946031AF1-268 GEN
Solar/Wind Harmer
7.423
270356AE2-297 GEN
Solar/Wind Harmer
0.01
270437AC2-090 C
Solar/Wind Harmer
0.003
959331AF2-224 GEN
Solar/Wind Harmer
5.219
965021AG1-366 GEN
Solar/Wind Harmer
2.485
971617AH1-308 GEN
Solar/Wind Harmer
6.14
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.942
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.041
274770LINCOLN ;1U
Adder
11.903
274771LINCOLN ;2U
Adder
11.903
960611AF2-352 GEN
Solar/Wind Harmer
3.259
274808UNIV PK N;4U
Adder
6.98
274888KELLY CRK;1U
Solar/Wind Harmer
0.573
274887GEN-1.85
Solar/Wind Harmer
0.257
276843GEN-1.7
Solar/Wind Harmer
0.316
958011AF2-095 GEN
Solar/Wind Harmer
14.061
972259AH1-714 GEN
Adder
26.685
274803UNIV PARK;6U
Adder
8.15
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274674JOLIET 9 ;6U
Adder
21.442
24441505OLIV SLR
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
14.489
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.307
276916AD2-100_GEN
Solar/Wind Harmer
20.263
276911AD2-131_GEN
Solar/Wind Harmer
1.335
971573AH1-285 GEN
Solar/Wind Harmer
1.794
958491AF2-143 GEN
Solar/Wind Harmer
14.439
270526AF1-158 GEN
Solar/Wind Harmer
0.012
274879MINONK ;1U
Solar/Wind Harmer
0.405
274696ROCKY RD ;4P
Adder
15.67
274695ROCKY RD ;2P
Adder
15.309
274693ROCKY RD ;1P
Adder
15.158
274697ROCKY RD ;3P
Adder
4.159
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274683WAUKEGAN ;8U
Adder
28.915
274683WAUKEGAN ;8U
Adder
24.374
962691AG1-118 GEN
Solar/Wind Harmer
28.676
970921AG2-575 GEN
Solar/Wind Harmer
9.546
970921AG2-575 GEN
Solar/Wind Harmer
3.182
942991AE2-321 GEN
Solar/Wind Harmer
10.614
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.373
276646AC1-214 GEN2
Solar/Wind Harmer
0.373
971333AH1-146 GEN
Solar/Wind Harmer
18.962
971335AH1-147 GEN
Solar/Wind Harmer
18.962
971341AH1-150 GEN
Solar/Wind Harmer
18.922
971343AH1-151 GEN
Solar/Wind Harmer
18.922
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274856ECOGROVE ;U1
Solar/Wind Harmer
0.222
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
5.315
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
12.51
274765LEE CO EC;6U
Adder
9.439
276741O09 GEN1
Solar/Wind Harmer
0.333
276708O09 GEN2
Solar/Wind Harmer
0.333
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
18.41
961051AF2-396 GEN
Solar/Wind Harmer
12.273
971613AH1-306 GEN
Solar/Wind Harmer
4.367
944541AF1-119 GEN
Solar/Wind Harmer
0.549
960971AF2-388 GEN
Solar/Wind Harmer
4.806
270599AE1-208 GEN
Solar/Wind Harmer
7.51
270031AE2-169
Solar/Wind Harmer
4.506
960441AF2-335 GEN
Solar/Wind Harmer
8.073
970825AG2-519 GEN
Solar/Wind Harmer
8.886
942221AE2-234 GEN
Solar/Wind Harmer
0.04
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
7.456
970627AG2-408 GEN
Solar/Wind Harmer
2.237
270383AD1-128 GEN
Solar/Wind Harmer
0.005
964611AG1-324 GEN
Solar/Wind Harmer
0.555
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970883AG2-550 GEN
Solar/Wind Harmer
6.873
970885AG2-551 GEN
Solar/Wind Harmer
2.291
964571AG1-320 GEN
Solar/Wind Harmer
6.134
970235AG2-159 GEN
Solar/Wind Harmer
3.809
970235AG2-159 GEN
Solar/Wind Harmer
2.185
970653AG2-424 GEN
Solar/Wind Harmer
2.907
970653AG2-424 GEN
Solar/Wind Harmer
1.506
970091AG2-072 GEN
50/50
198.882
270407AB1-088 ST1
50/50
3.172
970333AG2-219 GEN
Solar/Wind Harmer
12.809
270445AC2-157 GEN2
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
4.889
24791305MDL-5G
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
963741AG1-226 GEN
Solar/Wind Harmer
26.02
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
13.725
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
13.986
958381AF2-132 GEN
Solar/Wind Harmer
0.002
270055AF2-134 C O1
Solar/Wind Harmer
0.008
970373AG2-245 GEN
Solar/Wind Harmer
21.781
274773LINCOLN ;4U
Adder
11.903
274774LINCOLN ;5U
Adder
11.903
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
13.718
939401AE1-172 GEN
Solar/Wind Harmer
7.325
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274751CRETE EC ;1U
Adder
11.551
274754CRETE EC ;4U
Adder
11.551
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
8.079
274723RIVER EC ;12
Adder
25.097
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
7.01
276776AD2-060 GEN
Solar/Wind Harmer
1.019
274801UNIV PARK;4U
Adder
8.146
963831AG1-236 GEN
Solar/Wind Harmer
3.802
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
22.908
276615X2-022 GEN
Solar/Wind Harmer
0.102
274674JOLIET 9 ;6U
Adder
21.442
274676JOLIET 29;8U
Adder
42.703
276691AA1-018 GEN1
Solar/Wind Harmer
1.17
274745AC1-111 GEN9
Adder
7.736
965911AG1-460 GEN
Solar/Wind Harmer
1.93
276901AD2-066 C O1
Solar/Wind Harmer
0.01
971997AH1-543 GEN
Solar/Wind Harmer
5.053
274682WAUKEGAN ;7U
Adder
24.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274828WAUKEGAN ;BP
Adder
15.157
970569AG2-363 GEN
Solar/Wind Harmer
28.645
962781AG1-127 GEN
Solar/Wind Harmer
9.085
274872LEEDK;1U
Solar/Wind Harmer
0.006
276861AD2-134 GEN
Solar/Wind Harmer
0.17
957471AF2-041 GEN
Solar/Wind Harmer
28.383
959081AF2-199 GEN
Solar/Wind Harmer
9.461
971067AG2-660 GEN
Solar/Wind Harmer
3.154
970291AG2-192 GEN
Solar/Wind Harmer
1.229
274877BISHOP HL;1U
Solar/Wind Harmer
0.317
274822ROCKFORD ;11
Adder
26.534
972235AH1-702 GEN1
Adder
3.404
970819AG2-516 GEN
Solar/Wind Harmer
11.285
971475AH1-234 GEN
Solar/Wind Harmer
4.553
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
276158O29GEN2
Solar/Wind Harmer
0.001
270505AE1-170 C O1
Solar/Wind Harmer
9.741
945111AF1-176 GEN
Solar/Wind Harmer
16.452
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.8
270032AE2-172
Solar/Wind Harmer
6.065
276903AD2-071 C
Solar/Wind Harmer
10.136
270063AE2-323 C
Solar/Wind Harmer
0.007
965651AG1-433 GEN
Solar/Wind Harmer
2.403
958861AF2-177 GEN
Solar/Wind Harmer
3.539
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.846
270005AE1-210 C O1
Solar/Wind Harmer
1.734
965031AG1-367 GEN
Solar/Wind Harmer
8.001
970773AG2-487 GEN
Solar/Wind Harmer
1.37
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.665
965011AG1-365 GEN
Solar/Wind Harmer
7.456
247536S-71 GEN
Solar/Wind Harmer
0.284
944231AF1-091 GEN
Solar/Wind Harmer
1.864
971565AH1-281 GEN
Solar/Wind Harmer
1.306
247521TR3_G114
Solar/Wind Harmer
0.234
270246TR4_N_V150
Solar/Wind Harmer
0.041
24695305TIMB G C
Solar/Wind Harmer
0.002
944201AF1-088_MTX
50/50
211.042
957141AF2-008_MTX
50/50
105.521
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
1.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
162.55
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.289
MECLTFEXP_MEC->PJM
CLTF
20.301
SIGELTFEXP_SIGE->PJM
CLTF
0.641
CBM West 2LTFEXP_CBM-W2->PJM
CBM
121.55
LAGNLTFEXP_LAGN->PJM
CLTF
11.815
TVALTFEXP_TVA->PJM
CLTF
4.631
NYPJM->LTFIMP_NY
CLTF
2.584
LGEELTFEXP_LGEE->PJM
CLTF
8.153
WECLTFEXP_WEC->PJM
CLTF
5.142
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.945
AG2-052LTFEXP_AG2-052->PJM
LTF
0.335
AH1-155LTFEXP_AH1-155->PJM
LTF
0.503

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.24 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:314.27
MW Contribution:65.61
Bus #Bus NameTypeMW Contribution
970883AG2-550 GEN
Solar/Wind Harmer
65.613
970885AG2-551 GEN
Solar/Wind Harmer
15.259
247536S-71 GEN
Solar/Wind Harmer
26.562
971673AH1-337 GEN
Solar/Wind Harmer
31.433
971029AG2-637 GEN
Solar/Wind Harmer
100.458
270543AE2-219 C
Solar/Wind Harmer
33.597
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.734
MECLTFEXP_MEC->PJM
CLTF
0.088
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.355
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.024
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.067
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.025
WECLTFEXP_WEC->PJM
CLTF
0.026
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#10528_05BLUFFP 138_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10528_05BLUFFP 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.65 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.96
MW Contribution:65.62
Bus #Bus NameTypeMW Contribution
971673AH1-337 GEN
Solar/Wind Harmer
31.437
971029AG2-637 GEN
Solar/Wind Harmer
100.471
270543AE2-219 C
Solar/Wind Harmer
33.602
970883AG2-550 GEN
Solar/Wind Harmer
65.622
970885AG2-551 GEN
Solar/Wind Harmer
15.261
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.855
MECLTFEXP_MEC->PJM
CLTF
0.102
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.467
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.05
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.003
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.59 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.81
MW Contribution:33.24
Bus #Bus NameTypeMW Contribution
971673AH1-337 GEN
Solar/Wind Harmer
20.231
971029AG2-637 GEN
Solar/Wind Harmer
61.289
270543AE2-219 C
Solar/Wind Harmer
17.022
961761AG1-017 GEN
Solar/Wind Harmer
0.787
270024AE2-089 GEN
Solar/Wind Harmer
6.484
963791AG1-232 GEN
Solar/Wind Harmer
9.313
962031AG1-047 GEN
Solar/Wind Harmer
5.558
957741AF2-068 GEN
Solar/Wind Harmer
27.581
946031AF1-268 GEN
Solar/Wind Harmer
15.261
971617AH1-308 GEN
Solar/Wind Harmer
8.031
247536S-71 GEN
Solar/Wind Harmer
10.869
247621Y3-024
50/50
0.608
970883AG2-550 GEN
Solar/Wind Harmer
33.242
970885AG2-551 GEN
Solar/Wind Harmer
7.731
270201AC2-176 GEN
Solar/Wind Harmer
9.453
964611AG1-324 GEN
Solar/Wind Harmer
2.168
964611AG1-324 GEN
Solar/Wind Harmer
0.962
942221AE2-234 GEN
Solar/Wind Harmer
0.412
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.605
MECLTFEXP_MEC->PJM
CLTF
0.18
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.177
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.535
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.028
WECLTFEXP_WEC->PJM
CLTF
0.071
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.063

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#11242_05BLUFFP 138_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11242_05BLUFFP 138_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.59 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.8
MW Contribution:65.62
Bus #Bus NameTypeMW Contribution
970883AG2-550 GEN
Solar/Wind Harmer
65.621
970885AG2-551 GEN
Solar/Wind Harmer
15.261
971673AH1-337 GEN
Solar/Wind Harmer
31.437
971029AG2-637 GEN
Solar/Wind Harmer
100.471
270543AE2-219 C
Solar/Wind Harmer
33.602
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.856
MECLTFEXP_MEC->PJM
CLTF
0.102
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.468
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.05
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.003
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.74
MW Contribution:33.24
Bus #Bus NameTypeMW Contribution
247621Y3-024
50/50
0.608
970883AG2-550 GEN
Solar/Wind Harmer
33.239
970885AG2-551 GEN
Solar/Wind Harmer
7.73
270201AC2-176 GEN
Solar/Wind Harmer
9.452
964611AG1-324 GEN
Solar/Wind Harmer
2.168
964611AG1-324 GEN
Solar/Wind Harmer
0.962
942221AE2-234 GEN
Solar/Wind Harmer
0.412
962031AG1-047 GEN
Solar/Wind Harmer
5.557
957741AF2-068 GEN
Solar/Wind Harmer
27.578
946031AF1-268 GEN
Solar/Wind Harmer
15.26
971617AH1-308 GEN
Solar/Wind Harmer
8.03
247536S-71 GEN
Solar/Wind Harmer
10.868
971673AH1-337 GEN
Solar/Wind Harmer
20.23
971029AG2-637 GEN
Solar/Wind Harmer
61.285
270543AE2-219 C
Solar/Wind Harmer
17.02
961761AG1-017 GEN
Solar/Wind Harmer
0.787
270024AE2-089 GEN
Solar/Wind Harmer
6.483
963791AG1-232 GEN
Solar/Wind Harmer
9.312
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.606
MECLTFEXP_MEC->PJM
CLTF
0.18
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.176
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.533
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.028
WECLTFEXP_WEC->PJM
CLTF
0.071
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.063

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9728_05MALIS 138_L1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9728_05MALIS 138_L1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.65 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1756.35
MW Contribution:4.57
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.813
942871AE2-306 GEN
Solar/Wind Harmer
0.907
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.566
942051AE2-217 GEN
Solar/Wind Harmer
13.984
970065AG2-057 GEN
Solar/Wind Harmer
0.767
970605AG2-385 GEN
Solar/Wind Harmer
3.836
241955AC1-078 GEN
Solar/Wind Harmer
5.001
970153AG2-106 GEN
Solar/Wind Harmer
9.124
270491AE1-102 GEN2
Solar/Wind Harmer
0.782
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.663
270247TR4_N_V136
Solar/Wind Harmer
0.472
270258AD1-119 GEN
Solar/Wind Harmer
1.498
959331AF2-224 GEN
Solar/Wind Harmer
5.315
965021AG1-366 GEN
Solar/Wind Harmer
1.236
270044AE2-322 C
Solar/Wind Harmer
0.691
270404AC1-167 GEN
Solar/Wind Harmer
0.576
270588AE1-091_GEN
Solar/Wind Harmer
5.503
270043AE2-236 GEN
Solar/Wind Harmer
2.714
253338AC1-165 GEN
Solar/Wind Harmer
0.526
253333AC1-068 GEN
Solar/Wind Harmer
0.507
970031AG2-029 GEN
Solar/Wind Harmer
14.514
270036AE2-216 BAT
50/50
5.972
270284AF1-227 GEN1
Solar/Wind Harmer
6.854
270286AF1-227 GEN2
Solar/Wind Harmer
2.536
270287AF1-227 GEN3
Solar/Wind Harmer
2.536
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.822
270317AD1-130_GEN
Solar/Wind Harmer
2.998
270520AE2-214 GEN
Solar/Wind Harmer
5.402
970179AG2-119 GEN
Solar/Wind Harmer
6.794
962771AG1-126 GEN
Solar/Wind Harmer
20.924
957201AF2-014 GEN
Solar/Wind Harmer
2.73
270435AC2-044 GEN
Solar/Wind Harmer
1.204
241972AD1-140 GEN
Solar/Wind Harmer
2.573
247607V1-011 GEN
Solar/Wind Harmer
2.229
965051AG1-369 GEN
Solar/Wind Harmer
2.769
270297AD1-101 GEN
Solar/Wind Harmer
1.544
965041AG1-368 GEN
Solar/Wind Harmer
5.379
945631AF1-228 GEN
Solar/Wind Harmer
2.515
270156DARBY CT1
Adder
4.69
270157DARBY CT2
Adder
4.678
270158DARBY CT3
Adder
4.603
943861AF1-054 GEN
Solar/Wind Harmer
1.939
943851AF1-053 GEN
Solar/Wind Harmer
0.937
963791AG1-232 GEN
Solar/Wind Harmer
6.797
270071AF1-092 GEN
Solar/Wind Harmer
7.236
270024AE2-089 GEN
Solar/Wind Harmer
2.257
24729505KEY G4
Adder
3.093
253349AC2-067 GEN
Solar/Wind Harmer
2.35
253400AC2-068 GEN
Solar/Wind Harmer
0.945
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.472
25306009OHH W.
Adder
1.34
253372AE2-315 SEC3
Adder
0.879
253372AE2-315 SEC3
Adder
0.879
965101AG1-375 GEN
Solar/Wind Harmer
4.631
971347AH1-153 GEN
Solar/Wind Harmer
6.938
971771AH1-392 GEN
Solar/Wind Harmer
4.117
270543AE2-219 C
Solar/Wind Harmer
2.339
945581AF1-223 GEN
Solar/Wind Harmer
2.071
944161AF1-084 GEN
Solar/Wind Harmer
1.002
971769AH1-391 GEN
Solar/Wind Harmer
4.525
971029AG2-637 GEN
Solar/Wind Harmer
6.782
971673AH1-337 GEN
Solar/Wind Harmer
2.073
253383AE2-342_GEN
Solar/Wind Harmer
0.399
960681AF2-359 GEN
Solar/Wind Harmer
1.7
971617AH1-308 GEN
Solar/Wind Harmer
2.796
944531AF1-118 GEN
Solar/Wind Harmer
16.819
270541AE2-072 C
Solar/Wind Harmer
2.163
962031AG1-047 GEN
Solar/Wind Harmer
1.413
957741AF2-068 GEN
Solar/Wind Harmer
7.01
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
970349AG2-230 GEN
Solar/Wind Harmer
6.938
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.591
24642205MAYFLWER
Adder
0.29
970513AG2-328 GEN
Solar/Wind Harmer
8.061
970517AG2-330 GEN
Solar/Wind Harmer
7.311
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.187
946031AF1-268 GEN
Solar/Wind Harmer
3.715
958821AF2-173 GEN
Solar/Wind Harmer
6.18
270004AE1-209 GEN
Solar/Wind Harmer
2.413
274752CRETE EC ;2U
Adder
3.613
274753CRETE EC ;3U
Adder
3.613
274772LINCOLN ;3U
Adder
3.698
274724RIVER EC ;11
Adder
7.758
274802UNIV PARK;5U
Adder
2.533
274826FISK ;BP
Adder
4.755
274800UNIV PARK;3U
Adder
2.53
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.606
274676JOLIET 29;8U
Adder
12.77
274729ELWOOD EC;1P
Adder
7.088
274730ELWOOD EC;6P
Adder
7.088
274734ELWOOD EC;8P
Adder
7.088
274736ELWOOD EC;9P
Adder
7.088
270349AD2-093_GEN
Solar/Wind Harmer
4.882
971995AH1-542 GEN
Solar/Wind Harmer
11.801
270223U2-072_GEN1
Solar/Wind Harmer
1.977
270578AF1-285 GEN2
Solar/Wind Harmer
1.209
270391AF1-285 GEN3
Solar/Wind Harmer
1.209
270462AD2-086
Solar/Wind Harmer
6.507
241813AF1-122_GEN
Solar/Wind Harmer
4.908
970593AG2-378 GEN
Solar/Wind Harmer
1.421
962761AG1-125 GEN
Solar/Wind Harmer
20.924
970149AG2-104 GEN
Solar/Wind Harmer
25.841
970155AG2-107 GEN
Solar/Wind Harmer
9.124
246936BC-WTG1
Solar/Wind Harmer
2.355
270489AE1-102 GEN1
Solar/Wind Harmer
0.782
965421AG1-410 GEN
Solar/Wind Harmer
17.855
247521TR3_G114
Solar/Wind Harmer
1.865
270246TR4_N_V150
Solar/Wind Harmer
0.472
24695305TIMB G C
Solar/Wind Harmer
3.018
965011AG1-365 GEN
Solar/Wind Harmer
5.315
270159DARBY CT4
Adder
4.615
944231AF1-091 GEN
Solar/Wind Harmer
1.845
253343AC1-166 GEN
Solar/Wind Harmer
0.526
253325AC1-069 GEN
Solar/Wind Harmer
0.507
960071AF2-298 GEN
Solar/Wind Harmer
2.404
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.058
965651AG1-433 GEN
Solar/Wind Harmer
2.549
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.929
253371AE2-315 SEC2
Adder
0.879
958861AF2-177 GEN
Solar/Wind Harmer
5.061
247536S-71 GEN
Solar/Wind Harmer
1.868
945111AF1-176 GEN
Solar/Wind Harmer
8.176
270505AE1-170 C O1
Solar/Wind Harmer
6.853
945371AF1-202 GEN
Solar/Wind Harmer
3.186
270449AD2-020 GEN
Solar/Wind Harmer
1.276
943021AE2-325 GEN
Solar/Wind Harmer
1.657
970245AG2-165 GEN
Solar/Wind Harmer
8.061
970825AG2-519 GEN
Solar/Wind Harmer
1.042
270005AE1-210 C O1
Solar/Wind Harmer
2.413
965031AG1-367 GEN
Solar/Wind Harmer
4.414
970373AG2-245 GEN
Solar/Wind Harmer
9.267
274751CRETE EC ;1U
Adder
3.613
274754CRETE EC ;4U
Adder
3.613
274773LINCOLN ;4U
Adder
3.698
274774LINCOLN ;5U
Adder
3.698
274723RIVER EC ;12
Adder
7.85
274812UNIV PK N;8U
Adder
2.185
274801UNIV PARK;4U
Adder
2.53
274676JOLIET 29;8U
Adder
13.243
274674JOLIET 9 ;6U
Adder
6.64
274732ELWOOD EC;7P
Adder
7.088
970115AG2-085 GEN
Solar/Wind Harmer
1.77
274775LINCOLN ;6U
Adder
3.698
274776LINCOLN ;7U
Adder
3.698
274777LINCOLN ;8U
Adder
3.698
274814UNIV PK N;0U
Adder
2.205
274807UNIV PK N;3U
Adder
2.2
274805UNIV PK N;1U
Adder
2.19
274811UNIV PK N;7U
Adder
2.185
972037AH1-567 GEN1
Adder
0.08
274827FISK ;RP
Adder
3.37
972227AH1-698 GEN1
Adder
1.131
274687WILL CNTY;4U
Adder
12.072
274687WILL CNTY;4U
Adder
12.072
274675JOLIET 29;7U
Adder
13.243
274675JOLIET 29;7U
Adder
12.77
274731ELWOOD EC;2P
Adder
7.088
274733ELWOOD EC;3P
Adder
7.088
274735ELWOOD EC;4P
Adder
7.088
274728ELWOOD EC;5P
Adder
7.088
270054AF2-122 C O1
Solar/Wind Helper
0.823
971549AH1-272 GEN
Solar/Wind Harmer
6.331
270466AD2-091
50/50
5.429
270471AD2-092_GEN
Solar/Wind Harmer
4.882
938701AE1-092 GEN
Solar/Wind Harmer
21.983
964601AG1-323 GEN
Solar/Wind Harmer
3.2
964601AG1-323 GEN
Solar/Wind Harmer
1.488
270224U2-072_GEN2
Solar/Wind Harmer
1.977
270227U2-072_GEN3
Solar/Wind Harmer
1.977
270228U2-072_GEN4
Solar/Wind Harmer
1.977
270231U2-072_GEN5
Solar/Wind Harmer
1.977
946101AF1-275 GEN
Solar/Wind Harmer
1.348
241960AC2-195 GEN
Solar/Wind Harmer
2.362
971201AH1-060 GEN
Solar/Wind Harmer
1.534
970077AG2-063 GEN
Solar/Wind Harmer
3.836
253378AE2-206_GEN
Solar/Wind Harmer
2.399
276820AF1-078_GEN
Solar/Wind Harmer
1.066
25326509SID D
Adder
0.833
246938BC-WTG3
Solar/Wind Harmer
2.396
246937BC-WTG2
Solar/Wind Harmer
2.355
270007AE1-245 C
Solar/Wind Harmer
3.344
942801AE2-298 GEN
Solar/Wind Harmer
0.852
970611AG2-400 GEN
Solar/Wind Harmer
5.315
270518AE2-148 GEN
Solar/Wind Harmer
6.282
942861AE2-305 GEN
Solar/Wind Harmer
3.928
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.68
25322209TAIT E
Adder
4.575
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.402
944541AF1-119 GEN
Solar/Wind Harmer
1.954
960971AF2-388 GEN
Solar/Wind Harmer
5.098
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.929
964611AG1-324 GEN
Solar/Wind Harmer
0.546
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.28
960981AF2-389 GEN
Solar/Wind Harmer
0.691
957891AF2-083 GEN
Solar/Wind Harmer
1.542
970883AG2-550 GEN
Solar/Wind Harmer
4.568
970885AG2-551 GEN
Solar/Wind Harmer
1.062
961051AF2-396 GEN
Solar/Wind Harmer
7.242
961051AF2-396 GEN
Solar/Wind Harmer
3.368
270526AF1-158 GEN
Solar/Wind Harmer
2.06
24441505OLIV SLR
Solar/Wind Harmer
0.061
970321AG2-212 GEN
Solar/Wind Harmer
8.061
270599AE1-208 GEN
Solar/Wind Harmer
3.679
270031AE2-169
Solar/Wind Harmer
3.679
965681AG1-436 GEN
Solar/Wind Harmer
5.624
965791AG1-447 GEN
Solar/Wind Harmer
2.877
970825AG2-519 GEN
Solar/Wind Harmer
4.672
960441AF2-335 GEN
Solar/Wind Harmer
4.424
274770LINCOLN ;1U
Adder
3.698
274771LINCOLN ;2U
Adder
3.698
274808UNIV PK N;4U
Adder
2.176
274803UNIV PARK;6U
Adder
2.533
972259AH1-714 GEN
Adder
8.267
274674JOLIET 9 ;6U
Adder
6.64
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.507
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.587
MECLTFEXP_MEC->PJM
CLTF
6.34
SIGELTFEXP_SIGE->PJM
CLTF
0.182
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.92
LAGNLTFEXP_LAGN->PJM
CLTF
5.126
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.351
TVALTFEXP_TVA->PJM
CLTF
2.378
NYPJM->LTFIMP_NY
CLTF
1.307
LGEELTFEXP_LGEE->PJM
CLTF
2.299
WECLTFEXP_WEC->PJM
CLTF
1.593
AG2-052LTFEXP_AG2-052->PJM
LTF
0.101
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9730_05MALIS 138_P1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9730_05MALIS 138_P1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.16 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1749.36
MW Contribution:4.56
Bus #Bus NameTypeMW Contribution
270475AD2-096_GEN
50/50
7.794
942871AE2-306 GEN
Solar/Wind Harmer
0.905
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.951
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.946
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.824
241955AC1-078 GEN
Solar/Wind Harmer
4.991
970153AG2-106 GEN
Solar/Wind Harmer
9.103
270491AE1-102 GEN2
Solar/Wind Harmer
0.781
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.66
270247TR4_N_V136
Solar/Wind Harmer
0.471
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.303
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.69
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.492
270043AE2-236 GEN
Solar/Wind Harmer
2.708
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.483
971617AH1-308 GEN
Solar/Wind Harmer
2.79
944531AF1-118 GEN
Solar/Wind Harmer
16.782
270541AE2-072 C
Solar/Wind Harmer
2.158
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
970349AG2-230 GEN
Solar/Wind Harmer
6.923
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.586
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.044
970517AG2-330 GEN
Solar/Wind Harmer
7.296
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.707
958821AF2-173 GEN
Solar/Wind Harmer
6.167
270004AE1-209 GEN
Solar/Wind Harmer
2.407
274752CRETE EC ;2U
Adder
3.605
274753CRETE EC ;3U
Adder
3.605
274772LINCOLN ;3U
Adder
3.69
274724RIVER EC ;11
Adder
7.742
274802UNIV PARK;5U
Adder
2.528
274826FISK ;BP
Adder
4.745
274800UNIV PARK;3U
Adder
2.525
270036AE2-216 BAT
50/50
5.958
270284AF1-227 GEN1
Solar/Wind Harmer
6.838
270286AF1-227 GEN2
Solar/Wind Harmer
2.53
270287AF1-227 GEN3
Solar/Wind Harmer
2.53
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.951
270302AB2-170 GEN
Solar/Wind Harmer
7.804
270317AD1-130_GEN
Solar/Wind Harmer
2.992
270520AE2-214 GEN
Solar/Wind Harmer
5.387
970179AG2-119 GEN
Solar/Wind Harmer
6.779
962771AG1-126 GEN
Solar/Wind Harmer
20.876
957201AF2-014 GEN
Solar/Wind Harmer
2.724
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.566
247607V1-011 GEN
Solar/Wind Harmer
2.224
965051AG1-369 GEN
Solar/Wind Harmer
2.763
270297AD1-101 GEN
Solar/Wind Harmer
1.54
965041AG1-368 GEN
Solar/Wind Harmer
5.367
945631AF1-228 GEN
Solar/Wind Harmer
2.511
270156DARBY CT1
Adder
4.681
270157DARBY CT2
Adder
4.67
270158DARBY CT3
Adder
4.595
963791AG1-232 GEN
Solar/Wind Harmer
6.783
943861AF1-054 GEN
Solar/Wind Harmer
1.926
943851AF1-053 GEN
Solar/Wind Harmer
0.931
270071AF1-092 GEN
Solar/Wind Harmer
7.22
270024AE2-089 GEN
Solar/Wind Harmer
2.252
24729505KEY G4
Adder
3.086
253349AC2-067 GEN
Solar/Wind Harmer
2.345
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.2
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.877
253372AE2-315 SEC3
Adder
0.877
965101AG1-375 GEN
Solar/Wind Harmer
4.621
971347AH1-153 GEN
Solar/Wind Harmer
6.923
971771AH1-392 GEN
Solar/Wind Harmer
4.108
270543AE2-219 C
Solar/Wind Harmer
2.334
945581AF1-223 GEN
Solar/Wind Harmer
2.066
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.515
971029AG2-637 GEN
Solar/Wind Harmer
6.767
971673AH1-337 GEN
Solar/Wind Harmer
2.069
960681AF2-359 GEN
Solar/Wind Harmer
1.696
253383AE2-342_GEN
Solar/Wind Harmer
0.396
970115AG2-085 GEN
Solar/Wind Harmer
1.766
274775LINCOLN ;6U
Adder
3.69
274776LINCOLN ;7U
Adder
3.69
274777LINCOLN ;8U
Adder
3.69
274814UNIV PK N;0U
Adder
2.2
274807UNIV PK N;3U
Adder
2.195
274805UNIV PK N;1U
Adder
2.186
274811UNIV PK N;7U
Adder
2.181
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.363
972227AH1-698 GEN1
Adder
1.129
274687WILL CNTY;4U
Adder
12.046
274687WILL CNTY;4U
Adder
12.046
274675JOLIET 29;7U
Adder
13.215
274675JOLIET 29;7U
Adder
12.743
274731ELWOOD EC;2P
Adder
7.072
274733ELWOOD EC;3P
Adder
7.072
274735ELWOOD EC;4P
Adder
7.072
274728ELWOOD EC;5P
Adder
7.073
270054AF2-122 C O1
Solar/Wind Helper
0.817
971549AH1-272 GEN
Solar/Wind Harmer
6.317
270466AD2-091
50/50
5.416
270471AD2-092_GEN
Solar/Wind Harmer
4.871
938701AE1-092 GEN
Solar/Wind Harmer
21.927
964601AG1-323 GEN
Solar/Wind Harmer
3.191
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.972
270227U2-072_GEN3
Solar/Wind Harmer
1.972
270228U2-072_GEN4
Solar/Wind Harmer
1.972
270231U2-072_GEN5
Solar/Wind Harmer
1.972
946101AF1-275 GEN
Solar/Wind Harmer
1.344
241960AC2-195 GEN
Solar/Wind Harmer
2.356
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.824
253378AE2-206_GEN
Solar/Wind Harmer
2.393
276820AF1-078_GEN
Solar/Wind Harmer
1.063
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.391
246937BC-WTG2
Solar/Wind Harmer
2.35
270007AE1-245 C
Solar/Wind Harmer
3.337
942801AE2-298 GEN
Solar/Wind Harmer
0.85
970611AG2-400 GEN
Solar/Wind Harmer
5.303
270518AE2-148 GEN
Solar/Wind Harmer
6.27
942861AE2-305 GEN
Solar/Wind Harmer
3.903
25326109MON D
Adder
0.652
25322209TAIT E
Adder
4.67
25322209TAIT E
Adder
4.565
942221AE2-234 GEN
Solar/Wind Harmer
0.35
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.397
944541AF1-119 GEN
Solar/Wind Harmer
1.949
960971AF2-388 GEN
Solar/Wind Harmer
5.087
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.927
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
960981AF2-389 GEN
Solar/Wind Harmer
0.69
957891AF2-083 GEN
Solar/Wind Harmer
1.539
970883AG2-550 GEN
Solar/Wind Harmer
4.558
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.227
961051AF2-396 GEN
Solar/Wind Harmer
3.361
270526AF1-158 GEN
Solar/Wind Harmer
2.056
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.044
270599AE1-208 GEN
Solar/Wind Harmer
3.671
270031AE2-169
Solar/Wind Harmer
3.671
965681AG1-436 GEN
Solar/Wind Harmer
5.612
965791AG1-447 GEN
Solar/Wind Harmer
2.871
970825AG2-519 GEN
Solar/Wind Harmer
4.662
960441AF2-335 GEN
Solar/Wind Harmer
4.415
274770LINCOLN ;1U
Adder
3.69
274771LINCOLN ;2U
Adder
3.69
274808UNIV PK N;4U
Adder
2.171
274803UNIV PARK;6U
Adder
2.528
972259AH1-714 GEN
Adder
8.249
274674JOLIET 9 ;6U
Adder
6.626
270349AD2-093_GEN
Solar/Wind Harmer
4.871
971995AH1-542 GEN
Solar/Wind Harmer
11.773
270223U2-072_GEN1
Solar/Wind Harmer
1.972
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.492
241813AF1-122_GEN
Solar/Wind Harmer
4.897
970593AG2-378 GEN
Solar/Wind Harmer
1.416
962761AG1-125 GEN
Solar/Wind Harmer
20.876
970149AG2-104 GEN
Solar/Wind Harmer
25.782
970155AG2-107 GEN
Solar/Wind Harmer
9.103
246936BC-WTG1
Solar/Wind Harmer
2.35
270489AE1-102 GEN1
Solar/Wind Harmer
0.781
965421AG1-410 GEN
Solar/Wind Harmer
17.815
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.471
24695305TIMB G C
Solar/Wind Harmer
3.012
965011AG1-365 GEN
Solar/Wind Harmer
5.303
270159DARBY CT4
Adder
4.607
944231AF1-091 GEN
Solar/Wind Harmer
1.841
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.398
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.544
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.927
253371AE2-315 SEC2
Adder
0.877
958861AF2-177 GEN
Solar/Wind Harmer
5.05
247536S-71 GEN
Solar/Wind Harmer
1.864
945111AF1-176 GEN
Solar/Wind Harmer
8.158
270505AE1-170 C O1
Solar/Wind Harmer
6.839
945371AF1-202 GEN
Solar/Wind Harmer
3.179
270449AD2-020 GEN
Solar/Wind Harmer
1.273
943021AE2-325 GEN
Solar/Wind Harmer
1.654
970245AG2-165 GEN
Solar/Wind Harmer
8.044
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.407
965031AG1-367 GEN
Solar/Wind Harmer
4.405
970373AG2-245 GEN
Solar/Wind Harmer
9.248
274751CRETE EC ;1U
Adder
3.605
274754CRETE EC ;4U
Adder
3.605
274773LINCOLN ;4U
Adder
3.69
274774LINCOLN ;5U
Adder
3.69
274723RIVER EC ;12
Adder
7.833
274812UNIV PK N;8U
Adder
2.181
274801UNIV PARK;4U
Adder
2.525
274676JOLIET 29;8U
Adder
13.215
274674JOLIET 9 ;6U
Adder
6.626
274732ELWOOD EC;7P
Adder
7.073
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.603
274676JOLIET 29;8U
Adder
12.743
274729ELWOOD EC;1P
Adder
7.072
274730ELWOOD EC;6P
Adder
7.073
274734ELWOOD EC;8P
Adder
7.073
274736ELWOOD EC;9P
Adder
7.073
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.388
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.568
MECLTFEXP_MEC->PJM
CLTF
6.327
SIGELTFEXP_SIGE->PJM
CLTF
0.182
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.837
LAGNLTFEXP_LAGN->PJM
CLTF
5.116
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.348
TVALTFEXP_TVA->PJM
CLTF
2.374
NYPJM->LTFIMP_NY
CLTF
1.305
LGEELTFEXP_LGEE->PJM
CLTF
2.295
WECLTFEXP_WEC->PJM
CLTF
1.59
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.151

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#9729_05MALIS 138_M1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9729_05MALIS 138_M1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.05 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1747.91
MW Contribution:4.56
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.955
270284AF1-227 GEN1
Solar/Wind Harmer
6.834
270286AF1-227 GEN2
Solar/Wind Harmer
2.528
270287AF1-227 GEN3
Solar/Wind Harmer
2.528
270578AF1-285 GEN2
Solar/Wind Harmer
0.464
241973AD2-163_GEN1
Solar/Wind Harmer
1.95
270302AB2-170 GEN
Solar/Wind Harmer
7.799
270317AD1-130_GEN
Solar/Wind Harmer
2.99
270520AE2-214 GEN
Solar/Wind Harmer
5.383
970179AG2-119 GEN
Solar/Wind Harmer
6.775
962771AG1-126 GEN
Solar/Wind Harmer
20.865
957201AF2-014 GEN
Solar/Wind Harmer
2.722
270435AC2-044 GEN
Solar/Wind Harmer
1.201
241972AD1-140 GEN
Solar/Wind Harmer
2.565
247607V1-011 GEN
Solar/Wind Harmer
2.223
965051AG1-369 GEN
Solar/Wind Harmer
2.761
270297AD1-101 GEN
Solar/Wind Harmer
1.539
965041AG1-368 GEN
Solar/Wind Harmer
5.365
945631AF1-228 GEN
Solar/Wind Harmer
2.51
270156DARBY CT1
Adder
4.68
270157DARBY CT2
Adder
4.668
270158DARBY CT3
Adder
4.594
963791AG1-232 GEN
Solar/Wind Harmer
6.779
943861AF1-054 GEN
Solar/Wind Harmer
1.923
943851AF1-053 GEN
Solar/Wind Harmer
0.929
270071AF1-092 GEN
Solar/Wind Harmer
7.217
270024AE2-089 GEN
Solar/Wind Harmer
2.251
24729505KEY G4
Adder
3.085
270466AD2-091
50/50
5.413
270471AD2-092_GEN
Solar/Wind Harmer
4.868
938701AE1-092 GEN
Solar/Wind Harmer
21.914
964601AG1-323 GEN
Solar/Wind Harmer
3.189
964601AG1-323 GEN
Solar/Wind Harmer
1.483
270224U2-072_GEN2
Solar/Wind Harmer
1.971
270227U2-072_GEN3
Solar/Wind Harmer
1.971
270228U2-072_GEN4
Solar/Wind Harmer
1.971
270231U2-072_GEN5
Solar/Wind Harmer
1.971
946101AF1-275 GEN
Solar/Wind Harmer
1.343
241960AC2-195 GEN
Solar/Wind Harmer
2.355
971201AH1-060 GEN
Solar/Wind Harmer
1.53
970077AG2-063 GEN
Solar/Wind Harmer
3.821
253378AE2-206_GEN
Solar/Wind Harmer
2.391
276820AF1-078_GEN
Solar/Wind Harmer
1.062
25326509SID D
Adder
0.831
246938BC-WTG3
Solar/Wind Harmer
2.389
246937BC-WTG2
Solar/Wind Harmer
2.349
270007AE1-245 C
Solar/Wind Harmer
3.335
942801AE2-298 GEN
Solar/Wind Harmer
0.849
970611AG2-400 GEN
Solar/Wind Harmer
5.301
270518AE2-148 GEN
Solar/Wind Harmer
6.267
942861AE2-305 GEN
Solar/Wind Harmer
3.897
25326109MON D
Adder
0.651
25322209TAIT E
Adder
4.667
25322209TAIT E
Adder
4.562
942221AE2-234 GEN
Solar/Wind Harmer
0.349
247620Y3-023
Adder
0.215
270201AC2-176 GEN
Solar/Wind Harmer
2.396
944541AF1-119 GEN
Solar/Wind Harmer
1.948
960971AF2-388 GEN
Solar/Wind Harmer
5.085
247621Y3-024
Adder
0.112
253370AE2-315 SEC1
Adder
0.926
964611AG1-324 GEN
Solar/Wind Harmer
0.545
964611AG1-324 GEN
Solar/Wind Harmer
0.242
270216AD2-079_GEN
Solar/Wind Harmer
0.279
957891AF2-083 GEN
Solar/Wind Harmer
1.538
960981AF2-389 GEN
Solar/Wind Harmer
0.689
970883AG2-550 GEN
Solar/Wind Harmer
4.556
970885AG2-551 GEN
Solar/Wind Harmer
1.06
961051AF2-396 GEN
Solar/Wind Harmer
7.223
961051AF2-396 GEN
Solar/Wind Harmer
3.36
270526AF1-158 GEN
Solar/Wind Harmer
2.055
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.04
270599AE1-208 GEN
Solar/Wind Harmer
3.669
270031AE2-169
Solar/Wind Harmer
3.669
965681AG1-436 GEN
Solar/Wind Harmer
5.609
965791AG1-447 GEN
Solar/Wind Harmer
2.87
970825AG2-519 GEN
Solar/Wind Harmer
4.659
270349AD2-093_GEN
Solar/Wind Harmer
4.868
971995AH1-542 GEN
Solar/Wind Harmer
11.766
270223U2-072_GEN1
Solar/Wind Harmer
1.971
270578AF1-285 GEN2
Solar/Wind Harmer
1.206
270391AF1-285 GEN3
Solar/Wind Harmer
1.206
270462AD2-086
Solar/Wind Harmer
6.488
241813AF1-122_GEN
Solar/Wind Harmer
4.895
970593AG2-378 GEN
Solar/Wind Harmer
1.415
962761AG1-125 GEN
Solar/Wind Harmer
20.865
970149AG2-104 GEN
Solar/Wind Harmer
25.768
970155AG2-107 GEN
Solar/Wind Harmer
9.098
246936BC-WTG1
Solar/Wind Harmer
2.349
270489AE1-102 GEN1
Solar/Wind Harmer
0.78
965421AG1-410 GEN
Solar/Wind Harmer
17.806
247521TR3_G114
Solar/Wind Harmer
1.86
270246TR4_N_V150
Solar/Wind Harmer
0.47
24695305TIMB G C
Solar/Wind Harmer
3.01
965011AG1-365 GEN
Solar/Wind Harmer
5.301
270159DARBY CT4
Adder
4.605
944231AF1-091 GEN
Solar/Wind Harmer
1.84
253343AC1-166 GEN
Solar/Wind Harmer
0.525
253325AC1-069 GEN
Solar/Wind Harmer
0.506
960071AF2-298 GEN
Solar/Wind Harmer
2.397
25326309TAIT D
Adder
0.525
270063AE2-323 C
Solar/Wind Harmer
1.055
965651AG1-433 GEN
Solar/Wind Harmer
2.542
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
958861AF2-177 GEN
Solar/Wind Harmer
5.048
247536S-71 GEN
Solar/Wind Harmer
1.863
945111AF1-176 GEN
Solar/Wind Harmer
8.154
270505AE1-170 C O1
Solar/Wind Harmer
6.835
945371AF1-202 GEN
Solar/Wind Harmer
3.177
270449AD2-020 GEN
Solar/Wind Harmer
1.272
943021AE2-325 GEN
Solar/Wind Harmer
1.653
970245AG2-165 GEN
Solar/Wind Harmer
8.04
970825AG2-519 GEN
Solar/Wind Harmer
1.04
270005AE1-210 C O1
Solar/Wind Harmer
2.406
965031AG1-367 GEN
Solar/Wind Harmer
4.403
970373AG2-245 GEN
Solar/Wind Harmer
9.243
274751CRETE EC ;1U
Adder
3.603
274754CRETE EC ;4U
Adder
3.603
270475AD2-096_GEN
50/50
7.79
942871AE2-306 GEN
Solar/Wind Harmer
0.904
270391AF1-285 GEN3
Solar/Wind Harmer
0.464
241974AD2-163_GEN2
Solar/Wind Harmer
1.95
270485AE1-090_GEN
Solar/Wind Harmer
0.564
942051AE2-217 GEN
Solar/Wind Harmer
13.937
970065AG2-057 GEN
Solar/Wind Harmer
0.765
970605AG2-385 GEN
Solar/Wind Harmer
3.821
241955AC1-078 GEN
Solar/Wind Harmer
4.989
970153AG2-106 GEN
Solar/Wind Harmer
9.098
270491AE1-102 GEN2
Solar/Wind Harmer
0.78
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270191TR4_S_V150
Solar/Wind Harmer
1.659
270247TR4_N_V136
Solar/Wind Harmer
0.47
270258AD1-119 GEN
Solar/Wind Harmer
1.494
959331AF2-224 GEN
Solar/Wind Harmer
5.301
965021AG1-366 GEN
Solar/Wind Harmer
1.233
270044AE2-322 C
Solar/Wind Harmer
0.689
270404AC1-167 GEN
Solar/Wind Harmer
0.574
270588AE1-091_GEN
Solar/Wind Harmer
5.49
270043AE2-236 GEN
Solar/Wind Harmer
2.707
253338AC1-165 GEN
Solar/Wind Harmer
0.525
253333AC1-068 GEN
Solar/Wind Harmer
0.506
970031AG2-029 GEN
Solar/Wind Harmer
14.476
971617AH1-308 GEN
Solar/Wind Harmer
2.788
944531AF1-118 GEN
Solar/Wind Harmer
16.774
270541AE2-072 C
Solar/Wind Harmer
2.157
962031AG1-047 GEN
Solar/Wind Harmer
1.409
957741AF2-068 GEN
Solar/Wind Harmer
6.991
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.926
253371AE2-315 SEC2
Adder
0.876
274773LINCOLN ;4U
Adder
3.688
274774LINCOLN ;5U
Adder
3.688
274723RIVER EC ;12
Adder
7.829
274812UNIV PK N;8U
Adder
2.18
274801UNIV PARK;4U
Adder
2.524
274676JOLIET 29;8U
Adder
13.208
274674JOLIET 9 ;6U
Adder
6.622
274732ELWOOD EC;7P
Adder
7.069
970349AG2-230 GEN
Solar/Wind Harmer
6.92
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.584
24642205MAYFLWER
Adder
0.289
970513AG2-328 GEN
Solar/Wind Harmer
8.04
970517AG2-330 GEN
Solar/Wind Harmer
7.292
24441205WTRV SLR C
Solar/Wind Harmer
0.061
247604X1-042
Adder
0.186
946031AF1-268 GEN
Solar/Wind Harmer
3.705
958821AF2-173 GEN
Solar/Wind Harmer
6.164
270004AE1-209 GEN
Solar/Wind Harmer
2.406
274752CRETE EC ;2U
Adder
3.603
274753CRETE EC ;3U
Adder
3.603
274772LINCOLN ;3U
Adder
3.688
274724RIVER EC ;11
Adder
7.738
274802UNIV PARK;5U
Adder
2.527
274826FISK ;BP
Adder
4.742
274800UNIV PARK;3U
Adder
2.524
972038AH1-567 GEN2
Adder
0.158
972228AH1-698 GEN2
Adder
1.602
274676JOLIET 29;8U
Adder
12.736
274729ELWOOD EC;1P
Adder
7.069
274730ELWOOD EC;6P
Adder
7.069
274734ELWOOD EC;8P
Adder
7.069
274736ELWOOD EC;9P
Adder
7.069
960441AF2-335 GEN
Solar/Wind Harmer
4.412
274770LINCOLN ;1U
Adder
3.688
274771LINCOLN ;2U
Adder
3.688
274808UNIV PK N;4U
Adder
2.17
274803UNIV PARK;6U
Adder
2.527
972259AH1-714 GEN
Adder
8.245
274674JOLIET 9 ;6U
Adder
6.622
253349AC2-067 GEN
Solar/Wind Harmer
2.344
253400AC2-068 GEN
Solar/Wind Harmer
0.943
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.471
25306009OHH W.
Adder
1.337
253372AE2-315 SEC3
Adder
0.876
253372AE2-315 SEC3
Adder
0.876
965101AG1-375 GEN
Solar/Wind Harmer
4.618
971347AH1-153 GEN
Solar/Wind Harmer
6.92
971771AH1-392 GEN
Solar/Wind Harmer
4.106
270543AE2-219 C
Solar/Wind Harmer
2.333
945581AF1-223 GEN
Solar/Wind Harmer
2.065
944161AF1-084 GEN
Solar/Wind Harmer
1
971769AH1-391 GEN
Solar/Wind Harmer
4.513
971029AG2-637 GEN
Solar/Wind Harmer
6.764
971673AH1-337 GEN
Solar/Wind Harmer
2.068
960681AF2-359 GEN
Solar/Wind Harmer
1.695
253383AE2-342_GEN
Solar/Wind Harmer
0.395
970115AG2-085 GEN
Solar/Wind Harmer
1.765
274775LINCOLN ;6U
Adder
3.688
274776LINCOLN ;7U
Adder
3.688
274777LINCOLN ;8U
Adder
3.688
274814UNIV PK N;0U
Adder
2.199
274807UNIV PK N;3U
Adder
2.194
274805UNIV PK N;1U
Adder
2.185
274811UNIV PK N;7U
Adder
2.18
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.361
972227AH1-698 GEN1
Adder
1.128
274687WILL CNTY;4U
Adder
12.041
274687WILL CNTY;4U
Adder
12.041
274675JOLIET 29;7U
Adder
13.208
274675JOLIET 29;7U
Adder
12.736
274731ELWOOD EC;2P
Adder
7.069
274733ELWOOD EC;3P
Adder
7.069
274735ELWOOD EC;4P
Adder
7.069
274728ELWOOD EC;5P
Adder
7.069
270054AF2-122 C O1
Solar/Wind Helper
0.816
971549AH1-272 GEN
Solar/Wind Harmer
6.314
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.361
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.564
MECLTFEXP_MEC->PJM
CLTF
6.323
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.349
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.818
LAGNLTFEXP_LAGN->PJM
CLTF
5.114
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.347
TVALTFEXP_TVA->PJM
CLTF
2.373
NYPJM->LTFIMP_NY
CLTF
1.304
LGEELTFEXP_LGEE->PJM
CLTF
2.294
WECLTFEXP_WEC->PJM
CLTF
1.589
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:112.44 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.27
MW Contribution:4.54
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
972228AH1-698 GEN2
Adder
1.596
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
270349AD2-093_GEN
Solar/Wind Harmer
4.846
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7222_05MALIS 765_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7222_05MALIS 765_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1584.05
MW Contribution:4.54
Bus #Bus NameTypeMW Contribution
270349AD2-093_GEN
Solar/Wind Harmer
4.846
270036AE2-216 BAT
50/50
5.929
270284AF1-227 GEN1
Solar/Wind Harmer
6.804
270286AF1-227 GEN2
Solar/Wind Harmer
2.517
270287AF1-227 GEN3
Solar/Wind Harmer
2.517
270578AF1-285 GEN2
Solar/Wind Harmer
0.462
241973AD2-163_GEN1
Solar/Wind Harmer
1.939
270302AB2-170 GEN
Solar/Wind Harmer
7.765
270317AD1-130_GEN
Solar/Wind Harmer
2.977
270520AE2-214 GEN
Solar/Wind Harmer
5.355
970179AG2-119 GEN
Solar/Wind Harmer
6.746
962771AG1-126 GEN
Solar/Wind Harmer
20.775
957201AF2-014 GEN
Solar/Wind Harmer
2.711
270435AC2-044 GEN
Solar/Wind Harmer
1.195
241972AD1-140 GEN
Solar/Wind Harmer
2.551
247607V1-011 GEN
Solar/Wind Harmer
2.214
965051AG1-369 GEN
Solar/Wind Harmer
2.75
270297AD1-101 GEN
Solar/Wind Harmer
1.533
965041AG1-368 GEN
Solar/Wind Harmer
5.342
945631AF1-228 GEN
Solar/Wind Harmer
2.501
270156DARBY CT1
Adder
4.664
270157DARBY CT2
Adder
4.653
270158DARBY CT3
Adder
4.578
963791AG1-232 GEN
Solar/Wind Harmer
6.751
943861AF1-054 GEN
Solar/Wind Harmer
1.9
943851AF1-053 GEN
Solar/Wind Harmer
0.918
270071AF1-092 GEN
Solar/Wind Harmer
7.187
270024AE2-089 GEN
Solar/Wind Harmer
2.242
24729505KEY G4
Adder
3.072
253349AC2-067 GEN
Solar/Wind Harmer
2.334
253400AC2-068 GEN
Solar/Wind Harmer
0.939
961761AG1-017 GEN
Solar/Wind Harmer
0.199
958711AF2-162 GEN
Solar/Wind Harmer
0.469
25306009OHH W.
Adder
1.331
253372AE2-315 SEC3
Adder
0.873
253372AE2-315 SEC3
Adder
0.873
965101AG1-375 GEN
Solar/Wind Harmer
4.6
971347AH1-153 GEN
Solar/Wind Harmer
6.892
971771AH1-392 GEN
Solar/Wind Harmer
4.09
270543AE2-219 C
Solar/Wind Harmer
2.323
945581AF1-223 GEN
Solar/Wind Harmer
2.057
944161AF1-084 GEN
Solar/Wind Harmer
0.996
971769AH1-391 GEN
Solar/Wind Harmer
4.495
971029AG2-637 GEN
Solar/Wind Harmer
6.737
971673AH1-337 GEN
Solar/Wind Harmer
2.06
960681AF2-359 GEN
Solar/Wind Harmer
1.688
970115AG2-085 GEN
Solar/Wind Harmer
1.758
253383AE2-342_GEN
Solar/Wind Harmer
0.388
274775LINCOLN ;6U
Adder
3.673
274776LINCOLN ;7U
Adder
3.673
274777LINCOLN ;8U
Adder
3.673
274814UNIV PK N;0U
Adder
2.19
274807UNIV PK N;3U
Adder
2.185
274805UNIV PK N;1U
Adder
2.176
274811UNIV PK N;7U
Adder
2.171
972037AH1-567 GEN1
Adder
0.079
274827FISK ;RP
Adder
3.347
972227AH1-698 GEN1
Adder
1.124
270054AF2-122 C O1
Solar/Wind Helper
0.806
971549AH1-272 GEN
Solar/Wind Harmer
6.289
270475AD2-096_GEN
50/50
7.755
942871AE2-306 GEN
Solar/Wind Harmer
0.9
270391AF1-285 GEN3
Solar/Wind Harmer
0.462
241974AD2-163_GEN2
Solar/Wind Harmer
1.939
270485AE1-090_GEN
Solar/Wind Harmer
0.562
942051AE2-217 GEN
Solar/Wind Harmer
13.864
970065AG2-057 GEN
Solar/Wind Harmer
0.762
970605AG2-385 GEN
Solar/Wind Harmer
3.797
241955AC1-078 GEN
Solar/Wind Harmer
4.97
970153AG2-106 GEN
Solar/Wind Harmer
9.059
270491AE1-102 GEN2
Solar/Wind Harmer
0.777
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.652
270247TR4_N_V136
Solar/Wind Harmer
0.468
270258AD1-119 GEN
Solar/Wind Harmer
1.487
959331AF2-224 GEN
Solar/Wind Harmer
5.279
965021AG1-366 GEN
Solar/Wind Harmer
1.228
270044AE2-322 C
Solar/Wind Harmer
0.687
270404AC1-167 GEN
Solar/Wind Harmer
0.572
270588AE1-091_GEN
Solar/Wind Harmer
5.47
270043AE2-236 GEN
Solar/Wind Harmer
2.696
253338AC1-165 GEN
Solar/Wind Harmer
0.523
253333AC1-068 GEN
Solar/Wind Harmer
0.505
970031AG2-029 GEN
Solar/Wind Harmer
14.416
971617AH1-308 GEN
Solar/Wind Harmer
2.777
944531AF1-118 GEN
Solar/Wind Harmer
16.706
270541AE2-072 C
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
1.403
957741AF2-068 GEN
Solar/Wind Harmer
6.963
253303V4-073 C
Solar/Wind Harmer
0.053
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
970349AG2-230 GEN
Solar/Wind Harmer
6.892
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.574
24642205MAYFLWER
Adder
0.288
970513AG2-328 GEN
Solar/Wind Harmer
8.007
970517AG2-330 GEN
Solar/Wind Harmer
7.263
24441205WTRV SLR C
Solar/Wind Harmer
0.06
247604X1-042
Adder
0.185
946031AF1-268 GEN
Solar/Wind Harmer
3.69
958821AF2-173 GEN
Solar/Wind Harmer
6.139
270004AE1-209 GEN
Solar/Wind Harmer
2.397
274752CRETE EC ;2U
Adder
3.589
274753CRETE EC ;3U
Adder
3.589
274772LINCOLN ;3U
Adder
3.673
274724RIVER EC ;11
Adder
7.706
274802UNIV PARK;5U
Adder
2.517
274826FISK ;BP
Adder
4.723
274800UNIV PARK;3U
Adder
2.514
972038AH1-567 GEN2
Adder
0.157
971995AH1-542 GEN
Solar/Wind Harmer
11.714
270223U2-072_GEN1
Solar/Wind Harmer
1.963
270578AF1-285 GEN2
Solar/Wind Harmer
1.2
270391AF1-285 GEN3
Solar/Wind Harmer
1.2
270462AD2-086
Solar/Wind Harmer
6.46
241813AF1-122_GEN
Solar/Wind Harmer
4.874
970593AG2-378 GEN
Solar/Wind Harmer
1.406
962761AG1-125 GEN
Solar/Wind Harmer
20.775
970149AG2-104 GEN
Solar/Wind Harmer
25.657
970155AG2-107 GEN
Solar/Wind Harmer
9.059
246936BC-WTG1
Solar/Wind Harmer
2.339
270489AE1-102 GEN1
Solar/Wind Harmer
0.777
965421AG1-410 GEN
Solar/Wind Harmer
17.731
247521TR3_G114
Solar/Wind Harmer
1.852
270246TR4_N_V150
Solar/Wind Harmer
0.468
24695305TIMB G C
Solar/Wind Harmer
2.998
965011AG1-365 GEN
Solar/Wind Harmer
5.279
270159DARBY CT4
Adder
4.59
944231AF1-091 GEN
Solar/Wind Harmer
1.832
253343AC1-166 GEN
Solar/Wind Harmer
0.523
253325AC1-069 GEN
Solar/Wind Harmer
0.505
960071AF2-298 GEN
Solar/Wind Harmer
2.387
25326309TAIT D
Adder
0.523
270063AE2-323 C
Solar/Wind Harmer
1.051
965651AG1-433 GEN
Solar/Wind Harmer
2.532
24639705ELKHART HY
Adder
0.071
253370AE2-315 SEC1
Adder
0.923
253371AE2-315 SEC2
Adder
0.873
958861AF2-177 GEN
Solar/Wind Harmer
5.028
247536S-71 GEN
Solar/Wind Harmer
1.856
945111AF1-176 GEN
Solar/Wind Harmer
8.121
270505AE1-170 C O1
Solar/Wind Harmer
6.807
945371AF1-202 GEN
Solar/Wind Harmer
3.165
270449AD2-020 GEN
Solar/Wind Harmer
1.267
943021AE2-325 GEN
Solar/Wind Harmer
1.646
970245AG2-165 GEN
Solar/Wind Harmer
8.007
970825AG2-519 GEN
Solar/Wind Harmer
1.035
270005AE1-210 C O1
Solar/Wind Harmer
2.397
965031AG1-367 GEN
Solar/Wind Harmer
4.385
970373AG2-245 GEN
Solar/Wind Harmer
9.206
274751CRETE EC ;1U
Adder
3.589
274754CRETE EC ;4U
Adder
3.589
274773LINCOLN ;4U
Adder
3.673
274774LINCOLN ;5U
Adder
3.673
274723RIVER EC ;12
Adder
7.798
274812UNIV PK N;8U
Adder
2.171
274801UNIV PARK;4U
Adder
2.514
270466AD2-091
50/50
5.39
270471AD2-092_GEN
Solar/Wind Harmer
4.846
938701AE1-092 GEN
Solar/Wind Harmer
21.808
964601AG1-323 GEN
Solar/Wind Harmer
3.173
964601AG1-323 GEN
Solar/Wind Harmer
1.476
270224U2-072_GEN2
Solar/Wind Harmer
1.963
270227U2-072_GEN3
Solar/Wind Harmer
1.963
270228U2-072_GEN4
Solar/Wind Harmer
1.963
270231U2-072_GEN5
Solar/Wind Harmer
1.963
946101AF1-275 GEN
Solar/Wind Harmer
1.336
241960AC2-195 GEN
Solar/Wind Harmer
2.345
971201AH1-060 GEN
Solar/Wind Harmer
1.523
970077AG2-063 GEN
Solar/Wind Harmer
3.797
253378AE2-206_GEN
Solar/Wind Harmer
2.379
276820AF1-078_GEN
Solar/Wind Harmer
1.057
25326509SID D
Adder
0.827
246938BC-WTG3
Solar/Wind Harmer
2.379
246937BC-WTG2
Solar/Wind Harmer
2.339
270007AE1-245 C
Solar/Wind Harmer
3.321
942801AE2-298 GEN
Solar/Wind Harmer
0.846
970611AG2-400 GEN
Solar/Wind Harmer
5.279
270518AE2-148 GEN
Solar/Wind Harmer
6.245
942861AE2-305 GEN
Solar/Wind Harmer
3.849
25326109MON D
Adder
0.648
25322209TAIT E
Adder
4.647
25322209TAIT E
Adder
4.543
942221AE2-234 GEN
Solar/Wind Harmer
0.348
247620Y3-023
Adder
0.214
270201AC2-176 GEN
Solar/Wind Harmer
2.386
944541AF1-119 GEN
Solar/Wind Harmer
1.941
960971AF2-388 GEN
Solar/Wind Harmer
5.064
247621Y3-024
Adder
0.111
253370AE2-315 SEC1
Adder
0.923
964611AG1-324 GEN
Solar/Wind Harmer
0.542
964611AG1-324 GEN
Solar/Wind Harmer
0.241
270216AD2-079_GEN
Solar/Wind Harmer
0.278
960981AF2-389 GEN
Solar/Wind Harmer
0.686
957891AF2-083 GEN
Solar/Wind Harmer
1.532
970883AG2-550 GEN
Solar/Wind Harmer
4.537
970885AG2-551 GEN
Solar/Wind Harmer
1.055
961051AF2-396 GEN
Solar/Wind Harmer
7.194
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270526AF1-158 GEN
Solar/Wind Harmer
2.047
24441505OLIV SLR
Solar/Wind Harmer
0.06
970321AG2-212 GEN
Solar/Wind Harmer
8.007
270599AE1-208 GEN
Solar/Wind Harmer
3.654
270031AE2-169
Solar/Wind Harmer
3.654
965681AG1-436 GEN
Solar/Wind Harmer
5.586
965791AG1-447 GEN
Solar/Wind Harmer
2.858
970825AG2-519 GEN
Solar/Wind Harmer
4.641
960441AF2-335 GEN
Solar/Wind Harmer
4.395
274770LINCOLN ;1U
Adder
3.673
274771LINCOLN ;2U
Adder
3.673
274808UNIV PK N;4U
Adder
2.161
274803UNIV PARK;6U
Adder
2.517
972259AH1-714 GEN
Adder
8.212
972228AH1-698 GEN2
Adder
1.596
CBM West 1LTFEXP_CBM-W1->PJM
CBM
56.137
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.529
MECLTFEXP_MEC->PJM
CLTF
6.298
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.348
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.662
LAGNLTFEXP_LAGN->PJM
CLTF
5.094
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.339
TVALTFEXP_TVA->PJM
CLTF
2.364
NYPJM->LTFIMP_NY
CLTF
1.299
LGEELTFEXP_LGEE->PJM
CLTF
2.285
WECLTFEXP_WEC->PJM
CLTF
1.583
AG2-052LTFEXP_AG2-052->PJM
LTF
0.1
AH1-155LTFEXP_AH1-155->PJM
LTF
0.15

Details for 05HYATT-05VASSEL 345.0 kV Ckt 1 line l/o AEP_P4_#7216_05VASSEL 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HYATT-05VASSEL 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7216_05VASSEL 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:102.74 %
Rating:1409.0 MVA
Rating Type:B
MVA to Mitigate:1447.54
MW Contribution:4.51
Bus #Bus NameTypeMW Contribution
270036AE2-216 BAT
50/50
5.918
270284AF1-227 GEN1
Solar/Wind Harmer
6.793
270286AF1-227 GEN2
Solar/Wind Harmer
2.513
270287AF1-227 GEN3
Solar/Wind Harmer
2.513
270578AF1-285 GEN2
Solar/Wind Harmer
0.461
241973AD2-163_GEN1
Solar/Wind Harmer
1.957
270302AB2-170 GEN
Solar/Wind Harmer
7.752
270317AD1-130_GEN
Solar/Wind Harmer
2.972
270520AE2-214 GEN
Solar/Wind Harmer
5.445
970179AG2-119 GEN
Solar/Wind Harmer
6.8
962771AG1-126 GEN
Solar/Wind Harmer
20.13
957201AF2-014 GEN
Solar/Wind Harmer
2.694
270435AC2-044 GEN
Solar/Wind Harmer
1.188
241972AD1-140 GEN
Solar/Wind Harmer
2.576
247607V1-011 GEN
Solar/Wind Harmer
2.2
270297AD1-101 GEN
Solar/Wind Harmer
1.527
965051AG1-369 GEN
Solar/Wind Harmer
2.727
945631AF1-228 GEN
Solar/Wind Harmer
2.554
270156DARBY CT1
Adder
4.766
270157DARBY CT2
Adder
4.755
270158DARBY CT3
Adder
4.679
965041AG1-368 GEN
Solar/Wind Harmer
5.294
943861AF1-054 GEN
Solar/Wind Harmer
1.935
943851AF1-053 GEN
Solar/Wind Harmer
0.935
963791AG1-232 GEN
Solar/Wind Harmer
6.686
270024AE2-089 GEN
Solar/Wind Harmer
2.223
270071AF1-092 GEN
Solar/Wind Harmer
7.094
253349AC2-067 GEN
Solar/Wind Harmer
2.343
253400AC2-068 GEN
Solar/Wind Harmer
0.942
24729505KEY G4
Adder
3.036
25306009OHH W.
Adder
1.338
253372AE2-315 SEC3
Adder
0.878
253372AE2-315 SEC3
Adder
0.878
961761AG1-017 GEN
Solar/Wind Harmer
0.197
958711AF2-162 GEN
Solar/Wind Harmer
0.464
965101AG1-375 GEN
Solar/Wind Harmer
4.55
971347AH1-153 GEN
Solar/Wind Harmer
6.79
270543AE2-219 C
Solar/Wind Harmer
2.31
945581AF1-223 GEN
Solar/Wind Harmer
2.036
971771AH1-392 GEN
Solar/Wind Harmer
4.033
253383AE2-342_GEN
Solar/Wind Harmer
0.396
971029AG2-637 GEN
Solar/Wind Harmer
6.703
971673AH1-337 GEN
Solar/Wind Harmer
2.05
944161AF1-084 GEN
Solar/Wind Harmer
0.982
971769AH1-391 GEN
Solar/Wind Harmer
4.432
960681AF2-359 GEN
Solar/Wind Harmer
1.665
970115AG2-085 GEN
Solar/Wind Harmer
1.742
270054AF2-122 C O1
Solar/Wind Helper
0.786
270594AE1-207 GEN
Solar/Wind Harmer
2.721
270466AD2-091
50/50
5.38
270471AD2-092_GEN
Solar/Wind Harmer
4.839
938701AE1-092 GEN
Solar/Wind Harmer
21.937
964601AG1-323 GEN
Solar/Wind Harmer
3.19
964601AG1-323 GEN
Solar/Wind Harmer
1.484
270224U2-072_GEN2
Solar/Wind Harmer
1.959
270227U2-072_GEN3
Solar/Wind Harmer
1.959
270228U2-072_GEN4
Solar/Wind Harmer
1.959
270231U2-072_GEN5
Solar/Wind Harmer
1.959
946101AF1-275 GEN
Solar/Wind Harmer
1.359
241960AC2-195 GEN
Solar/Wind Harmer
2.364
971201AH1-060 GEN
Solar/Wind Harmer
1.536
970077AG2-063 GEN
Solar/Wind Harmer
3.843
253378AE2-206_GEN
Solar/Wind Harmer
2.386
276820AF1-078_GEN
Solar/Wind Harmer
1.06
25326509SID D
Adder
0.829
246938BC-WTG3
Solar/Wind Harmer
2.364
246937BC-WTG2
Solar/Wind Harmer
2.324
270007AE1-245 C
Solar/Wind Harmer
3.3
270475AD2-096_GEN
50/50
7.743
942871AE2-306 GEN
Solar/Wind Harmer
0.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.461
241974AD2-163_GEN2
Solar/Wind Harmer
1.957
270485AE1-090_GEN
Solar/Wind Harmer
0.561
942051AE2-217 GEN
Solar/Wind Harmer
14.042
970065AG2-057 GEN
Solar/Wind Harmer
0.768
970605AG2-385 GEN
Solar/Wind Harmer
3.843
241955AC1-078 GEN
Solar/Wind Harmer
5.062
970153AG2-106 GEN
Solar/Wind Harmer
8.778
270491AE1-102 GEN2
Solar/Wind Harmer
0.772
958091AF2-103 GEN
Solar/Wind Harmer
0.09
270191TR4_S_V150
Solar/Wind Harmer
1.639
270247TR4_N_V136
Solar/Wind Harmer
0.465
270258AD1-119 GEN
Solar/Wind Harmer
1.477
959331AF2-224 GEN
Solar/Wind Harmer
5.222
965021AG1-366 GEN
Solar/Wind Harmer
1.214
270044AE2-322 C
Solar/Wind Harmer
0.682
270404AC1-167 GEN
Solar/Wind Harmer
0.568
270588AE1-091_GEN
Solar/Wind Harmer
5.477
253338AC1-165 GEN
Solar/Wind Harmer
0.533
253333AC1-068 GEN
Solar/Wind Harmer
0.514
270043AE2-236 GEN
Solar/Wind Harmer
2.66
970031AG2-029 GEN
Solar/Wind Harmer
14.237
971617AH1-308 GEN
Solar/Wind Harmer
2.754
270541AE2-072 C
Solar/Wind Harmer
2.143
944531AF1-118 GEN
Solar/Wind Harmer
16.503
253303V4-073 C
Solar/Wind Harmer
0.054
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
962031AG1-047 GEN
Solar/Wind Harmer
1.393
957741AF2-068 GEN
Solar/Wind Harmer
6.912
970349AG2-230 GEN
Solar/Wind Harmer
6.79
247643Z2-116 C
Solar/Wind Harmer
0.032
945111AF1-176 GEN
Solar/Wind Harmer
2.539
24642205MAYFLWER
Adder
0.284
970513AG2-328 GEN
Solar/Wind Harmer
7.888
970517AG2-330 GEN
Solar/Wind Harmer
7.154
24441205WTRV SLR C
Solar/Wind Harmer
0.06
946031AF1-268 GEN
Solar/Wind Harmer
3.659
247604X1-042
Adder
0.183
958821AF2-173 GEN
Solar/Wind Harmer
6.084
270004AE1-209 GEN
Solar/Wind Harmer
2.375
270349AD2-093_GEN
Solar/Wind Harmer
4.839
971995AH1-542 GEN
Solar/Wind Harmer
11.797
270223U2-072_GEN1
Solar/Wind Harmer
1.959
270578AF1-285 GEN2
Solar/Wind Harmer
1.198
270391AF1-285 GEN3
Solar/Wind Harmer
1.198
270462AD2-086
Solar/Wind Harmer
6.448
241813AF1-122_GEN
Solar/Wind Harmer
4.917
970593AG2-378 GEN
Solar/Wind Harmer
1.423
962761AG1-125 GEN
Solar/Wind Harmer
20.13
970149AG2-104 GEN
Solar/Wind Harmer
24.861
970155AG2-107 GEN
Solar/Wind Harmer
8.778
246936BC-WTG1
Solar/Wind Harmer
2.324
270489AE1-102 GEN1
Solar/Wind Harmer
0.772
965421AG1-410 GEN
Solar/Wind Harmer
17.611
247521TR3_G114
Solar/Wind Harmer
1.837
270246TR4_N_V150
Solar/Wind Harmer
0.465
24695305TIMB G C
Solar/Wind Harmer
2.974
270159DARBY CT4
Adder
4.69
965011AG1-365 GEN
Solar/Wind Harmer
5.222
253343AC1-166 GEN
Solar/Wind Harmer
0.533
253325AC1-069 GEN
Solar/Wind Harmer
0.514
944231AF1-091 GEN
Solar/Wind Harmer
1.814
960071AF2-298 GEN
Solar/Wind Harmer
2.399
25326309TAIT D
Adder
0.526
270063AE2-323 C
Solar/Wind Harmer
1.037
253370AE2-315 SEC1
Adder
0.928
253371AE2-315 SEC2
Adder
0.878
965651AG1-433 GEN
Solar/Wind Harmer
2.504
247536S-71 GEN
Solar/Wind Harmer
1.844
958861AF2-177 GEN
Solar/Wind Harmer
4.973
24639705ELKHART HY
Adder
0.07
945111AF1-176 GEN
Solar/Wind Harmer
8.011
945371AF1-202 GEN
Solar/Wind Harmer
3.132
270505AE1-170 C O1
Solar/Wind Harmer
6.714
270449AD2-020 GEN
Solar/Wind Harmer
1.25
943021AE2-325 GEN
Solar/Wind Harmer
1.624
970245AG2-165 GEN
Solar/Wind Harmer
7.888
970825AG2-519 GEN
Solar/Wind Harmer
1.026
270005AE1-210 C O1
Solar/Wind Harmer
2.375
965031AG1-367 GEN
Solar/Wind Harmer
4.346
970373AG2-245 GEN
Solar/Wind Harmer
9.08
270032AE2-172
Solar/Wind Harmer
0.861
942801AE2-298 GEN
Solar/Wind Harmer
0.841
270518AE2-148 GEN
Solar/Wind Harmer
6.356
970611AG2-400 GEN
Solar/Wind Harmer
5.222
942861AE2-305 GEN
Solar/Wind Harmer
3.921
25326109MON D
Adder
0.653
25322209TAIT E
Adder
4.675
25322209TAIT E
Adder
4.57
942221AE2-234 GEN
Solar/Wind Harmer
0.344
253370AE2-315 SEC1
Adder
0.928
270201AC2-176 GEN
Solar/Wind Harmer
2.369
944541AF1-119 GEN
Solar/Wind Harmer
1.919
960971AF2-388 GEN
Solar/Wind Harmer
5.008
247620Y3-023
Adder
0.211
247621Y3-024
Adder
0.11
964611AG1-324 GEN
Solar/Wind Harmer
0.538
964611AG1-324 GEN
Solar/Wind Harmer
0.239
270216AD2-079_GEN
Solar/Wind Harmer
0.274
970883AG2-550 GEN
Solar/Wind Harmer
4.511
970885AG2-551 GEN
Solar/Wind Harmer
1.049
960981AF2-389 GEN
Solar/Wind Harmer
0.677
957891AF2-083 GEN
Solar/Wind Harmer
1.511
961051AF2-396 GEN
Solar/Wind Harmer
7.096
961051AF2-396 GEN
Solar/Wind Harmer
3.301
270526AF1-158 GEN
Solar/Wind Harmer
2.018
270599AE1-208 GEN
Solar/Wind Harmer
3.619
270031AE2-169
Solar/Wind Harmer
3.619
24441505OLIV SLR
Solar/Wind Harmer
0.059
970321AG2-212 GEN
Solar/Wind Harmer
7.888
965681AG1-436 GEN
Solar/Wind Harmer
5.508
965791AG1-447 GEN
Solar/Wind Harmer
2.818
970825AG2-519 GEN
Solar/Wind Harmer
4.6
960441AF2-335 GEN
Solar/Wind Harmer
4.356
270383AD1-128 GEN
Solar/Wind Harmer
2.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.504
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.444
MECLTFEXP_MEC->PJM
CLTF
6.218
SIGELTFEXP_SIGE->PJM
CLTF
0.179
CPLELTFEXP_CPLE->PJM
CLTF
0.34
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.234
LAGNLTFEXP_LAGN->PJM
CLTF
5.039
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.304
TVALTFEXP_TVA->PJM
CLTF
2.34
NYPJM->LTFIMP_NY
CLTF
1.287
LGEELTFEXP_LGEE->PJM
CLTF
2.274
WECLTFEXP_WEC->PJM
CLTF
1.561
AG2-052LTFEXP_AG2-052->PJM
LTF
0.099
AH1-155LTFEXP_AH1-155->PJM
LTF
0.148

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-024_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-024_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.01 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5081.52
MW Contribution:10.63
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.158
23559001PLEAS1
50/50
6.365
270051AF1-062 GEN
50/50
11.843
270475AD2-096_GEN
50/50
7.165
970153AG2-106 GEN
Solar/Wind Harmer
17.953
961921AG1-034 GEN
Solar/Wind Harmer
15.612
24721905FLATG4
Adder
24.144
241955AC1-078 GEN
Solar/Wind Harmer
8.824
241974AD2-163_GEN2
Solar/Wind Harmer
2.334
942051AE2-217 GEN
Solar/Wind Harmer
21.08
960801AF2-371 GEN
Solar/Wind Harmer
2.95
964871AG1-351 GEN
Solar/Wind Harmer
2.037
970605AG2-385 GEN
Solar/Wind Harmer
6.25
942871AE2-306 GEN
Solar/Wind Harmer
1.049
270391AF1-285 GEN3
Solar/Wind Harmer
0.538
253338AC1-165 GEN
Solar/Wind Harmer
1.243
253333AC1-068 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.692
270273AD2-016 GEN
Solar/Wind Harmer
3.037
972173AH1-669 GEN
Solar/Wind Harmer
5.679
253415AE1-040 GEN
Solar/Wind Harmer
1.251
270291AC1-194 GEN
Solar/Wind Harmer
11.751
253303V4-073 C
Solar/Wind Harmer
0.127
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
957541AF2-048 GEN
Solar/Wind Harmer
1.724
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253406AD2-031_GEN
Solar/Wind Harmer
1.391
270491AE1-102 GEN2
Solar/Wind Harmer
1.407
971191AH1-055 GEN
Solar/Wind Harmer
23.759
253316AC1-085 GEN3
Solar/Wind Harmer
9.037
253433AC1-085 GEN1
Solar/Wind Harmer
5.737
946181AF1-283 GEN
Solar/Wind Harmer
14.025
270191TR4_S_V150
Solar/Wind Harmer
3.232
270247TR4_N_V136
Solar/Wind Harmer
0.916
959331AF2-224 GEN
Solar/Wind Harmer
10.775
965021AG1-366 GEN
Solar/Wind Harmer
2.506
270377AD1-106 GEN
Solar/Wind Harmer
6.65
958091AF2-103 GEN
Solar/Wind Harmer
0.174
270588AE1-091_GEN
Solar/Wind Harmer
11.804
944531AF1-118 GEN
Solar/Wind Harmer
37.541
270043AE2-236 GEN
Solar/Wind Harmer
5.893
971617AH1-308 GEN
Solar/Wind Harmer
6.198
270258AD1-119 GEN
Solar/Wind Harmer
2.97
25196608WSDLE5
Adder
9.114
962031AG1-047 GEN
Solar/Wind Harmer
3.214
957741AF2-068 GEN
Solar/Wind Harmer
15.949
252510AF1-249 C
Solar/Wind Harmer
0.444
25194608D.CRK4
Adder
1.747
270222AC2-111 GEN
Solar/Wind Harmer
8.657
970031AG2-029 GEN
Solar/Wind Harmer
31.849
270044AE2-322 C
Solar/Wind Harmer
1.394
270404AC1-167 GEN
Solar/Wind Harmer
1.161
24642205MAYFLWER
Adder
0.667
25196008MFTGT1
Adder
1.411
247604X1-042
Adder
0.435
274752CRETE EC ;2U
Adder
8.515
274753CRETE EC ;3U
Adder
8.515
274772LINCOLN ;3U
Adder
8.715
274724RIVER EC ;11
Adder
18.285
274802UNIV PARK;5U
Adder
5.997
24728705AND G3
Adder
8.251
24728505AND G1
Adder
3.945
274826FISK ;BP
Adder
11.256
274800UNIV PARK;3U
Adder
5.993
972038AH1-567 GEN2
Adder
0.375
972228AH1-698 GEN2
Adder
3.807
274676JOLIET 29;8U
Adder
30.322
274729ELWOOD EC;1P
Adder
16.844
274730ELWOOD EC;6P
Adder
16.844
274734ELWOOD EC;8P
Adder
16.844
274736ELWOOD EC;9P
Adder
16.844
274682WAUKEGAN ;7U
Adder
9.773
964991AG1-363 GEN
Solar/Wind Helper
5.152
316097T157 G90
Solar/Wind Helper
1.508
23750701CROSSCHOOL
Solar/Wind Helper
1.51
238118U2-030_1
Solar/Wind Helper
0.344
238127S14_GEN_2
Solar/Wind Helper
0.832
238148AE2-230_GEN2
Solar/Wind Helper
0.498
237080AD1-060 GEN
Solar/Wind Helper
0.343
237038AE2-054 C
Solar/Wind Helper
0.273
235062AE1-101 C1
Solar/Wind Helper
1.665
23779801AA1-109
Solar/Wind Helper
0.194
237048AF1-022 C
Solar/Wind Helper
0.179
223401AF1-299 GEN
Solar/Wind Helper
0.369
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.078
233930AB2-032 GEN
Solar/Wind Helper
0.382
233915AB1-141 GEN
Solar/Wind Helper
0.504
232422X3-066 FULL
Solar/Wind Helper
0.115
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.509
232428Y3-058 C
Solar/Wind Helper
0.339
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.117
233972AC1-094 C
Solar/Wind Helper
0.303
230511AF1-262
Solar/Wind Helper
0.015
316045AC1-158 PL2
Solar/Wind Helper
4.149
230434AG1-499 GEN
Solar/Wind Helper
0.231
962771AG1-126 GEN
Solar/Wind Harmer
41.173
270459AD2-067 GEN
Solar/Wind Harmer
10.252
961821AG1-024 GEN
Solar/Wind Harmer
10.408
270054AF2-122 C O1
Solar/Wind Harmer
3.995
972239AH1-704 GEN
Adder
2.671
270284AF1-227 GEN1
Solar/Wind Harmer
6.806
270286AF1-227 GEN2
Solar/Wind Harmer
2.518
270287AF1-227 GEN3
Solar/Wind Harmer
2.518
270520AE2-214 GEN
Solar/Wind Harmer
7.284
253383AE2-342_GEN
Solar/Wind Harmer
1.047
241973AD2-163_GEN1
Solar/Wind Harmer
2.334
943861AF1-054 GEN
Solar/Wind Harmer
4.494
943851AF1-053 GEN
Solar/Wind Harmer
2.172
945631AF1-228 GEN
Solar/Wind Harmer
5.47
270156DARBY CT1
Adder
10.432
270157DARBY CT2
Adder
10.407
270158DARBY CT3
Adder
10.24
270578AF1-285 GEN2
Solar/Wind Harmer
0.538
970689AG2-444 GEN
Solar/Wind Harmer
18.845
270432AC2-029 GEN
Solar/Wind Harmer
8.059
270302AB2-170 GEN
Solar/Wind Harmer
9.566
270317AD1-130_GEN
Solar/Wind Harmer
3.667
270269AC2-059
Solar/Wind Harmer
10.62
940611AE2-048 GEN
Solar/Wind Harmer
24.866
941391AE2-136 GEN
Solar/Wind Harmer
12.885
241972AD1-140 GEN
Solar/Wind Harmer
5.031
270340AC2-060 GEN
Solar/Wind Harmer
3.353
958581AF2-149 GEN
Solar/Wind Harmer
4.732
970179AG2-119 GEN
Solar/Wind Harmer
8.844
970879AG2-548 GEN
Solar/Wind Harmer
4.736
253372AE2-315 SEC3
Adder
2.071
253372AE2-315 SEC3
Adder
2.071
25306009OHH W.
Adder
3.141
253349AC2-067 GEN
Solar/Wind Harmer
5.421
253400AC2-068 GEN
Solar/Wind Harmer
2.18
957201AF2-014 GEN
Solar/Wind Harmer
4.91
270435AC2-044 GEN
Solar/Wind Harmer
2.165
965051AG1-369 GEN
Solar/Wind Harmer
5.38
965041AG1-368 GEN
Solar/Wind Harmer
10.749
247607V1-011 GEN
Solar/Wind Harmer
4.249
24729505KEY G4
Adder
6.948
963791AG1-232 GEN
Solar/Wind Harmer
14.455
971567AH1-282 GEN
Solar/Wind Harmer
16.053
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.846
270071AF1-092 GEN
Solar/Wind Harmer
16.048
971985AH1-537 GEN
Solar/Wind Harmer
19.051
958711AF2-162 GEN
Solar/Wind Harmer
1.079
270024AE2-089 GEN
Solar/Wind Harmer
5.004
965101AG1-375 GEN
Solar/Wind Harmer
10.653
270367AC2-061_GEN
Solar/Wind Harmer
3.388
971673AH1-337 GEN
Solar/Wind Harmer
4.893
971029AG2-637 GEN
Solar/Wind Harmer
15.954
252524AE2-267 GEN
Solar/Wind Harmer
1.677
25196408WSDLE3
Adder
9.382
25196308WSDLE2
Adder
9.3
25196208WSDLE1
Adder
9.277
25196708WSDLE6
Adder
9.254
25196508WSDLE4
Adder
9.021
270543AE2-219 C
Solar/Wind Harmer
5.445
961761AG1-017 GEN
Solar/Wind Harmer
0.455
945581AF1-223 GEN
Solar/Wind Harmer
4.819
944031AF1-071 GEN
Solar/Wind Harmer
1.067
270297AD1-101 GEN
Solar/Wind Harmer
2.953
25196108MFTGT2
Adder
1.605
25196108MFTGT2
Adder
1.491
274775LINCOLN ;6U
Adder
8.715
274776LINCOLN ;7U
Adder
8.715
274777LINCOLN ;8U
Adder
8.715
274814UNIV PK N;0U
Adder
5.208
274807UNIV PK N;3U
Adder
5.196
274805UNIV PK N;1U
Adder
5.174
274811UNIV PK N;7U
Adder
5.162
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.977
972227AH1-698 GEN1
Adder
2.681
274687WILL CNTY;4U
Adder
28.653
274687WILL CNTY;4U
Adder
28.653
274675JOLIET 29;7U
Adder
31.445
274675JOLIET 29;7U
Adder
30.322
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
316254AC1-120 GEN1
Solar/Wind Helper
1.062
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.311
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.023
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.577
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
202652Y1-033 WT C
Solar/Wind Helper
0.5
961301AF2-421 GEN
Solar/Wind Helper
0.441
963151AG1-164 GEN
Solar/Wind Helper
0.441
970513AG2-328 GEN
Solar/Wind Harmer
4.981
970517AG2-330 GEN
Solar/Wind Harmer
4.518
274731ELWOOD EC;2P
Adder
16.844
274733ELWOOD EC;3P
Adder
16.844
274735ELWOOD EC;4P
Adder
16.844
274728ELWOOD EC;5P
Adder
16.844
972203AH1-686 GEN
Adder
2.356
274746AC1-111 G10
Adder
5.705
274744AC1-111 GEN8
Adder
5.705
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.832
238152AF2-075_GEN
Solar/Wind Helper
0.709
238208AF1-136 C
Solar/Wind Helper
0.221
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.655
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.891
316415AF1-147_GEN2
Solar/Wind Helper
0.891
23750501ELLIOTTS
Solar/Wind Helper
0.644
959381AF2-229 GEN
Solar/Wind Helper
0.359
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.511
205932AD2-116_GEN
Solar/Wind Helper
0.511
205956AE1-196_GEN
Solar/Wind Helper
0.511
233935AB2-179 C
Solar/Wind Helper
1.273
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.962
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.046
964001AG1-254 GEN
Solar/Wind Helper
0.959
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.508
270119AB2-067 GEN1
50/50
7.1
270120AB2-067 GEN2
50/50
7.1
24318905MLG2
50/50
7.059
270471AD2-092_GEN
Solar/Wind Harmer
4.477
946101AF1-275 GEN
Solar/Wind Harmer
1.818
942861AE2-305 GEN
Solar/Wind Harmer
9.105
970077AG2-063 GEN
Solar/Wind Harmer
6.25
270224U2-072_GEN2
Solar/Wind Harmer
2.287
270227U2-072_GEN3
Solar/Wind Harmer
2.287
270228U2-072_GEN4
Solar/Wind Harmer
2.287
270231U2-072_GEN5
Solar/Wind Harmer
2.287
938701AE1-092 GEN
Solar/Wind Harmer
23.86
964601AG1-323 GEN
Solar/Wind Harmer
3.665
964601AG1-323 GEN
Solar/Wind Harmer
1.705
270518AE2-148 GEN
Solar/Wind Harmer
13.911
253378AE2-206_GEN
Solar/Wind Harmer
4.016
276820AF1-078_GEN
Solar/Wind Harmer
1.784
972159AH1-661 GEN
Adder
1.111
972269AH1-719 GEN
Adder
2.557
25326509SID D
Adder
1.455
971199AH1-059 GEN
Solar/Wind Harmer
4.424
241960AC2-195 GEN
Solar/Wind Harmer
3.074
970879AG2-548 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
6.788
971073AG2-665 GEN
Solar/Wind Harmer
4.736
25326109MON D
Adder
1.447
25322209TAIT E
Adder
10.679
25322209TAIT E
Adder
10.439
253370AE2-315 SEC1
Adder
2.189
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253394AE2-221_GEN
Solar/Wind Harmer
4.93
253398AE2-221_GEN2
Solar/Wind Harmer
4.93
246938BC-WTG3
Solar/Wind Harmer
4.31
246937BC-WTG2
Solar/Wind Harmer
4.237
253317AC1-085 GEN4
Solar/Wind Harmer
9.037
970611AG2-400 GEN
Solar/Wind Harmer
10.775
971231AH1-075 GEN
Solar/Wind Harmer
0.862
270007AE1-245 C
Solar/Wind Harmer
6.374
942801AE2-298 GEN
Solar/Wind Harmer
1.626
962581AG1-107 GEN
Solar/Wind Harmer
5.38
961491AF2-440 GEN
Solar/Wind Harmer
2.236
25183208HLCRTG
Solar/Wind Harmer
6.467
944541AF1-119 GEN
Solar/Wind Harmer
4.468
960971AF2-388 GEN
Solar/Wind Harmer
11.659
942221AE2-234 GEN
Solar/Wind Harmer
0.781
252519AF1-045_GEN
Solar/Wind Harmer
6.466
252516AE2-318_GEN
Solar/Wind Harmer
4.932
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.634
970885AG2-551 GEN
Solar/Wind Harmer
2.473
270201AC2-176 GEN
Solar/Wind Harmer
5.466
25194408D.CRK1
Adder
8.037
25194508D.CRK3
Adder
1.502
964611AG1-324 GEN
Solar/Wind Harmer
1.252
964611AG1-324 GEN
Solar/Wind Harmer
0.556
252509AD1-136 GEN
Solar/Wind Harmer
0.272
247620Y3-023
Adder
0.486
24728805RICHG1
Adder
3.981
24728905RICHG2
Adder
3.981
274770LINCOLN ;1U
Adder
8.715
274771LINCOLN ;2U
Adder
8.715
274808UNIV PK N;4U
Adder
5.14
274803UNIV PARK;6U
Adder
5.997
972259AH1-714 GEN
Adder
19.596
274674JOLIET 9 ;6U
Adder
15.776
274696ROCKY RD ;4P
Adder
11.59
274695ROCKY RD ;2P
Adder
11.323
274693ROCKY RD ;1P
Adder
11.211
274697ROCKY RD ;3P
Adder
3.076
23585401KL_K28_T16
Solar/Wind Helper
1.493
238120AE2-309 GEN
Solar/Wind Helper
0.528
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.703
238170AE2-226 GEN2
Solar/Wind Helper
0.703
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.445
237034AC2-136 C
Solar/Wind Helper
0.228
235063AE1-101 C2
Solar/Wind Helper
1.665
237001AB1-127_GEN
Solar/Wind Helper
0.443
23777801MSM_W1-116
Solar/Wind Helper
0.115
237025AB1-124 C
Solar/Wind Helper
0.165
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.72
20390526W1-045 C
Solar/Wind Helper
0.351
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.35
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.117
233944AB2-135 GEN
Solar/Wind Helper
0.591
233946AB2-136 GEN
Solar/Wind Helper
0.57
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.509
232410W1-006 C
Solar/Wind Helper
0.509
233939AC1-091 C
Solar/Wind Helper
0.351
233970AC1-092 C
Solar/Wind Helper
0.351
315651AD1-115 GEN
Solar/Wind Helper
0.787
316447AC1-158 HLD
Solar/Wind Helper
2.853
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.327
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.099
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
203955AF1-039 C O1
Solar/Wind Helper
0.33
970321AG2-212 GEN
Solar/Wind Harmer
4.981
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.291
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.099
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.082
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.786
270166AC1-044 GEN3
50/50
7.1
23559101PLEAS2
50/50
6.365
962761AG1-125 GEN
Solar/Wind Harmer
41.173
970149AG2-104 GEN
Solar/Wind Harmer
50.849
970155AG2-107 GEN
Solar/Wind Harmer
17.953
270349AD2-093_GEN
Solar/Wind Harmer
4.477
24721705FLATG2
Adder
24.144
270159DARBY CT4
Adder
10.266
970593AG2-378 GEN
Solar/Wind Harmer
2.315
270223U2-072_GEN1
Solar/Wind Harmer
2.287
270578AF1-285 GEN2
Solar/Wind Harmer
1.399
270391AF1-285 GEN3
Solar/Wind Harmer
1.399
253343AC1-166 GEN
Solar/Wind Harmer
1.243
253325AC1-069 GEN
Solar/Wind Harmer
1.199
270462AD2-086
Solar/Wind Harmer
7.958
971995AH1-542 GEN
Solar/Wind Harmer
12.515
270263AC1-001 GEN
Solar/Wind Harmer
1.179
25326309TAIT D
Adder
1.2
960071AF2-298 GEN
Solar/Wind Harmer
5.454
253370AE2-315 SEC1
Adder
2.189
253371AE2-315 SEC2
Adder
2.071
927014AC1-188 GEN
Solar/Wind Harmer
1.729
241813AF1-122_GEN
Solar/Wind Harmer
6.978
246936BC-WTG1
Solar/Wind Harmer
4.237
270489AE1-102 GEN1
Solar/Wind Harmer
1.407
965421AG1-410 GEN
Solar/Wind Harmer
32.464
960001AF2-291 GEN
Solar/Wind Harmer
3.264
253432AC1-085 GEN2
Solar/Wind Harmer
0.289
946171AF1-282 GEN
Solar/Wind Harmer
10.789
247521TR3_G114
Solar/Wind Harmer
3.623
270246TR4_N_V150
Solar/Wind Harmer
0.916
965011AG1-365 GEN
Solar/Wind Harmer
10.775
24695305TIMB G C
Solar/Wind Harmer
5.916
965651AG1-433 GEN
Solar/Wind Harmer
5.83
958861AF2-177 GEN
Solar/Wind Harmer
11.644
247536S-71 GEN
Solar/Wind Harmer
4.305
25194608D.CRK4
Adder
1.747
945371AF1-202 GEN
Solar/Wind Harmer
7.414
252507AC2-088 GEN
Solar/Wind Harmer
1.904
270063AE2-323 C
Solar/Wind Harmer
2.336
25196808ZIMRHP
Adder
80.055
24639705ELKHART HY
Adder
0.162
25196008MFTGT1
Adder
1.456
274751CRETE EC ;1U
Adder
8.515
274754CRETE EC ;4U
Adder
8.515
274773LINCOLN ;4U
Adder
8.715
274774LINCOLN ;5U
Adder
8.715
274723RIVER EC ;12
Adder
18.501
274812UNIV PK N;8U
Adder
5.162
24728605AND G2
Adder
3.945
274801UNIV PARK;4U
Adder
5.993
274676JOLIET 29;8U
Adder
31.445
274732ELWOOD EC;7P
Adder
16.844
274674JOLIET 9 ;6U
Adder
15.776
274745AC1-111 GEN9
Adder
5.705
970091AG2-072 GEN
Adder
78.03
316095T157 G97
Solar/Wind Helper
1.508
23583801GRNGAP
Solar/Wind Helper
5.618
238185AF2-356 C
Solar/Wind Helper
2.662
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.043
235531U2-073 GEN
Solar/Wind Helper
3.301
238117U2-030
Solar/Wind Helper
0.344
238147AE2-230_GEN1
Solar/Wind Helper
0.496
238149AF1-291A_GEN
Solar/Wind Helper
0.142
23751201ROTHROCK
Solar/Wind Helper
0.832
23562501BACKB
Solar/Wind Helper
1.017
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.498
23751101LEADS_P59
Solar/Wind Helper
1.424
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.034
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.347
223402AF1-300 C
Solar/Wind Helper
0.369
205917AD1-020 ES
Solar/Wind Helper
0.37
233918AB1-142 GEN
Solar/Wind Helper
0.504
233982AB2-133 GEN
Solar/Wind Helper
0.359
233994AC2-023 GEN
Solar/Wind Helper
0.965
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.509
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.359
230430AE1-229_GEN
Solar/Wind Helper
3.385
316044AC1-158 PL1
Solar/Wind Helper
1.296
316450AC1-158 RIC
Solar/Wind Helper
0.346
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
963161AG1-165 GEN
Solar/Wind Helper
0.441
970245AG2-165 GEN
Solar/Wind Harmer
4.981
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.671
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.268
MECLTFEXP_MEC->PJM
CLTF
15.978
SIGELTFEXP_SIGE->PJM
CLTF
0.507
CPLELTFEXP_CPLE->PJM
CLTF
0.647
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.418
LAGNLTFEXP_LAGN->PJM
CLTF
14.924
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.891
TVALTFEXP_TVA->PJM
CLTF
7.337
NYPJM->LTFIMP_NY
CLTF
4.819
LGEELTFEXP_LGEE->PJM
CLTF
6.781
WECLTFEXP_WEC->PJM
CLTF
3.842
AG2-052LTFEXP_AG2-052->PJM
LTF
0.241
AH1-155LTFEXP_AH1-155->PJM
LTF
0.361

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-025_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-025_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:133.21 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5051.2
MW Contribution:10.61
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.115
23559001PLEAS1
50/50
6.183
270051AF1-062 GEN
50/50
11.828
270475AD2-096_GEN
50/50
7.148
970153AG2-106 GEN
Solar/Wind Harmer
17.883
961921AG1-034 GEN
Solar/Wind Harmer
15.599
24721905FLATG4
Adder
23.989
241955AC1-078 GEN
Solar/Wind Harmer
8.811
241974AD2-163_GEN2
Solar/Wind Harmer
2.33
942051AE2-217 GEN
Solar/Wind Harmer
21.044
960801AF2-371 GEN
Solar/Wind Harmer
2.947
964871AG1-351 GEN
Solar/Wind Harmer
2.035
970605AG2-385 GEN
Solar/Wind Harmer
6.239
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.241
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.032
972173AH1-669 GEN
Solar/Wind Harmer
5.669
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270291AC1-194 GEN
Solar/Wind Harmer
11.736
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
970065AG2-057 GEN
Solar/Wind Harmer
1.09
957541AF2-048 GEN
Solar/Wind Harmer
1.72
270512AE1-227 GEN2
Solar/Wind Harmer
2.283
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
971191AH1-055 GEN
Solar/Wind Harmer
23.693
270377AD1-106 GEN
Solar/Wind Harmer
6.649
253316AC1-085 GEN3
Solar/Wind Harmer
9.014
253433AC1-085 GEN1
Solar/Wind Harmer
5.722
946181AF1-283 GEN
Solar/Wind Harmer
13.99
270191TR4_S_V150
Solar/Wind Harmer
3.224
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.746
965021AG1-366 GEN
Solar/Wind Harmer
2.499
958091AF2-103 GEN
Solar/Wind Harmer
0.173
270588AE1-091_GEN
Solar/Wind Harmer
11.789
944531AF1-118 GEN
Solar/Wind Harmer
37.432
270043AE2-236 GEN
Solar/Wind Harmer
5.876
270258AD1-119 GEN
Solar/Wind Harmer
2.963
971617AH1-308 GEN
Solar/Wind Harmer
6.181
25196608WSDLE5
Adder
9.089
962031AG1-047 GEN
Solar/Wind Harmer
3.205
252510AF1-249 C
Solar/Wind Harmer
0.443
957741AF2-068 GEN
Solar/Wind Harmer
15.904
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.632
970031AG2-029 GEN
Solar/Wind Harmer
31.759
270044AE2-322 C
Solar/Wind Harmer
1.391
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.434
274752CRETE EC ;2U
Adder
8.489
274753CRETE EC ;3U
Adder
8.489
274772LINCOLN ;3U
Adder
8.688
274724RIVER EC ;11
Adder
18.229
24728705AND G3
Adder
8.226
274802UNIV PARK;5U
Adder
5.978
24728505AND G1
Adder
3.933
274826FISK ;BP
Adder
11.221
274800UNIV PARK;3U
Adder
5.975
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.796
274676JOLIET 29;8U
Adder
30.228
274729ELWOOD EC;1P
Adder
16.792
274730ELWOOD EC;6P
Adder
16.792
274734ELWOOD EC;8P
Adder
16.792
274736ELWOOD EC;9P
Adder
16.792
274682WAUKEGAN ;7U
Adder
9.742
964991AG1-363 GEN
Solar/Wind Helper
5.141
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.505
238118U2-030_1
Solar/Wind Helper
0.342
238127S14_GEN_2
Solar/Wind Helper
0.829
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.178
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
270119AB2-067 GEN1
50/50
7.072
270120AB2-067 GEN2
50/50
7.072
24318905MLG2
50/50
7.067
270471AD2-092_GEN
Solar/Wind Harmer
4.467
946101AF1-275 GEN
Solar/Wind Harmer
1.815
942861AE2-305 GEN
Solar/Wind Harmer
9.088
970077AG2-063 GEN
Solar/Wind Harmer
6.239
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
962771AG1-126 GEN
Solar/Wind Harmer
41.012
972239AH1-704 GEN
Adder
2.683
270459AD2-067 GEN
Solar/Wind Harmer
10.243
961821AG1-024 GEN
Solar/Wind Harmer
10.399
270054AF2-122 C O1
Solar/Wind Harmer
3.993
270520AE2-214 GEN
Solar/Wind Harmer
7.274
270284AF1-227 GEN1
Solar/Wind Harmer
6.791
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.33
945631AF1-228 GEN
Solar/Wind Harmer
5.461
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.416
270157DARBY CT2
Adder
10.391
270158DARBY CT3
Adder
10.225
970689AG2-444 GEN
Solar/Wind Harmer
18.82
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.046
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.66
940611AE2-048 GEN
Solar/Wind Harmer
25.033
941391AE2-136 GEN
Solar/Wind Harmer
12.972
270269AC2-059
Solar/Wind Harmer
10.602
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.736
970179AG2-119 GEN
Solar/Wind Harmer
8.837
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.728
253372AE2-315 SEC3
Adder
2.066
253372AE2-315 SEC3
Adder
2.066
25306009OHH W.
Adder
3.134
253349AC2-067 GEN
Solar/Wind Harmer
5.408
253400AC2-068 GEN
Solar/Wind Harmer
2.175
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.366
965041AG1-368 GEN
Solar/Wind Harmer
10.722
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.059
966831AG1-554 GEN
Solar/Wind Harmer
1.279
971989AH1-539 GEN
Solar/Wind Harmer
13.833
24729505KEY G4
Adder
6.928
963791AG1-232 GEN
Solar/Wind Harmer
14.415
270071AF1-092 GEN
Solar/Wind Harmer
16.001
971985AH1-537 GEN
Solar/Wind Harmer
18.998
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.99
270367AC2-061_GEN
Solar/Wind Harmer
3.379
965101AG1-375 GEN
Solar/Wind Harmer
10.622
971673AH1-337 GEN
Solar/Wind Harmer
4.88
252524AE2-267 GEN
Solar/Wind Harmer
1.673
971029AG2-637 GEN
Solar/Wind Harmer
15.909
25196408WSDLE3
Adder
9.356
25196308WSDLE2
Adder
9.275
25196208WSDLE1
Adder
9.252
25196708WSDLE6
Adder
9.228
25196508WSDLE4
Adder
8.996
270543AE2-219 C
Solar/Wind Harmer
5.43
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.805
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.601
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.688
274776LINCOLN ;7U
Adder
8.688
274777LINCOLN ;8U
Adder
8.688
274814UNIV PK N;0U
Adder
5.192
274807UNIV PK N;3U
Adder
5.18
274805UNIV PK N;1U
Adder
5.158
274811UNIV PK N;7U
Adder
5.147
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.953
972227AH1-698 GEN1
Adder
2.673
274687WILL CNTY;4U
Adder
28.564
274687WILL CNTY;4U
Adder
28.564
274675JOLIET 29;7U
Adder
31.348
274675JOLIET 29;7U
Adder
30.228
274731ELWOOD EC;2P
Adder
16.792
274733ELWOOD EC;3P
Adder
16.792
274735ELWOOD EC;4P
Adder
16.792
274728ELWOOD EC;5P
Adder
16.792
972203AH1-686 GEN
Adder
2.344
274746AC1-111 G10
Adder
5.687
274744AC1-111 GEN8
Adder
5.687
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.829
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.651
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.64
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
233990AG1-397 GEN
Solar/Wind Helper
0.03
234033AF1-007_GEN
Solar/Wind Helper
7.028
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.957
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
270166AC1-044 GEN3
50/50
7.072
23559101PLEAS2
50/50
6.183
962761AG1-125 GEN
Solar/Wind Harmer
41.012
970149AG2-104 GEN
Solar/Wind Harmer
50.65
970155AG2-107 GEN
Solar/Wind Harmer
17.883
270349AD2-093_GEN
Solar/Wind Harmer
4.467
24721705FLATG2
Adder
23.989
270159DARBY CT4
Adder
10.25
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.241
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.502
270263AC1-001 GEN
Solar/Wind Harmer
1.177
25326309TAIT D
Adder
1.197
960071AF2-298 GEN
Solar/Wind Harmer
5.441
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.066
241813AF1-122_GEN
Solar/Wind Harmer
6.974
927014AC1-188 GEN
Solar/Wind Harmer
1.725
270510AE1-227 GEN1
Solar/Wind Harmer
2.689
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.386
960001AF2-291 GEN
Solar/Wind Harmer
3.255
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.761
247521TR3_G114
Solar/Wind Harmer
3.613
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.746
24695305TIMB G C
Solar/Wind Harmer
5.901
965651AG1-433 GEN
Solar/Wind Harmer
5.813
958861AF2-177 GEN
Solar/Wind Harmer
11.61
247536S-71 GEN
Solar/Wind Harmer
4.293
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.392
252507AC2-088 GEN
Solar/Wind Harmer
1.899
270063AE2-323 C
Solar/Wind Harmer
2.33
25196808ZIMRHP
Adder
79.831
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.489
274754CRETE EC ;4U
Adder
8.489
274773LINCOLN ;4U
Adder
8.688
274774LINCOLN ;5U
Adder
8.688
274723RIVER EC ;12
Adder
18.445
274812UNIV PK N;8U
Adder
5.147
24728605AND G2
Adder
3.933
274801UNIV PARK;4U
Adder
5.975
274676JOLIET 29;8U
Adder
31.348
274732ELWOOD EC;7P
Adder
16.792
274674JOLIET 9 ;6U
Adder
15.727
274745AC1-111 GEN9
Adder
5.687
970091AG2-072 GEN
Adder
77.755
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.606
238185AF2-356 C
Solar/Wind Helper
2.651
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.034
235531U2-073 GEN
Solar/Wind Helper
3.288
238117U2-030
Solar/Wind Helper
0.342
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.826
23562501BACKB
Solar/Wind Helper
1.01
237061AD1-155 GEN
Solar/Wind Helper
0.053
238221AF1-254 C O1
Solar/Wind Helper
0.275
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.41
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.728
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.824
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.886
972269AH1-719 GEN
Adder
2.575
972159AH1-661 GEN
Adder
1.116
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.428
241960AC2-195 GEN
Solar/Wind Harmer
3.072
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
6.777
971073AG2-665 GEN
Solar/Wind Harmer
4.728
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.654
25322209TAIT E
Adder
10.414
253370AE2-315 SEC1
Adder
2.184
971201AH1-060 GEN
Solar/Wind Harmer
2.179
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
9.014
970611AG2-400 GEN
Solar/Wind Harmer
10.746
270007AE1-245 C
Solar/Wind Harmer
6.359
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.366
961491AF2-440 GEN
Solar/Wind Harmer
2.23
25183208HLCRTG
Solar/Wind Harmer
6.45
944541AF1-119 GEN
Solar/Wind Harmer
4.455
960971AF2-388 GEN
Solar/Wind Harmer
11.625
942221AE2-234 GEN
Solar/Wind Harmer
0.779
252519AF1-045_GEN
Solar/Wind Harmer
6.448
252516AE2-318_GEN
Solar/Wind Harmer
4.919
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.605
970885AG2-551 GEN
Solar/Wind Harmer
2.466
270201AC2-176 GEN
Solar/Wind Harmer
5.45
25194408D.CRK1
Adder
8.014
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.249
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.969
24728905RICHG2
Adder
3.969
274770LINCOLN ;1U
Adder
8.688
274771LINCOLN ;2U
Adder
8.688
274808UNIV PK N;4U
Adder
5.124
274803UNIV PARK;6U
Adder
5.978
972259AH1-714 GEN
Adder
19.535
274674JOLIET 9 ;6U
Adder
15.727
274696ROCKY RD ;4P
Adder
11.554
274695ROCKY RD ;2P
Adder
11.287
274693ROCKY RD ;1P
Adder
11.176
274697ROCKY RD ;3P
Adder
3.066
23585401KL_K28_T16
Solar/Wind Helper
1.485
238120AE2-309 GEN
Solar/Wind Helper
0.526
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.444
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.728
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
232434Z2-077 GEN
Solar/Wind Helper
0.127
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.06
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.728
970517AG2-330 GEN
Solar/Wind Harmer
3.381
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.501
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.265
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.153
MECLTFEXP_MEC->PJM
CLTF
15.925
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CPLELTFEXP_CPLE->PJM
CLTF
0.632
CBM West 2LTFEXP_CBM-W2->PJM
CBM
113.005
LAGNLTFEXP_LAGN->PJM
CLTF
14.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.83
TVALTFEXP_TVA->PJM
CLTF
7.306
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.759
WECLTFEXP_WEC->PJM
CLTF
3.83
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-015_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-015_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-014_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-014_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:132.9 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5039.69
MW Contribution:10.6
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.098
23559001PLEAS1
50/50
6.112
270051AF1-062 GEN
50/50
11.831
23684201S70BUS2
50/50
0.171
270475AD2-096_GEN
50/50
7.147
970153AG2-106 GEN
Solar/Wind Harmer
17.867
961921AG1-034 GEN
Solar/Wind Harmer
15.607
241955AC1-078 GEN
Solar/Wind Harmer
8.813
24721905FLATG4
Adder
23.946
241974AD2-163_GEN2
Solar/Wind Harmer
2.331
942051AE2-217 GEN
Solar/Wind Harmer
21.048
960801AF2-371 GEN
Solar/Wind Harmer
2.948
964871AG1-351 GEN
Solar/Wind Harmer
2.036
970605AG2-385 GEN
Solar/Wind Harmer
6.24
942871AE2-306 GEN
Solar/Wind Harmer
1.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.537
253338AC1-165 GEN
Solar/Wind Harmer
1.242
253333AC1-068 GEN
Solar/Wind Harmer
1.197
270485AE1-090_GEN
Solar/Wind Harmer
0.69
270273AD2-016 GEN
Solar/Wind Harmer
3.033
972173AH1-669 GEN
Solar/Wind Harmer
5.671
270291AC1-194 GEN
Solar/Wind Harmer
11.744
253415AE1-040 GEN
Solar/Wind Harmer
1.248
270512AE1-227 GEN2
Solar/Wind Harmer
2.315
970065AG2-057 GEN
Solar/Wind Harmer
1.09
253303V4-073 C
Solar/Wind Harmer
0.126
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
957541AF2-048 GEN
Solar/Wind Harmer
1.721
253406AD2-031_GEN
Solar/Wind Harmer
1.388
270491AE1-102 GEN2
Solar/Wind Harmer
1.404
270377AD1-106 GEN
Solar/Wind Harmer
6.655
971191AH1-055 GEN
Solar/Wind Harmer
23.692
253316AC1-085 GEN3
Solar/Wind Harmer
9.013
253433AC1-085 GEN1
Solar/Wind Harmer
5.721
946181AF1-283 GEN
Solar/Wind Harmer
13.988
270191TR4_S_V150
Solar/Wind Harmer
3.223
270247TR4_N_V136
Solar/Wind Harmer
0.914
959331AF2-224 GEN
Solar/Wind Harmer
10.743
965021AG1-366 GEN
Solar/Wind Harmer
2.498
270588AE1-091_GEN
Solar/Wind Harmer
11.792
958091AF2-103 GEN
Solar/Wind Harmer
0.173
944531AF1-118 GEN
Solar/Wind Harmer
37.418
270043AE2-236 GEN
Solar/Wind Harmer
5.874
270258AD1-119 GEN
Solar/Wind Harmer
2.962
971617AH1-308 GEN
Solar/Wind Harmer
6.179
25196608WSDLE5
Adder
9.087
252510AF1-249 C
Solar/Wind Harmer
0.443
962031AG1-047 GEN
Solar/Wind Harmer
3.204
957741AF2-068 GEN
Solar/Wind Harmer
15.899
25194608D.CRK4
Adder
1.742
270222AC2-111 GEN
Solar/Wind Harmer
8.63
970031AG2-029 GEN
Solar/Wind Harmer
31.748
270044AE2-322 C
Solar/Wind Harmer
1.39
270404AC1-167 GEN
Solar/Wind Harmer
1.158
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.406
247604X1-042
Adder
0.433
274752CRETE EC ;2U
Adder
8.485
274753CRETE EC ;3U
Adder
8.485
274772LINCOLN ;3U
Adder
8.684
274724RIVER EC ;11
Adder
18.221
24728705AND G3
Adder
8.223
274802UNIV PARK;5U
Adder
5.976
24728505AND G1
Adder
3.932
274826FISK ;BP
Adder
11.216
274800UNIV PARK;3U
Adder
5.972
972038AH1-567 GEN2
Adder
0.374
972228AH1-698 GEN2
Adder
3.794
274676JOLIET 29;8U
Adder
30.215
274729ELWOOD EC;1P
Adder
16.784
962771AG1-126 GEN
Solar/Wind Harmer
40.976
972239AH1-704 GEN
Adder
2.69
270054AF2-122 C O1
Solar/Wind Harmer
3.996
270459AD2-067 GEN
Solar/Wind Harmer
10.248
961821AG1-024 GEN
Solar/Wind Harmer
10.404
270520AE2-214 GEN
Solar/Wind Harmer
7.276
270284AF1-227 GEN1
Solar/Wind Harmer
6.79
270286AF1-227 GEN2
Solar/Wind Harmer
2.512
270287AF1-227 GEN3
Solar/Wind Harmer
2.512
253383AE2-342_GEN
Solar/Wind Harmer
1.045
241973AD2-163_GEN1
Solar/Wind Harmer
2.331
945631AF1-228 GEN
Solar/Wind Harmer
5.463
943861AF1-054 GEN
Solar/Wind Harmer
4.486
943851AF1-053 GEN
Solar/Wind Harmer
2.168
270156DARBY CT1
Adder
10.419
270157DARBY CT2
Adder
10.393
270158DARBY CT3
Adder
10.228
970689AG2-444 GEN
Solar/Wind Harmer
18.827
270578AF1-285 GEN2
Solar/Wind Harmer
0.537
270432AC2-029 GEN
Solar/Wind Harmer
8.049
940611AE2-048 GEN
Solar/Wind Harmer
25.14
941391AE2-136 GEN
Solar/Wind Harmer
13.027
270302AB2-170 GEN
Solar/Wind Harmer
9.546
270317AD1-130_GEN
Solar/Wind Harmer
3.659
270269AC2-059
Solar/Wind Harmer
10.605
241972AD1-140 GEN
Solar/Wind Harmer
5.021
958581AF2-149 GEN
Solar/Wind Harmer
4.743
970179AG2-119 GEN
Solar/Wind Harmer
8.842
270340AC2-060 GEN
Solar/Wind Harmer
3.346
970879AG2-548 GEN
Solar/Wind Harmer
4.73
253372AE2-315 SEC3
Adder
2.065
253372AE2-315 SEC3
Adder
2.065
25306009OHH W.
Adder
3.133
253349AC2-067 GEN
Solar/Wind Harmer
5.407
253400AC2-068 GEN
Solar/Wind Harmer
2.174
957201AF2-014 GEN
Solar/Wind Harmer
4.898
270435AC2-044 GEN
Solar/Wind Harmer
2.16
965051AG1-369 GEN
Solar/Wind Harmer
5.365
965041AG1-368 GEN
Solar/Wind Harmer
10.719
247607V1-011 GEN
Solar/Wind Harmer
4.239
971567AH1-282 GEN
Solar/Wind Harmer
16.075
966831AG1-554 GEN
Solar/Wind Harmer
1.28
971989AH1-539 GEN
Solar/Wind Harmer
13.838
24729505KEY G4
Adder
6.925
963791AG1-232 GEN
Solar/Wind Harmer
14.411
270071AF1-092 GEN
Solar/Wind Harmer
15.995
971985AH1-537 GEN
Solar/Wind Harmer
18.996
958711AF2-162 GEN
Solar/Wind Harmer
1.076
270024AE2-089 GEN
Solar/Wind Harmer
4.988
270367AC2-061_GEN
Solar/Wind Harmer
3.378
965101AG1-375 GEN
Solar/Wind Harmer
10.618
971673AH1-337 GEN
Solar/Wind Harmer
4.878
252524AE2-267 GEN
Solar/Wind Harmer
1.672
25196408WSDLE3
Adder
9.354
25196308WSDLE2
Adder
9.273
25196208WSDLE1
Adder
9.25
25196708WSDLE6
Adder
9.227
25196508WSDLE4
Adder
8.994
971029AG2-637 GEN
Solar/Wind Harmer
15.905
270543AE2-219 C
Solar/Wind Harmer
5.429
961761AG1-017 GEN
Solar/Wind Harmer
0.454
945581AF1-223 GEN
Solar/Wind Harmer
4.803
270297AD1-101 GEN
Solar/Wind Harmer
2.947
944031AF1-071 GEN
Solar/Wind Harmer
1.064
25196108MFTGT2
Adder
1.6
25196108MFTGT2
Adder
1.486
274775LINCOLN ;6U
Adder
8.684
274776LINCOLN ;7U
Adder
8.684
274777LINCOLN ;8U
Adder
8.684
274814UNIV PK N;0U
Adder
5.189
274807UNIV PK N;3U
Adder
5.178
274805UNIV PK N;1U
Adder
5.156
274811UNIV PK N;7U
Adder
5.144
972037AH1-567 GEN1
Adder
0.188
274827FISK ;RP
Adder
7.949
972227AH1-698 GEN1
Adder
2.671
274687WILL CNTY;4U
Adder
28.551
274687WILL CNTY;4U
Adder
28.551
274675JOLIET 29;7U
Adder
31.334
274675JOLIET 29;7U
Adder
30.215
274731ELWOOD EC;2P
Adder
16.784
274733ELWOOD EC;3P
Adder
16.784
274735ELWOOD EC;4P
Adder
16.784
274728ELWOOD EC;5P
Adder
16.784
972203AH1-686 GEN
Adder
2.341
274746AC1-111 G10
Adder
5.685
274744AC1-111 GEN8
Adder
5.685
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.826
238152AF2-075_GEN
Solar/Wind Helper
0.708
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.65
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.889
316415AF1-147_GEN2
Solar/Wind Helper
0.889
23750501ELLIOTTS
Solar/Wind Helper
0.637
959381AF2-229 GEN
Solar/Wind Helper
0.358
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.182
205943AE1-185 GEN
Solar/Wind Helper
0.51
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.27
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.959
234033AF1-007_GEN
Solar/Wind Helper
7.028
233990AG1-397 GEN
Solar/Wind Helper
0.03
232432Z2-076 GEN
Solar/Wind Helper
0.067
964001AG1-254 GEN
Solar/Wind Helper
0.956
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.5
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.097
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.137
270119AB2-067 GEN1
50/50
7.063
270120AB2-067 GEN2
50/50
7.063
24318905MLG2
50/50
7.074
270471AD2-092_GEN
Solar/Wind Harmer
4.466
946101AF1-275 GEN
Solar/Wind Harmer
1.816
942861AE2-305 GEN
Solar/Wind Harmer
9.089
970077AG2-063 GEN
Solar/Wind Harmer
6.24
270224U2-072_GEN2
Solar/Wind Harmer
2.282
270227U2-072_GEN3
Solar/Wind Harmer
2.282
270228U2-072_GEN4
Solar/Wind Harmer
2.282
270231U2-072_GEN5
Solar/Wind Harmer
2.282
938701AE1-092 GEN
Solar/Wind Harmer
23.829
964601AG1-323 GEN
Solar/Wind Harmer
3.66
964601AG1-323 GEN
Solar/Wind Harmer
1.702
270518AE2-148 GEN
Solar/Wind Harmer
13.889
972269AH1-719 GEN
Adder
2.587
972159AH1-661 GEN
Adder
1.119
253378AE2-206_GEN
Solar/Wind Harmer
4.007
276820AF1-078_GEN
Solar/Wind Harmer
1.78
971199AH1-059 GEN
Solar/Wind Harmer
4.433
241960AC2-195 GEN
Solar/Wind Harmer
3.073
25326509SID D
Adder
1.452
970879AG2-548 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
6.78
971073AG2-665 GEN
Solar/Wind Harmer
4.73
25326109MON D
Adder
1.444
25322209TAIT E
Adder
10.653
25322209TAIT E
Adder
10.414
971201AH1-060 GEN
Solar/Wind Harmer
2.181
253370AE2-315 SEC1
Adder
2.184
253394AE2-221_GEN
Solar/Wind Harmer
4.918
253398AE2-221_GEN2
Solar/Wind Harmer
4.918
246938BC-WTG3
Solar/Wind Harmer
4.299
246937BC-WTG2
Solar/Wind Harmer
4.226
971231AH1-075 GEN
Solar/Wind Harmer
0.862
253317AC1-085 GEN4
Solar/Wind Harmer
9.013
970611AG2-400 GEN
Solar/Wind Harmer
10.743
270007AE1-245 C
Solar/Wind Harmer
6.358
942801AE2-298 GEN
Solar/Wind Harmer
1.622
962581AG1-107 GEN
Solar/Wind Harmer
5.365
961491AF2-440 GEN
Solar/Wind Harmer
2.229
25183208HLCRTG
Solar/Wind Harmer
6.449
944541AF1-119 GEN
Solar/Wind Harmer
4.453
960971AF2-388 GEN
Solar/Wind Harmer
11.621
942221AE2-234 GEN
Solar/Wind Harmer
0.778
252519AF1-045_GEN
Solar/Wind Harmer
6.447
252516AE2-318_GEN
Solar/Wind Harmer
4.918
247621Y3-024
Adder
0.256
970883AG2-550 GEN
Solar/Wind Harmer
10.602
970885AG2-551 GEN
Solar/Wind Harmer
2.465
270201AC2-176 GEN
Solar/Wind Harmer
5.449
25194408D.CRK1
Adder
8.013
25194508D.CRK3
Adder
1.498
964611AG1-324 GEN
Solar/Wind Harmer
1.248
964611AG1-324 GEN
Solar/Wind Harmer
0.554
252509AD1-136 GEN
Solar/Wind Harmer
0.271
247620Y3-023
Adder
0.484
24728805RICHG1
Adder
3.968
24728905RICHG2
Adder
3.968
274770LINCOLN ;1U
Adder
8.684
274771LINCOLN ;2U
Adder
8.684
20675128HRM_W1-127
Solar/Wind Helper
0.03
209116AE2-175 GEN
Solar/Wind Helper
1.781
270166AC1-044 GEN3
50/50
7.063
23559101PLEAS2
50/50
6.112
23684101S70BUS1
50/50
0.168
962761AG1-125 GEN
Solar/Wind Harmer
40.976
970149AG2-104 GEN
Solar/Wind Harmer
50.605
970155AG2-107 GEN
Solar/Wind Harmer
17.867
270349AD2-093_GEN
Solar/Wind Harmer
4.466
24721705FLATG2
Adder
23.946
270159DARBY CT4
Adder
10.253
970593AG2-378 GEN
Solar/Wind Harmer
2.311
270223U2-072_GEN1
Solar/Wind Harmer
2.282
270578AF1-285 GEN2
Solar/Wind Harmer
1.396
270391AF1-285 GEN3
Solar/Wind Harmer
1.396
253343AC1-166 GEN
Solar/Wind Harmer
1.242
253325AC1-069 GEN
Solar/Wind Harmer
1.197
270462AD2-086
Solar/Wind Harmer
7.941
971995AH1-542 GEN
Solar/Wind Harmer
12.507
270263AC1-001 GEN
Solar/Wind Harmer
1.177
270510AE1-227 GEN1
Solar/Wind Harmer
2.727
25326309TAIT D
Adder
1.197
241813AF1-122_GEN
Solar/Wind Harmer
6.978
960071AF2-298 GEN
Solar/Wind Harmer
5.44
253370AE2-315 SEC1
Adder
2.184
253371AE2-315 SEC2
Adder
2.065
927014AC1-188 GEN
Solar/Wind Harmer
1.725
246936BC-WTG1
Solar/Wind Harmer
4.226
270489AE1-102 GEN1
Solar/Wind Harmer
1.404
965421AG1-410 GEN
Solar/Wind Harmer
32.379
960001AF2-291 GEN
Solar/Wind Harmer
3.256
253432AC1-085 GEN2
Solar/Wind Harmer
0.288
946171AF1-282 GEN
Solar/Wind Harmer
10.76
247521TR3_G114
Solar/Wind Harmer
3.612
270246TR4_N_V150
Solar/Wind Harmer
0.914
965011AG1-365 GEN
Solar/Wind Harmer
10.743
24695305TIMB G C
Solar/Wind Harmer
5.899
965651AG1-433 GEN
Solar/Wind Harmer
5.811
958861AF2-177 GEN
Solar/Wind Harmer
11.606
247536S-71 GEN
Solar/Wind Harmer
4.292
25194608D.CRK4
Adder
1.742
945371AF1-202 GEN
Solar/Wind Harmer
7.39
252507AC2-088 GEN
Solar/Wind Harmer
1.898
270063AE2-323 C
Solar/Wind Harmer
2.329
25196808ZIMRHP
Adder
79.816
24639705ELKHART HY
Adder
0.161
25196008MFTGT1
Adder
1.452
274751CRETE EC ;1U
Adder
8.485
274754CRETE EC ;4U
Adder
8.485
274773LINCOLN ;4U
Adder
8.684
274774LINCOLN ;5U
Adder
8.684
274723RIVER EC ;12
Adder
18.437
274812UNIV PK N;8U
Adder
5.144
24728605AND G2
Adder
3.932
274801UNIV PARK;4U
Adder
5.972
274676JOLIET 29;8U
Adder
31.334
274732ELWOOD EC;7P
Adder
16.784
274674JOLIET 9 ;6U
Adder
15.72
274745AC1-111 GEN9
Adder
5.685
970091AG2-072 GEN
Adder
77.715
316095T157 G97
Solar/Wind Helper
1.505
23583801GRNGAP
Solar/Wind Helper
5.607
238185AF2-356 C
Solar/Wind Helper
2.642
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.025
235531U2-073 GEN
Solar/Wind Helper
3.278
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
237061AD1-155 GEN
Solar/Wind Helper
0.053
23751201ROTHROCK
Solar/Wind Helper
0.819
238221AF1-254 C O1
Solar/Wind Helper
0.275
23562501BACKB
Solar/Wind Helper
1.001
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.388
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.033
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.368
205917AD1-020 ES
Solar/Wind Helper
0.369
233982AB2-133 GEN
Solar/Wind Helper
0.358
233918AB1-142 GEN
Solar/Wind Helper
0.503
233994AC2-023 GEN
Solar/Wind Helper
0.962
274730ELWOOD EC;6P
Adder
16.784
274734ELWOOD EC;8P
Adder
16.784
274736ELWOOD EC;9P
Adder
16.784
274682WAUKEGAN ;7U
Adder
9.459
964991AG1-363 GEN
Solar/Wind Helper
5.14
316097T157 G90
Solar/Wind Helper
1.505
23750701CROSSCHOOL
Solar/Wind Helper
1.501
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.826
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.661
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.368
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.077
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.503
232422X3-066 FULL
Solar/Wind Helper
0.114
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.262
232404W1-003 C
Solar/Wind Helper
0.508
232428Y3-058 C
Solar/Wind Helper
0.338
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.233
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.303
316045AC1-158 PL2
Solar/Wind Helper
4.142
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
316254AC1-120 GEN1
Solar/Wind Helper
1.061
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.496
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.573
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.03
970513AG2-328 GEN
Solar/Wind Harmer
3.726
970517AG2-330 GEN
Solar/Wind Harmer
3.379
274808UNIV PK N;4U
Adder
5.122
274803UNIV PARK;6U
Adder
5.976
972259AH1-714 GEN
Adder
19.527
274674JOLIET 9 ;6U
Adder
15.72
274696ROCKY RD ;4P
Adder
11.549
274695ROCKY RD ;2P
Adder
11.282
274693ROCKY RD ;1P
Adder
11.171
274697ROCKY RD ;3P
Adder
3.065
23585401KL_K28_T16
Solar/Wind Helper
1.478
238120AE2-309 GEN
Solar/Wind Helper
0.524
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.702
238170AE2-226 GEN2
Solar/Wind Helper
0.702
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237034AC2-136 C
Solar/Wind Helper
0.227
237002AB1-128_GEN
Solar/Wind Helper
0.443
235063AE1-101 C2
Solar/Wind Helper
1.661
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.715
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.344
233933AB2-153 GEN
Solar/Wind Helper
0.233
232424Y1-079 C
Solar/Wind Helper
0.116
233944AB2-135 GEN
Solar/Wind Helper
0.589
233946AB2-136 GEN
Solar/Wind Helper
0.569
234036AF2-325 C
Solar/Wind Helper
0.042
233901CHERRYDALE C
Solar/Wind Helper
0.233
232408W1-005 C
Solar/Wind Helper
0.508
232410W1-006 C
Solar/Wind Helper
0.508
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.848
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.169
20674928WA_W3-044
Solar/Wind Helper
0.098
964851AG1-348 GEN
Solar/Wind Helper
0.081
20676228FRD_X1-012
Solar/Wind Helper
0.092
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.045
211065PSPA IPP
Solar/Wind Helper
0.152
211065PSPA IPP
Solar/Wind Helper
0.152
970321AG2-212 GEN
Solar/Wind Harmer
3.726
233996TM1833_GEN
Solar/Wind Helper
0.262
233997TMININ_4.2
Solar/Wind Helper
0.262
232406W1-004 FULL
Solar/Wind Helper
0.508
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.233
233971AC1-093 C
Solar/Wind Helper
0.358
316044AC1-158 PL1
Solar/Wind Helper
1.294
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.376
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.111
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.012
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.354
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
970245AG2-165 GEN
Solar/Wind Harmer
3.726
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.216
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.135
MECLTFEXP_MEC->PJM
CLTF
15.918
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CPLELTFEXP_CPLE->PJM
CLTF
0.627
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.944
LAGNLTFEXP_LAGN->PJM
CLTF
14.855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.816
TVALTFEXP_TVA->PJM
CLTF
7.302
NYPJM->LTFIMP_NY
CLTF
4.803
LGEELTFEXP_LGEE->PJM
CLTF
6.756
WECLTFEXP_WEC->PJM
CLTF
3.828
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.36

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-007A_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-007A_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.92 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:5002.28
MW Contribution:7.39
Bus #Bus NameTypeMW Contribution
24318805MLG1
50/50
10.095
23559001PLEAS1
50/50
6.1
270051AF1-062 GEN
50/50
11.821
270475AD2-096_GEN
50/50
7.141
970153AG2-106 GEN
Solar/Wind Harmer
22.046
961921AG1-034 GEN
Solar/Wind Harmer
7.615
241955AC1-078 GEN
Solar/Wind Harmer
0.007
24721905FLATG4
Adder
23.918
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.671
970605AG2-385 GEN
Solar/Wind Harmer
4.899
270391AF1-285 GEN3
Solar/Wind Harmer
0.536
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.821
972173AH1-669 GEN
Solar/Wind Harmer
3.952
270291AC1-194 GEN
Solar/Wind Harmer
6.106
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270512AE1-227 GEN2
Solar/Wind Harmer
1.963
970065AG2-057 GEN
Solar/Wind Harmer
0.76
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
253406AD2-031_GEN
Solar/Wind Harmer
0.563
970191AG2-125 GEN
Solar/Wind Harmer
1.945
270491AE1-102 GEN2
Solar/Wind Harmer
0.979
270377AD1-106 GEN
Solar/Wind Harmer
2.855
971191AH1-055 GEN
Solar/Wind Harmer
19.26
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.749
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.048
959331AF2-224 GEN
Solar/Wind Harmer
5.242
965021AG1-366 GEN
Solar/Wind Harmer
2.496
962771AG1-126 GEN
Solar/Wind Harmer
34.524
270588AE1-091_GEN
Solar/Wind Harmer
5.845
944531AF1-118 GEN
Solar/Wind Harmer
33.395
270043AE2-236 GEN
Solar/Wind Harmer
4.777
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
6.173
25196608WSDLE5
Adder
9.077
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
252510AF1-249 C
Solar/Wind Harmer
0.057
957741AF2-068 GEN
Solar/Wind Harmer
11.081
25194608D.CRK4
Adder
1.74
270222AC2-111 GEN
Solar/Wind Harmer
3.739
970031AG2-029 GEN
Solar/Wind Harmer
4.795
270404AC1-167 GEN
Solar/Wind Harmer
0.003
970513AG2-328 GEN
Solar/Wind Harmer
3.191
970517AG2-330 GEN
Solar/Wind Harmer
19.146
970349AG2-230 GEN
Solar/Wind Harmer
11.025
946031AF1-268 GEN
Solar/Wind Harmer
6.992
958821AF2-173 GEN
Solar/Wind Harmer
10.273
270004AE1-209 GEN
Solar/Wind Harmer
1.59
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.804
970291AG2-192 GEN
Solar/Wind Harmer
0.731
247642Z2-115 C
Solar/Wind Harmer
0.003
945111AF1-176 GEN
Solar/Wind Harmer
5.919
24642205MAYFLWER
Adder
0.665
25196008MFTGT1
Adder
1.405
270356AE2-297 GEN
Solar/Wind Harmer
0.01
24441205WTRV SLR C
Solar/Wind Harmer
0
247604X1-042
Adder
0.433
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970217AG2-149 GEN
Solar/Wind Harmer
6.268
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.196
970243AG2-164 GEN
Solar/Wind Harmer
4.205
970519AG2-331 GEN
Solar/Wind Harmer
18.687
970699AG2-449 GEN
Solar/Wind Harmer
1.797
274752CRETE EC ;2U
Adder
8.477
274753CRETE EC ;3U
Adder
8.477
958171AF2-111 GEN
Solar/Wind Harmer
17.94
274772LINCOLN ;3U
Adder
8.676
274724RIVER EC ;11
Adder
18.203
972167AH1-666 GEN
Solar/Wind Harmer
5.717
24728705AND G3
Adder
8.214
274802UNIV PARK;5U
Adder
5.97
24728505AND G1
Adder
3.927
276806AD2-047 C O1
Solar/Wind Harmer
4.047
970941AG2-585 GEN
Solar/Wind Harmer
8.927
274826FISK ;BP
Adder
11.205
274800UNIV PARK;3U
Adder
5.966
972038AH1-567 GEN2
Adder
0.373
972228AH1-698 GEN2
Adder
3.79
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
23.303
274676JOLIET 29;8U
Adder
30.185
276893AG1-478 C
Solar/Wind Harmer
0.282
274729ELWOOD EC;1P
Adder
16.768
274730ELWOOD EC;6P
Adder
16.768
274734ELWOOD EC;8P
Adder
16.768
274736ELWOOD EC;9P
Adder
16.768
943121AE2-341 GEN
Solar/Wind Harmer
11.888
943591AF1-030 GEN
Solar/Wind Harmer
7.906
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
270541AE2-072 C
Solar/Wind Harmer
0.009
274682WAUKEGAN ;7U
Adder
9.728
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
5.136
316097T157 G90
Solar/Wind Helper
1.504
23750701CROSSCHOOL
Solar/Wind Helper
1.502
238118U2-030_1
Solar/Wind Helper
0.341
238127S14_GEN_2
Solar/Wind Helper
0.827
238148AE2-230_GEN2
Solar/Wind Helper
0.497
237080AD1-060 GEN
Solar/Wind Helper
0.342
237038AE2-054 C
Solar/Wind Helper
0.272
235062AE1-101 C1
Solar/Wind Helper
1.659
23779801AA1-109
Solar/Wind Helper
0.193
237048AF1-022 C
Solar/Wind Helper
0.177
223401AF1-299 GEN
Solar/Wind Helper
0.367
316006AB2-029 C
Solar/Wind Helper
0.117
966131AG1-482 GEN
Solar/Wind Helper
0.137
233930AB2-032 GEN
Solar/Wind Helper
0.381
233915AB1-141 GEN
Solar/Wind Helper
0.502
232422X3-066 FULL
Solar/Wind Helper
0.114
232428Y3-058 C
Solar/Wind Helper
0.338
232426Y1-080 FULL
Solar/Wind Helper
0.039
233964AF2-378 GEN
Solar/Wind Helper
0.042
233998TM1NIN_3.36
Solar/Wind Helper
0.261
232404W1-003 C
Solar/Wind Helper
0.507
232434Z2-077 GEN
Solar/Wind Helper
0.127
233954AC2-188 GEN
Solar/Wind Helper
0.232
233950AC2-186 GEN
Solar/Wind Helper
0.116
233972AC1-094 C
Solar/Wind Helper
0.302
316045AC1-158 PL2
Solar/Wind Helper
4.138
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.23
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.06
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.131
20720728JCB_W1-129
Solar/Wind Helper
0.057
972239AH1-704 GEN
Adder
2.689
270054AF2-122 C O1
Solar/Wind Harmer
0.007
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
5.077
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.011
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.127
943851AF1-053 GEN
Solar/Wind Harmer
2.166
270156DARBY CT1
Adder
10.409
270157DARBY CT2
Adder
10.383
270158DARBY CT3
Adder
10.218
970689AG2-444 GEN
Solar/Wind Harmer
16.436
270578AF1-285 GEN2
Solar/Wind Harmer
0.536
270432AC2-029 GEN
Solar/Wind Harmer
3.553
940611AE2-048 GEN
Solar/Wind Harmer
19.602
941391AE2-136 GEN
Solar/Wind Harmer
11.042
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.117
270269AC2-059
Solar/Wind Harmer
0.005
241972AD1-140 GEN
Solar/Wind Harmer
0.854
970179AG2-119 GEN
Solar/Wind Harmer
6.883
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.898
253372AE2-315 SEC3
Adder
2.063
253372AE2-315 SEC3
Adder
2.063
25306009OHH W.
Adder
3.13
253349AC2-067 GEN
Solar/Wind Harmer
2.381
253400AC2-068 GEN
Solar/Wind Harmer
0.958
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.953
965051AG1-369 GEN
Solar/Wind Harmer
3.739
965041AG1-368 GEN
Solar/Wind Harmer
7.471
247607V1-011 GEN
Solar/Wind Harmer
0.001
971567AH1-282 GEN
Solar/Wind Harmer
11.206
971989AH1-539 GEN
Solar/Wind Harmer
3.215
963791AG1-232 GEN
Solar/Wind Harmer
10.044
24729505KEY G4
Adder
6.919
270071AF1-092 GEN
Solar/Wind Harmer
14.245
971985AH1-537 GEN
Solar/Wind Harmer
2.206
270024AE2-089 GEN
Solar/Wind Harmer
0.008
270367AC2-061_GEN
Solar/Wind Harmer
0.006
965101AG1-375 GEN
Solar/Wind Harmer
7.401
971673AH1-337 GEN
Solar/Wind Harmer
4.804
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.344
25196308WSDLE2
Adder
9.263
25196208WSDLE1
Adder
9.24
25196708WSDLE6
Adder
9.217
25196508WSDLE4
Adder
8.984
971029AG2-637 GEN
Solar/Wind Harmer
11.085
270543AE2-219 C
Solar/Wind Harmer
0.004
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270297AD1-101 GEN
Solar/Wind Harmer
0.002
971347AH1-153 GEN
Solar/Wind Harmer
11.025
971609AH1-304 GEN
Solar/Wind Harmer
1.2
270240V3-007_GEN2
Solar/Wind Harmer
0.002
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.932
270594AE1-207 GEN
Solar/Wind Harmer
8.194
970289AG2-191 GEN
Solar/Wind Harmer
1.389
971771AH1-392 GEN
Solar/Wind Harmer
7.306
971619AH1-309 GEN
Solar/Wind Harmer
3.285
971769AH1-391 GEN
Solar/Wind Harmer
8.134
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.599
25196108MFTGT2
Adder
1.484
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.302
971549AH1-272 GEN
Solar/Wind Harmer
14.865
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.676
274776LINCOLN ;7U
Adder
8.676
274777LINCOLN ;8U
Adder
8.676
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
5.184
274807UNIV PK N;3U
Adder
5.173
274805UNIV PK N;1U
Adder
5.15
274811UNIV PK N;7U
Adder
5.139
972037AH1-567 GEN1
Adder
0.187
960591AF2-350 GEN
Solar/Wind Harmer
7.141
274827FISK ;RP
Adder
7.941
972227AH1-698 GEN1
Adder
2.669
963841AG1-237 GEN
Solar/Wind Harmer
3.09
972163AH1-664 GEN
Solar/Wind Harmer
7.933
972165AH1-665 GEN
Solar/Wind Harmer
6.354
274687WILL CNTY;4U
Adder
28.523
274687WILL CNTY;4U
Adder
28.523
270166AC1-044 GEN3
50/50
7.059
23559101PLEAS2
50/50
6.1
962761AG1-125 GEN
Solar/Wind Harmer
34.524
970149AG2-104 GEN
Solar/Wind Harmer
37.287
970155AG2-107 GEN
Solar/Wind Harmer
22.046
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
23.918
270159DARBY CT4
Adder
10.243
970593AG2-378 GEN
Solar/Wind Harmer
1.812
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.017
971995AH1-542 GEN
Solar/Wind Harmer
2.906
270263AC1-001 GEN
Solar/Wind Harmer
0.786
270510AE1-227 GEN1
Solar/Wind Harmer
1.963
25326309TAIT D
Adder
1.196
241813AF1-122_GEN
Solar/Wind Harmer
3.405
960071AF2-298 GEN
Solar/Wind Harmer
3.786
253370AE2-315 SEC1
Adder
2.182
253371AE2-315 SEC2
Adder
2.063
927014AC1-188 GEN
Solar/Wind Harmer
0.005
246936BC-WTG1
Solar/Wind Harmer
0.305
270489AE1-102 GEN1
Solar/Wind Harmer
0.979
965421AG1-410 GEN
Solar/Wind Harmer
22.57
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.499
247521TR3_G114
Solar/Wind Harmer
0.273
270246TR4_N_V150
Solar/Wind Harmer
0.048
965011AG1-365 GEN
Solar/Wind Harmer
7.488
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.174
958861AF2-177 GEN
Solar/Wind Harmer
3.207
247536S-71 GEN
Solar/Wind Harmer
0.297
25194608D.CRK4
Adder
1.74
945371AF1-202 GEN
Solar/Wind Harmer
0.001
252507AC2-088 GEN
Solar/Wind Harmer
0.335
270063AE2-323 C
Solar/Wind Harmer
0.006
970245AG2-165 GEN
Solar/Wind Harmer
3.191
970947AG2-589 GEN
Solar/Wind Harmer
0.245
270005AE1-210 C O1
Solar/Wind Harmer
1.59
965031AG1-367 GEN
Solar/Wind Harmer
7.338
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
274675JOLIET 29;7U
Adder
31.303
274675JOLIET 29;7U
Adder
30.185
274731ELWOOD EC;2P
Adder
16.768
274733ELWOOD EC;3P
Adder
16.768
274735ELWOOD EC;4P
Adder
16.768
274728ELWOOD EC;5P
Adder
16.768
970833AG2-524 GEN
Solar/Wind Harmer
7.824
970833AG2-524 GEN
Solar/Wind Harmer
5.216
274746AC1-111 G10
Adder
5.679
274744AC1-111 GEN8
Adder
5.679
972203AH1-686 GEN
Adder
2.338
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.414
276882AE2-255 GEN
Solar/Wind Harmer
0.824
238109AE1-109 GEN2
Solar/Wind Helper
0.114
238110AE1-109 GEN3
Solar/Wind Helper
0.114
238126S14_GEN_1
Solar/Wind Helper
0.827
238152AF2-075_GEN
Solar/Wind Helper
0.707
238208AF1-136 C
Solar/Wind Helper
0.22
23546401DTGZ2-030
Solar/Wind Helper
0.089
237085AD2-009_GEN
Solar/Wind Helper
1.649
3138216PACIFIC
Solar/Wind Helper
0.044
316411AF1-147_GEN1
Solar/Wind Helper
0.888
316415AF1-147_GEN2
Solar/Wind Helper
0.888
23750501ELLIOTTS
Solar/Wind Helper
0.638
959381AF2-229 GEN
Solar/Wind Helper
0.357
3141426STAFORD
Solar/Wind Helper
0.052
960921AF2-383 GEN
Solar/Wind Helper
0.364
205943AE1-185 GEN
Solar/Wind Helper
0.509
205932AD2-116_GEN
Solar/Wind Helper
0.509
205956AE1-196_GEN
Solar/Wind Helper
0.509
233935AB2-179 C
Solar/Wind Helper
1.269
232436AB1-176 C
Solar/Wind Helper
0.044
233923SMA
Solar/Wind Helper
0.958
233990AG1-397 GEN
Solar/Wind Helper
0.27
232432Z2-076 GEN
Solar/Wind Helper
0.067
234033AF1-007_GEN
Solar/Wind Helper
7.02
964001AG1-254 GEN
Solar/Wind Helper
0.955
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.115
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.08
203975AE1-071-GEN
Solar/Wind Helper
2.498
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.29
219620RIDERU C
Solar/Wind Helper
0.001
316164AC1-076 GEN
Solar/Wind Helper
1.096
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.16
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
207484AF2-139 C O1
Solar/Wind Helper
0.084
20674828DL_W4-046
Solar/Wind Helper
0.008
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.778
270119AB2-067 GEN1
50/50
7.059
270120AB2-067 GEN2
50/50
7.059
24318905MLG2
50/50
7.071
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.335
970077AG2-063 GEN
Solar/Wind Harmer
4.631
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.917
971655AH1-328 GEN
Solar/Wind Harmer
2.854
964601AG1-323 GEN
Solar/Wind Harmer
3.215
964601AG1-323 GEN
Solar/Wind Harmer
2.143
270518AE2-148 GEN
Solar/Wind Harmer
0.691
972269AH1-719 GEN
Adder
2.584
972159AH1-661 GEN
Adder
1.118
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.354
971199AH1-059 GEN
Solar/Wind Harmer
3.09
241960AC2-195 GEN
Solar/Wind Harmer
0.006
25326509SID D
Adder
1.451
971073AG2-665 GEN
Solar/Wind Harmer
6.898
25326109MON D
Adder
1.443
25322209TAIT E
Adder
10.642
25322209TAIT E
Adder
10.403
971201AH1-060 GEN
Solar/Wind Harmer
1.52
253370AE2-315 SEC1
Adder
2.182
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.273
246937BC-WTG2
Solar/Wind Harmer
0.305
971231AH1-075 GEN
Solar/Wind Harmer
0.861
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
970611AG2-400 GEN
Solar/Wind Harmer
7.488
970627AG2-408 GEN
Solar/Wind Harmer
2.246
270007AE1-245 C
Solar/Wind Harmer
0.002
962581AG1-107 GEN
Solar/Wind Harmer
0.002
25183208HLCRTG
Solar/Wind Harmer
0.012
944541AF1-119 GEN
Solar/Wind Harmer
0.497
960971AF2-388 GEN
Solar/Wind Harmer
4.347
970623AG2-406 GEN
Solar/Wind Harmer
1.356
942221AE2-234 GEN
Solar/Wind Harmer
0.037
252519AF1-045_GEN
Solar/Wind Harmer
6.44
252516AE2-318_GEN
Solar/Wind Harmer
5.712
247621Y3-024
Adder
0.255
970883AG2-550 GEN
Solar/Wind Harmer
7.389
970885AG2-551 GEN
Solar/Wind Harmer
2.463
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
8.004
25194508D.CRK3
Adder
1.496
970621AG2-405 GEN
Solar/Wind Harmer
1.351
964611AG1-324 GEN
Solar/Wind Harmer
0.553
252509AD1-136 GEN
Solar/Wind Harmer
0.037
970321AG2-212 GEN
Solar/Wind Harmer
3.191
270599AE1-208 GEN
Solar/Wind Harmer
6.737
270031AE2-169
Solar/Wind Harmer
4.042
270186AC1-089 GEN
Solar/Wind Harmer
0.004
270383AD1-128 GEN
Solar/Wind Harmer
0.004
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.127
247620Y3-023
Adder
0.484
960441AF2-335 GEN
Solar/Wind Harmer
7.33
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.512
24728805RICHG1
Adder
3.964
24728905RICHG2
Adder
3.964
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.589
961051AF2-396 GEN
Solar/Wind Harmer
9.726
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
9.095
965791AG1-447 GEN
Solar/Wind Harmer
6.67
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.797
274770LINCOLN ;1U
Adder
8.676
274771LINCOLN ;2U
Adder
8.676
966841AG1-555 GEN
Solar/Wind Harmer
0.81
274808UNIV PK N;4U
Adder
5.117
274803UNIV PARK;6U
Adder
5.97
274888KELLY CRK;1U
Solar/Wind Harmer
0.419
274887GEN-1.85
Solar/Wind Harmer
0.188
276843GEN-1.7
Solar/Wind Harmer
0.231
958011AF2-095 GEN
Solar/Wind Harmer
10.284
972259AH1-714 GEN
Adder
19.507
274674JOLIET 9 ;6U
Adder
15.704
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
970241AG2-163 GEN
Solar/Wind Harmer
4.144
958481AF2-142 GEN
Solar/Wind Harmer
10.621
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.958
971573AH1-285 GEN
Solar/Wind Harmer
1.319
274696ROCKY RD ;4P
Adder
11.537
274695ROCKY RD ;2P
Adder
11.271
274693ROCKY RD ;1P
Adder
11.16
274697ROCKY RD ;3P
Adder
3.062
958491AF2-143 GEN
Solar/Wind Harmer
10.588
274879MINONK ;1U
Solar/Wind Harmer
0.297
23585401KL_K28_T16
Solar/Wind Helper
1.482
238120AE2-309 GEN
Solar/Wind Helper
0.525
238175AF1-290_GEN
Solar/Wind Helper
0.153
238169AE2-226 GEN1
Solar/Wind Helper
0.701
238170AE2-226 GEN2
Solar/Wind Helper
0.701
970613AG2-401 GEN
Solar/Wind Harmer
5.378
970825AG2-519 GEN
Solar/Wind Harmer
2.603
25196808ZIMRHP
Adder
79.729
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
1.953
24639705ELKHART HY
Adder
0.161
270032AE2-172
Solar/Wind Harmer
4.877
970291AG2-192 GEN
Solar/Wind Harmer
0.95
945111AF1-176 GEN
Solar/Wind Harmer
13.03
270505AE1-170 C O1
Solar/Wind Harmer
7.665
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.805
276903AD2-071 C
Solar/Wind Harmer
8.137
25196008MFTGT1
Adder
1.45
247522W1-056 GEN
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.284
970373AG2-245 GEN
Solar/Wind Harmer
15.247
270055AF2-134 C O1
Solar/Wind Harmer
0.006
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.41
970515AG2-329 GEN
Solar/Wind Harmer
18.805
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
9.032
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
5.139
274751CRETE EC ;1U
Adder
8.477
274754CRETE EC ;4U
Adder
8.477
274773LINCOLN ;4U
Adder
8.676
274774LINCOLN ;5U
Adder
8.676
274723RIVER EC ;12
Adder
18.418
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
5.139
24728605AND G2
Adder
3.927
276776AD2-060 GEN
Solar/Wind Harmer
0.746
945681AF1-233 GEN
Solar/Wind Harmer
13.461
274801UNIV PARK;4U
Adder
5.966
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
31.303
274732ELWOOD EC;7P
Adder
16.768
274674JOLIET 9 ;6U
Adder
15.704
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.815
274745AC1-111 GEN9
Adder
5.679
939401AE1-172 GEN
Solar/Wind Harmer
5.301
276691AA1-018 GEN1
Solar/Wind Harmer
0.858
970091AG2-072 GEN
Adder
77.629
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.504
23583801GRNGAP
Solar/Wind Helper
5.601
238185AF2-356 C
Solar/Wind Helper
2.646
238108AE1-109 GEN1
Solar/Wind Helper
0.114
235054AD2-180 GEN
Solar/Wind Helper
2.03
235531U2-073 GEN
Solar/Wind Helper
3.282
316254AC1-120 GEN1
Solar/Wind Helper
1.059
207445AB1-138_GEN
Solar/Wind Helper
0.104
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.13
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.31
20715228NPK_W1-113
Solar/Wind Helper
0.078
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.495
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.138
207518AF1-320_GEN
Solar/Wind Helper
1.571
20671928W4-073
Solar/Wind Helper
0.09
20675828AU_W4-064
Solar/Wind Helper
0.029
235020AA1-095 C
Solar/Wind Helper
0.053
23777901MDS_W4-102
Solar/Wind Helper
0.177
237002AB1-128_GEN
Solar/Wind Helper
0.443
237034AC2-136 C
Solar/Wind Helper
0.227
235063AE1-101 C2
Solar/Wind Helper
1.659
237001AB1-127_GEN
Solar/Wind Helper
0.442
23777801MSM_W1-116
Solar/Wind Helper
0.114
237025AB1-124 C
Solar/Wind Helper
0.164
237006AB1-125 GEN
Solar/Wind Helper
0.123
226929AD2-058 GEN
Solar/Wind Helper
0.099
205916AD1-020 GEN
Solar/Wind Helper
1.713
20390526W1-045 C
Solar/Wind Helper
0.35
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
233987AB2-037 GEN
Solar/Wind Helper
2.342
233933AB2-153 GEN
Solar/Wind Helper
0.232
233944AB2-135 GEN
Solar/Wind Helper
0.588
232424Y1-079 C
Solar/Wind Helper
0.116
234036AF2-325 C
Solar/Wind Helper
0.042
233946AB2-136 GEN
Solar/Wind Helper
0.568
233901CHERRYDALE C
Solar/Wind Helper
0.232
232408W1-005 C
Solar/Wind Helper
0.507
232410W1-006 C
Solar/Wind Helper
0.507
233939AC1-091 C
Solar/Wind Helper
0.35
233970AC1-092 C
Solar/Wind Helper
0.35
315651AD1-115 GEN
Solar/Wind Helper
0.785
316447AC1-158 HLD
Solar/Wind Helper
2.845
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.04
219921AF1-264
Solar/Wind Helper
0.051
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.082
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.051
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.09
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.092
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.074
211065PSPA IPP
Solar/Wind Helper
0.151
211065PSPA IPP
Solar/Wind Helper
0.151
238117U2-030
Solar/Wind Helper
0.341
238147AE2-230_GEN1
Solar/Wind Helper
0.495
238149AF1-291A_GEN
Solar/Wind Helper
0.141
23751201ROTHROCK
Solar/Wind Helper
0.824
237061AD1-155 GEN
Solar/Wind Helper
0.053
23562501BACKB
Solar/Wind Helper
1.007
238221AF1-254 C O1
Solar/Wind Helper
0.274
235067AD1-061 GEN
Solar/Wind Helper
0.496
23751101LEADS_P59
Solar/Wind Helper
1.404
237030AB1-096 C
Solar/Wind Helper
0.071
3141196NOKESVL
Solar/Wind Helper
1.032
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.346
223402AF1-300 C
Solar/Wind Helper
0.367
205917AD1-020 ES
Solar/Wind Helper
0.368
233918AB1-142 GEN
Solar/Wind Helper
0.502
233982AB2-133 GEN
Solar/Wind Helper
0.358
233994AC2-023 GEN
Solar/Wind Helper
0.961
233996TM1833_GEN
Solar/Wind Helper
0.261
233997TMININ_4.2
Solar/Wind Helper
0.261
232406W1-004 FULL
Solar/Wind Helper
0.507
233940AF2-379 C
Solar/Wind Helper
0.062
234015AF2-250 C
Solar/Wind Helper
0.038
233952AC2-187 GEN
Solar/Wind Helper
0.232
233971AC1-093 C
Solar/Wind Helper
0.357
316044AC1-158 PL1
Solar/Wind Helper
1.293
316450AC1-158 RIC
Solar/Wind Helper
0.345
230430AE1-229_GEN
Solar/Wind Helper
3.372
230415AB2-049 C
Solar/Wind Helper
0.03
228729W2-030 C
Solar/Wind Helper
0.11
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.15
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.114
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.063
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
316170AC1-121 GEN2
Solar/Wind Helper
0.353
219276PARKLANDSO C
Solar/Wind Helper
0.089
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219908AB1-139 C
Solar/Wind Helper
0.074
219249CENTRALDIV C
Solar/Wind Helper
0.01
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
971997AH1-543 GEN
Solar/Wind Harmer
2.724
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.078
CBM South 1LTFEXP_CBM-S1->PJM
CBM
29.1
MECLTFEXP_MEC->PJM
CLTF
15.901
SIGELTFEXP_SIGE->PJM
CLTF
0.505
CPLELTFEXP_CPLE->PJM
CLTF
0.624
CBM West 2LTFEXP_CBM-W2->PJM
CBM
112.816
LAGNLTFEXP_LAGN->PJM
CLTF
14.837
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.802
TVALTFEXP_TVA->PJM
CLTF
7.293
NYPJM->LTFIMP_NY
CLTF
4.797
LGEELTFEXP_LGEE->PJM
CLTF
6.749
WECLTFEXP_WEC->PJM
CLTF
3.825
AG2-052LTFEXP_AG2-052->PJM
LTF
0.24
AH1-155LTFEXP_AH1-155->PJM
LTF
0.359

