AG2-564 Phase I Study Report

v1.00 released 2025-10-29 20:29

Sulphur Springs 138 kV

32.9 MW Capacity / 49.99 MW Energy

Introduction

This Phase I System Impact Study Report (PH1) has been prepared in accordance with the PJM Open Access Transmission Tariff, Part VII, Subpart D, sections 307 and 308 for New Service Requests (projects) in Transition Cycle 2. The Project Developer/Eligible Customer (developer) is Heartland Solar, LLC, and the Transmission Provider (TP) is PJM Interconnection, LLC (PJM). The interconnected Transmission Owner (TO) is American Electric Power.

Preface

The Phase I System Impact Study is conducted on an aggregate basis within a New Services Request’s Cycle, and results are provided in both (i) a single Cycle executive summary format and (ii) an individual project-level basis. The Phase I System Impact Study Results (for both the executive summary and individual reports) will be publicly available on PJM’s website. Developers must obtain the results from the website.

In accordance with PJM Manual 14H, section 4.3, PJM takes the following actions during the Phase I System Impact Study:
  1. PJM studies each New Service Request on a summer peak, winter peak and light load RTEP base case study. The case year is dependent on the new services cycle under study. PJM will identify the base case year to be used in the study of a specific cycle on its website.
  2. PJM will only perform load flow analysis during the Phase I System Impact Study.
  3. In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with Affected System impacts and provides each Affected System Operator with a list of New Service Request in the Cycle with potential impacts to their respective system.
  4. PJM will create both the short circuit and stability base cases to be used in the Phase II System Impact Study.
  5. The Phase I System Impact Study results will be publicly available on PJM’s website. Project Developers and Eligible Customers must obtain the results from the website.
The Transmission Owner takes the following actions during the Phase I System Impact Study:
  1. Identify required Interconnection Facilities to accommodate the New Service Request.
  2. Identify required Network Upgrades to mitigate system violations from the Phase I System Impact Study.
  3. Provide planning-level preliminary estimates of Interconnection Facilities and Network Upgrades including scope, cost and elapsed time to complete the work.

Decision Point I Requirements

At the close of Phase I System Impact Study, PJM will initiate Decision Point I (DP1). During DP1, the Project Developer will have 30 days to decide whether to proceed with their project. If the Project Developer elects to proceed, they should provide the elements defined in the PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.A.1. Additional information on these elements is available in PJM Manual 14H sections 4.4, 6, and 7.

Allowable project modifications at Decision Point I are defined in PJM Open Access Transmission Tariff, Part VII, Subpart D, section 309.B. Additional information regarding allowable project modifications can be found in PJM Manual 14H, section 9.8.

General

The Project Developer has proposed a Solar generating facility located in the American Electric Power zone — Crawford County, Ohio. The installed facilities will have a total capability of 49.99 MW with 32.9 MW of this output being recognized by PJM as Capacity.

Project Information
New Service Request Number:
AG2-564
Project Name:
Sulphur Springs 138 kV
Project Developer Name:
Heartland Solar, LLC
State:
Ohio
County:
Crawford
Transmission Owner:
American Electric Power
MFO:
49.99
MWE:
49.99
MWC:
32.9
Fuel Type:
Solar
Basecase Study Year:
2028

Physical Interconnection Facility Study

Physical Interconnection Facilities Study is not performed as part of the Phase I System Impact Study. Physical Interconnection Facilities Study will commence in the Phase II System Impact Study.

Point of Interconnection

AG2-564 will interconnect on the American Electric Power transmission system at the Sulphur Springs 138 kV Substation.

Cost Summary

The table below shows a summary of the total cost estimates for this New Service Request project. In the Phase I SIS, the costs shown are subject to change as a result of a facility study performed by the TO during the Phase II or Phase III System Impact Study.

Based on the Phase I SIS results, the AG2-564 project has the following allocation of costs for interconnection. The cost contribution towards Readiness Deposit are also shown below.

Cost Summary
DescriptionCost Allocated to AG2-564Cost Subject to Readiness*
Transmission Owner Interconnection Facilities (TOIF)$0$0
Other Scope$0$0
Option To Build Oversight$0$0
Physical Interconnection Network Upgrades
Stand Alone Network Upgrades$16,698,401$16,698,401
Network Upgrades$0$0
System Reliability Network Upgrades
Steady State Thermal & Voltage (SP & LL)$0$0
Transient Stability$0$0
Short Circuit$0$0
Transmission Owner Analysis
SubRegional$0$0
Distribution$0$0
Affected System Reinforcements
AFS - PJM Violatons$0$0
AFS - Non-PJM Violations$0$0
Total$16,698,401$16,698,401

* Contributes to calculation for Readiness Deposit #2 (RD2). See Readiness Deposit section of report for additional detail.

Definitions

Transmission Owner Interconnection Facilities: Facilities that are owned, controlled, operated and maintained by the Transmission Owner on the Transmission Owner’s side of the Point of Change of Ownership to the Point of Interconnection, including any modifications, additions or upgrades made to such facilities and equipment, that are necessary to physically and electrically interconnect the Generating Facility with the Transmission System or interconnected distribution facilities.

Stand Alone Network Upgrades: Network Upgrades, which are not part of an Affected System, which a Project Developer may construct without affecting day-to-day operations (e.g. taking a transmission outage) of the Transmission System during their construction.

Network Upgrades: Modifications or additions to transmission-related facilities that are integrated with and support the Transmission Provider’s overall Transmission System for the general benefit of all users of such Transmission System. Network Upgrades have no impact or potential impact on the Transmission System until the final tie-in is complete.

Notes

Note 1: PJM Open Access Transmission Tariff (OATT), Part VII, Subpart D, section 307.5 outlines cost allocation rules. The rules are further clarified in PJM Manual 14H, section 4.2.6. PJM shall identify the New Service Requests in the Cycle contributing to the need for the required Network Upgrades within the Cycle. All New Service Requests that contribute to the need for a Network Upgrade will receive cost allocation for that upgrade pursuant to each New Service Request’s contribution to the reliability violation identified on the transmission system in accordance with PJM Manuals.

Note 2: There will be no inter-Cycle cost allocation for Interconnection Facilities or Network Upgrades identified in the System Impact Study costs identified in a Cycle; all such costs shall be allocated to New Service Requests in that Cycle.

Note 3: For Project Developers with System Reinforcements listed: If this project presents cost allocation to a System Reinforcement indicates $0, then please be aware that as changes to the interconnection process occur, such as other projects withdrawing, reducing in size, etc, the cost responsibilities can change and a cost allocation may be assigned to this project. In addition, although this project presents cost allocation to a System Reinforcement is presently $0, this project may need this system reinforcement completed to be deliverable to the PJM system. If this project desires to come into service prior to completion of the system reinforcement, the Project Developer will need to request PJM to perform an interim deliverability study to determine if they would be deliverable for all or a portion of their output for each delivery year until the system reinforcement is complete.

Readiness Deposit

Per Tariff Part VII, Subpart D, section 309 (Decision Point I) A.1.a.i and PJM Manual 14H, section 6.2, Readiness Deposit #2 (RD2) are funds committed by the Project Developer or Eligible Customer based upon the applicable contribution to Network Upgrades as defined below. Readiness Deposits are not used to fund studies nor to offset Security.

During Decision Point I (DP1), the Project Developer or Eligible Customer is required to submit Readiness Deposit #2, which is calculated as 10% of cost allocation for required Phase I Network Upgrades minus Readiness Deposit #1.

Note 1: “Network Upgrades” referred to in the calculation include both (i) the Physical Interconnection Network Upgrades and (ii) the System Reliability Network Upgrades as shown in the Cost Summary table.

Note 2: Readiness Deposit #1 (RD1) = ($4,000 * Project Size (MW))

Note 3: Readiness Deposit #2 (RD2) = 10% of cost allocation for required Network Upgrades minus RD1. Readiness Deposit #2 (RD2) can be zero, but may not be a negative number.

Readiness Deposit #2 Due for Project AG2-564

Readiness Deposit #2 has been calculated for the project based on the Phase I System Impact Study results and is shown in the table below. This Readiness Deposit #2 must be provided at Decision Point I through either a wire transfer or letter of credit per Manual 14H, Section 6.2.

Readiness Deposit
Project ID10% of cost allocation for Phase I Network UpgradesReadiness Deposit #1 Received (RD1)Readiness Deposit #2 (RD2) for AG2-564 Project due at DP1
ABA - B
AG2-564$1,669,840$199,960$1,469,880

Note: Failure to provide an acceptable form of Readiness Deposit #2 by the end of Decision Point I will result in withdrawal and termination of the New Service Request.

For additional detail regarding Readiness Deposit Refunds, reference PJM Manual 14H, section 6.2.1. The Readiness Deposit Letter of Credit template can be found here.

Transmission Owner Scope of Work

The total preliminary cost estimate for the Transmission Owner scope of work (including TOIF and Physical Interconnection Network Upgrades) is given in the table below. These costs do not include CIAC Tax Gross-up.

Stand-Alone Network Upgrades
RTEP IDDescriptionTotal Cost ($USD)Allocated Cost ($USD)
(Pending)AEP will construct a new ring bus station, initially populated with 4 breakers.$16,698,401 $16,698,401

Based on the scope of work for the Interconnection Facilities, it is expected to take a range of 24 to 30 month(s) after the signing of a Generator Interconnection Agreement (as this is a FERC connection) and construction kickoff call to complete the installation of the physical connection work. This assumes that there will be no environmental issues with any of the new properties associated with this project, that there will be no delays in acquiring the necessary permits for implementing the defined interconnection work, and that all system outages will be allowed when requested.

The schedule for any required Network Impact Reinforcements will be more clearly identified in the Phase II and Phase III System Impact Studies.

Transmission Owner Analysis

No Transmission Owner impacts identified.

Developer Requirements

The developer is responsible for all design and construction related activities on the developer’s side of the Point of Change in Ownership. AEP interconnection requirements can be found here.

To the extent that these Applicable Technical Requirements and Standards may conflict with the terms and conditions of the Tariff, the Tariff shall control.

Revenue Metering and SCADA Requirements

PJM Requirements
The developer will be required to install equipment necessary to provide Revenue Metering (KWH, KVARH) and real time data (KW, KVAR) for their generating Resource. See PJM Manual 01, PJM Manual 14D, and PJM Tariff Part IX, Subpart B, Appendix 2, section 8.
Meteorological Data Reporting Requirement
The solar generation facility shall provide the Transmission Provider with site-specific meteorological data including:
  • Temperature (degrees Fahrenheit)
  • Atmospheric Pressure (hectopascals)
  • Irradiance
  • Forced outage data
Transmission Owner Requirements
The Project Developer will be required to comply with all interconnected Transmission Owner’s revenue metering requirements located at the following link: PJM - Transmission Owner Engineering & Construction Standards.

Summer Peak Analysis

The New Service Request AG2-564 was evaluated as a 49.99 MW (32.9 MW Capacity) injection in the AEP area.

AG2-564 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 49.99 MW (49.99 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

StudyAreaFacility DescriptionContingency NameContingency TypeDC|ACFinal Cycle LoadingRating (MVA)Rating TypeMVA to MitigateMW ContributionDetails
GD2AP
01KAMMER-01 502 J 500.0 kV Ckt 1 line
AP_P1-2_WP-500-303T_SRT-A
SingleAC102.42 %3729.0B3819.363.42
GD2ATSI
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
ATSI_P7-1_OEC-345-002_SRT-A
TowerAC109.31 %1745.0B1907.453.5
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-901_SRT-SL
BreakerAC113.76 %1720.0B1956.72.95
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-007A_SRT-SL
BreakerAC104.78 %1878.0B1967.822.66
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-031_SRT-A
BreakerAC100.84 %1878.0B1893.723.04
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-002_SRT-A
BreakerAC174.17 %1878.0B3270.934.28
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-003_SRT-SL
BreakerAC104.76 %1878.0B1967.482.97
GD2ATSI
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
ATSI_P2-3_OEC-345-028_SRT-A
BreakerAC101.37 %1878.0B1903.653.06
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC151.55 %1646.0B2494.572.19
GD2ATSI
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC128.94 %1646.0B2122.341.73
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-005_SRT-A
BreakerAC146.75 %1878.0B2755.892.94
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-006_SRT-SL
BreakerAC144.08 %1878.0B2705.743.1
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_TE-345-010A_SRT-SL
BreakerAC142.21 %1878.0B2670.762.97
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-825_SRT-A
SingleAC136.05 %1878.0B2554.952.27
GD2ATSI
02HAYES-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-824_SRT-A
SingleAC135.68 %1878.0B2548.092.27
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#6497_05MARYSV 345_J2_SRT-A
BreakerAC112.9 %971.0B1096.252.38
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A
BreakerAC105.18 %971.0B1021.282.4
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A
BreakerAC104.18 %971.0B1011.612.4
GD2AEP
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
BusAC104.17 %971.0B1011.542.4
GD2AEP/AP
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
AP_P1-2_WP-500-303T_SRT-A
SingleAC103.49 %3792.0B3924.383.42
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-009_SRT-SL
BreakerAC165.39 %1499.0B2479.152.37
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P2-3_OEC-345-1152-3_SRT-A
BreakerAC142.16 %1798.0B2556.012.18
GD2ATSI
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
ATSI_P1-2_OEC-345-809_SRT-A
SingleAC117.76 %1798.0B2117.361.73

Details for 01KAMMER-01 502 J 500.0 kV Ckt 1 line l/o AP_P1-2_WP-500-303T_SRT-A


Base Case Flowgate

Area:AP
Facility Description:
01KAMMER-01 502 J 500.0 kV Ckt 1 line
Contingency Name:
AP_P1-2_WP-500-303T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:102.42 %
Rating:3729.0 MVA
Rating Type:B
MVA to Mitigate:3819.36
MW Contribution:3.42
Bus #Bus NameTypeMW Contribution
942861AE2-305 GEN
Solar/Wind Harmer
5.429
270518AE2-148 GEN
Solar/Wind Harmer
0.589
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971199AH1-059 GEN
Solar/Wind Harmer
2.717
972159AH1-661 GEN
Adder
0.967
970329AG2-216 GEN
Solar/Wind Harmer
2.879
971231AH1-075 GEN
Solar/Wind Harmer
0.76
25326109MON D
Adder
1.224
971073AG2-665 GEN
Solar/Wind Harmer
5.736
944541AF1-119 GEN
Solar/Wind Harmer
0.422
247620Y3-023
Adder
0.415
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970885AG2-551 GEN
Solar/Wind Harmer
2.091
964611AG1-324 GEN
Solar/Wind Harmer
0.47
270031AE2-169
Solar/Wind Harmer
3.434
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.01
270383AD1-128 GEN
Solar/Wind Harmer
0.004
960441AF2-335 GEN
Solar/Wind Harmer
6.218
965791AG1-447 GEN
Solar/Wind Harmer
5.698
24379505HDWTR1G C
Solar/Wind Harmer
0.002
25194508D.CRK3
Adder
1.257
270120AB2-067 GEN2
50/50
6.34
938701AE1-092 GEN
Solar/Wind Harmer
11.216
270224U2-072_GEN2
Solar/Wind Harmer
0.001
964601AG1-323 GEN
Solar/Wind Harmer
2.785
964601AG1-323 GEN
Solar/Wind Harmer
1.857
971201AH1-060 GEN
Solar/Wind Harmer
1.348
970627AG2-408 GEN
Solar/Wind Harmer
1.931
960971AF2-388 GEN
Solar/Wind Harmer
3.699
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970883AG2-550 GEN
Solar/Wind Harmer
6.273
961051AF2-396 GEN
Solar/Wind Harmer
12.524
961051AF2-396 GEN
Solar/Wind Harmer
8.349
270599AE1-208 GEN
Solar/Wind Harmer
5.724
926881AC1-175 GEN
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.724
24728905RICHG2
Adder
3.349
274803UNIV PARK;6U
Adder
5.083
274887GEN-1.85
Solar/Wind Harmer
0.16
966841AG1-555 GEN
Solar/Wind Harmer
0.687
274674JOLIET 9 ;6U
Adder
13.366
958481AF2-142 GEN
Solar/Wind Harmer
9.035
274862TOP CROP ;2U
Solar/Wind Harmer
0.815
274693ROCKY RD ;1P
Adder
9.492
274683WAUKEGAN ;8U
Adder
18.127
274683WAUKEGAN ;8U
Adder
15.281
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270158DARBY CT3
Adder
8.723
270317AD1-130_GEN
Solar/Wind Harmer
0.01
965051AG1-369 GEN
Solar/Wind Harmer
3.223
253349AC2-067 GEN
Solar/Wind Harmer
2.017
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.423
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.403
971619AH1-309 GEN
Solar/Wind Harmer
2.819
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.657
971985AH1-537 GEN
Solar/Wind Harmer
1.825
274775LINCOLN ;6U
Adder
7.388
274777LINCOLN ;8U
Adder
7.388
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.16
270119AB2-067 GEN1
50/50
6.34
970077AG2-063 GEN
Solar/Wind Harmer
3.964
972269AH1-719 GEN
Adder
2.215
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.243
246938BC-WTG3
Solar/Wind Harmer
0.236
246937BC-WTG2
Solar/Wind Harmer
0.264
270007AE1-245 C
Solar/Wind Harmer
0.002
970621AG2-405 GEN
Solar/Wind Harmer
1.179
970611AG2-400 GEN
Solar/Wind Harmer
6.437
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
8.886
270157DARBY CT2
Adder
8.864
940611AE2-048 GEN
Solar/Wind Harmer
16.743
941391AE2-136 GEN
Solar/Wind Harmer
9.431
971567AH1-282 GEN
Solar/Wind Harmer
9.938
270435AC2-044 GEN
Solar/Wind Harmer
0.825
247607V1-011 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
5.736
270071AF1-092 GEN
Solar/Wind Harmer
12.163
24729505KEY G4
Adder
5.895
270543AE2-219 C
Solar/Wind Harmer
0.004
971673AH1-337 GEN
Solar/Wind Harmer
4.074
971771AH1-392 GEN
Solar/Wind Harmer
6.257
971769AH1-391 GEN
Solar/Wind Harmer
6.959
971549AH1-272 GEN
Solar/Wind Harmer
12.86
270240V3-007_GEN2
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
7.852
25196308WSDLE2
Adder
7.783
25196208WSDLE1
Adder
7.764
25196708WSDLE6
Adder
7.744
270594AE1-207 GEN
Solar/Wind Harmer
6.95
270367AC2-061_GEN
Solar/Wind Harmer
0.005
24691005MDL-2G C
Solar/Wind Harmer
0.001
25196108MFTGT2
Adder
1.342
25196108MFTGT2
Adder
1.246
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
14.27
274863CRW1-WTG
Solar/Wind Harmer
0.002
270051AF1-062 GEN
50/50
10.221
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970065AG2-057 GEN
Solar/Wind Harmer
0.674
965021AG1-366 GEN
Solar/Wind Harmer
2.146
270512AE1-227 GEN2
Solar/Wind Harmer
1.639
270043AE2-236 GEN
Solar/Wind Harmer
4.091
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.425
945111AF1-176 GEN
Solar/Wind Harmer
5.079
24441205WTRV SLR C
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.048
972059AH1-578 GEN
Solar/Wind Harmer
2.879
971191AH1-055 GEN
Solar/Wind Harmer
15.745
274724RIVER EC ;11
Adder
15.509
274772LINCOLN ;3U
Adder
7.388
25196008MFTGT1
Adder
1.179
274802UNIV PARK;5U
Adder
5.083
970941AG2-585 GEN
Solar/Wind Harmer
7.6
274800UNIV PARK;3U
Adder
5.08
276897AD1-100 C
Solar/Wind Harmer
0.008
274729ELWOOD EC;1P
Adder
14.27
276893AG1-478 C
Solar/Wind Harmer
0.24
241832AE2-181_GEN
Solar/Wind Harmer
0.002
970243AG2-164 GEN
Solar/Wind Harmer
3.519
276805AD2-038 GEN
Solar/Wind Harmer
0.002
961921AG1-034 GEN
Solar/Wind Harmer
6.59
942051AE2-217 GEN
Solar/Wind Harmer
12.577
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
970605AG2-385 GEN
Solar/Wind Harmer
4.193
253333AC1-068 GEN
Solar/Wind Harmer
0.011
270273AD2-016 GEN
Solar/Wind Harmer
0.693
270377AD1-106 GEN
Solar/Wind Harmer
2.517
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270247TR4_N_V136
Solar/Wind Harmer
0.042
962761AG1-125 GEN
Solar/Wind Harmer
29.106
270462AD2-086
Solar/Wind Harmer
0.014
241813AF1-122_GEN
Solar/Wind Harmer
3.02
25326309TAIT D
Adder
1.013
944231AF1-091 GEN
Solar/Wind Harmer
1.692
270063AE2-323 C
Solar/Wind Harmer
0.005
247536S-71 GEN
Solar/Wind Harmer
0.253
970245AG2-165 GEN
Solar/Wind Harmer
2.715
270361_3
Solar/Wind Harmer
4.246
252507AC2-088 GEN
Solar/Wind Harmer
0.281
276903AD2-071 C
Solar/Wind Harmer
6.897
972057AH1-577 GEN
Solar/Wind Harmer
4.319
972301AH1-735 GEN
Adder
5.33
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.224
24385905FR-11G C
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
14.27
274674JOLIET 9 ;6U
Adder
13.366
241808AF1-120 C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
4.507
241858AF1-205_GEN
Solar/Wind Harmer
2.406
238147AE2-230_GEN1
Solar/Wind Helper
0.399
235067AD1-061 GEN
Solar/Wind Helper
0.415
238117U2-030
Solar/Wind Helper
0.265
962771AG1-126 GEN
Solar/Wind Harmer
29.106
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.68
943851AF1-053 GEN
Solar/Wind Harmer
1.856
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.97
970689AG2-444 GEN
Solar/Wind Harmer
13.943
970179AG2-119 GEN
Solar/Wind Harmer
6.078
971989AH1-539 GEN
Solar/Wind Harmer
2.83
957201AF2-014 GEN
Solar/Wind Harmer
0
253372AE2-315 SEC3
Adder
1.746
253372AE2-315 SEC3
Adder
1.746
25306009OHH W.
Adder
2.649
963791AG1-232 GEN
Solar/Wind Harmer
8.602
270024AE2-089 GEN
Solar/Wind Harmer
0.007
252524AE2-267 GEN
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.178
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.378
274827FISK ;RP
Adder
6.762
972227AH1-698 GEN1
Adder
2.272
274735ELWOOD EC;4P
Adder
14.27
274744AC1-111 GEN8
Adder
4.832
238109AE1-109 GEN2
Solar/Wind Helper
0.09
238110AE1-109 GEN3
Solar/Wind Helper
0.09
970153AG2-106 GEN
Solar/Wind Harmer
18.586
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
270588AE1-091_GEN
Solar/Wind Harmer
5.133
24721905FLATG4
Adder
18.986
253370AE2-315 SEC1
Adder
1.846
253371AE2-315 SEC2
Adder
1.746
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.196
247643Z2-116 C
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
5.934
25194608D.CRK4
Adder
1.462
970289AG2-191 GEN
Solar/Wind Harmer
0.682
970291AG2-192 GEN
Solar/Wind Harmer
0.62
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
23906502RICHG2&3
Adder
1.066
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.445
274676JOLIET 29;8U
Adder
25.691
274734ELWOOD EC;8P
Adder
14.27
274736ELWOOD EC;9P
Adder
14.27
24728505AND G1
Adder
3.317
943121AE2-341 GEN
Solar/Wind Harmer
10.114
943591AF1-030 GEN
Solar/Wind Harmer
6.726
274682WAUKEGAN ;7U
Adder
15.467
964991AG1-363 GEN
Solar/Wind Helper
4.264
316097T157 G90
Solar/Wind Helper
1.188
237080AD1-060 GEN
Solar/Wind Helper
0.286
24318905MLG2
50/50
6.56
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971655AH1-328 GEN
Solar/Wind Harmer
2.478
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
9.018
25322209TAIT E
Adder
8.815
253370AE2-315 SEC1
Adder
1.846
971677AH1-339 GEN
Solar/Wind Harmer
0.712
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
247621Y3-024
Adder
0.217
965681AG1-436 GEN
Solar/Wind Harmer
7.77
252519AF1-045_GEN
Solar/Wind Harmer
5.405
252516AE2-318_GEN
Solar/Wind Harmer
4.794
971613AH1-306 GEN
Solar/Wind Harmer
2.979
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238169AE2-226 GEN1
Solar/Wind Helper
0.575
238170AE2-226 GEN2
Solar/Wind Helper
0.575
238120AE2-309 GEN
Solar/Wind Helper
0.413
23777801MSM_W1-116
Solar/Wind Helper
0.097
237025AB1-124 C
Solar/Wind Helper
0.14
970623AG2-406 GEN
Solar/Wind Harmer
1.175
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.715
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
6.895
270209AC1-174_GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270186AC1-089 GEN
Solar/Wind Harmer
0.004
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274770LINCOLN ;1U
Adder
7.388
274771LINCOLN ;2U
Adder
7.388
274808UNIV PK N;4U
Adder
4.359
274888KELLY CRK;1U
Solar/Wind Harmer
0.357
972259AH1-714 GEN
Adder
16.604
241996AE2-282_GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.504
970241AG2-163 GEN
Solar/Wind Harmer
3.509
274696ROCKY RD ;4P
Adder
9.813
274697ROCKY RD ;3P
Adder
2.604
238175AF1-290_GEN
Solar/Wind Helper
0.126
235020AA1-095 C
Solar/Wind Helper
0.044
270166AC1-044 GEN3
50/50
6.34
246936BC-WTG1
Solar/Wind Harmer
0.264
270489AE1-102 GEN1
Solar/Wind Harmer
0.847
247522W1-056 GEN
Solar/Wind Harmer
0.001
965011AG1-365 GEN
Solar/Wind Harmer
6.437
958861AF2-177 GEN
Solar/Wind Harmer
2.728
945371AF1-202 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
11.181
270505AE1-170 C O1
Solar/Wind Harmer
6.577
970905AG2-564 GEN
Solar/Wind Harmer
3.422
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
270005AE1-210 C O1
Solar/Wind Harmer
1.348
970825AG2-519 GEN
Solar/Wind Harmer
2.208
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
4.137
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
25196808ZIMRHP
Adder
66.86
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.678
274751CRETE EC ;1U
Adder
7.224
274723RIVER EC ;12
Adder
15.693
274773LINCOLN ;4U
Adder
7.388
274774LINCOLN ;5U
Adder
7.388
25196008MFTGT1
Adder
1.217
274801UNIV PARK;4U
Adder
5.08
24387305FR-4G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.302
23583801GRNGAP
Solar/Wind Helper
4.407
238221AF1-254 C O1
Solar/Wind Helper
0.229
238149AF1-291A_GEN
Solar/Wind Helper
0.114
237061AD1-155 GEN
Solar/Wind Helper
0.043
24318805MLG1
50/50
9.175
270475AD2-096_GEN
50/50
6.148
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.33
270491AE1-102 GEN2
Solar/Wind Harmer
0.847
970217AG2-149 GEN
Solar/Wind Harmer
5.603
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
4.506
270258AD1-119 GEN
Solar/Wind Harmer
0.002
970191AG2-125 GEN
Solar/Wind Harmer
1.648
971617AH1-308 GEN
Solar/Wind Harmer
5.264
24642205MAYFLWER
Adder
0.57
270222AC2-111 GEN
Solar/Wind Harmer
3.157
270004AE1-209 GEN
Solar/Wind Harmer
1.348
270575GUS2 35KV
Solar/Wind Harmer
4.246
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
0.008
274753CRETE EC ;3U
Adder
7.224
958321AF2-126 GEN
Solar/Wind Harmer
0.812
972038AH1-567 GEN2
Adder
0.318
238148AE2-230_GEN2
Solar/Wind Helper
0.401
237038AE2-054 C
Solar/Wind Helper
0.228
238118U2-030_1
Solar/Wind Helper
0.265
23779801AA1-109
Solar/Wind Helper
0.163
972239AH1-704 GEN
50/50
2.67
961821AG1-024 GEN
Solar/Wind Harmer
4.393
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
945631AF1-228 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.008
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.727
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270297AD1-101 GEN
Solar/Wind Harmer
0.002
965041AG1-368 GEN
Solar/Wind Harmer
6.437
253400AC2-068 GEN
Solar/Wind Harmer
0.811
965101AG1-375 GEN
Solar/Wind Harmer
6.295
270499AE1-146 GEN
Solar/Wind Harmer
0.028
971609AH1-304 GEN
Solar/Wind Harmer
1.02
970115AG2-085 GEN
Solar/Wind Harmer
2.487
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196508WSDLE4
Adder
7.549
24699105WLD G1 C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
7.388
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
4.416
274807UNIV PK N;3U
Adder
4.406
274805UNIV PK N;1U
Adder
4.387
24386205FR-12G C
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
24.279
274687WILL CNTY;4U
Adder
24.279
274731ELWOOD EC;2P
Adder
14.27
274733ELWOOD EC;3P
Adder
14.27
963841AG1-237 GEN
Solar/Wind Harmer
2.618
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
274746AC1-111 G10
Adder
4.832
238152AF2-075_GEN
Solar/Wind Helper
0.571
23546401DTGZ2-030
Solar/Wind Helper
0.072
270122AB2-093 CT
50/50
3.544
970149AG2-104 GEN
Solar/Wind Harmer
31.436
270223U2-072_GEN1
Solar/Wind Harmer
0.001
270159DARBY CT4
Adder
8.744
970593AG2-378 GEN
Solar/Wind Harmer
1.551
253325AC1-069 GEN
Solar/Wind Harmer
0.011
270263AC1-001 GEN
Solar/Wind Harmer
0.66
970515AG2-329 GEN
Solar/Wind Harmer
16.808
270510AE1-227 GEN1
Solar/Wind Harmer
1.639
943021AE2-325 GEN
Solar/Wind Harmer
3.267
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970373AG2-245 GEN
Solar/Wind Harmer
12.999
971917AH1-482 GEN
Solar/Wind Harmer
8.008
970773AG2-487 GEN
Solar/Wind Harmer
1.085
24791305MDL-5G
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
941551AE2-152 GEN
Solar/Wind Harmer
0
23920202STRYCT
Adder
1.209
276691AA1-018 GEN1
Solar/Wind Harmer
0.73
963741AG1-226 GEN
Solar/Wind Harmer
14.236
238108AE1-109 GEN1
Solar/Wind Helper
0.09
235531U2-073 GEN
Solar/Wind Helper
2.566
235054AD2-180 GEN
Solar/Wind Helper
1.552
270291AC1-194 GEN
Solar/Wind Harmer
5.098
270404AC1-167 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.474
944531AF1-118 GEN
Solar/Wind Harmer
28.469
970031AG2-029 GEN
Solar/Wind Harmer
4.115
270541AE2-072 C
Solar/Wind Harmer
0.008
970349AG2-230 GEN
Solar/Wind Harmer
9.423
970513AG2-328 GEN
Solar/Wind Harmer
2.715
970517AG2-330 GEN
Solar/Wind Harmer
16.29
247604X1-042
Adder
0.373
958821AF2-173 GEN
Solar/Wind Harmer
8.712
270437AC2-090 C
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
7.627
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274752CRETE EC ;2U
Adder
7.224
970781AG2-491 GEN
Solar/Wind Harmer
6.108
274826FISK ;BP
Adder
9.541
972228AH1-698 GEN2
Adder
3.226
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.835
274730ELWOOD EC;6P
Adder
14.27
24728705AND G3
Adder
6.937
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
15.642
970699AG2-449 GEN
Solar/Wind Harmer
1.504
958171AF2-111 GEN
Solar/Wind Harmer
15.012
23750701CROSSCHOOL
Solar/Wind Helper
1.186
235062AE1-101 C1
Solar/Wind Helper
1.39
238127S14_GEN_2
Solar/Wind Helper
0.65
970155AG2-107 GEN
Solar/Wind Harmer
18.586
270349AD2-093_GEN
Solar/Wind Harmer
0.005
971995AH1-542 GEN
Solar/Wind Harmer
2.546
253343AC1-166 GEN
Solar/Wind Harmer
0.003
24721705FLATG2
Adder
18.986
965421AG1-410 GEN
Solar/Wind Harmer
19.519
247521TR3_G114
Solar/Wind Harmer
0.235
270246TR4_N_V150
Solar/Wind Harmer
0.042
24695305TIMB G C
Solar/Wind Harmer
0.002
960071AF2-298 GEN
Solar/Wind Harmer
3.209
253370AE2-315 SEC1
Adder
1.846
253371AE2-315 SEC2
Adder
1.746
965651AG1-433 GEN
Solar/Wind Harmer
1.85
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.305
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
6.223
970613AG2-401 GEN
Solar/Wind Harmer
4.554
25194608D.CRK4
Adder
1.462
970291AG2-192 GEN
Solar/Wind Harmer
0.806
270428AC2-015 C
Solar/Wind Harmer
0.004
270055AF2-134 C O1
Solar/Wind Harmer
0.005
23906502RICHG2&3
Adder
1.066
23906402RICHG1
Adder
1.066
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.378
241840AF1-064_GEN
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.635
274676JOLIET 29;8U
Adder
26.643
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.317
274745AC1-111 GEN9
Adder
4.832
274682WAUKEGAN ;7U
Adder
15.467
274828WAUKEGAN ;BP
Adder
6.624
276901AD2-066 C O1
Solar/Wind Harmer
0.006
316095T157 G97
Solar/Wind Helper
1.188
238185AF2-356 C
Solar/Wind Helper
2.051
237030AB1-096 C
Solar/Wind Helper
0.06
274864CRW2-WTG
Solar/Wind Harmer
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.378
238126S14_GEN_1
Solar/Wind Helper
0.65
960591AF2-350 GEN
Solar/Wind Harmer
6.08
24386405FR-21G C
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
26.643
274675JOLIET 29;7U
Adder
25.691
970833AG2-524 GEN
Solar/Wind Harmer
6.658
970833AG2-524 GEN
Solar/Wind Harmer
4.438
238208AF1-136 C
Solar/Wind Helper
0.182
23777901MDS_W4-102
Solar/Wind Helper
0.148
237002AB1-128_GEN
Solar/Wind Helper
0.371
23585401KL_K28_T16
Solar/Wind Helper
1.117
237006AB1-125 GEN
Solar/Wind Helper
0.105
24728805RICHG1
Adder
3.349
252509AD1-136 GEN
Solar/Wind Harmer
0.031
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.197
958011AF2-095 GEN
Solar/Wind Harmer
8.755
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.122
274695ROCKY RD ;2P
Adder
9.586
958491AF2-143 GEN
Solar/Wind Harmer
9.003
237034AC2-136 C
Solar/Wind Helper
0.19
235063AE1-101 C2
Solar/Wind Helper
1.39
237001AB1-127_GEN
Solar/Wind Helper
0.371
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.332
CPLELTFEXP_CPLE->PJM
CLTF
0.483
SIGELTFEXP_SIGE->PJM
CLTF
0.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.222
WECLTFEXP_WEC->PJM
CLTF
3.25
LAGNLTFEXP_LAGN->PJM
CLTF
12.385
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.63
LGEELTFEXP_LGEE->PJM
CLTF
5.644
MECLTFEXP_MEC->PJM
CLTF
13.455
AH1-155LTFEXP_AH1-155->PJM
LTF
0.306
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.087
NYPJM->LTFIMP_NY
CLTF
4.259
TVALTFEXP_TVA->PJM
CLTF
6.061
AG2-052LTFEXP_AG2-052->PJM
LTF
0.204

Details for 02BEAVER-02CARLIL 345.0 kV Ckt 1 line l/o ATSI_P7-1_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02CARLIL 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P7-1_OEC-345-002_SRT-A
Contingency Type:Tower
DC|AC:AC
Final Cycle Loading:109.31 %
Rating:1745.0 MVA
Rating Type:B
MVA to Mitigate:1907.45
MW Contribution:3.5
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
Adder
1.187
270588AE1-091_GEN
Solar/Wind Harmer
6.591
247643Z2-116 C
Solar/Wind Harmer
0.032
203830AF1-094 GEN
Solar/Wind Helper
0.245
971989AH1-539 GEN
Solar/Wind Harmer
7.613
957201AF2-014 GEN
Solar/Wind Harmer
2.368
944161AF1-084 GEN
Solar/Wind Harmer
1.106
270302AB2-170 GEN
Solar/Wind Harmer
3.966
23857102WLORG-A
50/50
9.096
270541AE2-072 C
Solar/Wind Harmer
3.99
270404AC1-167 GEN
Solar/Wind Harmer
0.641
958091AF2-103 GEN
Solar/Wind Harmer
0.086
247604X1-042
Adder
0.22
270377AD1-106 GEN
Solar/Wind Harmer
3.082
270247TR4_N_V136
Solar/Wind Harmer
0.414
970031AG2-029 GEN
Solar/Wind Harmer
14.083
942871AE2-306 GEN
Solar/Wind Harmer
0.398
270391AF1-285 GEN3
Solar/Wind Harmer
0.204
254305AE2-115 C
Solar/Wind Helper
0.104
945641AF1-229 GEN
Solar/Wind Harmer
3.229
970159AG2-109 GEN
Solar/Wind Harmer
3.418
965051AG1-369 GEN
Solar/Wind Harmer
2.43
270317AD1-130_GEN
Solar/Wind Harmer
1.52
966321AG1-501 GEN
50/50
1.834
23856402BAYSG1
50/50
1.196
241858AF1-205_GEN
Solar/Wind Harmer
4.928
241808AF1-120 C
Solar/Wind Harmer
1.077
972301AH1-735 GEN
Adder
5.944
270361_3
Solar/Wind Harmer
8.521
944231AF1-091 GEN
Solar/Wind Harmer
2.19
241847AF2-150_GEN
Solar/Wind Harmer
2.294
270462AD2-086
Solar/Wind Harmer
3.299
270063AE2-323 C
Solar/Wind Harmer
1.038
241813AF1-122_GEN
Solar/Wind Harmer
2.935
270391AF1-285 GEN3
Solar/Wind Harmer
0.531
24189802OREGON_CT1
50/50
2.254
942801AE2-298 GEN
Solar/Wind Harmer
0.797
961051AF2-396 GEN
Solar/Wind Harmer
7.783
961051AF2-396 GEN
Solar/Wind Harmer
3.62
270216AD2-079_GEN
Solar/Wind Harmer
0.283
971201AH1-060 GEN
Solar/Wind Harmer
0.917
270224U2-072_GEN2
Solar/Wind Harmer
0.868
203947AF1-006 C
Solar/Wind Helper
0.283
241967AE2-285_GEN
Solar/Wind Helper
0.314
957071AF2-004 GEN
50/50
12.095
23929302BS-PKR
50/50
2.106
958321AF2-126 GEN
Solar/Wind Harmer
1.366
270575GUS2 35KV
Solar/Wind Harmer
10.039
970217AG2-149 GEN
Solar/Wind Harmer
22.552
270258AD1-119 GEN
Solar/Wind Harmer
1.565
961961AG1-039 GEN
Solar/Wind Harmer
1.583
270491AE1-102 GEN2
Solar/Wind Harmer
0.679
270191TR4_S_V150
Solar/Wind Harmer
1.46
24642205MAYFLWER
Adder
0.299
959331AF2-224 GEN
Solar/Wind Harmer
4.645
962511AG1-100 GEN
Solar/Wind Helper
0.255
959441AF2-235 GEN
Solar/Wind Helper
0.115
972211AH1-690 GEN
50/50
238.133
24191202EL_AA1-006
Adder
0.297
970817AG2-515 GEN
Solar/Wind Harmer
13.044
945411AF1-206 GEN
Solar/Wind Harmer
7.213
270499AE1-146 GEN
Solar/Wind Harmer
2.343
270297AD1-101 GEN
Solar/Wind Harmer
1.75
966831AG1-554 GEN
Solar/Wind Harmer
0.704
965041AG1-368 GEN
Solar/Wind Harmer
4.881
971219AH1-069 GEN
Solar/Wind Harmer
0.796
270578AF1-285 GEN2
Solar/Wind Harmer
0.204
960681AF2-359 GEN
Solar/Wind Harmer
1.625
241982AE2-343 S C
Solar/Wind Helper
0.109
254304AE2-114 C
Solar/Wind Helper
0.104
23920202STRYCT
Adder
1.608
970515AG2-329 GEN
Solar/Wind Harmer
10.227
943021AE2-325 GEN
Solar/Wind Harmer
1.799
270223U2-072_GEN1
Solar/Wind Harmer
0.868
270578AF1-285 GEN2
Solar/Wind Harmer
0.531
966311AG1-500 GEN
50/50
141.29
971231AH1-075 GEN
Solar/Wind Harmer
0.399
960981AF2-389 GEN
Solar/Wind Harmer
0.728
247620Y3-023
Adder
0.218
270526AF1-158 GEN
Solar/Wind Harmer
2.042
24441505OLIV SLR
Solar/Wind Harmer
0.06
241960AC2-195 GEN
Solar/Wind Harmer
1.215
965791AG1-447 GEN
Solar/Wind Harmer
2.75
970179AG2-119 GEN
Solar/Wind Harmer
3.495
963791AG1-232 GEN
Solar/Wind Harmer
5.807
241997AF1-093 GEN
Solar/Wind Helper
0.121
23917102WLORG-2
50/50
1.505
957111AF2-005 GEN
50/50
1.467
24189902OREGON_CT2
50/50
2.208
241807AE2-176_GEN
Solar/Wind Harmer
6.057
241840AF1-064_GEN
Solar/Wind Harmer
1.274
23906402RICHG1
Adder
1.189
23906502RICHG2&3
Adder
1.187
270428AC2-015 C
Solar/Wind Harmer
4.415
965421AG1-410 GEN
Solar/Wind Harmer
15.499
24695305TIMB G C
Solar/Wind Harmer
2.781
270449AD2-020 GEN
Solar/Wind Harmer
1.385
247521TR3_G114
Solar/Wind Harmer
1.636
270246TR4_N_V150
Solar/Wind Harmer
0.414
24639705ELKHART HY
Adder
0.072
971221AH1-070 GEN
Solar/Wind Harmer
0.796
203835AF1-098 GEN
Solar/Wind Helper
0.992
241966AE1-183 GEN
Solar/Wind Helper
0.121
203860AG1-193 C
Solar/Wind Helper
0.116
23857202WLORG-B
50/50
9.372
24190002OREGON_ST1
50/50
2.971
971677AH1-339 GEN
Solar/Wind Harmer
6.773
270227U2-072_GEN3
Solar/Wind Harmer
0.868
270228U2-072_GEN4
Solar/Wind Harmer
0.868
270231U2-072_GEN5
Solar/Wind Harmer
0.868
965681AG1-436 GEN
Solar/Wind Harmer
5.376
241801AE1-079 GEN
Solar/Wind Helper
0.122
203980AG1-197 GEN
Solar/Wind Helper
0.188
203979AG1-198 GEN
Solar/Wind Helper
0.147
23917502WLORG-6
50/50
0.764
241832AE2-181_GEN
Solar/Wind Harmer
1.75
270044AE2-322 C
Solar/Wind Harmer
0.769
24441205WTRV SLR C
Solar/Wind Harmer
0.07
945111AF1-176 GEN
Solar/Wind Harmer
2.737
270485AE1-090_GEN
Solar/Wind Harmer
0.287
965021AG1-366 GEN
Solar/Wind Harmer
1.08
970065AG2-057 GEN
Solar/Wind Harmer
0.459
270043AE2-236 GEN
Solar/Wind Harmer
2.394
23867002DVBSG1
50/50
10.407
241886AC2-103 GEN2
Solar/Wind Harmer
14.419
971549AH1-272 GEN
Solar/Wind Harmer
11.155
971567AH1-282 GEN
Solar/Wind Harmer
8.024
247607V1-011 GEN
Solar/Wind Harmer
2.098
270435AC2-044 GEN
Solar/Wind Harmer
1.044
971771AH1-392 GEN
Solar/Wind Harmer
4.129
971769AH1-391 GEN
Solar/Wind Harmer
4.471
23917402WLORG-5
50/50
1.527
241885AC2-103 GEN1
Solar/Wind Harmer
14.419
972253AH1-711 GEN
Adder
43.699
960841AF2-375 GEN
Solar/Wind Harmer
3.749
247522W1-056 GEN
Solar/Wind Harmer
1.589
970905AG2-564 GEN
Solar/Wind Harmer
3.497
246936BC-WTG1
Solar/Wind Harmer
2.043
270489AE1-102 GEN1
Solar/Wind Harmer
0.679
945111AF1-176 GEN
Solar/Wind Harmer
8.634
270505AE1-170 C O1
Solar/Wind Harmer
7.249
965011AG1-365 GEN
Solar/Wind Harmer
4.645
961971AG1-040 GEN
Solar/Wind Helper
0.251
254303AC2-168 GEN
Solar/Wind Helper
0.071
23917202WLORG-3
50/50
1.553
23917302WLORG-4
50/50
1.519
241996AE2-282_GEN
Solar/Wind Harmer
1.931
270007AE1-245 C
Solar/Wind Harmer
3.147
246938BC-WTG3
Solar/Wind Harmer
2.078
246937BC-WTG2
Solar/Wind Harmer
2.043
957891AF2-083 GEN
Solar/Wind Harmer
1.625
970611AG2-400 GEN
Solar/Wind Harmer
4.645
241985AE1-237 GEN
Solar/Wind Helper
0.122
962101AG1-054 GEN
Solar/Wind Helper
0.304
990527J1329
External Queue
1.536989450454712
991177J1571 G
External Queue
13.065269470214844
990142J1224
External Queue
11.235392570495605
CBM West 1LTFEXP_CBM-W1->PJM
CBM
79.335
NYPJM->LTFIMP_NY
CLTF
1.797
TVALTFEXP_TVA->PJM
CLTF
1.857
AG2-052LTFEXP_AG2-052->PJM
LTF
0.091
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.536
CPLELTFEXP_CPLE->PJM
CLTF
0.14
SIGELTFEXP_SIGE->PJM
CLTF
0.142
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.4
WECLTFEXP_WEC->PJM
CLTF
1.408
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
33.236
LGEELTFEXP_LGEE->PJM
CLTF
1.709
MECLTFEXP_MEC->PJM
CLTF
5.472
AH1-155LTFEXP_AH1-155->PJM
LTF
0.136