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P2-3_MP-500-012_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P2-3_MP-500-012_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:131.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4985.98
MW Contribution:10.73
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
3.102
962771AG1-126 GEN
Solar/Wind Harmer
40.965
270459AD2-067 GEN
Solar/Wind Harmer
10.453
961821AG1-024 GEN
Solar/Wind Harmer
10.613
270054AF2-122 C O1
Solar/Wind Harmer
4.071
270284AF1-227 GEN1
Solar/Wind Harmer
6.912
270286AF1-227 GEN2
Solar/Wind Harmer
2.557
270287AF1-227 GEN3
Solar/Wind Harmer
2.557
270520AE2-214 GEN
Solar/Wind Harmer
7.382
253383AE2-342_GEN
Solar/Wind Harmer
1.062
241973AD2-163_GEN1
Solar/Wind Harmer
2.37
940611AE2-048 GEN
Solar/Wind Harmer
26.074
941391AE2-136 GEN
Solar/Wind Harmer
13.511
270578AF1-285 GEN2
Solar/Wind Harmer
0.55
943861AF1-054 GEN
Solar/Wind Harmer
4.552
943851AF1-053 GEN
Solar/Wind Harmer
2.2
945631AF1-228 GEN
Solar/Wind Harmer
5.537
270156DARBY CT1
Adder
10.556
270157DARBY CT2
Adder
10.53
270158DARBY CT3
Adder
10.362
270302AB2-170 GEN
Solar/Wind Harmer
9.805
270317AD1-130_GEN
Solar/Wind Harmer
3.759
970689AG2-444 GEN
Solar/Wind Harmer
19.055
270432AC2-029 GEN
Solar/Wind Harmer
8.138
958581AF2-149 GEN
Solar/Wind Harmer
4.968
970179AG2-119 GEN
Solar/Wind Harmer
9.26
270269AC2-059
Solar/Wind Harmer
10.704
241972AD1-140 GEN
Solar/Wind Harmer
5.084
971567AH1-282 GEN
Solar/Wind Harmer
16.984
966831AG1-554 GEN
Solar/Wind Harmer
1.34
971989AH1-539 GEN
Solar/Wind Harmer
14.49
270340AC2-060 GEN
Solar/Wind Harmer
3.371
957201AF2-014 GEN
Solar/Wind Harmer
5.033
270435AC2-044 GEN
Solar/Wind Harmer
2.219
970879AG2-548 GEN
Solar/Wind Harmer
4.763
247607V1-011 GEN
Solar/Wind Harmer
4.359
253372AE2-315 SEC3
Adder
2.086
253372AE2-315 SEC3
Adder
2.086
965051AG1-369 GEN
Solar/Wind Harmer
5.494
25306009OHH W.
Adder
3.166
270297AD1-101 GEN
Solar/Wind Harmer
3.056
965041AG1-368 GEN
Solar/Wind Harmer
10.974
270119AB2-067 GEN1
50/50
7.033
270120AB2-067 GEN2
50/50
7.033
24318905MLG2
50/50
7.475
270471AD2-092_GEN
Solar/Wind Harmer
4.529
946101AF1-275 GEN
Solar/Wind Harmer
1.842
938701AE1-092 GEN
Solar/Wind Harmer
24.483
270224U2-072_GEN2
Solar/Wind Harmer
2.339
270227U2-072_GEN3
Solar/Wind Harmer
2.339
270228U2-072_GEN4
Solar/Wind Harmer
2.339
270231U2-072_GEN5
Solar/Wind Harmer
2.339
942861AE2-305 GEN
Solar/Wind Harmer
9.223
24318805MLG1
50/50
10.022
23559001PLEAS1
50/50
5.443
270051AF1-062 GEN
50/50
11.999
970153AG2-106 GEN
Solar/Wind Harmer
17.863
961921AG1-034 GEN
Solar/Wind Harmer
15.919
241955AC1-078 GEN
Solar/Wind Harmer
8.948
241974AD2-163_GEN2
Solar/Wind Harmer
2.37
942051AE2-217 GEN
Solar/Wind Harmer
21.374
942871AE2-306 GEN
Solar/Wind Harmer
1.073
270391AF1-285 GEN3
Solar/Wind Harmer
0.55
960801AF2-371 GEN
Solar/Wind Harmer
2.991
964871AG1-351 GEN
Solar/Wind Harmer
2.065
970605AG2-385 GEN
Solar/Wind Harmer
6.332
270485AE1-090_GEN
Solar/Wind Harmer
0.709
270512AE1-227 GEN2
Solar/Wind Harmer
2.455
24721905FLATG4
Adder
23.506
253338AC1-165 GEN
Solar/Wind Harmer
1.256
253333AC1-068 GEN
Solar/Wind Harmer
1.211
970065AG2-057 GEN
Solar/Wind Harmer
1.148
270273AD2-016 GEN
Solar/Wind Harmer
3.061
972173AH1-669 GEN
Solar/Wind Harmer
5.721
270377AD1-106 GEN
Solar/Wind Harmer
6.988
270588AE1-091_GEN
Solar/Wind Harmer
12.311
270291AC1-194 GEN
Solar/Wind Harmer
11.854
253415AE1-040 GEN
Solar/Wind Harmer
1.258
961961AG1-039 GEN
Solar/Wind Harmer
3.188
270491AE1-102 GEN2
Solar/Wind Harmer
1.443
970217AG2-149 GEN
Solar/Wind Harmer
35.355
958091AF2-103 GEN
Solar/Wind Harmer
0.178
253303V4-073 C
Solar/Wind Harmer
0.128
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
270191TR4_S_V150
Solar/Wind Harmer
3.3
270247TR4_N_V136
Solar/Wind Harmer
0.936
959331AF2-224 GEN
Solar/Wind Harmer
10.972
965021AG1-366 GEN
Solar/Wind Harmer
2.552
270258AD1-119 GEN
Solar/Wind Harmer
3.051
253406AD2-031_GEN
Solar/Wind Harmer
1.398
270044AE2-322 C
Solar/Wind Harmer
1.435
270404AC1-167 GEN
Solar/Wind Harmer
1.194
957541AF2-048 GEN
Solar/Wind Harmer
1.725
270043AE2-236 GEN
Solar/Wind Harmer
5.98
944531AF1-118 GEN
Solar/Wind Harmer
37.943
253316AC1-085 GEN3
Solar/Wind Harmer
9.07
253433AC1-085 GEN1
Solar/Wind Harmer
5.758
946181AF1-283 GEN
Solar/Wind Harmer
14.077
970031AG2-029 GEN
Solar/Wind Harmer
32.394
971617AH1-308 GEN
Solar/Wind Harmer
6.274
270541AE2-072 C
Solar/Wind Harmer
4.881
971191AH1-055 GEN
Solar/Wind Harmer
23.635
962031AG1-047 GEN
Solar/Wind Harmer
3.246
957741AF2-068 GEN
Solar/Wind Harmer
16.111
25196608WSDLE5
Adder
9.143
24642205MAYFLWER
Adder
0.678
25194608D.CRK4
Adder
1.752
247604X1-042
Adder
0.444
23906502RICHG2&3
Adder
1.272
25196008MFTGT1
Adder
1.413
274752CRETE EC ;2U
Adder
8.598
253349AC2-067 GEN
Solar/Wind Harmer
5.466
253400AC2-068 GEN
Solar/Wind Harmer
2.198
963791AG1-232 GEN
Solar/Wind Harmer
14.679
270071AF1-092 GEN
Solar/Wind Harmer
16.242
24729505KEY G4
Adder
7.02
945641AF1-229 GEN
Solar/Wind Harmer
3.923
270024AE2-089 GEN
Solar/Wind Harmer
5.065
958711AF2-162 GEN
Solar/Wind Harmer
1.089
965101AG1-375 GEN
Solar/Wind Harmer
10.752
961761AG1-017 GEN
Solar/Wind Harmer
0.46
270543AE2-219 C
Solar/Wind Harmer
5.494
971029AG2-637 GEN
Solar/Wind Harmer
16.089
971673AH1-337 GEN
Solar/Wind Harmer
4.934
25196408WSDLE3
Adder
9.412
25196308WSDLE2
Adder
9.33
25196208WSDLE1
Adder
9.306
25196708WSDLE6
Adder
9.283
25196508WSDLE4
Adder
9.049
25196108MFTGT2
Adder
1.608
25196108MFTGT2
Adder
1.494
274775LINCOLN ;6U
Adder
8.792
274776LINCOLN ;7U
Adder
8.792
274777LINCOLN ;8U
Adder
8.792
274814UNIV PK N;0U
Adder
5.256
274807UNIV PK N;3U
Adder
5.245
274805UNIV PK N;1U
Adder
5.222
274811UNIV PK N;7U
Adder
5.21
972037AH1-567 GEN1
Adder
0.19
274827FISK ;RP
Adder
8.047
972227AH1-698 GEN1
Adder
2.704
274687WILL CNTY;4U
Adder
28.893
274687WILL CNTY;4U
Adder
28.893
274675JOLIET 29;7U
Adder
31.706
274675JOLIET 29;7U
Adder
30.574
274731ELWOOD EC;2P
Adder
16.983
274733ELWOOD EC;3P
Adder
16.983
274735ELWOOD EC;4P
Adder
16.983
274728ELWOOD EC;5P
Adder
16.983
238109AE1-109 GEN2
Solar/Wind Helper
0.121
238110AE1-109 GEN3
Solar/Wind Helper
0.121
238152AF2-075_GEN
Solar/Wind Helper
0.789
23546401DTGZ2-030
Solar/Wind Helper
0.099
238126S14_GEN_1
Solar/Wind Helper
0.867
238208AF1-136 C
Solar/Wind Helper
0.236
237085AD2-009_GEN
Solar/Wind Helper
1.767
3138216PACIFIC
Solar/Wind Helper
0.049
316411AF1-147_GEN1
Solar/Wind Helper
0.978
316415AF1-147_GEN2
Solar/Wind Helper
0.978
3141426STAFORD
Solar/Wind Helper
0.058
316164AC1-076 GEN
Solar/Wind Helper
1.225
23750501ELLIOTTS
Solar/Wind Helper
0.629
959381AF2-229 GEN
Solar/Wind Helper
0.367
960921AF2-383 GEN
Solar/Wind Helper
0.185
205943AE1-185 GEN
Solar/Wind Helper
0.518
205932AD2-116_GEN
Solar/Wind Helper
0.518
205956AE1-196_GEN
Solar/Wind Helper
0.518
233935AB2-179 C
Solar/Wind Helper
1.29
232436AB1-176 C
Solar/Wind Helper
0.045
233923SMA
Solar/Wind Helper
0.974
233990AG1-397 GEN
Solar/Wind Helper
0.031
232432Z2-076 GEN
Solar/Wind Helper
0.068
234033AF1-007_GEN
Solar/Wind Helper
7.137
964001AG1-254 GEN
Solar/Wind Helper
0.966
227927V4-067C
Solar/Wind Helper
0.01
228754AB1-001 C
Solar/Wind Helper
0.026
219914AD2-027 C
Solar/Wind Helper
0.116
203975AE1-071-GEN
Solar/Wind Helper
2.53
219272CLEANLIGHT C
Solar/Wind Helper
0.026
219688LUMSOLAR_S C
Solar/Wind Helper
0.04
219607WPEMNERT C
Solar/Wind Helper
0.081
214067T20SOLAR
Solar/Wind Helper
0.011
20715728PEM_W1-119
Solar/Wind Helper
0.096
20715828PEM_W1-120
Solar/Wind Helper
0.096
207459AE1-142 C O1
Solar/Wind Helper
0.292
219620RIDERU C
Solar/Wind Helper
0.001
20675528CPH_W2-050
Solar/Wind Helper
0.087
218526CNTRALGAS2 C
Solar/Wind Helper
0.161
218524CNTRALGAS1 C
Solar/Wind Helper
0.161
966261AG1-495 GEN
Solar/Wind Helper
0.081
207530AG1-191 GEN
Solar/Wind Helper
0.066
20676328BVR_Y1-020
Solar/Wind Helper
0.027
20675928HOL_W4-097
Solar/Wind Helper
0.05
20674828DL_W4-046
Solar/Wind Helper
0.008
207484AF2-139 C O1
Solar/Wind Helper
0.084
207408W3-077 C
Solar/Wind Helper
0.084
20675728RH_W2-091
Solar/Wind Helper
0.136
20675128HRM_W1-127
Solar/Wind Helper
0.029
209116AE2-175 GEN
Solar/Wind Helper
1.768
945581AF1-223 GEN
Solar/Wind Harmer
0.763
964601AG1-323 GEN
Solar/Wind Harmer
3.753
964601AG1-323 GEN
Solar/Wind Harmer
1.746
972269AH1-719 GEN
Adder
2.7
970077AG2-063 GEN
Solar/Wind Harmer
6.332
972159AH1-661 GEN
Adder
1.166
270518AE2-148 GEN
Solar/Wind Harmer
14.068
971199AH1-059 GEN
Solar/Wind Harmer
4.644
241960AC2-195 GEN
Solar/Wind Harmer
3.219
971201AH1-060 GEN
Solar/Wind Harmer
2.296
253378AE2-206_GEN
Solar/Wind Harmer
4.086
276820AF1-078_GEN
Solar/Wind Harmer
1.815
971231AH1-075 GEN
Solar/Wind Harmer
0.905
25326509SID D
Adder
1.48
25326109MON D
Adder
1.461
246938BC-WTG3
Solar/Wind Harmer
4.418
246937BC-WTG2
Solar/Wind Harmer
4.343
970879AG2-548 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
6.827
971073AG2-665 GEN
Solar/Wind Harmer
4.763
25322209TAIT E
Adder
10.77
25322209TAIT E
Adder
10.528
270007AE1-245 C
Solar/Wind Harmer
6.539
942801AE2-298 GEN
Solar/Wind Harmer
1.667
253370AE2-315 SEC1
Adder
2.206
970611AG2-400 GEN
Solar/Wind Harmer
10.972
253394AE2-221_GEN
Solar/Wind Harmer
4.954
253398AE2-221_GEN2
Solar/Wind Harmer
4.954
253317AC1-085 GEN4
Solar/Wind Harmer
9.07
971677AH1-339 GEN
Solar/Wind Harmer
8.643
942221AE2-234 GEN
Solar/Wind Harmer
0.79
944541AF1-119 GEN
Solar/Wind Harmer
4.511
960971AF2-388 GEN
Solar/Wind Harmer
11.771
247621Y3-024
Adder
0.259
270201AC2-176 GEN
Solar/Wind Harmer
5.522
970883AG2-550 GEN
Solar/Wind Harmer
10.73
970885AG2-551 GEN
Solar/Wind Harmer
2.495
247620Y3-023
Adder
0.494
964611AG1-324 GEN
Solar/Wind Harmer
1.264
964611AG1-324 GEN
Solar/Wind Harmer
0.561
25194408D.CRK1
Adder
8.061
25194508D.CRK3
Adder
1.507
270166AC1-044 GEN3
50/50
7.033
23559101PLEAS2
50/50
5.443
270122AB2-093 CT
50/50
4.116
962761AG1-125 GEN
Solar/Wind Harmer
40.965
970149AG2-104 GEN
Solar/Wind Harmer
50.592
970155AG2-107 GEN
Solar/Wind Harmer
17.863
270349AD2-093_GEN
Solar/Wind Harmer
4.529
270223U2-072_GEN1
Solar/Wind Harmer
2.339
270578AF1-285 GEN2
Solar/Wind Harmer
1.43
270391AF1-285 GEN3
Solar/Wind Harmer
1.43
270159DARBY CT4
Adder
10.388
971995AH1-542 GEN
Solar/Wind Harmer
12.974
970593AG2-378 GEN
Solar/Wind Harmer
2.345
270462AD2-086
Solar/Wind Harmer
8.157
270510AE1-227 GEN1
Solar/Wind Harmer
2.893
24721705FLATG2
Adder
23.506
253343AC1-166 GEN
Solar/Wind Harmer
1.256
253325AC1-069 GEN
Solar/Wind Harmer
1.211
241813AF1-122_GEN
Solar/Wind Harmer
7.346
270263AC1-001 GEN
Solar/Wind Harmer
1.187
241847AF2-150_GEN
Solar/Wind Harmer
4.622
246936BC-WTG1
Solar/Wind Harmer
4.343
270489AE1-102 GEN1
Solar/Wind Harmer
1.443
965421AG1-410 GEN
Solar/Wind Harmer
33.256
970515AG2-329 GEN
Solar/Wind Harmer
16.033
25326309TAIT D
Adder
1.21
960071AF2-298 GEN
Solar/Wind Harmer
5.501
253370AE2-315 SEC1
Adder
2.206
253371AE2-315 SEC2
Adder
2.086
247521TR3_G114
Solar/Wind Harmer
3.699
270246TR4_N_V150
Solar/Wind Harmer
0.936
247522W1-056 GEN
Solar/Wind Harmer
2.477
24695305TIMB G C
Solar/Wind Harmer
6.051
965011AG1-365 GEN
Solar/Wind Harmer
10.972
927014AC1-188 GEN
Solar/Wind Harmer
1.729
944231AF1-091 GEN
Solar/Wind Harmer
4.078
253432AC1-085 GEN2
Solar/Wind Harmer
0.29
946171AF1-282 GEN
Solar/Wind Harmer
10.828
270063AE2-323 C
Solar/Wind Harmer
2.376
965651AG1-433 GEN
Solar/Wind Harmer
5.885
958861AF2-177 GEN
Solar/Wind Harmer
11.752
247536S-71 GEN
Solar/Wind Harmer
4.346
960001AF2-291 GEN
Solar/Wind Harmer
3.244
945371AF1-202 GEN
Solar/Wind Harmer
7.479
24639705ELKHART HY
Adder
0.164
25194608D.CRK4
Adder
1.752
25196808ZIMRHP
Adder
80.188
23906502RICHG2&3
Adder
1.272
972301AH1-735 GEN
Adder
6.357
23906402RICHG1
Adder
1.271
25196008MFTGT1
Adder
1.459
274751CRETE EC ;1U
Adder
8.598
274754CRETE EC ;4U
Adder
8.598
274723RIVER EC ;12
Adder
18.677
274773LINCOLN ;4U
Adder
8.792
274774LINCOLN ;5U
Adder
8.792
274812UNIV PK N;8U
Adder
5.21
23920202STRYCT
Adder
1.444
274801UNIV PARK;4U
Adder
6.045
274676JOLIET 29;8U
Adder
31.706
274732ELWOOD EC;7P
Adder
2.004
23583801GRNGAP
Solar/Wind Helper
6.365
316095T157 G97
Solar/Wind Helper
1.705
238108AE1-109 GEN1
Solar/Wind Helper
0.121
238185AF2-356 C
Solar/Wind Helper
2.767
238147AE2-230_GEN1
Solar/Wind Helper
0.552
238149AF1-291A_GEN
Solar/Wind Helper
0.158
237061AD1-155 GEN
Solar/Wind Helper
0.06
235054AD2-180 GEN
Solar/Wind Helper
2.111
235531U2-073 GEN
Solar/Wind Helper
3.439
238117U2-030
Solar/Wind Helper
0.356
238221AF1-254 C O1
Solar/Wind Helper
0.295
235067AD1-061 GEN
Solar/Wind Helper
0.532
3141196NOKESVL
Solar/Wind Helper
1.141
23751201ROTHROCK
Solar/Wind Helper
0.819
237030AB1-096 C
Solar/Wind Helper
0.075
23562501BACKB
Solar/Wind Helper
0.997
226910AB2-157 C
Solar/Wind Helper
0.015
227287AC2-120 GEN
Solar/Wind Helper
0.375
223402AF1-300 C
Solar/Wind Helper
0.387
316044AC1-158 PL1
Solar/Wind Helper
1.443
316450AC1-158 RIC
Solar/Wind Helper
0.385
316170AC1-121 GEN2
Solar/Wind Helper
0.395
23751101LEADS_P59
Solar/Wind Helper
1.316
205917AD1-020 ES
Solar/Wind Helper
0.379
3132273ORANGE
Solar/Wind Helper
0.049
233918AB1-142 GEN
Solar/Wind Helper
0.511
233982AB2-133 GEN
Solar/Wind Helper
0.364
233994AC2-023 GEN
Solar/Wind Helper
0.977
233996TM1833_GEN
Solar/Wind Helper
0.266
233997TMININ_4.2
Solar/Wind Helper
0.266
232406W1-004 FULL
Solar/Wind Helper
0.516
3147666LOUISA
Solar/Wind Helper
0.551
233940AF2-379 C
Solar/Wind Helper
0.063
234015AF2-250 C
Solar/Wind Helper
0.039
233952AC2-187 GEN
Solar/Wind Helper
0.236
233971AC1-093 C
Solar/Wind Helper
0.363
230430AE1-229_GEN
Solar/Wind Helper
3.409
230415AB2-049 C
Solar/Wind Helper
0.031
228729W2-030 C
Solar/Wind Helper
0.112
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.055
219912AD2-042 GEN
Solar/Wind Helper
0.151
219291REEVESSOUT C
Solar/Wind Helper
0.012
274753CRETE EC ;3U
Adder
8.598
274724RIVER EC ;11
Adder
18.459
274772LINCOLN ;3U
Adder
8.792
274802UNIV PARK;5U
Adder
6.05
274826FISK ;BP
Adder
11.355
274800UNIV PARK;3U
Adder
6.045
972038AH1-567 GEN2
Adder
0.378
972228AH1-698 GEN2
Adder
3.84
274676JOLIET 29;8U
Adder
30.573
274729ELWOOD EC;1P
Adder
16.983
274730ELWOOD EC;6P
Adder
16.983
964991AG1-363 GEN
Solar/Wind Helper
5.557
316097T157 G90
Solar/Wind Helper
1.705
23750701CROSSCHOOL
Solar/Wind Helper
1.586
238148AE2-230_GEN2
Solar/Wind Helper
0.555
238127S14_GEN_2
Solar/Wind Helper
0.867
238118U2-030_1
Solar/Wind Helper
0.356
237080AD1-060 GEN
Solar/Wind Helper
0.367
237038AE2-054 C
Solar/Wind Helper
0.292
235062AE1-101 C1
Solar/Wind Helper
1.776
23779801AA1-109
Solar/Wind Helper
0.207
316006AB2-029 C
Solar/Wind Helper
0.13
223401AF1-299 GEN
Solar/Wind Helper
0.387
316045AC1-158 PL2
Solar/Wind Helper
4.618
316254AC1-120 GEN1
Solar/Wind Helper
1.184
237048AF1-022 C
Solar/Wind Helper
0.173
966131AG1-482 GEN
Solar/Wind Helper
0.079
233930AB2-032 GEN
Solar/Wind Helper
0.387
233915AB1-141 GEN
Solar/Wind Helper
0.511
232422X3-066 FULL
Solar/Wind Helper
0.116
233964AF2-378 GEN
Solar/Wind Helper
0.042
232426Y1-080 FULL
Solar/Wind Helper
0.039
233998TM1NIN_3.36
Solar/Wind Helper
0.266
232404W1-003 C
Solar/Wind Helper
0.516
232428Y3-058 C
Solar/Wind Helper
0.344
3147666LOUISA
Solar/Wind Helper
0.958
232434Z2-077 GEN
Solar/Wind Helper
0.129
233954AC2-188 GEN
Solar/Wind Helper
0.236
233950AC2-186 GEN
Solar/Wind Helper
0.118
233972AC1-094 C
Solar/Wind Helper
0.307
316192AB2-158 GEN
Solar/Wind Helper
1.608
230511AF1-262
Solar/Wind Helper
0.015
230434AG1-499 GEN
Solar/Wind Helper
0.232
228728W1-130C
Solar/Wind Helper
0.054
219258KINSLEYDEP C
Solar/Wind Helper
0.077
219904AC1-010 C
Solar/Wind Helper
0.061
218660EHAMPSOLAR C
Solar/Wind Helper
0.033
219907AC1-030 C
Solar/Wind Helper
0.034
219686LUMSOLAR_N C
Solar/Wind Helper
0.04
219304NAMERICA C
Solar/Wind Helper
0.132
20720728JCB_W1-129
Solar/Wind Helper
0.057
207445AB1-138_GEN
Solar/Wind Helper
0.105
963711AG1-223 GEN
Solar/Wind Helper
0.064
20714828MDF_W3-079
Solar/Wind Helper
0.131
219680HOPEWELLV C1
Solar/Wind Helper
0.003
20715228NPK_W1-113
Solar/Wind Helper
0.078
207454AA2-184 E
Solar/Wind Helper
0.311
20742028HF_AC1-207
Solar/Wind Helper
0.141
205941AD2-115 GEN
Solar/Wind Helper
0.497
218428ETC SOLAR C
Solar/Wind Helper
0.005
217213AMBOY SO C
Solar/Wind Helper
0.029
207528AF2-192 GEN
Solar/Wind Helper
0.076
20673628F1S_V4-069
Solar/Wind Helper
0.03
20675428EAM_W2-061
Solar/Wind Helper
0.016
20676428JCR_X2-075
Solar/Wind Helper
0.068
217209CENTRL HS C
Solar/Wind Helper
0.008
217208PARK ELE C
Solar/Wind Helper
0.004
20674328GAR_V4-001
Solar/Wind Helper
0.022
207439AE1-081 C O1
Solar/Wind Helper
0.019
207437AD2-070 GEN
Solar/Wind Helper
0.137
207518AF1-320_GEN
Solar/Wind Helper
1.568
20671928W4-073
Solar/Wind Helper
0.089
20675828AU_W4-064
Solar/Wind Helper
0.029
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.042
219348LDSOLAR C
Solar/Wind Helper
0.115
959561AF2-247 GEN
Solar/Wind Helper
0.021
20720828JCB_W4-025
Solar/Wind Helper
0.064
20716028EGP_W2-019
Solar/Wind Helper
0.019
20715028HAN_X4-015
Solar/Wind Helper
0.057
219276PARKLANDSO C
Solar/Wind Helper
0.09
20714528FRN_Y2-051
Solar/Wind Helper
0.057
20720528MAN_W1-024
Solar/Wind Helper
0.028
966881AG1-559 GEN
Solar/Wind Helper
0.312
219612MATRIX C
Solar/Wind Helper
0.024
218438BLK ROCK C
Solar/Wind Helper
0.027
219249CENTRALDIV C
Solar/Wind Helper
0.01
219908AB1-139 C
Solar/Wind Helper
0.074
219919AE1-041 FULL
Solar/Wind Helper
0.004
20673728F2S_V4-070
Solar/Wind Helper
0.03
217211CAMDEN ST C
Solar/Wind Helper
0.005
217169METRODIV C
Solar/Wind Helper
0.004
20676728BRNX1-095
Solar/Wind Helper
0.03
207510AF2-138 C
Solar/Wind Helper
0.081
20674628WNG_W3-110
Solar/Wind Helper
0.089
24728805RICHG1
Adder
4.003
24728905RICHG2
Adder
4.003
970935AG2-582 GEN
Adder
239.406
274770LINCOLN ;1U
Adder
8.792
274771LINCOLN ;2U
Adder
8.792
274808UNIV PK N;4U
Adder
5.188
274803UNIV PARK;6U
Adder
6.05
972259AH1-714 GEN
Adder
19.76
238175AF1-290_GEN
Solar/Wind Helper
0.168
238169AE2-226 GEN1
Solar/Wind Helper
0.772
238170AE2-226 GEN2
Solar/Wind Helper
0.772
238120AE2-309 GEN
Solar/Wind Helper
0.552
23585401KL_K28_T16
Solar/Wind Helper
1.529
235020AA1-095 C
Solar/Wind Helper
0.057
23777901MDS_W4-102
Solar/Wind Helper
0.191
237034AC2-136 C
Solar/Wind Helper
0.244
237002AB1-128_GEN
Solar/Wind Helper
0.475
235063AE1-101 C2
Solar/Wind Helper
1.776
237001AB1-127_GEN
Solar/Wind Helper
0.473
23777801MSM_W1-116
Solar/Wind Helper
0.122
237025AB1-124 C
Solar/Wind Helper
0.175
237006AB1-125 GEN
Solar/Wind Helper
0.131
226929AD2-058 GEN
Solar/Wind Helper
0.108
315651AD1-115 GEN
Solar/Wind Helper
0.876
316447AC1-158 HLD
Solar/Wind Helper
3.175
205916AD1-020 GEN
Solar/Wind Helper
1.761
20390526W1-045 C
Solar/Wind Helper
0.36
208835TUHI V3-051
Solar/Wind Helper
0.025
208835TUHI V3-051
Solar/Wind Helper
0.025
3132123MT JACKSON
Solar/Wind Helper
0.764
233987AB2-037 GEN
Solar/Wind Helper
2.381
233933AB2-153 GEN
Solar/Wind Helper
0.236
232424Y1-079 C
Solar/Wind Helper
0.118
233944AB2-135 GEN
Solar/Wind Helper
0.598
233946AB2-136 GEN
Solar/Wind Helper
0.577
234036AF2-325 C
Solar/Wind Helper
0.043
233901CHERRYDALE C
Solar/Wind Helper
0.236
232408W1-005 C
Solar/Wind Helper
0.516
232410W1-006 C
Solar/Wind Helper
0.516
233939AC1-091 C
Solar/Wind Helper
0.356
233970AC1-092 C
Solar/Wind Helper
0.356
966001AG1-469 GEN
Solar/Wind Helper
0.255
230433AD2-135 GEN
Solar/Wind Helper
0.017
230407AD2-065 C
Solar/Wind Helper
0.041
219921AF1-264
Solar/Wind Helper
0.052
219615MILLCREEK C
Solar/Wind Helper
0.027
963401AG1-189 GEN
Solar/Wind Helper
0.056
963391AG1-188 GEN
Solar/Wind Helper
0.083
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.19
20716928W4-060COL
Solar/Wind Helper
0.052
218440SUMMTASSOC C
Solar/Wind Helper
0.016
20673828FLE_V3-070
Solar/Wind Helper
0.091
207442AE1-156 GEN
Solar/Wind Helper
0.326
20676128MHD_W3-029
Solar/Wind Helper
0.096
20671828STAW2-080
Solar/Wind Helper
0.027
217081WEATEXAS C
Solar/Wind Helper
0.013
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.006
217204WCALDSOLAR C
Solar/Wind Helper
0.003
207471AF2-354 C
Solar/Wind Helper
0.168
20674928WA_W3-044
Solar/Wind Helper
0.098
20676228FRD_X1-012
Solar/Wind Helper
0.091
964851AG1-348 GEN
Solar/Wind Helper
0.081
20674128FR_U2-059
Solar/Wind Helper
0.004
966111AG1-480 GEN
Solar/Wind Helper
0.044
211065PSPA IPP
Solar/Wind Helper
0.15
211065PSPA IPP
Solar/Wind Helper
0.15
CBM West 1LTFEXP_CBM-W1->PJM
CBM
146.579
CBM South 1LTFEXP_CBM-S1->PJM
CBM
28.544
MECLTFEXP_MEC->PJM
CLTF
15.979
SIGELTFEXP_SIGE->PJM
CLTF
0.506
CBM West 2LTFEXP_CBM-W2->PJM
CBM
111.893
LAGNLTFEXP_LAGN->PJM
CLTF
14.521
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.32
TVALTFEXP_TVA->PJM
CLTF
7.111
NYPJM->LTFIMP_NY
CLTF
4.554
LGEELTFEXP_LGEE->PJM
CLTF
6.753
WECLTFEXP_WEC->PJM
CLTF
3.866
AG2-052LTFEXP_AG2-052->PJM
LTF
0.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.364

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_MP-500-008A_SRT-SL


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_MP-500-008A_SRT-SL
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:125.38 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:4754.33
MW Contribution:7.12
Bus #Bus NameTypeMW Contribution
972239AH1-704 GEN
50/50
2.78
962771AG1-126 GEN
Solar/Wind Harmer
33.269
270459AD2-067 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Harmer
0.007
961821AG1-024 GEN
Solar/Wind Harmer
4.91
270520AE2-214 GEN
Solar/Wind Harmer
0.013
270284AF1-227 GEN1
Solar/Wind Harmer
0.01
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
253383AE2-342_GEN
Solar/Wind Harmer
0.003
241973AD2-163_GEN1
Solar/Wind Harmer
0.006
945631AF1-228 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
3.02
943851AF1-053 GEN
Solar/Wind Harmer
2.092
270156DARBY CT1
Adder
10.05
270157DARBY CT2
Adder
10.026
270158DARBY CT3
Adder
9.866
270578AF1-285 GEN2
Solar/Wind Harmer
0.518
970689AG2-444 GEN
Solar/Wind Harmer
15.861
270432AC2-029 GEN
Solar/Wind Harmer
3.428
940611AE2-048 GEN
Solar/Wind Harmer
18.967
941391AE2-136 GEN
Solar/Wind Harmer
10.684
270302AB2-170 GEN
Solar/Wind Harmer
0.005
270317AD1-130_GEN
Solar/Wind Harmer
0.011
971653AH1-327 GEN
Solar/Wind Harmer
1.08
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.824
970179AG2-119 GEN
Solar/Wind Harmer
6.658
270340AC2-060 GEN
Solar/Wind Harmer
0.009
970879AG2-548 GEN
Solar/Wind Harmer
6.645
253372AE2-315 SEC3
Adder
1.989
253372AE2-315 SEC3
Adder
1.989
25306009OHH W.
Adder
3.018
253349AC2-067 GEN
Solar/Wind Harmer
2.296
253400AC2-068 GEN
Solar/Wind Harmer
0.923
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.92
965051AG1-369 GEN
Solar/Wind Harmer
3.609
971567AH1-282 GEN
Solar/Wind Harmer
10.843
247607V1-011 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
7.21
971989AH1-539 GEN
Solar/Wind Harmer
3.109
963791AG1-232 GEN
Solar/Wind Harmer
9.689
24729505KEY G4
Adder
6.671
270071AF1-092 GEN
Solar/Wind Harmer
13.737
270024AE2-089 GEN
Solar/Wind Harmer
0.008
971985AH1-537 GEN
Solar/Wind Harmer
2.123
965101AG1-375 GEN
Solar/Wind Harmer
7.135
270297AD1-101 GEN
Solar/Wind Harmer
0.002
270367AC2-061_GEN
Solar/Wind Harmer
0.006
971673AH1-337 GEN
Solar/Wind Harmer
4.631
971029AG2-637 GEN
Solar/Wind Harmer
10.686
270543AE2-219 C
Solar/Wind Harmer
0.004
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.002
25196308WSDLE2
Adder
8.924
25196208WSDLE1
Adder
8.902
25196708WSDLE6
Adder
8.879
25196508WSDLE4
Adder
8.656
945581AF1-223 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
10.632
971609AH1-304 GEN
Solar/Wind Harmer
1.157
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
2.826
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
7.898
971771AH1-392 GEN
Solar/Wind Harmer
7.046
970289AG2-191 GEN
Solar/Wind Harmer
1.339
971619AH1-309 GEN
Solar/Wind Harmer
3.169
971769AH1-391 GEN
Solar/Wind Harmer
7.844
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196108MFTGT2
Adder
1.54
25196108MFTGT2
Adder
1.43
270536AF1-215 GEN2
Solar/Wind Harmer
0.009
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
4.146
971549AH1-272 GEN
Solar/Wind Harmer
14.344
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274775LINCOLN ;6U
Adder
8.364
274776LINCOLN ;7U
Adder
8.364
274777LINCOLN ;8U
Adder
8.364
274814UNIV PK N;0U
Adder
4.998
274807UNIV PK N;3U
Adder
4.987
274805UNIV PK N;1U
Adder
4.965
274811UNIV PK N;7U
Adder
4.954
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.181
960591AF2-350 GEN
Solar/Wind Harmer
6.884
274827FISK ;RP
Adder
7.655
972227AH1-698 GEN1
Adder
2.573
963841AG1-237 GEN
Solar/Wind Harmer
2.978
274687WILL CNTY;4U
Adder
27.495
274687WILL CNTY;4U
Adder
27.495
274675JOLIET 29;7U
Adder
30.175
274675JOLIET 29;7U
Adder
29.097
972163AH1-664 GEN
Solar/Wind Harmer
7.639
972165AH1-665 GEN
Solar/Wind Harmer
6.118
274731ELWOOD EC;2P
Adder
16.163
274733ELWOOD EC;3P
Adder
16.163
274735ELWOOD EC;4P
Adder
16.163
274728ELWOOD EC;5P
Adder
16.163
970833AG2-524 GEN
Solar/Wind Harmer
7.542
970833AG2-524 GEN
Solar/Wind Harmer
5.028
945641AF1-229 GEN
Solar/Wind Harmer
0.001
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
276868AE1-113 GEN
Solar/Wind Harmer
1.363
276882AE2-255 GEN
Solar/Wind Harmer
0.794
238109AE1-109 GEN2
Solar/Wind Helper
0.106
238110AE1-109 GEN3
Solar/Wind Helper
0.106
238152AF2-075_GEN
Solar/Wind Helper
0.683
23546401DTGZ2-030
Solar/Wind Helper
0.086
238208AF1-136 C
Solar/Wind Helper
0.211
238126S14_GEN_1
Solar/Wind Helper
0.766
237085AD2-009_GEN
Solar/Wind Helper
1.588
3138216PACIFIC
Solar/Wind Helper
0.043
316411AF1-147_GEN1
Solar/Wind Helper
0.86
316415AF1-147_GEN2
Solar/Wind Helper
0.86
959381AF2-229 GEN
Solar/Wind Helper
0.345
23750501ELLIOTTS
Solar/Wind Helper
0.571
3141426STAFORD
Solar/Wind Helper
0.051
960921AF2-383 GEN
Solar/Wind Helper
0.352
205943AE1-185 GEN
Solar/Wind Helper
0.492
205956AE1-196_GEN
Solar/Wind Helper
0.492
205932AD2-116_GEN
Solar/Wind Helper
0.492
233935AB2-179 C
Solar/Wind Helper
1.227
232436AB1-176 C
Solar/Wind Helper
0.043
233923SMA
Solar/Wind Helper
0.927
233990AG1-397 GEN
Solar/Wind Helper
0.261
234033AF1-007_GEN
Solar/Wind Helper
6.787
232432Z2-076 GEN
Solar/Wind Helper
0.065
964001AG1-254 GEN
Solar/Wind Helper
0.924
228754AB1-001 C
Solar/Wind Helper
0.025
227927V4-067C
Solar/Wind Helper
0.01
219914AD2-027 C
Solar/Wind Helper
0.111
219272CLEANLIGHT C
Solar/Wind Helper
0.025
219688LUMSOLAR_S C
Solar/Wind Helper
0.038
219607WPEMNERT C
Solar/Wind Helper
0.077
214067T20SOLAR
Solar/Wind Helper
0.011
203975AE1-071-GEN
Solar/Wind Helper
2.41
20715728PEM_W1-119
Solar/Wind Helper
0.093
20715828PEM_W1-120
Solar/Wind Helper
0.093
207459AE1-142 C O1
Solar/Wind Helper
0.28
316164AC1-076 GEN
Solar/Wind Helper
1.062
219620RIDERU C
Solar/Wind Helper
0.001
24318805MLG1
50/50
9.842
23559001PLEAS1
50/50
5.385
270051AF1-062 GEN
50/50
11.434
970153AG2-106 GEN
Solar/Wind Harmer
21.245
961921AG1-034 GEN
Solar/Wind Harmer
7.364
241955AC1-078 GEN
Solar/Wind Harmer
0.007
241974AD2-163_GEN2
Solar/Wind Harmer
0.006
942051AE2-217 GEN
Solar/Wind Harmer
14.169
24721905FLATG4
Adder
22.865
970605AG2-385 GEN
Solar/Wind Harmer
4.731
270391AF1-285 GEN3
Solar/Wind Harmer
0.518
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.012
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270273AD2-016 GEN
Solar/Wind Harmer
0.792
972173AH1-669 GEN
Solar/Wind Harmer
3.811
270512AE1-227 GEN2
Solar/Wind Harmer
1.904
270291AC1-194 GEN
Solar/Wind Harmer
5.884
253415AE1-040 GEN
Solar/Wind Harmer
0.003
970065AG2-057 GEN
Solar/Wind Harmer
0.735
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
970191AG2-125 GEN
Solar/Wind Harmer
1.876
253406AD2-031_GEN
Solar/Wind Harmer
0.543
270491AE1-102 GEN2
Solar/Wind Harmer
0.945
270377AD1-106 GEN
Solar/Wind Harmer
2.761
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.047
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.394
959331AF2-224 GEN
Solar/Wind Harmer
5.057
965021AG1-366 GEN
Solar/Wind Harmer
2.408
270588AE1-091_GEN
Solar/Wind Harmer
5.649
971191AH1-055 GEN
Solar/Wind Harmer
18.515
944531AF1-118 GEN
Solar/Wind Harmer
32.203
270043AE2-236 GEN
Solar/Wind Harmer
4.607
270258AD1-119 GEN
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
5.953
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
10.684
270404AC1-167 GEN
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
8.745
252510AF1-249 C
Solar/Wind Harmer
0.055
970031AG2-029 GEN
Solar/Wind Harmer
4.625
25194608D.CRK4
Adder
1.676
270222AC2-111 GEN
Solar/Wind Harmer
3.603
970513AG2-328 GEN
Solar/Wind Harmer
3.076
970517AG2-330 GEN
Solar/Wind Harmer
18.457
970349AG2-230 GEN
Solar/Wind Harmer
10.632
946031AF1-268 GEN
Solar/Wind Harmer
6.74
958821AF2-173 GEN
Solar/Wind Harmer
9.902
270004AE1-209 GEN
Solar/Wind Harmer
1.532
270437AC2-090 C
Solar/Wind Harmer
0.003
247643Z2-116 C
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.775
970291AG2-192 GEN
Solar/Wind Harmer
0.705
945111AF1-176 GEN
Solar/Wind Harmer
5.709
247642Z2-115 C
Solar/Wind Harmer
0.003
24642205MAYFLWER
Adder
0.641
24441205WTRV SLR C
Solar/Wind Harmer
0
25196008MFTGT1
Adder
1.353
270356AE2-297 GEN
Solar/Wind Harmer
0.009
970217AG2-149 GEN
Solar/Wind Harmer
6.066
247604X1-042
Adder
0.418
270535AF1-215 GEN1
Solar/Wind Harmer
0.009
964401AG1-302 GEN
Solar/Wind Harmer
0.001
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.935
970243AG2-164 GEN
Solar/Wind Harmer
4.047
970519AG2-331 GEN
Solar/Wind Harmer
17.988
970699AG2-449 GEN
Solar/Wind Harmer
1.73
274752CRETE EC ;2U
Adder
8.172
274753CRETE EC ;3U
Adder
8.172
274772LINCOLN ;3U
Adder
8.364
274724RIVER EC ;11
Adder
17.549
958171AF2-111 GEN
Solar/Wind Harmer
17.278
274802UNIV PARK;5U
Adder
5.755
276806AD2-047 C O1
Solar/Wind Harmer
3.901
970941AG2-585 GEN
Solar/Wind Harmer
8.605
274826FISK ;BP
Adder
10.802
24728705AND G3
Adder
7.914
24728505AND G1
Adder
3.784
274800UNIV PARK;3U
Adder
5.751
972038AH1-567 GEN2
Adder
0.36
972228AH1-698 GEN2
Adder
3.654
972167AH1-666 GEN
Solar/Wind Harmer
5.505
276897AD1-100 C
Solar/Wind Harmer
0.009
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
22.464
274676JOLIET 29;8U
Adder
29.097
274729ELWOOD EC;1P
Adder
16.163
274730ELWOOD EC;6P
Adder
13.491
276893AG1-478 C
Solar/Wind Harmer
0.272
270541AE2-072 C
Solar/Wind Harmer
0.009
943121AE2-341 GEN
Solar/Wind Harmer
11.459
943591AF1-030 GEN
Solar/Wind Harmer
7.62
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
276805AD2-038 GEN
Solar/Wind Harmer
0.002
964991AG1-363 GEN
Solar/Wind Helper
4.969
316097T157 G90
Solar/Wind Helper
1.455
23750701CROSSCHOOL
Solar/Wind Helper
1.397
238148AE2-230_GEN2
Solar/Wind Helper
0.48
238127S14_GEN_2
Solar/Wind Helper
0.766
238118U2-030_1
Solar/Wind Helper
0.314
237080AD1-060 GEN
Solar/Wind Helper
0.33
237038AE2-054 C
Solar/Wind Helper
0.262
235062AE1-101 C1
Solar/Wind Helper
1.6
23779801AA1-109
Solar/Wind Helper
0.187
223401AF1-299 GEN
Solar/Wind Helper
0.355
316006AB2-029 C
Solar/Wind Helper
0.113
966131AG1-482 GEN
Solar/Wind Helper
0.132
237048AF1-022 C
Solar/Wind Helper
0.159
233930AB2-032 GEN
Solar/Wind Helper
0.368
233915AB1-141 GEN
Solar/Wind Helper
0.486
232422X3-066 FULL
Solar/Wind Helper
0.11
232426Y1-080 FULL
Solar/Wind Helper
0.038
233964AF2-378 GEN
Solar/Wind Helper
0.04
233998TM1NIN_3.36
Solar/Wind Helper
0.253
232404W1-003 C
Solar/Wind Helper
0.49
232428Y3-058 C
Solar/Wind Helper
0.327
232434Z2-077 GEN
Solar/Wind Helper
0.123
233954AC2-188 GEN
Solar/Wind Helper
0.225
233950AC2-186 GEN
Solar/Wind Helper
0.112
233972AC1-094 C
Solar/Wind Helper
0.292
316045AC1-158 PL2
Solar/Wind Helper
4.009
230511AF1-262
Solar/Wind Helper
0.014
230434AG1-499 GEN
Solar/Wind Helper
0.222
228728W1-130C
Solar/Wind Helper
0.052
219258KINSLEYDEP C
Solar/Wind Helper
0.074
219904AC1-010 C
Solar/Wind Helper
0.058
218660EHAMPSOLAR C
Solar/Wind Helper
0.032
219907AC1-030 C
Solar/Wind Helper
0.033
219686LUMSOLAR_N C
Solar/Wind Helper
0.038
219304NAMERICA C
Solar/Wind Helper
0.127
316254AC1-120 GEN1
Solar/Wind Helper
1.026
20720728JCB_W1-129
Solar/Wind Helper
0.055
207445AB1-138_GEN
Solar/Wind Helper
0.101
963711AG1-223 GEN
Solar/Wind Helper
0.062
20714828MDF_W3-079
Solar/Wind Helper
0.126
219680HOPEWELLV C1
Solar/Wind Helper
0.003
207454AA2-184 E
Solar/Wind Helper
0.299
20715228NPK_W1-113
Solar/Wind Helper
0.075
270119AB2-067 GEN1
50/50
6.869
270120AB2-067 GEN2
50/50
6.869
24318905MLG2
50/50
6.89
270471AD2-092_GEN
Solar/Wind Harmer
0.006
942861AE2-305 GEN
Solar/Wind Harmer
6.118
970077AG2-063 GEN
Solar/Wind Harmer
4.471
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
938701AE1-092 GEN
Solar/Wind Harmer
12.484
971655AH1-328 GEN
Solar/Wind Harmer
2.758
964601AG1-323 GEN
Solar/Wind Harmer
3.106
964601AG1-323 GEN
Solar/Wind Harmer
2.071
270518AE2-148 GEN
Solar/Wind Harmer
0.667
972269AH1-719 GEN
Adder
2.501
972159AH1-661 GEN
Adder
1.082
253378AE2-206_GEN
Solar/Wind Harmer
0.004
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
3.237
971199AH1-059 GEN
Solar/Wind Harmer
2.99
241960AC2-195 GEN
Solar/Wind Harmer
0.006
970935AG2-582 GEN
Adder
242.403
25326509SID D
Adder
1.4
971073AG2-665 GEN
Solar/Wind Harmer
6.645
25326109MON D
Adder
1.391
971201AH1-060 GEN
Solar/Wind Harmer
1.471
25322209TAIT E
Adder
10.262
25322209TAIT E
Adder
10.031
253370AE2-315 SEC1
Adder
2.103
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
246938BC-WTG3
Solar/Wind Harmer
0.263
246937BC-WTG2
Solar/Wind Harmer
0.295
971231AH1-075 GEN
Solar/Wind Harmer
0.833
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
970611AG2-400 GEN
Solar/Wind Harmer
7.225
970627AG2-408 GEN
Solar/Wind Harmer
2.167
270007AE1-245 C
Solar/Wind Harmer
0.002
970623AG2-406 GEN
Solar/Wind Harmer
1.309
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25183208HLCRTG
Solar/Wind Harmer
0.011
944541AF1-119 GEN
Solar/Wind Harmer
0.479
960971AF2-388 GEN
Solar/Wind Harmer
4.192
942221AE2-234 GEN
Solar/Wind Harmer
0.036
252519AF1-045_GEN
Solar/Wind Harmer
6.204
252516AE2-318_GEN
Solar/Wind Harmer
5.503
970621AG2-405 GEN
Solar/Wind Harmer
1.305
247621Y3-024
Adder
0.246
970883AG2-550 GEN
Solar/Wind Harmer
7.123
970885AG2-551 GEN
Solar/Wind Harmer
2.374
270201AC2-176 GEN
Solar/Wind Harmer
0.001
25194408D.CRK1
Adder
7.711
25194508D.CRK3
Adder
1.442
964611AG1-324 GEN
Solar/Wind Harmer
0.534
252509AD1-136 GEN
Solar/Wind Harmer
0.036
970321AG2-212 GEN
Solar/Wind Harmer
3.076
270599AE1-208 GEN
Solar/Wind Harmer
6.495
270031AE2-169
Solar/Wind Harmer
3.897
270383AD1-128 GEN
Solar/Wind Harmer
0.004
270186AC1-089 GEN
Solar/Wind Harmer
0.004
247620Y3-023
Adder
0.466
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.834
960441AF2-335 GEN
Solar/Wind Harmer
7.065
270216AD2-079_GEN
Solar/Wind Harmer
0.001
971613AH1-306 GEN
Solar/Wind Harmer
3.385
24728805RICHG1
Adder
3.82
24728905RICHG2
Adder
3.82
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
14.072
961051AF2-396 GEN
Solar/Wind Harmer
9.381
270526AF1-158 GEN
Solar/Wind Harmer
0.009
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
8.77
965791AG1-447 GEN
Solar/Wind Harmer
6.431
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.73
274770LINCOLN ;1U
Adder
8.364
274771LINCOLN ;2U
Adder
8.364
274808UNIV PK N;4U
Adder
4.933
966841AG1-555 GEN
Solar/Wind Harmer
0.781
274803UNIV PARK;6U
Adder
5.755
274888KELLY CRK;1U
Solar/Wind Harmer
0.404
274887GEN-1.85
Solar/Wind Harmer
0.181
276843GEN-1.7
Solar/Wind Harmer
0.223
958011AF2-095 GEN
Solar/Wind Harmer
9.913
972259AH1-714 GEN
Adder
18.805
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
3.993
958481AF2-142 GEN
Solar/Wind Harmer
10.238
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
0.923
971573AH1-285 GEN
Solar/Wind Harmer
1.271
971677AH1-339 GEN
Solar/Wind Harmer
0.768
958491AF2-143 GEN
Solar/Wind Harmer
10.205
274879MINONK ;1U
Solar/Wind Harmer
0.287
238175AF1-290_GEN
Solar/Wind Helper
0.148
238169AE2-226 GEN1
Solar/Wind Helper
0.677
238170AE2-226 GEN2
Solar/Wind Helper
0.677
238120AE2-309 GEN
Solar/Wind Helper
0.487
235020AA1-095 C
Solar/Wind Helper
0.051
23777901MDS_W4-102
Solar/Wind Helper
0.171
23585401KL_K28_T16
Solar/Wind Helper
1.328
237034AC2-136 C
Solar/Wind Helper
0.219
237002AB1-128_GEN
Solar/Wind Helper
0.427
235063AE1-101 C2
Solar/Wind Helper
1.6
237001AB1-127_GEN
Solar/Wind Helper
0.426
23777801MSM_W1-116
Solar/Wind Helper
0.11
237025AB1-124 C
Solar/Wind Helper
0.159
237006AB1-125 GEN
Solar/Wind Helper
0.119
226929AD2-058 GEN
Solar/Wind Helper
0.096
205916AD1-020 GEN
Solar/Wind Helper
1.656
20390526W1-045 C
Solar/Wind Helper
0.338
208835TUHI V3-051
Solar/Wind Helper
0.023
208835TUHI V3-051
Solar/Wind Helper
0.023
233987AB2-037 GEN
Solar/Wind Helper
2.264
233933AB2-153 GEN
Solar/Wind Helper
0.225
232424Y1-079 C
Solar/Wind Helper
0.112
233944AB2-135 GEN
Solar/Wind Helper
0.569
233946AB2-136 GEN
Solar/Wind Helper
0.549
234036AF2-325 C
Solar/Wind Helper
0.041
233901CHERRYDALE C
Solar/Wind Helper
0.225
232408W1-005 C
Solar/Wind Helper
0.49
232410W1-006 C
Solar/Wind Helper
0.49
233939AC1-091 C
Solar/Wind Helper
0.338
233970AC1-092 C
Solar/Wind Helper
0.338
315651AD1-115 GEN
Solar/Wind Helper
0.76
316447AC1-158 HLD
Solar/Wind Helper
2.756
230433AD2-135 GEN
Solar/Wind Helper
0.016
230407AD2-065 C
Solar/Wind Helper
0.039
219921AF1-264
Solar/Wind Helper
0.049
219615MILLCREEK C
Solar/Wind Helper
0.026
963401AG1-189 GEN
Solar/Wind Helper
0.054
963391AG1-188 GEN
Solar/Wind Helper
0.079
20714928UPF_X1-085
Solar/Wind Helper
0.005
20720628TIN_W1-124
Solar/Wind Helper
0.183
270166AC1-044 GEN3
50/50
6.869
23559101PLEAS2
50/50
5.385
270122AB2-093 CT
50/50
3.689
962761AG1-125 GEN
Solar/Wind Harmer
33.269
970149AG2-104 GEN
Solar/Wind Harmer
35.932
970155AG2-107 GEN
Solar/Wind Harmer
21.245
270349AD2-093_GEN
Solar/Wind Harmer
0.006
24721705FLATG2
Adder
22.865
270159DARBY CT4
Adder
9.89
970593AG2-378 GEN
Solar/Wind Harmer
1.75
270223U2-072_GEN1
Solar/Wind Harmer
0.001
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.012
270462AD2-086
Solar/Wind Harmer
0.016
971995AH1-542 GEN
Solar/Wind Harmer
2.81
270263AC1-001 GEN
Solar/Wind Harmer
0.758
270510AE1-227 GEN1
Solar/Wind Harmer
1.904
241813AF1-122_GEN
Solar/Wind Harmer
3.294
25326309TAIT D
Adder
1.153
960071AF2-298 GEN
Solar/Wind Harmer
3.651
253370AE2-315 SEC1
Adder
2.103
253371AE2-315 SEC2
Adder
1.989
927014AC1-188 GEN
Solar/Wind Harmer
0.004
246936BC-WTG1
Solar/Wind Harmer
0.295
270489AE1-102 GEN1
Solar/Wind Harmer
0.945
965421AG1-410 GEN
Solar/Wind Harmer
21.788
247521TR3_G114
Solar/Wind Harmer
0.263
270246TR4_N_V150
Solar/Wind Harmer
0.047
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.226
965011AG1-365 GEN
Solar/Wind Harmer
7.225
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
2.096
958861AF2-177 GEN
Solar/Wind Harmer
3.092
247536S-71 GEN
Solar/Wind Harmer
0.287
945371AF1-202 GEN
Solar/Wind Harmer
0.001
25194608D.CRK4
Adder
1.676
270063AE2-323 C
Solar/Wind Harmer
0.006
252507AC2-088 GEN
Solar/Wind Harmer
0.323
970245AG2-165 GEN
Solar/Wind Harmer
3.076
944231AF1-091 GEN
Solar/Wind Harmer
1.885
270005AE1-210 C O1
Solar/Wind Harmer
1.532
965031AG1-367 GEN
Solar/Wind Harmer
7.073
970947AG2-589 GEN
Solar/Wind Harmer
0.236
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
5.183
970825AG2-519 GEN
Solar/Wind Harmer
2.509
24639705ELKHART HY
Adder
0.155
25196808ZIMRHP
Adder
76.799
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
270032AE2-172
Solar/Wind Harmer
4.701
970291AG2-192 GEN
Solar/Wind Harmer
0.916
945111AF1-176 GEN
Solar/Wind Harmer
12.568
270505AE1-170 C O1
Solar/Wind Harmer
7.393
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
3.67
247522W1-056 GEN
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.842
25196008MFTGT1
Adder
1.397
970773AG2-487 GEN
Solar/Wind Harmer
1.237
970373AG2-245 GEN
Solar/Wind Harmer
14.699
970515AG2-329 GEN
Solar/Wind Harmer
18.197
270055AF2-134 C O1
Solar/Wind Harmer
0.005
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
9.071
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
8.706
24791305MDL-5G
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
4.947
274751CRETE EC ;1U
Adder
8.172
274754CRETE EC ;4U
Adder
8.172
274773LINCOLN ;4U
Adder
8.364
274774LINCOLN ;5U
Adder
8.364
274723RIVER EC ;12
Adder
17.756
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.954
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.719
24728605AND G2
Adder
3.784
274801UNIV PARK;4U
Adder
5.751
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945681AF1-233 GEN
Solar/Wind Harmer
12.962
274676JOLIET 29;8U
Adder
30.175
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
16.202
939401AE1-172 GEN
Solar/Wind Harmer
5.109
276691AA1-018 GEN1
Solar/Wind Harmer
0.827
276901AD2-066 C O1
Solar/Wind Harmer
0.007
316095T157 G97
Solar/Wind Helper
1.455
23583801GRNGAP
Solar/Wind Helper
5.418
238108AE1-109 GEN1
Solar/Wind Helper
0.106
238185AF2-356 C
Solar/Wind Helper
2.425
238147AE2-230_GEN1
Solar/Wind Helper
0.478
238149AF1-291A_GEN
Solar/Wind Helper
0.137
235531U2-073 GEN
Solar/Wind Helper
3.034
235054AD2-180 GEN
Solar/Wind Helper
1.839
237061AD1-155 GEN
Solar/Wind Helper
0.051
238117U2-030
Solar/Wind Helper
0.314
238221AF1-254 C O1
Solar/Wind Helper
0.265
235067AD1-061 GEN
Solar/Wind Helper
0.478
237030AB1-096 C
Solar/Wind Helper
0.068
3141196NOKESVL
Solar/Wind Helper
0.999
226910AB2-157 C
Solar/Wind Helper
0.014
227287AC2-120 GEN
Solar/Wind Helper
0.335
223402AF1-300 C
Solar/Wind Helper
0.355
23751201ROTHROCK
Solar/Wind Helper
0.694
23562501BACKB
Solar/Wind Helper
0.842
205917AD1-020 ES
Solar/Wind Helper
0.356
233982AB2-133 GEN
Solar/Wind Helper
0.346
233918AB1-142 GEN
Solar/Wind Helper
0.486
233994AC2-023 GEN
Solar/Wind Helper
0.929
233996TM1833_GEN
Solar/Wind Helper
0.253
233997TMININ_4.2
Solar/Wind Helper
0.253
232406W1-004 FULL
Solar/Wind Helper
0.49
233940AF2-379 C
Solar/Wind Helper
0.06
234015AF2-250 C
Solar/Wind Helper
0.037
233952AC2-187 GEN
Solar/Wind Helper
0.225
233971AC1-093 C
Solar/Wind Helper
0.346
316044AC1-158 PL1
Solar/Wind Helper
1.252
316450AC1-158 RIC
Solar/Wind Helper
0.334
230430AE1-229_GEN
Solar/Wind Helper
3.26
230415AB2-049 C
Solar/Wind Helper
0.029
228729W2-030 C
Solar/Wind Helper
0.107
219623KINSLEYBEA C
Solar/Wind Helper
0.002
219766PARADISE C
Solar/Wind Helper
0.053
219912AD2-042 GEN
Solar/Wind Helper
0.145
219291REEVESSOUT C
Solar/Wind Helper
0.011
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219906AC1-017 C
Solar/Wind Helper
0.04
219348LDSOLAR C
Solar/Wind Helper
0.111
316170AC1-121 GEN2
Solar/Wind Helper
0.342
959561AF2-247 GEN
Solar/Wind Helper
0.02
20720828JCB_W4-025
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.018
20715028HAN_X4-015
Solar/Wind Helper
0.055
219276PARKLANDSO C
Solar/Wind Helper
0.086
20714528FRN_Y2-051
Solar/Wind Helper
0.055
20720528MAN_W1-024
Solar/Wind Helper
0.027
971997AH1-543 GEN
Solar/Wind Harmer
1.86
CBM West 1LTFEXP_CBM-W1->PJM
CBM
137.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
27.984
MECLTFEXP_MEC->PJM
CLTF
15.319
SIGELTFEXP_SIGE->PJM
CLTF
0.486
CPLELTFEXP_CPLE->PJM
CLTF
0.567
CBM West 2LTFEXP_CBM-W2->PJM
CBM
108.576
LAGNLTFEXP_LAGN->PJM
CLTF
14.268
CBM South 2LTFEXP_CBM-S2->PJM
CBM
7.432
TVALTFEXP_TVA->PJM
CLTF
7.011
NYPJM->LTFIMP_NY
CLTF
4.628
LGEELTFEXP_LGEE->PJM
CLTF
6.497
WECLTFEXP_WEC->PJM
CLTF
3.686
AG2-052LTFEXP_AG2-052->PJM
LTF
0.231
AH1-155LTFEXP_AH1-155->PJM
LTF
0.346

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#2942_05KAMMER 765_PP_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#2942_05KAMMER 765_PP_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.95 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5175.39
MW Contribution:12.28
Bus #Bus NameTypeMW Contribution
270051AF1-062 GEN
50/50
16.969
270475AD2-096_GEN
50/50
10
970153AG2-106 GEN
Solar/Wind Harmer
25.994
961921AG1-034 GEN
Solar/Wind Harmer
20.196
241955AC1-078 GEN
Solar/Wind Harmer
11.082
241974AD2-163_GEN2
Solar/Wind Harmer
2.945
942051AE2-217 GEN
Solar/Wind Harmer
26.379
942871AE2-306 GEN
Solar/Wind Harmer
1.313
270391AF1-285 GEN3
Solar/Wind Harmer
0.673
970605AG2-385 GEN
Solar/Wind Harmer
7.746
270485AE1-090_GEN
Solar/Wind Harmer
0.845
253338AC1-165 GEN
Solar/Wind Harmer
1.495
253333AC1-068 GEN
Solar/Wind Harmer
1.442
960801AF2-371 GEN
Solar/Wind Harmer
3.362
964871AG1-351 GEN
Solar/Wind Harmer
2.322
270273AD2-016 GEN
Solar/Wind Harmer
3.416
944531AF1-118 GEN
Solar/Wind Harmer
44.619
972173AH1-669 GEN
Solar/Wind Harmer
6.355
270043AE2-236 GEN
Solar/Wind Harmer
6.955
959331AF2-224 GEN
Solar/Wind Harmer
12.615
965021AG1-366 GEN
Solar/Wind Harmer
2.934
253303V4-073 C
Solar/Wind Harmer
0.146
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
970513AG2-328 GEN
Solar/Wind Harmer
22.419
970517AG2-330 GEN
Solar/Wind Harmer
20.333
253415AE1-040 GEN
Solar/Wind Harmer
1.412
970349AG2-230 GEN
Solar/Wind Harmer
18.681
270191TR4_S_V150
Solar/Wind Harmer
3.726
270247TR4_N_V136
Solar/Wind Harmer
1.057
24721905FLATG4
Adder
25.137
971617AH1-308 GEN
Solar/Wind Harmer
7.196
270491AE1-102 GEN2
Solar/Wind Harmer
1.608
270156DARBY CT1
50/50
13.604
270157DARBY CT2
50/50
13.571
270158DARBY CT3
50/50
13.354
270036AE2-216 BAT
50/50
8.921
962771AG1-126 GEN
Solar/Wind Harmer
59.614
270284AF1-227 GEN1
Solar/Wind Harmer
9.137
270286AF1-227 GEN2
Solar/Wind Harmer
3.38
270287AF1-227 GEN3
Solar/Wind Harmer
3.38
270459AD2-067 GEN
Solar/Wind Harmer
13.262
961821AG1-024 GEN
Solar/Wind Harmer
13.464
270520AE2-214 GEN
Solar/Wind Harmer
9.4
270054AF2-122 C O1
Solar/Wind Harmer
5.025
253383AE2-342_GEN
Solar/Wind Harmer
1.352
241973AD2-163_GEN1
Solar/Wind Harmer
2.945
943861AF1-054 GEN
Solar/Wind Harmer
5.682
943851AF1-053 GEN
Solar/Wind Harmer
2.746
270578AF1-285 GEN2
Solar/Wind Harmer
0.673
945631AF1-228 GEN
Solar/Wind Harmer
6.732
270302AB2-170 GEN
Solar/Wind Harmer
11.684
270317AD1-130_GEN
Solar/Wind Harmer
4.479
241972AD1-140 GEN
Solar/Wind Harmer
6.007
970689AG2-444 GEN
Solar/Wind Harmer
21.667
270432AC2-029 GEN
Solar/Wind Harmer
9.275
270269AC2-059
Solar/Wind Harmer
11.946
24729505KEY G4
Adder
8.242
270071AF1-092 GEN
Solar/Wind Harmer
18.992
253372AE2-315 SEC3
Adder
2.385
253372AE2-315 SEC3
Adder
2.385
958711AF2-162 GEN
Solar/Wind Harmer
1.273
965101AG1-375 GEN
Solar/Wind Harmer
12.544
25306009OHH W.
Adder
3.614
253349AC2-067 GEN
Solar/Wind Harmer
6.244
253400AC2-068 GEN
Solar/Wind Harmer
2.511
945581AF1-223 GEN
Solar/Wind Harmer
5.655
963791AG1-232 GEN
Solar/Wind Harmer
16.817
971347AH1-153 GEN
Solar/Wind Harmer
18.681
965051AG1-369 GEN
Solar/Wind Harmer
6.202
965041AG1-368 GEN
Solar/Wind Harmer
12.384
270024AE2-089 GEN
Solar/Wind Harmer
5.81
957201AF2-014 GEN
Solar/Wind Harmer
5.611
270435AC2-044 GEN
Solar/Wind Harmer
2.474
270340AC2-060 GEN
Solar/Wind Harmer
3.749
961761AG1-017 GEN
Solar/Wind Harmer
0.528
270543AE2-219 C
Solar/Wind Harmer
6.289
971029AG2-637 GEN
Solar/Wind Harmer
18.391
971673AH1-337 GEN
Solar/Wind Harmer
5.637
970115AG2-085 GEN
Solar/Wind Harmer
4.901
270594AE1-207 GEN
Solar/Wind Harmer
17.978
965461AG1-414 GEN
Solar/Wind Harmer
2.772
970289AG2-191 GEN
Solar/Wind Harmer
2.322
270240V3-007_GEN2
Solar/Wind Harmer
7.556
960681AF2-359 GEN
Solar/Wind Harmer
4.61
971771AH1-392 GEN
Solar/Wind Harmer
10.956
274775LINCOLN ;6U
Adder
10.257
274776LINCOLN ;7U
Adder
10.257
274777LINCOLN ;8U
Adder
10.257
274814UNIV PK N;0U
Adder
6.103
274807UNIV PK N;3U
Adder
6.089
274805UNIV PK N;1U
Adder
6.063
274811UNIV PK N;7U
Adder
6.05
972227AH1-698 GEN1
Adder
3.146
972037AH1-567 GEN1
Adder
0.221
274827FISK ;RP
Adder
9.358
274687WILL CNTY;4U
Adder
33.62
274687WILL CNTY;4U
Adder
33.62
274675JOLIET 29;7U
Adder
36.901
274675JOLIET 29;7U
Adder
35.583
274731ELWOOD EC;2P
Adder
19.763
274733ELWOOD EC;3P
Adder
19.763
274735ELWOOD EC;4P
Adder
19.763
274728ELWOOD EC;5P
Adder
19.763
274746AC1-111 G10
Adder
6.698
274744AC1-111 GEN8
Adder
6.698
25196408WSDLE3
Adder
10.507
25196308WSDLE2
Adder
10.416
25196208WSDLE1
Adder
10.39
25196708WSDLE6
Adder
10.364
25196508WSDLE4
Adder
10.103
274823ROCKFORD ;21
Adder
23.006
254304AE2-114 C
Solar/Wind Helper
0.216
241982AE2-343 S C
Solar/Wind Helper
0.22
241997AF1-093 GEN
Solar/Wind Helper
0.251
23750501ELLIOTTS
Solar/Wind Helper
0.617
20092526R32
Solar/Wind Helper
1.112
203961AE2-224 GEN
Solar/Wind Helper
2.307
20091526CHSTN_FL
Solar/Wind Helper
0.557
20090526Q36
Solar/Wind Helper
0.998
203993AD2-133_GEN1
Solar/Wind Helper
0.998
203846AF2-130 C
Solar/Wind Helper
0.431
238126S14_GEN_1
Solar/Wind Helper
0.648
941231AE2-117 GEN
Solar/Wind Helper
0.453
203855AF2-088 C
Solar/Wind Helper
0.146
203804AE2-113_GEN
Solar/Wind Helper
1.661
270119AB2-067 GEN1
50/50
18.357
270120AB2-067 GEN2
50/50
18.357
270160DARBY CT5
50/50
0.729
270161DARBY CT6
50/50
0.719
270466AD2-091
50/50
8.11
270471AD2-092_GEN
Solar/Wind Harmer
6.249
946101AF1-275 GEN
Solar/Wind Harmer
2.346
942861AE2-305 GEN
Solar/Wind Harmer
11.513
270224U2-072_GEN2
Solar/Wind Harmer
2.862
270227U2-072_GEN3
Solar/Wind Harmer
2.862
270228U2-072_GEN4
Solar/Wind Harmer
2.862
270231U2-072_GEN5
Solar/Wind Harmer
2.862
970077AG2-063 GEN
Solar/Wind Harmer
7.746
270518AE2-148 GEN
Solar/Wind Harmer
16.865
964601AG1-323 GEN
Solar/Wind Harmer
4.402
964601AG1-323 GEN
Solar/Wind Harmer
2.047
938701AE1-092 GEN
Solar/Wind Harmer
28.355
253378AE2-206_GEN
Solar/Wind Harmer
4.74
276820AF1-078_GEN
Solar/Wind Harmer
2.106
25326509SID D
Adder
1.698
25326109MON D
Adder
1.683
25322209TAIT E
Adder
12.344
25322209TAIT E
Adder
12.066
970611AG2-400 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
944541AF1-119 GEN
Solar/Wind Harmer
5.27
960971AF2-388 GEN
Solar/Wind Harmer
13.754
970321AG2-212 GEN
Solar/Wind Harmer
22.419
942221AE2-234 GEN
Solar/Wind Harmer
0.913
246938BC-WTG3
Solar/Wind Harmer
4.925
246937BC-WTG2
Solar/Wind Harmer
4.841
270599AE1-208 GEN
Solar/Wind Harmer
10.052
270031AE2-169
Solar/Wind Harmer
10.052
253394AE2-221_GEN
Solar/Wind Harmer
5.603
253398AE2-221_GEN2
Solar/Wind Harmer
5.603
270201AC2-176 GEN
Solar/Wind Harmer
6.336
964611AG1-324 GEN
Solar/Wind Harmer
1.452
964611AG1-324 GEN
Solar/Wind Harmer
0.644
247621Y3-024
Adder
0.297
970883AG2-550 GEN
Solar/Wind Harmer
12.281
970885AG2-551 GEN
Solar/Wind Harmer
2.856
970825AG2-519 GEN
Solar/Wind Harmer
12.934
960441AF2-335 GEN
Solar/Wind Harmer
12.253
270383AD1-128 GEN
Solar/Wind Harmer
7.465
24379505HDWTR1G C
Solar/Wind Harmer
9.658
270209AC1-174_GEN
Solar/Wind Harmer
6.816
926881AC1-175 GEN
Solar/Wind Harmer
6.816
965681AG1-436 GEN
Solar/Wind Harmer
15.255
965791AG1-447 GEN
Solar/Wind Harmer
7.805
270216AD2-079_GEN
Solar/Wind Harmer
0.738
247620Y3-023
Adder
0.56
274770LINCOLN ;1U
Adder
10.257
274771LINCOLN ;2U
Adder
10.257
274808UNIV PK N;4U
Adder
6.023
972259AH1-714 GEN
Adder
23.016
274803UNIV PARK;6U
Adder
7.033
24728805RICHG1
Adder
4.555
24728905RICHG2
Adder
4.555
274674JOLIET 9 ;6U
Adder
18.512
274696ROCKY RD ;4P
Adder
13.603
274695ROCKY RD ;2P
Adder
13.289
274693ROCKY RD ;1P
Adder
13.158
274697ROCKY RD ;3P
Adder
3.61
274683WAUKEGAN ;8U
Adder
25.124
274683WAUKEGAN ;8U
Adder
21.178
25194408D.CRK1
Adder
8.991
25194508D.CRK3
Adder
1.681
23652301WDPWR_K20
Solar/Wind Helper
0.139
241967AE2-285_GEN
Solar/Wind Helper
0.629
241801AE1-079 GEN
Solar/Wind Helper
0.245
241985AE1-237 GEN
Solar/Wind Helper
0.245
962101AG1-054 GEN
Solar/Wind Helper
0.639
946071AF1-272 GEN
Solar/Wind Helper
2.599
23585401KL_K28_T16
Solar/Wind Helper
1.182
203955AF1-039 C O1
Solar/Wind Helper
0.351
944781AF1-143 GEN
Solar/Wind Helper
2.342
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.34
20088926STNY CRK
Solar/Wind Helper
0.78
270166AC1-044 GEN3
50/50
18.357
270159DARBY CT4
50/50
13.387
962761AG1-125 GEN
Solar/Wind Harmer
59.614
970149AG2-104 GEN
Solar/Wind Harmer
73.623
970155AG2-107 GEN
Solar/Wind Harmer
25.994
270349AD2-093_GEN
Solar/Wind Harmer
6.249
270223U2-072_GEN1
Solar/Wind Harmer
2.862
270578AF1-285 GEN2
Solar/Wind Harmer
1.75
270391AF1-285 GEN3
Solar/Wind Harmer
1.75
970593AG2-378 GEN
Solar/Wind Harmer
2.869
270462AD2-086
Solar/Wind Harmer
9.72
253343AC1-166 GEN
Solar/Wind Harmer
1.495
253325AC1-069 GEN
Solar/Wind Harmer
1.442
25326309TAIT D
Adder
1.387
960071AF2-298 GEN
Solar/Wind Harmer
6.296
965011AG1-365 GEN
Solar/Wind Harmer
12.615
253370AE2-315 SEC1
Adder
2.522
253371AE2-315 SEC2
Adder
2.385
965651AG1-433 GEN
Solar/Wind Harmer
6.877
970245AG2-165 GEN
Solar/Wind Harmer
22.419
958861AF2-177 GEN
Solar/Wind Harmer
13.71
971995AH1-542 GEN
Solar/Wind Harmer
13.79
945371AF1-202 GEN
Solar/Wind Harmer
8.699
247521TR3_G114
Solar/Wind Harmer
4.176
270246TR4_N_V150
Solar/Wind Harmer
1.057
24721705FLATG2
Adder
25.137
965421AG1-410 GEN
Solar/Wind Harmer
37.184
246936BC-WTG1
Solar/Wind Harmer
4.841
270489AE1-102 GEN1
Solar/Wind Harmer
1.608
247536S-71 GEN
Solar/Wind Harmer
4.98
270005AE1-210 C O1
Solar/Wind Harmer
6.717
965031AG1-367 GEN
Solar/Wind Harmer
12.29
270063AE2-323 C
Solar/Wind Harmer
2.705
24695305TIMB G C
Solar/Wind Harmer
6.75
970825AG2-519 GEN
Solar/Wind Harmer
2.886
270263AC1-001 GEN
Solar/Wind Harmer
1.282
270032AE2-172
Solar/Wind Harmer
5.689
970291AG2-192 GEN
Solar/Wind Harmer
1.589
942081AE2-220 GEN
Solar/Wind Harmer
7.808
270239V3-007_GEN1
Solar/Wind Harmer
2.102
24639705ELKHART HY
Adder
0.187
274773LINCOLN ;4U
Adder
10.257
274774LINCOLN ;5U
Adder
10.257
274723RIVER EC ;12
Adder
21.689
274751CRETE EC ;1U
Adder
9.969
274754CRETE EC ;4U
Adder
9.969
274812UNIV PK N;8U
Adder
6.05
274801UNIV PARK;4U
Adder
7.031
274676JOLIET 29;8U
Adder
36.901
274674JOLIET 9 ;6U
Adder
18.512
274732ELWOOD EC;7P
Adder
19.763
274745AC1-111 GEN9
Adder
6.698
274682WAUKEGAN ;7U
Adder
21.437
274828WAUKEGAN ;BP
Adder
13.169
25194608D.CRK4
Adder
1.955
24728605AND G2
Adder
4.529
274822ROCKFORD ;11
Adder
23.174
972235AH1-702 GEN1
Adder
2.974
25196808ZIMRHP
Adder
57.753
254303AC2-168 GEN
Solar/Wind Helper
0.156
237046AF1-021 C
Solar/Wind Helper
0.468
241966AE1-183 GEN
Solar/Wind Helper
0.251
238185AF2-356 C
Solar/Wind Helper
2.051
20089226LOOKOUT
Solar/Wind Helper
0.549
20088826HIGHLAND
Solar/Wind Helper
0.858
20094526CT_V3-030
Solar/Wind Helper
0.452
235054AD2-180 GEN
Solar/Wind Helper
1.586
964201AG1-281 GEN
Solar/Wind Helper
0.463
238117U2-030
Solar/Wind Helper
0.272
235531U2-073 GEN
Solar/Wind Helper
2.578
964391AG1-301 GEN
Solar/Wind Helper
0.452
203954AE2-126 C
Solar/Wind Helper
0.449
23751201ROTHROCK
Solar/Wind Helper
0.661
238206AE2-263_GEN
Solar/Wind Helper
0.87
959471AF2-238 GEN
Solar/Wind Helper
0.445
203860AG1-193 C
Solar/Wind Helper
0.222
23562501BACKB
Solar/Wind Helper
0.804
253432AC1-085 GEN2
Solar/Wind Harmer
0.293
962031AG1-047 GEN
Solar/Wind Harmer
3.725
957741AF2-068 GEN
Solar/Wind Harmer
18.489
970031AG2-029 GEN
Solar/Wind Harmer
36.885
958821AF2-173 GEN
Solar/Wind Harmer
17.206
270004AE1-209 GEN
Solar/Wind Harmer
6.717
946031AF1-268 GEN
Solar/Wind Harmer
10.188
253406AD2-031_GEN
Solar/Wind Harmer
1.568
970289AG2-191 GEN
Solar/Wind Harmer
0.938
970291AG2-192 GEN
Solar/Wind Harmer
0.853
247642Z2-115 C
Solar/Wind Harmer
0.078
270437AC2-090 C
Solar/Wind Harmer
6.819
247643Z2-116 C
Solar/Wind Harmer
0.085
274772LINCOLN ;3U
Adder
10.257
274724RIVER EC ;11
Adder
21.436
274752CRETE EC ;2U
Adder
9.969
274753CRETE EC ;3U
Adder
9.969
24642205MAYFLWER
Adder
0.769
274802UNIV PARK;5U
Adder
7.033
972228AH1-698 GEN2
Adder
4.468
274826FISK ;BP
Adder
13.204
274800UNIV PARK;3U
Adder
7.031
972038AH1-567 GEN2
Adder
0.44
274676JOLIET 29;8U
Adder
35.583
274729ELWOOD EC;1P
Adder
19.763
274730ELWOOD EC;6P
Adder
19.763
274734ELWOOD EC;8P
Adder
19.763
274736ELWOOD EC;9P
Adder
19.763
274682WAUKEGAN ;7U
Adder
21.437
25196608WSDLE5
Adder
10.207
25194608D.CRK4
Adder
1.955
24728705AND G3
Adder
9.473
24728505AND G1
Adder
4.529
972236AH1-702 GEN2
Adder
2.586
235058AG1-386 C
Solar/Wind Helper
0.458
237048AF1-022 C
Solar/Wind Helper
0.178
254305AE2-115 C
Solar/Wind Helper
0.216
237043AE2-125 C
Solar/Wind Helper
0.174
964991AG1-363 GEN
Solar/Wind Helper
3.62
202652Y1-033 WT C
Solar/Wind Helper
0.532
20089126CSLMN_L13
Solar/Wind Helper
0.564
20089026BF_G21_K23
Solar/Wind Helper
0.447
23750701CROSSCHOOL
Solar/Wind Helper
1.136
203818AF1-086 GEN
Solar/Wind Helper
1.615
238118U2-030_1
Solar/Wind Helper
0.272
238127S14_GEN_2
Solar/Wind Helper
0.648
203854AF2-039 C
Solar/Wind Helper
0.304
20334926Z1-069 C
Solar/Wind Helper
1.285
238202AE2-262_GEN
Solar/Wind Helper
0.914
959441AF2-235 GEN
Solar/Wind Helper
0.223
941421AE2-139 GEN
Solar/Wind Helper
2.214
253316AC1-085 GEN3
Solar/Wind Harmer
9.161
253433AC1-085 GEN1
Solar/Wind Harmer
5.815
203940AF1-140 C
Solar/Wind Helper
0.378
20088626ARWF_N39
Solar/Wind Helper
1.161
20303426NA_O38_P22
Solar/Wind Helper
0.952
946381AF1-302 GEN
Solar/Wind Helper
0.212
203853AF1-134 C O1
Solar/Wind Helper
0.457
203952AE2-129 C
Solar/Wind Helper
0.453
203946AE2-131 C
Solar/Wind Helper
0.454
238120AE2-309 GEN
Solar/Wind Helper
0.406
238217AF1-153 C O1
Solar/Wind Helper
0.226
20398826ARMNA MT
Solar/Wind Helper
1.425
253317AC1-085 GEN4
Solar/Wind Harmer
9.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
154.079
CBM South 1LTFEXP_CBM-S1->PJM
CBM
33.973
MECLTFEXP_MEC->PJM
CLTF
18.683
SIGELTFEXP_SIGE->PJM
CLTF
0.577
CPLELTFEXP_CPLE->PJM
CLTF
2.579
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.191
LAGNLTFEXP_LAGN->PJM
CLTF
17.654
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.421
TVALTFEXP_TVA->PJM
CLTF
8.605
NYPJM->LTFIMP_NY
CLTF
5.405
LGEELTFEXP_LGEE->PJM
CLTF
7.595
WECLTFEXP_WEC->PJM
CLTF
4.506
AG2-052LTFEXP_AG2-052->PJM
LTF
0.28
AH1-155LTFEXP_AH1-155->PJM
LTF
0.42

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-020_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-020_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.6 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4995.09
MW Contribution:12.45
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.415
270159DARBY CT4
50/50
13.555
962761AG1-125 GEN
Solar/Wind Harmer
60.17
970149AG2-104 GEN
Solar/Wind Harmer
74.31
970155AG2-107 GEN
Solar/Wind Harmer
26.237
270349AD2-093_GEN
Solar/Wind Harmer
6.312
270223U2-072_GEN1
Solar/Wind Harmer
2.896
270578AF1-285 GEN2
Solar/Wind Harmer
1.771
270391AF1-285 GEN3
Solar/Wind Harmer
1.771
970593AG2-378 GEN
Solar/Wind Harmer
2.904
270462AD2-086
Solar/Wind Harmer
9.839
253343AC1-166 GEN
Solar/Wind Harmer
1.515
253325AC1-069 GEN
Solar/Wind Harmer
1.461
25326309TAIT D
Adder
1.406
960071AF2-298 GEN
Solar/Wind Harmer
6.383
965011AG1-365 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
965651AG1-433 GEN
Solar/Wind Harmer
6.97
970245AG2-165 GEN
Solar/Wind Harmer
22.72
958861AF2-177 GEN
Solar/Wind Harmer
13.896
971995AH1-542 GEN
Solar/Wind Harmer
13.983
945371AF1-202 GEN
Solar/Wind Harmer
8.818
247521TR3_G114
Solar/Wind Harmer
4.233
270246TR4_N_V150
Solar/Wind Harmer
1.071
24721705FLATG2
Adder
25.49
965421AG1-410 GEN
Solar/Wind Harmer
37.691
246936BC-WTG1
Solar/Wind Harmer
4.907
270489AE1-102 GEN1
Solar/Wind Harmer
1.63
247536S-71 GEN
Solar/Wind Harmer
5.049
270005AE1-210 C O1
Solar/Wind Harmer
6.81
965031AG1-367 GEN
Solar/Wind Harmer
12.46
270063AE2-323 C
Solar/Wind Harmer
2.742
24695305TIMB G C
Solar/Wind Harmer
6.843
970825AG2-519 GEN
Solar/Wind Harmer
2.926
270263AC1-001 GEN
Solar/Wind Harmer
1.301
270032AE2-172
Solar/Wind Harmer
5.768
970291AG2-192 GEN
Solar/Wind Harmer
1.611
942081AE2-220 GEN
Solar/Wind Harmer
7.917
270239V3-007_GEN1
Solar/Wind Harmer
2.131
253432AC1-085 GEN2
Solar/Wind Harmer
0.33
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.399
274774LINCOLN ;5U
Adder
10.399
274723RIVER EC ;12
Adder
21.989
274751CRETE EC ;1U
Adder
10.107
274754CRETE EC ;4U
Adder
10.107
274812UNIV PK N;8U
Adder
6.133
274801UNIV PARK;4U
Adder
7.128
274676JOLIET 29;8U
Adder
37.414
274674JOLIET 9 ;6U
Adder
18.77
274732ELWOOD EC;7P
Adder
20.037
274745AC1-111 GEN9
Adder
6.792
274682WAUKEGAN ;7U
Adder
21.737
274828WAUKEGAN ;BP
Adder
13.354
25194608D.CRK4
Adder
1.983
24728605AND G2
Adder
4.594
274822ROCKFORD ;11
Adder
23.501
972235AH1-702 GEN1
Adder
3.016
25196808ZIMRHP
Adder
58.606
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.465
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.036
20089226LOOKOUT
Solar/Wind Helper
0.545
20088826HIGHLAND
Solar/Wind Helper
0.85
20094526CT_V3-030
Solar/Wind Helper
0.448
235054AD2-180 GEN
Solar/Wind Helper
1.575
964201AG1-281 GEN
Solar/Wind Helper
0.458
238117U2-030
Solar/Wind Helper
0.27
235531U2-073 GEN
Solar/Wind Helper
2.559
964391AG1-301 GEN
Solar/Wind Helper
0.448
203954AE2-126 C
Solar/Wind Helper
0.445
23751201ROTHROCK
Solar/Wind Helper
0.656
238206AE2-263_GEN
Solar/Wind Helper
0.861
959471AF2-238 GEN
Solar/Wind Helper
0.441
270051AF1-062 GEN
50/50
17.137
270475AD2-096_GEN
50/50
10.101
970153AG2-106 GEN
Solar/Wind Harmer
26.237
961921AG1-034 GEN
Solar/Wind Harmer
20.428
241955AC1-078 GEN
Solar/Wind Harmer
11.216
241974AD2-163_GEN2
Solar/Wind Harmer
2.98
942051AE2-217 GEN
Solar/Wind Harmer
26.699
942871AE2-306 GEN
Solar/Wind Harmer
1.328
270391AF1-285 GEN3
Solar/Wind Harmer
0.681
970605AG2-385 GEN
Solar/Wind Harmer
7.841
270485AE1-090_GEN
Solar/Wind Harmer
0.855
253338AC1-165 GEN
Solar/Wind Harmer
1.515
253333AC1-068 GEN
Solar/Wind Harmer
1.461
960801AF2-371 GEN
Solar/Wind Harmer
3.409
964871AG1-351 GEN
Solar/Wind Harmer
2.354
270273AD2-016 GEN
Solar/Wind Harmer
3.465
944531AF1-118 GEN
Solar/Wind Harmer
45.213
972173AH1-669 GEN
Solar/Wind Harmer
6.446
270043AE2-236 GEN
Solar/Wind Harmer
7.048
959331AF2-224 GEN
Solar/Wind Harmer
12.784
965021AG1-366 GEN
Solar/Wind Harmer
2.973
253303V4-073 C
Solar/Wind Harmer
0.148
253370AE2-315 SEC1
Adder
2.557
253371AE2-315 SEC2
Adder
2.418
970513AG2-328 GEN
Solar/Wind Harmer
22.72
970517AG2-330 GEN
Solar/Wind Harmer
20.606
253415AE1-040 GEN
Solar/Wind Harmer
1.432
970349AG2-230 GEN
Solar/Wind Harmer
18.933
270191TR4_S_V150
Solar/Wind Harmer
3.777
270247TR4_N_V136
Solar/Wind Harmer
1.071
24721905FLATG4
Adder
25.49
971617AH1-308 GEN
Solar/Wind Harmer
7.295
270491AE1-102 GEN2
Solar/Wind Harmer
1.63
962031AG1-047 GEN
Solar/Wind Harmer
3.777
957741AF2-068 GEN
Solar/Wind Harmer
18.744
970031AG2-029 GEN
Solar/Wind Harmer
37.389
958821AF2-173 GEN
Solar/Wind Harmer
17.445
270004AE1-209 GEN
Solar/Wind Harmer
6.81
946031AF1-268 GEN
Solar/Wind Harmer
10.33
253406AD2-031_GEN
Solar/Wind Harmer
1.591
970289AG2-191 GEN
Solar/Wind Harmer
0.951
970291AG2-192 GEN
Solar/Wind Harmer
0.865
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.914
247643Z2-116 C
Solar/Wind Harmer
0.086
253316AC1-085 GEN3
Solar/Wind Harmer
10.337
253433AC1-085 GEN1
Solar/Wind Harmer
6.562
274772LINCOLN ;3U
Adder
10.399
274724RIVER EC ;11
Adder
21.733
274752CRETE EC ;2U
Adder
10.107
274753CRETE EC ;3U
Adder
10.107
24642205MAYFLWER
Adder
0.779
274802UNIV PARK;5U
Adder
7.13
972228AH1-698 GEN2
Adder
4.53
274826FISK ;BP
Adder
13.387
274800UNIV PARK;3U
Adder
7.128
972038AH1-567 GEN2
Adder
0.446
274676JOLIET 29;8U
Adder
36.078
274729ELWOOD EC;1P
Adder
20.037
274730ELWOOD EC;6P
Adder
20.037
274734ELWOOD EC;8P
Adder
20.037
274736ELWOOD EC;9P
Adder
20.037
274682WAUKEGAN ;7U
Adder
21.737
25196608WSDLE5
Adder
10.356
25194608D.CRK4
Adder
1.983
24728705AND G3
Adder
9.609
24728505AND G1
Adder
4.594
972236AH1-702 GEN2
Adder
2.622
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.177
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.598
202652Y1-033 WT C
Solar/Wind Helper
0.528
23750701CROSSCHOOL
Solar/Wind Helper
1.128
20089126CSLMN_L13
Solar/Wind Helper
0.559
20089026BF_G21_K23
Solar/Wind Helper
0.443
203818AF1-086 GEN
Solar/Wind Helper
1.599
238118U2-030_1
Solar/Wind Helper
0.27
270119AB2-067 GEN1
50/50
18.415
270156DARBY CT1
50/50
13.775
270157DARBY CT2
50/50
13.741
270158DARBY CT3
50/50
13.521
270036AE2-216 BAT
50/50
9.031
962771AG1-126 GEN
Solar/Wind Harmer
60.17
270284AF1-227 GEN1
Solar/Wind Harmer
9.235
270286AF1-227 GEN2
Solar/Wind Harmer
3.417
270287AF1-227 GEN3
Solar/Wind Harmer
3.417
270459AD2-067 GEN
Solar/Wind Harmer
13.414
961821AG1-024 GEN
Solar/Wind Harmer
13.619
270520AE2-214 GEN
Solar/Wind Harmer
9.509
270054AF2-122 C O1
Solar/Wind Harmer
5.085
253383AE2-342_GEN
Solar/Wind Harmer
1.367
241973AD2-163_GEN1
Solar/Wind Harmer
2.98
943861AF1-054 GEN
Solar/Wind Harmer
5.751
943851AF1-053 GEN
Solar/Wind Harmer
2.779
270578AF1-285 GEN2
Solar/Wind Harmer
0.681
945631AF1-228 GEN
Solar/Wind Harmer
6.816
270302AB2-170 GEN
Solar/Wind Harmer
11.828
270317AD1-130_GEN
Solar/Wind Harmer
4.534
241972AD1-140 GEN
Solar/Wind Harmer
6.086
970689AG2-444 GEN
Solar/Wind Harmer
21.964
270432AC2-029 GEN
Solar/Wind Harmer
9.402
270269AC2-059
Solar/Wind Harmer
12.116
24729505KEY G4
Adder
8.352
270071AF1-092 GEN
Solar/Wind Harmer
19.246
253372AE2-315 SEC3
Adder
2.418
253372AE2-315 SEC3
Adder
2.418
958711AF2-162 GEN
Solar/Wind Harmer
1.29
25306009OHH W.
Adder
3.664
965101AG1-375 GEN
Solar/Wind Harmer
12.713
253349AC2-067 GEN
Solar/Wind Harmer
6.33
253400AC2-068 GEN
Solar/Wind Harmer
2.546
945581AF1-223 GEN
Solar/Wind Harmer
5.732
963791AG1-232 GEN
Solar/Wind Harmer
17.046
971347AH1-153 GEN
Solar/Wind Harmer
18.933
965051AG1-369 GEN
Solar/Wind Harmer
6.287
965041AG1-368 GEN
Solar/Wind Harmer
12.553
270024AE2-089 GEN
Solar/Wind Harmer
5.889
270340AC2-060 GEN
Solar/Wind Harmer
3.803
957201AF2-014 GEN
Solar/Wind Harmer
5.688
270435AC2-044 GEN
Solar/Wind Harmer
2.508
961761AG1-017 GEN
Solar/Wind Harmer
0.535
270543AE2-219 C
Solar/Wind Harmer
6.376
971029AG2-637 GEN
Solar/Wind Harmer
18.648
971673AH1-337 GEN
Solar/Wind Harmer
5.716
970115AG2-085 GEN
Solar/Wind Harmer
4.969
270594AE1-207 GEN
Solar/Wind Harmer
18.228
965461AG1-414 GEN
Solar/Wind Harmer
2.81
970289AG2-191 GEN
Solar/Wind Harmer
2.355
270240V3-007_GEN2
Solar/Wind Harmer
7.662
960681AF2-359 GEN
Solar/Wind Harmer
4.674
274775LINCOLN ;6U
Adder
10.399
274776LINCOLN ;7U
Adder
10.399
274777LINCOLN ;8U
Adder
10.399
274814UNIV PK N;0U
Adder
6.187
274807UNIV PK N;3U
Adder
6.174
274805UNIV PK N;1U
Adder
6.147
274811UNIV PK N;7U
Adder
6.133
972037AH1-567 GEN1
Adder
0.224
972227AH1-698 GEN1
Adder
3.19
274827FISK ;RP
Adder
9.488
274687WILL CNTY;4U
Adder
34.087
274687WILL CNTY;4U
Adder
34.087
274675JOLIET 29;7U
Adder
37.414
274675JOLIET 29;7U
Adder
36.078
274731ELWOOD EC;2P
Adder
20.037
274733ELWOOD EC;3P
Adder
20.037
274735ELWOOD EC;4P
Adder
20.037
274728ELWOOD EC;5P
Adder
20.037
274746AC1-111 G10
Adder
6.792
274744AC1-111 GEN8
Adder
6.792
25196408WSDLE3
Adder
10.661
25196308WSDLE2
Adder
10.568
25196208WSDLE1
Adder
10.541
25196708WSDLE6
Adder
10.515
25196508WSDLE4
Adder
10.25
274823ROCKFORD ;21
Adder
23.331
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.613
20092526R32
Solar/Wind Helper
1.102
203961AE2-224 GEN
Solar/Wind Helper
2.286
20091526CHSTN_FL
Solar/Wind Helper
0.552
20090526Q36
Solar/Wind Helper
0.989
203993AD2-133_GEN1
Solar/Wind Helper
0.989
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.644
941231AE2-117 GEN
Solar/Wind Helper
0.449
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.643
238127S14_GEN_2
Solar/Wind Helper
0.644
203854AF2-039 C
Solar/Wind Helper
0.301
20334926Z1-069 C
Solar/Wind Helper
1.271
238202AE2-262_GEN
Solar/Wind Helper
0.905
959441AF2-235 GEN
Solar/Wind Helper
0.22
946181AF1-283 GEN
Solar/Wind Harmer
8.323
270120AB2-067 GEN2
50/50
18.415
270160DARBY CT5
50/50
0.738
270161DARBY CT6
50/50
0.728
270466AD2-091
50/50
8.21
270471AD2-092_GEN
Solar/Wind Harmer
6.312
946101AF1-275 GEN
Solar/Wind Harmer
2.373
942861AE2-305 GEN
Solar/Wind Harmer
11.65
270224U2-072_GEN2
Solar/Wind Harmer
2.896
270227U2-072_GEN3
Solar/Wind Harmer
2.896
270228U2-072_GEN4
Solar/Wind Harmer
2.896
270231U2-072_GEN5
Solar/Wind Harmer
2.896
970077AG2-063 GEN
Solar/Wind Harmer
7.841
270518AE2-148 GEN
Solar/Wind Harmer
17.081
964601AG1-323 GEN
Solar/Wind Harmer
4.458
964601AG1-323 GEN
Solar/Wind Harmer
2.073
938701AE1-092 GEN
Solar/Wind Harmer
28.718
253378AE2-206_GEN
Solar/Wind Harmer
4.802
276820AF1-078_GEN
Solar/Wind Harmer
2.133
25326509SID D
Adder
1.721
25326109MON D
Adder
1.706
25322209TAIT E
Adder
12.514
25322209TAIT E
Adder
12.233
970611AG2-400 GEN
Solar/Wind Harmer
12.784
253370AE2-315 SEC1
Adder
2.557
944541AF1-119 GEN
Solar/Wind Harmer
5.341
960971AF2-388 GEN
Solar/Wind Harmer
13.939
970321AG2-212 GEN
Solar/Wind Harmer
22.72
942221AE2-234 GEN
Solar/Wind Harmer
0.925
246938BC-WTG3
Solar/Wind Harmer
4.992
246937BC-WTG2
Solar/Wind Harmer
4.907
253394AE2-221_GEN
Solar/Wind Harmer
5.683
253398AE2-221_GEN2
Solar/Wind Harmer
5.683
270599AE1-208 GEN
Solar/Wind Harmer
10.191
270031AE2-169
Solar/Wind Harmer
10.191
270201AC2-176 GEN
Solar/Wind Harmer
6.424
964611AG1-324 GEN
Solar/Wind Harmer
1.472
964611AG1-324 GEN
Solar/Wind Harmer
0.653
247621Y3-024
Adder
0.301
970883AG2-550 GEN
Solar/Wind Harmer
12.452
970885AG2-551 GEN
Solar/Wind Harmer
2.896
970825AG2-519 GEN
Solar/Wind Harmer
13.114
960441AF2-335 GEN
Solar/Wind Harmer
12.423
270383AD1-128 GEN
Solar/Wind Harmer
7.569
24379505HDWTR1G C
Solar/Wind Harmer
9.793
270209AC1-174_GEN
Solar/Wind Harmer
6.911
926881AC1-175 GEN
Solar/Wind Harmer
6.911
965681AG1-436 GEN
Solar/Wind Harmer
15.464
965791AG1-447 GEN
Solar/Wind Harmer
7.912
270216AD2-079_GEN
Solar/Wind Harmer
0.748
253317AC1-085 GEN4
Solar/Wind Harmer
10.337
247620Y3-023
Adder
0.568
274770LINCOLN ;1U
Adder
10.399
274771LINCOLN ;2U
Adder
10.399
274808UNIV PK N;4U
Adder
6.107
972259AH1-714 GEN
Adder
23.335
274803UNIV PARK;6U
Adder
7.13
24728805RICHG1
Adder
4.62
24728905RICHG2
Adder
4.62
274674JOLIET 9 ;6U
Adder
18.77
274696ROCKY RD ;4P
Adder
13.793
274695ROCKY RD ;2P
Adder
13.475
274693ROCKY RD ;1P
Adder
13.342
274697ROCKY RD ;3P
Adder
3.661
274683WAUKEGAN ;8U
Adder
25.476
274683WAUKEGAN ;8U
Adder
21.475
25194408D.CRK1
Adder
9.122
25194508D.CRK3
Adder
1.705
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.575
23585401KL_K28_T16
Solar/Wind Helper
1.173
203955AF1-039 C O1
Solar/Wind Helper
0.348
944781AF1-143 GEN
Solar/Wind Helper
2.322
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.337
20088926STNY CRK
Solar/Wind Helper
0.773
203940AF1-140 C
Solar/Wind Helper
0.375
20088626ARWF_N39
Solar/Wind Helper
1.151
20303426NA_O38_P22
Solar/Wind Helper
0.944
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.453
238120AE2-309 GEN
Solar/Wind Helper
0.403
203952AE2-129 C
Solar/Wind Helper
0.449
203946AE2-131 C
Solar/Wind Helper
0.45
238217AF1-153 C O1
Solar/Wind Helper
0.224
20398826ARMNA MT
Solar/Wind Helper
1.411
CBM West 1LTFEXP_CBM-W1->PJM
CBM
156.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.576
MECLTFEXP_MEC->PJM
CLTF
18.96
SIGELTFEXP_SIGE->PJM
CLTF
0.586
CPLELTFEXP_CPLE->PJM
CLTF
2.716
CBM West 2LTFEXP_CBM-W2->PJM
CBM
134.362
LAGNLTFEXP_LAGN->PJM
CLTF
17.971
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.828
TVALTFEXP_TVA->PJM
CLTF
8.763
NYPJM->LTFIMP_NY
CLTF
5.354
LGEELTFEXP_LGEE->PJM
CLTF
7.711
WECLTFEXP_WEC->PJM
CLTF
4.569
AG2-052LTFEXP_AG2-052->PJM
LTF
0.284
AH1-155LTFEXP_AH1-155->PJM
LTF
0.426

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P2-3_MP-500-021_SRT-SL


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P2-3_MP-500-021_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.39 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4986.37
MW Contribution:12.41
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
18.405
270159DARBY CT4
50/50
13.513
962761AG1-125 GEN
Solar/Wind Harmer
60.041
970149AG2-104 GEN
Solar/Wind Harmer
74.151
970155AG2-107 GEN
Solar/Wind Harmer
26.181
270349AD2-093_GEN
Solar/Wind Harmer
6.297
270223U2-072_GEN1
Solar/Wind Harmer
2.888
270578AF1-285 GEN2
Solar/Wind Harmer
1.766
270391AF1-285 GEN3
Solar/Wind Harmer
1.766
970593AG2-378 GEN
Solar/Wind Harmer
2.895
270462AD2-086
Solar/Wind Harmer
9.812
253343AC1-166 GEN
Solar/Wind Harmer
1.51
253325AC1-069 GEN
Solar/Wind Harmer
1.456
25326309TAIT D
Adder
1.402
960071AF2-298 GEN
Solar/Wind Harmer
6.362
965011AG1-365 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
965651AG1-433 GEN
Solar/Wind Harmer
6.949
970245AG2-165 GEN
Solar/Wind Harmer
22.653
958861AF2-177 GEN
Solar/Wind Harmer
13.854
971995AH1-542 GEN
Solar/Wind Harmer
13.936
945371AF1-202 GEN
Solar/Wind Harmer
8.791
270156DARBY CT1
50/50
13.732
270157DARBY CT2
50/50
13.698
270158DARBY CT3
50/50
13.479
270036AE2-216 BAT
50/50
9.005
962771AG1-126 GEN
Solar/Wind Harmer
60.041
270284AF1-227 GEN1
Solar/Wind Harmer
9.212
270286AF1-227 GEN2
Solar/Wind Harmer
3.408
270287AF1-227 GEN3
Solar/Wind Harmer
3.408
270459AD2-067 GEN
Solar/Wind Harmer
13.375
961821AG1-024 GEN
Solar/Wind Harmer
13.579
270520AE2-214 GEN
Solar/Wind Harmer
9.481
270054AF2-122 C O1
Solar/Wind Harmer
5.069
253383AE2-342_GEN
Solar/Wind Harmer
1.364
241973AD2-163_GEN1
Solar/Wind Harmer
2.972
943861AF1-054 GEN
Solar/Wind Harmer
5.734
943851AF1-053 GEN
Solar/Wind Harmer
2.771
270578AF1-285 GEN2
Solar/Wind Harmer
0.679
945631AF1-228 GEN
Solar/Wind Harmer
6.795
270302AB2-170 GEN
Solar/Wind Harmer
11.795
270317AD1-130_GEN
Solar/Wind Harmer
4.522
241972AD1-140 GEN
Solar/Wind Harmer
6.067
970689AG2-444 GEN
Solar/Wind Harmer
21.887
270432AC2-029 GEN
Solar/Wind Harmer
9.37
270269AC2-059
Solar/Wind Harmer
12.072
24729505KEY G4
Adder
8.327
270071AF1-092 GEN
Solar/Wind Harmer
19.189
253372AE2-315 SEC3
Adder
2.411
253372AE2-315 SEC3
Adder
2.411
958711AF2-162 GEN
Solar/Wind Harmer
1.286
965101AG1-375 GEN
Solar/Wind Harmer
12.675
25306009OHH W.
Adder
3.652
253349AC2-067 GEN
Solar/Wind Harmer
6.31
253400AC2-068 GEN
Solar/Wind Harmer
2.537
945581AF1-223 GEN
Solar/Wind Harmer
5.714
963791AG1-232 GEN
Solar/Wind Harmer
16.994
971347AH1-153 GEN
Solar/Wind Harmer
18.878
965051AG1-369 GEN
Solar/Wind Harmer
6.268
965041AG1-368 GEN
Solar/Wind Harmer
12.515
270024AE2-089 GEN
Solar/Wind Harmer
5.871
957201AF2-014 GEN
Solar/Wind Harmer
5.67
270435AC2-044 GEN
Solar/Wind Harmer
2.5
270340AC2-060 GEN
Solar/Wind Harmer
3.789
961761AG1-017 GEN
Solar/Wind Harmer
0.533
270543AE2-219 C
Solar/Wind Harmer
6.356
971029AG2-637 GEN
Solar/Wind Harmer
18.589
971673AH1-337 GEN
Solar/Wind Harmer
5.698
970115AG2-085 GEN
Solar/Wind Harmer
4.954
270594AE1-207 GEN
Solar/Wind Harmer
18.171
965461AG1-414 GEN
Solar/Wind Harmer
2.801
970289AG2-191 GEN
Solar/Wind Harmer
2.347
270240V3-007_GEN2
Solar/Wind Harmer
7.638
960681AF2-359 GEN
Solar/Wind Harmer
4.66
971771AH1-392 GEN
Solar/Wind Harmer
11.073
274775LINCOLN ;6U
Adder
10.368
274776LINCOLN ;7U
Adder
10.368
274777LINCOLN ;8U
Adder
10.368
274814UNIV PK N;0U
Adder
6.169
274807UNIV PK N;3U
Adder
6.155
274805UNIV PK N;1U
Adder
6.128
274811UNIV PK N;7U
Adder
6.115
972227AH1-698 GEN1
Adder
3.18
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.459
274687WILL CNTY;4U
Adder
33.985
274687WILL CNTY;4U
Adder
33.985
274675JOLIET 29;7U
Adder
37.302
274675JOLIET 29;7U
Adder
35.969
274731ELWOOD EC;2P
Adder
19.977
274733ELWOOD EC;3P
Adder
19.977
274735ELWOOD EC;4P
Adder
19.977
274728ELWOOD EC;5P
Adder
19.977
274746AC1-111 G10
Adder
6.771
274744AC1-111 GEN8
Adder
6.771
25196408WSDLE3
Adder
10.624
25196308WSDLE2
Adder
10.532
25196208WSDLE1
Adder
10.505
25196708WSDLE6
Adder
10.479
25196508WSDLE4
Adder
10.215
274823ROCKFORD ;21
Adder
23.26
254304AE2-114 C
Solar/Wind Helper
0.213
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.611
20092526R32
Solar/Wind Helper
1.1
203961AE2-224 GEN
Solar/Wind Helper
2.28
20091526CHSTN_FL
Solar/Wind Helper
0.551
20090526Q36
Solar/Wind Helper
0.986
203993AD2-133_GEN1
Solar/Wind Helper
0.986
203846AF2-130 C
Solar/Wind Helper
0.426
238126S14_GEN_1
Solar/Wind Helper
0.641
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.145
203804AE2-113_GEN
Solar/Wind Helper
1.64
270051AF1-062 GEN
50/50
17.095
270475AD2-096_GEN
50/50
10.077
970153AG2-106 GEN
Solar/Wind Harmer
26.181
961921AG1-034 GEN
Solar/Wind Harmer
20.368
241955AC1-078 GEN
Solar/Wind Harmer
11.182
241974AD2-163_GEN2
Solar/Wind Harmer
2.972
942051AE2-217 GEN
Solar/Wind Harmer
26.62
942871AE2-306 GEN
Solar/Wind Harmer
1.325
270391AF1-285 GEN3
Solar/Wind Harmer
0.679
970605AG2-385 GEN
Solar/Wind Harmer
7.818
270485AE1-090_GEN
Solar/Wind Harmer
0.853
253338AC1-165 GEN
Solar/Wind Harmer
1.51
253333AC1-068 GEN
Solar/Wind Harmer
1.456
960801AF2-371 GEN
Solar/Wind Harmer
3.397
964871AG1-351 GEN
Solar/Wind Harmer
2.345
270273AD2-016 GEN
Solar/Wind Harmer
3.452
944531AF1-118 GEN
Solar/Wind Harmer
45.079
972173AH1-669 GEN
Solar/Wind Harmer
6.423
270043AE2-236 GEN
Solar/Wind Harmer
7.027
959331AF2-224 GEN
Solar/Wind Harmer
12.746
965021AG1-366 GEN
Solar/Wind Harmer
2.964
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.549
253371AE2-315 SEC2
Adder
2.411
970513AG2-328 GEN
Solar/Wind Harmer
22.653
970517AG2-330 GEN
Solar/Wind Harmer
20.546
253415AE1-040 GEN
Solar/Wind Harmer
1.427
970349AG2-230 GEN
Solar/Wind Harmer
18.878
270191TR4_S_V150
Solar/Wind Harmer
3.765
270247TR4_N_V136
Solar/Wind Harmer
1.068
24721905FLATG4
Adder
25.406
971617AH1-308 GEN
Solar/Wind Harmer
7.273
270491AE1-102 GEN2
Solar/Wind Harmer
1.625
962031AG1-047 GEN
Solar/Wind Harmer
3.765
957741AF2-068 GEN
Solar/Wind Harmer
18.686
970031AG2-029 GEN
Solar/Wind Harmer
37.277
958821AF2-173 GEN
Solar/Wind Harmer
17.391
270004AE1-209 GEN
Solar/Wind Harmer
6.789
946031AF1-268 GEN
Solar/Wind Harmer
10.298
253406AD2-031_GEN
Solar/Wind Harmer
1.585
970289AG2-191 GEN
Solar/Wind Harmer
0.948
970291AG2-192 GEN
Solar/Wind Harmer
0.862
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.893
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.368
274724RIVER EC ;11
Adder
21.668
274752CRETE EC ;2U
Adder
10.077
274753CRETE EC ;3U
Adder
10.077
24642205MAYFLWER
Adder
0.777
274802UNIV PARK;5U
Adder
7.109
972228AH1-698 GEN2
Adder
4.517
274826FISK ;BP
Adder
13.347
274800UNIV PARK;3U
Adder
7.107
972038AH1-567 GEN2
Adder
0.445
274676JOLIET 29;8U
Adder
35.969
274729ELWOOD EC;1P
Adder
19.977
274730ELWOOD EC;6P
Adder
19.977
274734ELWOOD EC;8P
Adder
19.977
274736ELWOOD EC;9P
Adder
19.977
274682WAUKEGAN ;7U
Adder
21.671
25196608WSDLE5
Adder
10.321
25194608D.CRK4
Adder
1.976
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.58
972236AH1-702 GEN2
Adder
2.615
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.213
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.583
202652Y1-033 WT C
Solar/Wind Helper
0.526
20089126CSLMN_L13
Solar/Wind Helper
0.558
20089026BF_G21_K23
Solar/Wind Helper
0.442
23750701CROSSCHOOL
Solar/Wind Helper
1.124
203818AF1-086 GEN
Solar/Wind Helper
1.596
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.641
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.269
238202AE2-262_GEN
Solar/Wind Helper
0.903
253316AC1-085 GEN3
Solar/Wind Harmer
9.261
253433AC1-085 GEN1
Solar/Wind Harmer
5.879
247521TR3_G114
Solar/Wind Harmer
4.221
270246TR4_N_V150
Solar/Wind Harmer
1.068
24721705FLATG2
Adder
25.406
965421AG1-410 GEN
Solar/Wind Harmer
37.577
246936BC-WTG1
Solar/Wind Harmer
4.892
270489AE1-102 GEN1
Solar/Wind Harmer
1.625
247536S-71 GEN
Solar/Wind Harmer
5.033
270005AE1-210 C O1
Solar/Wind Harmer
6.789
965031AG1-367 GEN
Solar/Wind Harmer
12.422
270063AE2-323 C
Solar/Wind Harmer
2.733
24695305TIMB G C
Solar/Wind Harmer
6.822
970825AG2-519 GEN
Solar/Wind Harmer
2.917
270263AC1-001 GEN
Solar/Wind Harmer
1.296
270032AE2-172
Solar/Wind Harmer
5.75
970291AG2-192 GEN
Solar/Wind Harmer
1.606
942081AE2-220 GEN
Solar/Wind Harmer
7.893
270239V3-007_GEN1
Solar/Wind Harmer
2.124
24639705ELKHART HY
Adder
0.189
274773LINCOLN ;4U
Adder
10.368
274774LINCOLN ;5U
Adder
10.368
274723RIVER EC ;12
Adder
21.923
274751CRETE EC ;1U
Adder
10.077
274754CRETE EC ;4U
Adder
10.077
274812UNIV PK N;8U
Adder
6.115
274801UNIV PARK;4U
Adder
7.107
274676JOLIET 29;8U
Adder
37.301
274674JOLIET 9 ;6U
Adder
18.713
274732ELWOOD EC;7P
Adder
19.977
274745AC1-111 GEN9
Adder
6.771
274682WAUKEGAN ;7U
Adder
21.671
274828WAUKEGAN ;BP
Adder
13.314
25194608D.CRK4
Adder
1.976
24728605AND G2
Adder
4.58
274822ROCKFORD ;11
Adder
23.43
972235AH1-702 GEN1
Adder
3.007
25196808ZIMRHP
Adder
58.404
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.464
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.029
20089226LOOKOUT
Solar/Wind Helper
0.543
20088826HIGHLAND
Solar/Wind Helper
0.848
20094526CT_V3-030
Solar/Wind Helper
0.447
235054AD2-180 GEN
Solar/Wind Helper
1.569
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.549
964391AG1-301 GEN
Solar/Wind Helper
0.447
203954AE2-126 C
Solar/Wind Helper
0.444
23751201ROTHROCK
Solar/Wind Helper
0.653
238206AE2-263_GEN
Solar/Wind Helper
0.859
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
270119AB2-067 GEN1
50/50
18.405
270120AB2-067 GEN2
50/50
18.405
270160DARBY CT5
50/50
0.736
270161DARBY CT6
50/50
0.726
270466AD2-091
50/50
8.187
270471AD2-092_GEN
Solar/Wind Harmer
6.297
946101AF1-275 GEN
Solar/Wind Harmer
2.366
942861AE2-305 GEN
Solar/Wind Harmer
11.617
270224U2-072_GEN2
Solar/Wind Harmer
2.888
270227U2-072_GEN3
Solar/Wind Harmer
2.888
270228U2-072_GEN4
Solar/Wind Harmer
2.888
270231U2-072_GEN5
Solar/Wind Harmer
2.888
970077AG2-063 GEN
Solar/Wind Harmer
7.818
270518AE2-148 GEN
Solar/Wind Harmer
17.027
964601AG1-323 GEN
Solar/Wind Harmer
4.444
964601AG1-323 GEN
Solar/Wind Harmer
2.067
938701AE1-092 GEN
Solar/Wind Harmer
28.63
253378AE2-206_GEN
Solar/Wind Harmer
4.787
276820AF1-078_GEN
Solar/Wind Harmer
2.127
25326509SID D
Adder
1.715
25326109MON D
Adder
1.7
25322209TAIT E
Adder
12.473
25322209TAIT E
Adder
12.193
970611AG2-400 GEN
Solar/Wind Harmer
12.746
253370AE2-315 SEC1
Adder
2.549
944541AF1-119 GEN
Solar/Wind Harmer
5.325
960971AF2-388 GEN
Solar/Wind Harmer
13.897
970321AG2-212 GEN
Solar/Wind Harmer
22.653
942221AE2-234 GEN
Solar/Wind Harmer
0.922
246938BC-WTG3
Solar/Wind Harmer
4.977
246937BC-WTG2
Solar/Wind Harmer
4.892
253394AE2-221_GEN
Solar/Wind Harmer
5.664
253398AE2-221_GEN2
Solar/Wind Harmer
5.664
270599AE1-208 GEN
Solar/Wind Harmer
10.159
270031AE2-169
Solar/Wind Harmer
10.159
270201AC2-176 GEN
Solar/Wind Harmer
6.404
964611AG1-324 GEN
Solar/Wind Harmer
1.468
964611AG1-324 GEN
Solar/Wind Harmer
0.651
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.413
970885AG2-551 GEN
Solar/Wind Harmer
2.887
970825AG2-519 GEN
Solar/Wind Harmer
13.073
960441AF2-335 GEN
Solar/Wind Harmer
12.384
270383AD1-128 GEN
Solar/Wind Harmer
7.545
24379505HDWTR1G C
Solar/Wind Harmer
9.762
270209AC1-174_GEN
Solar/Wind Harmer
6.889
926881AC1-175 GEN
Solar/Wind Harmer
6.889
965681AG1-436 GEN
Solar/Wind Harmer
15.418
965791AG1-447 GEN
Solar/Wind Harmer
7.888
270216AD2-079_GEN
Solar/Wind Harmer
0.746
247620Y3-023
Adder
0.566
274770LINCOLN ;1U
Adder
10.368
274771LINCOLN ;2U
Adder
10.368
274808UNIV PK N;4U
Adder
6.088
972259AH1-714 GEN
Adder
23.265
274803UNIV PARK;6U
Adder
7.109
24728805RICHG1
Adder
4.605
24728905RICHG2
Adder
4.605
274674JOLIET 9 ;6U
Adder
18.713
274696ROCKY RD ;4P
Adder
13.751
274695ROCKY RD ;2P
Adder
13.434
274693ROCKY RD ;1P
Adder
13.302
274697ROCKY RD ;3P
Adder
3.649
274683WAUKEGAN ;8U
Adder
25.399
274683WAUKEGAN ;8U
Adder
21.41
25194408D.CRK1
Adder
9.091
25194508D.CRK3
Adder
1.7
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.569
23585401KL_K28_T16
Solar/Wind Helper
1.169
203955AF1-039 C O1
Solar/Wind Helper
0.347
944781AF1-143 GEN
Solar/Wind Helper
2.315
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.771
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.148
20303426NA_O38_P22
Solar/Wind Helper
0.941
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.448
203946AE2-131 C
Solar/Wind Helper
0.449
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.408
253317AC1-085 GEN4
Solar/Wind Harmer
9.261
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.982
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.46
MECLTFEXP_MEC->PJM
CLTF
18.901
SIGELTFEXP_SIGE->PJM
CLTF
0.584
CPLELTFEXP_CPLE->PJM
CLTF
2.708
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.928
LAGNLTFEXP_LAGN->PJM
CLTF
17.912
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.787
TVALTFEXP_TVA->PJM
CLTF
8.734
NYPJM->LTFIMP_NY
CLTF
5.339
LGEELTFEXP_LGEE->PJM
CLTF
7.685
WECLTFEXP_WEC->PJM
CLTF
4.556
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.425

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AEP_P4_#37_05MOUNTN 765_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P4_#37_05MOUNTN 765_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:120.3 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4982.82
MW Contribution:12.4
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
59.984
270284AF1-227 GEN1
Solar/Wind Harmer
9.201
270286AF1-227 GEN2
Solar/Wind Harmer
3.404
270287AF1-227 GEN3
Solar/Wind Harmer
3.404
270459AD2-067 GEN
Solar/Wind Harmer
13.358
961821AG1-024 GEN
Solar/Wind Harmer
13.561
270520AE2-214 GEN
Solar/Wind Harmer
9.469
270054AF2-122 C O1
Solar/Wind Harmer
5.062
253383AE2-342_GEN
Solar/Wind Harmer
1.362
241973AD2-163_GEN1
Solar/Wind Harmer
2.968
943861AF1-054 GEN
Solar/Wind Harmer
5.727
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
6.786
270302AB2-170 GEN
Solar/Wind Harmer
11.78
270317AD1-130_GEN
Solar/Wind Harmer
4.516
241972AD1-140 GEN
Solar/Wind Harmer
6.058
970689AG2-444 GEN
Solar/Wind Harmer
21.853
270432AC2-029 GEN
Solar/Wind Harmer
9.355
270269AC2-059
Solar/Wind Harmer
12.053
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
19.164
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
958711AF2-162 GEN
Solar/Wind Harmer
1.285
965101AG1-375 GEN
Solar/Wind Harmer
12.658
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
6.301
253400AC2-068 GEN
Solar/Wind Harmer
2.534
945581AF1-223 GEN
Solar/Wind Harmer
5.707
963791AG1-232 GEN
Solar/Wind Harmer
16.971
971347AH1-153 GEN
Solar/Wind Harmer
18.853
965051AG1-369 GEN
Solar/Wind Harmer
6.259
965041AG1-368 GEN
Solar/Wind Harmer
12.498
270024AE2-089 GEN
Solar/Wind Harmer
5.863
957201AF2-014 GEN
Solar/Wind Harmer
5.663
270435AC2-044 GEN
Solar/Wind Harmer
2.497
270340AC2-060 GEN
Solar/Wind Harmer
3.783
961761AG1-017 GEN
Solar/Wind Harmer
0.532
270543AE2-219 C
Solar/Wind Harmer
6.347
971029AG2-637 GEN
Solar/Wind Harmer
18.562
971673AH1-337 GEN
Solar/Wind Harmer
5.69
970115AG2-085 GEN
Solar/Wind Harmer
4.947
270594AE1-207 GEN
Solar/Wind Harmer
18.147
965461AG1-414 GEN
Solar/Wind Harmer
2.797
970289AG2-191 GEN
Solar/Wind Harmer
2.344
270240V3-007_GEN2
Solar/Wind Harmer
7.627
960681AF2-359 GEN
Solar/Wind Harmer
4.654
971771AH1-392 GEN
Solar/Wind Harmer
11.059
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
26.156
961921AG1-034 GEN
Solar/Wind Harmer
20.342
241955AC1-078 GEN
Solar/Wind Harmer
11.167
241974AD2-163_GEN2
Solar/Wind Harmer
2.968
942051AE2-217 GEN
Solar/Wind Harmer
26.585
942871AE2-306 GEN
Solar/Wind Harmer
1.323
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
7.807
270485AE1-090_GEN
Solar/Wind Harmer
0.852
253338AC1-165 GEN
Solar/Wind Harmer
1.508
253333AC1-068 GEN
Solar/Wind Harmer
1.454
960801AF2-371 GEN
Solar/Wind Harmer
3.391
964871AG1-351 GEN
Solar/Wind Harmer
2.342
270273AD2-016 GEN
Solar/Wind Harmer
3.447
944531AF1-118 GEN
Solar/Wind Harmer
45.02
972173AH1-669 GEN
Solar/Wind Harmer
6.413
270043AE2-236 GEN
Solar/Wind Harmer
7.018
959331AF2-224 GEN
Solar/Wind Harmer
12.73
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253303V4-073 C
Solar/Wind Harmer
0.147
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
22.623
970517AG2-330 GEN
Solar/Wind Harmer
20.519
253415AE1-040 GEN
Solar/Wind Harmer
1.424
970349AG2-230 GEN
Solar/Wind Harmer
18.853
270191TR4_S_V150
Solar/Wind Harmer
3.76
270247TR4_N_V136
Solar/Wind Harmer
1.066
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.623
962031AG1-047 GEN
Solar/Wind Harmer
3.76
957741AF2-068 GEN
Solar/Wind Harmer
18.66
970031AG2-029 GEN
Solar/Wind Harmer
37.228
958821AF2-173 GEN
Solar/Wind Harmer
17.367
270004AE1-209 GEN
Solar/Wind Harmer
6.779
946031AF1-268 GEN
Solar/Wind Harmer
10.283
253406AD2-031_GEN
Solar/Wind Harmer
1.583
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.883
247643Z2-116 C
Solar/Wind Harmer
0.086
274772LINCOLN ;3U
Adder
10.354
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
25194608D.CRK4
Adder
1.973
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
253316AC1-085 GEN3
Solar/Wind Harmer
9.247
253433AC1-085 GEN1
Solar/Wind Harmer
5.87
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
59.984
970149AG2-104 GEN
Solar/Wind Harmer
74.081
970155AG2-107 GEN
Solar/Wind Harmer
26.156
270349AD2-093_GEN
Solar/Wind Harmer
6.29
270223U2-072_GEN1
Solar/Wind Harmer
2.884
270578AF1-285 GEN2
Solar/Wind Harmer
1.764
270391AF1-285 GEN3
Solar/Wind Harmer
1.764
970593AG2-378 GEN
Solar/Wind Harmer
2.892
270462AD2-086
Solar/Wind Harmer
9.8
253343AC1-166 GEN
Solar/Wind Harmer
1.508
253325AC1-069 GEN
Solar/Wind Harmer
1.454
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
6.353
965011AG1-365 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
6.939
970245AG2-165 GEN
Solar/Wind Harmer
22.623
958861AF2-177 GEN
Solar/Wind Harmer
13.835
971995AH1-542 GEN
Solar/Wind Harmer
13.916
945371AF1-202 GEN
Solar/Wind Harmer
8.779
247521TR3_G114
Solar/Wind Harmer
4.215
270246TR4_N_V150
Solar/Wind Harmer
1.066
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
37.527
246936BC-WTG1
Solar/Wind Harmer
4.886
270489AE1-102 GEN1
Solar/Wind Harmer
1.623
247536S-71 GEN
Solar/Wind Harmer
5.026
270005AE1-210 C O1
Solar/Wind Harmer
6.779
965031AG1-367 GEN
Solar/Wind Harmer
12.405
270063AE2-323 C
Solar/Wind Harmer
2.73
24695305TIMB G C
Solar/Wind Harmer
6.813
970825AG2-519 GEN
Solar/Wind Harmer
2.913
270263AC1-001 GEN
Solar/Wind Harmer
1.294
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.604
942081AE2-220 GEN
Solar/Wind Harmer
7.882
270239V3-007_GEN1
Solar/Wind Harmer
2.121
24639705ELKHART HY
Adder
0.188
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
274812UNIV PK N;8U
Adder
6.107
274801UNIV PARK;4U
Adder
7.097
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274745AC1-111 GEN9
Adder
6.762
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
25194608D.CRK4
Adder
1.973
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
253432AC1-085 GEN2
Solar/Wind Harmer
0.296
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
6.29
946101AF1-275 GEN
Solar/Wind Harmer
2.363
942861AE2-305 GEN
Solar/Wind Harmer
11.602
270224U2-072_GEN2
Solar/Wind Harmer
2.884
270227U2-072_GEN3
Solar/Wind Harmer
2.884
270228U2-072_GEN4
Solar/Wind Harmer
2.884
270231U2-072_GEN5
Solar/Wind Harmer
2.884
970077AG2-063 GEN
Solar/Wind Harmer
7.807
270518AE2-148 GEN
Solar/Wind Harmer
17.003
964601AG1-323 GEN
Solar/Wind Harmer
4.438
964601AG1-323 GEN
Solar/Wind Harmer
2.064
938701AE1-092 GEN
Solar/Wind Harmer
28.592
253378AE2-206_GEN
Solar/Wind Harmer
4.781
276820AF1-078_GEN
Solar/Wind Harmer
2.124
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
12.73
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
5.318
960971AF2-388 GEN
Solar/Wind Harmer
13.879
970321AG2-212 GEN
Solar/Wind Harmer
22.623
942221AE2-234 GEN
Solar/Wind Harmer
0.921
246938BC-WTG3
Solar/Wind Harmer
4.97
246937BC-WTG2
Solar/Wind Harmer
4.886
270599AE1-208 GEN
Solar/Wind Harmer
10.145
270031AE2-169
Solar/Wind Harmer
10.145
253394AE2-221_GEN
Solar/Wind Harmer
5.655
253398AE2-221_GEN2
Solar/Wind Harmer
5.655
270201AC2-176 GEN
Solar/Wind Harmer
6.395
964611AG1-324 GEN
Solar/Wind Harmer
1.466
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
12.396
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
13.055
960441AF2-335 GEN
Solar/Wind Harmer
12.367
270383AD1-128 GEN
Solar/Wind Harmer
7.535
24379505HDWTR1G C
Solar/Wind Harmer
9.748
270209AC1-174_GEN
Solar/Wind Harmer
6.88
926881AC1-175 GEN
Solar/Wind Harmer
6.88
965681AG1-436 GEN
Solar/Wind Harmer
15.398
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.745
247620Y3-023
Adder
0.565
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
274808UNIV PK N;4U
Adder
6.08
972259AH1-714 GEN
Adder
23.234
274803UNIV PARK;6U
Adder
7.1
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
253317AC1-085 GEN4
Solar/Wind Harmer
9.247
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424

Details for 05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line l/o AP_P1-3_MP-765-501T_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05KAMMER_RG-05KAMMER 765.0 kV Ckt Z1 line
Contingency Name:
AP_P1-3_MP-765-501T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.76 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:4919.18
MW Contribution:8.65
Bus #Bus NameTypeMW Contribution
270156DARBY CT1
50/50
13.713
270157DARBY CT2
50/50
13.679
270158DARBY CT3
50/50
13.461
270036AE2-216 BAT
50/50
8.994
962771AG1-126 GEN
Solar/Wind Harmer
50.586
270284AF1-227 GEN1
Solar/Wind Harmer
0.014
270286AF1-227 GEN2
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.006
270459AD2-067 GEN
Solar/Wind Harmer
0
961821AG1-024 GEN
Solar/Wind Harmer
6.623
270520AE2-214 GEN
Solar/Wind Harmer
0.017
270054AF2-122 C O1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.004
241973AD2-163_GEN1
Solar/Wind Harmer
0.008
943861AF1-054 GEN
Solar/Wind Harmer
3.995
943851AF1-053 GEN
Solar/Wind Harmer
2.767
270578AF1-285 GEN2
Solar/Wind Harmer
0.678
945631AF1-228 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.006
270317AD1-130_GEN
Solar/Wind Harmer
0.014
971653AH1-327 GEN
Solar/Wind Harmer
1.38
241972AD1-140 GEN
Solar/Wind Harmer
1.032
970689AG2-444 GEN
Solar/Wind Harmer
19.097
270432AC2-029 GEN
Solar/Wind Harmer
4.134
270269AC2-059
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
8.316
270071AF1-092 GEN
Solar/Wind Harmer
17.084
253372AE2-315 SEC3
Adder
2.407
253372AE2-315 SEC3
Adder
2.407
965101AG1-375 GEN
Solar/Wind Harmer
8.831
25306009OHH W.
Adder
3.647
253349AC2-067 GEN
Solar/Wind Harmer
2.778
253400AC2-068 GEN
Solar/Wind Harmer
1.117
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
11.841
971347AH1-153 GEN
Solar/Wind Harmer
13.153
965051AG1-369 GEN
Solar/Wind Harmer
4.367
965041AG1-368 GEN
Solar/Wind Harmer
8.719
270024AE2-089 GEN
Solar/Wind Harmer
0.009
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.103
270340AC2-060 GEN
Solar/Wind Harmer
0.01
971609AH1-304 GEN
Solar/Wind Harmer
1.419
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
12.951
971673AH1-337 GEN
Solar/Wind Harmer
5.609
970115AG2-085 GEN
Solar/Wind Harmer
3.451
270594AE1-207 GEN
Solar/Wind Harmer
9.648
970289AG2-191 GEN
Solar/Wind Harmer
1.635
270240V3-007_GEN2
Solar/Wind Harmer
0.003
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971771AH1-392 GEN
Solar/Wind Harmer
8.573
971769AH1-391 GEN
Solar/Wind Harmer
9.561
274775LINCOLN ;6U
Adder
10.354
274776LINCOLN ;7U
Adder
10.354
274777LINCOLN ;8U
Adder
10.354
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
247607V1-011 GEN
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
6.16
274807UNIV PK N;3U
Adder
6.147
274805UNIV PK N;1U
Adder
6.12
274811UNIV PK N;7U
Adder
6.107
958391AF2-133 GEN
Solar/Wind Harmer
0.001
960591AF2-350 GEN
Solar/Wind Harmer
8.497
972227AH1-698 GEN1
Adder
3.176
972037AH1-567 GEN1
Adder
0.223
274827FISK ;RP
Adder
9.447
971619AH1-309 GEN
Solar/Wind Harmer
3.821
971611AH1-305 GEN
Solar/Wind Harmer
5.053
274687WILL CNTY;4U
Adder
33.939
274687WILL CNTY;4U
Adder
33.939
274675JOLIET 29;7U
Adder
37.252
274675JOLIET 29;7U
Adder
35.922
274731ELWOOD EC;2P
Adder
19.951
274733ELWOOD EC;3P
Adder
19.951
274735ELWOOD EC;4P
Adder
19.951
274728ELWOOD EC;5P
Adder
19.951
970833AG2-524 GEN
Solar/Wind Harmer
9.313
970833AG2-524 GEN
Solar/Wind Harmer
6.209
274746AC1-111 G10
Adder
6.762
274744AC1-111 GEN8
Adder
6.762
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.608
25196308WSDLE2
Adder
10.516
25196208WSDLE1
Adder
10.49
25196708WSDLE6
Adder
10.463
25196508WSDLE4
Adder
10.2
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
276868AE1-113 GEN
Solar/Wind Harmer
1.681
276882AE2-255 GEN
Solar/Wind Harmer
0.979
970169AG2-114 GEN
Solar/Wind Harmer
8.358
971177AH1-047 GEN
Solar/Wind Harmer
5.154
971675AH1-338 GEN
Solar/Wind Harmer
3.256
971411AH1-196 GEN
Solar/Wind Harmer
12.519
963841AG1-237 GEN
Solar/Wind Harmer
3.615
971171AH1-044 GEN
Solar/Wind Harmer
16.66
926823AC1-168 GEN
Solar/Wind Harmer
1.415
274823ROCKFORD ;21
Adder
23.229
254304AE2-114 C
Solar/Wind Helper
0.214
241982AE2-343 S C
Solar/Wind Helper
0.217
241997AF1-093 GEN
Solar/Wind Helper
0.248
23750501ELLIOTTS
Solar/Wind Helper
0.61
20092526R32
Solar/Wind Helper
1.098
203961AE2-224 GEN
Solar/Wind Helper
2.278
20091526CHSTN_FL
Solar/Wind Helper
0.55
20090526Q36
Solar/Wind Helper
0.985
203993AD2-133_GEN1
Solar/Wind Helper
0.985
203846AF2-130 C
Solar/Wind Helper
0.425
238126S14_GEN_1
Solar/Wind Helper
0.64
941231AE2-117 GEN
Solar/Wind Helper
0.447
203855AF2-088 C
Solar/Wind Helper
0.144
203804AE2-113_GEN
Solar/Wind Helper
1.639
270051AF1-062 GEN
50/50
17.076
270475AD2-096_GEN
50/50
10.066
970153AG2-106 GEN
Solar/Wind Harmer
32.303
961921AG1-034 GEN
Solar/Wind Harmer
9.935
241955AC1-078 GEN
Solar/Wind Harmer
0.009
241974AD2-163_GEN2
Solar/Wind Harmer
0.008
942051AE2-217 GEN
Solar/Wind Harmer
18.548
270391AF1-285 GEN3
Solar/Wind Harmer
0.678
970605AG2-385 GEN
Solar/Wind Harmer
6.136
270485AE1-090_GEN
Solar/Wind Harmer
0.001
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.015
270273AD2-016 GEN
Solar/Wind Harmer
0.935
944531AF1-118 GEN
Solar/Wind Harmer
40.219
972173AH1-669 GEN
Solar/Wind Harmer
4.474
270043AE2-236 GEN
Solar/Wind Harmer
5.712
959331AF2-224 GEN
Solar/Wind Harmer
6.217
965021AG1-366 GEN
Solar/Wind Harmer
2.96
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
970513AG2-328 GEN
Solar/Wind Harmer
3.83
970517AG2-330 GEN
Solar/Wind Harmer
22.981
970191AG2-125 GEN
Solar/Wind Harmer
2.269
253415AE1-040 GEN
Solar/Wind Harmer
0.004
970349AG2-230 GEN
Solar/Wind Harmer
13.153
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.056
24721905FLATG4
Adder
25.369
971617AH1-308 GEN
Solar/Wind Harmer
7.263
270491AE1-102 GEN2
Solar/Wind Harmer
1.132
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.019
970031AG2-029 GEN
Solar/Wind Harmer
5.627
958821AF2-173 GEN
Solar/Wind Harmer
12.116
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
8.226
253406AD2-031_GEN
Solar/Wind Harmer
0.643
970289AG2-191 GEN
Solar/Wind Harmer
0.947
970291AG2-192 GEN
Solar/Wind Harmer
0.861
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
247643Z2-116 C
Solar/Wind Harmer
0
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.138
274772LINCOLN ;3U
Adder
10.354
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.32
274724RIVER EC ;11
Adder
21.639
274752CRETE EC ;2U
Adder
10.063
274753CRETE EC ;3U
Adder
10.063
24642205MAYFLWER
Adder
0.776
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970707AG2-453 GEN
Solar/Wind Harmer
27.781
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
276806AD2-047 C O1
Solar/Wind Harmer
4.815
970941AG2-585 GEN
Solar/Wind Harmer
10.621
274802UNIV PARK;5U
Adder
7.1
972228AH1-698 GEN2
Adder
4.511
274826FISK ;BP
Adder
13.329
274800UNIV PARK;3U
Adder
7.097
972038AH1-567 GEN2
Adder
0.444
276897AD1-100 C
Solar/Wind Harmer
0.011
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
945111AF1-176 GEN
Solar/Wind Harmer
6.882
274676JOLIET 29;8U
Adder
35.922
274729ELWOOD EC;1P
Adder
19.951
274730ELWOOD EC;6P
Adder
19.951
274734ELWOOD EC;8P
Adder
19.951
274736ELWOOD EC;9P
Adder
19.951
276893AG1-478 C
Solar/Wind Harmer
0.336
943121AE2-341 GEN
Solar/Wind Harmer
14.16
943591AF1-030 GEN
Solar/Wind Harmer
9.416
270356AE2-297 GEN
Solar/Wind Harmer
0.011
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
8.438
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
21.642
25196608WSDLE5
Adder
10.305
276805AD2-038 GEN
Solar/Wind Harmer
0.002
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.307
252510AF1-249 C
Solar/Wind Harmer
0.065
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.891
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.306
274850MENDOTA H;RU
Solar/Wind Harmer
0.098
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.15
959091AF2-200 GEN
Solar/Wind Harmer
16.66
24441205WTRV SLR C
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
16.64
24728705AND G3
Adder
9.564
24728505AND G1
Adder
4.573
270258AD1-119 GEN
Solar/Wind Harmer
0.002
972236AH1-702 GEN2
Adder
2.611
235058AG1-386 C
Solar/Wind Helper
0.453
237048AF1-022 C
Solar/Wind Helper
0.176
254305AE2-115 C
Solar/Wind Helper
0.214
237043AE2-125 C
Solar/Wind Helper
0.172
964991AG1-363 GEN
Solar/Wind Helper
3.577
202652Y1-033 WT C
Solar/Wind Helper
0.525
20089126CSLMN_L13
Solar/Wind Helper
0.557
20089026BF_G21_K23
Solar/Wind Helper
0.441
23750701CROSSCHOOL
Solar/Wind Helper
1.122
203818AF1-086 GEN
Solar/Wind Helper
1.594
238118U2-030_1
Solar/Wind Helper
0.269
238127S14_GEN_2
Solar/Wind Helper
0.64
203854AF2-039 C
Solar/Wind Helper
0.3
20334926Z1-069 C
Solar/Wind Helper
1.268
238202AE2-262_GEN
Solar/Wind Helper
0.902
270166AC1-044 GEN3
50/50
18.401
270159DARBY CT4
50/50
13.494
962761AG1-125 GEN
Solar/Wind Harmer
50.586
970149AG2-104 GEN
Solar/Wind Harmer
54.635
970155AG2-107 GEN
Solar/Wind Harmer
32.303
270349AD2-093_GEN
Solar/Wind Harmer
0.009
270223U2-072_GEN1
Solar/Wind Harmer
0.001
970593AG2-378 GEN
Solar/Wind Harmer
2.27
270462AD2-086
Solar/Wind Harmer
0.021
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.015
25326309TAIT D
Adder
1.4
960071AF2-298 GEN
Solar/Wind Harmer
4.426
965011AG1-365 GEN
Solar/Wind Harmer
8.881
253370AE2-315 SEC1
Adder
2.545
253371AE2-315 SEC2
Adder
2.407
965651AG1-433 GEN
Solar/Wind Harmer
2.599
970245AG2-165 GEN
Solar/Wind Harmer
3.83
958861AF2-177 GEN
Solar/Wind Harmer
3.827
971995AH1-542 GEN
Solar/Wind Harmer
3.236
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.319
270246TR4_N_V150
Solar/Wind Harmer
0.056
24721705FLATG2
Adder
25.369
965421AG1-410 GEN
Solar/Wind Harmer
26.181
246936BC-WTG1
Solar/Wind Harmer
0.353
270489AE1-102 GEN1
Solar/Wind Harmer
1.132
247536S-71 GEN
Solar/Wind Harmer
0.349
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.654
270063AE2-323 C
Solar/Wind Harmer
0.007
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.064
270263AC1-001 GEN
Solar/Wind Harmer
0.865
270032AE2-172
Solar/Wind Harmer
5.743
970291AG2-192 GEN
Solar/Wind Harmer
1.119
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.306
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.568
24639705ELKHART HY
Adder
0.188
276903AD2-071 C
Solar/Wind Harmer
9.56
274773LINCOLN ;4U
Adder
10.354
274774LINCOLN ;5U
Adder
10.354
970373AG2-245 GEN
Solar/Wind Harmer
17.958
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274723RIVER EC ;12
Adder
21.894
274751CRETE EC ;1U
Adder
10.063
274754CRETE EC ;4U
Adder
10.063
276164X3-005 C
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.064
274812UNIV PK N;8U
Adder
6.107
276776AD2-060 GEN
Solar/Wind Harmer
0.887
274801UNIV PARK;4U
Adder
7.097
941551AE2-152 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
15.149
270505AE1-170 C O1
Solar/Wind Harmer
8.915
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
10.609
274676JOLIET 29;8U
Adder
37.252
274674JOLIET 9 ;6U
Adder
18.689
274732ELWOOD EC;7P
Adder
19.951
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
970773AG2-487 GEN
Solar/Wind Harmer
1.492
274745AC1-111 GEN9
Adder
6.762
24791305MDL-5G
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.404
939401AE1-172 GEN
Solar/Wind Harmer
6.298
276691AA1-018 GEN1
Solar/Wind Harmer
1.02
274682WAUKEGAN ;7U
Adder
21.642
274828WAUKEGAN ;BP
Adder
13.296
276901AD2-066 C O1
Solar/Wind Harmer
0.008
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
962781AG1-127 GEN
Solar/Wind Harmer
7.975
971997AH1-543 GEN
Solar/Wind Harmer
4.396
25194608D.CRK4
Adder
1.973
274872LEEDK;1U
Solar/Wind Harmer
0.005
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.15
957471AF2-041 GEN
Solar/Wind Harmer
24.989
959081AF2-199 GEN
Solar/Wind Harmer
8.33
971067AG2-660 GEN
Solar/Wind Harmer
2.777
970569AG2-363 GEN
Solar/Wind Harmer
24.96
24728605AND G2
Adder
4.573
274822ROCKFORD ;11
Adder
23.399
972235AH1-702 GEN1
Adder
3.003
963741AG1-226 GEN
Solar/Wind Harmer
19.652
25196808ZIMRHP
Adder
58.315
254303AC2-168 GEN
Solar/Wind Helper
0.155
237046AF1-021 C
Solar/Wind Helper
0.463
241966AE1-183 GEN
Solar/Wind Helper
0.248
238185AF2-356 C
Solar/Wind Helper
2.025
20089226LOOKOUT
Solar/Wind Helper
0.542
20088826HIGHLAND
Solar/Wind Helper
0.847
20094526CT_V3-030
Solar/Wind Helper
0.446
235054AD2-180 GEN
Solar/Wind Helper
1.566
964201AG1-281 GEN
Solar/Wind Helper
0.457
238117U2-030
Solar/Wind Helper
0.269
235531U2-073 GEN
Solar/Wind Helper
2.545
964391AG1-301 GEN
Solar/Wind Helper
0.446
203954AE2-126 C
Solar/Wind Helper
0.443
23751201ROTHROCK
Solar/Wind Helper
0.652
238206AE2-263_GEN
Solar/Wind Helper
0.858
970819AG2-516 GEN
Solar/Wind Harmer
7.858
270119AB2-067 GEN1
50/50
18.401
270120AB2-067 GEN2
50/50
18.401
270160DARBY CT5
50/50
0.735
270161DARBY CT6
50/50
0.725
270466AD2-091
50/50
8.176
270471AD2-092_GEN
Solar/Wind Harmer
0.009
942861AE2-305 GEN
Solar/Wind Harmer
8.094
270224U2-072_GEN2
Solar/Wind Harmer
0.001
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
970077AG2-063 GEN
Solar/Wind Harmer
5.8
270518AE2-148 GEN
Solar/Wind Harmer
0.847
964601AG1-323 GEN
Solar/Wind Harmer
3.902
964601AG1-323 GEN
Solar/Wind Harmer
2.601
938701AE1-092 GEN
Solar/Wind Harmer
15.513
971655AH1-328 GEN
Solar/Wind Harmer
3.428
253378AE2-206_GEN
Solar/Wind Harmer
0.005
276820AF1-078_GEN
Solar/Wind Harmer
0.002
970329AG2-216 GEN
Solar/Wind Harmer
4.005
25326509SID D
Adder
1.713
25326109MON D
Adder
1.698
25322209TAIT E
Adder
12.455
25322209TAIT E
Adder
12.175
970611AG2-400 GEN
Solar/Wind Harmer
8.881
970627AG2-408 GEN
Solar/Wind Harmer
2.664
253370AE2-315 SEC1
Adder
2.545
944541AF1-119 GEN
Solar/Wind Harmer
0.594
960971AF2-388 GEN
Solar/Wind Harmer
5.197
970321AG2-212 GEN
Solar/Wind Harmer
3.83
942221AE2-234 GEN
Solar/Wind Harmer
0.044
246938BC-WTG3
Solar/Wind Harmer
0.316
246937BC-WTG2
Solar/Wind Harmer
0.353
270599AE1-208 GEN
Solar/Wind Harmer
7.961
270031AE2-169
Solar/Wind Harmer
4.777
253394AE2-221_GEN
Solar/Wind Harmer
0.011
253398AE2-221_GEN2
Solar/Wind Harmer
0.011
270201AC2-176 GEN
Solar/Wind Harmer
0.002
964611AG1-324 GEN
Solar/Wind Harmer
0.65
247621Y3-024
Adder
0.3
970883AG2-550 GEN
Solar/Wind Harmer
8.648
970885AG2-551 GEN
Solar/Wind Harmer
2.883
970825AG2-519 GEN
Solar/Wind Harmer
9.566
960441AF2-335 GEN
Solar/Wind Harmer
8.628
971613AH1-306 GEN
Solar/Wind Harmer
4.135
270383AD1-128 GEN
Solar/Wind Harmer
0.005
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
10.743
965791AG1-447 GEN
Solar/Wind Harmer
7.878
270216AD2-079_GEN
Solar/Wind Harmer
0.001
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
247620Y3-023
Adder
0.565
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24441505OLIV SLR
Solar/Wind Harmer
0
274770LINCOLN ;1U
Adder
10.354
274771LINCOLN ;2U
Adder
10.354
270007AE1-245 C
Solar/Wind Harmer
0.002
274808UNIV PK N;4U
Adder
6.08
274888KELLY CRK;1U
Solar/Wind Harmer
0.499
274887GEN-1.85
Solar/Wind Harmer
0.224
276843GEN-1.7
Solar/Wind Harmer
0.275
972259AH1-714 GEN
Adder
23.234
958011AF2-095 GEN
Solar/Wind Harmer
12.235
274803UNIV PARK;6U
Adder
7.1
957891AF2-083 GEN
Solar/Wind Harmer
0.001
24728805RICHG1
Adder
4.598
24728905RICHG2
Adder
4.598
274674JOLIET 9 ;6U
Adder
18.689
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
961051AF2-396 GEN
Solar/Wind Harmer
16.913
961051AF2-396 GEN
Solar/Wind Harmer
11.276
971573AH1-285 GEN
Solar/Wind Harmer
1.571
958481AF2-142 GEN
Solar/Wind Harmer
12.626
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.139
274696ROCKY RD ;4P
Adder
13.733
274695ROCKY RD ;2P
Adder
13.416
274693ROCKY RD ;1P
Adder
13.284
274697ROCKY RD ;3P
Adder
3.645
274683WAUKEGAN ;8U
Adder
25.365
274683WAUKEGAN ;8U
Adder
21.381
25183208HLCRTG
Solar/Wind Harmer
0.013
958491AF2-143 GEN
Solar/Wind Harmer
12.583
962691AG1-118 GEN
Solar/Wind Harmer
25.162
966841AG1-555 GEN
Solar/Wind Harmer
0.948
970921AG2-575 GEN
Solar/Wind Harmer
8.38
970921AG2-575 GEN
Solar/Wind Harmer
2.793
274879MINONK ;1U
Solar/Wind Harmer
0.353
25194408D.CRK1
Adder
9.077
25194508D.CRK3
Adder
1.697
252519AF1-045_GEN
Solar/Wind Harmer
7.283
252516AE2-318_GEN
Solar/Wind Harmer
6.46
942991AE2-321 GEN
Solar/Wind Harmer
9.334
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
16.689
971335AH1-147 GEN
Solar/Wind Harmer
16.689
971341AH1-150 GEN
Solar/Wind Harmer
16.66
971343AH1-151 GEN
Solar/Wind Harmer
16.66
970623AG2-406 GEN
Solar/Wind Harmer
1.522
970241AG2-163 GEN
Solar/Wind Harmer
4.844
23652301WDPWR_K20
Solar/Wind Helper
0.137
241967AE2-285_GEN
Solar/Wind Helper
0.621
241801AE1-079 GEN
Solar/Wind Helper
0.242
241985AE1-237 GEN
Solar/Wind Helper
0.242
962101AG1-054 GEN
Solar/Wind Helper
0.632
946071AF1-272 GEN
Solar/Wind Helper
2.567
23585401KL_K28_T16
Solar/Wind Helper
1.167
203955AF1-039 C O1
Solar/Wind Helper
0.346
944781AF1-143 GEN
Solar/Wind Helper
2.312
20083426SW_E13_K22
Solar/Wind Helper
0.053
20084626FORWARD
Solar/Wind Helper
0.336
20088926STNY CRK
Solar/Wind Helper
0.77
203940AF1-140 C
Solar/Wind Helper
0.374
20088626ARWF_N39
Solar/Wind Helper
1.147
20303426NA_O38_P22
Solar/Wind Helper
0.94
946381AF1-302 GEN
Solar/Wind Helper
0.21
203853AF1-134 C O1
Solar/Wind Helper
0.452
203952AE2-129 C
Solar/Wind Helper
0.447
203946AE2-131 C
Solar/Wind Helper
0.448
238120AE2-309 GEN
Solar/Wind Helper
0.401
238217AF1-153 C O1
Solar/Wind Helper
0.223
20398826ARMNA MT
Solar/Wind Helper
1.407
CBM West 1LTFEXP_CBM-W1->PJM
CBM
155.754
CBM South 1LTFEXP_CBM-S1->PJM
CBM
34.409
MECLTFEXP_MEC->PJM
CLTF
18.875
SIGELTFEXP_SIGE->PJM
CLTF
0.583
CPLELTFEXP_CPLE->PJM
CLTF
2.705
CBM West 2LTFEXP_CBM-W2->PJM
CBM
133.737
LAGNLTFEXP_LAGN->PJM
CLTF
17.886
CBM South 2LTFEXP_CBM-S2->PJM
CBM
12.768
TVALTFEXP_TVA->PJM
CLTF
8.721
NYPJM->LTFIMP_NY
CLTF
5.332
LGEELTFEXP_LGEE->PJM
CLTF
7.674
WECLTFEXP_WEC->PJM
CLTF
4.549
AG2-052LTFEXP_AG2-052->PJM
LTF
0.283
AH1-155LTFEXP_AH1-155->PJM
LTF
0.424