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-901_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-901_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:113.76 %
Rating:1720.0 MVA
Rating Type:B
MVA to Mitigate:1956.7
MW Contribution:2.95
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.149
241886AC2-103 GEN2
Solar/Wind Harmer
12.757
971549AH1-272 GEN
Solar/Wind Harmer
10.147
247607V1-011 GEN
Solar/Wind Harmer
1.919
971567AH1-282 GEN
Solar/Wind Harmer
7.189
270435AC2-044 GEN
Solar/Wind Harmer
0.957
241832AE2-181_GEN
Solar/Wind Harmer
1.539
270044AE2-322 C
Solar/Wind Harmer
0.699
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.527
270485AE1-090_GEN
Solar/Wind Harmer
0.265
965021AG1-366 GEN
Solar/Wind Harmer
1
23917402WLORG-5
50/50
1.356
241885AC2-103 GEN1
Solar/Wind Harmer
12.757
972253AH1-711 GEN
Adder
38.383
960841AF2-375 GEN
Solar/Wind Harmer
3.283
247522W1-056 GEN
Solar/Wind Harmer
1.41
970905AG2-564 GEN
Solar/Wind Harmer
2.954
246936BC-WTG1
Solar/Wind Harmer
1.873
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
945111AF1-176 GEN
Solar/Wind Harmer
7.974
270505AE1-170 C O1
Solar/Wind Harmer
6.696
965011AG1-365 GEN
Solar/Wind Harmer
4.301
961971AG1-040 GEN
Solar/Wind Helper
0.397
254303AC2-168 GEN
Solar/Wind Helper
0.068
945641AF1-229 GEN
Solar/Wind Harmer
2.848
970159AG2-109 GEN
Solar/Wind Harmer
2.554
965051AG1-369 GEN
Solar/Wind Harmer
2.239
270317AD1-130_GEN
Solar/Wind Harmer
1.405
203846AF2-130 C
Solar/Wind Helper
0.272
23856402BAYSG1
50/50
1.043
241858AF1-205_GEN
Solar/Wind Harmer
4.326
241808AF1-120 C
Solar/Wind Harmer
0.946
972301AH1-735 GEN
Adder
5.258
270361_3
Solar/Wind Harmer
7.454
966321AG1-501 GEN
Adder
0.867
944231AF1-091 GEN
Solar/Wind Harmer
1.993
241847AF2-150_GEN
Solar/Wind Harmer
1.989
270462AD2-086
Solar/Wind Harmer
3.05
270063AE2-323 C
Solar/Wind Harmer
0.96
24189802OREGON_CT1
50/50
1.98
942801AE2-298 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
7.181
961051AF2-396 GEN
Solar/Wind Harmer
3.34
270216AD2-079_GEN
Solar/Wind Harmer
0.262
203947AF1-006 C
Solar/Wind Helper
0.458
241967AE2-285_GEN
Solar/Wind Helper
0.308
971989AH1-539 GEN
Solar/Wind Harmer
6.852
957201AF2-014 GEN
Solar/Wind Harmer
2.171
944161AF1-084 GEN
Solar/Wind Harmer
1.019
270302AB2-170 GEN
Solar/Wind Harmer
3.666
203804AE2-113_GEN
Solar/Wind Helper
0.933
241997AF1-093 GEN
Solar/Wind Helper
0.118
23857102WLORG-A
Adder
4.299
270541AE2-072 C
Solar/Wind Harmer
3.537
270404AC1-167 GEN
Solar/Wind Harmer
0.582
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.202
270377AD1-106 GEN
Solar/Wind Harmer
2.793
270247TR4_N_V136
Solar/Wind Harmer
0.381
970031AG2-029 GEN
Solar/Wind Harmer
13.034
254305AE2-115 C
Solar/Wind Helper
0.102
957071AF2-004 GEN
50/50
10.742
23929302BS-PKR
50/50
1.836
958321AF2-126 GEN
Solar/Wind Harmer
1.2
270575GUS2 35KV
Solar/Wind Harmer
8.781
970217AG2-149 GEN
Solar/Wind Harmer
19.929
270258AD1-119 GEN
Solar/Wind Harmer
1.426
961961AG1-039 GEN
Solar/Wind Harmer
1.372
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
270191TR4_S_V150
Solar/Wind Harmer
1.345
24642205MAYFLWER
Adder
0.277
959331AF2-224 GEN
Solar/Wind Harmer
4.301
972211AH1-690 GEN
50/50
209.151
970817AG2-515 GEN
Solar/Wind Harmer
11.458
24191202EL_AA1-006
Adder
0.247
945411AF1-206 GEN
Solar/Wind Harmer
6.338
270499AE1-146 GEN
Solar/Wind Harmer
2.056
270297AD1-101 GEN
Solar/Wind Harmer
1.58
966831AG1-554 GEN
Solar/Wind Harmer
0.634
965041AG1-368 GEN
Solar/Wind Harmer
4.498
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
966311AG1-500 GEN
50/50
125.486
971231AH1-075 GEN
Solar/Wind Harmer
0.362
960981AF2-389 GEN
Solar/Wind Harmer
0.673
247620Y3-023
Adder
0.202
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
23917102WLORG-2
50/50
1.337
24189902OREGON_CT2
50/50
1.94
241807AE2-176_GEN
Solar/Wind Harmer
5.062
241840AF1-064_GEN
Solar/Wind Harmer
1.119
23906402RICHG1
Adder
1.052
23906502RICHG2&3
Adder
1.05
957111AF2-005 GEN
Adder
0.693
270428AC2-015 C
Solar/Wind Harmer
3.75
965421AG1-410 GEN
Solar/Wind Harmer
14.219
24695305TIMB G C
Solar/Wind Harmer
2.555
270449AD2-020 GEN
Solar/Wind Harmer
1.277
247521TR3_G114
Solar/Wind Harmer
1.508
270246TR4_N_V150
Solar/Wind Harmer
0.381
24639705ELKHART HY
Adder
0.067
203835AF1-098 GEN
Solar/Wind Helper
1.566
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
23906502RICHG2&3
Adder
1.05
270588AE1-091_GEN
Solar/Wind Harmer
5.941
247643Z2-116 C
Solar/Wind Harmer
0.03
203830AF1-094 GEN
Solar/Wind Helper
0.382
962511AG1-100 GEN
Solar/Wind Helper
0.409
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.688
23920202STRYCT
Adder
1.415
970515AG2-329 GEN
Solar/Wind Harmer
9.037
943021AE2-325 GEN
Solar/Wind Harmer
1.659
203954AE2-126 C
Solar/Wind Helper
0.23
24190002OREGON_ST1
50/50
2.61
23857202WLORG-B
Adder
4.429
971677AH1-339 GEN
Solar/Wind Harmer
5.947
203980AG1-197 GEN
Solar/Wind Helper
0.296
203979AG1-198 GEN
Solar/Wind Helper
0.229
241801AE1-079 GEN
Solar/Wind Helper
0.12
23917202WLORG-3
50/50
1.38
23917302WLORG-4
50/50
1.349
241996AE2-282_GEN
Solar/Wind Harmer
1.697
270007AE1-245 C
Solar/Wind Harmer
2.879
246938BC-WTG3
Solar/Wind Harmer
1.905
246937BC-WTG2
Solar/Wind Harmer
1.873
957891AF2-083 GEN
Solar/Wind Harmer
1.501
970611AG2-400 GEN
Solar/Wind Harmer
4.301
241985AE1-237 GEN
Solar/Wind Helper
0.119
962101AG1-054 GEN
Solar/Wind Helper
0.295
990527J1329
External Queue
1.3126888275146484
991177J1571 G
External Queue
11.149422645568848
990142J1224
External Queue
9.595755577087402
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.004
CPLELTFEXP_CPLE->PJM
CLTF
0.338
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.464
WECLTFEXP_WEC->PJM
CLTF
1.329
LAGNLTFEXP_LAGN->PJM
CLTF
4.111
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.563
LGEELTFEXP_LGEE->PJM
CLTF
1.688
MECLTFEXP_MEC->PJM
CLTF
5.219
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.576
NYPJM->LTFIMP_NY
CLTF
1.974
TVALTFEXP_TVA->PJM
CLTF
1.884
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-007A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-007A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.78 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.82
MW Contribution:2.66
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.378
241886AC2-103 GEN2
Solar/Wind Harmer
13.312
971549AH1-272 GEN
Solar/Wind Harmer
10.193
247607V1-011 GEN
Solar/Wind Harmer
1.912
270435AC2-044 GEN
Solar/Wind Harmer
0.954
971567AH1-282 GEN
Solar/Wind Harmer
6.891
241832AE2-181_GEN
Solar/Wind Harmer
1.549
270044AE2-322 C
Solar/Wind Harmer
0.698
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.531
270485AE1-090_GEN
Solar/Wind Harmer
0.263
23917402WLORG-5
50/50
1.431
241885AC2-103 GEN1
Solar/Wind Harmer
13.312
972253AH1-711 GEN
Adder
38.846
960841AF2-375 GEN
Solar/Wind Harmer
3.239
247522W1-056 GEN
Solar/Wind Harmer
1.38
970905AG2-564 GEN
Solar/Wind Harmer
2.663
246936BC-WTG1
Solar/Wind Harmer
1.867
270489AE1-102 GEN1
Solar/Wind Harmer
0.62
945111AF1-176 GEN
Solar/Wind Harmer
7.986
270505AE1-170 C O1
Solar/Wind Harmer
6.706
961971AG1-040 GEN
Solar/Wind Helper
0.395
254303AC2-168 GEN
Solar/Wind Helper
0.067
945641AF1-229 GEN
Solar/Wind Harmer
2.819
970159AG2-109 GEN
Solar/Wind Harmer
1.835
965051AG1-369 GEN
Solar/Wind Harmer
2.232
270317AD1-130_GEN
Solar/Wind Harmer
1.396
203846AF2-130 C
Solar/Wind Helper
0.27
241858AF1-205_GEN
Solar/Wind Harmer
4.354
241808AF1-120 C
Solar/Wind Harmer
0.952
972301AH1-735 GEN
Adder
5.278
270361_3
Solar/Wind Harmer
7.35
944231AF1-091 GEN
Solar/Wind Harmer
1.994
241847AF2-150_GEN
Solar/Wind Harmer
1.823
270063AE2-323 C
Solar/Wind Harmer
0.96
270462AD2-086
Solar/Wind Harmer
3.029
24189802OREGON_CT1
50/50
2.007
942801AE2-298 GEN
Solar/Wind Harmer
0.727
961051AF2-396 GEN
Solar/Wind Harmer
7.193
961051AF2-396 GEN
Solar/Wind Harmer
3.346
270216AD2-079_GEN
Solar/Wind Harmer
0.262
203947AF1-006 C
Solar/Wind Helper
0.455
241967AE2-285_GEN
Solar/Wind Helper
0.305
971989AH1-539 GEN
Solar/Wind Harmer
6.706
957201AF2-014 GEN
Solar/Wind Harmer
2.164
944161AF1-084 GEN
Solar/Wind Harmer
1.021
270302AB2-170 GEN
Solar/Wind Harmer
3.641
203804AE2-113_GEN
Solar/Wind Helper
0.928
241997AF1-093 GEN
Solar/Wind Helper
0.117
270541AE2-072 C
Solar/Wind Harmer
3.532
270404AC1-167 GEN
Solar/Wind Harmer
0.581
247604X1-042
Adder
0.202
958091AF2-103 GEN
Solar/Wind Harmer
0.078
270247TR4_N_V136
Solar/Wind Harmer
0.38
270377AD1-106 GEN
Solar/Wind Harmer
2.69
970031AG2-029 GEN
Solar/Wind Harmer
13.034
254305AE2-115 C
Solar/Wind Helper
0.101
972211AH1-690 GEN
50/50
212.091
970817AG2-515 GEN
Solar/Wind Harmer
11.575
945411AF1-206 GEN
Solar/Wind Harmer
6.379
24191202EL_AA1-006
Adder
0.223
270499AE1-146 GEN
Solar/Wind Harmer
2.029
270297AD1-101 GEN
Solar/Wind Harmer
1.573
966831AG1-554 GEN
Solar/Wind Harmer
0.62
965041AG1-368 GEN
Solar/Wind Harmer
4.486
241982AE2-343 S C
Solar/Wind Helper
0.106
254304AE2-114 C
Solar/Wind Helper
0.101
966311AG1-500 GEN
50/50
132.376
960981AF2-389 GEN
Solar/Wind Harmer
0.674
247620Y3-023
Adder
0.202
971231AH1-075 GEN
Solar/Wind Harmer
0.349
946381AF1-302 GEN
Solar/Wind Helper
0.109
238217AF1-153 C O1
Solar/Wind Helper
0.117
23917102WLORG-2
50/50
1.41
24189902OREGON_CT2
50/50
1.967
241807AE2-176_GEN
Solar/Wind Harmer
4.79
241840AF1-064_GEN
Solar/Wind Harmer
1.123
23906402RICHG1
Adder
1.056
23906502RICHG2&3
Adder
1.054
270428AC2-015 C
Solar/Wind Harmer
3.47
965421AG1-410 GEN
Solar/Wind Harmer
14.177
24695305TIMB G C
Solar/Wind Harmer
2.547
270449AD2-020 GEN
Solar/Wind Harmer
1.279
247521TR3_G114
Solar/Wind Harmer
1.503
270246TR4_N_V150
Solar/Wind Harmer
0.38
24639705ELKHART HY
Adder
0.067
203835AF1-098 GEN
Solar/Wind Helper
1.556
203860AG1-193 C
Solar/Wind Helper
0.17
241966AE1-183 GEN
Solar/Wind Helper
0.117
23906502RICHG2&3
Adder
1.054
270588AE1-091_GEN
Solar/Wind Harmer
5.847
247643Z2-116 C
Solar/Wind Harmer
0.03
203830AF1-094 GEN
Solar/Wind Helper
0.379
957071AF2-004 GEN
50/50
11.332
23929302BS-PKR
Adder
1.735
958321AF2-126 GEN
Solar/Wind Harmer
1.204
270575GUS2 35KV
Solar/Wind Harmer
8.659
970217AG2-149 GEN
Solar/Wind Harmer
19.363
270258AD1-119 GEN
Solar/Wind Harmer
1.423
270491AE1-102 GEN2
Solar/Wind Harmer
0.62
270191TR4_S_V150
Solar/Wind Harmer
1.341
961961AG1-039 GEN
Solar/Wind Harmer
1.258
24642205MAYFLWER
Adder
0.277
962511AG1-100 GEN
Solar/Wind Helper
0.406
959441AF2-235 GEN
Solar/Wind Helper
0.167
20334926Z1-069 C
Solar/Wind Helper
0.684
23920202STRYCT
Adder
1.423
970515AG2-329 GEN
Solar/Wind Harmer
8.781
943021AE2-325 GEN
Solar/Wind Harmer
1.662
203954AE2-126 C
Solar/Wind Helper
0.228
24190002OREGON_ST1
50/50
2.646
971677AH1-339 GEN
Solar/Wind Harmer
5.827
203980AG1-197 GEN
Solar/Wind Helper
0.294
203979AG1-198 GEN
Solar/Wind Helper
0.227
241801AE1-079 GEN
Solar/Wind Helper
0.119
23917202WLORG-3
50/50
1.455
23917302WLORG-4
50/50
1.423
241996AE2-282_GEN
Solar/Wind Harmer
1.708
270007AE1-245 C
Solar/Wind Harmer
2.868
246938BC-WTG3
Solar/Wind Harmer
1.899
246937BC-WTG2
Solar/Wind Harmer
1.867
957891AF2-083 GEN
Solar/Wind Harmer
1.504
241985AE1-237 GEN
Solar/Wind Helper
0.118
962101AG1-054 GEN
Solar/Wind Helper
0.293
990527J1329
External Queue
1.333598017692566
991177J1571 G
External Queue
11.313738822937012
990142J1224
External Queue
9.748601913452148
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.407
WECLTFEXP_WEC->PJM
CLTF
1.327
LAGNLTFEXP_LAGN->PJM
CLTF
4.085
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.394
LGEELTFEXP_LGEE->PJM
CLTF
1.675
MECLTFEXP_MEC->PJM
CLTF
5.205
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.887
NYPJM->LTFIMP_NY
CLTF
1.964
TVALTFEXP_TVA->PJM
CLTF
1.87
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
1.967
CPLELTFEXP_CPLE->PJM
CLTF
0.326
SIGELTFEXP_SIGE->PJM
CLTF
0.138

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-031_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-031_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:100.84 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1893.72
MW Contribution:3.04
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
8.998
241886AC2-103 GEN2
Solar/Wind Harmer
12.452
971549AH1-272 GEN
Solar/Wind Harmer
10.061
971567AH1-282 GEN
Solar/Wind Harmer
7.246
972211AH1-690 GEN
50/50
206.563
24191202EL_AA1-006
50/50
0.275
970817AG2-515 GEN
Solar/Wind Harmer
11.334
945411AF1-206 GEN
Solar/Wind Harmer
6.279
270499AE1-146 GEN
Solar/Wind Harmer
2.052
270297AD1-101 GEN
Solar/Wind Harmer
1.572
966831AG1-554 GEN
Solar/Wind Harmer
0.634
965041AG1-368 GEN
Solar/Wind Harmer
4.473
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
23906502RICHG2&3
Adder
1.042
270588AE1-091_GEN
Solar/Wind Harmer
5.936
203830AF1-094 GEN
Solar/Wind Helper
0.381
971989AH1-539 GEN
Solar/Wind Harmer
6.861
957201AF2-014 GEN
Solar/Wind Harmer
2.159
944161AF1-084 GEN
Solar/Wind Harmer
1.011
270302AB2-170 GEN
Solar/Wind Harmer
3.651
203804AE2-113_GEN
Solar/Wind Helper
0.931
241997AF1-093 GEN
Solar/Wind Helper
0.118
23857102WLORG-A
Adder
5.14
270541AE2-072 C
Solar/Wind Harmer
3.515
270404AC1-167 GEN
Solar/Wind Harmer
0.579
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.2
270377AD1-106 GEN
Solar/Wind Harmer
2.813
270247TR4_N_V136
Solar/Wind Harmer
0.379
970031AG2-029 GEN
Solar/Wind Harmer
12.948
254305AE2-115 C
Solar/Wind Helper
0.102
945641AF1-229 GEN
Solar/Wind Harmer
2.838
970159AG2-109 GEN
Solar/Wind Harmer
2.868
965051AG1-369 GEN
Solar/Wind Harmer
2.227
270317AD1-130_GEN
Solar/Wind Harmer
1.4
203846AF2-130 C
Solar/Wind Helper
0.271
23856402BAYSG1
50/50
1.035
241858AF1-205_GEN
Solar/Wind Harmer
4.286
241808AF1-120 C
Solar/Wind Harmer
0.937
966321AG1-501 GEN
Adder
1.036
972301AH1-735 GEN
Adder
5.214
270361_3
Solar/Wind Harmer
7.442
944231AF1-091 GEN
Solar/Wind Harmer
1.98
241847AF2-150_GEN
Solar/Wind Harmer
2.034
270462AD2-086
Solar/Wind Harmer
3.037
270063AE2-323 C
Solar/Wind Harmer
0.954
24189802OREGON_CT1
50/50
1.955
942801AE2-298 GEN
Solar/Wind Harmer
0.726
961051AF2-396 GEN
Solar/Wind Harmer
7.128
961051AF2-396 GEN
Solar/Wind Harmer
3.316
203947AF1-006 C
Solar/Wind Helper
0.458
241967AE2-285_GEN
Solar/Wind Helper
0.307
966311AG1-500 GEN
50/50
121.92
957071AF2-004 GEN
50/50
10.437
23929302BS-PKR
50/50
1.821
958321AF2-126 GEN
Solar/Wind Harmer
1.19
270575GUS2 35KV
Solar/Wind Harmer
8.767
970217AG2-149 GEN
Solar/Wind Harmer
19.989
270258AD1-119 GEN
Solar/Wind Harmer
1.418
961961AG1-039 GEN
Solar/Wind Harmer
1.403
270491AE1-102 GEN2
Solar/Wind Harmer
0.619
270191TR4_S_V150
Solar/Wind Harmer
1.338
24642205MAYFLWER
Adder
0.275
962511AG1-100 GEN
Solar/Wind Helper
0.408
959441AF2-235 GEN
Solar/Wind Helper
0.168
20334926Z1-069 C
Solar/Wind Helper
0.686
23920202STRYCT
Adder
1.402
970515AG2-329 GEN
Solar/Wind Harmer
9.065
943021AE2-325 GEN
Solar/Wind Harmer
1.647
203954AE2-126 C
Solar/Wind Helper
0.229
971231AH1-075 GEN
Solar/Wind Harmer
0.364
960981AF2-389 GEN
Solar/Wind Harmer
0.668
247620Y3-023
Adder
0.2
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.117
23917102WLORG-2
50/50
1.299
24189902OREGON_CT2
50/50
1.916
241807AE2-176_GEN
Solar/Wind Harmer
5.144
241840AF1-064_GEN
Solar/Wind Harmer
1.11
957111AF2-005 GEN
Adder
0.829
23906402RICHG1
Adder
1.043
23906502RICHG2&3
Adder
1.042
270428AC2-015 C
Solar/Wind Harmer
3.83
965421AG1-410 GEN
Solar/Wind Harmer
14.14
24695305TIMB G C
Solar/Wind Harmer
2.541
270449AD2-020 GEN
Solar/Wind Harmer
1.268
247521TR3_G114
Solar/Wind Harmer
1.5
270246TR4_N_V150
Solar/Wind Harmer
0.379
24639705ELKHART HY
Adder
0.066
203835AF1-098 GEN
Solar/Wind Helper
1.564
203860AG1-193 C
Solar/Wind Helper
0.171
241966AE1-183 GEN
Solar/Wind Helper
0.118
24190002OREGON_ST1
50/50
2.577
23857202WLORG-B
Adder
5.296
971677AH1-339 GEN
Solar/Wind Harmer
5.951
203980AG1-197 GEN
Solar/Wind Helper
0.295
203979AG1-198 GEN
Solar/Wind Helper
0.229
241801AE1-079 GEN
Solar/Wind Helper
0.119
23917402WLORG-5
50/50
1.318
241885AC2-103 GEN1
Solar/Wind Harmer
12.452
972253AH1-711 GEN
Adder
37.939
960841AF2-375 GEN
Solar/Wind Harmer
3.277
247522W1-056 GEN
Solar/Wind Harmer
1.411
241832AE2-181_GEN
Solar/Wind Harmer
1.524
270044AE2-322 C
Solar/Wind Harmer
0.695
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.509
270485AE1-090_GEN
Solar/Wind Harmer
0.264
247607V1-011 GEN
Solar/Wind Harmer
1.909
270435AC2-044 GEN
Solar/Wind Harmer
0.952
970905AG2-564 GEN
Solar/Wind Harmer
3.041
246936BC-WTG1
Solar/Wind Harmer
1.863
270489AE1-102 GEN1
Solar/Wind Harmer
0.619
945111AF1-176 GEN
Solar/Wind Harmer
7.917
270505AE1-170 C O1
Solar/Wind Harmer
6.647
961971AG1-040 GEN
Solar/Wind Helper
0.397
254303AC2-168 GEN
Solar/Wind Helper
0.068
23917202WLORG-3
50/50
1.34
23917302WLORG-4
50/50
1.311
241996AE2-282_GEN
Solar/Wind Harmer
1.681
270007AE1-245 C
Solar/Wind Harmer
2.864
246938BC-WTG3
Solar/Wind Harmer
1.895
246937BC-WTG2
Solar/Wind Harmer
1.863
957891AF2-083 GEN
Solar/Wind Harmer
1.491
241985AE1-237 GEN
Solar/Wind Helper
0.119
962101AG1-054 GEN
Solar/Wind Helper
0.294
990527J1329
External Queue
1.2952468395233154
991177J1571 G
External Queue
11.006390571594238
990142J1224
External Queue
9.468253135681152
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.428
LGEELTFEXP_LGEE->PJM
CLTF
1.683
MECLTFEXP_MEC->PJM
CLTF
5.19
AH1-155LTFEXP_AH1-155->PJM
LTF
0.127
CBM West 1LTFEXP_CBM-W1->PJM
CBM
71.973
NYPJM->LTFIMP_NY
CLTF
1.967
TVALTFEXP_TVA->PJM
CLTF
1.879
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.011
CPLELTFEXP_CPLE->PJM
CLTF
0.342
SIGELTFEXP_SIGE->PJM
CLTF
0.138
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.443
WECLTFEXP_WEC->PJM
CLTF
1.321
LAGNLTFEXP_LAGN->PJM
CLTF
4.096

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-002_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-002_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:174.17 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:3270.93
MW Contribution:4.28
Bus #Bus NameTypeMW Contribution
23856402BAYSG1
50/50
1.489
241858AF1-205_GEN
Solar/Wind Harmer
6.156
966321AG1-501 GEN
Adder
1.655
241808AF1-120 C
Solar/Wind Harmer
1.346
972301AH1-735 GEN
Adder
7.456
270361_3
Solar/Wind Harmer
10.624
944231AF1-091 GEN
Solar/Wind Harmer
2.791
241847AF2-150_GEN
Solar/Wind Harmer
2.847
270462AD2-086
Solar/Wind Harmer
4.24
270063AE2-323 C
Solar/Wind Harmer
1.334
241813AF1-122_GEN
Solar/Wind Harmer
3.682
270391AF1-285 GEN3
Solar/Wind Harmer
0.685
274754CRETE EC ;4U
Adder
2.532
958381AF2-132 GEN
Solar/Wind Harmer
4.687
274732ELWOOD EC;7P
Adder
8.208
274674JOLIET 9 ;6U
Adder
7.687
970245AG2-165 GEN
Solar/Wind Harmer
8.906
972235AH1-702 GEN1
Adder
1.208
20088826HIGHLAND
Solar/Wind Helper
0.435
971989AH1-539 GEN
Solar/Wind Harmer
9.641
957201AF2-014 GEN
Solar/Wind Harmer
3.029
944161AF1-084 GEN
Solar/Wind Harmer
1.419
270302AB2-170 GEN
Solar/Wind Harmer
5.097
963791AG1-232 GEN
Solar/Wind Harmer
7.497
970179AG2-119 GEN
Solar/Wind Harmer
4.411
270536AF1-215 GEN2
Solar/Wind Harmer
2.387
958391AF2-133 GEN
Solar/Wind Harmer
4.646
274811UNIV PK N;7U
Adder
2.564
274827FISK ;RP
Adder
3.924
270024AE2-089 GEN
Solar/Wind Harmer
2.366
23906502RICHG2&3
Adder
1.489
270588AE1-091_GEN
Solar/Wind Harmer
8.353
247643Z2-116 C
Solar/Wind Harmer
0.042
270535AF1-215 GEN1
Solar/Wind Harmer
2.387
972181SS23-001
Solar/Wind Harmer
3.073
276806AD2-047 C O1
Solar/Wind Harmer
5.394
274676JOLIET 29;8U
Adder
14.797
274734ELWOOD EC;8P
Adder
8.208
274736ELWOOD EC;9P
Adder
8.208
274682WAUKEGAN ;7U
Adder
8.816
203830AF1-094 GEN
Solar/Wind Helper
0.435
203818AF1-086 GEN
Solar/Wind Helper
0.912
235058AG1-386 C
Solar/Wind Helper
0.205
200917MEHOOPANY_G
Solar/Wind Helper
1.091
24190002OREGON_ST1
50/50
3.713
23857202WLORG-B
Adder
8.455
971677AH1-339 GEN
Solar/Wind Harmer
8.462
270227U2-072_GEN3
Solar/Wind Harmer
1.12
270228U2-072_GEN4
Solar/Wind Harmer
1.12
270231U2-072_GEN5
Solar/Wind Harmer
1.12
965681AG1-436 GEN
Solar/Wind Harmer
6.942
203980AG1-197 GEN
Solar/Wind Helper
0.336
203979AG1-198 GEN
Solar/Wind Helper
0.261
241801AE1-079 GEN
Solar/Wind Helper
0.162
203853AF1-134 C O1
Solar/Wind Helper
0.264
203952AE2-129 C
Solar/Wind Helper
0.257
20303426NA_O38_P22
Solar/Wind Helper
0.479
241832AE2-181_GEN
Solar/Wind Harmer
2.188
23917202WLORG-3
50/50
1.953
23917302WLORG-4
50/50
1.91
241996AE2-282_GEN
Solar/Wind Harmer
2.414
270007AE1-245 C
Solar/Wind Harmer
4.022
246938BC-WTG3
Solar/Wind Harmer
2.659
246937BC-WTG2
Solar/Wind Harmer
2.614
957891AF2-083 GEN
Solar/Wind Harmer
2.088
970611AG2-400 GEN
Solar/Wind Harmer
5.975
274808UNIV PK N;4U
Adder
2.553
942221AE2-234 GEN
Solar/Wind Harmer
0.373
274888KELLY CRK;1U
Solar/Wind Harmer
2.977
274770LINCOLN ;1U
Adder
3.125
274771LINCOLN ;2U
Adder
3.125
972259AH1-714 GEN
Adder
9.55
970321AG2-212 GEN
Solar/Wind Harmer
8.906
274696ROCKY RD ;4P
Adder
5.589
274697ROCKY RD ;3P
Adder
1.483
25326509SID D
Adder
0.633
241985AE1-237 GEN
Solar/Wind Helper
0.162
962101AG1-054 GEN
Solar/Wind Helper
0.402
203940AF1-140 C
Solar/Wind Helper
0.192
23917402WLORG-5
50/50
1.92
241885AC2-103 GEN1
Solar/Wind Harmer
18.089
972253AH1-711 GEN
Adder
54.605
960841AF2-375 GEN
Solar/Wind Harmer
4.677
247522W1-056 GEN
Solar/Wind Harmer
1.996
970905AG2-564 GEN
Solar/Wind Harmer
4.278
246936BC-WTG1
Solar/Wind Harmer
2.614
270489AE1-102 GEN1
Solar/Wind Harmer
0.868
945111AF1-176 GEN
Solar/Wind Harmer
11.092
270505AE1-170 C O1
Solar/Wind Harmer
9.313
965011AG1-365 GEN
Solar/Wind Harmer
5.975
274751CRETE EC ;1U
Adder
2.532
964861AG1-349 GEN
Solar/Wind Harmer
4.054
274723RIVER EC ;12
Adder
9.215
274801UNIV PARK;4U
Adder
2.944
940581AE2-045 GEN
Solar/Wind Harmer
5.147
971605AH1-302 GEN
Solar/Wind Harmer
4.401
274773LINCOLN ;4U
Adder
3.125
274774LINCOLN ;5U
Adder
3.125
274761LEE CO EC;2U
Adder
2.885
961971AG1-040 GEN
Solar/Wind Helper
0.451
254303AC2-168 GEN
Solar/Wind Helper
0.093
957071AF2-004 GEN
50/50
15.205
23929302BS-PKR
50/50
2.62
958321AF2-126 GEN
Solar/Wind Harmer
1.707
270575GUS2 35KV
Solar/Wind Harmer
12.516
970217AG2-149 GEN
Solar/Wind Harmer
28.273
270258AD1-119 GEN
Solar/Wind Harmer
1.996
961961AG1-039 GEN
Solar/Wind Harmer
1.964
972211AH1-690 GEN
50/50
297.552
24191202EL_AA1-006
Adder
0.36
970817AG2-515 GEN
Solar/Wind Harmer
16.3
945411AF1-206 GEN
Solar/Wind Harmer
9.015
270499AE1-146 GEN
Solar/Wind Harmer
2.926
270297AD1-101 GEN
Solar/Wind Harmer
2.22
966831AG1-554 GEN
Solar/Wind Harmer
0.892
965041AG1-368 GEN
Solar/Wind Harmer
6.263
270578AF1-285 GEN2
Solar/Wind Harmer
0.264
960681AF2-359 GEN
Solar/Wind Harmer
2.098
971219AH1-069 GEN
Solar/Wind Harmer
0.907
274814UNIV PK N;0U
Adder
2.586
274807UNIV PK N;3U
Adder
2.581
274805UNIV PK N;1U
Adder
2.569
274776LINCOLN ;7U
Adder
3.125
274687WILL CNTY;4U
Adder
14.004
274687WILL CNTY;4U
Adder
14.004
274731ELWOOD EC;2P
Adder
8.208
274733ELWOOD EC;3P
Adder
8.208
274746AC1-111 G10
Adder
2.761
241982AE2-343 S C
Solar/Wind Helper
0.145
254304AE2-114 C
Solar/Wind Helper
0.138
203961AE2-224 GEN
Solar/Wind Helper
1.164
23920202STRYCT
Adder
2.011
970515AG2-329 GEN
Solar/Wind Harmer
12.822
943021AE2-325 GEN
Solar/Wind Harmer
2.309
270223U2-072_GEN1
Solar/Wind Harmer
1.12
964391AG1-301 GEN
Solar/Wind Helper
0.226
23857102WLORG-A
Adder
8.207
270541AE2-072 C
Solar/Wind Harmer
5.011
270404AC1-167 GEN
Solar/Wind Harmer
0.816
958091AF2-103 GEN
Solar/Wind Harmer
0.109
247604X1-042
Adder
0.282
270377AD1-106 GEN
Solar/Wind Harmer
3.918
270247TR4_N_V136
Solar/Wind Harmer
0.531
970031AG2-029 GEN
Solar/Wind Harmer
18.113
942871AE2-306 GEN
Solar/Wind Harmer
0.514
270391AF1-285 GEN3
Solar/Wind Harmer
0.264
970349AG2-230 GEN
Solar/Wind Harmer
8.3
972231SS25-0005
Solar/Wind Harmer
4.917
274752CRETE EC ;2U
Adder
2.532
959141AF2-205 GEN
Solar/Wind Harmer
3.076
274826FISK ;BP
Adder
5.536
276772AC2-154 GEN
Solar/Wind Harmer
1.406
972228AH1-698 GEN2
Adder
1.862
939351AE1-166 GEN
Solar/Wind Harmer
2.963
970707AG2-453 GEN
Solar/Wind Harmer
13.981
274730ELWOOD EC;6P
Adder
8.208
970513AG2-328 GEN
Solar/Wind Harmer
8.906
970517AG2-330 GEN
Solar/Wind Harmer
8.078
254305AE2-115 C
Solar/Wind Helper
0.138
238202AE2-262_GEN
Solar/Wind Helper
0.528
941421AE2-139 GEN
Solar/Wind Helper
1.203
23917102WLORG-2
50/50
1.892
24189902OREGON_CT2
50/50
2.76
241807AE2-176_GEN
Solar/Wind Harmer
7.368
957111AF2-005 GEN
Adder
1.324
241840AF1-064_GEN
Solar/Wind Harmer
1.592
23906402RICHG1
Adder
1.491
23906502RICHG2&3
Adder
1.489
270428AC2-015 C
Solar/Wind Harmer
5.418
965421AG1-410 GEN
Solar/Wind Harmer
19.836
24695305TIMB G C
Solar/Wind Harmer
3.562
270449AD2-020 GEN
Solar/Wind Harmer
1.777
247521TR3_G114
Solar/Wind Harmer
2.099
270246TR4_N_V150
Solar/Wind Harmer
0.531
24639705ELKHART HY
Adder
0.093
971221AH1-070 GEN
Solar/Wind Harmer
0.907
270055AF2-134 C O1
Solar/Wind Harmer
1.591
274812UNIV PK N;8U
Adder
2.564
276164X3-005 C
Solar/Wind Harmer
0.358
276776AD2-060 GEN
Solar/Wind Harmer
0.213
972207SS24-0001
Solar/Wind Harmer
11.112
274676JOLIET 29;8U
Adder
15.345
274745AC1-111 GEN9
Adder
2.761
274682WAUKEGAN ;7U
Adder
8.816
274828WAUKEGAN ;BP
Adder
5.414
203835AF1-098 GEN
Solar/Wind Helper
1.778
203860AG1-193 C
Solar/Wind Helper
0.199
241966AE1-183 GEN
Solar/Wind Helper
0.16
959471AF2-238 GEN
Solar/Wind Helper
0.26
238206AE2-263_GEN
Solar/Wind Helper
0.502
964201AG1-281 GEN
Solar/Wind Helper
0.234
270578AF1-285 GEN2
Solar/Wind Harmer
0.685
970373AG2-245 GEN
Solar/Wind Harmer
11.24
971917AH1-482 GEN
Solar/Wind Harmer
4.678
941551AE2-152 GEN
Solar/Wind Harmer
2.266
274822ROCKFORD ;11
Adder
9.424
203954AE2-126 C
Solar/Wind Helper
0.282
20094526CT_V3-030
Solar/Wind Helper
0.243
270491AE1-102 GEN2
Solar/Wind Harmer
0.868
270191TR4_S_V150
Solar/Wind Harmer
1.873
24642205MAYFLWER
Adder
0.384
959331AF2-224 GEN
Solar/Wind Harmer
5.975
274753CRETE EC ;3U
Adder
2.532
964401AG1-302 GEN
Solar/Wind Harmer
4.687
972038AH1-567 GEN2
Adder
0.184
971617AH1-308 GEN
Solar/Wind Harmer
2.93
972236AH1-702 GEN2
Adder
1.051
274760LEE CO EC;1U
Adder
4.416
962511AG1-100 GEN
Solar/Wind Helper
0.462
959441AF2-235 GEN
Solar/Wind Helper
0.196
20334926Z1-069 C
Solar/Wind Helper
0.837
203854AF2-039 C
Solar/Wind Helper
0.18
972227AH1-698 GEN1
Adder
1.311
274735ELWOOD EC;4P
Adder
8.208
274744AC1-111 GEN8
Adder
2.761
241997AF1-093 GEN
Solar/Wind Helper
0.16
203804AE2-113_GEN
Solar/Wind Helper
1.128
20090526Q36
Solar/Wind Helper
0.548
203993AD2-133_GEN1
Solar/Wind Helper
0.548
20091526CHSTN_FL
Solar/Wind Helper
0.29
23867002DVBSG1
50/50
13.011
241886AC2-103 GEN2
Solar/Wind Harmer
18.089
971549AH1-272 GEN
Solar/Wind Harmer
14.209
247607V1-011 GEN
Solar/Wind Harmer
2.681
971567AH1-282 GEN
Solar/Wind Harmer
10.136
270435AC2-044 GEN
Solar/Wind Harmer
1.336
971771AH1-392 GEN
Solar/Wind Harmer
5.317
971769AH1-391 GEN
Solar/Wind Harmer
5.763
270071AF1-092 GEN
Solar/Wind Harmer
7.858
274728ELWOOD EC;5P
Adder
8.208
24729505KEY G4
Adder
3.179
941231AE2-117 GEN
Solar/Wind Helper
0.227
270044AE2-322 C
Solar/Wind Harmer
0.979
24441205WTRV SLR C
Solar/Wind Harmer
0.089
945111AF1-176 GEN
Solar/Wind Harmer
3.515
270485AE1-090_GEN
Solar/Wind Harmer
0.369
965021AG1-366 GEN
Solar/Wind Harmer
1.39
970065AG2-057 GEN
Solar/Wind Harmer
0.575
270043AE2-236 GEN
Solar/Wind Harmer
3.089
274724RIVER EC ;11
Adder
9.105
274802UNIV PARK;5U
Adder
2.953
274800UNIV PARK;3U
Adder
2.944
970941AG2-585 GEN
Solar/Wind Harmer
6.303
274772LINCOLN ;3U
Adder
3.125
276897AD1-100 C
Solar/Wind Harmer
14.503
276893AG1-478 C
Solar/Wind Harmer
0.209
274729ELWOOD EC;1P
Adder
8.208
945641AF1-229 GEN
Solar/Wind Harmer
4.044
970159AG2-109 GEN
Solar/Wind Harmer
3.924
965051AG1-369 GEN
Solar/Wind Harmer
3.117
270317AD1-130_GEN
Solar/Wind Harmer
1.954
971347AH1-153 GEN
Solar/Wind Harmer
8.3
972037AH1-567 GEN1
Adder
0.093
960591AF2-350 GEN
Solar/Wind Harmer
5.042
274775LINCOLN ;6U
Adder
3.125
274777LINCOLN ;8U
Adder
3.125
274675JOLIET 29;7U
Adder
15.345
274675JOLIET 29;7U
Adder
14.797
274823ROCKFORD ;21
Adder
9.356
203846AF2-130 C
Solar/Wind Helper
0.325
203855AF2-088 C
Solar/Wind Helper
0.087
20092526R32
Solar/Wind Helper
0.563
970833AG2-524 GEN
Solar/Wind Harmer
1.943
970833AG2-524 GEN
Solar/Wind Harmer
0.904
24189802OREGON_CT1
50/50
2.816
942801AE2-298 GEN
Solar/Wind Harmer
1.019
961051AF2-396 GEN
Solar/Wind Harmer
9.992
961051AF2-396 GEN
Solar/Wind Harmer
4.648
270216AD2-079_GEN
Solar/Wind Harmer
0.363
971201AH1-060 GEN
Solar/Wind Harmer
1.151
270224U2-072_GEN2
Solar/Wind Harmer
1.12
274803UNIV PARK;6U
Adder
2.953
274887GEN-1.85
Solar/Wind Harmer
2.688
274674JOLIET 9 ;6U
Adder
7.687
274693ROCKY RD ;1P
Adder
5.407
274683WAUKEGAN ;8U
Adder
10.328
274683WAUKEGAN ;8U
Adder
8.706
274764LEE CO EC;5U
Adder
4.426
203947AF1-006 C
Solar/Wind Helper
0.516
241967AE2-285_GEN
Solar/Wind Helper
0.417
20398826ARMNA MT
Solar/Wind Helper
0.849
946071AF1-272 GEN
Solar/Wind Helper
1.356
20084626FORWARD
Solar/Wind Helper
0.17
20083426SW_E13_K22
Solar/Wind Helper
0.025
966311AG1-500 GEN
50/50
177.624
971231AH1-075 GEN
Solar/Wind Harmer
0.508
960981AF2-389 GEN
Solar/Wind Harmer
0.936
247620Y3-023
Adder
0.281
270526AF1-158 GEN
Solar/Wind Harmer
2.631
24441505OLIV SLR
Solar/Wind Harmer
0.077
965791AG1-447 GEN
Solar/Wind Harmer
3.552
241960AC2-195 GEN
Solar/Wind Harmer
1.533
276843GEN-1.7
Solar/Wind Harmer
0.289
958011AF2-095 GEN
Solar/Wind Harmer
7.261
274695ROCKY RD ;2P
Adder
5.46
274765LEE CO EC;6U
Adder
4.426
946381AF1-302 GEN
Solar/Wind Helper
0.136
238217AF1-153 C O1
Solar/Wind Helper
0.144
203946AE2-131 C
Solar/Wind Helper
0.258
20088626ARWF_N39
Solar/Wind Helper
0.584
20088926STNY CRK
Solar/Wind Helper
0.38
990527J1329
External Queue
1.891624927520752
991177J1571 G
External Queue
16.072763442993164
991182J1586 G
External Queue
25.886547088623047
990142J1224
External Queue
13.827776908874512
CBM West 2LTFEXP_CBM-W2->PJM
CBM
44.143
LGEELTFEXP_LGEE->PJM
CLTF
2.281
MECLTFEXP_MEC->PJM
CLTF
7.157
AH1-155LTFEXP_AH1-155->PJM
LTF
0.177
CBM West 1LTFEXP_CBM-W1->PJM
CBM
101.376
NYPJM->LTFIMP_NY
CLTF
2.552
TVALTFEXP_TVA->PJM
CLTF
2.517
AG2-052LTFEXP_AG2-052->PJM
LTF
0.118
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.427
CPLELTFEXP_CPLE->PJM
CLTF
0.342
SIGELTFEXP_SIGE->PJM
CLTF
0.189
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.995
WECLTFEXP_WEC->PJM
CLTF
1.831
LAGNLTFEXP_LAGN->PJM
CLTF
5.524