Details for 05MADDOX-05E LIMA 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MADDOX-05E LIMA 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:120.12 %
Rating:2246.0 MVA
Rating Type:B
MVA to Mitigate:2697.98
MW Contribution:3.86
Bus #Bus NameTypeMW Contribution
970615AG2-402 GEN
50/50
4.57
24729405KEY G3
50/50
0.365
24729305KEY G2
50/50
0.359
24729205KEY G1
50/50
0.357
247620Y3-023
50/50
0.459
246938BC-WTG3
Solar/Wind Harmer
1.037
246937BC-WTG2
Solar/Wind Harmer
1.161
24727205RPMNG3
50/50
3.285
971599AH1-298 GEN
50/50
10.265
24729505KEY G4
50/50
6.681
957201AF2-014 GEN
Solar/Wind Harmer
0.002
270435AC2-044 GEN
Solar/Wind Harmer
3.625
963791AG1-232 GEN
Solar/Wind Harmer
11.533
965041AG1-368 GEN
Solar/Wind Harmer
8.372
270071AF1-092 GEN
Solar/Wind Harmer
14.295
965051AG1-369 GEN
Solar/Wind Harmer
3.565
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.034
971771AH1-392 GEN
Solar/Wind Harmer
5.793
971347AH1-153 GEN
Solar/Wind Harmer
8.606
971619AH1-309 GEN
Solar/Wind Harmer
2.577
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.222
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
965431AG1-411 GEN
50/50
45.318
24727105RPMNG2
50/50
3.312
970583AG2-370 GEN
50/50
2.791
270491AE1-102 GEN2
Solar/Wind Harmer
3.72
959331AF2-224 GEN
Solar/Wind Harmer
9.596
965021AG1-366 GEN
Solar/Wind Harmer
4.57
970031AG2-029 GEN
Solar/Wind Harmer
5.428
270043AE2-236 GEN
Solar/Wind Harmer
5.157
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.245
971617AH1-308 GEN
Solar/Wind Harmer
5.12
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.761
970349AG2-230 GEN
Solar/Wind Harmer
8.606
24642205MAYFLWER
Adder
0.519
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.283
970517AG2-330 GEN
Solar/Wind Harmer
13.699
274752CRETE EC ;2U
Adder
6.177
274753CRETE EC ;3U
Adder
6.177
274724RIVER EC ;11
Adder
13.226
247604X1-042
Adder
0.309
270535AF1-215 GEN1
Solar/Wind Harmer
0.006
274772LINCOLN ;3U
Adder
6.227
274802UNIV PARK;5U
Adder
4.274
274826FISK ;BP
Adder
8.017
274800UNIV PARK;3U
Adder
4.262
972038AH1-567 GEN2
Adder
0.267
276806AD2-047 C O1
Solar/Wind Harmer
2.886
970941AG2-585 GEN
Solar/Wind Harmer
6.366
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.696
970707AG2-453 GEN
Solar/Wind Harmer
16.532
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.371
971609AH1-304 GEN
Solar/Wind Harmer
0.881
274814UNIV PK N;0U
Adder
3.743
274807UNIV PK N;3U
Adder
3.735
274805UNIV PK N;1U
Adder
3.719
274811UNIV PK N;7U
Adder
3.711
270536AF1-215 GEN2
Solar/Wind Harmer
0.006
274775LINCOLN ;6U
Adder
6.227
274776LINCOLN ;7U
Adder
6.227
274777LINCOLN ;8U
Adder
6.227
972037AH1-567 GEN1
Adder
0.134
274827FISK ;RP
Adder
5.682
960591AF2-350 GEN
Solar/Wind Harmer
5.093
972227AH1-698 GEN1
Adder
1.898
274687WILL CNTY;4U
Adder
20.23
274687WILL CNTY;4U
Adder
20.23
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.163
274675JOLIET 29;7U
Adder
21.371
274731ELWOOD EC;2P
Adder
11.842
274733ELWOOD EC;3P
Adder
11.842
274735ELWOOD EC;4P
Adder
11.842
274728ELWOOD EC;5P
Adder
11.843
970833AG2-524 GEN
Solar/Wind Harmer
5.503
970833AG2-524 GEN
Solar/Wind Harmer
3.669
971611AH1-305 GEN
Solar/Wind Harmer
2.963
274746AC1-111 G10
Adder
3.978
274744AC1-111 GEN8
Adder
3.978
970289AG2-191 GEN
Solar/Wind Harmer
0.932
270594AE1-207 GEN
Solar/Wind Harmer
5.432
276868AE1-113 GEN
Solar/Wind Harmer
0.971
276882AE2-255 GEN
Solar/Wind Harmer
0.566
971177AH1-047 GEN
Solar/Wind Harmer
2.975
971411AH1-196 GEN
Solar/Wind Harmer
7.208
971675AH1-338 GEN
Solar/Wind Harmer
1.873
276893AG1-478 C
Solar/Wind Harmer
0.199
274729ELWOOD EC;1P
Adder
11.842
274730ELWOOD EC;6P
Adder
11.843
274734ELWOOD EC;8P
Adder
11.843
274736ELWOOD EC;9P
Adder
11.843
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.328
943591AF1-030 GEN
Solar/Wind Harmer
5.538
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.642
970289AG2-191 GEN
Solar/Wind Harmer
0.539
970291AG2-192 GEN
Solar/Wind Harmer
0.49
958821AF2-173 GEN
Solar/Wind Harmer
6.825
270004AE1-209 GEN
Solar/Wind Harmer
1.056
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.178
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.512
274855GSG-6 ;RU
Solar/Wind Harmer
0.176
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.086
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.78
959091AF2-200 GEN
Solar/Wind Harmer
9.543
972236AH1-702 GEN2
Adder
1.491
970571AG2-364 GEN
Solar/Wind Harmer
9.45
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.232
274767LEE CO EC;8U
Adder
6.158
946031AF1-268 GEN
Solar/Wind Harmer
4.44
970611AG2-400 GEN
Solar/Wind Harmer
13.709
970627AG2-408 GEN
Solar/Wind Harmer
4.113
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.416
960971AF2-388 GEN
Solar/Wind Harmer
3.647
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.449
961051AF2-396 GEN
Solar/Wind Harmer
7.632
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.819
965791AG1-447 GEN
Solar/Wind Harmer
5.001
270599AE1-208 GEN
Solar/Wind Harmer
4.943
270031AE2-169
Solar/Wind Harmer
2.966
970321AG2-212 GEN
Solar/Wind Harmer
2.283
274808UNIV PK N;4U
Adder
3.694
274770LINCOLN ;1U
Adder
6.227
274771LINCOLN ;2U
Adder
6.227
274803UNIV PARK;6U
Adder
4.274
274888KELLY CRK;1U
Solar/Wind Harmer
0.299
274887GEN-1.85
Solar/Wind Harmer
0.134
276843GEN-1.7
Solar/Wind Harmer
0.165
958011AF2-095 GEN
Solar/Wind Harmer
7.334
972259AH1-714 GEN
Adder
13.842
274674JOLIET 9 ;6U
Adder
11.098
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.921
958481AF2-142 GEN
Solar/Wind Harmer
7.4
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.667
274696ROCKY RD ;4P
Adder
8.021
274695ROCKY RD ;2P
Adder
7.836
24727005RPMNG1
50/50
3.301
960861AF2-377 GEN
50/50
2.381
970521AG2-332 GEN
50/50
10.716
24639705ELKHART HY
50/50
0.148
246936BC-WTG1
Solar/Wind Harmer
1.161
270489AE1-102 GEN1
Solar/Wind Harmer
3.72
965421AG1-410 GEN
Solar/Wind Harmer
81.572
965011AG1-365 GEN
Solar/Wind Harmer
13.709
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.26
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.84
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.823
958861AF2-177 GEN
Solar/Wind Harmer
2.615
945111AF1-176 GEN
Solar/Wind Harmer
10.481
270505AE1-170 C O1
Solar/Wind Harmer
6.013
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.942
970245AG2-165 GEN
Solar/Wind Harmer
2.283
970373AG2-245 GEN
Solar/Wind Harmer
11.033
274751CRETE EC ;1U
Adder
6.177
274754CRETE EC ;4U
Adder
6.177
274723RIVER EC ;12
Adder
13.388
274812UNIV PK N;8U
Adder
3.711
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.227
274774LINCOLN ;5U
Adder
6.227
274801UNIV PARK;4U
Adder
4.262
276776AD2-060 GEN
Solar/Wind Harmer
0.532
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.6
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.162
274674JOLIET 9 ;6U
Adder
11.098
274732ELWOOD EC;7P
Adder
11.843
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.22
274745AC1-111 GEN9
Adder
3.978
276691AA1-018 GEN1
Solar/Wind Harmer
0.598
274682WAUKEGAN ;7U
Adder
12.642
970291AG2-192 GEN
Solar/Wind Harmer
0.638
274828WAUKEGAN ;BP
Adder
7.76
270005AE1-210 C O1
Solar/Wind Harmer
1.056
965031AG1-367 GEN
Solar/Wind Harmer
4.875
962781AG1-127 GEN
Solar/Wind Harmer
4.624
939401AE1-172 GEN
Solar/Wind Harmer
3.633
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.233
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.531
276861AD2-134 GEN
Solar/Wind Harmer
0.086
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.315
959081AF2-199 GEN
Solar/Wind Harmer
4.772
971067AG2-660 GEN
Solar/Wind Harmer
1.591
274822ROCKFORD ;11
Adder
13.38
970825AG2-519 GEN
Solar/Wind Harmer
1.686
972235AH1-702 GEN1
Adder
1.714
970819AG2-516 GEN
Solar/Wind Harmer
5.675
970569AG2-363 GEN
Solar/Wind Harmer
14.175
971475AH1-234 GEN
Solar/Wind Harmer
2.289
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.232
274766LEE CO EC;7U
Adder
6.158
276903AD2-071 C
Solar/Wind Harmer
5.188
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.154
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.361
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.579
963741AG1-226 GEN
Solar/Wind Harmer
10.198
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.15
247536S-71 GEN
Solar/Wind Harmer
0.171
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.633
970115AG2-085 GEN
Solar/Wind Harmer
1.915
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.543
274823ROCKFORD ;21
Adder
13.283
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.802
970169AG2-114 GEN
Solar/Wind Harmer
4.71
971681AH1-341 GEN
Solar/Wind Harmer
7.556
971549AH1-272 GEN
Solar/Wind Harmer
9.681
961011AF2-392 GEN
Solar/Wind Harmer
2.722
957751AF2-069 GEN
Solar/Wind Harmer
0.152
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.771
941731AE2-173 GEN
Solar/Wind Harmer
3.786
946321AF1-296 GEN
Solar/Wind Harmer
2.514
963841AG1-237 GEN
Solar/Wind Harmer
1.925
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.154
276848AB2-070 GEN3
Solar/Wind Harmer
0.153
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.247
971029AG2-637 GEN
Solar/Wind Harmer
5.161
971673AH1-337 GEN
Solar/Wind Harmer
2.14
247607V1-011 GEN
Solar/Wind Harmer
0.001
270317AD1-130_GEN
Solar/Wind Helper
4.139
966831AG1-554 GEN
Solar/Wind Helper
0.884
270284AF1-227 GEN1
Solar/Wind Helper
1.894
270286AF1-227 GEN2
Solar/Wind Helper
0.695
270287AF1-227 GEN3
Solar/Wind Helper
0.695
270499AE1-146 GEN
Solar/Wind Helper
1.973
945641AF1-229 GEN
Solar/Wind Helper
0.949
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
6.987
276157O29GEN1
Solar/Wind Harmer
0.746
274878BISHOP HL;2U
Solar/Wind Harmer
0.154
942111AE2-223 GEN
Solar/Wind Harmer
1.477
965931AG1-462 GEN
Solar/Wind Harmer
11.384
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.388
959611AF2-252 GEN
Solar/Wind Harmer
1.488
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.154
971993AH1-541 GEN
Solar/Wind Harmer
1.946
276621W2-048 GEN
Solar/Wind Harmer
0.209
276838X2-022 GEN2
Solar/Wind Harmer
0.233
942481AE2-261 GEN
Solar/Wind Harmer
11.923
970193AG2-126 GEN
Solar/Wind Harmer
5.78
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.21
24728505AND G1
Adder
2.013
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.781
970519AG2-331 GEN
Solar/Wind Harmer
7.913
970699AG2-449 GEN
Solar/Wind Harmer
0.761
270485AE1-090_GEN
Solar/Wind Helper
0.325
942871AE2-306 GEN
Solar/Wind Helper
0.446
270541AE2-072 C
Solar/Wind Helper
0.947
276615X2-022 GEN
Solar/Wind Harmer
0.043
965911AG1-460 GEN
Solar/Wind Harmer
0.798
24728605AND G2
Adder
2.013
970773AG2-487 GEN
Solar/Wind Harmer
0.599
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.176
270462AD2-086
Solar/Wind Helper
3.736
270223U2-072_GEN1
Solar/Wind Helper
0.877
270578AF1-285 GEN2
Solar/Wind Helper
0.594
270391AF1-285 GEN3
Solar/Wind Helper
0.594
247522W1-056 GEN
Solar/Wind Helper
1.179
960841AF2-375 GEN
Solar/Wind Helper
1.188
270349AD2-093_GEN
Solar/Wind Helper
0.862
274693ROCKY RD ;1P
Adder
7.759
274697ROCKY RD ;3P
Adder
2.129
274683WAUKEGAN ;8U
Adder
14.804
274683WAUKEGAN ;8U
Adder
12.479
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.613
958491AF2-143 GEN
Solar/Wind Harmer
7.306
970921AG2-575 GEN
Solar/Wind Harmer
4.859
970921AG2-575 GEN
Solar/Wind Harmer
1.62
971613AH1-306 GEN
Solar/Wind Harmer
2.328
274879MINONK ;1U
Solar/Wind Harmer
0.204
942991AE2-321 GEN
Solar/Wind Harmer
5.39
971333AH1-146 GEN
Solar/Wind Harmer
9.601
971335AH1-147 GEN
Solar/Wind Harmer
9.601
960441AF2-335 GEN
Solar/Wind Harmer
4.786
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.543
971343AH1-151 GEN
Solar/Wind Harmer
9.543
970825AG2-519 GEN
Solar/Wind Harmer
5.263
274856ECOGROVE ;U1
Solar/Wind Harmer
0.111
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.658
274764LEE CO EC;5U
Adder
6.246
274765LEE CO EC;6U
Adder
6.246
274762LEE CO EC;3U
Adder
6.232
274763LEE CO EC;4U
Adder
6.173
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.349
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.761
276741O09 GEN1
Solar/Wind Harmer
0.164
276708O09 GEN2
Solar/Wind Harmer
0.164
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.181
276646AC1-214 GEN2
Solar/Wind Harmer
0.181
966841AG1-555 GEN
Solar/Wind Harmer
0.519
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.158
960611AF2-352 GEN
Solar/Wind Harmer
1.488
970241AG2-163 GEN
Solar/Wind Harmer
2.514
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.299
276911AD2-131_GEN
Solar/Wind Harmer
0.547
970883AG2-550 GEN
Solar/Wind Harmer
3.858
970885AG2-551 GEN
Solar/Wind Harmer
1.286
945391AF1-204 GEN
Solar/Wind Harmer
4.094
970623AG2-406 GEN
Solar/Wind Harmer
0.671
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.387
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.761
270224U2-072_GEN2
Solar/Wind Helper
0.877
270227U2-072_GEN3
Solar/Wind Helper
0.877
270228U2-072_GEN4
Solar/Wind Helper
0.877
270231U2-072_GEN5
Solar/Wind Helper
0.877
270471AD2-092_GEN
Solar/Wind Helper
0.862
253378AE2-206_GEN
Solar/Wind Helper
0.694
276820AF1-078_GEN
Solar/Wind Helper
0.324
241960AC2-195 GEN
Solar/Wind Helper
0.702
944201AF1-088_MTX
Adder
54.26
957141AF2-008_MTX
Adder
17.407
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
68.17
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.448
MECLTFEXP_MEC->PJM
CLTF
9.525
SIGELTFEXP_SIGE->PJM
CLTF
0.193
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.893
LAGNLTFEXP_LAGN->PJM
CLTF
5.535
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.203
TVALTFEXP_TVA->PJM
CLTF
2.191
NYPJM->LTFIMP_NY
CLTF
1.315
LGEELTFEXP_LGEE->PJM
CLTF
1.728
WECLTFEXP_WEC->PJM
CLTF
2.594
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.108
AG2-052LTFEXP_AG2-052->PJM
LTF
0.168
AH1-155LTFEXP_AH1-155->PJM
LTF
0.252

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.65 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:6032.93
MW Contribution:8.32
Bus #Bus NameTypeMW Contribution
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:140.14 %
Rating:4142.0 MVA
Rating Type:B
MVA to Mitigate:5804.66
MW Contribution:7.92
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632

Details for 05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MARYSVL_RS-05MARYSV 765.0 kV Ckt Z1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.5 %
Rating:4047.0 MVA
Rating Type:A
MVA to Mitigate:5281.19
MW Contribution:7.15
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
18.435
270144AC1-141 ST1_
50/50
3.968
24643105BUCHANAN
50/50
0.024
24653605MOTTVILLE
50/50
0.007
971347AH1-153 GEN
Solar/Wind Harmer
20.909
971771AH1-392 GEN
Solar/Wind Harmer
13.038
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971769AH1-391 GEN
Solar/Wind Harmer
14.442
270071AF1-092 GEN
Solar/Wind Harmer
24.752
971619AH1-309 GEN
Solar/Wind Harmer
5.808
274775LINCOLN ;6U
Adder
15.292
274776LINCOLN ;7U
Adder
15.292
274777LINCOLN ;8U
Adder
15.292
274814UNIV PK N;0U
Adder
8.954
274807UNIV PK N;3U
Adder
8.935
274805UNIV PK N;1U
Adder
8.896
274811UNIV PK N;7U
Adder
8.876
972037AH1-567 GEN1
Adder
0.323
274827FISK ;RP
Adder
13.681
960591AF2-350 GEN
Solar/Wind Harmer
12.291
24344005CKG1
50/50
12.252
270142AC1-141 CT1_
50/50
4.479
24641605TWIN BRNCH
50/50
0.032
24642205MAYFLWER
50/50
1.247
944961AF1-161 GEN
50/50
5.318
962601AG1-109 GEN
50/50
5.318
970349AG2-230 GEN
Solar/Wind Harmer
20.909
970513AG2-328 GEN
Solar/Wind Harmer
5.915
970517AG2-330 GEN
Solar/Wind Harmer
35.487
270043AE2-236 GEN
Solar/Wind Harmer
8.538
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
10.397
274772LINCOLN ;3U
Adder
15.292
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
31.641
944531AF1-118 GEN
Solar/Wind Harmer
55.84
274752CRETE EC ;2U
Adder
14.685
274753CRETE EC ;3U
Adder
14.685
970031AG2-029 GEN
Solar/Wind Harmer
8.073
247604X1-042
Adder
0.74
970707AG2-453 GEN
Solar/Wind Harmer
40.394
274802UNIV PARK;5U
Adder
10.281
274826FISK ;BP
Adder
19.304
276806AD2-047 C O1
Solar/Wind Harmer
6.965
970941AG2-585 GEN
Solar/Wind Harmer
15.363
274800UNIV PARK;3U
Adder
10.269
972038AH1-567 GEN2
Adder
0.643
972228AH1-698 GEN2
Adder
6.522
276897AD1-100 C
Solar/Wind Harmer
0.016
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
51.668
274730ELWOOD EC;6P
Adder
28.626
274734ELWOOD EC;8P
Adder
28.626
274736ELWOOD EC;9P
Adder
28.626
274729ELWOOD EC;1P
Adder
28.625
276893AG1-478 C
Solar/Wind Harmer
0.481
943121AE2-341 GEN
Solar/Wind Harmer
20.258
943591AF1-030 GEN
Solar/Wind Harmer
13.472
270535AF1-215 GEN1
Solar/Wind Harmer
0.015
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
30.6
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.431
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.24
274855GSG-6 ;RU
Solar/Wind Harmer
0.426
274850MENDOTA H;RU
Solar/Wind Harmer
0.137
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.208
959331AF2-224 GEN
Solar/Wind Harmer
8.128
965021AG1-366 GEN
Solar/Wind Harmer
3.871
959091AF2-200 GEN
Solar/Wind Harmer
23.073
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.601
970571AG2-364 GEN
Solar/Wind Harmer
22.715
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
15.031
274767LEE CO EC;8U
Adder
14.854
276157O29GEN1
Solar/Wind Harmer
1.797
274878BISHOP HL;2U
Solar/Wind Harmer
0.37
270102X2-052 ST
50/50
2.992
270100X2-052 CT1
50/50
2.757
270101X2-052 CT2
50/50
2.757
247620Y3-023
50/50
0.89
970321AG2-212 GEN
Solar/Wind Harmer
5.915
270216AD2-079_GEN
Solar/Wind Harmer
0.002
965681AG1-436 GEN
Solar/Wind Harmer
16.197
965791AG1-447 GEN
Solar/Wind Harmer
11.878
270526AF1-158 GEN
Solar/Wind Harmer
0.016
24441505OLIV SLR
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
25.575
961051AF2-396 GEN
Solar/Wind Harmer
17.05
274770LINCOLN ;1U
Adder
15.292
274771LINCOLN ;2U
Adder
15.292
274808UNIV PK N;4U
Adder
8.838
972259AH1-714 GEN
Adder
33.646
274803UNIV PARK;6U
Adder
10.281
274888KELLY CRK;1U
Solar/Wind Harmer
0.722
274887GEN-1.85
Solar/Wind Harmer
0.324
276843GEN-1.7
Solar/Wind Harmer
0.398
958011AF2-095 GEN
Solar/Wind Harmer
17.698
274674JOLIET 9 ;6U
Adder
26.84
274847GR RIDGE ;BU
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
2.237
274695ROCKY RD ;2P
Adder
18.993
274693ROCKY RD ;1P
Adder
18.806
274697ROCKY RD ;3P
Adder
5.159
972227AH1-698 GEN1
Adder
4.592
274687WILL CNTY;4U
Adder
48.86
274687WILL CNTY;4U
Adder
48.86
274675JOLIET 29;7U
Adder
53.583
274675JOLIET 29;7U
Adder
51.669
274728ELWOOD EC;5P
Adder
28.626
274731ELWOOD EC;2P
Adder
28.625
274733ELWOOD EC;3P
Adder
28.625
274735ELWOOD EC;4P
Adder
28.625
24729505KEY G4
Adder
11.296
970833AG2-524 GEN
Solar/Wind Harmer
13.35
970833AG2-524 GEN
Solar/Wind Harmer
8.9
274746AC1-111 G10
Adder
9.659
274744AC1-111 GEN8
Adder
9.659
270536AF1-215 GEN2
Solar/Wind Harmer
0.015
971177AH1-047 GEN
Solar/Wind Harmer
7.198
276868AE1-113 GEN
Solar/Wind Harmer
2.341
276882AE2-255 GEN
Solar/Wind Harmer
1.364
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971675AH1-338 GEN
Solar/Wind Harmer
4.532
971411AH1-196 GEN
Solar/Wind Harmer
17.431
971549AH1-272 GEN
Solar/Wind Harmer
23.961
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
23.073
274823ROCKFORD ;21
Adder
32.096
971611AH1-305 GEN
Solar/Wind Harmer
6.79
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
1.931
970169AG2-114 GEN
Solar/Wind Harmer
11.331
971681AH1-341 GEN
Solar/Wind Harmer
18.233
961011AF2-392 GEN
Solar/Wind Harmer
6.56
957751AF2-069 GEN
Solar/Wind Harmer
0.366
965101AG1-375 GEN
Solar/Wind Harmer
11.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
11.407
941731AE2-173 GEN
Solar/Wind Harmer
9.053
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
946321AF1-296 GEN
Solar/Wind Harmer
6.04
945581AF1-223 GEN
Solar/Wind Harmer
0.001
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963791AG1-232 GEN
Solar/Wind Harmer
13.932
963841AG1-237 GEN
Solar/Wind Harmer
4.358
965041AG1-368 GEN
Solar/Wind Harmer
10.015
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.363
276848AB2-070 GEN3
Solar/Wind Harmer
0.361
970289AG2-191 GEN
Solar/Wind Harmer
1.856
971609AH1-304 GEN
Solar/Wind Harmer
1.589
270594AE1-207 GEN
Solar/Wind Harmer
10.691
965051AG1-369 GEN
Solar/Wind Harmer
4.577
270024AE2-089 GEN
Solar/Wind Harmer
0.01
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
3.587
944221AF1-090 GEN
Solar/Wind Harmer
5.246
270240V3-007_GEN2
Solar/Wind Harmer
0.002
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.91
270543AE2-219 C
Solar/Wind Harmer
0.004
971029AG2-637 GEN
Solar/Wind Harmer
9.925
971673AH1-337 GEN
Solar/Wind Harmer
4.175
942111AE2-223 GEN
Solar/Wind Harmer
3.531
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
10.846
965931AG1-462 GEN
Solar/Wind Harmer
27.328
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
31.938
959611AF2-252 GEN
Solar/Wind Harmer
3.549
247642Z2-115 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.599
276668AB2-070 GEN1
Solar/Wind Harmer
0.363
970289AG2-191 GEN
Solar/Wind Harmer
1.074
970291AG2-192 GEN
Solar/Wind Harmer
0.977
276621W2-048 GEN
Solar/Wind Harmer
0.492
276838X2-022 GEN2
Solar/Wind Harmer
0.549
942481AE2-261 GEN
Solar/Wind Harmer
27.997
958821AF2-173 GEN
Solar/Wind Harmer
12.883
270004AE1-209 GEN
Solar/Wind Harmer
1.994
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.059
971617AH1-308 GEN
Solar/Wind Harmer
7.545
946031AF1-268 GEN
Solar/Wind Harmer
8.268
970193AG2-126 GEN
Solar/Wind Harmer
13.029
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.308
270404AC1-167 GEN
Solar/Wind Harmer
0.003
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
8.781
24728505AND G1
Adder
4.198
970243AG2-164 GEN
Solar/Wind Harmer
4.208
970519AG2-331 GEN
Solar/Wind Harmer
18.702
970699AG2-449 GEN
Solar/Wind Harmer
1.798
270491AE1-102 GEN2
Solar/Wind Harmer
0.934
270356AE2-297 GEN
Solar/Wind Harmer
0.009
274696ROCKY RD ;4P
Adder
19.441
958481AF2-142 GEN
Solar/Wind Harmer
17.825
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.607
274683WAUKEGAN ;8U
Adder
35.828
274683WAUKEGAN ;8U
Adder
30.201
962691AG1-118 GEN
Solar/Wind Harmer
35.425
970921AG2-575 GEN
Solar/Wind Harmer
11.776
970921AG2-575 GEN
Solar/Wind Harmer
3.925
958491AF2-143 GEN
Solar/Wind Harmer
17.589
942991AE2-321 GEN
Solar/Wind Harmer
13.041
274879MINONK ;1U
Solar/Wind Harmer
0.492
970611AG2-400 GEN
Solar/Wind Harmer
11.612
970627AG2-408 GEN
Solar/Wind Harmer
3.484
971333AH1-146 GEN
Solar/Wind Harmer
23.223
971335AH1-147 GEN
Solar/Wind Harmer
23.223
971341AH1-150 GEN
Solar/Wind Harmer
23.073
971343AH1-151 GEN
Solar/Wind Harmer
23.073
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.269
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.415
944541AF1-119 GEN
Solar/Wind Harmer
0.756
960971AF2-388 GEN
Solar/Wind Harmer
6.621
274764LEE CO EC;5U
Adder
15.066
274765LEE CO EC;6U
Adder
15.066
274762LEE CO EC;3U
Adder
15.031
274763LEE CO EC;4U
Adder
14.889
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
6.653
276741O09 GEN1
Solar/Wind Harmer
0.396
276708O09 GEN2
Solar/Wind Harmer
0.396
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.436
276646AC1-214 GEN2
Solar/Wind Harmer
0.436
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.549
942221AE2-234 GEN
Solar/Wind Harmer
0.052
966841AG1-555 GEN
Solar/Wind Harmer
1.176
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
5.684
270599AE1-208 GEN
Solar/Wind Harmer
8.918
270031AE2-169
Solar/Wind Harmer
5.351
971613AH1-306 GEN
Solar/Wind Harmer
4.582
276916AD2-100_GEN
Solar/Wind Harmer
19.464
276911AD2-131_GEN
Solar/Wind Harmer
1.282
960441AF2-335 GEN
Solar/Wind Harmer
8.968
970825AG2-519 GEN
Solar/Wind Harmer
9.877
945391AF1-204 GEN
Solar/Wind Harmer
9.229
964611AG1-324 GEN
Solar/Wind Harmer
0.623
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.274
970623AG2-406 GEN
Solar/Wind Harmer
1.433
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.417
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.798
246938BC-WTG3
Solar/Wind Harmer
0.26
246937BC-WTG2
Solar/Wind Harmer
0.291
970883AG2-550 GEN
Solar/Wind Harmer
7.146
970885AG2-551 GEN
Solar/Wind Harmer
2.382
270471AD2-092_GEN
Solar/Wind Helper
1.564
24344105CKG2
50/50
15.732
270143AC1-141 CT2_
50/50
4.479
24639705ELKHART HY
50/50
0.3
970521AG2-332 GEN
50/50
21.293
24307105BERRINSP G
50/50
0.04
970245AG2-165 GEN
Solar/Wind Harmer
5.915
270505AE1-170 C O1
Solar/Wind Harmer
13.553
945111AF1-176 GEN
Solar/Wind Harmer
22.888
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
6.663
274773LINCOLN ;4U
Adder
15.292
274774LINCOLN ;5U
Adder
15.292
270063AE2-323 C
Solar/Wind Harmer
0.01
274723RIVER EC ;12
Adder
32.009
274751CRETE EC ;1U
Adder
14.685
274754CRETE EC ;4U
Adder
14.685
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
8.876
970373AG2-245 GEN
Solar/Wind Harmer
25.833
276776AD2-060 GEN
Solar/Wind Harmer
1.283
274801UNIV PARK;4U
Adder
10.269
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
53.582
274674JOLIET 9 ;6U
Adder
26.84
274732ELWOOD EC;7P
Adder
28.626
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
9.659
270055AF2-134 C O1
Solar/Wind Harmer
0.009
276691AA1-018 GEN1
Solar/Wind Harmer
1.44
274682WAUKEGAN ;7U
Adder
30.6
274828WAUKEGAN ;BP
Adder
18.78
962781AG1-127 GEN
Solar/Wind Harmer
11.207
958381AF2-132 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.007
939401AE1-172 GEN
Solar/Wind Harmer
8.779
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
15.25
276901AD2-066 C O1
Solar/Wind Harmer
0.012
971997AH1-543 GEN
Solar/Wind Harmer
6.112
276861AD2-134 GEN
Solar/Wind Harmer
0.208
965011AG1-365 GEN
Solar/Wind Harmer
11.612
957471AF2-041 GEN
Solar/Wind Harmer
34.609
959081AF2-199 GEN
Solar/Wind Harmer
11.536
971067AG2-660 GEN
Solar/Wind Harmer
3.845
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
32.33
972235AH1-702 GEN1
Adder
4.141
970819AG2-516 GEN
Solar/Wind Harmer
13.704
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
14.256
971475AH1-234 GEN
Solar/Wind Harmer
5.525
970569AG2-363 GEN
Solar/Wind Harmer
34.072
965651AG1-433 GEN
Solar/Wind Harmer
3.31
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
15.031
274766LEE CO EC;7U
Adder
14.854
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.37
958861AF2-177 GEN
Solar/Wind Harmer
4.768
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
15.209
24791305MDL-5G
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
945371AF1-202 GEN
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
944231AF1-091 GEN
Solar/Wind Harmer
2.757
972175AH1-670 GEN
Solar/Wind Harmer
8.498
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
3.857
970291AG2-192 GEN
Solar/Wind Harmer
1.27
276615X2-022 GEN
Solar/Wind Harmer
0.102
963741AG1-226 GEN
Solar/Wind Harmer
23.062
270032AE2-172
Solar/Wind Harmer
6.364
965911AG1-460 GEN
Solar/Wind Harmer
1.873
276903AD2-071 C
Solar/Wind Harmer
10.292
270005AE1-210 C O1
Solar/Wind Harmer
1.994
965031AG1-367 GEN
Solar/Wind Harmer
9.202
247521TR3_G114
Solar/Wind Harmer
0.334
270246TR4_N_V150
Solar/Wind Harmer
0.059
24695305TIMB G C
Solar/Wind Harmer
0.002
970825AG2-519 GEN
Solar/Wind Harmer
3.164
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.065
24728605AND G2
Adder
4.198
247536S-71 GEN
Solar/Wind Harmer
0.307
965421AG1-410 GEN
Solar/Wind Harmer
22.83
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
970333AG2-219 GEN
Solar/Wind Harmer
5.143
246936BC-WTG1
Solar/Wind Harmer
0.291
270489AE1-102 GEN1
Solar/Wind Harmer
0.934
970773AG2-487 GEN
Solar/Wind Harmer
1.226
270349AD2-093_GEN
Solar/Wind Helper
1.564
944201AF1-088_MTX
Adder
123.107
957141AF2-008_MTX
Adder
33.614
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.3
CBM West 1LTFEXP_CBM-W1->PJM
CBM
190.688
CBM South 1LTFEXP_CBM-S1->PJM
CBM
18.117
MECLTFEXP_MEC->PJM
CLTF
22.614
SIGELTFEXP_SIGE->PJM
CLTF
0.431
CBM West 2LTFEXP_CBM-W2->PJM
CBM
109.586
LAGNLTFEXP_LAGN->PJM
CLTF
12.118
TVALTFEXP_TVA->PJM
CLTF
4.605
NYPJM->LTFIMP_NY
CLTF
2.955
LGEELTFEXP_LGEE->PJM
CLTF
4
WECLTFEXP_WEC->PJM
CLTF
6.262
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.805
AG2-052LTFEXP_AG2-052->PJM
LTF
0.392
AH1-155LTFEXP_AH1-155->PJM
LTF
0.587

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#17217_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17217_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:115.67 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6388.32
MW Contribution:9.35
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.756
972203AH1-686 GEN
Adder
4.425
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
3.805
270400AC1-102 GEN
Solar/Wind Harmer
3.805
962771AG1-126 GEN
Solar/Wind Harmer
46.194
24477305BRIDGE
Adder
0.588
970281AG2-184 GEN
Solar/Wind Harmer
22.926
972143AH1-644 GEN
Solar/Wind Harmer
11.827
971985AH1-537 GEN
Solar/Wind Harmer
3.245
941621AE2-160 GEN
Adder
5.057
971313AH1-133 GEN
Solar/Wind Harmer
10.378
270367AC2-061_GEN
Solar/Wind Harmer
0.008
970879AG2-548 GEN
Solar/Wind Harmer
9.191
972163AH1-664 GEN
Solar/Wind Harmer
11.344
972165AH1-665 GEN
Solar/Wind Harmer
9.085
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
25196108MFTGT2
Adder
2.193
25196108MFTGT2
Adder
2.036
3429211JKCT 2G
Adder
16.676
252524AE2-267 GEN
Solar/Wind Harmer
0.004
25196408WSDLE3
Adder
12.579
25196308WSDLE2
Adder
12.47
25196208WSDLE1
Adder
12.439
25196708WSDLE6
Adder
12.407
25196508WSDLE4
Adder
12.095
24734705WLF1G3
Adder
8.198
24734805WLF1G4
Adder
8.198
24734905WLF1G5
Adder
8.198
270340AC2-060 GEN
Solar/Wind Harmer
0.011
270132AB1-180 C
Adder
0.17
339211AE2-254 GEN
Solar/Wind Harmer
0.004
24735105WLF2G1
Adder
8.08
970455AG2-298 GEN
Solar/Wind Harmer
6.495
965401AG1-405 GEN
Solar/Wind Harmer
5.522
965411AG1-406 GEN
Solar/Wind Harmer
3.552
270269AC2-059
Solar/Wind Harmer
0.006
971061AG2-657 GEN
Solar/Wind Harmer
6.031
270240V3-007_GEN2
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
2.585
253372AE2-315 SEC3
Adder
2.585
25306009OHH W.
Adder
3.927
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.978
253400AC2-068 GEN
Solar/Wind Harmer
1.198
970289AG2-191 GEN
Solar/Wind Harmer
1.794
270594AE1-207 GEN
Solar/Wind Harmer
10.572
963841AG1-237 GEN
Solar/Wind Harmer
4.089
970115AG2-085 GEN
Solar/Wind Harmer
3.766
971673AH1-337 GEN
Solar/Wind Harmer
6.118
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
24289405MTG1
50/50
11.351
24318705GVG2
50/50
11.615
24722005FLATG5
50/50
2.756
24721905FLATG4
50/50
50.519
24686205CER G4
Adder
15.547
24686405CER G5
Adder
15.485
270053AF1-130 C
Solar/Wind Harmer
2.748
970153AG2-106 GEN
Solar/Wind Harmer
29.498
971191AH1-055 GEN
Solar/Wind Harmer
30.005
970913AG2-568 GEN
Solar/Wind Harmer
8.769
972103AH1-617 GEN
Solar/Wind Harmer
21.835
960911AF2-382 GEN
Solar/Wind Harmer
8.035
971461AH1-227 GEN
Solar/Wind Harmer
5.464
970243AG2-164 GEN
Solar/Wind Harmer
6.06
970519AG2-331 GEN
Solar/Wind Harmer
26.931
970699AG2-449 GEN
Solar/Wind Harmer
2.59
972167AH1-666 GEN
Solar/Wind Harmer
8.145
958171AF2-111 GEN
Solar/Wind Harmer
25.128
252510AF1-249 C
Solar/Wind Harmer
0.077
25196008MFTGT1
Adder
1.926
25194608D.CRK4
Adder
2.348
25196608WSDLE5
Adder
12.22
3429391JKCT 9G
Adder
11.865
970093AG2-073 GEN
Solar/Wind Harmer
9.929
253316AC1-085 GEN3
Solar/Wind Harmer
0.006
253433AC1-085 GEN1
Solar/Wind Harmer
0.005
946181AF1-283 GEN
Solar/Wind Harmer
12.875
253406AD2-031_GEN
Solar/Wind Harmer
0.735
966571AG1-526 GEN
Solar/Wind Harmer
21.864
270291AC1-194 GEN
Solar/Wind Harmer
7.771
253415AE1-040 GEN
Solar/Wind Harmer
0.004
972173AH1-669 GEN
Solar/Wind Harmer
4.843
270222AC2-111 GEN
Solar/Wind Harmer
4.893
972273AH1-721 GEN
Adder
114.731
270273AD2-016 GEN
Solar/Wind Harmer
0.998
270356AE2-297 GEN
Solar/Wind Harmer
0.013
24728705AND G3
Adder
11.022
24728505AND G1
Adder
5.27
970193AG2-126 GEN
Solar/Wind Harmer
14.303
270437AC2-090 C
Solar/Wind Harmer
0.004
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
270346AE1-212 GEN
Solar/Wind Harmer
8.4
970273AG2-179 GEN
Solar/Wind Harmer
5.694
960741AF2-365 GEN
Solar/Wind Harmer
4.731
970191AG2-125 GEN
Solar/Wind Harmer
2.433
247642Z2-115 C
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.039
970291AG2-192 GEN
Solar/Wind Harmer
0.944
958821AF2-173 GEN
Solar/Wind Harmer
13.219
270004AE1-209 GEN
Solar/Wind Harmer
2.046
946031AF1-268 GEN
Solar/Wind Harmer
8.936
339250AF1-203 GEN
Solar/Wind Harmer
0.001
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
9.369
971155AH1-034 GEN
Solar/Wind Harmer
10.922
970513AG2-328 GEN
Solar/Wind Harmer
4.056
970517AG2-330 GEN
Solar/Wind Harmer
24.338
962251AG1-071 GEN
Solar/Wind Harmer
5.847
942481AE2-261 GEN
Solar/Wind Harmer
27.825
276621W2-048 GEN
Solar/Wind Harmer
0.469
276838X2-022 GEN2
Solar/Wind Harmer
0.523
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.291
276668AB2-070 GEN1
Solar/Wind Harmer
0.339
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
943031AE2-326 GEN
Solar/Wind Harmer
4.828
274853TWINGROVE;U1
Solar/Wind Harmer
0.004
965091AG1-374 GEN
Solar/Wind Harmer
27.736
959611AF2-252 GEN
Solar/Wind Harmer
3.082
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.864
942111AE2-223 GEN
Solar/Wind Harmer
3.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
944531AF1-118 GEN
Solar/Wind Harmer
41.286
270535AF1-215 GEN1
Solar/Wind Harmer
0.011
274878BISHOP HL;2U
Solar/Wind Harmer
0.308
253338AC1-165 GEN
Solar/Wind Harmer
0.004
253333AC1-068 GEN
Solar/Wind Harmer
0.014
970571AG2-364 GEN
Solar/Wind Harmer
18.307
276889AE2-281 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.012
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274772LINCOLN ;3U
Adder
11.055
276805AD2-038 GEN
Solar/Wind Harmer
0.003
276157O29GEN1
Solar/Wind Harmer
1.478
970707AG2-453 GEN
Solar/Wind Harmer
29.848
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
943121AE2-341 GEN
Solar/Wind Harmer
15.314
943591AF1-030 GEN
Solar/Wind Harmer
10.184
274855GSG-6 ;RU
Solar/Wind Harmer
0.335
274850MENDOTA H;RU
Solar/Wind Harmer
0.108
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.164
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.974
274760LEE CO EC;1U
Adder
12.175
274767LEE CO EC;8U
Adder
12.032
274729ELWOOD EC;1P
Adder
21.509
237048AF1-022 C
Solar/Wind Helper
0.228
237043AE2-125 C
Solar/Wind Helper
0.207
235058AG1-386 C
Solar/Wind Helper
0.514
964991AG1-363 GEN
Solar/Wind Helper
4.415
23750701CROSSCHOOL
Solar/Wind Helper
1.427
238118U2-030_1
Solar/Wind Helper
0.343
202652Y1-033 WT C
Solar/Wind Helper
0.655
20089126CSLMN_L13
Solar/Wind Helper
0.683
20089026BF_G21_K23
Solar/Wind Helper
0.541
238127S14_GEN_2
Solar/Wind Helper
0.81
254305AE2-115 C
Solar/Wind Helper
0.239
203818AF1-086 GEN
Solar/Wind Helper
1.887
203854AF2-039 C
Solar/Wind Helper
0.354
20334926Z1-069 C
Solar/Wind Helper
1.49
238202AE2-262_GEN
Solar/Wind Helper
1.063
941421AE2-139 GEN
Solar/Wind Helper
2.573
959441AF2-235 GEN
Solar/Wind Helper
0.255
200917MEHOOPANY_G
Solar/Wind Helper
2.428
209071AE2-133 GEN
Solar/Wind Helper
0.09
946731AF1-337 GEN
Solar/Wind Helper
0.5
212507AE2-042_GEN
Solar/Wind Helper
1.772
961341AF2-425 GEN
Solar/Wind Helper
0.499
212266LOR1
Solar/Wind Helper
0.054
961301AF2-421 GEN
Solar/Wind Helper
0.496
24289405MTG1
50/50
11.351
243186AF1-051 GEN
50/50
12.478
24318705GVG2
50/50
11.615
24721805FLATG3
50/50
2.756
24721705FLATG2
50/50
50.519
24723205RIVRG3
Adder
36.021
24686105CER G3
Adder
15.629
24686505CER G6
Adder
15.608
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.412
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
971403AH1-188 GEN
Solar/Wind Harmer
16.785
962761AG1-125 GEN
Solar/Wind Harmer
46.194
970149AG2-104 GEN
Solar/Wind Harmer
49.891
970155AG2-107 GEN
Solar/Wind Harmer
29.498
971315AH1-136 GEN
Solar/Wind Harmer
2.232
927014AC1-188 GEN
Solar/Wind Harmer
0.007
971687AH1-348 GEN
Solar/Wind Harmer
1.067
24728305BUCHG2
Adder
6.831
970333AG2-219 GEN
Solar/Wind Harmer
7.406
970091AG2-072 GEN
Adder
113.581
945681AF1-233 GEN
Solar/Wind Harmer
19.197
252507AC2-088 GEN
Solar/Wind Harmer
0.46
25196808ZIMRHP
Adder
109.116
339216AC1-074 GEN
Solar/Wind Harmer
0.274
25196008MFTGT1
Adder
1.989
25194608D.CRK4
Adder
2.348
3429241JKCT 3G
Adder
16.894
3429421JKCT 10G
Adder
11.865
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
9.904
270263AC1-001 GEN
Solar/Wind Harmer
0.987
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
971565AH1-281 GEN
Solar/Wind Harmer
1.958
971821AH1-427 GEN
Solar/Wind Harmer
9.786
971029AG2-637 GEN
Solar/Wind Harmer
14.095
24690905MDL-1G C
Solar/Wind Harmer
0.003
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
945581AF1-223 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.006
971609AH1-304 GEN
Solar/Wind Harmer
1.526
270432AC2-029 GEN
Solar/Wind Harmer
4.141
944221AF1-090 GEN
Solar/Wind Harmer
5.475
965101AG1-375 GEN
Solar/Wind Harmer
9.315
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.339
276848AB2-070 GEN3
Solar/Wind Harmer
0.337
971611AH1-305 GEN
Solar/Wind Harmer
5.525
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.004
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
9.696
24729505KEY G4
Adder
8.586
941731AE2-173 GEN
Solar/Wind Harmer
7.695
966391AG1-508 GEN
Solar/Wind Harmer
1.427
970169AG2-114 GEN
Solar/Wind Harmer
9.2
274863CRW1-WTG
Solar/Wind Harmer
0.003
274864CRW2-WTG
Solar/Wind Harmer
0.003
241972AD1-140 GEN
Solar/Wind Harmer
1.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
957751AF2-069 GEN
Solar/Wind Harmer
0.302
243186AF1-051 GEN
50/50
12.478
24723005RIVRG1
Adder
36.021
24723105RIVRG2
Adder
36.021
24685805CER G1
Adder
15.526
24685905CER G2
Adder
15.526
944971AF1-162 GEN
Solar/Wind Harmer
12.174
971225AH1-072 GEN
Solar/Wind Harmer
2.13
971227AH1-073 GEN
Solar/Wind Harmer
2.13
24728205BUCHG1
Adder
6.831
970239AG2-162 GEN
Solar/Wind Harmer
2.59
270186AC1-089 GEN
Solar/Wind Harmer
0.006
962581AG1-107 GEN
Solar/Wind Harmer
0.002
960161AF2-307 GEN
Solar/Wind Harmer
6.771
971073AG2-665 GEN
Solar/Wind Harmer
9.191
252509AD1-136 GEN
Solar/Wind Harmer
0.051
339221AD2-048_GEN
Solar/Wind Harmer
0.006
972043AH1-570 GEN
Solar/Wind Harmer
2.614
972045AH1-571 GEN
Solar/Wind Harmer
2.094
25183208HLCRTG
Solar/Wind Harmer
0.016
252519AF1-045_GEN
Solar/Wind Harmer
8.714
252516AE2-318_GEN
Solar/Wind Harmer
7.729
970235AG2-159 GEN
Solar/Wind Harmer
6.108
970235AG2-159 GEN
Solar/Wind Harmer
3.504
971125AH1-004 GEN
Solar/Wind Harmer
3.992
970107AG2-081 GEN
Solar/Wind Harmer
2.994
25194408D.CRK1
Adder
10.799
25194508D.CRK3
Adder
2.019
942891AE2-308 GEN
Solar/Wind Harmer
9.954
253317AC1-085 GEN4
Solar/Wind Harmer
0.006
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.197
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
964571AG1-320 GEN
Solar/Wind Harmer
8.854
970653AG2-424 GEN
Solar/Wind Harmer
4.654
970653AG2-424 GEN
Solar/Wind Harmer
2.412
24728805RICHG1
Adder
5.204
24728905RICHG2
Adder
5.204
971081AG2-670 GEN
Solar/Wind Harmer
7.154
945391AF1-204 GEN
Solar/Wind Harmer
10.131
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
253370AE2-315 SEC1
Adder
2.733
270383AD1-128 GEN
Solar/Wind Harmer
0.006
970241AG2-163 GEN
Solar/Wind Harmer
5.517
971613AH1-306 GEN
Solar/Wind Harmer
4.531
25322209TAIT E
Adder
13.187
25322209TAIT E
Adder
12.891
970825AG2-519 GEN
Solar/Wind Harmer
10.439
960441AF2-335 GEN
Solar/Wind Harmer
9.416
966841AG1-555 GEN
Solar/Wind Harmer
1.065
339255AE2-071 GEN
Solar/Wind Harmer
-0.154
970321AG2-212 GEN
Solar/Wind Harmer
4.056
971485AH1-239 GEN
Solar/Wind Harmer
7.489
964781AG1-341 GEN
Solar/Wind Harmer
9.922
966021AG1-471 GEN
Solar/Wind Harmer
5.054
25326109MON D
Adder
1.763
970883AG2-550 GEN
Solar/Wind Harmer
9.347
970885AG2-551 GEN
Solar/Wind Harmer
3.116
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
270599AE1-208 GEN
Solar/Wind Harmer
8.564
270031AE2-169
Solar/Wind Harmer
5.138
276916AD2-100_GEN
Solar/Wind Harmer
19.555
276911AD2-131_GEN
Solar/Wind Harmer
1.288
944541AF1-119 GEN
Solar/Wind Harmer
0.623
960971AF2-388 GEN
Solar/Wind Harmer
5.453
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.696
247621Y3-024
Adder
0.32
960611AF2-352 GEN
Solar/Wind Harmer
3.082
270201AC2-176 GEN
Solar/Wind Harmer
0.002
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.36
276646AC1-214 GEN2
Solar/Wind Harmer
0.36
276782AC1-033 GEN
Solar/Wind Harmer
0.001
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
274879MINONK ;1U
Solar/Wind Harmer
0.386
274770LINCOLN ;1U
Adder
11.055
274771LINCOLN ;2U
Adder
11.055
276741O09 GEN1
Solar/Wind Harmer
0.325
276708O09 GEN2
Solar/Wind Harmer
0.325
958491AF2-143 GEN
Solar/Wind Harmer
13.709
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1.236
972259AH1-714 GEN
Adder
24.976
958481AF2-142 GEN
Solar/Wind Harmer
13.701
971573AH1-285 GEN
Solar/Wind Harmer
1.702
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
5.45
274696ROCKY RD ;4P
Adder
14.914
274695ROCKY RD ;2P
Adder
14.57
274693ROCKY RD ;1P
Adder
14.427
274764LEE CO EC;5U
Adder
12.204
274765LEE CO EC;6U
Adder
12.204
274762LEE CO EC;3U
Adder
12.175
274763LEE CO EC;4U
Adder
12.06
274697ROCKY RD ;3P
Adder
3.958
23652301WDPWR_K20
Solar/Wind Helper
0.168
23585401KL_K28_T16
Solar/Wind Helper
1.53
203955AF1-039 C O1
Solar/Wind Helper
0.432
944781AF1-143 GEN
Solar/Wind Helper
2.836
238120AE2-309 GEN
Solar/Wind Helper
0.507
962101AG1-054 GEN
Solar/Wind Helper
0.715
20083426SW_E13_K22
Solar/Wind Helper
0.064
241985AE1-237 GEN
Solar/Wind Helper
0.271
241967AE2-285_GEN
Solar/Wind Helper
0.696
241801AE1-079 GEN
Solar/Wind Helper
0.271
20088926STNY CRK
Solar/Wind Helper
0.928
946071AF1-272 GEN
Solar/Wind Helper
3.051
20084626FORWARD
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.446
20088626ARWF_N39
Solar/Wind Helper
1.362
20303426NA_O38_P22
Solar/Wind Helper
1.117
203853AF1-134 C O1
Solar/Wind Helper
0.534
946381AF1-302 GEN
Solar/Wind Helper
0.246
203952AE2-129 C
Solar/Wind Helper
0.529
203946AE2-131 C
Solar/Wind Helper
0.53
238217AF1-153 C O1
Solar/Wind Helper
0.262
20398826ARMNA MT
Solar/Wind Helper
1.656
209137AF2-361 C
Solar/Wind Helper
1.531
946751AF1-339 GEN
Solar/Wind Helper
0.5
209054AE2-059 GEN
Solar/Wind Helper
0.09
961431AF2-434 GEN
Solar/Wind Helper
0.499
208972BECR K09
Solar/Wind Helper
0.372
209029WAYMART-WD
Solar/Wind Helper
0.937
203979AG1-198 GEN
Solar/Wind Helper
0.297
211065PSPA IPP
Solar/Wind Helper
0.168
211065PSPA IPP
Solar/Wind Helper
0.168
203980AG1-197 GEN
Solar/Wind Helper
0.369
966111AG1-480 GEN
Solar/Wind Helper
0.082
20674128FR_U2-059
Solar/Wind Helper
0.004
964851AG1-348 GEN
Solar/Wind Helper
0.088
207471AF2-354 C
Solar/Wind Helper
0.184
20674928WA_W3-044
Solar/Wind Helper
0.107
20676228FRD_X1-012
Solar/Wind Helper
0.1
217204WCALDSOLAR C
Solar/Wind Helper
0.003
217201HACKENSOLA C
Solar/Wind Helper
0.003
217206BARNGR HS C
Solar/Wind Helper
0.007
217202FBANKSOLAR C
Solar/Wind Helper
0.003
217081WEATEXAS C
Solar/Wind Helper
0.014
20671828STAW2-080
Solar/Wind Helper
0.029
207442AE1-156 GEN
Solar/Wind Helper
0.351
20676128MHD_W3-029
Solar/Wind Helper
0.103
20673828FLE_V3-070
Solar/Wind Helper
0.097
218440SUMMTASSOC C
Solar/Wind Helper
0.018
20716928W4-060COL
Solar/Wind Helper
0.055
20720628TIN_W1-124
Solar/Wind Helper
0.203
963391AG1-188 GEN
Solar/Wind Helper
0.088
20714928UPF_X1-085
Solar/Wind Helper
0.005
963401AG1-189 GEN
Solar/Wind Helper
0.06
20390526W1-045 C
Solar/Wind Helper
0.357
219615MILLCREEK C
Solar/Wind Helper
0.028
219921AF1-264
Solar/Wind Helper
0.054
203947AF1-006 C
Solar/Wind Helper
0.527
230407AD2-065 C
Solar/Wind Helper
0.042
230433AD2-135 GEN
Solar/Wind Helper
0.018
233939AC1-091 C
Solar/Wind Helper
0.361
233970AC1-092 C
Solar/Wind Helper
0.361
233901CHERRYDALE C
Solar/Wind Helper
0.24
232408W1-005 C
Solar/Wind Helper
0.523
232410W1-006 C
Solar/Wind Helper
0.523
233946AB2-136 GEN
Solar/Wind Helper
0.586
234036AF2-325 C
Solar/Wind Helper
0.043
233987AB2-037 GEN
Solar/Wind Helper
2.415
233944AB2-135 GEN
Solar/Wind Helper
0.607
232424Y1-079 C
Solar/Wind Helper
0.12
233933AB2-153 GEN
Solar/Wind Helper
0.24
235063AE1-101 C2
Solar/Wind Helper
1.463
205916AD1-020 GEN
Solar/Wind Helper
1.711
237002AB1-128_GEN
Solar/Wind Helper
0.388
237001AB1-127_GEN
Solar/Wind Helper
0.388
235020AA1-095 C
Solar/Wind Helper
0.045
23777901MDS_W4-102
Solar/Wind Helper
0.15
208835TUHI V3-051
Solar/Wind Helper
0.024
208835TUHI V3-051
Solar/Wind Helper
0.024
237034AC2-136 C
Solar/Wind Helper
0.194
238175AF1-290_GEN
Solar/Wind Helper
0.123
237025AB1-124 C
Solar/Wind Helper
0.145
237006AB1-125 GEN
Solar/Wind Helper
0.109
23777801MSM_W1-116
Solar/Wind Helper
0.1
238169AE2-226 GEN1
Solar/Wind Helper
0.555
238170AE2-226 GEN2
Solar/Wind Helper
0.555
971341AH1-150 GEN
Solar/Wind Harmer
3.998
971343AH1-151 GEN
Solar/Wind Harmer
3.998
270536AF1-215 GEN2
Solar/Wind Harmer
0.011
926823AC1-168 GEN
Solar/Wind Harmer
1.557
276868AE1-113 GEN
Solar/Wind Harmer
1.835
276882AE2-255 GEN
Solar/Wind Harmer
1.069
274775LINCOLN ;6U
Adder
11.055
274776LINCOLN ;7U
Adder
11.055
274777LINCOLN ;8U
Adder
11.055
970833AG2-524 GEN
Solar/Wind Harmer
10.052
970833AG2-524 GEN
Solar/Wind Harmer
6.701
274746AC1-111 G10
Adder
7.316
274744AC1-111 GEN8
Adder
7.316
961011AF2-392 GEN
Solar/Wind Harmer
5.358
971675AH1-338 GEN
Solar/Wind Harmer
3.562
274731ELWOOD EC;2P
Adder
21.509
274733ELWOOD EC;3P
Adder
13.442
23750501ELLIOTTS
Solar/Wind Helper
0.788
238126S14_GEN_1
Solar/Wind Helper
0.81
254304AE2-114 C
Solar/Wind Helper
0.239
241997AF1-093 GEN
Solar/Wind Helper
0.28
241982AE2-343 S C
Solar/Wind Helper
0.243
20092526R32
Solar/Wind Helper
1.311
203961AE2-224 GEN
Solar/Wind Helper
2.707
20091526CHSTN_FL
Solar/Wind Helper
0.654
238109AE1-109 GEN2
Solar/Wind Helper
0.102
238110AE1-109 GEN3
Solar/Wind Helper
0.102
20090526Q36
Solar/Wind Helper
1.167
203993AD2-133_GEN1
Solar/Wind Helper
1.167
941231AE2-117 GEN
Solar/Wind Helper
0.53
203846AF2-130 C
Solar/Wind Helper
0.497
203855AF2-088 C
Solar/Wind Helper
0.17
203804AE2-113_GEN
Solar/Wind Helper
1.924
959431AF2-234 GEN
Solar/Wind Helper
1
964051AG1-259 GEN
Solar/Wind Helper
0.075
964061AG1-260 GEN
Solar/Wind Helper
0.075
959421AF2-233 GEN
Solar/Wind Helper
0.5
961261AF2-417 GEN
Solar/Wind Helper
0.495
209116AE2-175 GEN
Solar/Wind Helper
1.966
20675128HRM_W1-127
Solar/Wind Helper
0.032
207408W3-077 C
Solar/Wind Helper
0.092
20675728RH_W2-091
Solar/Wind Helper
0.149
207484AF2-139 C O1
Solar/Wind Helper
0.092
203975AE1-071-GEN
Solar/Wind Helper
2.674
20674828DL_W4-046
Solar/Wind Helper
0.008
20675928HOL_W4-097
Solar/Wind Helper
0.055
20676328BVR_Y1-020
Solar/Wind Helper
0.029
238208AF1-136 C
Solar/Wind Helper
0.192
207530AG1-191 GEN
Solar/Wind Helper
0.072
966261AG1-495 GEN
Solar/Wind Helper
0.088
218524CNTRALGAS1 C
Solar/Wind Helper
0.173
20675528CPH_W2-050
Solar/Wind Helper
0.093
218526CNTRALGAS2 C
Solar/Wind Helper
0.173
219620RIDERU C
Solar/Wind Helper
0.001
207459AE1-142 C O1
Solar/Wind Helper
0.309
20715728PEM_W1-119
Solar/Wind Helper
0.102
20715828PEM_W1-120
Solar/Wind Helper
0.102
214067T20SOLAR
Solar/Wind Helper
0.012
959381AF2-229 GEN
Solar/Wind Helper
0.364
219607WPEMNERT C
Solar/Wind Helper
0.085
219688LUMSOLAR_S C
Solar/Wind Helper
0.042
219272CLEANLIGHT C
Solar/Wind Helper
0.027
219914AD2-027 C
Solar/Wind Helper
0.121
227927V4-067C
Solar/Wind Helper
0.011
228754AB1-001 C
Solar/Wind Helper
0.027
964001AG1-254 GEN
Solar/Wind Helper
1.003
234033AF1-007_GEN
Solar/Wind Helper
7.245
233923SMA
Solar/Wind Helper
0.989
233990AG1-397 GEN
Solar/Wind Helper
0.279
232432Z2-076 GEN
Solar/Wind Helper
0.069
237085AD2-009_GEN
Solar/Wind Helper
1.449
24735205WLF2G2
Adder
8.08
970773AG2-487 GEN
Solar/Wind Harmer
1.7
24728605AND G2
Adder
5.27
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.984
253370AE2-315 SEC1
Adder
2.733
253371AE2-315 SEC2
Adder
2.585
970273AG2-179 GEN
Solar/Wind Harmer
3.322
276903AD2-071 C
Solar/Wind Harmer
10.574
963741AG1-226 GEN
Solar/Wind Harmer
22.385
970291AG2-192 GEN
Solar/Wind Harmer
1.228
270005AE1-210 C O1
Solar/Wind Harmer
2.046
965031AG1-367 GEN
Solar/Wind Harmer
9.442
270032AE2-172
Solar/Wind Harmer
6.293
25326309TAIT D
Adder
1.481
964901AG1-354 GEN
Solar/Wind Harmer
14.138
960071AF2-298 GEN
Solar/Wind Harmer
4.694
970825AG2-519 GEN
Solar/Wind Harmer
3.343
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.004
24791305MDL-5G
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
4.056
962241AG1-070 GEN
Solar/Wind Harmer
5.098
945371AF1-202 GEN
Solar/Wind Harmer
0.001
958861AF2-177 GEN
Solar/Wind Harmer
4.037
965911AG1-460 GEN
Solar/Wind Harmer
1.861
247536S-71 GEN
Solar/Wind Harmer
0.374
965651AG1-433 GEN
Solar/Wind Harmer
2.727
276615X2-022 GEN
Solar/Wind Harmer
0.098
963831AG1-236 GEN
Solar/Wind Harmer
3.623
274880W4-005 GEN4
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
11.601
972175AH1-670 GEN
Solar/Wind Harmer
7.662
274854TWINGROVE;U2
Solar/Wind Harmer
0.004
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
12.928
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
11.983
958381AF2-132 GEN
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
6.864
270055AF2-134 C O1
Solar/Wind Harmer
0.007
274877BISHOP HL;1U
Solar/Wind Harmer
0.308
253343AC1-166 GEN
Solar/Wind Harmer
0.004
253325AC1-069 GEN
Solar/Wind Harmer
0.014
970569AG2-363 GEN
Solar/Wind Harmer
27.46
971997AH1-543 GEN
Solar/Wind Harmer
4.802
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276901AD2-066 C O1
Solar/Wind Harmer
0.009
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274773LINCOLN ;4U
Adder
11.055
274774LINCOLN ;5U
Adder
11.055
276158O29GEN2
Solar/Wind Harmer
0.001
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
1.106
274745AC1-111 GEN9
Adder
7.316
276861AD2-134 GEN
Solar/Wind Harmer
0.164
274872LEEDK;1U
Solar/Wind Harmer
0.006
274761LEE CO EC;2U
Adder
12.175
274766LEE CO EC;7U
Adder
12.032
237046AF1-021 C
Solar/Wind Helper
0.577
238185AF2-356 C
Solar/Wind Helper
2.612
23751201ROTHROCK
Solar/Wind Helper
0.878
235054AD2-180 GEN
Solar/Wind Helper
2.032
23562501BACKB
Solar/Wind Helper
1.07
238117U2-030
Solar/Wind Helper
0.343
235531U2-073 GEN
Solar/Wind Helper
3.23
20089226LOOKOUT
Solar/Wind Helper
0.665
254303AC2-168 GEN
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.28
23751101LEADS_P59
Solar/Wind Helper
1.483
20088826HIGHLAND
Solar/Wind Helper
1.011
20094526CT_V3-030
Solar/Wind Helper
0.53
964201AG1-281 GEN
Solar/Wind Helper
0.544
238108AE1-109 GEN1
Solar/Wind Helper
0.102
964391AG1-301 GEN
Solar/Wind Helper
0.529
203954AE2-126 C
Solar/Wind Helper
0.522
238206AE2-263_GEN
Solar/Wind Helper
1.011
959471AF2-238 GEN
Solar/Wind Helper
0.517
203860AG1-193 C
Solar/Wind Helper
0.254
209067AE2-060 GEN
Solar/Wind Helper
0.091
946691AF1-333 GEN
Solar/Wind Helper
0.5
946741AF1-338 GEN
Solar/Wind Helper
0.5
961421AF2-433 GEN
Solar/Wind Helper
0.499
957921AF2-086 GEN
Solar/Wind Helper
0.493
961331AF2-424 GEN
Solar/Wind Helper
0.499
209027LOR2_Q27
Solar/Wind Helper
1.165
963071AG1-156 GEN
Solar/Wind Helper
1.625
963161AG1-165 GEN
Solar/Wind Helper
0.496
316095T157 G97
Solar/Wind Helper
1.154
23583801GRNGAP
Solar/Wind Helper
4.282
961971AG1-040 GEN
Solar/Wind Helper
0.492
203835AF1-098 GEN
Solar/Wind Helper
1.958
20674628WNG_W3-110
Solar/Wind Helper
0.097
207510AF2-138 C
Solar/Wind Helper
0.088
20676728BRNX1-095
Solar/Wind Helper
0.032
217169METRODIV C
Solar/Wind Helper
0.004
217211CAMDEN ST C
Solar/Wind Helper
0.005
20673728F2S_V4-070
Solar/Wind Helper
0.032
219249CENTRALDIV C
Solar/Wind Helper
0.011
219908AB1-139 C
Solar/Wind Helper
0.079
219919AE1-041 FULL
Solar/Wind Helper
0.004
218438BLK ROCK C
Solar/Wind Helper
0.029
219612MATRIX C
Solar/Wind Helper
0.025
20720528MAN_W1-024
Solar/Wind Helper
0.03
205932AD2-116_GEN
Solar/Wind Helper
0.523
205956AE1-196_GEN
Solar/Wind Helper
0.523
205943AE1-185 GEN
Solar/Wind Helper
0.523
232436AB1-176 C
Solar/Wind Helper
0.046
233935AB2-179 C
Solar/Wind Helper
1.307
960921AF2-383 GEN
Solar/Wind Helper
0.373
971171AH1-044 GEN
Solar/Wind Harmer
3.998
963151AG1-164 GEN
Solar/Wind Helper
0.496
316097T157 G90
Solar/Wind Helper
1.154
203830AF1-094 GEN
Solar/Wind Helper
0.495
20671928W4-073
Solar/Wind Helper
0.098
207518AF1-320_GEN
Solar/Wind Helper
1.718
207437AD2-070 GEN
Solar/Wind Helper
0.15
20675828AU_W4-064
Solar/Wind Helper
0.032
207439AE1-081 C O1
Solar/Wind Helper
0.02
20674328GAR_V4-001
Solar/Wind Helper
0.024
217208PARK ELE C
Solar/Wind Helper
0.005
217209CENTRL HS C
Solar/Wind Helper
0.009
20676428JCR_X2-075
Solar/Wind Helper
0.073
207528AF2-192 GEN
Solar/Wind Helper
0.082
20673628F1S_V4-069
Solar/Wind Helper
0.032
20675428EAM_W2-061
Solar/Wind Helper
0.017
962511AG1-100 GEN
Solar/Wind Helper
0.488
217213AMBOY SO C
Solar/Wind Helper
0.031
218428ETC SOLAR C
Solar/Wind Helper
0.005
205941AD2-115 GEN
Solar/Wind Helper
0.531
20742028HF_AC1-207
Solar/Wind Helper
0.15
20715228NPK_W1-113
Solar/Wind Helper
0.083
207454AA2-184 E
Solar/Wind Helper
0.331
219680HOPEWELLV C1
Solar/Wind Helper
0.003
963711AG1-223 GEN
Solar/Wind Helper
0.068
20714828MDF_W3-079
Solar/Wind Helper
0.139
207445AB1-138_GEN
Solar/Wind Helper
0.111
20720728JCB_W1-129
Solar/Wind Helper
0.061
219304NAMERICA C
Solar/Wind Helper
0.139
219686LUMSOLAR_N C
Solar/Wind Helper
0.042
219907AC1-030 C
Solar/Wind Helper
0.036
218660EHAMPSOLAR C
Solar/Wind Helper
0.035
219904AC1-010 C
Solar/Wind Helper
0.064
219258KINSLEYDEP C
Solar/Wind Helper
0.081
228728W1-130C
Solar/Wind Helper
0.057
230434AG1-499 GEN
Solar/Wind Helper
0.241
230511AF1-262
Solar/Wind Helper
0.015
233972AC1-094 C
Solar/Wind Helper
0.312
233998TM1NIN_3.36
Solar/Wind Helper
0.27
233954AC2-188 GEN
Solar/Wind Helper
0.24
232404W1-003 C
Solar/Wind Helper
0.523
233950AC2-186 GEN
Solar/Wind Helper
0.12
232428Y3-058 C
Solar/Wind Helper
0.349
232434Z2-077 GEN
Solar/Wind Helper
0.131
232426Y1-080 FULL
Solar/Wind Helper
0.04
233964AF2-378 GEN
Solar/Wind Helper
0.043
232422X3-066 FULL
Solar/Wind Helper
0.118
233930AB2-032 GEN
Solar/Wind Helper
0.392
233915AB1-141 GEN
Solar/Wind Helper
0.518
966131AG1-482 GEN
Solar/Wind Helper
0.139
235062AE1-101 C1
Solar/Wind Helper
1.463
237038AE2-054 C
Solar/Wind Helper
0.238
237080AD1-060 GEN
Solar/Wind Helper
0.296
23779801AA1-109
Solar/Wind Helper
0.168
223401AF1-299 GEN
Solar/Wind Helper
0.338
959091AF2-200 GEN
Solar/Wind Harmer
3.998
20714528FRN_Y2-051
Solar/Wind Helper
0.061
219276PARKLANDSO C
Solar/Wind Helper
0.095
20720828JCB_W4-025
Solar/Wind Helper
0.067
20715028HAN_X4-015
Solar/Wind Helper
0.061
20716028EGP_W2-019
Solar/Wind Helper
0.02
959561AF2-247 GEN
Solar/Wind Helper
0.022
219348LDSOLAR C
Solar/Wind Helper
0.121
219906AC1-017 C
Solar/Wind Helper
0.044
219236SOUTHERNHQ C
Solar/Wind Helper
0.005
219291REEVESSOUT C
Solar/Wind Helper
0.012
219912AD2-042 GEN
Solar/Wind Helper
0.158
219766PARADISE C
Solar/Wind Helper
0.057
219623KINSLEYBEA C
Solar/Wind Helper
0.002
228729W2-030 C
Solar/Wind Helper
0.116
230415AB2-049 C
Solar/Wind Helper
0.032
230430AE1-229_GEN
Solar/Wind Helper
3.539
233971AC1-093 C
Solar/Wind Helper
0.369
233996TM1833_GEN
Solar/Wind Helper
0.27
233997TMININ_4.2
Solar/Wind Helper
0.27
233952AC2-187 GEN
Solar/Wind Helper
0.24
232406W1-004 FULL
Solar/Wind Helper
0.523
233940AF2-379 C
Solar/Wind Helper
0.064
234015AF2-250 C
Solar/Wind Helper
0.039
233994AC2-023 GEN
Solar/Wind Helper
0.992
233982AB2-133 GEN
Solar/Wind Helper
0.369
233918AB1-142 GEN
Solar/Wind Helper
0.518
235067AD1-061 GEN
Solar/Wind Helper
0.433
205917AD1-020 ES
Solar/Wind Helper
0.368
238221AF1-254 C O1
Solar/Wind Helper
0.236
237030AB1-096 C
Solar/Wind Helper
0.063
223402AF1-300 C
Solar/Wind Helper
0.338
957471AF2-041 GEN
Solar/Wind Harmer
5.997
959081AF2-199 GEN
Solar/Wind Harmer
1.999
971067AG2-660 GEN
Solar/Wind Harmer
0.666
944201AF1-088_MTX
Adder
163.563
957141AF2-008_MTX
Adder
81.782
CBM West 1LTFEXP_CBM-W1->PJM
CBM
170.264
CBM South 1LTFEXP_CBM-S1->PJM
CBM
48.581
MECLTFEXP_MEC->PJM
CLTF
21.939
SIGELTFEXP_SIGE->PJM
CLTF
0.729
CPLELTFEXP_CPLE->PJM
CLTF
6.557
CBM West 2LTFEXP_CBM-W2->PJM
CBM
173.156
LAGNLTFEXP_LAGN->PJM
CLTF
24.864
CBM South 2LTFEXP_CBM-S2->PJM
CBM
25.24
TVALTFEXP_TVA->PJM
CLTF
12.63
NYPJM->LTFIMP_NY
CLTF
6.276
LGEELTFEXP_LGEE->PJM
CLTF
9.844
WECLTFEXP_WEC->PJM
CLTF
5.002
AG2-052LTFEXP_AG2-052->PJM
LTF
0.306
AH1-155LTFEXP_AH1-155->PJM
LTF
0.459

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.86 %
Rating:4558.0 MVA
Rating Type:A
MVA to Mitigate:4961.85
MW Contribution:6.37
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.473
972203AH1-686 GEN
Adder
3.978
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
24477305BRIDGE
Adder
0.546
270399AC1-101 GEN
Solar/Wind Harmer
3.444
270400AC1-102 GEN
Solar/Wind Harmer
3.444
941621AE2-160 GEN
Adder
4.703
970281AG2-184 GEN
Solar/Wind Harmer
20.149
972143AH1-644 GEN
Solar/Wind Harmer
10.394
971313AH1-133 GEN
Solar/Wind Harmer
9.492
270132AB1-180 C
Adder
0.159
971061AG2-657 GEN
Solar/Wind Harmer
5.654
24734705WLF1G3
Adder
7.306
24734805WLF1G4
Adder
7.306
24734905WLF1G5
Adder
7.306
971985AH1-537 GEN
Solar/Wind Harmer
2.617
24735105WLF2G1
Adder
7.162
966391AG1-508 GEN
Solar/Wind Harmer
1.328
970879AG2-548 GEN
Solar/Wind Harmer
7.21
971981AH1-535 GEN
Solar/Wind Harmer
5.272
270367AC2-061_GEN
Solar/Wind Harmer
0.006
972163AH1-664 GEN
Solar/Wind Harmer
8.62
972165AH1-665 GEN
Solar/Wind Harmer
6.904
3429211JKCT 2G
Adder
12.898
965401AG1-405 GEN
Solar/Wind Harmer
4.386
965411AG1-406 GEN
Solar/Wind Harmer
2.821
339211AE2-254 GEN
Solar/Wind Harmer
0.003
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
5.018
25196108MFTGT2
Adder
1.614
25196108MFTGT2
Adder
1.499
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.147
25196308WSDLE2
Adder
9.067
25196208WSDLE1
Adder
9.045
25196708WSDLE6
Adder
9.022
25196508WSDLE4
Adder
8.795
962771AG1-126 GEN
Solar/Wind Harmer
27.465
270340AC2-060 GEN
Solar/Wind Harmer
0.008
270069AE2-166 C O1
Solar/Wind Harmer
0.005
944221AF1-090 GEN
Solar/Wind Harmer
3.946
963841AG1-237 GEN
Solar/Wind Harmer
2.88
270240V3-007_GEN2
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
243186AF1-051 GEN
50/50
11.679
24723005RIVRG1
Adder
32.794
24723105RIVRG2
Adder
32.794
24685805CER G1
Adder
14.046
24685905CER G2
Adder
14.046
944971AF1-162 GEN
Solar/Wind Harmer
11.031
24728205BUCHG1
Adder
6.221
971225AH1-072 GEN
Solar/Wind Harmer
1.893
971227AH1-073 GEN
Solar/Wind Harmer
1.893
971277AH1-098 GEN
Solar/Wind Harmer
3.403
960161AF2-307 GEN
Solar/Wind Harmer
5.337
971073AG2-665 GEN
Solar/Wind Harmer
7.21
270583AD2-179 GEN
Solar/Wind Harmer
7.911
270186AC1-089 GEN
Solar/Wind Harmer
0.005
970239AG2-162 GEN
Solar/Wind Harmer
1.961
962581AG1-107 GEN
Solar/Wind Harmer
0.002
942891AE2-308 GEN
Solar/Wind Harmer
7.714
972043AH1-570 GEN
Solar/Wind Harmer
1.999
972045AH1-571 GEN
Solar/Wind Harmer
1.602
339221AD2-048_GEN
Solar/Wind Harmer
0.005
971125AH1-004 GEN
Solar/Wind Harmer
3.056
970107AG2-081 GEN
Solar/Wind Harmer
2.292
970235AG2-159 GEN
Solar/Wind Harmer
4.628
970235AG2-159 GEN
Solar/Wind Harmer
2.656
966021AG1-471 GEN
Solar/Wind Harmer
4.054
252509AD1-136 GEN
Solar/Wind Harmer
0.038
971485AH1-239 GEN
Solar/Wind Harmer
5.998
971081AG2-670 GEN
Solar/Wind Harmer
5.621
970653AG2-424 GEN
Solar/Wind Harmer
3.613
970653AG2-424 GEN
Solar/Wind Harmer
1.872
964571AG1-320 GEN
Solar/Wind Harmer
6.819
339255AE2-071 GEN
Solar/Wind Harmer
-0.122
964781AG1-341 GEN
Solar/Wind Harmer
7.848
25183208HLCRTG
Solar/Wind Harmer
0.011
252519AF1-045_GEN
Solar/Wind Harmer
6.373
252516AE2-318_GEN
Solar/Wind Harmer
5.653
270444AC2-157 GEN1
Solar/Wind Harmer
0.003
971587AH1-292 GEN
Solar/Wind Harmer
5.336
25194408D.CRK1
Adder
7.868
25194508D.CRK3
Adder
1.471
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
945391AF1-204 GEN
Solar/Wind Harmer
7.288
24728805RICHG1
Adder
3.669
24728905RICHG2
Adder
3.669
970241AG2-163 GEN
Solar/Wind Harmer
3.905
276916AD2-100_GEN
Solar/Wind Harmer
14.016
276911AD2-131_GEN
Solar/Wind Harmer
0.923
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.746
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
3.122
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.169
960441AF2-335 GEN
Solar/Wind Harmer
6.468
960611AF2-352 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
970883AG2-550 GEN
Solar/Wind Harmer
6.374
970885AG2-551 GEN
Solar/Wind Harmer
2.125
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.25
276646AC1-214 GEN2
Solar/Wind Harmer
0.25
270599AE1-208 GEN
Solar/Wind Harmer
5.819
270031AE2-169
Solar/Wind Harmer
3.492
276741O09 GEN1
Solar/Wind Harmer
0.226
276708O09 GEN2
Solar/Wind Harmer
0.226
972267AH1-718 GEN
Adder
3.783
25322209TAIT E
Adder
8.86
25322209TAIT E
Adder
8.661
24699105WLD G1 C
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.24
276848AB2-070 GEN3
Solar/Wind Harmer
0.239
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
24289405MTG1
50/50
10.907
243186AF1-051 GEN
50/50
11.679
24318705GVG2
50/50
10.872
24721805FLATG3
50/50
2.473
24721705FLATG2
50/50
45.331
24723205RIVRG3
Adder
32.794
24686105CER G3
Adder
14.139
24686505CER G6
Adder
14.12
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.368
971403AH1-188 GEN
Solar/Wind Harmer
15.305
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
6.221
971315AH1-136 GEN
Solar/Wind Harmer
1.928
971687AH1-348 GEN
Solar/Wind Harmer
0.947
927014AC1-188 GEN
Solar/Wind Harmer
0.005
24735205WLF2G2
Adder
7.162
971329AH1-144 GEN
Solar/Wind Harmer
6.901
970091AG2-072 GEN
Adder
86.947
970333AG2-219 GEN
Solar/Wind Harmer
5.608
945681AF1-233 GEN
Solar/Wind Harmer
14.563
3429241JKCT 3G
Adder
13.068
971821AH1-427 GEN
Solar/Wind Harmer
7.658
3429421JKCT 10G
Adder
9.139
339216AC1-074 GEN
Solar/Wind Harmer
0.209
970273AG2-179 GEN
Solar/Wind Harmer
2.644
971565AH1-281 GEN
Solar/Wind Harmer
1.508
252507AC2-088 GEN
Solar/Wind Harmer
0.341
964901AG1-354 GEN
Solar/Wind Harmer
11.154
25196808ZIMRHP
Adder
80.408
962241AG1-070 GEN
Solar/Wind Harmer
4.025
25196008MFTGT1
Adder
1.465
270445AC2-157 GEN2
Solar/Wind Harmer
0.003
25194608D.CRK4
Adder
1.71
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.086
962761AG1-125 GEN
Solar/Wind Harmer
27.465
970149AG2-104 GEN
Solar/Wind Harmer
29.663
970155AG2-107 GEN
Solar/Wind Harmer
17.538
270336AE1-100 GEN
Solar/Wind Harmer
0.004
270263AC1-001 GEN
Solar/Wind Harmer
0.699
24728605AND G2
Adder
3.761
970773AG2-487 GEN
Solar/Wind Harmer
1.204
971367AH1-164 GEN
Solar/Wind Harmer
2.344
963741AG1-226 GEN
Solar/Wind Harmer
15.844
965911AG1-460 GEN
Solar/Wind Harmer
1.332
943811AF1-049 GEN
Solar/Wind Harmer
-0.001
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
4.849
276615X2-022 GEN
Solar/Wind Harmer
0.069
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
2.568
274880W4-005 GEN4
Solar/Wind Harmer
0.001
276903AD2-071 C
Solar/Wind Harmer
7.334
972175AH1-670 GEN
Solar/Wind Harmer
5.394
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
0.846
270032AE2-172
Solar/Wind Harmer
4.336
270005AE1-210 C O1
Solar/Wind Harmer
1.405
965031AG1-367 GEN
Solar/Wind Harmer
6.485
970825AG2-519 GEN
Solar/Wind Harmer
2.296
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.009
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.976
274877BISHOP HL;1U
Solar/Wind Harmer
0.214
276158O29GEN2
Solar/Wind Harmer
0.001
960071AF2-298 GEN
Solar/Wind Harmer
3.157
25326309TAIT D
Adder
0.995
970569AG2-363 GEN
Solar/Wind Harmer
18.972
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
8.432
274766LEE CO EC;7U
Adder
8.332
945371AF1-202 GEN
Solar/Wind Harmer
0.001
247536S-71 GEN
Solar/Wind Harmer
0.254
971475AH1-234 GEN
Solar/Wind Harmer
3.061
970819AG2-516 GEN
Solar/Wind Harmer
7.565
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
972235AH1-702 GEN1
Adder
2.276
939401AE1-172 GEN
Solar/Wind Harmer
4.71
274822ROCKFORD ;11
Adder
17.71
957471AF2-041 GEN
Solar/Wind Harmer
18.878
959081AF2-199 GEN
Solar/Wind Harmer
6.293
24289405MTG1
50/50
10.907
24318705GVG2
50/50
10.872
24722005FLATG5
50/50
2.473
24721905FLATG4
50/50
45.331
24686205CER G4
Adder
14.065
24686405CER G5
Adder
14.009
270053AF1-130 C
Solar/Wind Harmer
2.49
970913AG2-568 GEN
Solar/Wind Harmer
8.136
971191AH1-055 GEN
Solar/Wind Harmer
25.624
960911AF2-382 GEN
Solar/Wind Harmer
7.284
972103AH1-617 GEN
Solar/Wind Harmer
19.189
971461AH1-227 GEN
Solar/Wind Harmer
4.855
270346AE1-212 GEN
Solar/Wind Harmer
7.86
943031AE2-326 GEN
Solar/Wind Harmer
4.498
971331AH1-145 GEN
Solar/Wind Harmer
10.953
247619Y1-049
Adder
0.497
958121AF2-106 GEN
Solar/Wind Harmer
0.001
970243AG2-164 GEN
Solar/Wind Harmer
4.588
970519AG2-331 GEN
Solar/Wind Harmer
20.392
970699AG2-449 GEN
Solar/Wind Harmer
1.961
970093AG2-073 GEN
Solar/Wind Harmer
7.734
972167AH1-666 GEN
Solar/Wind Harmer
6.174
972273AH1-721 GEN
Adder
91.659
966571AG1-526 GEN
Solar/Wind Harmer
17.032
3429391JKCT 9G
Adder
9.139
970273AG2-179 GEN
Solar/Wind Harmer
4.533
270291AC1-194 GEN
Solar/Wind Harmer
5.957
958171AF2-111 GEN
Solar/Wind Harmer
18.792
339250AF1-203 GEN
Solar/Wind Harmer
0.001
960741AF2-365 GEN
Solar/Wind Harmer
3.705
971155AH1-034 GEN
Solar/Wind Harmer
8.639
962251AG1-071 GEN
Solar/Wind Harmer
4.615
25196008MFTGT1
Adder
1.418
252510AF1-249 C
Solar/Wind Harmer
0.056
25194608D.CRK4
Adder
1.71
25196608WSDLE5
Adder
8.886
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.211
970153AG2-106 GEN
Solar/Wind Harmer
17.538
253406AD2-031_GEN
Solar/Wind Harmer
0.522
970193AG2-126 GEN
Solar/Wind Harmer
10.289
24728705AND G3
Adder
7.865
24728505AND G1
Adder
3.761
270356AE2-297 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
3.451
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270030AE2-140 GEN
Solar/Wind Harmer
13.595
942481AE2-261 GEN
Solar/Wind Harmer
19.91
972173AH1-669 GEN
Solar/Wind Harmer
3.31
270437AC2-090 C
Solar/Wind Harmer
0.003
276621W2-048 GEN
Solar/Wind Harmer
0.333
276838X2-022 GEN2
Solar/Wind Harmer
0.372
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.038
276668AB2-070 GEN1
Solar/Wind Harmer
0.24
247642Z2-115 C
Solar/Wind Harmer
0.003
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
6.514
270273AD2-016 GEN
Solar/Wind Harmer
0.675
970289AG2-191 GEN
Solar/Wind Harmer
0.716
970291AG2-192 GEN
Solar/Wind Harmer
0.651
958821AF2-173 GEN
Solar/Wind Harmer
9.079
270004AE1-209 GEN
Solar/Wind Harmer
1.405
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
19.404
959611AF2-252 GEN
Solar/Wind Harmer
2.156
253370AE2-315 SEC1
Adder
1.856
253371AE2-315 SEC2
Adder
1.755
942111AE2-223 GEN
Solar/Wind Harmer
2.091
946031AF1-268 GEN
Solar/Wind Harmer
6.117
970191AG2-125 GEN
Solar/Wind Harmer
1.65
965931AG1-462 GEN
Solar/Wind Harmer
16.291
274878BISHOP HL;2U
Solar/Wind Harmer
0.214
276157O29GEN1
Solar/Wind Harmer
1.026
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
970571AG2-364 GEN
Solar/Wind Harmer
12.648
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
8.432
274767LEE CO EC;8U
Adder
8.332
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
1.979
959091AF2-200 GEN
Solar/Wind Harmer
12.585
274682WAUKEGAN ;7U
Adder
16.093
274729ELWOOD EC;1P
Adder
6.64
237048AF1-022 C
Solar/Wind Helper
0.172
237043AE2-125 C
Solar/Wind Helper
0.155
235058AG1-386 C
Solar/Wind Helper
0.383
970513AG2-328 GEN
Solar/Wind Harmer
1.358
970517AG2-330 GEN
Solar/Wind Harmer
8.151
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
270269AC2-059
Solar/Wind Harmer
0.004
970289AG2-191 GEN
Solar/Wind Harmer
1.237
270594AE1-207 GEN
Solar/Wind Harmer
7.284
25306009OHH W.
Adder
2.673
970115AG2-085 GEN
Solar/Wind Harmer
2.587
253372AE2-315 SEC3
Adder
1.755
253372AE2-315 SEC3
Adder
1.755
971673AH1-337 GEN
Solar/Wind Harmer
4.2
971029AG2-637 GEN
Solar/Wind Harmer
9.661
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
6.757
941731AE2-173 GEN
Solar/Wind Harmer
5.363
253349AC2-067 GEN
Solar/Wind Harmer
2.02
253400AC2-068 GEN
Solar/Wind Harmer
0.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
3.573
971611AH1-305 GEN
Solar/Wind Harmer
3.799
270543AE2-219 C
Solar/Wind Harmer
0.004
957751AF2-069 GEN
Solar/Wind Harmer
0.21
970169AG2-114 GEN
Solar/Wind Harmer
6.359
971609AH1-304 GEN
Solar/Wind Harmer
1.037
961011AF2-392 GEN
Solar/Wind Harmer
3.717
926823AC1-168 GEN
Solar/Wind Harmer
1.076
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
10.171
945581AF1-223 GEN
Solar/Wind Harmer
0
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
17.581
971171AH1-044 GEN
Solar/Wind Harmer
12.585
274746AC1-111 G10
Adder
4.992
274744AC1-111 GEN8
Adder
4.992
23750501ELLIOTTS
Solar/Wind Helper
0.594
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
8.452
274765LEE CO EC;6U
Adder
8.452
274762LEE CO EC;3U
Adder
8.432
274763LEE CO EC;4U
Adder
8.352
938861AE1-114 GEN
Solar/Wind Harmer
3.58
274856ECOGROVE ;U1
Solar/Wind Harmer
0.149
276611AD2-172 GEN
Solar/Wind Harmer
0.002
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971341AH1-150 GEN
Solar/Wind Harmer
12.585
971343AH1-151 GEN
Solar/Wind Harmer
12.585
247621Y3-024
Adder
0.216
274683WAUKEGAN ;8U
Adder
18.876
274683WAUKEGAN ;8U
Adder
15.912
274696ROCKY RD ;4P
Adder
10.207
274695ROCKY RD ;2P
Adder
9.971
274693ROCKY RD ;1P
Adder
9.873
274697ROCKY RD ;3P
Adder
2.709
23652301WDPWR_K20
Solar/Wind Helper
0.126
23585401KL_K28_T16
Solar/Wind Helper
1.149
970321AG2-212 GEN
Solar/Wind Harmer
1.358
971067AG2-660 GEN
Solar/Wind Harmer
2.098
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
8.18
971997AH1-543 GEN
Solar/Wind Harmer
3.301
274828WAUKEGAN ;BP
Adder
9.895
274682WAUKEGAN ;7U
Adder
16.093
274745AC1-111 GEN9
Adder
4.992
237046AF1-021 C
Solar/Wind Helper
0.433
238185AF2-356 C
Solar/Wind Helper
1.954
23751201ROTHROCK
Solar/Wind Helper
0.662
235054AD2-180 GEN
Solar/Wind Helper
1.52
23562501BACKB
Solar/Wind Helper
0.806
970245AG2-165 GEN
Solar/Wind Harmer
1.358
944201AF1-088_MTX
Adder
121.273
957141AF2-008_MTX
Adder
60.637
CBM West 1LTFEXP_CBM-W1->PJM
CBM
116.498
CBM South 1LTFEXP_CBM-S1->PJM
CBM
38.98
MECLTFEXP_MEC->PJM
CLTF
15.75
SIGELTFEXP_SIGE->PJM
CLTF
0.547
CPLELTFEXP_CPLE->PJM
CLTF
6.38
CBM West 2LTFEXP_CBM-W2->PJM
CBM
132.776
LAGNLTFEXP_LAGN->PJM
CLTF
19.803
CBM South 2LTFEXP_CBM-S2->PJM
CBM
23.164
TVALTFEXP_TVA->PJM
CLTF
10.26
NYPJM->LTFIMP_NY
CLTF
4.59
LGEELTFEXP_LGEE->PJM
CLTF
7.503
WECLTFEXP_WEC->PJM
CLTF
3.454
AG2-052LTFEXP_AG2-052->PJM
LTF
0.209
AH1-155LTFEXP_AH1-155->PJM
LTF
0.313

Details for 05MOUNTN-05BELMON 765.0 kV Ckt 1 line l/o AEP_P1-2_#7422_16_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05MOUNTN-05BELMON 765.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7422_16_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:106.56 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5885.34
MW Contribution:7.71
Bus #Bus NameTypeMW Contribution
24721605FLATG1
50/50
2.714
972203AH1-686 GEN
Adder
4.544
957241AF2-018 GEN
Solar/Wind Harmer
-0.002
270399AC1-101 GEN
Solar/Wind Harmer
4.077
270400AC1-102 GEN
Solar/Wind Harmer
4.077
24477305BRIDGE
Adder
0.637
270330AC1-082 GEN2
Solar/Wind Harmer
0.001
270329AC1-082 GEN1
Solar/Wind Harmer
0.001
971313AH1-133 GEN
Solar/Wind Harmer
12.016
941621AE2-160 GEN
Adder
5.66
966391AG1-508 GEN
Solar/Wind Harmer
1.802
970281AG2-184 GEN
Solar/Wind Harmer
24.373
972143AH1-644 GEN
Solar/Wind Harmer
12.573
270132AB1-180 C
Adder
0.198
24734705WLF1G3
Adder
9.185
24734805WLF1G4
Adder
9.185
24734905WLF1G5
Adder
9.185
24735105WLF2G1
Adder
9.002
971061AG2-657 GEN
Solar/Wind Harmer
6.864
971985AH1-537 GEN
Solar/Wind Harmer
3.047
971981AH1-535 GEN
Solar/Wind Harmer
6.609
270069AE2-166 C O1
Solar/Wind Harmer
0.007
970879AG2-548 GEN
Solar/Wind Harmer
8.448
965401AG1-405 GEN
Solar/Wind Harmer
5.328
965411AG1-406 GEN
Solar/Wind Harmer
3.428
270367AC2-061_GEN
Solar/Wind Harmer
0.007
3429211JKCT 2G
Adder
15.52
339211AE2-254 GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
10.275
972165AH1-665 GEN
Solar/Wind Harmer
8.229
339243AC2-075 GEN1
Solar/Wind Harmer
0.002
970455AG2-298 GEN
Solar/Wind Harmer
6.053
25196108MFTGT2
Adder
1.926
25196108MFTGT2
Adder
1.788
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
10.91
25196308WSDLE2
Adder
10.815
25196208WSDLE1
Adder
10.788
25196708WSDLE6
Adder
10.761
25196508WSDLE4
Adder
10.49
270340AC2-060 GEN
Solar/Wind Harmer
0.01
962771AG1-126 GEN
Solar/Wind Harmer
32.213
944221AF1-090 GEN
Solar/Wind Harmer
4.776
963841AG1-237 GEN
Solar/Wind Harmer
3.474
270240V3-007_GEN2
Solar/Wind Harmer
0.002
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.29
276848AB2-070 GEN3
Solar/Wind Harmer
0.289
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
1.493
270594AE1-207 GEN
Solar/Wind Harmer
8.791
270269AC2-059
Solar/Wind Harmer
0.004
970115AG2-085 GEN
Solar/Wind Harmer
3.124
276655WTG1_EQ
Solar/Wind Harmer
0.003
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
8.194
941731AE2-173 GEN
Solar/Wind Harmer
6.503
25306009OHH W.
Adder
3.223
971673AH1-337 GEN
Solar/Wind Harmer
5.07
253372AE2-315 SEC3
Adder
2.117
253372AE2-315 SEC3
Adder
2.117
971029AG2-637 GEN
Solar/Wind Harmer
11.666
946321AF1-296 GEN
Solar/Wind Harmer
4.345
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
253349AC2-067 GEN
Solar/Wind Harmer
2.438
253400AC2-068 GEN
Solar/Wind Harmer
0.981
957751AF2-069 GEN
Solar/Wind Harmer
0.255
971611AH1-305 GEN
Solar/Wind Harmer
4.596
970169AG2-114 GEN
Solar/Wind Harmer
7.718
270543AE2-219 C
Solar/Wind Harmer
0.005
961011AF2-392 GEN
Solar/Wind Harmer
4.519
926823AC1-168 GEN
Solar/Wind Harmer
1.307
274863CRW1-WTG
Solar/Wind Harmer
0.002
24289405MTG1
50/50
11.79
24318705GVG2
50/50
11.866
24722005FLATG5
50/50
2.714
24721905FLATG4
50/50
49.755
24686205CER G4
Adder
16.139
24686405CER G5
Adder
16.075
270053AF1-130 C
Solar/Wind Harmer
2.937
970913AG2-568 GEN
Solar/Wind Harmer
9.858
960911AF2-382 GEN
Solar/Wind Harmer
9.021
943031AE2-326 GEN
Solar/Wind Harmer
6.109
971461AH1-227 GEN
Solar/Wind Harmer
5.958
972103AH1-617 GEN
Solar/Wind Harmer
23.212
971331AH1-145 GEN
Solar/Wind Harmer
15.359
247619Y1-049
Adder
0.704
971191AH1-055 GEN
Solar/Wind Harmer
29.418
270346AE1-212 GEN
Solar/Wind Harmer
10.08
958121AF2-106 GEN
Solar/Wind Harmer
0.001
972273AH1-721 GEN
Adder
111.61
270030AE2-140 GEN
Solar/Wind Harmer
18.75
970093AG2-073 GEN
Solar/Wind Harmer
9.318
970243AG2-164 GEN
Solar/Wind Harmer
5.432
970519AG2-331 GEN
Solar/Wind Harmer
24.144
970699AG2-449 GEN
Solar/Wind Harmer
2.322
966571AG1-526 GEN
Solar/Wind Harmer
20.57
270173AC1-122 GEN
Solar/Wind Harmer
0.435
3429391JKCT 9G
Adder
10.993
970273AG2-179 GEN
Solar/Wind Harmer
5.522
972167AH1-666 GEN
Solar/Wind Harmer
7.359
962751AG1-124 GEN
Solar/Wind Harmer
8.092
339250AF1-203 GEN
Solar/Wind Harmer
0.001
971155AH1-034 GEN
Solar/Wind Harmer
10.521
960741AF2-365 GEN
Solar/Wind Harmer
4.499
962251AG1-071 GEN
Solar/Wind Harmer
5.619
958171AF2-111 GEN
Solar/Wind Harmer
22.442
270291AC1-194 GEN
Solar/Wind Harmer
7.02
25196008MFTGT1
Adder
1.692
252510AF1-249 C
Solar/Wind Harmer
0.067
25194608D.CRK4
Adder
2.039
25196608WSDLE5
Adder
10.598
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
11.009
253406AD2-031_GEN
Solar/Wind Harmer
0.624
970193AG2-126 GEN
Solar/Wind Harmer
12.39
24728705AND G3
Adder
9.464
24728505AND G1
Adder
4.525
970153AG2-106 GEN
Solar/Wind Harmer
20.57
270574AD1-017 GEN2
Solar/Wind Harmer
0.001
3147312GRETNA
Solar/Wind Harmer
0.123
3146802CHATHAM
Solar/Wind Harmer
0.115
941801AE2-185 GEN
Solar/Wind Harmer
4.925
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270222AC2-111 GEN
Solar/Wind Harmer
4.144
253415AE1-040 GEN
Solar/Wind Harmer
0.003
942481AE2-261 GEN
Solar/Wind Harmer
24.109
276621W2-048 GEN
Solar/Wind Harmer
0.403
276838X2-022 GEN2
Solar/Wind Harmer
0.45
270437AC2-090 C
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
3.68
276668AB2-070 GEN1
Solar/Wind Harmer
0.29
972173AH1-669 GEN
Solar/Wind Harmer
3.965
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.866
247642Z2-115 C
Solar/Wind Harmer
0.003
970289AG2-191 GEN
Solar/Wind Harmer
0.864
970291AG2-192 GEN
Solar/Wind Harmer
0.786
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
23.525
959611AF2-252 GEN
Solar/Wind Harmer
2.614
958821AF2-173 GEN
Solar/Wind Harmer
10.961
270004AE1-209 GEN
Solar/Wind Harmer
1.696
270273AD2-016 GEN
Solar/Wind Harmer
0.81
942111AE2-223 GEN
Solar/Wind Harmer
2.536
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
965931AG1-462 GEN
Solar/Wind Harmer
19.808
946031AF1-268 GEN
Solar/Wind Harmer
7.391
3147123OTTER R
Solar/Wind Harmer
0.087
274878BISHOP HL;2U
Solar/Wind Harmer
0.26
970191AG2-125 GEN
Solar/Wind Harmer
1.992
276157O29GEN1
Solar/Wind Harmer
1.248
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
10.252
274767LEE CO EC;8U
Adder
10.131
970571AG2-364 GEN
Solar/Wind Harmer
15.368
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
972236AH1-702 GEN2
Adder
2.406
276889AE2-281 GEN
Solar/Wind Harmer
0.001
270016AE1-250 BESS
Solar/Wind Harmer
0.004
959091AF2-200 GEN
Solar/Wind Harmer
15.301
274855GSG-6 ;RU
Solar/Wind Harmer
0.28
274850MENDOTA H;RU
Solar/Wind Harmer
0.09
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.137
274682WAUKEGAN ;7U
Adder
19.567
274729ELWOOD EC;1P
Adder
8.072
237048AF1-022 C
Solar/Wind Helper
0.182
964991AG1-363 GEN
Solar/Wind Helper
3.709
23750701CROSSCHOOL
Solar/Wind Helper
1.197
238118U2-030_1
Solar/Wind Helper
0.288
238127S14_GEN_2
Solar/Wind Helper
0.687
237043AE2-125 C
Solar/Wind Helper
0.163
202652Y1-033 WT C
Solar/Wind Helper
0.534
316097T157 G90
Solar/Wind Helper
1.094
20089126CSLMN_L13
Solar/Wind Helper
0.554
20089026BF_G21_K23
Solar/Wind Helper
0.438
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
0.329
243186AF1-051 GEN
50/50
12.748
24723005RIVRG1
Adder
37.637
24723105RIVRG2
Adder
37.637
24685805CER G1
Adder
16.117
24685905CER G2
Adder
16.117
944971AF1-162 GEN
Solar/Wind Harmer
13.01
24728205BUCHG1
Adder
7.763
971225AH1-072 GEN
Solar/Wind Harmer
2.323
971227AH1-073 GEN
Solar/Wind Harmer
2.323
971277AH1-098 GEN
Solar/Wind Harmer
4.634
270583AD2-179 GEN
Solar/Wind Harmer
11.403
960161AF2-307 GEN
Solar/Wind Harmer
6.387
971073AG2-665 GEN
Solar/Wind Harmer
8.448
270186AC1-089 GEN
Solar/Wind Harmer
0.006
970239AG2-162 GEN
Solar/Wind Harmer
2.322
942891AE2-308 GEN
Solar/Wind Harmer
9.282
972043AH1-570 GEN
Solar/Wind Harmer
2.394
972045AH1-571 GEN
Solar/Wind Harmer
1.918
339221AD2-048_GEN
Solar/Wind Harmer
0.006
966021AG1-471 GEN
Solar/Wind Harmer
4.953
971125AH1-004 GEN
Solar/Wind Harmer
3.667
970107AG2-081 GEN
Solar/Wind Harmer
2.751
971485AH1-239 GEN
Solar/Wind Harmer
7.325
962581AG1-107 GEN
Solar/Wind Harmer
0.002
971081AG2-670 GEN
Solar/Wind Harmer
6.822
970235AG2-159 GEN
Solar/Wind Harmer
5.533
970235AG2-159 GEN
Solar/Wind Harmer
3.174
970653AG2-424 GEN
Solar/Wind Harmer
4.368
970653AG2-424 GEN
Solar/Wind Harmer
2.263
339255AE2-071 GEN
Solar/Wind Harmer
-0.148
964781AG1-341 GEN
Solar/Wind Harmer
9.557
964571AG1-320 GEN
Solar/Wind Harmer
8.226
252509AD1-136 GEN
Solar/Wind Harmer
0.045
25183208HLCRTG
Solar/Wind Harmer
0.014
252519AF1-045_GEN
Solar/Wind Harmer
7.591
252516AE2-318_GEN
Solar/Wind Harmer
6.733
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
6.388
25194408D.CRK1
Adder
9.381
25194508D.CRK3
Adder
1.754
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
945391AF1-204 GEN
Solar/Wind Harmer
8.776
253394AE2-221_GEN
Solar/Wind Harmer
0.01
253398AE2-221_GEN2
Solar/Wind Harmer
0.01
316217AC1-145 GEN
Solar/Wind Harmer
0.002
316197AC1-042 GEN
Solar/Wind Harmer
0.002
942671AE2-283 GEN
Solar/Wind Harmer
3.83
24728805RICHG1
Adder
4.412
24728905RICHG2
Adder
4.412
276916AD2-100_GEN
Solar/Wind Harmer
16.969
276911AD2-131_GEN
Solar/Wind Harmer
1.118
970241AG2-163 GEN
Solar/Wind Harmer
4.709
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
966841AG1-555 GEN
Solar/Wind Harmer
0.9
270383AD1-128 GEN
Solar/Wind Harmer
0.005
971613AH1-306 GEN
Solar/Wind Harmer
3.767
960611AF2-352 GEN
Solar/Wind Harmer
2.614
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
970825AG2-519 GEN
Solar/Wind Harmer
8.658
960441AF2-335 GEN
Solar/Wind Harmer
7.811
253370AE2-315 SEC1
Adder
2.238
276782AC1-033 GEN
Solar/Wind Harmer
0.001
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.304
276646AC1-214 GEN2
Solar/Wind Harmer
0.304
276741O09 GEN1
Solar/Wind Harmer
0.275
276708O09 GEN2
Solar/Wind Harmer
0.275
972267AH1-718 GEN
Adder
4.6
970883AG2-550 GEN
Solar/Wind Harmer
7.705
970885AG2-551 GEN
Solar/Wind Harmer
2.568
276603SUBLETTE C
Solar/Wind Harmer
0
274764LEE CO EC;5U
Adder
10.276
274765LEE CO EC;6U
Adder
10.276
274762LEE CO EC;3U
Adder
10.252
274763LEE CO EC;4U
Adder
10.155
938861AE1-114 GEN
Solar/Wind Harmer
4.353
270599AE1-208 GEN
Solar/Wind Harmer
7.04
270031AE2-169
Solar/Wind Harmer
4.224
274856ECOGROVE ;U1
Solar/Wind Harmer
0.181
276611AD2-172 GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
10.707
25322209TAIT E
Adder
10.466
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
270013AE1-250 PV
Solar/Wind Harmer
0.004
971341AH1-150 GEN
Solar/Wind Harmer
15.301
971343AH1-151 GEN
Solar/Wind Harmer
15.301
274683WAUKEGAN ;8U
Adder
22.951
274683WAUKEGAN ;8U
Adder
19.347
274696ROCKY RD ;4P
Adder
12.409
274695ROCKY RD ;2P
Adder
12.123
274693ROCKY RD ;1P
Adder
12.003
274697ROCKY RD ;3P
Adder
3.293
247621Y3-024
Adder
0.262
23585401KL_K28_T16
Solar/Wind Helper
1.267
23652301WDPWR_K20
Solar/Wind Helper
0.133
238120AE2-309 GEN
Solar/Wind Helper
0.43
203955AF1-039 C O1
Solar/Wind Helper
0.352
944781AF1-143 GEN
Solar/Wind Helper
2.298
20083426SW_E13_K22
Solar/Wind Helper
0.051
20088926STNY CRK
Solar/Wind Helper
0.747
20084626FORWARD
Solar/Wind Helper
0.323
946071AF1-272 GEN
Solar/Wind Helper
2.428
203940AF1-140 C
Solar/Wind Helper
0.359
24289405MTG1
50/50
11.79
243186AF1-051 GEN
50/50
12.748
24318705GVG2
50/50
11.866
24721805FLATG3
50/50
2.714
24721705FLATG2
50/50
49.755
24723205RIVRG3
Adder
37.637
24686105CER G3
Adder
16.224
24686505CER G6
Adder
16.203
971403AH1-188 GEN
Solar/Wind Harmer
18.202
270331AC1-082 GEN3
Solar/Wind Harmer
0.001
970947AG2-589 GEN
Solar/Wind Harmer
0.42
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
24728305BUCHG2
Adder
7.763
971687AH1-348 GEN
Solar/Wind Harmer
1.161
971329AH1-144 GEN
Solar/Wind Harmer
9.676
971315AH1-136 GEN
Solar/Wind Harmer
2.301
24735205WLF2G2
Adder
9.002
927014AC1-188 GEN
Solar/Wind Harmer
0.006
971367AH1-164 GEN
Solar/Wind Harmer
3.536
270336AE1-100 GEN
Solar/Wind Harmer
0.005
970091AG2-072 GEN
Adder
103.033
970333AG2-219 GEN
Solar/Wind Harmer
6.64
3429241JKCT 3G
Adder
15.723
971821AH1-427 GEN
Solar/Wind Harmer
9.259
3429421JKCT 10G
Adder
10.993
945681AF1-233 GEN
Solar/Wind Harmer
17.357
970273AG2-179 GEN
Solar/Wind Harmer
3.221
943811AF1-049 GEN
Solar/Wind Harmer
-0.002
339216AC1-074 GEN
Solar/Wind Harmer
0.25
971565AH1-281 GEN
Solar/Wind Harmer
1.817
964901AG1-354 GEN
Solar/Wind Harmer
13.566
962241AG1-070 GEN
Solar/Wind Harmer
4.9
252507AC2-088 GEN
Solar/Wind Harmer
0.405
25196808ZIMRHP
Adder
95.812
25196008MFTGT1
Adder
1.747
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
25194608D.CRK4
Adder
2.039
270018AE2-047 C O1
Solar/Wind Harmer
0.004
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.469
270263AC1-001 GEN
Solar/Wind Harmer
0.833
24728605AND G2
Adder
4.525
962761AG1-125 GEN
Solar/Wind Harmer
32.213
970149AG2-104 GEN
Solar/Wind Harmer
34.791
970155AG2-107 GEN
Solar/Wind Harmer
20.57
270197AD1-017 GEN1
Solar/Wind Harmer
1.016
3147312GRETNA
Solar/Wind Harmer
0.031
941821AE2-187 GEN
Solar/Wind Harmer
4.925
970773AG2-487 GEN
Solar/Wind Harmer
1.447
963741AG1-226 GEN
Solar/Wind Harmer
19.103
965911AG1-460 GEN
Solar/Wind Harmer
1.613
276615X2-022 GEN
Solar/Wind Harmer
0.084
963831AG1-236 GEN
Solar/Wind Harmer
3.11
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
5.842
274880W4-005 GEN4
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
276903AD2-071 C
Solar/Wind Harmer
8.845
972175AH1-670 GEN
Solar/Wind Harmer
6.537
24791305MDL-5G
Solar/Wind Harmer
0.001
970291AG2-192 GEN
Solar/Wind Harmer
1.021
270032AE2-172
Solar/Wind Harmer
5.233
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
1.696
965031AG1-367 GEN
Solar/Wind Harmer
7.829
970825AG2-519 GEN
Solar/Wind Harmer
2.773
276726Z2-087_GEN
Solar/Wind Harmer
0.003
939741AE1-205 GEN
Solar/Wind Harmer
10.926
253370AE2-315 SEC1
Adder
2.238
253371AE2-315 SEC2
Adder
2.117
274877BISHOP HL;1U
Solar/Wind Harmer
0.26
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.649
276158O29GEN2
Solar/Wind Harmer
0.001
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
10.252
274766LEE CO EC;7U
Adder
10.131
970569AG2-363 GEN
Solar/Wind Harmer
23.052
971475AH1-234 GEN
Solar/Wind Harmer
3.722
970819AG2-516 GEN
Solar/Wind Harmer
9.198
972235AH1-702 GEN1
Adder
2.767
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.815
25326309TAIT D
Adder
1.202
274822ROCKFORD ;11
Adder
21.533
957471AF2-041 GEN
Solar/Wind Harmer
22.952
959081AF2-199 GEN
Solar/Wind Harmer
7.651
971067AG2-660 GEN
Solar/Wind Harmer
2.55
939401AE1-172 GEN
Solar/Wind Harmer
5.72
971997AH1-543 GEN
Solar/Wind Harmer
4.011
276861AD2-134 GEN
Solar/Wind Harmer
0.137
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274828WAUKEGAN ;BP
Adder
12.03
274682WAUKEGAN ;7U
Adder
19.567
274745AC1-111 GEN9
Adder
6.069
238185AF2-356 C
Solar/Wind Helper
2.176
237046AF1-021 C
Solar/Wind Helper
0.457
235054AD2-180 GEN
Solar/Wind Helper
1.695
238117U2-030
Solar/Wind Helper
0.288
235531U2-073 GEN
Solar/Wind Helper
2.733
23751201ROTHROCK
Solar/Wind Helper
0.71
23562501BACKB
Solar/Wind Helper
0.864
23583801GRNGAP
Solar/Wind Helper
4.088
316095T157 G97
Solar/Wind Helper
1.094
238108AE1-109 GEN1
Solar/Wind Helper
0.088
20089226LOOKOUT
Solar/Wind Helper
0.539
20088826HIGHLAND
Solar/Wind Helper
0.812
274864CRW2-WTG
Solar/Wind Harmer
0.002
971681AH1-341 GEN
Solar/Wind Harmer
12.366
971609AH1-304 GEN
Solar/Wind Harmer
1.254
276612AE2-035 GEN
Solar/Wind Harmer
0.002
274823ROCKFORD ;21
Adder
21.377
958391AF2-133 GEN
Solar/Wind Harmer
0.001
971171AH1-044 GEN
Solar/Wind Harmer
15.301
971675AH1-338 GEN
Solar/Wind Harmer
2.979
945581AF1-223 GEN
Solar/Wind Harmer
0.001
274746AC1-111 G10
Adder
6.069
274744AC1-111 GEN8
Adder
6.069
23750501ELLIOTTS
Solar/Wind Helper
0.635
238126S14_GEN_1
Solar/Wind Helper
0.687
238109AE1-109 GEN2
Solar/Wind Helper
0.088
238110AE1-109 GEN3
Solar/Wind Helper
0.088
20092526R32
Solar/Wind Helper
1.053
944201AF1-088_MTX
Adder
145.184
957141AF2-008_MTX
Adder
72.592
CBM West 1LTFEXP_CBM-W1->PJM
CBM
143.592
CBM South 1LTFEXP_CBM-S1->PJM
CBM
47.815
MECLTFEXP_MEC->PJM
CLTF
19.173
SIGELTFEXP_SIGE->PJM
CLTF
0.659
CPLELTFEXP_CPLE->PJM
CLTF
7.791
CBM West 2LTFEXP_CBM-W2->PJM
CBM
162.06
LAGNLTFEXP_LAGN->PJM
CLTF
24.37
CBM South 2LTFEXP_CBM-S2->PJM
CBM
29.03
TVALTFEXP_TVA->PJM
CLTF
12.655
NYPJM->LTFIMP_NY
CLTF
5.271
LGEELTFEXP_LGEE->PJM
CLTF
8.989
WECLTFEXP_WEC->PJM
CLTF
4.2
AG2-052LTFEXP_AG2-052->PJM
LTF
0.253
AH1-155LTFEXP_AH1-155->PJM
LTF
0.38

Details for 05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:132.35 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2472.27
MW Contribution:3.91
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
960851AF2-376 GEN
50/50
2.105
24641605TWIN BRNCH
50/50
0.015
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
22.101
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7443_05DUMONT 765_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7443_05DUMONT 765_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.16 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3597.55
MW Contribution:10.71
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.233
24729505KEY G4
50/50
13.359
24727205RPMNG3
50/50
1.299
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.446
958711AF2-162 GEN
Solar/Wind Harmer
1.798
965101AG1-375 GEN
Solar/Wind Harmer
17.237
945581AF1-223 GEN
Solar/Wind Harmer
7.354
963791AG1-232 GEN
Solar/Wind Harmer
21.417
965041AG1-368 GEN
Solar/Wind Harmer
15.714
965051AG1-369 GEN
Solar/Wind Harmer
7.257
270024AE2-089 GEN
Solar/Wind Harmer
6.437
970115AG2-085 GEN
Solar/Wind Harmer
5.221
971771AH1-392 GEN
Solar/Wind Harmer
11.61
944161AF1-084 GEN
Solar/Wind Harmer
2.8
270594AE1-207 GEN
Solar/Wind Harmer
18.528
971347AH1-153 GEN
Solar/Wind Harmer
18.754
965461AG1-414 GEN
Solar/Wind Harmer
2.831
970289AG2-191 GEN
Solar/Wind Harmer
2.373
270240V3-007_GEN2
Solar/Wind Harmer
7.66
971769AH1-391 GEN
Solar/Wind Harmer
12.335
961761AG1-017 GEN
Solar/Wind Harmer
0.526
960681AF2-359 GEN
Solar/Wind Harmer
4.523
24725505WLD G2 C
Solar/Wind Harmer
4.748
24699105WLD G1 C
Solar/Wind Harmer
4.693
957201AF2-014 GEN
Solar/Wind Harmer
5.389
270435AC2-044 GEN
Solar/Wind Harmer
2.377
971549AH1-272 GEN
Solar/Wind Harmer
21.937
247607V1-011 GEN
Solar/Wind Harmer
4.688
270536AF1-215 GEN2
Solar/Wind Harmer
5.134
274814UNIV PK N;0U
Adder
5.591
970583AG2-370 GEN
50/50
3.654
960851AF2-376 GEN
50/50
3.29
24727105RPMNG2
50/50
1.31
24641605TWIN BRNCH
50/50
0.024
944531AF1-118 GEN
Solar/Wind Harmer
69.986
270043AE2-236 GEN
Solar/Wind Harmer
10.796
959331AF2-224 GEN
Solar/Wind Harmer
18.221
965021AG1-366 GEN
Solar/Wind Harmer
4.237
970031AG2-029 GEN
Solar/Wind Harmer
49.52
270191TR4_S_V150
Solar/Wind Harmer
4.359
270247TR4_N_V136
Solar/Wind Harmer
1.236
958821AF2-173 GEN
Solar/Wind Harmer
19.357
270004AE1-209 GEN
Solar/Wind Harmer
7.556
971617AH1-308 GEN
Solar/Wind Harmer
7.974
247643Z2-116 C
Solar/Wind Harmer
0.094
945111AF1-176 GEN
Solar/Wind Harmer
7.419
946031AF1-268 GEN
Solar/Wind Harmer
10.671
24642205MAYFLWER
Adder
0.811
970349AG2-230 GEN
Solar/Wind Harmer
18.754
970289AG2-191 GEN
Solar/Wind Harmer
0.958
970291AG2-192 GEN
Solar/Wind Harmer
0.871
24441205WTRV SLR C
Solar/Wind Harmer
0.167
270437AC2-090 C
Solar/Wind Harmer
6.912
247642Z2-115 C
Solar/Wind Harmer
0.079
270044AE2-322 C
Solar/Wind Harmer
1.621
270404AC1-167 GEN
Solar/Wind Harmer
1.35
962031AG1-047 GEN
Solar/Wind Harmer
3.717
957741AF2-068 GEN
Solar/Wind Harmer
18.445
270258AD1-119 GEN
Solar/Wind Harmer
3.413
247604X1-042
Adder
0.507
270491AE1-102 GEN2
Solar/Wind Harmer
1.545
958091AF2-103 GEN
Solar/Wind Harmer
0.191
270535AF1-215 GEN1
Solar/Wind Harmer
5.134
972231SS25-0005
Solar/Wind Harmer
10.654
972181SS23-001
Solar/Wind Harmer
6.659
274752CRETE EC ;2U
Adder
5.487
274753CRETE EC ;3U
Adder
5.487
274724RIVER EC ;11
Adder
19.749
964401AG1-302 GEN
Solar/Wind Harmer
10.079
959141AF2-205 GEN
Solar/Wind Harmer
6.613
274802UNIV PARK;5U
Adder
6.37
274826FISK ;BP
Adder
11.941
274800UNIV PARK;3U
Adder
6.347
972038AH1-567 GEN2
Adder
0.397
274772LINCOLN ;3U
Adder
6.747
276772AC2-154 GEN
Solar/Wind Harmer
3.03
276806AD2-047 C O1
Solar/Wind Harmer
11.624
970941AG2-585 GEN
Solar/Wind Harmer
13.583
972228AH1-698 GEN2
Adder
4.009
970513AG2-328 GEN
Solar/Wind Harmer
19.29
970517AG2-330 GEN
Solar/Wind Harmer
17.496
274676JOLIET 29;8U
Adder
31.789
276897AD1-100 C
Solar/Wind Harmer
31.167
939351AE1-166 GEN
Solar/Wind Harmer
6.368
970707AG2-453 GEN
Solar/Wind Harmer
30.052
276893AG1-478 C
Solar/Wind Harmer
0.448
274730ELWOOD EC;6P
Adder
17.624
274734ELWOOD EC;8P
Adder
17.624
274736ELWOOD EC;9P
Adder
17.624
274729ELWOOD EC;1P
Adder
17.623
274682WAUKEGAN ;7U
Adder
18.807
972236AH1-702 GEN2
Adder
2.221
274760LEE CO EC;1U
Adder
9.299
274767LEE CO EC;8U
Adder
9.189
24728705AND G3
Adder
7.723
24728505AND G1
Adder
3.693
23906502RICHG2&3
Adder
0.873
274807UNIV PK N;3U
Adder
5.579
274805UNIV PK N;1U
Adder
5.554
274811UNIV PK N;7U
Adder
5.542
958391AF2-133 GEN
Solar/Wind Harmer
9.99
972037AH1-567 GEN1
Adder
0.2
274827FISK ;RP
Adder
8.463
274775LINCOLN ;6U
Adder
6.747
274776LINCOLN ;7U
Adder
6.747
274777LINCOLN ;8U
Adder
6.747
960591AF2-350 GEN
Solar/Wind Harmer
10.866
972227AH1-698 GEN1
Adder
2.823
274687WILL CNTY;4U
Adder
30.105
274687WILL CNTY;4U
Adder
30.105
274675JOLIET 29;7U
Adder
32.967
274675JOLIET 29;7U
Adder
31.79
274728ELWOOD EC;5P
Adder
17.624
274731ELWOOD EC;2P
Adder
17.623
274733ELWOOD EC;3P
Adder
17.623
274735ELWOOD EC;4P
Adder
17.623
270543AE2-219 C
Solar/Wind Harmer
5.485
970833AG2-524 GEN
Solar/Wind Harmer
9.303
970833AG2-524 GEN
Solar/Wind Harmer
4.327
274746AC1-111 G10
Adder
5.907
274744AC1-111 GEN8
Adder
5.907
274823ROCKFORD ;21
Adder
19.792
270054AF2-122 C O1
Solar/Wind Helper
0.777
270284AF1-227 GEN1
Solar/Wind Helper
1.165
270286AF1-227 GEN2
Solar/Wind Helper
0.427
270287AF1-227 GEN3
Solar/Wind Helper
0.427
270520AE2-214 GEN
Solar/Wind Helper
2.4
960861AF2-377 GEN
50/50
3.382
970521AG2-332 GEN
50/50
16.176
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.305
960791AF2-370 GEN
50/50
3.035
965011AG1-365 GEN
Solar/Wind Harmer
18.221
965651AG1-433 GEN
Solar/Wind Harmer
9.713
958861AF2-177 GEN
Solar/Wind Harmer
18.841
945371AF1-202 GEN
Solar/Wind Harmer
11.314
944231AF1-091 GEN
Solar/Wind Harmer
5.796
270063AE2-323 C
Solar/Wind Harmer
3.37
247521TR3_G114
Solar/Wind Harmer
4.887
270246TR4_N_V150
Solar/Wind Harmer
1.236
24695305TIMB G C
Solar/Wind Harmer
7.786
270005AE1-210 C O1
Solar/Wind Harmer
7.556
965031AG1-367 GEN
Solar/Wind Harmer
13.826
945111AF1-176 GEN
Solar/Wind Harmer
23.41
970825AG2-519 GEN
Solar/Wind Harmer
3.074
270505AE1-170 C O1
Solar/Wind Harmer
19.365
270449AD2-020 GEN
Solar/Wind Harmer
3.585
943021AE2-325 GEN
Solar/Wind Harmer
4.658
270032AE2-172
Solar/Wind Harmer
5.863
965421AG1-410 GEN
Solar/Wind Harmer
37.469
970291AG2-192 GEN
Solar/Wind Harmer
1.623
942081AE2-220 GEN
Solar/Wind Harmer
7.915
270239V3-007_GEN1
Solar/Wind Harmer
2.13
276903AD2-071 C
Solar/Wind Harmer
12.035
246936BC-WTG1
Solar/Wind Harmer
4.65
270489AE1-102 GEN1
Solar/Wind Harmer
1.545
970373AG2-245 GEN
Solar/Wind Harmer
24.186
247536S-71 GEN
Solar/Wind Harmer
4.625
270055AF2-134 C O1
Solar/Wind Harmer
3.422
274751CRETE EC ;1U
Adder
5.487
274754CRETE EC ;4U
Adder
5.487
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.237
247620Y3-023
50/50
0.69
970611AG2-400 GEN
Solar/Wind Harmer
18.221
944541AF1-119 GEN
Solar/Wind Harmer
7.444
960971AF2-388 GEN
Solar/Wind Harmer
19.425
942221AE2-234 GEN
Solar/Wind Harmer
1.156
270599AE1-208 GEN
Solar/Wind Harmer
11.731
270031AE2-169
Solar/Wind Harmer
11.731
270216AD2-079_GEN
Solar/Wind Harmer
0.818
960441AF2-335 GEN
Solar/Wind Harmer
13.052
970825AG2-519 GEN
Solar/Wind Harmer
13.779
960981AF2-389 GEN
Solar/Wind Harmer
1.96
957891AF2-083 GEN
Solar/Wind Harmer
4.37
961051AF2-396 GEN
Solar/Wind Harmer
20.497
961051AF2-396 GEN
Solar/Wind Harmer
9.534
270526AF1-158 GEN
Solar/Wind Harmer
5.655
964611AG1-324 GEN
Solar/Wind Harmer
1.464
964611AG1-324 GEN
Solar/Wind Harmer
0.65
24379505HDWTR1G C
Solar/Wind Harmer
9.79
270209AC1-174_GEN
Solar/Wind Harmer
6.909
926881AC1-175 GEN
Solar/Wind Harmer
6.909
24441505OLIV SLR
Solar/Wind Harmer
0.165
270201AC2-176 GEN
Solar/Wind Harmer
6.321
965681AG1-436 GEN
Solar/Wind Harmer
14.967
965791AG1-447 GEN
Solar/Wind Harmer
7.657
246938BC-WTG3
Solar/Wind Harmer
4.73
246937BC-WTG2
Solar/Wind Harmer
4.65
247621Y3-024
Adder
0.286
270007AE1-245 C
Solar/Wind Harmer
7.028
270383AD1-128 GEN
Solar/Wind Harmer
6.977
274808UNIV PK N;4U
Adder
5.518
942801AE2-298 GEN
Solar/Wind Harmer
1.657
274803UNIV PARK;6U
Adder
6.37
274770LINCOLN ;1U
Adder
6.747
274771LINCOLN ;2U
Adder
6.747
274888KELLY CRK;1U
Solar/Wind Harmer
6.415
274887GEN-1.85
Solar/Wind Harmer
5.792
276843GEN-1.7
Solar/Wind Harmer
0.623
958011AF2-095 GEN
Solar/Wind Harmer
15.647
970321AG2-212 GEN
Solar/Wind Harmer
19.29
972259AH1-714 GEN
Adder
20.537
274674JOLIET 9 ;6U
Adder
16.509
970883AG2-550 GEN
Solar/Wind Harmer
10.712
970885AG2-551 GEN
Solar/Wind Harmer
2.491
274847GR RIDGE ;BU
Solar/Wind Harmer
5.386
945421AF1-207 GEN
Solar/Wind Harmer
14.883
274696ROCKY RD ;4P
Adder
11.924
274695ROCKY RD ;2P
Adder
11.649
274693ROCKY RD ;1P
Adder
11.534
274697ROCKY RD ;3P
Adder
3.165
274683WAUKEGAN ;8U
Adder
22.024
274683WAUKEGAN ;8U
Adder
18.565
274764LEE CO EC;5U
Adder
9.321
274765LEE CO EC;6U
Adder
9.321
274762LEE CO EC;3U
Adder
9.299
274763LEE CO EC;4U
Adder
9.211
972267AH1-718 GEN
Adder
4.123
24728805RICHG1
Adder
3.034
24728905RICHG2
Adder
3.034
270471AD2-092_GEN
Solar/Wind Helper
1.076
946101AF1-275 GEN
Solar/Wind Helper
0.301
957841AF2-078 GEN
Solar/Wind Harmer
2.133
274723RIVER EC ;12
Adder
19.991
958381AF2-132 GEN
Solar/Wind Harmer
10.079
964861AG1-349 GEN
Solar/Wind Harmer
8.717
971917AH1-482 GEN
Solar/Wind Harmer
10.06
274812UNIV PK N;8U
Adder
5.542
276164X3-005 C
Solar/Wind Harmer
0.775
274801UNIV PARK;4U
Adder
6.347
972207SS24-0001
Solar/Wind Harmer
23.99
274773LINCOLN ;4U
Adder
6.747
274774LINCOLN ;5U
Adder
6.747
276776AD2-060 GEN
Solar/Wind Harmer
0.459
940581AE2-045 GEN
Solar/Wind Harmer
11.063
971605AH1-302 GEN
Solar/Wind Harmer
9.46
970245AG2-165 GEN
Solar/Wind Harmer
19.29
274676JOLIET 29;8U
Adder
32.967
941551AE2-152 GEN
Solar/Wind Harmer
4.871
274674JOLIET 9 ;6U
Adder
16.509
274732ELWOOD EC;7P
Adder
17.624
274871GR RIDGE ;2U
Solar/Wind Harmer
8.188
274745AC1-111 GEN9
Adder
5.907
274682WAUKEGAN ;7U
Adder
18.807
274828WAUKEGAN ;BP
Adder
11.544
274822ROCKFORD ;11
Adder
19.937
972235AH1-702 GEN1
Adder
2.555
274761LEE CO EC;2U
Adder
9.299
274766LEE CO EC;7U
Adder
9.189
24728605AND G2
Adder
3.693
972301AH1-735 GEN
Adder
4.399
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
0.148
270349AD2-093_GEN
Solar/Wind Helper
1.076
944201AF1-088_MTX
Adder
86.769
957141AF2-008_MTX
Adder
43.385
990497J1323
External Queue
1.917611837387085
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.192
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.594
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.211
MECLTFEXP_MEC->PJM
CLTF
14.346
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.552
LAGNLTFEXP_LAGN->PJM
CLTF
8.254
TVALTFEXP_TVA->PJM
CLTF
3.263
NYPJM->LTFIMP_NY
CLTF
1.999
LGEELTFEXP_LGEE->PJM
CLTF
3.213
WECLTFEXP_WEC->PJM
CLTF
3.867
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.533
AG2-052LTFEXP_AG2-052->PJM
LTF
0.256
AH1-155LTFEXP_AH1-155->PJM
LTF
0.384

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7442_05SORENS 765_K2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7442_05SORENS 765_K2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.09 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3595.31
MW Contribution:10.72
Bus #Bus NameTypeMW Contribution
960861AF2-377 GEN
50/50
3.377
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
69.966
270043AE2-236 GEN
Solar/Wind Harmer
10.785
959331AF2-224 GEN
Solar/Wind Harmer
18.199
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
49.401
270191TR4_S_V150
Solar/Wind Harmer
4.354
270247TR4_N_V136
Solar/Wind Harmer
1.235
958821AF2-173 GEN
Solar/Wind Harmer
19.364
270004AE1-209 GEN
Solar/Wind Harmer
7.559
971617AH1-308 GEN
Solar/Wind Harmer
7.972
247643Z2-116 C
Solar/Wind Harmer
0.093
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
10.676
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
18.804
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.079
270437AC2-090 C
Solar/Wind Harmer
6.916
270044AE2-322 C
Solar/Wind Harmer
1.618
270404AC1-167 GEN
Solar/Wind Harmer
1.347
962031AG1-047 GEN
Solar/Wind Harmer
3.717
957741AF2-068 GEN
Solar/Wind Harmer
18.448
24441205WTRV SLR C
Solar/Wind Harmer
0.165
270258AD1-119 GEN
Solar/Wind Harmer
3.407
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.542
958091AF2-103 GEN
Solar/Wind Harmer
0.191
270535AF1-215 GEN1
Solar/Wind Harmer
5.131
972231SS25-0005
Solar/Wind Harmer
10.68
972181SS23-001
Solar/Wind Harmer
6.675
274752CRETE EC ;2U
Adder
5.501
274753CRETE EC ;3U
Adder
5.501
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
10.08
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.449
958711AF2-162 GEN
Solar/Wind Harmer
1.798
965101AG1-375 GEN
Solar/Wind Harmer
17.236
945581AF1-223 GEN
Solar/Wind Harmer
7.355
963791AG1-232 GEN
Solar/Wind Harmer
21.4
965041AG1-368 GEN
Solar/Wind Harmer
15.694
965051AG1-369 GEN
Solar/Wind Harmer
7.247
270024AE2-089 GEN
Solar/Wind Harmer
6.436
970115AG2-085 GEN
Solar/Wind Harmer
5.224
971771AH1-392 GEN
Solar/Wind Harmer
11.55
270594AE1-207 GEN
Solar/Wind Harmer
18.557
944161AF1-084 GEN
Solar/Wind Harmer
2.773
971347AH1-153 GEN
Solar/Wind Harmer
18.804
965461AG1-414 GEN
Solar/Wind Harmer
2.837
970289AG2-191 GEN
Solar/Wind Harmer
2.377
270240V3-007_GEN2
Solar/Wind Harmer
7.664
961761AG1-017 GEN
Solar/Wind Harmer
0.526
971769AH1-391 GEN
Solar/Wind Harmer
12.286
24725505WLD G2 C
Solar/Wind Harmer
4.756
24699105WLD G1 C
Solar/Wind Harmer
4.7
960681AF2-359 GEN
Solar/Wind Harmer
4.511
957201AF2-014 GEN
Solar/Wind Harmer
5.38
270435AC2-044 GEN
Solar/Wind Harmer
2.373
247607V1-011 GEN
Solar/Wind Harmer
4.68
971549AH1-272 GEN
Solar/Wind Harmer
21.784
270536AF1-215 GEN2
Solar/Wind Harmer
5.131
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
9.994
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
6.786
274776LINCOLN ;7U
Adder
6.786
274777LINCOLN ;8U
Adder
6.786
960591AF2-350 GEN
Solar/Wind Harmer
10.912
972227AH1-698 GEN1
Adder
2.835
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
5.487
970833AG2-524 GEN
Solar/Wind Harmer
9.348
970833AG2-524 GEN
Solar/Wind Harmer
4.348
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
274823ROCKFORD ;21
Adder
19.887
270054AF2-122 C O1
Solar/Wind Helper
0.778
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
18.199
944541AF1-119 GEN
Solar/Wind Harmer
7.443
960971AF2-388 GEN
Solar/Wind Harmer
19.424
942221AE2-234 GEN
Solar/Wind Harmer
1.156
270599AE1-208 GEN
Solar/Wind Harmer
11.735
270031AE2-169
Solar/Wind Harmer
11.735
270216AD2-079_GEN
Solar/Wind Harmer
0.814
960441AF2-335 GEN
Solar/Wind Harmer
13.06
970825AG2-519 GEN
Solar/Wind Harmer
13.786
960981AF2-389 GEN
Solar/Wind Harmer
1.943
957891AF2-083 GEN
Solar/Wind Harmer
4.334
961051AF2-396 GEN
Solar/Wind Harmer
20.314
961051AF2-396 GEN
Solar/Wind Harmer
9.449
964611AG1-324 GEN
Solar/Wind Harmer
1.464
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
5.631
24379505HDWTR1G C
Solar/Wind Harmer
9.795
270209AC1-174_GEN
Solar/Wind Harmer
6.913
926881AC1-175 GEN
Solar/Wind Harmer
6.913
270201AC2-176 GEN
Solar/Wind Harmer
6.323
24441505OLIV SLR
Solar/Wind Harmer
0.165
965681AG1-436 GEN
Solar/Wind Harmer
14.927
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
4.722
246937BC-WTG2
Solar/Wind Harmer
4.642
270007AE1-245 C
Solar/Wind Harmer
7.017
270383AD1-128 GEN
Solar/Wind Harmer
6.981
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
6.786
274771LINCOLN ;2U
Adder
6.786
942801AE2-298 GEN
Solar/Wind Harmer
1.654
970321AG2-212 GEN
Solar/Wind Harmer
19.508
274888KELLY CRK;1U
Solar/Wind Harmer
6.442
274887GEN-1.85
Solar/Wind Harmer
5.816
276843GEN-1.7
Solar/Wind Harmer
0.626
958011AF2-095 GEN
Solar/Wind Harmer
15.713
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
10.716
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
5.412
945421AF1-207 GEN
Solar/Wind Harmer
14.915
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
972267AH1-718 GEN
Adder
4.143
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
957841AF2-078 GEN
Solar/Wind Harmer
2.137
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.037
965011AG1-365 GEN
Solar/Wind Harmer
18.199
965651AG1-433 GEN
Solar/Wind Harmer
9.712
958861AF2-177 GEN
Solar/Wind Harmer
18.84
945371AF1-202 GEN
Solar/Wind Harmer
11.315
944231AF1-091 GEN
Solar/Wind Harmer
5.785
270063AE2-323 C
Solar/Wind Harmer
3.359
247521TR3_G114
Solar/Wind Harmer
4.88
270246TR4_N_V150
Solar/Wind Harmer
1.235
24695305TIMB G C
Solar/Wind Harmer
7.775
270005AE1-210 C O1
Solar/Wind Harmer
7.559
965031AG1-367 GEN
Solar/Wind Harmer
13.832
970825AG2-519 GEN
Solar/Wind Harmer
3.076
945111AF1-176 GEN
Solar/Wind Harmer
23.221
270505AE1-170 C O1
Solar/Wind Harmer
19.191
270449AD2-020 GEN
Solar/Wind Harmer
3.551
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.626
965421AG1-410 GEN
Solar/Wind Harmer
37.41
942081AE2-220 GEN
Solar/Wind Harmer
7.919
270239V3-007_GEN1
Solar/Wind Harmer
2.131
276903AD2-071 C
Solar/Wind Harmer
12.055
246936BC-WTG1
Solar/Wind Harmer
4.642
270489AE1-102 GEN1
Solar/Wind Harmer
1.542
970373AG2-245 GEN
Solar/Wind Harmer
24.151
247536S-71 GEN
Solar/Wind Harmer
4.626
270055AF2-134 C O1
Solar/Wind Harmer
3.42
274751CRETE EC ;1U
Adder
5.501
274754CRETE EC ;4U
Adder
5.501
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
10.08
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
8.718
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0.778
972207SS24-0001
Solar/Wind Harmer
24.127
274773LINCOLN ;4U
Adder
6.786
274774LINCOLN ;5U
Adder
6.786
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
19.508
276776AD2-060 GEN
Solar/Wind Harmer
0.461
940581AE2-045 GEN
Solar/Wind Harmer
11.076
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
4.894
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
8.227
274745AC1-111 GEN9
Adder
5.936
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
6.618
274772LINCOLN ;3U
Adder
6.786
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
19.508
970517AG2-330 GEN
Solar/Wind Harmer
17.693
276772AC2-154 GEN
Solar/Wind Harmer
3.043
276806AD2-047 C O1
Solar/Wind Harmer
11.673
970941AG2-585 GEN
Solar/Wind Harmer
13.64
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
31.315
939351AE1-166 GEN
Solar/Wind Harmer
6.398
970707AG2-453 GEN
Solar/Wind Harmer
30.212
276893AG1-478 C
Solar/Wind Harmer
0.45
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
274682WAUKEGAN ;7U
Adder
18.895
972236AH1-702 GEN2
Adder
2.232
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
23906502RICHG2&3
Adder
0.869
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
24728605AND G2
Adder
3.7
972301AH1-735 GEN
Adder
4.377
23906402RICHG1
Adder
0.875
23906502RICHG2&3
Adder
0.869
970091AG2-072 GEN
Adder
0.149
270349AD2-093_GEN
Solar/Wind Helper
1.077
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
43.559
990497J1323
External Queue
1.901388168334961
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P4_#7444_05DUMONT 765_A2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P4_#7444_05DUMONT 765_A2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3589.56
MW Contribution:10.73
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
3.66
960851AF2-376 GEN
50/50
3.295
24727105RPMNG2
50/50
1.312
24641605TWIN BRNCH
50/50
0.024
944531AF1-118 GEN
Solar/Wind Harmer
70.092
270043AE2-236 GEN
Solar/Wind Harmer
10.813
959331AF2-224 GEN
Solar/Wind Harmer
18.246
965021AG1-366 GEN
Solar/Wind Harmer
4.243
970031AG2-029 GEN
Solar/Wind Harmer
49.558
270191TR4_S_V150
Solar/Wind Harmer
4.366
270247TR4_N_V136
Solar/Wind Harmer
1.238
958821AF2-173 GEN
Solar/Wind Harmer
19.383
270004AE1-209 GEN
Solar/Wind Harmer
7.567
971617AH1-308 GEN
Solar/Wind Harmer
7.985
247643Z2-116 C
Solar/Wind Harmer
0.094
945111AF1-176 GEN
Solar/Wind Harmer
7.407
946031AF1-268 GEN
Solar/Wind Harmer
10.685
970349AG2-230 GEN
Solar/Wind Harmer
19.196
24642205MAYFLWER
Adder
0.812
970289AG2-191 GEN
Solar/Wind Harmer
0.959
970291AG2-192 GEN
Solar/Wind Harmer
0.872
270437AC2-090 C
Solar/Wind Harmer
6.922
247642Z2-115 C
Solar/Wind Harmer
0.079
270044AE2-322 C
Solar/Wind Harmer
1.623
270404AC1-167 GEN
Solar/Wind Harmer
1.352
24441205WTRV SLR C
Solar/Wind Harmer
0.166
962031AG1-047 GEN
Solar/Wind Harmer
3.722
957741AF2-068 GEN
Solar/Wind Harmer
18.469
270258AD1-119 GEN
Solar/Wind Harmer
3.418
247604X1-042
Adder
0.504
270491AE1-102 GEN2
Solar/Wind Harmer
1.547
958091AF2-103 GEN
Solar/Wind Harmer
0.192
270535AF1-215 GEN1
Solar/Wind Harmer
5.155
972231SS25-0005
Solar/Wind Harmer
10.698
972181SS23-001
Solar/Wind Harmer
6.686
274752CRETE EC ;2U
Adder
5.51
274753CRETE EC ;3U
Adder
5.51
274724RIVER EC ;11
Adder
19.836
964401AG1-302 GEN
Solar/Wind Harmer
10.112
959141AF2-205 GEN
Solar/Wind Harmer
6.631
274802UNIV PARK;5U
Adder
6.39
274826FISK ;BP
Adder
11.978
274800UNIV PARK;3U
Adder
6.366
972038AH1-567 GEN2
Adder
0.398
274772LINCOLN ;3U
Adder
6.754
276772AC2-154 GEN
Solar/Wind Harmer
3.039
276806AD2-047 C O1
Solar/Wind Harmer
11.656
970941AG2-585 GEN
Solar/Wind Harmer
13.62
972228AH1-698 GEN2
Adder
4.019
274676JOLIET 29;8U
Adder
31.865
276897AD1-100 C
Solar/Wind Harmer
31.229
939351AE1-166 GEN
Solar/Wind Harmer
6.381
276893AG1-478 C
Solar/Wind Harmer
0.449
971599AH1-298 GEN
50/50
20.277
24729505KEY G4
50/50
13.379
24727205RPMNG3
50/50
1.301
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
28.477
958711AF2-162 GEN
Solar/Wind Harmer
1.801
965101AG1-375 GEN
Solar/Wind Harmer
17.262
945581AF1-223 GEN
Solar/Wind Harmer
7.365
963791AG1-232 GEN
Solar/Wind Harmer
21.446
965041AG1-368 GEN
Solar/Wind Harmer
15.736
965051AG1-369 GEN
Solar/Wind Harmer
7.267
270024AE2-089 GEN
Solar/Wind Harmer
6.446
970115AG2-085 GEN
Solar/Wind Harmer
5.227
971771AH1-392 GEN
Solar/Wind Harmer
11.649
971347AH1-153 GEN
Solar/Wind Harmer
19.196
944161AF1-084 GEN
Solar/Wind Harmer
2.789
270594AE1-207 GEN
Solar/Wind Harmer
18.539
965461AG1-414 GEN
Solar/Wind Harmer
2.832
970289AG2-191 GEN
Solar/Wind Harmer
2.373
270240V3-007_GEN2
Solar/Wind Harmer
7.67
971769AH1-391 GEN
Solar/Wind Harmer
12.39
961761AG1-017 GEN
Solar/Wind Harmer
0.527
960681AF2-359 GEN
Solar/Wind Harmer
4.552
24725505WLD G2 C
Solar/Wind Harmer
4.752
24699105WLD G1 C
Solar/Wind Harmer
4.696
957201AF2-014 GEN
Solar/Wind Harmer
5.397
270435AC2-044 GEN
Solar/Wind Harmer
2.38
971549AH1-272 GEN
Solar/Wind Harmer
21.971
247607V1-011 GEN
Solar/Wind Harmer
4.695
270536AF1-215 GEN2
Solar/Wind Harmer
5.155
274814UNIV PK N;0U
Adder
5.61
274807UNIV PK N;3U
Adder
5.598
274805UNIV PK N;1U
Adder
5.574
274811UNIV PK N;7U
Adder
5.562
958391AF2-133 GEN
Solar/Wind Harmer
10.019
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.489
274775LINCOLN ;6U
Adder
6.754
274776LINCOLN ;7U
Adder
6.754
274777LINCOLN ;8U
Adder
6.754
960591AF2-350 GEN
Solar/Wind Harmer
10.896
972227AH1-698 GEN1
Adder
2.829
274687WILL CNTY;4U
Adder
30.181
274687WILL CNTY;4U
Adder
30.181
274675JOLIET 29;7U
Adder
33.046
274675JOLIET 29;7U
Adder
31.866
274728ELWOOD EC;5P
Adder
17.665
274731ELWOOD EC;2P
Adder
17.664
274733ELWOOD EC;3P
Adder
17.664
274735ELWOOD EC;4P
Adder
17.664
270543AE2-219 C
Solar/Wind Harmer
5.493
970833AG2-524 GEN
Solar/Wind Harmer
9.321
24729405KEY G3
50/50
0.73
24729305KEY G2
50/50
0.718
24729205KEY G1
50/50
0.714
970615AG2-402 GEN
50/50
4.243
247620Y3-023
50/50
0.692
970611AG2-400 GEN
Solar/Wind Harmer
18.246
944541AF1-119 GEN
Solar/Wind Harmer
7.455
960971AF2-388 GEN
Solar/Wind Harmer
19.454
942221AE2-234 GEN
Solar/Wind Harmer
1.157
270599AE1-208 GEN
Solar/Wind Harmer
11.746
270031AE2-169
Solar/Wind Harmer
11.746
270216AD2-079_GEN
Solar/Wind Harmer
0.821
960441AF2-335 GEN
Solar/Wind Harmer
13.068
970825AG2-519 GEN
Solar/Wind Harmer
13.796
960981AF2-389 GEN
Solar/Wind Harmer
1.957
957891AF2-083 GEN
Solar/Wind Harmer
4.363
961051AF2-396 GEN
Solar/Wind Harmer
20.443
961051AF2-396 GEN
Solar/Wind Harmer
9.508
270526AF1-158 GEN
Solar/Wind Harmer
5.679
964611AG1-324 GEN
Solar/Wind Harmer
1.466
964611AG1-324 GEN
Solar/Wind Harmer
0.651
24379505HDWTR1G C
Solar/Wind Harmer
9.803
270209AC1-174_GEN
Solar/Wind Harmer
6.918
926881AC1-175 GEN
Solar/Wind Harmer
6.918
24441505OLIV SLR
Solar/Wind Harmer
0.166
270201AC2-176 GEN
Solar/Wind Harmer
6.33
965681AG1-436 GEN
Solar/Wind Harmer
15.06
965791AG1-447 GEN
Solar/Wind Harmer
7.705
246938BC-WTG3
Solar/Wind Harmer
4.737
246937BC-WTG2
Solar/Wind Harmer
4.657
247621Y3-024
Adder
0.287
270007AE1-245 C
Solar/Wind Harmer
7.038
270383AD1-128 GEN
Solar/Wind Harmer
6.986
274808UNIV PK N;4U
Adder
5.537
942801AE2-298 GEN
Solar/Wind Harmer
1.659
274803UNIV PARK;6U
Adder
6.39
274770LINCOLN ;1U
Adder
6.754
274771LINCOLN ;2U
Adder
6.754
274888KELLY CRK;1U
Solar/Wind Harmer
6.433
274887GEN-1.85
Solar/Wind Harmer
5.808
276843GEN-1.7
Solar/Wind Harmer
0.625
958011AF2-095 GEN
Solar/Wind Harmer
15.69
972259AH1-714 GEN
Adder
20.574
274674JOLIET 9 ;6U
Adder
16.547
970321AG2-212 GEN
Solar/Wind Harmer
19.169
970883AG2-550 GEN
Solar/Wind Harmer
10.727
970885AG2-551 GEN
Solar/Wind Harmer
2.495
274847GR RIDGE ;BU
Solar/Wind Harmer
5.396
945421AF1-207 GEN
Solar/Wind Harmer
14.904
274695ROCKY RD ;2P
Adder
11.671
274693ROCKY RD ;1P
Adder
11.556
274697ROCKY RD ;3P
Adder
3.17
274696ROCKY RD ;4P
Adder
11.946
274683WAUKEGAN ;8U
Adder
22.068
274683WAUKEGAN ;8U
Adder
18.602
274764LEE CO EC;5U
Adder
9.338
274765LEE CO EC;6U
Adder
9.338
274762LEE CO EC;3U
Adder
9.316
274763LEE CO EC;4U
Adder
9.228
972267AH1-718 GEN
Adder
4.131
24728805RICHG1
Adder
3.038
24728905RICHG2
Adder
3.038
270471AD2-092_GEN
Solar/Wind Helper
1.074
946101AF1-275 GEN
Solar/Wind Helper
0.3
957841AF2-078 GEN
Solar/Wind Harmer
2.136
970707AG2-453 GEN
Solar/Wind Harmer
30.091
274730ELWOOD EC;6P
Adder
17.665
274734ELWOOD EC;8P
Adder
17.665
274736ELWOOD EC;9P
Adder
17.665
274729ELWOOD EC;1P
Adder
17.664
970513AG2-328 GEN
Solar/Wind Harmer
19.169
970517AG2-330 GEN
Solar/Wind Harmer
17.386
274682WAUKEGAN ;7U
Adder
18.845
972236AH1-702 GEN2
Adder
2.226
274760LEE CO EC;1U
Adder
9.316
274767LEE CO EC;8U
Adder
9.206
24728705AND G3
Adder
7.73
24728505AND G1
Adder
3.696
23906502RICHG2&3
Adder
0.873
970833AG2-524 GEN
Solar/Wind Harmer
4.335
274746AC1-111 G10
Adder
5.917
274744AC1-111 GEN8
Adder
5.917
274823ROCKFORD ;21
Adder
19.829
270054AF2-122 C O1
Solar/Wind Helper
0.776
270284AF1-227 GEN1
Solar/Wind Helper
1.163
270286AF1-227 GEN2
Solar/Wind Helper
0.426
270287AF1-227 GEN3
Solar/Wind Helper
0.426
270520AE2-214 GEN
Solar/Wind Helper
2.396
960861AF2-377 GEN
50/50
3.387
970521AG2-332 GEN
50/50
16.194
24639705ELKHART HY
50/50
0.225
24727005RPMNG1
50/50
1.307
960791AF2-370 GEN
50/50
3.039
965011AG1-365 GEN
Solar/Wind Harmer
18.246
965651AG1-433 GEN
Solar/Wind Harmer
9.727
958861AF2-177 GEN
Solar/Wind Harmer
18.868
945371AF1-202 GEN
Solar/Wind Harmer
11.33
944231AF1-091 GEN
Solar/Wind Harmer
5.803
270063AE2-323 C
Solar/Wind Harmer
3.379
247521TR3_G114
Solar/Wind Harmer
4.894
270246TR4_N_V150
Solar/Wind Harmer
1.238
24695305TIMB G C
Solar/Wind Harmer
7.798
270005AE1-210 C O1
Solar/Wind Harmer
7.567
965031AG1-367 GEN
Solar/Wind Harmer
13.845
945111AF1-176 GEN
Solar/Wind Harmer
23.371
970825AG2-519 GEN
Solar/Wind Harmer
3.078
270505AE1-170 C O1
Solar/Wind Harmer
19.319
270449AD2-020 GEN
Solar/Wind Harmer
3.573
943021AE2-325 GEN
Solar/Wind Harmer
4.643
270032AE2-172
Solar/Wind Harmer
5.867
965421AG1-410 GEN
Solar/Wind Harmer
37.525
970291AG2-192 GEN
Solar/Wind Harmer
1.624
942081AE2-220 GEN
Solar/Wind Harmer
7.926
270239V3-007_GEN1
Solar/Wind Harmer
2.133
276903AD2-071 C
Solar/Wind Harmer
12.042
246936BC-WTG1
Solar/Wind Harmer
4.657
270489AE1-102 GEN1
Solar/Wind Harmer
1.547
970373AG2-245 GEN
Solar/Wind Harmer
24.301
247536S-71 GEN
Solar/Wind Harmer
4.631
270055AF2-134 C O1
Solar/Wind Harmer
3.436
274751CRETE EC ;1U
Adder
5.51
274754CRETE EC ;4U
Adder
5.51
274723RIVER EC ;12
Adder
20.078
958381AF2-132 GEN
Solar/Wind Harmer
10.112
964861AG1-349 GEN
Solar/Wind Harmer
8.745
971917AH1-482 GEN
Solar/Wind Harmer
10.092
274812UNIV PK N;8U
Adder
5.562
276164X3-005 C
Solar/Wind Harmer
0.778
274801UNIV PARK;4U
Adder
6.366
972207SS24-0001
Solar/Wind Harmer
24.014
274773LINCOLN ;4U
Adder
6.754
274774LINCOLN ;5U
Adder
6.754
276776AD2-060 GEN
Solar/Wind Harmer
0.461
940581AE2-045 GEN
Solar/Wind Harmer
11.089
971605AH1-302 GEN
Solar/Wind Harmer
9.483
274676JOLIET 29;8U
Adder
33.046
941551AE2-152 GEN
Solar/Wind Harmer
4.881
274674JOLIET 9 ;6U
Adder
16.547
274732ELWOOD EC;7P
Adder
17.665
970245AG2-165 GEN
Solar/Wind Harmer
19.169
274871GR RIDGE ;2U
Solar/Wind Harmer
8.203
274745AC1-111 GEN9
Adder
5.917
274682WAUKEGAN ;7U
Adder
18.845
274828WAUKEGAN ;BP
Adder
11.568
274822ROCKFORD ;11
Adder
19.974
972235AH1-702 GEN1
Adder
2.559
274761LEE CO EC;2U
Adder
9.316
274766LEE CO EC;7U
Adder
9.206
24728605AND G2
Adder
3.696
972301AH1-735 GEN
Adder
4.398
23906402RICHG1
Adder
0.88
23906502RICHG2&3
Adder
0.873
970091AG2-072 GEN
Adder
0.148
270349AD2-093_GEN
Solar/Wind Helper
1.074
944201AF1-088_MTX
Adder
86.826
957141AF2-008_MTX
Adder
43.413
990497J1323
External Queue
1.9195195436477661
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.19
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.576
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.237
MECLTFEXP_MEC->PJM
CLTF
14.373
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.674
LAGNLTFEXP_LAGN->PJM
CLTF
8.272
TVALTFEXP_TVA->PJM
CLTF
3.271
NYPJM->LTFIMP_NY
CLTF
1.996
LGEELTFEXP_LGEE->PJM
CLTF
3.215
WECLTFEXP_WEC->PJM
CLTF
3.875
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.53
AG2-052LTFEXP_AG2-052->PJM
LTF
0.258
AH1-155LTFEXP_AH1-155->PJM
LTF
0.388

Details for 05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer l/o AEP_P1-2_#7442_200545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer
Contingency Name:
AEP_P1-2_#7442_200545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.07 %
Rating:3097.0 MVA
Rating Type:B
MVA to Mitigate:3439.74
MW Contribution:7.48
Bus #Bus NameTypeMW Contribution
970583AG2-370 GEN
50/50
3.65
960851AF2-376 GEN
50/50
3.285
24727105RPMNG2
50/50
1.308
24641605TWIN BRNCH
50/50
0.023
944531AF1-118 GEN
Solar/Wind Harmer
62.505
270043AE2-236 GEN
Solar/Wind Harmer
8.778
959331AF2-224 GEN
Solar/Wind Harmer
8.888
965021AG1-366 GEN
Solar/Wind Harmer
4.232
970031AG2-029 GEN
Solar/Wind Harmer
7.468
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.065
958821AF2-173 GEN
Solar/Wind Harmer
13.51
270004AE1-209 GEN
Solar/Wind Harmer
2.091
971617AH1-308 GEN
Solar/Wind Harmer
7.972
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
7.359
946031AF1-268 GEN
Solar/Wind Harmer
8.54
24642205MAYFLWER
Adder
0.806
970349AG2-230 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
0.96
970291AG2-192 GEN
Solar/Wind Harmer
0.873
247642Z2-115 C
Solar/Wind Harmer
0.004
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
12.871
24441205WTRV SLR C
Solar/Wind Harmer
0
270258AD1-119 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.501
270491AE1-102 GEN2
Solar/Wind Harmer
1.076
270535AF1-215 GEN1
Solar/Wind Harmer
0.01
274752CRETE EC ;2U
Adder
9.273
274753CRETE EC ;3U
Adder
9.273
274724RIVER EC ;11
Adder
19.816
964401AG1-302 GEN
Solar/Wind Harmer
0.001
274802UNIV PARK;5U
Adder
6.395
274826FISK ;BP
Adder
11.989
959141AF2-205 GEN
Solar/Wind Harmer
-0.002
274772LINCOLN ;3U
Adder
9.237
274800UNIV PARK;3U
Adder
6.373
972038AH1-567 GEN2
Adder
0.399
970513AG2-328 GEN
Solar/Wind Harmer
3.303
970517AG2-330 GEN
Solar/Wind Harmer
19.816
276806AD2-047 C O1
Solar/Wind Harmer
4.314
970941AG2-585 GEN
Solar/Wind Harmer
9.516
972228AH1-698 GEN2
Adder
4.027
274676JOLIET 29;8U
Adder
31.93
276897AD1-100 C
Solar/Wind Harmer
0.01
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
970707AG2-453 GEN
Solar/Wind Harmer
24.591
276893AG1-478 C
Solar/Wind Harmer
0.298
274730ELWOOD EC;6P
Adder
17.702
274734ELWOOD EC;8P
Adder
17.702
274736ELWOOD EC;9P
Adder
17.702
274729ELWOOD EC;1P
Adder
17.701
971599AH1-298 GEN
50/50
20.218
24729505KEY G4
50/50
13.356
24727205RPMNG3
50/50
1.297
24653605MOTTVILLE
50/50
0.005
270071AF1-092 GEN
Solar/Wind Harmer
25.362
965101AG1-375 GEN
Solar/Wind Harmer
12.025
945581AF1-223 GEN
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
14.93
965041AG1-368 GEN
Solar/Wind Harmer
10.949
965051AG1-369 GEN
Solar/Wind Harmer
5.056
971609AH1-304 GEN
Solar/Wind Harmer
1.641
270024AE2-089 GEN
Solar/Wind Harmer
0.01
970115AG2-085 GEN
Solar/Wind Harmer
3.655
971771AH1-392 GEN
Solar/Wind Harmer
8.953
971619AH1-309 GEN
Solar/Wind Harmer
4.017
270594AE1-207 GEN
Solar/Wind Harmer
9.866
971347AH1-153 GEN
Solar/Wind Harmer
13.119
970289AG2-191 GEN
Solar/Wind Harmer
1.658
270240V3-007_GEN2
Solar/Wind Harmer
0.003
971769AH1-391 GEN
Solar/Wind Harmer
9.572
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.048
247607V1-011 GEN
Solar/Wind Harmer
0.001
971549AH1-272 GEN
Solar/Wind Harmer
16.964
270536AF1-215 GEN2
Solar/Wind Harmer
0.01
274814UNIV PK N;0U
Adder
5.609
274807UNIV PK N;3U
Adder
5.596
274805UNIV PK N;1U
Adder
5.572
274811UNIV PK N;7U
Adder
5.56
958391AF2-133 GEN
Solar/Wind Harmer
0.001
972037AH1-567 GEN1
Adder
0.201
274827FISK ;RP
Adder
8.497
274775LINCOLN ;6U
Adder
9.237
274776LINCOLN ;7U
Adder
9.237
274777LINCOLN ;8U
Adder
9.237
960591AF2-350 GEN
Solar/Wind Harmer
7.613
972227AH1-698 GEN1
Adder
2.835
971611AH1-305 GEN
Solar/Wind Harmer
4.511
274687WILL CNTY;4U
Adder
30.235
274687WILL CNTY;4U
Adder
30.235
274675JOLIET 29;7U
Adder
33.113
274675JOLIET 29;7U
Adder
31.93
274728ELWOOD EC;5P
Adder
17.702
274731ELWOOD EC;2P
Adder
17.701
274733ELWOOD EC;3P
Adder
17.701
274735ELWOOD EC;4P
Adder
17.701
270543AE2-219 C
Solar/Wind Harmer
0.005
970833AG2-524 GEN
Solar/Wind Harmer
8.217
970833AG2-524 GEN
Solar/Wind Harmer
5.478
274746AC1-111 G10
Adder
5.936
274744AC1-111 GEN8
Adder
5.936
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.002
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
276868AE1-113 GEN
Solar/Wind Harmer
1.457
276882AE2-255 GEN
Solar/Wind Harmer
0.849
971177AH1-047 GEN
Solar/Wind Harmer
4.45
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
971411AH1-196 GEN
Solar/Wind Harmer
10.784
971675AH1-338 GEN
Solar/Wind Harmer
2.801
971171AH1-044 GEN
Solar/Wind Harmer
14.285
274823ROCKFORD ;21
Adder
19.887
970169AG2-114 GEN
Solar/Wind Harmer
7.099
926823AC1-168 GEN
Solar/Wind Harmer
1.205
276612AE2-035 GEN
Solar/Wind Harmer
0.002
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
11.326
961011AF2-392 GEN
Solar/Wind Harmer
4.084
957751AF2-069 GEN
Solar/Wind Harmer
0.229
971029AG2-637 GEN
Solar/Wind Harmer
10.391
276655WTG1_EQ
Solar/Wind Harmer
0.003
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
7.234
941731AE2-173 GEN
Solar/Wind Harmer
5.741
963841AG1-237 GEN
Solar/Wind Harmer
2.984
946321AF1-296 GEN
Solar/Wind Harmer
3.782
971673AH1-337 GEN
Solar/Wind Harmer
4.373
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.236
276848AB2-070 GEN3
Solar/Wind Harmer
0.235
944221AF1-090 GEN
Solar/Wind Harmer
3.489
270297AD1-101 GEN
Solar/Wind Harmer
0.001
945411AF1-206 GEN
Solar/Wind Harmer
0
270054AF2-122 C O1
Solar/Wind Helper
0.778
24729405KEY G3
50/50
0.729
24729305KEY G2
50/50
0.717
24729205KEY G1
50/50
0.713
970615AG2-402 GEN
50/50
4.232
247620Y3-023
50/50
0.687
970611AG2-400 GEN
Solar/Wind Harmer
12.697
970627AG2-408 GEN
Solar/Wind Harmer
3.809
944541AF1-119 GEN
Solar/Wind Harmer
0.831
960971AF2-388 GEN
Solar/Wind Harmer
7.274
942221AE2-234 GEN
Solar/Wind Harmer
0.055
270599AE1-208 GEN
Solar/Wind Harmer
9.209
270031AE2-169
Solar/Wind Harmer
5.525
270216AD2-079_GEN
Solar/Wind Harmer
0.001
960441AF2-335 GEN
Solar/Wind Harmer
9.138
970825AG2-519 GEN
Solar/Wind Harmer
10.102
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
17.858
961051AF2-396 GEN
Solar/Wind Harmer
11.905
971613AH1-306 GEN
Solar/Wind Harmer
4.228
964611AG1-324 GEN
Solar/Wind Harmer
0.65
270526AF1-158 GEN
Solar/Wind Harmer
0.011
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
970623AG2-406 GEN
Solar/Wind Harmer
1.561
965681AG1-436 GEN
Solar/Wind Harmer
10.414
965791AG1-447 GEN
Solar/Wind Harmer
7.637
247621Y3-024
Adder
0.286
246938BC-WTG3
Solar/Wind Harmer
0.3
246937BC-WTG2
Solar/Wind Harmer
0.336
270007AE1-245 C
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
274808UNIV PK N;4U
Adder
5.536
274803UNIV PARK;6U
Adder
6.395
274770LINCOLN ;1U
Adder
9.237
274771LINCOLN ;2U
Adder
9.237
970321AG2-212 GEN
Solar/Wind Harmer
3.303
274888KELLY CRK;1U
Solar/Wind Harmer
0.447
274887GEN-1.85
Solar/Wind Harmer
0.2
276843GEN-1.7
Solar/Wind Harmer
0.246
958011AF2-095 GEN
Solar/Wind Harmer
10.963
972259AH1-714 GEN
Adder
20.637
274674JOLIET 9 ;6U
Adder
16.583
970883AG2-550 GEN
Solar/Wind Harmer
7.476
970885AG2-551 GEN
Solar/Wind Harmer
2.492
274847GR RIDGE ;BU
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.002
958481AF2-142 GEN
Solar/Wind Harmer
11.087
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
274862TOP CROP ;2U
Solar/Wind Harmer
1
971573AH1-285 GEN
Solar/Wind Harmer
1.373
274695ROCKY RD ;2P
Adder
11.705
274693ROCKY RD ;1P
Adder
11.59
274697ROCKY RD ;3P
Adder
3.18
274696ROCKY RD ;4P
Adder
11.982
274683WAUKEGAN ;8U
Adder
22.127
274683WAUKEGAN ;8U
Adder
18.652
958491AF2-143 GEN
Solar/Wind Harmer
10.958
962691AG1-118 GEN
Solar/Wind Harmer
21.835
970921AG2-575 GEN
Solar/Wind Harmer
7.261
970921AG2-575 GEN
Solar/Wind Harmer
2.42
274879MINONK ;1U
Solar/Wind Harmer
0.306
942991AE2-321 GEN
Solar/Wind Harmer
8.062
276872AE1-163_GEN1
Solar/Wind Harmer
0.002
971333AH1-146 GEN
Solar/Wind Harmer
14.365
971335AH1-147 GEN
Solar/Wind Harmer
14.365
971341AH1-150 GEN
Solar/Wind Harmer
14.285
971343AH1-151 GEN
Solar/Wind Harmer
14.285
274856ECOGROVE ;U1
Solar/Wind Harmer
0.167
276611AD2-172 GEN
Solar/Wind Harmer
0.002
966841AG1-555 GEN
Solar/Wind Harmer
0.798
938861AE1-114 GEN
Solar/Wind Harmer
3.985
274764LEE CO EC;5U
Adder
9.365
274765LEE CO EC;6U
Adder
9.365
274762LEE CO EC;3U
Adder
9.343
274763LEE CO EC;4U
Adder
9.255
276603SUBLETTE C
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.273
276646AC1-214 GEN2
Solar/Wind Harmer
0.273
972267AH1-718 GEN
Adder
4.143
276741O09 GEN1
Solar/Wind Harmer
0.247
276708O09 GEN2
Solar/Wind Harmer
0.247
276782AC1-033 GEN
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
2.261
970241AG2-163 GEN
Solar/Wind Harmer
3.925
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
6.577
276916AD2-100_GEN
Solar/Wind Harmer
12.826
276911AD2-131_GEN
Solar/Wind Harmer
0.845
970621AG2-405 GEN
Solar/Wind Harmer
1.049
24728805RICHG1
Adder
3.037
24728905RICHG2
Adder
3.037
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.833
970239AG2-162 GEN
Solar/Wind Harmer
1.162
241996AE2-282_GEN
Solar/Wind Harmer
0.002
270471AD2-092_GEN
Solar/Wind Helper
1.077
946101AF1-275 GEN
Solar/Wind Helper
0.301
270284AF1-227 GEN1
Solar/Wind Helper
1.167
270286AF1-227 GEN2
Solar/Wind Helper
0.428
270287AF1-227 GEN3
Solar/Wind Helper
0.428
270520AE2-214 GEN
Solar/Wind Helper
2.4
960861AF2-377 GEN
50/50
3.377
970521AG2-332 GEN
50/50
16.09
24639705ELKHART HY
50/50
0.224
24727005RPMNG1
50/50
1.303
960791AF2-370 GEN
50/50
3.046
965011AG1-365 GEN
Solar/Wind Harmer
12.697
965651AG1-433 GEN
Solar/Wind Harmer
3.637
958861AF2-177 GEN
Solar/Wind Harmer
5.211
945371AF1-202 GEN
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
2.856
270063AE2-323 C
Solar/Wind Harmer
0.009
247521TR3_G114
Solar/Wind Harmer
0.369
270246TR4_N_V150
Solar/Wind Harmer
0.065
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.091
965031AG1-367 GEN
Solar/Wind Harmer
9.65
970825AG2-519 GEN
Solar/Wind Harmer
3.236
945111AF1-176 GEN
Solar/Wind Harmer
16.201
270505AE1-170 C O1
Solar/Wind Harmer
9.372
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
4.614
270032AE2-172
Solar/Wind Harmer
5.873
970291AG2-192 GEN
Solar/Wind Harmer
1.135
965421AG1-410 GEN
Solar/Wind Harmer
26.1
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.336
276903AD2-071 C
Solar/Wind Harmer
9.392
246936BC-WTG1
Solar/Wind Harmer
0.336
270489AE1-102 GEN1
Solar/Wind Harmer
1.076
970373AG2-245 GEN
Solar/Wind Harmer
16.85
247536S-71 GEN
Solar/Wind Harmer
0.321
270055AF2-134 C O1
Solar/Wind Harmer
0.006
274751CRETE EC ;1U
Adder
9.273
274754CRETE EC ;4U
Adder
9.273
274723RIVER EC ;12
Adder
20.057
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274812UNIV PK N;8U
Adder
5.56
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
10.061
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
9.237
274774LINCOLN ;5U
Adder
9.237
274801UNIV PARK;4U
Adder
6.373
970245AG2-165 GEN
Solar/Wind Harmer
3.303
276776AD2-060 GEN
Solar/Wind Harmer
0.795
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
9.471
274676JOLIET 29;8U
Adder
33.113
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
16.583
274732ELWOOD EC;7P
Adder
17.702
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
274745AC1-111 GEN9
Adder
5.936
276691AA1-018 GEN1
Solar/Wind Harmer
0.895
274682WAUKEGAN ;7U
Adder
18.895
274828WAUKEGAN ;BP
Adder
11.599
24791305MDL-5G
Solar/Wind Harmer
0.001
939401AE1-172 GEN
Solar/Wind Harmer
5.451
276901AD2-066 C O1
Solar/Wind Harmer
0.007
962781AG1-127 GEN
Solar/Wind Harmer
6.91
274872LEEDK;1U
Solar/Wind Harmer
0.004
971997AH1-543 GEN
Solar/Wind Harmer
3.793
276876AE1-163_GEN2
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.129
957471AF2-041 GEN
Solar/Wind Harmer
21.427
959081AF2-199 GEN
Solar/Wind Harmer
7.142
971067AG2-660 GEN
Solar/Wind Harmer
2.381
274822ROCKFORD ;11
Adder
20.032
972235AH1-702 GEN1
Adder
2.567
970569AG2-363 GEN
Solar/Wind Harmer
21.31
970819AG2-516 GEN
Solar/Wind Harmer
8.5
971475AH1-234 GEN
Solar/Wind Harmer
3.428
24385905FR-11G C
Solar/Wind Harmer
0.002
24387305FR-4G C
Solar/Wind Harmer
0.003
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
9.343
274766LEE CO EC;7U
Adder
9.233
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.232
276726Z2-087_GEN
Solar/Wind Harmer
0.002
939741AE1-205 GEN
Solar/Wind Harmer
9.645
274854TWINGROVE;U2
Solar/Wind Harmer
0.003
24728605AND G2
Adder
3.7
963741AG1-226 GEN
Solar/Wind Harmer
15.923
970773AG2-487 GEN
Solar/Wind Harmer
1.185
972175AH1-670 GEN
Solar/Wind Harmer
5.466
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
2.507
276615X2-022 GEN
Solar/Wind Harmer
0.067
965911AG1-460 GEN
Solar/Wind Harmer
1.231
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
3.324
241808AF1-120 C
Solar/Wind Harmer
0.001
241858AF1-205_GEN
Solar/Wind Harmer
1.342
241840AF1-064_GEN
Solar/Wind Harmer
0.001
270349AD2-093_GEN
Solar/Wind Helper
1.077
943121AE2-341 GEN
Solar/Wind Harmer
12.419
943591AF1-030 GEN
Solar/Wind Harmer
8.259
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
18.895
276805AD2-038 GEN
Solar/Wind Harmer
0.002
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
7.294
274872LEEDK;1U
Solar/Wind Harmer
0.266
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.766
276889AE2-281 GEN
Solar/Wind Harmer
0.001
274855GSG-6 ;RU
Solar/Wind Harmer
0.263
274850MENDOTA H;RU
Solar/Wind Harmer
0.085
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.129
959091AF2-200 GEN
Solar/Wind Harmer
14.285
972236AH1-702 GEN2
Adder
2.232
970571AG2-364 GEN
Solar/Wind Harmer
14.206
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
9.343
274767LEE CO EC;8U
Adder
9.233
276157O29GEN1
Solar/Wind Harmer
1.121
274878BISHOP HL;2U
Solar/Wind Harmer
0.232
942111AE2-223 GEN
Solar/Wind Harmer
2.239
274853TWINGROVE;U1
Solar/Wind Harmer
0.003
965091AG1-374 GEN
Solar/Wind Harmer
20.348
959611AF2-252 GEN
Solar/Wind Harmer
2.261
24728705AND G3
Adder
7.738
24728505AND G1
Adder
3.7
965931AG1-462 GEN
Solar/Wind Harmer
17.128
270356AE2-297 GEN
Solar/Wind Harmer
0.009
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
2.985
276668AB2-070 GEN1
Solar/Wind Harmer
0.236
276621W2-048 GEN
Solar/Wind Harmer
0.321
276838X2-022 GEN2
Solar/Wind Harmer
0.358
970193AG2-126 GEN
Solar/Wind Harmer
9.285
942481AE2-261 GEN
Solar/Wind Harmer
18.401
270222AC2-111 GEN
Solar/Wind Harmer
2.367
970243AG2-164 GEN
Solar/Wind Harmer
2.719
970519AG2-331 GEN
Solar/Wind Harmer
12.086
970699AG2-449 GEN
Solar/Wind Harmer
1.162
270541AE2-072 C
Solar/Wind Harmer
0.005
241832AE2-181_GEN
Solar/Wind Harmer
0.001
958321AF2-126 GEN
Solar/Wind Harmer
0.444
944201AF1-088_MTX
Adder
87.117
957141AF2-008_MTX
Adder
29.672
990792J1392
External Queue
6.540774822235107
991297J1743
External Queue
3.431180715560913
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.188
CBM West 1LTFEXP_CBM-W1->PJM
CBM
126.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.288
MECLTFEXP_MEC->PJM
CLTF
14.414
SIGELTFEXP_SIGE->PJM
CLTF
0.332
CBM West 2LTFEXP_CBM-W2->PJM
CBM
76.901
LAGNLTFEXP_LAGN->PJM
CLTF
8.301
TVALTFEXP_TVA->PJM
CLTF
3.284
NYPJM->LTFIMP_NY
CLTF
2
LGEELTFEXP_LGEE->PJM
CLTF
3.227
WECLTFEXP_WEC->PJM
CLTF
3.885
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.527
AG2-052LTFEXP_AG2-052->PJM
LTF
0.257
AH1-155LTFEXP_AH1-155->PJM
LTF
0.385

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.05 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:6022.77
MW Contribution:8.32
Bus #Bus NameTypeMW Contribution
270102X2-052 ST
50/50
3.353
270100X2-052 CT1
50/50
3.09
270101X2-052 CT2
50/50
3.09
274770LINCOLN ;1U
50/50
18.26
274771LINCOLN ;2U
50/50
18.26
970321AG2-212 GEN
Solar/Wind Harmer
6.717
965681AG1-436 GEN
Solar/Wind Harmer
18.169
965791AG1-447 GEN
Solar/Wind Harmer
13.324
270526AF1-158 GEN
Solar/Wind Harmer
0.018
24441505OLIV SLR
Solar/Wind Harmer
0
270216AD2-079_GEN
Solar/Wind Harmer
0.002
957891AF2-083 GEN
Solar/Wind Harmer
0.002
961051AF2-396 GEN
Solar/Wind Harmer
28.457
961051AF2-396 GEN
Solar/Wind Harmer
18.971
247620Y3-023
Adder
0.932
274808UNIV PK N;4U
Adder
9.967
972259AH1-714 GEN
Adder
37.97
274803UNIV PARK;6U
Adder
11.601
274888KELLY CRK;1U
Solar/Wind Harmer
0.815
274887GEN-1.85
Solar/Wind Harmer
0.365
276843GEN-1.7
Solar/Wind Harmer
0.449
958011AF2-095 GEN
Solar/Wind Harmer
19.978
274674JOLIET 9 ;6U
Adder
30.323
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.529
274695ROCKY RD ;2P
Adder
21.486
274693ROCKY RD ;1P
Adder
21.275
274697ROCKY RD ;3P
Adder
5.837
274696ROCKY RD ;4P
Adder
21.993
958481AF2-142 GEN
Solar/Wind Harmer
20.192
274861TOP CROP ;1U
Solar/Wind Harmer
0.004
274862TOP CROP ;2U
Solar/Wind Harmer
1.82
274683WAUKEGAN ;8U
Adder
40.539
274683WAUKEGAN ;8U
Adder
34.173
962691AG1-118 GEN
Solar/Wind Harmer
40.102
970921AG2-575 GEN
Solar/Wind Harmer
13.333
970921AG2-575 GEN
Solar/Wind Harmer
4.444
958491AF2-143 GEN
Solar/Wind Harmer
19.955
274879MINONK ;1U
Solar/Wind Harmer
0.559
942991AE2-321 GEN
Solar/Wind Harmer
14.775
971333AH1-146 GEN
Solar/Wind Harmer
26.325
971335AH1-147 GEN
Solar/Wind Harmer
26.325
971341AH1-150 GEN
Solar/Wind Harmer
26.172
971343AH1-151 GEN
Solar/Wind Harmer
26.172
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.305
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
7.288
274764LEE CO EC;5U
Adder
17.123
274765LEE CO EC;6U
Adder
17.123
274762LEE CO EC;3U
Adder
17.083
274763LEE CO EC;4U
Adder
16.922
276603SUBLETTE C
Solar/Wind Harmer
0
970611AG2-400 GEN
Solar/Wind Harmer
12.726
970627AG2-408 GEN
Solar/Wind Harmer
3.818
972267AH1-718 GEN
Adder
7.569
276741O09 GEN1
Solar/Wind Harmer
0.451
971599AH1-298 GEN
50/50
19.983
270144AC1-141 ST1_
50/50
4.41
24643105BUCHANAN
50/50
0.026
274775LINCOLN ;6U
50/50
18.26
274776LINCOLN ;7U
50/50
18.26
274777LINCOLN ;8U
50/50
18.26
24653605MOTTVILLE
50/50
0.008
971347AH1-153 GEN
Solar/Wind Harmer
23.209
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
971771AH1-392 GEN
Solar/Wind Harmer
14.529
971769AH1-391 GEN
Solar/Wind Harmer
16.154
971619AH1-309 GEN
Solar/Wind Harmer
6.462
270071AF1-092 GEN
Solar/Wind Harmer
27.514
274814UNIV PK N;0U
Adder
10.098
274807UNIV PK N;3U
Adder
10.076
274805UNIV PK N;1U
Adder
10.033
274811UNIV PK N;7U
Adder
10.011
972037AH1-567 GEN1
Adder
0.364
274827FISK ;RP
Adder
15.436
960591AF2-350 GEN
Solar/Wind Harmer
13.873
972227AH1-698 GEN1
Adder
5.185
270536AF1-215 GEN2
Solar/Wind Harmer
0.017
274687WILL CNTY;4U
Adder
55.173
274687WILL CNTY;4U
Adder
55.173
274675JOLIET 29;7U
Adder
60.513
274675JOLIET 29;7U
Adder
58.351
274731ELWOOD EC;2P
Adder
32.348
274733ELWOOD EC;3P
Adder
32.348
274735ELWOOD EC;4P
Adder
32.348
274728ELWOOD EC;5P
Adder
32.348
970833AG2-524 GEN
Solar/Wind Harmer
15.09
970833AG2-524 GEN
Solar/Wind Harmer
10.06
274746AC1-111 G10
Adder
10.916
274744AC1-111 GEN8
Adder
10.916
958391AF2-133 GEN
Solar/Wind Harmer
0.002
24729505KEY G4
Adder
12.474
971611AH1-305 GEN
Solar/Wind Harmer
7.91
276868AE1-113 GEN
Solar/Wind Harmer
2.657
276882AE2-255 GEN
Solar/Wind Harmer
1.548
971177AH1-047 GEN
Solar/Wind Harmer
8.156
971675AH1-338 GEN
Solar/Wind Harmer
5.138
971411AH1-196 GEN
Solar/Wind Harmer
19.757
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
26.172
274823ROCKFORD ;21
Adder
36.411
970169AG2-114 GEN
Solar/Wind Harmer
12.957
276612AE2-035 GEN
Solar/Wind Harmer
0.003
926823AC1-168 GEN
Solar/Wind Harmer
2.2
971549AH1-272 GEN
Solar/Wind Harmer
26.668
971681AH1-341 GEN
Solar/Wind Harmer
20.716
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.003
24697605MDL-3G C
Solar/Wind Harmer
0.003
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
961011AF2-392 GEN
Solar/Wind Harmer
7.462
957751AF2-069 GEN
Solar/Wind Harmer
0.418
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
13.14
941731AE2-173 GEN
Solar/Wind Harmer
10.429
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
946321AF1-296 GEN
Solar/Wind Harmer
6.891
965101AG1-375 GEN
Solar/Wind Harmer
12.296
963841AG1-237 GEN
Solar/Wind Harmer
5.208
945581AF1-223 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.002
276174W4-005 GEN2
Solar/Wind Harmer
0.002
276849AB2-070 GEN2
Solar/Wind Harmer
0.424
276848AB2-070 GEN3
Solar/Wind Harmer
0.422
963791AG1-232 GEN
Solar/Wind Harmer
15.504
970289AG2-191 GEN
Solar/Wind Harmer
2.164
270594AE1-207 GEN
Solar/Wind Harmer
12.434
971609AH1-304 GEN
Solar/Wind Harmer
1.81
965041AG1-368 GEN
Solar/Wind Harmer
11.055
944221AF1-090 GEN
Solar/Wind Harmer
6.244
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
4.131
270024AE2-089 GEN
Solar/Wind Harmer
0.011
965051AG1-369 GEN
Solar/Wind Harmer
5.072
270240V3-007_GEN2
Solar/Wind Harmer
0.003
270543AE2-219 C
Solar/Wind Harmer
0.005
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.018
971029AG2-637 GEN
Solar/Wind Harmer
11.658
971673AH1-337 GEN
Solar/Wind Harmer
4.919
276708O09 GEN2
Solar/Wind Harmer
0.451
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.497
276646AC1-214 GEN2
Solar/Wind Harmer
0.497
276782AC1-033 GEN
Solar/Wind Harmer
0.002
944541AF1-119 GEN
Solar/Wind Harmer
0.842
960971AF2-388 GEN
Solar/Wind Harmer
7.376
966841AG1-555 GEN
Solar/Wind Harmer
1.399
960611AF2-352 GEN
Solar/Wind Harmer
4.101
970241AG2-163 GEN
Solar/Wind Harmer
6.826
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
971613AH1-306 GEN
Solar/Wind Harmer
5.329
270599AE1-208 GEN
Solar/Wind Harmer
10.158
270031AE2-169
Solar/Wind Harmer
6.095
276916AD2-100_GEN
Solar/Wind Harmer
23.006
276911AD2-131_GEN
Solar/Wind Harmer
1.515
970239AG2-162 GEN
Solar/Wind Harmer
2.688
945391AF1-204 GEN
Solar/Wind Harmer
11.282
960441AF2-335 GEN
Solar/Wind Harmer
10.327
970825AG2-519 GEN
Solar/Wind Harmer
11.373
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
7.189
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.716
270201AC2-176 GEN
Solar/Wind Harmer
0.002
270383AD1-128 GEN
Solar/Wind Harmer
0.005
970623AG2-406 GEN
Solar/Wind Harmer
1.6
970883AG2-550 GEN
Solar/Wind Harmer
8.324
970885AG2-551 GEN
Solar/Wind Harmer
2.775
270007AE1-245 C
Solar/Wind Harmer
0.002
246938BC-WTG3
Solar/Wind Harmer
0.291
246937BC-WTG2
Solar/Wind Harmer
0.326
270471AD2-092_GEN
Solar/Wind Helper
1.548
24344105CKG2
50/50
17.41
270143AC1-141 CT2_
50/50
4.979
24639705ELKHART HY
50/50
0.333
274773LINCOLN ;4U
50/50
18.26
274774LINCOLN ;5U
50/50
18.26
970521AG2-332 GEN
50/50
23.674
970245AG2-165 GEN
Solar/Wind Harmer
6.717
270505AE1-170 C O1
Solar/Wind Harmer
15.077
945111AF1-176 GEN
Solar/Wind Harmer
25.462
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.414
274723RIVER EC ;12
Adder
36.059
970373AG2-245 GEN
Solar/Wind Harmer
29.431
274751CRETE EC ;1U
Adder
16.552
274754CRETE EC ;4U
Adder
16.552
276164X3-005 C
Solar/Wind Harmer
0
270063AE2-323 C
Solar/Wind Harmer
0.011
274812UNIV PK N;8U
Adder
10.011
276776AD2-060 GEN
Solar/Wind Harmer
1.448
274801UNIV PARK;4U
Adder
11.588
941551AE2-152 GEN
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.011
274676JOLIET 29;8U
Adder
60.512
274674JOLIET 9 ;6U
Adder
30.323
274732ELWOOD EC;7P
Adder
32.348
274871GR RIDGE ;2U
Solar/Wind Harmer
0.002
274745AC1-111 GEN9
Adder
10.916
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
17.617
276691AA1-018 GEN1
Solar/Wind Harmer
1.631
274682WAUKEGAN ;7U
Adder
34.62
274828WAUKEGAN ;BP
Adder
21.25
939401AE1-172 GEN
Solar/Wind Harmer
9.985
962781AG1-127 GEN
Solar/Wind Harmer
12.689
274872LEEDK;1U
Solar/Wind Harmer
0.008
940581AE2-045 GEN
Solar/Wind Harmer
-0.003
971605AH1-302 GEN
Solar/Wind Harmer
16.609
276901AD2-066 C O1
Solar/Wind Harmer
0.013
971997AH1-543 GEN
Solar/Wind Harmer
6.942
276861AD2-134 GEN
Solar/Wind Harmer
0.236
957471AF2-041 GEN
Solar/Wind Harmer
39.258
959081AF2-199 GEN
Solar/Wind Harmer
13.086
971067AG2-660 GEN
Solar/Wind Harmer
4.362
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
36.677
972235AH1-702 GEN1
Adder
4.699
970819AG2-516 GEN
Solar/Wind Harmer
15.555
970569AG2-363 GEN
Solar/Wind Harmer
38.8
971475AH1-234 GEN
Solar/Wind Harmer
6.272
274857EASY ROAD;U1
Solar/Wind Harmer
0.003
274761LEE CO EC;2U
Adder
17.083
274766LEE CO EC;7U
Adder
16.882
24791305MDL-5G
Solar/Wind Harmer
0.002
965011AG1-365 GEN
Solar/Wind Harmer
12.726
276158O29GEN2
Solar/Wind Harmer
0.001
274877BISHOP HL;1U
Solar/Wind Harmer
0.423
965651AG1-433 GEN
Solar/Wind Harmer
3.688
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
17.52
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.005
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
958861AF2-177 GEN
Solar/Wind Harmer
5.328
972175AH1-670 GEN
Solar/Wind Harmer
9.878
945371AF1-202 GEN
Solar/Wind Harmer
0.001
963741AG1-226 GEN
Solar/Wind Harmer
27.693
274880W4-005 GEN4
Solar/Wind Harmer
0.002
963831AG1-236 GEN
Solar/Wind Harmer
4.513
276615X2-022 GEN
Solar/Wind Harmer
0.12
944231AF1-091 GEN
Solar/Wind Harmer
3.041
970291AG2-192 GEN
Solar/Wind Harmer
1.481
270032AE2-172
Solar/Wind Harmer
7.401
965911AG1-460 GEN
Solar/Wind Harmer
2.209
276903AD2-071 C
Solar/Wind Harmer
12.04
970333AG2-219 GEN
Solar/Wind Harmer
7.687
270005AE1-210 C O1
Solar/Wind Harmer
2.283
965031AG1-367 GEN
Solar/Wind Harmer
10.536
970825AG2-519 GEN
Solar/Wind Harmer
3.643
247521TR3_G114
Solar/Wind Harmer
0.37
270246TR4_N_V150
Solar/Wind Harmer
0.066
24695305TIMB G C
Solar/Wind Harmer
0.003
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.029
247536S-71 GEN
Solar/Wind Harmer
0.355
965421AG1-410 GEN
Solar/Wind Harmer
25.459
970773AG2-487 GEN
Solar/Wind Harmer
1.469
246936BC-WTG1
Solar/Wind Harmer
0.326
270489AE1-102 GEN1
Solar/Wind Harmer
1.045
270349AD2-093_GEN
Solar/Wind Helper
1.548
24344005CKG1
50/50
13.628
270142AC1-141 CT1_
50/50
4.979
24641605TWIN BRNCH
50/50
0.036
24642205MAYFLWER
50/50
1.39
274772LINCOLN ;3U
50/50
18.26
970513AG2-328 GEN
Solar/Wind Harmer
6.717
970517AG2-330 GEN
Solar/Wind Harmer
40.303
970349AG2-230 GEN
Solar/Wind Harmer
23.209
270043AE2-236 GEN
Solar/Wind Harmer
9.37
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.566
274724RIVER EC ;11
Adder
35.644
274752CRETE EC ;2U
Adder
16.552
274753CRETE EC ;3U
Adder
16.552
24441205WTRV SLR C
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
45.547
274802UNIV PARK;5U
Adder
11.601
274826FISK ;BP
Adder
21.78
276806AD2-047 C O1
Solar/Wind Harmer
7.862
970941AG2-585 GEN
Solar/Wind Harmer
17.342
972228AH1-698 GEN2
Adder
7.363
274800UNIV PARK;3U
Adder
11.588
972038AH1-567 GEN2
Adder
0.725
276897AD1-100 C
Solar/Wind Harmer
0.018
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
247604X1-042
Adder
0.825
270535AF1-215 GEN1
Solar/Wind Harmer
0.017
274676JOLIET 29;8U
Adder
58.35
970031AG2-029 GEN
Solar/Wind Harmer
8.936
274729ELWOOD EC;1P
Adder
32.348
274730ELWOOD EC;6P
Adder
32.348
274734ELWOOD EC;8P
Adder
32.348
274736ELWOOD EC;9P
Adder
32.348
276893AG1-478 C
Solar/Wind Harmer
0.544
944531AF1-118 GEN
Solar/Wind Harmer
61.488
943121AE2-341 GEN
Solar/Wind Harmer
22.888
943591AF1-030 GEN
Solar/Wind Harmer
15.221
964401AG1-302 GEN
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
34.62
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
276805AD2-038 GEN
Solar/Wind Harmer
0.004
274872LEEDK;1U
Solar/Wind Harmer
0.488
276799AD1-013 GEN
Solar/Wind Harmer
0.003
946671AF1-331 GEN
Solar/Wind Harmer
1.406
274855GSG-6 ;RU
Solar/Wind Harmer
0.483
274850MENDOTA H;RU
Solar/Wind Harmer
0.155
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.236
959091AF2-200 GEN
Solar/Wind Harmer
26.172
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
4.086
970571AG2-364 GEN
Solar/Wind Harmer
25.867
274858EASY ROAD;U2
Solar/Wind Harmer
0.003
274760LEE CO EC;1U
Adder
17.083
274767LEE CO EC;8U
Adder
16.882
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
12.802
959331AF2-224 GEN
Solar/Wind Harmer
8.908
965021AG1-366 GEN
Solar/Wind Harmer
4.242
276157O29GEN1
Solar/Wind Harmer
2.046
274878BISHOP HL;2U
Solar/Wind Harmer
0.423
942111AE2-223 GEN
Solar/Wind Harmer
4.067
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
36.906
959611AF2-252 GEN
Solar/Wind Harmer
4.101
965931AG1-462 GEN
Solar/Wind Harmer
31.198
247642Z2-115 C
Solar/Wind Harmer
0.005
276686W4-005 GEN3
Solar/Wind Harmer
0.002
971993AH1-541 GEN
Solar/Wind Harmer
5.377
276668AB2-070 GEN1
Solar/Wind Harmer
0.424
276621W2-048 GEN
Solar/Wind Harmer
0.577
276838X2-022 GEN2
Solar/Wind Harmer
0.644
970289AG2-191 GEN
Solar/Wind Harmer
1.253
970291AG2-192 GEN
Solar/Wind Harmer
1.139
942481AE2-261 GEN
Solar/Wind Harmer
33.028
970243AG2-164 GEN
Solar/Wind Harmer
6.289
970519AG2-331 GEN
Solar/Wind Harmer
27.951
970699AG2-449 GEN
Solar/Wind Harmer
2.688
970193AG2-126 GEN
Solar/Wind Harmer
15.928
958821AF2-173 GEN
Solar/Wind Harmer
14.751
270004AE1-209 GEN
Solar/Wind Harmer
2.283
971617AH1-308 GEN
Solar/Wind Harmer
8.548
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.066
946031AF1-268 GEN
Solar/Wind Harmer
9.517
270437AC2-090 C
Solar/Wind Harmer
0.004
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
14.144
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
270356AE2-297 GEN
Solar/Wind Harmer
0.011
270491AE1-102 GEN2
Solar/Wind Harmer
1.045
944201AF1-088_MTX
Adder
163.382
957141AF2-008_MTX
Adder
69.441
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.516
CBM West 1LTFEXP_CBM-W1->PJM
CBM
217.631
CBM South 1LTFEXP_CBM-S1->PJM
CBM
22.154
MECLTFEXP_MEC->PJM
CLTF
26.031
SIGELTFEXP_SIGE->PJM
CLTF
0.551
CBM West 2LTFEXP_CBM-W2->PJM
CBM
131.138
LAGNLTFEXP_LAGN->PJM
CLTF
14.15
TVALTFEXP_TVA->PJM
CLTF
5.408
NYPJM->LTFIMP_NY
CLTF
3.386
LGEELTFEXP_LGEE->PJM
CLTF
5.588
WECLTFEXP_WEC->PJM
CLTF
7.104
HAMLETPJM->LTFIMP_HAMLET
CLTF
1.19
AG2-052LTFEXP_AG2-052->PJM
LTF
0.447
AH1-155LTFEXP_AH1-155->PJM
LTF
0.671

Details for 05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line l/o AEP_P1-2_#6463_16757_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line
Contingency Name:
AEP_P1-2_#6463_16757_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:104.68 %
Rating:5523.0 MVA
Rating Type:B
MVA to Mitigate:5781.3
MW Contribution:7.92
Bus #Bus NameTypeMW Contribution
971599AH1-298 GEN
50/50
20.512
24727205RPMNG3
50/50
2.026
270144AC1-141 ST1_
50/50
4.287
24653605MOTTVILLE
50/50
0.008
24643105BUCHANAN
50/50
0.025
957201AF2-014 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
1.893
971347AH1-153 GEN
Solar/Wind Harmer
22.406
270071AF1-092 GEN
Solar/Wind Harmer
27.685
971771AH1-392 GEN
Solar/Wind Harmer
14.093
971619AH1-309 GEN
Solar/Wind Harmer
6.277
971769AH1-391 GEN
Solar/Wind Harmer
15.555
960681AF2-359 GEN
Solar/Wind Harmer
-0.002
274775LINCOLN ;6U
Adder
16.368
274776LINCOLN ;7U
Adder
16.368
274777LINCOLN ;8U
Adder
16.368
24729505KEY G4
Adder
12.57
274814UNIV PK N;0U
Adder
9.612
274807UNIV PK N;3U
Adder
9.591
274805UNIV PK N;1U
Adder
9.549
274811UNIV PK N;7U
Adder
9.528
972037AH1-567 GEN1
Adder
0.346
274827FISK ;RP
Adder
14.675
960591AF2-350 GEN
Solar/Wind Harmer
13.18
972227AH1-698 GEN1
Adder
4.923
274687WILL CNTY;4U
Adder
52.393
274687WILL CNTY;4U
Adder
52.393
274675JOLIET 29;7U
Adder
57.451
274675JOLIET 29;7U
Adder
55.399
274731ELWOOD EC;2P
Adder
30.692
274733ELWOOD EC;3P
Adder
30.692
274735ELWOOD EC;4P
Adder
30.692
274728ELWOOD EC;5P
Adder
30.693
970833AG2-524 GEN
Solar/Wind Harmer
14.308
970833AG2-524 GEN
Solar/Wind Harmer
9.539
270536AF1-215 GEN2
Solar/Wind Harmer
0.016
274746AC1-111 G10
Adder
10.351
274744AC1-111 GEN8
Adder
10.351
970615AG2-402 GEN
50/50
4.988
270102X2-052 ST
50/50
3.214
270100X2-052 CT1
50/50
2.961
270101X2-052 CT2
50/50
2.961
247620Y3-023
50/50
0.98
970611AG2-400 GEN
Solar/Wind Harmer
14.965
970627AG2-408 GEN
Solar/Wind Harmer
4.49
246938BC-WTG3
Solar/Wind Harmer
0.542
246937BC-WTG2
Solar/Wind Harmer
0.606
970321AG2-212 GEN
Solar/Wind Harmer
6.295
270216AD2-079_GEN
Solar/Wind Harmer
0.002
270526AF1-158 GEN
Solar/Wind Harmer
0.017
957891AF2-083 GEN
Solar/Wind Harmer
0.002
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
17.4
965791AG1-447 GEN
Solar/Wind Harmer
12.76
961051AF2-396 GEN
Solar/Wind Harmer
27.667
961051AF2-396 GEN
Solar/Wind Harmer
18.445
274770LINCOLN ;1U
Adder
16.368
274771LINCOLN ;2U
Adder
16.368
274808UNIV PK N;4U
Adder
9.487
274803UNIV PARK;6U
Adder
11.029
972259AH1-714 GEN
Adder
36.054
274888KELLY CRK;1U
Solar/Wind Harmer
0.774
274887GEN-1.85
Solar/Wind Harmer
0.347
276843GEN-1.7
Solar/Wind Harmer
0.427
958011AF2-095 GEN
Solar/Wind Harmer
18.98
274674JOLIET 9 ;6U
Adder
28.777
274847GR RIDGE ;BU
Solar/Wind Harmer
0.005
971573AH1-285 GEN
Solar/Wind Harmer
2.397
274695ROCKY RD ;2P
Adder
20.358
274693ROCKY RD ;1P
Adder
20.158
274697ROCKY RD ;3P
Adder
5.53
274696ROCKY RD ;4P
Adder
20.838
958481AF2-142 GEN
Solar/Wind Harmer
19.12
274861TOP CROP ;1U
Solar/Wind Harmer
0.003
274862TOP CROP ;2U
Solar/Wind Harmer
1.724
274683WAUKEGAN ;8U
Adder
38.41
274683WAUKEGAN ;8U
Adder
32.378
962691AG1-118 GEN
Solar/Wind Harmer
37.971
970921AG2-575 GEN
Solar/Wind Harmer
12.623
970921AG2-575 GEN
Solar/Wind Harmer
4.208
958491AF2-143 GEN
Solar/Wind Harmer
18.868
944541AF1-119 GEN
Solar/Wind Harmer
0.84
960971AF2-388 GEN
Solar/Wind Harmer
7.355
942991AE2-321 GEN
Solar/Wind Harmer
13.981
274879MINONK ;1U
Solar/Wind Harmer
0.528
971333AH1-146 GEN
Solar/Wind Harmer
24.899
971335AH1-147 GEN
Solar/Wind Harmer
24.899
971341AH1-150 GEN
Solar/Wind Harmer
24.739
971343AH1-151 GEN
Solar/Wind Harmer
24.739
276872AE1-163_GEN1
Solar/Wind Harmer
0.003
274856ECOGROVE ;U1
Solar/Wind Harmer
0.288
276611AD2-172 GEN
Solar/Wind Harmer
0.003
938861AE1-114 GEN
Solar/Wind Harmer
6.879
274764LEE CO EC;5U
Adder
16.158
274765LEE CO EC;6U
Adder
16.158
274762LEE CO EC;3U
Adder
16.12
274763LEE CO EC;4U
Adder
15.968
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
7.136
945421AF1-207 GEN
Solar/Wind Harmer
0.001
957841AF2-078 GEN
Solar/Wind Harmer
-0.003
276741O09 GEN1
Solar/Wind Harmer
0.425
276708O09 GEN2
Solar/Wind Harmer
0.425
274851PROVIDENC;RU
Solar/Wind Harmer
0.002
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
24344105CKG2
50/50
16.743
24727005RPMNG1
50/50
2.036
270143AC1-141 CT2_
50/50
4.84
24639705ELKHART HY
50/50
0.328
970521AG2-332 GEN
50/50
23.369
24307105BERRINSP G
50/50
0.043
965011AG1-365 GEN
Solar/Wind Harmer
14.965
965421AG1-410 GEN
Solar/Wind Harmer
44.849
246936BC-WTG1
Solar/Wind Harmer
0.606
270489AE1-102 GEN1
Solar/Wind Harmer
1.943
970245AG2-165 GEN
Solar/Wind Harmer
6.295
270063AE2-323 C
Solar/Wind Harmer
0.012
270505AE1-170 C O1
Solar/Wind Harmer
14.646
945111AF1-176 GEN
Solar/Wind Harmer
24.826
270449AD2-020 GEN
Solar/Wind Harmer
0.001
943021AE2-325 GEN
Solar/Wind Harmer
7.196
274773LINCOLN ;4U
Adder
16.368
274774LINCOLN ;5U
Adder
16.368
274723RIVER EC ;12
Adder
34.361
274751CRETE EC ;1U
Adder
15.774
274754CRETE EC ;4U
Adder
15.774
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
9.528
970373AG2-245 GEN
Solar/Wind Harmer
27.796
274801UNIV PARK;4U
Adder
11.014
276776AD2-060 GEN
Solar/Wind Harmer
1.376
941551AE2-152 GEN
Solar/Wind Harmer
0.001
274676JOLIET 29;8U
Adder
57.45
274674JOLIET 9 ;6U
Adder
28.777
274732ELWOOD EC;7P
Adder
30.693
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.01
274745AC1-111 GEN9
Adder
10.351
276691AA1-018 GEN1
Solar/Wind Harmer
1.544
274682WAUKEGAN ;7U
Adder
32.805
274828WAUKEGAN ;BP
Adder
20.134
958381AF2-132 GEN
Solar/Wind Harmer
0.002
964861AG1-349 GEN
Solar/Wind Harmer
-0.002
971917AH1-482 GEN
Solar/Wind Harmer
16.434
962781AG1-127 GEN
Solar/Wind Harmer
12.012
274872LEEDK;1U
Solar/Wind Harmer
0.008
939401AE1-172 GEN
Solar/Wind Harmer
9.413
276901AD2-066 C O1
Solar/Wind Harmer
0.012
965651AG1-433 GEN
Solar/Wind Harmer
3.678
971997AH1-543 GEN
Solar/Wind Harmer
6.554
276861AD2-134 GEN
Solar/Wind Harmer
0.223
957471AF2-041 GEN
Solar/Wind Harmer
37.108
959081AF2-199 GEN
Solar/Wind Harmer
12.369
971067AG2-660 GEN
Solar/Wind Harmer
4.123
276876AE1-163_GEN2
Solar/Wind Harmer
0.003
274822ROCKFORD ;11
Adder
34.667
940581AE2-045 GEN
Solar/Wind Harmer
-0.002
971605AH1-302 GEN
Solar/Wind Harmer
15.377
972235AH1-702 GEN1
Adder
4.441
970819AG2-516 GEN
Solar/Wind Harmer
14.695
958861AF2-177 GEN
Solar/Wind Harmer
5.294
971475AH1-234 GEN
Solar/Wind Harmer
5.925
958391AF2-133 GEN
Solar/Wind Harmer
0.002
971177AH1-047 GEN
Solar/Wind Harmer
7.718
276868AE1-113 GEN
Solar/Wind Harmer
2.511
276882AE2-255 GEN
Solar/Wind Harmer
1.463
971411AH1-196 GEN
Solar/Wind Harmer
18.689
971675AH1-338 GEN
Solar/Wind Harmer
4.859
971549AH1-272 GEN
Solar/Wind Harmer
25.626
274863CRW1-WTG
Solar/Wind Harmer
0.004
274864CRW2-WTG
Solar/Wind Harmer
0.004
971171AH1-044 GEN
Solar/Wind Harmer
24.739
274823ROCKFORD ;21
Adder
34.415
971611AH1-305 GEN
Solar/Wind Harmer
7.323
963791AG1-232 GEN
Solar/Wind Harmer
16.568
276612AE2-035 GEN
Solar/Wind Harmer
0.003
965101AG1-375 GEN
Solar/Wind Harmer
12.216
926823AC1-168 GEN
Solar/Wind Harmer
2.071
970169AG2-114 GEN
Solar/Wind Harmer
12.156
971681AH1-341 GEN
Solar/Wind Harmer
19.553
961011AF2-392 GEN
Solar/Wind Harmer
7.036
965041AG1-368 GEN
Solar/Wind Harmer
11.932
957751AF2-069 GEN
Solar/Wind Harmer
0.392
274848CAMPGROVE;RU
Solar/Wind Harmer
0.002
24690905MDL-1G C
Solar/Wind Harmer
0.004
270180AB1-006 GEN1
Solar/Wind Harmer
0.003
946581AF1-322 GEN
Solar/Wind Harmer
0.001
24691005MDL-2G C
Solar/Wind Harmer
0.002
24697605MDL-3G C
Solar/Wind Harmer
0.002
24697905MDL-4G C
Solar/Wind Harmer
0.002
270181AB1-006 GEN2
Solar/Wind Harmer
0
276655WTG1_EQ
Solar/Wind Harmer
0.005
276656WTG2_EQ
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
12.245
941731AE2-173 GEN
Solar/Wind Harmer
9.718
945581AF1-223 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
6.48
24386205FR-12G C
Solar/Wind Harmer
0.002
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.002
963841AG1-237 GEN
Solar/Wind Harmer
4.707
971609AH1-304 GEN
Solar/Wind Harmer
1.767
965051AG1-369 GEN
Solar/Wind Harmer
5.379
970289AG2-191 GEN
Solar/Wind Harmer
2.036
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.39
276848AB2-070 GEN3
Solar/Wind Harmer
0.388
270594AE1-207 GEN
Solar/Wind Harmer
11.748
270024AE2-089 GEN
Solar/Wind Harmer
0.011
970115AG2-085 GEN
Solar/Wind Harmer
3.968
24725505WLD G2 C
Solar/Wind Harmer
0.002
24699105WLD G1 C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
5.647
270240V3-007_GEN2
Solar/Wind Harmer
0.003
247607V1-011 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.005
971029AG2-637 GEN
Solar/Wind Harmer
10.94
971673AH1-337 GEN
Solar/Wind Harmer
4.593
270284AF1-227 GEN1
Solar/Wind Helper
2.302
270286AF1-227 GEN2
Solar/Wind Helper
0.844
270287AF1-227 GEN3
Solar/Wind Helper
0.844
270054AF2-122 C O1
Solar/Wind Helper
1.201
24727105RPMNG2
50/50
2.043
965431AG1-411 GEN
50/50
24.916
270142AC1-141 CT1_
50/50
4.84
24641605TWIN BRNCH
50/50
0.035
24344005CKG1
50/50
13.145
24642205MAYFLWER
50/50
1.347
944961AF1-161 GEN
50/50
5.744
962601AG1-109 GEN
50/50
5.744
270043AE2-236 GEN
Solar/Wind Harmer
9.614
959331AF2-224 GEN
Solar/Wind Harmer
10.476
965021AG1-366 GEN
Solar/Wind Harmer
4.988
270491AE1-102 GEN2
Solar/Wind Harmer
1.943
970349AG2-230 GEN
Solar/Wind Harmer
22.406
970513AG2-328 GEN
Solar/Wind Harmer
6.295
970517AG2-330 GEN
Solar/Wind Harmer
37.773
970031AG2-029 GEN
Solar/Wind Harmer
9.246
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
11.278
944531AF1-118 GEN
Solar/Wind Harmer
62.173
274772LINCOLN ;3U
Adder
16.368
24441205WTRV SLR C
Solar/Wind Harmer
0
274724RIVER EC ;11
Adder
33.965
274752CRETE EC ;2U
Adder
15.774
274753CRETE EC ;3U
Adder
15.774
247604X1-042
Adder
0.795
970707AG2-453 GEN
Solar/Wind Harmer
43.26
274802UNIV PARK;5U
Adder
11.029
274826FISK ;BP
Adder
20.707
274800UNIV PARK;3U
Adder
11.014
972038AH1-567 GEN2
Adder
0.689
276806AD2-047 C O1
Solar/Wind Harmer
7.469
970941AG2-585 GEN
Solar/Wind Harmer
16.476
972228AH1-698 GEN2
Adder
6.992
276897AD1-100 C
Solar/Wind Harmer
0.017
939351AE1-166 GEN
Solar/Wind Harmer
-0.001
274676JOLIET 29;8U
Adder
55.398
274729ELWOOD EC;1P
Adder
30.692
274730ELWOOD EC;6P
Adder
30.693
274734ELWOOD EC;8P
Adder
30.693
274736ELWOOD EC;9P
Adder
30.693
276893AG1-478 C
Solar/Wind Harmer
0.516
943121AE2-341 GEN
Solar/Wind Harmer
21.706
943591AF1-030 GEN
Solar/Wind Harmer
14.435
270535AF1-215 GEN1
Solar/Wind Harmer
0.016
276694AA1-018 GEN2
Solar/Wind Harmer
0.002
274682WAUKEGAN ;7U
Adder
32.805
964401AG1-302 GEN
Solar/Wind Harmer
0.002
274872LEEDK;1U
Solar/Wind Harmer
0.462
276805AD2-038 GEN
Solar/Wind Harmer
0.004
276799AD1-013 GEN
Solar/Wind Harmer
0.002
946671AF1-331 GEN
Solar/Wind Harmer
1.33
274855GSG-6 ;RU
Solar/Wind Harmer
0.457
274850MENDOTA H;RU
Solar/Wind Harmer
0.147
276602WESTBROOK C
Solar/Wind Harmer
0.001
276863AD2-134 GEN
Solar/Wind Harmer
0.223
959141AF2-205 GEN
Solar/Wind Harmer
-0.003
959091AF2-200 GEN
Solar/Wind Harmer
24.739
276889AE2-281 GEN
Solar/Wind Harmer
0.001
972236AH1-702 GEN2
Adder
3.861
970571AG2-364 GEN
Solar/Wind Harmer
24.37
274858EASY ROAD;U2
Solar/Wind Harmer
0.002
274760LEE CO EC;1U
Adder
16.12
274767LEE CO EC;8U
Adder
15.93
276157O29GEN1
Solar/Wind Harmer
1.927
274878BISHOP HL;2U
Solar/Wind Harmer
0.397
24755605MDL-5G
Solar/Wind Harmer
0.002
970781AG2-491 GEN
Solar/Wind Harmer
11.712
942111AE2-223 GEN
Solar/Wind Harmer
3.79
965931AG1-462 GEN
Solar/Wind Harmer
29.323
274853TWINGROVE;U1
Solar/Wind Harmer
0.005
965091AG1-374 GEN
Solar/Wind Harmer
34.294
959611AF2-252 GEN
Solar/Wind Harmer
3.81
247642Z2-115 C
Solar/Wind Harmer
0.005
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.07
970289AG2-191 GEN
Solar/Wind Harmer
1.179
970291AG2-192 GEN
Solar/Wind Harmer
1.072
276686W4-005 GEN3
Solar/Wind Harmer
0.001
971993AH1-541 GEN
Solar/Wind Harmer
4.944
276668AB2-070 GEN1
Solar/Wind Harmer
0.39
276621W2-048 GEN
Solar/Wind Harmer
0.529
276838X2-022 GEN2
Solar/Wind Harmer
0.591
971617AH1-308 GEN
Solar/Wind Harmer
8.654
958821AF2-173 GEN
Solar/Wind Harmer
14.235
270004AE1-209 GEN
Solar/Wind Harmer
2.203
942481AE2-261 GEN
Solar/Wind Harmer
30.115
946031AF1-268 GEN
Solar/Wind Harmer
9.153
970193AG2-126 GEN
Solar/Wind Harmer
14.08
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
13.732
270437AC2-090 C
Solar/Wind Harmer
0.004
270404AC1-167 GEN
Solar/Wind Harmer
0.004
270258AD1-119 GEN
Solar/Wind Harmer
0.002
24728705AND G3
Adder
9.578
24728505AND G1
Adder
4.579
970243AG2-164 GEN
Solar/Wind Harmer
4.523
970519AG2-331 GEN
Solar/Wind Harmer
20.102
970699AG2-449 GEN
Solar/Wind Harmer
1.933
270356AE2-297 GEN
Solar/Wind Harmer
0.01
276645AC1-214 GEN1
Solar/Wind Harmer
0.467
276646AC1-214 GEN2
Solar/Wind Harmer
0.467
942221AE2-234 GEN
Solar/Wind Harmer
0.059
276782AC1-033 GEN
Solar/Wind Harmer
0.002
960611AF2-352 GEN
Solar/Wind Harmer
3.81
966841AG1-555 GEN
Solar/Wind Harmer
1.27
270599AE1-208 GEN
Solar/Wind Harmer
9.916
270031AE2-169
Solar/Wind Harmer
5.95
276763AC1-053 GEN1
Solar/Wind Harmer
0.002
276764AC1-053 GEN2
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
6.141
971613AH1-306 GEN
Solar/Wind Harmer
5.035
276916AD2-100_GEN
Solar/Wind Harmer
20.939
276911AD2-131_GEN
Solar/Wind Harmer
1.379
960441AF2-335 GEN
Solar/Wind Harmer
9.92
970825AG2-519 GEN
Solar/Wind Harmer
10.923
945391AF1-204 GEN
Solar/Wind Harmer
9.973
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
0.002
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.306
970623AG2-406 GEN
Solar/Wind Harmer
1.558
270383AD1-128 GEN
Solar/Wind Harmer
0.005
270444AC2-157 GEN1
Solar/Wind Harmer
0.004
971587AH1-292 GEN
Solar/Wind Harmer
5.849
970883AG2-550 GEN
Solar/Wind Harmer
7.917
970885AG2-551 GEN
Solar/Wind Harmer
2.639
270007AE1-245 C
Solar/Wind Harmer
0.002
970239AG2-162 GEN
Solar/Wind Harmer
1.933
270471AD2-092_GEN
Solar/Wind Helper
1.737
970569AG2-363 GEN
Solar/Wind Harmer
36.555
274857EASY ROAD;U1
Solar/Wind Harmer
0.002
274761LEE CO EC;2U
Adder
16.12
274766LEE CO EC;7U
Adder
15.93
276158O29GEN2
Solar/Wind Harmer
0.001
944231AF1-091 GEN
Solar/Wind Harmer
3.153
274877BISHOP HL;1U
Solar/Wind Harmer
0.397
24791305MDL-5G
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.004
939741AE1-205 GEN
Solar/Wind Harmer
16.327
945371AF1-202 GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.005
24385905FR-11G C
Solar/Wind Harmer
0.003
24387305FR-4G C
Solar/Wind Harmer
0.004
972175AH1-670 GEN
Solar/Wind Harmer
9.129
247521TR3_G114
Solar/Wind Harmer
0.393
270246TR4_N_V150
Solar/Wind Harmer
0.07
970291AG2-192 GEN
Solar/Wind Harmer
1.393
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
4.146
963741AG1-226 GEN
Solar/Wind Harmer
24.913
276615X2-022 GEN
Solar/Wind Harmer
0.11
270032AE2-172
Solar/Wind Harmer
6.993
24695305TIMB G C
Solar/Wind Harmer
0.003
270005AE1-210 C O1
Solar/Wind Harmer
2.203
965031AG1-367 GEN
Solar/Wind Harmer
10.168
276903AD2-071 C
Solar/Wind Harmer
11.298
965911AG1-460 GEN
Solar/Wind Harmer
2.014
970825AG2-519 GEN
Solar/Wind Harmer
3.499
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
6.684
247536S-71 GEN
Solar/Wind Harmer
0.341
24728605AND G2
Adder
4.579
270445AC2-157 GEN2
Solar/Wind Harmer
0.004
970333AG2-219 GEN
Solar/Wind Harmer
5.528
970773AG2-487 GEN
Solar/Wind Harmer
1.34
270349AD2-093_GEN
Solar/Wind Helper
1.737
944201AF1-088_MTX
Adder
132.938
957141AF2-008_MTX
Adder
17.09
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.281
CBM West 1LTFEXP_CBM-W1->PJM
CBM
201.431
CBM South 1LTFEXP_CBM-S1->PJM
CBM
19.695
MECLTFEXP_MEC->PJM
CLTF
24.295
SIGELTFEXP_SIGE->PJM
CLTF
0.466
CBM West 2LTFEXP_CBM-W2->PJM
CBM
118.505
LAGNLTFEXP_LAGN->PJM
CLTF
13.14
TVALTFEXP_TVA->PJM
CLTF
5.018
NYPJM->LTFIMP_NY
CLTF
3.194
LGEELTFEXP_LGEE->PJM
CLTF
4.31
WECLTFEXP_WEC->PJM
CLTF
6.715
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.799
AG2-052LTFEXP_AG2-052->PJM
LTF
0.422
AH1-155LTFEXP_AH1-155->PJM
LTF
0.632

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:128.08 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2967.71
MW Contribution:11.85
Bus #Bus NameTypeMW Contribution
964351AG1-297 GEN
50/50
22.593
961161AF2-407 GEN
50/50
55.693
24728705AND G3
50/50
11.013
24728505AND G1
50/50
5.266
270437AC2-090 C
Solar/Wind Harmer
13.802
270356AE2-297 GEN
Solar/Wind Harmer
10.957
24726905LAWG2S
50/50
8.873
24726605LAWG1S
50/50
8.864
24726705LAWG2A
50/50
5.965
24726505LAWG1B
50/50
5.923
24726805LAWG2B
50/50
5.905
24729505KEY G4
50/50
8.904
270240V3-007_GEN2
Solar/Wind Harmer
15.295
945581AF1-223 GEN
Solar/Wind Harmer
7.477
970115AG2-085 GEN
Solar/Wind Harmer
6.438
965101AG1-375 GEN
Solar/Wind Harmer
15.348
958711AF2-162 GEN
Solar/Wind Harmer
1.492
24725505WLD G2 C
Solar/Wind Harmer
5.718
24699105WLD G1 C
Solar/Wind Harmer
5.651
270594AE1-207 GEN
Solar/Wind Harmer
19.374
961761AG1-017 GEN
Solar/Wind Harmer
0.535
944031AF1-071 GEN
Solar/Wind Harmer
1.234
965461AG1-414 GEN
Solar/Wind Harmer
2.728
970289AG2-191 GEN
Solar/Wind Harmer
2.286
270543AE2-219 C
Solar/Wind Harmer
6.069
971029AG2-637 GEN
Solar/Wind Harmer
17.299
971673AH1-337 GEN
Solar/Wind Harmer
5.229
270024AE2-089 GEN
Solar/Wind Harmer
5.064
963791AG1-232 GEN
Solar/Wind Harmer
10.819
270071AF1-092 GEN
Solar/Wind Harmer
10.537
963841AG1-237 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
2.276
24386405FR-21G C
Solar/Wind Harmer
2.284
24386605FR-22G C
Solar/Wind Harmer
2.284
24387005FR-3G C
Solar/Wind Harmer
2.101
24690905MDL-1G C
Solar/Wind Harmer
4.071
270180AB1-006 GEN1
Solar/Wind Harmer
3.646
946581AF1-322 GEN
Solar/Wind Harmer
5.187
24691005MDL-2G C
Solar/Wind Harmer
1.875
24697605MDL-3G C
Solar/Wind Harmer
1.869
24697905MDL-4G C
Solar/Wind Harmer
1.164
270181AB1-006 GEN2
Solar/Wind Harmer
0.363
276785W4-005 GEN1
Solar/Wind Harmer
1.513
276174W4-005 GEN2
Solar/Wind Harmer
1.513
276849AB2-070 GEN2
Solar/Wind Harmer
1.124
276848AB2-070 GEN3
Solar/Wind Harmer
1.124
944221AF1-090 GEN
Solar/Wind Harmer
5.422
276655WTG1_EQ
Solar/Wind Harmer
4.275
276656WTG2_EQ
Solar/Wind Harmer
0.566
959341AF2-225 GEN
Solar/Wind Harmer
7.344
941731AE2-173 GEN
Solar/Wind Harmer
2.847
958391AF2-133 GEN
Solar/Wind Harmer
4.419
270536AF1-215 GEN2
Solar/Wind Harmer
2.186
970169AG2-114 GEN
Solar/Wind Harmer
4.799
274863CRW1-WTG
Solar/Wind Harmer
2.666
274864CRW2-WTG
Solar/Wind Harmer
2.666
965041AG1-368 GEN
Solar/Wind Harmer
4.759
274814UNIV PK N;0U
Adder
2.35
274807UNIV PK N;3U
Adder
2.345
274805UNIV PK N;1U
Adder
2.335
274811UNIV PK N;7U
Adder
2.33
972227AH1-698 GEN1
Adder
1.212
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.597
274731ELWOOD EC;2P
Adder
7.617
274733ELWOOD EC;3P
Adder
7.617
274735ELWOOD EC;4P
Adder
7.617
274728ELWOOD EC;5P
Adder
7.617
274687WILL CNTY;4U
Adder
12.918
274687WILL CNTY;4U
Adder
12.918
274675JOLIET 29;7U
Adder
14.173
274675JOLIET 29;7U
Adder
13.667
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
274746AC1-111 G10
Adder
2.566
274744AC1-111 GEN8
Adder
2.566
274823ROCKFORD ;21
Adder
8.809
252524AE2-267 GEN
Solar/Wind Helper
0.835
270367AC2-061_GEN
Solar/Wind Helper
1.885
241972AD1-140 GEN
Solar/Wind Helper
2.815
270340AC2-060 GEN
Solar/Wind Helper
1.185
339243AC2-075 GEN1
Solar/Wind Helper
0.22
945631AF1-228 GEN
Solar/Wind Helper
0.936
24726405LAWG1A
50/50
5.74
960791AF2-370 GEN
50/50
3.743
961171AF2-408 GEN
50/50
15.013
24728605AND G2
50/50
5.266
942081AE2-220 GEN
Solar/Wind Harmer
15.805
270239V3-007_GEN1
Solar/Wind Harmer
4.254
270005AE1-210 C O1
Solar/Wind Harmer
10.462
965031AG1-367 GEN
Solar/Wind Harmer
19.144
945371AF1-202 GEN
Solar/Wind Harmer
11.502
970825AG2-519 GEN
Solar/Wind Harmer
3.863
958861AF2-177 GEN
Solar/Wind Harmer
16.776
965651AG1-433 GEN
Solar/Wind Harmer
8.063
276903AD2-071 C
Solar/Wind Harmer
13.602
270032AE2-172
Solar/Wind Harmer
6.131
247536S-71 GEN
Solar/Wind Harmer
4.887
970291AG2-192 GEN
Solar/Wind Harmer
1.564
963741AG1-226 GEN
Solar/Wind Harmer
26.2
965011AG1-365 GEN
Solar/Wind Harmer
5.374
24385905FR-11G C
Solar/Wind Harmer
4.414
24387305FR-4G C
Solar/Wind Harmer
2.699
270063AE2-323 C
Solar/Wind Harmer
1.127
24791305MDL-5G
Solar/Wind Harmer
1.223
274880W4-005 GEN4
Solar/Wind Harmer
1.513
963831AG1-236 GEN
Solar/Wind Harmer
4.91
270445AC2-157 GEN2
Solar/Wind Harmer
2.779
276615X2-022 GEN
Solar/Wind Harmer
0.975
972175AH1-670 GEN
Solar/Wind Harmer
6.772
965911AG1-460 GEN
Solar/Wind Harmer
0.69
940581AE2-045 GEN
Solar/Wind Harmer
5.003
971605AH1-302 GEN
Solar/Wind Harmer
4.278
274854TWINGROVE;U2
Solar/Wind Harmer
3.461
276726Z2-087_GEN
Solar/Wind Harmer
3.873
939741AE1-205 GEN
Solar/Wind Harmer
9.793
964861AG1-349 GEN
Solar/Wind Harmer
3.816
971917AH1-482 GEN
Solar/Wind Harmer
4.403
958381AF2-132 GEN
Solar/Wind Harmer
4.4
24639705ELKHART HY
Adder
0.074
270055AF2-134 C O1
Solar/Wind Harmer
1.457
970373AG2-245 GEN
Solar/Wind Harmer
10.009
274751CRETE EC ;1U
Adder
3.842
274754CRETE EC ;4U
Adder
3.842
274723RIVER EC ;12
Adder
8.339
274812UNIV PK N;8U
Adder
2.33
274801UNIV PARK;4U
Adder
2.705
274732ELWOOD EC;7P
Adder
7.617
274674JOLIET 9 ;6U
Adder
7.123
274676JOLIET 29;8U
Adder
14.173
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
274745AC1-111 GEN9
Adder
2.566
274682WAUKEGAN ;7U
Adder
8.211
274828WAUKEGAN ;BP
Adder
5.044
274822ROCKFORD ;11
Adder
8.874
972235AH1-702 GEN1
Adder
1.139
274761LEE CO EC;2U
Adder
1.231
252507AC2-088 GEN
Solar/Wind Helper
1.706
339216AC1-074 GEN
Solar/Wind Helper
0.957
253343AC1-166 GEN
Solar/Wind Helper
0.547
253325AC1-069 GEN
Solar/Wind Helper
0.567
943111AE2-339 GEN
Solar/Wind Helper
0.361
24729405KEY G3
50/50
0.486
24729305KEY G2
50/50
0.478
24729205KEY G1
50/50
0.475
247621Y3-024
50/50
0.306
24728805RICHG1
50/50
4.511
24728905RICHG2
50/50
4.511
24379505HDWTR1G C
Solar/Wind Harmer
19.548
270209AC1-174_GEN
Solar/Wind Harmer
13.796
926881AC1-175 GEN
Solar/Wind Harmer
13.796
970825AG2-519 GEN
Solar/Wind Harmer
17.311
960441AF2-335 GEN
Solar/Wind Harmer
16.096
270383AD1-128 GEN
Solar/Wind Harmer
9.53
944541AF1-119 GEN
Solar/Wind Harmer
6.179
960971AF2-388 GEN
Solar/Wind Harmer
16.125
270599AE1-208 GEN
Solar/Wind Harmer
11.727
270031AE2-169
Solar/Wind Harmer
11.727
964611AG1-324 GEN
Solar/Wind Harmer
1.564
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
6.431
970883AG2-550 GEN
Solar/Wind Harmer
11.853
970885AG2-551 GEN
Solar/Wind Harmer
2.757
942221AE2-234 GEN
Solar/Wind Harmer
0.776
945391AF1-204 GEN
Solar/Wind Harmer
9.285
970241AG2-163 GEN
Solar/Wind Harmer
14.556
970611AG2-400 GEN
Solar/Wind Harmer
5.374
966841AG1-555 GEN
Solar/Wind Harmer
1.332
276763AC1-053 GEN1
Solar/Wind Harmer
1.974
276764AC1-053 GEN2
Solar/Wind Harmer
1.974
270444AC2-157 GEN1
Solar/Wind Harmer
2.779
945421AF1-207 GEN
Solar/Wind Harmer
6.965
957841AF2-078 GEN
Solar/Wind Harmer
2.997
276916AD2-100_GEN
Solar/Wind Harmer
10.395
276911AD2-131_GEN
Solar/Wind Harmer
2.101
957381AF2-032 GEN
Solar/Wind Harmer
0.207
960611AF2-352 GEN
Solar/Wind Harmer
1.141
247620Y3-023
Adder
0.225
270216AD2-079_GEN
Solar/Wind Harmer
0.29
274808UNIV PK N;4U
Adder
2.319
274803UNIV PARK;6U
Adder
2.707
274674JOLIET 9 ;6U
Adder
7.123
972259AH1-714 GEN
Adder
8.825
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
274696ROCKY RD ;4P
Adder
5.21
274695ROCKY RD ;2P
Adder
5.09
274693ROCKY RD ;1P
Adder
5.04
274697ROCKY RD ;3P
Adder
1.383
274683WAUKEGAN ;8U
Adder
9.622
274683WAUKEGAN ;8U
Adder
8.111
274764LEE CO EC;5U
Adder
4.2
274765LEE CO EC;6U
Adder
4.2
252509AD1-136 GEN
Solar/Wind Helper
0.244
25183208HLCRTG
Solar/Wind Helper
2.602
253394AE2-221_GEN
Solar/Wind Helper
1.545
253398AE2-221_GEN2
Solar/Wind Helper
1.545
270186AC1-089 GEN
Solar/Wind Helper
0.823
962581AG1-107 GEN
Solar/Wind Helper
0.942
961491AF2-440 GEN
Solar/Wind Helper
0.039
270518AE2-148 GEN
Solar/Wind Helper
7.331
339221AD2-048_GEN
Solar/Wind Helper
0.779
253378AE2-206_GEN
Solar/Wind Helper
0.65
276820AF1-078_GEN
Solar/Wind Helper
0.303
958821AF2-173 GEN
Solar/Wind Harmer
26.801
270004AE1-209 GEN
Solar/Wind Harmer
10.462
946031AF1-268 GEN
Solar/Wind Harmer
13.344
962031AG1-047 GEN
Solar/Wind Harmer
3.781
957741AF2-068 GEN
Solar/Wind Harmer
18.765
270222AC2-111 GEN
Solar/Wind Harmer
10.014
944531AF1-118 GEN
Solar/Wind Harmer
42.975
970289AG2-191 GEN
Solar/Wind Harmer
0.923
970291AG2-192 GEN
Solar/Wind Harmer
0.839
247642Z2-115 C
Solar/Wind Harmer
0.07
971617AH1-308 GEN
Solar/Wind Harmer
6.273
970193AG2-126 GEN
Solar/Wind Harmer
9.994
270043AE2-236 GEN
Solar/Wind Harmer
3.487
959331AF2-224 GEN
Solar/Wind Harmer
5.374
965021AG1-366 GEN
Solar/Wind Harmer
1.25
970031AG2-029 GEN
Solar/Wind Harmer
16.051
24755605MDL-5G
Solar/Wind Harmer
1.223
970781AG2-491 GEN
Solar/Wind Harmer
5.069
276686W4-005 GEN3
Solar/Wind Harmer
1.513
971993AH1-541 GEN
Solar/Wind Harmer
4.621
276668AB2-070 GEN1
Solar/Wind Harmer
1.124
276621W2-048 GEN
Solar/Wind Harmer
3.106
276838X2-022 GEN2
Solar/Wind Harmer
0.116
942481AE2-261 GEN
Solar/Wind Harmer
14.791
274853TWINGROVE;U1
Solar/Wind Harmer
3.535
965091AG1-374 GEN
Solar/Wind Harmer
14.716
959611AF2-252 GEN
Solar/Wind Harmer
1.141
942111AE2-223 GEN
Solar/Wind Harmer
4.014
959141AF2-205 GEN
Solar/Wind Harmer
2.954
964401AG1-302 GEN
Solar/Wind Harmer
4.4
270535AF1-215 GEN1
Solar/Wind Harmer
2.186
247643Z2-116 C
Solar/Wind Harmer
0.033
274752CRETE EC ;2U
Adder
3.842
274753CRETE EC ;3U
Adder
3.842
274724RIVER EC ;11
Adder
8.239
24642205MAYFLWER
Adder
0.295
972228AH1-698 GEN2
Adder
1.721
274802UNIV PARK;5U
Adder
2.707
274800UNIV PARK;3U
Adder
2.705
972038AH1-567 GEN2
Adder
0.169
274826FISK ;BP
Adder
5.075
274729ELWOOD EC;1P
Adder
7.617
274730ELWOOD EC;6P
Adder
7.617
274734ELWOOD EC;8P
Adder
7.617
274736ELWOOD EC;9P
Adder
7.617
274676JOLIET 29;8U
Adder
13.667
274772LINCOLN ;3U
Adder
3.895
274682WAUKEGAN ;7U
Adder
8.211
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.19
252510AF1-249 C
Solar/Wind Helper
0.565
253406AD2-031_GEN
Solar/Wind Helper
0.857
253415AE1-040 GEN
Solar/Wind Helper
0.538
253338AC1-165 GEN
Solar/Wind Helper
0.547
253333AC1-068 GEN
Solar/Wind Helper
0.567
939401AE1-172 GEN
Solar/Wind Harmer
4.626
944201AF1-088_MTX
Adder
57.869
957141AF2-008_MTX
Adder
28.934
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.286
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.39
MECLTFEXP_MEC->PJM
CLTF
6.961
SIGELTFEXP_SIGE->PJM
CLTF
0.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.516
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
TVALTFEXP_TVA->PJM
CLTF
1.489
NYPJM->LTFIMP_NY
CLTF
0.679
WECLTFEXP_WEC->PJM
CLTF
1.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.323
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.08 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2967.55
MW Contribution:11.85
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
8.873
24726605LAWG1S
50/50
8.864
24726705LAWG2A
50/50
5.965
24726505LAWG1B
50/50
5.923
24726805LAWG2B
50/50
5.905
24729505KEY G4
50/50
8.904
270240V3-007_GEN2
Solar/Wind Harmer
15.295
945581AF1-223 GEN
Solar/Wind Harmer
7.477
970115AG2-085 GEN
Solar/Wind Harmer
6.438
965101AG1-375 GEN
Solar/Wind Harmer
15.348
958711AF2-162 GEN
Solar/Wind Harmer
1.492
24725505WLD G2 C
Solar/Wind Harmer
5.718
24699105WLD G1 C
Solar/Wind Harmer
5.651
270594AE1-207 GEN
Solar/Wind Harmer
19.374
961761AG1-017 GEN
Solar/Wind Harmer
0.535
944031AF1-071 GEN
Solar/Wind Harmer
1.234
965461AG1-414 GEN
Solar/Wind Harmer
2.728
970289AG2-191 GEN
Solar/Wind Harmer
2.286
270543AE2-219 C
Solar/Wind Harmer
6.069
971029AG2-637 GEN
Solar/Wind Harmer
17.299
971673AH1-337 GEN
Solar/Wind Harmer
5.229
270024AE2-089 GEN
Solar/Wind Harmer
5.064
963791AG1-232 GEN
Solar/Wind Harmer
10.819
270071AF1-092 GEN
Solar/Wind Harmer
10.537
963841AG1-237 GEN
Solar/Wind Harmer
6.094
24386205FR-12G C
Solar/Wind Harmer
2.276
24386405FR-21G C
Solar/Wind Harmer
2.284
24386605FR-22G C
Solar/Wind Harmer
2.284
24387005FR-3G C
Solar/Wind Harmer
2.101
24690905MDL-1G C
Solar/Wind Harmer
4.071
270180AB1-006 GEN1
Solar/Wind Harmer
3.646
946581AF1-322 GEN
Solar/Wind Harmer
5.187
24691005MDL-2G C
Solar/Wind Harmer
1.875
24697605MDL-3G C
Solar/Wind Harmer
1.869
24697905MDL-4G C
Solar/Wind Harmer
1.164
270181AB1-006 GEN2
Solar/Wind Harmer
0.363
276785W4-005 GEN1
Solar/Wind Harmer
1.513
276174W4-005 GEN2
Solar/Wind Harmer
1.513
276849AB2-070 GEN2
Solar/Wind Harmer
1.124
276848AB2-070 GEN3
Solar/Wind Harmer
1.124
944221AF1-090 GEN
Solar/Wind Harmer
5.422
276655WTG1_EQ
Solar/Wind Harmer
4.275
276656WTG2_EQ
Solar/Wind Harmer
0.566
959341AF2-225 GEN
Solar/Wind Harmer
7.344
941731AE2-173 GEN
Solar/Wind Harmer
2.847
958391AF2-133 GEN
Solar/Wind Harmer
4.419
270536AF1-215 GEN2
Solar/Wind Harmer
2.186
970169AG2-114 GEN
Solar/Wind Harmer
4.799
274863CRW1-WTG
Solar/Wind Harmer
2.666
274864CRW2-WTG
Solar/Wind Harmer
2.666
965041AG1-368 GEN
Solar/Wind Harmer
4.759
274814UNIV PK N;0U
Adder
2.35
274807UNIV PK N;3U
Adder
2.345
274805UNIV PK N;1U
Adder
2.335
274811UNIV PK N;7U
Adder
2.33
972227AH1-698 GEN1
Adder
1.212
972037AH1-567 GEN1
Adder
0.085
274827FISK ;RP
Adder
3.597
274731ELWOOD EC;2P
Adder
7.617
274733ELWOOD EC;3P
Adder
7.617
274735ELWOOD EC;4P
Adder
7.617
274728ELWOOD EC;5P
Adder
7.617
274687WILL CNTY;4U
Adder
12.918
274687WILL CNTY;4U
Adder
12.918
274675JOLIET 29;7U
Adder
14.173
274675JOLIET 29;7U
Adder
13.667
274775LINCOLN ;6U
Adder
3.895
274776LINCOLN ;7U
Adder
3.895
274777LINCOLN ;8U
Adder
3.895
274746AC1-111 G10
Adder
2.566
274744AC1-111 GEN8
Adder
2.566
274823ROCKFORD ;21
Adder
8.809
252524AE2-267 GEN
Solar/Wind Helper
0.835
270367AC2-061_GEN
Solar/Wind Helper
1.885
241972AD1-140 GEN
Solar/Wind Helper
2.815
270340AC2-060 GEN
Solar/Wind Helper
1.185
339243AC2-075 GEN1
Solar/Wind Helper
0.22
945631AF1-228 GEN
Solar/Wind Helper
0.936
964351AG1-297 GEN
50/50
22.593
961161AF2-407 GEN
50/50
55.693
24728705AND G3
50/50
11.013
24728505AND G1
50/50
5.266
270437AC2-090 C
Solar/Wind Harmer
13.802
270356AE2-297 GEN
Solar/Wind Harmer
10.957
958821AF2-173 GEN
Solar/Wind Harmer
26.801
270004AE1-209 GEN
Solar/Wind Harmer
10.462
946031AF1-268 GEN
Solar/Wind Harmer
13.344
962031AG1-047 GEN
Solar/Wind Harmer
3.781
957741AF2-068 GEN
Solar/Wind Harmer
18.765
270222AC2-111 GEN
Solar/Wind Harmer
10.014
944531AF1-118 GEN
Solar/Wind Harmer
42.975
970289AG2-191 GEN
Solar/Wind Harmer
0.923
970291AG2-192 GEN
Solar/Wind Harmer
0.839
247642Z2-115 C
Solar/Wind Harmer
0.07
971617AH1-308 GEN
Solar/Wind Harmer
6.273
970193AG2-126 GEN
Solar/Wind Harmer
9.994
270043AE2-236 GEN
Solar/Wind Harmer
3.487
959331AF2-224 GEN
Solar/Wind Harmer
5.374
965021AG1-366 GEN
Solar/Wind Harmer
1.25
970031AG2-029 GEN
Solar/Wind Harmer
16.051
24755605MDL-5G
Solar/Wind Harmer
1.223
970781AG2-491 GEN
Solar/Wind Harmer
5.069
276686W4-005 GEN3
Solar/Wind Harmer
1.513
971993AH1-541 GEN
Solar/Wind Harmer
4.621
276668AB2-070 GEN1
Solar/Wind Harmer
1.124
276621W2-048 GEN
Solar/Wind Harmer
3.106
276838X2-022 GEN2
Solar/Wind Harmer
0.116
942481AE2-261 GEN
Solar/Wind Harmer
14.791
274853TWINGROVE;U1
Solar/Wind Harmer
3.535
965091AG1-374 GEN
Solar/Wind Harmer
14.716
959611AF2-252 GEN
Solar/Wind Harmer
1.141
942111AE2-223 GEN
Solar/Wind Harmer
4.014
959141AF2-205 GEN
Solar/Wind Harmer
2.954
964401AG1-302 GEN
Solar/Wind Harmer
4.4
270535AF1-215 GEN1
Solar/Wind Harmer
2.186
247643Z2-116 C
Solar/Wind Harmer
0.033
274752CRETE EC ;2U
Adder
3.842
274753CRETE EC ;3U
Adder
3.842
274724RIVER EC ;11
Adder
8.239
24642205MAYFLWER
Adder
0.295
972228AH1-698 GEN2
Adder
1.721
274802UNIV PARK;5U
Adder
2.707
274800UNIV PARK;3U
Adder
2.705
972038AH1-567 GEN2
Adder
0.169
274826FISK ;BP
Adder
5.075
274729ELWOOD EC;1P
Adder
7.617
274730ELWOOD EC;6P
Adder
7.617
274734ELWOOD EC;8P
Adder
7.617
274736ELWOOD EC;9P
Adder
7.617
274676JOLIET 29;8U
Adder
13.667
274772LINCOLN ;3U
Adder
3.895
274682WAUKEGAN ;7U
Adder
8.211
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.19
252510AF1-249 C
Solar/Wind Helper
0.565
253406AD2-031_GEN
Solar/Wind Helper
0.857
253415AE1-040 GEN
Solar/Wind Helper
0.538
253338AC1-165 GEN
Solar/Wind Helper
0.547
253333AC1-068 GEN
Solar/Wind Helper
0.567
24726405LAWG1A
50/50
5.74
960791AF2-370 GEN
50/50
3.743
961171AF2-408 GEN
50/50
15.013
24728605AND G2
50/50
5.266
942081AE2-220 GEN
Solar/Wind Harmer
15.805
270239V3-007_GEN1
Solar/Wind Harmer
4.254
270005AE1-210 C O1
Solar/Wind Harmer
10.462
965031AG1-367 GEN
Solar/Wind Harmer
19.144
945371AF1-202 GEN
Solar/Wind Harmer
11.502
970825AG2-519 GEN
Solar/Wind Harmer
3.863
958861AF2-177 GEN
Solar/Wind Harmer
16.776
965651AG1-433 GEN
Solar/Wind Harmer
8.063
276903AD2-071 C
Solar/Wind Harmer
13.602
270032AE2-172
Solar/Wind Harmer
6.131
247536S-71 GEN
Solar/Wind Harmer
4.887
970291AG2-192 GEN
Solar/Wind Harmer
1.564
963741AG1-226 GEN
Solar/Wind Harmer
26.2
965011AG1-365 GEN
Solar/Wind Harmer
5.374
24385905FR-11G C
Solar/Wind Harmer
4.414
24387305FR-4G C
Solar/Wind Harmer
2.699
270063AE2-323 C
Solar/Wind Harmer
1.127
24791305MDL-5G
Solar/Wind Harmer
1.223
274880W4-005 GEN4
Solar/Wind Harmer
1.513
963831AG1-236 GEN
Solar/Wind Harmer
4.91
270445AC2-157 GEN2
Solar/Wind Harmer
2.779
276615X2-022 GEN
Solar/Wind Harmer
0.975
972175AH1-670 GEN
Solar/Wind Harmer
6.772
965911AG1-460 GEN
Solar/Wind Harmer
0.69
940581AE2-045 GEN
Solar/Wind Harmer
5.003
971605AH1-302 GEN
Solar/Wind Harmer
4.278
274854TWINGROVE;U2
Solar/Wind Harmer
3.461
24729405KEY G3
50/50
0.486
24729305KEY G2
50/50
0.478
24729205KEY G1
50/50
0.475
247621Y3-024
50/50
0.306
24728805RICHG1
50/50
4.511
24728905RICHG2
50/50
4.511
24379505HDWTR1G C
Solar/Wind Harmer
19.548
270209AC1-174_GEN
Solar/Wind Harmer
13.796
926881AC1-175 GEN
Solar/Wind Harmer
13.796
970825AG2-519 GEN
Solar/Wind Harmer
17.311
960441AF2-335 GEN
Solar/Wind Harmer
16.096
270383AD1-128 GEN
Solar/Wind Harmer
9.53
944541AF1-119 GEN
Solar/Wind Harmer
6.179
960971AF2-388 GEN
Solar/Wind Harmer
16.125
270599AE1-208 GEN
Solar/Wind Harmer
11.727
270031AE2-169
Solar/Wind Harmer
11.727
964611AG1-324 GEN
Solar/Wind Harmer
1.564
964611AG1-324 GEN
Solar/Wind Harmer
0.694
270201AC2-176 GEN
Solar/Wind Harmer
6.431
970883AG2-550 GEN
Solar/Wind Harmer
11.853
970885AG2-551 GEN
Solar/Wind Harmer
2.757
942221AE2-234 GEN
Solar/Wind Harmer
0.776
945391AF1-204 GEN
Solar/Wind Harmer
9.285
970241AG2-163 GEN
Solar/Wind Harmer
14.556
970611AG2-400 GEN
Solar/Wind Harmer
5.374
966841AG1-555 GEN
Solar/Wind Harmer
1.332
276763AC1-053 GEN1
Solar/Wind Harmer
1.974
276764AC1-053 GEN2
Solar/Wind Harmer
1.974
270444AC2-157 GEN1
Solar/Wind Harmer
2.779
945421AF1-207 GEN
Solar/Wind Harmer
6.965
957841AF2-078 GEN
Solar/Wind Harmer
2.997
276916AD2-100_GEN
Solar/Wind Harmer
10.395
276911AD2-131_GEN
Solar/Wind Harmer
2.101
957381AF2-032 GEN
Solar/Wind Harmer
0.207
960611AF2-352 GEN
Solar/Wind Harmer
1.141
247620Y3-023
Adder
0.225
270216AD2-079_GEN
Solar/Wind Harmer
0.29
274808UNIV PK N;4U
Adder
2.319
274803UNIV PARK;6U
Adder
2.707
274674JOLIET 9 ;6U
Adder
7.123
972259AH1-714 GEN
Adder
8.825
274770LINCOLN ;1U
Adder
3.895
274771LINCOLN ;2U
Adder
3.895
274696ROCKY RD ;4P
Adder
5.21
274695ROCKY RD ;2P
Adder
5.09
274693ROCKY RD ;1P
Adder
5.04
274697ROCKY RD ;3P
Adder
1.383
274683WAUKEGAN ;8U
Adder
9.622
274683WAUKEGAN ;8U
Adder
8.111
274764LEE CO EC;5U
Adder
4.2
274765LEE CO EC;6U
Adder
4.2
252509AD1-136 GEN
Solar/Wind Helper
0.244
25183208HLCRTG
Solar/Wind Helper
2.602
253394AE2-221_GEN
Solar/Wind Helper
1.545
253398AE2-221_GEN2
Solar/Wind Helper
1.545
270186AC1-089 GEN
Solar/Wind Helper
0.823
962581AG1-107 GEN
Solar/Wind Helper
0.942
961491AF2-440 GEN
Solar/Wind Helper
0.039
270518AE2-148 GEN
Solar/Wind Helper
7.331
339221AD2-048_GEN
Solar/Wind Helper
0.779
253378AE2-206_GEN
Solar/Wind Helper
0.65
276820AF1-078_GEN
Solar/Wind Helper
0.303
276726Z2-087_GEN
Solar/Wind Harmer
3.873
939741AE1-205 GEN
Solar/Wind Harmer
9.793
964861AG1-349 GEN
Solar/Wind Harmer
3.816
971917AH1-482 GEN
Solar/Wind Harmer
4.403
958381AF2-132 GEN
Solar/Wind Harmer
4.4
24639705ELKHART HY
Adder
0.074
270055AF2-134 C O1
Solar/Wind Harmer
1.457
970373AG2-245 GEN
Solar/Wind Harmer
10.009
274751CRETE EC ;1U
Adder
3.842
274754CRETE EC ;4U
Adder
3.842
274723RIVER EC ;12
Adder
8.339
274812UNIV PK N;8U
Adder
2.33
274801UNIV PARK;4U
Adder
2.705
274732ELWOOD EC;7P
Adder
7.617
274674JOLIET 9 ;6U
Adder
7.123
274676JOLIET 29;8U
Adder
14.173
274773LINCOLN ;4U
Adder
3.895
274774LINCOLN ;5U
Adder
3.895
274745AC1-111 GEN9
Adder
2.566
274682WAUKEGAN ;7U
Adder
8.211
274828WAUKEGAN ;BP
Adder
5.044
274822ROCKFORD ;11
Adder
8.874
972235AH1-702 GEN1
Adder
1.139
274761LEE CO EC;2U
Adder
1.231
252507AC2-088 GEN
Solar/Wind Helper
1.706
339216AC1-074 GEN
Solar/Wind Helper
0.957
253343AC1-166 GEN
Solar/Wind Helper
0.547
253325AC1-069 GEN
Solar/Wind Helper
0.567
943111AE2-339 GEN
Solar/Wind Helper
0.361
939401AE1-172 GEN
Solar/Wind Harmer
4.626
944201AF1-088_MTX
Adder
57.869
957141AF2-008_MTX
Adder
28.934
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.161
CBM West 1LTFEXP_CBM-W1->PJM
CBM
52.286
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.39
MECLTFEXP_MEC->PJM
CLTF
6.961
SIGELTFEXP_SIGE->PJM
CLTF
0.246
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.516
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.171
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
TVALTFEXP_TVA->PJM
CLTF
1.489
NYPJM->LTFIMP_NY
CLTF
0.679
WECLTFEXP_WEC->PJM
CLTF
1.72
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.323
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.179

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.06 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2944.05
MW Contribution:6.0
Bus #Bus NameTypeMW Contribution
964351AG1-297 GEN
50/50
13.725
961161AF2-407 GEN
50/50
35.366
270437AC2-090 C
Solar/Wind Harmer
8.382
270356AE2-297 GEN
Solar/Wind Harmer
6.514
958821AF2-173 GEN
Solar/Wind Harmer
16.664
270004AE1-209 GEN
Solar/Wind Harmer
6.505
946031AF1-268 GEN
Solar/Wind Harmer
8.061
944531AF1-118 GEN
Solar/Wind Harmer
29.596
24728705AND G3
Adder
6.625
24728505AND G1
Adder
3.168
970289AG2-191 GEN
Solar/Wind Harmer
0.631
970291AG2-192 GEN
Solar/Wind Harmer
0.574
247642Z2-115 C
Solar/Wind Harmer
0.05
962031AG1-047 GEN
Solar/Wind Harmer
2.151
957741AF2-068 GEN
Solar/Wind Harmer
10.675
971617AH1-308 GEN
Solar/Wind Harmer
3.734
970193AG2-126 GEN
Solar/Wind Harmer
8.715
270043AE2-236 GEN
Solar/Wind Harmer
2.914
24755605MDL-5G
Solar/Wind Harmer
1.246
970781AG2-491 GEN
Solar/Wind Harmer
5.165
959141AF2-205 GEN
Solar/Wind Harmer
3.049
964401AG1-302 GEN
Solar/Wind Harmer
4.542
970513AG2-328 GEN
Solar/Wind Harmer
8.906
970517AG2-330 GEN
Solar/Wind Harmer
8.077
270535AF1-215 GEN1
Solar/Wind Harmer
2.257
276686W4-005 GEN3
Solar/Wind Harmer
1.484
971993AH1-541 GEN
Solar/Wind Harmer
4.533
276668AB2-070 GEN1
Solar/Wind Harmer
1.103
942111AE2-223 GEN
Solar/Wind Harmer
4.01
274853TWINGROVE;U1
Solar/Wind Harmer
3.521
965091AG1-374 GEN
Solar/Wind Harmer
14.656
959611AF2-252 GEN
Solar/Wind Harmer
1.136
276621W2-048 GEN
Solar/Wind Harmer
3.045
276838X2-022 GEN2
Solar/Wind Harmer
0.114
970349AG2-230 GEN
Solar/Wind Harmer
7.302
942481AE2-261 GEN
Solar/Wind Harmer
14.473
274772LINCOLN ;3U
Adder
4.077
972228AH1-698 GEN2
Adder
1.782
274724RIVER EC ;11
Adder
8.517
274752CRETE EC ;2U
Adder
3.961
274753CRETE EC ;3U
Adder
3.961
274802UNIV PARK;5U
Adder
2.8
274800UNIV PARK;3U
Adder
2.799
972038AH1-567 GEN2
Adder
0.175
274826FISK ;BP
Adder
5.253
274729ELWOOD EC;1P
Adder
7.88
274730ELWOOD EC;6P
Adder
7.88
274734ELWOOD EC;8P
Adder
7.88
274736ELWOOD EC;9P
Adder
7.88
274676JOLIET 29;8U
Adder
14.159
274682WAUKEGAN ;7U
Adder
8.507
252510AF1-249 C
Solar/Wind Helper
0.65
253406AD2-031_GEN
Solar/Wind Helper
0.912
253415AE1-040 GEN
Solar/Wind Helper
0.556
241974AD2-163_GEN2
Solar/Wind Helper
1.068
253338AC1-165 GEN
Solar/Wind Helper
0.598
253333AC1-068 GEN
Solar/Wind Helper
0.62
241955AC1-078 GEN
Solar/Wind Helper
1.022
24726905LAWG2S
50/50
5.151
24726605LAWG1S
50/50
5.146
24726705LAWG2A
50/50
3.463
24726505LAWG1B
50/50
3.439
24726805LAWG2B
50/50
3.428
24729505KEY G4
50/50
6.048
270240V3-007_GEN2
Solar/Wind Harmer
9.288
945581AF1-223 GEN
Solar/Wind Harmer
4.793
965101AG1-375 GEN
Solar/Wind Harmer
9.997
970115AG2-085 GEN
Solar/Wind Harmer
3.981
958711AF2-162 GEN
Solar/Wind Harmer
0.981
24725505WLD G2 C
Solar/Wind Harmer
3.701
24699105WLD G1 C
Solar/Wind Harmer
3.658
270594AE1-207 GEN
Solar/Wind Harmer
12.826
965461AG1-414 GEN
Solar/Wind Harmer
1.866
970289AG2-191 GEN
Solar/Wind Harmer
1.563
961761AG1-017 GEN
Solar/Wind Harmer
0.305
270024AE2-089 GEN
Solar/Wind Harmer
3.015
270543AE2-219 C
Solar/Wind Harmer
3.073
270071AF1-092 GEN
Solar/Wind Harmer
8.674
971029AG2-637 GEN
Solar/Wind Harmer
8.181
963841AG1-237 GEN
Solar/Wind Harmer
5.875
24386205FR-12G C
Solar/Wind Harmer
2.259
24386405FR-21G C
Solar/Wind Harmer
2.267
24386605FR-22G C
Solar/Wind Harmer
2.267
24387005FR-3G C
Solar/Wind Harmer
2.085
963791AG1-232 GEN
Solar/Wind Harmer
7.101
971673AH1-337 GEN
Solar/Wind Harmer
2.402
24690905MDL-1G C
Solar/Wind Harmer
4.148
270180AB1-006 GEN1
Solar/Wind Harmer
3.716
946581AF1-322 GEN
Solar/Wind Harmer
5.286
24691005MDL-2G C
Solar/Wind Harmer
1.911
24697605MDL-3G C
Solar/Wind Harmer
1.905
24697905MDL-4G C
Solar/Wind Harmer
1.186
270181AB1-006 GEN2
Solar/Wind Harmer
0.37
958391AF2-133 GEN
Solar/Wind Harmer
4.561
270536AF1-215 GEN2
Solar/Wind Harmer
2.257
276785W4-005 GEN1
Solar/Wind Harmer
1.484
276174W4-005 GEN2
Solar/Wind Harmer
1.484
276849AB2-070 GEN2
Solar/Wind Harmer
1.103
276848AB2-070 GEN3
Solar/Wind Harmer
1.103
276655WTG1_EQ
Solar/Wind Harmer
4.271
276656WTG2_EQ
Solar/Wind Harmer
0.565
959341AF2-225 GEN
Solar/Wind Harmer
7.337
941731AE2-173 GEN
Solar/Wind Harmer
2.844
971347AH1-153 GEN
Solar/Wind Harmer
7.302
970169AG2-114 GEN
Solar/Wind Harmer
4.858
274863CRW1-WTG
Solar/Wind Harmer
2.711
274864CRW2-WTG
Solar/Wind Harmer
2.711
274775LINCOLN ;6U
Adder
4.077
274776LINCOLN ;7U
Adder
4.077
274777LINCOLN ;8U
Adder
4.077
972227AH1-698 GEN1
Adder
1.255
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274811UNIV PK N;7U
Adder
2.406
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.723
274731ELWOOD EC;2P
Adder
7.88
274733ELWOOD EC;3P
Adder
7.88
274735ELWOOD EC;4P
Adder
7.88
274728ELWOOD EC;5P
Adder
7.88
274687WILL CNTY;4U
Adder
13.379
274687WILL CNTY;4U
Adder
13.379
274675JOLIET 29;7U
Adder
14.684
274675JOLIET 29;7U
Adder
14.159
274746AC1-111 G10
Adder
2.663
274744AC1-111 GEN8
Adder
2.663
252524AE2-267 GEN
Solar/Wind Helper
1.057
241972AD1-140 GEN
Solar/Wind Helper
3.496
270367AC2-061_GEN
Solar/Wind Helper
1.962
253383AE2-342_GEN
Solar/Wind Helper
0.486
241973AD2-163_GEN1
Solar/Wind Helper
1.068
945631AF1-228 GEN
Solar/Wind Helper
1.119
270340AC2-060 GEN
Solar/Wind Helper
1.195
25194708EBND2
50/50
6.252
24729405KEY G3
50/50
0.33
24729305KEY G2
50/50
0.325
24729205KEY G1
50/50
0.323
24379505HDWTR1G C
Solar/Wind Harmer
11.871
270209AC1-174_GEN
Solar/Wind Harmer
8.378
926881AC1-175 GEN
Solar/Wind Harmer
8.378
970825AG2-519 GEN
Solar/Wind Harmer
10.653
960441AF2-335 GEN
Solar/Wind Harmer
9.953
944541AF1-119 GEN
Solar/Wind Harmer
4.062
960971AF2-388 GEN
Solar/Wind Harmer
10.601
270599AE1-208 GEN
Solar/Wind Harmer
7.456
270031AE2-169
Solar/Wind Harmer
7.456
270383AD1-128 GEN
Solar/Wind Harmer
5.371
964611AG1-324 GEN
Solar/Wind Harmer
0.904
964611AG1-324 GEN
Solar/Wind Harmer
0.401
270201AC2-176 GEN
Solar/Wind Harmer
3.659
942221AE2-234 GEN
Solar/Wind Harmer
0.506
247621Y3-024
Adder
0.158
970883AG2-550 GEN
Solar/Wind Harmer
6.001
970885AG2-551 GEN
Solar/Wind Harmer
1.396
945391AF1-204 GEN
Solar/Wind Harmer
8.097
970241AG2-163 GEN
Solar/Wind Harmer
13.684
966841AG1-555 GEN
Solar/Wind Harmer
1.322
270444AC2-157 GEN1
Solar/Wind Harmer
2.938
945421AF1-207 GEN
Solar/Wind Harmer
7.188
957841AF2-078 GEN
Solar/Wind Harmer
3.093
970321AG2-212 GEN
Solar/Wind Harmer
8.906
276763AC1-053 GEN1
Solar/Wind Harmer
1.936
276764AC1-053 GEN2
Solar/Wind Harmer
1.936
960611AF2-352 GEN
Solar/Wind Harmer
1.136
957381AF2-032 GEN
Solar/Wind Harmer
0.203
274770LINCOLN ;1U
Adder
4.077
274771LINCOLN ;2U
Adder
4.077
274808UNIV PK N;4U
Adder
2.396
972259AH1-714 GEN
Adder
9.166
274803UNIV PARK;6U
Adder
2.8
274674JOLIET 9 ;6U
Adder
7.375
24728805RICHG1
Adder
1.799
24728905RICHG2
Adder
1.799
274695ROCKY RD ;2P
Adder
5.276
274693ROCKY RD ;1P
Adder
5.224
274697ROCKY RD ;3P
Adder
1.433
274696ROCKY RD ;4P
Adder
5.4
274683WAUKEGAN ;8U
Adder
9.968
274683WAUKEGAN ;8U
Adder
8.403
25183208HLCRTG
Solar/Wind Helper
2.479
253394AE2-221_GEN
Solar/Wind Helper
1.608
253398AE2-221_GEN2
Solar/Wind Helper
1.608
252509AD1-136 GEN
Solar/Wind Helper
0.195
253378AE2-206_GEN
Solar/Wind Helper
0.993
276820AF1-078_GEN
Solar/Wind Helper
0.464
962581AG1-107 GEN
Solar/Wind Helper
1.011
961491AF2-440 GEN
Solar/Wind Helper
0.041
270518AE2-148 GEN
Solar/Wind Helper
8.654
270186AC1-089 GEN
Solar/Wind Helper
0.816
276916AD2-100_GEN
Solar/Wind Harmer
8.155
276911AD2-131_GEN
Solar/Wind Harmer
1.648
24726405LAWG1A
50/50
3.332
961171AF2-408 GEN
50/50
9.38
960791AF2-370 GEN
50/50
2.315
942081AE2-220 GEN
Solar/Wind Harmer
9.598
270239V3-007_GEN1
Solar/Wind Harmer
2.583
270005AE1-210 C O1
Solar/Wind Harmer
6.505
965031AG1-367 GEN
Solar/Wind Harmer
11.903
945371AF1-202 GEN
Solar/Wind Harmer
7.374
970825AG2-519 GEN
Solar/Wind Harmer
2.377
958861AF2-177 GEN
Solar/Wind Harmer
10.927
965651AG1-433 GEN
Solar/Wind Harmer
5.3
276903AD2-071 C
Solar/Wind Harmer
8.956
270032AE2-172
Solar/Wind Harmer
4.059
24728605AND G2
Adder
3.168
970291AG2-192 GEN
Solar/Wind Harmer
1.07
247536S-71 GEN
Solar/Wind Harmer
2.611
963741AG1-226 GEN
Solar/Wind Harmer
24.631
24385905FR-11G C
Solar/Wind Harmer
4.38
24387305FR-4G C
Solar/Wind Harmer
2.678
270445AC2-157 GEN2
Solar/Wind Harmer
2.938
24791305MDL-5G
Solar/Wind Harmer
1.246
940581AE2-045 GEN
Solar/Wind Harmer
5.164
971605AH1-302 GEN
Solar/Wind Harmer
4.416
964861AG1-349 GEN
Solar/Wind Harmer
3.939
971917AH1-482 GEN
Solar/Wind Harmer
4.546
958381AF2-132 GEN
Solar/Wind Harmer
4.542
970245AG2-165 GEN
Solar/Wind Harmer
8.906
270055AF2-134 C O1
Solar/Wind Harmer
1.504
970373AG2-245 GEN
Solar/Wind Harmer
10.335
274880W4-005 GEN4
Solar/Wind Harmer
1.484
972175AH1-670 GEN
Solar/Wind Harmer
6.69
963831AG1-236 GEN
Solar/Wind Harmer
4.816
276726Z2-087_GEN
Solar/Wind Harmer
3.869
939741AE1-205 GEN
Solar/Wind Harmer
9.783
274854TWINGROVE;U2
Solar/Wind Harmer
3.447
276615X2-022 GEN
Solar/Wind Harmer
0.956
939401AE1-172 GEN
Solar/Wind Harmer
6.756
965911AG1-460 GEN
Solar/Wind Harmer
0.675
274773LINCOLN ;4U
Adder
4.077
274774LINCOLN ;5U
Adder
4.077
274723RIVER EC ;12
Adder
8.618
274751CRETE EC ;1U
Adder
3.961
274754CRETE EC ;4U
Adder
3.961
274812UNIV PK N;8U
Adder
2.406
274801UNIV PARK;4U
Adder
2.799
274732ELWOOD EC;7P
Adder
7.88
274674JOLIET 9 ;6U
Adder
7.375
274676JOLIET 29;8U
Adder
14.684
274745AC1-111 GEN9
Adder
2.663
970091AG2-072 GEN
Adder
36.424
274682WAUKEGAN ;7U
Adder
8.507
274828WAUKEGAN ;BP
Adder
3.651
252507AC2-088 GEN
Solar/Wind Helper
1.367
253343AC1-166 GEN
Solar/Wind Helper
0.598
253325AC1-069 GEN
Solar/Wind Helper
0.62
944201AF1-088_MTX
Adder
61.164
957141AF2-008_MTX
Adder
30.582
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.669
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.429
MECLTFEXP_MEC->PJM
CLTF
7.167
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.718
LAGNLTFEXP_LAGN->PJM
CLTF
4.844
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.764
TVALTFEXP_TVA->PJM
CLTF
1.963
NYPJM->LTFIMP_NY
CLTF
0.66
LGEELTFEXP_LGEE->PJM
CLTF
1.406
WECLTFEXP_WEC->PJM
CLTF
1.779
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.93 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2894.55
MW Contribution:6.07
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.157
24726605LAWG1S
50/50
5.152
24726705LAWG2A
50/50
3.467
24726505LAWG1B
50/50
3.443
24726805LAWG2B
50/50
3.432
24729505KEY G4
50/50
6.086
270240V3-007_GEN2
Solar/Wind Harmer
9.316
945581AF1-223 GEN
Solar/Wind Harmer
4.816
965101AG1-375 GEN
Solar/Wind Harmer
10.049
970115AG2-085 GEN
Solar/Wind Harmer
4
958711AF2-162 GEN
Solar/Wind Harmer
0.986
24725505WLD G2 C
Solar/Wind Harmer
3.717
24699105WLD G1 C
Solar/Wind Harmer
3.673
270594AE1-207 GEN
Solar/Wind Harmer
12.887
965461AG1-414 GEN
Solar/Wind Harmer
1.875
970289AG2-191 GEN
Solar/Wind Harmer
1.571
961761AG1-017 GEN
Solar/Wind Harmer
0.307
270024AE2-089 GEN
Solar/Wind Harmer
3.048
270543AE2-219 C
Solar/Wind Harmer
3.106
270071AF1-092 GEN
Solar/Wind Harmer
8.758
24726405LAWG1A
50/50
3.336
961171AF2-408 GEN
50/50
9.412
960791AF2-370 GEN
50/50
2.326
942081AE2-220 GEN
Solar/Wind Harmer
9.626
270239V3-007_GEN1
Solar/Wind Harmer
2.591
270005AE1-210 C O1
Solar/Wind Harmer
6.53
965031AG1-367 GEN
Solar/Wind Harmer
11.949
945371AF1-202 GEN
Solar/Wind Harmer
7.409
970825AG2-519 GEN
Solar/Wind Harmer
2.388
958861AF2-177 GEN
Solar/Wind Harmer
10.984
964351AG1-297 GEN
50/50
13.747
961161AF2-407 GEN
50/50
35.482
270437AC2-090 C
Solar/Wind Harmer
8.406
270356AE2-297 GEN
Solar/Wind Harmer
6.532
958821AF2-173 GEN
Solar/Wind Harmer
16.729
270004AE1-209 GEN
Solar/Wind Harmer
6.53
946031AF1-268 GEN
Solar/Wind Harmer
8.104
944531AF1-118 GEN
Solar/Wind Harmer
29.794
24728705AND G3
Adder
6.648
24728505AND G1
Adder
3.179
970289AG2-191 GEN
Solar/Wind Harmer
0.635
970291AG2-192 GEN
Solar/Wind Harmer
0.577
247642Z2-115 C
Solar/Wind Harmer
0.05
962031AG1-047 GEN
Solar/Wind Harmer
2.171
957741AF2-068 GEN
Solar/Wind Harmer
10.774
971617AH1-308 GEN
Solar/Wind Harmer
3.776
970193AG2-126 GEN
Solar/Wind Harmer
8.737
270043AE2-236 GEN
Solar/Wind Harmer
2.949
24755605MDL-5G
Solar/Wind Harmer
1.252
970781AG2-491 GEN
Solar/Wind Harmer
5.191
959141AF2-205 GEN
Solar/Wind Harmer
3.068
964401AG1-302 GEN
Solar/Wind Harmer
4.572
970513AG2-328 GEN
Solar/Wind Harmer
8.963
970517AG2-330 GEN
Solar/Wind Harmer
8.129
270535AF1-215 GEN1
Solar/Wind Harmer
2.273
276686W4-005 GEN3
Solar/Wind Harmer
1.489
971993AH1-541 GEN
Solar/Wind Harmer
4.549
276668AB2-070 GEN1
Solar/Wind Harmer
1.107
942111AE2-223 GEN
Solar/Wind Harmer
4.028
970349AG2-230 GEN
Solar/Wind Harmer
7.369
274853TWINGROVE;U1
Solar/Wind Harmer
3.536
965091AG1-374 GEN
Solar/Wind Harmer
14.718
959611AF2-252 GEN
Solar/Wind Harmer
1.141
276621W2-048 GEN
Solar/Wind Harmer
3.055
276838X2-022 GEN2
Solar/Wind Harmer
0.114
274772LINCOLN ;3U
Adder
3.015
274724RIVER EC ;11
Adder
8.577
972228AH1-698 GEN2
Adder
1.794
274752CRETE EC ;2U
Adder
3.99
274753CRETE EC ;3U
Adder
3.99
274802UNIV PARK;5U
Adder
2.819
274800UNIV PARK;3U
Adder
2.818
972038AH1-567 GEN2
Adder
0.176
274826FISK ;BP
Adder
5.288
274729ELWOOD EC;1P
Adder
7.93
274730ELWOOD EC;6P
Adder
7.929
274734ELWOOD EC;8P
Adder
7.929
274736ELWOOD EC;9P
Adder
7.929
274676JOLIET 29;8U
Adder
14.249
274682WAUKEGAN ;7U
Adder
8.557
24642205MAYFLWER
Adder
0.299
252510AF1-249 C
Solar/Wind Helper
0.648
253406AD2-031_GEN
Solar/Wind Helper
0.903
253415AE1-040 GEN
Solar/Wind Helper
0.547
253338AC1-165 GEN
Solar/Wind Helper
0.58
253333AC1-068 GEN
Solar/Wind Helper
0.601
241974AD2-163_GEN2
Solar/Wind Helper
1.018
241955AC1-078 GEN
Solar/Wind Helper
0.969
276897AD1-100 C
Solar/Wind Harmer
12.748
971029AG2-637 GEN
Solar/Wind Harmer
8.278
963841AG1-237 GEN
Solar/Wind Harmer
5.898
963791AG1-232 GEN
Solar/Wind Harmer
7.211
24386205FR-12G C
Solar/Wind Harmer
2.269
24386405FR-21G C
Solar/Wind Harmer
2.277
24386605FR-22G C
Solar/Wind Harmer
2.277
24387005FR-3G C
Solar/Wind Harmer
2.094
971673AH1-337 GEN
Solar/Wind Harmer
2.432
24690905MDL-1G C
Solar/Wind Harmer
4.169
270180AB1-006 GEN1
Solar/Wind Harmer
3.734
946581AF1-322 GEN
Solar/Wind Harmer
5.312
24691005MDL-2G C
Solar/Wind Harmer
1.92
24697605MDL-3G C
Solar/Wind Harmer
1.914
24697905MDL-4G C
Solar/Wind Harmer
1.192
270181AB1-006 GEN2
Solar/Wind Harmer
0.371
958391AF2-133 GEN
Solar/Wind Harmer
4.59
270536AF1-215 GEN2
Solar/Wind Harmer
2.273
276785W4-005 GEN1
Solar/Wind Harmer
1.489
276174W4-005 GEN2
Solar/Wind Harmer
1.489
276849AB2-070 GEN2
Solar/Wind Harmer
1.107
276848AB2-070 GEN3
Solar/Wind Harmer
1.107
276655WTG1_EQ
Solar/Wind Harmer
4.29
276656WTG2_EQ
Solar/Wind Harmer
0.568
959341AF2-225 GEN
Solar/Wind Harmer
7.371
941731AE2-173 GEN
Solar/Wind Harmer
2.857
971347AH1-153 GEN
Solar/Wind Harmer
7.369
970169AG2-114 GEN
Solar/Wind Harmer
4.882
274863CRW1-WTG
Solar/Wind Harmer
2.726
274864CRW2-WTG
Solar/Wind Harmer
2.726
274775LINCOLN ;6U
Adder
3.015
274776LINCOLN ;7U
Adder
3.015
274777LINCOLN ;8U
Adder
3.015
972227AH1-698 GEN1
Adder
1.263
274814UNIV PK N;0U
Adder
2.444
274807UNIV PK N;3U
Adder
2.439
274805UNIV PK N;1U
Adder
2.428
274811UNIV PK N;7U
Adder
2.423
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.748
274731ELWOOD EC;2P
Adder
7.93
274733ELWOOD EC;3P
Adder
7.93
274735ELWOOD EC;4P
Adder
7.93
274728ELWOOD EC;5P
Adder
7.929
274687WILL CNTY;4U
Adder
13.464
274687WILL CNTY;4U
Adder
13.464
274675JOLIET 29;7U
Adder
14.777
274675JOLIET 29;7U
Adder
14.249
274746AC1-111 G10
Adder
2.679
274744AC1-111 GEN8
Adder
2.679
252524AE2-267 GEN
Solar/Wind Helper
1.054
241972AD1-140 GEN
Solar/Wind Helper
3.429
270367AC2-061_GEN
Solar/Wind Helper
1.955
253383AE2-342_GEN
Solar/Wind Helper
0.463
270340AC2-060 GEN
Solar/Wind Helper
1.177
945631AF1-228 GEN
Solar/Wind Helper
1.077
241973AD2-163_GEN1
Solar/Wind Helper
1.018
965651AG1-433 GEN
Solar/Wind Harmer
5.329
276903AD2-071 C
Solar/Wind Harmer
8.995
270032AE2-172
Solar/Wind Harmer
4.078
24728605AND G2
Adder
3.179
970291AG2-192 GEN
Solar/Wind Harmer
1.075
247536S-71 GEN
Solar/Wind Harmer
2.637
963741AG1-226 GEN
Solar/Wind Harmer
24.721
24385905FR-11G C
Solar/Wind Harmer
4.4
24387305FR-4G C
Solar/Wind Harmer
2.69
270445AC2-157 GEN2
Solar/Wind Harmer
2.937
24791305MDL-5G
Solar/Wind Harmer
1.252
940581AE2-045 GEN
Solar/Wind Harmer
5.194
971605AH1-302 GEN
Solar/Wind Harmer
4.442
964861AG1-349 GEN
Solar/Wind Harmer
3.964
971917AH1-482 GEN
Solar/Wind Harmer
4.575
958381AF2-132 GEN
Solar/Wind Harmer
4.572
970245AG2-165 GEN
Solar/Wind Harmer
8.963
270055AF2-134 C O1
Solar/Wind Harmer
1.515
970373AG2-245 GEN
Solar/Wind Harmer
10.413
274880W4-005 GEN4
Solar/Wind Harmer
1.489
972175AH1-670 GEN
Solar/Wind Harmer
6.715
276726Z2-087_GEN
Solar/Wind Harmer
3.886
939741AE1-205 GEN
Solar/Wind Harmer
9.828
963831AG1-236 GEN
Solar/Wind Harmer
4.832
274854TWINGROVE;U2
Solar/Wind Harmer
3.462
276615X2-022 GEN
Solar/Wind Harmer
0.959
939401AE1-172 GEN
Solar/Wind Harmer
6.794
972207SS24-0001
Solar/Wind Harmer
10.72
274773LINCOLN ;4U
Adder
3.015
274774LINCOLN ;5U
Adder
3.015
274723RIVER EC ;12
Adder
8.679
274751CRETE EC ;1U
Adder
3.99
274754CRETE EC ;4U
Adder
3.99
274812UNIV PK N;8U
Adder
2.423
274801UNIV PARK;4U
Adder
2.818
274732ELWOOD EC;7P
Adder
7.929
274674JOLIET 9 ;6U
Adder
7.422
274676JOLIET 29;8U
Adder
14.777
274745AC1-111 GEN9
Adder
2.679
274682WAUKEGAN ;7U
Adder
8.557
274828WAUKEGAN ;BP
Adder
5.256
970091AG2-072 GEN
Adder
36.277
24639705ELKHART HY
Adder
0.072
274822ROCKFORD ;11
Adder
6.484
252507AC2-088 GEN
Solar/Wind Helper
1.361
253343AC1-166 GEN
Solar/Wind Helper
0.58
253325AC1-069 GEN
Solar/Wind Helper
0.601
25194708EBND2
50/50
6.266
24729405KEY G3
50/50
0.332
24729305KEY G2
50/50
0.327
24729205KEY G1
50/50
0.325
24379505HDWTR1G C
Solar/Wind Harmer
11.906
270209AC1-174_GEN
Solar/Wind Harmer
8.403
926881AC1-175 GEN
Solar/Wind Harmer
8.403
970825AG2-519 GEN
Solar/Wind Harmer
10.704
960441AF2-335 GEN
Solar/Wind Harmer
10.001
944541AF1-119 GEN
Solar/Wind Harmer
4.084
960971AF2-388 GEN
Solar/Wind Harmer
10.658
270599AE1-208 GEN
Solar/Wind Harmer
7.497
270031AE2-169
Solar/Wind Harmer
7.497
270383AD1-128 GEN
Solar/Wind Harmer
5.402
964611AG1-324 GEN
Solar/Wind Harmer
0.912
964611AG1-324 GEN
Solar/Wind Harmer
0.405
270201AC2-176 GEN
Solar/Wind Harmer
3.693
942221AE2-234 GEN
Solar/Wind Harmer
0.511
247621Y3-024
Adder
0.159
970883AG2-550 GEN
Solar/Wind Harmer
6.066
970885AG2-551 GEN
Solar/Wind Harmer
1.411
945391AF1-204 GEN
Solar/Wind Harmer
8.117
970241AG2-163 GEN
Solar/Wind Harmer
13.734
966841AG1-555 GEN
Solar/Wind Harmer
1.328
270444AC2-157 GEN1
Solar/Wind Harmer
2.937
945421AF1-207 GEN
Solar/Wind Harmer
7.226
957841AF2-078 GEN
Solar/Wind Harmer
3.11
970321AG2-212 GEN
Solar/Wind Harmer
8.963
276763AC1-053 GEN1
Solar/Wind Harmer
1.942
276764AC1-053 GEN2
Solar/Wind Harmer
1.942
960611AF2-352 GEN
Solar/Wind Harmer
1.141
274770LINCOLN ;1U
Adder
3.015
274771LINCOLN ;2U
Adder
3.015
274808UNIV PK N;4U
Adder
2.412
972259AH1-714 GEN
Adder
9.225
274803UNIV PARK;6U
Adder
2.819
274674JOLIET 9 ;6U
Adder
7.422
24728805RICHG1
Adder
1.818
24728905RICHG2
Adder
1.818
274696ROCKY RD ;4P
Adder
5.432
274695ROCKY RD ;2P
Adder
5.307
274693ROCKY RD ;1P
Adder
5.255
274697ROCKY RD ;3P
Adder
1.442
274683WAUKEGAN ;8U
Adder
10.027
274683WAUKEGAN ;8U
Adder
8.452
25183208HLCRTG
Solar/Wind Helper
2.467
252509AD1-136 GEN
Solar/Wind Helper
0.194
253394AE2-221_GEN
Solar/Wind Helper
1.592
253398AE2-221_GEN2
Solar/Wind Helper
1.592
253378AE2-206_GEN
Solar/Wind Helper
0.968
276820AF1-078_GEN
Solar/Wind Helper
0.452
962581AG1-107 GEN
Solar/Wind Helper
1.007
961491AF2-440 GEN
Solar/Wind Helper
0.041
270186AC1-089 GEN
Solar/Wind Helper
0.814
270518AE2-148 GEN
Solar/Wind Helper
8.413
944201AF1-088_MTX
Adder
61.158
957141AF2-008_MTX
Adder
30.579
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.258
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.271
MECLTFEXP_MEC->PJM
CLTF
7.181
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.453
LAGNLTFEXP_LAGN->PJM
CLTF
4.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.507
TVALTFEXP_TVA->PJM
CLTF
1.913
NYPJM->LTFIMP_NY
CLTF
0.653
LGEELTFEXP_LGEE->PJM
CLTF
1.404
WECLTFEXP_WEC->PJM
CLTF
1.789
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:124.59 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2886.84
MW Contribution:5.99
Bus #Bus NameTypeMW Contribution
24726405LAWG1A
50/50
3.33
961171AF2-408 GEN
50/50
9.356
960791AF2-370 GEN
50/50
2.31
942081AE2-220 GEN
Solar/Wind Harmer
9.585
270239V3-007_GEN1
Solar/Wind Harmer
2.58
270005AE1-210 C O1
Solar/Wind Harmer
6.494
25194708EBND2
50/50
6.245
24729405KEY G3
50/50
0.329
24729305KEY G2
50/50
0.324
24729205KEY G1
50/50
0.322
24379505HDWTR1G C
Solar/Wind Harmer
11.855
270209AC1-174_GEN
Solar/Wind Harmer
8.366
926881AC1-175 GEN
Solar/Wind Harmer
8.366
970825AG2-519 GEN
Solar/Wind Harmer
10.632
960441AF2-335 GEN
Solar/Wind Harmer
9.933
944541AF1-119 GEN
Solar/Wind Harmer
4.054
960971AF2-388 GEN
Solar/Wind Harmer
10.579
270599AE1-208 GEN
Solar/Wind Harmer
7.44
270031AE2-169
Solar/Wind Harmer
7.44
270383AD1-128 GEN
Solar/Wind Harmer
5.36
964611AG1-324 GEN
Solar/Wind Harmer
0.902
964611AG1-324 GEN
Solar/Wind Harmer
0.4
270201AC2-176 GEN
Solar/Wind Harmer
3.652
942221AE2-234 GEN
Solar/Wind Harmer
0.505
247621Y3-024
Adder
0.157
970883AG2-550 GEN
Solar/Wind Harmer
5.989
970885AG2-551 GEN
Solar/Wind Harmer
1.393
945391AF1-204 GEN
Solar/Wind Harmer
8.046
970241AG2-163 GEN
Solar/Wind Harmer
13.598
966841AG1-555 GEN
Solar/Wind Harmer
1.314
270444AC2-157 GEN1
Solar/Wind Harmer
2.913
945421AF1-207 GEN
Solar/Wind Harmer
7.143
957841AF2-078 GEN
Solar/Wind Harmer
3.074
970321AG2-212 GEN
Solar/Wind Harmer
8.853
276763AC1-053 GEN1
Solar/Wind Harmer
1.922
276764AC1-053 GEN2
Solar/Wind Harmer
1.922
960611AF2-352 GEN
Solar/Wind Harmer
1.128
957381AF2-032 GEN
Solar/Wind Harmer
0.201
274770LINCOLN ;1U
Adder
2.977
274771LINCOLN ;2U
Adder
2.977
274808UNIV PK N;4U
Adder
2.382
972259AH1-714 GEN
Adder
9.11
274803UNIV PARK;6U
Adder
2.783
274674JOLIET 9 ;6U
Adder
7.329
24728805RICHG1
Adder
1.793
24728905RICHG2
Adder
1.793
274696ROCKY RD ;4P
Adder
5.365
274695ROCKY RD ;2P
Adder
5.242
274693ROCKY RD ;1P
Adder
5.19
274697ROCKY RD ;3P
Adder
1.424
274683WAUKEGAN ;8U
Adder
9.903
274683WAUKEGAN ;8U
Adder
8.348
25183208HLCRTG
Solar/Wind Helper
2.48
252509AD1-136 GEN
Solar/Wind Helper
0.196
253394AE2-221_GEN
Solar/Wind Helper
1.604
253398AE2-221_GEN2
Solar/Wind Helper
1.604
253378AE2-206_GEN
Solar/Wind Helper
0.989
276820AF1-078_GEN
Solar/Wind Helper
0.462
962581AG1-107 GEN
Solar/Wind Helper
1.013
961491AF2-440 GEN
Solar/Wind Helper
0.042
270186AC1-089 GEN
Solar/Wind Helper
0.819
270518AE2-148 GEN
Solar/Wind Helper
8.518
965031AG1-367 GEN
Solar/Wind Harmer
11.882
945371AF1-202 GEN
Solar/Wind Harmer
7.36
970825AG2-519 GEN
Solar/Wind Harmer
2.372
958861AF2-177 GEN
Solar/Wind Harmer
10.906
965651AG1-433 GEN
Solar/Wind Harmer
5.29
276903AD2-071 C
Solar/Wind Harmer
8.931
270032AE2-172
Solar/Wind Harmer
4.048
24728605AND G2
Adder
3.157
970291AG2-192 GEN
Solar/Wind Harmer
1.066
247536S-71 GEN
Solar/Wind Harmer
2.606
963741AG1-226 GEN
Solar/Wind Harmer
24.476
24385905FR-11G C
Solar/Wind Harmer
4.353
24387305FR-4G C
Solar/Wind Harmer
2.661
270445AC2-157 GEN2
Solar/Wind Harmer
2.913
24791305MDL-5G
Solar/Wind Harmer
1.238
940581AE2-045 GEN
Solar/Wind Harmer
5.133
971605AH1-302 GEN
Solar/Wind Harmer
4.389
964861AG1-349 GEN
Solar/Wind Harmer
3.916
971917AH1-482 GEN
Solar/Wind Harmer
4.519
958381AF2-132 GEN
Solar/Wind Harmer
4.516
970245AG2-165 GEN
Solar/Wind Harmer
8.853
270055AF2-134 C O1
Solar/Wind Harmer
1.496
970373AG2-245 GEN
Solar/Wind Harmer
10.279
274880W4-005 GEN4
Solar/Wind Harmer
1.473
972175AH1-670 GEN
Solar/Wind Harmer
6.642
963831AG1-236 GEN
Solar/Wind Harmer
4.781
276726Z2-087_GEN
Solar/Wind Harmer
3.843
939741AE1-205 GEN
Solar/Wind Harmer
9.717
274854TWINGROVE;U2
Solar/Wind Harmer
3.423
276615X2-022 GEN
Solar/Wind Harmer
0.949
939401AE1-172 GEN
Solar/Wind Harmer
6.713
972207SS24-0001
Solar/Wind Harmer
10.585
274773LINCOLN ;4U
Adder
2.977
274774LINCOLN ;5U
Adder
2.977
274723RIVER EC ;12
Adder
8.568
274751CRETE EC ;1U
Adder
3.939
274754CRETE EC ;4U
Adder
3.939
274812UNIV PK N;8U
Adder
2.392
274801UNIV PARK;4U
Adder
2.783
274732ELWOOD EC;7P
Adder
7.831
274674JOLIET 9 ;6U
Adder
7.329
274676JOLIET 29;8U
Adder
14.593
274745AC1-111 GEN9
Adder
2.646
274682WAUKEGAN ;7U
Adder
8.452
274828WAUKEGAN ;BP
Adder
5.191
970091AG2-072 GEN
Adder
36
24639705ELKHART HY
Adder
0.071
252507AC2-088 GEN
Solar/Wind Helper
1.369
253343AC1-166 GEN
Solar/Wind Helper
0.587
253325AC1-069 GEN
Solar/Wind Helper
0.609
965911AG1-460 GEN
Solar/Wind Harmer
0.553
24726905LAWG2S
50/50
5.148
24726605LAWG1S
50/50
5.143
24726705LAWG2A
50/50
3.461
24726505LAWG1B
50/50
3.436
24726805LAWG2B
50/50
3.426
24729505KEY G4
50/50
6.035
270240V3-007_GEN2
Solar/Wind Harmer
9.275
945581AF1-223 GEN
Solar/Wind Harmer
4.784
965101AG1-375 GEN
Solar/Wind Harmer
9.978
970115AG2-085 GEN
Solar/Wind Harmer
3.973
958711AF2-162 GEN
Solar/Wind Harmer
0.979
24725505WLD G2 C
Solar/Wind Harmer
3.691
24699105WLD G1 C
Solar/Wind Harmer
3.648
270594AE1-207 GEN
Solar/Wind Harmer
12.791
965461AG1-414 GEN
Solar/Wind Harmer
1.86
970289AG2-191 GEN
Solar/Wind Harmer
1.559
961761AG1-017 GEN
Solar/Wind Harmer
0.304
270024AE2-089 GEN
Solar/Wind Harmer
3.009
270543AE2-219 C
Solar/Wind Harmer
3.067
270071AF1-092 GEN
Solar/Wind Harmer
8.644
971029AG2-637 GEN
Solar/Wind Harmer
8.165
963841AG1-237 GEN
Solar/Wind Harmer
5.838
963791AG1-232 GEN
Solar/Wind Harmer
7.086
24386205FR-12G C
Solar/Wind Harmer
2.244
24386405FR-21G C
Solar/Wind Harmer
2.252
24386605FR-22G C
Solar/Wind Harmer
2.252
24387005FR-3G C
Solar/Wind Harmer
2.072
971673AH1-337 GEN
Solar/Wind Harmer
2.397
24690905MDL-1G C
Solar/Wind Harmer
4.122
270180AB1-006 GEN1
Solar/Wind Harmer
3.693
946581AF1-322 GEN
Solar/Wind Harmer
5.253
24691005MDL-2G C
Solar/Wind Harmer
1.899
24697605MDL-3G C
Solar/Wind Harmer
1.893
24697905MDL-4G C
Solar/Wind Harmer
1.178
270181AB1-006 GEN2
Solar/Wind Harmer
0.367
958391AF2-133 GEN
Solar/Wind Harmer
4.534
270536AF1-215 GEN2
Solar/Wind Harmer
2.244
276785W4-005 GEN1
Solar/Wind Harmer
1.473
276174W4-005 GEN2
Solar/Wind Harmer
1.473
276849AB2-070 GEN2
Solar/Wind Harmer
1.095
276848AB2-070 GEN3
Solar/Wind Harmer
1.095
276655WTG1_EQ
Solar/Wind Harmer
4.242
276656WTG2_EQ
Solar/Wind Harmer
0.562
959341AF2-225 GEN
Solar/Wind Harmer
7.288
941731AE2-173 GEN
Solar/Wind Harmer
2.825
971347AH1-153 GEN
Solar/Wind Harmer
7.267
970169AG2-114 GEN
Solar/Wind Harmer
4.826
274863CRW1-WTG
Solar/Wind Harmer
2.693
274864CRW2-WTG
Solar/Wind Harmer
2.693
274775LINCOLN ;6U
Adder
2.977
274776LINCOLN ;7U
Adder
2.977
274777LINCOLN ;8U
Adder
2.977
972227AH1-698 GEN1
Adder
1.247
274814UNIV PK N;0U
Adder
2.413
274807UNIV PK N;3U
Adder
2.408
274805UNIV PK N;1U
Adder
2.397
274811UNIV PK N;7U
Adder
2.392
972037AH1-567 GEN1
Adder
0.087
274827FISK ;RP
Adder
3.701
274731ELWOOD EC;2P
Adder
7.831
274733ELWOOD EC;3P
Adder
7.831
274735ELWOOD EC;4P
Adder
7.831
274728ELWOOD EC;5P
Adder
7.831
274687WILL CNTY;4U
Adder
13.296
274687WILL CNTY;4U
Adder
13.296
274675JOLIET 29;7U
Adder
14.593
274675JOLIET 29;7U
Adder
14.072
274746AC1-111 G10
Adder
2.646
274744AC1-111 GEN8
Adder
2.646
274823ROCKFORD ;21
Adder
6.701
252524AE2-267 GEN
Solar/Wind Helper
1.057
241972AD1-140 GEN
Solar/Wind Helper
3.469
270367AC2-061_GEN
Solar/Wind Helper
1.966
253383AE2-342_GEN
Solar/Wind Helper
0.475
270340AC2-060 GEN
Solar/Wind Helper
1.188
241973AD2-163_GEN1
Solar/Wind Helper
1.045
945631AF1-228 GEN
Solar/Wind Helper
1.093
964351AG1-297 GEN
50/50
13.7
961161AF2-407 GEN
50/50
35.274
270437AC2-090 C
Solar/Wind Harmer
8.37
270356AE2-297 GEN
Solar/Wind Harmer
6.504
958821AF2-173 GEN
Solar/Wind Harmer
16.635
270004AE1-209 GEN
Solar/Wind Harmer
6.494
946031AF1-268 GEN
Solar/Wind Harmer
8.045
944531AF1-118 GEN
Solar/Wind Harmer
29.531
24728705AND G3
Adder
6.602
24728505AND G1
Adder
3.157
970289AG2-191 GEN
Solar/Wind Harmer
0.63
970291AG2-192 GEN
Solar/Wind Harmer
0.572
247642Z2-115 C
Solar/Wind Harmer
0.05
962031AG1-047 GEN
Solar/Wind Harmer
2.147
957741AF2-068 GEN
Solar/Wind Harmer
10.655
971617AH1-308 GEN
Solar/Wind Harmer
3.727
970193AG2-126 GEN
Solar/Wind Harmer
8.66
270043AE2-236 GEN
Solar/Wind Harmer
2.905
24755605MDL-5G
Solar/Wind Harmer
1.238
970781AG2-491 GEN
Solar/Wind Harmer
5.133
959141AF2-205 GEN
Solar/Wind Harmer
3.031
964401AG1-302 GEN
Solar/Wind Harmer
4.516
970513AG2-328 GEN
Solar/Wind Harmer
8.853
970517AG2-330 GEN
Solar/Wind Harmer
8.029
270535AF1-215 GEN1
Solar/Wind Harmer
2.244
276686W4-005 GEN3
Solar/Wind Harmer
1.473
971993AH1-541 GEN
Solar/Wind Harmer
4.5
276668AB2-070 GEN1
Solar/Wind Harmer
1.095
942111AE2-223 GEN
Solar/Wind Harmer
3.983
274853TWINGROVE;U1
Solar/Wind Harmer
3.497
965091AG1-374 GEN
Solar/Wind Harmer
14.554
959611AF2-252 GEN
Solar/Wind Harmer
1.128
970349AG2-230 GEN
Solar/Wind Harmer
7.267
276621W2-048 GEN
Solar/Wind Harmer
3.023
276838X2-022 GEN2
Solar/Wind Harmer
0.113
274772LINCOLN ;3U
Adder
2.977
972228AH1-698 GEN2
Adder
1.771
274724RIVER EC ;11
Adder
8.467
274752CRETE EC ;2U
Adder
3.939
274753CRETE EC ;3U
Adder
3.939
274800UNIV PARK;3U
Adder
2.783
274802UNIV PARK;5U
Adder
2.783
972038AH1-567 GEN2
Adder
0.174
274826FISK ;BP
Adder
5.222
274729ELWOOD EC;1P
Adder
7.831
274730ELWOOD EC;6P
Adder
7.831
274734ELWOOD EC;8P
Adder
7.831
274736ELWOOD EC;9P
Adder
7.831
274676JOLIET 29;8U
Adder
14.072
274682WAUKEGAN ;7U
Adder
8.452
252510AF1-249 C
Solar/Wind Helper
0.65
253406AD2-031_GEN
Solar/Wind Helper
0.91
253415AE1-040 GEN
Solar/Wind Helper
0.552
241974AD2-163_GEN2
Solar/Wind Helper
1.045
253338AC1-165 GEN
Solar/Wind Helper
0.587
253333AC1-068 GEN
Solar/Wind Helper
0.609
241955AC1-078 GEN
Solar/Wind Helper
0.99
942481AE2-261 GEN
Solar/Wind Harmer
11.858
944201AF1-088_MTX
Adder
60.646
957141AF2-008_MTX
Adder
30.323
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.372
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.198
MECLTFEXP_MEC->PJM
CLTF
7.101
SIGELTFEXP_SIGE->PJM
CLTF
0.232
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.032
LAGNLTFEXP_LAGN->PJM
CLTF
4.723
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.547
TVALTFEXP_TVA->PJM
CLTF
1.897
NYPJM->LTFIMP_NY
CLTF
0.638
LGEELTFEXP_LGEE->PJM
CLTF
1.377
WECLTFEXP_WEC->PJM
CLTF
1.767
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.175