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-003_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-003_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.76 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1967.48
MW Contribution:2.97
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.2
241886AC2-103 GEN2
Solar/Wind Harmer
12.828
971549AH1-272 GEN
Solar/Wind Harmer
10.203
247607V1-011 GEN
Solar/Wind Harmer
1.93
971567AH1-282 GEN
Solar/Wind Harmer
7.229
270435AC2-044 GEN
Solar/Wind Harmer
0.963
241832AE2-181_GEN
Solar/Wind Harmer
1.547
270044AE2-322 C
Solar/Wind Harmer
0.703
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.541
270485AE1-090_GEN
Solar/Wind Harmer
0.267
965021AG1-366 GEN
Solar/Wind Harmer
1.006
23917402WLORG-5
50/50
1.364
241885AC2-103 GEN1
Solar/Wind Harmer
12.828
972253AH1-711 GEN
Adder
38.596
960841AF2-375 GEN
Solar/Wind Harmer
3.301
247522W1-056 GEN
Solar/Wind Harmer
1.418
970905AG2-564 GEN
Solar/Wind Harmer
2.97
945641AF1-229 GEN
Solar/Wind Harmer
2.863
970159AG2-109 GEN
Solar/Wind Harmer
2.569
965051AG1-369 GEN
Solar/Wind Harmer
2.252
270317AD1-130_GEN
Solar/Wind Harmer
1.413
203846AF2-130 C
Solar/Wind Helper
0.273
23856402BAYSG1
50/50
1.049
241858AF1-205_GEN
Solar/Wind Harmer
4.35
241808AF1-120 C
Solar/Wind Harmer
0.951
972301AH1-735 GEN
Adder
5.287
270361_3
Solar/Wind Harmer
7.495
966321AG1-501 GEN
Adder
0.871
944231AF1-091 GEN
Solar/Wind Harmer
2.004
241847AF2-150_GEN
Solar/Wind Harmer
2
270462AD2-086
Solar/Wind Harmer
3.066
270063AE2-323 C
Solar/Wind Harmer
0.965
971989AH1-539 GEN
Solar/Wind Harmer
6.89
957201AF2-014 GEN
Solar/Wind Harmer
2.183
944161AF1-084 GEN
Solar/Wind Harmer
1.025
270302AB2-170 GEN
Solar/Wind Harmer
3.686
203804AE2-113_GEN
Solar/Wind Helper
0.939
241997AF1-093 GEN
Solar/Wind Helper
0.119
24189802OREGON_CT1
50/50
1.991
942801AE2-298 GEN
Solar/Wind Harmer
0.734
961051AF2-396 GEN
Solar/Wind Harmer
7.22
961051AF2-396 GEN
Solar/Wind Harmer
3.358
270216AD2-079_GEN
Solar/Wind Harmer
0.263
23857102WLORG-A
Adder
4.322
270541AE2-072 C
Solar/Wind Harmer
3.557
270404AC1-167 GEN
Solar/Wind Harmer
0.585
958091AF2-103 GEN
Solar/Wind Harmer
0.079
247604X1-042
Adder
0.203
270377AD1-106 GEN
Solar/Wind Harmer
2.809
270247TR4_N_V136
Solar/Wind Harmer
0.384
970031AG2-029 GEN
Solar/Wind Harmer
13.106
254305AE2-115 C
Solar/Wind Helper
0.103
972211AH1-690 GEN
50/50
210.311
970817AG2-515 GEN
Solar/Wind Harmer
11.522
24191202EL_AA1-006
Adder
0.249
945411AF1-206 GEN
Solar/Wind Harmer
6.374
270499AE1-146 GEN
Solar/Wind Harmer
2.067
270297AD1-101 GEN
Solar/Wind Harmer
1.589
966831AG1-554 GEN
Solar/Wind Harmer
0.637
965041AG1-368 GEN
Solar/Wind Harmer
4.523
241982AE2-343 S C
Solar/Wind Helper
0.108
254304AE2-114 C
Solar/Wind Helper
0.103
966311AG1-500 GEN
50/50
126.182
971231AH1-075 GEN
Solar/Wind Harmer
0.364
960981AF2-389 GEN
Solar/Wind Harmer
0.677
247620Y3-023
Adder
0.203
946381AF1-302 GEN
Solar/Wind Helper
0.111
238217AF1-153 C O1
Solar/Wind Helper
0.118
23917102WLORG-2
50/50
1.344
24189902OREGON_CT2
50/50
1.95
23906502RICHG2&3
Adder
1.056
270588AE1-091_GEN
Solar/Wind Harmer
5.974
247643Z2-116 C
Solar/Wind Harmer
0.03
203830AF1-094 GEN
Solar/Wind Helper
0.384
203947AF1-006 C
Solar/Wind Helper
0.461
241967AE2-285_GEN
Solar/Wind Helper
0.309
957071AF2-004 GEN
50/50
10.802
23929302BS-PKR
50/50
1.846
958321AF2-126 GEN
Solar/Wind Harmer
1.207
270575GUS2 35KV
Solar/Wind Harmer
8.83
970217AG2-149 GEN
Solar/Wind Harmer
20.039
270258AD1-119 GEN
Solar/Wind Harmer
1.434
961961AG1-039 GEN
Solar/Wind Harmer
1.38
270491AE1-102 GEN2
Solar/Wind Harmer
0.626
270191TR4_S_V150
Solar/Wind Harmer
1.353
24642205MAYFLWER
Adder
0.278
959331AF2-224 GEN
Solar/Wind Harmer
4.324
962511AG1-100 GEN
Solar/Wind Helper
0.411
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.692
23920202STRYCT
Adder
1.423
970515AG2-329 GEN
Solar/Wind Harmer
9.087
943021AE2-325 GEN
Solar/Wind Harmer
1.668
203954AE2-126 C
Solar/Wind Helper
0.231
241807AE2-176_GEN
Solar/Wind Harmer
5.09
241840AF1-064_GEN
Solar/Wind Harmer
1.126
23906402RICHG1
Adder
1.057
23906502RICHG2&3
Adder
1.056
957111AF2-005 GEN
Adder
0.697
270428AC2-015 C
Solar/Wind Harmer
3.771
965421AG1-410 GEN
Solar/Wind Harmer
14.298
24695305TIMB G C
Solar/Wind Harmer
2.569
270449AD2-020 GEN
Solar/Wind Harmer
1.284
247521TR3_G114
Solar/Wind Harmer
1.516
270246TR4_N_V150
Solar/Wind Harmer
0.384
24639705ELKHART HY
Adder
0.067
203835AF1-098 GEN
Solar/Wind Helper
1.575
203860AG1-193 C
Solar/Wind Helper
0.173
241966AE1-183 GEN
Solar/Wind Helper
0.119
24190002OREGON_ST1
50/50
2.624
23857202WLORG-B
Adder
4.453
971677AH1-339 GEN
Solar/Wind Harmer
5.98
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241801AE1-079 GEN
Solar/Wind Helper
0.12
246936BC-WTG1
Solar/Wind Harmer
1.883
270489AE1-102 GEN1
Solar/Wind Harmer
0.626
945111AF1-176 GEN
Solar/Wind Harmer
8.018
270505AE1-170 C O1
Solar/Wind Harmer
6.733
965011AG1-365 GEN
Solar/Wind Harmer
4.324
961971AG1-040 GEN
Solar/Wind Helper
0.4
254303AC2-168 GEN
Solar/Wind Helper
0.068
23917202WLORG-3
50/50
1.387
23917302WLORG-4
50/50
1.357
241996AE2-282_GEN
Solar/Wind Harmer
1.706
270007AE1-245 C
Solar/Wind Harmer
2.895
246938BC-WTG3
Solar/Wind Harmer
1.916
246937BC-WTG2
Solar/Wind Harmer
1.883
957891AF2-083 GEN
Solar/Wind Harmer
1.51
970611AG2-400 GEN
Solar/Wind Harmer
4.324
241985AE1-237 GEN
Solar/Wind Helper
0.12
962101AG1-054 GEN
Solar/Wind Helper
0.297
990527J1329
External Queue
1.3199658393859863
991177J1571 G
External Queue
11.211230278015137
990142J1224
External Queue
9.648950576782227
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.978
NYPJM->LTFIMP_NY
CLTF
1.985
TVALTFEXP_TVA->PJM
CLTF
1.895
AG2-052LTFEXP_AG2-052->PJM
LTF
0.086
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.016
CPLELTFEXP_CPLE->PJM
CLTF
0.34
SIGELTFEXP_SIGE->PJM
CLTF
0.14
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.506
WECLTFEXP_WEC->PJM
CLTF
1.336
LAGNLTFEXP_LAGN->PJM
CLTF
4.134
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.744
LGEELTFEXP_LGEE->PJM
CLTF
1.697
MECLTFEXP_MEC->PJM
CLTF
5.248
AH1-155LTFEXP_AH1-155->PJM
LTF
0.129

Details for 02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line l/o ATSI_P2-3_OEC-345-028_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line
Contingency Name:
ATSI_P2-3_OEC-345-028_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:101.37 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:1903.65
MW Contribution:3.06
Bus #Bus NameTypeMW Contribution
23867002DVBSG1
50/50
9.044
241886AC2-103 GEN2
Solar/Wind Harmer
12.516
971549AH1-272 GEN
Solar/Wind Harmer
10.113
971567AH1-282 GEN
Solar/Wind Harmer
7.283
247607V1-011 GEN
Solar/Wind Harmer
1.919
270435AC2-044 GEN
Solar/Wind Harmer
0.957
945641AF1-229 GEN
Solar/Wind Harmer
2.852
971989AH1-539 GEN
Solar/Wind Harmer
6.896
23857102WLORG-A
Adder
5.166
270541AE2-072 C
Solar/Wind Harmer
3.533
972211AH1-690 GEN
50/50
207.621
24191202EL_AA1-006
50/50
0.277
970817AG2-515 GEN
Solar/Wind Harmer
11.392
945411AF1-206 GEN
Solar/Wind Harmer
6.311
270499AE1-146 GEN
Solar/Wind Harmer
2.062
270297AD1-101 GEN
Solar/Wind Harmer
1.58
966831AG1-554 GEN
Solar/Wind Harmer
0.638
965041AG1-368 GEN
Solar/Wind Harmer
4.496
241982AE2-343 S C
Solar/Wind Helper
0.107
254304AE2-114 C
Solar/Wind Helper
0.102
966311AG1-500 GEN
50/50
122.544
971231AH1-075 GEN
Solar/Wind Harmer
0.366
960981AF2-389 GEN
Solar/Wind Harmer
0.672
23906502RICHG2&3
Adder
1.047
270588AE1-091_GEN
Solar/Wind Harmer
5.966
247643Z2-116 C
Solar/Wind Harmer
0.03
203830AF1-094 GEN
Solar/Wind Helper
0.383
957201AF2-014 GEN
Solar/Wind Harmer
2.17
944161AF1-084 GEN
Solar/Wind Harmer
1.017
270302AB2-170 GEN
Solar/Wind Harmer
3.67
203804AE2-113_GEN
Solar/Wind Helper
0.936
241997AF1-093 GEN
Solar/Wind Helper
0.118
270404AC1-167 GEN
Solar/Wind Harmer
0.582
958091AF2-103 GEN
Solar/Wind Harmer
0.078
247604X1-042
Adder
0.201
270377AD1-106 GEN
Solar/Wind Harmer
2.828
270247TR4_N_V136
Solar/Wind Harmer
0.381
970031AG2-029 GEN
Solar/Wind Harmer
13.014
254305AE2-115 C
Solar/Wind Helper
0.102
970159AG2-109 GEN
Solar/Wind Harmer
2.883
965051AG1-369 GEN
Solar/Wind Harmer
2.238
270317AD1-130_GEN
Solar/Wind Harmer
1.407
203846AF2-130 C
Solar/Wind Helper
0.273
23856402BAYSG1
50/50
1.04
241858AF1-205_GEN
Solar/Wind Harmer
4.307
241808AF1-120 C
Solar/Wind Harmer
0.942
966321AG1-501 GEN
Adder
1.042
972301AH1-735 GEN
Adder
5.24
270361_3
Solar/Wind Harmer
7.48
944231AF1-091 GEN
Solar/Wind Harmer
1.99
241847AF2-150_GEN
Solar/Wind Harmer
2.044
270462AD2-086
Solar/Wind Harmer
3.053
270063AE2-323 C
Solar/Wind Harmer
0.958
24189802OREGON_CT1
50/50
1.965
942801AE2-298 GEN
Solar/Wind Harmer
0.729
961051AF2-396 GEN
Solar/Wind Harmer
7.165
961051AF2-396 GEN
Solar/Wind Harmer
3.333
270216AD2-079_GEN
Solar/Wind Harmer
0.261
203947AF1-006 C
Solar/Wind Helper
0.46
241967AE2-285_GEN
Solar/Wind Helper
0.308
247620Y3-023
Adder
0.202
946381AF1-302 GEN
Solar/Wind Helper
0.11
238217AF1-153 C O1
Solar/Wind Helper
0.118
957071AF2-004 GEN
50/50
10.49
23929302BS-PKR
50/50
1.83
958321AF2-126 GEN
Solar/Wind Harmer
1.196
270575GUS2 35KV
Solar/Wind Harmer
8.812
970217AG2-149 GEN
Solar/Wind Harmer
20.092
270258AD1-119 GEN
Solar/Wind Harmer
1.425
961961AG1-039 GEN
Solar/Wind Harmer
1.41
270491AE1-102 GEN2
Solar/Wind Harmer
0.622
270191TR4_S_V150
Solar/Wind Harmer
1.345
24642205MAYFLWER
Adder
0.276
962511AG1-100 GEN
Solar/Wind Helper
0.41
959441AF2-235 GEN
Solar/Wind Helper
0.169
20334926Z1-069 C
Solar/Wind Helper
0.69
23920202STRYCT
Adder
1.409
970515AG2-329 GEN
Solar/Wind Harmer
9.111
943021AE2-325 GEN
Solar/Wind Harmer
1.655
203954AE2-126 C
Solar/Wind Helper
0.231
23917102WLORG-2
50/50
1.305
24189902OREGON_CT2
50/50
1.926
241807AE2-176_GEN
Solar/Wind Harmer
5.17
241840AF1-064_GEN
Solar/Wind Harmer
1.116
957111AF2-005 GEN
Adder
0.833
23906402RICHG1
Adder
1.048
23906502RICHG2&3
Adder
1.047
270428AC2-015 C
Solar/Wind Harmer
3.85
965421AG1-410 GEN
Solar/Wind Harmer
14.212
24695305TIMB G C
Solar/Wind Harmer
2.554
270449AD2-020 GEN
Solar/Wind Harmer
1.274
247521TR3_G114
Solar/Wind Harmer
1.507
270246TR4_N_V150
Solar/Wind Harmer
0.381
24639705ELKHART HY
Adder
0.067
203835AF1-098 GEN
Solar/Wind Helper
1.572
203860AG1-193 C
Solar/Wind Helper
0.172
241966AE1-183 GEN
Solar/Wind Helper
0.118
24190002OREGON_ST1
50/50
2.591
23857202WLORG-B
Adder
5.323
971677AH1-339 GEN
Solar/Wind Harmer
5.982
203980AG1-197 GEN
Solar/Wind Helper
0.297
203979AG1-198 GEN
Solar/Wind Helper
0.23
241801AE1-079 GEN
Solar/Wind Helper
0.12
23917402WLORG-5
50/50
1.325
241885AC2-103 GEN1
Solar/Wind Harmer
12.516
972253AH1-711 GEN
Adder
38.133
960841AF2-375 GEN
Solar/Wind Harmer
3.294
247522W1-056 GEN
Solar/Wind Harmer
1.419
970905AG2-564 GEN
Solar/Wind Harmer
3.056
246936BC-WTG1
Solar/Wind Harmer
1.872
270489AE1-102 GEN1
Solar/Wind Harmer
0.622
945111AF1-176 GEN
Solar/Wind Harmer
7.958
270505AE1-170 C O1
Solar/Wind Harmer
6.681
961971AG1-040 GEN
Solar/Wind Helper
0.399
254303AC2-168 GEN
Solar/Wind Helper
0.068
241832AE2-181_GEN
Solar/Wind Harmer
1.532
270044AE2-322 C
Solar/Wind Harmer
0.698
24441205WTRV SLR C
Solar/Wind Harmer
0.064
945111AF1-176 GEN
Solar/Wind Harmer
2.522
270485AE1-090_GEN
Solar/Wind Harmer
0.265
23917202WLORG-3
50/50
1.347
23917302WLORG-4
50/50
1.318
241996AE2-282_GEN
Solar/Wind Harmer
1.69
270007AE1-245 C
Solar/Wind Harmer
2.879
246938BC-WTG3
Solar/Wind Harmer
1.904
246937BC-WTG2
Solar/Wind Harmer
1.872
957891AF2-083 GEN
Solar/Wind Harmer
1.498
241985AE1-237 GEN
Solar/Wind Helper
0.12
962101AG1-054 GEN
Solar/Wind Helper
0.296
990527J1329
External Queue
1.3018794059753418
991177J1571 G
External Queue
11.062751770019531
990142J1224
External Queue
9.516737937927246
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.021
CPLELTFEXP_CPLE->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.139
CBM South 1LTFEXP_CBM-S1->PJM
CBM
7.481
WECLTFEXP_WEC->PJM
CLTF
1.328
LAGNLTFEXP_LAGN->PJM
CLTF
4.117
CBM West 2LTFEXP_CBM-W2->PJM
CBM
32.594
LGEELTFEXP_LGEE->PJM
CLTF
1.691
MECLTFEXP_MEC->PJM
CLTF
5.217
AH1-155LTFEXP_AH1-155->PJM
LTF
0.128
CBM West 1LTFEXP_CBM-W1->PJM
CBM
72.342
NYPJM->LTFIMP_NY
CLTF
1.977
TVALTFEXP_TVA->PJM
CLTF
1.889
AG2-052LTFEXP_AG2-052->PJM
LTF
0.085

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:151.55 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2494.57
MW Contribution:2.19
Bus #Bus NameTypeMW Contribution
24190002OREGON_ST1
50/50
3.497
971677AH1-339 GEN
Solar/Wind Harmer
6.682
965681AG1-436 GEN
Solar/Wind Harmer
6.166
270227U2-072_GEN3
Solar/Wind Harmer
0.958
270228U2-072_GEN4
Solar/Wind Harmer
0.958
270231U2-072_GEN5
Solar/Wind Harmer
0.958
274847GR RIDGE ;BU
Solar/Wind Harmer
2.221
241996AE2-282_GEN
Solar/Wind Harmer
2.162
270007AE1-245 C
Solar/Wind Harmer
3.485
246938BC-WTG3
Solar/Wind Harmer
2.318
246937BC-WTG2
Solar/Wind Harmer
2.279
957891AF2-083 GEN
Solar/Wind Harmer
1.863
970611AG2-400 GEN
Solar/Wind Harmer
5.243
274808UNIV PK N;4U
Adder
2.26
274888KELLY CRK;1U
Solar/Wind Harmer
2.634
274770LINCOLN ;1U
Adder
2.764
274771LINCOLN ;2U
Adder
2.764
942221AE2-234 GEN
Solar/Wind Harmer
0.326
972259AH1-714 GEN
Adder
8.447
970321AG2-212 GEN
Solar/Wind Harmer
7.863
274696ROCKY RD ;4P
Adder
4.941
274697ROCKY RD ;3P
Adder
1.311
241985AE1-237 GEN
Solar/Wind Helper
0.13
962101AG1-054 GEN
Solar/Wind Helper
0.324
972211AH1-690 GEN
50/50
280.319
970817AG2-515 GEN
Solar/Wind Harmer
14.976
945411AF1-206 GEN
Solar/Wind Harmer
8.075
270499AE1-146 GEN
Solar/Wind Harmer
2.365
270297AD1-101 GEN
Solar/Wind Harmer
1.906
966831AG1-554 GEN
Solar/Wind Harmer
0.708
965041AG1-368 GEN
Solar/Wind Harmer
5.468
960681AF2-359 GEN
Solar/Wind Harmer
1.863
270578AF1-285 GEN2
Solar/Wind Harmer
0.225
274814UNIV PK N;0U
Adder
2.289
274807UNIV PK N;3U
Adder
2.285
274805UNIV PK N;1U
Adder
2.275
274776LINCOLN ;7U
Adder
2.764
274687WILL CNTY;4U
Adder
12.387
274687WILL CNTY;4U
Adder
12.387
274731ELWOOD EC;2P
Adder
7.259
274733ELWOOD EC;3P
Adder
7.259
274746AC1-111 G10
Adder
2.441
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.111
270541AE2-072 C
Solar/Wind Harmer
4.33
270404AC1-167 GEN
Solar/Wind Harmer
0.711
247604X1-042
Adder
0.253
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270247TR4_N_V136
Solar/Wind Harmer
0.463
970031AG2-029 GEN
Solar/Wind Harmer
16.05
970349AG2-230 GEN
Solar/Wind Harmer
7.365
942871AE2-306 GEN
Solar/Wind Harmer
0.439
270391AF1-285 GEN3
Solar/Wind Harmer
0.225
270377AD1-106 GEN
Solar/Wind Harmer
2.883
972231SS25-0005
Solar/Wind Harmer
4.354
274752CRETE EC ;2U
Adder
2.243
959141AF2-205 GEN
Solar/Wind Harmer
2.72
274826FISK ;BP
Adder
4.899
276772AC2-154 GEN
Solar/Wind Harmer
1.244
972228AH1-698 GEN2
Adder
1.647
939351AE1-166 GEN
Solar/Wind Harmer
2.621
274730ELWOOD EC;6P
Adder
7.259
970707AG2-453 GEN
Solar/Wind Harmer
12.364
970513AG2-328 GEN
Solar/Wind Harmer
7.863
970517AG2-330 GEN
Solar/Wind Harmer
7.132
254305AE2-115 C
Solar/Wind Helper
0.111
276694AA1-018 GEN2
Solar/Wind Harmer
0.632
203980AG1-197 GEN
Solar/Wind Helper
0.247
203979AG1-198 GEN
Solar/Wind Helper
0.193
241801AE1-079 GEN
Solar/Wind Helper
0.131
24189902OREGON_CT2
50/50
2.599
241840AF1-064_GEN
Solar/Wind Harmer
1.394
23906402RICHG1
Adder
1.323
23906502RICHG2&3
Adder
1.32
241807AE2-176_GEN
Solar/Wind Harmer
2.793
965421AG1-410 GEN
Solar/Wind Harmer
17.306
270449AD2-020 GEN
Solar/Wind Harmer
1.589
270428AC2-015 C
Solar/Wind Harmer
3.1
24695305TIMB G C
Solar/Wind Harmer
3.1
247521TR3_G114
Solar/Wind Harmer
1.829
23920202STRYCT
50/50
1.908
970515AG2-329 GEN
Solar/Wind Harmer
10.167
943021AE2-325 GEN
Solar/Wind Harmer
2.064
270223U2-072_GEN1
Solar/Wind Harmer
0.958
270578AF1-285 GEN2
Solar/Wind Harmer
0.586
970373AG2-245 GEN
Solar/Wind Harmer
9.966
971917AH1-482 GEN
Solar/Wind Harmer
4.14
941551AE2-152 GEN
Solar/Wind Harmer
2.004
276691AA1-018 GEN1
Solar/Wind Harmer
0.047
23929302BS-PKR
50/50
2.267
958321AF2-126 GEN
Solar/Wind Harmer
1.494
270575GUS2 35KV
Solar/Wind Harmer
10.036
970217AG2-149 GEN
Solar/Wind Harmer
22.419
270258AD1-119 GEN
Solar/Wind Harmer
1.74
270491AE1-102 GEN2
Solar/Wind Harmer
0.757
270191TR4_S_V150
Solar/Wind Harmer
1.632
24642205MAYFLWER
Adder
0.343
959331AF2-224 GEN
Solar/Wind Harmer
5.243
274753CRETE EC ;3U
Adder
2.243
964401AG1-302 GEN
Solar/Wind Harmer
4.148
972038AH1-567 GEN2
Adder
0.163
971617AH1-308 GEN
Solar/Wind Harmer
2.555
962511AG1-100 GEN
Solar/Wind Helper
0.339
959441AF2-235 GEN
Solar/Wind Helper
0.146
20334926Z1-069 C
Solar/Wind Helper
0.639
270246TR4_N_V150
Solar/Wind Harmer
0.463
24639705ELKHART HY
Adder
0.083
270055AF2-134 C O1
Solar/Wind Harmer
1.409
274812UNIV PK N;8U
Adder
2.27
276164X3-005 C
Solar/Wind Harmer
0.317
276776AD2-060 GEN
Solar/Wind Harmer
0.189
972207SS24-0001
Solar/Wind Harmer
9.829
274676JOLIET 29;8U
Adder
13.573
274871GR RIDGE ;2U
Solar/Wind Harmer
3.377
274745AC1-111 GEN9
Adder
2.441
274682WAUKEGAN ;7U
Adder
7.794
274828WAUKEGAN ;BP
Adder
4.786
203835AF1-098 GEN
Solar/Wind Helper
1.307
203860AG1-193 C
Solar/Wind Helper
0.148
241966AE1-183 GEN
Solar/Wind Helper
0.129
971989AH1-539 GEN
Solar/Wind Harmer
7.656
957201AF2-014 GEN
Solar/Wind Harmer
2.642
944161AF1-084 GEN
Solar/Wind Harmer
1.269
270302AB2-170 GEN
Solar/Wind Harmer
4.373
963791AG1-232 GEN
Solar/Wind Harmer
6.558
270536AF1-215 GEN2
Solar/Wind Harmer
2.114
958391AF2-133 GEN
Solar/Wind Harmer
4.11
274811UNIV PK N;7U
Adder
2.27
274827FISK ;RP
Adder
3.472
972227AH1-698 GEN1
Adder
1.16
274735ELWOOD EC;4P
Adder
7.259
270024AE2-089 GEN
Solar/Wind Harmer
2.063
274744AC1-111 GEN8
Adder
2.441
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.858
23888702TROY G3
50/50
1.766
972253AH1-711 GEN
50/50
53.942
960841AF2-375 GEN
Solar/Wind Harmer
3.762
247522W1-056 GEN
Solar/Wind Harmer
1.578
246936BC-WTG1
Solar/Wind Harmer
2.279
270489AE1-102 GEN1
Solar/Wind Harmer
0.757
945111AF1-176 GEN
Solar/Wind Harmer
9.898
270505AE1-170 C O1
Solar/Wind Harmer
8.313
965011AG1-365 GEN
Solar/Wind Harmer
5.243
274751CRETE EC ;1U
Adder
2.243
964861AG1-349 GEN
Solar/Wind Harmer
3.588
274723RIVER EC ;12
Adder
8.158
274801UNIV PARK;4U
Adder
2.605
940581AE2-045 GEN
Solar/Wind Harmer
4.55
971605AH1-302 GEN
Solar/Wind Harmer
3.891
274773LINCOLN ;4U
Adder
2.764
274774LINCOLN ;5U
Adder
2.764
970905AG2-564 GEN
Solar/Wind Harmer
2.194
241885AC2-103 GEN1
Solar/Wind Helper
9.447
961971AG1-040 GEN
Solar/Wind Helper
0.332
254303AC2-168 GEN
Solar/Wind Helper
0.075
23867002DVBSG1
50/50
13.074
23888502TROY G1
50/50
1.766
23888602TROY G2
50/50
1.766
971549AH1-272 GEN
Solar/Wind Harmer
12.831
247607V1-011 GEN
Solar/Wind Harmer
2.323
270435AC2-044 GEN
Solar/Wind Harmer
1.165
971771AH1-392 GEN
Solar/Wind Harmer
4.733
971769AH1-391 GEN
Solar/Wind Harmer
5.127
971567AH1-282 GEN
Solar/Wind Harmer
7.606
270071AF1-092 GEN
Solar/Wind Harmer
6.904
274728ELWOOD EC;5P
Adder
7.259
241886AC2-103 GEN2
Solar/Wind Helper
9.447
241832AE2-181_GEN
Solar/Wind Harmer
1.96
270044AE2-322 C
Solar/Wind Harmer
0.854
24441205WTRV SLR C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
3.137
965021AG1-366 GEN
Solar/Wind Harmer
1.219
270485AE1-090_GEN
Solar/Wind Harmer
0.316
270043AE2-236 GEN
Solar/Wind Harmer
2.723
274724RIVER EC ;11
Adder
8.061
274802UNIV PARK;5U
Adder
2.613
274800UNIV PARK;3U
Adder
2.605
970941AG2-585 GEN
Solar/Wind Harmer
5.576
274772LINCOLN ;3U
Adder
2.764
276897AD1-100 C
Solar/Wind Harmer
12.825
276893AG1-478 C
Solar/Wind Harmer
0.185
274729ELWOOD EC;1P
Adder
7.259
945641AF1-229 GEN
Solar/Wind Harmer
3.442
965051AG1-369 GEN
Solar/Wind Harmer
2.716
270317AD1-130_GEN
Solar/Wind Harmer
1.676
971347AH1-153 GEN
Solar/Wind Harmer
7.365
972037AH1-567 GEN1
Adder
0.082
960591AF2-350 GEN
Solar/Wind Harmer
4.461
274775LINCOLN ;6U
Adder
2.764
274777LINCOLN ;8U
Adder
2.764
274675JOLIET 29;7U
Adder
13.573
274675JOLIET 29;7U
Adder
13.089
970833AG2-524 GEN
Solar/Wind Harmer
3.836
970833AG2-524 GEN
Solar/Wind Harmer
1.784
203846AF2-130 C
Solar/Wind Helper
0.246
23856402BAYSG1
50/50
1.288
241858AF1-205_GEN
Solar/Wind Harmer
5.509
241808AF1-120 C
Solar/Wind Harmer
1.205
972301AH1-735 GEN
Adder
6.613
270361_3
Solar/Wind Harmer
8.519
944231AF1-091 GEN
Solar/Wind Harmer
2.462
270063AE2-323 C
Solar/Wind Harmer
1.182
270462AD2-086
Solar/Wind Harmer
3.638
270391AF1-285 GEN3
Solar/Wind Harmer
0.586
274754CRETE EC ;4U
Adder
2.243
958381AF2-132 GEN
Solar/Wind Harmer
4.148
274732ELWOOD EC;7P
Adder
7.259
274674JOLIET 9 ;6U
Adder
6.799
970245AG2-165 GEN
Solar/Wind Harmer
7.863
24189802OREGON_CT1
50/50
2.653
942801AE2-298 GEN
Solar/Wind Harmer
0.882
961051AF2-396 GEN
Solar/Wind Harmer
8.926
961051AF2-396 GEN
Solar/Wind Harmer
4.152
270216AD2-079_GEN
Solar/Wind Harmer
0.324
270224U2-072_GEN2
Solar/Wind Harmer
0.958
274803UNIV PARK;6U
Adder
2.613
274887GEN-1.85
Solar/Wind Harmer
2.378
274674JOLIET 9 ;6U
Adder
6.799
274693ROCKY RD ;1P
Adder
4.78
274683WAUKEGAN ;8U
Adder
9.13
274683WAUKEGAN ;8U
Adder
7.697
203947AF1-006 C
Solar/Wind Helper
0.378
241967AE2-285_GEN
Solar/Wind Helper
0.336
23888802TROY G4
50/50
1.766
960981AF2-389 GEN
Solar/Wind Harmer
0.835
247620Y3-023
Adder
0.25
270526AF1-158 GEN
Solar/Wind Harmer
2.341
24441505OLIV SLR
Solar/Wind Harmer
0.069
965791AG1-447 GEN
Solar/Wind Harmer
3.155
971231AH1-075 GEN
Solar/Wind Harmer
0.374
276843GEN-1.7
Solar/Wind Harmer
0.256
958011AF2-095 GEN
Solar/Wind Harmer
6.424
274695ROCKY RD ;2P
Adder
4.827
946381AF1-302 GEN
Solar/Wind Helper
0.104
238217AF1-153 C O1
Solar/Wind Helper
0.11
23906502RICHG2&3
Adder
1.32
270588AE1-091_GEN
Solar/Wind Harmer
6.813
247643Z2-116 C
Solar/Wind Harmer
0.037
270535AF1-215 GEN1
Solar/Wind Harmer
2.114
972181SS23-001
Solar/Wind Harmer
2.721
276806AD2-047 C O1
Solar/Wind Harmer
4.772
274676JOLIET 29;8U
Adder
13.089
274734ELWOOD EC;8P
Adder
7.259
274736ELWOOD EC;9P
Adder
7.259
943121AE2-341 GEN
Solar/Wind Harmer
6.548
943591AF1-030 GEN
Solar/Wind Harmer
4.365
274682WAUKEGAN ;7U
Adder
7.794
203830AF1-094 GEN
Solar/Wind Helper
0.321
990527J1329
External Queue
1.7751743793487549
991177J1571 G
External Queue
14.956707954406738
991182J1586 G
External Queue
24.279396057128906
990142J1224
External Queue
12.976524353027344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.653
LGEELTFEXP_LGEE->PJM
CLTF
1.969
MECLTFEXP_MEC->PJM
CLTF
6.308
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.607
NYPJM->LTFIMP_NY
CLTF
2
TVALTFEXP_TVA->PJM
CLTF
2.196
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.167
CPLELTFEXP_CPLE->PJM
CLTF
0.331
SIGELTFEXP_SIGE->PJM
CLTF
0.164
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.701
WECLTFEXP_WEC->PJM
CLTF
1.618
LAGNLTFEXP_LAGN->PJM
CLTF
4.838

Details for 02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:128.94 %
Rating:1646.0 MVA
Rating Type:B
MVA to Mitigate:2122.34
MW Contribution:1.73
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.736
972253AH1-711 GEN
50/50
53.019
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.163
270489AE1-102 GEN1
Solar/Wind Harmer
0.522
945111AF1-176 GEN
Solar/Wind Harmer
6.808
270505AE1-170 C O1
Solar/Wind Harmer
4.002
965011AG1-365 GEN
Solar/Wind Harmer
3.611
970905AG2-564 GEN
Solar/Wind Harmer
1.733
274751CRETE EC ;1U
Adder
3.728
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.046
274801UNIV PARK;4U
Adder
2.569
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.837
274773LINCOLN ;4U
Adder
3.711
274774LINCOLN ;5U
Adder
3.711
241885AC2-103 GEN1
Solar/Wind Helper
9.503
961971AG1-040 GEN
Solar/Wind Helper
0.328
254303AC2-168 GEN
Solar/Wind Helper
0.074
23888802TROY G4
50/50
1.736
247620Y3-023
Adder
0.246
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.111
971231AH1-075 GEN
Solar/Wind Harmer
0.374
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.42
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
946381AF1-302 GEN
Solar/Wind Helper
0.103
241996AE2-282_GEN
Solar/Wind Harmer
0.005
970621AG2-405 GEN
Solar/Wind Harmer
0.866
970623AG2-406 GEN
Solar/Wind Harmer
0.788
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.163
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.611
274808UNIV PK N;4U
Adder
2.229
274888KELLY CRK;1U
Solar/Wind Harmer
0.18
274770LINCOLN ;1U
Adder
3.711
274771LINCOLN ;2U
Adder
3.711
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.331
970321AG2-212 GEN
Solar/Wind Harmer
1.313
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.321
24189802OREGON_CT1
50/50
2.603
961051AF2-396 GEN
Solar/Wind Harmer
7.735
961051AF2-396 GEN
Solar/Wind Harmer
5.157
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.083
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.577
274887GEN-1.85
Solar/Wind Harmer
0.081
274674JOLIET 9 ;6U
Adder
6.706
958481AF2-142 GEN
Solar/Wind Harmer
4.505
274862TOP CROP ;2U
Solar/Wind Harmer
0.406
203947AF1-006 C
Solar/Wind Helper
0.374
241967AE2-285_GEN
Solar/Wind Helper
0.332
24189902OREGON_CT2
50/50
2.551
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.308
23906502RICHG2&3
Adder
1.306
241807AE2-176_GEN
Solar/Wind Harmer
0.004
270428AC2-015 C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
11.925
270449AD2-020 GEN
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.137
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.082
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274812UNIV PK N;8U
Adder
2.238
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.32
274676JOLIET 29;8U
Adder
13.387
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.408
203835AF1-098 GEN
Solar/Wind Helper
1.293
203860AG1-193 C
Solar/Wind Helper
0.146
241966AE1-183 GEN
Solar/Wind Helper
0.128
972211AH1-690 GEN
50/50
275.118
970817AG2-515 GEN
Solar/Wind Harmer
10.289
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.769
24191202EL_AA1-006
Adder
0.112
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.223
274814UNIV PK N;0U
Adder
2.258
274807UNIV PK N;3U
Adder
2.253
274805UNIV PK N;1U
Adder
2.243
274776LINCOLN ;7U
Adder
3.711
274687WILL CNTY;4U
Adder
12.217
274687WILL CNTY;4U
Adder
12.217
274731ELWOOD EC;2P
Adder
7.16
274733ELWOOD EC;3P
Adder
7.16
274746AC1-111 G10
Adder
2.408
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.11
971989AH1-539 GEN
Solar/Wind Harmer
1.772
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.506
963791AG1-232 GEN
Solar/Wind Harmer
4.517
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.238
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.424
972227AH1-698 GEN1
Adder
1.144
274735ELWOOD EC;4P
Adder
7.16
270024AE2-089 GEN
Solar/Wind Harmer
0.003
274744AC1-111 GEN8
Adder
2.408
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.848
23929302BS-PKR
50/50
2.254
958321AF2-126 GEN
Solar/Wind Harmer
1.148
270575GUS2 35KV
Solar/Wind Harmer
4.656
970217AG2-149 GEN
Solar/Wind Harmer
4.19
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.522
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.715
965051AG1-369 GEN
Solar/Wind Harmer
1.872
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.067
972037AH1-567 GEN1
Adder
0.081
971611AH1-305 GEN
Solar/Wind Harmer
1.828
960591AF2-350 GEN
Solar/Wind Harmer
3.069
274775LINCOLN ;6U
Adder
3.711
274777LINCOLN ;8U
Adder
3.711
274675JOLIET 29;7U
Adder
13.387
274675JOLIET 29;7U
Adder
12.909
970833AG2-524 GEN
Solar/Wind Harmer
3.326
970833AG2-524 GEN
Solar/Wind Harmer
2.217
203846AF2-130 C
Solar/Wind Helper
0.243
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.249
23867002DVBSG1
50/50
12.729
23888502TROY G1
50/50
1.736
23888602TROY G2
50/50
1.736
971549AH1-272 GEN
Solar/Wind Harmer
9.844
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.508
971771AH1-392 GEN
Solar/Wind Harmer
3.617
971769AH1-391 GEN
Solar/Wind Harmer
3.938
971567AH1-282 GEN
Solar/Wind Harmer
5.256
270071AF1-092 GEN
Solar/Wind Harmer
6.074
274728ELWOOD EC;5P
Adder
7.16
241886AC2-103 GEN2
Solar/Wind Helper
9.503
241832AE2-181_GEN
Solar/Wind Harmer
0.003
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.093
965021AG1-366 GEN
Solar/Wind Harmer
1.204
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.187
274724RIVER EC ;11
Adder
7.95
274802UNIV PARK;5U
Adder
2.577
274800UNIV PARK;3U
Adder
2.569
970941AG2-585 GEN
Solar/Wind Harmer
3.837
274772LINCOLN ;3U
Adder
3.711
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.12
274729ELWOOD EC;1P
Adder
7.16
270247TR4_N_V136
Solar/Wind Harmer
0.024
970031AG2-029 GEN
Solar/Wind Harmer
2.393
970349AG2-230 GEN
Solar/Wind Harmer
5.067
270391AF1-285 GEN3
Solar/Wind Harmer
0.223
270377AD1-106 GEN
Solar/Wind Harmer
1.238
274752CRETE EC ;2U
Adder
3.728
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
4.831
972228AH1-698 GEN2
Adder
1.625
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
9.926
274730ELWOOD EC;6P
Adder
7.16
970513AG2-328 GEN
Solar/Wind Harmer
1.313
970517AG2-330 GEN
Solar/Wind Harmer
7.878
276694AA1-018 GEN2
Solar/Wind Harmer
0
254305AE2-115 C
Solar/Wind Helper
0.11
23856402BAYSG1
50/50
1.281
241858AF1-205_GEN
Solar/Wind Harmer
3.799
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
6.539
270361_3
Solar/Wind Harmer
4.656
944231AF1-091 GEN
Solar/Wind Harmer
1.201
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
3.728
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.16
274674JOLIET 9 ;6U
Adder
6.706
970245AG2-165 GEN
Solar/Wind Harmer
1.313
23906502RICHG2&3
Adder
1.306
270588AE1-091_GEN
Solar/Wind Harmer
3.358
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.739
274676JOLIET 29;8U
Adder
12.909
274734ELWOOD EC;8P
Adder
7.16
274736ELWOOD EC;9P
Adder
7.16
943121AE2-341 GEN
Solar/Wind Harmer
5.036
943591AF1-030 GEN
Solar/Wind Harmer
3.349
203830AF1-094 GEN
Solar/Wind Helper
0.317
24190002OREGON_ST1
50/50
3.432
971677AH1-339 GEN
Solar/Wind Harmer
0.655
965681AG1-436 GEN
Solar/Wind Harmer
4.242
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.244
203979AG1-198 GEN
Solar/Wind Helper
0.19
241801AE1-079 GEN
Solar/Wind Helper
0.129
270191TR4_S_V150
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.338
959331AF2-224 GEN
Solar/Wind Harmer
2.528
274753CRETE EC ;3U
Adder
3.728
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.161
971617AH1-308 GEN
Solar/Wind Harmer
2.523
962511AG1-100 GEN
Solar/Wind Helper
0.335
959441AF2-235 GEN
Solar/Wind Helper
0.144
20334926Z1-069 C
Solar/Wind Helper
0.632
23920202STRYCT
50/50
1.886
970515AG2-329 GEN
Solar/Wind Harmer
12.569
943021AE2-325 GEN
Solar/Wind Harmer
2.035
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.857
971917AH1-482 GEN
Solar/Wind Harmer
4.083
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.364
990527J1329
External Queue
1.745489239692688
991177J1571 G
External Queue
14.724894523620605
991182J1586 G
External Queue
23.868927001953125
990142J1224
External Queue
12.759525299072266
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.144
LGEELTFEXP_LGEE->PJM
CLTF
1.944
MECLTFEXP_MEC->PJM
CLTF
6.223
AH1-155LTFEXP_AH1-155->PJM
LTF
0.154
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.231
NYPJM->LTFIMP_NY
CLTF
1.977
TVALTFEXP_TVA->PJM
CLTF
2.168
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.139
CPLELTFEXP_CPLE->PJM
CLTF
0.326
SIGELTFEXP_SIGE->PJM
CLTF
0.162
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.589
WECLTFEXP_WEC->PJM
CLTF
1.596
LAGNLTFEXP_LAGN->PJM
CLTF
4.775

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-005_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-005_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:146.75 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2755.89
MW Contribution:2.94
Bus #Bus NameTypeMW Contribution
241996AE2-282_GEN
Solar/Wind Harmer
2.316
270007AE1-245 C
Solar/Wind Harmer
3.723
246938BC-WTG3
Solar/Wind Harmer
2.462
246937BC-WTG2
Solar/Wind Harmer
2.42
957891AF2-083 GEN
Solar/Wind Harmer
1.955
970611AG2-400 GEN
Solar/Wind Harmer
5.544
274808UNIV PK N;4U
Adder
2.372
942221AE2-234 GEN
Solar/Wind Harmer
0.344
274888KELLY CRK;1U
Solar/Wind Harmer
2.765
274770LINCOLN ;1U
Adder
2.903
274771LINCOLN ;2U
Adder
2.903
972259AH1-714 GEN
Adder
8.868
970321AG2-212 GEN
Solar/Wind Harmer
8.259
274696ROCKY RD ;4P
Adder
5.187
274697ROCKY RD ;3P
Adder
1.377
274762LEE CO EC;3U
Adder
4.095
25326509SID D
Adder
0.57
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.353
972211AH1-690 GEN
50/50
288.187
24191202EL_AA1-006
50/50
0.333
970817AG2-515 GEN
Solar/Wind Harmer
15.71
945411AF1-206 GEN
Solar/Wind Harmer
8.65
270499AE1-146 GEN
Solar/Wind Harmer
2.686
270297AD1-101 GEN
Solar/Wind Harmer
2.06
966831AG1-554 GEN
Solar/Wind Harmer
0.787
965041AG1-368 GEN
Solar/Wind Harmer
5.807
960681AF2-359 GEN
Solar/Wind Harmer
1.956
270578AF1-285 GEN2
Solar/Wind Harmer
0.24
274814UNIV PK N;0U
Adder
2.404
274807UNIV PK N;3U
Adder
2.399
274805UNIV PK N;1U
Adder
2.388
274776LINCOLN ;7U
Adder
2.903
274687WILL CNTY;4U
Adder
13.005
274687WILL CNTY;4U
Adder
13.005
274731ELWOOD EC;2P
Adder
7.621
274733ELWOOD EC;3P
Adder
7.621
274746AC1-111 G10
Adder
2.563
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
270541AE2-072 C
Solar/Wind Harmer
4.706
270404AC1-167 GEN
Solar/Wind Harmer
0.76
247604X1-042
Adder
0.265
958091AF2-103 GEN
Solar/Wind Harmer
0.101
270247TR4_N_V136
Solar/Wind Harmer
0.492
23920202STRYCT
50/50
2.045
970515AG2-329 GEN
Solar/Wind Harmer
10.896
943021AE2-325 GEN
Solar/Wind Harmer
2.165
270223U2-072_GEN1
Solar/Wind Harmer
1.021
270578AF1-285 GEN2
Solar/Wind Harmer
0.624
23929302BS-PKR
50/50
2.517
958321AF2-126 GEN
Solar/Wind Harmer
1.63
270575GUS2 35KV
Solar/Wind Harmer
11.477
970217AG2-149 GEN
Solar/Wind Harmer
24.027
270258AD1-119 GEN
Solar/Wind Harmer
1.858
270491AE1-102 GEN2
Solar/Wind Harmer
0.804
270191TR4_S_V150
Solar/Wind Harmer
1.734
24642205MAYFLWER
Adder
0.36
959331AF2-224 GEN
Solar/Wind Harmer
5.544
274753CRETE EC ;3U
Adder
2.355
964401AG1-302 GEN
Solar/Wind Harmer
4.356
961961AG1-039 GEN
Solar/Wind Harmer
1.348
972038AH1-567 GEN2
Adder
0.171
971617AH1-308 GEN
Solar/Wind Harmer
2.7
972236AH1-702 GEN2
Adder
0.975
274760LEE CO EC;1U
Adder
4.095
962511AG1-100 GEN
Solar/Wind Helper
0.369
959441AF2-235 GEN
Solar/Wind Helper
0.159
20334926Z1-069 C
Solar/Wind Helper
0.696
203854AF2-039 C
Solar/Wind Helper
0.151
24189902OREGON_CT2
50/50
2.672
241807AE2-176_GEN
Solar/Wind Harmer
7.277
241840AF1-064_GEN
Solar/Wind Harmer
1.52
23906402RICHG1
Adder
1.419
23906502RICHG2&3
Adder
1.417
270428AC2-015 C
Solar/Wind Harmer
4.143
965421AG1-410 GEN
Solar/Wind Harmer
18.372
24695305TIMB G C
Solar/Wind Harmer
3.301
270449AD2-020 GEN
Solar/Wind Harmer
1.666
247521TR3_G114
Solar/Wind Harmer
1.944
270246TR4_N_V150
Solar/Wind Harmer
0.492
24639705ELKHART HY
Adder
0.087
270055AF2-134 C O1
Solar/Wind Harmer
1.48
274812UNIV PK N;8U
Adder
2.383
276164X3-005 C
Solar/Wind Harmer
0.333
971989AH1-539 GEN
Solar/Wind Harmer
8.505
957201AF2-014 GEN
Solar/Wind Harmer
2.805
944161AF1-084 GEN
Solar/Wind Harmer
1.331
270302AB2-170 GEN
Solar/Wind Harmer
4.661
963791AG1-232 GEN
Solar/Wind Harmer
6.936
270536AF1-215 GEN2
Solar/Wind Harmer
2.22
958391AF2-133 GEN
Solar/Wind Harmer
4.316
274811UNIV PK N;7U
Adder
2.383
274827FISK ;RP
Adder
3.645
972227AH1-698 GEN1
Adder
1.218
270024AE2-089 GEN
Solar/Wind Harmer
2.18
274735ELWOOD EC;4P
Adder
7.621
274744AC1-111 GEN8
Adder
2.563
241997AF1-093 GEN
Solar/Wind Helper
0.14
203804AE2-113_GEN
Solar/Wind Helper
0.935
23888702TROY G3
50/50
1.831
972253AH1-711 GEN
50/50
55.942
23860302FRMENG 3
50/50
3.53
241885AC2-103 GEN1
Solar/Wind Harmer
12.859
960841AF2-375 GEN
Solar/Wind Harmer
4.291
247522W1-056 GEN
Solar/Wind Harmer
1.77
246936BC-WTG1
Solar/Wind Harmer
2.42
270489AE1-102 GEN1
Solar/Wind Harmer
0.804
970905AG2-564 GEN
Solar/Wind Harmer
2.943
945111AF1-176 GEN
Solar/Wind Harmer
10.388
270505AE1-170 C O1
Solar/Wind Harmer
8.723
965011AG1-365 GEN
Solar/Wind Harmer
5.544
274751CRETE EC ;1U
Adder
2.355
964861AG1-349 GEN
Solar/Wind Harmer
3.767
274723RIVER EC ;12
Adder
8.566
274801UNIV PARK;4U
Adder
2.735
940581AE2-045 GEN
Solar/Wind Harmer
4.778
971605AH1-302 GEN
Solar/Wind Harmer
4.086
274773LINCOLN ;4U
Adder
2.903
274774LINCOLN ;5U
Adder
2.903
274761LEE CO EC;2U
Adder
4.095
961971AG1-040 GEN
Solar/Wind Helper
0.361
254303AC2-168 GEN
Solar/Wind Helper
0.082
23867002DVBSG1
50/50
12.801
23888502TROY G1
50/50
1.831
23888602TROY G2
50/50
1.831
23860102FRMENG 1
50/50
1.729
23860202FRMENG 2
50/50
1.729
241886AC2-103 GEN2
Solar/Wind Harmer
12.859
971549AH1-272 GEN
Solar/Wind Harmer
13.433
247607V1-011 GEN
Solar/Wind Harmer
2.482
270435AC2-044 GEN
Solar/Wind Harmer
1.237
971771AH1-392 GEN
Solar/Wind Harmer
4.969
971567AH1-282 GEN
Solar/Wind Harmer
8.2
971769AH1-391 GEN
Solar/Wind Harmer
5.381
270071AF1-092 GEN
Solar/Wind Harmer
7.277
274728ELWOOD EC;5P
Adder
7.621
24729505KEY G4
Adder
2.933
241832AE2-181_GEN
Solar/Wind Harmer
2.098
270044AE2-322 C
Solar/Wind Harmer
0.913
24441205WTRV SLR C
Solar/Wind Harmer
0.084
945111AF1-176 GEN
Solar/Wind Harmer
3.292
270485AE1-090_GEN
Solar/Wind Harmer
0.337
965021AG1-366 GEN
Solar/Wind Harmer
1.289
270043AE2-236 GEN
Solar/Wind Harmer
2.87
274724RIVER EC ;11
Adder
8.463
274802UNIV PARK;5U
Adder
2.744
274800UNIV PARK;3U
Adder
2.735
970941AG2-585 GEN
Solar/Wind Harmer
5.854
274772LINCOLN ;3U
Adder
2.903
276897AD1-100 C
Solar/Wind Harmer
13.466
276893AG1-478 C
Solar/Wind Harmer
0.194
274729ELWOOD EC;1P
Adder
7.621
970031AG2-029 GEN
Solar/Wind Harmer
16.895
270377AD1-106 GEN
Solar/Wind Harmer
3.284
942871AE2-306 GEN
Solar/Wind Harmer
0.468
270391AF1-285 GEN3
Solar/Wind Harmer
0.24
970349AG2-230 GEN
Solar/Wind Harmer
7.734
972231SS25-0005
Solar/Wind Harmer
4.572
274752CRETE EC ;2U
Adder
2.355
959141AF2-205 GEN
Solar/Wind Harmer
2.857
274826FISK ;BP
Adder
5.143
276772AC2-154 GEN
Solar/Wind Harmer
1.306
972228AH1-698 GEN2
Adder
1.73
939351AE1-166 GEN
Solar/Wind Harmer
2.751
274730ELWOOD EC;6P
Adder
7.621
970707AG2-453 GEN
Solar/Wind Harmer
12.981
970513AG2-328 GEN
Solar/Wind Harmer
8.259
970517AG2-330 GEN
Solar/Wind Harmer
7.49
254305AE2-115 C
Solar/Wind Helper
0.121
945641AF1-229 GEN
Solar/Wind Harmer
3.662
965051AG1-369 GEN
Solar/Wind Harmer
2.887
270317AD1-130_GEN
Solar/Wind Harmer
1.787
971347AH1-153 GEN
Solar/Wind Harmer
7.734
972037AH1-567 GEN1
Adder
0.086
960591AF2-350 GEN
Solar/Wind Harmer
4.683
274775LINCOLN ;6U
Adder
2.903
274777LINCOLN ;8U
Adder
2.903
274675JOLIET 29;7U
Adder
14.25
274675JOLIET 29;7U
Adder
13.741
970833AG2-524 GEN
Solar/Wind Harmer
4.028
970833AG2-524 GEN
Solar/Wind Harmer
1.873
274823ROCKFORD ;21
Adder
8.678
203846AF2-130 C
Solar/Wind Helper
0.267
203855AF2-088 C
Solar/Wind Helper
0.073
23856402BAYSG1
50/50
1.43
241858AF1-205_GEN
Solar/Wind Harmer
5.91
241808AF1-120 C
Solar/Wind Harmer
1.291
972301AH1-735 GEN
Adder
7.097
270361_3
Solar/Wind Harmer
9.742
944231AF1-091 GEN
Solar/Wind Harmer
2.617
270063AE2-323 C
Solar/Wind Harmer
1.245
270462AD2-086
Solar/Wind Harmer
3.878
270391AF1-285 GEN3
Solar/Wind Harmer
0.624
274754CRETE EC ;4U
Adder
2.355
958381AF2-132 GEN
Solar/Wind Harmer
4.356
241847AF2-150_GEN
Solar/Wind Harmer
1.954
274732ELWOOD EC;7P
Adder
7.621
274674JOLIET 9 ;6U
Adder
7.138
970245AG2-165 GEN
Solar/Wind Harmer
8.259
972235AH1-702 GEN1
Adder
1.121
274766LEE CO EC;7U
Adder
4.047
24189802OREGON_CT1
50/50
2.727
942801AE2-298 GEN
Solar/Wind Harmer
0.943
961051AF2-396 GEN
Solar/Wind Harmer
9.365
961051AF2-396 GEN
Solar/Wind Harmer
4.356
270216AD2-079_GEN
Solar/Wind Harmer
0.34
270224U2-072_GEN2
Solar/Wind Harmer
1.021
274803UNIV PARK;6U
Adder
2.744
274887GEN-1.85
Solar/Wind Harmer
2.496
274674JOLIET 9 ;6U
Adder
7.138
274693ROCKY RD ;1P
Adder
5.018
274683WAUKEGAN ;8U
Adder
9.585
274683WAUKEGAN ;8U
Adder
8.08
274764LEE CO EC;5U
Adder
4.104
972267AH1-718 GEN
Adder
1.82
203947AF1-006 C
Solar/Wind Helper
0.411
241967AE2-285_GEN
Solar/Wind Helper
0.365
20398826ARMNA MT
Solar/Wind Helper
0.712
276776AD2-060 GEN
Solar/Wind Harmer
0.198
972207SS24-0001
Solar/Wind Harmer
10.32
274676JOLIET 29;8U
Adder
14.25
274871GR RIDGE ;2U
Solar/Wind Harmer
3.545
274745AC1-111 GEN9
Adder
2.563
274682WAUKEGAN ;7U
Adder
8.182
274828WAUKEGAN ;BP
Adder
5.024
203835AF1-098 GEN
Solar/Wind Helper
1.422
203860AG1-193 C
Solar/Wind Helper
0.161
241966AE1-183 GEN
Solar/Wind Helper
0.14
23888802TROY G4
50/50
1.831
960981AF2-389 GEN
Solar/Wind Harmer
0.877
247620Y3-023
Adder
0.262
270526AF1-158 GEN
Solar/Wind Harmer
2.458
24441505OLIV SLR
Solar/Wind Harmer
0.072
971231AH1-075 GEN
Solar/Wind Harmer
0.425
965791AG1-447 GEN
Solar/Wind Harmer
3.311
276843GEN-1.7
Solar/Wind Harmer
0.269
958011AF2-095 GEN
Solar/Wind Harmer
6.744
274695ROCKY RD ;2P
Adder
5.068
274765LEE CO EC;6U
Adder
4.104
274763LEE CO EC;4U
Adder
4.056
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.12
23906502RICHG2&3
Adder
1.417
270588AE1-091_GEN
Solar/Wind Harmer
7.489
247643Z2-116 C
Solar/Wind Harmer
0.039
270535AF1-215 GEN1
Solar/Wind Harmer
2.22
972181SS23-001
Solar/Wind Harmer
2.857
276806AD2-047 C O1
Solar/Wind Harmer
5.01
274676JOLIET 29;8U
Adder
13.741
274734ELWOOD EC;8P
Adder
7.621
274736ELWOOD EC;9P
Adder
7.621
274682WAUKEGAN ;7U
Adder
8.182
274767LEE CO EC;8U
Adder
4.047
203830AF1-094 GEN
Solar/Wind Helper
0.349
203818AF1-086 GEN
Solar/Wind Helper
0.772
943121AE2-341 GEN
Solar/Wind Harmer
2.136
943591AF1-030 GEN
Solar/Wind Harmer
1.424
970373AG2-245 GEN
Solar/Wind Harmer
10.463
971917AH1-482 GEN
Solar/Wind Harmer
4.347
941551AE2-152 GEN
Solar/Wind Harmer
2.104
274822ROCKFORD ;11
Adder
8.741
203954AE2-126 C
Solar/Wind Helper
0.235
24190002OREGON_ST1
50/50
3.596
971677AH1-339 GEN
Solar/Wind Harmer
7.553
965681AG1-436 GEN
Solar/Wind Harmer
6.472
270227U2-072_GEN3
Solar/Wind Harmer
1.021
270228U2-072_GEN4
Solar/Wind Harmer
1.021
270231U2-072_GEN5
Solar/Wind Harmer
1.021
274847GR RIDGE ;BU
Solar/Wind Harmer
2.332
203980AG1-197 GEN
Solar/Wind Helper
0.269
203979AG1-198 GEN
Solar/Wind Helper
0.209
241801AE1-079 GEN
Solar/Wind Helper
0.142
203853AF1-134 C O1
Solar/Wind Helper
0.222
990527J1329
External Queue
1.8513455390930176
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990142J1224
External Queue
13.53333568572998
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.15
CPLELTFEXP_CPLE->PJM
CLTF
0.293
SIGELTFEXP_SIGE->PJM
CLTF
0.172
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.083
WECLTFEXP_WEC->PJM
CLTF
1.698
LAGNLTFEXP_LAGN->PJM
CLTF
5.047
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.459
LGEELTFEXP_LGEE->PJM
CLTF
2.068
MECLTFEXP_MEC->PJM
CLTF
6.617
AH1-155LTFEXP_AH1-155->PJM
LTF
0.164
CBM West 1LTFEXP_CBM-W1->PJM
CBM
95.745
NYPJM->LTFIMP_NY
CLTF
2.188
TVALTFEXP_TVA->PJM
CLTF
2.288
AG2-052LTFEXP_AG2-052->PJM
LTF
0.109

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-006_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-006_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:144.08 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2705.74
MW Contribution:3.1
Bus #Bus NameTypeMW Contribution
241996AE2-282_GEN
Solar/Wind Harmer
2.333
270007AE1-245 C
Solar/Wind Harmer
3.775
246938BC-WTG3
Solar/Wind Harmer
2.496
246937BC-WTG2
Solar/Wind Harmer
2.454
957891AF2-083 GEN
Solar/Wind Harmer
1.981
970611AG2-400 GEN
Solar/Wind Harmer
5.623
274808UNIV PK N;4U
Adder
2.408
942221AE2-234 GEN
Solar/Wind Harmer
0.349
274888KELLY CRK;1U
Solar/Wind Harmer
2.807
274770LINCOLN ;1U
Adder
2.947
274771LINCOLN ;2U
Adder
2.947
972259AH1-714 GEN
Adder
9.004
970321AG2-212 GEN
Solar/Wind Harmer
8.386
274696ROCKY RD ;4P
Adder
5.267
274697ROCKY RD ;3P
Adder
1.398
274762LEE CO EC;3U
Adder
4.16
25326509SID D
Adder
0.581
241985AE1-237 GEN
Solar/Wind Helper
0.142
962101AG1-054 GEN
Solar/Wind Helper
0.354
972211AH1-690 GEN
50/50
289.616
24191202EL_AA1-006
50/50
0.345
970817AG2-515 GEN
Solar/Wind Harmer
15.806
945411AF1-206 GEN
Solar/Wind Harmer
8.713
270499AE1-146 GEN
Solar/Wind Harmer
2.723
270297AD1-101 GEN
Solar/Wind Harmer
2.086
966831AG1-554 GEN
Solar/Wind Harmer
0.802
965041AG1-368 GEN
Solar/Wind Harmer
5.889
960681AF2-359 GEN
Solar/Wind Harmer
1.984
270578AF1-285 GEN2
Solar/Wind Harmer
0.244
274814UNIV PK N;0U
Adder
2.44
274807UNIV PK N;3U
Adder
2.434
274805UNIV PK N;1U
Adder
2.424
274776LINCOLN ;7U
Adder
2.947
274687WILL CNTY;4U
Adder
13.203
23929302BS-PKR
50/50
2.537
958321AF2-126 GEN
Solar/Wind Harmer
1.643
270575GUS2 35KV
Solar/Wind Harmer
11.637
970217AG2-149 GEN
Solar/Wind Harmer
24.543
270258AD1-119 GEN
Solar/Wind Harmer
1.882
270491AE1-102 GEN2
Solar/Wind Harmer
0.815
270191TR4_S_V150
Solar/Wind Harmer
1.759
24642205MAYFLWER
Adder
0.364
959331AF2-224 GEN
Solar/Wind Harmer
5.623
961961AG1-039 GEN
Solar/Wind Harmer
1.415
971989AH1-539 GEN
Solar/Wind Harmer
8.669
957201AF2-014 GEN
Solar/Wind Harmer
2.844
944161AF1-084 GEN
Solar/Wind Harmer
1.348
270302AB2-170 GEN
Solar/Wind Harmer
4.734
963791AG1-232 GEN
Solar/Wind Harmer
7.04
270536AF1-215 GEN2
Solar/Wind Harmer
2.253
958391AF2-133 GEN
Solar/Wind Harmer
4.381
274811UNIV PK N;7U
Adder
2.419
274827FISK ;RP
Adder
3.7
972227AH1-698 GEN1
Adder
1.236
270024AE2-089 GEN
Solar/Wind Harmer
2.215
274735ELWOOD EC;4P
Adder
7.738
274744AC1-111 GEN8
Adder
2.602
241997AF1-093 GEN
Solar/Wind Helper
0.141
203804AE2-113_GEN
Solar/Wind Helper
0.937
23888702TROY G3
50/50
1.842
972253AH1-711 GEN
50/50
56.254
23860302FRMENG 3
50/50
3.59
241885AC2-103 GEN1
Solar/Wind Harmer
12.88
960841AF2-375 GEN
Solar/Wind Harmer
4.35
247522W1-056 GEN
Solar/Wind Harmer
1.802
246936BC-WTG1
Solar/Wind Harmer
2.454
270489AE1-102 GEN1
Solar/Wind Harmer
0.815
970905AG2-564 GEN
Solar/Wind Harmer
3.098
945111AF1-176 GEN
Solar/Wind Harmer
10.521
270505AE1-170 C O1
Solar/Wind Harmer
8.835
965011AG1-365 GEN
Solar/Wind Harmer
5.623
274751CRETE EC ;1U
Adder
2.389
23867002DVBSG1
50/50
12.822
23888502TROY G1
50/50
1.842
23888602TROY G2
50/50
1.842
23860102FRMENG 1
50/50
1.758
23860202FRMENG 2
50/50
1.758
241886AC2-103 GEN2
Solar/Wind Harmer
12.88
971549AH1-272 GEN
Solar/Wind Harmer
13.576
247607V1-011 GEN
Solar/Wind Harmer
2.516
270435AC2-044 GEN
Solar/Wind Harmer
1.254
971567AH1-282 GEN
Solar/Wind Harmer
8.435
971771AH1-392 GEN
Solar/Wind Harmer
5.035
971769AH1-391 GEN
Solar/Wind Harmer
5.455
270071AF1-092 GEN
Solar/Wind Harmer
7.388
274728ELWOOD EC;5P
Adder
7.738
24729505KEY G4
Adder
2.98
241832AE2-181_GEN
Solar/Wind Harmer
2.114
270044AE2-322 C
Solar/Wind Harmer
0.925
24441205WTRV SLR C
Solar/Wind Harmer
0.085
945111AF1-176 GEN
Solar/Wind Harmer
3.334
270485AE1-090_GEN
Solar/Wind Harmer
0.342
965021AG1-366 GEN
Solar/Wind Harmer
1.308
270043AE2-236 GEN
Solar/Wind Harmer
2.911
274724RIVER EC ;11
Adder
8.59
274802UNIV PARK;5U
Adder
2.785
274800UNIV PARK;3U
Adder
2.776
970941AG2-585 GEN
Solar/Wind Harmer
5.943
274772LINCOLN ;3U
Adder
2.947
276897AD1-100 C
Solar/Wind Harmer
13.671
276893AG1-478 C
Solar/Wind Harmer
0.197
274729ELWOOD EC;1P
Adder
7.738
270541AE2-072 C
Solar/Wind Harmer
4.757
270404AC1-167 GEN
Solar/Wind Harmer
0.77
247604X1-042
Adder
0.268
958091AF2-103 GEN
Solar/Wind Harmer
0.103
270247TR4_N_V136
Solar/Wind Harmer
0.499
970031AG2-029 GEN
Solar/Wind Harmer
17.123
270377AD1-106 GEN
Solar/Wind Harmer
3.371
942871AE2-306 GEN
Solar/Wind Harmer
0.476
270391AF1-285 GEN3
Solar/Wind Harmer
0.244
970349AG2-230 GEN
Solar/Wind Harmer
7.843
972231SS25-0005
Solar/Wind Harmer
4.639
945641AF1-229 GEN
Solar/Wind Harmer
3.712
965051AG1-369 GEN
Solar/Wind Harmer
2.928
270317AD1-130_GEN
Solar/Wind Harmer
1.815
971347AH1-153 GEN
Solar/Wind Harmer
7.843
972037AH1-567 GEN1
Adder
0.087
960591AF2-350 GEN
Solar/Wind Harmer
4.754
274775LINCOLN ;6U
Adder
2.947
274777LINCOLN ;8U
Adder
2.947
274675JOLIET 29;7U
Adder
14.468
274675JOLIET 29;7U
Adder
13.951
970833AG2-524 GEN
Solar/Wind Harmer
4.089
970833AG2-524 GEN
Solar/Wind Harmer
1.902
274823ROCKFORD ;21
Adder
8.814
203846AF2-130 C
Solar/Wind Helper
0.268
964861AG1-349 GEN
Solar/Wind Harmer
3.823
274723RIVER EC ;12
Adder
8.693
274801UNIV PARK;4U
Adder
2.776
940581AE2-045 GEN
Solar/Wind Harmer
4.851
971605AH1-302 GEN
Solar/Wind Harmer
4.148
274773LINCOLN ;4U
Adder
2.947
274774LINCOLN ;5U
Adder
2.947
274761LEE CO EC;2U
Adder
4.16
961971AG1-040 GEN
Solar/Wind Helper
0.363
254303AC2-168 GEN
Solar/Wind Helper
0.082
203855AF2-088 C
Solar/Wind Helper
0.073
23856402BAYSG1
50/50
1.441
241858AF1-205_GEN
Solar/Wind Harmer
5.953
241808AF1-120 C
Solar/Wind Harmer
1.301
972301AH1-735 GEN
Adder
7.158
270361_3
Solar/Wind Harmer
9.878
944231AF1-091 GEN
Solar/Wind Harmer
2.648
270063AE2-323 C
Solar/Wind Harmer
1.262
270462AD2-086
Solar/Wind Harmer
3.938
270391AF1-285 GEN3
Solar/Wind Harmer
0.635
241847AF2-150_GEN
Solar/Wind Harmer
2.052
274754CRETE EC ;4U
Adder
2.389
958381AF2-132 GEN
Solar/Wind Harmer
4.421
274732ELWOOD EC;7P
Adder
7.738
274674JOLIET 9 ;6U
Adder
7.247
970245AG2-165 GEN
Solar/Wind Harmer
8.386
972235AH1-702 GEN1
Adder
1.138
274766LEE CO EC;7U
Adder
4.111
24189802OREGON_CT1
50/50
2.741
942801AE2-298 GEN
Solar/Wind Harmer
0.956
961051AF2-396 GEN
Solar/Wind Harmer
9.484
961051AF2-396 GEN
Solar/Wind Harmer
4.411
270216AD2-079_GEN
Solar/Wind Harmer
0.344
270224U2-072_GEN2
Solar/Wind Harmer
1.038
274803UNIV PARK;6U
Adder
2.785
274887GEN-1.85
Solar/Wind Harmer
2.534
274674JOLIET 9 ;6U
Adder
7.247
274693ROCKY RD ;1P
Adder
5.095
274683WAUKEGAN ;8U
Adder
9.733
274683WAUKEGAN ;8U
Adder
8.205
274764LEE CO EC;5U
Adder
4.169
972267AH1-718 GEN
Adder
1.849
203947AF1-006 C
Solar/Wind Helper
0.413
241967AE2-285_GEN
Solar/Wind Helper
0.366
20398826ARMNA MT
Solar/Wind Helper
0.713
24189902OREGON_CT2
50/50
2.686
241807AE2-176_GEN
Solar/Wind Harmer
7.419
241840AF1-064_GEN
Solar/Wind Harmer
1.533
23906402RICHG1
Adder
1.432
23906502RICHG2&3
Adder
1.43
270428AC2-015 C
Solar/Wind Harmer
4.301
965421AG1-410 GEN
Solar/Wind Harmer
18.626
24695305TIMB G C
Solar/Wind Harmer
3.347
270449AD2-020 GEN
Solar/Wind Harmer
1.687
247521TR3_G114
Solar/Wind Harmer
1.972
270246TR4_N_V150
Solar/Wind Harmer
0.499
24639705ELKHART HY
Adder
0.088
270055AF2-134 C O1
Solar/Wind Harmer
1.502
274812UNIV PK N;8U
Adder
2.419
276164X3-005 C
Solar/Wind Harmer
0.338
276776AD2-060 GEN
Solar/Wind Harmer
0.201
972207SS24-0001
Solar/Wind Harmer
10.477
274676JOLIET 29;8U
Adder
14.467
274871GR RIDGE ;2U
Solar/Wind Harmer
3.6
274745AC1-111 GEN9
Adder
2.602
274682WAUKEGAN ;7U
Adder
8.309
274828WAUKEGAN ;BP
Adder
5.102
203835AF1-098 GEN
Solar/Wind Helper
1.429
203860AG1-193 C
Solar/Wind Helper
0.162
241966AE1-183 GEN
Solar/Wind Helper
0.141
274752CRETE EC ;2U
Adder
2.389
959141AF2-205 GEN
Solar/Wind Harmer
2.9
274826FISK ;BP
Adder
5.221
276772AC2-154 GEN
Solar/Wind Harmer
1.326
972228AH1-698 GEN2
Adder
1.756
939351AE1-166 GEN
Solar/Wind Harmer
2.793
970707AG2-453 GEN
Solar/Wind Harmer
13.179
274730ELWOOD EC;6P
Adder
7.738
970513AG2-328 GEN
Solar/Wind Harmer
8.386
970517AG2-330 GEN
Solar/Wind Harmer
7.606
254305AE2-115 C
Solar/Wind Helper
0.121
274753CRETE EC ;3U
Adder
2.389
964401AG1-302 GEN
Solar/Wind Harmer
4.421
972038AH1-567 GEN2
Adder
0.174
971617AH1-308 GEN
Solar/Wind Harmer
2.744
972236AH1-702 GEN2
Adder
0.99
274760LEE CO EC;1U
Adder
4.16
962511AG1-100 GEN
Solar/Wind Helper
0.371
959441AF2-235 GEN
Solar/Wind Helper
0.159
20334926Z1-069 C
Solar/Wind Helper
0.698
203854AF2-039 C
Solar/Wind Helper
0.151
274687WILL CNTY;4U
Adder
13.203
274731ELWOOD EC;2P
Adder
7.738
274733ELWOOD EC;3P
Adder
7.738
274746AC1-111 G10
Adder
2.602
241982AE2-343 S C
Solar/Wind Helper
0.127
254304AE2-114 C
Solar/Wind Helper
0.121
23888802TROY G4
50/50
1.842
960981AF2-389 GEN
Solar/Wind Harmer
0.888
247620Y3-023
Adder
0.266
270526AF1-158 GEN
Solar/Wind Harmer
2.491
971231AH1-075 GEN
Solar/Wind Harmer
0.437
24441505OLIV SLR
Solar/Wind Harmer
0.073
965791AG1-447 GEN
Solar/Wind Harmer
3.358
276843GEN-1.7
Solar/Wind Harmer
0.273
958011AF2-095 GEN
Solar/Wind Harmer
6.846
274695ROCKY RD ;2P
Adder
5.146
274765LEE CO EC;6U
Adder
4.169
274763LEE CO EC;4U
Adder
4.12
946381AF1-302 GEN
Solar/Wind Helper
0.114
238217AF1-153 C O1
Solar/Wind Helper
0.12
23906502RICHG2&3
Adder
1.43
270588AE1-091_GEN
Solar/Wind Harmer
7.618
247643Z2-116 C
Solar/Wind Harmer
0.04
270535AF1-215 GEN1
Solar/Wind Harmer
2.253
972181SS23-001
Solar/Wind Harmer
2.9
276806AD2-047 C O1
Solar/Wind Harmer
5.086
274676JOLIET 29;8U
Adder
13.951
274734ELWOOD EC;8P
Adder
7.738
274736ELWOOD EC;9P
Adder
7.738
274682WAUKEGAN ;7U
Adder
8.309
274767LEE CO EC;8U
Adder
4.111
203830AF1-094 GEN
Solar/Wind Helper
0.351
203818AF1-086 GEN
Solar/Wind Helper
0.773
943121AE2-341 GEN
Solar/Wind Harmer
2.169
943591AF1-030 GEN
Solar/Wind Harmer
1.446
23920202STRYCT
50/50
2.06
970515AG2-329 GEN
Solar/Wind Harmer
11.13
943021AE2-325 GEN
Solar/Wind Harmer
2.193
270223U2-072_GEN1
Solar/Wind Harmer
1.038
270578AF1-285 GEN2
Solar/Wind Harmer
0.635
970373AG2-245 GEN
Solar/Wind Harmer
10.614
971917AH1-482 GEN
Solar/Wind Harmer
4.412
941551AE2-152 GEN
Solar/Wind Harmer
2.137
274822ROCKFORD ;11
Adder
8.879
203954AE2-126 C
Solar/Wind Helper
0.236
24190002OREGON_ST1
50/50
3.613
971677AH1-339 GEN
Solar/Wind Harmer
7.68
965681AG1-436 GEN
Solar/Wind Harmer
6.563
270227U2-072_GEN3
Solar/Wind Harmer
1.038
270228U2-072_GEN4
Solar/Wind Harmer
1.038
270231U2-072_GEN5
Solar/Wind Harmer
1.038
274847GR RIDGE ;BU
Solar/Wind Harmer
2.368
247621Y3-024
Adder
0.105
203980AG1-197 GEN
Solar/Wind Helper
0.27
203979AG1-198 GEN
Solar/Wind Helper
0.21
241801AE1-079 GEN
Solar/Wind Helper
0.143
203853AF1-134 C O1
Solar/Wind Helper
0.223
990527J1329
External Queue
1.8554641008377075
991177J1571 G
External Queue
15.754436492919922
991182J1586 G
External Queue
25.351587295532227
990142J1224
External Queue
13.56344223022461
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.311
LGEELTFEXP_LGEE->PJM
CLTF
2.114
MECLTFEXP_MEC->PJM
CLTF
6.73
AH1-155LTFEXP_AH1-155->PJM
LTF
0.167
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.822
NYPJM->LTFIMP_NY
CLTF
2.183
TVALTFEXP_TVA->PJM
CLTF
2.348
AG2-052LTFEXP_AG2-052->PJM
LTF
0.111
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.294
CPLELTFEXP_CPLE->PJM
CLTF
0.34
SIGELTFEXP_SIGE->PJM
CLTF
0.176
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.312
WECLTFEXP_WEC->PJM
CLTF
1.725
LAGNLTFEXP_LAGN->PJM
CLTF
5.168

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_TE-345-010A_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_TE-345-010A_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.21 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2670.76
MW Contribution:2.97
Bus #Bus NameTypeMW Contribution
241996AE2-282_GEN
Solar/Wind Harmer
2.323
270007AE1-245 C
Solar/Wind Harmer
3.751
246938BC-WTG3
Solar/Wind Harmer
2.481
246937BC-WTG2
Solar/Wind Harmer
2.439
957891AF2-083 GEN
Solar/Wind Harmer
1.971
970611AG2-400 GEN
Solar/Wind Harmer
5.591
274808UNIV PK N;4U
Adder
2.396
942221AE2-234 GEN
Solar/Wind Harmer
0.347
274888KELLY CRK;1U
Solar/Wind Harmer
2.793
274770LINCOLN ;1U
Adder
2.932
274771LINCOLN ;2U
Adder
2.932
972259AH1-714 GEN
Adder
8.958
970321AG2-212 GEN
Solar/Wind Harmer
8.342
274696ROCKY RD ;4P
Adder
5.24
274697ROCKY RD ;3P
Adder
1.391
274762LEE CO EC;3U
Adder
4.138
25326509SID D
Adder
0.576
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
971989AH1-539 GEN
Solar/Wind Harmer
8.566
957201AF2-014 GEN
Solar/Wind Harmer
2.826
944161AF1-084 GEN
Solar/Wind Harmer
1.342
270302AB2-170 GEN
Solar/Wind Harmer
4.7
963791AG1-232 GEN
Solar/Wind Harmer
7
270536AF1-215 GEN2
Solar/Wind Harmer
2.241
958391AF2-133 GEN
Solar/Wind Harmer
4.359
274811UNIV PK N;7U
Adder
2.406
274827FISK ;RP
Adder
3.681
23867002DVBSG1
50/50
12.828
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
971549AH1-272 GEN
Solar/Wind Harmer
13.52
247607V1-011 GEN
Solar/Wind Harmer
2.5
270435AC2-044 GEN
Solar/Wind Harmer
1.246
971771AH1-392 GEN
Solar/Wind Harmer
5.011
971567AH1-282 GEN
Solar/Wind Harmer
8.27
971769AH1-391 GEN
Solar/Wind Harmer
5.428
270071AF1-092 GEN
Solar/Wind Harmer
7.347
274728ELWOOD EC;5P
Adder
7.698
24729505KEY G4
Adder
2.963
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241832AE2-181_GEN
Solar/Wind Harmer
2.105
270044AE2-322 C
Solar/Wind Harmer
0.919
24441205WTRV SLR C
Solar/Wind Harmer
0.084
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270485AE1-090_GEN
Solar/Wind Harmer
0.34
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270043AE2-236 GEN
Solar/Wind Harmer
2.896
274724RIVER EC ;11
Adder
8.546
274802UNIV PARK;5U
Adder
2.771
274800UNIV PARK;3U
Adder
2.762
970941AG2-585 GEN
Solar/Wind Harmer
5.913
274772LINCOLN ;3U
Adder
2.932
276897AD1-100 C
Solar/Wind Harmer
13.601
276893AG1-478 C
Solar/Wind Harmer
0.196
274729ELWOOD EC;1P
Adder
7.698
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
960841AF2-375 GEN
Solar/Wind Harmer
4.309
247522W1-056 GEN
Solar/Wind Harmer
1.78
246936BC-WTG1
Solar/Wind Harmer
2.439
270489AE1-102 GEN1
Solar/Wind Harmer
0.81
970905AG2-564 GEN
Solar/Wind Harmer
2.966
945111AF1-176 GEN
Solar/Wind Harmer
10.472
270505AE1-170 C O1
Solar/Wind Harmer
8.793
965011AG1-365 GEN
Solar/Wind Harmer
5.591
274751CRETE EC ;1U
Adder
2.377
964861AG1-349 GEN
Solar/Wind Harmer
3.804
274723RIVER EC ;12
Adder
8.649
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
4.826
971605AH1-302 GEN
Solar/Wind Harmer
4.126
274773LINCOLN ;4U
Adder
2.932
274774LINCOLN ;5U
Adder
2.932
274761LEE CO EC;2U
Adder
4.138
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
254303AC2-168 GEN
Solar/Wind Helper
0.081
945641AF1-229 GEN
Solar/Wind Harmer
3.679
965051AG1-369 GEN
Solar/Wind Harmer
2.91
270317AD1-130_GEN
Solar/Wind Harmer
1.802
971347AH1-153 GEN
Solar/Wind Harmer
7.804
972037AH1-567 GEN1
Adder
0.087
960591AF2-350 GEN
Solar/Wind Harmer
4.73
274775LINCOLN ;6U
Adder
2.932
274777LINCOLN ;8U
Adder
2.932
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
970833AG2-524 GEN
Solar/Wind Harmer
4.069
970833AG2-524 GEN
Solar/Wind Harmer
1.892
274823ROCKFORD ;21
Adder
8.769
203846AF2-130 C
Solar/Wind Helper
0.265
203855AF2-088 C
Solar/Wind Helper
0.072
23856402BAYSG1
50/50
1.434
241858AF1-205_GEN
Solar/Wind Harmer
5.929
241808AF1-120 C
Solar/Wind Harmer
1.295
972301AH1-735 GEN
Adder
7.125
270361_3
Solar/Wind Harmer
9.783
944231AF1-091 GEN
Solar/Wind Harmer
2.634
270063AE2-323 C
Solar/Wind Harmer
1.255
270462AD2-086
Solar/Wind Harmer
3.91
270391AF1-285 GEN3
Solar/Wind Harmer
0.63
274754CRETE EC ;4U
Adder
2.377
958381AF2-132 GEN
Solar/Wind Harmer
4.398
241847AF2-150_GEN
Solar/Wind Harmer
1.974
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
8.342
972235AH1-702 GEN1
Adder
1.133
274766LEE CO EC;7U
Adder
4.089
24189802OREGON_CT1
50/50
2.735
942801AE2-298 GEN
Solar/Wind Harmer
0.95
961051AF2-396 GEN
Solar/Wind Harmer
9.439
961051AF2-396 GEN
Solar/Wind Harmer
4.39
270216AD2-079_GEN
Solar/Wind Harmer
0.343
270224U2-072_GEN2
Solar/Wind Harmer
1.03
274803UNIV PARK;6U
Adder
2.771
274887GEN-1.85
Solar/Wind Harmer
2.521
274674JOLIET 9 ;6U
Adder
7.21
274693ROCKY RD ;1P
Adder
5.069
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
274764LEE CO EC;5U
Adder
4.148
972267AH1-718 GEN
Adder
1.84
203947AF1-006 C
Solar/Wind Helper
0.408
241967AE2-285_GEN
Solar/Wind Helper
0.362
20398826ARMNA MT
Solar/Wind Helper
0.704
972227AH1-698 GEN1
Adder
1.23
270024AE2-089 GEN
Solar/Wind Harmer
2.202
274735ELWOOD EC;4P
Adder
7.698
274744AC1-111 GEN8
Adder
2.589
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
24189902OREGON_CT2
50/50
2.68
241807AE2-176_GEN
Solar/Wind Harmer
7.294
241840AF1-064_GEN
Solar/Wind Harmer
1.525
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270428AC2-015 C
Solar/Wind Harmer
4.168
965421AG1-410 GEN
Solar/Wind Harmer
18.512
24695305TIMB G C
Solar/Wind Harmer
3.326
270449AD2-020 GEN
Solar/Wind Harmer
1.68
247521TR3_G114
Solar/Wind Harmer
1.96
270246TR4_N_V150
Solar/Wind Harmer
0.496
24639705ELKHART HY
Adder
0.088
270055AF2-134 C O1
Solar/Wind Harmer
1.494
274812UNIV PK N;8U
Adder
2.406
270541AE2-072 C
Solar/Wind Harmer
4.728
270404AC1-167 GEN
Solar/Wind Harmer
0.766
247604X1-042
Adder
0.267
958091AF2-103 GEN
Solar/Wind Harmer
0.102
270247TR4_N_V136
Solar/Wind Harmer
0.496
970031AG2-029 GEN
Solar/Wind Harmer
17.036
270377AD1-106 GEN
Solar/Wind Harmer
3.313
942871AE2-306 GEN
Solar/Wind Harmer
0.472
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
7.804
972231SS25-0005
Solar/Wind Harmer
4.616
274752CRETE EC ;2U
Adder
2.377
959141AF2-205 GEN
Solar/Wind Harmer
2.885
274826FISK ;BP
Adder
5.194
276772AC2-154 GEN
Solar/Wind Harmer
1.319
972228AH1-698 GEN2
Adder
1.747
939351AE1-166 GEN
Solar/Wind Harmer
2.779
970707AG2-453 GEN
Solar/Wind Harmer
13.112
274730ELWOOD EC;6P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
8.342
970517AG2-330 GEN
Solar/Wind Harmer
7.566
254305AE2-115 C
Solar/Wind Helper
0.12
23929302BS-PKR
50/50
2.524
958321AF2-126 GEN
Solar/Wind Harmer
1.635
270575GUS2 35KV
Solar/Wind Harmer
11.525
970217AG2-149 GEN
Solar/Wind Harmer
24.176
270258AD1-119 GEN
Solar/Wind Harmer
1.871
270491AE1-102 GEN2
Solar/Wind Harmer
0.81
270191TR4_S_V150
Solar/Wind Harmer
1.748
24642205MAYFLWER
Adder
0.363
959331AF2-224 GEN
Solar/Wind Harmer
5.591
274753CRETE EC ;3U
Adder
2.377
964401AG1-302 GEN
Solar/Wind Harmer
4.398
961961AG1-039 GEN
Solar/Wind Harmer
1.361
972038AH1-567 GEN2
Adder
0.173
971617AH1-308 GEN
Solar/Wind Harmer
2.727
972236AH1-702 GEN2
Adder
0.985
274760LEE CO EC;1U
Adder
4.138
962511AG1-100 GEN
Solar/Wind Helper
0.366
959441AF2-235 GEN
Solar/Wind Helper
0.157
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
972211AH1-690 GEN
50/50
288.97
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
15.756
945411AF1-206 GEN
Solar/Wind Harmer
8.678
270499AE1-146 GEN
Solar/Wind Harmer
2.698
270297AD1-101 GEN
Solar/Wind Harmer
2.073
966831AG1-554 GEN
Solar/Wind Harmer
0.792
965041AG1-368 GEN
Solar/Wind Harmer
5.854
960681AF2-359 GEN
Solar/Wind Harmer
1.974
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274776LINCOLN ;7U
Adder
2.932
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274746AC1-111 G10
Adder
2.589
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
23888802TROY G4
50/50
1.837
960981AF2-389 GEN
Solar/Wind Harmer
0.884
247620Y3-023
Adder
0.264
270526AF1-158 GEN
Solar/Wind Harmer
2.479
24441505OLIV SLR
Solar/Wind Harmer
0.073
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965791AG1-447 GEN
Solar/Wind Harmer
3.341
276843GEN-1.7
Solar/Wind Harmer
0.271
958011AF2-095 GEN
Solar/Wind Harmer
6.812
274695ROCKY RD ;2P
Adder
5.12
274765LEE CO EC;6U
Adder
4.148
274763LEE CO EC;4U
Adder
4.099
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
276164X3-005 C
Solar/Wind Harmer
0.336
276776AD2-060 GEN
Solar/Wind Harmer
0.2
972207SS24-0001
Solar/Wind Harmer
10.423
274676JOLIET 29;8U
Adder
14.394
274871GR RIDGE ;2U
Solar/Wind Harmer
3.581
274745AC1-111 GEN9
Adder
2.589
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
23906502RICHG2&3
Adder
1.423
270588AE1-091_GEN
Solar/Wind Harmer
7.54
247643Z2-116 C
Solar/Wind Harmer
0.039
270535AF1-215 GEN1
Solar/Wind Harmer
2.241
972181SS23-001
Solar/Wind Harmer
2.885
276806AD2-047 C O1
Solar/Wind Harmer
5.06
274676JOLIET 29;8U
Adder
13.879
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
274682WAUKEGAN ;7U
Adder
8.266
274767LEE CO EC;8U
Adder
4.089
203830AF1-094 GEN
Solar/Wind Helper
0.347
943121AE2-341 GEN
Solar/Wind Harmer
5.427
943591AF1-030 GEN
Solar/Wind Harmer
3.618
23920202STRYCT
50/50
2.052
970515AG2-329 GEN
Solar/Wind Harmer
10.964
943021AE2-325 GEN
Solar/Wind Harmer
2.182
270223U2-072_GEN1
Solar/Wind Harmer
1.03
270578AF1-285 GEN2
Solar/Wind Harmer
0.63
970373AG2-245 GEN
Solar/Wind Harmer
10.561
971917AH1-482 GEN
Solar/Wind Harmer
4.39
941551AE2-152 GEN
Solar/Wind Harmer
2.126
274822ROCKFORD ;11
Adder
8.833
203954AE2-126 C
Solar/Wind Helper
0.233
24190002OREGON_ST1
50/50
3.605
971677AH1-339 GEN
Solar/Wind Harmer
7.59
965681AG1-436 GEN
Solar/Wind Harmer
6.531
270227U2-072_GEN3
Solar/Wind Harmer
1.03
270228U2-072_GEN4
Solar/Wind Harmer
1.03
270231U2-072_GEN5
Solar/Wind Harmer
1.03
274847GR RIDGE ;BU
Solar/Wind Harmer
2.356
247621Y3-024
Adder
0.105
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241801AE1-079 GEN
Solar/Wind Helper
0.141
990527J1329
External Queue
1.8513455390930176
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990142J1224
External Queue
13.53333568572998
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
CPLELTFEXP_CPLE->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.175
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
WECLTFEXP_WEC->PJM
CLTF
1.716
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
LGEELTFEXP_LGEE->PJM
CLTF
2.101
MECLTFEXP_MEC->PJM
CLTF
6.695
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
NYPJM->LTFIMP_NY
CLTF
2.158
TVALTFEXP_TVA->PJM
CLTF
2.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-825_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-825_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:136.05 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2554.95
MW Contribution:2.27
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.836
972253AH1-711 GEN
50/50
56.068
23860302FRMENG 3
50/50
3.538
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.564
970905AG2-564 GEN
Solar/Wind Harmer
2.266
945111AF1-176 GEN
Solar/Wind Harmer
7.294
270505AE1-170 C O1
Solar/Wind Harmer
4.287
965011AG1-365 GEN
Solar/Wind Harmer
3.894
274751CRETE EC ;1U
Adder
4
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.632
274801UNIV PARK;4U
Adder
2.756
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.118
274773LINCOLN ;4U
Adder
3.982
274774LINCOLN ;5U
Adder
3.982
971997AH1-543 GEN
Solar/Wind Harmer
1.662
276861AD2-134 GEN
Solar/Wind Harmer
0.057
970569AG2-363 GEN
Solar/Wind Harmer
9.385
274761LEE CO EC;2U
Adder
4.129
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.328
939741AE1-205 GEN
Solar/Wind Harmer
4.276
945371AF1-202 GEN
Solar/Wind Harmer
0
961971AG1-040 GEN
Solar/Wind Helper
0.359
254303AC2-168 GEN
Solar/Wind Helper
0.081
23888802TROY G4
50/50
1.836
247620Y3-023
Adder
0.264
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.428
965791AG1-447 GEN
Solar/Wind Harmer
3.335
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.742
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.598
274695ROCKY RD ;2P
Adder
5.109
958491AF2-143 GEN
Solar/Wind Harmer
4.791
942991AE2-321 GEN
Solar/Wind Harmer
3.534
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.305
274765LEE CO EC;6U
Adder
4.139
274763LEE CO EC;4U
Adder
4.09
944541AF1-119 GEN
Solar/Wind Harmer
0.207
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
970329AG2-216 GEN
Solar/Wind Harmer
1.305
270031AE2-169
Solar/Wind Harmer
1.66
946381AF1-302 GEN
Solar/Wind Helper
0.113
238217AF1-153 C O1
Solar/Wind Helper
0.119
241996AE2-282_GEN
Solar/Wind Harmer
0.006
970621AG2-405 GEN
Solar/Wind Harmer
0.95
970623AG2-406 GEN
Solar/Wind Harmer
0.856
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.157
246937BC-WTG2
Solar/Wind Harmer
0.176
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.894
274808UNIV PK N;4U
Adder
2.391
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.193
274770LINCOLN ;1U
Adder
3.982
274771LINCOLN ;2U
Adder
3.982
972259AH1-714 GEN
Adder
8.939
970321AG2-212 GEN
Solar/Wind Harmer
1.409
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.229
274697ROCKY RD ;3P
Adder
1.388
962691AG1-118 GEN
Solar/Wind Harmer
9.548
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.759
274762LEE CO EC;3U
Adder
4.129
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
253378AE2-206_GEN
Solar/Wind Harmer
0.002
241985AE1-237 GEN
Solar/Wind Helper
0.141
962101AG1-054 GEN
Solar/Wind Helper
0.35
24189802OREGON_CT1
50/50
2.733
961051AF2-396 GEN
Solar/Wind Harmer
8.284
961051AF2-396 GEN
Solar/Wind Harmer
5.523
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.168
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.765
274887GEN-1.85
Solar/Wind Harmer
0.087
274674JOLIET 9 ;6U
Adder
7.195
958481AF2-142 GEN
Solar/Wind Harmer
4.833
274862TOP CROP ;2U
Solar/Wind Harmer
0.436
274693ROCKY RD ;1P
Adder
5.059
274683WAUKEGAN ;8U
Adder
9.663
274683WAUKEGAN ;8U
Adder
8.145
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.177
970921AG2-575 GEN
Solar/Wind Harmer
1.059
971335AH1-147 GEN
Solar/Wind Harmer
6.305
274764LEE CO EC;5U
Adder
4.139
966841AG1-555 GEN
Solar/Wind Harmer
0.35
960971AF2-388 GEN
Solar/Wind Harmer
1.815
276708O09 GEN2
Solar/Wind Harmer
0.109
276782AC1-033 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
1.007
270599AE1-208 GEN
Solar/Wind Harmer
2.766
203947AF1-006 C
Solar/Wind Helper
0.409
241967AE2-285_GEN
Solar/Wind Helper
0.363
20398826ARMNA MT
Solar/Wind Helper
0.706
24189902OREGON_CT2
50/50
2.678
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.424
23906502RICHG2&3
Adder
1.422
270428AC2-015 C
Solar/Wind Harmer
0.003
965421AG1-410 GEN
Solar/Wind Harmer
12.895
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.087
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.401
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.344
274676JOLIET 29;8U
Adder
14.364
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.583
274682WAUKEGAN ;7U
Adder
8.249
274828WAUKEGAN ;BP
Adder
5.065
276901AD2-066 C O1
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
9.419
965651AG1-433 GEN
Solar/Wind Harmer
0.908
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
203835AF1-098 GEN
Solar/Wind Helper
1.414
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
972211AH1-690 GEN
50/50
288.807
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.986
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
4.077
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274814UNIV PK N;0U
Adder
2.422
274807UNIV PK N;3U
Adder
2.417
274805UNIV PK N;1U
Adder
2.407
274776LINCOLN ;7U
Adder
3.982
274687WILL CNTY;4U
Adder
13.109
274687WILL CNTY;4U
Adder
13.109
274731ELWOOD EC;2P
Adder
7.682
274733ELWOOD EC;3P
Adder
7.682
274746AC1-111 G10
Adder
2.583
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.531
24386205FR-12G C
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
3.066
276655WTG1_EQ
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
1.315
971609AH1-304 GEN
Solar/Wind Harmer
0.493
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
971989AH1-539 GEN
Solar/Wind Harmer
1.989
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.55
963791AG1-232 GEN
Solar/Wind Harmer
4.874
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
2.401
274827FISK ;RP
Adder
3.674
972227AH1-698 GEN1
Adder
1.228
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274735ELWOOD EC;4P
Adder
7.682
274744AC1-111 GEN8
Adder
2.583
970169AG2-114 GEN
Solar/Wind Harmer
3.123
961011AF2-392 GEN
Solar/Wind Harmer
1.808
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
3.207
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.928
23929302BS-PKR
50/50
2.523
958321AF2-126 GEN
Solar/Wind Harmer
1.267
270575GUS2 35KV
Solar/Wind Harmer
5.343
970217AG2-149 GEN
Solar/Wind Harmer
4.562
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.564
270191TR4_S_V150
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.362
959331AF2-224 GEN
Solar/Wind Harmer
2.726
274753CRETE EC ;3U
Adder
4
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.173
971617AH1-308 GEN
Solar/Wind Harmer
2.722
274872LEEDK;1U
Solar/Wind Harmer
0.116
972236AH1-702 GEN2
Adder
0.983
274760LEE CO EC;1U
Adder
4.129
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
965091AG1-374 GEN
Solar/Wind Harmer
9.061
965931AG1-462 GEN
Solar/Wind Harmer
7.661
962511AG1-100 GEN
Solar/Wind Helper
0.367
959441AF2-235 GEN
Solar/Wind Helper
0.158
20334926Z1-069 C
Solar/Wind Helper
0.691
203854AF2-039 C
Solar/Wind Helper
0.15
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.837
965051AG1-369 GEN
Solar/Wind Harmer
2.027
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
5.434
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.961
960591AF2-350 GEN
Solar/Wind Harmer
3.293
274775LINCOLN ;6U
Adder
3.982
274777LINCOLN ;8U
Adder
3.982
274675JOLIET 29;7U
Adder
14.364
274675JOLIET 29;7U
Adder
13.851
970833AG2-524 GEN
Solar/Wind Harmer
3.569
970833AG2-524 GEN
Solar/Wind Harmer
2.379
276868AE1-113 GEN
Solar/Wind Harmer
0.638
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.733
971675AH1-338 GEN
Solar/Wind Harmer
1.229
971171AH1-044 GEN
Solar/Wind Harmer
6.279
274823ROCKFORD ;21
Adder
8.75
24386405FR-21G C
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.545
946321AF1-296 GEN
Solar/Wind Harmer
1.689
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.266
203855AF2-088 C
Solar/Wind Helper
0.072
270541AE2-072 C
Solar/Wind Harmer
0.009
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.266
270247TR4_N_V136
Solar/Wind Harmer
0.026
970031AG2-029 GEN
Solar/Wind Harmer
2.571
270377AD1-106 GEN
Solar/Wind Harmer
1.42
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.434
274752CRETE EC ;2U
Adder
4
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.184
972228AH1-698 GEN2
Adder
1.743
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.682
970707AG2-453 GEN
Solar/Wind Harmer
10.65
970513AG2-328 GEN
Solar/Wind Harmer
1.409
970517AG2-330 GEN
Solar/Wind Harmer
8.456
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.389
970781AG2-491 GEN
Solar/Wind Harmer
3.176
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.007
254305AE2-115 C
Solar/Wind Helper
0.12
23867002DVBSG1
50/50
12.822
23888502TROY G1
50/50
1.836
23888602TROY G2
50/50
1.836
23860102FRMENG 1
50/50
1.733
23860202FRMENG 2
50/50
1.733
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
971549AH1-272 GEN
Solar/Wind Harmer
10.515
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.55
971771AH1-392 GEN
Solar/Wind Harmer
3.877
971567AH1-282 GEN
Solar/Wind Harmer
5.76
971769AH1-391 GEN
Solar/Wind Harmer
4.221
270071AF1-092 GEN
Solar/Wind Harmer
6.537
274728ELWOOD EC;5P
Adder
7.682
24729505KEY G4
Adder
2.957
24691005MDL-2G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
1.951
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.102
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.313
270485AE1-090_GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
1.298
270043AE2-236 GEN
Solar/Wind Harmer
2.353
274724RIVER EC ;11
Adder
8.529
274802UNIV PARK;5U
Adder
2.765
274800UNIV PARK;3U
Adder
2.756
970941AG2-585 GEN
Solar/Wind Harmer
4.117
274772LINCOLN ;3U
Adder
3.982
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.129
274729ELWOOD EC;1P
Adder
7.682
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.336
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
970571AG2-364 GEN
Solar/Wind Harmer
6.257
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.497
942111AE2-223 GEN
Solar/Wind Harmer
0.993
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.58
23856402BAYSG1
50/50
1.433
241858AF1-205_GEN
Solar/Wind Harmer
4.134
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
7.119
270361_3
Solar/Wind Harmer
5.343
944231AF1-091 GEN
Solar/Wind Harmer
1.299
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
4
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.682
274674JOLIET 9 ;6U
Adder
7.195
970245AG2-165 GEN
Solar/Wind Harmer
1.409
939401AE1-172 GEN
Solar/Wind Harmer
2.382
962781AG1-127 GEN
Solar/Wind Harmer
3.024
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.13
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
0.439
24385905FR-11G C
Solar/Wind Harmer
0.001
23906502RICHG2&3
Adder
1.422
270588AE1-091_GEN
Solar/Wind Harmer
3.735
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.866
274676JOLIET 29;8U
Adder
13.851
274734ELWOOD EC;8P
Adder
7.682
274736ELWOOD EC;9P
Adder
7.682
943121AE2-341 GEN
Solar/Wind Harmer
5.404
943591AF1-030 GEN
Solar/Wind Harmer
3.594
274682WAUKEGAN ;7U
Adder
8.249
24755605MDL-5G
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
6.279
247642Z2-115 C
Solar/Wind Harmer
0.001
203830AF1-094 GEN
Solar/Wind Helper
0.347
24190002OREGON_ST1
50/50
3.603
971677AH1-339 GEN
Solar/Wind Harmer
0.745
965681AG1-436 GEN
Solar/Wind Harmer
4.548
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.279
971343AH1-151 GEN
Solar/Wind Harmer
6.279
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.109
276820AF1-078_GEN
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241801AE1-079 GEN
Solar/Wind Helper
0.141
203853AF1-134 C O1
Solar/Wind Helper
0.221
23920202STRYCT
50/50
2.05
970515AG2-329 GEN
Solar/Wind Harmer
13.687
943021AE2-325 GEN
Solar/Wind Harmer
2.179
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.354
971917AH1-482 GEN
Solar/Wind Harmer
4.381
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.39
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
959081AF2-199 GEN
Solar/Wind Harmer
3.14
971067AG2-660 GEN
Solar/Wind Harmer
1.047
274822ROCKFORD ;11
Adder
8.814
970819AG2-516 GEN
Solar/Wind Harmer
3.745
971475AH1-234 GEN
Solar/Wind Harmer
1.512
276726Z2-087_GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
203954AE2-126 C
Solar/Wind Helper
0.234
990527J1329
External Queue
1.8513455390930176
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990142J1224
External Queue
13.53333568572998
CBM West 2LTFEXP_CBM-W2->PJM
CBM
40.959
LGEELTFEXP_LGEE->PJM
CLTF
2.094
MECLTFEXP_MEC->PJM
CLTF
6.679
AH1-155LTFEXP_AH1-155->PJM
LTF
0.165
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.287
NYPJM->LTFIMP_NY
CLTF
2.164
TVALTFEXP_TVA->PJM
CLTF
2.326
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.262
CPLELTFEXP_CPLE->PJM
CLTF
0.333
SIGELTFEXP_SIGE->PJM
CLTF
0.174
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.224
WECLTFEXP_WEC->PJM
CLTF
1.712
LAGNLTFEXP_LAGN->PJM
CLTF
5.122