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:118.23 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2739.4
MW Contribution:4.23
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.157
24726605LAWG1S
50/50
5.152
24726705LAWG2A
50/50
3.467
24726505LAWG1B
50/50
3.443
24726805LAWG2B
50/50
3.432
24729505KEY G4
50/50
6.086
270240V3-007_GEN2
Solar/Wind Harmer
0.003
945581AF1-223 GEN
Solar/Wind Harmer
0.001
965101AG1-375 GEN
Solar/Wind Harmer
7.011
970115AG2-085 GEN
Solar/Wind Harmer
2.799
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.048
270594AE1-207 GEN
Solar/Wind Harmer
6.851
970289AG2-191 GEN
Solar/Wind Harmer
1.096
270024AE2-089 GEN
Solar/Wind Harmer
0.005
270543AE2-219 C
Solar/Wind Harmer
0.003
270071AF1-092 GEN
Solar/Wind Harmer
7.808
971029AG2-637 GEN
Solar/Wind Harmer
5.775
963841AG1-237 GEN
Solar/Wind Harmer
1.631
963791AG1-232 GEN
Solar/Wind Harmer
5.031
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
971673AH1-337 GEN
Solar/Wind Harmer
2.397
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971611AH1-305 GEN
Solar/Wind Harmer
2.115
958391AF2-133 GEN
Solar/Wind Harmer
0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.125
276848AB2-070 GEN3
Solar/Wind Harmer
0.125
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.6
941731AE2-173 GEN
Solar/Wind Harmer
2.857
971347AH1-153 GEN
Solar/Wind Harmer
5.141
970169AG2-114 GEN
Solar/Wind Harmer
3.406
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274775LINCOLN ;6U
Adder
4.104
274776LINCOLN ;7U
Adder
4.104
274777LINCOLN ;8U
Adder
4.104
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
972227AH1-698 GEN1
Adder
1.263
944221AF1-090 GEN
Solar/Wind Harmer
1.982
960591AF2-350 GEN
Solar/Wind Harmer
3.378
274814UNIV PK N;0U
Adder
2.444
274807UNIV PK N;3U
Adder
2.439
274805UNIV PK N;1U
Adder
2.428
274811UNIV PK N;7U
Adder
2.423
972037AH1-567 GEN1
Adder
0.088
274827FISK ;RP
Adder
3.748
970833AG2-524 GEN
Solar/Wind Harmer
3.704
970833AG2-524 GEN
Solar/Wind Harmer
2.47
274731ELWOOD EC;2P
Adder
7.93
274733ELWOOD EC;3P
Adder
7.93
274735ELWOOD EC;4P
Adder
7.93
274728ELWOOD EC;5P
Adder
7.929
274687WILL CNTY;4U
Adder
13.464
964351AG1-297 GEN
50/50
13.747
961161AF2-407 GEN
50/50
35.482
24728705AND G3
50/50
7.054
24728505AND G1
50/50
3.373
270437AC2-090 C
Solar/Wind Harmer
0.005
270356AE2-297 GEN
Solar/Wind Harmer
0.013
958821AF2-173 GEN
Solar/Wind Harmer
11.671
270004AE1-209 GEN
Solar/Wind Harmer
1.806
946031AF1-268 GEN
Solar/Wind Harmer
6.483
944531AF1-118 GEN
Solar/Wind Harmer
26.617
970289AG2-191 GEN
Solar/Wind Harmer
0.635
970291AG2-192 GEN
Solar/Wind Harmer
0.577
24726405LAWG1A
50/50
3.336
961171AF2-408 GEN
50/50
9.412
960791AF2-370 GEN
50/50
2.332
24728605AND G2
50/50
3.373
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
7.702
970773AG2-487 GEN
Solar/Wind Harmer
1.765
270005AE1-210 C O1
Solar/Wind Harmer
1.806
965031AG1-367 GEN
Solar/Wind Harmer
8.337
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.512
958861AF2-177 GEN
Solar/Wind Harmer
3.038
965651AG1-433 GEN
Solar/Wind Harmer
1.996
276903AD2-071 C
Solar/Wind Harmer
7.007
270032AE2-172
Solar/Wind Harmer
4.078
970291AG2-192 GEN
Solar/Wind Harmer
0.75
247536S-71 GEN
Solar/Wind Harmer
0.183
963741AG1-226 GEN
Solar/Wind Harmer
9.071
24385905FR-11G C
Solar/Wind Harmer
0.001
25194708EBND2
50/50
6.266
24729405KEY G3
50/50
0.332
24729305KEY G2
50/50
0.327
24729205KEY G1
50/50
0.325
247621Y3-024
50/50
0.169
24379505HDWTR1G C
Solar/Wind Harmer
0.003
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
7.843
960441AF2-335 GEN
Solar/Wind Harmer
6.997
944541AF1-119 GEN
Solar/Wind Harmer
0.456
960971AF2-388 GEN
Solar/Wind Harmer
3.991
270599AE1-208 GEN
Solar/Wind Harmer
5.883
270031AE2-169
Solar/Wind Harmer
3.53
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
2.936
964611AG1-324 GEN
Solar/Wind Harmer
0.405
270201AC2-176 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.024
970883AG2-550 GEN
Solar/Wind Harmer
4.232
970885AG2-551 GEN
Solar/Wind Harmer
1.411
945391AF1-204 GEN
Solar/Wind Harmer
4.318
970241AG2-163 GEN
Solar/Wind Harmer
2.236
966841AG1-555 GEN
Solar/Wind Harmer
0.418
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.691
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.517
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.141
274770LINCOLN ;1U
Adder
4.104
274771LINCOLN ;2U
Adder
4.104
276916AD2-100_GEN
Solar/Wind Harmer
7.107
276911AD2-131_GEN
Solar/Wind Harmer
0.468
965681AG1-436 GEN
Solar/Wind Harmer
4.229
965791AG1-447 GEN
Solar/Wind Harmer
3.101
274888KELLY CRK;1U
Solar/Wind Harmer
0.198
274887GEN-1.85
Solar/Wind Harmer
0.089
276843GEN-1.7
Solar/Wind Harmer
0.109
958011AF2-095 GEN
Solar/Wind Harmer
4.864
274808UNIV PK N;4U
Adder
2.412
972259AH1-714 GEN
Adder
9.225
274803UNIV PARK;6U
Adder
2.819
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274674JOLIET 9 ;6U
Adder
7.422
24728805RICHG1
Adder
1.818
24728905RICHG2
Adder
1.818
958481AF2-142 GEN
Solar/Wind Harmer
5.024
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.453
958491AF2-143 GEN
Solar/Wind Harmer
5.012
24441505OLIV SLR
Solar/Wind Harmer
0
274879MINONK ;1U
Solar/Wind Harmer
0.141
270526AF1-158 GEN
Solar/Wind Harmer
0.004
971573AH1-285 GEN
Solar/Wind Harmer
0.621
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274696ROCKY RD ;4P
Adder
5.432
274695ROCKY RD ;2P
Adder
5.307
274693ROCKY RD ;1P
Adder
5.255
274697ROCKY RD ;3P
Adder
1.442
274683WAUKEGAN ;8U
Adder
10.027
274683WAUKEGAN ;8U
Adder
8.452
962691AG1-118 GEN
Solar/Wind Harmer
9.946
970921AG2-575 GEN
Solar/Wind Harmer
3.312
970921AG2-575 GEN
Solar/Wind Harmer
1.104
270216AD2-079_GEN
Solar/Wind Harmer
0
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.13
276646AC1-214 GEN2
Solar/Wind Harmer
0.13
942991AE2-321 GEN
Solar/Wind Harmer
3.685
276782AC1-033 GEN
Solar/Wind Harmer
0
971333AH1-146 GEN
Solar/Wind Harmer
6.586
971335AH1-147 GEN
Solar/Wind Harmer
6.586
971341AH1-150 GEN
Solar/Wind Harmer
6.576
247642Z2-115 C
Solar/Wind Harmer
0.002
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.517
971617AH1-308 GEN
Solar/Wind Harmer
3.776
970193AG2-126 GEN
Solar/Wind Harmer
6.096
270043AE2-236 GEN
Solar/Wind Harmer
2.401
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.622
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.517
970517AG2-330 GEN
Solar/Wind Harmer
9.105
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.587
276668AB2-070 GEN1
Solar/Wind Harmer
0.125
942111AE2-223 GEN
Solar/Wind Harmer
1.114
970349AG2-230 GEN
Solar/Wind Harmer
5.141
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.269
959611AF2-252 GEN
Solar/Wind Harmer
1.141
276621W2-048 GEN
Solar/Wind Harmer
0.172
276838X2-022 GEN2
Solar/Wind Harmer
0.192
274772LINCOLN ;3U
Adder
4.104
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
942481AE2-261 GEN
Solar/Wind Harmer
10.124
274724RIVER EC ;11
Adder
8.577
972228AH1-698 GEN2
Adder
1.794
276806AD2-047 C O1
Solar/Wind Harmer
1.914
970941AG2-585 GEN
Solar/Wind Harmer
4.222
274752CRETE EC ;2U
Adder
3.99
274753CRETE EC ;3U
Adder
3.99
274802UNIV PARK;5U
Adder
2.819
274800UNIV PARK;3U
Adder
2.818
972038AH1-567 GEN2
Adder
0.176
274826FISK ;BP
Adder
5.288
970707AG2-453 GEN
Solar/Wind Harmer
11.009
276893AG1-478 C
Solar/Wind Harmer
0.133
274729ELWOOD EC;1P
Adder
7.93
274730ELWOOD EC;6P
Adder
7.929
274734ELWOOD EC;8P
Adder
7.929
274736ELWOOD EC;9P
Adder
7.929
274676JOLIET 29;8U
Adder
14.249
276694AA1-018 GEN2
Solar/Wind Harmer
0
943121AE2-341 GEN
Solar/Wind Harmer
5.605
943591AF1-030 GEN
Solar/Wind Harmer
3.727
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
6.644
274682WAUKEGAN ;7U
Adder
8.557
247643Z2-116 C
Solar/Wind Harmer
0
970031AG2-029 GEN
Solar/Wind Harmer
2.153
274872LEEDK;1U
Solar/Wind Harmer
0.121
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.352
274855GSG-6 ;RU
Solar/Wind Harmer
0.121
274850MENDOTA H;RU
Solar/Wind Harmer
0.039
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.059
274878BISHOP HL;2U
Solar/Wind Harmer
0.111
959091AF2-200 GEN
Solar/Wind Harmer
6.576
276157O29GEN1
Solar/Wind Harmer
0.527
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
2.628
965931AG1-462 GEN
Solar/Wind Harmer
8.158
270222AC2-111 GEN
Solar/Wind Harmer
1.616
970243AG2-164 GEN
Solar/Wind Harmer
1.864
970519AG2-331 GEN
Solar/Wind Harmer
8.287
970699AG2-449 GEN
Solar/Wind Harmer
0.797
24441205WTRV SLR C
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Helper
0.648
253406AD2-031_GEN
Solar/Wind Helper
0.903
253415AE1-040 GEN
Solar/Wind Helper
0.547
253338AC1-165 GEN
Solar/Wind Helper
0.58
253333AC1-068 GEN
Solar/Wind Helper
0.601
241974AD2-163_GEN2
Solar/Wind Helper
1.018
241955AC1-078 GEN
Solar/Wind Helper
0.969
971343AH1-151 GEN
Solar/Wind Harmer
6.576
274856ECOGROVE ;U1
Solar/Wind Harmer
0.077
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.85
276741O09 GEN1
Solar/Wind Harmer
0.116
276708O09 GEN2
Solar/Wind Harmer
0.116
276603SUBLETTE C
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
961051AF2-396 GEN
Solar/Wind Harmer
6.438
961051AF2-396 GEN
Solar/Wind Harmer
4.292
970239AG2-162 GEN
Solar/Wind Harmer
0.797
25183208HLCRTG
Solar/Wind Helper
2.467
252509AD1-136 GEN
Solar/Wind Helper
0.194
253394AE2-221_GEN
Solar/Wind Helper
1.592
274687WILL CNTY;4U
Adder
13.464
274675JOLIET 29;7U
Adder
14.777
274675JOLIET 29;7U
Adder
14.249
274746AC1-111 G10
Adder
2.679
274744AC1-111 GEN8
Adder
2.679
971769AH1-391 GEN
Solar/Wind Harmer
3.73
276868AE1-113 GEN
Solar/Wind Harmer
0.67
276882AE2-255 GEN
Solar/Wind Harmer
0.39
926823AC1-168 GEN
Solar/Wind Harmer
0.566
971771AH1-392 GEN
Solar/Wind Harmer
3.324
957751AF2-069 GEN
Solar/Wind Harmer
0.109
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
2.035
971675AH1-338 GEN
Solar/Wind Harmer
1.286
971411AH1-196 GEN
Solar/Wind Harmer
4.94
971171AH1-044 GEN
Solar/Wind Harmer
6.576
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.259
961011AF2-392 GEN
Solar/Wind Harmer
1.909
971619AH1-309 GEN
Solar/Wind Harmer
1.46
946321AF1-296 GEN
Solar/Wind Harmer
1.796
252524AE2-267 GEN
Solar/Wind Helper
1.054
241972AD1-140 GEN
Solar/Wind Helper
3.429
270367AC2-061_GEN
Solar/Wind Helper
1.955
253383AE2-342_GEN
Solar/Wind Helper
0.463
270340AC2-060 GEN
Solar/Wind Helper
1.177
945631AF1-228 GEN
Solar/Wind Helper
1.077
241973AD2-163_GEN1
Solar/Wind Helper
1.018
253398AE2-221_GEN2
Solar/Wind Helper
1.592
253378AE2-206_GEN
Solar/Wind Helper
0.968
276820AF1-078_GEN
Solar/Wind Helper
0.452
962581AG1-107 GEN
Solar/Wind Helper
1.007
961491AF2-440 GEN
Solar/Wind Helper
0.041
270186AC1-089 GEN
Solar/Wind Helper
0.814
270518AE2-148 GEN
Solar/Wind Helper
8.413
24387305FR-4G C
Solar/Wind Harmer
0.001
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.442
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.575
958381AF2-132 GEN
Solar/Wind Harmer
0.001
970245AG2-165 GEN
Solar/Wind Harmer
1.517
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
7.265
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.835
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.8
963831AG1-236 GEN
Solar/Wind Harmer
1.336
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276615X2-022 GEN
Solar/Wind Harmer
0.036
939401AE1-172 GEN
Solar/Wind Harmer
2.544
274773LINCOLN ;4U
Adder
4.104
274774LINCOLN ;5U
Adder
4.104
941551AE2-152 GEN
Solar/Wind Harmer
0
965911AG1-460 GEN
Solar/Wind Harmer
0.677
274723RIVER EC ;12
Adder
8.679
276776AD2-060 GEN
Solar/Wind Harmer
0.353
274751CRETE EC ;1U
Adder
3.99
274754CRETE EC ;4U
Adder
3.99
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
2.423
274801UNIV PARK;4U
Adder
2.818
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.929
274674JOLIET 9 ;6U
Adder
7.422
274676JOLIET 29;8U
Adder
14.777
276901AD2-066 C O1
Solar/Wind Harmer
0.003
276691AA1-018 GEN1
Solar/Wind Harmer
0.406
971997AH1-543 GEN
Solar/Wind Harmer
1.755
274745AC1-111 GEN9
Adder
2.679
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
970569AG2-363 GEN
Solar/Wind Harmer
9.966
274682WAUKEGAN ;7U
Adder
8.557
274828WAUKEGAN ;BP
Adder
5.256
962781AG1-127 GEN
Solar/Wind Harmer
3.152
274872LEEDK;1U
Solar/Wind Harmer
0.002
970091AG2-072 GEN
Adder
34.24
276861AD2-134 GEN
Solar/Wind Harmer
0.059
274877BISHOP HL;1U
Solar/Wind Harmer
0.111
957471AF2-041 GEN
Solar/Wind Harmer
9.864
959081AF2-199 GEN
Solar/Wind Harmer
3.288
971067AG2-660 GEN
Solar/Wind Harmer
1.096
970819AG2-516 GEN
Solar/Wind Harmer
3.925
971475AH1-234 GEN
Solar/Wind Harmer
1.584
276158O29GEN2
Solar/Wind Harmer
0
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
270063AE2-323 C
Solar/Wind Harmer
0.003
270505AE1-170 C O1
Solar/Wind Harmer
3.407
945111AF1-176 GEN
Solar/Wind Harmer
5.786
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
1.673
970333AG2-219 GEN
Solar/Wind Harmer
2.279
252507AC2-088 GEN
Solar/Wind Helper
1.361
253343AC1-166 GEN
Solar/Wind Helper
0.58
253325AC1-069 GEN
Solar/Wind Helper
0.601
944201AF1-088_MTX
Adder
61.158
957141AF2-008_MTX
Adder
30.579
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.258
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.271
MECLTFEXP_MEC->PJM
CLTF
7.181
SIGELTFEXP_SIGE->PJM
CLTF
0.234
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.453
LAGNLTFEXP_LAGN->PJM
CLTF
4.763
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.507
TVALTFEXP_TVA->PJM
CLTF
1.913
NYPJM->LTFIMP_NY
CLTF
0.653
LGEELTFEXP_LGEE->PJM
CLTF
1.404
WECLTFEXP_WEC->PJM
CLTF
1.789
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.91 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2685.57
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
25194708EBND2
50/50
7.982
24729405KEY G3
50/50
0.345
24729305KEY G2
50/50
0.339
24729205KEY G1
50/50
0.337
24379505HDWTR1G C
Solar/Wind Harmer
13.653
270209AC1-174_GEN
Solar/Wind Harmer
9.636
926881AC1-175 GEN
Solar/Wind Harmer
9.636
970825AG2-519 GEN
Solar/Wind Harmer
12.024
960441AF2-335 GEN
Solar/Wind Harmer
11.21
944541AF1-119 GEN
Solar/Wind Harmer
4.366
960971AF2-388 GEN
Solar/Wind Harmer
11.395
270383AD1-128 GEN
Solar/Wind Harmer
6.27
270599AE1-208 GEN
Solar/Wind Harmer
8.225
270031AE2-169
Solar/Wind Harmer
8.225
964611AG1-324 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
0.459
270201AC2-176 GEN
Solar/Wind Harmer
4.193
247621Y3-024
Adder
0.183
942221AE2-234 GEN
Solar/Wind Harmer
0.537
970883AG2-550 GEN
Solar/Wind Harmer
7.207
970885AG2-551 GEN
Solar/Wind Harmer
1.676
24728805RICHG1
Adder
2.375
24728905RICHG2
Adder
2.375
945391AF1-204 GEN
Solar/Wind Harmer
8.299
270444AC2-157 GEN1
Solar/Wind Harmer
3.001
970241AG2-163 GEN
Solar/Wind Harmer
13.41
966841AG1-555 GEN
Solar/Wind Harmer
1.256
945421AF1-207 GEN
Solar/Wind Harmer
6.621
957841AF2-078 GEN
Solar/Wind Harmer
2.849
276916AD2-100_GEN
Solar/Wind Harmer
9.759
276911AD2-131_GEN
Solar/Wind Harmer
1.972
957381AF2-032 GEN
Solar/Wind Harmer
0.194
276763AC1-053 GEN1
Solar/Wind Harmer
1.831
276764AC1-053 GEN2
Solar/Wind Harmer
1.831
960611AF2-352 GEN
Solar/Wind Harmer
1.048
970239AG2-162 GEN
Solar/Wind Harmer
4.766
25183208HLCRTG
Solar/Wind Helper
2.675
252509AD1-136 GEN
Solar/Wind Helper
0.237
253394AE2-221_GEN
Solar/Wind Helper
1.661
253398AE2-221_GEN2
Solar/Wind Helper
1.661
962581AG1-107 GEN
Solar/Wind Helper
1.055
961491AF2-440 GEN
Solar/Wind Helper
0.043
964351AG1-297 GEN
50/50
16.103
961161AF2-407 GEN
50/50
40.105
24728705AND G3
50/50
8.003
24728505AND G1
50/50
3.826
270437AC2-090 C
Solar/Wind Harmer
9.64
270356AE2-297 GEN
Solar/Wind Harmer
7.616
958821AF2-173 GEN
Solar/Wind Harmer
18.799
270004AE1-209 GEN
Solar/Wind Harmer
7.338
946031AF1-268 GEN
Solar/Wind Harmer
9.149
970289AG2-191 GEN
Solar/Wind Harmer
0.681
970291AG2-192 GEN
Solar/Wind Harmer
0.619
944531AF1-118 GEN
Solar/Wind Harmer
30.566
247642Z2-115 C
Solar/Wind Harmer
0.053
962031AG1-047 GEN
Solar/Wind Harmer
2.465
957741AF2-068 GEN
Solar/Wind Harmer
12.235
971617AH1-308 GEN
Solar/Wind Harmer
4.134
270222AC2-111 GEN
Solar/Wind Harmer
5.175
970193AG2-126 GEN
Solar/Wind Harmer
8.932
24755605MDL-5G
Solar/Wind Harmer
1.159
970781AG2-491 GEN
Solar/Wind Harmer
4.807
270043AE2-236 GEN
Solar/Wind Harmer
2.619
942481AE2-261 GEN
Solar/Wind Harmer
13.86
276686W4-005 GEN3
Solar/Wind Harmer
1.401
971993AH1-541 GEN
Solar/Wind Harmer
4.281
276668AB2-070 GEN1
Solar/Wind Harmer
1.041
276621W2-048 GEN
Solar/Wind Harmer
2.888
276838X2-022 GEN2
Solar/Wind Harmer
0.108
959141AF2-205 GEN
Solar/Wind Harmer
2.76
274853TWINGROVE;U1
Solar/Wind Harmer
3.249
965091AG1-374 GEN
Solar/Wind Harmer
13.523
959611AF2-252 GEN
Solar/Wind Harmer
1.048
964401AG1-302 GEN
Solar/Wind Harmer
4.075
942111AE2-223 GEN
Solar/Wind Harmer
3.676
270535AF1-215 GEN1
Solar/Wind Harmer
2.004
970243AG2-164 GEN
Solar/Wind Harmer
11.191
970519AG2-331 GEN
Solar/Wind Harmer
7.518
970699AG2-449 GEN
Solar/Wind Harmer
4.974
252510AF1-249 C
Solar/Wind Helper
0.645
253406AD2-031_GEN
Solar/Wind Helper
0.941
253415AE1-040 GEN
Solar/Wind Helper
0.581
253338AC1-165 GEN
Solar/Wind Helper
0.588
253333AC1-068 GEN
Solar/Wind Helper
0.61
241974AD2-163_GEN2
Solar/Wind Helper
0.951
241955AC1-078 GEN
Solar/Wind Helper
0.919
24726905LAWG2S
50/50
6.149
24726605LAWG1S
50/50
6.143
24726705LAWG2A
50/50
4.134
24726505LAWG1B
50/50
4.105
24726805LAWG2B
50/50
4.092
24729505KEY G4
50/50
6.321
270240V3-007_GEN2
Solar/Wind Harmer
10.683
945581AF1-223 GEN
Solar/Wind Harmer
5.266
970115AG2-085 GEN
Solar/Wind Harmer
4.484
965101AG1-375 GEN
Solar/Wind Harmer
10.832
958711AF2-162 GEN
Solar/Wind Harmer
1.055
24725505WLD G2 C
Solar/Wind Harmer
4.115
24699105WLD G1 C
Solar/Wind Harmer
4.067
270594AE1-207 GEN
Solar/Wind Harmer
14.029
965461AG1-414 GEN
Solar/Wind Harmer
2.013
970289AG2-191 GEN
Solar/Wind Harmer
1.687
961761AG1-017 GEN
Solar/Wind Harmer
0.349
270543AE2-219 C
Solar/Wind Harmer
3.69
270024AE2-089 GEN
Solar/Wind Harmer
3.337
971029AG2-637 GEN
Solar/Wind Harmer
10.114
971673AH1-337 GEN
Solar/Wind Harmer
3.006
944031AF1-071 GEN
Solar/Wind Harmer
0.638
963791AG1-232 GEN
Solar/Wind Harmer
7.285
270071AF1-092 GEN
Solar/Wind Harmer
8.082
963841AG1-237 GEN
Solar/Wind Harmer
5.673
24386205FR-12G C
Solar/Wind Harmer
2.145
24386405FR-21G C
Solar/Wind Harmer
2.153
24386605FR-22G C
Solar/Wind Harmer
2.153
24387005FR-3G C
Solar/Wind Harmer
1.98
24690905MDL-1G C
Solar/Wind Harmer
3.86
270180AB1-006 GEN1
Solar/Wind Harmer
3.458
946581AF1-322 GEN
Solar/Wind Harmer
4.919
24691005MDL-2G C
Solar/Wind Harmer
1.778
24697605MDL-3G C
Solar/Wind Harmer
1.773
24697905MDL-4G C
Solar/Wind Harmer
1.103
270181AB1-006 GEN2
Solar/Wind Harmer
0.344
944221AF1-090 GEN
Solar/Wind Harmer
5.122
276785W4-005 GEN1
Solar/Wind Harmer
1.401
276174W4-005 GEN2
Solar/Wind Harmer
1.401
276849AB2-070 GEN2
Solar/Wind Harmer
1.041
276848AB2-070 GEN3
Solar/Wind Harmer
1.041
958391AF2-133 GEN
Solar/Wind Harmer
4.113
276655WTG1_EQ
Solar/Wind Harmer
3.915
276656WTG2_EQ
Solar/Wind Harmer
0.518
959341AF2-225 GEN
Solar/Wind Harmer
6.727
941731AE2-173 GEN
Solar/Wind Harmer
2.607
270536AF1-215 GEN2
Solar/Wind Harmer
2.004
970169AG2-114 GEN
Solar/Wind Harmer
4.374
274863CRW1-WTG
Solar/Wind Harmer
2.424
274864CRW2-WTG
Solar/Wind Harmer
2.424
252524AE2-267 GEN
Solar/Wind Helper
1.02
241972AD1-140 GEN
Solar/Wind Helper
3.377
270367AC2-061_GEN
Solar/Wind Helper
2.057
270340AC2-060 GEN
Solar/Wind Helper
1.268
945631AF1-228 GEN
Solar/Wind Helper
1.057
253383AE2-342_GEN
Solar/Wind Helper
0.424
241973AD2-163_GEN1
Solar/Wind Helper
0.951
339243AC2-075 GEN1
Solar/Wind Helper
0.195
253378AE2-206_GEN
Solar/Wind Helper
0.901
276820AF1-078_GEN
Solar/Wind Helper
0.421
270186AC1-089 GEN
Solar/Wind Helper
0.87
270518AE2-148 GEN
Solar/Wind Helper
8.356
339221AD2-048_GEN
Solar/Wind Helper
0.686
24726405LAWG1A
50/50
3.978
961171AF2-408 GEN
50/50
10.692
960791AF2-370 GEN
50/50
2.607
24728605AND G2
50/50
3.826
942081AE2-220 GEN
Solar/Wind Harmer
11.039
270239V3-007_GEN1
Solar/Wind Harmer
2.971
270005AE1-210 C O1
Solar/Wind Harmer
7.338
965031AG1-367 GEN
Solar/Wind Harmer
13.428
945371AF1-202 GEN
Solar/Wind Harmer
8.101
970825AG2-519 GEN
Solar/Wind Harmer
2.683
958861AF2-177 GEN
Solar/Wind Harmer
11.84
965651AG1-433 GEN
Solar/Wind Harmer
5.698
276903AD2-071 C
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
4.44
970291AG2-192 GEN
Solar/Wind Harmer
1.154
247536S-71 GEN
Solar/Wind Harmer
3.066
270445AC2-157 GEN2
Solar/Wind Harmer
3.001
963741AG1-226 GEN
Solar/Wind Harmer
24.139
24385905FR-11G C
Solar/Wind Harmer
4.16
24387305FR-4G C
Solar/Wind Harmer
2.543
24791305MDL-5G
Solar/Wind Harmer
1.159
970091AG2-072 GEN
Adder
36.334
965911AG1-460 GEN
Solar/Wind Harmer
0.647
274880W4-005 GEN4
Solar/Wind Harmer
1.401
963831AG1-236 GEN
Solar/Wind Harmer
4.554
276615X2-022 GEN
Solar/Wind Harmer
0.907
940581AE2-045 GEN
Solar/Wind Harmer
4.696
971605AH1-302 GEN
Solar/Wind Harmer
4.016
972175AH1-670 GEN
Solar/Wind Harmer
6.25
274854TWINGROVE;U2
Solar/Wind Harmer
3.181
964861AG1-349 GEN
Solar/Wind Harmer
3.537
971917AH1-482 GEN
Solar/Wind Harmer
4.082
958381AF2-132 GEN
Solar/Wind Harmer
4.075
276726Z2-087_GEN
Solar/Wind Harmer
3.547
939741AE1-205 GEN
Solar/Wind Harmer
8.969
270055AF2-134 C O1
Solar/Wind Harmer
1.336
970333AG2-219 GEN
Solar/Wind Harmer
13.677
252507AC2-088 GEN
Solar/Wind Helper
1.662
253343AC1-166 GEN
Solar/Wind Helper
0.588
253325AC1-069 GEN
Solar/Wind Helper
0.61
339216AC1-074 GEN
Solar/Wind Helper
0.847
970373AG2-245 GEN
Solar/Wind Harmer
3.827
944201AF1-088_MTX
Adder
62.484
957141AF2-008_MTX
Adder
31.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.259
MECLTFEXP_MEC->PJM
CLTF
6.56
SIGELTFEXP_SIGE->PJM
CLTF
0.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.883
LAGNLTFEXP_LAGN->PJM
CLTF
4.567
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.198
TVALTFEXP_TVA->PJM
CLTF
1.859
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
1.558
WECLTFEXP_WEC->PJM
CLTF
1.569
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P7-1_#485___SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#485___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2685.44
MW Contribution:7.21
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
6.149
24726605LAWG1S
50/50
6.143
24726705LAWG2A
50/50
4.134
24726505LAWG1B
50/50
4.105
24726805LAWG2B
50/50
4.092
24729505KEY G4
50/50
6.321
270240V3-007_GEN2
Solar/Wind Harmer
10.683
945581AF1-223 GEN
Solar/Wind Harmer
5.266
970115AG2-085 GEN
Solar/Wind Harmer
4.484
965101AG1-375 GEN
Solar/Wind Harmer
10.832
958711AF2-162 GEN
Solar/Wind Harmer
1.055
24725505WLD G2 C
Solar/Wind Harmer
4.115
24699105WLD G1 C
Solar/Wind Harmer
4.067
270594AE1-207 GEN
Solar/Wind Harmer
14.029
965461AG1-414 GEN
Solar/Wind Harmer
2.013
970289AG2-191 GEN
Solar/Wind Harmer
1.687
961761AG1-017 GEN
Solar/Wind Harmer
0.349
270543AE2-219 C
Solar/Wind Harmer
3.69
270024AE2-089 GEN
Solar/Wind Harmer
3.337
971029AG2-637 GEN
Solar/Wind Harmer
10.114
971673AH1-337 GEN
Solar/Wind Harmer
3.006
944031AF1-071 GEN
Solar/Wind Harmer
0.638
963791AG1-232 GEN
Solar/Wind Harmer
7.285
270071AF1-092 GEN
Solar/Wind Harmer
8.082
24726405LAWG1A
50/50
3.978
961171AF2-408 GEN
50/50
10.692
960791AF2-370 GEN
50/50
2.607
24728605AND G2
50/50
3.826
942081AE2-220 GEN
Solar/Wind Harmer
11.039
270239V3-007_GEN1
Solar/Wind Harmer
2.971
270005AE1-210 C O1
Solar/Wind Harmer
7.338
965031AG1-367 GEN
Solar/Wind Harmer
13.428
945371AF1-202 GEN
Solar/Wind Harmer
8.101
970825AG2-519 GEN
Solar/Wind Harmer
2.683
958861AF2-177 GEN
Solar/Wind Harmer
11.84
965651AG1-433 GEN
Solar/Wind Harmer
5.698
276903AD2-071 C
Solar/Wind Harmer
9.873
270032AE2-172
Solar/Wind Harmer
4.44
970291AG2-192 GEN
Solar/Wind Harmer
1.154
247536S-71 GEN
Solar/Wind Harmer
3.066
270445AC2-157 GEN2
Solar/Wind Harmer
3.001
963741AG1-226 GEN
Solar/Wind Harmer
24.139
24385905FR-11G C
Solar/Wind Harmer
4.16
24387305FR-4G C
Solar/Wind Harmer
2.543
24791305MDL-5G
Solar/Wind Harmer
1.159
970091AG2-072 GEN
Adder
36.334
965911AG1-460 GEN
Solar/Wind Harmer
0.647
274880W4-005 GEN4
Solar/Wind Harmer
1.401
963831AG1-236 GEN
Solar/Wind Harmer
4.554
276615X2-022 GEN
Solar/Wind Harmer
0.907
940581AE2-045 GEN
Solar/Wind Harmer
4.696
971605AH1-302 GEN
Solar/Wind Harmer
4.016
972175AH1-670 GEN
Solar/Wind Harmer
6.25
274854TWINGROVE;U2
Solar/Wind Harmer
3.181
964861AG1-349 GEN
Solar/Wind Harmer
3.537
971917AH1-482 GEN
Solar/Wind Harmer
4.082
958381AF2-132 GEN
Solar/Wind Harmer
4.075
276726Z2-087_GEN
Solar/Wind Harmer
3.547
939741AE1-205 GEN
Solar/Wind Harmer
8.969
270055AF2-134 C O1
Solar/Wind Harmer
1.336
970333AG2-219 GEN
Solar/Wind Harmer
13.677
252507AC2-088 GEN
Solar/Wind Helper
1.662
253343AC1-166 GEN
Solar/Wind Helper
0.588
253325AC1-069 GEN
Solar/Wind Helper
0.61
339216AC1-074 GEN
Solar/Wind Helper
0.847
970373AG2-245 GEN
Solar/Wind Harmer
3.827
964351AG1-297 GEN
50/50
16.103
961161AF2-407 GEN
50/50
40.105
24728705AND G3
50/50
8.003
24728505AND G1
50/50
3.826
270437AC2-090 C
Solar/Wind Harmer
9.64
270356AE2-297 GEN
Solar/Wind Harmer
7.616
958821AF2-173 GEN
Solar/Wind Harmer
18.799
270004AE1-209 GEN
Solar/Wind Harmer
7.338
946031AF1-268 GEN
Solar/Wind Harmer
9.149
970289AG2-191 GEN
Solar/Wind Harmer
0.681
970291AG2-192 GEN
Solar/Wind Harmer
0.619
944531AF1-118 GEN
Solar/Wind Harmer
30.566
247642Z2-115 C
Solar/Wind Harmer
0.053
962031AG1-047 GEN
Solar/Wind Harmer
2.465
957741AF2-068 GEN
Solar/Wind Harmer
12.235
971617AH1-308 GEN
Solar/Wind Harmer
4.134
270222AC2-111 GEN
Solar/Wind Harmer
5.175
970193AG2-126 GEN
Solar/Wind Harmer
8.932
24755605MDL-5G
Solar/Wind Harmer
1.159
970781AG2-491 GEN
Solar/Wind Harmer
4.807
270043AE2-236 GEN
Solar/Wind Harmer
2.619
942481AE2-261 GEN
Solar/Wind Harmer
13.86
276686W4-005 GEN3
Solar/Wind Harmer
1.401
971993AH1-541 GEN
Solar/Wind Harmer
4.281
276668AB2-070 GEN1
Solar/Wind Harmer
1.041
276621W2-048 GEN
Solar/Wind Harmer
2.888
276838X2-022 GEN2
Solar/Wind Harmer
0.108
959141AF2-205 GEN
Solar/Wind Harmer
2.76
274853TWINGROVE;U1
Solar/Wind Harmer
3.249
965091AG1-374 GEN
Solar/Wind Harmer
13.523
959611AF2-252 GEN
Solar/Wind Harmer
1.048
964401AG1-302 GEN
Solar/Wind Harmer
4.075
942111AE2-223 GEN
Solar/Wind Harmer
3.676
270535AF1-215 GEN1
Solar/Wind Harmer
2.004
970243AG2-164 GEN
Solar/Wind Harmer
11.191
970519AG2-331 GEN
Solar/Wind Harmer
7.518
970699AG2-449 GEN
Solar/Wind Harmer
4.974
252510AF1-249 C
Solar/Wind Helper
0.645
253406AD2-031_GEN
Solar/Wind Helper
0.941
253415AE1-040 GEN
Solar/Wind Helper
0.581
253338AC1-165 GEN
Solar/Wind Helper
0.588
253333AC1-068 GEN
Solar/Wind Helper
0.61
241974AD2-163_GEN2
Solar/Wind Helper
0.951
241955AC1-078 GEN
Solar/Wind Helper
0.919
25194708EBND2
50/50
7.982
24729405KEY G3
50/50
0.345
24729305KEY G2
50/50
0.339
24729205KEY G1
50/50
0.337
24379505HDWTR1G C
Solar/Wind Harmer
13.653
270209AC1-174_GEN
Solar/Wind Harmer
9.636
926881AC1-175 GEN
Solar/Wind Harmer
9.636
970825AG2-519 GEN
Solar/Wind Harmer
12.024
960441AF2-335 GEN
Solar/Wind Harmer
11.21
944541AF1-119 GEN
Solar/Wind Harmer
4.366
960971AF2-388 GEN
Solar/Wind Harmer
11.395
270383AD1-128 GEN
Solar/Wind Harmer
6.27
270599AE1-208 GEN
Solar/Wind Harmer
8.225
270031AE2-169
Solar/Wind Harmer
8.225
964611AG1-324 GEN
Solar/Wind Harmer
1.034
964611AG1-324 GEN
Solar/Wind Harmer
0.459
270201AC2-176 GEN
Solar/Wind Harmer
4.193
247621Y3-024
Adder
0.183
942221AE2-234 GEN
Solar/Wind Harmer
0.537
970883AG2-550 GEN
Solar/Wind Harmer
7.207
970885AG2-551 GEN
Solar/Wind Harmer
1.676
24728805RICHG1
Adder
2.375
24728905RICHG2
Adder
2.375
945391AF1-204 GEN
Solar/Wind Harmer
8.299
270444AC2-157 GEN1
Solar/Wind Harmer
3.001
970241AG2-163 GEN
Solar/Wind Harmer
13.41
966841AG1-555 GEN
Solar/Wind Harmer
1.256
945421AF1-207 GEN
Solar/Wind Harmer
6.621
957841AF2-078 GEN
Solar/Wind Harmer
2.849
276916AD2-100_GEN
Solar/Wind Harmer
9.759
276911AD2-131_GEN
Solar/Wind Harmer
1.972
957381AF2-032 GEN
Solar/Wind Harmer
0.194
276763AC1-053 GEN1
Solar/Wind Harmer
1.831
276764AC1-053 GEN2
Solar/Wind Harmer
1.831
960611AF2-352 GEN
Solar/Wind Harmer
1.048
970239AG2-162 GEN
Solar/Wind Harmer
4.766
25183208HLCRTG
Solar/Wind Helper
2.675
252509AD1-136 GEN
Solar/Wind Helper
0.237
253394AE2-221_GEN
Solar/Wind Helper
1.661
253398AE2-221_GEN2
Solar/Wind Helper
1.661
962581AG1-107 GEN
Solar/Wind Helper
1.055
961491AF2-440 GEN
Solar/Wind Helper
0.043
253378AE2-206_GEN
Solar/Wind Helper
0.901
276820AF1-078_GEN
Solar/Wind Helper
0.421
270186AC1-089 GEN
Solar/Wind Helper
0.87
270518AE2-148 GEN
Solar/Wind Helper
8.356
339221AD2-048_GEN
Solar/Wind Helper
0.686
963841AG1-237 GEN
Solar/Wind Harmer
5.673
24386205FR-12G C
Solar/Wind Harmer
2.145
24386405FR-21G C
Solar/Wind Harmer
2.153
24386605FR-22G C
Solar/Wind Harmer
2.153
24387005FR-3G C
Solar/Wind Harmer
1.98
24690905MDL-1G C
Solar/Wind Harmer
3.86
270180AB1-006 GEN1
Solar/Wind Harmer
3.458
946581AF1-322 GEN
Solar/Wind Harmer
4.919
24691005MDL-2G C
Solar/Wind Harmer
1.778
24697605MDL-3G C
Solar/Wind Harmer
1.773
24697905MDL-4G C
Solar/Wind Harmer
1.103
270181AB1-006 GEN2
Solar/Wind Harmer
0.344
944221AF1-090 GEN
Solar/Wind Harmer
5.122
276785W4-005 GEN1
Solar/Wind Harmer
1.401
276174W4-005 GEN2
Solar/Wind Harmer
1.401
276849AB2-070 GEN2
Solar/Wind Harmer
1.041
276848AB2-070 GEN3
Solar/Wind Harmer
1.041
958391AF2-133 GEN
Solar/Wind Harmer
4.113
276655WTG1_EQ
Solar/Wind Harmer
3.915
276656WTG2_EQ
Solar/Wind Harmer
0.518
959341AF2-225 GEN
Solar/Wind Harmer
6.727
941731AE2-173 GEN
Solar/Wind Harmer
2.607
270536AF1-215 GEN2
Solar/Wind Harmer
2.004
970169AG2-114 GEN
Solar/Wind Harmer
4.374
274863CRW1-WTG
Solar/Wind Harmer
2.424
274864CRW2-WTG
Solar/Wind Harmer
2.424
252524AE2-267 GEN
Solar/Wind Helper
1.02
241972AD1-140 GEN
Solar/Wind Helper
3.377
270367AC2-061_GEN
Solar/Wind Helper
2.057
270340AC2-060 GEN
Solar/Wind Helper
1.268
945631AF1-228 GEN
Solar/Wind Helper
1.057
253383AE2-342_GEN
Solar/Wind Helper
0.424
241973AD2-163_GEN1
Solar/Wind Helper
0.951
339243AC2-075 GEN1
Solar/Wind Helper
0.195
944201AF1-088_MTX
Adder
62.484
957141AF2-008_MTX
Adder
31.242
CBM West 1LTFEXP_CBM-W1->PJM
CBM
47.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.259
MECLTFEXP_MEC->PJM
CLTF
6.56
SIGELTFEXP_SIGE->PJM
CLTF
0.255
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.883
LAGNLTFEXP_LAGN->PJM
CLTF
4.567
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.198
TVALTFEXP_TVA->PJM
CLTF
1.859
NYPJM->LTFIMP_NY
CLTF
0.616
LGEELTFEXP_LGEE->PJM
CLTF
1.558
WECLTFEXP_WEC->PJM
CLTF
1.569
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.055
AG2-052LTFEXP_AG2-052->PJM
LTF
0.106
AH1-155LTFEXP_AH1-155->PJM
LTF
0.159

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o DEOK_P4_1579_EASTBEND_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1579_EASTBEND_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.77 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2566.43
MW Contribution:6.07
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
5.818
24726605LAWG1S
50/50
5.812
24726705LAWG2A
50/50
3.911
24726505LAWG1B
50/50
3.884
24726805LAWG2B
50/50
3.872
270240V3-007_GEN2
Solar/Wind Harmer
9.951
945581AF1-223 GEN
Solar/Wind Harmer
4.851
970115AG2-085 GEN
Solar/Wind Harmer
4.09
965101AG1-375 GEN
Solar/Wind Harmer
9.965
958711AF2-162 GEN
Solar/Wind Harmer
0.969
24725505WLD G2 C
Solar/Wind Harmer
3.76
24699105WLD G1 C
Solar/Wind Harmer
3.715
270594AE1-207 GEN
Solar/Wind Harmer
12.795
24729505KEY G4
Adder
5.458
965461AG1-414 GEN
Solar/Wind Harmer
1.835
970289AG2-191 GEN
Solar/Wind Harmer
1.538
961761AG1-017 GEN
Solar/Wind Harmer
0.307
270024AE2-089 GEN
Solar/Wind Harmer
2.933
270543AE2-219 C
Solar/Wind Harmer
3.109
971029AG2-637 GEN
Solar/Wind Harmer
8.299
971673AH1-337 GEN
Solar/Wind Harmer
2.438
270071AF1-092 GEN
Solar/Wind Harmer
7.279
963791AG1-232 GEN
Solar/Wind Harmer
6.373
963841AG1-237 GEN
Solar/Wind Harmer
5.151
944031AF1-071 GEN
Solar/Wind Harmer
0.473
24386205FR-12G C
Solar/Wind Harmer
1.948
24386405FR-21G C
Solar/Wind Harmer
1.955
24386605FR-22G C
Solar/Wind Harmer
1.955
24387005FR-3G C
Solar/Wind Harmer
1.798
24690905MDL-1G C
Solar/Wind Harmer
3.504
270180AB1-006 GEN1
Solar/Wind Harmer
3.139
946581AF1-322 GEN
Solar/Wind Harmer
4.465
24691005MDL-2G C
Solar/Wind Harmer
1.614
24697605MDL-3G C
Solar/Wind Harmer
1.609
24697905MDL-4G C
Solar/Wind Harmer
1.002
270181AB1-006 GEN2
Solar/Wind Harmer
0.312
252524AE2-267 GEN
Solar/Wind Helper
1.139
241972AD1-140 GEN
Solar/Wind Helper
3.771
270367AC2-061_GEN
Solar/Wind Helper
2.308
24726405LAWG1A
50/50
3.764
961171AF2-408 GEN
50/50
9.769
960791AF2-370 GEN
50/50
2.378
942081AE2-220 GEN
Solar/Wind Harmer
10.283
270239V3-007_GEN1
Solar/Wind Harmer
2.768
270005AE1-210 C O1
Solar/Wind Harmer
6.778
965031AG1-367 GEN
Solar/Wind Harmer
12.403
945371AF1-202 GEN
Solar/Wind Harmer
7.462
970825AG2-519 GEN
Solar/Wind Harmer
2.448
958861AF2-177 GEN
Solar/Wind Harmer
10.891
965651AG1-433 GEN
Solar/Wind Harmer
5.237
276903AD2-071 C
Solar/Wind Harmer
9.015
270032AE2-172
Solar/Wind Harmer
4.049
24728605AND G2
Adder
3.251
970291AG2-192 GEN
Solar/Wind Harmer
1.052
247536S-71 GEN
Solar/Wind Harmer
2.634
270445AC2-157 GEN2
Solar/Wind Harmer
2.743
963741AG1-226 GEN
Solar/Wind Harmer
21.914
24385905FR-11G C
Solar/Wind Harmer
3.777
24387305FR-4G C
Solar/Wind Harmer
2.309
970091AG2-072 GEN
Adder
34
24791305MDL-5G
Solar/Wind Harmer
1.052
252507AC2-088 GEN
Solar/Wind Helper
1.774
253343AC1-166 GEN
Solar/Wind Helper
0.648
253325AC1-069 GEN
Solar/Wind Helper
0.671
339216AC1-074 GEN
Solar/Wind Helper
0.968
943111AE2-339 GEN
Solar/Wind Helper
0.37
25194708EBND2
50/50
13.331
24379505HDWTR1G C
Solar/Wind Harmer
12.719
270209AC1-174_GEN
Solar/Wind Harmer
8.976
926881AC1-175 GEN
Solar/Wind Harmer
8.976
970825AG2-519 GEN
Solar/Wind Harmer
10.969
960441AF2-335 GEN
Solar/Wind Harmer
10.226
944541AF1-119 GEN
Solar/Wind Harmer
4.013
960971AF2-388 GEN
Solar/Wind Harmer
10.473
270599AE1-208 GEN
Solar/Wind Harmer
7.49
270031AE2-169
Solar/Wind Harmer
7.49
270383AD1-128 GEN
Solar/Wind Harmer
5.557
964611AG1-324 GEN
Solar/Wind Harmer
0.917
964611AG1-324 GEN
Solar/Wind Harmer
0.407
270201AC2-176 GEN
Solar/Wind Harmer
3.69
247621Y3-024
Adder
0.158
942221AE2-234 GEN
Solar/Wind Harmer
0.481
970883AG2-550 GEN
Solar/Wind Harmer
6.072
970885AG2-551 GEN
Solar/Wind Harmer
1.412
945391AF1-204 GEN
Solar/Wind Harmer
7.532
270444AC2-157 GEN1
Solar/Wind Harmer
2.743
24728805RICHG1
Adder
1.851
24728905RICHG2
Adder
1.851
970241AG2-163 GEN
Solar/Wind Harmer
12.174
966841AG1-555 GEN
Solar/Wind Harmer
1.14
25183208HLCRTG
Solar/Wind Helper
3.041
252509AD1-136 GEN
Solar/Wind Helper
0.253
253394AE2-221_GEN
Solar/Wind Helper
1.882
253398AE2-221_GEN2
Solar/Wind Helper
1.882
962581AG1-107 GEN
Solar/Wind Helper
1.183
961491AF2-440 GEN
Solar/Wind Helper
0.049
253378AE2-206_GEN
Solar/Wind Helper
1.009
276820AF1-078_GEN
Solar/Wind Helper
0.472
270186AC1-089 GEN
Solar/Wind Helper
0.977
270518AE2-148 GEN
Solar/Wind Helper
9.191
339221AD2-048_GEN
Solar/Wind Helper
0.797
270340AC2-060 GEN
Solar/Wind Helper
1.341
945631AF1-228 GEN
Solar/Wind Helper
1.149
253383AE2-342_GEN
Solar/Wind Helper
0.467
241973AD2-163_GEN1
Solar/Wind Helper
1.045
339243AC2-075 GEN1
Solar/Wind Helper
0.223
964351AG1-297 GEN
50/50
15.023
961161AF2-407 GEN
50/50
36.754
270437AC2-090 C
Solar/Wind Harmer
8.98
270356AE2-297 GEN
Solar/Wind Harmer
7.046
958821AF2-173 GEN
Solar/Wind Harmer
17.364
270004AE1-209 GEN
Solar/Wind Harmer
6.778
946031AF1-268 GEN
Solar/Wind Harmer
8.306
24728705AND G3
Adder
6.799
24728505AND G1
Adder
3.251
970289AG2-191 GEN
Solar/Wind Harmer
0.621
970291AG2-192 GEN
Solar/Wind Harmer
0.565
944531AF1-118 GEN
Solar/Wind Harmer
27.973
247642Z2-115 C
Solar/Wind Harmer
0.048
962031AG1-047 GEN
Solar/Wind Harmer
2.169
957741AF2-068 GEN
Solar/Wind Harmer
10.766
971617AH1-308 GEN
Solar/Wind Harmer
3.633
970193AG2-126 GEN
Solar/Wind Harmer
8.107
270222AC2-111 GEN
Solar/Wind Harmer
3.839
24755605MDL-5G
Solar/Wind Harmer
1.052
970781AG2-491 GEN
Solar/Wind Harmer
4.363
252510AF1-249 C
Solar/Wind Helper
0.75
253406AD2-031_GEN
Solar/Wind Helper
1.05
253415AE1-040 GEN
Solar/Wind Helper
0.622
253338AC1-165 GEN
Solar/Wind Helper
0.648
253333AC1-068 GEN
Solar/Wind Helper
0.671
241974AD2-163_GEN2
Solar/Wind Helper
1.045
241955AC1-078 GEN
Solar/Wind Helper
0.988
944201AF1-088_MTX
Adder
57.114
957141AF2-008_MTX
Adder
28.557
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.67
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.072
MECLTFEXP_MEC->PJM
CLTF
5.881
SIGELTFEXP_SIGE->PJM
CLTF
0.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.536
LAGNLTFEXP_LAGN->PJM
CLTF
4.021
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.318
TVALTFEXP_TVA->PJM
CLTF
1.602
NYPJM->LTFIMP_NY
CLTF
0.528
LGEELTFEXP_LGEE->PJM
CLTF
1.157
WECLTFEXP_WEC->PJM
CLTF
1.41
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.011
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:100.05 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2318.24
MW Contribution:4.24
Bus #Bus NameTypeMW Contribution
964351AG1-297 GEN
50/50
15.023
961161AF2-407 GEN
50/50
36.754
24728705AND G3
50/50
7.214
24728505AND G1
50/50
3.45
270437AC2-090 C
Solar/Wind Harmer
0.005
270356AE2-297 GEN
Solar/Wind Harmer
0.014
958821AF2-173 GEN
Solar/Wind Harmer
12.115
270004AE1-209 GEN
Solar/Wind Harmer
1.875
946031AF1-268 GEN
Solar/Wind Harmer
6.644
970289AG2-191 GEN
Solar/Wind Harmer
0.621
970291AG2-192 GEN
Solar/Wind Harmer
0.565
944531AF1-118 GEN
Solar/Wind Harmer
24.99
247642Z2-115 C
Solar/Wind Harmer
0.002
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.511
971617AH1-308 GEN
Solar/Wind Harmer
3.633
970193AG2-126 GEN
Solar/Wind Harmer
5.656
270222AC2-111 GEN
Solar/Wind Harmer
1.665
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.044
252510AF1-249 C
Solar/Wind Helper
0.75
253406AD2-031_GEN
Solar/Wind Helper
1.05
253415AE1-040 GEN
Solar/Wind Helper
0.622
253338AC1-165 GEN
Solar/Wind Helper
0.648
253333AC1-068 GEN
Solar/Wind Helper
0.671
241974AD2-163_GEN2
Solar/Wind Helper
1.045
241955AC1-078 GEN
Solar/Wind Helper
0.988
24726905LAWG2S
50/50
5.818
24726605LAWG1S
50/50
5.812
24726705LAWG2A
50/50
3.911
24726505LAWG1B
50/50
3.884
24726805LAWG2B
50/50
3.872
24729505KEY G4
50/50
5.792
270240V3-007_GEN2
Solar/Wind Harmer
0.003
945581AF1-223 GEN
Solar/Wind Harmer
0.001
970115AG2-085 GEN
Solar/Wind Harmer
2.862
965101AG1-375 GEN
Solar/Wind Harmer
6.952
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
1.047
270594AE1-207 GEN
Solar/Wind Harmer
6.802
970289AG2-191 GEN
Solar/Wind Harmer
1.073
270024AE2-089 GEN
Solar/Wind Harmer
0.005
270543AE2-219 C
Solar/Wind Harmer
0.003
971029AG2-637 GEN
Solar/Wind Harmer
5.79
971673AH1-337 GEN
Solar/Wind Harmer
2.403
270071AF1-092 GEN
Solar/Wind Harmer
6.489
963791AG1-232 GEN
Solar/Wind Harmer
4.447
963841AG1-237 GEN
Solar/Wind Harmer
1.425
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0
270181AB1-006 GEN2
Solar/Wind Harmer
0
252524AE2-267 GEN
Solar/Wind Helper
1.139
241972AD1-140 GEN
Solar/Wind Helper
3.771
270367AC2-061_GEN
Solar/Wind Helper
2.308
270340AC2-060 GEN
Solar/Wind Helper
1.341
945631AF1-228 GEN
Solar/Wind Helper
1.149
253383AE2-342_GEN
Solar/Wind Helper
0.467
241973AD2-163_GEN1
Solar/Wind Helper
1.045
339243AC2-075 GEN1
Solar/Wind Helper
0.223
25194708EBND2
50/50
13.331
24729405KEY G3
50/50
0.316
24729305KEY G2
50/50
0.311
24729205KEY G1
50/50
0.309
247621Y3-024
50/50
0.168
24379505HDWTR1G C
Solar/Wind Harmer
0.004
270209AC1-174_GEN
Solar/Wind Harmer
0.001
926881AC1-175 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
8.038
960441AF2-335 GEN
Solar/Wind Harmer
7.155
944541AF1-119 GEN
Solar/Wind Harmer
0.448
960971AF2-388 GEN
Solar/Wind Harmer
3.922
270599AE1-208 GEN
Solar/Wind Harmer
5.878
270031AE2-169
Solar/Wind Harmer
3.527
270383AD1-128 GEN
Solar/Wind Harmer
0.004
971613AH1-306 GEN
Solar/Wind Harmer
2.915
964611AG1-324 GEN
Solar/Wind Harmer
0.407
270201AC2-176 GEN
Solar/Wind Harmer
0.001
942221AE2-234 GEN
Solar/Wind Harmer
0.023
970883AG2-550 GEN
Solar/Wind Harmer
4.236
970885AG2-551 GEN
Solar/Wind Harmer
1.412
945391AF1-204 GEN
Solar/Wind Harmer
4.007
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.513
24728805RICHG1
Adder
1.851
24728905RICHG2
Adder
1.851
970241AG2-163 GEN
Solar/Wind Harmer
1.982
966841AG1-555 GEN
Solar/Wind Harmer
0.359
25183208HLCRTG
Solar/Wind Helper
3.041
252509AD1-136 GEN
Solar/Wind Helper
0.253
253394AE2-221_GEN
Solar/Wind Helper
1.882
253398AE2-221_GEN2
Solar/Wind Helper
1.882
962581AG1-107 GEN
Solar/Wind Helper
1.183
961491AF2-440 GEN
Solar/Wind Helper
0.049
253378AE2-206_GEN
Solar/Wind Helper
1.009
276820AF1-078_GEN
Solar/Wind Helper
0.472
270186AC1-089 GEN
Solar/Wind Helper
0.977
270518AE2-148 GEN
Solar/Wind Helper
9.191
339221AD2-048_GEN
Solar/Wind Helper
0.797
24726405LAWG1A
50/50
3.764
961171AF2-408 GEN
50/50
9.769
960791AF2-370 GEN
50/50
2.385
24728605AND G2
50/50
3.45
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0.001
970613AG2-401 GEN
Solar/Wind Harmer
8.227
970773AG2-487 GEN
Solar/Wind Harmer
1.904
270005AE1-210 C O1
Solar/Wind Harmer
1.875
965031AG1-367 GEN
Solar/Wind Harmer
8.653
945371AF1-202 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
2.575
958861AF2-177 GEN
Solar/Wind Harmer
3.013
965651AG1-433 GEN
Solar/Wind Harmer
1.961
276903AD2-071 C
Solar/Wind Harmer
7.023
270032AE2-172
Solar/Wind Harmer
4.049
970291AG2-192 GEN
Solar/Wind Harmer
0.734
247536S-71 GEN
Solar/Wind Harmer
0.183
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
963741AG1-226 GEN
Solar/Wind Harmer
8.041
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
970091AG2-072 GEN
Adder
34
24791305MDL-5G
Solar/Wind Harmer
0
252507AC2-088 GEN
Solar/Wind Helper
1.774
253343AC1-166 GEN
Solar/Wind Helper
0.648
253325AC1-069 GEN
Solar/Wind Helper
0.671
339216AC1-074 GEN
Solar/Wind Helper
0.968
943111AE2-339 GEN
Solar/Wind Helper
0.37
944201AF1-088_MTX
Adder
57.114
957141AF2-008_MTX
Adder
28.557
CBM West 1LTFEXP_CBM-W1->PJM
CBM
42.67
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.072
MECLTFEXP_MEC->PJM
CLTF
5.881
SIGELTFEXP_SIGE->PJM
CLTF
0.223
CBM West 2LTFEXP_CBM-W2->PJM
CBM
43.536
LAGNLTFEXP_LAGN->PJM
CLTF
4.021
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.318
TVALTFEXP_TVA->PJM
CLTF
1.602
NYPJM->LTFIMP_NY
CLTF
0.528
LGEELTFEXP_LGEE->PJM
CLTF
1.157
WECLTFEXP_WEC->PJM
CLTF
1.41
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.011
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144

Details for 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P4_1403_MIAMI FORT_SRT-A


Base Case Flowgate

Area:OVEC
Facility Description:
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1403_MIAMI FORT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.32 %
Rating:942.0 MVA
Rating Type:B
MVA to Mitigate:982.66
MW Contribution:5.45
Bus #Bus NameTypeMW Contribution
964351AG1-297 GEN
50/50
9.217
270437AC2-090 C
Solar/Wind Harmer
5.588
270356AE2-297 GEN
Solar/Wind Harmer
4.499
958821AF2-173 GEN
Solar/Wind Harmer
11.074
270004AE1-209 GEN
Solar/Wind Harmer
4.323
946031AF1-268 GEN
Solar/Wind Harmer
5.669
270222AC2-111 GEN
Solar/Wind Harmer
4.901
24728705AND G3
Adder
4.627
24726405LAWG1A
50/50
2.236
942081AE2-220 GEN
Solar/Wind Harmer
6.399
270239V3-007_GEN1
Solar/Wind Harmer
1.722
270005AE1-210 C O1
Solar/Wind Harmer
4.323
965031AG1-367 GEN
Solar/Wind Harmer
7.91
970825AG2-519 GEN
Solar/Wind Harmer
1.632
945371AF1-202 GEN
Solar/Wind Harmer
4.783
958861AF2-177 GEN
Solar/Wind Harmer
6.999
965651AG1-433 GEN
Solar/Wind Harmer
3.37
276903AD2-071 C
Solar/Wind Harmer
5.844
24728605AND G2
Adder
2.213
270032AE2-172
Solar/Wind Harmer
2.634
247536S-71 GEN
Solar/Wind Harmer
2.213
970291AG2-192 GEN
Solar/Wind Harmer
0.678
252507AC2-088 GEN
Solar/Wind Helper
0.705
25194708EBND2
50/50
5.443
24379505HDWTR1G C
Solar/Wind Harmer
7.914
270209AC1-174_GEN
Solar/Wind Harmer
5.586
926881AC1-175 GEN
Solar/Wind Harmer
5.586
970825AG2-519 GEN
Solar/Wind Harmer
7.316
960441AF2-335 GEN
Solar/Wind Harmer
6.831
270383AD1-128 GEN
Solar/Wind Harmer
4.151
944541AF1-119 GEN
Solar/Wind Harmer
2.583
960971AF2-388 GEN
Solar/Wind Harmer
6.741
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
4.993
964611AG1-324 GEN
Solar/Wind Harmer
0.686
964611AG1-324 GEN
Solar/Wind Harmer
0.304
270201AC2-176 GEN
Solar/Wind Harmer
2.849
24728805RICHG1
Adder
2.093
24728905RICHG2
Adder
2.093
970883AG2-550 GEN
Solar/Wind Harmer
5.453
970885AG2-551 GEN
Solar/Wind Harmer
1.268
247621Y3-024
Adder
0.13
942221AE2-234 GEN
Solar/Wind Harmer
0.34
252509AD1-136 GEN
Solar/Wind Helper
0.101
24728505AND G1
Adder
2.213
962031AG1-047 GEN
Solar/Wind Harmer
1.675
957741AF2-068 GEN
Solar/Wind Harmer
8.314
970289AG2-191 GEN
Solar/Wind Harmer
0.4
970291AG2-192 GEN
Solar/Wind Harmer
0.364
944531AF1-118 GEN
Solar/Wind Harmer
18.148
971617AH1-308 GEN
Solar/Wind Harmer
2.794
247642Z2-115 C
Solar/Wind Harmer
0.031
24726905LAWG2S
50/50
3.457
24726605LAWG1S
50/50
3.453
24726705LAWG2A
50/50
2.324
24726505LAWG1B
50/50
2.307
24726805LAWG2B
50/50
2.3
270240V3-007_GEN2
Solar/Wind Harmer
6.192
945581AF1-223 GEN
Solar/Wind Harmer
3.109
970115AG2-085 GEN
Solar/Wind Harmer
2.732
965101AG1-375 GEN
Solar/Wind Harmer
6.403
958711AF2-162 GEN
Solar/Wind Harmer
0.624
24725505WLD G2 C
Solar/Wind Harmer
2.447
24699105WLD G1 C
Solar/Wind Harmer
2.418
944031AF1-071 GEN
Solar/Wind Harmer
0.604
270594AE1-207 GEN
Solar/Wind Harmer
8.324
961761AG1-017 GEN
Solar/Wind Harmer
0.237
270543AE2-219 C
Solar/Wind Harmer
2.792
24729505KEY G4
Adder
3.533
971029AG2-637 GEN
Solar/Wind Harmer
8.113
971673AH1-337 GEN
Solar/Wind Harmer
2.472
965461AG1-414 GEN
Solar/Wind Harmer
1.182
970289AG2-191 GEN
Solar/Wind Harmer
0.99
270024AE2-089 GEN
Solar/Wind Harmer
2.256
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.139
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.657
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.319
MECLTFEXP_MEC->PJM
CLTF
3.425
SIGELTFEXP_SIGE->PJM
CLTF
0.138
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.349
LAGNLTFEXP_LAGN->PJM
CLTF
2.144
TVALTFEXP_TVA->PJM
CLTF
0.84
NYPJM->LTFIMP_NY
CLTF
0.488
LGEELTFEXP_LGEE->PJM
CLTF
0.744
WECLTFEXP_WEC->PJM
CLTF
0.832
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.27

Details for 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o DEOK_P4_1401_MIAMI FORT_SRT-A


Base Case Flowgate

Area:OVEC
Facility Description:
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P4_1401_MIAMI FORT_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.8 %
Rating:942.0 MVA
Rating Type:B
MVA to Mitigate:977.75
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
24726905LAWG2S
50/50
3.457
24726605LAWG1S
50/50
3.454
24726705LAWG2A
50/50
2.324
24726505LAWG1B
50/50
2.308
24726805LAWG2B
50/50
2.301
270240V3-007_GEN2
Solar/Wind Harmer
6.194
945581AF1-223 GEN
Solar/Wind Harmer
3.11
970115AG2-085 GEN
Solar/Wind Harmer
2.733
965101AG1-375 GEN
Solar/Wind Harmer
6.406
958711AF2-162 GEN
Solar/Wind Harmer
0.624
24725505WLD G2 C
Solar/Wind Harmer
2.448
24699105WLD G1 C
Solar/Wind Harmer
2.419
944031AF1-071 GEN
Solar/Wind Harmer
0.604
270594AE1-207 GEN
Solar/Wind Harmer
8.327
961761AG1-017 GEN
Solar/Wind Harmer
0.237
270543AE2-219 C
Solar/Wind Harmer
2.794
24729505KEY G4
Adder
3.534
971029AG2-637 GEN
Solar/Wind Harmer
8.118
971673AH1-337 GEN
Solar/Wind Harmer
2.474
965461AG1-414 GEN
Solar/Wind Harmer
1.182
970289AG2-191 GEN
Solar/Wind Harmer
0.991
270024AE2-089 GEN
Solar/Wind Harmer
2.257
964351AG1-297 GEN
50/50
9.218
270437AC2-090 C
Solar/Wind Harmer
5.589
270356AE2-297 GEN
Solar/Wind Harmer
4.5
958821AF2-173 GEN
Solar/Wind Harmer
11.077
270004AE1-209 GEN
Solar/Wind Harmer
4.324
946031AF1-268 GEN
Solar/Wind Harmer
5.671
270222AC2-111 GEN
Solar/Wind Harmer
4.904
24728705AND G3
Adder
4.628
24728505AND G1
Adder
2.213
962031AG1-047 GEN
Solar/Wind Harmer
1.676
957741AF2-068 GEN
Solar/Wind Harmer
8.318
970289AG2-191 GEN
Solar/Wind Harmer
0.4
970291AG2-192 GEN
Solar/Wind Harmer
0.364
944531AF1-118 GEN
Solar/Wind Harmer
18.157
971617AH1-308 GEN
Solar/Wind Harmer
2.796
247642Z2-115 C
Solar/Wind Harmer
0.031
25194708EBND2
50/50
5.445
24379505HDWTR1G C
Solar/Wind Harmer
7.916
270209AC1-174_GEN
Solar/Wind Harmer
5.587
926881AC1-175 GEN
Solar/Wind Harmer
5.587
970825AG2-519 GEN
Solar/Wind Harmer
7.319
960441AF2-335 GEN
Solar/Wind Harmer
6.833
270383AD1-128 GEN
Solar/Wind Harmer
4.153
944541AF1-119 GEN
Solar/Wind Harmer
2.584
960971AF2-388 GEN
Solar/Wind Harmer
6.743
270599AE1-208 GEN
Solar/Wind Harmer
4.995
270031AE2-169
Solar/Wind Harmer
4.995
964611AG1-324 GEN
Solar/Wind Harmer
0.686
964611AG1-324 GEN
Solar/Wind Harmer
0.304
270201AC2-176 GEN
Solar/Wind Harmer
2.851
24728805RICHG1
Adder
2.094
24728905RICHG2
Adder
2.094
970883AG2-550 GEN
Solar/Wind Harmer
5.456
970885AG2-551 GEN
Solar/Wind Harmer
1.269
247621Y3-024
Adder
0.13
942221AE2-234 GEN
Solar/Wind Harmer
0.34
252509AD1-136 GEN
Solar/Wind Helper
0.101
24726405LAWG1A
50/50
2.236
942081AE2-220 GEN
Solar/Wind Harmer
6.4
270239V3-007_GEN1
Solar/Wind Harmer
1.723
270005AE1-210 C O1
Solar/Wind Harmer
4.324
965031AG1-367 GEN
Solar/Wind Harmer
7.912
970825AG2-519 GEN
Solar/Wind Harmer
1.633
945371AF1-202 GEN
Solar/Wind Harmer
4.784
958861AF2-177 GEN
Solar/Wind Harmer
7.002
965651AG1-433 GEN
Solar/Wind Harmer
3.372
276903AD2-071 C
Solar/Wind Harmer
5.846
24728605AND G2
Adder
2.213
270032AE2-172
Solar/Wind Harmer
2.635
247536S-71 GEN
Solar/Wind Harmer
2.214
970291AG2-192 GEN
Solar/Wind Harmer
0.678
252507AC2-088 GEN
Solar/Wind Helper
0.704
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.138
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.691
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.323
MECLTFEXP_MEC->PJM
CLTF
3.428
SIGELTFEXP_SIGE->PJM
CLTF
0.138
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.368
LAGNLTFEXP_LAGN->PJM
CLTF
2.147
TVALTFEXP_TVA->PJM
CLTF
0.842
NYPJM->LTFIMP_NY
CLTF
0.486
LGEELTFEXP_LGEE->PJM
CLTF
0.743
WECLTFEXP_WEC->PJM
CLTF
0.833
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.268

Details for 06DEARB1-06PIERCE 345.0 kV Ckt 1 line l/o AEP_P4_#2812_05TANNER 345_T2_SRT-A


Base Case Flowgate

Area:OVEC
Facility Description:
06DEARB1-06PIERCE 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#2812_05TANNER 345_T2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.75 %
Rating:942.0 MVA
Rating Type:B
MVA to Mitigate:977.33
MW Contribution:5.46
Bus #Bus NameTypeMW Contribution
24726405LAWG1A
50/50
2.236
942081AE2-220 GEN
Solar/Wind Harmer
6.401
270239V3-007_GEN1
Solar/Wind Harmer
1.723
270005AE1-210 C O1
Solar/Wind Harmer
4.325
965031AG1-367 GEN
Solar/Wind Harmer
7.913
970825AG2-519 GEN
Solar/Wind Harmer
1.633
945371AF1-202 GEN
Solar/Wind Harmer
4.785
958861AF2-177 GEN
Solar/Wind Harmer
7.003
965651AG1-433 GEN
Solar/Wind Harmer
3.372
276903AD2-071 C
Solar/Wind Harmer
5.847
24728605AND G2
Adder
2.214
270032AE2-172
Solar/Wind Harmer
2.636
247536S-71 GEN
Solar/Wind Harmer
2.214
970291AG2-192 GEN
Solar/Wind Harmer
0.678
252507AC2-088 GEN
Solar/Wind Helper
0.704
24726905LAWG2S
50/50
3.457
24726605LAWG1S
50/50
3.454
24726705LAWG2A
50/50
2.324
24726505LAWG1B
50/50
2.308
24726805LAWG2B
50/50
2.301
270240V3-007_GEN2
Solar/Wind Harmer
6.194
945581AF1-223 GEN
Solar/Wind Harmer
3.11
970115AG2-085 GEN
Solar/Wind Harmer
2.734
965101AG1-375 GEN
Solar/Wind Harmer
6.407
958711AF2-162 GEN
Solar/Wind Harmer
0.624
24725505WLD G2 C
Solar/Wind Harmer
2.448
24699105WLD G1 C
Solar/Wind Harmer
2.42
944031AF1-071 GEN
Solar/Wind Harmer
0.604
270594AE1-207 GEN
Solar/Wind Harmer
8.329
961761AG1-017 GEN
Solar/Wind Harmer
0.237
270543AE2-219 C
Solar/Wind Harmer
2.794
24729505KEY G4
Adder
3.535
971029AG2-637 GEN
Solar/Wind Harmer
8.118
971673AH1-337 GEN
Solar/Wind Harmer
2.474
965461AG1-414 GEN
Solar/Wind Harmer
1.183
970289AG2-191 GEN
Solar/Wind Harmer
0.991
270024AE2-089 GEN
Solar/Wind Harmer
2.257
25194708EBND2
50/50
5.444
24379505HDWTR1G C
Solar/Wind Harmer
7.917
270209AC1-174_GEN
Solar/Wind Harmer
5.587
926881AC1-175 GEN
Solar/Wind Harmer
5.587
970825AG2-519 GEN
Solar/Wind Harmer
7.319
960441AF2-335 GEN
Solar/Wind Harmer
6.834
270383AD1-128 GEN
Solar/Wind Harmer
4.153
944541AF1-119 GEN
Solar/Wind Harmer
2.584
960971AF2-388 GEN
Solar/Wind Harmer
6.744
270599AE1-208 GEN
Solar/Wind Harmer
4.995
270031AE2-169
Solar/Wind Harmer
4.995
964611AG1-324 GEN
Solar/Wind Harmer
0.686
964611AG1-324 GEN
Solar/Wind Harmer
0.305
270201AC2-176 GEN
Solar/Wind Harmer
2.851
24728805RICHG1
Adder
2.095
24728905RICHG2
Adder
2.095
970883AG2-550 GEN
Solar/Wind Harmer
5.456
970885AG2-551 GEN
Solar/Wind Harmer
1.269
247621Y3-024
Adder
0.13
942221AE2-234 GEN
Solar/Wind Harmer
0.34
252509AD1-136 GEN
Solar/Wind Helper
0.101
964351AG1-297 GEN
50/50
9.22
270437AC2-090 C
Solar/Wind Harmer
5.59
270356AE2-297 GEN
Solar/Wind Harmer
4.501
958821AF2-173 GEN
Solar/Wind Harmer
11.078
270004AE1-209 GEN
Solar/Wind Harmer
4.325
946031AF1-268 GEN
Solar/Wind Harmer
5.671
270222AC2-111 GEN
Solar/Wind Harmer
4.904
24728705AND G3
Adder
4.63
24728505AND G1
Adder
2.214
962031AG1-047 GEN
Solar/Wind Harmer
1.676
957741AF2-068 GEN
Solar/Wind Harmer
8.319
970289AG2-191 GEN
Solar/Wind Harmer
0.4
970291AG2-192 GEN
Solar/Wind Harmer
0.364
944531AF1-118 GEN
Solar/Wind Harmer
18.159
971617AH1-308 GEN
Solar/Wind Harmer
2.796
247642Z2-115 C
Solar/Wind Harmer
0.031
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.138
CBM West 1LTFEXP_CBM-W1->PJM
CBM
25.703
CBM South 1LTFEXP_CBM-S1->PJM
CBM
3.331
MECLTFEXP_MEC->PJM
CLTF
3.431
SIGELTFEXP_SIGE->PJM
CLTF
0.138
CBM West 2LTFEXP_CBM-W2->PJM
CBM
25.391
LAGNLTFEXP_LAGN->PJM
CLTF
2.15
TVALTFEXP_TVA->PJM
CLTF
0.843
NYPJM->LTFIMP_NY
CLTF
0.486
LGEELTFEXP_LGEE->PJM
CLTF
0.746
WECLTFEXP_WEC->PJM
CLTF
0.833
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.268

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:156.15 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2404.66
MW Contribution:7.18
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.429
24803306KYGER 4LP
50/50
2.379
971191AH1-055 GEN
Solar/Wind Harmer
84.382
25194608D.CRK4
Adder
1.718
25196608WSDLE5
Adder
8.955
252510AF1-249 C
Solar/Wind Harmer
0.436
253316AC1-085 GEN3
Solar/Wind Harmer
8.546
253433AC1-085 GEN1
Solar/Wind Harmer
5.425
946181AF1-283 GEN
Solar/Wind Harmer
13.263
25196008MFTGT1
Adder
1.348
958171AF2-111 GEN
Solar/Wind Harmer
24.756
972167AH1-666 GEN
Solar/Wind Harmer
7.453
253406AD2-031_GEN
Solar/Wind Harmer
1.157
972173AH1-669 GEN
Solar/Wind Harmer
4.43
270222AC2-111 GEN
Solar/Wind Harmer
6.98
270273AD2-016 GEN
Solar/Wind Harmer
2.257
253415AE1-040 GEN
Solar/Wind Harmer
0.952
253303V4-073 C
Solar/Wind Harmer
0.096
253370AE2-315 SEC1
Adder
1.653
253371AE2-315 SEC2
Adder
1.564
270356AE2-297 GEN
Solar/Wind Harmer
3.556
3429391JKCT 9G
Adder
6.489
270437AC2-090 C
Solar/Wind Harmer
4.209
970093AG2-073 GEN
Solar/Wind Harmer
7.103
958821AF2-173 GEN
Solar/Wind Harmer
9.9
270004AE1-209 GEN
Solar/Wind Harmer
3.865
24728705AND G3
Adder
5.629
24728505AND G1
Adder
2.691
946031AF1-268 GEN
Solar/Wind Harmer
5.792
966571AG1-526 GEN
Solar/Wind Harmer
15.251
962031AG1-047 GEN
Solar/Wind Harmer
2.032
957741AF2-068 GEN
Solar/Wind Harmer
10.082
970289AG2-191 GEN
Solar/Wind Harmer
0.497
970291AG2-192 GEN
Solar/Wind Harmer
0.451
247642Z2-115 C
Solar/Wind Harmer
0.041
971617AH1-308 GEN
Solar/Wind Harmer
3.659
944531AF1-118 GEN
Solar/Wind Harmer
21.491
253338AC1-165 GEN
Solar/Wind Harmer
0.666
253333AC1-068 GEN
Solar/Wind Harmer
0.642
970193AG2-126 GEN
Solar/Wind Harmer
8.968
970243AG2-164 GEN
Solar/Wind Harmer
15.315
970519AG2-331 GEN
Solar/Wind Harmer
10.289
970699AG2-449 GEN
Solar/Wind Harmer
6.806
24755605MDL-5G
Solar/Wind Harmer
1.348
970781AG2-491 GEN
Solar/Wind Harmer
5.589
972273AH1-721 GEN
Adder
43.969
274772LINCOLN ;3U
Adder
4.435
972228AH1-698 GEN2
Adder
1.944
274729ELWOOD EC;1P
Adder
8.613
274730ELWOOD EC;6P
Adder
8.613
274734ELWOOD EC;8P
Adder
8.613
274736ELWOOD EC;9P
Adder
8.613
274800UNIV PARK;3U
Adder
3.055
972038AH1-567 GEN2
Adder
0.191
274802UNIV PARK;5U
Adder
3.054
274826FISK ;BP
Adder
5.732
274724RIVER EC ;11
Adder
9.271
274752CRETE EC ;2U
Adder
4.312
274753CRETE EC ;3U
Adder
4.312
235780M24_1
Solar/Wind Helper
1.012
24802606KYGER 1HP
50/50
4.15
24802706KYGER 1LP
50/50
2.436
24803506KYGER 5LP
50/50
2.379
25016408BKJDB1
50/50
0.28
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
49.695
252524AE2-267 GEN
Solar/Wind Harmer
1.648
25196408WSDLE3
Adder
9.218
25196308WSDLE2
Adder
9.138
25196208WSDLE1
Adder
9.115
25196708WSDLE6
Adder
9.092
25196508WSDLE4
Adder
8.863
25196108MFTGT2
Adder
1.534
25196108MFTGT2
Adder
1.425
972163AH1-664 GEN
Solar/Wind Harmer
9.175
972165AH1-665 GEN
Solar/Wind Harmer
7.34
270367AC2-061_GEN
Solar/Wind Harmer
2.878
339243AC2-075 GEN1
Solar/Wind Harmer
0.403
270340AC2-060 GEN
Solar/Wind Harmer
2.625
944031AF1-071 GEN
Solar/Wind Harmer
0.86
270269AC2-059
Solar/Wind Harmer
7.894
253372AE2-315 SEC3
Adder
1.564
253372AE2-315 SEC3
Adder
1.564
25306009OHH W.
Adder
2.347
253349AC2-067 GEN
Solar/Wind Harmer
3.985
253400AC2-068 GEN
Solar/Wind Harmer
1.602
3429211JKCT 2G
Adder
8.846
270240V3-007_GEN2
Solar/Wind Harmer
4.664
971673AH1-337 GEN
Solar/Wind Harmer
3.435
971029AG2-637 GEN
Solar/Wind Harmer
11.093
970689AG2-444 GEN
Solar/Wind Harmer
12.048
270543AE2-219 C
Solar/Wind Harmer
3.676
970115AG2-085 GEN
Solar/Wind Harmer
2.777
24725505WLD G2 C
Solar/Wind Harmer
2.7
24699105WLD G1 C
Solar/Wind Harmer
2.668
961761AG1-017 GEN
Solar/Wind Harmer
0.288
945581AF1-223 GEN
Solar/Wind Harmer
3.044
241972AD1-140 GEN
Solar/Wind Harmer
2.991
970455AG2-298 GEN
Solar/Wind Harmer
3.991
270432AC2-029 GEN
Solar/Wind Harmer
4.641
339211AE2-254 GEN
Solar/Wind Harmer
1
270594AE1-207 GEN
Solar/Wind Harmer
9.705
965101AG1-375 GEN
Solar/Wind Harmer
6.557
958711AF2-162 GEN
Solar/Wind Harmer
0.655
965461AG1-414 GEN
Solar/Wind Harmer
1.467
970289AG2-191 GEN
Solar/Wind Harmer
1.229
270024AE2-089 GEN
Solar/Wind Harmer
2.954
24729505KEY G4
Adder
4.041
963841AG1-237 GEN
Solar/Wind Harmer
6.258
965401AG1-405 GEN
Solar/Wind Harmer
3.232
965411AG1-406 GEN
Solar/Wind Harmer
1.451
24386205FR-12G C
Solar/Wind Harmer
2.428
24386405FR-21G C
Solar/Wind Harmer
2.437
24386605FR-22G C
Solar/Wind Harmer
2.437
24387005FR-3G C
Solar/Wind Harmer
2.242
963791AG1-232 GEN
Solar/Wind Harmer
7.567
24690905MDL-1G C
Solar/Wind Harmer
4.488
270180AB1-006 GEN1
Solar/Wind Harmer
4.02
946581AF1-322 GEN
Solar/Wind Harmer
5.719
24691005MDL-2G C
Solar/Wind Harmer
2.067
24697605MDL-3G C
Solar/Wind Harmer
2.061
24697905MDL-4G C
Solar/Wind Harmer
1.283
270181AB1-006 GEN2
Solar/Wind Harmer
0.4
274775LINCOLN ;6U
Adder
4.435
274776LINCOLN ;7U
Adder
4.435
274777LINCOLN ;8U
Adder
4.435
972227AH1-698 GEN1
Adder
1.369
274731ELWOOD EC;2P
Adder
8.613
274733ELWOOD EC;3P
Adder
8.613
274735ELWOOD EC;4P
Adder
8.613
274728ELWOOD EC;5P
Adder
8.613
972037AH1-567 GEN1
Adder
0.096
274827FISK ;RP
Adder
4.063
274814UNIV PK N;0U
Adder
2.645
274807UNIV PK N;3U
Adder
2.64
274805UNIV PK N;1U
Adder
2.628
274811UNIV PK N;7U
Adder
2.622
274687WILL CNTY;4U
Adder
14.622
274687WILL CNTY;4U
Adder
14.622
274675JOLIET 29;7U
Adder
4.98
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.208
24803006KYGER 3HP
50/50
4.126
24802806KYGER 2HP
50/50
4.102
24802906KYGER 2LP
50/50
2.412
252509AD1-136 GEN
Solar/Wind Harmer
0.295
25183208HLCRTG
Solar/Wind Harmer
6.611
252519AF1-045_GEN
Solar/Wind Harmer
6.54
252516AE2-318_GEN
Solar/Wind Harmer
4.989
25194408D.CRK1
Adder
7.904
25194508D.CRK3
Adder
1.478
253317AC1-085 GEN4
Solar/Wind Harmer
8.546
253394AE2-221_GEN
Solar/Wind Harmer
4.374
253398AE2-221_GEN2
Solar/Wind Harmer
4.374
270186AC1-089 GEN
Solar/Wind Harmer
5.453
970235AG2-159 GEN
Solar/Wind Harmer
3.57
970235AG2-159 GEN
Solar/Wind Harmer
2.18
962581AG1-107 GEN
Solar/Wind Harmer
4.438
961491AF2-440 GEN
Solar/Wind Harmer
1.844
339221AD2-048_GEN
Solar/Wind Harmer
1.337
972043AH1-570 GEN
Solar/Wind Harmer
2.119
972045AH1-571 GEN
Solar/Wind Harmer
1.695
971125AH1-004 GEN
Solar/Wind Harmer
3.302
970107AG2-081 GEN
Solar/Wind Harmer
2.476
253370AE2-315 SEC1
Adder
1.653
24728805RICHG1
Adder
3.025
24728905RICHG2
Adder
3.025
25322209TAIT E
Adder
7.801
25322209TAIT E
Adder
7.626
25326109MON D
Adder
1.023
24379505HDWTR1G C
Solar/Wind Harmer
5.961
270209AC1-174_GEN
Solar/Wind Harmer
4.207
926881AC1-175 GEN
Solar/Wind Harmer
4.207
942891AE2-308 GEN
Solar/Wind Harmer
7.431
270383AD1-128 GEN
Solar/Wind Harmer
4.52
970883AG2-550 GEN
Solar/Wind Harmer
7.178
970885AG2-551 GEN
Solar/Wind Harmer
1.669
970825AG2-519 GEN
Solar/Wind Harmer
7.36
960161AF2-307 GEN
Solar/Wind Harmer
4.47
960441AF2-335 GEN
Solar/Wind Harmer
6.942
247621Y3-024
Adder
0.165
964611AG1-324 GEN
Solar/Wind Harmer
0.799
964611AG1-324 GEN
Solar/Wind Harmer
0.355
270201AC2-176 GEN
Solar/Wind Harmer
3.455
270599AE1-208 GEN
Solar/Wind Harmer
5.434
270031AE2-169
Solar/Wind Harmer
5.434
964571AG1-320 GEN
Solar/Wind Harmer
5.336
944541AF1-119 GEN
Solar/Wind Harmer
2.712
960971AF2-388 GEN
Solar/Wind Harmer
7.078
970653AG2-424 GEN
Solar/Wind Harmer
3.01
970653AG2-424 GEN
Solar/Wind Harmer
1.088
942221AE2-234 GEN
Solar/Wind Harmer
0.447
270444AC2-157 GEN1
Solar/Wind Harmer
3.342
945391AF1-204 GEN
Solar/Wind Harmer
8.332
970239AG2-162 GEN
Solar/Wind Harmer
6.523
970241AG2-163 GEN
Solar/Wind Harmer
14.458
25326509SID D
Adder
0.758
971081AG2-670 GEN
Solar/Wind Harmer
4.267
966841AG1-555 GEN
Solar/Wind Harmer
1.422
274770LINCOLN ;1U
Adder
4.435
274771LINCOLN ;2U
Adder
4.435
972259AH1-714 GEN
Adder
10.005
274803UNIV PARK;6U
Adder
3.054
274674JOLIET 9 ;6U
Adder
8.062
274808UNIV PK N;4U
Adder
2.611
237033AB1-150 GEN
Solar/Wind Helper
0.408
270518AE2-148 GEN
Solar/Wind Harmer
6.451
24803406KYGER 5HP
50/50
4.08
24803206KYGER 4HP
50/50
4.077
252507AC2-088 GEN
Solar/Wind Harmer
2.066
25196808ZIMRHP
Adder
80.623
25194608D.CRK4
Adder
1.718
253432AC1-085 GEN2
Solar/Wind Harmer
0.273
946171AF1-282 GEN
Solar/Wind Harmer
10.203
25196008MFTGT1
Adder
1.392
945681AF1-233 GEN
Solar/Wind Harmer
17.49
339216AC1-074 GEN
Solar/Wind Harmer
1.487
270263AC1-001 GEN
Solar/Wind Harmer
0.884
253370AE2-315 SEC1
Adder
1.653
253371AE2-315 SEC2
Adder
1.564
943111AE2-339 GEN
Solar/Wind Harmer
0.716
25326309TAIT D
Adder
0.876
960071AF2-298 GEN
Solar/Wind Harmer
3.959
3429421JKCT 10G
Adder
6.489
3429241JKCT 3G
Adder
8.962
942081AE2-220 GEN
Solar/Wind Harmer
4.82
270239V3-007_GEN1
Solar/Wind Harmer
1.297
270005AE1-210 C O1
Solar/Wind Harmer
3.865
965031AG1-367 GEN
Solar/Wind Harmer
7.071
24728605AND G2
Adder
2.691
247536S-71 GEN
Solar/Wind Harmer
2.823
970825AG2-519 GEN
Solar/Wind Harmer
1.642
971565AH1-281 GEN
Solar/Wind Harmer
1.372
945371AF1-202 GEN
Solar/Wind Harmer
4.682
276903AD2-071 C
Solar/Wind Harmer
6.687
270032AE2-172
Solar/Wind Harmer
3.071
958861AF2-177 GEN
Solar/Wind Harmer
7.167
971821AH1-427 GEN
Solar/Wind Harmer
6.495
965651AG1-433 GEN
Solar/Wind Harmer
3.539
970291AG2-192 GEN
Solar/Wind Harmer
0.841
253343AC1-166 GEN
Solar/Wind Harmer
0.666
253325AC1-069 GEN
Solar/Wind Harmer
0.642
970091AG2-072 GEN
Adder
46.366
270445AC2-157 GEN2
Solar/Wind Harmer
3.342
970333AG2-219 GEN
Solar/Wind Harmer
18.718
963741AG1-226 GEN
Solar/Wind Harmer
26.024
339241AF1-083 GEN
Solar/Wind Harmer
0.96
24385905FR-11G C
Solar/Wind Harmer
4.71
24387305FR-4G C
Solar/Wind Harmer
2.879
24791305MDL-5G
Solar/Wind Harmer
1.348
274773LINCOLN ;4U
Adder
4.435
274774LINCOLN ;5U
Adder
4.435
274732ELWOOD EC;7P
Adder
8.613
274801UNIV PARK;4U
Adder
3.055
274723RIVER EC ;12
Adder
9.381
274674JOLIET 9 ;6U
Adder
8.062
274812UNIV PK N;8U
Adder
2.622
274751CRETE EC ;1U
Adder
4.312
274754CRETE EC ;4U
Adder
4.312
960001AF2-291 GEN
Solar/Wind Helper
1.73
270331AC1-082 GEN3
Solar/Wind Helper
0.207
944201AF1-088_MTX
Adder
69.584
957141AF2-008_MTX
Adder
34.792
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
75.073
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.86
MECLTFEXP_MEC->PJM
CLTF
8.255
SIGELTFEXP_SIGE->PJM
CLTF
0.338
CBM West 2LTFEXP_CBM-W2->PJM
CBM
59.703
LAGNLTFEXP_LAGN->PJM
CLTF
6.68
TVALTFEXP_TVA->PJM
CLTF
3.156
NYPJM->LTFIMP_NY
CLTF
1.706
LGEELTFEXP_LGEE->PJM
CLTF
5.222
WECLTFEXP_WEC->PJM
CLTF
1.971
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.318
AG2-052LTFEXP_AG2-052->PJM
LTF
0.126
AH1-155LTFEXP_AH1-155->PJM
LTF
0.19

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:154.73 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2382.87
MW Contribution:6.94
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
25016408BKJDB1
50/50
0.276
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
49.57
252524AE2-267 GEN
Solar/Wind Harmer
1.62
25196408WSDLE3
Adder
9.062
25196308WSDLE2
Adder
8.983
25196208WSDLE1
Adder
8.961
25196708WSDLE6
Adder
8.938
25196508WSDLE4
Adder
8.713
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.402
972163AH1-664 GEN
Solar/Wind Harmer
9.052
972165AH1-665 GEN
Solar/Wind Harmer
7.242
270367AC2-061_GEN
Solar/Wind Harmer
2.835
339243AC2-075 GEN1
Solar/Wind Harmer
0.397
270340AC2-060 GEN
Solar/Wind Harmer
2.578
944031AF1-071 GEN
Solar/Wind Harmer
0.84
270269AC2-059
Solar/Wind Harmer
7.774
253372AE2-315 SEC3
Adder
1.517
253372AE2-315 SEC3
Adder
1.517
25306009OHH W.
Adder
2.274
253349AC2-067 GEN
Solar/Wind Harmer
3.854
253400AC2-068 GEN
Solar/Wind Harmer
1.55
3429211JKCT 2G
Adder
8.726
270240V3-007_GEN2
Solar/Wind Harmer
4.539
970689AG2-444 GEN
Solar/Wind Harmer
11.825
971673AH1-337 GEN
Solar/Wind Harmer
3.329
971029AG2-637 GEN
Solar/Wind Harmer
10.743
270543AE2-219 C
Solar/Wind Harmer
3.554
970115AG2-085 GEN
Solar/Wind Harmer
2.693
24725505WLD G2 C
Solar/Wind Harmer
2.621
24699105WLD G1 C
Solar/Wind Harmer
2.59
970455AG2-298 GEN
Solar/Wind Harmer
3.93
339211AE2-254 GEN
Solar/Wind Harmer
0.986
945581AF1-223 GEN
Solar/Wind Harmer
2.945
270432AC2-029 GEN
Solar/Wind Harmer
4.535
961761AG1-017 GEN
Solar/Wind Harmer
0.277
270594AE1-207 GEN
Solar/Wind Harmer
9.407
241972AD1-140 GEN
Solar/Wind Harmer
2.855
965101AG1-375 GEN
Solar/Wind Harmer
6.335
965461AG1-414 GEN
Solar/Wind Harmer
1.422
970289AG2-191 GEN
Solar/Wind Harmer
1.191
958711AF2-162 GEN
Solar/Wind Harmer
0.632
270024AE2-089 GEN
Solar/Wind Harmer
2.831
24729505KEY G4
Adder
3.892
965401AG1-405 GEN
Solar/Wind Harmer
3.19
965411AG1-406 GEN
Solar/Wind Harmer
1.432
963841AG1-237 GEN
Solar/Wind Harmer
6.07
24386205FR-12G C
Solar/Wind Harmer
2.353
24386405FR-21G C
Solar/Wind Harmer
2.362
24386605FR-22G C
Solar/Wind Harmer
2.362
24387005FR-3G C
Solar/Wind Harmer
2.172
24690905MDL-1G C
Solar/Wind Harmer
4.343
270180AB1-006 GEN1
Solar/Wind Harmer
3.891
946581AF1-322 GEN
Solar/Wind Harmer
5.534
24691005MDL-2G C
Solar/Wind Harmer
2.001
24697605MDL-3G C
Solar/Wind Harmer
1.994
24697905MDL-4G C
Solar/Wind Harmer
1.242
270181AB1-006 GEN2
Solar/Wind Harmer
0.387
274775LINCOLN ;6U
Adder
4.276
274776LINCOLN ;7U
Adder
4.276
274777LINCOLN ;8U
Adder
4.276
972227AH1-698 GEN1
Adder
1.32
274731ELWOOD EC;2P
Adder
8.308
274733ELWOOD EC;3P
Adder
8.308
274735ELWOOD EC;4P
Adder
8.308
274728ELWOOD EC;5P
Adder
8.308
24803106KYGER 3LP
50/50
2.431
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
84.399
25194608D.CRK4
Adder
1.69
25196608WSDLE5
Adder
8.803
252510AF1-249 C
Solar/Wind Harmer
0.429
253316AC1-085 GEN3
Solar/Wind Harmer
8.395
253433AC1-085 GEN1
Solar/Wind Harmer
5.329
946181AF1-283 GEN
Solar/Wind Harmer
13.029
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
24.417
972167AH1-666 GEN
Solar/Wind Harmer
7.353
253406AD2-031_GEN
Solar/Wind Harmer
1.133
972173AH1-669 GEN
Solar/Wind Harmer
4.368
270222AC2-111 GEN
Solar/Wind Harmer
6.813
270273AD2-016 GEN
Solar/Wind Harmer
2.223
253415AE1-040 GEN
Solar/Wind Harmer
0.933
253303V4-073 C
Solar/Wind Harmer
0.093
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
3429391JKCT 9G
Adder
6.399
270356AE2-297 GEN
Solar/Wind Harmer
3.47
270437AC2-090 C
Solar/Wind Harmer
4.096
970093AG2-073 GEN
Solar/Wind Harmer
7.006
958821AF2-173 GEN
Solar/Wind Harmer
9.609
270004AE1-209 GEN
Solar/Wind Harmer
3.751
24728705AND G3
Adder
5.489
24728505AND G1
Adder
2.624
966571AG1-526 GEN
Solar/Wind Harmer
15.039
946031AF1-268 GEN
Solar/Wind Harmer
5.61
962031AG1-047 GEN
Solar/Wind Harmer
1.957
957741AF2-068 GEN
Solar/Wind Harmer
9.713
970289AG2-191 GEN
Solar/Wind Harmer
0.481
970291AG2-192 GEN
Solar/Wind Harmer
0.437
247642Z2-115 C
Solar/Wind Harmer
0.039
971617AH1-308 GEN
Solar/Wind Harmer
3.507
944531AF1-118 GEN
Solar/Wind Harmer
20.676
253338AC1-165 GEN
Solar/Wind Harmer
0.642
253333AC1-068 GEN
Solar/Wind Harmer
0.619
970193AG2-126 GEN
Solar/Wind Harmer
8.731
970243AG2-164 GEN
Solar/Wind Harmer
15.006
970519AG2-331 GEN
Solar/Wind Harmer
10.081
970699AG2-449 GEN
Solar/Wind Harmer
6.669
960741AF2-365 GEN
Solar/Wind Harmer
2.727
24755605MDL-5G
Solar/Wind Harmer
1.304
970781AG2-491 GEN
Solar/Wind Harmer
5.408
972273AH1-721 GEN
Adder
43.396
274772LINCOLN ;3U
Adder
4.276
972228AH1-698 GEN2
Adder
1.875
274729ELWOOD EC;1P
Adder
8.308
274730ELWOOD EC;6P
Adder
8.308
274734ELWOOD EC;8P
Adder
8.308
274736ELWOOD EC;9P
Adder
8.308
274800UNIV PARK;3U
Adder
2.945
972038AH1-567 GEN2
Adder
0.184
274802UNIV PARK;5U
Adder
2.944
274826FISK ;BP
Adder
5.526
274676JOLIET 29;8U
Adder
14.929
235780M24_1
Solar/Wind Helper
0.99
24803006KYGER 3HP
50/50
4.129
24802806KYGER 2HP
50/50
4.105
24802906KYGER 2LP
50/50
2.413
252509AD1-136 GEN
Solar/Wind Harmer
0.291
25183208HLCRTG
Solar/Wind Harmer
6.511
252519AF1-045_GEN
Solar/Wind Harmer
6.438
252516AE2-318_GEN
Solar/Wind Harmer
4.911
25194408D.CRK1
Adder
7.772
25194508D.CRK3
Adder
1.453
253317AC1-085 GEN4
Solar/Wind Harmer
8.395
253394AE2-221_GEN
Solar/Wind Harmer
4.283
253398AE2-221_GEN2
Solar/Wind Harmer
4.283
270186AC1-089 GEN
Solar/Wind Harmer
5.375
970235AG2-159 GEN
Solar/Wind Harmer
3.519
970235AG2-159 GEN
Solar/Wind Harmer
2.149
962581AG1-107 GEN
Solar/Wind Harmer
4.366
961491AF2-440 GEN
Solar/Wind Harmer
1.815
339221AD2-048_GEN
Solar/Wind Harmer
1.319
972043AH1-570 GEN
Solar/Wind Harmer
2.09
972045AH1-571 GEN
Solar/Wind Harmer
1.672
971125AH1-004 GEN
Solar/Wind Harmer
3.256
970107AG2-081 GEN
Solar/Wind Harmer
2.442
253370AE2-315 SEC1
Adder
1.603
24728805RICHG1
Adder
2.949
24728905RICHG2
Adder
2.949
25322209TAIT E
Adder
7.54
25322209TAIT E
Adder
7.371
25326109MON D
Adder
0.986
24379505HDWTR1G C
Solar/Wind Harmer
5.802
270209AC1-174_GEN
Solar/Wind Harmer
4.094
926881AC1-175 GEN
Solar/Wind Harmer
4.094
942891AE2-308 GEN
Solar/Wind Harmer
7.33
270383AD1-128 GEN
Solar/Wind Harmer
4.391
970883AG2-550 GEN
Solar/Wind Harmer
6.941
970885AG2-551 GEN
Solar/Wind Harmer
1.614
960161AF2-307 GEN
Solar/Wind Harmer
4.414
970825AG2-519 GEN
Solar/Wind Harmer
7.137
960441AF2-335 GEN
Solar/Wind Harmer
6.731
247621Y3-024
Adder
0.159
964611AG1-324 GEN
Solar/Wind Harmer
0.771
964611AG1-324 GEN
Solar/Wind Harmer
0.342
270201AC2-176 GEN
Solar/Wind Harmer
3.329
270599AE1-208 GEN
Solar/Wind Harmer
5.257
270031AE2-169
Solar/Wind Harmer
5.257
964571AG1-320 GEN
Solar/Wind Harmer
5.25
944541AF1-119 GEN
Solar/Wind Harmer
2.619
960971AF2-388 GEN
Solar/Wind Harmer
6.834
970653AG2-424 GEN
Solar/Wind Harmer
2.963
970653AG2-424 GEN
Solar/Wind Harmer
1.071
942221AE2-234 GEN
Solar/Wind Harmer
0.429
270444AC2-157 GEN1
Solar/Wind Harmer
3.266
945391AF1-204 GEN
Solar/Wind Harmer
8.111
970239AG2-162 GEN
Solar/Wind Harmer
6.391
970241AG2-163 GEN
Solar/Wind Harmer
14.036
971081AG2-670 GEN
Solar/Wind Harmer
4.204
966841AG1-555 GEN
Solar/Wind Harmer
1.378
339236AF1-050_GEN
Solar/Wind Harmer
0.978
945421AF1-207 GEN
Solar/Wind Harmer
7.543
25326509SID D
Adder
0.697
274770LINCOLN ;1U
Adder
4.276
274771LINCOLN ;2U
Adder
4.276
972259AH1-714 GEN
Adder
9.649
274674JOLIET 9 ;6U
Adder
7.776
274803UNIV PARK;6U
Adder
2.944
237033AB1-150 GEN
Solar/Wind Helper
0.4
957841AF2-078 GEN
Solar/Wind Harmer
2.252
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.08
252507AC2-088 GEN
Solar/Wind Harmer
2.039
25196808ZIMRHP
Adder
79.423
25194608D.CRK4
Adder
1.69
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
946171AF1-282 GEN
Solar/Wind Harmer
10.022
25196008MFTGT1
Adder
1.369
945681AF1-233 GEN
Solar/Wind Harmer
17.256
339216AC1-074 GEN
Solar/Wind Harmer
1.467
270263AC1-001 GEN
Solar/Wind Harmer
0.873
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
943111AE2-339 GEN
Solar/Wind Harmer
0.706
25326309TAIT D
Adder
0.846
3429421JKCT 10G
Adder
6.399
972037AH1-567 GEN1
Adder
0.092
274827FISK ;RP
Adder
3.916
274675JOLIET 29;7U
Adder
15.482
274675JOLIET 29;7U
Adder
14.929
274687WILL CNTY;4U
Adder
14.101
274687WILL CNTY;4U
Adder
7.883
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.206
960071AF2-298 GEN
Solar/Wind Harmer
3.823
3429241JKCT 3G
Adder
8.84
942081AE2-220 GEN
Solar/Wind Harmer
4.691
270239V3-007_GEN1
Solar/Wind Harmer
1.263
270005AE1-210 C O1
Solar/Wind Harmer
3.751
965031AG1-367 GEN
Solar/Wind Harmer
6.864
24728605AND G2
Adder
2.624
970825AG2-519 GEN
Solar/Wind Harmer
1.592
971565AH1-281 GEN
Solar/Wind Harmer
1.351
247536S-71 GEN
Solar/Wind Harmer
2.726
945371AF1-202 GEN
Solar/Wind Harmer
4.531
276903AD2-071 C
Solar/Wind Harmer
6.489
971821AH1-427 GEN
Solar/Wind Harmer
6.405
270032AE2-172
Solar/Wind Harmer
2.977
958861AF2-177 GEN
Solar/Wind Harmer
6.924
970291AG2-192 GEN
Solar/Wind Harmer
0.815
965651AG1-433 GEN
Solar/Wind Harmer
3.417
970091AG2-072 GEN
Adder
45.505
253343AC1-166 GEN
Solar/Wind Harmer
0.642
253325AC1-069 GEN
Solar/Wind Harmer
0.619
270445AC2-157 GEN2
Solar/Wind Harmer
3.266
970333AG2-219 GEN
Solar/Wind Harmer
18.34
339241AF1-083 GEN
Solar/Wind Harmer
0.945
963741AG1-226 GEN
Solar/Wind Harmer
25.264
24385905FR-11G C
Solar/Wind Harmer
4.564
24387305FR-4G C
Solar/Wind Harmer
2.79
24791305MDL-5G
Solar/Wind Harmer
1.304
274773LINCOLN ;4U
Adder
4.276
274774LINCOLN ;5U
Adder
4.276
274732ELWOOD EC;7P
Adder
8.308
274674JOLIET 9 ;6U
Adder
7.776
274801UNIV PARK;4U
Adder
2.945
274676JOLIET 29;8U
Adder
15.482
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.205
944201AF1-088_MTX
Adder
67.999
957141AF2-008_MTX
Adder
33.999
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.636
MECLTFEXP_MEC->PJM
CLTF
8.008
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.397
LAGNLTFEXP_LAGN->PJM
CLTF
6.556
TVALTFEXP_TVA->PJM
CLTF
3.109
NYPJM->LTFIMP_NY
CLTF
1.661
LGEELTFEXP_LGEE->PJM
CLTF
5.141
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1558_05BAKER 765_Q_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1558_05BAKER 765_Q_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.9 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2370.07
MW Contribution:6.85
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.411
971191AH1-055 GEN
Solar/Wind Harmer
86.587
25194608D.CRK4
Adder
1.778
25196608WSDLE5
Adder
9.268
252510AF1-249 C
Solar/Wind Harmer
0.452
253316AC1-085 GEN3
Solar/Wind Harmer
8.99
253433AC1-085 GEN1
Solar/Wind Harmer
5.707
946181AF1-283 GEN
Solar/Wind Harmer
13.952
958171AF2-111 GEN
Solar/Wind Harmer
25.736
25196008MFTGT1
Adder
1.386
972173AH1-669 GEN
Solar/Wind Harmer
4.892
972167AH1-666 GEN
Solar/Wind Harmer
7.71
253406AD2-031_GEN
Solar/Wind Harmer
1.22
270273AD2-016 GEN
Solar/Wind Harmer
2.5
253415AE1-040 GEN
Solar/Wind Harmer
1.023
270222AC2-111 GEN
Solar/Wind Harmer
7.003
253303V4-073 C
Solar/Wind Harmer
0.1
253370AE2-315 SEC1
Adder
1.72
253371AE2-315 SEC2
Adder
1.627
3429391JKCT 9G
Adder
6.576
270356AE2-297 GEN
Solar/Wind Harmer
3.463
270437AC2-090 C
Solar/Wind Harmer
3.998
970093AG2-073 GEN
Solar/Wind Harmer
7.116
966571AG1-526 GEN
Solar/Wind Harmer
15.203
24728705AND G3
Adder
5.409
24728505AND G1
Adder
2.586
253338AC1-165 GEN
Solar/Wind Harmer
0.731
253333AC1-068 GEN
Solar/Wind Harmer
0.705
958821AF2-173 GEN
Solar/Wind Harmer
9.202
270004AE1-209 GEN
Solar/Wind Harmer
3.592
946031AF1-268 GEN
Solar/Wind Harmer
5.411
970243AG2-164 GEN
Solar/Wind Harmer
16.205
970519AG2-331 GEN
Solar/Wind Harmer
10.887
970699AG2-449 GEN
Solar/Wind Harmer
7.202
24803006KYGER 3HP
50/50
4.182
24802806KYGER 2HP
50/50
4.157
24802906KYGER 2LP
50/50
2.444
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.907
252519AF1-045_GEN
Solar/Wind Harmer
6.804
252516AE2-318_GEN
Solar/Wind Harmer
5.19
25194408D.CRK1
Adder
8.18
25194508D.CRK3
Adder
1.529
253317AC1-085 GEN4
Solar/Wind Harmer
8.99
253394AE2-221_GEN
Solar/Wind Harmer
4.598
253398AE2-221_GEN2
Solar/Wind Harmer
4.598
270186AC1-089 GEN
Solar/Wind Harmer
5.704
962581AG1-107 GEN
Solar/Wind Harmer
4.651
961491AF2-440 GEN
Solar/Wind Harmer
1.933
970235AG2-159 GEN
Solar/Wind Harmer
3.657
970235AG2-159 GEN
Solar/Wind Harmer
2.233
339221AD2-048_GEN
Solar/Wind Harmer
1.371
972043AH1-570 GEN
Solar/Wind Harmer
2.168
972045AH1-571 GEN
Solar/Wind Harmer
1.734
253370AE2-315 SEC1
Adder
1.72
971125AH1-004 GEN
Solar/Wind Harmer
3.367
970107AG2-081 GEN
Solar/Wind Harmer
2.525
25322209TAIT E
Adder
8.1
25322209TAIT E
Adder
7.918
25326109MON D
Adder
1.066
24728805RICHG1
Adder
2.989
24728905RICHG2
Adder
2.989
942891AE2-308 GEN
Solar/Wind Harmer
7.489
24379505HDWTR1G C
Solar/Wind Harmer
5.662
270209AC1-174_GEN
Solar/Wind Harmer
3.996
926881AC1-175 GEN
Solar/Wind Harmer
3.996
270383AD1-128 GEN
Solar/Wind Harmer
4.312
960161AF2-307 GEN
Solar/Wind Harmer
4.476
970883AG2-550 GEN
Solar/Wind Harmer
6.854
970885AG2-551 GEN
Solar/Wind Harmer
1.594
970825AG2-519 GEN
Solar/Wind Harmer
6.864
960441AF2-335 GEN
Solar/Wind Harmer
6.467
964571AG1-320 GEN
Solar/Wind Harmer
5.282
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.745
964611AG1-324 GEN
Solar/Wind Harmer
0.331
970239AG2-162 GEN
Solar/Wind Harmer
6.902
270201AC2-176 GEN
Solar/Wind Harmer
3.22
970653AG2-424 GEN
Solar/Wind Harmer
2.961
970653AG2-424 GEN
Solar/Wind Harmer
1.071
270518AE2-148 GEN
Solar/Wind Harmer
7.398
270599AE1-208 GEN
Solar/Wind Harmer
4.966
270031AE2-169
Solar/Wind Harmer
4.966
270444AC2-157 GEN1
Solar/Wind Harmer
3.313
25326509SID D
Adder
0.762
944541AF1-119 GEN
Solar/Wind Harmer
2.391
960971AF2-388 GEN
Solar/Wind Harmer
6.241
945391AF1-204 GEN
Solar/Wind Harmer
7.862
971081AG2-670 GEN
Solar/Wind Harmer
4.133
942221AE2-234 GEN
Solar/Wind Harmer
0.395
253378AE2-206_GEN
Solar/Wind Harmer
1.933
276820AF1-078_GEN
Solar/Wind Harmer
0.858
970241AG2-163 GEN
Solar/Wind Harmer
13.348
339236AF1-050_GEN
Solar/Wind Harmer
0.955
24802606KYGER 1HP
50/50
4.206
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.411
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.778
252524AE2-267 GEN
Solar/Wind Harmer
1.706
25196408WSDLE3
Adder
9.541
25196308WSDLE2
Adder
9.458
25196208WSDLE1
Adder
9.434
25196708WSDLE6
Adder
9.41
25196508WSDLE4
Adder
9.173
25196108MFTGT2
Adder
1.578
25196108MFTGT2
Adder
1.465
270367AC2-061_GEN
Solar/Wind Harmer
3.016
972163AH1-664 GEN
Solar/Wind Harmer
9.479
972165AH1-665 GEN
Solar/Wind Harmer
7.583
270269AC2-059
Solar/Wind Harmer
8.741
270340AC2-060 GEN
Solar/Wind Harmer
2.826
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
944031AF1-071 GEN
Solar/Wind Harmer
0.863
253372AE2-315 SEC3
Adder
1.627
253372AE2-315 SEC3
Adder
1.627
25306009OHH W.
Adder
2.431
970689AG2-444 GEN
Solar/Wind Harmer
13.51
253349AC2-067 GEN
Solar/Wind Harmer
4.095
253400AC2-068 GEN
Solar/Wind Harmer
1.647
3429211JKCT 2G
Adder
8.934
270432AC2-029 GEN
Solar/Wind Harmer
5.224
971673AH1-337 GEN
Solar/Wind Harmer
3.327
270240V3-007_GEN2
Solar/Wind Harmer
4.43
971029AG2-637 GEN
Solar/Wind Harmer
10.703
241972AD1-140 GEN
Solar/Wind Harmer
3.161
270543AE2-219 C
Solar/Wind Harmer
3.509
970455AG2-298 GEN
Solar/Wind Harmer
3.965
339211AE2-254 GEN
Solar/Wind Harmer
0.992
970115AG2-085 GEN
Solar/Wind Harmer
2.587
24725505WLD G2 C
Solar/Wind Harmer
2.527
24699105WLD G1 C
Solar/Wind Harmer
2.497
961761AG1-017 GEN
Solar/Wind Harmer
0.268
270594AE1-207 GEN
Solar/Wind Harmer
8.981
945581AF1-223 GEN
Solar/Wind Harmer
2.744
965461AG1-414 GEN
Solar/Wind Harmer
1.353
970289AG2-191 GEN
Solar/Wind Harmer
1.134
965101AG1-375 GEN
Solar/Wind Harmer
5.827
270024AE2-089 GEN
Solar/Wind Harmer
2.681
958711AF2-162 GEN
Solar/Wind Harmer
0.578
965401AG1-405 GEN
Solar/Wind Harmer
3.127
965411AG1-406 GEN
Solar/Wind Harmer
1.403
270156DARBY CT1
Adder
4.854
270157DARBY CT2
Adder
4.842
270158DARBY CT3
Adder
4.765
972203AH1-686 GEN
Adder
1.236
24729505KEY G4
Adder
3.472
963841AG1-237 GEN
Solar/Wind Harmer
5.739
945631AF1-228 GEN
Solar/Wind Harmer
2.433
24386205FR-12G C
Solar/Wind Harmer
2.21
24386405FR-21G C
Solar/Wind Harmer
2.218
24386605FR-22G C
Solar/Wind Harmer
2.218
24387005FR-3G C
Solar/Wind Harmer
2.04
24690905MDL-1G C
Solar/Wind Harmer
4.036
270180AB1-006 GEN1
Solar/Wind Harmer
3.615
274731ELWOOD EC;2P
Adder
7.226
274733ELWOOD EC;3P
Adder
7.226
274735ELWOOD EC;4P
Adder
7.226
274728ELWOOD EC;5P
Adder
7.225
972227AH1-698 GEN1
Adder
1.146
274675JOLIET 29;7U
Adder
13.447
274675JOLIET 29;7U
Adder
12.966
274687WILL CNTY;4U
Adder
12.245
274687WILL CNTY;4U
Adder
12.245
972037AH1-567 GEN1
Adder
0.08
274746AC1-111 G10
Adder
2.448
274744AC1-111 GEN8
Adder
2.448
274827FISK ;RP
Adder
3.396
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
946581AF1-322 GEN
Solar/Wind Harmer
1.964
962031AG1-047 GEN
Solar/Wind Harmer
1.893
957741AF2-068 GEN
Solar/Wind Harmer
9.396
970289AG2-191 GEN
Solar/Wind Harmer
0.458
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.321
970193AG2-126 GEN
Solar/Wind Harmer
8.463
960741AF2-365 GEN
Solar/Wind Harmer
2.669
944531AF1-118 GEN
Solar/Wind Harmer
18.282
970605AG2-385 GEN
Solar/Wind Harmer
2.789
972273AH1-721 GEN
Adder
41.984
274729ELWOOD EC;1P
Adder
7.226
274730ELWOOD EC;6P
Adder
7.225
274734ELWOOD EC;8P
Adder
7.225
274736ELWOOD EC;9P
Adder
7.225
972228AH1-698 GEN2
Adder
1.628
274800UNIV PARK;3U
Adder
2.555
972038AH1-567 GEN2
Adder
0.16
274676JOLIET 29;8U
Adder
12.966
274802UNIV PARK;5U
Adder
2.554
274826FISK ;BP
Adder
4.792
235780M24_1
Solar/Wind Helper
0.998
970077AG2-063 GEN
Solar/Wind Harmer
2.789
966841AG1-555 GEN
Solar/Wind Harmer
1.294
274674JOLIET 9 ;6U
Adder
6.759
972259AH1-714 GEN
Adder
8.367
274803UNIV PARK;6U
Adder
2.554
274696ROCKY RD ;4P
Adder
0.295
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803406KYGER 5HP
50/50
4.135
24803206KYGER 4HP
50/50
4.132
252507AC2-088 GEN
Solar/Wind Harmer
2.152
25196808ZIMRHP
Adder
83.726
25194608D.CRK4
Adder
1.778
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.732
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
18.088
270263AC1-001 GEN
Solar/Wind Harmer
0.979
339216AC1-074 GEN
Solar/Wind Harmer
1.526
253370AE2-315 SEC1
Adder
1.72
253371AE2-315 SEC2
Adder
1.627
25326309TAIT D
Adder
0.909
943111AE2-339 GEN
Solar/Wind Harmer
0.729
960071AF2-298 GEN
Solar/Wind Harmer
4.096
3429421JKCT 10G
Adder
6.576
3429241JKCT 3G
Adder
9.052
942081AE2-220 GEN
Solar/Wind Harmer
4.578
270239V3-007_GEN1
Solar/Wind Harmer
1.232
971565AH1-281 GEN
Solar/Wind Harmer
1.37
24728605AND G2
Adder
2.586
253343AC1-166 GEN
Solar/Wind Harmer
0.731
253325AC1-069 GEN
Solar/Wind Harmer
0.705
247536S-71 GEN
Solar/Wind Harmer
2.668
270005AE1-210 C O1
Solar/Wind Harmer
3.592
965031AG1-367 GEN
Solar/Wind Harmer
6.573
970825AG2-519 GEN
Solar/Wind Harmer
1.532
970091AG2-072 GEN
Adder
49.481
971821AH1-427 GEN
Solar/Wind Harmer
6.424
970333AG2-219 GEN
Solar/Wind Harmer
19.806
276903AD2-071 C
Solar/Wind Harmer
6.236
270032AE2-172
Solar/Wind Harmer
2.842
945371AF1-202 GEN
Solar/Wind Harmer
4.221
970291AG2-192 GEN
Solar/Wind Harmer
0.776
270445AC2-157 GEN2
Solar/Wind Harmer
3.313
958861AF2-177 GEN
Solar/Wind Harmer
6.369
965651AG1-433 GEN
Solar/Wind Harmer
3.12
339241AF1-083 GEN
Solar/Wind Harmer
0.932
270159DARBY CT4
Adder
4.776
963741AG1-226 GEN
Solar/Wind Harmer
24.026
970593AG2-378 GEN
Solar/Wind Harmer
1.033
24385905FR-11G C
Solar/Wind Harmer
4.286
24387305FR-4G C
Solar/Wind Harmer
2.62
964901AG1-354 GEN
Solar/Wind Harmer
7.622
274732ELWOOD EC;7P
Adder
7.225
274674JOLIET 9 ;6U
Adder
6.759
274801UNIV PARK;4U
Adder
2.555
274676JOLIET 29;8U
Adder
13.447
274745AC1-111 GEN9
Adder
2.448
960001AF2-291 GEN
Solar/Wind Helper
1.675
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
68.979
957141AF2-008_MTX
Adder
34.49
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.301
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.83
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.269
MECLTFEXP_MEC->PJM
CLTF
7.133
SIGELTFEXP_SIGE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.558
LAGNLTFEXP_LAGN->PJM
CLTF
5.577
TVALTFEXP_TVA->PJM
CLTF
2.613
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.304
WECLTFEXP_WEC->PJM
CLTF
1.665
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.668
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#309_05HANG R 765_B2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#309_05HANG R 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.46 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2363.36
MW Contribution:6.84
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
86.549
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.451
253316AC1-085 GEN3
Solar/Wind Harmer
8.982
253433AC1-085 GEN1
Solar/Wind Harmer
5.702
946181AF1-283 GEN
Solar/Wind Harmer
13.94
958171AF2-111 GEN
Solar/Wind Harmer
25.744
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
4.883
972167AH1-666 GEN
Solar/Wind Harmer
7.721
253406AD2-031_GEN
Solar/Wind Harmer
1.219
270273AD2-016 GEN
Solar/Wind Harmer
2.495
253415AE1-040 GEN
Solar/Wind Harmer
1.022
270222AC2-111 GEN
Solar/Wind Harmer
6.995
253303V4-073 C
Solar/Wind Harmer
0.099
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
3.459
270437AC2-090 C
Solar/Wind Harmer
3.992
970093AG2-073 GEN
Solar/Wind Harmer
7.147
966571AG1-526 GEN
Solar/Wind Harmer
15.27
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.729
253333AC1-068 GEN
Solar/Wind Harmer
0.703
958821AF2-173 GEN
Solar/Wind Harmer
9.186
270004AE1-209 GEN
Solar/Wind Harmer
3.586
946031AF1-268 GEN
Solar/Wind Harmer
5.401
970243AG2-164 GEN
Solar/Wind Harmer
16.159
970519AG2-331 GEN
Solar/Wind Harmer
10.856
970699AG2-449 GEN
Solar/Wind Harmer
7.182
962031AG1-047 GEN
Solar/Wind Harmer
1.89
957741AF2-068 GEN
Solar/Wind Harmer
9.378
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
8.454
960741AF2-365 GEN
Solar/Wind Harmer
2.685
944531AF1-118 GEN
Solar/Wind Harmer
18.231
970605AG2-385 GEN
Solar/Wind Harmer
2.779
972273AH1-721 GEN
Adder
42.389
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274802UNIV PARK;5U
Adder
2.549
235780M24_1
Solar/Wind Helper
0.999
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.756
252524AE2-267 GEN
Solar/Wind Harmer
1.704
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
9.494
972165AH1-665 GEN
Solar/Wind Harmer
7.595
270367AC2-061_GEN
Solar/Wind Harmer
3.018
270269AC2-059
Solar/Wind Harmer
8.724
270340AC2-060 GEN
Solar/Wind Harmer
2.823
339243AC2-075 GEN1
Solar/Wind Harmer
0.414
944031AF1-071 GEN
Solar/Wind Harmer
0.862
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
13.474
253349AC2-067 GEN
Solar/Wind Harmer
4.09
253400AC2-068 GEN
Solar/Wind Harmer
1.644
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
5.21
971673AH1-337 GEN
Solar/Wind Harmer
3.321
270240V3-007_GEN2
Solar/Wind Harmer
4.424
971029AG2-637 GEN
Solar/Wind Harmer
10.686
241972AD1-140 GEN
Solar/Wind Harmer
3.154
270543AE2-219 C
Solar/Wind Harmer
3.503
970455AG2-298 GEN
Solar/Wind Harmer
3.979
339211AE2-254 GEN
Solar/Wind Harmer
0.997
970115AG2-085 GEN
Solar/Wind Harmer
2.582
24725505WLD G2 C
Solar/Wind Harmer
2.523
24699105WLD G1 C
Solar/Wind Harmer
2.493
961761AG1-017 GEN
Solar/Wind Harmer
0.268
270594AE1-207 GEN
Solar/Wind Harmer
8.964
945581AF1-223 GEN
Solar/Wind Harmer
2.738
965461AG1-414 GEN
Solar/Wind Harmer
1.35
970289AG2-191 GEN
Solar/Wind Harmer
1.132
965101AG1-375 GEN
Solar/Wind Harmer
5.814
270024AE2-089 GEN
Solar/Wind Harmer
2.674
958711AF2-162 GEN
Solar/Wind Harmer
0.576
965401AG1-405 GEN
Solar/Wind Harmer
3.152
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
5.728
945631AF1-228 GEN
Solar/Wind Harmer
2.424
24386205FR-12G C
Solar/Wind Harmer
2.206
24386405FR-21G C
Solar/Wind Harmer
2.213
24386605FR-22G C
Solar/Wind Harmer
2.213
24387005FR-3G C
Solar/Wind Harmer
2.036
24690905MDL-1G C
Solar/Wind Harmer
4.026
270180AB1-006 GEN1
Solar/Wind Harmer
3.607
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
274746AC1-111 G10
Adder
2.444
274744AC1-111 GEN8
Adder
2.444
972037AH1-567 GEN1
Adder
0.08
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
946581AF1-322 GEN
Solar/Wind Harmer
1.959
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.901
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
5.186
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
8.982
253394AE2-221_GEN
Solar/Wind Harmer
4.593
253398AE2-221_GEN2
Solar/Wind Harmer
4.593
270186AC1-089 GEN
Solar/Wind Harmer
5.711
962581AG1-107 GEN
Solar/Wind Harmer
4.655
961491AF2-440 GEN
Solar/Wind Harmer
1.934
970235AG2-159 GEN
Solar/Wind Harmer
3.659
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
1.373
972043AH1-570 GEN
Solar/Wind Harmer
2.172
972045AH1-571 GEN
Solar/Wind Harmer
1.738
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
3.374
970107AG2-081 GEN
Solar/Wind Harmer
2.53
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
7.516
24379505HDWTR1G C
Solar/Wind Harmer
5.654
270209AC1-174_GEN
Solar/Wind Harmer
3.99
926881AC1-175 GEN
Solar/Wind Harmer
3.99
270383AD1-128 GEN
Solar/Wind Harmer
4.306
960161AF2-307 GEN
Solar/Wind Harmer
4.504
970883AG2-550 GEN
Solar/Wind Harmer
6.842
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
6.852
964571AG1-320 GEN
Solar/Wind Harmer
5.299
960441AF2-335 GEN
Solar/Wind Harmer
6.456
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.744
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
6.882
270201AC2-176 GEN
Solar/Wind Harmer
3.214
970653AG2-424 GEN
Solar/Wind Harmer
2.974
970653AG2-424 GEN
Solar/Wind Harmer
1.075
270518AE2-148 GEN
Solar/Wind Harmer
7.376
270599AE1-208 GEN
Solar/Wind Harmer
4.957
270031AE2-169
Solar/Wind Harmer
4.957
270444AC2-157 GEN1
Solar/Wind Harmer
3.31
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
2.386
960971AF2-388 GEN
Solar/Wind Harmer
6.226
945391AF1-204 GEN
Solar/Wind Harmer
7.855
971081AG2-670 GEN
Solar/Wind Harmer
4.16
942221AE2-234 GEN
Solar/Wind Harmer
0.394
253378AE2-206_GEN
Solar/Wind Harmer
1.926
276820AF1-078_GEN
Solar/Wind Harmer
0.856
970241AG2-163 GEN
Solar/Wind Harmer
13.326
339236AF1-050_GEN
Solar/Wind Harmer
0.962
970077AG2-063 GEN
Solar/Wind Harmer
2.779
966841AG1-555 GEN
Solar/Wind Harmer
1.291
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
972267AH1-718 GEN
Adder
1.821
274803UNIV PARK;6U
Adder
2.549
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
2.151
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.723
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
18.114
270263AC1-001 GEN
Solar/Wind Harmer
0.977
339216AC1-074 GEN
Solar/Wind Harmer
1.528
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
943111AE2-339 GEN
Solar/Wind Harmer
0.73
960071AF2-298 GEN
Solar/Wind Harmer
4.09
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
942081AE2-220 GEN
Solar/Wind Harmer
4.571
270239V3-007_GEN1
Solar/Wind Harmer
1.23
971565AH1-281 GEN
Solar/Wind Harmer
1.374
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.729
253325AC1-069 GEN
Solar/Wind Harmer
0.703
247536S-71 GEN
Solar/Wind Harmer
2.663
270005AE1-210 C O1
Solar/Wind Harmer
3.586
965031AG1-367 GEN
Solar/Wind Harmer
6.561
970825AG2-519 GEN
Solar/Wind Harmer
1.529
971821AH1-427 GEN
Solar/Wind Harmer
6.457
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
19.749
276903AD2-071 C
Solar/Wind Harmer
6.224
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
4.213
970291AG2-192 GEN
Solar/Wind Harmer
0.774
270445AC2-157 GEN2
Solar/Wind Harmer
3.31
958861AF2-177 GEN
Solar/Wind Harmer
6.354
965651AG1-433 GEN
Solar/Wind Harmer
3.113
339241AF1-083 GEN
Solar/Wind Harmer
0.937
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
23.987
970593AG2-378 GEN
Solar/Wind Harmer
1.029
24385905FR-11G C
Solar/Wind Harmer
4.277
24387305FR-4G C
Solar/Wind Harmer
2.615
964901AG1-354 GEN
Solar/Wind Harmer
7.68
274732ELWOOD EC;7P
Adder
7.212
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P4_#1560_05BAKER 765_Q2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#1560_05BAKER 765_Q2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:153.34 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2361.46
MW Contribution:6.83
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.203
24802706KYGER 1LP
50/50
2.467
24803506KYGER 5LP
50/50
2.409
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
50.731
252524AE2-267 GEN
Solar/Wind Harmer
1.703
25196408WSDLE3
Adder
9.524
25196308WSDLE2
Adder
9.441
25196208WSDLE1
Adder
9.417
25196708WSDLE6
Adder
9.394
25196508WSDLE4
Adder
9.157
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
972163AH1-664 GEN
Solar/Wind Harmer
9.474
972165AH1-665 GEN
Solar/Wind Harmer
7.579
270367AC2-061_GEN
Solar/Wind Harmer
3.01
270269AC2-059
Solar/Wind Harmer
8.712
270340AC2-060 GEN
Solar/Wind Harmer
2.818
339243AC2-075 GEN1
Solar/Wind Harmer
0.413
944031AF1-071 GEN
Solar/Wind Harmer
0.861
253372AE2-315 SEC3
Adder
1.623
253372AE2-315 SEC3
Adder
1.623
25306009OHH W.
Adder
2.424
970689AG2-444 GEN
Solar/Wind Harmer
13.458
253349AC2-067 GEN
Solar/Wind Harmer
4.085
253400AC2-068 GEN
Solar/Wind Harmer
1.643
3429211JKCT 2G
Adder
8.952
270432AC2-029 GEN
Solar/Wind Harmer
5.202
971673AH1-337 GEN
Solar/Wind Harmer
3.318
270240V3-007_GEN2
Solar/Wind Harmer
4.42
971029AG2-637 GEN
Solar/Wind Harmer
10.676
241972AD1-140 GEN
Solar/Wind Harmer
3.15
270543AE2-219 C
Solar/Wind Harmer
3.5
970455AG2-298 GEN
Solar/Wind Harmer
3.975
339211AE2-254 GEN
Solar/Wind Harmer
0.995
970115AG2-085 GEN
Solar/Wind Harmer
2.58
24725505WLD G2 C
Solar/Wind Harmer
2.521
24699105WLD G1 C
Solar/Wind Harmer
2.491
961761AG1-017 GEN
Solar/Wind Harmer
0.267
270594AE1-207 GEN
Solar/Wind Harmer
8.956
945581AF1-223 GEN
Solar/Wind Harmer
2.736
965461AG1-414 GEN
Solar/Wind Harmer
1.349
970289AG2-191 GEN
Solar/Wind Harmer
1.131
965101AG1-375 GEN
Solar/Wind Harmer
5.809
270024AE2-089 GEN
Solar/Wind Harmer
2.672
958711AF2-162 GEN
Solar/Wind Harmer
0.576
965401AG1-405 GEN
Solar/Wind Harmer
3.149
965411AG1-406 GEN
Solar/Wind Harmer
1.413
270156DARBY CT1
Adder
4.829
270157DARBY CT2
Adder
4.817
270158DARBY CT3
Adder
4.74
24729505KEY G4
Adder
3.46
972203AH1-686 GEN
Adder
1.224
963841AG1-237 GEN
Solar/Wind Harmer
5.724
945631AF1-228 GEN
Solar/Wind Harmer
2.42
24386205FR-12G C
Solar/Wind Harmer
2.204
24386405FR-21G C
Solar/Wind Harmer
2.212
24386605FR-22G C
Solar/Wind Harmer
2.212
24387005FR-3G C
Solar/Wind Harmer
2.034
24690905MDL-1G C
Solar/Wind Harmer
4.023
270180AB1-006 GEN1
Solar/Wind Harmer
3.604
274731ELWOOD EC;2P
Adder
7.207
274733ELWOOD EC;3P
Adder
7.207
274735ELWOOD EC;4P
Adder
7.207
274728ELWOOD EC;5P
Adder
7.207
972227AH1-698 GEN1
Adder
1.143
274675JOLIET 29;7U
Adder
13.413
274675JOLIET 29;7U
Adder
12.934
274687WILL CNTY;4U
Adder
12.214
274687WILL CNTY;4U
Adder
12.214
274746AC1-111 G10
Adder
2.442
274744AC1-111 GEN8
Adder
2.442
972037AH1-567 GEN1
Adder
0.08
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.2
946581AF1-322 GEN
Solar/Wind Harmer
1.958
24803106KYGER 3LP
50/50
2.46
24803306KYGER 4LP
50/50
2.409
971191AH1-055 GEN
Solar/Wind Harmer
86.509
25194608D.CRK4
Adder
1.775
25196608WSDLE5
Adder
9.252
252510AF1-249 C
Solar/Wind Harmer
0.451
253316AC1-085 GEN3
Solar/Wind Harmer
8.973
253433AC1-085 GEN1
Solar/Wind Harmer
5.696
946181AF1-283 GEN
Solar/Wind Harmer
13.926
958171AF2-111 GEN
Solar/Wind Harmer
25.716
25196008MFTGT1
Adder
1.384
972173AH1-669 GEN
Solar/Wind Harmer
4.876
972167AH1-666 GEN
Solar/Wind Harmer
7.706
253406AD2-031_GEN
Solar/Wind Harmer
1.218
270273AD2-016 GEN
Solar/Wind Harmer
2.491
253415AE1-040 GEN
Solar/Wind Harmer
1.02
270222AC2-111 GEN
Solar/Wind Harmer
6.988
253303V4-073 C
Solar/Wind Harmer
0.099
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
3429391JKCT 9G
Adder
6.587
270356AE2-297 GEN
Solar/Wind Harmer
3.456
270437AC2-090 C
Solar/Wind Harmer
3.989
970093AG2-073 GEN
Solar/Wind Harmer
7.136
966571AG1-526 GEN
Solar/Wind Harmer
15.255
24728705AND G3
Adder
5.399
24728505AND G1
Adder
2.582
253338AC1-165 GEN
Solar/Wind Harmer
0.728
253333AC1-068 GEN
Solar/Wind Harmer
0.702
958821AF2-173 GEN
Solar/Wind Harmer
9.178
270004AE1-209 GEN
Solar/Wind Harmer
3.583
946031AF1-268 GEN
Solar/Wind Harmer
5.397
970243AG2-164 GEN
Solar/Wind Harmer
16.146
970519AG2-331 GEN
Solar/Wind Harmer
10.848
970699AG2-449 GEN
Solar/Wind Harmer
7.176
962031AG1-047 GEN
Solar/Wind Harmer
1.888
957741AF2-068 GEN
Solar/Wind Harmer
9.369
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.415
247642Z2-115 C
Solar/Wind Harmer
0.037
971617AH1-308 GEN
Solar/Wind Harmer
3.31
970193AG2-126 GEN
Solar/Wind Harmer
8.449
960741AF2-365 GEN
Solar/Wind Harmer
2.684
944531AF1-118 GEN
Solar/Wind Harmer
18.215
970605AG2-385 GEN
Solar/Wind Harmer
2.775
972273AH1-721 GEN
Adder
42.355
274729ELWOOD EC;1P
Adder
7.207
274730ELWOOD EC;6P
Adder
7.207
274734ELWOOD EC;8P
Adder
7.207
274736ELWOOD EC;9P
Adder
7.207
972228AH1-698 GEN2
Adder
1.623
274676JOLIET 29;8U
Adder
12.934
274800UNIV PARK;3U
Adder
2.548
972038AH1-567 GEN2
Adder
0.159
274802UNIV PARK;5U
Adder
2.547
235780M24_1
Solar/Wind Helper
0.999
24803006KYGER 3HP
50/50
4.179
24802806KYGER 2HP
50/50
4.154
24802906KYGER 2LP
50/50
2.442
252509AD1-136 GEN
Solar/Wind Harmer
0.307
25183208HLCRTG
Solar/Wind Harmer
6.895
252519AF1-045_GEN
Solar/Wind Harmer
6.792
252516AE2-318_GEN
Solar/Wind Harmer
5.181
25194408D.CRK1
Adder
8.166
25194508D.CRK3
Adder
1.527
253317AC1-085 GEN4
Solar/Wind Harmer
8.973
253394AE2-221_GEN
Solar/Wind Harmer
4.589
253398AE2-221_GEN2
Solar/Wind Harmer
4.589
270186AC1-089 GEN
Solar/Wind Harmer
5.695
962581AG1-107 GEN
Solar/Wind Harmer
4.642
961491AF2-440 GEN
Solar/Wind Harmer
1.929
970235AG2-159 GEN
Solar/Wind Harmer
3.656
970235AG2-159 GEN
Solar/Wind Harmer
2.232
339221AD2-048_GEN
Solar/Wind Harmer
1.371
972043AH1-570 GEN
Solar/Wind Harmer
2.169
972045AH1-571 GEN
Solar/Wind Harmer
1.735
253370AE2-315 SEC1
Adder
1.716
971125AH1-004 GEN
Solar/Wind Harmer
3.37
970107AG2-081 GEN
Solar/Wind Harmer
2.527
25322209TAIT E
Adder
8.079
25322209TAIT E
Adder
7.897
25326109MON D
Adder
1.063
24728805RICHG1
Adder
2.983
24728905RICHG2
Adder
2.983
942891AE2-308 GEN
Solar/Wind Harmer
7.505
24379505HDWTR1G C
Solar/Wind Harmer
5.649
270209AC1-174_GEN
Solar/Wind Harmer
3.987
926881AC1-175 GEN
Solar/Wind Harmer
3.987
270383AD1-128 GEN
Solar/Wind Harmer
4.302
960161AF2-307 GEN
Solar/Wind Harmer
4.486
970883AG2-550 GEN
Solar/Wind Harmer
6.835
970885AG2-551 GEN
Solar/Wind Harmer
1.59
970825AG2-519 GEN
Solar/Wind Harmer
6.846
964571AG1-320 GEN
Solar/Wind Harmer
5.295
960441AF2-335 GEN
Solar/Wind Harmer
6.451
247621Y3-024
Adder
0.154
964611AG1-324 GEN
Solar/Wind Harmer
0.743
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
6.877
270201AC2-176 GEN
Solar/Wind Harmer
3.211
970653AG2-424 GEN
Solar/Wind Harmer
2.972
970653AG2-424 GEN
Solar/Wind Harmer
1.074
270518AE2-148 GEN
Solar/Wind Harmer
7.366
270599AE1-208 GEN
Solar/Wind Harmer
4.953
270031AE2-169
Solar/Wind Harmer
4.953
270444AC2-157 GEN1
Solar/Wind Harmer
3.307
25326509SID D
Adder
0.759
944541AF1-119 GEN
Solar/Wind Harmer
2.384
960971AF2-388 GEN
Solar/Wind Harmer
6.221
945391AF1-204 GEN
Solar/Wind Harmer
7.849
971081AG2-670 GEN
Solar/Wind Harmer
4.157
942221AE2-234 GEN
Solar/Wind Harmer
0.394
253378AE2-206_GEN
Solar/Wind Harmer
1.924
276820AF1-078_GEN
Solar/Wind Harmer
0.855
970241AG2-163 GEN
Solar/Wind Harmer
13.317
339236AF1-050_GEN
Solar/Wind Harmer
0.962
966841AG1-555 GEN
Solar/Wind Harmer
1.29
970077AG2-063 GEN
Solar/Wind Harmer
2.775
274674JOLIET 9 ;6U
Adder
6.742
972259AH1-714 GEN
Adder
8.345
972267AH1-718 GEN
Adder
1.82
274803UNIV PARK;6U
Adder
2.547
274764LEE CO EC;5U
Adder
4.073
274765LEE CO EC;6U
Adder
2.573
237033AB1-150 GEN
Solar/Wind Helper
0.403
24803406KYGER 5HP
50/50
4.132
24803206KYGER 4HP
50/50
4.129
252507AC2-088 GEN
Solar/Wind Harmer
2.149
25196808ZIMRHP
Adder
83.601
25194608D.CRK4
Adder
1.775
253432AC1-085 GEN2
Solar/Wind Harmer
0.287
946171AF1-282 GEN
Solar/Wind Harmer
10.712
25196008MFTGT1
Adder
1.429
945681AF1-233 GEN
Solar/Wind Harmer
18.078
270263AC1-001 GEN
Solar/Wind Harmer
0.975
339216AC1-074 GEN
Solar/Wind Harmer
1.526
253370AE2-315 SEC1
Adder
1.716
253371AE2-315 SEC2
Adder
1.623
25326309TAIT D
Adder
0.907
943111AE2-339 GEN
Solar/Wind Harmer
0.73
960071AF2-298 GEN
Solar/Wind Harmer
4.085
3429421JKCT 10G
Adder
6.587
3429241JKCT 3G
Adder
9.07
942081AE2-220 GEN
Solar/Wind Harmer
4.567
270239V3-007_GEN1
Solar/Wind Harmer
1.229
971565AH1-281 GEN
Solar/Wind Harmer
1.373
24728605AND G2
Adder
2.582
253343AC1-166 GEN
Solar/Wind Harmer
0.728
253325AC1-069 GEN
Solar/Wind Harmer
0.702
247536S-71 GEN
Solar/Wind Harmer
2.66
270005AE1-210 C O1
Solar/Wind Harmer
3.583
965031AG1-367 GEN
Solar/Wind Harmer
6.556
970825AG2-519 GEN
Solar/Wind Harmer
1.528
971821AH1-427 GEN
Solar/Wind Harmer
6.451
970091AG2-072 GEN
Adder
49.343
970333AG2-219 GEN
Solar/Wind Harmer
19.734
276903AD2-071 C
Solar/Wind Harmer
6.219
270032AE2-172
Solar/Wind Harmer
2.834
945371AF1-202 GEN
Solar/Wind Harmer
4.209
970291AG2-192 GEN
Solar/Wind Harmer
0.774
270445AC2-157 GEN2
Solar/Wind Harmer
3.307
958861AF2-177 GEN
Solar/Wind Harmer
6.349
965651AG1-433 GEN
Solar/Wind Harmer
3.11
339241AF1-083 GEN
Solar/Wind Harmer
0.937
270159DARBY CT4
Adder
4.752
963741AG1-226 GEN
Solar/Wind Harmer
23.97
24385905FR-11G C
Solar/Wind Harmer
4.274
24387305FR-4G C
Solar/Wind Harmer
2.613
970593AG2-378 GEN
Solar/Wind Harmer
1.028
964901AG1-354 GEN
Solar/Wind Harmer
7.677
274732ELWOOD EC;7P
Adder
7.207
274674JOLIET 9 ;6U
Adder
6.742
274676JOLIET 29;8U
Adder
13.413
274801UNIV PARK;4U
Adder
2.548
274745AC1-111 GEN9
Adder
2.442
960001AF2-291 GEN
Solar/Wind Helper
1.68
270331AC1-082 GEN3
Solar/Wind Helper
0.199
944201AF1-088_MTX
Adder
68.864
957141AF2-008_MTX
Adder
34.432
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.266
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.72
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.465
MECLTFEXP_MEC->PJM
CLTF
7.143
SIGELTFEXP_SIGE->PJM
CLTF
0.33
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.948
LAGNLTFEXP_LAGN->PJM
CLTF
5.68
TVALTFEXP_TVA->PJM
CLTF
2.676
NYPJM->LTFIMP_NY
CLTF
1.589
LGEELTFEXP_LGEE->PJM
CLTF
5.305
WECLTFEXP_WEC->PJM
CLTF
1.663
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.615
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:145.41 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2239.27
MW Contribution:4.84
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.431
24803306KYGER 4LP
50/50
2.38
971191AH1-055 GEN
Solar/Wind Harmer
68.697
25194608D.CRK4
Adder
1.69
25196608WSDLE5
Adder
8.803
252510AF1-249 C
Solar/Wind Harmer
0.055
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.09
25196008MFTGT1
Adder
1.326
958171AF2-111 GEN
Solar/Wind Harmer
17.035
972167AH1-666 GEN
Solar/Wind Harmer
5.13
253406AD2-031_GEN
Solar/Wind Harmer
0.461
972173AH1-669 GEN
Solar/Wind Harmer
3.047
270222AC2-111 GEN
Solar/Wind Harmer
2.955
270273AD2-016 GEN
Solar/Wind Harmer
0.603
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
970191AG2-125 GEN
Solar/Wind Harmer
1.388
3429391JKCT 9G
Adder
6.399
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.888
958821AF2-173 GEN
Solar/Wind Harmer
6.704
270004AE1-209 GEN
Solar/Wind Harmer
1.038
24728705AND G3
Adder
5.489
24728505AND G1
Adder
2.624
966571AG1-526 GEN
Solar/Wind Harmer
10.492
946031AF1-268 GEN
Solar/Wind Harmer
4.488
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.776
970289AG2-191 GEN
Solar/Wind Harmer
0.481
970291AG2-192 GEN
Solar/Wind Harmer
0.437
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.507
944531AF1-118 GEN
Solar/Wind Harmer
18.471
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.006
970193AG2-126 GEN
Solar/Wind Harmer
6.091
970243AG2-164 GEN
Solar/Wind Harmer
2.375
970519AG2-331 GEN
Solar/Wind Harmer
10.553
970699AG2-449 GEN
Solar/Wind Harmer
1.015
960741AF2-365 GEN
Solar/Wind Harmer
1.902
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
3.773
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.693
276668AB2-070 GEN1
Solar/Wind Harmer
0.134
276621W2-048 GEN
Solar/Wind Harmer
0.185
276838X2-022 GEN2
Solar/Wind Harmer
0.206
942481AE2-261 GEN
Solar/Wind Harmer
10.947
964401AG1-302 GEN
Solar/Wind Harmer
0.001
970513AG2-328 GEN
Solar/Wind Harmer
1.581
970517AG2-330 GEN
Solar/Wind Harmer
9.486
972273AH1-721 GEN
Adder
43.396
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.888
959611AF2-252 GEN
Solar/Wind Harmer
1.21
942111AE2-223 GEN
Solar/Wind Harmer
1.177
270535AF1-215 GEN1
Solar/Wind Harmer
0.005
970273AG2-179 GEN
Solar/Wind Harmer
2.134
276897AD1-100 C
Solar/Wind Harmer
0.005
939351AE1-166 GEN
Solar/Wind Harmer
0
274772LINCOLN ;3U
Adder
4.276
972228AH1-698 GEN2
Adder
1.875
276806AD2-047 C O1
Solar/Wind Harmer
2
970941AG2-585 GEN
Solar/Wind Harmer
4.411
274729ELWOOD EC;1P
Adder
8.308
276893AG1-478 C
Solar/Wind Harmer
0.14
274730ELWOOD EC;6P
Adder
8.308
274734ELWOOD EC;8P
Adder
8.308
274736ELWOOD EC;9P
Adder
8.308
970707AG2-453 GEN
Solar/Wind Harmer
11.517
274800UNIV PARK;3U
Adder
2.945
972038AH1-567 GEN2
Adder
0.184
276694AA1-018 GEN2
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
970571AG2-364 GEN
Solar/Wind Harmer
7.047
274802UNIV PARK;5U
Adder
2.944
270043AE2-236 GEN
Solar/Wind Harmer
2.261
274826FISK ;BP
Adder
5.526
274676JOLIET 29;8U
Adder
14.929
962251AG1-071 GEN
Solar/Wind Harmer
2.197
274878BISHOP HL;2U
Solar/Wind Harmer
0.118
943121AE2-341 GEN
Solar/Wind Harmer
5.891
943591AF1-030 GEN
Solar/Wind Harmer
3.917
339250AF1-203 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.128
971155AH1-034 GEN
Solar/Wind Harmer
4.077
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.373
274855GSG-6 ;RU
Solar/Wind Harmer
0.128
274850MENDOTA H;RU
Solar/Wind Harmer
0.041
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.063
959091AF2-200 GEN
Solar/Wind Harmer
6.979
235780M24_1
Solar/Wind Helper
0.99
970349AG2-230 GEN
Solar/Wind Harmer
0.971
24803406KYGER 5HP
50/50
4.083
24803206KYGER 4HP
50/50
4.08
252507AC2-088 GEN
Solar/Wind Harmer
0.36
25196808ZIMRHP
Adder
79.423
25194608D.CRK4
Adder
1.69
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.992
25196008MFTGT1
Adder
1.369
945681AF1-233 GEN
Solar/Wind Harmer
12.039
339216AC1-074 GEN
Solar/Wind Harmer
0.167
270263AC1-001 GEN
Solar/Wind Harmer
0.584
253370AE2-315 SEC1
Adder
1.603
253371AE2-315 SEC2
Adder
1.517
25326309TAIT D
Adder
0.846
3429421JKCT 10G
Adder
6.399
960071AF2-298 GEN
Solar/Wind Harmer
2.664
970773AG2-487 GEN
Solar/Wind Harmer
0.938
3429241JKCT 3G
Adder
8.84
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.753
270005AE1-210 C O1
Solar/Wind Harmer
1.038
965031AG1-367 GEN
Solar/Wind Harmer
4.789
24728605AND G2
Adder
2.624
970825AG2-519 GEN
Solar/Wind Harmer
1.675
971565AH1-281 GEN
Solar/Wind Harmer
0.942
247536S-71 GEN
Solar/Wind Harmer
0.189
945371AF1-202 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
5.056
971821AH1-427 GEN
Solar/Wind Harmer
4.468
270032AE2-172
Solar/Wind Harmer
2.977
958861AF2-177 GEN
Solar/Wind Harmer
1.915
970291AG2-192 GEN
Solar/Wind Harmer
0.569
965651AG1-433 GEN
Solar/Wind Harmer
1.28
970091AG2-072 GEN
Adder
45.505
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.006
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
2.902
963741AG1-226 GEN
Solar/Wind Harmer
9.27
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.626
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.429
276615X2-022 GEN
Solar/Wind Harmer
0.038
965911AG1-460 GEN
Solar/Wind Harmer
0.732
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
4.754
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.476
972175AH1-670 GEN
Solar/Wind Harmer
3.016
970245AG2-165 GEN
Solar/Wind Harmer
1.581
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
5.072
270055AF2-134 C O1
Solar/Wind Harmer
0.003
970373AG2-245 GEN
Solar/Wind Harmer
7.519
939401AE1-172 GEN
Solar/Wind Harmer
2.671
970273AG2-179 GEN
Solar/Wind Harmer
1.245
941551AE2-152 GEN
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
4.276
274774LINCOLN ;5U
Adder
4.276
276901AD2-066 C O1
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
1.852
274871GR RIDGE ;2U
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.368
274732ELWOOD EC;7P
Adder
8.308
274674JOLIET 9 ;6U
Adder
7.776
274801UNIV PARK;4U
Adder
2.945
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276691AA1-018 GEN1
Solar/Wind Harmer
0.427
970569AG2-363 GEN
Solar/Wind Harmer
10.571
276164X3-005 C
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
15.482
962241AG1-070 GEN
Solar/Wind Harmer
1.916
274877BISHOP HL;1U
Solar/Wind Harmer
0.118
962781AG1-127 GEN
Solar/Wind Harmer
3.331
274872LEEDK;1U
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.063
957471AF2-041 GEN
Solar/Wind Harmer
10.469
959081AF2-199 GEN
Solar/Wind Harmer
3.49
971067AG2-660 GEN
Solar/Wind Harmer
1.163
960001AF2-291 GEN
Solar/Wind Helper
1.722
270331AC1-082 GEN3
Solar/Wind Helper
0.205
24803006KYGER 3HP
50/50
4.129
24802806KYGER 2HP
50/50
4.105
24802906KYGER 2LP
50/50
2.413
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.438
252516AE2-318_GEN
Solar/Wind Harmer
5.71
25194408D.CRK1
Adder
7.772
25194508D.CRK3
Adder
1.453
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
970235AG2-159 GEN
Solar/Wind Harmer
3.745
970235AG2-159 GEN
Solar/Wind Harmer
2.149
962581AG1-107 GEN
Solar/Wind Harmer
0.001
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.516
972045AH1-571 GEN
Solar/Wind Harmer
1.215
971125AH1-004 GEN
Solar/Wind Harmer
2.272
970107AG2-081 GEN
Solar/Wind Harmer
1.704
253370AE2-315 SEC1
Adder
1.603
24728805RICHG1
Adder
2.949
24728905RICHG2
Adder
2.949
25322209TAIT E
Adder
7.54
25322209TAIT E
Adder
7.371
25326109MON D
Adder
0.986
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
942891AE2-308 GEN
Solar/Wind Harmer
5.114
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.843
970885AG2-551 GEN
Solar/Wind Harmer
1.614
960161AF2-307 GEN
Solar/Wind Harmer
3.166
970825AG2-519 GEN
Solar/Wind Harmer
5.23
960441AF2-335 GEN
Solar/Wind Harmer
4.696
247621Y3-024
Adder
0.159
964611AG1-324 GEN
Solar/Wind Harmer
0.342
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270599AE1-208 GEN
Solar/Wind Harmer
4.125
270031AE2-169
Solar/Wind Harmer
2.475
964571AG1-320 GEN
Solar/Wind Harmer
4.08
971613AH1-306 GEN
Solar/Wind Harmer
2.143
944541AF1-119 GEN
Solar/Wind Harmer
0.292
960971AF2-388 GEN
Solar/Wind Harmer
2.559
970653AG2-424 GEN
Solar/Wind Harmer
2.067
970653AG2-424 GEN
Solar/Wind Harmer
1.071
942221AE2-234 GEN
Solar/Wind Harmer
0.02
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.992
945391AF1-204 GEN
Solar/Wind Harmer
4.315
970239AG2-162 GEN
Solar/Wind Harmer
1.015
970241AG2-163 GEN
Solar/Wind Harmer
2.285
971081AG2-670 GEN
Solar/Wind Harmer
2.933
966841AG1-555 GEN
Solar/Wind Harmer
0.433
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.321
25326509SID D
Adder
0.697
276916AD2-100_GEN
Solar/Wind Harmer
7.697
276911AD2-131_GEN
Solar/Wind Harmer
0.507
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
970321AG2-212 GEN
Solar/Wind Harmer
1.581
960611AF2-352 GEN
Solar/Wind Harmer
1.21
274770LINCOLN ;1U
Adder
4.276
274771LINCOLN ;2U
Adder
4.276
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.207
274887GEN-1.85
Solar/Wind Harmer
0.093
276843GEN-1.7
Solar/Wind Harmer
0.114
958011AF2-095 GEN
Solar/Wind Harmer
5.082
972259AH1-714 GEN
Adder
9.649
274674JOLIET 9 ;6U
Adder
7.776
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
958481AF2-142 GEN
Solar/Wind Harmer
5.285
958491AF2-143 GEN
Solar/Wind Harmer
5.285
274803UNIV PARK;6U
Adder
2.944
274879MINONK ;1U
Solar/Wind Harmer
0.149
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.477
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.139
276646AC1-214 GEN2
Solar/Wind Harmer
0.139
276782AC1-033 GEN
Solar/Wind Harmer
0.001
971573AH1-285 GEN
Solar/Wind Harmer
0.654
339255AE2-071 GEN
Solar/Wind Harmer
-0.058
962691AG1-118 GEN
Solar/Wind Harmer
10.504
970921AG2-575 GEN
Solar/Wind Harmer
3.5
970921AG2-575 GEN
Solar/Wind Harmer
1.167
964781AG1-341 GEN
Solar/Wind Harmer
3.707
942991AE2-321 GEN
Solar/Wind Harmer
3.901
971333AH1-146 GEN
Solar/Wind Harmer
6.981
971335AH1-147 GEN
Solar/Wind Harmer
6.981
971341AH1-150 GEN
Solar/Wind Harmer
6.979
971343AH1-151 GEN
Solar/Wind Harmer
6.979
237033AB1-150 GEN
Solar/Wind Helper
0.4
24802606KYGER 1HP
50/50
4.153
24802706KYGER 1LP
50/50
2.437
24803506KYGER 5LP
50/50
2.38
25016408BKJDB1
50/50
0.276
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.764
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.062
25196308WSDLE2
Adder
8.983
25196208WSDLE1
Adder
8.961
25196708WSDLE6
Adder
8.938
25196508WSDLE4
Adder
8.713
25196108MFTGT2
Adder
1.509
25196108MFTGT2
Adder
1.402
972163AH1-664 GEN
Solar/Wind Harmer
7.031
972165AH1-665 GEN
Solar/Wind Harmer
5.631
270367AC2-061_GEN
Solar/Wind Harmer
0.005
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270269AC2-059
Solar/Wind Harmer
0.003
253372AE2-315 SEC3
Adder
1.517
253372AE2-315 SEC3
Adder
1.517
25306009OHH W.
Adder
2.274
253349AC2-067 GEN
Solar/Wind Harmer
1.699
253400AC2-068 GEN
Solar/Wind Harmer
0.683
3429211JKCT 2G
Adder
8.726
270240V3-007_GEN2
Solar/Wind Harmer
0.002
970689AG2-444 GEN
Solar/Wind Harmer
10.333
971673AH1-337 GEN
Solar/Wind Harmer
3.282
971029AG2-637 GEN
Solar/Wind Harmer
7.495
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.879
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
970455AG2-298 GEN
Solar/Wind Harmer
3.046
339211AE2-254 GEN
Solar/Wind Harmer
0.002
945581AF1-223 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
2.004
971609AH1-304 GEN
Solar/Wind Harmer
0.735
270594AE1-207 GEN
Solar/Wind Harmer
5.001
241972AD1-140 GEN
Solar/Wind Harmer
0.486
965101AG1-375 GEN
Solar/Wind Harmer
4.42
970289AG2-191 GEN
Solar/Wind Harmer
0.831
270024AE2-089 GEN
Solar/Wind Harmer
0.005
24729505KEY G4
Adder
3.892
965401AG1-405 GEN
Solar/Wind Harmer
2.225
965411AG1-406 GEN
Solar/Wind Harmer
1.432
963841AG1-237 GEN
Solar/Wind Harmer
1.679
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
5.01
270071AF1-092 GEN
Solar/Wind Harmer
7.101
971611AH1-305 GEN
Solar/Wind Harmer
2.203
944221AF1-090 GEN
Solar/Wind Harmer
2.159
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.134
276848AB2-070 GEN3
Solar/Wind Harmer
0.133
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.804
941731AE2-173 GEN
Solar/Wind Harmer
3.019
270536AF1-215 GEN2
Solar/Wind Harmer
0.005
970169AG2-114 GEN
Solar/Wind Harmer
3.59
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274775LINCOLN ;6U
Adder
4.276
274776LINCOLN ;7U
Adder
4.276
274777LINCOLN ;8U
Adder
4.276
926823AC1-168 GEN
Solar/Wind Harmer
0.6
972227AH1-698 GEN1
Adder
1.32
970833AG2-524 GEN
Solar/Wind Harmer
3.883
970833AG2-524 GEN
Solar/Wind Harmer
2.589
960591AF2-350 GEN
Solar/Wind Harmer
3.529
274731ELWOOD EC;2P
Adder
8.308
274733ELWOOD EC;3P
Adder
8.308
274735ELWOOD EC;4P
Adder
8.308
274728ELWOOD EC;5P
Adder
8.308
972037AH1-567 GEN1
Adder
0.092
276868AE1-113 GEN
Solar/Wind Harmer
0.707
276882AE2-255 GEN
Solar/Wind Harmer
0.412
957751AF2-069 GEN
Solar/Wind Harmer
0.116
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
274827FISK ;RP
Adder
3.916
274675JOLIET 29;7U
Adder
15.482
274675JOLIET 29;7U
Adder
14.929
274687WILL CNTY;4U
Adder
14.101
274687WILL CNTY;4U
Adder
7.883
971675AH1-338 GEN
Solar/Wind Harmer
1.363
971177AH1-047 GEN
Solar/Wind Harmer
2.154
971411AH1-196 GEN
Solar/Wind Harmer
5.236
971171AH1-044 GEN
Solar/Wind Harmer
6.979
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270330AC1-082 GEN2
Solar/Wind Helper
0.043
270329AC1-082 GEN1
Solar/Wind Helper
0.206
971347AH1-153 GEN
Solar/Wind Harmer
0.971
944201AF1-088_MTX
Adder
67.999
957141AF2-008_MTX
Adder
33.999
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.042
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.325
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.636
MECLTFEXP_MEC->PJM
CLTF
8.008
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
58.397
LAGNLTFEXP_LAGN->PJM
CLTF
6.556
TVALTFEXP_TVA->PJM
CLTF
3.109
NYPJM->LTFIMP_NY
CLTF
1.661
LGEELTFEXP_LGEE->PJM
CLTF
5.141
WECLTFEXP_WEC->PJM
CLTF
1.904
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.285
AG2-052LTFEXP_AG2-052->PJM
LTF
0.122
AH1-155LTFEXP_AH1-155->PJM
LTF
0.183