Details for 02HAYES-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-824_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
02HAYES-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-824_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:135.68 %
Rating:1878.0 MVA
Rating Type:B
MVA to Mitigate:2548.09
MW Contribution:2.27
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.837
972253AH1-711 GEN
50/50
56.101
23860302FRMENG 3
50/50
3.54
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.176
270489AE1-102 GEN1
Solar/Wind Harmer
0.565
970905AG2-564 GEN
Solar/Wind Harmer
2.27
945111AF1-176 GEN
Solar/Wind Harmer
7.306
270505AE1-170 C O1
Solar/Wind Harmer
4.294
965011AG1-365 GEN
Solar/Wind Harmer
3.901
274751CRETE EC ;1U
Adder
4.008
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.649
274801UNIV PARK;4U
Adder
2.762
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
4.126
274773LINCOLN ;4U
Adder
3.991
274774LINCOLN ;5U
Adder
3.991
971997AH1-543 GEN
Solar/Wind Harmer
1.665
276861AD2-134 GEN
Solar/Wind Harmer
0.057
970569AG2-363 GEN
Solar/Wind Harmer
9.405
274761LEE CO EC;2U
Adder
4.138
24387305FR-4G C
Solar/Wind Harmer
0.001
276158O29GEN2
Solar/Wind Harmer
0
958861AF2-177 GEN
Solar/Wind Harmer
1.331
939741AE1-205 GEN
Solar/Wind Harmer
4.286
945371AF1-202 GEN
Solar/Wind Harmer
0
241885AC2-103 GEN1
Solar/Wind Helper
4.614
961971AG1-040 GEN
Solar/Wind Helper
0.358
254303AC2-168 GEN
Solar/Wind Helper
0.081
23888802TROY G4
50/50
1.837
247620Y3-023
Adder
0.264
270526AF1-158 GEN
Solar/Wind Harmer
0.005
24441505OLIV SLR
Solar/Wind Harmer
0
971231AH1-075 GEN
Solar/Wind Harmer
0.429
965791AG1-447 GEN
Solar/Wind Harmer
3.341
276843GEN-1.7
Solar/Wind Harmer
0.107
958011AF2-095 GEN
Solar/Wind Harmer
4.752
274861TOP CROP ;1U
Solar/Wind Harmer
0.001
945421AF1-207 GEN
Solar/Wind Harmer
0
971573AH1-285 GEN
Solar/Wind Harmer
0.6
274695ROCKY RD ;2P
Adder
5.12
958491AF2-143 GEN
Solar/Wind Harmer
4.801
942991AE2-321 GEN
Solar/Wind Harmer
3.541
276872AE1-163_GEN1
Solar/Wind Harmer
0.001
971333AH1-146 GEN
Solar/Wind Harmer
6.319
274765LEE CO EC;6U
Adder
4.148
274763LEE CO EC;4U
Adder
4.099
944541AF1-119 GEN
Solar/Wind Harmer
0.208
274851PROVIDENC;RU
Solar/Wind Harmer
0
276646AC1-214 GEN2
Solar/Wind Harmer
0.121
270201AC2-176 GEN
Solar/Wind Harmer
0.001
964611AG1-324 GEN
Solar/Wind Harmer
0.227
970329AG2-216 GEN
Solar/Wind Harmer
1.308
270031AE2-169
Solar/Wind Harmer
1.663
946381AF1-302 GEN
Solar/Wind Helper
0.112
238217AF1-153 C O1
Solar/Wind Helper
0.119
241996AE2-282_GEN
Solar/Wind Harmer
0.006
970621AG2-405 GEN
Solar/Wind Harmer
0.951
970623AG2-406 GEN
Solar/Wind Harmer
0.857
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.158
246937BC-WTG2
Solar/Wind Harmer
0.176
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.901
274808UNIV PK N;4U
Adder
2.396
942221AE2-234 GEN
Solar/Wind Harmer
0.017
274888KELLY CRK;1U
Solar/Wind Harmer
0.194
274770LINCOLN ;1U
Adder
3.991
274771LINCOLN ;2U
Adder
3.991
972259AH1-714 GEN
Adder
8.958
970321AG2-212 GEN
Solar/Wind Harmer
1.412
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274696ROCKY RD ;4P
Adder
5.24
274697ROCKY RD ;3P
Adder
1.391
962691AG1-118 GEN
Solar/Wind Harmer
9.569
274856ECOGROVE ;U1
Solar/Wind Harmer
0.074
276611AD2-172 GEN
Solar/Wind Harmer
0.001
938861AE1-114 GEN
Solar/Wind Harmer
1.763
274762LEE CO EC;3U
Adder
4.138
276603SUBLETTE C
Solar/Wind Harmer
0
276645AC1-214 GEN1
Solar/Wind Harmer
0.121
253378AE2-206_GEN
Solar/Wind Harmer
0.002
241985AE1-237 GEN
Solar/Wind Helper
0.14
962101AG1-054 GEN
Solar/Wind Helper
0.35
24189802OREGON_CT1
50/50
2.735
961051AF2-396 GEN
Solar/Wind Harmer
8.298
961051AF2-396 GEN
Solar/Wind Harmer
5.532
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.17
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.771
274887GEN-1.85
Solar/Wind Harmer
0.087
274674JOLIET 9 ;6U
Adder
7.21
958481AF2-142 GEN
Solar/Wind Harmer
4.844
274862TOP CROP ;2U
Solar/Wind Harmer
0.437
274693ROCKY RD ;1P
Adder
5.069
274683WAUKEGAN ;8U
Adder
9.683
274683WAUKEGAN ;8U
Adder
8.163
274879MINONK ;1U
Solar/Wind Harmer
0.134
970921AG2-575 GEN
Solar/Wind Harmer
3.184
970921AG2-575 GEN
Solar/Wind Harmer
1.061
971335AH1-147 GEN
Solar/Wind Harmer
6.319
274764LEE CO EC;5U
Adder
4.148
966841AG1-555 GEN
Solar/Wind Harmer
0.351
960971AF2-388 GEN
Solar/Wind Harmer
1.819
276708O09 GEN2
Solar/Wind Harmer
0.11
276782AC1-033 GEN
Solar/Wind Harmer
0
960611AF2-352 GEN
Solar/Wind Harmer
1.009
270599AE1-208 GEN
Solar/Wind Harmer
2.772
203947AF1-006 C
Solar/Wind Helper
0.408
241967AE2-285_GEN
Solar/Wind Helper
0.362
20398826ARMNA MT
Solar/Wind Helper
0.704
24189902OREGON_CT2
50/50
2.68
241807AE2-176_GEN
Solar/Wind Harmer
0.009
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.425
23906502RICHG2&3
Adder
1.423
270428AC2-015 C
Solar/Wind Harmer
0.003
965421AG1-410 GEN
Solar/Wind Harmer
12.915
24695305TIMB G C
Solar/Wind Harmer
0.001
270449AD2-020 GEN
Solar/Wind Harmer
0
247521TR3_G114
Solar/Wind Harmer
0.148
270246TR4_N_V150
Solar/Wind Harmer
0.026
24639705ELKHART HY
Adder
0.088
270055AF2-134 C O1
Solar/Wind Harmer
0.003
274812UNIV PK N;8U
Adder
2.406
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.345
274676JOLIET 29;8U
Adder
14.394
274871GR RIDGE ;2U
Solar/Wind Harmer
0
274745AC1-111 GEN9
Adder
2.589
274682WAUKEGAN ;7U
Adder
8.266
274828WAUKEGAN ;BP
Adder
5.076
276901AD2-066 C O1
Solar/Wind Harmer
0.003
957471AF2-041 GEN
Solar/Wind Harmer
9.44
965651AG1-433 GEN
Solar/Wind Harmer
0.909
274877BISHOP HL;1U
Solar/Wind Harmer
0.103
203835AF1-098 GEN
Solar/Wind Helper
1.412
203860AG1-193 C
Solar/Wind Helper
0.16
241966AE1-183 GEN
Solar/Wind Helper
0.139
972211AH1-690 GEN
50/50
288.97
24191202EL_AA1-006
50/50
0.334
970817AG2-515 GEN
Solar/Wind Harmer
10.993
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.033
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
4.084
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.242
274814UNIV PK N;0U
Adder
2.427
274807UNIV PK N;3U
Adder
2.422
274805UNIV PK N;1U
Adder
2.412
274776LINCOLN ;7U
Adder
3.991
274687WILL CNTY;4U
Adder
13.136
274687WILL CNTY;4U
Adder
13.136
274731ELWOOD EC;2P
Adder
7.698
274733ELWOOD EC;3P
Adder
7.698
274746AC1-111 G10
Adder
2.589
276882AE2-255 GEN
Solar/Wind Harmer
0.372
24690905MDL-1G C
Solar/Wind Harmer
0.001
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0
926823AC1-168 GEN
Solar/Wind Harmer
0.532
24386205FR-12G C
Solar/Wind Harmer
0
965101AG1-375 GEN
Solar/Wind Harmer
3.072
276655WTG1_EQ
Solar/Wind Harmer
0.001
963841AG1-237 GEN
Solar/Wind Harmer
1.318
971609AH1-304 GEN
Solar/Wind Harmer
0.494
241982AE2-343 S C
Solar/Wind Helper
0.126
254304AE2-114 C
Solar/Wind Helper
0.12
971989AH1-539 GEN
Solar/Wind Harmer
1.992
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.551
963791AG1-232 GEN
Solar/Wind Harmer
4.883
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
2.406
274827FISK ;RP
Adder
3.681
972227AH1-698 GEN1
Adder
1.23
270024AE2-089 GEN
Solar/Wind Harmer
0.004
274735ELWOOD EC;4P
Adder
7.698
274744AC1-111 GEN8
Adder
2.589
970169AG2-114 GEN
Solar/Wind Harmer
3.129
961011AF2-392 GEN
Solar/Wind Harmer
1.812
274848CAMPGROVE;RU
Solar/Wind Harmer
0.001
959341AF2-225 GEN
Solar/Wind Harmer
3.214
241997AF1-093 GEN
Solar/Wind Helper
0.139
203804AE2-113_GEN
Solar/Wind Helper
0.926
23929302BS-PKR
50/50
2.524
958321AF2-126 GEN
Solar/Wind Harmer
1.268
270575GUS2 35KV
Solar/Wind Harmer
5.347
970217AG2-149 GEN
Solar/Wind Harmer
4.568
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.565
270191TR4_S_V150
Solar/Wind Harmer
0.001
24642205MAYFLWER
Adder
0.363
959331AF2-224 GEN
Solar/Wind Harmer
2.73
274753CRETE EC ;3U
Adder
4.008
964401AG1-302 GEN
Solar/Wind Harmer
0.001
972038AH1-567 GEN2
Adder
0.173
971617AH1-308 GEN
Solar/Wind Harmer
2.727
274872LEEDK;1U
Solar/Wind Harmer
0.117
972236AH1-702 GEN2
Adder
0.985
274760LEE CO EC;1U
Adder
4.138
274878BISHOP HL;2U
Solar/Wind Harmer
0.103
965091AG1-374 GEN
Solar/Wind Harmer
9.081
965931AG1-462 GEN
Solar/Wind Harmer
7.678
962511AG1-100 GEN
Solar/Wind Helper
0.366
959441AF2-235 GEN
Solar/Wind Helper
0.157
20334926Z1-069 C
Solar/Wind Helper
0.689
203854AF2-039 C
Solar/Wind Helper
0.149
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.84
965051AG1-369 GEN
Solar/Wind Harmer
2.03
270317AD1-130_GEN
Solar/Wind Harmer
0.006
971347AH1-153 GEN
Solar/Wind Harmer
5.444
972037AH1-567 GEN1
Adder
0.087
971611AH1-305 GEN
Solar/Wind Harmer
1.965
960591AF2-350 GEN
Solar/Wind Harmer
3.3
274775LINCOLN ;6U
Adder
3.991
274777LINCOLN ;8U
Adder
3.991
274675JOLIET 29;7U
Adder
14.394
274675JOLIET 29;7U
Adder
13.88
970833AG2-524 GEN
Solar/Wind Harmer
3.577
970833AG2-524 GEN
Solar/Wind Harmer
2.384
276868AE1-113 GEN
Solar/Wind Harmer
0.639
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
971411AH1-196 GEN
Solar/Wind Harmer
4.743
971675AH1-338 GEN
Solar/Wind Harmer
1.232
971171AH1-044 GEN
Solar/Wind Harmer
6.293
274823ROCKFORD ;21
Adder
8.769
24386405FR-21G C
Solar/Wind Harmer
0
276656WTG2_EQ
Solar/Wind Harmer
0
941731AE2-173 GEN
Solar/Wind Harmer
2.551
946321AF1-296 GEN
Solar/Wind Harmer
1.693
945581AF1-223 GEN
Solar/Wind Harmer
0
203846AF2-130 C
Solar/Wind Helper
0.265
203855AF2-088 C
Solar/Wind Helper
0.072
270541AE2-072 C
Solar/Wind Harmer
0.009
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.267
270247TR4_N_V136
Solar/Wind Harmer
0.026
970031AG2-029 GEN
Solar/Wind Harmer
2.575
270377AD1-106 GEN
Solar/Wind Harmer
1.422
270391AF1-285 GEN3
Solar/Wind Harmer
0.242
970349AG2-230 GEN
Solar/Wind Harmer
5.444
274752CRETE EC ;2U
Adder
4.008
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
5.194
972228AH1-698 GEN2
Adder
1.747
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
10.672
274730ELWOOD EC;6P
Adder
7.698
970513AG2-328 GEN
Solar/Wind Harmer
1.412
970517AG2-330 GEN
Solar/Wind Harmer
8.474
276694AA1-018 GEN2
Solar/Wind Harmer
0
944531AF1-118 GEN
Solar/Wind Harmer
14.419
970781AG2-491 GEN
Solar/Wind Harmer
3.183
274855GSG-6 ;RU
Solar/Wind Harmer
0.116
274853TWINGROVE;U1
Solar/Wind Harmer
0.001
959611AF2-252 GEN
Solar/Wind Harmer
1.009
254305AE2-115 C
Solar/Wind Helper
0.12
23867002DVBSG1
50/50
12.828
23888502TROY G1
50/50
1.837
23888602TROY G2
50/50
1.837
23860102FRMENG 1
50/50
1.734
23860202FRMENG 2
50/50
1.734
971549AH1-272 GEN
Solar/Wind Harmer
10.529
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.551
971771AH1-392 GEN
Solar/Wind Harmer
3.884
971567AH1-282 GEN
Solar/Wind Harmer
5.77
971769AH1-391 GEN
Solar/Wind Harmer
4.229
270071AF1-092 GEN
Solar/Wind Harmer
6.55
274728ELWOOD EC;5P
Adder
7.698
24729505KEY G4
Adder
2.963
24691005MDL-2G C
Solar/Wind Harmer
0.001
971177AH1-047 GEN
Solar/Wind Harmer
1.955
274863CRW1-WTG
Solar/Wind Harmer
0.001
274864CRW2-WTG
Solar/Wind Harmer
0.001
276612AE2-035 GEN
Solar/Wind Harmer
0.001
971681AH1-341 GEN
Solar/Wind Harmer
5.011
24386605FR-22G C
Solar/Wind Harmer
0
24387005FR-3G C
Solar/Wind Harmer
0.001
957751AF2-069 GEN
Solar/Wind Harmer
0.102
241886AC2-103 GEN2
Solar/Wind Helper
4.614
241832AE2-181_GEN
Solar/Wind Harmer
0.004
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.319
270485AE1-090_GEN
Solar/Wind Harmer
0.001
965021AG1-366 GEN
Solar/Wind Harmer
1.3
270043AE2-236 GEN
Solar/Wind Harmer
2.357
274724RIVER EC ;11
Adder
8.546
274802UNIV PARK;5U
Adder
2.771
274800UNIV PARK;3U
Adder
2.762
970941AG2-585 GEN
Solar/Wind Harmer
4.125
274772LINCOLN ;3U
Adder
3.991
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.13
274729ELWOOD EC;1P
Adder
7.698
276805AD2-038 GEN
Solar/Wind Harmer
0.001
276889AE2-281 GEN
Solar/Wind Harmer
0
276799AD1-013 GEN
Solar/Wind Harmer
0.001
946671AF1-331 GEN
Solar/Wind Harmer
0.337
274850MENDOTA H;RU
Solar/Wind Harmer
0.037
276602WESTBROOK C
Solar/Wind Harmer
0
276863AD2-134 GEN
Solar/Wind Harmer
0.057
970571AG2-364 GEN
Solar/Wind Harmer
6.27
274858EASY ROAD;U2
Solar/Wind Harmer
0.001
276157O29GEN1
Solar/Wind Harmer
0.498
942111AE2-223 GEN
Solar/Wind Harmer
0.995
962031AG1-047 GEN
Solar/Wind Harmer
0
957741AF2-068 GEN
Solar/Wind Harmer
4.59
23856402BAYSG1
50/50
1.434
241858AF1-205_GEN
Solar/Wind Harmer
4.136
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
7.125
270361_3
Solar/Wind Harmer
5.347
944231AF1-091 GEN
Solar/Wind Harmer
1.301
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
4.008
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
7.698
274674JOLIET 9 ;6U
Adder
7.21
970245AG2-165 GEN
Solar/Wind Harmer
1.412
939401AE1-172 GEN
Solar/Wind Harmer
2.387
962781AG1-127 GEN
Solar/Wind Harmer
3.03
276876AE1-163_GEN2
Solar/Wind Harmer
0.001
972235AH1-702 GEN1
Adder
1.133
274857EASY ROAD;U1
Solar/Wind Harmer
0.001
274766LEE CO EC;7U
Adder
0.44
24385905FR-11G C
Solar/Wind Harmer
0.001
23906502RICHG2&3
Adder
1.423
270588AE1-091_GEN
Solar/Wind Harmer
3.741
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.87
274676JOLIET 29;8U
Adder
13.879
274734ELWOOD EC;8P
Adder
7.698
274736ELWOOD EC;9P
Adder
7.698
943121AE2-341 GEN
Solar/Wind Harmer
5.415
943591AF1-030 GEN
Solar/Wind Harmer
3.601
274682WAUKEGAN ;7U
Adder
8.266
24755605MDL-5G
Solar/Wind Harmer
0
959091AF2-200 GEN
Solar/Wind Harmer
6.293
247642Z2-115 C
Solar/Wind Harmer
0.001
203830AF1-094 GEN
Solar/Wind Helper
0.347
24190002OREGON_ST1
50/50
3.605
971677AH1-339 GEN
Solar/Wind Harmer
0.746
965681AG1-436 GEN
Solar/Wind Harmer
4.556
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
971341AH1-150 GEN
Solar/Wind Harmer
6.293
971343AH1-151 GEN
Solar/Wind Harmer
6.293
274849CRESCENT ;1U
Solar/Wind Harmer
0
276741O09 GEN1
Solar/Wind Harmer
0.11
276820AF1-078_GEN
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.267
203979AG1-198 GEN
Solar/Wind Helper
0.208
241801AE1-079 GEN
Solar/Wind Helper
0.141
23920202STRYCT
50/50
2.052
970515AG2-329 GEN
Solar/Wind Harmer
13.704
943021AE2-325 GEN
Solar/Wind Harmer
2.182
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
7.368
971917AH1-482 GEN
Solar/Wind Harmer
4.39
941551AE2-152 GEN
Solar/Wind Harmer
0
276691AA1-018 GEN1
Solar/Wind Harmer
0.391
24791305MDL-5G
Solar/Wind Harmer
0
274872LEEDK;1U
Solar/Wind Harmer
0.002
959081AF2-199 GEN
Solar/Wind Harmer
3.147
971067AG2-660 GEN
Solar/Wind Harmer
1.049
274822ROCKFORD ;11
Adder
8.833
970819AG2-516 GEN
Solar/Wind Harmer
3.753
971475AH1-234 GEN
Solar/Wind Harmer
1.515
276726Z2-087_GEN
Solar/Wind Harmer
0.001
274854TWINGROVE;U2
Solar/Wind Harmer
0.001
203954AE2-126 C
Solar/Wind Helper
0.233
990527J1329
External Queue
1.8513455390930176
991177J1571 G
External Queue
15.714932441711426
991182J1586 G
External Queue
25.292837142944336
990142J1224
External Queue
13.53333568572998
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.292
CPLELTFEXP_CPLE->PJM
CLTF
0.344
SIGELTFEXP_SIGE->PJM
CLTF
0.175
CBM South 1LTFEXP_CBM-S1->PJM
CBM
9.261
WECLTFEXP_WEC->PJM
CLTF
1.716
LAGNLTFEXP_LAGN->PJM
CLTF
5.142
CBM West 2LTFEXP_CBM-W2->PJM
CBM
41.091
LGEELTFEXP_LGEE->PJM
CLTF
2.101
MECLTFEXP_MEC->PJM
CLTF
6.695
AH1-155LTFEXP_AH1-155->PJM
LTF
0.166
CBM West 1LTFEXP_CBM-W1->PJM
CBM
96.429
NYPJM->LTFIMP_NY
CLTF
2.158
TVALTFEXP_TVA->PJM
CLTF
2.336
AG2-052LTFEXP_AG2-052->PJM
LTF
0.11

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#6497_05MARYSV 345_J2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#6497_05MARYSV 345_J2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:112.9 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1096.25
MW Contribution:2.38
Bus #Bus NameTypeMW Contribution
270435AC2-044 GEN
Solar/Wind Harmer
2.796
247607V1-011 GEN
Solar/Wind Harmer
2.22
241886AC2-103 GEN2
Solar/Wind Harmer
3.01
270485AE1-090_GEN
Solar/Wind Harmer
1.469
241832AE2-181_GEN
Solar/Wind Harmer
1.046
965021AG1-366 GEN
Solar/Wind Harmer
1.424
270044AE2-322 C
Solar/Wind Harmer
0.58
246936BC-WTG1
Solar/Wind Harmer
5.471
270489AE1-102 GEN1
Solar/Wind Harmer
1.818
960841AF2-375 GEN
Solar/Wind Harmer
3.561
247522W1-056 GEN
Solar/Wind Harmer
1.881
972253AH1-711 GEN
Adder
24.425
965011AG1-365 GEN
Solar/Wind Harmer
6.123
241885AC2-103 GEN1
Solar/Wind Harmer
3.01
970905AG2-564 GEN
Solar/Wind Harmer
2.385
270036AE2-216 BAT
50/50
15.511
270317AD1-130_GEN
Solar/Wind Harmer
7.788
270287AF1-227 GEN3
Solar/Wind Harmer
5.065
945641AF1-229 GEN
Solar/Wind Harmer
2.888
270462AD2-086
Solar/Wind Harmer
16.9
270391AF1-285 GEN3
Solar/Wind Harmer
2.932
270361_3
Solar/Wind Harmer
7.855
241858AF1-205_GEN
Solar/Wind Harmer
2.862
241808AF1-120 C
Solar/Wind Harmer
0.631
972301AH1-735 GEN
Adder
4.188
944231AF1-091 GEN
Solar/Wind Harmer
1.77
270466AD2-091
50/50
14.101
270224U2-072_GEN2
Solar/Wind Harmer
4.793
24727205RPMNG3
50/50
1.104
270302AB2-170 GEN
Solar/Wind Harmer
20.316
270284AF1-227 GEN1
Solar/Wind Harmer
13.691
957201AF2-014 GEN
Solar/Wind Harmer
6.341
971989AH1-539 GEN
Solar/Wind Harmer
10.515
253383AE2-342_GEN
Solar/Wind Helper
0.488
942871AE2-306 GEN
Solar/Wind Harmer
2.199
270391AF1-285 GEN3
Solar/Wind Harmer
1.128
270541AE2-072 C
Solar/Wind Harmer
3.796
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270377AD1-106 GEN
Solar/Wind Harmer
3.205
270404AC1-167 GEN
Solar/Wind Harmer
0.483
270578AF1-285 GEN2
Solar/Wind Harmer
1.128
270286AF1-227 GEN2
Solar/Wind Harmer
5.065
270499AE1-146 GEN
Solar/Wind Harmer
2.321
966831AG1-554 GEN
Solar/Wind Harmer
0.972
972211AH1-690 GEN
Adder
115.56
970817AG2-515 GEN
Solar/Wind Harmer
7.248
945411AF1-206 GEN
Solar/Wind Harmer
4.225
965041AG1-368 GEN
Solar/Wind Harmer
5.14
24191202EL_AA1-006
Adder
0.108
241972AD1-140 GEN
Solar/Wind Helper
2.205
971231AH1-075 GEN
Solar/Wind Harmer
0.415
965421AG1-410 GEN
Solar/Wind Harmer
39.687
241840AF1-064_GEN
Solar/Wind Harmer
0.826
23906502RICHG2&3
Adder
0.842
23906402RICHG1
Adder
0.838
270428AC2-015 C
Solar/Wind Harmer
3.044
241807AE2-176_GEN
Solar/Wind Harmer
2.084
24695305TIMB G C
Solar/Wind Harmer
2.935
270349AD2-093_GEN
Solar/Wind Helper
0.767
965431AG1-411 GEN
50/50
15.383
24727105RPMNG2
50/50
1.113
270588AE1-091_GEN
Solar/Wind Harmer
10.17
23906502RICHG2&3
Adder
0.842
270491AE1-102 GEN2
Solar/Wind Harmer
1.818
270575GUS2 35KV
Solar/Wind Harmer
9.254
958321AF2-126 GEN
Solar/Wind Harmer
0.886
23929302BS-PKR
Adder
1.019
959331AF2-224 GEN
Solar/Wind Harmer
6.123
970217AG2-149 GEN
Solar/Wind Harmer
17.433
24727005RPMNG1
50/50
1.109
270223U2-072_GEN1
Solar/Wind Harmer
4.793
270578AF1-285 GEN2
Solar/Wind Harmer
2.932
23920202STRYCT
Adder
0.981
970515AG2-329 GEN
Solar/Wind Harmer
7.906
270227U2-072_GEN3
Solar/Wind Harmer
4.793
270228U2-072_GEN4
Solar/Wind Harmer
4.793
270231U2-072_GEN5
Solar/Wind Harmer
4.793
971677AH1-339 GEN
Solar/Wind Harmer
6.461
276820AF1-078_GEN
Solar/Wind Helper
0.805
270471AD2-092_GEN
Solar/Wind Helper
0.767
246938BC-WTG3
Solar/Wind Harmer
5.566
246937BC-WTG2
Solar/Wind Harmer
5.471
241996AE2-282_GEN
Solar/Wind Harmer
1.131
970611AG2-400 GEN
Solar/Wind Harmer
6.123
270007AE1-245 C
Solar/Wind Harmer
3.331
253378AE2-206_GEN
Solar/Wind Helper
1.724
990527J1329
External Queue
1.068130612373352
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
NYPJM->LTFIMP_NY
CLTF
0.093
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.355
MECLTFEXP_MEC->PJM
CLTF
1.044
CBM West 1LTFEXP_CBM-W1->PJM
CBM
31.659
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.562
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
WECLTFEXP_WEC->PJM
CLTF
0.42
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.855
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.588
GibsonPJM->LTFIMP_GIBSON
CLTF
0
PRAIRIEPJM->LTFIMP_PRAIRIE
CLTF
0.026
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:105.18 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1021.28
MW Contribution:2.4
Bus #Bus NameTypeMW Contribution
270435AC2-044 GEN
Solar/Wind Harmer
2.802
247607V1-011 GEN
Solar/Wind Harmer
2.231
241886AC2-103 GEN2
Solar/Wind Harmer
3.026
270485AE1-090_GEN
Solar/Wind Harmer
1.471
241832AE2-181_GEN
Solar/Wind Harmer
1.05
965021AG1-366 GEN
Solar/Wind Harmer
1.43
270044AE2-322 C
Solar/Wind Harmer
0.583
246936BC-WTG1
Solar/Wind Harmer
5.482
270489AE1-102 GEN1
Solar/Wind Harmer
1.821
960841AF2-375 GEN
Solar/Wind Harmer
3.572
247522W1-056 GEN
Solar/Wind Harmer
1.887
972253AH1-711 GEN
Adder
24.514
965011AG1-365 GEN
Solar/Wind Harmer
6.15
241885AC2-103 GEN1
Solar/Wind Harmer
3.026
970905AG2-564 GEN
Solar/Wind Harmer
2.399
270036AE2-216 BAT
50/50
15.529
270317AD1-130_GEN
Solar/Wind Harmer
7.797
945641AF1-229 GEN
Solar/Wind Harmer
2.898
270462AD2-086
Solar/Wind Harmer
16.919
270391AF1-285 GEN3
Solar/Wind Harmer
2.935
270361_3
Solar/Wind Harmer
7.879
241858AF1-205_GEN
Solar/Wind Harmer
2.873
241808AF1-120 C
Solar/Wind Harmer
0.633
972301AH1-735 GEN
Adder
4.205
944231AF1-091 GEN
Solar/Wind Harmer
1.78
270466AD2-091
50/50
14.117
270224U2-072_GEN2
Solar/Wind Harmer
4.799
24727205RPMNG3
50/50
1.106
270302AB2-170 GEN
Solar/Wind Harmer
20.339
957201AF2-014 GEN
Solar/Wind Harmer
6.354
971989AH1-539 GEN
Solar/Wind Harmer
10.55
253383AE2-342_GEN
Solar/Wind Helper
0.486
942871AE2-306 GEN
Solar/Wind Harmer
2.201
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270541AE2-072 C
Solar/Wind Harmer
3.809
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270377AD1-106 GEN
Solar/Wind Harmer
3.222
270404AC1-167 GEN
Solar/Wind Harmer
0.486
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
270499AE1-146 GEN
Solar/Wind Harmer
2.328
966831AG1-554 GEN
Solar/Wind Harmer
0.976
972211AH1-690 GEN
Adder
115.994
970817AG2-515 GEN
Solar/Wind Harmer
7.276
945411AF1-206 GEN
Solar/Wind Harmer
4.242
965041AG1-368 GEN
Solar/Wind Harmer
5.168
24191202EL_AA1-006
Adder
0.109
241972AD1-140 GEN
Solar/Wind Helper
2.193
971231AH1-075 GEN
Solar/Wind Harmer
0.417
965421AG1-410 GEN
Solar/Wind Harmer
39.77
241840AF1-064_GEN
Solar/Wind Harmer
0.829
23906502RICHG2&3
Adder
0.845
23906402RICHG1
Adder
0.841
270428AC2-015 C
Solar/Wind Harmer
3.059
241807AE2-176_GEN
Solar/Wind Harmer
2.095
24695305TIMB G C
Solar/Wind Harmer
2.95
270349AD2-093_GEN
Solar/Wind Helper
0.763
965431AG1-411 GEN
50/50
15.415
24727105RPMNG2
50/50
1.116
270588AE1-091_GEN
Solar/Wind Harmer
10.201
23906502RICHG2&3
Adder
0.845
270491AE1-102 GEN2
Solar/Wind Harmer
1.821
270575GUS2 35KV
Solar/Wind Harmer
9.282
958321AF2-126 GEN
Solar/Wind Harmer
0.889
23929302BS-PKR
Adder
1.023
959331AF2-224 GEN
Solar/Wind Harmer
6.15
970217AG2-149 GEN
Solar/Wind Harmer
17.522
24727005RPMNG1
50/50
1.112
270223U2-072_GEN1
Solar/Wind Harmer
4.799
270578AF1-285 GEN2
Solar/Wind Harmer
2.935
23920202STRYCT
Adder
0.985
970515AG2-329 GEN
Solar/Wind Harmer
7.946
270227U2-072_GEN3
Solar/Wind Harmer
4.799
270228U2-072_GEN4
Solar/Wind Harmer
4.799
270231U2-072_GEN5
Solar/Wind Harmer
4.799
971677AH1-339 GEN
Solar/Wind Harmer
6.484
276820AF1-078_GEN
Solar/Wind Helper
0.804
270471AD2-092_GEN
Solar/Wind Helper
0.763
246938BC-WTG3
Solar/Wind Harmer
5.577
246937BC-WTG2
Solar/Wind Harmer
5.482
241996AE2-282_GEN
Solar/Wind Harmer
1.136
970611AG2-400 GEN
Solar/Wind Harmer
6.15
270007AE1-245 C
Solar/Wind Harmer
3.347
253378AE2-206_GEN
Solar/Wind Helper
1.721
990527J1329
External Queue
1.068130612373352
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
NYPJM->LTFIMP_NY
CLTF
0.075
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.344
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.062
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.544
MECLTFEXP_MEC->PJM
CLTF
1.09
WECLTFEXP_WEC->PJM
CLTF
0.43
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.837
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.533

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:104.18 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1011.61
MW Contribution:2.4
Bus #Bus NameTypeMW Contribution
270435AC2-044 GEN
Solar/Wind Harmer
2.803
247607V1-011 GEN
Solar/Wind Harmer
2.233
241886AC2-103 GEN2
Solar/Wind Harmer
3.03
270485AE1-090_GEN
Solar/Wind Harmer
1.471
241832AE2-181_GEN
Solar/Wind Harmer
1.051
965021AG1-366 GEN
Solar/Wind Harmer
1.432
270044AE2-322 C
Solar/Wind Harmer
0.584
270036AE2-216 BAT
50/50
15.533
270317AD1-130_GEN
Solar/Wind Harmer
7.799
945641AF1-229 GEN
Solar/Wind Harmer
2.9
270287AF1-227 GEN3
Solar/Wind Helper
0.434
24727205RPMNG3
50/50
1.107
270302AB2-170 GEN
Solar/Wind Harmer
20.344
957201AF2-014 GEN
Solar/Wind Harmer
6.357
971989AH1-539 GEN
Solar/Wind Harmer
10.558
253383AE2-342_GEN
Solar/Wind Helper
0.485
270284AF1-227 GEN1
Solar/Wind Helper
1.184
942871AE2-306 GEN
Solar/Wind Harmer
2.202
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270541AE2-072 C
Solar/Wind Harmer
3.811
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270377AD1-106 GEN
Solar/Wind Harmer
3.226
270404AC1-167 GEN
Solar/Wind Harmer
0.486
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
270499AE1-146 GEN
Solar/Wind Harmer
2.33
966831AG1-554 GEN
Solar/Wind Harmer
0.976
972211AH1-690 GEN
Adder
116.091
970817AG2-515 GEN
Solar/Wind Harmer
7.282
945411AF1-206 GEN
Solar/Wind Harmer
4.246
965041AG1-368 GEN
Solar/Wind Harmer
5.174
24191202EL_AA1-006
Adder
0.109
241972AD1-140 GEN
Solar/Wind Helper
2.191
270286AF1-227 GEN2
Solar/Wind Helper
0.434
971231AH1-075 GEN
Solar/Wind Harmer
0.418
965431AG1-411 GEN
50/50
15.422
24727105RPMNG2
50/50
1.116
270588AE1-091_GEN
Solar/Wind Harmer
10.207
23906502RICHG2&3
Adder
0.846
270462AD2-086
Solar/Wind Harmer
16.924
270391AF1-285 GEN3
Solar/Wind Harmer
2.936
270361_3
Solar/Wind Harmer
7.884
241858AF1-205_GEN
Solar/Wind Harmer
2.875
241808AF1-120 C
Solar/Wind Harmer
0.634
972301AH1-735 GEN
Adder
4.209
944231AF1-091 GEN
Solar/Wind Harmer
1.782
270466AD2-091
50/50
14.121
270224U2-072_GEN2
Solar/Wind Harmer
4.8
270491AE1-102 GEN2
Solar/Wind Harmer
1.822
270575GUS2 35KV
Solar/Wind Harmer
9.288
958321AF2-126 GEN
Solar/Wind Harmer
0.89
23929302BS-PKR
Adder
1.023
959331AF2-224 GEN
Solar/Wind Harmer
6.157
970217AG2-149 GEN
Solar/Wind Harmer
17.541
24727005RPMNG1
50/50
1.112
270223U2-072_GEN1
Solar/Wind Harmer
4.8
270578AF1-285 GEN2
Solar/Wind Harmer
2.936
23920202STRYCT
Adder
0.986
970515AG2-329 GEN
Solar/Wind Harmer
7.955
965421AG1-410 GEN
Solar/Wind Harmer
39.788
241840AF1-064_GEN
Solar/Wind Harmer
0.83
23906502RICHG2&3
Adder
0.846
23906402RICHG1
Adder
0.842
270428AC2-015 C
Solar/Wind Harmer
3.063
241807AE2-176_GEN
Solar/Wind Harmer
2.097
24695305TIMB G C
Solar/Wind Harmer
2.953
270349AD2-093_GEN
Solar/Wind Helper
0.762
270227U2-072_GEN3
Solar/Wind Harmer
4.8
270228U2-072_GEN4
Solar/Wind Harmer
4.8
270231U2-072_GEN5
Solar/Wind Harmer
4.8
971677AH1-339 GEN
Solar/Wind Harmer
6.488
276820AF1-078_GEN
Solar/Wind Helper
0.803
270471AD2-092_GEN
Solar/Wind Helper
0.762
246936BC-WTG1
Solar/Wind Harmer
5.484
270489AE1-102 GEN1
Solar/Wind Harmer
1.822
960841AF2-375 GEN
Solar/Wind Harmer
3.575
247522W1-056 GEN
Solar/Wind Harmer
1.889
972253AH1-711 GEN
Adder
24.533
965011AG1-365 GEN
Solar/Wind Harmer
6.157
241885AC2-103 GEN1
Solar/Wind Harmer
3.03
970905AG2-564 GEN
Solar/Wind Harmer
2.402
246938BC-WTG3
Solar/Wind Harmer
5.579
246937BC-WTG2
Solar/Wind Harmer
5.484
241996AE2-282_GEN
Solar/Wind Harmer
1.137
970611AG2-400 GEN
Solar/Wind Harmer
6.157
270007AE1-245 C
Solar/Wind Harmer
3.351
253378AE2-206_GEN
Solar/Wind Helper
1.72
990527J1329
External Queue
1.068130612373352
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.833
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.521
NYPJM->LTFIMP_NY
CLTF
0.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.341
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.151
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.54
MECLTFEXP_MEC->PJM
CLTF
1.1
WECLTFEXP_WEC->PJM
CLTF
0.433
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0

Details for 05E LIMA-05SW LIM 345.0 kV Ckt 1 line l/o AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A


Base Case Flowgate

Area:AEP
Facility Description:
05E LIMA-05SW LIM 345.0 kV Ckt 1 line
Contingency Name:
AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A
Contingency Type:Bus
DC|AC:AC
Final Cycle Loading:104.17 %
Rating:971.0 MVA
Rating Type:B
MVA to Mitigate:1011.54
MW Contribution:2.4
Bus #Bus NameTypeMW Contribution
270578AF1-285 GEN2
Solar/Wind Harmer
1.129
270499AE1-146 GEN
Solar/Wind Harmer
2.33
966831AG1-554 GEN
Solar/Wind Harmer
0.976
972211AH1-690 GEN
Adder
116.091
970817AG2-515 GEN
Solar/Wind Harmer
7.282
945411AF1-206 GEN
Solar/Wind Harmer
4.246
965041AG1-368 GEN
Solar/Wind Harmer
5.174
24191202EL_AA1-006
Adder
0.109
241972AD1-140 GEN
Solar/Wind Helper
2.191
965431AG1-411 GEN
50/50
15.422
24727105RPMNG2
50/50
1.116
270588AE1-091_GEN
Solar/Wind Harmer
10.207
23906502RICHG2&3
Adder
0.846
24727205RPMNG3
50/50
1.107
270302AB2-170 GEN
Solar/Wind Harmer
20.344
957201AF2-014 GEN
Solar/Wind Harmer
6.357
971989AH1-539 GEN
Solar/Wind Harmer
10.558
253383AE2-342_GEN
Solar/Wind Helper
0.485
270284AF1-227 GEN1
Solar/Wind Helper
1.184
942871AE2-306 GEN
Solar/Wind Harmer
2.202
270391AF1-285 GEN3
Solar/Wind Harmer
1.129
270541AE2-072 C
Solar/Wind Harmer
3.811
958091AF2-103 GEN
Solar/Wind Harmer
0.091
270377AD1-106 GEN
Solar/Wind Harmer
3.226
270404AC1-167 GEN
Solar/Wind Harmer
0.486
270036AE2-216 BAT
50/50
15.533
270317AD1-130_GEN
Solar/Wind Harmer
7.799
945641AF1-229 GEN
Solar/Wind Harmer
2.9
270287AF1-227 GEN3
Solar/Wind Helper
0.434
270462AD2-086
Solar/Wind Harmer
16.924
270391AF1-285 GEN3
Solar/Wind Harmer
2.936
270361_3
Solar/Wind Harmer
7.884
241858AF1-205_GEN
Solar/Wind Harmer
2.875
241808AF1-120 C
Solar/Wind Harmer
0.634
972301AH1-735 GEN
Adder
4.209
944231AF1-091 GEN
Solar/Wind Harmer
1.782
270466AD2-091
50/50
14.121
270224U2-072_GEN2
Solar/Wind Harmer
4.8
270491AE1-102 GEN2
Solar/Wind Harmer
1.822
270575GUS2 35KV
Solar/Wind Harmer
9.288
958321AF2-126 GEN
Solar/Wind Harmer
0.89
23929302BS-PKR
Adder
1.023
959331AF2-224 GEN
Solar/Wind Harmer
6.157
970217AG2-149 GEN
Solar/Wind Harmer
17.541
270286AF1-227 GEN2
Solar/Wind Helper
0.434
24727005RPMNG1
50/50
1.112
270223U2-072_GEN1
Solar/Wind Harmer
4.8
270578AF1-285 GEN2
Solar/Wind Harmer
2.936
23920202STRYCT
Adder
0.986
970515AG2-329 GEN
Solar/Wind Harmer
7.955
971231AH1-075 GEN
Solar/Wind Harmer
0.418
965421AG1-410 GEN
Solar/Wind Harmer
39.788
241840AF1-064_GEN
Solar/Wind Harmer
0.83
23906502RICHG2&3
Adder
0.846
23906402RICHG1
Adder
0.842
270428AC2-015 C
Solar/Wind Harmer
3.063
241807AE2-176_GEN
Solar/Wind Harmer
2.097
24695305TIMB G C
Solar/Wind Harmer
2.953
270349AD2-093_GEN
Solar/Wind Helper
0.762
270227U2-072_GEN3
Solar/Wind Harmer
4.8
270228U2-072_GEN4
Solar/Wind Harmer
4.8
270231U2-072_GEN5
Solar/Wind Harmer
4.8
971677AH1-339 GEN
Solar/Wind Harmer
6.488
276820AF1-078_GEN
Solar/Wind Helper
0.803
270471AD2-092_GEN
Solar/Wind Helper
0.762
270485AE1-090_GEN
Solar/Wind Harmer
1.471
241832AE2-181_GEN
Solar/Wind Harmer
1.051
965021AG1-366 GEN
Solar/Wind Harmer
1.432
270044AE2-322 C
Solar/Wind Harmer
0.584
270435AC2-044 GEN
Solar/Wind Harmer
2.803
247607V1-011 GEN
Solar/Wind Harmer
2.233
241886AC2-103 GEN2
Solar/Wind Harmer
3.03
246936BC-WTG1
Solar/Wind Harmer
5.484
270489AE1-102 GEN1
Solar/Wind Harmer
1.822
960841AF2-375 GEN
Solar/Wind Harmer
3.575
247522W1-056 GEN
Solar/Wind Harmer
1.889
972253AH1-711 GEN
Adder
24.533
965011AG1-365 GEN
Solar/Wind Harmer
6.157
241885AC2-103 GEN1
Solar/Wind Harmer
3.03
970905AG2-564 GEN
Solar/Wind Harmer
2.402
246938BC-WTG3
Solar/Wind Harmer
5.579
246937BC-WTG2
Solar/Wind Harmer
5.484
241996AE2-282_GEN
Solar/Wind Harmer
1.137
970611AG2-400 GEN
Solar/Wind Harmer
6.157
270007AE1-245 C
Solar/Wind Harmer
3.351
253378AE2-206_GEN
Solar/Wind Helper
1.72
990527J1329
External Queue
1.068130612373352
991177J1571 G
External Queue
9.20388412475586
990142J1224
External Queue
7.808034420013428
WECLTFEXP_WEC->PJM
CLTF
0.433
CALDErWOODPJM->LTFIMP_CALDERWOOD
CLTF
0
GibsonPJM->LTFIMP_GIBSON
CLTF
0
TRIMBLEPJM->LTFIMP_TRIMBLE
CLTF
0.833
BlueGrassPJM->LTFIMP_BlueG
CLTF
2.521
NYPJM->LTFIMP_NY
CLTF
0.071
CATAWBAPJM->LTFIMP_CATAWBA
CLTF
0.341
CHEOAHPJM->LTFIMP_CHEOAH
CLTF
0
CBM West 1LTFEXP_CBM-W1->PJM
CBM
32.151
HAMLETPJM->LTFIMP_HAMLET
CLTF
0.54
MECLTFEXP_MEC->PJM
CLTF
1.1

Details for 05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer l/o AP_P1-2_WP-500-303T_SRT-A


Base Case Flowgate

Area:AEP/AP
Facility Description:
05KAMMER-01KAMMER 765.0/500.0 kV Ckt 1 transformer
Contingency Name:
AP_P1-2_WP-500-303T_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:103.49 %
Rating:3792.0 MVA
Rating Type:B
MVA to Mitigate:3924.38
MW Contribution:3.42
Bus #Bus NameTypeMW Contribution
270166AC1-044 GEN3
50/50
6.34
246936BC-WTG1
Solar/Wind Harmer
0.264
270489AE1-102 GEN1
Solar/Wind Harmer
0.847
942861AE2-305 GEN
Solar/Wind Harmer
5.429
270518AE2-148 GEN
Solar/Wind Harmer
0.589
241960AC2-195 GEN
Solar/Wind Harmer
0.005
971199AH1-059 GEN
Solar/Wind Harmer
2.717
972159AH1-661 GEN
Adder
0.967
970329AG2-216 GEN
Solar/Wind Harmer
2.879
971231AH1-075 GEN
Solar/Wind Harmer
0.76
25326109MON D
Adder
1.224
971073AG2-665 GEN
Solar/Wind Harmer
5.736
944541AF1-119 GEN
Solar/Wind Harmer
0.422
247620Y3-023
Adder
0.415
270201AC2-176 GEN
Solar/Wind Harmer
0.001
970885AG2-551 GEN
Solar/Wind Harmer
2.091
964611AG1-324 GEN
Solar/Wind Harmer
0.47
270031AE2-169
Solar/Wind Harmer
3.434
270526AF1-158 GEN
Solar/Wind Harmer
0.008
24441505OLIV SLR
Solar/Wind Harmer
0
25183208HLCRTG
Solar/Wind Harmer
0.01
270383AD1-128 GEN
Solar/Wind Harmer
0.004
960441AF2-335 GEN
Solar/Wind Harmer
6.218
965791AG1-447 GEN
Solar/Wind Harmer
5.698
24379505HDWTR1G C
Solar/Wind Harmer
0.002
25194508D.CRK3
Adder
1.257
24728805RICHG1
Adder
3.349
252509AD1-136 GEN
Solar/Wind Harmer
0.031
945421AF1-207 GEN
Solar/Wind Harmer
0.001
276843GEN-1.7
Solar/Wind Harmer
0.197
958011AF2-095 GEN
Solar/Wind Harmer
8.755
274861TOP CROP ;1U
Solar/Wind Harmer
0.002
971573AH1-285 GEN
Solar/Wind Harmer
1.122
274695ROCKY RD ;2P
Adder
9.586
958491AF2-143 GEN
Solar/Wind Harmer
9.003
237034AC2-136 C
Solar/Wind Helper
0.19
247522W1-056 GEN
Solar/Wind Harmer
0.001
965011AG1-365 GEN
Solar/Wind Harmer
6.437
958861AF2-177 GEN
Solar/Wind Harmer
2.728
945371AF1-202 GEN
Solar/Wind Harmer
0.001
945111AF1-176 GEN
Solar/Wind Harmer
11.181
270505AE1-170 C O1
Solar/Wind Harmer
6.577
970905AG2-564 GEN
Solar/Wind Harmer
3.422
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
270005AE1-210 C O1
Solar/Wind Harmer
1.348
970825AG2-519 GEN
Solar/Wind Harmer
2.208
942081AE2-220 GEN
Solar/Wind Harmer
-0.001
270239V3-007_GEN1
Solar/Wind Harmer
0
270032AE2-172
Solar/Wind Harmer
4.137
964861AG1-349 GEN
Solar/Wind Harmer
-0.001
25196808ZIMRHP
Adder
66.86
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
7.678
274751CRETE EC ;1U
Adder
7.224
274723RIVER EC ;12
Adder
15.693
274773LINCOLN ;4U
Adder
7.388
274774LINCOLN ;5U
Adder
7.388
25196008MFTGT1
Adder
1.217
274801UNIV PARK;4U
Adder
5.08
24387305FR-4G C
Solar/Wind Harmer
0.002
970333AG2-219 GEN
Solar/Wind Harmer
4.302
23583801GRNGAP
Solar/Wind Helper
4.407
238221AF1-254 C O1
Solar/Wind Helper
0.229
270120AB2-067 GEN2
50/50
6.34
938701AE1-092 GEN
Solar/Wind Harmer
11.216
270224U2-072_GEN2
Solar/Wind Harmer
0.001
964601AG1-323 GEN
Solar/Wind Harmer
2.785
964601AG1-323 GEN
Solar/Wind Harmer
1.857
971201AH1-060 GEN
Solar/Wind Harmer
1.348
970627AG2-408 GEN
Solar/Wind Harmer
1.931
960971AF2-388 GEN
Solar/Wind Harmer
3.699
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970883AG2-550 GEN
Solar/Wind Harmer
6.273
961051AF2-396 GEN
Solar/Wind Harmer
12.524
961051AF2-396 GEN
Solar/Wind Harmer
8.349
270599AE1-208 GEN
Solar/Wind Harmer
5.724
926881AC1-175 GEN
Solar/Wind Harmer
0
25194408D.CRK1
Adder
6.724
24728905RICHG2
Adder
3.349
274803UNIV PARK;6U
Adder
5.083
274887GEN-1.85
Solar/Wind Harmer
0.16
966841AG1-555 GEN
Solar/Wind Harmer
0.687
274674JOLIET 9 ;6U
Adder
13.366
958481AF2-142 GEN
Solar/Wind Harmer
9.035
274862TOP CROP ;2U
Solar/Wind Harmer
0.815
274693ROCKY RD ;1P
Adder
9.492
274683WAUKEGAN ;8U
Adder
18.127
274683WAUKEGAN ;8U
Adder
15.281
23777901MDS_W4-102
Solar/Wind Helper
0.148
970155AG2-107 GEN
Solar/Wind Harmer
18.586
270349AD2-093_GEN
Solar/Wind Harmer
0.005
971995AH1-542 GEN
Solar/Wind Harmer
2.546
253343AC1-166 GEN
Solar/Wind Harmer
0.003
24721705FLATG2
Adder
18.986
965421AG1-410 GEN
Solar/Wind Harmer
19.519
247521TR3_G114
Solar/Wind Harmer
0.235
270246TR4_N_V150
Solar/Wind Harmer
0.042
24695305TIMB G C
Solar/Wind Harmer
0.002
235063AE1-101 C2
Solar/Wind Helper
1.39
237001AB1-127_GEN
Solar/Wind Helper
0.371
960071AF2-298 GEN
Solar/Wind Harmer
3.209
253370AE2-315 SEC1
Adder
1.846
253371AE2-315 SEC2
Adder
1.746
965651AG1-433 GEN
Solar/Wind Harmer
1.85
253432AC1-085 GEN2
Solar/Wind Harmer
0
946171AF1-282 GEN
Solar/Wind Harmer
6.305
24639705ELKHART HY
Adder
0.138
270449AD2-020 GEN
Solar/Wind Harmer
0
965031AG1-367 GEN
Solar/Wind Harmer
6.223
970613AG2-401 GEN
Solar/Wind Harmer
4.554
25194608D.CRK4
Adder
1.462
970291AG2-192 GEN
Solar/Wind Harmer
0.806
270428AC2-015 C
Solar/Wind Harmer
0.004
270055AF2-134 C O1
Solar/Wind Harmer
0.005
23906502RICHG2&3
Adder
1.066
23906402RICHG1
Adder
1.066
276164X3-005 C
Solar/Wind Harmer
0
274812UNIV PK N;8U
Adder
4.378
241840AF1-064_GEN
Solar/Wind Harmer
0.003
276776AD2-060 GEN
Solar/Wind Harmer
0.635
274676JOLIET 29;8U
Adder
26.643
274871GR RIDGE ;2U
Solar/Wind Harmer
0.001
24728605AND G2
Adder
3.317
274745AC1-111 GEN9
Adder
4.832
274682WAUKEGAN ;7U
Adder
15.467
274828WAUKEGAN ;BP
Adder
6.624
276901AD2-066 C O1
Solar/Wind Harmer
0.006
962771AG1-126 GEN
Solar/Wind Harmer
29.106
270284AF1-227 GEN1
Solar/Wind Harmer
0.009
253383AE2-342_GEN
Solar/Wind Harmer
0.002
241973AD2-163_GEN1
Solar/Wind Harmer
0.005
943861AF1-054 GEN
Solar/Wind Harmer
2.68
943851AF1-053 GEN
Solar/Wind Harmer
1.856
270302AB2-170 GEN
Solar/Wind Harmer
0.004
971653AH1-327 GEN
Solar/Wind Harmer
0.97
970689AG2-444 GEN
Solar/Wind Harmer
13.943
970179AG2-119 GEN
Solar/Wind Harmer
6.078
971989AH1-539 GEN
Solar/Wind Harmer
2.83
957201AF2-014 GEN
Solar/Wind Harmer
0
972239AH1-704 GEN
50/50
2.67
961821AG1-024 GEN
Solar/Wind Harmer
4.393
270286AF1-227 GEN2
Solar/Wind Harmer
0.004
270578AF1-285 GEN2
Solar/Wind Harmer
0.465
945631AF1-228 GEN
Solar/Wind Harmer
0
270432AC2-029 GEN
Solar/Wind Harmer
3.008
270269AC2-059
Solar/Wind Harmer
0.004
241972AD1-140 GEN
Solar/Wind Harmer
0.727
270340AC2-060 GEN
Solar/Wind Harmer
0.007
270297AD1-101 GEN
Solar/Wind Harmer
0.002
965041AG1-368 GEN
Solar/Wind Harmer
6.437
253400AC2-068 GEN
Solar/Wind Harmer
0.811
965101AG1-375 GEN
Solar/Wind Harmer
6.295
270499AE1-146 GEN
Solar/Wind Harmer
0.028
971609AH1-304 GEN
Solar/Wind Harmer
1.02
970115AG2-085 GEN
Solar/Wind Harmer
2.487
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
25196508WSDLE4
Adder
7.549
24699105WLD G1 C
Solar/Wind Harmer
0.001
274776LINCOLN ;7U
Adder
7.388
24690905MDL-1G C
Solar/Wind Harmer
0.002
270180AB1-006 GEN1
Solar/Wind Harmer
0.001
946581AF1-322 GEN
Solar/Wind Harmer
0
24697905MDL-4G C
Solar/Wind Harmer
0.001
274814UNIV PK N;0U
Adder
4.416
274807UNIV PK N;3U
Adder
4.406
274805UNIV PK N;1U
Adder
4.387
24386205FR-12G C
Solar/Wind Harmer
0.001
274687WILL CNTY;4U
Adder
24.279
274687WILL CNTY;4U
Adder
24.279
274731ELWOOD EC;2P
Adder
14.27
274733ELWOOD EC;3P
Adder
14.27
963841AG1-237 GEN
Solar/Wind Harmer
2.618
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
274746AC1-111 G10
Adder
4.832
238152AF2-075_GEN
Solar/Wind Helper
0.571
237002AB1-128_GEN
Solar/Wind Helper
0.371
23585401KL_K28_T16
Solar/Wind Helper
1.117
237006AB1-125 GEN
Solar/Wind Helper
0.105
270054AF2-122 C O1
Solar/Wind Harmer
0.006
270287AF1-227 GEN3
Solar/Wind Harmer
0.004
270520AE2-214 GEN
Solar/Wind Harmer
0.011
270158DARBY CT3
Adder
8.723
270317AD1-130_GEN
Solar/Wind Harmer
0.01
965051AG1-369 GEN
Solar/Wind Harmer
3.223
253349AC2-067 GEN
Solar/Wind Harmer
2.017
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971347AH1-153 GEN
Solar/Wind Harmer
9.423
945581AF1-223 GEN
Solar/Wind Harmer
0
971029AG2-637 GEN
Solar/Wind Harmer
9.403
971619AH1-309 GEN
Solar/Wind Harmer
2.819
24725505WLD G2 C
Solar/Wind Harmer
0.001
971611AH1-305 GEN
Solar/Wind Harmer
3.657
971985AH1-537 GEN
Solar/Wind Harmer
1.825
274775LINCOLN ;6U
Adder
7.388
274777LINCOLN ;8U
Adder
7.388
24697605MDL-3G C
Solar/Wind Harmer
0.001
270181AB1-006 GEN2
Solar/Wind Harmer
0
972037AH1-567 GEN1
Adder
0.16
960591AF2-350 GEN
Solar/Wind Harmer
6.08
24386405FR-21G C
Solar/Wind Harmer
0.001
274675JOLIET 29;7U
Adder
26.643
274675JOLIET 29;7U
Adder
25.691
970833AG2-524 GEN
Solar/Wind Harmer
6.658
970833AG2-524 GEN
Solar/Wind Harmer
4.438
238208AF1-136 C
Solar/Wind Helper
0.182
270119AB2-067 GEN1
50/50
6.34
970077AG2-063 GEN
Solar/Wind Harmer
3.964
972269AH1-719 GEN
Adder
2.215
253378AE2-206_GEN
Solar/Wind Harmer
0.004
25326509SID D
Adder
1.243
246938BC-WTG3
Solar/Wind Harmer
0.236
246937BC-WTG2
Solar/Wind Harmer
0.264
270007AE1-245 C
Solar/Wind Harmer
0.002
970621AG2-405 GEN
Solar/Wind Harmer
1.179
970611AG2-400 GEN
Solar/Wind Harmer
6.437
970623AG2-406 GEN
Solar/Wind Harmer
1.175
253394AE2-221_GEN
Solar/Wind Harmer
0.008
253398AE2-221_GEN2
Solar/Wind Harmer
0.008
942221AE2-234 GEN
Solar/Wind Harmer
0.032
970321AG2-212 GEN
Solar/Wind Harmer
2.715
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970825AG2-519 GEN
Solar/Wind Harmer
6.895
270209AC1-174_GEN
Solar/Wind Harmer
0
962581AG1-107 GEN
Solar/Wind Harmer
0.001
270186AC1-089 GEN
Solar/Wind Harmer
0.004
957841AF2-078 GEN
Solar/Wind Harmer
-0.001
274770LINCOLN ;1U
Adder
7.388
274771LINCOLN ;2U
Adder
7.388
274808UNIV PK N;4U
Adder
4.359
274888KELLY CRK;1U
Solar/Wind Harmer
0.357
972259AH1-714 GEN
Adder
16.604
241996AE2-282_GEN
Solar/Wind Harmer
0.004
970239AG2-162 GEN
Solar/Wind Harmer
1.504
970241AG2-163 GEN
Solar/Wind Harmer
3.509
274696ROCKY RD ;4P
Adder
9.813
274697ROCKY RD ;3P
Adder
2.604
238175AF1-290_GEN
Solar/Wind Helper
0.126
235020AA1-095 C
Solar/Wind Helper
0.044
270459AD2-067 GEN
Solar/Wind Harmer
0
270156DARBY CT1
Adder
8.886
270157DARBY CT2
Adder
8.864
940611AE2-048 GEN
Solar/Wind Harmer
16.743
941391AE2-136 GEN
Solar/Wind Harmer
9.431
971567AH1-282 GEN
Solar/Wind Harmer
9.938
270435AC2-044 GEN
Solar/Wind Harmer
0.825
247607V1-011 GEN
Solar/Wind Harmer
0.001
970879AG2-548 GEN
Solar/Wind Harmer
5.736
270071AF1-092 GEN
Solar/Wind Harmer
12.163
24729505KEY G4
Adder
5.895
270543AE2-219 C
Solar/Wind Harmer
0.004
971673AH1-337 GEN
Solar/Wind Harmer
4.074
971771AH1-392 GEN
Solar/Wind Harmer
6.257
971769AH1-391 GEN
Solar/Wind Harmer
6.959
971549AH1-272 GEN
Solar/Wind Harmer
12.86
270240V3-007_GEN2
Solar/Wind Harmer
0.002
25196408WSDLE3
Adder
7.852
25196308WSDLE2
Adder
7.783
25196208WSDLE1
Adder
7.764
25196708WSDLE6
Adder
7.744
270594AE1-207 GEN
Solar/Wind Harmer
6.95
270367AC2-061_GEN
Solar/Wind Harmer
0.005
24691005MDL-2G C
Solar/Wind Harmer
0.001
25196108MFTGT2
Adder
1.342
25196108MFTGT2
Adder
1.246
24386605FR-22G C
Solar/Wind Harmer
0.001
24387005FR-3G C
Solar/Wind Harmer
0.001
274728ELWOOD EC;5P
Adder
14.27
274863CRW1-WTG
Solar/Wind Harmer
0.002
274864CRW2-WTG
Solar/Wind Harmer
0.002
237085AD2-009_GEN
Solar/Wind Helper
1.378
238126S14_GEN_1
Solar/Wind Helper
0.65
270051AF1-062 GEN
50/50
10.221
270485AE1-090_GEN
Solar/Wind Harmer
0.001
970065AG2-057 GEN
Solar/Wind Harmer
0.674
965021AG1-366 GEN
Solar/Wind Harmer
2.146
270512AE1-227 GEN2
Solar/Wind Harmer
1.639
270043AE2-236 GEN
Solar/Wind Harmer
4.091
962031AG1-047 GEN
Solar/Wind Harmer
-0.001
957741AF2-068 GEN
Solar/Wind Harmer
9.425
945111AF1-176 GEN
Solar/Wind Harmer
5.079
24441205WTRV SLR C
Solar/Wind Harmer
0
252510AF1-249 C
Solar/Wind Harmer
0.048
972059AH1-578 GEN
Solar/Wind Harmer
2.879
971191AH1-055 GEN
Solar/Wind Harmer
15.745
274724RIVER EC ;11
Adder
15.509
274772LINCOLN ;3U
Adder
7.388
25196008MFTGT1
Adder
1.179
274802UNIV PARK;5U
Adder
5.083
970941AG2-585 GEN
Solar/Wind Harmer
7.6
274800UNIV PARK;3U
Adder
5.08
276897AD1-100 C
Solar/Wind Harmer
0.008
274729ELWOOD EC;1P
Adder
14.27
276893AG1-478 C
Solar/Wind Harmer
0.24
241832AE2-181_GEN
Solar/Wind Harmer
0.002
970243AG2-164 GEN
Solar/Wind Harmer
3.519
276805AD2-038 GEN
Solar/Wind Harmer
0.002
961921AG1-034 GEN
Solar/Wind Harmer
6.59
942051AE2-217 GEN
Solar/Wind Harmer
12.577
270391AF1-285 GEN3
Solar/Wind Harmer
0.465
970605AG2-385 GEN
Solar/Wind Harmer
4.193
253333AC1-068 GEN
Solar/Wind Harmer
0.011
270273AD2-016 GEN
Solar/Wind Harmer
0.693
270377AD1-106 GEN
Solar/Wind Harmer
2.517
253415AE1-040 GEN
Solar/Wind Harmer
0.003
270247TR4_N_V136
Solar/Wind Harmer
0.042
270291AC1-194 GEN
Solar/Wind Harmer
5.098
270404AC1-167 GEN
Solar/Wind Harmer
0.003
253406AD2-031_GEN
Solar/Wind Harmer
0.474
944531AF1-118 GEN
Solar/Wind Harmer
28.469
970031AG2-029 GEN
Solar/Wind Harmer
4.115
270541AE2-072 C
Solar/Wind Harmer
0.008
970349AG2-230 GEN
Solar/Wind Harmer
9.423
970513AG2-328 GEN
Solar/Wind Harmer
2.715
970517AG2-330 GEN
Solar/Wind Harmer
16.29
247604X1-042
Adder
0.373
958821AF2-173 GEN
Solar/Wind Harmer
8.712
270437AC2-090 C
Solar/Wind Harmer
0.003
25196608WSDLE5
Adder
7.627
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274752CRETE EC ;2U
Adder
7.224
970781AG2-491 GEN
Solar/Wind Harmer
6.108
274826FISK ;BP
Adder
9.541
972228AH1-698 GEN2
Adder
3.226
939351AE1-166 GEN
Solar/Wind Harmer
0
970707AG2-453 GEN
Solar/Wind Harmer
19.835
274730ELWOOD EC;6P
Adder
14.27
24728705AND G3
Adder
6.937
276694AA1-018 GEN2
Solar/Wind Harmer
0.001
970519AG2-331 GEN
Solar/Wind Harmer
15.642
970699AG2-449 GEN
Solar/Wind Harmer
1.504
958171AF2-111 GEN
Solar/Wind Harmer
15.012
23750701CROSSCHOOL
Solar/Wind Helper
1.186
235062AE1-101 C1
Solar/Wind Helper
1.39
238127S14_GEN_2
Solar/Wind Helper
0.65
962761AG1-125 GEN
Solar/Wind Harmer
29.106
270462AD2-086
Solar/Wind Harmer
0.014
241813AF1-122_GEN
Solar/Wind Harmer
3.02
25326309TAIT D
Adder
1.013
944231AF1-091 GEN
Solar/Wind Harmer
1.692
270063AE2-323 C
Solar/Wind Harmer
0.005
247536S-71 GEN
Solar/Wind Harmer
0.253
970245AG2-165 GEN
Solar/Wind Harmer
2.715
270361_3
Solar/Wind Harmer
4.246
252507AC2-088 GEN
Solar/Wind Harmer
0.281
276903AD2-071 C
Solar/Wind Harmer
6.897
972057AH1-577 GEN
Solar/Wind Harmer
4.319
972301AH1-735 GEN
Adder
5.33
958381AF2-132 GEN
Solar/Wind Harmer
0.001
274754CRETE EC ;4U
Adder
7.224
24385905FR-11G C
Solar/Wind Harmer
0.001
274732ELWOOD EC;7P
Adder
14.27
274674JOLIET 9 ;6U
Adder
13.366
241808AF1-120 C
Solar/Wind Harmer
0.002
939401AE1-172 GEN
Solar/Wind Harmer
4.507
241858AF1-205_GEN
Solar/Wind Harmer
2.406
238147AE2-230_GEN1
Solar/Wind Helper
0.399
235067AD1-061 GEN
Solar/Wind Helper
0.415
238117U2-030
Solar/Wind Helper
0.265
253372AE2-315 SEC3
Adder
1.746
253372AE2-315 SEC3
Adder
1.746
25306009OHH W.
Adder
2.649
963791AG1-232 GEN
Solar/Wind Harmer
8.602
270024AE2-089 GEN
Solar/Wind Harmer
0.007
252524AE2-267 GEN
Solar/Wind Harmer
0.002
970289AG2-191 GEN
Solar/Wind Harmer
1.178
270536AF1-215 GEN2
Solar/Wind Harmer
0.008
958391AF2-133 GEN
Solar/Wind Harmer
0.001
274811UNIV PK N;7U
Adder
4.378
274827FISK ;RP
Adder
6.762
972227AH1-698 GEN1
Adder
2.272
274735ELWOOD EC;4P
Adder
14.27
274744AC1-111 GEN8
Adder
4.832
238109AE1-109 GEN2
Solar/Wind Helper
0.09
238110AE1-109 GEN3
Solar/Wind Helper
0.09
970153AG2-106 GEN
Solar/Wind Harmer
18.586
241955AC1-078 GEN
Solar/Wind Harmer
0.006
241974AD2-163_GEN2
Solar/Wind Harmer
0.005
270588AE1-091_GEN
Solar/Wind Harmer
5.133
24721905FLATG4
Adder
18.986
253370AE2-315 SEC1
Adder
1.846
253371AE2-315 SEC2
Adder
1.746
253316AC1-085 GEN3
Solar/Wind Harmer
0.004
253433AC1-085 GEN1
Solar/Wind Harmer
0.003
946181AF1-283 GEN
Solar/Wind Harmer
8.196
247643Z2-116 C
Solar/Wind Harmer
0
946031AF1-268 GEN
Solar/Wind Harmer
5.934
25194608D.CRK4
Adder
1.462
970289AG2-191 GEN
Solar/Wind Harmer
0.682
970291AG2-192 GEN
Solar/Wind Harmer
0.62
247642Z2-115 C
Solar/Wind Harmer
0.003
270535AF1-215 GEN1
Solar/Wind Harmer
0.008
23906502RICHG2&3
Adder
1.066
24755605MDL-5G
Solar/Wind Harmer
0.001
276806AD2-047 C O1
Solar/Wind Harmer
3.445
274676JOLIET 29;8U
Adder
25.691
274734ELWOOD EC;8P
Adder
14.27
274736ELWOOD EC;9P
Adder
14.27
24728505AND G1
Adder
3.317
943121AE2-341 GEN
Solar/Wind Harmer
10.114
943591AF1-030 GEN
Solar/Wind Harmer
6.726
274682WAUKEGAN ;7U
Adder
15.467
964991AG1-363 GEN
Solar/Wind Helper
4.264
316097T157 G90
Solar/Wind Helper
1.188
237080AD1-060 GEN
Solar/Wind Helper
0.286
24318905MLG2
50/50
6.56
270471AD2-092_GEN
Solar/Wind Harmer
0.005
971655AH1-328 GEN
Solar/Wind Harmer
2.478
270227U2-072_GEN3
Solar/Wind Harmer
0.001
270228U2-072_GEN4
Solar/Wind Harmer
0.001
270231U2-072_GEN5
Solar/Wind Harmer
0.001
276820AF1-078_GEN
Solar/Wind Harmer
0.002
25322209TAIT E
Adder
9.018
25322209TAIT E
Adder
8.815
253370AE2-315 SEC1
Adder
1.846
971677AH1-339 GEN
Solar/Wind Harmer
0.712
253317AC1-085 GEN4
Solar/Wind Harmer
0.004
247621Y3-024
Adder
0.217
965681AG1-436 GEN
Solar/Wind Harmer
7.77
252519AF1-045_GEN
Solar/Wind Harmer
5.405
252516AE2-318_GEN
Solar/Wind Harmer
4.794
971613AH1-306 GEN
Solar/Wind Harmer
2.979
274847GR RIDGE ;BU
Solar/Wind Harmer
0.002
238169AE2-226 GEN1
Solar/Wind Helper
0.575
238170AE2-226 GEN2
Solar/Wind Helper
0.575
238120AE2-309 GEN
Solar/Wind Helper
0.413
23777801MSM_W1-116
Solar/Wind Helper
0.097
237025AB1-124 C
Solar/Wind Helper
0.14
238149AF1-291A_GEN
Solar/Wind Helper
0.114
237061AD1-155 GEN
Solar/Wind Helper
0.043
24318805MLG1
50/50
9.175
270475AD2-096_GEN
50/50
6.148
253338AC1-165 GEN
Solar/Wind Harmer
0.003
972173AH1-669 GEN
Solar/Wind Harmer
3.33
270491AE1-102 GEN2
Solar/Wind Harmer
0.847
970217AG2-149 GEN
Solar/Wind Harmer
5.603
270191TR4_S_V150
Solar/Wind Harmer
0.001
959331AF2-224 GEN
Solar/Wind Harmer
4.506
270258AD1-119 GEN
Solar/Wind Harmer
0.002
970191AG2-125 GEN
Solar/Wind Harmer
1.648
971617AH1-308 GEN
Solar/Wind Harmer
5.264
24642205MAYFLWER
Adder
0.57
270222AC2-111 GEN
Solar/Wind Harmer
3.157
270004AE1-209 GEN
Solar/Wind Harmer
1.348
270575GUS2 35KV
Solar/Wind Harmer
4.246
964401AG1-302 GEN
Solar/Wind Harmer
0.001
270356AE2-297 GEN
Solar/Wind Harmer
0.008
274753CRETE EC ;3U
Adder
7.224
958321AF2-126 GEN
Solar/Wind Harmer
0.812
972038AH1-567 GEN2
Adder
0.318
238148AE2-230_GEN2
Solar/Wind Helper
0.401
237038AE2-054 C
Solar/Wind Helper
0.228
238118U2-030_1
Solar/Wind Helper
0.265
23779801AA1-109
Solar/Wind Helper
0.163
23546401DTGZ2-030
Solar/Wind Helper
0.072
270122AB2-093 CT
50/50
3.544
970149AG2-104 GEN
Solar/Wind Harmer
31.436
270223U2-072_GEN1
Solar/Wind Harmer
0.001
270159DARBY CT4
Adder
8.744
970593AG2-378 GEN
Solar/Wind Harmer
1.551
253325AC1-069 GEN
Solar/Wind Harmer
0.011
270263AC1-001 GEN
Solar/Wind Harmer
0.66
970515AG2-329 GEN
Solar/Wind Harmer
16.808
270510AE1-227 GEN1
Solar/Wind Harmer
1.639
943021AE2-325 GEN
Solar/Wind Harmer
3.267
927014AC1-188 GEN
Solar/Wind Harmer
0.004
970373AG2-245 GEN
Solar/Wind Harmer
12.999
971917AH1-482 GEN
Solar/Wind Harmer
8.008
970773AG2-487 GEN
Solar/Wind Harmer
1.085
24791305MDL-5G
Solar/Wind Harmer
0.001
960001AF2-291 GEN
Solar/Wind Harmer
-0.001
941551AE2-152 GEN
Solar/Wind Harmer
0
23920202STRYCT
Adder
1.209
276691AA1-018 GEN1
Solar/Wind Harmer
0.73
963741AG1-226 GEN
Solar/Wind Harmer
14.236
238108AE1-109 GEN1
Solar/Wind Helper
0.09
235531U2-073 GEN
Solar/Wind Helper
2.566
235054AD2-180 GEN
Solar/Wind Helper
1.552
316095T157 G97
Solar/Wind Helper
1.188
238185AF2-356 C
Solar/Wind Helper
2.051
237030AB1-096 C
Solar/Wind Helper
0.06
CBM West 2LTFEXP_CBM-W2->PJM
CBM
94.63
LGEELTFEXP_LGEE->PJM
CLTF
5.644
MECLTFEXP_MEC->PJM
CLTF
13.455
AH1-155LTFEXP_AH1-155->PJM
LTF
0.306
CBM West 1LTFEXP_CBM-W1->PJM
CBM
123.087
NYPJM->LTFIMP_NY
CLTF
4.259
TVALTFEXP_TVA->PJM
CLTF
6.061
AG2-052LTFEXP_AG2-052->PJM
LTF
0.204
CBM South 2LTFEXP_CBM-S2->PJM
CBM
6.332
CPLELTFEXP_CPLE->PJM
CLTF
0.483
SIGELTFEXP_SIGE->PJM
CLTF
0.424
CBM South 1LTFEXP_CBM-S1->PJM
CBM
24.222
WECLTFEXP_WEC->PJM
CLTF
3.25
LAGNLTFEXP_LAGN->PJM
CLTF
12.385