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P1-2_#309_15_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#309_15_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:141.78 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2183.34
MW Contribution:4.77
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.205
24802706KYGER 1LP
50/50
2.468
24803506KYGER 5LP
50/50
2.41
25016408BKJDB1
50/50
0.29
25183008BIOENL
50/50
0.032
971985AH1-537 GEN
Solar/Wind Harmer
5.902
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
9.532
25196308WSDLE2
Adder
9.449
25196208WSDLE1
Adder
9.426
25196708WSDLE6
Adder
9.402
25196508WSDLE4
Adder
9.165
25196108MFTGT2
Adder
1.577
25196108MFTGT2
Adder
1.464
972163AH1-664 GEN
Solar/Wind Harmer
7.374
972165AH1-665 GEN
Solar/Wind Harmer
5.906
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.004
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.625
253372AE2-315 SEC3
Adder
1.625
25306009OHH W.
Adder
2.427
970689AG2-444 GEN
Solar/Wind Harmer
11.775
253349AC2-067 GEN
Solar/Wind Harmer
1.803
253400AC2-068 GEN
Solar/Wind Harmer
0.725
3429211JKCT 2G
Adder
8.965
270432AC2-029 GEN
Solar/Wind Harmer
2.302
971673AH1-337 GEN
Solar/Wind Harmer
3.274
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
7.455
241972AD1-140 GEN
Solar/Wind Harmer
0.537
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
3.084
339211AE2-254 GEN
Solar/Wind Harmer
0.002
970115AG2-085 GEN
Solar/Wind Harmer
1.802
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.766
971609AH1-304 GEN
Solar/Wind Harmer
0.693
945581AF1-223 GEN
Solar/Wind Harmer
0
970289AG2-191 GEN
Solar/Wind Harmer
0.789
965101AG1-375 GEN
Solar/Wind Harmer
4.056
270024AE2-089 GEN
Solar/Wind Harmer
0.004
965401AG1-405 GEN
Solar/Wind Harmer
2.199
965411AG1-406 GEN
Solar/Wind Harmer
1.415
270156DARBY CT1
Adder
4.836
270157DARBY CT2
Adder
4.825
270158DARBY CT3
Adder
4.747
24729505KEY G4
Adder
3.463
972203AH1-686 GEN
Adder
1.225
963841AG1-237 GEN
Solar/Wind Harmer
1.584
945631AF1-228 GEN
Solar/Wind Harmer
0
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.022
971611AH1-305 GEN
Solar/Wind Harmer
2.007
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.123
276848AB2-070 GEN3
Solar/Wind Harmer
0.122
963791AG1-232 GEN
Solar/Wind Harmer
4.535
958391AF2-133 GEN
Solar/Wind Harmer
0
943861AF1-054 GEN
Solar/Wind Harmer
1.276
943851AF1-053 GEN
Solar/Wind Harmer
0.884
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.422
941731AE2-173 GEN
Solar/Wind Harmer
2.716
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
270071AF1-092 GEN
Solar/Wind Harmer
6.133
970169AG2-114 GEN
Solar/Wind Harmer
3.189
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.103
926823AC1-168 GEN
Solar/Wind Harmer
0.529
276868AE1-113 GEN
Solar/Wind Harmer
0.619
276882AE2-255 GEN
Solar/Wind Harmer
0.361
970833AG2-524 GEN
Solar/Wind Harmer
3.372
970833AG2-524 GEN
Solar/Wind Harmer
2.248
274731ELWOOD EC;2P
Adder
7.212
274733ELWOOD EC;3P
Adder
7.212
274735ELWOOD EC;4P
Adder
7.212
274728ELWOOD EC;5P
Adder
7.212
972227AH1-698 GEN1
Adder
1.144
960591AF2-350 GEN
Solar/Wind Harmer
3.057
961011AF2-392 GEN
Solar/Wind Harmer
1.791
274675JOLIET 29;7U
Adder
13.422
274675JOLIET 29;7U
Adder
12.942
274687WILL CNTY;4U
Adder
12.222
274687WILL CNTY;4U
Adder
12.222
971681AH1-341 GEN
Solar/Wind Harmer
4.912
274746AC1-111 G10
Adder
2.444
274744AC1-111 GEN8
Adder
2.444
971171AH1-044 GEN
Solar/Wind Harmer
6.1
971675AH1-338 GEN
Solar/Wind Harmer
1.189
972037AH1-567 GEN1
Adder
0.08
946321AF1-296 GEN
Solar/Wind Harmer
1.708
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803106KYGER 3LP
50/50
2.461
24803306KYGER 4LP
50/50
2.41
971191AH1-055 GEN
Solar/Wind Harmer
70.447
25194608D.CRK4
Adder
1.777
25196608WSDLE5
Adder
9.26
252510AF1-249 C
Solar/Wind Harmer
0.058
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.726
958171AF2-111 GEN
Solar/Wind Harmer
17.961
25196008MFTGT1
Adder
1.385
972173AH1-669 GEN
Solar/Wind Harmer
3.407
972167AH1-666 GEN
Solar/Wind Harmer
5.387
253406AD2-031_GEN
Solar/Wind Harmer
0.496
270273AD2-016 GEN
Solar/Wind Harmer
0.676
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270222AC2-111 GEN
Solar/Wind Harmer
3.033
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
970191AG2-125 GEN
Solar/Wind Harmer
1.473
3429391JKCT 9G
Adder
6.595
270356AE2-297 GEN
Solar/Wind Harmer
0.007
270437AC2-090 C
Solar/Wind Harmer
0.002
970093AG2-073 GEN
Solar/Wind Harmer
4.986
966571AG1-526 GEN
Solar/Wind Harmer
10.654
24728705AND G3
Adder
5.404
24728505AND G1
Adder
2.584
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
958821AF2-173 GEN
Solar/Wind Harmer
6.409
270004AE1-209 GEN
Solar/Wind Harmer
0.992
946031AF1-268 GEN
Solar/Wind Harmer
4.321
970243AG2-164 GEN
Solar/Wind Harmer
2.557
970519AG2-331 GEN
Solar/Wind Harmer
11.364
970699AG2-449 GEN
Solar/Wind Harmer
1.093
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.542
970289AG2-191 GEN
Solar/Wind Harmer
0.457
970291AG2-192 GEN
Solar/Wind Harmer
0.416
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
3.313
970193AG2-126 GEN
Solar/Wind Harmer
5.898
960741AF2-365 GEN
Solar/Wind Harmer
1.874
944531AF1-118 GEN
Solar/Wind Harmer
16.287
970605AG2-385 GEN
Solar/Wind Harmer
2.184
972273AH1-721 GEN
Adder
42.389
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.498
970273AG2-179 GEN
Solar/Wind Harmer
2.077
962251AG1-071 GEN
Solar/Wind Harmer
2.135
339250AF1-203 GEN
Solar/Wind Harmer
0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.156
971155AH1-034 GEN
Solar/Wind Harmer
3.958
276621W2-048 GEN
Solar/Wind Harmer
0.17
276838X2-022 GEN2
Solar/Wind Harmer
0.19
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.555
276668AB2-070 GEN1
Solar/Wind Harmer
0.123
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
964401AG1-302 GEN
Solar/Wind Harmer
0
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
9.838
959611AF2-252 GEN
Solar/Wind Harmer
1.093
942111AE2-223 GEN
Solar/Wind Harmer
1.059
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
970513AG2-328 GEN
Solar/Wind Harmer
1.366
970517AG2-330 GEN
Solar/Wind Harmer
8.195
274878BISHOP HL;2U
Solar/Wind Harmer
0.105
970571AG2-364 GEN
Solar/Wind Harmer
6.209
942051AE2-217 GEN
Solar/Wind Harmer
5.584
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
276694AA1-018 GEN2
Solar/Wind Harmer
0
276157O29GEN1
Solar/Wind Harmer
0.496
276893AG1-478 C
Solar/Wind Harmer
0.121
274729ELWOOD EC;1P
Adder
7.212
274730ELWOOD EC;6P
Adder
7.212
274734ELWOOD EC;8P
Adder
7.212
274736ELWOOD EC;9P
Adder
7.212
972228AH1-698 GEN2
Adder
1.624
276806AD2-047 C O1
Solar/Wind Harmer
1.732
970941AG2-585 GEN
Solar/Wind Harmer
3.821
274676JOLIET 29;8U
Adder
12.942
274800UNIV PARK;3U
Adder
2.55
972038AH1-567 GEN2
Adder
0.16
274855GSG-6 ;RU
Solar/Wind Harmer
0.112
274850MENDOTA H;RU
Solar/Wind Harmer
0.036
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.055
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.325
959091AF2-200 GEN
Solar/Wind Harmer
6.1
274802UNIV PARK;5U
Adder
2.549
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.774
274872LEEDK;1U
Solar/Wind Harmer
0.112
235780M24_1
Solar/Wind Helper
0.999
24803406KYGER 5HP
50/50
4.134
24803206KYGER 4HP
50/50
4.13
252507AC2-088 GEN
Solar/Wind Harmer
0.38
25196808ZIMRHP
Adder
83.68
25194608D.CRK4
Adder
1.777
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
7.481
25196008MFTGT1
Adder
1.431
945681AF1-233 GEN
Solar/Wind Harmer
12.638
270263AC1-001 GEN
Solar/Wind Harmer
0.653
339216AC1-074 GEN
Solar/Wind Harmer
0.174
253370AE2-315 SEC1
Adder
1.718
253371AE2-315 SEC2
Adder
1.625
25326309TAIT D
Adder
0.908
960071AF2-298 GEN
Solar/Wind Harmer
2.849
3429421JKCT 10G
Adder
6.595
3429241JKCT 3G
Adder
9.082
970773AG2-487 GEN
Solar/Wind Harmer
0.935
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.657
971565AH1-281 GEN
Solar/Wind Harmer
0.959
24728605AND G2
Adder
2.584
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
247536S-71 GEN
Solar/Wind Harmer
0.185
270005AE1-210 C O1
Solar/Wind Harmer
0.992
965031AG1-367 GEN
Solar/Wind Harmer
4.578
970825AG2-519 GEN
Solar/Wind Harmer
1.608
971821AH1-427 GEN
Solar/Wind Harmer
4.505
970091AG2-072 GEN
Adder
49.379
970333AG2-219 GEN
Solar/Wind Harmer
3.125
276903AD2-071 C
Solar/Wind Harmer
4.849
270032AE2-172
Solar/Wind Harmer
2.837
945371AF1-202 GEN
Solar/Wind Harmer
0
970291AG2-192 GEN
Solar/Wind Harmer
0.54
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
958861AF2-177 GEN
Solar/Wind Harmer
1.758
965651AG1-433 GEN
Solar/Wind Harmer
1.166
270159DARBY CT4
Adder
4.759
963741AG1-226 GEN
Solar/Wind Harmer
8.802
970593AG2-378 GEN
Solar/Wind Harmer
0.808
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
964901AG1-354 GEN
Solar/Wind Harmer
5.358
24791305MDL-5G
Solar/Wind Harmer
0
970273AG2-179 GEN
Solar/Wind Harmer
1.212
962241AG1-070 GEN
Solar/Wind Harmer
1.862
965911AG1-460 GEN
Solar/Wind Harmer
0.679
276615X2-022 GEN
Solar/Wind Harmer
0.035
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.214
24803006KYGER 3HP
50/50
4.181
24802806KYGER 2HP
50/50
4.156
24802906KYGER 2LP
50/50
2.443
252509AD1-136 GEN
Solar/Wind Harmer
0.042
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.799
252516AE2-318_GEN
Solar/Wind Harmer
6.03
25194408D.CRK1
Adder
8.173
25194508D.CRK3
Adder
1.528
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
253394AE2-221_GEN
Solar/Wind Harmer
0.009
253398AE2-221_GEN2
Solar/Wind Harmer
0.009
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.893
970235AG2-159 GEN
Solar/Wind Harmer
2.234
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.576
972045AH1-571 GEN
Solar/Wind Harmer
1.263
253370AE2-315 SEC1
Adder
1.718
971125AH1-004 GEN
Solar/Wind Harmer
2.354
970107AG2-081 GEN
Solar/Wind Harmer
1.765
25322209TAIT E
Adder
8.088
25322209TAIT E
Adder
7.906
963831AG1-236 GEN
Solar/Wind Harmer
1.313
274880W4-005 GEN4
Solar/Wind Harmer
0
972175AH1-670 GEN
Solar/Wind Harmer
2.749
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.279
958381AF2-132 GEN
Solar/Wind Harmer
0
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.562
270055AF2-134 C O1
Solar/Wind Harmer
0.002
970373AG2-245 GEN
Solar/Wind Harmer
6.619
970245AG2-165 GEN
Solar/Wind Harmer
1.366
939401AE1-172 GEN
Solar/Wind Harmer
2.35
274877BISHOP HL;1U
Solar/Wind Harmer
0.105
970569AG2-363 GEN
Solar/Wind Harmer
9.313
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
971997AH1-543 GEN
Solar/Wind Harmer
1.624
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.372
276158O29GEN2
Solar/Wind Harmer
0
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.212
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274674JOLIET 9 ;6U
Adder
6.747
274676JOLIET 29;8U
Adder
13.422
274801UNIV PARK;4U
Adder
2.55
274745AC1-111 GEN9
Adder
2.444
276861AD2-134 GEN
Solar/Wind Harmer
0.055
957471AF2-041 GEN
Solar/Wind Harmer
9.15
959081AF2-199 GEN
Solar/Wind Harmer
3.05
971067AG2-660 GEN
Solar/Wind Harmer
1.017
274872LEEDK;1U
Solar/Wind Harmer
0.002
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
962781AG1-127 GEN
Solar/Wind Harmer
2.901
960001AF2-291 GEN
Solar/Wind Helper
1.676
270331AC1-082 GEN3
Solar/Wind Helper
0.198
25326109MON D
Adder
1.064
24728805RICHG1
Adder
2.986
24728905RICHG2
Adder
2.986
942891AE2-308 GEN
Solar/Wind Harmer
5.244
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
960161AF2-307 GEN
Solar/Wind Harmer
3.231
970883AG2-550 GEN
Solar/Wind Harmer
4.773
970885AG2-551 GEN
Solar/Wind Harmer
1.591
970825AG2-519 GEN
Solar/Wind Harmer
5.021
964571AG1-320 GEN
Solar/Wind Harmer
4.118
960441AF2-335 GEN
Solar/Wind Harmer
4.504
247621Y3-024
Adder
0.155
964611AG1-324 GEN
Solar/Wind Harmer
0.33
970239AG2-162 GEN
Solar/Wind Harmer
1.093
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970653AG2-424 GEN
Solar/Wind Harmer
2.075
970653AG2-424 GEN
Solar/Wind Harmer
1.075
971613AH1-306 GEN
Solar/Wind Harmer
2.042
270518AE2-148 GEN
Solar/Wind Harmer
0.367
270599AE1-208 GEN
Solar/Wind Harmer
3.89
270031AE2-169
Solar/Wind Harmer
2.334
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.032
25326509SID D
Adder
0.76
944541AF1-119 GEN
Solar/Wind Harmer
0.266
960971AF2-388 GEN
Solar/Wind Harmer
2.332
945391AF1-204 GEN
Solar/Wind Harmer
4.178
971081AG2-670 GEN
Solar/Wind Harmer
2.902
942221AE2-234 GEN
Solar/Wind Harmer
0.019
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.613
970241AG2-163 GEN
Solar/Wind Harmer
2.169
970077AG2-063 GEN
Solar/Wind Harmer
2.064
966841AG1-555 GEN
Solar/Wind Harmer
0.406
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
276916AD2-100_GEN
Solar/Wind Harmer
7.156
276911AD2-131_GEN
Solar/Wind Harmer
0.471
339255AE2-071 GEN
Solar/Wind Harmer
-0.056
964781AG1-341 GEN
Solar/Wind Harmer
3.601
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
942861AE2-305 GEN
Solar/Wind Harmer
2.586
960611AF2-352 GEN
Solar/Wind Harmer
1.093
970321AG2-212 GEN
Solar/Wind Harmer
1.366
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.123
276646AC1-214 GEN2
Solar/Wind Harmer
0.123
971485AH1-239 GEN
Solar/Wind Harmer
2.495
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.13
958491AF2-143 GEN
Solar/Wind Harmer
4.624
966021AG1-471 GEN
Solar/Wind Harmer
1.664
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.416
958481AF2-142 GEN
Solar/Wind Harmer
4.61
276741O09 GEN1
Solar/Wind Harmer
0.109
276708O09 GEN2
Solar/Wind Harmer
0.109
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274887GEN-1.85
Solar/Wind Harmer
0.08
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.402
274674JOLIET 9 ;6U
Adder
6.747
972259AH1-714 GEN
Adder
8.351
276603SUBLETTE C
Solar/Wind Harmer
0
972267AH1-718 GEN
Adder
1.821
971341AH1-150 GEN
Solar/Wind Harmer
6.1
971343AH1-151 GEN
Solar/Wind Harmer
6.1
274803UNIV PARK;6U
Adder
2.549
938861AE1-114 GEN
Solar/Wind Harmer
1.728
962691AG1-118 GEN
Solar/Wind Harmer
9.146
274764LEE CO EC;5U
Adder
4.075
274765LEE CO EC;6U
Adder
2.574
970921AG2-575 GEN
Solar/Wind Harmer
3.048
970921AG2-575 GEN
Solar/Wind Harmer
1.016
971573AH1-285 GEN
Solar/Wind Harmer
0.568
237033AB1-150 GEN
Solar/Wind Helper
0.403
971333AH1-146 GEN
Solar/Wind Harmer
3.002
971335AH1-147 GEN
Solar/Wind Harmer
3.002
944201AF1-088_MTX
Adder
68.911
957141AF2-008_MTX
Adder
34.455
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.271
CBM West 1LTFEXP_CBM-W1->PJM
CBM
65.759
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.454
MECLTFEXP_MEC->PJM
CLTF
7.145
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.937
LAGNLTFEXP_LAGN->PJM
CLTF
5.672
TVALTFEXP_TVA->PJM
CLTF
2.671
NYPJM->LTFIMP_NY
CLTF
1.591
LGEELTFEXP_LGEE->PJM
CLTF
5.309
WECLTFEXP_WEC->PJM
CLTF
1.664
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.623
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109
AH1-155LTFEXP_AH1-155->PJM
LTF
0.163

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AEP_P2-2_#6763_05BIERSR 345_2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#6763_05BIERSR 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:135.59 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2088.16
MW Contribution:6.26
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.234
24802706KYGER 1LP
50/50
2.485
24803506KYGER 5LP
50/50
2.427
25016408BKJDB1
50/50
0.281
25183008BIOENL
50/50
0.031
971985AH1-537 GEN
Solar/Wind Harmer
50.621
270269AC2-059
Solar/Wind Harmer
11.349
252524AE2-267 GEN
Solar/Wind Harmer
1.629
25196408WSDLE3
Adder
9.115
25196308WSDLE2
Adder
9.036
25196208WSDLE1
Adder
9.013
25196708WSDLE6
Adder
8.99
25196508WSDLE4
Adder
8.764
270340AC2-060 GEN
Solar/Wind Harmer
3.131
25196108MFTGT2
Adder
1.507
25196108MFTGT2
Adder
1.4
270367AC2-061_GEN
Solar/Wind Harmer
3.017
972163AH1-664 GEN
Solar/Wind Harmer
9.331
972165AH1-665 GEN
Solar/Wind Harmer
7.465
339243AC2-075 GEN1
Solar/Wind Harmer
0.404
270432AC2-029 GEN
Solar/Wind Harmer
6.133
944031AF1-071 GEN
Solar/Wind Harmer
0.808
253372AE2-315 SEC3
Adder
1.505
253372AE2-315 SEC3
Adder
1.505
25306009OHH W.
Adder
2.25
3429211JKCT 2G
Adder
8.876
253349AC2-067 GEN
Solar/Wind Harmer
3.779
253400AC2-068 GEN
Solar/Wind Harmer
1.52
971673AH1-337 GEN
Solar/Wind Harmer
3.058
270240V3-007_GEN2
Solar/Wind Harmer
4.082
339211AE2-254 GEN
Solar/Wind Harmer
0.993
971029AG2-637 GEN
Solar/Wind Harmer
9.823
970455AG2-298 GEN
Solar/Wind Harmer
3.88
270543AE2-219 C
Solar/Wind Harmer
3.206
241972AD1-140 GEN
Solar/Wind Harmer
2.785
970115AG2-085 GEN
Solar/Wind Harmer
2.353
24725505WLD G2 C
Solar/Wind Harmer
2.288
24699105WLD G1 C
Solar/Wind Harmer
2.261
961761AG1-017 GEN
Solar/Wind Harmer
0.242
965401AG1-405 GEN
Solar/Wind Harmer
3.224
965411AG1-406 GEN
Solar/Wind Harmer
1.447
270594AE1-207 GEN
Solar/Wind Harmer
8.066
945581AF1-223 GEN
Solar/Wind Harmer
2.476
965461AG1-414 GEN
Solar/Wind Harmer
1.209
970289AG2-191 GEN
Solar/Wind Harmer
1.013
965101AG1-375 GEN
Solar/Wind Harmer
5.23
958711AF2-162 GEN
Solar/Wind Harmer
0.517
270024AE2-089 GEN
Solar/Wind Harmer
2.39
24729505KEY G4
Adder
3.077
963841AG1-237 GEN
Solar/Wind Harmer
5.029
24386205FR-12G C
Solar/Wind Harmer
1.926
24386405FR-21G C
Solar/Wind Harmer
1.932
24386605FR-22G C
Solar/Wind Harmer
1.932
24387005FR-3G C
Solar/Wind Harmer
1.777
270330AC1-082 GEN2
Solar/Wind Helper
0.039
270329AC1-082 GEN1
Solar/Wind Helper
0.188
24803106KYGER 3LP
50/50
2.478
24803306KYGER 4LP
50/50
2.427
971191AH1-055 GEN
Solar/Wind Harmer
87.457
972173AH1-669 GEN
Solar/Wind Harmer
6.452
270273AD2-016 GEN
Solar/Wind Harmer
3.245
252510AF1-249 C
Solar/Wind Harmer
0.433
25194608D.CRK4
Adder
1.702
25196608WSDLE5
Adder
8.854
253316AC1-085 GEN3
Solar/Wind Harmer
8.59
253433AC1-085 GEN1
Solar/Wind Harmer
5.453
946181AF1-283 GEN
Solar/Wind Harmer
13.332
958171AF2-111 GEN
Solar/Wind Harmer
25.055
25196008MFTGT1
Adder
1.324
253415AE1-040 GEN
Solar/Wind Harmer
1.099
972167AH1-666 GEN
Solar/Wind Harmer
7.578
253406AD2-031_GEN
Solar/Wind Harmer
1.187
270222AC2-111 GEN
Solar/Wind Harmer
6.559
253303V4-073 C
Solar/Wind Harmer
0.092
253370AE2-315 SEC1
Adder
1.591
253371AE2-315 SEC2
Adder
1.505
3429391JKCT 9G
Adder
6.507
970093AG2-073 GEN
Solar/Wind Harmer
7.118
270356AE2-297 GEN
Solar/Wind Harmer
3.213
966571AG1-526 GEN
Solar/Wind Harmer
15.167
270437AC2-090 C
Solar/Wind Harmer
3.683
24728705AND G3
Adder
4.972
24728505AND G1
Adder
2.377
958821AF2-173 GEN
Solar/Wind Harmer
8.396
270004AE1-209 GEN
Solar/Wind Harmer
3.277
946031AF1-268 GEN
Solar/Wind Harmer
4.924
962031AG1-047 GEN
Solar/Wind Harmer
1.711
957741AF2-068 GEN
Solar/Wind Harmer
8.489
253338AC1-165 GEN
Solar/Wind Harmer
0.608
253333AC1-068 GEN
Solar/Wind Harmer
0.586
960741AF2-365 GEN
Solar/Wind Harmer
2.673
24803406KYGER 5HP
50/50
4.162
24803206KYGER 4HP
50/50
4.159
270263AC1-001 GEN
Solar/Wind Harmer
1.225
252507AC2-088 GEN
Solar/Wind Harmer
2.082
25196808ZIMRHP
Adder
80.646
25194608D.CRK4
Adder
1.702
253432AC1-085 GEN2
Solar/Wind Harmer
0.275
946171AF1-282 GEN
Solar/Wind Harmer
10.256
25196008MFTGT1
Adder
1.367
945681AF1-233 GEN
Solar/Wind Harmer
17.786
339216AC1-074 GEN
Solar/Wind Harmer
1.493
943111AE2-339 GEN
Solar/Wind Harmer
0.717
253370AE2-315 SEC1
Adder
1.591
253371AE2-315 SEC2
Adder
1.505
3429421JKCT 10G
Adder
6.507
25326309TAIT D
Adder
0.835
3429241JKCT 3G
Adder
8.993
960071AF2-298 GEN
Solar/Wind Harmer
3.766
971565AH1-281 GEN
Solar/Wind Harmer
1.333
942081AE2-220 GEN
Solar/Wind Harmer
4.218
270239V3-007_GEN1
Solar/Wind Harmer
1.135
971821AH1-427 GEN
Solar/Wind Harmer
6.444
24728605AND G2
Adder
2.377
270005AE1-210 C O1
Solar/Wind Harmer
3.277
965031AG1-367 GEN
Solar/Wind Harmer
5.997
247536S-71 GEN
Solar/Wind Harmer
2.426
970825AG2-519 GEN
Solar/Wind Harmer
1.394
339241AF1-083 GEN
Solar/Wind Harmer
0.937
276903AD2-071 C
Solar/Wind Harmer
5.625
253343AC1-166 GEN
Solar/Wind Harmer
0.608
253325AC1-069 GEN
Solar/Wind Harmer
0.586
970091AG2-072 GEN
Adder
42.53
270032AE2-172
Solar/Wind Harmer
2.553
945371AF1-202 GEN
Solar/Wind Harmer
3.81
970291AG2-192 GEN
Solar/Wind Harmer
0.693
970333AG2-219 GEN
Solar/Wind Harmer
16.705
270445AC2-157 GEN2
Solar/Wind Harmer
2.94
958861AF2-177 GEN
Solar/Wind Harmer
5.717
964901AG1-354 GEN
Solar/Wind Harmer
7.741
965651AG1-433 GEN
Solar/Wind Harmer
2.793
970273AG2-179 GEN
Solar/Wind Harmer
1.244
962241AG1-070 GEN
Solar/Wind Harmer
2.225
963741AG1-226 GEN
Solar/Wind Harmer
21.164
24385905FR-11G C
Solar/Wind Harmer
3.734
24387305FR-4G C
Solar/Wind Harmer
2.283
960001AF2-291 GEN
Solar/Wind Helper
1.622
270331AC1-082 GEN3
Solar/Wind Helper
0.187
24803006KYGER 3HP
50/50
4.209
24802806KYGER 2HP
50/50
4.185
24802906KYGER 2LP
50/50
2.46
252509AD1-136 GEN
Solar/Wind Harmer
0.297
25183208HLCRTG
Solar/Wind Harmer
6.65
252519AF1-045_GEN
Solar/Wind Harmer
6.541
252516AE2-318_GEN
Solar/Wind Harmer
4.99
25194408D.CRK1
Adder
7.828
25194508D.CRK3
Adder
1.464
253317AC1-085 GEN4
Solar/Wind Harmer
8.59
253394AE2-221_GEN
Solar/Wind Harmer
4.35
253398AE2-221_GEN2
Solar/Wind Harmer
4.35
270186AC1-089 GEN
Solar/Wind Harmer
5.71
962581AG1-107 GEN
Solar/Wind Harmer
4.635
961491AF2-440 GEN
Solar/Wind Harmer
1.926
970235AG2-159 GEN
Solar/Wind Harmer
3.527
970235AG2-159 GEN
Solar/Wind Harmer
2.153
339221AD2-048_GEN
Solar/Wind Harmer
1.344
972043AH1-570 GEN
Solar/Wind Harmer
2.133
972045AH1-571 GEN
Solar/Wind Harmer
1.707
971125AH1-004 GEN
Solar/Wind Harmer
3.309
970107AG2-081 GEN
Solar/Wind Harmer
2.482
253370AE2-315 SEC1
Adder
1.591
25322209TAIT E
Adder
7.443
25322209TAIT E
Adder
7.276
942891AE2-308 GEN
Solar/Wind Harmer
7.449
25326109MON D
Adder
0.971
24728805RICHG1
Adder
2.784
24728905RICHG2
Adder
2.784
960161AF2-307 GEN
Solar/Wind Harmer
4.571
24379505HDWTR1G C
Solar/Wind Harmer
5.217
270209AC1-174_GEN
Solar/Wind Harmer
3.682
926881AC1-175 GEN
Solar/Wind Harmer
3.682
270383AD1-128 GEN
Solar/Wind Harmer
3.962
964571AG1-320 GEN
Solar/Wind Harmer
5.136
970883AG2-550 GEN
Solar/Wind Harmer
6.261
970885AG2-551 GEN
Solar/Wind Harmer
1.456
970653AG2-424 GEN
Solar/Wind Harmer
2.916
970653AG2-424 GEN
Solar/Wind Harmer
1.054
970825AG2-519 GEN
Solar/Wind Harmer
6.248
960441AF2-335 GEN
Solar/Wind Harmer
5.883
247621Y3-024
Adder
0.14
964611AG1-324 GEN
Solar/Wind Harmer
0.674
964611AG1-324 GEN
Solar/Wind Harmer
0.299
270201AC2-176 GEN
Solar/Wind Harmer
2.909
971081AG2-670 GEN
Solar/Wind Harmer
4.164
270599AE1-208 GEN
Solar/Wind Harmer
4.481
270031AE2-169
Solar/Wind Harmer
4.481
339236AF1-050_GEN
Solar/Wind Harmer
0.967
970239AG2-162 GEN
Solar/Wind Harmer
5.822
270444AC2-157 GEN1
Solar/Wind Harmer
2.94
339231AF1-038_GEN
Solar/Wind Harmer
0.928
944541AF1-119 GEN
Solar/Wind Harmer
2.14
960971AF2-388 GEN
Solar/Wind Harmer
5.586
25326509SID D
Adder
0.665
945391AF1-204 GEN
Solar/Wind Harmer
7.039
339255AE2-071 GEN
Solar/Wind Harmer
0.525
964781AG1-341 GEN
Solar/Wind Harmer
5.228
270518AE2-148 GEN
Solar/Wind Harmer
5.786
942221AE2-234 GEN
Solar/Wind Harmer
0.35
970241AG2-163 GEN
Solar/Wind Harmer
11.758
971485AH1-239 GEN
Solar/Wind Harmer
3.722
966021AG1-471 GEN
Solar/Wind Harmer
2.491
253378AE2-206_GEN
Solar/Wind Harmer
1.656
276820AF1-078_GEN
Solar/Wind Harmer
0.736
966841AG1-555 GEN
Solar/Wind Harmer
0.721
970289AG2-191 GEN
Solar/Wind Harmer
0.409
970291AG2-192 GEN
Solar/Wind Harmer
0.372
970243AG2-164 GEN
Solar/Wind Harmer
13.668
970519AG2-331 GEN
Solar/Wind Harmer
9.183
970699AG2-449 GEN
Solar/Wind Harmer
6.075
972273AH1-721 GEN
Adder
43.806
247642Z2-115 C
Solar/Wind Harmer
0.033
970273AG2-179 GEN
Solar/Wind Harmer
1.986
971617AH1-308 GEN
Solar/Wind Harmer
2.961
970193AG2-126 GEN
Solar/Wind Harmer
7.576
339250AF1-203 GEN
Solar/Wind Harmer
0.3
962251AG1-071 GEN
Solar/Wind Harmer
2.72
971155AH1-034 GEN
Solar/Wind Harmer
4.929
944531AF1-118 GEN
Solar/Wind Harmer
16.137
944201AF1-088_MTX
Adder
61.225
957141AF2-008_MTX
Adder
30.613
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.203
MECLTFEXP_MEC->PJM
CLTF
6.527
SIGELTFEXP_SIGE->PJM
CLTF
0.311
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.847
LAGNLTFEXP_LAGN->PJM
CLTF
6.069
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.548
TVALTFEXP_TVA->PJM
CLTF
2.997
NYPJM->LTFIMP_NY
CLTF
1.498
LGEELTFEXP_LGEE->PJM
CLTF
5.05
WECLTFEXP_WEC->PJM
CLTF
1.467
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1
AG2-052LTFEXP_AG2-052->PJM
LTF
0.095
AH1-155LTFEXP_AH1-155->PJM
LTF
0.142

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34569 34598 34524_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34569 34598 34524_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.73 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2044.01
MW Contribution:6.25
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.447
24803306KYGER 4LP
50/50
2.396
971191AH1-055 GEN
Solar/Wind Harmer
85.12
25196608WSDLE5
Adder
9.731
25194608D.CRK4
Adder
1.854
252510AF1-249 C
Solar/Wind Harmer
0.469
25196008MFTGT1
Adder
1.385
958171AF2-111 GEN
Solar/Wind Harmer
24.753
253316AC1-085 GEN3
Solar/Wind Harmer
7.888
24803006KYGER 3HP
50/50
4.157
24802806KYGER 2HP
50/50
4.133
24802906KYGER 2LP
50/50
2.43
252509AD1-136 GEN
Solar/Wind Harmer
0.304
253433AC1-085 GEN1
Solar/Wind Harmer
5.007
946181AF1-283 GEN
Solar/Wind Harmer
12.242
972167AH1-666 GEN
Solar/Wind Harmer
7.471
972173AH1-669 GEN
Solar/Wind Harmer
4.449
270273AD2-016 GEN
Solar/Wind Harmer
2.265
270222AC2-111 GEN
Solar/Wind Harmer
6.583
253406AD2-031_GEN
Solar/Wind Harmer
1.022
253415AE1-040 GEN
Solar/Wind Harmer
0.887
3429391JKCT 9G
Adder
6.458
270356AE2-297 GEN
Solar/Wind Harmer
3.298
970093AG2-073 GEN
Solar/Wind Harmer
7.066
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.454
24803506KYGER 5LP
50/50
2.396
25016408BKJDB1
50/50
0.293
25250008NTE_CT
50/50
1.921
25250108NTE_ST
50/50
1.463
971985AH1-537 GEN
Solar/Wind Harmer
50.537
252524AE2-267 GEN
Solar/Wind Harmer
1.791
25196408WSDLE3
Adder
10.017
25196308WSDLE2
Adder
9.93
25196208WSDLE1
Adder
9.905
25196708WSDLE6
Adder
9.88
25196508WSDLE4
Adder
9.631
25196108MFTGT2
Adder
1.576
25196108MFTGT2
Adder
1.463
972163AH1-664 GEN
Solar/Wind Harmer
9.197
972165AH1-665 GEN
Solar/Wind Harmer
7.358
270367AC2-061_GEN
Solar/Wind Harmer
2.867
339243AC2-075 GEN1
Solar/Wind Harmer
0.403
270269AC2-059
Solar/Wind Harmer
7.919
270340AC2-060 GEN
Solar/Wind Harmer
2.488
944031AF1-071 GEN
Solar/Wind Harmer
0.811
3429211JKCT 2G
Adder
8.808
970689AG2-444 GEN
Solar/Wind Harmer
12.105
270240V3-007_GEN2
Solar/Wind Harmer
4.203
270432AC2-029 GEN
Solar/Wind Harmer
4.625
971673AH1-337 GEN
Solar/Wind Harmer
3.039
339211AE2-254 GEN
Solar/Wind Harmer
0.989
971029AG2-637 GEN
Solar/Wind Harmer
9.777
970455AG2-298 GEN
Solar/Wind Harmer
3.893
253349AC2-067 GEN
Solar/Wind Harmer
3.188
253400AC2-068 GEN
Solar/Wind Harmer
1.282
25306009OHH W.
Adder
1.837
253372AE2-315 SEC3
Adder
1.189
253372AE2-315 SEC3
Adder
1.189
270543AE2-219 C
Solar/Wind Harmer
3.202
970115AG2-085 GEN
Solar/Wind Harmer
2.405
24725505WLD G2 C
Solar/Wind Harmer
2.339
24699105WLD G1 C
Solar/Wind Harmer
2.311
961761AG1-017 GEN
Solar/Wind Harmer
0.244
945581AF1-223 GEN
Solar/Wind Harmer
2.545
965401AG1-405 GEN
Solar/Wind Harmer
3.196
965411AG1-406 GEN
Solar/Wind Harmer
1.435
270594AE1-207 GEN
Solar/Wind Harmer
8.234
965461AG1-414 GEN
Solar/Wind Harmer
1.234
970289AG2-191 GEN
Solar/Wind Harmer
1.034
965101AG1-375 GEN
Solar/Wind Harmer
5.378
958711AF2-162 GEN
Solar/Wind Harmer
0.532
270024AE2-089 GEN
Solar/Wind Harmer
2.414
241972AD1-140 GEN
Solar/Wind Harmer
2.212
24729505KEY G4
Adder
3.167
963841AG1-237 GEN
Solar/Wind Harmer
5.111
24386205FR-12G C
Solar/Wind Harmer
1.958
24386405FR-21G C
Solar/Wind Harmer
1.964
24386605FR-22G C
Solar/Wind Harmer
1.964
24387005FR-3G C
Solar/Wind Harmer
1.807
270156DARBY CT1
Adder
3.979
270157DARBY CT2
Adder
3.97
270158DARBY CT3
Adder
3.906
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944221AF1-090 GEN
Solar/Wind Harmer
0.044
252519AF1-045_GEN
Solar/Wind Harmer
6.939
252516AE2-318_GEN
Solar/Wind Harmer
5.293
25194408D.CRK1
Adder
8.527
25194508D.CRK3
Adder
1.594
25183208HLCRTG
Solar/Wind Harmer
6.758
253317AC1-085 GEN4
Solar/Wind Harmer
7.888
970235AG2-159 GEN
Solar/Wind Harmer
3.588
970235AG2-159 GEN
Solar/Wind Harmer
2.19
270186AC1-089 GEN
Solar/Wind Harmer
5.394
339221AD2-048_GEN
Solar/Wind Harmer
1.338
962581AG1-107 GEN
Solar/Wind Harmer
4.27
961491AF2-440 GEN
Solar/Wind Harmer
1.775
972043AH1-570 GEN
Solar/Wind Harmer
2.119
972045AH1-571 GEN
Solar/Wind Harmer
1.695
253394AE2-221_GEN
Solar/Wind Harmer
3.836
253398AE2-221_GEN2
Solar/Wind Harmer
3.836
971125AH1-004 GEN
Solar/Wind Harmer
3.294
970107AG2-081 GEN
Solar/Wind Harmer
2.471
24728805RICHG1
Adder
2.798
24728905RICHG2
Adder
2.798
942891AE2-308 GEN
Solar/Wind Harmer
7.396
960161AF2-307 GEN
Solar/Wind Harmer
4.489
24379505HDWTR1G C
Solar/Wind Harmer
5.372
270209AC1-174_GEN
Solar/Wind Harmer
3.791
926881AC1-175 GEN
Solar/Wind Harmer
3.791
270383AD1-128 GEN
Solar/Wind Harmer
4.025
964571AG1-320 GEN
Solar/Wind Harmer
5.163
253370AE2-315 SEC1
Adder
1.257
970883AG2-550 GEN
Solar/Wind Harmer
6.253
970885AG2-551 GEN
Solar/Wind Harmer
1.454
25322209TAIT E
Adder
5.931
25322209TAIT E
Adder
5.798
970653AG2-424 GEN
Solar/Wind Harmer
2.924
970653AG2-424 GEN
Solar/Wind Harmer
1.057
970825AG2-519 GEN
Solar/Wind Harmer
6.385
960441AF2-335 GEN
Solar/Wind Harmer
6.012
247621Y3-024
Adder
0.141
25326109MON D
Adder
0.761
964611AG1-324 GEN
Solar/Wind Harmer
0.68
964611AG1-324 GEN
Solar/Wind Harmer
0.302
270201AC2-176 GEN
Solar/Wind Harmer
2.928
270599AE1-208 GEN
Solar/Wind Harmer
4.584
270031AE2-169
Solar/Wind Harmer
4.584
971081AG2-670 GEN
Solar/Wind Harmer
4.157
339236AF1-050_GEN
Solar/Wind Harmer
0.965
270444AC2-157 GEN1
Solar/Wind Harmer
2.967
970239AG2-162 GEN
Solar/Wind Harmer
5.82
944541AF1-119 GEN
Solar/Wind Harmer
2.201
960971AF2-388 GEN
Solar/Wind Harmer
5.745
945391AF1-204 GEN
Solar/Wind Harmer
7.147
339231AF1-038_GEN
Solar/Wind Harmer
0.921
339255AE2-071 GEN
Solar/Wind Harmer
0.523
964781AG1-341 GEN
Solar/Wind Harmer
5.213
942221AE2-234 GEN
Solar/Wind Harmer
0.356
970241AG2-163 GEN
Solar/Wind Harmer
11.947
971485AH1-239 GEN
Solar/Wind Harmer
3.69
966021AG1-471 GEN
Solar/Wind Harmer
2.468
966841AG1-555 GEN
Solar/Wind Harmer
1.146
25326509SID D
Adder
0.572
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803406KYGER 5HP
50/50
4.111
24803206KYGER 4HP
50/50
4.107
252507AC2-088 GEN
Solar/Wind Harmer
2.131
25194608D.CRK4
Adder
1.854
25196808ZIMRHP
Adder
83.848
25196008MFTGT1
Adder
1.43
253432AC1-085 GEN2
Solar/Wind Harmer
0.252
946171AF1-282 GEN
Solar/Wind Harmer
9.417
945681AF1-233 GEN
Solar/Wind Harmer
17.533
339216AC1-074 GEN
Solar/Wind Harmer
1.49
270263AC1-001 GEN
Solar/Wind Harmer
0.891
943111AE2-339 GEN
Solar/Wind Harmer
0.713
3429421JKCT 10G
Adder
6.458
3429241JKCT 3G
Adder
8.923
942081AE2-220 GEN
Solar/Wind Harmer
4.343
270239V3-007_GEN1
Solar/Wind Harmer
1.169
971565AH1-281 GEN
Solar/Wind Harmer
1.339
971821AH1-427 GEN
Solar/Wind Harmer
6.42
24728605AND G2
Adder
2.429
253370AE2-315 SEC1
Adder
1.257
253371AE2-315 SEC2
Adder
1.189
270005AE1-210 C O1
Solar/Wind Harmer
3.366
965031AG1-367 GEN
Solar/Wind Harmer
6.159
960071AF2-298 GEN
Solar/Wind Harmer
3.07
25326309TAIT D
Adder
0.666
970825AG2-519 GEN
Solar/Wind Harmer
1.425
247536S-71 GEN
Solar/Wind Harmer
2.43
276903AD2-071 C
Solar/Wind Harmer
5.746
253343AC1-166 GEN
Solar/Wind Harmer
0.615
253325AC1-069 GEN
Solar/Wind Harmer
0.593
339241AF1-083 GEN
Solar/Wind Harmer
0.936
945371AF1-202 GEN
Solar/Wind Harmer
3.916
270032AE2-172
Solar/Wind Harmer
2.606
970091AG2-072 GEN
Adder
42.548
970291AG2-192 GEN
Solar/Wind Harmer
0.707
958861AF2-177 GEN
Solar/Wind Harmer
5.878
270445AC2-157 GEN2
Solar/Wind Harmer
2.967
970333AG2-219 GEN
Solar/Wind Harmer
16.702
965651AG1-433 GEN
Solar/Wind Harmer
2.872
964901AG1-354 GEN
Solar/Wind Harmer
7.722
970273AG2-179 GEN
Solar/Wind Harmer
1.235
962241AG1-070 GEN
Solar/Wind Harmer
2.22
963741AG1-226 GEN
Solar/Wind Harmer
21.505
24385905FR-11G C
Solar/Wind Harmer
3.796
24387305FR-4G C
Solar/Wind Harmer
2.321
270159DARBY CT4
Adder
3.916
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.198
966571AG1-526 GEN
Solar/Wind Harmer
15.11
270437AC2-090 C
Solar/Wind Harmer
3.793
24728705AND G3
Adder
5.08
24728505AND G1
Adder
2.429
253303V4-073 C
Solar/Wind Harmer
0.073
253370AE2-315 SEC1
Adder
1.257
253371AE2-315 SEC2
Adder
1.189
958821AF2-173 GEN
Solar/Wind Harmer
8.623
270004AE1-209 GEN
Solar/Wind Harmer
3.366
946031AF1-268 GEN
Solar/Wind Harmer
5.017
962031AG1-047 GEN
Solar/Wind Harmer
1.721
957741AF2-068 GEN
Solar/Wind Harmer
8.543
253338AC1-165 GEN
Solar/Wind Harmer
0.615
253333AC1-068 GEN
Solar/Wind Harmer
0.593
970289AG2-191 GEN
Solar/Wind Harmer
0.418
970291AG2-192 GEN
Solar/Wind Harmer
0.38
960741AF2-365 GEN
Solar/Wind Harmer
2.673
970243AG2-164 GEN
Solar/Wind Harmer
13.665
970519AG2-331 GEN
Solar/Wind Harmer
9.181
970699AG2-449 GEN
Solar/Wind Harmer
6.073
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
43.41
971617AH1-308 GEN
Solar/Wind Harmer
2.99
970193AG2-126 GEN
Solar/Wind Harmer
7.693
970273AG2-179 GEN
Solar/Wind Harmer
1.973
339250AF1-203 GEN
Solar/Wind Harmer
0.299
962251AG1-071 GEN
Solar/Wind Harmer
2.713
971155AH1-034 GEN
Solar/Wind Harmer
4.913
944531AF1-118 GEN
Solar/Wind Harmer
16.613
235780M24_1
Solar/Wind Helper
0.923
944201AF1-088_MTX
Adder
61.779
957141AF2-008_MTX
Adder
30.89
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.602
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.08
MECLTFEXP_MEC->PJM
CLTF
6.608
SIGELTFEXP_SIGE->PJM
CLTF
0.315
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.963
LAGNLTFEXP_LAGN->PJM
CLTF
5.99
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.148
TVALTFEXP_TVA->PJM
CLTF
2.938
NYPJM->LTFIMP_NY
CLTF
1.486
LGEELTFEXP_LGEE->PJM
CLTF
5.109
WECLTFEXP_WEC->PJM
CLTF
1.495
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.187
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.145

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o 34524 34598_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
34524 34598_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:132.58 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2041.73
MW Contribution:6.23
Bus #Bus NameTypeMW Contribution
24803406KYGER 5HP
50/50
4.111
24803206KYGER 4HP
50/50
4.107
252507AC2-088 GEN
Solar/Wind Harmer
2.144
24803006KYGER 3HP
50/50
4.157
24802806KYGER 2HP
50/50
4.133
24802906KYGER 2LP
50/50
2.43
252509AD1-136 GEN
Solar/Wind Harmer
0.306
25183208HLCRTG
Solar/Wind Harmer
6.991
252519AF1-045_GEN
Solar/Wind Harmer
6.973
252516AE2-318_GEN
Solar/Wind Harmer
5.319
25194408D.CRK1
Adder
8.448
25194508D.CRK3
Adder
1.579
253317AC1-085 GEN4
Solar/Wind Harmer
7.982
970235AG2-159 GEN
Solar/Wind Harmer
3.58
970235AG2-159 GEN
Solar/Wind Harmer
2.186
270186AC1-089 GEN
Solar/Wind Harmer
5.399
339221AD2-048_GEN
Solar/Wind Harmer
1.342
253394AE2-221_GEN
Solar/Wind Harmer
3.877
253398AE2-221_GEN2
Solar/Wind Harmer
3.877
972043AH1-570 GEN
Solar/Wind Harmer
2.126
972045AH1-571 GEN
Solar/Wind Harmer
1.701
962581AG1-107 GEN
Solar/Wind Harmer
4.271
961491AF2-440 GEN
Solar/Wind Harmer
1.775
971125AH1-004 GEN
Solar/Wind Harmer
3.306
970107AG2-081 GEN
Solar/Wind Harmer
2.48
942891AE2-308 GEN
Solar/Wind Harmer
7.422
24728805RICHG1
Adder
2.785
24728905RICHG2
Adder
2.785
960161AF2-307 GEN
Solar/Wind Harmer
4.511
24803106KYGER 3LP
50/50
2.447
24803306KYGER 4LP
50/50
2.396
971191AH1-055 GEN
Solar/Wind Harmer
85.136
25196608WSDLE5
Adder
9.63
25194608D.CRK4
Adder
1.836
252510AF1-249 C
Solar/Wind Harmer
0.465
25196008MFTGT1
Adder
1.376
958171AF2-111 GEN
Solar/Wind Harmer
24.947
253316AC1-085 GEN3
Solar/Wind Harmer
7.982
253433AC1-085 GEN1
Solar/Wind Harmer
5.067
946181AF1-283 GEN
Solar/Wind Harmer
12.388
972167AH1-666 GEN
Solar/Wind Harmer
7.523
972173AH1-669 GEN
Solar/Wind Harmer
4.457
270273AD2-016 GEN
Solar/Wind Harmer
2.269
253406AD2-031_GEN
Solar/Wind Harmer
1.029
270222AC2-111 GEN
Solar/Wind Harmer
6.549
253415AE1-040 GEN
Solar/Wind Harmer
0.891
3429391JKCT 9G
Adder
6.486
270356AE2-297 GEN
Solar/Wind Harmer
3.281
970093AG2-073 GEN
Solar/Wind Harmer
7.088
966571AG1-526 GEN
Solar/Wind Harmer
15.14
270437AC2-090 C
Solar/Wind Harmer
3.774
24728705AND G3
Adder
5.059
24728505AND G1
Adder
2.419
253303V4-073 C
Solar/Wind Harmer
0.073
253370AE2-315 SEC1
Adder
1.261
253371AE2-315 SEC2
Adder
1.193
958821AF2-173 GEN
Solar/Wind Harmer
8.583
270004AE1-209 GEN
Solar/Wind Harmer
3.35
946031AF1-268 GEN
Solar/Wind Harmer
4.995
253338AC1-165 GEN
Solar/Wind Harmer
0.621
253333AC1-068 GEN
Solar/Wind Harmer
0.599
962031AG1-047 GEN
Solar/Wind Harmer
1.715
957741AF2-068 GEN
Solar/Wind Harmer
8.509
970289AG2-191 GEN
Solar/Wind Harmer
0.416
970291AG2-192 GEN
Solar/Wind Harmer
0.378
960741AF2-365 GEN
Solar/Wind Harmer
2.671
970243AG2-164 GEN
Solar/Wind Harmer
13.619
970519AG2-331 GEN
Solar/Wind Harmer
9.15
24802606KYGER 1HP
50/50
4.181
24802706KYGER 1LP
50/50
2.454
24803506KYGER 5LP
50/50
2.396
25016408BKJDB1
50/50
0.291
25183008BIOENL
50/50
0.032
25250008NTE_CT
50/50
1.9
25250108NTE_ST
50/50
1.447
971985AH1-537 GEN
Solar/Wind Harmer
50.462
252524AE2-267 GEN
Solar/Wind Harmer
1.772
25196408WSDLE3
Adder
9.913
25196308WSDLE2
Adder
9.827
25196208WSDLE1
Adder
9.802
25196708WSDLE6
Adder
9.777
25196508WSDLE4
Adder
9.531
25196108MFTGT2
Adder
1.567
25196108MFTGT2
Adder
1.455
972163AH1-664 GEN
Solar/Wind Harmer
9.259
972165AH1-665 GEN
Solar/Wind Harmer
7.407
270367AC2-061_GEN
Solar/Wind Harmer
2.864
339243AC2-075 GEN1
Solar/Wind Harmer
0.405
270269AC2-059
Solar/Wind Harmer
7.935
270340AC2-060 GEN
Solar/Wind Harmer
2.497
944031AF1-071 GEN
Solar/Wind Harmer
0.807
3429211JKCT 2G
Adder
8.843
970689AG2-444 GEN
Solar/Wind Harmer
12.133
270240V3-007_GEN2
Solar/Wind Harmer
4.182
270432AC2-029 GEN
Solar/Wind Harmer
4.637
971673AH1-337 GEN
Solar/Wind Harmer
3.026
339211AE2-254 GEN
Solar/Wind Harmer
0.991
971029AG2-637 GEN
Solar/Wind Harmer
9.737
970455AG2-298 GEN
Solar/Wind Harmer
3.891
253349AC2-067 GEN
Solar/Wind Harmer
3.191
253400AC2-068 GEN
Solar/Wind Harmer
1.283
25306009OHH W.
Adder
1.841
253372AE2-315 SEC3
Adder
1.193
253372AE2-315 SEC3
Adder
1.193
270543AE2-219 C
Solar/Wind Harmer
3.189
970115AG2-085 GEN
Solar/Wind Harmer
2.394
24725505WLD G2 C
Solar/Wind Harmer
2.329
24699105WLD G1 C
Solar/Wind Harmer
2.301
961761AG1-017 GEN
Solar/Wind Harmer
0.243
965401AG1-405 GEN
Solar/Wind Harmer
3.201
965411AG1-406 GEN
Solar/Wind Harmer
1.437
945581AF1-223 GEN
Solar/Wind Harmer
2.534
270594AE1-207 GEN
Solar/Wind Harmer
8.199
965461AG1-414 GEN
Solar/Wind Harmer
1.229
970289AG2-191 GEN
Solar/Wind Harmer
1.03
965101AG1-375 GEN
Solar/Wind Harmer
5.355
958711AF2-162 GEN
Solar/Wind Harmer
0.529
270024AE2-089 GEN
Solar/Wind Harmer
2.404
241972AD1-140 GEN
Solar/Wind Harmer
2.223
24729505KEY G4
Adder
3.154
963841AG1-237 GEN
Solar/Wind Harmer
5.094
24386205FR-12G C
Solar/Wind Harmer
1.951
24386405FR-21G C
Solar/Wind Harmer
1.958
24386605FR-22G C
Solar/Wind Harmer
1.958
24387005FR-3G C
Solar/Wind Harmer
1.801
270156DARBY CT1
Adder
4.019
270157DARBY CT2
Adder
4.009
270158DARBY CT3
Adder
3.945
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
944221AF1-090 GEN
Solar/Wind Harmer
0.044
24379505HDWTR1G C
Solar/Wind Harmer
5.345
270209AC1-174_GEN
Solar/Wind Harmer
3.772
926881AC1-175 GEN
Solar/Wind Harmer
3.772
270383AD1-128 GEN
Solar/Wind Harmer
4.006
253370AE2-315 SEC1
Adder
1.261
964571AG1-320 GEN
Solar/Wind Harmer
5.157
970883AG2-550 GEN
Solar/Wind Harmer
6.228
970885AG2-551 GEN
Solar/Wind Harmer
1.448
25322209TAIT E
Adder
5.949
25322209TAIT E
Adder
5.815
970653AG2-424 GEN
Solar/Wind Harmer
2.922
970653AG2-424 GEN
Solar/Wind Harmer
1.056
970825AG2-519 GEN
Solar/Wind Harmer
6.356
960441AF2-335 GEN
Solar/Wind Harmer
5.986
247621Y3-024
Adder
0.14
25326109MON D
Adder
0.764
964611AG1-324 GEN
Solar/Wind Harmer
0.677
964611AG1-324 GEN
Solar/Wind Harmer
0.301
270201AC2-176 GEN
Solar/Wind Harmer
2.916
270599AE1-208 GEN
Solar/Wind Harmer
4.564
270031AE2-169
Solar/Wind Harmer
4.564
971081AG2-670 GEN
Solar/Wind Harmer
4.155
339236AF1-050_GEN
Solar/Wind Harmer
0.964
270444AC2-157 GEN1
Solar/Wind Harmer
2.957
970239AG2-162 GEN
Solar/Wind Harmer
5.801
944541AF1-119 GEN
Solar/Wind Harmer
2.192
960971AF2-388 GEN
Solar/Wind Harmer
5.72
945391AF1-204 GEN
Solar/Wind Harmer
7.122
339231AF1-038_GEN
Solar/Wind Harmer
0.921
339255AE2-071 GEN
Solar/Wind Harmer
0.523
964781AG1-341 GEN
Solar/Wind Harmer
5.208
942221AE2-234 GEN
Solar/Wind Harmer
0.355
970241AG2-163 GEN
Solar/Wind Harmer
11.906
971485AH1-239 GEN
Solar/Wind Harmer
3.69
966021AG1-471 GEN
Solar/Wind Harmer
2.468
966841AG1-555 GEN
Solar/Wind Harmer
1.142
25194608D.CRK4
Adder
1.836
25196808ZIMRHP
Adder
83.684
25196008MFTGT1
Adder
1.421
253432AC1-085 GEN2
Solar/Wind Harmer
0.255
946171AF1-282 GEN
Solar/Wind Harmer
9.53
945681AF1-233 GEN
Solar/Wind Harmer
17.654
339216AC1-074 GEN
Solar/Wind Harmer
1.495
270263AC1-001 GEN
Solar/Wind Harmer
0.893
943111AE2-339 GEN
Solar/Wind Harmer
0.716
3429421JKCT 10G
Adder
6.486
3429241JKCT 3G
Adder
8.959
942081AE2-220 GEN
Solar/Wind Harmer
4.322
270239V3-007_GEN1
Solar/Wind Harmer
1.163
971565AH1-281 GEN
Solar/Wind Harmer
1.338
971821AH1-427 GEN
Solar/Wind Harmer
6.429
24728605AND G2
Adder
2.419
253370AE2-315 SEC1
Adder
1.261
253371AE2-315 SEC2
Adder
1.193
960071AF2-298 GEN
Solar/Wind Harmer
3.077
270005AE1-210 C O1
Solar/Wind Harmer
3.35
965031AG1-367 GEN
Solar/Wind Harmer
6.131
25326309TAIT D
Adder
0.668
970825AG2-519 GEN
Solar/Wind Harmer
1.418
247536S-71 GEN
Solar/Wind Harmer
2.42
276903AD2-071 C
Solar/Wind Harmer
5.722
253343AC1-166 GEN
Solar/Wind Harmer
0.621
253325AC1-069 GEN
Solar/Wind Harmer
0.599
339241AF1-083 GEN
Solar/Wind Harmer
0.936
945371AF1-202 GEN
Solar/Wind Harmer
3.898
270032AE2-172
Solar/Wind Harmer
2.595
970091AG2-072 GEN
Adder
42.403
970291AG2-192 GEN
Solar/Wind Harmer
0.704
958861AF2-177 GEN
Solar/Wind Harmer
5.853
270445AC2-157 GEN2
Solar/Wind Harmer
2.957
970333AG2-219 GEN
Solar/Wind Harmer
16.645
965651AG1-433 GEN
Solar/Wind Harmer
2.86
964901AG1-354 GEN
Solar/Wind Harmer
7.717
970273AG2-179 GEN
Solar/Wind Harmer
1.236
962241AG1-070 GEN
Solar/Wind Harmer
2.218
963741AG1-226 GEN
Solar/Wind Harmer
21.432
24385905FR-11G C
Solar/Wind Harmer
3.783
24387305FR-4G C
Solar/Wind Harmer
2.313
270159DARBY CT4
Adder
3.955
960001AF2-291 GEN
Solar/Wind Helper
1.678
270331AC1-082 GEN3
Solar/Wind Helper
0.198
970699AG2-449 GEN
Solar/Wind Harmer
6.053
247642Z2-115 C
Solar/Wind Harmer
0.034
972273AH1-721 GEN
Adder
43.453
971617AH1-308 GEN
Solar/Wind Harmer
2.978
970193AG2-126 GEN
Solar/Wind Harmer
7.666
970273AG2-179 GEN
Solar/Wind Harmer
1.973
339250AF1-203 GEN
Solar/Wind Harmer
0.299
962251AG1-071 GEN
Solar/Wind Harmer
2.711
971155AH1-034 GEN
Solar/Wind Harmer
4.909
944531AF1-118 GEN
Solar/Wind Harmer
16.546
235780M24_1
Solar/Wind Helper
0.922
25326509SID D
Adder
0.573
237033AB1-150 GEN
Solar/Wind Helper
0.372
944201AF1-088_MTX
Adder
61.569
957141AF2-008_MTX
Adder
30.784
CBM West 1LTFEXP_CBM-W1->PJM
CBM
59.458
CBM South 1LTFEXP_CBM-S1->PJM
CBM
14.052
MECLTFEXP_MEC->PJM
CLTF
6.588
SIGELTFEXP_SIGE->PJM
CLTF
0.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.814
LAGNLTFEXP_LAGN->PJM
CLTF
5.976
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.15
TVALTFEXP_TVA->PJM
CLTF
2.933
NYPJM->LTFIMP_NY
CLTF
1.483
LGEELTFEXP_LGEE->PJM
CLTF
5.097
WECLTFEXP_WEC->PJM
CLTF
1.49
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.186
AG2-052LTFEXP_AG2-052->PJM
LTF
0.096
AH1-155LTFEXP_AH1-155->PJM
LTF
0.144

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:131.72 %
Rating:1189.0 MVA
Rating Type:A
MVA to Mitigate:1566.09
MW Contribution:4.33
Bus #Bus NameTypeMW Contribution
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.392
971191AH1-055 GEN
Solar/Wind Harmer
69.07
25194608D.CRK4
Adder
1.656
25196608WSDLE5
Adder
8.625
252510AF1-249 C
Solar/Wind Harmer
0.054
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
9.086
958171AF2-111 GEN
Solar/Wind Harmer
16.854
25196008MFTGT1
Adder
1.285
972167AH1-666 GEN
Solar/Wind Harmer
5.077
972173AH1-669 GEN
Solar/Wind Harmer
3.165
253406AD2-031_GEN
Solar/Wind Harmer
0.462
270273AD2-016 GEN
Solar/Wind Harmer
0.628
253415AE1-040 GEN
Solar/Wind Harmer
0.002
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
270222AC2-111 GEN
Solar/Wind Harmer
2.79
970191AG2-125 GEN
Solar/Wind Harmer
1.36
3429391JKCT 9G
Adder
6.235
270356AE2-297 GEN
Solar/Wind Harmer
0.006
970093AG2-073 GEN
Solar/Wind Harmer
4.742
966571AG1-526 GEN
Solar/Wind Harmer
10.106
270437AC2-090 C
Solar/Wind Harmer
0.002
253338AC1-165 GEN
Solar/Wind Harmer
0.002
253333AC1-068 GEN
Solar/Wind Harmer
0.007
24728705AND G3
Adder
4.853
24728505AND G1
Adder
2.32
958821AF2-173 GEN
Solar/Wind Harmer
5.771
270004AE1-209 GEN
Solar/Wind Harmer
0.893
946031AF1-268 GEN
Solar/Wind Harmer
3.889
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
5.885
970289AG2-191 GEN
Solar/Wind Harmer
0.403
970291AG2-192 GEN
Solar/Wind Harmer
0.367
247642Z2-115 C
Solar/Wind Harmer
0.002
971617AH1-308 GEN
Solar/Wind Harmer
2.961
960741AF2-365 GEN
Solar/Wind Harmer
1.775
970243AG2-164 GEN
Solar/Wind Harmer
2.07
970519AG2-331 GEN
Solar/Wind Harmer
9.199
970699AG2-449 GEN
Solar/Wind Harmer
0.884
972273AH1-721 GEN
Adder
41.409
970193AG2-126 GEN
Solar/Wind Harmer
5.147
970273AG2-179 GEN
Solar/Wind Harmer
2.017
339250AF1-203 GEN
Solar/Wind Harmer
0
962251AG1-071 GEN
Solar/Wind Harmer
2.045
970605AG2-385 GEN
Solar/Wind Harmer
1.988
971155AH1-034 GEN
Solar/Wind Harmer
3.802
944531AF1-118 GEN
Solar/Wind Harmer
14.426
235780M24_1
Solar/Wind Helper
0.923
24802606KYGER 1HP
50/50
4.173
24802706KYGER 1LP
50/50
2.449
24803506KYGER 5LP
50/50
2.392
25016408BKJDB1
50/50
0.272
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
5.759
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.879
25196308WSDLE2
Adder
8.801
25196208WSDLE1
Adder
8.779
25196708WSDLE6
Adder
8.757
25196508WSDLE4
Adder
8.537
25196108MFTGT2
Adder
1.463
25196108MFTGT2
Adder
1.358
972163AH1-664 GEN
Solar/Wind Harmer
6.955
972165AH1-665 GEN
Solar/Wind Harmer
5.57
270367AC2-061_GEN
Solar/Wind Harmer
0.005
270269AC2-059
Solar/Wind Harmer
0.003
270340AC2-060 GEN
Solar/Wind Harmer
0.007
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
253372AE2-315 SEC3
Adder
1.506
253372AE2-315 SEC3
Adder
1.506
25306009OHH W.
Adder
2.247
970689AG2-444 GEN
Solar/Wind Harmer
10.893
253349AC2-067 GEN
Solar/Wind Harmer
1.665
253400AC2-068 GEN
Solar/Wind Harmer
0.67
3429211JKCT 2G
Adder
8.494
270432AC2-029 GEN
Solar/Wind Harmer
2.121
971673AH1-337 GEN
Solar/Wind Harmer
2.979
241972AD1-140 GEN
Solar/Wind Harmer
0.495
270240V3-007_GEN2
Solar/Wind Harmer
0.001
971029AG2-637 GEN
Solar/Wind Harmer
6.776
339211AE2-254 GEN
Solar/Wind Harmer
0.002
270543AE2-219 C
Solar/Wind Harmer
0.003
970455AG2-298 GEN
Solar/Wind Harmer
2.878
970115AG2-085 GEN
Solar/Wind Harmer
1.619
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.62
270594AE1-207 GEN
Solar/Wind Harmer
4.227
945581AF1-223 GEN
Solar/Wind Harmer
0
965401AG1-405 GEN
Solar/Wind Harmer
2.132
965411AG1-406 GEN
Solar/Wind Harmer
1.371
970289AG2-191 GEN
Solar/Wind Harmer
0.697
965101AG1-375 GEN
Solar/Wind Harmer
3.623
270024AE2-089 GEN
Solar/Wind Harmer
0.004
270156DARBY CT1
Adder
4.415
270157DARBY CT2
Adder
4.404
270158DARBY CT3
Adder
4.334
24729505KEY G4
Adder
3.073
945631AF1-228 GEN
Solar/Wind Harmer
0
963841AG1-237 GEN
Solar/Wind Harmer
1.363
24386205FR-12G C
Solar/Wind Harmer
0
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
944221AF1-090 GEN
Solar/Wind Harmer
1.779
943861AF1-054 GEN
Solar/Wind Harmer
1.158
943851AF1-053 GEN
Solar/Wind Harmer
0.802
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.199
24803006KYGER 3HP
50/50
4.149
24802806KYGER 2HP
50/50
4.125
24802906KYGER 2LP
50/50
2.425
252509AD1-136 GEN
Solar/Wind Harmer
0.04
25183208HLCRTG
Solar/Wind Harmer
0.012
252519AF1-045_GEN
Solar/Wind Harmer
6.35
252516AE2-318_GEN
Solar/Wind Harmer
5.632
25194408D.CRK1
Adder
7.616
25194508D.CRK3
Adder
1.424
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
270186AC1-089 GEN
Solar/Wind Harmer
0.004
962581AG1-107 GEN
Solar/Wind Harmer
0.001
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
339221AD2-048_GEN
Solar/Wind Harmer
0.004
972043AH1-570 GEN
Solar/Wind Harmer
1.484
972045AH1-571 GEN
Solar/Wind Harmer
1.189
253370AE2-315 SEC1
Adder
1.592
971125AH1-004 GEN
Solar/Wind Harmer
2.215
970107AG2-081 GEN
Solar/Wind Harmer
1.662
25322209TAIT E
Adder
7.486
25322209TAIT E
Adder
7.317
25326109MON D
Adder
0.984
24728805RICHG1
Adder
2.73
24728905RICHG2
Adder
2.73
942891AE2-308 GEN
Solar/Wind Harmer
4.97
960161AF2-307 GEN
Solar/Wind Harmer
3.112
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970883AG2-550 GEN
Solar/Wind Harmer
4.325
970885AG2-551 GEN
Solar/Wind Harmer
1.442
964571AG1-320 GEN
Solar/Wind Harmer
3.821
970825AG2-519 GEN
Solar/Wind Harmer
4.514
960441AF2-335 GEN
Solar/Wind Harmer
4.047
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
1.943
970653AG2-424 GEN
Solar/Wind Harmer
1.007
964611AG1-324 GEN
Solar/Wind Harmer
0.297
270201AC2-176 GEN
Solar/Wind Harmer
0.001
270518AE2-148 GEN
Solar/Wind Harmer
0.337
270599AE1-208 GEN
Solar/Wind Harmer
3.479
270031AE2-169
Solar/Wind Harmer
2.087
971613AH1-306 GEN
Solar/Wind Harmer
1.811
971081AG2-670 GEN
Solar/Wind Harmer
2.763
25326509SID D
Adder
0.693
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
2.6
944541AF1-119 GEN
Solar/Wind Harmer
0.237
960971AF2-388 GEN
Solar/Wind Harmer
2.079
970239AG2-162 GEN
Solar/Wind Harmer
0.884
945391AF1-204 GEN
Solar/Wind Harmer
3.646
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.467
942221AE2-234 GEN
Solar/Wind Harmer
0.017
339255AE2-071 GEN
Solar/Wind Harmer
-0.054
970077AG2-063 GEN
Solar/Wind Harmer
1.879
964781AG1-341 GEN
Solar/Wind Harmer
3.457
970241AG2-163 GEN
Solar/Wind Harmer
1.873
966841AG1-555 GEN
Solar/Wind Harmer
0.348
971485AH1-239 GEN
Solar/Wind Harmer
2.448
966021AG1-471 GEN
Solar/Wind Harmer
1.637
942861AE2-305 GEN
Solar/Wind Harmer
2.346
237033AB1-150 GEN
Solar/Wind Helper
0.372
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.099
252507AC2-088 GEN
Solar/Wind Harmer
0.356
25196808ZIMRHP
Adder
78.156
25194608D.CRK4
Adder
1.656
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.99
25196008MFTGT1
Adder
1.327
945681AF1-233 GEN
Solar/Wind Harmer
11.914
270263AC1-001 GEN
Solar/Wind Harmer
0.606
339216AC1-074 GEN
Solar/Wind Harmer
0.163
253370AE2-315 SEC1
Adder
1.592
253371AE2-315 SEC2
Adder
1.506
25326309TAIT D
Adder
0.84
960071AF2-298 GEN
Solar/Wind Harmer
2.635
3429421JKCT 10G
Adder
6.235
3429241JKCT 3G
Adder
8.606
970773AG2-487 GEN
Solar/Wind Harmer
0.849
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.314
971565AH1-281 GEN
Solar/Wind Harmer
0.891
253343AC1-166 GEN
Solar/Wind Harmer
0.002
253325AC1-069 GEN
Solar/Wind Harmer
0.007
971821AH1-427 GEN
Solar/Wind Harmer
4.286
24728605AND G2
Adder
2.32
247536S-71 GEN
Solar/Wind Harmer
0.167
270005AE1-210 C O1
Solar/Wind Harmer
0.893
965031AG1-367 GEN
Solar/Wind Harmer
4.122
970825AG2-519 GEN
Solar/Wind Harmer
1.446
276903AD2-071 C
Solar/Wind Harmer
4.31
270032AE2-172
Solar/Wind Harmer
2.516
945371AF1-202 GEN
Solar/Wind Harmer
0
970091AG2-072 GEN
Adder
40.612
970291AG2-192 GEN
Solar/Wind Harmer
0.477
958861AF2-177 GEN
Solar/Wind Harmer
1.57
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.04
970333AG2-219 GEN
Solar/Wind Harmer
2.53
270159DARBY CT4
Adder
4.344
964901AG1-354 GEN
Solar/Wind Harmer
5.126
970273AG2-179 GEN
Solar/Wind Harmer
1.177
962241AG1-070 GEN
Solar/Wind Harmer
1.783
970593AG2-378 GEN
Solar/Wind Harmer
0.735
963741AG1-226 GEN
Solar/Wind Harmer
7.599
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Helper
1.682
270331AC1-082 GEN3
Solar/Wind Helper
0.198
944201AF1-088_MTX
Adder
59.081
957141AF2-008_MTX
Adder
29.541
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.02
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.512
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.324
MECLTFEXP_MEC->PJM
CLTF
6.369
SIGELTFEXP_SIGE->PJM
CLTF
0.3
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.459
LAGNLTFEXP_LAGN->PJM
CLTF
5.678
TVALTFEXP_TVA->PJM
CLTF
2.775
NYPJM->LTFIMP_NY
CLTF
1.447
LGEELTFEXP_LGEE->PJM
CLTF
4.851
WECLTFEXP_WEC->PJM
CLTF
1.45
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.226
AG2-052LTFEXP_AG2-052->PJM
LTF
0.094
AH1-155LTFEXP_AH1-155->PJM
LTF
0.141

Details for 06KYGER-05SPORN 345.0 kV Ckt 1 line l/o AP_P2-2_WP-500-DRT14_SRT-SL


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06KYGER-05SPORN 345.0 kV Ckt 1 line
Contingency Name:
AP_P2-2_WP-500-DRT14_SRT-SL
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:130.87 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:2015.35
MW Contribution:6.19
Bus #Bus NameTypeMW Contribution
24802606KYGER 1HP
50/50
4.172
24802706KYGER 1LP
50/50
2.448
24803506KYGER 5LP
50/50
2.391
25016408BKJDB1
50/50
0.271
25183008BIOENL
50/50
0.03
971985AH1-537 GEN
Solar/Wind Harmer
49.503
252524AE2-267 GEN
Solar/Wind Harmer
1.585
25196408WSDLE3
Adder
8.868
25196308WSDLE2
Adder
8.791
25196208WSDLE1
Adder
8.769
25196708WSDLE6
Adder
8.747
25196508WSDLE4
Adder
8.527
25196108MFTGT2
Adder
1.461
25196108MFTGT2
Adder
1.356
972163AH1-664 GEN
Solar/Wind Harmer
8.942
972165AH1-665 GEN
Solar/Wind Harmer
7.153
270367AC2-061_GEN
Solar/Wind Harmer
2.821
270269AC2-059
Solar/Wind Harmer
8.083
270340AC2-060 GEN
Solar/Wind Harmer
2.623
24803406KYGER 5HP
50/50
4.102
24803206KYGER 4HP
50/50
4.098
252507AC2-088 GEN
Solar/Wind Harmer
2.011
25196808ZIMRHP
Adder
78.065
25194608D.CRK4
Adder
1.654
253432AC1-085 GEN2
Solar/Wind Harmer
0.268
946171AF1-282 GEN
Solar/Wind Harmer
10.007
25196008MFTGT1
Adder
1.325
945681AF1-233 GEN
Solar/Wind Harmer
17.054
270263AC1-001 GEN
Solar/Wind Harmer
0.904
339216AC1-074 GEN
Solar/Wind Harmer
1.432
253370AE2-315 SEC1
Adder
1.59
253371AE2-315 SEC2
Adder
1.504
943111AE2-339 GEN
Solar/Wind Harmer
0.687
25326309TAIT D
Adder
0.839
960071AF2-298 GEN
Solar/Wind Harmer
3.776
3429421JKCT 10G
Adder
6.225
3429241JKCT 3G
Adder
8.591
942081AE2-220 GEN
Solar/Wind Harmer
4.134
270239V3-007_GEN1
Solar/Wind Harmer
1.113
971565AH1-281 GEN
Solar/Wind Harmer
1.274
253343AC1-166 GEN
Solar/Wind Harmer
0.67
253325AC1-069 GEN
Solar/Wind Harmer
0.647
971821AH1-427 GEN
Solar/Wind Harmer
6.132
24728605AND G2
Adder
2.316
247536S-71 GEN
Solar/Wind Harmer
2.401
270005AE1-210 C O1
Solar/Wind Harmer
3.222
965031AG1-367 GEN
Solar/Wind Harmer
5.896
970825AG2-519 GEN
Solar/Wind Harmer
1.372
276903AD2-071 C
Solar/Wind Harmer
5.52
270032AE2-172
Solar/Wind Harmer
2.51
945371AF1-202 GEN
Solar/Wind Harmer
3.764
339241AF1-083 GEN
Solar/Wind Harmer
0.89
970091AG2-072 GEN
Adder
40.521
970291AG2-192 GEN
Solar/Wind Harmer
0.682
958861AF2-177 GEN
Solar/Wind Harmer
5.663
270445AC2-157 GEN2
Solar/Wind Harmer
2.831
965651AG1-433 GEN
Solar/Wind Harmer
2.77
970333AG2-219 GEN
Solar/Wind Harmer
15.949
270159DARBY CT4
Adder
4.334
964901AG1-354 GEN
Solar/Wind Harmer
7.329
970273AG2-179 GEN
Solar/Wind Harmer
1.174
962241AG1-070 GEN
Solar/Wind Harmer
2.105
970593AG2-378 GEN
Solar/Wind Harmer
0.935
963741AG1-226 GEN
Solar/Wind Harmer
20.657
960001AF2-291 GEN
Solar/Wind Helper
1.683
270331AC1-082 GEN3
Solar/Wind Helper
0.199
24385905FR-11G C
Solar/Wind Harmer
1.387
24387305FR-4G C
Solar/Wind Harmer
0.848
339243AC2-075 GEN1
Solar/Wind Harmer
0.388
253372AE2-315 SEC3
Adder
1.504
253372AE2-315 SEC3
Adder
1.504
944031AF1-071 GEN
Solar/Wind Harmer
0.792
25306009OHH W.
Adder
2.244
970689AG2-444 GEN
Solar/Wind Harmer
12.446
253349AC2-067 GEN
Solar/Wind Harmer
3.771
253400AC2-068 GEN
Solar/Wind Harmer
1.517
24803006KYGER 3HP
50/50
4.148
24802806KYGER 2HP
50/50
4.124
24802906KYGER 2LP
50/50
2.424
252509AD1-136 GEN
Solar/Wind Harmer
0.287
25183208HLCRTG
Solar/Wind Harmer
6.445
252519AF1-045_GEN
Solar/Wind Harmer
6.343
24803106KYGER 3LP
50/50
2.442
24803306KYGER 4LP
50/50
2.391
971191AH1-055 GEN
Solar/Wind Harmer
84.832
25194608D.CRK4
Adder
1.654
25196608WSDLE5
Adder
8.615
252510AF1-249 C
Solar/Wind Harmer
0.42
253316AC1-085 GEN3
Solar/Wind Harmer
8.382
253433AC1-085 GEN1
Solar/Wind Harmer
5.321
946181AF1-283 GEN
Solar/Wind Harmer
13.008
958171AF2-111 GEN
Solar/Wind Harmer
24.127
25196008MFTGT1
Adder
1.283
972167AH1-666 GEN
Solar/Wind Harmer
7.267
972173AH1-669 GEN
Solar/Wind Harmer
4.53
253406AD2-031_GEN
Solar/Wind Harmer
1.135
270273AD2-016 GEN
Solar/Wind Harmer
2.312
253415AE1-040 GEN
Solar/Wind Harmer
0.949
253303V4-073 C
Solar/Wind Harmer
0.092
253370AE2-315 SEC1
Adder
1.59
253371AE2-315 SEC2
Adder
1.504
270222AC2-111 GEN
Solar/Wind Harmer
6.424
3429391JKCT 9G
Adder
6.225
270356AE2-297 GEN
Solar/Wind Harmer
3.136
970093AG2-073 GEN
Solar/Wind Harmer
6.785
966571AG1-526 GEN
Solar/Wind Harmer
14.46
270437AC2-090 C
Solar/Wind Harmer
3.61
253338AC1-165 GEN
Solar/Wind Harmer
0.67
253333AC1-068 GEN
Solar/Wind Harmer
0.647
24728705AND G3
Adder
4.843
24728505AND G1
Adder
2.316
958821AF2-173 GEN
Solar/Wind Harmer
8.255
270004AE1-209 GEN
Solar/Wind Harmer
3.222
946031AF1-268 GEN
Solar/Wind Harmer
4.852
962031AG1-047 GEN
Solar/Wind Harmer
1.696
957741AF2-068 GEN
Solar/Wind Harmer
8.417
970289AG2-191 GEN
Solar/Wind Harmer
0.402
970291AG2-192 GEN
Solar/Wind Harmer
0.366
247642Z2-115 C
Solar/Wind Harmer
0.033
971617AH1-308 GEN
Solar/Wind Harmer
2.954
960741AF2-365 GEN
Solar/Wind Harmer
2.538
970243AG2-164 GEN
Solar/Wind Harmer
13.049
970519AG2-331 GEN
Solar/Wind Harmer
8.767
970699AG2-449 GEN
Solar/Wind Harmer
5.799
972273AH1-721 GEN
Adder
41.309
970193AG2-126 GEN
Solar/Wind Harmer
7.36
970273AG2-179 GEN
Solar/Wind Harmer
1.875
339250AF1-203 GEN
Solar/Wind Harmer
0.284
962251AG1-071 GEN
Solar/Wind Harmer
2.573
970605AG2-385 GEN
Solar/Wind Harmer
2.523
971155AH1-034 GEN
Solar/Wind Harmer
4.659
944531AF1-118 GEN
Solar/Wind Harmer
16.107
235780M24_1
Solar/Wind Helper
0.926
252516AE2-318_GEN
Solar/Wind Harmer
4.838
25194408D.CRK1
Adder
7.607
25194508D.CRK3
Adder
1.422
253317AC1-085 GEN4
Solar/Wind Harmer
8.382
253394AE2-221_GEN
Solar/Wind Harmer
4.278
253398AE2-221_GEN2
Solar/Wind Harmer
4.278
270186AC1-089 GEN
Solar/Wind Harmer
5.345
962581AG1-107 GEN
Solar/Wind Harmer
4.348
961491AF2-440 GEN
Solar/Wind Harmer
1.807
970235AG2-159 GEN
Solar/Wind Harmer
3.391
970235AG2-159 GEN
Solar/Wind Harmer
2.07
339221AD2-048_GEN
Solar/Wind Harmer
1.288
972043AH1-570 GEN
Solar/Wind Harmer
2.042
972045AH1-571 GEN
Solar/Wind Harmer
1.634
253370AE2-315 SEC1
Adder
1.59
971125AH1-004 GEN
Solar/Wind Harmer
3.171
970107AG2-081 GEN
Solar/Wind Harmer
2.378
25322209TAIT E
Adder
7.474
25322209TAIT E
Adder
7.306
25326109MON D
Adder
0.983
24728805RICHG1
Adder
2.726
24728905RICHG2
Adder
2.726
942891AE2-308 GEN
Solar/Wind Harmer
7.111
960161AF2-307 GEN
Solar/Wind Harmer
4.331
24379505HDWTR1G C
Solar/Wind Harmer
5.113
270209AC1-174_GEN
Solar/Wind Harmer
3.609
926881AC1-175 GEN
Solar/Wind Harmer
3.609
270383AD1-128 GEN
Solar/Wind Harmer
3.893
970883AG2-550 GEN
Solar/Wind Harmer
6.188
970885AG2-551 GEN
Solar/Wind Harmer
1.439
964571AG1-320 GEN
Solar/Wind Harmer
4.907
970825AG2-519 GEN
Solar/Wind Harmer
6.148
960441AF2-335 GEN
Solar/Wind Harmer
5.788
247621Y3-024
Adder
0.139
970653AG2-424 GEN
Solar/Wind Harmer
2.78
970653AG2-424 GEN
Solar/Wind Harmer
1.005
964611AG1-324 GEN
Solar/Wind Harmer
0.667
964611AG1-324 GEN
Solar/Wind Harmer
0.296
270201AC2-176 GEN
Solar/Wind Harmer
2.885
270518AE2-148 GEN
Solar/Wind Harmer
6.747
270599AE1-208 GEN
Solar/Wind Harmer
4.424
270031AE2-169
Solar/Wind Harmer
4.424
971081AG2-670 GEN
Solar/Wind Harmer
3.951
25326509SID D
Adder
0.691
270444AC2-157 GEN1
Solar/Wind Harmer
2.831
944541AF1-119 GEN
Solar/Wind Harmer
2.123
960971AF2-388 GEN
Solar/Wind Harmer
5.54
970239AG2-162 GEN
Solar/Wind Harmer
5.558
339236AF1-050_GEN
Solar/Wind Harmer
0.916
945391AF1-204 GEN
Solar/Wind Harmer
6.838
253378AE2-206_GEN
Solar/Wind Harmer
1.747
276820AF1-078_GEN
Solar/Wind Harmer
0.776
339231AF1-038_GEN
Solar/Wind Harmer
0.875
942221AE2-234 GEN
Solar/Wind Harmer
0.349
339255AE2-071 GEN
Solar/Wind Harmer
0.496
970077AG2-063 GEN
Solar/Wind Harmer
2.523
964781AG1-341 GEN
Solar/Wind Harmer
4.942
970241AG2-163 GEN
Solar/Wind Harmer
11.476
237033AB1-150 GEN
Solar/Wind Helper
0.373
3429211JKCT 2G
Adder
8.48
270432AC2-029 GEN
Solar/Wind Harmer
4.791
971673AH1-337 GEN
Solar/Wind Harmer
3.016
241972AD1-140 GEN
Solar/Wind Harmer
2.901
270240V3-007_GEN2
Solar/Wind Harmer
4.001
971029AG2-637 GEN
Solar/Wind Harmer
9.695
339211AE2-254 GEN
Solar/Wind Harmer
0.945
270543AE2-219 C
Solar/Wind Harmer
3.168
970455AG2-298 GEN
Solar/Wind Harmer
3.705
970115AG2-085 GEN
Solar/Wind Harmer
2.315
24725505WLD G2 C
Solar/Wind Harmer
2.245
24699105WLD G1 C
Solar/Wind Harmer
2.218
961761AG1-017 GEN
Solar/Wind Harmer
0.24
270594AE1-207 GEN
Solar/Wind Harmer
7.932
945581AF1-223 GEN
Solar/Wind Harmer
2.447
965401AG1-405 GEN
Solar/Wind Harmer
3.049
965411AG1-406 GEN
Solar/Wind Harmer
1.368
965461AG1-414 GEN
Solar/Wind Harmer
1.189
970289AG2-191 GEN
Solar/Wind Harmer
0.996
965101AG1-375 GEN
Solar/Wind Harmer
5.181
270024AE2-089 GEN
Solar/Wind Harmer
2.385
958711AF2-162 GEN
Solar/Wind Harmer
0.513
270156DARBY CT1
Adder
4.404
270157DARBY CT2
Adder
4.393
270158DARBY CT3
Adder
4.323
24729505KEY G4
Adder
3.066
945631AF1-228 GEN
Solar/Wind Harmer
2.201
963841AG1-237 GEN
Solar/Wind Harmer
4.916
270330AC1-082 GEN2
Solar/Wind Helper
0.041
270329AC1-082 GEN1
Solar/Wind Helper
0.2
24386205FR-12G C
Solar/Wind Harmer
0.715
24386405FR-21G C
Solar/Wind Harmer
0.718
24386605FR-22G C
Solar/Wind Harmer
0.718
24387005FR-3G C
Solar/Wind Harmer
0.66
944201AF1-088_MTX
Adder
58.943
957141AF2-008_MTX
Adder
29.471
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.025
CBM West 1LTFEXP_CBM-W1->PJM
CBM
58.337
CBM South 1LTFEXP_CBM-S1->PJM
CBM
13.278
MECLTFEXP_MEC->PJM
CLTF
6.349
SIGELTFEXP_SIGE->PJM
CLTF
0.299
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.298
LAGNLTFEXP_LAGN->PJM
CLTF
5.654
TVALTFEXP_TVA->PJM
CLTF
2.763
NYPJM->LTFIMP_NY
CLTF
1.454
LGEELTFEXP_LGEE->PJM
CLTF
4.843
WECLTFEXP_WEC->PJM
CLTF
1.446
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.234
AG2-052LTFEXP_AG2-052->PJM
LTF
0.093
AH1-155LTFEXP_AH1-155->PJM
LTF
0.14

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#6189_05HANG R 765_D1_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6189_05HANG R 765_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.42 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1731.23
MW Contribution:6.42
Bus #Bus NameTypeMW Contribution
25016408BKJDB1
50/50
0.314
25196108MFTGT2
Adder
1.553
25196108MFTGT2
Adder
1.442
252524AE2-267 GEN
Solar/Wind Harmer
1.576
25196408WSDLE3
Adder
8.818
25196308WSDLE2
Adder
8.742
25196208WSDLE1
Adder
8.72
25196708WSDLE6
Adder
8.698
25196508WSDLE4
Adder
8.479
971985AH1-537 GEN
Solar/Wind Harmer
17.666
944031AF1-071 GEN
Solar/Wind Harmer
0.792
270240V3-007_GEN2
Solar/Wind Harmer
4.445
971673AH1-337 GEN
Solar/Wind Harmer
3.08
971029AG2-637 GEN
Solar/Wind Harmer
9.944
270543AE2-219 C
Solar/Wind Harmer
3.289
970115AG2-085 GEN
Solar/Wind Harmer
2.56
24725505WLD G2 C
Solar/Wind Harmer
2.539
24699105WLD G1 C
Solar/Wind Harmer
2.509
270594AE1-207 GEN
Solar/Wind Harmer
9.028
253349AC2-067 GEN
Solar/Wind Harmer
3.02
253400AC2-068 GEN
Solar/Wind Harmer
1.214
965461AG1-414 GEN
Solar/Wind Harmer
1.368
970289AG2-191 GEN
Solar/Wind Harmer
1.147
945581AF1-223 GEN
Solar/Wind Harmer
2.728
961761AG1-017 GEN
Solar/Wind Harmer
0.256
339243AC2-075 GEN1
Solar/Wind Harmer
0.268
25306009OHH W.
Adder
1.694
253372AE2-315 SEC3
Adder
1.105
253372AE2-315 SEC3
Adder
1.105
965101AG1-375 GEN
Solar/Wind Harmer
5.783
970455AG2-298 GEN
Solar/Wind Harmer
3.424
958711AF2-162 GEN
Solar/Wind Harmer
0.573
963841AG1-237 GEN
Solar/Wind Harmer
6.011
270024AE2-089 GEN
Solar/Wind Harmer
2.562
24386205FR-12G C
Solar/Wind Harmer
2.319
24386405FR-21G C
Solar/Wind Harmer
2.327
24386605FR-22G C
Solar/Wind Harmer
2.327
24387005FR-3G C
Solar/Wind Harmer
2.141
24729505KEY G4
Adder
3.433
24690905MDL-1G C
Solar/Wind Harmer
4.237
25196008MFTGT1
Adder
1.364
25196608WSDLE5
Adder
8.567
25194608D.CRK4
Adder
1.618
252510AF1-249 C
Solar/Wind Harmer
0.399
270222AC2-111 GEN
Solar/Wind Harmer
6.429
270356AE2-297 GEN
Solar/Wind Harmer
3.466
970243AG2-164 GEN
Solar/Wind Harmer
18.655
970519AG2-331 GEN
Solar/Wind Harmer
12.533
25194408D.CRK1
Adder
7.445
25194508D.CRK3
Adder
1.392
252509AD1-136 GEN
Solar/Wind Harmer
0.247
252519AF1-045_GEN
Solar/Wind Harmer
5.249
25196008MFTGT1
Adder
1.408
25194608D.CRK4
Adder
1.618
252507AC2-088 GEN
Solar/Wind Harmer
1.731
25196808ZIMRHP
Adder
61.966
970091AG2-072 GEN
Adder
56.238
970333AG2-219 GEN
Solar/Wind Harmer
22.8
942081AE2-220 GEN
Solar/Wind Harmer
4.594
270239V3-007_GEN1
Solar/Wind Harmer
1.236
24728605AND G2
Adder
2.599
270005AE1-210 C O1
Solar/Wind Harmer
3.583
965031AG1-367 GEN
Solar/Wind Harmer
6.555
970825AG2-519 GEN
Solar/Wind Harmer
1.514
270445AC2-157 GEN2
Solar/Wind Harmer
3.557
276903AD2-071 C
Solar/Wind Harmer
6.281
247536S-71 GEN
Solar/Wind Harmer
2.52
270032AE2-172
Solar/Wind Harmer
2.857
970291AG2-192 GEN
Solar/Wind Harmer
0.784
971565AH1-281 GEN
Solar/Wind Harmer
1.205
945371AF1-202 GEN
Solar/Wind Harmer
4.196
339216AC1-074 GEN
Solar/Wind Harmer
0.989
960071AF2-298 GEN
Solar/Wind Harmer
2.911
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.105
25326309TAIT D
Adder
0.635
958861AF2-177 GEN
Solar/Wind Harmer
6.32
965651AG1-433 GEN
Solar/Wind Harmer
3.094
963741AG1-226 GEN
Solar/Wind Harmer
25.125
24385905FR-11G C
Solar/Wind Harmer
4.498
24387305FR-4G C
Solar/Wind Harmer
2.75
24791305MDL-5G
Solar/Wind Harmer
1.272
940581AE2-045 GEN
Solar/Wind Harmer
5.167
971605AH1-302 GEN
Solar/Wind Harmer
4.418
965911AG1-460 GEN
Solar/Wind Harmer
0.698
943111AE2-339 GEN
Solar/Wind Harmer
0.442
276615X2-022 GEN
Solar/Wind Harmer
0.974
274880W4-005 GEN4
Solar/Wind Harmer
1.501
963831AG1-236 GEN
Solar/Wind Harmer
4.882
964861AG1-349 GEN
Solar/Wind Harmer
3.873
971917AH1-482 GEN
Solar/Wind Harmer
4.469
958381AF2-132 GEN
Solar/Wind Harmer
4.46
972175AH1-670 GEN
Solar/Wind Harmer
6.696
274854TWINGROVE;U2
Solar/Wind Harmer
3.408
270055AF2-134 C O1
Solar/Wind Harmer
1.456
3429421JKCT 10G
Adder
3.867
3429241JKCT 3G
Adder
5.42
274732ELWOOD EC;7P
Adder
7.386
274674JOLIET 9 ;6U
Adder
6.909
274801UNIV PARK;4U
Adder
2.612
274676JOLIET 29;8U
Adder
13.743
274745AC1-111 GEN9
Adder
2.501
274812UNIV PK N;8U
Adder
2.239
274773LINCOLN ;4U
Adder
3.769
274774LINCOLN ;5U
Adder
3.769
927014AC1-188 GEN
Solar/Wind Helper
0.882
270263AC1-001 GEN
Solar/Wind Helper
0.627
270331AC1-082 GEN3
Solar/Wind Helper
0.1
960001AF2-291 GEN
Solar/Wind Helper
0.556
276726Z2-087_GEN
Solar/Wind Harmer
1.849
270180AB1-006 GEN1
Solar/Wind Harmer
3.795
946581AF1-322 GEN
Solar/Wind Harmer
5.399
24691005MDL-2G C
Solar/Wind Harmer
1.952
24697605MDL-3G C
Solar/Wind Harmer
1.946
24697905MDL-4G C
Solar/Wind Harmer
1.211
270181AB1-006 GEN2
Solar/Wind Harmer
0.377
944221AF1-090 GEN
Solar/Wind Harmer
5.552
958391AF2-133 GEN
Solar/Wind Harmer
4.51
276785W4-005 GEN1
Solar/Wind Harmer
1.501
276174W4-005 GEN2
Solar/Wind Harmer
1.501
276849AB2-070 GEN2
Solar/Wind Harmer
1.115
276848AB2-070 GEN3
Solar/Wind Harmer
1.115
270536AF1-215 GEN2
Solar/Wind Harmer
2.185
276655WTG1_EQ
Solar/Wind Harmer
4.19
3429211JKCT 2G
Adder
5.349
274731ELWOOD EC;2P
Adder
7.387
274733ELWOOD EC;3P
Adder
7.387
274735ELWOOD EC;4P
Adder
7.387
274728ELWOOD EC;5P
Adder
7.386
972227AH1-698 GEN1
Adder
1.172
274675JOLIET 29;7U
Adder
13.743
274675JOLIET 29;7U
Adder
13.252
972037AH1-567 GEN1
Adder
0.082
274687WILL CNTY;4U
Adder
12.515
274687WILL CNTY;4U
Adder
12.515
274827FISK ;RP
Adder
3.472
274746AC1-111 G10
Adder
2.501
274744AC1-111 GEN8
Adder
2.501
274814UNIV PK N;0U
Adder
2.259
274807UNIV PK N;3U
Adder
2.254
274805UNIV PK N;1U
Adder
2.244
274811UNIV PK N;7U
Adder
2.239
274775LINCOLN ;6U
Adder
3.769
274776LINCOLN ;7U
Adder
3.769
274777LINCOLN ;8U
Adder
1.5
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.1
970699AG2-449 GEN
Solar/Wind Harmer
8.291
270437AC2-090 C
Solar/Wind Harmer
4.012
24728705AND G3
Adder
5.435
24728505AND G1
Adder
2.599
958821AF2-173 GEN
Solar/Wind Harmer
9.177
270004AE1-209 GEN
Solar/Wind Harmer
3.583
946031AF1-268 GEN
Solar/Wind Harmer
5.309
970289AG2-191 GEN
Solar/Wind Harmer
0.463
970291AG2-192 GEN
Solar/Wind Harmer
0.421
962031AG1-047 GEN
Solar/Wind Harmer
1.809
957741AF2-068 GEN
Solar/Wind Harmer
8.978
247642Z2-115 C
Solar/Wind Harmer
0.038
970193AG2-126 GEN
Solar/Wind Harmer
8.804
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.168
253371AE2-315 SEC2
Adder
1.105
971617AH1-308 GEN
Solar/Wind Harmer
3.173
24755605MDL-5G
Solar/Wind Harmer
1.272
970781AG2-491 GEN
Solar/Wind Harmer
5.276
944531AF1-118 GEN
Solar/Wind Harmer
18.052
959141AF2-205 GEN
Solar/Wind Harmer
3.031
942481AE2-261 GEN
Solar/Wind Harmer
14.959
276621W2-048 GEN
Solar/Wind Harmer
3.102
276838X2-022 GEN2
Solar/Wind Harmer
0.116
276686W4-005 GEN3
Solar/Wind Harmer
1.501
971993AH1-541 GEN
Solar/Wind Harmer
4.586
276668AB2-070 GEN1
Solar/Wind Harmer
1.115
964401AG1-302 GEN
Solar/Wind Harmer
4.46
966571AG1-526 GEN
Solar/Wind Harmer
10.766
274853TWINGROVE;U1
Solar/Wind Harmer
3.481
965091AG1-374 GEN
Solar/Wind Harmer
14.491
959611AF2-252 GEN
Solar/Wind Harmer
1.123
270535AF1-215 GEN1
Solar/Wind Harmer
2.185
3429391JKCT 9G
Adder
3.867
274729ELWOOD EC;1P
Adder
7.387
274730ELWOOD EC;6P
Adder
7.386
274734ELWOOD EC;8P
Adder
7.386
274736ELWOOD EC;9P
Adder
7.386
972228AH1-698 GEN2
Adder
1.665
274800UNIV PARK;3U
Adder
2.612
972038AH1-567 GEN2
Adder
0.163
274676JOLIET 29;8U
Adder
13.252
274802UNIV PARK;5U
Adder
2.611
274826FISK ;BP
Adder
4.898
274772LINCOLN ;3U
Adder
3.769
957541AF2-048 GEN
Solar/Wind Helper
0.885
270273AD2-016 GEN
Solar/Wind Helper
1.46
252516AE2-318_GEN
Solar/Wind Harmer
4.004
970235AG2-159 GEN
Solar/Wind Harmer
3.379
970235AG2-159 GEN
Solar/Wind Harmer
2.062
24728805RICHG1
Adder
2.802
24728905RICHG2
Adder
2.802
970239AG2-162 GEN
Solar/Wind Harmer
7.946
24379505HDWTR1G C
Solar/Wind Harmer
5.682
270209AC1-174_GEN
Solar/Wind Harmer
4.01
926881AC1-175 GEN
Solar/Wind Harmer
4.01
25183208HLCRTG
Solar/Wind Harmer
4.17
270383AD1-128 GEN
Solar/Wind Harmer
4.168
970825AG2-519 GEN
Solar/Wind Harmer
6.785
970883AG2-550 GEN
Solar/Wind Harmer
6.422
970885AG2-551 GEN
Solar/Wind Harmer
1.494
960441AF2-335 GEN
Solar/Wind Harmer
6.4
270444AC2-157 GEN1
Solar/Wind Harmer
3.557
247621Y3-024
Adder
0.147
964611AG1-324 GEN
Solar/Wind Harmer
0.716
964611AG1-324 GEN
Solar/Wind Harmer
0.318
270599AE1-208 GEN
Solar/Wind Harmer
4.914
270031AE2-169
Solar/Wind Harmer
4.914
270201AC2-176 GEN
Solar/Wind Harmer
3.077
945391AF1-204 GEN
Solar/Wind Harmer
8.18
964571AG1-320 GEN
Solar/Wind Harmer
4.801
253370AE2-315 SEC1
Adder
1.168
25322209TAIT E
Adder
5.656
25322209TAIT E
Adder
5.529
944541AF1-119 GEN
Solar/Wind Harmer
2.371
960971AF2-388 GEN
Solar/Wind Harmer
6.188
25326109MON D
Adder
0.736
339221AD2-048_GEN
Solar/Wind Harmer
0.86
970241AG2-163 GEN
Solar/Wind Harmer
13.959
966841AG1-555 GEN
Solar/Wind Harmer
1.358
970653AG2-424 GEN
Solar/Wind Harmer
2.609
970653AG2-424 GEN
Solar/Wind Harmer
0.943
942221AE2-234 GEN
Solar/Wind Harmer
0.385
971125AH1-004 GEN
Solar/Wind Harmer
2.088
970107AG2-081 GEN
Solar/Wind Harmer
1.566
945421AF1-207 GEN
Solar/Wind Harmer
7.319
957841AF2-078 GEN
Solar/Wind Harmer
3.149
972043AH1-570 GEN
Solar/Wind Harmer
1.297
972045AH1-571 GEN
Solar/Wind Harmer
1.038
276916AD2-100_GEN
Solar/Wind Harmer
10.542
276911AD2-131_GEN
Solar/Wind Harmer
2.131
957381AF2-032 GEN
Solar/Wind Harmer
0.209
276763AC1-053 GEN1
Solar/Wind Harmer
1.963
276764AC1-053 GEN2
Solar/Wind Harmer
1.963
960611AF2-352 GEN
Solar/Wind Harmer
1.123
274674JOLIET 9 ;6U
Adder
6.909
972259AH1-714 GEN
Adder
8.555
274803UNIV PARK;6U
Adder
2.611
274808UNIV PK N;4U
Adder
2.229
274695ROCKY RD ;2P
Adder
4.974
274693ROCKY RD ;1P
Adder
4.925
274697ROCKY RD ;3P
Adder
1.351
274696ROCKY RD ;4P
Adder
5.092
274770LINCOLN ;1U
Adder
3.769
274771LINCOLN ;2U
Adder
3.769
944201AF1-088_MTX
Adder
74.065
957141AF2-008_MTX
Adder
37.033
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.348
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.286
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.315
MECLTFEXP_MEC->PJM
CLTF
7.201
SIGELTFEXP_SIGE->PJM
CLTF
0.328
CBM West 2LTFEXP_CBM-W2->PJM
CBM
52.731
LAGNLTFEXP_LAGN->PJM
CLTF
5.235
TVALTFEXP_TVA->PJM
CLTF
2.34
NYPJM->LTFIMP_NY
CLTF
1.1
LGEELTFEXP_LGEE->PJM
CLTF
5.188
WECLTFEXP_WEC->PJM
CLTF
1.697
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.679
AG2-052LTFEXP_AG2-052->PJM
LTF
0.112
AH1-155LTFEXP_AH1-155->PJM
LTF
0.168

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P4_#709_05HANG R 765_D2_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#709_05HANG R 765_D2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.09 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1664.56
MW Contribution:6.46
Bus #Bus NameTypeMW Contribution
25016408BKJDB1
50/50
0.315
25196108MFTGT2
Adder
1.559
25196108MFTGT2
Adder
1.448
252524AE2-267 GEN
Solar/Wind Harmer
1.583
25196408WSDLE3
Adder
8.856
25196308WSDLE2
Adder
8.779
25196208WSDLE1
Adder
8.757
25196708WSDLE6
Adder
8.735
25196508WSDLE4
Adder
8.515
971985AH1-537 GEN
Solar/Wind Harmer
17.742
944031AF1-071 GEN
Solar/Wind Harmer
0.797
270240V3-007_GEN2
Solar/Wind Harmer
4.472
971673AH1-337 GEN
Solar/Wind Harmer
3.1
971029AG2-637 GEN
Solar/Wind Harmer
10.008
270543AE2-219 C
Solar/Wind Harmer
3.31
970115AG2-085 GEN
Solar/Wind Harmer
2.577
24725505WLD G2 C
Solar/Wind Harmer
2.556
24699105WLD G1 C
Solar/Wind Harmer
2.526
270594AE1-207 GEN
Solar/Wind Harmer
9.091
253349AC2-067 GEN
Solar/Wind Harmer
3.041
253400AC2-068 GEN
Solar/Wind Harmer
1.223
965461AG1-414 GEN
Solar/Wind Harmer
1.378
970289AG2-191 GEN
Solar/Wind Harmer
1.155
945581AF1-223 GEN
Solar/Wind Harmer
2.747
961761AG1-017 GEN
Solar/Wind Harmer
0.258
339243AC2-075 GEN1
Solar/Wind Harmer
0.27
25306009OHH W.
Adder
1.706
253372AE2-315 SEC3
Adder
1.113
253372AE2-315 SEC3
Adder
1.113
965101AG1-375 GEN
Solar/Wind Harmer
5.825
970455AG2-298 GEN
Solar/Wind Harmer
3.45
958711AF2-162 GEN
Solar/Wind Harmer
0.577
963841AG1-237 GEN
Solar/Wind Harmer
6.058
270024AE2-089 GEN
Solar/Wind Harmer
2.582
24386205FR-12G C
Solar/Wind Harmer
2.337
24386405FR-21G C
Solar/Wind Harmer
2.346
24386605FR-22G C
Solar/Wind Harmer
2.346
24387005FR-3G C
Solar/Wind Harmer
2.158
24729505KEY G4
Adder
3.46
24690905MDL-1G C
Solar/Wind Harmer
4.271
270180AB1-006 GEN1
Solar/Wind Harmer
3.826
946581AF1-322 GEN
Solar/Wind Harmer
5.443
24691005MDL-2G C
Solar/Wind Harmer
1.967
24697605MDL-3G C
Solar/Wind Harmer
1.961
24697905MDL-4G C
Solar/Wind Harmer
1.221
270181AB1-006 GEN2
Solar/Wind Harmer
0.38
944221AF1-090 GEN
Solar/Wind Harmer
5.598
958391AF2-133 GEN
Solar/Wind Harmer
4.549
276785W4-005 GEN1
Solar/Wind Harmer
1.514
276174W4-005 GEN2
Solar/Wind Harmer
1.514
276849AB2-070 GEN2
Solar/Wind Harmer
1.125
276848AB2-070 GEN3
Solar/Wind Harmer
1.125
270536AF1-215 GEN2
Solar/Wind Harmer
2.204
276655WTG1_EQ
Solar/Wind Harmer
4.228
3429211JKCT 2G
Adder
5.399
274731ELWOOD EC;2P
Adder
7.457
274733ELWOOD EC;3P
Adder
7.457
274735ELWOOD EC;4P
Adder
7.457
972227AH1-698 GEN1
Adder
1.183
274728ELWOOD EC;5P
Adder
7.457
274675JOLIET 29;7U
Adder
13.874
274675JOLIET 29;7U
Adder
13.378
274687WILL CNTY;4U
Adder
12.634
274687WILL CNTY;4U
Adder
12.634
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.505
274746AC1-111 G10
Adder
2.525
274744AC1-111 GEN8
Adder
2.525
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.261
274775LINCOLN ;6U
Adder
3.805
274776LINCOLN ;7U
Adder
3.805
274777LINCOLN ;8U
Adder
1.515
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.099
25194408D.CRK1
Adder
7.477
25194508D.CRK3
Adder
1.398
252509AD1-136 GEN
Solar/Wind Harmer
0.248
252519AF1-045_GEN
Solar/Wind Harmer
5.274
252516AE2-318_GEN
Solar/Wind Harmer
4.023
970235AG2-159 GEN
Solar/Wind Harmer
3.396
970235AG2-159 GEN
Solar/Wind Harmer
2.073
24728805RICHG1
Adder
2.818
24728905RICHG2
Adder
2.818
970239AG2-162 GEN
Solar/Wind Harmer
7.992
24379505HDWTR1G C
Solar/Wind Harmer
5.715
270209AC1-174_GEN
Solar/Wind Harmer
4.034
926881AC1-175 GEN
Solar/Wind Harmer
4.034
25183208HLCRTG
Solar/Wind Harmer
4.196
270383AD1-128 GEN
Solar/Wind Harmer
4.194
970825AG2-519 GEN
Solar/Wind Harmer
6.83
970883AG2-550 GEN
Solar/Wind Harmer
6.465
970885AG2-551 GEN
Solar/Wind Harmer
1.503
960441AF2-335 GEN
Solar/Wind Harmer
6.443
270444AC2-157 GEN1
Solar/Wind Harmer
3.581
247621Y3-024
Adder
0.148
964611AG1-324 GEN
Solar/Wind Harmer
0.721
964611AG1-324 GEN
Solar/Wind Harmer
0.32
270599AE1-208 GEN
Solar/Wind Harmer
4.948
270031AE2-169
Solar/Wind Harmer
4.948
270201AC2-176 GEN
Solar/Wind Harmer
3.099
945391AF1-204 GEN
Solar/Wind Harmer
8.239
964571AG1-320 GEN
Solar/Wind Harmer
4.836
253370AE2-315 SEC1
Adder
1.177
25322209TAIT E
Adder
5.698
25322209TAIT E
Adder
5.57
944541AF1-119 GEN
Solar/Wind Harmer
2.389
960971AF2-388 GEN
Solar/Wind Harmer
6.235
25326109MON D
Adder
0.742
339221AD2-048_GEN
Solar/Wind Harmer
0.867
970241AG2-163 GEN
Solar/Wind Harmer
14.065
966841AG1-555 GEN
Solar/Wind Harmer
1.368
970653AG2-424 GEN
Solar/Wind Harmer
2.629
970653AG2-424 GEN
Solar/Wind Harmer
0.95
942221AE2-234 GEN
Solar/Wind Harmer
0.388
971125AH1-004 GEN
Solar/Wind Harmer
2.105
970107AG2-081 GEN
Solar/Wind Harmer
1.579
945421AF1-207 GEN
Solar/Wind Harmer
7.378
957841AF2-078 GEN
Solar/Wind Harmer
3.175
972043AH1-570 GEN
Solar/Wind Harmer
1.308
972045AH1-571 GEN
Solar/Wind Harmer
1.046
276916AD2-100_GEN
Solar/Wind Harmer
10.632
276911AD2-131_GEN
Solar/Wind Harmer
2.149
957381AF2-032 GEN
Solar/Wind Harmer
0.211
276763AC1-053 GEN1
Solar/Wind Harmer
1.979
276764AC1-053 GEN2
Solar/Wind Harmer
1.979
960611AF2-352 GEN
Solar/Wind Harmer
1.133
274674JOLIET 9 ;6U
Adder
6.975
972259AH1-714 GEN
Adder
8.636
274803UNIV PARK;6U
Adder
2.636
274808UNIV PK N;4U
Adder
2.251
274696ROCKY RD ;4P
Adder
5.14
274695ROCKY RD ;2P
Adder
5.022
274693ROCKY RD ;1P
Adder
4.972
274697ROCKY RD ;3P
Adder
1.364
274770LINCOLN ;1U
Adder
3.805
274771LINCOLN ;2U
Adder
3.805
25196008MFTGT1
Adder
1.37
25196608WSDLE5
Adder
8.603
25194608D.CRK4
Adder
1.625
252510AF1-249 C
Solar/Wind Harmer
0.4
270222AC2-111 GEN
Solar/Wind Harmer
6.463
270356AE2-297 GEN
Solar/Wind Harmer
3.485
970243AG2-164 GEN
Solar/Wind Harmer
18.765
970519AG2-331 GEN
Solar/Wind Harmer
12.607
970699AG2-449 GEN
Solar/Wind Harmer
8.34
270437AC2-090 C
Solar/Wind Harmer
4.035
24728705AND G3
Adder
5.469
24728505AND G1
Adder
2.615
958821AF2-173 GEN
Solar/Wind Harmer
9.237
270004AE1-209 GEN
Solar/Wind Harmer
3.606
946031AF1-268 GEN
Solar/Wind Harmer
5.344
970289AG2-191 GEN
Solar/Wind Harmer
0.466
970291AG2-192 GEN
Solar/Wind Harmer
0.424
962031AG1-047 GEN
Solar/Wind Harmer
1.822
957741AF2-068 GEN
Solar/Wind Harmer
9.042
247642Z2-115 C
Solar/Wind Harmer
0.038
970193AG2-126 GEN
Solar/Wind Harmer
8.868
253303V4-073 C
Solar/Wind Harmer
0.068
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
971617AH1-308 GEN
Solar/Wind Harmer
3.198
24755605MDL-5G
Solar/Wind Harmer
1.283
970781AG2-491 GEN
Solar/Wind Harmer
5.319
944531AF1-118 GEN
Solar/Wind Harmer
18.201
959141AF2-205 GEN
Solar/Wind Harmer
3.057
942481AE2-261 GEN
Solar/Wind Harmer
15.086
276621W2-048 GEN
Solar/Wind Harmer
3.128
276838X2-022 GEN2
Solar/Wind Harmer
0.117
276686W4-005 GEN3
Solar/Wind Harmer
1.514
971993AH1-541 GEN
Solar/Wind Harmer
4.625
276668AB2-070 GEN1
Solar/Wind Harmer
1.125
964401AG1-302 GEN
Solar/Wind Harmer
4.498
966571AG1-526 GEN
Solar/Wind Harmer
10.861
274853TWINGROVE;U1
Solar/Wind Harmer
3.512
965091AG1-374 GEN
Solar/Wind Harmer
14.619
959611AF2-252 GEN
Solar/Wind Harmer
1.133
270535AF1-215 GEN1
Solar/Wind Harmer
2.204
3429391JKCT 9G
Adder
3.902
274729ELWOOD EC;1P
Adder
7.457
972228AH1-698 GEN2
Adder
1.68
274730ELWOOD EC;6P
Adder
7.457
274734ELWOOD EC;8P
Adder
7.457
274736ELWOOD EC;9P
Adder
7.457
274800UNIV PARK;3U
Adder
2.637
972038AH1-567 GEN2
Adder
0.165
274676JOLIET 29;8U
Adder
13.378
274802UNIV PARK;5U
Adder
2.636
274826FISK ;BP
Adder
4.945
274772LINCOLN ;3U
Adder
3.805
957541AF2-048 GEN
Solar/Wind Helper
0.879
270273AD2-016 GEN
Solar/Wind Helper
1.449
25196008MFTGT1
Adder
1.414
25194608D.CRK4
Adder
1.625
252507AC2-088 GEN
Solar/Wind Harmer
1.738
25196808ZIMRHP
Adder
62.29
970091AG2-072 GEN
Adder
56.565
970333AG2-219 GEN
Solar/Wind Harmer
22.935
942081AE2-220 GEN
Solar/Wind Harmer
4.621
270239V3-007_GEN1
Solar/Wind Harmer
1.244
24728605AND G2
Adder
2.615
270005AE1-210 C O1
Solar/Wind Harmer
3.606
965031AG1-367 GEN
Solar/Wind Harmer
6.598
970825AG2-519 GEN
Solar/Wind Harmer
1.524
270445AC2-157 GEN2
Solar/Wind Harmer
3.581
276903AD2-071 C
Solar/Wind Harmer
6.323
247536S-71 GEN
Solar/Wind Harmer
2.537
270032AE2-172
Solar/Wind Harmer
2.877
970291AG2-192 GEN
Solar/Wind Harmer
0.79
971565AH1-281 GEN
Solar/Wind Harmer
1.214
945371AF1-202 GEN
Solar/Wind Harmer
4.226
339216AC1-074 GEN
Solar/Wind Harmer
0.996
960071AF2-298 GEN
Solar/Wind Harmer
2.932
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
25326309TAIT D
Adder
0.64
958861AF2-177 GEN
Solar/Wind Harmer
6.367
965651AG1-433 GEN
Solar/Wind Harmer
3.117
963741AG1-226 GEN
Solar/Wind Harmer
25.317
24385905FR-11G C
Solar/Wind Harmer
4.533
24387305FR-4G C
Solar/Wind Harmer
2.771
24791305MDL-5G
Solar/Wind Harmer
1.283
940581AE2-045 GEN
Solar/Wind Harmer
5.21
971605AH1-302 GEN
Solar/Wind Harmer
4.455
965911AG1-460 GEN
Solar/Wind Harmer
0.704
943111AE2-339 GEN
Solar/Wind Harmer
0.446
276615X2-022 GEN
Solar/Wind Harmer
0.982
274880W4-005 GEN4
Solar/Wind Harmer
1.514
963831AG1-236 GEN
Solar/Wind Harmer
4.924
964861AG1-349 GEN
Solar/Wind Harmer
3.906
971917AH1-482 GEN
Solar/Wind Harmer
4.508
958381AF2-132 GEN
Solar/Wind Harmer
4.498
972175AH1-670 GEN
Solar/Wind Harmer
6.754
274854TWINGROVE;U2
Solar/Wind Harmer
3.439
270055AF2-134 C O1
Solar/Wind Harmer
1.469
3429421JKCT 10G
Adder
3.902
3429241JKCT 3G
Adder
5.47
274732ELWOOD EC;7P
Adder
7.457
274674JOLIET 9 ;6U
Adder
6.975
274801UNIV PARK;4U
Adder
2.637
274676JOLIET 29;8U
Adder
13.874
274745AC1-111 GEN9
Adder
2.525
274812UNIV PK N;8U
Adder
2.261
274773LINCOLN ;4U
Adder
3.805
274774LINCOLN ;5U
Adder
3.805
927014AC1-188 GEN
Solar/Wind Helper
0.876
270263AC1-001 GEN
Solar/Wind Helper
0.622
270331AC1-082 GEN3
Solar/Wind Helper
0.099
960001AF2-291 GEN
Solar/Wind Helper
0.551
276726Z2-087_GEN
Solar/Wind Harmer
1.865
944201AF1-088_MTX
Adder
74.561
957141AF2-008_MTX
Adder
37.28
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.478
MECLTFEXP_MEC->PJM
CLTF
7.273
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.307
LAGNLTFEXP_LAGN->PJM
CLTF
5.322
TVALTFEXP_TVA->PJM
CLTF
2.383
NYPJM->LTFIMP_NY
CLTF
1.072
LGEELTFEXP_LGEE->PJM
CLTF
5.218
WECLTFEXP_WEC->PJM
CLTF
1.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.651
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169

Details for 06PIERCE-05MARQUI 345.0 kV Ckt 1 line l/o AEP_P1-2_#709_546_SRT-A


Base Case Flowgate

Area:AEP/OVEC
Facility Description:
06PIERCE-05MARQUI 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#709_546_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:101.36 %
Rating:1540.0 MVA
Rating Type:B
MVA to Mitigate:1561.02
MW Contribution:4.51
Bus #Bus NameTypeMW Contribution
25194408D.CRK1
Adder
7.477
25194508D.CRK3
Adder
1.398
252509AD1-136 GEN
Solar/Wind Harmer
0.034
252519AF1-045_GEN
Solar/Wind Harmer
5.274
252516AE2-318_GEN
Solar/Wind Harmer
4.678
970235AG2-159 GEN
Solar/Wind Harmer
3.613
970235AG2-159 GEN
Solar/Wind Harmer
2.073
24728805RICHG1
Adder
2.818
24728905RICHG2
Adder
2.818
970239AG2-162 GEN
Solar/Wind Harmer
1.269
24379505HDWTR1G C
Solar/Wind Harmer
0.002
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.007
270383AD1-128 GEN
Solar/Wind Harmer
0.003
970825AG2-519 GEN
Solar/Wind Harmer
5.005
970883AG2-550 GEN
Solar/Wind Harmer
4.51
970885AG2-551 GEN
Solar/Wind Harmer
1.503
960441AF2-335 GEN
Solar/Wind Harmer
4.495
270444AC2-157 GEN1
Solar/Wind Harmer
0.002
971587AH1-292 GEN
Solar/Wind Harmer
3.281
971613AH1-306 GEN
Solar/Wind Harmer
2.071
247621Y3-024
Adder
0.148
964611AG1-324 GEN
Solar/Wind Harmer
0.32
270599AE1-208 GEN
Solar/Wind Harmer
3.883
270031AE2-169
Solar/Wind Harmer
2.33
270201AC2-176 GEN
Solar/Wind Harmer
0.001
945391AF1-204 GEN
Solar/Wind Harmer
4.382
964571AG1-320 GEN
Solar/Wind Harmer
3.758
253370AE2-315 SEC1
Adder
1.177
25322209TAIT E
Adder
5.698
25322209TAIT E
Adder
5.57
944541AF1-119 GEN
Solar/Wind Harmer
0.267
960971AF2-388 GEN
Solar/Wind Harmer
2.335
25326109MON D
Adder
0.742
339221AD2-048_GEN
Solar/Wind Harmer
0.002
970241AG2-163 GEN
Solar/Wind Harmer
2.29
966841AG1-555 GEN
Solar/Wind Harmer
0.43
970653AG2-424 GEN
Solar/Wind Harmer
1.834
970653AG2-424 GEN
Solar/Wind Harmer
0.95
25196008MFTGT1
Adder
1.414
25194608D.CRK4
Adder
1.625
252507AC2-088 GEN
Solar/Wind Harmer
0.307
25196808ZIMRHP
Adder
62.29
970773AG2-487 GEN
Solar/Wind Harmer
0.942
970091AG2-072 GEN
Adder
56.565
970333AG2-219 GEN
Solar/Wind Harmer
3.629
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.697
24728605AND G2
Adder
2.615
270005AE1-210 C O1
Solar/Wind Harmer
0.997
965031AG1-367 GEN
Solar/Wind Harmer
4.603
970825AG2-519 GEN
Solar/Wind Harmer
1.603
270445AC2-157 GEN2
Solar/Wind Harmer
0.002
276903AD2-071 C
Solar/Wind Harmer
4.926
25016408BKJDB1
50/50
0.315
25196108MFTGT2
Adder
1.559
25196108MFTGT2
Adder
1.448
252524AE2-267 GEN
Solar/Wind Harmer
0.003
25196408WSDLE3
Adder
8.856
25196308WSDLE2
Adder
8.779
25196208WSDLE1
Adder
8.757
25196708WSDLE6
Adder
8.735
25196008MFTGT1
Adder
1.37
25196608WSDLE5
Adder
8.603
25194608D.CRK4
Adder
1.625
252510AF1-249 C
Solar/Wind Harmer
0.052
270222AC2-111 GEN
Solar/Wind Harmer
2.803
270356AE2-297 GEN
Solar/Wind Harmer
0.007
970243AG2-164 GEN
Solar/Wind Harmer
2.969
970519AG2-331 GEN
Solar/Wind Harmer
13.197
970699AG2-449 GEN
Solar/Wind Harmer
1.269
270437AC2-090 C
Solar/Wind Harmer
0.002
24728705AND G3
Adder
5.469
24728505AND G1
Adder
2.615
958821AF2-173 GEN
Solar/Wind Harmer
6.444
270004AE1-209 GEN
Solar/Wind Harmer
0.997
946031AF1-268 GEN
Solar/Wind Harmer
4.275
970191AG2-125 GEN
Solar/Wind Harmer
1.095
970289AG2-191 GEN
Solar/Wind Harmer
0.466
970291AG2-192 GEN
Solar/Wind Harmer
0.424
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
6.308
247642Z2-115 C
Solar/Wind Harmer
0.002
970193AG2-126 GEN
Solar/Wind Harmer
6.187
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
971617AH1-308 GEN
Solar/Wind Harmer
3.198
24755605MDL-5G
Solar/Wind Harmer
0
970781AG2-491 GEN
Solar/Wind Harmer
3.711
944531AF1-118 GEN
Solar/Wind Harmer
16.26
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
942481AE2-261 GEN
Solar/Wind Harmer
10.525
276621W2-048 GEN
Solar/Wind Harmer
0.176
276838X2-022 GEN2
Solar/Wind Harmer
0.197
276686W4-005 GEN3
Solar/Wind Harmer
0
971993AH1-541 GEN
Solar/Wind Harmer
1.613
276668AB2-070 GEN1
Solar/Wind Harmer
0.127
964401AG1-302 GEN
Solar/Wind Harmer
0.001
966571AG1-526 GEN
Solar/Wind Harmer
7.577
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
965091AG1-374 GEN
Solar/Wind Harmer
10.199
959611AF2-252 GEN
Solar/Wind Harmer
1.133
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
942111AE2-223 GEN
Solar/Wind Harmer
1.098
970513AG2-328 GEN
Solar/Wind Harmer
1.448
970517AG2-330 GEN
Solar/Wind Harmer
8.688
960741AF2-365 GEN
Solar/Wind Harmer
1.664
3429391JKCT 9G
Adder
3.902
274878BISHOP HL;2U
Solar/Wind Harmer
0.108
970571AG2-364 GEN
Solar/Wind Harmer
6.41
276889AE2-281 GEN
Solar/Wind Harmer
0
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276897AD1-100 C
Solar/Wind Harmer
0.004
939351AE1-166 GEN
Solar/Wind Harmer
0
970093AG2-073 GEN
Solar/Wind Harmer
3.181
276694AA1-018 GEN2
Solar/Wind Harmer
0
276893AG1-478 C
Solar/Wind Harmer
0.125
274729ELWOOD EC;1P
Adder
7.457
972228AH1-698 GEN2
Adder
1.68
274730ELWOOD EC;6P
Adder
7.457
274734ELWOOD EC;8P
Adder
7.457
274736ELWOOD EC;9P
Adder
7.457
276806AD2-047 C O1
Solar/Wind Harmer
1.792
970941AG2-585 GEN
Solar/Wind Harmer
3.953
276157O29GEN1
Solar/Wind Harmer
0.511
274800UNIV PARK;3U
Adder
2.637
972038AH1-567 GEN2
Adder
0.165
274676JOLIET 29;8U
Adder
13.378
274802UNIV PARK;5U
Adder
2.636
274826FISK ;BP
Adder
4.945
970707AG2-453 GEN
Solar/Wind Harmer
10.286
943121AE2-341 GEN
Solar/Wind Harmer
5.278
943591AF1-030 GEN
Solar/Wind Harmer
3.51
274772LINCOLN ;3U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.115
274855GSG-6 ;RU
Solar/Wind Harmer
0.115
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.056
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.335
959091AF2-200 GEN
Solar/Wind Harmer
6.288
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
965931AG1-462 GEN
Solar/Wind Harmer
7.987
962251AG1-071 GEN
Solar/Wind Harmer
1.885
958171AF2-111 GEN
Solar/Wind Harmer
7.532
970349AG2-230 GEN
Solar/Wind Harmer
4.502
957541AF2-048 GEN
Solar/Wind Helper
0.879
270273AD2-016 GEN
Solar/Wind Helper
1.449
25196508WSDLE4
Adder
8.515
971985AH1-537 GEN
Solar/Wind Harmer
2.063
270240V3-007_GEN2
Solar/Wind Harmer
0.002
971673AH1-337 GEN
Solar/Wind Harmer
3.056
971029AG2-637 GEN
Solar/Wind Harmer
6.982
270543AE2-219 C
Solar/Wind Harmer
0.003
970115AG2-085 GEN
Solar/Wind Harmer
1.798
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
270594AE1-207 GEN
Solar/Wind Harmer
4.833
253349AC2-067 GEN
Solar/Wind Harmer
1.341
253400AC2-068 GEN
Solar/Wind Harmer
0.539
970289AG2-191 GEN
Solar/Wind Harmer
0.806
971609AH1-304 GEN
Solar/Wind Harmer
0.692
945581AF1-223 GEN
Solar/Wind Harmer
0
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
25306009OHH W.
Adder
1.706
253372AE2-315 SEC3
Adder
1.113
253372AE2-315 SEC3
Adder
1.113
965101AG1-375 GEN
Solar/Wind Harmer
4.064
970455AG2-298 GEN
Solar/Wind Harmer
2.674
963841AG1-237 GEN
Solar/Wind Harmer
1.675
270024AE2-089 GEN
Solar/Wind Harmer
0.004
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
24729505KEY G4
Adder
3.46
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
944221AF1-090 GEN
Solar/Wind Harmer
2.096
971611AH1-305 GEN
Solar/Wind Harmer
2.122
958391AF2-133 GEN
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0
276174W4-005 GEN2
Solar/Wind Harmer
0
276849AB2-070 GEN2
Solar/Wind Harmer
0.127
276848AB2-070 GEN3
Solar/Wind Harmer
0.127
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
276655WTG1_EQ
Solar/Wind Harmer
0.001
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
3.547
941731AE2-173 GEN
Solar/Wind Harmer
2.815
339211AE2-254 GEN
Solar/Wind Harmer
0.001
970169AG2-114 GEN
Solar/Wind Harmer
3.303
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
963791AG1-232 GEN
Solar/Wind Harmer
4.381
270071AF1-092 GEN
Solar/Wind Harmer
6.208
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
3429211JKCT 2G
Adder
5.399
957751AF2-069 GEN
Solar/Wind Harmer
0.106
926823AC1-168 GEN
Solar/Wind Harmer
0.547
276868AE1-113 GEN
Solar/Wind Harmer
0.639
276882AE2-255 GEN
Solar/Wind Harmer
0.373
970833AG2-524 GEN
Solar/Wind Harmer
3.487
970833AG2-524 GEN
Solar/Wind Harmer
2.324
274731ELWOOD EC;2P
Adder
7.457
274733ELWOOD EC;3P
Adder
7.457
274735ELWOOD EC;4P
Adder
7.457
972227AH1-698 GEN1
Adder
1.183
274728ELWOOD EC;5P
Adder
7.457
960591AF2-350 GEN
Solar/Wind Harmer
3.162
274675JOLIET 29;7U
Adder
13.874
274675JOLIET 29;7U
Adder
13.378
274687WILL CNTY;4U
Adder
12.634
274687WILL CNTY;4U
Adder
12.634
972037AH1-567 GEN1
Adder
0.083
274827FISK ;RP
Adder
3.505
274746AC1-111 G10
Adder
2.525
274744AC1-111 GEN8
Adder
2.525
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274811UNIV PK N;7U
Adder
2.261
274775LINCOLN ;6U
Adder
3.805
274776LINCOLN ;7U
Adder
3.805
274777LINCOLN ;8U
Adder
1.515
971675AH1-338 GEN
Solar/Wind Harmer
1.227
971171AH1-044 GEN
Solar/Wind Harmer
6.288
961011AF2-392 GEN
Solar/Wind Harmer
1.844
971681AH1-341 GEN
Solar/Wind Harmer
5.059
971177AH1-047 GEN
Solar/Wind Harmer
1.937
971411AH1-196 GEN
Solar/Wind Harmer
4.711
276612AE2-035 GEN
Solar/Wind Harmer
0.001
946321AF1-296 GEN
Solar/Wind Harmer
1.755
241972AD1-140 GEN
Solar/Wind Harmer
0.34
247536S-71 GEN
Solar/Wind Harmer
0.176
270032AE2-172
Solar/Wind Harmer
2.877
970291AG2-192 GEN
Solar/Wind Harmer
0.551
971565AH1-281 GEN
Solar/Wind Harmer
0.847
945371AF1-202 GEN
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Harmer
0.113
960071AF2-298 GEN
Solar/Wind Harmer
2.043
253370AE2-315 SEC1
Adder
1.177
253371AE2-315 SEC2
Adder
1.113
25326309TAIT D
Adder
0.64
958861AF2-177 GEN
Solar/Wind Harmer
1.761
965651AG1-433 GEN
Solar/Wind Harmer
1.167
963741AG1-226 GEN
Solar/Wind Harmer
9.29
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.455
965911AG1-460 GEN
Solar/Wind Harmer
0.704
276615X2-022 GEN
Solar/Wind Harmer
0.037
274880W4-005 GEN4
Solar/Wind Harmer
0
963831AG1-236 GEN
Solar/Wind Harmer
1.362
964861AG1-349 GEN
Solar/Wind Harmer
0
971917AH1-482 GEN
Solar/Wind Harmer
4.508
958381AF2-132 GEN
Solar/Wind Harmer
0.001
972175AH1-670 GEN
Solar/Wind Harmer
2.851
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
270055AF2-134 C O1
Solar/Wind Harmer
0.003
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
4.729
970245AG2-165 GEN
Solar/Wind Harmer
1.448
971821AH1-427 GEN
Solar/Wind Harmer
3.331
970373AG2-245 GEN
Solar/Wind Harmer
6.927
3429421JKCT 10G
Adder
3.902
939401AE1-172 GEN
Solar/Wind Harmer
2.433
3429241JKCT 3G
Adder
5.47
274877BISHOP HL;1U
Solar/Wind Harmer
0.108
970569AG2-363 GEN
Solar/Wind Harmer
9.614
971997AH1-543 GEN
Solar/Wind Harmer
1.678
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
276901AD2-066 C O1
Solar/Wind Harmer
0.003
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.385
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.457
276776AD2-060 GEN
Solar/Wind Harmer
0.33
274674JOLIET 9 ;6U
Adder
6.975
276158O29GEN2
Solar/Wind Harmer
0
274801UNIV PARK;4U
Adder
2.637
274676JOLIET 29;8U
Adder
13.874
274745AC1-111 GEN9
Adder
2.525
274812UNIV PK N;8U
Adder
2.261
276164X3-005 C
Solar/Wind Harmer
0
274773LINCOLN ;4U
Adder
3.805
274774LINCOLN ;5U
Adder
3.805
274872LEEDK;1U
Solar/Wind Harmer
0.002
276861AD2-134 GEN
Solar/Wind Harmer
0.056
962781AG1-127 GEN
Solar/Wind Harmer
2.993
957471AF2-041 GEN
Solar/Wind Harmer
9.432
959081AF2-199 GEN
Solar/Wind Harmer
3.144
971067AG2-660 GEN
Solar/Wind Harmer
1.048
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
970819AG2-516 GEN
Solar/Wind Harmer
3.764
971475AH1-234 GEN
Solar/Wind Harmer
1.52
964901AG1-354 GEN
Solar/Wind Harmer
4.633
962241AG1-070 GEN
Solar/Wind Harmer
1.643
927014AC1-188 GEN
Solar/Wind Helper
0.876
270263AC1-001 GEN
Solar/Wind Helper
0.622
270331AC1-082 GEN3
Solar/Wind Helper
0.099
960001AF2-291 GEN
Solar/Wind Helper
0.551
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971769AH1-391 GEN
Solar/Wind Harmer
3.38
971347AH1-153 GEN
Solar/Wind Harmer
4.502
270330AC1-082 GEN2
Solar/Wind Helper
0.021
270329AC1-082 GEN1
Solar/Wind Helper
0.099
942221AE2-234 GEN
Solar/Wind Harmer
0.018
971125AH1-004 GEN
Solar/Wind Harmer
1.469
970107AG2-081 GEN
Solar/Wind Harmer
1.102
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
972043AH1-570 GEN
Solar/Wind Harmer
0.949
972045AH1-571 GEN
Solar/Wind Harmer
0.76
276916AD2-100_GEN
Solar/Wind Harmer
7.418
276911AD2-131_GEN
Solar/Wind Harmer
0.489
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
960611AF2-352 GEN
Solar/Wind Harmer
1.133
970321AG2-212 GEN
Solar/Wind Harmer
1.448
942891AE2-308 GEN
Solar/Wind Harmer
3.277
971081AG2-670 GEN
Solar/Wind Harmer
2.441
274851PROVIDENC;RU
Solar/Wind Harmer
0
274849CRESCENT ;1U
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.127
276646AC1-214 GEN2
Solar/Wind Harmer
0.127
276782AC1-033 GEN
Solar/Wind Harmer
0
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
274879MINONK ;1U
Solar/Wind Harmer
0.134
958491AF2-143 GEN
Solar/Wind Harmer
4.777
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.43
958481AF2-142 GEN
Solar/Wind Harmer
4.764
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
274888KELLY CRK;1U
Solar/Wind Harmer
0.186
274887GEN-1.85
Solar/Wind Harmer
0.083
276843GEN-1.7
Solar/Wind Harmer
0.102
958011AF2-095 GEN
Solar/Wind Harmer
4.553
274674JOLIET 9 ;6U
Adder
6.975
276741O09 GEN1
Solar/Wind Harmer
0.113
276708O09 GEN2
Solar/Wind Harmer
0.113
972259AH1-714 GEN
Adder
8.636
274803UNIV PARK;6U
Adder
2.636
274808UNIV PK N;4U
Adder
2.251
971573AH1-285 GEN
Solar/Wind Harmer
0.586
274696ROCKY RD ;4P
Adder
5.14
274695ROCKY RD ;2P
Adder
5.022
274693ROCKY RD ;1P
Adder
4.972
274697ROCKY RD ;3P
Adder
1.364
962691AG1-118 GEN
Solar/Wind Harmer
9.438
274770LINCOLN ;1U
Adder
3.805
274771LINCOLN ;2U
Adder
3.805
970921AG2-575 GEN
Solar/Wind Harmer
3.145
970921AG2-575 GEN
Solar/Wind Harmer
1.048
276603SUBLETTE C
Solar/Wind Harmer
0
971341AH1-150 GEN
Solar/Wind Harmer
6.288
971343AH1-151 GEN
Solar/Wind Harmer
6.288
942991AE2-321 GEN
Solar/Wind Harmer
3.508
971333AH1-146 GEN
Solar/Wind Harmer
6.283
971335AH1-147 GEN
Solar/Wind Harmer
6.283
938861AE1-114 GEN
Solar/Wind Harmer
1.78
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
965681AG1-436 GEN
Solar/Wind Harmer
3.864
965791AG1-447 GEN
Solar/Wind Harmer
2.834
24441505OLIV SLR
Solar/Wind Harmer
0
270526AF1-158 GEN
Solar/Wind Harmer
0.004
944201AF1-088_MTX
Adder
74.561
957141AF2-008_MTX
Adder
37.28
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.331
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.91
CBM South 1LTFEXP_CBM-S1->PJM
CBM
12.478
MECLTFEXP_MEC->PJM
CLTF
7.273
SIGELTFEXP_SIGE->PJM
CLTF
0.331
CBM West 2LTFEXP_CBM-W2->PJM
CBM
53.307
LAGNLTFEXP_LAGN->PJM
CLTF
5.322
TVALTFEXP_TVA->PJM
CLTF
2.383
NYPJM->LTFIMP_NY
CLTF
1.072
LGEELTFEXP_LGEE->PJM
CLTF
5.218
WECLTFEXP_WEC->PJM
CLTF
1.713
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.651
AG2-052LTFEXP_AG2-052->PJM
LTF
0.113
AH1-155LTFEXP_AH1-155->PJM
LTF
0.169

Details for 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT3281&13803_SRT-A


Base Case Flowgate

Area:DEO&K
Facility Description:
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT3281&13803_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:129.22 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:69.78
MW Contribution:2.42
Bus #Bus NameTypeMW Contribution
944031AF1-071 GEN
Solar/Wind Harmer
0.689
971029AG2-637 GEN
Solar/Wind Harmer
4.453
24728805RICHG1
Adder
1.52
24728905RICHG2
Adder
1.52
970883AG2-550 GEN
Solar/Wind Harmer
2.425
970885AG2-551 GEN
Solar/Wind Harmer
0.564
270222AC2-111 GEN
Solar/Wind Harmer
5.591
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.01
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.569
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.016
MECLTFEXP_MEC->PJM
CLTF
0.177
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.945
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.028
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.074
LAGNLTFEXP_LAGN->PJM
CLTF
0.067
TVALTFEXP_TVA->PJM
CLTF
0.015
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.015
WECLTFEXP_WEC->PJM
CLTF
0.049
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.36 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:248.78
MW Contribution:16.77
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
8.081
971617AH1-308 GEN
Solar/Wind Harmer
26.728
946031AF1-268 GEN
Solar/Wind Harmer
22.021
962031AG1-047 GEN
Solar/Wind Harmer
8.019
957741AF2-068 GEN
Solar/Wind Harmer
39.797
247621Y3-024
50/50
0.456
270201AC2-176 GEN
Solar/Wind Harmer
13.639
964611AG1-324 GEN
Solar/Wind Harmer
3.128
964611AG1-324 GEN
Solar/Wind Harmer
1.388
970883AG2-550 GEN
Solar/Wind Harmer
16.766
970885AG2-551 GEN
Solar/Wind Harmer
3.899
270024AE2-089 GEN
Solar/Wind Harmer
21.578
961761AG1-017 GEN
Solar/Wind Harmer
1.136
270543AE2-219 C
Solar/Wind Harmer
8.585
971029AG2-637 GEN
Solar/Wind Harmer
20.461
971673AH1-337 GEN
Solar/Wind Harmer
5.871
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.192
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.144
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.013
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.046
TVALTFEXP_TVA->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.017
LGEELTFEXP_LGEE->PJM
CLTF
0.116

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.32 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:248.71
MW Contribution:16.76
Bus #Bus NameTypeMW Contribution
971617AH1-308 GEN
Solar/Wind Harmer
26.727
962031AG1-047 GEN
Solar/Wind Harmer
8.019
957741AF2-068 GEN
Solar/Wind Harmer
39.794
946031AF1-268 GEN
Solar/Wind Harmer
22.02
247536S-71 GEN
Solar/Wind Harmer
8.08
270024AE2-089 GEN
Solar/Wind Harmer
21.577
961761AG1-017 GEN
Solar/Wind Harmer
1.135
270543AE2-219 C
Solar/Wind Harmer
8.584
971029AG2-637 GEN
Solar/Wind Harmer
20.457
971673AH1-337 GEN
Solar/Wind Harmer
5.87
247621Y3-024
50/50
0.456
270201AC2-176 GEN
Solar/Wind Harmer
13.638
964611AG1-324 GEN
Solar/Wind Harmer
3.128
964611AG1-324 GEN
Solar/Wind Harmer
1.388
970883AG2-550 GEN
Solar/Wind Harmer
16.764
970885AG2-551 GEN
Solar/Wind Harmer
3.899
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.19
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.147
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.013
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.047
TVALTFEXP_TVA->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.017
LGEELTFEXP_LGEE->PJM
CLTF
0.116

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.69 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:226.91
MW Contribution:17.27
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
8.329
247621Y3-024
50/50
0.448
270201AC2-176 GEN
Solar/Wind Harmer
14.334
970883AG2-550 GEN
Solar/Wind Harmer
17.275
970885AG2-551 GEN
Solar/Wind Harmer
4.017
942221AE2-234 GEN
Solar/Wind Helper
0.348
270024AE2-089 GEN
Solar/Wind Harmer
21.953
961761AG1-017 GEN
Solar/Wind Harmer
1.193
270543AE2-219 C
Solar/Wind Harmer
8.845
971029AG2-637 GEN
Solar/Wind Harmer
21.072
971673AH1-337 GEN
Solar/Wind Harmer
6.046
971617AH1-308 GEN
Solar/Wind Harmer
27.193
962031AG1-047 GEN
Solar/Wind Harmer
8.428
957741AF2-068 GEN
Solar/Wind Harmer
41.825
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.213
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.134
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.015
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.05
TVALTFEXP_TVA->PJM
CLTF
0.007
NYPJM->LTFIMP_NY
CLTF
0.014
LGEELTFEXP_LGEE->PJM
CLTF
0.114

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.84 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:223.12
MW Contribution:17.05
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
8.221
247621Y3-024
50/50
0.452
270201AC2-176 GEN
Solar/Wind Harmer
14.032
970883AG2-550 GEN
Solar/Wind Harmer
17.054
970885AG2-551 GEN
Solar/Wind Harmer
3.966
942221AE2-234 GEN
Solar/Wind Helper
0.334
270024AE2-089 GEN
Solar/Wind Harmer
21.79
961761AG1-017 GEN
Solar/Wind Harmer
1.168
270543AE2-219 C
Solar/Wind Harmer
8.732
971029AG2-637 GEN
Solar/Wind Harmer
20.806
971673AH1-337 GEN
Solar/Wind Harmer
5.97
971617AH1-308 GEN
Solar/Wind Harmer
26.991
962031AG1-047 GEN
Solar/Wind Harmer
8.25
957741AF2-068 GEN
Solar/Wind Harmer
40.943
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.198
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.145
SIGELTFEXP_SIGE->PJM
CLTF
0.004
CPLELTFEXP_CPLE->PJM
CLTF
0.016
MDUPJM->LTFIMP_MDU
CLTF
0
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.053
TVALTFEXP_TVA->PJM
CLTF
0.01
NYPJM->LTFIMP_NY
CLTF
0.014
LGEELTFEXP_LGEE->PJM
CLTF
0.116

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.07 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:213.35
MW Contribution:9.01
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
17.217
961761AG1-017 GEN
Solar/Wind Harmer
0.597
270543AE2-219 C
Solar/Wind Harmer
4.612
971029AG2-637 GEN
Solar/Wind Harmer
11.456
971673AH1-337 GEN
Solar/Wind Harmer
3.327
971617AH1-308 GEN
Solar/Wind Harmer
21.326
962031AG1-047 GEN
Solar/Wind Harmer
4.213
957741AF2-068 GEN
Solar/Wind Harmer
20.906
946031AF1-268 GEN
Solar/Wind Harmer
5.015
270201AC2-176 GEN
Solar/Wind Harmer
7.165
964611AG1-324 GEN
Solar/Wind Harmer
1.445
964611AG1-324 GEN
Solar/Wind Harmer
0.641
970883AG2-550 GEN
Solar/Wind Harmer
9.007
970885AG2-551 GEN
Solar/Wind Harmer
2.095
247621Y3-024
Adder
0.2
942221AE2-234 GEN
Solar/Wind Helper
0.538
247536S-71 GEN
Solar/Wind Harmer
4.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.102
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
0.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.351
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.336
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
TVALTFEXP_TVA->PJM
CLTF
0.229
NYPJM->LTFIMP_NY
CLTF
0.029
LGEELTFEXP_LGEE->PJM
CLTF
0.403

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:104.07 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:213.34
MW Contribution:9.01
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
17.217
961761AG1-017 GEN
Solar/Wind Harmer
0.597
270543AE2-219 C
Solar/Wind Harmer
4.612
971029AG2-637 GEN
Solar/Wind Harmer
11.456
971673AH1-337 GEN
Solar/Wind Harmer
3.327
971617AH1-308 GEN
Solar/Wind Harmer
21.326
962031AG1-047 GEN
Solar/Wind Harmer
4.213
957741AF2-068 GEN
Solar/Wind Harmer
20.906
946031AF1-268 GEN
Solar/Wind Harmer
5.015
270201AC2-176 GEN
Solar/Wind Harmer
7.165
964611AG1-324 GEN
Solar/Wind Harmer
1.445
964611AG1-324 GEN
Solar/Wind Harmer
0.641
970883AG2-550 GEN
Solar/Wind Harmer
9.007
970885AG2-551 GEN
Solar/Wind Harmer
2.095
247621Y3-024
Adder
0.2
942221AE2-234 GEN
Solar/Wind Helper
0.538
247536S-71 GEN
Solar/Wind Harmer
4.201
CBM South 1LTFEXP_CBM-S1->PJM
CBM
1.102
SIGELTFEXP_SIGE->PJM
CLTF
0.029
CPLELTFEXP_CPLE->PJM
CLTF
0.11
CBM West 2LTFEXP_CBM-W2->PJM
CBM
3.351
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.336
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.382
TVALTFEXP_TVA->PJM
CLTF
0.229
NYPJM->LTFIMP_NY
CLTF
0.029
LGEELTFEXP_LGEE->PJM
CLTF
0.403

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#17625_05HAYES 138_B_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17625_05HAYES 138_B_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:103.86 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:212.92
MW Contribution:11.44
Bus #Bus NameTypeMW Contribution
270024AE2-089 GEN
Solar/Wind Harmer
17.387
961761AG1-017 GEN
Solar/Wind Harmer
0.609
270543AE2-219 C
Solar/Wind Harmer
5.855
971029AG2-637 GEN
Solar/Wind Harmer
16.64
971673AH1-337 GEN
Solar/Wind Harmer
5.103
971617AH1-308 GEN
Solar/Wind Harmer
21.537
962031AG1-047 GEN
Solar/Wind Harmer
4.302
957741AF2-068 GEN
Solar/Wind Harmer
21.352
946031AF1-268 GEN
Solar/Wind Harmer
4.417
247621Y3-024
50/50
0.244
270201AC2-176 GEN
Solar/Wind Harmer
7.318
964611AG1-324 GEN
Solar/Wind Harmer
1.455
964611AG1-324 GEN
Solar/Wind Harmer
0.646
970883AG2-550 GEN
Solar/Wind Harmer
11.435
970885AG2-551 GEN
Solar/Wind Harmer
2.659
942221AE2-234 GEN
Solar/Wind Helper
0.526
247536S-71 GEN
Solar/Wind Harmer
4.826
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.601
SIGELTFEXP_SIGE->PJM
CLTF
0.016
CPLELTFEXP_CPLE->PJM
CLTF
0.052
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.877
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.185
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.191
TVALTFEXP_TVA->PJM
CLTF
0.125
NYPJM->LTFIMP_NY
CLTF
0.026
LGEELTFEXP_LGEE->PJM
CLTF
0.221

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P2-2_#13951_05N PORTLN 69.0_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#13951_05N PORTLN 69.0_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:102.02 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:209.13
MW Contribution:9.96
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
4.707
971617AH1-308 GEN
Solar/Wind Harmer
20.652
962031AG1-047 GEN
Solar/Wind Harmer
4.317
957741AF2-068 GEN
Solar/Wind Harmer
21.425
946031AF1-268 GEN
Solar/Wind Harmer
4.462
247621Y3-024
50/50
0.299
270201AC2-176 GEN
Solar/Wind Harmer
7.343
964611AG1-324 GEN
Solar/Wind Harmer
1.461
964611AG1-324 GEN
Solar/Wind Harmer
0.648
970883AG2-550 GEN
Solar/Wind Harmer
9.965
970885AG2-551 GEN
Solar/Wind Harmer
2.318
942221AE2-234 GEN
Solar/Wind Helper
0.648
270024AE2-089 GEN
Solar/Wind Harmer
16.673
961761AG1-017 GEN
Solar/Wind Harmer
0.611
270543AE2-219 C
Solar/Wind Harmer
5.103
971029AG2-637 GEN
Solar/Wind Harmer
12.476
971673AH1-337 GEN
Solar/Wind Harmer
3.606
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.691
SIGELTFEXP_SIGE->PJM
CLTF
0.018
CPLELTFEXP_CPLE->PJM
CLTF
0.07
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.963
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
0.2
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.243
TVALTFEXP_TVA->PJM
CLTF
0.141
NYPJM->LTFIMP_NY
CLTF
0.023
LGEELTFEXP_LGEE->PJM
CLTF
0.261

Details for AF1-118 TP-05SORENS 345.0 kV Ckt 2 line l/o AEP_P4_#4817_05SORENS 345_B2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-118 TP-05SORENS 345.0 kV Ckt 2 line
Contingency Name:
AEP_P4_#4817_05SORENS 345_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.66 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1045.34
MW Contribution:9.78
Bus #Bus NameTypeMW Contribution
24729505KEY G4
50/50
14.481
965101AG1-375 GEN
Solar/Wind Harmer
38.227
945581AF1-223 GEN
Solar/Wind Harmer
9.544
958711AF2-162 GEN
Solar/Wind Harmer
2.128
270240V3-007_GEN2
Solar/Wind Harmer
11.537
970115AG2-085 GEN
Solar/Wind Harmer
5.667
961761AG1-017 GEN
Solar/Wind Harmer
0.446
270594AE1-207 GEN
Solar/Wind Harmer
14.729
270543AE2-219 C
Solar/Wind Harmer
5.007
24725505WLD G2 C
Solar/Wind Harmer
3.817
24699105WLD G1 C
Solar/Wind Harmer
3.772
971029AG2-637 GEN
Solar/Wind Harmer
14.317
971673AH1-337 GEN
Solar/Wind Harmer
4.321
944031AF1-071 GEN
Solar/Wind Harmer
0.819
965461AG1-414 GEN
Solar/Wind Harmer
1.81
970289AG2-191 GEN
Solar/Wind Harmer
1.517
270024AE2-089 GEN
Solar/Wind Harmer
2.916
25196108MFTGT2
Adder
0.767
25196108MFTGT2
Adder
0.712
252524AE2-267 GEN
Solar/Wind Harmer
0.707
25196408WSDLE3
Adder
3.956
25196308WSDLE2
Adder
3.921
25196208WSDLE1
Adder
3.911
25196708WSDLE6
Adder
3.902
25196508WSDLE4
Adder
3.803
957201AF2-014 GEN
Solar/Wind Helper
0.932
961161AF2-407 GEN
50/50
45.177
24728705AND G3
50/50
7.369
24728505AND G1
50/50
3.523
944531AF1-118 GEN
Solar/Wind Harmer
182.43
958821AF2-173 GEN
Solar/Wind Harmer
29.465
270004AE1-209 GEN
Solar/Wind Harmer
11.502
270437AC2-090 C
Solar/Wind Harmer
10.411
946031AF1-268 GEN
Solar/Wind Harmer
12.846
270356AE2-297 GEN
Solar/Wind Harmer
4.824
962031AG1-047 GEN
Solar/Wind Harmer
3.148
957741AF2-068 GEN
Solar/Wind Harmer
15.622
270222AC2-111 GEN
Solar/Wind Harmer
6.645
970289AG2-191 GEN
Solar/Wind Harmer
0.613
970291AG2-192 GEN
Solar/Wind Harmer
0.557
971617AH1-308 GEN
Solar/Wind Harmer
3.612
247642Z2-115 C
Solar/Wind Harmer
0.039
25196008MFTGT1
Adder
0.674
25196608WSDLE5
Adder
3.843
25194608D.CRK4
Adder
0.735
252510AF1-249 C
Solar/Wind Harmer
0.181
270191TR4_S_V150
Solar/Wind Helper
0.576
270247TR4_N_V136
Solar/Wind Helper
0.264
960791AF2-370 GEN
50/50
3.295
961171AF2-408 GEN
50/50
11.131
24728605AND G2
50/50
3.523
958861AF2-177 GEN
Solar/Wind Harmer
41.783
270005AE1-210 C O1
Solar/Wind Harmer
11.502
965031AG1-367 GEN
Solar/Wind Harmer
21.047
945371AF1-202 GEN
Solar/Wind Harmer
14.682
965651AG1-433 GEN
Solar/Wind Harmer
11.498
942081AE2-220 GEN
Solar/Wind Harmer
11.922
270239V3-007_GEN1
Solar/Wind Harmer
3.209
970825AG2-519 GEN
Solar/Wind Harmer
3.555
270032AE2-172
Solar/Wind Harmer
4.661
247536S-71 GEN
Solar/Wind Harmer
4.006
276903AD2-071 C
Solar/Wind Harmer
8.8
970291AG2-192 GEN
Solar/Wind Harmer
1.038
25196008MFTGT1
Adder
0.695
25194608D.CRK4
Adder
0.735
944231AF1-091 GEN
Solar/Wind Helper
2.191
247521TR3_G114
Solar/Wind Helper
1.043
270246TR4_N_V150
Solar/Wind Helper
0.264
270063AE2-323 C
Solar/Wind Helper
1.044
246936BC-WTG1
Solar/Wind Helper
1.179
24695305TIMB G C
Solar/Wind Helper
1.286
24729405KEY G3
50/50
0.791
24729305KEY G2
50/50
0.777
24729205KEY G1
50/50
0.773
247621Y3-024
50/50
0.24
24728805RICHG1
50/50
3.735
24728905RICHG2
50/50
3.735
944541AF1-119 GEN
Solar/Wind Harmer
8.812
960971AF2-388 GEN
Solar/Wind Harmer
22.997
24379505HDWTR1G C
Solar/Wind Harmer
14.745
270209AC1-174_GEN
Solar/Wind Harmer
10.406
926881AC1-175 GEN
Solar/Wind Harmer
10.406
970825AG2-519 GEN
Solar/Wind Harmer
15.933
270383AD1-128 GEN
Solar/Wind Harmer
8.85
960441AF2-335 GEN
Solar/Wind Harmer
14.167
964611AG1-324 GEN
Solar/Wind Harmer
1.355
964611AG1-324 GEN
Solar/Wind Harmer
0.601
270201AC2-176 GEN
Solar/Wind Harmer
5.354
970883AG2-550 GEN
Solar/Wind Harmer
9.778
970885AG2-551 GEN
Solar/Wind Harmer
2.274
270599AE1-208 GEN
Solar/Wind Harmer
7.954
270031AE2-169
Solar/Wind Harmer
7.954
25194408D.CRK1
Adder
3.38
25194508D.CRK3
Adder
0.632
246938BC-WTG3
Solar/Wind Helper
1.199
246937BC-WTG2
Solar/Wind Helper
1.179
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.938
SIGELTFEXP_SIGE->PJM
CLTF
0.188
CPLELTFEXP_CPLE->PJM
CLTF
0.729
CBM West 2LTFEXP_CBM-W2->PJM
CBM
22.763
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
2.296
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.476
TVALTFEXP_TVA->PJM
CLTF
1.482
NYPJM->LTFIMP_NY
CLTF
0.074
LGEELTFEXP_LGEE->PJM
CLTF
2.411