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-009_SRT-SL


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-009_SRT-SL
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:165.39 %
Rating:1499.0 MVA
Rating Type:B
MVA to Mitigate:2479.15
MW Contribution:2.37
Bus #Bus NameTypeMW Contribution
23906502RICHG2&3
Adder
1.312
270588AE1-091_GEN
Solar/Wind Harmer
6.832
247643Z2-116 C
Solar/Wind Harmer
0.037
270535AF1-215 GEN1
Solar/Wind Harmer
2.093
972181SS23-001
Solar/Wind Harmer
2.694
276806AD2-047 C O1
Solar/Wind Harmer
4.723
274676JOLIET 29;8U
Adder
12.955
274734ELWOOD EC;8P
Adder
7.185
274736ELWOOD EC;9P
Adder
7.185
203830AF1-094 GEN
Solar/Wind Helper
0.322
943121AE2-341 GEN
Solar/Wind Harmer
2.014
943591AF1-030 GEN
Solar/Wind Harmer
1.343
24190002OREGON_ST1
50/50
3.442
971677AH1-339 GEN
Solar/Wind Harmer
6.747
965681AG1-436 GEN
Solar/Wind Harmer
6.102
270227U2-072_GEN3
Solar/Wind Harmer
0.952
270228U2-072_GEN4
Solar/Wind Harmer
0.952
270231U2-072_GEN5
Solar/Wind Harmer
0.952
274847GR RIDGE ;BU
Solar/Wind Harmer
2.199
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241801AE1-079 GEN
Solar/Wind Helper
0.131
241996AE2-282_GEN
Solar/Wind Harmer
2.147
270007AE1-245 C
Solar/Wind Harmer
3.464
246938BC-WTG3
Solar/Wind Harmer
2.302
246937BC-WTG2
Solar/Wind Harmer
2.263
957891AF2-083 GEN
Solar/Wind Harmer
1.844
970611AG2-400 GEN
Solar/Wind Harmer
5.199
274808UNIV PK N;4U
Adder
2.237
274888KELLY CRK;1U
Solar/Wind Harmer
2.607
274770LINCOLN ;1U
Adder
2.736
274771LINCOLN ;2U
Adder
2.736
942221AE2-234 GEN
Solar/Wind Harmer
0.323
972259AH1-714 GEN
Adder
8.361
970321AG2-212 GEN
Solar/Wind Harmer
7.784
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.325
23888702TROY G3
50/50
1.742
972253AH1-711 GEN
50/50
53.201
23860302FRMENG 3
50/50
2.426
241885AC2-103 GEN1
Solar/Wind Harmer
25.595
960841AF2-375 GEN
Solar/Wind Harmer
3.799
247522W1-056 GEN
Solar/Wind Harmer
1.591
246936BC-WTG1
Solar/Wind Harmer
2.263
270489AE1-102 GEN1
Solar/Wind Harmer
0.752
945111AF1-176 GEN
Solar/Wind Harmer
9.795
270505AE1-170 C O1
Solar/Wind Harmer
8.226
965011AG1-365 GEN
Solar/Wind Harmer
5.199
970905AG2-564 GEN
Solar/Wind Harmer
2.368
274751CRETE EC ;1U
Adder
2.22
964861AG1-349 GEN
Solar/Wind Harmer
3.551
274723RIVER EC ;12
Adder
8.075
274801UNIV PARK;4U
Adder
2.578
940581AE2-045 GEN
Solar/Wind Harmer
4.504
971605AH1-302 GEN
Solar/Wind Harmer
3.851
274773LINCOLN ;4U
Adder
2.736
274774LINCOLN ;5U
Adder
2.736
961971AG1-040 GEN
Solar/Wind Helper
0.333
254303AC2-168 GEN
Solar/Wind Helper
0.075
972211AH1-690 GEN
50/50
275.935
970817AG2-515 GEN
Solar/Wind Harmer
14.806
945411AF1-206 GEN
Solar/Wind Harmer
8.02
270499AE1-146 GEN
Solar/Wind Harmer
2.385
270297AD1-101 GEN
Solar/Wind Harmer
1.9
966831AG1-554 GEN
Solar/Wind Harmer
0.712
24191202EL_AA1-006
Adder
0.123
965041AG1-368 GEN
Solar/Wind Harmer
5.428
960681AF2-359 GEN
Solar/Wind Harmer
1.844
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
274814UNIV PK N;0U
Adder
2.266
274807UNIV PK N;3U
Adder
2.261
274805UNIV PK N;1U
Adder
2.251
274776LINCOLN ;7U
Adder
2.736
274687WILL CNTY;4U
Adder
12.261
274687WILL CNTY;4U
Adder
12.261
274731ELWOOD EC;2P
Adder
7.185
274733ELWOOD EC;3P
Adder
7.185
274746AC1-111 G10
Adder
2.416
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
23856402BAYSG1
50/50
1.289
270541AE2-072 C
Solar/Wind Harmer
4.319
270404AC1-167 GEN
Solar/Wind Harmer
0.707
247604X1-042
Adder
0.25
958091AF2-103 GEN
Solar/Wind Harmer
0.094
270247TR4_N_V136
Solar/Wind Harmer
0.459
970031AG2-029 GEN
Solar/Wind Harmer
15.896
970349AG2-230 GEN
Solar/Wind Harmer
7.29
942871AE2-306 GEN
Solar/Wind Harmer
0.437
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.928
972231SS25-0005
Solar/Wind Harmer
4.31
274752CRETE EC ;2U
Adder
2.22
959141AF2-205 GEN
Solar/Wind Harmer
2.693
274826FISK ;BP
Adder
4.849
276772AC2-154 GEN
Solar/Wind Harmer
1.231
972228AH1-698 GEN2
Adder
1.631
939351AE1-166 GEN
Solar/Wind Harmer
2.594
274730ELWOOD EC;6P
Adder
7.185
970707AG2-453 GEN
Solar/Wind Harmer
12.238
970513AG2-328 GEN
Solar/Wind Harmer
7.784
970517AG2-330 GEN
Solar/Wind Harmer
7.06
254305AE2-115 C
Solar/Wind Helper
0.112
24189902OREGON_CT2
50/50
2.559
241840AF1-064_GEN
Solar/Wind Harmer
1.39
23906402RICHG1
Adder
1.315
23906502RICHG2&3
Adder
1.312
241807AE2-176_GEN
Solar/Wind Harmer
3.58
270428AC2-015 C
Solar/Wind Harmer
3.305
965421AG1-410 GEN
Solar/Wind Harmer
17.181
270449AD2-020 GEN
Solar/Wind Harmer
1.572
24695305TIMB G C
Solar/Wind Harmer
3.08
247521TR3_G114
Solar/Wind Harmer
1.816
270246TR4_N_V150
Solar/Wind Harmer
0.459
24639705ELKHART HY
Adder
0.082
270055AF2-134 C O1
Solar/Wind Harmer
1.395
274812UNIV PK N;8U
Adder
2.246
276164X3-005 C
Solar/Wind Harmer
0.314
276776AD2-060 GEN
Solar/Wind Harmer
0.187
972207SS24-0001
Solar/Wind Harmer
9.729
274676JOLIET 29;8U
Adder
13.435
274871GR RIDGE ;2U
Solar/Wind Harmer
3.343
274745AC1-111 GEN9
Adder
2.416
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.129
23920202STRYCT
50/50
1.895
970515AG2-329 GEN
Solar/Wind Harmer
10.186
943021AE2-325 GEN
Solar/Wind Harmer
2.042
270223U2-072_GEN1
Solar/Wind Harmer
0.952
270578AF1-285 GEN2
Solar/Wind Harmer
0.582
970373AG2-245 GEN
Solar/Wind Harmer
9.864
971917AH1-482 GEN
Solar/Wind Harmer
4.098
941551AE2-152 GEN
Solar/Wind Harmer
1.984
23929302BS-PKR
50/50
2.268
958321AF2-126 GEN
Solar/Wind Harmer
1.49
270575GUS2 35KV
Solar/Wind Harmer
10.14
970217AG2-149 GEN
Solar/Wind Harmer
22.462
270258AD1-119 GEN
Solar/Wind Harmer
1.729
270491AE1-102 GEN2
Solar/Wind Harmer
0.752
270191TR4_S_V150
Solar/Wind Harmer
1.62
24642205MAYFLWER
Adder
0.339
959331AF2-224 GEN
Solar/Wind Harmer
5.199
274753CRETE EC ;3U
Adder
2.22
964401AG1-302 GEN
Solar/Wind Harmer
4.106
972038AH1-567 GEN2
Adder
0.161
961961AG1-039 GEN
Solar/Wind Harmer
1.256
971617AH1-308 GEN
Solar/Wind Harmer
2.534
962511AG1-100 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.146
20334926Z1-069 C
Solar/Wind Helper
0.641
971989AH1-539 GEN
Solar/Wind Harmer
7.704
957201AF2-014 GEN
Solar/Wind Harmer
2.623
944161AF1-084 GEN
Solar/Wind Harmer
1.256
270302AB2-170 GEN
Solar/Wind Harmer
4.348
963791AG1-232 GEN
Solar/Wind Harmer
6.504
270536AF1-215 GEN2
Solar/Wind Harmer
2.093
274811UNIV PK N;7U
Adder
2.246
958391AF2-133 GEN
Solar/Wind Harmer
4.069
274827FISK ;RP
Adder
3.436
972227AH1-698 GEN1
Adder
1.148
274735ELWOOD EC;4P
Adder
7.185
270024AE2-089 GEN
Solar/Wind Harmer
2.045
274744AC1-111 GEN8
Adder
2.416
241997AF1-093 GEN
Solar/Wind Helper
0.129
203804AE2-113_GEN
Solar/Wind Helper
0.861
23867002DVBSG1
50/50
12.736
23888502TROY G1
50/50
1.742
23888602TROY G2
50/50
1.742
23860102FRMENG 1
50/50
1.188
23860202FRMENG 2
50/50
1.188
241886AC2-103 GEN2
Solar/Wind Harmer
25.595
971549AH1-272 GEN
Solar/Wind Harmer
12.688
247607V1-011 GEN
Solar/Wind Harmer
2.309
270435AC2-044 GEN
Solar/Wind Harmer
1.157
971771AH1-392 GEN
Solar/Wind Harmer
4.684
971567AH1-282 GEN
Solar/Wind Harmer
7.657
971769AH1-391 GEN
Solar/Wind Harmer
5.074
270071AF1-092 GEN
Solar/Wind Harmer
6.841
274728ELWOOD EC;5P
Adder
7.185
241832AE2-181_GEN
Solar/Wind Harmer
1.946
270044AE2-322 C
Solar/Wind Harmer
0.849
24441205WTRV SLR C
Solar/Wind Harmer
0.079
945111AF1-176 GEN
Solar/Wind Harmer
3.104
965021AG1-366 GEN
Solar/Wind Harmer
1.209
270485AE1-090_GEN
Solar/Wind Harmer
0.314
270043AE2-236 GEN
Solar/Wind Harmer
2.698
274724RIVER EC ;11
Adder
7.979
274802UNIV PARK;5U
Adder
2.587
274800UNIV PARK;3U
Adder
2.578
970941AG2-585 GEN
Solar/Wind Harmer
5.519
274772LINCOLN ;3U
Adder
2.736
276897AD1-100 C
Solar/Wind Harmer
12.695
276893AG1-478 C
Solar/Wind Harmer
0.183
274729ELWOOD EC;1P
Adder
7.185
945641AF1-229 GEN
Solar/Wind Harmer
3.427
965051AG1-369 GEN
Solar/Wind Harmer
2.697
270317AD1-130_GEN
Solar/Wind Harmer
1.667
971347AH1-153 GEN
Solar/Wind Harmer
7.29
972037AH1-567 GEN1
Adder
0.081
960591AF2-350 GEN
Solar/Wind Harmer
4.415
274775LINCOLN ;6U
Adder
2.736
274777LINCOLN ;8U
Adder
2.736
274675JOLIET 29;7U
Adder
13.435
274675JOLIET 29;7U
Adder
12.955
970833AG2-524 GEN
Solar/Wind Harmer
3.797
970833AG2-524 GEN
Solar/Wind Harmer
1.766
203846AF2-130 C
Solar/Wind Helper
0.246
241858AF1-205_GEN
Solar/Wind Harmer
5.472
241808AF1-120 C
Solar/Wind Harmer
1.197
972301AH1-735 GEN
Adder
6.573
270361_3
Solar/Wind Harmer
8.607
944231AF1-091 GEN
Solar/Wind Harmer
2.443
270063AE2-323 C
Solar/Wind Harmer
1.171
270462AD2-086
Solar/Wind Harmer
3.617
270391AF1-285 GEN3
Solar/Wind Harmer
0.582
274754CRETE EC ;4U
Adder
2.22
958381AF2-132 GEN
Solar/Wind Harmer
4.106
241847AF2-150_GEN
Solar/Wind Harmer
1.821
274732ELWOOD EC;7P
Adder
7.185
274674JOLIET 9 ;6U
Adder
6.73
970245AG2-165 GEN
Solar/Wind Harmer
7.784
24189802OREGON_CT1
50/50
2.611
942801AE2-298 GEN
Solar/Wind Harmer
0.877
961051AF2-396 GEN
Solar/Wind Harmer
8.832
961051AF2-396 GEN
Solar/Wind Harmer
4.108
270216AD2-079_GEN
Solar/Wind Harmer
0.32
270224U2-072_GEN2
Solar/Wind Harmer
0.952
274803UNIV PARK;6U
Adder
2.587
274887GEN-1.85
Solar/Wind Harmer
2.354
274674JOLIET 9 ;6U
Adder
6.73
203947AF1-006 C
Solar/Wind Helper
0.379
241967AE2-285_GEN
Solar/Wind Helper
0.337
23888802TROY G4
50/50
1.742
960981AF2-389 GEN
Solar/Wind Harmer
0.827
247620Y3-023
Adder
0.247
270526AF1-158 GEN
Solar/Wind Harmer
2.317
24441505OLIV SLR
Solar/Wind Harmer
0.068
965791AG1-447 GEN
Solar/Wind Harmer
3.122
971231AH1-075 GEN
Solar/Wind Harmer
0.379
276843GEN-1.7
Solar/Wind Harmer
0.253
958011AF2-095 GEN
Solar/Wind Harmer
6.358
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
990527J1329
External Queue
1.7522491216659546
991177J1571 G
External Queue
14.786787033081055
991182J1586 G
External Queue
23.962841033935547
990142J1224
External Queue
12.808939933776855
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
CPLELTFEXP_CPLE->PJM
CLTF
0.311
SIGELTFEXP_SIGE->PJM
CLTF
0.163
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.6
WECLTFEXP_WEC->PJM
CLTF
1.601
LAGNLTFEXP_LAGN->PJM
CLTF
4.78
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.23
LGEELTFEXP_LGEE->PJM
CLTF
1.95
MECLTFEXP_MEC->PJM
CLTF
6.243
AH1-155LTFEXP_AH1-155->PJM
LTF
0.155
CBM West 1LTFEXP_CBM-W1->PJM
CBM
90.542
NYPJM->LTFIMP_NY
CLTF
2.01
TVALTFEXP_TVA->PJM
CLTF
2.169
AG2-052LTFEXP_AG2-052->PJM
LTF
0.103

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P2-3_OEC-345-1152-3_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P2-3_OEC-345-1152-3_SRT-A
Contingency Type:Breaker
DC|AC:AC
Final Cycle Loading:142.16 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2556.01
MW Contribution:2.18
Bus #Bus NameTypeMW Contribution
241996AE2-282_GEN
Solar/Wind Harmer
2.159
270007AE1-245 C
Solar/Wind Harmer
3.473
246938BC-WTG3
Solar/Wind Harmer
2.311
23867002DVBSG1
50/50
13.062
23888502TROY G1
50/50
1.764
23888602TROY G2
50/50
1.764
241886AC2-103 GEN2
Solar/Wind Harmer
25.888
971549AH1-272 GEN
Solar/Wind Harmer
12.795
247607V1-011 GEN
Solar/Wind Harmer
2.315
270435AC2-044 GEN
Solar/Wind Harmer
1.161
971771AH1-392 GEN
Solar/Wind Harmer
4.715
971769AH1-391 GEN
Solar/Wind Harmer
5.107
971567AH1-282 GEN
Solar/Wind Harmer
7.577
270071AF1-092 GEN
Solar/Wind Harmer
6.875
274728ELWOOD EC;5P
Adder
7.227
241832AE2-181_GEN
Solar/Wind Harmer
1.957
270044AE2-322 C
Solar/Wind Harmer
0.852
24441205WTRV SLR C
Solar/Wind Harmer
0.08
945111AF1-176 GEN
Solar/Wind Harmer
3.126
965021AG1-366 GEN
Solar/Wind Harmer
1.215
270485AE1-090_GEN
Solar/Wind Harmer
0.315
270043AE2-236 GEN
Solar/Wind Harmer
2.712
274724RIVER EC ;11
Adder
8.026
274802UNIV PARK;5U
Adder
2.602
274800UNIV PARK;3U
Adder
2.593
970941AG2-585 GEN
Solar/Wind Harmer
5.551
274772LINCOLN ;3U
Adder
2.752
276897AD1-100 C
Solar/Wind Harmer
12.768
276893AG1-478 C
Solar/Wind Harmer
0.184
274729ELWOOD EC;1P
Adder
7.227
23888702TROY G3
50/50
1.764
972253AH1-711 GEN
50/50
53.875
241885AC2-103 GEN1
Solar/Wind Harmer
25.888
960841AF2-375 GEN
Solar/Wind Harmer
3.755
247522W1-056 GEN
Solar/Wind Harmer
1.573
246936BC-WTG1
Solar/Wind Harmer
2.271
270489AE1-102 GEN1
Solar/Wind Harmer
0.755
945111AF1-176 GEN
Solar/Wind Harmer
9.863
270505AE1-170 C O1
Solar/Wind Harmer
8.284
965011AG1-365 GEN
Solar/Wind Harmer
5.223
274751CRETE EC ;1U
Adder
2.233
964861AG1-349 GEN
Solar/Wind Harmer
3.572
274723RIVER EC ;12
Adder
8.123
274801UNIV PARK;4U
Adder
2.593
940581AE2-045 GEN
Solar/Wind Harmer
4.53
971605AH1-302 GEN
Solar/Wind Harmer
3.873
274773LINCOLN ;4U
Adder
2.752
274774LINCOLN ;5U
Adder
2.752
970905AG2-564 GEN
Solar/Wind Harmer
2.184
961971AG1-040 GEN
Solar/Wind Helper
0.333
254303AC2-168 GEN
Solar/Wind Helper
0.075
945641AF1-229 GEN
Solar/Wind Harmer
3.434
965051AG1-369 GEN
Solar/Wind Harmer
2.706
270317AD1-130_GEN
Solar/Wind Harmer
1.67
971347AH1-153 GEN
Solar/Wind Harmer
7.336
972037AH1-567 GEN1
Adder
0.082
960591AF2-350 GEN
Solar/Wind Harmer
4.441
274775LINCOLN ;6U
Adder
2.752
274777LINCOLN ;8U
Adder
2.752
274675JOLIET 29;7U
Adder
13.513
274675JOLIET 29;7U
Adder
13.03
970833AG2-524 GEN
Solar/Wind Harmer
3.819
970833AG2-524 GEN
Solar/Wind Harmer
1.776
203846AF2-130 C
Solar/Wind Helper
0.247
23856402BAYSG1
50/50
1.286
241858AF1-205_GEN
Solar/Wind Harmer
5.501
241808AF1-120 C
Solar/Wind Harmer
1.204
972301AH1-735 GEN
Adder
6.601
270361_3
Solar/Wind Harmer
8.502
944231AF1-091 GEN
Solar/Wind Harmer
2.455
270063AE2-323 C
Solar/Wind Harmer
1.178
270462AD2-086
Solar/Wind Harmer
3.624
270391AF1-285 GEN3
Solar/Wind Harmer
0.583
274754CRETE EC ;4U
Adder
2.233
958381AF2-132 GEN
Solar/Wind Harmer
4.13
274732ELWOOD EC;7P
Adder
7.227
274674JOLIET 9 ;6U
Adder
6.769
970245AG2-165 GEN
Solar/Wind Harmer
7.828
24189802OREGON_CT1
50/50
2.65
942801AE2-298 GEN
Solar/Wind Harmer
0.88
961051AF2-396 GEN
Solar/Wind Harmer
8.895
961051AF2-396 GEN
Solar/Wind Harmer
4.137
270216AD2-079_GEN
Solar/Wind Harmer
0.322
270224U2-072_GEN2
Solar/Wind Harmer
0.954
274803UNIV PARK;6U
Adder
2.602
274887GEN-1.85
Solar/Wind Harmer
2.367
274674JOLIET 9 ;6U
Adder
6.769
274693ROCKY RD ;1P
Adder
4.758
274683WAUKEGAN ;8U
Adder
9.089
274683WAUKEGAN ;8U
Adder
7.662
203947AF1-006 C
Solar/Wind Helper
0.379
241967AE2-285_GEN
Solar/Wind Helper
0.337
971989AH1-539 GEN
Solar/Wind Harmer
7.631
957201AF2-014 GEN
Solar/Wind Harmer
2.633
944161AF1-084 GEN
Solar/Wind Harmer
1.265
270302AB2-170 GEN
Solar/Wind Harmer
4.356
963791AG1-232 GEN
Solar/Wind Harmer
6.532
270536AF1-215 GEN2
Solar/Wind Harmer
2.105
274811UNIV PK N;7U
Adder
2.26
958391AF2-133 GEN
Solar/Wind Harmer
4.092
274827FISK ;RP
Adder
3.457
972227AH1-698 GEN1
Adder
1.155
274735ELWOOD EC;4P
Adder
7.227
270024AE2-089 GEN
Solar/Wind Harmer
2.053
274744AC1-111 GEN8
Adder
2.43
241997AF1-093 GEN
Solar/Wind Helper
0.13
203804AE2-113_GEN
Solar/Wind Helper
0.862
270541AE2-072 C
Solar/Wind Harmer
4.321
270404AC1-167 GEN
Solar/Wind Harmer
0.709
247604X1-042
Adder
0.252
958091AF2-103 GEN
Solar/Wind Harmer
0.095
270247TR4_N_V136
Solar/Wind Harmer
0.461
970031AG2-029 GEN
Solar/Wind Harmer
15.991
970349AG2-230 GEN
Solar/Wind Harmer
7.336
942871AE2-306 GEN
Solar/Wind Harmer
0.438
270391AF1-285 GEN3
Solar/Wind Harmer
0.224
270377AD1-106 GEN
Solar/Wind Harmer
2.871
972231SS25-0005
Solar/Wind Harmer
4.336
274752CRETE EC ;2U
Adder
2.233
959141AF2-205 GEN
Solar/Wind Harmer
2.708
274826FISK ;BP
Adder
4.877
276772AC2-154 GEN
Solar/Wind Harmer
1.239
972228AH1-698 GEN2
Adder
1.64
939351AE1-166 GEN
Solar/Wind Harmer
2.609
274730ELWOOD EC;6P
Adder
7.227
970707AG2-453 GEN
Solar/Wind Harmer
12.309
970513AG2-328 GEN
Solar/Wind Harmer
7.828
970517AG2-330 GEN
Solar/Wind Harmer
7.1
254305AE2-115 C
Solar/Wind Helper
0.112
23929302BS-PKR
50/50
2.264
958321AF2-126 GEN
Solar/Wind Harmer
1.492
270575GUS2 35KV
Solar/Wind Harmer
10.016
970217AG2-149 GEN
Solar/Wind Harmer
22.356
270258AD1-119 GEN
Solar/Wind Harmer
1.735
270491AE1-102 GEN2
Solar/Wind Harmer
0.755
270191TR4_S_V150
Solar/Wind Harmer
1.626
24642205MAYFLWER
Adder
0.342
959331AF2-224 GEN
Solar/Wind Harmer
5.223
274753CRETE EC ;3U
Adder
2.233
964401AG1-302 GEN
Solar/Wind Harmer
4.13
972038AH1-567 GEN2
Adder
0.162
971617AH1-308 GEN
Solar/Wind Harmer
2.543
962511AG1-100 GEN
Solar/Wind Helper
0.34
959441AF2-235 GEN
Solar/Wind Helper
0.146
20334926Z1-069 C
Solar/Wind Helper
0.642
972211AH1-690 GEN
50/50
279.989
970817AG2-515 GEN
Solar/Wind Harmer
14.956
945411AF1-206 GEN
Solar/Wind Harmer
8.063
270499AE1-146 GEN
Solar/Wind Harmer
2.36
270297AD1-101 GEN
Solar/Wind Harmer
1.901
966831AG1-554 GEN
Solar/Wind Harmer
0.706
965041AG1-368 GEN
Solar/Wind Harmer
5.449
960681AF2-359 GEN
Solar/Wind Harmer
1.856
270578AF1-285 GEN2
Solar/Wind Harmer
0.224
274814UNIV PK N;0U
Adder
2.28
274807UNIV PK N;3U
Adder
2.275
274805UNIV PK N;1U
Adder
2.265
274776LINCOLN ;7U
Adder
2.752
274687WILL CNTY;4U
Adder
12.332
274687WILL CNTY;4U
Adder
12.332
274731ELWOOD EC;2P
Adder
7.227
274733ELWOOD EC;3P
Adder
7.227
274746AC1-111 G10
Adder
2.43
241982AE2-343 S C
Solar/Wind Helper
0.117
254304AE2-114 C
Solar/Wind Helper
0.112
23888802TROY G4
50/50
1.764
960981AF2-389 GEN
Solar/Wind Harmer
0.832
247620Y3-023
Adder
0.249
270526AF1-158 GEN
Solar/Wind Harmer
2.332
24441505OLIV SLR
Solar/Wind Harmer
0.068
965791AG1-447 GEN
Solar/Wind Harmer
3.142
971231AH1-075 GEN
Solar/Wind Harmer
0.372
276843GEN-1.7
Solar/Wind Harmer
0.255
958011AF2-095 GEN
Solar/Wind Harmer
6.395
274695ROCKY RD ;2P
Adder
4.805
946381AF1-302 GEN
Solar/Wind Helper
0.105
238217AF1-153 C O1
Solar/Wind Helper
0.111
24189902OREGON_CT2
50/50
2.596
241840AF1-064_GEN
Solar/Wind Harmer
1.392
23906402RICHG1
Adder
1.32
23906502RICHG2&3
Adder
1.318
241807AE2-176_GEN
Solar/Wind Harmer
2.785
965421AG1-410 GEN
Solar/Wind Harmer
17.247
270449AD2-020 GEN
Solar/Wind Harmer
1.583
270428AC2-015 C
Solar/Wind Harmer
3.089
24695305TIMB G C
Solar/Wind Harmer
3.089
247521TR3_G114
Solar/Wind Harmer
1.822
270246TR4_N_V150
Solar/Wind Harmer
0.461
24639705ELKHART HY
Adder
0.082
270055AF2-134 C O1
Solar/Wind Harmer
1.403
274812UNIV PK N;8U
Adder
2.26
276164X3-005 C
Solar/Wind Harmer
0.316
276776AD2-060 GEN
Solar/Wind Harmer
0.188
972207SS24-0001
Solar/Wind Harmer
9.786
274676JOLIET 29;8U
Adder
13.513
274871GR RIDGE ;2U
Solar/Wind Harmer
3.362
274745AC1-111 GEN9
Adder
2.43
274682WAUKEGAN ;7U
Adder
7.759
274828WAUKEGAN ;BP
Adder
4.764
203835AF1-098 GEN
Solar/Wind Helper
1.311
203860AG1-193 C
Solar/Wind Helper
0.149
241966AE1-183 GEN
Solar/Wind Helper
0.13
23906502RICHG2&3
Adder
1.318
270588AE1-091_GEN
Solar/Wind Harmer
6.791
247643Z2-116 C
Solar/Wind Harmer
0.037
270535AF1-215 GEN1
Solar/Wind Harmer
2.105
972181SS23-001
Solar/Wind Harmer
2.71
276806AD2-047 C O1
Solar/Wind Harmer
4.751
274676JOLIET 29;8U
Adder
13.03
274734ELWOOD EC;8P
Adder
7.227
274736ELWOOD EC;9P
Adder
7.227
274682WAUKEGAN ;7U
Adder
7.759
203830AF1-094 GEN
Solar/Wind Helper
0.322
943121AE2-341 GEN
Solar/Wind Harmer
3.856
943591AF1-030 GEN
Solar/Wind Harmer
2.571
23920202STRYCT
50/50
1.905
970515AG2-329 GEN
Solar/Wind Harmer
10.138
943021AE2-325 GEN
Solar/Wind Harmer
2.057
270223U2-072_GEN1
Solar/Wind Harmer
0.954
270578AF1-285 GEN2
Solar/Wind Harmer
0.583
970373AG2-245 GEN
Solar/Wind Harmer
9.924
971917AH1-482 GEN
Solar/Wind Harmer
4.122
941551AE2-152 GEN
Solar/Wind Harmer
1.995
24190002OREGON_ST1
50/50
3.493
971677AH1-339 GEN
Solar/Wind Harmer
6.666
965681AG1-436 GEN
Solar/Wind Harmer
6.141
270227U2-072_GEN3
Solar/Wind Harmer
0.954
270228U2-072_GEN4
Solar/Wind Harmer
0.954
270231U2-072_GEN5
Solar/Wind Harmer
0.954
274847GR RIDGE ;BU
Solar/Wind Harmer
2.211
203980AG1-197 GEN
Solar/Wind Helper
0.248
203979AG1-198 GEN
Solar/Wind Helper
0.193
241801AE1-079 GEN
Solar/Wind Helper
0.131
246937BC-WTG2
Solar/Wind Harmer
2.271
957891AF2-083 GEN
Solar/Wind Harmer
1.857
970611AG2-400 GEN
Solar/Wind Harmer
5.223
274808UNIV PK N;4U
Adder
2.25
274888KELLY CRK;1U
Solar/Wind Harmer
2.622
274770LINCOLN ;1U
Adder
2.752
274771LINCOLN ;2U
Adder
2.752
942221AE2-234 GEN
Solar/Wind Harmer
0.324
972259AH1-714 GEN
Adder
8.409
970321AG2-212 GEN
Solar/Wind Harmer
7.828
274696ROCKY RD ;4P
Adder
4.919
274697ROCKY RD ;3P
Adder
1.305
241985AE1-237 GEN
Solar/Wind Helper
0.131
962101AG1-054 GEN
Solar/Wind Helper
0.326
990527J1329
External Queue
1.7751743793487549
991177J1571 G
External Queue
14.956707954406738
991182J1586 G
External Queue
24.279396057128906
990142J1224
External Queue
12.976524353027344
CBM West 2LTFEXP_CBM-W2->PJM
CBM
38.387
LGEELTFEXP_LGEE->PJM
CLTF
1.955
MECLTFEXP_MEC->PJM
CLTF
6.275
AH1-155LTFEXP_AH1-155->PJM
LTF
0.156
CBM West 1LTFEXP_CBM-W1->PJM
CBM
91.319
NYPJM->LTFIMP_NY
CLTF
2.013
TVALTFEXP_TVA->PJM
CLTF
2.176
AG2-052LTFEXP_AG2-052->PJM
LTF
0.104
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.107
CPLELTFEXP_CPLE->PJM
CLTF
0.309
SIGELTFEXP_SIGE->PJM
CLTF
0.163
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.626
WECLTFEXP_WEC->PJM
CLTF
1.61
LAGNLTFEXP_LAGN->PJM
CLTF
4.798

Details for AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line l/o ATSI_P1-2_OEC-345-809_SRT-A


Base Case Flowgate

Area:ATSI
Facility Description:
AC2-103 TAP-02BEAVER 345.0 kV Ckt 1 line
Contingency Name:
ATSI_P1-2_OEC-345-809_SRT-A
Contingency Type:Single
DC|AC:AC
Final Cycle Loading:117.76 %
Rating:1798.0 MVA
Rating Type:B
MVA to Mitigate:2117.36
MW Contribution:1.73
Bus #Bus NameTypeMW Contribution
23888702TROY G3
50/50
1.734
972253AH1-711 GEN
50/50
52.952
241885AC2-103 GEN1
Solar/Wind Harmer
-0.001
960841AF2-375 GEN
Solar/Wind Harmer
-0.002
247522W1-056 GEN
Solar/Wind Harmer
0.001
246936BC-WTG1
Solar/Wind Harmer
0.162
270489AE1-102 GEN1
Solar/Wind Harmer
0.52
945111AF1-176 GEN
Solar/Wind Harmer
6.783
270505AE1-170 C O1
Solar/Wind Harmer
3.988
965011AG1-365 GEN
Solar/Wind Harmer
3.597
970905AG2-564 GEN
Solar/Wind Harmer
1.725
274751CRETE EC ;1U
Adder
3.712
964861AG1-349 GEN
Solar/Wind Harmer
0
274723RIVER EC ;12
Adder
8.011
274801UNIV PARK;4U
Adder
2.557
940581AE2-045 GEN
Solar/Wind Harmer
-0.001
971605AH1-302 GEN
Solar/Wind Harmer
3.82
274773LINCOLN ;4U
Adder
3.695
274774LINCOLN ;5U
Adder
3.695
961971AG1-040 GEN
Solar/Wind Helper
0.329
254303AC2-168 GEN
Solar/Wind Helper
0.075
23888802TROY G4
50/50
1.734
247620Y3-023
Adder
0.245
270526AF1-158 GEN
Solar/Wind Harmer
0.004
24441505OLIV SLR
Solar/Wind Harmer
0
965791AG1-447 GEN
Solar/Wind Harmer
3.098
971231AH1-075 GEN
Solar/Wind Harmer
0.372
276843GEN-1.7
Solar/Wind Harmer
0.099
958011AF2-095 GEN
Solar/Wind Harmer
4.4
946381AF1-302 GEN
Solar/Wind Helper
0.103
241996AE2-282_GEN
Solar/Wind Harmer
0.005
970621AG2-405 GEN
Solar/Wind Harmer
0.864
970623AG2-406 GEN
Solar/Wind Harmer
0.785
270007AE1-245 C
Solar/Wind Harmer
0.001
246938BC-WTG3
Solar/Wind Harmer
0.145
246937BC-WTG2
Solar/Wind Harmer
0.162
24189802OREGON_CT1
50/50
2.6
961051AF2-396 GEN
Solar/Wind Harmer
7.707
961051AF2-396 GEN
Solar/Wind Harmer
5.138
270216AD2-079_GEN
Solar/Wind Harmer
0.001
970627AG2-408 GEN
Solar/Wind Harmer
1.079
270224U2-072_GEN2
Solar/Wind Harmer
0
274803UNIV PARK;6U
Adder
2.566
274887GEN-1.85
Solar/Wind Harmer
0.08
274674JOLIET 9 ;6U
Adder
6.676
203947AF1-006 C
Solar/Wind Helper
0.375
241967AE2-285_GEN
Solar/Wind Helper
0.334
24189902OREGON_CT2
50/50
2.548
241840AF1-064_GEN
Solar/Wind Harmer
0.004
23906402RICHG1
Adder
1.305
23906502RICHG2&3
Adder
1.303
241807AE2-176_GEN
Solar/Wind Harmer
0.004
270428AC2-015 C
Solar/Wind Harmer
0.002
965421AG1-410 GEN
Solar/Wind Harmer
11.884
270449AD2-020 GEN
Solar/Wind Harmer
0
24695305TIMB G C
Solar/Wind Harmer
0.001
247521TR3_G114
Solar/Wind Harmer
0.136
270246TR4_N_V150
Solar/Wind Harmer
0.024
24639705ELKHART HY
Adder
0.081
270055AF2-134 C O1
Solar/Wind Harmer
0.002
274812UNIV PK N;8U
Adder
2.229
276164X3-005 C
Solar/Wind Harmer
0
276776AD2-060 GEN
Solar/Wind Harmer
0.319
274676JOLIET 29;8U
Adder
13.326
274871GR RIDGE ;2U
Solar/Wind Harmer
0
203835AF1-098 GEN
Solar/Wind Helper
1.297
203860AG1-193 C
Solar/Wind Helper
0.147
241966AE1-183 GEN
Solar/Wind Helper
0.128
971989AH1-539 GEN
Solar/Wind Harmer
1.766
957201AF2-014 GEN
Solar/Wind Harmer
0
270302AB2-170 GEN
Solar/Wind Harmer
0.002
971653AH1-327 GEN
Solar/Wind Harmer
0.505
963791AG1-232 GEN
Solar/Wind Harmer
4.499
270536AF1-215 GEN2
Solar/Wind Harmer
0.004
274811UNIV PK N;7U
Adder
2.229
958391AF2-133 GEN
Solar/Wind Harmer
0
274827FISK ;RP
Adder
3.409
972227AH1-698 GEN1
Adder
1.139
274735ELWOOD EC;4P
Adder
7.127
270024AE2-089 GEN
Solar/Wind Harmer
0.003
241997AF1-093 GEN
Solar/Wind Helper
0.128
203804AE2-113_GEN
Solar/Wind Helper
0.852
972211AH1-690 GEN
50/50
274.788
970817AG2-515 GEN
Solar/Wind Harmer
10.276
945411AF1-206 GEN
Solar/Wind Harmer
-0.001
270499AE1-146 GEN
Solar/Wind Harmer
0.029
270297AD1-101 GEN
Solar/Wind Harmer
0.001
965041AG1-368 GEN
Solar/Wind Harmer
3.755
24191202EL_AA1-006
Adder
0.112
960681AF2-359 GEN
Solar/Wind Harmer
-0.001
270578AF1-285 GEN2
Solar/Wind Harmer
0.222
274814UNIV PK N;0U
Adder
2.248
274807UNIV PK N;3U
Adder
2.243
274805UNIV PK N;1U
Adder
2.233
274776LINCOLN ;7U
Adder
3.695
274687WILL CNTY;4U
Adder
12.162
274687WILL CNTY;4U
Adder
12.162
274731ELWOOD EC;2P
Adder
7.127
274733ELWOOD EC;3P
Adder
7.127
241982AE2-343 S C
Solar/Wind Helper
0.116
254304AE2-114 C
Solar/Wind Helper
0.111
945641AF1-229 GEN
Solar/Wind Harmer
0.001
971619AH1-309 GEN
Solar/Wind Harmer
1.709
965051AG1-369 GEN
Solar/Wind Harmer
1.865
270317AD1-130_GEN
Solar/Wind Harmer
0.005
971347AH1-153 GEN
Solar/Wind Harmer
5.047
972037AH1-567 GEN1
Adder
0.081
971611AH1-305 GEN
Solar/Wind Harmer
1.819
960591AF2-350 GEN
Solar/Wind Harmer
3.056
274775LINCOLN ;6U
Adder
3.695
274777LINCOLN ;8U
Adder
3.695
274675JOLIET 29;7U
Adder
13.327
274675JOLIET 29;7U
Adder
12.851
970833AG2-524 GEN
Solar/Wind Harmer
3.311
970833AG2-524 GEN
Solar/Wind Harmer
2.207
203846AF2-130 C
Solar/Wind Helper
0.244
957891AF2-083 GEN
Solar/Wind Harmer
0.001
970611AG2-400 GEN
Solar/Wind Harmer
3.597
274808UNIV PK N;4U
Adder
2.219
274888KELLY CRK;1U
Solar/Wind Harmer
0.179
274770LINCOLN ;1U
Adder
3.695
274771LINCOLN ;2U
Adder
3.695
942221AE2-234 GEN
Solar/Wind Harmer
0.015
972259AH1-714 GEN
Adder
8.293
970321AG2-212 GEN
Solar/Wind Harmer
1.307
241985AE1-237 GEN
Solar/Wind Helper
0.129
962101AG1-054 GEN
Solar/Wind Helper
0.322
23867002DVBSG1
50/50
12.718
23888502TROY G1
50/50
1.734
23888602TROY G2
50/50
1.734
241886AC2-103 GEN2
Solar/Wind Harmer
-0.001
971549AH1-272 GEN
Solar/Wind Harmer
9.816
247607V1-011 GEN
Solar/Wind Harmer
0.001
270435AC2-044 GEN
Solar/Wind Harmer
0.507
971771AH1-392 GEN
Solar/Wind Harmer
3.604
971769AH1-391 GEN
Solar/Wind Harmer
3.923
971567AH1-282 GEN
Solar/Wind Harmer
5.235
270071AF1-092 GEN
Solar/Wind Harmer
6.048
274728ELWOOD EC;5P
Adder
7.127
241832AE2-181_GEN
Solar/Wind Harmer
0.003
24441205WTRV SLR C
Solar/Wind Harmer
0
945111AF1-176 GEN
Solar/Wind Harmer
3.081
965021AG1-366 GEN
Solar/Wind Harmer
1.199
270485AE1-090_GEN
Solar/Wind Harmer
0.001
270043AE2-236 GEN
Solar/Wind Harmer
2.178
274724RIVER EC ;11
Adder
7.915
274802UNIV PARK;5U
Adder
2.566
274800UNIV PARK;3U
Adder
2.557
970941AG2-585 GEN
Solar/Wind Harmer
3.82
274772LINCOLN ;3U
Adder
3.695
276897AD1-100 C
Solar/Wind Harmer
0.004
276893AG1-478 C
Solar/Wind Harmer
0.12
274729ELWOOD EC;1P
Adder
7.127
270541AE2-072 C
Solar/Wind Harmer
0.008
270404AC1-167 GEN
Solar/Wind Harmer
0.002
247604X1-042
Adder
0.248
270247TR4_N_V136
Solar/Wind Harmer
0.024
970031AG2-029 GEN
Solar/Wind Harmer
2.384
970349AG2-230 GEN
Solar/Wind Harmer
5.047
270391AF1-285 GEN3
Solar/Wind Harmer
0.222
270377AD1-106 GEN
Solar/Wind Harmer
1.233
274752CRETE EC ;2U
Adder
3.712
959141AF2-205 GEN
Solar/Wind Harmer
-0.001
274826FISK ;BP
Adder
4.81
972228AH1-698 GEN2
Adder
1.618
939351AE1-166 GEN
Solar/Wind Harmer
0
274730ELWOOD EC;6P
Adder
7.127
970707AG2-453 GEN
Solar/Wind Harmer
9.881
970513AG2-328 GEN
Solar/Wind Harmer
1.307
970517AG2-330 GEN
Solar/Wind Harmer
7.843
254305AE2-115 C
Solar/Wind Helper
0.111
23856402BAYSG1
50/50
1.279
241858AF1-205_GEN
Solar/Wind Harmer
3.794
241808AF1-120 C
Solar/Wind Harmer
0.003
972301AH1-735 GEN
Adder
6.527
270361_3
Solar/Wind Harmer
4.647
944231AF1-091 GEN
Solar/Wind Harmer
1.197
270063AE2-323 C
Solar/Wind Harmer
0.003
270462AD2-086
Solar/Wind Harmer
0.008
274754CRETE EC ;4U
Adder
3.712
958381AF2-132 GEN
Solar/Wind Harmer
0
274732ELWOOD EC;7P
Adder
7.127
274674JOLIET 9 ;6U
Adder
6.676
970245AG2-165 GEN
Solar/Wind Harmer
1.307
23906502RICHG2&3
Adder
1.303
270588AE1-091_GEN
Solar/Wind Harmer
3.347
247643Z2-116 C
Solar/Wind Harmer
0
270535AF1-215 GEN1
Solar/Wind Harmer
0.004
276806AD2-047 C O1
Solar/Wind Harmer
1.732
274676JOLIET 29;8U
Adder
12.851
274734ELWOOD EC;8P
Adder
7.127
274736ELWOOD EC;9P
Adder
7.127
203830AF1-094 GEN
Solar/Wind Helper
0.318
24190002OREGON_ST1
50/50
3.428
971677AH1-339 GEN
Solar/Wind Harmer
0.654
965681AG1-436 GEN
Solar/Wind Harmer
4.224
270227U2-072_GEN3
Solar/Wind Harmer
0
270228U2-072_GEN4
Solar/Wind Harmer
0
270231U2-072_GEN5
Solar/Wind Harmer
0
274847GR RIDGE ;BU
Solar/Wind Harmer
0.001
203980AG1-197 GEN
Solar/Wind Helper
0.245
203979AG1-198 GEN
Solar/Wind Helper
0.191
241801AE1-079 GEN
Solar/Wind Helper
0.13
23929302BS-PKR
50/50
2.251
958321AF2-126 GEN
Solar/Wind Harmer
1.147
270575GUS2 35KV
Solar/Wind Harmer
4.647
970217AG2-149 GEN
Solar/Wind Harmer
4.178
270258AD1-119 GEN
Solar/Wind Harmer
0.001
270491AE1-102 GEN2
Solar/Wind Harmer
0.52
270191TR4_S_V150
Solar/Wind Harmer
0
24642205MAYFLWER
Adder
0.337
959331AF2-224 GEN
Solar/Wind Harmer
2.518
274753CRETE EC ;3U
Adder
3.712
964401AG1-302 GEN
Solar/Wind Harmer
0
972038AH1-567 GEN2
Adder
0.16
971617AH1-308 GEN
Solar/Wind Harmer
2.511
962511AG1-100 GEN
Solar/Wind Helper
0.336
959441AF2-235 GEN
Solar/Wind Helper
0.145
20334926Z1-069 C
Solar/Wind Helper
0.635
23920202STRYCT
50/50
1.883
970515AG2-329 GEN
Solar/Wind Harmer
12.533
943021AE2-325 GEN
Solar/Wind Harmer
2.028
270223U2-072_GEN1
Solar/Wind Harmer
0
970373AG2-245 GEN
Solar/Wind Harmer
6.828
971917AH1-482 GEN
Solar/Wind Harmer
4.065
941551AE2-152 GEN
Solar/Wind Harmer
0
990527J1329
External Queue
1.745489239692688
991177J1571 G
External Queue
14.724894523620605
991182J1586 G
External Queue
23.868927001953125
990142J1224
External Queue
12.759525299072266
CBM South 2LTFEXP_CBM-S2->PJM
CBM
2.079
CPLELTFEXP_CPLE->PJM
CLTF
0.305
SIGELTFEXP_SIGE->PJM
CLTF
0.161
CBM South 1LTFEXP_CBM-S1->PJM
CBM
8.514
WECLTFEXP_WEC->PJM
CLTF
1.588
LAGNLTFEXP_LAGN->PJM
CLTF
4.735
CBM West 2LTFEXP_CBM-W2->PJM
CBM
37.878
LGEELTFEXP_LGEE->PJM
CLTF
1.931
MECLTFEXP_MEC->PJM
CLTF
6.19
AH1-155LTFEXP_AH1-155->PJM
LTF
0.153
CBM West 1LTFEXP_CBM-W1->PJM
CBM
89.942
NYPJM->LTFIMP_NY
CLTF
1.99
TVALTFEXP_TVA->PJM
CLTF
2.148
AG2-052LTFEXP_AG2-052->PJM
LTF
0.102
CONTINGENCY 'AP_P1-2_WP-500-303T_SRT-A'
 DISCONNECT BRANCH FROM BUS 235104 TO BUS 200011 CKT 1   /*01CABOT      500.0 - KEYSTONE     500.0
END
CONTINGENCY 'ATSI_P7-1_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-901_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 1 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-007A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 2          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-031_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 2   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-002_SRT-A'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238607 CKT 1   /*02BEAVER     345.0 - 02CARLIL     345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1   /*02BEAVER     345.0 - 02LAKEAVE    345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-003_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239725 CKT 1          /*02BEAVER     345.0 - 02LAKEAVE    345.0
 SET POSTCONTRATING 1394 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 238566 TO BUS 238569 CKT 1 /*02WLORAIN    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-028_SRT-A'
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 238569 CKT 1   /*02LAKEAVE    345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239725 TO BUS 239726 CKT 1   /*02LAKEAVE    345.0 - 02LAKEAVE    138.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-1152-3_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 239290 CKT 1   /*02HAYES      345.0 - 02HAYES      138.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-809_SRT-A'
 DISCONNECT BRANCH FROM BUS 239289 TO BUS 238569 CKT 1   /*02HAYES      345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-005_SRT-A'
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239171 CKT 2   /*02WLORAIN    345.0 - 02WLORG-2     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239172 CKT 3   /*02WLORAIN    345.0 - 02WLORG-3     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239173 CKT 4   /*02WLORAIN    345.0 - 02WLORG-4     13.8
 DISCONNECT BRANCH FROM BUS 238566 TO BUS 239174 CKT 5   /*02WLORAIN    345.0 - 02WLORG-5     13.8
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238566 CKT 1   /*02BEAVER     345.0 - 02WLORAIN    345.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1   /*02BEAVER     345.0 - AC2-103 TAP  345.0
 DISCONNECT BUS 239171                                   /*02WLORG-2     13.8
 DISCONNECT BUS 239172                                   /*02WLORG-3     13.8
 DISCONNECT BUS 239173                                   /*02WLORG-4     13.8
 DISCONNECT BUS 239174                                   /*02WLORG-5     13.8
 REMOVE MACHINE 2 FROM BUS 239171                        /*02WLORG-2     13.8
 REMOVE MACHINE 3 FROM BUS 239172                        /*02WLORG-3     13.8
 REMOVE MACHINE 4 FROM BUS 239173                        /*02WLORG-4     13.8
 REMOVE MACHINE 5 FROM BUS 239174                        /*02WLORG-5     13.8
END
CONTINGENCY 'ATSI_P2-3_OEC-345-006_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 241877 CKT 1          /*02BEAVER     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1646 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P2-3_TE-345-010A_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1          /*02DAV-BE     345.0 - AC2-103 TAP  345.0
 SET POSTCONTRATING 1683 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET POSTCONTRATING 1878 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET POSTCONTRATING 1892 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238654 TO BUS 238563 CKT 1 /*02DAV-BE     345.0 - 02BAY SH     345.0
 SET PRECONTRATING 1542 BRANCH FROM BUS 238654 TO BUS 238889 CKT 1 /*02DAV-BE     345.0 - 02LEMOYN     345.0
 SET PRECONTRATING 1555 BRANCH FROM BUS 238654 TO BUS 239289 CKT 1 /*02DAV-BE     345.0 - 02HAYES      345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-825_SRT-A'
 DISCONNECT BRANCH FROM BUS 241877 TO BUS 238569 CKT 1   /*AC2-103 TAP  345.0 - 02BEAVER     345.0
END
CONTINGENCY 'ATSI_P1-2_OEC-345-824_SRT-A'
 DISCONNECT BRANCH FROM BUS 238654 TO BUS 241877 CKT 1   /*02DAV-BE     345.0 - AC2-103 TAP  345.0
END
CONTINGENCY 'AEP_P4_#6497_05MARYSV 345_J2_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#17564_05BOKESCRK 345_CB2_SRT-A'
 OPEN BRANCH FROM BUS 242939 TO BUS 290984 CKT 1   /*05MARYSV     345.0 - 05BOKESCRK   345.0
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P4_#16659_05GUNN RD SW 345_M2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'AEP_P2-2_#16655_05GUNN RD SW 345_2_SRT-A'
 OPEN BRANCH FROM BUS 243903 TO BUS 290984 CKT 1   /*05GUNN RD SW 345.0 - 05BOKESCRK   345.0
END
CONTINGENCY 'ATSI_P2-3_OEC-345-009_SRT-SL'
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 238570 CKT 2          /*02BEAVER     345.0 - 02BEAVER     138.0
 DISCONNECT BRANCH FROM BUS 238569 TO BUS 239289 CKT 1          /*02BEAVER     345.0 - 02HAYES      345.0
 SET POSTCONTRATING 1499 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET POSTCONTRATING 1720 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1245 BRANCH FROM BUS 241877 TO BUS 238569 CKT 1 /*AC2-103 TAP  345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 238607 TO BUS 238569 CKT 1 /*02CARLIL     345.0 - 02BEAVER     345.0
 SET PRECONTRATING 1370 BRANCH FROM BUS 239725 TO BUS 238569 CKT 2 /*02LAKEAVE    345.0 - 02BEAVER     345.0
END
235117 to 235111 ckt 1
238569 to 238607 ckt 1
238569 to 239725 ckt 1
238569 to 239725 ckt 2
238654 to 241877 ckt 1
239289 to 238569 ckt 1
242935 to 242945 ckt 1
242925 to 235117 ckt 1
241877 to 238569 ckt 1

Winter Peak Analysis

The New Service Request AG2-564 was evaluated as a 49.99 MW (32.9 MW Capacity) injection in the AEP area.

AG2-564 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 49.99 MW (49.99 MW under study).

Note: The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for single or N-1 contingencies and multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Light Load Analysis

The New Service Request AG2-564 was evaluated as a 49.99 MW injection

AG2-564 was evaluated as part of a plant. The total Energy output of the plant was evaluated at its maximum seasonal capability of 49.99 MW (49.99 MW under study).

Note: The capacity portion of Generation Interconnection Requests are evaluated for single or N-1 contingencies. The energy portion, ramped up to a percentage of its full energy output based on season and fuel-specific ramping limits, of Generation Interconnection Requests are evaluated for multiple facility (common mode) contingencies (double circuit tower line, fault with a stuck breaker, and bus fault). For additional details regarding Generator Deliverability, reference PJM Manual 14B, Attachment C, Section C.3.

(No impacts were found for this analysis)

Short Circuit Analysis

Short Circuit analysis is not performed as part of the Phase I System Impact Study. Short Circuit analysis will commence in the Phase II System Impact Study.

Stability Analysis

Stability analysis is not performed as part of the Phase I System Impact Study. Stability analysis will commence in the Phase II System Impact Study.

Reactive Power Analysis

Reactive Power analysis is not performed as part of the Phase I System Impact Study. Reactive Power analysis will commence in the Phase II System Impact Study.

Steady-State Voltage Analysis

Steady State Voltage Analysis is Not Required.

New Service Request Dependencies

The New Service Requests below are listed in one or more dispatch for the overloads identified in this report. These projects contribute to the loading of the overloaded facilities identified in this report. The percent overload of a facility and cost allocation you may have towards a particular reinforcement could vary depending on the action of other projects. The status of each project at the time of the analysis is presented in the table. This list may change as other projects withdraw or modify their requests. This table is valid for load flow analyses only.

New Service Requests Dependencies
Project IDProject NameStatus
AA1-018Powerton-Goodings GroveIn Service
AA1-095Halfway-Marlowe 34.5kVIn Service
AB1-006Meadow Lake 345kVIn Service
AB1-096Carroll-Mt. Airy 34.5kVIn Service
AB1-124Carroll-Monocacy 34.5kVPartially in Service - Under Construction
AB1-125Carroll-Monocacy 34.5kVIn Service
AB1-127St. Thomas-Guilford 34.5kVIn Service
AB1-128St. Thomas-Mercersburg 34.5kVIn Service
AB2-067Kammer-Vassell 765kVIn Service
AB2-093Ormet 138kVIn Service
AB2-170East Lima-Marysville 345kVIn Service
AC1-001Delano 138kVIn Service
AC1-033Kewanee 138 kVIn Service
AC1-044Kammer-Vassell 765kVIn Service
AC1-068Atlanta 69kV IIn Service
AC1-069Atlanta 69kV IIIn Service
AC1-078Beatty-London 138kVIn Service
AC1-085Stuart-Clinton 345kVIn Service
AC1-089Hillsboro-Wildcat 138kVIn Service
AC1-111Aurora 138kVIn Service
AC1-165Atlanta 69kV IIIIn Service
AC1-166Atlanta 69kV IVIn Service
AC1-167Mark Center 69kVUnder Construction
AC1-168Kewanee-StreatorSuspended
AC1-174Losantville 345kVIn Service
AC1-175Losantville 345kVIn Service
AC1-188Rio-Lick 138kVEngineering & Procurement
AC1-194Elk 138kVActive
AC1-214Crescent RidgeIn Service
AC2-015Chatfield-Howard 138kVPartially in Service - Under Construction
AC2-029Circleville 138kVSuspended
AC2-044Maddox Creek 345kVSuspended
AC2-059Biers Run-Circleville 138kVIn Service
AC2-060Buckskin 69kVIn Service
AC2-061Hillsboro-Clinton 138kVIn Service
AC2-067Camden-Crystal I 69kVEngineering & Procurement
AC2-068Camden-Crystal II 69kVEngineering & Procurement
AC2-088S. Bethel-Brown 69kVIn Service
AC2-090Losantville 345kVIn Service
AC2-103Beaver-Davis Besse 345 kV IEngineering & Procurement
AC2-111College Corner 138kVEngineering & Procurement
AC2-136East Hagerstown 12kVUnder Construction
AC2-154Davis Creek 138kVEngineering & Procurement
AC2-168Clinton 23kVIn Service
AC2-176Jay 138 kVIn Service
AC2-195Galion-Roberts South 138 kVUnder Construction
AD1-013Twombly Road 138kVEngineering & Procurement
AD1-060Mercersburg-Milnor 34.5 kVIn Service
AD1-061McConnelsburg-Mercersburg 34 kVIn Service
AD1-100Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVUnder Construction
AD1-101Continental 69 kVIn Service
AD1-106North Waldo-Wild Creek 138 kVSuspended
AD1-119Payne 69 kVIn Service
AD1-128Modoc-Delaware 138 kVPartially in Service - Under Construction
AD1-130Hardin Switch 345 kVIn Service
AD1-136South Bethel-Brown 69 kVIn Service
AD1-140Greene-Clark 138 kVEngineering & Procurement
AD1-155Meadow Brook-Strasburg 138 kVIn Service
AD2-009McConnellsburg 138 kVIn Service
AD2-016Biers Run-Circleville 138 kVIn Service
AD2-020Valley 138 kVEngineering & Procurement
AD2-031Martinsville-Wilmington 69 kVIn Service
AD2-038Powerton-Nevada 345 kVUnder Construction
AD2-047Davis Creek 138 kVSuspended
AD2-060Davis Creek 138kVEngineering & Procurement
AD2-066Mazon-Crescent Ridge 138 kVEngineering & Procurement
AD2-067Centerburg 138kVEngineering & Procurement
AD2-071Strawton-Deer Creek 138 kVSuspended
AD2-079Capitol Ave 34.5kVIn Service
AD2-086Hardin Switch 345 kVIn Service
AD2-091Hardin Tap 345kVSuspended
AD2-092Marysville 345kVUnder Construction
AD2-093Marysville 345kVUnder Construction
AD2-096Marysville 345kVSuspended
AD2-133Eagle Valley 115kVIn Service
AD2-134Shady OaksPartially in Service - Under Construction
AD2-163Broadview-Tangy 138 kVIn Service
AD2-172Lena 138kVIn Service
AD2-180Elk Garden-Parr Run 138kVIn Service
AE1-040Greenfield 69 kVIn Service
AE1-079Maysville-Sharon 69 kVUnder Construction
AE1-090Hardin Switch 345 kVIn Service
AE1-091West Newton-Lynn 138 kVSuspended
AE1-092Blue Jacket-Kirby 138 kVActive
AE1-101McConnellsburg-Texas Eastern 138 kVIn Service
AE1-102Maddox Creek 345 kVSuspended
AE1-109Frenchs Mill 34 kVIn Service
AE1-113Mole Creek 345 kVEngineering & Procurement
AE1-114Maryland-Lancaster 138 kVActive
AE1-146Ebersole #2-Fostoria Central 138 kVUnder Construction
AE1-163Powerton-Nevada 345 kVEngineering & Procurement
AE1-166Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE1-170Kenzie Creek-Colby 138 kVSuspended
AE1-172Loretto-Wilton CenterActive
AE1-183Maysville-McDowell 69 kVEngineering & Procurement
AE1-205McLean 345 kVEngineering & Procurement
AE1-207Mississinewa-Gaston 138 kVSuspended
AE1-208Delaware-Van Buren 138 kVSuspended
AE1-209Desoto 345 kVSuspended
AE1-210Desoto 345 kVSuspended
AE1-227South Cumberland 69 kVSuspended
AE1-237Andover (Maysville) 69kV IUnder Construction
AE1-245Haviland 138 kVUnder Construction
AE2-035Lena 138 kVIn Service
AE2-045Olive-Reynolds 345 kVEngineering & Procurement
AE2-048Muskingum-W. Millersport 345 kVEngineering & Procurement
AE2-054Warfordsburg 34 kVIn Service
AE2-072East Leipsic-Richland 138 kVIn Service
AE2-089Pennville-Adams 138 kVEngineering & Procurement
AE2-113Farmers Valley-Ridgeway 115 kVUnder Construction
AE2-114Midland 23 kV IIn Service
AE2-115Midland 23 kV IIIn Service
AE2-117ABW Tap-Alexandria 46 kVSuspended
AE2-126Dubois-Curwensville 34.5 kVIn Service
AE2-129Philipsburg-Clarence 34.5 kVIn Service
AE2-131Philipsburg-Karthaus 34.5Under Construction
AE2-136Muskingum River-W. Millersport 345 kVEngineering & Procurement
AE2-139East Towanda-Grover 230 kVEngineering & Procurement
AE2-148Beatty-Greene 345 kVIn Service
AE2-152Loretto-Wilton 345 kV & Braidwood-Davis Creek 345 kVEngineering & Procurement
AE2-169Delaware-Van Buren 138 kVSuspended
AE2-172Mississinewa-Gaston 138 kVSuspended
AE2-173McLean 345 kVActive
AE2-176Groton 138 kV SolarIn Service
AE2-181Snyder 69kVUnder Construction
AE2-206East Sidney-Quincy 138 kVIn Service
AE2-214Cole 345 kVEngineering & Procurement
AE2-216Hardin Switch 345 kVEngineering & Procurement
AE2-217East Springfield-London 138 kVEngineering & Procurement
AE2-219Bluff Point-Randolph 138 kVSuspended
AE2-220Losantville 345 kVEngineering & Procurement
AE2-221Clinton-Stuart 345 kVUnder Construction
AE2-223McLean 345 kVActive
AE2-224Bear Rock-Johnstown 230 kVIn Service
AE2-226Millville-Old Chapel 138 kVEngineering & Procurement
AE2-230Bartonsville-Meadow Brook 138 kVIn Service
AE2-234Liberty Center-Buckeye Tap 69 kVEngineering & Procurement
AE2-236Columbia-Northeast 138 kVSuspended
AE2-255Molecreek 345 kVEngineering & Procurement
AE2-262Moshannon-Milesburg 230 kVEngineering & Procurement
AE2-263Moshannon-Milesburg 230 kV IIEngineering & Procurement
AE2-267Woodsdale 345 kVEngineering & Procurement
AE2-281Powerton-Nevada 345 kVEngineering & Procurement
AE2-282East Fayette 138 kVIn Service
AE2-285Maysville 69 kVEngineering & Procurement
AE2-297Madison-Tanners Creek 138 kVIn Service
AE2-298Cavett Switch - West Van Wert 69 kVEngineering & Procurement
AE2-305Givens-Mechanicsburg 138 kVEngineering & Procurement
AE2-306Gunn Road 345 kVUnder Construction
AE2-309Carlos Junction-Lonaconing 34.5 kVIn Service
AE2-315Yankee Tap 69 kVIn Service
AE2-318Ford-Cedarville 138 kVSuspended
AE2-321Belvidere-Marengo 138 kVActive
AE2-322Mark Center 69 kVUnder Construction
AE2-323Twin Branch-Guardian 138 kVUnder Construction
AE2-325Valley 138 kVActive
AE2-341Sandwich-Plano 138 kVActive
AE2-342Woodstock 69 kVEngineering & Procurement
AE2-343Andover (Maysville) 69 kV IIUnder Construction
AF1-006Fairview East 34.5 kVIn Service
AF1-030Sandwich-Plano 138 kVActive
AF1-045Cedarville-Ford 138 kVSuspended
AF1-053Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-054Givens-Mechanicsburg 138 kVEngineering & Procurement
AF1-062Jug Street 138 kVEngineering & Procurement
AF1-064Weston 69 kVUnder Construction
AF1-078East Sidney-Quincy 138 kVIn Service
AF1-084Hartford-Almena 69 kVEngineering & Procurement
AF1-086Madera-Westover South 115 kVUnder Construction
AF1-091Varner - Sowers 138 kVEngineering & Procurement
AF1-092Huntington Jct. 138 kVSuspended
AF1-093Henderson-Stoneboro 69 kVEngineering & Procurement
AF1-094Union City-Cambridge Springs 34.5 kVEngineering & Procurement
AF1-098Four Mile Jct-Corry East 115 kVEngineering & Procurement
AF1-118Sorenson-Desoto 345 kVEngineering & Procurement
AF1-119Keystone-Desoto 345 kVEngineering & Procurement
AF1-120East Fayette 2 138 kVIn Service
AF1-122Cardington-Liberty 69 kVSuspended
AF1-134Philipsburg-Madera 34.5 kVEngineering & Procurement
AF1-136Warfordsburg-Purcell Junction 34.5 kVEngineering & Procurement
AF1-140Claysburg 23 kVEngineering & Procurement
AF1-153Motion-Ridgeway 46 kVSuspended
AF1-158Edison-Gravel Pit 138 kVIn Service
AF1-176Corey 138 kVActive
AF1-202Keystone-Desoto 345 kVUnder Construction
AF1-205Napoleon Muni 138 kVSuspended
AF1-206East Fayette 138 kVEngineering & Procurement
AF1-207Reynolds-Olive #1 345 kVEngineering & Procurement
AF1-215Olive-Reynolds 345 kVIn Service
AF1-223Keystone-Desoto 345 kVUnder Construction
AF1-227Marysville – Gunn Road 345 kVIn Service
AF1-228Beatty-Greene 345 kVEngineering & Procurement
AF1-229Galion-South Berwick 345 kVEngineering & Procurement
AF1-249Nickel 12.47 kVIn Service
AF1-254Milnor-Huyetts 34.5 kVUnder Construction
AF1-268Desoto-Jay 138 kVEngineering & Procurement
AF1-272Lucerne 115 kVEngineering & Procurement
AF1-282Stuart-Clinton 345 kVEngineering & Procurement
AF1-283Stuart-Clinton 345 kVEngineering & Procurement
AF1-285Gunn Road 345 kVUnder Construction
AF1-290Feagans Mill-Millville 138 kVIn Service
AF1-291ABartonsville-Meadow Brook 138 kVIn Service
AF1-296Garden Plain 138 kVActive
AF1-302Brookville-Squab Hollow 138 kVEngineering & Procurement
AF1-322Meadow Lake 345 kVEngineering & Procurement
AF1-331Twombley RoadEngineering & Procurement
AF2-004Beaver 345 kVEngineering & Procurement
AF2-005Beaver 138 kVEngineering & Procurement
AF2-014Maddox Creek 345 kVEngineering & Procurement
AF2-039Shawville-Clearfield 34.5 kVEngineering & Procurement
AF2-041Nelson-Electric Junction 345 kVActive
AF2-068Jay 138 kVActive
AF2-069Crescent Ridge 138 kVActive
AF2-075Bartonsville-Meadow Brook 138 kV IIIIn Service
AF2-078Reynolds-Olive #1 345 kVEngineering & Procurement
AF2-083Kenzie Creek-Stone Lake 69 kVUnder Construction
AF2-088Shawville-Clearfield 34.5 kV IIEngineering & Procurement
AF2-095Davis Creek 138 kVActive
AF2-103Haviland 138 kVIn Service
AF2-111North Clark-Spurlock 345 kVActive
AF2-122Kirk 138 kVUnder Construction
AF2-126Weston 69 kV IIActive
AF2-130Cobalt Corners 34.5 kVIn Service
AF2-132Reynolds-Olive #1 345 kVUnder Construction
AF2-133Reynolds-Olive #2 345 kVUnder Construction
AF2-134Olive-Reynolds #2 345 kVIn Service
AF2-142Nevada 345 kVActive
AF2-143Powerton-Nevada 345 kVActive
AF2-150Galion 138 kVUnder Construction
AF2-173Desoto 345 kVActive
AF2-177Sorenson-DeSoto #2 345 kVActive
AF2-199Nelson-Electric Junction 345 kVActive
AF2-200Nelson-Electric Junction 345 kVActive
AF2-205Olive-Reynolds #2 345 kVEngineering & Procurement
AF2-224Allen 345 kVEngineering & Procurement
AF2-225McLean 345 kVActive
AF2-235Titusville-Oil Creek 34.5 kVWithdrawn
AF2-238Mansfield-South Troy 34.5 kVEngineering & Procurement
AF2-252Blue Mound 345 kVEngineering & Procurement
AF2-291Sporn South-Leon 138 kVEngineering & Procurement
AF2-298Crown-New Lebanon 69 kVEngineering & Procurement
AF2-335Delaware-Royerton 138 kVActive
AF2-350Kensington 138 kVActive
AF2-352Blue Mound 345 kVEngineering & Procurement
AF2-356Albright-Mt. Zion 138 kVUnder Construction
AF2-359Olive-University Park 345 kVEngineering & Procurement
AF2-375Ebersole-Fostoria 138 kVEngineering & Procurement
AF2-388Keystone-Desoto 345 kVActive
AF2-389Kenzie Creek-Stone Lake 69 kVWithdrawn
AF2-392Nelson-Dixon 138 kVActive
AF2-396Stinger 138 kVActive
AG1-024Centerburg 138 kVEngineering & Procurement
AG1-034Centerburg 138 kVEngineering & Procurement
AG1-039Galion 138 kV IIUnder Construction
AG1-040Morgan Street-Mount Hope 34.5 kVEngineering & Procurement
AG1-047Jay 138 kVEngineering & Procurement
AG1-054Potter-Harlan 69 kVEngineering & Procurement
AG1-100Venango-Saegertown 34.5 kVEngineering & Procurement
AG1-107Hillsboro-Middleboro 138 kVEngineering & Procurement
AG1-118Sugar Grove-Waterman 138kVActive
AG1-125Marysville-Flatlick 765 kVEngineering & Procurement
AG1-126Marysville-Flatlick 765 kVEngineering & Procurement
AG1-127Crego Rd 138 kVActive
AG1-193Utica Junction 34.5 kVSuspended
AG1-197Morgan Street-Cochranton 34.5 kVSuspended
AG1-198Union City 34.5 kVUnder Construction
AG1-226Dequine-Eugene 345 kVActive
AG1-232Magley 138 kVEngineering & Procurement
AG1-237Dequine-Eugene 345 kVEngineering & Procurement
AG1-281Claysburg-HCR Tap 46 kVEngineering & Procurement
AG1-301Miller REC-Warrior Ridge 46 kVEngineering & Procurement
AG1-302Olive-Reynolds #1 345 kVUnder Construction
AG1-323Blue Jacket 138 kVActive
AG1-324Jay-Desoto 138 kVEngineering & Procurement
AG1-349Olive-Reynolds #2 345 kVEngineering & Procurement
AG1-363Black Oak-Hatfield 500 kVEngineering & Procurement
AG1-365Allen 345 kVEngineering & Procurement
AG1-366Allen 345 kVEngineering & Procurement
AG1-367DeSoto 345 kVActive
AG1-368Tillman 138 kVEngineering & Procurement
AG1-369Logtown 138 kVEngineering & Procurement
AG1-374Blue Mound 345 kVActive
AG1-375Sorenson-Desoto 345 kVActive
AG1-386Smith-Francis Junction 25 kVIn Service
AG1-410Maddox Creek-RP Mone 345 kVActive
AG1-411Maddox Creek-RP Mone 345 kVActive
AG1-433Keystone-DeSoto 345 kVActive
AG1-436Olive-University Park 345 kVActive
AG1-447Olive-University Park 345 kVActive
AG1-462Cordova 345 kVActive
AG1-478Wilmington 34.5 kVEngineering & Procurement
AG1-500Beaver 345 kVEngineering & Procurement
AG1-501Beaver 138 kVEngineering & Procurement
AG1-554South Kenton 138 kVEngineering & Procurement
AG1-555Dequine 345 kVEngineering & Procurement
AG2-029Forest G. Hipple-Collingwood 345 kVActive
AG2-057Cardington-Liberty 69 kV IIActive
AG2-063North Hampton 69 kVActive
AG2-085Delaware-Royerton 138 kVActive
AG2-104Marysville-Flatlick 765 kVActive
AG2-106Marysville-Flatlick 765 kVActive
AG2-107Marysville-Flatlick 765 kVActive
AG2-109Fitchville-New London 69 kVActive
AG2-114Dresden-Pontiac Midpoint 345 kVActive
AG2-119Galion-Roberts South 138 kV IIActive
AG2-125Camden-Crystal 69 kVActive
AG2-149Galion-South Berwick 345 kVActive
AG2-162Jefferson-Greentown 765 kVActive
AG2-163Dequine-Eugene 345 kVActive
AG2-164Jefferson-Greentown 765 kVActive
AG2-165Dumont-Greentown 765 kVActive
AG2-191Mississinewa 138 kVActive
AG2-192Mississinewa 138 kVActive
AG2-212Dumont-Greentown 765 kVActive
AG2-216East Sidney-Quincy 138 kVActive
AG2-219Jefferson-Greentown 765 kVActive
AG2-230Dumont 345 kVActive
AG2-245Olive - Reynolds #1 345 kVActive
AG2-328Dumont - Greentown 765 kVActive
AG2-329S Berwick - Galion 345 kVActive
AG2-330Dumont - Greentown 765 kVActive
AG2-331Jefferson-Greentown 765 kVActive
AG2-363Powerton 345 kVActive
AG2-364Powerton 345 kVActive
AG2-378North Hampton – Medway 69 kVActive
AG2-385North Hampton 69 kVActive
AG2-400Allen 345 kVActive
AG2-401Losantville 345 kVActive
AG2-405Continental 69 kVActive
AG2-406Payne 69 kVActive
AG2-408Allen 345 kVActive
AG2-444Bixby - Biers Run 345 kVActive
AG2-449Jefferson-Greentown 765 kVActive
AG2-453Lasalle - Plano 345 kVActive
AG2-487Madison - Tanners Creek 138 kVActive
AG2-491Meadow Lake 345 kVActive
AG2-515Midway 345 kV IIIActive
AG2-516Pecatonica 138kVActive
AG2-519Royerton - Desoto 138 kVActive
AG2-524LaSalle Station - Mazon 138 kVActive
AG2-548Corwin - Elk 138 kVActive
AG2-550Bluff Point - Randolph 138 kVActive
AG2-551Bluff Point - Randolph 138 kVActive
AG2-575Crego Rd. 138 kVActive
AG2-585Kensington 138kVActive
AG2-637Randolph - Hodgin 138 kVActive
AG2-660Nelson-Electric Junction 345 kVActive
AG2-665Corwin - Elk 138 kVActive
AH1-044Nelson - Electric Junction 345 kVActive
AH1-047Marengo - Belvidere 138 kVActive
AH1-055Kyger Creek - Don Marquis 345 kVActive
AH1-059Sharp Road 69 kVActive
AH1-060Cardington-Liberty 69 kV IIIActive
AH1-069Jerome – Mohicanville 69 kVActive
AH1-070Jerome – Mohicanville 69 kVActive
AH1-075North Waldo - Wild Creek 138 kVActive
AH1-146White Rock - Wayne 345 kVActive
AH1-147White Rock - Wayne 345 kVActive
AH1-150Nelson-Electric Junction 345 kVActive
AH1-151Nelson-Electric Junction 345 kVActive
AH1-153Dumont 345 kVActive
AH1-196Prairie 345 kVActive
AH1-234Wempletown - Paddock 345 kVActive
AH1-272Argenta - Twin Branch 345 kVActive
AH1-282Galion - Ohio Central 345 kVActive
AH1-285Sandwich 138 kVActive
AH1-302Olive - Reynolds 345 kVActive
AH1-304Delaware-Van Buren 138 kVActive
AH1-305Olive - Reynolds 345 kVActive
AH1-306Mississinewa-Gaston 138 kVActive
AH1-308Pennville - Adams 138 kVActive
AH1-309Kenzie Creek-Colby 138 kVActive
AH1-327Hardin Switch 345 kVActive
AH1-328Blue Jacket - Kirby 138 kVActive
AH1-337Randolph - Hodgin 138 kVActive
AH1-338McGirr Rd - Ritchie Road 138kVActive
AH1-339West Crawford 69 kVActive
AH1-341Stillman - Dixon 138KVActive
AH1-391Olive 138 kVActive
AH1-392Gravel Pit-Kankakee 138 kVActive
AH1-482Olive - Reynolds #2 345 kVActive
AH1-537Pierce - Kyger Creek 345 kVActive
AH1-539South Kenton 138 kVActive
AH1-542Crissinger-Kirby 138kVActive
AH1-543Mulberry – Tazewell 345 kVActive
AH1-567University Park 138 kVActive
AH1-577Clutch 69 kVActive
AH1-578Clutch 69 kVActive
AH1-661Cannelville 12.47 kVActive
AH1-669Circleville-Biers Run 138 kVActive
AH1-690Bay Shore - Lallendorf 345 kVActive
AH1-698Braidwood 345 kVActive
AH1-702Byron 345 kVActive
AH1-704Hannibal 138 kVActive
AH1-711Lemoyne 345 kVActive
AH1-714Lasalle 345 kVActive
AH1-718Nelson 345 kVActive
AH1-719Beverly 345 kVActive
AH1-735Richland 138 kVActive
U2-030Four Mile Ridge Wind 138kVIn Service
U2-072East Lima-Marysville 345kVIn Service
U2-073Frostburg 138kV IIIn Service
V1-011Haviland 138kVIn Service
V3-007Desoto-Tanners Creek #1 345kVIn Service
W1-056Ada-Dunkirk 69kVIn Service
X1-042WatervlietIn Service
X3-005Wildwood 12kVIn Service
Y3-023Country Side 12kVIn Service
Y3-024Bluff Point 12kVIn Service
Z2-087Pontiac MidPoint-Brokaw 345kVIn Service
Z2-115Deer Creek 12.47kVIn Service
Z2-116Twin Branch 12.47kVIn Service

Affected System - PJM Identified Violations

As part of PJM's analysis, PJM evaluated the potential impacts on tie line facilities between PJM and an affected system entity, which were identified per PJM planning analysis criteria. This upgrade may be required on the affected system portion of the tie line along with cost allocation of such upgrade if applicable, in coordination with the affected system. Depending on the affected system, this project may not be contingent on upgrade based on PJM planning analysis criteria, but may be contingent on this upgrade based on the Affected System Operator's planning criteria, provided in the Affected Systems Study Section, herein.

Midcontinent Independent System Operator, Inc. (MISO)No Impact
New York Independent System Operator (NYISO)No Impact
Tennessee Valley Authority (TVA)No Impact
Louisville Gas & Electric (LG&E)No Impact
Duke Energy Carolinas (DUKE)No Impact
Duke Energy Progress – East (CPLE)No Impact
Duke Energy Progress – West (CPLW)No Impact

Affected System - Non-PJM Identified Violations

In Phase I of the Cycle, PJM conducts an Affected System screen to identify any New Service Request with potential Affected System impacts. PJM initiates coordination with each Affected System Operator by providing a list of New Service Requests in the Cycle with potential impacts to their respective system. If the Affected System Operator indicates an Affected System Study is required, PJM will notify the Project Developer or Eligible Customer of the need for an Affected System Study. See below if any Affected System Operator requires a study for this project:

Midcontinent Independent System Operator, Inc. (MISO)Not required
New York Independent System Operator (NYISO)Not required
Tennessee Valley Authority (TVA)Not required
Louisville Gas & Electric (LG&E)Not required
Duke Energy Carolinas (DUKE)Not required
Duke Energy Progress – East (CPLE)Not required
Duke Energy Progress – West (CPLW)Not required

System Reinforcements

No cost allocated system reinforcements were identified for this project in the Phase I System Impact Study load flow analysis.

Shown below are the details of the cost allocated, contingent, eliminated, topology and potential aggregate contributor reinforcements for this project. Please refer to the System Reinforcement table above and the information below for more detail.


System Reinforcement: b4000.1
Type
Load Flow
TO
AEP
RTEP ID / TO ID
b4000.1
Title
Add two 765 kV breakers at Amos Substation to expand the breaker and a half scheme to accommodate the new Amos-Welton Spring 765 kV line (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.2
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.2
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - AEP Section of the line is 30 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.3
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.3
Title
Construct a new 175 miles Amos to Welton Spring 765 kV line - APS/FE Section of the line is 145 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.4
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.4
Title
Construct a new 765 kV switchyard - Welton Spring (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.5
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.5
Title
Install four 250 MVAR shunt capacitors, and a +/-500 MVAR STATCOM at Welton Spring 765 kV substation
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.7
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.7
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line - in DVP local area/Millville to Lovettsville section, roughly 10.5 miles (Projected ISD 6/1/2029)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.8
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.8
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (DVP local area to Rocky Point, roughly 4.8 miles)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.9
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.9
Title
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard (Projected ISD 6/1/2029)
Description
Construct a new substation called Rocky Point with a 765 kV and a 500 kV yard. Loop in the Doubs-Goose Creek 500 kV line, the Doubs-Aspen 500 kV line, and the Woodside-Goose Creek 500 kV line. Install two 765/500 kV transformer at Rocky Point substation. 765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.11
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.11
Title
Expand Black Oak Substation & Loop in the 502 Jct-Woodside 500 kV line (Projected ISD 6/1/2029)
Description
Expand Black Oak Substation to accommodate the connection of the 502 Jct-Woodside 500 kV line and loop the 502 Jct-Woodside 500 kV line into the Black Oak substation by constructing ~0.85 miles of new 500 kV line into and out of Black Oak 500 kV substation
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)

System Reinforcement: b4000.10
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.10
Title
Install four 250 MVAR cap banks (two on 765 and two on 500 kV side) and a +/-500 MVAR STATCOM on the 765 kV Rocky Point yard
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.a
Title
Upgrade D120 and D125 disconnect switches at Beaver substation
Description
Upgrade D120 and D125 disconnect switches at Beaver substation
Total Cost ($USD)
$929,516
Allocated Cost ($USD)
$0
Time Estimate
22 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.b
Title
Upgrade (1) 3000 SAC 169 line drop at Beaver
Description
Upgrade (1) 3000 SAC 169 line drop at Beaver
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.c
Title
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV
Description
Reconductor (possible rebuild) 18.22 miles of 954 ACSR 48/7 transmission line and (3) line drops at Beaver on the Beaver - Carlisle Ckt 1 345 kV using dual (2) 795 26/7 "Drake ACSS
Total Cost ($USD)
$109,211,408
Allocated Cost ($USD)
$0
Time Estimate
63 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-004.d
Title
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Description
Upgrade (1) 3500 SAC 127 D120-to-B121 breaker lead at Beaver
Total Cost ($USD)
$265,209
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02CARLIL 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.a
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and line drops ( line drops at Hayes) on the Beaver - Hayes Ckt 1 345 kV line using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$175,902,477
Allocated Cost ($USD)
$0
Time Estimate
90 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.b
Title
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Description
Upgrade 3500 SAC (2) B3 and (2) B6 breaker leads at Hayes
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.c
Title
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Description
Upgrade (2) L3000 wavetraps at Beaver and Hayes
Total Cost ($USD)
$729,124
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.d
Title
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Description
Upgrade (4) circuit breakers at Beaver and Hayes (B88, B115, B3, B6)
Total Cost ($USD)
$7,937,520
Allocated Cost ($USD)
$0
Time Estimate
60 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.e
Title
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Description
Upgrade the 1590 AAC (2) B88 and (2) B15 breaker leads at Beaver
Total Cost ($USD)
$152,573
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.f
Title
Upgrade the B6 CT at Hayes
Description
Upgrade the B6 CT at Hayes
Total Cost ($USD)
$727,300
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.g
Title
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3)
Description
Upgrade (3) 1590 AAC line drops at Beaver (line drop to WT, Phase 1&3 "B-B", and SHARED NODE TO: WT, PH 2 / 5" AL, PH 1&3) using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$591,863
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.h
Title
Upgrade the B88 and B115 CTs at Beaver
Description
Upgrade the B88 and B115 CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.i
Title
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Description
Upgrade the 10A B115 relay and B88 meter thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.j
Title
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Description
Upgrade the B88 and B3 impedance relays at Beaver and Hayes
Total Cost ($USD)
$1,019,790
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-014.k
Title
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Description
Upgrade (9) 3000A disconnect switches at Beaver and Hayes (D:74,92,93,116,4,5,7,8,11)
Total Cost ($USD)
$3,774,791
Allocated Cost ($USD)
$0
Time Estimate
29 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02HAYES 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.a
Title
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Description
Upgrade (3) disconnect switches at Beaver (D:120,166,165)
Total Cost ($USD)
$1,350,788
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.b
Title
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Description
Upgrade (4) 954 ACSR 45/7 overhead line and line drops at Beaver Substation
Total Cost ($USD)
$809,465
Allocated Cost ($USD)
$0
Time Estimate
15 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005c
Title
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Description
Upgrade 3500 SAC 127 B161 (2) breaker leads and (1) B121-to-D120 breaker lead at Beaver
Total Cost ($USD)
$191,109
Allocated Cost ($USD)
$0
Time Estimate
11 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-005.d
Title
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV
Description
Reconductor (possible rebuild) 8.37 miles of 954 ACSR 48/7 transmission line on the Beaver - Lake Avenue Ckt 1 345 kV using dual (2) 954 54/7 "Cardinal" ACSS
Total Cost ($USD)
$50,053,445
Allocated Cost ($USD)
$0
Time Estimate
38 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 1 line(Any)

System Reinforcement: n9227.0
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
n9227.0 / TC1-ATSI-001.b
Title
Upgrade T-line drops, overhead substation conductor and TL reconductor
Description
Reconductor (possible rebuild) of 8.12 miles of dual transmission line and (2) single conductor line drops at Beaver on the Beaver-Lake Ave Ckt 2 345 kV line using triple (3) 1113 54/19 ""Finch"" ACSS"
Total Cost ($USD)
$48,873,856
Allocated Cost ($USD)
$0
Time Estimate
37 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.a
Title
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Description
Upgrade (4) circuit breakers at Beaver and Lake Ave (B:3,4,216,219)
Total Cost ($USD)
$7,786,809
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.b
Title
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Description
Upgrade 1590 AAC B3, B4, B216 and B219 breaker leads at Beaver and Lake Ave
Total Cost ($USD)
$305,540
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.c
Title
Upgrade the (3) B216, B219 and B4 1500 CTs
Description
Upgrade the (3) B216, B219 and B4 1500 CTs
Total Cost ($USD)
$853,850
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.d
Title
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Description
Upgrade (3) 1590 line drops at Beaver and Lake Ave
Total Cost ($USD)
$690,685
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.e
Title
Upgrade the (1) B219 1200 CT to PVD at Beaver
Description
Upgrade the (1) B219 1200 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$0
Time Estimate
16 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.f
Title
Upgrade the (1) B216 relay thermal at Beaver
Description
Upgrade the (1) B216 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.g
Title
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Description
Upgrade (1) 4.00 SPS.AL PIPE at Beaver
Total Cost ($USD)
$178,089
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.h
Title
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Description
Upgrade (9) disconnect switches at Beaver and Lake Ave (D: 19,20,21,22, 212,215,217,218,220)
Total Cost ($USD)
$3,850,794
Allocated Cost ($USD)
$0
Time Estimate
39 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.i
Title
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B3 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.j
Title
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (2) 2.50 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$173,391
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.k
Title
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Description
Upgrade the (15) B216, B219, B3 and B4 2000 CTs at Beaver and Lake Ave
Total Cost ($USD)
$2,701,212
Allocated Cost ($USD)
$0
Time Estimate
17 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.l
Title
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Description
Upgrade the (2) B216 SEL411L impedance relays at Lake Ave
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-021.m
Title
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Description
Upgrade (8) 5.00 SPS.AL PIPE SCCIR at Beaver
Total Cost ($USD)
$250,039
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-02LAKEAVE 345.0 kV Ckt 2 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.a
Title
Upgrade B185 and B182 circuit breakers at Beaver
Description
Upgrade B185 and B182 circuit breakers at Beaver
Total Cost ($USD)
$3,893,404
Allocated Cost ($USD)
$0
Time Estimate
56 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.b
Title
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Description
Upgrade (4) disconnect switches at Beaver (D186,184,181,183)
Total Cost ($USD)
$1,699,640
Allocated Cost ($USD)
$0
Time Estimate
25 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.c
Title
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Description
Upgrade 3000 AAC B185 and B185 breaker leads at Beaver
Total Cost ($USD)
$187,449
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.d
Title
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line
Description
Reconductor (possible rebuild) 29.61 miles of transmission line and (4) line drops beginning at Beaver towards Davis Besse on the Beaver - Davis Besse Ckt 1 345 kV line using dual (2) 1590 54/19 "Falcon" ACSS
Total Cost ($USD)
$149,403,319
Allocated Cost ($USD)
$0
Time Estimate
82 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.e
Title
Upgrade (2) L3000 wavetraps at Beaver
Description
Upgrade (2) L3000 wavetraps at Beaver
Total Cost ($USD)
$620,600
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.f
Title
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Description
Upgrade (2) B182 impedance relays at Beaver (SEL-321: Z2-BU & Z2-PR)
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.g
Title
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Description
Upgrade (2) B185 and B182 revenue meter CTs at Beaver
Total Cost ($USD)
$1,258,596
Allocated Cost ($USD)
$0
Time Estimate
21 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.h
Title
Upgrade the B185 CT to PVD at Beaver
Description
Upgrade the B185 CT to PVD at Beaver
Total Cost ($USD)
$349,952
Allocated Cost ($USD)
$0
Time Estimate
17 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-020.i
Title
Upgrade B182 relay thermal at Beaver
Description
Upgrade B182 relay thermal at Beaver
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
19 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02BEAVER-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.a
Title
Upgrade D41 and D42 disconnect switches at Davis Besse
Description
Upgrade D41 and D42 disconnect switches at Davis Besse
Total Cost ($USD)
$967,716
Allocated Cost ($USD)
$0
Time Estimate
36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.b
Title
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Description
Upgrade (1) 1024 ACAR 6E550-52-1 "A" line drop at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.c
Title
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line
Description
Reconductor (possible rebuild) 15.6 miles of 954 ACSR 45/7 on the Davis Besse - AC2-103 Tap 345 kV line using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$91,775,258
Allocated Cost ($USD)
$0
Time Estimate
57 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.d
Title
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Description
Upgrade (2) 3500 SAC 127 line drops at Davis Besse
Total Cost ($USD)
$263,169
Allocated Cost ($USD)
$0
Time Estimate
12 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.e
Title
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Description
Upgrade 3500 SAC B65 breaker leads and subconductor (D42 to wave trap) at Davis Besse
Total Cost ($USD)
$197,592
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.f
Title
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV
Description
Reconductor (possible rebuild) 18.7 miles of 954 ACSR 48/7 on the Davis Besse - AC2-103 TAP 345kV using dual (2) 1272 54/19 "Pheasant" ACSS
Total Cost ($USD)
$111,822,087
Allocated Cost ($USD)
$0
Time Estimate
64 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.g
Title
Upgrade (2) Wave Traps at Davis Besse
Description
Upgrade (2) Wave Traps at Davis Besse
Total Cost ($USD)
$620,599
Allocated Cost ($USD)
$0
Time Estimate
20 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.i
Title
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Description
Upgrade (4) 1590 ACSR 45/7 sub conductors at Davis Besse
Total Cost ($USD)
$756,208
Allocated Cost ($USD)
$0
Time Estimate
13 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.j
Title
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 13.03 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.k
Title
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Description
Upgrade (2) 6.65 Ohm B65 Impedance Relays at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.l
Title
Upgrade Circuit Breaker B65 at Davis Besse
Description
Upgrade Circuit Breaker B65 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.m
Title
Upgrade (2) B65 Meter Thermals at Davis Besse
Description
Upgrade (2) B65 Meter Thermals at Davis Besse
Total Cost ($USD)
$509,895
Allocated Cost ($USD)
$0
Time Estimate
18 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
ATSI
RTEP ID / TO ID
(Pending) / TC2-ATSI-008.h
Title
Upgrade Circuit Breaker 34564 at Davis Besse
Description
Upgrade Circuit Breaker 34564 at Davis Besse
Total Cost ($USD)
$2,068,856
Allocated Cost ($USD)
$0
Time Estimate
54 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
02DAV-BE-AC2-103 TAP 345.0 kV Ckt 1 line(Any)

System Reinforcement
Type
Load Flow
TO
AEP
RTEP ID / TO ID
(Pending) / AEP-TC2-18681
Title
05E LIMA 345.0 kV to 05SW LIM 345.0 kV ckt 1 - Rebuild
Description
AEP owned line, ~14.66 miles (total 21.97 miles) of 345kV single circuit needs to be rebuilt. Existing conductor is 1-1414 ACSR/PE 62/19 & 1-1708.8 ACSR/AE 66/19
Total Cost ($USD)
$58,640,000
Allocated Cost ($USD)
$0
Time Estimate
24 to 36 Months

Potential Aggregate Contributor

Note: Based on PJM cost allocation criteria, AG2-564 currently does not receive cost allocation towards this upgrade. As changes to the PJM process occur (such as other projects withdrawing from the cycle or reducing in size) AG2-564 could receive cost allocation. Although AG2-564 may not presently have cost responsibility for this upgrade, AG2-564 is a potential Aggregate Pool Contributor.

FacilityContingency
05E LIMA-05SW LIM 345.0 kV Ckt 1 line(Any)

System Reinforcement: b4000.6
Type
Load Flow
TO
APS
RTEP ID / TO ID
b4000.6
Title
Construct a new 86 miles Welton Spring to Rocky Point 765 kV line (Welton Spring to DVP local area, roughly 21 miles) (VA Portion)
Description
765kV Solution: 2024 W1 Solution - Regional Cluster Ties Doubs 500kV area to John Amos 765kV via a new 765kV line
Cost Information
Time Estimate
Jun 01 2029

Not Contingent

Note: AG2-564 contributes to the loading of an overloaded facility that is being mitigated by a planned baseline upgrade. AG2-564 is not contingent on this baseline upgrade as it does not meet the criteria for being a contingent facility or for having cost allocation for the upgrade.

FacilityContingency
01KAMMER-05KAMMER 500.0/765.0 kV Ckt 1 transformer(Any)
01 502 J-01KAMMER 500.0 kV Ckt 1 line(Any)

Attachments

AG2-564 One Line Diagram

AG2-564 One Line Diagram.jpg
The state in which the generator or merchant transmission facility is located.
The Transmission Owner of the facility where the New Service Request project interconnects to the transmission system.
Winter load flow analysis will be performed starting in Transition Cycle 2.