Details for AF1-118 TP-05SORENS 345.0 kV Ckt 2 line l/o AEP_P4_#7449_05SORENS 345_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-118 TP-05SORENS 345.0 kV Ckt 2 line
Contingency Name:
AEP_P4_#7449_05SORENS 345_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.32 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1032.36
MW Contribution:9.63
Bus #Bus NameTypeMW Contribution
24729405KEY G3
50/50
0.784
24729305KEY G2
50/50
0.771
24729205KEY G1
50/50
0.767
247621Y3-024
50/50
0.236
24728805RICHG1
50/50
3.696
24728905RICHG2
50/50
3.696
944541AF1-119 GEN
Solar/Wind Harmer
8.74
960971AF2-388 GEN
Solar/Wind Harmer
22.809
24379505HDWTR1G C
Solar/Wind Harmer
14.623
270209AC1-174_GEN
Solar/Wind Harmer
10.32
926881AC1-175 GEN
Solar/Wind Harmer
10.32
970825AG2-519 GEN
Solar/Wind Harmer
15.763
270383AD1-128 GEN
Solar/Wind Harmer
8.763
960441AF2-335 GEN
Solar/Wind Harmer
14.006
964611AG1-324 GEN
Solar/Wind Harmer
1.335
964611AG1-324 GEN
Solar/Wind Harmer
0.592
270201AC2-176 GEN
Solar/Wind Harmer
5.267
961161AF2-407 GEN
50/50
44.849
24728705AND G3
50/50
7.321
24728505AND G1
50/50
3.5
944531AF1-118 GEN
Solar/Wind Harmer
181.081
958821AF2-173 GEN
Solar/Wind Harmer
29.224
270004AE1-209 GEN
Solar/Wind Harmer
11.408
270437AC2-090 C
Solar/Wind Harmer
10.325
946031AF1-268 GEN
Solar/Wind Harmer
12.712
270356AE2-297 GEN
Solar/Wind Harmer
4.779
962031AG1-047 GEN
Solar/Wind Harmer
3.097
957741AF2-068 GEN
Solar/Wind Harmer
15.368
270222AC2-111 GEN
Solar/Wind Harmer
6.569
970289AG2-191 GEN
Solar/Wind Harmer
0.605
970291AG2-192 GEN
Solar/Wind Harmer
0.55
971617AH1-308 GEN
Solar/Wind Harmer
3.493
247642Z2-115 C
Solar/Wind Harmer
0.038
25196008MFTGT1
Adder
0.667
25196608WSDLE5
Adder
3.794
25194608D.CRK4
Adder
0.726
270191TR4_S_V150
Solar/Wind Helper
0.606
960791AF2-370 GEN
50/50
3.257
961171AF2-408 GEN
50/50
11.04
24728605AND G2
50/50
3.5
958861AF2-177 GEN
Solar/Wind Harmer
41.466
270005AE1-210 C O1
Solar/Wind Harmer
11.408
965031AG1-367 GEN
Solar/Wind Harmer
20.875
945371AF1-202 GEN
Solar/Wind Harmer
14.562
965651AG1-433 GEN
Solar/Wind Harmer
11.405
942081AE2-220 GEN
Solar/Wind Harmer
11.823
270239V3-007_GEN1
Solar/Wind Harmer
3.182
970825AG2-519 GEN
Solar/Wind Harmer
3.517
270032AE2-172
Solar/Wind Harmer
4.61
247536S-71 GEN
Solar/Wind Harmer
3.942
276903AD2-071 C
Solar/Wind Harmer
8.698
970291AG2-192 GEN
Solar/Wind Harmer
1.025
25196008MFTGT1
Adder
0.688
25194608D.CRK4
Adder
0.726
944231AF1-091 GEN
Solar/Wind Helper
2.27
247521TR3_G114
Solar/Wind Helper
1.097
270246TR4_N_V150
Solar/Wind Helper
0.278
246936BC-WTG1
Solar/Wind Helper
1.236
24695305TIMB G C
Solar/Wind Helper
1.352
270063AE2-323 C
Solar/Wind Helper
1.013
24729505KEY G4
50/50
14.363
965101AG1-375 GEN
Solar/Wind Harmer
37.937
945581AF1-223 GEN
Solar/Wind Harmer
9.466
958711AF2-162 GEN
Solar/Wind Harmer
2.111
270240V3-007_GEN2
Solar/Wind Harmer
11.442
970115AG2-085 GEN
Solar/Wind Harmer
5.602
961761AG1-017 GEN
Solar/Wind Harmer
0.438
270594AE1-207 GEN
Solar/Wind Harmer
14.566
270543AE2-219 C
Solar/Wind Harmer
4.931
24725505WLD G2 C
Solar/Wind Harmer
3.775
24699105WLD G1 C
Solar/Wind Harmer
3.73
971029AG2-637 GEN
Solar/Wind Harmer
14.11
971673AH1-337 GEN
Solar/Wind Harmer
4.259
944031AF1-071 GEN
Solar/Wind Harmer
0.81
965461AG1-414 GEN
Solar/Wind Harmer
1.788
970289AG2-191 GEN
Solar/Wind Harmer
1.499
270024AE2-089 GEN
Solar/Wind Harmer
2.82
25196108MFTGT2
Adder
0.759
25196108MFTGT2
Adder
0.705
252524AE2-267 GEN
Solar/Wind Harmer
0.698
25196408WSDLE3
Adder
3.906
25196308WSDLE2
Adder
3.872
25196208WSDLE1
Adder
3.862
25196708WSDLE6
Adder
3.853
25196508WSDLE4
Adder
3.756
957201AF2-014 GEN
Solar/Wind Helper
0.977
970883AG2-550 GEN
Solar/Wind Harmer
9.63
970885AG2-551 GEN
Solar/Wind Harmer
2.239
270599AE1-208 GEN
Solar/Wind Harmer
7.79
270031AE2-169
Solar/Wind Harmer
7.79
25194408D.CRK1
Adder
3.337
25194508D.CRK3
Adder
0.624
246938BC-WTG3
Solar/Wind Helper
1.257
246937BC-WTG2
Solar/Wind Helper
1.236
270247TR4_N_V136
Solar/Wind Helper
0.278
270044AE2-322 C
Solar/Wind Helper
0.568
270404AC1-167 GEN
Solar/Wind Helper
0.473
CBM South 1LTFEXP_CBM-S1->PJM
CBM
6.97
SIGELTFEXP_SIGE->PJM
CLTF
0.188
CPLELTFEXP_CPLE->PJM
CLTF
0.706
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.271
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
2.358
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.428
TVALTFEXP_TVA->PJM
CLTF
1.496
NYPJM->LTFIMP_NY
CLTF
0.097
LGEELTFEXP_LGEE->PJM
CLTF
2.401

Details for AF1-118 TP-05SORENS 345.0 kV Ckt 2 line l/o AEP_P4_#2896_05KEYSTN 345_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-118 TP-05SORENS 345.0 kV Ckt 2 line
Contingency Name:
AEP_P4_#2896_05KEYSTN 345_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.91 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:989.54
MW Contribution:9.8
Bus #Bus NameTypeMW Contribution
960791AF2-370 GEN
50/50
3.299
961171AF2-408 GEN
50/50
11.15
24728605AND G2
50/50
3.532
965101AG1-375 GEN
Solar/Wind Harmer
38.248
945581AF1-223 GEN
Solar/Wind Harmer
9.553
958711AF2-162 GEN
Solar/Wind Harmer
2.131
270240V3-007_GEN2
Solar/Wind Harmer
11.55
970115AG2-085 GEN
Solar/Wind Harmer
5.675
961761AG1-017 GEN
Solar/Wind Harmer
0.447
270594AE1-207 GEN
Solar/Wind Harmer
14.76
247621Y3-024
50/50
0.24
24728805RICHG1
50/50
3.743
24728905RICHG2
50/50
3.743
944541AF1-119 GEN
Solar/Wind Harmer
8.821
960971AF2-388 GEN
Solar/Wind Harmer
23.019
24379505HDWTR1G C
Solar/Wind Harmer
14.762
270209AC1-174_GEN
Solar/Wind Harmer
10.418
926881AC1-175 GEN
Solar/Wind Harmer
10.418
970825AG2-519 GEN
Solar/Wind Harmer
15.955
270383AD1-128 GEN
Solar/Wind Harmer
8.863
960441AF2-335 GEN
Solar/Wind Harmer
14.188
964611AG1-324 GEN
Solar/Wind Harmer
1.357
964611AG1-324 GEN
Solar/Wind Harmer
0.602
270201AC2-176 GEN
Solar/Wind Harmer
5.365
970883AG2-550 GEN
Solar/Wind Harmer
9.799
970885AG2-551 GEN
Solar/Wind Harmer
2.279
270599AE1-208 GEN
Solar/Wind Harmer
7.971
961161AF2-407 GEN
50/50
45.25
24728705AND G3
50/50
7.386
24728505AND G1
50/50
3.532
944531AF1-118 GEN
Solar/Wind Harmer
182.503
958821AF2-173 GEN
Solar/Wind Harmer
29.494
270004AE1-209 GEN
Solar/Wind Harmer
11.514
270437AC2-090 C
Solar/Wind Harmer
10.423
946031AF1-268 GEN
Solar/Wind Harmer
12.863
270356AE2-297 GEN
Solar/Wind Harmer
4.833
962031AG1-047 GEN
Solar/Wind Harmer
3.154
957741AF2-068 GEN
Solar/Wind Harmer
15.654
270222AC2-111 GEN
Solar/Wind Harmer
6.662
970289AG2-191 GEN
Solar/Wind Harmer
0.614
970291AG2-192 GEN
Solar/Wind Harmer
0.558
971617AH1-308 GEN
Solar/Wind Harmer
3.624
247642Z2-115 C
Solar/Wind Harmer
0.039
25196008MFTGT1
Adder
0.676
25196608WSDLE5
Adder
3.86
25194608D.CRK4
Adder
0.738
252510AF1-249 C
Solar/Wind Harmer
0.182
270191TR4_S_V150
Solar/Wind Helper
0.574
270247TR4_N_V136
Solar/Wind Helper
0.263
270543AE2-219 C
Solar/Wind Harmer
5.018
24725505WLD G2 C
Solar/Wind Harmer
3.825
24699105WLD G1 C
Solar/Wind Harmer
3.78
971029AG2-637 GEN
Solar/Wind Harmer
14.348
971673AH1-337 GEN
Solar/Wind Harmer
4.331
944031AF1-071 GEN
Solar/Wind Harmer
0.821
965461AG1-414 GEN
Solar/Wind Harmer
1.815
970289AG2-191 GEN
Solar/Wind Harmer
1.521
270024AE2-089 GEN
Solar/Wind Harmer
2.925
25196108MFTGT2
Adder
0.77
25196108MFTGT2
Adder
0.715
252524AE2-267 GEN
Solar/Wind Harmer
0.71
25196408WSDLE3
Adder
3.974
25196308WSDLE2
Adder
3.939
25196208WSDLE1
Adder
3.929
25196708WSDLE6
Adder
3.92
25196508WSDLE4
Adder
3.821
957201AF2-014 GEN
Solar/Wind Helper
0.928
958861AF2-177 GEN
Solar/Wind Harmer
41.806
270005AE1-210 C O1
Solar/Wind Harmer
11.514
965031AG1-367 GEN
Solar/Wind Harmer
21.067
945371AF1-202 GEN
Solar/Wind Harmer
14.696
965651AG1-433 GEN
Solar/Wind Harmer
11.51
942081AE2-220 GEN
Solar/Wind Harmer
11.935
270239V3-007_GEN1
Solar/Wind Harmer
3.212
970825AG2-519 GEN
Solar/Wind Harmer
3.56
270032AE2-172
Solar/Wind Harmer
4.671
247536S-71 GEN
Solar/Wind Harmer
4.014
276903AD2-071 C
Solar/Wind Harmer
8.82
970291AG2-192 GEN
Solar/Wind Harmer
1.041
25196008MFTGT1
Adder
0.698
25194608D.CRK4
Adder
0.738
944231AF1-091 GEN
Solar/Wind Helper
2.182
247521TR3_G114
Solar/Wind Helper
1.039
270246TR4_N_V150
Solar/Wind Helper
0.263
270063AE2-323 C
Solar/Wind Helper
1.039
246936BC-WTG1
Solar/Wind Helper
1.174
24695305TIMB G C
Solar/Wind Helper
1.28
270031AE2-169
Solar/Wind Harmer
7.971
25194408D.CRK1
Adder
3.396
25194508D.CRK3
Adder
0.635
246938BC-WTG3
Solar/Wind Helper
1.194
246937BC-WTG2
Solar/Wind Helper
1.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.017
SIGELTFEXP_SIGE->PJM
CLTF
0.189
CPLELTFEXP_CPLE->PJM
CLTF
0.752
CBM West 2LTFEXP_CBM-W2->PJM
CBM
23.044
MDUPJM->LTFIMP_MDU
CLTF
0
LAGNLTFEXP_LAGN->PJM
CLTF
2.338
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.539
TVALTFEXP_TVA->PJM
CLTF
1.503
NYPJM->LTFIMP_NY
CLTF
0.061
LGEELTFEXP_LGEE->PJM
CLTF
2.426

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:118.45 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1424.98
MW Contribution:5.13
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.038
253371AE2-315 SEC2
50/50
2.873
25322309TAIT W
50/50
0.712
25322209TAIT E
50/50
0.712
25326309TAIT D
50/50
1.628
960071AF2-298 GEN
Solar/Wind Harmer
6.567
253432AC1-085 GEN2
Solar/Wind Harmer
0.308
946171AF1-282 GEN
Solar/Wind Harmer
11.493
25194608D.CRK4
Adder
1.448
253343AC1-166 GEN
Solar/Wind Harmer
0.935
253325AC1-069 GEN
Solar/Wind Harmer
0.902
270159DARBY CT4
Adder
7.267
25196808ZIMRHP
Adder
60.162
252507AC2-088 GEN
Solar/Wind Harmer
1.394
25196008MFTGT1
Adder
0.977
945681AF1-233 GEN
Solar/Wind Harmer
12.435
339216AC1-074 GEN
Solar/Wind Harmer
0.981
943111AE2-339 GEN
Solar/Wind Harmer
0.48
3429421JKCT 10G
Adder
4.38
3429241JKCT 3G
Adder
6.04
247536S-71 GEN
Solar/Wind Harmer
1.898
253370AE2-315 SEC1
50/50
3.038
253371AE2-315 SEC2
50/50
2.873
25322309TAIT W
50/50
0.712
25322209TAIT E
50/50
0.703
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.5
253316AC1-085 GEN3
Solar/Wind Harmer
9.627
253433AC1-085 GEN1
Solar/Wind Harmer
6.111
946181AF1-283 GEN
Solar/Wind Harmer
14.94
25196608WSDLE5
Adder
7.709
25194608D.CRK4
Adder
1.448
252510AF1-249 C
Solar/Wind Harmer
0.366
253338AC1-165 GEN
Solar/Wind Harmer
0.935
253333AC1-068 GEN
Solar/Wind Harmer
0.902
270222AC2-111 GEN
Solar/Wind Harmer
5.989
958171AF2-111 GEN
Solar/Wind Harmer
17.625
25196008MFTGT1
Adder
0.946
972167AH1-666 GEN
Solar/Wind Harmer
5.299
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.38
970093AG2-073 GEN
Solar/Wind Harmer
4.741
270356AE2-297 GEN
Solar/Wind Harmer
2.157
966571AG1-526 GEN
Solar/Wind Harmer
9.893
960801AF2-371 GEN
Solar/Wind Helper
0.814
964871AG1-351 GEN
Solar/Wind Helper
0.562
241955AC1-078 GEN
Solar/Wind Helper
1.496
270273AD2-016 GEN
Solar/Wind Helper
1.395
25326109MON D
50/50
2.066
253370AE2-315 SEC1
50/50
3.038
253372AE2-315 SEC3
50/50
2.873
253372AE2-315 SEC3
50/50
2.873
25322309TAIT W
50/50
0.72
963581AG1-207 GEN
50/50
13.06
25306009OHH W.
50/50
4.021
945631AF1-228 GEN
Solar/Wind Harmer
27.818
253349AC2-067 GEN
Solar/Wind Harmer
6.021
253400AC2-068 GEN
Solar/Wind Harmer
2.421
241972AD1-140 GEN
Solar/Wind Harmer
5.044
252524AE2-267 GEN
Solar/Wind Harmer
1.419
25196408WSDLE3
Adder
7.936
25196308WSDLE2
Adder
7.867
25196208WSDLE1
Adder
7.848
25196708WSDLE6
Adder
7.828
25196508WSDLE4
Adder
7.631
270156DARBY CT1
Adder
7.385
270157DARBY CT2
Adder
7.367
270158DARBY CT3
Adder
7.249
944031AF1-071 GEN
Solar/Wind Harmer
0.738
25196108MFTGT2
Adder
1.077
25196108MFTGT2
Adder
1
270367AC2-061_GEN
Solar/Wind Harmer
2.217
972163AH1-664 GEN
Solar/Wind Harmer
6.512
972165AH1-665 GEN
Solar/Wind Harmer
5.209
339243AC2-075 GEN1
Solar/Wind Harmer
0.266
971673AH1-337 GEN
Solar/Wind Harmer
2.661
971029AG2-637 GEN
Solar/Wind Harmer
8.415
270543AE2-219 C
Solar/Wind Harmer
2.625
3429211JKCT 2G
Adder
5.962
270340AC2-060 GEN
Solar/Wind Harmer
1.539
270520AE2-214 GEN
Solar/Wind Helper
6.845
270054AF2-122 C O1
Solar/Wind Helper
0.907
25322209TAIT E
50/50
14.495
25322209TAIT E
50/50
14.169
270518AE2-148 GEN
Solar/Wind Harmer
58.767
253394AE2-221_GEN
Solar/Wind Harmer
6.182
253398AE2-221_GEN2
Solar/Wind Harmer
6.182
253317AC1-085 GEN4
Solar/Wind Harmer
9.627
25183208HLCRTG
Solar/Wind Harmer
5.419
252519AF1-045_GEN
Solar/Wind Harmer
5.386
252516AE2-318_GEN
Solar/Wind Harmer
4.109
25194408D.CRK1
Adder
6.661
25194508D.CRK3
Adder
1.245
252509AD1-136 GEN
Solar/Wind Harmer
0.199
962581AG1-107 GEN
Solar/Wind Harmer
3.823
961491AF2-440 GEN
Solar/Wind Harmer
1.589
25326509SID D
Adder
0.977
270186AC1-089 GEN
Solar/Wind Harmer
4.078
253378AE2-206_GEN
Solar/Wind Harmer
2.335
276820AF1-078_GEN
Solar/Wind Harmer
1.037
24728805RICHG1
Adder
2.332
24728905RICHG2
Adder
2.332
339221AD2-048_GEN
Solar/Wind Harmer
0.89
972043AH1-570 GEN
Solar/Wind Harmer
1.426
972045AH1-571 GEN
Solar/Wind Harmer
1.141
971125AH1-004 GEN
Solar/Wind Harmer
2.201
970107AG2-081 GEN
Solar/Wind Harmer
1.651
970235AG2-159 GEN
Solar/Wind Harmer
2.161
970235AG2-159 GEN
Solar/Wind Harmer
1.319
970883AG2-550 GEN
Solar/Wind Harmer
5.126
970885AG2-551 GEN
Solar/Wind Harmer
1.192
942891AE2-308 GEN
Solar/Wind Harmer
4.971
960161AF2-307 GEN
Solar/Wind Harmer
3.167
270383AD1-128 GEN
Solar/Wind Harmer
2.903
247621Y3-024
Adder
0.107
946101AF1-275 GEN
Solar/Wind Helper
0.857
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.65
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.706
MECLTFEXP_MEC->PJM
CLTF
3.158
SIGELTFEXP_SIGE->PJM
CLTF
0.179
CPLELTFEXP_CPLE->PJM
CLTF
0.156
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.018
LAGNLTFEXP_LAGN->PJM
CLTF
3.629
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.427
TVALTFEXP_TVA->PJM
CLTF
1.886
NYPJM->LTFIMP_NY
CLTF
0.874
LGEELTFEXP_LGEE->PJM
CLTF
2.944
WECLTFEXP_WEC->PJM
CLTF
0.645

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16622_05ADKINS 345_B1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16622_05ADKINS 345_B1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:116.03 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1395.78
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.887
253372AE2-315 SEC3
50/50
2.887
25322309TAIT W
50/50
0.724
963581AG1-207 GEN
50/50
13.121
25306009OHH W.
50/50
4.04
945631AF1-228 GEN
Solar/Wind Harmer
27.993
253349AC2-067 GEN
Solar/Wind Harmer
6.051
253400AC2-068 GEN
Solar/Wind Harmer
2.433
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.98
25196308WSDLE2
Adder
7.91
25196208WSDLE1
Adder
7.89
25196708WSDLE6
Adder
7.87
25196508WSDLE4
Adder
7.672
944031AF1-071 GEN
Solar/Wind Harmer
0.742
25196108MFTGT2
Adder
1.083
25196108MFTGT2
Adder
1.005
270367AC2-061_GEN
Solar/Wind Harmer
2.226
972163AH1-664 GEN
Solar/Wind Harmer
6.547
972165AH1-665 GEN
Solar/Wind Harmer
5.238
339243AC2-075 GEN1
Solar/Wind Harmer
0.267
971673AH1-337 GEN
Solar/Wind Harmer
2.677
971029AG2-637 GEN
Solar/Wind Harmer
8.464
270543AE2-219 C
Solar/Wind Harmer
2.641
3429211JKCT 2G
Adder
5.996
270340AC2-060 GEN
Solar/Wind Harmer
1.535
270520AE2-214 GEN
Solar/Wind Helper
6.73
270054AF2-122 C O1
Solar/Wind Helper
0.91
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.707
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.507
253316AC1-085 GEN3
Solar/Wind Harmer
9.678
253433AC1-085 GEN1
Solar/Wind Harmer
6.144
946181AF1-283 GEN
Solar/Wind Harmer
15.021
25196608WSDLE5
Adder
7.752
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.94
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.022
958171AF2-111 GEN
Solar/Wind Harmer
17.721
25196008MFTGT1
Adder
0.951
972167AH1-666 GEN
Solar/Wind Harmer
5.328
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.405
970093AG2-073 GEN
Solar/Wind Harmer
4.768
270356AE2-297 GEN
Solar/Wind Harmer
2.171
966571AG1-526 GEN
Solar/Wind Harmer
9.951
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.671
270273AD2-016 GEN
Solar/Wind Helper
1.462
25326109MON D
50/50
2.075
253370AE2-315 SEC1
50/50
3.053
25322209TAIT E
50/50
14.563
25322209TAIT E
50/50
14.236
270518AE2-148 GEN
Solar/Wind Harmer
59.131
253394AE2-221_GEN
Solar/Wind Harmer
6.215
253398AE2-221_GEN2
Solar/Wind Harmer
6.215
253317AC1-085 GEN4
Solar/Wind Harmer
9.678
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.131
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.838
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.982
270186AC1-089 GEN
Solar/Wind Harmer
4.095
253378AE2-206_GEN
Solar/Wind Harmer
2.346
276820AF1-078_GEN
Solar/Wind Harmer
1.042
24728805RICHG1
Adder
2.346
24728905RICHG2
Adder
2.346
339221AD2-048_GEN
Solar/Wind Harmer
0.895
972043AH1-570 GEN
Solar/Wind Harmer
1.434
972045AH1-571 GEN
Solar/Wind Harmer
1.147
971125AH1-004 GEN
Solar/Wind Harmer
2.214
970107AG2-081 GEN
Solar/Wind Harmer
1.66
970235AG2-159 GEN
Solar/Wind Harmer
2.174
970235AG2-159 GEN
Solar/Wind Harmer
1.327
970883AG2-550 GEN
Solar/Wind Harmer
5.157
970885AG2-551 GEN
Solar/Wind Harmer
1.199
942891AE2-308 GEN
Solar/Wind Harmer
4.999
960161AF2-307 GEN
Solar/Wind Harmer
3.185
270383AD1-128 GEN
Solar/Wind Harmer
2.921
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.843
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.636
960071AF2-298 GEN
Solar/Wind Harmer
6.599
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.554
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.94
253325AC1-069 GEN
Solar/Wind Harmer
0.907
25196808ZIMRHP
Adder
60.49
252507AC2-088 GEN
Solar/Wind Harmer
1.401
25196008MFTGT1
Adder
0.982
945681AF1-233 GEN
Solar/Wind Harmer
12.502
339216AC1-074 GEN
Solar/Wind Harmer
0.987
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.405
3429241JKCT 3G
Adder
6.075
247536S-71 GEN
Solar/Wind Harmer
1.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.863
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
3.185
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.25
LAGNLTFEXP_LAGN->PJM
CLTF
3.659
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.452
TVALTFEXP_TVA->PJM
CLTF
1.901
NYPJM->LTFIMP_NY
CLTF
0.872
LGEELTFEXP_LGEE->PJM
CLTF
2.962
WECLTFEXP_WEC->PJM
CLTF
0.651

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16620_05ADKINS 345_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16620_05ADKINS 345_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.99 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1395.31
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.707
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.507
253316AC1-085 GEN3
Solar/Wind Harmer
9.678
253433AC1-085 GEN1
Solar/Wind Harmer
6.144
946181AF1-283 GEN
Solar/Wind Harmer
15.021
25196608WSDLE5
Adder
7.752
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.94
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.022
958171AF2-111 GEN
Solar/Wind Harmer
17.721
25196008MFTGT1
Adder
0.951
972167AH1-666 GEN
Solar/Wind Harmer
5.328
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.405
970093AG2-073 GEN
Solar/Wind Harmer
4.768
270356AE2-297 GEN
Solar/Wind Harmer
2.171
966571AG1-526 GEN
Solar/Wind Harmer
9.951
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.671
270273AD2-016 GEN
Solar/Wind Helper
1.462
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.636
960071AF2-298 GEN
Solar/Wind Harmer
6.599
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.554
253372AE2-315 SEC3
50/50
2.887
253372AE2-315 SEC3
50/50
2.887
25322309TAIT W
50/50
0.724
963581AG1-207 GEN
50/50
13.121
25306009OHH W.
50/50
4.04
945631AF1-228 GEN
Solar/Wind Harmer
27.993
253349AC2-067 GEN
Solar/Wind Harmer
6.051
253400AC2-068 GEN
Solar/Wind Harmer
2.433
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.98
25196308WSDLE2
Adder
7.91
25196208WSDLE1
Adder
7.89
25196708WSDLE6
Adder
7.87
25196508WSDLE4
Adder
7.672
944031AF1-071 GEN
Solar/Wind Harmer
0.742
25196108MFTGT2
Adder
1.083
25196108MFTGT2
Adder
1.005
270367AC2-061_GEN
Solar/Wind Harmer
2.226
972163AH1-664 GEN
Solar/Wind Harmer
6.547
972165AH1-665 GEN
Solar/Wind Harmer
5.238
339243AC2-075 GEN1
Solar/Wind Harmer
0.267
971673AH1-337 GEN
Solar/Wind Harmer
2.677
971029AG2-637 GEN
Solar/Wind Harmer
8.464
270543AE2-219 C
Solar/Wind Harmer
2.641
3429211JKCT 2G
Adder
5.996
270340AC2-060 GEN
Solar/Wind Harmer
1.535
270520AE2-214 GEN
Solar/Wind Helper
6.73
270054AF2-122 C O1
Solar/Wind Helper
0.91
25326109MON D
50/50
2.075
253370AE2-315 SEC1
50/50
3.053
25322209TAIT E
50/50
14.563
25322209TAIT E
50/50
14.236
270518AE2-148 GEN
Solar/Wind Harmer
59.131
253394AE2-221_GEN
Solar/Wind Harmer
6.215
253398AE2-221_GEN2
Solar/Wind Harmer
6.215
253317AC1-085 GEN4
Solar/Wind Harmer
9.678
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.131
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.838
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.982
270186AC1-089 GEN
Solar/Wind Harmer
4.095
253378AE2-206_GEN
Solar/Wind Harmer
2.346
276820AF1-078_GEN
Solar/Wind Harmer
1.042
24728805RICHG1
Adder
2.346
24728905RICHG2
Adder
2.346
339221AD2-048_GEN
Solar/Wind Harmer
0.895
972043AH1-570 GEN
Solar/Wind Harmer
1.434
972045AH1-571 GEN
Solar/Wind Harmer
1.147
971125AH1-004 GEN
Solar/Wind Harmer
2.214
970107AG2-081 GEN
Solar/Wind Harmer
1.66
970235AG2-159 GEN
Solar/Wind Harmer
2.174
970235AG2-159 GEN
Solar/Wind Harmer
1.327
970883AG2-550 GEN
Solar/Wind Harmer
5.157
970885AG2-551 GEN
Solar/Wind Harmer
1.199
942891AE2-308 GEN
Solar/Wind Harmer
4.999
960161AF2-307 GEN
Solar/Wind Harmer
3.185
270383AD1-128 GEN
Solar/Wind Harmer
2.921
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.843
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.94
253325AC1-069 GEN
Solar/Wind Harmer
0.907
25196808ZIMRHP
Adder
60.49
252507AC2-088 GEN
Solar/Wind Harmer
1.401
25196008MFTGT1
Adder
0.982
945681AF1-233 GEN
Solar/Wind Harmer
12.502
339216AC1-074 GEN
Solar/Wind Harmer
0.987
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.405
3429241JKCT 3G
Adder
6.075
247536S-71 GEN
Solar/Wind Harmer
1.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.863
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
3.185
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.25
LAGNLTFEXP_LAGN->PJM
CLTF
3.659
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.452
TVALTFEXP_TVA->PJM
CLTF
1.901
NYPJM->LTFIMP_NY
CLTF
0.872
LGEELTFEXP_LGEE->PJM
CLTF
2.962
WECLTFEXP_WEC->PJM
CLTF
0.651

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#16621_05ADKINS 345_A1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16621_05ADKINS 345_A1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.99 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1395.3
MW Contribution:5.16
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.707
253303V4-073 C
Solar/Wind Harmer
0.166
253406AD2-031_GEN
Solar/Wind Harmer
1.507
253316AC1-085 GEN3
Solar/Wind Harmer
9.678
253433AC1-085 GEN1
Solar/Wind Harmer
6.144
946181AF1-283 GEN
Solar/Wind Harmer
15.021
25196608WSDLE5
Adder
7.752
25194608D.CRK4
Adder
1.456
252510AF1-249 C
Solar/Wind Harmer
0.368
253338AC1-165 GEN
Solar/Wind Harmer
0.94
253333AC1-068 GEN
Solar/Wind Harmer
0.907
270222AC2-111 GEN
Solar/Wind Harmer
6.022
958171AF2-111 GEN
Solar/Wind Harmer
17.721
25196008MFTGT1
Adder
0.951
972167AH1-666 GEN
Solar/Wind Harmer
5.328
253415AE1-040 GEN
Solar/Wind Harmer
0.71
3429391JKCT 9G
Adder
4.405
970093AG2-073 GEN
Solar/Wind Harmer
4.768
253372AE2-315 SEC3
50/50
2.887
253372AE2-315 SEC3
50/50
2.887
25322309TAIT W
50/50
0.724
963581AG1-207 GEN
50/50
13.121
25306009OHH W.
50/50
4.04
945631AF1-228 GEN
Solar/Wind Harmer
27.993
253349AC2-067 GEN
Solar/Wind Harmer
6.051
253400AC2-068 GEN
Solar/Wind Harmer
2.433
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.426
25196408WSDLE3
Adder
7.98
25196308WSDLE2
Adder
7.91
25196208WSDLE1
Adder
7.89
25196708WSDLE6
Adder
7.87
25196508WSDLE4
Adder
7.672
944031AF1-071 GEN
Solar/Wind Harmer
0.742
25196108MFTGT2
Adder
1.083
25196108MFTGT2
Adder
1.005
270367AC2-061_GEN
Solar/Wind Harmer
2.226
972163AH1-664 GEN
Solar/Wind Harmer
6.547
972165AH1-665 GEN
Solar/Wind Harmer
5.238
339243AC2-075 GEN1
Solar/Wind Harmer
0.267
971673AH1-337 GEN
Solar/Wind Harmer
2.677
971029AG2-637 GEN
Solar/Wind Harmer
8.464
270543AE2-219 C
Solar/Wind Harmer
2.641
3429211JKCT 2G
Adder
5.996
270340AC2-060 GEN
Solar/Wind Harmer
1.535
270520AE2-214 GEN
Solar/Wind Helper
6.73
25326109MON D
50/50
2.075
253370AE2-315 SEC1
50/50
3.053
25322209TAIT E
50/50
14.563
25322209TAIT E
50/50
14.236
270518AE2-148 GEN
Solar/Wind Harmer
59.131
253394AE2-221_GEN
Solar/Wind Harmer
6.215
253398AE2-221_GEN2
Solar/Wind Harmer
6.215
253317AC1-085 GEN4
Solar/Wind Harmer
9.678
25183208HLCRTG
Solar/Wind Harmer
5.448
252519AF1-045_GEN
Solar/Wind Harmer
5.415
252516AE2-318_GEN
Solar/Wind Harmer
4.131
25194408D.CRK1
Adder
6.697
25194508D.CRK3
Adder
1.252
252509AD1-136 GEN
Solar/Wind Harmer
0.2
962581AG1-107 GEN
Solar/Wind Harmer
3.838
961491AF2-440 GEN
Solar/Wind Harmer
1.595
25326509SID D
Adder
0.982
270186AC1-089 GEN
Solar/Wind Harmer
4.095
253378AE2-206_GEN
Solar/Wind Harmer
2.346
276820AF1-078_GEN
Solar/Wind Harmer
1.042
24728805RICHG1
Adder
2.346
24728905RICHG2
Adder
2.346
339221AD2-048_GEN
Solar/Wind Harmer
0.895
972043AH1-570 GEN
Solar/Wind Harmer
1.434
972045AH1-571 GEN
Solar/Wind Harmer
1.147
971125AH1-004 GEN
Solar/Wind Harmer
2.214
970107AG2-081 GEN
Solar/Wind Harmer
1.66
970235AG2-159 GEN
Solar/Wind Harmer
2.174
970235AG2-159 GEN
Solar/Wind Harmer
1.327
970883AG2-550 GEN
Solar/Wind Harmer
5.157
970885AG2-551 GEN
Solar/Wind Harmer
1.199
942891AE2-308 GEN
Solar/Wind Harmer
4.999
960161AF2-307 GEN
Solar/Wind Harmer
3.185
270383AD1-128 GEN
Solar/Wind Harmer
2.921
247621Y3-024
Adder
0.108
946101AF1-275 GEN
Solar/Wind Helper
0.843
270356AE2-297 GEN
Solar/Wind Harmer
2.171
966571AG1-526 GEN
Solar/Wind Harmer
9.951
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.671
270273AD2-016 GEN
Solar/Wind Helper
1.462
270054AF2-122 C O1
Solar/Wind Helper
0.91
253370AE2-315 SEC1
50/50
3.053
253371AE2-315 SEC2
50/50
2.887
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.636
960071AF2-298 GEN
Solar/Wind Harmer
6.599
253432AC1-085 GEN2
Solar/Wind Harmer
0.309
946171AF1-282 GEN
Solar/Wind Harmer
11.554
25194608D.CRK4
Adder
1.456
253343AC1-166 GEN
Solar/Wind Harmer
0.94
253325AC1-069 GEN
Solar/Wind Harmer
0.907
25196808ZIMRHP
Adder
60.49
252507AC2-088 GEN
Solar/Wind Harmer
1.401
25196008MFTGT1
Adder
0.982
945681AF1-233 GEN
Solar/Wind Harmer
12.502
339216AC1-074 GEN
Solar/Wind Harmer
0.987
943111AE2-339 GEN
Solar/Wind Harmer
0.482
3429421JKCT 10G
Adder
4.405
3429241JKCT 3G
Adder
6.075
247536S-71 GEN
Solar/Wind Harmer
1.91
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.863
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.771
MECLTFEXP_MEC->PJM
CLTF
3.185
SIGELTFEXP_SIGE->PJM
CLTF
0.181
CPLELTFEXP_CPLE->PJM
CLTF
0.163
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.25
LAGNLTFEXP_LAGN->PJM
CLTF
3.659
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.452
TVALTFEXP_TVA->PJM
CLTF
1.901
NYPJM->LTFIMP_NY
CLTF
0.872
LGEELTFEXP_LGEE->PJM
CLTF
2.962
WECLTFEXP_WEC->PJM
CLTF
0.651

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:115.08 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1384.41
MW Contribution:5.34
Bus #Bus NameTypeMW Contribution
25326109MON D
50/50
1.972
253370AE2-315 SEC1
50/50
2.874
25322209TAIT E
50/50
13.798
25322209TAIT E
50/50
13.488
270518AE2-148 GEN
Solar/Wind Harmer
59.931
253394AE2-221_GEN
Solar/Wind Harmer
5.257
253398AE2-221_GEN2
Solar/Wind Harmer
5.257
253317AC1-085 GEN4
Solar/Wind Harmer
7.514
25194408D.CRK1
Adder
6.003
25194508D.CRK3
Adder
1.122
252519AF1-045_GEN
Solar/Wind Harmer
4.563
252516AE2-318_GEN
Solar/Wind Harmer
3.481
25183208HLCRTG
Solar/Wind Harmer
4.249
25326509SID D
Adder
0.922
962581AG1-107 GEN
Solar/Wind Harmer
3.295
961491AF2-440 GEN
Solar/Wind Harmer
1.369
252509AD1-136 GEN
Solar/Wind Harmer
0.16
24728805RICHG1
Adder
2.301
24728905RICHG2
Adder
2.301
253378AE2-206_GEN
Solar/Wind Harmer
2.172
276820AF1-078_GEN
Solar/Wind Harmer
0.965
270186AC1-089 GEN
Solar/Wind Harmer
3.342
970883AG2-550 GEN
Solar/Wind Harmer
5.339
970885AG2-551 GEN
Solar/Wind Harmer
1.242
270383AD1-128 GEN
Solar/Wind Harmer
3.062
247621Y3-024
Adder
0.115
970235AG2-159 GEN
Solar/Wind Harmer
1.88
970235AG2-159 GEN
Solar/Wind Harmer
1.148
24379505HDWTR1G C
Solar/Wind Harmer
3.603
270209AC1-174_GEN
Solar/Wind Harmer
2.543
926881AC1-175 GEN
Solar/Wind Harmer
2.543
270201AC2-176 GEN
Solar/Wind Harmer
2.328
964611AG1-324 GEN
Solar/Wind Harmer
0.53
964611AG1-324 GEN
Solar/Wind Harmer
0.235
339221AD2-048_GEN
Solar/Wind Harmer
0.683
972043AH1-570 GEN
Solar/Wind Harmer
1.085
972045AH1-571 GEN
Solar/Wind Harmer
0.868
253370AE2-315 SEC1
50/50
2.874
253371AE2-315 SEC2
50/50
2.718
25322309TAIT W
50/50
0.677
25322209TAIT E
50/50
0.669
253303V4-073 C
Solar/Wind Harmer
0.157
253406AD2-031_GEN
Solar/Wind Harmer
1.252
253316AC1-085 GEN3
Solar/Wind Harmer
7.514
253372AE2-315 SEC3
50/50
2.718
253372AE2-315 SEC3
50/50
2.718
25322309TAIT W
50/50
0.686
963581AG1-207 GEN
50/50
12.455
25306009OHH W.
50/50
3.817
945631AF1-228 GEN
Solar/Wind Harmer
28.545
253349AC2-067 GEN
Solar/Wind Harmer
5.739
253400AC2-068 GEN
Solar/Wind Harmer
2.308
241972AD1-140 GEN
Solar/Wind Harmer
4.762
252524AE2-267 GEN
Solar/Wind Harmer
1.285
25196408WSDLE3
Adder
7.189
25196308WSDLE2
Adder
7.126
25196208WSDLE1
Adder
7.109
25196708WSDLE6
Adder
7.091
25196508WSDLE4
Adder
6.912
944031AF1-071 GEN
Solar/Wind Harmer
0.71
25196108MFTGT2
Adder
0.978
25196108MFTGT2
Adder
0.908
270367AC2-061_GEN
Solar/Wind Harmer
1.873
971673AH1-337 GEN
Solar/Wind Harmer
2.703
971029AG2-637 GEN
Solar/Wind Harmer
8.599
270543AE2-219 C
Solar/Wind Harmer
2.734
270240V3-007_GEN2
Solar/Wind Harmer
2.819
972163AH1-664 GEN
Solar/Wind Harmer
4.555
972165AH1-665 GEN
Solar/Wind Harmer
3.644
961761AG1-017 GEN
Solar/Wind Harmer
0.194
339243AC2-075 GEN1
Solar/Wind Harmer
0.203
270520AE2-214 GEN
Solar/Wind Helper
6.241
270054AF2-122 C O1
Solar/Wind Helper
0.929
253433AC1-085 GEN1
Solar/Wind Harmer
4.77
946181AF1-283 GEN
Solar/Wind Harmer
11.662
25196608WSDLE5
Adder
6.984
25194608D.CRK4
Adder
1.305
252510AF1-249 C
Solar/Wind Harmer
0.328
270222AC2-111 GEN
Solar/Wind Harmer
5.764
25196008MFTGT1
Adder
0.859
270356AE2-297 GEN
Solar/Wind Harmer
2.217
958171AF2-111 GEN
Solar/Wind Harmer
11.967
972167AH1-666 GEN
Solar/Wind Harmer
3.682
270437AC2-090 C
Solar/Wind Harmer
2.544
962031AG1-047 GEN
Solar/Wind Harmer
1.368
957741AF2-068 GEN
Solar/Wind Harmer
6.791
946031AF1-268 GEN
Solar/Wind Harmer
3.646
960801AF2-371 GEN
Solar/Wind Helper
0.823
964871AG1-351 GEN
Solar/Wind Helper
0.569
241955AC1-078 GEN
Solar/Wind Helper
1.555
253338AC1-165 GEN
Solar/Wind Helper
0.737
253333AC1-068 GEN
Solar/Wind Helper
0.763
270273AD2-016 GEN
Solar/Wind Helper
1.456
253370AE2-315 SEC1
50/50
2.874
253371AE2-315 SEC2
50/50
2.718
25322309TAIT W
50/50
0.677
25322209TAIT E
50/50
0.678
25326309TAIT D
50/50
1.55
960071AF2-298 GEN
Solar/Wind Harmer
6.251
253432AC1-085 GEN2
Solar/Wind Harmer
0.24
946171AF1-282 GEN
Solar/Wind Harmer
8.971
25194608D.CRK4
Adder
1.305
25196808ZIMRHP
Adder
48.8
25196008MFTGT1
Adder
0.887
252507AC2-088 GEN
Solar/Wind Harmer
1.122
247536S-71 GEN
Solar/Wind Harmer
2.017
945681AF1-233 GEN
Solar/Wind Harmer
8.649
942081AE2-220 GEN
Solar/Wind Harmer
2.913
270239V3-007_GEN1
Solar/Wind Harmer
0.784
339216AC1-074 GEN
Solar/Wind Harmer
0.75
253343AC1-166 GEN
Solar/Wind Helper
0.737
253325AC1-069 GEN
Solar/Wind Helper
0.763
270349AD2-093_GEN
Solar/Wind Helper
0.679
946101AF1-275 GEN
Solar/Wind Helper
0.782
270471AD2-092_GEN
Solar/Wind Helper
0.679
CBM West 1LTFEXP_CBM-W1->PJM
CBM
30.395
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.735
MECLTFEXP_MEC->PJM
CLTF
4.352
SIGELTFEXP_SIGE->PJM
CLTF
0.183
CPLELTFEXP_CPLE->PJM
CLTF
0.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.791
LAGNLTFEXP_LAGN->PJM
CLTF
4.028
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.362
TVALTFEXP_TVA->PJM
CLTF
1.964
NYPJM->LTFIMP_NY
CLTF
0.978
LGEELTFEXP_LGEE->PJM
CLTF
2.729
WECLTFEXP_WEC->PJM
CLTF
1.007
AG2-052LTFEXP_AG2-052->PJM
LTF
0.064
AH1-155LTFEXP_AH1-155->PJM
LTF
0.096

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-2
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:103.58 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1246.02
MW Contribution:5.42
Bus #Bus NameTypeMW Contribution
253372AE2-315 SEC3
50/50
2.797
253372AE2-315 SEC3
50/50
2.797
25322309TAIT W
50/50
0.707
963581AG1-207 GEN
50/50
12.873
25306009OHH W.
50/50
3.93
945631AF1-228 GEN
Solar/Wind Harmer
28.95
253349AC2-067 GEN
Solar/Wind Harmer
5.914
253400AC2-068 GEN
Solar/Wind Harmer
2.378
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.318
25196408WSDLE3
Adder
7.373
25196308WSDLE2
Adder
7.309
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.689
253303V4-073 C
Solar/Wind Harmer
0.161
253406AD2-031_GEN
Solar/Wind Harmer
1.299
253316AC1-085 GEN3
Solar/Wind Harmer
7.79
253433AC1-085 GEN1
Solar/Wind Harmer
4.945
946181AF1-283 GEN
Solar/Wind Harmer
12.09
25326109MON D
50/50
2.033
253370AE2-315 SEC1
50/50
2.957
25322209TAIT E
50/50
14.212
25322209TAIT E
50/50
13.892
270518AE2-148 GEN
Solar/Wind Harmer
60.837
253394AE2-221_GEN
Solar/Wind Harmer
5.421
253398AE2-221_GEN2
Solar/Wind Harmer
5.421
253317AC1-085 GEN4
Solar/Wind Harmer
7.79
25194408D.CRK1
Adder
6.158
25194508D.CRK3
Adder
1.151
252519AF1-045_GEN
Solar/Wind Harmer
4.698
252516AE2-318_GEN
Solar/Wind Harmer
3.584
25326509SID D
Adder
0.978
25183208HLCRTG
Solar/Wind Harmer
4.398
962581AG1-107 GEN
Solar/Wind Harmer
3.42
961491AF2-440 GEN
Solar/Wind Harmer
1.421
253378AE2-206_GEN
Solar/Wind Harmer
2.357
276820AF1-078_GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Harmer
0.165
24728805RICHG1
Adder
2.37
24728905RICHG2
Adder
2.37
270186AC1-089 GEN
Solar/Wind Harmer
3.469
970883AG2-550 GEN
Solar/Wind Harmer
5.423
970885AG2-551 GEN
Solar/Wind Harmer
1.261
270383AD1-128 GEN
Solar/Wind Harmer
3.26
24379505HDWTR1G C
Solar/Wind Harmer
4.037
270209AC1-174_GEN
Solar/Wind Harmer
2.849
926881AC1-175 GEN
Solar/Wind Harmer
2.849
944541AF1-119 GEN
Solar/Wind Harmer
2.028
960971AF2-388 GEN
Solar/Wind Harmer
5.293
247621Y3-024
Adder
0.115
970235AG2-159 GEN
Solar/Wind Harmer
1.869
970235AG2-159 GEN
Solar/Wind Harmer
1.141
964611AG1-324 GEN
Solar/Wind Harmer
0.54
964611AG1-324 GEN
Solar/Wind Harmer
0.24
270201AC2-176 GEN
Solar/Wind Harmer
2.339
970825AG2-519 GEN
Solar/Wind Harmer
4.771
339221AD2-048_GEN
Solar/Wind Harmer
0.691
960441AF2-335 GEN
Solar/Wind Harmer
4.409
972043AH1-570 GEN
Solar/Wind Harmer
1.097
972045AH1-571 GEN
Solar/Wind Harmer
0.878
946101AF1-275 GEN
Solar/Wind Helper
0.711
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.698
25326309TAIT D
50/50
1.596
960071AF2-298 GEN
Solar/Wind Harmer
6.443
253432AC1-085 GEN2
Solar/Wind Harmer
0.249
946171AF1-282 GEN
Solar/Wind Harmer
9.3
25194608D.CRK4
Adder
1.339
25196808ZIMRHP
Adder
50.253
25196008MFTGT1
Adder
0.903
252507AC2-088 GEN
Solar/Wind Harmer
1.156
942081AE2-220 GEN
Solar/Wind Harmer
3.264
270239V3-007_GEN1
Solar/Wind Harmer
0.878
247536S-71 GEN
Solar/Wind Harmer
2.035
958861AF2-177 GEN
Solar/Wind Harmer
5.292
965651AG1-433 GEN
Solar/Wind Harmer
2.646
945371AF1-202 GEN
Solar/Wind Harmer
3.378
270005AE1-210 C O1
Solar/Wind Harmer
2.645
965031AG1-367 GEN
Solar/Wind Harmer
4.839
945681AF1-233 GEN
Solar/Wind Harmer
8.93
970825AG2-519 GEN
Solar/Wind Harmer
1.065
339216AC1-074 GEN
Solar/Wind Harmer
0.759
253343AC1-166 GEN
Solar/Wind Helper
0.659
253325AC1-069 GEN
Solar/Wind Helper
0.683
25196608WSDLE5
Adder
7.162
25194608D.CRK4
Adder
1.339
252510AF1-249 C
Solar/Wind Harmer
0.337
270222AC2-111 GEN
Solar/Wind Harmer
5.95
25196008MFTGT1
Adder
0.875
270437AC2-090 C
Solar/Wind Harmer
2.85
270356AE2-297 GEN
Solar/Wind Harmer
2.265
958171AF2-111 GEN
Solar/Wind Harmer
12.391
944531AF1-118 GEN
Solar/Wind Harmer
16.954
958821AF2-173 GEN
Solar/Wind Harmer
6.775
270004AE1-209 GEN
Solar/Wind Harmer
2.645
972167AH1-666 GEN
Solar/Wind Harmer
3.803
946031AF1-268 GEN
Solar/Wind Harmer
3.894
962031AG1-047 GEN
Solar/Wind Harmer
1.375
957741AF2-068 GEN
Solar/Wind Harmer
6.824
960801AF2-371 GEN
Solar/Wind Helper
0.736
964871AG1-351 GEN
Solar/Wind Helper
0.508
241955AC1-078 GEN
Solar/Wind Helper
1.347
25196208WSDLE1
Adder
7.291
25196708WSDLE6
Adder
7.272
25196508WSDLE4
Adder
7.089
944031AF1-071 GEN
Solar/Wind Harmer
0.733
25196108MFTGT2
Adder
0.996
25196108MFTGT2
Adder
0.924
270367AC2-061_GEN
Solar/Wind Harmer
1.945
971673AH1-337 GEN
Solar/Wind Harmer
2.763
971029AG2-637 GEN
Solar/Wind Harmer
8.781
270543AE2-219 C
Solar/Wind Harmer
2.777
270240V3-007_GEN2
Solar/Wind Harmer
3.159
24729505KEY G4
Adder
3.142
958711AF2-162 GEN
Solar/Wind Harmer
0.49
965101AG1-375 GEN
Solar/Wind Harmer
4.842
945581AF1-223 GEN
Solar/Wind Harmer
2.196
972163AH1-664 GEN
Solar/Wind Harmer
4.698
972165AH1-665 GEN
Solar/Wind Harmer
3.758
961761AG1-017 GEN
Solar/Wind Harmer
0.195
339243AC2-075 GEN1
Solar/Wind Harmer
0.205
970115AG2-085 GEN
Solar/Wind Harmer
1.763
270520AE2-214 GEN
Solar/Wind Helper
5.68
270054AF2-122 C O1
Solar/Wind Helper
0.769
253338AC1-165 GEN
Solar/Wind Helper
0.659
253333AC1-068 GEN
Solar/Wind Helper
0.683
270273AD2-016 GEN
Solar/Wind Helper
1.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.583
MECLTFEXP_MEC->PJM
CLTF
2.702
SIGELTFEXP_SIGE->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.102
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.934
LAGNLTFEXP_LAGN->PJM
CLTF
3.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.138
TVALTFEXP_TVA->PJM
CLTF
1.63
NYPJM->LTFIMP_NY
CLTF
0.756
LGEELTFEXP_LGEE->PJM
CLTF
2.605
WECLTFEXP_WEC->PJM
CLTF
0.534

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P1-2_#762_8072_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#762_8072_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.19 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1229.31
MW Contribution:3.59
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
3.051
25326109MON D
50/50
2.074
253370AE2-315 SEC1
50/50
3.051
25322209TAIT E
50/50
14.556
25322209TAIT E
50/50
14.229
270518AE2-148 GEN
Solar/Wind Harmer
2.944
253394AE2-221_GEN
Solar/Wind Harmer
0.012
253398AE2-221_GEN2
Solar/Wind Harmer
0.012
253317AC1-085 GEN4
Solar/Wind Harmer
0.005
25183208HLCRTG
Solar/Wind Harmer
0.01
252519AF1-045_GEN
Solar/Wind Harmer
5.411
252516AE2-318_GEN
Solar/Wind Harmer
4.799
25194408D.CRK1
Adder
6.692
25194508D.CRK3
Adder
1.251
252509AD1-136 GEN
Solar/Wind Harmer
0.028
962581AG1-107 GEN
Solar/Wind Harmer
0.001
25326509SID D
Adder
0.981
270186AC1-089 GEN
Solar/Wind Harmer
0.003
253378AE2-206_GEN
Solar/Wind Harmer
0.002
276820AF1-078_GEN
Solar/Wind Harmer
0.001
970329AG2-216 GEN
Solar/Wind Harmer
1.963
24728805RICHG1
Adder
2.343
24728905RICHG2
Adder
2.343
339221AD2-048_GEN
Solar/Wind Harmer
0.002
972043AH1-570 GEN
Solar/Wind Harmer
1.039
972045AH1-571 GEN
Solar/Wind Harmer
0.833
971125AH1-004 GEN
Solar/Wind Harmer
1.542
970107AG2-081 GEN
Solar/Wind Harmer
1.157
970235AG2-159 GEN
Solar/Wind Harmer
2.31
970235AG2-159 GEN
Solar/Wind Harmer
1.325
970883AG2-550 GEN
Solar/Wind Harmer
3.593
970885AG2-551 GEN
Solar/Wind Harmer
1.198
942891AE2-308 GEN
Solar/Wind Harmer
3.483
960161AF2-307 GEN
Solar/Wind Harmer
2.281
270383AD1-128 GEN
Solar/Wind Harmer
0.002
247621Y3-024
Adder
0.107
946101AF1-275 GEN
Solar/Wind Helper
0.844
253370AE2-315 SEC1
50/50
3.051
253371AE2-315 SEC2
50/50
2.886
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.715
25326309TAIT D
50/50
1.635
960071AF2-298 GEN
Solar/Wind Harmer
4.595
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
8.056
25194608D.CRK4
Adder
1.455
253343AC1-166 GEN
Solar/Wind Harmer
0.003
253325AC1-069 GEN
Solar/Wind Harmer
0.009
270159DARBY CT4
Adder
7.297
25196808ZIMRHP
Adder
60.434
252507AC2-088 GEN
Solar/Wind Harmer
0.247
25196008MFTGT1
Adder
0.981
945681AF1-233 GEN
Solar/Wind Harmer
8.713
339216AC1-074 GEN
Solar/Wind Harmer
0.112
3429421JKCT 10G
Adder
4.399
3429241JKCT 3G
Adder
6.066
970773AG2-487 GEN
Solar/Wind Harmer
0.586
247536S-71 GEN
Solar/Wind Harmer
0.132
253372AE2-315 SEC3
50/50
2.886
253372AE2-315 SEC3
50/50
2.886
25322309TAIT W
50/50
0.723
963581AG1-207 GEN
50/50
13.114
25306009OHH W.
50/50
4.038
945631AF1-228 GEN
Solar/Wind Harmer
0
253349AC2-067 GEN
Solar/Wind Harmer
2.666
253400AC2-068 GEN
Solar/Wind Harmer
1.072
241972AD1-140 GEN
Solar/Wind Harmer
0.856
252524AE2-267 GEN
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
7.973
25196308WSDLE2
Adder
7.904
25196208WSDLE1
Adder
7.884
25196708WSDLE6
Adder
7.864
25196508WSDLE4
Adder
7.666
270156DARBY CT1
Adder
7.416
270157DARBY CT2
Adder
7.397
270158DARBY CT3
Adder
7.279
25196108MFTGT2
Adder
1.081
25196108MFTGT2
Adder
1.004
270367AC2-061_GEN
Solar/Wind Harmer
0.004
972163AH1-664 GEN
Solar/Wind Harmer
5.08
972165AH1-665 GEN
Solar/Wind Harmer
4.068
339243AC2-075 GEN1
Solar/Wind Harmer
0.001
971673AH1-337 GEN
Solar/Wind Harmer
2.635
971029AG2-637 GEN
Solar/Wind Harmer
5.898
270543AE2-219 C
Solar/Wind Harmer
0.002
3429211JKCT 2G
Adder
5.988
270340AC2-060 GEN
Solar/Wind Harmer
0.004
270520AE2-214 GEN
Solar/Wind Helper
6.734
270054AF2-122 C O1
Solar/Wind Helper
0.911
253371AE2-315 SEC2
50/50
2.886
25322309TAIT W
50/50
0.715
25322209TAIT E
50/50
0.706
970191AG2-125 GEN
Solar/Wind Harmer
2.178
253406AD2-031_GEN
Solar/Wind Harmer
0.612
253316AC1-085 GEN3
Solar/Wind Harmer
0.005
253433AC1-085 GEN1
Solar/Wind Harmer
0.004
946181AF1-283 GEN
Solar/Wind Harmer
10.473
25196608WSDLE5
Adder
7.745
25194608D.CRK4
Adder
1.455
252510AF1-249 C
Solar/Wind Harmer
0.047
253338AC1-165 GEN
Solar/Wind Harmer
0.003
253333AC1-068 GEN
Solar/Wind Harmer
0.009
270222AC2-111 GEN
Solar/Wind Harmer
2.609
958171AF2-111 GEN
Solar/Wind Harmer
12.35
25196008MFTGT1
Adder
0.95
972167AH1-666 GEN
Solar/Wind Harmer
3.713
253415AE1-040 GEN
Solar/Wind Harmer
0.002
3429391JKCT 9G
Adder
4.399
970093AG2-073 GEN
Solar/Wind Harmer
3.322
270356AE2-297 GEN
Solar/Wind Harmer
0.004
966571AG1-526 GEN
Solar/Wind Harmer
6.932
960801AF2-371 GEN
Solar/Wind Helper
0.866
964871AG1-351 GEN
Solar/Wind Helper
0.598
241955AC1-078 GEN
Solar/Wind Helper
1.673
270273AD2-016 GEN
Solar/Wind Helper
1.465
CBM West 1LTFEXP_CBM-W1->PJM
CBM
19.756
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.743
MECLTFEXP_MEC->PJM
CLTF
3.173
SIGELTFEXP_SIGE->PJM
CLTF
0.18
CPLELTFEXP_CPLE->PJM
CLTF
0.155
CBM West 2LTFEXP_CBM-W2->PJM
CBM
30.151
LAGNLTFEXP_LAGN->PJM
CLTF
3.644
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.43
TVALTFEXP_TVA->PJM
CLTF
1.893
NYPJM->LTFIMP_NY
CLTF
0.877
LGEELTFEXP_LGEE->PJM
CLTF
2.957
WECLTFEXP_WEC->PJM
CLTF
0.648

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P7-1_#11019___SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11019___SRT-A-1
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:102.16 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1229.04
MW Contribution:5.42
Bus #Bus NameTypeMW Contribution
25326109MON D
50/50
2.033
253370AE2-315 SEC1
50/50
2.957
25322209TAIT E
50/50
14.212
25322209TAIT E
50/50
13.892
270518AE2-148 GEN
Solar/Wind Harmer
60.837
253394AE2-221_GEN
Solar/Wind Harmer
5.421
253398AE2-221_GEN2
Solar/Wind Harmer
5.421
253317AC1-085 GEN4
Solar/Wind Harmer
7.79
25194408D.CRK1
Adder
6.158
25194508D.CRK3
Adder
1.151
252519AF1-045_GEN
Solar/Wind Harmer
4.698
252516AE2-318_GEN
Solar/Wind Harmer
3.584
25326509SID D
Adder
0.978
25183208HLCRTG
Solar/Wind Harmer
4.398
962581AG1-107 GEN
Solar/Wind Harmer
3.42
961491AF2-440 GEN
Solar/Wind Harmer
1.421
253378AE2-206_GEN
Solar/Wind Harmer
2.357
276820AF1-078_GEN
Solar/Wind Harmer
1.047
252509AD1-136 GEN
Solar/Wind Harmer
0.165
24728805RICHG1
Adder
2.37
24728905RICHG2
Adder
2.37
270186AC1-089 GEN
Solar/Wind Harmer
3.469
970883AG2-550 GEN
Solar/Wind Harmer
5.423
970885AG2-551 GEN
Solar/Wind Harmer
1.261
270383AD1-128 GEN
Solar/Wind Harmer
3.26
24379505HDWTR1G C
Solar/Wind Harmer
4.037
270209AC1-174_GEN
Solar/Wind Harmer
2.849
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.698
25326309TAIT D
50/50
1.596
960071AF2-298 GEN
Solar/Wind Harmer
6.443
253432AC1-085 GEN2
Solar/Wind Harmer
0.249
946171AF1-282 GEN
Solar/Wind Harmer
9.3
25194608D.CRK4
Adder
1.339
25196808ZIMRHP
Adder
50.253
25196008MFTGT1
Adder
0.903
252507AC2-088 GEN
Solar/Wind Harmer
1.156
942081AE2-220 GEN
Solar/Wind Harmer
3.264
270239V3-007_GEN1
Solar/Wind Harmer
0.878
247536S-71 GEN
Solar/Wind Harmer
2.035
958861AF2-177 GEN
Solar/Wind Harmer
5.292
965651AG1-433 GEN
Solar/Wind Harmer
2.646
945371AF1-202 GEN
Solar/Wind Harmer
3.378
270005AE1-210 C O1
Solar/Wind Harmer
2.645
965031AG1-367 GEN
Solar/Wind Harmer
4.839
945681AF1-233 GEN
Solar/Wind Harmer
8.93
970825AG2-519 GEN
Solar/Wind Harmer
1.065
339216AC1-074 GEN
Solar/Wind Harmer
0.759
253343AC1-166 GEN
Solar/Wind Helper
0.659
253325AC1-069 GEN
Solar/Wind Helper
0.683
926881AC1-175 GEN
Solar/Wind Harmer
2.849
944541AF1-119 GEN
Solar/Wind Harmer
2.028
960971AF2-388 GEN
Solar/Wind Harmer
5.293
247621Y3-024
Adder
0.115
970235AG2-159 GEN
Solar/Wind Harmer
1.869
970235AG2-159 GEN
Solar/Wind Harmer
1.141
964611AG1-324 GEN
Solar/Wind Harmer
0.54
964611AG1-324 GEN
Solar/Wind Harmer
0.24
270201AC2-176 GEN
Solar/Wind Harmer
2.339
970825AG2-519 GEN
Solar/Wind Harmer
4.771
339221AD2-048_GEN
Solar/Wind Harmer
0.691
960441AF2-335 GEN
Solar/Wind Harmer
4.409
972043AH1-570 GEN
Solar/Wind Harmer
1.097
972045AH1-571 GEN
Solar/Wind Harmer
0.878
946101AF1-275 GEN
Solar/Wind Helper
0.711
253372AE2-315 SEC3
50/50
2.797
253372AE2-315 SEC3
50/50
2.797
25322309TAIT W
50/50
0.707
963581AG1-207 GEN
50/50
12.873
25306009OHH W.
50/50
3.93
945631AF1-228 GEN
Solar/Wind Harmer
28.95
253349AC2-067 GEN
Solar/Wind Harmer
5.914
253400AC2-068 GEN
Solar/Wind Harmer
2.378
241972AD1-140 GEN
Solar/Wind Harmer
5.03
252524AE2-267 GEN
Solar/Wind Harmer
1.318
25196408WSDLE3
Adder
7.373
25196308WSDLE2
Adder
7.309
25196208WSDLE1
Adder
7.291
25196708WSDLE6
Adder
7.272
25196508WSDLE4
Adder
7.089
944031AF1-071 GEN
Solar/Wind Harmer
0.733
25196108MFTGT2
Adder
0.996
25196108MFTGT2
Adder
0.924
270367AC2-061_GEN
Solar/Wind Harmer
1.945
971673AH1-337 GEN
Solar/Wind Harmer
2.763
971029AG2-637 GEN
Solar/Wind Harmer
8.781
270543AE2-219 C
Solar/Wind Harmer
2.777
270240V3-007_GEN2
Solar/Wind Harmer
3.159
24729505KEY G4
Adder
3.142
958711AF2-162 GEN
Solar/Wind Harmer
0.49
965101AG1-375 GEN
Solar/Wind Harmer
4.842
945581AF1-223 GEN
Solar/Wind Harmer
2.196
972163AH1-664 GEN
Solar/Wind Harmer
4.698
972165AH1-665 GEN
Solar/Wind Harmer
3.758
961761AG1-017 GEN
Solar/Wind Harmer
0.195
339243AC2-075 GEN1
Solar/Wind Harmer
0.205
970115AG2-085 GEN
Solar/Wind Harmer
1.763
270520AE2-214 GEN
Solar/Wind Helper
5.68
270054AF2-122 C O1
Solar/Wind Helper
0.769
253370AE2-315 SEC1
50/50
2.957
253371AE2-315 SEC2
50/50
2.797
25322309TAIT W
50/50
0.698
25322209TAIT E
50/50
0.689
253303V4-073 C
Solar/Wind Harmer
0.161
253406AD2-031_GEN
Solar/Wind Harmer
1.299
253316AC1-085 GEN3
Solar/Wind Harmer
7.79
253433AC1-085 GEN1
Solar/Wind Harmer
4.945
946181AF1-283 GEN
Solar/Wind Harmer
12.09
25196608WSDLE5
Adder
7.162
25194608D.CRK4
Adder
1.339
252510AF1-249 C
Solar/Wind Harmer
0.337
270222AC2-111 GEN
Solar/Wind Harmer
5.95
25196008MFTGT1
Adder
0.875
270437AC2-090 C
Solar/Wind Harmer
2.85
270356AE2-297 GEN
Solar/Wind Harmer
2.265
958171AF2-111 GEN
Solar/Wind Harmer
12.391
958821AF2-173 GEN
Solar/Wind Harmer
6.775
270004AE1-209 GEN
Solar/Wind Harmer
2.645
972167AH1-666 GEN
Solar/Wind Harmer
3.803
946031AF1-268 GEN
Solar/Wind Harmer
3.894
962031AG1-047 GEN
Solar/Wind Harmer
1.375
957741AF2-068 GEN
Solar/Wind Harmer
6.824
960801AF2-371 GEN
Solar/Wind Helper
0.736
964871AG1-351 GEN
Solar/Wind Helper
0.508
241955AC1-078 GEN
Solar/Wind Helper
1.347
253338AC1-165 GEN
Solar/Wind Helper
0.659
253333AC1-068 GEN
Solar/Wind Helper
0.683
270273AD2-016 GEN
Solar/Wind Helper
1.278
CBM West 1LTFEXP_CBM-W1->PJM
CBM
16.384
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.583
MECLTFEXP_MEC->PJM
CLTF
2.702
SIGELTFEXP_SIGE->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.102
CBM West 2LTFEXP_CBM-W2->PJM
CBM
26.934
LAGNLTFEXP_LAGN->PJM
CLTF
3.146
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.138
TVALTFEXP_TVA->PJM
CLTF
1.63
NYPJM->LTFIMP_NY
CLTF
0.756
LGEELTFEXP_LGEE->PJM
CLTF
2.605
WECLTFEXP_WEC->PJM
CLTF
0.534

Details for AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line l/o AEP_P2-2_#7222_05MALIS 765_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-228 TP-05BEATTY 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#7222_05MALIS 765_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:101.86 %
Rating:1203.0 MVA
Rating Type:B
MVA to Mitigate:1225.43
MW Contribution:5.02
Bus #Bus NameTypeMW Contribution
253370AE2-315 SEC1
50/50
2.915
253371AE2-315 SEC2
50/50
2.757
25322309TAIT W
50/50
0.688
25322209TAIT E
50/50
0.689
253370AE2-315 SEC1
50/50
2.915
253371AE2-315 SEC2
50/50
2.757
25322309TAIT W
50/50
0.688
25322209TAIT E
50/50
0.68
253303V4-073 C
Solar/Wind Harmer
0.159
253406AD2-031_GEN
Solar/Wind Harmer
1.275
253316AC1-085 GEN3
Solar/Wind Harmer
7.64
253433AC1-085 GEN1
Solar/Wind Harmer
4.85
946181AF1-283 GEN
Solar/Wind Harmer
11.858
25196608WSDLE5
Adder
6.983
25194608D.CRK4
Adder
1.304
252510AF1-249 C
Solar/Wind Harmer
0.328
270222AC2-111 GEN
Solar/Wind Harmer
5.637
25196008MFTGT1
Adder
0.847
958171AF2-111 GEN
Solar/Wind Harmer
12.038
972167AH1-666 GEN
Solar/Wind Harmer
3.699
270356AE2-297 GEN
Solar/Wind Harmer
2.052
960801AF2-371 GEN
Solar/Wind Helper
0.775
964871AG1-351 GEN
Solar/Wind Helper
0.535
241955AC1-078 GEN
Solar/Wind Helper
1.426
253338AC1-165 GEN
Solar/Wind Helper
0.694
253333AC1-068 GEN
Solar/Wind Helper
0.719
270273AD2-016 GEN
Solar/Wind Helper
1.358
25326109MON D
50/50
2.008
253370AE2-315 SEC1
50/50
2.915
25322209TAIT E
50/50
14.016
25322209TAIT E
50/50
13.701
270518AE2-148 GEN
Solar/Wind Harmer
60.442
253394AE2-221_GEN
Solar/Wind Harmer
5.337
253398AE2-221_GEN2
Solar/Wind Harmer
5.337
253317AC1-085 GEN4
Solar/Wind Harmer
7.64
25194408D.CRK1
Adder
6.001
25194508D.CRK3
Adder
1.122
252519AF1-045_GEN
Solar/Wind Harmer
4.584
252516AE2-318_GEN
Solar/Wind Harmer
3.497
25326509SID D
Adder
0.981
25183208HLCRTG
Solar/Wind Harmer
4.288
962581AG1-107 GEN
Solar/Wind Harmer
3.343
961491AF2-440 GEN
Solar/Wind Harmer
1.389
253378AE2-206_GEN
Solar/Wind Harmer
2.369
276820AF1-078_GEN
Solar/Wind Harmer
1.052
252509AD1-136 GEN
Solar/Wind Harmer
0.161
24728805RICHG1
Adder
2.209
24728905RICHG2
Adder
2.209
270186AC1-089 GEN
Solar/Wind Harmer
3.383
970883AG2-550 GEN
Solar/Wind Harmer
5.018
970885AG2-551 GEN
Solar/Wind Harmer
1.167
270383AD1-128 GEN
Solar/Wind Harmer
2.82
970235AG2-159 GEN
Solar/Wind Harmer
1.829
970235AG2-159 GEN
Solar/Wind Harmer
1.116
247621Y3-024
Adder
0.106
339221AD2-048_GEN
Solar/Wind Harmer
0.675
946101AF1-275 GEN
Solar/Wind Helper
0.74
253372AE2-315 SEC3
50/50
2.757
253372AE2-315 SEC3
50/50
2.757
25322309TAIT W
50/50
0.697
963581AG1-207 GEN
50/50
12.726
25306009OHH W.
50/50
3.868
945631AF1-228 GEN
Solar/Wind Harmer
28.775
253349AC2-067 GEN
Solar/Wind Harmer
5.805
253400AC2-068 GEN
Solar/Wind Harmer
2.334
241972AD1-140 GEN
Solar/Wind Harmer
4.931
252524AE2-267 GEN
Solar/Wind Harmer
1.285
25196408WSDLE3
Adder
7.188
25196308WSDLE2
Adder
7.126
25196208WSDLE1
Adder
7.108
25196708WSDLE6
Adder
7.09
25196508WSDLE4
Adder
6.911
944031AF1-071 GEN
Solar/Wind Harmer
0.695
25196108MFTGT2
Adder
0.964
25196108MFTGT2
Adder
0.896
270367AC2-061_GEN
Solar/Wind Harmer
1.897
971673AH1-337 GEN
Solar/Wind Harmer
2.578
971029AG2-637 GEN
Solar/Wind Harmer
8.171
270543AE2-219 C
Solar/Wind Harmer
2.569
972163AH1-664 GEN
Solar/Wind Harmer
4.572
972165AH1-665 GEN
Solar/Wind Harmer
3.658
339243AC2-075 GEN1
Solar/Wind Harmer
0.201
270520AE2-214 GEN
Solar/Wind Helper
5.906
270054AF2-122 C O1
Solar/Wind Helper
0.848
25326309TAIT D
50/50
1.575
960071AF2-298 GEN
Solar/Wind Harmer
6.35
253432AC1-085 GEN2
Solar/Wind Harmer
0.244
946171AF1-282 GEN
Solar/Wind Harmer
9.121
25194608D.CRK4
Adder
1.304
25196808ZIMRHP
Adder
48.855
25196008MFTGT1
Adder
0.875
252507AC2-088 GEN
Solar/Wind Harmer
1.125
247536S-71 GEN
Solar/Wind Harmer
1.874
945681AF1-233 GEN
Solar/Wind Harmer
8.689
339216AC1-074 GEN
Solar/Wind Harmer
0.741
253343AC1-166 GEN
Solar/Wind Helper
0.694
253325AC1-069 GEN
Solar/Wind Helper
0.719
CBM West 1LTFEXP_CBM-W1->PJM
CBM
22.852
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.871
MECLTFEXP_MEC->PJM
CLTF
3.363
SIGELTFEXP_SIGE->PJM
CLTF
0.165
CPLELTFEXP_CPLE->PJM
CLTF
0.113
CBM West 2LTFEXP_CBM-W2->PJM
CBM
28.899
LAGNLTFEXP_LAGN->PJM
CLTF
3.446
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.245
TVALTFEXP_TVA->PJM
CLTF
1.732
NYPJM->LTFIMP_NY
CLTF
0.854
LGEELTFEXP_LGEE->PJM
CLTF
2.577
WECLTFEXP_WEC->PJM
CLTF
0.735

Details for AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AG1-410 TP-05MADDOX 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:138.82 %
Rating:1868.0 MVA
Rating Type:B
MVA to Mitigate:2593.18
MW Contribution:3.91
Bus #Bus NameTypeMW Contribution
24727205RPMNG3
50/50
3.292
971599AH1-298 GEN
50/50
10.333
24729505KEY G4
50/50
6.735
24653605MOTTVILLE
50/50
0.003
963791AG1-232 GEN
Solar/Wind Harmer
11.606
965041AG1-368 GEN
Solar/Wind Harmer
8.426
270071AF1-092 GEN
Solar/Wind Harmer
14.399
965051AG1-369 GEN
Solar/Wind Harmer
3.592
270024AE2-089 GEN
Solar/Wind Harmer
0.007
965101AG1-375 GEN
Solar/Wind Harmer
6.088
971771AH1-392 GEN
Solar/Wind Harmer
5.847
971347AH1-153 GEN
Solar/Wind Harmer
8.688
971619AH1-309 GEN
Solar/Wind Harmer
2.601
945581AF1-223 GEN
Solar/Wind Harmer
0
971769AH1-391 GEN
Solar/Wind Harmer
6.283
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
971609AH1-304 GEN
Solar/Wind Harmer
0.89
274814UNIV PK N;0U
Adder
3.782
274807UNIV PK N;3U
Adder
3.774
274805UNIV PK N;1U
Adder
3.758
274811UNIV PK N;7U
Adder
3.75
270536AF1-215 GEN2
Solar/Wind Harmer
0.007
274775LINCOLN ;6U
Adder
6.292
274776LINCOLN ;7U
Adder
6.292
274777LINCOLN ;8U
Adder
6.292
972037AH1-567 GEN1
Adder
0.136
274827FISK ;RP
Adder
5.742
960591AF2-350 GEN
Solar/Wind Harmer
5.147
972227AH1-698 GEN1
Adder
1.919
274687WILL CNTY;4U
Adder
20.447
274687WILL CNTY;4U
Adder
20.447
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
22.401
274675JOLIET 29;7U
Adder
21.601
274728ELWOOD EC;5P
Adder
11.97
274731ELWOOD EC;2P
Adder
11.97
274733ELWOOD EC;3P
Adder
11.97
274735ELWOOD EC;4P
Adder
11.97
970833AG2-524 GEN
Solar/Wind Harmer
5.563
970833AG2-524 GEN
Solar/Wind Harmer
3.709
971611AH1-305 GEN
Solar/Wind Harmer
2.995
274746AC1-111 G10
Adder
4.021
274744AC1-111 GEN8
Adder
4.021
970289AG2-191 GEN
Solar/Wind Harmer
0.942
270594AE1-207 GEN
Solar/Wind Harmer
5.492
276868AE1-113 GEN
Solar/Wind Harmer
0.982
276882AE2-255 GEN
Solar/Wind Harmer
0.572
971177AH1-047 GEN
Solar/Wind Harmer
3.009
971411AH1-196 GEN
Solar/Wind Harmer
7.289
971675AH1-338 GEN
Solar/Wind Harmer
1.894
970115AG2-085 GEN
Solar/Wind Harmer
1.936
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24691005MDL-2G C
Solar/Wind Harmer
0.001
24697605MDL-3G C
Solar/Wind Harmer
0.001
24697905MDL-4G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971171AH1-044 GEN
Solar/Wind Harmer
9.652
274823ROCKFORD ;21
Adder
13.435
276612AE2-035 GEN
Solar/Wind Harmer
0.001
926823AC1-168 GEN
Solar/Wind Harmer
0.811
970169AG2-114 GEN
Solar/Wind Harmer
4.764
971681AH1-341 GEN
Solar/Wind Harmer
7.643
971549AH1-272 GEN
Solar/Wind Harmer
9.793
961011AF2-392 GEN
Solar/Wind Harmer
2.754
957751AF2-069 GEN
Solar/Wind Harmer
0.154
24386205FR-12G C
Solar/Wind Harmer
0.001
24386405FR-21G C
Solar/Wind Harmer
0.001
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
24725505WLD G2 C
Solar/Wind Harmer
0.001
24699105WLD G1 C
Solar/Wind Harmer
0.001
276655WTG1_EQ
Solar/Wind Harmer
0.002
276656WTG2_EQ
Solar/Wind Harmer
0
959341AF2-225 GEN
Solar/Wind Harmer
4.828
941731AE2-173 GEN
Solar/Wind Harmer
3.831
946321AF1-296 GEN
Solar/Wind Harmer
2.545
963841AG1-237 GEN
Solar/Wind Harmer
1.949
270240V3-007_GEN2
Solar/Wind Harmer
0.001
276785W4-005 GEN1
Solar/Wind Harmer
0.001
276174W4-005 GEN2
Solar/Wind Harmer
0.001
276849AB2-070 GEN2
Solar/Wind Harmer
0.156
276848AB2-070 GEN3
Solar/Wind Harmer
0.155
270543AE2-219 C
Solar/Wind Harmer
0.002
944221AF1-090 GEN
Solar/Wind Harmer
2.279
971029AG2-637 GEN
Solar/Wind Harmer
5.242
971673AH1-337 GEN
Solar/Wind Harmer
2.175
247607V1-011 GEN
Solar/Wind Harmer
0.001
957201AF2-014 GEN
Solar/Wind Helper
8.613
270317AD1-130_GEN
Solar/Wind Helper
4.113
966831AG1-554 GEN
Solar/Wind Helper
0.876
270284AF1-227 GEN1
Solar/Wind Helper
1.876
270286AF1-227 GEN2
Solar/Wind Helper
0.688
270287AF1-227 GEN3
Solar/Wind Helper
0.688
270499AE1-146 GEN
Solar/Wind Helper
1.952
945641AF1-229 GEN
Solar/Wind Helper
0.937
965431AG1-411 GEN
50/50
45.408
24727105RPMNG2
50/50
3.32
970583AG2-370 GEN
50/50
2.809
959331AF2-224 GEN
Solar/Wind Harmer
9.634
965021AG1-366 GEN
Solar/Wind Harmer
4.588
970031AG2-029 GEN
Solar/Wind Harmer
5.463
270043AE2-236 GEN
Solar/Wind Harmer
5.191
270191TR4_S_V150
Solar/Wind Harmer
0.001
270247TR4_N_V136
Solar/Wind Harmer
0.046
944531AF1-118 GEN
Solar/Wind Harmer
31.488
971617AH1-308 GEN
Solar/Wind Harmer
5.166
247643Z2-116 C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
4.805
970349AG2-230 GEN
Solar/Wind Harmer
8.688
24642205MAYFLWER
Adder
0.524
24441205WTRV SLR C
Solar/Wind Harmer
0
970513AG2-328 GEN
Solar/Wind Harmer
2.307
970517AG2-330 GEN
Solar/Wind Harmer
13.84
274752CRETE EC ;2U
Adder
6.241
274753CRETE EC ;3U
Adder
6.241
274724RIVER EC ;11
Adder
13.364
247604X1-042
Adder
0.313
270535AF1-215 GEN1
Solar/Wind Harmer
0.007
274772LINCOLN ;3U
Adder
6.292
274802UNIV PARK;5U
Adder
4.319
274826FISK ;BP
Adder
8.102
274800UNIV PARK;3U
Adder
4.307
972038AH1-567 GEN2
Adder
0.27
276806AD2-047 C O1
Solar/Wind Harmer
2.917
970941AG2-585 GEN
Solar/Wind Harmer
6.434
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972228AH1-698 GEN2
Adder
2.725
970707AG2-453 GEN
Solar/Wind Harmer
16.709
276897AD1-100 C
Solar/Wind Harmer
0.007
939351AE1-166 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
21.601
276893AG1-478 C
Solar/Wind Harmer
0.201
274730ELWOOD EC;6P
Adder
11.97
274734ELWOOD EC;8P
Adder
11.97
274736ELWOOD EC;9P
Adder
11.97
274729ELWOOD EC;1P
Adder
11.97
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
943121AE2-341 GEN
Solar/Wind Harmer
8.419
943591AF1-030 GEN
Solar/Wind Harmer
5.599
247642Z2-115 C
Solar/Wind Harmer
0.002
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
274682WAUKEGAN ;7U
Adder
12.782
970289AG2-191 GEN
Solar/Wind Harmer
0.545
970291AG2-192 GEN
Solar/Wind Harmer
0.496
958821AF2-173 GEN
Solar/Wind Harmer
6.901
270004AE1-209 GEN
Solar/Wind Harmer
1.068
276805AD2-038 GEN
Solar/Wind Harmer
0.001
274872LEEDK;1U
Solar/Wind Harmer
0.18
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.518
274855GSG-6 ;RU
Solar/Wind Harmer
0.178
274850MENDOTA H;RU
Solar/Wind Harmer
0.057
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.087
276889AE2-281 GEN
Solar/Wind Harmer
0
24755605MDL-5G
Solar/Wind Harmer
0.001
970781AG2-491 GEN
Solar/Wind Harmer
4.834
959091AF2-200 GEN
Solar/Wind Harmer
9.652
972236AH1-702 GEN2
Adder
1.508
970571AG2-364 GEN
Solar/Wind Harmer
9.558
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
274760LEE CO EC;1U
Adder
6.304
274767LEE CO EC;8U
Adder
6.23
946031AF1-268 GEN
Solar/Wind Harmer
4.492
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
7.069
276157O29GEN1
Solar/Wind Harmer
0.755
274878BISHOP HL;2U
Solar/Wind Harmer
0.156
942111AE2-223 GEN
Solar/Wind Harmer
1.494
965931AG1-462 GEN
Solar/Wind Harmer
11.522
274853TWINGROVE;U1
Solar/Wind Harmer
0.002
965091AG1-374 GEN
Solar/Wind Harmer
13.551
959611AF2-252 GEN
Solar/Wind Harmer
1.506
270437AC2-090 C
Solar/Wind Harmer
0.002
276686W4-005 GEN3
Solar/Wind Harmer
0.001
276668AB2-070 GEN1
Solar/Wind Harmer
0.156
971993AH1-541 GEN
Solar/Wind Harmer
1.971
276621W2-048 GEN
Solar/Wind Harmer
0.211
276838X2-022 GEN2
Solar/Wind Harmer
0.236
942481AE2-261 GEN
Solar/Wind Harmer
12.085
970193AG2-126 GEN
Solar/Wind Harmer
5.861
270404AC1-167 GEN
Solar/Wind Harmer
0.002
270258AD1-119 GEN
Solar/Wind Harmer
0.001
24728705AND G3
Adder
4.272
24728505AND G1
Adder
2.043
270356AE2-297 GEN
Solar/Wind Harmer
0.005
970243AG2-164 GEN
Solar/Wind Harmer
1.812
970519AG2-331 GEN
Solar/Wind Harmer
8.054
970699AG2-449 GEN
Solar/Wind Harmer
0.774
270485AE1-090_GEN
Solar/Wind Helper
0.323
942871AE2-306 GEN
Solar/Wind Helper
0.443
270541AE2-072 C
Solar/Wind Helper
0.932
970615AG2-402 GEN
50/50
4.588
24729405KEY G3
50/50
0.368
24729305KEY G2
50/50
0.361
24729205KEY G1
50/50
0.36
247620Y3-023
50/50
0.463
970611AG2-400 GEN
Solar/Wind Harmer
13.763
970627AG2-408 GEN
Solar/Wind Harmer
4.129
942221AE2-234 GEN
Solar/Wind Harmer
0.034
944541AF1-119 GEN
Solar/Wind Harmer
0.42
960971AF2-388 GEN
Solar/Wind Harmer
3.679
270216AD2-079_GEN
Solar/Wind Harmer
0.001
957891AF2-083 GEN
Solar/Wind Harmer
0.001
961051AF2-396 GEN
Solar/Wind Harmer
11.557
961051AF2-396 GEN
Solar/Wind Harmer
7.705
270526AF1-158 GEN
Solar/Wind Harmer
0.007
24441505OLIV SLR
Solar/Wind Harmer
0
965681AG1-436 GEN
Solar/Wind Harmer
6.887
965791AG1-447 GEN
Solar/Wind Harmer
5.051
270599AE1-208 GEN
Solar/Wind Harmer
4.993
270031AE2-169
Solar/Wind Harmer
2.996
970321AG2-212 GEN
Solar/Wind Harmer
2.307
274808UNIV PK N;4U
Adder
3.733
274770LINCOLN ;1U
Adder
6.292
274771LINCOLN ;2U
Adder
6.292
274803UNIV PARK;6U
Adder
4.319
274888KELLY CRK;1U
Solar/Wind Harmer
0.302
274887GEN-1.85
Solar/Wind Harmer
0.136
276843GEN-1.7
Solar/Wind Harmer
0.167
958011AF2-095 GEN
Solar/Wind Harmer
7.412
972259AH1-714 GEN
Adder
13.99
274674JOLIET 9 ;6U
Adder
11.217
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
0.931
958481AF2-142 GEN
Solar/Wind Harmer
7.482
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
274862TOP CROP ;2U
Solar/Wind Harmer
0.675
274695ROCKY RD ;2P
Adder
7.922
274693ROCKY RD ;1P
Adder
7.844
274697ROCKY RD ;3P
Adder
2.152
274696ROCKY RD ;4P
Adder
8.109
274683WAUKEGAN ;8U
Adder
14.968
274683WAUKEGAN ;8U
Adder
12.617
945421AF1-207 GEN
Solar/Wind Harmer
0
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
962691AG1-118 GEN
Solar/Wind Harmer
14.776
958491AF2-143 GEN
Solar/Wind Harmer
7.388
970921AG2-575 GEN
Solar/Wind Harmer
4.913
970921AG2-575 GEN
Solar/Wind Harmer
1.638
971613AH1-306 GEN
Solar/Wind Harmer
2.354
274879MINONK ;1U
Solar/Wind Harmer
0.207
942991AE2-321 GEN
Solar/Wind Harmer
5.451
971333AH1-146 GEN
Solar/Wind Harmer
9.71
971335AH1-147 GEN
Solar/Wind Harmer
9.71
960441AF2-335 GEN
Solar/Wind Harmer
4.841
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
9.652
971343AH1-151 GEN
Solar/Wind Harmer
9.652
970825AG2-519 GEN
Solar/Wind Harmer
5.324
274856ECOGROVE ;U1
Solar/Wind Harmer
0.113
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
2.689
274764LEE CO EC;5U
Adder
6.319
274765LEE CO EC;6U
Adder
6.319
274762LEE CO EC;3U
Adder
6.304
274763LEE CO EC;4U
Adder
6.245
276603SUBLETTE C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.354
270201AC2-176 GEN
Solar/Wind Harmer
0.001
972267AH1-718 GEN
Adder
2.793
276741O09 GEN1
Solar/Wind Harmer
0.166
276708O09 GEN2
Solar/Wind Harmer
0.166
274851PROVIDENC;RU
Solar/Wind Harmer
0.001
274849CRESCENT ;1U
Solar/Wind Harmer
0.001
276645AC1-214 GEN1
Solar/Wind Harmer
0.183
276646AC1-214 GEN2
Solar/Wind Harmer
0.183
966841AG1-555 GEN
Solar/Wind Harmer
0.525
276782AC1-033 GEN
Solar/Wind Harmer
0.001
247621Y3-024
Adder
0.16
960611AF2-352 GEN
Solar/Wind Harmer
1.506
970241AG2-163 GEN
Solar/Wind Harmer
2.545
24379505HDWTR1G C
Solar/Wind Harmer
0.001
270209AC1-174_GEN
Solar/Wind Harmer
0
926881AC1-175 GEN
Solar/Wind Harmer
0
276763AC1-053 GEN1
Solar/Wind Harmer
0.001
276764AC1-053 GEN2
Solar/Wind Harmer
0.001
270383AD1-128 GEN
Solar/Wind Harmer
0.002
276916AD2-100_GEN
Solar/Wind Harmer
8.413
276911AD2-131_GEN
Solar/Wind Harmer
0.554
970883AG2-550 GEN
Solar/Wind Harmer
3.912
970885AG2-551 GEN
Solar/Wind Harmer
1.304
945391AF1-204 GEN
Solar/Wind Harmer
4.152
970623AG2-406 GEN
Solar/Wind Harmer
0.681
270444AC2-157 GEN1
Solar/Wind Harmer
0.001
971587AH1-292 GEN
Solar/Wind Harmer
2.427
270007AE1-245 C
Solar/Wind Harmer
0.001
970239AG2-162 GEN
Solar/Wind Harmer
0.774
246938BC-WTG3
Solar/Wind Helper
11.083
246937BC-WTG2
Solar/Wind Helper
10.895
270224U2-072_GEN2
Solar/Wind Helper
0.871
270227U2-072_GEN3
Solar/Wind Helper
0.871
270228U2-072_GEN4
Solar/Wind Helper
0.871
270231U2-072_GEN5
Solar/Wind Helper
0.871
270471AD2-092_GEN
Solar/Wind Helper
0.85
253378AE2-206_GEN
Solar/Wind Helper
0.684
276820AF1-078_GEN
Solar/Wind Helper
0.319
241960AC2-195 GEN
Solar/Wind Helper
0.69
24727005RPMNG1
50/50
3.308
960861AF2-377 GEN
50/50
2.399
970521AG2-332 GEN
50/50
10.806
24639705ELKHART HY
50/50
0.149
965421AG1-410 GEN
Solar/Wind Harmer
81.734
965011AG1-365 GEN
Solar/Wind Harmer
13.763
270063AE2-323 C
Solar/Wind Harmer
0.006
247521TR3_G114
Solar/Wind Harmer
0.262
270246TR4_N_V150
Solar/Wind Harmer
0.046
944231AF1-091 GEN
Solar/Wind Harmer
1.854
24695305TIMB G C
Solar/Wind Harmer
0.002
965651AG1-433 GEN
Solar/Wind Harmer
1.839
958861AF2-177 GEN
Solar/Wind Harmer
2.638
945111AF1-176 GEN
Solar/Wind Harmer
10.578
270505AE1-170 C O1
Solar/Wind Harmer
6.07
945371AF1-202 GEN
Solar/Wind Harmer
0
270449AD2-020 GEN
Solar/Wind Harmer
0
943021AE2-325 GEN
Solar/Wind Harmer
2.97
970245AG2-165 GEN
Solar/Wind Harmer
2.307
970373AG2-245 GEN
Solar/Wind Harmer
11.147
274751CRETE EC ;1U
Adder
6.241
274754CRETE EC ;4U
Adder
6.241
274723RIVER EC ;12
Adder
13.527
274812UNIV PK N;8U
Adder
3.75
276164X3-005 C
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0.004
274773LINCOLN ;4U
Adder
6.292
274774LINCOLN ;5U
Adder
6.292
274801UNIV PARK;4U
Adder
4.307
276776AD2-060 GEN
Solar/Wind Harmer
0.537
958381AF2-132 GEN
Solar/Wind Harmer
0.001
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
971917AH1-482 GEN
Solar/Wind Harmer
6.671
941551AE2-152 GEN
Solar/Wind Harmer
0
274676JOLIET 29;8U
Adder
22.401
274674JOLIET 9 ;6U
Adder
11.217
274732ELWOOD EC;7P
Adder
11.97
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
6.288
274745AC1-111 GEN9
Adder
4.021
276691AA1-018 GEN1
Solar/Wind Harmer
0.604
274682WAUKEGAN ;7U
Adder
12.782
970291AG2-192 GEN
Solar/Wind Harmer
0.645
274828WAUKEGAN ;BP
Adder
7.846
270005AE1-210 C O1
Solar/Wind Harmer
1.068
965031AG1-367 GEN
Solar/Wind Harmer
4.929
962781AG1-127 GEN
Solar/Wind Harmer
4.676
939401AE1-172 GEN
Solar/Wind Harmer
3.674
276901AD2-066 C O1
Solar/Wind Harmer
0.005
270032AE2-172
Solar/Wind Harmer
3.269
274872LEEDK;1U
Solar/Wind Harmer
0.003
971997AH1-543 GEN
Solar/Wind Harmer
2.559
276861AD2-134 GEN
Solar/Wind Harmer
0.087
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
24791305MDL-5G
Solar/Wind Harmer
0.001
957471AF2-041 GEN
Solar/Wind Harmer
14.477
959081AF2-199 GEN
Solar/Wind Harmer
4.826
971067AG2-660 GEN
Solar/Wind Harmer
1.609
274822ROCKFORD ;11
Adder
13.533
970825AG2-519 GEN
Solar/Wind Harmer
1.705
972235AH1-702 GEN1
Adder
1.734
970819AG2-516 GEN
Solar/Wind Harmer
5.74
970569AG2-363 GEN
Solar/Wind Harmer
14.338
971475AH1-234 GEN
Solar/Wind Harmer
2.315
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274761LEE CO EC;2U
Adder
6.304
274766LEE CO EC;7U
Adder
6.23
276903AD2-071 C
Solar/Wind Harmer
5.249
276158O29GEN2
Solar/Wind Harmer
0.001
24385905FR-11G C
Solar/Wind Harmer
0.001
24387305FR-4G C
Solar/Wind Harmer
0.002
274877BISHOP HL;1U
Solar/Wind Harmer
0.156
276726Z2-087_GEN
Solar/Wind Harmer
0.001
939741AE1-205 GEN
Solar/Wind Harmer
6.437
274854TWINGROVE;U2
Solar/Wind Harmer
0.002
972175AH1-670 GEN
Solar/Wind Harmer
3.624
963741AG1-226 GEN
Solar/Wind Harmer
10.327
942081AE2-220 GEN
Solar/Wind Harmer
0
270239V3-007_GEN1
Solar/Wind Harmer
0
970613AG2-401 GEN
Solar/Wind Harmer
3.19
247536S-71 GEN
Solar/Wind Harmer
0.173
274880W4-005 GEN4
Solar/Wind Harmer
0.001
963831AG1-236 GEN
Solar/Wind Harmer
1.654
276615X2-022 GEN
Solar/Wind Harmer
0.044
965911AG1-460 GEN
Solar/Wind Harmer
0.808
24728605AND G2
Adder
2.043
970773AG2-487 GEN
Solar/Wind Harmer
0.609
270445AC2-157 GEN2
Solar/Wind Harmer
0.001
970333AG2-219 GEN
Solar/Wind Harmer
2.215
246936BC-WTG1
Solar/Wind Helper
10.895
270462AD2-086
Solar/Wind Helper
3.714
270223U2-072_GEN1
Solar/Wind Helper
0.871
270578AF1-285 GEN2
Solar/Wind Helper
0.59
270391AF1-285 GEN3
Solar/Wind Helper
0.59
247522W1-056 GEN
Solar/Wind Helper
1.168
960841AF2-375 GEN
Solar/Wind Helper
1.175
270349AD2-093_GEN
Solar/Wind Helper
0.85
944201AF1-088_MTX
Adder
55.165
957141AF2-008_MTX
Adder
17.696
990792J1392
External Queue
5.474584102630615
990497J1323
External Queue
1.5914489030838013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
69.309
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.744
MECLTFEXP_MEC->PJM
CLTF
9.656
SIGELTFEXP_SIGE->PJM
CLTF
0.197
CBM West 2LTFEXP_CBM-W2->PJM
CBM
49.944
LAGNLTFEXP_LAGN->PJM
CLTF
5.694
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.439
TVALTFEXP_TVA->PJM
CLTF
2.27
NYPJM->LTFIMP_NY
CLTF
1.265
LGEELTFEXP_LGEE->PJM
CLTF
1.782
WECLTFEXP_WEC->PJM
CLTF
2.624
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.056
AG2-052LTFEXP_AG2-052->PJM
LTF
0.17
AH1-155LTFEXP_AH1-155->PJM
LTF
0.255

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:123.32 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:314.46
MW Contribution:65.61
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
26.562
971673AH1-337 GEN
Solar/Wind Harmer
31.433
971029AG2-637 GEN
Solar/Wind Harmer
100.458
270543AE2-219 C
Solar/Wind Harmer
33.597
970883AG2-550 GEN
Solar/Wind Harmer
65.613
970885AG2-551 GEN
Solar/Wind Harmer
15.259
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.013
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.734
MECLTFEXP_MEC->PJM
CLTF
0.088
SIGELTFEXP_SIGE->PJM
CLTF
0.001
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.355
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.024
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.067
LAGNLTFEXP_LAGN->PJM
CLTF
0.012
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.025
WECLTFEXP_WEC->PJM
CLTF
0.026
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.022

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#10528_05BLUFFP 138_D_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10528_05BLUFFP 138_D_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.68 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:272.02
MW Contribution:65.62
Bus #Bus NameTypeMW Contribution
970883AG2-550 GEN
Solar/Wind Harmer
65.622
970885AG2-551 GEN
Solar/Wind Harmer
15.261
971673AH1-337 GEN
Solar/Wind Harmer
31.437
971029AG2-637 GEN
Solar/Wind Harmer
100.471
270543AE2-219 C
Solar/Wind Harmer
33.602
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.855
MECLTFEXP_MEC->PJM
CLTF
0.102
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.467
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.05
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.003
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.64 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.94
MW Contribution:33.24
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
10.869
247621Y3-024
50/50
0.608
970883AG2-550 GEN
Solar/Wind Harmer
33.242
970885AG2-551 GEN
Solar/Wind Harmer
7.731
270201AC2-176 GEN
Solar/Wind Harmer
9.453
964611AG1-324 GEN
Solar/Wind Harmer
2.168
964611AG1-324 GEN
Solar/Wind Harmer
0.962
942221AE2-234 GEN
Solar/Wind Harmer
0.412
971673AH1-337 GEN
Solar/Wind Harmer
20.231
971029AG2-637 GEN
Solar/Wind Harmer
61.289
270543AE2-219 C
Solar/Wind Harmer
17.022
961761AG1-017 GEN
Solar/Wind Harmer
0.787
270024AE2-089 GEN
Solar/Wind Harmer
6.484
963791AG1-232 GEN
Solar/Wind Harmer
9.313
962031AG1-047 GEN
Solar/Wind Harmer
5.558
957741AF2-068 GEN
Solar/Wind Harmer
27.581
946031AF1-268 GEN
Solar/Wind Harmer
15.261
971617AH1-308 GEN
Solar/Wind Harmer
8.031
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.011
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.605
MECLTFEXP_MEC->PJM
CLTF
0.18
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.177
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.535
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.028
WECLTFEXP_WEC->PJM
CLTF
0.071
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.063

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.62 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.87
MW Contribution:33.24
Bus #Bus NameTypeMW Contribution
971673AH1-337 GEN
Solar/Wind Harmer
20.23
971029AG2-637 GEN
Solar/Wind Harmer
61.285
270543AE2-219 C
Solar/Wind Harmer
17.02
961761AG1-017 GEN
Solar/Wind Harmer
0.787
270024AE2-089 GEN
Solar/Wind Harmer
6.483
963791AG1-232 GEN
Solar/Wind Harmer
9.312
247621Y3-024
50/50
0.608
970883AG2-550 GEN
Solar/Wind Harmer
33.239
970885AG2-551 GEN
Solar/Wind Harmer
7.73
270201AC2-176 GEN
Solar/Wind Harmer
9.452
964611AG1-324 GEN
Solar/Wind Harmer
2.168
964611AG1-324 GEN
Solar/Wind Harmer
0.962
942221AE2-234 GEN
Solar/Wind Harmer
0.412
962031AG1-047 GEN
Solar/Wind Harmer
5.557
957741AF2-068 GEN
Solar/Wind Harmer
27.578
946031AF1-268 GEN
Solar/Wind Harmer
15.26
971617AH1-308 GEN
Solar/Wind Harmer
8.03
247536S-71 GEN
Solar/Wind Harmer
10.868
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.04
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.008
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.606
MECLTFEXP_MEC->PJM
CLTF
0.18
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.176
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.533
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.028
WECLTFEXP_WEC->PJM
CLTF
0.071
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.063

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#11242_05BLUFFP 138_D1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#11242_05BLUFFP 138_D1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:106.61 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:271.86
MW Contribution:65.62
Bus #Bus NameTypeMW Contribution
971673AH1-337 GEN
Solar/Wind Harmer
31.437
971029AG2-637 GEN
Solar/Wind Harmer
100.471
270543AE2-219 C
Solar/Wind Harmer
33.602
970883AG2-550 GEN
Solar/Wind Harmer
65.621
970885AG2-551 GEN
Solar/Wind Harmer
15.261
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
CBM West 1LTFEXP_CBM-W1->PJM
CBM
0.856
MECLTFEXP_MEC->PJM
CLTF
0.102
SIGELTFEXP_SIGE->PJM
CLTF
0.002
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.468
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.018
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.05
LAGNLTFEXP_LAGN->PJM
CLTF
0.029
TVALTFEXP_TVA->PJM
CLTF
0.003
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.02
WECLTFEXP_WEC->PJM
CLTF
0.029
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
CONTINGENCY 'AP_P2-3_WP-500-DRT10A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235111 TO BUS 235113 CKT 2                /*01 502 J     500.0 - 01 502JCT    138.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AEP_P4_#8975_05KAMMER 765_MM2_SRT-A'
 OPEN BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 OPEN BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_WP-500-DRT7A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1          /*01 502 J     500.0 - 01KAMMER     500.0
 SET POSTCONTRATING 4289 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3546 BRANCH FROM BUS 235111 TO BUS 314917 CKT 1 /*01 502 J     500.0 - 8MT STM      500.0
 SET PRECONTRATING 3753 BRANCH FROM BUS 235111 TO BUS 235098 CKT 1 /*01 502 J     500.0 - WOODSIDE     500.0
END
CONTINGENCY 'AP_P1-2_MP-500-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 235111 TO BUS 235117 CKT 1   /*01 502 J     500.0 - 01KAMMER     500.0
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-502T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235117 TO BUS 242925 CKT 1   /*01KAMMER     500.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P2-3_MP-500-024_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1   /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-025_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3   /*01BELMNT     500.0 - 01BELMNT     138.0
END
CONTINGENCY 'AP_P2-3_MP-500-015_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 2   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P2-3_MP-500-014_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235100 CKT 1   /*01FLINTRUN   500.0 - 01FLINTRN    138.0
END
CONTINGENCY 'AP_P1-2_MP-500-007A_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235235 CKT 1   /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-012_SRT-A'
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235235 CKT 1   /*01HARRSN     500.0 - 01FLINTRUN   500.0
 DISCONNECT BRANCH FROM BUS 235107 TO BUS 235703 CKT 1   /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'AP_P1-2_MP-500-008A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235235 TO BUS 235107 CKT 1          /*01FLINTRUN   500.0 - 01HARRSN     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235107 TO BUS 235703 CKT 1 /*01HARRSN     500.0 - 01WYLIE R    500.0
END
CONTINGENCY 'ATSI_P1-2_TE-345-601_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 238563 CKT 1   /*02DAV-BE     345.0 - 02BAY SH     345.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#XXXX_05BEATTY 345_304W_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 243469 CKT 3   /*05BEATTY     345.0 - 05BEATTY     138.0
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
END
CONTINGENCY 'AEP_P4_#16620_05ADKINS 345_A_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 253100 CKT 1   /*05ADKINS     345.0 - 09ATLNTA     345.0
END
CONTINGENCY 'AEP_P4_#16621_05ADKINS 345_A1_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1                /*05BEATTY     345.0 - 05ADKINS     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 270156 TO BUS 270157 CKT 1  /*05ADKINS     345.0 - DARBY CT1     13.8 - DARBY CT2     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270158 TO BUS 270159 CKT 1  /*05ADKINS     345.0 - DARBY CT3     13.8 - DARBY CT4     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270160 TO BUS 270161 CKT 1  /*05ADKINS     345.0 - DARBY CT5     13.8 - DARBY CT6     13.8
END
CONTINGENCY 'AEP_P4_#16622_05ADKINS 345_B1_SRT-A'
 OPEN BRANCH FROM BUS 245769 TO BUS 253100 CKT 1                /*05ADKINS     345.0 - 09ATLNTA     345.0
 OPEN BRANCH FROM BUS 245769 TO BUS 270156 TO BUS 270157 CKT 1  /*05ADKINS     345.0 - DARBY CT1     13.8 - DARBY CT2     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270158 TO BUS 270159 CKT 1  /*05ADKINS     345.0 - DARBY CT3     13.8 - DARBY CT4     13.8
 OPEN BRANCH FROM BUS 245769 TO BUS 270160 TO BUS 270161 CKT 1  /*05ADKINS     345.0 - DARBY CT5     13.8 - DARBY CT6     13.8
END
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'DEOK_P4_1403_MIAMI FORT_SRT-A'
 OPEN BRANCH FROM BUS 249567 TO BUS 243233 CKT 1   /*08M.FORT     345.0 - 05TANNER     345.0
 OPEN BRANCH FROM BUS 249567 TO BUS 251950 CKT 7   /*08M.FORT     345.0 - 08M.FRT7      22.0
END
CONTINGENCY 'AEP_P4_#2812_05TANNER 345_T2_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 249567 CKT 1   /*05TANNER     345.0 - 08M.FORT     345.0
END
CONTINGENCY 'DEOK_P4_1401_MIAMI FORT_SRT-A'
 OPEN BRANCH FROM BUS 249567 TO BUS 243233 CKT 1   /*08M.FORT     345.0 - 05TANNER     345.0
 OPEN BRANCH FROM BUS 249567 TO BUS 250057 CKT 9   /*08M.FORT     345.0 - 08M.FORT     138.0
END
CONTINGENCY 'DEOK_P_4561TODWOOD14562TODWOOD2_SRT-A'
 OPEN BRANCH FROM BUS 249574 TO BUS 249576 CKT 1   /*08TDHNTR     345.0 - 08WODSDL     345.0
 OPEN BRANCH FROM BUS 249574 TO BUS 249576 CKT 2   /*08TDHNTR     345.0 - 08WODSDL     345.0
END
CONTINGENCY 'DEOK_P4_1301_TERMINAL_SRT-A'
 OPEN BRANCH FROM BUS 249565 TO BUS 249575 CKT 1   /*08EBEND      345.0 - 08TERMNL     345.0
 OPEN BRANCH FROM BUS 249567 TO BUS 249575 CKT 1   /*08M.FORT     345.0 - 08TERMNL     345.0
END
CONTINGENCY 'AEP_P4_#10527_05BLUFFP 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1   /*05BLUFFP     138.0 - 05JAY        138.0
 OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1   /*05BLUFFP     138.0 - 05BLUFFPNT    69.0
END
CONTINGENCY 'AEP_P4_#10528_05BLUFFP 138_D_SRT-A'
 OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1   /*05BLUFFP     138.0 - 05BLUFFPNT    69.0
 OPEN BRANCH FROM BUS 243253 TO BUS 270542 CKT 1   /*05BLUFFP     138.0 - AE2-219 TAP  138.0
END
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'
 OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1   /*05DESOTO     138.0 - 05MEDFOR     138.0
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P4_#11242_05BLUFFP 138_D1_SRT-A'
 OPEN BRANCH FROM BUS 243253 TO BUS 270411 CKT 1   /*05BLUFFP     138.0 - S-71 MAIN    138.0
 OPEN BRANCH FROM BUS 243253 TO BUS 270542 CKT 1   /*05BLUFFP     138.0 - AE2-219 TAP  138.0
 REMOVE UNIT W1 FROM BUS 247536                    /*S-71 GEN       0.7
END
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A-1'
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P4_#9728_05MALIS 138_L1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 2    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9730_05MALIS 138_P1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243553 CKT 1    /*05MALIS      138.0 - 05POLARS     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#9729_05MALIS 138_M1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243526 TO BUS 243537 CKT 1    /*05HYATT      138.0 - 05MALIS      138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P2-2_#7222_05MALIS 765_1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7222_05MALIS 765_D_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1    /*05MALIS      765.0 - 05VASSEL     765.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290237 CKT 1    /*05MALIS      765.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 242926 TO BUS 290620 CKT 1    /*05MALIS      765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290620 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RM 765.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT SR   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243537 TO BUS 243538 CKT ZB   /*05MALIS      138.0 - 05MALISX     138.0
 OPEN BRANCH FROM BUS 243538 TO BUS 290237 CKT 1    /*05MALISX     138.0 - 05MALIS 1EQ    1.0
 OPEN BRANCH FROM BUS 290237 TO BUS 290238 CKT 1    /*05MALIS 1EQ    1.0 - 05MALIS T1    13.8
END
CONTINGENCY 'AEP_P4_#7216_05VASSEL 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 242926 TO BUS 246751 CKT 1   /*05MALIS      765.0 - 05VASSEL     765.0
END
CONTINGENCY 'AEP_P4_#2942_05KAMMER 765_PP_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 OPEN BRANCH FROM BUS 242925 TO BUS 243188 CKT 1   /*05KAMMER     765.0 - 05MLG1        26.0
 REMOVE UNIT 1 FROM BUS 243188                     /*05MLG1        26.0
END
CONTINGENCY 'AP_P2-3_MP-500-020_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 1          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 2          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AP_P2-3_MP-500-021_SRT-SL'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 235299 CKT 3          /*01BELMNT     500.0 - 01BELMNT     138.0
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5          /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1          /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1          /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                          /*05BELMON     765.0
 SET POSTCONTRATING 2492 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
 SET PRECONTRATING 1986 BRANCH FROM BUS 235102 TO BUS 235235 CKT 1 /*01BELMNT     500.0 - 01FLINTRUN   500.0
END
CONTINGENCY 'AEP_P4_#37_05MOUNTN 765_B1_SRT-A'
 OPEN BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242516 TO BUS 242920 CKT 1   /*05MOUNTN     765.0 - 05BELMON     765.0
 OPEN BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
END
CONTINGENCY 'AP_P1-3_MP-765-501T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235102 TO BUS 242920 CKT 5   /*01BELMNT     500.0 - 05BELMON     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242516 CKT 1   /*05BELMON     765.0 - 05MOUNTN     765.0
 DISCONNECT BRANCH FROM BUS 242920 TO BUS 242925 CKT 1   /*05BELMON     765.0 - 05KAMMER     765.0
 DISCONNECT BUS 242920                                   /*05BELMON     765.0
END
CONTINGENCY 'AEP_P1-2_#709_546_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'AEP_P1-2_#6463_16757_SRT-A'
 OPEN BRANCH FROM BUS 242935 TO BUS 246929 CKT 1   /*05E LIMA     345.0 - 05MADDOX     345.0
END
CONTINGENCY 'AEP_P1-2_#17217_SRT-A'
 OPEN BRANCH FROM BUS 242925 TO BUS 290623 CKT Z1   /*05KAMMER     765.0 - 05KAMMER_RG  765.0
 OPEN BRANCH FROM BUS 246526 TO BUS 290623 CKT 1    /*05GUERNSEY   765.0 - 05KAMMER_RG  765.0
END
CONTINGENCY 'AEP_P1-2_#7422_16_SRT-A'
 OPEN BRANCH FROM BUS 242519 TO BUS 314912 CKT 1   /*05CLOVRD     500.0 - 8LEXNGTN     500.0
END
CONTINGENCY 'AEP_P4_#7443_05DUMONT 765_A_SRT-A'
 OPEN BRANCH FROM BUS 243205 TO BUS 243206 CKT 1    /*05COOK       765.0 - 05DUMONT     765.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7442_05SORENS 765_K2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P4_#7444_05DUMONT 765_A2_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 243641 CKT 2    /*05DUMONT     765.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 243219 TO BUS 243641 CKT 2    /*05DUMONT     345.0 - 05DUMONT 2EQ   1.0
 OPEN BRANCH FROM BUS 243641 TO BUS 243642 CKT 2    /*05DUMONT 2EQ   1.0 - 05DUMONT T2   34.5
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P1-2_#7442_200545_SRT-A'
 OPEN BRANCH FROM BUS 243206 TO BUS 290606 CKT Z1   /*05DUMONT     765.0 - 05DUMONT_RS  765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290606 CKT 1    /*05SORENS     765.0 - 05DUMONT_RS  765.0
END
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A'
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1   /*06DEARB1     345.0 - 06PIERCE     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 248000 CKT 2   /*06DEARB2     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 249564 CKT 1   /*06DEARB2     345.0 - 08BUFTN1     345.0
END
CONTINGENCY 'AEP_P7-1_#485___SRT-A'
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1   /*06DEARB1     345.0 - 06PIERCE     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 249564 CKT 1   /*06DEARB2     345.0 - 08BUFTN1     345.0
END
CONTINGENCY 'DEOK_P4_1579_EASTBEND_SRT-A'
 OPEN BRANCH FROM BUS 249565 TO BUS 249575 CKT 1   /*08EBEND      345.0 - 08TERMNL     345.0
END
CONTINGENCY 'DEOK_P1_EAST BEND-TERMINAL 4516_SRT-A'
 OPEN BRANCH FROM BUS 249565 TO BUS 249575 CKT 1   /*08EBEND      345.0 - 08TERMNL     345.0
END
CONTINGENCY 'AEP_P4_#1558_05BAKER 765_Q_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242513 CKT 1   /*05BAKER      765.0 - 05CULLOD     765.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#309_05HANG R 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P4_#1560_05BAKER 765_Q2_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242523 CKT 1   /*05BAKER      765.0 - 05BAKER      345.0
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P1-2_#309_15_SRT-A'
 OPEN BRANCH FROM BUS 242510 TO BUS 242924 CKT 1   /*05BAKER      765.0 - 05HANG R     765.0
END
CONTINGENCY 'AEP_P2-2_#6763_05BIERSR 345_2_SRT-A'
 OPEN BRANCH FROM BUS 970688 TO BUS 246888 CKT 1   /*AG2-444 TP   345.0 - 05BIERSR     345.0
END
CONTINGENCY '34569 34598 34524_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 249578 CKT 1   /*08FOSTER     345.0 - 08HILCRT     345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY '34524 34598_SRT-A'
 OPEN BRANCH FROM BUS 249566 TO BUS 253006 CKT 1   /*08FOSTER     345.0 - 09BATH       345.0
 OPEN BRANCH FROM BUS 249566 TO BUS 253079 CKT 1   /*08FOSTER     345.0 - 09SUGRCK     345.0
END
CONTINGENCY 'AP_P2-2_WP-500-DRT14_SRT-SL'
 OPEN BRANCH FROM BUS 235109 TO BUS 235081 CKT 1                /*AB1-106 POI  500.0 - T-174  1     500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET POSTCONTRATING 3260 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235108 TO BUS 235109 CKT 1 /*01HATFLD     500.0 - AB1-106 POI  500.0
 SET PRECONTRATING 2707 BRANCH FROM BUS 235116 TO BUS 235109 CKT 1 /*01YUKON      500.0 - AB1-106 POI  500.0
END
CONTINGENCY 'AEP_P4_#6189_05HANG R 765_D1_SRT-A'
 OPEN BRANCH FROM BUS 242921 TO BUS 242924 CKT 1    /*05CORNU      765.0 - 05HANG R     765.0
 OPEN BRANCH FROM BUS 242921 TO BUS 242934 CKT 1    /*05CORNU      765.0 - 05CORNU      345.0
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
 REMOVE UNIT 1A FROM BUS 247245                     /*05HRKG1A      18.0
 REMOVE UNIT 1B FROM BUS 247246                     /*05HRKG1B      18.0
 REMOVE UNIT 1S FROM BUS 247247                     /*05HRKG1S      18.0
 REMOVE UNIT 2A FROM BUS 247248                     /*05HRKG2A      18.0
 REMOVE UNIT 2B FROM BUS 247249                     /*05HRKG2B      18.0
 REMOVE UNIT 2S FROM BUS 247250                     /*05HRKG2S      18.0
END
CONTINGENCY 'AEP_P4_#709_05HANG R 765_D2_SRT-A'
 OPEN BRANCH FROM BUS 242924 TO BUS 290618 CKT Z1   /*05HANG R     765.0 - 05HANGRCK_RJ 765.0
 OPEN BRANCH FROM BUS 243208 TO BUS 290619 CKT Z1   /*05JEFRSO     765.0 - 05JEFFRSN_RH 765.0
 OPEN BRANCH FROM BUS 290618 TO BUS 290619 CKT 1    /*05HANGRCK_RJ 765.0 - 05JEFFRSN_RH 765.0
END
CONTINGENCY 'DEOK_P_CIRCUIT3281&13803_SRT-A'
 OPEN BUS 250144   /*08HUSTRC     138.0
 OPEN BUS 250168   /*08TRENTON_2  138.0
END
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4   /*05JAY        138.0 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4   /*05JAY         34.5 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4   /*05JAY         69.0 - 05JAY 4EQ      1.0
END
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2   /*05JAY        138.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2   /*05JAY         69.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2   /*05JAY 2EQ      1.0 - 05JAY T2      13.1
 REMOVE SWSHUNT FROM BUS 243319                    /*05JAY        138.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-2'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 944530 TO BUS 243232 CKT 2   /*AF1-118 TP   345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P7-1_#11019___SRT-A-1'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 958860 TO BUS 944530 CKT 2   /*AF2-177 TP   345.0 - AF1-118 TP   345.0
END
CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A-1'
 OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1   /*09BLAZER     138.0 - 05HAYES      138.0
 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1   /*05HAYES      138.0 - 05HODGIN_BP  138.0
 OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1   /*AH1-337 TP   138.0 - 05HODGIN_BP  138.0
END
CONTINGENCY 'AEP_P2-2_#13951_05N PORTLN 69.0_2_SRT-A'
 OPEN BRANCH FROM BUS 246020 TO BUS 246022 CKT 1   /*05N PORTLN    69.0 - 05PORTLAND    69.0
 OPEN BRANCH FROM BUS 246020 TO BUS 247258 CKT 1   /*05N PORTLN    69.0 - 05ANTIVILL    69.0
END
CONTINGENCY 'AEP_P4_#4817_05SORENS 345_B2_SRT-A'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
END
CONTINGENCY 'AEP_P4_#7449_05SORENS 345_B_SRT-A'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243232 CKT 1   /*05MERIDN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 243228 TO BUS 243783 CKT 1   /*05MERIDN     345.0 - 05EWHTLY     345.0
END
CONTINGENCY 'AEP_P4_#2896_05KEYSTN 345_A_SRT-A'
 OPEN BRANCH FROM BUS 243225 TO BUS 243232 CKT 1   /*05KEYSTN     345.0 - 05SORENS     345.0
 OPEN BRANCH FROM BUS 243225 TO BUS 247296 CKT A   /*05KEYSTN     345.0 - 05KEYAEQ     999.0
 OPEN BRANCH FROM BUS 243225 TO BUS 247297 CKT B   /*05KEYSTN     345.0 - 05KEYBEQ     999.0
 OPEN BRANCH FROM BUS 243225 TO BUS 944540 CKT 1   /*05KEYSTN     345.0 - AF1-119 TP   345.0
 OPEN BRANCH FROM BUS 247292 TO BUS 247296 CKT A   /*05KEY G1      13.8 - 05KEYAEQ     999.0
 OPEN BRANCH FROM BUS 247293 TO BUS 247296 CKT A   /*05KEY G2      13.8 - 05KEYAEQ     999.0
 OPEN BRANCH FROM BUS 247294 TO BUS 247297 CKT B   /*05KEY G3      13.8 - 05KEYBEQ     999.0
 OPEN BRANCH FROM BUS 247295 TO BUS 247297 CKT B   /*05KEY G4      13.8 - 05KEYBEQ     999.0
 REMOVE UNIT 1 FROM BUS 247292                     /*05KEY G1      13.8
 REMOVE UNIT 2 FROM BUS 247293                     /*05KEY G2      13.8
 REMOVE UNIT 3 FROM BUS 247294                     /*05KEY G3      13.8
 REMOVE UNIT 4 FROM BUS 247295                     /*05KEY G4      13.8
END
CONTINGENCY 'AEP_P1-2_#762_8072_SRT-A'
 OPEN BRANCH FROM BUS 243453 TO BUS 245769 CKT 1   /*05BEATTY     345.0 - 05ADKINS     345.0
END
235102 to 235235 ckt 1
235235 to 235107 ckt 1
235117 to 235111 ckt 1
238889 to 238654 ckt 1
243211 to 242933 ckt 1
288724 to 945630 ckt 1
243262 to 250001 ckt 1
290618 to 242924 ckt Z1
290085 to 290084 ckt 1
243458 to 246752 ckt 1
242925 to 235117 ckt 1
290623 to 242925 ckt Z1
246929 to 242935 ckt 1
290608 to 242928 ckt Z1
242516 to 242920 ckt 1
242933 to 965420 ckt 1
243232 to 246999 ckt 3
246999 to 290607 ckt Z1
243233 to 249567 ckt 1
248001 to 248013 ckt 1
248005 to 242528 ckt 1
248013 to 242938 ckt 1
251382 to 251376 ckt 1
270019 to 243237 ckt 1
944530 to 243232 ckt 2
945630 to 243453 ckt 1
965420 to 246929 ckt 1
971672 to 290085 ckt 1

Winter Peak Analysis

The New Service Request AG2-550 was evaluated as a 100.0 MW (60.0 MW Capacity) injection in the AEP area.

AG2-550 was evaluated as part of a plant. The plant consists of AG2-550, AG2-551. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (120.0 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7445_05MARYSV 765_B_SRT-A
BreakerAC110.3 %2317.0B2555.590.35
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P1-2_#7441_100545_SRT-A
SingleAC109.35 %2317.0B2533.640.35
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7441_05SORENS 765_J1_SRT-A
BreakerAC108.51 %2317.0B2514.080.35
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
BreakerAC108.5 %2317.0B2514.00.35
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
BreakerAC107.9 %2317.0B2499.970.69
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
BusAC107.9 %2317.0B2499.960.69
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
TowerAC105.96 %2317.0B2455.150.42
GD2AEP/DEO&K
05TANNER-08M.FORT 345.0 kV Ckt 1 line
AEP_P7-1_#485___SRT-A
TowerAC105.96 %2317.0B2455.010.42

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7445_05MARYSV 765_B_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7445_05MARYSV 765_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.3 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2555.59
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.856
24691005MDL-2G C
Solar/Wind Harmer
3.747
24697605MDL-3G C
Solar/Wind Harmer
3.741
24697905MDL-4G C
Solar/Wind Harmer
2.47
24726405LAWG1A
50/50
3.66
24726505LAWG1B
50/50
3.66
24726605LAWG1S
50/50
5.639
24726705LAWG2A
50/50
3.66
24726805LAWG2B
50/50
3.438
24726905LAWG2S
50/50
5.639
24729205KEY G1
50/50
6.002
24729305KEY G2
50/50
6.103
24729405KEY G3
50/50
6.103
24729505KEY G4
50/50
6.002
247642Z2-115 C
Solar/Wind Harmer
0
25194708EBND2
50/50
6.229
274847GR RIDGE ;BU
Solar/Wind Harmer
4.938
274848CAMPGROVE;RU
Solar/Wind Harmer
4.717
274851PROVIDENC;RU
Solar/Wind Harmer
2.583
274853TWINGROVE;U1
Solar/Wind Harmer
6.957
274854TWINGROVE;U2
Solar/Wind Harmer
6.884
274861TOP CROP ;1U
Solar/Wind Harmer
5.431
274862TOP CROP ;2U
Solar/Wind Harmer
4.511
274871GR RIDGE ;2U
Solar/Wind Harmer
6.452
274879MINONK ;1U
Solar/Wind Harmer
6.451
274888KELLY CRK;1U
Solar/Wind Harmer
5.637
24379505HDWTR1G C
Solar/Wind Harmer
22.626
24385905FR-11G C
Solar/Wind Harmer
4.666
24386205FR-12G C
Solar/Wind Harmer
2.478
24386405FR-21G C
Solar/Wind Harmer
2.373
24386605FR-22G C
Solar/Wind Harmer
2.373
24387005FR-3G C
Solar/Wind Harmer
2.35
24387305FR-4G C
Solar/Wind Harmer
3.56
24699105WLD G1 C
Solar/Wind Harmer
6.981
24725505WLD G2 C
Solar/Wind Harmer
7.025
274849CRESCENT ;1U
Solar/Wind Harmer
1.785
24755605MDL-5G
Solar/Wind Harmer
2.47
252510AF1-249 C
Solar/Wind Helper
0.173
253303V4-073 C
Solar/Wind Helper
0.01
270201AC2-176 GEN
Solar/Wind Harmer
6.955
25183208HLCRTG
Solar/Wind Helper
1.135
276691AA1-018 GEN1
Solar/Wind Harmer
0.297
276694AA1-018 GEN2
Solar/Wind Harmer
5.315
274872LEEDK;1U
Solar/Wind Harmer
7.895
274872LEEDK;1U
Solar/Wind Harmer
0.12
276646AC1-214 GEN2
Solar/Wind Harmer
1.169
276645AC1-214 GEN1
Solar/Wind Harmer
1.169
276806AD2-047 C O1
Solar/Wind Harmer
8.552
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.587
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
28.576
253415AE1-040 GEN
Solar/Wind Helper
0.166
270180AB1-006 GEN1
Solar/Wind Harmer
7.02
270181AB1-006 GEN2
Solar/Wind Harmer
0.465
253378AE2-206_GEN
Solar/Wind Helper
0.46
253394AE2-221_GEN
Solar/Wind Helper
0.737
253398AE2-221_GEN2
Solar/Wind Helper
0.737
253383AE2-342_GEN
Solar/Wind Helper
0.136
252507AC2-088 GEN
Solar/Wind Helper
0.341
252509AD1-136 GEN
Solar/Wind Helper
0.049
252524AE2-267 GEN
Solar/Wind Helper
0.568
276889AE2-281 GEN
Solar/Wind Harmer
1.753
276872AE1-163_GEN1
Solar/Wind Harmer
6.137
276876AE1-163_GEN2
Solar/Wind Harmer
6.137
276882AE2-255 GEN
Solar/Wind Harmer
2.91
276868AE1-113 GEN
Solar/Wind Harmer
9.223
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253433AC1-085 GEN1
Solar/Wind Helper
0.438
253316AC1-085 GEN3
Solar/Wind Helper
0.691
253317AC1-085 GEN4
Solar/Wind Helper
0.691
276621W2-048 GEN
Solar/Wind Harmer
6.083
241955AC1-078 GEN
Solar/Wind Helper
0.554
276655WTG1_EQ
Solar/Wind Harmer
4.863
270209AC1-174_GEN
Solar/Wind Harmer
0
241974AD2-163_GEN2
Solar/Wind Helper
0.298
241973AD2-163_GEN1
Solar/Wind Helper
0.298
241972AD1-140 GEN
Solar/Wind Helper
0.877
270340AC2-060 GEN
Solar/Wind Helper
0.393
270367AC2-061_GEN
Solar/Wind Helper
0.529
270437AC2-090 C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.229
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.518
276805AD2-038 GEN
Solar/Wind Harmer
4.98
270594AE1-207 GEN
Solar/Wind Harmer
0.808
270032AE2-172
Solar/Wind Harmer
4.041
270599AE1-208 GEN
Solar/Wind Harmer
0.432
270031AE2-169
Solar/Wind Harmer
0.432
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
2.292
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.168
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.207
270526AF1-158 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Helper
0.23
270071AF1-092 GEN
Solar/Wind Harmer
0.501
270004AE1-209 GEN
Solar/Wind Harmer
10.76
270005AE1-210 C O1
Solar/Wind Harmer
10.76
276615X2-022 GEN
Solar/Wind Harmer
1.928
24791305MDL-5G
Solar/Wind Harmer
2.47
274863CRW1-WTG
Solar/Wind Harmer
5.298
274864CRW2-WTG
Solar/Wind Harmer
5.298
274880W4-005 GEN4
Solar/Wind Harmer
2.816
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.608
942481AE2-261 GEN
Solar/Wind Harmer
0.835
943121AE2-341 GEN
Solar/Wind Harmer
0.412
944221AF1-090 GEN
Solar/Wind Harmer
8.703
945391AF1-204 GEN
Solar/Wind Harmer
13.357
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.467
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.413
958491AF2-143 GEN
Solar/Wind Harmer
0.412
958821AF2-173 GEN
Solar/Wind Harmer
0.966
959341AF2-225 GEN
Solar/Wind Harmer
0.424
959611AF2-252 GEN
Solar/Wind Harmer
1.128
960441AF2-335 GEN
Solar/Wind Harmer
0.578
960611AF2-352 GEN
Solar/Wind Harmer
1.128
961491AF2-440 GEN
Solar/Wind Helper
0.208
962581AG1-107 GEN
Solar/Wind Helper
0.625
962691AG1-118 GEN
Solar/Wind Harmer
0.818
962781AG1-127 GEN
Solar/Wind Harmer
0.259
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.231
970169AG2-114 GEN
Solar/Wind Harmer
0.28
970193AG2-126 GEN
Solar/Wind Harmer
0.504
970241AG2-163 GEN
Solar/Wind Harmer
0.791
970289AG2-191 GEN
Solar/Wind Harmer
0.09
970289AG2-191 GEN
Solar/Wind Harmer
0.629
970291AG2-192 GEN
Solar/Wind Harmer
0.062
970291AG2-192 GEN
Solar/Wind Harmer
0.571
970569AG2-363 GEN
Solar/Wind Harmer
0.82
970571AG2-364 GEN
Solar/Wind Harmer
0.547
970781AG2-491 GEN
Solar/Wind Harmer
0.298
970825AG2-519 GEN
Solar/Wind Harmer
0.649
970825AG2-519 GEN
Solar/Wind Harmer
2.491
970921AG2-575 GEN
Solar/Wind Harmer
0.272
970921AG2-575 GEN
Solar/Wind Harmer
1.09
971573AH1-285 GEN
Solar/Wind Harmer
0.236
270239V3-007_GEN1
Solar/Wind Harmer
4.917
270240V3-007_GEN2
Solar/Wind Harmer
17.709
276174W4-005 GEN2
Solar/Wind Harmer
2.816
276656WTG2_EQ
Solar/Wind Harmer
0.644
276686W4-005 GEN3
Solar/Wind Harmer
2.816
276726Z2-087_GEN
Solar/Wind Harmer
7.342
276785W4-005 GEN1
Solar/Wind Harmer
2.816
939401AE1-172 GEN
Solar/Wind Harmer
11.133
939741AE1-205 GEN
Solar/Wind Harmer
0.565
941731AE2-173 GEN
Solar/Wind Harmer
2.824
957751AF2-069 GEN
Solar/Wind Harmer
0.357
963741AG1-226 GEN
Solar/Wind Harmer
1.423
963831AG1-236 GEN
Solar/Wind Harmer
7.936
963841AG1-237 GEN
Solar/Wind Harmer
9.688
965031AG1-367 GEN
Solar/Wind Harmer
0.69
965091AG1-374 GEN
Solar/Wind Harmer
0.846
965911AG1-460 GEN
Solar/Wind Harmer
0.671
971673AH1-337 GEN
Solar/Wind Harmer
0.139
971993AH1-541 GEN
Solar/Wind Harmer
0.262
971997AH1-543 GEN
Solar/Wind Harmer
0.433
972175AH1-670 GEN
Solar/Wind Harmer
11.024
274887GEN-1.85
Solar/Wind Harmer
5.178
939351AE1-166 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.275
944531AF1-118 GEN
Solar/Wind Harmer
1.713
944541AF1-119 GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
9.55
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.511
958861AF2-177 GEN
Solar/Wind Harmer
18.066
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.278
960681AF2-359 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
2.312
960971AF2-388 GEN
Solar/Wind Harmer
17.524
961161AF2-407 GEN
50/50
35.228
961171AF2-408 GEN
50/50
9.343
961761AG1-017 GEN
Solar/Wind Harmer
0.406
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.41
970245AG2-165 GEN
Solar/Wind Harmer
0.576
970321AG2-212 GEN
Solar/Wind Harmer
0.576
970349AG2-230 GEN
Solar/Wind Harmer
0.422
970373AG2-245 GEN
Solar/Wind Harmer
0.597
970513AG2-328 GEN
Solar/Wind Harmer
0.576
970517AG2-330 GEN
Solar/Wind Harmer
8.986
970707AG2-453 GEN
Solar/Wind Harmer
0.776
970833AG2-524 GEN
Solar/Wind Harmer
0.305
970833AG2-524 GEN
Solar/Wind Harmer
2.437
970883AG2-550 GEN
Solar/Wind Harmer
0.347
970885AG2-551 GEN
Solar/Wind Harmer
1.386
970941AG2-585 GEN
Solar/Wind Harmer
0.347
971029AG2-637 GEN
Solar/Wind Harmer
0.472
971347AH1-153 GEN
Solar/Wind Harmer
0.422
971605AH1-302 GEN
Solar/Wind Harmer
4.386
971617AH1-308 GEN
Solar/Wind Harmer
3.712
971769AH1-391 GEN
Solar/Wind Harmer
0.274
971771AH1-392 GEN
Solar/Wind Harmer
0.245
971917AH1-482 GEN
Solar/Wind Harmer
4.515
972181SS23-001
Solar/Wind Harmer
0.278
972207SS24-0001
Solar/Wind Harmer
0.837
972231SS25-0005
Solar/Wind Harmer
0.444
276843GEN-1.7
Solar/Wind Harmer
0.459
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.607
957741AF2-068 GEN
Solar/Wind Harmer
0.617
957841AF2-078 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.4
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
13.688
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.399
964861AG1-349 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.579
965651AG1-433 GEN
Solar/Wind Harmer
8.762
965681AG1-436 GEN
Solar/Wind Harmer
0.347
965791AG1-447 GEN
Solar/Wind Harmer
3.053
247536S-71 GEN
Solar/Wind Harmer
5.187
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
3.369
253325AC1-069 GEN
Solar/Wind Helper
0.165
253333AC1-068 GEN
Solar/Wind Helper
0.165
253338AC1-165 GEN
Solar/Wind Helper
0.165
253343AC1-166 GEN
Solar/Wind Helper
0.165
270186AC1-089 GEN
Solar/Wind Helper
0.588
276668AB2-070 GEN1
Solar/Wind Harmer
2.141
276763AC1-053 GEN1
Solar/Wind Harmer
3.674
276764AC1-053 GEN2
Solar/Wind Harmer
3.674
276848AB2-070 GEN3
Solar/Wind Harmer
2.142
276849AB2-070 GEN2
Solar/Wind Harmer
2.141
944201AF1-088_MTX
Adder
60.775
957141AF2-008_MTX
Adder
30.387
NYPJM->LTFIMP_NY
CLTF
0.678
LGEELTFEXP_LGEE->PJM
CLTF
1.41
WECLTFEXP_WEC->PJM
CLTF
1.768
LAGNLTFEXP_LAGN->PJM
CLTF
4.723
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.041
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.573
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.278
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.663
TVALTFEXP_TVA->PJM
CLTF
1.913
MECLTFEXP_MEC->PJM
CLTF
7.094
SIGELTFEXP_SIGE->PJM
CLTF
0.233
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P1-2_#7441_100545_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#7441_100545_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:109.35 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2533.64
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.898
24691005MDL-2G C
Solar/Wind Harmer
3.767
24697605MDL-3G C
Solar/Wind Harmer
3.761
24697905MDL-4G C
Solar/Wind Harmer
2.483
24726405LAWG1A
50/50
3.664
24726505LAWG1B
50/50
3.664
24726605LAWG1S
50/50
5.646
24726705LAWG2A
50/50
3.664
24726805LAWG2B
50/50
3.442
24726905LAWG2S
50/50
5.646
24728505AND G1
50/50
4.191
24728605AND G2
50/50
4.191
24728705AND G3
50/50
8.872
24729205KEY G1
50/50
6.041
24729305KEY G2
50/50
6.143
24729405KEY G3
50/50
6.143
24729505KEY G4
50/50
6.041
247621Y3-024
50/50
0.245
247642Z2-115 C
Solar/Wind Harmer
0
25194708EBND2
50/50
6.244
274847GR RIDGE ;BU
Solar/Wind Harmer
4.97
274848CAMPGROVE;RU
Solar/Wind Harmer
3.648
274851PROVIDENC;RU
Solar/Wind Harmer
2.596
274853TWINGROVE;U1
Solar/Wind Harmer
6.988
274854TWINGROVE;U2
Solar/Wind Harmer
6.915
274861TOP CROP ;1U
Solar/Wind Harmer
5.465
274862TOP CROP ;2U
Solar/Wind Harmer
4.539
274871GR RIDGE ;2U
Solar/Wind Harmer
6.494
274879MINONK ;1U
Solar/Wind Harmer
6.489
274888KELLY CRK;1U
Solar/Wind Harmer
5.675
24379505HDWTR1G C
Solar/Wind Harmer
22.695
24385905FR-11G C
Solar/Wind Harmer
4.688
24386205FR-12G C
Solar/Wind Harmer
2.489
24386405FR-21G C
Solar/Wind Harmer
2.385
24386605FR-22G C
Solar/Wind Harmer
2.385
24387005FR-3G C
Solar/Wind Harmer
2.361
24387305FR-4G C
Solar/Wind Harmer
3.577
24699105WLD G1 C
Solar/Wind Harmer
7.012
24725505WLD G2 C
Solar/Wind Harmer
7.055
274849CRESCENT ;1U
Solar/Wind Harmer
1.794
24755605MDL-5G
Solar/Wind Harmer
2.483
252510AF1-249 C
Solar/Wind Helper
0.172
253303V4-073 C
Solar/Wind Helper
0.01
270201AC2-176 GEN
Solar/Wind Harmer
7.021
25183208HLCRTG
Solar/Wind Helper
1.129
276691AA1-018 GEN1
Solar/Wind Harmer
0.298
276694AA1-018 GEN2
Solar/Wind Harmer
5.349
274872LEEDK;1U
Solar/Wind Harmer
7.942
274872LEEDK;1U
Solar/Wind Harmer
0.12
276646AC1-214 GEN2
Solar/Wind Harmer
1.175
276645AC1-214 GEN1
Solar/Wind Harmer
1.175
276806AD2-047 C O1
Solar/Wind Harmer
8.611
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.588
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
28.765
253415AE1-040 GEN
Solar/Wind Helper
0.164
270180AB1-006 GEN1
Solar/Wind Harmer
7.057
270181AB1-006 GEN2
Solar/Wind Harmer
0.468
253378AE2-206_GEN
Solar/Wind Helper
0.449
253394AE2-221_GEN
Solar/Wind Helper
0.729
253398AE2-221_GEN2
Solar/Wind Helper
0.729
253383AE2-342_GEN
Solar/Wind Helper
0.13
252507AC2-088 GEN
Solar/Wind Helper
0.339
252509AD1-136 GEN
Solar/Wind Helper
0.048
252524AE2-267 GEN
Solar/Wind Helper
0.567
276889AE2-281 GEN
Solar/Wind Harmer
1.763
276872AE1-163_GEN1
Solar/Wind Harmer
6.172
276876AE1-163_GEN2
Solar/Wind Harmer
6.172
276882AE2-255 GEN
Solar/Wind Harmer
2.927
276868AE1-113 GEN
Solar/Wind Harmer
9.278
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253433AC1-085 GEN1
Solar/Wind Helper
0.434
253316AC1-085 GEN3
Solar/Wind Helper
0.685
253317AC1-085 GEN4
Solar/Wind Helper
0.685
276621W2-048 GEN
Solar/Wind Harmer
6.104
241955AC1-078 GEN
Solar/Wind Helper
0.525
276655WTG1_EQ
Solar/Wind Harmer
4.886
270209AC1-174_GEN
Solar/Wind Harmer
0
241974AD2-163_GEN2
Solar/Wind Helper
0.284
241973AD2-163_GEN1
Solar/Wind Helper
0.284
241972AD1-140 GEN
Solar/Wind Helper
0.861
270340AC2-060 GEN
Solar/Wind Helper
0.387
270367AC2-061_GEN
Solar/Wind Helper
0.527
270437AC2-090 C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.23
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.521
276805AD2-038 GEN
Solar/Wind Harmer
5.01
270594AE1-207 GEN
Solar/Wind Harmer
0.812
270032AE2-172
Solar/Wind Harmer
4.061
270599AE1-208 GEN
Solar/Wind Harmer
0.434
270031AE2-169
Solar/Wind Harmer
0.434
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
2.228
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.17
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.202
270526AF1-158 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Helper
0.227
270071AF1-092 GEN
Solar/Wind Harmer
0.506
270004AE1-209 GEN
Solar/Wind Harmer
10.803
270005AE1-210 C O1
Solar/Wind Harmer
10.803
276615X2-022 GEN
Solar/Wind Harmer
1.935
24791305MDL-5G
Solar/Wind Harmer
2.483
274863CRW1-WTG
Solar/Wind Harmer
5.328
274864CRW2-WTG
Solar/Wind Harmer
5.328
274880W4-005 GEN4
Solar/Wind Harmer
2.827
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.64
942481AE2-261 GEN
Solar/Wind Harmer
0.838
942991AE2-321 GEN
Solar/Wind Harmer
0.273
943121AE2-341 GEN
Solar/Wind Harmer
0.415
944221AF1-090 GEN
Solar/Wind Harmer
8.723
945391AF1-204 GEN
Solar/Wind Harmer
13.393
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.469
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.416
958491AF2-143 GEN
Solar/Wind Harmer
0.415
958821AF2-173 GEN
Solar/Wind Harmer
0.969
959341AF2-225 GEN
Solar/Wind Harmer
0.426
959611AF2-252 GEN
Solar/Wind Harmer
1.133
960441AF2-335 GEN
Solar/Wind Harmer
0.581
960611AF2-352 GEN
Solar/Wind Harmer
1.133
961491AF2-440 GEN
Solar/Wind Helper
0.207
962581AG1-107 GEN
Solar/Wind Helper
0.622
962691AG1-118 GEN
Solar/Wind Harmer
0.823
962781AG1-127 GEN
Solar/Wind Harmer
0.261
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.232
970169AG2-114 GEN
Solar/Wind Harmer
0.282
970193AG2-126 GEN
Solar/Wind Harmer
0.505
970241AG2-163 GEN
Solar/Wind Harmer
0.794
970289AG2-191 GEN
Solar/Wind Harmer
0.091
970289AG2-191 GEN
Solar/Wind Harmer
0.632
970291AG2-192 GEN
Solar/Wind Harmer
0.062
970291AG2-192 GEN
Solar/Wind Harmer
0.574
970569AG2-363 GEN
Solar/Wind Harmer
0.825
970571AG2-364 GEN
Solar/Wind Harmer
0.55
970781AG2-491 GEN
Solar/Wind Harmer
0.3
970825AG2-519 GEN
Solar/Wind Harmer
0.652
970825AG2-519 GEN
Solar/Wind Harmer
2.503
970921AG2-575 GEN
Solar/Wind Harmer
0.274
970921AG2-575 GEN
Solar/Wind Harmer
1.096
971573AH1-285 GEN
Solar/Wind Harmer
0.237
270239V3-007_GEN1
Solar/Wind Harmer
4.932
270240V3-007_GEN2
Solar/Wind Harmer
17.763
276174W4-005 GEN2
Solar/Wind Harmer
2.827
276656WTG2_EQ
Solar/Wind Harmer
0.647
276686W4-005 GEN3
Solar/Wind Harmer
2.827
276726Z2-087_GEN
Solar/Wind Harmer
7.378
276785W4-005 GEN1
Solar/Wind Harmer
2.827
939401AE1-172 GEN
Solar/Wind Harmer
11.199
939741AE1-205 GEN
Solar/Wind Harmer
0.568
941731AE2-173 GEN
Solar/Wind Harmer
2.838
957751AF2-069 GEN
Solar/Wind Harmer
0.359
963741AG1-226 GEN
Solar/Wind Harmer
1.429
963831AG1-236 GEN
Solar/Wind Harmer
7.964
963841AG1-237 GEN
Solar/Wind Harmer
9.729
965031AG1-367 GEN
Solar/Wind Harmer
0.692
965091AG1-374 GEN
Solar/Wind Harmer
0.85
965911AG1-460 GEN
Solar/Wind Harmer
0.672
971673AH1-337 GEN
Solar/Wind Harmer
0.14
971993AH1-541 GEN
Solar/Wind Harmer
0.263
971997AH1-543 GEN
Solar/Wind Harmer
0.436
972175AH1-670 GEN
Solar/Wind Harmer
11.068
274887GEN-1.85
Solar/Wind Harmer
5.213
939351AE1-166 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.277
944531AF1-118 GEN
Solar/Wind Harmer
1.725
944541AF1-119 GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
9.597
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.492
958861AF2-177 GEN
Solar/Wind Harmer
18.162
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
960681AF2-359 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
2.324
960971AF2-388 GEN
Solar/Wind Harmer
17.622
961161AF2-407 GEN
50/50
35.348
961171AF2-408 GEN
50/50
9.376
961761AG1-017 GEN
Solar/Wind Harmer
0.41
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.417
970031AG2-029 GEN
Solar/Wind Harmer
0.822
970245AG2-165 GEN
Solar/Wind Harmer
0.58
970321AG2-212 GEN
Solar/Wind Harmer
0.58
970349AG2-230 GEN
Solar/Wind Harmer
0.426
970373AG2-245 GEN
Solar/Wind Harmer
0.601
970513AG2-328 GEN
Solar/Wind Harmer
0.58
970517AG2-330 GEN
Solar/Wind Harmer
9.046
970707AG2-453 GEN
Solar/Wind Harmer
0.781
970833AG2-524 GEN
Solar/Wind Harmer
0.307
970833AG2-524 GEN
Solar/Wind Harmer
2.453
970883AG2-550 GEN
Solar/Wind Harmer
0.35
970885AG2-551 GEN
Solar/Wind Harmer
1.402
970941AG2-585 GEN
Solar/Wind Harmer
0.349
971029AG2-637 GEN
Solar/Wind Harmer
0.478
971347AH1-153 GEN
Solar/Wind Harmer
0.426
971605AH1-302 GEN
Solar/Wind Harmer
4.413
971617AH1-308 GEN
Solar/Wind Harmer
3.755
971769AH1-391 GEN
Solar/Wind Harmer
0.276
971771AH1-392 GEN
Solar/Wind Harmer
0.248
971917AH1-482 GEN
Solar/Wind Harmer
4.546
972181SS23-001
Solar/Wind Harmer
0.28
972207SS24-0001
Solar/Wind Harmer
0.843
972231SS25-0005
Solar/Wind Harmer
0.447
276843GEN-1.7
Solar/Wind Harmer
0.462
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.581
957741AF2-068 GEN
Solar/Wind Harmer
0.623
957841AF2-078 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.403
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
13.711
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.403
964861AG1-349 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.582
965651AG1-433 GEN
Solar/Wind Harmer
8.811
965681AG1-436 GEN
Solar/Wind Harmer
0.35
965791AG1-447 GEN
Solar/Wind Harmer
3.081
247536S-71 GEN
Solar/Wind Harmer
5.241
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
3.387
253325AC1-069 GEN
Solar/Wind Helper
0.159
253333AC1-068 GEN
Solar/Wind Helper
0.159
253338AC1-165 GEN
Solar/Wind Helper
0.159
253343AC1-166 GEN
Solar/Wind Helper
0.159
270186AC1-089 GEN
Solar/Wind Helper
0.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.149
276763AC1-053 GEN1
Solar/Wind Harmer
3.687
276764AC1-053 GEN2
Solar/Wind Harmer
3.687
276848AB2-070 GEN3
Solar/Wind Harmer
2.15
276849AB2-070 GEN2
Solar/Wind Harmer
2.149
944201AF1-088_MTX
Adder
60.781
957141AF2-008_MTX
Adder
30.391
NYPJM->LTFIMP_NY
CLTF
0.669
LGEELTFEXP_LGEE->PJM
CLTF
1.409
WECLTFEXP_WEC->PJM
CLTF
1.777
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
4.643
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.564
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.326
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.409
TVALTFEXP_TVA->PJM
CLTF
1.863
MECLTFEXP_MEC->PJM
CLTF
7.109
SIGELTFEXP_SIGE->PJM
CLTF
0.233
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7441_05SORENS 765_J1_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7441_05SORENS 765_J1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.51 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2514.08
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.898
24691005MDL-2G C
Solar/Wind Harmer
3.767
24697605MDL-3G C
Solar/Wind Harmer
3.761
24697905MDL-4G C
Solar/Wind Harmer
2.483
24726405LAWG1A
50/50
3.664
24726505LAWG1B
50/50
3.664
24726605LAWG1S
50/50
5.646
24726705LAWG2A
50/50
3.664
24726805LAWG2B
50/50
3.442
24726905LAWG2S
50/50
5.646
24729205KEY G1
50/50
6.041
24729305KEY G2
50/50
6.143
24729405KEY G3
50/50
6.143
24729505KEY G4
50/50
6.041
247642Z2-115 C
Solar/Wind Harmer
0
25194708EBND2
50/50
6.244
274847GR RIDGE ;BU
Solar/Wind Harmer
4.97
274848CAMPGROVE;RU
Solar/Wind Harmer
3.648
274851PROVIDENC;RU
Solar/Wind Harmer
2.596
274853TWINGROVE;U1
Solar/Wind Harmer
6.988
274854TWINGROVE;U2
Solar/Wind Harmer
6.915
274861TOP CROP ;1U
Solar/Wind Harmer
5.465
274862TOP CROP ;2U
Solar/Wind Harmer
4.539
274871GR RIDGE ;2U
Solar/Wind Harmer
6.494
274879MINONK ;1U
Solar/Wind Harmer
6.489
274888KELLY CRK;1U
Solar/Wind Harmer
5.675
24379505HDWTR1G C
Solar/Wind Harmer
22.695
24385905FR-11G C
Solar/Wind Harmer
4.688
24386205FR-12G C
Solar/Wind Harmer
2.489
24386405FR-21G C
Solar/Wind Harmer
2.385
24386605FR-22G C
Solar/Wind Harmer
2.385
24387005FR-3G C
Solar/Wind Harmer
2.361
24387305FR-4G C
Solar/Wind Harmer
3.577
24699105WLD G1 C
Solar/Wind Harmer
7.012
24725505WLD G2 C
Solar/Wind Harmer
7.055
274849CRESCENT ;1U
Solar/Wind Harmer
1.794
24755605MDL-5G
Solar/Wind Harmer
2.483
252510AF1-249 C
Solar/Wind Helper
0.172
253303V4-073 C
Solar/Wind Helper
0.01
270201AC2-176 GEN
Solar/Wind Harmer
7.021
25183208HLCRTG
Solar/Wind Helper
1.129
276691AA1-018 GEN1
Solar/Wind Harmer
0.298
276694AA1-018 GEN2
Solar/Wind Harmer
5.349
274872LEEDK;1U
Solar/Wind Harmer
7.942
274872LEEDK;1U
Solar/Wind Harmer
0.12
276646AC1-214 GEN2
Solar/Wind Harmer
1.175
276645AC1-214 GEN1
Solar/Wind Harmer
1.175
276806AD2-047 C O1
Solar/Wind Harmer
8.611
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.588
276911AD2-131_GEN
Solar/Wind Harmer
0.14
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
28.765
253415AE1-040 GEN
Solar/Wind Helper
0.164
270180AB1-006 GEN1
Solar/Wind Harmer
7.057
270181AB1-006 GEN2
Solar/Wind Harmer
0.468
253378AE2-206_GEN
Solar/Wind Helper
0.449
253394AE2-221_GEN
Solar/Wind Helper
0.729
253398AE2-221_GEN2
Solar/Wind Helper
0.729
253383AE2-342_GEN
Solar/Wind Helper
0.13
252507AC2-088 GEN
Solar/Wind Helper
0.339
252509AD1-136 GEN
Solar/Wind Helper
0.048
252524AE2-267 GEN
Solar/Wind Helper
0.567
276889AE2-281 GEN
Solar/Wind Harmer
1.763
276872AE1-163_GEN1
Solar/Wind Harmer
6.172
276876AE1-163_GEN2
Solar/Wind Harmer
6.172
276882AE2-255 GEN
Solar/Wind Harmer
2.927
276868AE1-113 GEN
Solar/Wind Harmer
9.278
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253433AC1-085 GEN1
Solar/Wind Helper
0.434
253316AC1-085 GEN3
Solar/Wind Helper
0.685
253317AC1-085 GEN4
Solar/Wind Helper
0.685
276621W2-048 GEN
Solar/Wind Harmer
6.104
241955AC1-078 GEN
Solar/Wind Helper
0.525
276655WTG1_EQ
Solar/Wind Harmer
4.886
270209AC1-174_GEN
Solar/Wind Harmer
0
241974AD2-163_GEN2
Solar/Wind Helper
0.284
241973AD2-163_GEN1
Solar/Wind Helper
0.284
241972AD1-140 GEN
Solar/Wind Helper
0.861
270340AC2-060 GEN
Solar/Wind Helper
0.387
270367AC2-061_GEN
Solar/Wind Helper
0.527
270437AC2-090 C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.23
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.521
276805AD2-038 GEN
Solar/Wind Harmer
5.01
270594AE1-207 GEN
Solar/Wind Harmer
0.812
270032AE2-172
Solar/Wind Harmer
4.061
270599AE1-208 GEN
Solar/Wind Harmer
0.434
270031AE2-169
Solar/Wind Harmer
0.434
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
2.228
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.17
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.202
270526AF1-158 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Helper
0.227
270071AF1-092 GEN
Solar/Wind Harmer
0.506
270004AE1-209 GEN
Solar/Wind Harmer
10.803
270005AE1-210 C O1
Solar/Wind Harmer
10.803
276615X2-022 GEN
Solar/Wind Harmer
1.935
24791305MDL-5G
Solar/Wind Harmer
2.483
274863CRW1-WTG
Solar/Wind Harmer
5.328
274864CRW2-WTG
Solar/Wind Harmer
5.328
274880W4-005 GEN4
Solar/Wind Harmer
2.827
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.64
942481AE2-261 GEN
Solar/Wind Harmer
0.838
942991AE2-321 GEN
Solar/Wind Harmer
0.273
943121AE2-341 GEN
Solar/Wind Harmer
0.415
944221AF1-090 GEN
Solar/Wind Harmer
8.723
945391AF1-204 GEN
Solar/Wind Harmer
13.393
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.469
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.416
958491AF2-143 GEN
Solar/Wind Harmer
0.415
958821AF2-173 GEN
Solar/Wind Harmer
0.969
959341AF2-225 GEN
Solar/Wind Harmer
0.426
959611AF2-252 GEN
Solar/Wind Harmer
1.133
960441AF2-335 GEN
Solar/Wind Harmer
0.581
960611AF2-352 GEN
Solar/Wind Harmer
1.133
961491AF2-440 GEN
Solar/Wind Helper
0.207
962581AG1-107 GEN
Solar/Wind Helper
0.622
962691AG1-118 GEN
Solar/Wind Harmer
0.823
962781AG1-127 GEN
Solar/Wind Harmer
0.261
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.232
970169AG2-114 GEN
Solar/Wind Harmer
0.282
970193AG2-126 GEN
Solar/Wind Harmer
0.505
970241AG2-163 GEN
Solar/Wind Harmer
0.794
970289AG2-191 GEN
Solar/Wind Harmer
0.091
970289AG2-191 GEN
Solar/Wind Harmer
0.632
970291AG2-192 GEN
Solar/Wind Harmer
0.062
970291AG2-192 GEN
Solar/Wind Harmer
0.574
970569AG2-363 GEN
Solar/Wind Harmer
0.825
970571AG2-364 GEN
Solar/Wind Harmer
0.55
970781AG2-491 GEN
Solar/Wind Harmer
0.3
970825AG2-519 GEN
Solar/Wind Harmer
0.652
970825AG2-519 GEN
Solar/Wind Harmer
2.503
970921AG2-575 GEN
Solar/Wind Harmer
0.274
970921AG2-575 GEN
Solar/Wind Harmer
1.096
971573AH1-285 GEN
Solar/Wind Harmer
0.237
270239V3-007_GEN1
Solar/Wind Harmer
4.932
270240V3-007_GEN2
Solar/Wind Harmer
17.763
276174W4-005 GEN2
Solar/Wind Harmer
2.827
276656WTG2_EQ
Solar/Wind Harmer
0.647
276686W4-005 GEN3
Solar/Wind Harmer
2.827
276726Z2-087_GEN
Solar/Wind Harmer
7.378
276785W4-005 GEN1
Solar/Wind Harmer
2.827
939401AE1-172 GEN
Solar/Wind Harmer
11.199
939741AE1-205 GEN
Solar/Wind Harmer
0.568
941731AE2-173 GEN
Solar/Wind Harmer
2.838
957751AF2-069 GEN
Solar/Wind Harmer
0.359
963741AG1-226 GEN
Solar/Wind Harmer
1.429
963831AG1-236 GEN
Solar/Wind Harmer
7.964
963841AG1-237 GEN
Solar/Wind Harmer
9.729
965031AG1-367 GEN
Solar/Wind Harmer
0.692
965091AG1-374 GEN
Solar/Wind Harmer
0.85
965911AG1-460 GEN
Solar/Wind Harmer
0.672
971673AH1-337 GEN
Solar/Wind Harmer
0.14
971993AH1-541 GEN
Solar/Wind Harmer
0.263
971997AH1-543 GEN
Solar/Wind Harmer
0.436
972175AH1-670 GEN
Solar/Wind Harmer
11.068
274887GEN-1.85
Solar/Wind Harmer
5.213
939351AE1-166 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.277
944531AF1-118 GEN
Solar/Wind Harmer
1.725
944541AF1-119 GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
9.597
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.492
958861AF2-177 GEN
Solar/Wind Harmer
18.162
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.28
960681AF2-359 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
2.324
960971AF2-388 GEN
Solar/Wind Harmer
17.622
961161AF2-407 GEN
50/50
35.348
961171AF2-408 GEN
50/50
9.376
961761AG1-017 GEN
Solar/Wind Harmer
0.41
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.417
970031AG2-029 GEN
Solar/Wind Harmer
0.822
970245AG2-165 GEN
Solar/Wind Harmer
0.58
970321AG2-212 GEN
Solar/Wind Harmer
0.58
970349AG2-230 GEN
Solar/Wind Harmer
0.426
970373AG2-245 GEN
Solar/Wind Harmer
0.601
970513AG2-328 GEN
Solar/Wind Harmer
0.58
970517AG2-330 GEN
Solar/Wind Harmer
9.046
970707AG2-453 GEN
Solar/Wind Harmer
0.781
970833AG2-524 GEN
Solar/Wind Harmer
0.307
970833AG2-524 GEN
Solar/Wind Harmer
2.453
970883AG2-550 GEN
Solar/Wind Harmer
0.35
970885AG2-551 GEN
Solar/Wind Harmer
1.402
970941AG2-585 GEN
Solar/Wind Harmer
0.349
971029AG2-637 GEN
Solar/Wind Harmer
0.478
971347AH1-153 GEN
Solar/Wind Harmer
0.426
971605AH1-302 GEN
Solar/Wind Harmer
4.413
971617AH1-308 GEN
Solar/Wind Harmer
3.755
971769AH1-391 GEN
Solar/Wind Harmer
0.276
971771AH1-392 GEN
Solar/Wind Harmer
0.248
971917AH1-482 GEN
Solar/Wind Harmer
4.546
972181SS23-001
Solar/Wind Harmer
0.28
972207SS24-0001
Solar/Wind Harmer
0.843
972231SS25-0005
Solar/Wind Harmer
0.447
276843GEN-1.7
Solar/Wind Harmer
0.462
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.581
957741AF2-068 GEN
Solar/Wind Harmer
0.623
957841AF2-078 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.403
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
13.711
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.403
964861AG1-349 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.582
965651AG1-433 GEN
Solar/Wind Harmer
8.811
965681AG1-436 GEN
Solar/Wind Harmer
0.35
965791AG1-447 GEN
Solar/Wind Harmer
3.081
247536S-71 GEN
Solar/Wind Harmer
5.241
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
3.387
253325AC1-069 GEN
Solar/Wind Helper
0.159
253333AC1-068 GEN
Solar/Wind Helper
0.159
253338AC1-165 GEN
Solar/Wind Helper
0.159
253343AC1-166 GEN
Solar/Wind Helper
0.159
270186AC1-089 GEN
Solar/Wind Helper
0.586
276668AB2-070 GEN1
Solar/Wind Harmer
2.149
276763AC1-053 GEN1
Solar/Wind Harmer
3.687
276764AC1-053 GEN2
Solar/Wind Harmer
3.687
276848AB2-070 GEN3
Solar/Wind Harmer
2.15
276849AB2-070 GEN2
Solar/Wind Harmer
2.149
944201AF1-088_MTX
Adder
60.781
957141AF2-008_MTX
Adder
30.391
NYPJM->LTFIMP_NY
CLTF
0.669
LGEELTFEXP_LGEE->PJM
CLTF
1.409
WECLTFEXP_WEC->PJM
CLTF
1.777
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.008
LAGNLTFEXP_LAGN->PJM
CLTF
4.643
CBM West 1LTFEXP_CBM-W1->PJM
CBM
55.564
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.326
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.122
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.409
TVALTFEXP_TVA->PJM
CLTF
1.863
MECLTFEXP_MEC->PJM
CLTF
7.109
SIGELTFEXP_SIGE->PJM
CLTF
0.233
AG2-052LTFEXP_AG2-052->PJM
LTF
0.119
AH1-155LTFEXP_AH1-155->PJM
LTF
0.178

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#7446_05MARYSV 765_B2_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#7446_05MARYSV 765_B2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.5 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2514.0
MW Contribution:0.35
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.803
24691005MDL-2G C
Solar/Wind Harmer
3.722
24697605MDL-3G C
Solar/Wind Harmer
3.716
24697905MDL-4G C
Solar/Wind Harmer
2.454
24726405LAWG1A
50/50
3.657
24726505LAWG1B
50/50
3.657
24726605LAWG1S
50/50
5.635
24726705LAWG2A
50/50
3.657
24726805LAWG2B
50/50
3.436
24726905LAWG2S
50/50
5.635
24729205KEY G1
50/50
5.987
24729305KEY G2
50/50
6.088
24729405KEY G3
50/50
6.088
24729505KEY G4
50/50
5.987
247642Z2-115 C
Solar/Wind Harmer
0
25194708EBND2
50/50
6.221
274847GR RIDGE ;BU
Solar/Wind Harmer
4.904
274848CAMPGROVE;RU
Solar/Wind Harmer
4.68
274851PROVIDENC;RU
Solar/Wind Harmer
2.563
274853TWINGROVE;U1
Solar/Wind Harmer
6.904
274854TWINGROVE;U2
Solar/Wind Harmer
6.832
274861TOP CROP ;1U
Solar/Wind Harmer
5.393
274862TOP CROP ;2U
Solar/Wind Harmer
4.479
274871GR RIDGE ;2U
Solar/Wind Harmer
6.408
274879MINONK ;1U
Solar/Wind Harmer
6.405
274888KELLY CRK;1U
Solar/Wind Harmer
5.599
24379505HDWTR1G C
Solar/Wind Harmer
22.59
24385905FR-11G C
Solar/Wind Harmer
4.634
24386205FR-12G C
Solar/Wind Harmer
2.461
24386405FR-21G C
Solar/Wind Harmer
2.357
24386605FR-22G C
Solar/Wind Harmer
2.357
24387005FR-3G C
Solar/Wind Harmer
2.334
24387305FR-4G C
Solar/Wind Harmer
3.536
24699105WLD G1 C
Solar/Wind Harmer
6.961
24725505WLD G2 C
Solar/Wind Harmer
7.004
274849CRESCENT ;1U
Solar/Wind Harmer
1.771
24755605MDL-5G
Solar/Wind Harmer
2.454
252510AF1-249 C
Solar/Wind Helper
0.173
253303V4-073 C
Solar/Wind Helper
0.01
270201AC2-176 GEN
Solar/Wind Harmer
6.939
25183208HLCRTG
Solar/Wind Helper
1.136
276691AA1-018 GEN1
Solar/Wind Harmer
0.295
276694AA1-018 GEN2
Solar/Wind Harmer
5.278
274872LEEDK;1U
Solar/Wind Harmer
7.838
274872LEEDK;1U
Solar/Wind Harmer
0.119
276646AC1-214 GEN2
Solar/Wind Harmer
1.16
276645AC1-214 GEN1
Solar/Wind Harmer
1.16
276806AD2-047 C O1
Solar/Wind Harmer
8.495
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.582
276911AD2-131_GEN
Solar/Wind Harmer
0.138
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
28.383
253415AE1-040 GEN
Solar/Wind Helper
0.165
270180AB1-006 GEN1
Solar/Wind Harmer
6.973
270181AB1-006 GEN2
Solar/Wind Harmer
0.462
253378AE2-206_GEN
Solar/Wind Helper
0.458
253394AE2-221_GEN
Solar/Wind Helper
0.735
253398AE2-221_GEN2
Solar/Wind Helper
0.735
253383AE2-342_GEN
Solar/Wind Helper
0.133
252507AC2-088 GEN
Solar/Wind Helper
0.341
252509AD1-136 GEN
Solar/Wind Helper
0.049
252524AE2-267 GEN
Solar/Wind Helper
0.568
276889AE2-281 GEN
Solar/Wind Harmer
1.741
276872AE1-163_GEN1
Solar/Wind Harmer
6.092
276876AE1-163_GEN2
Solar/Wind Harmer
6.092
276882AE2-255 GEN
Solar/Wind Harmer
2.889
276868AE1-113 GEN
Solar/Wind Harmer
9.157
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253433AC1-085 GEN1
Solar/Wind Helper
0.437
253316AC1-085 GEN3
Solar/Wind Helper
0.691
253317AC1-085 GEN4
Solar/Wind Helper
0.691
276621W2-048 GEN
Solar/Wind Harmer
6.034
241955AC1-078 GEN
Solar/Wind Helper
0.537
276655WTG1_EQ
Solar/Wind Harmer
4.827
270209AC1-174_GEN
Solar/Wind Harmer
0
241974AD2-163_GEN2
Solar/Wind Helper
0.292
241973AD2-163_GEN1
Solar/Wind Helper
0.292
241972AD1-140 GEN
Solar/Wind Helper
0.871
270340AC2-060 GEN
Solar/Wind Helper
0.391
270367AC2-061_GEN
Solar/Wind Helper
0.53
270437AC2-090 C
Solar/Wind Harmer
0
276838X2-022 GEN2
Solar/Wind Harmer
0.227
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.517
276805AD2-038 GEN
Solar/Wind Harmer
4.944
270594AE1-207 GEN
Solar/Wind Harmer
0.806
270032AE2-172
Solar/Wind Harmer
4.029
270599AE1-208 GEN
Solar/Wind Harmer
0.431
270031AE2-169
Solar/Wind Harmer
0.431
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
2.257
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.168
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.207
270526AF1-158 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Helper
0.229
270071AF1-092 GEN
Solar/Wind Harmer
0.499
270004AE1-209 GEN
Solar/Wind Harmer
10.739
270005AE1-210 C O1
Solar/Wind Harmer
10.739
276615X2-022 GEN
Solar/Wind Harmer
1.913
24791305MDL-5G
Solar/Wind Harmer
2.454
274863CRW1-WTG
Solar/Wind Harmer
5.26
274864CRW2-WTG
Solar/Wind Harmer
5.26
274880W4-005 GEN4
Solar/Wind Harmer
2.794
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.559
942481AE2-261 GEN
Solar/Wind Harmer
0.828
943121AE2-341 GEN
Solar/Wind Harmer
0.41
944221AF1-090 GEN
Solar/Wind Harmer
8.628
945391AF1-204 GEN
Solar/Wind Harmer
13.266
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.466
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.41
958491AF2-143 GEN
Solar/Wind Harmer
0.409
958821AF2-173 GEN
Solar/Wind Harmer
0.964
959341AF2-225 GEN
Solar/Wind Harmer
0.42
959611AF2-252 GEN
Solar/Wind Harmer
1.12
960441AF2-335 GEN
Solar/Wind Harmer
0.577
960611AF2-352 GEN
Solar/Wind Harmer
1.12
961491AF2-440 GEN
Solar/Wind Helper
0.209
962581AG1-107 GEN
Solar/Wind Helper
0.627
962691AG1-118 GEN
Solar/Wind Harmer
0.812
962781AG1-127 GEN
Solar/Wind Harmer
0.257
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.231
970169AG2-114 GEN
Solar/Wind Harmer
0.278
970193AG2-126 GEN
Solar/Wind Harmer
0.5
970241AG2-163 GEN
Solar/Wind Harmer
0.785
970289AG2-191 GEN
Solar/Wind Harmer
0.09
970289AG2-191 GEN
Solar/Wind Harmer
0.626
970291AG2-192 GEN
Solar/Wind Harmer
0.062
970291AG2-192 GEN
Solar/Wind Harmer
0.57
970569AG2-363 GEN
Solar/Wind Harmer
0.814
970571AG2-364 GEN
Solar/Wind Harmer
0.543
970781AG2-491 GEN
Solar/Wind Harmer
0.296
970825AG2-519 GEN
Solar/Wind Harmer
0.647
970825AG2-519 GEN
Solar/Wind Harmer
2.485
970921AG2-575 GEN
Solar/Wind Harmer
0.27
970921AG2-575 GEN
Solar/Wind Harmer
1.082
971573AH1-285 GEN
Solar/Wind Harmer
0.234
270239V3-007_GEN1
Solar/Wind Harmer
4.909
270240V3-007_GEN2
Solar/Wind Harmer
17.681
276174W4-005 GEN2
Solar/Wind Harmer
2.794
276656WTG2_EQ
Solar/Wind Harmer
0.639
276686W4-005 GEN3
Solar/Wind Harmer
2.794
276726Z2-087_GEN
Solar/Wind Harmer
7.288
276785W4-005 GEN1
Solar/Wind Harmer
2.794
939401AE1-172 GEN
Solar/Wind Harmer
11.055
939741AE1-205 GEN
Solar/Wind Harmer
0.561
941731AE2-173 GEN
Solar/Wind Harmer
2.803
957751AF2-069 GEN
Solar/Wind Harmer
0.354
963741AG1-226 GEN
Solar/Wind Harmer
1.413
963831AG1-236 GEN
Solar/Wind Harmer
7.873
963841AG1-237 GEN
Solar/Wind Harmer
9.621
965031AG1-367 GEN
Solar/Wind Harmer
0.688
965091AG1-374 GEN
Solar/Wind Harmer
0.84
965911AG1-460 GEN
Solar/Wind Harmer
0.665
971673AH1-337 GEN
Solar/Wind Harmer
0.138
971993AH1-541 GEN
Solar/Wind Harmer
0.26
971997AH1-543 GEN
Solar/Wind Harmer
0.43
972175AH1-670 GEN
Solar/Wind Harmer
10.938
274887GEN-1.85
Solar/Wind Harmer
5.143
939351AE1-166 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
943591AF1-030 GEN
Solar/Wind Harmer
0.273
944531AF1-118 GEN
Solar/Wind Harmer
1.709
944541AF1-119 GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
9.53
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.5
958861AF2-177 GEN
Solar/Wind Harmer
18.025
959141AF2-205 GEN
Solar/Wind Harmer
0
960591AF2-350 GEN
Solar/Wind Harmer
0.276
960681AF2-359 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
2.307
960971AF2-388 GEN
Solar/Wind Harmer
17.484
961161AF2-407 GEN
50/50
35.127
961171AF2-408 GEN
50/50
9.317
961761AG1-017 GEN
Solar/Wind Harmer
0.405
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.409
970245AG2-165 GEN
Solar/Wind Harmer
0.572
970321AG2-212 GEN
Solar/Wind Harmer
0.572
970349AG2-230 GEN
Solar/Wind Harmer
0.419
970373AG2-245 GEN
Solar/Wind Harmer
0.593
970513AG2-328 GEN
Solar/Wind Harmer
0.572
970517AG2-330 GEN
Solar/Wind Harmer
8.927
970707AG2-453 GEN
Solar/Wind Harmer
0.771
970833AG2-524 GEN
Solar/Wind Harmer
0.303
970833AG2-524 GEN
Solar/Wind Harmer
2.42
970883AG2-550 GEN
Solar/Wind Harmer
0.346
970885AG2-551 GEN
Solar/Wind Harmer
1.383
970941AG2-585 GEN
Solar/Wind Harmer
0.345
971029AG2-637 GEN
Solar/Wind Harmer
0.471
971347AH1-153 GEN
Solar/Wind Harmer
0.419
971605AH1-302 GEN
Solar/Wind Harmer
4.358
971617AH1-308 GEN
Solar/Wind Harmer
3.703
971769AH1-391 GEN
Solar/Wind Harmer
0.272
971771AH1-392 GEN
Solar/Wind Harmer
0.244
971917AH1-482 GEN
Solar/Wind Harmer
4.486
972181SS23-001
Solar/Wind Harmer
0.276
972207SS24-0001
Solar/Wind Harmer
0.831
972231SS25-0005
Solar/Wind Harmer
0.441
276843GEN-1.7
Solar/Wind Harmer
0.456
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.594
957741AF2-068 GEN
Solar/Wind Harmer
0.616
957841AF2-078 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.397
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
13.661
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.398
964861AG1-349 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.578
965651AG1-433 GEN
Solar/Wind Harmer
8.742
965681AG1-436 GEN
Solar/Wind Harmer
0.345
965791AG1-447 GEN
Solar/Wind Harmer
3.036
247536S-71 GEN
Solar/Wind Harmer
5.175
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
3.344
253325AC1-069 GEN
Solar/Wind Helper
0.162
253333AC1-068 GEN
Solar/Wind Helper
0.162
253338AC1-165 GEN
Solar/Wind Helper
0.162
253343AC1-166 GEN
Solar/Wind Helper
0.162
270186AC1-089 GEN
Solar/Wind Helper
0.59
276668AB2-070 GEN1
Solar/Wind Harmer
2.124
276763AC1-053 GEN1
Solar/Wind Harmer
3.645
276764AC1-053 GEN2
Solar/Wind Harmer
3.645
276848AB2-070 GEN3
Solar/Wind Harmer
2.125
276849AB2-070 GEN2
Solar/Wind Harmer
2.124
944201AF1-088_MTX
Adder
60.225
957141AF2-008_MTX
Adder
30.113
NYPJM->LTFIMP_NY
CLTF
0.657
LGEELTFEXP_LGEE->PJM
CLTF
1.379
WECLTFEXP_WEC->PJM
CLTF
1.754
LAGNLTFEXP_LAGN->PJM
CLTF
4.596
CBM West 1LTFEXP_CBM-W1->PJM
CBM
54.654
CBM West 2LTFEXP_CBM-W2->PJM
CBM
47.851
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.036
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.438
TVALTFEXP_TVA->PJM
CLTF
1.844
MECLTFEXP_MEC->PJM
CLTF
7.023
SIGELTFEXP_SIGE->PJM
CLTF
0.23
AG2-052LTFEXP_AG2-052->PJM
LTF
0.117
AH1-155LTFEXP_AH1-155->PJM
LTF
0.176

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P4_#9456_06DEARB1 345_DC_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#9456_06DEARB1 345_DC_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2499.97
MW Contribution:0.69
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.752
24691005MDL-2G C
Solar/Wind Harmer
3.698
24697605MDL-3G C
Solar/Wind Harmer
3.692
24697905MDL-4G C
Solar/Wind Harmer
2.438
24726405LAWG1A
50/50
6.312
24726505LAWG1B
50/50
6.312
24726605LAWG1S
50/50
9.725
24726705LAWG2A
50/50
6.312
24726805LAWG2B
50/50
5.93
24726905LAWG2S
50/50
9.725
24728505AND G1
50/50
6.569
24728605AND G2
50/50
6.569
24728705AND G3
50/50
13.905
24728805RICHG1
50/50
5.707
24728905RICHG2
50/50
5.707
24729205KEY G1
50/50
8.868
24729305KEY G2
50/50
9.018
24729405KEY G3
50/50
9.018
24729505KEY G4
50/50
8.868
247621Y3-024
50/50
0.444
247642Z2-115 C
Solar/Wind Harmer
-0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
4.796
274848CAMPGROVE;RU
Solar/Wind Harmer
4.885
274851PROVIDENC;RU
Solar/Wind Harmer
2.548
274853TWINGROVE;U1
Solar/Wind Harmer
7.026
274854TWINGROVE;U2
Solar/Wind Harmer
6.952
274861TOP CROP ;1U
Solar/Wind Harmer
5.302
274862TOP CROP ;2U
Solar/Wind Harmer
4.404
274871GR RIDGE ;2U
Solar/Wind Harmer
6.267
274877BISHOP HL;1U
Solar/Wind Harmer
3.102
274878BISHOP HL;2U
Solar/Wind Harmer
3.102
274879MINONK ;1U
Solar/Wind Harmer
6.309
274888KELLY CRK;1U
Solar/Wind Harmer
5.479
24379505HDWTR1G C
Solar/Wind Harmer
37.341
24385905FR-11G C
Solar/Wind Harmer
4.727
24386205FR-12G C
Solar/Wind Harmer
2.51
24386405FR-21G C
Solar/Wind Harmer
2.404
24386605FR-22G C
Solar/Wind Harmer
2.404
24387005FR-3G C
Solar/Wind Harmer
2.38
24387305FR-4G C
Solar/Wind Harmer
3.607
24699105WLD G1 C
Solar/Wind Harmer
10.823
24725505WLD G2 C
Solar/Wind Harmer
10.89
274849CRESCENT ;1U
Solar/Wind Harmer
1.761
24755605MDL-5G
Solar/Wind Harmer
2.438
252510AF1-249 C
Solar/Wind Helper
0.15
253303V4-073 C
Solar/Wind Helper
0.008
270201AC2-176 GEN
Solar/Wind Harmer
12.282
25183208HLCRTG
Solar/Wind Helper
1.188
276691AA1-018 GEN1
Solar/Wind Harmer
0.29
276694AA1-018 GEN2
Solar/Wind Harmer
5.188
276646AC1-214 GEN2
Solar/Wind Harmer
1.154
276645AC1-214 GEN1
Solar/Wind Harmer
1.154
276806AD2-047 C O1
Solar/Wind Harmer
8.313
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.603
276911AD2-131_GEN
Solar/Wind Harmer
0.144
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
27.79
253415AE1-040 GEN
Solar/Wind Helper
0.16
270180AB1-006 GEN1
Solar/Wind Harmer
6.927
270181AB1-006 GEN2
Solar/Wind Harmer
0.459
253378AE2-206_GEN
Solar/Wind Helper
0.3
253394AE2-221_GEN
Solar/Wind Helper
0.706
253398AE2-221_GEN2
Solar/Wind Helper
0.706
252507AC2-088 GEN
Solar/Wind Helper
0.426
252509AD1-136 GEN
Solar/Wind Helper
0.061
252524AE2-267 GEN
Solar/Wind Helper
0.448
276889AE2-281 GEN
Solar/Wind Harmer
1.72
276872AE1-163_GEN1
Solar/Wind Harmer
6.018
276876AE1-163_GEN2
Solar/Wind Harmer
6.018
276882AE2-255 GEN
Solar/Wind Harmer
2.846
276868AE1-113 GEN
Solar/Wind Harmer
9.021
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253317AC1-085 GEN4
Solar/Wind Helper
0.695
339221AD2-048_GEN
Solar/Wind Helper
0.215
276621W2-048 GEN
Solar/Wind Harmer
6.241
276655WTG1_EQ
Solar/Wind Harmer
4.896
270209AC1-174_GEN
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Helper
0.704
270340AC2-060 GEN
Solar/Wind Helper
0.388
270367AC2-061_GEN
Solar/Wind Helper
0.507
270437AC2-090 C
Solar/Wind Harmer
0
270222AC2-111 GEN
Solar/Wind Harmer
0.582
276838X2-022 GEN2
Solar/Wind Harmer
0.235
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.79
276805AD2-038 GEN
Solar/Wind Harmer
4.87
270505AE1-170 C O1
Solar/Wind Harmer
0.402
270594AE1-207 GEN
Solar/Wind Harmer
1.225
270032AE2-172
Solar/Wind Harmer
6.127
270599AE1-208 GEN
Solar/Wind Harmer
0.681
270031AE2-169
Solar/Wind Harmer
0.681
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
1.934
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.203
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.135
270526AF1-158 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Helper
0.215
270071AF1-092 GEN
Solar/Wind Harmer
0.612
270004AE1-209 GEN
Solar/Wind Harmer
17.353
270005AE1-210 C O1
Solar/Wind Harmer
17.353
276615X2-022 GEN
Solar/Wind Harmer
1.978
24791305MDL-5G
Solar/Wind Harmer
2.438
274863CRW1-WTG
Solar/Wind Harmer
5.241
274864CRW2-WTG
Solar/Wind Harmer
5.241
274880W4-005 GEN4
Solar/Wind Harmer
2.888
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.653
942481AE2-261 GEN
Solar/Wind Harmer
0.859
943111AE2-339 GEN
Solar/Wind Helper
0.1
944221AF1-090 GEN
Solar/Wind Harmer
8.986
945391AF1-204 GEN
Solar/Wind Harmer
15.394
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.775
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.403
958491AF2-143 GEN
Solar/Wind Harmer
0.403
958821AF2-173 GEN
Solar/Wind Harmer
1.557
959341AF2-225 GEN
Solar/Wind Harmer
0.426
959611AF2-252 GEN
Solar/Wind Harmer
1.139
960441AF2-335 GEN
Solar/Wind Harmer
0.938
960611AF2-352 GEN
Solar/Wind Harmer
1.139
961491AF2-440 GEN
Solar/Wind Helper
0.193
962581AG1-107 GEN
Solar/Wind Helper
0.58
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.375
970169AG2-114 GEN
Solar/Wind Harmer
0.279
970193AG2-126 GEN
Solar/Wind Harmer
0.58
970241AG2-163 GEN
Solar/Wind Harmer
0.845
970289AG2-191 GEN
Solar/Wind Harmer
0.133
970289AG2-191 GEN
Solar/Wind Harmer
0.923
970291AG2-192 GEN
Solar/Wind Harmer
0.091
970291AG2-192 GEN
Solar/Wind Harmer
0.839
970569AG2-363 GEN
Solar/Wind Harmer
0.806
970571AG2-364 GEN
Solar/Wind Harmer
0.537
970781AG2-491 GEN
Solar/Wind Harmer
0.294
970825AG2-519 GEN
Solar/Wind Harmer
1.058
970825AG2-519 GEN
Solar/Wind Harmer
4.06
270239V3-007_GEN1
Solar/Wind Harmer
8.115
270240V3-007_GEN2
Solar/Wind Harmer
29.226
276174W4-005 GEN2
Solar/Wind Harmer
2.888
276656WTG2_EQ
Solar/Wind Harmer
0.648
276686W4-005 GEN3
Solar/Wind Harmer
2.888
276726Z2-087_GEN
Solar/Wind Harmer
7.392
276785W4-005 GEN1
Solar/Wind Harmer
2.888
939401AE1-172 GEN
Solar/Wind Harmer
10.958
939741AE1-205 GEN
Solar/Wind Harmer
0.569
941731AE2-173 GEN
Solar/Wind Harmer
2.843
957751AF2-069 GEN
Solar/Wind Harmer
0.352
963741AG1-226 GEN
Solar/Wind Harmer
1.522
963831AG1-236 GEN
Solar/Wind Harmer
8.138
963841AG1-237 GEN
Solar/Wind Harmer
10.103
965031AG1-367 GEN
Solar/Wind Harmer
1.112
965091AG1-374 GEN
Solar/Wind Harmer
0.854
965911AG1-460 GEN
Solar/Wind Harmer
0.689
971673AH1-337 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
0.268
971997AH1-543 GEN
Solar/Wind Harmer
0.424
972175AH1-670 GEN
Solar/Wind Harmer
11.223
274887GEN-1.85
Solar/Wind Harmer
5.033
939351AE1-166 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
2.497
944541AF1-119 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.483
945111AF1-176 GEN
Solar/Wind Harmer
2.633
945371AF1-202 GEN
Solar/Wind Harmer
14.943
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.426
958861AF2-177 GEN
Solar/Wind Harmer
27.824
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
0.312
960591AF2-350 GEN
Solar/Wind Harmer
0.27
960681AF2-359 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
3.752
960971AF2-388 GEN
Solar/Wind Harmer
26.744
961051AF2-396 GEN
Solar/Wind Harmer
0.504
961051AF2-396 GEN
Solar/Wind Harmer
4.034
961161AF2-407 GEN
50/50
55.656
961171AF2-408 GEN
50/50
15.002
961761AG1-017 GEN
Solar/Wind Harmer
0.716
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.628
970031AG2-029 GEN
Solar/Wind Harmer
0.932
970349AG2-230 GEN
Solar/Wind Harmer
0.405
970373AG2-245 GEN
Solar/Wind Harmer
0.581
970611AG2-400 GEN
Solar/Wind Harmer
0.312
970707AG2-453 GEN
Solar/Wind Harmer
0.749
970833AG2-524 GEN
Solar/Wind Harmer
0.296
970833AG2-524 GEN
Solar/Wind Harmer
2.367
970883AG2-550 GEN
Solar/Wind Harmer
0.689
970885AG2-551 GEN
Solar/Wind Harmer
2.754
970941AG2-585 GEN
Solar/Wind Harmer
0.337
971029AG2-637 GEN
Solar/Wind Harmer
1.005
971347AH1-153 GEN
Solar/Wind Harmer
0.405
971605AH1-302 GEN
Solar/Wind Harmer
4.274
971617AH1-308 GEN
Solar/Wind Harmer
6.268
971769AH1-391 GEN
Solar/Wind Harmer
0.271
971771AH1-392 GEN
Solar/Wind Harmer
0.246
971917AH1-482 GEN
Solar/Wind Harmer
4.398
972181SS23-001
Solar/Wind Harmer
0.271
972207SS24-0001
Solar/Wind Harmer
0.804
972231SS25-0005
Solar/Wind Harmer
0.433
276843GEN-1.7
Solar/Wind Harmer
0.446
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.46
957741AF2-068 GEN
Solar/Wind Harmer
1.09
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.389
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
22.581
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.694
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
0.312
965021AG1-366 GEN
Solar/Wind Harmer
1.248
965041AG1-368 GEN
Solar/Wind Harmer
0.276
965101AG1-375 GEN
Solar/Wind Harmer
0.892
965651AG1-433 GEN
Solar/Wind Harmer
13.372
965681AG1-436 GEN
Solar/Wind Harmer
0.338
965791AG1-447 GEN
Solar/Wind Harmer
2.974
247536S-71 GEN
Solar/Wind Harmer
9.762
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.253
339243AC2-075 GEN1
Solar/Wind Helper
0.063
926823AC1-168 GEN
Solar/Wind Harmer
3.314
253325AC1-069 GEN
Solar/Wind Helper
0.15
253333AC1-068 GEN
Solar/Wind Helper
0.15
253338AC1-165 GEN
Solar/Wind Helper
0.15
253343AC1-166 GEN
Solar/Wind Helper
0.15
270186AC1-089 GEN
Solar/Wind Helper
0.591
276668AB2-070 GEN1
Solar/Wind Harmer
2.195
276763AC1-053 GEN1
Solar/Wind Harmer
3.767
276764AC1-053 GEN2
Solar/Wind Harmer
3.767
276782AC1-033 GEN
Solar/Wind Harmer
3.504
276848AB2-070 GEN3
Solar/Wind Harmer
2.196
276849AB2-070 GEN2
Solar/Wind Harmer
2.195
944201AF1-088_MTX
Adder
57.805
957141AF2-008_MTX
Adder
28.902
NYPJM->LTFIMP_NY
CLTF
0.68
WECLTFEXP_WEC->PJM
CLTF
1.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.324
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.162
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.173
LAGNLTFEXP_LAGN->PJM
CLTF
4.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.249
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.276
TVALTFEXP_TVA->PJM
CLTF
1.464
MECLTFEXP_MEC->PJM
CLTF
6.937
SIGELTFEXP_SIGE->PJM
CLTF
0.246
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.182

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P2-2_#9456_06DEARB1 345_1_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#9456_06DEARB1 345_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.9 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2499.96
MW Contribution:0.69
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.752
24691005MDL-2G C
Solar/Wind Harmer
3.698
24697605MDL-3G C
Solar/Wind Harmer
3.692
24697905MDL-4G C
Solar/Wind Harmer
2.438
24726405LAWG1A
50/50
6.312
24726505LAWG1B
50/50
6.312
24726605LAWG1S
50/50
9.725
24726705LAWG2A
50/50
6.312
24726805LAWG2B
50/50
5.93
24726905LAWG2S
50/50
9.725
24728505AND G1
50/50
6.569
24728605AND G2
50/50
6.569
24728705AND G3
50/50
13.905
24728805RICHG1
50/50
5.707
24728905RICHG2
50/50
5.707
24729205KEY G1
50/50
8.868
24729305KEY G2
50/50
9.018
24729405KEY G3
50/50
9.018
24729505KEY G4
50/50
8.868
247621Y3-024
50/50
0.444
247642Z2-115 C
Solar/Wind Harmer
-0.001
274847GR RIDGE ;BU
Solar/Wind Harmer
4.796
274848CAMPGROVE;RU
Solar/Wind Harmer
4.885
274851PROVIDENC;RU
Solar/Wind Harmer
2.548
274853TWINGROVE;U1
Solar/Wind Harmer
7.026
274854TWINGROVE;U2
Solar/Wind Harmer
6.952
274861TOP CROP ;1U
Solar/Wind Harmer
5.302
274862TOP CROP ;2U
Solar/Wind Harmer
4.404
274871GR RIDGE ;2U
Solar/Wind Harmer
6.267
274877BISHOP HL;1U
Solar/Wind Harmer
3.102
274878BISHOP HL;2U
Solar/Wind Harmer
3.102
274879MINONK ;1U
Solar/Wind Harmer
6.309
274888KELLY CRK;1U
Solar/Wind Harmer
5.479
24379505HDWTR1G C
Solar/Wind Harmer
37.341
24385905FR-11G C
Solar/Wind Harmer
4.727
24386205FR-12G C
Solar/Wind Harmer
2.51
24386405FR-21G C
Solar/Wind Harmer
2.404
24386605FR-22G C
Solar/Wind Harmer
2.404
24387005FR-3G C
Solar/Wind Harmer
2.38
24387305FR-4G C
Solar/Wind Harmer
3.607
24699105WLD G1 C
Solar/Wind Harmer
10.823
24725505WLD G2 C
Solar/Wind Harmer
10.89
274849CRESCENT ;1U
Solar/Wind Harmer
1.761
24755605MDL-5G
Solar/Wind Harmer
2.438
252510AF1-249 C
Solar/Wind Helper
0.15
253303V4-073 C
Solar/Wind Helper
0.008
270201AC2-176 GEN
Solar/Wind Harmer
12.282
25183208HLCRTG
Solar/Wind Helper
1.188
276691AA1-018 GEN1
Solar/Wind Harmer
0.29
276694AA1-018 GEN2
Solar/Wind Harmer
5.188
276646AC1-214 GEN2
Solar/Wind Harmer
1.154
276645AC1-214 GEN1
Solar/Wind Harmer
1.154
276806AD2-047 C O1
Solar/Wind Harmer
8.313
276901AD2-066 C O1
Solar/Wind Harmer
0
276916AD2-100_GEN
Solar/Wind Harmer
0.603
276911AD2-131_GEN
Solar/Wind Harmer
0.144
276893AG1-478 C
Solar/Wind Harmer
0
276897AD1-100 C
Solar/Wind Harmer
27.79
253415AE1-040 GEN
Solar/Wind Helper
0.16
270180AB1-006 GEN1
Solar/Wind Harmer
6.927
270181AB1-006 GEN2
Solar/Wind Harmer
0.459
253378AE2-206_GEN
Solar/Wind Helper
0.3
253394AE2-221_GEN
Solar/Wind Helper
0.706
253398AE2-221_GEN2
Solar/Wind Helper
0.706
252507AC2-088 GEN
Solar/Wind Helper
0.426
252509AD1-136 GEN
Solar/Wind Helper
0.061
252524AE2-267 GEN
Solar/Wind Helper
0.448
276889AE2-281 GEN
Solar/Wind Harmer
1.72
276872AE1-163_GEN1
Solar/Wind Harmer
6.018
276876AE1-163_GEN2
Solar/Wind Harmer
6.018
276882AE2-255 GEN
Solar/Wind Harmer
2.846
276868AE1-113 GEN
Solar/Wind Harmer
9.021
253432AC1-085 GEN2
Solar/Wind Helper
0.023
253433AC1-085 GEN1
Solar/Wind Helper
0.44
253316AC1-085 GEN3
Solar/Wind Helper
0.695
253317AC1-085 GEN4
Solar/Wind Helper
0.695
339221AD2-048_GEN
Solar/Wind Helper
0.215
276621W2-048 GEN
Solar/Wind Harmer
6.241
276655WTG1_EQ
Solar/Wind Harmer
4.896
270209AC1-174_GEN
Solar/Wind Harmer
0
241972AD1-140 GEN
Solar/Wind Helper
0.704
270340AC2-060 GEN
Solar/Wind Helper
0.388
270367AC2-061_GEN
Solar/Wind Helper
0.507
270437AC2-090 C
Solar/Wind Harmer
0
270222AC2-111 GEN
Solar/Wind Harmer
0.582
276838X2-022 GEN2
Solar/Wind Harmer
0.235
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.79
276805AD2-038 GEN
Solar/Wind Harmer
4.87
270505AE1-170 C O1
Solar/Wind Harmer
0.402
270594AE1-207 GEN
Solar/Wind Harmer
1.225
270032AE2-172
Solar/Wind Harmer
6.127
270599AE1-208 GEN
Solar/Wind Harmer
0.681
270031AE2-169
Solar/Wind Harmer
0.681
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
1.934
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.203
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270063AE2-323 C
Solar/Wind Harmer
0
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.135
270526AF1-158 GEN
Solar/Wind Harmer
0
253406AD2-031_GEN
Solar/Wind Helper
0.215
270071AF1-092 GEN
Solar/Wind Harmer
0.612
270004AE1-209 GEN
Solar/Wind Harmer
17.353
270005AE1-210 C O1
Solar/Wind Harmer
17.353
276615X2-022 GEN
Solar/Wind Harmer
1.978
24791305MDL-5G
Solar/Wind Harmer
2.438
274863CRW1-WTG
Solar/Wind Harmer
5.241
274864CRW2-WTG
Solar/Wind Harmer
5.241
274880W4-005 GEN4
Solar/Wind Harmer
2.888
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.653
942481AE2-261 GEN
Solar/Wind Harmer
0.859
943111AE2-339 GEN
Solar/Wind Helper
0.1
944221AF1-090 GEN
Solar/Wind Harmer
8.986
945391AF1-204 GEN
Solar/Wind Harmer
15.394
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.775
946581AF1-322 GEN
Solar/Wind Harmer
0
958481AF2-142 GEN
Solar/Wind Harmer
0.403
958491AF2-143 GEN
Solar/Wind Harmer
0.403
958821AF2-173 GEN
Solar/Wind Harmer
1.557
959341AF2-225 GEN
Solar/Wind Harmer
0.426
959611AF2-252 GEN
Solar/Wind Harmer
1.139
960441AF2-335 GEN
Solar/Wind Harmer
0.938
960611AF2-352 GEN
Solar/Wind Harmer
1.139
961491AF2-440 GEN
Solar/Wind Helper
0.193
962581AG1-107 GEN
Solar/Wind Helper
0.58
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.375
970169AG2-114 GEN
Solar/Wind Harmer
0.279
970193AG2-126 GEN
Solar/Wind Harmer
0.58
970241AG2-163 GEN
Solar/Wind Harmer
0.845
970289AG2-191 GEN
Solar/Wind Harmer
0.133
970289AG2-191 GEN
Solar/Wind Harmer
0.923
970291AG2-192 GEN
Solar/Wind Harmer
0.091
970291AG2-192 GEN
Solar/Wind Harmer
0.839
970569AG2-363 GEN
Solar/Wind Harmer
0.806
970571AG2-364 GEN
Solar/Wind Harmer
0.537
970781AG2-491 GEN
Solar/Wind Harmer
0.294
970825AG2-519 GEN
Solar/Wind Harmer
1.058
970825AG2-519 GEN
Solar/Wind Harmer
4.06
270239V3-007_GEN1
Solar/Wind Harmer
8.115
270240V3-007_GEN2
Solar/Wind Harmer
29.226
276174W4-005 GEN2
Solar/Wind Harmer
2.888
276656WTG2_EQ
Solar/Wind Harmer
0.648
276686W4-005 GEN3
Solar/Wind Harmer
2.888
276726Z2-087_GEN
Solar/Wind Harmer
7.392
276785W4-005 GEN1
Solar/Wind Harmer
2.888
939401AE1-172 GEN
Solar/Wind Harmer
10.958
939741AE1-205 GEN
Solar/Wind Harmer
0.569
941731AE2-173 GEN
Solar/Wind Harmer
2.843
957751AF2-069 GEN
Solar/Wind Harmer
0.352
963741AG1-226 GEN
Solar/Wind Harmer
1.522
963831AG1-236 GEN
Solar/Wind Harmer
8.138
963841AG1-237 GEN
Solar/Wind Harmer
10.103
965031AG1-367 GEN
Solar/Wind Harmer
1.112
965091AG1-374 GEN
Solar/Wind Harmer
0.854
965911AG1-460 GEN
Solar/Wind Harmer
0.689
971673AH1-337 GEN
Solar/Wind Harmer
0.304
971993AH1-541 GEN
Solar/Wind Harmer
0.268
971997AH1-543 GEN
Solar/Wind Harmer
0.424
972175AH1-670 GEN
Solar/Wind Harmer
11.223
274887GEN-1.85
Solar/Wind Harmer
5.033
939351AE1-166 GEN
Solar/Wind Harmer
0
942081AE2-220 GEN
Solar/Wind Harmer
0
944231AF1-091 GEN
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
2.497
944541AF1-119 GEN
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
0.483
945111AF1-176 GEN
Solar/Wind Harmer
2.633
945371AF1-202 GEN
Solar/Wind Harmer
14.943
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.426
958861AF2-177 GEN
Solar/Wind Harmer
27.824
959141AF2-205 GEN
Solar/Wind Harmer
0
959331AF2-224 GEN
Solar/Wind Harmer
0.312
960591AF2-350 GEN
Solar/Wind Harmer
0.27
960681AF2-359 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
3.752
960971AF2-388 GEN
Solar/Wind Harmer
26.744
961051AF2-396 GEN
Solar/Wind Harmer
0.504
961051AF2-396 GEN
Solar/Wind Harmer
4.034
961161AF2-407 GEN
50/50
55.656
961171AF2-408 GEN
50/50
15.002
961761AG1-017 GEN
Solar/Wind Harmer
0.716
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.628
970031AG2-029 GEN
Solar/Wind Harmer
0.932
970349AG2-230 GEN
Solar/Wind Harmer
0.405
970373AG2-245 GEN
Solar/Wind Harmer
0.581
970611AG2-400 GEN
Solar/Wind Harmer
0.312
970707AG2-453 GEN
Solar/Wind Harmer
0.749
970833AG2-524 GEN
Solar/Wind Harmer
0.296
970833AG2-524 GEN
Solar/Wind Harmer
2.367
970883AG2-550 GEN
Solar/Wind Harmer
0.689
970885AG2-551 GEN
Solar/Wind Harmer
2.754
970941AG2-585 GEN
Solar/Wind Harmer
0.337
971029AG2-637 GEN
Solar/Wind Harmer
1.005
971347AH1-153 GEN
Solar/Wind Harmer
0.405
971605AH1-302 GEN
Solar/Wind Harmer
4.274
971617AH1-308 GEN
Solar/Wind Harmer
6.268
971769AH1-391 GEN
Solar/Wind Harmer
0.271
971771AH1-392 GEN
Solar/Wind Harmer
0.246
971917AH1-482 GEN
Solar/Wind Harmer
4.398
972181SS23-001
Solar/Wind Harmer
0.271
972207SS24-0001
Solar/Wind Harmer
0.804
972231SS25-0005
Solar/Wind Harmer
0.433
276843GEN-1.7
Solar/Wind Harmer
0.446
940581AE2-045 GEN
Solar/Wind Harmer
0
941551AE2-152 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.46
957741AF2-068 GEN
Solar/Wind Harmer
1.09
957841AF2-078 GEN
Solar/Wind Harmer
0
957891AF2-083 GEN
Solar/Wind Harmer
0
958011AF2-095 GEN
Solar/Wind Harmer
0.389
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
22.581
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.694
964861AG1-349 GEN
Solar/Wind Harmer
0
965011AG1-365 GEN
Solar/Wind Harmer
0.312
965021AG1-366 GEN
Solar/Wind Harmer
1.248
965041AG1-368 GEN
Solar/Wind Harmer
0.276
965101AG1-375 GEN
Solar/Wind Harmer
0.892
965651AG1-433 GEN
Solar/Wind Harmer
13.372
965681AG1-436 GEN
Solar/Wind Harmer
0.338
965791AG1-447 GEN
Solar/Wind Harmer
2.974
247536S-71 GEN
Solar/Wind Harmer
9.762
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.253
339243AC2-075 GEN1
Solar/Wind Helper
0.063
926823AC1-168 GEN
Solar/Wind Harmer
3.314
253325AC1-069 GEN
Solar/Wind Helper
0.15
253333AC1-068 GEN
Solar/Wind Helper
0.15
253338AC1-165 GEN
Solar/Wind Helper
0.15
253343AC1-166 GEN
Solar/Wind Helper
0.15
270186AC1-089 GEN
Solar/Wind Helper
0.591
276668AB2-070 GEN1
Solar/Wind Harmer
2.195
276763AC1-053 GEN1
Solar/Wind Harmer
3.767
276764AC1-053 GEN2
Solar/Wind Harmer
3.767
276782AC1-033 GEN
Solar/Wind Harmer
3.504
276848AB2-070 GEN3
Solar/Wind Harmer
2.196
276849AB2-070 GEN2
Solar/Wind Harmer
2.195
944201AF1-088_MTX
Adder
57.805
957141AF2-008_MTX
Adder
28.902
NYPJM->LTFIMP_NY
CLTF
0.68
WECLTFEXP_WEC->PJM
CLTF
1.719
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.324
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.162
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.173
LAGNLTFEXP_LAGN->PJM
CLTF
4.036
CBM West 1LTFEXP_CBM-W1->PJM
CBM
53.249
CBM West 2LTFEXP_CBM-W2->PJM
CBM
50.919
CBM South 1LTFEXP_CBM-S1->PJM
CBM
4.276
TVALTFEXP_TVA->PJM
CLTF
1.464
MECLTFEXP_MEC->PJM
CLTF
6.937
SIGELTFEXP_SIGE->PJM
CLTF
0.246
AG2-052LTFEXP_AG2-052->PJM
LTF
0.121
AH1-155LTFEXP_AH1-155->PJM
LTF
0.182

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.96 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2455.15
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.292
24691005MDL-2G C
Solar/Wind Harmer
3.478
24697605MDL-3G C
Solar/Wind Harmer
3.473
24697905MDL-4G C
Solar/Wind Harmer
2.293
24726405LAWG1A
50/50
4.369
24726505LAWG1B
50/50
4.369
24726605LAWG1S
50/50
6.731
24726705LAWG2A
50/50
4.369
24726805LAWG2B
50/50
4.104
24726905LAWG2S
50/50
6.731
24728505AND G1
50/50
4.753
24728605AND G2
50/50
4.753
24728705AND G3
50/50
10.06
24729205KEY G1
50/50
6.267
24729305KEY G2
50/50
6.374
24729405KEY G3
50/50
6.374
24729505KEY G4
50/50
6.267
247642Z2-115 C
Solar/Wind Harmer
0
25194708EBND2
50/50
7.956
274853TWINGROVE;U1
Solar/Wind Harmer
6.401
274854TWINGROVE;U2
Solar/Wind Harmer
6.334
24379505HDWTR1G C
Solar/Wind Harmer
26.019
24385905FR-11G C
Solar/Wind Harmer
4.421
24386205FR-12G C
Solar/Wind Harmer
2.348
24386405FR-21G C
Solar/Wind Harmer
2.249
24386605FR-22G C
Solar/Wind Harmer
2.249
24387005FR-3G C
Solar/Wind Harmer
2.226
24387305FR-4G C
Solar/Wind Harmer
3.373
24699105WLD G1 C
Solar/Wind Harmer
7.759
24725505WLD G2 C
Solar/Wind Harmer
7.807
24755605MDL-5G
Solar/Wind Harmer
2.293
252510AF1-249 C
Solar/Wind Helper
0.172
253303V4-073 C
Solar/Wind Helper
0.01
270201AC2-176 GEN
Solar/Wind Harmer
7.968
25183208HLCRTG
Solar/Wind Helper
1.226
276916AD2-100_GEN
Solar/Wind Harmer
0.562
276911AD2-131_GEN
Solar/Wind Harmer
0.134
253415AE1-040 GEN
Solar/Wind Helper
0.174
270180AB1-006 GEN1
Solar/Wind Harmer
6.516
270181AB1-006 GEN2
Solar/Wind Harmer
0.432
253378AE2-206_GEN
Solar/Wind Helper
0.418
253394AE2-221_GEN
Solar/Wind Helper
0.762
253398AE2-221_GEN2
Solar/Wind Helper
0.762
253383AE2-342_GEN
Solar/Wind Helper
0.119
252507AC2-088 GEN
Solar/Wind Helper
0.416
252509AD1-136 GEN
Solar/Wind Helper
0.059
252524AE2-267 GEN
Solar/Wind Helper
0.549
253432AC1-085 GEN2
Solar/Wind Helper
0.024
253433AC1-085 GEN1
Solar/Wind Helper
0.46
253316AC1-085 GEN3
Solar/Wind Helper
0.727
253317AC1-085 GEN4
Solar/Wind Helper
0.727
339221AD2-048_GEN
Solar/Wind Helper
0.191
276621W2-048 GEN
Solar/Wind Harmer
5.755
241955AC1-078 GEN
Solar/Wind Helper
0.5
276655WTG1_EQ
Solar/Wind Harmer
4.445
270209AC1-174_GEN
Solar/Wind Harmer
0
241974AD2-163_GEN2
Solar/Wind Helper
0.266
241973AD2-163_GEN1
Solar/Wind Helper
0.266
241972AD1-140 GEN
Solar/Wind Helper
0.849
270340AC2-060 GEN
Solar/Wind Helper
0.418
270367AC2-061_GEN
Solar/Wind Helper
0.555
270437AC2-090 C
Solar/Wind Harmer
0
270222AC2-111 GEN
Solar/Wind Harmer
0.298
276838X2-022 GEN2
Solar/Wind Harmer
0.216
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.571
270594AE1-207 GEN
Solar/Wind Harmer
0.884
270032AE2-172
Solar/Wind Harmer
4.418
270599AE1-208 GEN
Solar/Wind Harmer
0.476
270031AE2-169
Solar/Wind Harmer
0.476
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
2.217
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.151
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.189
253406AD2-031_GEN
Solar/Wind Helper
0.237
270071AF1-092 GEN
Solar/Wind Harmer
0.466
270004AE1-209 GEN
Solar/Wind Harmer
12.134
270005AE1-210 C O1
Solar/Wind Harmer
12.134
276615X2-022 GEN
Solar/Wind Harmer
1.824
24791305MDL-5G
Solar/Wind Harmer
2.293
274880W4-005 GEN4
Solar/Wind Harmer
2.653
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.041
942481AE2-261 GEN
Solar/Wind Harmer
0.798
944221AF1-090 GEN
Solar/Wind Harmer
8.419
945391AF1-204 GEN
Solar/Wind Harmer
13.668
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.53
946581AF1-322 GEN
Solar/Wind Harmer
0
958821AF2-173 GEN
Solar/Wind Harmer
1.089
959341AF2-225 GEN
Solar/Wind Harmer
0.387
959611AF2-252 GEN
Solar/Wind Harmer
1.038
960441AF2-335 GEN
Solar/Wind Harmer
0.651
960611AF2-352 GEN
Solar/Wind Harmer
1.038
961491AF2-440 GEN
Solar/Wind Helper
0.218
962581AG1-107 GEN
Solar/Wind Helper
0.653
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.26
970169AG2-114 GEN
Solar/Wind Harmer
0.252
970193AG2-126 GEN
Solar/Wind Harmer
0.515
970241AG2-163 GEN
Solar/Wind Harmer
0.773
970289AG2-191 GEN
Solar/Wind Harmer
0.098
970289AG2-191 GEN
Solar/Wind Harmer
0.678
970291AG2-192 GEN
Solar/Wind Harmer
0.067
970291AG2-192 GEN
Solar/Wind Harmer
0.616
970781AG2-491 GEN
Solar/Wind Harmer
0.277
970825AG2-519 GEN
Solar/Wind Harmer
0.732
970825AG2-519 GEN
Solar/Wind Harmer
2.81
270239V3-007_GEN1
Solar/Wind Harmer
5.654
270240V3-007_GEN2
Solar/Wind Harmer
20.364
276174W4-005 GEN2
Solar/Wind Harmer
2.653
276656WTG2_EQ
Solar/Wind Harmer
0.589
276686W4-005 GEN3
Solar/Wind Harmer
2.653
276726Z2-087_GEN
Solar/Wind Harmer
6.712
276785W4-005 GEN1
Solar/Wind Harmer
2.653
939741AE1-205 GEN
Solar/Wind Harmer
0.516
941731AE2-173 GEN
Solar/Wind Harmer
2.581
963741AG1-226 GEN
Solar/Wind Harmer
1.392
963831AG1-236 GEN
Solar/Wind Harmer
7.485
963841AG1-237 GEN
Solar/Wind Harmer
9.335
965031AG1-367 GEN
Solar/Wind Harmer
0.778
965091AG1-374 GEN
Solar/Wind Harmer
0.778
965911AG1-460 GEN
Solar/Wind Harmer
0.641
971673AH1-337 GEN
Solar/Wind Harmer
0.173
971993AH1-541 GEN
Solar/Wind Harmer
0.247
972175AH1-670 GEN
Solar/Wind Harmer
10.271
942081AE2-220 GEN
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
1.768
944541AF1-119 GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
10.487
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.484
958861AF2-177 GEN
Solar/Wind Harmer
19.564
959141AF2-205 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
2.603
960971AF2-388 GEN
Solar/Wind Harmer
18.826
961161AF2-407 GEN
50/50
39.935
961171AF2-408 GEN
50/50
10.647
961761AG1-017 GEN
Solar/Wind Harmer
0.465
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.42
970883AG2-550 GEN
Solar/Wind Harmer
0.416
970885AG2-551 GEN
Solar/Wind Harmer
1.665
971029AG2-637 GEN
Solar/Wind Harmer
0.584
971605AH1-302 GEN
Solar/Wind Harmer
3.978
971617AH1-308 GEN
Solar/Wind Harmer
4.107
971917AH1-482 GEN
Solar/Wind Harmer
4.042
940581AE2-045 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.553
957741AF2-068 GEN
Solar/Wind Harmer
0.707
957841AF2-078 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
16.059
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.627
965651AG1-433 GEN
Solar/Wind Harmer
9.413
247536S-71 GEN
Solar/Wind Harmer
6.09
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.225
339243AC2-075 GEN1
Solar/Wind Helper
0.056
253325AC1-069 GEN
Solar/Wind Helper
0.162
253333AC1-068 GEN
Solar/Wind Helper
0.162
253338AC1-165 GEN
Solar/Wind Helper
0.162
253343AC1-166 GEN
Solar/Wind Helper
0.162
270186AC1-089 GEN
Solar/Wind Helper
0.627
276668AB2-070 GEN1
Solar/Wind Harmer
2.017
276763AC1-053 GEN1
Solar/Wind Harmer
3.465
276764AC1-053 GEN2
Solar/Wind Harmer
3.465
276848AB2-070 GEN3
Solar/Wind Harmer
2.017
276849AB2-070 GEN2
Solar/Wind Harmer
2.017
944201AF1-088_MTX
Adder
61.971
957141AF2-008_MTX
Adder
30.986
NYPJM->LTFIMP_NY
CLTF
0.641
LGEELTFEXP_LGEE->PJM
CLTF
1.564
WECLTFEXP_WEC->PJM
CLTF
1.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
LAGNLTFEXP_LAGN->PJM
CLTF
4.425
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.557
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.067
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.063
TVALTFEXP_TVA->PJM
CLTF
1.796
MECLTFEXP_MEC->PJM
CLTF
6.481
SIGELTFEXP_SIGE->PJM
CLTF
0.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162

Details for 05TANNER-08M.FORT 345.0 kV Ckt 1 line l/o AEP_P7-1_#485___SRT-A


Base Case Flowgate

Area:AEP/DEO&K
Facility Description:
05TANNER-08M.FORT 345.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#485___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.96 %
Rating:2317.0 MVA
Rating Type:B
MVA to Mitigate:2455.01
MW Contribution:0.42
Bus #Bus NameTypeMW Contribution
24690905MDL-1G C
Solar/Wind Harmer
7.292
24691005MDL-2G C
Solar/Wind Harmer
3.478
24697605MDL-3G C
Solar/Wind Harmer
3.473
24697905MDL-4G C
Solar/Wind Harmer
2.293
24726405LAWG1A
50/50
4.369
24726505LAWG1B
50/50
4.369
24726605LAWG1S
50/50
6.731
24726705LAWG2A
50/50
4.369
24726805LAWG2B
50/50
4.104
24726905LAWG2S
50/50
6.731
24728505AND G1
50/50
4.753
24728605AND G2
50/50
4.753
24728705AND G3
50/50
10.06
24729205KEY G1
50/50
6.267
24729305KEY G2
50/50
6.374
24729405KEY G3
50/50
6.374
24729505KEY G4
50/50
6.267
247642Z2-115 C
Solar/Wind Harmer
0
25194708EBND2
50/50
7.956
274853TWINGROVE;U1
Solar/Wind Harmer
6.401
274854TWINGROVE;U2
Solar/Wind Harmer
6.334
24379505HDWTR1G C
Solar/Wind Harmer
26.019
24385905FR-11G C
Solar/Wind Harmer
4.421
24386205FR-12G C
Solar/Wind Harmer
2.348
24386405FR-21G C
Solar/Wind Harmer
2.249
24386605FR-22G C
Solar/Wind Harmer
2.249
24387005FR-3G C
Solar/Wind Harmer
2.226
24387305FR-4G C
Solar/Wind Harmer
3.373
24699105WLD G1 C
Solar/Wind Harmer
7.759
24725505WLD G2 C
Solar/Wind Harmer
7.807
24755605MDL-5G
Solar/Wind Harmer
2.293
252510AF1-249 C
Solar/Wind Helper
0.172
253303V4-073 C
Solar/Wind Helper
0.01
270201AC2-176 GEN
Solar/Wind Harmer
7.968
25183208HLCRTG
Solar/Wind Helper
1.226
276916AD2-100_GEN
Solar/Wind Harmer
0.562
276911AD2-131_GEN
Solar/Wind Harmer
0.134
253415AE1-040 GEN
Solar/Wind Helper
0.174
270180AB1-006 GEN1
Solar/Wind Harmer
6.516
270181AB1-006 GEN2
Solar/Wind Harmer
0.432
253378AE2-206_GEN
Solar/Wind Helper
0.418
253394AE2-221_GEN
Solar/Wind Helper
0.762
253398AE2-221_GEN2
Solar/Wind Helper
0.762
253383AE2-342_GEN
Solar/Wind Helper
0.119
252507AC2-088 GEN
Solar/Wind Helper
0.416
252509AD1-136 GEN
Solar/Wind Helper
0.059
252524AE2-267 GEN
Solar/Wind Helper
0.549
253432AC1-085 GEN2
Solar/Wind Helper
0.024
253433AC1-085 GEN1
Solar/Wind Helper
0.46
253316AC1-085 GEN3
Solar/Wind Helper
0.727
253317AC1-085 GEN4
Solar/Wind Helper
0.727
339221AD2-048_GEN
Solar/Wind Helper
0.191
276621W2-048 GEN
Solar/Wind Harmer
5.755
241955AC1-078 GEN
Solar/Wind Helper
0.5
276655WTG1_EQ
Solar/Wind Harmer
4.445
270209AC1-174_GEN
Solar/Wind Harmer
0
241974AD2-163_GEN2
Solar/Wind Helper
0.266
241973AD2-163_GEN1
Solar/Wind Helper
0.266
241972AD1-140 GEN
Solar/Wind Helper
0.849
270340AC2-060 GEN
Solar/Wind Helper
0.418
270367AC2-061_GEN
Solar/Wind Helper
0.555
270437AC2-090 C
Solar/Wind Harmer
0
270222AC2-111 GEN
Solar/Wind Harmer
0.298
276838X2-022 GEN2
Solar/Wind Harmer
0.216
270383AD1-128 GEN
Solar/Wind Harmer
0
276903AD2-071 C
Solar/Wind Harmer
0.571
270594AE1-207 GEN
Solar/Wind Harmer
0.884
270032AE2-172
Solar/Wind Harmer
4.418
270599AE1-208 GEN
Solar/Wind Harmer
0.476
270031AE2-169
Solar/Wind Harmer
0.476
270024AE2-089 GEN
Solar/Wind Harmer
0
270518AE2-148 GEN
Solar/Wind Helper
2.217
270543AE2-219 C
Solar/Wind Harmer
0
270043AE2-236 GEN
Solar/Wind Harmer
0.151
270356AE2-297 GEN
Solar/Wind Harmer
-0.001
270536AF1-215 GEN2
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0
270055AF2-134 C O1
Solar/Wind Harmer
0
276820AF1-078_GEN
Solar/Wind Helper
0.189
253406AD2-031_GEN
Solar/Wind Helper
0.237
270071AF1-092 GEN
Solar/Wind Harmer
0.466
270004AE1-209 GEN
Solar/Wind Harmer
12.134
270005AE1-210 C O1
Solar/Wind Harmer
12.134
276615X2-022 GEN
Solar/Wind Harmer
1.824
24791305MDL-5G
Solar/Wind Harmer
2.293
274880W4-005 GEN4
Solar/Wind Harmer
2.653
926881AC1-175 GEN
Solar/Wind Harmer
0
942111AE2-223 GEN
Solar/Wind Harmer
6.041
942481AE2-261 GEN
Solar/Wind Harmer
0.798
944221AF1-090 GEN
Solar/Wind Harmer
8.419
945391AF1-204 GEN
Solar/Wind Harmer
13.668
945421AF1-207 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
0.53
946581AF1-322 GEN
Solar/Wind Harmer
0
958821AF2-173 GEN
Solar/Wind Harmer
1.089
959341AF2-225 GEN
Solar/Wind Harmer
0.387
959611AF2-252 GEN
Solar/Wind Harmer
1.038
960441AF2-335 GEN
Solar/Wind Harmer
0.651
960611AF2-352 GEN
Solar/Wind Harmer
1.038
961491AF2-440 GEN
Solar/Wind Helper
0.218
962581AG1-107 GEN
Solar/Wind Helper
0.653
966841AG1-555 GEN
Solar/Wind Harmer
0
970115AG2-085 GEN
Solar/Wind Harmer
0.26
970169AG2-114 GEN
Solar/Wind Harmer
0.252
970193AG2-126 GEN
Solar/Wind Harmer
0.515
970241AG2-163 GEN
Solar/Wind Harmer
0.773
970289AG2-191 GEN
Solar/Wind Harmer
0.098
970289AG2-191 GEN
Solar/Wind Harmer
0.678
970291AG2-192 GEN
Solar/Wind Harmer
0.067
970291AG2-192 GEN
Solar/Wind Harmer
0.616
970781AG2-491 GEN
Solar/Wind Harmer
0.277
970825AG2-519 GEN
Solar/Wind Harmer
0.732
970825AG2-519 GEN
Solar/Wind Harmer
2.81
270239V3-007_GEN1
Solar/Wind Harmer
5.654
270240V3-007_GEN2
Solar/Wind Harmer
20.364
276174W4-005 GEN2
Solar/Wind Harmer
2.653
276656WTG2_EQ
Solar/Wind Harmer
0.589
276686W4-005 GEN3
Solar/Wind Harmer
2.653
276726Z2-087_GEN
Solar/Wind Harmer
6.712
276785W4-005 GEN1
Solar/Wind Harmer
2.653
939741AE1-205 GEN
Solar/Wind Harmer
0.516
941731AE2-173 GEN
Solar/Wind Harmer
2.581
963741AG1-226 GEN
Solar/Wind Harmer
1.392
963831AG1-236 GEN
Solar/Wind Harmer
7.485
963841AG1-237 GEN
Solar/Wind Harmer
9.335
965031AG1-367 GEN
Solar/Wind Harmer
0.778
965091AG1-374 GEN
Solar/Wind Harmer
0.778
965911AG1-460 GEN
Solar/Wind Harmer
0.641
971673AH1-337 GEN
Solar/Wind Harmer
0.173
971993AH1-541 GEN
Solar/Wind Harmer
0.247
972175AH1-670 GEN
Solar/Wind Harmer
10.271
942081AE2-220 GEN
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
1.768
944541AF1-119 GEN
Solar/Wind Harmer
0
945371AF1-202 GEN
Solar/Wind Harmer
10.487
945581AF1-223 GEN
Solar/Wind Harmer
0
945631AF1-228 GEN
Solar/Wind Helper
0.484
958861AF2-177 GEN
Solar/Wind Harmer
19.564
959141AF2-205 GEN
Solar/Wind Harmer
0
960791AF2-370 GEN
Solar/Wind Harmer
2.603
960971AF2-388 GEN
Solar/Wind Harmer
18.826
961161AF2-407 GEN
50/50
39.935
961171AF2-408 GEN
50/50
10.647
961761AG1-017 GEN
Solar/Wind Harmer
0.465
962031AG1-047 GEN
Solar/Wind Harmer
0
963791AG1-232 GEN
Solar/Wind Harmer
0.42
970883AG2-550 GEN
Solar/Wind Harmer
0.416
970885AG2-551 GEN
Solar/Wind Harmer
1.665
971029AG2-637 GEN
Solar/Wind Harmer
0.584
971605AH1-302 GEN
Solar/Wind Harmer
3.978
971617AH1-308 GEN
Solar/Wind Harmer
4.107
971917AH1-482 GEN
Solar/Wind Harmer
4.042
940581AE2-045 GEN
Solar/Wind Harmer
0
942051AE2-217 GEN
Solar/Wind Helper
0.553
957741AF2-068 GEN
Solar/Wind Harmer
0.707
957841AF2-078 GEN
Solar/Wind Harmer
0
958381AF2-132 GEN
Solar/Wind Harmer
0
958391AF2-133 GEN
Solar/Wind Harmer
0
964351AG1-297 GEN
50/50
16.059
964401AG1-302 GEN
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
0.456
964861AG1-349 GEN
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
0.627
965651AG1-433 GEN
Solar/Wind Harmer
9.413
247536S-71 GEN
Solar/Wind Harmer
6.09
270444AC2-157 GEN1
Solar/Wind Harmer
0
270445AC2-157 GEN2
Solar/Wind Harmer
0
339216AC1-074 GEN
Solar/Wind Helper
0.225
339243AC2-075 GEN1
Solar/Wind Helper
0.056
253325AC1-069 GEN
Solar/Wind Helper
0.162
253333AC1-068 GEN
Solar/Wind Helper
0.162
253338AC1-165 GEN
Solar/Wind Helper
0.162
253343AC1-166 GEN
Solar/Wind Helper
0.162
270186AC1-089 GEN
Solar/Wind Helper
0.627
276668AB2-070 GEN1
Solar/Wind Harmer
2.017
276763AC1-053 GEN1
Solar/Wind Harmer
3.465
276764AC1-053 GEN2
Solar/Wind Harmer
3.465
276848AB2-070 GEN3
Solar/Wind Harmer
2.017
276849AB2-070 GEN2
Solar/Wind Harmer
2.017
944201AF1-088_MTX
Adder
61.971
957141AF2-008_MTX
Adder
30.986
NYPJM->LTFIMP_NY
CLTF
0.641
LGEELTFEXP_LGEE->PJM
CLTF
1.564
WECLTFEXP_WEC->PJM
CLTF
1.553
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.081
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.003
LAGNLTFEXP_LAGN->PJM
CLTF
4.425
CBM West 1LTFEXP_CBM-W1->PJM
CBM
49.08
CBM West 2LTFEXP_CBM-W2->PJM
CBM
48.557
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.067
CBM South 2LTFEXP_CBM-S2->PJM
CBM
0.063
TVALTFEXP_TVA->PJM
CLTF
1.796
MECLTFEXP_MEC->PJM
CLTF
6.481
SIGELTFEXP_SIGE->PJM
CLTF
0.253
AG2-052LTFEXP_AG2-052->PJM
LTF
0.108
AH1-155LTFEXP_AH1-155->PJM
LTF
0.162
CONTINGENCY 'AEP_P4_#7445_05MARYSV 765_B_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290621 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RF 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 962760 TO BUS 290621 CKT 1    /*AG1-125 TP   765.0 - 05MARYSVL_RF 765.0
END
CONTINGENCY 'AEP_P1-2_#7441_100545_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7441_05SORENS 765_J1_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#7446_05MARYSV 765_B2_SRT-A'
 OPEN BRANCH FROM BUS 242928 TO BUS 242939 CKT 2    /*05MARYSV     765.0 - 05MARYSV     345.0
 OPEN BRANCH FROM BUS 242928 TO BUS 290608 CKT Z1   /*05MARYSV     765.0 - 05MARYSVL_RS 765.0
 OPEN BRANCH FROM BUS 246999 TO BUS 290607 CKT Z1   /*05SORENS     765.0 - 05SORENSN_RM 765.0
 OPEN BRANCH FROM BUS 290607 TO BUS 290608 CKT 1    /*05SORENSN_RM 765.0 - 05MARYSVL_RS 765.0
END
CONTINGENCY 'AEP_P4_#9456_06DEARB1 345_DC_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'AEP_P2-2_#9456_06DEARB1 345_1_SRT-A'
 OPEN BRANCH FROM BUS 243233 TO BUS 248001 CKT Z1   /*05TANNER     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 243233 TO BUS 249565 CKT 1    /*05TANNER     345.0 - 08EBEND      345.0
 OPEN BRANCH FROM BUS 248000 TO BUS 248001 CKT 1    /*06CLIFTY     345.0 - 06DEARB1     345.0
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1    /*06DEARB1     345.0 - 06PIERCE     345.0
END
CONTINGENCY 'DEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A'
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1   /*06DEARB1     345.0 - 06PIERCE     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 248000 CKT 2   /*06DEARB2     345.0 - 06CLIFTY     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 249564 CKT 1   /*06DEARB2     345.0 - 08BUFTN1     345.0
END
CONTINGENCY 'AEP_P7-1_#485___SRT-A'
 OPEN BRANCH FROM BUS 248001 TO BUS 248013 CKT 1   /*06DEARB1     345.0 - 06PIERCE     345.0
 OPEN BRANCH FROM BUS 248002 TO BUS 249564 CKT 1   /*06DEARB2     345.0 - 08BUFTN1     345.0
END
243233 to 249567 ckt 1

Light Load Analysis

The New Service Request AG2-550 was evaluated as a 100.0 MW injection

AG2-550 was evaluated as part of a plant. The plant consists of AG2-550, AG2-551. The total Energy output of the plant was evaluated at its maximum seasonal capability of 150.0 MW (150.0 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC134.87 %255.0B343.9223.19
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-1
SingleAC134.83 %255.0B343.8123.19
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
BreakerAC134.83 %255.0B343.8123.19
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-2
SingleAC130.16 %255.0B331.923.19
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC128.18 %255.0B326.8723.36
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC127.58 %255.0B325.3423.29
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC117.44 %255.0B299.4742.02
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P7-1_#11036___SRT-A
TowerAC113.5 %255.0B289.4217.69
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Base Case
SingleAC112.68 %219.0A246.7717.95
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P7-1_#11035___SRT-A
TowerAC105.43 %255.0B268.8417.86
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A
BusAC103.94 %255.0B265.0420.22
GD2AEP
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A
BusAC103.75 %255.0B264.5620.22
GD2DEO&K
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
DEOK_P_CIRCUIT3281&13803_SRT-A
TowerAC115.47 %54.0B62.351.59
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC121.86 %205.0B249.8113.35
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
BreakerAC121.82 %205.0B249.7313.35
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-1
SingleAC121.81 %205.0B249.7213.35
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-2
SingleAC113.55 %205.0B232.7813.35
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC112.49 %205.0B230.6113.89
GD2AEP
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC110.25 %205.0B226.0213.65
GD2AEP
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Base Case
SingleAC111.33 %323.0A359.5819.97
GD2AEP
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
AEP_P1-2_#17621_SRT-A-3
SingleAC108.94 %449.0B489.1529.41
GD2AEP
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
AEP_P4_#17624_05HAYES 138_A_SRT-A
BreakerAC108.93 %449.0B489.0929.41
GD2AEP
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
AEP_P4_#17625_05HAYES 138_B_SRT-A
BreakerAC108.74 %449.0B488.2629.4
GD2AEP
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
AEP_P1-2_#10526_SRT-A-2
SingleAC107.16 %449.0B481.1635.54
GD2AEP
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
AEP_P2-2_#10144_05RANDOLPH1 138_1_SRT-A
BusAC107.16 %449.0B481.1435.54
GD2AEP
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
AEP_P2-2_#16189_05RANDOLPH2 138_1_SRT-A
BusAC106.8 %449.0B479.5335.52
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#14047_05DESOTO 138_F_SRT-A
BreakerAC134.99 %255.0B344.2223.19
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
BreakerAC134.95 %255.0B344.1223.19
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-1
SingleAC134.94 %255.0B344.1123.19
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P1-2_#15020_SRT-A-2
SingleAC130.28 %255.0B332.2123.19
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15023_05JAY 138_E_SRT-A
BreakerAC128.3 %255.0B327.1723.36
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#15176_05JAY 138_E2_SRT-A
BreakerAC127.7 %255.0B325.6423.29
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
BreakerAC117.44 %255.0B299.4742.02
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P7-1_#11036___SRT-A
TowerAC113.61 %255.0B289.7117.69
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Base Case
SingleAC112.8 %219.0A247.0417.95
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P7-1_#11035___SRT-A
TowerAC105.53 %255.0B269.1117.86
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A
BusAC104.05 %255.0B265.3320.22
GD2AEP
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A
BusAC103.86 %255.0B264.8520.22

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.87 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:343.92
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.5
970883AG2-550 GEN
Solar/Wind Harmer
23.19
247536S-71 GEN
Solar/Wind Harmer
18.292
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.985
971617AH1-308 GEN
Solar/Wind Harmer
10.009
970885AG2-551 GEN
Solar/Wind Harmer
21.082
964611AG1-324 GEN
Solar/Wind Harmer
3.016
971673AH1-337 GEN
Solar/Wind Harmer
13.591
957741AF2-068 GEN
Solar/Wind Harmer
22.115
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
946031AF1-268 GEN
Solar/Wind Harmer
12.237
963791AG1-232 GEN
Solar/Wind Harmer
7.299
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.644
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.063
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.123
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.823
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.135
MECLTFEXP_MEC->PJM
CLTF
0.129

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.83 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:343.81
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.496
970883AG2-550 GEN
Solar/Wind Harmer
23.188
247536S-71 GEN
Solar/Wind Harmer
18.29
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.983
971617AH1-308 GEN
Solar/Wind Harmer
10.008
970885AG2-551 GEN
Solar/Wind Harmer
21.08
964611AG1-324 GEN
Solar/Wind Harmer
3.015
971673AH1-337 GEN
Solar/Wind Harmer
13.59
957741AF2-068 GEN
Solar/Wind Harmer
22.112
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
946031AF1-268 GEN
Solar/Wind Harmer
12.235
963791AG1-232 GEN
Solar/Wind Harmer
7.298
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.122
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.794
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
0.13

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.83 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:343.81
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.496
970883AG2-550 GEN
Solar/Wind Harmer
23.188
247536S-71 GEN
Solar/Wind Harmer
18.29
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.983
971617AH1-308 GEN
Solar/Wind Harmer
10.008
970885AG2-551 GEN
Solar/Wind Harmer
21.08
964611AG1-324 GEN
Solar/Wind Harmer
3.015
971673AH1-337 GEN
Solar/Wind Harmer
13.59
957741AF2-068 GEN
Solar/Wind Harmer
22.112
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
946031AF1-268 GEN
Solar/Wind Harmer
12.235
963791AG1-232 GEN
Solar/Wind Harmer
7.298
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.122
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.794
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
0.13

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.16 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:331.9
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.496
970883AG2-550 GEN
Solar/Wind Harmer
23.188
247536S-71 GEN
Solar/Wind Harmer
18.29
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.983
971617AH1-308 GEN
Solar/Wind Harmer
10.008
970885AG2-551 GEN
Solar/Wind Harmer
21.08
964611AG1-324 GEN
Solar/Wind Harmer
3.015
971673AH1-337 GEN
Solar/Wind Harmer
13.59
957741AF2-068 GEN
Solar/Wind Harmer
22.112
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
963791AG1-232 GEN
Solar/Wind Harmer
7.298
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.122
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.794
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
0.13

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.18 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:326.87
MW Contribution:23.36
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.71
970883AG2-550 GEN
Solar/Wind Harmer
23.365
247536S-71 GEN
Solar/Wind Harmer
18.489
944031AF1-071 GEN
Solar/Wind Helper
0.35
270201AC2-176 GEN
Solar/Wind Harmer
15.398
971617AH1-308 GEN
Solar/Wind Harmer
10.239
971673AH1-337 GEN
Solar/Wind Harmer
13.651
957741AF2-068 GEN
Solar/Wind Harmer
22.725
961761AG1-017 GEN
Solar/Wind Harmer
1.497
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
21.241
963791AG1-232 GEN
Solar/Wind Harmer
7.406
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.21
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.636
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.095
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.12
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.777
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.073
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.18
MECLTFEXP_MEC->PJM
CLTF
0.133

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.58 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:325.34
MW Contribution:23.29
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.619
970883AG2-550 GEN
Solar/Wind Harmer
23.289
247536S-71 GEN
Solar/Wind Harmer
18.403
944031AF1-071 GEN
Solar/Wind Helper
0.35
270201AC2-176 GEN
Solar/Wind Harmer
15.218
971617AH1-308 GEN
Solar/Wind Harmer
10.139
971673AH1-337 GEN
Solar/Wind Harmer
13.625
957741AF2-068 GEN
Solar/Wind Harmer
22.459
961761AG1-017 GEN
Solar/Wind Harmer
1.48
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
21.172
963791AG1-232 GEN
Solar/Wind Harmer
7.361
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.209
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.095
WECLTFEXP_WEC->PJM
CLTF
0.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.119
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.784
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.073
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.1
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.197
MECLTFEXP_MEC->PJM
CLTF
0.136

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.44 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:299.47
MW Contribution:42.02
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
64.319
247536S-71 GEN
Solar/Wind Harmer
39.417
970883AG2-550 GEN
Solar/Wind Harmer
42.017
971673AH1-337 GEN
Solar/Wind Harmer
20.122
270543AE2-219 C
Solar/Wind Harmer
0.001
970885AG2-551 GEN
Solar/Wind Harmer
38.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.059
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.177
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.063
WECLTFEXP_WEC->PJM
CLTF
0.005
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.946
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.051

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P7-1_#11036___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11036___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.5 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:289.42
MW Contribution:17.69
Bus #Bus NameTypeMW Contribution
270201AC2-176 GEN
Solar/Wind Harmer
6.937
971617AH1-308 GEN
Solar/Wind Harmer
4.782
971673AH1-337 GEN
Solar/Wind Harmer
11.494
957741AF2-068 GEN
Solar/Wind Harmer
10.238
971029AG2-637 GEN
Solar/Wind Harmer
34.421
970883AG2-550 GEN
Solar/Wind Harmer
17.687
247536S-71 GEN
Solar/Wind Harmer
12.296
944031AF1-071 GEN
Solar/Wind Helper
0.594
961761AG1-017 GEN
Solar/Wind Harmer
0.674
270543AE2-219 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
16.079
964611AG1-324 GEN
Solar/Wind Harmer
1.231
270383AD1-128 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
2.513
963791AG1-232 GEN
Solar/Wind Harmer
3.768
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.418
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.103
WECLTFEXP_WEC->PJM
CLTF
0.126
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.122
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.173
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.971
MECLTFEXP_MEC->PJM
CLTF
0.407
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.68 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:246.77
MW Contribution:17.95
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
35.277
970883AG2-550 GEN
Solar/Wind Harmer
17.949
247536S-71 GEN
Solar/Wind Harmer
12.318
944031AF1-071 GEN
Solar/Wind Helper
0.386
270201AC2-176 GEN
Solar/Wind Harmer
6.615
971617AH1-308 GEN
Solar/Wind Harmer
4.543
970885AG2-551 GEN
Solar/Wind Harmer
16.317
964611AG1-324 GEN
Solar/Wind Harmer
1.152
971673AH1-337 GEN
Solar/Wind Harmer
11.822
957741AF2-068 GEN
Solar/Wind Harmer
9.763
270543AE2-219 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
0.643
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.125
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.366
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.081
WECLTFEXP_WEC->PJM
CLTF
0.086
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.083
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.438
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.713
MECLTFEXP_MEC->PJM
CLTF
0.262

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P7-1_#11035___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11035___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.43 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:268.84
MW Contribution:17.86
Bus #Bus NameTypeMW Contribution
270201AC2-176 GEN
Solar/Wind Harmer
6.818
971617AH1-308 GEN
Solar/Wind Harmer
4.692
971673AH1-337 GEN
Solar/Wind Harmer
11.673
957741AF2-068 GEN
Solar/Wind Harmer
10.062
971029AG2-637 GEN
Solar/Wind Harmer
34.908
970883AG2-550 GEN
Solar/Wind Harmer
17.862
247536S-71 GEN
Solar/Wind Harmer
12.347
944031AF1-071 GEN
Solar/Wind Helper
0.527
961761AG1-017 GEN
Solar/Wind Harmer
0.663
270543AE2-219 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
16.238
964611AG1-324 GEN
Solar/Wind Harmer
1.2
946031AF1-268 GEN
Solar/Wind Harmer
2.283
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.13
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.374
LAGNLTFEXP_LAGN->PJM
CLTF
0.017
NYPJM->LTFIMP_NY
CLTF
0.095
WECLTFEXP_WEC->PJM
CLTF
0.111
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.092
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.991
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.506
MECLTFEXP_MEC->PJM
CLTF
0.358
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.94 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:265.04
MW Contribution:20.22
Bus #Bus NameTypeMW Contribution
270201AC2-176 GEN
Solar/Wind Harmer
7.269
971617AH1-308 GEN
Solar/Wind Harmer
4.985
971673AH1-337 GEN
Solar/Wind Harmer
12.908
957741AF2-068 GEN
Solar/Wind Harmer
10.728
971029AG2-637 GEN
Solar/Wind Harmer
39.109
970883AG2-550 GEN
Solar/Wind Harmer
20.216
247536S-71 GEN
Solar/Wind Harmer
13.806
944031AF1-071 GEN
Solar/Wind Helper
0.374
961761AG1-017 GEN
Solar/Wind Harmer
0.707
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
18.378
964611AG1-324 GEN
Solar/Wind Harmer
1.256
963791AG1-232 GEN
Solar/Wind Harmer
3.845
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.134
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.396
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.08
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.086
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.375
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.198
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.531
MECLTFEXP_MEC->PJM
CLTF
0.234

Details for 05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line l/o AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05HODGIN_BP-05HAYES 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.75 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:264.56
MW Contribution:20.22
Bus #Bus NameTypeMW Contribution
270201AC2-176 GEN
Solar/Wind Harmer
7.269
971617AH1-308 GEN
Solar/Wind Harmer
4.985
971673AH1-337 GEN
Solar/Wind Harmer
12.908
957741AF2-068 GEN
Solar/Wind Harmer
10.728
971029AG2-637 GEN
Solar/Wind Harmer
39.109
970883AG2-550 GEN
Solar/Wind Harmer
20.216
247536S-71 GEN
Solar/Wind Harmer
13.806
944031AF1-071 GEN
Solar/Wind Helper
0.374
961761AG1-017 GEN
Solar/Wind Harmer
0.707
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
18.378
964611AG1-324 GEN
Solar/Wind Harmer
1.256
963791AG1-232 GEN
Solar/Wind Harmer
3.845
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.134
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.396
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.08
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.086
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.375
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.198
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.531
MECLTFEXP_MEC->PJM
CLTF
0.234

Details for 08MCGFY1-08LOCST1 69.0 kV Ckt 1 line l/o DEOK_P_CIRCUIT3281&13803_SRT-A


Base Case Flowgate

Area:DEO&K
Facility Description:
08MCGFY1-08LOCST1 69.0 kV Ckt 1 line
Contingency Name:
DEOK_P_CIRCUIT3281&13803_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:115.47 %
Rating:54.0 MVA
Rating Type:B
MVA to Mitigate:62.35
MW Contribution:1.59
Bus #Bus NameTypeMW Contribution
270222AC2-111 GEN
Solar/Wind Harmer
3.576
971029AG2-637 GEN
Solar/Wind Harmer
2.889
970883AG2-550 GEN
Solar/Wind Harmer
1.587
970885AG2-551 GEN
Solar/Wind Harmer
1.443
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.038
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.105
LAGNLTFEXP_LAGN->PJM
CLTF
0.036
NYPJM->LTFIMP_NY
CLTF
0.027
WECLTFEXP_WEC->PJM
CLTF
0.043
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.028
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.543
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.68
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.017
CBM West 1LTFEXP_CBM-W1->PJM
CBM
1.417
MECLTFEXP_MEC->PJM
CLTF
0.152
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.86 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:249.81
MW Contribution:13.35
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
14.949
970883AG2-550 GEN
Solar/Wind Harmer
13.351
971029AG2-637 GEN
Solar/Wind Harmer
16.226
971617AH1-308 GEN
Solar/Wind Harmer
29.433
270201AC2-176 GEN
Solar/Wind Harmer
21.374
957741AF2-068 GEN
Solar/Wind Harmer
31.545
971673AH1-337 GEN
Solar/Wind Harmer
4.647
961761AG1-017 GEN
Solar/Wind Harmer
2.078
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
4.302
970885AG2-551 GEN
Solar/Wind Harmer
12.137
946031AF1-268 GEN
Solar/Wind Harmer
17.455
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TVALTFEXP_TVA->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.098
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.12
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:121.82 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:249.73
MW Contribution:13.35
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
14.947
970883AG2-550 GEN
Solar/Wind Harmer
13.348
971029AG2-637 GEN
Solar/Wind Harmer
16.222
971617AH1-308 GEN
Solar/Wind Harmer
29.431
270201AC2-176 GEN
Solar/Wind Harmer
21.372
957741AF2-068 GEN
Solar/Wind Harmer
31.542
971673AH1-337 GEN
Solar/Wind Harmer
4.646
961761AG1-017 GEN
Solar/Wind Harmer
2.078
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0
964611AG1-324 GEN
Solar/Wind Harmer
4.301
970885AG2-551 GEN
Solar/Wind Harmer
12.135
946031AF1-268 GEN
Solar/Wind Harmer
17.453
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TVALTFEXP_TVA->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.095
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.124
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:121.81 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:249.72
MW Contribution:13.35
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
14.947
970883AG2-550 GEN
Solar/Wind Harmer
13.348
971029AG2-637 GEN
Solar/Wind Harmer
16.222
971617AH1-308 GEN
Solar/Wind Harmer
29.431
270201AC2-176 GEN
Solar/Wind Harmer
21.372
964611AG1-324 GEN
Solar/Wind Harmer
4.301
970885AG2-551 GEN
Solar/Wind Harmer
12.135
957741AF2-068 GEN
Solar/Wind Harmer
31.542
971673AH1-337 GEN
Solar/Wind Harmer
4.646
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
2.078
946031AF1-268 GEN
Solar/Wind Harmer
17.453
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TVALTFEXP_TVA->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.095
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.124
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:113.55 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:232.78
MW Contribution:13.35
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
14.947
970883AG2-550 GEN
Solar/Wind Harmer
13.348
971029AG2-637 GEN
Solar/Wind Harmer
16.222
971617AH1-308 GEN
Solar/Wind Harmer
29.431
270201AC2-176 GEN
Solar/Wind Harmer
21.372
964611AG1-324 GEN
Solar/Wind Harmer
4.301
970885AG2-551 GEN
Solar/Wind Harmer
12.135
957741AF2-068 GEN
Solar/Wind Harmer
31.542
971673AH1-337 GEN
Solar/Wind Harmer
4.646
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
2.078
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TVALTFEXP_TVA->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.062
LGEELTFEXP_LGEE->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.019
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.009
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.095
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.124
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.49 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:230.61
MW Contribution:13.89
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
15.554
970883AG2-550 GEN
Solar/Wind Harmer
13.886
971029AG2-637 GEN
Solar/Wind Harmer
16.868
971617AH1-308 GEN
Solar/Wind Harmer
30.135
270201AC2-176 GEN
Solar/Wind Harmer
22.642
957741AF2-068 GEN
Solar/Wind Harmer
33.416
971673AH1-337 GEN
Solar/Wind Harmer
4.83
961761AG1-017 GEN
Solar/Wind Harmer
2.201
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
12.624
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TVALTFEXP_TVA->PJM
CLTF
0.004
NYPJM->LTFIMP_NY
CLTF
0.059
LGEELTFEXP_LGEE->PJM
CLTF
0.115
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.017
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.008
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.105
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.123
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AE2-089 TAP-05ADAM 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:110.25 %
Rating:205.0 MVA
Rating Type:B
MVA to Mitigate:226.02
MW Contribution:13.65
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
15.29
970883AG2-550 GEN
Solar/Wind Harmer
13.653
971029AG2-637 GEN
Solar/Wind Harmer
16.589
971617AH1-308 GEN
Solar/Wind Harmer
29.829
270201AC2-176 GEN
Solar/Wind Harmer
22.089
957741AF2-068 GEN
Solar/Wind Harmer
32.599
971673AH1-337 GEN
Solar/Wind Harmer
4.75
961761AG1-017 GEN
Solar/Wind Harmer
2.148
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
12.412
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TVALTFEXP_TVA->PJM
CLTF
0.008
NYPJM->LTFIMP_NY
CLTF
0.058
LGEELTFEXP_LGEE->PJM
CLTF
0.117
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.016
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.007
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.09
CBM South 1LTFEXP_CBM-S1->PJM
CBM
0.136
SIGELTFEXP_SIGE->PJM
CLTF
0.006

Details for AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:111.33 %
Rating:323.0 MVA
Rating Type:A
MVA to Mitigate:359.58
MW Contribution:19.97
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
22.758
970883AG2-550 GEN
Solar/Wind Harmer
19.968
971029AG2-637 GEN
Solar/Wind Harmer
23.701
270201AC2-176 GEN
Solar/Wind Harmer
31.891
971617AH1-308 GEN
Solar/Wind Harmer
20.828
964611AG1-324 GEN
Solar/Wind Harmer
7.102
970885AG2-551 GEN
Solar/Wind Harmer
18.152
957741AF2-068 GEN
Solar/Wind Harmer
47.066
971673AH1-337 GEN
Solar/Wind Harmer
6.741
970825AG2-519 GEN
50/50
Charging
1.963
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
3.101
946031AF1-268 GEN
Solar/Wind Harmer
39.097
963791AG1-232 GEN
Solar/Wind Harmer
14.379
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.332
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.049
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.151
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.643
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.097
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.313

Details for AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line l/o AEP_P1-2_#17621_SRT-A-3


Base Case Flowgate

Area:AEP
Facility Description:
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#17621_SRT-A-3
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:108.94 %
Rating:449.0 MVA
Rating Type:B
MVA to Mitigate:489.15
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
29.237
970883AG2-550 GEN
Solar/Wind Harmer
29.407
971029AG2-637 GEN
Solar/Wind Harmer
42.255
270201AC2-176 GEN
Solar/Wind Harmer
35.37
971617AH1-308 GEN
Solar/Wind Harmer
23.217
964611AG1-324 GEN
Solar/Wind Harmer
7.708
970885AG2-551 GEN
Solar/Wind Harmer
26.734
957741AF2-068 GEN
Solar/Wind Harmer
52.201
971673AH1-337 GEN
Solar/Wind Harmer
12.958
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.001
961761AG1-017 GEN
Solar/Wind Harmer
3.439
946031AF1-268 GEN
Solar/Wind Harmer
40.137
963791AG1-232 GEN
Solar/Wind Harmer
16.233
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.397
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.242
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.195
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.912
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.123
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.19

Details for AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line l/o AEP_P4_#17624_05HAYES 138_A_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17624_05HAYES 138_A_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.93 %
Rating:449.0 MVA
Rating Type:B
MVA to Mitigate:489.09
MW Contribution:29.41
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
29.234
970883AG2-550 GEN
Solar/Wind Harmer
29.405
971029AG2-637 GEN
Solar/Wind Harmer
42.251
270201AC2-176 GEN
Solar/Wind Harmer
35.368
971617AH1-308 GEN
Solar/Wind Harmer
23.216
957741AF2-068 GEN
Solar/Wind Harmer
52.197
971673AH1-337 GEN
Solar/Wind Harmer
12.957
961761AG1-017 GEN
Solar/Wind Harmer
3.439
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
7.707
970885AG2-551 GEN
Solar/Wind Harmer
26.732
946031AF1-268 GEN
Solar/Wind Harmer
40.134
963791AG1-232 GEN
Solar/Wind Harmer
16.231
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.398
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.243
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.108
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.195
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.918
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.123
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.192

Details for AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line l/o AEP_P4_#17625_05HAYES 138_B_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17625_05HAYES 138_B_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:108.74 %
Rating:449.0 MVA
Rating Type:B
MVA to Mitigate:488.26
MW Contribution:29.4
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
29.228
970883AG2-550 GEN
Solar/Wind Harmer
29.398
971029AG2-637 GEN
Solar/Wind Harmer
42.24
270201AC2-176 GEN
Solar/Wind Harmer
35.362
971617AH1-308 GEN
Solar/Wind Harmer
23.211
957741AF2-068 GEN
Solar/Wind Harmer
52.188
971673AH1-337 GEN
Solar/Wind Harmer
12.953
961761AG1-017 GEN
Solar/Wind Harmer
3.438
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
7.706
970885AG2-551 GEN
Solar/Wind Harmer
26.725
946031AF1-268 GEN
Solar/Wind Harmer
40.129
963791AG1-232 GEN
Solar/Wind Harmer
16.228
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.399
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.248
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.107
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.195
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
7.911
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.123
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.198

Details for AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line l/o AEP_P1-2_#10526_SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#10526_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:107.16 %
Rating:449.0 MVA
Rating Type:B
MVA to Mitigate:481.16
MW Contribution:35.54
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
33.338
970883AG2-550 GEN
Solar/Wind Harmer
35.537
270201AC2-176 GEN
Solar/Wind Harmer
37.351
971617AH1-308 GEN
Solar/Wind Harmer
24.567
964611AG1-324 GEN
Solar/Wind Harmer
8.037
970885AG2-551 GEN
Solar/Wind Harmer
32.306
957741AF2-068 GEN
Solar/Wind Harmer
55.124
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.001
961761AG1-017 GEN
Solar/Wind Harmer
3.631
946031AF1-268 GEN
Solar/Wind Harmer
40.435
963791AG1-232 GEN
Solar/Wind Harmer
17.245
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.43
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.341
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.12
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.213
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.642
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.134
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.242

Details for AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line l/o AEP_P2-2_#10144_05RANDOLPH1 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#10144_05RANDOLPH1 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:107.16 %
Rating:449.0 MVA
Rating Type:B
MVA to Mitigate:481.14
MW Contribution:35.54
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
33.338
970883AG2-550 GEN
Solar/Wind Harmer
35.537
270201AC2-176 GEN
Solar/Wind Harmer
37.351
971617AH1-308 GEN
Solar/Wind Harmer
24.567
957741AF2-068 GEN
Solar/Wind Harmer
55.124
961761AG1-017 GEN
Solar/Wind Harmer
3.631
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
8.037
970885AG2-551 GEN
Solar/Wind Harmer
32.306
946031AF1-268 GEN
Solar/Wind Harmer
40.435
963791AG1-232 GEN
Solar/Wind Harmer
17.245
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.43
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.341
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.12
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.213
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.642
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.134
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.242

Details for AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line l/o AEP_P2-2_#16189_05RANDOLPH2 138_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AF1-268 TP-05DESOTO 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#16189_05RANDOLPH2 138_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:106.8 %
Rating:449.0 MVA
Rating Type:B
MVA to Mitigate:479.53
MW Contribution:35.52
Bus #Bus NameTypeMW Contribution
247536S-71 GEN
Solar/Wind Harmer
33.325
970883AG2-550 GEN
Solar/Wind Harmer
35.523
270201AC2-176 GEN
Solar/Wind Harmer
37.336
971617AH1-308 GEN
Solar/Wind Harmer
24.556
957741AF2-068 GEN
Solar/Wind Harmer
55.102
961761AG1-017 GEN
Solar/Wind Harmer
3.63
962031AG1-047 GEN
Solar/Wind Harmer
0.001
270543AE2-219 C
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
8.034
970885AG2-551 GEN
Solar/Wind Harmer
32.293
946031AF1-268 GEN
Solar/Wind Harmer
40.42
963791AG1-232 GEN
Solar/Wind Harmer
17.235
270024AE2-089 GEN
Solar/Wind Harmer
-0.001
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.429
BlueGrassPJM->LTFIMP_BlueG
CLTF
1.34
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.12
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.212
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
8.613
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
MDUPJM->LTFIMP_MDU
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.134
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
1.247

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#14047_05DESOTO 138_F_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#14047_05DESOTO 138_F_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.99 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:344.22
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.5
970883AG2-550 GEN
Solar/Wind Harmer
23.19
247536S-71 GEN
Solar/Wind Harmer
18.292
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.985
971617AH1-308 GEN
Solar/Wind Harmer
10.009
970885AG2-551 GEN
Solar/Wind Harmer
21.082
964611AG1-324 GEN
Solar/Wind Harmer
3.016
971673AH1-337 GEN
Solar/Wind Harmer
13.591
957741AF2-068 GEN
Solar/Wind Harmer
22.115
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
946031AF1-268 GEN
Solar/Wind Harmer
12.237
963791AG1-232 GEN
Solar/Wind Harmer
7.299
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.644
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.063
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.123
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.823
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.113
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.135
MECLTFEXP_MEC->PJM
CLTF
0.129

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15019_05DESOTO 138_F1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15019_05DESOTO 138_F1_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:134.95 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:344.12
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.496
970883AG2-550 GEN
Solar/Wind Harmer
23.188
247536S-71 GEN
Solar/Wind Harmer
18.29
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.983
971617AH1-308 GEN
Solar/Wind Harmer
10.008
970885AG2-551 GEN
Solar/Wind Harmer
21.08
964611AG1-324 GEN
Solar/Wind Harmer
3.015
971673AH1-337 GEN
Solar/Wind Harmer
13.59
957741AF2-068 GEN
Solar/Wind Harmer
22.112
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
946031AF1-268 GEN
Solar/Wind Harmer
12.235
963791AG1-232 GEN
Solar/Wind Harmer
7.298
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.122
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.794
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
0.13

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-1


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-1
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:134.94 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:344.11
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.496
970883AG2-550 GEN
Solar/Wind Harmer
23.188
247536S-71 GEN
Solar/Wind Harmer
18.29
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.983
971617AH1-308 GEN
Solar/Wind Harmer
10.008
970885AG2-551 GEN
Solar/Wind Harmer
21.08
964611AG1-324 GEN
Solar/Wind Harmer
3.015
971673AH1-337 GEN
Solar/Wind Harmer
13.59
957741AF2-068 GEN
Solar/Wind Harmer
22.112
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
946031AF1-268 GEN
Solar/Wind Harmer
12.235
963791AG1-232 GEN
Solar/Wind Harmer
7.298
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.122
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.794
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
0.13

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P1-2_#15020_SRT-A-2


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P1-2_#15020_SRT-A-2
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:130.28 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:332.21
MW Contribution:23.19
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.496
970883AG2-550 GEN
Solar/Wind Harmer
23.188
247536S-71 GEN
Solar/Wind Harmer
18.29
944031AF1-071 GEN
Solar/Wind Helper
0.351
270201AC2-176 GEN
Solar/Wind Harmer
14.983
971617AH1-308 GEN
Solar/Wind Harmer
10.008
970885AG2-551 GEN
Solar/Wind Harmer
21.08
964611AG1-324 GEN
Solar/Wind Harmer
3.015
971673AH1-337 GEN
Solar/Wind Harmer
13.59
957741AF2-068 GEN
Solar/Wind Harmer
22.112
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.457
963791AG1-232 GEN
Solar/Wind Harmer
7.298
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.212
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.641
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.098
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.122
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.794
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.075
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.11
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.137
MECLTFEXP_MEC->PJM
CLTF
0.13

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15023_05JAY 138_E_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15023_05JAY 138_E_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:128.3 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:327.17
MW Contribution:23.36
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.71
970883AG2-550 GEN
Solar/Wind Harmer
23.365
247536S-71 GEN
Solar/Wind Harmer
18.489
944031AF1-071 GEN
Solar/Wind Helper
0.35
270201AC2-176 GEN
Solar/Wind Harmer
15.398
971617AH1-308 GEN
Solar/Wind Harmer
10.239
971673AH1-337 GEN
Solar/Wind Harmer
13.651
957741AF2-068 GEN
Solar/Wind Harmer
22.725
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
1.497
970885AG2-551 GEN
Solar/Wind Harmer
21.241
963791AG1-232 GEN
Solar/Wind Harmer
7.406
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.21
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.636
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.095
WECLTFEXP_WEC->PJM
CLTF
0.064
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.12
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.777
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.073
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.104
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.18
MECLTFEXP_MEC->PJM
CLTF
0.133

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#15176_05JAY 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#15176_05JAY 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:127.7 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:325.64
MW Contribution:23.29
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
41.619
970883AG2-550 GEN
Solar/Wind Harmer
23.289
247536S-71 GEN
Solar/Wind Harmer
18.403
944031AF1-071 GEN
Solar/Wind Helper
0.35
270201AC2-176 GEN
Solar/Wind Harmer
15.218
971617AH1-308 GEN
Solar/Wind Harmer
10.139
971673AH1-337 GEN
Solar/Wind Harmer
13.625
957741AF2-068 GEN
Solar/Wind Harmer
22.459
961761AG1-017 GEN
Solar/Wind Harmer
1.48
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
21.172
963791AG1-232 GEN
Solar/Wind Harmer
7.361
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.209
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.634
GibsonPJM->LTFIMP_GIBSON
CLTF
0
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.095
WECLTFEXP_WEC->PJM
CLTF
0.065
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.119
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.784
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.073
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.1
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.197
MECLTFEXP_MEC->PJM
CLTF
0.136

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P4_#10527_05BLUFFP 138_E2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#10527_05BLUFFP 138_E2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:117.44 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:299.47
MW Contribution:42.02
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
64.319
247536S-71 GEN
Solar/Wind Harmer
39.417
970883AG2-550 GEN
Solar/Wind Harmer
42.017
971673AH1-337 GEN
Solar/Wind Harmer
20.122
270543AE2-219 C
Solar/Wind Harmer
0.001
970885AG2-551 GEN
Solar/Wind Harmer
38.197
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.059
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.177
GibsonPJM->LTFIMP_GIBSON
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.063
WECLTFEXP_WEC->PJM
CLTF
0.005
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.06
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
0.946
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.036
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.051

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P7-1_#11036___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11036___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:113.61 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:289.71
MW Contribution:17.69
Bus #Bus NameTypeMW Contribution
270201AC2-176 GEN
Solar/Wind Harmer
6.937
971617AH1-308 GEN
Solar/Wind Harmer
4.782
971673AH1-337 GEN
Solar/Wind Harmer
11.494
957741AF2-068 GEN
Solar/Wind Harmer
10.238
971029AG2-637 GEN
Solar/Wind Harmer
34.421
970883AG2-550 GEN
Solar/Wind Harmer
17.687
247536S-71 GEN
Solar/Wind Harmer
12.296
944031AF1-071 GEN
Solar/Wind Helper
0.594
961761AG1-017 GEN
Solar/Wind Harmer
0.674
270543AE2-219 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
16.079
964611AG1-324 GEN
Solar/Wind Harmer
1.231
270383AD1-128 GEN
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
2.513
963791AG1-232 GEN
Solar/Wind Harmer
3.768
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.145
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.418
LAGNLTFEXP_LAGN->PJM
CLTF
0.028
NYPJM->LTFIMP_NY
CLTF
0.103
WECLTFEXP_WEC->PJM
CLTF
0.126
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.1
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
5.122
CBM West 2LTFEXP_CBM-W2->PJM
CBM
1.173
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.059
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.971
MECLTFEXP_MEC->PJM
CLTF
0.407
SIGELTFEXP_SIGE->PJM
CLTF
0.003

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o Base Case


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
Base Case
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:112.8 %
Rating:219.0 MVA
Rating Type:A
MVA to Mitigate:247.04
MW Contribution:17.95
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
35.277
970883AG2-550 GEN
Solar/Wind Harmer
17.949
247536S-71 GEN
Solar/Wind Harmer
12.318
944031AF1-071 GEN
Solar/Wind Helper
0.386
270201AC2-176 GEN
Solar/Wind Harmer
6.615
971617AH1-308 GEN
Solar/Wind Harmer
4.543
970885AG2-551 GEN
Solar/Wind Harmer
16.317
964611AG1-324 GEN
Solar/Wind Harmer
1.152
971673AH1-337 GEN
Solar/Wind Harmer
11.822
957741AF2-068 GEN
Solar/Wind Harmer
9.763
270543AE2-219 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
961761AG1-017 GEN
Solar/Wind Harmer
0.643
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.125
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.366
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.081
WECLTFEXP_WEC->PJM
CLTF
0.086
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.083
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.314
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.438
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.05
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.713
MECLTFEXP_MEC->PJM
CLTF
0.262

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P7-1_#11035___SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P7-1_#11035___SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:105.53 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:269.11
MW Contribution:17.86
Bus #Bus NameTypeMW Contribution
270201AC2-176 GEN
Solar/Wind Harmer
6.818
971617AH1-308 GEN
Solar/Wind Harmer
4.692
971673AH1-337 GEN
Solar/Wind Harmer
11.673
957741AF2-068 GEN
Solar/Wind Harmer
10.062
971029AG2-637 GEN
Solar/Wind Harmer
34.908
970883AG2-550 GEN
Solar/Wind Harmer
17.862
247536S-71 GEN
Solar/Wind Harmer
12.347
944031AF1-071 GEN
Solar/Wind Helper
0.527
961761AG1-017 GEN
Solar/Wind Harmer
0.663
270543AE2-219 C
Solar/Wind Harmer
0
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
16.238
964611AG1-324 GEN
Solar/Wind Harmer
1.2
946031AF1-268 GEN
Solar/Wind Harmer
2.283
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.13
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.374
LAGNLTFEXP_LAGN->PJM
CLTF
0.017
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
NYPJM->LTFIMP_NY
CLTF
0.095
WECLTFEXP_WEC->PJM
CLTF
0.111
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.092
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.548
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.991
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.055
CBM West 1LTFEXP_CBM-W1->PJM
CBM
3.506
MECLTFEXP_MEC->PJM
CLTF
0.358
SIGELTFEXP_SIGE->PJM
CLTF
0.002

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.05 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:265.33
MW Contribution:20.22
Bus #Bus NameTypeMW Contribution
971029AG2-637 GEN
Solar/Wind Harmer
39.109
970883AG2-550 GEN
Solar/Wind Harmer
20.216
247536S-71 GEN
Solar/Wind Harmer
13.806
944031AF1-071 GEN
Solar/Wind Helper
0.374
270201AC2-176 GEN
Solar/Wind Harmer
7.269
971617AH1-308 GEN
Solar/Wind Harmer
4.985
971673AH1-337 GEN
Solar/Wind Harmer
12.908
957741AF2-068 GEN
Solar/Wind Harmer
10.728
961761AG1-017 GEN
Solar/Wind Harmer
0.707
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
18.378
964611AG1-324 GEN
Solar/Wind Harmer
1.256
963791AG1-232 GEN
Solar/Wind Harmer
3.845
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.134
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.396
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.08
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.086
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.375
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.198
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.531
MECLTFEXP_MEC->PJM
CLTF
0.234

Details for AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line l/o AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
AH1-337 TP-05HODGIN_BP 138.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:103.86 %
Rating:255.0 MVA
Rating Type:B
MVA to Mitigate:264.85
MW Contribution:20.22
Bus #Bus NameTypeMW Contribution
270201AC2-176 GEN
Solar/Wind Harmer
7.269
971617AH1-308 GEN
Solar/Wind Harmer
4.985
971673AH1-337 GEN
Solar/Wind Harmer
12.908
957741AF2-068 GEN
Solar/Wind Harmer
10.728
971029AG2-637 GEN
Solar/Wind Harmer
39.109
970883AG2-550 GEN
Solar/Wind Harmer
20.216
247536S-71 GEN
Solar/Wind Harmer
13.806
944031AF1-071 GEN
Solar/Wind Helper
0.374
961761AG1-017 GEN
Solar/Wind Harmer
0.707
270543AE2-219 C
Solar/Wind Harmer
0.001
962031AG1-047 GEN
Solar/Wind Harmer
0
970885AG2-551 GEN
Solar/Wind Harmer
18.378
964611AG1-324 GEN
Solar/Wind Harmer
1.256
963791AG1-232 GEN
Solar/Wind Harmer
3.845
270024AE2-089 GEN
Solar/Wind Harmer
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.134
BlueGrassPJM->LTFIMP_BlueG
CLTF
0.396
NYPJM->LTFIMP_NY
CLTF
0.082
WECLTFEXP_WEC->PJM
CLTF
0.08
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.086
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
MISO WINDMISO-WIND_EXP->MISO-WIND_IMP
CLTF
4.375
CBM West 2LTFEXP_CBM-W2->PJM
CBM
0.198
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.052
CBM West 1LTFEXP_CBM-W1->PJM
CBM
2.531
MECLTFEXP_MEC->PJM
CLTF
0.234
CONTINGENCY 'AEP_P4_#14047_05DESOTO 138_F_SRT-A'
 OPEN BRANCH FROM BUS 243278 TO BUS 243340 CKT 1   /*05DESOTO     138.0 - 05MEDFOR     138.0
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-1'
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P4_#15019_05DESOTO 138_F1_SRT-A'
 OPEN BRANCH FROM BUS 243278 TO BUS 946030 CKT 1   /*05DESOTO     138.0 - AF1-268 TP   138.0
END
CONTINGENCY 'AEP_P1-2_#15020_SRT-A-2'
 OPEN BRANCH FROM BUS 946030 TO BUS 247837 CKT 1   /*AF1-268 TP   138.0 - 05PERCH      138.0
 OPEN BRANCH FROM BUS 964610 TO BUS 247837 CKT 1   /*AG1-324 TP   138.0 - 05PERCH      138.0
END
CONTINGENCY 'AEP_P4_#15023_05JAY 138_E_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 246018 CKT 4   /*05JAY        138.0 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246015 TO BUS 246018 CKT 4   /*05JAY         34.5 - 05JAY 4EQ      1.0
 OPEN BRANCH FROM BUS 246016 TO BUS 246018 CKT 4   /*05JAY         69.0 - 05JAY 4EQ      1.0
END
CONTINGENCY 'AEP_P4_#15176_05JAY 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243319 TO BUS 290130 CKT 2   /*05JAY        138.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 243319 TO BUS 964610 CKT 1   /*05JAY        138.0 - AG1-324 TP   138.0
 OPEN BRANCH FROM BUS 246016 TO BUS 290130 CKT 2   /*05JAY         69.0 - 05JAY 2EQ      1.0
 OPEN BRANCH FROM BUS 290130 TO BUS 290132 CKT 2   /*05JAY 2EQ      1.0 - 05JAY T2      13.1
 REMOVE SWSHUNT FROM BUS 243319                    /*05JAY        138.0
END
CONTINGENCY 'AEP_P4_#10527_05BLUFFP 138_E2_SRT-A'
 OPEN BRANCH FROM BUS 243253 TO BUS 243319 CKT 1   /*05BLUFFP     138.0 - 05JAY        138.0
 OPEN BRANCH FROM BUS 243253 TO BUS 246014 CKT 1   /*05BLUFFP     138.0 - 05BLUFFPNT    69.0
END
CONTINGENCY 'AEP_P7-1_#11036___SRT-A'
 OPEN BRANCH FROM BUS 243259 TO BUS 243262 CKT 1   /*05CNTRVL     138.0 - 05COLLEGE C  138.0
 OPEN BRANCH FROM BUS 243259 TO BUS 243344 CKT 1   /*05CNTRVL     138.0 - 05MODOC      138.0
 OPEN BRANCH FROM BUS 243259 TO BUS 250345 CKT 1   /*05CNTRVL     138.0 - 08CENTVL      69.0
 OPEN BRANCH FROM BUS 243364 TO BUS 288599 CKT 1   /*05RICHMO     138.0 - 05MODOC_BP   138.0
 OPEN BRANCH FROM BUS 243373 TO BUS 288599 CKT 1   /*05SELMAP     138.0 - 05MODOC_BP   138.0
 OPEN BRANCH FROM BUS 243407 TO BUS 250345 CKT 1   /*05RICHCT      69.0 - 08CENTVL      69.0
 OPEN BRANCH FROM BUS 250345 TO BUS 250734 CKT 1   /*08CENTVL      69.0 - 08NWRICH      69.0
END
CONTINGENCY 'AEP_P7-1_#11035___SRT-A'
 OPEN BRANCH FROM BUS 243259 TO BUS 243262 CKT 1   /*05CNTRVL     138.0 - 05COLLEGE C  138.0
 OPEN BRANCH FROM BUS 243259 TO BUS 243344 CKT 1   /*05CNTRVL     138.0 - 05MODOC      138.0
 OPEN BRANCH FROM BUS 243259 TO BUS 250345 CKT 1   /*05CNTRVL     138.0 - 08CENTVL      69.0
 OPEN BRANCH FROM BUS 243262 TO BUS 243364 CKT 1   /*05COLLEGE C  138.0 - 05RICHMO     138.0
 OPEN BRANCH FROM BUS 243407 TO BUS 250345 CKT 1   /*05RICHCT      69.0 - 08CENTVL      69.0
 OPEN BRANCH FROM BUS 250345 TO BUS 250734 CKT 1   /*08CENTVL      69.0 - 08NWRICH      69.0
END
CONTINGENCY 'AEP_P2-2_#15669_05RANDOLPH 69.0_1_SRT-A'
 OPEN BRANCH FROM BUS 244589 TO BUS 246087 CKT 4   /*05RANDOL 4EQ 999.0 - 05RANDOLPH    69.0
 OPEN BRANCH FROM BUS 246079 TO BUS 246087 CKT 1   /*05PRICE       69.0 - 05RANDOLPH    69.0
 REMOVE SWSHUNT FROM BUS 246087                    /*05RANDOLPH    69.0
END
CONTINGENCY 'AEP_P2-2_#15671_05ANCHORHO 69.0_2_SRT-A'
 OPEN BRANCH FROM BUS 246076 TO BUS 246079 CKT 1   /*05ANCHORHO    69.0 - 05PRICE       69.0
END
CONTINGENCY 'DEOK_P_CIRCUIT3281&13803_SRT-A'
 OPEN BUS 250144   /*08HUSTRC     138.0
 OPEN BUS 250168   /*08TRENTON_2  138.0
END
CONTINGENCY 'AEP_P1-2_#17621_SRT-A-3'
 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1   /*05HAYES      138.0 - 05HODGIN_BP  138.0
 OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1   /*AH1-337 TP   138.0 - 05HODGIN_BP  138.0
END
CONTINGENCY 'AEP_P4_#17624_05HAYES 138_A_SRT-A'
 OPEN BRANCH FROM BUS 243310 TO BUS 243400 CKT 1   /*05HODGIN     138.0 - 05HODGIN      69.0
 OPEN BRANCH FROM BUS 243310 TO BUS 290084 CKT 1   /*05HODGIN     138.0 - 05HAYES      138.0
 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1   /*05HAYES      138.0 - 05HODGIN_BP  138.0
 OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1   /*AH1-337 TP   138.0 - 05HODGIN_BP  138.0
END
CONTINGENCY 'AEP_P4_#17625_05HAYES 138_B_SRT-A'
 OPEN BRANCH FROM BUS 253290 TO BUS 290084 CKT 1   /*09BLAZER     138.0 - 05HAYES      138.0
 OPEN BRANCH FROM BUS 290084 TO BUS 290085 CKT 1   /*05HAYES      138.0 - 05HODGIN_BP  138.0
 OPEN BRANCH FROM BUS 971672 TO BUS 290085 CKT 1   /*AH1-337 TP   138.0 - 05HODGIN_BP  138.0
END
CONTINGENCY 'AEP_P1-2_#10526_SRT-A-2'
 OPEN BRANCH FROM BUS 270542 TO BUS 243362 CKT 1   /*AE2-219 TAP  138.0 - 05RANDOLPH1  138.0
END
CONTINGENCY 'AEP_P2-2_#10144_05RANDOLPH1 138_1_SRT-A'
 OPEN BRANCH FROM BUS 243362 TO BUS 244587 CKT Z1   /*05RANDOLPH1  138.0 - 05RANDOLPH2  138.0
 OPEN BRANCH FROM BUS 270542 TO BUS 243362 CKT 1    /*AE2-219 TAP  138.0 - 05RANDOLPH1  138.0
 REMOVE LOAD D3 FROM BUS 243362                     /*05RANDOLPH1  138.0
END
CONTINGENCY 'AEP_P2-2_#16189_05RANDOLPH2 138_1_SRT-A'
 OPEN BRANCH FROM BUS 243362 TO BUS 244587 CKT Z1   /*05RANDOLPH1  138.0 - 05RANDOLPH2  138.0
 OPEN BRANCH FROM BUS 244587 TO BUS 244589 CKT 4    /*05RANDOLPH2  138.0 - 05RANDOL 4EQ 999.0
 OPEN BRANCH FROM BUS 244587 TO BUS 971028 CKT 1    /*05RANDOLPH2  138.0 - AG2-637 TP   138.0
 OPEN BRANCH FROM BUS 244588 TO BUS 244589 CKT 4    /*05RANDOL T4   34.5 - 05RANDOL 4EQ 999.0
 OPEN BRANCH FROM BUS 244589 TO BUS 246087 CKT 4    /*05RANDOL 4EQ 999.0 - 05RANDOLPH    69.0
END
290085 to 290084 ckt 1
251382 to 251376 ckt 1
270019 to 243237 ckt 1
946030 to 243278 ckt 1
971672 to 290085 ckt 1

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AA2-184Atlantic-Red Bank 34kVIn Service
AB1-001Absecon 12 kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-087Sullivan 345kV #1Under Construction
AB1-088Sullivan 345kV #2Engineering & Procurement
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB1-138Navy 34.5kVIn Service
AB1-139Metuchen 26kVIn Service
AB1-141Church-Wye Mills 138 kV IIn Service
AB1-142Church-Wye Mills 138 kV IIIn Service
AB1-150Grassy Falls 138kVIn Service
AB1-176Price 25kV IIEngineering & Procurement
AB1-180Pine View 12kVIn Service
AB2-029Remington 34.5kVIn Service
AB2-032Church-Wye Mills 138 kVIn Service
AB2-037Keeney-Steele 230kVUnder Construction
AB2-049Gloucester Township 12kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-070Mt. Pulaski-BrokawIn Service
AB2-093Ormet 138kVIn Service
AB2-133Chestertown 69kVUnder Construction
AB2-135Church-Kent 69kVIn Service
AB2-136Cambridge-West Cambridge 69kVUnder Construction
AB2-153Church-Wye Mills 138 kVIn Service
AB2-157Prince George's County 12kVIn Service
AB2-158Louisa-South Anna 230kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AB2-179Townsend 138kVIn Service
AC1-001Delano 138kVIn Service
AC1-010Gloucester 26kVUnder Construction
AC1-017Levittown 13 kVIn Service
AC1-030Cinnaminson 13kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-042Altavista-Mt. Airy 69kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-053Lanesville-BrokawPartially in Service - Under Construction
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-074Jacksonville-Renaker 138kV IIn Service
AC1-076Locust Grove-Paytes 115kVIn Service
AC1-078Beatty-London 138kVIn Service
AC1-082Ravenswood-Hemlock 69kVUnder Construction
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-091Cedar Creek 138kV IEngineering & Procurement
AC1-092Cedar Creek 138kV IIEngineering & Procurement
AC1-093Cedar Creek 138kV IIIEngineering & Procurement
AC1-094Cedar Creek 138kV IVEngineering & Procurement
AC1-101Johns Creek-Excel 138kV ISuspended
AC1-102Johns Creek-Excel 138kV IISuspended
AC1-111Aurora 138kVIn Service
AC1-120Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-121Mitchell-Mountain Run 115kVEngineering & Procurement
AC1-122Smith Mountain-Candler's Mountain 138kVIn Service
AC1-141Cook-East Elkhart 345kVIn Service
AC1-145Gretna DP 69 kVIn Service
AC1-158Spotsylvania 500kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-023Hebron 69kVEngineering & Procurement
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-075Jacksonville-Renaker 138 kVIn Service
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-120Ripley 69kVIn Service
AC2-136East Hagerstown 12kVUnder Construction
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-157Sullivan 345 kVUnder Construction
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-186Harrington 25kVUnder Construction
AC2-187Harrington 69kVUnder Construction
AC2-188Harrington 69 kVUnder Construction
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-017Smith Mountain-Bearskin 138 kVIn Service
AD1-020Hunterstown-Lincoln 115 kVIn Service
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-115Mountain Run-Mitchell 115 kVEngineering & Procurement
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-027Camden Switch 26 kVIn Service
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-042Camden Switch 26 kV IIIn Service
AD2-047Davis Creek 138 kVSuspended
AD2-048Cynthia-Headquarters 69 kVUnder Construction
AD2-058St. Barnabas 13 kVIn Service
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-065Atco 12 kVIn Service
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-070Gilbert-Morris Park 34.5kVIn Service
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-100Kincaid-Pana 345 kVSuspended
AD2-115Lyons-Moselem 69kVIn Service
AD2-116Hokes-Grantley 69 kVIn Service
AD2-131Kincaid-Pana 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-135Williamstown 12kVPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-179Morgans Cut-Glen Lyn 138kVSuspended
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-041Edison 4kVIn Service
AE1-071Shade Gap-Roxbury 115 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-081Landing 12.47 kVIn Service
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-100Axton 138 kVIn Service
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-142Manitou-Pleasant Plains 34.5 kVIn Service
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-156Quakertown Solar II 34.5 kVPartially in Service - Under Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-185Hokes-Jackson 69 kVIn Service
AE1-196Hokes-Jackson 69 kV IIIn Service
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-212Grandview-Clifftop 138 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-229Deepwater-Upper Pittsgrove 138 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE1-250Smith Mountain-E. Danville 138 kVEngineering & Procurement
AE2-035Lena 138 kVIn Service
AE2-042Milton 69 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-047Ridgeway-Solite 69 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-059Derry Tap-Derry Bus 69 kVIn Service
AE2-060Mifflintown Bus-Mifflintown Tap 69 kVIn Service
AE2-071Patton Rd-Summer Shade 69 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-125Stahlstown-Ligonier 25 kVIn Service
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-133Penns Tap-Richfield Tie 69 kVIn Service
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-140Axton-Danville 138 kVSuspended
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-160Kanawha River 138 kVEngineering & Procurement
AE2-166Stockton 138 kVSuspended
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-175Jackson-Long Pond 69 kVPartially in Service - Under Construction
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-185Gladys DP-Stonemill Switching Station 69 kVActive
AE2-187Shockoe DP-Chatham 69 kVActive
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-254Garrard County-Tommy-Gooch 69 kVIn Service
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-261Kincaid-Pana 345 kVActive
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-276Sullivan 345kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-283Gladys-Stone Mill 69 kVActive
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-308Three Forks-Dale 138 kVActive
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-326Jacksons Ferry 138 kVEngineering & Procurement
AE2-339Avon 138 kVEngineering & Procurement
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-007Indian River 230 kV ISuspended
AF1-021Bethelboro-Connellsville #1 25 kVIn Service
AF1-022Lake Lynn-Uniontown 25 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-038Sewellton Jct-Webbs Crossroads 69 kVEngineering & Procurement
AF1-039Listonburg-Highpoint 24.9 kVIn Service
AF1-045Cedarville-Ford 138 kVSuspended
AF1-049Berry Hill 138 kVUnder Construction
AF1-050Summer Shade - Green County 161 kVEngineering & Procurement
AF1-051Gavin 765 kVIn Service
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-071College Corner 138 kVEngineering & Procurement
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-083Green County-Saloma 161 kVEngineering & Procurement
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-088Sullivan 345 kVActive
AF1-090Kincaid-PanaEngineering & Procurement
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-130Inez 138 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-143Lick Run 115 kVEngineering & Procurement
AF1-147Poland Rd-Runway DP 230kVUnder Construction
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-161Valley 138 kVActive
AF1-162Inez 138 kVEngineering & Procurement
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-203Patton Rd-Summer Shade 69 kVIn Service
AF1-204Eugene 345 kVActive
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-233Flemingsburg – Spurlock 138kVActive
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-262Upper Pittsgrove 12 kVIn Service
AF1-264Runnemede 13 kVIn Service
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-275Cole 345 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-299Otter Point 34.5 kV IIn Service
AF1-300Otter Point 34.5 kV IIIn Service
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-320Merrill Creek 115 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF1-333Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-337Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-338Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF1-339Laurelton-Mifflinburg 69 kVEngineering & Procurement
AF2-008Sullivan 345 kVActive
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-018Inez 138 kVEngineering & Procurement
AF2-032Kincaid 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-048Rio-Lick 138 kVEngineering & Procurement
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-086Scott Tap-Bowmans Mill Tap 69 kVEngineering & Procurement
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-106Hazel Hollow-Glen Lyn #1 138 kVEngineering & Procurement
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-138Flanders-West Wharton 34.5 kVIn Service
AF2-139Gilbert-Warren Glen 34.5 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-149Sharp Road 69 kVEngineering & Procurement
AF2-150Galion 138 kVUnder Construction
AF2-162Keystone-Desoto 345 kVEngineering & Procurement
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-192Frenchtown Solar-West Flemington 34.5 kVSuspended
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-229Roxbury 23 kVEngineering & Procurement
AF2-233Penns-Richfield Tie #1 69 kVEngineering & Procurement
AF2-234Sunbury Yard #1-Richfield Tie #2 69 kVEngineering & Procurement
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-247Bustleton 13.2 kVIn Service
AF2-250Edgewood 12 kV IIIIn Service
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-307Hope-Belvins Valley Tap 69 kVActive
AF2-325Jacktown 12 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-354Washington 34.5 kV IIEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-361Mifflintown Tap 69 kVEngineering & Procurement
AF2-365Munfordville KU Tap-Horse Cave Jct. 69 kVActive
AF2-370Delaware-Royerton 138 kVActive
AF2-371Harrison-Good Hope 138 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-376Timber Switch 138 kVActive
AF2-377Logtown 138 kVEngineering & Procurement
AF2-378Cambridge 12 kVEngineering & Procurement
AF2-379Princess Anne 25 kVUnder Construction
AF2-382Hurley 69 kVEngineering & Procurement
AF2-383Tolna 115 kVWithdrawn
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AF2-407Fall Creek 345 kVActive
AF2-408Fall Creek 138 kVEngineering & Procurement
AF2-417West Damascus Tap-West Damascus 69 kVEngineering & Procurement
AF2-421East Hazelton-Weatherly Tap 69Engineering & Procurement
AF2-424Reed-Reed Tap #1 69 kVEngineering & Procurement
AF2-425Reed-Reed Tap#1 69 kVEngineering & Procurement
AF2-433Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-434Columbia-Geisinger Tap #1 69 kVEngineering & Procurement
AF2-440Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-017Jay 138 kVUnder Construction
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-070Bon Ayr 69 kVActive
AG1-071Bon Ayr 69 kVActive
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-109Valley 138 kVActive
AG1-118Sugar Grove-Waterman 138kVActive
AG1-124Gladstone 138 kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-156Jack Frost-Lake Harmony 69 kVEngineering & Procurement
AG1-164East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-165East Hazelton-Weatherly Tap 69 kVEngineering & Procurement
AG1-188Manitou-Oyster Creek 34.5 kVEngineering & Procurement
AG1-189Oyster Creek-Bamber Lake 34.5Engineering & Procurement
AG1-191Chester-Pohatcong Mountain 34.5 kVPartially in Service - Under Construction
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-207Vandalia 69 kVEngineering & Procurement
AG1-223Larrabee-Allaire 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-236Lanesville-Brokaw 345 kVActive
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-254Salem-Woodstown 69 kVEngineering & Procurement
AG1-259Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-260Sunbury-Dalmatia 69 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-297Hanna-Tanners Creek 345 kVActive
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-320Glendale-Stephensburg 69 kVActive
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-341Summer Shade 161 kVActive
AG1-348Pequest River-Washington 34.5 kVIn Service
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-351Harrison-Good Hope 138 kVEngineering & Procurement
AG1-354Summershade-Green County 161 kVActive
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-397Walston 12 kVWithdrawn
AG1-405Walnut Grove-Asahi 69 kVActive
AG1-406Walnut Grove-Asahi 69 kVActive
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-414Mississinewa 138 kVEngineering & Procurement
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-460Kincaid-Pana 345 kVActive
AG1-462Cordova 345 kVActive
AG1-469Gordonsville 34.5 kVEngineering & Procurement
AG1-471Up Church-Wayne County 69 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-480Shawnee 34.5 kVEngineering & Procurement
AG1-482Hamilton 115 kVWithdrawn
AG1-495Gilbert-Rocktown 34.5 kVEngineering & Procurement
AG1-499Lambs 12.47 kVUnder Construction
AG1-508Point Lookout 69 kVEngineering & Procurement
AG1-526West Garrard 345 kVActive
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG1-559Caroline Pines 22 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-072Rockport 765 kVActive
AG2-073Crooksville 69 kVActive
AG2-081Mt. Sterling-Fogg Pike 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-126Eugene 345 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-159Williamstown 69 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-179Sewellton Junction 69 kVActive
AG2-184Harbert Metering 138 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-298Sulphur Creek-Loretto 69 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-332East Elkhart – Elcona Tap 138 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-370Tillman 138 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-402Allen 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-424Magnolia - Summersville 69 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-568Stink Run – Sundial 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-582Flint Run 500 kVActive
AG2-585Kensington 138kVActive
AG2-589Ravenswood - Hemlock 69 kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-657Kanawha River - Carbondale 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AG2-670Green County -Taylor County Junction 161 kVActive
AH1-004Avon - Renaker 138 kVActive
AH1-034Patton Road Junction - Summer Shade 69 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-072Red Onion - VC5 69 kVActive
AH1-073Red Onion - VC5 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-098Wolf Glade-West Carroll 138 kVActive
AH1-133Saltville - Tazewell 138 kVActive
AH1-136Falcon - Middle Creek 46 kVActive
AH1-144Peter's Mountain 138 kVActive
AH1-145Peter's Mountain 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-164Oak Level - Tank Hill 138 kVActive
AH1-188Pigeon Creek 138 kVActive
AH1-196Prairie 345 kVActive
AH1-227Flemming - Fremont 69 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-239Upchurch - Zula 69 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-281Bluegrass Parkway Tap - Woodlawn 69 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-292Sullivan 345 kVActive
AH1-298Meridian 345 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-348Pound 34.5 kVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-427Tommy Gooch - Garrard County 69 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-535Nagel - Cane River 230 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-541Chestnut 345 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-570Headquarters - Millersburg Junction 69 kVActive
AH1-571Headquarters - Millersburg Junction 69 kVActive
AH1-617Harbert Metering 138 kVActive
AH1-644Spicewood Metering 138 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-664Goddard-Plumville 138 kVActive
AH1-665Goddard-Plumsville 138 kV IIActive
AH1-666Flemingsburg - Spurlock 138 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-670Blue Mound-Chestnut 345 kVActive
AH1-686Hanging Rock 765 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-721Laurel-Cooper 161 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
V4-067Cates Road Egg Harbor Township 12kVDeactivated
V4-073Yankee 12.5kVIn Service
W1-003Oak HallIn Service
W1-004Oak HallIn Service
W1-005Oak HallIn Service
W1-006Oak HallIn Service
W1-056Ada-Dunkirk 69kVIn Service
W1-130Vine Road 12kVIn Service
W2-030Egg Harbor TownshipIn Service
W2-048Brokaw-LanesvilleIn Service
W3-077Broadway-Stewartsville 34.5kVIn Service
W4-005Blue Mound-LathamIn Service
X1-042WatervlietIn Service
X2-022Brokaw-LanesvilleIn Service
X2-052Dumont-Olive 345kVIn Service
X3-005Wildwood 12kVIn Service
X3-066Church Hill 69kVIn Service
Y1-033Penn Mar-Rock Wood 115kVIn Service
Y1-049Wurno 34.5kVIn Service
Y1-079Wye Mills 69kVIn Service
Y1-080Dorchester 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Y3-058Rockawalkin 69kVIn Service
Z2-076Worcester South 25kVIn Service
Z2-077Worcester North 25kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

Based on the Phase I analysis results, this project may have a cost responsibility for the following System Reinforcements:

AG2-550 System Reinforcements:
TORTEP IDTitleAllocated Cost ($USD)
DEOKn9187.0 / M220257Rebuild 11.9 mile DEOK portion of College Corner-Collinsville line with new structures and 954ACSS/TW Cardinal, 200C$20,673,478
DEOKn9176.0 / M240124Rebuild the 1.4 mile long feeder from McGuffey to Locust.$1,549,119
AEP(Pending) / AEPSERG03AF1-268 TP 138 KV to 05DESOTO 138 KV ckt 1 - Rebuild$457,372
AEP(Pending) / AEP-TC2-1862505HODGIN_BP 138.0 kV to 05HAYES 138.0 kV ckt 1 - Replace Conductor$28,703
AEP(Pending) / AEP-TC2-18633AH1-337 TP 138.0 kV to 05HODGIN_BP 138.0 kV ckt 1 - Replace conductor$28,703
Grand Total:$22,737,375

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: n9187.0
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
n9187.0 / M220257
Title
Rebuild 11.9 mile DEOK portion of College Corner-Collinsville line with new structures and 954ACSS/TW Cardinal, 200C
Description
Rebuild the 11.9 mile DEOK portion of the College Corner-Collinsville line with new structures and 954ACSS/TW, 1 conductor per phase, 200 deg C. This line is on shared structures with College Corner-Trenton. College Corner-Trenton will be rebuilt from College Corner to just outside Collinsville with 954ACSS/TW, 1 conductor per phase, 200 deg C. DEOK's rebuild sections will be built to 480/480/520/520 MVA (SN/SE/WN/WE). Following the DEOK rebuild, AEP's 0.1 mile section will limit the College Corner - Collinsville circuit, but the violation will be alleviated. New Overall circuit ratings: 167/245/210/271 (SN/SE/WN/WE).
Total Cost ($USD)
$58,406,862
Allocated Cost ($USD)
$20,673,478
Time Estimate
48 Months

Contributor

FacilityContingency
05COLLEGE C-08COLINV 138.0 kV Ckt 1 lineDEOK_P4_1403_MIAMI FORT_SRT-A
05COLLEGE C-08COLINV 138.0 kV Ckt 1 lineDEOK_P4_1301_TERMINAL_SRT-A
05COLLEGE C-08COLINV 138.0 kV Ckt 1 lineAEP_P4_#2812_05TANNER 345_T2_SRT-A
05COLLEGE C-08COLINV 138.0 kV Ckt 1 lineDEOK_P_4561TODWOOD14562TODWOOD2_SRT-A
05COLLEGE C-08COLINV 138.0 kV Ckt 1 lineDEOK_P4_1401_MIAMI FORT_SRT-A
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-550
6.9 MW35.4%$20,673,478
AG2-637
12.5 MW64.6%$37,733,384

System Reinforcement: n9176.0
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
n9176.0 / M240124
Title
Rebuild the 1.4 mile long feeder from McGuffey to Locust.
Description
Rebuild the 1.4 mile long feeder from McGuffey to Locust. Retire 54 wood poles. Retire 7,200ft of static. Retire 21,600ft of 4/0ACSR conductor. Install 54 light duty, steel poles. Install two engineered stub poles with foundations. Install 10,000ft of OPGW. Install 25,000ft of 954ACSR Rail conductor. Restore distribution underbuild on 44 poles. Perform two LiDAR flights, one for design engineering and one for post construction facility rating verification.
Total Cost ($USD)
$5,315,554
Allocated Cost ($USD)
$1,549,119
Time Estimate
36 to 39 Months

Aggregate Contributor

FacilityContingency
08LOCST1-08MCGFY1 69.0 kV Ckt 1 lineDEOK_P7_CIRCUIT3281&13803_SRT-A
08LOCST1-08MCGFY1 69.0 kV Ckt 1 lineDEOK_P4_806_TRENTON_SRT-A
08LOCST1-08MCGFY1 69.0 kV Ckt 1 lineDEOK_P_CIRCUIT3281&13803_SRT-A
08LOCST1-08MCGFY1 69.0 kV Ckt 1 lineDEOK_P2.2_HUSTON_SRT-A
08LOCST1-08MCGFY1 69.0 kV Ckt 1 lineDEOK_P2.2_TRENTON1_SRT-A
08LOCST1-08MCGFY1 69.0 kV Ckt 1 lineDEOK_P4_808_TRENTON_SRT-A
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-550
2.4 MW29.1%$1,549,119
AG2-551
1.4 MW17.3%$921,806
AG2-637
4.5 MW53.5%$2,844,629

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEPSERG03
Title
AF1-268 TP 138 KV to 05DESOTO 138 KV ckt 1 - Rebuild
Description
Rebuild 138 kV line from Desoto to AF1-268 ~1.05 miles. Line conductor overloaded size is 1233.6 ACSR/TW 38/19.
Total Cost ($USD)
$2,047,500
Allocated Cost ($USD)
$457,372
Time Estimate
18 to 24 Months

Contributor

FacilityContingency
05DESOTO-AF1-268 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-550
20.0 MW22.3%$457,372
AG2-551
18.2 MW20.3%$415,776
AG2-637
23.7 MW26.5%$542,877
AH1-308
20.8 MW23.3%$477,070
AH1-337
6.7 MW7.5%$154,404

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18625
Title
05HODGIN_BP 138.0 kV to 05HAYES 138.0 kV ckt 1 - Replace Conductor
Description
Replace at Hodgin 138 kV 795kCM AAC 37-Str bus conductor
Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$28,703
Time Estimate
30 to 36 Months

Contributor

FacilityContingency
05HAYES-05HODGIN_BP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-550
65.6 MW28.7%$28,703
AG2-551
21.1 MW9.2%$9,222
AG2-637
100.5 MW43.9%$43,946
AH1-308
10.0 MW4.4%$4,378
AH1-337
31.4 MW13.8%$13,751

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18633
Title
AH1-337 TP 138.0 kV to 05HODGIN_BP 138.0 kV ckt 1 - Replace conductor
Description
Replace at Hodgin 138 kV 795kCM AAC 37-Str bus conductor
Total Cost ($USD)
$100,000
Allocated Cost ($USD)
$28,703
Time Estimate
12 to 18 Months

Contributor

FacilityContingency
05HODGIN_BP-AH1-337 TP 138.0 kV Ckt 1 line(Any)
Cost Allocation
ProjectMW ImpactPercent AllocationAllocated Cost ($USD)
AG2-550
65.6 MW28.7%$28,703
AG2-551
21.1 MW9.2%$9,222
AG2-637
100.5 MW43.9%$43,946
AH1-308
10.0 MW4.4%$4,378
AH1-337
31.4 MW13.8%$13,751

System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.a
Title
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV
Description
Reconductor (possible rebuild) 21.68 miles of transmission line and (1) line drop (line drop at Lemoyne) on the Davis Besse - Lemoyne 345 kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$126,131,949
Allocated Cost ($USD)
$0
Time Estimate
73 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-015.b
Title
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Description
Upgrade (4) L300 wavetraps at Davis Besse and Lemoyne
Total Cost ($USD)
$1,132,675
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-02LEMOYN 345.0 kV Ckt 1 line(Any)

System Reinforcement: s2021.3
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2021.3
Title
Rebuild the ~38.5 mile Jay – Allen 138 kV line from Pennville to the juncture west of Allen station
Description
Rebuild the ~38.5 mile Jay – Allen 138 kV line from Pennville to the juncture west of Allen station. This line is a single circuit 138 kV line using 795 ACSR.
Cost Information
Time Estimate
Dec 20 2023

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-550 is not contingent on this supplemental project as it is already in-service.

FacilityContingency
05ADAM-AE2-089 TAP 138.0 kV Ckt 1 line(Any)

System Reinforcement: b3877.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3877.1
Title
Replace station conductor and switches in the 345 kV yard at Beatty
Description
Replace station conductor and switches in the 345 kV yard at Beatty that are currently limiting the 345 kV lines to Adkins and Chenoweth.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05BEATTY-AF1-228 TP 345.0 kV Ckt 1 line(Any)
05CHENOWETH-AF1-228 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending)
Title
AEP End Rating 245 MVA Rate B
Description
AEP End Rating 245 MVA Rate B
Total Cost ($USD)
$0
Allocated Cost ($USD)
$0
Time Estimate
TBD

Note: This reinforcement is fictitious and will not be cost allocated to projects. It is listed for information purposes only.

FacilityContingency
05COLLEGE C-08COLINV 138.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18693
Title
Greentown 765 kV to Marysville 765 kV - Greenfield Line
Description
Construct a new greenfield 765kV line from Greentown to Marysville (~160 miles). Install 2 new 765kV breakers at Marysville and 2 new 765kV breakers at Greentown. Install 765kV shunt reactors at both Marysville and Greentown The new 765kV line reduces equipment at Dumont to be replaced to CB A2 and switch A2S2. s3442.26 replaces Dumont 765kV CB A2 and A2S2 "CONTINGENCY 'AEP_P1-2_GREENTOWN TO MARYSVILLE 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_GREENTOWN CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END CONTINGENCY 'AEP_P4_MARYSVILLE CB 765_SRT-A' OPEN BRANCH FROM BUS 242928 TO BUS 243207 CKT 1 / 242928 05MARYSV 765 243207 05GRNTWN 765 1 END"
Total Cost ($USD)
$1,000,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 120 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05SORENS-05SORENS 345.0/765.0 kV Ckt 3 transformer(Any)
05SORENS-05SORENSN_RM 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18686
Title
05MADDOX 345.0 kV to 05E LIMA 345.0 kV ckt 1 - String the 2nd conductor
Description
AEP owned line; string the 2nd conductor (2-bundle 954 ACSS) ~30.28 miles on the double circuit line & six wire, At East Lima station replace sub conductor & relay trip limit and at Maddox Creek replace 5.0 IPS Sch. 40 bus work, sub conductor & relay trip limit
Total Cost ($USD)
$48,000,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05E LIMA-05MADDOX 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18687
Title
05HANGRCK_RJ 765.0 kV to 05HANG R 765.0 kV ckt Z1 - Replace Equipment
Description
At Hanging Rock Station replace the following equipment: D1S1 PH A, D1S1 PH B, D1S1 PH C, D1S2 PH A, D1S2 PH B, D1S2 PH C, D2S1 PH A, D2S1 PH B, D2S1 PH C, D2S2 PH A, D2S2 PH B, D2S2 PH C, Jefferson Trap PH A, Jefferson Trap PH B, Jefferson Trap PH C
Total Cost ($USD)
$500,000
Allocated Cost ($USD)
$0
Time Estimate
30 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05HANG R-05HANGRCK_RJ 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05KAMMER-05KAMMER_RG 765.0 kV Ckt Z1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
05MOUNTN-05BELMON 765.0 kV Ckt 1 line(Any)
05HYATT-05VASSEL 345.0 kV Ckt 1 line(Any)
01BELMNT-01FLINTRUN 500.0 kV Ckt 1 line(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01HARRSN-01FLINTRUN 500.0 kV Ckt 1 line(Any)

System Reinforcement: n7683
Type
Load Flow
TO
AEP
RTEP ID / TO ID
n7683
Title
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Description
Rebuild/reconductor 3.05 mi. of the 1275 ACSR/PE 54/19 conductor with 2-954 ACSR 54/7 conductor size with a SN rating of 1410 MVA.
Total Cost ($USD)
$18,460,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3775.1
Type
Load Flow
TO
ComEd
RTEP ID / TO ID
b3775.1
Title
Swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line
Description
Outside of the Green Acres substation, swap the NIPSCO Green Acre Tap towers from the St. John-Green Acres-Olive 345 kV line to the University Park N-Olive 345 kV line to create a University Park N-Green Acres-Olive and St. John-Olive 345 kV lines.
Cost Information
Time Estimate
Dec 01 2026

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18689
Title
AG1-410 TP 345.0 kV to 05MADDOX 345.0 kV ckt 1 - string the 2nd circuit
Description
AEP owned line; string the 2nd circuit on the rebuilt double circuit line, ~ 2.85 miles of 2-bundle 1590 ACSR conductor. At Maddox Creek: Replace 345kV circuit breaker B2, subconductor, disconnect switches.
Total Cost ($USD)
$7,250,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05MADDOX-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: s2213.9
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s2213.9 / (Pending)
Title
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Description
Six-wire 71.5 miles of the Pierce-Don Marquis line. Construct 0.13 miles of line to tie into Don Marquis station.
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned supplemental project. AG2-550 is not contingent on this supplemental project as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18819
Title
06PIERCE 345kV to 05MARQUIS 345kV ckt 1 - Replace Equipment
Description
At Pierce replace the following equipment: Switch 444, 446, 447, and 449, Bus, Risers, Jumpers, Wave Trap, and Line Relay At Don Marquis 345kV replace the following equipment: Circuit Breaker B2, Risers, and Line Reactor.
Total Cost ($USD)
$3,300,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARQUI-06PIERCE 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3878.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3878.1
Title
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station
Description
Upgrade 765 kV circuit breakers 'B' and 'B2' to 5000A 50kA breakers at Marysville Station. In addition, the project will upgrade the existing wavetrap towards Sorenson.
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18659
Title
05MARYSVL_RS 765.0 kV to 05MARYSV 765.0 kV ckt Z1 - Replace Equipment
Description
Replace wave trap, CB-B, and disconnect swiches at Marysville.
Total Cost ($USD)
$9,500,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05MARYSV-05MARYSVL_RS 765.0 kV Ckt Z1 line(Any)

System Reinforcement: b3851.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3851.1 / B3851.1
Title
Rebuild Allen-RP Mone 345kV
Description
Rebuild Allen –R.P. Mone 345kV line (18.6 miles).
Cost Information
Time Estimate
Jun 01 2027

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18707
Title
05ALLEN 345.0 kV to 05RPMONE 345.0 kV ckt 1 - Replace Equipment
Description
At RP Mone: Replace CB B and B2 and associated disconnect switches. Replace 2 - 1700 KCM AAC station conductor. At Allen: Replace the disconnect switches for CBs C and C2 at Allen. Replace 2 - 2000 KCM AAC station conductor. B3851.1 to rebuild the Allen - RP Mone line needs to be completed. CB B is also be proposed to be replaced on another flowgate
Total Cost ($USD)
$5,000,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-05ALLEN 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18732
Title
05RPMONE 345kV to AG1-410 TP 345kV ckt 1 - Replace Equipment
Description
At R.P. Mone: Replace 345kV circuit breakers B & B1, Bus bar 4 x 3/4 Ph C, angle bus buar 4x4x1/4 Ph B, sub conductor, disconnect switches on B and B1 breakers
Total Cost ($USD)
$4,500,000
Allocated Cost ($USD)
$0
Time Estimate
36 to 48 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05RPMONE-AG1-410 TP 345.0 kV Ckt 1 line(Any)

System Reinforcement: s3148.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
s3148.1 / s3148
Title
Reinforcement for AF1-118 TP 345 KV to 05SORENS 345 KV ckt 2
Description
Rebuild Sorenson-Keystone 345kV, Keystone-Desoto 345kV, Sorenson-Desoto 345kV
Cost Information
Time Estimate
Jun 10 2027

Contingent

Note: Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 may need this upgrade in-service to be deliverable to the PJM system. If AG2-550 desires to come into service prior to completion of the upgrade, the Project Developer will need to request PJM to perform an interim study to determine if they would be deliverable for all or a portion of their output for each delivery year until the upgrade is complete.

FacilityContingency
05SORENS-AF1-118 TP 345.0 kV Ckt 2 line(Any)

System Reinforcement: b3788.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b3788.1 / B3788.1
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace AEP-owned station takeoff riser and breaker BB risers at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Nov 18 2027

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement: b3788.2
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
b3788.2 / B3788.2
Title
Replace limiting station elements at Kyger Creek
Description
Upgrade existing 345 kV terminal equipment at Kyger Creek on the Kyger Creek-Sporn 345 kV line. Projected in-service date 6/1/2028 Replace OVEC-owned breaker AA risers, bus work, and breaker AA disconnect switches at OVEC-owned Kyger Creek station.
Cost Information
Time Estimate
Jun 01 2028

Not Contingent

Note: AG2-550 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-550 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18751
Title
05KYGER 345kV to 05SPORN 345kV ckt 1 - Replace Equipment and Sag Study
Description
Sag study Sporn - Kyger Creek line and at Kyger Creek Replace the following equipment: 2156.0 KCM ACSR (84/19), 3000A Switch, CB-BB, 2870 MCM ACSR (Bus), GCB AA, Wave Trap, Line Relay/CT, Meters, Switch 104, and Switch 10
Total Cost ($USD)
$5,052,000
Allocated Cost ($USD)
$0
Time Estimate
48 to 60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05SPORN-06KYGER 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18821
Title
AEP Reinforcements for DEOK New Sub and New 345kV Line from Tanner's Creek
Description
AEP Scope of Work: At Tanners Creek station- install a 345 kV circuit breaker "T", relocate Lawrenceburg #1 345 kV line (between breakers T and T2), relocate Miami Fort 345 kV line (between breakers T and T1), relocate formerly East Bend 345 kV line (to Idlewild Duke station) (between breakers S and S1), and install new Tanners Creek - Idlewild 345 kV line #2 (between breakers R and R1), ~0.35 miles of AEP install and ~2.48 miles of Duke install.
Total Cost ($USD)
$6,700,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
DEOK
RTEP ID / TO ID
(Pending) / F4504
Title
DEOK New Sub and New 345kV Line from Tanner's Creek
Description
This Network Upgrade will be joint effort between DEOK & AEP to mitigate the Miami Fort - Tanner's Creek 345kV violations. DEOK Scope of Work: - DEOK will construct a new 5-breaker Ring Bus, 345kV Switching Station in Northern Kentucky called 'Idlewild'(Lat: 39° 5'15.11"N, Long: 84°49'10.14"W) - DEOK will loop the Tanner's Creek (AEP) - East Bend (DEOK) and Miami Fort (DEOK) - Terminal (DEOK) 345kV circuits into Idlewild Substation - In order to loop the Miami Fort - Terminal circuit into Idlewild Substation, DEOK will retire ~0.68 miles of the Miami Fort - Terminal circuit and add ~0.95 miles of new 345kV conductor (954ACSR 45x7, 2cond/ph, 100C). The new conductor will be built on existing DEOK easement. - DEOK will construct a new 345kV circuit from Idlewild substation to a pole that is just outside AEP's Tanner's Creek Substation. This circuit will be ~2.48 miles long with (1) Ohio River Crossing. The new 345kV circuit will be built will 954ACSS/TW, 2-conductor/phase, 200C conductor. Part of the new 345kV circuit will be built on existing DEOK easement, but DEOK will need to obtain ~1.0 mile of new easement. Line ownership for this new circuit will change at the tower which is just outside AEP's Tanner's Creek Substation in Lawrenceburg, Indiana.
Total Cost ($USD)
$72,000,000
Allocated Cost ($USD)
$0
Time Estimate
72 to 84 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P1-2_#7441_100545_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7445_05MARYSV 765_B_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7441_05SORENS 765_J1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P2-2_#9456_06DEARB1 345_1_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P7-1_#485___SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#7446_05MARYSV 765_B2_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P_4519BUFFCLIFTYPIERCEDEAR1OVEC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineAEP_P4_#9456_06DEARB1 345_DC_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 lineDEOK_P4_1579_EASTBEND_SRT-A
05TANNER-08M.FORT 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9680.0
Type
Load Flow
TO
OVEC
RTEP ID / TO ID
n9680.0 / OVEC0001a
Title
Sag mitigations to bring the Dearborn – Pierce 345 kV line up to a maximum operating temperature of 311° F
Description
•Remove and replace sixteen (16) existing double circuit towers with taller double circuit custom steel poles. (Towers 11, 14, 45, 47, 52, 57, 59, 61, 63, 66, 67, 71, 77, 84, 91, and 96) •Remove and replace two (2) existing river crossing lattice towers with taller lattice structures. (Towers 2 and 140)
Total Cost ($USD)
$24,006,000
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-550 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-550 could receive cost allocation. Although AG2-550 may not presently have cost responsibility for this upgrade, AG2-550 is a potential Aggregate Pool Contributor.

FacilityContingency
06DEARB1-06PIERCE 345.0 kV Ckt 1 line(Any)

Attachments

AG2-550 One Line Diagram

AG2-550 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.